Table of Contents

Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:58

Tabular Output Report in Format: HTML

Building: HotelLarge

Environment: RUNPERIOD 1 ** Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745

Simulation Timestamp: 2023-10-16 08:58:43


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2023-10-16 08:58:43

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [GJ] Energy Per Total Building Area [MJ/m2] Energy Per Conditioned Building Area [MJ/m2]
Total Site Energy 15430.47 1360.08 1360.08
Net Site Energy 15430.47 1360.08 1360.08
Total Source Energy 37637.90 3317.49 3317.49
Net Source Energy 37637.90 3317.49 3317.49


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 1.200
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil No 1 1.050
Fuel Oil No 2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [m2]
Total Building Area 11345.29
Net Conditioned Building Area 11345.29
Unconditioned Building Area 0.00


End Uses

Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating 0.00 847.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 3046.80 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 1174.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 262.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 1751.30 1788.84 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 679.68 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 2057.84 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 311.71 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 590.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 90.78 2755.03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 9857.19
Refrigeration 74.19 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 10039.01 5391.46 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 9857.19
Note: Natural gas appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler 0.00 847.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 3046.80 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 1174.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 262.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 959.56 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Cooking 762.04 1198.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ReachInFreezer 16.27 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ReachInRefrigerator 13.43 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Laundry 0.00 590.20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Transformer 32.92 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLift 616.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLightsFan 30.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  General 2057.84 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 311.71 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 590.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Water Heater 90.78 2755.03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 5742.51
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 4114.69
Refrigeration General 18.27 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  LowTempRefrigeration 22.43 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  MedTempRefrigeration 33.49 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Space Type

Space Type Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating Unassigned 0.00 847.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling Unassigned 3046.80 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting GENERAL 1174.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Unassigned 262.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment GENERAL 1751.30 1788.84 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Unassigned 679.68 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Unassigned 2057.84 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps Unassigned 311.71 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery Unassigned 590.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Unassigned 90.78 2755.03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 9857.19
Refrigeration Unassigned 74.19 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 126.63 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 485.41 317.54 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.87
Other 272.82 157.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 884.86 475.22 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.87


Utility Use Per Total Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 126.63 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 485.41 317.54 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.87
Other 272.82 157.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 884.86 475.22 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.87


Electric Loads Satisfied

Electricity [GJ] Percent Electricity [%]
Fuel-Fired Power Generation 0.000 0.00
High Temperature Geothermal* 0.000 0.00
Photovoltaic Power 0.000 0.00
Wind Power 0.000 0.00
Power Conversion 0.000 0.00
Net Decrease in On-Site Storage 0.000 0.00
Total On-Site Electric Sources 0.000 0.00
     
Electricity Coming From Utility 10039.012 100.00
Surplus Electricity Going To Utility 0.000 0.00
Net Electricity From Utility 10039.012 100.00
     
Total On-Site and Utility Electric Sources 10039.012 100.00
Total Electricity End Uses 10039.012 100.00


On-Site Thermal Sources

Heat [GJ] Percent Heat [%]
Water-Side Heat Recovery 0.00 0.00
Air to Air Heat Recovery for Cooling 2393.25 69.80
Air to Air Heat Recovery for Heating 1035.41 30.20
High-Temperature Geothermal* 0.00 0.00
Solar Water Thermal 0.00 0.00
Solar Air Thermal 0.00 0.00
Total On-Site Thermal Sources 3428.65 100.00


Water Source Summary

Water [m3] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 9857.19 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 9857.19 100.00
Total Water End Uses 9857.19 100.00


Setpoint Not Met Criteria

Degrees [deltaC]
Tolerance for Zone Heating Setpoint Not Met Time 0.56
Tolerance for Zone Cooling Setpoint Not Met Time 0.56


Comfort and Setpoint Not Met Summary

Facility [Hours]
Time Setpoint Not Met During Occupied Heating 0.00
Time Setpoint Not Met During Occupied Cooling 26.17
Time Not Comfortable Based on Simple ASHRAE 55-2004 6325.83


Note 1: An asterisk (*) indicates that the feature is not yet implemented.

Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Adaptive Comfort Summary
Initialization Summary
Annual Heat Emissions Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
Coil Sizing Details
System Summary
Outdoor Air Summary
Outdoor Air Details
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary
Annual Thermal Resilience Summary
Annual CO2 Resilience Summary
Annual Visual Resilience Summary

NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODENAME IECC

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2012

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

| Environment |

NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE

| Environment |

NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 2B

| Environment |

NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_AZ_TUCSON

| Environment |

ZoneCoolingSummaryMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

ZoneHeatingSummaryMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

ZoneElectricSummaryMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

SpaceGainsMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

PeakSpaceGainsMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

SpaceGainComponentsAtCoolingPeakMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

EnergyConsumptionElectricityNaturalGasMonthly

| Meter |

EndUseEnergyConsumptionElectricityMonthly

| Meter |

EndUseEnergyConsumptionNaturalGasMonthly

| Meter |

PeakEnergyEndUseElectricityPart1Monthly

| Meter |

PeakEnergyEndUseElectricityPart2Monthly

| Meter |

ElectricComponentsOfPeakDemandMonthly

| Meter |

PeakEnergyEndUseNaturalGasMonthly

| Meter |

SetpointsNotMetWithTemperaturesMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

ComfortReportSimple55Monthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

OccupantComfortDataSummaryMonthly

| BASEMENT PEOPLE | RETAIL_1_FLR_1 PEOPLE | RETAIL_2_FLR_1 PEOPLE | LAUNDRY_FLR_1 PEOPLE | CAFE_FLR_1 PEOPLE | LOBBY_FLR_1 PEOPLE | ROOM_1_FLR_3 PEOPLE | ROOM_2_FLR_3 PEOPLE | ROOM_3_MULT19_FLR_3 PEOPLE | ROOM_4_MULT19_FLR_3 PEOPLE | ROOM_5_FLR_3 PEOPLE | ROOM_6_FLR_3 PEOPLE | ROOM_1_FLR_6 PEOPLE | ROOM_2_FLR_6 PEOPLE | ROOM_3_MULT9_FLR_6 PEOPLE | BANQUET_FLR_6 PEOPLE | DINING_FLR_6 PEOPLE | KITCHEN_FLR_6 PEOPLE | STORAGE_FLR_1 PEOPLE | CORRIDOR_FLR_3 PEOPLE | CORRIDOR_FLR_6 PEOPLE | MECH_FLR_1 PEOPLE |

ChillerReportMonthly

| COOLSYS1 CHILLER1 |

BoilerReportMonthly

| HEATSYS1 BOILER |

DXReportMonthly

| VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |

WindowReportMonthly

| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |

WindowEnergyReportMonthly

| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |

WindowZoneSummaryMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

WindowEnergyZoneSummaryMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

AverageOutdoorConditionsMonthly

| Environment |

OutdoorConditionsMaximumDryBulbMonthly

| Environment |

OutdoorConditionsMinimumDryBulbMonthly

| Environment |

OutdoorConditionsMaximumWetBulbMonthly

| Environment |

OutdoorConditionsMaximumDewPointMonthly

| Environment |

OutdoorGroundConditionsMonthly

| Environment |

WaterHeaterReportMonthly

| SWH BOOSTER E WATER HEATER | SWH LAUNDRY G WATER HEATER | SWHSYS1 WATER HEATER |

DaylightingReportMonthly

| Environment |

CoilReportMonthly

| VAV WITH REHEAT HEATING COIL | BASEMENT VAV BOX REHEAT COIL | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | MECH_FLR_1 VAV BOX REHEAT COIL | STORAGE_FLR_1 VAV BOX REHEAT COIL | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | CAFE_FLR_1 VAV BOX REHEAT COIL | LOBBY_FLR_1 VAV BOX REHEAT COIL | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | BANQUET_FLR_6 VAV BOX REHEAT COIL | DINING_FLR_6 VAV BOX REHEAT COIL | KITCHEN_FLR_6 VAV BOX REHEAT COIL | FLR_3_DOAS HEATING COIL | ROOM_1_FLR_3 FAN COIL HEATING COIL | ROOM_2_FLR_3 FAN COIL HEATING COIL | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_5_FLR_3 FAN COIL HEATING COIL | ROOM_6_FLR_3 FAN COIL HEATING COIL | ROOM_1_FLR_6 FAN COIL HEATING COIL | ROOM_2_FLR_6 FAN COIL HEATING COIL | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |

PlantLoopDemandReportMonthly

| HEATSYS1 | COOLSYS1 | SWHSYS1 |

FanReportMonthly

| FLR_3_DOAS FAN | VAV WITH REHEAT FAN | LAUNDRY_FLR_1 EXHAUST FAN | LOBBY_FLR_1 EXHAUST FAN | BANQUET_FLR_6 EXHAUST FAN | DINING_FLR_6 EXHAUST FAN | KITCHEN_FLR_6 EXHAUST FAN | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN |

PumpReportMonthly

| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 PUMP | SWHSYS1 PUMP |

CondLoopDemandReportMonthly

| HEATSYS1 | COOLSYS1 | SWHSYS1 |

ZoneTemperatureOscillationReportMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

AirLoopSystemEnergyAndWaterUseMonthly

| VAV WITH REHEAT | FLR_3_DOAS |

AirLoopSystemComponentLoadsMonthly

| VAV WITH REHEAT | FLR_3_DOAS |

AirLoopSystemComponentEnergyUseMonthly

| VAV WITH REHEAT | FLR_3_DOAS |

MechanicalVentilationLoadsMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

HeatEmissionsReportMonthly

| Environment |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2023-10-16 08:58:43

General

Value
Program Version and Build EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:58
RunPeriod RUNPERIOD 1
Weather File Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745
Latitude [deg] 32.17
Longitude [deg] -110.9
Elevation [m] 809.00
Time Zone -7.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 4559.59 1873.43 406.47 1873.22 406.47
Above Ground Wall Area [m2] 4025.82 1662.30 350.71 1662.10 350.71
Window Opening Area [m2] 1213.79 432.95 85.85 609.15 85.85
Gross Window-Wall Ratio [%] 26.62 23.11 21.12 32.52 21.12
Above Ground Window-Wall Ratio [%] 30.15 26.05 24.48 36.65 24.48


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 4559.59 1873.43 406.47 1873.22 406.47
Above Ground Wall Area [m2] 4025.82 1662.30 350.71 1662.10 350.71
Window Opening Area [m2] 1213.79 432.95 85.85 609.15 85.85
Gross Window-Wall Ratio [%] 26.62 23.11 21.12 32.52 21.12
Above Ground Window-Wall Ratio [%] 30.15 26.05 24.48 36.65 24.48


Skylight-Roof Ratio

Total
Gross Roof Area [m2] 1978.84
Skylight Area [m2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [m3] Multipliers Above Ground Gross Wall Area [m2] Underground Gross Wall Area [m2] Window Glass Area [m2] Opening Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
BASEMENT 1978.83 Yes Yes 4826.41 1.00 0.00 533.77 0.00 0.00 8.7495 18.58 5.3800
RETAIL_1_FLR_1 67.07 Yes Yes 265.76 1.00 68.84 0.00 23.26 23.26 13.0124 6.19 10.7600
RETAIL_2_FLR_1 77.67 Yes Yes 307.76 1.00 26.57 0.00 0.00 0.00 13.0124 6.19 10.7600
MECH_FLR_1 164.24 Yes Yes 650.80 1.00 62.80 0.00 0.00 0.00 10.0642 61.93 5.3800
STORAGE_FLR_1 94.76 Yes Yes 375.47 1.00 36.23 0.00 0.00 0.00 7.3195 46.45 2.6900
LAUNDRY_FLR_1 78.04 Yes Yes 309.22 1.00 85.75 0.00 0.00 0.00 5.4896 9.29 597.5300
CAFE_FLR_1 188.86 Yes Yes 748.35 1.00 152.17 0.00 65.50 65.50 12.8090 1.33 5.3800
LOBBY_FLR_1 1308.19 Yes Yes 5183.56 1.00 434.79 0.00 85.08 85.08 10.0642 3.10 8.0700
ROOM_1_FLR_3 39.02 Yes Yes 118.94 4.00 39.95 0.00 13.18 13.18 10.0642 26.01 6.7500
ROOM_2_FLR_3 39.02 Yes Yes 118.93 4.00 39.95 0.00 13.18 13.18 10.0642 26.01 6.7500
ROOM_3_MULT19_FLR_3 24.52 Yes Yes 74.75 76.00 11.15 0.00 3.68 3.68 10.0642 16.35 10.5200
ROOM_4_MULT19_FLR_3 24.53 Yes Yes 74.77 76.00 11.15 0.00 3.68 3.68 10.0642 16.35 10.5200
ROOM_5_FLR_3 39.02 Yes Yes 118.94 4.00 39.95 0.00 13.18 13.18 10.0642 26.01 6.7500
ROOM_6_FLR_3 39.02 Yes Yes 118.93 4.00 39.95 0.00 13.18 13.18 10.0642 26.01 6.7500
CORRIDOR_FLR_3 389.40 Yes Yes 1186.91 4.00 48.31 0.00 15.94 15.94 3.6597 18.58 0.0000
ROOM_1_FLR_6 39.02 Yes Yes 118.94 1.00 39.95 0.00 13.18 13.18 10.0642 26.01 6.7500
ROOM_2_FLR_6 39.02 Yes Yes 118.93 1.00 39.95 0.00 13.18 13.18 10.0642 26.01 6.7500
ROOM_3_MULT9_FLR_6 24.53 Yes Yes 74.77 9.00 20.44 0.00 6.74 6.74 10.0642 16.35 10.5200
BANQUET_FLR_6 331.66 Yes Yes 1010.89 1.00 97.55 0.00 32.19 32.19 12.8090 1.33 67.8200
DINING_FLR_6 331.66 Yes Yes 1010.89 1.00 97.55 0.00 32.19 32.19 12.8090 1.33 67.8200
KITCHEN_FLR_6 103.30 Yes Yes 314.87 1.00 87.33 0.00 26.37 26.37 10.9792 4.65 2936.4163
CORRIDOR_FLR_6 412.12 Yes Yes 1256.16 1.00 85.47 0.00 28.20 28.20 3.6597 18.58 0.0000
Total 11345.29     35184.81   4025.82 533.77 1213.79 1213.79 8.9207 7.07 41.0885
Conditioned Total 11345.29     35184.81   4025.82 533.77 1213.79 1213.79 8.9207 7.07 41.0885
Unconditioned Total 0.00     0.00   0.00 0.00 0.00 0.00      
Not Part of Total 0.00     0.00   0.00 0.00 0.00 0.00      


Space Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Multipliers Zone Name Space Type Radiant/Solar Enclosure Name Lighting [W/m2] People [m2 per person] Plug and Process [W/m2] Tags
BASEMENT 1978.83 Yes Yes 1.00 BASEMENT GENERAL BASEMENT 8.7495 18.58 5.3800  
RETAIL_1_FLR_1 67.07 Yes Yes 1.00 RETAIL_1_FLR_1 GENERAL RETAIL_1_FLR_1 13.0124 6.19 10.7600  
RETAIL_2_FLR_1 77.67 Yes Yes 1.00 RETAIL_2_FLR_1 GENERAL RETAIL_2_FLR_1 13.0124 6.19 10.7600  
MECH_FLR_1 164.24 Yes Yes 1.00 MECH_FLR_1 GENERAL MECH_FLR_1 10.0642 61.93 5.3800  
STORAGE_FLR_1 94.76 Yes Yes 1.00 STORAGE_FLR_1 GENERAL STORAGE_FLR_1 7.3195 46.45 2.6900  
LAUNDRY_FLR_1 78.04 Yes Yes 1.00 LAUNDRY_FLR_1 GENERAL LAUNDRY_FLR_1 5.4896 9.29 597.5300  
CAFE_FLR_1 188.86 Yes Yes 1.00 CAFE_FLR_1 GENERAL CAFE_FLR_1 12.8090 1.33 5.3800  
LOBBY_FLR_1 1308.19 Yes Yes 1.00 LOBBY_FLR_1 GENERAL LOBBY_FLR_1 10.0642 3.10 8.0700  
ROOM_1_FLR_3 39.02 Yes Yes 4.00 ROOM_1_FLR_3 GENERAL ROOM_1_FLR_3 10.0642 26.01 6.7500  
ROOM_2_FLR_3 39.02 Yes Yes 4.00 ROOM_2_FLR_3 GENERAL ROOM_2_FLR_3 10.0642 26.01 6.7500  
ROOM_3_MULT19_FLR_3 24.52 Yes Yes 76.00 ROOM_3_MULT19_FLR_3 GENERAL ROOM_3_MULT19_FLR_3 10.0642 16.35 10.5200  
ROOM_4_MULT19_FLR_3 24.53 Yes Yes 76.00 ROOM_4_MULT19_FLR_3 GENERAL ROOM_4_MULT19_FLR_3 10.0642 16.35 10.5200  
ROOM_5_FLR_3 39.02 Yes Yes 4.00 ROOM_5_FLR_3 GENERAL ROOM_5_FLR_3 10.0642 26.01 6.7500  
ROOM_6_FLR_3 39.02 Yes Yes 4.00 ROOM_6_FLR_3 GENERAL ROOM_6_FLR_3 10.0642 26.01 6.7500  
CORRIDOR_FLR_3 389.40 Yes Yes 4.00 CORRIDOR_FLR_3 GENERAL CORRIDOR_FLR_3 3.6597 18.58 0.0000  
ROOM_1_FLR_6 39.02 Yes Yes 1.00 ROOM_1_FLR_6 GENERAL ROOM_1_FLR_6 10.0642 26.01 6.7500  
ROOM_2_FLR_6 39.02 Yes Yes 1.00 ROOM_2_FLR_6 GENERAL ROOM_2_FLR_6 10.0642 26.01 6.7500  
ROOM_3_MULT9_FLR_6 24.53 Yes Yes 9.00 ROOM_3_MULT9_FLR_6 GENERAL ROOM_3_MULT9_FLR_6 10.0642 16.35 10.5200  
BANQUET_FLR_6 331.66 Yes Yes 1.00 BANQUET_FLR_6 GENERAL BANQUET_FLR_6 12.8090 1.33 67.8200  
DINING_FLR_6 331.66 Yes Yes 1.00 DINING_FLR_6 GENERAL DINING_FLR_6 12.8090 1.33 67.8200  
KITCHEN_FLR_6 103.30 Yes Yes 1.00 KITCHEN_FLR_6 GENERAL KITCHEN_FLR_6 10.9792 4.65 2936.4163  
CORRIDOR_FLR_6 412.12 Yes Yes 1.00 CORRIDOR_FLR_6 GENERAL CORRIDOR_FLR_6 3.6597 18.58 0.0000  
Total 11345.29             8.9207 3.54 41.0885  
Conditioned Total 11345.29             8.9207 3.54 41.0885  
Unconditioned Total 0.00             0.0000 0.00 0.0000  
Not Part of Total 0.00             0.0000 0.00 0.0000  


Space Type Summary

Total Area [m2] Conditioned Area [m2] Unconditioned Area [m2] Not Part of Total Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
GENERAL 11345.29 11345.29 0.00 0.00 4.6908 8.82 37.2165
Total 11345.29 11345.29 0.00 0.00      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2023-10-16 08:58:43

End Uses

Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Time of Peak 28-JUN-18:10 12-FEB-17:00 - - - - - - - - - - 02-JAN-21:10
Heating 0.00 87066.07 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 302441.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 82800.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 79617.06 87521.34 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 32686.23 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 91922.97 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 12752.43 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 19264.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 4455.32 242282.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 2899.46 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 628839.67 416869.49 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Subcategory

Subcategory Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Heating General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler 0.00 87066.07 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 302441.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 82800.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 49434.66 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Cooking 29240.64 74976.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ReachInFreezer 515.92 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ReachInRefrigerator 425.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Laundry 0.00 12545.23 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Transformer 1560.87 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLift 30153.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLightsFan 972.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  General 91922.97 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 12752.43 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 19264.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Water Heater 4455.32 242282.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 642.84 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  LowTempRefrigeration 1182.27 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  MedTempRefrigeration 1074.35 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2023-10-16 08:58:43

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [GJ] Source Natural Gas [GJ] Source Gasoline [GJ] Source Diesel [GJ] Source Coal [GJ] Source Fuel Oil No 1 [GJ] Source Fuel Oil No 2 [GJ] Source Propane [GJ] Source Other Fuel 1 [GJ] Source Other Fuel 2 [GJ] Source District Cooling [GJ] Source District Heating [GJ]
Heating 0.00 918.79 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 9649.23 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 3718.41 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 831.35 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 5546.36 1939.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 2152.55 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 6517.18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 987.18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 1868.84 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 287.49 2986.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 234.97 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 31793.55 5844.34 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 80.98 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 850.51 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 327.75 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 73.28 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 488.87 170.92 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 189.73 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 574.44 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 87.01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 164.72 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 25.34 263.23 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 20.71 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 2802.36 515.13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 80.98 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 850.51 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 327.75 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 73.28 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 488.87 170.92 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 189.73 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 574.44 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 87.01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 164.72 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 25.34 263.23 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 20.71 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 2802.36 515.13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2023-10-16 08:58:43

AirTerminal:SingleDuct:VAV:Reheat

Design Size Maximum Air Flow Rate [m3/s] Design Size Constant Minimum Air Flow Fraction User-Specified Constant Minimum Air Flow Fraction Design Size Minimum Air Flow Rate [m3/s] Design Size Maximum Flow Fraction during Reheat [] User-Specified Maximum Flow Fraction during Reheat [] Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] Design Size Maximum Reheat Water Flow Rate [m3/s] Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] Design Size Reheat Coil Sizing Inlet Air Temperature [C] Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir]
BASEMENT VAV BOX COMPONENT 2.87 0.524738 0.995000 2.86 1.00 0.500000 0.000726 0.000120 2.86 16.70 0.008000
RETAIL_1_FLR_1 VAV BOX COMPONENT 0.399326 0.127987 0.995000 0.397330 0.995000 0.500000 0.002977 0.000039 0.397330 16.70 0.008000
RETAIL_2_FLR_1 VAV BOX COMPONENT 0.282961 0.209159 0.995000 0.281546 0.995000 0.500000 0.001822 0.000019 0.281546 16.70 0.008000
MECH_FLR_1 VAV BOX COMPONENT 0.312183 0.400897 0.995000 0.310622 1.00 0.500000 0.000950 0.000027 0.310622 16.70 0.008000
STORAGE_FLR_1 VAV BOX COMPONENT 0.158154 0.456560 0.995000 0.157363 1.00 0.500000 0.000835 0.000015 0.157363 16.70 0.008000
LAUNDRY_FLR_1 VAV BOX COMPONENT 3.64 0.064763 0.995000 3.63 0.995000 0.500000 0.023345 0.000171 3.63 16.70 0.008000
CAFE_FLR_1 VAV BOX COMPONENT 1.65 0.087276 0.995000 1.64 0.995000 0.500000 0.004365 0.000125 1.64 16.70 0.008000
LOBBY_FLR_1 VAV BOX COMPONENT 5.39 0.184803 0.995000 5.37 0.995000 0.500000 0.002062 0.000357 5.37 16.70 0.008000
CORRIDOR_FLR_3 VAV BOX COMPONENT 1.40 0.846722 0.995000 1.39 1.00 0.500000 0.000450 0.000136 1.39 16.70 0.008000
BANQUET_FLR_6 VAV BOX COMPONENT 2.57 0.098433 0.995000 2.55 0.995000 0.500000 0.003871 0.000159 2.55 16.70 0.008000
DINING_FLR_6 VAV BOX COMPONENT 2.69 0.093973 0.995000 2.68 0.995000 0.500000 0.004054 0.000165 2.68 16.70 0.008000
KITCHEN_FLR_6 VAV BOX COMPONENT 2.55 0.740145 0.995000 2.54 0.995000 0.500000 0.012345 0.000117 2.54 16.70 0.008000
CORRIDOR_FLR_6 VAV BOX COMPONENT 0.852781 0.368253 0.995000 0.848517 0.995000 0.500000 0.001035 0.000090 0.848517 16.70 0.008000
User-Specified values were used. Design Size values were used if no User-Specified values were provided. Design Size values may be derived from alternate User-Specified values.

Coil:Heating:Water

Design Size Rated Capacity [W] Design Size Maximum Water Flow Rate [m3/s] Design Size U-Factor Times Area Value [W/K]
BASEMENT VAV BOX REHEAT COIL 13705.25 0.000120 285.80
RETAIL_1_FLR_1 VAV BOX REHEAT COIL 4468.08 0.000039 100.21
RETAIL_2_FLR_1 VAV BOX REHEAT COIL 2203.53 0.000019 47.51
MECH_FLR_1 VAV BOX REHEAT COIL 3101.04 0.000027 68.53
STORAGE_FLR_1 VAV BOX REHEAT COIL 1698.38 0.000015 37.89
LAUNDRY_FLR_1 VAV BOX REHEAT COIL 19527.16 0.000171 409.83
CAFE_FLR_1 VAV BOX REHEAT COIL 14253.78 0.000125 310.37
LOBBY_FLR_1 VAV BOX REHEAT COIL 40785.34 0.000357 877.21
ROOM_1_FLR_3 FAN COIL HEATING COIL 5573.41 0.000049 159.27
ROOM_2_FLR_3 FAN COIL HEATING COIL 5577.97 0.000049 159.40
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL 32042.69 0.000280 915.69
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL 32146.75 0.000281 918.66
ROOM_5_FLR_3 FAN COIL HEATING COIL 5563.54 0.000049 158.99
ROOM_6_FLR_3 FAN COIL HEATING COIL 5568.10 0.000049 159.12
CORRIDOR_FLR_3 VAV BOX REHEAT COIL 15525.10 0.000136 347.74
ROOM_1_FLR_6 FAN COIL HEATING COIL 1729.34 0.000015 49.42
ROOM_2_FLR_6 FAN COIL HEATING COIL 1729.86 0.000015 49.43
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL 8347.43 0.000073 238.53
BANQUET_FLR_6 VAV BOX REHEAT COIL 18141.00 0.000159 388.01
DINING_FLR_6 VAV BOX REHEAT COIL 18830.34 0.000165 402.46
KITCHEN_FLR_6 VAV BOX REHEAT COIL 13392.17 0.000117 280.74
CORRIDOR_FLR_6 VAV BOX REHEAT COIL 10312.81 0.000090 233.82
VAV WITH REHEAT HEATING COIL 131650.00 0.001152 2309.98
FLR_3_DOAS HEATING COIL 10951.44 0.000096 192.16
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:ZoneExhaust

User-Specified Maximum Flow Rate [m3/s]
LOBBY_FLR_1 EXHAUST FAN 0.000000
BANQUET_FLR_6 EXHAUST FAN 0.000000
DINING_FLR_6 EXHAUST FAN 0.000000
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirTerminal:SingleDuct:ConstantVolume:NoReheat

Design Size Maximum Air Flow Rate [m3/s]
ROOM_1_FLR_3 DIRECT AIR 0.061735
ROOM_2_FLR_3 DIRECT AIR 0.061728
ROOM_3_MULT19_FLR_3 DIRECT AIR 0.837072
ROOM_4_MULT19_FLR_3 DIRECT AIR 0.837300
ROOM_5_FLR_3 DIRECT AIR 0.061735
ROOM_6_FLR_3 DIRECT AIR 0.061728
ROOM_1_FLR_6 DIRECT AIR 0.015434
ROOM_2_FLR_6 DIRECT AIR 0.015432
ROOM_3_MULT9_FLR_6 DIRECT AIR 0.099154
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

ZoneHVAC:FourPipeFanCoil

Design Size Maximum Supply Air Flow Rate [m3/s] Design Size Maximum Hot Water Flow [m3/s] Design Size Maximum Cold Water Flow [m3/s]
ROOM_1_FLR_3 FAN COIL 1.31 0.000049 0.000512
ROOM_2_FLR_3 FAN COIL 1.30 0.000049 0.000509
ROOM_3_MULT19_FLR_3 FAN COIL 7.84 0.000280 0.003072
ROOM_4_MULT19_FLR_3 FAN COIL 8.37 0.000281 0.003374
ROOM_5_FLR_3 FAN COIL 1.15 0.000049 0.000451
ROOM_6_FLR_3 FAN COIL 1.14 0.000049 0.000448
ROOM_1_FLR_6 FAN COIL 0.353766 0.000015 0.000139
ROOM_2_FLR_6 FAN COIL 0.351139 0.000015 0.000138
ROOM_3_MULT9_FLR_6 FAN COIL 1.59 0.000073 0.000628
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:OnOff

Design Size Maximum Flow Rate [m3/s]
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN 1.31
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN 1.30
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN 7.84
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN 8.37
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN 1.15
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN 1.14
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN 0.353766
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN 0.351139
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN 1.59
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Cooling:Water

Design Size Design Inlet Air Temperature [C] Design Size Design Inlet Water Temperature [C] Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] Design Size Design Outlet Air Temperature [C] Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] Design Size Design Water Flow Rate [m3/s] Design Size Design Air Flow Rate [m3/s] Design Size Design Coil Load [W]
ROOM_1_FLR_3 FAN COIL COOLING COIL 22.63 6.70 0.008479 12.80 0.008479 0.000512 1.31  
ROOM_2_FLR_3 FAN COIL COOLING COIL 22.63 6.70 0.008479 12.80 0.008479 0.000509 1.30  
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL 22.63 6.70 0.008428 12.80 0.008428 0.003072 7.84  
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL 22.63 6.70 0.008614 12.80 0.008500 0.003374 8.37  
ROOM_5_FLR_3 FAN COIL COOLING COIL 22.63 6.70 0.008476 12.80 0.008476 0.000451 1.15  
ROOM_6_FLR_3 FAN COIL COOLING COIL 22.63 6.70 0.008475 12.80 0.008475 0.000448 1.14  
ROOM_1_FLR_6 FAN COIL COOLING COIL 22.63 6.70 0.008481 12.80 0.008481 0.000139 0.353766  
ROOM_2_FLR_6 FAN COIL COOLING COIL 22.63 6.70 0.008481 12.80 0.008481 0.000138 0.351139  
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL 22.63 6.70 0.008536 12.80 0.008500 0.000628 1.59  
VAV WITH REHEAT COOLING COIL 40.80 6.70 0.005631 10.78 0.005631 0.029346 24.66 821617.44
FLR_3_DOAS COOLING COIL 40.80 6.70 0.005631 11.84 0.005631 0.002355 2.05 65945.86
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC

Sum of Air Terminal Maximum Heating Flow Rates [m3/s] Sum of Air Terminal Minimum Heating Flow Rates [m3/s] Sum of Air Terminal Maximum Flow Rates [m3/s] Adjusted Heating Design Air Flow Rate [m3/s] Adjusted Cooling Design Air Flow Rate [m3/s] Adjusted Main Design Air Flow Rate [m3/s] User Heating Air Flow Ratio [] Calculated Heating Air Flow Ratio [] Design Supply Air Flow Rate [m3/s]
VAV WITH REHEAT 24.65 24.65 24.77 24.65 24.66 24.66 0.300000 0.999653 24.66
FLR_3_DOAS 2.05 2.05 2.05 2.05 2.05 2.05 0.300000 1.00 2.05
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:OutdoorAir

Maximum Outdoor Air Flow Rate [m3/s] Minimum Outdoor Air Flow Rate [m3/s]
VAV WITH REHEAT_OA_CONTROLLER 24.66 24.66
FLR_3_DOAS_OA_CONTROLLER 2.05 2.05
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

HeatExchanger:AirToAir:SensibleAndLatent

Design Size Nominal Supply Air Flow Rate [m3/s]
VAV WITH REHEAT OA HEAT RECOVERY 24.66
FLR_3_DOAS OA HEAT RECOVERY 2.05
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:VariableVolume

Design Size Maximum Flow Rate [m3/s]
VAV WITH REHEAT FAN 24.66
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:WaterCoil

Maximum Actuated Flow [m3/s] Controller Convergence Tolerance
VAV WITH REHEAT_COOLC_CONTROLLER 0.029346 0.000016
VAV WITH REHEAT_HEATC_CONTROLLER 0.001152  
FLR_3_DOAS_COOLC_CONTROLLER 0.002355 0.000202
FLR_3_DOAS_HEATC_CONTROLLER 0.000096  
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:ConstantVolume

User-Specified Maximum Flow Rate [m3/s]
FLR_3_DOAS FAN 2.05
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:VariableSpeed

Design Flow Rate [m3/s] Design Power Consumption [W] Design Minimum Flow Rate [m3/s]
COOLSYS1 PUMP SECONDARY 0.040971 8442.59  
HEATSYS1 PUMP 0.003647 1098.18 0.000000
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantLoop

Maximum Loop Flow Rate [m3/s] Plant Loop Volume [m3]
HEATSYS1 0.003647 0.437587
COOLSYS1 0.040971 4.92
SWHSYS1 0.000375 0.045004
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Boiler:HotWater

Design Size Nominal Capacity [W] User-Specified Nominal Capacity [W] Design Size Design Water Flow Rate [m3/s]
HEATSYS1 BOILER 416824.50 416824.50 0.003647
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:ConstantSpeed

Design Flow Rate [m3/s] Design Power Consumption [W]
COOLSYS1 PUMP 0.040971 5845.09
SWHSYS1 PUMP 0.000375 47.91
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Chiller:Electric:EIR

Design Size Reference Chilled Water Flow Rate [m3/s] Design Size Reference Capacity [W] User-Specified Reference Capacity [W] Design Size Reference Condenser Fluid Flow Rate [m3/s]
COOLSYS1 CHILLER1 0.040971 1147076.31 1147742.06 130.84
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

WaterHeater:Mixed

Use Side Design Flow Rate [m3/s]
SWHSYS1 WATER HEATER 0.000375
User-Specified values were used. Design Size values were used if no User-Specified values were provided.


Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2023-10-16 08:58:43

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

Possible Shadow Receivers
RETAIL_1_FLR_1_CEILING ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH |
CAFE_FLR_1_CEILING ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH |
LOBBY_FLR_1_CEILING_2 ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH |


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
RETAIL_1_FLR_1_WALL_SOUTH RETAIL_1_FLR_1_WALL_SOUTH_WINDOW |
RETAIL_2_FLR_1_WALL_WEST RETAIL_2_FLR_1_WALL_WEST_DOOR |
STORAGE_FLR_1_WALL_NORTH STORAGE_FLR_1_WALL_NORTH_ROLLDOOR |
LAUNDRY_FLR_1_WALL_EAST LAUNDRY_FLR_1_WALL_EAST_DOOR |
CAFE_FLR_1_WALL_EAST CAFE_FLR_1_WALL_EAST_DOOR |
CAFE_FLR_1_WALL_SOUTH CAFE_FLR_1_WALL_SOUTH_WINDOW |
LOBBY_FLR_1_WALL_1_NORTH LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 |
LOBBY_FLR_1_WALL_1_SOUTH LOBBY_FLR_1_WALL_SOUTH_WINDOW |
ROOM_1_FLR_3_WALL_SOUTH ROOM_1_FLR_3_WALL_SOUTH_WINDOW |
ROOM_1_FLR_3_WALL_WEST ROOM_1_FLR_3_WALL_WEST_WINDOW |
ROOM_2_FLR_3_WALL_NORTH ROOM_2_FLR_3_WALL_NORTH_WINDOW |
ROOM_2_FLR_3_WALL_WEST ROOM_2_FLR_3_WALL_WEST_WINDOW |
ROOM_3_MULT19_FLR_3_WALL_SOUTH ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW |
ROOM_4_MULT19_FLR_3_WALL_NORTH ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW |
ROOM_5_FLR_3_WALL_EAST ROOM_5_FLR_3_WALL_EAST_WINDOW |
ROOM_5_FLR_3_WALL_SOUTH ROOM_5_FLR_3_WALL_SOUTH_WINDOW |
ROOM_6_FLR_3_WALL_NORTH ROOM_6_FLR_3_WALL_NORTH_WINDOW |
ROOM_6_FLR_3_WALL_EAST ROOM_6_FLR_3_WALL_EAST_WINDOW |
CORRIDOR_FLR_3_WALL_1_NORTH CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW |
CORRIDOR_FLR_3_WALL_2_NORTH CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW |
CORRIDOR_FLR_3_WALL_1_SOUTH CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW |
CORRIDOR_FLR_3_WALL_2_SOUTH CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW |
ROOM_1_FLR_6_WALL_SOUTH ROOM_1_FLR_6_WALL_SOUTH_WINDOW |
ROOM_1_FLR_6_WALL_WEST ROOM_1_FLR_6_WALL_WEST_WINDOW |
ROOM_2_FLR_6_WALL_NORTH ROOM_2_FLR_6_WALL_NORTH_WINDOW |
ROOM_2_FLR_6_WALL_WEST ROOM_2_FLR_6_WALL_WEST_WINDOW |
ROOM_3_MULT9_FLR_6_WALL_SOUTH ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW |
BANQUET_FLR_6_WALL_NORTH BANQUET_FLR_6_WALL_NORTH_WINDOW |
DINING_FLR_6_WALL_NORTH DINING_FLR_6_WALL_NORTH_WINDOW |
KITCHEN_FLR_6_WALL_NORTH KITCHEN_FLR_6_WALL_NORTH_WINDOW |
KITCHEN_FLR_6_WALL_EAST KITCHEN_FLR_6_WALL_EAST_WINDOW |
KITCHEN_FLR_6_WALL_1_SOUTH KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW |
CORRIDOR_FLR_6_WALL_1_NORTH CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW |
CORRIDOR_FLR_6_WALL_2_NORTH CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW |
CORRIDOR_FLR_6_WALL_2_SOUTH CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2023-10-16 08:58:43

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: Initialization Summary

For: Entire Facility

Timestamp: 2023-10-16 08:58:43

Version

Version ID
1 22.1


Timesteps per Hour

#TimeSteps Minutes per TimeStep {minutes}
1 6 10


System Convergence Limits

Minimum System TimeStep {minutes} Max HVAC Iterations Minimum Plant Iterations Maximum Plant Iterations
1 1 20 2 8


Simulation Control

Do Zone Sizing Do System Sizing Do Plant Sizing Do Design Days Do Weather Simulation Do HVAC Sizing Simulation
1 Yes Yes Yes No Yes No


Performance Precision Tradeoffs

Use Coil Direct Simulation Zone Radiant Exchange Algorithm Override Mode Number of Timestep In Hour Force Euler Method Minimum Number of Warmup Days Force Suppress All Begin Environment Resets Minimum System Timestep MaxZoneTempDiff MaxAllowedDelTemp
1 No ScriptF Normal 6 No 1 No 1.0 0.300 2.0000E-003


Output Reporting Tolerances

Tolerance for Time Heating Setpoint Not Met Tolerance for Zone Cooling Setpoint Not Met Time
1 0.556 0.556


Site:GroundTemperature:BuildingSurface

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00


Site:GroundTemperature:FCfactorMethod

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 20.90 15.40 11.90 14.80 12.70 15.40 23.30 26.30 31.20 30.40 29.80 27.80


Site:GroundTemperature:Shallow

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00


Site:GroundTemperature:Deep

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00


Site:GroundReflectance

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:SnowModifier

Normal Daylighting {dimensionless}
1 1.000 1.000


Site:GroundReflectance:Snow

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:Snow:Daylighting

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Environment:Weather Station

Wind Sensor Height Above Ground {m} Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Sensor Height Above Ground {m} Wind Speed Modifier Coefficient-Internal Temperature Modifier Coefficient-Internal
1 10.000 0.140 270.000 1.500 1.586 9.750E-003


Site:Location

Location Name Latitude {N+/S- Deg} Longitude {E+/W- Deg} Time Zone Number {GMT+/-} Elevation {m} Standard Pressure at Elevation {Pa} Standard RhoAir at Elevation
1 Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745 32.17 -110.88 -7.00 809.00 91976 1.0932


Site Water Mains Temperature Information

Calculation Method{} Water Mains Temperature Schedule Name{} Annual Average Outdoor Air Temperature{C} Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} Fixed Default Water Mains Temperature{C}
1 Correlation NA 21.66 19.30 NA


Building Information

Building Name North Axis {deg} Terrain Loads Convergence Tolerance Value Temperature Convergence Tolerance Value Solar Distribution Maximum Number of Warmup Days Minimum Number of Warmup Days
1 HotelLarge 0.000 City 4.00000E-002 0.20000 FullInteriorAndExterior 25 6


Inside Convection Algorithm

Algorithm {Simple
TARP
CeilingDiffuser
AdaptiveConvectionAlgorithm}
1 TARP


Outside Convection Algorithm

Algorithm {SimpleCombined
TARP
MoWitt
DOE-2
AdaptiveConvectionAlgorithm}
1 DOE-2


Sky Radiance Distribution

Value {Anisotropic}
1 Anisotropic


Zone Air Solution Algorithm

Value {ThirdOrderBackwardDifference
AnalyticalSolution
EulerMethod}
1 ThirdOrderBackwardDifference


Zone Air Carbon Dioxide Balance Simulation

Simulation {Yes/No} Carbon Dioxide Concentration
1 No N/A


Zone Air Generic Contaminant Balance Simulation

Simulation {Yes/No} Generic Contaminant Concentration
1 No N/A


Zone Air Mass Flow Balance Simulation

Enforce Mass Balance



Adjust Zone Mixing and Return {AdjustMixingOnly
AdjustReturnOnly
AdjustMixingThenReturn
AdjustReturnThenMixing
None}
Adjust Zone Infiltration {AddInfiltration
AdjustInfiltration
None}

Infiltration Zones {MixingSourceZonesOnly
AllZones}


1 No N/A N/A N/A


HVACSystemRootFindingAlgorithm

Value {RegulaFalsi
Bisection
BisectionThenRegulaFalsi
RegulaFalsiThenBisection}
1 RegulaFalsi


Environment:Site Atmospheric Variation

Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Gradient Coefficient {K/m}
1 0.330 460.000 6.500000E-003


Surface Geometry

Starting Corner Vertex Input Direction Coordinate System Daylight Reference Point Coordinate System Rectangular (Simple) Surface Coordinate System
1 UpperLeftCorner Counterclockwise RelativeCoordinateSystem RelativeCoordinateSystem RelativeToZoneOrigin


Surface Heat Transfer Algorithm

Value {CTF - ConductionTransferFunction
EMPD - MoisturePenetrationDepthConductionTransferFunction
CondFD - ConductionFiniteDifference
HAMT - CombinedHeatAndMoistureFiniteElement} - Description
Inside Surface Max Temperature Limit{C}


Surface Convection Coefficient Lower Limit {W/m2-K}


Surface Convection Coefficient Upper Limit {W/m2-K}


1 CTF - ConductionTransferFunction 200 0.10 1000.0


Shading Summary

Number of Fixed Detached Shades Number of Building Detached Shades Number of Attached Shades
1 0 0 0


Zone Summary

Number of Zones Number of Zone Surfaces Number of SubSurfaces
1 22 235 36


Zone Information

Zone Name North Axis {deg} Origin X-Coordinate {m} Origin Y-Coordinate {m} Origin Z-Coordinate {m} Centroid X-Coordinate {m} Centroid Y-Coordinate {m} Centroid Z-Coordinate {m} Type Zone Multiplier Zone List Multiplier Minimum X {m} Maximum X {m} Minimum Y {m} Maximum Y {m} Minimum Z {m} Maximum Z {m} Ceiling Height {m} Volume {m3} Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} Floor Area {m2} Exterior Gross Wall Area {m2} Exterior Net Wall Area {m2} Exterior Window Area {m2} Number of Surfaces Number of SubSurfaces Number of Shading SubSurfaces Part of Total Building Area
1 BASEMENT 0.0 0.00 0.00 0.00 41.45 11.51 -1.22 1 1 1 0.00 86.56 0.00 22.86 -2.44 0.00 2.44 4826.41 TARP DOE-2 1978.83 0.00 0.00 0.00 13 0 0 Yes
2 RETAIL_1_FLR_1 0.0 0.00 0.00 0.00 5.79 2.90 1.98 1 1 1 0.00 11.58 0.00 5.79 0.00 3.96 3.96 265.76 TARP DOE-2 67.07 68.84 45.58 23.26 6 1 0 Yes
3 RETAIL_2_FLR_1 0.0 0.00 0.00 0.00 5.79 9.14 1.98 1 1 1 0.00 11.58 5.79 12.50 0.00 3.96 3.96 307.76 TARP DOE-2 77.67 26.57 24.62 0.00 6 1 0 Yes
4 MECH_FLR_1 0.0 0.00 0.00 0.00 61.87 17.68 1.98 1 1 1 53.95 69.80 12.50 22.86 0.00 3.96 3.96 650.80 TARP DOE-2 164.24 62.80 62.80 0.00 6 0 0 Yes
5 STORAGE_FLR_1 0.0 0.00 0.00 0.00 74.37 17.68 1.98 1 1 1 69.80 78.94 12.50 22.86 0.00 3.96 3.96 375.47 TARP DOE-2 94.76 36.23 28.80 0.00 6 1 0 Yes
6 LAUNDRY_FLR_1 0.0 0.00 0.00 0.00 84.28 14.33 1.98 1 1 1 81.99 86.56 5.79 22.86 0.00 3.96 3.96 309.22 TARP DOE-2 78.04 85.75 83.80 0.00 6 1 0 Yes
7 CAFE_FLR_1 0.0 0.00 0.00 0.00 70.26 2.90 1.98 1 1 1 53.95 86.56 0.00 5.79 0.00 3.96 3.96 748.35 TARP DOE-2 188.86 152.17 84.72 65.50 7 2 0 Yes
8 LOBBY_FLR_1 0.0 0.00 0.00 0.00 38.29 12.45 1.98 1 1 1 0.00 81.99 0.00 22.86 0.00 3.96 3.96 5183.56 TARP DOE-2 1308.19 434.79 345.80 85.08 18 3 0 Yes
9 ROOM_1_FLR_3 0.0 0.00 0.00 0.00 2.29 10.06 8.53 1 4 1 0.00 4.57 5.79 14.33 7.01 10.06 3.05 118.94 TARP DOE-2 39.02 39.95 26.77 13.18 6 2 0 Yes
10 ROOM_2_FLR_3 0.0 0.00 0.00 0.00 2.29 18.59 8.53 1 4 1 0.00 4.57 14.33 22.86 7.01 10.06 3.05 118.93 TARP DOE-2 39.02 39.95 26.76 13.18 6 2 0 Yes
11 ROOM_3_MULT19_FLR_3 0.0 0.00 0.00 0.00 8.53 9.14 8.53 1 76 1 6.71 10.36 5.79 12.50 7.01 10.06 3.05 74.75 TARP DOE-2 24.52 11.15 7.47 3.68 6 1 0 Yes
12 ROOM_4_MULT19_FLR_3 0.0 0.00 0.00 0.00 12.19 19.51 8.53 1 76 1 10.36 14.02 16.15 22.86 7.01 10.06 3.05 74.77 TARP DOE-2 24.53 11.15 7.47 3.68 6 1 0 Yes
13 ROOM_5_FLR_3 0.0 0.00 0.00 0.00 84.28 10.06 8.53 1 4 1 81.99 86.56 5.79 14.33 7.01 10.06 3.05 118.94 TARP DOE-2 39.02 39.95 26.77 13.18 6 2 0 Yes
14 ROOM_6_FLR_3 0.0 0.00 0.00 0.00 84.28 18.59 8.53 1 4 1 81.99 86.56 14.33 22.86 7.01 10.06 3.05 118.93 TARP DOE-2 39.02 39.95 26.76 13.18 6 2 0 Yes
15 CORRIDOR_FLR_3 0.0 0.00 0.00 0.00 43.28 14.33 8.53 1 4 1 4.57 81.99 5.79 22.86 7.01 10.06 3.05 1186.91 TARP DOE-2 389.40 48.31 32.37 15.94 20 4 0 Yes
16 ROOM_1_FLR_6 0.0 0.00 0.00 0.00 2.29 10.06 17.68 1 1 1 0.00 4.57 5.79 14.33 16.15 19.20 3.05 118.94 TARP DOE-2 39.02 39.95 26.77 13.18 6 2 0 Yes
17 ROOM_2_FLR_6 0.0 0.00 0.00 0.00 2.29 18.59 17.68 1 1 1 0.00 4.57 14.33 22.86 16.15 19.20 3.05 118.93 TARP DOE-2 39.02 39.95 26.76 13.18 6 2 0 Yes
18 ROOM_3_MULT9_FLR_6 0.0 0.00 0.00 0.00 7.93 7.62 17.68 1 9 1 4.57 11.28 5.79 9.45 16.15 19.20 3.05 74.77 TARP DOE-2 24.53 20.44 13.70 6.74 6 1 0 Yes
19 BANQUET_FLR_6 0.0 0.00 0.00 0.00 26.37 17.68 17.68 1 1 1 10.36 42.37 12.50 22.86 16.15 19.20 3.05 1010.89 TARP DOE-2 331.66 97.55 65.36 32.19 6 1 0 Yes
20 DINING_FLR_6 0.0 0.00 0.00 0.00 63.55 17.68 17.68 1 1 1 47.55 79.55 12.50 22.86 16.15 19.20 3.05 1010.89 TARP DOE-2 331.66 97.55 65.36 32.19 6 1 0 Yes
21 KITCHEN_FLR_6 0.0 0.00 0.00 0.00 82.99 14.11 17.68 1 1 1 79.55 86.56 5.79 22.86 16.15 19.20 3.05 314.87 TARP DOE-2 103.30 87.33 60.96 26.37 8 3 0 Yes
22 CORRIDOR_FLR_6 0.0 0.00 0.00 0.00 41.51 13.35 17.68 1 1 1 4.57 81.99 5.79 22.86 16.15 19.20 3.05 1256.16 TARP DOE-2 412.12 85.47 57.27 28.20 15 3 0 Yes


Zone Internal Gains Nominal

Zone Name Floor Area {m2} # Occupants Area per Occupant {m2/person} Occupant per Area {person/m2} Interior Lighting {W/m2} Electric Load {W/m2} Gas Load {W/m2} Other Load {W/m2} Hot Water Eq {W/m2} Steam Equipment {W/m2} Sum Loads per Area {W/m2} Outdoor Controlled Baseboard Heat
1 BASEMENT 1978.83 106.5 18.581 5.382E-002 8.749 5.380 0.000 0.000 0.000 0.000 14.129 No
2 RETAIL_1_FLR_1 67.07 10.8 6.194 0.161 13.012 10.760 0.000 0.000 0.000 0.000 23.772 No
3 RETAIL_2_FLR_1 77.67 12.5 6.194 0.161 13.012 10.760 0.000 0.000 0.000 0.000 23.772 No
4 MECH_FLR_1 164.24 2.7 61.932 1.615E-002 10.064 5.380 0.000 0.000 0.000 0.000 15.444 No
5 STORAGE_FLR_1 94.76 2.0 46.451 2.153E-002 7.319 2.690 0.000 0.000 0.000 0.000 10.009 No
6 LAUNDRY_FLR_1 78.04 8.4 9.290 0.108 5.490 61.680 535.850 0.000 0.000 0.000 603.020 No
7 CAFE_FLR_1 188.86 142.3 1.327 0.753 12.809 5.380 0.000 0.000 0.000 0.000 18.189 No
8 LOBBY_FLR_1 1308.19 422.4 3.097 0.323 10.064 8.070 0.000 0.000 0.000 0.000 18.134 No
9 ROOM_1_FLR_3 39.02 1.5 26.015 3.844E-002 10.064 6.750 0.000 0.000 0.000 0.000 16.814 No
10 ROOM_2_FLR_3 39.02 1.5 26.012 3.844E-002 10.064 6.750 0.000 0.000 0.000 0.000 16.814 No
11 ROOM_3_MULT19_FLR_3 24.52 1.5 16.349 6.116E-002 10.064 10.520 0.000 0.000 0.000 0.000 20.584 No
12 ROOM_4_MULT19_FLR_3 24.53 1.5 16.354 6.115E-002 10.064 10.520 0.000 0.000 0.000 0.000 20.584 No
13 ROOM_5_FLR_3 39.02 1.5 26.015 3.844E-002 10.064 6.750 0.000 0.000 0.000 0.000 16.814 No
14 ROOM_6_FLR_3 39.02 1.5 26.012 3.844E-002 10.064 6.750 0.000 0.000 0.000 0.000 16.814 No
15 CORRIDOR_FLR_3 389.40 21.0 18.581 5.382E-002 3.660 0.000 0.000 0.000 0.000 0.000 3.660 No
16 ROOM_1_FLR_6 39.02 1.5 26.015 3.844E-002 10.064 6.750 0.000 0.000 0.000 0.000 16.814 No
17 ROOM_2_FLR_6 39.02 1.5 26.012 3.844E-002 10.064 6.750 0.000 0.000 0.000 0.000 16.814 No
18 ROOM_3_MULT9_FLR_6 24.53 1.5 16.354 6.115E-002 10.064 10.520 0.000 0.000 0.000 0.000 20.584 No
19 BANQUET_FLR_6 331.66 249.9 1.327 0.753 12.809 67.820 0.000 0.000 0.000 0.000 80.629 No
20 DINING_FLR_6 331.66 249.9 1.327 0.753 12.809 67.820 0.000 0.000 0.000 0.000 80.629 No
21 KITCHEN_FLR_6 103.30 22.2 4.645 0.215 10.979 517.156 2419.260 0.000 0.000 0.000 2947.395 No
22 CORRIDOR_FLR_6 412.12 22.2 18.581 5.382E-002 3.660 0.000 0.000 0.000 0.000 0.000 3.660 No


People Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Number of People {} People/Floor Area {person/m2} Floor Area per person {m2/person} Fraction Radiant Fraction Convected Sensible Fraction Calculation Activity level ASHRAE 55 Warnings Carbon Dioxide Generation Rate Nominal Minimum Number of People Nominal Maximum Number of People MRT Calculation Type Work Efficiency Clothing Insulation Calculation Method Clothing Insulation Calculation Method Schedule Clothing Air Velocity Fanger Calculation Pierce Calculation KSU Calculation Cooling Effect Calculation Ankle Draft Calculation
1 BASEMENT PEOPLE BLDG_OCC_SCH BASEMENT 1978.83 106.5 106.5 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 106 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
2 RETAIL_1_FLR_1 PEOPLE BLDG_OCC_SCH RETAIL_1_FLR_1 67.07 10.8 10.8 0.161 6.194 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
3 RETAIL_2_FLR_1 PEOPLE BLDG_OCC_SCH RETAIL_2_FLR_1 77.67 12.5 12.5 0.161 6.194 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 13 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
4 LAUNDRY_FLR_1 PEOPLE BLDG_OCC_SCH LAUNDRY_FLR_1 78.04 8.4 8.4 0.108 9.290 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 8 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
5 CAFE_FLR_1 PEOPLE BLDG_OCC_SCH CAFE_FLR_1 188.86 142.3 142.3 0.753 1.327 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 142 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
6 LOBBY_FLR_1 PEOPLE BLDG_OCC_SCH LOBBY_FLR_1 1308.19 422.4 422.4 0.323 3.097 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 422 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
7 ROOM_1_FLR_3 PEOPLE GUESTROOM_OCC_SCH ROOM_1_FLR_3 39.02 1.5 1.5 3.844E-002 26.015 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
8 ROOM_2_FLR_3 PEOPLE GUESTROOM_OCC_SCH ROOM_2_FLR_3 39.02 1.5 1.5 3.844E-002 26.012 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
9 ROOM_3_MULT19_FLR_3 PEOPLE ALWAYS_OFF ROOM_3_MULT19_FLR_3 24.52 1.5 1.5 6.116E-002 16.349 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 0 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
10 ROOM_4_MULT19_FLR_3 PEOPLE GUESTROOM_OCC_SCH ROOM_4_MULT19_FLR_3 24.53 1.5 1.5 6.115E-002 16.354 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
11 ROOM_5_FLR_3 PEOPLE GUESTROOM_OCC_SCH ROOM_5_FLR_3 39.02 1.5 1.5 3.844E-002 26.015 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
12 ROOM_6_FLR_3 PEOPLE GUESTROOM_OCC_SCH ROOM_6_FLR_3 39.02 1.5 1.5 3.844E-002 26.012 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
13 ROOM_1_FLR_6 PEOPLE GUESTROOM_OCC_SCH ROOM_1_FLR_6 39.02 1.5 1.5 3.844E-002 26.015 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
14 ROOM_2_FLR_6 PEOPLE GUESTROOM_OCC_SCH ROOM_2_FLR_6 39.02 1.5 1.5 3.844E-002 26.012 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
15 ROOM_3_MULT9_FLR_6 PEOPLE GUESTROOM_OCC_SCH ROOM_3_MULT9_FLR_6 24.53 1.5 1.5 6.115E-002 16.354 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
16 BANQUET_FLR_6 PEOPLE BLDG_OCC_SCH BANQUET_FLR_6 331.66 249.9 249.9 0.753 1.327 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 250 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
17 DINING_FLR_6 PEOPLE BLDG_OCC_SCH DINING_FLR_6 331.66 249.9 249.9 0.753 1.327 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 250 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
18 KITCHEN_FLR_6 PEOPLE BLDG_OCC_SCH KITCHEN_FLR_6 103.30 22.2 22.2 0.215 4.645 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 22 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
19 STORAGE_FLR_1 PEOPLE BLDG_OCC_SCH STORAGE_FLR_1 94.76 2.0 2.0 2.153E-002 46.451 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
20 CORRIDOR_FLR_3 PEOPLE BLDG_OCC_SCH CORRIDOR_FLR_3 389.40 21.0 21.0 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 21 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
21 CORRIDOR_FLR_6 PEOPLE BLDG_OCC_SCH CORRIDOR_FLR_6 412.12 22.2 22.2 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 22 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
22 MECH_FLR_1 PEOPLE BLDG_OCC_SCH MECH_FLR_1 164.24 2.7 2.7 1.615E-002 61.932 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 3 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No


Lights Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Lighting Level {W} Lights/Floor Area {W/m2} Lights per person {W/person} Fraction Return Air Fraction Radiant Fraction Short Wave Fraction Convected Fraction Replaceable End-Use Category Nominal Minimum Lighting Level {W} Nominal Maximum Lighting Level {W}
1 BASEMENT_LIGHTS LTG_SCH_BASEMENT BASEMENT 1978.83 106.5 17313.725 8.749 162.572 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 17313.725
2 RETAIL_1_FLR_1_LIGHTS LTG_SCH_RETAIL RETAIL_1_FLR_1 67.07 10.8 872.757 13.012 80.594 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 872.757
3 RETAIL_2_FLR_1_LIGHTS LTG_SCH_RETAIL RETAIL_2_FLR_1 77.67 12.5 1010.656 13.012 80.595 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1010.656
4 MECH_FLR_1_LIGHTS LTG_SCH_MECHANIC MECH_FLR_1 164.24 2.7 1652.984 10.064 623.297 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1652.984
5 STORAGE_FLR_1_LIGHTS LTG_SCH_STORAGE STORAGE_FLR_1 94.76 2.0 693.586 7.319 339.993 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 693.586
6 LAUNDRY_FLR_1_LIGHTS LTG_SCH_LAUNDRY LAUNDRY_FLR_1 78.04 8.4 428.405 5.490 51.001 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 428.405
7 CAFE_FLR_1_LIGHTS LTG_SCH_DINING CAFE_FLR_1 188.86 142.3 2419.140 12.809 17.000 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2419.140
8 LOBBY_FLR_1_LIGHTS LTG_SCH_LOBBY LOBBY_FLR_1 1308.19 422.4 13165.908 10.064 31.167 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 13165.908
9 ROOM_1_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_1_FLR_3 39.02 1.5 392.727 10.064 261.818 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 392.727
10 ROOM_2_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_2_FLR_3 39.02 1.5 392.681 10.064 261.787 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 392.681
11 ROOM_3_MULT19_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_3_MULT19_FLR_3 24.52 1.5 246.814 10.064 164.543 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 246.814
12 ROOM_4_MULT19_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_4_MULT19_FLR_3 24.53 1.5 246.881 10.064 164.588 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 246.881
13 ROOM_5_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_5_FLR_3 39.02 1.5 392.727 10.064 261.818 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 392.727
14 ROOM_6_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_6_FLR_3 39.02 1.5 392.681 10.064 261.787 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 392.681
15 CORRIDOR_FLR_3_LIGHTS LTG_SCH_CORRIDOR CORRIDOR_FLR_3 389.40 21.0 1425.114 3.660 68.002 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1425.114
16 ROOM_1_FLR_6_LIGHTS LTG_SCH_GUESTROOM ROOM_1_FLR_6 39.02 1.5 392.727 10.064 261.818 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 392.727
17 ROOM_2_FLR_6_LIGHTS LTG_SCH_GUESTROOM ROOM_2_FLR_6 39.02 1.5 392.681 10.064 261.787 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 392.681
18 ROOM_3_MULT9_FLR_6_LIGHTS LTG_SCH_GUESTROOM ROOM_3_MULT9_FLR_6 24.53 1.5 246.881 10.064 164.588 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 246.881
19 BANQUET_FLR_6_LIGHTS LTG_SCH_DINING BANQUET_FLR_6 331.66 249.9 4248.214 12.809 17.000 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 4248.214
20 DINING_FLR_6_LIGHTS LTG_SCH_DINING DINING_FLR_6 331.66 249.9 4248.214 12.809 17.000 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 4248.214
21 KITCHEN_FLR_6_LIGHTS LTG_SCH_KITCHEN KITCHEN_FLR_6 103.30 22.2 1134.198 10.979 51.003 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1134.198
22 CORRIDOR_FLR_6_LIGHTS LTG_SCH_CORRIDOR CORRIDOR_FLR_6 412.12 22.2 1508.264 3.660 68.001 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1508.264


ElectricEquipment Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Equipment Level {W} Equipment/Floor Area {W/m2} Equipment per person {W/person} Fraction Latent Fraction Radiant Fraction Lost Fraction Convected End-Use SubCategory Nominal Minimum Equipment Level {W} Nominal Maximum Equipment Level {W}
1 BASEMENT_MISCPLUG_EQUIP BASEMENT_EQUIP_SCH BASEMENT 1978.83 106.5 10646.106 5.380 99.964 0.000 0.500 0.000 0.500 MiscPlug 0.000 10646.106
2 RETAIL_1_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH RETAIL_1_FLR_1 67.07 10.8 721.688 10.760 66.644 0.000 0.500 0.000 0.500 MiscPlug 0.000 721.688
3 RETAIL_2_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH RETAIL_2_FLR_1 77.67 12.5 835.717 10.760 66.644 0.000 0.500 0.000 0.500 MiscPlug 0.000 835.717
4 MECH_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH MECH_FLR_1 164.24 2.7 883.628 5.380 333.193 0.000 0.500 0.000 0.500 MiscPlug 0.000 883.628
5 STORAGE_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH STORAGE_FLR_1 94.76 2.0 254.902 2.690 124.952 0.000 0.500 0.000 0.500 MiscPlug 0.000 254.902
6 LAUNDRY_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH LAUNDRY_FLR_1 78.04 8.4 4813.474 61.680 573.033 0.000 0.500 0.000 0.500 MiscPlug 0.000 4813.474
7 CAFE_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH CAFE_FLR_1 188.86 142.3 1016.077 5.380 7.140 0.000 0.500 0.000 0.500 MiscPlug 0.000 1016.077
8 LOBBY_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH LOBBY_FLR_1 1308.19 422.4 10557.062 8.070 24.991 0.000 0.500 0.000 0.500 MiscPlug 0.000 10557.062
9 ROOM_1_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_BASE ROOM_1_FLR_3 39.02 1.5 263.399 6.750 175.599 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.399
10 ROOM_2_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_BASE ROOM_2_FLR_3 39.02 1.5 263.368 6.750 175.579 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.368
11 ROOM_3_MULT19_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_BASE ROOM_3_MULT19_FLR_3 24.52 1.5 257.991 10.520 171.994 0.000 0.500 0.000 0.500 MiscPlug 0.000 257.991
12 ROOM_4_MULT19_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_BASE ROOM_4_MULT19_FLR_3 24.53 1.5 258.061 10.520 172.041 0.000 0.500 0.000 0.500 MiscPlug 0.000 258.061
13 ROOM_5_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_BASE ROOM_5_FLR_3 39.02 1.5 263.399 6.750 175.599 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.399
14 ROOM_6_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_BASE ROOM_6_FLR_3 39.02 1.5 263.368 6.750 175.579 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.368
15 ROOM_1_FLR_6_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_BASE ROOM_1_FLR_6 39.02 1.5 263.399 6.750 175.599 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.399
16 ROOM_2_FLR_6_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_BASE ROOM_2_FLR_6 39.02 1.5 263.368 6.750 175.579 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.368
17 ROOM_3_MULT9_FLR_6_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_BASE ROOM_3_MULT9_FLR_6 24.53 1.5 258.061 10.520 172.041 0.000 0.500 0.000 0.500 MiscPlug 0.000 258.061
18 BANQUET_FLR_6_MISCPLUG_EQUIP KITCHEN_ELEC_EQUIP_SCH BANQUET_FLR_6 331.66 249.9 22493.008 67.820 90.009 0.000 0.500 0.000 0.500 Cooking 0.000 6747.903
19 DINING_FLR_6_MISCPLUG_EQUIP KITCHEN_ELEC_EQUIP_SCH DINING_FLR_6 331.66 249.9 22493.008 67.820 90.009 0.000 0.500 0.000 0.500 Cooking 0.000 6747.903
20 KITCHEN_FLR_6_MISCELEC_EQUIP KITCHEN_ELEC_EQUIP_SCH KITCHEN_FLR_6 103.30 22.2 52482.799 508.040 2360.050 0.200 0.500 0.100 0.200 Cooking 0.000 15744.840
21 KITCHEN_FLR_6_REACH-IN-FREEZER ALWAYS_ON KITCHEN_FLR_6 103.30 22.2 515.917 4.994 23.200 0.000 0.250 0.000 0.750 ReachInFreezer 515.917 515.917
22 KITCHEN_FLR_6_REACH-IN-REFRIGERATOR ALWAYS_ON KITCHEN_FLR_6 103.30 22.2 425.833 4.122 19.149 0.000 0.250 0.000 0.750 ReachInRefrigerator 425.833 425.833


GasEquipment Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Equipment Level {W} Equipment/Floor Area {W/m2} Equipment per person {W/person} Fraction Latent Fraction Radiant Fraction Lost Fraction Convected End-Use SubCategory Nominal Minimum Equipment Level {W} Nominal Maximum Equipment Level {W}
1 LAUNDRY_FLR_1_MISCGAS_EQUIP BLDG_EQUIP_SCH LAUNDRY_FLR_1 78.04 8.4 41817.449 535.850 4978.268 0.000 0.500 0.000 0.500 Laundry 0.000 41817.449
2 KITCHEN_FLR_6_MISCGAS_EQUIP KITCHEN_GAS_EQUIP_SCH KITCHEN_FLR_6 103.30 22.2 249920.353 2419.260 11238.437 0.100 0.200 0.700 0.000 Cooking 0.000 74976.106


Construction CTF

Construction Name Index #Layers #CTFs Time Step {hours} ThermalConductance {w/m2-K} OuterThermalAbsorptance InnerThermalAbsorptance OuterSolarAbsorptance InnerSolarAbsorptance Roughness
1 SWINGING DOOR_CON 1 1 1 0.167 3.464 0.900 0.900 0.700 0.700 MediumRough
2 OVERHEAD DOOR_CON 2 1 1 0.167 1.198 0.900 0.900 0.700 0.700 MediumRough
3 INTERIORFURNISHINGS 3 1 9 0.167 0.8000 0.900 0.900 0.700 0.700 MediumSmooth
4 INT_WALL 8 2 4 0.167 6.299 0.900 0.900 0.700 0.700 Smooth
5 NONRES_ROOF 18 3 3 0.167 0.2832 0.750 0.900 0.450 0.700 Rough
6 RES_ROOF 19 3 3 0.167 0.2832 0.750 0.900 0.450 0.700 Rough
7 NONRES_EXT_WALL_GRD 21 3 9 0.167 1.214 0.900 0.900 0.700 0.700 MediumRough
8 NONRES_EXT_WALL_MID 22 3 9 0.167 1.530 0.900 0.900 0.700 0.700 MediumRough
9 NONRES_EXT_WALL_TOP 23 3 9 0.167 1.605 0.900 0.900 0.700 0.700 MediumRough
10 RES_EXT_WALL_MID 25 3 9 0.167 1.370 0.900 0.900 0.700 0.700 MediumRough
11 RES_EXT_WALL_TOP 26 3 9 0.167 1.442 0.900 0.900 0.700 0.700 MediumRough
12 NONRES_FLOOR 30 3 7 0.167 0.1963 0.900 0.900 0.700 0.700 MediumSmooth
13 NONRES_FLOOR_CEILING 33 3 7 0.167 0.1963 0.900 0.900 0.700 0.700 VeryRough
14 BASEMENT_FLOOR 36 2 7 0.333 2.705 0.900 0.900 0.700 0.700 MediumRough
15 BASEMENT_WALL_NORTH_CFACTOR 39 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough
16 BASEMENT_WALL_EAST_CFACTOR 40 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough
17 BASEMENT_WALL_SOUTH_CFACTOR 41 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough
18 BASEMENT_WALL_WEST_CFACTOR 42 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough


Material CTF Summary

Material Name Thickness {m} Conductivity {w/m-K} Density {kg/m3} Specific Heat {J/kg-K} ThermalResistance {m2-K/w}
1 OPAQUE DOOR PANEL_CON 0.0000 0.000 0.000 0.000 0.2887
2 OVERHEAD DOOR_CON PANEL 0.0000 0.000 0.000 0.000 0.8346
3 STD WOOD 6INCH 0.1500 0.120 540.000 1210.000 1.250
4 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
5 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
6 F13 BUILT-UP ROOFING 0.0095 0.160 1120.000 1460.000 0.5938E-01
7 NONRES_ROOF_INSULATION 0.0000 0.000 0.000 0.000 3.472
8 F08 METAL SURFACE 0.0008 45.280 7824.000 500.000 0.1767E-04
9 F13 BUILT-UP ROOFING 0.0095 0.160 1120.000 1460.000 0.5938E-01
10 RES_ROOF_INSULATION 0.0000 0.000 0.000 0.000 3.472
11 F08 METAL SURFACE 0.0008 45.280 7824.000 500.000 0.1767E-04
12 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
13 NONRES_EXTERIOR_WALL_INSULATION_GRD 0.0000 0.000 0.000 0.000 0.6561
14 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
15 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
16 NONRES_EXTERIOR_WALL_INSULATION_MID 0.0000 0.000 0.000 0.000 0.4862
17 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
18 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
19 NONRES_EXTERIOR_WALL_INSULATION_TOP 0.0000 0.000 0.000 0.000 0.4557
20 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
21 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
22 RES_EXTERIOR_WALL_INSULATION_MID 0.0000 0.000 0.000 0.000 0.5624
23 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
24 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
25 RES_EXTERIOR_WALL_INSULATION_TOP 0.0000 0.000 0.000 0.000 0.5260
26 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
27 NONRES_FLOOR_INSULATION 0.0000 0.000 0.000 0.000 4.833
28 100MM NORMALWEIGHT CONCRETE FLOOR 0.1016 2.310 2322.000 832.000 0.4398E-01
29 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
30 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
31 100MM NORMALWEIGHT CONCRETE FLOOR 0.1016 2.310 2322.000 832.000 0.4398E-01
32 NONRES_FLOOR_INSULATION 0.0000 0.000 0.000 0.000 4.833
33 M10 200MM CONCRETE BLOCK BASEMENT WALL 0.2032 1.326 1842.000 912.000 0.1532
34 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
35 ~FC_Insulation_1 0.0000 0.000 0.000 0.000 0.9868
36 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
37 ~FC_Insulation_2 0.0000 0.000 0.000 0.000 0.9868
38 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
39 ~FC_Insulation_3 0.0000 0.000 0.000 0.000 0.9868
40 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
41 ~FC_Insulation_4 0.0000 0.000 0.000 0.000 0.9868
42 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01


CTF

Time Outside Cross Inside Flux (except final one)
1 1 0.0000000 0.0000000 -0.0000000 -0.0000000
2 0 3.4637404 3.4637404 3.4637404  
3 1 0.0000000 0.0000000 -0.0000000 -0.0000000
4 0 1.1981135 1.1981135 1.1981135  
5 9 -0.27580628E-02 0.97439125E-12 -0.27580628E-02 0.28516790E-03
6 8 0.73590997E-01 0.21837543E-08 0.73590997E-01 -0.77836043E-02
7 7 -0.82599318 0.23162835E-06 -0.82599318 0.89703933E-01
8 6 5.1113916 0.48671053E-05 5.1113916 -0.57224845
9 5 -19.214933 0.30163627E-04 -19.214933 2.2266322
10 4 45.557404 0.63181060E-04 45.557404 -5.4853312
11 3 -68.275533 0.44785456E-04 -68.275533 8.5710568
12 2 62.555368 0.93952058E-05 62.555368 -8.2111738
13 1 -31.904423 0.39200004E-06 -31.904423 4.3886678
14 0 6.9260389 0.77047546E-09 6.9260389  
15 4 0.68458728E-09 0.26079551E-09 0.68458728E-09 -0.34507121E-18
16 3 -0.72180374E-03 0.24295686E-03 -0.72180374E-03 0.69691454E-09
17 2 0.83054762 0.27682775 0.83054762 -0.35168967E-03
18 1 -12.650482 3.3590720 -12.650482 0.19281313
19 0 16.907513 1.4507143 16.907513  
20 3 -0.61927053E-06 0.12767249E-08 -0.37968499E-05 0.16832131E-17
21 2 0.77611055 0.17315568E-02 1.0534842 -0.72792597E-06
22 1 -21.915918 0.11588205 -6.3286394 0.20197014
23 0 21.365777 0.10835518 5.5011278  
24 3 -0.61927053E-06 0.12767249E-08 -0.37968499E-05 0.16832131E-17
25 2 0.77611055 0.17315568E-02 1.0534842 -0.72792597E-06
26 1 -21.915918 0.11588205 -6.3286394 0.20197014
27 0 21.365777 0.10835518 5.5011278  
28 9 0.16334608E-14 0.44521285E-16 -0.13626018E-09 -0.55408550E-17
29 8 0.19978482E-07 0.16087698E-12 0.35757339E-03 -0.22716220E-09
30 7 -0.11637212E-01 0.85329953E-08 -0.22215339E-01 0.13231934E-03
31 6 0.38892783 0.29989280E-05 0.45807963 -0.45541807E-02
32 5 -5.0302817 0.11296145E-03 -4.3335362 0.61196441E-01
33 4 32.293780 0.93138689E-03 21.019023 -0.41270848
34 3 -109.71729 0.20442050E-02 -54.790969 1.4933949
35 2 195.63536 0.11570803E-02 77.111252 -2.8769641
36 1 -170.61189 0.12423857E-03 -55.033492 2.7359019
37 0 57.057407 0.71170334E-06 15.595873  
38 9 0.10594392E-14 0.47202510E-16 -0.12114953E-09 -0.13223917E-17
39 8 0.17843092E-07 0.19779160E-12 0.33399960E-03 -0.20288210E-09
40 7 -0.10929829E-01 0.10778020E-07 -0.21195485E-01 0.12427612E-03
41 6 0.36970129 0.38290923E-05 0.44160549 -0.43275484E-02
42 5 -4.8425837 0.14557296E-03 -4.2065674 0.58869135E-01
43 4 31.463113 0.12102446E-02 20.521745 -0.40168017
44 3 -107.94871 0.26756904E-02 -53.807411 1.4678460
45 2 193.88106 0.15243179E-02 76.211002 -2.8491083
46 1 -169.96333 0.16464538E-03 -54.775095 2.7245352
47 0 57.057407 0.94931294E-06 15.641308  
48 9 0.90003388E-15 0.50867187E-16 -0.11754631E-09 -0.30069304E-17
49 8 0.17333232E-07 0.20603527E-12 0.32823068E-03 -0.19708482E-09
50 7 -0.10756240E-01 0.11305735E-07 -0.20945040E-01 0.12230235E-03
51 6 0.36498247 0.40277709E-05 0.43754979 -0.42719257E-02
52 5 -4.7965079 0.15349109E-03 -4.1752560 0.58297839E-01
53 4 31.259149 0.12787761E-02 20.398993 -0.39897233
54 3 -107.51430 0.28324589E-02 -53.564574 1.4615707
55 2 193.44998 0.16162686E-02 75.988960 -2.8422636
56 1 -169.80390 0.17483991E-03 -54.711782 2.7217408
57 0 57.057407 0.10098010E-05 15.652787  
58 9 0.10314710E-14 0.47183642E-16 -0.12881513E-09 -0.40099708E-17
59 8 0.18927665E-07 0.17950474E-12 0.34608657E-03 -0.21521408E-09
60 7 -0.11292911E-01 0.96443222E-08 -0.21719088E-01 0.12840450E-03
61 6 0.37957032 0.34070209E-05 0.45007157 -0.44438791E-02
62 5 -4.9389364 0.12890179E-03 -4.2718596 0.60063826E-01
63 4 31.889569 0.10670331E-02 20.777560 -0.40734193
64 3 -108.85680 0.23501275E-02 -54.313423 1.4809641
65 2 194.78196 0.13343675E-02 76.673975 -2.8634131
66 1 -170.29645 0.14368413E-03 -54.907648 2.7303734
67 0 57.057407 0.82565881E-06 15.617726  
68 9 0.86975537E-15 0.52023775E-16 -0.12536948E-09 -0.54620444E-17
69 8 0.18440443E-07 0.18784465E-12 0.34068694E-03 -0.20967419E-09
70 7 -0.11130813E-01 0.10155400E-07 -0.21485363E-01 0.12656138E-03
71 6 0.37516444 0.35965268E-05 0.44629465 -0.43919449E-02
72 5 -4.8959230 0.13636263E-03 -4.2427425 0.59530495E-01
73 4 31.699203 0.11309484E-02 20.663505 -0.40481456
74 3 -108.45147 0.24950915E-02 -54.087828 1.4751087
75 2 194.37988 0.14187814E-02 76.467519 -2.8570287
76 1 -170.14779 0.15298304E-03 -54.848449 2.7277680
77 0 57.057407 0.88039223E-06 15.628184  
78 7 -0.15963512E-14 -0.15187529E-16 -0.22427203E-13 0.56155309E-15
79 6 0.17983713E-10 0.23594901E-11 0.52322926E-09 -0.18637893E-10
80 5 -0.60139213E-07 0.11510628E-07 -0.21924491E-05 0.17161312E-06
81 4 0.62746279E-04 0.43399923E-05 0.17681060E-02 -0.28244642E-03
82 3 -0.90508353E-02 0.15320797E-03 -0.21560640 0.43341486E-01
83 2 0.12836503 0.66328859E-03 2.9007871 -0.61911613
84 1 -0.32478029 0.41934727E-03 -7.1379041 1.5697129
85 0 0.20664896 0.54311639E-05 4.4522013  
86 7 -0.22427203E-13 -0.15187529E-16 -0.15963512E-14 0.56155309E-15
87 6 0.52322926E-09 0.23594901E-11 0.17983713E-10 -0.18637893E-10
88 5 -0.21924491E-05 0.11510628E-07 -0.60139213E-07 0.17161312E-06
89 4 0.17681060E-02 0.43399923E-05 0.62746279E-04 -0.28244642E-03
90 3 -0.21560640 0.15320797E-03 -0.90508353E-02 0.43341486E-01
91 2 2.9007871 0.66328859E-03 0.12836503 -0.61911613
92 1 -7.1379041 0.41934727E-03 -0.32478029 1.5697129
93 0 4.4522013 0.54311639E-05 0.20664896  
94 7 -0.52459208E-15 -0.63961428E-15 -0.12292524E-09 -0.35846135E-17
95 6 0.39860198E-02 0.96339020E-07 0.40499006E-03 -0.70890431E-04
96 5 -0.20832379 0.49172556E-04 -0.20585669E-01 0.38489246E-02
97 4 3.5198270 0.18993977E-02 0.34924834 -0.69168259E-01
98 3 -23.366787 0.13311857E-01 -2.4329538 0.50524779
99 2 64.890127 0.19943872E-01 7.3672511 -1.5911358
100 1 -76.040094 0.56792084E-02 -9.5568013 2.1361271
101 0 31.242244 0.96490710E-04 4.3344156  
102 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
103 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
104 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
105 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
106 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
107 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
108 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
109 0 1.0055995 0.48413807E-04 60.838472  
110 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
111 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
112 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
113 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
114 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
115 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
116 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
117 0 1.0055995 0.48413807E-04 60.838472  
118 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
119 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
120 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
121 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
122 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
123 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
124 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
125 0 1.0055995 0.48413807E-04 60.838472  
126 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
127 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
128 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
129 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
130 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
131 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
132 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
133 0 1.0055995 0.48413807E-04 60.838472  


WindowConstruction

Construction Name Index #Layers Roughness Conductance {W/m2-K} Conductance (Before Adjusted) {W/m2-K} Convection Coefficient Adjustment Ratio SHGC Solar Transmittance at Normal Incidence Visible Transmittance at Normal Incidence
1 NONRESWINDOW_U_0.5119_SHGC_0.25 37 1 VerySmooth 2.910 2.910 1.000 0.251    
2 RESWINDOW_U_0.5119_SHGC_0.25 38 1 VerySmooth 2.910 2.910 1.000 0.251    


WindowMaterial:Glazing

Material Name Optical Data Type Spectral Data Set Name Thickness {m} Solar Transmittance Front Solar Reflectance Back Solar Reflectance Visible Transmittance Front Visible Reflectance Back Visible Reflectance Infrared Transmittance Front Thermal Emissivity Back Thermal Emissivity Conductivity {W/m-K} Dirt Factor Solar Diffusing
1 GLAZING LAYER SpectralAverage   1.79780E-002 0.16139 0.60964 0.60964 0.25000 0.16143 0.23877 0.00000 0.84000 0.84000 0.10364 1.00000 No
2 RESIDENTIAL WINDOW GLAZING LAYER SpectralAverage   1.79780E-002 0.16139 0.60964 0.60964 0.25000 0.16143 0.23877 0.00000 0.84000 0.84000 0.10364 1.00000 No


Shadowing/Sun Position Calculations Annual Simulations

Shading Calculation Method Shading Calculation Update Frequency Method Shading Calculation Update Frequency {days} Maximum Figures in Shadow Overlap Calculations {} Polygon Clipping Algorithm Pixel Counting Resolution Sky Diffuse Modeling Algorithm Output External Shading Calculation Results Disable Self-Shading Within Shading Zone Groups Disable Self-Shading From Shading Zone Groups to Other Zones
1 PolygonClipping Periodic 7 15000 SutherlandHodgman 512 SimpleSkyDiffuseModeling No No No


#Refrigeration Compressor Racks

Number of Refrigeration Compressor Racks
1 2


Refrigeration Compressor Rack

Compressor Rack Name # Refrigerated Cases Connected # WalkIn Coolers Connected Heat Rejection Location Condenser Type COP
1 RACK1 1 0 Zone Air-Cooled 1.500
2 RACK2 1 0 Zone Air-Cooled 3.000


Water Heater Information

Type Name Volume {m3} Maximum Capacity {W} Standard Rated Recovery Efficiency Standard Rated Energy Factor
1 WaterHeater:Mixed SWH BOOSTER E WATER HEATER 2.2712E-002 8000.0 1.240 1.1473
2 WaterHeater:Mixed SWH LAUNDRY G WATER HEATER 1.1356 163316.0 0.576 0.5074
3 WaterHeater:Mixed SWHSYS1 WATER HEATER 2.2712 175842.6 0.260 2.5713E-002


Surface Convection Parameters

Surface Name Outside Model Assignment Outside Area [m2] Outside Perimeter [m] Outside Height [m] Inside Model Assignment Inside Height [m] Inside Perimeter Envelope [m] Inside Hydraulic Diameter [m] Window Wall Ratio Window Location Near Radiant {Yes/No} Has Active HVAC {Yes/No}
1 BASEMENT_WALL_NORTH 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
2 BASEMENT_WALL_EAST 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
3 BASEMENT_WALL_SOUTH 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
4 BASEMENT_WALL_WEST 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
5 BASEMENT_FLOOR 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
6 BASEMENT_CEILING_1 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
7 BASEMENT_CEILING_2 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
8 BASEMENT_CEILING_3 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
9 BASEMENT_CEILING_4 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
10 BASEMENT_CEILING_5 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
11 BASEMENT_CEILING_6 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
12 BASEMENT_CEILING_7 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
13 BASEMENT_CEILING_8 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
14 BASEMENT_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
15 RETAIL_1_FLR_1_WALL_SOUTH 0 506.51 211.91 19.20 0 3.96 17.37 7.72 0.34 4 No No
16 RETAIL_1_FLR_1_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.96 17.37 7.72 0.34 1 No No
17 RETAIL_1_FLR_1_WALL_WEST 0 194.63 84.12 19.20 0 3.96 17.37 7.72 0.34 3 No No
18 RETAIL_1_FLR_1_WALL_NORTH 0 0.00 0.00 0.00 0 3.96 17.37 7.72 0.34 0 No No
19 RETAIL_1_FLR_1_WALL_EAST 0 0.00 0.00 0.00 0 3.96 17.37 7.72 0.34 0 No No
20 RETAIL_1_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 17.37 7.72 0.34 0 No No
21 RETAIL_1_FLR_1_CEILING 0 1782.60 293.11 15.24 0 3.96 17.37 7.72 0.34 0 No No
22 RETAIL_1_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 17.37 7.72 0.34 0 No No
23 RETAIL_2_FLR_1_WALL_WEST 0 194.63 84.12 19.20 0 3.96 6.71 8.49 0.00 0 No No
24 RETAIL_2_FLR_1_WALL_WEST_DOOR 0 194.63 84.12 19.20 0 3.96 6.71 8.49 0.00 0 No No
25 RETAIL_2_FLR_1_WALL_SOUTH 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
26 RETAIL_2_FLR_1_WALL_NORTH 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
27 RETAIL_2_FLR_1_WALL_EAST 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
28 RETAIL_2_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
29 RETAIL_2_FLR_1_CEILING 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
30 RETAIL_2_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
31 MECH_FLR_1_WALL_NORTH 0 670.01 217.46 19.20 0 3.96 15.85 12.53 0.00 0 No No
32 MECH_FLR_1_WALL_EAST 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
33 MECH_FLR_1_WALL_SOUTH 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
34 MECH_FLR_1_WALL_WEST 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
35 MECH_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
36 MECH_FLR_1_CEILING 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
37 MECH_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
38 STORAGE_FLR_1_WALL_NORTH 0 670.01 217.46 19.20 0 3.96 9.14 9.72 0.00 0 No No
39 STORAGE_FLR_1_WALL_NORTH_ROLLDOOR 0 670.01 217.46 19.20 0 3.96 9.14 9.72 0.00 0 No No
40 STORAGE_FLR_1_WALL_EAST 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
41 STORAGE_FLR_1_WALL_SOUTH 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
42 STORAGE_FLR_1_WALL_WEST 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
43 STORAGE_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
44 STORAGE_FLR_1_CEILING 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
45 STORAGE_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
46 LAUNDRY_FLR_1_WALL_NORTH 0 670.01 217.46 19.20 0 3.96 21.64 7.21 0.00 0 No No
47 LAUNDRY_FLR_1_WALL_EAST 0 194.63 217.46 19.20 0 3.96 21.64 7.21 0.00 0 No No
48 LAUNDRY_FLR_1_WALL_EAST_DOOR 0 194.63 217.46 19.20 0 3.96 21.64 7.21 0.00 0 No No
49 LAUNDRY_FLR_1_WALL_SOUTH 0 0.00 0.00 0.00 0 3.96 21.64 7.21 0.00 0 No No
50 LAUNDRY_FLR_1_WALL_WEST 0 0.00 0.00 0.00 0 3.96 21.64 7.21 0.00 0 No No
51 LAUNDRY_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 21.64 7.21 0.00 0 No No
52 LAUNDRY_FLR_1_CEILING 0 0.00 0.00 0.00 0 3.96 21.64 7.21 0.00 0 No No
53 LAUNDRY_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 21.64 7.21 0.00 0 No No
54 CAFE_FLR_1_WALL_EAST 0 194.63 217.46 19.20 0 3.96 38.40 9.84 0.43 3 No No
55 CAFE_FLR_1_WALL_EAST_DOOR 0 194.63 217.46 19.20 0 3.96 38.40 9.84 0.43 0 No No
56 CAFE_FLR_1_WALL_SOUTH 0 506.51 211.91 19.20 0 3.96 38.40 9.84 0.43 4 No No
57 CAFE_FLR_1_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.96 38.40 9.84 0.43 1 No No
58 CAFE_FLR_1_WALL_1_NORTH 0 0.00 0.00 0.00 0 3.96 38.40 9.84 0.43 0 No No
59 CAFE_FLR_1_WALL_2_NORTH 0 0.00 0.00 0.00 0 3.96 38.40 9.84 0.43 0 No No
60 CAFE_FLR_1_WALL_WEST 0 0.00 0.00 0.00 0 3.96 38.40 9.84 0.43 0 No No
61 CAFE_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 38.40 9.84 0.43 0 No No
62 CAFE_FLR_1_CEILING 0 1782.60 293.11 15.24 0 3.96 38.40 9.84 0.43 0 No No
63 CAFE_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 38.40 9.84 0.43 0 No No
64 LOBBY_FLR_1_WALL_1_NORTH 0 670.01 217.46 19.20 0 3.96 109.73 24.95 0.20 3 No No
65 LOBBY_FLR_1_WALL_1_NORTH_DOOR1 0 670.01 217.46 19.20 0 3.96 109.73 24.95 0.20 0 No No
66 LOBBY_FLR_1_WALL_1_NORTH_DOOR2 0 670.01 217.46 19.20 0 3.96 109.73 24.95 0.20 0 No No
67 LOBBY_FLR_1_WALL_2_NORTH 0 670.01 217.46 19.20 0 3.96 109.73 24.95 0.20 4 No No
68 LOBBY_FLR_1_WALL_1_SOUTH 0 506.51 211.91 19.20 0 3.96 109.73 24.95 0.20 4 No No
69 LOBBY_FLR_1_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.96 109.73 24.95 0.20 1 No No
70 LOBBY_FLR_1_WALL_1_WEST 0 194.63 84.12 19.20 0 3.96 109.73 24.95 0.20 3 No No
71 LOBBY_FLR_1_WALL_2_SOUTH 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
72 LOBBY_FLR_1_WALL_3_SOUTH 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
73 LOBBY_FLR_1_WALL_2_WEST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
74 LOBBY_FLR_1_WALL_3_WEST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
75 LOBBY_FLR_1_WALL_4_WEST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
76 LOBBY_FLR_1_WALL_3_NORTH 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
77 LOBBY_FLR_1_WALL_4_NORTH 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
78 LOBBY_FLR_1_WALL_1_EAST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
79 LOBBY_FLR_1_WALL_2_EAST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
80 LOBBY_FLR_1_WALL_3_EAST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
81 LOBBY_FLR_1_FLOOR_1 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
82 LOBBY_FLR_1_FLOOR_2 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
83 LOBBY_FLR_1_CEILING_1 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
84 LOBBY_FLR_1_CEILING_2 0 1782.60 293.11 15.24 0 3.96 109.73 24.95 0.20 0 No No
85 LOBBY_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
86 ROOM_1_FLR_3_WALL_SOUTH 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 3 No No
87 ROOM_1_FLR_3_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 2 No No
88 ROOM_1_FLR_3_WALL_WEST 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 3 No No
89 ROOM_1_FLR_3_WALL_WEST_WINDOW 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 2 No No
90 ROOM_1_FLR_3_WALL_NORTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
91 ROOM_1_FLR_3_WALL_EAST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
92 ROOM_1_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
93 ROOM_1_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
94 ROOM_1_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
95 ROOM_2_FLR_3_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 3 No No
96 ROOM_2_FLR_3_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 2 No No
97 ROOM_2_FLR_3_WALL_WEST 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 3 No No
98 ROOM_2_FLR_3_WALL_WEST_WINDOW 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 2 No No
99 ROOM_2_FLR_3_WALL_EAST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
100 ROOM_2_FLR_3_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
101 ROOM_2_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
102 ROOM_2_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
103 ROOM_2_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
104 ROOM_3_MULT19_FLR_3_WALL_SOUTH 0 506.51 211.91 19.20 0 3.05 3.66 4.73 0.33 3 No No
105 ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 3.66 4.73 0.33 2 No No
106 ROOM_3_MULT19_FLR_3_WALL_NORTH 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
107 ROOM_3_MULT19_FLR_3_WALL_EAST 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
108 ROOM_3_MULT19_FLR_3_WALL_WEST 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
109 ROOM_3_MULT19_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
110 ROOM_3_MULT19_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
111 ROOM_3_MULT19_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
112 ROOM_4_MULT19_FLR_3_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 3.66 4.73 0.33 3 No No
113 ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 3.66 4.73 0.33 2 No No
114 ROOM_4_MULT19_FLR_3_WALL_EAST 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
115 ROOM_4_MULT19_FLR_3_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
116 ROOM_4_MULT19_FLR_3_WALL_WEST 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
117 ROOM_4_MULT19_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
118 ROOM_4_MULT19_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
119 ROOM_4_MULT19_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
120 ROOM_5_FLR_3_WALL_EAST 0 194.63 217.46 19.20 0 3.05 13.11 5.95 0.33 3 No No
121 ROOM_5_FLR_3_WALL_EAST_WINDOW 0 194.63 217.46 19.20 0 3.05 13.11 5.95 0.33 2 No No
122 ROOM_5_FLR_3_WALL_SOUTH 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 3 No No
123 ROOM_5_FLR_3_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 2 No No
124 ROOM_5_FLR_3_WALL_NORTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
125 ROOM_5_FLR_3_WALL_WEST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
126 ROOM_5_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
127 ROOM_5_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
128 ROOM_5_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
129 ROOM_6_FLR_3_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 3 No No
130 ROOM_6_FLR_3_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 2 No No
131 ROOM_6_FLR_3_WALL_EAST 0 194.63 217.46 19.20 0 3.05 13.11 5.95 0.33 3 No No
132 ROOM_6_FLR_3_WALL_EAST_WINDOW 0 194.63 217.46 19.20 0 3.05 13.11 5.95 0.33 2 No No
133 ROOM_6_FLR_3_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
134 ROOM_6_FLR_3_WALL_WEST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
135 ROOM_6_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
136 ROOM_6_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
137 ROOM_6_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
138 CORRIDOR_FLR_3_WALL_1_NORTH 0 670.01 217.46 19.20 0 3.05 15.85 8.24 0.33 3 No No
139 CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 15.85 8.24 0.33 2 No No
140 CORRIDOR_FLR_3_WALL_2_NORTH 0 670.01 217.46 19.20 0 3.05 15.85 8.24 0.33 3 No No
141 CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 15.85 8.24 0.33 2 No No
142 CORRIDOR_FLR_3_WALL_1_SOUTH 0 506.51 211.91 19.20 0 3.05 15.85 8.24 0.33 3 No No
143 CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 15.85 8.24 0.33 2 No No
144 CORRIDOR_FLR_3_WALL_2_SOUTH 0 506.51 211.91 19.20 0 3.05 15.85 8.24 0.33 3 No No
145 CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 15.85 8.24 0.33 2 No No
146 CORRIDOR_FLR_3_WALL_3_NORTH 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
147 CORRIDOR_FLR_3_WALL_1_EAST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
148 CORRIDOR_FLR_3_WALL_2_EAST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
149 CORRIDOR_FLR_3_WALL_3_EAST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
150 CORRIDOR_FLR_3_WALL_4_EAST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
151 CORRIDOR_FLR_3_WALL_3_SOUTH 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
152 CORRIDOR_FLR_3_WALL_1_WEST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
153 CORRIDOR_FLR_3_WALL_2_WEST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
154 CORRIDOR_FLR_3_WALL_3_WEST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
155 CORRIDOR_FLR_3_WALL_4_WEST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
156 CORRIDOR_FLR_3_FLOOR_1 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
157 CORRIDOR_FLR_3_FLOOR_2 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
158 CORRIDOR_FLR_3_FLOOR_3 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
159 CORRIDOR_FLR_3_CEILING_1 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
160 CORRIDOR_FLR_3_CEILING_2 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
161 CORRIDOR_FLR_3_CEILING_3 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
162 CORRIDOR_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
163 ROOM_1_FLR_6_WALL_SOUTH 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 3 No No
164 ROOM_1_FLR_6_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 2 No No
165 ROOM_1_FLR_6_WALL_WEST 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 3 No No
166 ROOM_1_FLR_6_WALL_WEST_WINDOW 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 2 No No
167 ROOM_1_FLR_6_WALL_NORTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
168 ROOM_1_FLR_6_WALL_EAST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
169 ROOM_1_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
170 ROOM_1_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 13.11 5.95 0.33 0 No No
171 ROOM_1_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
172 ROOM_2_FLR_6_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 3 No No
173 ROOM_2_FLR_6_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 2 No No
174 ROOM_2_FLR_6_WALL_WEST 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 3 No No
175 ROOM_2_FLR_6_WALL_WEST_WINDOW 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 2 No No
176 ROOM_2_FLR_6_WALL_EAST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
177 ROOM_2_FLR_6_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
178 ROOM_2_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
179 ROOM_2_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 13.11 5.95 0.33 0 No No
180 ROOM_2_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
181 ROOM_3_MULT9_FLR_6_WALL_SOUTH 0 506.51 211.91 19.20 0 3.05 6.71 4.73 0.33 3 No No
182 ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 6.71 4.73 0.33 2 No No
183 ROOM_3_MULT9_FLR_6_WALL_NORTH 0 0.00 0.00 0.00 0 3.05 6.71 4.73 0.33 0 No No
184 ROOM_3_MULT9_FLR_6_WALL_EAST 0 0.00 0.00 0.00 0 3.05 6.71 4.73 0.33 0 No No
185 ROOM_3_MULT9_FLR_6_WALL_WEST 0 0.00 0.00 0.00 0 3.05 6.71 4.73 0.33 0 No No
186 ROOM_3_MULT9_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 6.71 4.73 0.33 0 No No
187 ROOM_3_MULT9_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 6.71 4.73 0.33 0 No No
188 ROOM_3_MULT9_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 6.71 4.73 0.33 0 No No
189 BANQUET_FLR_6_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 32.00 15.66 0.33 3 No No
190 BANQUET_FLR_6_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 32.00 15.66 0.33 2 No No
191 BANQUET_FLR_6_WALL_EAST 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
192 BANQUET_FLR_6_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
193 BANQUET_FLR_6_WALL_WEST 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
194 BANQUET_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
195 BANQUET_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 32.00 15.66 0.33 0 No No
196 BANQUET_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
197 DINING_FLR_6_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 32.00 15.66 0.33 3 No No
198 DINING_FLR_6_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 32.00 15.66 0.33 2 No No
199 DINING_FLR_6_WALL_EAST 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
200 DINING_FLR_6_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
201 DINING_FLR_6_WALL_WEST 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
202 DINING_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
203 DINING_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 32.00 15.66 0.33 0 No No
204 DINING_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
205 KITCHEN_FLR_6_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 28.65 8.58 0.30 3 No No
206 KITCHEN_FLR_6_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 28.65 8.58 0.30 2 No No
207 KITCHEN_FLR_6_WALL_EAST 0 194.63 217.46 19.20 0 3.05 28.65 8.58 0.30 3 No No
208 KITCHEN_FLR_6_WALL_EAST_WINDOW 0 194.63 217.46 19.20 0 3.05 28.65 8.58 0.30 2 No No
209 KITCHEN_FLR_6_WALL_1_SOUTH 0 506.51 211.91 19.20 0 3.05 28.65 8.58 0.30 3 No No
210 KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 28.65 8.58 0.30 2 No No
211 KITCHEN_FLR_6_WALL_2_SOUTH 0 0.00 0.00 0.00 0 3.05 28.65 8.58 0.30 0 No No
212 KITCHEN_FLR_6_WALL_1_WEST 0 0.00 0.00 0.00 0 3.05 28.65 8.58 0.30 0 No No
213 KITCHEN_FLR_6_WALL_2_WEST 0 0.00 0.00 0.00 0 3.05 28.65 8.58 0.30 0 No No
214 KITCHEN_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 28.65 8.58 0.30 0 No No
215 KITCHEN_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 28.65 8.58 0.30 0 No No
216 KITCHEN_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 28.65 8.58 0.30 0 No No
217 CORRIDOR_FLR_6_WALL_1_NORTH 0 670.01 217.46 19.20 0 3.05 28.04 8.72 0.33 3 No No
218 CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 28.04 8.72 0.33 2 No No
219 CORRIDOR_FLR_6_WALL_2_NORTH 0 670.01 217.46 19.20 0 3.05 28.04 8.72 0.33 3 No No
220 CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 28.04 8.72 0.33 2 No No
221 CORRIDOR_FLR_6_WALL_2_SOUTH 0 506.51 211.91 19.20 0 3.05 28.04 8.72 0.33 3 No No
222 CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 28.04 8.72 0.33 2 No No
223 CORRIDOR_FLR_6_WALL_3_NORTH 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
224 CORRIDOR_FLR_6_WALL_4_NORTH 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
225 CORRIDOR_FLR_6_WALL_1_SOUTH 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
226 CORRIDOR_FLR_6_WALL_1_WEST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
227 CORRIDOR_FLR_6_WALL_2_WEST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
228 CORRIDOR_FLR_6_WALL_3_WEST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
229 CORRIDOR_FLR_6_WALL_1_EAST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
230 CORRIDOR_FLR_6_WALL_2_EAST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
231 CORRIDOR_FLR_6_WALL_3_EAST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
232 CORRIDOR_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
233 CORRIDOR_FLR_6_CEILING_1 0 1782.60 293.11 15.24 0 3.05 28.04 8.72 0.33 0 No No
234 CORRIDOR_FLR_6_CEILING_2 0 1782.60 293.11 15.24 0 3.05 28.04 8.72 0.33 0 No No
235 CORRIDOR_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No


ZoneInfiltration Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Design Volume Flow Rate {m3/s} Volume Flow Rate/Floor Area {m3/s-m2} Volume Flow Rate/Exterior Surface Area {m3/s-m2} ACH - Air Changes per Hour Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2}
1 RETAIL_1_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH RETAIL_1_FLR_1 67.07 10.8 7.058E-002 1.052E-003 5.193E-004 0.956 1.000 0.000 0.000 0.000
2 RETAIL_2_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH RETAIL_2_FLR_1 77.67 12.5 2.724E-002 3.507E-004 9.551E-004 0.319 1.000 0.000 0.000 0.000
3 MECH_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH MECH_FLR_1 164.24 2.7 6.438E-002 3.920E-004 1.025E-003 0.356 1.000 0.000 0.000 0.000
4 STORAGE_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH STORAGE_FLR_1 94.76 2.0 3.715E-002 3.920E-004 8.507E-004 0.356 1.000 0.000 0.000 0.000
5 LAUNDRY_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH LAUNDRY_FLR_1 78.04 8.4 8.791E-002 1.127E-003 1.002E-003 1.023 1.000 0.000 0.000 0.000
6 CAFE_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH CAFE_FLR_1 188.86 142.3 0.156 8.261E-004 4.549E-004 0.751 1.000 0.000 0.000 0.000
7 LOBBY_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH LOBBY_FLR_1 1308.19 422.4 0.446 3.407E-004 6.517E-004 0.310 1.000 0.000 0.000 0.000
8 ROOM_1_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_1_FLR_3 39.02 1.5 4.096E-002 1.050E-003 1.025E-003 1.240 1.000 0.000 0.000 0.000
9 ROOM_2_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_2_FLR_3 39.02 1.5 4.095E-002 1.050E-003 1.025E-003 1.240 1.000 0.000 0.000 0.000
10 ROOM_3_MULT19_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_3_MULT19_FLR_3 24.52 1.5 1.143E-002 4.660E-004 1.025E-003 0.550 1.000 0.000 0.000 0.000
11 ROOM_4_MULT19_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_4_MULT19_FLR_3 24.53 1.5 1.143E-002 4.660E-004 1.025E-003 0.550 1.000 0.000 0.000 0.000
12 ROOM_5_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_5_FLR_3 39.02 1.5 4.096E-002 1.050E-003 1.025E-003 1.240 1.000 0.000 0.000 0.000
13 ROOM_6_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_6_FLR_3 39.02 1.5 4.095E-002 1.050E-003 1.025E-003 1.240 1.000 0.000 0.000 0.000
14 CORRIDOR_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH CORRIDOR_FLR_3 389.40 21.0 4.953E-002 1.272E-004 1.025E-003 0.150 1.000 0.000 0.000 0.000
15 ROOM_1_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_1_FLR_6 39.02 1.5 4.096E-002 1.050E-003 5.186E-004 1.240 1.000 0.000 0.000 0.000
16 ROOM_2_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_2_FLR_6 39.02 1.5 4.095E-002 1.050E-003 5.186E-004 1.240 1.000 0.000 0.000 0.000
17 ROOM_3_MULT9_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_3_MULT9_FLR_6 24.53 1.5 2.096E-002 8.543E-004 4.660E-004 1.009 1.000 0.000 0.000 0.000
18 BANQUET_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH BANQUET_FLR_6 331.66 249.9 0.100 3.015E-004 2.330E-004 0.356 1.000 0.000 0.000 0.000
19 DINING_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH DINING_FLR_6 331.66 249.9 0.100 3.015E-004 2.330E-004 0.356 1.000 0.000 0.000 0.000
20 KITCHEN_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH KITCHEN_FLR_6 103.30 22.2 8.953E-002 8.667E-004 4.697E-004 1.024 1.000 0.000 0.000 0.000
21 CORRIDOR_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH CORRIDOR_FLR_6 412.12 22.2 8.763E-002 2.126E-004 1.761E-004 0.251 1.000 0.000 0.000 0.000


ZoneVentilation Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Design Volume Flow Rate {m3/s} Volume Flow Rate/Floor Area {m3/s-m2} Volume Flow Rate/person Area {m3/s-person} ACH - Air Changes per Hour Fan Type {Exhaust;Intake;Natural} Fan Pressure Rise {Pa} Fan Efficiency {} Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2} Minimum Indoor Temperature{C}/Schedule Maximum Indoor Temperature{C}/Schedule Delta Temperature{C}/Schedule Minimum Outdoor Temperature{C}/Schedule Maximum Outdoor Temperature{C}/Schedule Maximum WindSpeed{m/s}
1 ROOM_1_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_1_FLR_3 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
2 ROOM_2_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_2_FLR_3 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
3 ROOM_3_MULT19_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_3_MULT19_FLR_3 24.52 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
4 ROOM_4_MULT19_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_4_MULT19_FLR_3 24.53 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
5 ROOM_5_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_5_FLR_3 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
6 ROOM_6_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_6_FLR_3 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
7 ROOM_1_FLR_6 SLIDING DOOR VENTILATION Constant-0.0 ROOM_1_FLR_6 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
8 ROOM_2_FLR_6 SLIDING DOOR VENTILATION Constant-0.0 ROOM_2_FLR_6 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
9 ROOM_3_MULT9_FLR_6 SLIDING DOOR VENTILATION Constant-0.0 ROOM_3_MULT9_FLR_6 24.53 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00


AirFlow Model

Simple
1 Simple


RoomAir Model

Zone Name Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined
1 BASEMENT Mixing/Well-Stirred
2 RETAIL_1_FLR_1 Mixing/Well-Stirred
3 RETAIL_2_FLR_1 Mixing/Well-Stirred
4 MECH_FLR_1 Mixing/Well-Stirred
5 STORAGE_FLR_1 Mixing/Well-Stirred
6 LAUNDRY_FLR_1 Mixing/Well-Stirred
7 CAFE_FLR_1 Mixing/Well-Stirred
8 LOBBY_FLR_1 Mixing/Well-Stirred
9 ROOM_1_FLR_3 Mixing/Well-Stirred
10 ROOM_2_FLR_3 Mixing/Well-Stirred
11 ROOM_3_MULT19_FLR_3 Mixing/Well-Stirred
12 ROOM_4_MULT19_FLR_3 Mixing/Well-Stirred
13 ROOM_5_FLR_3 Mixing/Well-Stirred
14 ROOM_6_FLR_3 Mixing/Well-Stirred
15 CORRIDOR_FLR_3 Mixing/Well-Stirred
16 ROOM_1_FLR_6 Mixing/Well-Stirred
17 ROOM_2_FLR_6 Mixing/Well-Stirred
18 ROOM_3_MULT9_FLR_6 Mixing/Well-Stirred
19 BANQUET_FLR_6 Mixing/Well-Stirred
20 DINING_FLR_6 Mixing/Well-Stirred
21 KITCHEN_FLR_6 Mixing/Well-Stirred
22 CORRIDOR_FLR_6 Mixing/Well-Stirred


AirflowNetwork Model:Control

No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation
1 NoMultizoneOrDistribution


Zone Volume Capacitance Multiplier

Sensible Heat Capacity Multiplier Moisture Capacity Multiplier Carbon Dioxide Capacity Multiplier Generic Contaminant Capacity Multiplier
1 1.000 1.000 1.000 1.000


Load Timesteps in Zone Design Calculation Averaging Window

Value
1 6


Heating Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Cooling Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Zone Sizing Information

Zone Name Load Type Calc Des Load {W} User Des Load {W} Calc Des Air Flow Rate {m3/s} User Des Air Flow Rate {m3/s} Design Day Name Date/Time of Peak Temperature at Peak {C} Humidity Ratio at Peak {kgWater/kgDryAir} Floor Area {m2} # Occupants Calc Outdoor Air Flow Rate {m3/s} Calc DOAS Heat Addition Rate {W}
1 BASEMENT Cooling 35904.54887 35904.54887 2.87356 2.87356 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 21:20:00 32.55400 5.61839E-003 1978.83018 106.49900 0.85446 0.00000
2 BASEMENT Heating 0.00000 0.00000 0.00000 0.85446   00:10:00 0.50000 4.31558E-003 1978.83018 106.49900 0.85446 0.00000
3 RETAIL_1_FLR_1 Cooling 4989.32668 4989.32668 0.39933 0.39933 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:10:00 40.80000 5.63111E-003 67.07136 10.82900 7.92179E-002 0.00000
4 RETAIL_1_FLR_1 Heating 2565.49011 2565.49011 0.12112 0.12112 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 0.50000 4.31558E-003 67.07136 10.82900 7.92179E-002 0.00000
5 RETAIL_2_FLR_1 Cooling 3535.21608 3535.21608 0.28296 0.28296 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:50:00 37.82967 5.62649E-003 77.66889 12.54000 9.17347E-002 0.00000
6 RETAIL_2_FLR_1 Heating 855.40626 855.40626 4.03864E-002 9.17347E-002 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 0.50000 4.31558E-003 77.66889 12.54000 9.17347E-002 0.00000
7 MECH_FLR_1 Cooling 3901.18837 3901.18837 0.31218 0.31218 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:20:00 36.94300 5.62512E-003 164.24319 2.65200 0.00000 0.00000
8 MECH_FLR_1 Heating 1614.01954 1614.01954 7.62028E-002 7.62028E-002 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 0.50000 4.31558E-003 164.24319 2.65200 0.00000 0.00000
9 STORAGE_FLR_1 Cooling 1976.34285 1976.34285 0.15815 0.15815 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:40:00 38.05133 5.62683E-003 94.75927 2.04000 5.77652E-002 0.00000
10 STORAGE_FLR_1 Heating 945.03119 945.03119 4.46178E-002 5.77652E-002 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 0.50000 4.31558E-003 94.75927 2.04000 5.77652E-002 0.00000
11 LAUNDRY_FLR_1 Cooling 45529.25143 45529.25143 3.64363 3.64363 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:50:00 40.13500 5.63007E-003 78.03947 8.40000 0.00000 0.00000
12 LAUNDRY_FLR_1 Heating 2173.14490 2173.14490 0.10260 0.10260 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 0.50000 4.31558E-003 78.03947 8.40000 0.00000 0.00000
13 CAFE_FLR_1 Cooling 20584.82554 20584.82554 1.64895 1.64895 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:10:00 40.80000 5.63111E-003 188.86188 142.30000 0.67639 0.00000
14 CAFE_FLR_1 Heating 6396.48027 6396.48027 0.30199 0.67639 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 0.50000 4.31558E-003 188.86188 142.30000 0.67639 0.00000
15 LOBBY_FLR_1 Cooling 67372.31625 67372.31625 5.39407 5.39407 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 40.80000 5.63111E-003 1308.18612 422.43500 1.89399 0.00000
16 LOBBY_FLR_1 Heating 15084.58628 15084.58628 0.71219 1.89399 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 0.50000 4.31558E-003 1308.18612 422.43500 1.89399 0.00000
17 ROOM_1_FLR_3 Cooling 12121.14482 12121.14482 1.30711 1.30711 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:50:00 39.11533 5.62848E-003 39.02202 1.50000 6.17350E-002 0.00000
18 ROOM_1_FLR_3 Heating 5573.54986 5573.54986 0.26468 0.26468 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 0.50000 4.31558E-003 39.02202 1.50000 6.17350E-002 0.00000
19 ROOM_2_FLR_3 Cooling 12039.24020 12039.24020 1.29828 1.29828 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00 38.93800 5.62821E-003 39.01745 1.50000 6.17278E-002 0.00000
20 ROOM_2_FLR_3 Heating 5578.10891 5578.10891 0.26490 0.26490 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 0.50000 4.31558E-003 39.01745 1.50000 6.17278E-002 0.00000
21 ROOM_3_MULT19_FLR_3 Cooling 72732.87282 72732.87282 7.84323 7.84323 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 40.80000 5.63111E-003 24.52384 1.50000 0.83707 0.00000
22 ROOM_3_MULT19_FLR_3 Heating 32043.09334 32043.09334 1.52173 1.52173 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 0.50000 4.31558E-003 24.52384 1.50000 0.83707 0.00000
23 ROOM_4_MULT19_FLR_3 Cooling 77647.06663 77647.06663 8.37380 8.37380 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:40:00 40.26800 5.63027E-003 24.53055 1.50000 0.83730 0.00000
24 ROOM_4_MULT19_FLR_3 Heating 32147.16108 32147.16108 1.52667 1.52667 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 0.50000 4.31558E-003 24.53055 1.50000 0.83730 0.00000
25 ROOM_5_FLR_3 Cooling 10670.43811 10670.43811 1.15067 1.15067 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:30:00 36.74350 5.62481E-003 39.02202 1.50000 6.17350E-002 0.00000
26 ROOM_5_FLR_3 Heating 5563.68222 5563.68222 0.26421 0.26421 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 0.50000 4.31558E-003 39.02202 1.50000 6.17350E-002 0.00000
27 ROOM_6_FLR_3 Cooling 10600.97546 10600.97546 1.14318 1.14318 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:20:00 36.41100 5.62429E-003 39.01745 1.50000 6.17278E-002 0.00000
28 ROOM_6_FLR_3 Heating 5568.24386 5568.24386 0.26443 0.26443 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 0.50000 4.31558E-003 39.01745 1.50000 6.17278E-002 0.00000
29 CORRIDOR_FLR_3 Cooling 17515.35684 17515.35684 1.40177 1.40177 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:30:00 40.40100 5.63048E-003 389.40468 20.95700 0.47476 0.00000
30 CORRIDOR_FLR_3 Heating 8844.66726 8844.66726 0.41759 0.47476 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 0.50000 4.31558E-003 389.40468 20.95700 0.47476 0.00000
31 ROOM_1_FLR_6 Cooling 3280.55095 3280.55095 0.35377 0.35377 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:50:00 39.11533 5.62848E-003 39.02202 1.50000 1.54338E-002 0.00000
32 ROOM_1_FLR_6 Heating 1729.37838 1729.37838 8.21257E-002 8.21257E-002 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 0.50000 4.31558E-003 39.02202 1.50000 1.54338E-002 0.00000
33 ROOM_2_FLR_6 Cooling 3256.18733 3256.18733 0.35114 0.35114 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:50:00 39.11533 5.62848E-003 39.01745 1.50000 1.54319E-002 0.00000
34 ROOM_2_FLR_6 Heating 1729.90738 1729.90738 8.21508E-002 8.21508E-002 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 0.50000 4.31558E-003 39.01745 1.50000 1.54319E-002 0.00000
35 ROOM_3_MULT9_FLR_6 Cooling 14743.42129 14743.42129 1.58995 1.58995 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 40.80000 5.63111E-003 24.53055 1.50000 9.91540E-002 0.00000
36 ROOM_3_MULT9_FLR_6 Heating 8347.59648 8347.59648 0.39642 0.39642 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 0.50000 4.31558E-003 24.53055 1.50000 9.91540E-002 0.00000
37 BANQUET_FLR_6 Cooling 32040.91967 32040.91967 2.56745 2.56745 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 40.80000 5.63111E-003 331.65745 249.89600 1.18780 0.00000
38 BANQUET_FLR_6 Heating 5903.54309 5903.54309 0.27872 1.18780 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 0.50000 4.31558E-003 331.65745 249.89600 1.18780 0.00000
39 DINING_FLR_6 Cooling 33562.09775 33562.09775 2.68931 2.68931 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 40.80000 5.63111E-003 331.65745 249.89600 1.18780 0.00000
40 DINING_FLR_6 Heating 6012.73059 6012.73059 0.28388 1.18780 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 19:10:00 0.50000 4.31558E-003 331.65745 249.89600 1.18780 0.00000
41 KITCHEN_FLR_6 Cooling 31785.95458 31785.95458 2.55057 2.55057 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 12:30:00 39.60300 5.62924E-003 103.30446 22.23800 0.36735 0.00000
42 KITCHEN_FLR_6 Heating 1286.91146 1286.91146 6.07509E-002 0.36735 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 23:30:00 0.50000 4.31558E-003 103.30446 22.23800 0.36735 0.00000
43 CORRIDOR_FLR_6 Cooling 10655.84965 10655.84965 0.85278 0.85278 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:50:00 40.80000 5.63111E-003 412.12471 22.18000 0.12562 0.00000
44 CORRIDOR_FLR_6 Heating 6247.85455 6247.85455 0.29498 0.29498 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 19:10:00 0.50000 4.31558E-003 412.12471 22.18000 0.12562 0.00000


System Sizing Information

System Name Load Type Peak Load Kind User Design Capacity Calc Des Air Flow Rate [m3/s] User Des Air Flow Rate [m3/s] Design Day Name Date/Time of Peak
1 VAV WITH REHEAT Cooling Sensible 758477.38 24.65939 24.65939 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 00:00:00
2 VAV WITH REHEAT Heating Sensible 131455.29 7.38688 7.38688 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 19:10:00
3 FLR_3_DOAS Cooling Sensible 63092.52 22.92702 2.05125 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 00:00:00
4 FLR_3_DOAS Heating Sensible 36503.53 4.66732 2.05125 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00


