Table of Contents

Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:58

Tabular Output Report in Format: HTML

Building: HotelLarge

Environment: RUNPERIOD 1 ** William R Fairchild WA USA TMY3 WMO#=727885

Simulation Timestamp: 2023-10-16 08:58:31


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2023-10-16 08:58:31

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [GJ] Energy Per Total Building Area [MJ/m2] Energy Per Conditioned Building Area [MJ/m2]
Total Site Energy 13654.84 1203.57 1203.57
Net Site Energy 13654.84 1203.57 1203.57
Total Source Energy 29174.92 2571.55 2571.55
Net Source Energy 29174.92 2571.55 2571.55


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 1.200
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil No 1 1.050
Fuel Oil No 2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [m2]
Total Building Area 11345.29
Net Conditioned Building Area 11345.29
Unconditioned Building Area 0.00


End Uses

Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating 0.00 1634.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 474.04 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 1174.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 261.73 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 1751.30 1788.84 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 679.68 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 1809.73 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 132.81 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 451.61 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 90.78 3330.89 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 9857.19
Refrigeration 74.39 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 6900.18 6754.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 9857.19
Note: Natural gas appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler 0.00 1634.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 474.04 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 1174.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 261.73 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 959.56 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Cooking 762.04 1198.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ReachInFreezer 16.27 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ReachInRefrigerator 13.43 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Laundry 0.00 590.20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Transformer 32.92 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLift 616.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLightsFan 30.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  General 1809.73 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 132.81 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 451.61 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Water Heater 90.78 3330.89 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 5742.51
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 4114.69
Refrigeration General 18.27 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  LowTempRefrigeration 22.38 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  MedTempRefrigeration 33.73 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Space Type

Space Type Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating Unassigned 0.00 1634.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling Unassigned 474.04 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting GENERAL 1174.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Unassigned 261.73 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment GENERAL 1751.30 1788.84 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Unassigned 679.68 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Unassigned 1809.73 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps Unassigned 132.81 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery Unassigned 451.61 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Unassigned 90.78 3330.89 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 9857.19
Refrigeration Unassigned 74.39 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 126.56 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 221.00 437.70 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.87
Other 260.63 157.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 608.20 595.37 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.87


Utility Use Per Total Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 126.56 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 221.00 437.70 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.87
Other 260.63 157.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 608.20 595.37 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.87


Electric Loads Satisfied

Electricity [GJ] Percent Electricity [%]
Fuel-Fired Power Generation 0.000 0.00
High Temperature Geothermal* 0.000 0.00
Photovoltaic Power 0.000 0.00
Wind Power 0.000 0.00
Power Conversion 0.000 0.00
Net Decrease in On-Site Storage 0.000 0.00
Total On-Site Electric Sources 0.000 0.00
     
Electricity Coming From Utility 6900.176 100.00
Surplus Electricity Going To Utility 0.000 0.00
Net Electricity From Utility 6900.176 100.00
     
Total On-Site and Utility Electric Sources 6900.176 100.00
Total Electricity End Uses 6900.176 100.00


On-Site Thermal Sources

Heat [GJ] Percent Heat [%]
Water-Side Heat Recovery 0.00 0.00
Air to Air Heat Recovery for Cooling 15.73 0.29
Air to Air Heat Recovery for Heating 5452.10 99.71
High-Temperature Geothermal* 0.00 0.00
Solar Water Thermal 0.00 0.00
Solar Air Thermal 0.00 0.00
Total On-Site Thermal Sources 5467.84 100.00


Water Source Summary

Water [m3] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 9857.19 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 9857.19 100.00
Total Water End Uses 9857.19 100.00


Setpoint Not Met Criteria

Degrees [deltaC]
Tolerance for Zone Heating Setpoint Not Met Time 0.56
Tolerance for Zone Cooling Setpoint Not Met Time 0.56


Comfort and Setpoint Not Met Summary

Facility [Hours]
Time Setpoint Not Met During Occupied Heating 24.50
Time Setpoint Not Met During Occupied Cooling 5.67
Time Not Comfortable Based on Simple ASHRAE 55-2004 6724.67


Note 1: An asterisk (*) indicates that the feature is not yet implemented.

Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Adaptive Comfort Summary
Initialization Summary
Annual Heat Emissions Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
Coil Sizing Details
System Summary
Outdoor Air Summary
Outdoor Air Details
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary
Annual Thermal Resilience Summary
Annual CO2 Resilience Summary
Annual Visual Resilience Summary

NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODENAME IECC

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2012

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

| Environment |

NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE

| Environment |

NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5C

| Environment |

NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_PORTANGELES

| Environment |

ZoneCoolingSummaryMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

ZoneHeatingSummaryMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

ZoneElectricSummaryMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

SpaceGainsMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

PeakSpaceGainsMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

SpaceGainComponentsAtCoolingPeakMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

EnergyConsumptionElectricityNaturalGasMonthly

| Meter |

EndUseEnergyConsumptionElectricityMonthly

| Meter |

EndUseEnergyConsumptionNaturalGasMonthly

| Meter |

PeakEnergyEndUseElectricityPart1Monthly

| Meter |

PeakEnergyEndUseElectricityPart2Monthly

| Meter |

ElectricComponentsOfPeakDemandMonthly

| Meter |

PeakEnergyEndUseNaturalGasMonthly

| Meter |

SetpointsNotMetWithTemperaturesMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

ComfortReportSimple55Monthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

OccupantComfortDataSummaryMonthly

| BASEMENT PEOPLE | RETAIL_1_FLR_1 PEOPLE | RETAIL_2_FLR_1 PEOPLE | LAUNDRY_FLR_1 PEOPLE | CAFE_FLR_1 PEOPLE | LOBBY_FLR_1 PEOPLE | ROOM_1_FLR_3 PEOPLE | ROOM_2_FLR_3 PEOPLE | ROOM_3_MULT19_FLR_3 PEOPLE | ROOM_4_MULT19_FLR_3 PEOPLE | ROOM_5_FLR_3 PEOPLE | ROOM_6_FLR_3 PEOPLE | ROOM_1_FLR_6 PEOPLE | ROOM_2_FLR_6 PEOPLE | ROOM_3_MULT9_FLR_6 PEOPLE | BANQUET_FLR_6 PEOPLE | DINING_FLR_6 PEOPLE | KITCHEN_FLR_6 PEOPLE | STORAGE_FLR_1 PEOPLE | CORRIDOR_FLR_3 PEOPLE | CORRIDOR_FLR_6 PEOPLE | MECH_FLR_1 PEOPLE |

ChillerReportMonthly

| COOLSYS1 CHILLER1 |

BoilerReportMonthly

| HEATSYS1 BOILER |

DXReportMonthly

| VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |

WindowReportMonthly

| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |

WindowEnergyReportMonthly

| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |

WindowZoneSummaryMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

WindowEnergyZoneSummaryMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

AverageOutdoorConditionsMonthly

| Environment |

OutdoorConditionsMaximumDryBulbMonthly

| Environment |

OutdoorConditionsMinimumDryBulbMonthly

| Environment |

OutdoorConditionsMaximumWetBulbMonthly

| Environment |

OutdoorConditionsMaximumDewPointMonthly

| Environment |

OutdoorGroundConditionsMonthly

| Environment |

WaterHeaterReportMonthly

| SWH BOOSTER E WATER HEATER | SWH LAUNDRY G WATER HEATER | SWHSYS1 WATER HEATER |

DaylightingReportMonthly

| Environment |

CoilReportMonthly

| VAV WITH REHEAT HEATING COIL | BASEMENT VAV BOX REHEAT COIL | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | MECH_FLR_1 VAV BOX REHEAT COIL | STORAGE_FLR_1 VAV BOX REHEAT COIL | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | CAFE_FLR_1 VAV BOX REHEAT COIL | LOBBY_FLR_1 VAV BOX REHEAT COIL | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | BANQUET_FLR_6 VAV BOX REHEAT COIL | DINING_FLR_6 VAV BOX REHEAT COIL | KITCHEN_FLR_6 VAV BOX REHEAT COIL | FLR_3_DOAS HEATING COIL | ROOM_1_FLR_3 FAN COIL HEATING COIL | ROOM_2_FLR_3 FAN COIL HEATING COIL | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_5_FLR_3 FAN COIL HEATING COIL | ROOM_6_FLR_3 FAN COIL HEATING COIL | ROOM_1_FLR_6 FAN COIL HEATING COIL | ROOM_2_FLR_6 FAN COIL HEATING COIL | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |

PlantLoopDemandReportMonthly

| HEATSYS1 | COOLSYS1 | SWHSYS1 |

FanReportMonthly

| FLR_3_DOAS FAN | VAV WITH REHEAT FAN | LAUNDRY_FLR_1 EXHAUST FAN | LOBBY_FLR_1 EXHAUST FAN | BANQUET_FLR_6 EXHAUST FAN | DINING_FLR_6 EXHAUST FAN | KITCHEN_FLR_6 EXHAUST FAN | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN |

PumpReportMonthly

| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 PUMP | SWHSYS1 PUMP |

CondLoopDemandReportMonthly

| HEATSYS1 | COOLSYS1 | SWHSYS1 |

ZoneTemperatureOscillationReportMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

AirLoopSystemEnergyAndWaterUseMonthly

| VAV WITH REHEAT | FLR_3_DOAS |

AirLoopSystemComponentLoadsMonthly

| VAV WITH REHEAT | FLR_3_DOAS |

AirLoopSystemComponentEnergyUseMonthly

| VAV WITH REHEAT | FLR_3_DOAS |

MechanicalVentilationLoadsMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

HeatEmissionsReportMonthly

| Environment |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2023-10-16 08:58:31

General

Value
Program Version and Build EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:58
RunPeriod RUNPERIOD 1
Weather File William R Fairchild WA USA TMY3 WMO#=727885
Latitude [deg] 48.12
Longitude [deg] -123.5
Elevation [m] 91.00
Time Zone -8.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 4559.59 1873.43 406.47 1873.22 406.47
Above Ground Wall Area [m2] 4025.82 1662.30 350.71 1662.10 350.71
Window Opening Area [m2] 1213.79 432.95 85.85 609.15 85.85
Gross Window-Wall Ratio [%] 26.62 23.11 21.12 32.52 21.12
Above Ground Window-Wall Ratio [%] 30.15 26.05 24.48 36.65 24.48


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 4559.59 1873.43 406.47 1873.22 406.47
Above Ground Wall Area [m2] 4025.82 1662.30 350.71 1662.10 350.71
Window Opening Area [m2] 1213.79 432.95 85.85 609.15 85.85
Gross Window-Wall Ratio [%] 26.62 23.11 21.12 32.52 21.12
Above Ground Window-Wall Ratio [%] 30.15 26.05 24.48 36.65 24.48


Skylight-Roof Ratio

Total
Gross Roof Area [m2] 1978.84
Skylight Area [m2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [m3] Multipliers Above Ground Gross Wall Area [m2] Underground Gross Wall Area [m2] Window Glass Area [m2] Opening Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
BASEMENT 1978.83 Yes Yes 4826.41 1.00 0.00 533.77 0.00 0.00 8.7495 18.58 5.3800
RETAIL_1_FLR_1 67.07 Yes Yes 265.76 1.00 68.84 0.00 23.26 23.26 13.0124 6.19 10.7600
RETAIL_2_FLR_1 77.67 Yes Yes 307.76 1.00 26.57 0.00 0.00 0.00 13.0124 6.19 10.7600
MECH_FLR_1 164.24 Yes Yes 650.80 1.00 62.80 0.00 0.00 0.00 10.0642 61.93 5.3800
STORAGE_FLR_1 94.76 Yes Yes 375.47 1.00 36.23 0.00 0.00 0.00 7.3195 46.45 2.6900
LAUNDRY_FLR_1 78.04 Yes Yes 309.22 1.00 85.75 0.00 0.00 0.00 5.4896 9.29 597.5300
CAFE_FLR_1 188.86 Yes Yes 748.35 1.00 152.17 0.00 65.50 65.50 12.8090 1.33 5.3800
LOBBY_FLR_1 1308.19 Yes Yes 5183.56 1.00 434.79 0.00 85.08 85.08 10.0642 3.10 8.0700
ROOM_1_FLR_3 39.02 Yes Yes 118.94 4.00 39.95 0.00 13.18 13.18 10.0642 26.01 6.7500
ROOM_2_FLR_3 39.02 Yes Yes 118.93 4.00 39.95 0.00 13.18 13.18 10.0642 26.01 6.7500
ROOM_3_MULT19_FLR_3 24.52 Yes Yes 74.75 76.00 11.15 0.00 3.68 3.68 10.0642 16.35 10.5200
ROOM_4_MULT19_FLR_3 24.53 Yes Yes 74.77 76.00 11.15 0.00 3.68 3.68 10.0642 16.35 10.5200
ROOM_5_FLR_3 39.02 Yes Yes 118.94 4.00 39.95 0.00 13.18 13.18 10.0642 26.01 6.7500
ROOM_6_FLR_3 39.02 Yes Yes 118.93 4.00 39.95 0.00 13.18 13.18 10.0642 26.01 6.7500
CORRIDOR_FLR_3 389.40 Yes Yes 1186.91 4.00 48.31 0.00 15.94 15.94 3.6597 18.58 0.0000
ROOM_1_FLR_6 39.02 Yes Yes 118.94 1.00 39.95 0.00 13.18 13.18 10.0642 26.01 6.7500
ROOM_2_FLR_6 39.02 Yes Yes 118.93 1.00 39.95 0.00 13.18 13.18 10.0642 26.01 6.7500
ROOM_3_MULT9_FLR_6 24.53 Yes Yes 74.77 9.00 20.44 0.00 6.74 6.74 10.0642 16.35 10.5200
BANQUET_FLR_6 331.66 Yes Yes 1010.89 1.00 97.55 0.00 32.19 32.19 12.8090 1.33 67.8200
DINING_FLR_6 331.66 Yes Yes 1010.89 1.00 97.55 0.00 32.19 32.19 12.8090 1.33 67.8200
KITCHEN_FLR_6 103.30 Yes Yes 314.87 1.00 87.33 0.00 26.37 26.37 10.9792 4.65 2936.4163
CORRIDOR_FLR_6 412.12 Yes Yes 1256.16 1.00 85.47 0.00 28.20 28.20 3.6597 18.58 0.0000
Total 11345.29     35184.81   4025.82 533.77 1213.79 1213.79 8.9207 7.07 41.0885
Conditioned Total 11345.29     35184.81   4025.82 533.77 1213.79 1213.79 8.9207 7.07 41.0885
Unconditioned Total 0.00     0.00   0.00 0.00 0.00 0.00      
Not Part of Total 0.00     0.00   0.00 0.00 0.00 0.00      


Space Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Multipliers Zone Name Space Type Radiant/Solar Enclosure Name Lighting [W/m2] People [m2 per person] Plug and Process [W/m2] Tags
BASEMENT 1978.83 Yes Yes 1.00 BASEMENT GENERAL BASEMENT 8.7495 18.58 5.3800  
RETAIL_1_FLR_1 67.07 Yes Yes 1.00 RETAIL_1_FLR_1 GENERAL RETAIL_1_FLR_1 13.0124 6.19 10.7600  
RETAIL_2_FLR_1 77.67 Yes Yes 1.00 RETAIL_2_FLR_1 GENERAL RETAIL_2_FLR_1 13.0124 6.19 10.7600  
MECH_FLR_1 164.24 Yes Yes 1.00 MECH_FLR_1 GENERAL MECH_FLR_1 10.0642 61.93 5.3800  
STORAGE_FLR_1 94.76 Yes Yes 1.00 STORAGE_FLR_1 GENERAL STORAGE_FLR_1 7.3195 46.45 2.6900  
LAUNDRY_FLR_1 78.04 Yes Yes 1.00 LAUNDRY_FLR_1 GENERAL LAUNDRY_FLR_1 5.4896 9.29 597.5300  
CAFE_FLR_1 188.86 Yes Yes 1.00 CAFE_FLR_1 GENERAL CAFE_FLR_1 12.8090 1.33 5.3800  
LOBBY_FLR_1 1308.19 Yes Yes 1.00 LOBBY_FLR_1 GENERAL LOBBY_FLR_1 10.0642 3.10 8.0700  
ROOM_1_FLR_3 39.02 Yes Yes 4.00 ROOM_1_FLR_3 GENERAL ROOM_1_FLR_3 10.0642 26.01 6.7500  
ROOM_2_FLR_3 39.02 Yes Yes 4.00 ROOM_2_FLR_3 GENERAL ROOM_2_FLR_3 10.0642 26.01 6.7500  
ROOM_3_MULT19_FLR_3 24.52 Yes Yes 76.00 ROOM_3_MULT19_FLR_3 GENERAL ROOM_3_MULT19_FLR_3 10.0642 16.35 10.5200  
ROOM_4_MULT19_FLR_3 24.53 Yes Yes 76.00 ROOM_4_MULT19_FLR_3 GENERAL ROOM_4_MULT19_FLR_3 10.0642 16.35 10.5200  
ROOM_5_FLR_3 39.02 Yes Yes 4.00 ROOM_5_FLR_3 GENERAL ROOM_5_FLR_3 10.0642 26.01 6.7500  
ROOM_6_FLR_3 39.02 Yes Yes 4.00 ROOM_6_FLR_3 GENERAL ROOM_6_FLR_3 10.0642 26.01 6.7500  
CORRIDOR_FLR_3 389.40 Yes Yes 4.00 CORRIDOR_FLR_3 GENERAL CORRIDOR_FLR_3 3.6597 18.58 0.0000  
ROOM_1_FLR_6 39.02 Yes Yes 1.00 ROOM_1_FLR_6 GENERAL ROOM_1_FLR_6 10.0642 26.01 6.7500  
ROOM_2_FLR_6 39.02 Yes Yes 1.00 ROOM_2_FLR_6 GENERAL ROOM_2_FLR_6 10.0642 26.01 6.7500  
ROOM_3_MULT9_FLR_6 24.53 Yes Yes 9.00 ROOM_3_MULT9_FLR_6 GENERAL ROOM_3_MULT9_FLR_6 10.0642 16.35 10.5200  
BANQUET_FLR_6 331.66 Yes Yes 1.00 BANQUET_FLR_6 GENERAL BANQUET_FLR_6 12.8090 1.33 67.8200  
DINING_FLR_6 331.66 Yes Yes 1.00 DINING_FLR_6 GENERAL DINING_FLR_6 12.8090 1.33 67.8200  
KITCHEN_FLR_6 103.30 Yes Yes 1.00 KITCHEN_FLR_6 GENERAL KITCHEN_FLR_6 10.9792 4.65 2936.4163  
CORRIDOR_FLR_6 412.12 Yes Yes 1.00 CORRIDOR_FLR_6 GENERAL CORRIDOR_FLR_6 3.6597 18.58 0.0000  
Total 11345.29             8.9207 3.54 41.0885  
Conditioned Total 11345.29             8.9207 3.54 41.0885  
Unconditioned Total 0.00             0.0000 0.00 0.0000  
Not Part of Total 0.00             0.0000 0.00 0.0000  


Space Type Summary

Total Area [m2] Conditioned Area [m2] Unconditioned Area [m2] Not Part of Total Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
GENERAL 11345.29 11345.29 0.00 0.00 4.6908 8.82 37.2165
Total 11345.29 11345.29 0.00 0.00      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2023-10-16 08:58:31

End Uses

Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Time of Peak 22-JUL-18:10 11-JAN-17:49 - - - - - - - - - - 02-JAN-21:10
Heating 0.00 166194.57 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 167714.04 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 82807.27 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 76644.19 89612.21 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 32608.13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 75740.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 8954.24 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 17755.68 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 4327.00 267293.60 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 2886.73 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 469437.58 523100.38 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Subcategory

Subcategory Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Heating General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler 0.00 166194.57 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 167714.04 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 82807.27 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 46461.80 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Cooking 29240.64 74976.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ReachInFreezer 515.92 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ReachInRefrigerator 425.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Laundry 0.00 14636.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Transformer 1482.77 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLift 30153.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLightsFan 972.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  General 75740.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 8954.24 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 17755.68 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Water Heater 4327.00 267293.60 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 618.76 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  LowTempRefrigeration 1178.23 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  MedTempRefrigeration 1089.74 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2023-10-16 08:58:31

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [GJ] Source Natural Gas [GJ] Source Gasoline [GJ] Source Diesel [GJ] Source Coal [GJ] Source Fuel Oil No 1 [GJ] Source Fuel Oil No 2 [GJ] Source Propane [GJ] Source Other Fuel 1 [GJ] Source Other Fuel 2 [GJ] Source District Cooling [GJ] Source District Heating [GJ]
Heating 0.00 1772.27 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 1501.28 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 3718.41 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 828.91 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 5546.36 1939.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 2152.55 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 5731.42 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 420.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 1430.25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 287.50 3610.68 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 235.58 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 21852.86 7322.06 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 156.21 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 132.33 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 327.75 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 73.06 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 488.87 170.92 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 189.73 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 505.18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 37.07 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 126.07 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 25.34 318.25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 20.76 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 1926.16 645.38 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 156.21 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 132.33 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 327.75 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 73.06 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 488.87 170.92 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 189.73 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 505.18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 37.07 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 126.07 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 25.34 318.25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 20.76 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 1926.16 645.38 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2023-10-16 08:58:31

AirTerminal:SingleDuct:VAV:Reheat

Design Size Maximum Air Flow Rate [m3/s] Design Size Constant Minimum Air Flow Fraction User-Specified Constant Minimum Air Flow Fraction Design Size Minimum Air Flow Rate [m3/s] Design Size Maximum Flow Fraction during Reheat [] User-Specified Maximum Flow Fraction during Reheat [] Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] Design Size Maximum Reheat Water Flow Rate [m3/s] Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] Design Size Reheat Coil Sizing Inlet Air Temperature [C] Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir]
BASEMENT VAV BOX COMPONENT 2.48 0.608098 0.995000 2.47 1.00 0.500000 0.000627 0.000125 2.47 16.70 0.008000
RETAIL_1_FLR_1 VAV BOX COMPONENT 0.474926 0.107613 0.995000 0.472551 0.995000 0.500000 0.003540 0.000042 0.472551 16.70 0.008000
RETAIL_2_FLR_1 VAV BOX COMPONENT 0.237483 0.249213 0.995000 0.236295 0.995000 0.500000 0.001529 0.000017 0.236295 16.70 0.008000
MECH_FLR_1 VAV BOX COMPONENT 0.222845 0.561617 0.995000 0.221730 1.00 0.500000 0.000678 0.000022 0.221730 16.70 0.008000
STORAGE_FLR_1 VAV BOX COMPONENT 0.109419 0.659911 0.995000 0.108872 1.00 0.500000 0.000577 0.000013 0.108872 16.70 0.008000
LAUNDRY_FLR_1 VAV BOX COMPONENT 3.28 0.071893 0.995000 3.27 0.995000 0.500000 0.021030 0.000165 3.27 16.70 0.008000
CAFE_FLR_1 VAV BOX COMPONENT 1.87 0.076875 0.995000 1.86 0.995000 0.500000 0.004956 0.000138 1.86 16.70 0.008000
LOBBY_FLR_1 VAV BOX COMPONENT 5.17 0.192988 0.995000 5.14 0.995000 0.500000 0.001974 0.000356 5.14 16.70 0.008000
CORRIDOR_FLR_3 VAV BOX COMPONENT 1.25 0.948663 0.995000 1.24 1.00 0.500000 0.000402 0.000127 1.24 16.70 0.008000
BANQUET_FLR_6 VAV BOX COMPONENT 2.19 0.115267 0.995000 2.18 0.995000 0.500000 0.003305 0.000149 2.18 16.70 0.008000
DINING_FLR_6 VAV BOX COMPONENT 2.30 0.109884 0.995000 2.29 0.995000 0.500000 0.003467 0.000155 2.29 16.70 0.008000
KITCHEN_FLR_6 VAV BOX COMPONENT 2.32 0.815387 0.995000 2.30 0.995000 0.500000 0.011206 0.000113 2.30 16.70 0.008000
CORRIDOR_FLR_6 VAV BOX COMPONENT 0.771151 0.407234 0.995000 0.767295 1.00 0.500000 0.000936 0.000088 0.767295 16.70 0.008000
User-Specified values were used. Design Size values were used if no User-Specified values were provided. Design Size values may be derived from alternate User-Specified values.

Coil:Heating:Water

Design Size Rated Capacity [W] Design Size Maximum Water Flow Rate [m3/s] Design Size U-Factor Times Area Value [W/K]
BASEMENT VAV BOX REHEAT COIL 14327.12 0.000125 300.51
RETAIL_1_FLR_1 VAV BOX REHEAT COIL 4825.41 0.000042 105.89
RETAIL_2_FLR_1 VAV BOX REHEAT COIL 1993.71 0.000017 42.95
MECH_FLR_1 VAV BOX REHEAT COIL 2551.24 0.000022 56.76
STORAGE_FLR_1 VAV BOX REHEAT COIL 1434.23 0.000013 32.49
LAUNDRY_FLR_1 VAV BOX REHEAT COIL 18849.13 0.000165 395.21
CAFE_FLR_1 VAV BOX REHEAT COIL 15718.65 0.000138 338.62
LOBBY_FLR_1 VAV BOX REHEAT COIL 40686.71 0.000356 871.81
ROOM_1_FLR_3 FAN COIL HEATING COIL 5188.67 0.000045 148.28
ROOM_2_FLR_3 FAN COIL HEATING COIL 5194.32 0.000045 148.44
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL 29731.12 0.000260 849.63
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL 29853.37 0.000261 853.12
ROOM_5_FLR_3 FAN COIL HEATING COIL 5176.67 0.000045 147.94
ROOM_6_FLR_3 FAN COIL HEATING COIL 5182.33 0.000045 148.10
CORRIDOR_FLR_3 VAV BOX REHEAT COIL 14547.38 0.000127 324.28
ROOM_1_FLR_6 FAN COIL HEATING COIL 1653.18 0.000014 47.24
ROOM_2_FLR_6 FAN COIL HEATING COIL 1654.61 0.000014 47.28
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL 7974.44 0.000070 227.87
BANQUET_FLR_6 VAV BOX REHEAT COIL 17055.32 0.000149 365.08
DINING_FLR_6 VAV BOX REHEAT COIL 17714.73 0.000155 378.90
KITCHEN_FLR_6 VAV BOX REHEAT COIL 12886.51 0.000113 269.72
CORRIDOR_FLR_6 VAV BOX REHEAT COIL 10065.78 0.000088 227.90
VAV WITH REHEAT HEATING COIL 170153.31 0.001489 2903.30
FLR_3_DOAS HEATING COIL 15471.26 0.000135 263.98
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:ZoneExhaust

User-Specified Maximum Flow Rate [m3/s]
LOBBY_FLR_1 EXHAUST FAN 0.000000
BANQUET_FLR_6 EXHAUST FAN 0.000000
DINING_FLR_6 EXHAUST FAN 0.000000
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirTerminal:SingleDuct:ConstantVolume:NoReheat

Design Size Maximum Air Flow Rate [m3/s]
ROOM_1_FLR_3 DIRECT AIR 0.061735
ROOM_2_FLR_3 DIRECT AIR 0.061728
ROOM_3_MULT19_FLR_3 DIRECT AIR 0.837072
ROOM_4_MULT19_FLR_3 DIRECT AIR 0.837300
ROOM_5_FLR_3 DIRECT AIR 0.061735
ROOM_6_FLR_3 DIRECT AIR 0.061728
ROOM_1_FLR_6 DIRECT AIR 0.015434
ROOM_2_FLR_6 DIRECT AIR 0.015432
ROOM_3_MULT9_FLR_6 DIRECT AIR 0.099154
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

ZoneHVAC:FourPipeFanCoil

Design Size Maximum Supply Air Flow Rate [m3/s] Design Size Maximum Hot Water Flow [m3/s] Design Size Maximum Cold Water Flow [m3/s]
ROOM_1_FLR_3 FAN COIL 1.24 0.000045 0.000532
ROOM_2_FLR_3 FAN COIL 1.11 0.000045 0.000477
ROOM_3_MULT19_FLR_3 FAN COIL 9.05 0.000260 0.003814
ROOM_4_MULT19_FLR_3 FAN COIL 5.75 0.000261 0.002574
ROOM_5_FLR_3 FAN COIL 1.13 0.000045 0.000484
ROOM_6_FLR_3 FAN COIL 1.02 0.000045 0.000437
ROOM_1_FLR_6 FAN COIL 0.333458 0.000014 0.000142
ROOM_2_FLR_6 FAN COIL 0.296105 0.000014 0.000127
ROOM_3_MULT9_FLR_6 FAN COIL 1.85 0.000070 0.000796
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:OnOff

Design Size Maximum Flow Rate [m3/s]
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN 1.24
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN 1.11
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN 9.05
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN 5.75
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN 1.13
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN 1.02
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN 0.333458
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN 0.296105
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN 1.85
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Cooling:Water

Design Size Design Inlet Air Temperature [C] Design Size Design Inlet Water Temperature [C] Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] Design Size Design Outlet Air Temperature [C] Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] Design Size Design Water Flow Rate [m3/s] Design Size Design Air Flow Rate [m3/s] Design Size Design Coil Load [W]
ROOM_1_FLR_3 FAN COIL COOLING COIL 22.50 6.70 0.008557 12.80 0.008500 0.000532 1.24  
ROOM_2_FLR_3 FAN COIL COOLING COIL 22.50 6.70 0.008564 12.80 0.008500 0.000477 1.11  
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL 22.50 6.70 0.008499 12.80 0.008499 0.003814 9.05  
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL 22.50 6.70 0.008741 12.80 0.008500 0.002574 5.75  
ROOM_5_FLR_3 FAN COIL COOLING COIL 22.50 6.70 0.008563 12.80 0.008500 0.000484 1.13  
ROOM_6_FLR_3 FAN COIL COOLING COIL 22.50 6.70 0.008570 12.80 0.008500 0.000437 1.02  
ROOM_1_FLR_6 FAN COIL COOLING COIL 22.50 6.70 0.008554 12.80 0.008500 0.000142 0.333458  
ROOM_2_FLR_6 FAN COIL COOLING COIL 22.50 6.70 0.008560 12.80 0.008500 0.000127 0.296105  
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL 22.50 6.70 0.008589 12.80 0.008500 0.000796 1.85  
VAV WITH REHEAT COOLING COIL 26.40 6.70 0.008407 10.96 0.008407 0.015129 22.56 423570.84
FLR_3_DOAS COOLING COIL 26.40 6.70 0.008407 11.92 0.008407 0.001290 2.05 36112.10
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC

Sum of Air Terminal Maximum Heating Flow Rates [m3/s] Sum of Air Terminal Minimum Heating Flow Rates [m3/s] Sum of Air Terminal Maximum Flow Rates [m3/s] Adjusted Heating Design Air Flow Rate [m3/s] Adjusted Cooling Design Air Flow Rate [m3/s] Adjusted Main Design Air Flow Rate [m3/s] User Heating Air Flow Ratio [] Calculated Heating Air Flow Ratio [] Design Supply Air Flow Rate [m3/s]
VAV WITH REHEAT 22.56 22.56 22.67 22.56 22.56 22.56 0.300000 1.00 22.56
FLR_3_DOAS 2.05 2.05 2.05 2.05 2.05 2.05 0.300000 1.00 2.05
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:OutdoorAir

Maximum Outdoor Air Flow Rate [m3/s] Minimum Outdoor Air Flow Rate [m3/s]
VAV WITH REHEAT_OA_CONTROLLER 22.56 22.56
FLR_3_DOAS_OA_CONTROLLER 2.05 2.05
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

HeatExchanger:AirToAir:SensibleAndLatent

Design Size Nominal Supply Air Flow Rate [m3/s]
VAV WITH REHEAT OA HEAT RECOVERY 22.56
FLR_3_DOAS OA HEAT RECOVERY 2.05
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:VariableVolume

Design Size Maximum Flow Rate [m3/s]
VAV WITH REHEAT FAN 22.56
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:WaterCoil

Maximum Actuated Flow [m3/s] Controller Convergence Tolerance
VAV WITH REHEAT_COOLC_CONTROLLER 0.015129 0.000031
VAV WITH REHEAT_HEATC_CONTROLLER 0.001489  
FLR_3_DOAS_COOLC_CONTROLLER 0.001290 0.000369
FLR_3_DOAS_HEATC_CONTROLLER 0.000135  
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:ConstantVolume

User-Specified Maximum Flow Rate [m3/s]
FLR_3_DOAS FAN 2.05
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:VariableSpeed

Design Flow Rate [m3/s] Design Power Consumption [W] Design Minimum Flow Rate [m3/s]
COOLSYS1 PUMP SECONDARY 0.025802 5316.91  
HEATSYS1 PUMP 0.003936 1185.30 0.000000
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantLoop

Maximum Loop Flow Rate [m3/s] Plant Loop Volume [m3]
HEATSYS1 0.003936 0.472299
COOLSYS1 0.025802 3.10
SWHSYS1 0.000375 0.045004
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Boiler:HotWater

Design Size Nominal Capacity [W] User-Specified Nominal Capacity [W] Design Size Design Water Flow Rate [m3/s]
HEATSYS1 BOILER 449889.21 449889.21 0.003936
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:ConstantSpeed

Design Flow Rate [m3/s] Design Power Consumption [W]
COOLSYS1 PUMP 0.025802 3681.07
SWHSYS1 PUMP 0.000375 47.91
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Chiller:Electric:EIR

Design Size Reference Chilled Water Flow Rate [m3/s] Design Size Reference Capacity [W] User-Specified Reference Capacity [W] Design Size Reference Condenser Fluid Flow Rate [m3/s]
COOLSYS1 CHILLER1 0.025802 722396.70 723021.47 82.42
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

WaterHeater:Mixed

Use Side Design Flow Rate [m3/s]
SWHSYS1 WATER HEATER 0.000375
User-Specified values were used. Design Size values were used if no User-Specified values were provided.


Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2023-10-16 08:58:31

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

Possible Shadow Receivers
RETAIL_1_FLR_1_CEILING ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH |
CAFE_FLR_1_CEILING ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH |
LOBBY_FLR_1_CEILING_2 ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH |


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
RETAIL_1_FLR_1_WALL_SOUTH RETAIL_1_FLR_1_WALL_SOUTH_WINDOW |
RETAIL_2_FLR_1_WALL_WEST RETAIL_2_FLR_1_WALL_WEST_DOOR |
STORAGE_FLR_1_WALL_NORTH STORAGE_FLR_1_WALL_NORTH_ROLLDOOR |
LAUNDRY_FLR_1_WALL_EAST LAUNDRY_FLR_1_WALL_EAST_DOOR |
CAFE_FLR_1_WALL_EAST CAFE_FLR_1_WALL_EAST_DOOR |
CAFE_FLR_1_WALL_SOUTH CAFE_FLR_1_WALL_SOUTH_WINDOW |
LOBBY_FLR_1_WALL_1_NORTH LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 |
LOBBY_FLR_1_WALL_1_SOUTH LOBBY_FLR_1_WALL_SOUTH_WINDOW |
ROOM_1_FLR_3_WALL_SOUTH ROOM_1_FLR_3_WALL_SOUTH_WINDOW |
ROOM_1_FLR_3_WALL_WEST ROOM_1_FLR_3_WALL_WEST_WINDOW |
ROOM_2_FLR_3_WALL_NORTH ROOM_2_FLR_3_WALL_NORTH_WINDOW |
ROOM_2_FLR_3_WALL_WEST ROOM_2_FLR_3_WALL_WEST_WINDOW |
ROOM_3_MULT19_FLR_3_WALL_SOUTH ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW |
ROOM_4_MULT19_FLR_3_WALL_NORTH ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW |
ROOM_5_FLR_3_WALL_EAST ROOM_5_FLR_3_WALL_EAST_WINDOW |
ROOM_5_FLR_3_WALL_SOUTH ROOM_5_FLR_3_WALL_SOUTH_WINDOW |
ROOM_6_FLR_3_WALL_NORTH ROOM_6_FLR_3_WALL_NORTH_WINDOW |
ROOM_6_FLR_3_WALL_EAST ROOM_6_FLR_3_WALL_EAST_WINDOW |
CORRIDOR_FLR_3_WALL_1_NORTH CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW |
CORRIDOR_FLR_3_WALL_2_NORTH CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW |
CORRIDOR_FLR_3_WALL_1_SOUTH CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW |
CORRIDOR_FLR_3_WALL_2_SOUTH CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW |
ROOM_1_FLR_6_WALL_SOUTH ROOM_1_FLR_6_WALL_SOUTH_WINDOW |
ROOM_1_FLR_6_WALL_WEST ROOM_1_FLR_6_WALL_WEST_WINDOW |
ROOM_2_FLR_6_WALL_NORTH ROOM_2_FLR_6_WALL_NORTH_WINDOW |
ROOM_2_FLR_6_WALL_WEST ROOM_2_FLR_6_WALL_WEST_WINDOW |
ROOM_3_MULT9_FLR_6_WALL_SOUTH ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW |
BANQUET_FLR_6_WALL_NORTH BANQUET_FLR_6_WALL_NORTH_WINDOW |
DINING_FLR_6_WALL_NORTH DINING_FLR_6_WALL_NORTH_WINDOW |
KITCHEN_FLR_6_WALL_NORTH KITCHEN_FLR_6_WALL_NORTH_WINDOW |
KITCHEN_FLR_6_WALL_EAST KITCHEN_FLR_6_WALL_EAST_WINDOW |
KITCHEN_FLR_6_WALL_1_SOUTH KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW |
CORRIDOR_FLR_6_WALL_1_NORTH CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW |
CORRIDOR_FLR_6_WALL_2_NORTH CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW |
CORRIDOR_FLR_6_WALL_2_SOUTH CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2023-10-16 08:58:31

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: Initialization Summary

For: Entire Facility

Timestamp: 2023-10-16 08:58:31

Version

Version ID
1 22.1


Timesteps per Hour

#TimeSteps Minutes per TimeStep {minutes}
1 6 10


System Convergence Limits

Minimum System TimeStep {minutes} Max HVAC Iterations Minimum Plant Iterations Maximum Plant Iterations
1 1 20 2 8


Simulation Control

Do Zone Sizing Do System Sizing Do Plant Sizing Do Design Days Do Weather Simulation Do HVAC Sizing Simulation
1 Yes Yes Yes No Yes No


Performance Precision Tradeoffs

Use Coil Direct Simulation Zone Radiant Exchange Algorithm Override Mode Number of Timestep In Hour Force Euler Method Minimum Number of Warmup Days Force Suppress All Begin Environment Resets Minimum System Timestep MaxZoneTempDiff MaxAllowedDelTemp
1 No ScriptF Normal 6 No 1 No 1.0 0.300 2.0000E-003


Output Reporting Tolerances

Tolerance for Time Heating Setpoint Not Met Tolerance for Zone Cooling Setpoint Not Met Time
1 0.556 0.556


Site:GroundTemperature:BuildingSurface

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00


Site:GroundTemperature:FCfactorMethod

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 9.30 6.70 4.10 4.20 4.20 5.90 9.00 10.00 13.30 15.00 15.70 13.40


Site:GroundTemperature:Shallow

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00


Site:GroundTemperature:Deep

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00


Site:GroundReflectance

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:SnowModifier

Normal Daylighting {dimensionless}
1 1.000 1.000


Site:GroundReflectance:Snow

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:Snow:Daylighting

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Environment:Weather Station

Wind Sensor Height Above Ground {m} Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Sensor Height Above Ground {m} Wind Speed Modifier Coefficient-Internal Temperature Modifier Coefficient-Internal
1 10.000 0.140 270.000 1.500 1.586 9.750E-003


Site:Location

Location Name Latitude {N+/S- Deg} Longitude {E+/W- Deg} Time Zone Number {GMT+/-} Elevation {m} Standard Pressure at Elevation {Pa} Standard RhoAir at Elevation
1 William R Fairchild WA USA TMY3 WMO#=727885 48.12 -123.50 -8.00 91.00 100237 1.1914


Site Water Mains Temperature Information

Calculation Method{} Water Mains Temperature Schedule Name{} Annual Average Outdoor Air Temperature{C} Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} Fixed Default Water Mains Temperature{C}
1 Correlation NA 9.23 11.60 NA


Building Information

Building Name North Axis {deg} Terrain Loads Convergence Tolerance Value Temperature Convergence Tolerance Value Solar Distribution Maximum Number of Warmup Days Minimum Number of Warmup Days
1 HotelLarge 0.000 City 4.00000E-002 0.20000 FullInteriorAndExterior 25 6


Inside Convection Algorithm

Algorithm {Simple
TARP
CeilingDiffuser
AdaptiveConvectionAlgorithm}
1 TARP


Outside Convection Algorithm

Algorithm {SimpleCombined
TARP
MoWitt
DOE-2
AdaptiveConvectionAlgorithm}
1 DOE-2


Sky Radiance Distribution

Value {Anisotropic}
1 Anisotropic


Zone Air Solution Algorithm

Value {ThirdOrderBackwardDifference
AnalyticalSolution
EulerMethod}
1 ThirdOrderBackwardDifference


Zone Air Carbon Dioxide Balance Simulation

Simulation {Yes/No} Carbon Dioxide Concentration
1 No N/A


Zone Air Generic Contaminant Balance Simulation

Simulation {Yes/No} Generic Contaminant Concentration
1 No N/A


Zone Air Mass Flow Balance Simulation

Enforce Mass Balance



Adjust Zone Mixing and Return {AdjustMixingOnly
AdjustReturnOnly
AdjustMixingThenReturn
AdjustReturnThenMixing
None}
Adjust Zone Infiltration {AddInfiltration
AdjustInfiltration
None}

Infiltration Zones {MixingSourceZonesOnly
AllZones}


1 No N/A N/A N/A


HVACSystemRootFindingAlgorithm

Value {RegulaFalsi
Bisection
BisectionThenRegulaFalsi
RegulaFalsiThenBisection}
1 RegulaFalsi


Environment:Site Atmospheric Variation

Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Gradient Coefficient {K/m}
1 0.330 460.000 6.500000E-003


Surface Geometry

Starting Corner Vertex Input Direction Coordinate System Daylight Reference Point Coordinate System Rectangular (Simple) Surface Coordinate System
1 UpperLeftCorner Counterclockwise RelativeCoordinateSystem RelativeCoordinateSystem RelativeToZoneOrigin


Surface Heat Transfer Algorithm

Value {CTF - ConductionTransferFunction
EMPD - MoisturePenetrationDepthConductionTransferFunction
CondFD - ConductionFiniteDifference
HAMT - CombinedHeatAndMoistureFiniteElement} - Description
Inside Surface Max Temperature Limit{C}


Surface Convection Coefficient Lower Limit {W/m2-K}


Surface Convection Coefficient Upper Limit {W/m2-K}


1 CTF - ConductionTransferFunction 200 0.10 1000.0


Shading Summary

Number of Fixed Detached Shades Number of Building Detached Shades Number of Attached Shades
1 0 0 0


Zone Summary

Number of Zones Number of Zone Surfaces Number of SubSurfaces
1 22 235 36


Zone Information

Zone Name North Axis {deg} Origin X-Coordinate {m} Origin Y-Coordinate {m} Origin Z-Coordinate {m} Centroid X-Coordinate {m} Centroid Y-Coordinate {m} Centroid Z-Coordinate {m} Type Zone Multiplier Zone List Multiplier Minimum X {m} Maximum X {m} Minimum Y {m} Maximum Y {m} Minimum Z {m} Maximum Z {m} Ceiling Height {m} Volume {m3} Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} Floor Area {m2} Exterior Gross Wall Area {m2} Exterior Net Wall Area {m2} Exterior Window Area {m2} Number of Surfaces Number of SubSurfaces Number of Shading SubSurfaces Part of Total Building Area
1 BASEMENT 0.0 0.00 0.00 0.00 41.45 11.51 -1.22 1 1 1 0.00 86.56 0.00 22.86 -2.44 0.00 2.44 4826.41 TARP DOE-2 1978.83 0.00 0.00 0.00 13 0 0 Yes
2 RETAIL_1_FLR_1 0.0 0.00 0.00 0.00 5.79 2.90 1.98 1 1 1 0.00 11.58 0.00 5.79 0.00 3.96 3.96 265.76 TARP DOE-2 67.07 68.84 45.58 23.26 6 1 0 Yes
3 RETAIL_2_FLR_1 0.0 0.00 0.00 0.00 5.79 9.14 1.98 1 1 1 0.00 11.58 5.79 12.50 0.00 3.96 3.96 307.76 TARP DOE-2 77.67 26.57 24.62 0.00 6 1 0 Yes
4 MECH_FLR_1 0.0 0.00 0.00 0.00 61.87 17.68 1.98 1 1 1 53.95 69.80 12.50 22.86 0.00 3.96 3.96 650.80 TARP DOE-2 164.24 62.80 62.80 0.00 6 0 0 Yes
5 STORAGE_FLR_1 0.0 0.00 0.00 0.00 74.37 17.68 1.98 1 1 1 69.80 78.94 12.50 22.86 0.00 3.96 3.96 375.47 TARP DOE-2 94.76 36.23 28.80 0.00 6 1 0 Yes
6 LAUNDRY_FLR_1 0.0 0.00 0.00 0.00 84.28 14.33 1.98 1 1 1 81.99 86.56 5.79 22.86 0.00 3.96 3.96 309.22 TARP DOE-2 78.04 85.75 83.80 0.00 6 1 0 Yes
7 CAFE_FLR_1 0.0 0.00 0.00 0.00 70.26 2.90 1.98 1 1 1 53.95 86.56 0.00 5.79 0.00 3.96 3.96 748.35 TARP DOE-2 188.86 152.17 84.72 65.50 7 2 0 Yes
8 LOBBY_FLR_1 0.0 0.00 0.00 0.00 38.29 12.45 1.98 1 1 1 0.00 81.99 0.00 22.86 0.00 3.96 3.96 5183.56 TARP DOE-2 1308.19 434.79 345.80 85.08 18 3 0 Yes
9 ROOM_1_FLR_3 0.0 0.00 0.00 0.00 2.29 10.06 8.53 1 4 1 0.00 4.57 5.79 14.33 7.01 10.06 3.05 118.94 TARP DOE-2 39.02 39.95 26.77 13.18 6 2 0 Yes
10 ROOM_2_FLR_3 0.0 0.00 0.00 0.00 2.29 18.59 8.53 1 4 1 0.00 4.57 14.33 22.86 7.01 10.06 3.05 118.93 TARP DOE-2 39.02 39.95 26.76 13.18 6 2 0 Yes
11 ROOM_3_MULT19_FLR_3 0.0 0.00 0.00 0.00 8.53 9.14 8.53 1 76 1 6.71 10.36 5.79 12.50 7.01 10.06 3.05 74.75 TARP DOE-2 24.52 11.15 7.47 3.68 6 1 0 Yes
12 ROOM_4_MULT19_FLR_3 0.0 0.00 0.00 0.00 12.19 19.51 8.53 1 76 1 10.36 14.02 16.15 22.86 7.01 10.06 3.05 74.77 TARP DOE-2 24.53 11.15 7.47 3.68 6 1 0 Yes
13 ROOM_5_FLR_3 0.0 0.00 0.00 0.00 84.28 10.06 8.53 1 4 1 81.99 86.56 5.79 14.33 7.01 10.06 3.05 118.94 TARP DOE-2 39.02 39.95 26.77 13.18 6 2 0 Yes
14 ROOM_6_FLR_3 0.0 0.00 0.00 0.00 84.28 18.59 8.53 1 4 1 81.99 86.56 14.33 22.86 7.01 10.06 3.05 118.93 TARP DOE-2 39.02 39.95 26.76 13.18 6 2 0 Yes
15 CORRIDOR_FLR_3 0.0 0.00 0.00 0.00 43.28 14.33 8.53 1 4 1 4.57 81.99 5.79 22.86 7.01 10.06 3.05 1186.91 TARP DOE-2 389.40 48.31 32.37 15.94 20 4 0 Yes
16 ROOM_1_FLR_6 0.0 0.00 0.00 0.00 2.29 10.06 17.68 1 1 1 0.00 4.57 5.79 14.33 16.15 19.20 3.05 118.94 TARP DOE-2 39.02 39.95 26.77 13.18 6 2 0 Yes
17 ROOM_2_FLR_6 0.0 0.00 0.00 0.00 2.29 18.59 17.68 1 1 1 0.00 4.57 14.33 22.86 16.15 19.20 3.05 118.93 TARP DOE-2 39.02 39.95 26.76 13.18 6 2 0 Yes
18 ROOM_3_MULT9_FLR_6 0.0 0.00 0.00 0.00 7.93 7.62 17.68 1 9 1 4.57 11.28 5.79 9.45 16.15 19.20 3.05 74.77 TARP DOE-2 24.53 20.44 13.70 6.74 6 1 0 Yes
19 BANQUET_FLR_6 0.0 0.00 0.00 0.00 26.37 17.68 17.68 1 1 1 10.36 42.37 12.50 22.86 16.15 19.20 3.05 1010.89 TARP DOE-2 331.66 97.55 65.36 32.19 6 1 0 Yes
20 DINING_FLR_6 0.0 0.00 0.00 0.00 63.55 17.68 17.68 1 1 1 47.55 79.55 12.50 22.86 16.15 19.20 3.05 1010.89 TARP DOE-2 331.66 97.55 65.36 32.19 6 1 0 Yes
21 KITCHEN_FLR_6 0.0 0.00 0.00 0.00 82.99 14.11 17.68 1 1 1 79.55 86.56 5.79 22.86 16.15 19.20 3.05 314.87 TARP DOE-2 103.30 87.33 60.96 26.37 8 3 0 Yes
22 CORRIDOR_FLR_6 0.0 0.00 0.00 0.00 41.51 13.35 17.68 1 1 1 4.57 81.99 5.79 22.86 16.15 19.20 3.05 1256.16 TARP DOE-2 412.12 85.47 57.27 28.20 15 3 0 Yes


Zone Internal Gains Nominal

Zone Name Floor Area {m2} # Occupants Area per Occupant {m2/person} Occupant per Area {person/m2} Interior Lighting {W/m2} Electric Load {W/m2} Gas Load {W/m2} Other Load {W/m2} Hot Water Eq {W/m2} Steam Equipment {W/m2} Sum Loads per Area {W/m2} Outdoor Controlled Baseboard Heat
1 BASEMENT 1978.83 106.5 18.581 5.382E-002 8.749 5.380 0.000 0.000 0.000 0.000 14.129 No
2 RETAIL_1_FLR_1 67.07 10.8 6.194 0.161 13.012 10.760 0.000 0.000 0.000 0.000 23.772 No
3 RETAIL_2_FLR_1 77.67 12.5 6.194 0.161 13.012 10.760 0.000 0.000 0.000 0.000 23.772 No
4 MECH_FLR_1 164.24 2.7 61.932 1.615E-002 10.064 5.380 0.000 0.000 0.000 0.000 15.444 No
5 STORAGE_FLR_1 94.76 2.0 46.451 2.153E-002 7.319 2.690 0.000 0.000 0.000 0.000 10.009 No
6 LAUNDRY_FLR_1 78.04 8.4 9.290 0.108 5.490 61.680 535.850 0.000 0.000 0.000 603.020 No
7 CAFE_FLR_1 188.86 142.3 1.327 0.753 12.809 5.380 0.000 0.000 0.000 0.000 18.189 No
8 LOBBY_FLR_1 1308.19 422.4 3.097 0.323 10.064 8.070 0.000 0.000 0.000 0.000 18.134 No
9 ROOM_1_FLR_3 39.02 1.5 26.015 3.844E-002 10.064 6.750 0.000 0.000 0.000 0.000 16.814 No
10 ROOM_2_FLR_3 39.02 1.5 26.012 3.844E-002 10.064 6.750 0.000 0.000 0.000 0.000 16.814 No
11 ROOM_3_MULT19_FLR_3 24.52 1.5 16.349 6.116E-002 10.064 10.520 0.000 0.000 0.000 0.000 20.584 No
12 ROOM_4_MULT19_FLR_3 24.53 1.5 16.354 6.115E-002 10.064 10.520 0.000 0.000 0.000 0.000 20.584 No
13 ROOM_5_FLR_3 39.02 1.5 26.015 3.844E-002 10.064 6.750 0.000 0.000 0.000 0.000 16.814 No
14 ROOM_6_FLR_3 39.02 1.5 26.012 3.844E-002 10.064 6.750 0.000 0.000 0.000 0.000 16.814 No
15 CORRIDOR_FLR_3 389.40 21.0 18.581 5.382E-002 3.660 0.000 0.000 0.000 0.000 0.000 3.660 No
16 ROOM_1_FLR_6 39.02 1.5 26.015 3.844E-002 10.064 6.750 0.000 0.000 0.000 0.000 16.814 No
17 ROOM_2_FLR_6 39.02 1.5 26.012 3.844E-002 10.064 6.750 0.000 0.000 0.000 0.000 16.814 No
18 ROOM_3_MULT9_FLR_6 24.53 1.5 16.354 6.115E-002 10.064 10.520 0.000 0.000 0.000 0.000 20.584 No
19 BANQUET_FLR_6 331.66 249.9 1.327 0.753 12.809 67.820 0.000 0.000 0.000 0.000 80.629 No
20 DINING_FLR_6 331.66 249.9 1.327 0.753 12.809 67.820 0.000 0.000 0.000 0.000 80.629 No
21 KITCHEN_FLR_6 103.30 22.2 4.645 0.215 10.979 517.156 2419.260 0.000 0.000 0.000 2947.395 No
22 CORRIDOR_FLR_6 412.12 22.2 18.581 5.382E-002 3.660 0.000 0.000 0.000 0.000 0.000 3.660 No


People Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Number of People {} People/Floor Area {person/m2} Floor Area per person {m2/person} Fraction Radiant Fraction Convected Sensible Fraction Calculation Activity level ASHRAE 55 Warnings Carbon Dioxide Generation Rate Nominal Minimum Number of People Nominal Maximum Number of People MRT Calculation Type Work Efficiency Clothing Insulation Calculation Method Clothing Insulation Calculation Method Schedule Clothing Air Velocity Fanger Calculation Pierce Calculation KSU Calculation Cooling Effect Calculation Ankle Draft Calculation
1 BASEMENT PEOPLE BLDG_OCC_SCH BASEMENT 1978.83 106.5 106.5 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 106 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
2 RETAIL_1_FLR_1 PEOPLE BLDG_OCC_SCH RETAIL_1_FLR_1 67.07 10.8 10.8 0.161 6.194 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
3 RETAIL_2_FLR_1 PEOPLE BLDG_OCC_SCH RETAIL_2_FLR_1 77.67 12.5 12.5 0.161 6.194 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 13 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
4 LAUNDRY_FLR_1 PEOPLE BLDG_OCC_SCH LAUNDRY_FLR_1 78.04 8.4 8.4 0.108 9.290 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 8 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
5 CAFE_FLR_1 PEOPLE BLDG_OCC_SCH CAFE_FLR_1 188.86 142.3 142.3 0.753 1.327 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 142 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
6 LOBBY_FLR_1 PEOPLE BLDG_OCC_SCH LOBBY_FLR_1 1308.19 422.4 422.4 0.323 3.097 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 422 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
7 ROOM_1_FLR_3 PEOPLE GUESTROOM_OCC_SCH ROOM_1_FLR_3 39.02 1.5 1.5 3.844E-002 26.015 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
8 ROOM_2_FLR_3 PEOPLE GUESTROOM_OCC_SCH ROOM_2_FLR_3 39.02 1.5 1.5 3.844E-002 26.012 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
9 ROOM_3_MULT19_FLR_3 PEOPLE ALWAYS_OFF ROOM_3_MULT19_FLR_3 24.52 1.5 1.5 6.116E-002 16.349 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 0 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
10 ROOM_4_MULT19_FLR_3 PEOPLE GUESTROOM_OCC_SCH ROOM_4_MULT19_FLR_3 24.53 1.5 1.5 6.115E-002 16.354 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
11 ROOM_5_FLR_3 PEOPLE GUESTROOM_OCC_SCH ROOM_5_FLR_3 39.02 1.5 1.5 3.844E-002 26.015 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
12 ROOM_6_FLR_3 PEOPLE GUESTROOM_OCC_SCH ROOM_6_FLR_3 39.02 1.5 1.5 3.844E-002 26.012 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
13 ROOM_1_FLR_6 PEOPLE GUESTROOM_OCC_SCH ROOM_1_FLR_6 39.02 1.5 1.5 3.844E-002 26.015 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
14 ROOM_2_FLR_6 PEOPLE GUESTROOM_OCC_SCH ROOM_2_FLR_6 39.02 1.5 1.5 3.844E-002 26.012 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
15 ROOM_3_MULT9_FLR_6 PEOPLE GUESTROOM_OCC_SCH ROOM_3_MULT9_FLR_6 24.53 1.5 1.5 6.115E-002 16.354 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
16 BANQUET_FLR_6 PEOPLE BLDG_OCC_SCH BANQUET_FLR_6 331.66 249.9 249.9 0.753 1.327 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 250 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
17 DINING_FLR_6 PEOPLE BLDG_OCC_SCH DINING_FLR_6 331.66 249.9 249.9 0.753 1.327 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 250 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
18 KITCHEN_FLR_6 PEOPLE BLDG_OCC_SCH KITCHEN_FLR_6 103.30 22.2 22.2 0.215 4.645 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 22 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
19 STORAGE_FLR_1 PEOPLE BLDG_OCC_SCH STORAGE_FLR_1 94.76 2.0 2.0 2.153E-002 46.451 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
20 CORRIDOR_FLR_3 PEOPLE BLDG_OCC_SCH CORRIDOR_FLR_3 389.40 21.0 21.0 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 21 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
21 CORRIDOR_FLR_6 PEOPLE BLDG_OCC_SCH CORRIDOR_FLR_6 412.12 22.2 22.2 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 22 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
22 MECH_FLR_1 PEOPLE BLDG_OCC_SCH MECH_FLR_1 164.24 2.7 2.7 1.615E-002 61.932 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 3 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No


Lights Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Lighting Level {W} Lights/Floor Area {W/m2} Lights per person {W/person} Fraction Return Air Fraction Radiant Fraction Short Wave Fraction Convected Fraction Replaceable End-Use Category Nominal Minimum Lighting Level {W} Nominal Maximum Lighting Level {W}
1 BASEMENT_LIGHTS LTG_SCH_BASEMENT BASEMENT 1978.83 106.5 17313.725 8.749 162.572 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 17313.725
2 RETAIL_1_FLR_1_LIGHTS LTG_SCH_RETAIL RETAIL_1_FLR_1 67.07 10.8 872.757 13.012 80.594 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 872.757
3 RETAIL_2_FLR_1_LIGHTS LTG_SCH_RETAIL RETAIL_2_FLR_1 77.67 12.5 1010.656 13.012 80.595 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1010.656
4 MECH_FLR_1_LIGHTS LTG_SCH_MECHANIC MECH_FLR_1 164.24 2.7 1652.984 10.064 623.297 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1652.984
5 STORAGE_FLR_1_LIGHTS LTG_SCH_STORAGE STORAGE_FLR_1 94.76 2.0 693.586 7.319 339.993 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 693.586
6 LAUNDRY_FLR_1_LIGHTS LTG_SCH_LAUNDRY LAUNDRY_FLR_1 78.04 8.4 428.405 5.490 51.001 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 428.405
7 CAFE_FLR_1_LIGHTS LTG_SCH_DINING CAFE_FLR_1 188.86 142.3 2419.140 12.809 17.000 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2419.140
8 LOBBY_FLR_1_LIGHTS LTG_SCH_LOBBY LOBBY_FLR_1 1308.19 422.4 13165.908 10.064 31.167 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 13165.908
9 ROOM_1_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_1_FLR_3 39.02 1.5 392.727 10.064 261.818 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 392.727
10 ROOM_2_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_2_FLR_3 39.02 1.5 392.681 10.064 261.787 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 392.681
11 ROOM_3_MULT19_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_3_MULT19_FLR_3 24.52 1.5 246.814 10.064 164.543 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 246.814
12 ROOM_4_MULT19_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_4_MULT19_FLR_3 24.53 1.5 246.881 10.064 164.588 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 246.881
13 ROOM_5_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_5_FLR_3 39.02 1.5 392.727 10.064 261.818 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 392.727
14 ROOM_6_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_6_FLR_3 39.02 1.5 392.681 10.064 261.787 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 392.681
15 CORRIDOR_FLR_3_LIGHTS LTG_SCH_CORRIDOR CORRIDOR_FLR_3 389.40 21.0 1425.114 3.660 68.002 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1425.114
16 ROOM_1_FLR_6_LIGHTS LTG_SCH_GUESTROOM ROOM_1_FLR_6 39.02 1.5 392.727 10.064 261.818 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 392.727
17 ROOM_2_FLR_6_LIGHTS LTG_SCH_GUESTROOM ROOM_2_FLR_6 39.02 1.5 392.681 10.064 261.787 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 392.681
18 ROOM_3_MULT9_FLR_6_LIGHTS LTG_SCH_GUESTROOM ROOM_3_MULT9_FLR_6 24.53 1.5 246.881 10.064 164.588 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 246.881
19 BANQUET_FLR_6_LIGHTS LTG_SCH_DINING BANQUET_FLR_6 331.66 249.9 4248.214 12.809 17.000 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 4248.214
20 DINING_FLR_6_LIGHTS LTG_SCH_DINING DINING_FLR_6 331.66 249.9 4248.214 12.809 17.000 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 4248.214
21 KITCHEN_FLR_6_LIGHTS LTG_SCH_KITCHEN KITCHEN_FLR_6 103.30 22.2 1134.198 10.979 51.003 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1134.198
22 CORRIDOR_FLR_6_LIGHTS LTG_SCH_CORRIDOR CORRIDOR_FLR_6 412.12 22.2 1508.264 3.660 68.001 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1508.264


ElectricEquipment Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Equipment Level {W} Equipment/Floor Area {W/m2} Equipment per person {W/person} Fraction Latent Fraction Radiant Fraction Lost Fraction Convected End-Use SubCategory Nominal Minimum Equipment Level {W} Nominal Maximum Equipment Level {W}
1 BASEMENT_MISCPLUG_EQUIP BASEMENT_EQUIP_SCH BASEMENT 1978.83 106.5 10646.106 5.380 99.964 0.000 0.500 0.000 0.500 MiscPlug 0.000 10646.106
2 RETAIL_1_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH RETAIL_1_FLR_1 67.07 10.8 721.688 10.760 66.644 0.000 0.500 0.000 0.500 MiscPlug 0.000 721.688
3 RETAIL_2_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH RETAIL_2_FLR_1 77.67 12.5 835.717 10.760 66.644 0.000 0.500 0.000 0.500 MiscPlug 0.000 835.717
4 MECH_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH MECH_FLR_1 164.24 2.7 883.628 5.380 333.193 0.000 0.500 0.000 0.500 MiscPlug 0.000 883.628
5 STORAGE_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH STORAGE_FLR_1 94.76 2.0 254.902 2.690 124.952 0.000 0.500 0.000 0.500 MiscPlug 0.000 254.902
6 LAUNDRY_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH LAUNDRY_FLR_1 78.04 8.4 4813.474 61.680 573.033 0.000 0.500 0.000 0.500 MiscPlug 0.000 4813.474
7 CAFE_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH CAFE_FLR_1 188.86 142.3 1016.077 5.380 7.140 0.000 0.500 0.000 0.500 MiscPlug 0.000 1016.077
8 LOBBY_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH LOBBY_FLR_1 1308.19 422.4 10557.062 8.070 24.991 0.000 0.500 0.000 0.500 MiscPlug 0.000 10557.062
9 ROOM_1_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_BASE ROOM_1_FLR_3 39.02 1.5 263.399 6.750 175.599 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.399
10 ROOM_2_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_BASE ROOM_2_FLR_3 39.02 1.5 263.368 6.750 175.579 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.368
11 ROOM_3_MULT19_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_BASE ROOM_3_MULT19_FLR_3 24.52 1.5 257.991 10.520 171.994 0.000 0.500 0.000 0.500 MiscPlug 0.000 257.991
12 ROOM_4_MULT19_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_BASE ROOM_4_MULT19_FLR_3 24.53 1.5 258.061 10.520 172.041 0.000 0.500 0.000 0.500 MiscPlug 0.000 258.061
13 ROOM_5_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_BASE ROOM_5_FLR_3 39.02 1.5 263.399 6.750 175.599 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.399
14 ROOM_6_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_BASE ROOM_6_FLR_3 39.02 1.5 263.368 6.750 175.579 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.368
15 ROOM_1_FLR_6_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_BASE ROOM_1_FLR_6 39.02 1.5 263.399 6.750 175.599 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.399
16 ROOM_2_FLR_6_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_BASE ROOM_2_FLR_6 39.02 1.5 263.368 6.750 175.579 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.368
17 ROOM_3_MULT9_FLR_6_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_BASE ROOM_3_MULT9_FLR_6 24.53 1.5 258.061 10.520 172.041 0.000 0.500 0.000 0.500 MiscPlug 0.000 258.061
18 BANQUET_FLR_6_MISCPLUG_EQUIP KITCHEN_ELEC_EQUIP_SCH BANQUET_FLR_6 331.66 249.9 22493.008 67.820 90.009 0.000 0.500 0.000 0.500 Cooking 0.000 6747.903
19 DINING_FLR_6_MISCPLUG_EQUIP KITCHEN_ELEC_EQUIP_SCH DINING_FLR_6 331.66 249.9 22493.008 67.820 90.009 0.000 0.500 0.000 0.500 Cooking 0.000 6747.903
20 KITCHEN_FLR_6_MISCELEC_EQUIP KITCHEN_ELEC_EQUIP_SCH KITCHEN_FLR_6 103.30 22.2 52482.799 508.040 2360.050 0.200 0.500 0.100 0.200 Cooking 0.000 15744.840
21 KITCHEN_FLR_6_REACH-IN-FREEZER ALWAYS_ON KITCHEN_FLR_6 103.30 22.2 515.917 4.994 23.200 0.000 0.250 0.000 0.750 ReachInFreezer 515.917 515.917
22 KITCHEN_FLR_6_REACH-IN-REFRIGERATOR ALWAYS_ON KITCHEN_FLR_6 103.30 22.2 425.833 4.122 19.149 0.000 0.250 0.000 0.750 ReachInRefrigerator 425.833 425.833


GasEquipment Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Equipment Level {W} Equipment/Floor Area {W/m2} Equipment per person {W/person} Fraction Latent Fraction Radiant Fraction Lost Fraction Convected End-Use SubCategory Nominal Minimum Equipment Level {W} Nominal Maximum Equipment Level {W}
1 LAUNDRY_FLR_1_MISCGAS_EQUIP BLDG_EQUIP_SCH LAUNDRY_FLR_1 78.04 8.4 41817.449 535.850 4978.268 0.000 0.500 0.000 0.500 Laundry 0.000 41817.449
2 KITCHEN_FLR_6_MISCGAS_EQUIP KITCHEN_GAS_EQUIP_SCH KITCHEN_FLR_6 103.30 22.2 249920.353 2419.260 11238.437 0.100 0.200 0.700 0.000 Cooking 0.000 74976.106


Construction CTF

Construction Name Index #Layers #CTFs Time Step {hours} ThermalConductance {w/m2-K} OuterThermalAbsorptance InnerThermalAbsorptance OuterSolarAbsorptance InnerSolarAbsorptance Roughness
1 SWINGING DOOR_CON 1 1 1 0.167 2.101 0.900 0.900 0.700 0.700 MediumRough
2 OVERHEAD DOOR_CON 2 1 1 0.167 1.198 0.900 0.900 0.700 0.700 MediumRough
3 INTERIORFURNISHINGS 3 1 9 0.167 0.8000 0.900 0.900 0.700 0.700 MediumSmooth
4 INT_WALL 8 2 4 0.167 6.299 0.900 0.900 0.700 0.700 Smooth
5 NONRES_ROOF 18 3 3 0.167 0.2284 0.900 0.900 0.770 0.700 Rough
6 RES_ROOF 19 3 3 0.167 0.2284 0.900 0.900 0.770 0.700 Rough
7 NONRES_EXT_WALL_GRD 21 3 9 0.167 0.7376 0.900 0.900 0.700 0.700 MediumRough
8 NONRES_EXT_WALL_MID 22 3 9 0.167 1.016 0.900 0.900 0.700 0.700 MediumRough
9 NONRES_EXT_WALL_TOP 23 3 9 0.167 1.081 0.900 0.900 0.700 0.700 MediumRough
10 RES_EXT_WALL_MID 25 3 9 0.167 1.016 0.900 0.900 0.700 0.700 MediumRough
11 RES_EXT_WALL_TOP 26 3 9 0.167 1.081 0.900 0.900 0.700 0.700 MediumRough
12 NONRES_FLOOR 30 3 7 0.167 0.1963 0.900 0.900 0.700 0.700 MediumSmooth
13 NONRES_FLOOR_CEILING 33 3 7 0.167 0.1963 0.900 0.900 0.700 0.700 VeryRough
14 BASEMENT_FLOOR 36 2 7 0.333 2.705 0.900 0.900 0.700 0.700 MediumRough
15 BASEMENT_WALL_NORTH_CFACTOR 39 2 7 0.167 0.4185 0.000 0.900 0.000 0.700 MediumRough
16 BASEMENT_WALL_EAST_CFACTOR 40 2 7 0.167 0.4185 0.000 0.900 0.000 0.700 MediumRough
17 BASEMENT_WALL_SOUTH_CFACTOR 41 2 7 0.167 0.4185 0.000 0.900 0.000 0.700 MediumRough
18 BASEMENT_WALL_WEST_CFACTOR 42 2 7 0.167 0.4185 0.000 0.900 0.000 0.700 MediumRough


Material CTF Summary

Material Name Thickness {m} Conductivity {w/m-K} Density {kg/m3} Specific Heat {J/kg-K} ThermalResistance {m2-K/w}
1 OPAQUE DOOR PANEL_CON 0.0000 0.000 0.000 0.000 0.4760
2 OVERHEAD DOOR_CON PANEL 0.0000 0.000 0.000 0.000 0.8346
3 STD WOOD 6INCH 0.1500 0.120 540.000 1210.000 1.250
4 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
5 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
6 F13 BUILT-UP ROOFING 0.0095 0.160 1120.000 1460.000 0.5938E-01
7 NONRES_ROOF_INSULATION 0.0000 0.000 0.000 0.000 4.319
8 F08 METAL SURFACE 0.0008 45.280 7824.000 500.000 0.1767E-04
9 F13 BUILT-UP ROOFING 0.0095 0.160 1120.000 1460.000 0.5938E-01
10 RES_ROOF_INSULATION 0.0000 0.000 0.000 0.000 4.319
11 F08 METAL SURFACE 0.0008 45.280 7824.000 500.000 0.1767E-04
12 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
13 NONRES_EXTERIOR_WALL_INSULATION_GRD 0.0000 0.000 0.000 0.000 1.188
14 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
15 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
16 NONRES_EXTERIOR_WALL_INSULATION_MID 0.0000 0.000 0.000 0.000 0.8173
17 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
18 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
19 NONRES_EXTERIOR_WALL_INSULATION_TOP 0.0000 0.000 0.000 0.000 0.7574
20 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
21 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
22 RES_EXTERIOR_WALL_INSULATION_MID 0.0000 0.000 0.000 0.000 0.8173
23 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
24 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
25 RES_EXTERIOR_WALL_INSULATION_TOP 0.0000 0.000 0.000 0.000 0.7574
26 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
27 NONRES_FLOOR_INSULATION 0.0000 0.000 0.000 0.000 4.833
28 100MM NORMALWEIGHT CONCRETE FLOOR 0.1016 2.310 2322.000 832.000 0.4398E-01
29 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
30 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
31 100MM NORMALWEIGHT CONCRETE FLOOR 0.1016 2.310 2322.000 832.000 0.4398E-01
32 NONRES_FLOOR_INSULATION 0.0000 0.000 0.000 0.000 4.833
33 M10 200MM CONCRETE BLOCK BASEMENT WALL 0.2032 1.326 1842.000 912.000 0.1532
34 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
35 ~FC_Insulation_1 0.0000 0.000 0.000 0.000 2.312
36 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
37 ~FC_Insulation_2 0.0000 0.000 0.000 0.000 2.312
38 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
39 ~FC_Insulation_3 0.0000 0.000 0.000 0.000 2.312
40 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
41 ~FC_Insulation_4 0.0000 0.000 0.000 0.000 2.312
42 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01


CTF

Time Outside Cross Inside Flux (except final one)
1 1 0.0000000 0.0000000 -0.0000000 -0.0000000
2 0 2.1009573 2.1009573 2.1009573  
3 1 0.0000000 0.0000000 -0.0000000 -0.0000000
4 0 1.1981135 1.1981135 1.1981135  
5 9 -0.27580628E-02 0.97439125E-12 -0.27580628E-02 0.28516790E-03
6 8 0.73590997E-01 0.21837543E-08 0.73590997E-01 -0.77836043E-02
7 7 -0.82599318 0.23162835E-06 -0.82599318 0.89703933E-01
8 6 5.1113916 0.48671053E-05 5.1113916 -0.57224845
9 5 -19.214933 0.30163627E-04 -19.214933 2.2266322
10 4 45.557404 0.63181060E-04 45.557404 -5.4853312
11 3 -68.275533 0.44785456E-04 -68.275533 8.5710568
12 2 62.555368 0.93952058E-05 62.555368 -8.2111738
13 1 -31.904423 0.39200004E-06 -31.904423 4.3886678
14 0 6.9260389 0.77047546E-09 6.9260389  
15 4 0.68458728E-09 0.26079551E-09 0.68458728E-09 -0.34507121E-18
16 3 -0.72180374E-03 0.24295686E-03 -0.72180374E-03 0.69691454E-09
17 2 0.83054762 0.27682775 0.83054762 -0.35168967E-03
18 1 -12.650482 3.3590720 -12.650482 0.19281313
19 0 16.907513 1.4507143 16.907513  
20 3 -0.62451068E-06 0.10350887E-08 -0.38276125E-05 0.11995084E-16
21 2 0.77976586 0.13989883E-02 1.0579789 -0.73382352E-06
22 1 -21.958702 0.93426804E-01 -6.3215779 0.20283230
23 0 21.361010 0.87247630E-01 5.4456762  
24 3 -0.62451068E-06 0.10350887E-08 -0.38276125E-05 0.11995084E-16
25 2 0.77976586 0.13989883E-02 1.0579789 -0.73382352E-06
26 1 -21.958702 0.93426804E-01 -6.3215779 0.20283230
27 0 21.361010 0.87247630E-01 5.4456762  
28 9 -0.36178815E-14 0.27139057E-16 -0.15868385E-09 0.72384540E-16
29 8 0.23132903E-07 0.10021651E-12 0.39088690E-03 -0.26302905E-09
30 7 -0.12631865E-01 0.51350721E-08 -0.23647662E-01 0.14362891E-03
31 6 0.41595524 0.17798199E-05 0.48111272 -0.48727686E-02
32 5 -5.2940477 0.66244475E-04 -4.5105076 0.64467011E-01
33 4 33.460551 0.54034224E-03 21.710910 -0.42819988
34 3 -112.19991 0.11746209E-02 -56.158897 1.5292621
35 2 198.09612 0.65921779E-03 78.365567 -2.9160408
36 1 -171.52093 0.70225444E-04 -55.397708 2.7518339
37 0 57.057407 0.39880044E-06 15.535293  
38 9 -0.27488611E-15 0.34931277E-16 -0.14567168E-09 -0.34479422E-18
39 8 0.21305634E-07 0.13616114E-12 0.37179150E-03 -0.24225240E-09
40 7 -0.12062412E-01 0.71136536E-08 -0.22827857E-01 0.13715401E-03
41 6 0.40048261 0.24848663E-05 0.46794369 -0.46903832E-02
42 5 -5.1430590 0.93107898E-04 -4.4094005 0.62594814E-01
43 4 32.792724 0.76407468E-03 21.315792 -0.41933293
44 3 -110.77914 0.16699767E-02 -55.377787 1.5087354
45 2 196.68811 0.94174532E-03 77.649029 -2.8936813
46 1 -171.00089 0.10077048E-03 -55.189078 2.7427195
47 0 57.057407 0.57514079E-06 15.569530  
48 9 0.31336604E-16 0.39008580E-16 -0.14256869E-09 0.20136749E-17
49 8 0.20868940E-07 0.14443760E-12 0.36714717E-03 -0.23728702E-09
50 7 -0.11923636E-01 0.75824706E-08 -0.22627983E-01 0.13557608E-03
51 6 0.39671154 0.26538398E-05 0.46472729 -0.46459316E-02
52 5 -5.1062546 0.99607489E-04 -4.3846760 0.62138459E-01
53 4 32.629908 0.81865718E-03 21.219102 -0.41717122
54 3 -110.43267 0.17916944E-02 -55.186609 1.5037299
55 2 196.34465 0.10116009E-02 77.473776 -2.8882273
56 1 -170.87399 0.10836560E-03 -55.138279 2.7404955
57 0 57.057407 0.61925266E-06 15.578052  
58 9 -0.27488611E-15 0.34931277E-16 -0.14567168E-09 -0.34479422E-18
59 8 0.21305634E-07 0.13616114E-12 0.37179150E-03 -0.24225240E-09
60 7 -0.12062412E-01 0.71136536E-08 -0.22827857E-01 0.13715401E-03
61 6 0.40048261 0.24848663E-05 0.46794369 -0.46903832E-02
62 5 -5.1430590 0.93107898E-04 -4.4094005 0.62594814E-01
63 4 32.792724 0.76407468E-03 21.315792 -0.41933293
64 3 -110.77914 0.16699767E-02 -55.377787 1.5087354
65 2 196.68811 0.94174532E-03 77.649029 -2.8936813
66 1 -171.00089 0.10077048E-03 -55.189078 2.7427195
67 0 57.057407 0.57514079E-06 15.569530  
68 9 0.31336604E-16 0.39008580E-16 -0.14256869E-09 0.20136749E-17
69 8 0.20868940E-07 0.14443760E-12 0.36714717E-03 -0.23728702E-09
70 7 -0.11923636E-01 0.75824706E-08 -0.22627983E-01 0.13557608E-03
71 6 0.39671154 0.26538398E-05 0.46472729 -0.46459316E-02
72 5 -5.1062546 0.99607489E-04 -4.3846760 0.62138459E-01
73 4 32.629908 0.81865718E-03 21.219102 -0.41717122
74 3 -110.43267 0.17916944E-02 -55.186609 1.5037299
75 2 196.34465 0.10116009E-02 77.473776 -2.8882273
76 1 -170.87399 0.10836560E-03 -55.138279 2.7404955
77 0 57.057407 0.61925266E-06 15.578052  
78 7 -0.15963512E-14 -0.15187529E-16 -0.22427203E-13 0.56155309E-15
79 6 0.17983713E-10 0.23594901E-11 0.52322926E-09 -0.18637893E-10
80 5 -0.60139213E-07 0.11510628E-07 -0.21924491E-05 0.17161312E-06
81 4 0.62746279E-04 0.43399923E-05 0.17681060E-02 -0.28244642E-03
82 3 -0.90508353E-02 0.15320797E-03 -0.21560640 0.43341486E-01
83 2 0.12836503 0.66328859E-03 2.9007871 -0.61911613
84 1 -0.32478029 0.41934727E-03 -7.1379041 1.5697129
85 0 0.20664896 0.54311639E-05 4.4522013  
86 7 -0.22427203E-13 -0.15187529E-16 -0.15963512E-14 0.56155309E-15
87 6 0.52322926E-09 0.23594901E-11 0.17983713E-10 -0.18637893E-10
88 5 -0.21924491E-05 0.11510628E-07 -0.60139213E-07 0.17161312E-06
89 4 0.17681060E-02 0.43399923E-05 0.62746279E-04 -0.28244642E-03
90 3 -0.21560640 0.15320797E-03 -0.90508353E-02 0.43341486E-01
91 2 2.9007871 0.66328859E-03 0.12836503 -0.61911613
92 1 -7.1379041 0.41934727E-03 -0.32478029 1.5697129
93 0 4.4522013 0.54311639E-05 0.20664896  
94 7 -0.52459208E-15 -0.63961428E-15 -0.12292524E-09 -0.35846135E-17
95 6 0.39860198E-02 0.96339020E-07 0.40499006E-03 -0.70890431E-04
96 5 -0.20832379 0.49172556E-04 -0.20585669E-01 0.38489246E-02
97 4 3.5198270 0.18993977E-02 0.34924834 -0.69168259E-01
98 3 -23.366787 0.13311857E-01 -2.4329538 0.50524779
99 2 64.890127 0.19943872E-01 7.3672511 -1.5911358
100 1 -76.040094 0.56792084E-02 -9.5568013 2.1361271
101 0 31.242244 0.96490710E-04 4.3344156  
102 7 -0.98583555E-09 -0.79843648E-16 0.12056005E-14 0.46388562E-17
103 6 0.11736010E-04 0.80964505E-08 0.31724491E-02 -0.26613162E-04
104 5 -0.85155955E-03 0.48044989E-05 -0.22273424 0.19474091E-02
105 4 0.19629464E-01 0.21887653E-03 4.8130477 -0.45106395E-01
106 3 -0.17247723 0.17421542E-02 -37.928201 0.39762344
107 2 0.61254091 0.29000861E-02 116.30250 -1.4155123
108 1 -0.88416489 0.88473762E-03 -143.80049 2.0472841
109 0 0.43108349 0.21254961E-04 60.838472  
110 7 -0.98583555E-09 -0.79843648E-16 0.12056005E-14 0.46388562E-17
111 6 0.11736010E-04 0.80964505E-08 0.31724491E-02 -0.26613162E-04
112 5 -0.85155955E-03 0.48044989E-05 -0.22273424 0.19474091E-02
113 4 0.19629464E-01 0.21887653E-03 4.8130477 -0.45106395E-01
114 3 -0.17247723 0.17421542E-02 -37.928201 0.39762344
115 2 0.61254091 0.29000861E-02 116.30250 -1.4155123
116 1 -0.88416489 0.88473762E-03 -143.80049 2.0472841
117 0 0.43108349 0.21254961E-04 60.838472  
118 7 -0.98583555E-09 -0.79843648E-16 0.12056005E-14 0.46388562E-17
119 6 0.11736010E-04 0.80964505E-08 0.31724491E-02 -0.26613162E-04
120 5 -0.85155955E-03 0.48044989E-05 -0.22273424 0.19474091E-02
121 4 0.19629464E-01 0.21887653E-03 4.8130477 -0.45106395E-01
122 3 -0.17247723 0.17421542E-02 -37.928201 0.39762344
123 2 0.61254091 0.29000861E-02 116.30250 -1.4155123
124 1 -0.88416489 0.88473762E-03 -143.80049 2.0472841
125 0 0.43108349 0.21254961E-04 60.838472  
126 7 -0.98583555E-09 -0.79843648E-16 0.12056005E-14 0.46388562E-17
127 6 0.11736010E-04 0.80964505E-08 0.31724491E-02 -0.26613162E-04
128 5 -0.85155955E-03 0.48044989E-05 -0.22273424 0.19474091E-02
129 4 0.19629464E-01 0.21887653E-03 4.8130477 -0.45106395E-01
130 3 -0.17247723 0.17421542E-02 -37.928201 0.39762344
131 2 0.61254091 0.29000861E-02 116.30250 -1.4155123
132 1 -0.88416489 0.88473762E-03 -143.80049 2.0472841
133 0 0.43108349 0.21254961E-04 60.838472  


WindowConstruction

Construction Name Index #Layers Roughness Conductance {W/m2-K} Conductance (Before Adjusted) {W/m2-K} Convection Coefficient Adjustment Ratio SHGC Solar Transmittance at Normal Incidence Visible Transmittance at Normal Incidence
1 NONRESWINDOW_U_0.3856_SHGC_0.4 37 1 VerySmooth 2.191 2.191 1.000 0.401    
2 RESWINDOW_U_0.3856_SHGC_0.4 38 1 VerySmooth 2.191 2.191 1.000 0.401    


WindowMaterial:Glazing

Material Name Optical Data Type Spectral Data Set Name Thickness {m} Solar Transmittance Front Solar Reflectance Back Solar Reflectance Visible Transmittance Front Visible Reflectance Back Visible Reflectance Infrared Transmittance Front Thermal Emissivity Back Thermal Emissivity Conductivity {W/m-K} Dirt Factor Solar Diffusing
1 GLAZING LAYER SpectralAverage   3.40174E-002 0.31435 0.47878 0.47878 0.40000 0.13759 0.17962 0.00000 0.84000 0.84000 0.11969 1.00000 No
2 RESIDENTIAL WINDOW GLAZING LAYER SpectralAverage   3.40174E-002 0.31435 0.47878 0.47878 0.40000 0.13759 0.17962 0.00000 0.84000 0.84000 0.11969 1.00000 No


Shadowing/Sun Position Calculations Annual Simulations

Shading Calculation Method Shading Calculation Update Frequency Method Shading Calculation Update Frequency {days} Maximum Figures in Shadow Overlap Calculations {} Polygon Clipping Algorithm Pixel Counting Resolution Sky Diffuse Modeling Algorithm Output External Shading Calculation Results Disable Self-Shading Within Shading Zone Groups Disable Self-Shading From Shading Zone Groups to Other Zones
1 PolygonClipping Periodic 7 15000 SutherlandHodgman 512 SimpleSkyDiffuseModeling No No No


#Refrigeration Compressor Racks

Number of Refrigeration Compressor Racks
1 2


Refrigeration Compressor Rack

Compressor Rack Name # Refrigerated Cases Connected # WalkIn Coolers Connected Heat Rejection Location Condenser Type COP
1 RACK1 1 0 Zone Air-Cooled 1.500
2 RACK2 1 0 Zone Air-Cooled 3.000


Water Heater Information

Type Name Volume {m3} Maximum Capacity {W} Standard Rated Recovery Efficiency Standard Rated Energy Factor
1 WaterHeater:Mixed SWH BOOSTER E WATER HEATER 2.2712E-002 8000.0 1.240 1.1473
2 WaterHeater:Mixed SWH LAUNDRY G WATER HEATER 1.1356 163316.0 0.576 0.5074
3 WaterHeater:Mixed SWHSYS1 WATER HEATER 2.2712 175842.6 0.260 2.5713E-002


Surface Convection Parameters

Surface Name Outside Model Assignment Outside Area [m2] Outside Perimeter [m] Outside Height [m] Inside Model Assignment Inside Height [m] Inside Perimeter Envelope [m] Inside Hydraulic Diameter [m] Window Wall Ratio Window Location Near Radiant {Yes/No} Has Active HVAC {Yes/No}
1 BASEMENT_WALL_NORTH 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
2 BASEMENT_WALL_EAST 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
3 BASEMENT_WALL_SOUTH 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
4 BASEMENT_WALL_WEST 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
5 BASEMENT_FLOOR 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
6 BASEMENT_CEILING_1 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
7 BASEMENT_CEILING_2 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
8 BASEMENT_CEILING_3 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
9 BASEMENT_CEILING_4 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
10 BASEMENT_CEILING_5 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
11 BASEMENT_CEILING_6 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
12 BASEMENT_CEILING_7 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
13 BASEMENT_CEILING_8 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
14 BASEMENT_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
15 RETAIL_1_FLR_1_WALL_SOUTH 0 506.51 211.91 19.20 0 3.96 17.37 7.72 0.34 4 No No
16 RETAIL_1_FLR_1_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.96 17.37 7.72 0.34 1 No No
17 RETAIL_1_FLR_1_WALL_WEST 0 194.63 84.12 19.20 0 3.96 17.37 7.72 0.34 3 No No
18 RETAIL_1_FLR_1_WALL_NORTH 0 0.00 0.00 0.00 0 3.96 17.37 7.72 0.34 0 No No
19 RETAIL_1_FLR_1_WALL_EAST 0 0.00 0.00 0.00 0 3.96 17.37 7.72 0.34 0 No No
20 RETAIL_1_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 17.37 7.72 0.34 0 No No
21 RETAIL_1_FLR_1_CEILING 0 1782.60 293.11 15.24 0 3.96 17.37 7.72 0.34 0 No No
22 RETAIL_1_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 17.37 7.72 0.34 0 No No
23 RETAIL_2_FLR_1_WALL_WEST 0 194.63 84.12 19.20 0 3.96 6.71 8.49 0.00 0 No No
24 RETAIL_2_FLR_1_WALL_WEST_DOOR 0 194.63 84.12 19.20 0 3.96 6.71 8.49 0.00 0 No No
25 RETAIL_2_FLR_1_WALL_SOUTH 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
26 RETAIL_2_FLR_1_WALL_NORTH 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
27 RETAIL_2_FLR_1_WALL_EAST 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
28 RETAIL_2_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
29 RETAIL_2_FLR_1_CEILING 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
30 RETAIL_2_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
31 MECH_FLR_1_WALL_NORTH 0 670.01 217.46 19.20 0 3.96 15.85 12.53 0.00 0 No No
32 MECH_FLR_1_WALL_EAST 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
33 MECH_FLR_1_WALL_SOUTH 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
34 MECH_FLR_1_WALL_WEST 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
35 MECH_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
36 MECH_FLR_1_CEILING 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
37 MECH_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
38 STORAGE_FLR_1_WALL_NORTH 0 670.01 217.46 19.20 0 3.96 9.14 9.72 0.00 0 No No
39 STORAGE_FLR_1_WALL_NORTH_ROLLDOOR 0 670.01 217.46 19.20 0 3.96 9.14 9.72 0.00 0 No No
40 STORAGE_FLR_1_WALL_EAST 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
41 STORAGE_FLR_1_WALL_SOUTH 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
42 STORAGE_FLR_1_WALL_WEST 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
43 STORAGE_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
44 STORAGE_FLR_1_CEILING 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
45 STORAGE_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
46 LAUNDRY_FLR_1_WALL_NORTH 0 670.01 217.46 19.20 0 3.96 21.64 7.21 0.00 0 No No
47 LAUNDRY_FLR_1_WALL_EAST 0 194.63 217.46 19.20 0 3.96 21.64 7.21 0.00 0 No No
48 LAUNDRY_FLR_1_WALL_EAST_DOOR 0 194.63 217.46 19.20 0 3.96 21.64 7.21 0.00 0 No No
49 LAUNDRY_FLR_1_WALL_SOUTH 0 0.00 0.00 0.00 0 3.96 21.64 7.21 0.00 0 No No
50 LAUNDRY_FLR_1_WALL_WEST 0 0.00 0.00 0.00 0 3.96 21.64 7.21 0.00 0 No No
51 LAUNDRY_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 21.64 7.21 0.00 0 No No
52 LAUNDRY_FLR_1_CEILING 0 0.00 0.00 0.00 0 3.96 21.64 7.21 0.00 0 No No
53 LAUNDRY_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 21.64 7.21 0.00 0 No No
54 CAFE_FLR_1_WALL_EAST 0 194.63 217.46 19.20 0 3.96 38.40 9.84 0.43 3 No No
55 CAFE_FLR_1_WALL_EAST_DOOR 0 194.63 217.46 19.20 0 3.96 38.40 9.84 0.43 0 No No
56 CAFE_FLR_1_WALL_SOUTH 0 506.51 211.91 19.20 0 3.96 38.40 9.84 0.43 4 No No
57 CAFE_FLR_1_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.96 38.40 9.84 0.43 1 No No
58 CAFE_FLR_1_WALL_1_NORTH 0 0.00 0.00 0.00 0 3.96 38.40 9.84 0.43 0 No No
59 CAFE_FLR_1_WALL_2_NORTH 0 0.00 0.00 0.00 0 3.96 38.40 9.84 0.43 0 No No
60 CAFE_FLR_1_WALL_WEST 0 0.00 0.00 0.00 0 3.96 38.40 9.84 0.43 0 No No
61 CAFE_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 38.40 9.84 0.43 0 No No
62 CAFE_FLR_1_CEILING 0 1782.60 293.11 15.24 0 3.96 38.40 9.84 0.43 0 No No
63 CAFE_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 38.40 9.84 0.43 0 No No
64 LOBBY_FLR_1_WALL_1_NORTH 0 670.01 217.46 19.20 0 3.96 109.73 24.95 0.20 3 No No
65 LOBBY_FLR_1_WALL_1_NORTH_DOOR1 0 670.01 217.46 19.20 0 3.96 109.73 24.95 0.20 0 No No
66 LOBBY_FLR_1_WALL_1_NORTH_DOOR2 0 670.01 217.46 19.20 0 3.96 109.73 24.95 0.20 0 No No
67 LOBBY_FLR_1_WALL_2_NORTH 0 670.01 217.46 19.20 0 3.96 109.73 24.95 0.20 4 No No
68 LOBBY_FLR_1_WALL_1_SOUTH 0 506.51 211.91 19.20 0 3.96 109.73 24.95 0.20 4 No No
69 LOBBY_FLR_1_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.96 109.73 24.95 0.20 1 No No
70 LOBBY_FLR_1_WALL_1_WEST 0 194.63 84.12 19.20 0 3.96 109.73 24.95 0.20 3 No No
71 LOBBY_FLR_1_WALL_2_SOUTH 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
72 LOBBY_FLR_1_WALL_3_SOUTH 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
73 LOBBY_FLR_1_WALL_2_WEST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
74 LOBBY_FLR_1_WALL_3_WEST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
75 LOBBY_FLR_1_WALL_4_WEST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
76 LOBBY_FLR_1_WALL_3_NORTH 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
77 LOBBY_FLR_1_WALL_4_NORTH 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
78 LOBBY_FLR_1_WALL_1_EAST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
79 LOBBY_FLR_1_WALL_2_EAST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
80 LOBBY_FLR_1_WALL_3_EAST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
81 LOBBY_FLR_1_FLOOR_1 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
82 LOBBY_FLR_1_FLOOR_2 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
83 LOBBY_FLR_1_CEILING_1 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
84 LOBBY_FLR_1_CEILING_2 0 1782.60 293.11 15.24 0 3.96 109.73 24.95 0.20 0 No No
85 LOBBY_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
86 ROOM_1_FLR_3_WALL_SOUTH 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 3 No No
87 ROOM_1_FLR_3_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 2 No No
88 ROOM_1_FLR_3_WALL_WEST 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 3 No No
89 ROOM_1_FLR_3_WALL_WEST_WINDOW 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 2 No No
90 ROOM_1_FLR_3_WALL_NORTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
91 ROOM_1_FLR_3_WALL_EAST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
92 ROOM_1_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
93 ROOM_1_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
94 ROOM_1_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
95 ROOM_2_FLR_3_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 3 No No
96 ROOM_2_FLR_3_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 2 No No
97 ROOM_2_FLR_3_WALL_WEST 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 3 No No
98 ROOM_2_FLR_3_WALL_WEST_WINDOW 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 2 No No
99 ROOM_2_FLR_3_WALL_EAST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
100 ROOM_2_FLR_3_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
101 ROOM_2_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
102 ROOM_2_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
103 ROOM_2_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
104 ROOM_3_MULT19_FLR_3_WALL_SOUTH 0 506.51 211.91 19.20 0 3.05 3.66 4.73 0.33 3 No No
105 ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 3.66 4.73 0.33 2 No No
106 ROOM_3_MULT19_FLR_3_WALL_NORTH 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
107 ROOM_3_MULT19_FLR_3_WALL_EAST 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
108 ROOM_3_MULT19_FLR_3_WALL_WEST 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
109 ROOM_3_MULT19_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
110 ROOM_3_MULT19_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
111 ROOM_3_MULT19_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
112 ROOM_4_MULT19_FLR_3_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 3.66 4.73 0.33 3 No No
113 ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 3.66 4.73 0.33 2 No No
114 ROOM_4_MULT19_FLR_3_WALL_EAST 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
115 ROOM_4_MULT19_FLR_3_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
116 ROOM_4_MULT19_FLR_3_WALL_WEST 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
117 ROOM_4_MULT19_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
118 ROOM_4_MULT19_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
119 ROOM_4_MULT19_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
120 ROOM_5_FLR_3_WALL_EAST 0 194.63 217.46 19.20 0 3.05 13.11 5.95 0.33 3 No No
121 ROOM_5_FLR_3_WALL_EAST_WINDOW 0 194.63 217.46 19.20 0 3.05 13.11 5.95 0.33 2 No No
122 ROOM_5_FLR_3_WALL_SOUTH 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 3 No No
123 ROOM_5_FLR_3_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 2 No No
124 ROOM_5_FLR_3_WALL_NORTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
125 ROOM_5_FLR_3_WALL_WEST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
126 ROOM_5_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
127 ROOM_5_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
128 ROOM_5_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
129 ROOM_6_FLR_3_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 3 No No
130 ROOM_6_FLR_3_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 2 No No
131 ROOM_6_FLR_3_WALL_EAST 0 194.63 217.46 19.20 0 3.05 13.11 5.95 0.33 3 No No
132 ROOM_6_FLR_3_WALL_EAST_WINDOW 0 194.63 217.46 19.20 0 3.05 13.11 5.95 0.33 2 No No
133 ROOM_6_FLR_3_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
134 ROOM_6_FLR_3_WALL_WEST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
135 ROOM_6_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
136 ROOM_6_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
137 ROOM_6_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
138 CORRIDOR_FLR_3_WALL_1_NORTH 0 670.01 217.46 19.20 0 3.05 15.85 8.24 0.33 3 No No
139 CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 15.85 8.24 0.33 2 No No
140 CORRIDOR_FLR_3_WALL_2_NORTH 0 670.01 217.46 19.20 0 3.05 15.85 8.24 0.33 3 No No
141 CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 15.85 8.24 0.33 2 No No
142 CORRIDOR_FLR_3_WALL_1_SOUTH 0 506.51 211.91 19.20 0 3.05 15.85 8.24 0.33 3 No No
143 CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 15.85 8.24 0.33 2 No No
144 CORRIDOR_FLR_3_WALL_2_SOUTH 0 506.51 211.91 19.20 0 3.05 15.85 8.24 0.33 3 No No
145 CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 15.85 8.24 0.33 2 No No
146 CORRIDOR_FLR_3_WALL_3_NORTH 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
147 CORRIDOR_FLR_3_WALL_1_EAST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
148 CORRIDOR_FLR_3_WALL_2_EAST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
149 CORRIDOR_FLR_3_WALL_3_EAST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
150 CORRIDOR_FLR_3_WALL_4_EAST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
151 CORRIDOR_FLR_3_WALL_3_SOUTH 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
152 CORRIDOR_FLR_3_WALL_1_WEST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
153 CORRIDOR_FLR_3_WALL_2_WEST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
154 CORRIDOR_FLR_3_WALL_3_WEST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
155 CORRIDOR_FLR_3_WALL_4_WEST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
156 CORRIDOR_FLR_3_FLOOR_1 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
157 CORRIDOR_FLR_3_FLOOR_2 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
158 CORRIDOR_FLR_3_FLOOR_3 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
159 CORRIDOR_FLR_3_CEILING_1 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
160 CORRIDOR_FLR_3_CEILING_2 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
161 CORRIDOR_FLR_3_CEILING_3 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
162 CORRIDOR_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
163 ROOM_1_FLR_6_WALL_SOUTH 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 3 No No
164 ROOM_1_FLR_6_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 2 No No
165 ROOM_1_FLR_6_WALL_WEST 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 3 No No
166 ROOM_1_FLR_6_WALL_WEST_WINDOW 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 2 No No
167 ROOM_1_FLR_6_WALL_NORTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
168 ROOM_1_FLR_6_WALL_EAST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
169 ROOM_1_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
170 ROOM_1_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 13.11 5.95 0.33 0 No No
171 ROOM_1_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
172 ROOM_2_FLR_6_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 3 No No
173 ROOM_2_FLR_6_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 2 No No
174 ROOM_2_FLR_6_WALL_WEST 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 3 No No
175 ROOM_2_FLR_6_WALL_WEST_WINDOW 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 2 No No
176 ROOM_2_FLR_6_WALL_EAST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
177 ROOM_2_FLR_6_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
178 ROOM_2_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
179 ROOM_2_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 13.11 5.95 0.33 0 No No
180 ROOM_2_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
181 ROOM_3_MULT9_FLR_6_WALL_SOUTH 0 506.51 211.91 19.20 0 3.05 6.71 4.73 0.33 3 No No
182 ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 6.71 4.73 0.33 2 No No
183 ROOM_3_MULT9_FLR_6_WALL_NORTH 0 0.00 0.00 0.00 0 3.05 6.71 4.73 0.33 0 No No
184 ROOM_3_MULT9_FLR_6_WALL_EAST 0 0.00 0.00 0.00 0 3.05 6.71 4.73 0.33 0 No No
185 ROOM_3_MULT9_FLR_6_WALL_WEST 0 0.00 0.00 0.00 0 3.05 6.71 4.73 0.33 0 No No
186 ROOM_3_MULT9_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 6.71 4.73 0.33 0 No No
187 ROOM_3_MULT9_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 6.71 4.73 0.33 0 No No
188 ROOM_3_MULT9_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 6.71 4.73 0.33 0 No No
189 BANQUET_FLR_6_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 32.00 15.66 0.33 3 No No
190 BANQUET_FLR_6_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 32.00 15.66 0.33 2 No No
191 BANQUET_FLR_6_WALL_EAST 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
192 BANQUET_FLR_6_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
193 BANQUET_FLR_6_WALL_WEST 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
194 BANQUET_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
195 BANQUET_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 32.00 15.66 0.33 0 No No
196 BANQUET_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
197 DINING_FLR_6_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 32.00 15.66 0.33 3 No No
198 DINING_FLR_6_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 32.00 15.66 0.33 2 No No
199 DINING_FLR_6_WALL_EAST 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
200 DINING_FLR_6_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
201 DINING_FLR_6_WALL_WEST 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
202 DINING_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
203 DINING_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 32.00 15.66 0.33 0 No No
204 DINING_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
205 KITCHEN_FLR_6_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 28.65 8.58 0.30 3 No No
206 KITCHEN_FLR_6_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 28.65 8.58 0.30 2 No No
207 KITCHEN_FLR_6_WALL_EAST 0 194.63 217.46 19.20 0 3.05 28.65 8.58 0.30 3 No No
208 KITCHEN_FLR_6_WALL_EAST_WINDOW 0 194.63 217.46 19.20 0 3.05 28.65 8.58 0.30 2 No No
209 KITCHEN_FLR_6_WALL_1_SOUTH 0 506.51 211.91 19.20 0 3.05 28.65 8.58 0.30 3 No No
210 KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 28.65 8.58 0.30 2 No No
211 KITCHEN_FLR_6_WALL_2_SOUTH 0 0.00 0.00 0.00 0 3.05 28.65 8.58 0.30 0 No No
212 KITCHEN_FLR_6_WALL_1_WEST 0 0.00 0.00 0.00 0 3.05 28.65 8.58 0.30 0 No No
213 KITCHEN_FLR_6_WALL_2_WEST 0 0.00 0.00 0.00 0 3.05 28.65 8.58 0.30 0 No No
214 KITCHEN_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 28.65 8.58 0.30 0 No No
215 KITCHEN_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 28.65 8.58 0.30 0 No No
216 KITCHEN_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 28.65 8.58 0.30 0 No No
217 CORRIDOR_FLR_6_WALL_1_NORTH 0 670.01 217.46 19.20 0 3.05 28.04 8.72 0.33 3 No No
218 CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 28.04 8.72 0.33 2 No No
219 CORRIDOR_FLR_6_WALL_2_NORTH 0 670.01 217.46 19.20 0 3.05 28.04 8.72 0.33 3 No No
220 CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 28.04 8.72 0.33 2 No No
221 CORRIDOR_FLR_6_WALL_2_SOUTH 0 506.51 211.91 19.20 0 3.05 28.04 8.72 0.33 3 No No
222 CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 28.04 8.72 0.33 2 No No
223 CORRIDOR_FLR_6_WALL_3_NORTH 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
224 CORRIDOR_FLR_6_WALL_4_NORTH 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
225 CORRIDOR_FLR_6_WALL_1_SOUTH 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
226 CORRIDOR_FLR_6_WALL_1_WEST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
227 CORRIDOR_FLR_6_WALL_2_WEST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
228 CORRIDOR_FLR_6_WALL_3_WEST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
229 CORRIDOR_FLR_6_WALL_1_EAST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
230 CORRIDOR_FLR_6_WALL_2_EAST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
231 CORRIDOR_FLR_6_WALL_3_EAST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
232 CORRIDOR_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
233 CORRIDOR_FLR_6_CEILING_1 0 1782.60 293.11 15.24 0 3.05 28.04 8.72 0.33 0 No No
234 CORRIDOR_FLR_6_CEILING_2 0 1782.60 293.11 15.24 0 3.05 28.04 8.72 0.33 0 No No
235 CORRIDOR_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No