Component Sizing Information

Component Type Component Name Input Field Description Value
1 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.87356
2 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.52474
3 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.99500
4 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 2.85919
5 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
6 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
7 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 7.26076E-004
8 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.19899E-004
9 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 2.85919
10 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
11 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
12 Coil:Heating:Water BASEMENT VAV BOX REHEAT COIL Design Size Rated Capacity [W] 13705.24677
13 Coil:Heating:Water BASEMENT VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.19899E-004
14 Coil:Heating:Water BASEMENT VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 285.79930
15 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.39933
16 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.12799
17 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.99500
18 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.39733
19 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.99500
20 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
21 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.97688E-003
22 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 3.90887E-005
23 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.39733
24 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
25 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
26 Coil:Heating:Water RETAIL_1_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 4468.07556
27 Coil:Heating:Water RETAIL_1_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 3.90887E-005
28 Coil:Heating:Water RETAIL_1_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 100.21308
29 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.28296
30 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.20916
31 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.99500
32 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.28155
33 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.99500
34 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
35 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.82158E-003
36 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.92774E-005
37 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.28155
38 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
39 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
40 Coil:Heating:Water RETAIL_2_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 2203.52598
41 Coil:Heating:Water RETAIL_2_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.92774E-005
42 Coil:Heating:Water RETAIL_2_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 47.51476
43 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.31218
44 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.40090
45 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.99500
46 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.31062
47 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
48 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
49 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 9.50369E-004
50 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.71293E-005
51 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.31062
52 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
53 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
54 Coil:Heating:Water MECH_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 3101.04465
55 Coil:Heating:Water MECH_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.71293E-005
56 Coil:Heating:Water MECH_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 68.53157
57 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.15815
58 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.45656
59 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.99500
60 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.15736
61 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
62 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
63 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 8.34502E-004
64 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.48581E-005
65 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.15736
66 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
67 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
68 Coil:Heating:Water STORAGE_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 1698.37625
69 Coil:Heating:Water STORAGE_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.48581E-005
70 Coil:Heating:Water STORAGE_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 37.88973
71 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 3.64363
72 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 6.47633E-002
73 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.99500
74 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 3.62542
75 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.99500
76 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
77 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.33448E-002
78 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.70832E-004
79 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 3.62542
80 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
81 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
82 Coil:Heating:Water LAUNDRY_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 19527.15634
83 Coil:Heating:Water LAUNDRY_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.70832E-004
84 Coil:Heating:Water LAUNDRY_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 409.83290
85 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.64895
86 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 8.72755E-002
87 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.99500
88 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.64070
89 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.99500
90 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
91 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 4.36549E-003
92 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.24698E-004
93 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.64070
94 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
95 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
96 Coil:Heating:Water CAFE_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 14253.78170
97 Coil:Heating:Water CAFE_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.24698E-004
98 Coil:Heating:Water CAFE_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 310.37079
99 Fan:ZoneExhaust LOBBY_FLR_1 EXHAUST FAN User-Specified Maximum Flow Rate [m3/s] 0.00000
100 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 5.39407
101 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.18480
102 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.99500
103 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 5.36710
104 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.99500
105 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
106 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.06166E-003
107 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 3.56808E-004
108 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 5.36710
109 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
110 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
111 Coil:Heating:Water LOBBY_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 40785.34036
112 Coil:Heating:Water LOBBY_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 3.56808E-004
113 Coil:Heating:Water LOBBY_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 877.20966
114 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_1_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 6.17350E-002
115 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 1.30711
116 Fan:OnOff ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 1.30711
117 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 4.87586E-005
118 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 5.11960E-004
119 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 22.62865
120 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
121 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.47948E-003
122 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
123 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.47948E-003
124 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 5.11960E-004
125 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 1.30711
126 Coil:Heating:Water ROOM_1_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 5573.40608
127 Coil:Heating:Water ROOM_1_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 4.87586E-005
128 Coil:Heating:Water ROOM_1_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 159.27408
129 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_2_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 6.17278E-002
130 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 1.29828
131 Fan:OnOff ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 1.29828
132 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 4.87985E-005
133 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 5.08501E-004
134 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 22.62865
135 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
136 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.47926E-003
137 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
138 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.47926E-003
139 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 5.08501E-004
140 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 1.29828
141 Coil:Heating:Water ROOM_2_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 5577.96501
142 Coil:Heating:Water ROOM_2_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 4.87985E-005
143 Coil:Heating:Water ROOM_2_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 159.40433
144 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_3_MULT19_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.83707
145 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT19_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 7.84323
146 Fan:OnOff ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 7.84323
147 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT19_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 2.80323E-004
148 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT19_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 3.07177E-003
149 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 22.62890
150 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
151 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.42835E-003
152 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
153 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.42835E-003
154 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 3.07177E-003
155 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 7.84323
156 Coil:Heating:Water ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 32042.68587
157 Coil:Heating:Water ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 2.80323E-004
158 Coil:Heating:Water ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 915.68508
159 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_4_MULT19_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.83730
160 ZoneHVAC:FourPipeFanCoil ROOM_4_MULT19_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 8.37380
161 Fan:OnOff ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 8.37380
162 ZoneHVAC:FourPipeFanCoil ROOM_4_MULT19_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 2.81234E-004
163 ZoneHVAC:FourPipeFanCoil ROOM_4_MULT19_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 3.37406E-003
164 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 22.62775
165 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
166 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.61360E-003
167 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
168 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
169 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 3.37406E-003
170 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 8.37380
171 Coil:Heating:Water ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 32146.75233
172 Coil:Heating:Water ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 2.81234E-004
173 Coil:Heating:Water ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 918.65831
174 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_5_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 6.17350E-002
175 ZoneHVAC:FourPipeFanCoil ROOM_5_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 1.15067
176 Fan:OnOff ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 1.15067
177 ZoneHVAC:FourPipeFanCoil ROOM_5_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 4.86723E-005
178 ZoneHVAC:FourPipeFanCoil ROOM_5_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 4.50684E-004
179 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 22.62867
180 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
181 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.47566E-003
182 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
183 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.47566E-003
184 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 4.50684E-004
185 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 1.15067
186 Coil:Heating:Water ROOM_5_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 5563.53867
187 Coil:Heating:Water ROOM_5_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 4.86723E-005
188 Coil:Heating:Water ROOM_5_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 158.99217
189 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_6_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 6.17278E-002
190 ZoneHVAC:FourPipeFanCoil ROOM_6_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 1.14318
191 Fan:OnOff ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 1.14318
192 ZoneHVAC:FourPipeFanCoil ROOM_6_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 4.87122E-005
193 ZoneHVAC:FourPipeFanCoil ROOM_6_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 4.47750E-004
194 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 22.62867
195 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
196 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.47539E-003
197 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
198 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.47539E-003
199 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 4.47750E-004
200 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 1.14318
201 Coil:Heating:Water ROOM_6_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 5568.10020
202 Coil:Heating:Water ROOM_6_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 4.87122E-005
203 Coil:Heating:Water ROOM_6_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 159.12249
204 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.40177
205 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.84672
206 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.99500
207 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.39476
208 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
209 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
210 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 4.49971E-004
211 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.35820E-004
212 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.39476
213 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
214 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
215 Coil:Heating:Water CORRIDOR_FLR_3 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 15525.09896
216 Coil:Heating:Water CORRIDOR_FLR_3 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.35820E-004
217 Coil:Heating:Water CORRIDOR_FLR_3 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 347.73802
218 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_1_FLR_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 1.54338E-002
219 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_6 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 0.35377
220 Fan:OnOff ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 0.35377
221 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_6 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 1.51290E-005
222 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_6 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 1.38561E-004
223 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 22.62864
224 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
225 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.48097E-003
226 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
227 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.48097E-003
228 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 1.38561E-004
229 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 0.35377
230 Coil:Heating:Water ROOM_1_FLR_6 FAN COIL HEATING COIL Design Size Rated Capacity [W] 1729.33509
231 Coil:Heating:Water ROOM_1_FLR_6 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 1.51290E-005
232 Coil:Heating:Water ROOM_1_FLR_6 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 49.41749
233 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_2_FLR_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 1.54319E-002
234 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_6 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 0.35114
235 Fan:OnOff ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 0.35114
236 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_6 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 1.51336E-005
237 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_6 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 1.37532E-004
238 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 22.62864
239 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
240 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.48085E-003
241 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
242 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.48085E-003
243 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 1.37532E-004
244 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 0.35114
245 Coil:Heating:Water ROOM_2_FLR_6 FAN COIL HEATING COIL Design Size Rated Capacity [W] 1729.86407
246 Coil:Heating:Water ROOM_2_FLR_6 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 1.51336E-005
247 Coil:Heating:Water ROOM_2_FLR_6 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 49.43260
248 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_3_MULT9_FLR_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 9.91540E-002
249 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT9_FLR_6 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 1.58995
250 Fan:OnOff ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 1.58995
251 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT9_FLR_6 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 7.30269E-005
252 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT9_FLR_6 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 6.28386E-004
253 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 22.62818
254 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
255 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.53580E-003
256 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
257 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
258 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 6.28386E-004
259 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 1.58995
260 Coil:Heating:Water ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL Design Size Rated Capacity [W] 8347.42829
261 Coil:Heating:Water ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 7.30269E-005
262 Coil:Heating:Water ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 238.53403
263 Fan:ZoneExhaust BANQUET_FLR_6 EXHAUST FAN User-Specified Maximum Flow Rate [m3/s] 0.00000
264 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.56745
265 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 9.84333E-002
266 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.99500
267 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 2.55462
268 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.99500
269 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
270 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.87064E-003
271 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.58705E-004
272 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 2.55462
273 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
274 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
275 Coil:Heating:Water BANQUET_FLR_6 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 18141.00026
276 Coil:Heating:Water BANQUET_FLR_6 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.58705E-004
277 Coil:Heating:Water BANQUET_FLR_6 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 388.00744
278 Fan:ZoneExhaust DINING_FLR_6 EXHAUST FAN User-Specified Maximum Flow Rate [m3/s] 0.00000
279 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.68931
280 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 9.39733E-002
281 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.99500
282 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 2.67586
283 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.99500
284 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
285 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 4.05434E-003
286 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.64736E-004
287 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 2.67586
288 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
289 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
290 Coil:Heating:Water DINING_FLR_6 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 18830.34444
291 Coil:Heating:Water DINING_FLR_6 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.64736E-004
292 Coil:Heating:Water DINING_FLR_6 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 402.46349
293 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.55057
294 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.74014
295 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.99500
296 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 2.53781
297 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.99500
298 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
299 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.23449E-002
300 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.17161E-004
301 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 2.53781
302 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
303 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
304 Coil:Heating:Water KITCHEN_FLR_6 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 13392.17347
305 Coil:Heating:Water KITCHEN_FLR_6 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.17161E-004
306 Coil:Heating:Water KITCHEN_FLR_6 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 280.73910
307 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.85278
308 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.36825
309 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.99500
310 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.84852
311 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.99500
312 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
313 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.03461E-003
314 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 9.02210E-005
315 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.84852
316 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
317 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
318 Coil:Heating:Water CORRIDOR_FLR_6 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 10312.81000
319 Coil:Heating:Water CORRIDOR_FLR_6 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 9.02210E-005
320 Coil:Heating:Water CORRIDOR_FLR_6 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 233.81878
321 AirLoopHVAC VAV WITH REHEAT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 24.65083
322 AirLoopHVAC VAV WITH REHEAT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 24.65083
323 AirLoopHVAC VAV WITH REHEAT Sum of Air Terminal Maximum Flow Rates [m3/s] 24.77471
324 AirLoopHVAC VAV WITH REHEAT Adjusted Heating Design Air Flow Rate [m3/s] 24.65083
325 AirLoopHVAC VAV WITH REHEAT Adjusted Cooling Design Air Flow Rate [m3/s] 24.65939
326 AirLoopHVAC VAV WITH REHEAT Adjusted Main Design Air Flow Rate [m3/s] 24.65939
327 AirLoopHVAC VAV WITH REHEAT User Heating Air Flow Ratio [] 0.30000
328 AirLoopHVAC VAV WITH REHEAT Calculated Heating Air Flow Ratio [] 0.99965
329 AirLoopHVAC FLR_3_DOAS Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 2.05132
330 AirLoopHVAC FLR_3_DOAS Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 2.05132
331 AirLoopHVAC FLR_3_DOAS Sum of Air Terminal Maximum Flow Rates [m3/s] 2.05132
332 AirLoopHVAC FLR_3_DOAS Adjusted Heating Design Air Flow Rate [m3/s] 2.05132
333 AirLoopHVAC FLR_3_DOAS Adjusted Cooling Design Air Flow Rate [m3/s] 2.05132
334 AirLoopHVAC FLR_3_DOAS Adjusted Main Design Air Flow Rate [m3/s] 2.05132
335 AirLoopHVAC FLR_3_DOAS User Heating Air Flow Ratio [] 0.30000
336 AirLoopHVAC FLR_3_DOAS Calculated Heating Air Flow Ratio [] 1.00000
337 AirLoopHVAC VAV WITH REHEAT Design Supply Air Flow Rate [m3/s] 24.65939
338 AirLoopHVAC FLR_3_DOAS Design Supply Air Flow Rate [m3/s] 2.05132
339 Controller:OutdoorAir VAV WITH REHEAT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 24.65939
340 Controller:OutdoorAir VAV WITH REHEAT_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 24.65939
341 HeatExchanger:AirToAir:SensibleAndLatent VAV WITH REHEAT OA HEAT RECOVERY Design Size Nominal Supply Air Flow Rate [m3/s] 24.65939
342 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Inlet Air Temperature [C] 40.80000
343 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
344 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Outlet Air Temperature [C] 10.78128
345 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 5.63111E-003
346 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 5.63111E-003
347 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Coil Load [W] 821617.44097
348 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Water Flow Rate [m3/s] 2.93463E-002
349 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Air Flow Rate [m3/s] 24.65939
350 Coil:Heating:Water VAV WITH REHEAT HEATING COIL Design Size Rated Capacity [W] 131650.00216
351 Coil:Heating:Water VAV WITH REHEAT HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 1.15173E-003
352 Coil:Heating:Water VAV WITH REHEAT HEATING COIL Design Size U-Factor Times Area Value [W/K] 2309.98315
353 Fan:VariableVolume VAV WITH REHEAT FAN Design Size Maximum Flow Rate [m3/s] 24.65939
354 Controller:WaterCoil VAV WITH REHEAT_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 2.93463E-002
355 Controller:WaterCoil VAV WITH REHEAT_COOLC_CONTROLLER Controller Convergence Tolerance 1.62266E-005
356 Controller:WaterCoil VAV WITH REHEAT_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 1.15173E-003
357 Controller:OutdoorAir FLR_3_DOAS_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 2.05132
358 Controller:OutdoorAir FLR_3_DOAS_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 2.05125
359 HeatExchanger:AirToAir:SensibleAndLatent FLR_3_DOAS OA HEAT RECOVERY Design Size Nominal Supply Air Flow Rate [m3/s] 2.05125
360 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Inlet Air Temperature [C] 40.80000
361 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
362 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Outlet Air Temperature [C] 11.83593
363 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 5.63111E-003
364 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 5.63111E-003
365 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Coil Load [W] 65945.85541
366 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Water Flow Rate [m3/s] 2.35543E-003
367 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Air Flow Rate [m3/s] 2.05132
368 Coil:Heating:Water FLR_3_DOAS HEATING COIL Design Size Rated Capacity [W] 10951.44367
369 Coil:Heating:Water FLR_3_DOAS HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 9.58080E-005
370 Coil:Heating:Water FLR_3_DOAS HEATING COIL Design Size U-Factor Times Area Value [W/K] 192.15837
371 Fan:ConstantVolume FLR_3_DOAS FAN User-Specified Maximum Flow Rate [m3/s] 2.05125
372 Controller:WaterCoil FLR_3_DOAS_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 2.35543E-003
373 Controller:WaterCoil FLR_3_DOAS_COOLC_CONTROLLER Controller Convergence Tolerance 2.02167E-004
374 Controller:WaterCoil FLR_3_DOAS_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 9.58080E-005
375 Pump:VariableSpeed COOLSYS1 PUMP SECONDARY Design Flow Rate [m3/s] 4.09709E-002
376 Pump:VariableSpeed COOLSYS1 PUMP SECONDARY Design Power Consumption [W] 8442.58563
377 PlantLoop HEATSYS1 Maximum Loop Flow Rate [m3/s] 3.64656E-003
378 PlantLoop HEATSYS1 Plant Loop Volume [m3] 0.43759
379 Pump:VariableSpeed HEATSYS1 PUMP Design Flow Rate [m3/s] 3.64656E-003
380 Pump:VariableSpeed HEATSYS1 PUMP Design Power Consumption [W] 1098.18449
381 Pump:VariableSpeed HEATSYS1 PUMP Design Minimum Flow Rate [m3/s] 0.00000
382 Boiler:HotWater HEATSYS1 BOILER Design Size Nominal Capacity [W] 416824.49617
383 Boiler:HotWater HEATSYS1 BOILER User-Specified Nominal Capacity [W] 416824.50000
384 Boiler:HotWater HEATSYS1 BOILER Design Size Design Water Flow Rate [m3/s] 3.64656E-003
385 PlantLoop COOLSYS1 Maximum Loop Flow Rate [m3/s] 4.09709E-002
386 PlantLoop COOLSYS1 Plant Loop Volume [m3] 4.91651
387 Pump:ConstantSpeed COOLSYS1 PUMP Design Flow Rate [m3/s] 4.09709E-002
388 Pump:ConstantSpeed COOLSYS1 PUMP Design Power Consumption [W] 5845.08679
389 Chiller:Electric:EIR COOLSYS1 CHILLER1 Design Size Reference Chilled Water Flow Rate [m3/s] 4.09709E-002
390 Chiller:Electric:EIR COOLSYS1 CHILLER1 Design Size Reference Capacity [W] 1147076.31124
391 Chiller:Electric:EIR COOLSYS1 CHILLER1 User-Specified Reference Capacity [W] 1147742.06000
392 Chiller:Electric:EIR COOLSYS1 CHILLER1 Design Size Reference Condenser Fluid Flow Rate [m3/s] 130.84259
393 PlantLoop SWHSYS1 Maximum Loop Flow Rate [m3/s] 3.75036E-004
394 PlantLoop SWHSYS1 Plant Loop Volume [m3] 4.50044E-002
395 Pump:ConstantSpeed SWHSYS1 PUMP Design Flow Rate [m3/s] 3.75036E-004
396 Pump:ConstantSpeed SWHSYS1 PUMP Design Power Consumption [W] 47.90688
397 WaterHeater:Mixed SWHSYS1 WATER HEATER Use Side Design Flow Rate [m3/s] 3.75036E-004


Water Heating Coil Capacity Information

Component Type Name Nominal Total Capacity {W}
1 Coil:Heating:Water BASEMENT VAV BOX REHEAT COIL 13776.60
2 Coil:Heating:Water RETAIL_1_FLR_1 VAV BOX REHEAT COIL 4489.73
3 Coil:Heating:Water RETAIL_2_FLR_1 VAV BOX REHEAT COIL 2214.71
4 Coil:Heating:Water MECH_FLR_1 VAV BOX REHEAT COIL 3116.27
5 Coil:Heating:Water STORAGE_FLR_1 VAV BOX REHEAT COIL 1706.65
6 Coil:Heating:Water LAUNDRY_FLR_1 VAV BOX REHEAT COIL 19628.30
7 Coil:Heating:Water CAFE_FLR_1 VAV BOX REHEAT COIL 14325.59
8 Coil:Heating:Water LOBBY_FLR_1 VAV BOX REHEAT COIL 40992.66
9 Coil:Heating:Water ROOM_1_FLR_3 FAN COIL HEATING COIL 6004.30
10 Coil:Heating:Water ROOM_2_FLR_3 FAN COIL HEATING COIL 6009.21
11 Coil:Heating:Water ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL 34519.76
12 Coil:Heating:Water ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL 34631.86
13 Coil:Heating:Water ROOM_5_FLR_3 FAN COIL HEATING COIL 5993.67
14 Coil:Heating:Water ROOM_6_FLR_3 FAN COIL HEATING COIL 5998.58
15 Coil:Heating:Water CORRIDOR_FLR_3 VAV BOX REHEAT COIL 15600.43
16 Coil:Heating:Water ROOM_1_FLR_6 FAN COIL HEATING COIL 1862.98
17 Coil:Heating:Water ROOM_2_FLR_6 FAN COIL HEATING COIL 1863.55
18 Coil:Heating:Water ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL 8992.47
19 Coil:Heating:Water BANQUET_FLR_6 VAV BOX REHEAT COIL 18233.60
20 Coil:Heating:Water DINING_FLR_6 VAV BOX REHEAT COIL 18926.52
21 Coil:Heating:Water KITCHEN_FLR_6 VAV BOX REHEAT COIL 13461.61
22 Coil:Heating:Water CORRIDOR_FLR_6 VAV BOX REHEAT COIL 10362.34
23 Coil:Heating:Water VAV WITH REHEAT HEATING COIL 106028.13
24 Coil:Heating:Water FLR_3_DOAS HEATING COIL 8820.06


Water Cooling Coil Capacity Information

Component Type Name Nominal Total Capacity {W} Nominal Sensible Capacity {W} Nominal Latent Capacity {W} Nominal Sensible Heat Ratio Nominal Coil UA Value {W/C} Nominal Coil Surface Area {m2}
1 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL 22906.95 17355.99 5550.96 0.76 3028.13 30.71
2 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL 22752.64 17239.03 5513.61 0.76 3007.91 30.51
3 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL 138105.24 104575.20 33530.04 0.76 18511.08 187.75
4 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL 149091.03 112073.05 37017.98 0.75 19470.15 197.48
5 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL 20172.89 15283.75 4889.14 0.76 2669.59 27.08
6 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL 20042.10 15184.61 4857.49 0.76 2652.48 26.90
7 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL 6198.79 4696.75 1502.04 0.76 819.09 8.31
8 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL 6152.83 4661.91 1490.91 0.76 813.04 8.25
9 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL 27961.22 21135.97 6825.26 0.76 3665.44 37.18
10 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL 686960.31 431435.91 255524.40 0.63 73391.12 744.37
11 Coil:Cooling:Water FLR_3_DOAS COOLING COIL 54169.20 34464.63 19704.58 0.64 5364.64 54.41


Chiller Standard Rating Information

Component Type Component Name IPLV in SI Units {W/W} IPLV in IP Units {Btu/W-h}
1 Chiller:Electric:EIR COOLSYS1 CHILLER1 3.72 12.68


Zone Surfaces

Zone Name # Surfaces
1 BASEMENT 14
2 RETAIL_1_FLR_1 8
3 RETAIL_2_FLR_1 8
4 MECH_FLR_1 7
5 STORAGE_FLR_1 8
6 LAUNDRY_FLR_1 8
7 CAFE_FLR_1 10
8 LOBBY_FLR_1 22
9 ROOM_1_FLR_3 9
10 ROOM_2_FLR_3 9
11 ROOM_3_MULT19_FLR_3 8
12 ROOM_4_MULT19_FLR_3 8
13 ROOM_5_FLR_3 9
14 ROOM_6_FLR_3 9
15 CORRIDOR_FLR_3 25
16 ROOM_1_FLR_6 9
17 ROOM_2_FLR_6 9
18 ROOM_3_MULT9_FLR_6 8
19 BANQUET_FLR_6 8
20 DINING_FLR_6 8
21 KITCHEN_FLR_6 12
22 CORRIDOR_FLR_6 19


HeatTransfer Surface

Surface Name Surface Class Base Surface Heat Transfer Algorithm Construction Nominal U (w/o film coefs) {W/m2-K} Nominal U (with film coefs) {W/m2-K} Solar Diffusing Area (Net) {m2} Area (Gross) {m2} Area (Sunlit Calc) {m2} Azimuth {deg} Tilt {deg} ~Width {m} ~Height {m} Reveal {m} ExtBoundCondition ExtConvCoeffCalc IntConvCoeffCalc SunExposure WindExposure ViewFactorToGround ViewFactorToSky ViewFactorToGround-IR ViewFactorToSky-IR #Sides
1 BASEMENT_WALL_NORTH Wall   CTF - ConductionTransferFunction BASEMENT_WALL_NORTH_CFACTOR 0.940 0.824   211.13 211.13 211.13 0.00 90.00 86.56 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
2 BASEMENT_WALL_EAST Wall   CTF - ConductionTransferFunction BASEMENT_WALL_EAST_CFACTOR 0.940 0.824   55.76 55.76 55.76 90.00 90.00 22.86 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
3 BASEMENT_WALL_SOUTH Wall   CTF - ConductionTransferFunction BASEMENT_WALL_SOUTH_CFACTOR 0.940 0.824   211.13 211.13 211.13 180.00 90.00 86.56 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
4 BASEMENT_WALL_WEST Wall   CTF - ConductionTransferFunction BASEMENT_WALL_WEST_CFACTOR 0.940 0.824   55.76 55.76 55.76 270.00 90.00 22.86 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
5 BASEMENT_FLOOR Floor   CTF - ConductionTransferFunction BASEMENT_FLOOR 2.705 1.632   1978.83 1978.83 1978.83 0.00 180.00 86.56 22.86 0.00 BASEMENT_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
6 BASEMENT_CEILING_1 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   67.07 67.07 67.07 180.00 0.00 11.58 5.79 0.00 RETAIL_1_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
7 BASEMENT_CEILING_2 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   77.67 77.67 77.67 180.00 0.00 11.58 6.71 0.00 RETAIL_2_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
8 BASEMENT_CEILING_3 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   164.24 164.24 164.24 180.00 0.00 15.85 10.36 0.00 MECH_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
9 BASEMENT_CEILING_4 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   94.76 94.76 94.76 180.00 0.00 9.14 10.36 0.00 STORAGE_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
10 BASEMENT_CEILING_5 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   78.04 78.04 78.04 180.00 0.00 4.57 17.07 0.00 LAUNDRY_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
11 BASEMENT_CEILING_6 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   188.86 188.86 188.86 180.00 0.00 32.61 5.79 0.00 CAFE_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
12 BASEMENT_CEILING_7 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   1088.56 1088.56 1088.56 180.00 0.00 32.99 32.99 0.00 LOBBY_FLR_1_FLOOR_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 6
13 BASEMENT_CEILING_8 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   219.63 219.63 219.63 90.00 0.00 14.82 14.82 0.00 LOBBY_FLR_1_FLOOR_2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 6
14 BASEMENT_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   3957.66 3957.66 3957.66 0.00 90.00 3957.66 1.00 0.00 BASEMENT_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
15 RETAIL_1_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.214 1.028   22.63 45.89 22.63 180.00 90.00 11.58 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
16 RETAIL_1_FLR_1_WALL_SOUTH_WINDOW Window RETAIL_1_FLR_1_WALL_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.5119_SHGC_0.25 N/A 2.910 No 23.26 23.26 23.26 180.00 90.00 10.92 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
17 RETAIL_1_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.214 1.028   22.95 22.95 22.95 270.00 90.00 5.79 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
18 RETAIL_1_FLR_1_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   45.89 45.89 45.89 0.00 90.00 11.58 3.96 0.00 RETAIL_2_FLR_1_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
19 RETAIL_1_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.95 22.95 22.95 90.00 90.00 5.79 3.96 0.00 LOBBY_FLR_1_WALL_2_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
20 RETAIL_1_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   67.07 67.07 67.07 0.00 180.00 11.58 5.79 0.00 BASEMENT_CEILING_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
21 RETAIL_1_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.283 0.269   67.07 67.07 67.07 180.00 0.00 11.58 5.79 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 7.62E-002 0.92 4
22 RETAIL_1_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   134.14 134.14 134.14 0.00 90.00 134.14 1.00 0.00 RETAIL_1_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
23 RETAIL_2_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.214 1.028   24.62 26.57 24.62 270.00 90.00 6.71 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
24 RETAIL_2_FLR_1_WALL_WEST_DOOR Door RETAIL_2_FLR_1_WALL_WEST CTF - ConductionTransferFunction SWINGING DOOR_CON 3.464 3.464   1.95 1.95 1.95 270.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
25 RETAIL_2_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   45.89 45.89 45.89 180.00 90.00 11.58 3.96 0.00 RETAIL_1_FLR_1_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
26 RETAIL_2_FLR_1_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   45.89 45.89 45.89 0.00 90.00 11.58 3.96 0.00 LOBBY_FLR_1_WALL_2_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
27 RETAIL_2_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.57 26.57 26.57 90.00 90.00 6.71 3.96 0.00 LOBBY_FLR_1_WALL_3_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
28 RETAIL_2_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   77.67 77.67 77.67 0.00 180.00 11.58 6.71 0.00 BASEMENT_CEILING_2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
29 RETAIL_2_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   77.67 77.67 77.67 180.00 0.00 11.58 6.71 0.00 RETAIL_2_FLR_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
30 RETAIL_2_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   155.34 155.34 155.34 0.00 90.00 155.34 1.00 0.00 RETAIL_2_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
31 MECH_FLR_1_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.214 1.028   62.80 62.80 62.80 0.00 90.00 15.85 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
32 MECH_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 90.00 90.00 10.36 3.96 0.00 STORAGE_FLR_1_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
33 MECH_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   62.80 62.80 62.80 180.00 90.00 15.85 3.96 0.00 LOBBY_FLR_1_WALL_3_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
34 MECH_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 270.00 90.00 10.36 3.96 0.00 LOBBY_FLR_1_WALL_1_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
35 MECH_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   164.24 164.24 164.24 0.00 180.00 15.85 10.36 0.00 BASEMENT_CEILING_3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
36 MECH_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   164.24 164.24 164.24 180.00 0.00 15.85 10.36 0.00 MECH_FLR_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
37 MECH_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   328.49 328.49 328.49 0.00 90.00 328.49 1.00 0.00 MECH_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
38 STORAGE_FLR_1_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.214 1.028   28.80 36.23 28.80 0.00 90.00 9.14 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
39 STORAGE_FLR_1_WALL_NORTH_ROLLDOOR Door STORAGE_FLR_1_WALL_NORTH CTF - ConductionTransferFunction OVERHEAD DOOR_CON 1.198 1.198   7.43 7.43 7.43 0.00 90.00 3.05 2.44 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
40 STORAGE_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 90.00 90.00 10.36 3.96 0.00 LOBBY_FLR_1_WALL_4_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
41 STORAGE_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   36.23 36.23 36.23 180.00 90.00 9.14 3.96 0.00 LOBBY_FLR_1_WALL_4_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
42 STORAGE_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 270.00 90.00 10.36 3.96 0.00 MECH_FLR_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
43 STORAGE_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   94.76 94.76 94.76 0.00 180.00 9.14 10.36 0.00 BASEMENT_CEILING_4 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
44 STORAGE_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   94.76 94.76 94.76 180.00 0.00 9.14 10.36 0.00 STORAGE_FLR_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
45 STORAGE_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   189.52 189.52 189.52 0.00 90.00 189.52 1.00 0.00 STORAGE_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
46 LAUNDRY_FLR_1_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.214 1.028   18.12 18.12 18.12 0.00 90.00 4.57 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
47 LAUNDRY_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.214 1.028   65.68 67.63 65.68 90.00 90.00 17.07 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
48 LAUNDRY_FLR_1_WALL_EAST_DOOR Door LAUNDRY_FLR_1_WALL_EAST CTF - ConductionTransferFunction SWINGING DOOR_CON 3.464 3.464   1.95 1.95 1.95 90.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
49 LAUNDRY_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   18.12 18.12 18.12 180.00 90.00 4.57 3.96 0.00 CAFE_FLR_1_WALL_2_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
50 LAUNDRY_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   67.63 67.63 67.63 270.00 90.00 17.07 3.96 0.00 LOBBY_FLR_1_WALL_3_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
51 LAUNDRY_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   78.04 78.04 78.04 0.00 180.00 4.57 17.07 0.00 BASEMENT_CEILING_5 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
52 LAUNDRY_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   78.04 78.04 78.04 180.00 0.00 4.57 17.07 0.00 LAUNDRY_FLR_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
53 LAUNDRY_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   156.08 156.08 156.08 0.00 90.00 156.08 1.00 0.00 LAUNDRY_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
54 CAFE_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.214 1.028   21.00 22.95 21.00 90.00 90.00 5.79 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
55 CAFE_FLR_1_WALL_EAST_DOOR Door CAFE_FLR_1_WALL_EAST CTF - ConductionTransferFunction SWINGING DOOR_CON 3.464 3.464   1.95 1.95 1.95 90.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
56 CAFE_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.214 1.028   63.73 129.23 63.73 180.00 90.00 32.61 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
57 CAFE_FLR_1_WALL_SOUTH_WINDOW Window CAFE_FLR_1_WALL_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.5119_SHGC_0.25 N/A 2.910 No 65.50 65.50 65.50 180.00 90.00 30.75 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
58 CAFE_FLR_1_WALL_1_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.11 111.11 111.11 0.00 90.00 28.04 3.96 0.00 LOBBY_FLR_1_WALL_3_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
59 CAFE_FLR_1_WALL_2_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   18.12 18.12 18.12 0.00 90.00 4.57 3.96 0.00 LAUNDRY_FLR_1_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
60 CAFE_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.95 22.95 22.95 270.00 90.00 5.79 3.96 0.00 LOBBY_FLR_1_WALL_2_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
61 CAFE_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   188.86 188.86 188.86 0.00 180.00 32.61 5.79 0.00 BASEMENT_CEILING_6 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
62 CAFE_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.283 0.269   188.86 188.86 188.86 180.00 0.00 32.61 5.79 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 3.86E-002 0.96 4
63 CAFE_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   377.72 377.72 377.72 0.00 90.00 377.72 1.00 0.00 CAFE_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
64 LOBBY_FLR_1_WALL_1_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.214 1.028   209.87 213.77 209.87 0.00 90.00 53.95 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
65 LOBBY_FLR_1_WALL_1_NORTH_DOOR1 Door LOBBY_FLR_1_WALL_1_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.464 3.464   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
66 LOBBY_FLR_1_WALL_1_NORTH_DOOR2 Door LOBBY_FLR_1_WALL_1_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.464 3.464   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
67 LOBBY_FLR_1_WALL_2_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.214 1.028   12.08 12.08 12.08 0.00 90.00 3.05 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
68 LOBBY_FLR_1_WALL_1_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.214 1.028   82.79 167.88 82.79 180.00 90.00 42.37 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
69 LOBBY_FLR_1_WALL_SOUTH_WINDOW Window LOBBY_FLR_1_WALL_1_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.5119_SHGC_0.25 N/A 2.910 No 85.08 85.08 85.08 180.00 90.00 39.95 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
70 LOBBY_FLR_1_WALL_1_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.214 1.028   41.06 41.06 41.06 270.00 90.00 10.36 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
71 LOBBY_FLR_1_WALL_2_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   45.89 45.89 45.89 180.00 90.00 11.58 3.96 0.00 RETAIL_2_FLR_1_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
72 LOBBY_FLR_1_WALL_3_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.11 111.11 111.11 180.00 90.00 28.04 3.96 0.00 CAFE_FLR_1_WALL_1_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
73 LOBBY_FLR_1_WALL_2_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.95 22.95 22.95 270.00 90.00 5.79 3.96 0.00 RETAIL_1_FLR_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
74 LOBBY_FLR_1_WALL_3_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.57 26.57 26.57 270.00 90.00 6.71 3.96 0.00 RETAIL_2_FLR_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
75 LOBBY_FLR_1_WALL_4_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 270.00 90.00 10.36 3.96 0.00 STORAGE_FLR_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
76 LOBBY_FLR_1_WALL_3_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   62.80 62.80 62.80 0.00 90.00 15.85 3.96 0.00 MECH_FLR_1_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
77 LOBBY_FLR_1_WALL_4_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   36.23 36.23 36.23 0.00 90.00 9.14 3.96 0.00 STORAGE_FLR_1_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
78 LOBBY_FLR_1_WALL_1_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 90.00 90.00 10.36 3.96 0.00 MECH_FLR_1_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
79 LOBBY_FLR_1_WALL_2_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.95 22.95 22.95 90.00 90.00 5.79 3.96 0.00 CAFE_FLR_1_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
80 LOBBY_FLR_1_WALL_3_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   67.63 67.63 67.63 90.00 90.00 17.07 3.96 0.00 LAUNDRY_FLR_1_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
81 LOBBY_FLR_1_FLOOR_1 Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   1088.56 1088.56 1088.56 180.00 180.00 32.99 32.99 0.00 BASEMENT_CEILING_7 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 6
82 LOBBY_FLR_1_FLOOR_2 Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   219.63 219.63 219.63 90.00 180.00 14.82 14.82 0.00 BASEMENT_CEILING_8 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 6
83 LOBBY_FLR_1_CEILING_1 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   1062.83 1062.83 1062.83 270.00 0.00 32.60 32.60 0.00 LOBBY_FLR_1_CEILING_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 10
84 LOBBY_FLR_1_CEILING_2 Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.283 0.269   245.35 245.35 245.35 180.00 0.00 42.37 5.79 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 4.22E-003 1.00 4
85 LOBBY_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   2616.37 2616.37 2616.37 0.00 90.00 2616.37 1.00 0.00 LOBBY_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
86 ROOM_1_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.370 1.137   9.34 13.94 9.34 180.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
87 ROOM_1_FLR_3_WALL_SOUTH_WINDOW Window ROOM_1_FLR_3_WALL_SOUTH Window5 Detailed Fenestration RESWINDOW_U_0.5119_SHGC_0.25 N/A 2.910 No 4.60 4.60 4.60 180.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
88 ROOM_1_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.370 1.137   17.43 26.01 17.43 270.00 90.00 8.54 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
89 ROOM_1_FLR_3_WALL_WEST_WINDOW Window ROOM_1_FLR_3_WALL_WEST Window5 Detailed Fenestration RESWINDOW_U_0.5119_SHGC_0.25 N/A 2.910 No 8.58 8.58 8.58 270.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
90 ROOM_1_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 0.00 90.00 4.57 3.05 0.00 ROOM_2_FLR_3_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
91 ROOM_1_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.54 3.05 0.00 CORRIDOR_FLR_3_WALL_3_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
92 ROOM_1_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   39.02 39.02 39.02 0.00 180.00 4.57 8.54 0.00 ROOM_1_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
93 ROOM_1_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   39.02 39.02 39.02 180.00 0.00 4.57 8.54 0.00 ROOM_1_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
94 ROOM_1_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.04 78.04 78.04 0.00 90.00 78.04 1.00 0.00 ROOM_1_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
95 ROOM_2_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.370 1.137   9.34 13.94 9.34 0.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
96 ROOM_2_FLR_3_WALL_NORTH_WINDOW Window ROOM_2_FLR_3_WALL_NORTH Window5 Detailed Fenestration RESWINDOW_U_0.5119_SHGC_0.25 N/A 2.910 No 4.60 4.60 4.60 0.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
97 ROOM_2_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.370 1.137   17.43 26.01 17.43 270.00 90.00 8.53 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
98 ROOM_2_FLR_3_WALL_WEST_WINDOW Window ROOM_2_FLR_3_WALL_WEST Window5 Detailed Fenestration RESWINDOW_U_0.5119_SHGC_0.25 N/A 2.910 No 8.58 8.58 8.58 270.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
99 ROOM_2_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.53 3.05 0.00 CORRIDOR_FLR_3_WALL_4_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
100 ROOM_2_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 180.00 90.00 4.57 3.05 0.00 ROOM_1_FLR_3_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
101 ROOM_2_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   39.02 39.02 39.02 0.00 180.00 4.57 8.53 0.00 ROOM_2_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
102 ROOM_2_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   39.02 39.02 39.02 180.00 0.00 4.57 8.53 0.00 ROOM_2_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
103 ROOM_2_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.03 78.03 78.03 0.00 90.00 78.03 1.00 0.00 ROOM_2_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
104 ROOM_3_MULT19_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.370 1.137   7.47 11.15 7.47 180.00 90.00 3.66 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
105 ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW Window ROOM_3_MULT19_FLR_3_WALL_SOUTH Window5 Detailed Fenestration RESWINDOW_U_0.5119_SHGC_0.25 N/A 2.910 No 3.68 3.68 3.68 180.00 90.00 3.02 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
106 ROOM_3_MULT19_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 0.00 90.00 3.66 3.05 0.00 ROOM_3_MULT19_FLR_3_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
107 ROOM_3_MULT19_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 90.00 90.00 6.71 3.05 0.00 ROOM_3_MULT19_FLR_3_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
108 ROOM_3_MULT19_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 270.00 90.00 6.71 3.05 0.00 ROOM_3_MULT19_FLR_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
109 ROOM_3_MULT19_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   24.52 24.52 24.52 0.00 180.00 3.66 6.71 0.00 ROOM_3_MULT19_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
110 ROOM_3_MULT19_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   24.52 24.52 24.52 180.00 0.00 3.66 6.71 0.00 ROOM_3_MULT19_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
111 ROOM_3_MULT19_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   49.05 49.05 49.05 0.00 90.00 49.05 1.00 0.00 ROOM_3_MULT19_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
112 ROOM_4_MULT19_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.370 1.137   7.47 11.15 7.47 0.00 90.00 3.66 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
113 ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW Window ROOM_4_MULT19_FLR_3_WALL_NORTH Window5 Detailed Fenestration RESWINDOW_U_0.5119_SHGC_0.25 N/A 2.910 No 3.68 3.68 3.68 0.00 90.00 3.02 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
114 ROOM_4_MULT19_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 90.00 90.00 6.71 3.05 0.00 ROOM_4_MULT19_FLR_3_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
115 ROOM_4_MULT19_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 180.00 90.00 3.66 3.05 0.00 ROOM_4_MULT19_FLR_3_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
116 ROOM_4_MULT19_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 270.00 90.00 6.71 3.05 0.00 ROOM_4_MULT19_FLR_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
117 ROOM_4_MULT19_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   24.53 24.53 24.53 0.00 180.00 3.66 6.71 0.00 ROOM_4_MULT19_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
118 ROOM_4_MULT19_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   24.53 24.53 24.53 180.00 0.00 3.66 6.71 0.00 ROOM_4_MULT19_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
119 ROOM_4_MULT19_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   49.06 49.06 49.06 0.00 90.00 49.06 1.00 0.00 ROOM_4_MULT19_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
120 ROOM_5_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.370 1.137   17.43 26.01 17.43 90.00 90.00 8.54 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
121 ROOM_5_FLR_3_WALL_EAST_WINDOW Window ROOM_5_FLR_3_WALL_EAST Window5 Detailed Fenestration RESWINDOW_U_0.5119_SHGC_0.25 N/A 2.910 No 8.58 8.58 8.58 90.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
122 ROOM_5_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.370 1.137   9.34 13.94 9.34 180.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
123 ROOM_5_FLR_3_WALL_SOUTH_WINDOW Window ROOM_5_FLR_3_WALL_SOUTH Window5 Detailed Fenestration RESWINDOW_U_0.5119_SHGC_0.25 N/A 2.910 No 4.60 4.60 4.60 180.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
124 ROOM_5_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 0.00 90.00 4.57 3.05 0.00 ROOM_6_FLR_3_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
125 ROOM_5_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 270.00 90.00 8.54 3.05 0.00 CORRIDOR_FLR_3_WALL_3_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
126 ROOM_5_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   39.02 39.02 39.02 0.00 180.00 4.57 8.54 0.00 ROOM_5_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
127 ROOM_5_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   39.02 39.02 39.02 180.00 0.00 4.57 8.54 0.00 ROOM_5_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
128 ROOM_5_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.04 78.04 78.04 0.00 90.00 78.04 1.00 0.00 ROOM_5_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
129 ROOM_6_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.370 1.137   9.34 13.94 9.34 0.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
130 ROOM_6_FLR_3_WALL_NORTH_WINDOW Window ROOM_6_FLR_3_WALL_NORTH Window5 Detailed Fenestration RESWINDOW_U_0.5119_SHGC_0.25 N/A 2.910 No 4.60 4.60 4.60 0.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
131 ROOM_6_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.370 1.137   17.43 26.01 17.43 90.00 90.00 8.53 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
132 ROOM_6_FLR_3_WALL_EAST_WINDOW Window ROOM_6_FLR_3_WALL_EAST Window5 Detailed Fenestration RESWINDOW_U_0.5119_SHGC_0.25 N/A 2.910 No 8.58 8.58 8.58 90.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
133 ROOM_6_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 180.00 90.00 4.57 3.05 0.00 ROOM_5_FLR_3_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
134 ROOM_6_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 270.00 90.00 8.53 3.05 0.00 CORRIDOR_FLR_3_WALL_4_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
135 ROOM_6_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   39.02 39.02 39.02 0.00 180.00 4.57 8.53 0.00 ROOM_6_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
136 ROOM_6_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   39.02 39.02 39.02 180.00 0.00 4.57 8.53 0.00 ROOM_6_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
137 ROOM_6_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.03 78.03 78.03 0.00 90.00 78.03 1.00 0.00 ROOM_6_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
138 CORRIDOR_FLR_3_WALL_1_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.530 1.245   11.83 17.65 11.83 0.00 90.00 5.79 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
139 CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW Window CORRIDOR_FLR_3_WALL_1_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.5119_SHGC_0.25 N/A 2.910 No 5.82 5.82 5.82 0.00 90.00 4.78 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
140 CORRIDOR_FLR_3_WALL_2_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.530 1.245   4.35 6.50 4.35 0.00 90.00 2.13 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
141 CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW Window CORRIDOR_FLR_3_WALL_2_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.5119_SHGC_0.25 N/A 2.910 No 2.15 2.15 2.15 0.00 90.00 1.76 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
142 CORRIDOR_FLR_3_WALL_1_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.530 1.245   4.36 6.50 4.36 180.00 90.00 2.13 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
143 CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW Window CORRIDOR_FLR_3_WALL_1_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.5119_SHGC_0.25 N/A 2.910 No 2.15 2.15 2.15 180.00 90.00 1.76 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
144 CORRIDOR_FLR_3_WALL_2_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.530 1.245   11.83 17.65 11.83 180.00 90.00 5.79 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
145 CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW Window CORRIDOR_FLR_3_WALL_2_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.5119_SHGC_0.25 N/A 2.910 No 5.82 5.82 5.82 180.00 90.00 4.78 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
146 CORRIDOR_FLR_3_WALL_3_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   211.82 211.82 211.82 0.00 90.00 69.50 3.05 0.00 CORRIDOR_FLR_3_WALL_3_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
147 CORRIDOR_FLR_3_WALL_1_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 90.00 90.00 6.71 3.05 0.00 CORRIDOR_FLR_3_WALL_1_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
148 CORRIDOR_FLR_3_WALL_2_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 90.00 90.00 6.71 3.05 0.00 CORRIDOR_FLR_3_WALL_2_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
149 CORRIDOR_FLR_3_WALL_3_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.54 3.05 0.00 ROOM_5_FLR_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
150 CORRIDOR_FLR_3_WALL_4_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.53 3.05 0.00 ROOM_6_FLR_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
151 CORRIDOR_FLR_3_WALL_3_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   211.82 211.82 211.82 180.00 90.00 69.49 3.05 0.00 CORRIDOR_FLR_3_WALL_3_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
152 CORRIDOR_FLR_3_WALL_1_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 270.00 90.00 6.71 3.05 0.00 CORRIDOR_FLR_3_WALL_1_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
153 CORRIDOR_FLR_3_WALL_2_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 270.00 90.00 6.71 3.05 0.00 CORRIDOR_FLR_3_WALL_2_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
154 CORRIDOR_FLR_3_WALL_3_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 270.00 90.00 8.54 3.05 0.00 ROOM_1_FLR_3_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
155 CORRIDOR_FLR_3_WALL_4_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 270.00 90.00 8.53 3.05 0.00 ROOM_2_FLR_3_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
156 CORRIDOR_FLR_3_FLOOR_1 Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   74.32 74.32 74.32 180.00 180.00 8.62 8.62 0.00 CORRIDOR_FLR_3_FLOOR_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 6
157 CORRIDOR_FLR_3_FLOOR_2 Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   240.77 240.77 240.77 270.00 180.00 3.66 65.84 0.00 CORRIDOR_FLR_3_FLOOR_2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
158 CORRIDOR_FLR_3_FLOOR_3 Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   74.32 74.32 74.32 90.00 180.00 8.62 8.62 0.00 CORRIDOR_FLR_3_FLOOR_3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 6
159 CORRIDOR_FLR_3_CEILING_1 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   74.32 74.32 74.32 90.00 0.00 8.62 8.62 0.00 CORRIDOR_FLR_3_CEILING_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 6
160 CORRIDOR_FLR_3_CEILING_2 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   240.77 240.77 240.77 90.00 0.00 3.66 65.84 0.00 CORRIDOR_FLR_3_CEILING_2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
161 CORRIDOR_FLR_3_CEILING_3 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   74.32 74.32 74.32 90.00 0.00 8.62 8.62 0.00 CORRIDOR_FLR_3_CEILING_3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 6
162 CORRIDOR_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   778.81 778.81 778.81 0.00 90.00 778.81 1.00 0.00 CORRIDOR_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
163 ROOM_1_FLR_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_TOP 1.442 1.186   9.34 13.94 9.34 180.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
164 ROOM_1_FLR_6_WALL_SOUTH_WINDOW Window ROOM_1_FLR_6_WALL_SOUTH Window5 Detailed Fenestration RESWINDOW_U_0.5119_SHGC_0.25 N/A 2.910 No 4.60 4.60 4.60 180.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
165 ROOM_1_FLR_6_WALL_WEST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_TOP 1.442 1.186   17.43 26.01 17.43 270.00 90.00 8.54 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
166 ROOM_1_FLR_6_WALL_WEST_WINDOW Window ROOM_1_FLR_6_WALL_WEST Window5 Detailed Fenestration RESWINDOW_U_0.5119_SHGC_0.25 N/A 2.910 No 8.58 8.58 8.58 270.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
167 ROOM_1_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 0.00 90.00 4.57 3.05 0.00 ROOM_2_FLR_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
168 ROOM_1_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.54 3.05 0.00 ROOM_1_FLR_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
169 ROOM_1_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   39.02 39.02 39.02 0.00 180.00 4.57 8.54 0.00 ROOM_1_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
170 ROOM_1_FLR_6_CEILING Roof   CTF - ConductionTransferFunction RES_ROOF 0.283 0.269   39.02 39.02 39.02 180.00 0.00 4.57 8.54 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
171 ROOM_1_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.04 78.04 78.04 0.00 90.00 78.04 1.00 0.00 ROOM_1_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
172 ROOM_2_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_TOP 1.442 1.186   9.34 13.94 9.34 0.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
173 ROOM_2_FLR_6_WALL_NORTH_WINDOW Window ROOM_2_FLR_6_WALL_NORTH Window5 Detailed Fenestration RESWINDOW_U_0.5119_SHGC_0.25 N/A 2.910 No 4.60 4.60 4.60 0.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
174 ROOM_2_FLR_6_WALL_WEST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_TOP 1.442 1.186   17.43 26.01 17.43 270.00 90.00 8.53 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
175 ROOM_2_FLR_6_WALL_WEST_WINDOW Window ROOM_2_FLR_6_WALL_WEST Window5 Detailed Fenestration RESWINDOW_U_0.5119_SHGC_0.25 N/A 2.910 No 8.58 8.58 8.58 270.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
176 ROOM_2_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.53 3.05 0.00 ROOM_2_FLR_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
177 ROOM_2_FLR_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 180.00 90.00 4.57 3.05 0.00 ROOM_1_FLR_6_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
178 ROOM_2_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   39.02 39.02 39.02 0.00 180.00 4.57 8.53 0.00 ROOM_2_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
179 ROOM_2_FLR_6_CEILING Roof   CTF - ConductionTransferFunction RES_ROOF 0.283 0.269   39.02 39.02 39.02 180.00 0.00 4.57 8.53 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
180 ROOM_2_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.03 78.03 78.03 0.00 90.00 78.03 1.00 0.00 ROOM_2_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
181 ROOM_3_MULT9_FLR_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_TOP 1.442 1.186   13.70 20.44 13.70 180.00 90.00 6.71 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
182 ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW Window ROOM_3_MULT9_FLR_6_WALL_SOUTH Window5 Detailed Fenestration RESWINDOW_U_0.5119_SHGC_0.25 N/A 2.910 No 6.74 6.74 6.74 180.00 90.00 5.53 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
183 ROOM_3_MULT9_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 0.00 90.00 6.71 3.05 0.00 ROOM_3_MULT9_FLR_6_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
184 ROOM_3_MULT9_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 90.00 90.00 3.66 3.05 0.00 ROOM_3_MULT9_FLR_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
185 ROOM_3_MULT9_FLR_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 270.00 90.00 3.66 3.05 0.00 ROOM_3_MULT9_FLR_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
186 ROOM_3_MULT9_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   24.53 24.53 24.53 0.00 180.00 6.71 3.66 0.00 ROOM_3_MULT9_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
187 ROOM_3_MULT9_FLR_6_CEILING Roof   CTF - ConductionTransferFunction RES_ROOF 0.283 0.269   24.53 24.53 24.53 180.00 0.00 6.71 3.66 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
188 ROOM_3_MULT9_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   49.06 49.06 49.06 0.00 90.00 49.06 1.00 0.00 ROOM_3_MULT9_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
189 BANQUET_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.605 1.294   65.36 97.55 65.36 0.00 90.00 32.00 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
190 BANQUET_FLR_6_WALL_NORTH_WINDOW Window BANQUET_FLR_6_WALL_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.5119_SHGC_0.25 N/A 2.910 No 32.19 32.19 32.19 0.00 90.00 26.40 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
191 BANQUET_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 90.00 90.00 10.36 3.05 0.00 CORRIDOR_FLR_6_WALL_3_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
192 BANQUET_FLR_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   97.55 97.55 97.55 180.00 90.00 32.00 3.05 0.00 CORRIDOR_FLR_6_WALL_3_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
193 BANQUET_FLR_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 270.00 90.00 10.36 3.05 0.00 CORRIDOR_FLR_6_WALL_1_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
194 BANQUET_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   331.66 331.66 331.66 0.00 180.00 32.00 10.36 0.00 BANQUET_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
195 BANQUET_FLR_6_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.283 0.269   331.66 331.66 331.66 180.00 0.00 32.00 10.36 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
196 BANQUET_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   663.31 663.31 663.31 0.00 90.00 663.31 1.00 0.00 BANQUET_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
197 DINING_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.605 1.294   65.36 97.55 65.36 0.00 90.00 32.00 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
198 DINING_FLR_6_WALL_NORTH_WINDOW Window DINING_FLR_6_WALL_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.5119_SHGC_0.25 N/A 2.910 No 32.19 32.19 32.19 0.00 90.00 26.40 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
199 DINING_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 90.00 90.00 10.36 3.05 0.00 KITCHEN_FLR_6_WALL_2_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
200 DINING_FLR_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   97.55 97.55 97.55 180.00 90.00 32.00 3.05 0.00 DINING_FLR_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
201 DINING_FLR_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 270.00 90.00 10.36 3.05 0.00 CORRIDOR_FLR_6_WALL_2_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
202 DINING_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   331.66 331.66 331.66 0.00 180.00 32.00 10.36 0.00 DINING_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
203 DINING_FLR_6_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.283 0.269   331.66 331.66 331.66 180.00 0.00 32.00 10.36 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
204 DINING_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   663.31 663.31 663.31 0.00 90.00 663.31 1.00 0.00 DINING_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
205 KITCHEN_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.605 1.294   16.77 21.37 16.77 0.00 90.00 7.01 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
206 KITCHEN_FLR_6_WALL_NORTH_WINDOW Window KITCHEN_FLR_6_WALL_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.5119_SHGC_0.25 N/A 2.910 No 4.60 4.60 4.60 0.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
207 KITCHEN_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.605 1.294   34.86 52.03 34.86 90.00 90.00 17.07 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
208 KITCHEN_FLR_6_WALL_EAST_WINDOW Window KITCHEN_FLR_6_WALL_EAST Window5 Detailed Fenestration NONRESWINDOW_U_0.5119_SHGC_0.25 N/A 2.910 No 17.17 17.17 17.17 90.00 90.00 14.08 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
209 KITCHEN_FLR_6_WALL_1_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.605 1.294   9.34 13.94 9.34 180.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
210 KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW Window KITCHEN_FLR_6_WALL_1_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.5119_SHGC_0.25 N/A 2.910 No 4.60 4.60 4.60 180.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
211 KITCHEN_FLR_6_WALL_2_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 180.00 90.00 2.44 3.05 0.00 KITCHEN_FLR_6_WALL_2_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
212 KITCHEN_FLR_6_WALL_1_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 270.00 90.00 6.71 3.05 0.00 CORRIDOR_FLR_6_WALL_3_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
213 KITCHEN_FLR_6_WALL_2_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 270.00 90.00 10.36 3.05 0.00 DINING_FLR_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
214 KITCHEN_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   103.30 103.30 103.30 180.00 180.00 10.16 10.16 0.00 KITCHEN_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 6
215 KITCHEN_FLR_6_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.283 0.269   103.30 103.30 103.30 270.00 0.00 10.16 10.16 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 6
216 KITCHEN_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   206.61 206.61 206.61 0.00 90.00 206.61 1.00 0.00 KITCHEN_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
217 CORRIDOR_FLR_6_WALL_1_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.605 1.294   11.83 17.65 11.83 0.00 90.00 5.79 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
218 CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW Window CORRIDOR_FLR_6_WALL_1_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.5119_SHGC_0.25 N/A 2.910 No 5.82 5.82 5.82 0.00 90.00 4.78 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
219 CORRIDOR_FLR_6_WALL_2_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.605 1.294   10.58 15.79 10.58 0.00 90.00 5.18 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
220 CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW Window CORRIDOR_FLR_6_WALL_2_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.5119_SHGC_0.25 N/A 2.910 No 5.21 5.21 5.21 0.00 90.00 4.27 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
221 CORRIDOR_FLR_6_WALL_2_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.605 1.294   34.86 52.03 34.86 180.00 90.00 17.07 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
222 CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW Window CORRIDOR_FLR_6_WALL_2_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.5119_SHGC_0.25 N/A 2.910 No 17.17 17.17 17.17 180.00 90.00 14.08 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
223 CORRIDOR_FLR_6_WALL_3_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   97.55 97.55 97.55 0.00 90.00 32.00 3.05 0.00 BANQUET_FLR_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
224 CORRIDOR_FLR_6_WALL_4_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   104.98 104.98 104.98 0.00 90.00 34.44 3.05 0.00 CORRIDOR_FLR_6_WALL_4_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
225 CORRIDOR_FLR_6_WALL_1_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   183.95 183.95 183.95 180.00 90.00 60.35 3.05 0.00 CORRIDOR_FLR_6_WALL_1_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
226 CORRIDOR_FLR_6_WALL_1_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 270.00 90.00 3.66 3.05 0.00 CORRIDOR_FLR_6_WALL_1_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
227 CORRIDOR_FLR_6_WALL_2_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   40.88 40.88 40.88 270.00 90.00 13.41 3.05 0.00 CORRIDOR_FLR_6_WALL_2_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
228 CORRIDOR_FLR_6_WALL_3_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 270.00 90.00 10.36 3.05 0.00 BANQUET_FLR_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
229 CORRIDOR_FLR_6_WALL_1_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 90.00 90.00 10.36 3.05 0.00 BANQUET_FLR_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
230 CORRIDOR_FLR_6_WALL_2_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 90.00 90.00 10.36 3.05 0.00 DINING_FLR_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
231 CORRIDOR_FLR_6_WALL_3_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 90.00 90.00 6.71 3.05 0.00 KITCHEN_FLR_6_WALL_1_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
232 CORRIDOR_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   412.12 412.12 412.12 180.00 180.00 20.30 20.30 0.00 CORRIDOR_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 12
233 CORRIDOR_FLR_6_CEILING_1 Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.283 0.269   244.71 244.71 244.71 90.00 0.00 15.64 15.64 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 8
234 CORRIDOR_FLR_6_CEILING_2 Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.283 0.269   167.42 167.42 167.42 270.00 0.00 12.94 12.94 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 6
235 CORRIDOR_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   824.25 824.25 824.25 0.00 90.00 824.25 1.00 0.00 CORRIDOR_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0


Environment

Environment Name Environment Type Start Date End Date Start DayOfWeek Duration {#days} Source:Start DayOfWeek Use Daylight Saving Use Holidays Apply Weekend Holiday Rule Use Rain Values Use Snow Values Sky Temperature Model
1 RUNPERIOD 1 WeatherFileRunPeriod 01/01/2017 12/31/2017 Sunday 365 Use RunPeriod Specified Day No No No Yes Yes Clark and Allen


Environment:Special Days

Special Day Name Special Day Type Source Start Date Duration {#days}
1 NEW YEARS DAY Holiday InputFile 01/01 1Environment:Special Days


Environment:Daylight Saving

Daylight Saving Indicator Source Start Date End Date
1 Yes InputFile 03/12 11/05


Tabular Report

Style Unit Conversion
1 Commaandhtml commaandhtml


Warmup Convergence Information

Zone Name Environment Type/Name Average Warmup Temperature Difference {deltaC} Std Dev Warmup Temperature Difference {deltaC} Max Temperature Pass/Fail Convergence Min Temperature Pass/Fail Convergence Average Warmup Load Difference {W} Std Dev Warmup Load Difference {W} Heating Load Pass/Fail Convergence Cooling Load Pass/Fail Convergence
1 BASEMENT RunPeriod: RUNPERIOD 1 7.7305442462E-003 1.5487018400E-002 Pass Pass 1.0627947039E-002 2.5446983983E-002 Pass Pass
2 RETAIL_1_FLR_1 RunPeriod: RUNPERIOD 1 1.3593350206E-002 2.8883012214E-002 Pass Pass 0.3660999878 2.4073958640 Pass Pass
3 RETAIL_2_FLR_1 RunPeriod: RUNPERIOD 1 1.3799332100E-003 1.1649990569E-003 Pass Pass 2.0327417517E-002 3.5208897987E-002 Pass Pass
4 MECH_FLR_1 RunPeriod: RUNPERIOD 1 1.0157043107E-003 7.8084370870E-004 Pass Pass 0.9086243550 6.3008710258 Pass Pass
5 STORAGE_FLR_1 RunPeriod: RUNPERIOD 1 1.4878549323E-003 1.6702349797E-003 Pass Pass 0.3092371721 0.9401610031 Pass Pass
6 LAUNDRY_FLR_1 RunPeriod: RUNPERIOD 1 4.3185146701E-002 0.1347932161 Pass Pass 1.9421317468E-002 5.5750008308E-002 Pass Pass
7 CAFE_FLR_1 RunPeriod: RUNPERIOD 1 1.8630214901E-002 3.7296444615E-002 Pass Pass 2.3461047086E-002 3.5763814708E-002 Pass Pass
8 LOBBY_FLR_1 RunPeriod: RUNPERIOD 1 4.7304537206E-003 1.3057818208E-002 Pass Pass 1.8391364114E-002 3.6264759295E-002 Pass Pass
9 ROOM_1_FLR_3 RunPeriod: RUNPERIOD 1 5.6423041933E-002 0.2003652632 Pass Pass 0.2819050557 0.7888745911 Pass Pass
10 ROOM_2_FLR_3 RunPeriod: RUNPERIOD 1 7.4199703066E-002 0.2156391012 Pass Pass 0.3464172645 1.4038661445 Pass Pass
11 ROOM_3_MULT19_FLR_3 RunPeriod: RUNPERIOD 1 2.2072484525E-002 4.2222284154E-002 Pass Pass 3.4798390825E-002 6.5972266065E-002 Pass Pass
12 ROOM_4_MULT19_FLR_3 RunPeriod: RUNPERIOD 1 1.1653956601E-002 3.6281606234E-002 Pass Pass 0.7637174925 4.0645428285 Pass Pass
13 ROOM_5_FLR_3 RunPeriod: RUNPERIOD 1 4.1725369820E-002 0.1559024453 Pass Pass 0.7288922300 6.5892440933 Pass Pass
14 ROOM_6_FLR_3 RunPeriod: RUNPERIOD 1 3.8878621551E-002 0.1262851827 Pass Pass 0.1776677353 0.5397721288 Pass Pass
15 CORRIDOR_FLR_3 RunPeriod: RUNPERIOD 1 5.9714378938E-004 4.8932532477E-004 Pass Pass 3.6012715986E-002 4.6631527275E-002 Pass Pass
16 ROOM_1_FLR_6 RunPeriod: RUNPERIOD 1 6.7513285117E-002 0.2327659579 Pass Pass 0.2251483497 0.8394263877 Pass Pass
17 ROOM_2_FLR_6 RunPeriod: RUNPERIOD 1 8.3387706622E-002 0.2457464356 Pass Pass 0.7286721805 3.6423439265 Pass Pass
18 ROOM_3_MULT9_FLR_6 RunPeriod: RUNPERIOD 1 6.9722835383E-002 0.2690630098 Pass Pass 0.2243671792 0.6888343974 Pass Pass
19 BANQUET_FLR_6 RunPeriod: RUNPERIOD 1 1.4292083397E-002 5.2508950236E-002 Pass Pass 1.4354041174E-002 4.1912340814E-002 Pass Pass
20 DINING_FLR_6 RunPeriod: RUNPERIOD 1 1.6266682357E-002 5.5413079925E-002 Pass Pass 1.3266877497E-002 3.6644376722E-002 Pass Pass
21 KITCHEN_FLR_6 RunPeriod: RUNPERIOD 1 6.9922749918E-002 0.1131686437 Pass Pass 1.8358033662E-002 3.4322446567E-002 Pass Pass
22 CORRIDOR_FLR_6 RunPeriod: RUNPERIOD 1 1.3882369715E-003 1.0340313282E-003 Pass Pass 0.1486049918 0.3367597726 Pass Pass



Table of Contents

Report: Annual Heat Emissions Summary

For: Entire Facility

Timestamp: 2023-10-16 08:58:43

Heat Emission by Components

Envelope Convection Zone Exfiltration Zone Exhaust Air HVAC Relief Air HVAC Reject Heat Total
Heat Emissions [GJ] 2658.64 20.71 184.64 829.91 12331.40 16025.31



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2023-10-16 08:58:43

SizingPeriod:DesignDay

Maximum Dry Bulb [C] Daily Temperature Range [deltaC] Humidity Value Humidity Type Wind Speed [m/s] Wind Direction
TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 0.50 0.00 0.50 Wetbulb [C] 2.10 140.00
TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 40.80 13.30 18.50 Wetbulb [C] 4.80 310.00


Monthly Precipitation Summary

Monthly Total Precipitation from .epw [mm] Monthly Total Hours of Rain from .epw Monthly Total Precipitation in Site:Precipitation [mm] Monthly Total Roof Irrigation Depth [mm] Monthly Total Rain Collection Volume [m3]
Jan 3.00 2      
Feb 34.00 28      
Mar 40.00 18      
Apr 0.00 0      
May 0.00 0      
Jun 0.00 0      
Jul 81.00 18      
Aug 71.00 20      
Sep 27.00 12      
Oct 9.00 6      
Nov 35.00 14      
Dec 0.00 0      


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2023-10-16 08:58:43

Opaque Exterior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
BASEMENT_WALL_NORTH BASEMENT_WALL_NORTH_CFACTOR 1.00 0.845 0.940 211.13 211.13 0.00 90.00 N
BASEMENT_WALL_EAST BASEMENT_WALL_EAST_CFACTOR 1.00 0.845 0.940 55.76 55.76 90.00 90.00 E
BASEMENT_WALL_SOUTH BASEMENT_WALL_SOUTH_CFACTOR 1.00 0.845 0.940 211.13 211.13 180.00 90.00 S
BASEMENT_WALL_WEST BASEMENT_WALL_WEST_CFACTOR 1.00 0.845 0.940 55.76 55.76 270.00 90.00 W
RETAIL_1_FLR_1_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 1.028 1.214 45.89 22.63 180.00 90.00 S
RETAIL_1_FLR_1_WALL_WEST NONRES_EXT_WALL_GRD 0.30 1.028 1.214 22.95 22.95 270.00 90.00 W
RETAIL_1_FLR_1_CEILING NONRES_ROOF 0.55 0.273 0.283 67.07 67.07 180.00 0.00  
RETAIL_2_FLR_1_WALL_WEST NONRES_EXT_WALL_GRD 0.30 1.028 1.214 26.57 24.62 270.00 90.00 W
MECH_FLR_1_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 1.028 1.214 62.80 62.80 0.00 90.00 N
STORAGE_FLR_1_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 1.028 1.214 36.23 28.80 0.00 90.00 N
LAUNDRY_FLR_1_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 1.028 1.214 18.12 18.12 0.00 90.00 N
LAUNDRY_FLR_1_WALL_EAST NONRES_EXT_WALL_GRD 0.30 1.028 1.214 67.63 65.68 90.00 90.00 E
CAFE_FLR_1_WALL_EAST NONRES_EXT_WALL_GRD 0.30 1.028 1.214 22.95 21.00 90.00 90.00 E
CAFE_FLR_1_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 1.028 1.214 129.23 63.73 180.00 90.00 S
CAFE_FLR_1_CEILING NONRES_ROOF 0.55 0.273 0.283 188.86 188.86 180.00 0.00  
LOBBY_FLR_1_WALL_1_NORTH NONRES_EXT_WALL_GRD 0.30 1.028 1.214 213.77 209.87 0.00 90.00 N
LOBBY_FLR_1_WALL_2_NORTH NONRES_EXT_WALL_GRD 0.30 1.028 1.214 12.08 12.08 0.00 90.00 N
LOBBY_FLR_1_WALL_1_SOUTH NONRES_EXT_WALL_GRD 0.30 1.028 1.214 167.88 82.79 180.00 90.00 S
LOBBY_FLR_1_WALL_1_WEST NONRES_EXT_WALL_GRD 0.30 1.028 1.214 41.06 41.06 270.00 90.00 W
LOBBY_FLR_1_CEILING_2 NONRES_ROOF 0.55 0.273 0.283 245.35 245.35 180.00 0.00  
ROOM_1_FLR_3_WALL_SOUTH RES_EXT_WALL_MID 0.30 1.137 1.370 55.74 37.35 180.00 90.00 S
ROOM_1_FLR_3_WALL_WEST RES_EXT_WALL_MID 0.30 1.137 1.370 104.06 69.72 270.00 90.00 W
ROOM_2_FLR_3_WALL_NORTH RES_EXT_WALL_MID 0.30 1.137 1.370 55.74 37.35 0.00 90.00 N
ROOM_2_FLR_3_WALL_WEST RES_EXT_WALL_MID 0.30 1.137 1.370 104.05 69.71 270.00 90.00 W
ROOM_3_MULT19_FLR_3_WALL_SOUTH RES_EXT_WALL_MID 0.30 1.137 1.370 847.14 567.58 180.00 90.00 S
ROOM_4_MULT19_FLR_3_WALL_NORTH RES_EXT_WALL_MID 0.30 1.137 1.370 847.37 567.71 0.00 90.00 N
ROOM_5_FLR_3_WALL_EAST RES_EXT_WALL_MID 0.30 1.137 1.370 104.06 69.72 90.00 90.00 E
ROOM_5_FLR_3_WALL_SOUTH RES_EXT_WALL_MID 0.30 1.137 1.370 55.74 37.35 180.00 90.00 S
ROOM_6_FLR_3_WALL_NORTH RES_EXT_WALL_MID 0.30 1.137 1.370 55.74 37.35 0.00 90.00 N
ROOM_6_FLR_3_WALL_EAST RES_EXT_WALL_MID 0.30 1.137 1.370 104.05 69.71 90.00 90.00 E
CORRIDOR_FLR_3_WALL_1_NORTH NONRES_EXT_WALL_MID 0.30 1.245 1.530 70.60 47.31 0.00 90.00 N
CORRIDOR_FLR_3_WALL_2_NORTH NONRES_EXT_WALL_MID 0.30 1.245 1.530 26.01 17.42 0.00 90.00 N
CORRIDOR_FLR_3_WALL_1_SOUTH NONRES_EXT_WALL_MID 0.30 1.245 1.530 26.02 17.43 180.00 90.00 S
CORRIDOR_FLR_3_WALL_2_SOUTH NONRES_EXT_WALL_MID 0.30 1.245 1.530 70.60 47.31 180.00 90.00 S
ROOM_1_FLR_6_WALL_SOUTH RES_EXT_WALL_TOP 0.30 1.186 1.442 13.94 9.34 180.00 90.00 S
ROOM_1_FLR_6_WALL_WEST RES_EXT_WALL_TOP 0.30 1.186 1.442 26.01 17.43 270.00 90.00 W
ROOM_1_FLR_6_CEILING RES_ROOF 0.55 0.273 0.283 39.02 39.02 180.00 0.00  
ROOM_2_FLR_6_WALL_NORTH RES_EXT_WALL_TOP 0.30 1.186 1.442 13.94 9.34 0.00 90.00 N
ROOM_2_FLR_6_WALL_WEST RES_EXT_WALL_TOP 0.30 1.186 1.442 26.01 17.43 270.00 90.00 W
ROOM_2_FLR_6_CEILING RES_ROOF 0.55 0.273 0.283 39.02 39.02 180.00 0.00  
ROOM_3_MULT9_FLR_6_WALL_SOUTH RES_EXT_WALL_TOP 0.30 1.186 1.442 183.96 123.26 180.00 90.00 S
ROOM_3_MULT9_FLR_6_CEILING RES_ROOF 0.55 0.273 0.283 220.77 220.77 180.00 0.00  
BANQUET_FLR_6_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 1.294 1.605 97.55 65.36 0.00 90.00 N
BANQUET_FLR_6_CEILING NONRES_ROOF 0.55 0.273 0.283 331.66 331.66 180.00 0.00  
DINING_FLR_6_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 1.294 1.605 97.55 65.36 0.00 90.00 N
DINING_FLR_6_CEILING NONRES_ROOF 0.55 0.273 0.283 331.66 331.66 180.00 0.00  
KITCHEN_FLR_6_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 1.294 1.605 21.37 16.77 0.00 90.00 N
KITCHEN_FLR_6_WALL_EAST NONRES_EXT_WALL_TOP 0.30 1.294 1.605 52.03 34.86 90.00 90.00 E
KITCHEN_FLR_6_WALL_1_SOUTH NONRES_EXT_WALL_TOP 0.30 1.294 1.605 13.94 9.34 180.00 90.00 S
KITCHEN_FLR_6_CEILING NONRES_ROOF 0.55 0.273 0.283 103.30 103.30 270.00 0.00  
CORRIDOR_FLR_6_WALL_1_NORTH NONRES_EXT_WALL_TOP 0.30 1.294 1.605 17.65 11.83 0.00 90.00 N
CORRIDOR_FLR_6_WALL_2_NORTH NONRES_EXT_WALL_TOP 0.30 1.294 1.605 15.79 10.58 0.00 90.00 N
CORRIDOR_FLR_6_WALL_2_SOUTH NONRES_EXT_WALL_TOP 0.30 1.294 1.605 52.03 34.86 180.00 90.00 S
CORRIDOR_FLR_6_CEILING_1 NONRES_ROOF 0.55 0.273 0.283 244.71 244.71 90.00 0.00  
CORRIDOR_FLR_6_CEILING_2 NONRES_ROOF 0.55 0.273 0.283 167.42 167.42 270.00 0.00  


Opaque Interior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
BASEMENT_FLOOR BASEMENT_FLOOR 0.30 1.441 2.705 1978.83 1978.83 0.00 180.00  
BASEMENT_CEILING_1 NONRES_FLOOR_CEILING 0.30 0.186 0.196 67.07 67.07 180.00 0.00  
BASEMENT_CEILING_2 NONRES_FLOOR_CEILING 0.30 0.186 0.196 77.67 77.67 180.00 0.00  
BASEMENT_CEILING_3 NONRES_FLOOR_CEILING 0.30 0.186 0.196 164.24 164.24 180.00 0.00  
BASEMENT_CEILING_4 NONRES_FLOOR_CEILING 0.30 0.186 0.196 94.76 94.76 180.00 0.00  
BASEMENT_CEILING_5 NONRES_FLOOR_CEILING 0.30 0.186 0.196 78.04 78.04 180.00 0.00  
BASEMENT_CEILING_6 NONRES_FLOOR_CEILING 0.30 0.186 0.196 188.86 188.86 180.00 0.00  
BASEMENT_CEILING_7 NONRES_FLOOR_CEILING 0.30 0.186 0.196 1088.56 1088.56 180.00 0.00  
BASEMENT_CEILING_8 NONRES_FLOOR_CEILING 0.30 0.186 0.196 219.63 219.63 90.00 0.00  
RETAIL_1_FLR_1_WALL_NORTH INT_WALL 0.30 2.511 6.299 45.89 45.89 0.00 90.00 N
RETAIL_1_FLR_1_WALL_EAST INT_WALL 0.30 2.511 6.299 22.95 22.95 90.00 90.00 E
RETAIL_1_FLR_1_FLOOR NONRES_FLOOR 0.30 0.186 0.196 67.07 67.07 0.00 180.00  
RETAIL_2_FLR_1_WALL_SOUTH INT_WALL 0.30 2.511 6.299 45.89 45.89 180.00 90.00 S
RETAIL_2_FLR_1_WALL_NORTH INT_WALL 0.30 2.511 6.299 45.89 45.89 0.00 90.00 N
RETAIL_2_FLR_1_WALL_EAST INT_WALL 0.30 2.511 6.299 26.57 26.57 90.00 90.00 E
RETAIL_2_FLR_1_FLOOR NONRES_FLOOR 0.30 0.186 0.196 77.67 77.67 0.00 180.00  
RETAIL_2_FLR_1_CEILING NONRES_FLOOR_CEILING 0.30 0.188 0.196 77.67 77.67 180.00 0.00  
MECH_FLR_1_WALL_EAST INT_WALL 0.30 2.511 6.299 41.06 41.06 90.00 90.00 E
MECH_FLR_1_WALL_SOUTH INT_WALL 0.30 2.511 6.299 62.80 62.80 180.00 90.00 S
MECH_FLR_1_WALL_WEST INT_WALL 0.30 2.511 6.299 41.06 41.06 270.00 90.00 W
MECH_FLR_1_FLOOR NONRES_FLOOR 0.30 0.186 0.196 164.24 164.24 0.00 180.00  
MECH_FLR_1_CEILING NONRES_FLOOR_CEILING 0.30 0.188 0.196 164.24 164.24 180.00 0.00  
STORAGE_FLR_1_WALL_EAST INT_WALL 0.30 2.511 6.299 41.06 41.06 90.00 90.00 E
STORAGE_FLR_1_WALL_SOUTH INT_WALL 0.30 2.511 6.299 36.23 36.23 180.00 90.00 S
STORAGE_FLR_1_WALL_WEST INT_WALL 0.30 2.511 6.299 41.06 41.06 270.00 90.00 W
STORAGE_FLR_1_FLOOR NONRES_FLOOR 0.30 0.186 0.196 94.76 94.76 0.00 180.00  
STORAGE_FLR_1_CEILING NONRES_FLOOR_CEILING 0.30 0.188 0.196 94.76 94.76 180.00 0.00  
LAUNDRY_FLR_1_WALL_SOUTH INT_WALL 0.30 2.511 6.299 18.12 18.12 180.00 90.00 S
LAUNDRY_FLR_1_WALL_WEST INT_WALL 0.30 2.511 6.299 67.63 67.63 270.00 90.00 W
LAUNDRY_FLR_1_FLOOR NONRES_FLOOR 0.30 0.186 0.196 78.04 78.04 0.00 180.00  
LAUNDRY_FLR_1_CEILING NONRES_FLOOR_CEILING 0.30 0.188 0.196 78.04 78.04 180.00 0.00  
CAFE_FLR_1_WALL_1_NORTH INT_WALL 0.30 2.511 6.299 111.11 111.11 0.00 90.00 N
CAFE_FLR_1_WALL_2_NORTH INT_WALL 0.30 2.511 6.299 18.12 18.12 0.00 90.00 N
CAFE_FLR_1_WALL_WEST INT_WALL 0.30 2.511 6.299 22.95 22.95 270.00 90.00 W
CAFE_FLR_1_FLOOR NONRES_FLOOR 0.30 0.186 0.196 188.86 188.86 0.00 180.00  
LOBBY_FLR_1_WALL_2_SOUTH INT_WALL 0.30 2.511 6.299 45.89 45.89 180.00 90.00 S
LOBBY_FLR_1_WALL_3_SOUTH INT_WALL 0.30 2.511 6.299 111.11 111.11 180.00 90.00 S
LOBBY_FLR_1_WALL_2_WEST INT_WALL 0.30 2.511 6.299 22.95 22.95 270.00 90.00 W
LOBBY_FLR_1_WALL_3_WEST INT_WALL 0.30 2.511 6.299 26.57 26.57 270.00 90.00 W
LOBBY_FLR_1_WALL_4_WEST INT_WALL 0.30 2.511 6.299 41.06 41.06 270.00 90.00 W
LOBBY_FLR_1_WALL_3_NORTH INT_WALL 0.30 2.511 6.299 62.80 62.80 0.00 90.00 N
LOBBY_FLR_1_WALL_4_NORTH INT_WALL 0.30 2.511 6.299 36.23 36.23 0.00 90.00 N
LOBBY_FLR_1_WALL_1_EAST INT_WALL 0.30 2.511 6.299 41.06 41.06 90.00 90.00 E
LOBBY_FLR_1_WALL_2_EAST INT_WALL 0.30 2.511 6.299 22.95 22.95 90.00 90.00 E
LOBBY_FLR_1_WALL_3_EAST INT_WALL 0.30 2.511 6.299 67.63 67.63 90.00 90.00 E
LOBBY_FLR_1_FLOOR_1 NONRES_FLOOR 0.30 0.186 0.196 1088.56 1088.56 180.00 180.00  
LOBBY_FLR_1_FLOOR_2 NONRES_FLOOR 0.30 0.186 0.196 219.63 219.63 90.00 180.00  
LOBBY_FLR_1_CEILING_1 NONRES_FLOOR_CEILING 0.30 0.188 0.196 1062.83 1062.83 270.00 0.00  
ROOM_1_FLR_3_WALL_NORTH INT_WALL 0.30 2.511 6.299 55.74 55.74 0.00 90.00 N
ROOM_1_FLR_3_WALL_EAST INT_WALL 0.30 2.511 6.299 104.06 104.06 90.00 90.00 E
ROOM_1_FLR_3_FLOOR NONRES_FLOOR 0.30 0.185 0.196 156.09 156.09 0.00 180.00  
ROOM_1_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 0.188 0.196 156.09 156.09 180.00 0.00  
ROOM_2_FLR_3_WALL_EAST INT_WALL 0.30 2.511 6.299 104.05 104.05 90.00 90.00 E
ROOM_2_FLR_3_WALL_SOUTH INT_WALL 0.30 2.511 6.299 55.74 55.74 180.00 90.00 S
ROOM_2_FLR_3_FLOOR NONRES_FLOOR 0.30 0.185 0.196 156.07 156.07 0.00 180.00  
ROOM_2_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 0.188 0.196 156.07 156.07 180.00 0.00  
ROOM_3_MULT19_FLR_3_WALL_NORTH INT_WALL 0.30 2.511 6.299 847.14 847.14 0.00 90.00 N
ROOM_3_MULT19_FLR_3_WALL_EAST INT_WALL 0.30 2.511 6.299 1553.43 1553.43 90.00 90.00 E
ROOM_3_MULT19_FLR_3_WALL_WEST INT_WALL 0.30 2.511 6.299 1553.43 1553.43 270.00 90.00 W
ROOM_3_MULT19_FLR_3_FLOOR NONRES_FLOOR 0.30 0.185 0.196 1863.81 1863.81 0.00 180.00  
ROOM_3_MULT19_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 0.188 0.196 1863.81 1863.81 180.00 0.00  
ROOM_4_MULT19_FLR_3_WALL_EAST INT_WALL 0.30 2.511 6.299 1553.43 1553.43 90.00 90.00 E
ROOM_4_MULT19_FLR_3_WALL_SOUTH INT_WALL 0.30 2.511 6.299 847.37 847.37 180.00 90.00 S
ROOM_4_MULT19_FLR_3_WALL_WEST INT_WALL 0.30 2.511 6.299 1553.43 1553.43 270.00 90.00 W
ROOM_4_MULT19_FLR_3_FLOOR NONRES_FLOOR 0.30 0.185 0.196 1864.32 1864.32 0.00 180.00  
ROOM_4_MULT19_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 0.188 0.196 1864.32 1864.32 180.00 0.00  
ROOM_5_FLR_3_WALL_NORTH INT_WALL 0.30 2.511 6.299 55.74 55.74 0.00 90.00 N
ROOM_5_FLR_3_WALL_WEST INT_WALL 0.30 2.511 6.299 104.06 104.06 270.00 90.00 W
ROOM_5_FLR_3_FLOOR NONRES_FLOOR 0.30 0.185 0.196 156.09 156.09 0.00 180.00  
ROOM_5_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 0.188 0.196 156.09 156.09 180.00 0.00  
ROOM_6_FLR_3_WALL_SOUTH INT_WALL 0.30 2.511 6.299 55.74 55.74 180.00 90.00 S
ROOM_6_FLR_3_WALL_WEST INT_WALL 0.30 2.511 6.299 104.05 104.05 270.00 90.00 W
ROOM_6_FLR_3_FLOOR NONRES_FLOOR 0.30 0.185 0.196 156.07 156.07 0.00 180.00  
ROOM_6_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 0.188 0.196 156.07 156.07 180.00 0.00  
CORRIDOR_FLR_3_WALL_3_NORTH INT_WALL 0.30 2.511 6.299 847.28 847.28 0.00 90.00 N
CORRIDOR_FLR_3_WALL_1_EAST INT_WALL 0.30 2.511 6.299 81.76 81.76 90.00 90.00 E
CORRIDOR_FLR_3_WALL_2_EAST INT_WALL 0.30 2.511 6.299 81.76 81.76 90.00 90.00 E
CORRIDOR_FLR_3_WALL_3_EAST INT_WALL 0.30 2.511 6.299 104.06 104.06 90.00 90.00 E
CORRIDOR_FLR_3_WALL_4_EAST INT_WALL 0.30 2.511 6.299 104.05 104.05 90.00 90.00 E
CORRIDOR_FLR_3_WALL_3_SOUTH INT_WALL 0.30 2.511 6.299 847.27 847.27 180.00 90.00 S
CORRIDOR_FLR_3_WALL_1_WEST INT_WALL 0.30 2.511 6.299 81.76 81.76 270.00 90.00 W
CORRIDOR_FLR_3_WALL_2_WEST INT_WALL 0.30 2.511 6.299 81.76 81.76 270.00 90.00 W
CORRIDOR_FLR_3_WALL_3_WEST INT_WALL 0.30 2.511 6.299 104.06 104.06 270.00 90.00 W
CORRIDOR_FLR_3_WALL_4_WEST INT_WALL 0.30 2.511 6.299 104.05 104.05 270.00 90.00 W
CORRIDOR_FLR_3_FLOOR_1 NONRES_FLOOR 0.30 0.185 0.196 297.29 297.29 180.00 180.00  
CORRIDOR_FLR_3_FLOOR_2 NONRES_FLOOR 0.30 0.185 0.196 963.06 963.06 270.00 180.00  
CORRIDOR_FLR_3_FLOOR_3 NONRES_FLOOR 0.30 0.185 0.196 297.26 297.26 90.00 180.00  
CORRIDOR_FLR_3_CEILING_1 NONRES_FLOOR_CEILING 0.30 0.188 0.196 297.29 297.29 90.00 0.00  
CORRIDOR_FLR_3_CEILING_2 NONRES_FLOOR_CEILING 0.30 0.188 0.196 963.06 963.06 90.00 0.00  
CORRIDOR_FLR_3_CEILING_3 NONRES_FLOOR_CEILING 0.30 0.188 0.196 297.26 297.26 90.00 0.00  
ROOM_1_FLR_6_WALL_NORTH INT_WALL 0.30 2.511 6.299 13.94 13.94 0.00 90.00 N
ROOM_1_FLR_6_WALL_EAST INT_WALL 0.30 2.511 6.299 26.01 26.01 90.00 90.00 E
ROOM_1_FLR_6_FLOOR NONRES_FLOOR 0.30 0.185 0.196 39.02 39.02 0.00 180.00  
ROOM_2_FLR_6_WALL_EAST INT_WALL 0.30 2.511 6.299 26.01 26.01 90.00 90.00 E
ROOM_2_FLR_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 13.94 13.94 180.00 90.00 S
ROOM_2_FLR_6_FLOOR NONRES_FLOOR 0.30 0.185 0.196 39.02 39.02 0.00 180.00  
ROOM_3_MULT9_FLR_6_WALL_NORTH INT_WALL 0.30 2.511 6.299 183.96 183.96 0.00 90.00 N
ROOM_3_MULT9_FLR_6_WALL_EAST INT_WALL 0.30 2.511 6.299 100.35 100.35 90.00 90.00 E
ROOM_3_MULT9_FLR_6_WALL_WEST INT_WALL 0.30 2.511 6.299 100.35 100.35 270.00 90.00 W
ROOM_3_MULT9_FLR_6_FLOOR NONRES_FLOOR 0.30 0.185 0.196 220.77 220.77 0.00 180.00  
BANQUET_FLR_6_WALL_EAST INT_WALL 0.30 2.511 6.299 31.59 31.59 90.00 90.00 E
BANQUET_FLR_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 97.55 97.55 180.00 90.00 S
BANQUET_FLR_6_WALL_WEST INT_WALL 0.30 2.511 6.299 31.59 31.59 270.00 90.00 W
BANQUET_FLR_6_FLOOR NONRES_FLOOR 0.30 0.185 0.196 331.66 331.66 0.00 180.00  
DINING_FLR_6_WALL_EAST INT_WALL 0.30 2.511 6.299 31.59 31.59 90.00 90.00 E
DINING_FLR_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 97.55 97.55 180.00 90.00 S
DINING_FLR_6_WALL_WEST INT_WALL 0.30 2.511 6.299 31.59 31.59 270.00 90.00 W
DINING_FLR_6_FLOOR NONRES_FLOOR 0.30 0.185 0.196 331.66 331.66 0.00 180.00  
KITCHEN_FLR_6_WALL_2_SOUTH INT_WALL 0.30 2.511 6.299 7.43 7.43 180.00 90.00 S
KITCHEN_FLR_6_WALL_1_WEST INT_WALL 0.30 2.511 6.299 20.44 20.44 270.00 90.00 W
KITCHEN_FLR_6_WALL_2_WEST INT_WALL 0.30 2.511 6.299 31.59 31.59 270.00 90.00 W
KITCHEN_FLR_6_FLOOR NONRES_FLOOR 0.30 0.185 0.196 103.30 103.30 180.00 180.00  
CORRIDOR_FLR_6_WALL_3_NORTH INT_WALL 0.30 2.511 6.299 97.55 97.55 0.00 90.00 N
CORRIDOR_FLR_6_WALL_4_NORTH INT_WALL 0.30 2.511 6.299 104.98 104.98 0.00 90.00 N
CORRIDOR_FLR_6_WALL_1_SOUTH INT_WALL 0.30 2.511 6.299 183.95 183.95 180.00 90.00 S
CORRIDOR_FLR_6_WALL_1_WEST INT_WALL 0.30 2.511 6.299 11.15 11.15 270.00 90.00 W
CORRIDOR_FLR_6_WALL_2_WEST INT_WALL 0.30 2.511 6.299 40.88 40.88 270.00 90.00 W
CORRIDOR_FLR_6_WALL_3_WEST INT_WALL 0.30 2.511 6.299 31.59 31.59 270.00 90.00 W
CORRIDOR_FLR_6_WALL_1_EAST INT_WALL 0.30 2.511 6.299 31.59 31.59 90.00 90.00 E
CORRIDOR_FLR_6_WALL_2_EAST INT_WALL 0.30 2.511 6.299 31.59 31.59 90.00 90.00 E
CORRIDOR_FLR_6_WALL_3_EAST INT_WALL 0.30 2.511 6.299 20.44 20.44 90.00 90.00 E
CORRIDOR_FLR_6_FLOOR NONRES_FLOOR 0.30 0.185 0.196 412.12 412.12 180.00 180.00  
BASEMENT_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 3957.66   0.00 90.00 N
RETAIL_1_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 134.14   0.00 90.00 N
RETAIL_2_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 155.34   0.00 90.00 N
MECH_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 328.49   0.00 90.00 N
STORAGE_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 189.52   0.00 90.00 N
LAUNDRY_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 156.08   0.00 90.00 N
CAFE_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 377.72   0.00 90.00 N
LOBBY_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 2616.37   0.00 90.00 N
ROOM_1_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 312.18   0.00 90.00 N
ROOM_2_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 312.14   0.00 90.00 N
ROOM_3_MULT19_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 3727.63   0.00 90.00 N
ROOM_4_MULT19_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 3728.64   0.00 90.00 N
ROOM_5_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 312.18   0.00 90.00 N
ROOM_6_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 312.14   0.00 90.00 N
CORRIDOR_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 3115.24   0.00 90.00 N
ROOM_1_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 78.04   0.00 90.00 N
ROOM_2_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 78.03   0.00 90.00 N
ROOM_3_MULT9_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 441.55   0.00 90.00 N
BANQUET_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 663.31   0.00 90.00 N
DINING_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 663.31   0.00 90.00 N
KITCHEN_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 206.61   0.00 90.00 N
CORRIDOR_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 824.25   0.00 90.00 N


Exterior Fenestration

Construction Frame and Divider Glass Area [m2] Frame Area [m2] Divider Area [m2] Area of One Opening [m2] Area of Multiplied Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Frame Conductance [W/m2-K] Divider Conductance [W/m2-K] NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW NONRESWINDOW_U_0.5119_SHGC_0.25   23.26 0.00 0.00 23.26 23.26 2.910 0.251 0.251             No RETAIL_1_FLR_1_WALL_SOUTH 180.00 90.00 S
CAFE_FLR_1_WALL_SOUTH_WINDOW NONRESWINDOW_U_0.5119_SHGC_0.25   65.50 0.00 0.00 65.50 65.50 2.910 0.251 0.251             No CAFE_FLR_1_WALL_SOUTH 180.00 90.00 S
LOBBY_FLR_1_WALL_SOUTH_WINDOW NONRESWINDOW_U_0.5119_SHGC_0.25   85.08 0.00 0.00 85.08 85.08 2.910 0.251 0.251             No LOBBY_FLR_1_WALL_1_SOUTH 180.00 90.00 S
ROOM_1_FLR_3_WALL_SOUTH_WINDOW RESWINDOW_U_0.5119_SHGC_0.25   4.60 0.00 0.00 4.60 18.40 2.910 0.251 0.251             No ROOM_1_FLR_3_WALL_SOUTH 180.00 90.00 S
ROOM_1_FLR_3_WALL_WEST_WINDOW RESWINDOW_U_0.5119_SHGC_0.25   8.58 0.00 0.00 8.58 34.34 2.910 0.251 0.251             No ROOM_1_FLR_3_WALL_WEST 270.00 90.00 W
ROOM_2_FLR_3_WALL_NORTH_WINDOW RESWINDOW_U_0.5119_SHGC_0.25   4.60 0.00 0.00 4.60 18.40 2.910 0.251 0.251             No ROOM_2_FLR_3_WALL_NORTH 0.00 90.00 N
ROOM_2_FLR_3_WALL_WEST_WINDOW RESWINDOW_U_0.5119_SHGC_0.25   8.58 0.00 0.00 8.58 34.34 2.910 0.251 0.251             No ROOM_2_FLR_3_WALL_WEST 270.00 90.00 W
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW RESWINDOW_U_0.5119_SHGC_0.25   3.68 0.00 0.00 3.68 279.56 2.910 0.251 0.251             No ROOM_3_MULT19_FLR_3_WALL_SOUTH 180.00 90.00 S
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW RESWINDOW_U_0.5119_SHGC_0.25   3.68 0.00 0.00 3.68 279.65 2.910 0.251 0.251             No ROOM_4_MULT19_FLR_3_WALL_NORTH 0.00 90.00 N
ROOM_5_FLR_3_WALL_EAST_WINDOW RESWINDOW_U_0.5119_SHGC_0.25   8.58 0.00 0.00 8.58 34.34 2.910 0.251 0.251             No ROOM_5_FLR_3_WALL_EAST 90.00 90.00 E
ROOM_5_FLR_3_WALL_SOUTH_WINDOW RESWINDOW_U_0.5119_SHGC_0.25   4.60 0.00 0.00 4.60 18.40 2.910 0.251 0.251             No ROOM_5_FLR_3_WALL_SOUTH 180.00 90.00 S
ROOM_6_FLR_3_WALL_NORTH_WINDOW RESWINDOW_U_0.5119_SHGC_0.25   4.60 0.00 0.00 4.60 18.40 2.910 0.251 0.251             No ROOM_6_FLR_3_WALL_NORTH 0.00 90.00 N
ROOM_6_FLR_3_WALL_EAST_WINDOW RESWINDOW_U_0.5119_SHGC_0.25   8.58 0.00 0.00 8.58 34.34 2.910 0.251 0.251             No ROOM_6_FLR_3_WALL_EAST 90.00 90.00 E
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW NONRESWINDOW_U_0.5119_SHGC_0.25   5.82 0.00 0.00 5.82 23.30 2.910 0.251 0.251             No CORRIDOR_FLR_3_WALL_1_NORTH 0.00 90.00 N
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW NONRESWINDOW_U_0.5119_SHGC_0.25   2.15 0.00 0.00 2.15 8.59 2.910 0.251 0.251             No CORRIDOR_FLR_3_WALL_2_NORTH 0.00 90.00 N
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW NONRESWINDOW_U_0.5119_SHGC_0.25   2.15 0.00 0.00 2.15 8.58 2.910 0.251 0.251             No CORRIDOR_FLR_3_WALL_1_SOUTH 180.00 90.00 S
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW NONRESWINDOW_U_0.5119_SHGC_0.25   5.82 0.00 0.00 5.82 23.30 2.910 0.251 0.251             No CORRIDOR_FLR_3_WALL_2_SOUTH 180.00 90.00 S
ROOM_1_FLR_6_WALL_SOUTH_WINDOW RESWINDOW_U_0.5119_SHGC_0.25   4.60 0.00 0.00 4.60 4.60 2.910 0.251 0.251             No ROOM_1_FLR_6_WALL_SOUTH 180.00 90.00 S
ROOM_1_FLR_6_WALL_WEST_WINDOW RESWINDOW_U_0.5119_SHGC_0.25   8.58 0.00 0.00 8.58 8.58 2.910 0.251 0.251             No ROOM_1_FLR_6_WALL_WEST 270.00 90.00 W
ROOM_2_FLR_6_WALL_NORTH_WINDOW RESWINDOW_U_0.5119_SHGC_0.25   4.60 0.00 0.00 4.60 4.60 2.910 0.251 0.251             No ROOM_2_FLR_6_WALL_NORTH 0.00 90.00 N
ROOM_2_FLR_6_WALL_WEST_WINDOW RESWINDOW_U_0.5119_SHGC_0.25   8.58 0.00 0.00 8.58 8.58 2.910 0.251 0.251             No ROOM_2_FLR_6_WALL_WEST 270.00 90.00 W
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW RESWINDOW_U_0.5119_SHGC_0.25   6.74 0.00 0.00 6.74 60.70 2.910 0.251 0.251             No ROOM_3_MULT9_FLR_6_WALL_SOUTH 180.00 90.00 S
BANQUET_FLR_6_WALL_NORTH_WINDOW NONRESWINDOW_U_0.5119_SHGC_0.25   32.19 0.00 0.00 32.19 32.19 2.910 0.251 0.251             No BANQUET_FLR_6_WALL_NORTH 0.00 90.00 N
DINING_FLR_6_WALL_NORTH_WINDOW NONRESWINDOW_U_0.5119_SHGC_0.25   32.19 0.00 0.00 32.19 32.19 2.910 0.251 0.251             No DINING_FLR_6_WALL_NORTH 0.00 90.00 N
KITCHEN_FLR_6_WALL_NORTH_WINDOW NONRESWINDOW_U_0.5119_SHGC_0.25   4.60 0.00 0.00 4.60 4.60 2.910 0.251 0.251             No KITCHEN_FLR_6_WALL_NORTH 0.00 90.00 N
KITCHEN_FLR_6_WALL_EAST_WINDOW NONRESWINDOW_U_0.5119_SHGC_0.25   17.17 0.00 0.00 17.17 17.17 2.910 0.251 0.251             No KITCHEN_FLR_6_WALL_EAST 90.00 90.00 E
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW NONRESWINDOW_U_0.5119_SHGC_0.25   4.60 0.00 0.00 4.60 4.60 2.910 0.251 0.251             No KITCHEN_FLR_6_WALL_1_SOUTH 180.00 90.00 S
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW NONRESWINDOW_U_0.5119_SHGC_0.25   5.82 0.00 0.00 5.82 5.82 2.910 0.251 0.251             No CORRIDOR_FLR_6_WALL_1_NORTH 0.00 90.00 N
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW NONRESWINDOW_U_0.5119_SHGC_0.25   5.21 0.00 0.00 5.21 5.21 2.910 0.251 0.251             No CORRIDOR_FLR_6_WALL_2_NORTH 0.00 90.00 N
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW NONRESWINDOW_U_0.5119_SHGC_0.25   17.17 0.00 0.00 17.17 17.17 2.910 0.251 0.251             No CORRIDOR_FLR_6_WALL_2_SOUTH 180.00 90.00 S
Total or Average             1213.79 2.910 0.251 0.251                      
North Total or Average             432.95 2.910 0.251 0.251                      
Non-North Total or Average             780.84 2.910 0.251 0.251                      


Exterior Fenestration Shaded State

Frame and Divider Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance
None                


Interior Fenestration

Construction Area of One Opening [m2] Area of Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance
Total or Average     0.00 - - -


Exterior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
RETAIL_2_FLR_1_WALL_WEST_DOOR SWINGING DOOR_CON 2.281 3.464 1.95 RETAIL_2_FLR_1_WALL_WEST
STORAGE_FLR_1_WALL_NORTH_ROLLDOOR OVERHEAD DOOR_CON 1.016 1.198 7.43 STORAGE_FLR_1_WALL_NORTH
LAUNDRY_FLR_1_WALL_EAST_DOOR SWINGING DOOR_CON 2.281 3.464 1.95 LAUNDRY_FLR_1_WALL_EAST
CAFE_FLR_1_WALL_EAST_DOOR SWINGING DOOR_CON 2.281 3.464 1.95 CAFE_FLR_1_WALL_EAST
LOBBY_FLR_1_WALL_1_NORTH_DOOR1 SWINGING DOOR_CON 2.281 3.464 1.95 LOBBY_FLR_1_WALL_1_NORTH
LOBBY_FLR_1_WALL_1_NORTH_DOOR2 SWINGING DOOR_CON 2.281 3.464 1.95 LOBBY_FLR_1_WALL_1_NORTH


Interior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
None          



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2023-10-16 08:58:43

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
CAFE_FLR_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
LOBBY_FLR_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
ROOM_1_FLR_3_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
ROOM_1_FLR_3_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
ROOM_2_FLR_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_3_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
ROOM_5_FLR_3_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
ROOM_5_FLR_3_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
ROOM_6_FLR_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
ROOM_6_FLR_3_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
ROOM_1_FLR_6_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
ROOM_1_FLR_6_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
ROOM_2_FLR_6_WALL_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_6_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
BANQUET_FLR_6_WALL_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
DINING_FLR_6_WALL_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
KITCHEN_FLR_6_WALL_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
KITCHEN_FLR_6_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00


Window Control

Name Type Shaded Construction Control Glare Control
None          



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2023-10-16 08:58:43

Interior Lighting

Zone Name Space Name Space Type Lighting Power Density [W/m2] Space Area [m2] Total Power [W] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [GJ]
BASEMENT_LIGHTS BASEMENT BASEMENT GENERAL 8.7495 1978.83 17313.73 LightsWired LTG_SCH_BASEMENT 50.91 168.00 50.86 0.0000 Y 165.29
RETAIL_1_FLR_1_LIGHTS RETAIL_1_FLR_1 RETAIL_1_FLR_1 GENERAL 13.0124 67.07 872.76 LightsWired LTG_SCH_RETAIL 51.36 168.00 51.30 0.0000 Y 8.40
RETAIL_2_FLR_1_LIGHTS RETAIL_2_FLR_1 RETAIL_2_FLR_1 GENERAL 13.0124 77.67 1010.66 LightsWired LTG_SCH_RETAIL 51.36 168.00 51.30 0.0000 Y 9.73
MECH_FLR_1_LIGHTS MECH_FLR_1 MECH_FLR_1 GENERAL 10.0642 164.24 1652.98 LightsWired LTG_SCH_MECHANIC 58.69 168.00 58.63 0.0000 Y 18.19
STORAGE_FLR_1_LIGHTS STORAGE_FLR_1 STORAGE_FLR_1 GENERAL 7.3195 94.76 693.59 LightsWired LTG_SCH_STORAGE 25.68 168.00 25.65 0.0000 Y 3.34
LAUNDRY_FLR_1_LIGHTS LAUNDRY_FLR_1 LAUNDRY_FLR_1 GENERAL 5.4896 78.04 428.40 LightsWired LTG_SCH_LAUNDRY 51.36 168.00 51.30 0.0000 Y 4.13
CAFE_FLR_1_LIGHTS CAFE_FLR_1 CAFE_FLR_1 GENERAL 12.8090 188.86 2419.14 LightsWired LTG_SCH_DINING 58.69 168.00 58.63 0.0000 Y 26.62
LOBBY_FLR_1_LIGHTS LOBBY_FLR_1 LOBBY_FLR_1 GENERAL 10.0642 1308.19 13165.91 LightsWired LTG_SCH_LOBBY 58.69 168.00 58.63 0.0000 Y 144.89
ROOM_1_FLR_3_LIGHTS ROOM_1_FLR_3 ROOM_1_FLR_3 GENERAL 10.0642 156.09 1570.91 LightsWired LTG_SCH_GUESTROOM 69.03 168.00 69.21 0.0000 Y 20.41
ROOM_2_FLR_3_LIGHTS ROOM_2_FLR_3 ROOM_2_FLR_3 GENERAL 10.0642 156.07 1570.72 LightsWired LTG_SCH_GUESTROOM 69.03 168.00 69.21 0.0000 Y 20.41
ROOM_3_MULT19_FLR_3_LIGHTS ROOM_3_MULT19_FLR_3 ROOM_3_MULT19_FLR_3 GENERAL 10.0642 1863.81 18757.86 LightsWired LTG_SCH_GUESTROOM 69.03 168.00 69.21 0.0000 Y 243.70
ROOM_4_MULT19_FLR_3_LIGHTS ROOM_4_MULT19_FLR_3 ROOM_4_MULT19_FLR_3 GENERAL 10.0642 1864.32 18762.99 LightsWired LTG_SCH_GUESTROOM 69.03 168.00 69.21 0.0000 Y 243.77
ROOM_5_FLR_3_LIGHTS ROOM_5_FLR_3 ROOM_5_FLR_3 GENERAL 10.0642 156.09 1570.91 LightsWired LTG_SCH_GUESTROOM 69.03 168.00 69.21 0.0000 Y 20.41
ROOM_6_FLR_3_LIGHTS ROOM_6_FLR_3 ROOM_6_FLR_3 GENERAL 10.0642 156.07 1570.72 LightsWired LTG_SCH_GUESTROOM 69.03 168.00 69.21 0.0000 Y 20.41
CORRIDOR_FLR_3_LIGHTS CORRIDOR_FLR_3 CORRIDOR_FLR_3 GENERAL 3.6597 1557.62 5700.46 LightsWired LTG_SCH_CORRIDOR 58.69 168.00 58.63 0.0000 Y 62.73
ROOM_1_FLR_6_LIGHTS ROOM_1_FLR_6 ROOM_1_FLR_6 GENERAL 10.0642 39.02 392.73 LightsWired LTG_SCH_GUESTROOM 69.03 168.00 69.21 0.0000 Y 5.10
ROOM_2_FLR_6_LIGHTS ROOM_2_FLR_6 ROOM_2_FLR_6 GENERAL 10.0642 39.02 392.68 LightsWired LTG_SCH_GUESTROOM 69.03 168.00 69.21 0.0000 Y 5.10
ROOM_3_MULT9_FLR_6_LIGHTS ROOM_3_MULT9_FLR_6 ROOM_3_MULT9_FLR_6 GENERAL 10.0642 220.77 2221.93 LightsWired LTG_SCH_GUESTROOM 69.03 168.00 69.21 0.0000 Y 28.87
BANQUET_FLR_6_LIGHTS BANQUET_FLR_6 BANQUET_FLR_6 GENERAL 12.8090 331.66 4248.21 LightsWired LTG_SCH_DINING 58.69 168.00 58.63 0.0000 Y 46.75
DINING_FLR_6_LIGHTS DINING_FLR_6 DINING_FLR_6 GENERAL 12.8090 331.66 4248.21 LightsWired LTG_SCH_DINING 58.69 168.00 58.63 0.0000 Y 46.75
KITCHEN_FLR_6_LIGHTS KITCHEN_FLR_6 KITCHEN_FLR_6 GENERAL 10.9792 103.30 1134.20 LightsWired LTG_SCH_KITCHEN 58.69 168.00 58.63 0.0000 Y 12.48
CORRIDOR_FLR_6_LIGHTS CORRIDOR_FLR_6 CORRIDOR_FLR_6 GENERAL 3.6597 412.12 1508.26 LightsWired LTG_SCH_CORRIDOR 58.69 168.00 58.63 0.0000 Y 16.60
Interior Lighting Total       8.9207 11345.29 101207.97               559.10


Daylighting

Zone Control Name Daylighting Method Control Type Fraction Controlled Lighting Installed in Zone [W] Lighting Controlled [W]
None              


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [GJ]
EXTERIOR FACADE LIGHTING 16690.39 AstronomicalClock -   83.79 83.79 262.50
Exterior Lighting Total 16690.39           262.50



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2023-10-16 08:58:43

Central Plant

Type Reference Capacity [W] Reference Efficiency [W/W] Rated Capacity [W] Rated Efficiency [W/W] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
HEATSYS1 BOILER Boiler:HotWater 416824.50 0.80        
COOLSYS1 CHILLER1 Chiller:Electric:EIR 1147742.06 2.80 1147943.80 2.80 3.72 12.68


Cooling Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Sensible Capacity [W] Nominal Latent Capacity [W] Nominal Sensible Heat Ratio Nominal Efficiency [W/W] Nominal Coil UA Value [W/C] Nominal Coil Surface Area [m2]
ROOM_1_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 14333.80 22906.95 17355.99 5550.96 0.76 - 3028.13 30.71
ROOM_2_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 14236.94 22752.64 17239.03 5513.61 0.76 - 3007.91 30.51
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 86002.93 138105.24 104575.20 33530.04 0.76 - 18511.08 187.75
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 94466.48 149091.03 112073.05 37017.98 0.75 - 19470.15 197.48
ROOM_5_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 12618.19 20172.89 15283.75 4889.14 0.76 - 2669.59 27.08
ROOM_6_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 12536.05 20042.10 15184.61 4857.49 0.76 - 2652.48 26.90
ROOM_1_FLR_6 FAN COIL COOLING COIL Coil:Cooling:Water 3879.41 6198.79 4696.75 1502.04 0.76 - 819.09 8.31
ROOM_2_FLR_6 FAN COIL COOLING COIL Coil:Cooling:Water 3850.60 6152.83 4661.91 1490.91 0.76 - 813.04 8.25
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Coil:Cooling:Water 17593.47 27961.22 21135.97 6825.26 0.76 - 3665.44 37.18
VAV WITH REHEAT COOLING COIL Coil:Cooling:Water 821617.44 686960.31 431435.91 255524.40 0.63 - 73391.12 744.37
FLR_3_DOAS COOLING COIL Coil:Cooling:Water 65945.86 54169.20 34464.63 19704.58 0.64 - 5364.64 54.41
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [W] Standard Rated Net COP [W/W] EER [Btu/W-h] SEER User [Btu/W-h] SEER Standard [Btu/W-h] IEER [Btu/W-h]
None              


DX Cooling Coil ASHRAE 127 Standard Ratings Report

DX Cooling Coil Type Rated Net Cooling Capacity Test A [W] Rated Electric Power Test A [W] Rated Net Cooling Capacity Test B [W] Rated Electric Power Test B [W] Rated Net Cooling Capacity Test C [W] Rated Electric Power Test C [W] Rated Net Cooling Capacity Test D [W] Rated Electric Power Test D [W]
None                  


DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [W] Low Temperature Heating (net) Rating Capacity [W] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Efficiency [W/W]
BASEMENT VAV BOX REHEAT COIL Coil:Heating:Water 13705.25 13776.60 -
RETAIL_1_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 4468.08 4489.73 -
RETAIL_2_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 2203.53 2214.71 -
MECH_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 3101.04 3116.27 -
STORAGE_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 1698.38 1706.65 -
LAUNDRY_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 19527.16 19628.30 -
CAFE_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 14253.78 14325.59 -
LOBBY_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 40785.34 40992.66 -
ROOM_1_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 5573.41 6004.30 -
ROOM_2_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 5577.97 6009.21 -
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 32042.69 34519.76 -
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 32146.75 34631.86 -
ROOM_5_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 5563.54 5993.67 -
ROOM_6_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 5568.10 5998.58 -
CORRIDOR_FLR_3 VAV BOX REHEAT COIL Coil:Heating:Water 15525.10 15600.43 -
ROOM_1_FLR_6 FAN COIL HEATING COIL Coil:Heating:Water 1729.34 1862.98 -
ROOM_2_FLR_6 FAN COIL HEATING COIL Coil:Heating:Water 1729.86 1863.55 -
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL Coil:Heating:Water 8347.43 8992.47 -
BANQUET_FLR_6 VAV BOX REHEAT COIL Coil:Heating:Water 18141.00 18233.60 -
DINING_FLR_6 VAV BOX REHEAT COIL Coil:Heating:Water 18830.34 18926.52 -
KITCHEN_FLR_6 VAV BOX REHEAT COIL Coil:Heating:Water 13392.17 13461.61 -
CORRIDOR_FLR_6 VAV BOX REHEAT COIL Coil:Heating:Water 10312.81 10362.34 -
VAV WITH REHEAT HEATING COIL Coil:Heating:Water 131650.00 106028.13 -
FLR_3_DOAS HEATING COIL Coil:Heating:Water 10951.44 8820.06 -
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

Fans

Type Total Efficiency [W/W] Delta Pressure [pa] Max Air Flow Rate [m3/s] Rated Electricity Rate [W] Rated Power Per Max Air Flow Rate [W-s/m3] Motor Heat In Air Fraction Fan Energy Index End Use Subcategory Design Day Name for Fan Sizing Peak Date/Time for Fan Sizing Peak
LAUNDRY_FLR_1 EXHAUST FAN Fan:ZoneExhaust 0.16 125.00 0.24 184.35 781.25 1.00 1.15 General    
LOBBY_FLR_1 EXHAUST FAN Fan:ZoneExhaust 1.00 0.00 0.00 0.00   1.00 0.00 General    
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.16 270.90 1.31 2213.11 1693.12 1.00 0.47 General TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:50:00
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.16 270.90 1.30 2198.15 1693.12 1.00 0.47 General TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.16 270.90 7.84 13279.56 1693.12 1.00 0.39 General TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.16 270.90 8.37 14177.88 1693.12 1.00 0.39 General TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:40:00
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.16 270.90 1.15 1948.23 1693.12 1.00 0.48 General TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:30:00
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.16 270.90 1.14 1935.55 1693.12 1.00 0.48 General TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:20:00
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.16 270.90 0.35 598.97 1693.12 1.00 0.67 General TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:50:00
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.16 270.90 0.35 594.52 1693.12 1.00 0.67 General TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:50:00
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.16 270.90 1.59 2691.99 1693.12 1.00 0.46 General TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00
BANQUET_FLR_6 EXHAUST FAN Fan:ZoneExhaust 1.00 0.00 0.00 0.00   1.00 0.00 General    
DINING_FLR_6 EXHAUST FAN Fan:ZoneExhaust 1.00 0.00 0.00 0.00   1.00 0.00 General    
KITCHEN_FLR_6 EXHAUST FAN Fan:ZoneExhaust 0.16 125.00 1.89 1474.84 781.25 1.00 0.62 General    
VAV WITH REHEAT FAN Fan:VariableVolume 0.62 1389.42 24.66 55252.78 2240.64 1.00 1.11 General TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:40:00
FLR_3_DOAS FAN Fan:ConstantVolume 0.58 622.50 2.05 2194.93 1070.05 1.00 1.30 General TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00


Pumps

Type Control Head [pa] Water Flow [m3/s] Electricity Rate [W] Power Per Water Flow Rate [W-s/m3] Motor Efficiency [W/W] End Use Subcategory
COOLSYS1 PUMP SECONDARY Pump:VariableSpeed Intermittent 133527.72 0.040971 8442.59 206062.94 0.90 General
HEATSYS1 PUMP Pump:VariableSpeed Intermittent 180705.70 0.003647 1098.18 301156.09 0.90 General
COOLSYS1 PUMP Pump:ConstantSpeed Intermittent 92445.74 0.040971 5845.09 142664.32 0.90 General
SWHSYS1 PUMP Pump:ConstantSpeed Intermittent 29891.00 0.000375 47.91 127739.32 0.30 General


Service Water Heating

Type Storage Volume [m3] Input [W] Thermal Efficiency [W/W] Recovery Efficiency [W/W] Energy Factor
SWH BOOSTER E WATER HEATER WaterHeater:Mixed 0.02 8000.00 1.00 1.24 1.15
SWH LAUNDRY G WATER HEATER WaterHeater:Mixed 1.14 163316.00 0.80 0.58 0.51
SWHSYS1 WATER HEATER WaterHeater:Mixed 2.27 175842.60 0.80 0.26 0.03



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2023-10-16 08:58:43

Zone Sensible Cooling

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
BASEMENT 35904.55 35904.55 18.14 2.874 2.874 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 21:20:00 24.00 24.00 0.00917 32.55 0.00562 0.854 0.00
RETAIL_1_FLR_1 4989.33 4989.33 74.39 0.399 0.399 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:10:00 24.00 24.00 0.00886 40.80 0.00563 0.079 0.00
RETAIL_2_FLR_1 3535.22 3535.22 45.52 0.283 0.283 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:50:00 24.00 24.00 0.00922 37.83 0.00563 0.092 0.00
MECH_FLR_1 3901.19 3901.19 23.75 0.312 0.312 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:20:00 24.00 24.00 0.00852 36.94 0.00563 0.000 0.00
STORAGE_FLR_1 1976.34 1976.34 20.86 0.158 0.158 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:40:00 24.00 24.00 0.00857 38.05 0.00563 0.058 0.00
LAUNDRY_FLR_1 45529.25 45529.25 583.41 3.644 3.644 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:50:00 24.00 24.00 0.00853 40.13 0.00563 0.000 0.00
CAFE_FLR_1 20584.83 20584.83 108.99 1.649 1.649 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:10:00 24.00 23.99 0.00997 40.80 0.00563 0.676 0.00
LOBBY_FLR_1 67372.32 67372.32 51.50 5.394 5.394 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 24.00 23.99 0.00984 40.80 0.00563 1.894 0.00
ROOM_1_FLR_3 12121.14 12121.14 310.62 1.307 1.307 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:50:00 21.11 21.11 0.00848 39.12 0.00563 0.062 0.00
ROOM_2_FLR_3 12039.24 12039.24 308.56 1.298 1.298 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00 21.11 21.11 0.00848 38.94 0.00563 0.062 0.00
ROOM_3_MULT19_FLR_3 72732.87 72732.87 2965.80 7.843 7.843 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 21.11 21.11 0.00843 40.80 0.00563 0.837 0.00
ROOM_4_MULT19_FLR_3 77647.07 77647.07 3165.32 8.374 8.374 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:40:00 21.11 21.11 0.00861 40.27 0.00563 0.837 0.00
ROOM_5_FLR_3 10670.44 10670.44 273.45 1.151 1.151 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:30:00 21.11 21.11 0.00848 36.74 0.00562 0.062 0.00
ROOM_6_FLR_3 10600.98 10600.98 271.70 1.143 1.143 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:20:00 21.11 21.11 0.00848 36.41 0.00562 0.062 0.00
CORRIDOR_FLR_3 17515.36 17515.36 44.98 1.402 1.402 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:30:00 24.00 24.00 0.00946 40.40 0.00563 0.475 0.00
ROOM_1_FLR_6 3280.55 3280.55 84.07 0.354 0.354 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:50:00 21.11 21.11 0.00848 39.12 0.00563 0.015 0.00
ROOM_2_FLR_6 3256.19 3256.19 83.45 0.351 0.351 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:50:00 21.11 21.11 0.00848 39.12 0.00563 0.015 0.00
ROOM_3_MULT9_FLR_6 14743.42 14743.42 601.02 1.590 1.590 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 21.11 21.11 0.00854 40.80 0.00563 0.099 0.00
BANQUET_FLR_6 32040.92 32040.92 96.61 2.567 2.567 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 24.00 23.98 0.01022 40.80 0.00563 1.188 0.00
DINING_FLR_6 33562.10 33562.10 101.20 2.689 2.689 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 24.00 23.99 0.01014 40.80 0.00563 1.188 0.00
KITCHEN_FLR_6 31785.95 31785.95 307.69 2.551 2.551 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 12:30:00 24.00 23.97 0.00999 39.60 0.00563 0.367 0.00
CORRIDOR_FLR_6 10655.85 10655.85 25.86 0.853 0.853 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:50:00 24.00 24.00 0.00889 40.80 0.00563 0.126 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

Zone Sensible Heating

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
BASEMENT 0.00 0.00 0.00 0.000 0.854   00:10:00 21.00 24.00 0.00849 0.50 0.00432 0.854 0.00
RETAIL_1_FLR_1 2565.49 2565.49 38.25 0.121 0.121 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.00 21.00 0.00751 0.50 0.00432 0.079 0.00
RETAIL_2_FLR_1 855.41 855.41 11.01 0.040 0.092 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.00 21.00 0.00744 0.50 0.00432 0.092 0.00
MECH_FLR_1 1614.02 1614.02 9.83 0.076 0.076 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.00 21.00 0.00732 0.50 0.00432 0.000 0.00
STORAGE_FLR_1 945.03 945.03 9.97 0.045 0.058 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.00 21.00 0.00733 0.50 0.00432 0.058 0.00
LAUNDRY_FLR_1 2173.14 2173.14 27.85 0.103 0.103 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.00 21.00 0.00732 0.50 0.00432 0.000 0.00
CAFE_FLR_1 6396.48 6396.48 33.87 0.302 0.676 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.00 21.00 0.00755 0.50 0.00432 0.676 0.00
LOBBY_FLR_1 15084.59 15084.59 11.53 0.712 1.894 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.00 21.00 0.00747 0.50 0.00432 1.894 0.00
ROOM_1_FLR_3 5573.55 5573.55 142.83 0.265 0.265 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.11 21.11 0.00748 0.50 0.00432 0.062 0.00
ROOM_2_FLR_3 5578.11 5578.11 142.96 0.265 0.265 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.11 21.11 0.00748 0.50 0.00432 0.062 0.00
ROOM_3_MULT19_FLR_3 32043.09 32043.09 1306.61 1.522 1.522 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.11 21.11 0.00751 0.50 0.00432 0.837 0.00
ROOM_4_MULT19_FLR_3 32147.16 32147.16 1310.50 1.527 1.527 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.11 21.11 0.00752 0.50 0.00432 0.837 0.00
ROOM_5_FLR_3 5563.68 5563.68 142.58 0.264 0.264 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.11 21.11 0.00748 0.50 0.00432 0.062 0.00
ROOM_6_FLR_3 5568.24 5568.24 142.71 0.264 0.264 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.11 21.11 0.00748 0.50 0.00432 0.062 0.00
CORRIDOR_FLR_3 8844.67 8844.67 22.71 0.418 0.475 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.00 21.00 0.00759 0.50 0.00432 0.475 0.00
ROOM_1_FLR_6 1729.38 1729.38 44.32 0.082 0.082 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.11 21.11 0.00757 0.50 0.00432 0.015 0.00
ROOM_2_FLR_6 1729.91 1729.91 44.34 0.082 0.082 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.11 21.11 0.00757 0.50 0.00432 0.015 0.00
ROOM_3_MULT9_FLR_6 8347.60 8347.60 340.29 0.396 0.396 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.11 21.11 0.00759 0.50 0.00432 0.099 0.00
BANQUET_FLR_6 5903.54 5903.54 17.80 0.279 1.188 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.00 21.00 0.00768 0.50 0.00432 1.188 0.00
DINING_FLR_6 6012.73 6012.73 18.13 0.284 1.188 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 19:10:00 21.00 21.00 0.00768 0.50 0.00432 1.188 0.00
KITCHEN_FLR_6 1286.91 1286.91 12.46 0.061 0.367 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 23:30:00 21.00 21.00 0.00579 0.50 0.00432 0.367 0.00
CORRIDOR_FLR_6 6247.85 6247.85 15.16 0.295 0.295 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 19:10:00 21.00 21.00 0.00773 0.50 0.00432 0.126 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

System Design Air Flow Rates

Calculated cooling [m3/s] User cooling [m3/s] Calculated heating [m3/s] User heating [m3/s] Adjusted cooling [m3/s] Adjusted heating [m3/s] Adjusted main [m3/s] Calculated Heating Air Flow Ratio [] User Heating Air Flow Ratio []
VAV WITH REHEAT 24.66 24.66 7.39 7.39 24.6594 24.6508 24.6594 0.9997 0.3000
FLR_3_DOAS 22.93 2.05 4.67 2.05 2.0513 2.0513 2.0513 1.0000 0.3000


Plant Loop Coincident Design Fluid Flow Rate Adjustments

Previous Design Volume Flow Rate [m3/s] Algorithm Volume Flow Rate [m3/s] Coincident Design Volume Flow Rate [m3/s] Coincident Size Adjusted Peak Sizing Period Name Peak Day into Period {TIMESTAMP}[day] Peak Hour Of Day {TIMESTAMP}[hr] Peak Step Start Minute {TIMESTAMP}[min]
None                


Coil Sizing Summary

Coil Type HVAC Type HVAC Name Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Flow Percentage at Ideal Loads Peak [%] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W]
BASEMENT VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT BASEMENT VAV BOX 13705.247 13705.247 2.859195 0.00011990 285.799   12/21 00:10:00   12/21 00:10:00 13705.25 13705.25 2.859195 16.70 12.29 0.00800000 40.00 20.06 0.00800000 0.50 0.00431558 0.50 0.0000 21.00 0.00800000 46.9512 0.00 0.00 13782.28 13782.28
RETAIL_1_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT RETAIL_1_FLR_1 VAV BOX 4468.076 4468.076 0.397330 0.00003909 100.213 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 4468.08 4468.08 0.397330 16.70 12.29 0.00800000 40.00 20.06 0.00800000 0.50 0.00431558 0.50 0.0000 21.00 0.00750558 44.0857 2565.49 0.00 4492.26 4492.26
RETAIL_2_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT RETAIL_2_FLR_1 VAV BOX 2203.526 2203.526 0.281546 0.00001928 47.515 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 2203.53 2203.53 0.281546 16.70 12.29 0.00800000 40.00 20.06 0.00800000 0.50 0.00431558 0.50 0.0000 21.00 0.00743945 43.7008 855.41 0.00 2215.77 2215.77
MECH_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT MECH_FLR_1 VAV BOX 3101.045 3101.045 0.310622 0.00002713 68.532 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 3101.04 3101.04 0.310622 16.70 12.29 0.00800000 40.00 20.06 0.00800000 0.50 0.00431558 0.50 0.0000 21.00 0.00732382 43.0296 1614.02 0.00 3117.93 3117.93
STORAGE_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT STORAGE_FLR_1 VAV BOX 1698.376 1698.376 0.157363 0.00001486 37.890 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 1698.38 1698.38 0.157363 16.70 12.29 0.00800000 40.00 20.06 0.00800000 0.50 0.00431558 0.50 0.0000 21.00 0.00733193 43.0766 945.03 0.00 1707.59 1707.59
LAUNDRY_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 19527.156 19527.156 3.625416 0.00017083 409.833 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 19527.16 19527.16 3.625416 16.70 12.29 0.00800000 40.00 20.06 0.00800000 0.50 0.00431558 0.50 0.0000 21.00 0.00731608 42.9856 2173.14 0.00 19636.65 19636.65
CAFE_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CAFE_FLR_1 VAV BOX 14253.782 14253.782 1.640703 0.00012470 310.371 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 14253.78 14253.78 1.640703 16.70 12.29 0.00800000 40.00 20.06 0.00800000 0.50 0.00431558 0.50 0.0000 21.00 0.00755488 44.3715 6396.48 0.00 14332.79 14332.79
LOBBY_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 40785.340 40785.340 5.367097 0.00035681 877.210 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 40785.34 40785.34 5.367097 16.70 12.29 0.00800000 40.00 20.06 0.00800000 0.50 0.00431558 0.50 0.0000 21.00 0.00747410 43.9020 15084.59 0.00 41012.20 41012.20
ROOM_1_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_3 FAN COIL 14333.798 -999.000 1.307114 0.00051196 -999.000 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:50:00 unknown 7/21 16:50:00 14333.80 14333.80 1.307114 22.63 14.91 0.00847948 12.80 11.21 0.00847948 39.12 0.00562848 18.06 0.0000 21.11 0.00847948 49.3890 12121.14 0.00 15706.28 15317.65
ROOM_1_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_3 FAN COIL 5573.406 5573.406 0.264680 0.00004876 159.274 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 5573.41 5573.41 0.264680 21.11 13.48 0.00747908 40.00 20.06 0.00800000 0.50 0.00431558 0.50 0.0000 21.11 0.00747908 43.6336 5573.55 0.00 6008.26 6008.26
ROOM_2_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_3 FAN COIL 14236.938 -999.000 1.298281 0.00050850 -999.000 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00 unknown 7/21 17:00:00 14236.94 14236.94 1.298281 22.63 14.91 0.00847926 12.80 11.21 0.00847926 38.94 0.00562821 18.00 0.0000 21.11 0.00847926 49.3878 12039.24 0.00 15600.19 15214.60
ROOM_2_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_3 FAN COIL 5577.965 5577.965 0.264896 0.00004880 159.404 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 5577.97 5577.97 0.264896 21.11 13.48 0.00747948 40.00 20.06 0.00800000 0.50 0.00431558 0.50 0.0000 21.11 0.00747948 43.6359 5578.11 0.00 6013.18 6013.18
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT19_FLR_3 FAN COIL 86002.932 -999.000 7.843225 0.00307177 -999.000 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 unknown 7/21 14:30:00 86002.93 86002.93 7.843225 22.63 14.86 0.00842835 12.80 11.16 0.00842835 40.80 0.00563111 18.58 0.0000 21.11 0.00842835 49.0949 72732.87 0.00 94264.37 92537.62
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT19_FLR_3 FAN COIL 32042.686 32042.686 1.521731 0.00028032 915.685 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 32042.69 32042.69 1.521731 21.11 13.51 0.00751430 40.00 20.06 0.00800000 0.50 0.00431558 0.50 0.0000 21.11 0.00751430 43.8356 32043.09 0.00 34542.98 34542.98
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_4_MULT19_FLR_3 FAN COIL 94466.478 -999.000 8.373796 0.00337406 -999.000 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:40:00 unknown 7/21 15:40:00 94466.48 92371.96 8.373796 22.63 15.02 0.00861360 12.80 11.23 0.00850000 40.27 0.00563027 18.42 0.0000 21.11 0.00861360 50.1612 77647.07 0.00 103372.69 98118.20
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_4_MULT19_FLR_3 FAN COIL 32146.752 32146.752 1.526673 0.00028123 918.658 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 32146.75 32146.75 1.526673 21.11 13.51 0.00751555 40.00 20.06 0.00800000 0.50 0.00431558 0.50 0.0000 21.11 0.00751555 43.8428 32147.16 0.00 34655.17 34655.17
ROOM_5_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_5_FLR_3 FAN COIL 12618.193 -999.000 1.150672 0.00045068 -999.000 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:30:00 unknown 7/21 10:30:00 12618.19 12618.19 1.150672 22.63 14.90 0.00847566 12.80 11.21 0.00847566 36.74 0.00562481 17.31 0.0000 21.11 0.00847566 49.3671 10670.44 0.00 13827.01 13491.46
ROOM_5_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_5_FLR_3 FAN COIL 5563.539 5563.539 0.264211 0.00004867 158.992 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 5563.54 5563.54 0.264211 21.11 13.48 0.00747828 40.00 20.06 0.00800000 0.50 0.00431558 0.50 0.0000 21.11 0.00747828 43.6290 5563.68 0.00 5997.62 5997.62
ROOM_6_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_6_FLR_3 FAN COIL 12536.045 -999.000 1.143181 0.00044775 -999.000 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:20:00 unknown 7/21 10:20:00 12536.05 12536.05 1.143181 22.63 14.90 0.00847539 12.80 11.21 0.00847539 36.41 0.00562429 17.20 0.0000 21.11 0.00847539 49.3655 10600.98 0.00 13737.03 13404.12
ROOM_6_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_6_FLR_3 FAN COIL 5568.100 5568.100 0.264428 0.00004871 159.122 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 5568.10 5568.10 0.264428 21.11 13.48 0.00747868 40.00 20.06 0.00800000 0.50 0.00431558 0.50 0.0000 21.11 0.00747868 43.6314 5568.24 0.00 6002.54 6002.54
CORRIDOR_FLR_3 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORRIDOR_FLR_3 VAV BOX 15525.099 15525.099 1.394756 0.00013582 347.738 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 15525.10 15525.10 1.394756 16.70 12.29 0.00800000 40.00 20.06 0.00800000 0.50 0.00431558 0.50 0.0000 21.00 0.00758697 44.5567 8844.67 0.00 15609.17 15609.17
ROOM_1_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_6 FAN COIL 3879.408 -999.000 0.353766 0.00013856 -999.000 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:50:00 unknown 7/21 16:50:00 3879.41 3879.41 0.353766 22.63 14.91 0.00848097 12.80 11.21 0.00848097 39.12 0.00562848 18.06 0.0000 21.11 0.00848097 49.3976 3280.55 0.00 4250.80 4144.83
ROOM_1_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_6 FAN COIL 1729.335 1729.335 0.082126 0.00001513 49.417 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 1729.34 1729.34 0.082126 21.11 13.56 0.00756836 40.00 20.06 0.00800000 0.50 0.00431558 0.50 0.0000 21.11 0.00756836 44.1482 1729.38 0.00 1864.26 1864.26
ROOM_2_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_6 FAN COIL 3850.596 -999.000 0.351139 0.00013753 -999.000 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:50:00 unknown 7/21 16:50:00 3850.60 3850.60 0.351139 22.63 14.91 0.00848085 12.80 11.21 0.00848085 39.12 0.00562848 18.06 0.0000 21.11 0.00848085 49.3969 3256.19 0.00 4219.23 4114.11
ROOM_2_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_6 FAN COIL 1729.864 1729.864 0.082151 0.00001513 49.433 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 1729.86 1729.86 0.082151 21.11 13.56 0.00756850 40.00 20.06 0.00800000 0.50 0.00431558 0.50 0.0000 21.11 0.00756850 44.1491 1729.91 0.00 1864.83 1864.83
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT9_FLR_6 FAN COIL 17593.473 -999.000 1.589953 0.00062839 -999.000 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 unknown 7/21 14:30:00 17593.47 17468.65 1.589953 22.63 14.95 0.00853580 12.80 11.23 0.00850000 40.80 0.00563111 18.58 0.0000 21.11 0.00853580 49.7136 14743.42 0.00 19262.91 18592.30
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT9_FLR_6 FAN COIL 8347.428 8347.428 0.396420 0.00007303 238.534 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 8347.43 8347.43 0.396420 21.11 13.58 0.00758599 40.00 20.06 0.00800000 0.50 0.00431558 0.50 0.0000 21.11 0.00758599 44.2495 8347.60 0.00 8998.74 8998.74
BANQUET_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 18141.000 18141.000 2.554616 0.00015871 388.007 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 18141.00 18141.00 2.554616 16.70 12.29 0.00800000 40.00 20.06 0.00800000 0.50 0.00431558 0.50 0.0000 21.00 0.00767888 45.0902 5903.54 0.00 18242.08 18242.08
DINING_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 18830.344 18830.344 2.675859 0.00016474 402.463 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 19:10:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 19:10:00 18830.34 18830.34 2.675859 16.70 12.29 0.00800000 40.00 20.06 0.00800000 0.50 0.00431558 0.50 0.0000 21.00 0.00768421 45.1218 6012.73 0.00 18935.29 18935.29
KITCHEN_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 13392.173 13392.173 2.537815 0.00011716 280.739 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 23:30:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 23:30:00 13392.17 13392.17 2.537815 16.70 12.29 0.00800000 40.00 20.06 0.00800000 0.50 0.00431558 0.50 0.0000 21.00 0.00578905 34.1028 1286.91 0.00 13467.30 13467.30
CORRIDOR_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORRIDOR_FLR_6 VAV BOX 10312.810 10312.810 0.848517 0.00009022 233.819 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 19:10:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 19:10:00 10312.81 10312.81 0.848517 16.70 12.29 0.00800000 40.00 20.06 0.00800000 0.50 0.00431558 0.50 0.0000 21.00 0.00773009 45.3875 6247.85 0.00 10368.40 10368.40
VAV WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoopHVAC VAV WITH REHEAT 821617.441 -999.000 24.659390 0.02934627 -999.000 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:40:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:40:00 821617.44 821617.44 24.659390 40.80 18.58 0.00563111 10.78 7.37 0.00563111 40.80 0.00563111 18.58 100.0000 23.99 0.00954907 46.6101 307915.97 0.00 822381.20 822381.20
VAV WITH REHEAT HEATING COIL Coil:Heating:Water AirLoopHVAC VAV WITH REHEAT 131650.002 131650.002 7.397817 0.00115173 2309.983 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 19:10:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 19:10:00 131650.00 131650.00 7.397817 0.50 0.50 0.00431558 16.70 12.29 0.00800000 0.50 0.00431558 0.50 333.3333 21.97 0.00786035 43.4756 57323.34 0.00 128301.45 128301.45
FLR_3_DOAS COOLING COIL Coil:Cooling:Water AirLoopHVAC FLR_3_DOAS 65945.855 -999.000 2.051317 0.00235543 -999.000 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:30:00 65945.86 65945.86 2.051317 40.80 18.58 0.00563111 11.84 7.85 0.00563111 40.80 0.00563111 18.58 99.9965 21.11 0.00852349 49.6426 211994.85 0.00 66000.58 66000.58
FLR_3_DOAS HEATING COIL Coil:Heating:Water AirLoopHVAC FLR_3_DOAS 10951.444 10951.444 0.615395 0.00009581 192.158 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 10951.44 10951.44 0.615395 0.50 0.50 0.00431558 16.70 12.29 0.00800000 0.50 0.00431558 0.50 333.3216 21.11 0.00751538 43.8419 98280.72 0.00 10672.89 10672.89