ZoneInfiltration Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Design Volume Flow Rate {m3/s} Volume Flow Rate/Floor Area {m3/s-m2} Volume Flow Rate/Exterior Surface Area {m3/s-m2} ACH - Air Changes per Hour Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2}
1 RETAIL_1_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH RETAIL_1_FLR_1 67.07 10.8 3.921E-002 5.846E-004 2.885E-004 0.531 1.000 0.000 0.000 0.000
2 RETAIL_2_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH RETAIL_2_FLR_1 77.67 12.5 1.513E-002 1.949E-004 5.306E-004 0.177 1.000 0.000 0.000 0.000
3 MECH_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH MECH_FLR_1 164.24 2.7 3.577E-002 2.178E-004 5.696E-004 0.198 1.000 0.000 0.000 0.000
4 STORAGE_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH STORAGE_FLR_1 94.76 2.0 2.064E-002 2.178E-004 4.726E-004 0.198 1.000 0.000 0.000 0.000
5 LAUNDRY_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH LAUNDRY_FLR_1 78.04 8.4 4.884E-002 6.258E-004 5.569E-004 0.569 1.000 0.000 0.000 0.000
6 CAFE_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH CAFE_FLR_1 188.86 142.3 8.667E-002 4.589E-004 2.527E-004 0.417 1.000 0.000 0.000 0.000
7 LOBBY_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH LOBBY_FLR_1 1308.19 422.4 0.248 1.893E-004 3.620E-004 0.172 1.000 0.000 0.000 0.000
8 ROOM_1_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_1_FLR_3 39.02 1.5 2.275E-002 5.831E-004 5.696E-004 0.689 1.000 0.000 0.000 0.000
9 ROOM_2_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_2_FLR_3 39.02 1.5 2.275E-002 5.831E-004 5.696E-004 0.689 1.000 0.000 0.000 0.000
10 ROOM_3_MULT19_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_3_MULT19_FLR_3 24.52 1.5 6.349E-003 2.589E-004 5.696E-004 0.306 1.000 0.000 0.000 0.000
11 ROOM_4_MULT19_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_4_MULT19_FLR_3 24.53 1.5 6.350E-003 2.589E-004 5.696E-004 0.306 1.000 0.000 0.000 0.000
12 ROOM_5_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_5_FLR_3 39.02 1.5 2.275E-002 5.831E-004 5.696E-004 0.689 1.000 0.000 0.000 0.000
13 ROOM_6_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_6_FLR_3 39.02 1.5 2.275E-002 5.831E-004 5.696E-004 0.689 1.000 0.000 0.000 0.000
14 CORRIDOR_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH CORRIDOR_FLR_3 389.40 21.0 2.751E-002 7.066E-005 5.696E-004 8.345E-002 1.000 0.000 0.000 0.000
15 ROOM_1_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_1_FLR_6 39.02 1.5 2.275E-002 5.831E-004 2.881E-004 0.689 1.000 0.000 0.000 0.000
16 ROOM_2_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_2_FLR_6 39.02 1.5 2.275E-002 5.831E-004 2.881E-004 0.689 1.000 0.000 0.000 0.000
17 ROOM_3_MULT9_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_3_MULT9_FLR_6 24.53 1.5 1.164E-002 4.746E-004 2.589E-004 0.561 1.000 0.000 0.000 0.000
18 BANQUET_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH BANQUET_FLR_6 331.66 249.9 5.556E-002 1.675E-004 1.295E-004 0.198 1.000 0.000 0.000 0.000
19 DINING_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH DINING_FLR_6 331.66 249.9 5.556E-002 1.675E-004 1.295E-004 0.198 1.000 0.000 0.000 0.000
20 KITCHEN_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH KITCHEN_FLR_6 103.30 22.2 4.974E-002 4.815E-004 2.609E-004 0.569 1.000 0.000 0.000 0.000
21 CORRIDOR_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH CORRIDOR_FLR_6 412.12 22.2 4.868E-002 1.181E-004 9.784E-005 0.140 1.000 0.000 0.000 0.000


ZoneVentilation Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Design Volume Flow Rate {m3/s} Volume Flow Rate/Floor Area {m3/s-m2} Volume Flow Rate/person Area {m3/s-person} ACH - Air Changes per Hour Fan Type {Exhaust;Intake;Natural} Fan Pressure Rise {Pa} Fan Efficiency {} Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2} Minimum Indoor Temperature{C}/Schedule Maximum Indoor Temperature{C}/Schedule Delta Temperature{C}/Schedule Minimum Outdoor Temperature{C}/Schedule Maximum Outdoor Temperature{C}/Schedule Maximum WindSpeed{m/s}
1 ROOM_1_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_1_FLR_3 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
2 ROOM_2_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_2_FLR_3 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
3 ROOM_3_MULT19_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_3_MULT19_FLR_3 24.52 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
4 ROOM_4_MULT19_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_4_MULT19_FLR_3 24.53 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
5 ROOM_5_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_5_FLR_3 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
6 ROOM_6_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_6_FLR_3 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
7 ROOM_1_FLR_6 SLIDING DOOR VENTILATION Constant-0.0 ROOM_1_FLR_6 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
8 ROOM_2_FLR_6 SLIDING DOOR VENTILATION Constant-0.0 ROOM_2_FLR_6 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
9 ROOM_3_MULT9_FLR_6 SLIDING DOOR VENTILATION Constant-0.0 ROOM_3_MULT9_FLR_6 24.53 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00


AirFlow Model

Simple
1 Simple


RoomAir Model

Zone Name Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined
1 BASEMENT Mixing/Well-Stirred
2 RETAIL_1_FLR_1 Mixing/Well-Stirred
3 RETAIL_2_FLR_1 Mixing/Well-Stirred
4 MECH_FLR_1 Mixing/Well-Stirred
5 STORAGE_FLR_1 Mixing/Well-Stirred
6 LAUNDRY_FLR_1 Mixing/Well-Stirred
7 CAFE_FLR_1 Mixing/Well-Stirred
8 LOBBY_FLR_1 Mixing/Well-Stirred
9 ROOM_1_FLR_3 Mixing/Well-Stirred
10 ROOM_2_FLR_3 Mixing/Well-Stirred
11 ROOM_3_MULT19_FLR_3 Mixing/Well-Stirred
12 ROOM_4_MULT19_FLR_3 Mixing/Well-Stirred
13 ROOM_5_FLR_3 Mixing/Well-Stirred
14 ROOM_6_FLR_3 Mixing/Well-Stirred
15 CORRIDOR_FLR_3 Mixing/Well-Stirred
16 ROOM_1_FLR_6 Mixing/Well-Stirred
17 ROOM_2_FLR_6 Mixing/Well-Stirred
18 ROOM_3_MULT9_FLR_6 Mixing/Well-Stirred
19 BANQUET_FLR_6 Mixing/Well-Stirred
20 DINING_FLR_6 Mixing/Well-Stirred
21 KITCHEN_FLR_6 Mixing/Well-Stirred
22 CORRIDOR_FLR_6 Mixing/Well-Stirred


AirflowNetwork Model:Control

No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation
1 NoMultizoneOrDistribution


Zone Volume Capacitance Multiplier

Sensible Heat Capacity Multiplier Moisture Capacity Multiplier Carbon Dioxide Capacity Multiplier Generic Contaminant Capacity Multiplier
1 1.000 1.000 1.000 1.000


Load Timesteps in Zone Design Calculation Averaging Window

Value
1 6


Heating Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Cooling Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Zone Sizing Information

Zone Name Load Type Calc Des Load {W} User Des Load {W} Calc Des Air Flow Rate {m3/s} User Des Air Flow Rate {m3/s} Design Day Name Date/Time of Peak Temperature at Peak {C} Humidity Ratio at Peak {kgWater/kgDryAir} Floor Area {m2} # Occupants Calc Outdoor Air Flow Rate {m3/s} Calc DOAS Heat Addition Rate {W}
1 BASEMENT Cooling 33765.31537 33765.31537 2.47965 2.47965 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 18:40:00 23.30600 8.40224E-003 1978.83018 106.49900 0.85446 0.00000
2 BASEMENT Heating 1439.64678 1439.64678 6.23703E-002 0.85446 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 24:00:00 -4.30000 2.65759E-003 1978.83018 106.49900 0.85446 0.00000
3 RETAIL_1_FLR_1 Cooling 6466.55962 6466.55962 0.47493 0.47493 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 13:30:00 26.17250 8.40672E-003 67.07136 10.82900 7.92179E-002 0.00000
4 RETAIL_1_FLR_1 Heating 2359.52947 2359.52947 0.10222 0.10222 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:20:00 -4.30000 2.65759E-003 67.07136 10.82900 7.92179E-002 0.00000
5 RETAIL_2_FLR_1 Cooling 3233.45548 3233.45548 0.23748 0.23748 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 15:20:00 26.21800 8.40679E-003 77.66889 12.54000 9.17347E-002 0.00000
6 RETAIL_2_FLR_1 Heating 760.71402 760.71402 3.29561E-002 9.17347E-002 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 24:00:00 -4.30000 2.65759E-003 77.66889 12.54000 9.17347E-002 0.00000
7 MECH_FLR_1 Cooling 3034.79529 3034.79529 0.22284 0.22284 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 15:10:00 26.30900 8.40693E-003 164.24319 2.65200 0.00000 0.00000
8 MECH_FLR_1 Heating 1394.55860 1394.55860 6.04157E-002 6.04157E-002 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 24:00:00 -4.30000 2.65759E-003 164.24319 2.65200 0.00000 0.00000
9 STORAGE_FLR_1 Cooling 1490.09926 1490.09926 0.10942 0.10942 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 14:50:00 26.40000 8.40708E-003 94.75927 2.04000 5.77652E-002 0.00000
10 STORAGE_FLR_1 Heating 866.24448 866.24448 3.75278E-002 5.77652E-002 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 24:00:00 -4.30000 2.65759E-003 94.75927 2.04000 5.77652E-002 0.00000
11 LAUNDRY_FLR_1 Cooling 44695.51748 44695.51748 3.28229 3.28229 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 14:30:00 26.40000 8.40708E-003 78.03947 8.40000 0.00000 0.00000
12 LAUNDRY_FLR_1 Heating 1815.44408 1815.44408 7.86481E-002 7.86481E-002 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:20:00 -4.30000 2.65759E-003 78.03947 8.40000 0.00000 0.00000
13 CAFE_FLR_1 Cooling 25469.38276 25469.38276 1.87203 1.87203 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 13:30:00 26.17250 8.40672E-003 188.86188 142.30000 0.67639 0.00000
14 CAFE_FLR_1 Heating 5997.44110 5997.44110 0.25982 0.67639 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:20:00 -4.30000 2.65759E-003 188.86188 142.30000 0.67639 0.00000
15 LOBBY_FLR_1 Cooling 70309.14605 70309.14605 5.16528 5.16528 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 13:40:00 26.24833 8.40684E-003 1308.18612 422.43500 1.89399 0.00000
16 LOBBY_FLR_1 Heating 13866.23776 13866.23776 0.60072 1.89399 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 24:00:00 -4.30000 2.65759E-003 1308.18612 422.43500 1.89399 0.00000
17 ROOM_1_FLR_3 Cooling 12580.63778 12580.63778 1.24494 1.24494 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 16:40:00 25.36867 8.40546E-003 39.02202 1.50000 6.17350E-002 0.00000
18 ROOM_1_FLR_3 Heating 5188.66322 5188.66322 0.22610 0.22610 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:20:00 -4.30000 2.65759E-003 39.02202 1.50000 6.17350E-002 0.00000
19 ROOM_2_FLR_3 Cooling 11248.27181 11248.27181 1.11309 1.11309 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 17:00:00 25.12600 8.40508E-003 39.01745 1.50000 6.17278E-002 0.00000
20 ROOM_2_FLR_3 Heating 5194.31924 5194.31924 0.22635 0.22635 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:20:00 -4.30000 2.65759E-003 39.01745 1.50000 6.17278E-002 0.00000
21 ROOM_3_MULT19_FLR_3 Cooling 91451.39819 91451.39819 9.04933 9.04933 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 13:30:00 26.17250 8.40672E-003 24.52384 1.50000 0.83707 0.00000
22 ROOM_3_MULT19_FLR_3 Heating 29731.10843 29731.10843 1.29559 1.29559 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:20:00 -4.30000 2.65759E-003 24.52384 1.50000 0.83707 0.00000
23 ROOM_4_MULT19_FLR_3 Cooling 58139.32953 58139.32953 5.75346 5.75346 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 26.40000 8.40708E-003 24.53055 1.50000 0.83730 0.00000
24 ROOM_4_MULT19_FLR_3 Heating 29853.35889 29853.35889 1.30092 1.30092 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:20:00 -4.30000 2.65759E-003 24.53055 1.50000 0.83730 0.00000
25 ROOM_5_FLR_3 Cooling 11423.97709 11423.97709 1.13048 1.13048 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 10:00:00 22.94200 8.40167E-003 39.02202 1.50000 6.17350E-002 0.00000
26 ROOM_5_FLR_3 Heating 5176.66915 5176.66915 0.22558 0.22558 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:20:00 -4.30000 2.65759E-003 39.02202 1.50000 6.17350E-002 0.00000
27 ROOM_6_FLR_3 Cooling 10298.39311 10298.39311 1.01909 1.01909 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 09:10:00 21.65283 8.39969E-003 39.01745 1.50000 6.17278E-002 0.00000
28 ROOM_6_FLR_3 Heating 5182.32854 5182.32854 0.22583 0.22583 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:20:00 -4.30000 2.65759E-003 39.01745 1.50000 6.17278E-002 0.00000
29 CORRIDOR_FLR_3 Cooling 17037.06920 17037.06920 1.25113 1.25113 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 14:10:00 26.40000 8.40708E-003 389.40468 20.95700 0.47476 0.00000
30 CORRIDOR_FLR_3 Heating 8049.46645 8049.46645 0.34873 0.47476 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:20:00 -4.30000 2.65759E-003 389.40468 20.95700 0.47476 0.00000
31 ROOM_1_FLR_6 Cooling 3369.73956 3369.73956 0.33346 0.33346 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 16:30:00 25.49000 8.40565E-003 39.02202 1.50000 1.54338E-002 0.00000
32 ROOM_1_FLR_6 Heating 1653.18198 1653.18198 7.20390E-002 7.20390E-002 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:20:00 -4.30000 2.65759E-003 39.02202 1.50000 1.54338E-002 0.00000
33 ROOM_2_FLR_6 Cooling 2992.27507 2992.27507 0.29611 0.29611 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 17:00:00 25.12600 8.40508E-003 39.01745 1.50000 1.54319E-002 0.00000
34 ROOM_2_FLR_6 Heating 1654.60650 1654.60650 7.21011E-002 7.21011E-002 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:20:00 -4.30000 2.65759E-003 39.01745 1.50000 1.54319E-002 0.00000
35 ROOM_3_MULT9_FLR_6 Cooling 18669.62523 18669.62523 1.84752 1.84752 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 13:40:00 26.24833 8.40684E-003 24.53055 1.50000 9.91540E-002 0.00000
36 ROOM_3_MULT9_FLR_6 Heating 7974.43762 7974.43762 0.34750 0.34750 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:20:00 -4.30000 2.65759E-003 24.53055 1.50000 9.91540E-002 0.00000
37 BANQUET_FLR_6 Cooling 29819.49215 29819.49215 2.19250 2.19250 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 14:30:00 26.40000 8.40708E-003 331.65745 249.89600 1.18780 0.00000
38 BANQUET_FLR_6 Heating 5666.38285 5666.38285 0.24548 1.18780 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:20:00 -4.30000 2.65759E-003 331.65745 249.89600 1.18780 0.00000
39 DINING_FLR_6 Cooling 31280.59482 31280.59482 2.29990 2.29990 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 14:20:00 26.40000 8.40708E-003 331.65745 249.89600 1.18780 0.00000
40 DINING_FLR_6 Heating 5767.94836 5767.94836 0.24988 1.18780 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 19:20:00 -4.30000 2.65759E-003 331.65745 249.89600 1.18780 0.00000
41 KITCHEN_FLR_6 Cooling 31445.53133 31445.53133 2.31521 2.31521 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 12:30:00 25.58100 8.40579E-003 103.30446 22.23800 0.36735 0.00000
42 KITCHEN_FLR_6 Heating 937.60221 937.60221 4.06135E-002 0.36735 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 23:30:00 -4.30000 2.65759E-003 103.30446 22.23800 0.36735 0.00000
43 CORRIDOR_FLR_6 Cooling 10501.10778 10501.10778 0.77115 0.77115 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 14:00:00 26.40000 8.40708E-003 412.12471 22.18000 0.12562 0.00000
44 CORRIDOR_FLR_6 Heating 6059.60211 6059.60211 0.26252 0.26252 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 19:20:00 -4.30000 2.65759E-003 412.12471 22.18000 0.12562 0.00000


System Sizing Information

System Name Load Type Peak Load Kind User Design Capacity Calc Des Air Flow Rate [m3/s] User Des Air Flow Rate [m3/s] Design Day Name Date/Time of Peak
1 VAV WITH REHEAT Cooling Sensible 367120.94 22.55588 22.55588 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 00:00:00
2 VAV WITH REHEAT Heating Sensible 183419.29 7.29581 7.29581 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 19:20:00
3 FLR_3_DOAS Cooling Sensible 33397.10 20.41511 2.05125 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 00:00:00
4 FLR_3_DOAS Heating Sensible 51569.06 3.99200 2.05125 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:20:00


Component Sizing Information

Component Type Component Name Input Field Description Value
1 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.47965
2 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.60810
3 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.99500
4 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 2.46725
5 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
6 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
7 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 6.26543E-004
8 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.25340E-004
9 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 2.46725
10 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
11 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
12 Coil:Heating:Water BASEMENT VAV BOX REHEAT COIL Design Size Rated Capacity [W] 14327.11670
13 Coil:Heating:Water BASEMENT VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.25340E-004
14 Coil:Heating:Water BASEMENT VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 300.50608
15 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.47493
16 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.10761
17 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.99500
18 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.47255
19 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.99500
20 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
21 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.54045E-003
22 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 4.22148E-005
23 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.47255
24 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
25 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
26 Coil:Heating:Water RETAIL_1_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 4825.40856
27 Coil:Heating:Water RETAIL_1_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 4.22148E-005
28 Coil:Heating:Water RETAIL_1_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 105.88582
29 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.23748
30 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.24921
31 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.99500
32 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.23630
33 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.99500
34 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
35 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.52882E-003
36 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.74418E-005
37 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.23630
38 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
39 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
40 Coil:Heating:Water RETAIL_2_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 1993.71054
41 Coil:Heating:Water RETAIL_2_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.74418E-005
42 Coil:Heating:Water RETAIL_2_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 42.94962
43 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.22284
44 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.56162
45 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.99500
46 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.22173
47 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
48 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
49 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 6.78398E-004
50 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.23193E-005
51 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.22173
52 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
53 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
54 Coil:Heating:Water MECH_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 2551.23755
55 Coil:Heating:Water MECH_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.23193E-005
56 Coil:Heating:Water MECH_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 56.75998
57 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.10942
58 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.65991
59 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.99500
60 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.10887
61 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
62 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
63 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 5.77351E-004
64 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.25473E-005
65 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.10887
66 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
67 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
68 Coil:Heating:Water STORAGE_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 1434.23167
69 Coil:Heating:Water STORAGE_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.25473E-005
70 Coil:Heating:Water STORAGE_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 32.49217
71 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 3.28229
72 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 7.18931E-002
73 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.99500
74 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 3.26588
75 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.99500
76 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
77 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.10297E-002
78 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.64900E-004
79 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 3.26588
80 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
81 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
82 Coil:Heating:Water LAUNDRY_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 18849.12599
83 Coil:Heating:Water LAUNDRY_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.64900E-004
84 Coil:Heating:Water LAUNDRY_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 395.21391
85 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.87203
86 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 7.68752E-002
87 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.99500
88 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.86267
89 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.99500
90 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
91 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 4.95608E-003
92 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.37514E-004
93 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.86267
94 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
95 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
96 Coil:Heating:Water CAFE_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 15718.64927
97 Coil:Heating:Water CAFE_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.37514E-004
98 Coil:Heating:Water CAFE_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 338.62483
99 Fan:ZoneExhaust LOBBY_FLR_1 EXHAUST FAN User-Specified Maximum Flow Rate [m3/s] 0.00000
100 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 5.16528
101 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.19299
102 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.99500
103 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 5.13945
104 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.99500
105 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
106 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.97421E-003
107 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 3.55945E-004
108 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 5.13945
109 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
110 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
111 Coil:Heating:Water LOBBY_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 40686.71056
112 Coil:Heating:Water LOBBY_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 3.55945E-004
113 Coil:Heating:Water LOBBY_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 871.80933
114 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_1_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 6.17350E-002
115 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 1.24494
116 Fan:OnOff ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 1.24494
117 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 4.53927E-005
118 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 5.32340E-004
119 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 22.50292
120 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
121 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.55731E-003
122 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
123 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
124 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 5.32340E-004
125 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 1.24494
126 Coil:Heating:Water ROOM_1_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 5188.66763
127 Coil:Heating:Water ROOM_1_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 4.53927E-005
128 Coil:Heating:Water ROOM_1_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 148.27945
129 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_2_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 6.17278E-002
130 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 1.11309
131 Fan:OnOff ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 1.11309
132 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 4.54422E-005
133 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 4.76766E-004
134 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 22.50290
135 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
136 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.56399E-003
137 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
138 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
139 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 4.76766E-004
140 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 1.11309
141 Coil:Heating:Water ROOM_2_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 5194.32365
142 Coil:Heating:Water ROOM_2_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 4.54422E-005
143 Coil:Heating:Water ROOM_2_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 148.44104
144 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_3_MULT19_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.83707
145 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT19_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 9.04933
146 Fan:OnOff ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 9.04933
147 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT19_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 2.60101E-004
148 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT19_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 3.81361E-003
149 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 22.50342
150 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
151 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.49881E-003
152 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
153 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.49881E-003
154 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 3.81361E-003
155 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 9.04933
156 Coil:Heating:Water ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 29731.11927
157 Coil:Heating:Water ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 2.60101E-004
158 Coil:Heating:Water ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 849.62915
159 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_4_MULT19_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.83730
160 ZoneHVAC:FourPipeFanCoil ROOM_4_MULT19_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 5.75346
161 Fan:OnOff ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 5.75346
162 ZoneHVAC:FourPipeFanCoil ROOM_4_MULT19_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 2.61170E-004
163 ZoneHVAC:FourPipeFanCoil ROOM_4_MULT19_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 2.57417E-003
164 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 22.50217
165 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
166 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.74067E-003
167 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
168 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
169 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 2.57417E-003
170 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 5.75346
171 Coil:Heating:Water ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 29853.36980
172 Coil:Heating:Water ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 2.61170E-004
173 Coil:Heating:Water ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 853.12186
174 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_5_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 6.17350E-002
175 ZoneHVAC:FourPipeFanCoil ROOM_5_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 1.13048
176 Fan:OnOff ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 1.13048
177 ZoneHVAC:FourPipeFanCoil ROOM_5_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 4.52878E-005
178 ZoneHVAC:FourPipeFanCoil ROOM_5_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 4.84102E-004
179 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 22.50291
180 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
181 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.56308E-003
182 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
183 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
184 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 4.84102E-004
185 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 1.13048
186 Coil:Heating:Water ROOM_5_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 5176.67355
187 Coil:Heating:Water ROOM_5_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 4.52878E-005
188 Coil:Heating:Water ROOM_5_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 147.93679
189 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_6_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 6.17278E-002
190 ZoneHVAC:FourPipeFanCoil ROOM_6_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 1.01909
191 Fan:OnOff ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 1.01909
192 ZoneHVAC:FourPipeFanCoil ROOM_6_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 4.53373E-005
193 ZoneHVAC:FourPipeFanCoil ROOM_6_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 4.37132E-004
194 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 22.50289
195 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
196 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.56969E-003
197 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
198 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
199 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 4.37132E-004
200 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 1.01909
201 Coil:Heating:Water ROOM_6_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 5182.33294
202 Coil:Heating:Water ROOM_6_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 4.53373E-005
203 Coil:Heating:Water ROOM_6_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 148.09847
204 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.25113
205 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.94866
206 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.99500
207 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.24488
208 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
209 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
210 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 4.01618E-004
211 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.27267E-004
212 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.24488
213 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
214 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
215 Coil:Heating:Water CORRIDOR_FLR_3 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 14547.38460
216 Coil:Heating:Water CORRIDOR_FLR_3 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.27267E-004
217 Coil:Heating:Water CORRIDOR_FLR_3 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 324.27675
218 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_1_FLR_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 1.54338E-002
219 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_6 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 0.33346
220 Fan:OnOff ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 0.33346
221 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_6 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 1.44628E-005
222 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_6 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 1.42453E-004
223 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 22.50294
224 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
225 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.55356E-003
226 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
227 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
228 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 1.42453E-004
229 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 0.33346
230 Coil:Heating:Water ROOM_1_FLR_6 FAN COIL HEATING COIL Design Size Rated Capacity [W] 1653.18350
231 Coil:Heating:Water ROOM_1_FLR_6 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 1.44628E-005
232 Coil:Heating:Water ROOM_1_FLR_6 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 47.24104
233 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_2_FLR_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 1.54319E-002
234 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_6 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 0.29611
235 Fan:OnOff ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 0.29611
236 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_6 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 1.44752E-005
237 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_6 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 1.26711E-004
238 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 22.50292
239 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
240 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.56028E-003
241 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
242 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
243 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 1.26711E-004
244 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 0.29611
245 Coil:Heating:Water ROOM_2_FLR_6 FAN COIL HEATING COIL Design Size Rated Capacity [W] 1654.60802
246 Coil:Heating:Water ROOM_2_FLR_6 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 1.44752E-005
247 Coil:Heating:Water ROOM_2_FLR_6 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 47.28174
248 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_3_MULT9_FLR_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 9.91540E-002
249 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT9_FLR_6 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 1.84752
250 Fan:OnOff ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 1.84752
251 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT9_FLR_6 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 6.97639E-005
252 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT9_FLR_6 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 7.96248E-004
253 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 22.50265
254 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
255 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.58862E-003
256 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
257 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
258 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 7.96248E-004
259 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 1.84752
260 Coil:Heating:Water ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL Design Size Rated Capacity [W] 7974.44413
261 Coil:Heating:Water ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 6.97639E-005
262 Coil:Heating:Water ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 227.87416
263 Fan:ZoneExhaust BANQUET_FLR_6 EXHAUST FAN User-Specified Maximum Flow Rate [m3/s] 0.00000
264 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.19250
265 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.11527
266 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.99500
267 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 2.18154
268 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.99500
269 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
270 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.30537E-003
271 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.49207E-004
272 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 2.18154
273 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
274 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
275 Coil:Heating:Water BANQUET_FLR_6 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 17055.31940
276 Coil:Heating:Water BANQUET_FLR_6 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.49207E-004
277 Coil:Heating:Water BANQUET_FLR_6 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 365.08170
278 Fan:ZoneExhaust DINING_FLR_6 EXHAUST FAN User-Specified Maximum Flow Rate [m3/s] 0.00000
279 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.29990
280 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.10988
281 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.99500
282 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 2.28840
283 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.99500
284 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
285 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.46728E-003
286 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.54976E-004
287 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 2.28840
288 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
289 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
290 Coil:Heating:Water DINING_FLR_6 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 17714.73017
291 Coil:Heating:Water DINING_FLR_6 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.54976E-004
292 Coil:Heating:Water DINING_FLR_6 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 378.89830
293 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.31521
294 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.81539
295 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.99500
296 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 2.30363
297 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.99500
298 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
299 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.12057E-002
300 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.12737E-004
301 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 2.30363
302 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
303 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
304 Coil:Heating:Water KITCHEN_FLR_6 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 12886.51466
305 Coil:Heating:Water KITCHEN_FLR_6 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.12737E-004
306 Coil:Heating:Water KITCHEN_FLR_6 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 269.71648
307 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.77115
308 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.40723
309 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.99500
310 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.76730
311 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
312 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
313 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 9.35579E-004
314 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 8.80598E-005
315 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.76730
316 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
317 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
318 Coil:Heating:Water CORRIDOR_FLR_6 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 10065.77554
319 Coil:Heating:Water CORRIDOR_FLR_6 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 8.80598E-005
320 Coil:Heating:Water CORRIDOR_FLR_6 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 227.89973
321 AirLoopHVAC VAV WITH REHEAT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 22.56044
322 AirLoopHVAC VAV WITH REHEAT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 22.56044
323 AirLoopHVAC VAV WITH REHEAT Sum of Air Terminal Maximum Flow Rates [m3/s] 22.67381
324 AirLoopHVAC VAV WITH REHEAT Adjusted Heating Design Air Flow Rate [m3/s] 22.56044
325 AirLoopHVAC VAV WITH REHEAT Adjusted Cooling Design Air Flow Rate [m3/s] 22.56044
326 AirLoopHVAC VAV WITH REHEAT Adjusted Main Design Air Flow Rate [m3/s] 22.56044
327 AirLoopHVAC VAV WITH REHEAT User Heating Air Flow Ratio [] 0.30000
328 AirLoopHVAC VAV WITH REHEAT Calculated Heating Air Flow Ratio [] 1.00000
329 AirLoopHVAC FLR_3_DOAS Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 2.05132
330 AirLoopHVAC FLR_3_DOAS Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 2.05132
331 AirLoopHVAC FLR_3_DOAS Sum of Air Terminal Maximum Flow Rates [m3/s] 2.05132
332 AirLoopHVAC FLR_3_DOAS Adjusted Heating Design Air Flow Rate [m3/s] 2.05132
333 AirLoopHVAC FLR_3_DOAS Adjusted Cooling Design Air Flow Rate [m3/s] 2.05132
334 AirLoopHVAC FLR_3_DOAS Adjusted Main Design Air Flow Rate [m3/s] 2.05132
335 AirLoopHVAC FLR_3_DOAS User Heating Air Flow Ratio [] 0.30000
336 AirLoopHVAC FLR_3_DOAS Calculated Heating Air Flow Ratio [] 1.00000
337 AirLoopHVAC VAV WITH REHEAT Design Supply Air Flow Rate [m3/s] 22.56044
338 AirLoopHVAC FLR_3_DOAS Design Supply Air Flow Rate [m3/s] 2.05132
339 Controller:OutdoorAir VAV WITH REHEAT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 22.56044
340 Controller:OutdoorAir VAV WITH REHEAT_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 22.55588
341 HeatExchanger:AirToAir:SensibleAndLatent VAV WITH REHEAT OA HEAT RECOVERY Design Size Nominal Supply Air Flow Rate [m3/s] 22.55588
342 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Inlet Air Temperature [C] 26.40000
343 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
344 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Outlet Air Temperature [C] 10.95700
345 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.40708E-003
346 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.40708E-003
347 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Coil Load [W] 423570.84074
348 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Water Flow Rate [m3/s] 1.51290E-002
349 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Air Flow Rate [m3/s] 22.56044
350 Coil:Heating:Water VAV WITH REHEAT HEATING COIL Design Size Rated Capacity [W] 170153.30987
351 Coil:Heating:Water VAV WITH REHEAT HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 1.48858E-003
352 Coil:Heating:Water VAV WITH REHEAT HEATING COIL Design Size U-Factor Times Area Value [W/K] 2903.29538
353 Fan:VariableVolume VAV WITH REHEAT FAN Design Size Maximum Flow Rate [m3/s] 22.56044
354 Controller:WaterCoil VAV WITH REHEAT_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 1.51290E-002
355 Controller:WaterCoil VAV WITH REHEAT_COOLC_CONTROLLER Controller Convergence Tolerance 3.14754E-005
356 Controller:WaterCoil VAV WITH REHEAT_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 1.48858E-003
357 Controller:OutdoorAir FLR_3_DOAS_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 2.05132
358 Controller:OutdoorAir FLR_3_DOAS_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 2.05125
359 HeatExchanger:AirToAir:SensibleAndLatent FLR_3_DOAS OA HEAT RECOVERY Design Size Nominal Supply Air Flow Rate [m3/s] 2.05125
360 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Inlet Air Temperature [C] 26.40000
361 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
362 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Outlet Air Temperature [C] 11.91985
363 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.40708E-003
364 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.40708E-003
365 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Coil Load [W] 36112.10278
366 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Water Flow Rate [m3/s] 1.28984E-003
367 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Air Flow Rate [m3/s] 2.05132
368 Coil:Heating:Water FLR_3_DOAS HEATING COIL Design Size Rated Capacity [W] 15471.26131
369 Coil:Heating:Water FLR_3_DOAS HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 1.35349E-004
370 Coil:Heating:Water FLR_3_DOAS HEATING COIL Design Size U-Factor Times Area Value [W/K] 263.98335
371 Fan:ConstantVolume FLR_3_DOAS FAN User-Specified Maximum Flow Rate [m3/s] 2.05125
372 Controller:WaterCoil FLR_3_DOAS_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 1.28984E-003
373 Controller:WaterCoil FLR_3_DOAS_COOLC_CONTROLLER Controller Convergence Tolerance 3.69186E-004
374 Controller:WaterCoil FLR_3_DOAS_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 1.35349E-004
375 Pump:VariableSpeed COOLSYS1 PUMP SECONDARY Design Flow Rate [m3/s] 2.58023E-002
376 Pump:VariableSpeed COOLSYS1 PUMP SECONDARY Design Power Consumption [W] 5316.90522
377 PlantLoop HEATSYS1 Maximum Loop Flow Rate [m3/s] 3.93583E-003
378 PlantLoop HEATSYS1 Plant Loop Volume [m3] 0.47230
379 Pump:VariableSpeed HEATSYS1 PUMP Design Flow Rate [m3/s] 3.93583E-003
380 Pump:VariableSpeed HEATSYS1 PUMP Design Power Consumption [W] 1185.29827
381 Pump:VariableSpeed HEATSYS1 PUMP Design Minimum Flow Rate [m3/s] 0.00000
382 Boiler:HotWater HEATSYS1 BOILER Design Size Nominal Capacity [W] 449889.20891
383 Boiler:HotWater HEATSYS1 BOILER User-Specified Nominal Capacity [W] 449889.21000
384 Boiler:HotWater HEATSYS1 BOILER Design Size Design Water Flow Rate [m3/s] 3.93583E-003
385 PlantLoop COOLSYS1 Maximum Loop Flow Rate [m3/s] 2.58023E-002
386 PlantLoop COOLSYS1 Plant Loop Volume [m3] 3.09628
387 Pump:ConstantSpeed COOLSYS1 PUMP Design Flow Rate [m3/s] 2.58023E-002
388 Pump:ConstantSpeed COOLSYS1 PUMP Design Power Consumption [W] 3681.07281
389 Chiller:Electric:EIR COOLSYS1 CHILLER1 Design Size Reference Chilled Water Flow Rate [m3/s] 2.58023E-002
390 Chiller:Electric:EIR COOLSYS1 CHILLER1 Design Size Reference Capacity [W] 722396.70310
391 Chiller:Electric:EIR COOLSYS1 CHILLER1 User-Specified Reference Capacity [W] 723021.47000
392 Chiller:Electric:EIR COOLSYS1 CHILLER1 Design Size Reference Condenser Fluid Flow Rate [m3/s] 82.42445
393 PlantLoop SWHSYS1 Maximum Loop Flow Rate [m3/s] 3.75036E-004
394 PlantLoop SWHSYS1 Plant Loop Volume [m3] 4.50044E-002
395 Pump:ConstantSpeed SWHSYS1 PUMP Design Flow Rate [m3/s] 3.75036E-004
396 Pump:ConstantSpeed SWHSYS1 PUMP Design Power Consumption [W] 47.90688
397 WaterHeater:Mixed SWHSYS1 WATER HEATER Use Side Design Flow Rate [m3/s] 3.75036E-004


Water Heating Coil Capacity Information

Component Type Name Nominal Total Capacity {W}
1 Coil:Heating:Water BASEMENT VAV BOX REHEAT COIL 14400.77
2 Coil:Heating:Water RETAIL_1_FLR_1 VAV BOX REHEAT COIL 4848.88
3 Coil:Heating:Water RETAIL_2_FLR_1 VAV BOX REHEAT COIL 2003.71
4 Coil:Heating:Water MECH_FLR_1 VAV BOX REHEAT COIL 2563.47
5 Coil:Heating:Water STORAGE_FLR_1 VAV BOX REHEAT COIL 1440.98
6 Coil:Heating:Water LAUNDRY_FLR_1 VAV BOX REHEAT COIL 18946.06
7 Coil:Heating:Water CAFE_FLR_1 VAV BOX REHEAT COIL 15797.50
8 Coil:Heating:Water LOBBY_FLR_1 VAV BOX REHEAT COIL 40891.79
9 Coil:Heating:Water ROOM_1_FLR_3 FAN COIL HEATING COIL 5588.77
10 Coil:Heating:Water ROOM_2_FLR_3 FAN COIL HEATING COIL 5594.86
11 Coil:Heating:Water ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL 32023.54
12 Coil:Heating:Water ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL 32155.20
13 Coil:Heating:Water ROOM_5_FLR_3 FAN COIL HEATING COIL 5575.85
14 Coil:Heating:Water ROOM_6_FLR_3 FAN COIL HEATING COIL 5581.95
15 Coil:Heating:Water CORRIDOR_FLR_3 VAV BOX REHEAT COIL 14617.01
16 Coil:Heating:Water ROOM_1_FLR_6 FAN COIL HEATING COIL 1780.60
17 Coil:Heating:Water ROOM_2_FLR_6 FAN COIL HEATING COIL 1782.13
18 Coil:Heating:Water ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL 8589.02
19 Coil:Heating:Water BANQUET_FLR_6 VAV BOX REHEAT COIL 17141.36
20 Coil:Heating:Water DINING_FLR_6 VAV BOX REHEAT COIL 17804.16
21 Coil:Heating:Water KITCHEN_FLR_6 VAV BOX REHEAT COIL 12952.89
22 Coil:Heating:Water CORRIDOR_FLR_6 VAV BOX REHEAT COIL 10113.20
23 Coil:Heating:Water VAV WITH REHEAT HEATING COIL 129454.91
24 Coil:Heating:Water FLR_3_DOAS HEATING COIL 11770.74


Water Cooling Coil Capacity Information

Component Type Name Nominal Total Capacity {W} Nominal Sensible Capacity {W} Nominal Latent Capacity {W} Nominal Sensible Heat Ratio Nominal Coil UA Value {W/C} Nominal Coil Surface Area {m2}
1 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL 21584.43 17086.44 4498.00 0.79 2416.78 24.51
2 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL 19319.28 15287.11 4032.16 0.79 2162.93 21.94
3 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL 155426.92 123471.76 31955.16 0.79 17415.74 176.64
4 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL 102646.17 80387.06 22259.10 0.78 11464.82 116.28
5 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL 19618.16 15524.48 4093.68 0.79 2196.43 22.28
6 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL 17704.01 14004.14 3699.87 0.79 1981.92 20.10
7 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL 5777.92 4574.90 1203.02 0.79 646.98 6.56
8 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL 5136.26 4065.18 1071.08 0.79 575.07 5.83
9 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL 32192.73 25435.98 6756.75 0.79 3602.88 36.54
10 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL 530774.70 378834.66 151940.04 0.71 65136.51 660.65
11 Coil:Cooling:Water FLR_3_DOAS COOLING COIL 45302.65 32936.56 12366.09 0.73 5220.86 52.95


Chiller Standard Rating Information

Component Type Component Name IPLV in SI Units {W/W} IPLV in IP Units {Btu/W-h}
1 Chiller:Electric:EIR COOLSYS1 CHILLER1 3.72 12.68


Zone Surfaces

Zone Name # Surfaces
1 BASEMENT 14
2 RETAIL_1_FLR_1 8
3 RETAIL_2_FLR_1 8
4 MECH_FLR_1 7
5 STORAGE_FLR_1 8
6 LAUNDRY_FLR_1 8
7 CAFE_FLR_1 10
8 LOBBY_FLR_1 22
9 ROOM_1_FLR_3 9
10 ROOM_2_FLR_3 9
11 ROOM_3_MULT19_FLR_3 8
12 ROOM_4_MULT19_FLR_3 8
13 ROOM_5_FLR_3 9
14 ROOM_6_FLR_3 9
15 CORRIDOR_FLR_3 25
16 ROOM_1_FLR_6 9
17 ROOM_2_FLR_6 9
18 ROOM_3_MULT9_FLR_6 8
19 BANQUET_FLR_6 8
20 DINING_FLR_6 8
21 KITCHEN_FLR_6 12
22 CORRIDOR_FLR_6 19


HeatTransfer Surface

Surface Name Surface Class Base Surface Heat Transfer Algorithm Construction Nominal U (w/o film coefs) {W/m2-K} Nominal U (with film coefs) {W/m2-K} Solar Diffusing Area (Net) {m2} Area (Gross) {m2} Area (Sunlit Calc) {m2} Azimuth {deg} Tilt {deg} ~Width {m} ~Height {m} Reveal {m} ExtBoundCondition ExtConvCoeffCalc IntConvCoeffCalc SunExposure WindExposure ViewFactorToGround ViewFactorToSky ViewFactorToGround-IR ViewFactorToSky-IR #Sides
1 BASEMENT_WALL_NORTH Wall   CTF - ConductionTransferFunction BASEMENT_WALL_NORTH_CFACTOR 0.419 0.394   211.13 211.13 211.13 0.00 90.00 86.56 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
2 BASEMENT_WALL_EAST Wall   CTF - ConductionTransferFunction BASEMENT_WALL_EAST_CFACTOR 0.419 0.394   55.76 55.76 55.76 90.00 90.00 22.86 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
3 BASEMENT_WALL_SOUTH Wall   CTF - ConductionTransferFunction BASEMENT_WALL_SOUTH_CFACTOR 0.419 0.394   211.13 211.13 211.13 180.00 90.00 86.56 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
4 BASEMENT_WALL_WEST Wall   CTF - ConductionTransferFunction BASEMENT_WALL_WEST_CFACTOR 0.419 0.394   55.76 55.76 55.76 270.00 90.00 22.86 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
5 BASEMENT_FLOOR Floor   CTF - ConductionTransferFunction BASEMENT_FLOOR 2.705 1.632   1978.83 1978.83 1978.83 0.00 180.00 86.56 22.86 0.00 BASEMENT_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
6 BASEMENT_CEILING_1 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   67.07 67.07 67.07 180.00 0.00 11.58 5.79 0.00 RETAIL_1_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
7 BASEMENT_CEILING_2 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   77.67 77.67 77.67 180.00 0.00 11.58 6.71 0.00 RETAIL_2_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
8 BASEMENT_CEILING_3 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   164.24 164.24 164.24 180.00 0.00 15.85 10.36 0.00 MECH_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
9 BASEMENT_CEILING_4 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   94.76 94.76 94.76 180.00 0.00 9.14 10.36 0.00 STORAGE_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
10 BASEMENT_CEILING_5 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   78.04 78.04 78.04 180.00 0.00 4.57 17.07 0.00 LAUNDRY_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
11 BASEMENT_CEILING_6 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   188.86 188.86 188.86 180.00 0.00 32.61 5.79 0.00 CAFE_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
12 BASEMENT_CEILING_7 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   1088.56 1088.56 1088.56 180.00 0.00 32.99 32.99 0.00 LOBBY_FLR_1_FLOOR_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 6
13 BASEMENT_CEILING_8 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   219.63 219.63 219.63 90.00 0.00 14.82 14.82 0.00 LOBBY_FLR_1_FLOOR_2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 6
14 BASEMENT_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   3957.66 3957.66 3957.66 0.00 90.00 3957.66 1.00 0.00 BASEMENT_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
15 RETAIL_1_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.738 0.664   22.63 45.89 22.63 180.00 90.00 11.58 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
16 RETAIL_1_FLR_1_WALL_SOUTH_WINDOW Window RETAIL_1_FLR_1_WALL_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.3856_SHGC_0.4 N/A 2.191 No 23.26 23.26 23.26 180.00 90.00 10.92 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
17 RETAIL_1_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.738 0.664   22.95 22.95 22.95 270.00 90.00 5.79 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
18 RETAIL_1_FLR_1_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   45.89 45.89 45.89 0.00 90.00 11.58 3.96 0.00 RETAIL_2_FLR_1_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
19 RETAIL_1_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.95 22.95 22.95 90.00 90.00 5.79 3.96 0.00 LOBBY_FLR_1_WALL_2_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
20 RETAIL_1_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   67.07 67.07 67.07 0.00 180.00 11.58 5.79 0.00 BASEMENT_CEILING_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
21 RETAIL_1_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.228 0.219   67.07 67.07 67.07 180.00 0.00 11.58 5.79 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 7.62E-002 0.92 4
22 RETAIL_1_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   134.14 134.14 134.14 0.00 90.00 134.14 1.00 0.00 RETAIL_1_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
23 RETAIL_2_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.738 0.664   24.62 26.57 24.62 270.00 90.00 6.71 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
24 RETAIL_2_FLR_1_WALL_WEST_DOOR Door RETAIL_2_FLR_1_WALL_WEST CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 270.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
25 RETAIL_2_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   45.89 45.89 45.89 180.00 90.00 11.58 3.96 0.00 RETAIL_1_FLR_1_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
26 RETAIL_2_FLR_1_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   45.89 45.89 45.89 0.00 90.00 11.58 3.96 0.00 LOBBY_FLR_1_WALL_2_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
27 RETAIL_2_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.57 26.57 26.57 90.00 90.00 6.71 3.96 0.00 LOBBY_FLR_1_WALL_3_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
28 RETAIL_2_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   77.67 77.67 77.67 0.00 180.00 11.58 6.71 0.00 BASEMENT_CEILING_2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
29 RETAIL_2_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   77.67 77.67 77.67 180.00 0.00 11.58 6.71 0.00 RETAIL_2_FLR_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
30 RETAIL_2_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   155.34 155.34 155.34 0.00 90.00 155.34 1.00 0.00 RETAIL_2_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
31 MECH_FLR_1_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.738 0.664   62.80 62.80 62.80 0.00 90.00 15.85 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
32 MECH_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 90.00 90.00 10.36 3.96 0.00 STORAGE_FLR_1_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
33 MECH_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   62.80 62.80 62.80 180.00 90.00 15.85 3.96 0.00 LOBBY_FLR_1_WALL_3_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
34 MECH_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 270.00 90.00 10.36 3.96 0.00 LOBBY_FLR_1_WALL_1_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
35 MECH_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   164.24 164.24 164.24 0.00 180.00 15.85 10.36 0.00 BASEMENT_CEILING_3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
36 MECH_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   164.24 164.24 164.24 180.00 0.00 15.85 10.36 0.00 MECH_FLR_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
37 MECH_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   328.49 328.49 328.49 0.00 90.00 328.49 1.00 0.00 MECH_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
38 STORAGE_FLR_1_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.738 0.664   28.80 36.23 28.80 0.00 90.00 9.14 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
39 STORAGE_FLR_1_WALL_NORTH_ROLLDOOR Door STORAGE_FLR_1_WALL_NORTH CTF - ConductionTransferFunction OVERHEAD DOOR_CON 1.198 1.198   7.43 7.43 7.43 0.00 90.00 3.05 2.44 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
40 STORAGE_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 90.00 90.00 10.36 3.96 0.00 LOBBY_FLR_1_WALL_4_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
41 STORAGE_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   36.23 36.23 36.23 180.00 90.00 9.14 3.96 0.00 LOBBY_FLR_1_WALL_4_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
42 STORAGE_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 270.00 90.00 10.36 3.96 0.00 MECH_FLR_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
43 STORAGE_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   94.76 94.76 94.76 0.00 180.00 9.14 10.36 0.00 BASEMENT_CEILING_4 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
44 STORAGE_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   94.76 94.76 94.76 180.00 0.00 9.14 10.36 0.00 STORAGE_FLR_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
45 STORAGE_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   189.52 189.52 189.52 0.00 90.00 189.52 1.00 0.00 STORAGE_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
46 LAUNDRY_FLR_1_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.738 0.664   18.12 18.12 18.12 0.00 90.00 4.57 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
47 LAUNDRY_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.738 0.664   65.68 67.63 65.68 90.00 90.00 17.07 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
48 LAUNDRY_FLR_1_WALL_EAST_DOOR Door LAUNDRY_FLR_1_WALL_EAST CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 90.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
49 LAUNDRY_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   18.12 18.12 18.12 180.00 90.00 4.57 3.96 0.00 CAFE_FLR_1_WALL_2_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
50 LAUNDRY_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   67.63 67.63 67.63 270.00 90.00 17.07 3.96 0.00 LOBBY_FLR_1_WALL_3_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
51 LAUNDRY_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   78.04 78.04 78.04 0.00 180.00 4.57 17.07 0.00 BASEMENT_CEILING_5 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
52 LAUNDRY_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   78.04 78.04 78.04 180.00 0.00 4.57 17.07 0.00 LAUNDRY_FLR_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
53 LAUNDRY_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   156.08 156.08 156.08 0.00 90.00 156.08 1.00 0.00 LAUNDRY_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
54 CAFE_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.738 0.664   21.00 22.95 21.00 90.00 90.00 5.79 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
55 CAFE_FLR_1_WALL_EAST_DOOR Door CAFE_FLR_1_WALL_EAST CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 90.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
56 CAFE_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.738 0.664   63.73 129.23 63.73 180.00 90.00 32.61 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
57 CAFE_FLR_1_WALL_SOUTH_WINDOW Window CAFE_FLR_1_WALL_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.3856_SHGC_0.4 N/A 2.191 No 65.50 65.50 65.50 180.00 90.00 30.75 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
58 CAFE_FLR_1_WALL_1_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.11 111.11 111.11 0.00 90.00 28.04 3.96 0.00 LOBBY_FLR_1_WALL_3_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
59 CAFE_FLR_1_WALL_2_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   18.12 18.12 18.12 0.00 90.00 4.57 3.96 0.00 LAUNDRY_FLR_1_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
60 CAFE_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.95 22.95 22.95 270.00 90.00 5.79 3.96 0.00 LOBBY_FLR_1_WALL_2_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
61 CAFE_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   188.86 188.86 188.86 0.00 180.00 32.61 5.79 0.00 BASEMENT_CEILING_6 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
62 CAFE_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.228 0.219   188.86 188.86 188.86 180.00 0.00 32.61 5.79 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 3.86E-002 0.96 4
63 CAFE_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   377.72 377.72 377.72 0.00 90.00 377.72 1.00 0.00 CAFE_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
64 LOBBY_FLR_1_WALL_1_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.738 0.664   209.87 213.77 209.87 0.00 90.00 53.95 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
65 LOBBY_FLR_1_WALL_1_NORTH_DOOR1 Door LOBBY_FLR_1_WALL_1_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
66 LOBBY_FLR_1_WALL_1_NORTH_DOOR2 Door LOBBY_FLR_1_WALL_1_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
67 LOBBY_FLR_1_WALL_2_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.738 0.664   12.08 12.08 12.08 0.00 90.00 3.05 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
68 LOBBY_FLR_1_WALL_1_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.738 0.664   82.79 167.88 82.79 180.00 90.00 42.37 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
69 LOBBY_FLR_1_WALL_SOUTH_WINDOW Window LOBBY_FLR_1_WALL_1_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.3856_SHGC_0.4 N/A 2.191 No 85.08 85.08 85.08 180.00 90.00 39.95 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
70 LOBBY_FLR_1_WALL_1_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.738 0.664   41.06 41.06 41.06 270.00 90.00 10.36 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
71 LOBBY_FLR_1_WALL_2_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   45.89 45.89 45.89 180.00 90.00 11.58 3.96 0.00 RETAIL_2_FLR_1_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
72 LOBBY_FLR_1_WALL_3_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.11 111.11 111.11 180.00 90.00 28.04 3.96 0.00 CAFE_FLR_1_WALL_1_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
73 LOBBY_FLR_1_WALL_2_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.95 22.95 22.95 270.00 90.00 5.79 3.96 0.00 RETAIL_1_FLR_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
74 LOBBY_FLR_1_WALL_3_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.57 26.57 26.57 270.00 90.00 6.71 3.96 0.00 RETAIL_2_FLR_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
75 LOBBY_FLR_1_WALL_4_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 270.00 90.00 10.36 3.96 0.00 STORAGE_FLR_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
76 LOBBY_FLR_1_WALL_3_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   62.80 62.80 62.80 0.00 90.00 15.85 3.96 0.00 MECH_FLR_1_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
77 LOBBY_FLR_1_WALL_4_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   36.23 36.23 36.23 0.00 90.00 9.14 3.96 0.00 STORAGE_FLR_1_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
78 LOBBY_FLR_1_WALL_1_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 90.00 90.00 10.36 3.96 0.00 MECH_FLR_1_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
79 LOBBY_FLR_1_WALL_2_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.95 22.95 22.95 90.00 90.00 5.79 3.96 0.00 CAFE_FLR_1_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
80 LOBBY_FLR_1_WALL_3_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   67.63 67.63 67.63 90.00 90.00 17.07 3.96 0.00 LAUNDRY_FLR_1_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
81 LOBBY_FLR_1_FLOOR_1 Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   1088.56 1088.56 1088.56 180.00 180.00 32.99 32.99 0.00 BASEMENT_CEILING_7 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 6
82 LOBBY_FLR_1_FLOOR_2 Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   219.63 219.63 219.63 90.00 180.00 14.82 14.82 0.00 BASEMENT_CEILING_8 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 6
83 LOBBY_FLR_1_CEILING_1 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   1062.83 1062.83 1062.83 270.00 0.00 32.60 32.60 0.00 LOBBY_FLR_1_CEILING_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 10
84 LOBBY_FLR_1_CEILING_2 Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.228 0.219   245.35 245.35 245.35 180.00 0.00 42.37 5.79 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 4.22E-003 1.00 4
85 LOBBY_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   2616.37 2616.37 2616.37 0.00 90.00 2616.37 1.00 0.00 LOBBY_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
86 ROOM_1_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.016 0.882   9.34 13.94 9.34 180.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
87 ROOM_1_FLR_3_WALL_SOUTH_WINDOW Window ROOM_1_FLR_3_WALL_SOUTH Window5 Detailed Fenestration RESWINDOW_U_0.3856_SHGC_0.4 N/A 2.191 No 4.60 4.60 4.60 180.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
88 ROOM_1_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.016 0.882   17.43 26.01 17.43 270.00 90.00 8.54 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
89 ROOM_1_FLR_3_WALL_WEST_WINDOW Window ROOM_1_FLR_3_WALL_WEST Window5 Detailed Fenestration RESWINDOW_U_0.3856_SHGC_0.4 N/A 2.191 No 8.58 8.58 8.58 270.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
90 ROOM_1_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 0.00 90.00 4.57 3.05 0.00 ROOM_2_FLR_3_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
91 ROOM_1_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.54 3.05 0.00 CORRIDOR_FLR_3_WALL_3_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
92 ROOM_1_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   39.02 39.02 39.02 0.00 180.00 4.57 8.54 0.00 ROOM_1_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
93 ROOM_1_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   39.02 39.02 39.02 180.00 0.00 4.57 8.54 0.00 ROOM_1_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
94 ROOM_1_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.04 78.04 78.04 0.00 90.00 78.04 1.00 0.00 ROOM_1_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
95 ROOM_2_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.016 0.882   9.34 13.94 9.34 0.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
96 ROOM_2_FLR_3_WALL_NORTH_WINDOW Window ROOM_2_FLR_3_WALL_NORTH Window5 Detailed Fenestration RESWINDOW_U_0.3856_SHGC_0.4 N/A 2.191 No 4.60 4.60 4.60 0.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
97 ROOM_2_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.016 0.882   17.43 26.01 17.43 270.00 90.00 8.53 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
98 ROOM_2_FLR_3_WALL_WEST_WINDOW Window ROOM_2_FLR_3_WALL_WEST Window5 Detailed Fenestration RESWINDOW_U_0.3856_SHGC_0.4 N/A 2.191 No 8.58 8.58 8.58 270.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
99 ROOM_2_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.53 3.05 0.00 CORRIDOR_FLR_3_WALL_4_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
100 ROOM_2_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 180.00 90.00 4.57 3.05 0.00 ROOM_1_FLR_3_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
101 ROOM_2_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   39.02 39.02 39.02 0.00 180.00 4.57 8.53 0.00 ROOM_2_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
102 ROOM_2_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   39.02 39.02 39.02 180.00 0.00 4.57 8.53 0.00 ROOM_2_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
103 ROOM_2_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.03 78.03 78.03 0.00 90.00 78.03 1.00 0.00 ROOM_2_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
104 ROOM_3_MULT19_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.016 0.882   7.47 11.15 7.47 180.00 90.00 3.66 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
105 ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW Window ROOM_3_MULT19_FLR_3_WALL_SOUTH Window5 Detailed Fenestration RESWINDOW_U_0.3856_SHGC_0.4 N/A 2.191 No 3.68 3.68 3.68 180.00 90.00 3.02 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
106 ROOM_3_MULT19_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 0.00 90.00 3.66 3.05 0.00 ROOM_3_MULT19_FLR_3_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
107 ROOM_3_MULT19_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 90.00 90.00 6.71 3.05 0.00 ROOM_3_MULT19_FLR_3_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
108 ROOM_3_MULT19_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 270.00 90.00 6.71 3.05 0.00 ROOM_3_MULT19_FLR_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
109 ROOM_3_MULT19_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   24.52 24.52 24.52 0.00 180.00 3.66 6.71 0.00 ROOM_3_MULT19_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
110 ROOM_3_MULT19_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   24.52 24.52 24.52 180.00 0.00 3.66 6.71 0.00 ROOM_3_MULT19_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
111 ROOM_3_MULT19_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   49.05 49.05 49.05 0.00 90.00 49.05 1.00 0.00 ROOM_3_MULT19_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
112 ROOM_4_MULT19_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.016 0.882   7.47 11.15 7.47 0.00 90.00 3.66 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
113 ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW Window ROOM_4_MULT19_FLR_3_WALL_NORTH Window5 Detailed Fenestration RESWINDOW_U_0.3856_SHGC_0.4 N/A 2.191 No 3.68 3.68 3.68 0.00 90.00 3.02 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
114 ROOM_4_MULT19_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 90.00 90.00 6.71 3.05 0.00 ROOM_4_MULT19_FLR_3_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
115 ROOM_4_MULT19_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 180.00 90.00 3.66 3.05 0.00 ROOM_4_MULT19_FLR_3_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
116 ROOM_4_MULT19_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 270.00 90.00 6.71 3.05 0.00 ROOM_4_MULT19_FLR_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
117 ROOM_4_MULT19_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   24.53 24.53 24.53 0.00 180.00 3.66 6.71 0.00 ROOM_4_MULT19_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
118 ROOM_4_MULT19_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   24.53 24.53 24.53 180.00 0.00 3.66 6.71 0.00 ROOM_4_MULT19_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
119 ROOM_4_MULT19_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   49.06 49.06 49.06 0.00 90.00 49.06 1.00 0.00 ROOM_4_MULT19_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
120 ROOM_5_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.016 0.882   17.43 26.01 17.43 90.00 90.00 8.54 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
121 ROOM_5_FLR_3_WALL_EAST_WINDOW Window ROOM_5_FLR_3_WALL_EAST Window5 Detailed Fenestration RESWINDOW_U_0.3856_SHGC_0.4 N/A 2.191 No 8.58 8.58 8.58 90.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
122 ROOM_5_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.016 0.882   9.34 13.94 9.34 180.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
123 ROOM_5_FLR_3_WALL_SOUTH_WINDOW Window ROOM_5_FLR_3_WALL_SOUTH Window5 Detailed Fenestration RESWINDOW_U_0.3856_SHGC_0.4 N/A 2.191 No 4.60 4.60 4.60 180.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
124 ROOM_5_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 0.00 90.00 4.57 3.05 0.00 ROOM_6_FLR_3_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
125 ROOM_5_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 270.00 90.00 8.54 3.05 0.00 CORRIDOR_FLR_3_WALL_3_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
126 ROOM_5_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   39.02 39.02 39.02 0.00 180.00 4.57 8.54 0.00 ROOM_5_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
127 ROOM_5_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   39.02 39.02 39.02 180.00 0.00 4.57 8.54 0.00 ROOM_5_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
128 ROOM_5_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.04 78.04 78.04 0.00 90.00 78.04 1.00 0.00 ROOM_5_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
129 ROOM_6_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.016 0.882   9.34 13.94 9.34 0.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
130 ROOM_6_FLR_3_WALL_NORTH_WINDOW Window ROOM_6_FLR_3_WALL_NORTH Window5 Detailed Fenestration RESWINDOW_U_0.3856_SHGC_0.4 N/A 2.191 No 4.60 4.60 4.60 0.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
131 ROOM_6_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.016 0.882   17.43 26.01 17.43 90.00 90.00 8.53 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
132 ROOM_6_FLR_3_WALL_EAST_WINDOW Window ROOM_6_FLR_3_WALL_EAST Window5 Detailed Fenestration RESWINDOW_U_0.3856_SHGC_0.4 N/A 2.191 No 8.58 8.58 8.58 90.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
133 ROOM_6_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 180.00 90.00 4.57 3.05 0.00 ROOM_5_FLR_3_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
134 ROOM_6_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 270.00 90.00 8.53 3.05 0.00 CORRIDOR_FLR_3_WALL_4_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
135 ROOM_6_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   39.02 39.02 39.02 0.00 180.00 4.57 8.53 0.00 ROOM_6_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
136 ROOM_6_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   39.02 39.02 39.02 180.00 0.00 4.57 8.53 0.00 ROOM_6_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
137 ROOM_6_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.03 78.03 78.03 0.00 90.00 78.03 1.00 0.00 ROOM_6_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
138 CORRIDOR_FLR_3_WALL_1_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.016 0.882   11.83 17.65 11.83 0.00 90.00 5.79 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
139 CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW Window CORRIDOR_FLR_3_WALL_1_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.3856_SHGC_0.4 N/A 2.191 No 5.82 5.82 5.82 0.00 90.00 4.78 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
140 CORRIDOR_FLR_3_WALL_2_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.016 0.882   4.35 6.50 4.35 0.00 90.00 2.13 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
141 CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW Window CORRIDOR_FLR_3_WALL_2_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.3856_SHGC_0.4 N/A 2.191 No 2.15 2.15 2.15 0.00 90.00 1.76 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
142 CORRIDOR_FLR_3_WALL_1_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.016 0.882   4.36 6.50 4.36 180.00 90.00 2.13 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
143 CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW Window CORRIDOR_FLR_3_WALL_1_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.3856_SHGC_0.4 N/A 2.191 No 2.15 2.15 2.15 180.00 90.00 1.76 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
144 CORRIDOR_FLR_3_WALL_2_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.016 0.882   11.83 17.65 11.83 180.00 90.00 5.79 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
145 CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW Window CORRIDOR_FLR_3_WALL_2_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.3856_SHGC_0.4 N/A 2.191 No 5.82 5.82 5.82 180.00 90.00 4.78 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
146 CORRIDOR_FLR_3_WALL_3_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   211.82 211.82 211.82 0.00 90.00 69.50 3.05 0.00 CORRIDOR_FLR_3_WALL_3_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
147 CORRIDOR_FLR_3_WALL_1_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 90.00 90.00 6.71 3.05 0.00 CORRIDOR_FLR_3_WALL_1_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
148 CORRIDOR_FLR_3_WALL_2_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 90.00 90.00 6.71 3.05 0.00 CORRIDOR_FLR_3_WALL_2_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
149 CORRIDOR_FLR_3_WALL_3_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.54 3.05 0.00 ROOM_5_FLR_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
150 CORRIDOR_FLR_3_WALL_4_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.53 3.05 0.00 ROOM_6_FLR_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
151 CORRIDOR_FLR_3_WALL_3_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   211.82 211.82 211.82 180.00 90.00 69.49 3.05 0.00 CORRIDOR_FLR_3_WALL_3_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
152 CORRIDOR_FLR_3_WALL_1_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 270.00 90.00 6.71 3.05 0.00 CORRIDOR_FLR_3_WALL_1_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
153 CORRIDOR_FLR_3_WALL_2_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 270.00 90.00 6.71 3.05 0.00 CORRIDOR_FLR_3_WALL_2_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
154 CORRIDOR_FLR_3_WALL_3_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 270.00 90.00 8.54 3.05 0.00 ROOM_1_FLR_3_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
155 CORRIDOR_FLR_3_WALL_4_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 270.00 90.00 8.53 3.05 0.00 ROOM_2_FLR_3_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
156 CORRIDOR_FLR_3_FLOOR_1 Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   74.32 74.32 74.32 180.00 180.00 8.62 8.62 0.00 CORRIDOR_FLR_3_FLOOR_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 6
157 CORRIDOR_FLR_3_FLOOR_2 Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   240.77 240.77 240.77 270.00 180.00 3.66 65.84 0.00 CORRIDOR_FLR_3_FLOOR_2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
158 CORRIDOR_FLR_3_FLOOR_3 Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   74.32 74.32 74.32 90.00 180.00 8.62 8.62 0.00 CORRIDOR_FLR_3_FLOOR_3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 6
159 CORRIDOR_FLR_3_CEILING_1 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   74.32 74.32 74.32 90.00 0.00 8.62 8.62 0.00 CORRIDOR_FLR_3_CEILING_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 6
160 CORRIDOR_FLR_3_CEILING_2 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   240.77 240.77 240.77 90.00 0.00 3.66 65.84 0.00 CORRIDOR_FLR_3_CEILING_2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
161 CORRIDOR_FLR_3_CEILING_3 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   74.32 74.32 74.32 90.00 0.00 8.62 8.62 0.00 CORRIDOR_FLR_3_CEILING_3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 6
162 CORRIDOR_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   778.81 778.81 778.81 0.00 90.00 778.81 1.00 0.00 CORRIDOR_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
163 ROOM_1_FLR_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_TOP 1.081 0.931   9.34 13.94 9.34 180.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
164 ROOM_1_FLR_6_WALL_SOUTH_WINDOW Window ROOM_1_FLR_6_WALL_SOUTH Window5 Detailed Fenestration RESWINDOW_U_0.3856_SHGC_0.4 N/A 2.191 No 4.60 4.60 4.60 180.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
165 ROOM_1_FLR_6_WALL_WEST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_TOP 1.081 0.931   17.43 26.01 17.43 270.00 90.00 8.54 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
166 ROOM_1_FLR_6_WALL_WEST_WINDOW Window ROOM_1_FLR_6_WALL_WEST Window5 Detailed Fenestration RESWINDOW_U_0.3856_SHGC_0.4 N/A 2.191 No 8.58 8.58 8.58 270.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
167 ROOM_1_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 0.00 90.00 4.57 3.05 0.00 ROOM_2_FLR_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
168 ROOM_1_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.54 3.05 0.00 ROOM_1_FLR_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
169 ROOM_1_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   39.02 39.02 39.02 0.00 180.00 4.57 8.54 0.00 ROOM_1_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
170 ROOM_1_FLR_6_CEILING Roof   CTF - ConductionTransferFunction RES_ROOF 0.228 0.219   39.02 39.02 39.02 180.00 0.00 4.57 8.54 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
171 ROOM_1_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.04 78.04 78.04 0.00 90.00 78.04 1.00 0.00 ROOM_1_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
172 ROOM_2_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_TOP 1.081 0.931   9.34 13.94 9.34 0.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
173 ROOM_2_FLR_6_WALL_NORTH_WINDOW Window ROOM_2_FLR_6_WALL_NORTH Window5 Detailed Fenestration RESWINDOW_U_0.3856_SHGC_0.4 N/A 2.191 No 4.60 4.60 4.60 0.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
174 ROOM_2_FLR_6_WALL_WEST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_TOP 1.081 0.931   17.43 26.01 17.43 270.00 90.00 8.53 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
175 ROOM_2_FLR_6_WALL_WEST_WINDOW Window ROOM_2_FLR_6_WALL_WEST Window5 Detailed Fenestration RESWINDOW_U_0.3856_SHGC_0.4 N/A 2.191 No 8.58 8.58 8.58 270.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
176 ROOM_2_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.53 3.05 0.00 ROOM_2_FLR_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
177 ROOM_2_FLR_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 180.00 90.00 4.57 3.05 0.00 ROOM_1_FLR_6_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
178 ROOM_2_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   39.02 39.02 39.02 0.00 180.00 4.57 8.53 0.00 ROOM_2_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
179 ROOM_2_FLR_6_CEILING Roof   CTF - ConductionTransferFunction RES_ROOF 0.228 0.219   39.02 39.02 39.02 180.00 0.00 4.57 8.53 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
180 ROOM_2_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.03 78.03 78.03 0.00 90.00 78.03 1.00 0.00 ROOM_2_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
181 ROOM_3_MULT9_FLR_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_TOP 1.081 0.931   13.70 20.44 13.70 180.00 90.00 6.71 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
182 ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW Window ROOM_3_MULT9_FLR_6_WALL_SOUTH Window5 Detailed Fenestration RESWINDOW_U_0.3856_SHGC_0.4 N/A 2.191 No 6.74 6.74 6.74 180.00 90.00 5.53 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
183 ROOM_3_MULT9_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 0.00 90.00 6.71 3.05 0.00 ROOM_3_MULT9_FLR_6_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
184 ROOM_3_MULT9_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 90.00 90.00 3.66 3.05 0.00 ROOM_3_MULT9_FLR_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
185 ROOM_3_MULT9_FLR_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 270.00 90.00 3.66 3.05 0.00 ROOM_3_MULT9_FLR_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
186 ROOM_3_MULT9_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   24.53 24.53 24.53 0.00 180.00 6.71 3.66 0.00 ROOM_3_MULT9_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
187 ROOM_3_MULT9_FLR_6_CEILING Roof   CTF - ConductionTransferFunction RES_ROOF 0.228 0.219   24.53 24.53 24.53 180.00 0.00 6.71 3.66 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
188 ROOM_3_MULT9_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   49.06 49.06 49.06 0.00 90.00 49.06 1.00 0.00 ROOM_3_MULT9_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
189 BANQUET_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.081 0.931   65.36 97.55 65.36 0.00 90.00 32.00 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
190 BANQUET_FLR_6_WALL_NORTH_WINDOW Window BANQUET_FLR_6_WALL_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.3856_SHGC_0.4 N/A 2.191 No 32.19 32.19 32.19 0.00 90.00 26.40 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
191 BANQUET_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 90.00 90.00 10.36 3.05 0.00 CORRIDOR_FLR_6_WALL_3_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
192 BANQUET_FLR_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   97.55 97.55 97.55 180.00 90.00 32.00 3.05 0.00 CORRIDOR_FLR_6_WALL_3_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
193 BANQUET_FLR_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 270.00 90.00 10.36 3.05 0.00 CORRIDOR_FLR_6_WALL_1_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
194 BANQUET_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   331.66 331.66 331.66 0.00 180.00 32.00 10.36 0.00 BANQUET_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
195 BANQUET_FLR_6_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.228 0.219   331.66 331.66 331.66 180.00 0.00 32.00 10.36 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
196 BANQUET_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   663.31 663.31 663.31 0.00 90.00 663.31 1.00 0.00 BANQUET_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
197 DINING_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.081 0.931   65.36 97.55 65.36 0.00 90.00 32.00 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
198 DINING_FLR_6_WALL_NORTH_WINDOW Window DINING_FLR_6_WALL_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.3856_SHGC_0.4 N/A 2.191 No 32.19 32.19 32.19 0.00 90.00 26.40 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
199 DINING_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 90.00 90.00 10.36 3.05 0.00 KITCHEN_FLR_6_WALL_2_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
200 DINING_FLR_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   97.55 97.55 97.55 180.00 90.00 32.00 3.05 0.00 DINING_FLR_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
201 DINING_FLR_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 270.00 90.00 10.36 3.05 0.00 CORRIDOR_FLR_6_WALL_2_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
202 DINING_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   331.66 331.66 331.66 0.00 180.00 32.00 10.36 0.00 DINING_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
203 DINING_FLR_6_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.228 0.219   331.66 331.66 331.66 180.00 0.00 32.00 10.36 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
204 DINING_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   663.31 663.31 663.31 0.00 90.00 663.31 1.00 0.00 DINING_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
205 KITCHEN_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.081 0.931   16.77 21.37 16.77 0.00 90.00 7.01 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
206 KITCHEN_FLR_6_WALL_NORTH_WINDOW Window KITCHEN_FLR_6_WALL_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.3856_SHGC_0.4 N/A 2.191 No 4.60 4.60 4.60 0.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
207 KITCHEN_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.081 0.931   34.86 52.03 34.86 90.00 90.00 17.07 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
208 KITCHEN_FLR_6_WALL_EAST_WINDOW Window KITCHEN_FLR_6_WALL_EAST Window5 Detailed Fenestration NONRESWINDOW_U_0.3856_SHGC_0.4 N/A 2.191 No 17.17 17.17 17.17 90.00 90.00 14.08 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
209 KITCHEN_FLR_6_WALL_1_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.081 0.931   9.34 13.94 9.34 180.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
210 KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW Window KITCHEN_FLR_6_WALL_1_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.3856_SHGC_0.4 N/A 2.191 No 4.60 4.60 4.60 180.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
211 KITCHEN_FLR_6_WALL_2_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 180.00 90.00 2.44 3.05 0.00 KITCHEN_FLR_6_WALL_2_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
212 KITCHEN_FLR_6_WALL_1_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 270.00 90.00 6.71 3.05 0.00 CORRIDOR_FLR_6_WALL_3_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
213 KITCHEN_FLR_6_WALL_2_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 270.00 90.00 10.36 3.05 0.00 DINING_FLR_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
214 KITCHEN_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   103.30 103.30 103.30 180.00 180.00 10.16 10.16 0.00 KITCHEN_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 6
215 KITCHEN_FLR_6_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.228 0.219   103.30 103.30 103.30 270.00 0.00 10.16 10.16 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 6
216 KITCHEN_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   206.61 206.61 206.61 0.00 90.00 206.61 1.00 0.00 KITCHEN_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
217 CORRIDOR_FLR_6_WALL_1_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.081 0.931   11.83 17.65 11.83 0.00 90.00 5.79 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
218 CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW Window CORRIDOR_FLR_6_WALL_1_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.3856_SHGC_0.4 N/A 2.191 No 5.82 5.82 5.82 0.00 90.00 4.78 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
219 CORRIDOR_FLR_6_WALL_2_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.081 0.931   10.58 15.79 10.58 0.00 90.00 5.18 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
220 CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW Window CORRIDOR_FLR_6_WALL_2_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.3856_SHGC_0.4 N/A 2.191 No 5.21 5.21 5.21 0.00 90.00 4.27 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
221 CORRIDOR_FLR_6_WALL_2_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.081 0.931   34.86 52.03 34.86 180.00 90.00 17.07 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
222 CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW Window CORRIDOR_FLR_6_WALL_2_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.3856_SHGC_0.4 N/A 2.191 No 17.17 17.17 17.17 180.00 90.00 14.08 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
223 CORRIDOR_FLR_6_WALL_3_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   97.55 97.55 97.55 0.00 90.00 32.00 3.05 0.00 BANQUET_FLR_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
224 CORRIDOR_FLR_6_WALL_4_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   104.98 104.98 104.98 0.00 90.00 34.44 3.05 0.00 CORRIDOR_FLR_6_WALL_4_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
225 CORRIDOR_FLR_6_WALL_1_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   183.95 183.95 183.95 180.00 90.00 60.35 3.05 0.00 CORRIDOR_FLR_6_WALL_1_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
226 CORRIDOR_FLR_6_WALL_1_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 270.00 90.00 3.66 3.05 0.00 CORRIDOR_FLR_6_WALL_1_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
227 CORRIDOR_FLR_6_WALL_2_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   40.88 40.88 40.88 270.00 90.00 13.41 3.05 0.00 CORRIDOR_FLR_6_WALL_2_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
228 CORRIDOR_FLR_6_WALL_3_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 270.00 90.00 10.36 3.05 0.00 BANQUET_FLR_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
229 CORRIDOR_FLR_6_WALL_1_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 90.00 90.00 10.36 3.05 0.00 BANQUET_FLR_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
230 CORRIDOR_FLR_6_WALL_2_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 90.00 90.00 10.36 3.05 0.00 DINING_FLR_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
231 CORRIDOR_FLR_6_WALL_3_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 90.00 90.00 6.71 3.05 0.00 KITCHEN_FLR_6_WALL_1_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
232 CORRIDOR_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   412.12 412.12 412.12 180.00 180.00 20.30 20.30 0.00 CORRIDOR_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 12
233 CORRIDOR_FLR_6_CEILING_1 Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.228 0.219   244.71 244.71 244.71 90.00 0.00 15.64 15.64 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 8
234 CORRIDOR_FLR_6_CEILING_2 Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.228 0.219   167.42 167.42 167.42 270.00 0.00 12.94 12.94 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 6
235 CORRIDOR_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   824.25 824.25 824.25 0.00 90.00 824.25 1.00 0.00 CORRIDOR_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0


Environment

Environment Name Environment Type Start Date End Date Start DayOfWeek Duration {#days} Source:Start DayOfWeek Use Daylight Saving Use Holidays Apply Weekend Holiday Rule Use Rain Values Use Snow Values Sky Temperature Model
1 RUNPERIOD 1 WeatherFileRunPeriod 01/01/2017 12/31/2017 Sunday 365 Use RunPeriod Specified Day No No No Yes Yes Clark and Allen


Environment:Special Days

Special Day Name Special Day Type Source Start Date Duration {#days}
1 NEW YEARS DAY Holiday InputFile 01/01 1Environment:Special Days


Environment:Daylight Saving

Daylight Saving Indicator Source Start Date End Date
1 Yes InputFile 03/12 11/05


Tabular Report

Style Unit Conversion
1 Commaandhtml commaandhtml


Warmup Convergence Information

Zone Name Environment Type/Name Average Warmup Temperature Difference {deltaC} Std Dev Warmup Temperature Difference {deltaC} Max Temperature Pass/Fail Convergence Min Temperature Pass/Fail Convergence Average Warmup Load Difference {W} Std Dev Warmup Load Difference {W} Heating Load Pass/Fail Convergence Cooling Load Pass/Fail Convergence
1 BASEMENT RunPeriod: RUNPERIOD 1 5.2623365258E-003 1.2711278802E-002 Pass Pass 1.3154118037E-002 3.2912598172E-002 Pass Pass
2 RETAIL_1_FLR_1 RunPeriod: RUNPERIOD 1 2.8056424181E-003 2.2619808357E-003 Pass Pass 0.1559146167 0.5709625185 Pass Pass
3 RETAIL_2_FLR_1 RunPeriod: RUNPERIOD 1 1.5222009089E-003 1.1448392363E-003 Pass Pass 2.1000204833E-002 3.9581332162E-002 Pass Pass
4 MECH_FLR_1 RunPeriod: RUNPERIOD 1 8.7590414733E-004 6.3518476069E-004 Pass Pass 5.0254054477E-002 8.8083112936E-002 Pass Pass
5 STORAGE_FLR_1 RunPeriod: RUNPERIOD 1 7.3735640199E-004 5.8347698498E-004 Pass Pass 0.3935060497 0.8727603337 Pass Pass
6 LAUNDRY_FLR_1 RunPeriod: RUNPERIOD 1 4.5068532314E-002 0.1381091053 Pass Pass 1.9182102397E-002 5.5559894979E-002 Pass Pass
7 CAFE_FLR_1 RunPeriod: RUNPERIOD 1 3.8905976687E-003 6.1276763221E-003 Pass Pass 2.8725664628E-002 5.0893171198E-002 Pass Pass
8 LOBBY_FLR_1 RunPeriod: RUNPERIOD 1 1.6942172878E-003 1.3453041884E-003 Pass Pass 2.0889470063E-002 4.2423677550E-002 Pass Pass
9 ROOM_1_FLR_3 RunPeriod: RUNPERIOD 1 3.7671845067E-002 0.1321052577 Pass Pass 7.6084375274 86.9806950726 Pass Pass
10 ROOM_2_FLR_3 RunPeriod: RUNPERIOD 1 7.6198652059E-002 0.2297708712 Pass Pass 0.3168847591 1.6927311196 Pass Pass
11 ROOM_3_MULT19_FLR_3 RunPeriod: RUNPERIOD 1 2.0865844607E-002 3.8527408415E-002 Pass Pass 3.2107522850E-002 6.5048796273E-002 Pass Pass
12 ROOM_4_MULT19_FLR_3 RunPeriod: RUNPERIOD 1 1.7614097657E-002 6.4680758334E-002 Pass Pass 0.1608308027 0.6767559376 Pass Pass
13 ROOM_5_FLR_3 RunPeriod: RUNPERIOD 1 4.4836538050E-002 0.1255821579 Pass Pass 0.1277388261 0.4728897339 Pass Pass
14 ROOM_6_FLR_3 RunPeriod: RUNPERIOD 1 7.0007751814E-002 0.2209586244 Pass Pass 0.4361486565 2.4164806535 Pass Pass
15 CORRIDOR_FLR_3 RunPeriod: RUNPERIOD 1 6.3812172119E-004 4.8304849761E-004 Pass Pass 3.9222876311E-002 6.5343668307E-002 Pass Pass
16 ROOM_1_FLR_6 RunPeriod: RUNPERIOD 1 5.8641403791E-002 0.2071662096 Pass Pass 0.2071434924 0.8419709962 Pass Pass
17 ROOM_2_FLR_6 RunPeriod: RUNPERIOD 1 9.3757782771E-002 0.3051395688 Pass Pass 0.3624285474 1.3362502124 Pass Pass
18 ROOM_3_MULT9_FLR_6 RunPeriod: RUNPERIOD 1 4.8142350995E-002 0.2158637755 Pass Pass 0.1899321171 0.6235026316 Pass Pass
19 BANQUET_FLR_6 RunPeriod: RUNPERIOD 1 2.5483023527E-002 6.8920311564E-002 Pass Pass 1.2170807723E-002 3.5743555358E-002 Pass Pass
20 DINING_FLR_6 RunPeriod: RUNPERIOD 1 2.7620822775E-002 6.9168347657E-002 Pass Pass 1.0992329383E-002 3.0770220901E-002 Pass Pass
21 KITCHEN_FLR_6 RunPeriod: RUNPERIOD 1 7.1005009587E-002 0.1153196099 Pass Pass 1.7397091246E-002 3.3094615395E-002 Pass Pass
22 CORRIDOR_FLR_6 RunPeriod: RUNPERIOD 1 1.3178323339E-003 1.0752371982E-003 Pass Pass 0.6048549036 2.0847357773 Pass Pass



Table of Contents

Report: Annual Heat Emissions Summary

For: Entire Facility

Timestamp: 2023-10-16 08:58:31

Heat Emission by Components

Envelope Convection Zone Exfiltration Zone Exhaust Air HVAC Relief Air HVAC Reject Heat Total
Heat Emissions [GJ] 3443.26 127.23 1032.85 12281.91 2691.65 19576.92



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2023-10-16 08:58:31

SizingPeriod:DesignDay

Maximum Dry Bulb [C] Daily Temperature Range [deltaC] Humidity Value Humidity Type Wind Speed [m/s] Wind Direction
WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB -4.30 0.00 -4.30 Wetbulb [C] 1.20 110.00
WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 26.40 9.10 17.00 Wetbulb [C] 2.10 90.00


Monthly Precipitation Summary

Monthly Total Precipitation from .epw [mm] Monthly Total Hours of Rain from .epw Monthly Total Precipitation in Site:Precipitation [mm] Monthly Total Roof Irrigation Depth [mm] Monthly Total Rain Collection Volume [m3]
Jan 0.00 0      
Feb 42.00 35      
Mar 0.00 0      
Apr 0.00 0      
May 40.00 22      
Jun 4.00 8      
Jul 5.00 4      
Aug 7.00 8      
Sep 17.00 10      
Oct 50.00 49      
Nov 69.00 59      
Dec 95.00 53      


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2023-10-16 08:58:31

Opaque Exterior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
BASEMENT_WALL_NORTH BASEMENT_WALL_NORTH_CFACTOR 1.00 0.399 0.419 211.13 211.13 0.00 90.00 N
BASEMENT_WALL_EAST BASEMENT_WALL_EAST_CFACTOR 1.00 0.399 0.419 55.76 55.76 90.00 90.00 E
BASEMENT_WALL_SOUTH BASEMENT_WALL_SOUTH_CFACTOR 1.00 0.399 0.419 211.13 211.13 180.00 90.00 S
BASEMENT_WALL_WEST BASEMENT_WALL_WEST_CFACTOR 1.00 0.399 0.419 55.76 55.76 270.00 90.00 W
RETAIL_1_FLR_1_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 0.664 0.738 45.89 22.63 180.00 90.00 S
RETAIL_1_FLR_1_WALL_WEST NONRES_EXT_WALL_GRD 0.30 0.664 0.738 22.95 22.95 270.00 90.00 W
RETAIL_1_FLR_1_CEILING NONRES_ROOF 0.23 0.221 0.228 67.07 67.07 180.00 0.00  
RETAIL_2_FLR_1_WALL_WEST NONRES_EXT_WALL_GRD 0.30 0.664 0.738 26.57 24.62 270.00 90.00 W
MECH_FLR_1_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 0.664 0.738 62.80 62.80 0.00 90.00 N
STORAGE_FLR_1_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 0.664 0.738 36.23 28.80 0.00 90.00 N
LAUNDRY_FLR_1_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 0.664 0.738 18.12 18.12 0.00 90.00 N
LAUNDRY_FLR_1_WALL_EAST NONRES_EXT_WALL_GRD 0.30 0.664 0.738 67.63 65.68 90.00 90.00 E
CAFE_FLR_1_WALL_EAST NONRES_EXT_WALL_GRD 0.30 0.664 0.738 22.95 21.00 90.00 90.00 E
CAFE_FLR_1_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 0.664 0.738 129.23 63.73 180.00 90.00 S
CAFE_FLR_1_CEILING NONRES_ROOF 0.23 0.221 0.228 188.86 188.86 180.00 0.00  
LOBBY_FLR_1_WALL_1_NORTH NONRES_EXT_WALL_GRD 0.30 0.664 0.738 213.77 209.87 0.00 90.00 N
LOBBY_FLR_1_WALL_2_NORTH NONRES_EXT_WALL_GRD 0.30 0.664 0.738 12.08 12.08 0.00 90.00 N
LOBBY_FLR_1_WALL_1_SOUTH NONRES_EXT_WALL_GRD 0.30 0.664 0.738 167.88 82.79 180.00 90.00 S
LOBBY_FLR_1_WALL_1_WEST NONRES_EXT_WALL_GRD 0.30 0.664 0.738 41.06 41.06 270.00 90.00 W
LOBBY_FLR_1_CEILING_2 NONRES_ROOF 0.23 0.221 0.228 245.35 245.35 180.00 0.00  
ROOM_1_FLR_3_WALL_SOUTH RES_EXT_WALL_MID 0.30 0.882 1.016 55.74 37.35 180.00 90.00 S
ROOM_1_FLR_3_WALL_WEST RES_EXT_WALL_MID 0.30 0.882 1.016 104.06 69.72 270.00 90.00 W
ROOM_2_FLR_3_WALL_NORTH RES_EXT_WALL_MID 0.30 0.882 1.016 55.74 37.35 0.00 90.00 N
ROOM_2_FLR_3_WALL_WEST RES_EXT_WALL_MID 0.30 0.882 1.016 104.05 69.71 270.00 90.00 W
ROOM_3_MULT19_FLR_3_WALL_SOUTH RES_EXT_WALL_MID 0.30 0.882 1.016 847.14 567.58 180.00 90.00 S
ROOM_4_MULT19_FLR_3_WALL_NORTH RES_EXT_WALL_MID 0.30 0.882 1.016 847.37 567.71 0.00 90.00 N
ROOM_5_FLR_3_WALL_EAST RES_EXT_WALL_MID 0.30 0.882 1.016 104.06 69.72 90.00 90.00 E
ROOM_5_FLR_3_WALL_SOUTH RES_EXT_WALL_MID 0.30 0.882 1.016 55.74 37.35 180.00 90.00 S
ROOM_6_FLR_3_WALL_NORTH RES_EXT_WALL_MID 0.30 0.882 1.016 55.74 37.35 0.00 90.00 N
ROOM_6_FLR_3_WALL_EAST RES_EXT_WALL_MID 0.30 0.882 1.016 104.05 69.71 90.00 90.00 E
CORRIDOR_FLR_3_WALL_1_NORTH NONRES_EXT_WALL_MID 0.30 0.882 1.016 70.60 47.31 0.00 90.00 N
CORRIDOR_FLR_3_WALL_2_NORTH NONRES_EXT_WALL_MID 0.30 0.882 1.016 26.01 17.42 0.00 90.00 N
CORRIDOR_FLR_3_WALL_1_SOUTH NONRES_EXT_WALL_MID 0.30 0.882 1.016 26.02 17.43 180.00 90.00 S
CORRIDOR_FLR_3_WALL_2_SOUTH NONRES_EXT_WALL_MID 0.30 0.882 1.016 70.60 47.31 180.00 90.00 S
ROOM_1_FLR_6_WALL_SOUTH RES_EXT_WALL_TOP 0.30 0.931 1.081 13.94 9.34 180.00 90.00 S
ROOM_1_FLR_6_WALL_WEST RES_EXT_WALL_TOP 0.30 0.931 1.081 26.01 17.43 270.00 90.00 W
ROOM_1_FLR_6_CEILING RES_ROOF 0.23 0.221 0.228 39.02 39.02 180.00 0.00  
ROOM_2_FLR_6_WALL_NORTH RES_EXT_WALL_TOP 0.30 0.931 1.081 13.94 9.34 0.00 90.00 N
ROOM_2_FLR_6_WALL_WEST RES_EXT_WALL_TOP 0.30 0.931 1.081 26.01 17.43 270.00 90.00 W
ROOM_2_FLR_6_CEILING RES_ROOF 0.23 0.221 0.228 39.02 39.02 180.00 0.00  
ROOM_3_MULT9_FLR_6_WALL_SOUTH RES_EXT_WALL_TOP 0.30 0.931 1.081 183.96 123.26 180.00 90.00 S
ROOM_3_MULT9_FLR_6_CEILING RES_ROOF 0.23 0.221 0.228 220.77 220.77 180.00 0.00  
BANQUET_FLR_6_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 0.931 1.081 97.55 65.36 0.00 90.00 N
BANQUET_FLR_6_CEILING NONRES_ROOF 0.23 0.221 0.228 331.66 331.66 180.00 0.00  
DINING_FLR_6_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 0.931 1.081 97.55 65.36 0.00 90.00 N
DINING_FLR_6_CEILING NONRES_ROOF 0.23 0.221 0.228 331.66 331.66 180.00 0.00  
KITCHEN_FLR_6_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 0.931 1.081 21.37 16.77 0.00 90.00 N
KITCHEN_FLR_6_WALL_EAST NONRES_EXT_WALL_TOP 0.30 0.931 1.081 52.03 34.86 90.00 90.00 E
KITCHEN_FLR_6_WALL_1_SOUTH NONRES_EXT_WALL_TOP 0.30 0.931 1.081 13.94 9.34 180.00 90.00 S
KITCHEN_FLR_6_CEILING NONRES_ROOF 0.23 0.221 0.228 103.30 103.30 270.00 0.00  
CORRIDOR_FLR_6_WALL_1_NORTH NONRES_EXT_WALL_TOP 0.30 0.931 1.081 17.65 11.83 0.00 90.00 N
CORRIDOR_FLR_6_WALL_2_NORTH NONRES_EXT_WALL_TOP 0.30 0.931 1.081 15.79 10.58 0.00 90.00 N
CORRIDOR_FLR_6_WALL_2_SOUTH NONRES_EXT_WALL_TOP 0.30 0.931 1.081 52.03 34.86 180.00 90.00 S
CORRIDOR_FLR_6_CEILING_1 NONRES_ROOF 0.23 0.221 0.228 244.71 244.71 90.00 0.00  
CORRIDOR_FLR_6_CEILING_2 NONRES_ROOF 0.23 0.221 0.228 167.42 167.42 270.00 0.00  


Opaque Interior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
BASEMENT_FLOOR BASEMENT_FLOOR 0.30 1.441 2.705 1978.83 1978.83 0.00 180.00  
BASEMENT_CEILING_1 NONRES_FLOOR_CEILING 0.30 0.186 0.196 67.07 67.07 180.00 0.00  
BASEMENT_CEILING_2 NONRES_FLOOR_CEILING 0.30 0.186 0.196 77.67 77.67 180.00 0.00  
BASEMENT_CEILING_3 NONRES_FLOOR_CEILING 0.30 0.186 0.196 164.24 164.24 180.00 0.00  
BASEMENT_CEILING_4 NONRES_FLOOR_CEILING 0.30 0.186 0.196 94.76 94.76 180.00 0.00  
BASEMENT_CEILING_5 NONRES_FLOOR_CEILING 0.30 0.186 0.196 78.04 78.04 180.00 0.00  
BASEMENT_CEILING_6 NONRES_FLOOR_CEILING 0.30 0.186 0.196 188.86 188.86 180.00 0.00  
BASEMENT_CEILING_7 NONRES_FLOOR_CEILING 0.30 0.186 0.196 1088.56 1088.56 180.00 0.00  
BASEMENT_CEILING_8 NONRES_FLOOR_CEILING 0.30 0.186 0.196 219.63 219.63 90.00 0.00  
RETAIL_1_FLR_1_WALL_NORTH INT_WALL 0.30 2.511 6.299 45.89 45.89 0.00 90.00 N
RETAIL_1_FLR_1_WALL_EAST INT_WALL 0.30 2.511 6.299 22.95 22.95 90.00 90.00 E
RETAIL_1_FLR_1_FLOOR NONRES_FLOOR 0.30 0.186 0.196 67.07 67.07 0.00 180.00  
RETAIL_2_FLR_1_WALL_SOUTH INT_WALL 0.30 2.511 6.299 45.89 45.89 180.00 90.00 S
RETAIL_2_FLR_1_WALL_NORTH INT_WALL 0.30 2.511 6.299 45.89 45.89 0.00 90.00 N
RETAIL_2_FLR_1_WALL_EAST INT_WALL 0.30 2.511 6.299 26.57 26.57 90.00 90.00 E
RETAIL_2_FLR_1_FLOOR NONRES_FLOOR 0.30 0.186 0.196 77.67 77.67 0.00 180.00  
RETAIL_2_FLR_1_CEILING NONRES_FLOOR_CEILING 0.30 0.188 0.196 77.67 77.67 180.00 0.00  
MECH_FLR_1_WALL_EAST INT_WALL 0.30 2.511 6.299 41.06 41.06 90.00 90.00 E
MECH_FLR_1_WALL_SOUTH INT_WALL 0.30 2.511 6.299 62.80 62.80 180.00 90.00 S
MECH_FLR_1_WALL_WEST INT_WALL 0.30 2.511 6.299 41.06 41.06 270.00 90.00 W
MECH_FLR_1_FLOOR NONRES_FLOOR 0.30 0.186 0.196 164.24 164.24 0.00 180.00  
MECH_FLR_1_CEILING NONRES_FLOOR_CEILING 0.30 0.188 0.196 164.24 164.24 180.00 0.00  
STORAGE_FLR_1_WALL_EAST INT_WALL 0.30 2.511 6.299 41.06 41.06 90.00 90.00 E
STORAGE_FLR_1_WALL_SOUTH INT_WALL 0.30 2.511 6.299 36.23 36.23 180.00 90.00 S
STORAGE_FLR_1_WALL_WEST INT_WALL 0.30 2.511 6.299 41.06 41.06 270.00 90.00 W
STORAGE_FLR_1_FLOOR NONRES_FLOOR 0.30 0.186 0.196 94.76 94.76 0.00 180.00  
STORAGE_FLR_1_CEILING NONRES_FLOOR_CEILING 0.30 0.188 0.196 94.76 94.76 180.00 0.00  
LAUNDRY_FLR_1_WALL_SOUTH INT_WALL 0.30 2.511 6.299 18.12 18.12 180.00 90.00 S
LAUNDRY_FLR_1_WALL_WEST INT_WALL 0.30 2.511 6.299 67.63 67.63 270.00 90.00 W
LAUNDRY_FLR_1_FLOOR NONRES_FLOOR 0.30 0.186 0.196 78.04 78.04 0.00 180.00  
LAUNDRY_FLR_1_CEILING NONRES_FLOOR_CEILING 0.30 0.188 0.196 78.04 78.04 180.00 0.00  
CAFE_FLR_1_WALL_1_NORTH INT_WALL 0.30 2.511 6.299 111.11 111.11 0.00 90.00 N
CAFE_FLR_1_WALL_2_NORTH INT_WALL 0.30 2.511 6.299 18.12 18.12 0.00 90.00 N
CAFE_FLR_1_WALL_WEST INT_WALL 0.30 2.511 6.299 22.95 22.95 270.00 90.00 W
CAFE_FLR_1_FLOOR NONRES_FLOOR 0.30 0.186 0.196 188.86 188.86 0.00 180.00  
LOBBY_FLR_1_WALL_2_SOUTH INT_WALL 0.30 2.511 6.299 45.89 45.89 180.00 90.00 S
LOBBY_FLR_1_WALL_3_SOUTH INT_WALL 0.30 2.511 6.299 111.11 111.11 180.00 90.00 S
LOBBY_FLR_1_WALL_2_WEST INT_WALL 0.30 2.511 6.299 22.95 22.95 270.00 90.00 W
LOBBY_FLR_1_WALL_3_WEST INT_WALL 0.30 2.511 6.299 26.57 26.57 270.00 90.00 W
LOBBY_FLR_1_WALL_4_WEST INT_WALL 0.30 2.511 6.299 41.06 41.06 270.00 90.00 W
LOBBY_FLR_1_WALL_3_NORTH INT_WALL 0.30 2.511 6.299 62.80 62.80 0.00 90.00 N
LOBBY_FLR_1_WALL_4_NORTH INT_WALL 0.30 2.511 6.299 36.23 36.23 0.00 90.00 N
LOBBY_FLR_1_WALL_1_EAST INT_WALL 0.30 2.511 6.299 41.06 41.06 90.00 90.00 E
LOBBY_FLR_1_WALL_2_EAST INT_WALL 0.30 2.511 6.299 22.95 22.95 90.00 90.00 E
LOBBY_FLR_1_WALL_3_EAST INT_WALL 0.30 2.511 6.299 67.63 67.63 90.00 90.00 E
LOBBY_FLR_1_FLOOR_1 NONRES_FLOOR 0.30 0.186 0.196 1088.56 1088.56 180.00 180.00  
LOBBY_FLR_1_FLOOR_2 NONRES_FLOOR 0.30 0.186 0.196 219.63 219.63 90.00 180.00  
LOBBY_FLR_1_CEILING_1 NONRES_FLOOR_CEILING 0.30 0.188 0.196 1062.83 1062.83 270.00 0.00  
ROOM_1_FLR_3_WALL_NORTH INT_WALL 0.30 2.511 6.299 55.74 55.74 0.00 90.00 N
ROOM_1_FLR_3_WALL_EAST INT_WALL 0.30 2.511 6.299 104.06 104.06 90.00 90.00 E
ROOM_1_FLR_3_FLOOR NONRES_FLOOR 0.30 0.185 0.196 156.09 156.09 0.00 180.00  
ROOM_1_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 0.188 0.196 156.09 156.09 180.00 0.00  
ROOM_2_FLR_3_WALL_EAST INT_WALL 0.30 2.511 6.299 104.05 104.05 90.00 90.00 E
ROOM_2_FLR_3_WALL_SOUTH INT_WALL 0.30 2.511 6.299 55.74 55.74 180.00 90.00 S
ROOM_2_FLR_3_FLOOR NONRES_FLOOR 0.30 0.185 0.196 156.07 156.07 0.00 180.00  
ROOM_2_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 0.188 0.196 156.07 156.07 180.00 0.00  
ROOM_3_MULT19_FLR_3_WALL_NORTH INT_WALL 0.30 2.511 6.299 847.14 847.14 0.00 90.00 N
ROOM_3_MULT19_FLR_3_WALL_EAST INT_WALL 0.30 2.511 6.299 1553.43 1553.43 90.00 90.00 E
ROOM_3_MULT19_FLR_3_WALL_WEST INT_WALL 0.30 2.511 6.299 1553.43 1553.43 270.00 90.00 W
ROOM_3_MULT19_FLR_3_FLOOR NONRES_FLOOR 0.30 0.185 0.196 1863.81 1863.81 0.00 180.00  
ROOM_3_MULT19_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 0.188 0.196 1863.81 1863.81 180.00 0.00  
ROOM_4_MULT19_FLR_3_WALL_EAST INT_WALL 0.30 2.511 6.299 1553.43 1553.43 90.00 90.00 E
ROOM_4_MULT19_FLR_3_WALL_SOUTH INT_WALL 0.30 2.511 6.299 847.37 847.37 180.00 90.00 S
ROOM_4_MULT19_FLR_3_WALL_WEST INT_WALL 0.30 2.511 6.299 1553.43 1553.43 270.00 90.00 W
ROOM_4_MULT19_FLR_3_FLOOR NONRES_FLOOR 0.30 0.185 0.196 1864.32 1864.32 0.00 180.00  
ROOM_4_MULT19_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 0.188 0.196 1864.32 1864.32 180.00 0.00  
ROOM_5_FLR_3_WALL_NORTH INT_WALL 0.30 2.511 6.299 55.74 55.74 0.00 90.00 N
ROOM_5_FLR_3_WALL_WEST INT_WALL 0.30 2.511 6.299 104.06 104.06 270.00 90.00 W
ROOM_5_FLR_3_FLOOR NONRES_FLOOR 0.30 0.185 0.196 156.09 156.09 0.00 180.00  
ROOM_5_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 0.188 0.196 156.09 156.09 180.00 0.00  
ROOM_6_FLR_3_WALL_SOUTH INT_WALL 0.30 2.511 6.299 55.74 55.74 180.00 90.00 S
ROOM_6_FLR_3_WALL_WEST INT_WALL 0.30 2.511 6.299 104.05 104.05 270.00 90.00 W
ROOM_6_FLR_3_FLOOR NONRES_FLOOR 0.30 0.185 0.196 156.07 156.07 0.00 180.00  
ROOM_6_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 0.188 0.196 156.07 156.07 180.00 0.00  
CORRIDOR_FLR_3_WALL_3_NORTH INT_WALL 0.30 2.511 6.299 847.28 847.28 0.00 90.00 N
CORRIDOR_FLR_3_WALL_1_EAST INT_WALL 0.30 2.511 6.299 81.76 81.76 90.00 90.00 E
CORRIDOR_FLR_3_WALL_2_EAST INT_WALL 0.30 2.511 6.299 81.76 81.76 90.00 90.00 E
CORRIDOR_FLR_3_WALL_3_EAST INT_WALL 0.30 2.511 6.299 104.06 104.06 90.00 90.00 E
CORRIDOR_FLR_3_WALL_4_EAST INT_WALL 0.30 2.511 6.299 104.05 104.05 90.00 90.00 E
CORRIDOR_FLR_3_WALL_3_SOUTH INT_WALL 0.30 2.511 6.299 847.27 847.27 180.00 90.00 S
CORRIDOR_FLR_3_WALL_1_WEST INT_WALL 0.30 2.511 6.299 81.76 81.76 270.00 90.00 W
CORRIDOR_FLR_3_WALL_2_WEST INT_WALL 0.30 2.511 6.299 81.76 81.76 270.00 90.00 W
CORRIDOR_FLR_3_WALL_3_WEST INT_WALL 0.30 2.511 6.299 104.06 104.06 270.00 90.00 W
CORRIDOR_FLR_3_WALL_4_WEST INT_WALL 0.30 2.511 6.299 104.05 104.05 270.00 90.00 W
CORRIDOR_FLR_3_FLOOR_1 NONRES_FLOOR 0.30 0.185 0.196 297.29 297.29 180.00 180.00  
CORRIDOR_FLR_3_FLOOR_2 NONRES_FLOOR 0.30 0.185 0.196 963.06 963.06 270.00 180.00  
CORRIDOR_FLR_3_FLOOR_3 NONRES_FLOOR 0.30 0.185 0.196 297.26 297.26 90.00 180.00  
CORRIDOR_FLR_3_CEILING_1 NONRES_FLOOR_CEILING 0.30 0.188 0.196 297.29 297.29 90.00 0.00  
CORRIDOR_FLR_3_CEILING_2 NONRES_FLOOR_CEILING 0.30 0.188 0.196 963.06 963.06 90.00 0.00  
CORRIDOR_FLR_3_CEILING_3 NONRES_FLOOR_CEILING 0.30 0.188 0.196 297.26 297.26 90.00 0.00  
ROOM_1_FLR_6_WALL_NORTH INT_WALL 0.30 2.511 6.299 13.94 13.94 0.00 90.00 N
ROOM_1_FLR_6_WALL_EAST INT_WALL 0.30 2.511 6.299 26.01 26.01 90.00 90.00 E
ROOM_1_FLR_6_FLOOR NONRES_FLOOR 0.30 0.185 0.196 39.02 39.02 0.00 180.00  
ROOM_2_FLR_6_WALL_EAST INT_WALL 0.30 2.511 6.299 26.01 26.01 90.00 90.00 E
ROOM_2_FLR_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 13.94 13.94 180.00 90.00 S
ROOM_2_FLR_6_FLOOR NONRES_FLOOR 0.30 0.185 0.196 39.02 39.02 0.00 180.00  
ROOM_3_MULT9_FLR_6_WALL_NORTH INT_WALL 0.30 2.511 6.299 183.96 183.96 0.00 90.00 N
ROOM_3_MULT9_FLR_6_WALL_EAST INT_WALL 0.30 2.511 6.299 100.35 100.35 90.00 90.00 E
ROOM_3_MULT9_FLR_6_WALL_WEST INT_WALL 0.30 2.511 6.299 100.35 100.35 270.00 90.00 W
ROOM_3_MULT9_FLR_6_FLOOR NONRES_FLOOR 0.30 0.185 0.196 220.77 220.77 0.00 180.00  
BANQUET_FLR_6_WALL_EAST INT_WALL 0.30 2.511 6.299 31.59 31.59 90.00 90.00 E
BANQUET_FLR_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 97.55 97.55 180.00 90.00 S
BANQUET_FLR_6_WALL_WEST INT_WALL 0.30 2.511 6.299 31.59 31.59 270.00 90.00 W
BANQUET_FLR_6_FLOOR NONRES_FLOOR 0.30 0.185 0.196 331.66 331.66 0.00 180.00  
DINING_FLR_6_WALL_EAST INT_WALL 0.30 2.511 6.299 31.59 31.59 90.00 90.00 E
DINING_FLR_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 97.55 97.55 180.00 90.00 S
DINING_FLR_6_WALL_WEST INT_WALL 0.30 2.511 6.299 31.59 31.59 270.00 90.00 W
DINING_FLR_6_FLOOR NONRES_FLOOR 0.30 0.185 0.196 331.66 331.66 0.00 180.00  
KITCHEN_FLR_6_WALL_2_SOUTH INT_WALL 0.30 2.511 6.299 7.43 7.43 180.00 90.00 S
KITCHEN_FLR_6_WALL_1_WEST INT_WALL 0.30 2.511 6.299 20.44 20.44 270.00 90.00 W
KITCHEN_FLR_6_WALL_2_WEST INT_WALL 0.30 2.511 6.299 31.59 31.59 270.00 90.00 W
KITCHEN_FLR_6_FLOOR NONRES_FLOOR 0.30 0.185 0.196 103.30 103.30 180.00 180.00  
CORRIDOR_FLR_6_WALL_3_NORTH INT_WALL 0.30 2.511 6.299 97.55 97.55 0.00 90.00 N
CORRIDOR_FLR_6_WALL_4_NORTH INT_WALL 0.30 2.511 6.299 104.98 104.98 0.00 90.00 N
CORRIDOR_FLR_6_WALL_1_SOUTH INT_WALL 0.30 2.511 6.299 183.95 183.95 180.00 90.00 S
CORRIDOR_FLR_6_WALL_1_WEST INT_WALL 0.30 2.511 6.299 11.15 11.15 270.00 90.00 W
CORRIDOR_FLR_6_WALL_2_WEST INT_WALL 0.30 2.511 6.299 40.88 40.88 270.00 90.00 W
CORRIDOR_FLR_6_WALL_3_WEST INT_WALL 0.30 2.511 6.299 31.59 31.59 270.00 90.00 W
CORRIDOR_FLR_6_WALL_1_EAST INT_WALL 0.30 2.511 6.299 31.59 31.59 90.00 90.00 E
CORRIDOR_FLR_6_WALL_2_EAST INT_WALL 0.30 2.511 6.299 31.59 31.59 90.00 90.00 E
CORRIDOR_FLR_6_WALL_3_EAST INT_WALL 0.30 2.511 6.299 20.44 20.44 90.00 90.00 E
CORRIDOR_FLR_6_FLOOR NONRES_FLOOR 0.30 0.185 0.196 412.12 412.12 180.00 180.00  
BASEMENT_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 3957.66   0.00 90.00 N
RETAIL_1_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 134.14   0.00 90.00 N
RETAIL_2_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 155.34   0.00 90.00 N
MECH_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 328.49   0.00 90.00 N
STORAGE_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 189.52   0.00 90.00 N
LAUNDRY_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 156.08   0.00 90.00 N
CAFE_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 377.72   0.00 90.00 N
LOBBY_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 2616.37   0.00 90.00 N
ROOM_1_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 312.18   0.00 90.00 N
ROOM_2_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 312.14   0.00 90.00 N
ROOM_3_MULT19_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 3727.63   0.00 90.00 N
ROOM_4_MULT19_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 3728.64   0.00 90.00 N
ROOM_5_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 312.18   0.00 90.00 N
ROOM_6_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 312.14   0.00 90.00 N
CORRIDOR_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 3115.24   0.00 90.00 N
ROOM_1_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 78.04   0.00 90.00 N
ROOM_2_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 78.03   0.00 90.00 N
ROOM_3_MULT9_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 441.55   0.00 90.00 N
BANQUET_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 663.31   0.00 90.00 N
DINING_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 663.31   0.00 90.00 N
KITCHEN_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 206.61   0.00 90.00 N
CORRIDOR_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 824.25   0.00 90.00 N


Exterior Fenestration

Construction Frame and Divider Glass Area [m2] Frame Area [m2] Divider Area [m2] Area of One Opening [m2] Area of Multiplied Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Frame Conductance [W/m2-K] Divider Conductance [W/m2-K] NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW NONRESWINDOW_U_0.3856_SHGC_0.4   23.26 0.00 0.00 23.26 23.26 2.191 0.401 0.402             No RETAIL_1_FLR_1_WALL_SOUTH 180.00 90.00 S
CAFE_FLR_1_WALL_SOUTH_WINDOW NONRESWINDOW_U_0.3856_SHGC_0.4   65.50 0.00 0.00 65.50 65.50 2.191 0.401 0.402             No CAFE_FLR_1_WALL_SOUTH 180.00 90.00 S
LOBBY_FLR_1_WALL_SOUTH_WINDOW NONRESWINDOW_U_0.3856_SHGC_0.4   85.08 0.00 0.00 85.08 85.08 2.191 0.401 0.402             No LOBBY_FLR_1_WALL_1_SOUTH 180.00 90.00 S
ROOM_1_FLR_3_WALL_SOUTH_WINDOW RESWINDOW_U_0.3856_SHGC_0.4   4.60 0.00 0.00 4.60 18.40 2.191 0.401 0.402             No ROOM_1_FLR_3_WALL_SOUTH 180.00 90.00 S
ROOM_1_FLR_3_WALL_WEST_WINDOW RESWINDOW_U_0.3856_SHGC_0.4   8.58 0.00 0.00 8.58 34.34 2.191 0.401 0.402             No ROOM_1_FLR_3_WALL_WEST 270.00 90.00 W
ROOM_2_FLR_3_WALL_NORTH_WINDOW RESWINDOW_U_0.3856_SHGC_0.4   4.60 0.00 0.00 4.60 18.40 2.191 0.401 0.402             No ROOM_2_FLR_3_WALL_NORTH 0.00 90.00 N
ROOM_2_FLR_3_WALL_WEST_WINDOW RESWINDOW_U_0.3856_SHGC_0.4   8.58 0.00 0.00 8.58 34.34 2.191 0.401 0.402             No ROOM_2_FLR_3_WALL_WEST 270.00 90.00 W
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW RESWINDOW_U_0.3856_SHGC_0.4   3.68 0.00 0.00 3.68 279.56 2.191 0.401 0.402             No ROOM_3_MULT19_FLR_3_WALL_SOUTH 180.00 90.00 S
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW RESWINDOW_U_0.3856_SHGC_0.4   3.68 0.00 0.00 3.68 279.65 2.191 0.401 0.402             No ROOM_4_MULT19_FLR_3_WALL_NORTH 0.00 90.00 N
ROOM_5_FLR_3_WALL_EAST_WINDOW RESWINDOW_U_0.3856_SHGC_0.4   8.58 0.00 0.00 8.58 34.34 2.191 0.401 0.402             No ROOM_5_FLR_3_WALL_EAST 90.00 90.00 E
ROOM_5_FLR_3_WALL_SOUTH_WINDOW RESWINDOW_U_0.3856_SHGC_0.4   4.60 0.00 0.00 4.60 18.40 2.191 0.401 0.402             No ROOM_5_FLR_3_WALL_SOUTH 180.00 90.00 S
ROOM_6_FLR_3_WALL_NORTH_WINDOW RESWINDOW_U_0.3856_SHGC_0.4   4.60 0.00 0.00 4.60 18.40 2.191 0.401 0.402             No ROOM_6_FLR_3_WALL_NORTH 0.00 90.00 N
ROOM_6_FLR_3_WALL_EAST_WINDOW RESWINDOW_U_0.3856_SHGC_0.4   8.58 0.00 0.00 8.58 34.34 2.191 0.401 0.402             No ROOM_6_FLR_3_WALL_EAST 90.00 90.00 E
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW NONRESWINDOW_U_0.3856_SHGC_0.4   5.82 0.00 0.00 5.82 23.30 2.191 0.401 0.402             No CORRIDOR_FLR_3_WALL_1_NORTH 0.00 90.00 N
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW NONRESWINDOW_U_0.3856_SHGC_0.4   2.15 0.00 0.00 2.15 8.59 2.191 0.401 0.402             No CORRIDOR_FLR_3_WALL_2_NORTH 0.00 90.00 N
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW NONRESWINDOW_U_0.3856_SHGC_0.4   2.15 0.00 0.00 2.15 8.58 2.191 0.401 0.402             No CORRIDOR_FLR_3_WALL_1_SOUTH 180.00 90.00 S
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW NONRESWINDOW_U_0.3856_SHGC_0.4   5.82 0.00 0.00 5.82 23.30 2.191 0.401 0.402             No CORRIDOR_FLR_3_WALL_2_SOUTH 180.00 90.00 S
ROOM_1_FLR_6_WALL_SOUTH_WINDOW RESWINDOW_U_0.3856_SHGC_0.4   4.60 0.00 0.00 4.60 4.60 2.191 0.401 0.402             No ROOM_1_FLR_6_WALL_SOUTH 180.00 90.00 S
ROOM_1_FLR_6_WALL_WEST_WINDOW RESWINDOW_U_0.3856_SHGC_0.4   8.58 0.00 0.00 8.58 8.58 2.191 0.401 0.402             No ROOM_1_FLR_6_WALL_WEST 270.00 90.00 W
ROOM_2_FLR_6_WALL_NORTH_WINDOW RESWINDOW_U_0.3856_SHGC_0.4   4.60 0.00 0.00 4.60 4.60 2.191 0.401 0.402             No ROOM_2_FLR_6_WALL_NORTH 0.00 90.00 N
ROOM_2_FLR_6_WALL_WEST_WINDOW RESWINDOW_U_0.3856_SHGC_0.4   8.58 0.00 0.00 8.58 8.58 2.191 0.401 0.402             No ROOM_2_FLR_6_WALL_WEST 270.00 90.00 W
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW RESWINDOW_U_0.3856_SHGC_0.4   6.74 0.00 0.00 6.74 60.70 2.191 0.401 0.402             No ROOM_3_MULT9_FLR_6_WALL_SOUTH 180.00 90.00 S
BANQUET_FLR_6_WALL_NORTH_WINDOW NONRESWINDOW_U_0.3856_SHGC_0.4   32.19 0.00 0.00 32.19 32.19 2.191 0.401 0.402             No BANQUET_FLR_6_WALL_NORTH 0.00 90.00 N
DINING_FLR_6_WALL_NORTH_WINDOW NONRESWINDOW_U_0.3856_SHGC_0.4   32.19 0.00 0.00 32.19 32.19 2.191 0.401 0.402             No DINING_FLR_6_WALL_NORTH 0.00 90.00 N
KITCHEN_FLR_6_WALL_NORTH_WINDOW NONRESWINDOW_U_0.3856_SHGC_0.4   4.60 0.00 0.00 4.60 4.60 2.191 0.401 0.402             No KITCHEN_FLR_6_WALL_NORTH 0.00 90.00 N
KITCHEN_FLR_6_WALL_EAST_WINDOW NONRESWINDOW_U_0.3856_SHGC_0.4   17.17 0.00 0.00 17.17 17.17 2.191 0.401 0.402             No KITCHEN_FLR_6_WALL_EAST 90.00 90.00 E
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW NONRESWINDOW_U_0.3856_SHGC_0.4   4.60 0.00 0.00 4.60 4.60 2.191 0.401 0.402             No KITCHEN_FLR_6_WALL_1_SOUTH 180.00 90.00 S
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW NONRESWINDOW_U_0.3856_SHGC_0.4   5.82 0.00 0.00 5.82 5.82 2.191 0.401 0.402             No CORRIDOR_FLR_6_WALL_1_NORTH 0.00 90.00 N
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW NONRESWINDOW_U_0.3856_SHGC_0.4   5.21 0.00 0.00 5.21 5.21 2.191 0.401 0.402             No CORRIDOR_FLR_6_WALL_2_NORTH 0.00 90.00 N
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW NONRESWINDOW_U_0.3856_SHGC_0.4   17.17 0.00 0.00 17.17 17.17 2.191 0.401 0.402             No CORRIDOR_FLR_6_WALL_2_SOUTH 180.00 90.00 S
Total or Average             1213.79 2.191 0.401 0.402                      
North Total or Average             432.95 2.191 0.401 0.402                      
Non-North Total or Average             780.84 2.191 0.401 0.402                      


Exterior Fenestration Shaded State

Frame and Divider Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance
None                


Interior Fenestration

Construction Area of One Opening [m2] Area of Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance
Total or Average     0.00 - - -


Exterior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
RETAIL_2_FLR_1_WALL_WEST_DOOR SWINGING DOOR_CON 1.598 2.101 1.95 RETAIL_2_FLR_1_WALL_WEST
STORAGE_FLR_1_WALL_NORTH_ROLLDOOR OVERHEAD DOOR_CON 1.016 1.198 7.43 STORAGE_FLR_1_WALL_NORTH
LAUNDRY_FLR_1_WALL_EAST_DOOR SWINGING DOOR_CON 1.598 2.101 1.95 LAUNDRY_FLR_1_WALL_EAST
CAFE_FLR_1_WALL_EAST_DOOR SWINGING DOOR_CON 1.598 2.101 1.95 CAFE_FLR_1_WALL_EAST
LOBBY_FLR_1_WALL_1_NORTH_DOOR1 SWINGING DOOR_CON 1.598 2.101 1.95 LOBBY_FLR_1_WALL_1_NORTH
LOBBY_FLR_1_WALL_1_NORTH_DOOR2 SWINGING DOOR_CON 1.598 2.101 1.95 LOBBY_FLR_1_WALL_1_NORTH


Interior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
None          



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2023-10-16 08:58:31

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
CAFE_FLR_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
LOBBY_FLR_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
ROOM_1_FLR_3_WALL_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
ROOM_1_FLR_3_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
ROOM_2_FLR_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_3_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ROOM_5_FLR_3_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
ROOM_5_FLR_3_WALL_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
ROOM_6_FLR_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ROOM_6_FLR_3_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
ROOM_1_FLR_6_WALL_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
ROOM_1_FLR_6_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
ROOM_2_FLR_6_WALL_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_6_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
BANQUET_FLR_6_WALL_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
DINING_FLR_6_WALL_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
KITCHEN_FLR_6_WALL_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
KITCHEN_FLR_6_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00


Window Control

Name Type Shaded Construction Control Glare Control
None          



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2023-10-16 08:58:31

Interior Lighting

Zone Name Space Name Space Type Lighting Power Density [W/m2] Space Area [m2] Total Power [W] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [GJ]
BASEMENT_LIGHTS BASEMENT BASEMENT GENERAL 8.7495 1978.83 17313.73 LightsWired LTG_SCH_BASEMENT 50.91 168.00 50.86 0.0000 Y 165.29
RETAIL_1_FLR_1_LIGHTS RETAIL_1_FLR_1 RETAIL_1_FLR_1 GENERAL 13.0124 67.07 872.76 LightsWired LTG_SCH_RETAIL 51.36 168.00 51.30 0.0000 Y 8.40
RETAIL_2_FLR_1_LIGHTS RETAIL_2_FLR_1 RETAIL_2_FLR_1 GENERAL 13.0124 77.67 1010.66 LightsWired LTG_SCH_RETAIL 51.36 168.00 51.30 0.0000 Y 9.73
MECH_FLR_1_LIGHTS MECH_FLR_1 MECH_FLR_1 GENERAL 10.0642 164.24 1652.98 LightsWired LTG_SCH_MECHANIC 58.69 168.00 58.63 0.0000 Y 18.19
STORAGE_FLR_1_LIGHTS STORAGE_FLR_1 STORAGE_FLR_1 GENERAL 7.3195 94.76 693.59 LightsWired LTG_SCH_STORAGE 25.68 168.00 25.65 0.0000 Y 3.34
LAUNDRY_FLR_1_LIGHTS LAUNDRY_FLR_1 LAUNDRY_FLR_1 GENERAL 5.4896 78.04 428.40 LightsWired LTG_SCH_LAUNDRY 51.36 168.00 51.30 0.0000 Y 4.13
CAFE_FLR_1_LIGHTS CAFE_FLR_1 CAFE_FLR_1 GENERAL 12.8090 188.86 2419.14 LightsWired LTG_SCH_DINING 58.69 168.00 58.63 0.0000 Y 26.62
LOBBY_FLR_1_LIGHTS LOBBY_FLR_1 LOBBY_FLR_1 GENERAL 10.0642 1308.19 13165.91 LightsWired LTG_SCH_LOBBY 58.69 168.00 58.63 0.0000 Y 144.89
ROOM_1_FLR_3_LIGHTS ROOM_1_FLR_3 ROOM_1_FLR_3 GENERAL 10.0642 156.09 1570.91 LightsWired LTG_SCH_GUESTROOM 69.03 168.00 69.21 0.0000 Y 20.41
ROOM_2_FLR_3_LIGHTS ROOM_2_FLR_3 ROOM_2_FLR_3 GENERAL 10.0642 156.07 1570.72 LightsWired LTG_SCH_GUESTROOM 69.03 168.00 69.21 0.0000 Y 20.41
ROOM_3_MULT19_FLR_3_LIGHTS ROOM_3_MULT19_FLR_3 ROOM_3_MULT19_FLR_3 GENERAL 10.0642 1863.81 18757.86 LightsWired LTG_SCH_GUESTROOM 69.03 168.00 69.21 0.0000 Y 243.70
ROOM_4_MULT19_FLR_3_LIGHTS ROOM_4_MULT19_FLR_3 ROOM_4_MULT19_FLR_3 GENERAL 10.0642 1864.32 18762.99 LightsWired LTG_SCH_GUESTROOM 69.03 168.00 69.21 0.0000 Y 243.77
ROOM_5_FLR_3_LIGHTS ROOM_5_FLR_3 ROOM_5_FLR_3 GENERAL 10.0642 156.09 1570.91 LightsWired LTG_SCH_GUESTROOM 69.03 168.00 69.21 0.0000 Y 20.41
ROOM_6_FLR_3_LIGHTS ROOM_6_FLR_3 ROOM_6_FLR_3 GENERAL 10.0642 156.07 1570.72 LightsWired LTG_SCH_GUESTROOM 69.03 168.00 69.21 0.0000 Y 20.41
CORRIDOR_FLR_3_LIGHTS CORRIDOR_FLR_3 CORRIDOR_FLR_3 GENERAL 3.6597 1557.62 5700.46 LightsWired LTG_SCH_CORRIDOR 58.69 168.00 58.63 0.0000 Y 62.73
ROOM_1_FLR_6_LIGHTS ROOM_1_FLR_6 ROOM_1_FLR_6 GENERAL 10.0642 39.02 392.73 LightsWired LTG_SCH_GUESTROOM 69.03 168.00 69.21 0.0000 Y 5.10
ROOM_2_FLR_6_LIGHTS ROOM_2_FLR_6 ROOM_2_FLR_6 GENERAL 10.0642 39.02 392.68 LightsWired LTG_SCH_GUESTROOM 69.03 168.00 69.21 0.0000 Y 5.10
ROOM_3_MULT9_FLR_6_LIGHTS ROOM_3_MULT9_FLR_6 ROOM_3_MULT9_FLR_6 GENERAL 10.0642 220.77 2221.93 LightsWired LTG_SCH_GUESTROOM 69.03 168.00 69.21 0.0000 Y 28.87
BANQUET_FLR_6_LIGHTS BANQUET_FLR_6 BANQUET_FLR_6 GENERAL 12.8090 331.66 4248.21 LightsWired LTG_SCH_DINING 58.69 168.00 58.63 0.0000 Y 46.75
DINING_FLR_6_LIGHTS DINING_FLR_6 DINING_FLR_6 GENERAL 12.8090 331.66 4248.21 LightsWired LTG_SCH_DINING 58.69 168.00 58.63 0.0000 Y 46.75
KITCHEN_FLR_6_LIGHTS KITCHEN_FLR_6 KITCHEN_FLR_6 GENERAL 10.9792 103.30 1134.20 LightsWired LTG_SCH_KITCHEN 58.69 168.00 58.63 0.0000 Y 12.48
CORRIDOR_FLR_6_LIGHTS CORRIDOR_FLR_6 CORRIDOR_FLR_6 GENERAL 3.6597 412.12 1508.26 LightsWired LTG_SCH_CORRIDOR 58.69 168.00 58.63 0.0000 Y 16.60
Interior Lighting Total       8.9207 11345.29 101207.97               559.10


Daylighting

Zone Control Name Daylighting Method Control Type Fraction Controlled Lighting Installed in Zone [W] Lighting Controlled [W]
None              


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [GJ]
EXTERIOR FACADE LIGHTING 16690.39 AstronomicalClock -   83.54 83.54 261.73
Exterior Lighting Total 16690.39           261.73



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2023-10-16 08:58:31

Central Plant

Type Reference Capacity [W] Reference Efficiency [W/W] Rated Capacity [W] Rated Efficiency [W/W] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
HEATSYS1 BOILER Boiler:HotWater 449889.21 0.80        
COOLSYS1 CHILLER1 Chiller:Electric:EIR 723021.47 2.80 723148.56 2.80 3.72 12.68


Cooling Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Sensible Capacity [W] Nominal Latent Capacity [W] Nominal Sensible Heat Ratio Nominal Efficiency [W/W] Nominal Coil UA Value [W/C] Nominal Coil Surface Area [m2]
ROOM_1_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 14904.39 21584.43 17086.44 4498.00 0.79 - 2416.78 24.51
ROOM_2_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 13348.44 19319.28 15287.11 4032.16 0.79 - 2162.93 21.94
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 106772.85 155426.92 123471.76 31955.16 0.79 - 17415.74 176.64
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 72071.16 102646.17 80387.06 22259.10 0.78 - 11464.82 116.28
ROOM_5_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 13553.81 19618.16 15524.48 4093.68 0.79 - 2196.43 22.28
ROOM_6_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 12238.77 17704.01 14004.14 3699.87 0.79 - 1981.92 20.10
ROOM_1_FLR_6 FAN COIL COOLING COIL Coil:Cooling:Water 3988.37 5777.92 4574.90 1203.02 0.79 - 646.98 6.56
ROOM_2_FLR_6 FAN COIL COOLING COIL Coil:Cooling:Water 3547.63 5136.26 4065.18 1071.08 0.79 - 575.07 5.83
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Coil:Cooling:Water 22293.24 32192.73 25435.98 6756.75 0.79 - 3602.88 36.54
VAV WITH REHEAT COOLING COIL Coil:Cooling:Water 423570.84 530774.70 378834.66 151940.04 0.71 - 65136.51 660.65
FLR_3_DOAS COOLING COIL Coil:Cooling:Water 36112.10 45302.65 32936.56 12366.09 0.73 - 5220.86 52.95
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [W] Standard Rated Net COP [W/W] EER [Btu/W-h] SEER User [Btu/W-h] SEER Standard [Btu/W-h] IEER [Btu/W-h]
None              


DX Cooling Coil ASHRAE 127 Standard Ratings Report

DX Cooling Coil Type Rated Net Cooling Capacity Test A [W] Rated Electric Power Test A [W] Rated Net Cooling Capacity Test B [W] Rated Electric Power Test B [W] Rated Net Cooling Capacity Test C [W] Rated Electric Power Test C [W] Rated Net Cooling Capacity Test D [W] Rated Electric Power Test D [W]
None                  


DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [W] Low Temperature Heating (net) Rating Capacity [W] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Efficiency [W/W]
BASEMENT VAV BOX REHEAT COIL Coil:Heating:Water 14327.12 14400.77 -
RETAIL_1_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 4825.41 4848.88 -
RETAIL_2_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 1993.71 2003.71 -
MECH_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 2551.24 2563.47 -
STORAGE_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 1434.23 1440.98 -
LAUNDRY_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 18849.13 18946.06 -
CAFE_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 15718.65 15797.50 -
LOBBY_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 40686.71 40891.79 -
ROOM_1_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 5188.67 5588.77 -
ROOM_2_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 5194.32 5594.86 -
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 29731.12 32023.54 -
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 29853.37 32155.20 -
ROOM_5_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 5176.67 5575.85 -
ROOM_6_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 5182.33 5581.95 -
CORRIDOR_FLR_3 VAV BOX REHEAT COIL Coil:Heating:Water 14547.38 14617.01 -
ROOM_1_FLR_6 FAN COIL HEATING COIL Coil:Heating:Water 1653.18 1780.60 -
ROOM_2_FLR_6 FAN COIL HEATING COIL Coil:Heating:Water 1654.61 1782.13 -
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL Coil:Heating:Water 7974.44 8589.02 -
BANQUET_FLR_6 VAV BOX REHEAT COIL Coil:Heating:Water 17055.32 17141.36 -
DINING_FLR_6 VAV BOX REHEAT COIL Coil:Heating:Water 17714.73 17804.16 -
KITCHEN_FLR_6 VAV BOX REHEAT COIL Coil:Heating:Water 12886.51 12952.89 -
CORRIDOR_FLR_6 VAV BOX REHEAT COIL Coil:Heating:Water 10065.78 10113.20 -
VAV WITH REHEAT HEATING COIL Coil:Heating:Water 170153.31 129454.91 -
FLR_3_DOAS HEATING COIL Coil:Heating:Water 15471.26 11770.74 -
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

Fans

Type Total Efficiency [W/W] Delta Pressure [pa] Max Air Flow Rate [m3/s] Rated Electricity Rate [W] Rated Power Per Max Air Flow Rate [W-s/m3] Motor Heat In Air Fraction Fan Energy Index End Use Subcategory Design Day Name for Fan Sizing Peak Date/Time for Fan Sizing Peak
LAUNDRY_FLR_1 EXHAUST FAN Fan:ZoneExhaust 0.16 125.00 0.24 184.35 781.25 1.00 1.15 General    
LOBBY_FLR_1 EXHAUST FAN Fan:ZoneExhaust 1.00 0.00 0.00 0.00   1.00 0.00 General    
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.16 270.90 1.24 2107.83 1693.12 1.00 0.48 General WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 16:40:00
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.16 270.90 1.11 1884.60 1693.12 1.00 0.49 General WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 17:00:00
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.16 270.90 9.05 15321.65 1693.12 1.00 0.39 General WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 13:30:00
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.16 270.90 5.75 9741.33 1693.12 1.00 0.40 General WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.16 270.90 1.13 1914.04 1693.12 1.00 0.49 General WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 10:00:00
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.16 270.90 1.02 1725.45 1693.12 1.00 0.50 General WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 09:10:00
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.16 270.90 0.33 564.59 1693.12 1.00 0.68 General WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 16:30:00
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.16 270.90 0.30 501.34 1693.12 1.00 0.72 General WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 17:00:00
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.16 270.90 1.85 3128.09 1693.12 1.00 0.45 General WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 13:40:00
BANQUET_FLR_6 EXHAUST FAN Fan:ZoneExhaust 1.00 0.00 0.00 0.00   1.00 0.00 General    
DINING_FLR_6 EXHAUST FAN Fan:ZoneExhaust 1.00 0.00 0.00 0.00   1.00 0.00 General    
KITCHEN_FLR_6 EXHAUST FAN Fan:ZoneExhaust 0.16 125.00 1.89 1474.84 781.25 1.00 0.62 General    
VAV WITH REHEAT FAN Fan:VariableVolume 0.62 1389.42 22.56 50549.79 2240.64 1.00 1.11 General WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 19:20:00
FLR_3_DOAS FAN Fan:ConstantVolume 0.58 622.50 2.05 2194.93 1070.05 1.00 1.30 General WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:20:00


Pumps

Type Control Head [pa] Water Flow [m3/s] Electricity Rate [W] Power Per Water Flow Rate [W-s/m3] Motor Efficiency [W/W] End Use Subcategory
COOLSYS1 PUMP SECONDARY Pump:VariableSpeed Intermittent 133527.72 0.025802 5316.91 206062.94 0.90 General
HEATSYS1 PUMP Pump:VariableSpeed Intermittent 180705.70 0.003936 1185.30 301156.09 0.90 General
COOLSYS1 PUMP Pump:ConstantSpeed Intermittent 92445.74 0.025802 3681.07 142664.32 0.90 General
SWHSYS1 PUMP Pump:ConstantSpeed Intermittent 29891.00 0.000375 47.91 127739.32 0.30 General


Service Water Heating

Type Storage Volume [m3] Input [W] Thermal Efficiency [W/W] Recovery Efficiency [W/W] Energy Factor
SWH BOOSTER E WATER HEATER WaterHeater:Mixed 0.02 8000.00 1.00 1.24 1.15
SWH LAUNDRY G WATER HEATER WaterHeater:Mixed 1.14 163316.00 0.80 0.58 0.51
SWHSYS1 WATER HEATER WaterHeater:Mixed 2.27 175842.60 0.80 0.26 0.03



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2023-10-16 08:58:31

Zone Sensible Cooling

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
BASEMENT 33765.32 33765.32 17.06 2.480 2.480 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 18:40:00 24.00 24.00 0.00921 23.31 0.00840 0.854 0.00
RETAIL_1_FLR_1 6466.56 6466.56 96.41 0.475 0.475 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 13:30:00 24.00 24.00 0.00887 26.17 0.00841 0.079 0.00
RETAIL_2_FLR_1 3233.46 3233.46 41.63 0.237 0.237 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 15:20:00 24.00 24.00 0.00936 26.22 0.00841 0.092 0.00
MECH_FLR_1 3034.80 3034.80 18.48 0.223 0.223 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 15:10:00 24.00 24.00 0.00869 26.31 0.00841 0.000 0.00
STORAGE_FLR_1 1490.10 1490.10 15.73 0.109 0.109 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 14:50:00 24.00 24.00 0.00879 26.40 0.00841 0.058 0.00
LAUNDRY_FLR_1 44695.52 44695.52 572.73 3.282 3.282 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 14:30:00 24.00 24.00 0.00854 26.40 0.00841 0.000 0.00
CAFE_FLR_1 25469.38 25469.38 134.86 1.872 1.872 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 13:30:00 24.00 23.99 0.00975 26.17 0.00841 0.676 0.00
LOBBY_FLR_1 70309.15 70309.15 53.75 5.165 5.165 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 13:40:00 24.00 23.99 0.00984 26.25 0.00841 1.894 0.00
ROOM_1_FLR_3 12580.64 12580.64 322.40 1.245 1.245 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 16:40:00 21.11 21.11 0.00856 25.37 0.00841 0.062 0.00
ROOM_2_FLR_3 11248.27 11248.27 288.29 1.113 1.113 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 17:00:00 21.11 21.11 0.00856 25.13 0.00841 0.062 0.00
ROOM_3_MULT19_FLR_3 91451.40 91451.40 3729.08 9.049 9.049 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 13:30:00 21.11 21.11 0.00850 26.17 0.00841 0.837 0.00
ROOM_4_MULT19_FLR_3 58139.33 58139.33 2370.08 5.753 5.753 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 21.11 21.11 0.00874 26.40 0.00841 0.837 0.00
ROOM_5_FLR_3 11423.98 11423.98 292.76 1.130 1.130 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 10:00:00 21.11 21.11 0.00856 22.94 0.00840 0.062 0.00
ROOM_6_FLR_3 10298.39 10298.39 263.94 1.019 1.019 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 09:10:00 21.11 21.11 0.00857 21.65 0.00840 0.062 0.00
CORRIDOR_FLR_3 17037.07 17037.07 43.75 1.251 1.251 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 14:10:00 24.00 24.00 0.00961 26.40 0.00841 0.475 0.00
ROOM_1_FLR_6 3369.74 3369.74 86.35 0.333 0.333 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 16:30:00 21.11 21.11 0.00855 25.49 0.00841 0.015 0.00
ROOM_2_FLR_6 2992.28 2992.28 76.69 0.296 0.296 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 17:00:00 21.11 21.11 0.00856 25.13 0.00841 0.015 0.00
ROOM_3_MULT9_FLR_6 18669.63 18669.63 761.08 1.848 1.848 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 13:40:00 21.11 21.11 0.00859 26.25 0.00841 0.099 0.00
BANQUET_FLR_6 29819.49 29819.49 89.91 2.193 2.193 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 14:30:00 24.00 23.99 0.01038 26.40 0.00841 1.188 0.00
DINING_FLR_6 31280.59 31280.59 94.32 2.300 2.300 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 14:20:00 24.00 23.99 0.01029 26.40 0.00841 1.188 0.00
KITCHEN_FLR_6 31445.53 31445.53 304.40 2.315 2.315 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 12:30:00 24.00 23.97 0.01004 25.58 0.00841 0.367 0.00
CORRIDOR_FLR_6 10501.11 10501.11 25.48 0.771 0.771 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 14:00:00 24.00 24.00 0.00897 26.40 0.00841 0.126 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

Zone Sensible Heating

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
BASEMENT 1439.65 1439.65 0.73 0.062 0.854 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.00 21.00 0.00795 -4.30 0.00266 0.854 0.00
RETAIL_1_FLR_1 2359.53 2359.53 35.18 0.102 0.102 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:20:00 21.00 21.00 0.00750 -4.30 0.00266 0.079 0.00
RETAIL_2_FLR_1 760.71 760.71 9.79 0.033 0.092 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.00 21.00 0.00741 -4.30 0.00266 0.092 0.00
MECH_FLR_1 1394.56 1394.56 8.49 0.060 0.060 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.00 21.00 0.00726 -4.30 0.00266 0.000 0.00
STORAGE_FLR_1 866.24 866.24 9.14 0.038 0.058 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.00 21.00 0.00731 -4.30 0.00266 0.058 0.00
LAUNDRY_FLR_1 1815.44 1815.44 23.26 0.079 0.079 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:20:00 21.00 21.00 0.00723 -4.30 0.00266 0.000 0.00
CAFE_FLR_1 5997.44 5997.44 31.76 0.260 0.676 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:20:00 21.00 21.00 0.00756 -4.30 0.00266 0.676 0.00
LOBBY_FLR_1 13866.24 13866.24 10.60 0.601 1.894 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.00 21.00 0.00746 -4.30 0.00266 1.894 0.00
ROOM_1_FLR_3 5188.66 5188.66 132.97 0.226 0.226 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:20:00 21.11 21.11 0.00747 -4.30 0.00266 0.062 0.00
ROOM_2_FLR_3 5194.32 5194.32 133.13 0.226 0.226 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:20:00 21.11 21.11 0.00747 -4.30 0.00266 0.062 0.00
ROOM_3_MULT19_FLR_3 29731.11 29731.11 1212.33 1.296 1.296 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:20:00 21.11 21.11 0.00751 -4.30 0.00266 0.837 0.00
ROOM_4_MULT19_FLR_3 29853.36 29853.36 1216.99 1.301 1.301 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:20:00 21.11 21.11 0.00751 -4.30 0.00266 0.837 0.00
ROOM_5_FLR_3 5176.67 5176.67 132.66 0.226 0.226 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:20:00 21.11 21.11 0.00747 -4.30 0.00266 0.062 0.00
ROOM_6_FLR_3 5182.33 5182.33 132.82 0.226 0.226 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:20:00 21.11 21.11 0.00747 -4.30 0.00266 0.062 0.00
CORRIDOR_FLR_3 8049.47 8049.47 20.67 0.349 0.475 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:20:00 21.00 21.00 0.00758 -4.30 0.00266 0.475 0.00
ROOM_1_FLR_6 1653.18 1653.18 42.37 0.072 0.072 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:20:00 21.11 21.11 0.00758 -4.30 0.00266 0.015 0.00
ROOM_2_FLR_6 1654.61 1654.61 42.41 0.072 0.072 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:20:00 21.11 21.11 0.00758 -4.30 0.00266 0.015 0.00
ROOM_3_MULT9_FLR_6 7974.44 7974.44 325.08 0.347 0.347 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:20:00 21.11 21.11 0.00760 -4.30 0.00266 0.099 0.00
BANQUET_FLR_6 5666.38 5666.38 17.09 0.245 1.188 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:20:00 21.00 21.00 0.00769 -4.30 0.00266 1.188 0.00
DINING_FLR_6 5767.95 5767.95 17.39 0.250 1.188 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 19:20:00 21.00 21.00 0.00770 -4.30 0.00266 1.188 0.00
KITCHEN_FLR_6 937.60 937.60 9.08 0.041 0.367 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 23:30:00 21.00 21.00 0.00467 -4.30 0.00266 0.367 0.00
CORRIDOR_FLR_6 6059.60 6059.60 14.70 0.263 0.263 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 19:20:00 21.00 21.00 0.00774 -4.30 0.00266 0.126 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

System Design Air Flow Rates

Calculated cooling [m3/s] User cooling [m3/s] Calculated heating [m3/s] User heating [m3/s] Adjusted cooling [m3/s] Adjusted heating [m3/s] Adjusted main [m3/s] Calculated Heating Air Flow Ratio [] User Heating Air Flow Ratio []
VAV WITH REHEAT 22.56 22.56 7.30 7.30 22.5604 22.5604 22.5604 1.0000 0.3000
FLR_3_DOAS 20.42 2.05 3.99 2.05 2.0513 2.0513 2.0513 1.0000 0.3000


Plant Loop Coincident Design Fluid Flow Rate Adjustments

Previous Design Volume Flow Rate [m3/s] Algorithm Volume Flow Rate [m3/s] Coincident Design Volume Flow Rate [m3/s] Coincident Size Adjusted Peak Sizing Period Name Peak Day into Period {TIMESTAMP}[day] Peak Hour Of Day {TIMESTAMP}[hr] Peak Step Start Minute {TIMESTAMP}[min]
None                


Coil Sizing Summary

Coil Type HVAC Type HVAC Name Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Flow Percentage at Ideal Loads Peak [%] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W]
BASEMENT VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT BASEMENT VAV BOX 14327.117 14327.117 2.467248 0.00012534 300.506 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 24:00:00 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 24:00:00 14327.12 14327.12 2.467248 16.70 13.09 0.00800000 40.00 21.06 0.00800000 -4.30 0.00265759 -4.30 0.0000 21.00 0.00795178 50.8633 1439.65 0.00 14407.47 14407.47
RETAIL_1_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT RETAIL_1_FLR_1 VAV BOX 4825.409 4825.409 0.472551 0.00004221 105.886 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:20:00 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:20:00 4825.41 4825.41 0.472551 16.70 13.09 0.00800000 40.00 21.06 0.00800000 -4.30 0.00265759 -4.30 0.0000 21.00 0.00749616 47.9858 2359.53 0.00 4851.75 4851.75
RETAIL_2_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT RETAIL_2_FLR_1 VAV BOX 1993.711 1993.711 0.236295 0.00001744 42.950 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 24:00:00 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 24:00:00 1993.71 1993.71 0.236295 16.70 13.09 0.00800000 40.00 21.06 0.00800000 -4.30 0.00265759 -4.30 0.0000 21.00 0.00740777 47.4250 760.71 0.00 2004.79 2004.79
MECH_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT MECH_FLR_1 VAV BOX 2551.238 2551.238 0.221730 0.00002232 56.760 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 24:00:00 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 24:00:00 2551.24 2551.24 0.221730 16.70 13.09 0.00800000 40.00 21.06 0.00800000 -4.30 0.00265759 -4.30 0.0000 21.00 0.00726019 46.4911 1394.56 0.00 2565.09 2565.09
STORAGE_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT STORAGE_FLR_1 VAV BOX 1434.232 1434.232 0.108872 0.00001255 32.492 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 24:00:00 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 24:00:00 1434.23 1434.23 0.108872 16.70 13.09 0.00800000 40.00 21.06 0.00800000 -4.30 0.00265759 -4.30 0.0000 21.00 0.00730601 46.7812 866.24 0.00 1441.97 1441.97
LAUNDRY_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 18849.126 18849.126 3.265876 0.00016490 395.214 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:20:00 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:20:00 18849.13 18849.13 3.265876 16.70 13.09 0.00800000 40.00 21.06 0.00800000 -4.30 0.00265759 -4.30 0.0000 21.00 0.00722922 46.2967 1815.44 0.00 18954.86 18954.86
CAFE_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CAFE_FLR_1 VAV BOX 15718.649 15718.649 1.862671 0.00013751 338.625 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:20:00 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:20:00 15718.65 15718.65 1.862671 16.70 13.09 0.00800000 40.00 21.06 0.00800000 -4.30 0.00265759 -4.30 0.0000 21.00 0.00755637 48.3662 5997.44 0.00 15806.04 15806.04
LOBBY_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 40686.711 40686.711 5.139451 0.00035595 871.809 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 24:00:00 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 24:00:00 40686.71 40686.71 5.139451 16.70 13.09 0.00800000 40.00 21.06 0.00800000 -4.30 0.00265759 -4.30 0.0000 21.00 0.00746228 47.7699 13866.24 0.00 40913.28 40913.28
ROOM_1_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_3 FAN COIL 14904.394 -999.000 1.244936 0.00053234 -999.000 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 16:40:00 unknown 8/21 16:40:00 14904.39 14714.54 1.244936 22.50 15.79 0.00855731 12.80 12.00 0.00850000 25.37 0.00840546 16.68 0.0000 21.11 0.00855731 54.3135 12580.64 0.00 15056.55 14610.62
ROOM_1_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_3 FAN COIL 5188.668 5188.668 0.226101 0.00004539 148.279 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:20:00 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:20:00 5188.67 5188.67 0.226101 21.11 14.31 0.00747362 40.00 21.06 0.00800000 -4.30 0.00265759 -4.30 0.0000 21.11 0.00747362 47.5184 5188.66 0.00 5593.49 5593.49
ROOM_2_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_3 FAN COIL 13348.439 -999.000 1.113091 0.00047677 -999.000 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 17:00:00 unknown 8/21 17:00:00 13348.44 13158.86 1.113091 22.50 15.80 0.00856399 12.80 12.00 0.00850000 25.13 0.00840508 16.59 0.0000 21.11 0.00856399 54.3553 11248.27 0.00 13484.59 13066.75
ROOM_2_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_3 FAN COIL 5194.324 5194.324 0.226348 0.00004544 148.441 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:20:00 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:20:00 5194.32 5194.32 0.226348 21.11 14.31 0.00747417 40.00 21.06 0.00800000 -4.30 0.00265759 -4.30 0.0000 21.11 0.00747417 47.5219 5194.32 0.00 5599.59 5599.59
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT19_FLR_3 FAN COIL 106772.845 -999.000 9.049329 0.00381361 -999.000 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 13:30:00 unknown 8/21 13:30:00 106772.85 106772.84 9.049329 22.50 15.74 0.00849881 12.80 12.00 0.00849881 26.17 0.00840672 16.96 0.0000 21.11 0.00849881 53.9460 91451.40 0.00 107848.32 105958.05
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT19_FLR_3 FAN COIL 29731.119 29731.119 1.295593 0.00026010 849.629 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:20:00 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:20:00 29731.12 29731.12 1.295593 21.11 14.34 0.00750938 40.00 21.06 0.00800000 -4.30 0.00265759 -4.30 0.0000 21.11 0.00750938 47.7417 29731.11 0.00 32051.00 32051.00
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_4_MULT19_FLR_3 FAN COIL 72071.162 -999.000 5.753464 0.00257417 -999.000 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 unknown 8/21 15:00:00 72071.16 68366.53 5.753464 22.50 15.95 0.00874067 12.80 12.00 0.00850000 26.40 0.00840708 17.04 0.0000 21.11 0.00874067 55.4621 58139.33 0.00 72789.83 67995.52
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_4_MULT19_FLR_3 FAN COIL 29853.370 29853.370 1.300920 0.00026117 853.122 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:20:00 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:20:00 29853.37 29853.37 1.300920 21.11 14.34 0.00751109 40.00 21.06 0.00800000 -4.30 0.00265759 -4.30 0.0000 21.11 0.00751109 47.7525 29853.36 0.00 32182.79 32182.79
ROOM_5_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_5_FLR_3 FAN COIL 13553.813 -999.000 1.130478 0.00048410 -999.000 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 10:00:00 unknown 8/21 10:00:00 13553.81 13364.03 1.130478 22.50 15.80 0.00856308 12.80 12.00 0.00850000 22.94 0.00840167 15.82 0.0000 21.11 0.00856308 54.3496 11423.98 0.00 13692.08 13270.37
ROOM_5_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_5_FLR_3 FAN COIL 5176.674 5176.674 0.225578 0.00004529 147.937 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:20:00 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:20:00 5176.67 5176.67 0.225578 21.11 14.30 0.00747252 40.00 21.06 0.00800000 -4.30 0.00265759 -4.30 0.0000 21.11 0.00747252 47.5115 5176.67 0.00 5580.56 5580.56
ROOM_6_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_6_FLR_3 FAN COIL 12238.768 -999.000 1.019094 0.00043713 -999.000 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 09:10:00 unknown 8/21 09:10:00 12238.77 12049.72 1.019094 22.50 15.81 0.00856969 12.80 12.00 0.00850000 21.65 0.00839969 15.35 0.0000 21.11 0.00856969 54.3910 10298.39 0.00 12363.51 11966.00
ROOM_6_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_6_FLR_3 FAN COIL 5182.333 5182.333 0.225825 0.00004534 148.098 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:20:00 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:20:00 5182.33 5182.33 0.225825 21.11 14.31 0.00747307 40.00 21.06 0.00800000 -4.30 0.00265759 -4.30 0.0000 21.11 0.00747307 47.5150 5182.33 0.00 5586.66 5586.66
CORRIDOR_FLR_3 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORRIDOR_FLR_3 VAV BOX 14547.385 14547.385 1.244879 0.00012727 324.277 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:20:00 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:20:00 14547.38 14547.38 1.244879 16.70 13.09 0.00800000 40.00 21.06 0.00800000 -4.30 0.00265759 -4.30 0.0000 21.00 0.00757832 48.5036 8049.47 0.00 14626.31 14626.31
ROOM_1_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_6 FAN COIL 3988.372 -999.000 0.333458 0.00014245 -999.000 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 16:30:00 unknown 8/21 16:30:00 3988.37 3940.86 0.333458 22.50 15.79 0.00855356 12.80 12.00 0.00850000 25.49 0.00840565 16.72 0.0000 21.11 0.00855356 54.2900 3369.74 0.00 4029.11 3912.88
ROOM_1_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_6 FAN COIL 1653.183 1653.183 0.072039 0.00001446 47.241 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:20:00 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:20:00 1653.18 1653.18 0.072039 21.11 14.40 0.00757795 40.00 21.06 0.00800000 -4.30 0.00265759 -4.30 0.0000 21.11 0.00757795 48.1737 1653.18 0.00 1782.17 1782.17
ROOM_2_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_6 FAN COIL 3547.634 -999.000 0.296105 0.00012671 -999.000 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 17:00:00 unknown 8/21 17:00:00 3547.63 3500.14 0.296105 22.50 15.80 0.00856028 12.80 12.00 0.00850000 25.13 0.00840508 16.59 0.0000 21.11 0.00856028 54.3321 2992.28 0.00 3583.84 3475.51
ROOM_2_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_6 FAN COIL 1654.608 1654.608 0.072101 0.00001448 47.282 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:20:00 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:20:00 1654.61 1654.61 0.072101 21.11 14.40 0.00757831 40.00 21.06 0.00800000 -4.30 0.00265759 -4.30 0.0000 21.11 0.00757831 48.1760 1654.61 0.00 1783.70 1783.70
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT9_FLR_6 FAN COIL 22293.238 -999.000 1.847525 0.00079625 -999.000 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 13:40:00 unknown 8/21 13:40:00 22293.24 21857.12 1.847525 22.50 15.82 0.00858862 12.80 12.00 0.00850000 26.25 0.00840684 16.99 0.0000 21.11 0.00858862 54.5102 18669.63 0.00 22519.90 21709.08
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT9_FLR_6 FAN COIL 7974.444 7974.444 0.347497 0.00006976 227.874 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:20:00 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:20:00 7974.44 7974.44 0.347497 21.11 14.42 0.00759566 40.00 21.06 0.00800000 -4.30 0.00265759 -4.30 0.0000 21.11 0.00759566 48.2845 7974.44 0.00 8596.64 8596.64
BANQUET_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 17055.319 17055.319 2.181540 0.00014921 365.082 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:20:00 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:20:00 17055.32 17055.32 2.181540 16.70 13.09 0.00800000 40.00 21.06 0.00800000 -4.30 0.00265759 -4.30 0.0000 21.00 0.00769064 49.2142 5666.38 0.00 17150.33 17150.33
DINING_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 17714.730 17714.730 2.288398 0.00015498 378.898 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 19:20:00 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 19:20:00 17714.73 17714.73 2.288398 16.70 13.09 0.00800000 40.00 21.06 0.00800000 -4.30 0.00265759 -4.30 0.0000 21.00 0.00769576 49.2467 5767.95 0.00 17813.43 17813.43
KITCHEN_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 12886.515 12886.515 2.303631 0.00011274 269.716 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 23:30:00 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 23:30:00 12886.51 12886.51 2.303631 16.70 13.09 0.00800000 40.00 21.06 0.00800000 -4.30 0.00265759 -4.30 0.0000 21.00 0.00467342 30.0577 937.60 0.00 12958.85 12958.85
CORRIDOR_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORRIDOR_FLR_6 VAV BOX 10065.776 10065.776 0.767295 0.00008806 227.900 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 19:20:00 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 19:20:00 10065.78 10065.78 0.767295 16.70 13.09 0.00800000 40.00 21.06 0.00800000 -4.30 0.00265759 -4.30 0.0000 21.00 0.00774384 49.5503 6059.60 0.00 10120.06 10120.06
VAV WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoopHVAC VAV WITH REHEAT 423570.841 -999.000 22.560437 0.01512897 -999.000 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 14:00:00 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 13:50:00 423570.84 423570.84 22.560437 26.40 17.04 0.00840708 10.96 10.96 0.00840708 26.40 0.00840708 17.04 99.9798 23.99 0.00961050 51.1177 306846.22 0.00 427330.34 406605.80
VAV WITH REHEAT HEATING COIL Coil:Heating:Water AirLoopHVAC VAV WITH REHEAT 170153.310 170153.310 6.768131 0.00148858 2903.295 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 19:20:00 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 19:20:00 170153.31 170153.31 6.768131 -4.30 -4.30 0.00265759 16.70 13.09 0.00800000 -4.30 0.00265759 -4.30 333.2660 21.00 0.00755857 48.3707 54412.52 0.00 156576.45 156576.45
FLR_3_DOAS COOLING COIL Coil:Cooling:Water AirLoopHVAC FLR_3_DOAS 36112.103 -999.000 2.051317 0.00128984 -999.000 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 14:30:00 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 14:30:00 36112.10 36112.10 2.051317 26.40 17.04 0.00840708 11.92 11.55 0.00840708 26.40 0.00840708 17.04 99.9965 21.11 0.00859361 54.5404 206305.12 0.00 36425.73 35509.87
FLR_3_DOAS HEATING COIL Coil:Heating:Water AirLoopHVAC FLR_3_DOAS 15471.261 15471.261 0.615395 0.00013535 263.983 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:20:00 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:20:00 15471.26 15471.26 0.615395 -4.30 -4.30 0.00265759 16.70 13.09 0.00800000 -4.30 0.00265759 -4.30 333.3216 21.11 0.00751094 47.7516 91608.67 0.00 14236.78 14236.78



Table of Contents

Report: Coil Sizing Details

For: Entire Facility

Timestamp: 2023-10-16 08:58:31

Coils

Coil Type Coil Location HVAC Type HVAC Name Zone Name(s) System Sizing Method Concurrence System Sizing Method Capacity System Sizing Method Air Flow Autosized Coil Capacity? Autosized Coil Airflow? Autosized Coil Water Flow? OA Pretreated prior to coil inlet? Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Terminal Unit Reheat Coil Multiplier DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio Moist Air Heat Capacity [J/kg-K] Dry Air Heat Capacity [J/kg-K] Standard Air Density Adjusted for Elevation [kg/m3] Supply Fan Name for Coil Supply Fan Type for Coil Supply Fan Maximum Air Volume Flow Rate [m3/s] Supply Fan Maximum Air Mass Flow Rate [kg/s] Plant Name for Coil Plant Fluid Specific Heat Capacity [J/kg-K] Plant Fluid Density [kg/m3] Plant Maximum Fluid Mass Flow Rate [kg/s] Plant Design Fluid Return Temperature [C] Plant Design Fluid Supply Temperature [C] Plant Design Fluid Temperature Difference [deltaC] Plant Design Capacity [W] Coil Capacity Percentage of Plant Design Capacity [%] Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Total Ideal Loads Peak Date/Time at Total Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Peak Load Type to Size On Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] Supply Fan Air Heat Gain at Ideal Loads Peak [W] Coil and Fan Net Total Capacity at Ideal Loads Peak [W] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] Outdoor Air Flow Percentage at Ideal Loads Peak [%] System Return Air Drybulb at Ideal Loads Peak [C] System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W] Coil Air Mass Flow Rate at Rating Conditions [kg/s] Coil Entering Air Drybulb at Rating Conditions [C] Coil Entering Air Wetbulb at Rating Conditions [C] Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] Coil Leaving Air Drybulb at Rating Conditions [C] Coil Leaving Air Wetbulb at Rating Conditions [C] Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K]
BASEMENT VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT BASEMENT VAV BOX BASEMENT N/A N/A N/A Yes Yes Yes No 14327.117 14327.117 2.467248 0.00012534 300.506 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1914 unknown unknown -999.0 -999.0   4197.9300 999.8980 3.93542556 54.44 82.22 27.78 458943.41 3.1218 3.184588 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 14327.12 14327.12 1.0000 2.93941025 2.467248 16.70 13.09 0.00800000 37036.7 40.00 21.06 0.00800000 60796.0 0.12532708 60.00 32.22 27.78 0.000 14327.12 -4.30 0.00265759 -4.30 0.00000000 0.0000 21.00 0.00795178 21.00 0.00795178 50.8633 1439.65 0.00 14407.47 14407.47 2.93941025 16.60 13.15 0.00800000 36934.7 21.41 15.00 0.00800000 41836.2
RETAIL_1_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT RETAIL_1_FLR_1 VAV BOX RETAIL_1_FLR_1 N/A N/A N/A Yes Yes Yes No 4825.409 4825.409 0.472551 0.00004221 105.886 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1914 unknown unknown -999.0 -999.0   4197.9300 999.8980 3.93542556 54.44 82.22 27.78 458943.41 1.0514 1.072577 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:20:00 unknown unknown WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:20:00 Sensible 4825.41 4825.41 1.0000 0.56298421 0.472551 16.70 13.09 0.00800000 37036.7 40.00 21.06 0.00800000 60796.0 0.04221047 60.00 32.22 27.78 0.000 4825.41 -4.30 0.00265759 -4.30 0.00000000 0.0000 21.00 0.00749616 21.00 0.00749616 47.9858 2359.53 0.00 4851.75 4851.75 0.56298421 16.60 13.15 0.00800000 36934.7 25.05 16.33 0.00800000 45552.7
RETAIL_2_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT RETAIL_2_FLR_1 VAV BOX RETAIL_2_FLR_1 N/A N/A N/A Yes Yes Yes No 1993.711 1993.711 0.236295 0.00001744 42.950 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1914 unknown unknown -999.0 -999.0   4197.9300 999.8980 3.93542556 54.44 82.22 27.78 458943.41 0.4344 0.443156 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 1993.71 1993.71 1.0000 0.28151576 0.236295 16.70 13.09 0.00800000 37036.7 40.00 21.06 0.00800000 60796.0 0.01744007 60.00 32.22 27.78 0.000 1993.71 -4.30 0.00265759 -4.30 0.00000000 0.0000 21.00 0.00740777 21.00 0.00740777 47.4250 760.71 0.00 2004.79 2004.79 0.28151576 16.60 13.15 0.00800000 36934.7 23.58 15.80 0.00800000 44056.2
MECH_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT MECH_FLR_1 VAV BOX MECH_FLR_1 N/A N/A N/A Yes Yes Yes No 2551.238 2551.238 0.221730 0.00002232 56.760 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1914 unknown unknown -999.0 -999.0   4197.9300 999.8980 3.93542556 54.44 82.22 27.78 458943.41 0.5559 0.567081 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 2551.24 2551.24 1.0000 0.26416328 0.221730 16.70 13.09 0.00800000 37036.7 40.00 21.06 0.00800000 60796.0 0.02231706 60.00 32.22 27.78 0.000 2551.24 -4.30 0.00265759 -4.30 0.00000000 0.0000 21.00 0.00726019 21.00 0.00726019 46.4911 1394.56 0.00 2565.09 2565.09 0.26416328 16.60 13.15 0.00800000 36934.7 26.12 16.71 0.00800000 46645.0
STORAGE_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT STORAGE_FLR_1 VAV BOX STORAGE_FLR_1 N/A N/A N/A Yes Yes Yes No 1434.232 1434.232 0.108872 0.00001255 32.492 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1914 unknown unknown -999.0 -999.0   4197.9300 999.8980 3.93542556 54.44 82.22 27.78 458943.41 0.3125 0.318797 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 1434.23 1434.23 1.0000 0.12970653 0.108872 16.70 13.09 0.00800000 37036.7 40.00 21.06 0.00800000 60796.0 0.01254600 60.00 32.22 27.78 0.000 1434.23 -4.30 0.00265759 -4.30 0.00000000 0.0000 21.00 0.00730601 21.00 0.00730601 46.7812 866.24 0.00 1441.97 1441.97 0.12970653 16.60 13.15 0.00800000 36934.7 27.50 17.19 0.00800000 48051.9
LAUNDRY_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown LAUNDRY_FLR_1 N/A N/A N/A Yes Yes Yes No 18849.126 18849.126 3.265876 0.00016490 395.214 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1914 unknown unknown -999.0 -999.0   4197.9300 999.8980 3.93542556 54.44 82.22 27.78 458943.41 4.1071 4.189726 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:20:00 unknown unknown WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:20:00 Sensible 18849.13 18849.13 1.0000 3.89087329 3.265876 16.70 13.09 0.00800000 37036.7 40.00 21.06 0.00800000 60796.0 0.16488356 60.00 32.22 27.78 0.000 18849.13 -4.30 0.00265759 -4.30 0.00000000 0.0000 21.00 0.00722922 21.00 0.00722922 46.2967 1815.44 0.00 18954.86 18954.86 3.89087329 16.60 13.15 0.00800000 36934.7 21.38 14.99 0.00800000 41806.4
CAFE_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CAFE_FLR_1 VAV BOX CAFE_FLR_1 N/A N/A N/A Yes Yes Yes No 15718.649 15718.649 1.862671 0.00013751 338.625 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1914 unknown unknown -999.0 -999.0   4197.9300 999.8980 3.93542556 54.44 82.22 27.78 458943.41 3.4250 3.493893 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:20:00 unknown unknown WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:20:00 Sensible 15718.65 15718.65 1.0000 2.21913371 1.862671 16.70 13.09 0.00800000 37036.7 40.00 21.06 0.00800000 60796.0 0.13749957 60.00 32.22 27.78 0.000 15718.65 -4.30 0.00265759 -4.30 0.00000000 0.0000 21.00 0.00755637 21.00 0.00755637 48.3662 5997.44 0.00 15806.04 15806.04 2.21913371 16.60 13.15 0.00800000 36934.7 23.58 15.81 0.00800000 44057.3
LOBBY_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown LOBBY_FLR_1 N/A N/A N/A Yes Yes Yes No 40686.711 40686.711 5.139451 0.00035595 871.809 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1914 unknown unknown -999.0 -999.0   4197.9300 999.8980 3.93542556 54.44 82.22 27.78 458943.41 8.8653 9.043718 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 40686.71 40686.71 1.0000 6.12299777 5.139451 16.70 13.09 0.00800000 37036.7 40.00 21.06 0.00800000 60796.0 0.35590878 60.00 32.22 27.78 0.000 40686.71 -4.30 0.00265759 -4.30 0.00000000 0.0000 21.00 0.00746228 21.00 0.00746228 47.7699 13866.24 0.00 40913.28 40913.28 6.12299777 16.60 13.15 0.00800000 36934.7 23.15 15.65 0.00800000 43616.6
ROOM_1_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_3 FAN COIL ROOM_1_FLR_3 N/A N/A N/A Yes Yes Yes No 14904.394 -999.000 1.244936 0.00053234 -999.000 -999.0000 1.00000 1.00000 1020.7476 1004.8586 1.1914 ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 1.244936 1.48318246   4197.9300 999.8980 25.79970433 13.37 6.70 6.67 722396.70 2.0632 2.063148 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 16:40:00 unknown unknown unknown 8/21 16:40:00 Sensible 14904.39 14714.54 1.0000 1.48318246 1.244936 22.50 15.79 0.00855731 44371.1 12.80 12.00 0.00850000 34322.2 0.53228617 6.70 13.37 6.67 0.000 14904.39 25.37 0.00840546 16.68 0.00000000 0.0000 21.11 0.00855731 21.11 0.00855731 54.3135 12580.64 0.00 15056.55 14610.62 1.48318246 22.50 15.90 0.00855731 44371.1 12.85 12.06 0.00843823 34219.6
ROOM_1_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_3 FAN COIL ROOM_1_FLR_3 N/A N/A N/A Yes Yes Yes No 5188.668 5188.668 0.226101 0.00004539 148.279 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1914 ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 1.244936 1.48318246   4197.9300 999.8980 3.93542556 54.44 82.22 27.78 458943.41 1.1306 1.153321 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:20:00 unknown unknown WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:20:00 Sensible 5188.67 5188.67 1.0000 0.26937047 0.226101 21.11 14.31 0.00747362 40196.7 40.00 21.06 0.00800000 60796.0 0.04538810 60.00 32.22 27.78 0.000 5188.67 -4.30 0.00265759 -4.30 0.00000000 0.0000 21.11 0.00747362 21.11 0.00747362 47.5184 5188.66 0.00 5593.49 5593.49 0.26937047 16.60 12.64 0.00747362 35602.0 36.98 19.88 0.00747362 56367.1
ROOM_2_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_3 FAN COIL ROOM_2_FLR_3 N/A N/A N/A Yes Yes Yes No 13348.439 -999.000 1.113091 0.00047677 -999.000 -999.0000 1.00000 1.00000 1020.7600 1004.8586 1.1914 ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 1.113091 1.32610551   4197.9300 999.8980 25.79970433 13.37 6.70 6.67 722396.70 1.8478 1.847765 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 17:00:00 unknown unknown unknown 8/21 17:00:00 Sensible 13348.44 13158.86 1.0000 1.32610551 1.113091 22.50 15.80 0.00856399 44388.1 12.80 12.00 0.00850000 34322.2 0.47671778 6.70 13.37 6.67 0.000 13348.44 25.13 0.00840508 16.59 0.00000000 0.0000 21.11 0.00856399 21.11 0.00856399 54.3553 11248.27 0.00 13484.59 13066.75 1.32610551 22.50 15.91 0.00856399 44388.1 12.85 12.06 0.00843919 34219.5
ROOM_2_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_3 FAN COIL ROOM_2_FLR_3 N/A N/A N/A Yes Yes Yes No 5194.324 5194.324 0.226348 0.00004544 148.441 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1914 ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 1.113091 1.32610551   4197.9300 999.8980 3.93542556 54.44 82.22 27.78 458943.41 1.1318 1.154578 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:20:00 unknown unknown WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:20:00 Sensible 5194.32 5194.32 1.0000 0.26966410 0.226348 21.11 14.31 0.00747417 40198.1 40.00 21.06 0.00800000 60796.0 0.04543757 60.00 32.22 27.78 0.000 5194.32 -4.30 0.00265759 -4.30 0.00000000 0.0000 21.11 0.00747417 21.11 0.00747417 47.5219 5194.32 0.00 5599.59 5599.59 0.26966410 16.60 12.64 0.00747417 35603.4 36.98 19.88 0.00747417 56368.5
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT19_FLR_3 FAN COIL ROOM_3_MULT19_FLR_3 N/A N/A N/A Yes Yes Yes No 106772.845 -999.000 9.049329 0.00381361 -999.000 -999.0000 1.00000 1.00000 1020.6389 1004.8586 1.1914 ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 9.049329 10.78111762   4197.9300 999.8980 25.79970433 13.37 6.70 6.67 722396.70 14.7804 14.780086 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 13:30:00 unknown unknown unknown 8/21 13:30:00 Sensible 106772.85 106772.84 1.0000 10.78111762 9.049329 22.50 15.74 0.00849881 44222.9 12.80 12.00 0.00849881 34319.2 3.81321839 6.70 13.37 6.67 0.000 106772.85 26.17 0.00840672 16.96 0.00000000 0.0000 21.11 0.00849881 21.11 0.00849881 53.9460 91451.40 0.00 107848.32 105958.05 10.78111762 22.50 15.85 0.00849881 44222.9 12.87 12.06 0.00842937 34219.4
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT19_FLR_3 FAN COIL ROOM_3_MULT19_FLR_3 N/A N/A N/A Yes Yes Yes No 29731.119 29731.119 1.295593 0.00026010 849.629 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1914 ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 9.049329 10.78111762   4197.9300 999.8980 3.93542556 54.44 82.22 27.78 458943.41 6.4782 6.608542 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:20:00 unknown unknown WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:20:00 Sensible 29731.12 29731.12 1.0000 1.54353275 1.295593 21.11 14.34 0.00750938 40288.0 40.00 21.06 0.00800000 60796.0 0.26007427 60.00 32.22 27.78 0.000 29731.12 -4.30 0.00265759 -4.30 0.00000000 0.0000 21.11 0.00750938 21.11 0.00750938 47.7417 29731.11 0.00 32051.00 32051.00 1.54353275 16.60 12.67 0.00750938 35692.6 36.98 19.90 0.00750938 56457.3
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_4_MULT19_FLR_3 FAN COIL ROOM_4_MULT19_FLR_3 N/A N/A N/A Yes Yes Yes No 72071.162 -999.000 5.753464 0.00257417 -999.000 -999.0000 1.00000 1.00000 1021.0885 1004.8586 1.1914 ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 5.753464 6.85451627   4197.9300 999.8980 25.79970433 13.37 6.70 6.67 722396.70 9.9767 9.976487 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 unknown unknown unknown 8/21 15:00:00 Sensible 72071.16 68366.53 1.0000 6.85451627 5.753464 22.50 15.95 0.00874067 44836.6 12.80 12.00 0.00850000 34322.2 2.57390425 6.70 13.37 6.67 0.000 72071.16 26.40 0.00840708 17.04 0.00000000 0.0000 21.11 0.00874067 21.11 0.00874067 55.4621 58139.33 0.00 72789.83 67995.52 6.85451627 22.50 16.06 0.00874067 44836.6 12.79 12.06 0.00846363 34217.4
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_4_MULT19_FLR_3 FAN COIL ROOM_4_MULT19_FLR_3 N/A N/A N/A Yes Yes Yes No 29853.370 29853.370 1.300920 0.00026117 853.122 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1914 ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 5.753464 6.85451627   4197.9300 999.8980 3.93542556 54.44 82.22 27.78 458943.41 6.5048 6.635716 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:20:00 unknown unknown WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:20:00 Sensible 29853.37 29853.37 1.0000 1.54987955 1.300920 21.11 14.34 0.00751109 40292.3 40.00 21.06 0.00800000 60796.0 0.26114366 60.00 32.22 27.78 0.000 29853.37 -4.30 0.00265759 -4.30 0.00000000 0.0000 21.11 0.00751109 21.11 0.00751109 47.7525 29853.36 0.00 32182.79 32182.79 1.54987955 16.60 12.67 0.00751109 35696.9 36.98 19.90 0.00751109 56461.6
ROOM_5_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_5_FLR_3 FAN COIL ROOM_5_FLR_3 N/A N/A N/A Yes Yes Yes No 13553.813 -999.000 1.130478 0.00048410 -999.000 -999.0000 1.00000 1.00000 1020.7583 1004.8586 1.1914 ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 1.130478 1.34681930   4197.9300 999.8980 25.79970433 13.37 6.70 6.67 722396.70 1.8762 1.876193 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 10:00:00 unknown unknown unknown 8/21 10:00:00 Sensible 13553.81 13364.03 1.0000 1.34681930 1.130478 22.50 15.80 0.00856308 44385.8 12.80 12.00 0.00850000 34322.2 0.48405237 6.70 13.37 6.67 0.000 13553.81 22.94 0.00840167 15.82 0.00000000 0.0000 21.11 0.00856308 21.11 0.00856308 54.3496 11423.98 0.00 13692.08 13270.37 1.34681930 22.50 15.91 0.00856308 44385.8 12.85 12.06 0.00843906 34219.5
ROOM_5_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_5_FLR_3 FAN COIL ROOM_5_FLR_3 N/A N/A N/A Yes Yes Yes No 5176.674 5176.674 0.225578 0.00004529 147.937 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1914 ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 1.130478 1.34681930   4197.9300 999.8980 3.93542556 54.44 82.22 27.78 458943.41 1.1280 1.150655 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:20:00 unknown unknown WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:20:00 Sensible 5176.67 5176.67 1.0000 0.26874780 0.225578 21.11 14.30 0.00747252 40193.9 40.00 21.06 0.00800000 60796.0 0.04528318 60.00 32.22 27.78 0.000 5176.67 -4.30 0.00265759 -4.30 0.00000000 0.0000 21.11 0.00747252 21.11 0.00747252 47.5115 5176.67 0.00 5580.56 5580.56 0.26874780 16.60 12.64 0.00747252 35599.3 36.98 19.88 0.00747252 56364.3
ROOM_6_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_6_FLR_3 FAN COIL ROOM_6_FLR_3 N/A N/A N/A Yes Yes Yes No 12238.768 -999.000 1.019094 0.00043713 -999.000 -999.0000 1.00000 1.00000 1020.7706 1004.8586 1.1914 ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 1.019094 1.21412046   4197.9300 999.8980 25.79970433 13.37 6.70 6.67 722396.70 1.6942 1.694158 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 09:10:00 unknown unknown unknown 8/21 09:10:00 Sensible 12238.77 12049.72 1.0000 1.21412046 1.019094 22.50 15.81 0.00856969 44402.6 12.80 12.00 0.00850000 34322.2 0.43708769 6.70 13.37 6.67 0.000 12238.77 21.65 0.00839969 15.35 0.00000000 0.0000 21.11 0.00856969 21.11 0.00856969 54.3910 10298.39 0.00 12363.51 11966.00 1.21412046 22.50 15.91 0.00856969 44402.6 12.85 12.06 0.00844001 34219.5
ROOM_6_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_6_FLR_3 FAN COIL ROOM_6_FLR_3 N/A N/A N/A Yes Yes Yes No 5182.333 5182.333 0.225825 0.00004534 148.098 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1914 ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 1.019094 1.21412046   4197.9300 999.8980 3.93542556 54.44 82.22 27.78 458943.41 1.1292 1.151913 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:20:00 unknown unknown WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:20:00 Sensible 5182.33 5182.33 1.0000 0.26904160 0.225825 21.11 14.31 0.00747307 40195.3 40.00 21.06 0.00800000 60796.0 0.04533268 60.00 32.22 27.78 0.000 5182.33 -4.30 0.00265759 -4.30 0.00000000 0.0000 21.11 0.00747307 21.11 0.00747307 47.5150 5182.33 0.00 5586.66 5586.66 0.26904160 16.60 12.64 0.00747307 35600.7 36.98 19.88 0.00747307 56365.7
CORRIDOR_FLR_3 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORRIDOR_FLR_3 VAV BOX CORRIDOR_FLR_3 N/A N/A N/A Yes Yes Yes No 14547.385 14547.385 1.244879 0.00012727 324.277 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1914 unknown unknown -999.0 -999.0   4197.9300 999.8980 3.93542556 54.44 82.22 27.78 458943.41 3.1698 3.233548 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:20:00 unknown unknown WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:20:00 Sensible 14547.38 14547.38 1.0000 1.48311409 1.244879 16.70 13.09 0.00800000 37036.7 40.00 21.06 0.00800000 60796.0 0.12725388 60.00 32.22 27.78 0.000 14547.38 -4.30 0.00265759 -4.30 0.00000000 0.0000 21.00 0.00757832 21.00 0.00757832 48.5036 8049.47 0.00 14626.31 14626.31 1.48311409 16.60 13.15 0.00800000 36934.7 26.27 16.76 0.00800000 46796.6
ROOM_1_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_6 FAN COIL ROOM_1_FLR_6 N/A N/A N/A Yes Yes Yes No 3988.372 -999.000 0.333458 0.00014245 -999.000 -999.0000 1.00000 1.00000 1020.7406 1004.8586 1.1914 ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.333458 0.39727216   4197.9300 999.8980 25.79970433 13.37 6.70 6.67 722396.70 0.5521 0.552092 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 16:30:00 unknown unknown unknown 8/21 16:30:00 Sensible 3988.37 3940.86 1.0000 0.39727216 0.333458 22.50 15.79 0.00855356 44361.6 12.80 12.00 0.00850000 34322.2 0.14243823 6.70 13.37 6.67 0.000 3988.37 25.49 0.00840565 16.72 0.00000000 0.0000 21.11 0.00855356 21.11 0.00855356 54.2900 3369.74 0.00 4029.11 3912.88 0.39727216 22.50 15.90 0.00855356 44361.6 12.85 12.06 0.00843768 34219.7
ROOM_1_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_6 FAN COIL ROOM_1_FLR_6 N/A N/A N/A Yes Yes Yes No 1653.183 1653.183 0.072039 0.00001446 47.241 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1914 ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.333458 0.39727216   4197.9300 999.8980 3.93542556 54.44 82.22 27.78 458943.41 0.3602 0.367465 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:20:00 unknown unknown WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:20:00 Sensible 1653.18 1653.18 1.0000 0.08582529 0.072039 21.11 14.40 0.00757795 40461.7 40.00 21.06 0.00800000 60796.0 0.01446130 60.00 32.22 27.78 0.000 1653.18 -4.30 0.00265759 -4.30 0.00000000 0.0000 21.11 0.00757795 21.11 0.00757795 48.1737 1653.18 0.00 1782.17 1782.17 0.08582529 16.60 12.74 0.00757795 35866.2 36.98 19.95 0.00757795 56631.2
ROOM_2_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_6 FAN COIL ROOM_2_FLR_6 N/A N/A N/A Yes Yes Yes No 3547.634 -999.000 0.296105 0.00012671 -999.000 -999.0000 1.00000 1.00000 1020.7531 1004.8586 1.1914 ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.296105 0.35277158   4197.9300 999.8980 25.79970433 13.37 6.70 6.67 722396.70 0.4911 0.491083 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 17:00:00 unknown unknown unknown 8/21 17:00:00 Sensible 3547.63 3500.14 1.0000 0.35277158 0.296105 22.50 15.80 0.00856028 44378.7 12.80 12.00 0.00850000 34322.2 0.12669799 6.70 13.37 6.67 0.000 3547.63 25.13 0.00840508 16.59 0.00000000 0.0000 21.11 0.00856028 21.11 0.00856028 54.3321 2992.28 0.00 3583.84 3475.51 0.35277158 22.50 15.91 0.00856028 44378.7 12.85 12.06 0.00843866 34219.6
ROOM_2_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_6 FAN COIL ROOM_2_FLR_6 N/A N/A N/A Yes Yes Yes No 1654.608 1654.608 0.072101 0.00001448 47.282 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1914 ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.296105 0.35277158   4197.9300 999.8980 3.93542556 54.44 82.22 27.78 458943.41 0.3605 0.367781 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:20:00 unknown unknown WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:20:00 Sensible 1654.61 1654.61 1.0000 0.08589924 0.072101 21.11 14.40 0.00757831 40462.6 40.00 21.06 0.00800000 60796.0 0.01447376 60.00 32.22 27.78 0.000 1654.61 -4.30 0.00265759 -4.30 0.00000000 0.0000 21.11 0.00757831 21.11 0.00757831 48.1760 1654.61 0.00 1783.70 1783.70 0.08589924 16.60 12.74 0.00757831 35867.1 36.98 19.95 0.00757831 56632.1
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT9_FLR_6 FAN COIL ROOM_3_MULT9_FLR_6 N/A N/A N/A Yes Yes Yes No 22293.238 -999.000 1.847525 0.00079625 -999.000 -999.0000 1.00000 1.00000 1020.8058 1004.8586 1.1914 ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 1.847525 2.20108927   4197.9300 999.8980 25.79970433 13.37 6.70 6.67 722396.70 3.0860 3.085953 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 13:40:00 unknown unknown unknown 8/21 13:40:00 Sensible 22293.24 21857.12 1.0000 2.20108927 1.847525 22.50 15.82 0.00858862 44450.5 12.80 12.00 0.00850000 34322.2 0.79616670 6.70 13.37 6.67 0.000 22293.24 26.25 0.00840684 16.99 0.00000000 0.0000 21.11 0.00858862 21.11 0.00858862 54.5102 18669.63 0.00 22519.90 21709.08 2.20108927 22.50 15.93 0.00858862 44450.5 12.84 12.06 0.00844272 34219.2
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT9_FLR_6 FAN COIL ROOM_3_MULT9_FLR_6 N/A N/A N/A Yes Yes Yes No 7974.444 7974.444 0.347497 0.00006976 227.874 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1914 ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 1.847525 2.20108927   4197.9300 999.8980 3.93542556 54.44 82.22 27.78 458943.41 1.7376 1.772535 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:20:00 unknown unknown WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:20:00 Sensible 7974.44 7974.44 1.0000 0.41399804 0.347497 21.11 14.42 0.00759566 40506.8 40.00 21.06 0.00800000 60796.0 0.06975680 60.00 32.22 27.78 0.000 7974.44 -4.30 0.00265759 -4.30 0.00000000 0.0000 21.11 0.00759566 21.11 0.00759566 48.2845 7974.44 0.00 8596.64 8596.64 0.41399804 16.60 12.76 0.00759566 35911.0 36.98 19.97 0.00759566 56675.9
BANQUET_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown BANQUET_FLR_6 N/A N/A N/A Yes Yes Yes No 17055.319 17055.319 2.181540 0.00014921 365.082 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1914 unknown unknown -999.0 -999.0   4197.9300 999.8980 3.93542556 54.44 82.22 27.78 458943.41 3.7162 3.791004 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:20:00 unknown unknown WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:20:00 Sensible 17055.32 17055.32 1.0000 2.59902561 2.181540 16.70 13.09 0.00800000 37036.7 40.00 21.06 0.00800000 60796.0 0.14919215 60.00 32.22 27.78 0.000 17055.32 -4.30 0.00265759 -4.30 0.00000000 0.0000 21.00 0.00769064 21.00 0.00769064 49.2142 5666.38 0.00 17150.33 17150.33 2.59902561 16.60 13.15 0.00800000 36934.7 23.07 15.62 0.00800000 43533.5
DINING_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown DINING_FLR_6 N/A N/A N/A Yes Yes Yes No 17714.730 17714.730 2.288398 0.00015498 378.898 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1914 unknown unknown -999.0 -999.0   4197.9300 999.8980 3.93542556 54.44 82.22 27.78 458943.41 3.8599 3.937576 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 19:20:00 unknown unknown WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 19:20:00 Sensible 17714.73 17714.73 1.0000 2.72633374 2.288398 16.70 13.09 0.00800000 37036.7 40.00 21.06 0.00800000 60796.0 0.15496038 60.00 32.22 27.78 0.000 17714.73 -4.30 0.00265759 -4.30 0.00000000 0.0000 21.00 0.00769576 21.00 0.00769576 49.2467 5767.95 0.00 17813.43 17813.43 2.72633374 16.60 13.15 0.00800000 36934.7 23.01 15.59 0.00800000 43468.6
KITCHEN_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown KITCHEN_FLR_6 N/A N/A N/A Yes Yes Yes No 12886.515 12886.515 2.303631 0.00011274 269.716 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1914 unknown unknown -999.0 -999.0   4197.9300 999.8980 3.93542556 54.44 82.22 27.78 458943.41 2.8079 2.864375 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 23:30:00 unknown unknown WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 23:30:00 Sensible 12886.51 12886.51 1.0000 2.74448130 2.303631 16.70 13.09 0.00800000 37036.7 40.00 21.06 0.00800000 60796.0 0.11272535 60.00 32.22 27.78 0.000 12886.51 -4.30 0.00265759 -4.30 0.00000000 0.0000 19.73 0.00467342 21.00 0.00467342 30.0577 937.60 0.00 12958.85 12958.85 2.74448130 16.60 13.15 0.00800000 36934.7 21.23 14.94 0.00800000 41656.5
CORRIDOR_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORRIDOR_FLR_6 VAV BOX CORRIDOR_FLR_6 N/A N/A N/A Yes Yes Yes No 10065.776 10065.776 0.767295 0.00008806 227.900 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1914 unknown unknown -999.0 -999.0   4197.9300 999.8980 3.93542556 54.44 82.22 27.78 458943.41 2.1932 2.237390 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 19:20:00 unknown unknown WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 19:20:00 Sensible 10065.78 10065.78 1.0000 0.91413381 0.767295 16.70 13.09 0.00800000 37036.7 40.00 21.06 0.00800000 60796.0 0.08805081 60.00 32.22 27.78 0.000 10065.78 -4.30 0.00265759 -4.30 0.00000000 0.0000 21.00 0.00774384 21.00 0.00774384 49.5503 6059.60 0.00 10120.06 10120.06 0.91413381 16.60 13.15 0.00800000 36934.7 27.46 17.17 0.00800000 48005.4
VAV WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC VAV WITH REHEAT BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; Coincident CoolingDesignCapacity N/A Yes Yes Yes No 423570.841 -999.000 22.560437 0.01512897 -999.000 -999.0000 1.00000 1.00000 1020.4683 1004.8586 1.1914 VAV WITH REHEAT FAN Fan:VariableVolume 22.560437 26.87787333   4197.9300 999.8980 25.79970433 13.37 6.70 6.67 722396.70 58.6341 58.634105 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 14:00:00 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 14:00:00 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 13:50:00 Sensible 423570.84 423570.84 1.0000 26.87787333 22.560437 26.40 17.04 0.00840708 47966.0 10.96 10.96 0.00840708 32206.9 15.12742570 6.70 13.37 6.67 50549.786 373021.05 26.40 0.00840708 17.04 22.55588000 99.9798 23.99 0.00961017 23.99 0.00961050 51.1177 306846.22 0.00 427330.34 406605.80 26.87787333 26.40 17.15 0.00840708 47966.0 11.58 11.18 0.00810140 32067.0
VAV WITH REHEAT HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC VAV WITH REHEAT BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 170153.310 170153.310 6.768131 0.00148858 2903.295 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1914 VAV WITH REHEAT FAN Fan:VariableVolume 22.560437 26.87787333   4197.9300 999.8980 3.93542556 54.44 82.22 27.78 458943.41 37.0750 37.821158 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 19:20:00 unknown unknown WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 19:20:00 Sensible 170153.31 170153.31 1.0000 8.06336200 6.768131 -4.30 -4.30 0.00265759 2304.4 16.70 13.09 0.00800000 37036.7 1.48842353 60.00 32.22 27.78 0.000 170153.31 -4.30 0.00265759 -4.30 22.55588000 333.2660 20.92 0.00748388 21.00 0.00755857 48.3707 54412.52 0.00 156576.45 156576.45 8.06336200 2.80 0.02 0.00265759 9473.9 22.03 9.93 0.00265759 28892.1
FLR_3_DOAS COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC FLR_3_DOAS ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; Coincident CoolingDesignCapacity N/A Yes Yes Yes No 36112.103 -999.000 2.051317 0.00128984 -999.000 -999.0000 1.00000 1.00000 1020.4683 1004.8586 1.1914 FLR_3_DOAS FAN Fan:ConstantVolume 2.051245 2.44379602   4197.9300 999.8980 25.79970433 13.37 6.70 6.67 722396.70 4.9989 4.998930 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 14:30:00 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 14:30:00 WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB 8/21 14:30:00 Sensible 36112.10 36112.10 1.0000 2.44388195 2.051317 26.40 17.04 0.00840708 47966.0 11.92 11.55 0.00840708 33189.4 1.28970906 6.70 13.37 6.67 2195.006 33917.10 26.40 0.00840708 17.04 2.05124512 99.9965 21.11 0.00859088 21.11 0.00859361 54.5404 206305.12 0.00 36425.73 35509.87 2.44388195 26.40 17.15 0.00840708 47966.0 12.16 11.59 0.00825857 33061.1
FLR_3_DOAS HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC FLR_3_DOAS ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 15471.261 15471.261 0.615395 0.00013535 263.983 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1914 FLR_3_DOAS FAN Fan:ConstantVolume 2.051245 2.44379602   4197.9300 999.8980 3.93542556 54.44 82.22 27.78 458943.41 3.3711 3.438905 WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:20:00 unknown unknown WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB 1/21 12:20:00 Sensible 15471.26 15471.26 1.0000 0.73316458 0.615395 -4.30 -4.30 0.00265759 2304.4 16.70 13.09 0.00800000 37036.7 0.13533554 60.00 32.22 27.78 0.000 15471.26 -4.30 0.00265759 -4.30 2.05124512 333.3216 21.11 0.00751177 21.11 0.00751094 47.7516 91608.67 0.00 14236.78 14236.78 0.73316458 2.80 0.02 0.00265759 9473.9 22.03 9.93 0.00265759 28892.1



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2023-10-16 08:58:31

Economizer

High Limit Shutoff Control Minimum Outdoor Air [m3/s] Maximum Outdoor Air [m3/s] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [C] Outdoor Air Enthalpy Limit [C]
VAV WITH REHEAT_OA_CONTROLLER DifferentialDryBulb 22.56 22.56 -      
FLR_3_DOAS_OA_CONTROLLER DifferentialDryBulb 2.05 2.05 -      


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [m3/s-person] Outdoor Air Per Area [m3/s-m2] Outdoor Air Per Zone [m3/s] Outdoor Air ACH [ach] Outdoor Air Method Outdoor Air Schedule Name Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule Name
BASEMENT VAV WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
RETAIL_1_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.001181 0.000000 0.000000 Flow/Area   1.00 1.00  
RETAIL_2_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.001181 0.000000 0.000000 Flow/Area   1.00 1.00  
MECH_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.000000 0.000000 0.000000 Flow/Area   1.00 1.00  
STORAGE_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.000610 0.000000 0.000000 Flow/Area   1.00 1.00  
LAUNDRY_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.000000 0.000000 0.000000 Flow/Area   1.00 1.00  
CAFE_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.003581 0.000000 0.000000 Flow/Area   1.00 1.00  
LOBBY_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.001448 0.000000 0.000000 Flow/Area   1.00 1.00  
CORRIDOR_FLR_3 VAV WITH REHEAT_DCV 0.000000 0.000305 0.000000 0.000000 Flow/Area   1.00 1.00  
BANQUET_FLR_6 VAV WITH REHEAT_DCV 0.000000 0.003581 0.000000 0.000000 Flow/Area   1.00 1.00  
DINING_FLR_6 VAV WITH REHEAT_DCV 0.000000 0.003581 0.000000 0.000000 Flow/Area   1.00 1.00  
KITCHEN_FLR_6 VAV WITH REHEAT_DCV 0.000000 0.003556 0.000000 0.000000 Flow/Area   1.00 1.00  
CORRIDOR_FLR_6 VAV WITH REHEAT_DCV 0.000000 0.000305 0.000000 0.000000 Flow/Area   1.00 1.00  


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
BASEMENT 3.33 8760.00 3.33
RETAIL_1_FLR_1 1400.00 8709.33 1388.00
RETAIL_2_FLR_1 5.83 8760.00 5.83
MECH_FLR_1 109.67 8760.00 109.67
STORAGE_FLR_1 247.83 8760.00 247.83
LAUNDRY_FLR_1 2583.17 5011.83 1146.17
CAFE_FLR_1 118.67 8690.00 105.50
LOBBY_FLR_1 0.00 8760.00 0.00
ROOM_1_FLR_3 1676.50 8449.83 1625.83
ROOM_2_FLR_3 2279.17 8615.00 2269.50
ROOM_3_MULT19_FLR_3 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 318.00 8760.00 318.00
ROOM_5_FLR_3 1607.67 8357.33 1605.50
ROOM_6_FLR_3 2250.17 8651.33 2249.33
CORRIDOR_FLR_3 161.83 8760.00 161.83
ROOM_1_FLR_6 2648.17 8305.00 2495.17
ROOM_2_FLR_6 3191.33 8511.00 3140.00
ROOM_3_MULT9_FLR_6 1170.83 8163.67 1002.00
BANQUET_FLR_6 4.17 8683.50 0.00
DINING_FLR_6 34.33 8547.50 0.00
KITCHEN_FLR_6 6463.33 6838.50 4877.17
CORRIDOR_FLR_6 578.00 8760.00 578.00
Facility 7465.17 8760.00 6724.67
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
BASEMENT 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 23.33 0.00 23.33 0.00
RETAIL_2_FLR_1 0.00 0.00 0.00 0.00
MECH_FLR_1 0.00 0.00 0.00 0.00
STORAGE_FLR_1 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 0.00 0.00 0.00 0.00
CAFE_FLR_1 0.00 0.00 0.00 0.00
LOBBY_FLR_1 0.00 0.00 0.00 0.00
ROOM_1_FLR_3 0.00 1.00 0.00 1.00
ROOM_2_FLR_3 0.50 0.83 0.50 0.83
ROOM_3_MULT19_FLR_3 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 0.33 1.17 0.33 1.17
ROOM_5_FLR_3 0.00 0.00 0.00 0.00
ROOM_6_FLR_3 0.83 0.00 0.83 0.00
CORRIDOR_FLR_3 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 0.00 3.17 0.00 3.17
ROOM_2_FLR_6 0.17 3.00 0.17 3.00
ROOM_3_MULT9_FLR_6 0.00 1.00 0.00 1.00
BANQUET_FLR_6 0.00 0.00 0.00 0.00
DINING_FLR_6 0.00 0.00 0.00 0.00
KITCHEN_FLR_6 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6 0.00 0.00 0.00 0.00
Facility 24.50 5.67 24.50 5.67
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2023-10-16 08:58:31

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
BASEMENT 61.80 106.50 4826.41 1.856 0.000 0.000 0.000
RETAIL_1_FLR_1 6.28 10.83 265.76 6.454 0.138 0.000 0.000
RETAIL_2_FLR_1 7.28 12.54 307.76 2.788 0.046 0.000 0.000
MECH_FLR_1 1.54 2.65 650.80 1.237 0.052 0.000 0.000
STORAGE_FLR_1 1.18 2.04 375.47 1.052 0.052 0.000 0.000
LAUNDRY_FLR_1 4.87 8.40 309.22 38.394 0.148 0.000 0.000
CAFE_FLR_1 82.58 142.30 748.35 9.041 0.109 0.000 0.000
LOBBY_FLR_1 245.14 422.44 5183.56 3.602 0.045 0.000 0.000
ROOM_1_FLR_3 0.95 1.50 118.94 0.472 0.180 0.000 0.027
ROOM_2_FLR_3 0.95 1.50 118.93 0.472 0.180 0.000 0.027
ROOM_3_MULT19_FLR_3   1.50 74.75        
ROOM_4_MULT19_FLR_3 0.95 1.50 74.77 0.536 0.080 0.000 0.043
ROOM_5_FLR_3 0.95 1.50 118.94 0.472 0.180 0.000 0.027
ROOM_6_FLR_3 0.95 1.50 118.93 0.472 0.180 0.000 0.027
CORRIDOR_FLR_3 12.16 20.96 1186.91 0.952 0.022 0.000 0.000
ROOM_1_FLR_6 0.95 1.50 118.94 0.472 0.180 0.000 0.031
ROOM_2_FLR_6 0.95 1.50 118.93 0.472 0.180 0.000 0.031
ROOM_3_MULT9_FLR_6 0.95 1.50 74.77 0.537 0.147 0.000 0.049
BANQUET_FLR_6 145.01 249.90 1010.89 7.856 0.052 0.000 0.000
DINING_FLR_6 145.01 249.90 1010.89 8.243 0.052 0.000 0.000
KITCHEN_FLR_6 12.90 22.24 314.87 26.786 0.149 0.000 0.000
CORRIDOR_FLR_6 12.87 22.18 1256.16 2.218 0.036 0.000 0.000
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
BASEMENT 61.80 106.50 4826.41 1.794 0.000 0.000 0.000
RETAIL_1_FLR_1 6.28 10.83 265.76 6.239 0.003 0.000 0.000
RETAIL_2_FLR_1 7.28 12.54 307.76 2.695 0.001 0.000 0.000
MECH_FLR_1 1.54 2.65 650.80 1.195 0.001 0.000 0.000
STORAGE_FLR_1 1.18 2.04 375.47 1.017 0.001 0.000 0.000
LAUNDRY_FLR_1 4.87 8.40 309.22 37.056 0.003 0.000 0.000
CAFE_FLR_1 82.58 142.30 748.35 8.737 0.002 0.000 0.000
LOBBY_FLR_1 245.14 422.44 5183.56 3.480 0.001 0.000 0.000
ROOM_1_FLR_3 0.95 1.50 118.94 0.456 0.003 0.000 0.000
ROOM_2_FLR_3 0.95 1.50 118.93 0.456 0.003 0.000 0.000
ROOM_3_MULT19_FLR_3   1.50 74.75        
ROOM_4_MULT19_FLR_3 0.95 1.50 74.77 0.518 0.002 0.000 0.000
ROOM_5_FLR_3 0.95 1.50 118.94 0.456 0.003 0.000 0.000
ROOM_6_FLR_3 0.95 1.50 118.93 0.456 0.003 0.000 0.000
CORRIDOR_FLR_3 12.16 20.96 1186.91 0.920 0.000 0.000 0.000
ROOM_1_FLR_6 0.95 1.50 118.94 0.456 0.003 0.000 0.000
ROOM_2_FLR_6 0.95 1.50 118.93 0.456 0.003 0.000 0.000
ROOM_3_MULT9_FLR_6 0.95 1.50 74.77 0.518 0.003 0.000 0.000
BANQUET_FLR_6 145.01 249.90 1010.89 7.609 0.001 0.000 0.000
DINING_FLR_6 145.01 249.90 1010.89 7.985 0.001 0.000 0.000
KITCHEN_FLR_6 12.90 22.24 314.87 25.732 0.003 0.000 0.000
CORRIDOR_FLR_6 12.87 22.18 1256.16 2.144 0.001 0.000 0.000
Values shown for a single zone without multipliers