Table of Contents

Report: Coil Sizing Details

For: Entire Facility

Timestamp: 2023-10-16 08:58:43

Coils

Coil Type Coil Location HVAC Type HVAC Name Zone Name(s) System Sizing Method Concurrence System Sizing Method Capacity System Sizing Method Air Flow Autosized Coil Capacity? Autosized Coil Airflow? Autosized Coil Water Flow? OA Pretreated prior to coil inlet? Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Terminal Unit Reheat Coil Multiplier DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio Moist Air Heat Capacity [J/kg-K] Dry Air Heat Capacity [J/kg-K] Standard Air Density Adjusted for Elevation [kg/m3] Supply Fan Name for Coil Supply Fan Type for Coil Supply Fan Maximum Air Volume Flow Rate [m3/s] Supply Fan Maximum Air Mass Flow Rate [kg/s] Plant Name for Coil Plant Fluid Specific Heat Capacity [J/kg-K] Plant Fluid Density [kg/m3] Plant Maximum Fluid Mass Flow Rate [kg/s] Plant Design Fluid Return Temperature [C] Plant Design Fluid Supply Temperature [C] Plant Design Fluid Temperature Difference [deltaC] Plant Design Capacity [W] Coil Capacity Percentage of Plant Design Capacity [%] Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Total Ideal Loads Peak Date/Time at Total Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Peak Load Type to Size On Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] Supply Fan Air Heat Gain at Ideal Loads Peak [W] Coil and Fan Net Total Capacity at Ideal Loads Peak [W] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] Outdoor Air Flow Percentage at Ideal Loads Peak [%] System Return Air Drybulb at Ideal Loads Peak [C] System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W] Coil Air Mass Flow Rate at Rating Conditions [kg/s] Coil Entering Air Drybulb at Rating Conditions [C] Coil Entering Air Wetbulb at Rating Conditions [C] Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] Coil Leaving Air Drybulb at Rating Conditions [C] Coil Leaving Air Wetbulb at Rating Conditions [C] Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K]
BASEMENT VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT BASEMENT VAV BOX BASEMENT N/A N/A N/A Yes Yes Yes No 13705.247 13705.247 2.859195 0.00011990 285.799 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0932 unknown unknown -999.0 -999.0   4197.9300 999.8980 3.64619054 54.44 82.22 27.78 425213.25 3.2231 3.288014   12/21 00:10:00 unknown unknown   12/21 00:10:00 Sensible 13705.25 13705.25 1.0000 3.12565503 2.859195 16.70 12.29 0.00800000 37036.7 40.00 20.06 0.00800000 60796.0 0.11988725 60.00 32.22 27.78 0.000 13705.25 0.50 0.00431558 0.50 0.00000000 0.0000 21.00 0.00800000 21.00 0.00800000 46.9512 0.00 0.00 13782.28 13782.28 3.12565503 16.60 13.15 0.00800000 36934.7 20.92 14.82 0.00800000 41344.1
RETAIL_1_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT RETAIL_1_FLR_1 VAV BOX RETAIL_1_FLR_1 N/A N/A N/A Yes Yes Yes No 4468.076 4468.076 0.397330 0.00003909 100.213 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0932 unknown unknown -999.0 -999.0   4197.9300 999.8980 3.64619054 54.44 82.22 27.78 425213.25 1.0508 1.071932 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 4468.08 4468.08 1.0000 0.43435834 0.397330 16.70 12.29 0.00800000 37036.7 40.00 20.06 0.00800000 60796.0 0.03908469 60.00 32.22 27.78 0.000 4468.08 0.50 0.00431558 0.50 0.00000000 0.0000 21.00 0.00750558 21.00 0.00750558 44.0857 2565.49 0.00 4492.26 4492.26 0.43435834 16.60 13.15 0.00800000 36934.7 26.74 16.93 0.00800000 47277.0
RETAIL_2_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT RETAIL_2_FLR_1 VAV BOX RETAIL_2_FLR_1 N/A N/A N/A Yes Yes Yes No 2203.526 2203.526 0.281546 0.00001928 47.515 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0932 unknown unknown -999.0 -999.0   4197.9300 999.8980 3.64619054 54.44 82.22 27.78 425213.25 0.5182 0.528646 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 2203.53 2203.53 1.0000 0.30778450 0.281546 16.70 12.29 0.00800000 37036.7 40.00 20.06 0.00800000 60796.0 0.01927544 60.00 32.22 27.78 0.000 2203.53 0.50 0.00431558 0.50 0.00000000 0.0000 21.00 0.00743945 21.00 0.00743945 43.7008 855.41 0.00 2215.77 2215.77 0.30778450 16.60 13.15 0.00800000 36934.7 23.66 15.83 0.00800000 44133.8
MECH_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT MECH_FLR_1 VAV BOX MECH_FLR_1 N/A N/A N/A Yes Yes Yes No 3101.045 3101.045 0.310622 0.00002713 68.532 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0932 unknown unknown -999.0 -999.0   4197.9300 999.8980 3.64619054 54.44 82.22 27.78 425213.25 0.7293 0.743969 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 3101.04 3101.04 1.0000 0.33957064 0.310622 16.70 12.29 0.00800000 37036.7 40.00 20.06 0.00800000 60796.0 0.02712652 60.00 32.22 27.78 0.000 3101.04 0.50 0.00431558 0.50 0.00000000 0.0000 21.00 0.00732382 21.00 0.00732382 43.0296 1614.02 0.00 3117.93 3117.93 0.33957064 16.60 13.15 0.00800000 36934.7 25.60 16.53 0.00800000 46116.7
STORAGE_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT STORAGE_FLR_1 VAV BOX STORAGE_FLR_1 N/A N/A N/A Yes Yes Yes No 1698.376 1698.376 0.157363 0.00001486 37.890 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0932 unknown unknown -999.0 -999.0   4197.9300 999.8980 3.64619054 54.44 82.22 27.78 425213.25 0.3994 0.407456 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 1698.38 1698.38 1.0000 0.17202805 0.157363 16.70 12.29 0.00800000 37036.7 40.00 20.06 0.00800000 60796.0 0.01485662 60.00 32.22 27.78 0.000 1698.38 0.50 0.00431558 0.50 0.00000000 0.0000 21.00 0.00733193 21.00 0.00733193 43.0766 945.03 0.00 1707.59 1707.59 0.17202805 16.60 13.15 0.00800000 36934.7 26.33 16.78 0.00800000 46860.9
LAUNDRY_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown LAUNDRY_FLR_1 N/A N/A N/A Yes Yes Yes No 19527.156 19527.156 3.625416 0.00017083 409.833 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0932 unknown unknown -999.0 -999.0   4197.9300 999.8980 3.64619054 54.44 82.22 27.78 425213.25 4.5923 4.684743 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 19527.16 19527.16 1.0000 3.96328393 3.625416 16.70 12.29 0.00800000 37036.7 40.00 20.06 0.00800000 60796.0 0.17081466 60.00 32.22 27.78 0.000 19527.16 0.50 0.00431558 0.50 0.00000000 0.0000 21.00 0.00731608 21.00 0.00731608 42.9856 2173.14 0.00 19636.65 19636.65 3.96328393 16.60 13.15 0.00800000 36934.7 21.46 15.02 0.00800000 41889.4
CAFE_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CAFE_FLR_1 VAV BOX CAFE_FLR_1 N/A N/A N/A Yes Yes Yes No 14253.782 14253.782 1.640703 0.00012470 310.371 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0932 unknown unknown -999.0 -999.0   4197.9300 999.8980 3.64619054 54.44 82.22 27.78 425213.25 3.3521 3.419612 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 14253.78 14253.78 1.0000 1.79360692 1.640703 16.70 12.29 0.00800000 37036.7 40.00 20.06 0.00800000 60796.0 0.12468558 60.00 32.22 27.78 0.000 14253.78 0.50 0.00431558 0.50 0.00000000 0.0000 21.00 0.00755488 21.00 0.00755488 44.3715 6396.48 0.00 14332.79 14332.79 1.79360692 16.60 13.15 0.00800000 36934.7 24.44 16.11 0.00800000 44925.8
LOBBY_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown LOBBY_FLR_1 N/A N/A N/A Yes Yes Yes No 40785.340 40785.340 5.367097 0.00035681 877.210 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0932 unknown unknown -999.0 -999.0   4197.9300 999.8980 3.64619054 54.44 82.22 27.78 425213.25 9.5917 9.784775 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 40785.34 40785.34 1.0000 5.86727907 5.367097 16.70 12.29 0.00800000 37036.7 40.00 20.06 0.00800000 60796.0 0.35677155 60.00 32.22 27.78 0.000 40785.34 0.50 0.00431558 0.50 0.00000000 0.0000 21.00 0.00747410 21.00 0.00747410 43.9020 15084.59 0.00 41012.20 41012.20 5.86727907 16.60 13.15 0.00800000 36934.7 23.45 15.76 0.00800000 43924.7
ROOM_1_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_3 FAN COIL ROOM_1_FLR_3 N/A N/A N/A Yes Yes Yes No 14333.798 -999.000 1.307114 0.00051196 -999.000 -999.0000 1.00000 1.00000 1020.6029 1004.8586 1.0932 ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 1.307114 1.42892935   4197.9300 999.8980 40.96672859 13.37 6.70 6.67 1147076.31 1.2496 1.249571 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:50:00 unknown unknown unknown 7/21 16:50:00 Sensible 14333.80 14333.80 1.0000 1.42892935 1.307114 22.63 14.91 0.00847948 44301.5 12.80 11.21 0.00847948 34270.4 0.51190828 6.70 13.37 6.67 0.000 14333.80 39.12 0.00562848 18.06 0.00000000 0.0000 21.11 0.00847948 21.11 0.00847948 49.3890 12121.14 0.00 15706.28 15317.65 1.42892935 22.63 15.88 0.00847948 44301.5 12.13 11.69 0.00837170 33309.9
ROOM_1_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_3 FAN COIL ROOM_1_FLR_3 N/A N/A N/A Yes Yes Yes No 5573.406 5573.406 0.264680 0.00004876 159.274 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0932 ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 1.307114 1.42892935   4197.9300 999.8980 3.64619054 54.44 82.22 27.78 425213.25 1.3107 1.337111 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 5573.41 5573.41 1.0000 0.28934647 0.264680 21.11 13.48 0.00747908 40210.7 40.00 20.06 0.00800000 60796.0 0.04875361 60.00 32.22 27.78 0.000 5573.41 0.50 0.00431558 0.50 0.00000000 0.0000 21.11 0.00747908 21.11 0.00747908 43.6336 5573.55 0.00 6008.26 6008.26 0.28934647 16.60 12.64 0.00747908 35615.9 36.98 19.88 0.00747908 56380.8
ROOM_2_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_3 FAN COIL ROOM_2_FLR_3 N/A N/A N/A Yes Yes Yes No 14236.938 -999.000 1.298281 0.00050850 -999.000 -999.0000 1.00000 1.00000 1020.6025 1004.8586 1.0932 ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 1.298281 1.41927380   4197.9300 999.8980 40.96672859 13.37 6.70 6.67 1147076.31 1.2412 1.241127 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00 unknown unknown unknown 7/21 17:00:00 Sensible 14236.94 14236.94 1.0000 1.41927380 1.298281 22.63 14.91 0.00847926 44301.0 12.80 11.21 0.00847926 34269.8 0.50844906 6.70 13.37 6.67 0.000 14236.94 38.94 0.00562821 18.00 0.00000000 0.0000 21.11 0.00847926 21.11 0.00847926 49.3878 12039.24 0.00 15600.19 15214.60 1.41927380 22.63 15.88 0.00847926 44301.0 12.13 11.69 0.00837160 33309.3
ROOM_2_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_3 FAN COIL ROOM_2_FLR_3 N/A N/A N/A Yes Yes Yes No 5577.965 5577.965 0.264896 0.00004880 159.404 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0932 ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 1.298281 1.41927380   4197.9300 999.8980 3.64619054 54.44 82.22 27.78 425213.25 1.3118 1.338205 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 5577.97 5577.97 1.0000 0.28958315 0.264896 21.11 13.48 0.00747948 40211.7 40.00 20.06 0.00800000 60796.0 0.04879349 60.00 32.22 27.78 0.000 5577.97 0.50 0.00431558 0.50 0.00000000 0.0000 21.11 0.00747948 21.11 0.00747948 43.6359 5578.11 0.00 6013.18 6013.18 0.28958315 16.60 12.64 0.00747948 35616.9 36.98 19.88 0.00747948 56381.8
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT19_FLR_3 FAN COIL ROOM_3_MULT19_FLR_3 N/A N/A N/A Yes Yes Yes No 86002.932 -999.000 7.843225 0.00307177 -999.000 -999.0000 1.00000 1.00000 1020.5079 1004.8586 1.0932 ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 7.843225 8.57416839   4197.9300 999.8980 40.96672859 13.37 6.70 6.67 1147076.31 7.4976 7.497437 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 unknown unknown unknown 7/21 14:30:00 Sensible 86002.93 86002.93 1.0000 8.57416839 7.843225 22.63 14.86 0.00842835 44171.8 12.80 11.16 0.00842835 34141.3 3.07145475 6.70 13.37 6.67 0.000 86002.93 40.80 0.00563111 18.58 0.00000000 0.0000 21.11 0.00842835 21.11 0.00842835 49.0949 72732.87 0.00 94264.37 92537.62 8.57416839 22.63 15.84 0.00842835 44171.8 12.05 11.64 0.00834854 33177.8
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT19_FLR_3 FAN COIL ROOM_3_MULT19_FLR_3 N/A N/A N/A Yes Yes Yes No 32042.686 32042.686 1.521731 0.00028032 915.685 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0932 ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 7.843225 8.57416839   4197.9300 999.8980 3.64619054 54.44 82.22 27.78 425213.25 7.5357 7.687333 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 32042.69 32042.69 1.0000 1.66354720 1.521731 21.11 13.51 0.00751430 40300.5 40.00 20.06 0.00800000 60796.0 0.28029480 60.00 32.22 27.78 0.000 32042.69 0.50 0.00431558 0.50 0.00000000 0.0000 21.11 0.00751430 21.11 0.00751430 43.8356 32043.09 0.00 34542.98 34542.98 1.66354720 16.60 12.68 0.00751430 35705.0 36.98 19.91 0.00751430 56469.7
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_4_MULT19_FLR_3 FAN COIL ROOM_4_MULT19_FLR_3 N/A N/A N/A Yes Yes Yes No 94466.478 -999.000 8.373796 0.00337406 -999.000 -999.0000 1.00000 1.00000 1020.8522 1004.8586 1.0932 ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 8.373796 9.15418568   4197.9300 999.8980 40.96672859 13.37 6.70 6.67 1147076.31 8.2354 8.235260 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:40:00 unknown unknown unknown 7/21 15:40:00 Sensible 94466.48 92371.96 1.0000 9.15418568 8.373796 22.63 15.02 0.00861360 44641.7 12.80 11.23 0.00850000 34322.2 3.37371652 6.70 13.37 6.67 0.000 94466.48 40.27 0.00563027 18.42 0.00000000 0.0000 21.11 0.00861360 21.11 0.00861360 50.1612 77647.07 0.00 103372.69 98118.20 9.15418568 22.63 16.00 0.00861360 44641.7 12.13 11.71 0.00838614 33349.3
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_4_MULT19_FLR_3 FAN COIL ROOM_4_MULT19_FLR_3 N/A N/A N/A Yes Yes Yes No 32146.752 32146.752 1.526673 0.00028123 918.658 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0932 ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 8.373796 9.15418568   4197.9300 999.8980 3.64619054 54.44 82.22 27.78 425213.25 7.5601 7.712299 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 32146.75 32146.75 1.0000 1.66894997 1.526673 21.11 13.51 0.00751555 40303.7 40.00 20.06 0.00800000 60796.0 0.28120512 60.00 32.22 27.78 0.000 32146.75 0.50 0.00431558 0.50 0.00000000 0.0000 21.11 0.00751555 21.11 0.00751555 43.8428 32147.16 0.00 34655.17 34655.17 1.66894997 16.60 12.68 0.00751555 35708.2 36.98 19.91 0.00751555 56472.9
ROOM_5_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_5_FLR_3 FAN COIL ROOM_5_FLR_3 N/A N/A N/A Yes Yes Yes No 12618.193 -999.000 1.150672 0.00045068 -999.000 -999.0000 1.00000 1.00000 1020.5958 1004.8586 1.0932 ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 1.150672 1.25790769   4197.9300 999.8980 40.96672859 13.37 6.70 6.67 1147076.31 1.1000 1.100010 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:30:00 unknown unknown unknown 7/21 10:30:00 Sensible 12618.19 12618.19 1.0000 1.25790769 1.150672 22.63 14.90 0.00847566 44291.8 12.80 11.21 0.00847566 34260.7 0.45063822 6.70 13.37 6.67 0.000 12618.19 36.74 0.00562481 17.31 0.00000000 0.0000 21.11 0.00847566 21.11 0.00847566 49.3671 10670.44 0.00 13827.01 13491.46 1.25790769 22.63 15.88 0.00847566 44291.8 12.12 11.69 0.00836995 33299.8
ROOM_5_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_5_FLR_3 FAN COIL ROOM_5_FLR_3 N/A N/A N/A Yes Yes Yes No 5563.539 5563.539 0.264211 0.00004867 158.992 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0932 ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 1.150672 1.25790769   4197.9300 999.8980 3.64619054 54.44 82.22 27.78 425213.25 1.3084 1.334744 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 5563.54 5563.54 1.0000 0.28883420 0.264211 21.11 13.48 0.00747828 40208.7 40.00 20.06 0.00800000 60796.0 0.04866730 60.00 32.22 27.78 0.000 5563.54 0.50 0.00431558 0.50 0.00000000 0.0000 21.11 0.00747828 21.11 0.00747828 43.6290 5563.68 0.00 5997.62 5997.62 0.28883420 16.60 12.64 0.00747828 35613.9 36.98 19.88 0.00747828 56378.8
ROOM_6_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_6_FLR_3 FAN COIL ROOM_6_FLR_3 N/A N/A N/A Yes Yes Yes No 12536.045 -999.000 1.143181 0.00044775 -999.000 -999.0000 1.00000 1.00000 1020.5953 1004.8586 1.0932 ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 1.143181 1.24971882   4197.9300 999.8980 40.96672859 13.37 6.70 6.67 1147076.31 1.0929 1.092849 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:20:00 unknown unknown unknown 7/21 10:20:00 Sensible 12536.05 12536.05 1.0000 1.24971882 1.143181 22.63 14.90 0.00847539 44291.2 12.80 11.21 0.00847539 34260.1 0.44770445 6.70 13.37 6.67 0.000 12536.05 36.41 0.00562429 17.20 0.00000000 0.0000 21.11 0.00847539 21.11 0.00847539 49.3655 10600.98 0.00 13737.03 13404.12 1.24971882 22.63 15.88 0.00847539 44291.2 12.12 11.69 0.00836983 33299.1
ROOM_6_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_6_FLR_3 FAN COIL ROOM_6_FLR_3 N/A N/A N/A Yes Yes Yes No 5568.100 5568.100 0.264428 0.00004871 159.122 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0932 ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 1.143181 1.24971882   4197.9300 999.8980 3.64619054 54.44 82.22 27.78 425213.25 1.3095 1.335838 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 5568.10 5568.10 1.0000 0.28907102 0.264428 21.11 13.48 0.00747868 40209.7 40.00 20.06 0.00800000 60796.0 0.04870720 60.00 32.22 27.78 0.000 5568.10 0.50 0.00431558 0.50 0.00000000 0.0000 21.11 0.00747868 21.11 0.00747868 43.6314 5568.24 0.00 6002.54 6002.54 0.28907102 16.60 12.64 0.00747868 35614.9 36.98 19.88 0.00747868 56379.8
CORRIDOR_FLR_3 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORRIDOR_FLR_3 VAV BOX CORRIDOR_FLR_3 N/A N/A N/A Yes Yes Yes No 15525.099 15525.099 1.394756 0.00013582 347.738 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0932 unknown unknown -999.0 -999.0   4197.9300 999.8980 3.64619054 54.44 82.22 27.78 425213.25 3.6511 3.724613 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 15525.10 15525.10 1.0000 1.52473958 1.394756 16.70 12.29 0.00800000 37036.7 40.00 20.06 0.00800000 60796.0 0.13580648 60.00 32.22 27.78 0.000 15525.10 0.50 0.00431558 0.50 0.00000000 0.0000 21.00 0.00758697 21.00 0.00758697 44.5567 8844.67 0.00 15609.17 15609.17 1.52473958 16.60 13.15 0.00800000 36934.7 26.64 16.89 0.00800000 47172.0
ROOM_1_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_6 FAN COIL ROOM_1_FLR_6 N/A N/A N/A Yes Yes Yes No 3879.408 -999.000 0.353766 0.00013856 -999.000 -999.0000 1.00000 1.00000 1020.6057 1004.8586 1.0932 ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.353766 0.38673546   4197.9300 999.8980 40.96672859 13.37 6.70 6.67 1147076.31 0.3382 0.338193 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:50:00 unknown unknown unknown 7/21 16:50:00 Sensible 3879.41 3879.41 1.0000 0.38673546 0.353766 22.63 14.91 0.00848097 44305.3 12.80 11.21 0.00848097 34274.1 0.13854674 6.70 13.37 6.67 0.000 3879.41 39.12 0.00562848 18.06 0.00000000 0.0000 21.11 0.00848097 21.11 0.00848097 49.3976 3280.55 0.00 4250.80 4144.83 0.38673546 22.63 15.88 0.00848097 44305.3 12.13 11.69 0.00837239 33313.8
ROOM_1_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_6 FAN COIL ROOM_1_FLR_6 N/A N/A N/A Yes Yes Yes No 1729.335 1729.335 0.082126 0.00001513 49.417 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0932 ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.353766 0.38673546   4197.9300 999.8980 3.64619054 54.44 82.22 27.78 425213.25 0.4067 0.414883 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 1729.34 1729.34 1.0000 0.08977936 0.082126 21.11 13.56 0.00756836 40437.5 40.00 20.06 0.00800000 60796.0 0.01512743 60.00 32.22 27.78 0.000 1729.34 0.50 0.00431558 0.50 0.00000000 0.0000 21.11 0.00756836 21.11 0.00756836 44.1482 1729.38 0.00 1864.26 1864.26 0.08977936 16.60 12.73 0.00756836 35841.9 36.98 19.95 0.00756836 56606.8
ROOM_2_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_6 FAN COIL ROOM_2_FLR_6 N/A N/A N/A Yes Yes Yes No 3850.596 -999.000 0.351139 0.00013753 -999.000 -999.0000 1.00000 1.00000 1020.6055 1004.8586 1.0932 ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.351139 0.38386328   4197.9300 999.8980 40.96672859 13.37 6.70 6.67 1147076.31 0.3357 0.335682 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:50:00 unknown unknown unknown 7/21 16:50:00 Sensible 3850.60 3850.60 1.0000 0.38386328 0.351139 22.63 14.91 0.00848085 44305.0 12.80 11.21 0.00848085 34273.9 0.13751777 6.70 13.37 6.67 0.000 3850.60 39.12 0.00562848 18.06 0.00000000 0.0000 21.11 0.00848085 21.11 0.00848085 49.3969 3256.19 0.00 4219.23 4114.11 0.38386328 22.63 15.88 0.00848085 44305.0 12.13 11.69 0.00837233 33313.5
ROOM_2_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_6 FAN COIL ROOM_2_FLR_6 N/A N/A N/A Yes Yes Yes No 1729.864 1729.864 0.082151 0.00001513 49.433 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0932 ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.351139 0.38386328   4197.9300 999.8980 3.64619054 54.44 82.22 27.78 425213.25 0.4068 0.415010 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 1729.86 1729.86 1.0000 0.08980682 0.082151 21.11 13.56 0.00756850 40437.8 40.00 20.06 0.00800000 60796.0 0.01513206 60.00 32.22 27.78 0.000 1729.86 0.50 0.00431558 0.50 0.00000000 0.0000 21.11 0.00756850 21.11 0.00756850 44.1491 1729.91 0.00 1864.83 1864.83 0.08980682 16.60 12.73 0.00756850 35842.3 36.98 19.95 0.00756850 56607.2
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT9_FLR_6 FAN COIL ROOM_3_MULT9_FLR_6 N/A N/A N/A Yes Yes Yes No 17593.473 -999.000 1.589953 0.00062839 -999.000 -999.0000 1.00000 1.00000 1020.7076 1004.8586 1.0932 ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 1.589953 1.73812792   4197.9300 999.8980 40.96672859 13.37 6.70 6.67 1147076.31 1.5338 1.533738 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 unknown unknown unknown 7/21 14:30:00 Sensible 17593.47 17468.65 1.0000 1.73812792 1.589953 22.63 14.95 0.00853580 44444.3 12.80 11.23 0.00850000 34322.2 0.62832225 6.70 13.37 6.67 0.000 17593.47 40.80 0.00563111 18.58 0.00000000 0.0000 21.11 0.00853580 21.11 0.00853580 49.7136 14743.42 0.00 19262.91 18592.30 1.73812792 22.63 15.93 0.00853580 44444.3 12.15 11.71 0.00838291 33361.7
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT9_FLR_6 FAN COIL ROOM_3_MULT9_FLR_6 N/A N/A N/A Yes Yes Yes No 8347.428 8347.428 0.396420 0.00007303 238.534 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0932 ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 1.589953 1.73812792   4197.9300 999.8980 3.64619054 54.44 82.22 27.78 425213.25 1.9631 2.002624 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 8347.43 8347.43 1.0000 0.43336424 0.396420 21.11 13.58 0.00758599 40482.4 40.00 20.06 0.00800000 60796.0 0.07301949 60.00 32.22 27.78 0.000 8347.43 0.50 0.00431558 0.50 0.00000000 0.0000 21.11 0.00758599 21.11 0.00758599 44.2495 8347.60 0.00 8998.74 8998.74 0.43336424 16.60 12.75 0.00758599 35886.6 36.98 19.96 0.00758599 56651.4
BANQUET_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown BANQUET_FLR_6 N/A N/A N/A Yes Yes Yes No 18141.000 18141.000 2.554616 0.00015871 388.007 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0932 unknown unknown -999.0 -999.0   4197.9300 999.8980 3.64619054 54.44 82.22 27.78 425213.25 4.2663 4.352191 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 18141.00 18141.00 1.0000 2.79269140 2.554616 16.70 12.29 0.00800000 37036.7 40.00 20.06 0.00800000 60796.0 0.15868919 60.00 32.22 27.78 0.000 18141.00 0.50 0.00431558 0.50 0.00000000 0.0000 21.00 0.00767888 21.00 0.00767888 45.0902 5903.54 0.00 18242.08 18242.08 2.79269140 16.60 13.15 0.00800000 36934.7 23.01 15.59 0.00800000 43466.8
DINING_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown DINING_FLR_6 N/A N/A N/A Yes Yes Yes No 18830.344 18830.344 2.675859 0.00016474 402.463 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0932 unknown unknown -999.0 -999.0   4197.9300 999.8980 3.64619054 54.44 82.22 27.78 425213.25 4.4284 4.517571 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 19:10:00 unknown unknown TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 19:10:00 Sensible 18830.34 18830.34 1.0000 2.92523314 2.675859 16.70 12.29 0.00800000 37036.7 40.00 20.06 0.00800000 60796.0 0.16471926 60.00 32.22 27.78 0.000 18830.34 0.50 0.00431558 0.50 0.00000000 0.0000 21.00 0.00768421 21.00 0.00768421 45.1218 6012.73 0.00 18935.29 18935.29 2.92523314 16.60 13.15 0.00800000 36934.7 22.95 15.57 0.00800000 43407.8
KITCHEN_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown KITCHEN_FLR_6 N/A N/A N/A Yes Yes Yes No 13392.173 13392.173 2.537815 0.00011716 280.739 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0932 unknown unknown -999.0 -999.0   4197.9300 999.8980 3.64619054 54.44 82.22 27.78 425213.25 3.1495 3.212905 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 23:30:00 unknown unknown TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 23:30:00 Sensible 13392.17 13392.17 1.0000 2.77432451 2.537815 16.70 12.29 0.00800000 37036.7 40.00 20.06 0.00800000 60796.0 0.11714862 60.00 32.22 27.78 0.000 13392.17 0.50 0.00431558 0.50 0.00000000 0.0000 20.20 0.00578905 21.00 0.00578905 34.1028 1286.91 0.00 13467.30 13467.30 2.77432451 16.60 13.15 0.00800000 36934.7 21.36 14.99 0.00800000 41789.0
CORRIDOR_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORRIDOR_FLR_6 VAV BOX CORRIDOR_FLR_6 N/A N/A N/A Yes Yes Yes No 10312.810 10312.810 0.848517 0.00009022 233.819 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0932 unknown unknown -999.0 -999.0   4197.9300 999.8980 3.64619054 54.44 82.22 27.78 425213.25 2.4253 2.474137 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 19:10:00 unknown unknown TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 19:10:00 Sensible 10312.81 10312.81 1.0000 0.92759367 0.848517 16.70 12.29 0.00800000 37036.7 40.00 20.06 0.00800000 60796.0 0.09021176 60.00 32.22 27.78 0.000 10312.81 0.50 0.00431558 0.50 0.00000000 0.0000 21.00 0.00773009 21.00 0.00773009 45.3875 6247.85 0.00 10368.40 10368.40 0.92759367 16.60 13.15 0.00800000 36934.7 27.56 17.21 0.00800000 48112.5
VAV WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC VAV WITH REHEAT BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; Coincident CoolingDesignCapacity N/A Yes Yes Yes No 821617.441 -999.000 24.659390 0.02934627 -999.000 -999.0000 1.00000 1.00000 1015.3079 1004.8586 1.0932 VAV WITH REHEAT FAN Fan:VariableVolume 24.659390 26.95750237   4197.9300 999.8980 40.96672859 13.37 6.70 6.67 1147076.31 71.6271 71.627095 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:40:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:40:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:40:00 Sensible 821617.44 821617.44 1.0000 26.95750237 24.659390 40.80 18.58 0.00563111 55507.6 10.78 7.37 0.00563111 25029.4 29.34327767 6.70 13.37 6.67 55252.781 766364.66 40.80 0.00563111 18.58 24.65939000 100.0000 23.99 0.00956200 23.99 0.00954907 46.6101 307915.97 0.00 822381.20 822381.20 26.95750237 40.80 19.66 0.00563111 55507.6 10.75 8.12 0.00563111 25001.0
VAV WITH REHEAT HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC VAV WITH REHEAT BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 131650.002 131650.002 7.397817 0.00115173 2309.983 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.0932 VAV WITH REHEAT FAN Fan:VariableVolume 24.659390 26.95750237   4197.9300 999.8980 3.64619054 54.44 82.22 27.78 425213.25 30.9609 31.584037 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 19:10:00 unknown unknown TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 19:10:00 Sensible 131650.00 131650.00 1.0000 8.08725071 7.397817 0.50 0.50 0.00431558 11299.5 16.70 12.29 0.00800000 37036.7 1.15161416 60.00 32.22 27.78 0.000 131650.00 0.50 0.00431558 0.50 24.65939000 333.3333 18.52 0.00760149 21.97 0.00786035 43.4756 57323.34 0.00 128301.45 128301.45 8.08725071 2.80 2.38 0.00431558 13629.0 18.46 10.16 0.00431558 29493.7
FLR_3_DOAS COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC FLR_3_DOAS ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; Coincident CoolingDesignCapacity N/A Yes Yes Yes No 65945.855 -999.000 2.051317 0.00235543 -999.000 -999.0000 1.00000 1.00000 1015.3079 1004.8586 1.0932 FLR_3_DOAS FAN Fan:ConstantVolume 2.051245 2.24240930   4197.9300 999.8980 40.96672859 13.37 6.70 6.67 1147076.31 5.7490 5.749038 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:30:00 Sensible 65945.86 65945.86 1.0000 2.24248814 2.051317 40.80 18.58 0.00563111 55507.6 11.84 7.85 0.00563111 26100.2 2.35519288 6.70 13.37 6.67 2195.006 63750.85 40.80 0.00563111 18.58 2.05124512 99.9965 21.11 0.00851439 21.11 0.00852349 49.6426 211994.85 0.00 66000.58 66000.58 2.24248814 40.80 19.66 0.00563111 55507.6 11.81 8.61 0.00563111 26075.8
FLR_3_DOAS HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC FLR_3_DOAS ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 10951.444 10951.444 0.615395 0.00009581 192.158 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.0932 FLR_3_DOAS FAN Fan:ConstantVolume 2.051245 2.24240930   4197.9300 999.8980 3.64619054 54.44 82.22 27.78 425213.25 2.5755 2.627351 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 10951.44 10951.44 1.0000 0.67274644 0.615395 0.50 0.50 0.00431558 11299.5 16.70 12.29 0.00800000 37036.7 0.09579823 60.00 32.22 27.78 0.000 10951.44 0.50 0.00431558 0.50 2.05124512 333.3216 21.11 0.00751467 21.11 0.00751538 43.8419 98280.72 0.00 10672.89 10672.89 0.67274644 2.80 2.38 0.00431558 13629.0 18.46 10.16 0.00431558 29493.7



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2023-10-16 08:58:43

Economizer

High Limit Shutoff Control Minimum Outdoor Air [m3/s] Maximum Outdoor Air [m3/s] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [C] Outdoor Air Enthalpy Limit [C]
VAV WITH REHEAT_OA_CONTROLLER DifferentialDryBulb 24.66 24.66 -      
FLR_3_DOAS_OA_CONTROLLER DifferentialDryBulb 2.05 2.05 -      


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [m3/s-person] Outdoor Air Per Area [m3/s-m2] Outdoor Air Per Zone [m3/s] Outdoor Air ACH [ach] Outdoor Air Method Outdoor Air Schedule Name Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule Name
BASEMENT VAV WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
RETAIL_1_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.001181 0.000000 0.000000 Flow/Area   1.00 1.00  
RETAIL_2_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.001181 0.000000 0.000000 Flow/Area   1.00 1.00  
MECH_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.000000 0.000000 0.000000 Flow/Area   1.00 1.00  
STORAGE_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.000610 0.000000 0.000000 Flow/Area   1.00 1.00  
LAUNDRY_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.000000 0.000000 0.000000 Flow/Area   1.00 1.00  
CAFE_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.003581 0.000000 0.000000 Flow/Area   1.00 1.00  
LOBBY_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.001448 0.000000 0.000000 Flow/Area   1.00 1.00  
CORRIDOR_FLR_3 VAV WITH REHEAT_DCV 0.000000 0.000305 0.000000 0.000000 Flow/Area   1.00 1.00  
BANQUET_FLR_6 VAV WITH REHEAT_DCV 0.000000 0.003581 0.000000 0.000000 Flow/Area   1.00 1.00  
DINING_FLR_6 VAV WITH REHEAT_DCV 0.000000 0.003581 0.000000 0.000000 Flow/Area   1.00 1.00  
KITCHEN_FLR_6 VAV WITH REHEAT_DCV 0.000000 0.003556 0.000000 0.000000 Flow/Area   1.00 1.00  
CORRIDOR_FLR_6 VAV WITH REHEAT_DCV 0.000000 0.000305 0.000000 0.000000 Flow/Area   1.00 1.00  


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
BASEMENT 352.00 8760.00 352.00
RETAIL_1_FLR_1 395.67 8589.17 364.83
RETAIL_2_FLR_1 41.50 8760.00 41.50
MECH_FLR_1 580.67 8760.00 580.67
STORAGE_FLR_1 967.83 8760.00 967.83
LAUNDRY_FLR_1 3472.67 4326.33 1126.83
CAFE_FLR_1 64.33 8482.17 30.50
LOBBY_FLR_1 0.00 8760.00 0.00
ROOM_1_FLR_3 378.50 8147.00 287.67
ROOM_2_FLR_3 787.33 8268.33 731.00
ROOM_3_MULT19_FLR_3 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 196.17 8760.00 196.17
ROOM_5_FLR_3 353.00 8051.67 273.50
ROOM_6_FLR_3 684.33 8142.33 650.83
CORRIDOR_FLR_3 461.67 8760.00 461.67
ROOM_1_FLR_6 878.83 7839.00 567.33
ROOM_2_FLR_6 1324.17 7993.50 1090.67
ROOM_3_MULT9_FLR_6 278.00 7824.67 131.33
BANQUET_FLR_6 253.50 8074.67 13.00
DINING_FLR_6 430.00 7746.83 1.67
KITCHEN_FLR_6 6864.33 6843.17 5409.83
CORRIDOR_FLR_6 636.00 8760.00 636.00
Facility 7477.83 8760.00 6325.83
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
BASEMENT 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 0.00 0.00 0.00 0.00
MECH_FLR_1 0.00 0.00 0.00 0.00
STORAGE_FLR_1 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 0.00 0.00 0.00 0.00
CAFE_FLR_1 0.00 0.00 0.00 0.00
LOBBY_FLR_1 0.00 0.00 0.00 0.00
ROOM_1_FLR_3 0.00 5.50 0.00 5.50
ROOM_2_FLR_3 0.00 4.33 0.00 4.33
ROOM_3_MULT19_FLR_3 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 0.00 3.17 0.00 3.17
ROOM_5_FLR_3 0.00 3.00 0.00 3.00
ROOM_6_FLR_3 0.00 3.17 0.00 3.17
CORRIDOR_FLR_3 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 0.00 15.00 0.00 15.00
ROOM_2_FLR_6 0.00 12.83 0.00 12.83
ROOM_3_MULT9_FLR_6 0.00 14.33 0.00 14.33
BANQUET_FLR_6 0.00 0.00 0.00 0.00
DINING_FLR_6 0.00 0.00 0.00 0.00
KITCHEN_FLR_6 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6 0.00 0.00 0.00 0.00
Facility 0.00 26.17 0.00 26.17
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2023-10-16 08:58:43

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
BASEMENT 61.80 106.50 4826.41 2.158 0.000 0.000 0.000
RETAIL_1_FLR_1 6.28 10.83 265.76 5.446 0.239 0.000 0.000
RETAIL_2_FLR_1 7.28 12.54 307.76 3.332 0.080 0.000 0.000
MECH_FLR_1 1.54 2.65 650.80 1.737 0.089 0.000 0.000
STORAGE_FLR_1 1.18 2.04 375.47 1.525 0.089 0.000 0.000
LAUNDRY_FLR_1 4.87 8.40 309.22 42.728 0.256 0.000 0.000
CAFE_FLR_1 82.58 142.30 748.35 7.994 0.188 0.000 0.000
LOBBY_FLR_1 245.14 422.44 5183.56 3.775 0.077 0.000 0.000
ROOM_1_FLR_3 0.95 1.50 118.94 0.474 0.310 0.000 0.052
ROOM_2_FLR_3 0.95 1.50 118.93 0.473 0.310 0.000 0.048
ROOM_3_MULT19_FLR_3   1.50 74.75        
ROOM_4_MULT19_FLR_3 0.95 1.50 74.77 0.538 0.138 0.000 0.077
ROOM_5_FLR_3 0.95 1.50 118.94 0.474 0.310 0.000 0.052
ROOM_6_FLR_3 0.95 1.50 118.93 0.474 0.310 0.000 0.049
CORRIDOR_FLR_3 12.16 20.96 1186.91 1.071 0.038 0.000 0.000
ROOM_1_FLR_6 0.95 1.50 118.94 0.474 0.310 0.000 0.061
ROOM_2_FLR_6 0.95 1.50 118.93 0.473 0.310 0.000 0.056
ROOM_3_MULT9_FLR_6 0.95 1.50 74.77 0.538 0.253 0.000 0.097
BANQUET_FLR_6 145.01 249.90 1010.89 9.227 0.089 0.000 0.000
DINING_FLR_6 145.01 249.90 1010.89 9.666 0.089 0.000 0.000
KITCHEN_FLR_6 12.90 22.24 314.87 29.615 0.258 0.000 0.000
CORRIDOR_FLR_6 12.87 22.18 1256.16 2.461 0.063 0.000 0.000
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
BASEMENT 61.80 106.50 4826.41 2.115 0.000 0.000 0.000
RETAIL_1_FLR_1 6.28 10.83 265.76 5.347 0.005 0.000 0.000
RETAIL_2_FLR_1 7.28 12.54 307.76 3.267 0.002 0.000 0.000
MECH_FLR_1 1.54 2.65 650.80 1.704 0.002 0.000 0.000
STORAGE_FLR_1 1.18 2.04 375.47 1.496 0.002 0.000 0.000
LAUNDRY_FLR_1 4.87 8.40 309.22 41.862 0.005 0.000 0.000
CAFE_FLR_1 82.58 142.30 748.35 7.842 0.004 0.000 0.000
LOBBY_FLR_1 245.14 422.44 5183.56 3.699 0.001 0.000 0.000
ROOM_1_FLR_3 0.95 1.50 118.94 0.464 0.006 0.000 0.000
ROOM_2_FLR_3 0.95 1.50 118.93 0.463 0.006 0.000 0.000
ROOM_3_MULT19_FLR_3   1.50 74.75        
ROOM_4_MULT19_FLR_3 0.95 1.50 74.77 0.527 0.003 0.000 0.000
ROOM_5_FLR_3 0.95 1.50 118.94 0.464 0.006 0.000 0.000
ROOM_6_FLR_3 0.95 1.50 118.93 0.464 0.006 0.000 0.000
CORRIDOR_FLR_3 12.16 20.96 1186.91 1.049 0.001 0.000 0.000
ROOM_1_FLR_6 0.95 1.50 118.94 0.463 0.006 0.000 0.000
ROOM_2_FLR_6 0.95 1.50 118.93 0.462 0.006 0.000 0.000
ROOM_3_MULT9_FLR_6 0.95 1.50 74.77 0.527 0.005 0.000 0.000
BANQUET_FLR_6 145.01 249.90 1010.89 9.028 0.002 0.000 0.000
DINING_FLR_6 145.01 249.90 1010.89 9.457 0.002 0.000 0.000
KITCHEN_FLR_6 12.90 22.24 314.87 29.003 0.005 0.000 0.000
CORRIDOR_FLR_6 12.87 22.18 1256.16 2.412 0.001 0.000 0.000
Values shown for a single zone without multipliers


Table of Contents

Report: Outdoor Air Details

For: Entire Facility

Timestamp: 2023-10-16 08:58:43

Mechanical Ventilation Parameters by Zone

AirLoop Name Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Zone Area [m2] Design Zone Outdoor Airflow - Voz [m3/s] Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s]
BASEMENT VAV WITH REHEAT 61.80 106.50 4826.41 1978.83 0.0000 0.854
RETAIL_1_FLR_1 VAV WITH REHEAT 6.28 10.83 265.76 67.07 0.0000 0.079
RETAIL_2_FLR_1 VAV WITH REHEAT 7.28 12.54 307.76 77.67 0.0000 0.092
MECH_FLR_1 VAV WITH REHEAT 1.54 2.65 650.80 164.24 0.0000 0.000
STORAGE_FLR_1 VAV WITH REHEAT 1.18 2.04 375.47 94.76 0.0000 0.058
LAUNDRY_FLR_1 VAV WITH REHEAT 4.87 8.40 309.22 78.04 0.0000 0.000
CAFE_FLR_1 VAV WITH REHEAT 82.58 142.30 748.35 188.86 0.0000 0.676
LOBBY_FLR_1 VAV WITH REHEAT 245.14 422.44 5183.56 1308.19 0.0000 1.894
ROOM_1_FLR_3 FLR_3_DOAS 0.95 1.50 118.94 39.02 0.0000 0.062
ROOM_2_FLR_3 FLR_3_DOAS 0.95 1.50 118.93 39.02 0.0000 0.062
ROOM_3_MULT19_FLR_3 FLR_3_DOAS   1.50 74.75 24.52 0.0000 0.837
ROOM_4_MULT19_FLR_3 FLR_3_DOAS 0.95 1.50 74.77 24.53 0.0000 0.837
ROOM_5_FLR_3 FLR_3_DOAS 0.95 1.50 118.94 39.02 0.0000 0.062
ROOM_6_FLR_3 FLR_3_DOAS 0.95 1.50 118.93 39.02 0.0000 0.062
CORRIDOR_FLR_3 VAV WITH REHEAT 12.16 20.96 1186.91 389.40 0.0000 0.475
ROOM_1_FLR_6 FLR_3_DOAS 0.95 1.50 118.94 39.02 0.0000 0.015
ROOM_2_FLR_6 FLR_3_DOAS 0.95 1.50 118.93 39.02 0.0000 0.015
ROOM_3_MULT9_FLR_6 FLR_3_DOAS 0.95 1.50 74.77 24.53 0.0000 0.099
BANQUET_FLR_6 VAV WITH REHEAT 145.01 249.90 1010.89 331.66 0.0000 1.188
DINING_FLR_6 VAV WITH REHEAT 145.01 249.90 1010.89 331.66 0.0000 1.188
KITCHEN_FLR_6 VAV WITH REHEAT 12.90 22.24 314.87 103.30 0.0000 0.367
CORRIDOR_FLR_6 VAV WITH REHEAT 12.87 22.18 1256.16 412.12 0.0000 0.126
Total Facility   873.39 1604.23 35184.81 11345.29 0.0000 137.584


Total Outdoor Air by Zone

Mechanical Ventilation [m3] Natural Ventilation [m3] Total Ventilation [m3] Infiltration [m3] Total Ventilation and Infiltration [m3] Dynamic Target Ventilation - Voz-dyn [m3] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr] Time Above Zero When Unoccupied [hr]
BASEMENT 90165337.77 0.00 90165337.77 0.00 90165337.77 26946214.98 0.00 0.00 8760.00 0.00
RETAIL_1_FLR_1 12529874.96 0.00 12529874.96 549390.10 13079265.06 2498216.28 0.00 0.00 8760.00 0.00
RETAIL_2_FLR_1 8878616.97 0.00 8878616.97 212065.27 9090682.24 2892943.94 0.00 0.00 8760.00 0.00
MECH_FLR_1 9795547.26 0.00 9795547.26 501196.32 10296743.58 0.00 0.00 0.00 8760.00 0.00
STORAGE_FLR_1 4962469.25 0.00 4962469.25 289162.67 5251631.92 1821682.01 0.00 0.00 8760.00 0.00
LAUNDRY_FLR_1 0.11E+09 0.00 0.11E+09 684357.98 0.12E+09 0.00 0.00 0.00 8760.00 0.00
CAFE_FLR_1 51739930.33 0.00 51739930.33 1214457.92 52954388.25 21330615.53 0.00 0.00 8760.00 0.00
LOBBY_FLR_1 0.17E+09 0.00 0.17E+09 3469983.66 0.17E+09 59728886.00 0.00 0.00 8760.00 0.00
ROOM_1_FLR_3 1946875.62 53368.25 2000243.87 318881.11 2319124.98 1946875.62 0.00 7861.67 898.33 0.00
ROOM_2_FLR_3 1946647.51 49733.90 1996381.41 318856.78 2315238.19 1946647.51 0.00 7861.67 898.33 0.00
ROOM_3_MULT19_FLR_3 26397887.27 59101.16 26456988.43 88971.41 26545959.84 26397887.27 0.00 7878.50 881.50 8760.00
ROOM_4_MULT19_FLR_3 26405105.73 49704.64 26454810.37 88995.74 26543806.11 26405105.73 0.00 7909.59 850.41 0.00
ROOM_5_FLR_3 1946875.62 53523.29 2000398.91 318881.11 2319280.03 1946875.62 0.00 7861.67 898.33 0.00
ROOM_6_FLR_3 1946647.51 49913.38 1996560.89 318856.78 2315417.68 1946647.51 0.00 7861.67 898.33 0.00
CORRIDOR_FLR_3 43983951.43 0.00 43983951.43 385591.42 44369542.85 14972100.18 0.00 0.00 8760.00 0.00
ROOM_1_FLR_6 486718.90 62396.04 549114.95 318945.54 868060.48 486718.90 0.00 7861.67 898.33 0.00
ROOM_2_FLR_6 486661.88 57577.57 544239.45 318921.20 863160.65 486661.88 0.00 7861.67 898.33 0.00
ROOM_3_MULT9_FLR_6 3126920.42 62612.39 3189532.80 163183.70 3352716.50 3126920.42 0.00 7861.67 898.33 0.00
BANQUET_FLR_6 80560382.02 0.00 80560382.02 778784.84 81339166.86 37458366.31 0.00 0.00 8760.00 0.00
DINING_FLR_6 84383795.27 0.00 84383795.27 778784.84 85162580.12 37458366.31 0.00 0.00 8760.00 0.00
KITCHEN_FLR_6 80137262.14 0.00 80137262.14 697192.99 80834455.13 11584760.86 0.00 0.00 8760.00 0.00
CORRIDOR_FLR_6 26758166.15 0.00 26758166.15 682373.60 27440539.74 3961413.96 0.00 0.00 8760.00 0.00
Total Facility 0.50E+10 9778881.31 0.50E+10 32134041.92 0.50E+10 0.43E+10 0.00 7924.04 8760.00 8760.00


Average Outdoor Air During Occupancy by Zone - Flow Rates

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Infiltration [m3/s] Total Ventilation and Infiltration [m3/s] Dynamic Target Ventilation - Voz-dyn [m3/s] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr]
BASEMENT 2.8591 0.0000 2.8591 0.0000 2.8591 0.8545 0.00 0.00 8760.00
RETAIL_1_FLR_1 0.3973 0.0000 0.3973 0.0174 0.4147 0.0792 0.00 0.00 8760.00
RETAIL_2_FLR_1 0.2815 0.0000 0.2815 0.0067 0.2883 0.0917 0.00 0.00 8760.00
MECH_FLR_1 0.3106 0.0000 0.3106 0.0159 0.3265 0.0000 0.00 0.00 8760.00
STORAGE_FLR_1 0.1574 0.0000 0.1574 0.0092 0.1665 0.0578 0.00 0.00 8760.00
LAUNDRY_FLR_1 3.6260 0.0000 3.6260 0.0217 3.6477 0.0000 0.00 0.00 8760.00
CAFE_FLR_1 1.6407 0.0000 1.6407 0.0385 1.6792 0.6764 0.00 0.00 8760.00
LOBBY_FLR_1 5.3670 0.0000 5.3670 0.1100 5.4770 1.8940 0.00 0.00 8760.00
ROOM_1_FLR_3 0.0617 0.0017 0.0634 0.0101 0.0735 0.0617 0.00 7861.67 898.33
ROOM_2_FLR_3 0.0617 0.0016 0.0633 0.0101 0.0734 0.0617 0.00 7861.67 898.33
ROOM_4_MULT19_FLR_3 0.8373 0.0016 0.8389 0.0028 0.8417 0.8373 0.00 7909.59 850.41
ROOM_5_FLR_3 0.0617 0.0017 0.0634 0.0101 0.0735 0.0617 0.00 7861.67 898.33
ROOM_6_FLR_3 0.0617 0.0016 0.0633 0.0101 0.0734 0.0617 0.00 7861.67 898.33
CORRIDOR_FLR_3 1.3947 0.0000 1.3947 0.0122 1.4069 0.4748 0.00 0.00 8760.00
ROOM_1_FLR_6 0.0154 0.0020 0.0174 0.0101 0.0275 0.0154 0.00 7861.67 898.33
ROOM_2_FLR_6 0.0154 0.0018 0.0173 0.0101 0.0274 0.0154 0.00 7861.67 898.33
ROOM_3_MULT9_FLR_6 0.0992 0.0020 0.1011 0.0052 0.1063 0.0992 0.00 7861.67 898.33
BANQUET_FLR_6 2.5546 0.0000 2.5546 0.0247 2.5792 1.1878 0.00 0.00 8760.00
DINING_FLR_6 2.6758 0.0000 2.6758 0.0247 2.7005 1.1878 0.00 0.00 8760.00
KITCHEN_FLR_6 2.5411 0.0000 2.5411 0.0221 2.5632 0.3674 0.00 0.00 8760.00
CORRIDOR_FLR_6 0.8485 0.0000 0.8485 0.0216 0.8701 0.1256 0.00 0.00 8760.00
Total Facility 94.3842 0.1677 94.5519 0.8045 95.3564 73.9670 0.00 7924.04 8760.00


Total Outdoor Air by AirLoop

Mechanical Ventilation [m3] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr] Time Above Zero When Unoccupied [hr]
VAV WITH REHEAT 0.93E+09 0.00 0.93E+09 0.22E+09 0.00 0.00 8760.00 0.00
FLR_3_DOAS 77309717.76 497930.62 77807648.39 64690340.46 0.00 0.00 8760.00 0.00


Average Outdoor Air During Occupancy by AirLoop

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr]
VAV WITH REHEAT 29.4637 0.0000 29.4637 6.9969 0.00 0.00 8760.00
FLR_3_DOAS 2.4515 0.0158 2.4673 2.0513 0.00 0.00 8760.00


Outdoor Air Controller Limiting Factors by AirLoop

No Limiting Factor [hr] Limits and Scheduled Limits [hr] Economizer [hr] Exhaust Flow [hr] Mixed Air Flow [hr] High Humidity [hr] Demand Controlled Ventilation [hr] Night Ventilation [hr] Demand Limiting [hr] Energy Management System [hr]
VAV WITH REHEAT 0.00 1900.23 0.00 0.00 6859.77 0.00 0.00 0.00 0.00 0.00
FLR_3_DOAS 0.00 6522.10 2237.90 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Average Outdoor Air for Limiting Factors During Occupancy

No Limiting Factor [m3/s] Limits and Scheduled Limits [m3/s] Economizer [m3/s] Exhaust Flow [m3/s] Mixed Air Flow [m3/s] High Humidity [m3/s] Demand Controlled Ventilation [m3/s] Night Ventilation [m3/s] Demand Limiting [m3/s] Energy Management System [m3/s]
VAV WITH REHEAT 0.0000 29.4734 0.0000 0.0000 29.4653 0.0000 0.0000 0.0000 0.0000 0.0000
FLR_3_DOAS 0.0000 2.4515 2.4525 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000



Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2023-10-16 08:58:43

Surfaces by Class

Total Outdoors
Wall 119 44
Floor 25 0
Roof 33 11
Internal Mass 22 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 30 30
Door 6 6
Glass Door 0 0
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 2
Conditioned Zones 22
Unconditioned Zones 0
Supply Plenums 0
Return Plenums 0


Input Fields

Count
IDF Objects 1306
Defaulted Fields 1181
Fields with Defaults 3945
Autosized Fields 350
Autosizable Fields 402
Autocalculated Fields 280
Autocalculatable Fields 539



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2023-10-16 08:58:43

Annual and Peak Values - Electricity

Electricity Annual Value [GJ] Electricity Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Electricity Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
Electricity:Facility 10039.01 144844.55 26-OCT-01:50 628839.67 28-JUN-18:10
Electricity:Building 2943.68 36656.90 02-JAN-02:10 182730.36 02-JAN-20:10
Electricity:Zone:BASEMENT 315.54 3631.19 02-JAN-02:10 23630.80 02-JAN-20:10
Electricity:SpaceType:GENERAL 2925.41 36182.64 02-JAN-02:10 182063.43 02-JAN-20:10
InteriorLights:Electricity 1174.11 10291.59 02-JAN-02:10 93091.76 02-JAN-20:10
InteriorLights:Electricity:Zone:BASEMENT 165.29 1501.97 02-JAN-02:10 13517.00 02-JAN-20:10
InteriorLights:Electricity:SpaceType:GENERAL 1174.11 10291.59 02-JAN-02:10 93091.76 02-JAN-20:10
LightsWired:InteriorLights:Electricity 1174.11 10291.59 02-JAN-02:10 93091.76 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:BASEMENT 165.29 1501.97 02-JAN-02:10 13517.00 02-JAN-20:10
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL 1174.11 10291.59 02-JAN-02:10 93091.76 02-JAN-20:10
Electricity:Zone:RETAIL_1_FLR_1 18.59 220.70 02-JAN-02:10 1372.90 02-JAN-20:10
InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 8.40 76.37 02-JAN-02:10 687.30 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 8.40 76.37 02-JAN-02:10 687.30 02-JAN-20:10
Electricity:Zone:RETAIL_2_FLR_1 21.53 255.58 02-JAN-02:10 1589.82 02-JAN-20:10
InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 9.73 88.43 02-JAN-02:10 795.89 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 9.73 88.43 02-JAN-02:10 795.89 02-JAN-20:10
Electricity:Zone:MECH_FLR_1 30.66 342.02 02-JAN-02:10 2327.13 02-JAN-20:10
InteriorLights:Electricity:Zone:MECH_FLR_1 18.19 165.30 02-JAN-02:10 1487.69 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:MECH_FLR_1 18.19 165.30 02-JAN-02:10 1487.69 02-JAN-20:10
Electricity:Zone:STORAGE_FLR_1 6.94 81.32 02-JAN-02:10 515.26 02-JAN-20:10
InteriorLights:Electricity:Zone:STORAGE_FLR_1 3.34 30.34 02-JAN-02:10 273.10 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:STORAGE_FLR_1 3.34 30.34 02-JAN-02:10 273.10 02-JAN-20:10
Electricity:Zone:LAUNDRY_FLR_1 72.06 1000.18 02-JAN-02:10 4910.17 02-JAN-20:10
InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 4.13 37.49 02-JAN-02:10 337.37 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 4.13 37.49 02-JAN-02:10 337.37 02-JAN-20:10
Electricity:Zone:CAFE_FLR_1 40.96 445.13 02-JAN-02:10 3142.50 02-JAN-20:10
InteriorLights:Electricity:Zone:CAFE_FLR_1 26.62 241.91 02-JAN-02:10 2177.23 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:CAFE_FLR_1 26.62 241.91 02-JAN-02:10 2177.23 02-JAN-20:10
Electricity:Zone:LOBBY_FLR_1 293.89 3428.00 02-JAN-02:10 21878.53 02-JAN-20:10
InteriorLights:Electricity:Zone:LOBBY_FLR_1 144.90 1316.59 02-JAN-02:10 11849.32 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:LOBBY_FLR_1 144.90 1316.59 02-JAN-02:10 11849.32 02-JAN-20:10
Electricity:Zone:ROOM_1_FLR_3 32.70 383.52 01-JAN-02:10 2308.42 01-JAN-21:10
InteriorLights:Electricity:Zone:ROOM_1_FLR_3 20.41 172.80 01-JAN-02:10 1570.91 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_3 20.41 172.80 01-JAN-02:10 1570.91 01-JAN-19:10
Electricity:Zone:ROOM_2_FLR_3 32.70 383.47 01-JAN-02:10 2308.15 01-JAN-21:10
InteriorLights:Electricity:Zone:ROOM_2_FLR_3 20.41 172.78 01-JAN-02:10 1570.72 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_3 20.41 172.78 01-JAN-02:10 1570.72 01-JAN-19:10
Electricity:Zone:ROOM_3_MULT19_FLR_3 472.46 5984.83 01-JAN-02:10 32482.97 01-JAN-21:10
InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 243.71 2063.36 01-JAN-02:10 18757.86 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 243.71 2063.36 01-JAN-02:10 18757.86 01-JAN-19:10
Electricity:Zone:ROOM_4_MULT19_FLR_3 472.59 5986.46 01-JAN-02:10 32491.86 01-JAN-21:10
InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 243.77 2063.93 01-JAN-02:10 18762.99 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 243.77 2063.93 01-JAN-02:10 18762.99 01-JAN-19:10
Electricity:Zone:ROOM_5_FLR_3 32.70 383.52 01-JAN-02:10 2308.42 01-JAN-21:10
InteriorLights:Electricity:Zone:ROOM_5_FLR_3 20.41 172.80 01-JAN-02:10 1570.91 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_5_FLR_3 20.41 172.80 01-JAN-02:10 1570.91 01-JAN-19:10
Electricity:Zone:ROOM_6_FLR_3 32.70 383.47 01-JAN-02:10 2308.15 01-JAN-21:10
InteriorLights:Electricity:Zone:ROOM_6_FLR_3 20.41 172.78 01-JAN-02:10 1570.72 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_6_FLR_3 20.41 172.78 01-JAN-02:10 1570.72 01-JAN-19:10
Electricity:Zone:CORRIDOR_FLR_3 62.74 570.05 02-JAN-02:10 5130.41 02-JAN-20:10
InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 62.74 570.05 02-JAN-02:10 5130.41 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 62.74 570.05 02-JAN-02:10 5130.41 02-JAN-20:10
Electricity:Zone:ROOM_1_FLR_6 8.18 95.88 01-JAN-02:10 577.11 01-JAN-21:10
InteriorLights:Electricity:Zone:ROOM_1_FLR_6 5.10 43.20 01-JAN-02:10 392.73 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_6 5.10 43.20 01-JAN-02:10 392.73 01-JAN-19:10
Electricity:Zone:ROOM_2_FLR_6 8.17 95.87 01-JAN-02:10 577.04 01-JAN-21:10
InteriorLights:Electricity:Zone:ROOM_2_FLR_6 5.10 43.19 01-JAN-02:10 392.68 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_6 5.10 43.19 01-JAN-02:10 392.68 01-JAN-19:10
Electricity:Zone:ROOM_3_MULT9_FLR_6 55.96 708.92 01-JAN-02:10 3847.72 01-JAN-21:10
InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 28.87 244.41 01-JAN-02:10 2221.93 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 28.87 244.41 01-JAN-02:10 2221.93 01-JAN-19:10
Electricity:Zone:BANQUET_FLR_6 222.61 2674.12 02-JAN-02:10 10571.30 02-JAN-20:10
InteriorLights:Electricity:Zone:BANQUET_FLR_6 46.75 424.82 02-JAN-02:10 3823.39 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:BANQUET_FLR_6 46.75 424.82 02-JAN-02:10 3823.39 02-JAN-20:10
Electricity:Zone:DINING_FLR_6 222.61 2674.12 02-JAN-02:10 10571.30 02-JAN-20:10
InteriorLights:Electricity:Zone:DINING_FLR_6 46.75 424.82 02-JAN-02:10 3823.39 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:DINING_FLR_6 46.75 424.82 02-JAN-02:10 3823.39 02-JAN-20:10
Electricity:Zone:KITCHEN_FLR_6 470.78 6777.71 02-JAN-02:10 19298.76 01-JAN-11:10
InteriorLights:Electricity:Zone:KITCHEN_FLR_6 12.48 113.42 02-JAN-02:10 1020.78 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:KITCHEN_FLR_6 12.48 113.42 02-JAN-02:10 1020.78 02-JAN-20:10
Electricity:Zone:CORRIDOR_FLR_6 16.60 150.83 02-JAN-02:10 1357.44 02-JAN-20:10
InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 16.60 150.83 02-JAN-02:10 1357.44 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 16.60 150.83 02-JAN-02:10 1357.44 02-JAN-20:10
InteriorEquipment:Electricity 1751.30 25891.05 02-JAN-02:10 89674.66 02-JAN-07:10
InteriorEquipment:Electricity:Zone:BASEMENT 150.26 2129.22 02-JAN-02:10 10113.80 02-JAN-20:10
InteriorEquipment:Electricity:SpaceType:GENERAL 1751.30 25891.05 02-JAN-02:10 89674.66 02-JAN-07:10
MiscPlug:InteriorEquipment:Electricity 959.56 15202.41 02-JAN-02:10 59492.27 02-JAN-07:10
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT 150.26 2129.22 02-JAN-02:10 10113.80 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL 959.56 15202.41 02-JAN-02:10 59492.27 02-JAN-07:10
InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 10.19 144.34 02-JAN-02:10 685.60 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 10.19 144.34 02-JAN-02:10 685.60 02-JAN-20:10
InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 11.79 167.14 02-JAN-02:10 793.93 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 11.79 167.14 02-JAN-02:10 793.93 02-JAN-20:10
InteriorEquipment:Electricity:Zone:MECH_FLR_1 12.47 176.73 02-JAN-02:10 839.45 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:MECH_FLR_1 12.47 176.73 02-JAN-02:10 839.45 02-JAN-20:10
InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 3.60 50.98 02-JAN-02:10 242.16 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 3.60 50.98 02-JAN-02:10 242.16 02-JAN-20:10
InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 67.94 962.69 02-JAN-02:10 4572.80 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 67.94 962.69 02-JAN-02:10 4572.80 02-JAN-20:10
InteriorEquipment:Electricity:Zone:CAFE_FLR_1 14.34 203.22 02-JAN-02:10 965.27 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:CAFE_FLR_1 14.34 203.22 02-JAN-02:10 965.27 02-JAN-20:10
InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 149.00 2111.41 02-JAN-02:10 10029.21 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 149.00 2111.41 02-JAN-02:10 10029.21 02-JAN-20:10
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 12.29 210.72 01-JAN-00:10 948.23 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 12.29 210.72 01-JAN-00:10 948.23 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 12.29 210.69 01-JAN-00:10 948.12 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 12.29 210.69 01-JAN-00:10 948.12 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 228.75 3921.46 01-JAN-00:10 17646.57 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 228.75 3921.46 01-JAN-00:10 17646.57 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 228.82 3922.53 01-JAN-00:10 17651.40 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 228.82 3922.53 01-JAN-00:10 17651.40 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 12.29 210.72 01-JAN-00:10 948.23 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 12.29 210.72 01-JAN-00:10 948.23 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 12.29 210.69 01-JAN-00:10 948.12 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 12.29 210.69 01-JAN-00:10 948.12 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 3.07 52.68 01-JAN-00:10 237.06 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 3.07 52.68 01-JAN-00:10 237.06 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 3.07 52.67 01-JAN-00:10 237.03 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 3.07 52.67 01-JAN-00:10 237.03 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 27.10 464.51 01-JAN-00:10 2090.30 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 27.10 464.51 01-JAN-00:10 2090.30 01-JAN-08:10
InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 175.86 2249.30 01-JAN-00:10 6747.90 01-JAN-07:10
Cooking:InteriorEquipment:Electricity 762.04 9746.88 01-JAN-00:10 29240.64 01-JAN-07:10
Cooking:InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 175.86 2249.30 01-JAN-00:10 6747.90 01-JAN-07:10
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL 762.04 9746.88 01-JAN-00:10 29240.64 01-JAN-07:10
InteriorEquipment:Electricity:Zone:DINING_FLR_6 175.86 2249.30 01-JAN-00:10 6747.90 01-JAN-07:10
Cooking:InteriorEquipment:Electricity:Zone:DINING_FLR_6 175.86 2249.30 01-JAN-00:10 6747.90 01-JAN-07:10
InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 440.03 6190.03 01-JAN-00:10 16686.59 01-JAN-07:10
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 410.33 5248.28 01-JAN-00:10 15744.84 01-JAN-07:10
ReachInFreezer:InteriorEquipment:Electricity 16.27 515.92 01-JAN-00:10 515.92 01-JAN-00:10
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 16.27 515.92 01-JAN-00:10 515.92 01-JAN-00:10
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL 16.27 515.92 01-JAN-00:10 515.92 01-JAN-00:10
ReachInRefrigerator:InteriorEquipment:Electricity 13.43 425.83 01-JAN-00:10 425.83 01-JAN-00:10
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 13.43 425.83 01-JAN-00:10 425.83 01-JAN-00:10
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL 13.43 425.83 01-JAN-00:10 425.83 01-JAN-00:10
Refrigeration:Electricity 74.19 1237.52 05-DEC-23:30 3639.15 14-JUL-07:00
Refrigeration:Electricity:Zone:KITCHEN_FLR_6 18.27 261.51 02-JAN-11:30 2271.91 01-JAN-11:10
General:Refrigeration:Electricity 18.27 261.51 02-JAN-11:30 2271.91 01-JAN-11:10
General:Refrigeration:Electricity:Zone:KITCHEN_FLR_6 18.27 261.51 02-JAN-11:30 2271.91 01-JAN-11:10
Electricity:Plant 3505.21 2806.60 29-MAR-00:50 342325.72 17-JUN-16:00
LowTempRefrigeration:Refrigeration:Electricity 22.43 0.00 01-JAN-11:10 1889.40 27-JUN-07:20
MedTempRefrigeration:Refrigeration:Electricity 33.49 935.76 22-MAY-02:50 1196.73 14-JUL-13:10
Fans:Electricity 2057.84 58067.15 14-OCT-05:40 91952.36 28-JUN-18:30
Fans:Electricity:Zone:ROOM_1_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_2_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_5_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_5_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_6_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_6_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_1_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_2_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Electricity:HVAC 2680.85 60425.56 26-MAR-18:00 112799.91 28-JUN-18:30
ExteriorEquipment:Electricity 679.68 10574.27 02-JAN-02:20 40537.60 02-JAN-07:20
Transformer:ExteriorEquipment:Electricity 32.92 556.27 02-JAN-02:20 1912.91 02-JAN-21:10
ElectricityPurchased:Facility 10039.01 144844.55 26-OCT-01:50 628839.67 28-JUN-18:10
ElectricityPurchased:Plant 10039.01 144844.55 26-OCT-01:50 628839.67 28-JUN-18:10
Cogeneration:ElectricityPurchased 10039.01 144844.55 26-OCT-01:50 628839.67 28-JUN-18:10
General:Cogeneration:ElectricityPurchased 10039.01 144844.55 26-OCT-01:50 628839.67 28-JUN-18:10
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricityNet:Facility 10039.01 144844.55 26-OCT-01:50 628839.67 28-JUN-18:10
ElectricityNet:Plant 10039.01 144844.55 26-OCT-01:50 628839.67 28-JUN-18:10
Cogeneration:ElectricityNet 10039.01 144844.55 26-OCT-01:50 628839.67 28-JUN-18:10
General:Cogeneration:ElectricityNet 10039.01 144844.55 26-OCT-01:50 628839.67 28-JUN-18:10
General:Fans:Electricity 2057.84 58067.15 14-OCT-05:40 91952.36 28-JUN-18:30
ExteriorLights:Electricity 262.50 0.00 01-JAN-07:30 16690.39 01-JAN-00:10
General:ExteriorLights:Electricity 262.50 0.00 01-JAN-07:30 16690.39 01-JAN-00:10
ElevatorLift:ExteriorEquipment:Electricity 616.11 9046.01 01-JAN-00:10 37691.69 01-JAN-07:10
ElevatorLightsFan:ExteriorEquipment:Electricity 30.65 972.00 01-JAN-00:10 972.00 01-JAN-00:10
HeatRecovery:Electricity 590.10 0.00 02-JAN-16:50 19264.94 01-JAN-00:10
General:HeatRecovery:Electricity 590.10 0.00 02-JAN-16:50 19264.94 01-JAN-00:10
WaterSystems:Electricity 90.78 1087.01 28-JUN-00:10 4739.44 02-JAN-07:10
Water Heater:WaterSystems:Electricity 90.78 1087.01 28-JUN-00:10 4739.44 02-JAN-07:10
Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Boiler Parasitic:Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:Electricity 3046.80 0.00 01-JAN-00:20 324965.30 17-JUN-16:00
General:Cooling:Electricity 3046.80 0.00 01-JAN-00:20 324965.30 17-JUN-16:00
Pumps:Electricity 311.71 243.68 20-FEB-08:30 14664.31 28-JUN-16:50
General:Pumps:Electricity 311.71 243.68 20-FEB-08:30 14664.31 28-JUN-16:50
WIRED_LTG_ELECTRICITY 41.33 0.00 01-JAN-00:10 3276.83 02-JAN-20:20


Annual and Peak Values - Natural Gas

Natural Gas Annual Value [GJ] Natural Gas Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Natural Gas Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
NaturalGas:Facility 5391.46 40837.88 21-JUL-23:10 416869.49 12-FEB-18:00
NaturalGas:Building 1788.84 13361.90 02-JAN-02:10 104248.32 02-JAN-18:10
NaturalGas:Zone:LAUNDRY_FLR_1 590.20 8363.49 02-JAN-02:10 39726.58 02-JAN-20:10
NaturalGas:SpaceType:GENERAL 1788.84 13361.90 02-JAN-02:10 104248.32 02-JAN-18:10
InteriorEquipment:NaturalGas 1788.84 13361.90 02-JAN-02:10 104248.32 02-JAN-18:10
InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 590.20 8363.49 02-JAN-02:10 39726.58 02-JAN-20:10
InteriorEquipment:NaturalGas:SpaceType:GENERAL 1788.84 13361.90 02-JAN-02:10 104248.32 02-JAN-18:10
Laundry:InteriorEquipment:NaturalGas 590.20 8363.49 02-JAN-02:10 39726.58 02-JAN-20:10
Laundry:InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 590.20 8363.49 02-JAN-02:10 39726.58 02-JAN-20:10
Laundry:InteriorEquipment:NaturalGas:SpaceType:GENERAL 590.20 8363.49 02-JAN-02:10 39726.58 02-JAN-20:10
NaturalGas:Zone:KITCHEN_FLR_6 1198.64 4998.41 01-JAN-00:10 74976.11 01-JAN-16:10
InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 1198.64 4998.41 01-JAN-00:10 74976.11 01-JAN-16:10
Cooking:InteriorEquipment:NaturalGas 1198.64 4998.41 01-JAN-00:10 74976.11 01-JAN-16:10
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 1198.64 4998.41 01-JAN-00:10 74976.11 01-JAN-16:10
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL 1198.64 4998.41 01-JAN-00:10 74976.11 01-JAN-16:10
NaturalGas:Plant 3602.62 18467.44 28-AUG-07:10 329348.15 12-FEB-18:00
WaterSystems:NaturalGas 2755.03 18467.44 06-JAN-00:10 247963.40 23-JAN-21:20
Water Heater:WaterSystems:NaturalGas 2755.03 18467.44 06-JAN-00:10 247963.40 23-JAN-21:20
Heating:NaturalGas 847.59 0.00 03-APR-21:10 110140.86 27-MAR-10:40
Boiler:Heating:NaturalGas 847.59 0.00 03-APR-21:10 110140.86 27-MAR-10:40


Annual and Peak Values - Cooling

Cooling Annual Value [GJ] Cooling Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Cooling Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
PlantLoopCoolingDemand:Facility 8534.64 0.00 01-JAN-00:20 843396.17 13-JUL-18:10
PlantLoopCoolingDemand:HVAC 8534.64 0.00 01-JAN-00:20 843396.17 13-JUL-18:10
CoolingCoils:PlantLoopCoolingDemand 8534.64 0.00 01-JAN-00:20 843396.17 13-JUL-18:10


Annual and Peak Values - Water

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
Water:Facility 9857.19 0.00 02-JAN-01:10 0.00 02-JAN-21:10
Water:Plant 9857.19 0.00 02-JAN-01:10 0.00 02-JAN-21:10
WaterSystems:Water 9857.19 0.00 02-JAN-01:10 0.00 02-JAN-21:10
Water Heater:WaterSystems:Water 5742.51 0.00 02-JAN-01:10 0.00 02-JAN-19:20
MainsWater:Facility 9857.19 0.00 02-JAN-01:10 0.00 02-JAN-21:10
MainsWater:Plant 9857.19 0.00 02-JAN-01:10 0.00 02-JAN-21:10
WaterSystems:MainsWater 9857.19 0.00 02-JAN-01:10 0.00 02-JAN-21:10
Water Heater:WaterSystems:MainsWater 5742.51 0.00 02-JAN-01:10 0.00 02-JAN-19:20
WaterUse:WaterSystems:Water 4114.69 0.00 02-JAN-01:10 0.00 02-JAN-07:10
WaterUse:WaterSystems:MainsWater 4114.69 0.00 02-JAN-01:10 0.00 02-JAN-07:10


Annual and Peak Values - Other by Weight/Mass

Annual Value [kg] Minimum Value [kg/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [kg/s] Timestamp of Maximum {TIMESTAMP}
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10


Annual and Peak Values - Other Volumetric

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [L] Minimum Value [L] Timestamp of Minimum {TIMESTAMP} Maximum Value [L] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other

Annual Value [GJ] Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
EnergyTransfer:Facility 41495.67 243535.27 09-MAR-08:30 3618088.90 13-JUL-18:10
EnergyTransfer:Building 7102.73 95702.15 12-FEB-16:00 438252.75 20-JUL-18:20
EnergyTransfer:Zone:KITCHEN_FLR_6 769.25 11270.52 07-DEC-04:00 36560.54 13-AUG-10:40
Refrigeration:EnergyTransfer 186.11 3683.82 05-DEC-23:30 10357.85 04-AUG-07:00
Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 93.06 1841.91 05-DEC-23:30 5178.92 04-AUG-07:00
General:Refrigeration:EnergyTransfer 93.06 1841.91 05-DEC-23:30 5178.92 04-AUG-07:00
General:Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 93.06 1841.91 05-DEC-23:30 5178.92 04-AUG-07:00
EnergyTransfer:Plant 21877.69 38924.44 15-DEC-23:20 1968895.22 13-JUL-18:10
LowTempRefrigeration:Refrigeration:EnergyTransfer 25.69 0.00 01-JAN-11:10 2686.44 01-JAN-11:40
MedTempRefrigeration:Refrigeration:EnergyTransfer 67.37 1757.28 22-MAY-02:50 2540.19 14-JUL-13:10
EnergyTransfer:Zone:BASEMENT 519.08 7767.52 27-MAR-11:00 25264.43 07-SEP-18:10
Heating:EnergyTransfer 17.94 0.00 01-JAN-12:10 29329.95 07-DEC-05:00
Heating:EnergyTransfer:Zone:BASEMENT 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer 17.94 0.00 01-JAN-12:10 29329.95 07-DEC-05:00
General:Heating:EnergyTransfer:Zone:BASEMENT 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer 6991.74 92813.58 12-FEB-16:00 434493.00 20-JUL-18:20
Cooling:EnergyTransfer:Zone:BASEMENT 519.08 7767.52 27-MAR-11:00 25264.43 07-SEP-18:10
General:Cooling:EnergyTransfer 6991.74 92813.58 12-FEB-16:00 434493.00 20-JUL-18:20
General:Cooling:EnergyTransfer:Zone:BASEMENT 519.08 7767.52 27-MAR-11:00 25264.43 07-SEP-18:10
EnergyTransfer:Zone:RETAIL_1_FLR_1 62.41 0.20 02-JAN-03:40 3904.40 28-JUN-18:10
Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 0.09 0.00 01-JAN-00:10 586.79 16-DEC-07:20
General:Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 0.09 0.00 01-JAN-00:10 586.79 16-DEC-07:20
Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 62.32 0.00 01-JAN-02:50 3904.40 28-JUN-18:10
General:Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 62.32 0.00 01-JAN-02:50 3904.40 28-JUN-18:10
EnergyTransfer:Zone:RETAIL_2_FLR_1 49.33 482.55 12-FEB-16:00 2637.25 28-JUN-18:10
Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 49.33 482.55 12-FEB-16:00 2637.25 28-JUN-18:10
General:Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 49.33 482.55 12-FEB-16:00 2637.25 28-JUN-18:10
EnergyTransfer:Zone:MECH_FLR_1 43.93 0.33 18-DEC-05:50 2922.57 28-JUN-18:10
Heating:EnergyTransfer:Zone:MECH_FLR_1 0.01 0.00 01-JAN-00:10 203.89 07-DEC-05:00
General:Heating:EnergyTransfer:Zone:MECH_FLR_1 0.01 0.00 01-JAN-00:10 203.89 07-DEC-05:00
Cooling:EnergyTransfer:Zone:MECH_FLR_1 43.92 0.00 01-JAN-04:20 2922.57 28-JUN-18:10
General:Cooling:EnergyTransfer:Zone:MECH_FLR_1 43.92 0.00 01-JAN-04:20 2922.57 28-JUN-18:10
EnergyTransfer:Zone:STORAGE_FLR_1 19.81 0.05 09-DEC-03:20 1467.00 28-JUN-18:10
Heating:EnergyTransfer:Zone:STORAGE_FLR_1 0.05 0.00 01-JAN-12:10 196.86 07-DEC-05:00
General:Heating:EnergyTransfer:Zone:STORAGE_FLR_1 0.05 0.00 01-JAN-12:10 196.86 07-DEC-05:00
Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 19.76 0.00 01-JAN-00:10 1467.00 28-JUN-18:10
General:Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 19.76 0.00 01-JAN-00:10 1467.00 28-JUN-18:10
EnergyTransfer:Zone:LAUNDRY_FLR_1 624.25 8968.97 07-DEC-05:00 38927.46 29-JUN-20:00
Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 624.25 8968.97 07-DEC-05:00 38927.46 29-JUN-20:00
General:Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 624.25 8968.97 07-DEC-05:00 38927.46 29-JUN-20:00
EnergyTransfer:Zone:CAFE_FLR_1 319.23 2173.57 19-FEB-14:20 15483.90 28-JUN-18:10
Heating:EnergyTransfer:Zone:CAFE_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:CAFE_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:CAFE_FLR_1 319.23 2173.57 19-FEB-14:20 15483.90 28-JUN-18:10
General:Cooling:EnergyTransfer:Zone:CAFE_FLR_1 319.23 2173.57 19-FEB-14:20 15483.90 28-JUN-18:10
EnergyTransfer:Zone:LOBBY_FLR_1 1039.36 11294.11 12-FEB-16:00 49888.30 28-JUN-18:50
Heating:EnergyTransfer:Zone:LOBBY_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:LOBBY_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 1039.36 11294.11 12-FEB-16:00 49888.30 28-JUN-18:50
General:Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 1039.36 11294.11 12-FEB-16:00 49888.30 28-JUN-18:50
EnergyTransfer:Zone:ROOM_1_FLR_3 95.98 0.04 04-FEB-19:40 13544.24 27-JUN-18:10
Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 2.06 0.00 01-JAN-08:10 2805.73 07-DEC-06:00
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 2.06 0.00 01-JAN-08:10 2805.73 07-DEC-06:00
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 93.93 0.00 01-JAN-00:10 13544.24 27-JUN-18:10
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 93.93 0.00 01-JAN-00:10 13544.24 27-JUN-18:10
EnergyTransfer:Zone:ROOM_2_FLR_3 86.45 0.00 25-NOV-23:50 13811.34 27-JUN-18:10
Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 4.01 0.00 01-JAN-08:10 4232.42 07-DEC-09:10
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 4.01 0.00 01-JAN-08:10 4232.42 07-DEC-09:10
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 82.44 0.00 01-JAN-00:10 13811.34 27-JUN-18:10
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 82.44 0.00 01-JAN-00:10 13811.34 27-JUN-18:10
EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 782.57 5274.41 13-FEB-06:00 60248.35 20-NOV-14:30
Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 782.57 5274.41 13-FEB-06:00 60248.35 20-NOV-14:30
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 782.57 5274.41 13-FEB-06:00 60248.35 20-NOV-14:30
EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 743.79 0.10 30-DEC-04:40 88162.22 27-JUN-18:20
Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 1.66 0.00 01-JAN-00:10 16709.88 07-DEC-16:10
General:Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 1.66 0.00 01-JAN-00:10 16709.88 07-DEC-16:10
Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 742.13 0.00 01-JAN-02:00 88162.22 27-JUN-18:20
General:Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 742.13 0.00 01-JAN-02:00 88162.22 27-JUN-18:20
EnergyTransfer:Zone:ROOM_5_FLR_3 98.80 0.12 22-DEC-02:40 10807.09 29-JUN-08:20
Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 2.08 0.00 01-JAN-08:10 2830.63 07-DEC-06:00
General:Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 2.08 0.00 01-JAN-08:10 2830.63 07-DEC-06:00
Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 96.72 0.00 01-JAN-00:10 10807.09 29-JUN-08:20
General:Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 96.72 0.00 01-JAN-00:10 10807.09 29-JUN-08:20
EnergyTransfer:Zone:ROOM_6_FLR_3 88.79 0.02 13-DEC-20:20 10980.74 19-JUN-08:10
Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 3.83 0.00 01-JAN-08:10 3531.42 07-DEC-05:00
General:Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 3.83 0.00 01-JAN-08:10 3531.42 07-DEC-05:00
Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 84.95 0.00 01-JAN-00:10 10980.74 19-JUN-08:10
General:Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 84.95 0.00 01-JAN-00:10 10980.74 19-JUN-08:10
EnergyTransfer:Zone:CORRIDOR_FLR_3 272.07 55.03 06-DEC-07:10 14762.04 28-JUN-18:10
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 0.00 0.00 01-JAN-00:10 107.28 07-DEC-07:10
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 0.00 0.00 01-JAN-00:10 107.28 07-DEC-07:10
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 272.07 0.00 06-DEC-07:10 14762.04 28-JUN-18:10
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 272.07 0.00 06-DEC-07:10 14762.04 28-JUN-18:10
EnergyTransfer:Zone:ROOM_1_FLR_6 27.08 0.07 20-NOV-05:20 3784.90 27-JUN-18:10
Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 1.06 0.00 01-JAN-08:10 1022.43 07-DEC-06:00
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 1.06 0.00 01-JAN-08:10 1022.43 07-DEC-06:00
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 26.02 0.00 01-JAN-00:10 3784.90 27-JUN-18:10
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 26.02 0.00 01-JAN-00:10 3784.90 27-JUN-18:10
EnergyTransfer:Zone:ROOM_2_FLR_6 24.84 0.02 15-NOV-01:40 3852.17 27-JUN-18:10
Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 1.79 0.00 01-JAN-08:10 1211.77 07-DEC-06:00
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 1.79 0.00 01-JAN-08:10 1211.77 07-DEC-06:00
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 23.05 0.00 01-JAN-00:10 3852.17 27-JUN-18:10
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 23.05 0.00 01-JAN-00:10 3852.17 27-JUN-18:10
EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 160.01 0.01 05-NOV-03:50 18217.01 28-SEP-15:10
Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 0.96 0.00 01-JAN-00:10 2829.45 07-DEC-06:00
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 0.96 0.00 01-JAN-00:10 2829.45 07-DEC-06:00
Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 159.05 0.00 01-JAN-01:40 18217.01 28-SEP-15:10
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 159.05 0.00 01-JAN-01:40 18217.01 28-SEP-15:10
EnergyTransfer:Zone:BANQUET_FLR_6 553.26 8669.52 07-DEC-09:10 25729.00 28-JUN-18:10
Heating:EnergyTransfer:Zone:BANQUET_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:BANQUET_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 553.26 8669.52 07-DEC-09:10 25729.00 28-JUN-18:10
General:Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 553.26 8669.52 07-DEC-09:10 25729.00 28-JUN-18:10
EnergyTransfer:Zone:DINING_FLR_6 589.65 9831.87 07-DEC-09:20 27091.17 28-JUN-18:10
Heating:EnergyTransfer:Zone:DINING_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:DINING_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:DINING_FLR_6 589.65 9831.87 07-DEC-09:20 27091.17 28-JUN-18:10
General:Cooling:EnergyTransfer:Zone:DINING_FLR_6 589.65 9831.87 07-DEC-09:20 27091.17 28-JUN-18:10
Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 676.19 9125.76 07-DEC-04:00 31531.89 18-JUN-10:50
General:Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 676.19 9125.76 07-DEC-04:00 31531.89 18-JUN-10:50
EnergyTransfer:Zone:CORRIDOR_FLR_6 132.79 2.14 05-FEB-03:30 8815.49 28-JUN-18:10
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 0.34 0.00 01-JAN-00:10 1743.91 06-DEC-07:20
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 0.34 0.00 01-JAN-00:10 1743.91 06-DEC-07:20
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 132.45 0.00 01-JAN-01:10 8815.49 28-JUN-18:10
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 132.45 0.00 01-JAN-01:10 8815.49 28-JUN-18:10
PlantLoopHeatingDemand:Facility 1136.50 8872.64 23-JUL-00:30 120099.80 06-DEC-07:10
PlantLoopHeatingDemand:Plant 584.54 6302.63 27-JUL-01:40 46102.31 24-JAN-07:30
WaterSystems:PlantLoopHeatingDemand 584.54 6302.63 27-JUL-01:40 46102.31 24-JAN-07:30
General:WaterSystems:PlantLoopHeatingDemand 584.54 6302.63 27-JUL-01:40 46102.31 24-JAN-07:30
EnergyTransfer:HVAC 12515.25 29094.14 27-JAN-05:40 1305803.31 17-JUN-16:00
HeatingCoils:EnergyTransfer 551.96 0.00 03-APR-21:20 80719.27 27-MAR-10:40
PlantLoopHeatingDemand:HVAC 551.96 0.00 03-APR-21:20 80719.27 27-MAR-10:40
HeatingCoils:PlantLoopHeatingDemand 551.96 0.00 03-APR-21:20 80719.27 27-MAR-10:40
CoolingCoils:EnergyTransfer 8534.64 0.00 01-JAN-00:20 843396.17 13-JUL-18:10
HeatRecoveryForHeating:EnergyTransfer 1035.41 0.00 01-JAN-14:30 499786.65 05-DEC-04:00
HeatRecoveryForCooling:EnergyTransfer 2393.25 0.00 01-JAN-00:10 522949.12 17-JUN-16:00
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
WaterSystems:EnergyTransfer 584.54 6302.63 27-JUL-01:40 46102.31 24-JAN-07:30
WaterUse:WaterSystems:EnergyTransfer 584.54 6302.63 27-JUL-01:40 46102.31 24-JAN-07:30
Boilers:EnergyTransfer 547.32 0.00 03-APR-21:10 84245.66 27-MAR-10:40
Chillers:EnergyTransfer 8802.98 0.00 01-JAN-00:20 853987.34 13-JUL-18:10
HeatRejection:EnergyTransfer 11849.79 0.00 01-JAN-00:20 1090259.35 13-JUL-18:10
General:HeatRejection:EnergyTransfer 11849.79 0.00 01-JAN-00:20 1090259.35 13-JUL-18:10



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2023-10-16 08:58:43

Annual Building Sensible Heat Gain Components

HVAC Zone Eq & Other Sensible Air Heating [GJ] HVAC Zone Eq & Other Sensible Air Cooling [GJ] HVAC Terminal Unit Sensible Air Heating [GJ] HVAC Terminal Unit Sensible Air Cooling [GJ] HVAC Input Heated Surface Heating [GJ] HVAC Input Cooled Surface Cooling [GJ] People Sensible Heat Addition [GJ] Lights Sensible Heat Addition [GJ] Equipment Sensible Heat Addition [GJ] Window Heat Addition [GJ] Interzone Air Transfer Heat Addition [GJ] Infiltration Heat Addition [GJ] Opaque Surface Conduction and Other Heat Addition [GJ] Equipment Sensible Heat Removal [GJ] Window Heat Removal [GJ] Interzone Air Transfer Heat Removal [GJ] Infiltration Heat Removal [GJ] Opaque Surface Conduction and Other Heat Removal [GJ]
BASEMENT 0.000 0.000 0.000 -519.086 0.000 0.000 156.973 165.288 150.255 0.000 0.000 0.000 46.570 0.000 0.000 0.000 0.000 -0.000
RETAIL_1_FLR_1 0.000 0.000 0.090 -62.317 0.000 0.000 16.047 8.404 10.186 28.041 0.000 2.340 5.531 0.000 -6.118 0.000 -2.204 -0.001
RETAIL_2_FLR_1 0.000 0.000 0.000 -49.329 0.000 0.000 18.510 9.732 11.795 0.000 0.000 0.915 9.227 0.000 0.000 0.000 -0.850 -0.000
MECH_FLR_1 0.000 0.000 0.009 -43.921 0.000 0.000 3.939 18.192 12.471 0.000 0.000 2.191 9.112 0.000 0.000 0.000 -1.993 -0.000
STORAGE_FLR_1 0.000 0.000 0.050 -19.759 0.000 0.000 3.037 3.340 3.598 0.000 0.000 1.274 9.610 0.000 0.000 0.000 -1.149 -0.000
LAUNDRY_FLR_1 0.000 0.000 0.000 -624.253 0.000 0.000 12.211 4.125 658.131 0.000 0.000 2.905 0.000 0.000 0.000 0.000 -2.877 -50.243
CAFE_FLR_1 0.000 0.000 0.000 -319.229 0.000 0.000 208.544 26.624 14.341 78.492 0.000 5.092 8.693 0.000 -17.631 0.000 -4.926 -0.000
LOBBY_FLR_1 0.000 0.000 0.000 -1039.368 0.000 0.000 618.052 144.896 148.998 105.139 0.000 14.732 44.769 0.000 -23.080 0.000 -14.139 -0.001
ROOM_1_FLR_3 3.497 -78.486 0.000 -16.881 0.000 0.000 9.657 20.410 12.292 57.851 0.000 5.103 7.018 0.000 -14.535 0.000 -5.925 -0.001
ROOM_2_FLR_3 6.144 -67.942 0.000 -16.631 0.000 0.000 9.684 20.407 12.291 45.285 0.000 5.125 6.181 0.000 -14.802 0.000 -5.741 -0.001
ROOM_3_MULT19_FLR_3 0.000 -506.153 0.000 -276.415 0.000 0.000 0.000 243.708 228.754 323.727 0.000 21.682 114.410 0.000 -93.258 0.000 -56.453 -0.003
ROOM_4_MULT19_FLR_3 6.300 -522.020 0.000 -224.745 0.000 0.000 184.094 243.774 228.817 140.011 0.000 28.480 32.953 0.000 -79.759 0.000 -37.904 -0.007
ROOM_5_FLR_3 3.496 -81.152 0.000 -16.985 0.000 0.000 9.645 20.410 12.292 59.576 0.000 5.091 7.486 0.000 -13.858 0.000 -6.001 -0.000
ROOM_6_FLR_3 5.795 -70.176 0.000 -16.738 0.000 0.000 9.673 20.407 12.291 46.468 0.000 5.108 6.578 0.000 -13.595 0.000 -5.810 -0.002
CORRIDOR_FLR_3 0.000 0.000 0.000 -272.074 0.000 0.000 122.169 62.736 0.000 55.523 0.000 6.168 48.812 0.000 -17.086 0.000 -6.248 -0.001
ROOM_1_FLR_6 1.510 -22.260 0.000 -4.217 0.000 0.000 2.415 5.102 3.073 14.305 0.000 1.267 3.924 0.000 -3.609 0.000 -1.511 -0.000
ROOM_2_FLR_6 2.403 -19.502 0.000 -4.156 0.000 0.000 2.421 5.102 3.073 11.191 0.000 1.271 3.319 0.000 -3.660 0.000 -1.461 -0.000
ROOM_3_MULT9_FLR_6 2.031 -132.792 0.000 -27.336 0.000 0.000 21.690 28.868 27.097 72.315 0.000 5.923 26.772 0.000 -16.712 0.000 -7.856 -0.001
BANQUET_FLR_6 0.000 0.000 0.000 -553.263 0.000 0.000 357.009 46.753 175.857 15.872 0.000 3.099 0.000 0.000 -9.854 0.000 -3.361 -32.114
DINING_FLR_6 0.000 0.000 0.000 -589.649 0.000 0.000 355.864 46.753 175.857 15.525 0.000 3.071 6.127 0.000 -10.166 0.000 -3.381 -0.001
KITCHEN_FLR_6 0.000 0.000 0.000 -676.179 0.000 0.000 30.379 12.482 556.656 27.225 0.000 2.178 58.806 0.000 -8.105 0.000 -3.443 -0.001
CORRIDOR_FLR_6 0.000 0.000 0.340 -132.450 0.000 0.000 32.775 16.599 0.000 26.593 0.000 2.842 63.574 0.000 -7.522 0.000 -2.751 -0.000
Total Facility 31.176 -1500.485 0.490 -5504.979 0.000 0.000 2184.786 1174.112 2458.123 1123.138 0.000 125.857 519.473 0.000 -353.351 0.000 -175.983 -82.376


Peak Cooling Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
BASEMENT 07-SEP-18:10 0.00 0.00 0.00 -25462.48 0.00 0.00 6120.04 12015.03 9581.50 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -2254.09
RETAIL_1_FLR_1 28-JUN-17:09 0.00 0.00 0.00 -4015.51 0.00 0.00 432.58 458.20 505.18 1420.46 0.00 360.03 839.06 0.00 -0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 28-JUN-18:10 0.00 0.00 0.00 -2660.57 0.00 0.00 719.85 707.46 752.15 0.00 0.00 135.91 345.21 0.00 -0.00 0.00 0.00 0.00
MECH_FLR_1 28-JUN-18:10 0.00 0.00 0.00 -2935.04 0.00 0.00 151.31 1322.39 795.27 0.00 0.00 321.22 344.86 0.00 -0.00 0.00 0.00 0.00
STORAGE_FLR_1 28-JUN-17:09 0.00 0.00 0.00 -1483.79 0.00 0.00 83.59 182.07 178.43 0.00 0.00 195.29 844.40 0.00 -0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 29-JUN-20:00 0.00 0.00 0.00 -38927.00 0.00 0.00 427.04 337.37 44299.38 0.00 0.00 311.28 0.00 0.00 -0.00 0.00 0.00 -6448.07
CAFE_FLR_1 28-JUN-17:09 0.00 0.00 0.00 -15773.74 0.00 0.00 5804.57 1451.48 711.25 4046.80 0.00 813.75 2945.88 0.00 -0.00 0.00 0.00 0.00
LOBBY_FLR_1 28-JUN-18:10 0.00 0.00 0.00 -50440.36 0.00 0.00 24432.59 10532.73 9501.36 4542.19 0.00 2229.63 0.00 0.00 -0.00 0.00 0.00 -798.13
ROOM_1_FLR_3 27-JUN-18:02 0.00 -15335.97 0.00 -673.30 0.00 0.00 335.50 1398.11 516.26 7593.90 0.00 721.95 5443.54 0.00 -0.00 0.00 0.00 0.00
ROOM_2_FLR_3 27-JUN-18:02 0.00 -15278.83 0.00 -675.40 0.00 0.00 335.50 1397.95 516.20 8242.15 0.00 720.54 4741.88 0.00 -0.00 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 20-NOV-14:30 0.00 -50484.76 0.00 -9760.33 0.00 0.00 0.00 5252.20 5097.90 56765.71 0.00 845.52 0.00 0.00 -0.00 0.00 0.00 -7716.23
ROOM_4_MULT19_FLR_3 26-JUN-18:02 0.00 -100320.66 0.00 -9259.19 0.00 0.00 6374.71 16699.06 9610.21 23660.77 0.00 3601.22 49633.88 0.00 -0.00 0.00 0.00 0.00
ROOM_5_FLR_3 19-JUN-08:61 0.00 -13539.50 0.00 -676.06 0.00 0.00 87.14 691.20 453.05 8118.47 0.00 366.07 4499.63 0.00 -0.00 0.00 0.00 0.00
ROOM_6_FLR_3 19-JUN-08:61 0.00 -13477.46 0.00 -677.39 0.00 0.00 87.15 691.12 452.99 8311.11 0.00 365.19 4247.30 0.00 -0.00 0.00 0.00 0.00
CORRIDOR_FLR_3 28-JUN-17:09 0.00 0.00 0.00 -14837.85 0.00 0.00 3236.04 3420.27 0.00 4793.74 0.00 984.73 2403.07 0.00 -0.00 0.00 0.00 0.00
ROOM_1_FLR_6 27-JUN-18:02 0.00 -4157.72 0.00 -168.67 0.00 0.00 83.88 349.53 129.07 1881.28 0.00 179.68 1702.96 0.00 -0.00 0.00 0.00 0.00
ROOM_2_FLR_6 27-JUN-18:02 0.00 -4140.42 0.00 -169.24 0.00 0.00 83.88 349.49 129.05 2042.42 0.00 179.30 1525.53 0.00 -0.00 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 06-OCT-15:01 0.00 -18973.46 0.00 -1102.53 0.00 0.00 529.40 622.14 603.86 7529.04 0.00 594.19 10197.35 0.00 -0.00 0.00 0.00 0.00
BANQUET_FLR_6 28-JUN-18:10 0.00 0.00 0.00 -26081.98 0.00 0.00 14028.99 3398.57 6747.90 2960.20 0.00 479.08 0.00 0.00 -0.00 0.00 0.00 -1532.78
DINING_FLR_6 28-JUN-18:10 0.00 0.00 0.00 -27441.07 0.00 0.00 13987.03 3398.57 6747.90 2940.61 0.00 478.02 0.00 0.00 -0.00 0.00 0.00 -111.06
KITCHEN_FLR_6 28-JUN-17:09 0.00 0.00 0.00 -32314.53 0.00 0.00 768.29 680.52 26958.36 1867.30 0.00 402.41 1637.66 0.00 -0.00 0.00 0.00 0.00
CORRIDOR_FLR_6 28-JUN-17:09 0.00 0.00 0.00 -9038.66 0.00 0.00 855.61 904.96 0.00 2031.15 0.00 433.94 4813.00 0.00 -0.00 0.00 0.00 0.00
Total Facility 26-AUG-18:02 0.00 -222281.47 0.00 -252034.97 0.00 0.00 71894.95 82807.27 115371.52 55949.12 0.00 17129.10 131164.49 0.00 0.00 0.00 0.00 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
BASEMENT - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 16-DEC-07:20 0.00 0.00 586.75 0.00 0.00 0.00 448.61 229.10 288.68 0.00 0.00 0.00 0.00 0.00 -1056.03 0.00 -402.09 -95.01
RETAIL_2_FLR_1 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
MECH_FLR_1 07-DEC-05:00 0.00 0.00 203.89 0.00 0.00 0.00 198.07 165.30 176.73 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -417.84 -326.15
STORAGE_FLR_1 07-DEC-05:00 0.00 0.00 196.86 0.00 0.00 0.00 152.81 30.34 50.98 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -240.42 -190.57
LAUNDRY_FLR_1 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CAFE_FLR_1 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
LOBBY_FLR_1 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_3 27-MAR-08:62 6521.32 335.87 0.00 -335.87 0.00 0.00 104.95 691.20 453.05 0.00 0.00 0.00 0.00 0.00 -409.12 0.00 -498.98 -6862.40
ROOM_2_FLR_3 07-DEC-09:02 6734.20 272.62 0.00 -272.62 0.00 0.00 108.88 691.12 452.99 0.00 0.00 0.00 0.00 0.00 -981.48 0.00 -606.90 -6398.82
ROOM_3_MULT19_FLR_3 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 26-FEB-16:03 40753.27 5500.75 0.00 -5500.75 0.00 0.00 2719.24 6191.79 5687.67 0.00 0.00 0.00 0.00 0.00 -1172.98 0.00 -11805.34 -42373.66
ROOM_5_FLR_3 12-FEB-16:02 6074.26 364.60 0.00 -364.60 0.00 0.00 155.26 518.40 305.54 0.00 0.00 0.00 0.00 0.00 -308.35 0.00 -314.62 -6430.49
ROOM_6_FLR_3 07-DEC-16:01 6331.54 350.73 0.00 -350.73 0.00 0.00 279.79 439.80 273.90 0.00 0.00 0.00 0.00 0.00 -647.33 0.00 -631.41 -6046.30
CORRIDOR_FLR_3 07-DEC-07:10 0.00 0.00 107.27 0.00 0.00 0.00 2771.48 2850.23 0.00 0.00 0.00 0.00 0.00 0.00 -3286.91 0.00 -1142.72 -1299.35
ROOM_1_FLR_6 07-DEC-09:02 1947.30 73.29 0.00 -73.29 0.00 0.00 27.05 172.80 113.26 343.37 0.00 0.00 0.00 0.00 -0.00 0.00 -156.00 -2447.80
ROOM_2_FLR_6 07-DEC-09:02 1991.33 69.01 0.00 -69.01 0.00 0.00 27.22 172.78 113.25 0.00 0.00 0.00 0.00 0.00 -236.40 0.00 -153.04 -1915.14
ROOM_3_MULT9_FLR_6 27-MAR-08:62 8984.43 574.52 0.00 -574.52 0.00 0.00 232.73 977.65 998.70 103.78 0.00 0.00 0.00 0.00 -0.00 0.00 -594.94 -10702.34
BANQUET_FLR_6 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
DINING_FLR_6 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
KITCHEN_FLR_6 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6 06-DEC-07:20 0.00 0.00 1743.76 0.00 0.00 0.00 735.08 754.13 0.00 0.00 0.00 0.00 0.00 0.00 -911.77 0.00 -543.07 -1778.14
Total Facility 07-DEC-09:02 -58481.55 116285.59 488.37 -116285.59 0.00 0.00 24617.97 41166.03 88631.48 70881.40 0.00 0.00 0.00 0.00 -8978.87 0.00 -17457.24 -140867.59



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2023-10-16 08:58:43

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow - Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
VAV WITH REHEAT 24.7747 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 24.6594 0.0000 1.0000 Not calculated 0.0000 0.0000    
FLR_3_DOAS 2.0513 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 2.0513 0.0000 1.0000 Not calculated 0.0000 0.0000    


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
VAV WITH REHEAT 24.6508 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 24.6508 0.0000 1.0000 Not calculated 0.0000 0.0000    
FLR_3_DOAS 2.0513 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 2.0513 0.0000 1.0000 Not calculated 0.0000 0.0000    


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [m3/s-person] Zone Population - Pz Area Outdoor Air Rate - Ra [m3/s-m2] Zone Floor Area - Az [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [m3/s]
BASEMENT VAV WITH REHEAT 0.000000 106.4990 0.000432 1978.83 0.0000 1.0000 0.0000 1.000 0.0000
RETAIL_1_FLR_1 VAV WITH REHEAT 0.000000 10.8290 0.001181 67.07 0.0000 1.0000 0.0000 1.000 0.0000
RETAIL_2_FLR_1 VAV WITH REHEAT 0.000000 12.5400 0.001181 77.67 0.0000 1.0000 0.0000 1.000 0.0000
MECH_FLR_1 VAV WITH REHEAT 0.000000 2.6520 0.000000 164.24 0.0000 1.0000 0.0000 1.000 0.0000
STORAGE_FLR_1 VAV WITH REHEAT 0.000000 2.0400 0.000610 94.76 0.0000 1.0000 0.0000 1.000 0.0000
LAUNDRY_FLR_1 VAV WITH REHEAT 0.000000 8.4000 0.000000 78.04 0.0000 1.0000 0.0000 1.000 0.0000
CAFE_FLR_1 VAV WITH REHEAT 0.000000 142.3000 0.003581 188.86 0.0000 1.0000 0.0000 1.000 0.0000
LOBBY_FLR_1 VAV WITH REHEAT 0.000000 422.4350 0.001448 1308.19 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_1_FLR_3 FLR_3_DOAS 0.000000 6.0000 0.000396 156.09 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_2_FLR_3 FLR_3_DOAS 0.000000 6.0000 0.000396 156.07 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_3_MULT19_FLR_3 FLR_3_DOAS 0.000000 114.0000 0.000449 1863.81 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_4_MULT19_FLR_3 FLR_3_DOAS 0.000000 114.0000 0.000449 1864.32 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_5_FLR_3 FLR_3_DOAS 0.000000 6.0000 0.000396 156.09 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_6_FLR_3 FLR_3_DOAS 0.000000 6.0000 0.000396 156.07 0.0000 1.0000 0.0000 1.000 0.0000
CORRIDOR_FLR_3 VAV WITH REHEAT 0.000000 83.8280 0.000305 1557.62 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_1_FLR_6 FLR_3_DOAS 0.000000 1.5000 0.000396 39.02 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_2_FLR_6 FLR_3_DOAS 0.000000 1.5000 0.000396 39.02 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_3_MULT9_FLR_6 FLR_3_DOAS 0.000000 13.5000 0.000449 220.77 0.0000 1.0000 0.0000 1.000 0.0000
BANQUET_FLR_6 VAV WITH REHEAT 0.000000 249.8960 0.003581 331.66 0.0000 1.0000 0.0000 1.000 0.0000
DINING_FLR_6 VAV WITH REHEAT 0.000000 249.8960 0.003581 331.66 0.0000 1.0000 0.0000 1.000 0.0000
KITCHEN_FLR_6 VAV WITH REHEAT 0.000000 22.2380 0.003556 103.30 0.0000 1.0000 0.0000 1.000 0.0000
CORRIDOR_FLR_6 VAV WITH REHEAT 0.000000 22.1800 0.000305 412.12 0.0000 1.0000 0.0000 1.000 0.0000


System Ventilation Parameters

People Outdoor Air Rate - Rp [m3/s-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [m3/s-m2] Sum of Zone Floor Area - Az-sum [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Outdoor Airflow - Voz-htg [m3/s]
VAV WITH REHEAT   0.00 0.001045 6694.0231 0.0000 0.0000 0.0000
FLR_3_DOAS   0.00 0.000441 4651.2638 0.0000 0.0000 0.0000


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
BASEMENT VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.8736 2.8736 2.8592 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
RETAIL_1_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.3993 0.3993 0.3973 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
RETAIL_2_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.2830 0.2830 0.2815 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
MECH_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.3122 0.3122 0.3106 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
STORAGE_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1582 0.1582 0.1574 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LAUNDRY_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 3.6436 3.6436 3.6254 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CAFE_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.6489 1.6489 1.6407 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LOBBY_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 5.3941 5.3941 5.3671 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_1_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_2_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_3_MULT19_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.8371 0.8371 0.8371 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_4_MULT19_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.8373 0.8373 0.8373 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_5_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_6_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORRIDOR_FLR_3 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.4018 1.4018 1.3948 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_1_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0154 0.0154 0.0154 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_2_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0154 0.0154 0.0154 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_3_MULT9_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0992 0.0992 0.0992 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
BANQUET_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.5675 2.5675 2.5546 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DINING_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.6893 2.6893 2.6759 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
KITCHEN_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.5506 2.5506 2.5378 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORRIDOR_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.8528 0.8528 0.8485 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Zone Ventilation Efficiency - Evz-min
VAV WITH REHEAT 24.7747 24.6594 24.7747 24.6508 0.0000 1.0000
FLR_3_DOAS 2.0513 2.0513 2.0513 2.0513 0.0000 1.0000


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Heating - Voz-htg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
BASEMENT VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.8592 2.8592 2.8592 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
RETAIL_1_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.3973 0.3973 0.3973 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
RETAIL_2_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.2815 0.2815 0.2815 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
MECH_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.3106 0.3106 0.3106 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
STORAGE_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1574 0.1574 0.1574 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LAUNDRY_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 3.6254 3.6254 3.6254 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CAFE_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.6407 1.6407 1.6407 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LOBBY_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 5.3671 5.3671 5.3671 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_1_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_2_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_3_MULT19_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.8371 0.8371 0.8371 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_4_MULT19_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.8373 0.8373 0.8373 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_5_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_6_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORRIDOR_FLR_3 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.3948 1.3948 1.3948 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_1_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0154 0.0154 0.0154 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_2_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0154 0.0154 0.0154 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_3_MULT9_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0992 0.0992 0.0992 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
BANQUET_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.5546 2.5546 2.5546 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DINING_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.6759 2.6759 2.6759 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
KITCHEN_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.5378 2.5378 2.5378 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORRIDOR_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.8485 0.8485 0.8485 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Zone Ventilation Efficiency - Evz-min
VAV WITH REHEAT 24.6508 24.6508 24.6508 24.6508 0.0000 1.0000
FLR_3_DOAS 2.0513 2.0513 2.0513 2.0513 0.0000 1.0000



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2023-10-16 08:58:43

Sec1.1A-General Information

Data
Weather File RUNPERIOD 1 ** Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745
Total gross floor area [m2] 11345.29
Principal Heating Source Natural Gas


EAp2-1. Space Usage Type

Space Area [m2] Regularly Occupied Area [m2] Unconditioned Area [m2] Typical Hours/Week in Operation [hr/wk]
BASEMENT 1978.83 1978.83 0.00 168.00
RETAIL_1_FLR_1 67.07 67.07 0.00 168.00
RETAIL_2_FLR_1 77.67 77.67 0.00 168.00
MECH_FLR_1 164.24 164.24 0.00 168.00
STORAGE_FLR_1 94.76 94.76 0.00 168.00
LAUNDRY_FLR_1 78.04 78.04 0.00 168.00
CAFE_FLR_1 188.86 188.86 0.00 168.00
LOBBY_FLR_1 1308.19 1308.19 0.00 168.00
ROOM_1_FLR_3 39.02 39.02 0.00 168.00
ROOM_2_FLR_3 39.02 39.02 0.00 168.00
ROOM_3_MULT19_FLR_3 24.52 24.52 0.00 0.00
ROOM_4_MULT19_FLR_3 24.53 24.53 0.00 168.00
ROOM_5_FLR_3 39.02 39.02 0.00 168.00
ROOM_6_FLR_3 39.02 39.02 0.00 168.00
CORRIDOR_FLR_3 389.40 389.40 0.00 168.00
ROOM_1_FLR_6 39.02 39.02 0.00 168.00
ROOM_2_FLR_6 39.02 39.02 0.00 168.00
ROOM_3_MULT9_FLR_6 24.53 24.53 0.00 168.00
BANQUET_FLR_6 331.66 331.66 0.00 168.00
DINING_FLR_6 331.66 331.66 0.00 168.00
KITCHEN_FLR_6 103.30 103.30 0.00 168.00
CORRIDOR_FLR_6 412.12 412.12 0.00 168.00
Totals 11345.29 11345.29 0.00  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 0.00
Number of hours cooling loads not met 26.17
Number of hours not met 26.17


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electricity Energy Use [GJ] Electricity Demand [W] Natural Gas Energy Use [GJ] Natural Gas Demand [W] Gasoline Use [GJ] Gasoline Demand [W] Diesel Use [GJ] Diesel Demand [W] Coal Use [GJ] Coal Demand [W] Fuel Oil No 1 Use [GJ] Fuel Oil No 1 Demand [W] Fuel Oil No 2 Use [GJ] Fuel Oil No 2 Demand [W] Propane Use [GJ] Propane Demand [W] Other Fuel 1 Use [GJ] Other Fuel 1 Demand [W] Other Fuel 2 Use [GJ] Other Fuel 2 Demand [W] District Cooling Use [GJ] District Cooling Demand [W] District Heating Use [GJ] District Heating Demand [W]
Heating -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heating -- Boiler 0.00 0.00 847.59 110140.86 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heating -- Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling -- General 3046.80 324965.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting -- LightsWired 1174.11 93091.76 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting -- General 262.50 16690.39 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- MiscPlug 959.56 59492.27 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- Cooking 762.04 29240.64 1198.64 74976.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- ReachInFreezer 16.27 515.92 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- ReachInRefrigerator 13.43 425.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- Laundry 0.00 0.00 590.20 39726.58 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- Transformer 32.92 1912.91 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- ElevatorLift 616.11 37691.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- ElevatorLightsFan 30.65 972.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- General 2057.84 91952.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps -- General 311.71 14664.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery -- General 590.10 19264.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- Water Heater 90.78 4739.44 2755.03 247963.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- General 18.27 2271.91 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- LowTempRefrigeration 22.43 1889.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- MedTempRefrigeration 33.49 1196.73 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


EAp2-6. Energy Use Summary

Process Subtotal [GJ] Total Energy Use [GJ]
Electricity 1825.49 10039.01
Natural Gas 1788.84 5391.46
Additional 0.00 0.00
Total 3614.33 15430.47


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [GJ]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [MJ/m2]
Interior Lighting (All) 103.49
Space Heating 0.00
Space Cooling 268.55
Fans (All) 181.38
Service Water Heating 8.00
Receptacle Equipment 154.36
Miscellaneous (All) 884.86
Subtotal 884.86


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [MJ/m2]
Space Heating 74.71
Service Water Heating 242.83
Miscellaneous (All) 475.22
Subtotal 475.22


EAp2-17c. Energy Use Intensity - Additional

Additional [MJ/m2]
Subtotal 0.00
Miscellaneous 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting (All) 7.61
Space Heating 5.49
Space Cooling 19.75
Fans (All) 13.34
Service Water Heating 18.44
Receptacle Equipment 22.94
Miscellaneous 12.43


Schedules-Equivalent Full Load Hours (Schedule Type=Fraction)

Equivalent Full Load Hours of Operation Per Year [hr] Hours > 1% [hr]
LTG_SCH_KITCHEN 3061. 8760.
LTG_SCH_DINING 3061. 8760.
LTG_SCH_BASEMENT 2655. 8760.
LTG_SCH_LOBBY 3061. 8760.
LTG_SCH_STORAGE 1339. 8760.
LTG_SCH_MECHANIC 3061. 8760.
LTG_SCH_LAUNDRY 2678. 8760.
LTG_SCH_GUESTROOM 3599. 8760.
LTG_SCH_CORRIDOR 3061. 8760.
LTG_SCH_RETAIL 2678. 8760.
WALKIN_OCC_LGHT_SCH_1 3061. 8760.
EXTERIOR_LTG_SCH 4380. 4380.
BASEMENT_EQUIP_SCH 3924. 8760.
BLDG_EQUIP_SCH 3924. 8760.
GUESTROOM_EQP_SCH_BASE 3239. 8760.
GUESTROOM_EQP_SCH_ADVA 2762. 8760.
LOBBY_EQP_SCH 3292. 8760.
OFFICE_EQP_SCH 4941. 8760.
EMPLOYEELOUNGE_EQP_SCH 4044. 8760.
LAUNDRYROOM_EQP_ELEC_SCH 2920. 2920.
LAUNDRYROOM_EQP_GAS_SCH 2920. 2920.
MEETINGROOM_EQP_SCH 1336. 4745.
EXERCISEROOM_EQP_SCH 3832. 5840.
KITCHEN_ELEC_EQUIP_SCH 2172. 8760.
KITCHEN_GAS_EQUIP_SCH 1332. 8760.
KITCHEN_EXHAUST_SCH 6205. 6205.
BLDG_ELEVATORS 2270. 8760.
ELEV_LIGHT_FAN_SCH_24_7 8760. 8760.
ELEV_LIGHT_FAN_SCH_ADD_DF 2154. 8760.
BLDG_OCC_SCH 5026. 8760.
GUESTROOM_OCC_SCH 5515. 8760.
LOBBY_OCC_SCH 2304. 8760.
OFFICE_OCC_SCH 3954. 8760.
EMPLOYEELOUNGE_OCC_SCH 948. 5475.
MEETINGROOM_OCC_SCH 1168. 4745.
LAUNDRYROOM_OCC_SCH 427. 2920.
EXERCISEROOM_OCC_SCH 5292. 5840.
INFIL_SCH 8760. 8760.
INFIL_HALF_ON_SCH 4380. 8760.
INFIL_QUARTER_ON_SCH 2190. 8760.
LAUNDRY_SWH_SCH 2555. 2555.
BLDG_SWH_SCH 3301. 8760.
GUESTROOM_SWH_SCH 2899. 8760.
LAUNDRYROOM_SWH_SCH 2920. 2920.
EXTERIOR_LGT_ALWAYS_ON 8760. 8760.
ALWAYS_ON 8760. 8760.
ALWAYS_OFF 0. 0.
FAN_SCH 8760. 8760.
REHEATCOILAVAILSCHED 8760. 8760.
COOLINGCOILAVAILSCHED 8760. 8760.
OCC_GUESTROOM_VENT_CTRL_30MIN 6570. 6570.
OCC_GUESTROOM_VENT_CTRL_20MIN 6327. 6327.
VAC_GUESTROOM_VENTILATION_SCHEDULE 365. 365.
MINOA_MOTORIZEDDAMPER_SCHED 8760. 8760.
MINOA_SCHED 8760. 8760.
WORK_EFF_SCH 0. 0.
ROOM_1_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_1_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_2_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_2_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_5_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_5_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_6_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_6_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_1_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_1_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_2_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_2_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
KITCHEN_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
KITCHEN_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
KITCHEN_FLR_6_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED 2774. 8760.
FLR_3_DOAS_OAMINOAFRACSCHEDULE 8760. 8760.
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE 0. 0.
LAUNDRY_FLR_1 EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE 0. 0.
SLIDING_DOORS_VENTILATION_AVAILABILITY_SCH 3285. 3285.