Table of Contents

Report: Outdoor Air Details

For: Entire Facility

Timestamp: 2023-10-16 08:58:31

Mechanical Ventilation Parameters by Zone

AirLoop Name Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Zone Area [m2] Design Zone Outdoor Airflow - Voz [m3/s] Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s]
BASEMENT VAV WITH REHEAT 61.80 106.50 4826.41 1978.83 0.0000 0.854
RETAIL_1_FLR_1 VAV WITH REHEAT 6.28 10.83 265.76 67.07 0.0000 0.079
RETAIL_2_FLR_1 VAV WITH REHEAT 7.28 12.54 307.76 77.67 0.0000 0.092
MECH_FLR_1 VAV WITH REHEAT 1.54 2.65 650.80 164.24 0.0000 0.000
STORAGE_FLR_1 VAV WITH REHEAT 1.18 2.04 375.47 94.76 0.0000 0.058
LAUNDRY_FLR_1 VAV WITH REHEAT 4.87 8.40 309.22 78.04 0.0000 0.000
CAFE_FLR_1 VAV WITH REHEAT 82.58 142.30 748.35 188.86 0.0000 0.676
LOBBY_FLR_1 VAV WITH REHEAT 245.14 422.44 5183.56 1308.19 0.0000 1.894
ROOM_1_FLR_3 FLR_3_DOAS 0.95 1.50 118.94 39.02 0.0000 0.062
ROOM_2_FLR_3 FLR_3_DOAS 0.95 1.50 118.93 39.02 0.0000 0.062
ROOM_3_MULT19_FLR_3 FLR_3_DOAS   1.50 74.75 24.52 0.0000 0.837
ROOM_4_MULT19_FLR_3 FLR_3_DOAS 0.95 1.50 74.77 24.53 0.0000 0.837
ROOM_5_FLR_3 FLR_3_DOAS 0.95 1.50 118.94 39.02 0.0000 0.062
ROOM_6_FLR_3 FLR_3_DOAS 0.95 1.50 118.93 39.02 0.0000 0.062
CORRIDOR_FLR_3 VAV WITH REHEAT 12.16 20.96 1186.91 389.40 0.0000 0.475
ROOM_1_FLR_6 FLR_3_DOAS 0.95 1.50 118.94 39.02 0.0000 0.015
ROOM_2_FLR_6 FLR_3_DOAS 0.95 1.50 118.93 39.02 0.0000 0.015
ROOM_3_MULT9_FLR_6 FLR_3_DOAS 0.95 1.50 74.77 24.53 0.0000 0.099
BANQUET_FLR_6 VAV WITH REHEAT 145.01 249.90 1010.89 331.66 0.0000 1.188
DINING_FLR_6 VAV WITH REHEAT 145.01 249.90 1010.89 331.66 0.0000 1.188
KITCHEN_FLR_6 VAV WITH REHEAT 12.90 22.24 314.87 103.30 0.0000 0.367
CORRIDOR_FLR_6 VAV WITH REHEAT 12.87 22.18 1256.16 412.12 0.0000 0.126
Total Facility   873.39 1604.23 35184.81 11345.29 0.0000 137.584


Total Outdoor Air by Zone

Mechanical Ventilation [m3] Natural Ventilation [m3] Total Ventilation [m3] Infiltration [m3] Total Ventilation and Infiltration [m3] Dynamic Target Ventilation - Voz-dyn [m3] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr] Time Above Zero When Unoccupied [hr]
BASEMENT 77784493.65 0.00 77784493.65 0.00 77784493.65 26946214.98 0.00 0.00 8760.00 0.00
RETAIL_1_FLR_1 14898036.60 0.00 14898036.60 319403.00 15217439.61 2498216.28 0.00 0.00 8760.00 0.00
RETAIL_2_FLR_1 7449644.31 0.00 7449644.31 123289.96 7572934.28 2892943.94 0.00 0.00 8760.00 0.00
MECH_FLR_1 6990452.15 0.00 6990452.15 291384.23 7281836.38 0.00 0.00 0.00 8760.00 0.00
STORAGE_FLR_1 3432374.57 0.00 3432374.57 168112.65 3600487.22 1821682.01 0.00 0.00 8760.00 0.00
LAUNDRY_FLR_1 0.10E+09 0.00 0.10E+09 397870.28 0.10E+09 0.00 0.00 0.00 8760.00 0.00
CAFE_FLR_1 58724089.86 0.00 58724089.86 706058.42 59430148.28 21330615.53 0.00 0.00 8760.00 0.00
LOBBY_FLR_1 0.16E+09 0.00 0.16E+09 2017370.18 0.16E+09 59728886.00 0.00 0.00 8760.00 0.00
ROOM_1_FLR_3 1946875.62 27936.79 1974812.41 185391.43 2160203.84 1946875.62 0.00 8310.83 449.17 0.00
ROOM_2_FLR_3 1946647.51 28013.68 1974661.19 185377.29 2160038.48 1946647.51 0.00 8310.83 449.17 0.00
ROOM_3_MULT19_FLR_3 26397887.27 31461.34 26429348.61 51726.29 26481074.90 26397887.27 0.00 8317.67 442.33 8760.00
ROOM_4_MULT19_FLR_3 26405105.73 27621.51 26432727.24 51740.43 26484467.67 26405105.73 0.00 8324.18 435.82 0.00
ROOM_5_FLR_3 1946875.62 27897.14 1974772.75 185391.43 2160164.19 1946875.62 0.00 8310.83 449.17 0.00
ROOM_6_FLR_3 1946647.51 27931.68 1974579.19 185377.29 2159956.48 1946647.51 0.00 8310.83 449.17 0.00
CORRIDOR_FLR_3 39247083.14 0.00 39247083.14 224175.54 39471258.68 14972100.18 0.00 0.00 8760.00 0.00
ROOM_1_FLR_6 486718.90 31732.37 518451.27 185430.49 703881.76 486718.90 0.00 8311.00 449.00 0.00
ROOM_2_FLR_6 486661.88 31877.63 518539.51 185416.35 703955.85 486661.88 0.00 8311.00 449.00 0.00
ROOM_3_MULT9_FLR_6 3126920.42 31640.24 3158560.66 94872.73 3253433.39 3126920.42 0.00 8311.00 449.00 0.00
BANQUET_FLR_6 68777024.56 0.00 68777024.56 452774.66 69229799.22 37458366.31 0.00 0.00 8760.00 0.00
DINING_FLR_6 72145931.20 0.00 72145931.20 452774.66 72598705.86 37458366.31 0.00 0.00 8760.00 0.00
KITCHEN_FLR_6 72690838.37 0.00 72690838.37 405338.30 73096176.67 11584760.86 0.00 0.00 8760.00 0.00
CORRIDOR_FLR_6 24190374.80 0.00 24190374.80 396722.51 24587097.30 3961413.96 0.00 0.00 8760.00 0.00
Total Facility 0.49E+10 5285785.99 0.49E+10 18682123.06 0.49E+10 0.43E+10 0.00 8329.64 8760.00 8760.00


Average Outdoor Air During Occupancy by Zone - Flow Rates

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Infiltration [m3/s] Total Ventilation and Infiltration [m3/s] Dynamic Target Ventilation - Voz-dyn [m3/s] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr]
BASEMENT 2.4665 0.0000 2.4665 0.0000 2.4665 0.8545 0.00 0.00 8760.00
RETAIL_1_FLR_1 0.4724 0.0000 0.4724 0.0101 0.4825 0.0792 0.00 0.00 8760.00
RETAIL_2_FLR_1 0.2362 0.0000 0.2362 0.0039 0.2401 0.0917 0.00 0.00 8760.00
MECH_FLR_1 0.2217 0.0000 0.2217 0.0092 0.2309 0.0000 0.00 0.00 8760.00
STORAGE_FLR_1 0.1088 0.0000 0.1088 0.0053 0.1142 0.0578 0.00 0.00 8760.00
LAUNDRY_FLR_1 3.2658 0.0000 3.2658 0.0126 3.2784 0.0000 0.00 0.00 8760.00
CAFE_FLR_1 1.8621 0.0000 1.8621 0.0224 1.8845 0.6764 0.00 0.00 8760.00
LOBBY_FLR_1 5.1380 0.0000 5.1380 0.0640 5.2019 1.8940 0.00 0.00 8760.00
ROOM_1_FLR_3 0.0617 0.0009 0.0626 0.0059 0.0685 0.0617 0.00 8310.83 449.17
ROOM_2_FLR_3 0.0617 0.0009 0.0626 0.0059 0.0685 0.0617 0.00 8310.83 449.17
ROOM_4_MULT19_FLR_3 0.8373 0.0009 0.8382 0.0016 0.8398 0.8373 0.00 8324.18 435.82
ROOM_5_FLR_3 0.0617 0.0009 0.0626 0.0059 0.0685 0.0617 0.00 8310.83 449.17
ROOM_6_FLR_3 0.0617 0.0009 0.0626 0.0059 0.0685 0.0617 0.00 8310.83 449.17
CORRIDOR_FLR_3 1.2445 0.0000 1.2445 0.0071 1.2516 0.4748 0.00 0.00 8760.00
ROOM_1_FLR_6 0.0154 0.0010 0.0164 0.0059 0.0223 0.0154 0.00 8311.00 449.00
ROOM_2_FLR_6 0.0154 0.0010 0.0164 0.0059 0.0223 0.0154 0.00 8311.00 449.00
ROOM_3_MULT9_FLR_6 0.0992 0.0010 0.1002 0.0030 0.1032 0.0992 0.00 8311.00 449.00
BANQUET_FLR_6 2.1809 0.0000 2.1809 0.0144 2.1953 1.1878 0.00 0.00 8760.00
DINING_FLR_6 2.2877 0.0000 2.2877 0.0144 2.3021 1.1878 0.00 0.00 8760.00
KITCHEN_FLR_6 2.3050 0.0000 2.3050 0.0129 2.3179 0.3674 0.00 0.00 8760.00
CORRIDOR_FLR_6 0.7671 0.0000 0.7671 0.0126 0.7797 0.1256 0.00 0.00 8760.00
Total Facility 91.8361 0.0918 91.9279 0.4677 92.3956 73.9670 0.00 8329.64 8760.00


Total Outdoor Air by AirLoop

Mechanical Ventilation [m3] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr] Time Above Zero When Unoccupied [hr]
VAV WITH REHEAT 0.10E+10 0.00 0.10E+10 0.22E+09 0.00 0.00 8760.00 0.00
FLR_3_DOAS 91819351.87 266112.37 92085464.25 64690340.46 0.00 0.00 8760.00 0.00


Average Outdoor Air During Occupancy by AirLoop

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr]
VAV WITH REHEAT 32.0163 0.0000 32.0163 6.9969 0.00 0.00 8760.00
FLR_3_DOAS 2.9116 0.0084 2.9200 2.0513 0.00 0.00 8760.00


Outdoor Air Controller Limiting Factors by AirLoop

No Limiting Factor [hr] Limits and Scheduled Limits [hr] Economizer [hr] Exhaust Flow [hr] Mixed Air Flow [hr] High Humidity [hr] Demand Controlled Ventilation [hr] Night Ventilation [hr] Demand Limiting [hr] Energy Management System [hr]
VAV WITH REHEAT 0.00 7397.32 1314.70 0.00 47.98 0.00 0.00 0.00 0.00 0.00
FLR_3_DOAS 0.00 8760.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Average Outdoor Air for Limiting Factors During Occupancy

No Limiting Factor [m3/s] Limits and Scheduled Limits [m3/s] Economizer [m3/s] Exhaust Flow [m3/s] Mixed Air Flow [m3/s] High Humidity [m3/s] Demand Controlled Ventilation [m3/s] Night Ventilation [m3/s] Demand Limiting [m3/s] Energy Management System [m3/s]
VAV WITH REHEAT 0.0000 32.0168 32.0386 0.0000 32.6783 0.0000 0.0000 0.0000 0.0000 0.0000
FLR_3_DOAS 0.0000 2.9116 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000



Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2023-10-16 08:58:31

Surfaces by Class

Total Outdoors
Wall 119 44
Floor 25 0
Roof 33 11
Internal Mass 22 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 30 30
Door 6 6
Glass Door 0 0
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 2
Conditioned Zones 22
Unconditioned Zones 0
Supply Plenums 0
Return Plenums 0


Input Fields

Count
IDF Objects 1306
Defaulted Fields 1181
Fields with Defaults 3945
Autosized Fields 350
Autosizable Fields 402
Autocalculated Fields 280
Autocalculatable Fields 539



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2023-10-16 08:58:31

Annual and Peak Values - Electricity

Electricity Annual Value [GJ] Electricity Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Electricity Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
Electricity:Facility 6900.18 130132.03 06-MAY-05:00 469437.58 22-JUL-18:10
Electricity:Building 2943.68 36656.90 02-JAN-02:10 182730.36 02-JAN-20:10
Electricity:Zone:BASEMENT 315.54 3631.19 02-JAN-02:10 23630.80 02-JAN-20:10
Electricity:SpaceType:GENERAL 2925.41 36182.64 02-JAN-02:10 182063.43 02-JAN-20:10
InteriorLights:Electricity 1174.11 10291.59 02-JAN-02:10 93091.76 02-JAN-20:10
InteriorLights:Electricity:Zone:BASEMENT 165.29 1501.97 02-JAN-02:10 13517.00 02-JAN-20:10
InteriorLights:Electricity:SpaceType:GENERAL 1174.11 10291.59 02-JAN-02:10 93091.76 02-JAN-20:10
LightsWired:InteriorLights:Electricity 1174.11 10291.59 02-JAN-02:10 93091.76 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:BASEMENT 165.29 1501.97 02-JAN-02:10 13517.00 02-JAN-20:10
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL 1174.11 10291.59 02-JAN-02:10 93091.76 02-JAN-20:10
Electricity:Zone:RETAIL_1_FLR_1 18.59 220.70 02-JAN-02:10 1372.90 02-JAN-20:10
InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 8.40 76.37 02-JAN-02:10 687.30 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 8.40 76.37 02-JAN-02:10 687.30 02-JAN-20:10
Electricity:Zone:RETAIL_2_FLR_1 21.53 255.58 02-JAN-02:10 1589.82 02-JAN-20:10
InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 9.73 88.43 02-JAN-02:10 795.89 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 9.73 88.43 02-JAN-02:10 795.89 02-JAN-20:10
Electricity:Zone:MECH_FLR_1 30.66 342.02 02-JAN-02:10 2327.13 02-JAN-20:10
InteriorLights:Electricity:Zone:MECH_FLR_1 18.19 165.30 02-JAN-02:10 1487.69 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:MECH_FLR_1 18.19 165.30 02-JAN-02:10 1487.69 02-JAN-20:10
Electricity:Zone:STORAGE_FLR_1 6.94 81.32 02-JAN-02:10 515.26 02-JAN-20:10
InteriorLights:Electricity:Zone:STORAGE_FLR_1 3.34 30.34 02-JAN-02:10 273.10 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:STORAGE_FLR_1 3.34 30.34 02-JAN-02:10 273.10 02-JAN-20:10
Electricity:Zone:LAUNDRY_FLR_1 72.06 1000.18 02-JAN-02:10 4910.17 02-JAN-20:10
InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 4.13 37.49 02-JAN-02:10 337.37 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 4.13 37.49 02-JAN-02:10 337.37 02-JAN-20:10
Electricity:Zone:CAFE_FLR_1 40.96 445.13 02-JAN-02:10 3142.50 02-JAN-20:10
InteriorLights:Electricity:Zone:CAFE_FLR_1 26.62 241.91 02-JAN-02:10 2177.23 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:CAFE_FLR_1 26.62 241.91 02-JAN-02:10 2177.23 02-JAN-20:10
Electricity:Zone:LOBBY_FLR_1 293.89 3428.00 02-JAN-02:10 21878.53 02-JAN-20:10
InteriorLights:Electricity:Zone:LOBBY_FLR_1 144.90 1316.59 02-JAN-02:10 11849.32 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:LOBBY_FLR_1 144.90 1316.59 02-JAN-02:10 11849.32 02-JAN-20:10
Electricity:Zone:ROOM_1_FLR_3 32.70 383.52 01-JAN-02:10 2308.42 01-JAN-21:10
InteriorLights:Electricity:Zone:ROOM_1_FLR_3 20.41 172.80 01-JAN-02:10 1570.91 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_3 20.41 172.80 01-JAN-02:10 1570.91 01-JAN-19:10
Electricity:Zone:ROOM_2_FLR_3 32.70 383.47 01-JAN-02:10 2308.15 01-JAN-21:10
InteriorLights:Electricity:Zone:ROOM_2_FLR_3 20.41 172.78 01-JAN-02:10 1570.72 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_3 20.41 172.78 01-JAN-02:10 1570.72 01-JAN-19:10
Electricity:Zone:ROOM_3_MULT19_FLR_3 472.46 5984.83 01-JAN-02:10 32482.97 01-JAN-21:10
InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 243.71 2063.36 01-JAN-02:10 18757.86 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 243.71 2063.36 01-JAN-02:10 18757.86 01-JAN-19:10
Electricity:Zone:ROOM_4_MULT19_FLR_3 472.59 5986.46 01-JAN-02:10 32491.86 01-JAN-21:10
InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 243.77 2063.93 01-JAN-02:10 18762.99 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 243.77 2063.93 01-JAN-02:10 18762.99 01-JAN-19:10
Electricity:Zone:ROOM_5_FLR_3 32.70 383.52 01-JAN-02:10 2308.42 01-JAN-21:10
InteriorLights:Electricity:Zone:ROOM_5_FLR_3 20.41 172.80 01-JAN-02:10 1570.91 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_5_FLR_3 20.41 172.80 01-JAN-02:10 1570.91 01-JAN-19:10
Electricity:Zone:ROOM_6_FLR_3 32.70 383.47 01-JAN-02:10 2308.15 01-JAN-21:10
InteriorLights:Electricity:Zone:ROOM_6_FLR_3 20.41 172.78 01-JAN-02:10 1570.72 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_6_FLR_3 20.41 172.78 01-JAN-02:10 1570.72 01-JAN-19:10
Electricity:Zone:CORRIDOR_FLR_3 62.74 570.05 02-JAN-02:10 5130.41 02-JAN-20:10
InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 62.74 570.05 02-JAN-02:10 5130.41 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 62.74 570.05 02-JAN-02:10 5130.41 02-JAN-20:10
Electricity:Zone:ROOM_1_FLR_6 8.18 95.88 01-JAN-02:10 577.11 01-JAN-21:10
InteriorLights:Electricity:Zone:ROOM_1_FLR_6 5.10 43.20 01-JAN-02:10 392.73 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_6 5.10 43.20 01-JAN-02:10 392.73 01-JAN-19:10
Electricity:Zone:ROOM_2_FLR_6 8.17 95.87 01-JAN-02:10 577.04 01-JAN-21:10
InteriorLights:Electricity:Zone:ROOM_2_FLR_6 5.10 43.19 01-JAN-02:10 392.68 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_6 5.10 43.19 01-JAN-02:10 392.68 01-JAN-19:10
Electricity:Zone:ROOM_3_MULT9_FLR_6 55.96 708.92 01-JAN-02:10 3847.72 01-JAN-21:10
InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 28.87 244.41 01-JAN-02:10 2221.93 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 28.87 244.41 01-JAN-02:10 2221.93 01-JAN-19:10
Electricity:Zone:BANQUET_FLR_6 222.61 2674.12 02-JAN-02:10 10571.30 02-JAN-20:10
InteriorLights:Electricity:Zone:BANQUET_FLR_6 46.75 424.82 02-JAN-02:10 3823.39 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:BANQUET_FLR_6 46.75 424.82 02-JAN-02:10 3823.39 02-JAN-20:10
Electricity:Zone:DINING_FLR_6 222.61 2674.12 02-JAN-02:10 10571.30 02-JAN-20:10
InteriorLights:Electricity:Zone:DINING_FLR_6 46.75 424.82 02-JAN-02:10 3823.39 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:DINING_FLR_6 46.75 424.82 02-JAN-02:10 3823.39 02-JAN-20:10
Electricity:Zone:KITCHEN_FLR_6 470.78 6777.71 02-JAN-02:10 19298.76 01-JAN-11:10
InteriorLights:Electricity:Zone:KITCHEN_FLR_6 12.48 113.42 02-JAN-02:10 1020.78 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:KITCHEN_FLR_6 12.48 113.42 02-JAN-02:10 1020.78 02-JAN-20:10
Electricity:Zone:CORRIDOR_FLR_6 16.60 150.83 02-JAN-02:10 1357.44 02-JAN-20:10
InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 16.60 150.83 02-JAN-02:10 1357.44 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 16.60 150.83 02-JAN-02:10 1357.44 02-JAN-20:10
InteriorEquipment:Electricity 1751.30 25891.05 02-JAN-02:10 89674.66 02-JAN-07:10
InteriorEquipment:Electricity:Zone:BASEMENT 150.26 2129.22 02-JAN-02:10 10113.80 02-JAN-20:10
InteriorEquipment:Electricity:SpaceType:GENERAL 1751.30 25891.05 02-JAN-02:10 89674.66 02-JAN-07:10
MiscPlug:InteriorEquipment:Electricity 959.56 15202.41 02-JAN-02:10 59492.27 02-JAN-07:10
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT 150.26 2129.22 02-JAN-02:10 10113.80 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL 959.56 15202.41 02-JAN-02:10 59492.27 02-JAN-07:10
InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 10.19 144.34 02-JAN-02:10 685.60 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 10.19 144.34 02-JAN-02:10 685.60 02-JAN-20:10
InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 11.79 167.14 02-JAN-02:10 793.93 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 11.79 167.14 02-JAN-02:10 793.93 02-JAN-20:10
InteriorEquipment:Electricity:Zone:MECH_FLR_1 12.47 176.73 02-JAN-02:10 839.45 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:MECH_FLR_1 12.47 176.73 02-JAN-02:10 839.45 02-JAN-20:10
InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 3.60 50.98 02-JAN-02:10 242.16 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 3.60 50.98 02-JAN-02:10 242.16 02-JAN-20:10
InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 67.94 962.69 02-JAN-02:10 4572.80 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 67.94 962.69 02-JAN-02:10 4572.80 02-JAN-20:10
InteriorEquipment:Electricity:Zone:CAFE_FLR_1 14.34 203.22 02-JAN-02:10 965.27 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:CAFE_FLR_1 14.34 203.22 02-JAN-02:10 965.27 02-JAN-20:10
InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 149.00 2111.41 02-JAN-02:10 10029.21 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 149.00 2111.41 02-JAN-02:10 10029.21 02-JAN-20:10
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 12.29 210.72 01-JAN-00:10 948.23 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 12.29 210.72 01-JAN-00:10 948.23 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 12.29 210.69 01-JAN-00:10 948.12 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 12.29 210.69 01-JAN-00:10 948.12 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 228.75 3921.46 01-JAN-00:10 17646.57 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 228.75 3921.46 01-JAN-00:10 17646.57 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 228.82 3922.53 01-JAN-00:10 17651.40 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 228.82 3922.53 01-JAN-00:10 17651.40 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 12.29 210.72 01-JAN-00:10 948.23 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 12.29 210.72 01-JAN-00:10 948.23 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 12.29 210.69 01-JAN-00:10 948.12 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 12.29 210.69 01-JAN-00:10 948.12 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 3.07 52.68 01-JAN-00:10 237.06 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 3.07 52.68 01-JAN-00:10 237.06 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 3.07 52.67 01-JAN-00:10 237.03 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 3.07 52.67 01-JAN-00:10 237.03 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 27.10 464.51 01-JAN-00:10 2090.30 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 27.10 464.51 01-JAN-00:10 2090.30 01-JAN-08:10
InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 175.86 2249.30 01-JAN-00:10 6747.90 01-JAN-07:10
Cooking:InteriorEquipment:Electricity 762.04 9746.88 01-JAN-00:10 29240.64 01-JAN-07:10
Cooking:InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 175.86 2249.30 01-JAN-00:10 6747.90 01-JAN-07:10
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL 762.04 9746.88 01-JAN-00:10 29240.64 01-JAN-07:10
InteriorEquipment:Electricity:Zone:DINING_FLR_6 175.86 2249.30 01-JAN-00:10 6747.90 01-JAN-07:10
Cooking:InteriorEquipment:Electricity:Zone:DINING_FLR_6 175.86 2249.30 01-JAN-00:10 6747.90 01-JAN-07:10
InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 440.03 6190.03 01-JAN-00:10 16686.59 01-JAN-07:10
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 410.33 5248.28 01-JAN-00:10 15744.84 01-JAN-07:10
ReachInFreezer:InteriorEquipment:Electricity 16.27 515.92 01-JAN-00:10 515.92 01-JAN-00:10
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 16.27 515.92 01-JAN-00:10 515.92 01-JAN-00:10
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL 16.27 515.92 01-JAN-00:10 515.92 01-JAN-00:10
ReachInRefrigerator:InteriorEquipment:Electricity 13.43 425.83 01-JAN-00:10 425.83 01-JAN-00:10
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 13.43 425.83 01-JAN-00:10 425.83 01-JAN-00:10
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL 13.43 425.83 01-JAN-00:10 425.83 01-JAN-00:10
Refrigeration:Electricity 74.39 1237.96 10-JAN-23:30 3643.15 18-JUL-07:00
Refrigeration:Electricity:Zone:KITCHEN_FLR_6 18.27 261.51 02-JAN-11:30 2271.91 01-JAN-11:10
General:Refrigeration:Electricity 18.27 261.51 02-JAN-11:30 2271.91 01-JAN-11:10
General:Refrigeration:Electricity:Zone:KITCHEN_FLR_6 18.27 261.51 02-JAN-11:30 2271.91 01-JAN-11:10
Electricity:Plant 753.74 2862.54 01-NOV-01:20 183263.24 22-JUL-18:10
LowTempRefrigeration:Refrigeration:Electricity 22.38 0.00 01-JAN-11:10 1901.39 20-APR-10:50
MedTempRefrigeration:Refrigeration:Electricity 33.73 935.87 11-JAN-05:00 1197.79 18-JUL-13:10
Fans:Electricity 1809.73 53944.17 04-OCT-01:40 76877.01 22-JUL-15:20
Fans:Electricity:Zone:ROOM_1_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_2_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_5_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_5_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_6_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_6_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_1_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_2_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Electricity:HVAC 2294.26 55264.56 09-AUG-04:40 95950.27 22-JUL-18:20
ExteriorEquipment:Electricity 679.68 10574.27 02-JAN-02:20 40537.60 02-JAN-07:20
Transformer:ExteriorEquipment:Electricity 32.92 556.27 02-JAN-02:20 1912.91 02-JAN-21:10
ElectricityPurchased:Facility 6900.18 130132.03 06-MAY-05:00 469437.58 22-JUL-18:10
ElectricityPurchased:Plant 6900.18 130132.03 06-MAY-05:00 469437.58 22-JUL-18:10
Cogeneration:ElectricityPurchased 6900.18 130132.03 06-MAY-05:00 469437.58 22-JUL-18:10
General:Cogeneration:ElectricityPurchased 6900.18 130132.03 06-MAY-05:00 469437.58 22-JUL-18:10
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricityNet:Facility 6900.18 130132.03 06-MAY-05:00 469437.58 22-JUL-18:10
ElectricityNet:Plant 6900.18 130132.03 06-MAY-05:00 469437.58 22-JUL-18:10
Cogeneration:ElectricityNet 6900.18 130132.03 06-MAY-05:00 469437.58 22-JUL-18:10
General:Cogeneration:ElectricityNet 6900.18 130132.03 06-MAY-05:00 469437.58 22-JUL-18:10
General:Fans:Electricity 1809.73 53944.17 04-OCT-01:40 76877.01 22-JUL-15:20
ExteriorLights:Electricity 261.73 0.00 01-JAN-08:20 16690.39 01-JAN-00:10
General:ExteriorLights:Electricity 261.73 0.00 01-JAN-08:20 16690.39 01-JAN-00:10
ElevatorLift:ExteriorEquipment:Electricity 616.11 9046.01 01-JAN-00:10 37691.69 01-JAN-07:10
ElevatorLightsFan:ExteriorEquipment:Electricity 30.65 972.00 01-JAN-00:10 972.00 01-JAN-00:10
HeatRecovery:Electricity 451.61 0.00 20-APR-15:20 17755.68 30-APR-17:10
General:HeatRecovery:Electricity 451.61 0.00 20-APR-15:20 17755.68 30-APR-17:10
WaterSystems:Electricity 90.78 1087.06 18-SEP-00:20 4739.90 02-JAN-07:10
Water Heater:WaterSystems:Electricity 90.78 1087.06 18-SEP-00:20 4739.90 02-JAN-07:10
Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Boiler Parasitic:Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:Electricity 474.04 0.00 01-JAN-00:10 167714.04 22-JUL-18:10
General:Cooling:Electricity 474.04 0.00 01-JAN-00:10 167714.04 22-JUL-18:10
Pumps:Electricity 132.81 216.74 11-NOV-08:50 8954.24 22-JUL-18:10
General:Pumps:Electricity 132.81 216.74 11-NOV-08:50 8954.24 22-JUL-18:10
WIRED_LTG_ELECTRICITY 41.33 0.00 01-JAN-00:10 3276.83 02-JAN-20:20


Annual and Peak Values - Natural Gas

Natural Gas Annual Value [GJ] Natural Gas Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Natural Gas Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
NaturalGas:Facility 6754.67 48779.99 21-JUL-23:20 523100.38 11-JAN-17:50
NaturalGas:Building 1788.84 13361.90 02-JAN-02:10 104248.32 02-JAN-18:10
NaturalGas:Zone:LAUNDRY_FLR_1 590.20 8363.49 02-JAN-02:10 39726.58 02-JAN-20:10
NaturalGas:SpaceType:GENERAL 1788.84 13361.90 02-JAN-02:10 104248.32 02-JAN-18:10
InteriorEquipment:NaturalGas 1788.84 13361.90 02-JAN-02:10 104248.32 02-JAN-18:10
InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 590.20 8363.49 02-JAN-02:10 39726.58 02-JAN-20:10
InteriorEquipment:NaturalGas:SpaceType:GENERAL 1788.84 13361.90 02-JAN-02:10 104248.32 02-JAN-18:10
Laundry:InteriorEquipment:NaturalGas 590.20 8363.49 02-JAN-02:10 39726.58 02-JAN-20:10
Laundry:InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 590.20 8363.49 02-JAN-02:10 39726.58 02-JAN-20:10
Laundry:InteriorEquipment:NaturalGas:SpaceType:GENERAL 590.20 8363.49 02-JAN-02:10 39726.58 02-JAN-20:10
NaturalGas:Zone:KITCHEN_FLR_6 1198.64 4998.41 01-JAN-00:10 74976.11 01-JAN-16:10
InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 1198.64 4998.41 01-JAN-00:10 74976.11 01-JAN-16:10
Cooking:InteriorEquipment:NaturalGas 1198.64 4998.41 01-JAN-00:10 74976.11 01-JAN-16:10
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 1198.64 4998.41 01-JAN-00:10 74976.11 01-JAN-16:10
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL 1198.64 4998.41 01-JAN-00:10 74976.11 01-JAN-16:10
NaturalGas:Plant 4965.83 29984.18 22-JUL-23:30 433488.17 11-JAN-17:50
WaterSystems:NaturalGas 3330.89 18467.44 07-JAN-11:10 289920.15 16-FEB-21:40
Water Heater:WaterSystems:NaturalGas 3330.89 18467.44 07-JAN-11:10 289920.15 16-FEB-21:40
Heating:NaturalGas 1634.94 1366.33 14-AUG-21:10 203209.92 10-JAN-09:10
Boiler:Heating:NaturalGas 1634.94 1366.33 14-AUG-21:10 203209.92 10-JAN-09:10


Annual and Peak Values - Cooling

Cooling Annual Value [GJ] Cooling Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Cooling Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
PlantLoopCoolingDemand:Facility 1418.60 0.00 01-JAN-00:10 661295.17 25-JUN-18:20
PlantLoopCoolingDemand:HVAC 1418.60 0.00 01-JAN-00:10 661295.17 25-JUN-18:20
CoolingCoils:PlantLoopCoolingDemand 1418.60 0.00 01-JAN-00:10 661295.17 25-JUN-18:20


Annual and Peak Values - Water

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
Water:Facility 9857.19 0.00 02-JAN-01:10 0.00 02-JAN-21:10
Water:Plant 9857.19 0.00 02-JAN-01:10 0.00 02-JAN-21:10
WaterSystems:Water 9857.19 0.00 02-JAN-01:10 0.00 02-JAN-21:10
Water Heater:WaterSystems:Water 5742.51 0.00 02-JAN-01:10 0.00 02-JAN-19:20
MainsWater:Facility 9857.19 0.00 02-JAN-01:10 0.00 02-JAN-21:10
MainsWater:Plant 9857.19 0.00 02-JAN-01:10 0.00 02-JAN-21:10
WaterSystems:MainsWater 9857.19 0.00 02-JAN-01:10 0.00 02-JAN-21:10
Water Heater:WaterSystems:MainsWater 5742.51 0.00 02-JAN-01:10 0.00 02-JAN-19:20
WaterUse:WaterSystems:Water 4114.69 0.00 02-JAN-01:10 0.00 02-JAN-07:10
WaterUse:WaterSystems:MainsWater 4114.69 0.00 02-JAN-01:10 0.00 02-JAN-07:10


Annual and Peak Values - Other by Weight/Mass

Annual Value [kg] Minimum Value [kg/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [kg/s] Timestamp of Maximum {TIMESTAMP}
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10


Annual and Peak Values - Other Volumetric

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [L] Minimum Value [L] Timestamp of Minimum {TIMESTAMP} Maximum Value [L] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other

Annual Value [GJ] Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
EnergyTransfer:Facility 18918.11 252580.51 18-OCT-13:40 2641870.71 25-JUN-18:10
EnergyTransfer:Building 5354.46 87304.61 10-DEC-15:00 378982.62 22-JUL-18:20
EnergyTransfer:Zone:KITCHEN_FLR_6 732.01 11570.55 11-JAN-04:00 36298.79 23-JUL-10:40
Refrigeration:EnergyTransfer 187.63 3686.45 10-JAN-23:30 10380.41 18-JUL-07:00
Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 93.82 1843.22 10-JAN-23:30 5190.21 18-JUL-07:00
General:Refrigeration:EnergyTransfer 93.82 1843.22 10-JAN-23:30 5190.21 18-JUL-07:00
General:Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 93.82 1843.22 10-JAN-23:30 5190.21 18-JUL-07:00
EnergyTransfer:Plant 5544.61 42620.90 09-FEB-23:20 1532778.63 25-JUN-18:20
LowTempRefrigeration:Refrigeration:EnergyTransfer 25.74 0.00 01-JAN-11:10 2686.44 01-JAN-11:40
MedTempRefrigeration:Refrigeration:EnergyTransfer 68.08 1757.60 11-JAN-05:00 2543.38 18-JUL-13:10
EnergyTransfer:Zone:BASEMENT 440.29 7337.57 08-MAY-11:00 21036.06 13-SEP-18:10
Heating:EnergyTransfer 91.05 0.00 01-JAN-08:30 55022.59 12-JAN-16:10
Heating:EnergyTransfer:Zone:BASEMENT 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer 91.05 0.00 01-JAN-08:30 55022.59 12-JAN-16:10
General:Heating:EnergyTransfer:Zone:BASEMENT 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer 5169.59 77991.50 10-DEC-16:00 375245.57 22-JUL-18:20
Cooling:EnergyTransfer:Zone:BASEMENT 440.29 7337.57 08-MAY-11:00 21036.06 13-SEP-18:10
General:Cooling:EnergyTransfer 5169.59 77991.50 10-DEC-16:00 375245.57 22-JUL-18:20
General:Cooling:EnergyTransfer:Zone:BASEMENT 440.29 7337.57 08-MAY-11:00 21036.06 13-SEP-18:10
EnergyTransfer:Zone:RETAIL_1_FLR_1 33.35 0.01 21-JAN-04:20 4418.15 27-SEP-10:40
Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 0.61 0.00 01-JAN-00:10 525.39 10-JAN-08:00
General:Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 0.61 0.00 01-JAN-00:10 525.39 10-JAN-08:00
Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 32.74 0.00 02-JAN-02:20 4418.15 27-SEP-10:40
General:Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 32.74 0.00 02-JAN-02:20 4418.15 27-SEP-10:40
EnergyTransfer:Zone:RETAIL_2_FLR_1 36.53 289.04 10-DEC-15:50 2158.78 22-JUL-18:10
Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 36.53 289.04 10-DEC-15:50 2158.78 22-JUL-18:10
General:Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 36.53 289.04 10-DEC-15:50 2158.78 22-JUL-18:10
EnergyTransfer:Zone:MECH_FLR_1 23.54 0.12 10-JAN-17:50 1994.41 22-JUL-18:20
Heating:EnergyTransfer:Zone:MECH_FLR_1 0.01 0.00 01-JAN-00:10 187.85 12-JAN-05:00
General:Heating:EnergyTransfer:Zone:MECH_FLR_1 0.01 0.00 01-JAN-00:10 187.85 12-JAN-05:00
Cooling:EnergyTransfer:Zone:MECH_FLR_1 23.53 0.00 09-JAN-02:40 1994.41 22-JUL-18:20
General:Cooling:EnergyTransfer:Zone:MECH_FLR_1 23.53 0.00 09-JAN-02:40 1994.41 22-JUL-18:20
EnergyTransfer:Zone:STORAGE_FLR_1 7.62 0.02 20-DEC-17:30 901.58 22-JUL-18:50
Heating:EnergyTransfer:Zone:STORAGE_FLR_1 0.26 0.00 01-JAN-00:10 231.68 12-JAN-14:00
General:Heating:EnergyTransfer:Zone:STORAGE_FLR_1 0.26 0.00 01-JAN-00:10 231.68 12-JAN-14:00
Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 7.37 0.00 01-JAN-02:40 901.58 22-JUL-18:50
General:Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 7.37 0.00 01-JAN-02:40 901.58 22-JUL-18:50
EnergyTransfer:Zone:LAUNDRY_FLR_1 594.12 9017.10 09-JAN-05:00 36973.20 12-JUN-20:00
Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 594.12 9017.10 09-JAN-05:00 36973.20 12-JUN-20:00
General:Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 594.12 9017.10 09-JAN-05:00 36973.20 12-JUN-20:00
EnergyTransfer:Zone:CAFE_FLR_1 250.65 974.73 10-DEC-16:00 16004.01 12-SEP-15:20
Heating:EnergyTransfer:Zone:CAFE_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:CAFE_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:CAFE_FLR_1 250.65 974.73 10-DEC-16:00 16004.01 12-SEP-15:20
General:Cooling:EnergyTransfer:Zone:CAFE_FLR_1 250.65 974.73 10-DEC-16:00 16004.01 12-SEP-15:20
EnergyTransfer:Zone:LOBBY_FLR_1 872.28 7751.06 10-DEC-16:00 44785.43 14-AUG-18:20
Heating:EnergyTransfer:Zone:LOBBY_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:LOBBY_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 872.28 7751.06 10-DEC-16:00 44785.43 14-AUG-18:20
General:Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 872.28 7751.06 10-DEC-16:00 44785.43 14-AUG-18:20
EnergyTransfer:Zone:ROOM_1_FLR_3 48.01 0.10 01-JAN-10:10 11891.05 13-JUN-18:10
Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 13.01 0.00 01-JAN-08:10 4436.27 27-DEC-09:10
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 13.01 0.00 01-JAN-08:10 4436.27 27-DEC-09:10
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 35.00 0.00 01-JAN-00:10 11891.05 13-JUN-18:10
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 35.00 0.00 01-JAN-00:10 11891.05 13-JUN-18:10
EnergyTransfer:Zone:ROOM_2_FLR_3 43.81 0.01 16-DEC-12:50 11501.34 13-JUN-18:10
Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 16.52 0.00 01-JAN-08:10 4743.82 10-JAN-09:10
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 16.52 0.00 01-JAN-08:10 4743.82 10-JAN-09:10
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 27.29 0.00 01-JAN-00:10 11501.34 13-JUN-18:10
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 27.29 0.00 01-JAN-00:10 11501.34 13-JUN-18:10
EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 427.51 3.27 16-DEC-16:50 64905.00 27-SEP-13:20
Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 0.28 0.00 01-JAN-00:10 6418.64 17-DEC-04:40
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 0.28 0.00 01-JAN-00:10 6418.64 17-DEC-04:40
Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 427.22 0.00 14-DEC-02:50 64905.00 27-SEP-13:20
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 427.22 0.00 14-DEC-02:50 64905.00 27-SEP-13:20
EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 392.16 0.63 20-DEC-16:50 67406.11 13-JUN-18:20
Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 5.37 0.00 01-JAN-00:10 29085.82 11-JAN-16:10
General:Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 5.37 0.00 01-JAN-00:10 29085.82 11-JAN-16:10
Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 386.79 0.00 01-JAN-16:30 67406.11 13-JUN-18:20
General:Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 386.79 0.00 01-JAN-16:30 67406.11 13-JUN-18:20
EnergyTransfer:Zone:ROOM_5_FLR_3 48.54 0.23 28-MAY-03:00 10757.50 23-JUL-08:10
Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 13.02 0.00 01-JAN-08:10 4486.89 12-JAN-16:10
General:Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 13.02 0.00 01-JAN-08:10 4486.89 12-JAN-16:10
Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 35.52 0.00 01-JAN-00:10 10757.50 23-JUL-08:10
General:Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 35.52 0.00 01-JAN-00:10 10757.50 23-JUL-08:10
EnergyTransfer:Zone:ROOM_6_FLR_3 43.60 0.14 21-MAY-01:20 10398.82 23-JUL-08:10
Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 16.42 0.00 01-JAN-08:10 4701.52 10-JAN-16:10
General:Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 16.42 0.00 01-JAN-08:10 4701.52 10-JAN-16:10
Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 27.18 0.00 01-JAN-00:10 10398.82 23-JUL-08:10
General:Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 27.18 0.00 01-JAN-00:10 10398.82 23-JUL-08:10
EnergyTransfer:Zone:CORRIDOR_FLR_3 169.80 0.16 18-DEC-08:00 12607.30 23-JUL-10:40
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 0.39 0.00 01-JAN-00:10 1442.62 10-DEC-16:00
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 0.39 0.00 01-JAN-00:10 1442.62 10-DEC-16:00
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 169.42 0.00 03-JAN-09:20 12607.30 23-JUL-10:40
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 169.42 0.00 03-JAN-09:20 12607.30 23-JUL-10:40
EnergyTransfer:Zone:ROOM_1_FLR_6 15.01 0.02 05-NOV-19:20 3397.62 13-JUN-18:10
Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 5.60 0.00 01-JAN-08:10 1497.87 27-DEC-16:10
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 5.60 0.00 01-JAN-08:10 1497.87 27-DEC-16:10
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 9.42 0.00 01-JAN-00:10 3397.62 13-JUN-18:10
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 9.42 0.00 01-JAN-00:10 3397.62 13-JUN-18:10
EnergyTransfer:Zone:ROOM_2_FLR_6 14.08 0.03 30-JUL-03:30 3245.98 13-JUN-18:10
Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 6.78 0.00 01-JAN-08:10 1564.00 27-DEC-16:10
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 6.78 0.00 01-JAN-08:10 1564.00 27-DEC-16:10
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 7.30 0.00 01-JAN-00:10 3245.98 13-JUN-18:10
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 7.30 0.00 01-JAN-00:10 3245.98 13-JUN-18:10
EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 80.30 0.09 18-MAY-23:30 18432.75 12-SEP-15:10
Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 10.84 0.00 01-JAN-08:10 6166.61 30-DEC-16:10
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 10.84 0.00 01-JAN-08:10 6166.61 30-DEC-16:10
Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 69.46 0.00 01-JAN-00:10 18432.75 12-SEP-15:10
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 69.46 0.00 01-JAN-00:10 18432.75 12-SEP-15:10
EnergyTransfer:Zone:BANQUET_FLR_6 488.54 8082.10 11-JAN-09:30 22243.00 22-JUL-18:10
Heating:EnergyTransfer:Zone:BANQUET_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:BANQUET_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 488.54 8082.10 11-JAN-09:30 22243.00 22-JUL-18:10
General:Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 488.54 8082.10 11-JAN-09:30 22243.00 22-JUL-18:10
EnergyTransfer:Zone:DINING_FLR_6 525.67 9268.81 12-JAN-15:00 23662.83 22-JUL-18:10
Heating:EnergyTransfer:Zone:DINING_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:DINING_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:DINING_FLR_6 525.67 9268.81 12-JAN-15:00 23662.83 22-JUL-18:10
General:Cooling:EnergyTransfer:Zone:DINING_FLR_6 525.67 9268.81 12-JAN-15:00 23662.83 22-JUL-18:10
Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 638.19 9425.11 11-JAN-04:00 31212.90 23-JUL-10:40
General:Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 638.19 9425.11 11-JAN-04:00 31212.90 23-JUL-10:40
EnergyTransfer:Zone:CORRIDOR_FLR_6 67.02 0.02 25-DEC-20:00 7396.15 23-JUL-10:40
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 1.94 0.00 01-JAN-00:10 1747.35 10-JAN-08:00
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 1.94 0.00 01-JAN-00:10 1747.35 10-JAN-08:00
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 65.09 0.00 01-JAN-01:20 7396.15 23-JUL-10:40
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 65.09 0.00 01-JAN-01:20 7396.15 23-JUL-10:40
PlantLoopHeatingDemand:Facility 1930.98 18830.63 21-JUL-22:10 203027.47 10-JAN-08:00
PlantLoopHeatingDemand:Plant 798.36 10164.92 15-AUG-00:20 55889.63 13-FEB-07:10
WaterSystems:PlantLoopHeatingDemand 798.36 10164.92 15-AUG-00:20 55889.63 13-FEB-07:10
General:WaterSystems:PlantLoopHeatingDemand 798.36 10164.92 15-AUG-00:20 55889.63 13-FEB-07:10
EnergyTransfer:HVAC 8019.05 33881.70 13-JUL-07:50 822236.10 25-JUN-18:10
HeatingCoils:EnergyTransfer 1132.61 819.82 14-AUG-21:10 154295.47 10-JAN-09:10
PlantLoopHeatingDemand:HVAC 1132.61 819.82 14-AUG-21:10 154295.47 10-JAN-09:10
HeatingCoils:PlantLoopHeatingDemand 1132.61 819.82 14-AUG-21:10 154295.47 10-JAN-09:10
CoolingCoils:EnergyTransfer 1418.60 0.00 01-JAN-00:10 661295.17 25-JUN-18:20
HeatRecoveryForHeating:EnergyTransfer 5452.10 0.00 20-APR-15:20 640848.05 12-JAN-00:10
HeatRecoveryForCooling:EnergyTransfer 15.73 0.00 01-JAN-00:10 206467.96 25-JUN-18:00
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
WaterSystems:EnergyTransfer 798.36 10164.92 15-AUG-00:20 55889.63 13-FEB-07:10
WaterUse:WaterSystems:EnergyTransfer 798.36 10164.92 15-AUG-00:20 55889.63 13-FEB-07:10
Boilers:EnergyTransfer 1122.99 820.83 14-AUG-21:10 158305.36 10-JAN-09:10
Chillers:EnergyTransfer 1527.70 0.00 01-JAN-00:10 662950.67 25-JUN-18:20
HeatRejection:EnergyTransfer 2001.74 0.00 01-JAN-00:10 824420.51 25-JUN-18:20
General:HeatRejection:EnergyTransfer 2001.74 0.00 01-JAN-00:10 824420.51 25-JUN-18:20



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2023-10-16 08:58:31

Annual Building Sensible Heat Gain Components

HVAC Zone Eq & Other Sensible Air Heating [GJ] HVAC Zone Eq & Other Sensible Air Cooling [GJ] HVAC Terminal Unit Sensible Air Heating [GJ] HVAC Terminal Unit Sensible Air Cooling [GJ] HVAC Input Heated Surface Heating [GJ] HVAC Input Cooled Surface Cooling [GJ] People Sensible Heat Addition [GJ] Lights Sensible Heat Addition [GJ] Equipment Sensible Heat Addition [GJ] Window Heat Addition [GJ] Interzone Air Transfer Heat Addition [GJ] Infiltration Heat Addition [GJ] Opaque Surface Conduction and Other Heat Addition [GJ] Equipment Sensible Heat Removal [GJ] Window Heat Removal [GJ] Interzone Air Transfer Heat Removal [GJ] Infiltration Heat Removal [GJ] Opaque Surface Conduction and Other Heat Removal [GJ]
BASEMENT 0.000 0.000 0.000 -440.291 0.000 0.000 158.390 165.288 150.255 0.000 0.000 0.000 0.001 0.000 0.000 0.000 0.000 -33.642
RETAIL_1_FLR_1 0.000 0.000 0.609 -32.739 0.000 0.000 16.175 8.404 10.186 23.766 0.000 0.013 0.000 0.000 -11.216 0.000 -4.592 -10.606
RETAIL_2_FLR_1 0.000 0.000 0.000 -36.532 0.000 0.000 18.673 9.732 11.795 0.000 0.000 0.005 0.000 0.000 0.000 0.000 -1.778 -1.895
MECH_FLR_1 0.000 0.000 0.012 -23.529 0.000 0.000 3.958 18.192 12.471 0.000 0.000 0.013 0.000 0.000 0.000 0.000 -4.192 -6.924
STORAGE_FLR_1 0.000 0.000 0.256 -7.367 0.000 0.000 3.046 3.340 3.598 0.000 0.000 0.007 0.000 0.000 0.000 0.000 -2.417 -0.462
LAUNDRY_FLR_1 0.000 0.000 0.000 -594.117 0.000 0.000 12.193 4.125 658.131 0.000 0.000 0.017 0.000 0.000 0.000 0.000 -5.921 -74.428
CAFE_FLR_1 0.000 0.000 0.000 -250.649 0.000 0.000 212.375 26.624 14.341 66.580 0.000 0.029 0.000 0.000 -31.627 0.000 -10.162 -27.512
LOBBY_FLR_1 0.000 0.000 0.000 -872.284 0.000 0.000 628.258 144.896 148.998 88.126 0.000 0.088 0.000 0.000 -42.306 0.000 -29.136 -66.640
ROOM_1_FLR_3 17.922 -25.889 0.000 -14.022 0.000 0.000 9.748 20.410 12.292 43.873 0.000 0.026 0.000 0.000 -26.094 0.000 -11.452 -26.814
ROOM_2_FLR_3 21.953 -19.024 0.000 -13.694 0.000 0.000 9.778 20.407 12.291 30.490 0.000 0.026 0.000 0.000 -26.272 0.000 -11.324 -24.631
ROOM_3_MULT19_FLR_3 0.867 -197.878 0.000 -229.928 0.000 0.000 0.000 243.708 228.754 275.771 0.000 0.060 0.002 0.000 -155.744 0.000 -79.975 -85.634
ROOM_4_MULT19_FLR_3 24.437 -216.247 0.000 -189.606 0.000 0.000 185.223 243.774 228.817 72.265 0.000 0.248 0.000 0.000 -146.923 0.000 -67.223 -134.765
ROOM_5_FLR_3 17.884 -26.272 0.000 -14.113 0.000 0.000 9.739 20.410 12.292 44.320 0.000 0.026 0.000 0.000 -25.634 0.000 -11.483 -27.170
ROOM_6_FLR_3 21.799 -18.694 0.000 -13.858 0.000 0.000 9.764 20.407 12.291 30.668 0.000 0.026 0.000 0.000 -25.608 0.000 -11.377 -25.418
CORRIDOR_FLR_3 0.000 0.000 0.387 -169.416 0.000 0.000 124.920 62.736 0.000 40.788 0.000 0.035 0.000 0.000 -32.273 0.000 -12.972 -14.204
ROOM_1_FLR_6 6.978 -7.317 0.000 -3.479 0.000 0.000 2.440 5.102 3.073 10.878 0.000 0.006 0.000 0.000 -6.462 0.000 -2.885 -8.334
ROOM_2_FLR_6 8.297 -5.409 0.000 -3.406 0.000 0.000 2.447 5.102 3.073 7.538 0.000 0.007 0.000 0.000 -6.498 0.000 -2.857 -8.293
ROOM_3_MULT9_FLR_6 16.836 -52.392 0.000 -23.057 0.000 0.000 21.858 28.868 27.097 60.404 0.000 0.038 0.000 0.000 -30.695 0.000 -14.120 -34.836
BANQUET_FLR_6 0.000 0.000 0.000 -488.538 0.000 0.000 359.186 46.753 175.857 8.263 0.000 0.017 0.000 0.000 -17.241 0.000 -6.857 -77.440
DINING_FLR_6 0.000 0.000 0.000 -525.675 0.000 0.000 357.639 46.753 175.857 8.075 0.000 0.016 0.000 0.000 -17.637 0.000 -6.895 -38.133
KITCHEN_FLR_6 0.000 0.000 0.000 -638.184 0.000 0.000 30.601 12.482 556.656 21.086 0.000 0.004 36.505 0.000 -12.384 0.000 -6.766 0.000
CORRIDOR_FLR_6 0.000 0.000 1.936 -65.088 0.000 0.000 33.105 16.599 0.000 20.094 0.000 0.015 13.440 0.000 -14.344 0.000 -5.757 -0.001
Total Facility 136.974 -569.123 3.200 -4649.575 0.000 0.000 2209.516 1174.112 2458.123 852.986 0.000 0.724 49.948 0.000 -628.959 0.000 -310.143 -727.782


Peak Cooling Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
BASEMENT 13-SEP-18:02 0.00 0.00 0.00 -21180.23 0.00 0.00 6161.73 12015.03 9581.50 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -6578.02
RETAIL_1_FLR_1 12-SEP-10:35 0.00 0.00 0.00 -4500.07 0.00 0.00 175.58 190.92 252.59 5792.49 0.00 0.00 0.00 0.00 -0.00 0.00 -41.95 -1869.56
RETAIL_2_FLR_1 22-JUL-18:07 0.00 0.00 0.00 -2163.17 0.00 0.00 621.92 619.03 668.57 0.00 0.00 38.67 214.98 0.00 -0.00 0.00 0.00 0.00
MECH_FLR_1 22-JUL-18:20 0.00 0.00 0.00 -1995.49 0.00 0.00 131.53 1157.09 706.90 0.00 0.00 89.61 0.00 0.00 -0.00 0.00 0.00 -89.64
STORAGE_FLR_1 22-JUL-18:25 0.00 0.00 0.00 -902.39 0.00 0.00 101.17 212.41 203.92 0.00 0.00 50.80 334.08 0.00 -0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 12-JUN-20:00 0.00 0.00 0.00 -36974.87 0.00 0.00 419.86 337.37 44299.38 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -24.28 -8057.46
CAFE_FLR_1 23-SEP-10:35 0.00 0.00 0.00 -16213.68 0.00 0.00 3483.25 604.78 355.63 16652.41 0.00 0.00 0.00 0.00 -0.00 0.00 -80.61 -4801.79
LOBBY_FLR_1 14-AUG-18:20 0.00 0.00 0.00 -44789.97 0.00 0.00 24441.66 10532.73 9501.36 1335.46 0.00 362.23 0.00 0.00 -0.00 0.00 0.00 -1383.46
ROOM_1_FLR_3 21-MAY-15:01 0.00 -14202.45 0.00 -651.38 0.00 0.00 130.72 518.40 305.54 10306.36 0.00 0.00 4115.55 0.00 -0.00 0.00 -522.75 0.00
ROOM_2_FLR_3 21-MAY-15:01 0.00 -12718.50 0.00 -651.72 0.00 0.00 130.71 518.34 305.51 9258.32 0.00 0.00 3689.39 0.00 -0.00 0.00 -532.06 0.00
ROOM_3_MULT19_FLR_3 27-SEP-13:20 0.00 -54864.40 0.00 -10035.37 0.00 0.00 0.00 5252.20 5097.90 76654.87 0.00 0.00 0.00 0.00 -0.00 0.00 -294.87 -21810.34
ROOM_4_MULT19_FLR_3 12-JUN-18:02 0.00 -67228.01 0.00 -10247.90 0.00 0.00 6374.83 16699.06 9610.21 17268.03 0.00 393.75 27130.02 0.00 -0.00 0.00 0.00 0.00
ROOM_5_FLR_3 21-MAY-15:01 0.00 -12770.16 0.00 -643.89 0.00 0.00 130.72 518.40 305.54 2834.93 0.00 0.00 10133.38 0.00 -0.00 0.00 -508.93 0.00
ROOM_6_FLR_3 21-MAY-15:01 0.00 -11522.96 0.00 -643.77 0.00 0.00 130.72 518.34 305.51 1793.11 0.00 0.00 9936.21 0.00 -0.00 0.00 -517.15 0.00
CORRIDOR_FLR_3 23-JUL-10:35 0.00 0.00 0.00 -12651.06 0.00 0.00 2044.88 1710.14 0.00 6836.10 0.00 0.00 2070.82 0.00 -0.00 0.00 -10.88 0.00
ROOM_1_FLR_6 21-MAY-15:01 0.00 -3807.75 0.00 -163.12 0.00 0.00 32.68 129.60 76.39 2554.55 0.00 0.00 1329.35 0.00 -0.00 0.00 -151.70 0.00
ROOM_2_FLR_6 21-MAY-15:01 0.00 -3388.80 0.00 -163.31 0.00 0.00 32.68 129.58 76.38 2293.80 0.00 0.00 1174.81 0.00 -0.00 0.00 -155.14 0.00
ROOM_3_MULT9_FLR_6 07-OCT-15:02 0.00 -21089.06 0.00 -1041.98 0.00 0.00 294.11 733.24 673.54 8849.62 0.00 0.00 12322.25 0.00 -0.00 0.00 -741.71 0.00
BANQUET_FLR_6 22-JUL-18:10 0.00 0.00 0.00 -22256.39 0.00 0.00 11938.16 2973.75 6747.90 1966.04 0.00 128.48 0.00 0.00 -0.00 0.00 0.00 -1497.94
DINING_FLR_6 22-JUL-18:10 0.00 0.00 0.00 -23677.46 0.00 0.00 11862.93 2973.75 6747.90 1946.73 0.00 126.56 19.59 0.00 -0.00 0.00 0.00 0.00
KITCHEN_FLR_6 23-JUL-10:35 0.00 0.00 0.00 -31216.92 0.00 0.00 464.15 340.26 24459.16 3966.47 0.00 0.00 2033.12 0.00 -0.00 0.00 -46.24 0.00
CORRIDOR_FLR_6 23-JUL-10:35 0.00 0.00 0.00 -7606.36 0.00 0.00 545.54 452.48 0.00 3363.39 0.00 0.00 3247.73 0.00 -0.00 0.00 -2.77 0.00
Total Facility 22-JUL-18:02 0.00 -164360.61 0.00 -233619.62 0.00 0.00 72266.65 82807.27 115371.52 67142.94 0.00 4888.82 55503.03 0.00 0.00 0.00 0.00 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
BASEMENT - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 10-JAN-08:00 0.00 0.00 525.32 0.00 0.00 0.00 371.28 381.83 433.01 0.00 0.00 0.00 0.00 0.00 -1081.88 0.00 -336.61 -292.95
RETAIL_2_FLR_1 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
MECH_FLR_1 12-JAN-05:00 0.00 0.00 187.86 0.00 0.00 0.00 197.30 165.30 176.73 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -267.09 -460.09
STORAGE_FLR_1 12-JAN-14:00 0.00 0.00 231.68 0.00 0.00 0.00 33.76 75.86 89.22 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -146.85 -283.67
LAUNDRY_FLR_1 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CAFE_FLR_1 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
LOBBY_FLR_1 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_3 27-DEC-16:02 6469.03 290.03 0.00 -290.03 0.00 0.00 293.99 439.85 273.93 0.00 0.00 0.00 0.00 0.00 -1618.93 0.00 -477.01 -5380.86
ROOM_2_FLR_3 11-JAN-09:02 6297.35 286.35 0.00 -286.35 0.00 0.00 108.89 691.12 452.99 0.00 0.00 0.00 0.00 0.00 -1775.75 0.00 -686.01 -5088.59
ROOM_3_MULT19_FLR_3 17-DEC-04:40 6418.49 3428.50 0.00 -3428.50 0.00 0.00 0.00 2063.36 3921.46 0.00 0.00 0.00 2089.25 0.00 -11676.88 0.00 -2815.68 0.00
ROOM_4_MULT19_FLR_3 11-JAN-16:01 33490.46 4174.59 0.00 -4174.59 0.00 0.00 5471.13 5253.64 5099.29 0.00 0.00 0.00 0.00 0.00 -9754.09 0.00 -3406.21 -36154.22
ROOM_5_FLR_3 27-DEC-16:02 6273.83 289.04 0.00 -289.04 0.00 0.00 293.99 439.85 273.93 0.00 0.00 0.00 0.00 0.00 -1619.65 0.00 -476.63 -5185.33
ROOM_6_FLR_3 10-JAN-16:01 6185.74 281.08 0.00 -281.08 0.00 0.00 293.99 439.80 273.90 0.00 0.00 0.00 0.00 0.00 -2009.84 0.00 -656.73 -4526.87
CORRIDOR_FLR_3 10-DEC-16:00 0.00 0.00 1442.61 0.00 0.00 0.00 1388.53 1140.09 0.00 0.00 0.00 0.00 0.00 0.00 -1945.04 0.00 -591.69 -1434.51
ROOM_1_FLR_6 27-DEC-16:02 1958.86 72.80 0.00 -72.80 0.00 0.00 73.50 109.96 68.48 0.00 0.00 0.00 0.00 0.00 -399.09 0.00 -119.82 -1691.90
ROOM_2_FLR_6 27-DEC-16:02 1900.89 72.00 0.00 -72.00 0.00 0.00 73.50 109.95 68.48 0.00 0.00 0.00 0.00 0.00 -395.74 0.00 -119.51 -1637.56
ROOM_3_MULT9_FLR_6 27-DEC-16:02 9670.10 472.80 0.00 -472.80 0.00 0.00 661.47 622.14 603.86 0.00 0.00 0.00 0.00 0.00 -1900.33 0.00 -553.17 -9104.07
BANQUET_FLR_6 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
DINING_FLR_6 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
KITCHEN_FLR_6 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6 10-JAN-08:00 0.00 0.00 1747.05 0.00 0.00 0.00 739.07 754.13 0.00 0.00 0.00 0.00 0.00 0.00 -1386.77 0.00 -429.52 -1423.96
Total Facility 10-DEC-16:02 -9247.18 86435.84 2931.67 -86435.84 0.00 0.00 37190.68 25732.27 75340.19 0.00 0.00 0.00 0.00 0.00 -34302.55 0.00 -11769.87 -85875.20



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2023-10-16 08:58:31

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow - Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
VAV WITH REHEAT 22.6738 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 22.5604 0.0000 1.0000 Not calculated 0.0000 0.0000    
FLR_3_DOAS 2.0513 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 2.0513 0.0000 1.0000 Not calculated 0.0000 0.0000    


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
VAV WITH REHEAT 22.5604 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 22.5604 0.0000 1.0000 Not calculated 0.0000 0.0000    
FLR_3_DOAS 2.0513 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 2.0513 0.0000 1.0000 Not calculated 0.0000 0.0000    


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [m3/s-person] Zone Population - Pz Area Outdoor Air Rate - Ra [m3/s-m2] Zone Floor Area - Az [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [m3/s]
BASEMENT VAV WITH REHEAT 0.000000 106.4990 0.000432 1978.83 0.0000 1.0000 0.0000 1.000 0.0000
RETAIL_1_FLR_1 VAV WITH REHEAT 0.000000 10.8290 0.001181 67.07 0.0000 1.0000 0.0000 1.000 0.0000
RETAIL_2_FLR_1 VAV WITH REHEAT 0.000000 12.5400 0.001181 77.67 0.0000 1.0000 0.0000 1.000 0.0000
MECH_FLR_1 VAV WITH REHEAT 0.000000 2.6520 0.000000 164.24 0.0000 1.0000 0.0000 1.000 0.0000
STORAGE_FLR_1 VAV WITH REHEAT 0.000000 2.0400 0.000610 94.76 0.0000 1.0000 0.0000 1.000 0.0000
LAUNDRY_FLR_1 VAV WITH REHEAT 0.000000 8.4000 0.000000 78.04 0.0000 1.0000 0.0000 1.000 0.0000
CAFE_FLR_1 VAV WITH REHEAT 0.000000 142.3000 0.003581 188.86 0.0000 1.0000 0.0000 1.000 0.0000
LOBBY_FLR_1 VAV WITH REHEAT 0.000000 422.4350 0.001448 1308.19 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_1_FLR_3 FLR_3_DOAS 0.000000 6.0000 0.000396 156.09 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_2_FLR_3 FLR_3_DOAS 0.000000 6.0000 0.000396 156.07 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_3_MULT19_FLR_3 FLR_3_DOAS 0.000000 114.0000 0.000449 1863.81 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_4_MULT19_FLR_3 FLR_3_DOAS 0.000000 114.0000 0.000449 1864.32 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_5_FLR_3 FLR_3_DOAS 0.000000 6.0000 0.000396 156.09 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_6_FLR_3 FLR_3_DOAS 0.000000 6.0000 0.000396 156.07 0.0000 1.0000 0.0000 1.000 0.0000
CORRIDOR_FLR_3 VAV WITH REHEAT 0.000000 83.8280 0.000305 1557.62 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_1_FLR_6 FLR_3_DOAS 0.000000 1.5000 0.000396 39.02 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_2_FLR_6 FLR_3_DOAS 0.000000 1.5000 0.000396 39.02 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_3_MULT9_FLR_6 FLR_3_DOAS 0.000000 13.5000 0.000449 220.77 0.0000 1.0000 0.0000 1.000 0.0000
BANQUET_FLR_6 VAV WITH REHEAT 0.000000 249.8960 0.003581 331.66 0.0000 1.0000 0.0000 1.000 0.0000
DINING_FLR_6 VAV WITH REHEAT 0.000000 249.8960 0.003581 331.66 0.0000 1.0000 0.0000 1.000 0.0000
KITCHEN_FLR_6 VAV WITH REHEAT 0.000000 22.2380 0.003556 103.30 0.0000 1.0000 0.0000 1.000 0.0000
CORRIDOR_FLR_6 VAV WITH REHEAT 0.000000 22.1800 0.000305 412.12 0.0000 1.0000 0.0000 1.000 0.0000


System Ventilation Parameters

People Outdoor Air Rate - Rp [m3/s-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [m3/s-m2] Sum of Zone Floor Area - Az-sum [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Outdoor Airflow - Voz-htg [m3/s]
VAV WITH REHEAT   0.00 0.001045 6694.0231 0.0000 0.0000 0.0000
FLR_3_DOAS   0.00 0.000441 4651.2638 0.0000 0.0000 0.0000


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
BASEMENT VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.4796 2.4796 2.4672 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
RETAIL_1_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.4749 0.4749 0.4726 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
RETAIL_2_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.2375 0.2375 0.2363 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
MECH_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.2228 0.2228 0.2217 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
STORAGE_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1094 0.1094 0.1089 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LAUNDRY_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 3.2823 3.2823 3.2659 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CAFE_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.8720 1.8720 1.8627 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LOBBY_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 5.1653 5.1653 5.1395 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_1_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_2_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_3_MULT19_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.8371 0.8371 0.8371 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_4_MULT19_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.8373 0.8373 0.8373 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_5_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_6_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORRIDOR_FLR_3 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.2511 1.2511 1.2449 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_1_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0154 0.0154 0.0154 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_2_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0154 0.0154 0.0154 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_3_MULT9_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0992 0.0992 0.0992 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
BANQUET_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.1925 2.1925 2.1815 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DINING_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.2999 2.2999 2.2884 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
KITCHEN_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.3152 2.3152 2.3036 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORRIDOR_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.7712 0.7712 0.7673 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Zone Ventilation Efficiency - Evz-min
VAV WITH REHEAT 22.6738 22.5604 22.6738 22.5604 0.0000 1.0000
FLR_3_DOAS 2.0513 2.0513 2.0513 2.0513 0.0000 1.0000


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Heating - Voz-htg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
BASEMENT VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.4672 2.4672 2.4672 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
RETAIL_1_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.4726 0.4726 0.4726 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
RETAIL_2_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.2363 0.2363 0.2363 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
MECH_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.2217 0.2217 0.2217 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
STORAGE_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1089 0.1089 0.1089 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LAUNDRY_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 3.2659 3.2659 3.2659 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CAFE_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.8627 1.8627 1.8627 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LOBBY_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 5.1395 5.1395 5.1395 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_1_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_2_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_3_MULT19_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.8371 0.8371 0.8371 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_4_MULT19_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.8373 0.8373 0.8373 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_5_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_6_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORRIDOR_FLR_3 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.2449 1.2449 1.2449 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_1_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0154 0.0154 0.0154 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_2_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0154 0.0154 0.0154 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_3_MULT9_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0992 0.0992 0.0992 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
BANQUET_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.1815 2.1815 2.1815 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DINING_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.2884 2.2884 2.2884 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
KITCHEN_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.3036 2.3036 2.3036 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORRIDOR_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.7673 0.7673 0.7673 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Zone Ventilation Efficiency - Evz-min
VAV WITH REHEAT 22.5604 22.5604 22.5604 22.5604 0.0000 1.0000
FLR_3_DOAS 2.0513 2.0513 2.0513 2.0513 0.0000 1.0000



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2023-10-16 08:58:31

Sec1.1A-General Information

Data
Weather File RUNPERIOD 1 ** William R Fairchild WA USA TMY3 WMO#=727885
Total gross floor area [m2] 11345.29
Principal Heating Source Natural Gas


EAp2-1. Space Usage Type

Space Area [m2] Regularly Occupied Area [m2] Unconditioned Area [m2] Typical Hours/Week in Operation [hr/wk]
BASEMENT 1978.83 1978.83 0.00 168.00
RETAIL_1_FLR_1 67.07 67.07 0.00 168.00
RETAIL_2_FLR_1 77.67 77.67 0.00 168.00
MECH_FLR_1 164.24 164.24 0.00 168.00
STORAGE_FLR_1 94.76 94.76 0.00 168.00
LAUNDRY_FLR_1 78.04 78.04 0.00 168.00
CAFE_FLR_1 188.86 188.86 0.00 168.00
LOBBY_FLR_1 1308.19 1308.19 0.00 168.00
ROOM_1_FLR_3 39.02 39.02 0.00 168.00
ROOM_2_FLR_3 39.02 39.02 0.00 168.00
ROOM_3_MULT19_FLR_3 24.52 24.52 0.00 0.00
ROOM_4_MULT19_FLR_3 24.53 24.53 0.00 168.00
ROOM_5_FLR_3 39.02 39.02 0.00 168.00
ROOM_6_FLR_3 39.02 39.02 0.00 168.00
CORRIDOR_FLR_3 389.40 389.40 0.00 168.00
ROOM_1_FLR_6 39.02 39.02 0.00 168.00
ROOM_2_FLR_6 39.02 39.02 0.00 168.00
ROOM_3_MULT9_FLR_6 24.53 24.53 0.00 168.00
BANQUET_FLR_6 331.66 331.66 0.00 168.00
DINING_FLR_6 331.66 331.66 0.00 168.00
KITCHEN_FLR_6 103.30 103.30 0.00 168.00
CORRIDOR_FLR_6 412.12 412.12 0.00 168.00
Totals 11345.29 11345.29 0.00  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 24.50
Number of hours cooling loads not met 5.67
Number of hours not met 30.17


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electricity Energy Use [GJ] Electricity Demand [W] Natural Gas Energy Use [GJ] Natural Gas Demand [W] Gasoline Use [GJ] Gasoline Demand [W] Diesel Use [GJ] Diesel Demand [W] Coal Use [GJ] Coal Demand [W] Fuel Oil No 1 Use [GJ] Fuel Oil No 1 Demand [W] Fuel Oil No 2 Use [GJ] Fuel Oil No 2 Demand [W] Propane Use [GJ] Propane Demand [W] Other Fuel 1 Use [GJ] Other Fuel 1 Demand [W] Other Fuel 2 Use [GJ] Other Fuel 2 Demand [W] District Cooling Use [GJ] District Cooling Demand [W] District Heating Use [GJ] District Heating Demand [W]
Heating -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heating -- Boiler 0.00 0.00 1634.94 203209.92 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heating -- Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling -- General 474.04 167714.04 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting -- LightsWired 1174.11 93091.76 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting -- General 261.73 16690.39 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- MiscPlug 959.56 59492.27 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- Cooking 762.04 29240.64 1198.64 74976.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- ReachInFreezer 16.27 515.92 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- ReachInRefrigerator 13.43 425.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- Laundry 0.00 0.00 590.20 39726.58 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- Transformer 32.92 1912.91 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- ElevatorLift 616.11 37691.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- ElevatorLightsFan 30.65 972.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- General 1809.73 76877.01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps -- General 132.81 8954.24 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery -- General 451.61 17755.68 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- Water Heater 90.78 4739.90 3330.89 289920.15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- General 18.27 2271.91 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- LowTempRefrigeration 22.38 1901.39 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- MedTempRefrigeration 33.73 1197.79 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


EAp2-6. Energy Use Summary

Process Subtotal [GJ] Total Energy Use [GJ]
Electricity 1825.68 6900.18
Natural Gas 1788.84 6754.67
Additional 0.00 0.00
Total 3614.52 13654.84


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [GJ]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [MJ/m2]
Interior Lighting (All) 103.49
Space Heating 0.00
Space Cooling 41.78
Fans (All) 159.51
Service Water Heating 8.00
Receptacle Equipment 154.36
Miscellaneous (All) 608.20
Subtotal 608.20


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [MJ/m2]
Space Heating 144.11
Service Water Heating 293.59
Miscellaneous (All) 595.37
Subtotal 595.37


EAp2-17c. Energy Use Intensity - Additional

Additional [MJ/m2]
Subtotal 0.00
Miscellaneous 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting (All) 8.60
Space Heating 11.97
Space Cooling 3.47
Fans (All) 13.25
Service Water Heating 25.06
Receptacle Equipment 25.93
Miscellaneous 11.72


Schedules-Equivalent Full Load Hours (Schedule Type=Fraction)

Equivalent Full Load Hours of Operation Per Year [hr] Hours > 1% [hr]
LTG_SCH_KITCHEN 3061. 8760.
LTG_SCH_DINING 3061. 8760.
LTG_SCH_BASEMENT 2655. 8760.
LTG_SCH_LOBBY 3061. 8760.
LTG_SCH_STORAGE 1339. 8760.
LTG_SCH_MECHANIC 3061. 8760.
LTG_SCH_LAUNDRY 2678. 8760.
LTG_SCH_GUESTROOM 3599. 8760.
LTG_SCH_CORRIDOR 3061. 8760.
LTG_SCH_RETAIL 2678. 8760.
WALKIN_OCC_LGHT_SCH_1 3061. 8760.
EXTERIOR_LTG_SCH 4380. 4380.
BASEMENT_EQUIP_SCH 3924. 8760.
BLDG_EQUIP_SCH 3924. 8760.
GUESTROOM_EQP_SCH_BASE 3239. 8760.
GUESTROOM_EQP_SCH_ADVA 2762. 8760.
LOBBY_EQP_SCH 3292. 8760.
OFFICE_EQP_SCH 4941. 8760.
EMPLOYEELOUNGE_EQP_SCH 4044. 8760.
LAUNDRYROOM_EQP_ELEC_SCH 2920. 2920.
LAUNDRYROOM_EQP_GAS_SCH 2920. 2920.
MEETINGROOM_EQP_SCH 1336. 4745.
EXERCISEROOM_EQP_SCH 3832. 5840.
KITCHEN_ELEC_EQUIP_SCH 2172. 8760.
KITCHEN_GAS_EQUIP_SCH 1332. 8760.
KITCHEN_EXHAUST_SCH 6205. 6205.
BLDG_ELEVATORS 2270. 8760.
ELEV_LIGHT_FAN_SCH_24_7 8760. 8760.
ELEV_LIGHT_FAN_SCH_ADD_DF 2154. 8760.
BLDG_OCC_SCH 5026. 8760.
GUESTROOM_OCC_SCH 5515. 8760.
LOBBY_OCC_SCH 2304. 8760.
OFFICE_OCC_SCH 3954. 8760.
EMPLOYEELOUNGE_OCC_SCH 948. 5475.
MEETINGROOM_OCC_SCH 1168. 4745.
LAUNDRYROOM_OCC_SCH 427. 2920.
EXERCISEROOM_OCC_SCH 5292. 5840.
INFIL_SCH 8760. 8760.
INFIL_HALF_ON_SCH 4380. 8760.
INFIL_QUARTER_ON_SCH 2190. 8760.
LAUNDRY_SWH_SCH 2555. 2555.
BLDG_SWH_SCH 3301. 8760.
GUESTROOM_SWH_SCH 2899. 8760.
LAUNDRYROOM_SWH_SCH 2920. 2920.
EXTERIOR_LGT_ALWAYS_ON 8760. 8760.
ALWAYS_ON 8760. 8760.
ALWAYS_OFF 0. 0.
FAN_SCH 8760. 8760.
REHEATCOILAVAILSCHED 8760. 8760.
COOLINGCOILAVAILSCHED 8760. 8760.
OCC_GUESTROOM_VENT_CTRL_30MIN 6570. 6570.
OCC_GUESTROOM_VENT_CTRL_20MIN 6327. 6327.
VAC_GUESTROOM_VENTILATION_SCHEDULE 365. 365.
MINOA_MOTORIZEDDAMPER_SCHED 8760. 8760.
MINOA_SCHED 8760. 8760.
WORK_EFF_SCH 0. 0.
ROOM_1_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_1_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_2_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_2_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_5_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_5_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_6_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_6_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_1_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_1_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_2_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_2_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
KITCHEN_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
KITCHEN_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
KITCHEN_FLR_6_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED 2774. 8760.
FLR_3_DOAS_OAMINOAFRACSCHEDULE 8760. 8760.
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE 0. 0.
LAUNDRY_FLR_1 EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE 0. 0.
SLIDING_DOORS_VENTILATION_AVAILABILITY_SCH 3285. 3285.


Schedules-SetPoints (Schedule Type=Temperature)

First Object Used Month Assumed 11am First Wednesday [C] Days with Same 11am Value 11pm First Wednesday [C] Days with Same 11pm Value
VACGUESTROOM_HTGSP_SCH VACGUESTROOM THERMOSTAT DUAL SP CONTROL January 18.89 365 18.89 365
VACGUESTROOM_CLGSP_SCH VACGUESTROOM THERMOSTAT DUAL SP CONTROL July 23.33 365 23.33 365
OBCRESET_S_OCCGUESTROOM_HTGSP_SCH_30MIN S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL January 21.11 365 21.11 365
OBCRESET_S_OCCGUESTROOM_CLGSP_SCH_30MIN S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL July 23.33 365 21.11 365
OBCRESET_N_OCCGUESTROOM_HTGSP_SCH_30MIN N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL January 21.11 365 21.11 365
OBCRESET_N_OCCGUESTROOM_CLGSP_SCH_30MIN N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL July 23.33 365 21.11 365
HTGSETP_SCH BASEMENT DUAL SP CONTROL January 21.00 365 21.00 365
CLGSETP_SCH BASEMENT DUAL SP CONTROL July 24.00 365 24.00 365



Table of Contents

Report: Annual Thermal Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 08:58:31

Heat Index Hours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
BASEMENT 8760.00 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 8760.00 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 8760.00 0.00 0.00 0.00 0.00
MECH_FLR_1 8760.00 0.00 0.00 0.00 0.00
STORAGE_FLR_1 8760.00 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 8760.00 0.00 0.00 0.00 0.00
CAFE_FLR_1 8760.00 0.00 0.00 0.00 0.00
LOBBY_FLR_1 8760.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_5_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_6_FLR_3 8760.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 8760.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_6 8760.00 0.00 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 8760.00 0.00 0.00 0.00 0.00
BANQUET_FLR_6 8760.00 0.00 0.00 0.00 0.00
DINING_FLR_6 8760.00 0.00 0.00 0.00 0.00
KITCHEN_FLR_6 8760.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6 8760.00 0.00 0.00 0.00 0.00
Min 8760.00 0.00 0.00 0.00 0.00
Max 8760.00 0.00 0.00 0.00 0.00
Average 8760.00 0.00 0.00 0.00 0.00
Sum 192720.00 0.00 0.00 0.00 0.00


Heat Index OccupantHours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
BASEMENT 529331.00 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 50179.00 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 59156.00 0.00 0.00 0.00 0.00
MECH_FLR_1 8977.00 0.00 0.00 0.00 0.00
STORAGE_FLR_1 5588.00 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 37203.00 0.00 0.00 0.00 0.00
CAFE_FLR_1 710417.00 0.00 0.00 0.00 0.00
LOBBY_FLR_1 2115429.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 0.00 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_5_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_6_FLR_3 4154.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3 100358.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 4154.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_6 4154.00 0.00 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 4154.00 0.00 0.00 0.00 0.00
BANQUET_FLR_6 1245715.00 0.00 0.00 0.00 0.00
DINING_FLR_6 1245715.00 0.00 0.00 0.00 0.00
KITCHEN_FLR_6 108269.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6 105946.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 2115429.00 0.00 0.00 0.00 0.00
Average 288887.05 0.00 0.00 0.00 0.00
Sum 6355515.00 0.00 0.00 0.00 0.00


Humidex Hours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
BASEMENT 8760.00 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 8760.00 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 8760.00 0.00 0.00 0.00 0.00
MECH_FLR_1 8760.00 0.00 0.00 0.00 0.00
STORAGE_FLR_1 8760.00 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 8760.00 0.00 0.00 0.00 0.00
CAFE_FLR_1 8760.00 0.00 0.00 0.00 0.00
LOBBY_FLR_1 8760.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_5_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_6_FLR_3 8760.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 8760.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_6 8760.00 0.00 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 8760.00 0.00 0.00 0.00 0.00
BANQUET_FLR_6 8760.00 0.00 0.00 0.00 0.00
DINING_FLR_6 8760.00 0.00 0.00 0.00 0.00
KITCHEN_FLR_6 8760.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6 8760.00 0.00 0.00 0.00 0.00
Min 8760.00 0.00 0.00 0.00 0.00
Max 8760.00 0.00 0.00 0.00 0.00
Average 8760.00 0.00 0.00 0.00 0.00
Sum 192720.00 0.00 0.00 0.00 0.00


Humidex OccupantHours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
BASEMENT 529331.00 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 50179.00 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 59156.00 0.00 0.00 0.00 0.00
MECH_FLR_1 8977.00 0.00 0.00 0.00 0.00
STORAGE_FLR_1 5588.00 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 37203.00 0.00 0.00 0.00 0.00
CAFE_FLR_1 710417.00 0.00 0.00 0.00 0.00
LOBBY_FLR_1 2115429.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 0.00 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_5_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_6_FLR_3 4154.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3 100358.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 4154.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_6 4154.00 0.00 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 4154.00 0.00 0.00 0.00 0.00
BANQUET_FLR_6 1245715.00 0.00 0.00 0.00 0.00
DINING_FLR_6 1245715.00 0.00 0.00 0.00 0.00
KITCHEN_FLR_6 108269.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6 105946.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 2115429.00 0.00 0.00 0.00 0.00
Average 288887.05 0.00 0.00 0.00 0.00
Sum 6355515.00 0.00 0.00 0.00 0.00


Heating SET Hours

SET ≤ 12.2°C Hours (°C) SET ≤ 12.2°C OccupantHours (°C) Longest SET ≤ 12.2°C Duration [hr] Start Time of the Longest SET ≤ 12.2°C Duration
None        


Cooling SET Hours

SET > 30°C Hours (°C) SET > 30°C OccupantHours (°C) Longest SET > 30°C Duration [hr] Start Time of the Longest SET > 30°C Duration
None        



Table of Contents

Report: Annual CO2 Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 08:58:31

CO2 Level Hours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      


CO2 Level OccupantHours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      



Table of Contents

Report: Annual Visual Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 08:58:31

Illuminance Level Hours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
None        


Illuminance Level OccupantHours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
None        



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR

For: Environment

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 4.180
February 4.245
March 5.898
April 8.962
May 9.987
June 13.308
July 15.016
August 15.650
September 13.434
October 9.327
November 6.665
December 4.103
   
Annual Sum or Average 9.257
Minimum of Months 4.103
Maximum of Months 15.650



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC

For: Environment

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 4.180
February 4.245
March 5.898
April 8.962
May 9.987
June 13.308
July 15.016
August 15.650
September 13.434
October 9.327
November 6.665
December 4.103
   
Annual Sum or Average 9.257
Minimum of Months 4.103
Maximum of Months 15.650



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2012

For: Environment

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 4.180
February 4.245
March 5.898
April 8.962
May 9.987
June 13.308
July 15.016
August 15.650
September 13.434
October 9.327
November 6.665
December 4.103
   
Annual Sum or Average 9.257
Minimum of Months 4.103
Maximum of Months 15.650



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

For: Environment

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 4.180
February 4.245
March 5.898
April 8.962
May 9.987
June 13.308
July 15.016
August 15.650
September 13.434
October 9.327
November 6.665
December 4.103
   
Annual Sum or Average 9.257
Minimum of Months 4.103
Maximum of Months 15.650



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE

For: Environment

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 4.180
February 4.245
March 5.898
April 8.962
May 9.987
June 13.308
July 15.016
August 15.650
September 13.434
October 9.327
November 6.665
December 4.103
   
Annual Sum or Average 9.257
Minimum of Months 4.103
Maximum of Months 15.650



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

For: Environment

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 4.180
February 4.245
March 5.898
April 8.962
May 9.987
June 13.308
July 15.016
August 15.650
September 13.434
October 9.327
November 6.665
December 4.103
   
Annual Sum or Average 9.257
Minimum of Months 4.103
Maximum of Months 15.650



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

For: Environment

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 4.180
February 4.245
March 5.898
April 8.962
May 9.987
June 13.308
July 15.016
August 15.650
September 13.434
October 9.327
November 6.665
December 4.103
   
Annual Sum or Average 9.257
Minimum of Months 4.103
Maximum of Months 15.650



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5C

For: Environment

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 4.180
February 4.245
March 5.898
April 8.962
May 9.987
June 13.308
July 15.016
August 15.650
September 13.434
October 9.327
November 6.665
December 4.103
   
Annual Sum or Average 9.257
Minimum of Months 4.103
Maximum of Months 15.650



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_PORTANGELES

For: Environment

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 4.180
February 4.245
March 5.898
April 8.962
May 9.987
June 13.308
July 15.016
August 15.650
September 13.434
October 9.327
November 6.665
December 4.103
   
Annual Sum or Average 9.257
Minimum of Months 4.103
Maximum of Months 15.650



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.370717E+11 18958.62 20-JAN-21:00 1.00 0.17 0.614828E+10 3784.89 11-JAN-22:10 1.00 0.17
February 0.324113E+11 18799.56 22-FEB-21:00 5.00 4.08 0.554936E+10 3755.61 01-FEB-22:10 5.00 4.08
March 0.345787E+11 18741.74 31-MAR-20:00 6.00 2.98 0.615671E+10 3732.66 01-MAR-22:10 6.00 2.98
April 0.337551E+11 19630.53 27-APR-19:10 16.17 10.74 0.593371E+10 3715.47 07-APR-21:10 16.17 10.74
May 0.348489E+11 20231.62 30-MAY-18:06 12.00 9.79 0.613380E+10 3716.80 04-MAY-21:10 12.00 9.79
June 0.347514E+11 20588.93 21-JUN-19:10 18.50 14.60 0.594948E+10 3747.03 20-JUN-22:10 18.50 14.60
July 0.374478E+11 20690.53 10-JUL-19:10 18.67 13.72 0.613035E+10 3794.34 07-JUL-22:10 18.67 13.72
August 0.382292E+11 20663.04 17-AUG-18:40 19.00 15.36 0.616510E+10 3774.54 02-AUG-22:10 19.00 15.36
September 0.385146E+11 21180.16 13-SEP-18:02 17.50 14.11 0.596858E+10 3806.89 27-SEP-21:10 13.67 9.68
October 0.403016E+11 19811.37 04-OCT-18:10 9.67 7.79 0.617943E+10 3812.50 27-OCT-21:10 8.00 8.00
November 0.392155E+11 19407.70 10-NOV-21:00 4.00 4.00 0.598561E+10 3832.66 29-NOV-22:10 3.00 2.55
December 0.391650E+11 19119.52 20-DEC-21:00 7.00 6.47 0.617080E+10 3817.25 01-DEC-22:10 7.00 6.47
                     
Annual Sum or Average 0.440291E+12         0.724712E+11        
Minimum of Months 0.324113E+11 18741.74   1.00 0.17 0.554936E+10 3715.47   1.00 0.17
Maximum of Months 0.403016E+11 21180.16   19.00 15.36 0.617943E+10 3832.66   19.00 15.36



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.116551E+10 3751.23 15-JAN-11:40 8.67 6.43 0.615798E+09 364.33 24-JAN-05:30 6.00 5.49
February 0.138796E+10 3947.29 04-FEB-11:40 7.67 5.05 0.558538E+09 364.32 23-FEB-03:39 4.00 3.53
March 0.113833E+10 2811.21 25-MAR-11:30 11.75 8.68 0.621509E+09 364.32 23-MAR-02:09 11.75 8.68
April 0.343861E+10 4043.60 30-APR-12:00 22.00 14.01 0.601675E+09 364.30 24-APR-04:30 22.00 14.01
May 0.334927E+10 3691.53 23-MAY-12:00 20.00 15.13 0.621040E+09 364.31 19-MAY-03:30 20.00 15.13
June 0.387009E+10 3719.81 13-JUN-12:00 23.00 16.68 0.602021E+09 364.27 08-JUN-02:00 23.00 16.68
July 0.451457E+10 3959.08 22-JUL-12:00 27.00 17.16 0.619986E+09 364.28 27-JUL-02:30 10.00 9.45
August 0.491230E+10 4040.09 28-AUG-15:15 24.00 15.59 0.623737E+09 364.30 30-AUG-02:39 9.67 9.50
September 0.458466E+10 4499.17 12-SEP-10:35 17.67 14.44 0.603749E+09 364.34 29-SEP-03:09 10.83 9.24
October 0.251848E+10 4323.16 04-OCT-10:35 13.07 9.87 0.620834E+09 364.36 26-OCT-04:49 7.00 6.56
November 0.126479E+10 3583.44 11-NOV-11:40 9.00 6.87 0.598241E+09 364.38 25-NOV-03:30 8.00 6.73
December 0.594271E+09 3280.02 18-DEC-13:30 8.00 5.46 0.611879E+09 364.31 11-DEC-22:10 8.00 5.46
                     
Annual Sum or Average 0.327388E+11         0.729901E+10        
Minimum of Months 0.594271E+09 2811.21   7.67 5.05 0.558538E+09 364.27   4.00 3.53
Maximum of Months 0.491230E+10 4499.17   27.00 17.16 0.623737E+09 364.38   23.00 16.68



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.253394E+10 1715.87 23-JAN-21:00 9.00 7.43 0.717723E+09 429.87 17-JAN-22:19 9.00 7.43
February 0.237641E+10 1725.63 27-FEB-21:00 6.00 6.00 0.649086E+09 432.25 27-FEB-22:19 4.67 4.67
March 0.267900E+10 1749.82 20-MAR-20:00 7.00 4.68 0.721626E+09 433.87 20-MAR-21:19 4.80 3.90
April 0.319118E+10 2001.47 27-APR-18:02 17.83 10.48 0.700126E+09 456.07 28-APR-21:40 11.33 8.56
May 0.333800E+10 2089.25 22-MAY-18:03 19.00 14.26 0.724419E+09 458.00 23-MAY-21:30 12.00 9.78
June 0.350079E+10 2147.71 12-JUN-18:02 25.67 17.63 0.705160E+09 463.30 21-JUN-22:10 12.83 11.81
July 0.373327E+10 2163.16 22-JUL-18:07 29.83 16.84 0.727211E+09 465.05 25-JUL-22:10 13.00 12.44
August 0.377833E+10 2128.96 14-AUG-18:10 26.48 13.67 0.730259E+09 459.71 14-AUG-21:40 16.73 11.70
September 0.349415E+10 2055.88 11-SEP-18:10 21.50 15.69 0.702391E+09 460.88 11-SEP-22:10 12.83 11.23
October 0.300950E+10 1830.92 03-OCT-20:00 7.00 6.01 0.720059E+09 444.58 03-OCT-21:40 8.00 6.49
November 0.256617E+10 1728.11 15-NOV-21:00 7.00 6.47 0.694536E+09 431.28 15-NOV-22:19 5.33 4.84
December 0.233166E+10 1630.24 21-DEC-22:00 3.00 3.00 0.717413E+09 424.98 21-DEC-22:19 3.00 3.00
                     
Annual Sum or Average 0.365324E+11         0.851001E+10        
Minimum of Months 0.233166E+10 1630.24   3.00 3.00 0.649086E+09 424.98   3.00 3.00
Maximum of Months 0.377833E+10 2163.16   29.83 17.63 0.730259E+09 465.05   16.73 12.44



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.113131E+10 1393.05 18-JAN-21:00 8.00 6.97 0.151697E+09 89.15 05-JAN-03:09 8.00 6.97
February 0.107603E+10 1344.42 22-FEB-21:00 5.00 4.08 0.137151E+09 89.15 08-FEB-02:39 5.00 4.08
March 0.149274E+10 1483.23 20-MAR-20:00 7.00 4.68 0.152411E+09 89.15 20-MAR-01:39 7.00 4.68
April 0.206327E+10 1787.28 30-APR-19:10 22.83 13.25 0.147123E+09 91.37 28-APR-21:10 22.83 13.25
May 0.228623E+10 1849.85 22-MAY-19:00 19.00 14.26 0.152158E+09 92.73 23-MAY-21:10 12.00 9.78
June 0.271594E+10 1921.57 12-JUN-18:40 24.67 17.00 0.147874E+09 93.96 13-JUN-21:10 14.00 12.84
July 0.298987E+10 1995.46 22-JUL-18:20 29.67 16.87 0.152378E+09 93.74 21-JUL-21:10 29.67 16.87
August 0.298274E+10 1913.65 14-AUG-18:30 25.45 13.46 0.152986E+09 92.86 14-AUG-21:10 17.83 11.86
September 0.254357E+10 1799.39 11-SEP-18:50 19.50 14.98 0.147271E+09 92.06 12-SEP-21:10 15.17 13.86
October 0.189396E+10 1625.67 10-OCT-20:00 10.00 9.41 0.151770E+09 89.43 10-OCT-21:10 8.83 8.83
November 0.137702E+10 1480.96 08-NOV-21:00 11.00 11.00 0.146742E+09 89.15 25-NOV-05:00 7.00 5.14
December 0.976669E+09 1267.13 05-DEC-21:00 7.00 6.46 0.151698E+09 89.15 26-DEC-04:00 2.00 0.31
                     
Annual Sum or Average 0.235294E+11         0.179126E+10        
Minimum of Months 0.976669E+09 1267.13   5.00 4.08 0.137151E+09 89.15   2.00 0.31
Maximum of Months 0.298987E+10 1995.46   29.67 17.00 0.152986E+09 93.96   29.67 16.87



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.155788E+09 366.86 18-JAN-22:00 8.00 7.45 0.116691E+09 68.57 30-JAN-04:10 3.75 3.18
February 0.137682E+09 331.91 07-FEB-22:00 7.00 7.00 0.105502E+09 68.58 15-FEB-05:40 5.33 2.47
March 0.289149E+09 398.04 20-MAR-20:10 6.67 4.60 0.117240E+09 68.57 07-MAR-01:19 6.67 4.60
April 0.661618E+09 712.24 30-APR-19:05 22.83 13.25 0.113126E+09 68.57 27-APR-03:09 22.83 13.25
May 0.780142E+09 731.11 22-MAY-19:40 17.67 13.35 0.116938E+09 68.57 01-MAY-04:10 17.67 13.35
June 0.106908E+10 860.91 13-JUN-19:05 20.08 15.24 0.113381E+09 69.41 13-JUN-22:10 13.83 12.78
July 0.122558E+10 902.38 22-JUL-18:25 29.50 16.91 0.116706E+09 69.42 21-JUL-22:10 29.50 16.91
August 0.121774E+10 787.07 14-AUG-20:40 19.03 12.06 0.117186E+09 68.89 14-AUG-21:40 16.73 11.70
September 0.960913E+09 712.15 12-SEP-21:00 15.00 13.80 0.113071E+09 68.57 11-SEP-02:00 15.00 13.80
October 0.530471E+09 483.63 10-OCT-20:50 9.17 9.07 0.116746E+09 68.57 27-OCT-00:00 9.00 8.43
November 0.256938E+09 430.97 08-NOV-22:00 11.00 11.00 0.112879E+09 68.58 25-NOV-05:10 7.83 5.92
December 82365383.03 275.45 05-DEC-21:00 7.00 6.46 0.116691E+09 68.58 15-DEC-04:00 3.00 1.30
                     
Annual Sum or Average 0.736746E+10         0.137616E+10        
Minimum of Months 82365383.03 275.45   6.67 4.60 0.105502E+09 68.57   3.00 1.30
Maximum of Months 0.122558E+10 902.38   29.50 16.91 0.117240E+09 69.42   29.50 16.91



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.490074E+11 35664.57 23-JAN-21:00 9.00 7.43 0.511097E+09 381.90 24-JAN-22:10 4.03 4.03
February 0.443796E+11 35682.37 07-FEB-21:00 8.00 7.45 0.462069E+09 381.89 21-FEB-22:10 4.17 4.17
March 0.496389E+11 35794.37 31-MAR-20:00 6.00 2.98 0.513872E+09 381.90 17-MAR-21:10 6.00 2.98
April 0.492262E+11 36617.29 28-APR-20:00 13.00 9.28 0.493774E+09 383.29 28-APR-21:10 11.83 8.82
May 0.510488E+11 36735.67 22-MAY-20:00 17.00 12.89 0.510710E+09 386.42 23-MAY-21:10 12.00 9.78
June 0.501419E+11 36973.20 12-JUN-20:00 22.00 16.43 0.494769E+09 383.86 23-JUN-21:10 12.83 10.83
July 0.519335E+11 36964.54 21-JUL-20:00 21.00 15.02 0.507850E+09 390.08 26-JUL-21:10 12.67 11.32
August 0.522112E+11 36889.43 14-AUG-20:00 20.70 12.26 0.511633E+09 385.73 23-AUG-21:10 11.83 9.23
September 0.498672E+11 36676.41 12-SEP-20:00 15.00 13.80 0.493809E+09 387.17 27-SEP-21:10 13.67 9.68
October 0.501730E+11 36168.53 06-OCT-20:00 8.00 6.07 0.510752E+09 381.91 17-OCT-21:10 11.00 11.00
November 0.478377E+11 35766.00 08-NOV-21:00 11.00 11.00 0.494553E+09 381.89 17-NOV-22:10 6.00 5.12
December 0.486516E+11 35522.20 20-DEC-21:00 7.00 6.47 0.510811E+09 381.89 22-DEC-22:10 3.83 3.37
                     
Annual Sum or Average 0.594117E+12         0.601570E+10        
Minimum of Months 0.443796E+11 35522.20   6.00 2.98 0.462069E+09 381.89   3.83 2.98
Maximum of Months 0.522112E+11 36973.20   22.00 16.43 0.513872E+09 390.08   13.67 11.32



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.166846E+11 14641.12 07-JAN-11:35 6.67 4.01 0.814339E+10 4790.50 30-JAN-05:40 2.73 2.42
February 0.162514E+11 15281.79 04-FEB-11:40 7.67 5.05 0.736598E+10 4790.24 27-FEB-04:30 6.00 6.00
March 0.168251E+11 11590.81 25-MAR-11:30 11.75 8.68 0.818145E+10 4789.75 24-MAR-04:49 11.75 8.68
April 0.229487E+11 15241.32 28-APR-15:13 20.07 13.24 0.790247E+10 4831.94 28-APR-21:19 11.67 8.73
May 0.229502E+11 14076.33 22-MAY-15:03 23.83 15.94 0.816073E+10 4839.04 22-MAY-21:30 14.50 12.46
June 0.237372E+11 13984.59 13-JUN-15:02 26.08 17.81 0.791211E+10 4919.80 21-JUN-22:10 12.83 11.81
July 0.258840E+11 14800.29 21-JUL-15:13 27.33 15.92 0.814565E+10 4939.10 24-JUL-22:10 13.00 13.00
August 0.272186E+11 15556.68 28-AUG-15:15 24.00 15.59 0.818765E+10 4920.92 14-AUG-21:30 24.00 15.59
September 0.261069E+11 16211.77 23-SEP-10:35 18.00 14.39 0.792096E+10 4998.21 11-SEP-22:10 18.00 14.39
October 0.207922E+11 15990.71 07-OCT-10:35 14.67 10.10 0.815595E+10 4789.91 28-OCT-03:00 8.00 7.44
November 0.166773E+11 13807.20 11-NOV-11:40 9.00 6.87 0.787751E+10 4789.95 03-NOV-04:49 9.00 6.87
December 0.145725E+11 12611.35 18-DEC-13:30 8.00 5.46 0.813932E+10 4790.05 15-DEC-02:00 8.00 5.46
                     
Annual Sum or Average 0.250649E+12         0.960932E+11        
Minimum of Months 0.145725E+11 11590.81   6.67 4.01 0.736598E+10 4789.75   2.73 2.42
Maximum of Months 0.272186E+11 16211.77   27.33 17.81 0.818765E+10 4998.21   24.00 15.59



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.644019E+11 36892.47 23-JAN-22:00 8.00 7.45 0.242101E+11 14809.97 23-JAN-22:40 8.00 7.45
February 0.600211E+11 37124.24 27-FEB-21:00 6.00 6.00 0.218978E+11 14797.29 27-FEB-22:40 4.33 4.33
March 0.661395E+11 37567.84 20-MAR-20:00 7.00 4.68 0.243509E+11 14858.19 20-MAR-21:40 4.60 3.70
April 0.754888E+11 41752.33 27-APR-18:30 17.50 10.71 0.236258E+11 15451.20 28-APR-21:40 11.33 8.56
May 0.776180E+11 43368.59 22-MAY-18:40 19.00 14.26 0.244511E+11 15473.90 23-MAY-21:40 12.00 9.78
June 0.791822E+11 44639.07 12-JUN-18:40 24.67 17.00 0.238380E+11 15718.20 21-JUN-22:10 12.83 11.81
July 0.841051E+11 44154.37 10-JUL-18:30 20.00 13.91 0.246078E+11 15814.29 25-JUL-22:10 13.00 12.44
August 0.859031E+11 44790.30 14-AUG-18:20 25.97 13.57 0.247509E+11 15633.87 18-AUG-22:10 12.83 11.81
September 0.815527E+11 43478.52 11-SEP-18:02 21.50 15.69 0.237874E+11 15745.01 11-SEP-22:10 12.83 11.23
October 0.730035E+11 39148.77 03-OCT-20:00 7.00 6.01 0.243166E+11 15194.31 03-OCT-21:40 8.00 6.49
November 0.641509E+11 37318.51 15-NOV-21:00 7.00 6.47 0.234391E+11 14832.07 08-NOV-22:40 7.00 6.47
December 0.607158E+11 35953.02 21-DEC-22:00 3.00 3.00 0.241925E+11 14628.58 21-DEC-22:40 3.00 3.00
                     
Annual Sum or Average 0.872283E+12         0.287468E+12        
Minimum of Months 0.600211E+11 35953.02   3.00 3.00 0.218978E+11 14628.58   3.00 3.00
Maximum of Months 0.859031E+11 44790.30   25.97 17.00 0.247509E+11 15814.29   13.00 12.44



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 84852359.78 2738.75 25-JAN-16:01 9.00 8.43 94229815.73 56.69 29-JAN-00:20 7.20 6.95
February 0.139778E+09 3588.17 18-FEB-16:01 5.83 4.00 85755426.63 56.69 27-FEB-22:19 4.67 4.67
March 0.125412E+09 3467.60 31-MAR-15:01 7.33 4.46 94850976.00 56.69 20-MAR-21:19 7.33 4.46
April 0.889192E+09 3652.25 13-APR-15:02 12.00 7.14 94577113.71 56.69 20-APR-21:00 11.00 7.91
May 0.102551E+10 3713.54 21-MAY-15:01 18.83 10.43 97757154.94 56.69 22-MAY-22:00 14.00 12.24
June 0.140895E+10 3547.78 08-JUN-18:02 15.83 9.50 95252642.31 56.69 13-JUN-21:10 14.00 12.84
July 0.168836E+10 3527.11 26-JUL-15:02 19.68 15.17 98443394.03 56.69 18-JUL-21:30 19.68 15.17
August 0.161413E+10 3486.67 27-AUG-18:02 16.33 13.76 98602656.63 56.69 16-AUG-21:00 16.33 13.76
September 0.123892E+10 3635.31 29-SEP-15:01 15.67 9.39 95043107.50 56.69 12-SEP-22:00 15.67 9.39
October 0.390735E+09 3661.29 07-OCT-15:02 18.83 10.03 96067552.05 56.69 07-OCT-23:10 10.83 9.32
November 93169345.47 3559.11 03-NOV-15:01 8.83 5.57 91504513.02 56.69 30-NOV-00:20 3.33 3.18
December 51283132.42 487.11 20-DEC-19:05 7.67 7.21 93194711.01 56.69 16-DEC-00:20 7.67 7.21
                     
Annual Sum or Average 0.875029E+10         0.113528E+10        
Minimum of Months 51283132.42 487.11   5.83 4.00 85755426.63 56.69   3.33 3.18
Maximum of Months 0.168836E+10 3713.54   19.68 15.17 98602656.63 56.69   19.68 15.17



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 55506213.90 2001.23 19-JAN-16:01 7.67 7.22 93299898.07 56.69 11-JAN-00:10 7.67 7.22
February 80532454.94 2991.45 19-FEB-16:02 5.17 4.17 84745538.11 56.69 10-FEB-00:10 5.17 4.17
March 97105853.57 3004.22 20-MAR-18:02 7.83 5.10 94379014.34 56.69 20-MAR-21:19 4.80 3.90
April 0.612791E+09 3258.57 26-APR-15:02 14.83 9.50 93820850.30 56.69 27-APR-21:10 8.83 7.27
May 0.839531E+09 3342.63 21-MAY-15:01 18.83 10.43 97303846.76 56.69 22-MAY-22:00 14.00 12.24
June 0.126885E+10 3221.88 08-JUN-18:02 15.83 9.50 95032198.85 56.70 26-JUN-21:10 14.00 14.00
July 0.148768E+10 3253.47 24-JUL-15:02 19.17 15.95 98216009.94 56.70 21-JUL-21:10 19.17 15.95
August 0.127042E+10 3236.95 19-AUG-15:02 20.00 15.22 98209536.68 56.69 15-AUG-21:00 20.00 15.22
September 0.798778E+09 3257.18 11-SEP-15:02 22.00 15.85 94264340.95 56.69 12-SEP-22:10 15.83 13.97
October 0.207611E+09 3255.35 07-OCT-15:02 18.83 10.03 95128808.07 56.69 07-OCT-23:10 10.83 9.32
November 64205485.18 1910.06 10-NOV-16:02 10.33 8.12 90686411.73 56.69 01-NOV-23:19 10.33 8.12
December 38329141.05 286.37 02-DEC-09:05 7.00 6.47 92647291.81 56.69 04-DEC-22:19 7.00 7.00
                     
Annual Sum or Average 0.682134E+10         0.112773E+10        
Minimum of Months 38329141.05 286.37   5.17 4.17 84745538.11 56.69   4.80 3.90
Maximum of Months 0.148768E+10 3342.63   22.00 15.95 98216009.94 56.70   20.00 15.95



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.282151E+09 580.61 21-JAN-11:25 6.00 5.05 0.00 0.00 01-JAN-00:10 6.00 5.05
February 0.273037E+09 527.06 04-FEB-14:00 9.00 6.13 0.00 0.00 01-FEB-00:10 9.00 6.13
March 0.227439E+09 252.23 25-MAR-11:40 11.83 8.75 0.00 0.00 01-MAR-00:10 11.83 8.75
April 0.589924E+09 733.86 30-APR-12:50 22.00 13.22 0.00 0.00 01-APR-00:10 22.00 13.22
May 0.526615E+09 586.72 22-MAY-13:20 22.33 15.12 0.00 0.00 01-MAY-00:10 22.33 15.12
June 0.580889E+09 594.29 13-JUN-13:20 24.37 17.19 0.00 0.00 01-JUN-00:10 24.37 17.19
July 0.672380E+09 679.47 22-JUL-13:30 28.00 16.51 0.00 0.00 01-JUL-00:10 28.00 16.51
August 0.752910E+09 721.13 20-AUG-13:00 23.00 14.82 0.00 0.00 01-AUG-00:10 23.00 14.82
September 0.802729E+09 854.01 27-SEP-13:20 21.33 13.25 0.00 0.00 01-SEP-00:10 21.33 13.25
October 0.476826E+09 798.64 07-OCT-13:10 17.00 9.32 0.00 0.00 01-OCT-00:10 17.00 9.32
November 0.272065E+09 559.27 11-NOV-13:30 9.00 7.22 0.00 0.00 01-NOV-00:10 9.00 7.22
December 0.164394E+09 249.69 26-DEC-14:30 6.00 2.98 0.00 0.00 01-DEC-00:10 6.00 2.98
                     
Annual Sum or Average 0.562136E+10         0.00        
Minimum of Months 0.164394E+09 249.69   6.00 2.98 0.00 0.00   6.00 2.98
Maximum of Months 0.802729E+09 854.01   28.00 17.19 0.00 0.00   28.00 17.19



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.180118E+09 801.50 29-JAN-19:02 9.00 8.43 95109904.30 56.69 19-JAN-22:19 9.00 8.43
February 0.169961E+09 868.92 12-FEB-09:02 2.33 1.83 86089866.69 56.69 22-FEB-22:10 4.17 3.62
March 0.298190E+09 909.11 20-MAR-18:02 7.83 5.10 96016207.96 56.69 14-MAR-21:10 7.83 5.10
April 0.469392E+09 973.74 22-APR-15:02 17.67 9.75 93727501.70 56.69 14-APR-21:10 17.67 9.75
May 0.562973E+09 984.28 28-MAY-18:01 11.83 7.52 97176156.08 56.69 22-MAY-22:00 11.83 7.52
June 0.693290E+09 1019.41 12-JUN-18:02 25.67 17.63 94584113.05 56.69 13-JUN-21:40 14.00 12.84
July 0.748004E+09 1008.63 10-JUL-15:02 22.67 16.49 97657291.74 56.69 10-JUL-21:40 17.00 13.49
August 0.679134E+09 980.70 14-AUG-15:02 25.17 16.00 97404046.48 56.69 15-AUG-21:10 15.00 13.19
September 0.548533E+09 972.44 11-SEP-18:02 21.50 15.69 93881815.53 56.69 28-SEP-22:10 12.00 11.55
October 0.372082E+09 920.67 07-OCT-15:02 18.83 10.03 96221028.77 56.69 17-OCT-21:10 11.00 11.00
November 0.231771E+09 887.09 26-NOV-09:02 5.17 2.51 92426864.44 56.69 24-NOV-23:10 5.17 2.51
December 0.135885E+09 735.97 02-DEC-09:02 7.00 6.47 94794970.39 56.69 04-DEC-22:19 7.00 7.00
                     
Annual Sum or Average 0.508933E+10         0.113509E+10        
Minimum of Months 0.135885E+09 735.97   2.33 1.83 86089866.69 56.69   4.17 2.51
Maximum of Months 0.748004E+09 1019.41   25.67 17.63 97657291.74 56.69   17.67 13.49



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.101048E+09 1922.75 21-JAN-16:02 5.75 4.88 94192209.60 56.69 03-JAN-23:49 5.75 4.88
February 0.122964E+09 3066.15 04-FEB-16:01 7.00 5.54 85671517.60 56.69 22-FEB-00:10 6.00 6.00
March 0.121846E+09 2743.32 20-MAR-15:01 10.83 7.32 94915691.18 56.69 20-MAR-21:19 4.80 3.90
April 0.989263E+09 3326.83 15-APR-08:62 9.33 5.61 95081505.14 56.69 20-APR-21:40 11.00 7.79
May 0.102550E+10 3353.59 21-MAY-15:01 18.83 10.43 98215974.23 56.69 22-MAY-22:40 14.00 12.24
June 0.131743E+10 3251.29 13-JUN-08:62 21.10 15.99 95461574.65 56.69 26-JUN-22:00 15.00 14.41
July 0.159255E+10 3270.73 23-JUL-08:61 19.17 15.34 98727979.48 56.69 17-JUL-21:00 19.17 15.34
August 0.167200E+10 3279.39 14-AUG-08:62 20.17 15.19 98805440.61 56.69 16-AUG-21:00 16.00 14.77
September 0.135976E+10 3289.03 29-SEP-15:01 15.67 9.39 95407055.04 56.69 14-SEP-21:00 15.67 9.39
October 0.412002E+09 3310.68 07-OCT-15:02 18.83 10.03 96243087.41 56.69 07-OCT-23:10 10.83 9.32
November 0.103536E+09 3012.74 03-NOV-15:01 8.83 5.57 91476795.49 56.69 30-NOV-00:20 3.33 3.18
December 62391730.06 737.83 06-DEC-09:03 2.33 1.83 93276040.03 56.69 16-DEC-00:20 4.00 3.69
                     
Annual Sum or Average 0.888029E+10         0.113747E+10        
Minimum of Months 62391730.06 737.83   2.33 1.83 85671517.60 56.69   3.33 3.18
Maximum of Months 0.167200E+10 3353.59   21.10 15.99 98805440.61 56.69   19.17 15.34



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 57277580.07 689.84 19-JAN-09:03 7.17 6.56 93288258.31 56.69 14-JAN-00:20 7.17 6.56
February 71673750.26 1830.15 20-FEB-09:02 3.33 2.81 84610866.61 56.69 17-FEB-23:49 3.33 2.81
March 90713001.60 912.17 10-MAR-09:02 7.17 4.01 94449778.22 56.69 15-MAR-23:19 2.57 1.57
April 0.689306E+09 3029.15 15-APR-08:62 9.33 5.61 94521053.45 56.69 27-APR-21:10 8.83 7.27
May 0.828171E+09 3041.75 21-MAY-15:01 18.83 10.43 97913353.53 56.69 22-MAY-22:30 14.00 12.24
June 0.116849E+10 2967.41 13-JUN-08:62 21.10 15.99 95336319.08 56.69 26-JUN-22:00 15.00 14.41
July 0.137782E+10 2986.74 23-JUL-08:61 19.17 15.34 98644775.44 56.69 17-JUL-21:40 19.17 15.34
August 0.130381E+10 3006.14 14-AUG-08:62 20.17 15.19 98656837.64 56.69 16-AUG-21:30 16.50 14.93
September 0.881116E+09 2940.32 23-SEP-08:62 17.00 13.57 95022963.70 56.69 12-SEP-22:10 17.00 13.57
October 0.218529E+09 2842.10 07-OCT-15:02 18.83 10.03 95375380.74 56.69 07-OCT-23:10 10.83 9.32
November 67051846.44 1089.55 11-NOV-09:02 6.50 5.33 90655447.98 56.69 01-NOV-22:49 6.50 5.33
December 40516547.00 505.73 11-DEC-09:05 3.50 2.91 92723885.01 56.69 04-DEC-22:19 3.50 2.91
                     
Annual Sum or Average 0.679446E+10         0.113120E+10        
Minimum of Months 40516547.00 505.73   3.33 2.81 84610866.61 56.69   2.57 1.57
Maximum of Months 0.137782E+10 3041.75   21.10 15.99 98656837.64 56.69   19.17 15.34



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.172938E+10 1577.81 23-JAN-22:03 8.00 7.45 0.119882E+10 704.49 09-JAN-04:40 8.00 7.45
February 0.186539E+10 1873.12 04-FEB-14:20 9.00 6.28 0.108386E+10 704.48 02-FEB-02:20 9.00 6.28
March 0.218933E+10 1761.06 20-MAR-18:03 7.83 5.10 0.120445E+10 704.47 07-MAR-01:49 7.83 5.10
April 0.425506E+10 2984.50 30-APR-10:35 19.33 11.65 0.116522E+10 730.90 28-APR-21:40 19.33 11.65
May 0.452874E+10 2832.46 22-MAY-18:10 19.00 14.26 0.120505E+10 736.13 23-MAY-21:40 12.00 9.78
June 0.509145E+10 2973.33 13-JUN-10:35 22.00 15.85 0.117368E+10 747.92 13-JUN-21:40 14.00 12.84
July 0.556859E+10 3162.57 23-JUL-10:35 21.00 15.99 0.121658E+10 751.32 24-JUL-22:10 13.00 13.00
August 0.568363E+10 3076.09 14-AUG-17:08 27.00 14.28 0.122017E+10 741.63 14-AUG-21:40 16.73 11.70
September 0.509909E+10 2913.29 12-SEP-10:35 17.67 14.44 0.117294E+10 742.09 12-SEP-21:40 15.67 14.03
October 0.327432E+10 2457.14 07-OCT-17:12 13.67 8.88 0.119991E+10 711.69 03-OCT-21:40 13.67 8.88
November 0.194946E+10 1788.08 11-NOV-13:00 9.00 7.43 0.115965E+10 704.49 25-NOV-01:39 9.00 8.43
December 0.111949E+10 1236.39 21-DEC-22:03 3.00 3.00 0.119882E+10 704.50 05-DEC-02:20 3.00 3.00
                     
Annual Sum or Average 0.423539E+11         0.141992E+11        
Minimum of Months 0.111949E+10 1236.39   3.00 3.00 0.108386E+10 704.47   3.00 3.00
Maximum of Months 0.568363E+10 3162.57   27.00 15.99 0.122017E+10 751.32   19.33 14.03



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 66261860.01 2883.16 25-JAN-16:01 9.00 8.43 93658254.77 56.69 03-JAN-22:19 9.00 8.43
February 0.128113E+09 3812.42 09-FEB-16:01 7.67 5.50 85254704.03 56.69 26-FEB-00:20 2.00 2.00
March 0.108611E+09 3676.82 10-MAR-16:01 7.83 4.01 94391055.62 56.69 20-MAR-21:19 4.80 3.90
April 0.972131E+09 3907.50 13-APR-15:02 12.00 7.14 94533740.12 56.69 27-APR-21:10 8.83 7.27
May 0.110938E+10 3970.98 21-MAY-15:01 18.83 10.43 97744746.18 56.69 25-MAY-21:30 9.50 8.92
June 0.156176E+10 3842.59 13-JUN-18:02 23.37 16.34 95318216.73 56.69 25-JUN-03:39 10.33 9.99
July 0.189851E+10 3768.49 16-JUL-18:02 18.67 15.16 98510390.55 56.70 21-JUL-21:10 17.00 13.87
August 0.178416E+10 3758.24 10-AUG-15:02 20.67 15.35 98633125.72 56.69 16-AUG-21:49 16.17 14.83
September 0.130265E+10 3863.96 29-SEP-15:01 15.67 9.39 95038521.31 56.69 14-SEP-21:40 15.67 9.39
October 0.371877E+09 3910.58 07-OCT-15:02 18.83 10.03 95712043.57 56.69 08-OCT-00:49 10.00 8.90
November 77007576.24 3748.33 03-NOV-15:01 8.83 5.57 90942839.80 56.69 01-NOV-22:49 8.83 5.57
December 35108602.52 386.08 26-DEC-16:05 2.67 1.50 92720765.02 56.69 27-DEC-00:20 1.67 1.38
                     
Annual Sum or Average 0.941557E+10         0.113246E+10        
Minimum of Months 35108602.52 386.08   2.67 1.50 85254704.03 56.69   1.67 1.38
Maximum of Months 0.189851E+10 3970.98   23.37 16.34 98633125.72 56.70   17.00 14.83



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 37762236.83 1345.54 19-JAN-16:01 7.67 7.22 92819372.87 56.69 12-JAN-23:49 7.67 7.22
February 63377857.10 2757.61 19-FEB-16:02 5.17 4.17 84215653.66 56.69 04-FEB-00:10 5.17 4.17
March 83774853.26 3199.66 20-MAR-18:02 7.83 5.10 93890290.50 56.69 05-MAR-00:20 7.83 5.10
April 0.668954E+09 3468.02 26-APR-15:02 14.83 9.50 93851893.85 56.69 28-APR-22:49 9.33 8.03
May 0.901057E+09 3552.20 21-MAY-15:01 18.83 10.43 97368234.60 56.70 22-MAY-21:10 14.83 12.59
June 0.139917E+10 3499.22 13-JUN-18:02 23.37 16.34 95191066.29 56.70 21-JUN-21:10 13.83 12.18
July 0.166967E+10 3426.28 24-JUL-18:02 17.67 14.85 98389548.13 56.69 21-JUL-21:10 17.67 14.85
August 0.139618E+10 3396.68 27-AUG-15:02 18.17 14.46 98404769.22 56.69 24-AUG-00:49 18.17 14.46
September 0.822232E+09 3423.80 29-SEP-15:01 15.67 9.39 94383476.20 56.69 14-SEP-03:20 15.67 9.39
October 0.191869E+09 3445.90 07-OCT-15:02 18.83 10.03 94741579.97 56.69 07-OCT-23:10 10.83 9.32
November 49256655.64 1464.58 10-NOV-16:02 10.33 8.12 90126301.32 56.69 29-NOV-00:20 -1.0 -1.4
December 17484888.41 99.93 06-DEC-11:02 7.17 5.22 92327267.86 56.69 31-DEC-00:10 1.00 0.58
                     
Annual Sum or Average 0.730080E+10         0.112571E+10        
Minimum of Months 17484888.41 99.93   5.17 4.17 84215653.66 56.69   -1.0 -1.4
Maximum of Months 0.166967E+10 3552.20   23.37 16.34 98404769.22 56.70   18.17 14.85



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.237727E+09 2366.52 11-JAN-16:01 -2.2 -4.4 95665145.61 56.69 17-JAN-22:19 5.10 4.61
February 0.277516E+09 2401.31 18-FEB-16:01 5.83 4.00 86900416.61 56.69 27-FEB-22:19 4.67 4.67
March 0.165512E+09 2373.54 20-MAR-15:01 10.83 7.32 95806587.28 56.69 20-MAR-21:10 4.90 3.99
April 0.842885E+09 2429.20 13-APR-15:02 12.00 7.14 95040993.05 56.69 13-APR-22:10 5.88 4.06
May 0.744174E+09 2432.77 11-MAY-15:01 17.17 9.62 98066384.71 56.69 22-MAY-22:00 14.00 12.24
June 0.915565E+09 2327.33 12-JUN-18:02 25.67 17.63 95340825.96 56.69 26-JUN-22:00 15.00 14.41
July 0.112628E+10 2345.99 26-JUL-15:02 19.68 15.17 98537512.89 56.69 17-JUL-22:40 19.68 15.17
August 0.127827E+10 2336.78 10-AUG-15:02 20.67 15.35 98645076.29 56.69 15-AUG-22:00 14.00 12.84
September 0.124299E+10 2403.17 29-SEP-15:01 15.67 9.39 95374454.25 56.70 11-SEP-21:10 15.67 9.39
October 0.568290E+09 2459.10 07-OCT-15:02 18.83 10.03 96985110.80 56.69 07-OCT-23:00 10.00 8.90
November 0.216041E+09 2411.53 03-NOV-15:01 8.83 5.57 92746682.89 56.69 03-NOV-21:19 4.00 2.72
December 0.102292E+09 2272.53 18-DEC-16:02 5.17 3.90 94513090.98 56.69 31-DEC-00:10 1.00 0.58
                     
Annual Sum or Average 0.771755E+10         0.114362E+10        
Minimum of Months 0.102292E+09 2272.53   -2.2 -4.4 86900416.61 56.69   1.00 0.58
Maximum of Months 0.127827E+10 2459.10   25.67 17.63 98645076.29 56.70   19.68 15.17



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.375097E+11 18575.80 18-JAN-23:00 7.80 7.26 0.151136E+11 9927.17 18-JAN-23:10 7.80 7.23
February 0.344667E+11 18510.29 07-FEB-23:00 7.00 7.00 0.136906E+11 9900.73 07-FEB-23:10 6.83 6.83
March 0.395466E+11 18656.64 17-MAR-22:00 8.00 7.45 0.153829E+11 9966.63 30-MAR-22:10 5.43 3.80
April 0.412603E+11 20484.79 29-APR-18:03 19.67 12.19 0.150266E+11 10278.38 28-APR-21:40 19.67 12.19
May 0.433936E+11 21408.22 22-MAY-18:10 19.00 14.26 0.156707E+11 10394.22 22-MAY-21:40 14.33 12.38
June 0.438991E+11 22203.62 12-JUN-18:10 25.67 17.63 0.154314E+11 10659.52 21-JUN-22:10 12.83 11.81
July 0.459212E+11 22256.21 22-JUL-18:10 29.83 16.84 0.159090E+11 10647.75 25-JUL-22:10 13.00 12.44
August 0.454661E+11 22154.24 14-AUG-17:08 27.00 14.28 0.159314E+11 10546.80 02-AUG-22:10 27.00 14.28
September 0.421877E+11 20493.64 11-SEP-18:10 21.50 15.69 0.151503E+11 10474.07 11-SEP-22:10 12.83 11.23
October 0.405088E+11 19011.88 17-OCT-22:00 11.00 11.00 0.153908E+11 10072.55 12-OCT-22:10 11.00 11.00
November 0.373596E+11 18896.75 08-NOV-23:00 11.00 11.00 0.147438E+11 10022.46 08-NOV-23:10 11.00 11.00
December 0.370184E+11 18252.70 04-DEC-23:00 7.00 7.00 0.150809E+11 9804.00 04-DEC-23:10 7.00 7.00
                     
Annual Sum or Average 0.488538E+12         0.182522E+12        
Minimum of Months 0.344667E+11 18252.70   7.00 7.00 0.136906E+11 9804.00   5.43 3.80
Maximum of Months 0.459212E+11 22256.21   29.83 17.63 0.159314E+11 10659.52   27.00 14.28



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.405662E+11 19786.82 18-JAN-23:00 7.80 7.26 0.152198E+11 10035.27 18-JAN-23:10 7.80 7.23
February 0.372250E+11 19716.50 07-FEB-23:00 7.00 7.00 0.137899E+11 10008.08 07-FEB-23:10 6.83 6.83
March 0.426763E+11 19886.43 17-MAR-22:00 8.00 7.45 0.155085E+11 10078.54 30-MAR-22:10 5.43 3.80
April 0.443281E+11 21823.48 29-APR-18:03 19.67 12.19 0.151584E+11 10387.33 28-APR-22:10 19.67 12.19
May 0.466074E+11 22778.05 22-MAY-18:10 19.00 14.26 0.158167E+11 10508.55 22-MAY-22:10 14.00 12.24
June 0.470688E+11 23613.89 12-JUN-18:10 25.67 17.63 0.155867E+11 10782.84 21-JUN-22:10 12.83 11.81
July 0.491871E+11 23677.26 22-JUL-18:10 29.83 16.84 0.160717E+11 10773.52 25-JUL-22:10 13.00 12.44
August 0.487082E+11 23569.19 14-AUG-17:08 27.00 14.28 0.160817E+11 10669.86 02-AUG-22:10 27.00 14.28
September 0.452599E+11 21788.01 11-SEP-18:10 21.50 15.69 0.152800E+11 10582.01 11-SEP-22:10 12.83 11.23
October 0.436206E+11 20255.36 17-OCT-22:00 11.00 11.00 0.155145E+11 10182.65 12-OCT-22:10 11.00 11.00
November 0.403330E+11 20135.01 08-NOV-23:00 11.00 11.00 0.148567E+11 10134.83 08-NOV-23:10 11.00 11.00
December 0.400938E+11 19445.97 04-DEC-23:00 7.00 7.00 0.151843E+11 9910.70 04-DEC-23:10 7.00 7.00
                     
Annual Sum or Average 0.525674E+12         0.184069E+12        
Minimum of Months 0.372250E+11 19445.97   7.00 7.00 0.137899E+11 9910.70   5.43 3.80
Maximum of Months 0.491871E+11 23677.26   29.83 17.63 0.160817E+11 10782.84   27.00 14.28



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.509090E+11 26672.72 15-JAN-11:50 8.83 6.51 0.186191E+11 11319.61 07-JAN-18:19 8.83 6.51
February 0.463822E+11 26896.83 22-FEB-11:40 10.00 8.60 0.168225E+11 11319.56 18-FEB-18:19 10.00 8.60
March 0.520964E+11 27770.77 25-MAR-10:50 11.42 8.36 0.186356E+11 11319.55 11-MAR-18:19 11.42 8.36
April 0.536528E+11 30429.54 30-APR-10:40 19.33 11.65 0.180535E+11 11327.14 15-APR-17:10 19.33 11.65
May 0.557704E+11 30306.53 23-MAY-10:50 20.00 14.59 0.186590E+11 11323.23 06-MAY-17:00 20.00 14.59
June 0.554119E+11 30626.29 13-JUN-10:40 22.00 15.85 0.180679E+11 11319.74 10-JUN-17:19 22.00 15.85
July 0.578396E+11 31221.45 23-JUL-10:40 21.00 15.99 0.186689E+11 11319.75 15-JUL-17:19 21.00 15.99
August 0.578742E+11 30773.76 14-AUG-17:08 27.00 14.28 0.186732E+11 11319.76 19-AUG-17:19 18.00 14.38
September 0.547856E+11 29955.44 12-SEP-10:40 17.67 14.44 0.180603E+11 11334.10 30-SEP-17:40 11.67 8.71
October 0.534044E+11 28886.76 04-OCT-10:35 13.07 9.87 0.186396E+11 11319.87 07-OCT-17:49 11.67 8.56
November 0.498507E+11 26686.77 11-NOV-11:50 9.00 6.94 0.180231E+11 11319.55 25-NOV-18:19 7.00 4.56
December 0.502151E+11 25726.04 03-DEC-11:50 6.83 4.26 0.186120E+11 11319.54 02-DEC-18:30 6.83 4.26
                     
Annual Sum or Average 0.638192E+12         0.219535E+12        
Minimum of Months 0.463822E+11 25726.04   6.83 4.26 0.168225E+11 11319.54   6.83 4.26
Maximum of Months 0.578742E+11 31221.45   27.00 15.99 0.186732E+11 11334.10   22.00 15.99



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.134445E+10 3777.44 15-JAN-13:00 10.00 6.68 0.126872E+10 745.73 30-JAN-01:39 5.67 5.07
February 0.170108E+10 4167.31 04-FEB-13:40 9.00 6.13 0.114712E+10 745.76 14-FEB-05:00 4.00 2.70
March 0.242526E+10 4013.48 25-MAR-11:50 11.92 8.82 0.127475E+10 745.74 20-MAR-04:30 11.92 8.82
April 0.673506E+10 6741.10 29-APR-17:12 20.00 12.62 0.123139E+10 745.69 08-APR-03:20 20.00 12.62
May 0.743841E+10 6669.91 22-MAY-17:12 19.00 14.26 0.127246E+10 745.71 18-MAY-04:10 19.00 14.26
June 0.923583E+10 7278.48 25-JUN-10:35 20.00 13.96 0.123464E+10 751.62 13-JUN-21:30 20.00 13.96
July 0.104667E+11 7605.39 23-JUL-10:35 21.00 15.99 0.127207E+10 754.11 21-JUL-21:30 21.00 15.99
August 0.103789E+11 7515.19 14-AUG-17:08 27.00 14.28 0.127716E+10 745.69 26-AUG-00:10 14.00 11.92
September 0.842491E+10 6493.49 13-SEP-16:20 23.00 16.07 0.123134E+10 745.70 18-SEP-00:30 12.00 9.30
October 0.441052E+10 5688.90 07-OCT-15:30 18.50 9.89 0.126949E+10 745.75 28-OCT-03:49 8.00 7.44
November 0.196168E+10 3690.09 11-NOV-13:00 9.00 7.43 0.122734E+10 745.75 21-NOV-01:19 2.67 2.23
December 0.564803E+09 2749.62 18-DEC-13:30 8.00 5.46 0.126878E+10 745.74 21-DEC-01:00 5.00 4.09
                     
Annual Sum or Average 0.650876E+11         0.149753E+11        
Minimum of Months 0.564803E+09 2749.62   8.00 5.46 0.114712E+10 745.69   2.67 2.23
Maximum of Months 0.104667E+11 7605.39   27.00 16.07 0.127716E+10 754.11   21.00 15.99



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 1.92
February 0.00 0.00 01-FEB-00:03 7.00
March 0.00 0.00 01-MAR-00:03 3.80
April 0.00 0.00 01-APR-00:10 4.23
May 0.00 0.00 01-MAY-00:10 10.47
June 0.00 0.00 01-JUN-00:10 9.27
July 0.00 0.00 01-JUL-00:10 11.00
August 0.00 0.00 01-AUG-00:10 11.43
September 0.00 0.00 01-SEP-00:10 12.43
October 0.00 0.00 01-OCT-00:10 7.57
November 0.00 0.00 01-NOV-00:10 6.57
December 0.00 0.00 01-DEC-00:03 4.00
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   1.92
Maximum of Months 0.00 0.00   12.43



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.142146E+09 525.39 10-JAN-08:00 -6.0
February 74547518.04 425.65 17-FEB-07:20 -3.7
March 47592495.16 276.90 16-MAR-06:30 1.50
April 1293464.20 102.63 01-APR-06:20 3.33
May 0.00 0.00 01-MAY-00:10 10.47
June 0.00 0.00 01-JUN-00:10 9.27
July 0.00 0.00 01-JUL-00:10 11.00
August 0.00 0.00 01-AUG-00:10 11.43
September 0.00 0.00 01-SEP-00:10 12.43
October 1338224.87 137.82 28-OCT-06:50 4.50
November 57423732.24 338.53 29-NOV-09:10 1.17
December 0.284543E+09 448.22 30-DEC-09:10 0.00
         
Annual Sum or Average 0.608884E+09      
Minimum of Months 0.00 0.00   -6.0
Maximum of Months 0.284543E+09 525.39   12.43



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 1.92
February 0.00 0.00 01-FEB-00:03 7.00
March 0.00 0.00 01-MAR-00:03 3.80
April 0.00 0.00 01-APR-00:10 4.23
May 0.00 0.00 01-MAY-00:10 10.47
June 0.00 0.00 01-JUN-00:10 9.27
July 0.00 0.00 01-JUL-00:10 11.00
August 0.00 0.00 01-AUG-00:10 11.43
September 0.00 0.00 01-SEP-00:10 12.43
October 0.00 0.00 01-OCT-00:10 7.57
November 0.00 0.00 01-NOV-00:10 6.57
December 0.00 0.00 01-DEC-00:03 4.00
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   1.92
Maximum of Months 0.00 0.00   12.43



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 9917418.00 187.85 12-JAN-05:00 -2.0
February 212135.15 39.65 18-FEB-05:00 -3.0
March 0.00 0.00 01-MAR-00:03 3.80
April 0.00 0.00 01-APR-00:10 4.23
May 0.00 0.00 01-MAY-00:10 10.47
June 0.00 0.00 01-JUN-00:10 9.27
July 0.00 0.00 01-JUL-00:10 11.00
August 0.00 0.00 01-AUG-00:10 11.43
September 0.00 0.00 01-SEP-00:10 12.43
October 0.00 0.00 01-OCT-00:10 7.57
November 28911.17 9.96 29-NOV-04:30 -0.5
December 1961916.76 111.77 30-DEC-05:30 -1.5
         
Annual Sum or Average 12120381.09      
Minimum of Months 0.00 0.00   -3.0
Maximum of Months 9917418.00 187.85   12.43



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 89230342.80 231.68 12-JAN-14:00 -1.0
February 37366151.80 138.81 18-FEB-05:10 -2.7
March 7942133.99 96.54 15-MAR-11:50 1.17
April 0.00 0.00 01-APR-00:10 4.23
May 0.00 0.00 01-MAY-00:10 10.47
June 0.00 0.00 01-JUN-00:10 9.27
July 0.00 0.00 01-JUL-00:10 11.00
August 0.00 0.00 01-AUG-00:10 11.43
September 0.00 0.00 01-SEP-00:10 12.43
October 0.00 0.00 01-OCT-00:10 7.57
November 21027376.52 150.93 29-NOV-11:05 3.17
December 0.100758E+09 194.81 30-DEC-17:00 1.00
         
Annual Sum or Average 0.256324E+09      
Minimum of Months 0.00 0.00   -2.7
Maximum of Months 0.100758E+09 231.68   12.43



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 1.92
February 0.00 0.00 01-FEB-00:03 7.00
March 0.00 0.00 01-MAR-00:03 3.80
April 0.00 0.00 01-APR-00:10 4.23
May 0.00 0.00 01-MAY-00:10 10.47
June 0.00 0.00 01-JUN-00:10 9.27
July 0.00 0.00 01-JUL-00:10 11.00
August 0.00 0.00 01-AUG-00:10 11.43
September 0.00 0.00 01-SEP-00:10 12.43
October 0.00 0.00 01-OCT-00:10 7.57
November 0.00 0.00 01-NOV-00:10 6.57
December 0.00 0.00 01-DEC-00:03 4.00
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   1.92
Maximum of Months 0.00 0.00   12.43



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 1.92
February 0.00 0.00 01-FEB-00:03 7.00
March 0.00 0.00 01-MAR-00:03 3.80
April 0.00 0.00 01-APR-00:10 4.23
May 0.00 0.00 01-MAY-00:10 10.47
June 0.00 0.00 01-JUN-00:10 9.27
July 0.00 0.00 01-JUL-00:10 11.00
August 0.00 0.00 01-AUG-00:10 11.43
September 0.00 0.00 01-SEP-00:10 12.43
October 0.00 0.00 01-OCT-00:10 7.57
November 0.00 0.00 01-NOV-00:10 6.57
December 0.00 0.00 01-DEC-00:03 4.00
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   1.92
Maximum of Months 0.00 0.00   12.43



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 1.92
February 0.00 0.00 01-FEB-00:03 7.00
March 0.00 0.00 01-MAR-00:03 3.80
April 0.00 0.00 01-APR-00:10 4.23
May 0.00 0.00 01-MAY-00:10 10.47
June 0.00 0.00 01-JUN-00:10 9.27
July 0.00 0.00 01-JUL-00:10 11.00
August 0.00 0.00 01-AUG-00:10 11.43
September 0.00 0.00 01-SEP-00:10 12.43
October 0.00 0.00 01-OCT-00:10 7.57
November 0.00 0.00 01-NOV-00:10 6.57
December 0.00 0.00 01-DEC-00:03 4.00
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   1.92
Maximum of Months 0.00 0.00   12.43



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.651345E+09 1610.32 03-JAN-16:02 3.83
February 0.461183E+09 1584.24 16-FEB-09:02 3.22
March 0.413215E+09 1593.71 15-MAR-15:02 3.00
April 66560429.92 1491.04 10-APR-15:02 7.17
May 44545485.51 1514.42 05-MAY-08:62 8.17
June 3400167.31 1000.60 18-JUN-08:03 13.17
July 3717660.73 967.89 30-JUL-08:03 14.83
August 1947855.19 914.28 12-AUG-08:03 14.33
September 9917799.35 835.69 06-SEP-18:03 12.83
October 0.178661E+09 1557.12 19-OCT-15:02 9.00
November 0.480093E+09 1611.49 29-NOV-16:02 3.83
December 0.938416E+09 1617.25 27-DEC-16:02 3.00
         
Annual Sum or Average 0.325300E+10      
Minimum of Months 1947855.19 835.69   3.00
Maximum of Months 0.938416E+09 1617.25   14.83



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.860364E+09 1574.35 11-JAN-09:02 -3.8
February 0.629031E+09 1548.14 17-FEB-09:02 1.33
March 0.488573E+09 1547.00 15-MAR-15:02 3.00
April 0.102942E+09 1474.45 11-APR-08:62 7.17
May 53806890.77 1470.98 05-MAY-08:62 8.17
June 3387362.58 751.77 17-JUN-18:04 14.83
July 3866729.08 902.05 04-JUL-08:03 12.00
August 1893840.00 883.83 12-AUG-08:03 14.33
September 18346201.65 860.97 10-SEP-08:03 15.33
October 0.256883E+09 1511.30 19-OCT-15:02 9.00
November 0.627244E+09 1566.75 29-NOV-16:02 3.83
December 0.108363E+10 1572.96 27-DEC-16:02 3.00
         
Annual Sum or Average 0.412997E+10      
Minimum of Months 1893840.00 751.77   -3.8
Maximum of Months 0.108363E+10 1574.35   15.33



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 1.92
February 0.00 0.00 01-FEB-00:03 7.00
March 0.00 0.00 01-MAR-00:03 3.80
April 0.00 0.00 01-APR-00:10 4.23
May 0.00 0.00 01-MAY-00:10 10.47
June 0.00 0.00 01-JUN-00:10 9.27
July 0.00 0.00 01-JUL-00:10 11.00
August 0.00 0.00 01-AUG-00:10 11.43
September 0.00 0.00 01-SEP-00:10 12.43
October 0.00 0.00 01-OCT-00:10 7.57
November 0.00 0.00 01-NOV-00:10 6.57
December 3725419.00 84.46 17-DEC-04:40 1.00
         
Annual Sum or Average 3725419.00      
Minimum of Months 0.00 0.00   1.00
Maximum of Months 3725419.00 84.46   12.43



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 27783427.33 440.66 11-JAN-16:01 -2.2
February 6671581.43 413.89 17-FEB-16:02 5.83
March 1210263.10 411.39 15-MAR-15:02 3.00
April 750051.10 301.58 01-APR-18:04 8.83
May 497928.93 226.22 26-MAY-08:05 10.17
June 144365.99 214.47 27-JUN-08:06 14.67
July 258337.45 240.76 13-JUL-08:06 14.50
August 231018.39 347.05 04-AUG-08:05 14.27
September 564217.09 384.97 29-SEP-15:04 15.67
October 1053268.74 257.20 06-OCT-18:04 11.33
November 5892930.73 425.78 29-NOV-16:02 3.83
December 25600028.96 429.77 27-DEC-16:02 3.00
         
Annual Sum or Average 70657419.24      
Minimum of Months 144365.99 214.47   -2.2
Maximum of Months 27783427.33 440.66   15.67



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.657742E+09 1566.24 12-JAN-16:02 -1.0
February 0.491066E+09 1540.00 01-FEB-16:02 7.00
March 0.419606E+09 1547.35 15-MAR-15:02 3.00
April 62828879.81 1443.05 10-APR-15:02 7.17
May 46004832.58 718.33 14-MAY-15:04 11.83
June 5873596.24 823.69 03-JUN-15:04 16.17
July 2146553.15 754.67 02-JUL-15:04 15.67
August 1027243.20 767.80 26-AUG-15:04 17.00
September 6176835.12 664.12 08-SEP-15:04 14.83
October 0.178596E+09 1511.43 27-OCT-15:02 9.00
November 0.483497E+09 1563.86 29-NOV-16:02 3.83
December 0.900211E+09 1568.45 27-DEC-16:02 3.00
         
Annual Sum or Average 0.325478E+10      
Minimum of Months 1027243.20 664.12   -1.0
Maximum of Months 0.900211E+09 1568.45   17.00



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.854592E+09 1546.43 10-JAN-16:01 -3.0
February 0.670395E+09 1502.16 25-FEB-16:02 5.00
March 0.492996E+09 1504.73 15-MAR-15:02 3.00
April 96790812.37 1410.06 10-APR-15:02 7.17
May 58498975.85 704.11 04-MAY-08:63 9.00
June 6710557.38 836.27 17-JUN-15:04 15.83
July 2551896.36 695.18 07-JUL-15:04 15.83
August 1689714.14 671.10 22-AUG-15:05 17.00
September 13766804.76 929.20 29-SEP-18:03 11.83
October 0.253338E+09 1470.42 27-OCT-15:02 9.00
November 0.623980E+09 1522.44 29-NOV-16:02 3.83
December 0.103078E+10 1528.71 27-DEC-16:02 3.00
         
Annual Sum or Average 0.410608E+10      
Minimum of Months 1689714.14 671.10   -3.0
Maximum of Months 0.103078E+10 1546.43   17.00



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 20174980.55 345.05 04-JAN-15:00 4.00
February 2862648.94 136.45 16-FEB-09:03 3.22
March 872653.55 87.12 15-MAR-13:50 2.83
April 0.00 0.00 01-APR-00:10 4.23
May 0.00 0.00 01-MAY-00:10 10.47
June 0.00 0.00 01-JUN-00:10 9.27
July 0.00 0.00 01-JUL-00:10 11.00
August 0.00 0.00 01-AUG-00:10 11.43
September 0.00 0.00 01-SEP-00:10 12.43
October 0.00 0.00 01-OCT-00:10 7.57
November 9304738.01 292.90 30-NOV-15:00 6.00
December 63560192.34 360.66 10-DEC-16:00 4.00
         
Annual Sum or Average 96775213.39      
Minimum of Months 0.00 0.00   2.83
Maximum of Months 63560192.34 360.66   12.43



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.109233E+10 1944.50 03-JAN-16:02 3.83
February 0.793206E+09 1916.94 16-FEB-09:02 3.22
March 0.730245E+09 1914.52 15-MAR-15:02 3.00
April 0.158776E+09 1824.55 11-APR-08:62 7.17
May 0.105104E+09 1827.26 05-MAY-08:62 8.17
June 8644107.74 973.97 03-JUN-08:03 11.17
July 10959018.24 1009.13 30-JUL-08:03 14.83
August 2141251.99 875.59 03-AUG-08:03 14.17
September 30947181.73 936.73 02-SEP-08:03 13.33
October 0.375155E+09 1888.12 19-OCT-15:02 9.00
November 0.835954E+09 1947.70 29-NOV-16:02 3.83
December 0.145348E+10 1958.86 27-DEC-16:02 3.00
         
Annual Sum or Average 0.559694E+10      
Minimum of Months 2141251.99 875.59   3.00
Maximum of Months 0.145348E+10 1958.86   14.83



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.135997E+10 1899.50 10-JAN-09:02 -3.8
February 0.100933E+10 1864.74 17-FEB-09:02 1.33
March 0.831947E+09 1856.71 15-MAR-08:62 2.00
April 0.219555E+09 1779.64 11-APR-08:62 7.17
May 0.123896E+09 1774.44 05-MAY-08:62 8.17
June 9912817.26 915.58 18-JUN-08:03 13.17
July 11604534.19 974.37 30-JUL-08:03 14.83
August 3262681.73 833.40 26-AUG-15:04 17.00
September 56814626.03 1741.27 20-SEP-08:62 11.50
October 0.502124E+09 1831.87 19-OCT-15:02 9.00
November 0.102523E+10 1892.13 29-NOV-16:02 3.83
December 0.162922E+10 1900.89 27-DEC-16:02 3.00
         
Annual Sum or Average 0.678287E+10      
Minimum of Months 3262681.73 833.40   -3.8
Maximum of Months 0.162922E+10 1900.89   17.00



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.236621E+09 1070.10 04-JAN-16:02 3.92
February 0.164524E+09 1047.21 02-FEB-09:02 4.33
March 0.164627E+09 1052.69 15-MAR-15:02 3.00
April 18305546.71 695.91 10-APR-15:02 7.17
May 15920546.05 533.32 24-MAY-08:03 12.17
June 2304614.68 597.78 20-JUN-08:03 15.17
July 1263677.39 569.77 12-JUL-08:03 13.50
August 882196.67 596.54 04-AUG-08:03 14.27
September 1536864.14 488.46 17-SEP-08:03 12.17
October 46564822.65 1027.43 27-OCT-15:02 9.00
November 0.152706E+09 1069.61 30-NOV-16:02 6.00
December 0.399565E+09 1074.45 27-DEC-16:02 3.00
         
Annual Sum or Average 0.120482E+10      
Minimum of Months 882196.67 488.46   3.00
Maximum of Months 0.399565E+09 1074.45   15.17



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 1.92
February 0.00 0.00 01-FEB-00:03 7.00
March 0.00 0.00 01-MAR-00:03 3.80
April 0.00 0.00 01-APR-00:10 4.23
May 0.00 0.00 01-MAY-00:10 10.47
June 0.00 0.00 01-JUN-00:10 9.27
July 0.00 0.00 01-JUL-00:10 11.00
August 0.00 0.00 01-AUG-00:10 11.43
September 0.00 0.00 01-SEP-00:10 12.43
October 0.00 0.00 01-OCT-00:10 7.57
November 0.00 0.00 01-NOV-00:10 6.57
December 0.00 0.00 01-DEC-00:03 4.00
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   1.92
Maximum of Months 0.00 0.00   12.43



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 1.92
February 0.00 0.00 01-FEB-00:03 7.00
March 0.00 0.00 01-MAR-00:03 3.80
April 0.00 0.00 01-APR-00:10 4.23
May 0.00 0.00 01-MAY-00:10 10.47
June 0.00 0.00 01-JUN-00:10 9.27
July 0.00 0.00 01-JUL-00:10 11.00
August 0.00 0.00 01-AUG-00:10 11.43
September 0.00 0.00 01-SEP-00:10 12.43
October 0.00 0.00 01-OCT-00:10 7.57
November 0.00 0.00 01-NOV-00:10 6.57
December 0.00 0.00 01-DEC-00:03 4.00
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   1.92
Maximum of Months 0.00 0.00   12.43



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 1.92
February 0.00 0.00 01-FEB-00:03 7.00
March 0.00 0.00 01-MAR-00:03 3.80
April 0.00 0.00 01-APR-00:10 4.23
May 0.00 0.00 01-MAY-00:10 10.47
June 0.00 0.00 01-JUN-00:10 9.27
July 0.00 0.00 01-JUL-00:10 11.00
August 0.00 0.00 01-AUG-00:10 11.43
September 0.00 0.00 01-SEP-00:10 12.43
October 0.00 0.00 01-OCT-00:10 7.57
November 0.00 0.00 01-NOV-00:10 6.57
December 0.00 0.00 01-DEC-00:03 4.00
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   1.92
Maximum of Months 0.00 0.00   12.43



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.587317E+09 1747.35 10-JAN-08:00 -6.0
February 0.271905E+09 1656.21 17-FEB-07:30 -3.5
March 0.102036E+09 1028.86 16-MAR-06:10 1.17
April 6478280.96 393.91 09-APR-05:00 1.00
May 0.00 0.00 01-MAY-00:10 10.47
June 0.00 0.00 01-JUN-00:10 9.27
July 0.00 0.00 01-JUL-00:10 11.00
August 0.00 0.00 01-AUG-00:10 11.43
September 0.00 0.00 01-SEP-00:10 12.43
October 5362252.79 454.56 23-OCT-06:10 4.00
November 0.161533E+09 1395.28 29-NOV-09:02 1.17
December 0.801419E+09 1608.70 27-DEC-09:40 0.33
         
Annual Sum or Average 0.193605E+10      
Minimum of Months 0.00 0.00   -6.0
Maximum of Months 0.801419E+09 1747.35   12.43



Table of Contents

Report: ZoneElectricSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.140333E+11 13517.00 02-JAN-20:10 0.127587E+11 10113.80 02-JAN-20:10
February 0.126708E+11 13517.00 01-FEB-20:10 0.115208E+11 10113.80 01-FEB-20:10
March 0.140766E+11 13517.00 01-MAR-20:10 0.127855E+11 10113.80 01-MAR-20:10
April 0.135575E+11 13517.00 03-APR-19:10 0.123314E+11 10113.80 03-APR-19:10
May 0.140576E+11 13517.00 01-MAY-19:10 0.127741E+11 10113.80 01-MAY-19:10
June 0.136197E+11 13517.00 01-JUN-19:10 0.123716E+11 10113.80 01-JUN-19:10
July 0.139955E+11 13517.00 03-JUL-19:10 0.127338E+11 10113.80 03-JUL-19:10
August 0.140820E+11 13517.00 01-AUG-19:10 0.127894E+11 10113.80 01-AUG-19:10
September 0.135629E+11 13517.00 01-SEP-19:10 0.123352E+11 10113.80 01-SEP-19:10
October 0.140279E+11 13517.00 02-OCT-19:10 0.127549E+11 10113.80 02-OCT-19:10
November 0.136089E+11 13517.00 01-NOV-19:10 0.123659E+11 10113.80 01-NOV-19:10
December 0.139955E+11 13517.00 01-DEC-20:10 0.127338E+11 10113.80 01-DEC-20:10
             
Annual Sum or Average 0.165288E+12     0.150255E+12    
Minimum of Months 0.126708E+11 13517.00   0.115208E+11 10113.80  
Maximum of Months 0.140820E+11 13517.00   0.127894E+11 10113.80  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.713551E+09 687.30 02-JAN-20:10 0.864900E+09 685.60 02-JAN-20:10
February 0.644271E+09 687.30 01-FEB-20:10 0.780982E+09 685.60 01-FEB-20:10
March 0.715750E+09 687.30 01-MAR-20:10 0.866718E+09 685.60 01-MAR-20:10
April 0.689358E+09 687.30 03-APR-19:10 0.835931E+09 685.60 03-APR-19:10
May 0.714788E+09 687.30 01-MAY-19:10 0.865939E+09 685.60 01-MAY-19:10
June 0.692519E+09 687.30 01-JUN-19:10 0.838659E+09 685.60 01-JUN-19:10
July 0.711626E+09 687.30 03-JUL-19:10 0.863211E+09 685.60 03-JUL-19:10
August 0.716025E+09 687.30 01-AUG-19:10 0.866978E+09 685.60 01-AUG-19:10
September 0.689633E+09 687.30 01-SEP-19:10 0.836191E+09 685.60 01-SEP-19:10
October 0.713276E+09 687.30 02-OCT-19:10 0.864640E+09 685.60 02-OCT-19:10
November 0.691970E+09 687.30 01-NOV-19:10 0.838269E+09 685.60 01-NOV-19:10
December 0.711626E+09 687.30 01-DEC-20:10 0.863211E+09 685.60 01-DEC-20:10
             
Annual Sum or Average 0.840439E+10     0.101856E+11    
Minimum of Months 0.644271E+09 687.30   0.780982E+09 685.60  
Maximum of Months 0.716025E+09 687.30   0.866978E+09 685.60  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.826294E+09 795.89 02-JAN-20:10 0.100156E+10 793.93 02-JAN-20:10
February 0.746069E+09 795.89 01-FEB-20:10 0.904380E+09 793.93 01-FEB-20:10
March 0.828841E+09 795.89 01-MAR-20:10 0.100366E+10 793.93 01-MAR-20:10
April 0.798279E+09 795.89 03-APR-19:10 0.968011E+09 793.93 03-APR-19:10
May 0.827727E+09 795.89 01-MAY-19:10 0.100276E+10 793.93 01-MAY-19:10
June 0.801940E+09 795.89 01-JUN-19:10 0.971170E+09 793.93 01-JUN-19:10
July 0.824066E+09 795.89 03-JUL-19:10 0.999601E+09 793.93 03-JUL-19:10
August 0.829160E+09 795.89 01-AUG-19:10 0.100396E+10 793.93 01-AUG-19:10
September 0.798597E+09 795.89 01-SEP-19:10 0.968312E+09 793.93 01-SEP-19:10
October 0.825976E+09 795.89 02-OCT-19:10 0.100126E+10 793.93 02-OCT-19:10
November 0.801303E+09 795.89 01-NOV-19:10 0.970719E+09 793.93 01-NOV-19:10
December 0.824066E+09 795.89 01-DEC-20:10 0.999601E+09 793.93 01-DEC-20:10
             
Annual Sum or Average 0.973232E+10     0.117950E+11    
Minimum of Months 0.746069E+09 795.89   0.904380E+09 793.93  
Maximum of Months 0.829160E+09 795.89   0.100396E+10 793.93  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.154452E+10 1487.69 02-JAN-20:10 0.105898E+10 839.45 02-JAN-20:10
February 0.139456E+10 1487.69 01-FEB-20:10 0.956227E+09 839.45 01-FEB-20:10
March 0.154928E+10 1487.69 01-MAR-20:10 0.106120E+10 839.45 01-MAR-20:10
April 0.149215E+10 1487.69 03-APR-19:10 0.102351E+10 839.45 03-APR-19:10
May 0.154719E+10 1487.69 01-MAY-19:10 0.106025E+10 839.45 01-MAY-19:10
June 0.149899E+10 1487.69 01-JUN-19:10 0.102685E+10 839.45 01-JUN-19:10
July 0.154035E+10 1487.69 03-JUL-19:10 0.105691E+10 839.45 03-JUL-19:10
August 0.154987E+10 1487.69 01-AUG-19:10 0.106152E+10 839.45 01-AUG-19:10
September 0.149274E+10 1487.69 01-SEP-19:10 0.102382E+10 839.45 01-SEP-19:10
October 0.154392E+10 1487.69 02-OCT-19:10 0.105866E+10 839.45 02-OCT-19:10
November 0.149780E+10 1487.69 01-NOV-19:10 0.102637E+10 839.45 01-NOV-19:10
December 0.154035E+10 1487.69 01-DEC-20:10 0.105691E+10 839.45 01-DEC-20:10
             
Annual Sum or Average 0.181917E+11     0.124712E+11    
Minimum of Months 0.139456E+10 1487.69   0.956227E+09 839.45  
Maximum of Months 0.154987E+10 1487.69   0.106152E+10 839.45  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.283535E+09 273.10 02-JAN-20:10 0.305485E+09 242.16 02-JAN-20:10
February 0.256006E+09 273.10 01-FEB-20:10 0.275845E+09 242.16 01-FEB-20:10
March 0.284409E+09 273.10 01-MAR-20:10 0.306128E+09 242.16 01-MAR-20:10
April 0.273921E+09 273.10 03-APR-19:10 0.295253E+09 242.16 03-APR-19:10
May 0.284026E+09 273.10 01-MAY-19:10 0.305852E+09 242.16 01-MAY-19:10
June 0.275178E+09 273.10 01-JUN-19:10 0.296217E+09 242.16 01-JUN-19:10
July 0.282770E+09 273.10 03-JUL-19:10 0.304889E+09 242.16 03-JUL-19:10
August 0.284518E+09 273.10 01-AUG-19:10 0.306219E+09 242.16 01-AUG-19:10
September 0.274031E+09 273.10 01-SEP-19:10 0.295345E+09 242.16 01-SEP-19:10
October 0.283425E+09 273.10 02-OCT-19:10 0.305393E+09 242.16 02-OCT-19:10
November 0.274959E+09 273.10 01-NOV-19:10 0.296079E+09 242.16 01-NOV-19:10
December 0.282770E+09 273.10 01-DEC-20:10 0.304889E+09 242.16 01-DEC-20:10
             
Annual Sum or Average 0.333955E+10     0.359760E+10    
Minimum of Months 0.256006E+09 273.10   0.275845E+09 242.16  
Maximum of Months 0.284518E+09 273.10   0.306219E+09 242.16  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.350256E+09 337.37 02-JAN-20:10 0.576866E+10 4572.80 02-JAN-20:10
February 0.316249E+09 337.37 01-FEB-20:10 0.520895E+10 4572.80 01-FEB-20:10
March 0.351336E+09 337.37 01-MAR-20:10 0.578079E+10 4572.80 01-MAR-20:10
April 0.338381E+09 337.37 03-APR-19:10 0.557545E+10 4572.80 03-APR-19:10
May 0.350863E+09 337.37 01-MAY-19:10 0.577559E+10 4572.80 01-MAY-19:10
June 0.339933E+09 337.37 01-JUN-19:10 0.559364E+10 4572.80 01-JUN-19:10
July 0.349311E+09 337.37 03-JUL-19:10 0.575740E+10 4572.80 03-JUL-19:10
August 0.351471E+09 337.37 01-AUG-19:10 0.578252E+10 4572.80 01-AUG-19:10
September 0.338516E+09 337.37 01-SEP-19:10 0.557718E+10 4572.80 01-SEP-19:10
October 0.350121E+09 337.37 02-OCT-19:10 0.576693E+10 4572.80 02-OCT-19:10
November 0.339663E+09 337.37 01-NOV-19:10 0.559104E+10 4572.80 01-NOV-19:10
December 0.349311E+09 337.37 01-DEC-20:10 0.575740E+10 4572.80 01-DEC-20:10
             
Annual Sum or Average 0.412541E+10     0.679355E+11    
Minimum of Months 0.316249E+09 337.37   0.520895E+10 4572.80  
Maximum of Months 0.351471E+09 337.37   0.578252E+10 4572.80  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.226040E+10 2177.23 02-JAN-20:10 0.121771E+10 965.27 02-JAN-20:10
February 0.204093E+10 2177.23 01-FEB-20:10 0.109956E+10 965.27 01-FEB-20:10
March 0.226736E+10 2177.23 01-MAR-20:10 0.122027E+10 965.27 01-MAR-20:10
April 0.218376E+10 2177.23 03-APR-19:10 0.117692E+10 965.27 03-APR-19:10
May 0.226431E+10 2177.23 01-MAY-19:10 0.121917E+10 965.27 01-MAY-19:10
June 0.219377E+10 2177.23 01-JUN-19:10 0.118076E+10 965.27 01-JUN-19:10
July 0.225430E+10 2177.23 03-JUL-19:10 0.121533E+10 965.27 03-JUL-19:10
August 0.226823E+10 2177.23 01-AUG-19:10 0.122063E+10 965.27 01-AUG-19:10
September 0.218463E+10 2177.23 01-SEP-19:10 0.117729E+10 965.27 01-SEP-19:10
October 0.225952E+10 2177.23 02-OCT-19:10 0.121734E+10 965.27 02-OCT-19:10
November 0.219203E+10 2177.23 01-NOV-19:10 0.118021E+10 965.27 01-NOV-19:10
December 0.225430E+10 2177.23 01-DEC-20:10 0.121533E+10 965.27 01-DEC-20:10
             
Annual Sum or Average 0.266236E+11     0.143405E+11    
Minimum of Months 0.204093E+10 2177.23   0.109956E+10 965.27  
Maximum of Months 0.226823E+10 2177.23   0.122063E+10 965.27  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.123020E+11 11849.32 02-JAN-20:10 0.126520E+11 10029.21 02-JAN-20:10
February 0.111075E+11 11849.32 01-FEB-20:10 0.114244E+11 10029.21 01-FEB-20:10
March 0.123399E+11 11849.32 01-MAR-20:10 0.126786E+11 10029.21 01-MAR-20:10
April 0.118849E+11 11849.32 03-APR-19:10 0.122282E+11 10029.21 03-APR-19:10
May 0.123233E+11 11849.32 01-MAY-19:10 0.126672E+11 10029.21 01-MAY-19:10
June 0.119394E+11 11849.32 01-JUN-19:10 0.122682E+11 10029.21 01-JUN-19:10
July 0.122688E+11 11849.32 03-JUL-19:10 0.126273E+11 10029.21 03-JUL-19:10
August 0.123446E+11 11849.32 01-AUG-19:10 0.126824E+11 10029.21 01-AUG-19:10
September 0.118896E+11 11849.32 01-SEP-19:10 0.122320E+11 10029.21 01-SEP-19:10
October 0.122972E+11 11849.32 02-OCT-19:10 0.126482E+11 10029.21 02-OCT-19:10
November 0.119299E+11 11849.32 01-NOV-19:10 0.122624E+11 10029.21 01-NOV-19:10
December 0.122688E+11 11849.32 01-DEC-20:10 0.126273E+11 10029.21 01-DEC-20:10
             
Annual Sum or Average 0.144896E+12     0.148998E+12    
Minimum of Months 0.111075E+11 11849.32   0.114244E+11 10029.21  
Maximum of Months 0.123446E+11 11849.32   0.126824E+11 10029.21  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.434056E+09 392.73 01-JAN-19:10 0.261068E+09 237.06 01-JAN-08:09
February 0.391995E+09 392.73 01-FEB-20:10 0.235798E+09 237.06 01-FEB-07:10
March 0.430607E+09 392.73 01-MAR-20:10 0.260708E+09 237.06 01-MAR-07:10
April 0.420554E+09 392.73 01-APR-18:10 0.252705E+09 237.06 01-APR-07:10
May 0.432331E+09 392.73 01-MAY-19:10 0.260888E+09 237.06 01-MAY-06:10
June 0.417218E+09 392.73 01-JUN-19:10 0.252344E+09 237.06 01-JUN-06:10
July 0.435725E+09 392.73 01-JUL-18:10 0.261248E+09 237.06 01-JUL-07:10
August 0.430607E+09 392.73 01-AUG-19:10 0.260708E+09 237.06 01-AUG-06:10
September 0.420667E+09 392.73 01-SEP-19:10 0.252705E+09 237.06 01-SEP-06:10
October 0.434000E+09 392.73 01-OCT-18:10 0.261068E+09 237.06 01-OCT-07:10
November 0.418886E+09 392.73 01-NOV-19:10 0.252524E+09 237.06 01-NOV-06:10
December 0.435781E+09 392.73 01-DEC-20:10 0.261248E+09 237.06 01-DEC-07:10
             
Annual Sum or Average 0.510243E+10     0.307301E+10    
Minimum of Months 0.391995E+09 392.73   0.235798E+09 237.06  
Maximum of Months 0.435781E+09 392.73   0.261248E+09 237.06  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.434005E+09 392.68 01-JAN-19:10 0.261038E+09 237.03 01-JAN-08:09
February 0.391949E+09 392.68 01-FEB-20:10 0.235770E+09 237.03 01-FEB-07:10
March 0.430556E+09 392.68 01-MAR-20:10 0.260677E+09 237.03 01-MAR-07:10
April 0.420505E+09 392.68 01-APR-18:10 0.252675E+09 237.03 01-APR-07:10
May 0.432281E+09 392.68 01-MAY-19:10 0.260857E+09 237.03 01-MAY-06:10
June 0.417169E+09 392.68 01-JUN-19:10 0.252315E+09 237.03 01-JUN-06:10
July 0.435674E+09 392.68 01-JUL-18:10 0.261218E+09 237.03 01-JUL-07:10
August 0.430556E+09 392.68 01-AUG-19:10 0.260677E+09 237.03 01-AUG-06:10
September 0.420618E+09 392.68 01-SEP-19:10 0.252675E+09 237.03 01-SEP-06:10
October 0.433949E+09 392.68 01-OCT-18:10 0.261038E+09 237.03 01-OCT-07:10
November 0.418837E+09 392.68 01-NOV-19:10 0.252495E+09 237.03 01-NOV-06:10
December 0.435730E+09 392.68 01-DEC-20:10 0.261218E+09 237.03 01-DEC-07:10
             
Annual Sum or Average 0.510183E+10     0.307265E+10    
Minimum of Months 0.391949E+09 392.68   0.235770E+09 237.03  
Maximum of Months 0.435730E+09 392.68   0.261218E+09 237.03  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.272788E+09 246.81 01-JAN-19:10 0.255708E+09 232.19 01-JAN-08:09
February 0.246354E+09 246.81 01-FEB-20:10 0.230956E+09 232.19 01-FEB-07:10
March 0.270620E+09 246.81 01-MAR-20:10 0.255355E+09 232.19 01-MAR-07:10
April 0.264302E+09 246.81 01-APR-18:10 0.247516E+09 232.19 01-APR-07:10
May 0.271704E+09 246.81 01-MAY-19:10 0.255532E+09 232.19 01-MAY-06:10
June 0.262205E+09 246.81 01-JUN-19:10 0.247163E+09 232.19 01-JUN-06:10
July 0.273836E+09 246.81 01-JUL-18:10 0.255885E+09 232.19 01-JUL-07:10
August 0.270620E+09 246.81 01-AUG-19:10 0.255355E+09 232.19 01-AUG-06:10
September 0.264373E+09 246.81 01-SEP-19:10 0.247516E+09 232.19 01-SEP-06:10
October 0.272752E+09 246.81 01-OCT-18:10 0.255708E+09 232.19 01-OCT-07:10
November 0.263254E+09 246.81 01-NOV-19:10 0.247340E+09 232.19 01-NOV-06:10
December 0.273872E+09 246.81 01-DEC-20:10 0.255885E+09 232.19 01-DEC-07:10
             
Annual Sum or Average 0.320668E+10     0.300992E+10    
Minimum of Months 0.246354E+09 246.81   0.230956E+09 232.19  
Maximum of Months 0.273872E+09 246.81   0.255885E+09 232.19  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.272862E+09 246.88 01-JAN-19:10 0.255778E+09 232.26 01-JAN-08:09
February 0.246421E+09 246.88 01-FEB-20:10 0.231020E+09 232.26 01-FEB-07:10
March 0.270694E+09 246.88 01-MAR-20:10 0.255425E+09 232.26 01-MAR-07:10
April 0.264375E+09 246.88 01-APR-18:10 0.247584E+09 232.26 01-APR-07:10
May 0.271778E+09 246.88 01-MAY-19:10 0.255602E+09 232.26 01-MAY-06:10
June 0.262277E+09 246.88 01-JUN-19:10 0.247231E+09 232.26 01-JUN-06:10
July 0.273911E+09 246.88 01-JUL-18:10 0.255955E+09 232.26 01-JUL-07:10
August 0.270694E+09 246.88 01-AUG-19:10 0.255425E+09 232.26 01-AUG-06:10
September 0.264446E+09 246.88 01-SEP-19:10 0.247584E+09 232.26 01-SEP-06:10
October 0.272827E+09 246.88 01-OCT-18:10 0.255778E+09 232.26 01-OCT-07:10
November 0.263326E+09 246.88 01-NOV-19:10 0.247408E+09 232.26 01-NOV-06:10
December 0.273947E+09 246.88 01-DEC-20:10 0.255955E+09 232.26 01-DEC-07:10
             
Annual Sum or Average 0.320756E+10     0.301074E+10    
Minimum of Months 0.246421E+09 246.88   0.231020E+09 232.26  
Maximum of Months 0.273947E+09 246.88   0.255955E+09 232.26  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.434056E+09 392.73 01-JAN-19:10 0.261068E+09 237.06 01-JAN-08:09
February 0.391995E+09 392.73 01-FEB-20:10 0.235798E+09 237.06 01-FEB-07:10
March 0.430607E+09 392.73 01-MAR-20:10 0.260708E+09 237.06 01-MAR-07:10
April 0.420554E+09 392.73 01-APR-18:10 0.252705E+09 237.06 01-APR-07:10
May 0.432331E+09 392.73 01-MAY-19:10 0.260888E+09 237.06 01-MAY-06:10
June 0.417218E+09 392.73 01-JUN-19:10 0.252344E+09 237.06 01-JUN-06:10
July 0.435725E+09 392.73 01-JUL-18:10 0.261248E+09 237.06 01-JUL-07:10
August 0.430607E+09 392.73 01-AUG-19:10 0.260708E+09 237.06 01-AUG-06:10
September 0.420667E+09 392.73 01-SEP-19:10 0.252705E+09 237.06 01-SEP-06:10
October 0.434000E+09 392.73 01-OCT-18:10 0.261068E+09 237.06 01-OCT-07:10
November 0.418886E+09 392.73 01-NOV-19:10 0.252524E+09 237.06 01-NOV-06:10
December 0.435781E+09 392.73 01-DEC-20:10 0.261248E+09 237.06 01-DEC-07:10
             
Annual Sum or Average 0.510243E+10     0.307301E+10    
Minimum of Months 0.391995E+09 392.73   0.235798E+09 237.06  
Maximum of Months 0.435781E+09 392.73   0.261248E+09 237.06  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.434005E+09 392.68 01-JAN-19:10 0.261038E+09 237.03 01-JAN-08:09
February 0.391949E+09 392.68 01-FEB-20:10 0.235770E+09 237.03 01-FEB-07:10
March 0.430556E+09 392.68 01-MAR-20:10 0.260677E+09 237.03 01-MAR-07:10
April 0.420505E+09 392.68 01-APR-18:10 0.252675E+09 237.03 01-APR-07:10
May 0.432281E+09 392.68 01-MAY-19:10 0.260857E+09 237.03 01-MAY-06:10
June 0.417169E+09 392.68 01-JUN-19:10 0.252315E+09 237.03 01-JUN-06:10
July 0.435674E+09 392.68 01-JUL-18:10 0.261218E+09 237.03 01-JUL-07:10
August 0.430556E+09 392.68 01-AUG-19:10 0.260677E+09 237.03 01-AUG-06:10
September 0.420618E+09 392.68 01-SEP-19:10 0.252675E+09 237.03 01-SEP-06:10
October 0.433949E+09 392.68 01-OCT-18:10 0.261038E+09 237.03 01-OCT-07:10
November 0.418837E+09 392.68 01-NOV-19:10 0.252495E+09 237.03 01-NOV-06:10
December 0.435730E+09 392.68 01-DEC-20:10 0.261218E+09 237.03 01-DEC-07:10
             
Annual Sum or Average 0.510183E+10     0.307265E+10    
Minimum of Months 0.391949E+09 392.68   0.235770E+09 237.03  
Maximum of Months 0.435730E+09 392.68   0.261218E+09 237.03  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY []
January 0.133160E+10 1282.60 02-JAN-20:10 0.00 0.00
February 0.120231E+10 1282.60 01-FEB-20:10 0.00 0.00
March 0.133570E+10 1282.60 01-MAR-20:10 0.00 0.00
April 0.128645E+10 1282.60 03-APR-19:10 0.00 0.00
May 0.133391E+10 1282.60 01-MAY-19:10 0.00 0.00
June 0.129235E+10 1282.60 01-JUN-19:10 0.00 0.00
July 0.132801E+10 1282.60 03-JUL-19:10 0.00 0.00
August 0.133622E+10 1282.60 01-AUG-19:10 0.00 0.00
September 0.128696E+10 1282.60 01-SEP-19:10 0.00 0.00
October 0.133109E+10 1282.60 02-OCT-19:10 0.00 0.00
November 0.129132E+10 1282.60 01-NOV-19:10 0.00 0.00
December 0.132801E+10 1282.60 01-DEC-20:10 0.00 0.00
           
Annual Sum or Average 0.156839E+11     0.00 0.00
Minimum of Months 0.120231E+10 1282.60   0.00 0.00
Maximum of Months 0.133622E+10 1282.60   0.00 0.00



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.434056E+09 392.73 01-JAN-19:10 0.261068E+09 237.06 01-JAN-08:09
February 0.391995E+09 392.73 01-FEB-20:10 0.235798E+09 237.06 01-FEB-07:10
March 0.430607E+09 392.73 01-MAR-20:10 0.260708E+09 237.06 01-MAR-07:10
April 0.420554E+09 392.73 01-APR-18:10 0.252705E+09 237.06 01-APR-07:10
May 0.432331E+09 392.73 01-MAY-19:10 0.260888E+09 237.06 01-MAY-06:10
June 0.417218E+09 392.73 01-JUN-19:10 0.252344E+09 237.06 01-JUN-06:10
July 0.435725E+09 392.73 01-JUL-18:10 0.261248E+09 237.06 01-JUL-07:10
August 0.430607E+09 392.73 01-AUG-19:10 0.260708E+09 237.06 01-AUG-06:10
September 0.420667E+09 392.73 01-SEP-19:10 0.252705E+09 237.06 01-SEP-06:10
October 0.434000E+09 392.73 01-OCT-18:10 0.261068E+09 237.06 01-OCT-07:10
November 0.418886E+09 392.73 01-NOV-19:10 0.252524E+09 237.06 01-NOV-06:10
December 0.435781E+09 392.73 01-DEC-20:10 0.261248E+09 237.06 01-DEC-07:10
             
Annual Sum or Average 0.510243E+10     0.307301E+10    
Minimum of Months 0.391995E+09 392.73   0.235798E+09 237.06  
Maximum of Months 0.435781E+09 392.73   0.261248E+09 237.06  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.434005E+09 392.68 01-JAN-19:10 0.261038E+09 237.03 01-JAN-08:09
February 0.391949E+09 392.68 01-FEB-20:10 0.235770E+09 237.03 01-FEB-07:10
March 0.430556E+09 392.68 01-MAR-20:10 0.260677E+09 237.03 01-MAR-07:10
April 0.420505E+09 392.68 01-APR-18:10 0.252675E+09 237.03 01-APR-07:10
May 0.432281E+09 392.68 01-MAY-19:10 0.260857E+09 237.03 01-MAY-06:10
June 0.417169E+09 392.68 01-JUN-19:10 0.252315E+09 237.03 01-JUN-06:10
July 0.435674E+09 392.68 01-JUL-18:10 0.261218E+09 237.03 01-JUL-07:10
August 0.430556E+09 392.68 01-AUG-19:10 0.260677E+09 237.03 01-AUG-06:10
September 0.420618E+09 392.68 01-SEP-19:10 0.252675E+09 237.03 01-SEP-06:10
October 0.433949E+09 392.68 01-OCT-18:10 0.261038E+09 237.03 01-OCT-07:10
November 0.418837E+09 392.68 01-NOV-19:10 0.252495E+09 237.03 01-NOV-06:10
December 0.435730E+09 392.68 01-DEC-20:10 0.261218E+09 237.03 01-DEC-07:10
             
Annual Sum or Average 0.510183E+10     0.307265E+10    
Minimum of Months 0.391949E+09 392.68   0.235770E+09 237.03  
Maximum of Months 0.435730E+09 392.68   0.261218E+09 237.03  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.272862E+09 246.88 01-JAN-19:10 0.255778E+09 232.26 01-JAN-08:09
February 0.246421E+09 246.88 01-FEB-20:10 0.231020E+09 232.26 01-FEB-07:10
March 0.270694E+09 246.88 01-MAR-20:10 0.255425E+09 232.26 01-MAR-07:10
April 0.264375E+09 246.88 01-APR-18:10 0.247584E+09 232.26 01-APR-07:10
May 0.271778E+09 246.88 01-MAY-19:10 0.255602E+09 232.26 01-MAY-06:10
June 0.262277E+09 246.88 01-JUN-19:10 0.247231E+09 232.26 01-JUN-06:10
July 0.273911E+09 246.88 01-JUL-18:10 0.255955E+09 232.26 01-JUL-07:10
August 0.270694E+09 246.88 01-AUG-19:10 0.255425E+09 232.26 01-AUG-06:10
September 0.264446E+09 246.88 01-SEP-19:10 0.247584E+09 232.26 01-SEP-06:10
October 0.272827E+09 246.88 01-OCT-18:10 0.255778E+09 232.26 01-OCT-07:10
November 0.263326E+09 246.88 01-NOV-19:10 0.247408E+09 232.26 01-NOV-06:10
December 0.273947E+09 246.88 01-DEC-20:10 0.255955E+09 232.26 01-DEC-07:10
             
Annual Sum or Average 0.320756E+10     0.301074E+10    
Minimum of Months 0.246421E+09 246.88   0.231020E+09 232.26  
Maximum of Months 0.273947E+09 246.88   0.255955E+09 232.26  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.396945E+10 3823.39 02-JAN-20:10 0.149358E+11 6747.90 01-JAN-07:10
February 0.358405E+10 3823.39 01-FEB-20:10 0.134904E+11 6747.90 01-FEB-07:10
March 0.398168E+10 3823.39 01-MAR-20:10 0.149358E+11 6747.90 01-MAR-07:10
April 0.383486E+10 3823.39 03-APR-19:10 0.144540E+11 6747.90 01-APR-06:10
May 0.397633E+10 3823.39 01-MAY-19:10 0.149358E+11 6747.90 01-MAY-06:10
June 0.385245E+10 3823.39 01-JUN-19:10 0.144540E+11 6747.90 01-JUN-06:10
July 0.395874E+10 3823.39 03-JUL-19:10 0.149358E+11 6747.90 01-JUL-06:10
August 0.398321E+10 3823.39 01-AUG-19:10 0.149358E+11 6747.90 01-AUG-06:10
September 0.383639E+10 3823.39 01-SEP-19:10 0.144540E+11 6747.90 01-SEP-06:10
October 0.396792E+10 3823.39 02-OCT-19:10 0.149358E+11 6747.90 01-OCT-06:10
November 0.384939E+10 3823.39 01-NOV-19:10 0.144540E+11 6747.90 01-NOV-06:10
December 0.395874E+10 3823.39 01-DEC-20:10 0.149358E+11 6747.90 01-DEC-07:10
             
Annual Sum or Average 0.467532E+11     0.175857E+12    
Minimum of Months 0.358405E+10 3823.39   0.134904E+11 6747.90  
Maximum of Months 0.398321E+10 3823.39   0.149358E+11 6747.90  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.396945E+10 3823.39 02-JAN-20:10 0.149358E+11 6747.90 01-JAN-07:10
February 0.358405E+10 3823.39 01-FEB-20:10 0.134904E+11 6747.90 01-FEB-07:10
March 0.398168E+10 3823.39 01-MAR-20:10 0.149358E+11 6747.90 01-MAR-07:10
April 0.383486E+10 3823.39 03-APR-19:10 0.144540E+11 6747.90 01-APR-06:10
May 0.397633E+10 3823.39 01-MAY-19:10 0.149358E+11 6747.90 01-MAY-06:10
June 0.385245E+10 3823.39 01-JUN-19:10 0.144540E+11 6747.90 01-JUN-06:10
July 0.395874E+10 3823.39 03-JUL-19:10 0.149358E+11 6747.90 01-JUL-06:10
August 0.398321E+10 3823.39 01-AUG-19:10 0.149358E+11 6747.90 01-AUG-06:10
September 0.383639E+10 3823.39 01-SEP-19:10 0.144540E+11 6747.90 01-SEP-06:10
October 0.396792E+10 3823.39 02-OCT-19:10 0.149358E+11 6747.90 01-OCT-06:10
November 0.384939E+10 3823.39 01-NOV-19:10 0.144540E+11 6747.90 01-NOV-06:10
December 0.395874E+10 3823.39 01-DEC-20:10 0.149358E+11 6747.90 01-DEC-07:10
             
Annual Sum or Average 0.467532E+11     0.175857E+12    
Minimum of Months 0.358405E+10 3823.39   0.134904E+11 6747.90  
Maximum of Months 0.398321E+10 3823.39   0.149358E+11 6747.90  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.105977E+10 1020.78 02-JAN-20:10 0.373720E+11 16686.59 01-JAN-07:10
February 0.956878E+09 1020.78 01-FEB-20:10 0.337554E+11 16686.59 01-FEB-07:10
March 0.106304E+10 1020.78 01-MAR-20:10 0.373720E+11 16686.59 01-MAR-07:10
April 0.102384E+10 1020.78 03-APR-19:10 0.361665E+11 16686.59 01-APR-06:10
May 0.106161E+10 1020.78 01-MAY-19:10 0.373720E+11 16686.59 01-MAY-06:10
June 0.102854E+10 1020.78 01-JUN-19:10 0.361665E+11 16686.59 01-JUN-06:10
July 0.105691E+10 1020.78 03-JUL-19:10 0.373720E+11 16686.59 01-JUL-06:10
August 0.106345E+10 1020.78 01-AUG-19:10 0.373720E+11 16686.59 01-AUG-06:10
September 0.102425E+10 1020.78 01-SEP-19:10 0.361665E+11 16686.59 01-SEP-06:10
October 0.105936E+10 1020.78 02-OCT-19:10 0.373720E+11 16686.59 01-OCT-06:10
November 0.102772E+10 1020.78 01-NOV-19:10 0.361665E+11 16686.59 01-NOV-06:10
December 0.105691E+10 1020.78 01-DEC-20:10 0.373720E+11 16686.59 01-DEC-07:10
             
Annual Sum or Average 0.124823E+11     0.440025E+12    
Minimum of Months 0.956878E+09 1020.78   0.337554E+11 16686.59  
Maximum of Months 0.106345E+10 1020.78   0.373720E+11 16686.59  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY []
January 0.140929E+10 1357.44 02-JAN-20:10 0.00 0.00
February 0.127246E+10 1357.44 01-FEB-20:10 0.00 0.00
March 0.141364E+10 1357.44 01-MAR-20:10 0.00 0.00
April 0.136151E+10 1357.44 03-APR-19:10 0.00 0.00
May 0.141173E+10 1357.44 01-MAY-19:10 0.00 0.00
June 0.136775E+10 1357.44 01-JUN-19:10 0.00 0.00
July 0.140549E+10 1357.44 03-JUL-19:10 0.00 0.00
August 0.141418E+10 1357.44 01-AUG-19:10 0.00 0.00
September 0.136205E+10 1357.44 01-SEP-19:10 0.00 0.00
October 0.140875E+10 1357.44 02-OCT-19:10 0.00 0.00
November 0.136667E+10 1357.44 01-NOV-19:10 0.00 0.00
December 0.140549E+10 1357.44 01-DEC-20:10 0.00 0.00
           
Annual Sum or Average 0.165990E+11     0.00 0.00
Minimum of Months 0.127246E+10 1357.44   0.00 0.00
Maximum of Months 0.141418E+10 1357.44   0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.195762E+11 0.140333E+11 0.127587E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.176991E+11 0.126708E+11 0.115208E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.196682E+11 0.140766E+11 0.127855E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.189781E+11 0.135575E+11 0.123314E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.196176E+11 0.140576E+11 0.127741E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.190195E+11 0.136197E+11 0.123716E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.195762E+11 0.139955E+11 0.127338E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.196590E+11 0.140820E+11 0.127894E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.189689E+11 0.135629E+11 0.123352E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.195854E+11 0.140279E+11 0.127549E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.189367E+11 0.136089E+11 0.123659E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.195762E+11 0.139955E+11 0.127338E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.230861E+12 0.165288E+12 0.150255E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.176991E+11 0.126708E+11 0.115208E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.196682E+11 0.140820E+11 0.127894E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.199054E+10 0.713551E+09 0.864900E+09 0.00 0.00 0.00 0.00 0.00 0.562626E+09
February 0.179968E+10 0.644271E+09 0.780982E+09 0.00 0.00 0.00 0.00 0.00 0.504423E+09
March 0.199990E+10 0.715750E+09 0.866718E+09 0.00 0.00 0.00 0.00 0.00 0.502486E+09
April 0.192973E+10 0.689358E+09 0.835931E+09 0.00 0.00 0.00 0.00 617930.27 0.386046E+09
May 0.199475E+10 0.714788E+09 0.865939E+09 0.00 0.00 0.00 0.00 258036.21 0.363801E+09
June 0.193394E+10 0.692519E+09 0.838659E+09 0.00 0.00 0.00 0.00 3129631.63 0.245937E+09
July 0.199054E+10 0.711626E+09 0.863211E+09 0.00 0.00 0.00 0.00 6142050.82 0.201459E+09
August 0.199896E+10 0.716025E+09 0.866978E+09 0.00 0.00 0.00 0.00 1951415.91 0.176927E+09
September 0.192879E+10 0.689633E+09 0.836191E+09 0.00 0.00 0.00 0.00 495235.93 0.242358E+09
October 0.199148E+10 0.713276E+09 0.864640E+09 0.00 0.00 0.00 0.00 0.00 0.384806E+09
November 0.192552E+10 0.691970E+09 0.838269E+09 0.00 0.00 0.00 0.00 0.00 0.462376E+09
December 0.199054E+10 0.711626E+09 0.863211E+09 0.00 0.00 0.00 0.00 0.00 0.558901E+09
                   
Annual Sum or Average 0.234744E+11 0.840439E+10 0.101856E+11 0.00 0.00 0.00 0.00 12594300.76 0.459215E+10
Minimum of Months 0.179968E+10 0.644271E+09 0.780982E+09 0.00 0.00 0.00 0.00 0.00 0.176927E+09
Maximum of Months 0.199990E+10 0.716025E+09 0.866978E+09 0.00 0.00 0.00 0.00 6142050.82 0.562626E+09



Table of Contents

Report: SpaceGainsMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.230505E+10 0.826294E+09 0.100156E+10 0.00 0.00 0.00 0.00 0.00 0.217911E+09
February 0.208403E+10 0.746069E+09 0.904380E+09 0.00 0.00 0.00 0.00 0.00 0.194944E+09
March 0.231589E+10 0.828841E+09 0.100366E+10 0.00 0.00 0.00 0.00 0.00 0.194237E+09
April 0.223463E+10 0.798279E+09 0.968011E+09 0.00 0.00 0.00 0.00 285966.29 0.149153E+09
May 0.230993E+10 0.827727E+09 0.100276E+10 0.00 0.00 0.00 0.00 121232.07 0.140966E+09
June 0.223950E+10 0.801940E+09 0.971170E+09 0.00 0.00 0.00 0.00 1242239.61 95807569.77
July 0.230505E+10 0.824066E+09 0.999601E+09 0.00 0.00 0.00 0.00 2419784.39 78687883.20
August 0.231480E+10 0.829160E+09 0.100396E+10 0.00 0.00 0.00 0.00 914774.04 68857277.63
September 0.223354E+10 0.798597E+09 0.968312E+09 0.00 0.00 0.00 0.00 400765.71 93211219.97
October 0.230614E+10 0.825976E+09 0.100126E+10 0.00 0.00 0.00 0.00 0.00 0.148381E+09
November 0.222975E+10 0.801303E+09 0.970719E+09 0.00 0.00 0.00 0.00 0.00 0.178766E+09
December 0.230505E+10 0.824066E+09 0.999601E+09 0.00 0.00 0.00 0.00 0.00 0.217356E+09
                   
Annual Sum or Average 0.271834E+11 0.973232E+10 0.117950E+11 0.00 0.00 0.00 0.00 5384762.11 0.177828E+10
Minimum of Months 0.208403E+10 0.746069E+09 0.904380E+09 0.00 0.00 0.00 0.00 0.00 68857277.63
Maximum of Months 0.231589E+10 0.829160E+09 0.100396E+10 0.00 0.00 0.00 0.00 2419784.39 0.217911E+09



Table of Contents

Report: SpaceGainsMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.487480E+09 0.154452E+10 0.105898E+10 0.00 0.00 0.00 0.00 0.00 0.514897E+09
February 0.440737E+09 0.139456E+10 0.956227E+09 0.00 0.00 0.00 0.00 0.00 0.460581E+09
March 0.489771E+09 0.154928E+10 0.106120E+10 0.00 0.00 0.00 0.00 0.00 0.458804E+09
April 0.472586E+09 0.149215E+10 0.102351E+10 0.00 0.00 0.00 0.00 679312.60 0.351310E+09
May 0.488511E+09 0.154719E+10 0.106025E+10 0.00 0.00 0.00 0.00 286563.14 0.331842E+09
June 0.473617E+09 0.149899E+10 0.102685E+10 0.00 0.00 0.00 0.00 2951302.65 0.224909E+09
July 0.487480E+09 0.154035E+10 0.105691E+10 0.00 0.00 0.00 0.00 5742523.30 0.184277E+09
August 0.489542E+09 0.154987E+10 0.106152E+10 0.00 0.00 0.00 0.00 2171563.81 0.160987E+09
September 0.472357E+09 0.149274E+10 0.102382E+10 0.00 0.00 0.00 0.00 947668.39 0.218718E+09
October 0.487709E+09 0.154392E+10 0.105866E+10 0.00 0.00 0.00 0.00 0.00 0.350030E+09
November 0.471555E+09 0.149780E+10 0.102637E+10 0.00 0.00 0.00 0.00 0.00 0.422318E+09
December 0.487480E+09 0.154035E+10 0.105691E+10 0.00 0.00 0.00 0.00 0.00 0.513668E+09
                   
Annual Sum or Average 0.574883E+10 0.181917E+11 0.124712E+11 0.00 0.00 0.00 0.00 12778933.89 0.419234E+10
Minimum of Months 0.440737E+09 0.139456E+10 0.956227E+09 0.00 0.00 0.00 0.00 0.00 0.160987E+09
Maximum of Months 0.489771E+09 0.154987E+10 0.106152E+10 0.00 0.00 0.00 0.00 5742523.30 0.514897E+09



Table of Contents

Report: SpaceGainsMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.374985E+09 0.283535E+09 0.305485E+09 0.00 0.00 0.00 0.00 0.00 0.297067E+09
February 0.339028E+09 0.256006E+09 0.275845E+09 0.00 0.00 0.00 0.00 0.00 0.265730E+09
March 0.376747E+09 0.284409E+09 0.306128E+09 0.00 0.00 0.00 0.00 0.00 0.264706E+09
April 0.363528E+09 0.273921E+09 0.295253E+09 0.00 0.00 0.00 0.00 392175.87 0.202642E+09
May 0.375778E+09 0.284026E+09 0.305852E+09 0.00 0.00 0.00 0.00 165331.78 0.191354E+09
June 0.364321E+09 0.275178E+09 0.296217E+09 0.00 0.00 0.00 0.00 1708103.26 0.129415E+09
July 0.374985E+09 0.282770E+09 0.304889E+09 0.00 0.00 0.00 0.00 3335238.63 0.105857E+09
August 0.376571E+09 0.284518E+09 0.306219E+09 0.00 0.00 0.00 0.00 1256427.69 92415286.07
September 0.363352E+09 0.274031E+09 0.295345E+09 0.00 0.00 0.00 0.00 546702.04 0.125985E+09
October 0.375161E+09 0.283425E+09 0.305393E+09 0.00 0.00 0.00 0.00 0.00 0.201948E+09
November 0.362735E+09 0.274959E+09 0.296079E+09 0.00 0.00 0.00 0.00 0.00 0.243655E+09
December 0.374985E+09 0.282770E+09 0.304889E+09 0.00 0.00 0.00 0.00 0.00 0.296359E+09
                   
Annual Sum or Average 0.442217E+10 0.333955E+10 0.359760E+10 0.00 0.00 0.00 0.00 7403979.27 0.241713E+10
Minimum of Months 0.339028E+09 0.256006E+09 0.275845E+09 0.00 0.00 0.00 0.00 0.00 92415286.07
Maximum of Months 0.376747E+09 0.284518E+09 0.306219E+09 0.00 0.00 0.00 0.00 3335238.63 0.297067E+09



Table of Contents

Report: SpaceGainsMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.154405E+10 0.350256E+09 0.576866E+10 0.501157E+11 0.00 0.00 0.00 0.00 0.721218E+09
February 0.139600E+10 0.316249E+09 0.520895E+10 0.452532E+11 0.00 0.00 0.00 0.00 0.645225E+09
March 0.155131E+10 0.351336E+09 0.578079E+10 0.502211E+11 0.00 0.00 0.00 0.00 0.644601E+09
April 0.149688E+10 0.338381E+09 0.557545E+10 0.484372E+11 0.00 0.00 0.00 863184.98 0.495548E+09
May 0.154732E+10 0.350863E+09 0.577559E+10 0.501759E+11 0.00 0.00 0.00 390710.99 0.469513E+09
June 0.150015E+10 0.339933E+09 0.559364E+10 0.485952E+11 0.00 0.00 0.00 3859815.01 0.321653E+09
July 0.154405E+10 0.349311E+09 0.575740E+10 0.500179E+11 0.00 0.00 0.00 7649165.79 0.265511E+09
August 0.155059E+10 0.351471E+09 0.578252E+10 0.502361E+11 0.00 0.00 0.00 2855119.35 0.234694E+09
September 0.149615E+10 0.338516E+09 0.557718E+10 0.484522E+11 0.00 0.00 0.00 1289820.90 0.314113E+09
October 0.154478E+10 0.350121E+09 0.576693E+10 0.501006E+11 0.00 0.00 0.00 0.00 0.495295E+09
November 0.149361E+10 0.339663E+09 0.559104E+10 0.485726E+11 0.00 0.00 0.00 0.00 0.594107E+09
December 0.154405E+10 0.349311E+09 0.575740E+10 0.500179E+11 0.00 0.00 0.00 0.00 0.719359E+09
                   
Annual Sum or Average 0.182090E+11 0.412541E+10 0.679355E+11 0.590196E+12 0.00 0.00 0.00 16907817.02 0.592084E+10
Minimum of Months 0.139600E+10 0.316249E+09 0.520895E+10 0.452532E+11 0.00 0.00 0.00 0.00 0.234694E+09
Maximum of Months 0.155131E+10 0.351471E+09 0.578252E+10 0.502361E+11 0.00 0.00 0.00 7649165.79 0.721218E+09



Table of Contents

Report: SpaceGainsMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.261570E+11 0.226040E+10 0.121771E+10 0.00 0.00 0.00 0.00 0.00 0.124781E+10
February 0.236489E+11 0.204093E+10 0.109956E+10 0.00 0.00 0.00 0.00 0.00 0.111687E+10
March 0.262800E+11 0.226736E+10 0.122027E+10 0.00 0.00 0.00 0.00 0.00 0.111192E+10
April 0.253579E+11 0.218376E+10 0.117692E+10 0.00 0.00 0.00 0.00 1523170.32 0.852515E+09
May 0.262123E+11 0.226431E+10 0.121917E+10 0.00 0.00 0.00 0.00 666685.57 0.803943E+09
June 0.254132E+11 0.219377E+10 0.118076E+10 0.00 0.00 0.00 0.00 7158175.13 0.543734E+09
July 0.261570E+11 0.225430E+10 0.121533E+10 0.00 0.00 0.00 0.00 13908339.10 0.444885E+09
August 0.262677E+11 0.226823E+10 0.122063E+10 0.00 0.00 0.00 0.00 4813520.89 0.389400E+09
September 0.253456E+11 0.218463E+10 0.117729E+10 0.00 0.00 0.00 0.00 1341864.43 0.533110E+09
October 0.261693E+11 0.225952E+10 0.121734E+10 0.00 0.00 0.00 0.00 0.00 0.849865E+09
November 0.253025E+11 0.219203E+10 0.118021E+10 0.00 0.00 0.00 0.00 0.00 0.102353E+10
December 0.261570E+11 0.225430E+10 0.121533E+10 0.00 0.00 0.00 0.00 0.00 0.124402E+10
                   
Annual Sum or Average 0.308468E+12 0.266236E+11 0.143405E+11 0.00 0.00 0.00 0.00 29411755.44 0.101616E+11
Minimum of Months 0.236489E+11 0.204093E+10 0.109956E+10 0.00 0.00 0.00 0.00 0.00 0.389400E+09
Maximum of Months 0.262800E+11 0.226823E+10 0.122063E+10 0.00 0.00 0.00 0.00 13908339.10 0.124781E+10



Table of Contents

Report: SpaceGainsMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.776503E+11 0.123020E+11 0.126520E+11 0.00 0.00 0.00 0.00 0.00 0.356738E+10
February 0.702046E+11 0.111075E+11 0.114244E+11 0.00 0.00 0.00 0.00 0.00 0.319157E+10
March 0.780153E+11 0.123399E+11 0.126786E+11 0.00 0.00 0.00 0.00 0.00 0.318047E+10
April 0.752779E+11 0.118849E+11 0.122282E+11 0.00 0.00 0.00 0.00 4703995.63 0.244243E+10
May 0.778146E+11 0.123233E+11 0.126672E+11 0.00 0.00 0.00 0.00 1982933.05 0.230873E+10
June 0.754422E+11 0.119394E+11 0.122682E+11 0.00 0.00 0.00 0.00 20414616.59 0.157158E+10
July 0.776503E+11 0.122688E+11 0.126273E+11 0.00 0.00 0.00 0.00 39764807.62 0.129286E+10
August 0.779788E+11 0.123446E+11 0.126824E+11 0.00 0.00 0.00 0.00 15015117.60 0.113387E+10
September 0.752414E+11 0.118896E+11 0.122320E+11 0.00 0.00 0.00 0.00 6532900.81 0.153121E+10
October 0.776868E+11 0.122972E+11 0.126482E+11 0.00 0.00 0.00 0.00 0.00 0.243097E+10
November 0.751137E+11 0.119299E+11 0.122624E+11 0.00 0.00 0.00 0.00 0.00 0.292738E+10
December 0.776503E+11 0.122688E+11 0.126273E+11 0.00 0.00 0.00 0.00 0.00 0.355792E+10
                   
Annual Sum or Average 0.915726E+12 0.144896E+12 0.148998E+12 0.00 0.00 0.00 0.00 88414371.30 0.291364E+11
Minimum of Months 0.702046E+11 0.111075E+11 0.114244E+11 0.00 0.00 0.00 0.00 0.00 0.113387E+10
Maximum of Months 0.780153E+11 0.123446E+11 0.126824E+11 0.00 0.00 0.00 0.00 39764807.62 0.356738E+10



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.434056E+09 0.261068E+09 0.00 0.00 0.00 0.00 0.00 0.326002E+09
February 0.273974E+09 0.391995E+09 0.235798E+09 0.00 0.00 0.00 0.00 0.00 0.293975E+09
March 0.303685E+09 0.430607E+09 0.260708E+09 0.00 0.00 0.00 0.00 0.00 0.291848E+09
April 0.293479E+09 0.420554E+09 0.252705E+09 0.00 0.00 0.00 0.00 228995.09 0.233309E+09
May 0.303504E+09 0.432331E+09 0.260888E+09 0.00 0.00 0.00 0.00 65450.92 0.221135E+09
June 0.293842E+09 0.417218E+09 0.252344E+09 0.00 0.00 0.00 0.00 970988.06 0.153626E+09
July 0.303141E+09 0.435725E+09 0.261248E+09 0.00 0.00 0.00 0.00 2576440.24 0.128345E+09
August 0.303685E+09 0.430607E+09 0.260708E+09 0.00 0.00 0.00 0.00 728709.87 0.114042E+09
September 0.293479E+09 0.420667E+09 0.252705E+09 0.00 0.00 0.00 0.00 249515.19 0.150211E+09
October 0.303322E+09 0.434000E+09 0.261068E+09 0.00 0.00 0.00 0.00 0.00 0.227613E+09
November 0.293661E+09 0.418886E+09 0.252524E+09 0.00 0.00 0.00 0.00 0.00 0.268126E+09
December 0.303141E+09 0.435781E+09 0.261248E+09 0.00 0.00 0.00 0.00 0.00 0.321586E+09
                   
Annual Sum or Average 0.357224E+10 0.510243E+10 0.307301E+10 0.00 0.00 0.00 0.00 4820099.37 0.272982E+10
Minimum of Months 0.273974E+09 0.391995E+09 0.235798E+09 0.00 0.00 0.00 0.00 0.00 0.114042E+09
Maximum of Months 0.303685E+09 0.435781E+09 0.261248E+09 0.00 0.00 0.00 0.00 2576440.24 0.326002E+09