Schedules-SetPoints (Schedule Type=Temperature)

First Object Used Month Assumed 11am First Wednesday [C] Days with Same 11am Value 11pm First Wednesday [C] Days with Same 11pm Value
VACGUESTROOM_HTGSP_SCH VACGUESTROOM THERMOSTAT DUAL SP CONTROL January 18.89 365 18.89 365
VACGUESTROOM_CLGSP_SCH VACGUESTROOM THERMOSTAT DUAL SP CONTROL July 23.33 365 23.33 365
OBCRESET_S_OCCGUESTROOM_HTGSP_SCH_30MIN S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL January 21.11 365 21.11 365
OBCRESET_S_OCCGUESTROOM_CLGSP_SCH_30MIN S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL July 23.33 365 21.11 365
OBCRESET_N_OCCGUESTROOM_HTGSP_SCH_30MIN N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL January 21.11 365 21.11 365
OBCRESET_N_OCCGUESTROOM_CLGSP_SCH_30MIN N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL July 23.33 365 21.11 365
HTGSETP_SCH BASEMENT DUAL SP CONTROL January 21.00 365 21.00 365
CLGSETP_SCH BASEMENT DUAL SP CONTROL July 24.00 365 24.00 365



Table of Contents

Report: Annual Thermal Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 08:58:43

Heat Index Hours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
BASEMENT 8760.00 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 8760.00 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 8760.00 0.00 0.00 0.00 0.00
MECH_FLR_1 8760.00 0.00 0.00 0.00 0.00
STORAGE_FLR_1 8760.00 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 8760.00 0.00 0.00 0.00 0.00
CAFE_FLR_1 8760.00 0.00 0.00 0.00 0.00
LOBBY_FLR_1 8760.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_5_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_6_FLR_3 8760.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 8760.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_6 8760.00 0.00 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 8760.00 0.00 0.00 0.00 0.00
BANQUET_FLR_6 8760.00 0.00 0.00 0.00 0.00
DINING_FLR_6 8760.00 0.00 0.00 0.00 0.00
KITCHEN_FLR_6 8760.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6 8760.00 0.00 0.00 0.00 0.00
Min 8760.00 0.00 0.00 0.00 0.00
Max 8760.00 0.00 0.00 0.00 0.00
Average 8760.00 0.00 0.00 0.00 0.00
Sum 192720.00 0.00 0.00 0.00 0.00


Heat Index OccupantHours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
BASEMENT 529331.00 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 50179.00 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 59156.00 0.00 0.00 0.00 0.00
MECH_FLR_1 8977.00 0.00 0.00 0.00 0.00
STORAGE_FLR_1 5588.00 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 37203.00 0.00 0.00 0.00 0.00
CAFE_FLR_1 710417.00 0.00 0.00 0.00 0.00
LOBBY_FLR_1 2115429.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 0.00 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_5_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_6_FLR_3 4154.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3 100358.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 4154.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_6 4154.00 0.00 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 4154.00 0.00 0.00 0.00 0.00
BANQUET_FLR_6 1245715.00 0.00 0.00 0.00 0.00
DINING_FLR_6 1245715.00 0.00 0.00 0.00 0.00
KITCHEN_FLR_6 108269.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6 105946.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 2115429.00 0.00 0.00 0.00 0.00
Average 288887.05 0.00 0.00 0.00 0.00
Sum 6355515.00 0.00 0.00 0.00 0.00


Humidex Hours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
BASEMENT 8760.00 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 8760.00 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 8760.00 0.00 0.00 0.00 0.00
MECH_FLR_1 8760.00 0.00 0.00 0.00 0.00
STORAGE_FLR_1 8760.00 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 8760.00 0.00 0.00 0.00 0.00
CAFE_FLR_1 8760.00 0.00 0.00 0.00 0.00
LOBBY_FLR_1 8760.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_5_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_6_FLR_3 8760.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 8760.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_6 8760.00 0.00 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 8760.00 0.00 0.00 0.00 0.00
BANQUET_FLR_6 8760.00 0.00 0.00 0.00 0.00
DINING_FLR_6 8760.00 0.00 0.00 0.00 0.00
KITCHEN_FLR_6 8760.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6 8760.00 0.00 0.00 0.00 0.00
Min 8760.00 0.00 0.00 0.00 0.00
Max 8760.00 0.00 0.00 0.00 0.00
Average 8760.00 0.00 0.00 0.00 0.00
Sum 192720.00 0.00 0.00 0.00 0.00


Humidex OccupantHours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
BASEMENT 529331.00 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 50179.00 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 59156.00 0.00 0.00 0.00 0.00
MECH_FLR_1 8977.00 0.00 0.00 0.00 0.00
STORAGE_FLR_1 5588.00 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 37203.00 0.00 0.00 0.00 0.00
CAFE_FLR_1 710417.00 0.00 0.00 0.00 0.00
LOBBY_FLR_1 2115429.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 0.00 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_5_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_6_FLR_3 4154.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3 100358.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 4154.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_6 4154.00 0.00 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 4154.00 0.00 0.00 0.00 0.00
BANQUET_FLR_6 1245715.00 0.00 0.00 0.00 0.00
DINING_FLR_6 1245715.00 0.00 0.00 0.00 0.00
KITCHEN_FLR_6 108269.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6 105946.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 2115429.00 0.00 0.00 0.00 0.00
Average 288887.05 0.00 0.00 0.00 0.00
Sum 6355515.00 0.00 0.00 0.00 0.00


Heating SET Hours

SET ≤ 12.2°C Hours (°C) SET ≤ 12.2°C OccupantHours (°C) Longest SET ≤ 12.2°C Duration [hr] Start Time of the Longest SET ≤ 12.2°C Duration
None        


Cooling SET Hours

SET > 30°C Hours (°C) SET > 30°C OccupantHours (°C) Longest SET > 30°C Duration [hr] Start Time of the Longest SET > 30°C Duration
None        



Table of Contents

Report: Annual CO2 Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 08:58:43

CO2 Level Hours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      


CO2 Level OccupantHours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      



Table of Contents

Report: Annual Visual Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 08:58:43

Illuminance Level Hours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
None        


Illuminance Level OccupantHours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
None        



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR

For: Environment

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 14.827
February 12.716
March 15.425
April 23.310
May 26.312
June 31.196
July 30.423
August 29.815
September 27.754
October 20.869
November 15.431
December 11.863
   
Annual Sum or Average 21.705
Minimum of Months 11.863
Maximum of Months 31.196



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC

For: Environment

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 14.827
February 12.716
March 15.425
April 23.310
May 26.312
June 31.196
July 30.423
August 29.815
September 27.754
October 20.869
November 15.431
December 11.863
   
Annual Sum or Average 21.705
Minimum of Months 11.863
Maximum of Months 31.196



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2012

For: Environment

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 14.827
February 12.716
March 15.425
April 23.310
May 26.312
June 31.196
July 30.423
August 29.815
September 27.754
October 20.869
November 15.431
December 11.863
   
Annual Sum or Average 21.705
Minimum of Months 11.863
Maximum of Months 31.196



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

For: Environment

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 14.827
February 12.716
March 15.425
April 23.310
May 26.312
June 31.196
July 30.423
August 29.815
September 27.754
October 20.869
November 15.431
December 11.863
   
Annual Sum or Average 21.705
Minimum of Months 11.863
Maximum of Months 31.196



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE

For: Environment

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 14.827
February 12.716
March 15.425
April 23.310
May 26.312
June 31.196
July 30.423
August 29.815
September 27.754
October 20.869
November 15.431
December 11.863
   
Annual Sum or Average 21.705
Minimum of Months 11.863
Maximum of Months 31.196



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

For: Environment

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 14.827
February 12.716
March 15.425
April 23.310
May 26.312
June 31.196
July 30.423
August 29.815
September 27.754
October 20.869
November 15.431
December 11.863
   
Annual Sum or Average 21.705
Minimum of Months 11.863
Maximum of Months 31.196



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

For: Environment

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 14.827
February 12.716
March 15.425
April 23.310
May 26.312
June 31.196
July 30.423
August 29.815
September 27.754
October 20.869
November 15.431
December 11.863
   
Annual Sum or Average 21.705
Minimum of Months 11.863
Maximum of Months 31.196



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 2B

For: Environment

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 14.827
February 12.716
March 15.425
April 23.310
May 26.312
June 31.196
July 30.423
August 29.815
September 27.754
October 20.869
November 15.431
December 11.863
   
Annual Sum or Average 21.705
Minimum of Months 11.863
Maximum of Months 31.196



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_AZ_TUCSON

For: Environment

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 14.827
February 12.716
March 15.425
April 23.310
May 26.312
June 31.196
July 30.423
August 29.815
September 27.754
October 20.869
November 15.431
December 11.863
   
Annual Sum or Average 21.705
Minimum of Months 11.863
Maximum of Months 31.196



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.432115E+11 20832.38 19-JAN-19:10 19.75 8.45 0.617989E+10 3824.94 20-JAN-22:10 12.93 10.23
February 0.336843E+11 19838.18 01-FEB-21:00 11.00 5.83 0.554047E+10 3775.81 01-FEB-22:10 9.67 5.16
March 0.335814E+11 19880.00 16-MAR-19:30 23.00 12.60 0.613261E+10 3694.38 01-MAR-22:10 23.00 12.60
April 0.356539E+11 21387.37 13-APR-19:40 29.67 12.13 0.591862E+10 3695.46 07-APR-21:19 29.67 12.13
May 0.348414E+11 20645.00 25-MAY-20:00 29.00 12.55 0.609861E+10 3660.95 01-MAY-22:10 29.00 12.55
June 0.367696E+11 21916.23 22-JUN-20:00 34.00 15.31 0.591840E+10 3694.12 09-JUN-22:10 34.00 15.31
July 0.461072E+11 24331.59 20-JUL-18:30 38.00 19.12 0.618306E+10 3828.73 28-JUL-22:10 24.00 19.60
August 0.495277E+11 24902.88 14-AUG-18:10 37.83 18.84 0.630597E+10 3893.09 25-AUG-22:10 28.83 11.92
September 0.523482E+11 25462.54 07-SEP-18:10 35.82 19.33 0.628050E+10 4043.39 21-SEP-22:10 20.92 16.58
October 0.529465E+11 24701.30 04-OCT-18:10 32.67 17.42 0.653469E+10 4093.22 27-OCT-21:10 14.00 7.22
November 0.503245E+11 23559.40 01-NOV-18:10 23.67 14.38 0.634240E+10 4075.52 24-NOV-22:10 11.83 5.35
December 0.500881E+11 22077.04 01-DEC-21:00 11.00 4.29 0.645330E+10 4053.22 01-DEC-22:10 10.00 4.18
                     
Annual Sum or Average 0.519084E+12         0.738885E+11        
Minimum of Months 0.335814E+11 19838.18   11.00 4.29 0.554047E+10 3660.95   9.67 4.18
Maximum of Months 0.529465E+11 25462.54   38.00 19.33 0.653469E+10 4093.22   34.00 19.60



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.451635E+10 3431.88 29-JAN-11:35 21.33 8.67 0.629720E+09 364.26 02-JAN-03:39 21.33 8.67
February 0.259467E+10 3063.03 26-FEB-11:35 15.33 10.16 0.561578E+09 364.29 21-FEB-03:00 15.33 10.16
March 0.335588E+10 3119.62 18-MAR-15:15 27.20 12.06 0.623684E+09 364.78 16-MAR-21:19 27.20 12.06
April 0.544266E+10 3460.60 14-APR-15:15 35.00 14.57 0.607686E+09 400.25 14-APR-21:30 28.00 12.96
May 0.586897E+10 3399.54 31-MAY-18:10 35.67 13.49 0.625780E+09 389.38 09-MAY-21:40 35.67 13.49
June 0.689925E+10 4015.68 28-JUN-17:09 41.83 19.10 0.622009E+09 419.95 29-JUN-22:10 33.83 15.97
July 0.690610E+10 3711.05 20-JUL-18:10 38.67 19.18 0.633658E+09 413.00 21-JUL-22:10 32.83 20.17
August 0.694633E+10 3829.85 28-AUG-10:35 35.33 21.21 0.640870E+09 414.34 15-AUG-21:40 35.33 21.21
September 0.654919E+10 3799.74 28-SEP-15:15 37.33 15.40 0.617357E+09 417.06 07-SEP-21:40 37.33 15.40
October 0.552145E+10 3785.99 06-OCT-10:35 31.33 15.60 0.633064E+09 399.45 06-OCT-21:30 26.00 13.58
November 0.422698E+10 3704.27 20-NOV-11:35 25.00 11.54 0.606901E+09 373.37 01-NOV-21:19 25.00 11.54
December 0.348883E+10 3513.64 25-DEC-11:35 22.33 10.13 0.625375E+09 364.25 08-DEC-05:30 22.33 10.13
                     
Annual Sum or Average 0.623167E+11         0.742768E+10        
Minimum of Months 0.259467E+10 3063.03   15.33 8.67 0.561578E+09 364.25   15.33 8.67
Maximum of Months 0.694633E+10 4015.68   41.83 21.21 0.640870E+09 419.95   37.33 21.21



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.358953E+10 2019.88 19-JAN-19:03 19.75 8.45 0.722332E+09 448.50 31-JAN-22:19 14.27 4.94
February 0.285109E+10 1934.07 28-FEB-21:00 13.00 8.69 0.650591E+09 441.73 28-FEB-22:10 12.55 9.16
March 0.345186E+10 2160.70 16-MAR-18:10 25.22 13.24 0.725639E+09 455.59 17-MAR-21:40 20.87 12.09
April 0.429731E+10 2389.00 13-APR-18:10 32.67 13.82 0.714131E+09 481.49 14-APR-22:10 26.83 12.60
May 0.464441E+10 2437.05 31-MAY-18:10 35.67 13.49 0.743846E+09 478.30 19-MAY-22:10 35.67 13.49
June 0.498985E+10 2660.74 28-JUN-18:10 40.83 17.83 0.739051E+09 497.03 30-JUN-22:10 32.32 14.76
July 0.496983E+10 2551.13 20-JUL-18:10 38.67 19.18 0.750998E+09 488.05 21-JUL-22:10 32.83 20.17
August 0.495662E+10 2529.36 14-AUG-18:10 37.83 18.84 0.754370E+09 490.88 15-AUG-22:10 30.83 16.85
September 0.464662E+10 2505.41 07-SEP-18:10 35.82 19.33 0.721243E+09 488.60 08-SEP-22:10 29.22 19.02
October 0.418684E+10 2380.28 04-OCT-18:10 32.67 17.42 0.731933E+09 477.85 06-OCT-22:10 26.00 14.45
November 0.354652E+10 2181.91 01-NOV-18:10 23.67 14.38 0.699425E+09 460.50 01-NOV-21:19 18.00 13.11
December 0.319793E+10 1975.03 22-DEC-21:00 14.00 5.51 0.719466E+09 445.69 26-DEC-22:19 14.67 7.12
                     
Annual Sum or Average 0.493284E+11         0.867303E+10        
Minimum of Months 0.285109E+10 1934.07   13.00 5.51 0.650591E+09 441.73   12.55 4.94
Maximum of Months 0.498985E+10 2660.74   40.83 19.33 0.754370E+09 497.03   35.67 20.17



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.218407E+10 1930.17 27-JAN-21:00 17.00 6.99 0.151697E+09 89.15 24-JAN-05:49 17.00 6.99
February 0.169242E+10 1735.07 16-FEB-21:00 14.00 12.80 0.137151E+09 89.16 01-FEB-04:10 14.00 12.80
March 0.240670E+10 2175.36 16-MAR-19:10 23.53 12.61 0.152447E+09 91.02 17-MAR-21:10 21.42 12.50
April 0.390148E+10 2486.49 13-APR-18:20 32.33 13.74 0.147854E+09 95.12 25-APR-21:19 26.67 13.95
May 0.473730E+10 2636.70 31-MAY-18:03 35.67 13.49 0.153888E+09 96.14 31-MAY-22:10 27.83 10.97
June 0.558835E+10 2935.25 28-JUN-18:10 40.83 17.83 0.153583E+09 102.37 30-JUN-22:10 32.32 14.76
July 0.559525E+10 2829.51 22-JUL-10:35 35.67 19.48 0.156729E+09 100.49 21-JUL-22:10 35.67 19.48
August 0.535990E+10 2751.92 14-AUG-18:10 37.83 18.84 0.156114E+09 99.02 15-AUG-22:10 30.83 16.85
September 0.487562E+10 2686.88 07-SEP-18:10 35.82 19.33 0.149326E+09 97.78 08-SEP-22:10 29.22 19.02
October 0.358543E+10 2585.01 02-OCT-18:10 32.50 19.26 0.152388E+09 95.85 03-OCT-21:40 28.00 18.15
November 0.237036E+10 2178.47 01-NOV-19:10 21.83 14.03 0.146764E+09 90.92 02-NOV-21:10 20.00 15.60
December 0.162380E+10 1744.35 22-DEC-21:00 14.00 5.51 0.151692E+09 89.15 07-DEC-02:00 14.00 5.51
                     
Annual Sum or Average 0.439207E+11         0.180963E+10        
Minimum of Months 0.162380E+10 1735.07   14.00 5.51 0.137151E+09 89.15   14.00 5.51
Maximum of Months 0.559525E+10 2935.25   40.83 19.48 0.156729E+09 102.37   35.67 19.48



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.775711E+09 676.66 27-JAN-20:50 17.33 7.11 0.116690E+09 68.58 02-JAN-04:49 17.33 7.11
February 0.519864E+09 568.01 22-FEB-21:50 13.00 10.72 0.105501E+09 68.58 01-FEB-04:19 13.00 10.72
March 0.887609E+09 897.17 17-MAR-21:00 21.60 12.64 0.117239E+09 68.58 24-MAR-21:40 11.97 4.05
April 0.178529E+10 1149.68 13-APR-20:00 29.00 11.51 0.113229E+09 70.85 25-APR-22:10 25.83 13.39
May 0.226076E+10 1258.25 31-MAY-19:00 34.00 12.73 0.117414E+09 71.58 09-MAY-22:10 34.00 12.73
June 0.278582E+10 1483.82 28-JUN-17:09 41.83 19.10 0.116745E+09 76.29 30-JUN-22:10 32.32 14.76
July 0.278225E+10 1437.03 22-JUL-10:35 35.67 19.48 0.119255E+09 74.96 21-JUL-22:10 35.67 19.48
August 0.264490E+10 1368.46 14-AUG-18:10 37.83 18.84 0.118907E+09 73.82 15-AUG-22:10 30.83 16.85
September 0.237575E+10 1300.38 07-SEP-18:15 35.53 19.30 0.113875E+09 72.98 08-SEP-22:10 29.22 19.02
October 0.158041E+10 1218.09 02-OCT-19:10 29.50 19.51 0.116886E+09 71.48 03-OCT-21:49 27.50 17.99
November 0.887601E+09 877.74 02-NOV-21:00 20.00 15.51 0.112879E+09 68.58 25-NOV-03:09 10.00 4.16
December 0.473163E+09 594.47 26-DEC-22:00 15.00 7.29 0.116672E+09 68.58 05-DEC-05:49 15.00 7.29
                     
Annual Sum or Average 0.197591E+11         0.138529E+10        
Minimum of Months 0.473163E+09 568.01   13.00 7.11 0.105501E+09 68.58   10.00 4.05
Maximum of Months 0.278582E+10 1483.82   41.83 19.51 0.119255E+09 76.29   35.67 19.48



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.506614E+11 36375.38 27-JAN-21:00 17.00 6.99 0.509800E+09 381.73 03-JAN-22:10 17.00 6.99
February 0.452528E+11 36045.16 21-FEB-21:00 15.00 11.45 0.460964E+09 381.79 21-FEB-22:10 14.00 12.80
March 0.510882E+11 36763.18 16-MAR-20:00 22.20 12.56 0.512721E+09 381.75 07-MAR-22:10 22.20 12.56
April 0.519962E+11 37764.33 13-APR-20:00 29.00 11.51 0.492754E+09 381.70 07-APR-21:10 29.00 11.51
May 0.547317E+11 38012.93 18-MAY-20:00 30.00 12.86 0.509482E+09 381.68 02-MAY-21:10 30.00 12.86
June 0.545754E+11 38927.46 29-JUN-20:00 37.00 17.00 0.492670E+09 381.64 13-JUN-21:10 37.00 17.00
July 0.556895E+11 38718.16 20-JUL-20:00 36.00 18.39 0.505896E+09 381.61 28-JUL-21:10 24.83 19.53
August 0.556132E+11 38451.97 14-AUG-20:00 34.00 18.28 0.510004E+09 381.62 18-AUG-21:10 25.50 19.00
September 0.529382E+11 38365.43 07-SEP-20:00 33.80 19.25 0.491550E+09 381.66 15-SEP-21:10 26.52 13.71
October 0.526953E+11 37804.39 04-OCT-20:00 28.00 16.16 0.509290E+09 381.72 13-OCT-21:10 15.83 5.47
November 0.493150E+11 36692.89 01-NOV-20:00 21.00 13.76 0.493435E+09 381.73 17-NOV-22:10 10.00 8.40
December 0.496918E+11 36097.10 22-DEC-21:00 14.00 5.51 0.509819E+09 381.81 12-DEC-22:10 14.00 5.51
                     
Annual Sum or Average 0.624249E+12         0.599839E+10        
Minimum of Months 0.452528E+11 36045.16   14.00 5.51 0.460964E+09 381.61   10.00 5.47
Maximum of Months 0.556895E+11 38927.46   37.00 19.25 0.512721E+09 381.81   37.00 19.53



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.260817E+11 13927.77 29-JAN-11:35 21.33 8.67 0.834329E+10 5241.74 19-JAN-22:19 21.33 8.67
February 0.195262E+11 12648.84 26-FEB-11:35 15.33 10.16 0.740453E+10 5076.06 21-FEB-22:30 15.33 10.16
March 0.225644E+11 12865.92 18-MAR-17:12 26.63 12.71 0.825726E+10 5329.49 16-MAR-21:30 26.63 12.71
April 0.267772E+11 14100.94 13-APR-18:10 32.67 13.82 0.819401E+10 5624.69 14-APR-21:40 27.67 12.83
May 0.278550E+11 14186.01 31-MAY-18:10 35.67 13.49 0.850527E+10 5548.40 09-MAY-21:40 35.67 13.49
June 0.297416E+11 15774.43 28-JUN-17:09 41.83 19.10 0.848436E+10 5765.66 30-JUN-22:10 32.32 14.76
July 0.303794E+11 15189.66 20-JUL-18:10 38.67 19.18 0.869937E+10 5762.92 21-JUL-22:10 32.83 20.17
August 0.306914E+11 14957.86 14-AUG-18:10 37.83 18.84 0.877495E+10 5737.29 15-AUG-21:49 31.33 17.02
September 0.295176E+11 14991.41 07-SEP-18:10 35.82 19.33 0.844431E+10 5777.34 07-SEP-21:40 31.10 19.30
October 0.280056E+11 14782.53 05-OCT-15:25 34.00 15.34 0.852271E+10 5648.24 03-OCT-21:40 34.00 15.34
November 0.246570E+11 14374.56 01-NOV-15:13 28.67 16.04 0.805298E+10 5400.19 01-NOV-21:30 18.00 13.11
December 0.234303E+11 14204.15 25-DEC-11:35 22.33 10.13 0.824174E+10 5229.04 26-DEC-22:19 14.67 7.12
                     
Annual Sum or Average 0.319227E+12         0.999248E+11        
Minimum of Months 0.195262E+11 12648.84   15.33 8.67 0.740453E+10 5076.06   14.67 7.12
Maximum of Months 0.306914E+11 15774.43   41.83 19.33 0.877495E+10 5777.34   35.67 20.17



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.816648E+11 39304.20 27-JAN-21:00 17.00 6.99 0.246506E+11 15666.46 31-JAN-22:40 13.83 4.56
February 0.666140E+11 38023.91 22-FEB-19:10 16.67 11.30 0.221244E+11 15391.22 21-FEB-22:40 16.67 11.30
March 0.769638E+11 41899.58 16-MAR-18:10 25.22 13.24 0.247675E+11 15958.83 17-MAR-21:40 20.87 12.09
April 0.869830E+11 45649.03 13-APR-18:10 32.67 13.82 0.245242E+11 16560.61 14-APR-21:49 27.33 12.71
May 0.924184E+11 46612.00 31-MAY-18:10 35.67 13.49 0.255965E+11 16538.35 09-MAY-21:49 35.67 13.49
June 0.975164E+11 50442.95 28-JUN-18:10 40.83 17.83 0.253769E+11 17079.21 30-JUN-22:10 32.32 14.76
July 0.993094E+11 49091.72 20-JUL-18:10 38.67 19.18 0.259803E+11 16975.52 21-JUL-22:10 32.83 20.17
August 0.991084E+11 48321.24 14-AUG-18:10 37.83 18.84 0.260632E+11 16897.37 15-AUG-22:10 30.83 16.85
September 0.945449E+11 47846.97 07-SEP-18:10 35.82 19.33 0.250142E+11 16864.41 08-SEP-21:49 29.87 18.99
October 0.892147E+11 46105.89 04-OCT-18:10 32.67 17.42 0.252117E+11 16605.48 03-OCT-21:40 32.67 17.42
November 0.791930E+11 42159.81 01-NOV-18:10 23.67 14.38 0.239119E+11 16026.09 01-NOV-21:40 18.00 13.11
December 0.758322E+11 38523.23 22-DEC-21:00 14.00 5.51 0.244530E+11 15602.65 26-DEC-22:40 14.33 6.96
                     
Annual Sum or Average 0.103936E+13         0.297674E+12        
Minimum of Months 0.666140E+11 38023.91   14.00 5.51 0.221244E+11 15391.22   13.83 4.56
Maximum of Months 0.993094E+11 50442.95   40.83 19.33 0.260632E+11 17079.21   35.67 20.17



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.102183E+10 3933.56 31-JAN-16:01 29.00 10.73 97968187.06 56.69 30-JAN-22:10 29.00 10.73
February 0.434454E+09 3875.28 28-FEB-16:01 19.00 8.42 87312897.71 56.69 16-FEB-22:10 19.00 8.42
March 0.855861E+09 3904.94 09-MAR-16:01 22.70 11.30 97616794.65 56.69 23-MAR-21:30 14.40 7.77
April 0.228983E+10 3984.34 14-APR-18:01 33.50 13.96 95556671.52 56.70 12-APR-22:00 33.50 13.96
May 0.272008E+10 3963.16 05-MAY-15:01 34.83 13.09 99004730.45 56.70 10-MAY-22:00 26.00 15.12
June 0.353742E+10 4002.28 27-JUN-18:02 39.83 15.83 96056654.09 56.70 29-JUN-21:30 34.50 16.25
July 0.324526E+10 3977.91 05-JUL-18:02 37.83 16.08 99086014.19 56.70 20-JUL-21:49 32.67 18.26
August 0.316928E+10 3985.36 27-AUG-15:02 40.00 18.27 99156400.98 56.70 01-AUG-21:10 40.00 18.27
September 0.275571E+10 3971.63 28-SEP-15:02 37.52 15.49 95822301.51 56.70 07-SEP-21:30 37.52 15.49
October 0.186263E+10 3995.96 06-OCT-15:01 35.00 14.90 98514963.40 56.70 03-OCT-23:40 35.00 14.90
November 0.101005E+10 3962.28 20-NOV-16:01 26.83 12.13 94736454.73 56.69 14-NOV-22:30 26.83 12.13
December 0.579431E+09 3919.89 24-DEC-16:01 22.83 10.09 97234501.06 56.69 26-DEC-22:10 14.83 7.20
                     
Annual Sum or Average 0.234819E+11         0.115807E+10        
Minimum of Months 0.434454E+09 3875.28   19.00 8.42 87312897.71 56.69   14.40 7.20
Maximum of Months 0.353742E+10 4002.28   40.00 18.27 99156400.98 56.70   40.00 18.27



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.504013E+09 3842.68 31-JAN-16:01 29.00 10.73 96535804.44 56.69 27-JAN-22:10 29.00 10.73
February 0.227389E+09 3786.16 28-FEB-16:01 19.00 8.42 86295152.99 56.69 01-FEB-00:49 19.00 8.42
March 0.640048E+09 3852.38 18-MAR-18:01 25.13 12.09 96903358.00 56.69 16-MAR-21:49 25.13 12.09
April 0.203743E+10 3953.19 25-APR-18:01 31.67 15.03 95444885.72 56.70 25-APR-22:10 25.83 13.39
May 0.265383E+10 3938.21 27-MAY-18:01 29.83 11.10 99009171.78 56.70 10-MAY-22:00 29.83 11.10
June 0.357529E+10 3988.52 27-JUN-18:02 39.83 15.83 96087570.25 56.70 29-JUN-21:40 34.33 16.16
July 0.323372E+10 3962.66 05-JUL-18:02 37.83 16.08 99098304.55 56.70 21-JUL-21:49 33.17 20.33
August 0.302123E+10 3951.46 25-AUG-18:02 38.67 17.09 99147368.10 56.70 17-AUG-21:10 38.67 17.09
September 0.249547E+10 3905.04 28-SEP-15:02 37.52 15.49 95777935.94 56.70 08-SEP-21:10 37.52 15.49
October 0.141419E+10 3928.54 06-OCT-15:01 35.00 14.90 97936805.73 56.70 03-OCT-22:00 35.00 14.90
November 0.568724E+09 3872.04 20-NOV-16:01 26.83 12.13 93654378.82 56.69 02-NOV-22:10 26.83 12.13
December 0.238508E+09 3819.70 24-DEC-16:01 22.83 10.09 95458430.38 56.69 12-DEC-22:10 22.83 10.09
                     
Annual Sum or Average 0.206098E+11         0.115135E+10        
Minimum of Months 0.227389E+09 3786.16   19.00 8.42 86295152.99 56.69   19.00 8.42
Maximum of Months 0.357529E+10 3988.52   39.83 17.09 99147368.10 56.70   38.67 20.33



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.863249E+09 772.41 14-JAN-13:40 26.67 10.98 0.00 0.00 01-JAN-00:10 26.67 10.98
February 0.456290E+09 596.69 01-FEB-15:30 15.50 6.96 0.00 0.00 01-FEB-00:10 15.50 6.96
March 0.519003E+09 584.14 18-MAR-13:40 26.27 12.12 0.00 0.00 01-MAR-00:10 26.27 12.12
April 0.844685E+09 596.23 14-APR-13:40 34.00 14.40 0.00 0.00 01-APR-00:10 34.00 14.40
May 0.872260E+09 549.72 07-MAY-20:03 30.67 12.72 0.00 0.00 01-MAY-00:10 30.67 12.72
June 0.105102E+10 660.86 28-JUN-19:10 39.50 16.83 0.00 0.00 01-JUN-00:10 39.50 16.83
July 0.107272E+10 646.26 22-JUL-19:10 35.67 20.23 0.00 0.00 01-JUL-00:10 35.67 20.23
August 0.110814E+10 678.75 27-AUG-14:00 40.00 18.27 0.00 0.00 01-AUG-00:10 40.00 18.27
September 0.108766E+10 746.19 28-SEP-13:40 36.47 16.05 0.00 0.00 01-SEP-00:10 36.47 16.05
October 0.961902E+09 762.89 18-OCT-13:40 30.67 12.12 0.00 0.00 01-OCT-00:10 30.67 12.12
November 0.754910E+09 792.74 20-NOV-14:30 27.00 11.68 0.00 0.00 01-NOV-00:10 27.00 11.68
December 0.705170E+09 766.96 25-DEC-13:30 25.50 11.81 0.00 0.00 01-DEC-00:10 25.50 11.81
                     
Annual Sum or Average 0.102970E+11         0.00        
Minimum of Months 0.456290E+09 549.72   15.50 6.96 0.00 0.00   15.50 6.96
Maximum of Months 0.110814E+10 792.74   40.00 20.23 0.00 0.00   40.00 20.23



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.408264E+09 1356.97 31-JAN-19:01 23.00 8.93 96315055.17 56.69 12-JAN-22:10 23.00 8.93
February 0.330636E+09 1281.09 22-FEB-16:02 20.83 11.61 86933429.95 56.69 15-FEB-23:40 20.83 11.61
March 0.503422E+09 1414.35 16-MAR-18:01 25.22 13.24 96853278.28 56.69 16-MAR-21:40 20.37 12.33
April 0.873034E+09 1437.43 25-APR-18:01 31.67 15.03 95002880.16 56.69 25-APR-00:30 31.67 15.03
May 0.109980E+10 1435.88 26-MAY-18:01 30.67 13.06 98736172.28 56.69 23-MAY-21:30 30.67 13.06
June 0.136919E+10 1441.83 26-JUN-18:02 38.83 16.12 95910749.82 56.70 27-JUN-21:40 34.00 14.28
July 0.134892E+10 1438.79 07-JUL-18:02 36.83 15.93 98930415.80 56.70 14-JUL-22:10 27.00 20.14
August 0.125200E+10 1433.05 25-AUG-18:02 38.67 17.09 98931823.14 56.70 31-AUG-21:49 27.28 17.77
September 0.111036E+10 1436.39 27-SEP-18:01 33.85 15.73 95526895.61 56.70 20-SEP-21:49 33.85 15.73
October 0.746840E+09 1431.99 06-OCT-15:01 35.00 14.90 97556227.19 56.70 03-OCT-21:40 35.00 14.90
November 0.438848E+09 1349.72 09-NOV-19:01 21.58 9.60 93404958.21 56.69 14-NOV-22:10 14.67 13.13
December 0.283512E+09 1291.70 25-DEC-16:02 25.67 11.87 95841254.99 56.69 12-DEC-23:10 25.67 11.87
                     
Annual Sum or Average 0.976483E+10         0.114994E+10        
Minimum of Months 0.283512E+09 1281.09   20.83 8.93 86933429.95 56.69   14.67 8.93
Maximum of Months 0.136919E+10 1441.83   38.83 17.09 98931823.14 56.70   35.00 20.14



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.976106E+09 3472.52 31-JAN-16:01 29.00 10.73 98319534.52 56.69 25-JAN-22:10 29.00 10.73
February 0.489542E+09 3424.03 21-FEB-16:01 20.67 11.05 87812435.69 56.69 21-FEB-22:10 14.00 12.80
March 0.891162E+09 3456.68 23-MAR-15:01 24.80 11.21 98126114.47 56.69 21-MAR-21:30 24.80 11.21
April 0.231460E+10 3522.10 14-APR-15:01 35.00 14.57 95908959.08 56.70 24-APR-23:40 26.33 13.11
May 0.279665E+10 3529.17 18-MAY-08:61 27.33 12.53 99197113.88 56.70 10-MAY-23:40 27.33 12.53
June 0.361522E+10 3553.90 19-JUN-08:61 31.17 13.53 96043230.65 56.70 29-JUN-21:00 34.00 15.96
July 0.345387E+10 3535.05 01-JUL-08:61 27.50 10.46 99137814.30 56.70 27-JUL-21:10 30.67 20.57
August 0.333971E+10 3545.21 27-AUG-08:61 29.67 14.57 99231649.24 56.70 11-AUG-21:49 29.67 14.57
September 0.284472E+10 3514.89 28-SEP-15:02 37.52 15.49 95917538.57 56.70 08-SEP-21:00 37.52 15.49
October 0.192486E+10 3534.90 06-OCT-15:01 35.00 14.90 98832405.79 56.70 04-OCT-00:40 35.00 14.90
November 0.943398E+09 3480.30 20-NOV-16:01 26.83 12.13 94986379.60 56.69 02-NOV-23:49 26.83 12.13
December 0.590816E+09 3451.03 24-DEC-16:01 22.83 10.09 97580561.32 56.69 26-DEC-22:10 14.83 7.20
                     
Annual Sum or Average 0.241807E+11         0.116109E+10        
Minimum of Months 0.489542E+09 3424.03   20.67 10.09 87812435.69 56.69   14.00 7.20
Maximum of Months 0.361522E+10 3553.90   37.52 15.49 99231649.24 56.70   37.52 20.57



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.460070E+09 3389.26 31-JAN-16:01 29.00 10.73 96742244.88 56.69 19-JAN-22:10 29.00 10.73
February 0.266760E+09 3172.39 21-FEB-16:01 20.67 11.05 86727526.38 56.69 21-FEB-22:10 14.00 12.80
March 0.664105E+09 3414.04 19-MAR-15:01 26.10 11.81 97448964.58 56.69 16-MAR-21:00 26.10 11.81
April 0.205067E+10 3478.64 14-APR-15:01 35.00 14.57 95896505.40 56.69 05-APR-21:49 35.00 14.57
May 0.272829E+10 3510.57 18-MAY-08:61 27.33 12.53 99197253.36 56.69 08-MAY-00:40 27.33 12.53
June 0.365286E+10 3538.72 19-JUN-08:61 31.17 13.53 96051508.44 56.70 29-JUN-22:10 33.83 15.97
July 0.344160E+10 3519.82 01-JUL-08:61 27.50 10.46 99138263.91 56.70 12-JUL-21:40 29.33 20.33
August 0.319009E+10 3521.28 27-AUG-08:61 29.67 14.57 99228532.87 56.70 11-AUG-21:30 29.67 14.57
September 0.258014E+10 3487.31 18-SEP-08:61 27.67 13.20 95908638.87 56.70 06-SEP-21:10 27.67 13.20
October 0.145566E+10 3475.28 06-OCT-15:01 35.00 14.90 98399202.40 56.70 02-OCT-23:00 35.00 14.90
November 0.511801E+09 3393.87 10-NOV-16:01 24.50 12.16 93745182.80 56.69 10-NOV-22:10 17.83 14.16
December 0.236563E+09 3199.42 24-DEC-09:01 15.67 6.96 95596567.01 56.69 12-DEC-22:10 15.67 6.96
                     
Annual Sum or Average 0.212386E+11         0.115408E+10        
Minimum of Months 0.236563E+09 3172.39   15.67 6.96 86727526.38 56.69   14.00 6.96
Maximum of Months 0.365286E+10 3538.72   35.00 14.90 99228532.87 56.70   35.00 20.33



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.475227E+10 2568.69 29-JAN-11:35 21.33 8.67 0.120329E+10 725.45 31-JAN-22:40 13.83 4.56
February 0.329899E+10 2218.73 22-FEB-16:50 20.17 11.33 0.108401E+10 716.83 01-FEB-00:10 20.17 11.33
March 0.429971E+10 2734.44 18-MAR-18:03 25.13 12.09 0.120809E+10 735.44 17-MAR-21:40 25.13 12.09
April 0.608597E+10 3149.75 15-APR-10:35 28.00 13.04 0.121171E+10 786.53 14-APR-21:40 28.00 13.04
May 0.666037E+10 3224.60 18-MAY-18:10 34.67 14.15 0.128302E+10 789.50 09-MAY-21:49 34.67 14.15
June 0.721265E+10 3709.51 28-JUN-17:09 41.83 19.10 0.131644E+10 850.09 30-JUN-22:10 32.32 14.76
July 0.734199E+10 3560.92 22-JUL-10:35 35.67 19.48 0.134606E+10 837.43 01-JUL-00:10 35.67 19.48
August 0.721742E+10 3496.20 14-AUG-18:10 37.83 18.84 0.133891E+10 828.80 15-AUG-21:49 31.33 17.02
September 0.677291E+10 3444.43 09-SEP-10:35 33.43 20.70 0.127700E+10 819.39 08-SEP-21:49 33.43 20.70
October 0.594525E+10 3270.49 04-OCT-18:10 32.67 17.42 0.125296E+10 804.37 06-OCT-21:40 26.00 13.83
November 0.464306E+10 2775.73 01-NOV-18:10 23.67 14.38 0.116563E+10 743.74 01-NOV-21:40 18.00 13.11
December 0.378769E+10 2568.11 25-DEC-11:35 22.33 10.13 0.119978E+10 719.93 26-DEC-22:40 14.33 6.96
                     
Annual Sum or Average 0.680183E+11         0.148869E+11        
Minimum of Months 0.329899E+10 2218.73   20.17 8.67 0.108401E+10 716.83   13.83 4.56
Maximum of Months 0.734199E+10 3709.51   41.83 20.70 0.134606E+10 850.09   35.67 20.70



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.103172E+10 4236.81 31-JAN-16:01 29.00 10.73 97862723.18 56.69 19-JAN-22:10 29.00 10.73
February 0.415003E+09 4170.26 28-FEB-16:01 19.00 8.42 87159377.24 56.69 01-FEB-01:49 19.00 8.42
March 0.900240E+09 4207.32 09-MAR-16:01 22.70 11.30 97574008.73 56.69 22-MAR-21:10 13.35 7.10
April 0.256902E+10 4310.91 14-APR-15:01 35.00 14.57 95540095.99 56.70 19-APR-21:10 20.83 9.47
May 0.308498E+10 4289.81 15-MAY-15:01 36.00 15.08 99015438.52 56.70 22-MAY-22:10 23.83 11.56
June 0.402461E+10 4326.35 27-JUN-18:02 39.83 15.83 96117197.43 56.70 29-JUN-21:40 34.33 16.16
July 0.370642E+10 4296.45 05-JUL-18:02 37.83 16.08 99104418.78 56.70 21-JUL-22:10 32.83 20.17
August 0.361052E+10 4313.46 27-AUG-15:02 40.00 18.27 99182530.52 56.70 01-AUG-21:10 40.00 18.27
September 0.309424E+10 4296.77 28-SEP-15:02 37.52 15.49 95831084.35 56.70 07-SEP-21:40 37.52 15.49
October 0.200144E+10 4312.48 06-OCT-15:01 35.00 14.90 98469150.48 56.70 03-OCT-23:40 35.00 14.90
November 0.102682E+10 4275.63 20-NOV-16:01 26.83 12.13 94646413.71 56.69 02-NOV-22:00 26.83 12.13
December 0.559435E+09 4215.93 24-DEC-16:01 22.83 10.09 97002669.29 56.69 12-DEC-22:10 22.83 10.09
                     
Annual Sum or Average 0.260244E+11         0.115751E+10        
Minimum of Months 0.415003E+09 4170.26   19.00 8.42 87159377.24 56.69   13.35 7.10
Maximum of Months 0.402461E+10 4326.35   40.00 18.27 99182530.52 56.70   40.00 20.17



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.498349E+09 4128.91 31-JAN-16:01 29.00 10.73 96444133.37 56.69 31-JAN-22:10 14.48 5.13
February 0.210191E+09 4063.54 28-FEB-16:01 19.00 8.42 86112931.76 56.69 21-FEB-22:19 19.00 8.42
March 0.670840E+09 4147.25 18-MAR-18:01 25.13 12.09 96906067.43 56.69 16-MAR-21:49 25.13 12.09
April 0.230151E+10 4267.38 25-APR-18:01 31.67 15.03 95474046.98 56.69 05-APR-21:30 31.67 15.03
May 0.301557E+10 4254.33 15-MAY-15:01 36.00 15.08 99025622.88 56.70 10-MAY-22:00 36.00 15.08
June 0.406398E+10 4309.62 27-JUN-18:02 39.83 15.83 96148489.59 56.70 29-JUN-21:49 34.17 16.06
July 0.369417E+10 4277.98 05-JUL-18:02 37.83 16.08 99114705.14 56.70 21-JUL-22:10 32.83 20.17
August 0.345553E+10 4270.71 25-AUG-18:02 38.67 17.09 99169984.05 56.70 01-AUG-21:10 38.67 17.09
September 0.282067E+10 4220.15 28-SEP-15:02 37.52 15.49 95792193.58 56.70 08-SEP-21:10 37.52 15.49
October 0.152665E+10 4234.99 06-OCT-15:01 35.00 14.90 97949760.25 56.70 03-OCT-22:40 35.00 14.90
November 0.568508E+09 4167.71 20-NOV-16:01 26.83 12.13 93592033.97 56.70 16-NOV-22:49 26.83 12.13
December 0.222649E+09 4094.01 24-DEC-16:01 22.83 10.09 95194683.45 56.70 21-DEC-22:40 22.83 10.09
                     
Annual Sum or Average 0.230486E+11         0.115092E+10        
Minimum of Months 0.210191E+09 4063.54   19.00 8.42 86112931.76 56.69   14.48 5.13
Maximum of Months 0.406398E+10 4309.62   39.83 17.09 99169984.05 56.70   38.67 20.17



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.131882E+10 2213.20 31-JAN-16:01 29.00 10.73 98700535.48 56.69 09-JAN-22:10 29.00 10.73
February 0.617221E+09 2165.85 21-FEB-16:01 20.67 11.05 88237772.87 56.69 16-FEB-22:00 20.67 11.05
March 0.786586E+09 2185.98 18-MAR-15:02 27.20 12.30 98169451.01 56.69 16-MAR-21:40 27.20 12.30
April 0.149677E+10 2210.67 14-APR-15:01 35.00 14.57 95567775.57 56.69 25-APR-00:20 25.67 13.17
May 0.159972E+10 2188.49 06-MAY-15:01 34.00 13.45 98980036.43 56.69 10-MAY-23:40 25.33 14.90
June 0.200653E+10 2183.53 27-JUN-15:02 41.00 15.93 95981786.33 56.70 27-JUN-21:10 35.50 14.88
July 0.202490E+10 2174.64 07-JUL-15:02 37.00 15.61 99076332.06 56.70 18-JUL-21:49 30.17 19.76
August 0.207188E+10 2204.54 26-AUG-15:02 41.00 16.32 99170433.75 56.70 31-AUG-21:10 27.62 17.64
September 0.197674E+10 2222.78 28-SEP-15:02 37.52 15.49 95868908.11 56.70 01-SEP-21:40 37.52 15.49
October 0.161583E+10 2230.66 06-OCT-15:01 35.00 14.90 98790733.67 56.70 03-OCT-21:49 35.00 14.90
November 0.116813E+10 2224.84 20-NOV-16:01 26.83 12.13 95356210.26 56.69 20-NOV-22:30 14.00 9.66
December 0.989560E+09 2209.87 24-DEC-16:01 22.83 10.09 98357678.54 56.69 26-DEC-22:40 14.33 6.96
                     
Annual Sum or Average 0.176727E+11         0.116226E+10        
Minimum of Months 0.617221E+09 2165.85   20.67 10.09 88237772.87 56.69   14.00 6.96
Maximum of Months 0.207188E+10 2230.66   41.00 16.32 99170433.75 56.70   37.52 19.76



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.418427E+11 19862.35 06-JAN-22:20 17.33 9.21 0.151030E+11 9921.14 06-JAN-22:30 17.00 9.12
February 0.372374E+11 19767.66 15-FEB-23:00 15.00 13.76 0.136299E+11 9819.04 15-FEB-23:10 14.83 13.71
March 0.431164E+11 21110.37 16-MAR-18:10 25.22 13.24 0.153417E+11 10184.91 17-MAR-22:10 20.32 11.79
April 0.466563E+11 23106.08 13-APR-18:10 32.67 13.82 0.152566E+11 10570.94 14-APR-21:40 27.67 12.83
May 0.502579E+11 24066.54 31-MAY-18:10 35.67 13.49 0.160320E+11 10629.83 09-MAY-22:10 35.67 13.49
June 0.522601E+11 26082.64 28-JUN-18:10 40.83 17.83 0.159783E+11 10986.72 30-JUN-22:10 32.32 14.76
July 0.532289E+11 25245.97 20-JUL-18:10 38.67 19.18 0.163322E+11 10902.53 21-JUL-22:10 32.83 20.17
August 0.524209E+11 24547.08 14-AUG-18:10 37.83 18.84 0.163091E+11 10792.44 15-AUG-22:10 30.83 16.85
September 0.491897E+11 24118.42 07-SEP-18:10 35.82 19.33 0.155632E+11 10716.63 08-SEP-22:10 29.22 19.02
October 0.459379E+11 23038.01 02-OCT-18:10 32.50 19.26 0.155383E+11 10532.11 03-OCT-21:40 28.00 18.15
November 0.411081E+11 20798.61 01-NOV-18:10 23.67 14.38 0.146829E+11 10096.14 02-NOV-22:10 19.83 16.01
December 0.400037E+11 19504.63 26-DEC-23:00 14.00 6.79 0.149312E+11 9804.95 26-DEC-23:10 13.50 6.50
                     
Annual Sum or Average 0.553260E+12         0.184698E+12        
Minimum of Months 0.372374E+11 19504.63   14.00 6.79 0.136299E+11 9804.95   13.50 6.50
Maximum of Months 0.532289E+11 26082.64   40.83 19.33 0.163322E+11 10986.72   35.67 20.17



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.448099E+11 21071.84 06-JAN-22:20 17.33 9.21 0.151822E+11 10010.67 06-JAN-22:30 17.00 9.12
February 0.399586E+11 20984.13 15-FEB-23:00 15.00 13.76 0.137072E+11 9911.02 15-FEB-23:10 14.83 13.71
March 0.461993E+11 22402.87 16-MAR-18:10 25.22 13.24 0.154398E+11 10280.28 17-MAR-22:10 20.32 11.79
April 0.497340E+11 24433.25 13-APR-18:10 32.67 13.82 0.153695E+11 10651.12 14-APR-22:10 26.83 12.60
May 0.534954E+11 25471.15 31-MAY-18:10 35.67 13.49 0.161623E+11 10718.63 09-MAY-22:10 35.67 13.49
June 0.553250E+11 27441.81 28-JUN-18:10 40.83 17.83 0.160713E+11 11035.06 30-JUN-22:10 32.32 14.76
July 0.563714E+11 26605.89 20-JUL-18:10 38.67 19.18 0.164300E+11 10962.35 21-JUL-22:10 32.83 20.17
August 0.555563E+11 25863.03 14-AUG-18:10 37.83 18.84 0.164067E+11 10850.78 15-AUG-22:10 30.83 16.85
September 0.522319E+11 25431.86 07-SEP-18:10 35.82 19.33 0.156669E+11 10778.51 08-SEP-22:10 29.22 19.02
October 0.490223E+11 24364.43 02-OCT-18:10 32.50 19.26 0.156367E+11 10610.78 03-OCT-21:40 28.00 18.15
November 0.440112E+11 22039.13 01-NOV-18:10 23.67 14.38 0.147649E+11 10186.85 02-NOV-22:10 19.83 16.01
December 0.429309E+11 20690.52 12-DEC-23:00 12.00 9.19 0.150065E+11 9886.02 26-DEC-23:10 13.50 6.50
                     
Annual Sum or Average 0.589646E+12         0.185844E+12        
Minimum of Months 0.399586E+11 20690.52   12.00 9.19 0.137072E+11 9886.02   13.50 6.50
Maximum of Months 0.563714E+11 27441.81   40.83 19.33 0.164300E+11 11035.06   35.67 20.17



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.536384E+11 27574.62 29-JAN-11:40 21.33 8.67 0.186383E+11 11319.59 07-JAN-18:19 21.33 8.67
February 0.478389E+11 27406.30 26-FEB-11:50 15.67 10.28 0.168296E+11 11319.51 25-FEB-18:19 15.67 10.28
March 0.541894E+11 28464.92 18-MAR-10:45 24.12 14.75 0.186476E+11 11319.68 18-MAR-17:19 26.63 12.71
April 0.565840E+11 30126.15 30-APR-10:50 30.50 11.24 0.180699E+11 11319.67 08-APR-17:19 30.50 11.24
May 0.598539E+11 30388.17 20-MAY-10:50 31.67 12.61 0.186825E+11 11319.66 20-MAY-17:19 33.67 14.02
June 0.606443E+11 32315.38 28-JUN-17:09 41.83 19.10 0.180971E+11 11319.65 17-JUN-17:19 41.83 19.10
July 0.621163E+11 31472.96 22-JUL-10:40 35.67 19.48 0.186916E+11 11319.66 22-JUL-17:19 38.00 18.94
August 0.617545E+11 31492.05 13-AUG-10:40 33.67 21.36 0.186946E+11 11319.66 12-AUG-17:19 33.67 21.36
September 0.584979E+11 31112.18 09-SEP-10:50 33.62 20.75 0.180804E+11 11319.68 23-SEP-17:19 33.27 17.89
October 0.568147E+11 30157.87 02-OCT-10:40 32.33 19.00 0.186595E+11 11319.67 14-OCT-17:19 30.00 11.31
November 0.521936E+11 28332.46 01-NOV-10:50 24.67 16.10 0.180384E+11 11319.56 04-NOV-17:19 17.67 8.15
December 0.520628E+11 27385.29 25-DEC-11:40 22.33 10.13 0.186269E+11 11319.50 30-DEC-18:19 16.07 7.26
                     
Annual Sum or Average 0.676189E+12         0.219756E+12        
Minimum of Months 0.478389E+11 27385.29   15.67 8.67 0.168296E+11 11319.50   15.67 7.26
Maximum of Months 0.621163E+11 32315.38   41.83 21.36 0.186946E+11 11319.68   41.83 21.36



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.718599E+10 5841.67 31-JAN-16:50 29.00 10.73 0.126960E+10 745.75 24-JAN-01:39 29.00 10.73
February 0.469817E+10 5144.00 23-FEB-14:20 18.00 10.64 0.114712E+10 745.75 01-FEB-03:30 18.00 10.64
March 0.694933E+10 6477.88 18-MAR-17:12 26.63 12.71 0.127520E+10 745.74 09-MAR-02:20 26.63 12.71
April 0.121427E+11 7538.55 14-APR-17:12 34.67 14.39 0.124386E+10 805.62 14-APR-21:40 27.67 12.83
May 0.141343E+11 7590.01 31-MAY-18:10 35.67 13.49 0.129643E+10 803.22 09-MAY-21:40 35.67 13.49
June 0.164706E+11 9038.95 28-JUN-17:09 41.83 19.10 0.132485E+10 873.01 30-JUN-22:10 32.32 14.76
July 0.166759E+11 8463.22 23-JUL-10:35 33.67 21.75 0.135136E+10 856.12 21-JUL-22:10 33.67 21.75
August 0.162672E+11 8337.10 13-AUG-10:35 33.67 21.36 0.134556E+10 847.07 15-AUG-21:49 31.33 17.02
September 0.147987E+11 8098.93 09-SEP-10:35 33.43 20.70 0.127264E+10 838.98 08-SEP-21:40 33.43 20.70
October 0.108919E+11 7517.56 02-OCT-10:35 32.33 19.00 0.128157E+10 803.68 03-OCT-21:40 28.00 18.15
November 0.720909E+10 6442.56 01-NOV-16:20 27.33 15.26 0.122837E+10 745.71 27-NOV-05:19 8.37 3.73
December 0.502556E+10 5583.39 22-DEC-16:40 24.33 9.71 0.126895E+10 745.74 15-DEC-04:00 24.33 9.71
                     
Annual Sum or Average 0.132449E+12         0.153055E+11        
Minimum of Months 0.469817E+10 5144.00   18.00 9.71 0.114712E+10 745.71   8.37 3.73
Maximum of Months 0.166759E+11 9038.95   41.83 21.75 0.135136E+10 873.01   35.67 21.75



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 4.27
February 0.00 0.00 01-FEB-00:03 11.90
March 0.00 0.00 01-MAR-00:03 11.85
April 0.00 0.00 01-APR-00:10 15.28
May 0.00 0.00 01-MAY-00:10 19.10
June 0.00 0.00 01-JUN-00:10 25.83
July 0.00 0.00 01-JUL-00:10 27.73
August 0.00 0.00 01-AUG-00:10 29.40
September 0.00 0.00 01-SEP-00:10 26.22
October 0.00 0.00 01-OCT-00:10 25.15
November 0.00 0.00 01-NOV-00:10 17.23
December 0.00 0.00 01-DEC-00:03 9.20
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   4.27
Maximum of Months 0.00 0.00   29.40



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 5085272.59 371.83 01-JAN-06:00 0.80
February 2611846.49 196.67 13-FEB-07:10 8.33
March 21535485.01 542.15 27-MAR-06:10 1.97
April 0.00 0.00 01-APR-00:10 15.28
May 0.00 0.00 01-MAY-00:10 19.10
June 0.00 0.00 01-JUN-00:10 25.83
July 0.00 0.00 01-JUL-00:10 27.73
August 0.00 0.00 01-AUG-00:10 29.40
September 0.00 0.00 01-SEP-00:10 26.22
October 72595.68 49.52 25-OCT-06:30 5.00
November 3436586.61 278.09 23-NOV-07:00 0.00
December 57376110.95 586.79 16-DEC-07:20 1.33
         
Annual Sum or Average 90117897.34      
Minimum of Months 0.00 0.00   0.00
Maximum of Months 57376110.95 586.79   29.40



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 4.27
February 0.00 0.00 01-FEB-00:03 11.90
March 0.00 0.00 01-MAR-00:03 11.85
April 0.00 0.00 01-APR-00:10 15.28
May 0.00 0.00 01-MAY-00:10 19.10
June 0.00 0.00 01-JUN-00:10 25.83
July 0.00 0.00 01-JUL-00:10 27.73
August 0.00 0.00 01-AUG-00:10 29.40
September 0.00 0.00 01-SEP-00:10 26.22
October 0.00 0.00 01-OCT-00:10 25.15
November 0.00 0.00 01-NOV-00:10 17.23
December 0.00 0.00 01-DEC-00:03 9.20
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   4.27
Maximum of Months 0.00 0.00   29.40



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 856959.39 109.45 02-JAN-05:00 4.00
February 0.00 0.00 01-FEB-00:03 11.90
March 179008.13 80.55 27-MAR-04:00 2.20
April 0.00 0.00 01-APR-00:10 15.28
May 0.00 0.00 01-MAY-00:10 19.10
June 0.00 0.00 01-JUN-00:10 25.83
July 0.00 0.00 01-JUL-00:10 27.73
August 0.00 0.00 01-AUG-00:10 29.40
September 0.00 0.00 01-SEP-00:10 26.22
October 0.00 0.00 01-OCT-00:10 25.15
November 72390.85 52.84 24-NOV-05:00 4.00
December 7565689.94 203.89 07-DEC-05:00 -1.1
         
Annual Sum or Average 8674048.30      
Minimum of Months 0.00 0.00   -1.1
Maximum of Months 7565689.94 203.89   29.40



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 7346674.19 174.41 01-JAN-06:00 0.80
February 128814.32 24.36 05-FEB-06:00 8.00
March 4731818.87 137.20 27-MAR-03:50 2.47
April 0.00 0.00 01-APR-00:10 15.28
May 0.00 0.00 01-MAY-00:10 19.10
June 0.00 0.00 01-JUN-00:10 25.83
July 0.00 0.00 01-JUL-00:10 27.73
August 0.00 0.00 01-AUG-00:10 29.40
September 0.00 0.00 01-SEP-00:10 26.22
October 0.00 0.00 01-OCT-00:10 25.15
November 2526872.65 114.52 24-NOV-05:00 4.00
December 35590724.92 196.86 07-DEC-05:00 -1.1
         
Annual Sum or Average 50324904.95      
Minimum of Months 0.00 0.00   -1.1
Maximum of Months 35590724.92 196.86   29.40



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 4.27
February 0.00 0.00 01-FEB-00:03 11.90
March 0.00 0.00 01-MAR-00:03 11.85
April 0.00 0.00 01-APR-00:10 15.28
May 0.00 0.00 01-MAY-00:10 19.10
June 0.00 0.00 01-JUN-00:10 25.83
July 0.00 0.00 01-JUL-00:10 27.73
August 0.00 0.00 01-AUG-00:10 29.40
September 0.00 0.00 01-SEP-00:10 26.22
October 0.00 0.00 01-OCT-00:10 25.15
November 0.00 0.00 01-NOV-00:10 17.23
December 0.00 0.00 01-DEC-00:03 9.20
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   4.27
Maximum of Months 0.00 0.00   29.40



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 4.27
February 0.00 0.00 01-FEB-00:03 11.90
March 0.00 0.00 01-MAR-00:03 11.85
April 0.00 0.00 01-APR-00:10 15.28
May 0.00 0.00 01-MAY-00:10 19.10
June 0.00 0.00 01-JUN-00:10 25.83
July 0.00 0.00 01-JUL-00:10 27.73
August 0.00 0.00 01-AUG-00:10 29.40
September 0.00 0.00 01-SEP-00:10 26.22
October 0.00 0.00 01-OCT-00:10 25.15
November 0.00 0.00 01-NOV-00:10 17.23
December 0.00 0.00 01-DEC-00:03 9.20
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   4.27
Maximum of Months 0.00 0.00   29.40



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 4.27
February 0.00 0.00 01-FEB-00:03 11.90
March 0.00 0.00 01-MAR-00:03 11.85
April 0.00 0.00 01-APR-00:10 15.28
May 0.00 0.00 01-MAY-00:10 19.10
June 0.00 0.00 01-JUN-00:10 25.83
July 0.00 0.00 01-JUL-00:10 27.73
August 0.00 0.00 01-AUG-00:10 29.40
September 0.00 0.00 01-SEP-00:10 26.22
October 0.00 0.00 01-OCT-00:10 25.15
November 0.00 0.00 01-NOV-00:10 17.23
December 0.00 0.00 01-DEC-00:03 9.20
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   4.27
Maximum of Months 0.00 0.00   29.40



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 58762025.38 1608.78 01-JAN-09:02 5.90
February 0.105071E+09 1579.70 12-FEB-16:02 14.00
March 82279534.15 1630.34 27-MAR-08:62 9.77
April 1553617.08 935.18 09-APR-08:03 21.33
May 752191.13 741.63 01-MAY-08:03 19.50
June 99706.01 268.34 13-JUN-08:04 25.50
July 395000.60 601.19 29-JUL-08:04 26.33
August 527484.50 675.25 05-AUG-08:04 23.33
September 782889.19 789.18 04-SEP-08:04 23.08
October 12589496.96 1030.10 25-OCT-08:62 8.50
November 46456598.51 1056.63 24-NOV-09:02 9.00
December 0.204858E+09 1626.95 07-DEC-09:02 6.67
         
Annual Sum or Average 0.514127E+09      
Minimum of Months 99706.01 268.34   5.90
Maximum of Months 0.204858E+09 1630.34   26.33



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.152820E+09 1661.77 01-JAN-09:02 5.90
February 0.185174E+09 1633.26 03-FEB-09:02 10.33
March 0.120748E+09 1642.10 27-MAR-08:62 9.77
April 1815969.30 991.40 11-APR-08:03 23.33
May 730724.08 739.29 01-MAY-08:03 19.50
June 36558.03 165.97 13-JUN-08:04 25.50
July 373530.83 626.57 27-JUL-08:04 25.33
August 565364.14 651.36 05-AUG-08:04 23.33
September 961433.18 822.95 22-SEP-08:03 22.47
October 29221929.90 1582.69 25-OCT-08:62 8.50
November 0.107828E+09 1645.15 24-NOV-09:02 9.00
December 0.402269E+09 1683.56 07-DEC-09:02 6.67
         
Annual Sum or Average 0.100254E+10      
Minimum of Months 36558.03 165.97   5.90
Maximum of Months 0.402269E+09 1683.56   25.50



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 4.27
February 0.00 0.00 01-FEB-00:03 11.90
March 0.00 0.00 01-MAR-00:03 11.85
April 0.00 0.00 01-APR-00:10 15.28
May 0.00 0.00 01-MAY-00:10 19.10
June 0.00 0.00 01-JUN-00:10 25.83
July 0.00 0.00 01-JUL-00:10 27.73
August 0.00 0.00 01-AUG-00:10 29.40
September 0.00 0.00 01-SEP-00:10 26.22
October 0.00 0.00 01-OCT-00:10 25.15
November 0.00 0.00 01-NOV-00:10 17.23
December 0.00 0.00 01-DEC-00:03 9.20
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   4.27
Maximum of Months 0.00 0.00   29.40



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 2699136.89 464.64 24-JAN-09:03 15.83
February 2025924.01 536.24 26-FEB-16:03 16.17
March 1857577.40 423.95 11-MAR-16:04 15.78
April 492696.78 490.14 26-APR-08:04 24.33
May 513305.83 491.88 25-MAY-08:04 25.33
June 15690.43 78.47 05-JUN-08:07 30.17
July 18623.65 76.83 07-JUL-08:07 30.33
August 152803.76 344.33 07-AUG-08:05 23.50
September 237035.82 450.85 29-SEP-08:04 26.65
October 1154174.64 424.54 05-OCT-08:04 24.33
November 2011196.03 459.93 04-NOV-15:03 19.00
December 10647364.45 511.79 07-DEC-16:01 15.67
         
Annual Sum or Average 21825529.70      
Minimum of Months 15690.43 76.83   15.67
Maximum of Months 10647364.45 536.24   30.33



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 69543307.01 875.47 11-JAN-19:03 14.00
February 0.101740E+09 1518.56 12-FEB-16:02 14.00
March 79018353.85 839.36 25-MAR-18:03 13.43
April 270751.18 511.39 29-APR-08:04 24.33
May 50776.33 474.45 25-MAY-08:04 25.33
June 0.00 0.00 01-JUN-00:10 25.83
July 0.00 0.00 01-JUL-00:10 27.73
August 17669.46 176.44 04-AUG-08:05 22.33
September 133212.25 360.44 03-SEP-18:04 27.02
October 11197986.36 804.88 12-OCT-18:03 16.83
November 54846916.62 1092.01 25-NOV-16:03 17.00
December 0.203526E+09 1348.43 06-DEC-16:03 15.67
         
Annual Sum or Average 0.520345E+09      
Minimum of Months 0.00 0.00   13.43
Maximum of Months 0.203526E+09 1518.56   27.73



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.163802E+09 1545.09 01-JAN-19:02 11.03
February 0.162903E+09 1523.86 04-FEB-09:02 9.50
March 0.111941E+09 1155.81 12-MAR-15:03 16.18
April 561048.21 489.95 29-APR-08:04 24.33
May 53936.37 484.35 25-MAY-08:04 25.33
June 0.00 0.00 01-JUN-00:10 25.83
July 0.00 0.00 01-JUL-00:10 27.73
August 17600.56 176.01 04-AUG-08:05 22.33
September 187833.11 412.22 25-SEP-08:04 24.68
October 25305008.33 929.76 25-OCT-15:03 17.00
November 0.118668E+09 1510.53 23-NOV-19:02 8.83
December 0.375268E+09 1582.89 07-DEC-16:01 15.67
         
Annual Sum or Average 0.958708E+09      
Minimum of Months 0.00 0.00   8.83
Maximum of Months 0.375268E+09 1582.89   27.73



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 4.27
February 0.00 0.00 01-FEB-00:03 11.90
March 0.00 0.00 01-MAR-00:03 11.85
April 0.00 0.00 01-APR-00:10 15.28
May 0.00 0.00 01-MAY-00:10 19.10
June 0.00 0.00 01-JUN-00:10 25.83
July 0.00 0.00 01-JUL-00:10 27.73
August 0.00 0.00 01-AUG-00:10 29.40
September 0.00 0.00 01-SEP-00:10 26.22
October 0.00 0.00 01-OCT-00:10 25.15
November 0.00 0.00 01-NOV-00:10 17.23
December 24346.87 26.82 07-DEC-07:10 1.33
         
Annual Sum or Average 24346.87      
Minimum of Months 0.00 0.00   1.33
Maximum of Months 24346.87 26.82   29.40



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.141779E+09 1929.27 01-JAN-09:02 5.90
February 0.221976E+09 1895.67 08-FEB-09:02 10.17
March 0.159098E+09 1939.65 27-MAR-08:62 9.77
April 2563477.62 963.69 11-APR-08:03 23.33
May 637598.41 841.49 13-MAY-08:03 21.17
June 14970.24 121.74 01-JUN-08:04 28.37
July 179686.71 560.43 27-JUL-08:04 25.33
August 268654.33 573.45 05-AUG-08:04 23.33
September 666913.33 818.48 22-SEP-08:03 22.47
October 35864916.37 1846.06 25-OCT-08:62 8.50
November 0.107150E+09 1895.77 24-NOV-09:02 9.00
December 0.387391E+09 1947.31 07-DEC-09:02 6.67
         
Annual Sum or Average 0.105759E+10      
Minimum of Months 14970.24 121.74   5.90
Maximum of Months 0.387391E+09 1947.31   28.37



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.290588E+09 1977.94 01-JAN-09:02 5.90
February 0.343659E+09 1942.33 03-FEB-09:02 10.33
March 0.214676E+09 1951.87 27-MAR-08:62 9.77
April 3593829.53 923.47 11-APR-08:03 23.33
May 610931.87 747.99 13-MAY-08:03 21.17
June 6918.31 75.67 01-JUN-08:04 28.37
July 170076.35 531.39 27-JUL-08:04 25.33
August 304647.98 551.80 05-AUG-08:04 23.33
September 813373.11 777.57 22-SEP-08:03 22.47
October 64696752.68 1887.07 13-OCT-08:62 14.67
November 0.206351E+09 1956.89 24-NOV-09:02 9.00
December 0.667334E+09 1991.34 07-DEC-09:02 6.67
         
Annual Sum or Average 0.179280E+10      
Minimum of Months 6918.31 75.67   5.90
Maximum of Months 0.667334E+09 1991.34   28.37



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 6543813.45 433.97 02-JAN-09:03 12.50
February 20238517.37 844.94 12-FEB-16:02 14.00
March 26205832.89 998.28 27-MAR-08:62 9.77
April 722215.05 517.71 01-APR-08:03 20.67
May 706864.79 369.13 01-MAY-08:03 19.50
June 370918.80 372.71 12-JUN-08:04 27.33
July 419658.30 404.58 27-JUL-08:04 25.33
August 494617.00 431.13 29-AUG-08:04 26.67
September 430378.51 436.29 27-SEP-08:04 24.27
October 1231617.76 366.93 28-OCT-08:04 13.50
November 6776783.24 395.57 24-NOV-09:03 9.00
December 42044327.07 448.01 11-DEC-19:04 14.67
         
Annual Sum or Average 0.106186E+09      
Minimum of Months 370918.80 366.93   9.00
Maximum of Months 42044327.07 998.28   27.33



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 4.27
February 0.00 0.00 01-FEB-00:03 11.90
March 0.00 0.00 01-MAR-00:03 11.85
April 0.00 0.00 01-APR-00:10 15.28
May 0.00 0.00 01-MAY-00:10 19.10
June 0.00 0.00 01-JUN-00:10 25.83
July 0.00 0.00 01-JUL-00:10 27.73
August 0.00 0.00 01-AUG-00:10 29.40
September 0.00 0.00 01-SEP-00:10 26.22
October 0.00 0.00 01-OCT-00:10 25.15
November 0.00 0.00 01-NOV-00:10 17.23
December 0.00 0.00 01-DEC-00:03 9.20
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   4.27
Maximum of Months 0.00 0.00   29.40



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 4.27
February 0.00 0.00 01-FEB-00:03 11.90
March 0.00 0.00 01-MAR-00:03 11.85
April 0.00 0.00 01-APR-00:10 15.28
May 0.00 0.00 01-MAY-00:10 19.10
June 0.00 0.00 01-JUN-00:10 25.83
July 0.00 0.00 01-JUL-00:10 27.73
August 0.00 0.00 01-AUG-00:10 29.40
September 0.00 0.00 01-SEP-00:10 26.22
October 0.00 0.00 01-OCT-00:10 25.15
November 0.00 0.00 01-NOV-00:10 17.23
December 0.00 0.00 01-DEC-00:03 9.20
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   4.27
Maximum of Months 0.00 0.00   29.40



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 4.27
February 0.00 0.00 01-FEB-00:03 11.90
March 0.00 0.00 01-MAR-00:03 11.85
April 0.00 0.00 01-APR-00:10 15.28
May 0.00 0.00 01-MAY-00:10 19.10
June 0.00 0.00 01-JUN-00:10 25.83
July 0.00 0.00 01-JUL-00:10 27.73
August 0.00 0.00 01-AUG-00:10 29.40
September 0.00 0.00 01-SEP-00:10 26.22
October 0.00 0.00 01-OCT-00:10 25.15
November 0.00 0.00 01-NOV-00:10 17.23
December 0.00 0.00 01-DEC-00:03 9.20
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   4.27
Maximum of Months 0.00 0.00   29.40



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 35831620.38 1273.17 01-JAN-06:00 0.80
February 9088045.07 480.03 09-FEB-07:10 6.17
March 50554100.44 1252.03 27-MAR-06:10 1.97
April 0.00 0.00 01-APR-00:10 15.28
May 0.00 0.00 01-MAY-00:10 19.10
June 0.00 0.00 01-JUN-00:10 25.83
July 0.00 0.00 01-JUL-00:10 27.73
August 0.00 0.00 01-AUG-00:10 29.40
September 0.00 0.00 01-SEP-00:10 26.22
October 672241.45 213.66 26-OCT-06:30 8.50
November 21153865.84 1009.97 24-NOV-07:05 4.50
December 0.223144E+09 1743.91 06-DEC-07:20 -0.0
         
Annual Sum or Average 0.340444E+09      
Minimum of Months 0.00 0.00   -0.0
Maximum of Months 0.223144E+09 1743.91   29.40



Table of Contents

Report: ZoneElectricSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.140333E+11 13517.00 02-JAN-20:10 0.127587E+11 10113.80 02-JAN-20:10
February 0.126708E+11 13517.00 01-FEB-20:10 0.115208E+11 10113.80 01-FEB-20:10
March 0.140766E+11 13517.00 01-MAR-20:10 0.127855E+11 10113.80 01-MAR-20:10
April 0.135575E+11 13517.00 03-APR-19:10 0.123314E+11 10113.80 03-APR-19:10
May 0.140576E+11 13517.00 01-MAY-19:10 0.127741E+11 10113.80 01-MAY-19:10
June 0.136197E+11 13517.00 01-JUN-19:10 0.123716E+11 10113.80 01-JUN-19:10
July 0.139955E+11 13517.00 03-JUL-19:10 0.127338E+11 10113.80 03-JUL-19:10
August 0.140820E+11 13517.00 01-AUG-19:10 0.127894E+11 10113.80 01-AUG-19:10
September 0.135629E+11 13517.00 01-SEP-19:10 0.123352E+11 10113.80 01-SEP-19:10
October 0.140279E+11 13517.00 02-OCT-19:10 0.127549E+11 10113.80 02-OCT-19:10
November 0.136089E+11 13517.00 01-NOV-19:10 0.123659E+11 10113.80 01-NOV-19:10
December 0.139955E+11 13517.00 01-DEC-20:10 0.127338E+11 10113.80 01-DEC-20:10
             
Annual Sum or Average 0.165288E+12     0.150255E+12    
Minimum of Months 0.126708E+11 13517.00   0.115208E+11 10113.80  
Maximum of Months 0.140820E+11 13517.00   0.127894E+11 10113.80  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.713551E+09 687.30 02-JAN-20:10 0.864900E+09 685.60 02-JAN-20:10
February 0.644271E+09 687.30 01-FEB-20:10 0.780982E+09 685.60 01-FEB-20:10
March 0.715750E+09 687.30 01-MAR-20:10 0.866718E+09 685.60 01-MAR-20:10
April 0.689358E+09 687.30 03-APR-19:10 0.835931E+09 685.60 03-APR-19:10
May 0.714788E+09 687.30 01-MAY-19:10 0.865939E+09 685.60 01-MAY-19:10
June 0.692519E+09 687.30 01-JUN-19:10 0.838659E+09 685.60 01-JUN-19:10
July 0.711626E+09 687.30 03-JUL-19:10 0.863211E+09 685.60 03-JUL-19:10
August 0.716025E+09 687.30 01-AUG-19:10 0.866978E+09 685.60 01-AUG-19:10
September 0.689633E+09 687.30 01-SEP-19:10 0.836191E+09 685.60 01-SEP-19:10
October 0.713276E+09 687.30 02-OCT-19:10 0.864640E+09 685.60 02-OCT-19:10
November 0.691970E+09 687.30 01-NOV-19:10 0.838269E+09 685.60 01-NOV-19:10
December 0.711626E+09 687.30 01-DEC-20:10 0.863211E+09 685.60 01-DEC-20:10
             
Annual Sum or Average 0.840439E+10     0.101856E+11    
Minimum of Months 0.644271E+09 687.30   0.780982E+09 685.60  
Maximum of Months 0.716025E+09 687.30   0.866978E+09 685.60  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.826294E+09 795.89 02-JAN-20:10 0.100156E+10 793.93 02-JAN-20:10
February 0.746069E+09 795.89 01-FEB-20:10 0.904380E+09 793.93 01-FEB-20:10
March 0.828841E+09 795.89 01-MAR-20:10 0.100366E+10 793.93 01-MAR-20:10
April 0.798279E+09 795.89 03-APR-19:10 0.968011E+09 793.93 03-APR-19:10
May 0.827727E+09 795.89 01-MAY-19:10 0.100276E+10 793.93 01-MAY-19:10
June 0.801940E+09 795.89 01-JUN-19:10 0.971170E+09 793.93 01-JUN-19:10
July 0.824066E+09 795.89 03-JUL-19:10 0.999601E+09 793.93 03-JUL-19:10
August 0.829160E+09 795.89 01-AUG-19:10 0.100396E+10 793.93 01-AUG-19:10
September 0.798597E+09 795.89 01-SEP-19:10 0.968312E+09 793.93 01-SEP-19:10
October 0.825976E+09 795.89 02-OCT-19:10 0.100126E+10 793.93 02-OCT-19:10
November 0.801303E+09 795.89 01-NOV-19:10 0.970719E+09 793.93 01-NOV-19:10
December 0.824066E+09 795.89 01-DEC-20:10 0.999601E+09 793.93 01-DEC-20:10
             
Annual Sum or Average 0.973232E+10     0.117950E+11    
Minimum of Months 0.746069E+09 795.89   0.904380E+09 793.93  
Maximum of Months 0.829160E+09 795.89   0.100396E+10 793.93  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.154452E+10 1487.69 02-JAN-20:10 0.105898E+10 839.45 02-JAN-20:10
February 0.139456E+10 1487.69 01-FEB-20:10 0.956227E+09 839.45 01-FEB-20:10
March 0.154928E+10 1487.69 01-MAR-20:10 0.106120E+10 839.45 01-MAR-20:10
April 0.149215E+10 1487.69 03-APR-19:10 0.102351E+10 839.45 03-APR-19:10
May 0.154719E+10 1487.69 01-MAY-19:10 0.106025E+10 839.45 01-MAY-19:10
June 0.149899E+10 1487.69 01-JUN-19:10 0.102685E+10 839.45 01-JUN-19:10
July 0.154035E+10 1487.69 03-JUL-19:10 0.105691E+10 839.45 03-JUL-19:10
August 0.154987E+10 1487.69 01-AUG-19:10 0.106152E+10 839.45 01-AUG-19:10
September 0.149274E+10 1487.69 01-SEP-19:10 0.102382E+10 839.45 01-SEP-19:10
October 0.154392E+10 1487.69 02-OCT-19:10 0.105866E+10 839.45 02-OCT-19:10
November 0.149780E+10 1487.69 01-NOV-19:10 0.102637E+10 839.45 01-NOV-19:10
December 0.154035E+10 1487.69 01-DEC-20:10 0.105691E+10 839.45 01-DEC-20:10
             
Annual Sum or Average 0.181917E+11     0.124712E+11    
Minimum of Months 0.139456E+10 1487.69   0.956227E+09 839.45  
Maximum of Months 0.154987E+10 1487.69   0.106152E+10 839.45  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.283535E+09 273.10 02-JAN-20:10 0.305485E+09 242.16 02-JAN-20:10
February 0.256006E+09 273.10 01-FEB-20:10 0.275845E+09 242.16 01-FEB-20:10
March 0.284409E+09 273.10 01-MAR-20:10 0.306128E+09 242.16 01-MAR-20:10
April 0.273921E+09 273.10 03-APR-19:10 0.295253E+09 242.16 03-APR-19:10
May 0.284026E+09 273.10 01-MAY-19:10 0.305852E+09 242.16 01-MAY-19:10
June 0.275178E+09 273.10 01-JUN-19:10 0.296217E+09 242.16 01-JUN-19:10
July 0.282770E+09 273.10 03-JUL-19:10 0.304889E+09 242.16 03-JUL-19:10
August 0.284518E+09 273.10 01-AUG-19:10 0.306219E+09 242.16 01-AUG-19:10
September 0.274031E+09 273.10 01-SEP-19:10 0.295345E+09 242.16 01-SEP-19:10
October 0.283425E+09 273.10 02-OCT-19:10 0.305393E+09 242.16 02-OCT-19:10
November 0.274959E+09 273.10 01-NOV-19:10 0.296079E+09 242.16 01-NOV-19:10
December 0.282770E+09 273.10 01-DEC-20:10 0.304889E+09 242.16 01-DEC-20:10
             
Annual Sum or Average 0.333955E+10     0.359760E+10    
Minimum of Months 0.256006E+09 273.10   0.275845E+09 242.16  
Maximum of Months 0.284518E+09 273.10   0.306219E+09 242.16  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.350256E+09 337.37 02-JAN-20:10 0.576866E+10 4572.80 02-JAN-20:10
February 0.316249E+09 337.37 01-FEB-20:10 0.520895E+10 4572.80 01-FEB-20:10
March 0.351336E+09 337.37 01-MAR-20:10 0.578079E+10 4572.80 01-MAR-20:10
April 0.338381E+09 337.37 03-APR-19:10 0.557545E+10 4572.80 03-APR-19:10
May 0.350863E+09 337.37 01-MAY-19:10 0.577559E+10 4572.80 01-MAY-19:10
June 0.339933E+09 337.37 01-JUN-19:10 0.559364E+10 4572.80 01-JUN-19:10
July 0.349311E+09 337.37 03-JUL-19:10 0.575740E+10 4572.80 03-JUL-19:10
August 0.351471E+09 337.37 01-AUG-19:10 0.578252E+10 4572.80 01-AUG-19:10
September 0.338516E+09 337.37 01-SEP-19:10 0.557718E+10 4572.80 01-SEP-19:10
October 0.350121E+09 337.37 02-OCT-19:10 0.576693E+10 4572.80 02-OCT-19:10
November 0.339663E+09 337.37 01-NOV-19:10 0.559104E+10 4572.80 01-NOV-19:10
December 0.349311E+09 337.37 01-DEC-20:10 0.575740E+10 4572.80 01-DEC-20:10
             
Annual Sum or Average 0.412541E+10     0.679355E+11    
Minimum of Months 0.316249E+09 337.37   0.520895E+10 4572.80  
Maximum of Months 0.351471E+09 337.37   0.578252E+10 4572.80  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.226040E+10 2177.23 02-JAN-20:10 0.121771E+10 965.27 02-JAN-20:10
February 0.204093E+10 2177.23 01-FEB-20:10 0.109956E+10 965.27 01-FEB-20:10
March 0.226736E+10 2177.23 01-MAR-20:10 0.122027E+10 965.27 01-MAR-20:10
April 0.218376E+10 2177.23 03-APR-19:10 0.117692E+10 965.27 03-APR-19:10
May 0.226431E+10 2177.23 01-MAY-19:10 0.121917E+10 965.27 01-MAY-19:10
June 0.219377E+10 2177.23 01-JUN-19:10 0.118076E+10 965.27 01-JUN-19:10
July 0.225430E+10 2177.23 03-JUL-19:10 0.121533E+10 965.27 03-JUL-19:10
August 0.226823E+10 2177.23 01-AUG-19:10 0.122063E+10 965.27 01-AUG-19:10
September 0.218463E+10 2177.23 01-SEP-19:10 0.117729E+10 965.27 01-SEP-19:10
October 0.225952E+10 2177.23 02-OCT-19:10 0.121734E+10 965.27 02-OCT-19:10
November 0.219203E+10 2177.23 01-NOV-19:10 0.118021E+10 965.27 01-NOV-19:10
December 0.225430E+10 2177.23 01-DEC-20:10 0.121533E+10 965.27 01-DEC-20:10
             
Annual Sum or Average 0.266236E+11     0.143405E+11    
Minimum of Months 0.204093E+10 2177.23   0.109956E+10 965.27  
Maximum of Months 0.226823E+10 2177.23   0.122063E+10 965.27  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.123020E+11 11849.32 02-JAN-20:10 0.126520E+11 10029.21 02-JAN-20:10
February 0.111075E+11 11849.32 01-FEB-20:10 0.114244E+11 10029.21 01-FEB-20:10
March 0.123399E+11 11849.32 01-MAR-20:10 0.126786E+11 10029.21 01-MAR-20:10
April 0.118849E+11 11849.32 03-APR-19:10 0.122282E+11 10029.21 03-APR-19:10
May 0.123233E+11 11849.32 01-MAY-19:10 0.126672E+11 10029.21 01-MAY-19:10
June 0.119394E+11 11849.32 01-JUN-19:10 0.122682E+11 10029.21 01-JUN-19:10
July 0.122688E+11 11849.32 03-JUL-19:10 0.126273E+11 10029.21 03-JUL-19:10
August 0.123446E+11 11849.32 01-AUG-19:10 0.126824E+11 10029.21 01-AUG-19:10
September 0.118896E+11 11849.32 01-SEP-19:10 0.122320E+11 10029.21 01-SEP-19:10
October 0.122972E+11 11849.32 02-OCT-19:10 0.126482E+11 10029.21 02-OCT-19:10
November 0.119299E+11 11849.32 01-NOV-19:10 0.122624E+11 10029.21 01-NOV-19:10
December 0.122688E+11 11849.32 01-DEC-20:10 0.126273E+11 10029.21 01-DEC-20:10
             
Annual Sum or Average 0.144896E+12     0.148998E+12    
Minimum of Months 0.111075E+11 11849.32   0.114244E+11 10029.21  
Maximum of Months 0.123446E+11 11849.32   0.126824E+11 10029.21  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.434056E+09 392.73 01-JAN-19:10 0.261068E+09 237.06 01-JAN-08:09
February 0.391995E+09 392.73 01-FEB-20:10 0.235798E+09 237.06 01-FEB-07:10
March 0.430607E+09 392.73 01-MAR-20:10 0.260708E+09 237.06 01-MAR-07:10
April 0.420554E+09 392.73 01-APR-18:10 0.252705E+09 237.06 01-APR-07:10
May 0.432331E+09 392.73 01-MAY-19:10 0.260888E+09 237.06 01-MAY-06:10
June 0.417218E+09 392.73 01-JUN-19:10 0.252344E+09 237.06 01-JUN-06:10
July 0.435725E+09 392.73 01-JUL-18:10 0.261248E+09 237.06 01-JUL-07:10
August 0.430607E+09 392.73 01-AUG-19:10 0.260708E+09 237.06 01-AUG-06:10
September 0.420667E+09 392.73 01-SEP-19:10 0.252705E+09 237.06 01-SEP-06:10
October 0.434000E+09 392.73 01-OCT-18:10 0.261068E+09 237.06 01-OCT-07:10
November 0.418886E+09 392.73 01-NOV-19:10 0.252524E+09 237.06 01-NOV-06:10
December 0.435781E+09 392.73 01-DEC-20:10 0.261248E+09 237.06 01-DEC-07:10
             
Annual Sum or Average 0.510243E+10     0.307301E+10    
Minimum of Months 0.391995E+09 392.73   0.235798E+09 237.06  
Maximum of Months 0.435781E+09 392.73   0.261248E+09 237.06  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.434005E+09 392.68 01-JAN-19:10 0.261038E+09 237.03 01-JAN-08:09
February 0.391949E+09 392.68 01-FEB-20:10 0.235770E+09 237.03 01-FEB-07:10
March 0.430556E+09 392.68 01-MAR-20:10 0.260677E+09 237.03 01-MAR-07:10
April 0.420505E+09 392.68 01-APR-18:10 0.252675E+09 237.03 01-APR-07:10
May 0.432281E+09 392.68 01-MAY-19:10 0.260857E+09 237.03 01-MAY-06:10
June 0.417169E+09 392.68 01-JUN-19:10 0.252315E+09 237.03 01-JUN-06:10
July 0.435674E+09 392.68 01-JUL-18:10 0.261218E+09 237.03 01-JUL-07:10
August 0.430556E+09 392.68 01-AUG-19:10 0.260677E+09 237.03 01-AUG-06:10
September 0.420618E+09 392.68 01-SEP-19:10 0.252675E+09 237.03 01-SEP-06:10
October 0.433949E+09 392.68 01-OCT-18:10 0.261038E+09 237.03 01-OCT-07:10
November 0.418837E+09 392.68 01-NOV-19:10 0.252495E+09 237.03 01-NOV-06:10
December 0.435730E+09 392.68 01-DEC-20:10 0.261218E+09 237.03 01-DEC-07:10
             
Annual Sum or Average 0.510183E+10     0.307265E+10    
Minimum of Months 0.391949E+09 392.68   0.235770E+09 237.03  
Maximum of Months 0.435730E+09 392.68   0.261218E+09 237.03  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.272788E+09 246.81 01-JAN-19:10 0.255708E+09 232.19 01-JAN-08:09
February 0.246354E+09 246.81 01-FEB-20:10 0.230956E+09 232.19 01-FEB-07:10
March 0.270620E+09 246.81 01-MAR-20:10 0.255355E+09 232.19 01-MAR-07:10
April 0.264302E+09 246.81 01-APR-18:10 0.247516E+09 232.19 01-APR-07:10
May 0.271704E+09 246.81 01-MAY-19:10 0.255532E+09 232.19 01-MAY-06:10
June 0.262205E+09 246.81 01-JUN-19:10 0.247163E+09 232.19 01-JUN-06:10
July 0.273836E+09 246.81 01-JUL-18:10 0.255885E+09 232.19 01-JUL-07:10
August 0.270620E+09 246.81 01-AUG-19:10 0.255355E+09 232.19 01-AUG-06:10
September 0.264373E+09 246.81 01-SEP-19:10 0.247516E+09 232.19 01-SEP-06:10
October 0.272752E+09 246.81 01-OCT-18:10 0.255708E+09 232.19 01-OCT-07:10
November 0.263254E+09 246.81 01-NOV-19:10 0.247340E+09 232.19 01-NOV-06:10
December 0.273872E+09 246.81 01-DEC-20:10 0.255885E+09 232.19 01-DEC-07:10
             
Annual Sum or Average 0.320668E+10     0.300992E+10    
Minimum of Months 0.246354E+09 246.81   0.230956E+09 232.19  
Maximum of Months 0.273872E+09 246.81   0.255885E+09 232.19  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.272862E+09 246.88 01-JAN-19:10 0.255778E+09 232.26 01-JAN-08:09
February 0.246421E+09 246.88 01-FEB-20:10 0.231020E+09 232.26 01-FEB-07:10
March 0.270694E+09 246.88 01-MAR-20:10 0.255425E+09 232.26 01-MAR-07:10
April 0.264375E+09 246.88 01-APR-18:10 0.247584E+09 232.26 01-APR-07:10
May 0.271778E+09 246.88 01-MAY-19:10 0.255602E+09 232.26 01-MAY-06:10
June 0.262277E+09 246.88 01-JUN-19:10 0.247231E+09 232.26 01-JUN-06:10
July 0.273911E+09 246.88 01-JUL-18:10 0.255955E+09 232.26 01-JUL-07:10
August 0.270694E+09 246.88 01-AUG-19:10 0.255425E+09 232.26 01-AUG-06:10
September 0.264446E+09 246.88 01-SEP-19:10 0.247584E+09 232.26 01-SEP-06:10
October 0.272827E+09 246.88 01-OCT-18:10 0.255778E+09 232.26 01-OCT-07:10
November 0.263326E+09 246.88 01-NOV-19:10 0.247408E+09 232.26 01-NOV-06:10
December 0.273947E+09 246.88 01-DEC-20:10 0.255955E+09 232.26 01-DEC-07:10
             
Annual Sum or Average 0.320756E+10     0.301074E+10    
Minimum of Months 0.246421E+09 246.88   0.231020E+09 232.26  
Maximum of Months 0.273947E+09 246.88   0.255955E+09 232.26  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.434056E+09 392.73 01-JAN-19:10 0.261068E+09 237.06 01-JAN-08:09
February 0.391995E+09 392.73 01-FEB-20:10 0.235798E+09 237.06 01-FEB-07:10
March 0.430607E+09 392.73 01-MAR-20:10 0.260708E+09 237.06 01-MAR-07:10
April 0.420554E+09 392.73 01-APR-18:10 0.252705E+09 237.06 01-APR-07:10
May 0.432331E+09 392.73 01-MAY-19:10 0.260888E+09 237.06 01-MAY-06:10
June 0.417218E+09 392.73 01-JUN-19:10 0.252344E+09 237.06 01-JUN-06:10
July 0.435725E+09 392.73 01-JUL-18:10 0.261248E+09 237.06 01-JUL-07:10
August 0.430607E+09 392.73 01-AUG-19:10 0.260708E+09 237.06 01-AUG-06:10
September 0.420667E+09 392.73 01-SEP-19:10 0.252705E+09 237.06 01-SEP-06:10
October 0.434000E+09 392.73 01-OCT-18:10 0.261068E+09 237.06 01-OCT-07:10
November 0.418886E+09 392.73 01-NOV-19:10 0.252524E+09 237.06 01-NOV-06:10
December 0.435781E+09 392.73 01-DEC-20:10 0.261248E+09 237.06 01-DEC-07:10
             
Annual Sum or Average 0.510243E+10     0.307301E+10    
Minimum of Months 0.391995E+09 392.73   0.235798E+09 237.06  
Maximum of Months 0.435781E+09 392.73   0.261248E+09 237.06  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.434005E+09 392.68 01-JAN-19:10 0.261038E+09 237.03 01-JAN-08:09
February 0.391949E+09 392.68 01-FEB-20:10 0.235770E+09 237.03 01-FEB-07:10
March 0.430556E+09 392.68 01-MAR-20:10 0.260677E+09 237.03 01-MAR-07:10
April 0.420505E+09 392.68 01-APR-18:10 0.252675E+09 237.03 01-APR-07:10
May 0.432281E+09 392.68 01-MAY-19:10 0.260857E+09 237.03 01-MAY-06:10
June 0.417169E+09 392.68 01-JUN-19:10 0.252315E+09 237.03 01-JUN-06:10
July 0.435674E+09 392.68 01-JUL-18:10 0.261218E+09 237.03 01-JUL-07:10
August 0.430556E+09 392.68 01-AUG-19:10 0.260677E+09 237.03 01-AUG-06:10
September 0.420618E+09 392.68 01-SEP-19:10 0.252675E+09 237.03 01-SEP-06:10
October 0.433949E+09 392.68 01-OCT-18:10 0.261038E+09 237.03 01-OCT-07:10
November 0.418837E+09 392.68 01-NOV-19:10 0.252495E+09 237.03 01-NOV-06:10
December 0.435730E+09 392.68 01-DEC-20:10 0.261218E+09 237.03 01-DEC-07:10
             
Annual Sum or Average 0.510183E+10     0.307265E+10    
Minimum of Months 0.391949E+09 392.68   0.235770E+09 237.03  
Maximum of Months 0.435730E+09 392.68   0.261218E+09 237.03  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY []
January 0.133160E+10 1282.60 02-JAN-20:10 0.00 0.00
February 0.120231E+10 1282.60 01-FEB-20:10 0.00 0.00
March 0.133570E+10 1282.60 01-MAR-20:10 0.00 0.00
April 0.128645E+10 1282.60 03-APR-19:10 0.00 0.00
May 0.133391E+10 1282.60 01-MAY-19:10 0.00 0.00
June 0.129235E+10 1282.60 01-JUN-19:10 0.00 0.00
July 0.132801E+10 1282.60 03-JUL-19:10 0.00 0.00
August 0.133622E+10 1282.60 01-AUG-19:10 0.00 0.00
September 0.128696E+10 1282.60 01-SEP-19:10 0.00 0.00
October 0.133109E+10 1282.60 02-OCT-19:10 0.00 0.00
November 0.129132E+10 1282.60 01-NOV-19:10 0.00 0.00
December 0.132801E+10 1282.60 01-DEC-20:10 0.00 0.00
           
Annual Sum or Average 0.156839E+11     0.00 0.00
Minimum of Months 0.120231E+10 1282.60   0.00 0.00
Maximum of Months 0.133622E+10 1282.60   0.00 0.00



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.434056E+09 392.73 01-JAN-19:10 0.261068E+09 237.06 01-JAN-08:09
February 0.391995E+09 392.73 01-FEB-20:10 0.235798E+09 237.06 01-FEB-07:10
March 0.430607E+09 392.73 01-MAR-20:10 0.260708E+09 237.06 01-MAR-07:10
April 0.420554E+09 392.73 01-APR-18:10 0.252705E+09 237.06 01-APR-07:10
May 0.432331E+09 392.73 01-MAY-19:10 0.260888E+09 237.06 01-MAY-06:10
June 0.417218E+09 392.73 01-JUN-19:10 0.252344E+09 237.06 01-JUN-06:10
July 0.435725E+09 392.73 01-JUL-18:10 0.261248E+09 237.06 01-JUL-07:10
August 0.430607E+09 392.73 01-AUG-19:10 0.260708E+09 237.06 01-AUG-06:10
September 0.420667E+09 392.73 01-SEP-19:10 0.252705E+09 237.06 01-SEP-06:10
October 0.434000E+09 392.73 01-OCT-18:10 0.261068E+09 237.06 01-OCT-07:10
November 0.418886E+09 392.73 01-NOV-19:10 0.252524E+09 237.06 01-NOV-06:10
December 0.435781E+09 392.73 01-DEC-20:10 0.261248E+09 237.06 01-DEC-07:10
             
Annual Sum or Average 0.510243E+10     0.307301E+10    
Minimum of Months 0.391995E+09 392.73   0.235798E+09 237.06  
Maximum of Months 0.435781E+09 392.73   0.261248E+09 237.06  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.434005E+09 392.68 01-JAN-19:10 0.261038E+09 237.03 01-JAN-08:09
February 0.391949E+09 392.68 01-FEB-20:10 0.235770E+09 237.03 01-FEB-07:10
March 0.430556E+09 392.68 01-MAR-20:10 0.260677E+09 237.03 01-MAR-07:10
April 0.420505E+09 392.68 01-APR-18:10 0.252675E+09 237.03 01-APR-07:10
May 0.432281E+09 392.68 01-MAY-19:10 0.260857E+09 237.03 01-MAY-06:10
June 0.417169E+09 392.68 01-JUN-19:10 0.252315E+09 237.03 01-JUN-06:10
July 0.435674E+09 392.68 01-JUL-18:10 0.261218E+09 237.03 01-JUL-07:10
August 0.430556E+09 392.68 01-AUG-19:10 0.260677E+09 237.03 01-AUG-06:10
September 0.420618E+09 392.68 01-SEP-19:10 0.252675E+09 237.03 01-SEP-06:10
October 0.433949E+09 392.68 01-OCT-18:10 0.261038E+09 237.03 01-OCT-07:10
November 0.418837E+09 392.68 01-NOV-19:10 0.252495E+09 237.03 01-NOV-06:10
December 0.435730E+09 392.68 01-DEC-20:10 0.261218E+09 237.03 01-DEC-07:10
             
Annual Sum or Average 0.510183E+10     0.307265E+10    
Minimum of Months 0.391949E+09 392.68   0.235770E+09 237.03  
Maximum of Months 0.435730E+09 392.68   0.261218E+09 237.03  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.272862E+09 246.88 01-JAN-19:10 0.255778E+09 232.26 01-JAN-08:09
February 0.246421E+09 246.88 01-FEB-20:10 0.231020E+09 232.26 01-FEB-07:10
March 0.270694E+09 246.88 01-MAR-20:10 0.255425E+09 232.26 01-MAR-07:10
April 0.264375E+09 246.88 01-APR-18:10 0.247584E+09 232.26 01-APR-07:10
May 0.271778E+09 246.88 01-MAY-19:10 0.255602E+09 232.26 01-MAY-06:10
June 0.262277E+09 246.88 01-JUN-19:10 0.247231E+09 232.26 01-JUN-06:10
July 0.273911E+09 246.88 01-JUL-18:10 0.255955E+09 232.26 01-JUL-07:10
August 0.270694E+09 246.88 01-AUG-19:10 0.255425E+09 232.26 01-AUG-06:10
September 0.264446E+09 246.88 01-SEP-19:10 0.247584E+09 232.26 01-SEP-06:10
October 0.272827E+09 246.88 01-OCT-18:10 0.255778E+09 232.26 01-OCT-07:10
November 0.263326E+09 246.88 01-NOV-19:10 0.247408E+09 232.26 01-NOV-06:10
December 0.273947E+09 246.88 01-DEC-20:10 0.255955E+09 232.26 01-DEC-07:10
             
Annual Sum or Average 0.320756E+10     0.301074E+10    
Minimum of Months 0.246421E+09 246.88   0.231020E+09 232.26  
Maximum of Months 0.273947E+09 246.88   0.255955E+09 232.26  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.396945E+10 3823.39 02-JAN-20:10 0.149358E+11 6747.90 01-JAN-07:10
February 0.358405E+10 3823.39 01-FEB-20:10 0.134904E+11 6747.90 01-FEB-07:10
March 0.398168E+10 3823.39 01-MAR-20:10 0.149358E+11 6747.90 01-MAR-07:10
April 0.383486E+10 3823.39 03-APR-19:10 0.144540E+11 6747.90 01-APR-06:10
May 0.397633E+10 3823.39 01-MAY-19:10 0.149358E+11 6747.90 01-MAY-06:10
June 0.385245E+10 3823.39 01-JUN-19:10 0.144540E+11 6747.90 01-JUN-06:10
July 0.395874E+10 3823.39 03-JUL-19:10 0.149358E+11 6747.90 01-JUL-06:10
August 0.398321E+10 3823.39 01-AUG-19:10 0.149358E+11 6747.90 01-AUG-06:10
September 0.383639E+10 3823.39 01-SEP-19:10 0.144540E+11 6747.90 01-SEP-06:10
October 0.396792E+10 3823.39 02-OCT-19:10 0.149358E+11 6747.90 01-OCT-06:10
November 0.384939E+10 3823.39 01-NOV-19:10 0.144540E+11 6747.90 01-NOV-06:10
December 0.395874E+10 3823.39 01-DEC-20:10 0.149358E+11 6747.90 01-DEC-07:10
             
Annual Sum or Average 0.467532E+11     0.175857E+12    
Minimum of Months 0.358405E+10 3823.39   0.134904E+11 6747.90  
Maximum of Months 0.398321E+10 3823.39   0.149358E+11 6747.90  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.396945E+10 3823.39 02-JAN-20:10 0.149358E+11 6747.90 01-JAN-07:10
February 0.358405E+10 3823.39 01-FEB-20:10 0.134904E+11 6747.90 01-FEB-07:10
March 0.398168E+10 3823.39 01-MAR-20:10 0.149358E+11 6747.90 01-MAR-07:10
April 0.383486E+10 3823.39 03-APR-19:10 0.144540E+11 6747.90 01-APR-06:10
May 0.397633E+10 3823.39 01-MAY-19:10 0.149358E+11 6747.90 01-MAY-06:10
June 0.385245E+10 3823.39 01-JUN-19:10 0.144540E+11 6747.90 01-JUN-06:10
July 0.395874E+10 3823.39 03-JUL-19:10 0.149358E+11 6747.90 01-JUL-06:10
August 0.398321E+10 3823.39 01-AUG-19:10 0.149358E+11 6747.90 01-AUG-06:10
September 0.383639E+10 3823.39 01-SEP-19:10 0.144540E+11 6747.90 01-SEP-06:10
October 0.396792E+10 3823.39 02-OCT-19:10 0.149358E+11 6747.90 01-OCT-06:10
November 0.384939E+10 3823.39 01-NOV-19:10 0.144540E+11 6747.90 01-NOV-06:10
December 0.395874E+10 3823.39 01-DEC-20:10 0.149358E+11 6747.90 01-DEC-07:10
             
Annual Sum or Average 0.467532E+11     0.175857E+12    
Minimum of Months 0.358405E+10 3823.39   0.134904E+11 6747.90  
Maximum of Months 0.398321E+10 3823.39   0.149358E+11 6747.90  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.105977E+10 1020.78 02-JAN-20:10 0.373720E+11 16686.59 01-JAN-07:10
February 0.956878E+09 1020.78 01-FEB-20:10 0.337554E+11 16686.59 01-FEB-07:10
March 0.106304E+10 1020.78 01-MAR-20:10 0.373720E+11 16686.59 01-MAR-07:10
April 0.102384E+10 1020.78 03-APR-19:10 0.361665E+11 16686.59 01-APR-06:10
May 0.106161E+10 1020.78 01-MAY-19:10 0.373720E+11 16686.59 01-MAY-06:10
June 0.102854E+10 1020.78 01-JUN-19:10 0.361665E+11 16686.59 01-JUN-06:10
July 0.105691E+10 1020.78 03-JUL-19:10 0.373720E+11 16686.59 01-JUL-06:10
August 0.106345E+10 1020.78 01-AUG-19:10 0.373720E+11 16686.59 01-AUG-06:10
September 0.102425E+10 1020.78 01-SEP-19:10 0.361665E+11 16686.59 01-SEP-06:10
October 0.105936E+10 1020.78 02-OCT-19:10 0.373720E+11 16686.59 01-OCT-06:10
November 0.102772E+10 1020.78 01-NOV-19:10 0.361665E+11 16686.59 01-NOV-06:10
December 0.105691E+10 1020.78 01-DEC-20:10 0.373720E+11 16686.59 01-DEC-07:10
             
Annual Sum or Average 0.124823E+11     0.440025E+12    
Minimum of Months 0.956878E+09 1020.78   0.337554E+11 16686.59  
Maximum of Months 0.106345E+10 1020.78   0.373720E+11 16686.59  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY []
January 0.140929E+10 1357.44 02-JAN-20:10 0.00 0.00
February 0.127246E+10 1357.44 01-FEB-20:10 0.00 0.00
March 0.141364E+10 1357.44 01-MAR-20:10 0.00 0.00
April 0.136151E+10 1357.44 03-APR-19:10 0.00 0.00
May 0.141173E+10 1357.44 01-MAY-19:10 0.00 0.00
June 0.136775E+10 1357.44 01-JUN-19:10 0.00 0.00
July 0.140549E+10 1357.44 03-JUL-19:10 0.00 0.00
August 0.141418E+10 1357.44 01-AUG-19:10 0.00 0.00
September 0.136205E+10 1357.44 01-SEP-19:10 0.00 0.00
October 0.140875E+10 1357.44 02-OCT-19:10 0.00 0.00
November 0.136667E+10 1357.44 01-NOV-19:10 0.00 0.00
December 0.140549E+10 1357.44 01-DEC-20:10 0.00 0.00
           
Annual Sum or Average 0.165990E+11     0.00 0.00
Minimum of Months 0.127246E+10 1357.44   0.00 0.00
Maximum of Months 0.141418E+10 1357.44   0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.195762E+11 0.140333E+11 0.127587E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.176991E+11 0.126708E+11 0.115208E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.196682E+11 0.140766E+11 0.127855E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.189781E+11 0.135575E+11 0.123314E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.196176E+11 0.140576E+11 0.127741E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.190195E+11 0.136197E+11 0.123716E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.195762E+11 0.139955E+11 0.127338E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.196590E+11 0.140820E+11 0.127894E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.189689E+11 0.135629E+11 0.123352E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.195854E+11 0.140279E+11 0.127549E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.189367E+11 0.136089E+11 0.123659E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.195762E+11 0.139955E+11 0.127338E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.230861E+12 0.165288E+12 0.150255E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.176991E+11 0.126708E+11 0.115208E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.196682E+11 0.140820E+11 0.127894E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.199054E+10 0.713551E+09 0.864900E+09 0.00 0.00 0.00 0.00 12921511.87 0.363374E+09
February 0.179968E+10 0.644271E+09 0.780982E+09 0.00 0.00 0.00 0.00 189566.21 0.403696E+09
March 0.199990E+10 0.715750E+09 0.866718E+09 0.00 0.00 0.00 0.00 27446180.71 0.330098E+09
April 0.192973E+10 0.689358E+09 0.835931E+09 0.00 0.00 0.00 0.00 0.184076E+09 83288529.97
May 0.199475E+10 0.714788E+09 0.865939E+09 0.00 0.00 0.00 0.00 0.291613E+09 31360973.26
June 0.193394E+10 0.692519E+09 0.838659E+09 0.00 0.00 0.00 0.00 0.476080E+09 1441011.85
July 0.199054E+10 0.711626E+09 0.863211E+09 0.00 0.00 0.00 0.00 0.461318E+09 1166489.54
August 0.199896E+10 0.716025E+09 0.866978E+09 0.00 0.00 0.00 0.00 0.425930E+09 1227795.35
September 0.192879E+10 0.689633E+09 0.836191E+09 0.00 0.00 0.00 0.00 0.316478E+09 4674109.50
October 0.199148E+10 0.713276E+09 0.864640E+09 0.00 0.00 0.00 0.00 0.122387E+09 0.153328E+09
November 0.192552E+10 0.691970E+09 0.838269E+09 0.00 0.00 0.00 0.00 17722544.82 0.320520E+09
December 0.199054E+10 0.711626E+09 0.863211E+09 0.00 0.00 0.00 0.00 4251177.77 0.509589E+09
                   
Annual Sum or Average 0.234744E+11 0.840439E+10 0.101856E+11 0.00 0.00 0.00 0.00 0.234041E+10 0.220376E+10
Minimum of Months 0.179968E+10 0.644271E+09 0.780982E+09 0.00 0.00 0.00 0.00 189566.21 1166489.54
Maximum of Months 0.199990E+10 0.716025E+09 0.866978E+09 0.00 0.00 0.00 0.00 0.476080E+09 0.509589E+09



Table of Contents

Report: SpaceGainsMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.230505E+10 0.826294E+09 0.100156E+10 0.00 0.00 0.00 0.00 9013920.52 0.139092E+09
February 0.208403E+10 0.746069E+09 0.904380E+09 0.00 0.00 0.00 0.00 73267.20 0.155202E+09
March 0.231589E+10 0.828841E+09 0.100366E+10 0.00 0.00 0.00 0.00 11143827.17 0.128129E+09
April 0.223463E+10 0.798279E+09 0.968011E+09 0.00 0.00 0.00 0.00 71988520.10 33247300.17
May 0.230993E+10 0.827727E+09 0.100276E+10 0.00 0.00 0.00 0.00 0.110735E+09 12852222.71
June 0.223950E+10 0.801940E+09 0.971170E+09 0.00 0.00 0.00 0.00 0.182017E+09 796599.90
July 0.230505E+10 0.824066E+09 0.999601E+09 0.00 0.00 0.00 0.00 0.176323E+09 602012.67
August 0.231480E+10 0.829160E+09 0.100396E+10 0.00 0.00 0.00 0.00 0.164573E+09 594544.58
September 0.223354E+10 0.798597E+09 0.968312E+09 0.00 0.00 0.00 0.00 0.124107E+09 2013909.98
October 0.230614E+10 0.825976E+09 0.100126E+10 0.00 0.00 0.00 0.00 51766604.61 60022810.37
November 0.222975E+10 0.801303E+09 0.970719E+09 0.00 0.00 0.00 0.00 9685946.30 0.122843E+09
December 0.230505E+10 0.824066E+09 0.999601E+09 0.00 0.00 0.00 0.00 3153904.08 0.194821E+09
                   
Annual Sum or Average 0.271834E+11 0.973232E+10 0.117950E+11 0.00 0.00 0.00 0.00 0.914581E+09 0.850217E+09
Minimum of Months 0.208403E+10 0.746069E+09 0.904380E+09 0.00 0.00 0.00 0.00 73267.20 594544.58
Maximum of Months 0.231589E+10 0.829160E+09 0.100396E+10 0.00 0.00 0.00 0.00 0.182017E+09 0.194821E+09



Table of Contents

Report: SpaceGainsMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.487480E+09 0.154452E+10 0.105898E+10 0.00 0.00 0.00 0.00 21308445.26 0.326495E+09
February 0.440737E+09 0.139456E+10 0.956227E+09 0.00 0.00 0.00 0.00 173167.40 0.365893E+09
March 0.489771E+09 0.154928E+10 0.106120E+10 0.00 0.00 0.00 0.00 26492868.00 0.300914E+09
April 0.472586E+09 0.149215E+10 0.102351E+10 0.00 0.00 0.00 0.00 0.173857E+09 76115772.60
May 0.488511E+09 0.154719E+10 0.106025E+10 0.00 0.00 0.00 0.00 0.266504E+09 28621377.76
June 0.473617E+09 0.149899E+10 0.102685E+10 0.00 0.00 0.00 0.00 0.433883E+09 1447483.22
July 0.487480E+09 0.154035E+10 0.105691E+10 0.00 0.00 0.00 0.00 0.419813E+09 1274848.97
August 0.489542E+09 0.154987E+10 0.106152E+10 0.00 0.00 0.00 0.00 0.394925E+09 1155414.74
September 0.472357E+09 0.149274E+10 0.102382E+10 0.00 0.00 0.00 0.00 0.298944E+09 4295491.22
October 0.487709E+09 0.154392E+10 0.105866E+10 0.00 0.00 0.00 0.00 0.124395E+09 0.139184E+09
November 0.471555E+09 0.149780E+10 0.102637E+10 0.00 0.00 0.00 0.00 22952778.67 0.288022E+09
December 0.487480E+09 0.154035E+10 0.105691E+10 0.00 0.00 0.00 0.00 7454357.09 0.459462E+09
                   
Annual Sum or Average 0.574883E+10 0.181917E+11 0.124712E+11 0.00 0.00 0.00 0.00 0.219070E+10 0.199288E+10
Minimum of Months 0.440737E+09 0.139456E+10 0.956227E+09 0.00 0.00 0.00 0.00 173167.40 1155414.74
Maximum of Months 0.489771E+09 0.154987E+10 0.106152E+10 0.00 0.00 0.00 0.00 0.433883E+09 0.459462E+09



Table of Contents

Report: SpaceGainsMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.374985E+09 0.283535E+09 0.305485E+09 0.00 0.00 0.00 0.00 12293771.44 0.188369E+09
February 0.339028E+09 0.256006E+09 0.275845E+09 0.00 0.00 0.00 0.00 99903.17 0.211102E+09
March 0.376747E+09 0.284409E+09 0.306128E+09 0.00 0.00 0.00 0.00 15299254.19 0.173583E+09
April 0.363528E+09 0.273921E+09 0.295253E+09 0.00 0.00 0.00 0.00 0.100974E+09 43824201.26
May 0.375778E+09 0.284026E+09 0.305852E+09 0.00 0.00 0.00 0.00 0.155180E+09 16500301.54
June 0.364321E+09 0.275178E+09 0.296217E+09 0.00 0.00 0.00 0.00 0.252507E+09 790027.15
July 0.374985E+09 0.282770E+09 0.304889E+09 0.00 0.00 0.00 0.00 0.244295E+09 679076.43
August 0.376571E+09 0.284518E+09 0.306219E+09 0.00 0.00 0.00 0.00 0.229736E+09 646745.63
September 0.363352E+09 0.274031E+09 0.295345E+09 0.00 0.00 0.00 0.00 0.174028E+09 2460205.68
October 0.375161E+09 0.283425E+09 0.305393E+09 0.00 0.00 0.00 0.00 72187755.29 80211194.73
November 0.362735E+09 0.274959E+09 0.296079E+09 0.00 0.00 0.00 0.00 13244586.18 0.166150E+09
December 0.374985E+09 0.282770E+09 0.304889E+09 0.00 0.00 0.00 0.00 4300719.38 0.265060E+09
                   
Annual Sum or Average 0.442217E+10 0.333955E+10 0.359760E+10 0.00 0.00 0.00 0.00 0.127414E+10 0.114938E+10
Minimum of Months 0.339028E+09 0.256006E+09 0.275845E+09 0.00 0.00 0.00 0.00 99903.17 646745.63
Maximum of Months 0.376747E+09 0.284518E+09 0.306219E+09 0.00 0.00 0.00 0.00 0.252507E+09 0.265060E+09



Table of Contents

Report: SpaceGainsMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.154405E+10 0.350256E+09 0.576866E+10 0.501157E+11 0.00 0.00 0.00 28955106.61 0.473162E+09
February 0.139600E+10 0.316249E+09 0.520895E+10 0.452532E+11 0.00 0.00 0.00 234939.98 0.524609E+09
March 0.155131E+10 0.351336E+09 0.578079E+10 0.502211E+11 0.00 0.00 0.00 34345583.11 0.436491E+09
April 0.149688E+10 0.338381E+09 0.557545E+10 0.484372E+11 0.00 0.00 0.00 0.221117E+09 0.109558E+09
May 0.154732E+10 0.350863E+09 0.577559E+10 0.501759E+11 0.00 0.00 0.00 0.345066E+09 39883271.74
June 0.150015E+10 0.339933E+09 0.559364E+10 0.485952E+11 0.00 0.00 0.00 0.588133E+09 1857666.33
July 0.154405E+10 0.349311E+09 0.575740E+10 0.500179E+11 0.00 0.00 0.00 0.565499E+09 1453156.62
August 0.155059E+10 0.351471E+09 0.578252E+10 0.502361E+11 0.00 0.00 0.00 0.526845E+09 2492533.30
September 0.149615E+10 0.338516E+09 0.557718E+10 0.484522E+11 0.00 0.00 0.00 0.392543E+09 6707439.20
October 0.154478E+10 0.350121E+09 0.576693E+10 0.501006E+11 0.00 0.00 0.00 0.161352E+09 0.205797E+09
November 0.149361E+10 0.339663E+09 0.559104E+10 0.485726E+11 0.00 0.00 0.00 30904817.34 0.419468E+09
December 0.154405E+10 0.349311E+09 0.575740E+10 0.500179E+11 0.00 0.00 0.00 10169997.63 0.655311E+09
                   
Annual Sum or Average 0.182090E+11 0.412541E+10 0.679355E+11 0.590196E+12 0.00 0.00 0.00 0.290517E+10 0.287679E+10
Minimum of Months 0.139600E+10 0.316249E+09 0.520895E+10 0.452532E+11 0.00 0.00 0.00 234939.98 1453156.62
Maximum of Months 0.155131E+10 0.351471E+09 0.578252E+10 0.502361E+11 0.00 0.00 0.00 0.588133E+09 0.655311E+09



Table of Contents

Report: SpaceGainsMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.261570E+11 0.226040E+10 0.121771E+10 0.00 0.00 0.00 0.00 33262442.16 0.808811E+09
February 0.236489E+11 0.204093E+10 0.109956E+10 0.00 0.00 0.00 0.00 419422.05 0.893667E+09
March 0.262800E+11 0.226736E+10 0.122027E+10 0.00 0.00 0.00 0.00 61292544.86 0.734701E+09
April 0.253579E+11 0.218376E+10 0.117692E+10 0.00 0.00 0.00 0.00 0.403899E+09 0.193674E+09
May 0.262123E+11 0.226431E+10 0.121917E+10 0.00 0.00 0.00 0.00 0.631293E+09 76153563.33
June 0.254132E+11 0.219377E+10 0.118076E+10 0.00 0.00 0.00 0.00 0.103497E+10 4777326.09
July 0.261570E+11 0.225430E+10 0.121533E+10 0.00 0.00 0.00 0.00 0.994906E+09 3308787.13
August 0.262677E+11 0.226823E+10 0.122063E+10 0.00 0.00 0.00 0.00 0.921806E+09 3819309.27
September 0.253456E+11 0.218463E+10 0.117729E+10 0.00 0.00 0.00 0.00 0.683763E+09 13959695.30
October 0.261693E+11 0.225952E+10 0.121734E+10 0.00 0.00 0.00 0.00 0.272469E+09 0.350948E+09
November 0.253025E+11 0.219203E+10 0.118021E+10 0.00 0.00 0.00 0.00 42975044.91 0.714373E+09
December 0.261570E+11 0.225430E+10 0.121533E+10 0.00 0.00 0.00 0.00 11209133.71 0.112746E+10
                   
Annual Sum or Average 0.308468E+12 0.266236E+11 0.143405E+11 0.00 0.00 0.00 0.00 0.509227E+10 0.492565E+10
Minimum of Months 0.236489E+11 0.204093E+10 0.109956E+10 0.00 0.00 0.00 0.00 419422.05 3308787.13
Maximum of Months 0.262800E+11 0.226823E+10 0.122063E+10 0.00 0.00 0.00 0.00 0.103497E+10 0.112746E+10



Table of Contents

Report: SpaceGainsMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.776503E+11 0.123020E+11 0.126520E+11 0.00 0.00 0.00 0.00 0.146786E+09 0.230282E+10
February 0.702046E+11 0.111075E+11 0.114244E+11 0.00 0.00 0.00 0.00 1198275.45 0.255740E+10
March 0.780153E+11 0.123399E+11 0.126786E+11 0.00 0.00 0.00 0.00 0.181500E+09 0.212280E+10
April 0.752779E+11 0.118849E+11 0.122282E+11 0.00 0.00 0.00 0.00 0.116852E+10 0.573118E+09
May 0.778146E+11 0.123233E+11 0.126672E+11 0.00 0.00 0.00 0.00 0.179277E+10 0.235169E+09
June 0.754422E+11 0.119394E+11 0.122682E+11 0.00 0.00 0.00 0.00 0.294478E+10 17351877.54
July 0.776503E+11 0.122688E+11 0.126273E+11 0.00 0.00 0.00 0.00 0.283144E+10 12301153.65
August 0.779788E+11 0.123446E+11 0.126824E+11 0.00 0.00 0.00 0.00 0.264344E+10 13031769.06
September 0.752414E+11 0.118896E+11 0.122320E+11 0.00 0.00 0.00 0.00 0.198119E+10 44481730.14
October 0.776868E+11 0.122972E+11 0.126482E+11 0.00 0.00 0.00 0.00 0.831597E+09 0.101450E+10
November 0.751137E+11 0.119299E+11 0.122624E+11 0.00 0.00 0.00 0.00 0.157524E+09 0.203920E+10
December 0.776503E+11 0.122688E+11 0.126273E+11 0.00 0.00 0.00 0.00 51423732.20 0.320683E+10
                   
Annual Sum or Average 0.915726E+12 0.144896E+12 0.148998E+12 0.00 0.00 0.00 0.00 0.147322E+11 0.141390E+11
Minimum of Months 0.702046E+11 0.111075E+11 0.114244E+11 0.00 0.00 0.00 0.00 1198275.45 12301153.65
Maximum of Months 0.780153E+11 0.123446E+11 0.126824E+11 0.00 0.00 0.00 0.00 0.294478E+10 0.320683E+10



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.434056E+09 0.261068E+09 0.00 0.00 0.00 0.00 6176807.46 0.219207E+09
February 0.273974E+09 0.391995E+09 0.235798E+09 0.00 0.00 0.00 0.00 4202.78 0.243360E+09
March 0.303685E+09 0.430607E+09 0.260708E+09 0.00 0.00 0.00 0.00 10989642.80 0.200995E+09
April 0.293479E+09 0.420554E+09 0.252705E+09 0.00 0.00 0.00 0.00 94041077.92 51715323.73
May 0.303504E+09 0.432331E+09 0.260888E+09 0.00 0.00 0.00 0.00 0.150988E+09 19559716.19
June 0.293842E+09 0.417218E+09 0.252344E+09 0.00 0.00 0.00 0.00 0.262442E+09 983740.81
July 0.303141E+09 0.435725E+09 0.261248E+09 0.00 0.00 0.00 0.00 0.251256E+09 781872.00
August 0.303685E+09 0.430607E+09 0.260708E+09 0.00 0.00 0.00 0.00 0.233899E+09 1007993.20
September 0.293479E+09 0.420667E+09 0.252705E+09 0.00 0.00 0.00 0.00 0.172046E+09 3397504.36
October 0.303322E+09 0.434000E+09 0.261068E+09 0.00 0.00 0.00 0.00 65893939.80 95056323.18
November 0.293661E+09 0.418886E+09 0.252524E+09 0.00 0.00 0.00 0.00 8343941.59 0.194591E+09
December 0.303141E+09 0.435781E+09 0.261248E+09 0.00 0.00 0.00 0.00 1716445.22 0.304750E+09
                   
Annual Sum or Average 0.357224E+10 0.510243E+10 0.307301E+10 0.00 0.00 0.00 0.00 0.125780E+10 0.133541E+10
Minimum of Months 0.273974E+09 0.391995E+09 0.235798E+09 0.00 0.00 0.00 0.00 4202.78 781872.00
Maximum of Months 0.303685E+09 0.435781E+09 0.261248E+09 0.00 0.00 0.00 0.00 0.262442E+09 0.304750E+09



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.434005E+09 0.261038E+09 0.00 0.00 0.00 0.00 8318543.48 0.212759E+09
February 0.273974E+09 0.391949E+09 0.235770E+09 0.00 0.00 0.00 0.00 7333.93 0.236885E+09
March 0.303685E+09 0.430556E+09 0.260677E+09 0.00 0.00 0.00 0.00 11769952.18 0.197177E+09
April 0.293479E+09 0.420505E+09 0.252675E+09 0.00 0.00 0.00 0.00 94485030.12 51437815.97
May 0.303504E+09 0.432281E+09 0.260857E+09 0.00 0.00 0.00 0.00 0.151019E+09 19582060.82
June 0.293842E+09 0.417169E+09 0.252315E+09 0.00 0.00 0.00 0.00 0.262317E+09 983612.51
July 0.303141E+09 0.435674E+09 0.261218E+09 0.00 0.00 0.00 0.00 0.251199E+09 781910.14
August 0.303685E+09 0.430556E+09 0.260677E+09 0.00 0.00 0.00 0.00 0.233957E+09 1004572.18
September 0.293479E+09 0.420618E+09 0.252675E+09 0.00 0.00 0.00 0.00 0.172274E+09 3363336.21
October 0.303322E+09 0.433949E+09 0.261038E+09 0.00 0.00 0.00 0.00 66900973.71 92448204.62
November 0.293661E+09 0.418837E+09 0.252495E+09 0.00 0.00 0.00 0.00 9581158.28 0.189469E+09
December 0.303141E+09 0.435730E+09 0.261218E+09 0.00 0.00 0.00 0.00 2825112.23 0.295045E+09
                   
Annual Sum or Average 0.357224E+10 0.510183E+10 0.307265E+10 0.00 0.00 0.00 0.00 0.126465E+10 0.130094E+10
Minimum of Months 0.273974E+09 0.391949E+09 0.235770E+09 0.00 0.00 0.00 0.00 7333.93 781910.14
Maximum of Months 0.303685E+09 0.435730E+09 0.261218E+09 0.00 0.00 0.00 0.00 0.262317E+09 0.295045E+09



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.272788E+09 0.255708E+09 0.00 0.00 0.00 0.00 1105601.59 74977098.14
February 0.00 0.246354E+09 0.230956E+09 0.00 0.00 0.00 0.00 0.00 81289001.33
March 0.00 0.270620E+09 0.255355E+09 0.00 0.00 0.00 0.00 2008870.84 69117379.21
April 0.00 0.264302E+09 0.247516E+09 0.00 0.00 0.00 0.00 20460373.62 21821581.81
May 0.00 0.271704E+09 0.255532E+09 0.00 0.00 0.00 0.00 34093590.91 10734646.80
June 0.00 0.262205E+09 0.247163E+09 0.00 0.00 0.00 0.00 62012410.63 1531109.73
July 0.00 0.273836E+09 0.255885E+09 0.00 0.00 0.00 0.00 57846211.31 1000182.28
August 0.00 0.270620E+09 0.255355E+09 0.00 0.00 0.00 0.00 53381514.91 1494587.28
September 0.00 0.264373E+09 0.247516E+09 0.00 0.00 0.00 0.00 37675575.70 3436054.55
October 0.00 0.272752E+09 0.255708E+09 0.00 0.00 0.00 0.00 14242288.91 36285794.50
November 0.00 0.263254E+09 0.247340E+09 0.00 0.00 0.00 0.00 1580855.39 67446582.75
December 0.00 0.273872E+09 0.255885E+09 0.00 0.00 0.00 0.00 299391.67 99191469.70
                   
Annual Sum or Average 0.00 0.320668E+10 0.300992E+10 0.00 0.00 0.00 0.00 0.284707E+09 0.468325E+09
Minimum of Months 0.00 0.246354E+09 0.230956E+09 0.00 0.00 0.00 0.00 0.00 1000182.28
Maximum of Months 0.00 0.273872E+09 0.255885E+09 0.00 0.00 0.00 0.00 62012410.63 99191469.70



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.272862E+09 0.255778E+09 0.00 0.00 0.00 0.00 2964686.93 59593099.27
February 0.273974E+09 0.246421E+09 0.231020E+09 0.00 0.00 0.00 0.00 1154.11 67033120.09
March 0.303685E+09 0.270694E+09 0.255425E+09 0.00 0.00 0.00 0.00 3625995.86 55384784.39
April 0.293479E+09 0.264375E+09 0.247584E+09 0.00 0.00 0.00 0.00 27057512.45 14313647.75
May 0.303504E+09 0.271778E+09 0.255602E+09 0.00 0.00 0.00 0.00 42599873.57 5460357.19
June 0.293842E+09 0.262277E+09 0.247231E+09 0.00 0.00 0.00 0.00 73467062.71 274443.66
July 0.303141E+09 0.273911E+09 0.255955E+09 0.00 0.00 0.00 0.00 70357814.28 218164.71
August 0.303685E+09 0.270694E+09 0.255425E+09 0.00 0.00 0.00 0.00 65603879.98 273270.58
September 0.293479E+09 0.264446E+09 0.247584E+09 0.00 0.00 0.00 0.00 48460392.78 934043.11
October 0.303322E+09 0.272827E+09 0.255778E+09 0.00 0.00 0.00 0.00 19317146.26 25903045.91
November 0.293661E+09 0.263326E+09 0.247408E+09 0.00 0.00 0.00 0.00 3212295.53 52903435.15
December 0.303141E+09 0.273947E+09 0.255955E+09 0.00 0.00 0.00 0.00 1020969.09 83041254.10
                   