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.434005E+09 0.261038E+09 0.00 0.00 0.00 0.00 0.00 0.322061E+09
February 0.273974E+09 0.391949E+09 0.235770E+09 0.00 0.00 0.00 0.00 0.00 0.289879E+09
March 0.303685E+09 0.430556E+09 0.260677E+09 0.00 0.00 0.00 0.00 0.00 0.289866E+09
April 0.293479E+09 0.420505E+09 0.252675E+09 0.00 0.00 0.00 0.00 231146.05 0.230173E+09
May 0.303504E+09 0.432281E+09 0.260857E+09 0.00 0.00 0.00 0.00 65843.31 0.219199E+09
June 0.293842E+09 0.417169E+09 0.252315E+09 0.00 0.00 0.00 0.00 969913.63 0.152652E+09
July 0.303141E+09 0.435674E+09 0.261218E+09 0.00 0.00 0.00 0.00 2599912.31 0.127418E+09
August 0.303685E+09 0.430556E+09 0.260677E+09 0.00 0.00 0.00 0.00 733104.96 0.112461E+09
September 0.293479E+09 0.420618E+09 0.252675E+09 0.00 0.00 0.00 0.00 254146.71 0.147233E+09
October 0.303322E+09 0.433949E+09 0.261038E+09 0.00 0.00 0.00 0.00 0.00 0.223923E+09
November 0.293661E+09 0.418837E+09 0.252495E+09 0.00 0.00 0.00 0.00 0.00 0.264727E+09
December 0.303141E+09 0.435730E+09 0.261218E+09 0.00 0.00 0.00 0.00 0.00 0.319050E+09
                   
Annual Sum or Average 0.357224E+10 0.510183E+10 0.307265E+10 0.00 0.00 0.00 0.00 4854066.96 0.269864E+10
Minimum of Months 0.273974E+09 0.391949E+09 0.235770E+09 0.00 0.00 0.00 0.00 0.00 0.112461E+09
Maximum of Months 0.303685E+09 0.435730E+09 0.261218E+09 0.00 0.00 0.00 0.00 2599912.31 0.322061E+09



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.272788E+09 0.255708E+09 0.00 0.00 0.00 0.00 0.00 96297035.00
February 0.00 0.246354E+09 0.230956E+09 0.00 0.00 0.00 0.00 0.00 87483767.45
March 0.00 0.270620E+09 0.255355E+09 0.00 0.00 0.00 0.00 0.00 85970393.70
April 0.00 0.264302E+09 0.247516E+09 0.00 0.00 0.00 0.00 18504.03 73248693.77
May 0.00 0.271704E+09 0.255532E+09 0.00 0.00 0.00 0.00 2652.87 70173681.22
June 0.00 0.262205E+09 0.247163E+09 0.00 0.00 0.00 0.00 138788.52 50973767.67
July 0.00 0.273836E+09 0.255885E+09 0.00 0.00 0.00 0.00 506435.91 44086125.60
August 0.00 0.270620E+09 0.255355E+09 0.00 0.00 0.00 0.00 94347.22 40314263.81
September 0.00 0.264373E+09 0.247516E+09 0.00 0.00 0.00 0.00 0.00 50314249.46
October 0.00 0.272752E+09 0.255708E+09 0.00 0.00 0.00 0.00 0.00 71897361.75
November 0.00 0.263254E+09 0.247340E+09 0.00 0.00 0.00 0.00 0.00 81121972.05
December 0.00 0.273872E+09 0.255885E+09 0.00 0.00 0.00 0.00 0.00 87459761.94
                   
Annual Sum or Average 0.00 0.320668E+10 0.300992E+10 0.00 0.00 0.00 0.00 760728.55 0.839341E+09
Minimum of Months 0.00 0.246354E+09 0.230956E+09 0.00 0.00 0.00 0.00 0.00 40314263.81
Maximum of Months 0.00 0.273872E+09 0.255885E+09 0.00 0.00 0.00 0.00 506435.91 96297035.00



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.272862E+09 0.255778E+09 0.00 0.00 0.00 0.00 0.00 91710379.29
February 0.273974E+09 0.246421E+09 0.231020E+09 0.00 0.00 0.00 0.00 0.00 82256154.29
March 0.303685E+09 0.270694E+09 0.255425E+09 0.00 0.00 0.00 0.00 0.00 82564183.75
April 0.293479E+09 0.264375E+09 0.247584E+09 0.00 0.00 0.00 0.00 73082.38 64268362.26
May 0.303504E+09 0.271778E+09 0.255602E+09 0.00 0.00 0.00 0.00 23555.51 61127910.91
June 0.293842E+09 0.262277E+09 0.247231E+09 0.00 0.00 0.00 0.00 294397.22 42242984.31
July 0.303141E+09 0.273911E+09 0.255955E+09 0.00 0.00 0.00 0.00 774055.98 35129724.03
August 0.303685E+09 0.270694E+09 0.255425E+09 0.00 0.00 0.00 0.00 236120.07 30748673.80
September 0.293479E+09 0.264446E+09 0.247584E+09 0.00 0.00 0.00 0.00 78951.45 40780660.58
October 0.303322E+09 0.272827E+09 0.255778E+09 0.00 0.00 0.00 0.00 0.00 63544135.85
November 0.293661E+09 0.263326E+09 0.247408E+09 0.00 0.00 0.00 0.00 0.00 75625829.76
December 0.303141E+09 0.273947E+09 0.255955E+09 0.00 0.00 0.00 0.00 0.00 91237714.29
                   
Annual Sum or Average 0.357224E+10 0.320756E+10 0.301074E+10 0.00 0.00 0.00 0.00 1480162.62 0.761237E+09
Minimum of Months 0.273974E+09 0.246421E+09 0.231020E+09 0.00 0.00 0.00 0.00 0.00 30748673.80
Maximum of Months 0.303685E+09 0.273947E+09 0.255955E+09 0.00 0.00 0.00 0.00 774055.98 91710379.29



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.434056E+09 0.261068E+09 0.00 0.00 0.00 0.00 0.00 0.325914E+09
February 0.273974E+09 0.391995E+09 0.235798E+09 0.00 0.00 0.00 0.00 0.00 0.293770E+09
March 0.303685E+09 0.430607E+09 0.260708E+09 0.00 0.00 0.00 0.00 0.00 0.292382E+09
April 0.293479E+09 0.420554E+09 0.252705E+09 0.00 0.00 0.00 0.00 237247.41 0.235327E+09
May 0.303504E+09 0.432331E+09 0.260888E+09 0.00 0.00 0.00 0.00 66511.75 0.222884E+09
June 0.293842E+09 0.417218E+09 0.252344E+09 0.00 0.00 0.00 0.00 981649.09 0.154447E+09
July 0.303141E+09 0.435725E+09 0.261248E+09 0.00 0.00 0.00 0.00 2559441.92 0.129285E+09
August 0.303685E+09 0.430607E+09 0.260708E+09 0.00 0.00 0.00 0.00 734431.29 0.114771E+09
September 0.293479E+09 0.420667E+09 0.252705E+09 0.00 0.00 0.00 0.00 255523.02 0.151453E+09
October 0.303322E+09 0.434000E+09 0.261068E+09 0.00 0.00 0.00 0.00 0.00 0.228390E+09
November 0.293661E+09 0.418886E+09 0.252524E+09 0.00 0.00 0.00 0.00 0.00 0.268022E+09
December 0.303141E+09 0.435781E+09 0.261248E+09 0.00 0.00 0.00 0.00 0.00 0.321903E+09
                   
Annual Sum or Average 0.357224E+10 0.510243E+10 0.307301E+10 0.00 0.00 0.00 0.00 4834804.48 0.273855E+10
Minimum of Months 0.273974E+09 0.391995E+09 0.235798E+09 0.00 0.00 0.00 0.00 0.00 0.114771E+09
Maximum of Months 0.303685E+09 0.435781E+09 0.261248E+09 0.00 0.00 0.00 0.00 2559441.92 0.325914E+09



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.434005E+09 0.261038E+09 0.00 0.00 0.00 0.00 0.00 0.322058E+09
February 0.273974E+09 0.391949E+09 0.235770E+09 0.00 0.00 0.00 0.00 0.00 0.289474E+09
March 0.303685E+09 0.430556E+09 0.260677E+09 0.00 0.00 0.00 0.00 0.00 0.290454E+09
April 0.293479E+09 0.420505E+09 0.252675E+09 0.00 0.00 0.00 0.00 240029.18 0.233386E+09
May 0.303504E+09 0.432281E+09 0.260857E+09 0.00 0.00 0.00 0.00 66624.61 0.221799E+09
June 0.293842E+09 0.417169E+09 0.252315E+09 0.00 0.00 0.00 0.00 982823.41 0.154002E+09
July 0.303141E+09 0.435674E+09 0.261218E+09 0.00 0.00 0.00 0.00 2561437.56 0.129040E+09
August 0.303685E+09 0.430556E+09 0.260677E+09 0.00 0.00 0.00 0.00 737322.99 0.114377E+09
September 0.293479E+09 0.420618E+09 0.252675E+09 0.00 0.00 0.00 0.00 259071.51 0.150319E+09
October 0.303322E+09 0.433949E+09 0.261038E+09 0.00 0.00 0.00 0.00 0.00 0.225179E+09
November 0.293661E+09 0.418837E+09 0.252495E+09 0.00 0.00 0.00 0.00 0.00 0.264602E+09
December 0.303141E+09 0.435730E+09 0.261218E+09 0.00 0.00 0.00 0.00 0.00 0.319358E+09
                   
Annual Sum or Average 0.357224E+10 0.510183E+10 0.307265E+10 0.00 0.00 0.00 0.00 4847309.26 0.271405E+10
Minimum of Months 0.273974E+09 0.391949E+09 0.235770E+09 0.00 0.00 0.00 0.00 0.00 0.114377E+09
Maximum of Months 0.303685E+09 0.435730E+09 0.261218E+09 0.00 0.00 0.00 0.00 2561437.56 0.322058E+09



Table of Contents

Report: SpaceGainsMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.385223E+10 0.133160E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.397144E+09
February 0.348285E+10 0.120231E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.355253E+09
March 0.387034E+10 0.133570E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.353981E+09
April 0.373454E+10 0.128645E+10 0.00 0.00 0.00 0.00 0.00 450138.95 0.271642E+09
May 0.386038E+10 0.133391E+10 0.00 0.00 0.00 0.00 0.00 190054.31 0.256658E+09
June 0.374269E+10 0.129235E+10 0.00 0.00 0.00 0.00 0.00 2042148.79 0.174518E+09
July 0.385223E+10 0.132801E+10 0.00 0.00 0.00 0.00 0.00 4072789.58 0.144351E+09
August 0.386853E+10 0.133622E+10 0.00 0.00 0.00 0.00 0.00 1443684.07 0.126450E+09
September 0.373273E+10 0.128696E+10 0.00 0.00 0.00 0.00 0.00 432796.45 0.170532E+09
October 0.385404E+10 0.133109E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.270411E+09
November 0.372639E+10 0.129132E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.325879E+09
December 0.385223E+10 0.132801E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.396190E+09
                   
Annual Sum or Average 0.454292E+11 0.156839E+11 0.00 0.00 0.00 0.00 0.00 8631612.15 0.324301E+10
Minimum of Months 0.348285E+10 0.120231E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.126450E+09
Maximum of Months 0.387034E+10 0.133622E+10 0.00 0.00 0.00 0.00 0.00 4072789.58 0.397144E+09



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.434056E+09 0.261068E+09 0.00 0.00 0.00 0.00 0.00 0.325068E+09
February 0.273974E+09 0.391995E+09 0.235798E+09 0.00 0.00 0.00 0.00 0.00 0.293200E+09
March 0.303685E+09 0.430607E+09 0.260708E+09 0.00 0.00 0.00 0.00 0.00 0.291310E+09
April 0.293479E+09 0.420554E+09 0.252705E+09 0.00 0.00 0.00 0.00 207775.55 0.234374E+09
May 0.303504E+09 0.432331E+09 0.260888E+09 0.00 0.00 0.00 0.00 61200.44 0.222351E+09
June 0.293842E+09 0.417218E+09 0.252344E+09 0.00 0.00 0.00 0.00 935263.56 0.155000E+09
July 0.303141E+09 0.435725E+09 0.261248E+09 0.00 0.00 0.00 0.00 2506318.53 0.129707E+09
August 0.303685E+09 0.430607E+09 0.260708E+09 0.00 0.00 0.00 0.00 703404.14 0.115309E+09
September 0.293479E+09 0.420667E+09 0.252705E+09 0.00 0.00 0.00 0.00 231162.05 0.151353E+09
October 0.303322E+09 0.434000E+09 0.261068E+09 0.00 0.00 0.00 0.00 0.00 0.227487E+09
November 0.293661E+09 0.418886E+09 0.252524E+09 0.00 0.00 0.00 0.00 0.00 0.267193E+09
December 0.303141E+09 0.435781E+09 0.261248E+09 0.00 0.00 0.00 0.00 0.00 0.321042E+09
                   
Annual Sum or Average 0.357224E+10 0.510243E+10 0.307301E+10 0.00 0.00 0.00 0.00 4645124.27 0.273339E+10
Minimum of Months 0.273974E+09 0.391995E+09 0.235798E+09 0.00 0.00 0.00 0.00 0.00 0.115309E+09
Maximum of Months 0.303685E+09 0.435781E+09 0.261248E+09 0.00 0.00 0.00 0.00 2506318.53 0.325068E+09



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.434005E+09 0.261038E+09 0.00 0.00 0.00 0.00 0.00 0.321486E+09
February 0.273974E+09 0.391949E+09 0.235770E+09 0.00 0.00 0.00 0.00 0.00 0.288964E+09
March 0.303685E+09 0.430556E+09 0.260677E+09 0.00 0.00 0.00 0.00 0.00 0.289200E+09
April 0.293479E+09 0.420505E+09 0.252675E+09 0.00 0.00 0.00 0.00 212256.95 0.231571E+09
May 0.303504E+09 0.432281E+09 0.260857E+09 0.00 0.00 0.00 0.00 61848.26 0.220751E+09
June 0.293842E+09 0.417169E+09 0.252315E+09 0.00 0.00 0.00 0.00 932169.82 0.154438E+09
July 0.303141E+09 0.435674E+09 0.261218E+09 0.00 0.00 0.00 0.00 2514717.17 0.129233E+09
August 0.303685E+09 0.430556E+09 0.260677E+09 0.00 0.00 0.00 0.00 708623.79 0.114435E+09
September 0.293479E+09 0.420618E+09 0.252675E+09 0.00 0.00 0.00 0.00 237944.39 0.148828E+09
October 0.303322E+09 0.433949E+09 0.261038E+09 0.00 0.00 0.00 0.00 0.00 0.223654E+09
November 0.293661E+09 0.418837E+09 0.252495E+09 0.00 0.00 0.00 0.00 0.00 0.263749E+09
December 0.303141E+09 0.435730E+09 0.261218E+09 0.00 0.00 0.00 0.00 0.00 0.319111E+09
                   
Annual Sum or Average 0.357224E+10 0.510183E+10 0.307265E+10 0.00 0.00 0.00 0.00 4667560.38 0.270542E+10
Minimum of Months 0.273974E+09 0.391949E+09 0.235770E+09 0.00 0.00 0.00 0.00 0.00 0.114435E+09
Maximum of Months 0.303685E+09 0.435730E+09 0.261218E+09 0.00 0.00 0.00 0.00 2514717.17 0.321486E+09



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.272862E+09 0.255778E+09 0.00 0.00 0.00 0.00 0.00 0.170218E+09
February 0.273974E+09 0.246421E+09 0.231020E+09 0.00 0.00 0.00 0.00 0.00 0.153135E+09
March 0.303685E+09 0.270694E+09 0.255425E+09 0.00 0.00 0.00 0.00 0.00 0.151859E+09
April 0.293479E+09 0.264375E+09 0.247584E+09 0.00 0.00 0.00 0.00 116198.26 0.120905E+09
May 0.303504E+09 0.271778E+09 0.255602E+09 0.00 0.00 0.00 0.00 32389.26 0.114408E+09
June 0.293842E+09 0.262277E+09 0.247231E+09 0.00 0.00 0.00 0.00 485375.23 79381962.58
July 0.303141E+09 0.273911E+09 0.255955E+09 0.00 0.00 0.00 0.00 1289661.86 66425890.64
August 0.303685E+09 0.270694E+09 0.255425E+09 0.00 0.00 0.00 0.00 362593.35 59068390.15
September 0.293479E+09 0.264446E+09 0.247584E+09 0.00 0.00 0.00 0.00 116496.43 77974417.66
October 0.303322E+09 0.272827E+09 0.255778E+09 0.00 0.00 0.00 0.00 0.00 0.118663E+09
November 0.293661E+09 0.263326E+09 0.247408E+09 0.00 0.00 0.00 0.00 0.00 0.140155E+09
December 0.303141E+09 0.273947E+09 0.255955E+09 0.00 0.00 0.00 0.00 0.00 0.167818E+09
                   
Annual Sum or Average 0.357224E+10 0.320756E+10 0.301074E+10 0.00 0.00 0.00 0.00 2402714.39 0.142001E+10
Minimum of Months 0.273974E+09 0.246421E+09 0.231020E+09 0.00 0.00 0.00 0.00 0.00 59068390.15
Maximum of Months 0.303685E+09 0.273947E+09 0.255955E+09 0.00 0.00 0.00 0.00 1289661.86 0.170218E+09



Table of Contents

Report: SpaceGainsMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.459349E+11 0.396945E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.00 0.821956E+09
February 0.415303E+11 0.358405E+10 0.134904E+11 0.00 0.00 0.00 0.00 0.00 0.735878E+09
March 0.461508E+11 0.398168E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.00 0.738992E+09
April 0.445315E+11 0.383486E+10 0.144540E+11 0.00 0.00 0.00 0.00 940762.33 0.575101E+09
May 0.460320E+11 0.397633E+10 0.149358E+11 0.00 0.00 0.00 0.00 344090.24 0.548834E+09
June 0.446286E+11 0.385245E+10 0.144540E+11 0.00 0.00 0.00 0.00 3737300.10 0.385345E+09
July 0.459349E+11 0.395874E+10 0.149358E+11 0.00 0.00 0.00 0.00 7800297.92 0.323488E+09
August 0.461292E+11 0.398321E+10 0.149358E+11 0.00 0.00 0.00 0.00 2861154.30 0.286241E+09
September 0.445099E+11 0.383639E+10 0.144540E+11 0.00 0.00 0.00 0.00 1076226.79 0.370557E+09
October 0.459565E+11 0.396792E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.00 0.571206E+09
November 0.444343E+11 0.384939E+10 0.144540E+11 0.00 0.00 0.00 0.00 0.00 0.679827E+09
December 0.459349E+11 0.395874E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.00 0.819195E+09
                   
Annual Sum or Average 0.541708E+12 0.467532E+11 0.175857E+12 0.00 0.00 0.00 0.00 16759831.69 0.685662E+10
Minimum of Months 0.415303E+11 0.358405E+10 0.134904E+11 0.00 0.00 0.00 0.00 0.00 0.286241E+09
Maximum of Months 0.461508E+11 0.398321E+10 0.149358E+11 0.00 0.00 0.00 0.00 7800297.92 0.821956E+09



Table of Contents

Report: SpaceGainsMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.459349E+11 0.396945E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.00 0.824400E+09
February 0.415303E+11 0.358405E+10 0.134904E+11 0.00 0.00 0.00 0.00 0.00 0.738201E+09
March 0.461508E+11 0.398168E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.00 0.741966E+09
April 0.445315E+11 0.383486E+10 0.144540E+11 0.00 0.00 0.00 0.00 897383.15 0.578467E+09
May 0.460320E+11 0.397633E+10 0.149358E+11 0.00 0.00 0.00 0.00 318541.67 0.552688E+09
June 0.446286E+11 0.385245E+10 0.144540E+11 0.00 0.00 0.00 0.00 3518301.27 0.389399E+09
July 0.459349E+11 0.395874E+10 0.149358E+11 0.00 0.00 0.00 0.00 7555072.15 0.327885E+09
August 0.461292E+11 0.398321E+10 0.149358E+11 0.00 0.00 0.00 0.00 2745781.60 0.290192E+09
September 0.445099E+11 0.383639E+10 0.144540E+11 0.00 0.00 0.00 0.00 985140.85 0.373807E+09
October 0.459565E+11 0.396792E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.00 0.574190E+09
November 0.444343E+11 0.384939E+10 0.144540E+11 0.00 0.00 0.00 0.00 0.00 0.682496E+09
December 0.459349E+11 0.395874E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.00 0.821520E+09
                   
Annual Sum or Average 0.541708E+12 0.467532E+11 0.175857E+12 0.00 0.00 0.00 0.00 16020220.69 0.689521E+10
Minimum of Months 0.415303E+11 0.358405E+10 0.134904E+11 0.00 0.00 0.00 0.00 0.00 0.290192E+09
Maximum of Months 0.461508E+11 0.398321E+10 0.149358E+11 0.00 0.00 0.00 0.00 7555072.15 0.824400E+09



Table of Contents

Report: SpaceGainsMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.408770E+10 0.105977E+10 0.338870E+11 0.305408E+11 0.00 0.00 0.00 0.00 0.789925E+09
February 0.369574E+10 0.956878E+09 0.306077E+11 0.275852E+11 0.00 0.00 0.00 0.00 0.708662E+09
March 0.410691E+10 0.106304E+10 0.338870E+11 0.305408E+11 0.00 0.00 0.00 0.00 0.714948E+09
April 0.396281E+10 0.102384E+10 0.327939E+11 0.295556E+11 0.00 0.00 0.00 0.00 0.569854E+09
May 0.409635E+10 0.106161E+10 0.338870E+11 0.305408E+11 0.00 0.00 0.00 0.00 0.546846E+09
June 0.397146E+10 0.102854E+10 0.327939E+11 0.295556E+11 0.00 0.00 0.00 598721.31 0.392875E+09
July 0.408770E+10 0.105691E+10 0.338870E+11 0.305408E+11 0.00 0.00 0.00 3106966.11 0.338057E+09
August 0.410499E+10 0.106345E+10 0.338870E+11 0.305408E+11 0.00 0.00 0.00 446030.58 0.307612E+09
September 0.396089E+10 0.102425E+10 0.327939E+11 0.295556E+11 0.00 0.00 0.00 0.00 0.385601E+09
October 0.408962E+10 0.105936E+10 0.338870E+11 0.305408E+11 0.00 0.00 0.00 0.00 0.566164E+09
November 0.395417E+10 0.102772E+10 0.327939E+11 0.295556E+11 0.00 0.00 0.00 0.00 0.659919E+09
December 0.408770E+10 0.105691E+10 0.338870E+11 0.305408E+11 0.00 0.00 0.00 0.00 0.785099E+09
                   
Annual Sum or Average 0.482060E+11 0.124823E+11 0.398993E+12 0.359593E+12 0.00 0.00 0.00 4151718.01 0.676556E+10
Minimum of Months 0.369574E+10 0.956878E+09 0.306077E+11 0.275852E+11 0.00 0.00 0.00 0.00 0.307612E+09
Maximum of Months 0.410691E+10 0.106345E+10 0.338870E+11 0.305408E+11 0.00 0.00 0.00 3106966.11 0.789925E+09



Table of Contents

Report: SpaceGainsMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.407704E+10 0.140929E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.705274E+09
February 0.368610E+10 0.127246E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.630911E+09
March 0.409620E+10 0.141364E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.628896E+09
April 0.395248E+10 0.136151E+10 0.00 0.00 0.00 0.00 0.00 742080.08 0.482823E+09
May 0.408566E+10 0.141173E+10 0.00 0.00 0.00 0.00 0.00 270118.95 0.456173E+09
June 0.396110E+10 0.136775E+10 0.00 0.00 0.00 0.00 0.00 3304913.22 0.309642E+09
July 0.407704E+10 0.140549E+10 0.00 0.00 0.00 0.00 0.00 7077592.08 0.254711E+09
August 0.409429E+10 0.141418E+10 0.00 0.00 0.00 0.00 0.00 2409278.55 0.223306E+09
September 0.395056E+10 0.136205E+10 0.00 0.00 0.00 0.00 0.00 778091.36 0.301852E+09
October 0.407896E+10 0.140875E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.480799E+09
November 0.394385E+10 0.136667E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.579087E+09
December 0.407704E+10 0.140549E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.703597E+09
                   
Annual Sum or Average 0.480803E+11 0.165990E+11 0.00 0.00 0.00 0.00 0.00 14582074.24 0.575707E+10
Minimum of Months 0.368610E+10 0.127246E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.223306E+09
Maximum of Months 0.409620E+10 0.141418E+10 0.00 0.00 0.00 0.00 0.00 7077592.08 0.705274E+09



Table of Contents

Report: PeakSpaceGainsMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 11501.89 02-JAN-00:10 13517.00 02-JAN-20:10 10113.80 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 0.00
February 11501.89 01-FEB-00:10 13517.00 01-FEB-20:10 10113.80 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 0.00
March 11501.89 01-MAR-00:10 13517.00 01-MAR-20:10 10113.80 01-MAR-20:10 0.00 0.00 0.00 0.00 0.00 0.00
April 11501.89 01-APR-00:10 13517.00 03-APR-19:10 10113.80 03-APR-19:10 0.00 0.00 0.00 0.00 0.00 0.00
May 11501.89 01-MAY-00:10 13517.00 01-MAY-19:10 10113.80 01-MAY-19:10 0.00 0.00 0.00 0.00 0.00 0.00
June 11501.89 01-JUN-00:10 13517.00 01-JUN-19:10 10113.80 01-JUN-19:10 0.00 0.00 0.00 0.00 0.00 0.00
July 11501.89 01-JUL-00:10 13517.00 03-JUL-19:10 10113.80 03-JUL-19:10 0.00 0.00 0.00 0.00 0.00 0.00
August 11501.89 01-AUG-00:10 13517.00 01-AUG-19:10 10113.80 01-AUG-19:10 0.00 0.00 0.00 0.00 0.00 0.00
September 11501.89 01-SEP-00:10 13517.00 01-SEP-19:10 10113.80 01-SEP-19:10 0.00 0.00 0.00 0.00 0.00 0.00
October 11501.89 01-OCT-23:10 13517.00 02-OCT-19:10 10113.80 02-OCT-19:10 0.00 0.00 0.00 0.00 0.00 0.00
November 11501.89 01-NOV-00:10 13517.00 01-NOV-19:10 10113.80 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 0.00
December 11501.89 01-DEC-00:10 13517.00 01-DEC-20:10 10113.80 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 11501.89   13517.00   10113.80   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 11501.89   13517.00   10113.80   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1169.53 02-JAN-00:10 687.30 02-JAN-20:10 685.60 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 347.94 11-JAN-23:53
February 1169.53 01-FEB-00:10 687.30 01-FEB-20:10 685.60 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 316.24 17-FEB-07:00
March 1169.53 01-MAR-00:10 687.30 01-MAR-20:10 685.60 01-MAR-20:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:03 277.95 08-MAR-07:00
April 1169.53 01-APR-00:10 687.30 03-APR-19:10 685.60 03-APR-19:10 0.00 0.00 0.00 0.00 34.89 30-APR-19:00 265.44 08-APR-06:00
May 1169.53 01-MAY-00:10 687.30 01-MAY-19:10 685.60 01-MAY-19:10 0.00 0.00 0.00 0.00 32.78 22-MAY-15:10 240.83 06-MAY-05:00
June 1169.53 01-JUN-00:10 687.30 01-JUN-19:10 685.60 01-JUN-19:10 0.00 0.00 0.00 0.00 68.85 13-JUN-17:00 186.91 07-JUN-05:00
July 1169.53 01-JUL-00:10 687.30 03-JUL-19:10 685.60 03-JUL-19:10 0.00 0.00 0.00 0.00 102.02 22-JUL-18:00 173.76 31-JUL-05:00
August 1169.53 01-AUG-00:10 687.30 01-AUG-19:10 685.60 01-AUG-19:10 0.00 0.00 0.00 0.00 69.07 14-AUG-17:17 160.58 24-AUG-06:00
September 1169.53 01-SEP-00:10 687.30 01-SEP-19:10 685.60 01-SEP-19:10 0.00 0.00 0.00 0.00 23.27 13-SEP-17:00 200.65 21-SEP-06:00
October 1169.53 01-OCT-23:10 687.30 02-OCT-19:10 685.60 02-OCT-19:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 239.25 15-OCT-04:00
November 1169.53 01-NOV-00:10 687.30 01-NOV-19:10 685.60 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 295.56 29-NOV-02:00
December 1169.53 01-DEC-00:10 687.30 01-DEC-20:10 685.60 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 306.62 29-DEC-23:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1169.53   687.30   685.60   0.00 0.00 0.00 0.00 0.00   160.58  
Maximum of Months 1169.53   687.30   685.60   0.00 0.00 0.00 0.00 102.02   347.94  



Table of Contents

Report: PeakSpaceGainsMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1354.32 02-JAN-00:10 795.89 02-JAN-20:10 793.93 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 134.36 11-JAN-24:00
February 1354.32 01-FEB-00:10 795.89 01-FEB-20:10 793.93 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 124.51 17-FEB-07:00
March 1354.32 01-MAR-00:10 795.89 01-MAR-20:10 793.93 01-MAR-20:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:03 107.95 08-MAR-07:00
April 1354.32 01-APR-00:10 795.89 03-APR-19:10 793.93 03-APR-19:10 0.00 0.00 0.00 0.00 13.45 30-APR-18:20 102.45 08-APR-06:00
May 1354.32 01-MAY-00:10 795.89 01-MAY-19:10 793.93 01-MAY-19:10 0.00 0.00 0.00 0.00 13.44 22-MAY-15:00 92.96 06-MAY-05:00
June 1354.32 01-JUN-00:10 795.89 01-JUN-19:10 793.93 01-JUN-19:10 0.00 0.00 0.00 0.00 26.60 13-JUN-17:00 72.13 07-JUN-05:00
July 1354.32 01-JUL-00:10 795.89 03-JUL-19:10 793.93 03-JUL-19:10 0.00 0.00 0.00 0.00 39.38 22-JUL-18:00 67.09 31-JUL-05:00
August 1354.32 01-AUG-00:10 795.89 01-AUG-19:10 793.93 01-AUG-19:10 0.00 0.00 0.00 0.00 26.66 14-AUG-17:06 61.98 20-AUG-05:00
September 1354.32 01-SEP-00:10 795.89 01-SEP-19:10 793.93 01-SEP-19:10 0.00 0.00 0.00 0.00 8.99 13-SEP-14:20 77.46 21-SEP-06:00
October 1354.32 01-OCT-23:10 795.89 02-OCT-19:10 793.93 02-OCT-19:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 92.34 15-OCT-04:00
November 1354.32 01-NOV-00:10 795.89 01-NOV-19:10 793.93 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 114.84 29-NOV-02:00
December 1354.32 01-DEC-00:10 795.89 01-DEC-20:10 793.93 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 118.48 29-DEC-21:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1354.32   795.89   793.93   0.00 0.00 0.00 0.00 0.00   61.98  
Maximum of Months 1354.32   795.89   793.93   0.00 0.00 0.00 0.00 39.38   134.36  



Table of Contents

Report: PeakSpaceGainsMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 286.42 02-JAN-00:10 1487.69 02-JAN-20:10 839.45 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 317.53 11-JAN-24:00
February 286.42 01-FEB-00:10 1487.69 01-FEB-20:10 839.45 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 294.24 17-FEB-07:00
March 286.42 01-MAR-00:10 1487.69 01-MAR-20:10 839.45 01-MAR-20:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:03 255.10 08-MAR-07:00
April 286.42 01-APR-00:10 1487.69 03-APR-19:10 839.45 03-APR-19:10 0.00 0.00 0.00 0.00 31.80 30-APR-18:50 242.12 08-APR-06:00
May 286.42 01-MAY-00:10 1487.69 01-MAY-19:10 839.45 01-MAY-19:10 0.00 0.00 0.00 0.00 31.77 22-MAY-15:00 219.68 06-MAY-05:00
June 286.42 01-JUN-00:10 1487.69 01-JUN-19:10 839.45 01-JUN-19:10 0.00 0.00 0.00 0.00 62.88 13-JUN-17:00 170.47 07-JUN-05:00
July 286.42 01-JUL-00:10 1487.69 03-JUL-19:10 839.45 03-JUL-19:10 0.00 0.00 0.00 0.00 93.07 22-JUL-18:00 158.55 31-JUL-05:00
August 286.42 01-AUG-00:10 1487.69 01-AUG-19:10 839.45 01-AUG-19:10 0.00 0.00 0.00 0.00 63.00 14-AUG-17:01 146.48 20-AUG-05:00
September 286.42 01-SEP-00:10 1487.69 01-SEP-19:10 839.45 01-SEP-19:10 0.00 0.00 0.00 0.00 21.25 13-SEP-14:50 183.06 21-SEP-06:00
October 286.42 01-OCT-23:10 1487.69 02-OCT-19:10 839.45 02-OCT-19:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 218.18 15-OCT-04:00
November 286.42 01-NOV-00:10 1487.69 01-NOV-19:10 839.45 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 271.39 29-NOV-02:00
December 286.42 01-DEC-00:10 1487.69 01-DEC-20:10 839.45 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 280.00 29-DEC-21:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 286.42   1487.69   839.45   0.00 0.00 0.00 0.00 0.00   146.48  
Maximum of Months 286.42   1487.69   839.45   0.00 0.00 0.00 0.00 93.07   317.53  



Table of Contents

Report: PeakSpaceGainsMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 220.32 02-JAN-00:10 273.10 02-JAN-20:10 242.16 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 183.20 11-JAN-23:57
February 220.32 01-FEB-00:10 273.10 01-FEB-20:10 242.16 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 169.77 17-FEB-07:00
March 220.32 01-MAR-00:10 273.10 01-MAR-20:10 242.16 01-MAR-20:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:03 147.18 08-MAR-07:00
April 220.32 01-APR-00:10 273.10 03-APR-19:10 242.16 03-APR-19:10 0.00 0.00 0.00 0.00 18.35 30-APR-19:00 139.70 08-APR-06:00
May 220.32 01-MAY-00:10 273.10 01-MAY-19:10 242.16 01-MAY-19:10 0.00 0.00 0.00 0.00 18.33 22-MAY-15:00 126.75 06-MAY-05:00
June 220.32 01-JUN-00:10 273.10 01-JUN-19:10 242.16 01-JUN-19:10 0.00 0.00 0.00 0.00 36.27 13-JUN-17:00 98.36 07-JUN-05:00
July 220.32 01-JUL-00:10 273.10 03-JUL-19:10 242.16 03-JUL-19:10 0.00 0.00 0.00 0.00 53.70 22-JUL-18:00 91.48 31-JUL-05:00
August 220.32 01-AUG-00:10 273.10 01-AUG-19:10 242.16 01-AUG-19:10 0.00 0.00 0.00 0.00 36.35 14-AUG-17:00 84.51 20-AUG-05:00
September 220.32 01-SEP-00:10 273.10 01-SEP-19:10 242.16 01-SEP-19:10 0.00 0.00 0.00 0.00 12.26 13-SEP-14:30 105.62 21-SEP-06:00
October 220.32 01-OCT-23:10 273.10 02-OCT-19:10 242.16 02-OCT-19:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 125.89 15-OCT-04:00
November 220.32 01-NOV-00:10 273.10 01-NOV-19:10 242.16 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 156.58 29-NOV-02:00
December 220.32 01-DEC-00:10 273.10 01-DEC-20:10 242.16 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 161.55 29-DEC-21:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 220.32   273.10   242.16   0.00 0.00 0.00 0.00 0.00   84.51  
Maximum of Months 220.32   273.10   242.16   0.00 0.00 0.00 0.00 53.70   183.20  



Table of Contents

Report: PeakSpaceGainsMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 907.20 02-JAN-00:10 337.37 02-JAN-20:10 4572.80 02-JAN-20:10 39726.58 02-JAN-20:10 0.00 0.00 0.00 0.00 01-JAN-00:05 460.82 10-JAN-22:00
February 907.20 01-FEB-00:10 337.37 01-FEB-20:10 4572.80 01-FEB-20:10 39726.58 01-FEB-20:10 0.00 0.00 0.00 0.00 01-FEB-00:03 433.68 17-FEB-21:00
March 907.20 01-MAR-00:10 337.37 01-MAR-20:10 4572.80 01-MAR-20:10 39726.58 01-MAR-20:10 0.00 0.00 0.00 0.00 01-MAR-00:03 369.96 14-MAR-21:00
April 907.20 01-APR-00:10 337.37 03-APR-19:10 4572.80 03-APR-19:10 39726.58 03-APR-19:10 0.00 0.00 0.00 44.60 30-APR-16:40 330.68 08-APR-06:00
May 907.20 01-MAY-00:10 337.37 01-MAY-19:10 4572.80 01-MAY-19:10 39726.58 01-MAY-19:10 0.00 0.00 0.00 43.56 22-MAY-15:00 299.68 06-MAY-05:00
June 907.20 01-JUN-00:10 337.37 01-JUN-19:10 4572.80 01-JUN-19:10 39726.58 01-JUN-19:10 0.00 0.00 0.00 85.74 13-JUN-17:00 263.07 07-JUN-21:00
July 907.20 01-JUL-00:10 337.37 03-JUL-19:10 4572.80 03-JUL-19:10 39726.58 03-JUL-19:10 0.00 0.00 0.00 126.95 22-JUL-18:00 229.43 03-JUL-21:00
August 907.20 01-AUG-00:10 337.37 01-AUG-19:10 4572.80 01-AUG-19:10 39726.58 01-AUG-19:10 0.00 0.00 0.00 86.02 14-AUG-17:25 200.09 24-AUG-06:00
September 907.20 01-SEP-00:10 337.37 01-SEP-19:10 4572.80 01-SEP-19:10 39726.58 01-SEP-19:10 0.00 0.00 0.00 29.11 13-SEP-14:30 250.80 21-SEP-06:10
October 907.20 01-OCT-23:10 337.37 02-OCT-19:10 4572.80 02-OCT-19:10 39726.58 02-OCT-19:10 0.00 0.00 0.00 0.00 01-OCT-00:10 297.64 15-OCT-04:00
November 907.20 01-NOV-00:10 337.37 01-NOV-19:10 4572.80 01-NOV-19:10 39726.58 01-NOV-19:10 0.00 0.00 0.00 0.00 01-NOV-00:10 401.73 28-NOV-21:00
December 907.20 01-DEC-00:10 337.37 01-DEC-20:10 4572.80 01-DEC-20:10 39726.58 01-DEC-20:10 0.00 0.00 0.00 0.00 01-DEC-00:03 430.12 29-DEC-21:00
                               
Annual Sum or Average                 0.00 0.00 0.00        
Minimum of Months 907.20   337.37   4572.80   39726.58   0.00 0.00 0.00 0.00   200.09  
Maximum of Months 907.20   337.37   4572.80   39726.58   0.00 0.00 0.00 126.95   460.82  



Table of Contents

Report: PeakSpaceGainsMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 15368.40 02-JAN-00:10 2177.23 02-JAN-20:10 965.27 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 769.54 11-JAN-23:57
February 15368.40 01-FEB-00:10 2177.23 01-FEB-20:10 965.27 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 713.09 17-FEB-07:00
March 15368.40 01-MAR-00:10 2177.23 01-MAR-20:10 965.27 01-MAR-20:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:03 618.34 08-MAR-07:00
April 15368.40 01-APR-00:10 2177.23 03-APR-19:10 965.27 03-APR-19:10 0.00 0.00 0.00 0.00 77.06 30-APR-18:30 587.04 08-APR-06:00
May 15368.40 01-MAY-00:10 2177.23 01-MAY-19:10 965.27 01-MAY-19:10 0.00 0.00 0.00 0.00 76.78 22-MAY-15:00 532.49 06-MAY-05:00
June 15368.40 01-JUN-00:10 2177.23 01-JUN-19:10 965.27 01-JUN-19:10 0.00 0.00 0.00 0.00 152.21 13-JUN-17:00 413.11 07-JUN-05:00
July 15368.40 01-JUL-00:10 2177.23 03-JUL-19:10 965.27 03-JUL-19:10 0.00 0.00 0.00 0.00 225.53 22-JUL-18:00 384.33 31-JUL-05:00
August 15368.40 01-AUG-00:10 2177.23 01-AUG-19:10 965.27 01-AUG-19:10 0.00 0.00 0.00 0.00 152.70 14-AUG-17:20 355.20 20-AUG-05:00
September 15368.40 01-SEP-00:10 2177.23 01-SEP-19:10 965.27 01-SEP-19:10 0.00 0.00 0.00 0.00 51.50 11-SEP-17:00 443.72 21-SEP-06:00
October 15368.40 01-OCT-23:10 2177.23 02-OCT-19:10 965.27 02-OCT-19:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 528.83 15-OCT-04:00
November 15368.40 01-NOV-00:10 2177.23 01-NOV-19:10 965.27 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 657.90 29-NOV-02:00
December 15368.40 01-DEC-00:10 2177.23 01-DEC-20:10 965.27 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 678.52 29-DEC-21:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 15368.40   2177.23   965.27   0.00 0.00 0.00 0.00 0.00   355.20  
Maximum of Months 15368.40   2177.23   965.27   0.00 0.00 0.00 0.00 225.53   769.54  



Table of Contents

Report: PeakSpaceGainsMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 45622.98 02-JAN-00:10 11849.32 02-JAN-20:10 10029.21 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 2198.56 11-JAN-23:53
February 45622.98 01-FEB-00:10 11849.32 01-FEB-20:10 10029.21 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 2037.20 17-FEB-07:00
March 45622.98 01-MAR-00:10 11849.32 01-MAR-20:10 10029.21 01-MAR-20:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:03 1766.04 08-MAR-07:00
April 45622.98 01-APR-00:10 11849.32 03-APR-19:10 10029.21 03-APR-19:10 0.00 0.00 0.00 0.00 220.32 30-APR-19:00 1676.43 08-APR-05:50
May 45622.98 01-MAY-00:10 11849.32 01-MAY-19:10 10029.21 01-MAY-19:10 0.00 0.00 0.00 0.00 219.76 22-MAY-15:00 1521.18 06-MAY-05:00
June 45622.98 01-JUN-00:10 11849.32 01-JUN-19:10 10029.21 01-JUN-19:10 0.00 0.00 0.00 0.00 435.02 13-JUN-17:00 1180.42 07-JUN-05:00
July 45622.98 01-JUL-00:10 11849.32 03-JUL-19:10 10029.21 03-JUL-19:10 0.00 0.00 0.00 0.00 644.26 22-JUL-18:00 1098.06 31-JUL-05:00
August 45622.98 01-AUG-00:10 11849.32 01-AUG-19:10 10029.21 01-AUG-19:10 0.00 0.00 0.00 0.00 436.18 14-AUG-17:01 1014.29 24-AUG-06:00
September 45622.98 01-SEP-00:10 11849.32 01-SEP-19:10 10029.21 01-SEP-19:10 0.00 0.00 0.00 0.00 147.12 13-SEP-15:00 1277.50 20-SEP-24:00
October 45622.98 01-OCT-23:10 11849.32 02-OCT-19:10 10029.21 02-OCT-19:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 1510.81 15-OCT-04:00
November 45622.98 01-NOV-00:10 11849.32 01-NOV-19:10 10029.21 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 1879.26 29-NOV-02:00
December 45622.98 01-DEC-00:10 11849.32 01-DEC-20:10 10029.21 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 1941.16 29-DEC-23:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 45622.98   11849.32   10029.21   0.00 0.00 0.00 0.00 0.00   1014.29  
Maximum of Months 45622.98   11849.32   10029.21   0.00 0.00 0.00 0.00 644.26   2198.56  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 392.73 01-JAN-19:10 237.06 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 203.17 11-JAN-24:00
February 180.00 01-FEB-00:10 392.73 01-FEB-20:10 237.06 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 188.35 17-FEB-07:00
March 180.00 01-MAR-00:10 392.73 01-MAR-20:10 237.06 01-MAR-07:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:03 163.43 08-MAR-07:00
April 180.00 01-APR-00:10 392.73 01-APR-18:10 237.06 01-APR-07:10 0.00 0.00 0.00 0.00 19.19 30-APR-18:50 155.17 08-APR-06:00
May 180.00 01-MAY-00:10 392.73 01-MAY-19:10 237.06 01-MAY-06:10 0.00 0.00 0.00 0.00 18.05 22-MAY-15:10 140.90 06-MAY-05:00
June 180.00 01-JUN-00:10 392.73 01-JUN-19:10 237.06 01-JUN-06:10 0.00 0.00 0.00 0.00 38.98 13-JUN-17:00 109.57 07-JUN-05:00
July 180.00 01-JUL-00:10 392.73 01-JUL-18:10 237.06 01-JUL-07:10 0.00 0.00 0.00 0.00 57.12 22-JUL-18:10 101.98 31-JUL-05:00
August 180.00 01-AUG-00:10 392.73 01-AUG-19:10 237.06 01-AUG-06:10 0.00 0.00 0.00 0.00 39.06 14-AUG-17:00 94.29 20-AUG-05:00
September 180.00 01-SEP-00:10 392.73 01-SEP-19:10 237.06 01-SEP-06:10 0.00 0.00 0.00 0.00 12.47 13-SEP-15:10 117.58 21-SEP-06:00
October 180.00 01-OCT-00:10 392.73 01-OCT-18:10 237.06 01-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 139.94 15-OCT-04:00
November 180.00 01-NOV-00:10 392.73 01-NOV-19:10 237.06 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 173.82 29-NOV-02:00
December 180.00 01-DEC-00:10 392.73 01-DEC-20:10 237.06 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 179.28 29-DEC-21:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   392.73   237.06   0.00 0.00 0.00 0.00 0.00   94.29  
Maximum of Months 180.00   392.73   237.06   0.00 0.00 0.00 0.00 57.12   203.17  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 392.68 01-JAN-19:10 237.03 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 203.16 11-JAN-24:00
February 180.00 01-FEB-00:10 392.68 01-FEB-20:10 237.03 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 188.34 17-FEB-07:00
March 180.00 01-MAR-00:10 392.68 01-MAR-20:10 237.03 01-MAR-07:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:03 163.42 08-MAR-07:00
April 180.00 01-APR-00:10 392.68 01-APR-18:10 237.03 01-APR-07:10 0.00 0.00 0.00 0.00 19.19 30-APR-19:00 155.16 08-APR-06:00
May 180.00 01-MAY-00:10 392.68 01-MAY-19:10 237.03 01-MAY-06:10 0.00 0.00 0.00 0.00 18.06 22-MAY-15:10 140.89 06-MAY-05:00
June 180.00 01-JUN-00:10 392.68 01-JUN-19:10 237.03 01-JUN-06:10 0.00 0.00 0.00 0.00 38.98 13-JUN-17:00 109.56 07-JUN-05:00
July 180.00 01-JUL-00:10 392.68 01-JUL-18:10 237.03 01-JUL-07:10 0.00 0.00 0.00 0.00 55.91 22-JUL-18:10 101.97 31-JUL-05:00
August 180.00 01-AUG-00:10 392.68 01-AUG-19:10 237.03 01-AUG-06:10 0.00 0.00 0.00 0.00 39.06 14-AUG-17:00 94.28 20-AUG-05:00
September 180.00 01-SEP-00:10 392.68 01-SEP-19:10 237.03 01-SEP-06:10 0.00 0.00 0.00 0.00 12.47 11-SEP-17:00 117.57 21-SEP-06:00
October 180.00 01-OCT-00:10 392.68 01-OCT-18:10 237.03 01-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 139.93 15-OCT-04:00
November 180.00 01-NOV-00:10 392.68 01-NOV-19:10 237.03 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 173.81 29-NOV-02:00
December 180.00 01-DEC-00:10 392.68 01-DEC-20:10 237.03 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 179.27 29-DEC-21:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   392.68   237.03   0.00 0.00 0.00 0.00 0.00   94.28  
Maximum of Months 180.00   392.68   237.03   0.00 0.00 0.00 0.00 55.91   203.16  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 01-JAN-00:10 246.81 01-JAN-19:10 232.19 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 58.72 11-JAN-23:53
February 0.00 01-FEB-00:10 246.81 01-FEB-20:10 232.19 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 54.79 17-FEB-21:00
March 0.00 01-MAR-00:10 246.81 01-MAR-20:10 232.19 01-MAR-07:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:03 45.90 14-MAR-21:00
April 0.00 01-APR-00:10 246.81 01-APR-18:10 232.19 01-APR-07:10 0.00 0.00 0.00 0.00 1.17 30-APR-19:00 45.33 08-APR-06:00
May 0.00 01-MAY-00:10 246.81 01-MAY-19:10 232.19 01-MAY-06:10 0.00 0.00 0.00 0.00 1.17 22-MAY-15:00 41.37 07-MAY-05:00
June 0.00 01-JUN-00:10 246.81 01-JUN-19:10 232.19 01-JUN-06:10 0.00 0.00 0.00 0.00 6.74 13-JUN-17:00 33.36 01-JUN-04:30
July 0.00 01-JUL-00:10 246.81 01-JUL-18:10 232.19 01-JUL-07:10 0.00 0.00 0.00 0.00 12.16 22-JUL-18:00 31.70 31-JUL-05:00
August 0.00 01-AUG-00:10 246.81 01-AUG-19:10 232.19 01-AUG-06:10 0.00 0.00 0.00 0.00 6.75 14-AUG-17:00 30.67 24-AUG-06:00
September 0.00 01-SEP-00:10 246.81 01-SEP-19:10 232.19 01-SEP-06:10 0.00 0.00 0.00 0.00 0.00 01-SEP-00:10 37.15 20-SEP-24:00
October 0.00 01-OCT-00:10 246.81 01-OCT-18:10 232.19 01-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 42.05 07-OCT-04:00
November 0.00 01-NOV-00:10 246.81 01-NOV-19:10 232.19 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 49.53 28-NOV-21:00
December 0.00 01-DEC-00:10 246.81 01-DEC-20:10 232.19 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 50.03 26-DEC-20:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 0.00   246.81   232.19   0.00 0.00 0.00 0.00 0.00   30.67  
Maximum of Months 0.00   246.81   232.19   0.00 0.00 0.00 0.00 12.16   58.72  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 246.88 01-JAN-19:10 232.26 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 56.70 11-JAN-23:57
February 180.00 01-FEB-00:10 246.88 01-FEB-20:10 232.26 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 52.57 17-FEB-07:00
March 180.00 01-MAR-00:10 246.88 01-MAR-20:10 232.26 01-MAR-07:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:03 45.61 08-MAR-07:00
April 180.00 01-APR-00:10 246.88 01-APR-18:10 232.26 01-APR-07:10 0.00 0.00 0.00 0.00 5.36 30-APR-19:00 43.31 08-APR-06:00
May 180.00 01-MAY-00:10 246.88 01-MAY-19:10 232.26 01-MAY-06:10 0.00 0.00 0.00 0.00 5.04 22-MAY-15:10 39.32 06-MAY-05:00
June 180.00 01-JUN-00:10 246.88 01-JUN-19:10 232.26 01-JUN-06:10 0.00 0.00 0.00 0.00 10.88 13-JUN-17:00 30.58 07-JUN-05:00
July 180.00 01-JUL-00:10 246.88 01-JUL-18:10 232.26 01-JUL-07:10 0.00 0.00 0.00 0.00 15.95 22-JUL-18:10 28.46 31-JUL-05:00
August 180.00 01-AUG-00:10 246.88 01-AUG-19:10 232.26 01-AUG-06:10 0.00 0.00 0.00 0.00 10.90 14-AUG-17:00 26.31 20-AUG-05:00
September 180.00 01-SEP-00:10 246.88 01-SEP-19:10 232.26 01-SEP-06:10 0.00 0.00 0.00 0.00 3.48 11-SEP-17:00 32.82 21-SEP-06:00
October 180.00 01-OCT-00:10 246.88 01-OCT-18:10 232.26 01-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 39.06 15-OCT-04:00
November 180.00 01-NOV-00:10 246.88 01-NOV-19:10 232.26 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 48.51 29-NOV-02:00
December 180.00 01-DEC-00:10 246.88 01-DEC-20:10 232.26 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 50.04 29-DEC-21:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   246.88   232.26   0.00 0.00 0.00 0.00 0.00   26.31  
Maximum of Months 180.00   246.88   232.26   0.00 0.00 0.00 0.00 15.95   56.70  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 392.73 01-JAN-19:10 237.06 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 203.17 11-JAN-24:00
February 180.00 01-FEB-00:10 392.73 01-FEB-20:10 237.06 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 188.36 17-FEB-07:00
March 180.00 01-MAR-00:10 392.73 01-MAR-20:10 237.06 01-MAR-07:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:03 163.44 08-MAR-07:00
April 180.00 01-APR-00:10 392.73 01-APR-18:10 237.06 01-APR-07:10 0.00 0.00 0.00 0.00 19.20 30-APR-19:00 155.17 08-APR-06:00
May 180.00 01-MAY-00:10 392.73 01-MAY-19:10 237.06 01-MAY-06:10 0.00 0.00 0.00 0.00 18.06 22-MAY-15:10 140.90 06-MAY-05:00
June 180.00 01-JUN-00:10 392.73 01-JUN-19:10 237.06 01-JUN-06:10 0.00 0.00 0.00 0.00 38.98 13-JUN-17:00 109.57 07-JUN-05:00
July 180.00 01-JUL-00:10 392.73 01-JUL-18:10 237.06 01-JUL-07:10 0.00 0.00 0.00 0.00 57.14 22-JUL-18:10 101.98 31-JUL-05:00
August 180.00 01-AUG-00:10 392.73 01-AUG-19:10 237.06 01-AUG-06:10 0.00 0.00 0.00 0.00 39.06 14-AUG-17:00 94.29 20-AUG-05:00
September 180.00 01-SEP-00:10 392.73 01-SEP-19:10 237.06 01-SEP-06:10 0.00 0.00 0.00 0.00 12.47 11-SEP-17:00 117.58 21-SEP-06:00
October 180.00 01-OCT-00:10 392.73 01-OCT-18:10 237.06 01-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 139.94 15-OCT-04:00
November 180.00 01-NOV-00:10 392.73 01-NOV-19:10 237.06 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 173.82 29-NOV-02:00
December 180.00 01-DEC-00:10 392.73 01-DEC-20:10 237.06 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 179.28 29-DEC-21:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   392.73   237.06   0.00 0.00 0.00 0.00 0.00   94.29  
Maximum of Months 180.00   392.73   237.06   0.00 0.00 0.00 0.00 57.14   203.17  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 392.68 01-JAN-19:10 237.03 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 203.16 11-JAN-24:00
February 180.00 01-FEB-00:10 392.68 01-FEB-20:10 237.03 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 188.34 17-FEB-07:00
March 180.00 01-MAR-00:10 392.68 01-MAR-20:10 237.03 01-MAR-07:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:03 163.42 08-MAR-07:00
April 180.00 01-APR-00:10 392.68 01-APR-18:10 237.03 01-APR-07:10 0.00 0.00 0.00 0.00 19.20 30-APR-19:00 155.16 08-APR-06:00
May 180.00 01-MAY-00:10 392.68 01-MAY-19:10 237.03 01-MAY-06:10 0.00 0.00 0.00 0.00 18.06 22-MAY-15:10 140.89 06-MAY-05:00
June 180.00 01-JUN-00:10 392.68 01-JUN-19:10 237.03 01-JUN-06:10 0.00 0.00 0.00 0.00 38.97 13-JUN-17:00 109.56 07-JUN-05:00
July 180.00 01-JUL-00:10 392.68 01-JUL-18:10 237.03 01-JUL-07:10 0.00 0.00 0.00 0.00 57.13 22-JUL-18:10 101.97 31-JUL-05:00
August 180.00 01-AUG-00:10 392.68 01-AUG-19:10 237.03 01-AUG-06:10 0.00 0.00 0.00 0.00 39.06 14-AUG-17:00 94.28 20-AUG-05:00
September 180.00 01-SEP-00:10 392.68 01-SEP-19:10 237.03 01-SEP-06:10 0.00 0.00 0.00 0.00 12.47 11-SEP-17:00 117.57 21-SEP-06:00
October 180.00 01-OCT-00:10 392.68 01-OCT-18:10 237.03 01-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 139.93 15-OCT-04:00
November 180.00 01-NOV-00:10 392.68 01-NOV-19:10 237.03 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 173.81 29-NOV-02:00
December 180.00 01-DEC-00:10 392.68 01-DEC-20:10 237.03 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 179.27 29-DEC-21:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   392.68   237.03   0.00 0.00 0.00 0.00 0.00   94.28  
Maximum of Months 180.00   392.68   237.03   0.00 0.00 0.00 0.00 57.13   203.16  



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2263.36 02-JAN-00:10 1282.60 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 244.68 11-JAN-24:00
February 2263.36 01-FEB-00:10 1282.60 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 226.76 17-FEB-07:00
March 2263.36 01-MAR-00:10 1282.60 01-MAR-20:10 0.00 0.00 0.00 0.00 0.00 0.00 01-MAR-00:03 196.65 08-MAR-07:00
April 2263.36 01-APR-00:10 1282.60 03-APR-19:10 0.00 0.00 0.00 0.00 0.00 22.84 30-APR-17:20 186.65 08-APR-06:00
May 2263.36 01-MAY-00:10 1282.60 01-MAY-19:10 0.00 0.00 0.00 0.00 0.00 21.98 22-MAY-15:00 169.41 06-MAY-05:00
June 2263.36 01-JUN-00:10 1282.60 01-JUN-19:10 0.00 0.00 0.00 0.00 0.00 46.08 13-JUN-17:00 131.52 07-JUN-05:00
July 2263.36 01-JUL-00:10 1282.60 03-JUL-19:10 0.00 0.00 0.00 0.00 0.00 67.63 22-JUL-18:00 122.37 31-JUL-05:00
August 2263.36 01-AUG-00:10 1282.60 01-AUG-19:10 0.00 0.00 0.00 0.00 0.00 46.42 14-AUG-17:35 113.07 20-AUG-05:00
September 2263.36 01-SEP-00:10 1282.60 01-SEP-19:10 0.00 0.00 0.00 0.00 0.00 13.97 11-SEP-17:00 141.21 21-SEP-06:00
October 2263.36 01-OCT-23:10 1282.60 02-OCT-19:10 0.00 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 168.25 15-OCT-04:00
November 2263.36 01-NOV-00:10 1282.60 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 209.20 29-NOV-02:00
December 2263.36 01-DEC-00:10 1282.60 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 215.80 29-DEC-21:00
                           
Annual Sum or Average         0.00 0.00 0.00 0.00 0.00        
Minimum of Months 2263.36   1282.60   0.00 0.00 0.00 0.00 0.00 0.00   113.07  
Maximum of Months 2263.36   1282.60   0.00 0.00 0.00 0.00 0.00 67.63   244.68  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 392.73 01-JAN-19:10 237.06 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 203.66 11-JAN-24:00
February 180.00 01-FEB-00:10 392.73 01-FEB-20:10 237.06 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 188.84 17-FEB-07:00
March 180.00 01-MAR-00:10 392.73 01-MAR-20:10 237.06 01-MAR-07:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:03 163.91 08-MAR-07:00
April 180.00 01-APR-00:10 392.73 01-APR-18:10 237.06 01-APR-07:10 0.00 0.00 0.00 0.00 18.79 30-APR-19:00 155.64 08-APR-06:00
May 180.00 01-MAY-00:10 392.73 01-MAY-19:10 237.06 01-MAY-06:10 0.00 0.00 0.00 0.00 17.60 22-MAY-15:10 141.37 06-MAY-05:00
June 180.00 01-JUN-00:10 392.73 01-JUN-19:10 237.06 01-JUN-06:10 0.00 0.00 0.00 0.00 38.58 13-JUN-17:00 110.02 07-JUN-05:00
July 180.00 01-JUL-00:10 392.73 01-JUL-18:10 237.06 01-JUL-07:10 0.00 0.00 0.00 0.00 55.70 22-JUL-18:10 102.43 31-JUL-05:00
August 180.00 01-AUG-00:10 392.73 01-AUG-19:10 237.06 01-AUG-06:10 0.00 0.00 0.00 0.00 38.67 14-AUG-17:00 94.73 20-AUG-05:00
September 180.00 01-SEP-00:10 392.73 01-SEP-19:10 237.06 01-SEP-06:10 0.00 0.00 0.00 0.00 12.07 11-SEP-17:00 118.04 21-SEP-06:00
October 180.00 01-OCT-00:10 392.73 01-OCT-18:10 237.06 01-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 140.41 15-OCT-04:00
November 180.00 01-NOV-00:10 392.73 01-NOV-19:10 237.06 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 174.31 29-NOV-02:00
December 180.00 01-DEC-00:10 392.73 01-DEC-20:10 237.06 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 179.76 29-DEC-21:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   392.73   237.06   0.00 0.00 0.00 0.00 0.00   94.73  
Maximum of Months 180.00   392.73   237.06   0.00 0.00 0.00 0.00 55.70   203.66  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 392.68 01-JAN-19:10 237.03 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 203.65 11-JAN-24:00
February 180.00 01-FEB-00:10 392.68 01-FEB-20:10 237.03 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 188.83 17-FEB-07:00
March 180.00 01-MAR-00:10 392.68 01-MAR-20:10 237.03 01-MAR-07:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:03 163.89 08-MAR-07:00
April 180.00 01-APR-00:10 392.68 01-APR-18:10 237.03 01-APR-07:10 0.00 0.00 0.00 0.00 18.76 30-APR-19:00 155.63 08-APR-06:00
May 180.00 01-MAY-00:10 392.68 01-MAY-19:10 237.03 01-MAY-06:10 0.00 0.00 0.00 0.00 17.65 22-MAY-15:10 141.36 06-MAY-05:00
June 180.00 01-JUN-00:10 392.68 01-JUN-19:10 237.03 01-JUN-06:10 0.00 0.00 0.00 0.00 38.58 13-JUN-17:00 110.01 07-JUN-05:00
July 180.00 01-JUL-00:10 392.68 01-JUL-18:10 237.03 01-JUL-07:10 0.00 0.00 0.00 0.00 54.44 22-JUL-18:10 102.42 31-JUL-05:00
August 180.00 01-AUG-00:10 392.68 01-AUG-19:10 237.03 01-AUG-06:10 0.00 0.00 0.00 0.00 38.67 14-AUG-17:00 94.73 20-AUG-05:00
September 180.00 01-SEP-00:10 392.68 01-SEP-19:10 237.03 01-SEP-06:10 0.00 0.00 0.00 0.00 12.07 13-SEP-15:10 118.03 21-SEP-06:00
October 180.00 01-OCT-00:10 392.68 01-OCT-18:10 237.03 01-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 140.40 15-OCT-04:00
November 180.00 01-NOV-00:10 392.68 01-NOV-19:10 237.03 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 174.29 29-NOV-02:00
December 180.00 01-DEC-00:10 392.68 01-DEC-20:10 237.03 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 179.75 29-DEC-21:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   392.68   237.03   0.00 0.00 0.00 0.00 0.00   94.73  
Maximum of Months 180.00   392.68   237.03   0.00 0.00 0.00 0.00 54.44   203.65  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 246.88 01-JAN-19:10 232.26 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 104.20 11-JAN-24:00
February 180.00 01-FEB-00:10 246.88 01-FEB-20:10 232.26 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 96.62 17-FEB-07:00
March 180.00 01-MAR-00:10 246.88 01-MAR-20:10 232.26 01-MAR-07:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:03 83.86 08-MAR-07:00
April 180.00 01-APR-00:10 246.88 01-APR-18:10 232.26 01-APR-07:10 0.00 0.00 0.00 0.00 9.62 30-APR-19:00 79.63 08-APR-06:00
May 180.00 01-MAY-00:10 246.88 01-MAY-19:10 232.26 01-MAY-06:10 0.00 0.00 0.00 0.00 9.04 22-MAY-15:10 72.33 06-MAY-05:00
June 180.00 01-JUN-00:10 246.88 01-JUN-19:10 232.26 01-JUN-06:10 0.00 0.00 0.00 0.00 19.74 13-JUN-17:00 56.29 07-JUN-05:00
July 180.00 01-JUL-00:10 246.88 01-JUL-18:10 232.26 01-JUL-07:10 0.00 0.00 0.00 0.00 29.04 22-JUL-18:10 52.41 31-JUL-05:00
August 180.00 01-AUG-00:10 246.88 01-AUG-19:10 232.26 01-AUG-06:10 0.00 0.00 0.00 0.00 19.79 14-AUG-17:00 48.47 20-AUG-05:00
September 180.00 01-SEP-00:10 246.88 01-SEP-19:10 232.26 01-SEP-06:10 0.00 0.00 0.00 0.00 6.17 11-SEP-17:00 60.39 21-SEP-06:00
October 180.00 01-OCT-00:10 246.88 01-OCT-18:10 232.26 01-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 71.84 15-OCT-04:00
November 180.00 01-NOV-00:10 246.88 01-NOV-19:10 232.26 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 89.18 29-NOV-02:00
December 180.00 01-DEC-00:10 246.88 01-DEC-20:10 232.26 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 91.97 29-DEC-21:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   246.88   232.26   0.00 0.00 0.00 0.00 0.00   48.47  
Maximum of Months 180.00   246.88   232.26   0.00 0.00 0.00 0.00 29.04   104.20  



Table of Contents

Report: PeakSpaceGainsMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 26988.77 02-JAN-00:10 3823.39 02-JAN-20:10 6747.90 01-JAN-07:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 514.47 11-JAN-23:53
February 26988.77 01-FEB-00:10 3823.39 01-FEB-20:10 6747.90 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 464.96 17-FEB-07:00
March 26988.77 01-MAR-00:10 3823.39 01-MAR-20:10 6747.90 01-MAR-07:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:03 407.38 08-MAR-07:00
April 26988.77 01-APR-00:10 3823.39 03-APR-19:10 6747.90 01-APR-06:10 0.00 0.00 0.00 0.00 47.71 30-APR-17:40 390.08 08-APR-05:00
May 26988.77 01-MAY-00:10 3823.39 01-MAY-19:10 6747.90 01-MAY-06:10 0.00 0.00 0.00 0.00 41.60 22-MAY-15:00 357.20 06-MAY-05:00
June 26988.77 01-JUN-00:10 3823.39 01-JUN-19:10 6747.90 01-JUN-06:10 0.00 0.00 0.00 0.00 88.72 13-JUN-17:00 284.85 08-JUN-05:00
July 26988.77 01-JUL-00:10 3823.39 03-JUL-19:10 6747.90 01-JUL-06:10 0.00 0.00 0.00 0.00 131.16 22-JUL-18:00 266.54 05-JUL-05:00
August 26988.77 01-AUG-00:10 3823.39 01-AUG-19:10 6747.90 01-AUG-06:10 0.00 0.00 0.00 0.00 92.21 14-AUG-18:00 247.07 23-AUG-04:00
September 26988.77 01-SEP-00:10 3823.39 01-SEP-19:10 6747.90 01-SEP-06:10 0.00 0.00 0.00 0.00 30.22 13-SEP-14:00 303.56 20-SEP-24:00
October 26988.77 01-OCT-23:10 3823.39 02-OCT-19:10 6747.90 01-OCT-06:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 353.08 07-OCT-04:00
November 26988.77 01-NOV-00:10 3823.39 01-NOV-19:10 6747.90 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 433.83 29-NOV-02:00
December 26988.77 01-DEC-00:10 3823.39 01-DEC-20:10 6747.90 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 458.72 29-DEC-23:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 26988.77   3823.39   6747.90   0.00 0.00 0.00 0.00 0.00   247.07  
Maximum of Months 26988.77   3823.39   6747.90   0.00 0.00 0.00 0.00 131.16   514.47  



Table of Contents

Report: PeakSpaceGainsMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 26988.77 02-JAN-00:10 3823.39 02-JAN-20:10 6747.90 01-JAN-07:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 516.08 11-JAN-23:53
February 26988.77 01-FEB-00:10 3823.39 01-FEB-20:10 6747.90 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 466.21 17-FEB-07:00
March 26988.77 01-MAR-00:10 3823.39 01-MAR-20:10 6747.90 01-MAR-07:10 0.00 0.00 0.00 0.00 0.00 01-MAR-00:03 408.65 08-MAR-07:00
April 26988.77 01-APR-00:10 3823.39 03-APR-19:10 6747.90 01-APR-06:10 0.00 0.00 0.00 0.00 47.44 30-APR-16:00 390.81 08-APR-05:00
May 26988.77 01-MAY-00:10 3823.39 01-MAY-19:10 6747.90 01-MAY-06:10 0.00 0.00 0.00 0.00 39.69 22-MAY-15:00 357.94 06-MAY-05:00
June 26988.77 01-JUN-00:10 3823.39 01-JUN-19:10 6747.90 01-JUN-06:10 0.00 0.00 0.00 0.00 86.71 13-JUN-17:00 285.68 08-JUN-05:00
July 26988.77 01-JUL-00:10 3823.39 03-JUL-19:10 6747.90 01-JUL-06:10 0.00 0.00 0.00 0.00 129.25 22-JUL-18:00 267.37 05-JUL-05:00
August 26988.77 01-AUG-00:10 3823.39 01-AUG-19:10 6747.90 01-AUG-06:10 0.00 0.00 0.00 0.00 90.14 14-AUG-18:00 247.89 24-AUG-06:00
September 26988.77 01-SEP-00:10 3823.39 01-SEP-19:10 6747.90 01-SEP-06:10 0.00 0.00 0.00 0.00 28.45 13-SEP-14:00 305.11 20-SEP-24:00
October 26988.77 01-OCT-23:10 3823.39 02-OCT-19:10 6747.90 01-OCT-06:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 353.74 07-OCT-04:00
November 26988.77 01-NOV-00:10 3823.39 01-NOV-19:10 6747.90 01-NOV-06:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 434.88 29-NOV-02:00
December 26988.77 01-DEC-00:10 3823.39 01-DEC-20:10 6747.90 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 460.56 29-DEC-23:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 26988.77   3823.39   6747.90   0.00 0.00 0.00 0.00 0.00   247.89  
Maximum of Months 26988.77   3823.39   6747.90   0.00 0.00 0.00 0.00 129.25   516.08  



Table of Contents

Report: PeakSpaceGainsMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2401.70 02-JAN-00:10 1020.78 02-JAN-20:10 15112.11 01-JAN-07:10 22492.83 01-JAN-16:10 0.00 0.00 0.00 0.00 01-JAN-00:05 473.57 10-JAN-08:00
February 2401.70 01-FEB-00:10 1020.78 01-FEB-20:10 15112.11 01-FEB-07:10 22492.83 01-FEB-16:10 0.00 0.00 0.00 0.00 01-FEB-00:03 433.63 17-FEB-07:20
March 2401.70 01-MAR-00:10 1020.78 01-MAR-20:10 15112.11 01-MAR-07:10 22492.83 01-MAR-16:10 0.00 0.00 0.00 0.00 01-MAR-00:03 369.82 02-MAR-21:00
April 2401.70 01-APR-00:10 1020.78 03-APR-19:10 15112.11 01-APR-06:10 22492.83 01-APR-15:09 0.00 0.00 0.00 0.00 01-APR-00:10 350.22 08-APR-06:00
May 2401.70 01-MAY-00:10 1020.78 01-MAY-19:10 15112.11 01-MAY-06:10 22492.83 01-MAY-15:09 0.00 0.00 0.00 0.00 01-MAY-00:10 311.93 06-MAY-05:20
June 2401.70 01-JUN-00:10 1020.78 01-JUN-19:10 15112.11 01-JUN-06:10 22492.83 01-JUN-15:09 0.00 0.00 0.00 42.39 13-JUN-17:00 264.49 07-JUN-21:00
July 2401.70 01-JUL-00:10 1020.78 03-JUL-19:10 15112.11 01-JUL-06:10 22492.83 01-JUL-15:09 0.00 0.00 0.00 84.80 22-JUL-18:00 234.93 04-JUL-21:00
August 2401.70 01-AUG-00:10 1020.78 01-AUG-19:10 15112.11 01-AUG-06:10 22492.83 01-AUG-15:09 0.00 0.00 0.00 42.46 14-AUG-18:00 225.60 24-AUG-06:00
September 2401.70 01-SEP-00:10 1020.78 01-SEP-19:10 15112.11 01-SEP-06:10 22492.83 01-SEP-15:09 0.00 0.00 0.00 0.00 01-SEP-00:10 271.50 21-SEP-06:00
October 2401.70 01-OCT-23:10 1020.78 02-OCT-19:10 15112.11 01-OCT-06:10 22492.83 01-OCT-15:09 0.00 0.00 0.00 0.00 01-OCT-00:10 329.10 06-OCT-07:00
November 2401.70 01-NOV-00:10 1020.78 01-NOV-19:10 15112.11 01-NOV-06:10 22492.83 01-NOV-15:09 0.00 0.00 0.00 0.00 01-NOV-00:10 397.63 28-NOV-21:00
December 2401.70 01-DEC-00:10 1020.78 01-DEC-20:10 15112.11 01-DEC-07:10 22492.83 01-DEC-16:10 0.00 0.00 0.00 0.00 01-DEC-00:03 424.80 29-DEC-21:00
                               
Annual Sum or Average                 0.00 0.00 0.00        
Minimum of Months 2401.70   1020.78   15112.11   22492.83   0.00 0.00 0.00 0.00   225.60  
Maximum of Months 2401.70   1020.78   15112.11   22492.83   0.00 0.00 0.00 84.80   473.57  



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2395.44 02-JAN-00:10 1357.44 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 433.97 11-JAN-23:57
February 2395.44 01-FEB-00:10 1357.44 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 402.30 17-FEB-07:00
March 2395.44 01-MAR-00:10 1357.44 01-MAR-20:10 0.00 0.00 0.00 0.00 0.00 0.00 01-MAR-00:03 348.93 08-MAR-07:00
April 2395.44 01-APR-00:10 1357.44 03-APR-19:10 0.00 0.00 0.00 0.00 0.00 41.84 30-APR-18:50 331.26 08-APR-06:00
May 2395.44 01-MAY-00:10 1357.44 01-MAY-19:10 0.00 0.00 0.00 0.00 0.00 33.88 22-MAY-15:00 300.77 06-MAY-05:00
June 2395.44 01-JUN-00:10 1357.44 01-JUN-19:10 0.00 0.00 0.00 0.00 0.00 80.56 13-JUN-17:00 233.67 07-JUN-05:00
July 2395.44 01-JUL-00:10 1357.44 03-JUL-19:10 0.00 0.00 0.00 0.00 0.00 121.30 22-JUL-18:00 217.44 31-JUL-05:00
August 2395.44 01-AUG-00:10 1357.44 01-AUG-19:10 0.00 0.00 0.00 0.00 0.00 84.30 14-AUG-18:00 200.99 20-AUG-05:00
September 2395.44 01-SEP-00:10 1357.44 01-SEP-19:10 0.00 0.00 0.00 0.00 0.00 27.08 11-SEP-17:00 250.84 21-SEP-06:00
October 2395.44 01-OCT-23:10 1357.44 02-OCT-19:10 0.00 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 298.66 15-OCT-04:00
November 2395.44 01-NOV-00:10 1357.44 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 371.14 29-NOV-02:00
December 2395.44 01-DEC-00:10 1357.44 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 382.86 29-DEC-21:00
                           
Annual Sum or Average         0.00 0.00 0.00 0.00 0.00        
Minimum of Months 2395.44   1357.44   0.00 0.00 0.00 0.00 0.00 0.00   200.99  
Maximum of Months 2395.44   1357.44   0.00 0.00 0.00 0.00 0.00 121.30   433.97  



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 18958.62 20-JAN-21:00 8945.92 13517.00 10113.80 0.00 0.00 0.00 0.00 0.00 0.00
February 18799.56 22-FEB-21:00 8945.92 13517.00 10113.80 0.00 0.00 0.00 0.00 0.00 0.00
March 18741.74 31-MAR-20:00 8945.92 13517.00 10113.80 0.00 0.00 0.00 0.00 0.00 0.00
April 19630.53 27-APR-19:10 17891.83 27034.00 20227.60 0.00 0.00 0.00 0.00 0.00 0.00
May 20231.62 30-MAY-18:06 62621.41 84105.23 67070.47 0.00 0.00 0.00 0.00 0.00 0.00
June 20588.93 21-JUN-19:10 17891.83 27034.00 20227.60 0.00 0.00 0.00 0.00 0.00 0.00
July 20690.53 10-JUL-19:10 17891.83 27034.00 20227.60 0.00 0.00 0.00 0.00 0.00 0.00
August 20663.04 17-AUG-18:40 8945.92 12015.03 9581.50 0.00 0.00 0.00 0.00 0.00 0.00
September 21180.16 13-SEP-18:02 53675.50 72090.20 57488.97 0.00 0.00 0.00 0.00 0.00 0.00
October 19811.37 04-OCT-18:10 53675.50 72090.20 57488.97 0.00 0.00 0.00 0.00 0.00 0.00
November 19407.70 10-NOV-21:00 8945.92 13517.00 10113.80 0.00 0.00 0.00 0.00 0.00 0.00
December 19119.52 20-DEC-21:00 8945.92 13517.00 10113.80 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 18741.74   8945.92 12015.03 9581.50 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 21180.16   62621.41 84105.23 67070.47 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 3751.23 15-JAN-11:40 389.84 229.10 288.68 0.00 0.00 0.00 0.00 0.00 154.48
February 3947.29 04-FEB-11:40 389.84 190.92 252.59 0.00 0.00 0.00 0.00 0.00 167.10
March 2811.21 25-MAR-11:30 389.84 190.92 252.59 0.00 0.00 0.00 0.00 0.00 111.85
April 4043.60 30-APR-12:00 389.84 229.10 288.68 0.00 0.00 0.00 0.00 4.39 0.00
May 3691.53 23-MAY-12:00 259.90 190.92 252.59 0.00 0.00 0.00 0.00 0.00 12.58
June 3719.81 13-JUN-12:00 259.90 190.92 252.59 0.00 0.00 0.00 0.00 23.26 0.00
July 3959.08 22-JUL-12:00 389.84 190.92 252.59 0.00 0.00 0.00 0.00 67.25 0.00
August 4040.09 28-AUG-15:15 1299.48 381.83 505.18 0.00 0.00 0.00 0.00 27.81 0.00
September 4499.17 12-SEP-10:35 519.79 381.83 505.18 0.00 0.00 0.00 0.00 0.00 41.95
October 4323.16 04-OCT-10:35 519.79 381.83 505.18 0.00 0.00 0.00 0.00 0.00 100.36
November 3583.44 11-NOV-11:40 389.84 229.10 288.68 0.00 0.00 0.00 0.00 0.00 148.54
December 3280.02 18-DEC-13:30 259.90 190.92 252.59 0.00 0.00 0.00 0.00 0.00 164.79
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2811.21   259.90 190.92 252.59 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 4499.17   1299.48 381.83 505.18 0.00 0.00 0.00 0.00 67.25 167.10



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1715.87 23-JAN-21:00 1053.36 795.89 793.93 0.00 0.00 0.00 0.00 0.00 56.49
February 1725.63 27-FEB-21:00 1053.36 795.89 793.93 0.00 0.00 0.00 0.00 0.00 71.48
March 1749.82 20-MAR-20:00 1053.36 795.89 793.93 0.00 0.00 0.00 0.00 0.00 67.59
April 2001.47 27-APR-18:02 6320.16 4244.75 4512.87 0.00 0.00 0.00 0.00 0.00 14.43
May 2089.25 22-MAY-18:03 6320.16 4244.75 4512.87 0.00 0.00 0.00 0.00 0.00 9.13
June 2147.71 12-JUN-18:02 6320.16 4244.75 4512.87 0.00 0.00 0.00 0.00 20.85 0.00
July 2163.16 22-JUL-18:07 5417.28 3714.16 4011.44 0.00 0.00 0.00 0.00 38.67 0.00
August 2128.96 14-AUG-18:10 6320.16 4244.75 4512.87 0.00 0.00 0.00 0.00 24.31 0.00
September 2055.88 11-SEP-18:10 6320.16 4244.75 4512.87 0.00 0.00 0.00 0.00 2.12 0.00
October 1830.92 03-OCT-20:00 1053.36 795.89 793.93 0.00 0.00 0.00 0.00 0.00 68.61
November 1728.11 15-NOV-21:00 1053.36 795.89 793.93 0.00 0.00 0.00 0.00 0.00 67.05
December 1630.24 21-DEC-22:00 1203.84 707.46 752.15 0.00 0.00 0.00 0.00 0.00 88.02
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1630.24   1053.36 707.46 752.15 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 2163.16   6320.16 4244.75 4512.87 0.00 0.00 0.00 0.00 38.67 88.02



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1393.05 18-JAN-21:00 222.77 1487.69 839.45 0.00 0.00 0.00 0.00 0.00 146.45
February 1344.42 22-FEB-21:00 222.77 1487.69 839.45 0.00 0.00 0.00 0.00 0.00 179.81
March 1483.23 20-MAR-20:00 222.77 1487.69 839.45 0.00 0.00 0.00 0.00 0.00 158.70
April 1787.28 30-APR-19:10 381.89 2644.77 1590.53 0.00 0.00 0.00 0.00 19.29 0.00
May 1849.85 22-MAY-19:00 222.77 1322.39 795.27 0.00 0.00 0.00 0.00 0.00 21.59
June 1921.57 12-JUN-18:40 222.77 1322.39 795.27 0.00 0.00 0.00 0.00 38.83 0.00
July 1995.46 22-JUL-18:20 572.83 3471.27 2120.71 0.00 0.00 0.00 0.00 89.61 0.00
August 1913.65 14-AUG-18:30 222.77 1322.39 795.27 0.00 0.00 0.00 0.00 46.96 0.00
September 1799.39 11-SEP-18:50 222.77 1322.39 795.27 0.00 0.00 0.00 0.00 0.00 16.18
October 1625.67 10-OCT-20:00 222.77 1487.69 839.45 0.00 0.00 0.00 0.00 0.00 121.87
November 1480.96 08-NOV-21:00 222.77 1487.69 839.45 0.00 0.00 0.00 0.00 0.00 110.78
December 1267.13 05-DEC-21:00 222.77 1487.69 839.45 0.00 0.00 0.00 0.00 0.00 153.74
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1267.13   222.77 1322.39 795.27 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 1995.46   572.83 3471.27 2120.71 0.00 0.00 0.00 0.00 89.61 179.81



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 366.86 18-JAN-22:00 195.84 242.76 229.41 0.00 0.00 0.00 0.00 0.00 84.51
February 331.91 07-FEB-22:00 195.84 242.76 229.41 0.00 0.00 0.00 0.00 0.00 91.33
March 398.04 20-MAR-20:10 195.84 242.76 229.41 0.00 0.00 0.00 0.00 0.00 93.87
April 712.24 30-APR-19:05 293.76 485.51 458.82 0.00 0.00 0.00 0.00 11.25 0.00
May 731.11 22-MAY-19:40 171.36 273.10 242.16 0.00 0.00 0.00 0.00 0.00 20.83
June 860.91 13-JUN-19:05 342.72 546.20 484.31 0.00 0.00 0.00 0.00 0.00 5.69
July 902.38 22-JUL-18:25 293.76 424.82 407.84 0.00 0.00 0.00 0.00 50.80 0.00
August 787.07 14-AUG-20:40 195.84 242.76 229.41 0.00 0.00 0.00 0.00 0.00 12.26
September 712.15 12-SEP-21:00 195.84 242.76 229.41 0.00 0.00 0.00 0.00 0.00 37.91
October 483.63 10-OCT-20:50 195.84 242.76 229.41 0.00 0.00 0.00 0.00 0.00 75.92
November 430.97 08-NOV-22:00 195.84 242.76 229.41 0.00 0.00 0.00 0.00 0.00 63.91
December 275.45 05-DEC-21:00 171.36 273.10 242.16 0.00 0.00 0.00 0.00 0.00 88.70
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 275.45   171.36 242.76 229.41 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 902.38   342.72 546.20 484.31 0.00 0.00 0.00 0.00 50.80 93.87



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 35664.57 23-JAN-21:00 705.60 337.37 4572.80 39726.58 0.00 0.00 0.00 0.00 227.63
February 35682.37 07-FEB-21:00 705.60 337.37 4572.80 39726.58 0.00 0.00 0.00 0.00 246.20
March 35794.37 31-MAR-20:00 705.60 337.37 4572.80 39726.58 0.00 0.00 0.00 0.00 277.40
April 36617.29 28-APR-20:00 705.60 337.37 4572.80 39726.58 0.00 0.00 0.00 0.00 164.84
May 36735.67 22-MAY-20:00 705.60 337.37 4572.80 39726.58 0.00 0.00 0.00 0.00 100.88
June 36973.20 12-JUN-20:00 705.60 337.37 4572.80 39726.58 0.00 0.00 0.00 0.00 24.28
July 36964.54 21-JUL-20:00 705.60 337.37 4572.80 39726.58 0.00 0.00 0.00 0.00 43.55
August 36889.43 14-AUG-20:00 705.60 337.37 4572.80 39726.58 0.00 0.00 0.00 0.00 45.43
September 36676.41 12-SEP-20:00 705.60 337.37 4572.80 39726.58 0.00 0.00 0.00 0.00 134.33
October 36168.53 06-OCT-20:00 705.60 337.37 4572.80 39726.58 0.00 0.00 0.00 0.00 244.63
November 35766.00 08-NOV-21:00 705.60 337.37 4572.80 39726.58 0.00 0.00 0.00 0.00 196.30
December 35522.20 20-DEC-21:00 705.60 337.37 4572.80 39726.58 0.00 0.00 0.00 0.00 260.96
                       
Annual Sum or Average             0.00 0.00 0.00    
Minimum of Months 35522.20   705.60 337.37 4572.80 39726.58 0.00 0.00 0.00 0.00 24.28
Maximum of Months 36973.20   705.60 337.37 4572.80 39726.58 0.00 0.00 0.00 0.00 277.40



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 14641.12 07-JAN-11:35 10245.60 1209.57 711.25 0.00 0.00 0.00 0.00 0.00 391.45
February 15281.79 04-FEB-11:40 5122.80 604.78 355.63 0.00 0.00 0.00 0.00 0.00 367.16
March 11590.81 25-MAR-11:30 5122.80 604.78 355.63 0.00 0.00 0.00 0.00 0.00 247.10
April 15241.32 28-APR-15:13 25614.00 1814.35 1066.88 0.00 0.00 0.00 0.00 0.00 32.74
May 14076.33 22-MAY-15:03 51228.00 3628.71 2133.76 0.00 0.00 0.00 0.00 72.66 0.00
June 13984.59 13-JUN-15:02 51228.00 3628.71 2133.76 0.00 0.00 0.00 0.00 129.50 0.00
July 14800.29 21-JUL-15:13 25614.00 1814.35 1066.88 0.00 0.00 0.00 0.00 160.96 0.00
August 15556.68 28-AUG-15:15 17076.00 1209.57 711.25 0.00 0.00 0.00 0.00 65.75 0.00
September 16211.77 23-SEP-10:35 10245.60 1209.57 711.25 0.00 0.00 0.00 0.00 0.00 80.61
October 15990.71 07-OCT-10:35 10245.60 1209.57 711.25 0.00 0.00 0.00 0.00 0.00 169.99
November 13807.20 11-NOV-11:40 5122.80 725.74 406.43 0.00 0.00 0.00 0.00 0.00 329.30
December 12611.35 18-DEC-13:30 3415.20 604.78 355.63 0.00 0.00 0.00 0.00 0.00 360.39
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 11590.81   3415.20 604.78 355.63 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 16211.77   51228.00 3628.71 2133.76 0.00 0.00 0.00 0.00 160.96 391.45



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 36892.47 23-JAN-22:00 40553.76 10532.73 9501.36 0.00 0.00 0.00 0.00 0.00 1024.10
February 37124.24 27-FEB-21:00 35484.54 11849.32 10029.21 0.00 0.00 0.00 0.00 0.00 1164.36
March 37567.84 20-MAR-20:00 35484.54 11849.32 10029.21 0.00 0.00 0.00 0.00 0.00 1099.46
April 41752.33 27-APR-18:30 35484.54 10532.73 9501.36 0.00 0.00 0.00 0.00 0.00 261.22
May 43368.59 22-MAY-18:40 35484.54 10532.73 9501.36 0.00 0.00 0.00 0.00 0.00 149.54
June 44639.07 12-JUN-18:40 35484.54 10532.73 9501.36 0.00 0.00 0.00 0.00 268.79 0.00
July 44154.37 10-JUL-18:30 35484.54 10532.73 9501.36 0.00 0.00 0.00 0.00 0.00 74.83
August 44790.30 14-AUG-18:20 70969.08 21065.45 19002.71 0.00 0.00 0.00 0.00 362.23 0.00
September 43478.52 11-SEP-18:02 212907.24 63196.36 57008.13 0.00 0.00 0.00 0.00 36.74 0.00
October 39148.77 03-OCT-20:00 35484.54 11849.32 10029.21 0.00 0.00 0.00 0.00 0.00 1113.90
November 37318.51 15-NOV-21:00 35484.54 11849.32 10029.21 0.00 0.00 0.00 0.00 0.00 1093.56
December 35953.02 21-DEC-22:00 40553.76 10532.73 9501.36 0.00 0.00 0.00 0.00 0.00 1446.39
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 35953.02   35484.54 10532.73 9501.36 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 44790.30   212907.24 63196.36 57008.13 0.00 0.00 0.00 0.00 362.23 1446.39



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2738.75 25-JAN-16:01 680.40 769.75 479.39 0.00 0.00 0.00 0.00 0.00 89.26
February 3588.17 18-FEB-16:01 378.00 907.20 534.70 0.00 0.00 0.00 0.00 0.00 120.24
March 3467.60 31-MAR-15:01 680.40 769.75 479.39 0.00 0.00 0.00 0.00 0.00 104.08
April 3652.25 13-APR-15:02 583.20 659.78 410.90 0.00 0.00 0.00 0.00 0.00 74.85
May 3713.54 21-MAY-15:01 378.00 907.20 534.70 0.00 0.00 0.00 0.00 0.00 26.25
June 3547.78 08-JUN-18:02 831.60 2097.16 774.39 0.00 0.00 0.00 0.00 0.00 45.01
July 3527.11 26-JUL-15:02 583.20 659.78 410.90 0.00 0.00 0.00 0.00 0.00 19.51
August 3486.67 27-AUG-18:02 702.00 2356.36 774.39 0.00 0.00 0.00 0.00 0.00 41.93
September 3635.31 29-SEP-15:01 680.40 769.75 479.39 0.00 0.00 0.00 0.00 0.00 47.18
October 3661.29 07-OCT-15:02 324.00 777.60 458.31 0.00 0.00 0.00 0.00 0.00 25.12
November 3559.11 03-NOV-15:01 680.40 769.75 479.39 0.00 0.00 0.00 0.00 0.00 97.58
December 487.11 20-DEC-19:05 831.60 2097.16 774.39 0.00 0.00 0.00 0.00 0.00 96.22
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 487.11   324.00 659.78 410.90 0.00 0.00 0.00 0.00 0.00 19.51
Maximum of Months 3713.54   831.60 2356.36 774.39 0.00 0.00 0.00 0.00 0.00 120.24



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2001.23 19-JAN-16:01 680.40 769.66 479.33 0.00 0.00 0.00 0.00 0.00 97.39
February 2991.45 19-FEB-16:02 324.00 777.51 458.26 0.00 0.00 0.00 0.00 0.00 116.92
March 3004.22 20-MAR-18:02 831.60 2096.92 774.30 0.00 0.00 0.00 0.00 0.00 98.18
April 3258.57 26-APR-15:02 583.20 659.70 410.85 0.00 0.00 0.00 0.00 0.00 53.25
May 3342.63 21-MAY-15:01 378.00 907.09 534.64 0.00 0.00 0.00 0.00 0.00 26.29
June 3221.88 08-JUN-18:02 831.60 2096.92 774.30 0.00 0.00 0.00 0.00 0.00 45.66
July 3253.47 24-JUL-15:02 583.20 659.70 410.85 0.00 0.00 0.00 0.00 0.00 23.86
August 3236.95 19-AUG-15:02 324.00 777.51 458.26 0.00 0.00 0.00 0.00 0.00 17.93
September 3257.18 11-SEP-15:02 583.20 659.70 410.85 0.00 0.00 0.00 0.00 0.00 4.03
October 3255.35 07-OCT-15:02 324.00 777.51 458.26 0.00 0.00 0.00 0.00 0.00 24.39
November 1910.06 10-NOV-16:02 583.20 659.70 410.85 0.00 0.00 0.00 0.00 0.00 77.36
December 286.37 02-DEC-09:05 324.00 1319.41 979.73 0.00 0.00 0.00 0.00 0.00 101.38
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 286.37   324.00 659.70 410.85 0.00 0.00 0.00 0.00 0.00 4.03
Maximum of Months 3342.63   831.60 2096.92 979.73 0.00 0.00 0.00 0.00 0.00 116.92



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 580.61 21-JAN-11:25 0.00 162.90 149.63 0.00 0.00 0.00 0.00 0.00 34.96
February 527.06 04-FEB-14:00 0.00 81.45 74.82 0.00 0.00 0.00 0.00 0.00 28.53
March 252.23 25-MAR-11:40 0.00 81.45 74.82 0.00 0.00 0.00 0.00 0.00 22.59
April 733.86 30-APR-12:50 0.00 81.45 74.82 0.00 0.00 0.00 0.00 0.00 2.60
May 586.72 22-MAY-13:20 0.00 69.11 67.08 0.00 0.00 0.00 0.00 0.00 1.98
June 594.29 13-JUN-13:20 0.00 69.11 67.08 0.00 0.00 0.00 0.00 1.86 0.00
July 679.47 22-JUL-13:30 0.00 81.45 74.82 0.00 0.00 0.00 0.00 8.56 0.00
August 721.13 20-AUG-13:00 0.00 81.45 74.82 0.00 0.00 0.00 0.00 0.00 0.72
September 854.01 27-SEP-13:20 0.00 69.11 67.08 0.00 0.00 0.00 0.00 0.00 3.88
October 798.64 07-OCT-13:10 0.00 81.45 74.82 0.00 0.00 0.00 0.00 0.00 12.29
November 559.27 11-NOV-13:30 0.00 81.45 74.82 0.00 0.00 0.00 0.00 0.00 28.67
December 249.69 26-DEC-14:30 0.00 69.11 67.08 0.00 0.00 0.00 0.00 0.00 34.91
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 249.69   0.00 69.11 67.08 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 854.01   0.00 162.90 149.63 0.00 0.00 0.00 0.00 8.56 34.96



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 801.50 29-JAN-19:02 585.00 1234.41 632.25 0.00 0.00 0.00 0.00 0.00 24.68
February 868.92 12-FEB-09:02 324.00 829.52 959.99 0.00 0.00 0.00 0.00 0.00 37.89
March 909.11 20-MAR-18:02 831.60 1318.35 758.70 0.00 0.00 0.00 0.00 0.00 27.56
April 973.74 22-APR-15:02 324.00 488.83 449.03 0.00 0.00 0.00 0.00 0.00 8.91
May 984.28 28-MAY-18:01 819.00 1728.17 885.15 0.00 0.00 0.00 0.00 0.00 21.08
June 1019.41 12-JUN-18:02 831.60 1318.35 758.70 0.00 0.00 0.00 0.00 5.18 0.00
July 1008.63 10-JUL-15:02 583.20 414.76 402.58 0.00 0.00 0.00 0.00 0.00 0.16
August 980.70 14-AUG-15:02 583.20 414.76 402.58 0.00 0.00 0.00 0.00 5.25 0.00
September 972.44 11-SEP-18:02 831.60 1318.35 758.70 0.00 0.00 0.00 0.00 0.00 1.55
October 920.67 07-OCT-15:02 324.00 488.83 449.03 0.00 0.00 0.00 0.00 0.00 4.99
November 887.09 26-NOV-09:02 324.00 829.52 959.99 0.00 0.00 0.00 0.00 0.00 32.58
December 735.97 02-DEC-09:02 324.00 829.52 959.99 0.00 0.00 0.00 0.00 0.00 28.65
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 735.97   324.00 414.76 402.58 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 1019.41   831.60 1728.17 959.99 0.00 0.00 0.00 0.00 5.25 37.89



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1922.75 21-JAN-16:02 324.00 777.60 458.31 0.00 0.00 0.00 0.00 0.00 112.05
February 3066.15 04-FEB-16:01 378.00 907.20 534.70 0.00 0.00 0.00 0.00 0.00 103.86
March 2743.32 20-MAR-15:01 680.40 769.75 479.39 0.00 0.00 0.00 0.00 0.00 74.07
April 3326.83 15-APR-08:62 324.00 1319.56 979.84 0.00 0.00 0.00 0.00 0.00 94.14
May 3353.59 21-MAY-15:01 378.00 907.20 534.70 0.00 0.00 0.00 0.00 0.00 25.56
June 3251.29 13-JUN-08:62 216.00 1036.80 679.57 0.00 0.00 0.00 0.00 0.00 11.00
July 3270.73 23-JUL-08:61 378.00 1539.49 1143.15 0.00 0.00 0.00 0.00 0.00 25.17
August 3279.39 14-AUG-08:62 216.00 1036.80 679.57 0.00 0.00 0.00 0.00 0.00 17.08
September 3289.03 29-SEP-15:01 680.40 769.75 479.39 0.00 0.00 0.00 0.00 0.00 46.67
October 3310.68 07-OCT-15:02 324.00 777.60 458.31 0.00 0.00 0.00 0.00 0.00 24.52
November 3012.74 03-NOV-15:01 680.40 769.75 479.39 0.00 0.00 0.00 0.00 0.00 90.10
December 737.83 06-DEC-09:03 216.00 1036.80 679.57 0.00 0.00 0.00 0.00 0.00 135.42
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 737.83   216.00 769.75 458.31 0.00 0.00 0.00 0.00 0.00 11.00
Maximum of Months 3353.59   680.40 1539.49 1143.15 0.00 0.00 0.00 0.00 0.00 135.42



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 689.84 19-JAN-09:03 216.00 1036.68 679.49 0.00 0.00 0.00 0.00 0.00 100.53
February 1830.15 20-FEB-09:02 324.00 1319.41 979.73 0.00 0.00 0.00 0.00 0.00 128.78
March 912.17 10-MAR-09:02 180.00 863.90 566.24 0.00 0.00 0.00 0.00 0.00 99.08
April 3029.15 15-APR-08:62 324.00 1319.41 979.73 0.00 0.00 0.00 0.00 0.00 94.45
May 3041.75 21-MAY-15:01 378.00 907.09 534.64 0.00 0.00 0.00 0.00 0.00 25.56
June 2967.41 13-JUN-08:62 216.00 1036.68 679.49 0.00 0.00 0.00 0.00 0.00 11.58
July 2986.74 23-JUL-08:61 378.00 1539.31 1143.02 0.00 0.00 0.00 0.00 0.00 25.63
August 3006.14 14-AUG-08:62 216.00 1036.68 679.49 0.00 0.00 0.00 0.00 0.00 17.45
September 2940.32 23-SEP-08:62 324.00 1319.41 979.73 0.00 0.00 0.00 0.00 0.00 38.88
October 2842.10 07-OCT-15:02 324.00 777.51 458.26 0.00 0.00 0.00 0.00 0.00 19.55
November 1089.55 11-NOV-09:02 324.00 1319.41 979.73 0.00 0.00 0.00 0.00 0.00 105.87
December 505.73 11-DEC-09:05 216.00 1036.68 679.49 0.00 0.00 0.00 0.00 0.00 127.64
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 505.73   180.00 777.51 458.26 0.00 0.00 0.00 0.00 0.00 11.58
Maximum of Months 3041.75   378.00 1539.31 1143.02 0.00 0.00 0.00 0.00 0.00 128.78



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1577.81 23-JAN-22:03 6790.07 2565.21 0.00 0.00 0.00 0.00 0.00 0.00 112.07
February 1873.12 04-FEB-14:20 754.45 356.28 0.00 0.00 0.00 0.00 0.00 0.00 103.58
March 1761.06 20-MAR-18:03 10562.33 6840.55 0.00 0.00 0.00 0.00 0.00 0.00 114.88
April 2984.50 30-APR-10:35 1508.90 855.07 0.00 0.00 0.00 0.00 0.00 0.00 14.51
May 2832.46 22-MAY-18:10 10562.33 6840.55 0.00 0.00 0.00 0.00 0.00 0.00 18.38
June 2973.33 13-JUN-10:35 1005.94 712.56 0.00 0.00 0.00 0.00 0.00 7.83 0.00
July 3162.57 23-JUL-10:35 1508.90 855.07 0.00 0.00 0.00 0.00 0.00 0.00 2.72
August 3076.09 14-AUG-17:08 10059.36 6840.55 0.00 0.00 0.00 0.00 0.00 46.10 0.00
September 2913.29 12-SEP-10:35 1005.94 712.56 0.00 0.00 0.00 0.00 0.00 0.00 28.68
October 2457.14 07-OCT-17:12 6035.62 3420.27 0.00 0.00 0.00 0.00 0.00 0.00 62.36
November 1788.08 11-NOV-13:00 754.45 427.53 0.00 0.00 0.00 0.00 0.00 0.00 104.10
December 1236.39 21-DEC-22:03 6790.07 2565.21 0.00 0.00 0.00 0.00 0.00 0.00 159.79
                       
Annual Sum or Average         0.00 0.00 0.00 0.00 0.00    
Minimum of Months 1236.39   754.45 356.28 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3162.57   10562.33 6840.55 0.00 0.00 0.00 0.00 0.00 46.10 159.79



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2883.16 25-JAN-16:01 680.40 769.75 479.39 0.00 0.00 0.00 0.00 0.00 88.64
February 3812.42 09-FEB-16:01 680.40 769.75 479.39 0.00 0.00 0.00 0.00 0.00 105.37
March 3676.82 10-MAR-16:01 680.40 769.75 479.39 0.00 0.00 0.00 0.00 0.00 100.06
April 3907.50 13-APR-15:02 583.20 659.78 410.90 0.00 0.00 0.00 0.00 0.00 75.38
May 3970.98 21-MAY-15:01 378.00 907.20 534.70 0.00 0.00 0.00 0.00 0.00 26.76
June 3842.59 13-JUN-18:02 831.60 2097.16 774.39 0.00 0.00 0.00 0.00 3.50 0.00
July 3768.49 16-JUL-18:02 702.00 2356.36 774.39 0.00 0.00 0.00 0.00 0.00 26.79
August 3758.24 10-AUG-15:02 583.20 659.78 410.90 0.00 0.00 0.00 0.00 0.00 12.43
September 3863.96 29-SEP-15:01 680.40 769.75 479.39 0.00 0.00 0.00 0.00 0.00 47.28
October 3910.58 07-OCT-15:02 324.00 777.60 458.31 0.00 0.00 0.00 0.00 0.00 25.55
November 3748.33 03-NOV-15:01 680.40 769.75 479.39 0.00 0.00 0.00 0.00 0.00 96.85
December 386.08 26-DEC-16:05 583.20 659.78 410.90 0.00 0.00 0.00 0.00 0.00 135.32
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 386.08   324.00 659.78 410.90 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3970.98   831.60 2356.36 774.39 0.00 0.00 0.00 0.00 3.50 135.32



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1345.54 19-JAN-16:01 680.40 769.66 479.33 0.00 0.00 0.00 0.00 0.00 97.53
February 2757.61 19-FEB-16:02 324.00 777.51 458.26 0.00 0.00 0.00 0.00 0.00 116.25
March 3199.66 20-MAR-18:02 831.60 2096.92 774.30 0.00 0.00 0.00 0.00 0.00 99.20
April 3468.02 26-APR-15:02 583.20 659.70 410.85 0.00 0.00 0.00 0.00 0.00 53.87
May 3552.20 21-MAY-15:01 378.00 907.09 534.64 0.00 0.00 0.00 0.00 0.00 26.85
June 3499.22 13-JUN-18:02 831.60 2096.92 774.30 0.00 0.00 0.00 0.00 2.82 0.00
July 3426.28 24-JUL-18:02 831.60 2096.92 774.30 0.00 0.00 0.00 0.00 0.00 34.64
August 3396.68 27-AUG-15:02 324.00 777.51 458.26 0.00 0.00 0.00 0.00 0.00 30.48
September 3423.80 29-SEP-15:01 680.40 769.66 479.33 0.00 0.00 0.00 0.00 0.00 46.82
October 3445.90 07-OCT-15:02 324.00 777.51 458.26 0.00 0.00 0.00 0.00 0.00 24.69
November 1464.58 10-NOV-16:02 583.20 659.70 410.85 0.00 0.00 0.00 0.00 0.00 77.66
December 99.93 06-DEC-11:02 180.00 549.75 342.38 0.00 0.00 0.00 0.00 0.00 97.49
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 99.93   180.00 549.75 342.38 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3552.20   831.60 2096.92 774.30 0.00 0.00 0.00 0.00 2.82 116.25



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2366.52 11-JAN-16:01 680.40 483.89 469.67 0.00 0.00 0.00 0.00 0.00 92.35
February 2401.31 18-FEB-16:01 378.00 570.30 523.86 0.00 0.00 0.00 0.00 0.00 61.99
March 2373.54 20-MAR-15:01 680.40 483.89 469.67 0.00 0.00 0.00 0.00 0.00 42.18
April 2429.20 13-APR-15:02 583.20 414.76 402.58 0.00 0.00 0.00 0.00 0.00 38.55
May 2432.77 11-MAY-15:01 680.40 483.89 469.67 0.00 0.00 0.00 0.00 0.00 19.17
June 2327.33 12-JUN-18:02 831.60 1318.35 758.70 0.00 0.00 0.00 0.00 11.04 0.00
July 2345.99 26-JUL-15:02 583.20 414.76 402.58 0.00 0.00 0.00 0.00 0.00 9.89
August 2336.78 10-AUG-15:02 583.20 414.76 402.58 0.00 0.00 0.00 0.00 0.00 6.28
September 2403.17 29-SEP-15:01 680.40 483.89 469.67 0.00 0.00 0.00 0.00 0.00 24.19
October 2459.10 07-OCT-15:02 324.00 488.83 449.03 0.00 0.00 0.00 0.00 0.00 13.39
November 2411.53 03-NOV-15:01 680.40 483.89 469.67 0.00 0.00 0.00 0.00 0.00 50.89
December 2272.53 18-DEC-16:02 583.20 414.76 402.58 0.00 0.00 0.00 0.00 0.00 62.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2272.53   324.00 414.76 402.58 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 2459.10   831.60 1318.35 758.70 0.00 0.00 0.00 0.00 11.04 92.35



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 18575.80 18-JAN-23:00 26988.77 2548.93 6747.90 0.00 0.00 0.00 0.00 0.00 261.22
February 18510.29 07-FEB-23:00 26988.77 2548.93 6747.90 0.00 0.00 0.00 0.00 0.00 275.28
March 18656.64 17-MAR-22:00 26988.77 2548.93 6747.90 0.00 0.00 0.00 0.00 0.00 257.03
April 20484.79 29-APR-18:03 107955.07 17842.50 40487.42 0.00 0.00 0.00 0.00 0.00 32.40
May 21408.22 22-MAY-18:10 125947.58 20391.43 40487.42 0.00 0.00 0.00 0.00 0.00 47.79
June 22203.62 12-JUN-18:10 125947.58 20391.43 40487.42 0.00 0.00 0.00 0.00 60.88 0.00
July 22256.21 22-JUL-18:10 107955.07 17842.50 40487.42 0.00 0.00 0.00 0.00 128.48 0.00
August 22154.24 14-AUG-17:08 119950.08 20391.43 53983.22 0.00 0.00 0.00 0.00 88.31 0.00
September 20493.64 11-SEP-18:10 125947.58 20391.43 40487.42 0.00 0.00 0.00 0.00 0.00 3.26
October 19011.88 17-OCT-22:00 26988.77 2548.93 6747.90 0.00 0.00 0.00 0.00 0.00 203.33
November 18896.75 08-NOV-23:00 26988.77 2548.93 6747.90 0.00 0.00 0.00 0.00 0.00 203.21
December 18252.70 04-DEC-23:00 26988.77 2548.93 6747.90 0.00 0.00 0.00 0.00 0.00 269.23
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 18252.70   26988.77 2548.93 6747.90 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 22256.21   125947.58 20391.43 53983.22 0.00 0.00 0.00 0.00 128.48 275.28



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 19786.82 18-JAN-23:00 26988.77 2548.93 6747.90 0.00 0.00 0.00 0.00 0.00 263.13
February 19716.50 07-FEB-23:00 26988.77 2548.93 6747.90 0.00 0.00 0.00 0.00 0.00 277.18
March 19886.43 17-MAR-22:00 26988.77 2548.93 6747.90 0.00 0.00 0.00 0.00 0.00 259.02
April 21823.48 29-APR-18:03 107955.07 17842.50 40487.42 0.00 0.00 0.00 0.00 0.00 34.43
May 22778.05 22-MAY-18:10 125947.58 20391.43 40487.42 0.00 0.00 0.00 0.00 0.00 49.73
June 23613.89 12-JUN-18:10 125947.58 20391.43 40487.42 0.00 0.00 0.00 0.00 58.97 0.00
July 23677.26 22-JUL-18:10 107955.07 17842.50 40487.42 0.00 0.00 0.00 0.00 126.56 0.00
August 23569.19 14-AUG-17:08 119950.08 20391.43 53983.22 0.00 0.00 0.00 0.00 86.36 0.00
September 21788.01 11-SEP-18:10 125947.58 20391.43 40487.42 0.00 0.00 0.00 0.00 0.00 5.00
October 20255.36 17-OCT-22:00 26988.77 2548.93 6747.90 0.00 0.00 0.00 0.00 0.00 205.26
November 20135.01 08-NOV-23:00 26988.77 2548.93 6747.90 0.00 0.00 0.00 0.00 0.00 205.15
December 19445.97 04-DEC-23:00 26988.77 2548.93 6747.90 0.00 0.00 0.00 0.00 0.00 271.10
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 19445.97   26988.77 2548.93 6747.90 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 23677.26   125947.58 20391.43 53983.22 0.00 0.00 0.00 0.00 126.56 277.18



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 26672.72 15-JAN-11:50 800.57 340.26 15112.11 18744.03 0.00 0.00 0.00 0.00 239.64
February 26896.83 22-FEB-11:40 533.71 283.55 15112.11 18744.03 0.00 0.00 0.00 0.00 213.16
March 27770.77 25-MAR-10:50 1601.14 567.10 30224.21 37488.05 0.00 0.00 0.00 0.00 194.53
April 30429.54 30-APR-10:40 1601.14 680.52 30224.21 37488.05 0.00 0.00 0.00 0.00 70.86
May 30306.53 23-MAY-10:50 533.71 283.55 15112.11 18744.03 0.00 0.00 0.00 0.00 61.27
June 30626.29 13-JUN-10:40 1067.42 567.10 30224.21 37488.05 0.00 0.00 0.00 0.00 31.15
July 31221.45 23-JUL-10:40 1601.14 680.52 30224.21 37488.05 0.00 0.00 0.00 0.00 46.26
August 30773.76 14-AUG-17:08 10674.24 5444.15 120896.85 179942.65 0.00 0.00 0.00 41.29 0.00
September 29955.44 12-SEP-10:40 1067.42 567.10 30224.21 37488.05 0.00 0.00 0.00 0.00 97.07
October 28886.76 04-OCT-10:35 1067.42 567.10 30224.21 37488.05 0.00 0.00 0.00 0.00 171.25
November 26686.77 11-NOV-11:50 800.57 340.26 15112.11 18744.03 0.00 0.00 0.00 0.00 234.70
December 25726.04 03-DEC-11:50 800.57 340.26 15112.11 18744.03 0.00 0.00 0.00 0.00 270.75
                       
Annual Sum or Average             0.00 0.00 0.00    
Minimum of Months 25726.04   533.71 283.55 15112.11 18744.03 0.00 0.00 0.00 0.00 0.00
Maximum of Months 31221.45   10674.24 5444.15 120896.85 179942.65 0.00 0.00 0.00 41.29 270.75



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 3777.44 15-JAN-13:00 798.48 452.48 0.00 0.00 0.00 0.00 0.00 0.00 171.07
February 4167.31 04-FEB-13:40 798.48 377.07 0.00 0.00 0.00 0.00 0.00 0.00 184.17
March 4013.48 25-MAR-11:50 798.48 377.07 0.00 0.00 0.00 0.00 0.00 0.00 137.86
April 6741.10 29-APR-17:12 6387.84 3619.83 0.00 0.00 0.00 0.00 0.00 0.00 16.63
May 6669.91 22-MAY-17:12 5323.20 3619.83 0.00 0.00 0.00 0.00 0.00 0.00 31.10
June 7278.48 25-JUN-10:35 1596.96 904.96 0.00 0.00 0.00 0.00 0.00 0.00 16.29
July 7605.39 23-JUL-10:35 1596.96 904.96 0.00 0.00 0.00 0.00 0.00 0.00 2.77
August 7515.19 14-AUG-17:08 10646.40 7239.66 0.00 0.00 0.00 0.00 0.00 81.63 0.00
September 6493.49 13-SEP-16:20 1330.80 377.07 0.00 0.00 0.00 0.00 0.00 24.63 0.00
October 5688.90 07-OCT-15:30 798.48 377.07 0.00 0.00 0.00 0.00 0.00 0.00 38.95
November 3690.09 11-NOV-13:00 798.48 452.48 0.00 0.00 0.00 0.00 0.00 0.00 185.16
December 2749.62 18-DEC-13:30 532.32 377.07 0.00 0.00 0.00 0.00 0.00 0.00 200.89
                       
Annual Sum or Average         0.00 0.00 0.00 0.00 0.00    
Minimum of Months 2749.62   532.32 377.07 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 7605.39   10646.40 7239.66 0.00 0.00 0.00 0.00 0.00 81.63 200.89



Table of Contents

Report: EnergyConsumptionElectricityNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ELECTRICITY:FACILITY [J] ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} NATURALGAS:FACILITY [J] NATURALGAS:FACILITY {Maximum} [W] NATURALGAS:FACILITY {TIMESTAMP}
January 0.558669E+12 328709.79 23-JAN-20:49 0.639772E+12 523100.38 11-JAN-17:49
February 0.502924E+12 326790.77 22-FEB-20:49 0.562239E+12 445138.97 14-FEB-17:00
March 0.552614E+12 328419.46 20-MAR-19:49 0.613488E+12 450634.31 05-MAR-17:49
April 0.569749E+12 424440.37 30-APR-19:19 0.540661E+12 432792.14 04-APR-17:19
May 0.585822E+12 371889.35 22-MAY-19:10 0.552607E+12 429094.48 15-MAY-17:49
June 0.591862E+12 453115.40 25-JUN-18:10 0.515228E+12 419823.11 04-JUN-17:49
July 0.633105E+12 469437.58 22-JUL-18:10 0.520091E+12 406964.60 04-JUL-16:00
August 0.639125E+12 437511.97 14-AUG-18:10 0.513430E+12 396842.68 09-AUG-17:00
September 0.599318E+12 407203.88 11-SEP-18:10 0.501230E+12 402146.69 08-SEP-17:49
October 0.571819E+12 343334.13 02-OCT-19:19 0.563306E+12 425810.95 27-OCT-17:00
November 0.540382E+12 328579.91 15-NOV-20:00 0.584291E+12 444123.21 26-NOV-17:10
December 0.554789E+12 322194.23 20-DEC-20:00 0.648322E+12 501915.04 29-DEC-17:30
             
Annual Sum or Average 0.690018E+13     0.675467E+13    
Minimum of Months 0.502924E+12 322194.23   0.501230E+12 396842.68  
Maximum of Months 0.639125E+12 469437.58   0.648322E+12 523100.38  



Table of Contents

Report: EndUseEnergyConsumptionElectricityMonthly

For: Meter

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY [J] EXTERIORLIGHTS:ELECTRICITY [J] INTERIOREQUIPMENT:ELECTRICITY [J] EXTERIOREQUIPMENT:ELECTRICITY [J] FANS:ELECTRICITY [J] PUMPS:ELECTRICITY [J] HEATING:ELECTRICITY [J] COOLING:ELECTRICITY [J] HEATREJECTION:ELECTRICITY [] HUMIDIFIER:ELECTRICITY [] HEATRECOVERY:ELECTRICITY [J] WATERSYSTEMS:ELECTRICITY [J] COGENERATION:ELECTRICITY []
January 0.997859E+11 0.286107E+11 0.148746E+12 0.577258E+11 0.151285E+12 0.601509E+10 0.00 0.500455E+10 0.00 0.00 0.475276E+11 0.770799E+10 0.00
February 0.901073E+11 0.235435E+11 0.134341E+12 0.521396E+11 0.136131E+12 0.578722E+10 0.00 0.529441E+10 0.00 0.00 0.429545E+11 0.696516E+10 0.00
March 0.995228E+11 0.229126E+11 0.148757E+12 0.577286E+11 0.149486E+12 0.693914E+10 0.00 0.573984E+10 0.00 0.00 0.475471E+11 0.770665E+10 0.00
April 0.965474E+11 0.189870E+11 0.143913E+12 0.558635E+11 0.149628E+12 0.133032E+11 0.00 0.367272E+11 0.00 0.00 0.412220E+11 0.746767E+10 0.00
May 0.996636E+11 0.168239E+11 0.148757E+12 0.577273E+11 0.154383E+12 0.138606E+11 0.00 0.392408E+11 0.00 0.00 0.413242E+11 0.770734E+10 0.00
June 0.963626E+11 0.147910E+11 0.143963E+12 0.558662E+11 0.151869E+12 0.153260E+11 0.00 0.704460E+11 0.00 0.00 0.295990E+11 0.745932E+10 0.00
July 0.998551E+11 0.159427E+11 0.148708E+12 0.577246E+11 0.158288E+12 0.169577E+11 0.00 0.999313E+11 0.00 0.00 0.216121E+11 0.771508E+10 0.00
August 0.995413E+11 0.183761E+11 0.148768E+12 0.577287E+11 0.157827E+12 0.174100E+11 0.00 0.109496E+12 0.00 0.00 0.158725E+11 0.770697E+10 0.00
September 0.965794E+11 0.207895E+11 0.143924E+12 0.558636E+11 0.152101E+12 0.155743E+11 0.00 0.745081E+11 0.00 0.00 0.263392E+11 0.746895E+10 0.00
October 0.997606E+11 0.247552E+11 0.148735E+12 0.577257E+11 0.151580E+12 0.108966E+11 0.00 0.201605E+11 0.00 0.00 0.441759E+11 0.770633E+10 0.00
November 0.965244E+11 0.268181E+11 0.143978E+12 0.558644E+11 0.145341E+12 0.668908E+10 0.00 0.575846E+10 0.00 0.00 0.458800E+11 0.745234E+10 0.00
December 0.998619E+11 0.293818E+11 0.148708E+12 0.577246E+11 0.151814E+12 0.404644E+10 0.00 0.173023E+10 0.00 0.00 0.475568E+11 0.771633E+10 0.00
                           
Annual Sum or Average 0.117411E+13 0.261732E+12 0.175130E+13 0.679683E+12 0.180973E+13 0.132805E+12 0.00 0.474038E+12 0.00 0.00 0.451611E+12 0.907801E+11 0.00
Minimum of Months 0.901073E+11 0.147910E+11 0.134341E+12 0.521396E+11 0.136131E+12 0.404644E+10 0.00 0.173023E+10 0.00 0.00 0.158725E+11 0.696516E+10 0.00
Maximum of Months 0.998619E+11 0.293818E+11 0.148768E+12 0.577287E+11 0.158288E+12 0.174100E+11 0.00 0.109496E+12 0.00 0.00 0.475568E+11 0.771633E+10 0.00



Table of Contents

Report: EndUseEnergyConsumptionNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS [J] EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS [J] COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS [J] COGENERATION:NATURALGAS [] HUMIDIFIER:NATURALGAS []
January 0.151918E+12 0.00 0.196158E+12 0.00 0.291697E+12 0.00 0.00
February 0.137204E+12 0.00 0.160371E+12 0.00 0.264664E+12 0.00 0.00
March 0.152024E+12 0.00 0.169699E+12 0.00 0.291765E+12 0.00 0.00
April 0.146956E+12 0.00 0.114933E+12 0.00 0.278773E+12 0.00 0.00
May 0.151978E+12 0.00 0.117614E+12 0.00 0.283015E+12 0.00 0.00
June 0.147114E+12 0.00 0.990932E+11 0.00 0.269021E+12 0.00 0.00
July 0.151820E+12 0.00 0.940916E+11 0.00 0.274179E+12 0.00 0.00
August 0.152039E+12 0.00 0.885188E+11 0.00 0.272873E+12 0.00 0.00
September 0.146971E+12 0.00 0.889284E+11 0.00 0.265331E+12 0.00 0.00
October 0.151903E+12 0.00 0.133560E+12 0.00 0.277843E+12 0.00 0.00
November 0.147091E+12 0.00 0.163434E+12 0.00 0.273767E+12 0.00 0.00
December 0.151820E+12 0.00 0.208538E+12 0.00 0.287963E+12 0.00 0.00
               
Annual Sum or Average 0.178884E+13 0.00 0.163494E+13 0.00 0.333089E+13 0.00 0.00
Minimum of Months 0.137204E+12 0.00 0.885188E+11 0.00 0.264664E+12 0.00 0.00
Maximum of Months 0.152039E+12 0.00 0.208538E+12 0.00 0.291765E+12 0.00 0.00



Table of Contents

Report: PeakEnergyEndUseElectricityPart1Monthly

For: Meter

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY {Maximum} [W] INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} FANS:ELECTRICITY {Maximum} [W] FANS:ELECTRICITY {TIMESTAMP} PUMPS:ELECTRICITY {Maximum} [W] PUMPS:ELECTRICITY {TIMESTAMP} HEATING:ELECTRICITY {Maximum} [W] HEATING:ELECTRICITY {TIMESTAMP}
January 93091.76 02-JAN-20:10 16690.39 01-JAN-00:10 89674.66 02-JAN-07:10 40537.60 02-JAN-07:19 70136.67 12-JAN-16:10 6042.54 21-JAN-10:00 0.00 01-JAN-00:10
February 93091.76 01-FEB-20:10 16690.39 01-FEB-00:10 89674.66 01-FEB-07:10 40537.60 01-FEB-07:19 65894.88 17-FEB-16:10 6106.87 19-FEB-16:10 0.00 01-FEB-00:10
March 93091.76 01-MAR-20:10 16690.39 01-MAR-00:10 89674.66 01-MAR-07:10 40537.60 01-MAR-07:19 64298.86 15-MAR-15:09 5884.42 20-MAR-16:19 0.00 01-MAR-00:10
April 93091.76 03-APR-19:10 16690.39 01-APR-00:10 89674.66 03-APR-06:10 40537.60 03-APR-06:19 76873.48 30-APR-15:20 8581.04 29-APR-16:49 0.00 01-APR-00:10
May 93091.76 01-MAY-19:10 16690.39 01-MAY-00:10 89674.66 01-MAY-06:10 40537.60 01-MAY-06:19 72623.81 22-MAY-15:09 8471.57 21-MAY-16:00 0.00 01-MAY-00:10
June 93091.76 01-JUN-19:10 16690.39 01-JUN-00:10 89674.66 01-JUN-06:10 40537.60 01-JUN-06:19 75394.20 13-JUN-18:19 8825.76 25-JUN-18:10 0.00 01-JUN-00:10
July 93091.76 03-JUL-19:10 16690.39 01-JUL-00:10 89674.66 03-JUL-06:10 40537.60 03-JUL-06:19 76877.01 22-JUL-15:20 8954.24 22-JUL-18:10 0.00 01-JUL-00:10
August 93091.76 01-AUG-19:10 16690.39 01-AUG-00:10 89674.66 01-AUG-06:10 40537.60 01-AUG-06:19 74014.04 20-AUG-15:09 8919.94 14-AUG-16:00 0.00 01-AUG-00:10
September 93091.76 01-SEP-19:10 16690.39 01-SEP-00:10 89674.66 01-SEP-06:10 40537.60 01-SEP-06:19 73752.24 25-SEP-15:20 8693.37 27-SEP-15:00 0.00 01-SEP-00:10
October 93091.76 02-OCT-19:10 16690.39 01-OCT-00:10 89674.66 02-OCT-06:10 40537.60 02-OCT-06:19 70274.88 01-OCT-15:09 7738.92 07-OCT-15:30 0.00 01-OCT-00:10
November 93091.76 01-NOV-19:10 16690.39 01-NOV-00:10 89674.66 01-NOV-06:10 40537.60 01-NOV-06:19 67801.53 29-NOV-16:10 6149.84 24-NOV-11:50 0.00 01-NOV-00:10
December 93091.76 01-DEC-20:10 16690.39 01-DEC-00:10 89674.66 01-DEC-07:10 40537.60 01-DEC-07:19 69286.88 27-DEC-16:10 5082.14 26-DEC-14:30 0.00 01-DEC-00:10
                             
Annual Sum or Average                            
Minimum of Months 93091.76   16690.39   89674.66   40537.60   64298.86   5082.14   0.00  
Maximum of Months 93091.76   16690.39   89674.66   40537.60   76877.01   8954.24   0.00  



Table of Contents

Report: PeakEnergyEndUseElectricityPart2Monthly

For: Meter

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

COOLING:ELECTRICITY {Maximum} [W] COOLING:ELECTRICITY {TIMESTAMP} HEATREJECTION:ELECTRICITY [] HUMIDIFIER:ELECTRICITY [] HEATRECOVERY:ELECTRICITY {Maximum} [W] HEATRECOVERY:ELECTRICITY {TIMESTAMP} WATERSYSTEMS:ELECTRICITY {Maximum} [W] WATERSYSTEMS:ELECTRICITY {TIMESTAMP} COGENERATION:ELECTRICITY []
January 18897.72 21-JAN-10:00 0.00 0.00 17755.68 01-JAN-00:10 4739.90 02-JAN-07:10 0.00
February 20020.55 19-FEB-16:10 0.00 0.00 17755.68 01-FEB-00:10 4739.76 22-FEB-07:10 0.00
March 13036.05 25-MAR-20:19 0.00 0.00 17755.68 01-MAR-00:10 4738.91 17-MAR-06:10 0.00
April 120587.90 30-APR-18:10 0.00 0.00 17755.68 30-APR-17:10 4738.50 10-APR-06:00 0.00
May 116124.61 22-MAY-15:09 0.00 0.00 17755.68 01-MAY-00:10 4738.87 31-MAY-06:10 0.00
June 161469.84 25-JUN-18:19 0.00 0.00 17755.68 12-JUN-17:10 4738.63 19-JUN-06:30 0.00
July 167714.04 22-JUL-18:10 0.00 0.00 17755.68 21-JUL-17:10 4738.66 27-JUL-18:10 0.00
August 136463.25 14-AUG-18:10 0.00 0.00 17755.68 14-AUG-17:10 4738.46 28-AUG-06:30 0.00
September 115962.91 13-SEP-15:50 0.00 0.00 17755.68 11-SEP-17:10 4738.78 18-SEP-06:30 0.00
October 75575.79 07-OCT-15:09 0.00 0.00 17755.68 01-OCT-00:10 4739.32 24-OCT-06:10 0.00
November 26968.99 24-NOV-11:50 0.00 0.00 17755.68 01-NOV-00:10 4738.81 14-NOV-07:10 0.00
December 7486.44 26-DEC-12:39 0.00 0.00 17755.68 01-DEC-00:10 4738.82 18-DEC-07:00 0.00
                   
Annual Sum or Average     0.00 0.00         0.00
Minimum of Months 7486.44   0.00 0.00 17755.68   4738.46   0.00
Maximum of Months 167714.04   0.00 0.00 17755.68   4739.90   0.00



Table of Contents

Report: ElectricComponentsOfPeakDemandMonthly

For: Meter

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] FANS:ELECTRICITY {AT MAX/MIN} [W] PUMPS:ELECTRICITY {AT MAX/MIN} [W] HEATING:ELECTRICITY {AT MAX/MIN} [W] COOLING:ELECTRICITY {AT MAX/MIN} [W] HEATREJECTION:ELECTRICITY []
January 328709.79 23-JAN-20:49 93091.76 88971.67 16690.39 33025.38 58039.62 5287.55 0.00 9033.71 0.00
February 326790.77 22-FEB-20:49 93091.76 88971.67 16690.39 33025.38 57819.90 5156.62 0.00 7315.46 0.00
March 328419.46 20-MAR-19:49 93091.76 88971.67 16690.39 33025.38 57462.95 5225.61 0.00 9293.37 0.00
April 424440.37 30-APR-19:19 87949.43 87485.24 16690.39 32967.42 67334.79 8151.21 0.00 101621.97 0.00
May 371889.35 22-MAY-19:10 93091.76 88971.67 0.00 33012.66 65693.88 7762.25 0.00 76666.74 0.00
June 453115.40 25-JUN-18:10 82807.27 76644.19 0.00 32602.97 72758.06 8825.76 0.00 156610.18 0.00
July 469437.58 22-JUL-18:10 82807.27 76644.19 0.00 32608.13 75740.31 8954.24 0.00 167714.04 0.00
August 437511.97 14-AUG-18:10 82800.17 79617.06 0.00 32686.23 72582.29 8097.84 0.00 136463.25 0.00
September 407203.88 11-SEP-18:10 82800.17 79617.06 0.00 32686.23 68260.93 8064.67 0.00 111903.73 0.00
October 343334.13 02-OCT-19:19 93091.76 88971.67 16690.39 33025.38 60783.97 6281.12 0.00 19961.16 0.00
November 328579.91 15-NOV-20:00 93091.76 88971.67 16690.39 33025.38 58075.96 5296.37 0.00 8953.87 0.00
December 322194.23 20-DEC-20:00 93091.76 88971.67 16690.39 33025.38 56933.01 4608.04 0.00 4368.40 0.00
                       
Annual Sum or Average                     0.00
Minimum of Months 322194.23   82800.17 76644.19 0.00 32602.97 56933.01 4608.04 0.00 4368.40 0.00
Maximum of Months 469437.58   93091.76 88971.67 16690.39 33025.38 75740.31 8954.24 0.00 167714.04 0.00



Table of Contents

Report: PeakEnergyEndUseNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS {Maximum} [W] INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS {Maximum} [W] HEATING:NATURALGAS {TIMESTAMP} COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS {Maximum} [W] WATERSYSTEMS:NATURALGAS {TIMESTAMP} COGENERATION:NATURALGAS []
January 104248.32 02-JAN-18:10 0.00 203209.92 10-JAN-09:09 0.00 289656.02 31-JAN-21:30 0.00
February 104248.32 01-FEB-18:10 0.00 152664.73 17-FEB-07:10 0.00 289920.15 16-FEB-21:40 0.00
March 104248.32 01-MAR-18:10 0.00 119187.94 15-MAR-08:09 0.00 289618.33 03-MAR-21:30 0.00
April 104248.32 01-APR-17:10 0.00 112454.81 18-APR-10:39 0.00 287215.33 04-APR-20:19 0.00
May 104248.32 01-MAY-17:10 0.00 115745.97 18-MAY-10:39 0.00 283456.88 04-MAY-20:40 0.00
June 104248.32 01-JUN-17:10 0.00 114377.63 07-JUN-10:39 0.00 274154.56 07-JUN-20:19 0.00
July 104248.32 01-JUL-17:10 0.00 111406.41 03-JUL-10:39 0.00 250760.43 03-JUL-20:00 0.00
August 104248.32 01-AUG-17:10 0.00 110406.22 08-AUG-10:39 0.00 250565.72 21-AUG-20:40 0.00
September 104248.32 01-SEP-17:10 0.00 113519.46 08-SEP-10:39 0.00 253252.95 28-SEP-20:49 0.00
October 104248.32 02-OCT-17:10 0.00 115511.19 17-OCT-10:39 0.00 272938.46 31-OCT-20:40 0.00
November 104248.32 01-NOV-17:10 0.00 135348.42 29-NOV-09:09 0.00 276263.30 22-NOV-21:40 0.00
December 104248.32 01-DEC-18:10 0.00 166881.62 27-DEC-09:09 0.00 287262.92 28-DEC-21:19 0.00
                   
Annual Sum or Average     0.00     0.00     0.00
Minimum of Months 104248.32   0.00 110406.22   0.00 250565.72   0.00
Maximum of Months 104248.32   0.00 203209.92   0.00 289920.15   0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 7.50 20.39 7.50 20.39 0.00 20.39 0.00 20.39
February 0.50 20.41 0.50 20.41 0.00 20.41 0.00 20.41
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 15.33 20.41 15.33 20.41 0.00 20.41 0.00 20.41
                 
Annual Sum or Average 23.33 20.40 23.33 20.40 0.00 20.40 0.00 20.40
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 15.33 20.41 15.33 20.41 0.00 20.41 0.00 20.41



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.83 21.73 0.83 21.73
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.17 21.72 0.17 21.72
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   1.00 21.73 1.00 21.73
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.83 21.73 0.83 21.73



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.33 20.55 0.33 20.55 0.00 20.55 0.00 20.55
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.33 21.76 0.33 21.76
May 0.00 0.00 0.00 0.00 0.17 21.68 0.17 21.68
June 0.00 0.00 0.00 0.00 0.17 21.74 0.17 21.74
July 0.00 0.00 0.00 0.00 0.17 21.93 0.17 21.93
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.17 20.55 0.17 20.55 0.00 20.55 0.00 20.55
                 
Annual Sum or Average 0.50 20.55 0.50 20.55 0.83 21.10 0.83 21.31
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.33 20.55 0.33 20.55 0.33 21.93 0.33 21.93



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.33 20.53 0.33 20.53 0.00 20.53 0.00 20.53
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.17 21.69 0.17 21.69
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.50 21.71 0.50 21.71
July 0.00 0.00 0.00 0.00 0.33 21.78 0.33 21.78
August 0.00 0.00 0.00 0.00 0.17 21.70 0.17 21.70
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.33 20.53 0.33 20.53 1.17 21.29 1.17 21.46
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.33 20.53 0.33 20.53 0.50 21.78 0.50 21.78



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.50 20.54 0.50 20.54 0.00 20.54 0.00 20.54
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.33 20.53 0.33 20.53 0.00 20.53 0.00 20.53
                 
Annual Sum or Average 0.83 20.53 0.83 20.53 0.00 20.53 0.00 20.53
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.50 20.54 0.50 20.54 0.00 20.54 0.00 20.54



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 1.33 21.86 1.33 21.86
May 0.00 0.00 0.00 0.00 0.17 21.75 0.17 21.75
June 0.00 0.00 0.00 0.00 0.17 21.75 0.17 21.75
July 0.00 0.00 0.00 0.00 0.50 21.89 0.50 21.89
August 0.00 0.00 0.00 0.00 0.50 21.73 0.50 21.73
September 0.00 0.00 0.00 0.00 0.50 21.70 0.50 21.70
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   3.17 21.81 3.17 21.81
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 1.33 21.89 1.33 21.89



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.67 21.85 0.67 21.85
May 0.00 0.00 0.00 0.00 0.50 21.71 0.50 21.71
June 0.00 0.00 0.00 0.00 0.67 21.74 0.67 21.74
July 0.00 0.00 0.00 0.00 1.17 21.79 1.17 21.79
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.17 20.55 0.17 20.55 0.00 20.55 0.00 20.55
                 
Annual Sum or Average 0.17 20.55 0.17 20.55 3.00 21.65 3.00 21.71
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.17 20.55 0.17 20.55 1.17 21.85 1.17 21.85



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.33 21.72 0.33 21.72
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.50 21.79 0.50 21.79
October 0.00 0.00 0.00 0.00 0.17 21.75 0.17 21.75
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   1.00 21.76 1.00 21.76
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.50 21.79 0.50 21.79



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: BASEMENT

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.06 3.33 21.06 3.33 21.06
February 672.00 21.05 0.00 21.05 0.00 21.05
March 744.00 21.04 0.00 21.04 0.00 21.04
April 720.00 21.03 0.00 21.03 0.00 21.03
May 744.00 21.03 0.00 21.03 0.00 21.03
June 720.00 21.03 0.00 21.03 0.00 21.03
July 744.00 21.04 0.00 21.04 0.00 21.04
August 744.00 21.05 0.00 21.05 0.00 21.05
September 720.00 21.07 0.00 21.07 0.00 21.07
October 744.00 21.09 0.00 21.09 0.00 21.09
November 720.00 21.11 0.00 21.11 0.00 21.11
December 744.00 21.09 0.00 21.09 0.00 21.09
             
Annual Sum or Average 8760.00 21.06 3.33 21.06 3.33 21.06
Minimum of Months 672.00 21.03 0.00 21.03 0.00 21.03
Maximum of Months 744.00 21.11 3.33 21.11 3.33 21.11



Table of Contents

Report: ComfortReportSimple55Monthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 20.95 290.33 20.92 290.33 20.91
February 672.00 20.99 183.83 20.97 183.83 20.95
March 744.00 20.99 216.67 20.98 216.67 20.98
April 720.00 21.04 24.33 21.04 24.33 21.04
May 744.00 21.01 4.17 21.01 4.17 21.01
June 720.00 21.01 0.00 21.01 0.00 21.01
July 744.00 21.02 0.00 21.02 0.00 21.02
August 735.67 21.05 0.00 21.05 0.00 21.05
September 681.00 21.05 12.00 21.07 0.00 21.07
October 740.67 21.03 9.33 21.03 9.33 21.03
November 720.00 20.98 160.50 20.97 160.50 20.96
December 744.00 20.88 498.83 20.85 498.83 20.84
             
Annual Sum or Average 8709.33 21.00 1400.00 20.98 1388.00 20.97
Minimum of Months 672.00 20.88 0.00 20.85 0.00 20.84
Maximum of Months 744.00 21.05 498.83 21.07 498.83 21.07



Table of Contents

Report: ComfortReportSimple55Monthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.00 0.83 21.00 0.83 21.00
February 672.00 21.01 0.00 21.01 0.00 21.01
March 744.00 21.01 0.00 21.01 0.00 21.01
April 720.00 21.04 0.00 21.04 0.00 21.04
May 744.00 21.05 0.00 21.05 0.00 21.05
June 720.00 21.08 0.00 21.08 0.00 21.08
July 744.00 21.09 0.00 21.09 0.00 21.09
August 744.00 21.09 0.00 21.09 0.00 21.09
September 720.00 21.07 0.00 21.07 0.00 21.07
October 744.00 21.02 0.00 21.02 0.00 21.02
November 720.00 21.01 0.00 21.01 0.00 21.01
December 744.00 21.00 5.00 21.00 5.00 21.00
             
Annual Sum or Average 8760.00 21.04 5.83 21.04 5.83 21.04
Minimum of Months 672.00 21.00 0.00 21.00 0.00 21.00
Maximum of Months 744.00 21.09 5.00 21.09 5.00 21.09



Table of Contents

Report: ComfortReportSimple55Monthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.00 77.33 21.00 77.33 21.00
February 672.00 21.00 0.00 21.00 0.00 21.00
March 744.00 21.00 0.00 21.00 0.00 21.00
April 720.00 21.00 0.00 21.00 0.00 21.00
May 744.00 21.01 0.00 21.01 0.00 21.01
June 720.00 21.02 0.00 21.02 0.00 21.02
July 744.00 21.03 0.00 21.03 0.00 21.03
August 744.00 21.03 0.00 21.03 0.00 21.03
September 720.00 21.01 0.00 21.01 0.00 21.01
October 744.00 21.00 0.00 21.00 0.00 21.00
November 720.00 21.00 1.00 21.00 1.00 21.00
December 744.00 21.00 31.33 21.00 31.33 21.00
             
Annual Sum or Average 8760.00 21.01 109.67 21.01 109.67 21.01
Minimum of Months 672.00 21.00 0.00 21.00 0.00 21.00
Maximum of Months 744.00 21.03 77.33 21.03 77.33 21.03



Table of Contents

Report: ComfortReportSimple55Monthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.00 129.67 21.00 129.67 21.00
February 672.00 21.00 10.67 21.00 10.67 21.00
March 744.00 21.00 2.17 21.00 2.17 21.00
April 720.00 21.00 0.67 21.00 0.67 21.00
May 744.00 21.00 0.00 21.00 0.00 21.00
June 720.00 21.00 0.00 21.00 0.00 21.00
July 744.00 21.00 0.00 21.00 0.00 21.00
August 744.00 21.00 0.00 21.00 0.00 21.00
September 720.00 21.00 0.00 21.00 0.00 21.00
October 744.00 21.00 0.00 21.00 0.00 21.00
November 720.00 21.00 16.17 21.00 16.17 21.00
December 744.00 21.00 88.50 21.00 88.50 21.00
             
Annual Sum or Average 8760.00 21.00 247.83 21.00 247.83 21.00
Minimum of Months 672.00 21.00 0.00 21.00 0.00 21.00
Maximum of Months 744.00 21.00 129.67 21.00 129.67 21.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 541.50 21.42 164.33 21.77 85.17 21.97
February 487.50 21.43 153.33 21.77 78.50 21.98
March 533.50 21.47 172.50 21.80 96.00 22.02
April 477.17 21.49 181.67 21.79 94.33 22.01
May 433.50 21.58 214.33 21.85 101.67 22.07
June 261.17 21.96 277.50 22.00 104.33 22.23
July 244.50 22.00 301.33 21.97 103.67 22.19
August 248.00 22.06 313.33 22.01 109.50 22.23
September 278.17 21.90 258.67 22.02 103.17 22.25
October 461.00 21.55 210.00 21.85 100.33 22.07
November 498.50 21.47 176.83 21.80 88.67 22.01
December 547.33 21.39 159.33 21.75 80.83 21.95
             
Annual Sum or Average 5011.83 21.57 2583.17 21.86 1146.17 22.07
Minimum of Months 244.50 21.39 153.33 21.75 78.50 21.95
Maximum of Months 547.33 22.06 313.33 22.02 109.50 22.25



Table of Contents

Report: ComfortReportSimple55Monthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.00 34.67 21.00 34.67 21.00
February 669.83 21.01 1.17 21.01 1.17 21.01
March 744.00 21.00 0.00 21.00 0.00 21.00
April 716.83 21.02 0.00 21.02 0.00 21.02
May 744.00 21.00 0.00 21.00 0.00 21.00
June 720.00 21.00 0.00 21.00 0.00 21.00
July 744.00 21.01 0.00 21.01 0.00 21.01
August 732.67 21.02 0.00 21.02 0.00 21.02
September 672.83 21.02 13.17 21.04 0.00 21.04
October 737.83 21.02 0.00 21.02 0.00 21.02
November 720.00 21.00 5.50 21.00 5.50 21.00
December 744.00 20.99 64.17 20.98 64.17 20.98
             
Annual Sum or Average 8690.00 21.01 118.67 21.01 105.50 21.01
Minimum of Months 669.83 20.99 0.00 20.98 0.00 20.98
Maximum of Months 744.00 21.02 64.17 21.04 64.17 21.04



Table of Contents

Report: ComfortReportSimple55Monthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.01 0.00 21.01 0.00 21.01
February 672.00 21.01 0.00 21.01 0.00 21.01
March 744.00 21.02 0.00 21.02 0.00 21.02
April 720.00 21.05 0.00 21.05 0.00 21.05
May 744.00 21.06 0.00 21.06 0.00 21.06
June 720.00 21.09 0.00 21.09 0.00 21.09
July 744.00 21.11 0.00 21.11 0.00 21.11
August 744.00 21.12 0.00 21.12 0.00 21.12
September 720.00 21.10 0.00 21.10 0.00 21.10
October 744.00 21.04 0.00 21.04 0.00 21.04
November 720.00 21.02 0.00 21.02 0.00 21.02
December 744.00 21.01 0.00 21.01 0.00 21.01
             
Annual Sum or Average 8760.00 21.05 0.00 21.05 0.00 21.05
Minimum of Months 672.00 21.01 0.00 21.01 0.00 21.01
Maximum of Months 744.00 21.12 0.00 21.12 0.00 21.12



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 20.88 358.33 20.77 358.33 20.72
February 672.00 21.01 220.83 20.90 220.83 20.84
March 744.00 20.95 196.50 20.88 196.50 20.83
April 700.17 21.46 8.50 21.45 7.33 21.44
May 718.67 21.43 3.50 21.44 0.00 21.44
June 669.83 21.48 9.50 21.51 0.00 21.51
July 669.17 21.46 16.83 21.50 0.00 21.50
August 664.83 21.45 10.00 21.48 0.00 21.48
September 666.00 21.46 9.67 21.49 0.00 21.49
October 737.17 21.20 32.00 21.15 32.00 21.10
November 720.00 20.93 224.50 20.81 224.50 20.74
December 744.00 20.68 586.33 20.63 586.33 20.61
             
Annual Sum or Average 8449.83 21.19 1676.50 21.10 1625.83 21.02
Minimum of Months 664.83 20.68 3.50 20.63 0.00 20.61
Maximum of Months 744.00 21.48 586.33 21.51 586.33 21.51



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 20.67 495.50 20.59 495.50 20.56
February 672.00 20.78 373.00 20.68 373.00 20.63
March 744.00 20.85 300.00 20.76 300.00 20.71
April 714.17 21.32 15.50 21.30 15.50 21.29
May 732.17 21.37 0.33 21.37 0.17 21.37
June 688.83 21.48 5.00 21.49 0.00 21.49
July 697.50 21.48 4.50 21.49 0.00 21.49
August 707.67 21.47 0.00 21.47 0.00 21.47
September 706.67 21.40 0.00 21.40 0.00 21.40
October 744.00 21.02 54.50 20.95 54.50 20.89
November 720.00 20.75 353.33 20.64 353.33 20.58
December 744.00 20.55 677.50 20.53 677.50 20.52
             
Annual Sum or Average 8615.00 21.09 2279.17 20.96 2269.50 20.88
Minimum of Months 672.00 20.55 0.00 20.53 0.00 20.52
Maximum of Months 744.00 21.48 677.50 21.49 677.50 21.49



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.01 128.50 20.95 128.50 20.91
February 672.00 21.05 22.50 21.04 22.50 21.02
March 744.00 21.16 3.50 21.16 3.50 21.16
April 720.00 21.34 0.00 21.34 0.00 21.34
May 744.00 21.39 0.00 21.39 0.00 21.39
June 720.00 21.48 0.00 21.48 0.00 21.48
July 744.00 21.50 0.00 21.50 0.00 21.50
August 744.00 21.43 0.00 21.43 0.00 21.43
September 720.00 21.37 0.00 21.37 0.00 21.37
October 744.00 21.22 0.00 21.22 0.00 21.22
November 720.00 21.08 26.67 21.06 26.67 21.04
December 744.00 20.96 136.83 20.89 136.83 20.84
             
Annual Sum or Average 8760.00 21.25 318.00 21.23 318.00 21.20
Minimum of Months 672.00 20.96 0.00 20.89 0.00 20.84
Maximum of Months 744.00 21.50 136.83 21.50 136.83 21.50



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 20.87 355.00 20.77 355.00 20.72
February 672.00 21.00 233.00 20.90 233.00 20.85
March 744.00 20.98 194.67 20.91 194.67 20.86
April 697.00 21.56 6.50 21.55 6.50 21.55
May 715.00 21.52 0.00 21.52 0.00 21.52
June 655.67 21.49 0.33 21.49 0.00 21.49
July 652.17 21.46 1.67 21.47 0.00 21.47
August 628.67 21.39 0.17 21.39 0.00 21.39
September 640.83 21.47 0.00 21.47 0.00 21.47
October 744.00 21.26 29.67 21.21 29.67 21.17
November 720.00 20.92 226.50 20.81 226.50 20.74
December 744.00 20.70 560.17 20.64 560.17 20.62
             
Annual Sum or Average 8357.33 21.21 1607.67 21.10 1605.50 21.03
Minimum of Months 628.67 20.70 0.00 20.64 0.00 20.62
Maximum of Months 744.00 21.56 560.17 21.55 560.17 21.55



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 20.67 492.67 20.59 492.67 20.56
February 672.00 20.75 417.67 20.68 417.67 20.65
March 744.00 20.88 280.50 20.80 280.50 20.76
April 717.50 21.51 10.67 21.49 10.67 21.48
May 735.67 21.51 0.00 21.51 0.00 21.51
June 684.67 21.55 0.17 21.55 0.00 21.55
July 707.17 21.60 0.67 21.60 0.00 21.60
August 720.67 21.61 0.00 21.61 0.00 21.61
September 717.67 21.60 0.00 21.60 0.00 21.60
October 744.00 21.09 42.83 21.03 42.83 20.98
November 720.00 20.74 356.83 20.63 356.83 20.58
December 744.00 20.57 648.17 20.53 648.17 20.52
             
Annual Sum or Average 8651.33 21.17 2250.17 21.03 2249.33 20.94
Minimum of Months 672.00 20.57 0.00 20.53 0.00 20.52
Maximum of Months 744.00 21.61 648.17 21.61 648.17 21.61



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.00 96.67 21.00 96.67 21.00
February 672.00 21.00 0.00 21.00 0.00 21.00
March 744.00 21.00 0.00 21.00 0.00 21.00
April 720.00 21.03 0.00 21.03 0.00 21.03
May 744.00 21.02 0.00 21.02 0.00 21.02
June 720.00 21.06 0.00 21.06 0.00 21.06
July 744.00 21.12 0.00 21.12 0.00 21.12
August 744.00 21.11 0.00 21.11 0.00 21.11
September 720.00 21.09 0.00 21.09 0.00 21.09
October 744.00 21.01 0.00 21.01 0.00 21.01
November 720.00 21.00 7.17 21.00 7.17 21.00
December 744.00 21.00 58.00 21.00 58.00 21.00
             
Annual Sum or Average 8760.00 21.04 161.83 21.04 161.83 21.03
Minimum of Months 672.00 21.00 0.00 21.00 0.00 21.00
Maximum of Months 744.00 21.12 96.67 21.12 96.67 21.12



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 20.76 517.33 20.69 517.33 20.66
February 672.00 20.90 388.00 20.80 388.00 20.76
March 744.00 20.86 402.67 20.80 402.67 20.77
April 684.83 21.41 40.50 21.40 34.83 21.36
May 704.00 21.40 15.83 21.43 4.50 21.42
June 643.00 21.43 26.33 21.51 0.00 21.51
July 637.83 21.39 44.67 21.52 0.00 21.52
August 631.67 21.36 40.50 21.48 0.00 21.48
September 647.33 21.42 24.50 21.49 0.00 21.49
October 732.33 21.11 74.17 21.02 74.17 20.94
November 720.00 20.81 372.50 20.70 372.50 20.65
December 744.00 20.59 701.17 20.58 701.17 20.57
             
Annual Sum or Average 8305.00 21.11 2648.17 21.02 2495.17 20.94
Minimum of Months 631.67 20.59 15.83 20.58 0.00 20.57
Maximum of Months 744.00 21.43 701.17 21.52 701.17 21.52



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 20.58 639.67 20.54 639.67 20.53
February 672.00 20.66 559.83 20.62 559.83 20.60
March 744.00 20.75 502.17 20.69 502.17 20.67
April 708.00 21.32 56.50 21.28 56.33 21.24
May 723.67 21.36 10.67 21.37 6.00 21.37
June 666.50 21.46 14.00 21.50 0.00 21.50
July 667.33 21.44 23.33 21.51 0.00 21.51
August 682.00 21.45 8.17 21.48 0.00 21.48
September 695.50 21.40 1.00 21.40 0.00 21.40
October 744.00 20.95 143.00 20.82 143.00 20.74
November 720.00 20.63 492.33 20.54 492.33 20.51
December 744.00 20.49 740.67 20.49 740.67 20.49
             
Annual Sum or Average 8511.00 21.03 3191.33 20.90 3140.00 20.82
Minimum of Months 666.50 20.49 1.00 20.49 0.00 20.49
Maximum of Months 744.00 21.46 740.67 21.51 740.67 21.51



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 730.17 21.12 219.50 21.00 219.50 20.93
February 651.00 21.19 116.83 21.11 116.83 21.05
March 744.00 21.15 127.33 21.08 127.33 21.03
April 663.17 21.46 12.33 21.50 0.00 21.50
May 690.17 21.43 5.00 21.44 0.00 21.44
June 651.83 21.46 7.33 21.48 0.00 21.48
July 646.67 21.41 20.67 21.47 0.00 21.47
August 630.33 21.36 58.00 21.53 0.00 21.53
September 611.50 21.37 57.83 21.54 0.00 21.54
October 696.67 21.25 21.50 21.25 13.83 21.23
November 706.67 21.14 121.33 21.05 121.33 20.98
December 741.50 20.95 403.17 20.83 403.17 20.78
             
Annual Sum or Average 8163.67 21.27 1170.83 21.23 1002.00 21.17
Minimum of Months 611.50 20.95 5.00 20.83 0.00 20.78
Maximum of Months 744.00 21.46 403.17 21.54 403.17 21.54



Table of Contents

Report: ComfortReportSimple55Monthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.36 0.00 21.36 0.00 21.36
February 672.00 21.37 0.00 21.37 0.00 21.37
March 744.00 21.45 0.00 21.45 0.00 21.45
April 720.00 21.55 0.00 21.55 0.00 21.55
May 742.17 21.61 0.00 21.61 0.00 21.61
June 704.83 21.72 2.00 21.72 0.00 21.72
July 711.17 21.70 1.50 21.71 0.00 21.71
August 720.50 21.68 0.67 21.69 0.00 21.69
September 716.83 21.60 0.00 21.60 0.00 21.60
October 744.00 21.48 0.00 21.48 0.00 21.48
November 720.00 21.41 0.00 21.41 0.00 21.41
December 744.00 21.34 0.00 21.34 0.00 21.34
             
Annual Sum or Average 8683.50 21.52 4.17 21.52 0.00 21.52
Minimum of Months 672.00 21.34 0.00 21.34 0.00 21.34
Maximum of Months 744.00 21.72 2.00 21.72 0.00 21.72



Table of Contents

Report: ComfortReportSimple55Monthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.41 0.00 21.41 0.00 21.41
February 672.00 21.42 0.00 21.42 0.00 21.42
March 744.00 21.51 0.00 21.51 0.00 21.51
April 719.67 21.62 0.00 21.62 0.00 21.62
May 732.17 21.68 0.33 21.68 0.00 21.68
June 667.50 21.75 7.17 21.77 0.00 21.77
July 670.50 21.75 15.50 21.78 0.00 21.78
August 689.67 21.72 10.33 21.74 0.00 21.74
September 700.33 21.65 1.00 21.65 0.00 21.65
October 743.67 21.55 0.00 21.55 0.00 21.55
November 720.00 21.47 0.00 21.47 0.00 21.47
December 744.00 21.39 0.00 21.39 0.00 21.39
             
Annual Sum or Average 8547.50 21.57 34.33 21.58 0.00 21.58
Minimum of Months 667.50 21.39 0.00 21.39 0.00 21.39
Maximum of Months 744.00 21.75 15.50 21.78 0.00 21.78



Table of Contents

Report: ComfortReportSimple55Monthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 512.67 22.65 526.83 22.96 322.33 23.11
February 499.00 22.73 479.50 23.02 327.50 23.17
March 552.00 22.77 532.83 23.06 367.50 23.21
April 597.67 23.05 528.17 23.32 429.50 23.46
May 624.83 23.08 557.83 23.33 460.67 23.47
June 606.50 23.21 552.17 23.41 471.00 23.54
July 622.83 23.28 576.00 23.46 496.50 23.57
August 626.00 23.26 573.83 23.45 493.83 23.57
September 603.67 23.17 545.17 23.39 458.33 23.52
October 588.83 22.91 546.00 23.17 416.17 23.31
November 521.83 22.73 519.17 23.01 345.00 23.15
December 482.67 22.56 525.83 22.88 288.83 23.04
             
Annual Sum or Average 6838.50 22.97 6463.33 23.22 4877.17 23.36
Minimum of Months 482.67 22.56 479.50 22.88 288.83 23.04
Maximum of Months 626.00 23.28 576.00 23.46 496.50 23.57



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.00 193.17 21.00 193.17 21.00
February 672.00 21.00 76.67 21.00 76.67 21.00
March 744.00 21.00 44.00 21.00 44.00 21.00
April 720.00 21.02 3.67 21.02 3.67 21.02
May 744.00 21.01 0.00 21.01 0.00 21.01
June 720.00 21.03 0.00 21.03 0.00 21.03
July 744.00 21.04 0.00 21.04 0.00 21.04
August 744.00 21.04 0.00 21.04 0.00 21.04
September 720.00 21.03 0.00 21.03 0.00 21.03
October 744.00 21.00 0.00 21.00 0.00 21.00
November 720.00 21.00 54.67 21.00 54.67 21.00
December 744.00 21.00 205.83 21.00 205.83 21.00
             
Annual Sum or Average 8760.00 21.02 578.00 21.01 578.00 21.01
Minimum of Months 672.00 21.00 0.00 21.00 0.00 21.00
Maximum of Months 744.00 21.04 205.83 21.04 205.83 21.04



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: BASEMENT PEOPLE

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.06172 34.07310 -0.4120 8.59739
February 672.00000 21.05059 35.03809 -0.4131 8.59128
March 744.00000 21.03937 34.84797 -0.4211 8.73797
April 720.00000 21.02970 35.38859 -0.4209 8.76435
May 744.00000 21.02976 42.13857 -1.5781 55.15026
June 720.00000 21.03222 51.23411 -1.5201 52.00054
July 744.00000 21.03984 53.54081 -1.4968 50.73775
August 744.00000 21.04930 53.83779 -1.4885 50.28921
September 720.00000 21.07289 49.53367 -1.4964 50.74195
October 744.00000 21.09219 43.56982 -0.3394 7.45921
November 720.00000 21.10516 38.66087 -0.3641 7.83604
December 744.00000 21.08661 33.36295 -0.4034 8.44107
           
Annual Sum or Average 8760.00000 21.05747 42.14270 -0.8656 26.55518
Minimum of Months 672.00000 21.02970 33.36295 -1.5781 7.45921
Maximum of Months 744.00000 21.10516 53.83779 -0.3394 55.15026



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: RETAIL_1_FLR_1 PEOPLE

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 20.94744 33.26064 -0.4997 10.60634
February 672.00000 20.98582 34.16560 -0.4620 9.84374
March 744.00000 20.98715 33.93491 -0.4801 9.96819
April 720.00000 21.03777 34.41338 -0.3482 8.06043
May 744.00000 21.00934 41.22413 -1.4924 50.64538
June 720.00000 21.00618 50.36561 -1.3990 45.66606
July 744.00000 21.01787 52.67676 -1.3529 43.33066
August 744.00000 21.05640 52.88425 -1.3186 41.78949
September 720.00000 21.11526 48.45245 -1.3362 43.15693
October 744.00000 21.03479 42.75916 -0.3539 8.02327
November 720.00000 20.98331 37.93257 -0.4556 9.58927
December 744.00000 20.87553 32.73684 -0.5605 11.85565
           
Annual Sum or Average 8760.00000 21.00456 41.27489 -0.8408 24.47286
Minimum of Months 672.00000 20.87553 32.73684 -1.4924 8.02327
Maximum of Months 744.00000 21.11526 52.88425 -0.3482 50.64538



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: RETAIL_2_FLR_1 PEOPLE

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.00387 34.53269 -0.4167 8.67766
February 672.00000 21.00559 35.48092 -0.4059 8.46029
March 744.00000 21.00854 35.26643 -0.4051 8.45998
April 720.00000 21.04426 35.74405 -0.3662 7.88958
May 744.00000 21.04993 42.47780 -1.4981 50.82013
June 720.00000 21.07541 51.51056 -1.4215 46.70987
July 744.00000 21.08770 53.79819 -1.3978 45.46131
August 744.00000 21.08760 54.13931 -1.3940 45.23961
September 720.00000 21.06753 49.93909 -1.4323 47.31149
October 744.00000 21.02187 44.12297 -0.3361 7.39210
November 720.00000 21.00621 39.24371 -0.3845 8.13238
December 744.00000 21.00118 33.86816 -0.4318 8.91898
           
Annual Sum or Average 8760.00000 21.03847 42.55058 -0.8268 24.55411
Minimum of Months 672.00000 21.00118 33.86816 -1.4981 7.39210
Maximum of Months 744.00000 21.08770 54.13931 -0.3361 50.82013



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: LAUNDRY_FLR_1 PEOPLE

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.43420 31.55631 0.27266 9.18529
February 672.00000 21.43427 32.48547 0.28143 9.28571
March 744.00000 21.43732 32.23004 0.28969 9.46975
April 720.00000 21.40472 32.82967 0.31337 9.68061
May 744.00000 21.40667 39.43772 -0.5271 16.05351
June 720.00000 21.39815 48.38503 -0.4565 14.52854
July 744.00000 21.37959 50.72411 -0.4435 14.02266
August 744.00000 21.40155 50.99642 -0.4299 14.01144
September 720.00000 21.40791 46.78269 -0.4680 14.79203
October 744.00000 21.42405 40.95051 0.34947 10.16267
November 720.00000 21.43461 36.11698 0.30686 9.65776
December 744.00000 21.43267 30.89376 0.26087 9.03669
           
Annual Sum or Average 8760.00000 21.41621 39.48898 -0.0228 11.67115
Minimum of Months 672.00000 21.37959 30.89376 -0.5271 9.03669
Maximum of Months 744.00000 21.43732 50.99642 0.34947 16.05351



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CAFE_FLR_1 PEOPLE

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.00226 35.59898 -0.3839 8.34854
February 672.00000 21.01268 36.53295 -0.3529 7.88887
March 744.00000 21.00257 36.33592 -0.3738 8.01717
April 720.00000 21.02281 36.85842 -0.2562 6.78401
May 744.00000 21.00427 43.64910 -1.3688 44.09335
June 720.00000 21.00367 52.76286 -1.2820 39.58763
July 744.00000 21.00658 55.09147 -1.2397 37.53095
August 744.00000 21.02482 55.37202 -1.2086 36.16853
September 720.00000 21.07274 50.96153 -1.2235 37.33907
October 744.00000 21.02395 45.17744 -0.2565 6.68858
November 720.00000 21.00297 40.31504 -0.3476 7.71946
December 744.00000 20.99110 34.93896 -0.4303 9.04312
           
Annual Sum or Average 8760.00000 21.01409 43.67380 -0.7295 20.85039
Minimum of Months 672.00000 20.99110 34.93896 -1.3688 6.68858
Maximum of Months 744.00000 21.07274 55.37202 -0.2562 44.09335



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: LOBBY_FLR_1 PEOPLE

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.01207 35.83835 -0.3760 8.01452
February 672.00000 21.01470 36.78126 -0.3630 7.78037
March 744.00000 21.01902 36.57010 -0.3650 7.81860
April 720.00000 21.05333 37.04941 -0.3172 7.18985
May 744.00000 21.06013 43.77446 -1.4362 47.48952
June 720.00000 21.09448 52.76736 -1.3561 43.24841
July 744.00000 21.11262 55.02992 -1.3275 41.76874
August 744.00000 21.12233 55.35222 -1.3164 41.17691
September 720.00000 21.09788 51.16502 -1.3531 43.12634
October 744.00000 21.03652 45.39680 -0.2885 6.77902
November 720.00000 21.01732 40.53865 -0.3425 7.50365
December 744.00000 21.00763 35.16768 -0.3942 8.27822
           
Annual Sum or Average 8760.00000 21.05420 43.82604 -0.7722 22.60545
Minimum of Months 672.00000 21.00763 35.16768 -1.4362 6.77902
Maximum of Months 744.00000 21.12233 55.35222 -0.2885 47.48952



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_1_FLR_3 PEOPLE

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 20.87506 40.81248 -0.5329 11.46644
February 672.00000 21.01099 41.44099 -0.4753 10.26135
March 744.00000 20.95427 41.42983 -0.4872 10.20430
April 720.00000 21.50820 40.58007 -0.2531 7.32898
May 744.00000 21.49860 46.47286 -1.3494 43.89040
June 720.00000 21.61267 52.50327 -1.2220 37.72054
July 744.00000 21.64289 53.22628 -1.1835 36.00391
August 744.00000 21.64837 53.78535 -1.1831 36.00931
September 720.00000 21.60391 51.62791 -1.2502 39.22223
October 744.00000 21.21730 49.35431 -0.3343 7.97714
November 720.00000 20.92692 45.39799 -0.4848 10.33597
December 744.00000 20.68403 40.78735 -0.6107 13.24588
           
Annual Sum or Average 8760.00000 21.26574 46.48095 -0.7828 22.05005
Minimum of Months 672.00000 20.68403 40.58007 -1.3494 7.32898
Maximum of Months 744.00000 21.64837 53.78535 -0.2531 43.89040



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_2_FLR_3 PEOPLE

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 20.67223 41.26322 -0.6036 13.09608
February 672.00000 20.77563 41.95598 -0.5560 11.77175
March 744.00000 20.85170 41.65131 -0.5227 10.92923
April 720.00000 21.33755 40.95298 -0.3211 7.80124
May 744.00000 21.39729 46.76085 -1.4053 46.45541
June 720.00000 21.55959 52.76562 -1.2547 39.04028
July 744.00000 21.59245 53.65333 -1.2199 37.42763
August 744.00000 21.56321 54.70448 -1.2453 38.52813
September 720.00000 21.43880 52.76345 -1.3553 43.85103
October 744.00000 21.02274 49.86560 -0.4059 8.72640
November 720.00000 20.74531 45.82413 -0.5460 11.57758
December 744.00000 20.55341 41.09066 -0.6548 14.46464
           
Annual Sum or Average 8760.00000 21.12712 46.96610 -0.8429 23.71552
Minimum of Months 672.00000 20.55341 40.95298 -1.4053 7.80124
Maximum of Months 744.00000 21.59245 54.70448 -0.3211 46.45541



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_3_MULT19_FLR_3 PEOPLE

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 0.00000 0.00000 0.00000 0.00000 0.00000
February 0.00000 0.00000 0.00000 0.00000 0.00000
March 0.00000 0.00000 0.00000 0.00000 0.00000
April 0.00000 0.00000 0.00000 0.00000 0.00000
May 0.00000 0.00000 0.00000 0.00000 0.00000
June 0.00000 0.00000 0.00000 0.00000 0.00000
July 0.00000 0.00000 0.00000 0.00000 0.00000
August 0.00000 0.00000 0.00000 0.00000 0.00000
September 0.00000 0.00000 0.00000 0.00000 0.00000
October 0.00000 0.00000 0.00000 0.00000 0.00000
November 0.00000 0.00000 0.00000 0.00000 0.00000
December 0.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 0.00000        
Minimum of Months 0.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 0.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_4_MULT19_FLR_3 PEOPLE

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.00956 39.31170 -0.4619 9.65603
February 672.00000 21.05401 40.12306 -0.4408 9.10551
March 744.00000 21.16173 39.62454 -0.3987 8.37612
April 720.00000 21.33921 39.55758 -0.3310 7.44380
May 744.00000 21.38537 45.17421 -1.4376 47.64479
June 720.00000 21.48207 50.81475 -1.3429 42.80827
July 744.00000 21.49859 52.01907 -1.3229 41.80110
August 744.00000 21.43253 52.60316 -1.3520 43.20893
September 720.00000 21.37362 50.52211 -1.4091 46.14980
October 744.00000 21.22032 47.47956 -0.3299 7.32110
November 720.00000 21.07968 43.61617 -0.4077 8.56676
December 744.00000 20.96175 39.02221 -0.4840 10.00934
           
Annual Sum or Average 8760.00000 21.25073 45.01653 -0.8122 23.59603
Minimum of Months 672.00000 20.96175 39.02221 -1.4376 7.32110
Maximum of Months 744.00000 21.49859 52.60316 -0.3299 47.64479



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_5_FLR_3 PEOPLE

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 20.87037 40.81662 -0.5329 11.44515
February 672.00000 20.99907 41.44969 -0.4829 10.28111
March 744.00000 20.98233 41.36536 -0.4814 10.10279
April 720.00000 21.61740 40.41145 -0.2162 7.11036
May 744.00000 21.59056 46.10919 -1.3166 42.37519
June 720.00000 21.65726 52.19323 -1.2161 37.50461
July 744.00000 21.69381 52.91346 -1.1733 35.56916
August 744.00000 21.68702 53.19258 -1.1643 35.24976
September 720.00000 21.67191 51.12898 -1.2123 37.53903
October 744.00000 21.25815 49.20262 -0.3223 7.88274
November 720.00000 20.92094 45.40903 -0.4854 10.29723
December 744.00000 20.70049 40.74256 -0.6018 13.02677
           
Annual Sum or Average 8760.00000 21.30483 46.27256 -0.7693 21.60714
Minimum of Months 672.00000 20.70049 40.41145 -1.3166 7.11036
Maximum of Months 744.00000 21.69381 53.19258 -0.2162 42.37519



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_6_FLR_3 PEOPLE

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 20.67198 41.25779 -0.6026 13.06797
February 672.00000 20.75218 41.98671 -0.5666 11.98943
March 744.00000 20.88260 41.57097 -0.5163 10.77905
April 720.00000 21.51236 40.59478 -0.2708 7.34770
May 744.00000 21.53444 46.29177 -1.3602 44.26604
June 720.00000 21.63336 52.39523 -1.2409 38.48016
July 744.00000 21.68110 53.26974 -1.1994 36.56151
August 744.00000 21.66612 53.91025 -1.2078 36.97149
September 720.00000 21.60951 51.85778 -1.2880 40.70514
October 744.00000 21.08904 49.67394 -0.3883 8.46882
November 720.00000 20.73821 45.83581 -0.5468 11.58136
December 744.00000 20.56938 41.04455 -0.6461 14.23085
           
Annual Sum or Average 8760.00000 21.19671 46.66774 -0.8214 22.94206
Minimum of Months 672.00000 20.56938 40.59478 -1.3602 7.34770
Maximum of Months 744.00000 21.68110 53.91025 -0.2708 44.26604



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_1_FLR_6 PEOPLE

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 20.76333 41.55657 -0.5974 13.11880
February 672.00000 20.90290 42.17155 -0.5337 11.64028
March 744.00000 20.86332 42.16738 -0.5377 11.39414
April 720.00000 21.50528 41.01994 -0.2578 7.71498
May 744.00000 21.50094 46.95529 -1.3500 44.23786
June 720.00000 21.62907 52.77685 -1.2024 37.17246
July 744.00000 21.65867 53.41533 -1.1583 35.22282
August 744.00000 21.65702 54.02167 -1.1635 35.47960
September 720.00000 21.60675 52.15922 -1.2480 39.46430
October 744.00000 21.14843 50.28613 -0.3708 8.72508
November 720.00000 20.81402 46.29576 -0.5437 11.73432
December 744.00000 20.59232 41.47143 -0.6737 15.03029
           
Annual Sum or Average 8760.00000 21.22093 47.05328 -0.8052 22.65199
Minimum of Months 672.00000 20.59232 41.01994 -1.3500 7.71498
Maximum of Months 744.00000 21.65867 54.02167 -0.2578 44.23786



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_2_FLR_6 PEOPLE

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 20.57895 42.00170 -0.6658 14.85383
February 672.00000 20.65950 42.72806 -0.6180 13.41404
March 744.00000 20.75407 42.41441 -0.5753 12.24593
April 720.00000 21.35297 41.37085 -0.3251 8.15350
May 744.00000 21.41759 47.22439 -1.4032 46.61602
June 720.00000 21.59896 53.00514 -1.2298 38.22438
July 744.00000 21.63341 53.82437 -1.1887 36.34471
August 744.00000 21.61009 54.88897 -1.2172 37.57154
September 720.00000 21.46693 53.33250 -1.3503 43.85934
October 744.00000 20.94642 50.83937 -0.4468 9.61086
November 720.00000 20.62988 46.74893 -0.6066 13.17670
December 744.00000 20.49329 41.71939 -0.7127 16.21330
           
Annual Sum or Average 8760.00000 21.09692 47.53534 -0.8635 24.26069
Minimum of Months 672.00000 20.49329 41.37085 -1.4032 8.15350
Maximum of Months 744.00000 21.63341 54.88897 -0.3251 46.61602



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_3_MULT9_FLR_6 PEOPLE

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.15767 41.11465 -0.4310 9.98590
February 672.00000 21.25519 41.76864 -0.3853 9.09767
March 744.00000 21.15053 41.74637 -0.4300 9.29721
April 720.00000 21.60942 41.16497 -0.2093 7.27475
May 744.00000 21.56707 46.83909 -1.3355 43.48957
June 720.00000 21.63666 52.52755 -1.2385 38.71588
July 744.00000 21.66428 53.06111 -1.1946 36.76081
August 744.00000 21.66426 52.85606 -1.1701 35.83448
September 720.00000 21.66480 50.59927 -1.1901 37.01282
October 744.00000 21.38310 49.28881 -0.2638 7.52870
November 720.00000 21.17584 45.53933 -0.3961 9.11384
December 744.00000 20.95447 41.08121 -0.5231 11.58945
           
Annual Sum or Average 8760.00000 21.40693 46.49332 -0.7332 21.38993
Minimum of Months 672.00000 20.95447 41.08121 -1.3355 7.27475
Maximum of Months 744.00000 21.66480 53.06111 -0.2093 43.48957



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: BANQUET_FLR_6 PEOPLE

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.35818 36.75836 -0.2509 6.61145
February 672.00000 21.37042 37.66685 -0.2347 6.37891
March 744.00000 21.44943 37.34007 -0.2009 6.10449
April 720.00000 21.54937 37.68318 -0.1391 5.70167
May 744.00000 21.61700 44.08814 -1.1533 33.42186
June 720.00000 21.74341 52.56755 -1.0283 27.82021
July 744.00000 21.76189 54.72652 -0.9995 26.63157
August 744.00000 21.72538 55.19160 -1.0188 27.38062
September 720.00000 21.60777 51.37300 -1.1103 31.44502
October 744.00000 21.48388 45.89658 -0.1302 5.62886
November 720.00000 21.41483 41.24827 -0.1970 6.14183
December 744.00000 21.34277 36.10714 -0.2648 6.70359
           
Annual Sum or Average 8760.00000 21.53624 44.25806 -0.5627 15.88720
Minimum of Months 672.00000 21.34277 36.10714 -1.1533 5.62886
Maximum of Months 744.00000 21.76189 55.19160 -0.1302 33.42186



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: DINING_FLR_6 PEOPLE

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.40965 36.42933 -0.2056 6.21621
February 672.00000 21.42479 37.33252 -0.1891 6.00812
March 744.00000 21.51249 36.98831 -0.1529 5.78523
April 720.00000 21.62513 37.30507 -0.0892 5.49325
May 744.00000 21.70044 43.66285 -1.0797 30.10541
June 720.00000 21.83972 52.06331 -0.9503 24.64042
July 744.00000 21.86358 54.19345 -0.9202 23.47109
August 744.00000 21.81469 54.69249 -0.9438 24.33742
September 720.00000 21.68299 50.93413 -1.0402 28.37295
October 744.00000 21.54801 45.51296 -0.0827 5.44939
November 720.00000 21.47329 40.89006 -0.1503 5.84060
December 744.00000 21.39201 35.78613 -0.2196 6.28156
           
Annual Sum or Average 8760.00000 21.60820 43.85293 -0.5039 14.38268
Minimum of Months 672.00000 21.39201 35.78613 -1.0797 5.44939
Maximum of Months 744.00000 21.86358 54.69249 -0.0827 30.10541



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: KITCHEN_FLR_6 PEOPLE

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 22.63522 35.66377 0.69013 19.85393
February 672.00000 22.68392 36.39242 0.71594 20.80587
March 744.00000 22.72352 36.09627 0.73939 21.50267
April 720.00000 22.94917 36.16667 0.86410 26.64564
May 744.00000 22.96738 42.01299 0.24604 18.12934
June 720.00000 23.02794 49.72593 0.35566 19.64257
July 744.00000 23.05301 51.71168 0.39447 20.31558
August 744.00000 23.04962 51.97355 0.39265 20.35542
September 720.00000 23.00191 48.35886 0.31912 19.29420
October 744.00000 22.80984 43.71574 0.83269 24.81409
November 720.00000 22.67425 39.76378 0.73680 21.21853
December 744.00000 22.57215 35.21186 0.65614 18.57992
           
Annual Sum or Average 8760.00000 22.84625 42.26687 0.57757 20.92239
Minimum of Months 672.00000 22.57215 35.21186 0.24604 18.12934
Maximum of Months 744.00000 23.05301 51.97355 0.86410 26.64564



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: STORAGE_FLR_1 PEOPLE

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.00005 32.90425 -0.4893 10.05886
February 672.00000 21.00013 33.85261 -0.4810 9.85312
March 744.00000 21.00014 33.66118 -0.4746 9.73253
April 720.00000 21.00014 34.20332 -0.4548 9.37515
May 744.00000 21.00011 40.98647 -1.6170 57.26274
June 720.00000 21.00056 50.16412 -1.5447 53.33585
July 744.00000 21.00101 52.51565 -1.5246 52.24161
August 744.00000 21.00017 52.83877 -1.5244 52.23000
September 720.00000 21.00012 48.58044 -1.5607 54.22690
October 744.00000 21.00013 42.58591 -0.4130 8.58758
November 720.00000 21.00015 37.63356 -0.4543 9.35478
December 744.00000 21.00014 32.25129 -0.4981 10.20822
           
Annual Sum or Average 8760.00000 21.00024 41.05580 -0.9224 28.14969
Minimum of Months 672.00000 21.00005 32.25129 -1.6170 8.58758
Maximum of Months 744.00000 21.00101 52.83877 -0.4130 57.26274



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORRIDOR_FLR_3 PEOPLE

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.00043 35.14460 -0.4751 9.76278
February 672.00000 21.00042 36.08490 -0.4639 9.51005
March 744.00000 21.00039 35.90523 -0.4636 9.51277
April 720.00000 21.02518 36.35149 -0.4292 8.90837
May 744.00000 21.02387 43.12250 -1.5903 55.81666
June 720.00000 21.05758 52.15483 -1.5158 51.76790
July 744.00000 21.11695 54.30057 -1.4786 49.76482
August 744.00000 21.11076 54.65412 -1.4774 49.68733
September 720.00000 21.08722 50.49297 -1.5139 51.69078
October 744.00000 21.00620 44.76398 -0.3980 8.32612
November 720.00000 21.00041 39.85830 -0.4441 9.15485
December 744.00000 21.00036 34.48260 -0.4906 10.05003
           
Annual Sum or Average 8760.00000 21.03603 43.14983 -0.8977 27.10267
Minimum of Months 672.00000 21.00036 34.48260 -1.5903 8.32612
Maximum of Months 744.00000 21.11695 54.65412 -0.3980 55.81666



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORRIDOR_FLR_6 PEOPLE

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 20.99985 33.46733 -0.4981 10.26713
February 672.00000 21.00039 34.42074 -0.4816 9.88696
March 744.00000 21.00046 34.20632 -0.4744 9.74302
April 720.00000 21.02039 34.71318 -0.4180 8.77681
May 744.00000 21.01431 41.48071 -1.5668 54.54660
June 720.00000 21.02681 50.57217 -1.4807 49.89237
July 744.00000 21.04221 52.86505 -1.4501 48.25386
August 744.00000 21.04350 53.18602 -1.4500 48.25008
September 720.00000 21.02886 48.97529 -1.5015 51.04025
October 744.00000 21.00210 43.10237 -0.4008 8.39882
November 720.00000 21.00046 38.18268 -0.4582 9.44320
December 744.00000 21.00041 32.80499 -0.5152 10.58448
           
Annual Sum or Average 8760.00000 21.01505 41.53857 -0.8938 26.69254
Minimum of Months 672.00000 20.99985 32.80499 -1.5668 8.39882
Maximum of Months 744.00000 21.04350 53.18602 -0.4008 54.54660



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: MECH_FLR_1 PEOPLE

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.00007 32.63399 -0.4658 9.58517
February 672.00000 21.00009 33.58532 -0.4584 9.40776
March 744.00000 21.00008 33.38531 -0.4522 9.30055
April 720.00000 21.00283 33.92679 -0.4339 8.99223
May 744.00000 21.00600 40.69518 -1.5861 55.58815
June 720.00000 21.02178 49.81623 -1.5104 51.47285
July 744.00000 21.02946 52.14013 -1.4889 50.30888
August 744.00000 21.02782 52.46850 -1.4887 50.29851
September 720.00000 21.01246 48.25831 -1.5287 52.49046
October 744.00000 21.00015 42.30910 -0.3920 8.23621
November 720.00000 21.00008 37.36069 -0.4319 8.94014
December 744.00000 21.00009 31.98105 -0.4740 9.71586
           
Annual Sum or Average 8760.00000 21.00847 40.75414 -0.8952 27.13513
Minimum of Months 672.00000 21.00007 31.98105 -1.5861 8.23621
Maximum of Months 744.00000 21.02946 52.46850 -0.3920 55.58815



Table of Contents

Report: ChillerReportMonthly

For: COOLSYS1 CHILLER1

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

CHILLER ELECTRICITY ENERGY [J] CHILLER ELECTRICITY RATE {Maximum} [W] CHILLER ELECTRICITY RATE {TIMESTAMP} CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] CHILLER EVAPORATOR COOLING ENERGY [J] CHILLER EVAPORATOR COOLING RATE [] CHILLER CONDENSER HEAT TRANSFER ENERGY [J] CHILLER COP [W/W] CHILLER COP {Maximum} [W/W] CHILLER COP {TIMESTAMP} CHILLER PART LOAD RATIO [] CHILLER PART LOAD RATIO []
January 0.500455E+10 22472.13 21-JAN-16:03 302.57 0.147503E+11 0.00 0.197549E+11 1.20 2.95 06-JAN-09:05 0.00 0.00
February 0.529441E+10 24598.20 09-FEB-16:03 300.46 0.156053E+11 0.00 0.208997E+11 1.32 2.95 24-FEB-20:10 0.00 0.00
March 0.573984E+10 22422.81 20-MAR-18:02 376.63 0.169176E+11 0.00 0.226575E+11 1.49 2.95 08-MAR-19:05 0.00 0.00
April 0.367272E+11 127841.47 30-APR-18:03 671.21 0.115117E+12 0.00 0.151844E+12 2.78 4.03 29-APR-18:03 0.00 0.00
May 0.392408E+11 125940.75 22-MAY-15:03 699.39 0.121657E+12 0.00 0.160897E+12 2.80 4.07 22-MAY-18:03 0.00 0.00
June 0.704460E+11 169427.10 25-JUN-18:20 715.56 0.227250E+12 0.00 0.297696E+12 3.01 4.35 26-JUN-18:03 0.00 0.00
July 0.999313E+11 175531.77 22-JUL-18:03 743.90 0.328192E+12 0.00 0.428123E+12 3.09 4.26 17-JUL-18:02 0.00 0.00
August 0.109496E+12 147665.75 14-AUG-18:03 744.00 0.364008E+12 0.00 0.473504E+12 3.14 4.25 16-AUG-18:02 0.00 0.00
September 0.745081E+11 125674.75 13-SEP-15:03 715.58 0.242529E+12 0.00 0.317037E+12 3.03 4.23 10-SEP-18:02 0.00 0.00
October 0.201605E+11 89495.33 07-OCT-15:02 586.22 0.596110E+11 0.00 0.797714E+11 2.32 4.00 07-OCT-15:02 0.00 0.00
November 0.575846E+10 26968.99 24-NOV-11:50 364.17 0.169634E+11 0.00 0.227219E+11 1.49 2.95 01-NOV-00:50 0.00 0.00
December 0.173023E+10 9283.98 25-DEC-09:02 182.68 0.509986E+10 0.00 0.683010E+10 0.72 2.95 01-DEC-08:00 0.00 0.00
                         
Annual Sum or Average 0.474038E+12     6402.38 0.152770E+13 0.00 0.200174E+13 2.20     0.00 0.00
Minimum of Months 0.173023E+10 9283.98   182.68 0.509986E+10 0.00 0.683010E+10 0.72 2.95   0.00 0.00
Maximum of Months 0.109496E+12 175531.77   744.00 0.364008E+12 0.00 0.473504E+12 3.14 4.35   0.00 0.00



Table of Contents

Report: BoilerReportMonthly

For: HEATSYS1 BOILER

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

BOILER HEATING ENERGY [J] BOILER GAS CONSUMPTION [] BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] BOILER HEATING RATE {Maximum} [W] BOILER HEATING RATE {TIMESTAMP} BOILER GAS CONSUMPTION RATE [] BOILER INLET TEMPERATURE [C] BOILER OUTLET TEMPERATURE [C] BOILER MASS FLOW RATE [kg/s] BOILER ANCILLARY ELECTRICITY RATE [W] BOILER PART LOAD RATIO [] BOILER PART LOAD RATIO {Maximum} [] BOILER PART LOAD RATIO {TIMESTAMP}
January 0.141449E+12 0.00 744.00 181124.91 10-JAN-09:02 0.00 38.08 60.00 0.58 0.00 0.12 0.40 10-JAN-09:02
February 0.113410E+12 0.00 672.00 124686.34 13-FEB-09:02 0.00 36.99 60.00 0.50 0.00 0.10 0.28 13-FEB-09:02
March 0.119703E+12 0.00 744.00 115676.90 04-MAR-16:02 0.00 37.24 60.00 0.47 0.00 0.10 0.26 04-MAR-16:02
April 0.766344E+11 0.00 720.00 86853.70 11-APR-10:35 0.00 34.26 60.00 0.28 0.00 0.07 0.19 11-APR-10:35
May 0.780615E+11 0.00 744.00 90019.11 05-MAY-10:35 0.00 32.43 60.00 0.26 0.00 0.06 0.20 05-MAY-10:35
June 0.644120E+11 0.00 720.00 88889.83 06-JUN-10:35 0.00 31.19 60.00 0.22 0.00 0.06 0.20 06-JUN-10:35
July 0.603656E+11 0.00 744.00 88642.58 03-JUL-10:35 0.00 30.74 60.00 0.19 0.00 0.05 0.20 03-JUL-10:35
August 0.561626E+11 0.00 744.00 84660.74 01-AUG-10:35 0.00 30.57 60.00 0.18 0.00 0.05 0.19 01-AUG-10:35
September 0.566126E+11 0.00 720.00 86469.58 08-SEP-10:40 0.00 30.97 60.00 0.19 0.00 0.05 0.19 08-SEP-10:40
October 0.902955E+11 0.00 744.00 102972.85 19-OCT-08:03 0.00 34.37 60.00 0.33 0.00 0.07 0.23 19-OCT-08:03
November 0.114621E+12 0.00 720.00 119859.29 29-NOV-09:02 0.00 36.73 60.00 0.46 0.00 0.10 0.27 29-NOV-09:02
December 0.151264E+12 0.00 744.00 147074.25 27-DEC-09:03 0.00 38.25 60.00 0.63 0.00 0.13 0.33 27-DEC-09:03
                           
Annual Sum or Average 0.112299E+13 0.00 8760.00     0.00 34.31 60.00 0.36 0.00 0.08    
Minimum of Months 0.561626E+11 0.00 672.00 84660.74   0.00 30.57 60.00 0.18 0.00 0.05 0.19  
Maximum of Months 0.151264E+12 0.00 744.00 181124.91   0.00 38.25 60.00 0.63 0.00 0.13 0.40  



Table of Contents

Report: DXReportMonthly

For: VAV WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 6818783.35 0.00 0.50 6818783.35 0.00 0.00 0.00 0.00 6819.07 29-JAN-06:00 6819.07 29-JAN-06:00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 0.00 01-FEB-00:03 0.00 0.00 0.00
March 4067563.16 0.00 0.82 4067563.16 0.00 0.00 0.00 0.00 6762.51 25-MAR-13:00 6762.51 25-MAR-13:00 0.00 0.00 0.00
April 0.309439E+11 0.00 85.41 0.308306E+11 0.00 0.00 0.00 0.00 279294.24 30-APR-18:10 279294.24 30-APR-18:10 0.00 0.00 0.00
May 0.333113E+11 0.00 105.02 0.333113E+11 0.00 0.00 0.00 0.00 257668.21 22-MAY-15:30 257668.21 22-MAY-15:30 0.00 0.00 0.00
June 0.103271E+12 0.00 300.66 0.969350E+11 0.00 0.00 0.00 0.00 487407.05 25-JUN-18:17 305733.29 12-JUN-18:10 0.00 0.00 0.00
July 0.177173E+12 0.00 457.83 0.169732E+12 0.00 0.00 0.00 0.00 380312.18 22-JUL-10:35 343556.89 22-JUL-18:10 0.00 0.00 0.00
August 0.210060E+12 0.00 531.92 0.201853E+12 0.00 0.00 0.00 0.00 349922.15 14-AUG-10:35 322923.68 14-AUG-17:08 0.00 0.00 0.00
September 0.113591E+12 0.00 339.67 0.110409E+12 0.00 0.00 0.00 0.00 293907.01 10-SEP-16:00 260576.17 11-SEP-17:13 0.00 0.00 0.00
October 0.809054E+10 0.00 55.97 0.809054E+10 0.00 0.00 0.00 0.00 149490.71 07-OCT-15:20 149490.71 07-OCT-15:20 0.00 0.00 0.00
November 0.223888E+09 0.00 2.50 0.223888E+09 0.00 0.00 0.00 0.00 68230.25 24-NOV-11:50 68230.25 24-NOV-11:50 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 0.00 01-DEC-00:03 0.00 0.00 0.00
                               
Annual Sum or Average 0.676676E+12 0.00 1880.29 0.651396E+12 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00   0.00   0.00 0.00 0.00
Maximum of Months 0.210060E+12 0.00 531.92 0.201853E+12 0.00 0.00 0.00 0.00 487407.05   343556.89   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: FLR_3_DOAS COOLING COIL

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 0.00 01-JAN-00:05 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 0.00 01-FEB-00:03 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-MAR-00:03 0.00 01-MAR-00:03 0.00 0.00 0.00
April 0.246108E+10 0.00 59.17 0.245921E+10 0.00 0.00 0.00 0.00 28621.53 30-APR-18:02 28621.53 30-APR-18:02 0.00 0.00 0.00
May 0.246348E+10 0.00 71.33 0.246348E+10 0.00 0.00 0.00 0.00 28400.77 22-MAY-15:00 28400.77 22-MAY-15:00 0.00 0.00 0.00
June 0.833263E+10 0.00 198.50 0.762647E+10 0.00 0.00 0.00 0.00 45838.53 25-JUN-18:00 30131.67 13-JUN-15:02 0.00 0.00 0.00
July 0.147069E+11 0.00 353.83 0.139146E+11 0.00 0.00 0.00 0.00 34524.85 23-JUL-16:00 31124.00 22-JUL-15:00 0.00 0.00 0.00
August 0.178711E+11 0.00 428.83 0.169080E+11 0.00 0.00 0.00 0.00 34502.27 17-AUG-15:00 29172.51 14-AUG-15:02 0.00 0.00 0.00
September 0.919189E+10 0.00 248.83 0.876880E+10 0.00 0.00 0.00 0.00 32609.72 12-SEP-14:00 27620.04 13-SEP-15:02 0.00 0.00 0.00
October 0.434540E+09 0.00 26.50 0.434540E+09 0.00 0.00 0.00 0.00 15105.80 07-OCT-15:00 15105.80 07-OCT-15:00 0.00 0.00 0.00
November 6967953.45 0.00 1.17 6967953.45 0.00 0.00 0.00 0.00 4049.57 24-NOV-12:00 4049.57 24-NOV-12:00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 0.00 01-DEC-00:03 0.00 0.00 0.00
                               
Annual Sum or Average 0.554687E+11 0.00 1388.17 0.525820E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00   0.00   0.00 0.00 0.00
Maximum of Months 0.178711E+11 0.00 428.83 0.169080E+11 0.00 0.00 0.00 0.00 45838.53   31124.00   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_1_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 49961726.72 0.00 12.24 27665834.08 0.00 0.00 0.00 0.00 13848.27 25-JAN-16:01 13848.27 25-JAN-16:01 0.00 0.00 0.00
February 0.251777E+09 0.00 44.43 0.223900E+09 0.00 0.00 0.00 0.00 17442.06 09-FEB-16:01 17442.06 09-FEB-16:01 0.00 0.00 0.00
March 0.148833E+09 0.00 35.41 0.125953E+09 0.00 0.00 0.00 0.00 17019.93 20-MAR-18:02 17019.93 20-MAR-18:02 0.00 0.00 0.00
April 0.310788E+10 0.00 369.98 0.235885E+10 0.00 0.00 0.00 0.00 17443.39 16-APR-18:01 17443.39 16-APR-18:01 0.00 0.00 0.00
May 0.366562E+10 0.00 417.38 0.242128E+10 0.00 0.00 0.00 0.00 17442.63 29-MAY-18:02 17442.63 29-MAY-18:02 0.00 0.00 0.00
June 0.541757E+10 0.00 557.44 0.314633E+10 0.00 0.00 0.00 0.00 19084.52 27-JUN-08:62 17441.59 08-JUN-18:02 0.00 0.00 0.00
July 0.677845E+10 0.00 598.73 0.395179E+10 0.00 0.00 0.00 0.00 18424.54 18-JUL-15:02 16859.16 28-JUL-18:01 0.00 0.00 0.00
August 0.631989E+10 0.00 646.92 0.348576E+10 0.00 0.00 0.00 0.00 19014.40 11-AUG-15:01 17045.65 27-AUG-18:02 0.00 0.00 0.00
September 0.463672E+10 0.00 520.23 0.261315E+10 0.00 0.00 0.00 0.00 18403.18 19-SEP-15:02 17441.33 29-SEP-18:01 0.00 0.00 0.00
October 0.110357E+10 0.00 176.24 0.707337E+09 0.00 0.00 0.00 0.00 17438.84 07-OCT-15:02 17438.84 07-OCT-15:02 0.00 0.00 0.00
November 62416711.75 0.00 18.04 40049363.14 0.00 0.00 0.00 0.00 17371.64 03-NOV-15:01 17371.64 03-NOV-15:01 0.00 0.00 0.00
December 1333379.28 0.00 0.39 727366.99 0.00 0.00 0.00 0.00 1758.17 20-DEC-19:05 1384.32 18-DEC-19:05 0.00 0.00 0.00
                               
Annual Sum or Average 0.315440E+11 0.00 3397.44 0.191028E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 1333379.28 0.00 0.39 727366.99 0.00 0.00 0.00 0.00 1758.17   1384.32   0.00 0.00 0.00
Maximum of Months 0.677845E+10 0.00 646.92 0.395179E+10 0.00 0.00 0.00 0.00 19084.52   17443.39   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_2_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 6353835.19 0.00 2.28 2612811.09 0.00 0.00 0.00 0.00 10034.87 19-JAN-16:01 9265.00 19-JAN-16:01 0.00 0.00 0.00
February 70422738.66 0.00 16.49 61249054.75 0.00 0.00 0.00 0.00 14748.13 19-FEB-16:02 14748.13 19-FEB-16:02 0.00 0.00 0.00
March 77928660.08 0.00 21.93 68066188.26 0.00 0.00 0.00 0.00 14838.60 20-MAR-18:02 14838.60 20-MAR-18:02 0.00 0.00 0.00
April 0.195476E+10 0.00 261.40 0.148247E+10 0.00 0.00 0.00 0.00 15607.82 17-APR-15:02 15607.82 17-APR-15:02 0.00 0.00 0.00
May 0.287266E+10 0.00 344.44 0.194040E+10 0.00 0.00 0.00 0.00 15607.24 29-MAY-18:02 15607.24 29-MAY-18:02 0.00 0.00 0.00
June 0.478536E+10 0.00 514.48 0.286091E+10 0.00 0.00 0.00 0.00 17046.44 27-JUN-08:62 15606.45 08-JUN-18:02 0.00 0.00 0.00
July 0.584941E+10 0.00 556.33 0.346332E+10 0.00 0.00 0.00 0.00 16557.58 18-JUL-15:02 15242.93 24-JUL-15:02 0.00 0.00 0.00
August 0.470072E+10 0.00 567.32 0.255919E+10 0.00 0.00 0.00 0.00 16878.89 11-AUG-18:02 15173.47 19-AUG-15:02 0.00 0.00 0.00
September 0.266203E+10 0.00 386.44 0.144750E+10 0.00 0.00 0.00 0.00 16248.04 02-SEP-18:02 15603.91 29-SEP-15:01 0.00 0.00 0.00
October 0.429624E+09 0.00 80.18 0.290441E+09 0.00 0.00 0.00 0.00 15602.71 07-OCT-15:02 15602.71 07-OCT-15:02 0.00 0.00 0.00
November 11172250.42 0.00 4.28 7899018.29 0.00 0.00 0.00 0.00 8992.55 10-NOV-16:02 8808.01 10-NOV-16:02 0.00 0.00 0.00
December 100458.08 0.00 0.08 30120.70 0.00 0.00 0.00 0.00 858.75 02-DEC-09:05 206.31 02-DEC-09:05 0.00 0.00 0.00
                               
Annual Sum or Average 0.234205E+11 0.00 2755.66 0.141841E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 100458.08 0.00 0.08 30120.70 0.00 0.00 0.00 0.00 858.75   206.31   0.00 0.00 0.00
Maximum of Months 0.584941E+10 0.00 567.32 0.346332E+10 0.00 0.00 0.00 0.00 17046.44   15607.82   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.483953E+10 0.00 116.85 0.443967E+10 0.00 0.00 0.00 0.00 40129.05 21-JAN-11:25 40129.05 21-JAN-11:25 0.00 0.00 0.00
February 0.518336E+10 0.00 128.17 0.490526E+10 0.00 0.00 0.00 0.00 35724.21 04-FEB-14:00 35724.21 04-FEB-14:00 0.00 0.00 0.00
March 0.266107E+09 0.00 25.46 0.218088E+09 0.00 0.00 0.00 0.00 12965.78 25-MAR-11:40 12965.78 25-MAR-11:40 0.00 0.00 0.00
April 0.279663E+11 0.00 444.39 0.259005E+11 0.00 0.00 0.00 0.00 50667.71 30-APR-12:30 50460.94 30-APR-12:30 0.00 0.00 0.00
May 0.219573E+11 0.00 426.04 0.152986E+11 0.00 0.00 0.00 0.00 41368.51 23-MAY-13:00 36013.99 11-MAY-13:10 0.00 0.00 0.00
June 0.265572E+11 0.00 512.83 0.116983E+11 0.00 0.00 0.00 0.00 40575.61 13-JUN-13:10 28316.98 13-JUN-13:20 0.00 0.00 0.00
July 0.333793E+11 0.00 579.96 0.154748E+11 0.00 0.00 0.00 0.00 47050.33 22-JUL-13:10 38897.14 22-JUL-13:30 0.00 0.00 0.00
August 0.400160E+11 0.00 602.89 0.217659E+11 0.00 0.00 0.00 0.00 51889.83 19-AUG-12:50 44328.41 20-AUG-13:00 0.00 0.00 0.00
September 0.458117E+11 0.00 573.00 0.293918E+11 0.00 0.00 0.00 0.00 64095.34 23-SEP-14:30 53830.64 13-SEP-13:40 0.00 0.00 0.00
October 0.186119E+11 0.00 289.03 0.147188E+11 0.00 0.00 0.00 0.00 59066.09 07-OCT-13:10 59066.09 07-OCT-13:10 0.00 0.00 0.00
November 0.375125E+10 0.00 93.47 0.335427E+10 0.00 0.00 0.00 0.00 38365.73 11-NOV-13:30 38365.73 11-NOV-13:30 0.00 0.00 0.00
December 0.193796E+09 0.00 7.33 0.193796E+09 0.00 0.00 0.00 0.00 12782.98 26-DEC-14:30 12782.98 26-DEC-14:30 0.00 0.00 0.00
                               
Annual Sum or Average 0.228534E+12 0.00 3799.42 0.147360E+12 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.193796E+09 0.00 7.33 0.193796E+09 0.00 0.00 0.00 0.00 12782.98   12782.98   0.00 0.00 0.00
Maximum of Months 0.458117E+11 0.00 602.89 0.293918E+11 0.00 0.00 0.00 0.00 64095.34   59066.09   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.397135E+10 0.00 188.95 0.203052E+10 0.00 0.00 0.00 0.00 68115.58 29-JAN-19:02 68115.58 29-JAN-19:02 0.00 0.00 0.00
February 0.368559E+10 0.00 178.16 0.229004E+10 0.00 0.00 0.00 0.00 73288.34 12-FEB-09:02 73288.34 12-FEB-09:02 0.00 0.00 0.00
March 0.102947E+11 0.00 353.15 0.740858E+10 0.00 0.00 0.00 0.00 76155.67 11-MAR-09:02 76155.67 11-MAR-09:02 0.00 0.00 0.00
April 0.233654E+11 0.00 480.38 0.183338E+11 0.00 0.00 0.00 0.00 79550.06 22-APR-15:02 79550.06 22-APR-15:02 0.00 0.00 0.00
May 0.314232E+11 0.00 519.76 0.219693E+11 0.00 0.00 0.00 0.00 80746.96 23-MAY-15:02 80531.40 28-MAY-18:01 0.00 0.00 0.00
June 0.457088E+11 0.00 510.48 0.306776E+11 0.00 0.00 0.00 0.00 89052.07 26-JUN-18:02 80281.23 12-JUN-18:02 0.00 0.00 0.00
July 0.504623E+11 0.00 528.51 0.337060E+11 0.00 0.00 0.00 0.00 84684.00 25-JUL-15:02 79644.68 10-JUL-15:02 0.00 0.00 0.00
August 0.439096E+11 0.00 525.67 0.274162E+11 0.00 0.00 0.00 0.00 86170.75 11-AUG-15:01 78523.23 24-AUG-15:02 0.00 0.00 0.00
September 0.319454E+11 0.00 507.81 0.192857E+11 0.00 0.00 0.00 0.00 84855.17 16-SEP-08:62 77421.17 29-SEP-18:01 0.00 0.00 0.00
October 0.155821E+11 0.00 459.29 0.828760E+10 0.00 0.00 0.00 0.00 80430.89 09-OCT-08:62 76703.82 07-OCT-18:02 0.00 0.00 0.00
November 0.648716E+10 0.00 272.43 0.329906E+10 0.00 0.00 0.00 0.00 77258.89 08-NOV-19:03 74723.89 26-NOV-09:02 0.00 0.00 0.00
December 0.205604E+10 0.00 137.08 0.112322E+10 0.00 0.00 0.00 0.00 62577.53 02-DEC-09:02 62577.53 02-DEC-09:02 0.00 0.00 0.00
                               