Annual Sum or Average 0.357224E+10 0.320756E+10 0.301074E+10 0.00 0.00 0.00 0.00 0.357689E+09 0.365333E+09
Minimum of Months 0.273974E+09 0.246421E+09 0.231020E+09 0.00 0.00 0.00 0.00 1154.11 218164.71
Maximum of Months 0.303685E+09 0.273947E+09 0.255955E+09 0.00 0.00 0.00 0.00 73467062.71 83041254.10



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.434056E+09 0.261068E+09 0.00 0.00 0.00 0.00 6173855.56 0.221117E+09
February 0.273974E+09 0.391995E+09 0.235798E+09 0.00 0.00 0.00 0.00 4081.95 0.246285E+09
March 0.303685E+09 0.430607E+09 0.260708E+09 0.00 0.00 0.00 0.00 10754700.97 0.204200E+09
April 0.293479E+09 0.420554E+09 0.252705E+09 0.00 0.00 0.00 0.00 93738907.07 52994771.90
May 0.303504E+09 0.432331E+09 0.260888E+09 0.00 0.00 0.00 0.00 0.150467E+09 19941020.72
June 0.293842E+09 0.417218E+09 0.252344E+09 0.00 0.00 0.00 0.00 0.262142E+09 983801.71
July 0.303141E+09 0.435725E+09 0.261248E+09 0.00 0.00 0.00 0.00 0.250829E+09 786236.32
August 0.303685E+09 0.430607E+09 0.260708E+09 0.00 0.00 0.00 0.00 0.233508E+09 1077528.22
September 0.293479E+09 0.420667E+09 0.252705E+09 0.00 0.00 0.00 0.00 0.171780E+09 3602532.64
October 0.303322E+09 0.434000E+09 0.261068E+09 0.00 0.00 0.00 0.00 65820119.03 96738130.05
November 0.293661E+09 0.418886E+09 0.252524E+09 0.00 0.00 0.00 0.00 8271875.46 0.195834E+09
December 0.303141E+09 0.435781E+09 0.261248E+09 0.00 0.00 0.00 0.00 1691546.36 0.306586E+09
                   
Annual Sum or Average 0.357224E+10 0.510243E+10 0.307301E+10 0.00 0.00 0.00 0.00 0.125518E+10 0.135014E+10
Minimum of Months 0.273974E+09 0.391995E+09 0.235798E+09 0.00 0.00 0.00 0.00 4081.95 786236.32
Maximum of Months 0.303685E+09 0.435781E+09 0.261248E+09 0.00 0.00 0.00 0.00 0.262142E+09 0.306586E+09



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.434005E+09 0.261038E+09 0.00 0.00 0.00 0.00 8383293.43 0.214363E+09
February 0.273974E+09 0.391949E+09 0.235770E+09 0.00 0.00 0.00 0.00 4168.33 0.239690E+09
March 0.303685E+09 0.430556E+09 0.260677E+09 0.00 0.00 0.00 0.00 11047007.45 0.200532E+09
April 0.293479E+09 0.420505E+09 0.252675E+09 0.00 0.00 0.00 0.00 93794184.99 52951673.51
May 0.303504E+09 0.432281E+09 0.260857E+09 0.00 0.00 0.00 0.00 0.150463E+09 19943840.86
June 0.293842E+09 0.417169E+09 0.252315E+09 0.00 0.00 0.00 0.00 0.262071E+09 983756.49
July 0.303141E+09 0.435674E+09 0.261218E+09 0.00 0.00 0.00 0.00 0.250799E+09 786376.94
August 0.303685E+09 0.430556E+09 0.260677E+09 0.00 0.00 0.00 0.00 0.233522E+09 1072628.20
September 0.293479E+09 0.420618E+09 0.252675E+09 0.00 0.00 0.00 0.00 0.171854E+09 3588930.71
October 0.303322E+09 0.433949E+09 0.261038E+09 0.00 0.00 0.00 0.00 66287508.70 94810522.89
November 0.293661E+09 0.418837E+09 0.252495E+09 0.00 0.00 0.00 0.00 9493710.13 0.190022E+09
December 0.303141E+09 0.435730E+09 0.261218E+09 0.00 0.00 0.00 0.00 2934105.76 0.296105E+09
                   
Annual Sum or Average 0.357224E+10 0.510183E+10 0.307265E+10 0.00 0.00 0.00 0.00 0.126065E+10 0.131485E+10
Minimum of Months 0.273974E+09 0.391949E+09 0.235770E+09 0.00 0.00 0.00 0.00 4168.33 786376.94
Maximum of Months 0.303685E+09 0.435730E+09 0.261218E+09 0.00 0.00 0.00 0.00 0.262071E+09 0.296105E+09



Table of Contents

Report: SpaceGainsMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.385223E+10 0.133160E+10 0.00 0.00 0.00 0.00 0.00 15380073.62 0.253129E+09
February 0.348285E+10 0.120231E+10 0.00 0.00 0.00 0.00 0.00 126258.18 0.282972E+09
March 0.387034E+10 0.133570E+10 0.00 0.00 0.00 0.00 0.00 19818960.62 0.233283E+09
April 0.373454E+10 0.128645E+10 0.00 0.00 0.00 0.00 0.00 0.125949E+09 62964886.96
May 0.386038E+10 0.133391E+10 0.00 0.00 0.00 0.00 0.00 0.191150E+09 26854768.87
June 0.374269E+10 0.129235E+10 0.00 0.00 0.00 0.00 0.00 0.306517E+09 2501400.56
July 0.385223E+10 0.132801E+10 0.00 0.00 0.00 0.00 0.00 0.293818E+09 1916840.03
August 0.386853E+10 0.133622E+10 0.00 0.00 0.00 0.00 0.00 0.275561E+09 1818520.44
September 0.373273E+10 0.128696E+10 0.00 0.00 0.00 0.00 0.00 0.205302E+09 5696325.99
October 0.385404E+10 0.133109E+10 0.00 0.00 0.00 0.00 0.00 86304645.80 0.112032E+09
November 0.372639E+10 0.129132E+10 0.00 0.00 0.00 0.00 0.00 16728663.13 0.223739E+09
December 0.385223E+10 0.132801E+10 0.00 0.00 0.00 0.00 0.00 5445117.37 0.355138E+09
                   
Annual Sum or Average 0.454292E+11 0.156839E+11 0.00 0.00 0.00 0.00 0.00 0.154210E+10 0.156205E+10
Minimum of Months 0.348285E+10 0.120231E+10 0.00 0.00 0.00 0.00 0.00 126258.18 1818520.44
Maximum of Months 0.387034E+10 0.133622E+10 0.00 0.00 0.00 0.00 0.00 0.306517E+09 0.355138E+09



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.434056E+09 0.261068E+09 0.00 0.00 0.00 0.00 5976441.23 0.220361E+09
February 0.273974E+09 0.391995E+09 0.235798E+09 0.00 0.00 0.00 0.00 3370.69 0.244284E+09
March 0.303685E+09 0.430607E+09 0.260708E+09 0.00 0.00 0.00 0.00 10651563.78 0.202387E+09
April 0.293479E+09 0.420554E+09 0.252705E+09 0.00 0.00 0.00 0.00 92929467.42 52343791.22
May 0.303504E+09 0.432331E+09 0.260888E+09 0.00 0.00 0.00 0.00 0.149551E+09 19977203.56
June 0.293842E+09 0.417218E+09 0.252344E+09 0.00 0.00 0.00 0.00 0.260638E+09 1043916.95
July 0.303141E+09 0.435725E+09 0.261248E+09 0.00 0.00 0.00 0.00 0.249446E+09 824839.69
August 0.303685E+09 0.430607E+09 0.260708E+09 0.00 0.00 0.00 0.00 0.232104E+09 1087915.41
September 0.293479E+09 0.420667E+09 0.252705E+09 0.00 0.00 0.00 0.00 0.170418E+09 3538242.47
October 0.303322E+09 0.434000E+09 0.261068E+09 0.00 0.00 0.00 0.00 65124514.05 95916565.43
November 0.293661E+09 0.418886E+09 0.252524E+09 0.00 0.00 0.00 0.00 8068408.33 0.195714E+09
December 0.303141E+09 0.435781E+09 0.261248E+09 0.00 0.00 0.00 0.00 1626991.48 0.305408E+09
                   
Annual Sum or Average 0.357224E+10 0.510243E+10 0.307301E+10 0.00 0.00 0.00 0.00 0.124654E+10 0.134289E+10
Minimum of Months 0.273974E+09 0.391995E+09 0.235798E+09 0.00 0.00 0.00 0.00 3370.69 824839.69
Maximum of Months 0.303685E+09 0.435781E+09 0.261248E+09 0.00 0.00 0.00 0.00 0.260638E+09 0.305408E+09



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.434005E+09 0.261038E+09 0.00 0.00 0.00 0.00 7860781.45 0.213763E+09
February 0.273974E+09 0.391949E+09 0.235770E+09 0.00 0.00 0.00 0.00 3959.01 0.237631E+09
March 0.303685E+09 0.430556E+09 0.260677E+09 0.00 0.00 0.00 0.00 11188107.46 0.198603E+09
April 0.293479E+09 0.420505E+09 0.252675E+09 0.00 0.00 0.00 0.00 93142937.56 52137818.87
May 0.303504E+09 0.432281E+09 0.260857E+09 0.00 0.00 0.00 0.00 0.149549E+09 19999349.70
June 0.293842E+09 0.417169E+09 0.252315E+09 0.00 0.00 0.00 0.00 0.260511E+09 1043844.04
July 0.303141E+09 0.435674E+09 0.261218E+09 0.00 0.00 0.00 0.00 0.249390E+09 824890.90
August 0.303685E+09 0.430556E+09 0.260677E+09 0.00 0.00 0.00 0.00 0.232157E+09 1084192.53
September 0.293479E+09 0.420618E+09 0.252675E+09 0.00 0.00 0.00 0.00 0.170607E+09 3506425.63
October 0.303322E+09 0.433949E+09 0.261038E+09 0.00 0.00 0.00 0.00 65811061.11 93328844.34
November 0.293661E+09 0.418837E+09 0.252495E+09 0.00 0.00 0.00 0.00 9048316.95 0.190551E+09
December 0.303141E+09 0.435730E+09 0.261218E+09 0.00 0.00 0.00 0.00 2651445.24 0.295358E+09
                   
Annual Sum or Average 0.357224E+10 0.510183E+10 0.307265E+10 0.00 0.00 0.00 0.00 0.125192E+10 0.130783E+10
Minimum of Months 0.273974E+09 0.391949E+09 0.235770E+09 0.00 0.00 0.00 0.00 3959.01 824890.90
Maximum of Months 0.303685E+09 0.435730E+09 0.261218E+09 0.00 0.00 0.00 0.00 0.260511E+09 0.295358E+09



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.272862E+09 0.255778E+09 0.00 0.00 0.00 0.00 3029794.74 0.114765E+09
February 0.273974E+09 0.246421E+09 0.231020E+09 0.00 0.00 0.00 0.00 1663.58 0.127973E+09
March 0.303685E+09 0.270694E+09 0.255425E+09 0.00 0.00 0.00 0.00 5365938.79 0.105398E+09
April 0.293479E+09 0.264375E+09 0.247584E+09 0.00 0.00 0.00 0.00 47540988.80 26830243.87
May 0.303504E+09 0.271778E+09 0.255602E+09 0.00 0.00 0.00 0.00 76627036.89 10214587.41
June 0.293842E+09 0.262277E+09 0.247231E+09 0.00 0.00 0.00 0.00 0.133593E+09 533970.74
July 0.303141E+09 0.273911E+09 0.255955E+09 0.00 0.00 0.00 0.00 0.127714E+09 421929.73
August 0.303685E+09 0.270694E+09 0.255425E+09 0.00 0.00 0.00 0.00 0.118778E+09 554170.88
September 0.293479E+09 0.264446E+09 0.247584E+09 0.00 0.00 0.00 0.00 87119684.13 1839851.25
October 0.303322E+09 0.272827E+09 0.255778E+09 0.00 0.00 0.00 0.00 33213962.17 49885827.30
November 0.293661E+09 0.263326E+09 0.247408E+09 0.00 0.00 0.00 0.00 4015760.70 0.101766E+09
December 0.303141E+09 0.273947E+09 0.255955E+09 0.00 0.00 0.00 0.00 822321.06 0.159705E+09
                   
Annual Sum or Average 0.357224E+10 0.320756E+10 0.301074E+10 0.00 0.00 0.00 0.00 0.637822E+09 0.699887E+09
Minimum of Months 0.273974E+09 0.246421E+09 0.231020E+09 0.00 0.00 0.00 0.00 1663.58 421929.73
Maximum of Months 0.303685E+09 0.273947E+09 0.255955E+09 0.00 0.00 0.00 0.00 0.133593E+09 0.159705E+09



Table of Contents

Report: SpaceGainsMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.459349E+11 0.396945E+10 0.149358E+11 0.00 0.00 0.00 0.00 31430861.23 0.540405E+09
February 0.415303E+11 0.358405E+10 0.134904E+11 0.00 0.00 0.00 0.00 235400.52 0.598970E+09
March 0.461508E+11 0.398168E+10 0.149358E+11 0.00 0.00 0.00 0.00 38025529.26 0.504389E+09
April 0.445315E+11 0.383486E+10 0.144540E+11 0.00 0.00 0.00 0.00 0.246495E+09 0.146646E+09
May 0.460320E+11 0.397633E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.376370E+09 66545028.96
June 0.446286E+11 0.385245E+10 0.144540E+11 0.00 0.00 0.00 0.00 0.620667E+09 6995206.99
July 0.459349E+11 0.395874E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.593500E+09 4620932.44
August 0.461292E+11 0.398321E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.555808E+09 5620420.56
September 0.445099E+11 0.383639E+10 0.144540E+11 0.00 0.00 0.00 0.00 0.414947E+09 15284944.92
October 0.459565E+11 0.396792E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.177194E+09 0.247115E+09
November 0.444343E+11 0.384939E+10 0.144540E+11 0.00 0.00 0.00 0.00 33780252.60 0.481472E+09
December 0.459349E+11 0.395874E+10 0.149358E+11 0.00 0.00 0.00 0.00 10974021.18 0.742502E+09
                   
Annual Sum or Average 0.541708E+12 0.467532E+11 0.175857E+12 0.00 0.00 0.00 0.00 0.309943E+10 0.336057E+10
Minimum of Months 0.415303E+11 0.358405E+10 0.134904E+11 0.00 0.00 0.00 0.00 235400.52 4620932.44
Maximum of Months 0.461508E+11 0.398321E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.620667E+09 0.742502E+09



Table of Contents

Report: SpaceGainsMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.459349E+11 0.396945E+10 0.149358E+11 0.00 0.00 0.00 0.00 31199989.25 0.543121E+09
February 0.415303E+11 0.358405E+10 0.134904E+11 0.00 0.00 0.00 0.00 235417.16 0.601843E+09
March 0.461508E+11 0.398168E+10 0.149358E+11 0.00 0.00 0.00 0.00 37388900.95 0.507480E+09
April 0.445315E+11 0.383486E+10 0.144540E+11 0.00 0.00 0.00 0.00 0.243516E+09 0.148571E+09
May 0.460320E+11 0.397633E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.371598E+09 67791363.25
June 0.446286E+11 0.385245E+10 0.144540E+11 0.00 0.00 0.00 0.00 0.616247E+09 7151305.77
July 0.459349E+11 0.395874E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.588749E+09 4707456.55
August 0.461292E+11 0.398321E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.551381E+09 5886249.42
September 0.445099E+11 0.383639E+10 0.144540E+11 0.00 0.00 0.00 0.00 0.410580E+09 15796900.39
October 0.459565E+11 0.396792E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.175438E+09 0.249398E+09
November 0.444343E+11 0.384939E+10 0.144540E+11 0.00 0.00 0.00 0.00 33513585.04 0.484307E+09
December 0.459349E+11 0.395874E+10 0.149358E+11 0.00 0.00 0.00 0.00 10918417.47 0.745212E+09
                   
Annual Sum or Average 0.541708E+12 0.467532E+11 0.175857E+12 0.00 0.00 0.00 0.00 0.307077E+10 0.338127E+10
Minimum of Months 0.415303E+11 0.358405E+10 0.134904E+11 0.00 0.00 0.00 0.00 235417.16 4707456.55
Maximum of Months 0.461508E+11 0.398321E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.616247E+09 0.745212E+09



Table of Contents

Report: SpaceGainsMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.408770E+10 0.105977E+10 0.338870E+11 0.305408E+11 0.00 0.00 0.00 5948416.40 0.559348E+09
February 0.369574E+10 0.956878E+09 0.306077E+11 0.275852E+11 0.00 0.00 0.00 0.00 0.621414E+09
March 0.410691E+10 0.106304E+10 0.338870E+11 0.305408E+11 0.00 0.00 0.00 12090567.19 0.522344E+09
April 0.396281E+10 0.102384E+10 0.327939E+11 0.295556E+11 0.00 0.00 0.00 0.143424E+09 0.140508E+09
May 0.409635E+10 0.106161E+10 0.338870E+11 0.305408E+11 0.00 0.00 0.00 0.249103E+09 55416236.22
June 0.397146E+10 0.102854E+10 0.327939E+11 0.295556E+11 0.00 0.00 0.00 0.483376E+09 4360069.19
July 0.408770E+10 0.105691E+10 0.338870E+11 0.305408E+11 0.00 0.00 0.00 0.454914E+09 2812890.62
August 0.410499E+10 0.106345E+10 0.338870E+11 0.305408E+11 0.00 0.00 0.00 0.420370E+09 6319336.78
September 0.396089E+10 0.102425E+10 0.327939E+11 0.295556E+11 0.00 0.00 0.00 0.294073E+09 15326926.81
October 0.408962E+10 0.105936E+10 0.338870E+11 0.305408E+11 0.00 0.00 0.00 0.103802E+09 0.258165E+09
November 0.395417E+10 0.102772E+10 0.327939E+11 0.295556E+11 0.00 0.00 0.00 9355516.56 0.502984E+09
December 0.408770E+10 0.105691E+10 0.338870E+11 0.305408E+11 0.00 0.00 0.00 1621136.82 0.753697E+09
                   
Annual Sum or Average 0.482060E+11 0.124823E+11 0.398993E+12 0.359593E+12 0.00 0.00 0.00 0.217808E+10 0.344269E+10
Minimum of Months 0.369574E+10 0.956878E+09 0.306077E+11 0.275852E+11 0.00 0.00 0.00 0.00 2812890.62
Maximum of Months 0.410691E+10 0.106345E+10 0.338870E+11 0.305408E+11 0.00 0.00 0.00 0.483376E+09 0.753697E+09



Table of Contents

Report: SpaceGainsMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.407704E+10 0.140929E+10 0.00 0.00 0.00 0.00 0.00 27098928.66 0.450157E+09
February 0.368610E+10 0.127246E+10 0.00 0.00 0.00 0.00 0.00 206548.76 0.504261E+09
March 0.409620E+10 0.141364E+10 0.00 0.00 0.00 0.00 0.00 34561096.09 0.415167E+09
April 0.395248E+10 0.136151E+10 0.00 0.00 0.00 0.00 0.00 0.227002E+09 0.105967E+09
May 0.408566E+10 0.141173E+10 0.00 0.00 0.00 0.00 0.00 0.350513E+09 40514209.53
June 0.396110E+10 0.136775E+10 0.00 0.00 0.00 0.00 0.00 0.562340E+09 2147187.65
July 0.407704E+10 0.140549E+10 0.00 0.00 0.00 0.00 0.00 0.543003E+09 1832190.27
August 0.409429E+10 0.141418E+10 0.00 0.00 0.00 0.00 0.00 0.509771E+09 1812417.76
September 0.395056E+10 0.136205E+10 0.00 0.00 0.00 0.00 0.00 0.387207E+09 6290660.83
October 0.407896E+10 0.140875E+10 0.00 0.00 0.00 0.00 0.00 0.161094E+09 0.192993E+09
November 0.394385E+10 0.136667E+10 0.00 0.00 0.00 0.00 0.00 29369859.28 0.397652E+09
December 0.407704E+10 0.140549E+10 0.00 0.00 0.00 0.00 0.00 9518404.63 0.631927E+09
                   
Annual Sum or Average 0.480803E+11 0.165990E+11 0.00 0.00 0.00 0.00 0.00 0.284168E+10 0.275072E+10
Minimum of Months 0.368610E+10 0.127246E+10 0.00 0.00 0.00 0.00 0.00 206548.76 1812417.76
Maximum of Months 0.409620E+10 0.141418E+10 0.00 0.00 0.00 0.00 0.00 0.562340E+09 0.631927E+09



Table of Contents

Report: PeakSpaceGainsMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 11501.89 02-JAN-00:10 13517.00 02-JAN-20:10 10113.80 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 0.00
February 11501.89 01-FEB-00:10 13517.00 01-FEB-20:10 10113.80 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 0.00
March 11501.89 01-MAR-00:10 13517.00 01-MAR-20:10 10113.80 01-MAR-20:10 0.00 0.00 0.00 0.00 0.00 0.00
April 11501.89 01-APR-00:10 13517.00 03-APR-19:10 10113.80 03-APR-19:10 0.00 0.00 0.00 0.00 0.00 0.00
May 11501.89 01-MAY-00:10 13517.00 01-MAY-19:10 10113.80 01-MAY-19:10 0.00 0.00 0.00 0.00 0.00 0.00
June 11501.89 01-JUN-00:10 13517.00 01-JUN-19:10 10113.80 01-JUN-19:10 0.00 0.00 0.00 0.00 0.00 0.00
July 11501.89 01-JUL-00:10 13517.00 03-JUL-19:10 10113.80 03-JUL-19:10 0.00 0.00 0.00 0.00 0.00 0.00
August 11501.89 01-AUG-00:10 13517.00 01-AUG-19:10 10113.80 01-AUG-19:10 0.00 0.00 0.00 0.00 0.00 0.00
September 11501.89 01-SEP-00:10 13517.00 01-SEP-19:10 10113.80 01-SEP-19:10 0.00 0.00 0.00 0.00 0.00 0.00
October 11501.89 01-OCT-23:10 13517.00 02-OCT-19:10 10113.80 02-OCT-19:10 0.00 0.00 0.00 0.00 0.00 0.00
November 11501.89 01-NOV-00:10 13517.00 01-NOV-19:10 10113.80 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 0.00
December 11501.89 01-DEC-00:10 13517.00 01-DEC-20:10 10113.80 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 11501.89   13517.00   10113.80   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 11501.89   13517.00   10113.80   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1169.53 02-JAN-00:10 687.30 02-JAN-20:10 685.60 02-JAN-20:10 0.00 0.00 0.00 0.00 131.98 31-JAN-17:00 427.07 01-JAN-08:00
February 1169.53 01-FEB-00:10 687.30 01-FEB-20:10 685.60 01-FEB-20:10 0.00 0.00 0.00 0.00 19.22 18-FEB-15:30 327.79 28-FEB-06:50
March 1169.53 01-MAR-00:10 687.30 01-MAR-20:10 685.60 01-MAR-20:10 0.00 0.00 0.00 0.00 146.73 20-MAR-17:00 425.67 26-MAR-06:00
April 1169.53 01-APR-00:10 687.30 03-APR-19:10 685.60 03-APR-19:10 0.00 0.00 0.00 0.00 250.38 14-APR-17:00 262.76 21-APR-04:50
May 1169.53 01-MAY-00:10 687.30 01-MAY-19:10 685.60 01-MAY-19:10 0.00 0.00 0.00 0.00 293.29 31-MAY-17:00 179.59 01-MAY-04:00
June 1169.53 01-JUN-00:10 687.30 01-JUN-19:10 685.60 01-JUN-19:10 0.00 0.00 0.00 0.00 367.92 16-JUN-16:00 58.43 21-JUN-06:00
July 1169.53 01-JUL-00:10 687.30 03-JUL-19:10 685.60 03-JUL-19:10 0.00 0.00 0.00 0.00 333.26 19-JUL-13:00 58.84 01-JUL-06:00
August 1169.53 01-AUG-00:10 687.30 01-AUG-19:10 685.60 01-AUG-19:10 0.00 0.00 0.00 0.00 351.71 25-AUG-17:00 78.76 05-AUG-18:00
September 1169.53 01-SEP-00:10 687.30 01-SEP-19:10 685.60 01-SEP-19:10 0.00 0.00 0.00 0.00 295.11 08-SEP-16:00 86.61 22-SEP-06:00
October 1169.53 01-OCT-23:10 687.30 02-OCT-19:10 685.60 02-OCT-19:10 0.00 0.00 0.00 0.00 280.12 01-OCT-13:00 325.84 25-OCT-06:30
November 1169.53 01-NOV-00:10 687.30 01-NOV-19:10 685.60 01-NOV-19:10 0.00 0.00 0.00 0.00 113.91 10-NOV-14:00 438.32 23-NOV-06:30
December 1169.53 01-DEC-00:10 687.30 01-DEC-20:10 685.60 01-DEC-20:10 0.00 0.00 0.00 0.00 76.37 02-DEC-15:00 460.84 05-DEC-04:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1169.53   687.30   685.60   0.00 0.00 0.00 0.00 19.22   58.43  
Maximum of Months 1169.53   687.30   685.60   0.00 0.00 0.00 0.00 367.92   460.84  



Table of Contents

Report: PeakSpaceGainsMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1354.32 02-JAN-00:10 795.89 02-JAN-20:10 793.93 02-JAN-20:10 0.00 0.00 0.00 0.00 58.41 31-JAN-16:50 164.87 01-JAN-08:00
February 1354.32 01-FEB-00:10 795.89 01-FEB-20:10 793.93 01-FEB-20:10 0.00 0.00 0.00 0.00 7.43 18-FEB-14:00 126.52 28-FEB-07:00
March 1354.32 01-MAR-00:10 795.89 01-MAR-20:10 793.93 01-MAR-20:10 0.00 0.00 0.00 0.00 56.70 16-MAR-15:10 164.29 26-MAR-06:00
April 1354.32 01-APR-00:10 795.89 03-APR-19:10 793.93 03-APR-19:10 0.00 0.00 0.00 0.00 99.51 14-APR-15:20 101.41 21-APR-04:50
May 1354.32 01-MAY-00:10 795.89 01-MAY-19:10 793.93 01-MAY-19:10 0.00 0.00 0.00 0.00 113.20 31-MAY-16:50 69.30 01-MAY-04:00
June 1354.32 01-JUN-00:10 795.89 01-JUN-19:10 793.93 01-JUN-19:10 0.00 0.00 0.00 0.00 146.42 28-JUN-15:50 25.34 21-JUN-05:50
July 1354.32 01-JUL-00:10 795.89 03-JUL-19:10 793.93 03-JUL-19:10 0.00 0.00 0.00 0.00 134.15 19-JUL-13:00 26.27 01-JUL-06:00
August 1354.32 01-AUG-00:10 795.89 01-AUG-19:10 793.93 01-AUG-19:10 0.00 0.00 0.00 0.00 140.54 25-AUG-14:00 30.39 05-AUG-18:00
September 1354.32 01-SEP-00:10 795.89 01-SEP-19:10 793.93 01-SEP-19:10 0.00 0.00 0.00 0.00 122.38 08-SEP-15:30 33.42 22-SEP-06:00
October 1354.32 01-OCT-23:10 795.89 02-OCT-19:10 793.93 02-OCT-19:10 0.00 0.00 0.00 0.00 113.61 01-OCT-13:40 125.79 25-OCT-07:00
November 1354.32 01-NOV-00:10 795.89 01-NOV-19:10 793.93 01-NOV-19:10 0.00 0.00 0.00 0.00 58.18 01-NOV-15:00 169.18 23-NOV-06:40
December 1354.32 01-DEC-00:10 795.89 01-DEC-20:10 793.93 01-DEC-20:10 0.00 0.00 0.00 0.00 36.86 21-DEC-15:00 177.86 05-DEC-04:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1354.32   795.89   793.93   0.00 0.00 0.00 0.00 7.43   25.34  
Maximum of Months 1354.32   795.89   793.93   0.00 0.00 0.00 0.00 146.42   177.86  



Table of Contents

Report: PeakSpaceGainsMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 286.42 02-JAN-00:10 1487.69 02-JAN-20:10 839.45 02-JAN-20:10 0.00 0.00 0.00 0.00 138.04 31-JAN-16:30 389.60 01-JAN-08:00
February 286.42 01-FEB-00:10 1487.69 01-FEB-20:10 839.45 01-FEB-20:10 0.00 0.00 0.00 0.00 17.52 18-FEB-14:00 299.01 28-FEB-07:00
March 286.42 01-MAR-00:10 1487.69 01-MAR-20:10 839.45 01-MAR-20:10 0.00 0.00 0.00 0.00 134.05 16-MAR-15:00 388.28 26-MAR-06:00
April 286.42 01-APR-00:10 1487.69 03-APR-19:10 839.45 03-APR-19:10 0.00 0.00 0.00 0.00 235.18 14-APR-15:40 239.63 21-APR-05:00
May 286.42 01-MAY-00:10 1487.69 01-MAY-19:10 839.45 01-MAY-19:10 0.00 0.00 0.00 0.00 267.54 31-MAY-17:00 163.77 01-MAY-04:00
June 286.42 01-JUN-00:10 1487.69 01-JUN-19:10 839.45 01-JUN-19:10 0.00 0.00 0.00 0.00 345.65 16-JUN-16:00 56.63 21-JUN-06:00
July 286.42 01-JUL-00:10 1487.69 03-JUL-19:10 839.45 03-JUL-19:10 0.00 0.00 0.00 0.00 317.09 19-JUL-13:00 60.98 01-JUL-06:00
August 286.42 01-AUG-00:10 1487.69 01-AUG-19:10 839.45 01-AUG-19:10 0.00 0.00 0.00 0.00 332.10 25-AUG-14:00 71.80 05-AUG-18:00
September 286.42 01-SEP-00:10 1487.69 01-SEP-19:10 839.45 01-SEP-19:10 0.00 0.00 0.00 0.00 289.46 08-SEP-15:00 78.99 22-SEP-06:00
October 286.42 01-OCT-23:10 1487.69 02-OCT-19:10 839.45 02-OCT-19:10 0.00 0.00 0.00 0.00 268.50 01-OCT-13:00 297.23 25-OCT-07:00
November 286.42 01-NOV-00:10 1487.69 01-NOV-19:10 839.45 01-NOV-19:10 0.00 0.00 0.00 0.00 137.44 01-NOV-15:00 399.81 23-NOV-06:00
December 286.42 01-DEC-00:10 1487.69 01-DEC-20:10 839.45 01-DEC-20:10 0.00 0.00 0.00 0.00 87.13 21-DEC-15:00 420.33 05-DEC-04:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 286.42   1487.69   839.45   0.00 0.00 0.00 0.00 17.52   56.63  
Maximum of Months 286.42   1487.69   839.45   0.00 0.00 0.00 0.00 345.65   420.33  



Table of Contents

Report: PeakSpaceGainsMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 220.32 02-JAN-00:10 273.10 02-JAN-20:10 242.16 02-JAN-20:10 0.00 0.00 0.00 0.00 79.64 31-JAN-16:30 224.79 01-JAN-08:00
February 220.32 01-FEB-00:10 273.10 01-FEB-20:10 242.16 01-FEB-20:10 0.00 0.00 0.00 0.00 10.11 18-FEB-14:20 172.52 28-FEB-07:00
March 220.32 01-MAR-00:10 273.10 01-MAR-20:10 242.16 01-MAR-20:10 0.00 0.00 0.00 0.00 77.33 16-MAR-15:00 224.01 26-MAR-06:00
April 220.32 01-APR-00:10 273.10 03-APR-19:10 242.16 03-APR-19:10 0.00 0.00 0.00 0.00 135.69 14-APR-15:40 138.25 21-APR-05:00
May 220.32 01-MAY-00:10 273.10 01-MAY-19:10 242.16 01-MAY-19:10 0.00 0.00 0.00 0.00 154.35 31-MAY-17:00 94.50 01-MAY-04:00
June 220.32 01-JUN-00:10 273.10 01-JUN-19:10 242.16 01-JUN-19:10 0.00 0.00 0.00 0.00 199.21 16-JUN-16:00 31.15 21-JUN-06:00
July 220.32 01-JUL-00:10 273.10 03-JUL-19:10 242.16 03-JUL-19:10 0.00 0.00 0.00 0.00 182.77 19-JUL-13:00 34.01 01-JUL-06:00
August 220.32 01-AUG-00:10 273.10 01-AUG-19:10 242.16 01-AUG-19:10 0.00 0.00 0.00 0.00 191.51 25-AUG-14:30 41.41 05-AUG-18:00
September 220.32 01-SEP-00:10 273.10 01-SEP-19:10 242.16 01-SEP-19:10 0.00 0.00 0.00 0.00 166.96 08-SEP-15:10 45.57 22-SEP-06:00
October 220.32 01-OCT-23:10 273.10 02-OCT-19:10 242.16 02-OCT-19:10 0.00 0.00 0.00 0.00 154.92 01-OCT-13:50 171.50 25-OCT-07:00
November 220.32 01-NOV-00:10 273.10 01-NOV-19:10 242.16 01-NOV-19:10 0.00 0.00 0.00 0.00 79.32 01-NOV-15:00 230.66 23-NOV-06:50
December 220.32 01-DEC-00:10 273.10 01-DEC-20:10 242.16 01-DEC-20:10 0.00 0.00 0.00 0.00 50.25 21-DEC-15:00 242.49 05-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 220.32   273.10   242.16   0.00 0.00 0.00 0.00 10.11   31.15  
Maximum of Months 220.32   273.10   242.16   0.00 0.00 0.00 0.00 199.21   242.49  



Table of Contents

Report: PeakSpaceGainsMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 907.20 02-JAN-00:10 337.37 02-JAN-20:10 4572.80 02-JAN-20:10 39726.58 02-JAN-20:10 0.00 0.00 0.00 188.60 31-JAN-16:15 532.00 01-JAN-08:00
February 907.20 01-FEB-00:10 337.37 01-FEB-20:10 4572.80 01-FEB-20:10 39726.58 01-FEB-20:10 0.00 0.00 0.00 23.85 18-FEB-14:00 417.97 01-FEB-08:00
March 907.20 01-MAR-00:10 337.37 01-MAR-20:10 4572.80 01-MAR-20:10 39726.58 01-MAR-20:10 0.00 0.00 0.00 183.05 16-MAR-15:20 530.03 26-MAR-05:40
April 907.20 01-APR-00:10 337.37 03-APR-19:10 4572.80 03-APR-19:10 39726.58 03-APR-19:10 0.00 0.00 0.00 321.42 14-APR-16:10 327.53 21-APR-04:20
May 907.20 01-MAY-00:10 337.37 01-MAY-19:10 4572.80 01-MAY-19:10 39726.58 01-MAY-19:10 0.00 0.00 0.00 365.28 31-MAY-16:10 223.62 01-MAY-04:00
June 907.20 01-JUN-00:10 337.37 01-JUN-19:10 4572.80 01-JUN-19:10 39726.58 01-JUN-19:10 0.00 0.00 0.00 472.74 28-JUN-15:40 73.79 21-JUN-06:00
July 907.20 01-JUL-00:10 337.37 03-JUL-19:10 4572.80 03-JUL-19:10 39726.58 03-JUL-19:10 0.00 0.00 0.00 433.07 19-JUL-13:00 73.31 01-JUL-06:00
August 907.20 01-AUG-00:10 337.37 01-AUG-19:10 4572.80 01-AUG-19:10 39726.58 01-AUG-19:10 0.00 0.00 0.00 453.36 25-AUG-14:20 121.48 05-AUG-18:20
September 907.20 01-SEP-00:10 337.37 01-SEP-19:10 4572.80 01-SEP-19:10 39726.58 01-SEP-19:10 0.00 0.00 0.00 395.30 08-SEP-15:07 111.41 22-SEP-06:10
October 907.20 01-OCT-23:10 337.37 02-OCT-19:10 4572.80 02-OCT-19:10 39726.58 02-OCT-19:10 0.00 0.00 0.00 366.41 01-OCT-14:00 417.65 25-OCT-07:00
November 907.20 01-NOV-00:10 337.37 01-NOV-19:10 4572.80 01-NOV-19:10 39726.58 01-NOV-19:10 0.00 0.00 0.00 187.51 01-NOV-15:00 545.77 23-NOV-07:00
December 907.20 01-DEC-00:10 337.37 01-DEC-20:10 4572.80 01-DEC-20:10 39726.58 01-DEC-20:10 0.00 0.00 0.00 119.12 25-DEC-15:10 573.95 05-DEC-04:00
                               
Annual Sum or Average                 0.00 0.00 0.00        
Minimum of Months 907.20   337.37   4572.80   39726.58   0.00 0.00 0.00 23.85   73.31  
Maximum of Months 907.20   337.37   4572.80   39726.58   0.00 0.00 0.00 472.74   573.95  



Table of Contents

Report: PeakSpaceGainsMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 15368.40 02-JAN-00:10 2177.23 02-JAN-20:10 965.27 02-JAN-20:10 0.00 0.00 0.00 0.00 293.12 31-JAN-17:00 944.27 01-JAN-08:00
February 15368.40 01-FEB-00:10 2177.23 01-FEB-20:10 965.27 01-FEB-20:10 0.00 0.00 0.00 0.00 42.51 18-FEB-14:50 724.65 28-FEB-07:00
March 15368.40 01-MAR-00:10 2177.23 01-MAR-20:10 965.27 01-MAR-20:10 0.00 0.00 0.00 0.00 324.45 20-MAR-17:00 941.05 26-MAR-06:00
April 15368.40 01-APR-00:10 2177.23 03-APR-19:10 965.27 03-APR-19:10 0.00 0.00 0.00 0.00 561.90 14-APR-17:00 581.03 21-APR-04:40
May 15368.40 01-MAY-00:10 2177.23 01-MAY-19:10 965.27 01-MAY-19:10 0.00 0.00 0.00 0.00 648.25 31-MAY-16:30 397.38 01-MAY-04:00
June 15368.40 01-JUN-00:10 2177.23 01-JUN-19:10 965.27 01-JUN-19:10 0.00 0.00 0.00 0.00 828.71 28-JUN-16:50 151.11 21-JUN-05:00
July 15368.40 01-JUL-00:10 2177.23 03-JUL-19:10 965.27 03-JUL-19:10 0.00 0.00 0.00 0.00 761.04 12-JUL-14:00 138.50 01-JUL-06:00
August 15368.40 01-AUG-00:10 2177.23 01-AUG-19:10 965.27 01-AUG-19:10 0.00 0.00 0.00 0.00 794.49 26-AUG-16:00 174.03 05-AUG-18:00
September 15368.40 01-SEP-00:10 2177.23 01-SEP-19:10 965.27 01-SEP-19:10 0.00 0.00 0.00 0.00 668.49 08-SEP-16:00 191.62 22-SEP-06:00
October 15368.40 01-OCT-23:10 2177.23 02-OCT-19:10 965.27 02-OCT-19:10 0.00 0.00 0.00 0.00 642.41 01-OCT-13:00 720.54 25-OCT-06:40
November 15368.40 01-NOV-00:10 2177.23 01-NOV-19:10 965.27 01-NOV-19:10 0.00 0.00 0.00 0.00 262.16 01-NOV-15:00 969.08 23-NOV-06:40
December 15368.40 01-DEC-00:10 2177.23 01-DEC-20:10 965.27 01-DEC-20:10 0.00 0.00 0.00 0.00 168.74 02-DEC-15:00 1018.63 05-DEC-04:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 15368.40   2177.23   965.27   0.00 0.00 0.00 0.00 42.51   138.50  
Maximum of Months 15368.40   2177.23   965.27   0.00 0.00 0.00 0.00 828.71   1018.63  



Table of Contents

Report: PeakSpaceGainsMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 45622.98 02-JAN-00:10 11849.32 02-JAN-20:10 10029.21 02-JAN-20:10 0.00 0.00 0.00 0.00 955.50 31-JAN-16:00 2697.45 01-JAN-08:00
February 45622.98 01-FEB-00:10 11849.32 01-FEB-20:10 10029.21 01-FEB-20:10 0.00 0.00 0.00 0.00 121.40 18-FEB-14:30 2070.41 28-FEB-07:00
March 45622.98 01-MAR-00:10 11849.32 01-MAR-20:10 10029.21 01-MAR-20:10 0.00 0.00 0.00 0.00 927.79 16-MAR-15:00 2688.39 26-MAR-06:00
April 45622.98 01-APR-00:10 11849.32 03-APR-19:10 10029.21 03-APR-19:10 0.00 0.00 0.00 0.00 1628.39 14-APR-15:00 1678.05 21-APR-04:30
May 45622.98 01-MAY-00:10 11849.32 01-MAY-19:10 10029.21 01-MAY-19:10 0.00 0.00 0.00 0.00 1852.35 31-MAY-16:50 1177.07 01-MAY-04:00
June 45622.98 01-JUN-00:10 11849.32 01-JUN-19:10 10029.21 01-JUN-19:10 0.00 0.00 0.00 0.00 2395.58 28-JUN-16:00 468.70 21-JUN-05:00
July 45622.98 01-JUL-00:10 11849.32 03-JUL-19:10 10029.21 03-JUL-19:10 0.00 0.00 0.00 0.00 2195.52 19-JUL-13:00 456.68 01-JUL-06:00
August 45622.98 01-AUG-00:10 11849.32 01-AUG-19:10 10029.21 01-AUG-19:10 0.00 0.00 0.00 0.00 2297.37 25-AUG-17:00 497.33 05-AUG-18:00
September 45622.98 01-SEP-00:10 11849.32 01-SEP-19:10 10029.21 01-SEP-19:10 0.00 0.00 0.00 0.00 1995.39 08-SEP-16:00 589.65 22-SEP-06:00
October 45622.98 01-OCT-23:10 11849.32 02-OCT-19:10 10029.21 02-OCT-19:10 0.00 0.00 0.00 0.00 1859.02 01-OCT-13:10 2058.32 25-OCT-07:00
November 45622.98 01-NOV-00:10 11849.32 01-NOV-19:10 10029.21 01-NOV-19:10 0.00 0.00 0.00 0.00 924.95 01-NOV-15:00 2768.36 23-NOV-06:10
December 45622.98 01-DEC-00:10 11849.32 01-DEC-20:10 10029.21 01-DEC-20:10 0.00 0.00 0.00 0.00 603.21 21-DEC-15:00 2910.34 05-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 45622.98   11849.32   10029.21   0.00 0.00 0.00 0.00 121.40   456.68  
Maximum of Months 45622.98   11849.32   10029.21   0.00 0.00 0.00 0.00 2395.58   2910.34  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 392.73 01-JAN-19:10 237.06 01-JAN-08:09 0.00 0.00 0.00 0.00 86.12 31-JAN-17:00 249.73 01-JAN-08:00
February 180.00 01-FEB-00:10 392.73 01-FEB-20:10 237.06 01-FEB-07:10 0.00 0.00 0.00 0.00 5.70 18-FEB-16:09 192.07 28-FEB-07:00
March 180.00 01-MAR-00:10 392.73 01-MAR-20:10 237.06 01-MAR-07:10 0.00 0.00 0.00 0.00 83.58 16-MAR-15:10 248.88 26-MAR-06:00
April 180.00 01-APR-00:10 392.73 01-APR-18:10 237.06 01-APR-07:10 0.00 0.00 0.00 0.00 147.98 14-APR-15:10 154.24 21-APR-04:00
May 180.00 01-MAY-00:10 392.73 01-MAY-19:10 237.06 01-MAY-06:10 0.00 0.00 0.00 0.00 168.57 31-MAY-17:00 105.99 01-MAY-04:00
June 180.00 01-JUN-00:10 392.73 01-JUN-19:10 237.06 01-JUN-06:10 0.00 0.00 0.00 0.00 218.32 16-JUN-16:00 35.61 21-JUN-06:00
July 180.00 01-JUL-00:10 392.73 01-JUL-18:10 237.06 01-JUL-07:10 0.00 0.00 0.00 0.00 197.82 20-JUL-15:10 35.86 01-JUL-06:00
August 180.00 01-AUG-00:10 392.73 01-AUG-19:10 237.06 01-AUG-06:10 0.00 0.00 0.00 0.00 209.48 25-AUG-16:00 68.50 05-AUG-18:00
September 180.00 01-SEP-00:10 392.73 01-SEP-19:10 237.06 01-SEP-06:10 0.00 0.00 0.00 0.00 182.45 08-SEP-15:10 52.00 22-SEP-06:00
October 180.00 01-OCT-00:10 392.73 01-OCT-18:10 237.06 01-OCT-07:10 0.00 0.00 0.00 0.00 148.37 03-OCT-16:00 190.93 25-OCT-07:00
November 180.00 01-NOV-00:10 392.73 01-NOV-19:10 237.06 01-NOV-06:10 0.00 0.00 0.00 0.00 83.99 01-NOV-15:10 256.21 23-NOV-06:00
December 180.00 01-DEC-00:10 392.73 01-DEC-20:10 237.06 01-DEC-07:10 0.00 0.00 0.00 0.00 49.89 25-DEC-16:10 269.28 05-DEC-04:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   392.73   237.06   0.00 0.00 0.00 0.00 5.70   35.61  
Maximum of Months 180.00   392.73   237.06   0.00 0.00 0.00 0.00 218.32   269.28  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 392.68 01-JAN-19:10 237.03 01-JAN-08:09 0.00 0.00 0.00 0.00 86.12 31-JAN-16:40 249.71 01-JAN-08:00
February 180.00 01-FEB-00:10 392.68 01-FEB-20:10 237.03 01-FEB-07:10 0.00 0.00 0.00 0.00 5.70 18-FEB-16:10 192.06 28-FEB-07:00
March 180.00 01-MAR-00:10 392.68 01-MAR-20:10 237.03 01-MAR-07:10 0.00 0.00 0.00 0.00 83.57 16-MAR-15:08 248.86 26-MAR-06:00
April 180.00 01-APR-00:10 392.68 01-APR-18:10 237.03 01-APR-07:10 0.00 0.00 0.00 0.00 147.97 14-APR-15:07 154.23 21-APR-04:20
May 180.00 01-MAY-00:10 392.68 01-MAY-19:10 237.03 01-MAY-06:10 0.00 0.00 0.00 0.00 168.56 31-MAY-17:00 105.98 01-MAY-04:00
June 180.00 01-JUN-00:10 392.68 01-JUN-19:10 237.03 01-JUN-06:10 0.00 0.00 0.00 0.00 218.29 16-JUN-16:00 35.60 21-JUN-06:00
July 180.00 01-JUL-00:10 392.68 01-JUL-18:10 237.03 01-JUL-07:10 0.00 0.00 0.00 0.00 197.81 20-JUL-15:10 35.86 01-JUL-06:00
August 180.00 01-AUG-00:10 392.68 01-AUG-19:10 237.03 01-AUG-06:10 0.00 0.00 0.00 0.00 209.47 25-AUG-16:50 66.76 05-AUG-18:00
September 180.00 01-SEP-00:10 392.68 01-SEP-19:10 237.03 01-SEP-06:10 0.00 0.00 0.00 0.00 182.47 08-SEP-15:10 51.99 22-SEP-06:00
October 180.00 01-OCT-00:10 392.68 01-OCT-18:10 237.03 01-OCT-07:10 0.00 0.00 0.00 0.00 148.35 03-OCT-16:00 190.91 25-OCT-07:00
November 180.00 01-NOV-00:10 392.68 01-NOV-19:10 237.03 01-NOV-06:10 0.00 0.00 0.00 0.00 83.98 01-NOV-15:10 256.19 23-NOV-06:00
December 180.00 01-DEC-00:10 392.68 01-DEC-20:10 237.03 01-DEC-07:10 0.00 0.00 0.00 0.00 49.88 25-DEC-16:07 269.26 05-DEC-04:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   392.68   237.03   0.00 0.00 0.00 0.00 5.70   35.60  
Maximum of Months 180.00   392.68   237.03   0.00 0.00 0.00 0.00 218.29   269.26  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 01-JAN-00:10 246.81 01-JAN-19:10 232.19 01-JAN-08:09 0.00 0.00 0.00 0.00 17.22 31-JAN-16:00 73.80 01-JAN-08:00
February 0.00 01-FEB-00:10 246.81 01-FEB-20:10 232.19 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 60.75 01-FEB-08:00
March 0.00 01-MAR-00:10 246.81 01-MAR-20:10 232.19 01-MAR-07:10 0.00 0.00 0.00 0.00 16.54 16-MAR-15:00 70.95 26-MAR-04:00
April 0.00 01-APR-00:10 246.81 01-APR-18:10 232.19 01-APR-07:10 0.00 0.00 0.00 0.00 34.66 14-APR-15:00 47.99 21-APR-04:00
May 0.00 01-MAY-00:10 246.81 01-MAY-19:10 232.19 01-MAY-06:10 0.00 0.00 0.00 0.00 40.44 31-MAY-17:00 36.39 01-MAY-04:00
June 0.00 01-JUN-00:10 246.81 01-JUN-19:10 232.19 01-JUN-06:10 0.00 0.00 0.00 0.00 54.48 28-JUN-16:00 16.93 21-JUN-06:00
July 0.00 01-JUL-00:10 246.81 01-JUL-18:10 232.19 01-JUL-07:10 0.00 0.00 0.00 0.00 49.25 19-JUL-13:00 16.92 01-JUL-06:00
August 0.00 01-AUG-00:10 246.81 01-AUG-19:10 232.19 01-AUG-06:10 0.00 0.00 0.00 0.00 51.95 25-AUG-14:00 20.31 05-AUG-18:00
September 0.00 01-SEP-00:10 246.81 01-SEP-19:10 232.19 01-SEP-06:10 0.00 0.00 0.00 0.00 44.33 08-SEP-15:00 20.74 22-SEP-06:00
October 0.00 01-OCT-00:10 246.81 01-OCT-18:10 232.19 01-OCT-07:10 0.00 0.00 0.00 0.00 40.58 01-OCT-13:00 60.57 25-OCT-07:00
November 0.00 01-NOV-00:10 246.81 01-NOV-19:10 232.19 01-NOV-06:10 0.00 0.00 0.00 0.00 17.15 01-NOV-15:00 74.90 23-NOV-06:30
December 0.00 01-DEC-00:10 246.81 01-DEC-20:10 232.19 01-DEC-07:10 0.00 0.00 0.00 0.00 8.11 21-DEC-15:00 78.70 05-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 0.00   246.81   232.19   0.00 0.00 0.00 0.00 0.00   16.92  
Maximum of Months 0.00   246.81   232.19   0.00 0.00 0.00 0.00 54.48   78.70  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 246.88 01-JAN-19:10 232.26 01-JAN-08:09 0.00 0.00 0.00 0.00 24.04 31-JAN-16:30 69.70 01-JAN-08:00
February 180.00 01-FEB-00:10 246.88 01-FEB-20:10 232.26 01-FEB-07:10 0.00 0.00 0.00 0.00 1.59 18-FEB-16:06 53.60 28-FEB-07:00
March 180.00 01-MAR-00:10 246.88 01-MAR-20:10 232.26 01-MAR-07:10 0.00 0.00 0.00 0.00 23.33 16-MAR-15:08 69.46 26-MAR-06:00
April 180.00 01-APR-00:10 246.88 01-APR-18:10 232.26 01-APR-07:10 0.00 0.00 0.00 0.00 41.30 14-APR-15:50 43.05 21-APR-04:00
May 180.00 01-MAY-00:10 246.88 01-MAY-19:10 232.26 01-MAY-06:10 0.00 0.00 0.00 0.00 47.05 31-MAY-17:00 29.58 01-MAY-04:00
June 180.00 01-JUN-00:10 246.88 01-JUN-19:10 232.26 01-JUN-06:10 0.00 0.00 0.00 0.00 60.99 28-JUN-16:00 9.94 21-JUN-06:00
July 180.00 01-JUL-00:10 246.88 01-JUL-18:10 232.26 01-JUL-07:10 0.00 0.00 0.00 0.00 55.21 20-JUL-15:10 10.01 01-JUL-06:00
August 180.00 01-AUG-00:10 246.88 01-AUG-19:10 232.26 01-AUG-06:10 0.00 0.00 0.00 0.00 58.46 25-AUG-17:00 17.51 05-AUG-18:00
September 180.00 01-SEP-00:10 246.88 01-SEP-19:10 232.26 01-SEP-06:10 0.00 0.00 0.00 0.00 50.93 08-SEP-15:08 14.51 22-SEP-06:00
October 180.00 01-OCT-00:10 246.88 01-OCT-18:10 232.26 01-OCT-07:10 0.00 0.00 0.00 0.00 41.41 03-OCT-16:00 53.29 25-OCT-07:00
November 180.00 01-NOV-00:10 246.88 01-NOV-19:10 232.26 01-NOV-06:10 0.00 0.00 0.00 0.00 23.44 01-NOV-15:08 71.50 23-NOV-06:00
December 180.00 01-DEC-00:10 246.88 01-DEC-20:10 232.26 01-DEC-07:10 0.00 0.00 0.00 0.00 13.92 25-DEC-16:08 75.15 05-DEC-04:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   246.88   232.26   0.00 0.00 0.00 0.00 1.59   9.94  
Maximum of Months 180.00   246.88   232.26   0.00 0.00 0.00 0.00 60.99   75.15  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 392.73 01-JAN-19:10 237.06 01-JAN-08:09 0.00 0.00 0.00 0.00 86.13 31-JAN-16:50 249.73 01-JAN-08:00
February 180.00 01-FEB-00:10 392.73 01-FEB-20:10 237.06 01-FEB-07:10 0.00 0.00 0.00 0.00 5.70 18-FEB-16:09 192.07 28-FEB-07:00
March 180.00 01-MAR-00:10 392.73 01-MAR-20:10 237.06 01-MAR-07:10 0.00 0.00 0.00 0.00 83.58 16-MAR-15:10 248.88 26-MAR-06:00
April 180.00 01-APR-00:10 392.73 01-APR-18:10 237.06 01-APR-07:10 0.00 0.00 0.00 0.00 147.98 14-APR-16:00 154.24 21-APR-04:00
May 180.00 01-MAY-00:10 392.73 01-MAY-19:10 237.06 01-MAY-06:10 0.00 0.00 0.00 0.00 168.58 31-MAY-17:00 105.99 01-MAY-04:00
June 180.00 01-JUN-00:10 392.73 01-JUN-19:10 237.06 01-JUN-06:10 0.00 0.00 0.00 0.00 218.53 28-JUN-16:00 35.61 21-JUN-06:00
July 180.00 01-JUL-00:10 392.73 01-JUL-18:10 237.06 01-JUL-07:10 0.00 0.00 0.00 0.00 197.83 20-JUL-15:10 35.86 01-JUL-06:00
August 180.00 01-AUG-00:10 392.73 01-AUG-19:10 237.06 01-AUG-06:10 0.00 0.00 0.00 0.00 209.48 25-AUG-15:10 69.66 05-AUG-18:00
September 180.00 01-SEP-00:10 392.73 01-SEP-19:10 237.06 01-SEP-06:10 0.00 0.00 0.00 0.00 182.48 08-SEP-15:10 52.00 22-SEP-06:00
October 180.00 01-OCT-00:10 392.73 01-OCT-18:10 237.06 01-OCT-07:10 0.00 0.00 0.00 0.00 148.37 03-OCT-16:00 190.93 25-OCT-07:00
November 180.00 01-NOV-00:10 392.73 01-NOV-19:10 237.06 01-NOV-06:10 0.00 0.00 0.00 0.00 83.99 01-NOV-15:10 256.21 23-NOV-06:00
December 180.00 01-DEC-00:10 392.73 01-DEC-20:10 237.06 01-DEC-07:10 0.00 0.00 0.00 0.00 49.89 25-DEC-16:10 269.28 05-DEC-04:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   392.73   237.06   0.00 0.00 0.00 0.00 5.70   35.61  
Maximum of Months 180.00   392.73   237.06   0.00 0.00 0.00 0.00 218.53   269.28  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 392.68 01-JAN-19:10 237.03 01-JAN-08:09 0.00 0.00 0.00 0.00 86.12 31-JAN-16:40 249.72 01-JAN-08:00
February 180.00 01-FEB-00:10 392.68 01-FEB-20:10 237.03 01-FEB-07:10 0.00 0.00 0.00 0.00 5.70 18-FEB-16:10 192.06 28-FEB-07:00
March 180.00 01-MAR-00:10 392.68 01-MAR-20:10 237.03 01-MAR-07:10 0.00 0.00 0.00 0.00 83.57 16-MAR-15:10 248.85 26-MAR-06:00
April 180.00 01-APR-00:10 392.68 01-APR-18:10 237.03 01-APR-07:10 0.00 0.00 0.00 0.00 147.97 14-APR-15:50 154.23 21-APR-05:00
May 180.00 01-MAY-00:10 392.68 01-MAY-19:10 237.03 01-MAY-06:10 0.00 0.00 0.00 0.00 168.57 31-MAY-17:00 105.98 01-MAY-04:00
June 180.00 01-JUN-00:10 392.68 01-JUN-19:10 237.03 01-JUN-06:10 0.00 0.00 0.00 0.00 218.51 28-JUN-16:00 35.60 21-JUN-06:00
July 180.00 01-JUL-00:10 392.68 01-JUL-18:10 237.03 01-JUL-07:10 0.00 0.00 0.00 0.00 197.81 20-JUL-15:10 35.86 01-JUL-06:00
August 180.00 01-AUG-00:10 392.68 01-AUG-19:10 237.03 01-AUG-06:10 0.00 0.00 0.00 0.00 209.46 25-AUG-15:08 67.93 05-AUG-18:00
September 180.00 01-SEP-00:10 392.68 01-SEP-19:10 237.03 01-SEP-06:10 0.00 0.00 0.00 0.00 182.47 08-SEP-15:10 51.99 22-SEP-06:00
October 180.00 01-OCT-00:10 392.68 01-OCT-18:10 237.03 01-OCT-07:10 0.00 0.00 0.00 0.00 148.35 03-OCT-16:00 190.91 25-OCT-07:00
November 180.00 01-NOV-00:10 392.68 01-NOV-19:10 237.03 01-NOV-06:10 0.00 0.00 0.00 0.00 83.98 01-NOV-15:10 256.19 23-NOV-06:30
December 180.00 01-DEC-00:10 392.68 01-DEC-20:10 237.03 01-DEC-07:10 0.00 0.00 0.00 0.00 49.88 25-DEC-16:07 269.26 05-DEC-04:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   392.68   237.03   0.00 0.00 0.00 0.00 5.70   35.60  
Maximum of Months 180.00   392.68   237.03   0.00 0.00 0.00 0.00 218.51   269.26  



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2263.36 02-JAN-00:10 1282.60 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 101.87 31-JAN-17:00 300.38 01-JAN-08:00
February 2263.36 01-FEB-00:10 1282.60 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 12.90 18-FEB-14:40 230.67 28-FEB-07:00
March 2263.36 01-MAR-00:10 1282.60 01-MAR-20:10 0.00 0.00 0.00 0.00 0.00 102.26 20-MAR-17:00 299.35 26-MAR-06:00
April 2263.36 01-APR-00:10 1282.60 03-APR-19:10 0.00 0.00 0.00 0.00 0.00 172.19 14-APR-17:00 184.95 21-APR-04:40
May 2263.36 01-MAY-00:10 1282.60 01-MAY-19:10 0.00 0.00 0.00 0.00 0.00 198.88 15-MAY-17:00 130.41 01-MAY-04:00
June 2263.36 01-JUN-00:10 1282.60 01-JUN-19:10 0.00 0.00 0.00 0.00 0.00 251.48 16-JUN-16:00 55.63 21-JUN-05:00
July 2263.36 01-JUL-00:10 1282.60 03-JUL-19:10 0.00 0.00 0.00 0.00 0.00 231.09 19-JUL-13:00 59.06 01-JUL-06:00
August 2263.36 01-AUG-00:10 1282.60 01-AUG-19:10 0.00 0.00 0.00 0.00 0.00 241.79 25-AUG-17:00 62.73 05-AUG-18:00
September 2263.36 01-SEP-00:10 1282.60 01-SEP-19:10 0.00 0.00 0.00 0.00 0.00 207.46 08-SEP-16:00 68.13 22-SEP-06:00
October 2263.36 01-OCT-23:10 1282.60 02-OCT-19:10 0.00 0.00 0.00 0.00 0.00 195.34 01-OCT-13:00 229.30 25-OCT-07:00
November 2263.36 01-NOV-00:10 1282.60 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 98.89 01-NOV-15:00 308.21 23-NOV-06:00
December 2263.36 01-DEC-00:10 1282.60 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 65.48 21-DEC-15:00 324.01 05-DEC-04:00
                           
Annual Sum or Average         0.00 0.00 0.00 0.00 0.00        
Minimum of Months 2263.36   1282.60   0.00 0.00 0.00 0.00 0.00 12.90   55.63  
Maximum of Months 2263.36   1282.60   0.00 0.00 0.00 0.00 0.00 251.48   324.01  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 392.73 01-JAN-19:10 237.06 01-JAN-08:09 0.00 0.00 0.00 0.00 85.49 31-JAN-17:00 250.51 01-JAN-08:00
February 180.00 01-FEB-00:10 392.73 01-FEB-20:10 237.06 01-FEB-07:10 0.00 0.00 0.00 0.00 5.04 18-FEB-16:10 192.82 28-FEB-07:00
March 180.00 01-MAR-00:10 392.73 01-MAR-20:10 237.06 01-MAR-07:10 0.00 0.00 0.00 0.00 82.95 16-MAR-15:10 249.64 26-MAR-06:00
April 180.00 01-APR-00:10 392.73 01-APR-18:10 237.06 01-APR-07:10 0.00 0.00 0.00 0.00 147.37 14-APR-16:00 154.97 21-APR-05:00
May 180.00 01-MAY-00:10 392.73 01-MAY-19:10 237.06 01-MAY-06:10 0.00 0.00 0.00 0.00 167.98 31-MAY-17:00 106.70 01-MAY-04:00
June 180.00 01-JUN-00:10 392.73 01-JUN-19:10 237.06 01-JUN-06:10 0.00 0.00 0.00 0.00 217.71 16-JUN-16:00 36.28 21-JUN-06:00
July 180.00 01-JUL-00:10 392.73 01-JUL-18:10 237.06 01-JUL-07:10 0.00 0.00 0.00 0.00 196.66 20-JUL-15:10 36.54 01-JUL-06:00
August 180.00 01-AUG-00:10 392.73 01-AUG-19:10 237.06 01-AUG-06:10 0.00 0.00 0.00 0.00 208.89 25-AUG-15:10 70.37 05-AUG-18:00
September 180.00 01-SEP-00:10 392.73 01-SEP-19:10 237.06 01-SEP-06:10 0.00 0.00 0.00 0.00 181.60 08-SEP-16:00 52.68 22-SEP-06:00
October 180.00 01-OCT-00:10 392.73 01-OCT-18:10 237.06 01-OCT-07:10 0.00 0.00 0.00 0.00 147.76 03-OCT-16:00 191.67 25-OCT-07:00
November 180.00 01-NOV-00:10 392.73 01-NOV-19:10 237.06 01-NOV-06:10 0.00 0.00 0.00 0.00 83.35 01-NOV-15:10 256.99 23-NOV-06:00
December 180.00 01-DEC-00:10 392.73 01-DEC-20:10 237.06 01-DEC-07:10 0.00 0.00 0.00 0.00 49.24 25-DEC-16:10 270.06 05-DEC-04:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   392.73   237.06   0.00 0.00 0.00 0.00 5.04   36.28  
Maximum of Months 180.00   392.73   237.06   0.00 0.00 0.00 0.00 217.71   270.06  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 392.68 01-JAN-19:10 237.03 01-JAN-08:09 0.00 0.00 0.00 0.00 85.48 31-JAN-16:50 250.49 01-JAN-08:00
February 180.00 01-FEB-00:10 392.68 01-FEB-20:10 237.03 01-FEB-07:10 0.00 0.00 0.00 0.00 5.04 18-FEB-16:07 192.80 28-FEB-07:00
March 180.00 01-MAR-00:10 392.68 01-MAR-20:10 237.03 01-MAR-07:10 0.00 0.00 0.00 0.00 82.94 16-MAR-15:10 249.63 26-MAR-06:00
April 180.00 01-APR-00:10 392.68 01-APR-18:10 237.03 01-APR-07:10 0.00 0.00 0.00 0.00 147.36 14-APR-16:00 154.96 21-APR-04:30
May 180.00 01-MAY-00:10 392.68 01-MAY-19:10 237.03 01-MAY-06:10 0.00 0.00 0.00 0.00 167.97 31-MAY-17:00 106.69 01-MAY-04:00
June 180.00 01-JUN-00:10 392.68 01-JUN-19:10 237.03 01-JUN-06:10 0.00 0.00 0.00 0.00 217.69 16-JUN-16:00 36.28 21-JUN-06:00
July 180.00 01-JUL-00:10 392.68 01-JUL-18:10 237.03 01-JUL-07:10 0.00 0.00 0.00 0.00 197.07 20-JUL-15:10 36.54 01-JUL-06:00
August 180.00 01-AUG-00:10 392.68 01-AUG-19:10 237.03 01-AUG-06:10 0.00 0.00 0.00 0.00 208.88 25-AUG-17:00 68.38 05-AUG-18:00
September 180.00 01-SEP-00:10 392.68 01-SEP-19:10 237.03 01-SEP-06:10 0.00 0.00 0.00 0.00 181.85 08-SEP-15:10 52.68 22-SEP-06:00
October 180.00 01-OCT-00:10 392.68 01-OCT-18:10 237.03 01-OCT-07:10 0.00 0.00 0.00 0.00 147.75 03-OCT-16:00 191.65 25-OCT-07:00
November 180.00 01-NOV-00:10 392.68 01-NOV-19:10 237.03 01-NOV-06:10 0.00 0.00 0.00 0.00 83.35 01-NOV-15:10 256.96 23-NOV-06:00
December 180.00 01-DEC-00:10 392.68 01-DEC-20:10 237.03 01-DEC-07:10 0.00 0.00 0.00 0.00 49.24 25-DEC-16:07 270.04 05-DEC-04:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   392.68   237.03   0.00 0.00 0.00 0.00 5.04   36.28  
Maximum of Months 180.00   392.68   237.03   0.00 0.00 0.00 0.00 217.69   270.04  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 246.88 01-JAN-19:10 232.26 01-JAN-08:09 0.00 0.00 0.00 0.00 43.74 31-JAN-17:00 128.17 01-JAN-08:00
February 180.00 01-FEB-00:10 246.88 01-FEB-20:10 232.26 01-FEB-07:10 0.00 0.00 0.00 0.00 2.58 18-FEB-16:10 98.65 28-FEB-07:00
March 180.00 01-MAR-00:10 246.88 01-MAR-20:10 232.26 01-MAR-07:10 0.00 0.00 0.00 0.00 42.44 16-MAR-15:10 127.73 26-MAR-06:00
April 180.00 01-APR-00:10 246.88 01-APR-18:10 232.26 01-APR-07:10 0.00 0.00 0.00 0.00 75.40 14-APR-16:00 79.29 21-APR-04:00
May 180.00 01-MAY-00:10 246.88 01-MAY-19:10 232.26 01-MAY-06:10 0.00 0.00 0.00 0.00 85.94 31-MAY-17:00 54.59 01-MAY-04:00
June 180.00 01-JUN-00:10 246.88 01-JUN-19:10 232.26 01-JUN-06:10 0.00 0.00 0.00 0.00 111.49 28-JUN-16:00 18.56 21-JUN-06:00
July 180.00 01-JUL-00:10 246.88 01-JUL-18:10 232.26 01-JUL-07:10 0.00 0.00 0.00 0.00 100.90 20-JUL-15:10 18.69 01-JUL-06:00
August 180.00 01-AUG-00:10 246.88 01-AUG-19:10 232.26 01-AUG-06:10 0.00 0.00 0.00 0.00 106.88 25-AUG-16:20 34.80 05-AUG-18:00
September 180.00 01-SEP-00:10 246.88 01-SEP-19:10 232.26 01-SEP-06:10 0.00 0.00 0.00 0.00 92.99 08-SEP-15:10 26.96 22-SEP-06:00
October 180.00 01-OCT-00:10 246.88 01-OCT-18:10 232.26 01-OCT-07:10 0.00 0.00 0.00 0.00 75.60 03-OCT-16:00 98.07 25-OCT-07:00
November 180.00 01-NOV-00:10 246.88 01-NOV-19:10 232.26 01-NOV-06:10 0.00 0.00 0.00 0.00 40.69 01-NOV-15:10 131.48 23-NOV-07:00
December 180.00 01-DEC-00:10 246.88 01-DEC-20:10 232.26 01-DEC-07:10 0.00 0.00 0.00 0.00 25.19 25-DEC-16:10 138.17 05-DEC-04:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   246.88   232.26   0.00 0.00 0.00 0.00 2.58   18.56  
Maximum of Months 180.00   246.88   232.26   0.00 0.00 0.00 0.00 111.49   138.17  



Table of Contents

Report: PeakSpaceGainsMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 26988.77 02-JAN-00:10 3823.39 02-JAN-20:10 6747.90 01-JAN-07:10 0.00 0.00 0.00 0.00 211.54 31-JAN-16:00 611.60 01-JAN-08:00
February 26988.77 01-FEB-00:10 3823.39 01-FEB-20:10 6747.90 01-FEB-07:10 0.00 0.00 0.00 0.00 24.52 18-FEB-14:10 480.68 01-FEB-05:30
March 26988.77 01-MAR-00:10 3823.39 01-MAR-20:10 6747.90 01-MAR-07:10 0.00 0.00 0.00 0.00 200.76 20-MAR-17:00 606.47 26-MAR-06:00
April 26988.77 01-APR-00:10 3823.39 03-APR-19:10 6747.90 01-APR-06:10 0.00 0.00 0.00 0.00 353.02 14-APR-17:00 395.06 21-APR-04:20
May 26988.77 01-MAY-00:10 3823.39 01-MAY-19:10 6747.90 01-MAY-06:10 0.00 0.00 0.00 0.00 401.61 15-MAY-17:00 284.44 01-MAY-04:00
June 26988.77 01-JUN-00:10 3823.39 01-JUN-19:10 6747.90 01-JUN-06:10 0.00 0.00 0.00 0.00 517.78 28-JUN-16:40 122.67 21-JUN-05:00
July 26988.77 01-JUL-00:10 3823.39 03-JUL-19:10 6747.90 01-JUL-06:10 0.00 0.00 0.00 0.00 483.78 19-JUL-13:00 125.89 01-JUL-06:00
August 26988.77 01-AUG-00:10 3823.39 01-AUG-19:10 6747.90 01-AUG-06:10 0.00 0.00 0.00 0.00 508.53 26-AUG-16:00 126.95 05-AUG-18:00
September 26988.77 01-SEP-00:10 3823.39 01-SEP-19:10 6747.90 01-SEP-06:10 0.00 0.00 0.00 0.00 434.92 08-SEP-15:00 152.64 22-SEP-06:00
October 26988.77 01-OCT-23:10 3823.39 02-OCT-19:10 6747.90 01-OCT-06:10 0.00 0.00 0.00 0.00 411.77 01-OCT-13:00 477.94 25-OCT-06:00
November 26988.77 01-NOV-00:10 3823.39 01-NOV-19:10 6747.90 01-NOV-06:10 0.00 0.00 0.00 0.00 206.46 01-NOV-15:00 625.14 23-NOV-07:00
December 26988.77 01-DEC-00:10 3823.39 01-DEC-20:10 6747.90 01-DEC-07:10 0.00 0.00 0.00 0.00 132.61 21-DEC-15:00 661.50 05-DEC-04:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 26988.77   3823.39   6747.90   0.00 0.00 0.00 0.00 24.52   122.67  
Maximum of Months 26988.77   3823.39   6747.90   0.00 0.00 0.00 0.00 517.78   661.50  



Table of Contents

Report: PeakSpaceGainsMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 26988.77 02-JAN-00:10 3823.39 02-JAN-20:10 6747.90 01-JAN-07:10 0.00 0.00 0.00 0.00 210.33 31-JAN-16:00 613.11 01-JAN-08:00
February 26988.77 01-FEB-00:10 3823.39 01-FEB-20:10 6747.90 01-FEB-07:10 0.00 0.00 0.00 0.00 24.50 18-FEB-15:40 481.29 01-FEB-05:30
March 26988.77 01-MAR-00:10 3823.39 01-MAR-20:10 6747.90 01-MAR-07:10 0.00 0.00 0.00 0.00 198.16 16-MAR-15:00 607.11 26-MAR-06:00
April 26988.77 01-APR-00:10 3823.39 03-APR-19:10 6747.90 01-APR-06:10 0.00 0.00 0.00 0.00 350.78 14-APR-17:00 396.02 21-APR-04:20
May 26988.77 01-MAY-00:10 3823.39 01-MAY-19:10 6747.90 01-MAY-06:10 0.00 0.00 0.00 0.00 398.97 15-MAY-17:00 285.44 01-MAY-04:00
June 26988.77 01-JUN-00:10 3823.39 01-JUN-19:10 6747.90 01-JUN-06:10 0.00 0.00 0.00 0.00 516.38 28-JUN-16:40 123.87 21-JUN-06:00
July 26988.77 01-JUL-00:10 3823.39 03-JUL-19:10 6747.90 01-JUL-06:10 0.00 0.00 0.00 0.00 481.52 19-JUL-13:00 126.58 01-JUL-06:00
August 26988.77 01-AUG-00:10 3823.39 01-AUG-19:10 6747.90 01-AUG-06:10 0.00 0.00 0.00 0.00 506.47 26-AUG-16:00 130.35 05-AUG-18:00
September 26988.77 01-SEP-00:10 3823.39 01-SEP-19:10 6747.90 01-SEP-06:10 0.00 0.00 0.00 0.00 433.31 08-SEP-15:00 154.29 22-SEP-06:00
October 26988.77 01-OCT-23:10 3823.39 02-OCT-19:10 6747.90 01-OCT-06:10 0.00 0.00 0.00 0.00 408.55 01-OCT-13:00 479.45 25-OCT-06:00
November 26988.77 01-NOV-00:10 3823.39 01-NOV-19:10 6747.90 01-NOV-06:10 0.00 0.00 0.00 0.00 204.33 01-NOV-15:00 626.09 23-NOV-07:00
December 26988.77 01-DEC-00:10 3823.39 01-DEC-20:10 6747.90 01-DEC-07:10 0.00 0.00 0.00 0.00 132.64 21-DEC-15:00 662.23 05-DEC-04:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 26988.77   3823.39   6747.90   0.00 0.00 0.00 0.00 24.50   123.87  
Maximum of Months 26988.77   3823.39   6747.90   0.00 0.00 0.00 0.00 516.38   662.23  



Table of Contents

Report: PeakSpaceGainsMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2401.70 02-JAN-00:10 1020.78 02-JAN-20:10 15112.11 01-JAN-07:10 22492.83 01-JAN-16:10 0.00 0.00 0.00 121.01 31-JAN-16:00 573.48 01-JAN-08:00
February 2401.70 01-FEB-00:10 1020.78 01-FEB-20:10 15112.11 01-FEB-07:10 22492.83 01-FEB-16:10 0.00 0.00 0.00 0.00 01-FEB-00:03 455.78 28-FEB-07:10
March 2401.70 01-MAR-00:10 1020.78 01-MAR-20:10 15112.11 01-MAR-07:10 22492.83 01-MAR-16:10 0.00 0.00 0.00 113.86 16-MAR-15:00 554.25 26-MAR-06:00
April 2401.70 01-APR-00:10 1020.78 03-APR-19:10 15112.11 01-APR-06:10 22492.83 01-APR-15:09 0.00 0.00 0.00 255.03 14-APR-15:40 359.47 21-APR-05:20
May 2401.70 01-MAY-00:10 1020.78 01-MAY-19:10 15112.11 01-MAY-06:10 22492.83 01-MAY-15:09 0.00 0.00 0.00 300.36 31-MAY-17:00 235.97 01-MAY-06:00
June 2401.70 01-JUN-00:10 1020.78 01-JUN-19:10 15112.11 01-JUN-06:10 22492.83 01-JUN-15:09 0.00 0.00 0.00 410.58 28-JUN-16:00 116.81 21-JUN-06:00
July 2401.70 01-JUL-00:10 1020.78 03-JUL-19:10 15112.11 01-JUL-06:10 22492.83 01-JUL-15:09 0.00 0.00 0.00 369.29 19-JUL-13:00 115.27 01-JUL-06:00
August 2401.70 01-AUG-00:10 1020.78 01-AUG-19:10 15112.11 01-AUG-06:10 22492.83 01-AUG-15:09 0.00 0.00 0.00 390.53 25-AUG-14:00 176.87 05-AUG-18:00
September 2401.70 01-SEP-00:10 1020.78 01-SEP-19:10 15112.11 01-SEP-06:10 22492.83 01-SEP-15:09 0.00 0.00 0.00 330.67 08-SEP-15:00 160.21 22-SEP-06:20
October 2401.70 01-OCT-23:10 1020.78 02-OCT-19:10 15112.11 01-OCT-06:10 22492.83 01-OCT-15:09 0.00 0.00 0.00 303.11 01-OCT-14:00 453.74 25-OCT-07:00
November 2401.70 01-NOV-00:10 1020.78 01-NOV-19:10 15112.11 01-NOV-06:10 22492.83 01-NOV-15:09 0.00 0.00 0.00 117.52 01-NOV-15:00 570.76 23-NOV-07:00
December 2401.70 01-DEC-00:10 1020.78 01-DEC-20:10 15112.11 01-DEC-07:10 22492.83 01-DEC-16:10 0.00 0.00 0.00 62.06 21-DEC-15:00 616.28 05-DEC-07:00
                               
Annual Sum or Average                 0.00 0.00 0.00        
Minimum of Months 2401.70   1020.78   15112.11   22492.83   0.00 0.00 0.00 0.00   115.27  
Maximum of Months 2401.70   1020.78   15112.11   22492.83   0.00 0.00 0.00 410.58   616.28  



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2395.44 02-JAN-00:10 1357.44 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 183.20 31-JAN-17:00 533.11 01-JAN-08:00
February 2395.44 01-FEB-00:10 1357.44 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 21.44 18-FEB-14:00 409.69 28-FEB-07:00
March 2395.44 01-MAR-00:10 1357.44 01-MAR-20:10 0.00 0.00 0.00 0.00 0.00 179.90 20-MAR-17:00 531.27 26-MAR-06:00
April 2395.44 01-APR-00:10 1357.44 03-APR-19:10 0.00 0.00 0.00 0.00 0.00 302.84 14-APR-17:00 328.83 21-APR-05:00
May 2395.44 01-MAY-00:10 1357.44 01-MAY-19:10 0.00 0.00 0.00 0.00 0.00 350.47 31-MAY-17:00 225.54 01-MAY-04:00
June 2395.44 01-JUN-00:10 1357.44 01-JUN-19:10 0.00 0.00 0.00 0.00 0.00 442.44 16-JUN-16:00 74.99 21-JUN-06:00
July 2395.44 01-JUL-00:10 1357.44 03-JUL-19:10 0.00 0.00 0.00 0.00 0.00 404.03 19-JUL-13:00 82.92 01-JUL-06:00
August 2395.44 01-AUG-00:10 1357.44 01-AUG-19:10 0.00 0.00 0.00 0.00 0.00 429.05 25-AUG-17:00 100.22 05-AUG-18:00
September 2395.44 01-SEP-00:10 1357.44 01-SEP-19:10 0.00 0.00 0.00 0.00 0.00 365.67 08-SEP-16:00 110.03 22-SEP-06:00
October 2395.44 01-OCT-23:10 1357.44 02-OCT-19:10 0.00 0.00 0.00 0.00 0.00 349.32 01-OCT-13:00 407.28 25-OCT-06:20
November 2395.44 01-NOV-00:10 1357.44 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 170.67 01-NOV-15:00 547.04 23-NOV-06:10
December 2395.44 01-DEC-00:10 1357.44 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 116.09 21-DEC-15:00 574.97 05-DEC-04:00
                           
Annual Sum or Average         0.00 0.00 0.00 0.00 0.00        
Minimum of Months 2395.44   1357.44   0.00 0.00 0.00 0.00 0.00 21.44   74.99  
Maximum of Months 2395.44   1357.44   0.00 0.00 0.00 0.00 0.00 442.44   574.97  



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 20832.38 19-JAN-19:10 62621.41 84105.23 67070.47 0.00 0.00 0.00 0.00 0.00 0.00
February 19838.18 01-FEB-21:00 8945.92 13517.00 10113.80 0.00 0.00 0.00 0.00 0.00 0.00
March 19880.00 16-MAR-19:30 8945.92 13517.00 10113.80 0.00 0.00 0.00 0.00 0.00 0.00
April 21387.37 13-APR-19:40 8945.92 13517.00 10113.80 0.00 0.00 0.00 0.00 0.00 0.00
May 20645.00 25-MAY-20:00 8945.92 13517.00 10113.80 0.00 0.00 0.00 0.00 0.00 0.00
June 21916.23 22-JUN-20:00 8945.92 13517.00 10113.80 0.00 0.00 0.00 0.00 0.00 0.00
July 24331.59 20-JUL-18:30 8945.92 12015.03 9581.50 0.00 0.00 0.00 0.00 0.00 0.00
August 24902.88 14-AUG-18:10 53675.50 72090.20 57488.97 0.00 0.00 0.00 0.00 0.00 0.00
September 25462.54 07-SEP-18:10 53675.50 72090.20 57488.97 0.00 0.00 0.00 0.00 0.00 0.00
October 24701.30 04-OCT-18:10 53675.50 72090.20 57488.97 0.00 0.00 0.00 0.00 0.00 0.00
November 23559.40 01-NOV-18:10 62621.41 84105.23 67070.47 0.00 0.00 0.00 0.00 0.00 0.00
December 22077.04 01-DEC-21:00 8945.92 13517.00 10113.80 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 19838.18   8945.92 12015.03 9581.50 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 25462.54   62621.41 84105.23 67070.47 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 3431.88 29-JAN-11:35 779.69 458.20 577.35 0.00 0.00 0.00 0.00 0.00 13.61
February 3063.03 26-FEB-11:35 779.69 458.20 577.35 0.00 0.00 0.00 0.00 0.00 116.73
March 3119.62 18-MAR-15:15 779.69 381.83 505.18 0.00 0.00 0.00 0.00 98.35 0.00
April 3460.60 14-APR-15:15 1299.48 381.83 505.18 0.00 0.00 0.00 0.00 235.40 0.00
May 3399.54 31-MAY-18:10 5457.82 3665.58 3897.11 0.00 0.00 0.00 0.00 268.34 0.00
June 4015.68 28-JUN-17:09 5197.92 3665.58 4041.45 0.00 0.00 0.00 0.00 360.03 0.00
July 3711.05 20-JUL-18:10 5457.82 3665.58 3897.11 0.00 0.00 0.00 0.00 314.75 0.00
August 3829.85 28-AUG-10:35 519.79 381.83 505.18 0.00 0.00 0.00 0.00 252.50 0.00
September 3799.74 28-SEP-15:15 1299.48 381.83 505.18 0.00 0.00 0.00 0.00 264.27 0.00
October 3785.99 06-OCT-10:35 519.79 381.83 505.18 0.00 0.00 0.00 0.00 174.44 0.00
November 3704.27 20-NOV-11:35 519.79 381.83 505.18 0.00 0.00 0.00 0.00 45.70 0.00
December 3513.64 25-DEC-11:35 779.69 458.20 577.35 0.00 0.00 0.00 0.00 1.09 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 3063.03   519.79 381.83 505.18 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 4015.68   5457.82 3665.58 4041.45 0.00 0.00 0.00 0.00 360.03 116.73



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2019.88 19-JAN-19:03 7373.52 4952.21 5265.02 0.00 0.00 0.00 0.00 0.00 9.50
February 1934.07 28-FEB-21:00 1053.36 795.89 793.93 0.00 0.00 0.00 0.00 0.00 63.64
March 2160.70 16-MAR-18:10 7373.52 4952.21 5265.02 0.00 0.00 0.00 0.00 30.82 0.00
April 2389.00 13-APR-18:10 7373.52 4952.21 5265.02 0.00 0.00 0.00 0.00 82.39 0.00
May 2437.05 31-MAY-18:10 6320.16 4244.75 4512.87 0.00 0.00 0.00 0.00 102.95 0.00
June 2660.74 28-JUN-18:10 5266.80 3537.29 3760.73 0.00 0.00 0.00 0.00 135.91 0.00
July 2551.13 20-JUL-18:10 6320.16 4244.75 4512.87 0.00 0.00 0.00 0.00 123.28 0.00
August 2529.36 14-AUG-18:10 6320.16 4244.75 4512.87 0.00 0.00 0.00 0.00 116.89 0.00
September 2505.41 07-SEP-18:10 6320.16 4244.75 4512.87 0.00 0.00 0.00 0.00 103.45 0.00
October 2380.28 04-OCT-18:10 6320.16 4244.75 4512.87 0.00 0.00 0.00 0.00 82.48 0.00
November 2181.91 01-NOV-18:10 7373.52 4952.21 5265.02 0.00 0.00 0.00 0.00 18.62 0.00
December 1975.03 22-DEC-21:00 1053.36 795.89 793.93 0.00 0.00 0.00 0.00 0.00 56.49
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1934.07   1053.36 795.89 793.93 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 2660.74   7373.52 4952.21 5265.02 0.00 0.00 0.00 0.00 135.91 63.64



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1930.17 27-JAN-21:00 222.77 1487.69 839.45 0.00 0.00 0.00 0.00 0.00 71.72
February 1735.07 16-FEB-21:00 222.77 1487.69 839.45 0.00 0.00 0.00 0.00 0.00 126.60
March 2175.36 16-MAR-19:10 445.54 2975.37 1678.89 0.00 0.00 0.00 0.00 44.20 0.00
April 2486.49 13-APR-18:20 445.54 2644.77 1590.53 0.00 0.00 0.00 0.00 192.58 0.00
May 2636.70 31-MAY-18:03 1336.61 7934.32 4771.59 0.00 0.00 0.00 0.00 245.91 0.00
June 2935.25 28-JUN-18:10 1113.84 6611.94 3976.33 0.00 0.00 0.00 0.00 321.22 0.00
July 2829.51 22-JUL-10:35 190.94 826.49 618.54 0.00 0.00 0.00 0.00 245.55 0.00
August 2751.92 14-AUG-18:10 1336.61 7934.32 4771.59 0.00 0.00 0.00 0.00 278.08 0.00
September 2686.88 07-SEP-18:10 1336.61 7934.32 4771.59 0.00 0.00 0.00 0.00 248.18 0.00
October 2585.01 02-OCT-18:10 1336.61 7934.32 4771.59 0.00 0.00 0.00 0.00 194.00 0.00
November 2178.47 01-NOV-19:10 445.54 2975.37 1678.89 0.00 0.00 0.00 0.00 14.61 0.00
December 1744.35 22-DEC-21:00 222.77 1487.69 839.45 0.00 0.00 0.00 0.00 0.00 126.80
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1735.07   190.94 826.49 618.54 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 2935.25   1336.61 7934.32 4771.59 0.00 0.00 0.00 0.00 321.22 126.80



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 676.66 27-JAN-20:50 171.36 273.10 242.16 0.00 0.00 0.00 0.00 0.00 37.89
February 568.01 22-FEB-21:50 195.84 242.76 229.41 0.00 0.00 0.00 0.00 0.00 83.63
March 897.17 17-MAR-21:00 195.84 242.76 229.41 0.00 0.00 0.00 0.00 6.09 0.00
April 1149.68 13-APR-20:00 171.36 273.10 242.16 0.00 0.00 0.00 0.00 79.20 0.00
May 1258.25 31-MAY-19:00 171.36 242.76 229.41 0.00 0.00 0.00 0.00 126.33 0.00
June 1483.82 28-JUN-17:09 979.20 1456.53 1427.45 0.00 0.00 0.00 0.00 195.29 0.00
July 1437.03 22-JUL-10:35 146.88 151.73 178.43 0.00 0.00 0.00 0.00 141.48 0.00
August 1368.46 14-AUG-18:10 1028.16 1456.53 1376.47 0.00 0.00 0.00 0.00 161.85 0.00
September 1300.38 07-SEP-18:15 342.72 485.51 458.82 0.00 0.00 0.00 0.00 141.36 0.00
October 1218.09 02-OCT-19:10 342.72 546.20 484.31 0.00 0.00 0.00 0.00 83.90 0.00
November 877.74 02-NOV-21:00 195.84 242.76 229.41 0.00 0.00 0.00 0.00 0.00 10.24
December 594.47 26-DEC-22:00 195.84 242.76 229.41 0.00 0.00 0.00 0.00 0.00 62.57
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 568.01   146.88 151.73 178.43 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 1483.82   1028.16 1456.53 1427.45 0.00 0.00 0.00 0.00 195.29 83.63



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 36375.38 27-JAN-21:00 705.60 337.37 4572.80 39726.58 0.00 0.00 0.00 0.00 171.16
February 36045.16 21-FEB-21:00 705.60 337.37 4572.80 39726.58 0.00 0.00 0.00 0.00 221.19
March 36763.18 16-MAR-20:00 705.60 337.37 4572.80 39726.58 0.00 0.00 0.00 0.00 41.05
April 37764.33 13-APR-20:00 705.60 337.37 4572.80 39726.58 0.00 0.00 0.00 124.27 0.00
May 38012.93 18-MAY-20:00 705.60 337.37 4572.80 39726.58 0.00 0.00 0.00 148.16 0.00
June 38927.46 29-JUN-20:00 705.60 337.37 4572.80 39726.58 0.00 0.00 0.00 311.28 0.00
July 38718.16 20-JUL-20:00 705.60 337.37 4572.80 39726.58 0.00 0.00 0.00 289.34 0.00
August 38451.97 14-AUG-20:00 705.60 337.37 4572.80 39726.58 0.00 0.00 0.00 242.39 0.00
September 38365.43 07-SEP-20:00 705.60 337.37 4572.80 39726.58 0.00 0.00 0.00 238.79 0.00
October 37804.39 04-OCT-20:00 705.60 337.37 4572.80 39726.58 0.00 0.00 0.00 102.28 0.00
November 36692.89 01-NOV-20:00 705.60 337.37 4572.80 39726.58 0.00 0.00 0.00 0.00 70.35
December 36097.10 22-DEC-21:00 705.60 337.37 4572.80 39726.58 0.00 0.00 0.00 0.00 247.21
                       
Annual Sum or Average             0.00 0.00 0.00    
Minimum of Months 36045.16   705.60 337.37 4572.80 39726.58 0.00 0.00 0.00 0.00 0.00
Maximum of Months 38927.46   705.60 337.37 4572.80 39726.58 0.00 0.00 0.00 311.28 247.21



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 13927.77 29-JAN-11:35 10245.60 1451.48 812.86 0.00 0.00 0.00 0.00 0.00 24.12
February 12648.84 26-FEB-11:35 10245.60 1451.48 812.86 0.00 0.00 0.00 0.00 0.00 257.91
March 12865.92 18-MAR-17:12 40982.40 5805.94 2845.02 0.00 0.00 0.00 0.00 227.17 0.00
April 14100.94 13-APR-18:10 83672.40 13547.18 6401.28 0.00 0.00 0.00 0.00 468.03 0.00
May 14186.01 31-MAY-18:10 71719.20 11611.87 5486.82 0.00 0.00 0.00 0.00 590.15 0.00
June 15774.43 28-JUN-17:09 68304.00 11611.87 5690.03 0.00 0.00 0.00 0.00 813.75 0.00
July 15189.66 20-JUL-18:10 71719.20 11611.87 5486.82 0.00 0.00 0.00 0.00 699.04 0.00
August 14957.86 14-AUG-18:10 71719.20 11611.87 5486.82 0.00 0.00 0.00 0.00 664.80 0.00
September 14991.41 07-SEP-18:10 71719.20 11611.87 5486.82 0.00 0.00 0.00 0.00 583.92 0.00
October 14782.53 05-OCT-15:25 17076.00 1209.57 711.25 0.00 0.00 0.00 0.00 473.21 0.00
November 14374.56 01-NOV-15:13 25614.00 1814.35 1066.88 0.00 0.00 0.00 0.00 245.45 0.00
December 14204.15 25-DEC-11:35 10245.60 1451.48 812.86 0.00 0.00 0.00 0.00 9.78 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 12648.84   10245.60 1209.57 711.25 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 15774.43   83672.40 13547.18 6401.28 0.00 0.00 0.00 0.00 813.75 257.91



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 39304.20 27-JAN-21:00 35484.54 11849.32 10029.21 0.00 0.00 0.00 0.00 0.00 567.66
February 38023.91 22-FEB-19:10 177422.70 52663.63 47506.78 0.00 0.00 0.00 0.00 0.00 541.64
March 41899.58 16-MAR-18:10 248391.78 73729.08 66509.49 0.00 0.00 0.00 0.00 490.36 0.00
April 45649.03 13-APR-18:10 248391.78 73729.08 66509.49 0.00 0.00 0.00 0.00 1346.51 0.00
May 46612.00 31-MAY-18:10 212907.24 63196.36 57008.13 0.00 0.00 0.00 0.00 1681.94 0.00
June 50442.95 28-JUN-18:10 177422.70 52663.63 47506.78 0.00 0.00 0.00 0.00 2229.63 0.00
July 49091.72 20-JUL-18:10 212907.24 63196.36 57008.13 0.00 0.00 0.00 0.00 2008.82 0.00
August 48321.24 14-AUG-18:10 212907.24 63196.36 57008.13 0.00 0.00 0.00 0.00 1911.14 0.00
September 47846.97 07-SEP-18:10 212907.24 63196.36 57008.13 0.00 0.00 0.00 0.00 1691.43 0.00
October 46105.89 04-OCT-18:10 212907.24 63196.36 57008.13 0.00 0.00 0.00 0.00 1335.73 0.00
November 42159.81 01-NOV-18:10 248391.78 73729.08 66509.49 0.00 0.00 0.00 0.00 293.66 0.00
December 38523.23 22-DEC-21:00 35484.54 11849.32 10029.21 0.00 0.00 0.00 0.00 0.00 942.26
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 38023.91   35484.54 11849.32 10029.21 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 50442.95   248391.78 73729.08 66509.49 0.00 0.00 0.00 0.00 2229.63 942.26



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 3933.56 31-JAN-16:01 680.40 769.75 479.39 0.00 0.00 0.00 0.00 71.11 0.00
February 3875.28 28-FEB-16:01 680.40 769.75 479.39 0.00 0.00 0.00 0.00 0.00 38.56
March 3904.94 09-MAR-16:01 680.40 769.75 479.39 0.00 0.00 0.00 0.00 2.96 0.00
April 3984.34 14-APR-18:01 970.20 2446.69 903.46 0.00 0.00 0.00 0.00 116.44 0.00
May 3963.16 05-MAY-15:01 680.40 769.75 479.39 0.00 0.00 0.00 0.00 131.43 0.00
June 4002.28 27-JUN-18:02 831.60 2097.16 774.39 0.00 0.00 0.00 0.00 180.49 0.00
July 3977.91 05-JUL-18:02 831.60 2097.16 774.39 0.00 0.00 0.00 0.00 161.83 0.00
August 3985.36 27-AUG-15:02 324.00 777.60 458.31 0.00 0.00 0.00 0.00 183.17 0.00
September 3971.63 28-SEP-15:02 583.20 659.78 410.90 0.00 0.00 0.00 0.00 158.80 0.00
October 3995.96 06-OCT-15:01 680.40 769.75 479.39 0.00 0.00 0.00 0.00 131.65 0.00
November 3962.28 20-NOV-16:01 680.40 769.75 479.39 0.00 0.00 0.00 0.00 46.75 0.00
December 3919.89 24-DEC-16:01 378.00 907.20 534.70 0.00 0.00 0.00 0.00 3.96 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 3875.28   324.00 659.78 410.90 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 4002.28   970.20 2446.69 903.46 0.00 0.00 0.00 0.00 183.17 38.56



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 3842.68 31-JAN-16:01 680.40 769.66 479.33 0.00 0.00 0.00 0.00 73.01 0.00
February 3786.16 28-FEB-16:01 680.40 769.66 479.33 0.00 0.00 0.00 0.00 0.00 36.64
March 3852.38 18-MAR-18:01 819.00 2748.77 903.35 0.00 0.00 0.00 0.00 30.86 0.00
April 3953.19 25-APR-18:01 970.20 2446.40 903.35 0.00 0.00 0.00 0.00 97.89 0.00
May 3938.21 27-MAY-18:01 819.00 2748.77 903.35 0.00 0.00 0.00 0.00 78.79 0.00
June 3988.52 27-JUN-18:02 831.60 2096.92 774.30 0.00 0.00 0.00 0.00 180.14 0.00
July 3962.66 05-JUL-18:02 831.60 2096.92 774.30 0.00 0.00 0.00 0.00 161.53 0.00
August 3951.46 25-AUG-18:02 831.60 2096.92 774.30 0.00 0.00 0.00 0.00 170.62 0.00
September 3905.04 28-SEP-15:02 583.20 659.70 410.85 0.00 0.00 0.00 0.00 159.94 0.00
October 3928.54 06-OCT-15:01 680.40 769.66 479.33 0.00 0.00 0.00 0.00 132.81 0.00
November 3872.04 20-NOV-16:01 680.40 769.66 479.33 0.00 0.00 0.00 0.00 48.64 0.00
December 3819.70 24-DEC-16:01 378.00 907.09 534.64 0.00 0.00 0.00 0.00 6.18 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 3786.16   378.00 659.70 410.85 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3988.52   970.20 2748.77 903.35 0.00 0.00 0.00 0.00 180.14 36.64



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 772.41 14-JAN-13:40 0.00 81.45 74.82 0.00 0.00 0.00 0.00 10.18 0.00
February 596.69 01-FEB-15:30 0.00 69.11 67.08 0.00 0.00 0.00 0.00 0.00 25.11
March 584.14 18-MAR-13:40 0.00 81.45 74.82 0.00 0.00 0.00 0.00 8.95 0.00
April 596.23 14-APR-13:40 0.00 69.11 67.08 0.00 0.00 0.00 0.00 31.84 0.00
May 549.72 07-MAY-20:03 0.00 740.44 541.78 0.00 0.00 0.00 0.00 22.14 0.00
June 660.86 28-JUN-19:10 0.00 493.63 340.55 0.00 0.00 0.00 0.00 47.44 0.00
July 646.26 22-JUL-19:10 0.00 246.81 170.27 0.00 0.00 0.00 0.00 36.64 0.00
August 678.75 27-AUG-14:00 0.00 81.45 74.82 0.00 0.00 0.00 0.00 48.97 0.00
September 746.19 28-SEP-13:40 0.00 69.11 67.08 0.00 0.00 0.00 0.00 39.09 0.00
October 762.89 18-OCT-13:40 0.00 69.11 67.08 0.00 0.00 0.00 0.00 22.19 0.00
November 792.74 20-NOV-14:30 0.00 69.11 67.08 0.00 0.00 0.00 0.00 11.13 0.00
December 766.96 25-DEC-13:30 0.00 81.45 74.82 0.00 0.00 0.00 0.00 6.55 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 549.72   0.00 69.11 67.08 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 792.74   0.00 740.44 541.78 0.00 0.00 0.00 0.00 48.97 25.11



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1356.97 31-JAN-19:01 970.20 1538.07 885.15 0.00 0.00 0.00 0.00 3.08 0.00
February 1281.09 22-FEB-16:02 583.20 414.76 402.58 0.00 0.00 0.00 0.00 0.00 1.33
March 1414.35 16-MAR-18:01 970.20 1538.07 885.15 0.00 0.00 0.00 0.00 8.17 0.00
April 1437.43 25-APR-18:01 970.20 1538.07 885.15 0.00 0.00 0.00 0.00 26.87 0.00
May 1435.88 26-MAY-18:01 970.20 1538.07 885.15 0.00 0.00 0.00 0.00 23.86 0.00
June 1441.83 26-JUN-18:02 831.60 1318.35 758.70 0.00 0.00 0.00 0.00 47.38 0.00
July 1438.79 07-JUL-18:02 831.60 1318.35 758.70 0.00 0.00 0.00 0.00 41.78 0.00
August 1433.05 25-AUG-18:02 831.60 1318.35 758.70 0.00 0.00 0.00 0.00 47.26 0.00
September 1436.39 27-SEP-18:01 970.20 1538.07 885.15 0.00 0.00 0.00 0.00 33.33 0.00
October 1431.99 06-OCT-15:01 680.40 483.89 469.67 0.00 0.00 0.00 0.00 36.55 0.00
November 1349.72 09-NOV-19:01 970.20 1538.07 885.15 0.00 0.00 0.00 0.00 0.00 1.13
December 1291.70 25-DEC-16:02 324.00 488.83 449.03 0.00 0.00 0.00 0.00 13.23 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1281.09   324.00 414.76 402.58 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 1441.83   970.20 1538.07 885.15 0.00 0.00 0.00 0.00 47.38 1.33



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 3472.52 31-JAN-16:01 680.40 769.75 479.39 0.00 0.00 0.00 0.00 71.49 0.00
February 3424.03 21-FEB-16:01 680.40 769.75 479.39 0.00 0.00 0.00 0.00 0.00 18.67
March 3456.68 23-MAR-15:01 680.40 769.75 479.39 0.00 0.00 0.00 0.00 26.20 0.00
April 3522.10 14-APR-15:01 680.40 769.75 479.39 0.00 0.00 0.00 0.00 132.26 0.00
May 3529.17 18-MAY-08:61 252.00 1209.60 792.83 0.00 0.00 0.00 0.00 51.78 0.00
June 3553.90 19-JUN-08:61 252.00 1209.60 792.83 0.00 0.00 0.00 0.00 91.52 0.00
July 3535.05 01-JUL-08:61 378.00 1539.49 1143.15 0.00 0.00 0.00 0.00 53.24 0.00
August 3545.21 27-AUG-08:61 378.00 1539.49 1143.15 0.00 0.00 0.00 0.00 76.19 0.00
September 3514.89 28-SEP-15:02 583.20 659.78 410.90 0.00 0.00 0.00 0.00 158.90 0.00
October 3534.90 06-OCT-15:01 680.40 769.75 479.39 0.00 0.00 0.00 0.00 131.79 0.00
November 3480.30 20-NOV-16:01 680.40 769.75 479.39 0.00 0.00 0.00 0.00 47.72 0.00
December 3451.03 24-DEC-16:01 378.00 907.20 534.70 0.00 0.00 0.00 0.00 4.67 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 3424.03   252.00 659.78 410.90 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3553.90   680.40 1539.49 1143.15 0.00 0.00 0.00 0.00 158.90 18.67



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 3389.26 31-JAN-16:01 680.40 769.66 479.33 0.00 0.00 0.00 0.00 73.53 0.00
February 3172.39 21-FEB-16:01 680.40 769.66 479.33 0.00 0.00 0.00 0.00 0.00 7.95
March 3414.04 19-MAR-15:01 378.00 907.09 534.64 0.00 0.00 0.00 0.00 41.32 0.00
April 3478.64 14-APR-15:01 680.40 769.66 479.33 0.00 0.00 0.00 0.00 132.95 0.00
May 3510.57 18-MAY-08:61 252.00 1209.46 792.74 0.00 0.00 0.00 0.00 51.67 0.00
June 3538.72 19-JUN-08:61 252.00 1209.46 792.74 0.00 0.00 0.00 0.00 91.30 0.00
July 3519.82 01-JUL-08:61 378.00 1539.31 1143.02 0.00 0.00 0.00 0.00 53.02 0.00
August 3521.28 27-AUG-08:61 378.00 1539.31 1143.02 0.00 0.00 0.00 0.00 76.26 0.00
September 3487.31 18-SEP-08:61 252.00 1209.46 792.74 0.00 0.00 0.00 0.00 56.24 0.00
October 3475.28 06-OCT-15:01 680.40 769.66 479.33 0.00 0.00 0.00 0.00 132.99 0.00
November 3393.87 10-NOV-16:01 680.40 769.66 479.33 0.00 0.00 0.00 0.00 24.40 0.00
December 3199.42 24-DEC-09:01 378.00 1539.31 1143.02 0.00 0.00 0.00 0.00 0.00 69.05
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 3172.39   252.00 769.66 479.33 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3538.72   680.40 1539.31 1143.02 0.00 0.00 0.00 0.00 132.99 69.05



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2568.69 29-JAN-11:35 1508.90 855.07 0.00 0.00 0.00 0.00 0.00 3.92 0.00
February 2218.73 22-FEB-16:50 1257.42 356.28 0.00 0.00 0.00 0.00 0.00 0.00 12.57
March 2734.44 18-MAR-18:03 10562.33 6983.06 0.00 0.00 0.00 0.00 0.00 52.18 0.00
April 3149.75 15-APR-10:35 1508.90 712.56 0.00 0.00 0.00 0.00 0.00 85.02 0.00
May 3224.60 18-MAY-18:10 10562.33 6840.55 0.00 0.00 0.00 0.00 0.00 167.04 0.00
June 3709.51 28-JUN-17:09 10059.36 6840.55 0.00 0.00 0.00 0.00 0.00 246.18 0.00
July 3560.92 22-JUL-10:35 1508.90 712.56 0.00 0.00 0.00 0.00 0.00 175.65 0.00
August 3496.20 14-AUG-18:10 10562.33 6840.55 0.00 0.00 0.00 0.00 0.00 200.06 0.00
September 3444.43 09-SEP-10:35 1508.90 712.56 0.00 0.00 0.00 0.00 0.00 150.05 0.00
October 3270.49 04-OCT-18:10 10562.33 6840.55 0.00 0.00 0.00 0.00 0.00 138.62 0.00
November 2775.73 01-NOV-18:10 12322.72 7980.64 0.00 0.00 0.00 0.00 0.00 30.75 0.00
December 2568.11 25-DEC-11:35 1508.90 855.07 0.00 0.00 0.00 0.00 0.00 17.43 0.00
                       
Annual Sum or Average         0.00 0.00 0.00 0.00 0.00    
Minimum of Months 2218.73   1257.42 356.28 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3709.51   12322.72 7980.64 0.00 0.00 0.00 0.00 0.00 246.18 12.57



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 4236.81 31-JAN-16:01 680.40 769.75 479.39 0.00 0.00 0.00 0.00 70.65 0.00
February 4170.26 28-FEB-16:01 680.40 769.75 479.39 0.00 0.00 0.00 0.00 0.00 38.90
March 4207.32 09-MAR-16:01 680.40 769.75 479.39 0.00 0.00 0.00 0.00 2.45 0.00
April 4310.91 14-APR-15:01 680.40 769.75 479.39 0.00 0.00 0.00 0.00 131.10 0.00
May 4289.81 15-MAY-15:01 680.40 769.75 479.39 0.00 0.00 0.00 0.00 141.97 0.00
June 4326.35 27-JUN-18:02 831.60 2097.16 774.39 0.00 0.00 0.00 0.00 179.68 0.00
July 4296.45 05-JUL-18:02 831.60 2097.16 774.39 0.00 0.00 0.00 0.00 161.11 0.00
August 4313.46 27-AUG-15:02 324.00 777.60 458.31 0.00 0.00 0.00 0.00 182.22 0.00
September 4296.77 28-SEP-15:02 583.20 659.78 410.90 0.00 0.00 0.00 0.00 157.89 0.00
October 4312.48 06-OCT-15:01 680.40 769.75 479.39 0.00 0.00 0.00 0.00 131.00 0.00
November 4275.63 20-NOV-16:01 680.40 769.75 479.39 0.00 0.00 0.00 0.00 46.09 0.00
December 4215.93 24-DEC-16:01 378.00 907.20 534.70 0.00 0.00 0.00 0.00 3.66 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 4170.26   324.00 659.78 410.90 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 4326.35   831.60 2097.16 774.39 0.00 0.00 0.00 0.00 182.22 38.90



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 4128.91 31-JAN-16:01 680.40 769.66 479.33 0.00 0.00 0.00 0.00 72.76 0.00
February 4063.54 28-FEB-16:01 680.40 769.66 479.33 0.00 0.00 0.00 0.00 0.00 36.76
March 4147.25 18-MAR-18:01 819.00 2748.77 903.35 0.00 0.00 0.00 0.00 30.38 0.00
April 4267.38 25-APR-18:01 970.20 2446.40 903.35 0.00 0.00 0.00 0.00 97.13 0.00
May 4254.33 15-MAY-15:01 680.40 769.66 479.33 0.00 0.00 0.00 0.00 142.08 0.00
June 4309.62 27-JUN-18:02 831.60 2096.92 774.30 0.00 0.00 0.00 0.00 179.30 0.00
July 4277.98 05-JUL-18:02 831.60 2096.92 774.30 0.00 0.00 0.00 0.00 160.78 0.00
August 4270.71 25-AUG-18:02 831.60 2096.92 774.30 0.00 0.00 0.00 0.00 169.74 0.00
September 4220.15 28-SEP-15:02 583.20 659.70 410.85 0.00 0.00 0.00 0.00 159.08 0.00
October 4234.99 06-OCT-15:01 680.40 769.66 479.33 0.00 0.00 0.00 0.00 132.22 0.00
November 4167.71 20-NOV-16:01 680.40 769.66 479.33 0.00 0.00 0.00 0.00 48.19 0.00
December 4094.01 24-DEC-16:01 378.00 907.09 534.64 0.00 0.00 0.00 0.00 6.19 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 4063.54   378.00 659.70 410.85 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 4309.62   970.20 2748.77 903.35 0.00 0.00 0.00 0.00 179.30 36.76



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2213.20 31-JAN-16:01 680.40 483.89 469.67 0.00 0.00 0.00 0.00 34.54 0.00
February 2165.85 21-FEB-16:01 680.40 483.89 469.67 0.00 0.00 0.00 0.00 0.00 11.17
March 2185.98 18-MAR-15:02 324.00 488.83 449.03 0.00 0.00 0.00 0.00 25.49 0.00
April 2210.67 14-APR-15:01 680.40 483.89 469.67 0.00 0.00 0.00 0.00 66.57 0.00
May 2188.49 06-MAY-15:01 378.00 570.30 523.86 0.00 0.00 0.00 0.00 62.24 0.00
June 2183.53 27-JUN-15:02 583.20 414.76 402.58 0.00 0.00 0.00 0.00 98.45 0.00
July 2174.64 07-JUL-15:02 583.20 414.76 402.58 0.00 0.00 0.00 0.00 78.31 0.00
August 2204.54 26-AUG-15:02 324.00 488.83 449.03 0.00 0.00 0.00 0.00 98.15 0.00
September 2222.78 28-SEP-15:02 583.20 414.76 402.58 0.00 0.00 0.00 0.00 79.78 0.00
October 2230.66 06-OCT-15:01 680.40 483.89 469.67 0.00 0.00 0.00 0.00 66.02 0.00
November 2224.84 20-NOV-16:01 680.40 483.89 469.67 0.00 0.00 0.00 0.00 22.19 0.00
December 2209.87 24-DEC-16:01 378.00 570.30 523.86 0.00 0.00 0.00 0.00 0.03 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2165.85   324.00 414.76 402.58 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 2230.66   680.40 570.30 523.86 0.00 0.00 0.00 0.00 98.45 11.17



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 19862.35 06-JAN-22:20 26988.77 2548.93 6747.90 0.00 0.00 0.00 0.00 0.00 150.03
February 19767.66 15-FEB-23:00 26988.77 2548.93 6747.90 0.00 0.00 0.00 0.00 0.00 213.36
March 21110.37 16-MAR-18:10 146938.85 23790.00 47235.32 0.00 0.00 0.00 0.00 96.34 0.00
April 23106.08 13-APR-18:10 146938.85 23790.00 47235.32 0.00 0.00 0.00 0.00 286.76 0.00
May 24066.54 31-MAY-18:10 125947.58 20391.43 40487.42 0.00 0.00 0.00 0.00 357.56 0.00
June 26082.64 28-JUN-18:10 104956.32 16992.86 33739.51 0.00 0.00 0.00 0.00 479.08 0.00
July 25245.97 20-JUL-18:10 125947.58 20391.43 40487.42 0.00 0.00 0.00 0.00 431.17 0.00
August 24547.08 14-AUG-18:10 125947.58 20391.43 40487.42 0.00 0.00 0.00 0.00 412.29 0.00
September 24118.42 07-SEP-18:10 125947.58 20391.43 40487.42 0.00 0.00 0.00 0.00 364.70 0.00
October 23038.01 02-OCT-18:10 125947.58 20391.43 40487.42 0.00 0.00 0.00 0.00 282.60 0.00
November 20798.61 01-NOV-18:10 146938.85 23790.00 47235.32 0.00 0.00 0.00 0.00 56.28 0.00
December 19504.63 26-DEC-23:00 26988.77 2548.93 6747.90 0.00 0.00 0.00 0.00 0.00 241.75
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 19504.63   26988.77 2548.93 6747.90 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 26082.64   146938.85 23790.00 47235.32 0.00 0.00 0.00 0.00 479.08 241.75



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 21071.84 06-JAN-22:20 26988.77 2548.93 6747.90 0.00 0.00 0.00 0.00 0.00 152.55
February 20984.13 15-FEB-23:00 26988.77 2548.93 6747.90 0.00 0.00 0.00 0.00 0.00 215.98
March 22402.87 16-MAR-18:10 146938.85 23790.00 47235.32 0.00 0.00 0.00 0.00 93.70 0.00
April 24433.25 13-APR-18:10 146938.85 23790.00 47235.32 0.00 0.00 0.00 0.00 284.70 0.00
May 25471.15 31-MAY-18:10 125947.58 20391.43 40487.42 0.00 0.00 0.00 0.00 355.23 0.00
June 27441.81 28-JUN-18:10 104956.32 16992.86 33739.51 0.00 0.00 0.00 0.00 478.02 0.00
July 26605.89 20-JUL-18:10 125947.58 20391.43 40487.42 0.00 0.00 0.00 0.00 429.75 0.00
August 25863.03 14-AUG-18:10 125947.58 20391.43 40487.42 0.00 0.00 0.00 0.00 410.97 0.00
September 25431.86 07-SEP-18:10 125947.58 20391.43 40487.42 0.00 0.00 0.00 0.00 363.22 0.00
October 24364.43 02-OCT-18:10 125947.58 20391.43 40487.42 0.00 0.00 0.00 0.00 280.54 0.00
November 22039.13 01-NOV-18:10 146938.85 23790.00 47235.32 0.00 0.00 0.00 0.00 53.97 0.00
December 20690.52 12-DEC-23:00 26988.77 2548.93 6747.90 0.00 0.00 0.00 0.00 0.00 301.07
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 20690.52   26988.77 2548.93 6747.90 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 27441.81   146938.85 23790.00 47235.32 0.00 0.00 0.00 0.00 478.02 301.07



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 27574.62 29-JAN-11:40 1601.14 680.52 30224.21 37488.05 0.00 0.00 0.00 0.00 67.54
February 27406.30 26-FEB-11:50 800.57 340.26 15112.11 18744.03 0.00 0.00 0.00 0.00 209.69
March 28464.92 18-MAR-10:45 1601.14 567.10 30224.21 37488.05 0.00 0.00 0.00 0.66 0.00
April 30126.15 30-APR-10:50 800.57 340.26 15112.11 18744.03 0.00 0.00 0.00 152.60 0.00
May 30388.17 20-MAY-10:50 800.57 283.55 15112.11 18744.03 0.00 0.00 0.00 179.99 0.00
June 32315.38 28-JUN-17:09 10674.24 5444.15 120896.85 179942.65 0.00 0.00 0.00 402.41 0.00
July 31472.96 22-JUL-10:40 1601.14 567.10 30224.21 37488.05 0.00 0.00 0.00 271.46 0.00
August 31492.05 13-AUG-10:40 1601.14 680.52 30224.21 37488.05 0.00 0.00 0.00 226.45 0.00
September 31112.18 09-SEP-10:50 800.57 283.55 15112.11 18744.03 0.00 0.00 0.00 225.55 0.00
October 30157.87 02-OCT-10:40 1067.42 567.10 30224.21 37488.05 0.00 0.00 0.00 195.27 0.00
November 28332.46 01-NOV-10:50 533.71 283.55 15112.11 18744.03 0.00 0.00 0.00 14.15 0.00
December 27385.29 25-DEC-11:40 1601.14 680.52 30224.21 37488.05 0.00 0.00 0.00 0.00 42.05
                       
Annual Sum or Average             0.00 0.00 0.00    
Minimum of Months 27385.29   533.71 283.55 15112.11 18744.03 0.00 0.00 0.00 0.00 0.00
Maximum of Months 32315.38   10674.24 5444.15 120896.85 179942.65 0.00 0.00 0.00 402.41 209.69



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 5841.67 31-JAN-16:50 1330.80 377.07 0.00 0.00 0.00 0.00 0.00 182.35 0.00
February 5144.00 23-FEB-14:20 532.32 377.07 0.00 0.00 0.00 0.00 0.00 0.00 76.51
March 6477.88 18-MAR-17:12 6387.84 3619.83 0.00 0.00 0.00 0.00 0.00 129.43 0.00
April 7538.55 14-APR-17:12 5323.20 3619.83 0.00 0.00 0.00 0.00 0.00 296.15 0.00
May 7590.01 31-MAY-18:10 11178.72 7239.66 0.00 0.00 0.00 0.00 0.00 322.89 0.00
June 9038.95 28-JUN-17:09 10646.40 7239.66 0.00 0.00 0.00 0.00 0.00 433.94 0.00
July 8463.22 23-JUL-10:35 1596.96 904.96 0.00 0.00 0.00 0.00 0.00 269.14 0.00
August 8337.10 13-AUG-10:35 1596.96 904.96 0.00 0.00 0.00 0.00 0.00 273.83 0.00
September 8098.93 09-SEP-10:35 1596.96 754.13 0.00 0.00 0.00 0.00 0.00 270.91 0.00
October 7517.56 02-OCT-10:35 1064.64 754.13 0.00 0.00 0.00 0.00 0.00 252.53 0.00
November 6442.56 01-NOV-16:20 1330.80 377.07 0.00 0.00 0.00 0.00 0.00 138.32 0.00
December 5583.39 22-DEC-16:40 1330.80 377.07 0.00 0.00 0.00 0.00 0.00 74.16 0.00
                       
Annual Sum or Average         0.00 0.00 0.00 0.00 0.00    
Minimum of Months 5144.00   532.32 377.07 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 9038.95   11178.72 7239.66 0.00 0.00 0.00 0.00 0.00 433.94 76.51



Table of Contents

Report: EnergyConsumptionElectricityNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ELECTRICITY:FACILITY [J] ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} NATURALGAS:FACILITY [J] NATURALGAS:FACILITY {Maximum} [W] NATURALGAS:FACILITY {TIMESTAMP}
January 0.702832E+12 442128.39 31-JAN-19:10 0.498627E+12 390479.33 08-JAN-17:00
February 0.570559E+12 384486.26 09-FEB-20:10 0.479185E+12 416869.49 12-FEB-17:00
March 0.697051E+12 461369.39 16-MAR-19:10 0.513533E+12 396045.83 26-MAR-17:00
April 0.839201E+12 520324.33 14-APR-19:10 0.442563E+12 369611.06 02-APR-17:40
May 0.932981E+12 546181.20 31-MAY-18:10 0.442688E+12 351773.56 14-MAY-16:00
June 0.101978E+13 628839.67 28-JUN-18:10 0.406972E+12 345889.22 11-JUN-16:30
July 0.106795E+13 604897.65 21-JUL-19:00 0.403520E+12 342865.53 09-JUL-16:49
August 0.105371E+13 592259.48 27-AUG-19:10 0.401544E+12 339125.26 20-AUG-16:49
September 0.979995E+12 582329.02 08-SEP-19:10 0.390645E+12 337276.84 03-SEP-16:30
October 0.826796E+12 557209.17 01-OCT-18:10 0.437195E+12 355968.75 22-OCT-17:49
November 0.693834E+12 457292.45 01-NOV-18:10 0.459469E+12 383731.70 23-NOV-18:00
December 0.654327E+12 396774.88 02-DEC-19:10 0.515517E+12 392746.56 17-DEC-18:00
             
Annual Sum or Average 0.100390E+14     0.539146E+13    
Minimum of Months 0.570559E+12 384486.26   0.390645E+12 337276.84  
Maximum of Months 0.106795E+13 628839.67   0.515517E+12 416869.49  



Table of Contents

Report: EndUseEnergyConsumptionElectricityMonthly

For: Meter

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY [J] EXTERIORLIGHTS:ELECTRICITY [J] INTERIOREQUIPMENT:ELECTRICITY [J] EXTERIOREQUIPMENT:ELECTRICITY [J] FANS:ELECTRICITY [J] PUMPS:ELECTRICITY [J] HEATING:ELECTRICITY [J] COOLING:ELECTRICITY [J] HEATREJECTION:ELECTRICITY [] HUMIDIFIER:ELECTRICITY [] HEATRECOVERY:ELECTRICITY [J] WATERSYSTEMS:ELECTRICITY [J] COGENERATION:ELECTRICITY []
January 0.997859E+11 0.257065E+11 0.148746E+12 0.577258E+11 0.168597E+12 0.219676E+11 0.00 0.117059E+12 0.00 0.00 0.492860E+11 0.770744E+10 0.00
February 0.901073E+11 0.220513E+11 0.134341E+12 0.521396E+11 0.148550E+12 0.169732E+11 0.00 0.490635E+11 0.00 0.00 0.446725E+11 0.696499E+10 0.00
March 0.995228E+11 0.226722E+11 0.148757E+12 0.577286E+11 0.166036E+12 0.220105E+11 0.00 0.117203E+12 0.00 0.00 0.491382E+11 0.770638E+10 0.00
April 0.965474E+11 0.201587E+11 0.143913E+12 0.558635E+11 0.169634E+12 0.273714E+11 0.00 0.263734E+12 0.00 0.00 0.484617E+11 0.746741E+10 0.00
May 0.996636E+11 0.192974E+11 0.148757E+12 0.577273E+11 0.178239E+12 0.297970E+11 0.00 0.335076E+12 0.00 0.00 0.504563E+11 0.770671E+10 0.00
June 0.963626E+11 0.180356E+11 0.143963E+12 0.558662E+11 0.180531E+12 0.307313E+11 0.00 0.431052E+12 0.00 0.00 0.496672E+11 0.745897E+10 0.00
July 0.998551E+11 0.188768E+11 0.148708E+12 0.577246E+11 0.184299E+12 0.324716E+11 0.00 0.460497E+12 0.00 0.00 0.514307E+11 0.771475E+10 0.00
August 0.995413E+11 0.201386E+11 0.148768E+12 0.577287E+11 0.183098E+12 0.323806E+11 0.00 0.446614E+12 0.00 0.00 0.513230E+11 0.770666E+10 0.00
September 0.965794E+11 0.211501E+11 0.143924E+12 0.558636E+11 0.175567E+12 0.309626E+11 0.00 0.392851E+12 0.00 0.00 0.494299E+11 0.746862E+10 0.00
October 0.997606E+11 0.237137E+11 0.148735E+12 0.577257E+11 0.173816E+12 0.269807E+11 0.00 0.232496E+12 0.00 0.00 0.495666E+11 0.770591E+10 0.00
November 0.965244E+11 0.245048E+11 0.143978E+12 0.558644E+11 0.162619E+12 0.222289E+11 0.00 0.127287E+12 0.00 0.00 0.473082E+11 0.745190E+10 0.00
December 0.998619E+11 0.261972E+11 0.148708E+12 0.577246E+11 0.166854E+12 0.178325E+11 0.00 0.738718E+11 0.00 0.00 0.493563E+11 0.771589E+10 0.00
                           
Annual Sum or Average 0.117411E+13 0.262503E+12 0.175130E+13 0.679683E+12 0.205784E+13 0.311708E+12 0.00 0.304680E+13 0.00 0.00 0.590097E+12 0.907756E+11 0.00
Minimum of Months 0.901073E+11 0.180356E+11 0.134341E+12 0.521396E+11 0.148550E+12 0.169732E+11 0.00 0.490635E+11 0.00 0.00 0.446725E+11 0.696499E+10 0.00
Maximum of Months 0.998619E+11 0.261972E+11 0.148768E+12 0.577287E+11 0.184299E+12 0.324716E+11 0.00 0.460497E+12 0.00 0.00 0.514307E+11 0.771589E+10 0.00



Table of Contents

Report: EndUseEnergyConsumptionNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS [J] EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS [J] COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS [J] COGENERATION:NATURALGAS [] HUMIDIFIER:NATURALGAS []
January 0.151918E+12 0.00 0.878221E+11 0.00 0.258886E+12 0.00 0.00
February 0.137204E+12 0.00 0.109556E+12 0.00 0.232425E+12 0.00 0.00
March 0.152024E+12 0.00 0.111751E+12 0.00 0.249758E+12 0.00 0.00
April 0.146956E+12 0.00 0.654661E+11 0.00 0.230142E+12 0.00 0.00
May 0.151978E+12 0.00 0.658505E+11 0.00 0.224859E+12 0.00 0.00
June 0.147114E+12 0.00 0.523788E+11 0.00 0.207480E+12 0.00 0.00
July 0.151820E+12 0.00 0.425469E+11 0.00 0.209153E+12 0.00 0.00
August 0.152039E+12 0.00 0.387245E+11 0.00 0.210781E+12 0.00 0.00
September 0.146971E+12 0.00 0.321471E+11 0.00 0.211527E+12 0.00 0.00
October 0.151903E+12 0.00 0.547306E+11 0.00 0.230561E+12 0.00 0.00
November 0.147091E+12 0.00 0.767533E+11 0.00 0.235625E+12 0.00 0.00
December 0.151820E+12 0.00 0.109864E+12 0.00 0.253833E+12 0.00 0.00
               
Annual Sum or Average 0.178884E+13 0.00 0.847590E+12 0.00 0.275503E+13 0.00 0.00
Minimum of Months 0.137204E+12 0.00 0.321471E+11 0.00 0.207480E+12 0.00 0.00
Maximum of Months 0.152039E+12 0.00 0.111751E+12 0.00 0.258886E+12 0.00 0.00



Table of Contents

Report: PeakEnergyEndUseElectricityPart1Monthly

For: Meter

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY {Maximum} [W] INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} FANS:ELECTRICITY {Maximum} [W] FANS:ELECTRICITY {TIMESTAMP} PUMPS:ELECTRICITY {Maximum} [W] PUMPS:ELECTRICITY {TIMESTAMP} HEATING:ELECTRICITY {Maximum} [W] HEATING:ELECTRICITY {TIMESTAMP}
January 93091.76 02-JAN-20:10 16690.39 01-JAN-00:10 89674.66 02-JAN-07:10 40537.60 02-JAN-07:19 75766.86 14-JAN-16:10 11928.65 08-JAN-11:50 0.00 01-JAN-00:10
February 93091.76 01-FEB-20:10 16690.39 01-FEB-00:10 89674.66 01-FEB-07:10 40537.60 01-FEB-07:19 73817.81 22-FEB-16:10 11673.64 18-FEB-16:10 0.00 01-FEB-00:10
March 93091.76 01-MAR-20:10 16690.39 01-MAR-00:10 89674.66 01-MAR-07:10 40537.60 01-MAR-07:19 76788.66 17-MAR-15:09 12637.38 14-MAR-16:00 0.00 01-MAR-00:10
April 93091.76 03-APR-19:10 16690.39 01-APR-00:10 89674.66 03-APR-06:10 40537.60 03-APR-06:19 79271.79 14-APR-15:09 12713.90 16-APR-10:50 0.00 01-APR-00:10
May 93091.76 01-MAY-19:10 16690.39 01-MAY-00:10 89674.66 01-MAY-06:10 40537.60 01-MAY-06:19 81066.50 31-MAY-18:19 12511.89 15-MAY-16:00 0.00 01-MAY-00:10
June 93091.76 01-JUN-19:10 16690.39 01-JUN-00:10 89674.66 01-JUN-06:10 40537.60 01-JUN-06:19 91952.36 28-JUN-18:30 14664.31 28-JUN-16:49 0.00 01-JUN-00:10
July 93091.76 03-JUL-19:10 16690.39 01-JUL-00:10 89674.66 03-JUL-06:10 40537.60 03-JUL-06:19 88740.95 22-JUL-18:19 14546.35 11-JUL-16:19 0.00 01-JUL-00:10
August 93091.76 01-AUG-19:10 16690.39 01-AUG-00:10 89674.66 01-AUG-06:10 40537.60 01-AUG-06:19 89613.31 27-AUG-18:19 14250.01 30-AUG-18:19 0.00 01-AUG-00:10
September 93091.76 01-SEP-19:10 16690.39 01-SEP-00:10 89674.66 01-SEP-06:10 40537.60 01-SEP-06:19 86704.25 16-SEP-15:20 13693.89 16-SEP-18:10 0.00 01-SEP-00:10
October 93091.76 02-OCT-19:10 16690.39 01-OCT-00:10 89674.66 02-OCT-06:10 40537.60 02-OCT-06:19 87016.32 05-OCT-15:20 12938.89 03-OCT-10:39 0.00 01-OCT-00:10
November 93091.76 01-NOV-19:10 16690.39 01-NOV-00:10 89674.66 01-NOV-06:10 40537.60 01-NOV-06:19 80995.67 01-NOV-15:09 12656.02 01-NOV-16:00 0.00 01-NOV-00:10
December 93091.76 01-DEC-20:10 16690.39 01-DEC-00:10 89674.66 01-DEC-07:10 40537.60 01-DEC-07:19 76560.07 22-DEC-16:10 11624.18 25-DEC-16:40 0.00 01-DEC-00:10
                             
Annual Sum or Average                            
Minimum of Months 93091.76   16690.39   89674.66   40537.60   73817.81   11624.18   0.00  
Maximum of Months 93091.76   16690.39   89674.66   40537.60   91952.36   14664.31   0.00  



Table of Contents

Report: PeakEnergyEndUseElectricityPart2Monthly

For: Meter

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

COOLING:ELECTRICITY {Maximum} [W] COOLING:ELECTRICITY {TIMESTAMP} HEATREJECTION:ELECTRICITY [] HUMIDIFIER:ELECTRICITY [] HEATRECOVERY:ELECTRICITY {Maximum} [W] HEATRECOVERY:ELECTRICITY {TIMESTAMP} WATERSYSTEMS:ELECTRICITY {Maximum} [W] WATERSYSTEMS:ELECTRICITY {TIMESTAMP} COGENERATION:ELECTRICITY []
January 151331.52 31-JAN-16:10 0.00 0.00 19264.94 01-JAN-00:10 4739.44 02-JAN-07:10 0.00
February 102462.90 22-FEB-16:10 0.00 0.00 19264.94 01-FEB-00:10 4739.37 22-FEB-07:10 0.00
March 152335.27 16-MAR-15:09 0.00 0.00 19264.94 01-MAR-00:10 4739.25 21-MAR-06:10 0.00
April 212856.03 14-APR-15:09 0.00 0.00 19264.94 01-APR-04:19 4738.61 10-APR-06:30 0.00
May 231154.53 31-MAY-18:10 0.00 0.00 19264.94 01-MAY-02:39 4738.76 09-MAY-06:10 0.00
June 324965.30 17-JUN-15:00 0.00 0.00 19264.94 01-JUN-00:10 4738.50 13-JUN-06:10 0.00
July 274671.34 18-JUL-15:30 0.00 0.00 19264.94 01-JUL-00:10 4738.51 25-JUL-06:10 0.00
August 283857.65 26-AUG-15:09 0.00 0.00 19264.94 01-AUG-00:10 4738.88 29-AUG-06:10 0.00
September 262575.96 01-SEP-15:09 0.00 0.00 19264.94 01-SEP-00:10 4739.01 27-SEP-06:10 0.00
October 231176.88 01-OCT-18:10 0.00 0.00 19264.94 01-OCT-00:10 4738.99 31-OCT-06:10 0.00
November 160873.00 01-NOV-15:09 0.00 0.00 19264.94 01-NOV-09:39 4739.19 14-NOV-07:10 0.00
December 132078.98 25-DEC-16:10 0.00 0.00 19264.94 01-DEC-00:10 4738.73 27-DEC-07:10 0.00
                   
Annual Sum or Average     0.00 0.00         0.00
Minimum of Months 102462.90   0.00 0.00 19264.94   4738.50   0.00
Maximum of Months 324965.30   0.00 0.00 19264.94   4739.44   0.00



Table of Contents

Report: ElectricComponentsOfPeakDemandMonthly

For: Meter

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] FANS:ELECTRICITY {AT MAX/MIN} [W] PUMPS:ELECTRICITY {AT MAX/MIN} [W] HEATING:ELECTRICITY {AT MAX/MIN} [W] COOLING:ELECTRICITY {AT MAX/MIN} [W] HEATREJECTION:ELECTRICITY []
January 442128.39 31-JAN-19:10 82800.17 79617.06 16690.39 32686.23 72716.38 11449.51 0.00 120078.19 0.00
February 384486.26 09-FEB-20:10 93091.76 88971.67 16690.39 33012.66 63354.76 9354.72 0.00 55752.32 0.00
March 461369.39 16-MAR-19:10 93091.76 88971.67 16690.39 33012.66 69953.53 11784.26 0.00 121685.70 0.00
April 520324.33 14-APR-19:10 93091.76 88971.67 16690.39 33012.66 75659.70 12025.75 0.00 175381.02 0.00
May 546181.20 31-MAY-18:10 82800.17 79617.06 0.00 32686.23 80729.62 12486.08 0.00 231154.53 0.00
June 628839.67 28-JUN-18:10 82800.17 79617.06 0.00 32686.23 91922.97 12752.43 0.00 302441.11 0.00
July 604897.65 21-JUL-19:00 93091.76 88971.67 16690.39 33025.38 78784.37 12638.41 0.00 256259.52 0.00
August 592259.48 27-AUG-19:10 87949.43 87485.24 16690.39 32961.22 85822.82 13718.11 0.00 242372.44 0.00
September 582329.02 08-SEP-19:10 93091.76 88971.67 16690.39 33012.66 78195.23 12581.48 0.00 234268.82 0.00
October 557209.17 01-OCT-18:10 82807.27 76644.19 16690.39 32602.97 78665.52 12744.74 0.00 231176.88 0.00
November 457292.45 01-NOV-18:10 82800.17 79617.06 16690.39 32686.23 75238.56 12432.93 0.00 131220.15 0.00
December 396774.88 02-DEC-19:10 82807.27 76644.19 16690.39 32608.13 67497.64 10321.58 0.00 85218.01 0.00
                       
Annual Sum or Average                     0.00
Minimum of Months 384486.26   82800.17 76644.19 0.00 32602.97 63354.76 9354.72 0.00 55752.32 0.00
Maximum of Months 628839.67   93091.76 88971.67 16690.39 33025.38 91922.97 13718.11 0.00 302441.11 0.00



Table of Contents

Report: PeakEnergyEndUseNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS {Maximum} [W] INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS {Maximum} [W] HEATING:NATURALGAS {TIMESTAMP} COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS {Maximum} [W] WATERSYSTEMS:NATURALGAS {TIMESTAMP} COGENERATION:NATURALGAS []
January 104248.32 02-JAN-18:10 0.00 100925.27 01-JAN-05:00 0.00 247963.40 23-JAN-21:19 0.00
February 104248.32 01-FEB-18:10 0.00 103606.23 12-FEB-16:10 0.00 247913.24 01-FEB-21:19 0.00
March 104248.32 01-MAR-18:10 0.00 110140.86 27-MAR-10:39 0.00 247093.19 01-MAR-21:00 0.00
April 104248.32 01-APR-17:10 0.00 98502.36 21-APR-10:39 0.00 241084.57 01-APR-17:40 0.00
May 104248.32 01-MAY-17:10 0.00 88470.34 01-MAY-10:39 0.00 216551.55 03-MAY-20:00 0.00
June 104248.32 01-JUN-17:10 0.00 81266.91 13-JUN-10:39 0.00 212785.86 01-JUN-20:00 0.00
July 104248.32 01-JUL-17:10 0.00 88245.66 27-JUL-10:39 0.00 209681.64 06-JUL-20:40 0.00
August 104248.32 01-AUG-17:10 0.00 89832.01 07-AUG-10:39 0.00 210798.66 28-AUG-20:40 0.00
September 104248.32 01-SEP-17:10 0.00 75623.41 05-SEP-10:39 0.00 214380.06 29-SEP-20:00 0.00
October 104248.32 02-OCT-17:10 0.00 82768.37 25-OCT-10:39 0.00 226556.15 31-OCT-20:10 0.00
November 104248.32 01-NOV-17:10 0.00 86392.29 13-NOV-11:39 0.00 246071.74 29-NOV-21:19 0.00
December 104248.32 01-DEC-18:10 0.00 103730.43 07-DEC-09:09 0.00 247486.47 27-DEC-21:30 0.00
                   
Annual Sum or Average     0.00     0.00     0.00
Minimum of Months 104248.32   0.00 75623.41   0.00 209681.64   0.00
Maximum of Months 104248.32   0.00 110140.86   0.00 247963.40   0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 2.67 21.98 2.67 21.98
July 0.00 0.00 0.00 0.00 0.67 21.77 0.67 21.77
August 0.00 0.00 0.00 0.00 0.67 21.88 0.67 21.88
September 0.00 0.00 0.00 0.00 1.00 21.77 1.00 21.77
October 0.00 0.00 0.00 0.00 0.50 21.84 0.50 21.84
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   5.50 21.89 5.50 21.89
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 2.67 21.98 2.67 21.98



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 3.33 22.00 3.33 22.00
July 0.00 0.00 0.00 0.00 0.50 21.79 0.50 21.79
August 0.00 0.00 0.00 0.00 0.33 21.97 0.33 21.97
September 0.00 0.00 0.00 0.00 0.17 21.70 0.17 21.70
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   4.33 21.96 4.33 21.96
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 3.33 22.00 3.33 22.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 2.17 21.88 2.17 21.88
July 0.00 0.00 0.00 0.00 0.50 21.71 0.50 21.71
August 0.00 0.00 0.00 0.00 0.17 21.90 0.17 21.90
September 0.00 0.00 0.00 0.00 0.33 21.69 0.33 21.69
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   3.17 21.84 3.17 21.84
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 2.17 21.90 2.17 21.90



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 2.33 21.82 2.33 21.82
July 0.00 0.00 0.00 0.00 0.17 21.76 0.17 21.76
August 0.00 0.00 0.00 0.00 0.17 21.89 0.17 21.89
September 0.00 0.00 0.00 0.00 0.17 21.69 0.17 21.69
October 0.00 0.00 0.00 0.00 0.17 21.82 0.17 21.82
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   3.00 21.81 3.00 21.81
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 2.33 21.89 2.33 21.89



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 2.83 21.86 2.83 21.86
July 0.00 0.00 0.00 0.00 0.17 21.81 0.17 21.81
August 0.00 0.00 0.00 0.00 0.17 21.81 0.17 21.81
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   3.17 21.86 3.17 21.86
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 2.83 21.86 2.83 21.86



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 7.83 21.96 7.83 21.96
July 0.00 0.00 0.00 0.00 1.50 21.80 1.50 21.80
August 0.00 0.00 0.00 0.00 2.67 21.84 2.67 21.84
September 0.00 0.00 0.00 0.00 1.50 21.91 1.50 21.91
October 0.00 0.00 0.00 0.00 1.50 21.85 1.50 21.85
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   15.00 21.90 15.00 21.90
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 7.83 21.96 7.83 21.96



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 8.67 22.01 8.67 22.01
July 0.00 0.00 0.00 0.00 1.67 21.78 1.67 21.78
August 0.00 0.00 0.00 0.00 1.67 21.83 1.67 21.83
September 0.00 0.00 0.00 0.00 0.67 21.75 0.67 21.75
October 0.00 0.00 0.00 0.00 0.17 21.77 0.17 21.77
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   12.83 21.94 12.83 21.94
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 8.67 22.01 8.67 22.01



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.50 21.87 0.50 21.87
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.33 21.69 0.33 21.69
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 1.67 21.80 1.67 21.80
July 0.00 0.00 0.00 0.00 0.67 21.69 0.67 21.69
August 0.00 0.00 0.00 0.00 3.00 21.85 3.00 21.85
September 0.00 0.00 0.00 0.00 4.17 21.85 4.17 21.85
October 0.00 0.00 0.00 0.00 3.17 21.94 3.17 21.94
November 0.00 0.00 0.00 0.00 0.83 21.85 0.83 21.85
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   14.33 21.86 14.33 21.86
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 4.17 21.94 4.17 21.94



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: BASEMENT

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.10 2.17 21.10 2.17 21.10
February 672.00 21.04 0.00 21.04 0.00 21.04
March 744.00 21.01 53.50 21.01 53.50 21.01
April 720.00 21.01 113.33 21.00 113.33 21.00
May 744.00 20.97 171.67 20.96 171.67 20.95
June 720.00 20.98 9.67 20.98 9.67 20.97
July 744.00 21.10 1.67 21.10 1.67 21.10
August 744.00 21.21 0.00 21.21 0.00 21.21
September 720.00 21.49 0.00 21.49 0.00 21.49
October 744.00 21.56 0.00 21.56 0.00 21.56
November 720.00 21.60 0.00 21.60 0.00 21.60
December 744.00 21.45 0.00 21.45 0.00 21.45
             
Annual Sum or Average 8760.00 21.21 352.00 21.20 352.00 21.19
Minimum of Months 672.00 20.97 0.00 20.96 0.00 20.95
Maximum of Months 744.00 21.60 171.67 21.60 171.67 21.60



Table of Contents

Report: ComfortReportSimple55Monthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 726.17 21.27 24.83 21.26 24.83 21.25
February 672.00 21.06 4.83 21.05 4.83 21.05
March 744.00 21.04 62.50 21.03 62.50 21.03
April 720.00 21.17 14.50 21.16 14.50 21.16
May 744.00 21.09 2.17 21.09 2.17 21.09
June 720.00 21.29 0.00 21.29 0.00 21.29
July 744.00 21.21 0.00 21.21 0.00 21.21
August 724.00 21.28 0.67 21.29 0.00 21.29
September 663.83 21.24 14.17 21.27 0.00 21.27
October 700.33 21.22 33.83 21.24 22.33 21.24
November 693.83 21.19 43.00 21.19 38.50 21.18
December 737.00 21.17 195.17 21.14 195.17 21.11
             
Annual Sum or Average 8589.17 21.18 395.67 21.18 364.83 21.18
Minimum of Months 663.83 21.04 0.00 21.03 0.00 21.03
Maximum of Months 744.00 21.29 195.17 21.29 195.17 21.29



Table of Contents

Report: ComfortReportSimple55Monthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.05 0.00 21.05 0.00 21.05
February 672.00 21.02 0.00 21.02 0.00 21.02
March 744.00 21.04 0.00 21.04 0.00 21.04
April 720.00 21.17 0.00 21.17 0.00 21.17
May 744.00 21.22 0.00 21.22 0.00 21.22
June 720.00 21.39 0.00 21.39 0.00 21.39
July 744.00 21.30 0.00 21.30 0.00 21.30
August 744.00 21.30 0.00 21.30 0.00 21.30
September 720.00 21.24 0.00 21.24 0.00 21.24
October 744.00 21.13 0.00 21.13 0.00 21.13
November 720.00 21.05 0.00 21.05 0.00 21.05
December 744.00 21.02 41.50 21.02 41.50 21.02
             
Annual Sum or Average 8760.00 21.16 41.50 21.16 41.50 21.16
Minimum of Months 672.00 21.02 0.00 21.02 0.00 21.02
Maximum of Months 744.00 21.39 41.50 21.39 41.50 21.39



Table of Contents

Report: ComfortReportSimple55Monthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.00 75.83 21.00 75.83 21.00
February 672.00 21.00 0.33 21.00 0.33 21.00
March 744.00 21.00 74.17 21.00 74.17 21.00
April 720.00 21.03 33.67 21.03 33.67 21.03
May 744.00 21.08 0.00 21.08 0.00 21.08
June 720.00 21.30 0.00 21.30 0.00 21.30
July 744.00 21.24 0.00 21.24 0.00 21.24
August 744.00 21.17 0.00 21.17 0.00 21.17
September 720.00 21.11 0.00 21.11 0.00 21.11
October 744.00 21.03 42.17 21.02 42.17 21.02
November 720.00 21.00 81.17 21.00 81.17 21.00
December 744.00 21.00 273.33 21.00 273.33 21.00
             
Annual Sum or Average 8760.00 21.08 580.67 21.07 580.67 21.07
Minimum of Months 672.00 21.00 0.00 21.00 0.00 21.00
Maximum of Months 744.00 21.30 273.33 21.30 273.33 21.30



Table of Contents

Report: ComfortReportSimple55Monthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.00 144.50 21.00 144.50 21.00
February 672.00 21.00 8.33 21.00 8.33 21.00
March 744.00 21.00 129.50 21.00 129.50 21.00
April 720.00 21.01 67.83 21.01 67.83 21.00
May 744.00 21.03 5.17 21.03 5.17 21.02
June 720.00 21.21 0.00 21.21 0.00 21.21
July 744.00 21.15 0.00 21.15 0.00 21.15
August 744.00 21.10 0.00 21.10 0.00 21.10
September 720.00 21.05 0.00 21.05 0.00 21.05
October 744.00 21.01 73.33 21.01 73.33 21.01
November 720.00 21.00 143.33 21.00 143.33 21.00
December 744.00 21.00 395.83 21.00 395.83 21.00
             
Annual Sum or Average 8760.00 21.05 967.83 21.04 967.83 21.04
Minimum of Months 672.00 21.00 0.00 21.00 0.00 21.00
Maximum of Months 744.00 21.21 395.83 21.21 395.83 21.21



Table of Contents

Report: ComfortReportSimple55Monthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 521.83 21.43 168.17 21.76 88.00 21.97
February 377.83 21.59 217.00 21.84 89.83 22.06
March 472.00 21.52 196.83 21.82 96.33 22.04
April 447.00 21.48 180.83 21.78 87.50 21.99
May 450.17 21.50 188.50 21.80 92.83 22.01
June 234.00 21.93 271.50 21.96 97.33 22.17
July 164.67 22.37 539.17 21.70 106.33 21.88
August 140.83 22.76 572.83 21.75 112.00 21.95
September 140.83 22.69 512.00 21.78 107.50 21.98
October 375.33 21.62 268.17 21.82 94.83 22.03
November 430.50 21.51 212.33 21.80 86.33 22.01
December 571.33 21.33 145.33 21.67 68.00 21.85
             
Annual Sum or Average 4326.33 21.63 3472.67 21.78 1126.83 21.99
Minimum of Months 140.83 21.33 145.33 21.67 68.00 21.85
Maximum of Months 571.33 22.76 572.83 21.96 112.00 22.17



Table of Contents

Report: ComfortReportSimple55Monthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 713.83 21.27 0.00 21.27 0.00 21.27
February 672.00 21.07 0.00 21.07 0.00 21.07
March 744.00 21.07 5.33 21.07 5.33 21.07
April 720.00 21.28 0.00 21.28 0.00 21.28
May 744.00 21.27 0.00 21.27 0.00 21.27
June 717.83 21.46 0.00 21.46 0.00 21.46
July 708.33 21.39 4.00 21.39 0.00 21.39
August 705.33 21.45 2.50 21.45 0.00 21.45
September 645.00 21.45 12.33 21.46 0.00 21.46
October 694.67 21.34 10.00 21.36 0.00 21.36
November 687.33 21.21 5.00 21.22 0.00 21.22
December 729.83 21.16 25.17 21.15 25.17 21.15
             
Annual Sum or Average 8482.17 21.28 64.33 21.29 30.50 21.28
Minimum of Months 645.00 21.07 0.00 21.07 0.00 21.07
Maximum of Months 744.00 21.46 25.17 21.46 25.17 21.46



Table of Contents

Report: ComfortReportSimple55Monthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.13 0.00 21.13 0.00 21.13
February 672.00 21.08 0.00 21.08 0.00 21.08
March 744.00 21.13 0.00 21.13 0.00 21.13
April 720.00 21.29 0.00 21.29 0.00 21.29
May 744.00 21.35 0.00 21.35 0.00 21.35
June 720.00 21.51 0.00 21.51 0.00 21.51
July 744.00 21.48 0.00 21.48 0.00 21.48
August 744.00 21.47 0.00 21.47 0.00 21.47
September 720.00 21.44 0.00 21.44 0.00 21.44
October 744.00 21.27 0.00 21.27 0.00 21.27
November 720.00 21.14 0.00 21.14 0.00 21.14
December 744.00 21.08 0.00 21.08 0.00 21.08
             
Annual Sum or Average 8760.00 21.28 0.00 21.28 0.00 21.28
Minimum of Months 672.00 21.08 0.00 21.08 0.00 21.08
Maximum of Months 744.00 21.51 0.00 21.51 0.00 21.51



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 740.17 21.57 12.83 21.56 12.83 21.55
February 671.00 21.34 7.67 21.33 7.67 21.32
March 741.17 21.46 36.50 21.44 36.50 21.41
April 698.00 21.64 0.00 21.64 0.00 21.64
May 719.67 21.66 0.00 21.66 0.00 21.66
June 634.00 21.54 7.17 21.56 0.00 21.56
July 613.00 21.40 22.50 21.47 0.00 21.47
August 597.83 21.35 31.67 21.45 0.50 21.45
September 591.17 21.38 28.67 21.47 5.33 21.48
October 694.67 21.53 11.50 21.54 7.00 21.53
November 702.83 21.52 59.50 21.50 57.33 21.48
December 743.50 21.46 160.50 21.39 160.50 21.33
             
Annual Sum or Average 8147.00 21.49 378.50 21.50 287.67 21.48
Minimum of Months 591.17 21.34 0.00 21.33 0.00 21.32
Maximum of Months 743.50 21.66 160.50 21.66 160.50 21.66



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.30 70.00 21.26 70.00 21.23
February 672.00 21.11 35.17 21.08 35.17 21.05
March 744.00 21.32 76.83 21.28 76.83 21.24
April 710.17 21.64 0.50 21.64 0.50 21.64
May 723.83 21.67 0.00 21.67 0.00 21.67
June 635.50 21.55 8.50 21.57 0.00 21.57
July 616.33 21.42 18.50 21.47 0.00 21.47
August 615.50 21.40 22.67 21.47 0.83 21.47
September 627.00 21.48 13.17 21.52 5.67 21.53
October 719.00 21.47 33.33 21.44 33.33 21.42
November 717.00 21.34 126.50 21.29 126.50 21.26
December 744.00 21.11 382.17 21.04 382.17 21.00
             
Annual Sum or Average 8268.33 21.40 787.33 21.37 731.00 21.34
Minimum of Months 615.50 21.11 0.00 21.04 0.00 21.00
Maximum of Months 744.00 21.67 382.17 21.67 382.17 21.67



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.24 13.17 21.24 13.17 21.23
February 672.00 21.23 0.00 21.23 0.00 21.23
March 744.00 21.32 2.17 21.32 2.17 21.32
April 720.00 21.57 0.00 21.57 0.00 21.57
May 744.00 21.66 0.00 21.66 0.00 21.66
June 720.00 21.72 0.00 21.72 0.00 21.72
July 744.00 21.71 0.00 21.71 0.00 21.71
August 744.00 21.70 1.00 21.70 1.00 21.70
September 720.00 21.67 0.67 21.67 0.67 21.67
October 744.00 21.46 1.33 21.46 1.33 21.46
November 720.00 21.28 31.67 21.27 31.67 21.27
December 744.00 21.16 146.17 21.14 146.17 21.12
             
Annual Sum or Average 8760.00 21.48 196.17 21.47 196.17 21.46
Minimum of Months 672.00 21.16 0.00 21.14 0.00 21.12
Maximum of Months 744.00 21.72 146.17 21.72 146.17 21.72



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.64 14.17 21.63 14.17 21.62
February 672.00 21.45 9.67 21.44 9.67 21.43
March 743.00 21.58 30.00 21.56 30.00 21.54
April 711.50 21.72 1.00 21.72 1.00 21.72
May 739.83 21.74 0.00 21.74 0.00 21.74
June 594.33 21.43 5.67 21.45 0.00 21.45
July 576.67 21.30 24.50 21.38 0.00 21.38
August 559.83 21.23 31.17 21.34 0.33 21.35
September 562.17 21.30 19.33 21.37 3.67 21.38
October 691.33 21.58 3.33 21.59 0.50 21.59
November 713.00 21.59 65.67 21.55 65.67 21.52
December 744.00 21.52 148.50 21.45 148.50 21.40
             
Annual Sum or Average 8051.67 21.52 353.00 21.53 273.50 21.51
Minimum of Months 559.83 21.23 0.00 21.34 0.00 21.35
Maximum of Months 744.00 21.74 148.50 21.74 148.50 21.74



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.35 69.67 21.32 69.67 21.30
February 672.00 21.21 24.00 21.19 24.00 21.18
March 744.00 21.45 44.33 21.43 44.33 21.41
April 718.33 21.74 4.17 21.73 4.17 21.73
May 741.50 21.74 0.00 21.74 0.00 21.74
June 593.83 21.43 6.17 21.45 0.00 21.45
July 580.83 21.31 17.00 21.37 0.00 21.37
August 572.83 21.28 9.17 21.31 0.50 21.31
September 597.17 21.42 5.67 21.43 4.00 21.44
October 713.83 21.55 21.17 21.54 21.17 21.53
November 720.00 21.36 137.83 21.32 137.83 21.28
December 744.00 21.14 345.17 21.09 345.17 21.07
             
Annual Sum or Average 8142.33 21.42 684.33 21.40 650.83 21.37
Minimum of Months 572.83 21.14 0.00 21.09 0.00 21.07
Maximum of Months 744.00 21.74 345.17 21.74 345.17 21.74



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.04 22.17 21.04 22.17 21.04
February 672.00 21.00 0.00 21.00 0.00 21.00
March 744.00 21.02 79.83 21.02 79.83 21.02
April 720.00 21.34 27.83 21.33 27.83 21.32
May 744.00 21.56 0.00 21.56 0.00 21.56
June 720.00 22.10 0.00 22.10 0.00 22.10
July 744.00 22.04 0.00 22.04 0.00 22.04
August 744.00 21.95 0.00 21.95 0.00 21.95
September 720.00 21.85 0.00 21.85 0.00 21.85
October 744.00 21.38 25.83 21.37 25.83 21.36
November 720.00 21.04 60.83 21.04 60.83 21.04
December 744.00 21.01 245.17 21.01 245.17 21.01
             
Annual Sum or Average 8760.00 21.45 461.67 21.43 461.67 21.41
Minimum of Months 672.00 21.00 0.00 21.00 0.00 21.00
Maximum of Months 744.00 22.10 245.17 22.10 245.17 22.10



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 731.67 21.53 46.33 21.50 46.33 21.47
February 667.67 21.30 38.83 21.27 38.83 21.23
March 732.00 21.43 65.83 21.39 65.83 21.36
April 655.00 21.53 7.67 21.52 7.00 21.52
May 675.83 21.56 0.00 21.56 0.00 21.56
June 568.50 21.37 35.00 21.48 0.00 21.48
July 574.67 21.30 78.67 21.54 0.00 21.54
August 566.33 21.27 96.17 21.57 1.17 21.57
September 559.50 21.29 80.83 21.54 6.00 21.55
October 674.33 21.47 46.83 21.51 25.17 21.49
November 693.17 21.48 114.50 21.44 108.83 21.40
December 740.33 21.42 268.17 21.31 268.17 21.25
             
Annual Sum or Average 7839.00 21.42 878.83 21.46 567.33 21.43
Minimum of Months 559.50 21.27 0.00 21.27 0.00 21.23
Maximum of Months 740.33 21.56 268.17 21.57 268.17 21.57



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.28 158.33 21.21 158.33 21.16
February 672.00 21.08 87.50 21.01 87.50 20.96
March 742.67 21.32 102.17 21.26 102.17 21.22
April 683.00 21.59 9.33 21.58 8.83 21.57
May 686.17 21.59 0.00 21.59 0.00 21.59
June 568.67 21.38 37.00 21.50 0.00 21.50
July 575.33 21.30 72.17 21.52 0.00 21.52
August 576.50 21.29 75.67 21.53 1.33 21.53
September 580.67 21.34 50.67 21.49 6.33 21.50
October 705.50 21.44 63.00 21.41 57.83 21.38
November 715.00 21.32 191.33 21.26 191.33 21.21
December 744.00 21.06 477.00 20.99 477.00 20.95
             
Annual Sum or Average 7993.50 21.33 1324.17 21.33 1090.67 21.28
Minimum of Months 568.67 21.06 0.00 20.99 0.00 20.95
Maximum of Months 744.00 21.59 477.00 21.59 477.00 21.59



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 644.50 21.44 1.33 21.44 1.33 21.44
February 630.67 21.41 0.00 21.41 0.00 21.41
March 724.67 21.54 31.33 21.52 31.33 21.50
April 679.00 21.59 3.33 21.59 3.33 21.59
May 740.50 21.71 0.00 21.71 0.00 21.71
June 651.50 21.57 0.00 21.57 0.00 21.57
July 615.17 21.41 3.67 21.42 0.00 21.42
August 589.67 21.33 44.17 21.46 1.17 21.47
September 569.17 21.32 65.67 21.52 3.50 21.53
October 642.00 21.44 24.83 21.52 0.00 21.52
November 643.67 21.46 43.17 21.49 30.17 21.48
December 694.17 21.52 60.50 21.49 60.50 21.46
             
Annual Sum or Average 7824.67 21.49 278.00 21.51 131.33 21.51
Minimum of Months 569.17 21.32 0.00 21.41 0.00 21.41
Maximum of Months 740.50 21.71 65.67 21.71 60.50 21.71



Table of Contents

Report: ComfortReportSimple55Monthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.36 0.00 21.36 0.00 21.36
February 672.00 21.34 0.00 21.34 0.00 21.34
March 744.00 21.43 0.00 21.43 0.00 21.43
April 715.33 21.66 0.00 21.66 0.00 21.66
May 731.33 21.78 0.00 21.78 0.00 21.78
June 625.67 21.88 7.33 21.90 0.00 21.90
July 514.83 21.67 106.83 21.89 4.33 21.89
August 552.17 21.64 79.67 21.81 3.00 21.82
September 593.00 21.64 45.00 21.73 0.00 21.73
October 720.33 21.52 9.17 21.54 0.17 21.54
November 718.00 21.39 5.50 21.39 5.50 21.40
December 744.00 21.28 0.00 21.28 0.00 21.28
             
Annual Sum or Average 8074.67 21.54 253.50 21.58 13.00 21.58
Minimum of Months 514.83 21.28 0.00 21.28 0.00 21.28
Maximum of Months 744.00 21.88 106.83 21.90 5.50 21.90



Table of Contents

Report: ComfortReportSimple55Monthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.39 0.00 21.39 0.00 21.39
February 671.50 21.38 0.00 21.38 0.00 21.38
March 741.33 21.48 0.00 21.48 0.00 21.48
April 703.83 21.70 0.17 21.70 0.00 21.70
May 704.67 21.81 0.00 21.81 0.00 21.81
June 569.67 21.87 23.00 21.93 0.00 21.93
July 450.00 21.66 162.00 21.97 0.50 21.98
August 470.17 21.59 144.50 21.90 0.00 21.90
September 530.17 21.63 82.83 21.80 0.00 21.80
October 705.33 21.56 14.50 21.58 0.00 21.58
November 712.17 21.42 3.00 21.42 1.17 21.43
December 744.00 21.32 0.00 21.32 0.00 21.32
             
Annual Sum or Average 7746.83 21.56 430.00 21.63 1.67 21.63
Minimum of Months 450.00 21.32 0.00 21.32 0.00 21.32
Maximum of Months 744.00 21.87 162.00 21.97 1.17 21.98



Table of Contents

Report: ComfortReportSimple55Monthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 587.33 22.90 531.50 23.19 403.67 23.34
February 529.50 22.88 496.17 23.11 378.50 23.25
March 595.17 22.94 543.33 23.20 421.50 23.34
April 605.50 23.20 533.50 23.45 456.83 23.57
May 632.17 23.28 562.00 23.50 488.83 23.63
June 570.00 23.60 576.00 23.66 504.67 23.75
July 548.83 23.77 687.33 23.54 523.33 23.65
August 541.17 23.80 686.83 23.54 522.17 23.65
September 522.00 23.75 637.00 23.55 500.50 23.64
October 591.00 23.18 566.00 23.36 453.83 23.50
November 571.17 22.95 528.17 23.20 407.67 23.34
December 549.33 22.74 516.50 23.08 348.33 23.23
             
Annual Sum or Average 6843.17 23.24 6864.33 23.37 5409.83 23.50
Minimum of Months 522.00 22.74 496.17 23.08 348.33 23.23
Maximum of Months 632.17 23.80 687.33 23.66 523.33 23.75



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.01 67.00 21.01 67.00 21.01
February 672.00 21.00 6.17 21.00 6.17 21.00
March 744.00 21.01 72.67 21.01 72.67 21.01
April 720.00 21.13 31.00 21.12 31.00 21.12
May 744.00 21.20 6.50 21.20 6.50 21.20
June 720.00 21.68 0.00 21.68 0.00 21.68
July 744.00 21.60 0.00 21.60 0.00 21.60
August 744.00 21.52 0.00 21.52 0.00 21.52
September 720.00 21.34 0.00 21.34 0.00 21.34
October 744.00 21.11 41.83 21.10 41.83 21.10
November 720.00 21.02 81.17 21.01 81.17 21.01
December 744.00 21.00 329.67 21.00 329.67 21.00
             
Annual Sum or Average 8760.00 21.22 636.00 21.20 636.00 21.19
Minimum of Months 672.00 21.00 0.00 21.00 0.00 21.00
Maximum of Months 744.00 21.68 329.67 21.68 329.67 21.68



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: BASEMENT PEOPLE

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.09603 27.19056 -0.4253 8.89227
February 672.00000 21.03920 42.11853 -0.3704 7.96479
March 744.00000 21.00922 32.70802 -0.4437 9.20200
April 720.00000 21.00667 22.50797 -0.4947 10.22057
May 744.00000 20.97027 21.25586 -1.7182 62.70460
June 720.00000 20.97862 31.07219 -1.6451 58.77930
July 744.00000 21.09837 50.51743 -1.4580 48.66433
August 744.00000 21.21202 53.32091 -1.3910 45.09510
September 720.00000 21.48688 52.30407 -1.2859 39.70205
October 744.00000 21.56326 32.32639 -0.2585 6.58817
November 720.00000 21.60310 31.79600 -0.2542 6.61245
December 744.00000 21.45135 18.81623 -0.3723 7.98433
           
Annual Sum or Average 8760.00000 21.21033 34.60253 -0.8462 26.15206
Minimum of Months 672.00000 20.97027 18.81623 -1.7182 6.58817
Maximum of Months 744.00000 21.60310 53.32091 -0.2542 62.70460



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: RETAIL_1_FLR_1 PEOPLE

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.30691 26.43398 -0.2873 7.75810
February 672.00000 21.05532 41.61218 -0.3300 7.59365
March 744.00000 21.03760 32.12123 -0.3688 8.19504
April 720.00000 21.16591 21.76277 -0.3102 7.50198
May 744.00000 21.09021 20.55318 -1.4509 48.33317
June 720.00000 21.28858 29.92194 -1.2665 38.88511
July 744.00000 21.21141 49.96772 -1.1854 34.89223
August 744.00000 21.31255 52.79662 -1.1323 32.57828
September 720.00000 21.33846 52.56197 -1.1291 32.72982
October 744.00000 21.31776 32.19662 -0.2145 7.10646
November 720.00000 21.24574 32.05381 -0.2754 7.58526
December 744.00000 21.18951 18.47850 -0.4057 9.40729
           
Annual Sum or Average 8760.00000 21.21412 34.14559 -0.6988 20.30158
Minimum of Months 672.00000 21.03760 18.47850 -1.4509 7.10646
Maximum of Months 744.00000 21.33846 52.79662 -0.2145 48.33317



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: RETAIL_2_FLR_1 PEOPLE

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.04613 27.53157 -0.3996 8.42977
February 672.00000 21.02081 42.43792 -0.3378 7.47572
March 744.00000 21.04461 32.91000 -0.3759 8.07328
April 720.00000 21.17068 22.55754 -0.3712 8.08726
May 744.00000 21.21913 21.21200 -1.5012 51.02909
June 720.00000 21.38935 30.59483 -1.3663 43.92566
July 744.00000 21.30494 50.36425 -1.2871 39.84641
August 744.00000 21.30424 53.46692 -1.2698 38.93601
September 720.00000 21.24076 53.47265 -1.2956 40.25010
October 744.00000 21.12637 33.31923 -0.3261 7.52094
November 720.00000 21.05162 33.07137 -0.3633 8.00964
December 744.00000 21.01989 19.47523 -0.4682 9.64231
           
Annual Sum or Average 8760.00000 21.16214 34.97482 -0.7831 22.69949
Minimum of Months 672.00000 21.01989 19.47523 -1.5012 7.47572
Maximum of Months 744.00000 21.38935 53.47265 -0.3261 51.02909



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: LAUNDRY_FLR_1 PEOPLE

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.41430 25.12586 0.26403 9.07594
February 672.00000 21.41686 39.68890 0.34063 10.07034
March 744.00000 21.42006 30.44235 0.30428 9.56178
April 720.00000 21.38994 20.46049 0.29007 9.26822
May 744.00000 21.39108 19.21167 -0.5532 16.33043
June 720.00000 21.37004 28.87849 -0.4594 13.98478
July 744.00000 21.35552 48.31542 -0.3676 12.35118
August 744.00000 21.38230 51.34274 -0.3459 12.18086
September 720.00000 21.37587 51.17933 -0.3706 12.54692
October 744.00000 21.40153 31.04928 0.33498 9.91237
November 720.00000 21.41710 30.55617 0.30203 9.67868
December 744.00000 21.41745 17.25845 0.20037 8.35583
           
Annual Sum or Average 8760.00000 21.39592 32.73601 -0.0073 11.11547
Minimum of Months 672.00000 21.35552 17.25845 -0.5532 8.35583
Maximum of Months 744.00000 21.42006 51.34274 0.34063 16.33043



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CAFE_FLR_1 PEOPLE

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.31219 29.10508 -0.1945 6.55967
February 672.00000 21.06709 44.21713 -0.2322 6.38983
March 744.00000 21.07498 34.72117 -0.2713 6.84756
April 720.00000 21.27769 24.33274 -0.2112 6.31664
May 744.00000 21.26691 23.06069 -1.3041 40.67529
June 720.00000 21.46059 32.39376 -1.1276 32.16034
July 744.00000 21.43672 51.82389 -1.0250 27.70962
August 744.00000 21.49390 54.78980 -0.9829 25.85557
September 720.00000 21.51269 54.56602 -0.9772 25.75159
October 744.00000 21.40313 34.71186 -0.1126 6.13088
November 720.00000 21.26229 34.62824 -0.1827 6.48160
December 744.00000 21.18147 21.17790 -0.3108 7.79710
           
Annual Sum or Average 8760.00000 21.31377 36.56659 -0.5800 16.62758
Minimum of Months 672.00000 21.06709 21.17790 -1.3041 6.13088
Maximum of Months 744.00000 21.51269 54.78980 -0.1126 40.67529



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: LOBBY_FLR_1 PEOPLE

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.12767 28.94773 -0.3348 7.45584
February 672.00000 21.07939 43.80904 -0.2828 6.78597
March 744.00000 21.12567 34.29176 -0.3188 7.28816
April 720.00000 21.29149 23.96791 -0.3070 7.20952
May 744.00000 21.35410 22.61835 -1.4101 46.20588
June 720.00000 21.51118 31.96031 -1.2734 39.24102
July 744.00000 21.47945 51.35784 -1.1730 34.39814
August 744.00000 21.46775 54.47724 -1.1599 33.68442
September 720.00000 21.43559 54.39456 -1.1729 34.28149
October 744.00000 21.27180 34.58287 -0.2485 6.66302
November 720.00000 21.14431 34.40807 -0.2985 7.15242
December 744.00000 21.07630 20.95182 -0.4097 8.59364
           
Annual Sum or Average 8760.00000 21.28133 36.25379 -0.7018 19.99864
Minimum of Months 672.00000 21.07630 20.95182 -1.4101 6.66302
Maximum of Months 744.00000 21.51118 54.47724 -0.2485 46.20588



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_1_FLR_3 PEOPLE

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.57845 31.16123 -0.2815 7.53438
February 672.00000 21.34342 45.88327 -0.3009 7.40785
March 744.00000 21.46931 36.26620 -0.2947 7.54059
April 720.00000 21.68841 26.03297 -0.1949 6.77308
May 744.00000 21.71907 24.57428 -1.2473 38.76329
June 720.00000 21.75009 33.14829 -1.1073 32.32202
July 744.00000 21.74115 45.21466 -1.0723 30.76024
August 744.00000 21.73716 47.59235 -1.0660 30.56549
September 720.00000 21.72991 48.79359 -1.0846 31.37642
October 744.00000 21.64846 34.63535 -0.1852 6.86836
November 720.00000 21.55894 36.21770 -0.2531 7.30121
December 744.00000 21.46418 23.54428 -0.3993 9.23928
           
Annual Sum or Average 8760.00000 21.62062 36.00862 -0.6262 18.10965
Minimum of Months 672.00000 21.34342 23.54428 -1.2473 6.77308
Maximum of Months 744.00000 21.75009 48.79359 -0.1852 38.76329



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_2_FLR_3 PEOPLE

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.29677 31.64680 -0.4034 8.86053
February 672.00000 21.10980 46.47755 -0.3874 8.41359
March 744.00000 21.31810 36.54966 -0.3532 8.16586
April 720.00000 21.66329 26.09124 -0.2205 6.88314
May 744.00000 21.71843 24.61657 -1.2540 39.03373
June 720.00000 21.75386 33.15873 -1.1021 32.07566
July 744.00000 21.74244 45.24815 -1.0727 30.74301
August 744.00000 21.73442 47.79662 -1.0798 31.08020
September 720.00000 21.72027 49.23656 -1.1121 32.44480
October 744.00000 21.52874 35.02906 -0.2493 7.31275
November 720.00000 21.34338 36.84892 -0.3490 8.27583
December 744.00000 21.11060 23.95104 -0.5358 11.48782
           
Annual Sum or Average 8760.00000 21.50530 36.30523 -0.6788 18.80319
Minimum of Months 672.00000 21.10980 23.95104 -1.2540 6.88314
Maximum of Months 744.00000 21.75386 49.23656 -0.2205 39.03373



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_3_MULT19_FLR_3 PEOPLE

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 0.00000 0.00000 0.00000 0.00000 0.00000
February 0.00000 0.00000 0.00000 0.00000 0.00000
March 0.00000 0.00000 0.00000 0.00000 0.00000
April 0.00000 0.00000 0.00000 0.00000 0.00000
May 0.00000 0.00000 0.00000 0.00000 0.00000
June 0.00000 0.00000 0.00000 0.00000 0.00000
July 0.00000 0.00000 0.00000 0.00000 0.00000
August 0.00000 0.00000 0.00000 0.00000 0.00000
September 0.00000 0.00000 0.00000 0.00000 0.00000
October 0.00000 0.00000 0.00000 0.00000 0.00000
November 0.00000 0.00000 0.00000 0.00000 0.00000
December 0.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 0.00000        
Minimum of Months 0.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 0.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_4_MULT19_FLR_3 PEOPLE

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.24293 30.83265 -0.4158 8.71933
February 672.00000 21.22717 44.69098 -0.3419 7.56849
March 744.00000 21.31699 35.65808 -0.3557 7.86471
April 720.00000 21.57151 25.52948 -0.3126 7.48901
May 744.00000 21.66286 24.06155 -1.3909 45.49886
June 720.00000 21.72153 33.00090 -1.2740 39.71800
July 744.00000 21.71223 45.37099 -1.2116 36.74659
August 744.00000 21.69618 47.83874 -1.2172 36.99637
September 720.00000 21.67204 48.94931 -1.2320 37.63735
October 744.00000 21.46171 34.16548 -0.3032 7.46648
November 720.00000 21.27782 35.44353 -0.3725 8.20508
December 744.00000 21.16163 23.10834 -0.4987 10.31323
           
Annual Sum or Average 8760.00000 21.47819 35.64700 -0.7466 21.27445
Minimum of Months 672.00000 21.16163 23.10834 -1.3909 7.46648
Maximum of Months 744.00000 21.72153 48.94931 -0.3032 45.49886



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_5_FLR_3 PEOPLE

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.64011 31.02594 -0.2699 7.42634
February 672.00000 21.44833 45.37075 -0.2702 7.19335
March 744.00000 21.58162 36.04867 -0.2628 7.26436
April 720.00000 21.74244 25.99966 -0.1764 6.71712
May 744.00000 21.74930 24.58547 -1.2245 37.77868
June 720.00000 21.76053 33.21070 -1.0922 31.78446
July 744.00000 21.75579 45.05073 -1.0461 29.77616
August 744.00000 21.75266 47.29846 -1.0433 29.71430
September 720.00000 21.74618 48.56273 -1.0694 30.80054
October 744.00000 21.70586 34.47522 -0.1652 6.78990
November 720.00000 21.60287 36.20308 -0.2476 7.22123
December 744.00000 21.52385 23.47000 -0.3828 8.93434
           
Annual Sum or Average 8760.00000 21.66876 35.86371 -0.6065 17.68581
Minimum of Months 672.00000 21.44833 23.47000 -1.2245 6.71712
Maximum of Months 744.00000 21.76053 48.56273 -0.1652 37.77868



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_6_FLR_3 PEOPLE

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.34585 31.54574 -0.3943 8.57780
February 672.00000 21.21033 46.04525 -0.3556 7.93211
March 744.00000 21.45171 36.28621 -0.3169 7.68395
April 720.00000 21.73891 26.02772 -0.1971 6.78760
May 744.00000 21.74919 24.63042 -1.2312 38.04350
June 720.00000 21.76235 33.23338 -1.0878 31.57419
July 744.00000 21.75614 45.12286 -1.0467 29.76838
August 744.00000 21.75142 47.51545 -1.0564 30.19280
September 720.00000 21.74266 48.85076 -1.0956 31.80227
October 744.00000 21.62678 34.73761 -0.2209 7.06714
November 720.00000 21.36423 36.86143 -0.3484 8.13283
December 744.00000 21.14009 23.88614 -0.5246 11.06551
           
Annual Sum or Average 8760.00000 21.55504 36.14773 -0.6585 18.28870
Minimum of Months 672.00000 21.14009 23.88614 -1.2312 6.78760
Maximum of Months 744.00000 21.76235 48.85076 -0.1971 38.04350



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_1_FLR_6 PEOPLE

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.56168 31.45126 -0.2957 7.95035
February 672.00000 21.31545 46.56270 -0.3226 7.89994
March 744.00000 21.46543 36.58352 -0.3004 7.85044
April 720.00000 21.68958 26.11815 -0.1735 6.87508
May 744.00000 21.72333 24.64411 -1.2070 37.17290
June 720.00000 21.75895 33.28399 -1.0522 30.30434
July 744.00000 21.74681 45.01655 -1.0232 28.96834
August 744.00000 21.74331 47.36429 -1.0192 28.92283
September 720.00000 21.73365 48.75347 -1.0468 30.03380
October 744.00000 21.64319 34.75815 -0.1798 7.10496
November 720.00000 21.54546 36.58054 -0.2627 7.65273
December 744.00000 21.42678 23.75289 -0.4302 10.03774
           
Annual Sum or Average 8760.00000 21.61449 36.15489 -0.6115 17.63126
Minimum of Months 672.00000 21.31545 23.75289 -1.2070 6.87508
Maximum of Months 744.00000 21.75895 48.75347 -0.1735 37.17290



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_2_FLR_6 PEOPLE

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.28368 31.95685 -0.4219 9.35668
February 672.00000 21.07555 47.16351 -0.4139 8.99512
March 744.00000 21.32358 36.85707 -0.3589 8.46356
April 720.00000 21.67498 26.17871 -0.1969 6.93776
May 744.00000 21.72381 24.70222 -1.2131 37.39273
June 720.00000 21.76278 33.32518 -1.0468 30.05374
July 744.00000 21.74803 45.03661 -1.0236 28.94478
August 744.00000 21.74074 47.53774 -1.0331 29.39774
September 720.00000 21.72548 49.17270 -1.0740 31.02649
October 744.00000 21.53495 35.15375 -0.2434 7.52476
November 720.00000 21.33751 37.22313 -0.3611 8.68432
December 744.00000 21.06474 24.17897 -0.5733 12.53419
           
Annual Sum or Average 8760.00000 21.50176 36.45394 -0.6653 18.34241
Minimum of Months 672.00000 21.06474 24.17897 -1.2131 6.93776
Maximum of Months 744.00000 21.76278 49.17270 -0.1969 37.39273



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_3_MULT9_FLR_6 PEOPLE

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.69145 31.84720 -0.1900 7.13312
February 672.00000 21.52561 45.65123 -0.2218 6.98169
March 744.00000 21.58897 36.72111 -0.2485 7.31740
April 720.00000 21.69317 27.23791 -0.1994 6.97988
May 744.00000 21.71549 25.89414 -1.2834 40.60559
June 720.00000 21.74197 34.47167 -1.1611 34.80923
July 744.00000 21.74081 45.50072 -1.1000 32.08005
August 744.00000 21.74149 47.61878 -1.0803 31.36024
September 720.00000 21.74064 48.64645 -1.0745 31.19282
October 744.00000 21.70207 35.07251 -0.1407 6.84663
November 720.00000 21.66005 36.33693 -0.1821 6.97882
December 744.00000 21.64561 24.61674 -0.2831 8.13247
           
Annual Sum or Average 8760.00000 21.68327 36.56008 -0.5995 18.44397
Minimum of Months 672.00000 21.52561 24.61674 -1.2834 6.84663
Maximum of Months 744.00000 21.74197 48.64645 -0.1407 40.60559



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: BANQUET_FLR_6 PEOPLE

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.35578 29.54472 -0.2446 6.52029
February 672.00000 21.34288 44.10433 -0.1677 5.89660
March 744.00000 21.43121 34.70511 -0.1816 6.04586
April 720.00000 21.66620 24.52363 -0.1334 5.77637
May 744.00000 21.80137 23.14154 -1.1207 32.03770
June 720.00000 22.04002 32.12322 -0.9333 24.15878
July 744.00000 21.99008 50.86160 -0.8449 20.92961
August 744.00000 21.92584 54.03570 -0.8607 21.40388
September 720.00000 21.83438 54.10929 -0.9121 23.30915
October 744.00000 21.56044 35.00233 -0.1188 5.92115
November 720.00000 21.38988 34.85699 -0.1972 6.33723
December 744.00000 21.27986 21.69351 -0.3301 7.48700
           
Annual Sum or Average 8760.00000 21.63615 36.49818 -0.5061 13.87195
Minimum of Months 672.00000 21.27986 21.69351 -1.1207 5.77637
Maximum of Months 744.00000 22.04002 54.10929 -0.1188 32.03770



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: DINING_FLR_6 PEOPLE

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.39476 29.29298 -0.2055 6.18372
February 672.00000 21.38496 43.81160 -0.1271 5.67888
March 744.00000 21.48109 34.42429 -0.1392 5.79426
April 720.00000 21.73590 24.24969 -0.0869 5.57781
May 744.00000 21.88508 22.85780 -1.0494 28.87147
June 720.00000 22.10697 31.81885 -0.8698 21.73546
July 744.00000 22.05802 50.47506 -0.7813 18.72802
August 744.00000 21.99151 53.64104 -0.7977 19.18253
September 720.00000 21.90455 53.70612 -0.8469 20.89234
October 744.00000 21.61549 34.70634 -0.0760 5.77261
November 720.00000 21.43254 34.58313 -0.1572 6.07355
December 744.00000 21.31617 21.46476 -0.2913 7.00974
           
Annual Sum or Average 8760.00000 21.69365 36.19230 -0.4546 12.67177
Minimum of Months 672.00000 21.31617 21.46476 -1.0494 5.57781
Maximum of Months 744.00000 22.10697 53.70612 -0.0760 28.87147



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: KITCHEN_FLR_6 PEOPLE

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 22.82258 29.02519 0.75093 22.26603
February 672.00000 22.75140 42.26987 0.80163 23.44409
March 744.00000 22.83208 33.69692 0.79300 23.54849
April 720.00000 23.05560 24.41435 0.87342 26.76309
May 744.00000 23.11825 23.25809 0.29249 18.12275
June 720.00000 23.20592 31.60075 0.44831 20.02670
July 744.00000 23.18077 48.75997 0.53066 21.43902
August 744.00000 23.16735 51.49125 0.53027 21.43333
September 720.00000 23.11746 51.50384 0.47839 20.26043
October 744.00000 22.97058 33.86055 0.87907 26.87887
November 720.00000 22.83357 33.85791 0.78968 23.48275
December 744.00000 22.72894 21.90489 0.65411 19.39547
           
Annual Sum or Average 8760.00000 22.98316 35.41579 0.65065 22.24117
Minimum of Months 672.00000 22.72894 21.90489 0.29249 18.12275
Maximum of Months 744.00000 23.20592 51.50384 0.87907 26.87887



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: STORAGE_FLR_1 PEOPLE

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.00010 26.14734 -0.4971 10.24653
February 672.00000 21.00014 41.04211 -0.4180 8.74080
March 744.00000 21.00013 31.53970 -0.4611 9.54060
April 720.00000 21.00569 21.28026 -0.4859 10.03669
May 744.00000 21.02525 19.92781 -1.6561 59.37639
June 720.00000 21.21025 29.32455 -1.5136 51.67121
July 744.00000 21.15488 49.53084 -1.4183 46.55515
August 744.00000 21.09841 52.79171 -1.4250 46.89068
September 720.00000 21.04501 52.83158 -1.4485 48.16788
October 744.00000 21.00747 32.12566 -0.4305 9.10963
November 720.00000 21.00014 31.77651 -0.4582 9.61949
December 744.00000 20.99903 18.04035 -0.5567 11.53563
           
Annual Sum or Average 8760.00000 21.04570 33.80485 -0.9005 26.90546
Minimum of Months 672.00000 20.99903 18.04035 -1.6561 8.74080
Maximum of Months 744.00000 21.21025 52.83158 -0.4180 59.37639



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORRIDOR_FLR_3 PEOPLE

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.03734 28.19345 -0.4687 9.65409
February 672.00000 21.00136 43.07421 -0.4034 8.47060
March 744.00000 21.02249 33.58033 -0.4463 9.25410
April 720.00000 21.34300 22.96179 -0.4138 8.75368
May 744.00000 21.56076 21.45814 -1.5112 51.52356
June 720.00000 22.09985 30.04970 -1.2705 38.88143
July 744.00000 22.04465 49.01691 -1.1736 34.10245
August 744.00000 21.95320 52.24476 -1.1869 34.72797
September 720.00000 21.84894 52.37660 -1.2222 36.45716
October 744.00000 21.38305 33.37657 -0.3434 7.97250
November 720.00000 21.04498 33.72931 -0.4344 9.15959
December 744.00000 21.00922 20.13069 -0.5319 10.96327
           
Annual Sum or Average 8760.00000 21.44787 34.95240 -0.7864 21.75033
Minimum of Months 672.00000 21.00136 20.13069 -1.5112 7.97250
Maximum of Months 744.00000 22.09985 52.37660 -0.3434 51.52356



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORRIDOR_FLR_6 PEOPLE

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.01263 26.76578 -0.4639 9.58895
February 672.00000 21.00054 41.67137 -0.3993 8.41623
March 744.00000 21.00615 32.15849 -0.4356 9.08225
April 720.00000 21.13006 21.79172 -0.4158 8.81783
May 744.00000 21.19930 20.42817 -1.5435 53.27775
June 720.00000 21.67595 29.26673 -1.2990 40.46089
July 744.00000 21.59562 48.72771 -1.2130 36.14020
August 744.00000 21.52221 52.00051 -1.2239 36.68055
September 720.00000 21.33891 52.39488 -1.2938 40.16305
October 744.00000 21.10984 32.48868 -0.3723 8.31787
November 720.00000 21.01572 32.33869 -0.4278 9.07738
December 744.00000 21.00320 18.67621 -0.5358 11.09920
           
Annual Sum or Average 8760.00000 21.21850 33.99773 -0.8047 22.68772
Minimum of Months 672.00000 21.00054 18.67621 -1.5435 8.31787
Maximum of Months 744.00000 21.67595 52.39488 -0.3723 53.27775



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: MECH_FLR_1 PEOPLE

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.00009 25.96846 -0.4792 9.88376
February 672.00000 21.00009 40.86863 -0.3992 8.42665
March 744.00000 21.00166 31.35772 -0.4419 9.18285
April 720.00000 21.03482 21.06761 -0.4609 9.56084
May 744.00000 21.07900 19.69343 -1.6133 57.06045
June 720.00000 21.29738 29.01150 -1.4606 48.84366
July 744.00000 21.23541 49.08503 -1.3683 43.95308
August 744.00000 21.17003 52.36226 -1.3780 44.42826
September 720.00000 21.10571 52.42752 -1.4050 45.86894
October 744.00000 21.02641 31.89633 -0.4078 8.73586
November 720.00000 21.00107 31.58772 -0.4397 9.27897
December 744.00000 20.99986 17.86202 -0.5383 11.11268
           
Annual Sum or Average 8760.00000 21.07961 33.54010 -0.8690 25.63722
Minimum of Months 672.00000 20.99986 17.86202 -1.6133 8.42665
Maximum of Months 744.00000 21.29738 52.42752 -0.3992 57.06045



Table of Contents

Report: ChillerReportMonthly

For: COOLSYS1 CHILLER1

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

CHILLER ELECTRICITY ENERGY [J] CHILLER ELECTRICITY RATE {Maximum} [W] CHILLER ELECTRICITY RATE {TIMESTAMP} CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] CHILLER EVAPORATOR COOLING ENERGY [J] CHILLER EVAPORATOR COOLING RATE [] CHILLER CONDENSER HEAT TRANSFER ENERGY [J] CHILLER COP [W/W] CHILLER COP {Maximum} [W/W] CHILLER COP {TIMESTAMP} CHILLER PART LOAD RATIO [] CHILLER PART LOAD RATIO []
January 0.117059E+12 173099.42 31-JAN-16:01 694.39 0.343522E+12 0.00 0.460582E+12 2.72 3.88 08-JAN-16:01 0.00 0.00
February 0.490635E+11 119189.69 21-FEB-16:01 598.03 0.138257E+12 0.00 0.187321E+12 2.57 3.55 21-FEB-16:01 0.00 0.00
March 0.117203E+12 172950.19 16-MAR-15:02 694.90 0.337871E+12 0.00 0.455074E+12 2.69 3.65 23-MAR-18:01 0.00 0.00
April 0.263734E+12 234670.88 14-APR-15:03 719.67 0.766687E+12 0.00 0.103042E+13 2.90 3.68 26-APR-18:03 0.00 0.00
May 0.335076E+12 251154.90 31-MAY-18:03 744.00 0.955805E+12 0.00 0.129088E+13 2.86 3.59 13-MAY-08:62 0.00 0.00
June 0.431052E+12 340978.78 28-JUN-15:10 720.00 0.116881E+13 0.00 0.159986E+13 2.77 3.34 13-JUN-08:61 0.00 0.00
July 0.460497E+12 286531.93 18-JUL-15:03 744.00 0.132977E+13 0.00 0.179027E+13 2.92 3.73 27-JUL-01:00 0.00 0.00
August 0.446614E+12 305430.53 26-AUG-15:03 744.00 0.129694E+13 0.00 0.174356E+13 2.95 4.04 28-AUG-17:00 0.00 0.00
September 0.392851E+12 279466.95 01-SEP-15:03 720.00 0.118451E+13 0.00 0.157736E+13 3.04 4.13 03-SEP-08:62 0.00 0.00
October 0.232496E+12 250207.90 01-OCT-18:03 738.17 0.684735E+12 0.00 0.917232E+12 2.90 3.67 30-OCT-18:01 0.00 0.00
November 0.127287E+12 176072.91 01-NOV-15:03 682.47 0.382682E+12 0.00 0.509968E+12 2.80 4.16 11-NOV-19:03 0.00 0.00
December 0.738718E+11 155330.54 25-DEC-16:02 595.36 0.213393E+12 0.00 0.287265E+12 2.32 3.57 03-DEC-16:01 0.00 0.00
                         
Annual Sum or Average 0.304680E+13     8394.99 0.880298E+13 0.00 0.118498E+14 2.79     0.00 0.00
Minimum of Months 0.490635E+11 119189.69   595.36 0.138257E+12 0.00 0.187321E+12 2.32 3.34   0.00 0.00
Maximum of Months 0.460497E+12 340978.78   744.00 0.132977E+13 0.00 0.179027E+13 3.04 4.16   0.00 0.00



Table of Contents

Report: BoilerReportMonthly

For: HEATSYS1 BOILER

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

BOILER HEATING ENERGY [J] BOILER GAS CONSUMPTION [] BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] BOILER HEATING RATE {Maximum} [W] BOILER HEATING RATE {TIMESTAMP} BOILER GAS CONSUMPTION RATE [] BOILER INLET TEMPERATURE [C] BOILER OUTLET TEMPERATURE [C] BOILER MASS FLOW RATE [kg/s] BOILER ANCILLARY ELECTRICITY RATE [W] BOILER PART LOAD RATIO [] BOILER PART LOAD RATIO {Maximum} [] BOILER PART LOAD RATIO {TIMESTAMP}
January 0.566467E+11 0.00 744.00 85196.62 02-JAN-09:02 0.00 31.55 60.00 0.19 0.00 0.05 0.20 02-JAN-09:02
February 0.743826E+11 0.00 672.00 91742.89 12-FEB-16:02 0.00 33.10 60.00 0.29 0.00 0.07 0.22 12-FEB-16:02
March 0.753389E+11 0.00 744.00 112522.94 27-MAR-08:62 0.00 32.63 60.00 0.26 0.00 0.07 0.27 27-MAR-08:62
April 0.410316E+11 0.00 691.94 77057.88 21-APR-10:35 0.00 31.73 58.90 0.14 0.00 0.04 0.18 21-APR-10:35
May 0.412109E+11 0.00 695.19 71829.69 25-MAY-08:04 0.00 32.90 58.18 0.14 0.00 0.04 0.17 25-MAY-08:04
June 0.325434E+11 0.00 653.67 59930.57 13-JUN-10:40 0.00 33.67 57.52 0.12 0.00 0.03 0.14 13-JUN-10:40
July 0.263583E+11 0.00 635.06 69026.67 27-JUL-10:35 0.00 31.22 55.52 0.09 0.00 0.02 0.17 27-JUL-10:35
August 0.237756E+11 0.00 639.96 70349.35 07-AUG-10:35 0.00 30.76 55.72 0.08 0.00 0.02 0.17 07-AUG-10:35
September 0.195749E+11 0.00 636.06 59392.27 11-SEP-08:04 0.00 31.14 56.66 0.06 0.00 0.02 0.14 11-SEP-08:04
October 0.340899E+11 0.00 722.22 80872.20 30-OCT-08:04 0.00 30.34 59.18 0.11 0.00 0.03 0.19 30-OCT-08:04
November 0.489144E+11 0.00 720.00 87116.50 24-NOV-09:02 0.00 30.97 60.00 0.17 0.00 0.05 0.21 24-NOV-09:02
December 0.734489E+11 0.00 744.00 104064.67 07-DEC-09:02 0.00 33.44 60.00 0.27 0.00 0.07 0.25 07-DEC-09:02
                           
Annual Sum or Average 0.547316E+12 0.00 8298.10     0.00 31.94 58.46 0.16 0.00 0.04    
Minimum of Months 0.195749E+11 0.00 635.06 59392.27   0.00 30.34 55.52 0.06 0.00 0.02 0.14  
Maximum of Months 0.753389E+11 0.00 744.00 112522.94   0.00 33.67 60.00 0.29 0.00 0.07 0.27  



Table of Contents

Report: DXReportMonthly

For: VAV WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.214851E+12 0.00 410.08 0.213001E+12 0.00 0.00 0.00 0.00 295052.36 31-JAN-17:00 295052.36 31-JAN-17:00 0.00 0.00 0.00
February 0.746772E+11 0.00 289.21 0.741326E+11 0.00 0.00 0.00 0.00 213860.07 18-FEB-14:00 213860.07 18-FEB-14:00 0.00 0.00 0.00
March 0.234339E+12 0.00 456.31 0.234339E+12 0.00 0.00 0.00 0.00 304911.93 20-MAR-17:12 304911.93 20-MAR-17:12 0.00 0.00 0.00
April 0.542470E+12 0.00 680.83 0.542470E+12 0.00 0.00 0.00 0.00 379153.04 14-APR-17:12 379153.04 14-APR-17:12 0.00 0.00 0.00
May 0.686613E+12 0.00 741.00 0.686613E+12 0.00 0.00 0.00 0.00 399523.97 31-MAY-18:10 399523.97 31-MAY-18:10 0.00 0.00 0.00
June 0.826783E+12 0.00 720.00 0.825029E+12 0.00 0.00 0.00 0.00 546622.60 17-JUN-16:00 469723.88 28-JUN-17:09 0.00 0.00 0.00
July 0.962945E+12 0.00 744.00 0.832588E+12 0.00 0.00 0.00 0.00 621956.02 13-JUL-18:10 436897.88 20-JUL-18:10 0.00 0.00 0.00
August 0.938036E+12 0.00 744.00 0.816408E+12 0.00 0.00 0.00 0.00 590469.37 28-AUG-17:00 438171.79 25-AUG-17:13 0.00 0.00 0.00
September 0.856449E+12 0.00 720.00 0.732932E+12 0.00 0.00 0.00 0.00 573752.44 04-SEP-10:35 407266.24 08-SEP-16:20 0.00 0.00 0.00
October 0.472406E+12 0.00 635.17 0.458139E+12 0.00 0.00 0.00 0.00 496579.68 03-OCT-10:35 374823.08 01-OCT-10:35 0.00 0.00 0.00
November 0.254917E+12 0.00 449.94 0.218064E+12 0.00 0.00 0.00 0.00 420112.47 12-NOV-15:00 299140.47 01-NOV-15:30 0.00 0.00 0.00
December 0.125691E+12 0.00 291.62 0.125691E+12 0.00 0.00 0.00 0.00 261274.58 22-DEC-11:50 261274.58 22-DEC-11:50 0.00 0.00 0.00
                               
Annual Sum or Average 0.619018E+13 0.00 6882.15 0.575941E+13 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.746772E+11 0.00 289.21 0.741326E+11 0.00 0.00 0.00 0.00 213860.07   213860.07   0.00 0.00 0.00
Maximum of Months 0.962945E+12 0.00 744.00 0.832588E+12 0.00 0.00 0.00 0.00 621956.02   469723.88   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: FLR_3_DOAS COOLING COIL

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.199430E+11 0.00 362.33 0.198096E+11 0.00 0.00 0.00 0.00 28446.23 31-JAN-16:01 28446.23 31-JAN-16:01 0.00 0.00 0.00
February 0.520636E+10 0.00 212.00 0.520636E+10 0.00 0.00 0.00 0.00 23246.09 18-FEB-14:00 23246.09 18-FEB-14:00 0.00 0.00 0.00
March 0.213396E+11 0.00 408.00 0.213396E+11 0.00 0.00 0.00 0.00 28923.70 16-MAR-15:02 28923.70 16-MAR-15:02 0.00 0.00 0.00
April 0.507919E+11 0.00 662.50 0.507919E+11 0.00 0.00 0.00 0.00 32711.51 14-APR-15:00 32711.51 14-APR-15:00 0.00 0.00 0.00
May 0.643393E+11 0.00 735.50 0.643393E+11 0.00 0.00 0.00 0.00 33442.98 31-MAY-17:10 33442.98 31-MAY-17:10 0.00 0.00 0.00
June 0.748333E+11 0.00 720.00 0.747447E+11 0.00 0.00 0.00 0.00 40852.50 17-JUN-16:00 36671.73 28-JUN-17:20 0.00 0.00 0.00
July 0.880898E+11 0.00 744.00 0.767142E+11 0.00 0.00 0.00 0.00 50371.12 13-JUL-18:02 36038.90 19-JUL-14:00 0.00 0.00 0.00
August 0.873130E+11 0.00 744.00 0.756907E+11 0.00 0.00 0.00 0.00 55604.06 05-AUG-08:00 36153.56 25-AUG-15:02 0.00 0.00 0.00
September 0.816009E+11 0.00 720.00 0.693110E+11 0.00 0.00 0.00 0.00 59502.56 04-SEP-08:61 34859.33 08-SEP-15:00 0.00 0.00 0.00
October 0.443094E+11 0.00 603.17 0.429107E+11 0.00 0.00 0.00 0.00 45960.15 03-OCT-05:00 34107.67 01-OCT-13:00 0.00 0.00 0.00
November 0.228498E+11 0.00 407.33 0.197102E+11 0.00 0.00 0.00 0.00 44169.39 12-NOV-14:30 29094.35 01-NOV-15:00 0.00 0.00 0.00
December 0.112014E+11 0.00 250.33 0.112014E+11 0.00 0.00 0.00 0.00 26699.29 25-DEC-16:00 26699.29 25-DEC-16:00 0.00 0.00 0.00
                               
Annual Sum or Average 0.571818E+12 0.00 6569.17 0.531770E+12 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.520636E+10 0.00 212.00 0.520636E+10 0.00 0.00 0.00 0.00 23246.09   23246.09   0.00 0.00 0.00
Maximum of Months 0.880898E+11 0.00 744.00 0.767142E+11 0.00 0.00 0.00 0.00 59502.56   36671.73   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_1_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.353540E+10 0.00 431.42 0.325475E+10 0.00 0.00 0.00 0.00 19209.10 08-JAN-16:01 18556.50 07-JAN-16:02 0.00 0.00 0.00
February 0.125846E+10 0.00 227.77 0.906619E+09 0.00 0.00 0.00 0.00 18561.70 24-FEB-16:02 18561.70 24-FEB-16:02 0.00 0.00 0.00
March 0.279561E+10 0.00 389.22 0.222281E+10 0.00 0.00 0.00 0.00 18560.42 02-MAR-16:01 18560.42 02-MAR-16:01 0.00 0.00 0.00
April 0.881471E+10 0.00 659.71 0.859121E+10 0.00 0.00 0.00 0.00 18558.15 25-APR-18:01 18558.15 25-APR-18:01 0.00 0.00 0.00
May 0.106036E+11 0.00 699.60 0.105350E+11 0.00 0.00 0.00 0.00 18562.93 11-MAY-08:61 18562.93 11-MAY-08:61 0.00 0.00 0.00
June 0.143903E+11 0.00 695.78 0.136570E+11 0.00 0.00 0.00 0.00 18563.55 01-JUN-18:02 18563.55 01-JUN-18:02 0.00 0.00 0.00
July 0.140550E+11 0.00 714.85 0.101852E+11 0.00 0.00 0.00 0.00 20229.52 27-JUL-08:61 18551.84 03-JUL-18:02 0.00 0.00 0.00
August 0.137452E+11 0.00 711.53 0.963464E+10 0.00 0.00 0.00 0.00 21212.80 05-AUG-08:61 18563.66 27-AUG-15:02 0.00 0.00 0.00
September 0.118245E+11 0.00 681.57 0.780684E+10 0.00 0.00 0.00 0.00 22066.59 04-SEP-08:61 18563.37 27-SEP-18:01 0.00 0.00 0.00
October 0.719214E+10 0.00 598.07 0.584479E+10 0.00 0.00 0.00 0.00 19421.23 03-OCT-08:61 18564.96 11-OCT-15:01 0.00 0.00 0.00
November 0.356850E+10 0.00 447.91 0.281305E+10 0.00 0.00 0.00 0.00 21235.76 13-NOV-16:01 18554.30 18-NOV-16:01 0.00 0.00 0.00
December 0.177850E+10 0.00 290.94 0.177529E+10 0.00 0.00 0.00 0.00 18552.61 13-DEC-16:01 18552.61 13-DEC-16:01 0.00 0.00 0.00
                               
Annual Sum or Average 0.935619E+11 0.00 6548.37 0.772273E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.125846E+10 0.00 227.77 0.906619E+09 0.00 0.00 0.00 0.00 18552.61   18551.84   0.00 0.00 0.00
Maximum of Months 0.143903E+11 0.00 714.85 0.136570E+11 0.00 0.00 0.00 0.00 22066.59   18564.96   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_2_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.140122E+10 0.00 239.63 0.128591E+10 0.00 0.00 0.00 0.00 19116.05 08-JAN-16:01 18438.09 09-JAN-16:01 0.00 0.00 0.00
February 0.478842E+09 0.00 121.25 0.353537E+09 0.00 0.00 0.00 0.00 18434.74 21-FEB-16:01 18434.74 21-FEB-16:01 0.00 0.00 0.00
March 0.190175E+10 0.00 307.73 0.151383E+10 0.00 0.00 0.00 0.00 18435.63 16-MAR-18:01 18435.63 16-MAR-18:01 0.00 0.00 0.00
April 0.769002E+10 0.00 634.75 0.747311E+10 0.00 0.00 0.00 0.00 18433.30 25-APR-18:01 18433.30 25-APR-18:01 0.00 0.00 0.00
May 0.103068E+11 0.00 697.03 0.102380E+11 0.00 0.00 0.00 0.00 18438.39 11-MAY-08:61 18438.39 11-MAY-08:61 0.00 0.00 0.00
June 0.145692E+11 0.00 697.57 0.138474E+11 0.00 0.00 0.00 0.00 18438.56 01-JUN-18:02 18438.56 01-JUN-18:02 0.00 0.00 0.00
July 0.139999E+11 0.00 715.73 0.101635E+11 0.00 0.00 0.00 0.00 19996.48 27-JUL-08:61 18426.94 03-JUL-18:02 0.00 0.00 0.00
August 0.130381E+11 0.00 708.59 0.900959E+10 0.00 0.00 0.00 0.00 20804.04 05-AUG-08:61 18438.79 27-AUG-15:02 0.00 0.00 0.00
September 0.105770E+11 0.00 674.10 0.672815E+10 0.00 0.00 0.00 0.00 21685.70 04-SEP-08:61 18438.41 27-SEP-18:01 0.00 0.00 0.00
October 0.520812E+10 0.00 514.04 0.403513E+10 0.00 0.00 0.00 0.00 19270.63 03-OCT-08:61 18439.38 05-OCT-18:02 0.00 0.00 0.00
November 0.168740E+10 0.00 300.22 0.120282E+10 0.00 0.00 0.00 0.00 21274.22 13-NOV-16:01 18428.14 18-NOV-16:01 0.00 0.00 0.00
December 0.475854E+09 0.00 110.01 0.475854E+09 0.00 0.00 0.00 0.00 18416.74 27-DEC-16:01 18416.74 27-DEC-16:01 0.00 0.00 0.00
                               
Annual Sum or Average 0.813343E+11 0.00 5720.66 0.663269E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.475854E+09 0.00 110.01 0.353537E+09 0.00 0.00 0.00 0.00 18416.74   18416.74   0.00 0.00 0.00
Maximum of Months 0.145692E+11 0.00 715.73 0.138474E+11 0.00 0.00 0.00 0.00 21685.70   18439.38   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.496434E+11 0.00 572.19 0.482450E+11 0.00 0.00 0.00 0.00 55236.46 14-JAN-13:40 55236.46 14-JAN-13:40 0.00 0.00 0.00
February 0.193957E+11 0.00 356.44 0.158045E+11 0.00 0.00 0.00 0.00 42059.66 01-FEB-15:30 42059.66 01-FEB-15:30 0.00 0.00 0.00
March 0.207904E+11 0.00 460.42 0.186698E+11 0.00 0.00 0.00 0.00 38552.53 18-MAR-13:50 38235.38 18-MAR-14:20 0.00 0.00 0.00
April 0.454817E+11 0.00 650.43 0.452374E+11 0.00 0.00 0.00 0.00 39298.19 14-APR-13:40 39298.19 14-APR-13:40 0.00 0.00 0.00
May 0.459099E+11 0.00 706.13 0.458812E+11 0.00 0.00 0.00 0.00 35475.04 07-MAY-20:03 35475.04 07-MAY-20:03 0.00 0.00 0.00
June 0.610696E+11 0.00 719.33 0.587693E+11 0.00 0.00 0.00 0.00 47183.93 17-JUN-19:10 44581.72 28-JUN-19:10 0.00 0.00 0.00
July 0.652796E+11 0.00 740.67 0.433602E+11 0.00 0.00 0.00 0.00 46001.11 22-JUL-20:10 40899.68 22-JUL-19:10 0.00 0.00 0.00
August 0.685384E+11 0.00 739.33 0.454220E+11 0.00 0.00 0.00 0.00 49225.08 28-AUG-12:30 46071.59 27-AUG-14:00 0.00 0.00 0.00
September 0.681551E+11 0.00 716.25 0.480993E+11 0.00 0.00 0.00 0.00 52992.66 28-SEP-13:40 52992.66 28-SEP-13:40 0.00 0.00 0.00
October 0.563190E+11 0.00 656.89 0.494068E+11 0.00 0.00 0.00 0.00 54466.37 18-OCT-13:40 54466.37 18-OCT-13:40 0.00 0.00 0.00
November 0.415958E+11 0.00 525.71 0.374191E+11 0.00 0.00 0.00 0.00 56920.94 20-NOV-14:30 56920.94 20-NOV-14:30 0.00 0.00 0.00
December 0.375970E+11 0.00 482.48 0.374574E+11 0.00 0.00 0.00 0.00 54781.62 25-DEC-13:30 54781.62 25-DEC-13:30 0.00 0.00 0.00
                               
Annual Sum or Average 0.579775E+12 0.00 7326.29 0.493772E+12 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.193957E+11 0.00 356.44 0.158045E+11 0.00 0.00 0.00 0.00 35475.04   35475.04   0.00 0.00 0.00
Maximum of Months 0.685384E+11 0.00 740.67 0.587693E+11 0.00 0.00 0.00 0.00 56920.94   56920.94   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.179820E+11 0.00 447.49 0.157823E+11 0.00 0.00 0.00 0.00 115630.66 08-JAN-16:01 114791.40 31-JAN-19:01 0.00 0.00 0.00
February 0.152403E+11 0.00 401.90 0.798597E+10 0.00 0.00 0.00 0.00 120973.25 18-FEB-19:02 112150.47 25-FEB-19:02 0.00 0.00 0.00
March 0.254972E+11 0.00 484.96 0.196311E+11 0.00 0.00 0.00 0.00 119001.53 16-MAR-18:01 119001.53 16-MAR-18:01 0.00 0.00 0.00
April 0.536553E+11 0.00 546.46 0.522723E+11 0.00 0.00 0.00 0.00 119838.08 25-APR-18:01 119838.08 25-APR-18:01 0.00 0.00 0.00
May 0.711973E+11 0.00 621.75 0.708064E+11 0.00 0.00 0.00 0.00 119765.64 10-MAY-18:02 119765.64 10-MAY-18:02 0.00 0.00 0.00
June 0.950416E+11 0.00 665.62 0.906667E+11 0.00 0.00 0.00 0.00 119882.53 03-JUN-08:61 119882.53 03-JUN-08:61 0.00 0.00 0.00
July 0.100256E+12 0.00 679.25 0.770601E+11 0.00 0.00 0.00 0.00 121974.70 27-JUL-08:61 119854.32 05-JUL-08:61 0.00 0.00 0.00
August 0.924743E+11 0.00 662.52 0.674896E+11 0.00 0.00 0.00 0.00 140323.99 28-AUG-18:02 119884.01 27-AUG-15:02 0.00 0.00 0.00
September 0.805722E+11 0.00 613.43 0.556422E+11 0.00 0.00 0.00 0.00 138565.94 03-SEP-08:62 119891.74 19-SEP-18:02 0.00 0.00 0.00
October 0.451968E+11 0.00 543.90 0.371465E+11 0.00 0.00 0.00 0.00 119881.66 05-OCT-18:02 119881.66 05-OCT-18:02 0.00 0.00 0.00
November 0.225113E+11 0.00 456.62 0.157214E+11 0.00 0.00 0.00 0.00 136027.30 12-NOV-09:02 114366.67 09-NOV-19:01 0.00 0.00 0.00
December 0.103064E+11 0.00 321.61 0.101309E+11 0.00 0.00 0.00 0.00 113528.31 03-DEC-09:02 113528.31 03-DEC-09:02 0.00 0.00 0.00
                               
Annual Sum or Average 0.629930E+12 0.00 6445.53 0.520335E+12 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.103064E+11 0.00 321.61 0.798597E+10 0.00 0.00 0.00 0.00 113528.31   112150.47   0.00 0.00 0.00
Maximum of Months 0.100256E+12 0.00 679.25 0.906667E+11 0.00 0.00 0.00 0.00 140323.99   119891.74   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_5_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.332458E+10 0.00 447.78 0.304683E+10 0.00 0.00 0.00 0.00 16929.52 08-JAN-16:01 16348.89 09-JAN-16:01 0.00 0.00 0.00
February 0.149847E+10 0.00 262.61 0.100101E+10 0.00 0.00 0.00 0.00 16615.94 18-FEB-09:02 16346.24 21-FEB-16:01 0.00 0.00 0.00
March 0.290814E+10 0.00 428.32 0.228858E+10 0.00 0.00 0.00 0.00 16346.66 16-MAR-18:01 16346.66 16-MAR-18:01 0.00 0.00 0.00
April 0.890446E+10 0.00 689.65 0.868798E+10 0.00 0.00 0.00 0.00 16349.59 18-APR-08:62 16349.59 18-APR-08:62 0.00 0.00 0.00
May 0.109356E+11 0.00 727.58 0.108754E+11 0.00 0.00 0.00 0.00 16349.52 11-MAY-08:61 16349.52 11-MAY-08:61 0.00 0.00 0.00
June 0.147575E+11 0.00 710.74 0.141410E+11 0.00 0.00 0.00 0.00 16350.30 06-JUN-08:61 16350.30 06-JUN-08:61 0.00 0.00 0.00
July 0.150387E+11 0.00 730.91 0.112663E+11 0.00 0.00 0.00 0.00 17054.54 09-JUL-08:61 16339.65 03-JUL-18:02 0.00 0.00 0.00
August 0.145558E+11 0.00 727.63 0.105706E+11 0.00 0.00 0.00 0.00 18586.05 04-AUG-08:62 16349.42 27-AUG-15:02 0.00 0.00 0.00
September 0.122754E+11 0.00 697.80 0.834003E+10 0.00 0.00 0.00 0.00 19097.38 03-SEP-08:62 16348.77 27-SEP-18:01 0.00 0.00 0.00
October 0.747596E+10 0.00 627.95 0.611972E+10 0.00 0.00 0.00 0.00 17075.93 22-OCT-08:62 16350.04 11-OCT-15:01 0.00 0.00 0.00
November 0.325943E+10 0.00 450.32 0.261520E+10 0.00 0.00 0.00 0.00 18182.14 13-NOV-16:01 16347.37 26-NOV-09:01 0.00 0.00 0.00
December 0.180247E+10 0.00 298.84 0.179247E+10 0.00 0.00 0.00 0.00 16335.34 03-DEC-16:01 16335.34 03-DEC-16:01 0.00 0.00 0.00
                               
Annual Sum or Average 0.967365E+11 0.00 6800.13 0.807452E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.149847E+10 0.00 262.61 0.100101E+10 0.00 0.00 0.00 0.00 16335.34   16335.34   0.00 0.00 0.00
Maximum of Months 0.150387E+11 0.00 730.91 0.141410E+11 0.00 0.00 0.00 0.00 19097.38   16350.30   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_6_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.116202E+10 0.00 240.72 0.103144E+10 0.00 0.00 0.00 0.00 16205.01 31-JAN-16:01 16205.01 31-JAN-16:01 0.00 0.00 0.00
February 0.591004E+09 0.00 159.21 0.311154E+09 0.00 0.00 0.00 0.00 16433.58 20-FEB-09:02 15326.30 21-FEB-16:01 0.00 0.00 0.00
March 0.194748E+10 0.00 341.71 0.148593E+10 0.00 0.00 0.00 0.00 16240.93 16-MAR-18:01 16240.93 16-MAR-18:01 0.00 0.00 0.00
April 0.772212E+10 0.00 680.00 0.750895E+10 0.00 0.00 0.00 0.00 16239.33 25-APR-18:01 16239.33 25-APR-18:01 0.00 0.00 0.00
May 0.106310E+11 0.00 727.46 0.105702E+11 0.00 0.00 0.00 0.00 16243.96 11-MAY-08:61 16243.96 11-MAY-08:61 0.00 0.00 0.00
June 0.149366E+11 0.00 711.16 0.143364E+11 0.00 0.00 0.00 0.00 16243.62 01-JUN-18:02 16243.62 01-JUN-18:02 0.00 0.00 0.00
July 0.149795E+11 0.00 731.07 0.112159E+11 0.00 0.00 0.00 0.00 16885.53 09-JUL-08:61 16233.79 03-JUL-18:02 0.00 0.00 0.00
August 0.138551E+11 0.00 726.59 0.983497E+10 0.00 0.00 0.00 0.00 18130.77 04-AUG-08:62 16244.00 27-AUG-15:02 0.00 0.00 0.00
September 0.110314E+11 0.00 694.46 0.721108E+10 0.00 0.00 0.00 0.00 18971.21 03-SEP-08:62 16243.19 27-SEP-18:01 0.00 0.00 0.00
October 0.536881E+10 0.00 547.09 0.418064E+10 0.00 0.00 0.00 0.00 16883.64 22-OCT-08:62 16244.52 06-OCT-08:61 0.00 0.00 0.00
November 0.140069E+10 0.00 286.60 0.996452E+09 0.00 0.00 0.00 0.00 16220.46 20-NOV-16:01 16220.46 20-NOV-16:01 0.00 0.00 0.00
December 0.427013E+09 0.00 122.02 0.423256E+09 0.00 0.00 0.00 0.00 15618.59 25-DEC-16:02 15618.59 25-DEC-16:02 0.00 0.00 0.00
                               
Annual Sum or Average 0.840528E+11 0.00 5968.10 0.691065E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.427013E+09 0.00 122.02 0.311154E+09 0.00 0.00 0.00 0.00 15618.59   15326.30   0.00 0.00 0.00
Maximum of Months 0.149795E+11 0.00 731.07 0.143364E+11 0.00 0.00 0.00 0.00 18971.21   16244.52   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_1_FLR_6 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.916616E+09 0.00 386.87 0.852375E+09 0.00 0.00 0.00 0.00 5173.37 08-JAN-16:01 5021.36 07-JAN-16:02 0.00 0.00 0.00
February 0.311384E+09 0.00 195.18 0.235682E+09 0.00 0.00 0.00 0.00 5022.90 24-FEB-16:02 5022.90 24-FEB-16:02 0.00 0.00 0.00
March 0.764838E+09 0.00 364.13 0.623263E+09 0.00 0.00 0.00 0.00 5022.45 02-MAR-16:01 5022.45 02-MAR-16:01 0.00 0.00 0.00
April 0.252217E+10 0.00 656.75 0.246242E+10 0.00 0.00 0.00 0.00 5021.74 25-APR-18:01 5021.74 25-APR-18:01 0.00 0.00 0.00
May 0.306320E+10 0.00 703.80 0.304457E+10 0.00 0.00 0.00 0.00 5023.28 11-MAY-08:61 5023.28 11-MAY-08:61 0.00 0.00 0.00
June 0.415876E+10 0.00 701.03 0.395462E+10 0.00 0.00 0.00 0.00 5023.25 01-JUN-18:02 5023.25 01-JUN-18:02 0.00 0.00 0.00
July 0.406328E+10 0.00 720.98 0.300720E+10 0.00 0.00 0.00 0.00 5604.54 27-JUL-08:61 5019.95 03-JUL-18:02 0.00 0.00 0.00
August 0.396830E+10 0.00 715.66 0.285803E+10 0.00 0.00 0.00 0.00 5877.99 05-AUG-08:61 5023.41 27-AUG-15:02 0.00 0.00 0.00
September 0.336249E+10 0.00 684.80 0.227770E+10 0.00 0.00 0.00 0.00 6156.86 04-SEP-08:61 5023.24 27-SEP-18:01 0.00 0.00 0.00
October 0.196820E+10 0.00 581.07 0.160791E+10 0.00 0.00 0.00 0.00 5399.98 03-OCT-08:61 5023.60 11-OCT-15:01 0.00 0.00 0.00
November 0.931320E+09 0.00 410.96 0.744035E+09 0.00 0.00 0.00 0.00 5707.54 13-NOV-16:01 5020.81 18-NOV-16:01 0.00 0.00 0.00
December 0.441887E+09 0.00 254.56 0.441506E+09 0.00 0.00 0.00 0.00 5020.35 13-DEC-16:01 5020.35 13-DEC-16:01 0.00 0.00 0.00
                               
Annual Sum or Average 0.264724E+11 0.00 6375.79 0.221093E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.311384E+09 0.00 195.18 0.235682E+09 0.00 0.00 0.00 0.00 5020.35   5019.95   0.00 0.00 0.00
Maximum of Months 0.415876E+10 0.00 720.98 0.395462E+10 0.00 0.00 0.00 0.00 6156.86   5023.60   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_2_FLR_6 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.360341E+09 0.00 214.53 0.338172E+09 0.00 0.00 0.00 0.00 5188.09 08-JAN-16:01 4986.00 09-JAN-16:01 0.00 0.00 0.00
February 0.113794E+09 0.00 97.12 89896803.75 0.00 0.00 0.00 0.00 4985.05 21-FEB-16:01 4985.05 21-FEB-16:01 0.00 0.00 0.00
March 0.524790E+09 0.00 287.30 0.428053E+09 0.00 0.00 0.00 0.00 4985.09 02-MAR-16:01 4985.09 02-MAR-16:01 0.00 0.00 0.00
April 0.222529E+10 0.00 639.80 0.216830E+10 0.00 0.00 0.00 0.00 4984.52 25-APR-18:01 4984.52 25-APR-18:01 0.00 0.00 0.00
May 0.298581E+10 0.00 703.55 0.296558E+10 0.00 0.00 0.00 0.00 4985.40 10-MAY-08:61 4985.40 10-MAY-08:61 0.00 0.00 0.00
June 0.420591E+10 0.00 702.32 0.399943E+10 0.00 0.00 0.00 0.00 4986.08 01-JUN-18:02 4986.08 01-JUN-18:02 0.00 0.00 0.00
July 0.404961E+10 0.00 721.78 0.299960E+10 0.00 0.00 0.00 0.00 5521.65 27-JUL-08:61 4982.74 03-JUL-18:02 0.00 0.00 0.00
August 0.378505E+10 0.00 714.23 0.268115E+10 0.00 0.00 0.00 0.00 5753.49 05-AUG-08:61 4986.08 27-AUG-15:02 0.00 0.00 0.00
September 0.303635E+10 0.00 679.77 0.197376E+10 0.00 0.00 0.00 0.00 6044.49 04-SEP-08:61 4986.00 27-SEP-18:01 0.00 0.00 0.00
October 0.144165E+10 0.00 500.78 0.112056E+10 0.00 0.00 0.00 0.00 5357.32 03-OCT-08:61 4986.28 11-OCT-15:01 0.00 0.00 0.00
November 0.438709E+09 0.00 269.42 0.320017E+09 0.00 0.00 0.00 0.00 5757.16 13-NOV-16:01 4983.23 18-NOV-16:01 0.00 0.00 0.00
December 0.115820E+09 0.00 87.04 0.115808E+09 0.00 0.00 0.00 0.00 4981.77 03-DEC-16:01 4981.77 03-DEC-16:01 0.00 0.00 0.00
                               
Annual Sum or Average 0.232831E+11 0.00 5617.64 0.192003E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.113794E+09 0.00 87.04 89896803.75 0.00 0.00 0.00 0.00 4981.77   4981.77   0.00 0.00 0.00
Maximum of Months 0.420591E+10 0.00 721.78 0.399943E+10 0.00 0.00 0.00 0.00 6044.49   4986.28   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.113094E+11 0.00 615.67 0.106696E+11 0.00 0.00 0.00 0.00 22666.51 08-JAN-16:01 22594.93 11-JAN-19:02 0.00 0.00 0.00
February 0.486778E+10 0.00 409.00 0.354267E+10 0.00 0.00 0.00 0.00 23442.85 18-FEB-19:02 22597.02 05-FEB-16:01 0.00 0.00 0.00
March 0.606501E+10 0.00 503.41 0.491625E+10 0.00 0.00 0.00 0.00 22595.67 16-MAR-18:01 22595.67 16-MAR-18:01 0.00 0.00 0.00
April 0.127032E+11 0.00 666.77 0.123695E+11 0.00 0.00 0.00 0.00 22592.63 25-APR-18:01 22592.63 25-APR-18:01 0.00 0.00 0.00
May 0.135290E+11 0.00 696.12 0.134370E+11 0.00 0.00 0.00 0.00 22587.50 10-MAY-08:61 22587.50 10-MAY-08:61 0.00 0.00 0.00
June 0.177926E+11 0.00 691.12 0.166704E+11 0.00 0.00 0.00 0.00 22596.94 19-JUN-15:02 22596.94 19-JUN-15:02 0.00 0.00 0.00
July 0.193924E+11 0.00 713.22 0.144222E+11 0.00 0.00 0.00 0.00 24599.35 27-JUL-08:61 22585.28 03-JUL-18:02 0.00 0.00 0.00
August 0.199915E+11 0.00 712.45 0.146981E+11 0.00 0.00 0.00 0.00 26192.89 05-AUG-08:61 22594.37 23-AUG-18:02 0.00 0.00 0.00
September 0.190725E+11 0.00 686.40 0.137426E+11 0.00 0.00 0.00 0.00 27081.14 04-SEP-08:61 22592.72 18-SEP-18:02 0.00 0.00 0.00
October 0.143759E+11 0.00 666.67 0.123958E+11 0.00 0.00 0.00 0.00 23476.98 03-OCT-08:61 22595.47 20-OCT-18:01 0.00 0.00 0.00
November 0.101402E+11 0.00 580.51 0.873900E+10 0.00 0.00 0.00 0.00 25696.11 13-NOV-16:01 22590.56 26-NOV-09:01 0.00 0.00 0.00
December 0.825955E+10 0.00 500.53 0.822091E+10 0.00 0.00 0.00 0.00 22586.37 13-DEC-16:01 22586.37 13-DEC-16:01 0.00 0.00 0.00
                               
Annual Sum or Average 0.157499E+12 0.00 7441.86 0.133824E+12 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.486778E+10 0.00 409.00 0.354267E+10 0.00 0.00 0.00 0.00 22586.37   22585.28   0.00 0.00 0.00
Maximum of Months 0.199915E+11 0.00 713.22 0.166704E+11 0.00 0.00 0.00 0.00 27081.14   22597.02   0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 835.71 667.64 168.07 1315.12 366.53 0.00 0.00 0.00
February 521.47 349.59 171.87 748.03 354.74 0.00 0.00 0.00
March 431.69 218.75 212.94 682.31 315.72 0.00 0.00 0.00
April 378.88 156.07 222.81 784.31 149.22 0.00 0.00 0.00
May 253.16 44.04 209.12 614.93 89.55 0.00 0.00 0.00
June 214.28 16.35 197.94 712.74 23.74 0.00 0.00 0.00
July 217.14 20.65 196.50 715.51 14.60 0.00 0.00 0.00
August 268.51 75.62 192.88 788.45 16.67 0.00 0.00 0.00
September 381.40 161.20 220.20 907.03 30.46 0.00 0.00 0.00
October 612.22 423.82 188.40 1089.12 198.27 0.00 0.00 0.00
November 719.63 552.71 166.92 1126.57 322.78 0.00 0.00 0.00
December 778.28 616.61 161.67 1171.52 453.41 0.00 0.00 0.00
                 
Annual Sum or Average 467.74 275.23 192.51 889.18 194.02 0.00 0.00 0.00
Minimum of Months 214.28 16.35 161.67 614.93 14.60 0.00 0.00 0.00
Maximum of Months 835.71 667.64 222.81 1315.12 453.41 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CAFE_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 2353.32 1880.03 473.29 3690.04 1044.43 0.00 0.00 0.00
February 1468.41 984.43 483.99 2088.88 1015.58 0.00 0.00 0.00
March 1215.60 615.98 599.62 1903.18 901.93 0.00 0.00 0.00
April 1066.89 439.48 627.41 2199.91 432.87 0.00 0.00 0.00
May 712.87 124.01 588.87 1719.02 266.16 0.00 0.00 0.00
June 603.41 46.04 557.38 1997.43 76.66 0.00 0.00 0.00
July 611.46 58.14 553.32 1987.90 47.04 0.00 0.00 0.00
August 756.09 212.94 543.15 2203.02 57.62 0.00 0.00 0.00
September 1074.00 453.93 620.07 2540.10 102.53 0.00 0.00 0.00
October 1723.96 1193.45 530.51 3056.59 575.62 0.00 0.00 0.00
November 2026.44 1556.40 470.05 3159.26 921.79 0.00 0.00 0.00
December 2191.58 1736.32 455.26 3281.71 1288.27 0.00 0.00 0.00
                 
Annual Sum or Average 1317.12 775.03 542.09 2488.97 559.08 0.00 0.00 0.00
Minimum of Months 603.41 46.04 455.26 1719.02 47.04 0.00 0.00 0.00
Maximum of Months 2353.32 1880.03 627.41 3690.04 1288.27 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: LOBBY_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 3057.09 2442.27 614.83 4922.79 1355.51 0.00 0.00 0.00
February 1907.55 1278.83 628.73 2777.68 1344.22 0.00 0.00 0.00
March 1579.13 800.19 778.94 2536.32 1196.79 0.00 0.00 0.00
April 1385.95 570.91 815.04 2954.28 568.48 0.00 0.00 0.00
May 926.06 161.09 764.97 2312.07 353.30 0.00 0.00 0.00
June 783.87 59.80 724.06 2694.69 100.22 0.00 0.00 0.00
July 794.32 75.52 718.79 2682.01 61.27 0.00 0.00 0.00
August 982.21 276.63 705.58 2975.42 71.63 0.00 0.00 0.00
September 1395.19 589.68 805.51 3423.39 126.09 0.00 0.00 0.00
October 2239.52 1550.35 689.17 4094.30 743.68 0.00 0.00 0.00
November 2632.46 2021.85 610.62 4213.92 1200.59 0.00 0.00 0.00
December 2846.99 2255.58 591.41 4365.03 1689.62 0.00 0.00 0.00
                 
Annual Sum or Average 1711.02 1006.81 704.21 3333.94 731.85 0.00 0.00 0.00
Minimum of Months 783.87 59.80 591.41 2312.07 61.27 0.00 0.00 0.00
Maximum of Months 3057.09 2442.27 815.04 4922.79 1689.62 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 165.24 132.00 33.23 259.71 74.52 0.00 0.00 0.00
February 103.10 69.12 33.98 146.36 72.64 0.00 0.00 0.00
March 85.35 43.25 42.10 132.10 65.57 0.00 0.00 0.00
April 74.91 30.86 44.05 152.40 30.29 0.00 0.00 0.00
May 50.05 8.71 41.35 119.38 18.03 0.00 0.00 0.00
June 42.37 3.23 39.14 141.90 4.63 0.00 0.00 0.00
July 42.93 4.08 38.85 141.69 2.91 0.00 0.00 0.00
August 53.09 14.95 38.14 156.62 3.23 0.00 0.00 0.00
September 75.41 31.87 43.54 179.59 5.63 0.00 0.00 0.00
October 121.05 83.80 37.25 214.38 39.76 0.00 0.00 0.00
November 142.28 109.28 33.00 221.57 65.78 0.00 0.00 0.00
December 153.88 121.91 31.97 232.00 92.23 0.00 0.00 0.00
                 
Annual Sum or Average 92.48 54.42 38.06 175.05 39.47 0.00 0.00 0.00
Minimum of Months 42.37 3.23 31.97 119.38 2.91 0.00 0.00 0.00
Maximum of Months 165.24 132.00 44.05 259.71 92.23 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_1_FLR_3_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 127.00 79.12 47.88 186.98 153.53 0.00 0.00 0.00
February 102.87 49.92 52.94 122.82 146.85 0.00 0.00 0.00
March 136.12 65.10 71.02 193.47 125.08 0.00 0.00 0.00
April 208.46 118.98 89.48 376.19 56.25 0.00 0.00 0.00
May 209.22 117.24 91.97 410.21 33.35 0.00 0.00 0.00
June 221.79 130.41 91.37 506.11 8.36 0.00 0.00 0.00
July 161.33 75.18 86.15 398.78 5.33 0.00 0.00 0.00
August 154.44 77.66 76.78 372.77 5.91 0.00 0.00 0.00
September 134.39 56.51 77.89 308.08 10.61 0.00 0.00 0.00
October 138.07 79.18 58.89 240.58 79.44 0.00 0.00 0.00
November 126.39 76.26 50.13 184.00 134.71 0.00 0.00 0.00
December 101.41 57.49 43.91 132.88 191.41 0.00 0.00 0.00
                 
Annual Sum or Average 151.96 82.04 69.93 286.78 78.97 0.00 0.00 0.00
Minimum of Months 101.41 49.92 43.91 122.82 5.33 0.00 0.00 0.00
Maximum of Months 221.79 130.41 91.97 506.11 191.41 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_2_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 20.04 0.00 20.04 19.66 79.83 0.00 0.00 0.00
February 22.83 0.00 22.83 13.65 77.86 0.00 0.00 0.00
March 30.35 0.00 30.35 33.83 67.47 0.00 0.00 0.00
April 37.17 0.55 36.63 72.60 28.74 0.00 0.00 0.00
May 43.60 3.70 39.90 100.88 16.03 0.00 0.00 0.00
June 50.36 9.20 41.15 156.02 4.07 0.00 0.00 0.00
July 43.08 4.63 38.45 140.02 2.61 0.00 0.00 0.00
August 34.66 0.85 33.81 115.43 3.01 0.00 0.00 0.00
September 32.69 0.02 32.67 96.37 5.52 0.00 0.00 0.00
October 25.27 0.00 25.27 46.57 41.79 0.00 0.00 0.00
November 21.06 0.00 21.06 20.26 70.61 0.00 0.00 0.00
December 18.72 0.00 18.72 12.29 100.07 0.00 0.00 0.00
                 
Annual Sum or Average 31.68 1.58 30.10 69.23 41.32 0.00 0.00 0.00
Minimum of Months 18.72 0.00 18.72 12.29 2.61 0.00 0.00 0.00
Maximum of Months 50.36 9.20 41.15 156.02 100.07 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_2_FLR_3_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 127.00 79.12 47.88 194.98 148.04 0.00 0.00 0.00
February 102.87 49.92 52.94 128.18 142.69 0.00 0.00 0.00
March 136.12 65.10 71.02 198.02 122.93 0.00 0.00 0.00
April 208.46 118.98 89.48 378.77 55.41 0.00 0.00 0.00
May 209.22 117.24 91.97 410.81 33.19 0.00 0.00 0.00
June 221.79 130.41 91.37 505.76 8.37 0.00 0.00 0.00
July 161.33 75.18 86.15 398.91 5.33 0.00 0.00 0.00
August 154.44 77.66 76.78 374.13 5.80 0.00 0.00 0.00
September 134.39 56.51 77.89 310.65 10.25 0.00 0.00 0.00
October 138.07 79.18 58.89 246.02 76.98 0.00 0.00 0.00
November 126.39 76.26 50.13 190.51 130.20 0.00 0.00 0.00
December 101.41 57.49 43.91 140.79 184.92 0.00 0.00 0.00
                 
Annual Sum or Average 151.96 82.04 69.93 290.50 76.75 0.00 0.00 0.00
Minimum of Months 101.41 49.92 43.91 128.18 5.33 0.00 0.00 0.00
Maximum of Months 221.79 130.41 91.97 505.76 184.92 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 132.16 105.58 26.58 202.35 71.02 0.00 0.00 0.00
February 82.47 55.29 27.18 111.92 70.66 0.00 0.00 0.00
March 68.27 34.59 33.67 100.55 62.66 0.00 0.00 0.00
April 59.92 24.68 35.24 118.80 31.08 0.00 0.00 0.00
May 40.04 6.96 33.07 92.31 19.60 0.00 0.00 0.00
June 33.89 2.59 31.30 109.56 6.00 0.00 0.00 0.00
July 34.34 3.26 31.07 107.02 3.90 0.00 0.00 0.00
August 42.46 11.96 30.50 119.54 5.20 0.00 0.00 0.00
September 60.32 25.49 34.82 138.02 8.54 0.00 0.00 0.00
October 96.82 67.02 29.79 166.61 40.15 0.00 0.00 0.00
November 113.80 87.41 26.40 172.17 63.64 0.00 0.00 0.00
December 123.08 97.51 25.57 179.71 86.06 0.00 0.00 0.00
                 
Annual Sum or Average 73.97 43.53 30.44 135.07 38.91 0.00 0.00 0.00
Minimum of Months 33.89 2.59 25.57 92.31 3.90 0.00 0.00 0.00
Maximum of Months 132.16 105.58 35.24 202.35 86.06 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 16.03 0.00 16.03 16.36 64.81 0.00 0.00 0.00
February 18.27 0.00 18.27 10.77 64.90 0.00 0.00 0.00
March 24.29 0.00 24.28 27.79 54.73 0.00 0.00 0.00
April 29.74 0.44 29.30 62.27 21.87 0.00 0.00 0.00
May 34.89 2.96 31.92 85.52 11.76 0.00 0.00 0.00
June 40.29 7.36 32.93 131.70 2.56 0.00 0.00 0.00
July 34.47 3.70 30.76 117.90 1.76 0.00 0.00 0.00
August 27.73 0.68 27.05 97.99 2.00 0.00 0.00 0.00
September 26.15 0.02 26.14 81.67 3.79 0.00 0.00 0.00
October 20.22 0.00 20.22 39.67 33.07 0.00 0.00 0.00
November 16.85 0.00 16.85 17.03 57.08 0.00 0.00 0.00
December 14.98 0.00 14.98 9.63 82.54 0.00 0.00 0.00
                 
Annual Sum or Average 25.35 1.27 24.08 58.42 33.28 0.00 0.00 0.00
Minimum of Months 14.98 0.00 14.98 9.63 1.76 0.00 0.00 0.00
Maximum of Months 40.29 7.36 32.93 131.70 82.54 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_5_FLR_3_WALL_EAST_WINDOW

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 120.94 75.91 45.03 160.74 138.98 0.00 0.00 0.00
February 120.23 69.17 51.05 141.29 137.27 0.00 0.00 0.00
March 149.29 76.81 72.48 204.50 115.85 0.00 0.00 0.00
April 212.74 126.76 85.99 379.14 50.30 0.00 0.00 0.00
May 220.85 131.04 89.80 428.02 29.17 0.00 0.00 0.00
June 229.78 142.76 87.03 523.71 7.30 0.00 0.00 0.00
July 194.36 109.67 84.69 457.81 4.76 0.00 0.00 0.00
August 184.63 105.48 79.14 424.59 5.67 0.00 0.00 0.00
September 151.29 72.97 78.32 336.04 9.91 0.00 0.00 0.00
October 151.83 92.35 59.47 257.20 73.12 0.00 0.00 0.00
November 116.83 70.11 46.72 154.97 123.54 0.00 0.00 0.00
December 106.72 64.54 42.18 124.20 174.99 0.00 0.00 0.00
                 
Annual Sum or Average 163.49 94.92 68.57 300.11 72.31 0.00 0.00 0.00
Minimum of Months 106.72 64.54 42.18 124.20 4.76 0.00 0.00 0.00
Maximum of Months 229.78 142.76 89.80 523.71 174.99 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 165.24 132.00 33.23 258.63 73.92 0.00 0.00 0.00
February 103.10 69.12 33.98 144.62 72.66 0.00 0.00 0.00
March 85.35 43.25 42.10 130.19 65.39 0.00 0.00 0.00
April 74.91 30.86 44.05 151.33 30.15 0.00 0.00 0.00
May 50.05 8.71 41.35 118.31 17.83 0.00 0.00 0.00
June 42.37 3.23 39.14 141.11 4.41 0.00 0.00 0.00
July 42.93 4.08 38.85 140.37 2.85 0.00 0.00 0.00
August 53.09 14.95 38.14 155.50 3.22 0.00 0.00 0.00
September 75.41 31.87 43.54 178.82 5.59 0.00 0.00 0.00
October 121.05 83.80 37.25 212.97 39.49 0.00 0.00 0.00
November 142.28 109.28 33.00 220.77 65.07 0.00 0.00 0.00
December 153.88 121.91 31.97 230.85 91.93 0.00 0.00 0.00
                 
Annual Sum or Average 92.48 54.42 38.06 173.87 39.25 0.00 0.00 0.00
Minimum of Months 42.37 3.23 31.97 118.31 2.85 0.00 0.00 0.00
Maximum of Months 165.24 132.00 44.05 258.63 91.93 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_6_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 20.04 0.00 20.04 18.75 79.31 0.00 0.00 0.00
February 22.83 0.00 22.83 12.59 78.54 0.00 0.00 0.00
March 30.35 0.00 30.35 32.09 67.64 0.00 0.00 0.00
April 37.17 0.55 36.63 71.31 28.69 0.00 0.00 0.00
May 43.60 3.70 39.90 99.62 15.72 0.00 0.00 0.00
June 50.36 9.20 41.15 155.30 3.90 0.00 0.00 0.00
July 43.08 4.63 38.45 138.70 2.56 0.00 0.00 0.00
August 34.66 0.85 33.81 114.21 2.99 0.00 0.00 0.00
September 32.69 0.02 32.67 95.49 5.48 0.00 0.00 0.00
October 25.27 0.00 25.27 45.14 41.91 0.00 0.00 0.00
November 21.06 0.00 21.06 19.67 69.94 0.00 0.00 0.00
December 18.72 0.00 18.72 11.57 99.91 0.00 0.00 0.00
                 
Annual Sum or Average 31.68 1.58 30.10 68.13 41.23 0.00 0.00 0.00
Minimum of Months 18.72 0.00 18.72 11.57 2.56 0.00 0.00 0.00
Maximum of Months 50.36 9.20 41.15 155.30 99.91 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_6_FLR_3_WALL_EAST_WINDOW

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 120.94 75.91 45.03 169.03 133.46 0.00 0.00 0.00
February 120.23 69.17 51.05 146.60 133.14 0.00 0.00 0.00
March 149.29 76.81 72.48 208.68 113.70 0.00 0.00 0.00
April 212.74 126.76 85.99 381.41 49.56 0.00 0.00 0.00
May 220.85 131.04 89.80 428.62 29.03 0.00 0.00 0.00
June 229.78 142.76 87.03 523.47 7.34 0.00 0.00 0.00
July 194.36 109.67 84.69 457.98 4.76 0.00 0.00 0.00
August 184.63 105.48 79.14 425.91 5.56 0.00 0.00 0.00
September 151.29 72.97 78.32 338.49 9.58 0.00 0.00 0.00
October 151.83 92.35 59.47 262.15 70.83 0.00 0.00 0.00
November 116.83 70.11 46.72 161.58 118.72 0.00 0.00 0.00
December 106.72 64.54 42.18 131.88 167.86 0.00 0.00 0.00
                 
Annual Sum or Average 163.49 94.92 68.57 303.74 70.04 0.00 0.00 0.00
Minimum of Months 106.72 64.54 42.18 131.88 4.76 0.00 0.00 0.00
Maximum of Months 229.78 142.76 89.80 523.47 167.86 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 25.38 0.00 25.38 26.28 102.55 0.00 0.00 0.00
February 28.92 0.00 28.92 17.65 101.70 0.00 0.00 0.00
March 38.44 0.00 38.44 46.23 85.28 0.00 0.00 0.00
April 47.08 0.69 46.38 103.20 34.65 0.00 0.00 0.00
May 55.22 4.69 50.53 140.40 19.13 0.00 0.00 0.00
June 63.77 11.65 52.12 208.91 4.97 0.00 0.00 0.00
July 54.55 5.86 48.69 186.80 3.34 0.00 0.00 0.00
August 43.90 1.08 42.82 155.61 3.73 0.00 0.00 0.00
September 41.39 0.03 41.37 130.73 7.05 0.00 0.00 0.00
October 32.01 0.00 32.01 64.35 52.70 0.00 0.00 0.00
November 26.67 0.00 26.67 27.94 89.85 0.00 0.00 0.00
December 23.71 0.00 23.71 15.11 131.52 0.00 0.00 0.00
                 
Annual Sum or Average 40.13 2.00 38.12 93.96 52.85 0.00 0.00 0.00
Minimum of Months 23.71 0.00 23.71 15.11 3.34 0.00 0.00 0.00
Maximum of Months 63.77 11.65 52.12 208.91 131.52 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 9.36 0.00 9.36 9.69 37.81 0.00 0.00 0.00
February 10.66 0.00 10.66 6.51 37.49 0.00 0.00 0.00
March 14.17 0.00 14.17 17.04 31.44 0.00 0.00 0.00
April 17.35 0.26 17.10 38.04 12.77 0.00 0.00 0.00
May 20.36 1.73 18.63 51.76 7.05 0.00 0.00 0.00
June 23.51 4.30 19.21 77.01 1.83 0.00 0.00 0.00
July 20.11 2.16 17.95 68.86 1.23 0.00 0.00 0.00
August 16.18 0.40 15.78 57.36 1.38 0.00 0.00 0.00
September 15.26 0.01 15.25 48.19 2.60 0.00 0.00 0.00
October 11.80 0.00 11.80 23.72 19.43 0.00 0.00 0.00
November 9.83 0.00 9.83 10.30 33.12 0.00 0.00 0.00
December 8.74 0.00 8.74 5.57 48.48 0.00 0.00 0.00
                 
Annual Sum or Average 14.79 0.74 14.05 34.64 19.48 0.00 0.00 0.00
Minimum of Months 8.74 0.00 8.74 5.57 1.23 0.00 0.00 0.00
Maximum of Months 23.51 4.30 19.21 77.01 48.48 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 77.10 61.59 15.51 124.05 33.98 0.00 0.00 0.00
February 48.11 32.25 15.86 69.80 34.02 0.00 0.00 0.00
March 39.82 20.18 19.64 63.98 30.04 0.00 0.00 0.00
April 34.95 14.40 20.56 75.80 13.28 0.00 0.00 0.00
May 23.36 4.06 19.29 60.47 7.94 0.00 0.00 0.00
June 19.77 1.51 18.26 70.27 2.10 0.00 0.00 0.00
July 20.03 1.90 18.13 69.59 1.38 0.00 0.00 0.00
August 24.77 6.98 17.79 76.80 1.45 0.00 0.00 0.00
September 35.19 14.87 20.31 87.51 2.57 0.00 0.00 0.00
October 56.48 39.10 17.38 103.39 17.96 0.00 0.00 0.00
November 66.39 50.99 15.40 106.18 29.84 0.00 0.00 0.00
December 71.80 56.88 14.92 110.20 43.02 0.00 0.00 0.00
                 
Annual Sum or Average 43.15 25.39 17.76 84.96 18.07 0.00 0.00 0.00
Minimum of Months 19.77 1.51 14.92 60.47 1.38 0.00 0.00 0.00
Maximum of Months 77.10 61.59 20.56 124.05 43.02 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 209.26 167.17 42.09 336.69 92.23 0.00 0.00 0.00
February 130.57 87.54 43.04 189.46 92.33 0.00 0.00 0.00
March 108.09 54.77 53.32 173.64 81.52 0.00 0.00 0.00
April 94.87 39.08 55.79 205.73 36.05 0.00 0.00 0.00
May 63.39 11.03 52.36 164.13 21.56 0.00 0.00 0.00
June 53.66 4.09 49.56 190.73 5.71 0.00 0.00 0.00
July 54.37 5.17 49.20 188.87 3.75 0.00 0.00 0.00
August 67.23 18.94 48.30 208.44 3.95 0.00 0.00 0.00
September 95.50 40.36 55.14 237.53 6.98 0.00 0.00 0.00
October 153.30 106.12 47.17 280.63 48.76 0.00 0.00 0.00
November 180.19 138.40 41.80 288.19 80.99 0.00 0.00 0.00
December 194.88 154.40 40.48 299.10 116.77 0.00 0.00 0.00
                 
Annual Sum or Average 117.12 68.92 48.20 230.59 49.05 0.00 0.00 0.00
Minimum of Months 53.66 4.09 40.48 164.13 3.75 0.00 0.00 0.00
Maximum of Months 209.26 167.17 55.79 336.69 116.77 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 165.24 132.00 33.23 257.68 74.28 0.00 0.00 0.00
February 103.10 69.12 33.98 144.96 72.12 0.00 0.00 0.00
March 85.35 43.25 42.10 130.30 65.57 0.00 0.00 0.00
April 74.91 30.86 44.05 150.18 30.06 0.00 0.00 0.00
May 50.05 8.71 41.35 117.89 17.73 0.00 0.00 0.00
June 42.37 3.23 39.14 140.76 4.44 0.00 0.00 0.00
July 42.93 4.08 38.85 140.23 2.86 0.00 0.00 0.00
August 53.09 14.95 38.14 154.98 3.20 0.00 0.00 0.00
September 75.41 31.87 43.54 177.59 5.51 0.00 0.00 0.00
October 121.05 83.80 37.25 212.15 39.44 0.00 0.00 0.00
November 142.28 109.28 33.00 219.55 65.63 0.00 0.00 0.00
December 153.88 121.91 31.97 230.84 91.64 0.00 0.00 0.00
                 
Annual Sum or Average 92.48 54.42 38.06 173.34 39.25 0.00 0.00 0.00
Minimum of Months 42.37 3.23 31.97 117.89 2.86 0.00 0.00 0.00
Maximum of Months 165.24 132.00 44.05 257.68 91.64 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_1_FLR_6_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 127.00 79.12 47.88 184.66 152.25 0.00 0.00 0.00
February 102.87 49.92 52.94 120.72 145.27 0.00 0.00 0.00
March 136.12 65.10 71.02 190.32 124.57 0.00 0.00 0.00
April 208.46 118.98 89.48 371.05 55.80 0.00 0.00 0.00
May 209.22 117.24 91.97 405.53 32.89 0.00 0.00 0.00
June 221.79 130.41 91.37 501.47 8.15 0.00 0.00 0.00
July 161.33 75.18 86.15 394.60 5.29 0.00 0.00 0.00
August 154.44 77.66 76.78 368.80 5.93 0.00 0.00 0.00
September 134.39 56.51 77.89 304.41 10.50 0.00 0.00 0.00
October 138.07 79.18 58.89 237.47 78.63 0.00 0.00 0.00
November 126.39 76.26 50.13 181.38 133.87 0.00 0.00 0.00
December 101.41 57.49 43.91 131.44 189.19 0.00 0.00 0.00
                 
Annual Sum or Average 151.96 82.04 69.93 283.36 78.27 0.00 0.00 0.00
Minimum of Months 101.41 49.92 43.91 120.72 5.29 0.00 0.00 0.00
Maximum of Months 221.79 130.41 91.97 501.47 189.19 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_2_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 20.04 0.00 20.04 19.53 78.93 0.00 0.00 0.00
February 22.83 0.00 22.83 13.37 76.91 0.00 0.00 0.00
March 30.35 0.00 30.35 33.05 67.18 0.00 0.00 0.00
April 37.17 0.55 36.63 71.19 28.56 0.00 0.00 0.00
May 43.60 3.70 39.90 99.51 15.85 0.00 0.00 0.00
June 50.36 9.20 41.15 154.61 3.99 0.00 0.00 0.00
July 43.08 4.63 38.45 138.48 2.60 0.00 0.00 0.00
August 34.66 0.85 33.81 114.01 3.03 0.00 0.00 0.00
September 32.69 0.02 32.67 95.11 5.46 0.00 0.00 0.00
October 25.27 0.00 25.27 45.85 41.30 0.00 0.00 0.00
November 21.06 0.00 21.06 19.89 70.01 0.00 0.00 0.00
December 18.72 0.00 18.72 12.42 98.64 0.00 0.00 0.00
                 
Annual Sum or Average 31.68 1.58 30.10 68.35 40.90 0.00 0.00 0.00
Minimum of Months 18.72 0.00 18.72 12.42 2.60 0.00 0.00 0.00
Maximum of Months 50.36 9.20 41.15 154.61 98.64 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_2_FLR_6_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 127.00 79.12 47.88 193.18 146.32 0.00 0.00 0.00
February 102.87 49.92 52.94 126.52 140.78 0.00 0.00 0.00
March 136.12 65.10 71.02 195.01 122.31 0.00 0.00 0.00
April 208.46 118.98 89.48 373.52 54.97 0.00 0.00 0.00
May 209.22 117.24 91.97 406.10 32.73 0.00 0.00 0.00
June 221.79 130.41 91.37 501.10 8.16 0.00 0.00 0.00
July 161.33 75.18 86.15 394.73 5.29 0.00 0.00 0.00
August 154.44 77.66 76.78 370.17 5.81 0.00 0.00 0.00
September 134.39 56.51 77.89 306.98 10.14 0.00 0.00 0.00
October 138.07 79.18 58.89 243.03 76.04 0.00 0.00 0.00
November 126.39 76.26 50.13 188.24 129.01 0.00 0.00 0.00
December 101.41 57.49 43.91 140.02 182.29 0.00 0.00 0.00
                 
Annual Sum or Average 151.96 82.04 69.93 287.25 75.90 0.00 0.00 0.00
Minimum of Months 101.41 49.92 43.91 126.52 5.29 0.00 0.00 0.00
Maximum of Months 221.79 130.41 91.97 501.10 182.29 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 242.33 193.60 48.74 372.23 113.18 0.00 0.00 0.00
February 151.21 101.37 49.84 207.65 110.69 0.00 0.00 0.00
March 125.18 63.43 61.75 188.25 97.90 0.00 0.00 0.00
April 109.86 45.26 64.61 223.49 42.73 0.00 0.00 0.00
May 73.41 12.77 60.64 178.84 24.37 0.00 0.00 0.00
June 62.14 4.74 57.40 215.53 5.44 0.00 0.00 0.00
July 62.97 5.99 56.98 212.56 3.72 0.00 0.00 0.00
August 77.86 21.93 55.93 232.91 4.23 0.00 0.00 0.00
September 110.60 46.74 63.85 263.34 7.62 0.00 0.00 0.00
October 177.53 122.90 54.63 309.26 58.88 0.00 0.00 0.00
November 208.67 160.27 48.40 317.52 99.57 0.00 0.00 0.00
December 225.68 178.80 46.88 331.34 140.70 0.00 0.00 0.00
                 
Annual Sum or Average 135.63 79.81 55.82 254.79 58.88 0.00 0.00 0.00
Minimum of Months 62.14 4.74 46.88 178.84 3.72 0.00 0.00 0.00
Maximum of Months 242.33 193.60 64.61 372.23 140.70 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: BANQUET_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 140.27 0.00 140.27 137.76 590.32 0.00 0.00 0.00
February 159.84 0.00 159.84 86.49 593.78 0.00 0.00 0.00
March 212.46 0.01 212.45 237.02 507.21 0.00 0.00 0.00
April 260.20 3.83 256.37 549.26 218.21 0.00 0.00 0.00
May 305.21 25.92 279.29 750.89 126.84 0.00 0.00 0.00
June 352.47 64.40 288.07 1133.19 36.63 0.00 0.00 0.00
July 301.52 32.40 269.12 1006.14 24.41 0.00 0.00 0.00
August 242.62 5.96 236.66 838.51 30.52 0.00 0.00 0.00
September 228.79 0.14 228.65 707.27 53.29 0.00 0.00 0.00
October 176.90 0.00 176.90 347.73 313.97 0.00 0.00 0.00
November 147.39 0.00 147.39 143.99 524.94 0.00 0.00 0.00
December 131.03 0.00 131.03 77.83 743.13 0.00 0.00 0.00
                 
Annual Sum or Average 221.78 11.08 210.70 503.30 312.46 0.00 0.00 0.00
Minimum of Months 131.03 0.00 131.03 77.83 24.41 0.00 0.00 0.00
Maximum of Months 352.47 64.40 288.07 1133.19 743.13 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: DINING_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 140.27 0.00 140.27 132.71 604.85 0.00 0.00 0.00
February 159.84 0.00 159.84 82.47 610.23 0.00 0.00 0.00
March 212.46 0.01 212.45 229.82 521.30 0.00 0.00 0.00
April 260.20 3.83 256.37 537.15 228.23 0.00 0.00 0.00
May 305.21 25.92 279.29 735.06 134.37 0.00 0.00 0.00
June 352.47 64.40 288.07 1115.58 39.77 0.00 0.00 0.00
July 301.52 32.40 269.12 987.41 26.59 0.00 0.00 0.00
August 242.62 5.96 236.66 821.40 34.18 0.00 0.00 0.00
September 228.79 0.14 228.65 691.44 59.07 0.00 0.00 0.00
October 176.90 0.00 176.90 338.51 325.73 0.00 0.00 0.00
November 147.39 0.00 147.39 138.66 539.75 0.00 0.00 0.00
December 131.03 0.00 131.03 74.03 758.51 0.00 0.00 0.00
                 
Annual Sum or Average 221.78 11.08 210.70 492.28 322.36 0.00 0.00 0.00
Minimum of Months 131.03 0.00 131.03 74.03 26.59 0.00 0.00 0.00
Maximum of Months 352.47 64.40 288.07 1115.58 758.51 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: KITCHEN_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 20.04 0.00 20.04 19.60 90.20 0.00 0.00 0.00
February 22.83 0.00 22.83 12.37 91.37 0.00 0.00 0.00
March 30.35 0.00 30.35 33.41 78.69 0.00 0.00 0.00
April 37.17 0.55 36.63 76.89 35.33 0.00 0.00 0.00
May 43.60 3.70 39.90 106.11 21.62 0.00 0.00 0.00
June 50.36 9.20 41.15 160.49 6.29 0.00 0.00 0.00
July 43.08 4.63 38.45 142.30 4.67 0.00 0.00 0.00
August 34.66 0.85 33.81 119.08 6.34 0.00 0.00 0.00
September 32.69 0.02 32.67 99.81 9.85 0.00 0.00 0.00
October 25.27 0.00 25.27 48.35 50.06 0.00 0.00 0.00
November 21.06 0.00 21.06 20.41 81.06 0.00 0.00 0.00
December 18.72 0.00 18.72 11.74 110.48 0.00 0.00 0.00
                 
Annual Sum or Average 31.68 1.58 30.10 71.16 48.65 0.00 0.00 0.00
Minimum of Months 18.72 0.00 18.72 11.74 4.67 0.00 0.00 0.00
Maximum of Months 50.36 9.20 41.15 160.49 110.48 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: KITCHEN_FLR_6_WALL_EAST_WINDOW

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 241.87 151.81 90.06 341.66 307.87 0.00 0.00 0.00
February 240.43 138.34 102.10 293.98 315.29 0.00 0.00 0.00
March 298.56 153.60 144.96 422.75 270.03 0.00 0.00 0.00
April 425.45 253.49 171.96 784.68 126.14 0.00 0.00 0.00
May 441.66 262.07 179.60 879.75 80.49 0.00 0.00 0.00
June 459.53 285.49 174.04 1063.70 23.63 0.00 0.00 0.00
July 388.70 219.32 169.38 927.52 17.47 0.00 0.00 0.00
August 369.23 210.95 158.27 867.43 23.75 0.00 0.00 0.00
September 302.56 145.93 156.63 690.99 36.07 0.00 0.00 0.00
October 303.63 184.69 118.94 537.14 173.05 0.00 0.00 0.00
November 233.65 140.21 93.44 327.10 279.67 0.00 0.00 0.00
December 213.43 129.08 84.35 265.90 376.12 0.00 0.00 0.00
                 
Annual Sum or Average 326.95 189.82 137.13 618.44 168.51 0.00 0.00 0.00
Minimum of Months 213.43 129.08 84.35 265.90 17.47 0.00 0.00 0.00
Maximum of Months 459.53 285.49 179.60 1063.70 376.12 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 165.24 132.00 33.23 265.29 81.84 0.00 0.00 0.00
February 103.10 69.12 33.98 148.39 83.02 0.00 0.00 0.00
March 85.35 43.25 42.10 134.18 75.36 0.00 0.00 0.00
April 74.91 30.86 44.05 157.72 36.44 0.00 0.00 0.00
May 50.05 8.71 41.35 124.43 23.36 0.00 0.00 0.00
June 42.37 3.23 39.14 145.84 6.72 0.00 0.00 0.00
July 42.93 4.08 38.85 144.15 4.93 0.00 0.00 0.00
August 53.09 14.95 38.14 161.04 6.42 0.00 0.00 0.00
September 75.41 31.87 43.54 184.19 9.78 0.00 0.00 0.00
October 121.05 83.80 37.25 219.39 46.45 0.00 0.00 0.00
November 142.28 109.28 33.00 226.51 73.76 0.00 0.00 0.00
December 153.88 121.91 31.97 237.23 99.03 0.00 0.00 0.00
                 
Annual Sum or Average 92.48 54.42 38.06 179.29 45.44 0.00 0.00 0.00
Minimum of Months 42.37 3.23 31.97 124.43 4.93 0.00 0.00 0.00
Maximum of Months 165.24 132.00 44.05 265.29 99.03 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 25.38 0.00 25.38 24.70 103.29 0.00 0.00 0.00
February 28.92 0.00 28.92 16.07 103.09 0.00 0.00 0.00
March 38.44 0.00 38.44 44.02 86.33 0.00 0.00 0.00
April 47.08 0.69 46.38 101.06 33.97 0.00 0.00 0.00
May 55.22 4.69 50.53 139.56 18.06 0.00 0.00 0.00
June 63.77 11.65 52.12 208.44 4.32 0.00 0.00 0.00
July 54.55 5.86 48.69 186.67 2.95 0.00 0.00 0.00
August 43.90 1.08 42.82 155.18 3.25 0.00 0.00 0.00
September 41.39 0.03 41.37 131.15 6.06 0.00 0.00 0.00
October 32.01 0.00 32.01 63.53 51.87 0.00 0.00 0.00
November 26.67 0.00 26.67 26.22 90.77 0.00 0.00 0.00
December 23.71 0.00 23.71 13.93 132.17 0.00 0.00 0.00
                 
Annual Sum or Average 40.13 2.00 38.12 92.91 52.81 0.00 0.00 0.00
Minimum of Months 23.71 0.00 23.71 13.93 2.95 0.00 0.00 0.00
Maximum of Months 63.77 11.65 52.12 208.44 132.17 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 22.71 0.00 22.71 22.10 92.40 0.00 0.00 0.00
February 25.87 0.00 25.87 14.37 92.24 0.00 0.00 0.00
March 34.39 0.00 34.39 39.38 77.24 0.00 0.00 0.00
April 42.12 0.62 41.50 90.42 30.39 0.00 0.00 0.00
May 49.41 4.20 45.21 124.86 16.16 0.00 0.00 0.00
June 57.06 10.43 46.63 186.50 3.87 0.00 0.00 0.00
July 48.81 5.24 43.56 167.02 2.64 0.00 0.00 0.00
August 39.27 0.96 38.31 138.84 2.90 0.00 0.00 0.00
September 37.04 0.02 37.01 117.34 5.43 0.00 0.00 0.00
October 28.64 0.00 28.64 56.84 46.41 0.00 0.00 0.00
November 23.86 0.00 23.86 23.46 81.21 0.00 0.00 0.00
December 21.21 0.00 21.21 12.46 118.24 0.00 0.00 0.00
                 
Annual Sum or Average 35.90 1.79 34.11 83.12 47.25 0.00 0.00 0.00
Minimum of Months 21.21 0.00 21.21 12.46 2.64 0.00 0.00 0.00
Maximum of Months 57.06 10.43 46.63 186.50 118.24 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 616.87 492.81 124.06 980.73 274.51 0.00 0.00 0.00
February 384.91 258.05 126.87 549.27 276.27 0.00 0.00 0.00
March 318.65 161.47 157.18 501.39 244.26 0.00 0.00 0.00
April 279.66 115.20 164.46 597.02 104.27 0.00 0.00 0.00
May 186.87 32.51 154.36 480.51 59.92 0.00 0.00 0.00
June 158.17 12.07 146.11 561.22 14.35 0.00 0.00 0.00
July 160.28 15.24 145.04 556.29 9.69 0.00 0.00 0.00
August 198.20 55.82 142.38 612.23 10.02 0.00 0.00 0.00
September 281.53 118.99 162.54 698.79 17.54 0.00 0.00 0.00
October 451.90 312.84 139.06 819.38 141.56 0.00 0.00 0.00
November 531.19 407.98 123.21 838.01 241.64 0.00 0.00 0.00
December 574.48 455.14 119.34 872.50 346.45 0.00 0.00 0.00
                 
Annual Sum or Average 345.26 203.16 142.10 673.27 144.52 0.00 0.00 0.00
Minimum of Months 158.17 12.07 119.34 480.51 9.69 0.00 0.00 0.00
Maximum of Months 616.87 492.81 164.46 980.73 346.45 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyReportMonthly

For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.223838E+10 0.178821E+10 0.450171E+09 0.352241E+10 0.981718E+09
February 0.126153E+10 0.845731E+09 0.415798E+09 0.180963E+10 0.858176E+09
March 0.115623E+10 0.585894E+09 0.570335E+09 0.182750E+10 0.845636E+09
April 0.982044E+09 0.404532E+09 0.577512E+09 0.203293E+10 0.386783E+09
May 0.678057E+09 0.117952E+09 0.560105E+09 0.164704E+10 0.239845E+09
June 0.555427E+09 42376069.35 0.513050E+09 0.184743E+10 61534314.25
July 0.581591E+09 55297824.35 0.526293E+09 0.191643E+10 39110474.19
August 0.719166E+09 0.202544E+09 0.516622E+09 0.211178E+10 44640341.68
September 0.988595E+09 0.417832E+09 0.570763E+09 0.235103E+10 78942972.48
October 0.163976E+10 0.113516E+10 0.504604E+09 0.291710E+10 0.531045E+09
November 0.186529E+10 0.143263E+10 0.432667E+09 0.292007E+10 0.836652E+09
December 0.208454E+10 0.165152E+10 0.433026E+09 0.313780E+10 0.121441E+10
           
Annual Sum or Average 0.147506E+11 0.867966E+10 0.607095E+10 0.280412E+11 0.611849E+10
Minimum of Months 0.555427E+09 42376069.35 0.415798E+09 0.164704E+10 39110474.19
Maximum of Months 0.223838E+10 0.178821E+10 0.577512E+09 0.352241E+10 0.121441E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: CAFE_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.630312E+10 0.503547E+10 0.126765E+10 0.988341E+10 0.279739E+10
February 0.355238E+10 0.238152E+10 0.117086E+10 0.505342E+10 0.245689E+10
March 0.325586E+10 0.164984E+10 0.160603E+10 0.509749E+10 0.241573E+10
April 0.276537E+10 0.113914E+10 0.162624E+10 0.570217E+10 0.112199E+10
May 0.190936E+10 0.332145E+09 0.157722E+10 0.460423E+10 0.712889E+09
June 0.156404E+10 0.119328E+09 0.144472E+10 0.517735E+10 0.198703E+09
July 0.163772E+10 0.155715E+09 0.148201E+10 0.532439E+10 0.125999E+09
August 0.202512E+10 0.570351E+09 0.145477E+10 0.590056E+10 0.154334E+09
September 0.278382E+10 0.117659E+10 0.160723E+10 0.658395E+10 0.265749E+09
October 0.461746E+10 0.319653E+10 0.142093E+10 0.818677E+10 0.154173E+10
November 0.525254E+10 0.403418E+10 0.121836E+10 0.818880E+10 0.238928E+10
December 0.586993E+10 0.465056E+10 0.121937E+10 0.878974E+10 0.345050E+10
           
Annual Sum or Average 0.415367E+11 0.244414E+11 0.170954E+11 0.784923E+11 0.176312E+11
Minimum of Months 0.156404E+10 0.119328E+09 0.117086E+10 0.460423E+10 0.125999E+09
Maximum of Months 0.630312E+10 0.503547E+10 0.162624E+10 0.988341E+10 0.345050E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: LOBBY_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.818812E+10 0.654136E+10 0.164675E+10 0.131852E+11 0.363059E+10
February 0.461475E+10 0.309374E+10 0.152101E+10 0.671977E+10 0.325194E+10
March 0.422955E+10 0.214323E+10 0.208632E+10 0.679328E+10 0.320549E+10
April 0.359238E+10 0.147980E+10 0.211257E+10 0.765749E+10 0.147351E+10
May 0.248037E+10 0.431476E+09 0.204890E+10 0.619266E+10 0.946278E+09
June 0.203178E+10 0.155014E+09 0.187677E+10 0.698462E+10 0.259765E+09
July 0.212749E+10 0.202283E+09 0.192521E+10 0.718351E+10 0.164111E+09
August 0.263075E+10 0.740919E+09 0.188983E+10 0.796935E+10 0.191852E+09
September 0.361634E+10 0.152845E+10 0.208788E+10 0.887343E+10 0.326812E+09
October 0.599834E+10 0.415247E+10 0.184587E+10 0.109662E+11 0.199188E+10
November 0.682335E+10 0.524063E+10 0.158272E+10 0.109225E+11 0.311192E+10
December 0.762538E+10 0.604134E+10 0.158404E+10 0.116913E+11 0.452547E+10
           
Annual Sum or Average 0.539586E+11 0.317507E+11 0.222079E+11 0.105139E+12 0.230796E+11
Minimum of Months 0.203178E+10 0.155014E+09 0.152101E+10 0.619266E+10 0.164111E+09
Maximum of Months 0.818812E+10 0.654136E+10 0.211257E+10 0.131852E+11 0.452547E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.442566E+09 0.353559E+09 89007348.67 0.695596E+09 0.199601E+09
February 0.249427E+09 0.167216E+09 82211105.16 0.354072E+09 0.175721E+09
March 0.228607E+09 0.115841E+09 0.112766E+09 0.353814E+09 0.175611E+09
April 0.194169E+09 79982898.78 0.114186E+09 0.395016E+09 78513672.51
May 0.134065E+09 23321164.89 0.110744E+09 0.319760E+09 48302716.69
June 0.109819E+09 8378476.71 0.101441E+09 0.367815E+09 11998030.37
July 0.114992E+09 10933329.61 0.104059E+09 0.379493E+09 7806358.79
August 0.142193E+09 40046470.60 0.102146E+09 0.419500E+09 8656102.59
September 0.195463E+09 82612529.72 0.112851E+09 0.465500E+09 14605298.66
October 0.324210E+09 0.224440E+09 99769849.61 0.574198E+09 0.106489E+09
November 0.368801E+09 0.283255E+09 85546508.11 0.574321E+09 0.170494E+09
December 0.412151E+09 0.326533E+09 85617432.54 0.621384E+09 0.247020E+09
           
Annual Sum or Average 0.291646E+10 0.171612E+10 0.120034E+10 0.552047E+10 0.124482E+10
Minimum of Months 0.109819E+09 8378476.71 82211105.16 0.319760E+09 7806358.79
Maximum of Months 0.442566E+09 0.353559E+09 0.114186E+09 0.695596E+09 0.247020E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_1_FLR_3_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.340154E+09 0.211926E+09 0.128229E+09 0.500815E+09 0.411228E+09
February 0.248858E+09 0.120775E+09 0.128083E+09 0.297123E+09 0.355248E+09
March 0.364588E+09 0.174372E+09 0.190216E+09 0.518195E+09 0.335019E+09
April 0.540336E+09 0.308393E+09 0.231943E+09 0.975073E+09 0.145790E+09
May 0.560366E+09 0.314023E+09 0.246343E+09 0.109871E+10 89311729.90
June 0.574867E+09 0.338034E+09 0.236833E+09 0.131183E+10 21674179.48
July 0.432114E+09 0.201359E+09 0.230755E+09 0.106809E+10 14269353.33
August 0.413642E+09 0.208000E+09 0.205642E+09 0.998428E+09 15831373.86
September 0.348351E+09 0.146469E+09 0.201882E+09 0.798532E+09 27509431.20
October 0.369811E+09 0.212073E+09 0.157738E+09 0.644359E+09 0.212781E+09
November 0.327596E+09 0.197665E+09 0.129932E+09 0.476937E+09 0.349172E+09
December 0.271608E+09 0.153993E+09 0.117616E+09 0.355896E+09 0.512669E+09
           
Annual Sum or Average 0.479229E+10 0.258708E+10 0.220521E+10 0.904399E+10 0.249050E+10
Minimum of Months 0.248858E+09 0.120775E+09 0.117616E+09 0.297123E+09 14269353.33
Maximum of Months 0.574867E+09 0.338034E+09 0.246343E+09 0.131183E+10 0.512669E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_2_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 53674072.02 0.00 53674072.02 52644882.37 0.213826E+09
February 55241433.50 0.00 55241433.50 33021342.35 0.188361E+09
March 81295770.76 3216.16 81292554.60 90610316.87 0.180702E+09
April 96350800.51 1418628.78 94932171.74 0.188184E+09 74486975.24
May 0.116786E+09 9916509.70 0.106870E+09 0.270185E+09 42930886.54
June 0.130521E+09 23848337.92 0.106672E+09 0.404407E+09 10559192.57
July 0.115375E+09 12397170.40 0.102978E+09 0.375017E+09 7003297.77
August 92836668.46 2279405.50 90557262.96 0.309160E+09 8062862.57
September 84720382.40 52432.38 84667950.02 0.249793E+09 14299851.77
October 67690153.51 0.00 67690153.51 0.124722E+09 0.111922E+09
November 54578999.93 0.00 54578999.93 52522058.54 0.183009E+09
December 50136496.34 0.00 50136496.34 32912333.79 0.268023E+09
           
Annual Sum or Average 0.999207E+09 49915700.83 0.949291E+09 0.218318E+10 0.130319E+10
Minimum of Months 50136496.34 0.00 50136496.34 32912333.79 7003297.77
Maximum of Months 0.130521E+09 23848337.92 0.106870E+09 0.404407E+09 0.268023E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_2_FLR_3_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.340154E+09 0.211926E+09 0.128229E+09 0.522224E+09 0.396519E+09
February 0.248858E+09 0.120775E+09 0.128083E+09 0.310100E+09 0.345203E+09
March 0.364588E+09 0.174372E+09 0.190216E+09 0.530369E+09 0.329266E+09
April 0.540336E+09 0.308393E+09 0.231943E+09 0.981761E+09 0.143632E+09
May 0.560366E+09 0.314023E+09 0.246343E+09 0.110032E+10 88893454.48
June 0.574867E+09 0.338034E+09 0.236833E+09 0.131092E+10 21694324.79
July 0.432114E+09 0.201359E+09 0.230755E+09 0.106844E+10 14269149.95
August 0.413642E+09 0.208000E+09 0.205642E+09 0.100208E+10 15521371.00
September 0.348351E+09 0.146469E+09 0.201882E+09 0.805206E+09 26569762.06
October 0.369811E+09 0.212073E+09 0.157738E+09 0.658946E+09 0.206186E+09
November 0.327596E+09 0.197665E+09 0.129932E+09 0.493795E+09 0.337470E+09
December 0.271608E+09 0.153993E+09 0.117616E+09 0.377104E+09 0.495302E+09
           
Annual Sum or Average 0.479229E+10 0.258708E+10 0.220521E+10 0.916128E+10 0.242053E+10
Minimum of Months 0.248858E+09 0.120775E+09 0.117616E+09 0.310100E+09 14269149.95
Maximum of Months 0.574867E+09 0.338034E+09 0.246343E+09 0.131092E+10 0.495302E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.353983E+09 0.282791E+09 71191720.82 0.541980E+09 0.190207E+09
February 0.199502E+09 0.133746E+09 65755807.07 0.270759E+09 0.170938E+09
March 0.182850E+09 92654621.17 90194909.73 0.269315E+09 0.167827E+09
April 0.155304E+09 63973596.40 91330373.15 0.307926E+09 80570885.62
May 0.107231E+09 18653222.29 88577606.46 0.247232E+09 52497954.33
June 87837819.98 6701448.63 81136371.35 0.283978E+09 15541416.58
July 91975290.32 8744924.55 83230365.76 0.286629E+09 10447176.85
August 0.113732E+09 32030806.41 81700800.92 0.320182E+09 13918632.51
September 0.156339E+09 66076882.86 90262586.66 0.357745E+09 22140271.55
October 0.259316E+09 0.179516E+09 79800009.62 0.446236E+09 0.107533E+09
November 0.294982E+09 0.226559E+09 68423598.87 0.446253E+09 0.164958E+09
December 0.329655E+09 0.261175E+09 68480327.14 0.481325E+09 0.230505E+09
           
Annual Sum or Average 0.233271E+10 0.137262E+10 0.960084E+09 0.425956E+10 0.122708E+10
Minimum of Months 87837819.98 6701448.63 65755807.07 0.247232E+09 10447176.85
Maximum of Months 0.353983E+09 0.282791E+09 91330373.15 0.541980E+09 0.230505E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 42944949.46 0.00 42944949.46 43821602.30 0.173583E+09
February 44199004.85 0.00 44199004.85 26062853.05 0.157007E+09
March 65045237.58 2573.27 65042664.31 74421221.25 0.146590E+09
April 77090857.89 1135053.46 75955804.43 0.161394E+09 56679407.48
May 93441433.49 7934259.35 85507174.14 0.229070E+09 31493736.85
June 0.104430E+09 19081199.32 85349110.47 0.341364E+09 6638073.99
July 92312481.83 9919050.97 82393430.86 0.315797E+09 4704943.93
August 74279179.59 1823766.12 72455413.47 0.262444E+09 5352069.58
September 67785290.05 41951.47 67743338.59 0.211688E+09 9822701.93
October 54159300.98 0.00 54159300.98 0.106262E+09 88582860.15
November 43668987.75 0.00 43668987.75 44140725.37 0.147944E+09
December 40114513.77 0.00 40114513.77 25782917.78 0.221063E+09
           
Annual Sum or Average 0.799472E+09 39937853.95 0.759534E+09 0.184225E+10 0.104946E+10
Minimum of Months 40114513.77 0.00 40114513.77 25782917.78 4704943.93
Maximum of Months 0.104430E+09 19081199.32 85507174.14 0.341364E+09 0.221063E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_5_FLR_3_WALL_EAST_WINDOW

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.323939E+09 0.203319E+09 0.120620E+09 0.430532E+09 0.372257E+09
February 0.290851E+09 0.167343E+09 0.123508E+09 0.341813E+09 0.332093E+09
March 0.399855E+09 0.205717E+09 0.194139E+09 0.547742E+09 0.310304E+09
April 0.551427E+09 0.328551E+09 0.222876E+09 0.982736E+09 0.130375E+09
May 0.591518E+09 0.350985E+09 0.240533E+09 0.114640E+10 78136024.27
June 0.595597E+09 0.370022E+09 0.225575E+09 0.135747E+10 18924615.83
July 0.520577E+09 0.293732E+09 0.226845E+09 0.122620E+10 12738270.41
August 0.494504E+09 0.282527E+09 0.211977E+09 0.113722E+10 15191618.64
September 0.392148E+09 0.189135E+09 0.203013E+09 0.871016E+09 25698019.51
October 0.406651E+09 0.247359E+09 0.159292E+09 0.688891E+09 0.195841E+09
November 0.302834E+09 0.181731E+09 0.121103E+09 0.401685E+09 0.320211E+09
December 0.285842E+09 0.172873E+09 0.112970E+09 0.332668E+09 0.468685E+09
           
Annual Sum or Average 0.515574E+10 0.299329E+10 0.216245E+10 0.946438E+10 0.228045E+10
Minimum of Months 0.285842E+09 0.167343E+09 0.112970E+09 0.332668E+09 12738270.41
Maximum of Months 0.595597E+09 0.370022E+09 0.240533E+09 0.135747E+10 0.468685E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.442566E+09 0.353559E+09 89007348.67 0.692710E+09 0.197978E+09
February 0.249427E+09 0.167216E+09 82211105.16 0.349876E+09 0.175785E+09
March 0.228607E+09 0.115841E+09 0.112766E+09 0.348701E+09 0.175150E+09
April 0.194169E+09 79982898.78 0.114186E+09 0.392249E+09 78159597.68
May 0.134065E+09 23321164.89 0.110744E+09 0.316882E+09 47745260.90
June 0.109819E+09 8378476.71 0.101441E+09 0.365755E+09 11435020.24
July 0.114992E+09 10933329.61 0.104059E+09 0.375964E+09 7627084.08
August 0.142193E+09 40046470.60 0.102146E+09 0.416486E+09 8634246.70
September 0.195463E+09 82612529.72 0.112851E+09 0.463505E+09 14479625.91
October 0.324210E+09 0.224440E+09 99769849.61 0.570432E+09 0.105771E+09
November 0.368801E+09 0.283255E+09 85546508.11 0.572226E+09 0.168669E+09
December 0.412151E+09 0.326533E+09 85617432.54 0.618301E+09 0.246227E+09
           
Annual Sum or Average 0.291646E+10 0.171612E+10 0.120034E+10 0.548309E+10 0.123766E+10
Minimum of Months 0.109819E+09 8378476.71 82211105.16 0.316882E+09 7627084.08
Maximum of Months 0.442566E+09 0.353559E+09 0.114186E+09 0.692710E+09 0.246227E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_6_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 53674072.02 0.00 53674072.02 50227958.45 0.212436E+09
February 55241433.50 0.00 55241433.50 30467234.39 0.190004E+09
March 81295770.76 3216.16 81292554.60 85940663.89 0.181163E+09
April 96350800.51 1418628.78 94932171.74 0.184826E+09 74352952.97
May 0.116786E+09 9916509.70 0.106870E+09 0.266817E+09 42109766.35
June 0.130521E+09 23848337.92 0.106672E+09 0.402530E+09 10114415.67
July 0.115375E+09 12397170.40 0.102978E+09 0.371491E+09 6843715.59
August 92836668.46 2279405.50 90557262.96 0.305902E+09 8013034.79
September 84720382.40 52432.38 84667950.02 0.247520E+09 14206983.19
October 67690153.51 0.00 67690153.51 0.120906E+09 0.112247E+09
November 54578999.93 0.00 54578999.93 50975438.34 0.181285E+09
December 50136496.34 0.00 50136496.34 30980972.96 0.267606E+09
           
Annual Sum or Average 0.999207E+09 49915700.83 0.949291E+09 0.214858E+10 0.130038E+10
Minimum of Months 50136496.34 0.00 50136496.34 30467234.39 6843715.59
Maximum of Months 0.130521E+09 23848337.92 0.106870E+09 0.402530E+09 0.267606E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_6_FLR_3_WALL_EAST_WINDOW

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.323939E+09 0.203319E+09 0.120620E+09 0.452722E+09 0.357457E+09
February 0.290851E+09 0.167343E+09 0.123508E+09 0.354661E+09 0.322097E+09
March 0.399855E+09 0.205717E+09 0.194139E+09 0.558939E+09 0.304529E+09
April 0.551427E+09 0.328551E+09 0.222876E+09 0.988606E+09 0.128464E+09
May 0.591518E+09 0.350985E+09 0.240533E+09 0.114801E+10 77762138.53
June 0.595597E+09 0.370022E+09 0.225575E+09 0.135683E+10 19013468.95
July 0.520577E+09 0.293732E+09 0.226845E+09 0.122666E+10 12754125.34
August 0.494504E+09 0.282527E+09 0.211977E+09 0.114076E+10 14888874.48
September 0.392148E+09 0.189135E+09 0.203013E+09 0.877359E+09 24818572.79
October 0.406651E+09 0.247359E+09 0.159292E+09 0.702137E+09 0.189699E+09
November 0.302834E+09 0.181731E+09 0.121103E+09 0.418823E+09 0.307713E+09
December 0.285842E+09 0.172873E+09 0.112970E+09 0.353230E+09 0.449607E+09
           
Annual Sum or Average 0.515574E+10 0.299329E+10 0.216245E+10 0.957873E+10 0.220880E+10
Minimum of Months 0.285842E+09 0.167343E+09 0.112970E+09 0.353230E+09 12754125.34
Maximum of Months 0.595597E+09 0.370022E+09 0.240533E+09 0.135683E+10 0.449607E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 67974825.56 0.00 67974825.56 70378947.54 0.274682E+09
February 69959789.98 0.00 69959789.98 42709610.62 0.246024E+09
March 0.102956E+09 4073.06 0.102952E+09 0.123833E+09 0.228424E+09
April 0.122022E+09 1796603.83 0.120226E+09 0.267501E+09 89800451.01
May 0.147902E+09 12558633.84 0.135344E+09 0.376049E+09 51250149.07
June 0.165296E+09 30202415.22 0.135094E+09 0.541498E+09 12887489.39
July 0.146116E+09 15700234.09 0.130415E+09 0.500316E+09 8956518.66
August 0.117572E+09 2886723.24 0.114685E+09 0.416777E+09 9998251.07
September 0.107293E+09 66402.30 0.107227E+09 0.338850E+09 18268630.55
October 85725308.41 0.00 85725308.41 0.172349E+09 0.141158E+09
November 69120859.66 0.00 69120859.66 72430829.00 0.232891E+09
December 63494709.17 0.00 63494709.17 40480684.46 0.352260E+09
           
Annual Sum or Average 0.126543E+10 63215085.59 0.120222E+10 0.296317E+10 0.166660E+10
Minimum of Months 63494709.17 0.00 63494709.17 40480684.46 8956518.66
Maximum of Months 0.165296E+09 30202415.22 0.135344E+09 0.541498E+09 0.352260E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 25058335.32 0.00 25058335.32 25944594.23 0.101259E+09
February 25790075.39 0.00 25790075.39 15744530.94 90694675.06
March 37953831.47 1501.50 37952329.97 45649828.88 84206556.08
April 44982438.94 662302.56 44320136.38 98611962.90 33104164.59
May 54522983.56 4629632.44 49893351.11 0.138627E+09 18892927.05
June 60934981.96 11133860.83 49801121.12 0.199619E+09 4750862.22
July 53864241.38 5787756.38 48076485.00 0.184437E+09 3301743.64
August 43341827.45 1064165.72 42277661.74 0.153641E+09 3685769.34
September 39552649.37 24478.64 39528170.73 0.124914E+09 6734573.67
October 31601898.29 0.00 31601898.29 63534809.55 52036676.26
November 25480810.94 0.00 25480810.94 26701002.69 85853391.24
December 23406778.91 0.00 23406778.91 14922856.47 0.129858E+09
           
Annual Sum or Average 0.466491E+09 23303698.08 0.443187E+09 0.109235E+10 0.614378E+09
Minimum of Months 23406778.91 0.00 23406778.91 14922856.47 3301743.64
Maximum of Months 60934981.96 11133860.83 49893351.11 0.199619E+09 0.129858E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.206500E+09 0.164969E+09 41530470.22 0.332253E+09 91012811.31
February 0.116382E+09 78022138.43 38359370.38 0.168866E+09 82292617.25
March 0.106667E+09 54051088.25 52616188.64 0.171351E+09 80449447.23
April 90598271.93 37319698.27 53278573.67 0.196465E+09 34430873.69
May 62554278.62 10881561.56 51672717.06 0.161966E+09 21277214.28
June 51241154.51 3909363.47 47331791.04 0.182139E+09 5452575.28
July 53654793.16 5101447.54 48553345.62 0.186381E+09 3702399.69
August 66346579.02 18685521.81 47661057.22 0.205692E+09 3894363.08
September 91202342.18 38546673.46 52655668.72 0.226838E+09 6666602.28
October 0.151275E+09 0.104723E+09 46552209.79 0.276931E+09 48117066.75
November 0.172081E+09 0.132165E+09 39915655.96 0.275218E+09 77340137.99
December 0.192308E+09 0.152359E+09 39948749.01 0.295150E+09 0.115234E+09
           
Annual Sum or Average 0.136081E+10 0.800734E+09 0.560076E+09 0.267925E+10 0.569870E+09
Minimum of Months 51241154.51 3909363.47 38359370.38 0.161966E+09 3702399.69
Maximum of Months 0.206500E+09 0.164969E+09 53278573.67 0.332253E+09 0.115234E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.560483E+09 0.447760E+09 0.112722E+09 0.901802E+09 0.247027E+09
February 0.315883E+09 0.211768E+09 0.104115E+09 0.458337E+09 0.223359E+09
March 0.289517E+09 0.146706E+09 0.142811E+09 0.465081E+09 0.218356E+09
April 0.245902E+09 0.101293E+09 0.144609E+09 0.533246E+09 93452281.07
May 0.169785E+09 29534783.85 0.140250E+09 0.439610E+09 57750711.72
June 0.139079E+09 10610812.10 0.128468E+09 0.494363E+09 14799404.61
July 0.145630E+09 13846372.09 0.131784E+09 0.505876E+09 10049070.07
August 0.180078E+09 50716328.22 0.129362E+09 0.558290E+09 10570097.97
September 0.247542E+09 0.104624E+09 0.142918E+09 0.615684E+09 18094522.22
October 0.410591E+09 0.284239E+09 0.126352E+09 0.751646E+09 0.130600E+09
November 0.467063E+09 0.358724E+09 0.108339E+09 0.746998E+09 0.209917E+09
December 0.521963E+09 0.413534E+09 0.108429E+09 0.801098E+09 0.312769E+09
           
Annual Sum or Average 0.369352E+10 0.217336E+10 0.152016E+10 0.727203E+10 0.154674E+10
Minimum of Months 0.139079E+09 10610812.10 0.104115E+09 0.439610E+09 10049070.07
Maximum of Months 0.560483E+09 0.447760E+09 0.144609E+09 0.901802E+09 0.312769E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.442566E+09 0.353559E+09 89007348.67 0.690169E+09 0.198956E+09
February 0.249427E+09 0.167216E+09 82211105.16 0.350699E+09 0.174469E+09
March 0.228607E+09 0.115841E+09 0.112766E+09 0.348990E+09 0.175632E+09
April 0.194169E+09 79982898.78 0.114186E+09 0.389278E+09 77903127.65
May 0.134065E+09 23321164.89 0.110744E+09 0.315768E+09 47484137.56
June 0.109819E+09 8378476.71 0.101441E+09 0.364850E+09 11510181.23
July 0.114992E+09 10933329.61 0.104059E+09 0.375605E+09 7670032.74
August 0.142193E+09 40046470.60 0.102146E+09 0.415095E+09 8562071.96
September 0.195463E+09 82612529.72 0.112851E+09 0.460319E+09 14274021.23
October 0.324210E+09 0.224440E+09 99769849.61 0.568218E+09 0.105633E+09
November 0.368801E+09 0.283255E+09 85546508.11 0.569064E+09 0.170112E+09
December 0.412151E+09 0.326533E+09 85617432.54 0.618272E+09 0.245446E+09
           
Annual Sum or Average 0.291646E+10 0.171612E+10 0.120034E+10 0.546633E+10 0.123765E+10
Minimum of Months 0.109819E+09 8378476.71 82211105.16 0.315768E+09 7670032.74
Maximum of Months 0.442566E+09 0.353559E+09 0.114186E+09 0.690169E+09 0.245446E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_1_FLR_6_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.340154E+09 0.211926E+09 0.128229E+09 0.494595E+09 0.407794E+09
February 0.248858E+09 0.120775E+09 0.128083E+09 0.292055E+09 0.351449E+09
March 0.364588E+09 0.174372E+09 0.190216E+09 0.509742E+09 0.333637E+09
April 0.540336E+09 0.308393E+09 0.231943E+09 0.961767E+09 0.144635E+09
May 0.560366E+09 0.314023E+09 0.246343E+09 0.108617E+10 88081317.68
June 0.574867E+09 0.338034E+09 0.236833E+09 0.129980E+10 21121531.01
July 0.432114E+09 0.201359E+09 0.230755E+09 0.105691E+10 14163449.57
August 0.413642E+09 0.208000E+09 0.205642E+09 0.987791E+09 15876062.70
September 0.348351E+09 0.146469E+09 0.201882E+09 0.789026E+09 27222712.56
October 0.369811E+09 0.212073E+09 0.157738E+09 0.636043E+09 0.210590E+09
November 0.327596E+09 0.197665E+09 0.129932E+09 0.470140E+09 0.346984E+09
December 0.271608E+09 0.153993E+09 0.117616E+09 0.352048E+09 0.506722E+09
           
Annual Sum or Average 0.479229E+10 0.258708E+10 0.220521E+10 0.893608E+10 0.246828E+10
Minimum of Months 0.248858E+09 0.120775E+09 0.117616E+09 0.292055E+09 14163449.57
Maximum of Months 0.574867E+09 0.338034E+09 0.246343E+09 0.129980E+10 0.506722E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_2_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 53674072.02 0.00 53674072.02 52311614.06 0.211408E+09
February 55241433.50 0.00 55241433.50 32352470.18 0.186065E+09
March 81295770.76 3216.16 81292554.60 88532139.83 0.179941E+09
April 96350800.51 1418628.78 94932171.74 0.184514E+09 74036155.65
May 0.116786E+09 9916509.70 0.106870E+09 0.266536E+09 42450963.44
June 0.130521E+09 23848337.92 0.106672E+09 0.400752E+09 10332590.39
July 0.115375E+09 12397170.40 0.102978E+09 0.370895E+09 6974394.75
August 92836668.46 2279405.50 90557262.96 0.305354E+09 8103064.30
September 84720382.40 52432.38 84667950.02 0.246531E+09 14154503.83
October 67690153.51 0.00 67690153.51 0.122799E+09 0.110605E+09
November 54578999.93 0.00 54578999.93 51566501.41 0.181453E+09
December 50136496.34 0.00 50136496.34 33255359.82 0.264186E+09
           
Annual Sum or Average 0.999207E+09 49915700.83 0.949291E+09 0.215540E+10 0.128971E+10
Minimum of Months 50136496.34 0.00 50136496.34 32352470.18 6974394.75
Maximum of Months 0.130521E+09 23848337.92 0.106870E+09 0.400752E+09 0.264186E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_2_FLR_6_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.340154E+09 0.211926E+09 0.128229E+09 0.517402E+09 0.391897E+09
February 0.248858E+09 0.120775E+09 0.128083E+09 0.306070E+09 0.340575E+09
March 0.364588E+09 0.174372E+09 0.190216E+09 0.522322E+09 0.327595E+09
April 0.540336E+09 0.308393E+09 0.231943E+09 0.968172E+09 0.142480E+09
May 0.560366E+09 0.314023E+09 0.246343E+09 0.108769E+10 87666215.09
June 0.574867E+09 0.338034E+09 0.236833E+09 0.129886E+10 21143780.56
July 0.432114E+09 0.201359E+09 0.230755E+09 0.105725E+10 14163662.13
August 0.413642E+09 0.208000E+09 0.205642E+09 0.991455E+09 15562641.77
September 0.348351E+09 0.146469E+09 0.201882E+09 0.795704E+09 26272978.60
October 0.369811E+09 0.212073E+09 0.157738E+09 0.650937E+09 0.203662E+09
November 0.327596E+09 0.197665E+09 0.129932E+09 0.487922E+09 0.334392E+09
December 0.271608E+09 0.153993E+09 0.117616E+09 0.375017E+09 0.488237E+09
           
Annual Sum or Average 0.479229E+10 0.258708E+10 0.220521E+10 0.905880E+10 0.239365E+10
Minimum of Months 0.248858E+09 0.120775E+09 0.117616E+09 0.306070E+09 14163662.13
Maximum of Months 0.574867E+09 0.338034E+09 0.246343E+09 0.129886E+10 0.488237E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.649066E+09 0.518528E+09 0.130538E+09 0.996987E+09 0.303131E+09
February 0.365808E+09 0.245238E+09 0.120570E+09 0.502344E+09 0.267772E+09
March 0.335275E+09 0.169892E+09 0.165382E+09 0.504198E+09 0.262224E+09
April 0.284767E+09 0.117303E+09 0.167464E+09 0.579292E+09 0.110748E+09
May 0.196619E+09 34202726.45 0.162417E+09 0.479003E+09 65270934.12
June 0.161060E+09 12287840.18 0.148772E+09 0.558664E+09 14096782.23
July 0.168647E+09 16034777.14 0.152612E+09 0.569314E+09 9977035.33
August 0.208539E+09 58731992.40 0.149807E+09 0.623825E+09 11317132.72
September 0.286666E+09 0.121159E+09 0.165506E+09 0.682573E+09 19758031.52
October 0.475485E+09 0.329163E+09 0.146322E+09 0.828316E+09 0.157697E+09
November 0.540882E+09 0.415420E+09 0.125462E+09 0.823020E+09 0.258090E+09
December 0.604458E+09 0.478892E+09 0.125566E+09 0.887473E+09 0.376859E+09
           
Annual Sum or Average 0.427727E+10 0.251685E+10 0.176042E+10 0.803501E+10 0.185694E+10
Minimum of Months 0.161060E+09 12287840.18 0.120570E+09 0.479003E+09 9977035.33
Maximum of Months 0.649066E+09 0.518528E+09 0.167464E+09 0.996987E+09 0.376859E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: BANQUET_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.375704E+09 0.00 0.375704E+09 0.368983E+09 0.158112E+10
February 0.386675E+09 0.00 0.386675E+09 0.209229E+09 0.143648E+10
March 0.569049E+09 22512.27 0.569026E+09 0.634830E+09 0.135852E+10
April 0.674430E+09 9930025.34 0.664500E+09 0.142369E+10 0.565592E+09
May 0.817473E+09 69412938.91 0.748060E+09 0.201118E+10 0.339741E+09
June 0.913609E+09 0.166932E+09 0.746677E+09 0.293723E+10 94941368.79
July 0.807597E+09 86776906.14 0.720820E+09 0.269484E+10 65366436.79
August 0.649832E+09 15955234.21 0.633877E+09 0.224588E+10 81751330.29
September 0.593020E+09 367012.78 0.592653E+09 0.183325E+10 0.138136E+09
October 0.473813E+09 0.00 0.473813E+09 0.931358E+09 0.840929E+09
November 0.382039E+09 0.00 0.382039E+09 0.373230E+09 0.136065E+10
December 0.350942E+09 0.00 0.350942E+09 0.208456E+09 0.199041E+10
           
Annual Sum or Average 0.699418E+10 0.349397E+09 0.664479E+10 0.158721E+11 0.985364E+10
Minimum of Months 0.350942E+09 0.00 0.350942E+09 0.208456E+09 65366436.79
Maximum of Months 0.913609E+09 0.166932E+09 0.748060E+09 0.293723E+10 0.199041E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: DINING_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.375704E+09 0.00 0.375704E+09 0.355459E+09 0.162003E+10
February 0.386675E+09 0.00 0.386675E+09 0.199516E+09 0.147627E+10
March 0.569049E+09 22512.27 0.569026E+09 0.615559E+09 0.139624E+10
April 0.674430E+09 9930025.34 0.664500E+09 0.139229E+10 0.591582E+09
May 0.817473E+09 69412938.91 0.748060E+09 0.196880E+10 0.359898E+09
June 0.913609E+09 0.166932E+09 0.746677E+09 0.289159E+10 0.103090E+09
July 0.807597E+09 86776906.14 0.720820E+09 0.264469E+10 71220136.87
August 0.649832E+09 15955234.21 0.633877E+09 0.220004E+10 91553498.84
September 0.593020E+09 367012.78 0.592653E+09 0.179220E+10 0.153118E+09
October 0.473813E+09 0.00 0.473813E+09 0.906671E+09 0.872434E+09
November 0.382039E+09 0.00 0.382039E+09 0.359403E+09 0.139902E+10
December 0.350942E+09 0.00 0.350942E+09 0.198293E+09 0.203159E+10
           
Annual Sum or Average 0.699418E+10 0.349397E+09 0.664479E+10 0.155245E+11 0.101661E+11
Minimum of Months 0.350942E+09 0.00 0.350942E+09 0.198293E+09 71220136.87
Maximum of Months 0.913609E+09 0.166932E+09 0.748060E+09 0.289159E+10 0.203159E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: KITCHEN_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 53674072.02 0.00 53674072.02 52505089.23 0.241587E+09
February 55241433.50 0.00 55241433.50 29919754.09 0.221045E+09
March 81295770.76 3216.16 81292554.60 89475325.84 0.210769E+09
April 96350800.51 1418628.78 94932171.74 0.199303E+09 91582036.15
May 0.116786E+09 9916509.70 0.106870E+09 0.284194E+09 57899714.41
June 0.130521E+09 23848337.92 0.106672E+09 0.416001E+09 16302065.68
July 0.115375E+09 12397170.40 0.102978E+09 0.381142E+09 12510217.29
August 92836668.46 2279405.50 90557262.96 0.318949E+09 16976856.63
September 84720382.40 52432.38 84667950.02 0.258707E+09 25524228.56
October 67690153.51 0.00 67690153.51 0.129487E+09 0.134069E+09
November 54578999.93 0.00 54578999.93 52915628.79 0.210106E+09
December 50136496.34 0.00 50136496.34 31452485.86 0.295913E+09
           
Annual Sum or Average 0.999207E+09 49915700.83 0.949291E+09 0.224405E+10 0.153428E+10
Minimum of Months 50136496.34 0.00 50136496.34 29919754.09 12510217.29
Maximum of Months 0.130521E+09 23848337.92 0.106870E+09 0.416001E+09 0.295913E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: KITCHEN_FLR_6_WALL_EAST_WINDOW

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.647832E+09 0.406608E+09 0.241223E+09 0.915097E+09 0.824599E+09
February 0.581660E+09 0.334662E+09 0.246998E+09 0.711208E+09 0.762740E+09
March 0.799654E+09 0.411405E+09 0.388250E+09 0.113230E+10 0.723240E+09
April 0.110278E+10 0.657056E+09 0.445720E+09 0.203390E+10 0.326963E+09
May 0.118295E+10 0.701920E+09 0.481032E+09 0.235633E+10 0.215590E+09
June 0.119111E+10 0.739991E+09 0.451119E+09 0.275712E+10 61243899.45
July 0.104108E+10 0.587423E+09 0.453658E+09 0.248426E+10 46804421.74
August 0.988937E+09 0.565014E+09 0.423923E+09 0.232332E+10 63613453.85
September 0.784240E+09 0.378243E+09 0.405997E+09 0.179105E+10 93499803.50
October 0.813243E+09 0.494683E+09 0.318561E+09 0.143866E+10 0.463487E+09
November 0.605626E+09 0.363437E+09 0.242189E+09 0.847847E+09 0.724915E+09
December 0.571644E+09 0.345721E+09 0.225923E+09 0.712178E+09 0.100741E+10
           
Annual Sum or Average 0.103108E+11 0.598616E+10 0.432459E+10 0.195033E+11 0.531410E+10
Minimum of Months 0.571644E+09 0.334662E+09 0.225923E+09 0.711208E+09 46804421.74
Maximum of Months 0.119111E+10 0.739991E+09 0.481032E+09 0.275712E+10 0.100741E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.442566E+09 0.353559E+09 89007348.67 0.710561E+09 0.219197E+09
February 0.249427E+09 0.167216E+09 82211105.16 0.358989E+09 0.200834E+09
March 0.228607E+09 0.115841E+09 0.112766E+09 0.359396E+09 0.201857E+09
April 0.194169E+09 79982898.78 0.114186E+09 0.408804E+09 94458376.31
May 0.134065E+09 23321164.89 0.110744E+09 0.333280E+09 62576462.20
June 0.109819E+09 8378476.71 0.101441E+09 0.378028E+09 17416979.97
July 0.114992E+09 10933329.61 0.104059E+09 0.386098E+09 13206466.18
August 0.142193E+09 40046470.60 0.102146E+09 0.431333E+09 17205245.53
September 0.195463E+09 82612529.72 0.112851E+09 0.477423E+09 25355635.80
October 0.324210E+09 0.224440E+09 99769849.61 0.587607E+09 0.124415E+09
November 0.368801E+09 0.283255E+09 85546508.11 0.587108E+09 0.191182E+09
December 0.412151E+09 0.326533E+09 85617432.54 0.635402E+09 0.265253E+09
           
Annual Sum or Average 0.291646E+10 0.171612E+10 0.120034E+10 0.565403E+10 0.143296E+10
Minimum of Months 0.109819E+09 8378476.71 82211105.16 0.333280E+09 13206466.18
Maximum of Months 0.442566E+09 0.353559E+09 0.114186E+09 0.710561E+09 0.265253E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 67974825.56 0.00 67974825.56 66146788.52 0.276650E+09
February 69959789.98 0.00 69959789.98 38865852.55 0.249401E+09
March 0.102956E+09 4073.06 0.102952E+09 0.117895E+09 0.231239E+09
April 0.122022E+09 1796603.83 0.120226E+09 0.261942E+09 88039438.57
May 0.147902E+09 12558633.84 0.135344E+09 0.373785E+09 48366798.85
June 0.165296E+09 30202415.22 0.135094E+09 0.540288E+09 11209524.24
July 0.146116E+09 15700234.09 0.130415E+09 0.499988E+09 7914514.81
August 0.117572E+09 2886723.24 0.114685E+09 0.415630E+09 8692084.98
September 0.107293E+09 66402.30 0.107227E+09 0.339945E+09 15718653.18
October 85725308.41 0.00 85725308.41 0.170163E+09 0.138934E+09
November 69120859.66 0.00 69120859.66 67953103.09 0.235288E+09
December 63494709.17 0.00 63494709.17 37314214.64 0.354006E+09
           
Annual Sum or Average 0.126543E+10 63215085.59 0.120222E+10 0.292992E+10 0.166546E+10
Minimum of Months 63494709.17 0.00 63494709.17 37314214.64 7914514.81
Maximum of Months 0.165296E+09 30202415.22 0.135344E+09 0.540288E+09 0.354006E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 60817333.99 0.00 60817333.99 59181782.32 0.247489E+09
February 62593289.17 0.00 62593289.17 34773425.54 0.223140E+09
March 92115091.26 3644.19 92111447.08 0.105481E+09 0.206891E+09
April 0.109174E+09 1607428.26 0.107566E+09 0.234361E+09 78769219.27
May 0.132329E+09 11236257.28 0.121093E+09 0.334427E+09 43273958.19
June 0.147891E+09 27022215.34 0.120869E+09 0.483398E+09 10029203.81
July 0.130730E+09 14047058.93 0.116683E+09 0.447341E+09 7081146.39
August 0.105192E+09 2582762.23 0.102609E+09 0.371865E+09 7776841.36
September 95995470.41 59410.39 95936060.02 0.304150E+09 14063538.56
October 76698758.25 0.00 76698758.25 0.152246E+09 0.124307E+09
November 61842695.04 0.00 61842695.04 60797898.81 0.210504E+09
December 56808956.88 0.00 56808956.88 33385169.23 0.316687E+09
           
Annual Sum or Average 0.113219E+10 56558776.60 0.107563E+10 0.262141E+10 0.149001E+10
Minimum of Months 56808956.88 0.00 56808956.88 33385169.23 7081146.39
Maximum of Months 0.147891E+09 27022215.34 0.121093E+09 0.483398E+09 0.316687E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.165223E+10 0.131994E+10 0.332291E+09 0.262678E+10 0.735242E+09
February 0.931184E+09 0.624266E+09 0.306919E+09 0.132879E+10 0.668352E+09
March 0.853459E+09 0.432470E+09 0.420989E+09 0.134293E+10 0.654224E+09
April 0.724889E+09 0.298600E+09 0.426289E+09 0.154747E+10 0.270280E+09
May 0.500505E+09 87064857.88 0.413440E+09 0.128700E+10 0.160502E+09
June 0.409987E+09 31279350.23 0.378708E+09 0.145467E+10 37194156.47
July 0.429299E+09 40817377.39 0.388482E+09 0.148996E+10 25961637.07
August 0.530848E+09 0.149505E+09 0.381343E+09 0.163979E+10 26836847.04
September 0.729722E+09 0.308417E+09 0.421305E+09 0.181126E+10 45474104.48
October 0.121037E+10 0.837901E+09 0.372471E+09 0.219464E+10 0.379151E+09
November 0.137684E+10 0.105747E+10 0.319371E+09 0.217213E+10 0.626322E+09
December 0.153868E+10 0.121905E+10 0.319635E+09 0.233691E+10 0.927938E+09
           
Annual Sum or Average 0.108880E+11 0.640678E+10 0.448124E+10 0.212323E+11 0.455748E+10
Minimum of Months 0.409987E+09 31279350.23 0.306919E+09 0.128700E+10 25961637.07
Maximum of Months 0.165223E+10 0.131994E+10 0.426289E+09 0.262678E+10 0.927938E+09



Table of Contents

Report: WindowZoneSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 1315.12 366.53 835.71 667.64 168.07 0.00 0.00
February 748.03 354.74 521.47 349.59 171.87 0.00 0.00
March 682.31 315.72 431.69 218.75 212.94 0.00 0.00
April 784.31 149.22 378.88 156.07 222.81 0.00 0.00
May 614.93 89.55 253.16 44.04 209.12 0.00 0.00
June 712.74 23.74 214.28 16.35 197.94 0.00 0.00
July 715.51 14.60 217.14 20.65 196.50 0.00 0.00
August 788.45 16.67 268.51 75.62 192.88 0.00 0.00
September 907.03 30.46 381.40 161.20 220.20 0.00 0.00
October 1089.12 198.27 612.22 423.82 188.40 0.00 0.00
November 1126.57 322.78 719.63 552.71 166.92 0.00 0.00
December 1171.52 453.41 778.28 616.61 161.67 0.00 0.00
               
Annual Sum or Average 889.18 194.02 467.74 275.23 192.51 0.00 0.00
Minimum of Months 614.93 14.60 214.28 16.35 161.67 0.00 0.00
Maximum of Months 1315.12 453.41 835.71 667.64 222.81 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 3690.04 1044.43 2353.32 1880.03 473.29 0.00 0.00
February 2088.88 1015.58 1468.41 984.43 483.99 0.00 0.00
March 1903.18 901.93 1215.60 615.98 599.62 0.00 0.00
April 2199.91 432.87 1066.89 439.48 627.41 0.00 0.00
May 1719.02 266.16 712.87 124.01 588.87 0.00 0.00
June 1997.43 76.66 603.41 46.04 557.38 0.00 0.00
July 1987.90 47.04 611.46 58.14 553.32 0.00 0.00
August 2203.02 57.62 756.09 212.94 543.15 0.00 0.00
September 2540.10 102.53 1074.00 453.93 620.07 0.00 0.00
October 3056.59 575.62 1723.96 1193.45 530.51 0.00 0.00
November 3159.26 921.79 2026.44 1556.40 470.05 0.00 0.00
December 3281.71 1288.27 2191.58 1736.32 455.26 0.00 0.00
               
Annual Sum or Average 2488.97 559.08 1317.12 775.03 542.09 0.00 0.00
Minimum of Months 1719.02 47.04 603.41 46.04 455.26 0.00 0.00
Maximum of Months 3690.04 1288.27 2353.32 1880.03 627.41 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 4922.79 1355.51 3057.09 2442.27 614.83 0.00 0.00
February 2777.68 1344.22 1907.55 1278.83 628.73 0.00 0.00
March 2536.32 1196.79 1579.13 800.19 778.94 0.00 0.00
April 2954.28 568.48 1385.95 570.91 815.04 0.00 0.00
May 2312.07 353.30 926.06 161.09 764.97 0.00 0.00
June 2694.69 100.22 783.87 59.80 724.06 0.00 0.00
July 2682.01 61.27 794.32 75.52 718.79 0.00 0.00
August 2975.42 71.63 982.21 276.63 705.58 0.00 0.00
September 3423.39 126.09 1395.19 589.68 805.51 0.00 0.00
October 4094.30 743.68 2239.52 1550.35 689.17 0.00 0.00
November 4213.92 1200.59 2632.46 2021.85 610.62 0.00 0.00
December 4365.03 1689.62 2846.99 2255.58 591.41 0.00 0.00
               
Annual Sum or Average 3333.94 731.85 1711.02 1006.81 704.21 0.00 0.00
Minimum of Months 2312.07 61.27 783.87 59.80 591.41 0.00 0.00
Maximum of Months 4922.79 1689.62 3057.09 2442.27 815.04 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 438.18 219.55 292.23 211.13 81.11 0.00 0.00
February 262.90 213.21 205.97 119.04 86.93 0.00 0.00
March 323.25 188.32 221.47 108.35 113.12 0.00 0.00
April 528.39 86.35 283.37 149.84 133.54 0.00 0.00
May 529.59 51.38 259.27 125.95 133.32 0.00 0.00
June 648.01 12.99 264.15 133.65 130.51 0.00 0.00
July 540.47 8.24 204.27 79.26 125.00 0.00 0.00
August 529.38 9.13 207.52 92.61 114.91 0.00 0.00
September 487.65 16.23 209.80 88.38 121.42 0.00 0.00
October 452.23 116.47 259.12 162.98 96.14 0.00 0.00
November 398.42 193.33 268.67 185.54 83.13 0.00 0.00
December 353.29 272.06 255.29 179.41 75.88 0.00 0.00
               
Annual Sum or Average 458.61 115.22 244.44 136.45 107.99 0.00 0.00
Minimum of Months 262.90 8.24 204.27 79.26 75.88 0.00 0.00
Maximum of Months 648.01 272.06 292.23 211.13 133.54 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 213.98 227.23 147.04 79.12 67.91 0.00 0.00
February 140.36 219.08 125.70 49.92 75.78 0.00 0.00
March 230.26 188.81 166.47 65.10 101.37 0.00 0.00
April 451.22 84.01 245.64 119.53 126.11 0.00 0.00
May 510.31 47.84 252.82 120.95 131.87 0.00 0.00
June 661.09 11.75 272.14 139.62 132.53 0.00 0.00
July 538.67 7.68 204.41 79.81 124.60 0.00 0.00
August 489.45 8.70 189.10 78.51 110.59 0.00 0.00
September 407.02 15.76 167.08 56.53 110.55 0.00 0.00
October 292.17 118.34 163.34 79.18 84.17 0.00 0.00
November 209.86 199.89 147.44 76.26 71.18 0.00 0.00
December 151.85 283.76 120.13 57.49 62.63 0.00 0.00
               
Annual Sum or Average 359.00 117.34 183.65 83.62 100.03 0.00 0.00
Minimum of Months 140.36 7.68 120.13 49.92 62.63 0.00 0.00
Maximum of Months 661.09 283.76 272.14 139.62 132.53 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 202.35 71.02 132.16 105.58 26.58 0.00 0.00
February 111.92 70.66 82.47 55.29 27.18 0.00 0.00
March 100.55 62.66 68.27 34.59 33.67 0.00 0.00
April 118.80 31.08 59.92 24.68 35.24 0.00 0.00
May 92.31 19.60 40.04 6.96 33.07 0.00 0.00
June 109.56 6.00 33.89 2.59 31.30 0.00 0.00
July 107.02 3.90 34.34 3.26 31.07 0.00 0.00
August 119.54 5.20 42.46 11.96 30.50 0.00 0.00
September 138.02 8.54 60.32 25.49 34.82 0.00 0.00
October 166.61 40.15 96.82 67.02 29.79 0.00 0.00
November 172.17 63.64 113.80 87.41 26.40 0.00 0.00
December 179.71 86.06 123.08 97.51 25.57 0.00 0.00
               
Annual Sum or Average 135.07 38.91 73.97 43.53 30.44 0.00 0.00
Minimum of Months 92.31 3.90 33.89 2.59 25.57 0.00 0.00
Maximum of Months 202.35 86.06 132.16 105.58 35.24 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 16.36 64.81 16.03 0.00 16.03 0.00 0.00
February 10.77 64.90 18.27 0.00 18.27 0.00 0.00
March 27.79 54.73 24.29 0.00 24.28 0.00 0.00
April 62.27 21.87 29.74 0.44 29.30 0.00 0.00
May 85.52 11.76 34.89 2.96 31.92 0.00 0.00
June 131.70 2.56 40.29 7.36 32.93 0.00 0.00
July 117.90 1.76 34.47 3.70 30.76 0.00 0.00
August 97.99 2.00 27.73 0.68 27.05 0.00 0.00
September 81.67 3.79 26.15 0.02 26.14 0.00 0.00
October 39.67 33.07 20.22 0.00 20.22 0.00 0.00
November 17.03 57.08 16.85 0.00 16.85 0.00 0.00
December 9.63 82.54 14.98 0.00 14.98 0.00 0.00
               
Annual Sum or Average 58.42 33.28 25.35 1.27 24.08 0.00 0.00
Minimum of Months 9.63 1.76 14.98 0.00 14.98 0.00 0.00
Maximum of Months 131.70 82.54 40.29 7.36 32.93 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 417.74 211.28 286.18 207.91 78.27 0.00 0.00
February 283.43 207.45 223.33 138.29 85.04 0.00 0.00
March 331.05 177.61 234.64 120.06 114.59 0.00 0.00
April 527.28 77.26 287.65 157.61 130.04 0.00 0.00
May 544.24 44.91 270.90 139.75 131.15 0.00 0.00
June 664.38 11.27 272.15 145.99 126.16 0.00 0.00
July 597.90 7.33 237.29 113.75 123.55 0.00 0.00
August 579.92 8.73 237.72 120.44 117.28 0.00 0.00
September 514.61 15.25 226.70 104.84 121.86 0.00 0.00
October 469.07 111.50 272.87 176.15 96.72 0.00 0.00
November 373.77 186.65 259.12 179.39 79.73 0.00 0.00
December 351.87 263.73 260.60 186.46 74.14 0.00 0.00
               
Annual Sum or Average 472.28 109.86 255.97 149.33 106.63 0.00 0.00
Minimum of Months 283.43 7.33 223.33 104.84 74.14 0.00 0.00
Maximum of Months 664.38 263.73 287.65 207.91 131.15 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 180.58 205.57 140.98 75.91 65.07 0.00 0.00
February 152.29 204.78 143.06 69.17 73.89 0.00 0.00
March 234.81 175.38 179.64 76.81 102.83 0.00 0.00
April 450.49 76.03 249.91 127.30 122.61 0.00 0.00
May 528.05 44.57 264.45 134.75 129.71 0.00 0.00
June 678.77 11.24 280.14 151.96 128.18 0.00 0.00
July 596.67 7.30 237.44 114.30 123.14 0.00 0.00
August 540.11 8.54 219.29 106.33 112.95 0.00 0.00
September 433.70 14.78 183.98 72.99 110.99 0.00 0.00
October 303.44 108.88 177.10 92.35 84.75 0.00 0.00
November 174.97 182.38 137.89 70.11 67.78 0.00 0.00
December 134.19 258.51 125.44 64.54 60.90 0.00 0.00
               
Annual Sum or Average 368.37 107.78 195.17 96.50 98.67 0.00 0.00
Minimum of Months 134.19 7.30 125.44 64.54 60.90 0.00 0.00
Maximum of Months 678.77 258.51 280.14 151.96 129.71 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 486.91 256.77 321.09 228.77 92.33 0.00 0.00
February 275.78 257.88 218.26 119.79 98.47 0.00 0.00
March 299.19 226.58 200.53 74.96 125.57 0.00 0.00
April 422.58 96.56 194.25 54.43 139.83 0.00 0.00
May 415.08 54.02 162.32 21.51 140.82 0.00 0.00
June 546.14 13.84 160.71 21.55 139.16 0.00 0.00
July 513.79 9.39 149.07 15.10 133.97 0.00 0.00
August 498.08 10.38 152.08 27.39 124.70 0.00 0.00
September 503.94 19.17 187.34 55.27 132.07 0.00 0.00
October 469.13 135.89 253.58 145.22 108.36 0.00 0.00
November 424.02 225.20 283.08 189.39 93.69 0.00 0.00
December 415.72 325.54 299.12 211.28 87.84 0.00 0.00
               
Annual Sum or Average 440.16 135.45 215.19 97.05 118.14 0.00 0.00
Minimum of Months 275.78 9.39 149.07 15.10 87.84 0.00 0.00
Maximum of Months 546.14 325.54 321.09 228.77 140.82 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 434.28 218.47 292.23 211.13 81.11 0.00 0.00
February 259.66 211.37 205.97 119.04 86.93 0.00 0.00
March 318.31 187.84 221.47 108.35 113.12 0.00 0.00
April 521.04 85.65 283.37 149.84 133.54 0.00 0.00
May 523.42 50.61 259.27 125.95 133.32 0.00 0.00
June 642.22 12.59 264.15 133.65 130.51 0.00 0.00
July 534.84 8.15 204.27 79.26 125.00 0.00 0.00
August 523.77 9.11 207.52 92.61 114.91 0.00 0.00
September 481.98 15.99 209.80 88.38 121.42 0.00 0.00
October 447.03 115.47 259.12 162.98 96.14 0.00 0.00
November 394.05 192.62 268.67 185.54 83.13 0.00 0.00
December 351.29 269.84 255.29 179.41 75.88 0.00 0.00
               
Annual Sum or Average 453.62 114.43 244.44 136.45 107.99 0.00 0.00
Minimum of Months 259.66 8.15 204.27 79.26 75.88 0.00 0.00
Maximum of Months 642.22 269.84 292.23 211.13 133.54 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 212.03 224.58 147.04 79.12 67.91 0.00 0.00
February 138.35 216.16 125.70 49.92 75.78 0.00 0.00
March 226.42 187.85 166.47 65.10 101.37 0.00 0.00
April 444.56 83.38 245.64 119.53 126.11 0.00 0.00
May 504.27 47.24 252.82 120.95 131.87 0.00 0.00
June 655.05 11.48 272.14 139.62 132.53 0.00 0.00
July 532.96 7.64 204.41 79.81 124.60 0.00 0.00
August 484.06 8.73 189.10 78.51 110.59 0.00 0.00
September 402.09 15.59 167.08 56.53 110.55 0.00 0.00
October 288.44 116.90 163.34 79.18 84.17 0.00 0.00
November 207.18 198.06 147.44 76.26 71.18 0.00 0.00
December 151.24 279.73 120.13 57.49 62.63 0.00 0.00
               
Annual Sum or Average 354.86 116.06 183.65 83.62 100.03 0.00 0.00
Minimum of Months 138.35 7.64 120.13 49.92 62.63 0.00 0.00
Maximum of Months 655.05 279.73 272.14 139.62 132.53 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 372.23 113.18 242.33 193.60 48.74 0.00 0.00
February 207.65 110.69 151.21 101.37 49.84 0.00 0.00
March 188.25 97.90 125.18 63.43 61.75 0.00 0.00
April 223.49 42.73 109.86 45.26 64.61 0.00 0.00
May 178.84 24.37 73.41 12.77 60.64 0.00 0.00
June 215.53 5.44 62.14 4.74 57.40 0.00 0.00
July 212.56 3.72 62.97 5.99 56.98 0.00 0.00
August 232.91 4.23 77.86 21.93 55.93 0.00 0.00
September 263.34 7.62 110.60 46.74 63.85 0.00 0.00
October 309.26 58.88 177.53 122.90 54.63 0.00 0.00
November 317.52 99.57 208.67 160.27 48.40 0.00 0.00
December 331.34 140.70 225.68 178.80 46.88 0.00 0.00
               
Annual Sum or Average 254.79 58.88 135.63 79.81 55.82 0.00 0.00
Minimum of Months 178.84 3.72 62.14 4.74 46.88 0.00 0.00
Maximum of Months 372.23 140.70 242.33 193.60 64.61 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 137.76 590.32 140.27 0.00 140.27 0.00 0.00
February 86.49 593.78 159.84 0.00 159.84 0.00 0.00
March 237.02 507.21 212.46 0.01 212.45 0.00 0.00
April 549.26 218.21 260.20 3.83 256.37 0.00 0.00
May 750.89 126.84 305.21 25.92 279.29 0.00 0.00
June 1133.19 36.63 352.47 64.40 288.07 0.00 0.00
July 1006.14 24.41 301.52 32.40 269.12 0.00 0.00
August 838.51 30.52 242.62 5.96 236.66 0.00 0.00
September 707.27 53.29 228.79 0.14 228.65 0.00 0.00
October 347.73 313.97 176.90 0.00 176.90 0.00 0.00
November 143.99 524.94 147.39 0.00 147.39 0.00 0.00
December 77.83 743.13 131.03 0.00 131.03 0.00 0.00
               
Annual Sum or Average 503.30 312.46 221.78 11.08 210.70 0.00 0.00
Minimum of Months 77.83 24.41 131.03 0.00 131.03 0.00 0.00
Maximum of Months 1133.19 743.13 352.47 64.40 288.07 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 132.71 604.85 140.27 0.00 140.27 0.00 0.00
February 82.47 610.23 159.84 0.00 159.84 0.00 0.00
March 229.82 521.30 212.46 0.01 212.45 0.00 0.00
April 537.15 228.23 260.20 3.83 256.37 0.00 0.00
May 735.06 134.37 305.21 25.92 279.29 0.00 0.00
June 1115.58 39.77 352.47 64.40 288.07 0.00 0.00
July 987.41 26.59 301.52 32.40 269.12 0.00 0.00
August 821.40 34.18 242.62 5.96 236.66 0.00 0.00
September 691.44 59.07 228.79 0.14 228.65 0.00 0.00
October 338.51 325.73 176.90 0.00 176.90 0.00 0.00
November 138.66 539.75 147.39 0.00 147.39 0.00 0.00
December 74.03 758.51 131.03 0.00 131.03 0.00 0.00
               
Annual Sum or Average 492.28 322.36 221.78 11.08 210.70 0.00 0.00
Minimum of Months 74.03 26.59 131.03 0.00 131.03 0.00 0.00
Maximum of Months 1115.58 758.51 352.47 64.40 288.07 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 616.60 469.96 427.15 283.81 143.33 0.00 0.00
February 444.07 479.00 366.37 207.46 158.92 0.00 0.00
March 580.71 414.45 414.26 196.85 217.41 0.00 0.00
April 1014.67 193.30 537.54 284.90 252.64 0.00 0.00
May 1108.26 123.44 535.32 274.48 260.84 0.00 0.00
June 1369.64 36.24 552.26 297.92 254.33 0.00 0.00
July 1213.68 26.78 474.70 228.03 246.68 0.00 0.00
August 1147.40 36.36 456.98 226.75 230.22 0.00 0.00
September 974.55 55.26 410.66 177.82 232.84 0.00 0.00
October 799.96 264.65 449.95 268.49 181.46 0.00 0.00
November 564.31 424.78 396.99 249.50 147.50 0.00 0.00
December 500.16 570.93 386.03 250.99 135.03 0.00 0.00
               
Annual Sum or Average 863.29 256.99 451.12 245.82 205.30 0.00 0.00
Minimum of Months 444.07 26.78 366.37 177.82 135.03 0.00 0.00
Maximum of Months 1369.64 570.93 552.26 297.92 260.84 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 1013.01 455.69 664.96 492.81 172.15 0.00 0.00
February 567.98 459.87 439.71 258.05 181.66 0.00 0.00
March 582.13 405.18 391.48 161.47 230.01 0.00 0.00
April 788.18 168.32 368.86 116.51 252.35 0.00 0.00
May 742.06 91.27 291.49 41.39 250.10 0.00 0.00
June 954.88 21.27 279.00 34.15 244.86 0.00 0.00
July 909.47 14.78 263.64 26.35 237.30 0.00 0.00
August 906.04 15.97 281.37 57.86 223.51 0.00 0.00
September 947.24 28.99 359.96 119.04 240.92 0.00 0.00
October 935.32 235.41 512.54 312.84 199.71 0.00 0.00
November 874.72 400.65 581.72 407.98 173.74 0.00 0.00
December 877.58 575.54 619.39 455.14 164.25 0.00 0.00
               
Annual Sum or Average 843.25 238.53 421.29 206.96 214.33 0.00 0.00
Minimum of Months 567.98 14.78 263.64 26.35 164.25 0.00 0.00
Maximum of Months 1013.01 575.54 664.96 492.81 252.35 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.352241E+10 0.981718E+09 0.223838E+10 0.178821E+10 0.450171E+09 0.00 0.00
February 0.180963E+10 0.858176E+09 0.126153E+10 0.845731E+09 0.415798E+09 0.00 0.00
March 0.182750E+10 0.845636E+09 0.115623E+10 0.585894E+09 0.570335E+09 0.00 0.00
April 0.203293E+10 0.386783E+09 0.982044E+09 0.404532E+09 0.577512E+09 0.00 0.00
May 0.164704E+10 0.239845E+09 0.678057E+09 0.117952E+09 0.560105E+09 0.00 0.00
June 0.184743E+10 61534314.25 0.555427E+09 42376069.35 0.513050E+09 0.00 0.00
July 0.191643E+10 39110474.19 0.581591E+09 55297824.35 0.526293E+09 0.00 0.00
August 0.211178E+10 44640341.68 0.719166E+09 0.202544E+09 0.516622E+09 0.00 0.00
September 0.235103E+10 78942972.48 0.988595E+09 0.417832E+09 0.570763E+09 0.00 0.00
October 0.291710E+10 0.531045E+09 0.163976E+10 0.113516E+10 0.504604E+09 0.00 0.00
November 0.292007E+10 0.836652E+09 0.186529E+10 0.143263E+10 0.432667E+09 0.00 0.00
December 0.313780E+10 0.121441E+10 0.208454E+10 0.165152E+10 0.433026E+09 0.00 0.00
               
Annual Sum or Average 0.280412E+11 0.611849E+10 0.147506E+11 0.867966E+10 0.607095E+10 0.00 0.00
Minimum of Months 0.164704E+10 39110474.19 0.555427E+09 42376069.35 0.415798E+09 0.00 0.00
Maximum of Months 0.352241E+10 0.121441E+10 0.223838E+10 0.178821E+10 0.577512E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.988341E+10 0.279739E+10 0.630312E+10 0.503547E+10 0.126765E+10 0.00 0.00
February 0.505342E+10 0.245689E+10 0.355238E+10 0.238152E+10 0.117086E+10 0.00 0.00
March 0.509749E+10 0.241573E+10 0.325586E+10 0.164984E+10 0.160603E+10 0.00 0.00
April 0.570217E+10 0.112199E+10 0.276537E+10 0.113914E+10 0.162624E+10 0.00 0.00
May 0.460423E+10 0.712889E+09 0.190936E+10 0.332145E+09 0.157722E+10 0.00 0.00
June 0.517735E+10 0.198703E+09 0.156404E+10 0.119328E+09 0.144472E+10 0.00 0.00
July 0.532439E+10 0.125999E+09 0.163772E+10 0.155715E+09 0.148201E+10 0.00 0.00
August 0.590056E+10 0.154334E+09 0.202512E+10 0.570351E+09 0.145477E+10 0.00 0.00
September 0.658395E+10 0.265749E+09 0.278382E+10 0.117659E+10 0.160723E+10 0.00 0.00
October 0.818677E+10 0.154173E+10 0.461746E+10 0.319653E+10 0.142093E+10 0.00 0.00
November 0.818880E+10 0.238928E+10 0.525254E+10 0.403418E+10 0.121836E+10 0.00 0.00
December 0.878974E+10 0.345050E+10 0.586993E+10 0.465056E+10 0.121937E+10 0.00 0.00
               
Annual Sum or Average 0.784923E+11 0.176312E+11 0.415367E+11 0.244414E+11 0.170954E+11 0.00 0.00
Minimum of Months 0.460423E+10 0.125999E+09 0.156404E+10 0.119328E+09 0.117086E+10 0.00 0.00
Maximum of Months 0.988341E+10 0.345050E+10 0.630312E+10 0.503547E+10 0.162624E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.131852E+11 0.363059E+10 0.818812E+10 0.654136E+10 0.164675E+10 0.00 0.00
February 0.671977E+10 0.325194E+10 0.461475E+10 0.309374E+10 0.152101E+10 0.00 0.00
March 0.679328E+10 0.320549E+10 0.422955E+10 0.214323E+10 0.208632E+10 0.00 0.00
April 0.765749E+10 0.147351E+10 0.359238E+10 0.147980E+10 0.211257E+10 0.00 0.00
May 0.619266E+10 0.946278E+09 0.248037E+10 0.431476E+09 0.204890E+10 0.00 0.00
June 0.698462E+10 0.259765E+09 0.203178E+10 0.155014E+09 0.187677E+10 0.00 0.00
July 0.718351E+10 0.164111E+09 0.212749E+10 0.202283E+09 0.192521E+10 0.00 0.00
August 0.796935E+10 0.191852E+09 0.263075E+10 0.740919E+09 0.188983E+10 0.00 0.00
September 0.887343E+10 0.326812E+09 0.361634E+10 0.152845E+10 0.208788E+10 0.00 0.00
October 0.109662E+11 0.199188E+10 0.599834E+10 0.415247E+10 0.184587E+10 0.00 0.00
November 0.109225E+11 0.311192E+10 0.682335E+10 0.524063E+10 0.158272E+10 0.00 0.00
December 0.116913E+11 0.452547E+10 0.762538E+10 0.604134E+10 0.158404E+10 0.00 0.00
               
Annual Sum or Average 0.105139E+12 0.230796E+11 0.539586E+11 0.317507E+11 0.222079E+11 0.00 0.00
Minimum of Months 0.619266E+10 0.164111E+09 0.203178E+10 0.155014E+09 0.152101E+10 0.00 0.00
Maximum of Months 0.131852E+11 0.452547E+10 0.818812E+10 0.654136E+10 0.211257E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.117362E+10 0.588035E+09 0.782721E+09 0.565485E+09 0.217236E+09 0.00 0.00
February 0.636016E+09 0.515791E+09 0.498285E+09 0.287991E+09 0.210294E+09 0.00 0.00
March 0.865782E+09 0.504403E+09 0.593196E+09 0.290214E+09 0.302982E+09 0.00 0.00
April 0.136960E+10 0.223810E+09 0.734505E+09 0.388376E+09 0.346129E+09 0.00 0.00
May 0.141846E+10 0.137611E+09 0.694431E+09 0.337345E+09 0.357087E+09 0.00 0.00
June 0.167964E+10 33669419.59 0.684686E+09 0.346412E+09 0.338274E+09 0.00 0.00
July 0.144759E+10 22075032.80 0.547106E+09 0.212292E+09 0.334813E+09 0.00 0.00
August 0.141790E+10 24463179.79 0.555835E+09 0.248047E+09 0.307788E+09 0.00 0.00
September 0.126399E+10 42075919.20 0.543814E+09 0.229081E+09 0.314733E+09 0.00 0.00
October 0.121125E+10 0.311966E+09 0.694021E+09 0.436513E+09 0.257508E+09 0.00 0.00
November 0.103270E+10 0.501109E+09 0.696397E+09 0.480919E+09 0.215478E+09 0.00 0.00
December 0.946263E+09 0.728673E+09 0.683759E+09 0.480526E+09 0.203233E+09 0.00 0.00
               
Annual Sum or Average 0.144628E+11 0.363368E+10 0.770875E+10 0.430320E+10 0.340555E+10 0.00 0.00
Minimum of Months 0.636016E+09 22075032.80 0.498285E+09 0.212292E+09 0.203233E+09 0.00 0.00
Maximum of Months 0.167964E+10 0.728673E+09 0.782721E+09 0.565485E+09 0.357087E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.573132E+09 0.608607E+09 0.393828E+09 0.211926E+09 0.181903E+09 0.00 0.00
February 0.339555E+09 0.529998E+09 0.304099E+09 0.120775E+09 0.183324E+09 0.00 0.00
March 0.616732E+09 0.505721E+09 0.445884E+09 0.174376E+09 0.271508E+09 0.00 0.00
April 0.116957E+10 0.217745E+09 0.636687E+09 0.309812E+09 0.326875E+09 0.00 0.00
May 0.136682E+10 0.128136E+09 0.677152E+09 0.323940E+09 0.353213E+09 0.00 0.00
June 0.171354E+10 30464481.44 0.705388E+09 0.361882E+09 0.343505E+09 0.00 0.00
July 0.144276E+10 20572904.22 0.547489E+09 0.213756E+09 0.333733E+09 0.00 0.00
August 0.131094E+10 23288998.81 0.506479E+09 0.210280E+09 0.296199E+09 0.00 0.00
September 0.105499E+10 40856279.88 0.433071E+09 0.146521E+09 0.286550E+09 0.00 0.00
October 0.782536E+09 0.316975E+09 0.437501E+09 0.212073E+09 0.225428E+09 0.00 0.00
November 0.543965E+09 0.518127E+09 0.382175E+09 0.197665E+09 0.184511E+09 0.00 0.00
December 0.406722E+09 0.760032E+09 0.321745E+09 0.153993E+09 0.167752E+09 0.00 0.00
               
Annual Sum or Average 0.113213E+11 0.370052E+10 0.579150E+10 0.263700E+10 0.315450E+10 0.00 0.00
Minimum of Months 0.339555E+09 20572904.22 0.304099E+09 0.120775E+09 0.167752E+09 0.00 0.00
Maximum of Months 0.171354E+10 0.760032E+09 0.705388E+09 0.361882E+09 0.353213E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.541980E+09 0.190207E+09 0.353983E+09 0.282791E+09 71191720.82 0.00 0.00
February 0.270759E+09 0.170938E+09 0.199502E+09 0.133746E+09 65755807.07 0.00 0.00
March 0.269315E+09 0.167827E+09 0.182850E+09 92654621.17 90194909.73 0.00 0.00
April 0.307926E+09 80570885.62 0.155304E+09 63973596.40 91330373.15 0.00 0.00
May 0.247232E+09 52497954.33 0.107231E+09 18653222.29 88577606.46 0.00 0.00
June 0.283978E+09 15541416.58 87837819.98 6701448.63 81136371.35 0.00 0.00
July 0.286629E+09 10447176.85 91975290.32 8744924.55 83230365.76 0.00 0.00
August 0.320182E+09 13918632.51 0.113732E+09 32030806.41 81700800.92 0.00 0.00
September 0.357745E+09 22140271.55 0.156339E+09 66076882.86 90262586.66 0.00 0.00
October 0.446236E+09 0.107533E+09 0.259316E+09 0.179516E+09 79800009.62 0.00 0.00
November 0.446253E+09 0.164958E+09 0.294982E+09 0.226559E+09 68423598.87 0.00 0.00
December 0.481325E+09 0.230505E+09 0.329655E+09 0.261175E+09 68480327.14 0.00 0.00
               
Annual Sum or Average 0.425956E+10 0.122708E+10 0.233271E+10 0.137262E+10 0.960084E+09 0.00 0.00
Minimum of Months 0.247232E+09 10447176.85 87837819.98 6701448.63 65755807.07 0.00 0.00
Maximum of Months 0.541980E+09 0.230505E+09 0.353983E+09 0.282791E+09 91330373.15 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 43821602.30 0.173583E+09 42944949.46 0.00 42944949.46 0.00 0.00
February 26062853.05 0.157007E+09 44199004.85 0.00 44199004.85 0.00 0.00
March 74421221.25 0.146590E+09 65045237.58 2573.27 65042664.31 0.00 0.00
April 0.161394E+09 56679407.48 77090857.89 1135053.46 75955804.43 0.00 0.00
May 0.229070E+09 31493736.85 93441433.49 7934259.35 85507174.14 0.00 0.00
June 0.341364E+09 6638073.99 0.104430E+09 19081199.32 85349110.47 0.00 0.00
July 0.315797E+09 4704943.93 92312481.83 9919050.97 82393430.86 0.00 0.00
August 0.262444E+09 5352069.58 74279179.59 1823766.12 72455413.47 0.00 0.00
September 0.211688E+09 9822701.93 67785290.05 41951.47 67743338.59 0.00 0.00
October 0.106262E+09 88582860.15 54159300.98 0.00 54159300.98 0.00 0.00
November 44140725.37 0.147944E+09 43668987.75 0.00 43668987.75 0.00 0.00
December 25782917.78 0.221063E+09 40114513.77 0.00 40114513.77 0.00 0.00
               
Annual Sum or Average 0.184225E+10 0.104946E+10 0.799472E+09 39937853.95 0.759534E+09 0.00 0.00
Minimum of Months 25782917.78 4704943.93 40114513.77 0.00 40114513.77 0.00 0.00
Maximum of Months 0.341364E+09 0.221063E+09 0.104430E+09 19081199.32 85507174.14 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.111889E+10 0.565881E+09 0.766505E+09 0.556878E+09 0.209627E+09 0.00 0.00
February 0.685666E+09 0.501855E+09 0.540277E+09 0.334558E+09 0.205719E+09 0.00 0.00
March 0.886693E+09 0.475703E+09 0.628463E+09 0.321558E+09 0.306905E+09 0.00 0.00
April 0.136670E+10 0.200249E+09 0.745596E+09 0.408534E+09 0.337062E+09 0.00 0.00
May 0.145770E+10 0.120295E+09 0.725583E+09 0.374306E+09 0.351277E+09 0.00 0.00
June 0.172208E+10 29221797.91 0.705417E+09 0.378400E+09 0.327016E+09 0.00 0.00
July 0.160143E+10 19627555.12 0.635569E+09 0.304666E+09 0.330904E+09 0.00 0.00
August 0.155326E+10 23375702.11 0.636696E+09 0.322574E+09 0.314123E+09 0.00 0.00
September 0.133388E+10 39536397.94 0.587611E+09 0.271747E+09 0.315864E+09 0.00 0.00
October 0.125636E+10 0.298645E+09 0.730860E+09 0.471799E+09 0.259061E+09 0.00 0.00
November 0.968815E+09 0.483784E+09 0.671635E+09 0.464986E+09 0.206650E+09 0.00 0.00
December 0.942439E+09 0.706382E+09 0.697993E+09 0.499406E+09 0.198587E+09 0.00 0.00
               
Annual Sum or Average 0.148939E+11 0.346456E+10 0.807221E+10 0.470941E+10 0.336279E+10 0.00 0.00
Minimum of Months 0.685666E+09 19627555.12 0.540277E+09 0.271747E+09 0.198587E+09 0.00 0.00
Maximum of Months 0.172208E+10 0.706382E+09 0.766505E+09 0.556878E+09 0.351277E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.483666E+09 0.550609E+09 0.377613E+09 0.203319E+09 0.174294E+09 0.00 0.00
February 0.368421E+09 0.495393E+09 0.346092E+09 0.167343E+09 0.178749E+09 0.00 0.00
March 0.628927E+09 0.469739E+09 0.481151E+09 0.205720E+09 0.275431E+09 0.00 0.00
April 0.116767E+10 0.197059E+09 0.647778E+09 0.329970E+09 0.317808E+09 0.00 0.00
May 0.141434E+10 0.119388E+09 0.708304E+09 0.360901E+09 0.347403E+09 0.00 0.00
June 0.175936E+10 29125838.01 0.726118E+09 0.393870E+09 0.332248E+09 0.00 0.00
July 0.159811E+10 19557774.43 0.635953E+09 0.306130E+09 0.329823E+09 0.00 0.00
August 0.144662E+10 22860165.27 0.587340E+09 0.284806E+09 0.302534E+09 0.00 0.00
September 0.112416E+10 38306463.00 0.476868E+09 0.189187E+09 0.287681E+09 0.00 0.00
October 0.812725E+09 0.291629E+09 0.474341E+09 0.247359E+09 0.226982E+09 0.00 0.00
November 0.453521E+09 0.472722E+09 0.357413E+09 0.181731E+09 0.175682E+09 0.00 0.00
December 0.359402E+09 0.692405E+09 0.335979E+09 0.172873E+09 0.163106E+09 0.00 0.00
               
Annual Sum or Average 0.116169E+11 0.339879E+10 0.615495E+10 0.304321E+10 0.311174E+10 0.00 0.00
Minimum of Months 0.359402E+09 19557774.43 0.335979E+09 0.167343E+09 0.163106E+09 0.00 0.00
Maximum of Months 0.175936E+10 0.692405E+09 0.726118E+09 0.393870E+09 0.347403E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.130414E+10 0.687740E+09 0.860015E+09 0.612730E+09 0.247286E+09 0.00 0.00
February 0.667159E+09 0.623872E+09 0.528015E+09 0.289790E+09 0.238224E+09 0.00 0.00
March 0.801348E+09 0.606869E+09 0.537094E+09 0.200762E+09 0.336332E+09 0.00 0.00
April 0.109532E+10 0.250285E+09 0.503505E+09 0.141072E+09 0.362433E+09 0.00 0.00
May 0.111176E+10 0.144682E+09 0.434765E+09 57604611.69 0.377160E+09 0.00 0.00
June 0.141559E+10 35863773.63 0.416551E+09 55856451.63 0.360695E+09 0.00 0.00
July 0.137615E+10 25145671.81 0.399265E+09 40435810.09 0.358829E+09 0.00 0.00
August 0.133406E+10 27812762.31 0.407338E+09 73352738.99 0.333986E+09 0.00 0.00
September 0.130622E+10 49694980.94 0.485590E+09 0.143261E+09 0.342329E+09 0.00 0.00
October 0.125651E+10 0.363965E+09 0.679193E+09 0.388962E+09 0.290232E+09 0.00 0.00
November 0.109907E+10 0.583726E+09 0.733746E+09 0.490890E+09 0.242857E+09 0.00 0.00
December 0.111346E+10 0.871925E+09 0.801172E+09 0.565893E+09 0.235279E+09 0.00 0.00
               
Annual Sum or Average 0.138808E+11 0.427158E+10 0.678625E+10 0.306061E+10 0.372564E+10 0.00 0.00
Minimum of Months 0.667159E+09 25145671.81 0.399265E+09 40435810.09 0.235279E+09 0.00 0.00
Maximum of Months 0.141559E+10 0.871925E+09 0.860015E+09 0.612730E+09 0.377160E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.116316E+10 0.585150E+09 0.782721E+09 0.565485E+09 0.217236E+09 0.00 0.00
February 0.628172E+09 0.511336E+09 0.498285E+09 0.287991E+09 0.210294E+09 0.00 0.00
March 0.852562E+09 0.503099E+09 0.593196E+09 0.290214E+09 0.302982E+09 0.00 0.00
April 0.135052E+10 0.222017E+09 0.734505E+09 0.388376E+09 0.346129E+09 0.00 0.00
May 0.140192E+10 0.135555E+09 0.694431E+09 0.337345E+09 0.357087E+09 0.00 0.00
June 0.166465E+10 32630374.47 0.684686E+09 0.346412E+09 0.338274E+09 0.00 0.00
July 0.143251E+10 21832798.90 0.547106E+09 0.212292E+09 0.334813E+09 0.00 0.00
August 0.140285E+10 24406114.45 0.555835E+09 0.248047E+09 0.307788E+09 0.00 0.00
September 0.124930E+10 41456405.08 0.543814E+09 0.229081E+09 0.314733E+09 0.00 0.00
October 0.119732E+10 0.309284E+09 0.694021E+09 0.436513E+09 0.257508E+09 0.00 0.00
November 0.102137E+10 0.499259E+09 0.696397E+09 0.480919E+09 0.215478E+09 0.00 0.00
December 0.940901E+09 0.722749E+09 0.683759E+09 0.480526E+09 0.203233E+09 0.00 0.00
               
Annual Sum or Average 0.143053E+11 0.360878E+10 0.770875E+10 0.430320E+10 0.340555E+10 0.00 0.00
Minimum of Months 0.628172E+09 21832798.90 0.498285E+09 0.212292E+09 0.203233E+09 0.00 0.00
Maximum of Months 0.166465E+10 0.722749E+09 0.782721E+09 0.565485E+09 0.357087E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.567910E+09 0.601502E+09 0.393828E+09 0.211926E+09 0.181903E+09 0.00 0.00
February 0.334706E+09 0.522923E+09 0.304099E+09 0.120775E+09 0.183324E+09 0.00 0.00
March 0.606448E+09 0.503130E+09 0.445884E+09 0.174376E+09 0.271508E+09 0.00 0.00
April 0.115229E+10 0.216118E+09 0.636687E+09 0.309812E+09 0.326875E+09 0.00 0.00
May 0.135064E+10 0.126527E+09 0.677152E+09 0.323940E+09 0.353213E+09 0.00 0.00
June 0.169790E+10 29763223.23 0.705388E+09 0.361882E+09 0.343505E+09 0.00 0.00
July 0.142748E+10 20469035.18 0.547489E+09 0.213756E+09 0.333733E+09 0.00 0.00
August 0.129652E+10 23372950.98 0.506479E+09 0.210280E+09 0.296199E+09 0.00 0.00
September 0.104222E+10 40415154.56 0.433071E+09 0.146521E+09 0.286550E+09 0.00 0.00
October 0.772568E+09 0.313098E+09 0.437501E+09 0.212073E+09 0.225428E+09 0.00 0.00
November 0.537021E+09 0.513377E+09 0.382175E+09 0.197665E+09 0.184511E+09 0.00 0.00
December 0.405072E+09 0.749222E+09 0.321745E+09 0.153993E+09 0.167752E+09 0.00 0.00
               
Annual Sum or Average 0.111908E+11 0.365992E+10 0.579150E+10 0.263700E+10 0.315450E+10 0.00 0.00
Minimum of Months 0.334706E+09 20469035.18 0.304099E+09 0.120775E+09 0.167752E+09 0.00 0.00
Maximum of Months 0.169790E+10 0.749222E+09 0.705388E+09 0.361882E+09 0.353213E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.996987E+09 0.303131E+09 0.649066E+09 0.518528E+09 0.130538E+09 0.00 0.00
February 0.502344E+09 0.267772E+09 0.365808E+09 0.245238E+09 0.120570E+09 0.00 0.00
March 0.504198E+09 0.262224E+09 0.335275E+09 0.169892E+09 0.165382E+09 0.00 0.00
April 0.579292E+09 0.110748E+09 0.284767E+09 0.117303E+09 0.167464E+09 0.00 0.00
May 0.479003E+09 65270934.12 0.196619E+09 34202726.45 0.162417E+09 0.00 0.00
June 0.558664E+09 14096782.23 0.161060E+09 12287840.18 0.148772E+09 0.00 0.00
July 0.569314E+09 9977035.33 0.168647E+09 16034777.14 0.152612E+09 0.00 0.00
August 0.623825E+09 11317132.72 0.208539E+09 58731992.40 0.149807E+09 0.00 0.00
September 0.682573E+09 19758031.52 0.286666E+09 0.121159E+09 0.165506E+09 0.00 0.00
October 0.828316E+09 0.157697E+09 0.475485E+09 0.329163E+09 0.146322E+09 0.00 0.00
November 0.823020E+09 0.258090E+09 0.540882E+09 0.415420E+09 0.125462E+09 0.00 0.00
December 0.887473E+09 0.376859E+09 0.604458E+09 0.478892E+09 0.125566E+09 0.00 0.00
               
Annual Sum or Average 0.803501E+10 0.185694E+10 0.427727E+10 0.251685E+10 0.176042E+10 0.00 0.00
Minimum of Months 0.479003E+09 9977035.33 0.161060E+09 12287840.18 0.120570E+09 0.00 0.00
Maximum of Months 0.996987E+09 0.376859E+09 0.649066E+09 0.518528E+09 0.167464E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.368983E+09 0.158112E+10 0.375704E+09 0.00 0.375704E+09 0.00 0.00
February 0.209229E+09 0.143648E+10 0.386675E+09 0.00 0.386675E+09 0.00 0.00
March 0.634830E+09 0.135852E+10 0.569049E+09 22512.27 0.569026E+09 0.00 0.00
April 0.142369E+10 0.565592E+09 0.674430E+09 9930025.34 0.664500E+09 0.00 0.00
May 0.201118E+10 0.339741E+09 0.817473E+09 69412938.91 0.748060E+09 0.00 0.00
June 0.293723E+10 94941368.79 0.913609E+09 0.166932E+09 0.746677E+09 0.00 0.00
July 0.269484E+10 65366436.79 0.807597E+09 86776906.14 0.720820E+09 0.00 0.00
August 0.224588E+10 81751330.29 0.649832E+09 15955234.21 0.633877E+09 0.00 0.00
September 0.183325E+10 0.138136E+09 0.593020E+09 367012.78 0.592653E+09 0.00 0.00
October 0.931358E+09 0.840929E+09 0.473813E+09 0.00 0.473813E+09 0.00 0.00
November 0.373230E+09 0.136065E+10 0.382039E+09 0.00 0.382039E+09 0.00 0.00
December 0.208456E+09 0.199041E+10 0.350942E+09 0.00 0.350942E+09 0.00 0.00
               
Annual Sum or Average 0.158721E+11 0.985364E+10 0.699418E+10 0.349397E+09 0.664479E+10 0.00 0.00
Minimum of Months 0.208456E+09 65366436.79 0.350942E+09 0.00 0.350942E+09 0.00 0.00
Maximum of Months 0.293723E+10 0.199041E+10 0.913609E+09 0.166932E+09 0.748060E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.355459E+09 0.162003E+10 0.375704E+09 0.00 0.375704E+09 0.00 0.00
February 0.199516E+09 0.147627E+10 0.386675E+09 0.00 0.386675E+09 0.00 0.00
March 0.615559E+09 0.139624E+10 0.569049E+09 22512.27 0.569026E+09 0.00 0.00
April 0.139229E+10 0.591582E+09 0.674430E+09 9930025.34 0.664500E+09 0.00 0.00
May 0.196880E+10 0.359898E+09 0.817473E+09 69412938.91 0.748060E+09 0.00 0.00
June 0.289159E+10 0.103090E+09 0.913609E+09 0.166932E+09 0.746677E+09 0.00 0.00
July 0.264469E+10 71220136.87 0.807597E+09 86776906.14 0.720820E+09 0.00 0.00
August 0.220004E+10 91553498.84 0.649832E+09 15955234.21 0.633877E+09 0.00 0.00
September 0.179220E+10 0.153118E+09 0.593020E+09 367012.78 0.592653E+09 0.00 0.00
October 0.906671E+09 0.872434E+09 0.473813E+09 0.00 0.473813E+09 0.00 0.00
November 0.359403E+09 0.139902E+10 0.382039E+09 0.00 0.382039E+09 0.00 0.00
December 0.198293E+09 0.203159E+10 0.350942E+09 0.00 0.350942E+09 0.00 0.00
               
Annual Sum or Average 0.155245E+11 0.101661E+11 0.699418E+10 0.349397E+09 0.664479E+10 0.00 0.00
Minimum of Months 0.198293E+09 71220136.87 0.350942E+09 0.00 0.350942E+09 0.00 0.00
Maximum of Months 0.289159E+10 0.203159E+10 0.913609E+09 0.166932E+09 0.748060E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.165151E+10 0.125873E+10 0.114407E+10 0.760168E+09 0.383905E+09 0.00 0.00
February 0.107429E+10 0.115879E+10 0.886328E+09 0.501877E+09 0.384451E+09 0.00 0.00
March 0.155537E+10 0.111007E+10 0.110956E+10 0.527249E+09 0.582308E+09 0.00 0.00
April 0.263003E+10 0.501023E+09 0.139330E+10 0.738458E+09 0.654838E+09 0.00 0.00
May 0.296835E+10 0.330619E+09 0.143380E+10 0.735158E+09 0.698645E+09 0.00 0.00
June 0.355011E+10 93924541.28 0.143145E+10 0.772218E+09 0.659232E+09 0.00 0.00
July 0.325072E+10 71738769.85 0.127145E+10 0.610754E+09 0.660695E+09 0.00 0.00
August 0.307320E+10 97394921.97 0.122397E+10 0.607340E+09 0.616627E+09 0.00 0.00
September 0.252603E+10 0.143226E+09 0.106442E+10 0.460908E+09 0.603516E+09 0.00 0.00
October 0.214263E+10 0.708840E+09 0.120514E+10 0.719123E+09 0.486021E+09 0.00 0.00
November 0.146269E+10 0.110103E+10 0.102901E+10 0.646691E+09 0.382315E+09 0.00 0.00
December 0.133963E+10 0.152917E+10 0.103393E+10 0.672254E+09 0.361677E+09 0.00 0.00
               
Annual Sum or Average 0.272246E+11 0.810456E+10 0.142264E+11 0.775220E+10 0.647423E+10 0.00 0.00
Minimum of Months 0.107429E+10 71738769.85 0.886328E+09 0.460908E+09 0.361677E+09 0.00 0.00
Maximum of Months 0.355011E+10 0.152917E+10 0.143380E+10 0.772218E+09 0.698645E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.271325E+10 0.122053E+10 0.178102E+10 0.131994E+10 0.461083E+09 0.00 0.00
February 0.137405E+10 0.111252E+10 0.106374E+10 0.624266E+09 0.439472E+09 0.00 0.00
March 0.155919E+10 0.108523E+10 0.104853E+10 0.432478E+09 0.616053E+09 0.00 0.00
April 0.204296E+10 0.436275E+09 0.956085E+09 0.302004E+09 0.654081E+09 0.00 0.00
May 0.198754E+10 0.244467E+09 0.780737E+09 0.110860E+09 0.669877E+09 0.00 0.00
June 0.247506E+10 55129382.26 0.723175E+09 88503980.79 0.634671E+09 0.00 0.00
July 0.243591E+10 39583169.14 0.706145E+09 70564670.40 0.635580E+09 0.00 0.00
August 0.242674E+10 42765409.57 0.753612E+09 0.154975E+09 0.598637E+09 0.00 0.00
September 0.245525E+10 75153368.64 0.933011E+09 0.308543E+09 0.624468E+09 0.00 0.00
October 0.250516E+10 0.630513E+09 0.137280E+10 0.837901E+09 0.534895E+09 0.00 0.00
November 0.226726E+10 0.103849E+10 0.150781E+10 0.105747E+10 0.450334E+09 0.00 0.00
December 0.235051E+10 0.154153E+10 0.165898E+10 0.121905E+10 0.439939E+09 0.00 0.00
               
Annual Sum or Average 0.265929E+11 0.752219E+10 0.132856E+11 0.652656E+10 0.675909E+10 0.00 0.00
Minimum of Months 0.137405E+10 39583169.14 0.706145E+09 70564670.40 0.439472E+09 0.00 0.00
Maximum of Months 0.271325E+10 0.154153E+10 0.178102E+10 0.131994E+10 0.669877E+09 0.00 0.00



Table of Contents

Report: AverageOutdoorConditionsMonthly

For: Environment

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] SITE OUTDOOR AIR WETBULB TEMPERATURE [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] SITE WIND SPEED [m/s] SITE SKY TEMPERATURE [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] SITE RAIN STATUS []
January 14.83 7.47 -0.8 2.99 -0.8 34.08 283.26 0.00
February 12.72 9.35 6.24 2.64 2.53 52.02 191.85 0.02
March 15.42 8.67 1.96 3.53 3.02 74.19 207.67 0.01
April 23.31 10.14 -4.1 3.42 6.81 72.47 350.22 0.00
May 26.31 11.07 -4.9 3.62 8.60 75.22 359.64 0.00
June 31.20 14.28 0.18 3.69 15.53 67.31 396.02 0.00
July 30.42 17.99 9.86 3.72 19.28 82.46 278.62 0.02
August 29.82 18.15 11.14 3.33 18.26 71.82 270.19 0.02
September 27.75 17.59 11.45 3.72 17.29 82.54 200.28 0.01
October 20.87 10.99 1.63 3.42 6.03 49.01 269.00 0.00
November 15.43 8.80 1.49 3.02 1.83 40.49 251.35 0.01
December 11.86 4.25 -5.9 2.21 -4.3 34.74 244.35 0.00
                 
Annual Sum or Average 21.70 11.57 2.33 3.28 7.86 61.39 275.62 0.01
Minimum of Months 11.86 4.25 -5.9 2.21 -4.3 34.08 191.85 0.00
Maximum of Months 31.20 18.15 11.45 3.72 19.28 82.54 396.02 0.02



Table of Contents

Report: OutdoorConditionsMaximumDryBulbMonthly

For: Environment

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 29.00 31-JAN-15:00 10.73 -14.0 2.10 7.75 109.00 697.00
February 22.00 18-FEB-14:09 14.42 9.67 5.20 14.10 264.00 225.33
March 28.80 16-MAR-15:20 13.79 1.47 3.77 14.35 156.17 666.17
April 35.00 14-APR-14:00 14.57 -4.0 1.50 19.70 150.00 819.50
May 37.00 15-MAY-16:00 15.57 -2.0 4.60 20.75 127.50 679.00
June 42.00 16-JUN-15:00 16.74 -5.0 5.70 25.49 135.00 753.50
July 40.00 12-JUL-13:00 19.40 7.00 2.10 27.95 147.00 3.00
August 41.00 25-AUG-14:09 17.27 -0.7 3.43 25.74 162.33 768.67
September 38.30 08-SEP-14:00 19.81 10.00 3.00 25.82 142.00 699.00
October 37.00 01-OCT-12:00 19.01 9.00 4.10 27.14 262.50 136.00
November 29.00 01-NOV-14:00 16.20 8.00 2.60 16.49 73.50 907.50
December 26.00 21-DEC-14:00 10.90 -5.0 2.60 7.35 68.50 756.50
                 
Annual Sum or Average                
Minimum of Months 22.00   10.73 -14.0 1.50 7.35 68.50 3.00
Maximum of Months 42.00   19.81 10.00 5.70 27.95 264.00 907.50



Table of Contents

Report: OutdoorConditionsMinimumDryBulbMonthly

For: Environment

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 0.50 01-JAN-07:00 -1.2 -3.3 3.30 -16.2 17.50 352.00
February 5.00 01-FEB-04:00 3.59 2.00 3.10 -10.7 0.00 0.00
March 0.50 26-MAR-03:00 -2.4 -6.7 2.50 -17.0 0.00 0.00
April 8.00 21-APR-03:00 0.42 -14.0 1.00 -11.7 0.00 0.00
May 12.00 01-MAY-03:00 3.97 -7.0 2.60 -6.2 0.00 0.00
June 18.00 21-JUN-04:00 8.24 -2.0 1.50 3.48 0.00 0.00
July 18.00 01-JUL-05:00 6.53 -9.0 3.10 -1.2 16.00 325.00
August 17.00 05-AUG-17:00 15.02 14.00 5.70 11.46 29.00 0.00
September 16.60 22-SEP-05:00 13.83 12.20 3.00 4.92 0.00 0.00
October 5.00 25-OCT-05:00 0.48 -6.0 3.10 -12.7 0.00 0.00
November 0.00 23-NOV-05:00 -2.5 -6.0 2.10 -17.3 0.00 0.00
December -1.1 07-DEC-04:00 -5.6 -16.0 3.10 -20.8 0.00 0.00
                 
Annual Sum or Average                
Minimum of Months -1.1   -5.6 -16.0 1.00 -20.8 0.00 0.00
Maximum of Months 18.00   15.02 14.00 5.70 11.46 29.00 352.00



Table of Contents

Report: OutdoorConditionsMaximumWetBulbMonthly

For: Environment

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

SITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 16.66 08-JAN-15:00 18.00 16.00 4.60 11.46 102.00 332.00
February 14.73 18-FEB-17:00 16.00 14.00 6.20 10.50 0.00 0.00
March 15.18 17-MAR-10:00 25.50 8.30 2.50 18.46 167.50 459.00
April 15.71 11-APR-14:00 33.00 3.00 2.10 15.94 178.50 758.00
May 15.57 15-MAY-16:00 37.00 -2.0 4.60 20.75 127.50 679.00
June 23.18 17-JUN-15:00 41.00 16.00 3.60 31.13 257.00 9.00
July 23.11 13-JUL-17:00 26.00 22.00 4.60 22.13 79.00 56.50
August 22.19 16-AUG-10:00 35.00 17.00 2.10 24.33 140.50 837.00
September 22.23 01-SEP-11:00 34.40 17.20 4.60 23.82 193.50 725.50
October 21.53 01-OCT-17:00 32.00 17.00 2.10 25.33 30.50 1.50
November 18.59 12-NOV-14:00 20.00 18.00 3.10 15.39 115.00 0.00
December 12.06 12-DEC-12:00 20.00 6.00 1.50 12.60 182.50 6.00
                 
Annual Sum or Average                
Minimum of Months 12.06   16.00 -2.0 1.50 10.50 0.00 0.00
Maximum of Months 23.18   41.00 22.00 6.20 31.13 257.00 837.00



Table of Contents

Report: OutdoorConditionsMaximumDewPointMonthly

For: Environment

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

SITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 16.00 08-JAN-15:00 18.00 16.66 4.60 11.46 102.00 332.00
February 14.00 18-FEB-17:00 16.00 14.73 6.20 10.50 0.00 0.00
March 13.30 06-MAR-10:00 14.40 13.70 6.10 10.69 254.50 82.00
April 8.00 15-APR-20:00 23.00 14.00 6.20 7.75 0.00 0.00
May 9.00 26-MAY-02:00 21.00 13.75 3.60 16.30 0.00 0.00
June 16.00 17-JUN-15:00 41.00 23.18 3.60 31.13 257.00 9.00
July 22.00 13-JUL-17:00 26.00 23.11 4.60 22.13 79.00 56.50
August 20.00 09-AUG-17:00 25.00 21.44 5.10 19.17 35.00 0.00
September 20.50 02-SEP-22:10 22.62 21.05 3.18 20.17 0.00 0.00
October 19.00 03-OCT-02:00 23.00 20.15 2.10 10.30 0.00 0.00
November 18.00 12-NOV-14:00 20.00 18.59 3.10 15.39 115.00 0.00
December 10.00 12-DEC-23:00 12.00 10.87 1.50 7.55 0.00 0.00
                 
Annual Sum or Average                
Minimum of Months 8.00   12.00 10.87 1.50 7.55 0.00 0.00
Maximum of Months 22.00   41.00 23.18 6.20 31.13 257.00 332.00



Table of Contents

Report: OutdoorGroundConditionsMonthly

For: Environment

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

SITE GROUND TEMPERATURE [C] SITE SURFACE GROUND TEMPERATURE [C] SITE DEEP GROUND TEMPERATURE [C] SITE MAINS WATER TEMPERATURE [C] SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] SITE SNOW ON GROUND STATUS []
January 18.00 13.00 16.00 18.65 31.23 0.00
February 18.00 13.00 16.00 19.06 29.93 0.00
March 18.00 13.00 16.00 20.99 39.76 0.00
April 18.00 13.00 16.00 24.03 60.89 0.00
May 18.00 13.00 16.00 27.32 65.75 0.00
June 18.00 13.00 16.00 29.99 69.24 0.00
July 18.00 13.00 16.00 31.31 56.42 0.00
August 18.00 13.00 16.00 30.91 52.05 0.00
September 18.00 13.00 16.00 28.91 42.71 0.00
October 18.00 13.00 16.00 25.85 39.20 0.00
November 18.00 13.00 16.00 22.56 30.64 0.00
December 18.00 13.00 16.00 19.93 27.41 0.00
             
Annual Sum or Average 18.00 13.00 16.00 24.99 45.50 0.00
Minimum of Months 18.00 13.00 16.00 18.65 27.41 0.00
Maximum of Months 18.00 13.00 16.00 31.31 69.24 0.00



Table of Contents

Report: WaterHeaterReportMonthly

For: SWH BOOSTER E WATER HEATER

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] WATER HEATER BURNER HEATING ENERGY [] WATER HEATER GAS CONSUMPTION [] WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] WATER HEATER LOSS DEMAND ENERGY [] WATER HEATER HEAT LOSS ENERGY [J] WATER HEATER TANK TEMPERATURE [C] WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] WATER HEATER SOURCE ENERGY []
January 0.770750E+10 -0.754278E+10 0.00 0.00 744.00 0.00 -164717001.5 81.21 0.00 0.00
February 0.696492E+10 -0.681597E+10 0.00 0.00 672.00 0.00 -148958620.3 81.21 0.00 0.00
March 0.770615E+10 -0.754146E+10 0.00 0.00 744.00 0.00 -164694234.6 81.21 0.00 0.00
April 0.746736E+10 -0.730860E+10 0.00 0.00 720.00 0.00 -158764684.7 81.21 0.00 0.00
May 0.770668E+10 -0.754280E+10 0.00 0.00 744.00 0.00 -163879763.4 81.21 0.00 0.00
June 0.745888E+10 -0.730053E+10 0.00 0.00 720.00 0.00 -158351874.9 81.21 0.00 0.00
July 0.771456E+10 -0.755086E+10 0.00 0.00 744.00 0.00 -163702968.3 81.21 0.00 0.00
August 0.770655E+10 -0.754281E+10 0.00 0.00 744.00 0.00 -163740108.0 81.21 0.00 0.00
September 0.746854E+10 -0.730994E+10 0.00 0.00 720.00 0.00 -158596746.6 81.21 0.00 0.00
October 0.770573E+10 -0.754143E+10 0.00 0.00 744.00 0.00 -164299446.7 81.21 0.00 0.00
November 0.745181E+10 -0.729243E+10 0.00 0.00 720.00 0.00 -159373178.9 81.21 0.00 0.00
December 0.771583E+10 -0.755085E+10 0.00 0.00 744.00 0.00 -164981406.8 81.21 0.00 0.00
                     
Annual Sum or Average 0.907745E+11 -0.888405E+11 0.00 0.00 8760.00 0.00 -0.193406E+10 81.21 0.00 0.00
Minimum of Months 0.696492E+10 -0.755086E+10 0.00 0.00 672.00 0.00 -164981406.8 81.21 0.00 0.00
Maximum of Months 0.771583E+10 -0.681597E+10 0.00 0.00 744.00 0.00 -148958620.3 81.21 0.00 0.00



Table of Contents

Report: WaterHeaterReportMonthly

For: SWH LAUNDRY G WATER HEATER

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] WATER HEATER BURNER HEATING ENERGY [] WATER HEATER GAS CONSUMPTION [] WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] WATER HEATER LOSS DEMAND ENERGY [] WATER HEATER HEAT LOSS ENERGY [J] WATER HEATER TANK TEMPERATURE [C] WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] WATER HEATER SOURCE ENERGY []
January 0.107786E+12 -0.105973E+12 0.00 0.00 744.00 0.00 -0.181335E+10 81.25 0.00 0.00
February 0.967233E+11 -0.950839E+11 0.00 0.00 672.00 0.00 -0.163936E+10 81.25 0.00 0.00
March 0.103813E+12 -0.101997E+12 0.00 0.00 744.00 0.00 -0.181607E+10 81.26 0.00 0.00
April 0.954867E+11 -0.937295E+11 0.00 0.00 720.00 0.00 -0.175719E+10 81.24 0.00 0.00
May 0.930860E+11 -0.912690E+11 0.00 0.00 744.00 0.00 -0.181693E+10 81.25 0.00 0.00
June 0.857048E+11 -0.839468E+11 0.00 0.00 720.00 0.00 -0.175805E+10 81.25 0.00 0.00
July 0.863273E+11 -0.845146E+11 0.00 0.00 744.00 0.00 -0.181271E+10 81.23 0.00 0.00
August 0.870019E+11 -0.851922E+11 0.00 0.00 744.00 0.00 -0.180964E+10 81.25 0.00 0.00
September 0.874645E+11 -0.857213E+11 0.00 0.00 720.00 0.00 -0.174320E+10 81.24 0.00 0.00
October 0.955612E+11 -0.937622E+11 0.00 0.00 744.00 0.00 -0.179905E+10 81.25 0.00 0.00
November 0.978734E+11 -0.961334E+11 0.00 0.00 720.00 0.00 -0.173997E+10 81.25 0.00 0.00
December 0.105604E+12 -0.103801E+12 0.00 0.00 744.00 0.00 -0.180258E+10 81.25 0.00 0.00
                     
Annual Sum or Average 0.114243E+13 -0.112112E+13 0.00 0.00 8760.00 0.00 -0.213081E+11 81.25 0.00 0.00
Minimum of Months 0.857048E+11 -0.105973E+12 0.00 0.00 672.00 0.00 -0.181693E+10 81.23 0.00 0.00
Maximum of Months 0.107786E+12 -0.839468E+11 0.00 0.00 744.00 0.00 -0.163936E+10 81.26 0.00 0.00



Table of Contents

Report: WaterHeaterReportMonthly

For: SWHSYS1 WATER HEATER

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] WATER HEATER BURNER HEATING ENERGY [] WATER HEATER GAS CONSUMPTION [] WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] WATER HEATER LOSS DEMAND ENERGY [] WATER HEATER HEAT LOSS ENERGY [J] WATER HEATER TANK TEMPERATURE [C] WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] WATER HEATER SOURCE ENERGY []
January 0.605069E+11 -0.589238E+11 0.00 0.00 744.00 0.00 -0.158306E+10 58.98 0.00 0.00
February 0.541195E+11 -0.526875E+11 0.00 0.00 672.00 0.00 -0.143200E+10 58.98 0.00 0.00
March 0.571324E+11 -0.555458E+11 0.00 0.00 744.00 0.00 -0.158664E+10 58.98 0.00 0.00
April 0.509646E+11 -0.494291E+11 0.00 0.00 720.00 0.00 -0.153555E+10 58.98 0.00 0.00
May 0.478521E+11 -0.462640E+11 0.00 0.00 744.00 0.00 -0.158812E+10 58.98 0.00 0.00
June 0.425421E+11 -0.410056E+11 0.00 0.00 720.00 0.00 -0.153653E+10 58.98 0.00 0.00
July 0.419879E+11 -0.404052E+11 0.00 0.00 744.00 0.00 -0.158272E+10 58.97 0.00 0.00
August 0.426112E+11 -0.410333E+11 0.00 0.00 744.00 0.00 -0.157794E+10 58.97 0.00 0.00
September 0.440349E+11 -0.425190E+11 0.00 0.00 720.00 0.00 -0.151597E+10 58.98 0.00 0.00
October 0.499524E+11 -0.483890E+11 0.00 0.00 744.00 0.00 -0.156343E+10 58.98 0.00 0.00
November 0.529947E+11 -0.514833E+11 0.00 0.00 720.00 0.00 -0.151141E+10 58.98 0.00 0.00
December 0.586163E+11 -0.570482E+11 0.00 0.00 744.00 0.00 -0.156817E+10 58.98 0.00 0.00
                     
Annual Sum or Average 0.603315E+12 -0.584734E+12 0.00 0.00 8760.00 0.00 -0.185815E+11 58.98 0.00 0.00
Minimum of Months 0.419879E+11 -0.589238E+11 0.00 0.00 672.00 0.00 -0.158812E+10 58.97 0.00 0.00
Maximum of Months 0.605069E+11 -0.404052E+11 0.00 0.00 744.00 0.00 -0.143200E+10 58.98 0.00 0.00



Table of Contents

Report: DaylightingReportMonthly

For: Environment

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER [] DAYLIGHTING LIGHTING POWER MULTIPLIER [] DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME []
January 309.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 241.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 344.33 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 380.33 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 403.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 418.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 399.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 361.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 350.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 348.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 288.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 290.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average 4135.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 241.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 418.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: VAV WITH REHEAT HEATING COIL

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 9984007.16 10711.60 23-FEB-19:40 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:03 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 25629985.92 13326.26 22-NOV-18:03 0.00 0.00 0.00 0.00 0.00
December 18740838.95 16619.76 04-DEC-18:13 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 54354832.03     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 25629985.92 16619.76   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: BASEMENT VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.440800E+10 8665.71 09-JAN-11:40 0.00 0.00 0.00 0.00 0.00
February 0.873344E+10 9169.27 18-FEB-11:40 0.00 0.00 0.00 0.00 0.00
March 0.136187E+11 9222.40 18-MAR-10:45 0.00 0.00 0.00 0.00 0.00
April 0.119248E+11 9343.98 30-APR-10:50 0.00 0.00 0.00 0.00 0.00
May 0.147502E+11 9359.05 20-MAY-10:50 0.00 0.00 0.00 0.00 0.00
June 0.131278E+11 9433.16 28-JUN-17:09 0.00 0.00 0.00 0.00 0.00
July 0.598234E+10 9408.21 22-JUL-10:40 0.00 0.00 0.00 0.00 0.00
August 0.328882E+10 9358.42 01-AUG-10:50 0.00 0.00 0.00 0.00 0.00
September 0.170842E+09 6682.94 01-SEP-10:50 0.00 0.00 0.00 0.00 0.00
October 47369573.68 4780.68 02-OCT-10:40 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 14244704.60 3623.20 26-DEC-11:40 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.760666E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.147502E+11 9433.16   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: RETAIL_1_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.235207E+10 2746.37 01-JAN-06:00 0.00 0.00 0.00 0.00 0.00
February 0.331793E+10 2589.07 13-FEB-07:10 0.00 0.00 0.00 0.00 0.00
March 0.325682E+10 2916.00 27-MAR-06:10 0.00 0.00 0.00 0.00 0.00
April 0.134944E+10 2071.08 21-APR-06:10 0.00 0.00 0.00 0.00 0.00
May 0.116284E+10 1643.86 14-MAY-05:00 0.00 0.00 0.00 0.00 0.00
June 0.388090E+09 1228.25 13-JUN-07:35 0.00 0.00 0.00 0.00 0.00
July 0.466053E+09 1267.92 29-JUL-06:10 0.00 0.00 0.00 0.00 0.00
August 0.511381E+09 1465.92 06-AUG-04:50 0.00 0.00 0.00 0.00 0.00
September 0.576695E+09 1518.74 03-SEP-10:40 0.00 0.00 0.00 0.00 0.00
October 0.155107E+10 2421.12 25-OCT-06:30 0.00 0.00 0.00 0.00 0.00
November 0.235834E+10 2650.87 23-NOV-07:00 0.00 0.00 0.00 0.00 0.00
December 0.322038E+10 2915.63 16-DEC-07:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.205111E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.388090E+09 1228.25   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.331793E+10 2916.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: RETAIL_2_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.105778E+10 1189.91 02-JAN-11:40 0.00 0.00 0.00 0.00 0.00
February 0.131189E+10 1334.87 13-FEB-11:40 0.00 0.00 0.00 0.00 0.00
March 0.122595E+10 1428.76 27-MAR-10:40 0.00 0.00 0.00 0.00 0.00
April 0.521033E+09 1173.48 21-APR-10:50 0.00 0.00 0.00 0.00 0.00
May 0.447534E+09 1090.38 01-MAY-10:35 0.00 0.00 0.00 0.00 0.00
June 0.257160E+09 985.63 19-JUN-10:50 0.00 0.00 0.00 0.00 0.00
July 0.334141E+09 1080.33 29-JUL-10:50 0.00 0.00 0.00 0.00 0.00
August 0.322521E+09 1095.98 07-AUG-10:35 0.00 0.00 0.00 0.00 0.00
September 0.324673E+09 1063.25 22-SEP-10:40 0.00 0.00 0.00 0.00 0.00
October 0.666061E+09 1242.71 23-OCT-10:40 0.00 0.00 0.00 0.00 0.00
November 0.962013E+09 1141.61 24-NOV-11:40 0.00 0.00 0.00 0.00 0.00
December 0.137557E+10 1235.26 19-DEC-11:40 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.880633E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.257160E+09 985.63   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.137557E+10 1428.76   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: MECH_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.289930E+10 1965.88 02-JAN-05:00 0.00 0.00 0.00 0.00 0.00
February 0.288127E+10 1882.89 13-FEB-11:40 0.00 0.00 0.00 0.00 0.00
March 0.271250E+10 2071.45 27-MAR-10:40 0.00 0.00 0.00 0.00 0.00
April 0.129071E+10 1620.17 01-APR-10:45 0.00 0.00 0.00 0.00 0.00
May 0.748602E+09 1265.82 01-MAY-10:35 0.00 0.00 0.00 0.00 0.00
June 0.115378E+09 865.23 01-JUN-10:50 0.00 0.00 0.00 0.00 0.00
July 0.189230E+09 1164.22 29-JUL-10:50 0.00 0.00 0.00 0.00 0.00
August 0.337076E+09 1177.97 06-AUG-10:50 0.00 0.00 0.00 0.00 0.00
September 0.485053E+09 1155.84 22-SEP-10:35 0.00 0.00 0.00 0.00 0.00
October 0.167380E+10 1750.94 26-OCT-10:40 0.00 0.00 0.00 0.00 0.00
November 0.255637E+10 1903.77 24-NOV-05:00 0.00 0.00 0.00 0.00 0.00
December 0.340907E+10 2035.18 07-DEC-11:40 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.192984E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.115378E+09 865.23   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.340907E+10 2071.45   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: STORAGE_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.180647E+10 1108.38 01-JAN-06:30 0.00 0.00 0.00 0.00 0.00
February 0.179736E+10 1046.40 13-FEB-11:40 0.00 0.00 0.00 0.00 0.00
March 0.170974E+10 1134.77 27-MAR-10:40 0.00 0.00 0.00 0.00 0.00
April 0.832026E+09 847.63 01-APR-10:35 0.00 0.00 0.00 0.00 0.00
May 0.493468E+09 694.84 01-MAY-10:40 0.00 0.00 0.00 0.00 0.00
June 64454799.58 468.17 13-JUN-10:40 0.00 0.00 0.00 0.00 0.00
July 0.110519E+09 593.40 29-JUL-10:50 0.00 0.00 0.00 0.00 0.00
August 0.207691E+09 621.85 06-AUG-10:35 0.00 0.00 0.00 0.00 0.00
September 0.312498E+09 624.73 22-SEP-10:35 0.00 0.00 0.00 0.00 0.00
October 0.107512E+10 976.55 26-OCT-10:40 0.00 0.00 0.00 0.00 0.00
November 0.161039E+10 1057.46 24-NOV-11:40 0.00 0.00 0.00 0.00 0.00
December 0.210787E+10 1118.77 07-DEC-11:40 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.121276E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 64454799.58 468.17   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.210787E+10 1134.77   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: LAUNDRY_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.131390E+11 12632.65 02-JAN-05:00 0.00 0.00 0.00 0.00 0.00
February 0.122208E+11 12543.77 13-FEB-04:30 0.00 0.00 0.00 0.00 0.00
March 0.131884E+11 12539.69 27-MAR-04:00 0.00 0.00 0.00 0.00 0.00
April 0.123091E+11 13305.10 14-APR-10:50 0.00 0.00 0.00 0.00 0.00
May 0.126575E+11 13337.20 20-MAY-10:50 0.00 0.00 0.00 0.00 0.00
June 0.127499E+11 13420.70 28-JUN-10:50 0.00 0.00 0.00 0.00 0.00
July 0.131189E+11 13407.98 22-JUL-10:40 0.00 0.00 0.00 0.00 0.00
August 0.131761E+11 13409.24 13-AUG-10:35 0.00 0.00 0.00 0.00 0.00
September 0.124637E+11 13376.47 09-SEP-10:50 0.00 0.00 0.00 0.00 0.00
October 0.127414E+11 13288.96 02-OCT-10:50 0.00 0.00 0.00 0.00 0.00
November 0.125475E+11 12538.54 24-NOV-05:00 0.00 0.00 0.00 0.00 0.00
December 0.134627E+11 12539.92 18-DEC-05:00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.153775E+12     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.122208E+11 12538.54   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.134627E+11 13420.70   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CAFE_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.231099E+10 6449.14 20-JAN-09:20 0.00 0.00 0.00 0.00 0.00
February 0.495085E+10 7745.18 19-FEB-14:20 0.00 0.00 0.00 0.00 0.00
March 0.485895E+10 7547.88 27-MAR-08:03 0.00 0.00 0.00 0.00 0.00
April 0.182236E+10 5506.52 21-APR-08:62 0.00 0.00 0.00 0.00 0.00
May 0.206879E+10 5585.71 22-MAY-10:40 0.00 0.00 0.00 0.00 0.00
June 0.119113E+10 5374.08 13-JUN-10:40 0.00 0.00 0.00 0.00 0.00
July 0.119795E+10 5022.12 27-JUL-10:35 0.00 0.00 0.00 0.00 0.00
August 0.102454E+10 4889.11 07-AUG-10:35 0.00 0.00 0.00 0.00 0.00
September 0.763720E+09 5385.32 03-SEP-10:40 0.00 0.00 0.00 0.00 0.00
October 0.164292E+10 6065.06 25-OCT-06:30 0.00 0.00 0.00 0.00 0.00
November 0.262534E+10 7244.40 13-NOV-11:40 0.00 0.00 0.00 0.00 0.00
December 0.402199E+10 7547.14 06-DEC-07:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.284795E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.763720E+09 4889.11   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.495085E+10 7745.18   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: LOBBY_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.827513E+10 17613.30 06-JAN-11:40 0.00 0.00 0.00 0.00 0.00
February 0.136349E+11 20989.49 12-FEB-16:00 0.00 0.00 0.00 0.00 0.00
March 0.135510E+11 22371.73 27-MAR-10:40 0.00 0.00 0.00 0.00 0.00
April 0.677765E+10 19411.18 21-APR-10:40 0.00 0.00 0.00 0.00 0.00
May 0.684801E+10 19035.04 30-MAY-10:35 0.00 0.00 0.00 0.00 0.00
June 0.444265E+10 17743.97 12-JUN-10:50 0.00 0.00 0.00 0.00 0.00
July 0.465937E+10 17877.51 27-JUL-10:35 0.00 0.00 0.00 0.00 0.00
August 0.421184E+10 18459.41 07-AUG-10:40 0.00 0.00 0.00 0.00 0.00
September 0.330503E+10 16219.12 05-SEP-10:35 0.00 0.00 0.00 0.00 0.00
October 0.566933E+10 17988.36 27-OCT-10:40 0.00 0.00 0.00 0.00 0.00
November 0.823385E+10 20045.87 13-NOV-11:40 0.00 0.00 0.00 0.00 0.00
December 0.122961E+11 20596.08 11-DEC-11:40 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.919049E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.330503E+10 16219.12   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.136349E+11 22371.73   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORRIDOR_FLR_3 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.398002E+10 7130.30 02-JAN-07:20 0.00 0.00 0.00 0.00 0.00
February 0.735543E+10 7453.74 12-FEB-16:00 0.00 0.00 0.00 0.00 0.00
March 0.588561E+10 7811.06 27-MAR-06:20 0.00 0.00 0.00 0.00 0.00
April 0.221161E+09 3920.70 01-APR-06:10 0.00 0.00 0.00 0.00 0.00
May 1242032.12 1420.72 01-MAY-10:50 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.133361E+10 5710.57 26-OCT-06:10 0.00 0.00 0.00 0.00 0.00
November 0.373934E+10 6788.73 24-NOV-07:05 0.00 0.00 0.00 0.00 0.00
December 0.746358E+10 8409.55 07-DEC-07:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.299800E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.746358E+10 8409.55   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORRIDOR_FLR_6 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.676674E+10 6343.53 01-JAN-06:00 0.00 0.00 0.00 0.00 0.00
February 0.780711E+10 5564.09 09-FEB-07:10 0.00 0.00 0.00 0.00 0.00
March 0.709768E+10 6316.50 27-MAR-06:10 0.00 0.00 0.00 0.00 0.00
April 0.227535E+10 4402.36 21-APR-06:05 0.00 0.00 0.00 0.00 0.00
May 0.115711E+10 3102.91 14-MAY-05:10 0.00 0.00 0.00 0.00 0.00
June 37596447.65 1300.03 13-JUN-07:35 0.00 0.00 0.00 0.00 0.00
July 42281327.46 1427.58 29-JUL-06:10 0.00 0.00 0.00 0.00 0.00
August 0.192157E+09 2209.66 06-AUG-05:00 0.00 0.00 0.00 0.00 0.00
September 0.420638E+09 2580.18 22-SEP-07:40 0.00 0.00 0.00 0.00 0.00
October 0.368874E+10 5275.11 26-OCT-06:10 0.00 0.00 0.00 0.00 0.00
November 0.630741E+10 6066.08 24-NOV-07:05 0.00 0.00 0.00 0.00 0.00
December 0.893432E+10 6731.17 05-DEC-07:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.447271E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 37596447.65 1300.03   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.893432E+10 6731.17   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: BANQUET_FLR_6 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.271548E+10 7501.63 02-JAN-11:40 0.00 0.00 0.00 0.00 0.00
February 0.279248E+10 7417.75 03-FEB-11:40 0.00 0.00 0.00 0.00 0.00
March 0.230974E+10 7546.83 28-MAR-10:40 0.00 0.00 0.00 0.00 0.00
April 0.739087E+09 6305.01 21-APR-10:40 0.00 0.00 0.00 0.00 0.00
May 0.400601E+09 5642.82 01-MAY-10:40 0.00 0.00 0.00 0.00 0.00
June 0.180848E+09 4673.64 13-JUN-10:40 0.00 0.00 0.00 0.00 0.00
July 0.182806E+09 4542.29 28-JUL-10:50 0.00 0.00 0.00 0.00 0.00
August 0.283646E+09 5367.23 07-AUG-10:35 0.00 0.00 0.00 0.00 0.00
September 0.356864E+09 5646.65 22-SEP-10:40 0.00 0.00 0.00 0.00 0.00
October 0.143827E+10 7256.72 26-OCT-10:40 0.00 0.00 0.00 0.00 0.00
November 0.233024E+10 7076.92 24-NOV-11:40 0.00 0.00 0.00 0.00 0.00
December 0.350198E+10 7325.45 20-DEC-11:40 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.172321E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.180848E+09 4542.29   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.350198E+10 7546.83   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: DINING_FLR_6 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.217085E+10 7199.74 02-JAN-11:40 0.00 0.00 0.00 0.00 0.00
February 0.227296E+10 7104.48 03-FEB-11:40 0.00 0.00 0.00 0.00 0.00
March 0.177772E+10 7140.65 28-MAR-10:40 0.00 0.00 0.00 0.00 0.00
April 0.443473E+09 5774.84 21-APR-10:40 0.00 0.00 0.00 0.00 0.00
May 0.228376E+09 5094.11 02-MAY-10:50 0.00 0.00 0.00 0.00 0.00
June 0.116725E+09 4205.57 20-JUN-10:40 0.00 0.00 0.00 0.00 0.00
July 0.115554E+09 4283.78 31-JUL-10:40 0.00 0.00 0.00 0.00 0.00
August 0.172445E+09 4832.89 07-AUG-10:35 0.00 0.00 0.00 0.00 0.00
September 0.207189E+09 5186.19 05-SEP-10:35 0.00 0.00 0.00 0.00 0.00
October 0.103825E+10 6919.71 26-OCT-10:40 0.00 0.00 0.00 0.00 0.00
November 0.181546E+10 6731.89 24-NOV-11:40 0.00 0.00 0.00 0.00 0.00
December 0.292556E+10 6895.93 20-DEC-11:40 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.132846E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.115554E+09 4205.57   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.292556E+10 7199.74   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: KITCHEN_FLR_6 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.176786E+10 5524.26 01-JAN-03:50 0.00 0.00 0.00 0.00 0.00
February 0.162123E+10 4987.19 05-FEB-04:00 0.00 0.00 0.00 0.00 0.00
March 0.160135E+10 5394.72 26-MAR-03:00 0.00 0.00 0.00 0.00 0.00
April 0.768042E+09 3813.11 21-APR-03:00 0.00 0.00 0.00 0.00 0.00
May 0.546141E+09 2978.46 14-MAY-03:00 0.00 0.00 0.00 0.00 0.00
June 0.158082E+09 1782.08 11-JUN-03:00 0.00 0.00 0.00 0.00 0.00
July 0.166083E+09 2016.69 29-JUL-03:00 0.00 0.00 0.00 0.00 0.00
August 0.214303E+09 2673.84 06-AUG-03:00 0.00 0.00 0.00 0.00 0.00
September 0.311864E+09 2568.83 22-SEP-03:00 0.00 0.00 0.00 0.00 0.00
October 0.102608E+10 4621.81 26-OCT-03:00 0.00 0.00 0.00 0.00 0.00
November 0.158746E+10 5261.91 24-NOV-03:50 0.00 0.00 0.00 0.00 0.00
December 0.212960E+10 6011.04 07-DEC-04:00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.118981E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.158082E+09 1782.08   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.212960E+10 6011.04   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLR_3_DOAS HEATING COIL

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 31831.69 0.46 10-JAN-18:00 0.00 0.00 0.00 0.00 0.00
February 20405.45 0.46 09-FEB-21:40 0.00 0.00 0.00 0.00 0.00
March 21816.41 0.46 14-MAR-12:00 0.00 0.00 0.00 0.00 0.00
April 60989.00 0.46 24-APR-22:15 0.00 0.00 0.00 0.00 0.00
May 71521.74 0.46 01-MAY-18:08 0.00 0.00 0.00 0.00 0.00
June 83493.92 0.46 25-JUN-18:02 0.00 0.00 0.00 0.00 0.00
July 36308.54 0.46 12-JUL-22:07 0.00 0.00 0.00 0.00 0.00
August 34367.06 0.46 01-AUG-22:20 0.00 0.00 0.00 0.00 0.00
September 33576.99 0.46 04-SEP-23:50 0.00 0.00 0.00 0.00 0.00
October 36798.95 0.46 01-OCT-23:00 0.00 0.00 0.00 0.00 0.00
November 32202.85 0.47 14-NOV-09:40 0.00 0.00 0.00 0.00 0.00
December 13073.82 0.46 24-DEC-18:30 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 476386.43     0.00 0.00 0.00 0.00 0.00
Minimum of Months 13073.82 0.46   0.00 0.00 0.00 0.00 0.00
Maximum of Months 83493.92 0.47   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_1_FLR_3 FAN COIL HEATING COIL

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.339727E+09 5485.98 01-JAN-09:02 0.00 0.00 0.00 0.00 0.00
February 0.564941E+09 5533.76 12-FEB-16:02 0.00 0.00 0.00 0.00 0.00
March 0.424818E+09 5562.30 27-MAR-08:62 0.00 0.00 0.00 0.00 0.00
April 7695845.67 3568.64 09-APR-08:03 0.00 0.00 0.00 0.00 0.00
May 3520289.68 2861.79 01-MAY-08:03 0.00 0.00 0.00 0.00 0.00
June 872996.97 1287.45 13-JUN-08:04 0.00 0.00 0.00 0.00 0.00
July 1967454.86 2436.25 29-JUL-08:04 0.00 0.00 0.00 0.00 0.00
August 2585121.01 2691.66 05-AUG-08:04 0.00 0.00 0.00 0.00 0.00
September 3515777.95 3091.16 04-SEP-08:04 0.00 0.00 0.00 0.00 0.00
October 87364260.33 3704.26 25-OCT-08:62 0.00 0.00 0.00 0.00 0.00
November 0.261851E+09 3780.07 26-NOV-09:03 0.00 0.00 0.00 0.00 0.00
December 0.930863E+09 5555.80 07-DEC-09:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.262972E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 872996.97 1287.45   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.930863E+09 5562.30   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_2_FLR_3 FAN COIL HEATING COIL

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.760061E+09 5630.01 01-JAN-09:02 0.00 0.00 0.00 0.00 0.00
February 0.913717E+09 5571.94 09-FEB-09:02 0.00 0.00 0.00 0.00 0.00
March 0.592741E+09 5597.49 27-MAR-08:62 0.00 0.00 0.00 0.00 0.00
April 11118412.55 3765.79 11-APR-08:03 0.00 0.00 0.00 0.00 0.00
May 3454916.53 2857.95 01-MAY-08:03 0.00 0.00 0.00 0.00 0.00
June 562813.35 939.49 13-JUN-08:04 0.00 0.00 0.00 0.00 0.00
July 1863094.57 2528.80 27-JUL-08:04 0.00 0.00 0.00 0.00 0.00
August 2771386.14 2610.76 05-AUG-08:04 0.00 0.00 0.00 0.00 0.00
September 4216835.44 3179.58 22-SEP-08:03 0.00 0.00 0.00 0.00 0.00
October 0.173624E+09 5527.60 25-OCT-08:62 0.00 0.00 0.00 0.00 0.00
November 0.542826E+09 5591.12 24-NOV-09:02 0.00 0.00 0.00 0.00 0.00
December 0.171278E+10 5682.85 06-DEC-09:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.471974E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 562813.35 939.49   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.171278E+10 5682.85   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:03 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:03 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.590355E+09 28080.02 04-JAN-19:03 0.00 0.00 0.00 0.00 0.00
February 0.477894E+09 31480.77 26-FEB-16:03 0.00 0.00 0.00 0.00 0.00
March 0.410192E+09 29207.32 15-MAR-15:04 0.00 0.00 0.00 0.00 0.00
April 51145655.66 30496.58 26-APR-08:04 0.00 0.00 0.00 0.00 0.00
May 41391959.58 30584.53 25-MAY-08:04 0.00 0.00 0.00 0.00 0.00
June 2216819.00 10855.75 05-JUN-08:07 0.00 0.00 0.00 0.00 0.00
July 7571611.34 10754.51 07-JUL-08:07 0.00 0.00 0.00 0.00 0.00
August 19098889.51 25169.02 07-AUG-08:05 0.00 0.00 0.00 0.00 0.00
September 23744074.41 28315.88 29-SEP-08:04 0.00 0.00 0.00 0.00 0.00
October 0.116312E+09 28235.36 06-OCT-08:04 0.00 0.00 0.00 0.00 0.00
November 0.428727E+09 28267.48 10-NOV-09:03 0.00 0.00 0.00 0.00 0.00
December 0.238330E+10 32026.90 07-DEC-09:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.455195E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 2216819.00 10754.51   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.238330E+10 32026.90   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_5_FLR_3 FAN COIL HEATING COIL

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.394954E+09 3268.91 11-JAN-19:03 0.00 0.00 0.00 0.00 0.00
February 0.551791E+09 5396.22 12-FEB-16:02 0.00 0.00 0.00 0.00 0.00
March 0.411129E+09 3311.88 07-MAR-09:02 0.00 0.00 0.00 0.00 0.00
April 4062112.97 2158.55 29-APR-08:04 0.00 0.00 0.00 0.00 0.00
May 327342.15 2029.72 25-MAY-08:04 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 131181.39 1002.36 04-AUG-08:05 0.00 0.00 0.00 0.00 0.00
September 748825.20 1623.66 03-SEP-18:04 0.00 0.00 0.00 0.00 0.00
October 84540604.69 3053.62 12-OCT-18:03 0.00 0.00 0.00 0.00 0.00
November 0.310823E+09 3673.13 25-NOV-16:03 0.00 0.00 0.00 0.00 0.00
December 0.941491E+09 4583.11 11-DEC-09:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.270000E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.941491E+09 5396.22   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_6_FLR_3 FAN COIL HEATING COIL

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.798373E+09 5382.35 01-JAN-19:02 0.00 0.00 0.00 0.00 0.00
February 0.818063E+09 5407.72 04-FEB-19:03 0.00 0.00 0.00 0.00 0.00
March 0.553891E+09 4193.25 07-MAR-09:02 0.00 0.00 0.00 0.00 0.00
April 8867571.87 2085.40 29-APR-08:04 0.00 0.00 0.00 0.00 0.00
May 360081.50 2066.18 25-MAY-08:04 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 113823.31 1002.18 04-AUG-08:05 0.00 0.00 0.00 0.00 0.00
September 993806.26 1805.60 25-SEP-08:04 0.00 0.00 0.00 0.00 0.00
October 0.154796E+09 3524.73 25-OCT-15:03 0.00 0.00 0.00 0.00 0.00
November 0.592248E+09 5362.66 23-NOV-19:02 0.00 0.00 0.00 0.00 0.00
December 0.163626E+10 5430.09 07-DEC-19:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.456396E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.163626E+10 5430.09   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_1_FLR_6 FAN COIL HEATING COIL

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.167535E+09 1696.42 01-JAN-09:02 0.00 0.00 0.00 0.00 0.00
February 0.251966E+09 1698.10 12-FEB-16:02 0.00 0.00 0.00 0.00 0.00
March 0.180658E+09 1710.59 27-MAR-08:62 0.00 0.00 0.00 0.00 0.00
April 4320374.63 920.20 11-APR-08:03 0.00 0.00 0.00 0.00 0.00
May 794375.08 796.94 13-MAY-08:03 0.00 0.00 0.00 0.00 0.00
June 50001.92 196.52 01-JUN-08:04 0.00 0.00 0.00 0.00 0.00
July 262496.50 578.42 27-JUL-08:04 0.00 0.00 0.00 0.00 0.00
August 381048.54 587.54 05-AUG-08:04 0.00 0.00 0.00 0.00 0.00
September 779343.54 795.33 22-SEP-08:03 0.00 0.00 0.00 0.00 0.00
October 46243512.23 1675.81 25-OCT-08:62 0.00 0.00 0.00 0.00 0.00
November 0.127980E+09 1675.33 24-NOV-09:02 0.00 0.00 0.00 0.00 0.00
December 0.401456E+09 1717.00 07-DEC-09:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.118243E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 50001.92 196.52   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.401456E+09 1717.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_2_FLR_6 FAN COIL HEATING COIL

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.318081E+09 1722.25 01-JAN-09:02 0.00 0.00 0.00 0.00 0.00
February 0.372267E+09 1711.31 09-FEB-09:02 0.00 0.00 0.00 0.00 0.00
March 0.237547E+09 1719.91 27-MAR-08:62 0.00 0.00 0.00 0.00 0.00
April 6484261.78 887.67 11-APR-08:03 0.00 0.00 0.00 0.00 0.00
May 770066.45 714.27 13-MAY-08:03 0.00 0.00 0.00 0.00 0.00
June 34423.48 158.84 01-JUN-08:04 0.00 0.00 0.00 0.00 0.00
July 241747.75 552.21 27-JUL-08:04 0.00 0.00 0.00 0.00 0.00
August 418545.23 569.23 05-AUG-08:04 0.00 0.00 0.00 0.00 0.00
September 907998.72 762.56 22-SEP-08:03 0.00 0.00 0.00 0.00 0.00
October 78420328.92 1696.66 25-OCT-08:62 0.00 0.00 0.00 0.00 0.00
November 0.230147E+09 1718.19 24-NOV-09:02 0.00 0.00 0.00 0.00 0.00
December 0.667715E+09 1722.18 14-DEC-09:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.191303E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 34423.48 158.84   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.667715E+09 1722.25   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.117611E+09 3787.08 02-JAN-09:03 0.00 0.00 0.00 0.00 0.00
February 0.338010E+09 7191.04 12-FEB-16:02 0.00 0.00 0.00 0.00 0.00
March 0.363714E+09 7967.22 27-MAR-08:62 0.00 0.00 0.00 0.00 0.00
April 10540291.65 4700.18 01-APR-08:03 0.00 0.00 0.00 0.00 0.00
May 7330310.47 3512.74 11-MAY-08:04 0.00 0.00 0.00 0.00 0.00
June 3927197.16 3583.93 12-JUN-08:04 0.00 0.00 0.00 0.00 0.00
July 4487376.53 3840.79 27-JUL-08:04 0.00 0.00 0.00 0.00 0.00
August 5364278.53 4049.46 29-AUG-08:04 0.00 0.00 0.00 0.00 0.00
September 4538970.18 4089.66 27-SEP-08:04 0.00 0.00 0.00 0.00 0.00
October 38400060.96 3377.66 16-OCT-08:04 0.00 0.00 0.00 0.00 0.00
November 0.122782E+09 3487.08 24-NOV-09:03 0.00 0.00 0.00 0.00 0.00
December 0.532496E+09 3874.24 11-DEC-19:04 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.154920E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 3927197.16 3377.66   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.532496E+09 7967.22   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: VAV WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.214851E+12 0.213001E+12 295052.36 31-JAN-17:00 295052.36 0.04
February 0.00 0.00 0.746772E+11 0.741326E+11 213860.07 18-FEB-14:00 213860.07 0.19
March 0.00 0.00 0.234339E+12 0.234339E+12 304911.93 20-MAR-17:12 304911.93 0.12
April 0.00 0.00 0.542470E+12 0.542470E+12 379153.04 14-APR-17:12 379153.04 0.03
May 0.00 0.00 0.686613E+12 0.686613E+12 399523.97 31-MAY-18:10 399523.97 0.01
June 0.00 0.00 0.826783E+12 0.825029E+12 546622.60 17-JUN-16:00 433530.97 0.13
July 0.00 0.00 0.962945E+12 0.832588E+12 621956.02 13-JUL-18:10 315856.63 0.78
August 0.00 0.00 0.938036E+12 0.816408E+12 590469.37 28-AUG-17:00 236007.90 0.85
September 0.00 0.00 0.856449E+12 0.732932E+12 573752.44 04-SEP-10:35 323843.87 0.82
October 0.00 0.00 0.472406E+12 0.458139E+12 496579.68 03-OCT-10:35 348203.83 0.28
November 0.00 0.00 0.254917E+12 0.218064E+12 420112.47 12-NOV-15:00 177815.31 0.25
December 0.00 0.00 0.125691E+12 0.125691E+12 261274.58 22-DEC-11:50 261274.58 0.00
                 
Annual Sum or Average 0.00 0.00 0.619018E+13 0.575941E+13       0.29
Minimum of Months 0.00 0.00 0.746772E+11 0.741326E+11 213860.07   177815.31 0.00
Maximum of Months 0.00 0.00 0.962945E+12 0.832588E+12 621956.02   433530.97 0.85



Table of Contents

Report: CoilReportMonthly

For: FLR_3_DOAS COOLING COIL

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.199430E+11 0.198096E+11 28446.23 31-JAN-16:01 28446.23 0.04
February 0.00 0.00 0.520636E+10 0.520636E+10 23246.09 18-FEB-14:00 23246.09 0.13
March 0.00 0.00 0.213396E+11 0.213396E+11 28923.70 16-MAR-15:02 28923.70 0.11
April 0.00 0.00 0.507919E+11 0.507919E+11 32711.51 14-APR-15:00 32711.51 0.02
May 0.00 0.00 0.643393E+11 0.643393E+11 33442.98 31-MAY-17:10 33442.98 0.01
June 0.00 0.00 0.748333E+11 0.747447E+11 40852.50 17-JUN-16:00 34473.88 0.11
July 0.00 0.00 0.880898E+11 0.767142E+11 50371.12 13-JUL-18:02 28134.88 0.77
August 0.00 0.00 0.873130E+11 0.756907E+11 55604.06 05-AUG-08:00 24815.05 0.85
September 0.00 0.00 0.816009E+11 0.693110E+11 59502.56 04-SEP-08:61 24047.55 0.81
October 0.00 0.00 0.443094E+11 0.429107E+11 45960.15 03-OCT-05:00 23454.84 0.27
November 0.00 0.00 0.228498E+11 0.197102E+11 44169.39 12-NOV-14:30 21149.34 0.24
December 0.00 0.00 0.112014E+11 0.112014E+11 26699.29 25-DEC-16:00 26699.29 0.00
                 
Annual Sum or Average 0.00 0.00 0.571818E+12 0.531770E+12       0.28
Minimum of Months 0.00 0.00 0.520636E+10 0.520636E+10 23246.09   21149.34 0.00
Maximum of Months 0.00 0.00 0.880898E+11 0.767142E+11 59502.56   34473.88 0.85



Table of Contents

Report: CoilReportMonthly

For: ROOM_1_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.353540E+10 0.325475E+10 19209.10 08-JAN-16:01 16662.07 0.11
February 0.00 0.00 0.125846E+10 0.906619E+09 18561.70 24-FEB-16:02 18561.70 0.20
March 0.00 0.00 0.279561E+10 0.222281E+10 18560.42 02-MAR-16:01 18560.42 0.26
April 0.00 0.00 0.881471E+10 0.859121E+10 18558.15 25-APR-18:01 18558.15 0.08
May 0.00 0.00 0.106036E+11 0.105350E+11 18562.93 11-MAY-08:61 18562.93 0.02
June 0.00 0.00 0.143903E+11 0.136570E+11 18563.55 01-JUN-18:02 18563.55 0.24
July 0.00 0.00 0.140550E+11 0.101852E+11 20229.52 27-JUL-08:61 15899.00 0.76
August 0.00 0.00 0.137452E+11 0.963464E+10 21212.80 05-AUG-08:61 15545.35 0.83
September 0.00 0.00 0.118245E+11 0.780684E+10 22066.59 04-SEP-08:61 15045.63 0.87
October 0.00 0.00 0.719214E+10 0.584479E+10 19421.23 03-OCT-08:61 16542.95 0.35
November 0.00 0.00 0.356850E+10 0.281305E+10 21235.76 13-NOV-16:01 15534.38 0.26
December 0.00 0.00 0.177850E+10 0.177529E+10 18552.61 13-DEC-16:01 18552.61 0.00
                 
Annual Sum or Average 0.00 0.00 0.935619E+11 0.772273E+11       0.33
Minimum of Months 0.00 0.00 0.125846E+10 0.906619E+09 18552.61   15045.63 0.00
Maximum of Months 0.00 0.00 0.143903E+11 0.136570E+11 22066.59   18563.55 0.87



Table of Contents

Report: CoilReportMonthly

For: ROOM_2_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.140122E+10 0.128591E+10 19116.05 08-JAN-16:01 16287.76 0.07
February 0.00 0.00 0.478842E+09 0.353537E+09 18434.74 21-FEB-16:01 18434.74 0.10
March 0.00 0.00 0.190175E+10 0.151383E+10 18435.63 16-MAR-18:01 18435.63 0.21
April 0.00 0.00 0.769002E+10 0.747311E+10 18433.30 25-APR-18:01 18433.30 0.08
May 0.00 0.00 0.103068E+11 0.102380E+11 18438.39 11-MAY-08:61 18438.39 0.02
June 0.00 0.00 0.145692E+11 0.138474E+11 18438.56 01-JUN-18:02 18438.56 0.24
July 0.00 0.00 0.139999E+11 0.101635E+11 19996.48 27-JUL-08:61 15999.70 0.76
August 0.00 0.00 0.130381E+11 0.900959E+10 20804.04 05-AUG-08:61 15591.59 0.82
September 0.00 0.00 0.105770E+11 0.672815E+10 21685.70 04-SEP-08:61 15021.53 0.86
October 0.00 0.00 0.520812E+10 0.403513E+10 19270.63 03-OCT-08:61 16323.94 0.32
November 0.00 0.00 0.168740E+10 0.120282E+10 21274.22 13-NOV-16:01 15318.49 0.20
December 0.00 0.00 0.475854E+09 0.475854E+09 18416.74 27-DEC-16:01 18416.74 0.00
                 
Annual Sum or Average 0.00 0.00 0.813343E+11 0.663269E+11       0.31
Minimum of Months 0.00 0.00 0.475854E+09 0.353537E+09 18416.74   15021.53 0.00
Maximum of Months 0.00 0.00 0.145692E+11 0.138474E+11 21685.70   18438.56 0.86



Table of Contents

Report: CoilReportMonthly

For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.496434E+11 0.482450E+11 55236.46 14-JAN-13:40 55236.46 0.07
February 0.00 0.00 0.193957E+11 0.158045E+11 42059.66 01-FEB-15:30 42059.66 0.22
March 0.00 0.00 0.207904E+11 0.186698E+11 38552.53 18-MAR-13:50 34938.74 0.13
April 0.00 0.00 0.454817E+11 0.452374E+11 39298.19 14-APR-13:40 39298.19 0.02
May 0.00 0.00 0.459099E+11 0.458812E+11 35475.04 07-MAY-20:03 35475.04 0.00
June 0.00 0.00 0.610696E+11 0.587693E+11 47183.93 17-JUN-19:10 41087.03 0.11
July 0.00 0.00 0.652796E+11 0.433602E+11 46001.11 22-JUL-20:10 39562.13 0.77
August 0.00 0.00 0.685384E+11 0.454220E+11 49225.08 28-AUG-12:30 43874.13 0.84
September 0.00 0.00 0.681551E+11 0.480993E+11 52992.66 28-SEP-13:40 52992.66 0.79
October 0.00 0.00 0.563190E+11 0.494068E+11 54466.37 18-OCT-13:40 54466.37 0.28
November 0.00 0.00 0.415958E+11 0.374191E+11 56920.94 20-NOV-14:30 56920.94 0.22
December 0.00 0.00 0.375970E+11 0.374574E+11 54781.62 25-DEC-13:30 54781.62 0.01
                 
Annual Sum or Average 0.00 0.00 0.579775E+12 0.493772E+12       0.29
Minimum of Months 0.00 0.00 0.193957E+11 0.158045E+11 35475.04   34938.74 0.00
Maximum of Months 0.00 0.00 0.685384E+11 0.587693E+11 56920.94   56920.94 0.84



Table of Contents

Report: CoilReportMonthly

For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.179820E+11 0.157823E+11 115630.66 08-JAN-16:01 100947.75 0.13
February 0.00 0.00 0.152403E+11 0.798597E+10 120973.25 18-FEB-19:02 101108.14 0.45
March 0.00 0.00 0.254972E+11 0.196311E+11 119001.53 16-MAR-18:01 119001.53 0.33
April 0.00 0.00 0.536553E+11 0.522723E+11 119838.08 25-APR-18:01 119838.08 0.07
May 0.00 0.00 0.711973E+11 0.708064E+11 119765.64 10-MAY-18:02 119765.64 0.02
June 0.00 0.00 0.950416E+11 0.906667E+11 119882.53 03-JUN-08:61 119882.53 0.23
July 0.00 0.00 0.100256E+12 0.770601E+11 121974.70 27-JUL-08:61 106113.60 0.72
August 0.00 0.00 0.924743E+11 0.674896E+11 140323.99 28-AUG-18:02 99125.30 0.76
September 0.00 0.00 0.805722E+11 0.556422E+11 138565.94 03-SEP-08:62 97410.85 0.79
October 0.00 0.00 0.451968E+11 0.371465E+11 119881.66 05-OCT-18:02 119881.66 0.29
November 0.00 0.00 0.225113E+11 0.157214E+11 136027.30 12-NOV-09:02 91338.57 0.27
December 0.00 0.00 0.103064E+11 0.101309E+11 113528.31 03-DEC-09:02 113528.31 0.01
                 
Annual Sum or Average 0.00 0.00 0.629930E+12 0.520335E+12       0.34
Minimum of Months 0.00 0.00 0.103064E+11 0.798597E+10 113528.31   91338.57 0.01
Maximum of Months 0.00 0.00 0.100256E+12 0.906667E+11 140323.99   119882.53 0.79



Table of Contents

Report: CoilReportMonthly

For: ROOM_5_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.332458E+10 0.304683E+10 16929.52 08-JAN-16:01 14386.88 0.12
February 0.00 0.00 0.149847E+10 0.100101E+10 16615.94 18-FEB-09:02 13921.09 0.25
March 0.00 0.00 0.290814E+10 0.228858E+10 16346.66 16-MAR-18:01 16346.66 0.29
April 0.00 0.00 0.890446E+10 0.868798E+10 16349.59 18-APR-08:62 16349.59 0.08
May 0.00 0.00 0.109356E+11 0.108754E+11 16349.52 11-MAY-08:61 16349.52 0.02
June 0.00 0.00 0.147575E+11 0.141410E+11 16350.30 06-JUN-08:61 16350.30 0.24
July 0.00 0.00 0.150387E+11 0.112663E+11 17054.54 09-JUL-08:61 14596.93 0.78
August 0.00 0.00 0.145558E+11 0.105706E+11 18586.05 04-AUG-08:62 13405.90 0.85
September 0.00 0.00 0.122754E+11 0.834003E+10 19097.38 03-SEP-08:62 12983.19 0.89
October 0.00 0.00 0.747596E+10 0.611972E+10 17075.93 22-OCT-08:62 14560.22 0.37
November 0.00 0.00 0.325943E+10 0.261520E+10 18182.14 13-NOV-16:01 12485.95 0.26
December 0.00 0.00 0.180247E+10 0.179247E+10 16335.34 03-DEC-16:01 16335.34 0.00
                 
Annual Sum or Average 0.00 0.00 0.967365E+11 0.807452E+11       0.35
Minimum of Months 0.00 0.00 0.149847E+10 0.100101E+10 16335.34   12485.95 0.00
Maximum of Months 0.00 0.00 0.150387E+11 0.141410E+11 19097.38   16350.30 0.89



Table of Contents

Report: CoilReportMonthly

For: ROOM_6_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.116202E+10 0.103144E+10 16205.01 31-JAN-16:01 16205.01 0.07
February 0.00 0.00 0.591004E+09 0.311154E+09 16433.58 20-FEB-09:02 14624.05 0.17
March 0.00 0.00 0.194748E+10 0.148593E+10 16240.93 16-MAR-18:01 16240.93 0.23
April 0.00 0.00 0.772212E+10 0.750895E+10 16239.33 25-APR-18:01 16239.33 0.08
May 0.00 0.00 0.106310E+11 0.105702E+11 16243.96 11-MAY-08:61 16243.96 0.02
June 0.00 0.00 0.149366E+11 0.143364E+11 16243.62 01-JUN-18:02 16243.62 0.25
July 0.00 0.00 0.149795E+11 0.112159E+11 16885.53 09-JUL-08:61 14534.20 0.78
August 0.00 0.00 0.138551E+11 0.983497E+10 18130.77 04-AUG-08:62 13516.99 0.84
September 0.00 0.00 0.110314E+11 0.721108E+10 18971.21 03-SEP-08:62 12853.17 0.88
October 0.00 0.00 0.536881E+10 0.418064E+10 16883.64 22-OCT-08:62 14231.97 0.34
November 0.00 0.00 0.140069E+10 0.996452E+09 16220.46 20-NOV-16:01 16220.46 0.20
December 0.00 0.00 0.427013E+09 0.423256E+09 15618.59 25-DEC-16:02 15618.59 0.00
                 
Annual Sum or Average 0.00 0.00 0.840528E+11 0.691065E+11       0.32
Minimum of Months 0.00 0.00 0.427013E+09 0.311154E+09 15618.59   12853.17 0.00
Maximum of Months 0.00 0.00 0.149795E+11 0.143364E+11 18971.21   16243.96 0.88



Table of Contents

Report: CoilReportMonthly

For: ROOM_1_FLR_6 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.916616E+09 0.852375E+09 5173.37 08-JAN-16:01 4522.65 0.10
February 0.00 0.00 0.311384E+09 0.235682E+09 5022.90 24-FEB-16:02 5022.90 0.17
March 0.00 0.00 0.764838E+09 0.623263E+09 5022.45 02-MAR-16:01 5022.45 0.24
April 0.00 0.00 0.252217E+10 0.246242E+10 5021.74 25-APR-18:01 5021.74 0.08
May 0.00 0.00 0.306320E+10 0.304457E+10 5023.28 11-MAY-08:61 5023.28 0.02
June 0.00 0.00 0.415876E+10 0.395462E+10 5023.25 01-JUN-18:02 5023.25 0.25
July 0.00 0.00 0.406328E+10 0.300720E+10 5604.54 27-JUL-08:61 4265.21 0.77
August 0.00 0.00 0.396830E+10 0.285803E+10 5877.99 05-AUG-08:61 4128.05 0.84
September 0.00 0.00 0.336249E+10 0.227770E+10 6156.86 04-SEP-08:61 3963.45 0.88
October 0.00 0.00 0.196820E+10 0.160791E+10 5399.98 03-OCT-08:61 4397.04 0.35
November 0.00 0.00 0.931320E+09 0.744035E+09 5707.54 13-NOV-16:01 4226.02 0.24
December 0.00 0.00 0.441887E+09 0.441506E+09 5020.35 13-DEC-16:01 5020.35 0.00
                 
Annual Sum or Average 0.00 0.00 0.264724E+11 0.221093E+11       0.33
Minimum of Months 0.00 0.00 0.311384E+09 0.235682E+09 5020.35   3963.45 0.00
Maximum of Months 0.00 0.00 0.415876E+10 0.395462E+10 6156.86   5023.28 0.88



Table of Contents

Report: CoilReportMonthly

For: ROOM_2_FLR_6 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.360341E+09 0.338172E+09 5188.09 08-JAN-16:01 4429.39 0.06
February 0.00 0.00 0.113794E+09 89896803.75 4985.05 21-FEB-16:01 4985.05 0.08
March 0.00 0.00 0.524790E+09 0.428053E+09 4985.09 02-MAR-16:01 4985.09 0.19
April 0.00 0.00 0.222529E+10 0.216830E+10 4984.52 25-APR-18:01 4984.52 0.08
May 0.00 0.00 0.298581E+10 0.296558E+10 4985.40 10-MAY-08:61 4985.40 0.02
June 0.00 0.00 0.420591E+10 0.399943E+10 4986.08 01-JUN-18:02 4986.08 0.25
July 0.00 0.00 0.404961E+10 0.299960E+10 5521.65 27-JUL-08:61 4273.41 0.77
August 0.00 0.00 0.378505E+10 0.268115E+10 5753.49 05-AUG-08:61 4143.82 0.83
September 0.00 0.00 0.303635E+10 0.197376E+10 6044.49 04-SEP-08:61 3972.90 0.87
October 0.00 0.00 0.144165E+10 0.112056E+10 5357.32 03-OCT-08:61 4340.22 0.31
November 0.00 0.00 0.438709E+09 0.320017E+09 5757.16 13-NOV-16:01 4141.53 0.18
December 0.00 0.00 0.115820E+09 0.115808E+09 4981.77 03-DEC-16:01 4981.77 0.00
                 
Annual Sum or Average 0.00 0.00 0.232831E+11 0.192003E+11       0.30
Minimum of Months 0.00 0.00 0.113794E+09 89896803.75 4981.77   3972.90 0.00
Maximum of Months 0.00 0.00 0.420591E+10 0.399943E+10 6044.49   4986.08 0.87



Table of Contents

Report: CoilReportMonthly

For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.113094E+11 0.106696E+11 22666.51 08-JAN-16:01 20703.89 0.18
February 0.00 0.00 0.486778E+10 0.354267E+10 23442.85 18-FEB-19:02 19166.68 0.42
March 0.00 0.00 0.606501E+10 0.491625E+10 22595.67 16-MAR-18:01 22595.67 0.34
April 0.00 0.00 0.127032E+11 0.123695E+11 22592.63 25-APR-18:01 22592.63 0.09
May 0.00 0.00 0.135290E+11 0.134370E+11 22587.50 10-MAY-08:61 22587.50 0.02
June 0.00 0.00 0.177926E+11 0.166704E+11 22596.94 19-JUN-15:02 22596.94 0.29
July 0.00 0.00 0.193924E+11 0.144222E+11 24599.35 27-JUL-08:61 19364.90 0.76
August 0.00 0.00 0.199915E+11 0.146981E+11 26192.89 05-AUG-08:61 18764.16 0.84
September 0.00 0.00 0.190725E+11 0.137426E+11 27081.14 04-SEP-08:61 18257.95 0.90
October 0.00 0.00 0.143759E+11 0.123958E+11 23476.98 03-OCT-08:61 20264.45 0.39
November 0.00 0.00 0.101402E+11 0.873900E+10 25696.11 13-NOV-16:01 19046.39 0.32
December 0.00 0.00 0.825955E+10 0.822091E+10 22586.37 13-DEC-16:01 22586.37 0.01
                 
Annual Sum or Average 0.00 0.00 0.157499E+12 0.133824E+12       0.38
Minimum of Months 0.00 0.00 0.486778E+10 0.354267E+10 22586.37   18257.95 0.01
Maximum of Months 0.00 0.00 0.199915E+11 0.166704E+11 27081.14   22596.94 0.90



Table of Contents

Report: PlantLoopDemandReportMonthly

For: HEATSYS1

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:05 21149.46 85196.62 02-JAN-09:02
February 0.00 0.00 01-FEB-00:03 30746.78 91742.89 12-FEB-16:02
March 0.00 0.00 01-MAR-00:03 28128.34 112522.94 27-MAR-08:62
April 0.00 0.00 01-APR-00:10 15830.11 77057.88 21-APR-10:35
May 0.00 0.00 01-MAY-00:10 15386.40 71829.69 25-MAY-08:04
June 0.00 0.00 01-JUN-00:10 12555.34 59930.57 13-JUN-10:40
July 0.00 0.00 01-JUL-00:10 9841.05 69026.67 27-JUL-10:35
August 0.00 0.00 01-AUG-00:10 8876.79 70349.35 07-AUG-10:35
September 0.00 0.00 01-SEP-00:10 7552.03 59392.27 11-SEP-08:04
October 0.00 0.00 01-OCT-00:10 12727.70 80872.20 30-OCT-08:04
November 0.00 0.00 01-NOV-00:10 18871.31 87116.50 24-NOV-09:02
December 0.00 0.00 01-DEC-00:03 27422.68 104064.67 07-DEC-09:02
             
Annual Sum or Average 0.00     17355.28    
Minimum of Months 0.00 0.00   7552.03 59392.27  
Maximum of Months 0.00 0.00   30746.78 112522.94  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: COOLSYS1

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 128256.59 541851.52 31-JAN-16:01 0.00 0.00 01-JAN-00:05
February 57149.99 423376.02 21-FEB-16:01 0.00 0.00 01-FEB-00:03
March 126146.59 545987.28 15-MAR-18:01 0.00 0.00 01-MAR-00:03
April 295789.88 650129.38 13-APR-18:03 0.00 0.00 01-APR-00:10
May 356856.75 681874.99 31-MAY-18:03 0.00 0.00 01-MAY-00:10
June 450928.07 786996.67 17-JUN-18:03 0.00 0.00 01-JUN-00:10
July 496480.02 916587.32 13-JUL-18:03 0.00 0.00 01-JUL-00:10
August 484223.44 840366.78 09-AUG-18:03 0.00 0.00 01-AUG-00:10
September 456986.19 799558.91 03-SEP-08:62 0.00 0.00 01-SEP-00:10
October 255650.89 765361.92 01-OCT-18:03 0.00 0.00 01-OCT-00:10
November 147639.58 611898.39 11-NOV-19:03 0.00 0.00 01-NOV-00:10
December 79671.97 524657.79 25-DEC-16:02 0.00 0.00 01-DEC-00:03
             
Annual Sum or Average 279140.78     0.00    
Minimum of Months 57149.99 423376.02   0.00 0.00  
Maximum of Months 496480.02 916587.32   0.00 0.00  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:05 23575.60 47628.23 20-JAN-07:10
February 0.00 0.00 01-FEB-00:03 23355.36 47503.16 01-FEB-08:00
March 0.00 0.00 01-MAR-00:03 22317.61 46192.72 01-MAR-07:10
April 0.00 0.00 01-APR-00:10 20652.96 42863.41 03-APR-07:00
May 0.00 0.00 01-MAY-00:10 18861.62 39392.81 01-MAY-07:00
June 0.00 0.00 01-JUN-00:10 17412.41 35815.96 01-JUN-07:00
July 0.00 0.00 01-JUL-00:10 16680.50 33442.36 03-JUL-06:40
August 0.00 0.00 01-AUG-00:10 16915.09 34401.73 31-AUG-06:50
September 0.00 0.00 01-SEP-00:10 17995.30 37263.94 29-SEP-06:10
October 0.00 0.00 01-OCT-00:10 19651.28 41135.10 31-OCT-07:00
November 0.00 0.00 01-NOV-00:10 21443.99 44618.68 30-NOV-08:00
December 0.00 0.00 01-DEC-00:03 22877.13 46933.69 29-DEC-08:00
             
Annual Sum or Average 0.00     20126.94    
Minimum of Months 0.00 0.00   16680.50 33442.36  
Maximum of Months 0.00 0.00   23575.60 47628.23  



Table of Contents

Report: FanReportMonthly

For: FLR_3_DOAS FAN

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.587890E+10 0.97 2194.93 01-JAN-00:05 0.97
February 0.530997E+10 0.96 2194.93 01-FEB-00:03 0.97
March 0.587890E+10 0.96 2194.93 01-MAR-00:03 0.96
April 0.568926E+10 0.97 2194.93 01-APR-00:10 0.97
May 0.587890E+10 0.97 2194.93 01-MAY-00:10 0.97
June 0.568926E+10 0.97 2194.93 01-JUN-00:10 0.97
July 0.587890E+10 0.96 2194.93 01-JUL-00:10 0.96
August 0.587890E+10 0.96 2194.93 01-AUG-00:10 0.96
September 0.568926E+10 0.96 2194.93 01-SEP-00:10 0.96
October 0.587890E+10 0.96 2194.93 01-OCT-00:10 0.96
November 0.568926E+10 0.96 2194.93 01-NOV-00:10 0.96
December 0.587890E+10 0.97 2194.93 01-DEC-00:03 0.97
           
Annual Sum or Average 0.692193E+11 0.96      
Minimum of Months 0.530997E+10 0.96 2194.93   0.96
Maximum of Months 0.587890E+10 0.97 2194.93   0.97



Table of Contents

Report: FanReportMonthly

For: VAV WITH REHEAT FAN

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.147825E+12 2.02 55230.68 01-JAN-11:40 2.03
February 0.133512E+12 2.01 55230.68 01-FEB-11:35 2.02
March 0.147826E+12 2.02 55230.68 01-MAR-11:40 2.01
April 0.143085E+12 2.03 55230.68 01-APR-09:10 2.03
May 0.147861E+12 2.03 55230.68 01-MAY-09:10 2.03
June 0.143104E+12 2.02 55230.68 01-JUN-07:30 2.02
July 0.147869E+12 2.01 55230.68 01-JUL-07:50 2.03
August 0.147866E+12 2.01 55230.68 01-AUG-06:30 2.00
September 0.143089E+12 2.01 55230.68 01-SEP-06:20 2.00
October 0.147843E+12 2.02 55230.68 01-OCT-09:10 2.00
November 0.143056E+12 2.02 55230.68 01-NOV-11:00 2.00
December 0.147817E+12 2.03 55230.68 01-DEC-08:30 2.02
           
Annual Sum or Average 0.174075E+13 2.02      
Minimum of Months 0.133512E+12 2.01 55230.68   2.00
Maximum of Months 0.147869E+12 2.03 55230.68   2.03



Table of Contents

Report: FanReportMonthly

For: LAUNDRY_FLR_1 EXHAUST FAN

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.493775E+09 0.71 184.35 01-JAN-00:05 0.71
February 0.445990E+09 0.70 184.35 01-FEB-00:03 0.71
March 0.493775E+09 0.70 184.35 01-MAR-00:03 0.70
April 0.477847E+09 0.71 184.35 01-APR-00:10 0.71
May 0.493775E+09 0.71 184.35 01-MAY-00:10 0.71
June 0.477847E+09 0.70 184.35 01-JUN-00:10 0.71
July 0.493775E+09 0.70 184.35 01-JUL-00:10 0.70
August 0.493775E+09 0.70 184.35 01-AUG-00:10 0.70
September 0.477847E+09 0.70 184.35 01-SEP-00:10 0.70
October 0.493775E+09 0.70 184.35 01-OCT-00:10 0.70
November 0.477847E+09 0.70 184.35 01-NOV-00:10 0.70
December 0.493775E+09 0.71 184.35 01-DEC-00:03 0.71
           
Annual Sum or Average 0.581380E+10 0.70      
Minimum of Months 0.445990E+09 0.70 184.35   0.70
Maximum of Months 0.493775E+09 0.71 184.35   0.71



Table of Contents

Report: FanReportMonthly

For: LOBBY_FLR_1 EXHAUST FAN

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.00 0.00 0.00 01-JAN-00:05 0.00
February 0.00 0.00 0.00 01-FEB-00:03 0.00
March 0.00 0.00 0.00 01-MAR-00:03 0.00
April 0.00 0.00 0.00 01-APR-00:10 0.00
May 0.00 0.00 0.00 01-MAY-00:10 0.00
June 0.00 0.00 0.00 01-JUN-00:10 0.00
July 0.00 0.00 0.00 01-JUL-00:10 0.00
August 0.00 0.00 0.00 01-AUG-00:10 0.00
September 0.00 0.00 0.00 01-SEP-00:10 0.00
October 0.00 0.00 0.00 01-OCT-00:10 0.00
November 0.00 0.00 0.00 01-NOV-00:10 0.00
December 0.00 0.00 0.00 01-DEC-00:03 0.00
           
Annual Sum or Average 0.00 0.00      
Minimum of Months 0.00 0.00 0.00   0.00
Maximum of Months 0.00 0.00 0.00   0.00



Table of Contents

Report: FanReportMonthly

For: BANQUET_FLR_6 EXHAUST FAN

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.00 0.00 0.00 01-JAN-00:05 0.00
February 0.00 0.00 0.00 01-FEB-00:03 0.00
March 0.00 0.00 0.00 01-MAR-00:03 0.00
April 0.00 0.00 0.00 01-APR-00:10 0.00
May 0.00 0.00 0.00 01-MAY-00:10 0.00
June 0.00 0.00 0.00 01-JUN-00:10 0.00
July 0.00 0.00 0.00 01-JUL-00:10 0.00
August 0.00 0.00 0.00 01-AUG-00:10 0.00
September 0.00 0.00 0.00 01-SEP-00:10 0.00
October 0.00 0.00 0.00 01-OCT-00:10 0.00
November 0.00 0.00 0.00 01-NOV-00:10 0.00
December 0.00 0.00 0.00 01-DEC-00:03 0.00
           
Annual Sum or Average 0.00 0.00      
Minimum of Months 0.00 0.00 0.00   0.00
Maximum of Months 0.00 0.00 0.00   0.00



Table of Contents

Report: FanReportMonthly

For: DINING_FLR_6 EXHAUST FAN

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.00 0.00 0.00 01-JAN-00:05 0.00
February 0.00 0.00 0.00 01-FEB-00:03 0.00
March 0.00 0.00 0.00 01-MAR-00:03 0.00
April 0.00 0.00 0.00 01-APR-00:10 0.00
May 0.00 0.00 0.00 01-MAY-00:10 0.00
June 0.00 0.00 0.00 01-JUN-00:10 0.00
July 0.00 0.00 0.00 01-JUL-00:10 0.00
August 0.00 0.00 0.00 01-AUG-00:10 0.00
September 0.00 0.00 0.00 01-SEP-00:10 0.00
October 0.00 0.00 0.00 01-OCT-00:10 0.00
November 0.00 0.00 0.00 01-NOV-00:10 0.00
December 0.00 0.00 0.00 01-DEC-00:03 0.00
           
Annual Sum or Average 0.00 0.00      
Minimum of Months 0.00 0.00 0.00   0.00
Maximum of Months 0.00 0.00 0.00   0.00



Table of Contents

Report: FanReportMonthly

For: KITCHEN_FLR_6 EXHAUST FAN

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.279806E+10 0.50 1474.84 01-JAN-07:10 0.70
February 0.252728E+10 0.50 1474.84 01-FEB-07:10 0.70
March 0.279806E+10 0.50 1474.84 01-MAR-07:05 0.70
April 0.270780E+10 0.50 1474.84 01-APR-06:10 0.71
May 0.279806E+10 0.50 1474.84 01-MAY-06:05 0.71
June 0.270780E+10 0.50 1474.84 01-JUN-06:05 0.70
July 0.279806E+10 0.50 1474.84 01-JUL-06:10 0.71
August 0.279806E+10 0.49 1474.84 01-AUG-06:05 0.70
September 0.270780E+10 0.49 1474.84 01-SEP-06:05 0.70
October 0.279806E+10 0.50 1474.84 01-OCT-06:10 0.70
November 0.270780E+10 0.50 1474.84 01-NOV-06:05 0.70
December 0.279806E+10 0.50 1474.84 01-DEC-07:10 0.70
           
Annual Sum or Average 0.329449E+11 0.50      
Minimum of Months 0.252728E+10 0.49 1474.84   0.70
Maximum of Months 0.279806E+10 0.50 1474.84   0.71



Table of Contents

Report: FanReportMonthly

For: ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.585447E+09 1.28 2213.11 01-JAN-09:02 1.53
February 0.369993E+09 1.14 2213.11 01-FEB-16:01 1.53
March 0.522333E+09 1.20 2213.11 02-MAR-16:01 1.52
April 0.108525E+10 1.41 2213.11 01-APR-15:02 1.53
May 0.127795E+10 1.44 2213.11 01-MAY-15:02 1.53
June 0.174161E+10 1.47 2213.11 01-JUN-08:61 1.52
July 0.155600E+10 1.46 2213.11 01-JUL-08:61 1.53
August 0.152231E+10 1.45 2213.11 01-AUG-08:61 1.51
September 0.131117E+10 1.44 2213.11 01-SEP-08:61 1.51
October 0.906010E+09 1.35 2213.11 01-OCT-08:61 1.51
November 0.545911E+09 1.27 2213.11 01-NOV-15:02 1.52
December 0.519117E+09 1.23 2213.11 01-DEC-16:01 1.53
           
Annual Sum or Average 0.119431E+11 1.35      
Minimum of Months 0.369993E+09 1.14 2213.11   1.51
Maximum of Months 0.174161E+10 1.47 2213.11   1.53



Table of Contents

Report: FanReportMonthly

For: ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.440271E+09 1.14 2198.15 01-JAN-09:02 1.53
February 0.364868E+09 1.08 2198.15 01-FEB-09:02 1.52
March 0.454211E+09 1.13 2198.15 02-MAR-16:01 1.52
April 0.964336E+09 1.37 2198.15 01-APR-15:02 1.53
May 0.124607E+10 1.43 2198.15 01-MAY-15:02 1.53
June 0.176820E+10 1.48 2198.15 01-JUN-08:61 1.52
July 0.155102E+10 1.46 2198.15 01-JUL-08:61 1.53
August 0.143337E+10 1.45 2198.15 01-AUG-08:61 1.51
September 0.116734E+10 1.42 2198.15 01-SEP-08:61 1.51
October 0.706262E+09 1.26 2198.15 01-OCT-08:61 1.51
November 0.404652E+09 1.14 2198.15 01-NOV-15:02 1.52
December 0.532311E+09 1.10 2198.15 01-DEC-09:02 1.53
           
Annual Sum or Average 0.110329E+11 1.29      
Minimum of Months 0.364868E+09 1.08 2198.15   1.51
Maximum of Months 0.176820E+10 1.48 2198.15   1.53



Table of Contents

Report: FanReportMonthly

For: ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.524986E+10 1.18 6784.62 09-JAN-14:30 1.52
February 0.219176E+10 0.81 3965.55 01-FEB-15:30 1.53
March 0.248822E+10 0.94 4016.59 18-MAR-14:00 1.52
April 0.487999E+10 1.38 3743.16 14-APR-13:40 1.53
May 0.501074E+10 1.45 3438.67 07-MAY-20:03 1.53
June 0.635638E+10 1.53 6531.58 28-JUN-18:30 1.52
July 0.635094E+10 1.51 4128.13 22-JUL-19:10 1.52
August 0.657874E+10 1.51 4278.46 27-AUG-14:00 1.52
September 0.655755E+10 1.51 7165.13 28-SEP-12:20 1.52
October 0.592933E+10 1.35 7348.24 05-OCT-14:10 1.52
November 0.441560E+10 1.11 6799.36 15-NOV-14:30 1.52
December 0.403615E+10 0.99 6245.89 25-DEC-13:30 1.53
           
Annual Sum or Average 0.600453E+11 1.28      
Minimum of Months 0.219176E+10 0.81 3438.67   1.52
Maximum of Months 0.657874E+10 1.53 7348.24   1.53



Table of Contents

Report: FanReportMonthly

For: ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.271451E+10 1.08 14177.88 04-JAN-19:01 1.53
February 0.220783E+10 1.08 14177.88 01-FEB-19:02 1.53
March 0.347167E+10 1.08 14177.88 01-MAR-16:02 1.52
April 0.658516E+10 1.16 14177.88 01-APR-08:62 1.53
May 0.871729E+10 1.28 14177.88 01-MAY-08:62 1.53
June 0.118592E+11 1.41 14177.88 01-JUN-08:61 1.52
July 0.113947E+11 1.39 14177.88 01-JUL-08:61 1.53
August 0.103191E+11 1.35 14177.88 01-AUG-08:61 1.51
September 0.910668E+10 1.29 14177.88 01-SEP-08:61 1.51
October 0.544051E+10 1.13 14177.88 01-OCT-08:61 1.52
November 0.295522E+10 1.08 14177.88 01-NOV-15:02 1.52
December 0.237779E+10 1.08 14177.88 01-DEC-19:01 1.53
           
Annual Sum or Average 0.771497E+11 1.20      
Minimum of Months 0.220783E+10 1.08 14177.88   1.51
Maximum of Months 0.118592E+11 1.41 14177.88   1.53



Table of Contents

Report: FanReportMonthly

For: ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.547424E+09 1.33 1948.23 01-JAN-16:02 1.53
February 0.366838E+09 1.16 1948.23 01-FEB-09:02 1.52
March 0.504958E+09 1.25 1948.23 01-MAR-16:02 1.52
April 0.108405E+10 1.48 1948.23 01-APR-08:62 1.53
May 0.131205E+10 1.50 1948.23 01-MAY-08:62 1.53
June 0.180600E+10 1.51 1948.23 01-JUN-08:61 1.52
July 0.167999E+10 1.49 1948.23 01-JUL-08:61 1.53
August 0.160227E+10 1.48 1948.23 01-AUG-08:61 1.51
September 0.136571E+10 1.47 1948.23 01-SEP-08:61 1.51
October 0.933062E+09 1.42 1948.23 01-OCT-08:61 1.51
November 0.505192E+09 1.30 1948.23 01-NOV-15:02 1.52
December 0.489172E+09 1.22 1948.23 01-DEC-09:02 1.53
           
Annual Sum or Average 0.121967E+11 1.38      
Minimum of Months 0.366838E+09 1.16 1948.23   1.51
Maximum of Months 0.180600E+10 1.51 1948.23   1.53



Table of Contents

Report: FanReportMonthly

For: ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.388807E+09 1.08 1935.55 01-JAN-16:02 1.53
February 0.320757E+09 1.08 1935.55 04-FEB-09:02 1.52
March 0.425351E+09 1.15 1935.55 02-MAR-09:02 1.52
April 0.953216E+09 1.47 1935.55 01-APR-08:62 1.53
May 0.128096E+10 1.50 1935.55 01-MAY-08:62 1.53
June 0.183386E+10 1.51 1935.55 01-JUN-08:61 1.52
July 0.167889E+10 1.49 1935.55 01-JUL-08:61 1.53
August 0.152933E+10 1.48 1935.55 01-AUG-08:61 1.51
September 0.122308E+10 1.46 1935.55 01-SEP-08:61 1.51
October 0.701579E+09 1.30 1935.55 01-OCT-08:61 1.51
November 0.358474E+09 1.10 1935.55 01-NOV-15:02 1.52
December 0.463738E+09 1.08 1935.55 02-DEC-09:01 1.53
           
Annual Sum or Average 0.111580E+11 1.31      
Minimum of Months 0.320757E+09 1.08 1935.55   1.51
Maximum of Months 0.183386E+10 1.51 1935.55   1.53



Table of Contents

Report: FanReportMonthly

For: ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.169067E+09 1.29 598.97 01-JAN-09:02 1.53
February 0.114874E+09 1.15 598.97 01-FEB-16:01 1.53
March 0.154315E+09 1.22 598.97 01-MAR-16:02 1.52
April 0.308726E+09 1.43 598.97 01-APR-15:02 1.53
May 0.366352E+09 1.45 598.97 01-MAY-15:02 1.53
June 0.506842E+09 1.48 598.97 01-JUN-08:61 1.52
July 0.453872E+09 1.47 598.97 01-JUL-08:61 1.53
August 0.445450E+09 1.46 598.97 01-AUG-08:61 1.51
September 0.375663E+09 1.44 598.97 01-SEP-08:61 1.51
October 0.253083E+09 1.37 598.97 01-OCT-08:61 1.51
November 0.155670E+09 1.28 598.97 01-NOV-15:02 1.52
December 0.159558E+09 1.23 598.97 01-DEC-16:01 1.53
           
Annual Sum or Average 0.346347E+10 1.36      
Minimum of Months 0.114874E+09 1.15 598.97   1.51
Maximum of Months 0.506842E+09 1.48 598.97   1.53



Table of Contents

Report: FanReportMonthly

For: ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.135479E+09 1.14 594.52 01-JAN-09:02 1.53
February 0.116491E+09 1.08 594.52 01-FEB-09:02 1.52
March 0.136998E+09 1.15 594.52 02-MAR-16:01 1.52
April 0.277935E+09 1.40 594.52 01-APR-15:02 1.53
May 0.358416E+09 1.45 594.52 01-MAY-15:02 1.53
June 0.515370E+09 1.49 594.52 01-JUN-08:61 1.52
July 0.453162E+09 1.47 594.52 01-JUL-08:61 1.53
August 0.423480E+09 1.46 594.52 01-AUG-08:61 1.51
September 0.338975E+09 1.43 594.52 01-SEP-08:61 1.51
October 0.201147E+09 1.28 594.52 01-OCT-08:61 1.51
November 0.121751E+09 1.15 594.52 01-NOV-15:02 1.52
December 0.170086E+09 1.12 594.52 01-DEC-09:02 1.53
           
Annual Sum or Average 0.324929E+10 1.30      
Minimum of Months 0.116491E+09 1.08 594.52   1.51
Maximum of Months 0.515370E+09 1.49 594.52   1.53



Table of Contents

Report: FanReportMonthly

For: ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.137135E+10 1.41 2691.99 01-JAN-16:02 1.53
February 0.701080E+09 1.29 2691.99 01-FEB-09:02 1.52
March 0.881252E+09 1.30 2691.99 01-MAR-16:02 1.52
April 0.153562E+10 1.43 2691.99 01-APR-15:02 1.53
May 0.163759E+10 1.43 2691.99 01-MAY-15:02 1.53
June 0.216436E+10 1.46 2691.99 01-JUN-08:61 1.52
July 0.214104E+10 1.46 2691.99 01-JUL-08:61 1.53
August 0.220680E+10 1.45 2691.99 01-AUG-08:61 1.51
September 0.215641E+10 1.45 2691.99 01-SEP-08:61 1.51
October 0.173148E+10 1.43 2691.99 01-OCT-08:61 1.51
November 0.122638E+10 1.37 2691.99 01-NOV-15:02 1.52
December 0.111814E+10 1.37 2691.99 01-DEC-09:02 1.53
           
Annual Sum or Average 0.188715E+11 1.40      
Minimum of Months 0.701080E+09 1.29 2691.99   1.51
Maximum of Months 0.220680E+10 1.46 2691.99   1.53



Table of Contents

Report: PumpReportMonthly

For: HEATSYS1 PUMP

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.452441E+09 0.407197E+09 586.46 01-JAN-06:00 527.81 527.81 38.46 0.85
February 0.586854E+09 0.528169E+09 620.21 12-FEB-16:02 558.18 558.18 36.45 0.93
March 0.596524E+09 0.536872E+09 661.76 27-MAR-08:62 595.59 595.59 34.23 1.04
April 0.328861E+09 0.295975E+09 498.62 21-APR-10:40 448.76 448.76 34.30 0.67
May 0.342995E+09 0.308695E+09 473.15 01-MAY-10:40 425.83 425.83 34.96 0.62
June 0.284440E+09 0.255996E+09 446.93 13-JUN-10:40 402.24 402.24 35.14 0.58
July 0.210869E+09 0.189783E+09 447.05 27-JUL-10:40 402.34 402.34 34.02 0.58
August 0.186645E+09 0.167981E+09 442.48 07-AUG-10:40 398.23 398.23 33.09 0.57
September 0.155610E+09 0.140049E+09 385.93 05-SEP-10:40 347.34 347.34 31.94 0.48
October 0.264392E+09 0.237953E+09 485.46 23-OCT-08:04 436.91 436.91 30.48 0.65
November 0.387065E+09 0.348358E+09 544.10 12-NOV-16:05 489.69 489.69 33.42 0.76
December 0.606151E+09 0.545536E+09 613.98 07-DEC-05:00 552.58 552.58 40.21 0.92
                 
Annual Sum or Average 0.440285E+10 0.396256E+10            
Minimum of Months 0.155610E+09 0.140049E+09 385.93   347.34 347.34 30.48 0.48
Maximum of Months 0.606151E+09 0.545536E+09 661.76   595.59 595.59 40.21 1.04



Table of Contents

Report: PumpReportMonthly

For: COOLSYS1 PUMP SECONDARY

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.677533E+10 0.609780E+10 6043.70 31-JAN-16:01 5439.33 5439.33 6.73 17.27
February 0.368660E+10 0.331794E+10 6016.43 18-FEB-16:01 5414.78 5414.78 6.73 17.05
March 0.666330E+10 0.599697E+10 6610.49 14-MAR-18:02 5949.44 5949.44 6.73 23.94
April 0.117749E+11 0.105974E+11 6703.35 15-APR-20:00 6033.02 6033.02 6.73 25.51
May 0.136702E+11 0.123032E+11 6578.39 31-MAY-18:03 5920.55 5920.55 6.73 23.42
June 0.151722E+11 0.136550E+11 8588.82 28-JUN-15:13 7729.94 7729.94 6.73 40.45
July 0.164770E+11 0.148293E+11 8436.19 11-JUL-16:20 7592.57 7592.57 6.73 39.86
August 0.164102E+11 0.147692E+11 8631.42 30-AUG-18:03 7768.27 7768.27 6.73 40.61
September 0.155323E+11 0.139791E+11 7920.47 16-SEP-18:03 7128.42 7128.42 6.73 37.49
October 0.110553E+11 0.994977E+10 6972.34 04-OCT-18:03 6275.11 6275.11 6.73 29.75
November 0.735690E+10 0.662121E+10 6649.84 01-NOV-17:00 5984.86 5984.86 6.73 24.60
December 0.457027E+10 0.411324E+10 5860.75 24-DEC-16:01 5274.68 5274.68 6.73 15.91
                 
Annual Sum or Average 0.129145E+12 0.116230E+12            
Minimum of Months 0.368660E+10 0.331794E+10 5860.75   5274.68 5274.68 6.73 15.91
Maximum of Months 0.164770E+11 0.148293E+11 8631.42   7768.27 7768.27 6.73 40.61



Table of Contents

Report: PumpReportMonthly

For: COOLSYS1 PUMP

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.146115E+11 0.131504E+11 5845.09 01-JAN-00:05 5260.58 5260.58 6.73 40.97
February 0.125839E+11 0.113255E+11 5845.09 01-FEB-00:03 5260.58 5260.58 6.89 40.97
March 0.146224E+11 0.131601E+11 5845.09 01-MAR-00:03 5260.58 5260.58 6.81 40.97
April 0.151435E+11 0.136291E+11 5845.09 01-APR-00:10 5260.58 5260.58 7.11 40.97
May 0.156555E+11 0.140899E+11 5845.09 01-MAY-00:10 5260.58 5260.58 7.99 40.97
June 0.151505E+11 0.136354E+11 5845.09 01-JUN-00:10 5260.58 5260.58 8.75 40.97
July 0.156555E+11 0.140899E+11 5845.09 01-JUL-00:10 5260.58 5260.58 9.03 40.97
August 0.156555E+11 0.140899E+11 5845.09 01-AUG-00:10 5260.58 5260.58 9.18 40.97
September 0.151505E+11 0.136354E+11 5845.09 01-SEP-00:10 5260.58 5260.58 8.83 40.97
October 0.155327E+11 0.139795E+11 5845.09 01-OCT-00:10 5260.58 5260.58 8.74 40.97
November 0.143608E+11 0.129247E+11 5845.09 01-NOV-00:10 5260.58 5260.58 7.55 40.97
December 0.125278E+11 0.112750E+11 5845.09 01-DEC-00:03 5260.58 5260.58 6.80 40.97
                 
Annual Sum or Average 0.176650E+12 0.158985E+12            
Minimum of Months 0.125278E+11 0.112750E+11 5845.09   5260.58 5260.58 6.73 40.97
Maximum of Months 0.156555E+11 0.140899E+11 5845.09   5260.58 5260.58 9.18 40.97



Table of Contents

Report: PumpReportMonthly

For: SWHSYS1 PUMP

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.128314E+09 38494137.67 47.91 01-JAN-00:05 14.37 14.37 50.05 0.37
February 0.115896E+09 34768898.54 47.91 01-FEB-00:03 14.37 14.37 49.92 0.37
March 0.128314E+09 38494137.67 47.91 01-MAR-00:03 14.37 14.37 50.95 0.37
April 0.124175E+09 37252391.29 47.91 01-APR-00:10 14.37 14.37 53.20 0.37
May 0.128314E+09 38494137.67 47.91 01-MAY-00:10 14.37 14.37 54.02 0.37
June 0.124175E+09 37252391.29 47.91 01-JUN-00:10 14.37 14.37 53.80 0.37
July 0.128314E+09 38494137.67 47.91 01-JUL-00:10 14.37 14.37 54.41 0.37
August 0.128314E+09 38494137.67 47.91 01-AUG-00:10 14.37 14.37 54.31 0.37
September 0.124175E+09 37252391.29 47.91 01-SEP-00:10 14.37 14.37 54.77 0.37
October 0.128314E+09 38494137.67 47.91 01-OCT-00:10 14.37 14.37 53.85 0.37
November 0.124175E+09 37252391.29 47.91 01-NOV-00:10 14.37 14.37 53.94 0.37
December 0.128314E+09 38494137.67 47.91 01-DEC-00:03 14.37 14.37 51.24 0.37
                 
Annual Sum or Average 0.151079E+10 0.453237E+09            
Minimum of Months 0.115896E+09 34768898.54 47.91   14.37 14.37 49.92 0.37
Maximum of Months 0.128314E+09 38494137.67 47.91   14.37 14.37 54.77 0.37



Table of Contents

Report: CondLoopDemandReportMonthly

For: HEATSYS1

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:05 39.21 60.00 21149.46 85196.62 02-JAN-09:02
February 0.00 0.00 01-FEB-00:03 25.57 60.00 30746.78 91742.89 12-FEB-16:02
March 0.00 0.00 01-MAR-00:03 30.57 60.00 28128.34 112522.94 27-MAR-08:62
April 0.00 0.00 01-APR-00:10 28.69 60.00 15830.11 77057.88 21-APR-10:35
May 0.00 0.00 01-MAY-00:10 28.25 60.00 15386.40 71829.69 25-MAY-08:04
June 0.00 0.00 01-JUN-00:10 29.39 60.00 12555.34 59930.57 13-JUN-10:40
July 0.00 0.00 01-JUL-00:10 30.35 60.00 9841.05 69026.67 27-JUL-10:35
August 0.00 0.00 01-AUG-00:10 29.23 60.00 8876.79 70349.35 07-AUG-10:35
September 0.00 0.00 01-SEP-00:10 28.75 60.00 7552.03 59392.27 11-SEP-08:04
October 0.00 0.00 01-OCT-00:10 29.28 60.00 12727.70 80872.20 30-OCT-08:04
November 0.00 0.00 01-NOV-00:10 28.22 60.00 18871.31 87116.50 24-NOV-09:02
December 0.00 0.00 01-DEC-00:03 35.12 60.00 27422.68 104064.67 07-DEC-09:02
                 
Annual Sum or Average 0.00         17355.28    
Minimum of Months 0.00 0.00   25.57 60.00 7552.03 59392.27  
Maximum of Months 0.00 0.00   39.21 60.00 30746.78 112522.94  



Table of Contents

Report: CondLoopDemandReportMonthly

For: COOLSYS1

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 128256.59 541851.52 31-JAN-16:01 9.86 6.70 0.00 0.00 01-JAN-00:05
February 57149.99 423376.02 21-FEB-16:01 9.17 6.70 0.00 0.00 01-FEB-00:03
March 126146.59 545987.28 15-MAR-18:01 9.88 6.70 0.00 0.00 01-MAR-00:03
April 295789.88 650129.38 13-APR-18:03 10.49 6.70 0.00 0.00 01-APR-00:10
May 356856.75 681874.99 31-MAY-18:03 10.67 6.70 0.00 0.00 01-MAY-00:10
June 450928.07 786996.67 17-JUN-18:03 11.29 6.70 0.00 0.00 01-JUN-00:10
July 496480.02 916587.32 13-JUL-18:03 12.04 6.70 0.00 0.00 01-JUL-00:10
August 484223.44 840366.78 09-AUG-18:03 11.60 6.70 0.00 0.00 01-AUG-00:10
September 456986.19 799558.91 03-SEP-08:62 11.36 6.70 0.00 0.00 01-SEP-00:10
October 255650.89 765361.92 01-OCT-18:03 11.16 6.70 0.00 0.00 01-OCT-00:10
November 147639.58 611898.39 11-NOV-19:03 10.26 6.70 0.00 0.00 01-NOV-00:10
December 79671.97 524657.79 25-DEC-16:02 9.76 6.70 0.00 0.00 01-DEC-00:03
                 
Annual Sum or Average 279140.78         0.00    
Minimum of Months 57149.99 423376.02   9.17 6.70 0.00 0.00  
Maximum of Months 496480.02 916587.32   12.04 6.70 0.00 0.00  



Table of Contents

Report: CondLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:05 50.05 59.74 23575.60 47628.23 20-JAN-07:10
February 0.00 0.00 01-FEB-00:03 49.92 58.55 23355.36 47503.16 01-FEB-08:00
March 0.00 0.00 01-MAR-00:03 50.95 59.31 22317.61 46192.72 01-MAR-07:10
April 0.00 0.00 01-APR-00:10 53.20 58.87 20652.96 42863.41 03-APR-07:00
May 0.00 0.00 01-MAY-00:10 54.02 59.16 18861.62 39392.81 01-MAY-07:00
June 0.00 0.00 01-JUN-00:10 53.80 58.26 17412.41 35815.96 01-JUN-07:00
July 0.00 0.00 01-JUL-00:10 54.41 58.61 16680.50 33442.36 03-JUL-06:40
August 0.00 0.00 01-AUG-00:10 54.31 58.40 16915.09 34401.73 31-AUG-06:50
September 0.00 0.00 01-SEP-00:10 54.77 59.26 17995.30 37263.94 29-SEP-06:10
October 0.00 0.00 01-OCT-00:10 53.85 59.54 19651.28 41135.10 31-OCT-07:00
November 0.00 0.00 01-NOV-00:10 53.94 59.59 21443.99 44618.68 30-NOV-08:00
December 0.00 0.00 01-DEC-00:03 51.24 59.34 22877.13 46933.69 29-DEC-08:00
                 
Annual Sum or Average 0.00         20126.94    
Minimum of Months 0.00 0.00   49.92 58.26 16680.50 33442.36  
Maximum of Months 0.00 0.00   54.77 59.74 23575.60 47628.23  



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: VAV WITH REHEAT

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.536497E+11 0.00 0.214851E+12 0.147825E+12 0.00 0.00
February 0.707076E+11 0.00 0.746772E+11 0.133512E+12 0.00 0.00
March 0.727942E+11 0.00 0.234339E+12 0.147826E+12 0.00 0.00
April 0.412742E+11 0.00 0.542470E+12 0.143085E+12 0.00 0.00
May 0.415104E+11 0.00 0.686613E+12 0.147861E+12 0.00 0.00
June 0.328298E+11 0.00 0.826783E+12 0.143104E+12 0.00 0.00
July 0.265652E+11 0.00 0.962945E+12 0.147869E+12 0.00 0.00
August 0.239425E+11 0.00 0.938036E+12 0.147866E+12 0.00 0.00
September 0.196988E+11 0.00 0.856449E+12 0.143089E+12 0.00 0.00
October 0.335921E+11 0.00 0.472406E+12 0.147843E+12 0.00 0.00
November 0.466994E+11 0.00 0.254917E+12 0.143056E+12 0.00 0.00
December 0.648817E+11 0.00 0.125691E+12 0.147817E+12 0.00 0.00
             
Annual Sum or Average 0.528145E+12 0.00 0.619018E+13 0.174075E+13 0.00 0.00
Minimum of Months 0.196988E+11 0.00 0.746772E+11 0.133512E+12 0.00 0.00
Maximum of Months 0.727942E+11 0.00 0.962945E+12 0.147869E+12 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: FLR_3_DOAS

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 31831.69 0.00 0.199430E+11 0.587890E+10 0.00 0.00
February 20405.45 0.00 0.520636E+10 0.530997E+10 0.00 0.00
March 21816.41 0.00 0.213396E+11 0.587890E+10 0.00 0.00
April 60989.00 0.00 0.507919E+11 0.568926E+10 0.00 0.00
May 71521.74 0.00 0.643393E+11 0.587890E+10 0.00 0.00
June 83493.92 0.00 0.748333E+11 0.568926E+10 0.00 0.00
July 36308.54 0.00 0.880898E+11 0.587890E+10 0.00 0.00
August 34367.06 0.00 0.873130E+11 0.587890E+10 0.00 0.00
September 33576.99 0.00 0.816009E+11 0.568926E+10 0.00 0.00
October 36798.95 0.00 0.443094E+11 0.587890E+10 0.00 0.00
November 32202.85 0.00 0.228498E+11 0.568926E+10 0.00 0.00
December 13073.82 0.00 0.112014E+11 0.587890E+10 0.00 0.00
             
Annual Sum or Average 476386.43 0.00 0.571818E+12 0.692193E+11 0.00 0.00
Minimum of Months 13073.82 0.00 0.520636E+10 0.530997E+10 0.00 0.00
Maximum of Months 83493.92 0.00 0.880898E+11 0.587890E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: VAV WITH REHEAT

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.147825E+12 0.214851E+12 0.536497E+11 0.157293E+12 0.119760E+11 0.00 0.00 0.00
February 0.133512E+12 0.746772E+11 0.707076E+11 0.147292E+12 0.00 0.00 0.00 0.00
March 0.147826E+12 0.234339E+12 0.727942E+11 0.135368E+12 0.172997E+11 0.00 0.00 0.00
April 0.143085E+12 0.542470E+12 0.412742E+11 0.133973E+11 0.135899E+12 0.00 0.00 0.00
May 0.147861E+12 0.686613E+12 0.415104E+11 0.119698E+11 0.216705E+12 0.00 0.00 0.00
June 0.143104E+12 0.826783E+12 0.328298E+11 0.118797E+11 0.376146E+12 0.00 0.00 0.00
July 0.147869E+12 0.962945E+12 0.265652E+11 0.313188E+10 0.501432E+12 0.00 0.00 0.00
August 0.147866E+12 0.938036E+12 0.239425E+11 0.361546E+10 0.449608E+12 0.00 0.00 0.00
September 0.143089E+12 0.856449E+12 0.196988E+11 0.482091E+10 0.357498E+12 0.00 0.00 0.00
October 0.147843E+12 0.472406E+12 0.335921E+11 0.402919E+11 0.108486E+12 0.00 0.00 0.00
November 0.143056E+12 0.254917E+12 0.466994E+11 0.118311E+12 0.156081E+11 0.00 0.00 0.00
December 0.147817E+12 0.125691E+12 0.648817E+11 0.290518E+12 0.418750E+10 0.00 0.00 0.00
                 
Annual Sum or Average 0.174075E+13 0.619018E+13 0.528145E+12 0.937890E+12 0.219485E+13 0.00 0.00 0.00
Minimum of Months 0.133512E+12 0.746772E+11 0.196988E+11 0.313188E+10 0.00 0.00 0.00 0.00
Maximum of Months 0.147869E+12 0.962945E+12 0.727942E+11 0.290518E+12 0.501432E+12 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: FLR_3_DOAS

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.587890E+10 0.199430E+11 31831.69 0.169873E+11 0.255173E+09 0.00 0.00 0.00
February 0.530997E+10 0.520636E+10 20405.45 0.162783E+11 0.00 0.00 0.00 0.00
March 0.587890E+10 0.213396E+11 21816.41 0.144626E+11 0.675347E+09 0.00 0.00 0.00
April 0.568926E+10 0.507919E+11 60989.00 0.143052E+10 0.902320E+10 0.00 0.00 0.00
May 0.587890E+10 0.643393E+11 71521.74 0.676762E+09 0.156718E+11 0.00 0.00 0.00
June 0.568926E+10 0.748333E+11 83493.92 0.589387E+09 0.305879E+11 0.00 0.00 0.00
July 0.587890E+10 0.880898E+11 36308.54 0.199540E+09 0.503505E+11 0.00 0.00 0.00
August 0.587890E+10 0.873130E+11 34367.06 0.152401E+09 0.461163E+11 0.00 0.00 0.00
September 0.568926E+10 0.816009E+11 33576.99 0.153188E+09 0.355892E+11 0.00 0.00 0.00
October 0.587890E+10 0.443094E+11 36798.95 0.443909E+10 0.941780E+10 0.00 0.00 0.00
November 0.568926E+10 0.228498E+11 32202.85 0.129672E+11 0.603826E+09 0.00 0.00 0.00
December 0.587890E+10 0.112014E+11 13073.82 0.291814E+11 0.111267E+09 0.00 0.00 0.00
                 
Annual Sum or Average 0.692193E+11 0.571818E+12 476386.43 0.975177E+11 0.198402E+12 0.00 0.00 0.00
Minimum of Months 0.530997E+10 0.520636E+10 13073.82 0.152401E+09 0.00 0.00 0.00 0.00
Maximum of Months 0.587890E+10 0.880898E+11 83493.92 0.291814E+11 0.503505E+11 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: VAV WITH REHEAT

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.147825E+12 0.536497E+11 0.214851E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.133512E+12 0.707076E+11 0.746772E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.147826E+12 0.727942E+11 0.234339E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.143085E+12 0.412742E+11 0.542470E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.147861E+12 0.415104E+11 0.686613E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.143104E+12 0.328298E+11 0.826783E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.147869E+12 0.265652E+11 0.962945E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.147866E+12 0.239425E+11 0.938036E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.143089E+12 0.196988E+11 0.856449E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.147843E+12 0.335921E+11 0.472406E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.143056E+12 0.466994E+11 0.254917E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.147817E+12 0.648817E+11 0.125691E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.174075E+13 0.528145E+12 0.619018E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.133512E+12 0.196988E+11 0.746772E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.147869E+12 0.727942E+11 0.962945E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: FLR_3_DOAS

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.587890E+10 31831.69 0.199430E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.530997E+10 20405.45 0.520636E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.587890E+10 21816.41 0.213396E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.568926E+10 60989.00 0.507919E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.587890E+10 71521.74 0.643393E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.568926E+10 83493.92 0.748333E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.587890E+10 36308.54 0.880898E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.587890E+10 34367.06 0.873130E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.568926E+10 33576.99 0.816009E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.587890E+10 36798.95 0.443094E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.568926E+10 32202.85 0.228498E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.587890E+10 13073.82 0.112014E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.692193E+11 476386.43 0.571818E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.530997E+10 13073.82 0.520636E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.587890E+10 83493.92 0.880898E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.520043E+11 0.00 0.00 0.00 0.387564E+09 0.00 0.00 0.00 2.14
February 0.597824E+11 0.00 0.00 0.00 919142.42 0.00 0.00 0.00 2.17
March 0.502260E+11 0.00 1457000.78 0.00 0.641578E+09 315005.41 0.00 5587.07 2.16
April 0.204233E+11 0.00 15818395.25 0.00 0.576926E+10 0.00 0.00 161289.81 2.15
May 0.112800E+11 0.00 0.182529E+09 0.00 0.932011E+10 0.00 0.00 1789020.52 2.15
June 0.296234E+10 0.00 0.179606E+09 0.00 0.164825E+11 0.00 0.00 1208253.11 2.16
July 0.116714E+10 0.00 0.00 0.00 0.282481E+11 0.00 0.00 0.00 2.16
August 0.103422E+10 0.00 0.00 0.00 0.254855E+11 0.00 0.00 0.00 2.17
September 0.293416E+10 0.00 0.00 0.00 0.216237E+11 0.00 0.00 0.00 2.17
October 0.301406E+11 0.00 0.00 0.00 0.519863E+10 0.00 0.00 0.00 2.16
November 0.467834E+11 0.00 0.00 0.00 0.152159E+10 0.00 0.00 0.00 2.16
December 0.614891E+11 0.00 0.00 0.00 0.135037E+09 0.00 0.00 0.00 2.15
                   
Annual Sum or Average 0.340227E+12 0.00 0.379410E+09 0.00 0.114814E+12 315005.41 0.00 3164150.52 2.16
Minimum of Months 0.103422E+10 0.00 0.00 0.00 919142.42 0.00 0.00 0.00 2.14
Maximum of Months 0.614891E+11 0.00 0.182529E+09 0.00 0.282481E+11 315005.41 0.00 1789020.52 2.17



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.701423E+10 40871762.67 0.00 161266.98 12986328.88 0.130241E+09 82172456.27 0.00 5.41
February 0.813270E+10 0.00 0.00 0.00 127729.12 0.175004E+09 0.00 0.00 5.47
March 0.651570E+10 960803.37 0.00 656.10 88399626.40 0.463569E+09 459120.29 0.00 5.44
April 0.283813E+10 72190540.36 0.00 0.00 0.731758E+09 0.00 0.00 0.00 5.43
May 0.156754E+10 0.00 0.00 0.00 0.132079E+10 0.00 0.00 0.00 5.43
June 0.411662E+09 0.106738E+09 0.00 0.00 0.220889E+10 0.00 0.00 0.00 5.45
July 0.162192E+09 24594288.17 0.00 0.00 0.390091E+10 0.00 0.00 0.00 5.46
August 0.143721E+09 0.340535E+09 0.00 0.00 0.320108E+10 0.00 0.00 0.00 5.47
September 0.407747E+09 0.415092E+09 0.00 0.00 0.258985E+10 0.00 0.00 0.00 5.47
October 0.418089E+10 0.263386E+09 0.00 8841.58 0.459044E+09 6763891.87 845894.06 0.00 5.45
November 0.633907E+10 44514600.51 0.00 85564.27 0.166934E+09 0.101545E+09 60581230.16 0.00 5.44
December 0.755224E+10 15367433.36 0.00 73601.58 3398071.04 0.932540E+09 60023168.79 0.00 5.42
                   
Annual Sum or Average 0.452658E+11 0.132425E+10 0.00 329930.51 0.146842E+11 0.180966E+10 0.204082E+09 0.00 5.45
Minimum of Months 0.143721E+09 0.00 0.00 0.00 127729.12 0.00 0.00 0.00 5.41
Maximum of Months 0.813270E+10 0.415092E+09 0.00 161266.98 0.390091E+10 0.932540E+09 82172456.27 0.00 5.47



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.512088E+10 0.00 0.00 0.00 38163618.29 0.00 0.00 0.00 3.31
February 0.588680E+10 0.00 0.00 0.00 90508.32 0.00 0.00 0.00 3.34
March 0.494581E+10 0.00 0.00 0.00 63320426.59 0.00 0.00 0.00 3.33
April 0.201109E+10 0.00 0.00 0.00 0.569674E+09 0.00 0.00 0.00 3.32
May 0.111075E+10 0.00 0.00 0.00 0.935904E+09 0.00 0.00 0.00 3.32
June 0.291702E+09 0.00 0.00 0.00 0.164085E+10 0.00 0.00 0.00 3.34
July 0.114929E+09 0.00 0.00 0.00 0.278160E+10 0.00 0.00 0.00 3.34
August 0.101840E+09 0.00 0.00 0.00 0.250957E+10 0.00 0.00 0.00 3.35
September 0.288927E+09 0.00 0.00 0.00 0.212929E+10 0.00 0.00 0.00 3.35
October 0.296796E+10 0.00 0.00 0.00 0.511911E+09 0.00 0.00 0.00 3.33
November 0.460678E+10 0.00 0.00 0.00 0.149831E+09 0.00 0.00 0.00 3.33
December 0.605486E+10 0.00 0.00 0.00 13297157.89 0.00 0.00 0.00 3.32
                   
Annual Sum or Average 0.335023E+11 0.00 0.00 0.00 0.113435E+11 0.00 0.00 0.00 3.33
Minimum of Months 0.101840E+09 0.00 0.00 0.00 90508.32 0.00 0.00 0.00 3.31
Maximum of Months 0.605486E+10 0.00 0.00 0.00 0.278160E+10 0.00 0.00 0.00 3.35



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.558218E+10 0.00 0.00 0.00 42104927.82 67556789.07 0.00 0.00 1.73
February 0.649475E+10 0.00 0.00 0.00 99855.48 0.00 0.00 0.00 1.74
March 0.544343E+10 0.00 0.00 0.00 69859780.35 13152740.53 0.00 0.00 1.74
April 0.221878E+10 0.00 0.00 0.00 0.628507E+09 0.00 0.00 0.00 1.73
May 0.122546E+10 0.00 0.00 0.00 0.103256E+10 0.00 0.00 0.00 1.73
June 0.321828E+09 0.00 0.00 0.00 0.181030E+10 0.00 0.00 0.00 1.74
July 0.126798E+09 0.00 0.00 0.00 0.306886E+10 0.00 0.00 0.00 1.74
August 0.112357E+09 0.00 0.00 0.00 0.276874E+10 0.00 0.00 0.00 1.75
September 0.318766E+09 0.00 0.00 0.00 0.234919E+10 0.00 0.00 0.00 1.75
October 0.327447E+10 0.00 0.00 0.00 0.564778E+09 0.00 0.00 0.00 1.74
November 0.507507E+10 0.00 0.00 0.00 0.165305E+09 7467818.39 0.00 0.00 1.74
December 0.642913E+10 0.00 0.00 0.00 14670408.58 0.251044E+09 0.00 0.00 1.73
                   
Annual Sum or Average 0.366230E+11 0.00 0.00 0.00 0.125150E+11 0.339222E+09 0.00 0.00 1.74
Minimum of Months 0.112357E+09 0.00 0.00 0.00 99855.48 0.00 0.00 0.00 1.73
Maximum of Months 0.649475E+10 0.00 0.00 0.00 0.306886E+10 0.251044E+09 0.00 0.00 1.75



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.273927E+10 0.00 0.00 0.00 21330549.91 0.122913E+09 0.00 0.00 1.52
February 0.326897E+10 0.00 0.00 0.00 50587.24 21302490.52 0.00 0.00 1.53
March 0.264452E+10 0.00 0.00 0.00 35391285.75 0.119810E+09 0.00 0.00 1.53
April 0.112404E+10 0.00 0.00 0.00 0.318405E+09 0.00 0.00 0.00 1.52
May 0.620825E+09 0.00 0.00 0.00 0.523099E+09 0.00 0.00 0.00 1.52
June 0.163039E+09 0.00 0.00 0.00 0.917107E+09 0.00 0.00 0.00 1.53
July 64236296.61 0.00 0.00 0.00 0.155470E+10 0.00 0.00 0.00 1.53
August 56920703.13 0.00 0.00 0.00 0.140266E+10 0.00 0.00 0.00 1.53
September 0.161488E+09 0.00 0.00 0.00 0.119011E+10 0.00 0.00 0.00 1.53
October 0.165886E+10 0.00 0.00 0.00 0.286119E+09 0.00 0.00 0.00 1.53
November 0.249409E+10 0.00 0.00 0.00 83744233.22 80743367.51 0.00 0.00 1.52
December 0.270826E+10 0.00 0.00 0.00 7432096.40 0.675942E+09 0.00 0.00 1.52
                   
Annual Sum or Average 0.177045E+11 0.00 0.00 0.00 0.634015E+10 0.102071E+10 0.00 0.00 1.53
Minimum of Months 56920703.13 0.00 0.00 0.00 50587.24 0.00 0.00 0.00 1.52
Maximum of Months 0.326897E+10 0.00 0.00 0.00 0.155470E+10 0.675942E+09 0.00 0.00 1.53



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.728999E+09 0.472001E+09 0.00 64265600.87 19424562.86 0.00 0.651735E+11 0.00 42.47
February 0.971620E+09 1165458.87 0.00 59987175.54 0.00 0.00 0.747971E+11 0.00 42.92
March 0.444436E+09 0.784992E+09 0.00 62953015.18 30373506.90 0.00 0.631997E+11 0.00 42.75
April 0.143259E+09 0.698880E+10 0.00 37605690.45 0.347270E+09 0.00 0.257188E+11 0.00 42.60
May 32430695.89 0.115660E+11 0.00 27289126.52 0.486403E+09 0.00 0.142434E+11 0.00 42.61
June 4228382.57 0.202891E+11 0.00 13490322.37 0.840402E+09 0.00 0.373848E+10 0.00 42.78
July 1047590.21 0.346496E+11 0.00 5210876.91 0.117039E+10 0.00 0.147366E+10 0.00 42.84
August 0.00 0.312521E+11 0.00 6292570.94 0.106567E+10 0.00 0.130508E+10 0.00 42.90
September 578716.91 0.265436E+11 0.00 12003232.13 0.876700E+09 0.00 0.370792E+10 0.00 42.91
October 0.338243E+09 0.631202E+10 0.00 48701734.21 0.280020E+09 0.00 0.378422E+11 0.00 42.73
November 0.686376E+09 0.188048E+10 0.00 58407981.18 48867597.66 0.00 0.586001E+11 0.00 42.69
December 0.108511E+10 0.166473E+09 0.00 64516830.37 4752522.39 0.00 0.768455E+11 0.00 42.57
                   
Annual Sum or Average 0.443633E+10 0.140906E+12 0.00 0.460724E+09 0.517027E+10 0.00 0.426646E+12 0.00 42.73
Minimum of Months 0.00 1165458.87 0.00 5210876.91 0.00 0.00 0.130508E+10 0.00 42.47
Maximum of Months 0.108511E+10 0.346496E+11 0.00 64516830.37 0.117039E+10 0.00 0.768455E+11 0.00 42.92



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.274962E+11 0.188785E+09 0.00 1255189.40 33612550.92 0.00 0.234436E+10 0.00 7.94
February 0.336913E+11 0.00 0.00 73358.98 527435.11 0.00 0.613801E+09 0.00 8.02
March 0.281750E+11 45486737.51 0.00 125485.04 0.323512E+09 0.00 0.646420E+09 0.00 7.99
April 0.981343E+10 0.855315E+09 0.00 1067670.37 0.246445E+10 0.00 0.190506E+10 0.00 7.97
May 0.479396E+10 0.436465E+09 0.00 1280375.06 0.501750E+10 0.00 0.167763E+10 0.00 7.97
June 0.533355E+09 0.244363E+10 0.00 2036889.29 0.711836E+10 0.00 0.116450E+10 0.00 8.01
July 0.318166E+09 0.500466E+10 0.00 764989.22 0.112050E+11 0.00 0.350813E+09 0.00 8.02
August 0.183277E+09 0.539486E+10 0.00 1053938.42 0.922960E+10 0.00 0.409139E+09 0.00 8.03
September 0.722197E+09 0.499107E+10 0.00 1304802.48 0.741733E+10 0.00 0.960216E+09 0.00 8.03
October 0.146939E+11 0.171340E+10 0.00 1378237.38 0.126975E+10 0.00 0.260040E+10 0.00 8.00
November 0.243175E+11 0.202550E+09 0.00 911218.53 0.670588E+09 0.00 0.252745E+10 0.00 7.98
December 0.340021E+11 64753624.99 0.00 735677.53 12735248.05 0.00 0.128176E+10 0.00 7.96
                   
Annual Sum or Average 0.178740E+12 0.213410E+11 0.00 11987831.70 0.447630E+11 0.00 0.164815E+11 0.00 7.99
Minimum of Months 0.183277E+09 0.00 0.00 73358.98 527435.11 0.00 0.350813E+09 0.00 7.94
Maximum of Months 0.340021E+11 0.539486E+10 0.00 2036889.29 0.112050E+11 0.00 0.260040E+10 0.00 8.03



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.976191E+11 0.00 0.00 0.00 0.727511E+09 0.00 0.00 0.00 3.75
February 0.112220E+12 0.00 0.00 0.00 1725355.17 0.00 0.00 0.00 3.79
March 0.942817E+11 0.00 0.00 0.00 0.120707E+10 0.00 0.00 0.00 3.77
April 0.383344E+11 359726.28 0.00 2518.20 0.108593E+11 0.00 2846831.64 0.00 3.76
May 0.211717E+11 1431584.07 0.00 521.93 0.178397E+11 0.00 2504338.36 0.00 3.77
June 0.552576E+10 0.570582E+09 0.00 40791.40 0.307088E+11 0.00 34905112.21 0.00 3.78
July 0.219042E+10 0.560898E+09 0.00 6301.39 0.524646E+11 0.00 448952.25 0.00 3.79
August 0.193524E+10 0.279317E+09 0.00 28124.26 0.475605E+11 0.00 6102672.23 0.00 3.79
September 0.548167E+10 0.303866E+09 0.00 36661.44 0.402867E+11 0.00 26098796.31 0.00 3.79
October 0.565650E+11 62572825.10 0.00 1610.74 0.969596E+10 0.00 13006261.39 0.00 3.77
November 0.878188E+11 0.00 0.00 0.00 0.285622E+10 0.00 0.00 0.00 3.77
December 0.115423E+12 0.00 0.00 0.00 0.253483E+09 0.00 0.00 0.00 3.76
                   
Annual Sum or Average 0.638567E+12 0.177903E+10 0.00 116529.36 0.214461E+12 0.00 85912964.38 0.00 3.77
Minimum of Months 0.193524E+10 0.00 0.00 0.00 1725355.17 0.00 0.00 0.00 3.75
Maximum of Months 0.115423E+12 0.570582E+09 0.00 40791.40 0.524646E+11 0.00 34905112.21 0.00 3.79



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.157418E+09 878927.88 10400.94 8487657.17 188364.08 0.307092E+09 0.736173E+09 1543.40 0.47
February 0.305628E+09 94664.05 0.00 4002890.60 0.00 0.459164E+09 0.565403E+09 0.00 0.48
March 0.212019E+09 3043356.23 11434.42 6652582.34 335439.50 0.315570E+09 0.630725E+09 1468.13 0.47
April 40886054.75 56390319.69 3264.88 8831448.46 1719164.34 1247011.02 0.465871E+09 5391.38 0.47
May 8396905.35 0.103462E+09 18647.46 6930753.76 2780667.31 96365.20 0.279351E+09 9051.40 0.47
June 408010.75 0.231220E+09 37285.87 4918644.72 4543477.31 0.00 67313403.67 3584.59 0.47
July 160169.32 0.644899E+09 337588.89 1325608.35 22172834.29 0.00 28444806.14 18069.33 0.47
August 601231.07 0.613188E+09 338908.73 1402101.37 25251691.87 0.00 17028357.49 24145.60 0.47
September 1928187.83 0.503815E+09 344570.63 2315993.92 24476234.23 2500.18 39423636.75 30724.51 0.48
October 85819228.38 0.102569E+09 70652.93 7891166.90 4443240.20 83828140.56 0.525403E+09 10559.68 0.47
November 0.141013E+09 10631907.94 53246.62 7493755.99 6864856.26 0.217339E+09 0.703178E+09 4948.07 0.47
December 0.238927E+09 294075.26 0.00 4991951.88 510948.19 0.548402E+09 0.594655E+09 0.00 0.47
                   
Annual Sum or Average 0.119320E+10 0.227049E+10 1226001.39 65244555.46 93286917.59 0.193274E+10 0.465297E+10 109486.08 0.47
Minimum of Months 160169.32 94664.05 0.00 1325608.35 0.00 0.00 17028357.49 0.00 0.47
Maximum of Months 0.305628E+09 0.644899E+09 344570.63 8831448.46 25251691.87 0.548402E+09 0.736173E+09 30724.51 0.48



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.204168E+09 616365.10 9607.10 3856911.24 450801.82 0.560891E+09 0.440113E+09 2335.84 0.47
February 0.356677E+09 94652.96 0.00 1872686.17 0.00 0.653086E+09 0.322406E+09 0.00 0.48
March 0.234943E+09 2709224.27 9081.09 4761948.40 669175.58 0.409876E+09 0.515250E+09 3819.95 0.47
April 44465733.96 55693431.37 5417.83 7963602.47 2405354.77 3898895.67 0.460446E+09 7126.93 0.47
May 8400534.58 0.103303E+09 19045.25 6853962.24 2927818.43 97732.93 0.279388E+09 8650.37 0.47
June 351905.23 0.231431E+09 4154.62 5036324.61 4339681.33 0.00 67243318.45 1451.77 0.47
July 150475.48 0.645158E+09 332012.52 1348176.65 21842670.16 0.00 28428424.87 17071.67 0.47
August 601160.63 0.611626E+09 355003.05 1346229.89 26720900.76 0.00 17082069.58 25892.02 0.47
September 1973677.15 0.498731E+09 339158.11 2159749.69 29497319.86 2892.84 39528882.39 36809.43 0.48
October 0.103415E+09 98652309.31 78021.96 5679503.73 8336761.12 0.157345E+09 0.436420E+09 13545.30 0.47
November 0.196925E+09 9850435.07 59743.18 3759810.81 7635201.68 0.400450E+09 0.467765E+09 7522.15 0.47
December 0.297325E+09 141528.70 0.00 1660917.56 663400.42 0.831854E+09 0.255973E+09 0.00 0.47
                   
Annual Sum or Average 0.144940E+10 0.225801E+10 1211244.70 46299823.46 0.105489E+09 0.301750E+10 0.333004E+10 124225.44 0.47
Minimum of Months 150475.48 94652.96 0.00 1346229.89 0.00 0.00 17082069.58 0.00 0.47
Maximum of Months 0.356677E+09 0.645158E+09 355003.05 7963602.47 29497319.86 0.831854E+09 0.515250E+09 36809.43 0.48



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.356064E+10 14633476.35 0.00 0.140575E+09 0.00 0.00 0.126940E+11 0.00 0.54
February 0.705178E+10 1283559.57 0.00 61779214.41 0.00 0.00 0.109770E+11 0.00 0.54
March 0.615527E+10 45988386.77 0.00 66229721.50 0.00 0.00 0.957440E+10 0.00 0.54
April 0.810813E+09 0.788030E+09 0.00 65432636.98 0.00 0.00 0.613158E+10 0.00 0.54
May 0.192303E+09 0.144094E+10 0.00 47095069.03 0.00 0.00 0.375748E+10 0.00 0.54
June 0.00 0.319729E+10 0.00 30215413.33 0.00 0.00 0.954719E+09 0.00 0.54
July 0.00 0.904972E+10 0.00 8468516.67 0.00 0.00 0.397363E+09 0.00 0.54
August 0.00 0.865811E+10 0.00 8082982.15 3480730.93 0.00 0.249970E+09 0.00 0.54
September 16150490.93 0.716824E+10 0.00 17122810.46 0.00 0.00 0.558857E+09 0.00 0.54
October 0.149205E+10 0.145209E+10 0.00 84071525.84 0.00 0.00 0.795514E+10 0.00 0.54
November 0.327392E+10 0.227405E+09 0.00 0.108992E+09 10624631.32 0.00 0.111121E+11 0.00 0.54
December 0.608099E+10 10915395.93 0.00 0.106972E+09 0.00 0.00 0.126182E+11 0.00 0.54
                   
Annual Sum or Average 0.286339E+11 0.320546E+11 0.00 0.745037E+09 14105362.26 0.00 0.769808E+11 0.00 0.54
Minimum of Months 0.00 1283559.57 0.00 8082982.15 0.00 0.00 0.249970E+09 0.00 0.54
Maximum of Months 0.705178E+10 0.904972E+10 0.00 0.140575E+09 10624631.32 0.00 0.126940E+11 0.00 0.54



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.288782E+10 4446426.08 171738.95 59353954.69 10009267.02 0.388782E+09 0.130638E+11 10045.80 0.53
February 0.494940E+10 1283910.56 0.00 48742874.52 0.00 0.117497E+09 0.129798E+11 0.00 0.54
March 0.330791E+10 24928427.09 170496.02 71795946.98 20798327.83 0.230509E+09 0.121900E+11 103711.27 0.54
April 0.655377E+09 0.620373E+09 542191.07 80658817.95 0.167134E+09 5718178.66 0.626798E+10 195886.99 0.54
May 0.128754E+09 0.129547E+10 303404.89 70180880.97 0.145464E+09 454780.99 0.379859E+10 91823.10 0.54
June 7270549.97 0.301687E+10 40652.01 46156893.56 0.181241E+09 0.00 0.931776E+09 11557.57 0.54
July 2767428.06 0.842643E+10 810838.85 12246422.78 0.624946E+09 0.00 0.390929E+09 14680.13 0.54
August 8154383.32 0.794063E+10 1747054.69 12133527.30 0.721458E+09 436648.95 0.237399E+09 118211.48 0.54
September 28109442.72 0.639781E+10 1384353.36 22072376.21 0.770829E+09 18841.29 0.542092E+09 174004.50 0.54
October 0.145596E+10 0.118214E+10 1039876.28 71917835.76 0.269041E+09 20219813.26 0.798577E+10 260053.58 0.54
November 0.283720E+10 0.116802E+09 970945.12 57406415.72 0.120220E+09 0.259829E+09 0.113445E+11 101292.43 0.54
December 0.408522E+10 759182.51 26305.23 39100228.11 10117342.45 0.185573E+10 0.128312E+11 15550.53 0.54
                   
Annual Sum or Average 0.203539E+11 0.290279E+11 7207856.48 0.591766E+09 0.304126E+10 0.287919E+10 0.825640E+11 1096817.38 0.54
Minimum of Months 2767428.06 759182.51 0.00 12133527.30 0.00 0.00 0.237399E+09 0.00 0.53
Maximum of Months 0.494940E+10 0.842643E+10 1747054.69 80658817.95 0.770829E+09 0.185573E+10 0.130638E+11 260053.58 0.54



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.128034E+09 799579.68 9501.96 8857742.91 267712.28 0.326315E+09 0.745964E+09 2442.38 0.47
February 0.263192E+09 94664.05 0.00 4713224.81 0.00 0.430493E+09 0.635800E+09 0.00 0.48
March 0.168174E+09 3064895.86 10691.62 7208711.59 311260.78 0.298817E+09 0.690767E+09 4850.03 0.47
April 15338450.44 56719286.55 3802.55 10166949.40 1393301.62 2985920.13 0.488344E+09 1749.57 0.47
May 2401762.89 0.104125E+09 0.00 8095396.99 2145975.79 2214.83 0.284275E+09 0.00 0.47
June 85941.27 0.233106E+09 0.00 5426141.63 2697663.76 0.00 67127976.24 0.00 0.47
July 51830.47 0.656589E+09 0.00 1416010.90 10838582.63 0.00 28462742.43 0.00 0.47
August 568768.23 0.625559E+09 18347.97 1340459.63 13224794.88 0.00 17122462.09 693.11 0.47
September 1028318.09 0.513281E+09 106077.48 2342215.07 15273534.45 0.00 40299785.52 5776.40 0.48
October 54605901.77 0.104494E+09 22713.76 8739628.82 2574157.25 86746591.42 0.552850E+09 2739.06 0.47
November 0.123059E+09 10272504.26 60335.71 7579334.96 7217062.05 0.254479E+09 0.683908E+09 5056.88 0.47
December 0.253094E+09 294075.26 0.00 5339567.27 510948.19 0.539394E+09 0.589148E+09 0.00 0.47
                   
Annual Sum or Average 0.100963E+10 0.230840E+10 231471.04 71225383.96 56454993.69 0.193923E+10 0.482407E+10 23307.43 0.47
Minimum of Months 51830.47 94664.05 0.00 1340459.63 0.00 0.00 17122462.09 0.00 0.47
Maximum of Months 0.263192E+09 0.656589E+09 106077.48 10166949.40 15273534.45 0.539394E+09 0.745964E+09 5776.40 0.48



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.211978E+09 464757.29 6756.04 3553776.69 601808.69 0.539466E+09 0.454031E+09 5787.84 0.47
February 0.363239E+09 94652.96 0.00 2117097.17 0.00 0.545581E+09 0.423105E+09 0.00 0.48
March 0.232455E+09 2848029.50 8034.48 5047948.82 526959.46 0.359475E+09 0.567852E+09 8277.45 0.47
April 17290067.89 56364886.78 16127.76 9249850.16 1726607.41 6008162.87 0.484227E+09 3708.95 0.47
May 2353418.76 0.104074E+09 6175.19 8032055.14 2177731.77 2214.57 0.284353E+09 38.05 0.47
June 79858.09 0.233156E+09 0.00 5527208.57 2620142.16 0.00 67024481.64 0.00 0.47
July 47764.49 0.656688E+09 0.00 1439437.30 10661222.61 0.00 28439875.21 0.00 0.47
August 571208.34 0.624995E+09 18347.08 1282952.15 13713005.68 0.00 17175299.60 691.77 0.47
September 1084430.35 0.511652E+09 149856.20 2180732.05 16793757.15 0.00 40400039.67 8164.94 0.48
October 98078505.34 0.103542E+09 31822.49 6223238.86 3497998.87 0.144384E+09 0.454174E+09 8981.30 0.47
November 0.208210E+09 10082283.90 66536.11 3477300.67 7389554.78 0.397569E+09 0.459643E+09 14527.28 0.47
December 0.300803E+09 55968.75 708.57 1549430.25 745874.67 0.785784E+09 0.298678E+09 2377.14 0.47
                   
Annual Sum or Average 0.143619E+10 0.230402E+10 304363.91 49681027.83 60454663.26 0.277827E+10 0.357910E+10 52554.73 0.47
Minimum of Months 47764.49 55968.75 0.00 1282952.15 0.00 0.00 17175299.60 0.00 0.47
Maximum of Months 0.363239E+09 0.656688E+09 149856.20 9249850.16 16793757.15 0.785784E+09 0.567852E+09 14527.28 0.48



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.253684E+11 0.00 0.00 0.00 0.189059E+09 0.00 0.00 0.00 1.06
February 0.291627E+11 0.00 0.00 0.00 448370.92 0.00 0.00 0.00 1.07
March 0.245011E+11 0.00 0.00 0.00 0.313684E+09 0.00 0.00 0.00 1.07
April 0.996276E+10 0.00 0.00 0.00 0.282212E+10 0.00 0.00 0.00 1.07
May 0.550257E+10 0.00 0.00 0.00 0.463640E+10 0.00 0.00 0.00 1.07
June 0.144507E+10 0.00 0.00 0.00 0.812862E+10 0.00 0.00 0.00 1.08
July 0.569347E+09 0.00 0.00 0.00 0.137798E+11 0.00 0.00 0.00 1.08
August 0.504506E+09 0.00 0.00 0.00 0.124322E+11 0.00 0.00 0.00 1.08
September 0.143132E+10 0.00 0.00 0.00 0.105483E+11 0.00 0.00 0.00 1.08
October 0.147030E+11 0.00 0.00 0.00 0.253597E+10 0.00 0.00 0.00 1.07
November 0.228216E+11 0.00 0.00 0.00 0.742252E+09 0.00 0.00 0.00 1.07
December 0.299783E+11 0.00 0.00 0.00 65873046.33 16971322.27 0.00 0.00 1.07
                   
Annual Sum or Average 0.165951E+12 0.00 0.00 0.00 0.561948E+11 16971322.27 0.00 0.00 1.07
Minimum of Months 0.504506E+09 0.00 0.00 0.00 448370.92 0.00 0.00 0.00 1.06
Maximum of Months 0.299783E+11 0.00 0.00 0.00 0.137798E+11 16971322.27 0.00 0.00 1.08



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 38940179.06 225294.80 2821.29 2079573.61 41528.19 0.111311E+09 0.149962E+09 164.80 0.47
February 73108885.14 23666.01 0.00 966116.97 0.00 0.145361E+09 0.114114E+09 0.00 0.48
March 51451703.94 770152.25 0.00 1715824.33 77772.33 0.103302E+09 0.134772E+09 0.00 0.47
April 9683392.43 14184715.15 1470.42 2273628.29 341683.37 2433081.30 0.114819E+09 1666.14 0.47
May 2149017.00 26026750.43 5380.04 1767646.48 534290.60 21334.49 69755698.78 1263.58 0.47
June 94563.02 58043529.90 215.91 1265138.18 907100.05 0.00 16800313.58 165.60 0.47
July 38929.72 0.162338E+09 47264.06 339603.19 4469844.92 0.00 7104113.04 2059.77 0.47
August 150307.77 0.154209E+09 67379.22 360514.24 5421365.16 0.00 4247100.48 3074.31 0.47
September 488851.32 0.126670E+09 54678.35 589445.51 5435368.08 786.49 9838496.35 6049.70 0.48
October 20593568.42 25793509.10 18627.47 1978528.29 959483.96 35199132.08 0.117964E+09 1675.68 0.47
November 34698399.26 2675872.06 13901.11 1830614.38 1698318.99 83755127.04 0.146972E+09 647.56 0.47
December 60251683.96 73518.81 0.00 1178134.78 127737.05 0.170649E+09 0.114665E+09 0.00 0.47
                   
Annual Sum or Average 0.291649E+09 0.571034E+09 211737.88 16344768.24 20014492.68 0.652032E+09 0.100101E+10 16767.13 0.47
Minimum of Months 38929.72 23666.01 0.00 339603.19 0.00 0.00 4247100.48 0.00 0.47
Maximum of Months 73108885.14 0.162338E+09 67379.22 2273628.29 5435368.08 0.170649E+09 0.149962E+09 6049.70 0.48



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 50317594.21 157094.72 2472.21 935527.19 109697.01 0.167398E+09 83606291.56 513.53 0.47
February 88355491.66 2728.97 20901.59 439883.94 0.00 0.186023E+09 58692213.92 32.68 0.48
March 57798278.50 713000.53 794.19 1232095.98 133970.51 0.124510E+09 0.107667E+09 59.99 0.47
April 10616021.30 14091364.86 1037.40 2057801.63 433331.67 5010304.05 0.111510E+09 2098.79 0.47
May 2093952.47 25965436.67 6054.09 1749611.42 591889.05 25077.31 69816421.26 1192.05 0.47
June 85186.78 58083229.89 309.50 1293396.39 860493.13 0.00 16779303.90 71.97 0.47
July 34421.67 0.162440E+09 47372.28 344959.04 4348244.68 0.00 7102388.54 1945.77 0.47
August 150290.16 0.153920E+09 62876.41 346392.56 5695453.34 0.00 4260682.31 3494.69 0.47
September 498251.77 0.125746E+09 61497.97 551106.90 6336118.19 786.40 9866155.46 7151.07 0.48
October 25534219.98 24973033.79 17726.16 1411993.02 1776682.31 51523353.11 97245266.41 2717.07 0.47
November 48740704.77 2553773.36 13224.22 902392.93 1819905.19 0.123718E+09 93863665.11 1322.75 0.47
December 71829495.58 44313.30 0.00 376685.34 156918.99 0.227737E+09 46759946.74 0.00 0.47
                   
Annual Sum or Average 0.356054E+09 0.568690E+09 234266.00 11641846.33 22262704.06 0.885945E+09 0.707169E+09 20600.37 0.47
Minimum of Months 34421.67 2728.97 0.00 344959.04 0.00 0.00 4260682.31 0.00 0.47
Maximum of Months 88355491.66 0.162440E+09 62876.41 2057801.63 6336118.19 0.227737E+09 0.111510E+09 7151.07 0.48



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.150777E+09 1733385.53 0.00 25802736.33 0.00 85396807.82 0.168010E+10 0.00 0.54
February 0.291234E+09 152042.04 0.00 12999013.43 0.00 0.295689E+09 0.154296E+10 0.00 0.54
March 0.245614E+09 5029434.10 10590.83 13899491.51 405988.44 0.275087E+09 0.133648E+10 1469.00 0.54
April 60073412.77 90591977.91 2847.08 12960316.49 2746006.50 4862648.13 0.752204E+09 4011.73 0.54
May 13574909.54 0.165051E+09 22692.94 9411382.33 5588743.62 123537.76 0.450335E+09 21794.82 0.54
June 743090.09 0.369400E+09 66150.98 6406588.73 9235248.58 6326.61 0.109513E+09 28768.15 0.54
July 272751.53 0.103544E+10 611674.07 1701025.09 35873504.46 0.00 46098402.54 40836.71 0.54
August 965650.66 0.986924E+09 729290.81 1925751.01 38290923.86 0.00 27675820.63 50161.41 0.54
September 3039356.76 0.815680E+09 448979.89 3596661.77 32930668.44 0.00 63503855.70 43125.83 0.54
October 92166394.98 0.167059E+09 118098.11 16460946.61 4813746.21 29219174.19 0.991164E+09 14181.36 0.54
November 0.139119E+09 17596600.17 82513.43 20833733.14 10509403.58 0.103546E+09 0.145349E+10 6894.41 0.54
December 0.218704E+09 472320.84 0.00 19893997.56 820645.30 0.379503E+09 0.160955E+10 0.00 0.54
                   
Annual Sum or Average 0.121628E+10 0.365513E+10 2092838.14 0.145892E+09 0.141215E+09 0.117343E+10 0.100631E+11 211243.42 0.54
Minimum of Months 272751.53 152042.04 0.00 1701025.09 0.00 0.00 27675820.63 0.00 0.54
Maximum of Months 0.291234E+09 0.103544E+10 729290.81 25802736.33 38290923.86 0.379503E+09 0.168010E+10 50161.41 0.54



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.193012E+11 22131938.83 0.00 7822846.81 0.324147E+09 0.00 0.271555E+11 0.00 9.16
February 0.278399E+11 0.00 0.00 6849332.15 821229.82 0.00 0.255674E+11 0.00 9.26
March 0.181727E+11 0.135262E+09 0.00 10347463.02 0.439278E+09 0.00 0.266928E+11 0.00 9.22
April 0.355963E+10 0.176337E+10 0.00 14739958.20 0.340559E+10 0.00 0.146733E+11 0.00 9.20
May 0.915272E+09 0.386751E+10 0.00 16444338.16 0.462445E+10 0.00 0.914671E+10 0.00 9.21
June 65170042.40 0.105244E+11 0.00 13161693.11 0.436388E+10 0.00 0.256844E+10 0.00 9.25
July 19205186.56 0.177380E+11 0.00 4852960.81 0.750093E+10 0.00 0.101875E+10 0.00 9.26
August 26693968.84 0.142712E+11 0.00 5657815.53 0.849946E+10 0.00 0.891695E+09 0.00 9.27
September 0.181068E+09 0.112464E+11 0.00 8119629.60 0.807383E+10 0.00 0.243240E+10 0.00 9.27
October 0.879579E+10 0.166006E+10 0.00 11787157.36 0.298478E+10 0.00 0.181223E+11 0.00 9.22
November 0.176315E+11 0.248366E+09 0.00 8186594.86 0.111113E+10 0.00 0.241600E+11 0.00 9.21
December 0.286304E+11 192917.17 0.00 5641379.96 0.120459E+09 0.00 0.263029E+11 0.00 9.18
                   
Annual Sum or Average 0.125139E+12 0.614768E+11 0.00 0.113611E+09 0.414488E+11 0.00 0.178732E+12 0.00 9.23
Minimum of Months 19205186.56 0.00 0.00 4852960.81 821229.82 0.00 0.891695E+09 0.00 9.16
Maximum of Months 0.286304E+11 0.177380E+11 0.00 16444338.16 0.849946E+10 0.00 0.271555E+11 0.00 9.27



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.181047E+11 34426933.06 0.00 10191964.63 0.328286E+09 0.00 0.305549E+11 0.00 9.60
February 0.262267E+11 0.00 0.00 8980222.84 860205.57 0.00 0.297134E+11 0.00 9.70
March 0.165697E+11 0.148376E+09 0.00 13460211.21 0.453432E+09 0.00 0.304226E+11 0.00 9.66
April 0.262841E+10 0.267064E+10 0.00 17856899.00 0.274364E+10 0.00 0.164674E+11 0.00 9.64
May 0.597168E+09 0.540821E+10 0.00 19500944.22 0.348678E+10 0.00 0.994008E+10 0.00 9.65
June 47082073.01 0.131279E+11 0.00 14805495.68 0.246692E+10 0.00 0.271050E+10 0.00 9.69
July 13478851.24 0.218724E+11 0.00 5456716.40 0.456432E+10 0.00 0.107336E+10 0.00 9.71
August 21647871.91 0.180189E+11 0.00 6391436.81 0.583246E+10 0.00 0.939863E+09 0.00 9.72
September 0.121417E+09 0.136699E+11 0.00 9462666.65 0.656725E+10 0.00 0.261513E+10 0.00 9.71
October 0.768134E+10 0.222410E+10 0.00 14650997.77 0.264118E+10 0.00 0.205120E+11 0.00 9.66
November 0.163781E+11 0.297925E+09 0.00 10539551.84 0.112610E+10 0.00 0.273949E+11 0.00 9.65
December 0.275511E+11 202073.06 0.00 7593362.74 0.126176E+09 0.00 0.299876E+11 0.00 9.62
                   
Annual Sum or Average 0.115941E+12 0.774730E+11 0.00 0.138890E+09 0.303374E+11 0.00 0.202332E+12 0.00 9.67
Minimum of Months 13478851.24 0.00 0.00 5456716.40 860205.57 0.00 0.939863E+09 0.00 9.60
Maximum of Months 0.275511E+11 0.218724E+11 0.00 19500944.22 0.656725E+10 0.00 0.305549E+11 0.00 9.72



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.00 0.344315E+09 0.00 94888185.52 0.00 0.00 0.460806E+11 0.00 29.40
February 0.00 815828.78 0.00 88124932.08 0.00 0.00 0.529979E+11 0.00 29.69
March 0.00 0.571705E+09 0.00 88690556.46 0.00 0.00 0.445078E+11 0.00 29.60
April 0.00 0.515093E+10 0.00 50830348.12 0.00 0.00 0.180797E+11 0.00 29.54
May 0.00 0.846321E+10 0.00 37258405.50 0.00 0.00 0.997575E+10 0.00 29.57
June 0.00 0.148415E+11 0.00 18186695.94 0.00 0.00 0.261130E+10 0.00 29.71
July 0.00 0.251407E+11 0.00 6935343.08 0.00 0.00 0.102902E+10 0.00 29.74
August 0.00 0.226825E+11 0.00 8107436.53 0.00 0.00 0.909943E+09 0.00 29.77
September 0.00 0.192396E+11 0.00 15478717.64 0.00 0.00 0.258915E+10 0.00 29.77
October 0.00 0.462724E+10 0.00 66782658.63 0.00 0.00 0.266938E+11 0.00 29.61
November 0.00 0.135185E+10 0.00 83145224.03 0.00 0.00 0.414584E+11 0.00 29.55
December 0.00 0.119923E+09 0.00 94182619.00 0.00 0.00 0.545056E+11 0.00 29.45
                   
Annual Sum or Average 0.00 0.102534E+12 0.00 0.652611E+09 0.00 0.00 0.301439E+12 0.00 29.61
Minimum of Months 0.00 815828.78 0.00 6935343.08 0.00 0.00 0.909943E+09 0.00 29.40
Maximum of Months 0.00 0.251407E+11 0.00 94888185.52 0.00 0.00 0.545056E+11 0.00 29.77



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.148977E+11 0.00 0.00 0.00 0.115017E+09 0.535472E+09 0.00 0.00 2.44
February 0.172658E+11 0.00 0.00 0.00 272771.84 0.475680E+09 0.00 0.00 2.47
March 0.140610E+11 0.00 0.00 0.00 0.190834E+09 0.844570E+09 0.00 0.00 2.46
April 0.606097E+10 0.00 0.00 0.00 0.171687E+10 0.00 0.00 0.00 2.45
May 0.334755E+10 0.00 0.00 0.00 0.282061E+10 0.00 0.00 0.00 2.45
June 0.879126E+09 0.00 0.00 0.00 0.494514E+10 0.00 0.00 0.00 2.47
July 0.346369E+09 0.00 0.00 0.00 0.838311E+10 0.00 0.00 0.00 2.47
August 0.306923E+09 0.00 0.00 0.00 0.756329E+10 0.00 0.00 0.00 2.47
September 0.870763E+09 0.00 0.00 0.00 0.641721E+10 0.00 0.00 0.00 2.47
October 0.889520E+10 0.00 0.00 0.00 0.154278E+10 49558038.81 0.00 0.00 2.46
November 0.134784E+11 0.00 0.00 0.00 0.451558E+09 0.405431E+09 0.00 0.00 2.46
December 0.153666E+11 0.00 0.00 0.00 40074660.44 0.288135E+10 0.00 0.00 2.45
                   
Annual Sum or Average 0.957765E+11 0.00 0.00 0.00 0.341868E+11 0.519206E+10 0.00 0.00 2.46
Minimum of Months 0.306923E+09 0.00 0.00 0.00 272771.84 0.00 0.00 0.00 2.44
Maximum of Months 0.172658E+11 0.00 0.00 0.00 0.838311E+10 0.288135E+10 0.00 0.00 2.47



Table of Contents

Report: HeatEmissionsReportMonthly

For: Environment

Timestamp: 2023-10-16 08:58:43

Custom Monthly Report

SITE TOTAL SURFACE HEAT EMISSION TO AIR [J] SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J]
January 0.145106E+12 0.107577E+11 0.489290E+11 0.619497E+12 0.506619E+12
February 0.183227E+12 0.116324E+11 0.553244E+11 0.686782E+12 0.235510E+12
March 0.243622E+12 0.994652E+10 0.461589E+11 0.573083E+12 0.505975E+12
April 0.288947E+12 0.989888E+09 0.118584E+11 0.210628E+11 0.106993E+13
May 0.293637E+12 -0.216114E+10 -720974258.3 -0.175069E+12 0.133117E+13
June 0.307239E+12 -0.687485E+10 -0.217719E+11 -0.475183E+12 0.163523E+13
July 0.291183E+12 -0.114926E+11 -0.339722E+11 -0.748283E+12 0.182276E+13
August 0.243175E+12 -0.104659E+11 -0.299064E+11 -0.672739E+12 0.177490E+13
September 0.204234E+12 -0.823677E+10 -0.200600E+11 -0.525385E+12 0.160569E+13
October 0.185321E+12 0.317123E+10 0.222336E+11 0.160555E+12 0.953356E+12
November 0.157909E+12 0.900742E+10 0.437078E+11 0.516803E+12 0.552155E+12
December 0.115039E+12 0.144332E+11 0.628607E+11 0.848613E+12 0.338087E+12
           
Annual Sum or Average 0.265864E+13 0.207071E+11 0.184641E+12 0.829738E+12 0.123314E+14
Minimum of Months 0.115039E+12 -0.114926E+11 -0.339722E+11 -0.748283E+12 0.235510E+12
Maximum of Months 0.307239E+12 0.144332E+11 0.628607E+11 0.848613E+12 0.182276E+13