Annual Sum or Average 0.268892E+12 0.00 4661.66 0.175828E+12 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.205604E+10 0.00 137.08 0.112322E+10 0.00 0.00 0.00 0.00 62577.53   62577.53   0.00 0.00 0.00
Maximum of Months 0.504623E+11 0.00 528.51 0.337060E+11 0.00 0.00 0.00 0.00 89052.07   80531.40   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_5_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.108374E+09 0.00 22.44 55059275.29 0.00 0.00 0.00 0.00 9839.28 21-JAN-16:02 9078.73 21-JAN-16:02 0.00 0.00 0.00
February 0.179290E+09 0.00 34.22 0.121510E+09 0.00 0.00 0.00 0.00 14973.91 04-FEB-16:01 14973.91 04-FEB-16:01 0.00 0.00 0.00
March 0.121181E+09 0.00 37.18 81728651.96 0.00 0.00 0.00 0.00 13338.00 20-MAR-15:01 13338.00 20-MAR-15:01 0.00 0.00 0.00
April 0.350823E+10 0.00 416.84 0.267003E+10 0.00 0.00 0.00 0.00 15850.09 17-APR-15:02 15850.09 17-APR-15:02 0.00 0.00 0.00
May 0.366563E+10 0.00 455.29 0.226648E+10 0.00 0.00 0.00 0.00 15848.97 02-MAY-15:02 15848.97 02-MAY-15:02 0.00 0.00 0.00
June 0.503741E+10 0.00 553.55 0.281164E+10 0.00 0.00 0.00 0.00 17451.68 27-JUN-08:62 15406.52 23-JUN-18:01 0.00 0.00 0.00
July 0.633149E+10 0.00 627.99 0.356296E+10 0.00 0.00 0.00 0.00 16843.18 28-JUL-15:01 15439.44 16-JUL-15:02 0.00 0.00 0.00
August 0.663048E+10 0.00 662.15 0.370201E+10 0.00 0.00 0.00 0.00 17293.30 11-AUG-15:01 15482.57 19-AUG-08:62 0.00 0.00 0.00
September 0.519220E+10 0.00 561.51 0.296899E+10 0.00 0.00 0.00 0.00 16866.72 02-SEP-08:62 15846.22 29-SEP-15:01 0.00 0.00 0.00
October 0.118751E+10 0.00 187.27 0.742591E+09 0.00 0.00 0.00 0.00 15845.66 07-OCT-15:02 15845.66 07-OCT-15:02 0.00 0.00 0.00
November 0.105128E+09 0.00 23.48 62226146.73 0.00 0.00 0.00 0.00 14714.48 03-NOV-15:01 14714.48 03-NOV-15:01 0.00 0.00 0.00
December 29268839.52 0.00 10.61 15325714.17 0.00 0.00 0.00 0.00 2894.65 06-DEC-09:03 1730.63 06-DEC-09:03 0.00 0.00 0.00
                               
Annual Sum or Average 0.320962E+11 0.00 3592.53 0.190606E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 29268839.52 0.00 10.61 15325714.17 0.00 0.00 0.00 0.00 2894.65   1730.63   0.00 0.00 0.00
Maximum of Months 0.663048E+10 0.00 662.15 0.370201E+10 0.00 0.00 0.00 0.00 17451.68   15850.09   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_6_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 9111572.95 0.00 5.69 2573627.78 0.00 0.00 0.00 0.00 2640.41 19-JAN-09:03 1542.59 20-JAN-16:05 0.00 0.00 0.00
February 36580418.67 0.00 15.18 20076180.46 0.00 0.00 0.00 0.00 9308.76 20-FEB-09:02 9048.45 20-FEB-09:02 0.00 0.00 0.00
March 42920641.72 0.00 19.13 24623906.10 0.00 0.00 0.00 0.00 3786.21 10-MAR-09:02 2989.37 10-MAR-09:02 0.00 0.00 0.00
April 0.221858E+10 0.00 317.67 0.164160E+10 0.00 0.00 0.00 0.00 14298.66 20-APR-08:62 14298.66 20-APR-08:62 0.00 0.00 0.00
May 0.280307E+10 0.00 380.46 0.176907E+10 0.00 0.00 0.00 0.00 14555.62 23-MAY-15:02 14296.83 21-MAY-15:01 0.00 0.00 0.00
June 0.436619E+10 0.00 506.63 0.251687E+10 0.00 0.00 0.00 0.00 15726.88 27-JUN-08:62 13889.79 23-JUN-18:01 0.00 0.00 0.00
July 0.533014E+10 0.00 605.85 0.305281E+10 0.00 0.00 0.00 0.00 15238.34 25-JUL-15:02 13907.19 10-JUL-15:02 0.00 0.00 0.00
August 0.489475E+10 0.00 625.93 0.266871E+10 0.00 0.00 0.00 0.00 15455.62 11-AUG-15:01 13964.14 05-AUG-15:02 0.00 0.00 0.00
September 0.303582E+10 0.00 438.58 0.166491E+10 0.00 0.00 0.00 0.00 15108.36 02-SEP-08:62 13873.12 23-SEP-08:62 0.00 0.00 0.00
October 0.437056E+09 0.00 93.90 0.250412E+09 0.00 0.00 0.00 0.00 13700.19 07-OCT-15:02 13700.19 07-OCT-15:02 0.00 0.00 0.00
November 14554033.57 0.00 7.71 5069846.51 0.00 0.00 0.00 0.00 4560.61 11-NOV-09:02 3984.60 11-NOV-09:02 0.00 0.00 0.00
December 1223460.61 0.00 0.56 481602.79 0.00 0.00 0.00 0.00 1850.75 11-DEC-09:05 853.08 08-DEC-09:05 0.00 0.00 0.00
                               
Annual Sum or Average 0.231900E+11 0.00 3017.30 0.136172E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 1223460.61 0.00 0.56 481602.79 0.00 0.00 0.00 0.00 1850.75   853.08   0.00 0.00 0.00
Maximum of Months 0.533014E+10 0.00 625.93 0.305281E+10 0.00 0.00 0.00 0.00 15726.88   14298.66   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_1_FLR_6 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 9907519.64 0.00 7.12 5915679.90 0.00 0.00 0.00 0.00 3686.22 25-JAN-16:01 3686.22 25-JAN-16:01 0.00 0.00 0.00
February 64342783.93 0.00 35.40 59044578.05 0.00 0.00 0.00 0.00 4669.85 09-FEB-16:01 4669.85 09-FEB-16:01 0.00 0.00 0.00
March 33232519.72 0.00 26.48 29251211.92 0.00 0.00 0.00 0.00 4623.00 20-MAR-18:02 4623.00 20-MAR-18:02 0.00 0.00 0.00
April 0.894364E+09 0.00 337.18 0.714605E+09 0.00 0.00 0.00 0.00 4670.34 06-APR-18:01 4670.34 06-APR-18:01 0.00 0.00 0.00
May 0.103773E+10 0.00 381.87 0.722846E+09 0.00 0.00 0.00 0.00 4670.04 29-MAY-18:02 4670.04 29-MAY-18:02 0.00 0.00 0.00
June 0.155390E+10 0.00 536.89 0.960143E+09 0.00 0.00 0.00 0.00 5271.68 27-JUN-08:62 4669.61 08-JUN-18:02 0.00 0.00 0.00
July 0.195809E+10 0.00 601.03 0.120627E+10 0.00 0.00 0.00 0.00 5029.43 18-JUL-08:62 4527.16 16-JUL-18:02 0.00 0.00 0.00
August 0.179425E+10 0.00 637.72 0.105276E+10 0.00 0.00 0.00 0.00 5138.51 11-AUG-15:01 4559.11 29-AUG-18:02 0.00 0.00 0.00
September 0.125693E+10 0.00 487.27 0.750021E+09 0.00 0.00 0.00 0.00 4999.27 02-SEP-08:62 4669.63 29-SEP-18:01 0.00 0.00 0.00
October 0.282028E+09 0.00 140.69 0.192192E+09 0.00 0.00 0.00 0.00 4669.02 07-OCT-15:02 4669.02 07-OCT-15:02 0.00 0.00 0.00
November 13681357.36 0.00 10.93 9405639.54 0.00 0.00 0.00 0.00 4623.13 03-NOV-15:01 4623.13 03-NOV-15:01 0.00 0.00 0.00
December 80784.45 0.00 0.11 65021.44 0.00 0.00 0.00 0.00 333.51 26-DEC-16:05 333.51 26-DEC-16:05 0.00 0.00 0.00
                               
Annual Sum or Average 0.889854E+10 0.00 3202.70 0.570251E+10 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 80784.45 0.00 0.11 65021.44 0.00 0.00 0.00 0.00 333.51   333.51   0.00 0.00 0.00
Maximum of Months 0.195809E+10 0.00 637.72 0.120627E+10 0.00 0.00 0.00 0.00 5271.68   4670.34   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_2_FLR_6 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 1060553.34 0.00 1.03 476762.93 0.00 0.00 0.00 0.00 1438.13 19-JAN-16:01 1354.96 19-JAN-16:01 0.00 0.00 0.00
February 13041292.02 0.00 14.16 10858633.35 0.00 0.00 0.00 0.00 3402.17 19-FEB-16:02 3402.17 19-FEB-16:02 0.00 0.00 0.00
March 16727962.15 0.00 15.58 14704498.11 0.00 0.00 0.00 0.00 3981.05 20-MAR-18:02 3981.05 20-MAR-18:02 0.00 0.00 0.00
April 0.572491E+09 0.00 237.36 0.456072E+09 0.00 0.00 0.00 0.00 4150.31 17-APR-15:02 4150.31 17-APR-15:02 0.00 0.00 0.00
May 0.812806E+09 0.00 318.25 0.581077E+09 0.00 0.00 0.00 0.00 4150.09 29-MAY-18:02 4150.09 29-MAY-18:02 0.00 0.00 0.00
June 0.137083E+10 0.00 498.02 0.870226E+09 0.00 0.00 0.00 0.00 4678.84 27-JUN-08:62 4149.72 08-JUN-18:02 0.00 0.00 0.00
July 0.169168E+10 0.00 569.19 0.105812E+10 0.00 0.00 0.00 0.00 4460.58 18-JUL-08:62 4049.37 24-JUL-18:02 0.00 0.00 0.00
August 0.134067E+10 0.00 560.15 0.779053E+09 0.00 0.00 0.00 0.00 4518.44 11-AUG-15:01 4053.57 27-AUG-15:02 0.00 0.00 0.00
September 0.718698E+09 0.00 347.16 0.416298E+09 0.00 0.00 0.00 0.00 4310.13 02-SEP-18:02 4149.17 29-SEP-15:01 0.00 0.00 0.00
October 0.106560E+09 0.00 65.87 77854850.43 0.00 0.00 0.00 0.00 4148.92 07-OCT-15:02 4148.92 07-OCT-15:02 0.00 0.00 0.00
November 1408423.27 0.00 2.65 707075.90 0.00 0.00 0.00 0.00 1699.14 10-NOV-16:02 1296.42 10-NOV-16:02 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 0.00 01-DEC-00:03 0.00 0.00 0.00
                               
Annual Sum or Average 0.664598E+10 0.00 2629.43 0.426545E+10 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00   0.00   0.00 0.00 0.00
Maximum of Months 0.169168E+10 0.00 569.19 0.105812E+10 0.00 0.00 0.00 0.00 4678.84   4150.31   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.151551E+10 0.00 157.04 0.994676E+09 0.00 0.00 0.00 0.00 25972.16 01-JAN-16:01 25972.16 01-JAN-16:01 0.00 0.00 0.00
February 0.187154E+10 0.00 177.67 0.150479E+10 0.00 0.00 0.00 0.00 25980.12 05-FEB-16:01 25980.12 05-FEB-16:01 0.00 0.00 0.00
March 0.695490E+09 0.00 130.65 0.528520E+09 0.00 0.00 0.00 0.00 25974.45 20-MAR-15:01 25974.45 20-MAR-15:01 0.00 0.00 0.00
April 0.687770E+10 0.00 470.16 0.537162E+10 0.00 0.00 0.00 0.00 25979.53 27-APR-18:02 25979.53 27-APR-18:02 0.00 0.00 0.00
May 0.587780E+10 0.00 478.90 0.343414E+10 0.00 0.00 0.00 0.00 25978.99 06-MAY-15:02 25978.99 06-MAY-15:02 0.00 0.00 0.00
June 0.774384E+10 0.00 594.27 0.404928E+10 0.00 0.00 0.00 0.00 28636.45 26-JUN-18:02 25341.23 23-JUN-18:01 0.00 0.00 0.00
July 0.100107E+11 0.00 626.86 0.546686E+10 0.00 0.00 0.00 0.00 27034.59 24-JUL-18:02 25767.44 05-JUL-18:02 0.00 0.00 0.00
August 0.115311E+11 0.00 667.39 0.670179E+10 0.00 0.00 0.00 0.00 28673.92 11-AUG-15:01 25288.95 27-AUG-18:02 0.00 0.00 0.00
September 0.111078E+11 0.00 615.48 0.720371E+10 0.00 0.00 0.00 0.00 27647.58 19-SEP-15:02 25978.35 29-SEP-18:01 0.00 0.00 0.00
October 0.432570E+10 0.00 342.77 0.279127E+10 0.00 0.00 0.00 0.00 25978.39 07-OCT-18:02 25978.39 07-OCT-18:02 0.00 0.00 0.00
November 0.124368E+10 0.00 150.92 0.834309E+09 0.00 0.00 0.00 0.00 25974.12 19-NOV-16:01 25974.12 19-NOV-16:01 0.00 0.00 0.00
December 0.432071E+09 0.00 51.37 0.362869E+09 0.00 0.00 0.00 0.00 25539.83 18-DEC-16:02 25539.83 18-DEC-16:02 0.00 0.00 0.00
                               
Annual Sum or Average 0.632330E+11 0.00 4463.48 0.392438E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.432071E+09 0.00 51.37 0.362869E+09 0.00 0.00 0.00 0.00 25539.83   25288.95   0.00 0.00 0.00
Maximum of Months 0.115311E+11 0.00 667.39 0.720371E+10 0.00 0.00 0.00 0.00 28673.92   25980.12   0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 563.62 364.98 198.64 563.58 505.50 0.00 0.00 0.00
February 683.92 416.83 267.09 701.24 488.32 0.00 0.00 0.00
March 422.12 122.02 300.10 355.57 407.44 0.00 0.00 0.00
April 865.32 383.42 481.90 1002.76 332.88 0.00 0.00 0.00
May 725.42 235.00 490.43 790.01 282.58 0.00 0.00 0.00
June 669.64 161.95 507.69 770.09 204.28 0.00 0.00 0.00
July 721.80 223.30 498.49 888.76 184.21 0.00 0.00 0.00
August 847.76 379.84 467.92 1085.41 201.23 0.00 0.00 0.00
September 1015.94 599.62 416.32 1272.02 269.39 0.00 0.00 0.00
October 677.90 390.83 287.07 756.45 371.25 0.00 0.00 0.00
November 489.54 297.70 191.84 493.20 458.89 0.00 0.00 0.00
December 388.47 249.10 139.37 376.12 569.67 0.00 0.00 0.00
                 
Annual Sum or Average 671.57 317.45 354.12 753.62 355.66 0.00 0.00 0.00
Minimum of Months 388.47 122.02 139.37 355.57 184.21 0.00 0.00 0.00
Maximum of Months 1015.94 599.62 507.69 1272.02 569.67 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CAFE_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 1587.11 1027.75 559.36 1575.35 1434.16 0.00 0.00 0.00
February 1925.88 1173.78 752.10 1962.04 1382.30 0.00 0.00 0.00
March 1188.66 343.60 845.06 987.72 1151.32 0.00 0.00 0.00
April 2436.68 1079.69 1356.99 2811.49 931.35 0.00 0.00 0.00
May 2042.74 661.73 1381.00 2211.20 790.38 0.00 0.00 0.00
June 1885.66 456.04 1429.61 2156.80 567.10 0.00 0.00 0.00
July 2032.53 628.81 1403.72 2492.80 510.38 0.00 0.00 0.00
August 2387.23 1069.59 1317.63 3048.21 558.05 0.00 0.00 0.00
September 2860.82 1688.48 1172.34 3573.39 751.71 0.00 0.00 0.00
October 1908.91 1100.54 808.37 2119.76 1047.84 0.00 0.00 0.00
November 1378.50 838.29 540.21 1379.13 1303.27 0.00 0.00 0.00
December 1093.90 701.44 392.46 1050.28 1628.55 0.00 0.00 0.00
                 
Annual Sum or Average 1891.09 893.91 997.17 2111.25 1002.87 0.00 0.00 0.00
Minimum of Months 1093.90 343.60 392.46 987.72 510.38 0.00 0.00 0.00
Maximum of Months 2860.82 1688.48 1429.61 3573.39 1628.55 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: LOBBY_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 2061.74 1335.10 726.64 2074.05 1920.53 0.00 0.00 0.00
February 2501.82 1524.80 977.02 2586.31 1843.63 0.00 0.00 0.00
March 1544.14 446.36 1097.78 1304.86 1546.67 0.00 0.00 0.00
April 3165.39 1402.59 1762.80 3725.87 1238.41 0.00 0.00 0.00
May 2653.63 859.63 1794.00 2935.78 1055.26 0.00 0.00 0.00
June 2449.58 592.43 1857.15 2867.73 761.90 0.00 0.00 0.00
July 2640.37 816.86 1823.51 3311.00 685.72 0.00 0.00 0.00
August 3101.14 1389.46 1711.68 4041.69 745.02 0.00 0.00 0.00
September 3716.37 2193.43 1522.94 4732.38 994.91 0.00 0.00 0.00
October 2479.78 1429.67 1050.12 2801.04 1397.81 0.00 0.00 0.00
November 1790.75 1088.99 701.76 1816.30 1745.41 0.00 0.00 0.00
December 1421.04 911.21 509.83 1379.54 2191.37 0.00 0.00 0.00
                 
Annual Sum or Average 2456.63 1161.25 1295.39 2794.44 1341.52 0.00 0.00 0.00
Minimum of Months 1421.04 446.36 509.83 1304.86 685.72 0.00 0.00 0.00
Maximum of Months 3716.37 2193.43 1857.15 4732.38 2191.37 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 111.44 72.16 39.27 112.58 101.00 0.00 0.00 0.00
February 135.22 82.42 52.81 139.18 98.49 0.00 0.00 0.00
March 83.46 24.13 59.33 70.69 82.00 0.00 0.00 0.00
April 171.09 75.81 95.28 196.27 68.65 0.00 0.00 0.00
May 143.43 46.46 96.97 152.56 59.30 0.00 0.00 0.00
June 132.40 32.02 100.38 147.52 43.13 0.00 0.00 0.00
July 142.71 44.15 98.56 171.25 38.80 0.00 0.00 0.00
August 167.62 75.10 92.52 211.47 41.77 0.00 0.00 0.00
September 200.87 118.55 82.32 249.94 55.49 0.00 0.00 0.00
October 134.03 77.27 56.76 149.48 75.06 0.00 0.00 0.00
November 96.79 58.86 37.93 98.07 91.82 0.00 0.00 0.00
December 76.81 49.25 27.56 75.27 114.38 0.00 0.00 0.00
                 
Annual Sum or Average 132.78 62.77 70.02 147.65 72.36 0.00 0.00 0.00
Minimum of Months 76.81 24.13 27.56 70.69 38.80 0.00 0.00 0.00
Maximum of Months 200.87 118.55 100.38 249.94 114.38 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_1_FLR_3_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 73.05 23.94 49.11 44.33 203.23 0.00 0.00 0.00
February 129.22 55.01 74.22 101.60 192.98 0.00 0.00 0.00
March 116.25 22.35 93.89 75.52 153.53 0.00 0.00 0.00
April 273.78 108.55 165.23 285.45 124.77 0.00 0.00 0.00
May 321.27 130.65 190.62 333.77 105.38 0.00 0.00 0.00
June 346.85 142.80 204.06 390.69 77.26 0.00 0.00 0.00
July 353.04 155.51 197.53 415.35 69.80 0.00 0.00 0.00
August 297.09 128.70 168.39 351.62 76.26 0.00 0.00 0.00
September 240.07 108.52 131.55 270.04 103.49 0.00 0.00 0.00
October 127.97 46.48 81.49 113.59 143.51 0.00 0.00 0.00
November 69.04 20.37 48.67 42.60 180.46 0.00 0.00 0.00
December 38.49 7.82 30.67 13.68 227.16 0.00 0.00 0.00
                 
Annual Sum or Average 199.05 79.25 119.80 203.54 137.88 0.00 0.00 0.00
Minimum of Months 38.49 7.82 30.67 13.68 69.80 0.00 0.00 0.00
Maximum of Months 353.04 155.51 204.06 415.35 227.16 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_2_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 19.53 0.00 19.53 2.22 111.70 0.00 0.00 0.00
February 30.49 0.00 30.49 6.11 105.32 0.00 0.00 0.00
March 42.20 0.00 42.20 17.13 84.58 0.00 0.00 0.00
April 68.95 0.46 68.49 48.38 66.55 0.00 0.00 0.00
May 86.20 4.40 81.81 61.06 53.19 0.00 0.00 0.00
June 94.97 5.94 89.03 85.39 39.25 0.00 0.00 0.00
July 90.30 5.31 84.99 87.08 35.27 0.00 0.00 0.00
August 71.09 1.33 69.76 67.63 39.05 0.00 0.00 0.00
September 53.92 0.03 53.89 44.69 55.46 0.00 0.00 0.00
October 34.53 0.00 34.53 17.26 77.20 0.00 0.00 0.00
November 20.75 0.00 20.75 3.44 97.23 0.00 0.00 0.00
December 14.13 0.00 14.13 0.27 121.99 0.00 0.00 0.00
                 
Annual Sum or Average 52.35 1.47 50.89 36.88 73.74 0.00 0.00 0.00
Minimum of Months 14.13 0.00 14.13 0.27 35.27 0.00 0.00 0.00
Maximum of Months 94.97 5.94 89.03 87.08 121.99 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_2_FLR_3_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 73.05 23.94 49.11 47.05 200.70 0.00 0.00 0.00
February 129.22 55.01 74.22 105.46 190.28 0.00 0.00 0.00
March 116.25 22.35 93.89 77.43 152.44 0.00 0.00 0.00
April 273.78 108.55 165.23 290.15 123.30 0.00 0.00 0.00
May 321.27 130.65 190.62 336.77 104.62 0.00 0.00 0.00
June 346.85 142.80 204.06 392.57 76.80 0.00 0.00 0.00
July 353.04 155.51 197.53 417.58 69.26 0.00 0.00 0.00
August 297.09 128.70 168.39 355.27 75.21 0.00 0.00 0.00
September 240.07 108.52 131.55 275.39 101.53 0.00 0.00 0.00
October 127.97 46.48 81.49 117.57 141.39 0.00 0.00 0.00
November 69.04 20.37 48.67 45.13 178.15 0.00 0.00 0.00
December 38.49 7.82 30.67 14.91 225.23 0.00 0.00 0.00
                 
Annual Sum or Average 199.05 79.25 119.80 206.61 136.32 0.00 0.00 0.00
Minimum of Months 38.49 7.82 30.67 14.91 69.26 0.00 0.00 0.00
Maximum of Months 353.04 155.51 204.06 417.58 225.23 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 89.13 57.72 31.41 86.79 88.91 0.00 0.00 0.00
February 108.16 65.92 42.24 108.09 87.07 0.00 0.00 0.00
March 66.76 19.30 47.46 53.64 71.54 0.00 0.00 0.00
April 136.84 60.64 76.21 153.33 62.45 0.00 0.00 0.00
May 114.72 37.16 77.56 118.48 54.57 0.00 0.00 0.00
June 105.90 25.61 80.29 114.92 40.73 0.00 0.00 0.00
July 114.15 35.31 78.83 134.03 37.12 0.00 0.00 0.00
August 134.07 60.07 74.00 166.15 40.28 0.00 0.00 0.00
September 160.66 94.82 65.84 196.37 52.45 0.00 0.00 0.00
October 107.20 61.81 45.40 116.03 69.99 0.00 0.00 0.00
November 77.42 47.08 30.34 75.52 83.21 0.00 0.00 0.00
December 61.43 39.39 22.04 59.28 92.93 0.00 0.00 0.00
                 
Annual Sum or Average 106.20 50.20 56.00 115.06 64.98 0.00 0.00 0.00
Minimum of Months 61.43 19.30 22.04 53.64 37.12 0.00 0.00 0.00
Maximum of Months 160.66 94.82 80.29 196.37 92.93 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 15.62 0.00 15.62 1.26 94.82 0.00 0.00 0.00
February 24.39 0.00 24.39 3.93 88.36 0.00 0.00 0.00
March 33.76 0.00 33.76 12.36 71.18 0.00 0.00 0.00
April 55.17 0.37 54.80 39.68 53.76 0.00 0.00 0.00
May 68.97 3.52 65.46 50.37 42.91 0.00 0.00 0.00
June 75.98 4.75 71.23 70.88 31.20 0.00 0.00 0.00
July 72.25 4.25 68.00 72.54 27.85 0.00 0.00 0.00
August 56.88 1.06 55.82 56.69 30.75 0.00 0.00 0.00
September 43.14 0.03 43.12 37.08 44.35 0.00 0.00 0.00
October 27.62 0.00 27.62 13.27 64.60 0.00 0.00 0.00
November 16.60 0.00 16.60 2.10 82.98 0.00 0.00 0.00
December 11.30 0.00 11.30 0.07 104.41 0.00 0.00 0.00
                 
Annual Sum or Average 41.89 1.17 40.71 30.15 61.30 0.00 0.00 0.00
Minimum of Months 11.30 0.00 11.30 0.07 27.85 0.00 0.00 0.00
Maximum of Months 75.98 4.75 71.23 72.54 104.41 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_5_FLR_3_WALL_EAST_WINDOW

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 74.10 29.51 44.59 43.12 200.09 0.00 0.00 0.00
February 111.90 41.69 70.20 73.46 188.70 0.00 0.00 0.00
March 116.26 22.93 93.33 74.29 151.97 0.00 0.00 0.00
April 311.45 146.03 165.42 328.89 119.50 0.00 0.00 0.00
May 327.92 143.03 184.89 338.43 101.99 0.00 0.00 0.00
June 324.49 129.63 194.86 359.09 74.89 0.00 0.00 0.00
July 331.18 140.68 190.50 383.03 67.19 0.00 0.00 0.00
August 314.61 150.61 163.99 372.27 72.78 0.00 0.00 0.00
September 282.45 150.08 132.37 321.28 99.47 0.00 0.00 0.00
October 137.38 57.45 79.93 123.44 140.91 0.00 0.00 0.00
November 71.10 24.19 46.91 41.16 176.26 0.00 0.00 0.00
December 52.88 19.79 33.09 26.45 220.57 0.00 0.00 0.00
                 
Annual Sum or Average 204.94 88.08 116.86 207.57 134.27 0.00 0.00 0.00
Minimum of Months 52.88 19.79 33.09 26.45 67.19 0.00 0.00 0.00
Maximum of Months 331.18 150.61 194.86 383.03 220.57 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 111.44 72.16 39.27 112.37 100.83 0.00 0.00 0.00
February 135.22 82.42 52.81 139.13 98.03 0.00 0.00 0.00
March 83.46 24.13 59.33 70.28 81.80 0.00 0.00 0.00
April 171.09 75.81 95.28 194.44 68.45 0.00 0.00 0.00
May 143.43 46.46 96.97 151.15 58.81 0.00 0.00 0.00
June 132.40 32.02 100.38 146.88 42.39 0.00 0.00 0.00
July 142.71 44.15 98.56 170.48 38.14 0.00 0.00 0.00
August 167.62 75.10 92.52 210.44 41.38 0.00 0.00 0.00
September 200.87 118.55 82.32 248.42 55.32 0.00 0.00 0.00
October 134.03 77.27 56.76 148.79 74.88 0.00 0.00 0.00
November 96.79 58.86 37.93 97.89 91.65 0.00 0.00 0.00
December 76.81 49.25 27.56 74.94 114.53 0.00 0.00 0.00
                 
Annual Sum or Average 132.78 62.77 70.02 146.90 72.06 0.00 0.00 0.00
Minimum of Months 76.81 24.13 27.56 70.28 38.14 0.00 0.00 0.00
Maximum of Months 200.87 118.55 100.38 248.42 114.53 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_6_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 19.53 0.00 19.53 2.04 111.45 0.00 0.00 0.00
February 30.49 0.00 30.49 5.79 104.63 0.00 0.00 0.00
March 42.20 0.00 42.20 16.72 84.40 0.00 0.00 0.00
April 68.95 0.46 68.49 46.22 66.56 0.00 0.00 0.00
May 86.20 4.40 81.81 59.42 52.85 0.00 0.00 0.00
June 94.97 5.94 89.03 84.64 38.71 0.00 0.00 0.00
July 90.30 5.31 84.99 86.12 34.77 0.00 0.00 0.00
August 71.09 1.33 69.76 66.09 38.71 0.00 0.00 0.00
September 53.92 0.03 53.89 42.59 55.52 0.00 0.00 0.00
October 34.53 0.00 34.53 16.50 77.08 0.00 0.00 0.00
November 20.75 0.00 20.75 3.25 96.94 0.00 0.00 0.00
December 14.13 0.00 14.13 0.22 122.02 0.00 0.00 0.00
                 
Annual Sum or Average 52.35 1.47 50.89 35.95 73.48 0.00 0.00 0.00
Minimum of Months 14.13 0.00 14.13 0.22 34.77 0.00 0.00 0.00
Maximum of Months 94.97 5.94 89.03 86.12 122.02 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_6_FLR_3_WALL_EAST_WINDOW

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 74.10 29.51 44.59 44.93 196.49 0.00 0.00 0.00
February 111.90 41.69 70.20 76.40 185.01 0.00 0.00 0.00
March 116.26 22.93 93.33 76.02 150.74 0.00 0.00 0.00
April 311.45 146.03 165.42 332.74 117.98 0.00 0.00 0.00
May 327.92 143.03 184.89 340.91 101.19 0.00 0.00 0.00
June 324.49 129.63 194.86 360.71 74.49 0.00 0.00 0.00
July 331.18 140.68 190.50 384.89 66.69 0.00 0.00 0.00
August 314.61 150.61 163.99 375.13 71.77 0.00 0.00 0.00
September 282.45 150.08 132.37 325.40 97.57 0.00 0.00 0.00
October 137.38 57.45 79.93 127.01 138.62 0.00 0.00 0.00
November 71.10 24.19 46.91 43.13 173.25 0.00 0.00 0.00
December 52.88 19.79 33.09 27.35 217.86 0.00 0.00 0.00
                 
Annual Sum or Average 204.94 88.08 116.86 210.03 132.39 0.00 0.00 0.00
Minimum of Months 52.88 19.79 33.09 27.35 66.69 0.00 0.00 0.00
Maximum of Months 331.18 150.61 194.86 384.89 217.86 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 24.73 0.00 24.73 1.90 152.22 0.00 0.00 0.00
February 38.61 0.00 38.61 5.90 141.22 0.00 0.00 0.00
March 53.44 0.00 53.44 20.11 112.47 0.00 0.00 0.00
April 87.32 0.58 86.74 64.49 84.66 0.00 0.00 0.00
May 109.17 5.57 103.61 82.64 67.20 0.00 0.00 0.00
June 120.27 7.52 112.75 116.43 48.53 0.00 0.00 0.00
July 114.35 6.73 107.63 118.91 43.51 0.00 0.00 0.00
August 90.03 1.68 88.35 92.66 48.28 0.00 0.00 0.00
September 68.29 0.04 68.25 60.21 69.91 0.00 0.00 0.00
October 43.73 0.00 43.73 21.43 101.82 0.00 0.00 0.00
November 26.27 0.00 26.27 3.26 132.09 0.00 0.00 0.00
December 17.89 0.00 17.89 0.08 167.67 0.00 0.00 0.00
                 
Annual Sum or Average 66.30 1.86 64.44 49.22 97.25 0.00 0.00 0.00
Minimum of Months 17.89 0.00 17.89 0.08 43.51 0.00 0.00 0.00
Maximum of Months 120.27 7.52 112.75 118.91 167.67 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 9.12 0.00 9.12 0.70 56.11 0.00 0.00 0.00
February 14.23 0.00 14.23 2.17 52.06 0.00 0.00 0.00
March 19.70 0.00 19.70 7.41 41.46 0.00 0.00 0.00
April 32.19 0.21 31.98 23.77 31.21 0.00 0.00 0.00
May 40.25 2.05 38.19 30.46 24.77 0.00 0.00 0.00
June 44.34 2.77 41.56 42.92 17.89 0.00 0.00 0.00
July 42.16 2.48 39.68 43.83 16.04 0.00 0.00 0.00
August 33.19 0.62 32.57 34.16 17.80 0.00 0.00 0.00
September 25.17 0.01 25.16 22.20 25.77 0.00 0.00 0.00
October 16.12 0.00 16.12 7.90 37.53 0.00 0.00 0.00
November 9.69 0.00 9.69 1.20 48.69 0.00 0.00 0.00
December 6.60 0.00 6.60 0.03 61.81 0.00 0.00 0.00
                 
Annual Sum or Average 24.44 0.68 23.76 18.15 35.85 0.00 0.00 0.00
Minimum of Months 6.60 0.00 6.60 0.03 16.04 0.00 0.00 0.00
Maximum of Months 44.34 2.77 41.56 43.83 61.81 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 52.00 33.67 18.33 52.30 49.42 0.00 0.00 0.00
February 63.09 38.45 24.64 65.13 47.69 0.00 0.00 0.00
March 38.94 11.26 27.69 32.74 39.80 0.00 0.00 0.00
April 79.83 35.37 44.46 93.84 31.76 0.00 0.00 0.00
May 66.92 21.68 45.24 73.65 27.31 0.00 0.00 0.00
June 61.78 14.94 46.84 72.16 19.49 0.00 0.00 0.00
July 66.59 20.60 45.99 83.43 17.46 0.00 0.00 0.00
August 78.21 35.04 43.17 102.01 18.75 0.00 0.00 0.00
September 93.72 55.32 38.41 119.31 25.32 0.00 0.00 0.00
October 62.54 36.06 26.48 70.64 35.89 0.00 0.00 0.00
November 45.16 27.46 17.70 45.72 45.04 0.00 0.00 0.00
December 35.84 22.98 12.86 34.73 56.91 0.00 0.00 0.00
                 
Annual Sum or Average 61.96 29.29 32.67 70.38 34.51 0.00 0.00 0.00
Minimum of Months 35.84 11.26 12.86 32.74 17.46 0.00 0.00 0.00
Maximum of Months 93.72 55.32 46.84 119.31 56.91 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 141.13 91.39 49.74 141.96 134.14 0.00 0.00 0.00
February 171.25 104.37 66.88 176.77 129.45 0.00 0.00 0.00
March 105.70 30.55 75.14 88.87 108.02 0.00 0.00 0.00
April 216.67 96.01 120.67 254.70 86.21 0.00 0.00 0.00
May 181.64 58.84 122.80 199.89 74.12 0.00 0.00 0.00
June 167.68 40.55 127.12 195.87 52.89 0.00 0.00 0.00
July 180.74 55.91 124.82 226.46 47.40 0.00 0.00 0.00
August 212.28 95.11 117.17 276.88 50.90 0.00 0.00 0.00
September 254.39 150.14 104.25 323.83 68.72 0.00 0.00 0.00
October 169.74 97.86 71.88 191.73 97.41 0.00 0.00 0.00
November 122.58 74.54 48.04 124.09 122.26 0.00 0.00 0.00
December 97.27 62.37 34.90 94.26 154.46 0.00 0.00 0.00
                 
Annual Sum or Average 168.16 79.49 88.67 191.03 93.66 0.00 0.00 0.00
Minimum of Months 97.27 30.55 34.90 88.87 47.40 0.00 0.00 0.00
Maximum of Months 254.39 150.14 127.12 323.83 154.46 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 111.44 72.16 39.27 112.91 99.35 0.00 0.00 0.00
February 135.22 82.42 52.81 139.24 97.35 0.00 0.00 0.00
March 83.46 24.13 59.33 70.83 80.76 0.00 0.00 0.00
April 171.09 75.81 95.28 194.69 68.39 0.00 0.00 0.00
May 143.43 46.46 96.97 150.78 59.48 0.00 0.00 0.00
June 132.40 32.02 100.38 145.42 43.43 0.00 0.00 0.00
July 142.71 44.15 98.56 169.05 39.09 0.00 0.00 0.00
August 167.62 75.10 92.52 209.46 41.89 0.00 0.00 0.00
September 200.87 118.55 82.32 248.26 55.44 0.00 0.00 0.00
October 134.03 77.27 56.76 149.13 74.14 0.00 0.00 0.00
November 96.79 58.86 37.93 98.22 90.39 0.00 0.00 0.00
December 76.81 49.25 27.56 75.46 113.03 0.00 0.00 0.00
                 
Annual Sum or Average 132.78 62.77 70.02 146.75 71.77 0.00 0.00 0.00
Minimum of Months 76.81 24.13 27.56 70.83 39.09 0.00 0.00 0.00
Maximum of Months 200.87 118.55 100.38 248.26 113.03 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_1_FLR_6_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 73.05 23.94 49.11 44.78 199.57 0.00 0.00 0.00
February 129.22 55.01 74.22 101.81 190.39 0.00 0.00 0.00
March 116.25 22.35 93.89 75.74 151.06 0.00 0.00 0.00
April 273.78 108.55 165.23 282.21 124.05 0.00 0.00 0.00
May 321.27 130.65 190.62 329.53 105.51 0.00 0.00 0.00
June 346.85 142.80 204.06 385.48 77.67 0.00 0.00 0.00
July 353.04 155.51 197.53 410.18 70.17 0.00 0.00 0.00
August 297.09 128.70 168.39 347.34 76.35 0.00 0.00 0.00
September 240.07 108.52 131.55 267.22 103.26 0.00 0.00 0.00
October 127.97 46.48 81.49 113.09 141.52 0.00 0.00 0.00
November 69.04 20.37 48.67 42.96 177.40 0.00 0.00 0.00
December 38.49 7.82 30.67 13.96 224.06 0.00 0.00 0.00
                 
Annual Sum or Average 199.05 79.25 119.80 201.53 136.49 0.00 0.00 0.00
Minimum of Months 38.49 7.82 30.67 13.96 70.17 0.00 0.00 0.00
Maximum of Months 353.04 155.51 204.06 410.18 224.06 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_2_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 19.53 0.00 19.53 2.41 109.66 0.00 0.00 0.00
February 30.49 0.00 30.49 6.39 103.75 0.00 0.00 0.00
March 42.20 0.00 42.20 17.42 83.16 0.00 0.00 0.00
April 68.95 0.46 68.49 47.14 66.18 0.00 0.00 0.00
May 86.20 4.40 81.81 59.38 53.22 0.00 0.00 0.00
June 94.97 5.94 89.03 83.18 39.45 0.00 0.00 0.00
July 90.30 5.31 84.99 84.90 35.47 0.00 0.00 0.00
August 71.09 1.33 69.76 65.89 39.13 0.00 0.00 0.00
September 53.92 0.03 53.89 43.73 55.29 0.00 0.00 0.00
October 34.53 0.00 34.53 17.35 75.98 0.00 0.00 0.00
November 20.75 0.00 20.75 3.69 95.35 0.00 0.00 0.00
December 14.13 0.00 14.13 0.34 120.19 0.00 0.00 0.00
                 
Annual Sum or Average 52.35 1.47 50.89 36.13 72.92 0.00 0.00 0.00
Minimum of Months 14.13 0.00 14.13 0.34 35.47 0.00 0.00 0.00
Maximum of Months 94.97 5.94 89.03 84.90 120.19 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_2_FLR_6_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 73.05 23.94 49.11 47.62 197.21 0.00 0.00 0.00
February 129.22 55.01 74.22 105.98 187.62 0.00 0.00 0.00
March 116.25 22.35 93.89 77.82 149.93 0.00 0.00 0.00
April 273.78 108.55 165.23 287.01 122.49 0.00 0.00 0.00
May 321.27 130.65 190.62 332.52 104.70 0.00 0.00 0.00
June 346.85 142.80 204.06 387.22 77.20 0.00 0.00 0.00
July 353.04 155.51 197.53 412.24 69.63 0.00 0.00 0.00
August 297.09 128.70 168.39 350.74 75.25 0.00 0.00 0.00
September 240.07 108.52 131.55 272.63 101.15 0.00 0.00 0.00
October 127.97 46.48 81.49 117.39 139.19 0.00 0.00 0.00
November 69.04 20.37 48.67 45.71 175.09 0.00 0.00 0.00
December 38.49 7.82 30.67 15.19 222.40 0.00 0.00 0.00
                 
Annual Sum or Average 199.05 79.25 119.80 204.67 134.90 0.00 0.00 0.00
Minimum of Months 38.49 7.82 30.67 15.19 69.63 0.00 0.00 0.00
Maximum of Months 353.04 155.51 204.06 412.24 222.40 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 163.43 105.83 57.60 160.11 152.15 0.00 0.00 0.00
February 198.32 120.87 77.45 199.21 148.59 0.00 0.00 0.00
March 122.40 35.38 87.02 100.09 122.30 0.00 0.00 0.00
April 250.92 111.18 139.74 283.13 101.38 0.00 0.00 0.00
May 210.35 68.14 142.21 220.50 87.32 0.00 0.00 0.00
June 194.18 46.96 147.22 214.72 62.86 0.00 0.00 0.00
July 209.30 64.75 144.55 249.37 56.48 0.00 0.00 0.00
August 245.83 110.14 135.68 307.15 61.16 0.00 0.00 0.00
September 294.59 173.87 120.72 361.61 82.58 0.00 0.00 0.00
October 196.57 113.33 83.24 214.73 113.00 0.00 0.00 0.00
November 141.95 86.32 55.63 139.69 139.17 0.00 0.00 0.00
December 112.65 72.23 40.41 107.00 173.21 0.00 0.00 0.00
                 
Annual Sum or Average 194.74 92.05 102.68 212.82 108.15 0.00 0.00 0.00
Minimum of Months 112.65 35.38 40.41 100.09 56.48 0.00 0.00 0.00
Maximum of Months 294.59 173.87 147.22 361.61 173.21 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: BANQUET_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 136.67 0.00 136.67 9.89 835.58 0.00 0.00 0.00
February 213.42 0.00 213.42 30.75 780.02 0.00 0.00 0.00
March 295.36 0.00 295.36 105.63 624.85 0.00 0.00 0.00
April 482.63 3.21 479.42 343.86 475.44 0.00 0.00 0.00
May 603.41 30.77 572.64 435.27 389.09 0.00 0.00 0.00
June 664.75 41.58 623.17 617.34 288.80 0.00 0.00 0.00
July 632.05 37.17 594.87 634.01 259.60 0.00 0.00 0.00
August 497.63 9.31 488.32 497.01 284.36 0.00 0.00 0.00
September 377.45 0.22 377.22 325.08 398.28 0.00 0.00 0.00
October 241.68 0.00 241.68 114.02 571.60 0.00 0.00 0.00
November 145.21 0.00 145.21 16.90 736.03 0.00 0.00 0.00
December 98.89 0.00 98.89 0.39 930.31 0.00 0.00 0.00
                 
Annual Sum or Average 366.45 10.26 356.19 262.03 546.72 0.00 0.00 0.00
Minimum of Months 98.89 0.00 98.89 0.39 259.60 0.00 0.00 0.00
Maximum of Months 664.75 41.58 623.17 634.01 930.31 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: DINING_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 136.67 0.00 136.67 8.95 851.48 0.00 0.00 0.00
February 213.42 0.00 213.42 28.55 795.04 0.00 0.00 0.00
March 295.36 0.00 295.36 101.52 638.60 0.00 0.00 0.00
April 482.63 3.21 479.42 336.35 486.21 0.00 0.00 0.00
May 603.41 30.77 572.64 424.87 398.44 0.00 0.00 0.00
June 664.75 41.58 623.17 605.76 297.53 0.00 0.00 0.00
July 632.05 37.17 594.87 621.98 268.02 0.00 0.00 0.00
August 497.63 9.31 488.32 487.18 294.03 0.00 0.00 0.00
September 377.45 0.22 377.22 318.01 409.65 0.00 0.00 0.00
October 241.68 0.00 241.68 109.98 585.69 0.00 0.00 0.00
November 145.21 0.00 145.21 15.48 752.42 0.00 0.00 0.00
December 98.89 0.00 98.89 0.27 947.62 0.00 0.00 0.00
                 
Annual Sum or Average 366.45 10.26 356.19 256.07 559.28 0.00 0.00 0.00
Minimum of Months 98.89 0.00 98.89 0.27 268.02 0.00 0.00 0.00
Maximum of Months 664.75 41.58 623.17 621.98 947.62 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: KITCHEN_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 19.53 0.00 19.53 4.18 102.84 0.00 0.00 0.00
February 30.49 0.00 30.49 9.10 98.69 0.00 0.00 0.00
March 42.20 0.00 42.20 23.76 79.00 0.00 0.00 0.00
April 68.95 0.46 68.49 61.27 63.68 0.00 0.00 0.00
May 86.20 4.40 81.81 75.67 54.75 0.00 0.00 0.00
June 94.97 5.94 89.03 103.93 41.02 0.00 0.00 0.00
July 90.30 5.31 84.99 106.95 37.21 0.00 0.00 0.00
August 71.09 1.33 69.76 85.43 39.38 0.00 0.00 0.00
September 53.92 0.03 53.89 57.38 52.95 0.00 0.00 0.00
October 34.53 0.00 34.53 24.07 72.75 0.00 0.00 0.00
November 20.75 0.00 20.75 6.02 91.10 0.00 0.00 0.00
December 14.13 0.00 14.13 1.05 116.14 0.00 0.00 0.00
                 
Annual Sum or Average 52.35 1.47 50.89 46.76 70.66 0.00 0.00 0.00
Minimum of Months 14.13 0.00 14.13 1.05 37.21 0.00 0.00 0.00
Maximum of Months 94.97 5.94 89.03 106.95 116.14 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: KITCHEN_FLR_6_WALL_EAST_WINDOW

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 148.18 59.02 89.17 105.81 367.97 0.00 0.00 0.00
February 223.78 83.38 140.39 172.16 353.86 0.00 0.00 0.00
March 232.50 45.86 186.64 183.75 286.70 0.00 0.00 0.00
April 622.85 292.03 330.82 730.91 231.78 0.00 0.00 0.00
May 655.80 286.04 369.76 745.77 209.04 0.00 0.00 0.00
June 648.94 259.24 389.70 795.39 156.41 0.00 0.00 0.00
July 662.31 281.33 380.98 848.88 141.06 0.00 0.00 0.00
August 629.17 301.20 327.96 826.61 147.43 0.00 0.00 0.00
September 564.86 300.14 264.72 715.33 191.91 0.00 0.00 0.00
October 274.74 114.89 159.85 288.85 265.83 0.00 0.00 0.00
November 142.19 48.38 93.81 101.86 329.47 0.00 0.00 0.00
December 105.76 39.58 66.18 64.34 420.59 0.00 0.00 0.00
                 
Annual Sum or Average 409.84 176.15 233.70 466.05 258.06 0.00 0.00 0.00
Minimum of Months 105.76 39.58 66.18 64.34 141.06 0.00 0.00 0.00
Maximum of Months 662.31 301.20 389.70 848.88 420.59 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 111.44 72.16 39.27 120.32 93.80 0.00 0.00 0.00
February 135.22 82.42 52.81 148.53 93.09 0.00 0.00 0.00
March 83.46 24.13 59.33 80.24 77.25 0.00 0.00 0.00
April 171.09 75.81 95.28 213.08 64.97 0.00 0.00 0.00
May 143.43 46.46 96.97 168.91 59.23 0.00 0.00 0.00
June 132.40 32.02 100.38 167.09 43.67 0.00 0.00 0.00
July 142.71 44.15 98.56 192.13 39.35 0.00 0.00 0.00
August 167.62 75.10 92.52 231.64 40.82 0.00 0.00 0.00
September 200.87 118.55 82.32 267.72 52.64 0.00 0.00 0.00
October 134.03 77.27 56.76 161.18 70.92 0.00 0.00 0.00
November 96.79 58.86 37.93 104.81 86.56 0.00 0.00 0.00
December 76.81 49.25 27.56 79.39 109.99 0.00 0.00 0.00
                 
Annual Sum or Average 132.78 62.77 70.02 161.06 69.24 0.00 0.00 0.00
Minimum of Months 76.81 24.13 27.56 79.39 39.35 0.00 0.00 0.00
Maximum of Months 200.87 118.55 100.38 267.72 109.99 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 24.73 0.00 24.73 1.66 152.43 0.00 0.00 0.00
February 38.61 0.00 38.61 5.20 141.79 0.00 0.00 0.00
March 53.44 0.00 53.44 19.13 112.77 0.00 0.00 0.00
April 87.32 0.58 86.74 61.64 85.11 0.00 0.00 0.00
May 109.17 5.57 103.61 79.24 67.97 0.00 0.00 0.00
June 120.27 7.52 112.75 112.64 49.25 0.00 0.00 0.00
July 114.35 6.73 107.63 115.30 43.96 0.00 0.00 0.00
August 90.03 1.68 88.35 89.56 48.67 0.00 0.00 0.00
September 68.29 0.04 68.25 57.87 70.34 0.00 0.00 0.00
October 43.73 0.00 43.73 20.20 102.51 0.00 0.00 0.00
November 26.27 0.00 26.27 2.87 132.84 0.00 0.00 0.00
December 17.89 0.00 17.89 0.05 168.36 0.00 0.00 0.00
                 
Annual Sum or Average 66.30 1.86 64.44 47.33 97.79 0.00 0.00 0.00
Minimum of Months 17.89 0.00 17.89 0.05 43.96 0.00 0.00 0.00
Maximum of Months 120.27 7.52 112.75 115.30 168.36 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 22.12 0.00 22.12 1.49 136.35 0.00 0.00 0.00
February 34.55 0.00 34.55 4.65 126.86 0.00 0.00 0.00
March 47.81 0.00 47.81 17.12 100.89 0.00 0.00 0.00
April 78.13 0.52 77.61 55.15 76.15 0.00 0.00 0.00
May 97.68 4.98 92.70 70.90 60.81 0.00 0.00 0.00
June 107.61 6.73 100.88 100.78 44.06 0.00 0.00 0.00
July 102.31 6.02 96.30 103.16 39.33 0.00 0.00 0.00
August 80.55 1.51 79.05 80.13 43.54 0.00 0.00 0.00
September 61.10 0.04 61.06 51.78 62.93 0.00 0.00 0.00
October 39.12 0.00 39.12 18.07 91.71 0.00 0.00 0.00
November 23.51 0.00 23.51 2.57 118.85 0.00 0.00 0.00
December 16.01 0.00 16.01 0.05 150.61 0.00 0.00 0.00
                 
Annual Sum or Average 59.32 1.66 57.66 42.35 87.49 0.00 0.00 0.00
Minimum of Months 16.01 0.00 16.01 0.05 39.33 0.00 0.00 0.00
Maximum of Months 107.61 6.73 100.88 103.16 150.61 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 416.03 269.40 146.62 415.43 395.53 0.00 0.00 0.00
February 504.83 307.68 197.15 516.57 383.22 0.00 0.00 0.00
March 311.58 90.07 221.51 257.78 319.56 0.00 0.00 0.00
April 638.73 283.02 355.71 741.26 255.97 0.00 0.00 0.00
May 535.46 173.46 362.00 578.91 221.77 0.00 0.00 0.00
June 494.29 119.54 374.75 566.17 158.82 0.00 0.00 0.00
July 532.79 164.83 367.96 656.33 141.73 0.00 0.00 0.00
August 625.76 280.37 345.39 805.53 151.65 0.00 0.00 0.00
September 749.91 442.60 307.31 945.16 204.27 0.00 0.00 0.00
October 500.38 288.48 211.90 559.83 289.70 0.00 0.00 0.00
November 361.34 219.74 141.60 362.46 362.92 0.00 0.00 0.00
December 286.74 183.87 102.88 275.71 457.97 0.00 0.00 0.00
                 
Annual Sum or Average 495.71 234.32 261.39 556.03 278.09 0.00 0.00 0.00
Minimum of Months 286.74 90.07 102.88 257.78 141.73 0.00 0.00 0.00
Maximum of Months 749.91 442.60 374.75 945.16 457.97 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyReportMonthly

For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.150959E+10 0.977552E+09 0.532037E+09 0.150950E+10 0.135393E+10
February 0.165454E+10 0.100840E+10 0.646136E+09 0.169645E+10 0.118136E+10
March 0.113060E+10 0.326821E+09 0.803783E+09 0.952353E+09 0.109129E+10
April 0.224291E+10 0.993833E+09 0.124907E+10 0.259916E+10 0.862828E+09
May 0.194297E+10 0.629412E+09 0.131355E+10 0.211598E+10 0.756874E+09
June 0.173570E+10 0.419778E+09 0.131592E+10 0.199607E+10 0.529504E+09
July 0.193326E+10 0.598097E+09 0.133516E+10 0.238046E+10 0.493387E+09
August 0.227063E+10 0.101735E+10 0.125328E+10 0.290717E+10 0.538967E+09
September 0.263332E+10 0.155420E+10 0.107911E+10 0.329708E+10 0.698258E+09
October 0.181568E+10 0.104679E+10 0.768888E+09 0.202606E+10 0.994367E+09
November 0.126888E+10 0.771630E+09 0.497246E+09 0.127837E+10 0.118943E+10
December 0.104048E+10 0.667184E+09 0.373294E+09 0.100740E+10 0.152581E+10
           
Annual Sum or Average 0.211785E+11 0.100111E+11 0.111675E+11 0.237661E+11 0.112160E+11
Minimum of Months 0.104048E+10 0.326821E+09 0.373294E+09 0.952353E+09 0.493387E+09
Maximum of Months 0.263332E+10 0.155420E+10 0.133516E+10 0.329708E+10 0.152581E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: CAFE_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.425090E+10 0.275272E+10 0.149818E+10 0.421943E+10 0.384126E+10
February 0.465908E+10 0.283960E+10 0.181948E+10 0.474657E+10 0.334406E+10
March 0.318371E+10 0.920306E+09 0.226340E+10 0.264551E+10 0.308370E+10
April 0.631588E+10 0.279857E+10 0.351731E+10 0.728738E+10 0.241406E+10
May 0.547127E+10 0.177238E+10 0.369888E+10 0.592249E+10 0.211695E+10
June 0.488762E+10 0.118207E+10 0.370556E+10 0.559043E+10 0.146993E+10
July 0.544392E+10 0.168420E+10 0.375972E+10 0.667671E+10 0.136701E+10
August 0.639395E+10 0.286480E+10 0.352915E+10 0.816433E+10 0.149469E+10
September 0.741524E+10 0.437654E+10 0.303871E+10 0.926222E+10 0.194844E+10
October 0.511283E+10 0.294769E+10 0.216514E+10 0.567755E+10 0.280653E+10
November 0.357307E+10 0.217286E+10 0.140021E+10 0.357471E+10 0.337808E+10
December 0.292991E+10 0.187874E+10 0.105117E+10 0.281308E+10 0.436191E+10
           
Annual Sum or Average 0.596374E+11 0.281905E+11 0.314469E+11 0.665804E+11 0.316266E+11
Minimum of Months 0.292991E+10 0.920306E+09 0.105117E+10 0.264551E+10 0.136701E+10
Maximum of Months 0.741524E+10 0.437654E+10 0.375972E+10 0.926222E+10 0.436191E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: LOBBY_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.552217E+10 0.357594E+10 0.194622E+10 0.555513E+10 0.514394E+10
February 0.605241E+10 0.368880E+10 0.236360E+10 0.625679E+10 0.446012E+10
March 0.413581E+10 0.119553E+10 0.294029E+10 0.349494E+10 0.414259E+10
April 0.820468E+10 0.363550E+10 0.456918E+10 0.965744E+10 0.320995E+10
May 0.710749E+10 0.230242E+10 0.480506E+10 0.786320E+10 0.282640E+10
June 0.634930E+10 0.153557E+10 0.481373E+10 0.743315E+10 0.197486E+10
July 0.707196E+10 0.218787E+10 0.488409E+10 0.886818E+10 0.183663E+10
August 0.830611E+10 0.372154E+10 0.458457E+10 0.108253E+11 0.199545E+10
September 0.963282E+10 0.568537E+10 0.394745E+10 0.122663E+11 0.257880E+10
October 0.664185E+10 0.382922E+10 0.281264E+10 0.750230E+10 0.374390E+10
November 0.464162E+10 0.282267E+10 0.181896E+10 0.470784E+10 0.452412E+10
December 0.380613E+10 0.244060E+10 0.136553E+10 0.369496E+10 0.586937E+10
           
Annual Sum or Average 0.774723E+11 0.366210E+11 0.408513E+11 0.881255E+11 0.423061E+11
Minimum of Months 0.380613E+10 0.119553E+10 0.136553E+10 0.349494E+10 0.183663E+10
Maximum of Months 0.963282E+10 0.568537E+10 0.488409E+10 0.122663E+11 0.586937E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.298472E+09 0.193279E+09 0.105193E+09 0.301526E+09 0.270507E+09
February 0.327132E+09 0.199379E+09 0.127753E+09 0.336712E+09 0.238262E+09
March 0.223541E+09 64618063.64 0.158923E+09 0.189336E+09 0.219634E+09
April 0.443463E+09 0.196498E+09 0.246965E+09 0.508733E+09 0.177929E+09
May 0.384160E+09 0.124445E+09 0.259715E+09 0.408623E+09 0.158836E+09
June 0.343181E+09 82997281.99 0.260183E+09 0.382385E+09 0.111801E+09
July 0.382241E+09 0.118254E+09 0.263986E+09 0.458679E+09 0.103915E+09
August 0.448945E+09 0.201148E+09 0.247797E+09 0.566394E+09 0.111876E+09
September 0.520653E+09 0.307293E+09 0.213361E+09 0.647837E+09 0.143818E+09
October 0.358991E+09 0.206968E+09 0.152023E+09 0.400379E+09 0.201042E+09
November 0.250879E+09 0.152564E+09 98314557.38 0.254205E+09 0.238002E+09
December 0.205721E+09 0.131914E+09 73806852.46 0.201598E+09 0.306359E+09
           
Annual Sum or Average 0.418738E+10 0.197936E+10 0.220802E+10 0.465640E+10 0.228198E+10
Minimum of Months 0.205721E+09 64618063.64 73806852.46 0.189336E+09 0.103915E+09
Maximum of Months 0.520653E+09 0.307293E+09 0.263986E+09 0.647837E+09 0.306359E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_1_FLR_3_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.195660E+09 64128920.97 0.131532E+09 0.118727E+09 0.544334E+09
February 0.312615E+09 0.133073E+09 0.179541E+09 0.245797E+09 0.466858E+09
March 0.311355E+09 59870921.37 0.251484E+09 0.202274E+09 0.411226E+09
April 0.709636E+09 0.281355E+09 0.428281E+09 0.739889E+09 0.323408E+09
May 0.860491E+09 0.349933E+09 0.510558E+09 0.893982E+09 0.282252E+09
June 0.899047E+09 0.370125E+09 0.528922E+09 0.101266E+10 0.200262E+09
July 0.945570E+09 0.416516E+09 0.529053E+09 0.111247E+10 0.186940E+09
August 0.795714E+09 0.344711E+09 0.451003E+09 0.941790E+09 0.204262E+09
September 0.622261E+09 0.281272E+09 0.340989E+09 0.699941E+09 0.268256E+09
October 0.342754E+09 0.124483E+09 0.218272E+09 0.304230E+09 0.384382E+09
November 0.178958E+09 52801937.15 0.126156E+09 0.110406E+09 0.467741E+09
December 0.103093E+09 20956149.08 82136943.91 36640758.67 0.608412E+09
           
Annual Sum or Average 0.627716E+10 0.249923E+10 0.377793E+10 0.641880E+10 0.434833E+10
Minimum of Months 0.103093E+09 20956149.08 82136943.91 36640758.67 0.186940E+09
Maximum of Months 0.945570E+09 0.416516E+09 0.529053E+09 0.111247E+10 0.608412E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_2_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 52296148.79 0.00 52296148.79 5933558.99 0.299164E+09
February 73759823.15 0.00 73759823.15 14778031.26 0.254793E+09
March 0.113018E+09 763.87 0.113017E+09 45886354.12 0.226543E+09
April 0.178718E+09 1187800.51 0.177530E+09 0.125396E+09 0.172497E+09
May 0.230890E+09 11774052.52 0.219116E+09 0.163538E+09 0.142452E+09
June 0.246156E+09 15397270.00 0.230758E+09 0.221322E+09 0.101736E+09
July 0.241849E+09 14224473.17 0.227624E+09 0.233241E+09 94478050.32
August 0.190413E+09 3560925.39 0.186852E+09 0.181140E+09 0.104579E+09
September 0.139769E+09 82607.68 0.139686E+09 0.115834E+09 0.143740E+09
October 92475413.30 0.00 92475413.30 46230489.26 0.206766E+09
November 53771554.59 0.00 53771554.59 8906821.03 0.252023E+09
December 37838893.74 0.00 37838893.74 736250.32 0.326748E+09
           
Annual Sum or Average 0.165095E+10 46227893.14 0.160473E+10 0.116294E+10 0.232552E+10
Minimum of Months 37838893.74 0.00 37838893.74 736250.32 94478050.32
Maximum of Months 0.246156E+09 15397270.00 0.230758E+09 0.233241E+09 0.326748E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_2_FLR_3_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.195660E+09 64128920.97 0.131532E+09 0.126026E+09 0.537553E+09
February 0.312615E+09 0.133073E+09 0.179541E+09 0.255138E+09 0.460333E+09
March 0.311355E+09 59870921.37 0.251484E+09 0.207378E+09 0.408305E+09
April 0.709636E+09 0.281355E+09 0.428281E+09 0.752063E+09 0.319597E+09
May 0.860491E+09 0.349933E+09 0.510558E+09 0.902014E+09 0.280206E+09
June 0.899047E+09 0.370125E+09 0.528922E+09 0.101755E+10 0.199072E+09
July 0.945570E+09 0.416516E+09 0.529053E+09 0.111844E+10 0.185509E+09
August 0.795714E+09 0.344711E+09 0.451003E+09 0.951549E+09 0.201434E+09
September 0.622261E+09 0.281272E+09 0.340989E+09 0.713809E+09 0.263171E+09
October 0.342754E+09 0.124483E+09 0.218272E+09 0.314911E+09 0.378689E+09
November 0.178958E+09 52801937.15 0.126156E+09 0.116982E+09 0.461753E+09
December 0.103093E+09 20956149.08 82136943.91 39933017.18 0.603261E+09
           
Annual Sum or Average 0.627716E+10 0.249923E+10 0.377793E+10 0.651579E+10 0.429888E+10
Minimum of Months 0.103093E+09 20956149.08 82136943.91 39933017.18 0.185509E+09
Maximum of Months 0.945570E+09 0.416516E+09 0.529053E+09 0.111844E+10 0.603261E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.238730E+09 0.154592E+09 84137898.18 0.232469E+09 0.238130E+09
February 0.261653E+09 0.159471E+09 0.102182E+09 0.261501E+09 0.210643E+09
March 0.178797E+09 51684172.32 0.127113E+09 0.143661E+09 0.191606E+09
April 0.354700E+09 0.157167E+09 0.197533E+09 0.397427E+09 0.161870E+09
May 0.307267E+09 99536592.27 0.207730E+09 0.317327E+09 0.146168E+09
June 0.274490E+09 66384623.48 0.208105E+09 0.297883E+09 0.105569E+09
July 0.305732E+09 94584426.86 0.211147E+09 0.358995E+09 99408841.43
August 0.359085E+09 0.160887E+09 0.198198E+09 0.445026E+09 0.107886E+09
September 0.416440E+09 0.245785E+09 0.170655E+09 0.508980E+09 0.135952E+09
October 0.287136E+09 0.165542E+09 0.121594E+09 0.310766E+09 0.187453E+09
November 0.200663E+09 0.122027E+09 78636007.32 0.195744E+09 0.215690E+09
December 0.164544E+09 0.105510E+09 59033741.75 0.158784E+09 0.248892E+09
           
Annual Sum or Average 0.334924E+10 0.158317E+10 0.176607E+10 0.362856E+10 0.204927E+10
Minimum of Months 0.164544E+09 51684172.32 59033741.75 0.143661E+09 99408841.43
Maximum of Months 0.416440E+09 0.245785E+09 0.211147E+09 0.508980E+09 0.248892E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 41842464.75 0.00 41842464.75 3383701.88 0.253966E+09
February 59015680.35 0.00 59015680.35 9510838.88 0.213762E+09
March 90426079.04 611.18 90425467.87 33113323.56 0.190646E+09
April 0.142993E+09 950366.37 0.142043E+09 0.102841E+09 0.139358E+09
May 0.184736E+09 9420490.59 0.175316E+09 0.134907E+09 0.114931E+09
June 0.196951E+09 12319448.80 0.184631E+09 0.183716E+09 80865322.40
July 0.193505E+09 11381086.97 0.182124E+09 0.194284E+09 74587656.09
August 0.152351E+09 2849117.93 0.149502E+09 0.151839E+09 82370167.36
September 0.111830E+09 66094.90 0.111764E+09 96100804.10 0.114947E+09
October 73990137.15 0.00 73990137.15 35529048.83 0.173023E+09
November 43022945.85 0.00 43022945.85 5443946.53 0.215092E+09
December 30275127.60 0.00 30275127.60 186279.94 0.279647E+09
           
Annual Sum or Average 0.132094E+10 36987216.73 0.128395E+10 0.950856E+09 0.193320E+10
Minimum of Months 30275127.60 0.00 30275127.60 186279.94 74587656.09
Maximum of Months 0.196951E+09 12319448.80 0.184631E+09 0.194284E+09 0.279647E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_5_FLR_3_WALL_EAST_WINDOW

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.198462E+09 79042420.23 0.119420E+09 0.115492E+09 0.535928E+09
February 0.270698E+09 0.100866E+09 0.169832E+09 0.177719E+09 0.456499E+09
March 0.311380E+09 61414734.22 0.249966E+09 0.198987E+09 0.407046E+09
April 0.807271E+09 0.378498E+09 0.428772E+09 0.852478E+09 0.309750E+09
May 0.878305E+09 0.383093E+09 0.495212E+09 0.906452E+09 0.273161E+09
June 0.841083E+09 0.335996E+09 0.505087E+09 0.930767E+09 0.194113E+09
July 0.887034E+09 0.376787E+09 0.510247E+09 0.102590E+10 0.179954E+09
August 0.842638E+09 0.403400E+09 0.439238E+09 0.997095E+09 0.194932E+09
September 0.732111E+09 0.389014E+09 0.343096E+09 0.832757E+09 0.257828E+09
October 0.367956E+09 0.153873E+09 0.214083E+09 0.330622E+09 0.377404E+09
November 0.184287E+09 62706204.31 0.121580E+09 0.106692E+09 0.456861E+09
December 0.141644E+09 53003264.31 88640916.87 70837982.01 0.590787E+09
           
Annual Sum or Average 0.646287E+10 0.277770E+10 0.368517E+10 0.654580E+10 0.423426E+10
Minimum of Months 0.141644E+09 53003264.31 88640916.87 70837982.01 0.179954E+09
Maximum of Months 0.887034E+09 0.403400E+09 0.510247E+09 0.102590E+10 0.590787E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.298472E+09 0.193279E+09 0.105193E+09 0.300978E+09 0.270068E+09
February 0.327132E+09 0.199379E+09 0.127753E+09 0.336578E+09 0.237146E+09
March 0.223541E+09 64618063.64 0.158923E+09 0.188238E+09 0.219094E+09
April 0.443463E+09 0.196498E+09 0.246965E+09 0.503996E+09 0.177418E+09
May 0.384160E+09 0.124445E+09 0.259715E+09 0.404853E+09 0.157519E+09
June 0.343181E+09 82997281.99 0.260183E+09 0.380713E+09 0.109875E+09
July 0.382241E+09 0.118254E+09 0.263986E+09 0.456624E+09 0.102144E+09
August 0.448945E+09 0.201148E+09 0.247797E+09 0.563652E+09 0.110843E+09
September 0.520653E+09 0.307293E+09 0.213361E+09 0.643908E+09 0.143394E+09
October 0.358991E+09 0.206968E+09 0.152023E+09 0.398515E+09 0.200561E+09
November 0.250879E+09 0.152564E+09 98314557.38 0.253738E+09 0.237570E+09
December 0.205721E+09 0.131914E+09 73806852.46 0.200731E+09 0.306763E+09
           
Annual Sum or Average 0.418738E+10 0.197936E+10 0.220802E+10 0.463252E+10 0.227239E+10
Minimum of Months 0.205721E+09 64618063.64 73806852.46 0.188238E+09 0.102144E+09
Maximum of Months 0.520653E+09 0.307293E+09 0.263986E+09 0.643908E+09 0.306763E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_6_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 52296148.79 0.00 52296148.79 5452628.70 0.298501E+09
February 73759823.15 0.00 73759823.15 14011875.59 0.253118E+09
March 0.113018E+09 763.87 0.113017E+09 44778733.77 0.226046E+09
April 0.178718E+09 1187800.51 0.177530E+09 0.119792E+09 0.172518E+09
May 0.230890E+09 11774052.52 0.219116E+09 0.159164E+09 0.141563E+09
June 0.246156E+09 15397270.00 0.230758E+09 0.219387E+09 0.100331E+09
July 0.241849E+09 14224473.17 0.227624E+09 0.230665E+09 93118212.80
August 0.190413E+09 3560925.39 0.186852E+09 0.177018E+09 0.103689E+09
September 0.139769E+09 82607.68 0.139686E+09 0.110397E+09 0.143910E+09
October 92475413.30 0.00 92475413.30 44183648.63 0.206450E+09
November 53771554.59 0.00 53771554.59 8420373.53 0.251274E+09
December 37838893.74 0.00 37838893.74 596211.63 0.326823E+09
           
Annual Sum or Average 0.165095E+10 46227893.14 0.160473E+10 0.113387E+10 0.231734E+10
Minimum of Months 37838893.74 0.00 37838893.74 596211.63 93118212.80
Maximum of Months 0.246156E+09 15397270.00 0.230758E+09 0.230665E+09 0.326823E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_6_FLR_3_WALL_EAST_WINDOW

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.198462E+09 79042420.23 0.119420E+09 0.120334E+09 0.526279E+09
February 0.270698E+09 0.100866E+09 0.169832E+09 0.184819E+09 0.447567E+09
March 0.311380E+09 61414734.22 0.249966E+09 0.203623E+09 0.403732E+09
April 0.807271E+09 0.378498E+09 0.428772E+09 0.862454E+09 0.305815E+09
May 0.878305E+09 0.383093E+09 0.495212E+09 0.913085E+09 0.271014E+09
June 0.841083E+09 0.335996E+09 0.505087E+09 0.934956E+09 0.193086E+09
July 0.887034E+09 0.376787E+09 0.510247E+09 0.103088E+10 0.178623E+09
August 0.842638E+09 0.403400E+09 0.439238E+09 0.100476E+10 0.192224E+09
September 0.732111E+09 0.389014E+09 0.343096E+09 0.843449E+09 0.252892E+09
October 0.367956E+09 0.153873E+09 0.214083E+09 0.340172E+09 0.371286E+09
November 0.184287E+09 62706204.31 0.121580E+09 0.111802E+09 0.449053E+09
December 0.141644E+09 53003264.31 88640916.87 73260550.40 0.583509E+09
           
Annual Sum or Average 0.646287E+10 0.277770E+10 0.368517E+10 0.662359E+10 0.417508E+10
Minimum of Months 0.141644E+09 53003264.31 88640916.87 73260550.40 0.178623E+09
Maximum of Months 0.887034E+09 0.403400E+09 0.510247E+09 0.103088E+10 0.583509E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 66229772.74 0.00 66229772.74 5100125.80 0.407707E+09
February 93412162.03 0.00 93412162.03 14266772.54 0.341635E+09
March 0.143130E+09 967.39 0.143129E+09 53853262.42 0.301235E+09
April 0.226335E+09 1504274.40 0.224831E+09 0.167162E+09 0.219448E+09
May 0.292407E+09 14911094.62 0.277496E+09 0.221343E+09 0.179990E+09
June 0.311741E+09 19499670.94 0.292241E+09 0.301777E+09 0.125792E+09
July 0.306286E+09 18014397.76 0.288272E+09 0.318477E+09 0.116534E+09
August 0.241146E+09 4509687.32 0.236636E+09 0.248174E+09 0.129321E+09
September 0.177008E+09 104617.41 0.176903E+09 0.156064E+09 0.181214E+09
October 0.117114E+09 0.00 0.117114E+09 57387090.36 0.272706E+09
November 68098281.09 0.00 68098281.09 8446420.20 0.342367E+09
December 47920571.43 0.00 47920571.43 213442.30 0.449076E+09
           
Annual Sum or Average 0.209083E+10 58544709.85 0.203228E+10 0.155226E+10 0.306702E+10
Minimum of Months 47920571.43 0.00 47920571.43 213442.30 0.116534E+09
Maximum of Months 0.311741E+09 19499670.94 0.292241E+09 0.318477E+09 0.449076E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 24415036.59 0.00 24415036.59 1880117.55 0.150298E+09
February 34435590.82 0.00 34435590.82 5259323.10 0.125941E+09
March 52763527.24 356.62 52763170.61 19852542.42 0.111048E+09
April 83436499.74 554537.83 82881961.91 61622842.00 80897459.78
May 0.107793E+09 5496846.90 0.102297E+09 81596345.24 66351637.67
June 0.114921E+09 7188386.13 0.107732E+09 0.111247E+09 46372209.58
July 0.112910E+09 6640852.93 0.106269E+09 0.117404E+09 42959264.91
August 88896459.85 1662457.48 87234002.37 91487312.50 47673088.56
September 65252479.21 38566.31 65213912.90 57531756.62 66802851.80
October 43173171.48 0.00 43173171.48 21155257.72 0.100531E+09
November 25103846.14 0.00 25103846.14 3113700.22 0.126211E+09
December 17665506.86 0.00 17665506.86 78683.67 0.165548E+09
           
Annual Sum or Average 0.770766E+09 21582004.20 0.749184E+09 0.572229E+09 0.113063E+10
Minimum of Months 17665506.86 0.00 17665506.86 78683.67 42959264.91
Maximum of Months 0.114921E+09 7188386.13 0.107732E+09 0.117404E+09 0.165548E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.139266E+09 90183137.34 49082764.60 0.140092E+09 0.132374E+09
February 0.152638E+09 93029421.80 59608931.11 0.157553E+09 0.115376E+09
March 0.104303E+09 30150528.10 74152630.13 87699571.68 0.106592E+09
April 0.206918E+09 91685143.13 0.115233E+09 0.243235E+09 82328392.75
May 0.179248E+09 58065761.49 0.121182E+09 0.197256E+09 73139575.53
June 0.160127E+09 38726197.32 0.121400E+09 0.187050E+09 50511708.82
July 0.178352E+09 55176861.55 0.123175E+09 0.223469E+09 46772860.82
August 0.209476E+09 93855004.78 0.115621E+09 0.273225E+09 50225077.00
September 0.242935E+09 0.143382E+09 99553201.59 0.309252E+09 65629877.96
October 0.167504E+09 96570534.75 70933434.58 0.189205E+09 96121472.20
November 0.117059E+09 71185959.25 45873176.30 0.118501E+09 0.116755E+09
December 95988358.37 61550378.44 34437979.94 93013841.02 0.152421E+09
           
Annual Sum or Average 0.195381E+10 0.923561E+09 0.103025E+10 0.221955E+10 0.108825E+10
Minimum of Months 95988358.37 30150528.10 34437979.94 87699571.68 46772860.82
Maximum of Months 0.242935E+09 0.143382E+09 0.123175E+09 0.309252E+09 0.152421E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.377996E+09 0.244775E+09 0.133221E+09 0.380238E+09 0.359290E+09
February 0.414292E+09 0.252501E+09 0.161791E+09 0.427630E+09 0.313154E+09
March 0.283100E+09 81834700.42 0.201265E+09 0.238035E+09 0.289313E+09
April 0.561618E+09 0.248852E+09 0.312766E+09 0.660191E+09 0.223456E+09
May 0.486515E+09 0.157602E+09 0.328912E+09 0.535393E+09 0.198516E+09
June 0.434616E+09 0.105111E+09 0.329506E+09 0.507691E+09 0.137099E+09
July 0.484084E+09 0.149761E+09 0.334322E+09 0.606541E+09 0.126951E+09
August 0.568561E+09 0.254742E+09 0.313819E+09 0.741589E+09 0.136321E+09
September 0.659375E+09 0.389167E+09 0.270208E+09 0.839374E+09 0.178133E+09
October 0.454640E+09 0.262112E+09 0.192528E+09 0.513540E+09 0.260893E+09
November 0.317722E+09 0.193213E+09 0.124509E+09 0.321637E+09 0.316898E+09
December 0.260532E+09 0.167060E+09 93471721.68 0.252459E+09 0.413702E+09
           
Annual Sum or Average 0.530305E+10 0.250673E+10 0.279632E+10 0.602432E+10 0.295373E+10
Minimum of Months 0.260532E+09 81834700.42 93471721.68 0.238035E+09 0.126951E+09
Maximum of Months 0.659375E+09 0.389167E+09 0.334322E+09 0.839374E+09 0.413702E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.298472E+09 0.193279E+09 0.105193E+09 0.302417E+09 0.266109E+09
February 0.327132E+09 0.199379E+09 0.127753E+09 0.336859E+09 0.235504E+09
March 0.223541E+09 64618063.64 0.158923E+09 0.189720E+09 0.216298E+09
April 0.443463E+09 0.196498E+09 0.246965E+09 0.504645E+09 0.177274E+09
May 0.384160E+09 0.124445E+09 0.259715E+09 0.403837E+09 0.159302E+09
June 0.343181E+09 82997281.99 0.260183E+09 0.376917E+09 0.112562E+09
July 0.382241E+09 0.118254E+09 0.263986E+09 0.452778E+09 0.104691E+09
August 0.448945E+09 0.201148E+09 0.247797E+09 0.561030E+09 0.112189E+09
September 0.520653E+09 0.307293E+09 0.213361E+09 0.643478E+09 0.143711E+09
October 0.358991E+09 0.206968E+09 0.152023E+09 0.399437E+09 0.198570E+09
November 0.250879E+09 0.152564E+09 98314557.38 0.254581E+09 0.234289E+09
December 0.205721E+09 0.131914E+09 73806852.46 0.202125E+09 0.302728E+09
           
Annual Sum or Average 0.418738E+10 0.197936E+10 0.220802E+10 0.462783E+10 0.226323E+10
Minimum of Months 0.205721E+09 64618063.64 73806852.46 0.189720E+09 0.104691E+09
Maximum of Months 0.520653E+09 0.307293E+09 0.263986E+09 0.643478E+09 0.302728E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_1_FLR_6_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.195660E+09 64128920.97 0.131532E+09 0.119939E+09 0.534524E+09
February 0.312615E+09 0.133073E+09 0.179541E+09 0.246297E+09 0.460583E+09
March 0.311355E+09 59870921.37 0.251484E+09 0.202868E+09 0.404608E+09
April 0.709636E+09 0.281355E+09 0.428281E+09 0.731495E+09 0.321543E+09
May 0.860491E+09 0.349933E+09 0.510558E+09 0.882604E+09 0.282607E+09
June 0.899047E+09 0.370125E+09 0.528922E+09 0.999152E+09 0.201314E+09
July 0.945570E+09 0.416516E+09 0.529053E+09 0.109862E+10 0.187950E+09
August 0.795714E+09 0.344711E+09 0.451003E+09 0.930308E+09 0.204493E+09
September 0.622261E+09 0.281272E+09 0.340989E+09 0.692641E+09 0.267641E+09
October 0.342754E+09 0.124483E+09 0.218272E+09 0.302906E+09 0.379034E+09
November 0.178958E+09 52801937.15 0.126156E+09 0.111359E+09 0.459825E+09
December 0.103093E+09 20956149.08 82136943.91 37389405.64 0.600122E+09
           
Annual Sum or Average 0.627716E+10 0.249923E+10 0.377793E+10 0.635558E+10 0.430424E+10
Minimum of Months 0.103093E+09 20956149.08 82136943.91 37389405.64 0.187950E+09
Maximum of Months 0.945570E+09 0.416516E+09 0.529053E+09 0.109862E+10 0.600122E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_2_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 52296148.79 0.00 52296148.79 6444896.80 0.293723E+09
February 73759823.15 0.00 73759823.15 15459905.10 0.250999E+09
March 0.113018E+09 763.87 0.113017E+09 46655341.13 0.222740E+09
April 0.178718E+09 1187800.51 0.177530E+09 0.122179E+09 0.171539E+09
May 0.230890E+09 11774052.52 0.219116E+09 0.159030E+09 0.142543E+09
June 0.246156E+09 15397270.00 0.230758E+09 0.215603E+09 0.102248E+09
July 0.241849E+09 14224473.17 0.227624E+09 0.227394E+09 95013658.90
August 0.190413E+09 3560925.39 0.186852E+09 0.176476E+09 0.104793E+09
September 0.139769E+09 82607.68 0.139686E+09 0.113354E+09 0.143302E+09
October 92475413.30 0.00 92475413.30 46463774.55 0.203493E+09
November 53771554.59 0.00 53771554.59 9563912.95 0.247158E+09
December 37838893.74 0.00 37838893.74 909325.64 0.321913E+09
           
Annual Sum or Average 0.165095E+10 46227893.14 0.160473E+10 0.113953E+10 0.229947E+10
Minimum of Months 37838893.74 0.00 37838893.74 909325.64 95013658.90
Maximum of Months 0.246156E+09 15397270.00 0.230758E+09 0.227394E+09 0.321913E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_2_FLR_6_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.195660E+09 64128920.97 0.131532E+09 0.127548E+09 0.528208E+09
February 0.312615E+09 0.133073E+09 0.179541E+09 0.256379E+09 0.453891E+09
March 0.311355E+09 59870921.37 0.251484E+09 0.208422E+09 0.401581E+09
April 0.709636E+09 0.281355E+09 0.428281E+09 0.743933E+09 0.317500E+09
May 0.860491E+09 0.349933E+09 0.510558E+09 0.890622E+09 0.280431E+09
June 0.899047E+09 0.370125E+09 0.528922E+09 0.100368E+10 0.200107E+09
July 0.945570E+09 0.416516E+09 0.529053E+09 0.110415E+10 0.186499E+09
August 0.795714E+09 0.344711E+09 0.451003E+09 0.939435E+09 0.201562E+09
September 0.622261E+09 0.281272E+09 0.340989E+09 0.706659E+09 0.262191E+09
October 0.342754E+09 0.124483E+09 0.218272E+09 0.314420E+09 0.372818E+09
November 0.178958E+09 52801937.15 0.126156E+09 0.118475E+09 0.453830E+09
December 0.103093E+09 20956149.08 82136943.91 40691416.10 0.595664E+09
           
Annual Sum or Average 0.627716E+10 0.249923E+10 0.377793E+10 0.645442E+10 0.425428E+10
Minimum of Months 0.103093E+09 20956149.08 82136943.91 40691416.10 0.186499E+09
Maximum of Months 0.945570E+09 0.416516E+09 0.529053E+09 0.110415E+10 0.595664E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.437738E+09 0.283462E+09 0.154276E+09 0.428844E+09 0.407517E+09
February 0.479770E+09 0.292408E+09 0.187362E+09 0.481938E+09 0.359469E+09
March 0.327844E+09 94768591.74 0.233075E+09 0.268093E+09 0.327567E+09
April 0.650381E+09 0.288183E+09 0.362198E+09 0.733872E+09 0.262774E+09
May 0.563408E+09 0.182511E+09 0.380897E+09 0.590598E+09 0.233879E+09
June 0.503307E+09 0.121723E+09 0.381584E+09 0.556560E+09 0.162928E+09
July 0.560592E+09 0.173431E+09 0.387162E+09 0.667907E+09 0.151275E+09
August 0.658421E+09 0.295003E+09 0.363418E+09 0.822674E+09 0.163813E+09
September 0.763588E+09 0.450674E+09 0.312914E+09 0.937304E+09 0.214043E+09
October 0.526495E+09 0.303539E+09 0.222957E+09 0.575133E+09 0.302648E+09
November 0.367938E+09 0.223750E+09 0.144188E+09 0.362076E+09 0.360724E+09
December 0.301709E+09 0.193464E+09 0.108245E+09 0.286580E+09 0.463935E+09
           
Annual Sum or Average 0.614119E+10 0.290292E+10 0.323827E+10 0.671158E+10 0.341057E+10
Minimum of Months 0.301709E+09 94768591.74 0.108245E+09 0.268093E+09 0.151275E+09
Maximum of Months 0.763588E+09 0.450674E+09 0.387162E+09 0.937304E+09 0.463935E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: BANQUET_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.366059E+09 0.00 0.366059E+09 26497778.32 0.223801E+10
February 0.516299E+09 0.00 0.516299E+09 74382455.92 0.188701E+10
March 0.791093E+09 5346.90 0.791088E+09 0.282911E+09 0.167360E+10
April 0.125098E+10 8314288.68 0.124266E+10 0.891290E+09 0.123233E+10
May 0.161617E+10 82415246.22 0.153375E+10 0.116584E+10 0.104214E+10
June 0.172303E+10 0.107777E+09 0.161525E+10 0.160015E+10 0.748582E+09
July 0.169288E+10 99567541.14 0.159331E+10 0.169814E+10 0.695319E+09
August 0.133284E+10 24925533.69 0.130792E+10 0.133119E+10 0.761643E+09
September 0.978343E+09 578231.83 0.977764E+09 0.842619E+09 0.103235E+10
October 0.647303E+09 0.00 0.647303E+09 0.305403E+09 0.153098E+10
November 0.376387E+09 0.00 0.376387E+09 43798847.09 0.190778E+10
December 0.264862E+09 0.00 0.264862E+09 1050216.35 0.249173E+10
           
Annual Sum or Average 0.115562E+11 0.323583E+09 0.112327E+11 0.826327E+10 0.172415E+11
Minimum of Months 0.264862E+09 0.00 0.264862E+09 1050216.35 0.695319E+09
Maximum of Months 0.172303E+10 0.107777E+09 0.161525E+10 0.169814E+10 0.249173E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: DINING_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.366059E+09 0.00 0.366059E+09 23962966.92 0.228060E+10
February 0.516299E+09 0.00 0.516299E+09 69061034.79 0.192336E+10
March 0.791093E+09 5346.90 0.791088E+09 0.271905E+09 0.171042E+10
April 0.125098E+10 8314288.68 0.124266E+10 0.871816E+09 0.126026E+10
May 0.161617E+10 82415246.22 0.153375E+10 0.113799E+10 0.106719E+10
June 0.172303E+10 0.107777E+09 0.161525E+10 0.157013E+10 0.771208E+09
July 0.169288E+10 99567541.14 0.159331E+10 0.166592E+10 0.717867E+09
August 0.133284E+10 24925533.69 0.130792E+10 0.130486E+10 0.787524E+09
September 0.978343E+09 578231.83 0.977764E+09 0.824276E+09 0.106183E+10
October 0.647303E+09 0.00 0.647303E+09 0.294559E+09 0.156870E+10
November 0.376387E+09 0.00 0.376387E+09 40115672.81 0.195028E+10
December 0.264862E+09 0.00 0.264862E+09 720839.11 0.253811E+10
           
Annual Sum or Average 0.115562E+11 0.323583E+09 0.112327E+11 0.807531E+10 0.176373E+11
Minimum of Months 0.264862E+09 0.00 0.264862E+09 720839.11 0.717867E+09
Maximum of Months 0.172303E+10 0.107777E+09 0.161525E+10 0.166592E+10 0.253811E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: KITCHEN_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 52296148.79 0.00 52296148.79 11197718.70 0.275451E+09
February 73759823.15 0.00 73759823.15 22022363.95 0.238750E+09
March 0.113018E+09 763.87 0.113017E+09 63645869.80 0.211603E+09
April 0.178718E+09 1187800.51 0.177530E+09 0.158808E+09 0.165054E+09
May 0.230890E+09 11774052.52 0.219116E+09 0.202687E+09 0.146637E+09
June 0.246156E+09 15397270.00 0.230758E+09 0.269392E+09 0.106315E+09
July 0.241849E+09 14224473.17 0.227624E+09 0.286452E+09 99676313.38
August 0.190413E+09 3560925.39 0.186852E+09 0.228821E+09 0.105466E+09
September 0.139769E+09 82607.68 0.139686E+09 0.148719E+09 0.137241E+09
October 92475413.30 0.00 92475413.30 64467538.57 0.194855E+09
November 53771554.59 0.00 53771554.59 15609586.83 0.236142E+09
December 37838893.74 0.00 37838893.74 2809468.21 0.311066E+09
           
Annual Sum or Average 0.165095E+10 46227893.14 0.160473E+10 0.147463E+10 0.222826E+10
Minimum of Months 37838893.74 0.00 37838893.74 2809468.21 99676313.38
Maximum of Months 0.246156E+09 15397270.00 0.230758E+09 0.286452E+09 0.311066E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: KITCHEN_FLR_6_WALL_EAST_WINDOW

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.396896E+09 0.158074E+09 0.238823E+09 0.283392E+09 0.985564E+09
February 0.541358E+09 0.201718E+09 0.339640E+09 0.416486E+09 0.856063E+09
March 0.622717E+09 0.122821E+09 0.499896E+09 0.492152E+09 0.767910E+09
April 0.161443E+10 0.756943E+09 0.857483E+09 0.189453E+10 0.600771E+09
May 0.175648E+10 0.766132E+09 0.990353E+09 0.199746E+10 0.559899E+09
June 0.168205E+10 0.671945E+09 0.101010E+10 0.206165E+10 0.405408E+09
July 0.177394E+10 0.753521E+09 0.102042E+10 0.227363E+10 0.377811E+09
August 0.168516E+10 0.806743E+09 0.878414E+09 0.221398E+10 0.394879E+09
September 0.146412E+10 0.777974E+09 0.686144E+09 0.185413E+10 0.497441E+09
October 0.735860E+09 0.307724E+09 0.428136E+09 0.773664E+09 0.711998E+09
November 0.368547E+09 0.125404E+09 0.243143E+09 0.264021E+09 0.853999E+09
December 0.283268E+09 0.105999E+09 0.177269E+09 0.172324E+09 0.112652E+10
           
Annual Sum or Average 0.129248E+11 0.555500E+10 0.736983E+10 0.146974E+11 0.813827E+10
Minimum of Months 0.283268E+09 0.105999E+09 0.177269E+09 0.172324E+09 0.377811E+09
Maximum of Months 0.177394E+10 0.806743E+09 0.102042E+10 0.227363E+10 0.112652E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.298472E+09 0.193279E+09 0.105193E+09 0.322269E+09 0.251229E+09
February 0.327132E+09 0.199379E+09 0.127753E+09 0.359331E+09 0.225206E+09
March 0.223541E+09 64618063.64 0.158923E+09 0.214922E+09 0.206907E+09
April 0.443463E+09 0.196498E+09 0.246965E+09 0.552299E+09 0.168399E+09
May 0.384160E+09 0.124445E+09 0.259715E+09 0.452413E+09 0.158634E+09
June 0.343181E+09 82997281.99 0.260183E+09 0.433089E+09 0.113190E+09
July 0.382241E+09 0.118254E+09 0.263986E+09 0.514612E+09 0.105399E+09
August 0.448945E+09 0.201148E+09 0.247797E+09 0.620417E+09 0.109330E+09
September 0.520653E+09 0.307293E+09 0.213361E+09 0.693937E+09 0.136454E+09
October 0.358991E+09 0.206968E+09 0.152023E+09 0.431693E+09 0.189964E+09
November 0.250879E+09 0.152564E+09 98314557.38 0.271668E+09 0.224372E+09
December 0.205721E+09 0.131914E+09 73806852.46 0.212650E+09 0.294591E+09
           
Annual Sum or Average 0.418738E+10 0.197936E+10 0.220802E+10 0.507930E+10 0.218368E+10
Minimum of Months 0.205721E+09 64618063.64 73806852.46 0.212650E+09 0.105399E+09
Maximum of Months 0.520653E+09 0.307293E+09 0.263986E+09 0.693937E+09 0.294591E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 66229772.74 0.00 66229772.74 4449959.98 0.408268E+09
February 93412162.03 0.00 93412162.03 12584436.32 0.343026E+09
March 0.143130E+09 967.39 0.143129E+09 51235960.81 0.302038E+09
April 0.226335E+09 1504274.40 0.224831E+09 0.159777E+09 0.220599E+09
May 0.292407E+09 14911094.62 0.277496E+09 0.212244E+09 0.182051E+09
June 0.311741E+09 19499670.94 0.292241E+09 0.291972E+09 0.127645E+09
July 0.306286E+09 18014397.76 0.288272E+09 0.308828E+09 0.117733E+09
August 0.241146E+09 4509687.32 0.236636E+09 0.239876E+09 0.130351E+09
September 0.177008E+09 104617.41 0.176903E+09 0.150009E+09 0.182314E+09
October 0.117114E+09 0.00 0.117114E+09 54101310.62 0.274558E+09
November 68098281.09 0.00 68098281.09 7438444.96 0.344330E+09
December 47920571.43 0.00 47920571.43 140529.17 0.450933E+09
           
Annual Sum or Average 0.209083E+10 58544709.85 0.203228E+10 0.149266E+10 0.308385E+10
Minimum of Months 47920571.43 0.00 47920571.43 140529.17 0.117733E+09
Maximum of Months 0.311741E+09 19499670.94 0.292241E+09 0.308828E+09 0.450933E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 59256028.61 0.00 59256028.61 3981396.06 0.365205E+09
February 83576215.31 0.00 83576215.31 11259342.86 0.306906E+09
March 0.128059E+09 865.53 0.128058E+09 45841008.27 0.270235E+09
April 0.202503E+09 1345880.01 0.201157E+09 0.142953E+09 0.197371E+09
May 0.261618E+09 13341012.85 0.248277E+09 0.189896E+09 0.162881E+09
June 0.278916E+09 17446429.47 0.261469E+09 0.261228E+09 0.114205E+09
July 0.274036E+09 16117549.93 0.257918E+09 0.276309E+09 0.105336E+09
August 0.215754E+09 4034834.34 0.211720E+09 0.214618E+09 0.116626E+09
September 0.158370E+09 93601.59 0.158276E+09 0.134214E+09 0.163117E+09
October 0.104783E+09 0.00 0.104783E+09 48404647.60 0.245648E+09
November 60927790.11 0.00 60927790.11 6655204.89 0.308052E+09
December 42874716.83 0.00 42874716.83 125731.98 0.403401E+09
           
Annual Sum or Average 0.187067E+10 52380173.73 0.181829E+10 0.133549E+10 0.275898E+10
Minimum of Months 42874716.83 0.00 42874716.83 125731.98 0.105336E+09
Maximum of Months 0.278916E+09 17446429.47 0.261469E+09 0.276309E+09 0.403401E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.111429E+10 0.721568E+09 0.392718E+09 0.111268E+10 0.105939E+10
February 0.122128E+10 0.744341E+09 0.476939E+09 0.124969E+10 0.927076E+09
March 0.834544E+09 0.241238E+09 0.593305E+09 0.690428E+09 0.855913E+09
April 0.165558E+10 0.733585E+09 0.921994E+09 0.192134E+10 0.663471E+09
May 0.143418E+10 0.464592E+09 0.969593E+09 0.155054E+10 0.593987E+09
June 0.128120E+10 0.309854E+09 0.971342E+09 0.146751E+10 0.411673E+09
July 0.142702E+10 0.441478E+09 0.985540E+09 0.175790E+10 0.379599E+09
August 0.167605E+10 0.750947E+09 0.925100E+09 0.215753E+10 0.406181E+09
September 0.194375E+10 0.114722E+10 0.796539E+09 0.244985E+10 0.529464E+09
October 0.134022E+10 0.772674E+09 0.567548E+09 0.149945E+10 0.775929E+09
November 0.936606E+09 0.569569E+09 0.367038E+09 0.939508E+09 0.940680E+09
December 0.768016E+09 0.492473E+09 0.275543E+09 0.738469E+09 0.122662E+10
           
Annual Sum or Average 0.156327E+11 0.738953E+10 0.824320E+10 0.175349E+11 0.876998E+10
Minimum of Months 0.768016E+09 0.241238E+09 0.275543E+09 0.690428E+09 0.379599E+09
Maximum of Months 0.194375E+10 0.114722E+10 0.985540E+09 0.244985E+10 0.122662E+10



Table of Contents

Report: WindowZoneSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 563.58 505.50 563.62 364.98 198.64 0.00 0.00
February 701.24 488.32 683.92 416.83 267.09 0.00 0.00
March 355.57 407.44 422.12 122.02 300.10 0.00 0.00
April 1002.76 332.88 865.32 383.42 481.90 0.00 0.00
May 790.01 282.58 725.42 235.00 490.43 0.00 0.00
June 770.09 204.28 669.64 161.95 507.69 0.00 0.00
July 888.76 184.21 721.80 223.30 498.49 0.00 0.00
August 1085.41 201.23 847.76 379.84 467.92 0.00 0.00
September 1272.02 269.39 1015.94 599.62 416.32 0.00 0.00
October 756.45 371.25 677.90 390.83 287.07 0.00 0.00
November 493.20 458.89 489.54 297.70 191.84 0.00 0.00
December 376.12 569.67 388.47 249.10 139.37 0.00 0.00
               
Annual Sum or Average 753.62 355.66 671.57 317.45 354.12 0.00 0.00
Minimum of Months 355.57 184.21 388.47 122.02 139.37 0.00 0.00
Maximum of Months 1272.02 569.67 1015.94 599.62 507.69 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 1575.35 1434.16 1587.11 1027.75 559.36 0.00 0.00
February 1962.04 1382.30 1925.88 1173.78 752.10 0.00 0.00
March 987.72 1151.32 1188.66 343.60 845.06 0.00 0.00
April 2811.49 931.35 2436.68 1079.69 1356.99 0.00 0.00
May 2211.20 790.38 2042.74 661.73 1381.00 0.00 0.00
June 2156.80 567.10 1885.66 456.04 1429.61 0.00 0.00
July 2492.80 510.38 2032.53 628.81 1403.72 0.00 0.00
August 3048.21 558.05 2387.23 1069.59 1317.63 0.00 0.00
September 3573.39 751.71 2860.82 1688.48 1172.34 0.00 0.00
October 2119.76 1047.84 1908.91 1100.54 808.37 0.00 0.00
November 1379.13 1303.27 1378.50 838.29 540.21 0.00 0.00
December 1050.28 1628.55 1093.90 701.44 392.46 0.00 0.00
               
Annual Sum or Average 2111.25 1002.87 1891.09 893.91 997.17 0.00 0.00
Minimum of Months 987.72 510.38 1093.90 343.60 392.46 0.00 0.00
Maximum of Months 3573.39 1628.55 2860.82 1688.48 1429.61 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 2074.05 1920.53 2061.74 1335.10 726.64 0.00 0.00
February 2586.31 1843.63 2501.82 1524.80 977.02 0.00 0.00
March 1304.86 1546.67 1544.14 446.36 1097.78 0.00 0.00
April 3725.87 1238.41 3165.39 1402.59 1762.80 0.00 0.00
May 2935.78 1055.26 2653.63 859.63 1794.00 0.00 0.00
June 2867.73 761.90 2449.58 592.43 1857.15 0.00 0.00
July 3311.00 685.72 2640.37 816.86 1823.51 0.00 0.00
August 4041.69 745.02 3101.14 1389.46 1711.68 0.00 0.00
September 4732.38 994.91 3716.37 2193.43 1522.94 0.00 0.00
October 2801.04 1397.81 2479.78 1429.67 1050.12 0.00 0.00
November 1816.30 1745.41 1790.75 1088.99 701.76 0.00 0.00
December 1379.54 2191.37 1421.04 911.21 509.83 0.00 0.00
               
Annual Sum or Average 2794.44 1341.52 2456.63 1161.25 1295.39 0.00 0.00
Minimum of Months 1304.86 685.72 1421.04 446.36 509.83 0.00 0.00
Maximum of Months 4732.38 2191.37 3716.37 2193.43 1857.15 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 147.64 294.96 184.49 96.11 88.38 0.00 0.00
February 236.11 286.80 264.45 137.42 127.02 0.00 0.00
March 144.30 233.63 199.71 46.48 153.23 0.00 0.00
April 479.67 191.36 444.87 184.36 260.51 0.00 0.00
May 483.86 162.20 464.70 177.11 287.59 0.00 0.00
June 537.06 119.25 479.25 174.82 304.44 0.00 0.00
July 585.41 107.40 495.75 199.66 296.09 0.00 0.00
August 562.23 117.17 464.70 203.80 260.90 0.00 0.00
September 518.53 157.53 440.94 227.07 213.87 0.00 0.00
October 260.77 216.28 262.00 123.75 138.25 0.00 0.00
November 135.52 267.13 165.83 79.23 86.60 0.00 0.00
December 80.76 333.35 115.30 57.08 58.22 0.00 0.00
               
Annual Sum or Average 347.80 206.86 331.83 142.02 189.81 0.00 0.00
Minimum of Months 80.76 107.40 115.30 46.48 58.22 0.00 0.00
Maximum of Months 585.41 333.35 495.75 227.07 304.44 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 45.62 308.74 92.58 23.94 68.63 0.00 0.00
February 108.80 292.83 159.71 55.01 104.70 0.00 0.00
March 92.56 235.02 158.44 22.35 136.09 0.00 0.00
April 336.94 188.27 342.73 109.01 233.72 0.00 0.00
May 395.84 155.81 407.47 135.05 272.43 0.00 0.00
June 476.01 114.11 441.82 148.74 293.09 0.00 0.00
July 503.01 102.89 443.33 160.82 282.51 0.00 0.00
August 422.02 113.38 368.18 130.03 238.15 0.00 0.00
September 319.01 155.92 293.99 108.55 185.45 0.00 0.00
October 133.57 217.32 162.50 46.48 116.02 0.00 0.00
November 47.01 273.81 89.79 20.37 69.42 0.00 0.00
December 14.04 346.09 52.62 7.82 44.79 0.00 0.00
               
Annual Sum or Average 241.70 208.27 251.40 80.72 170.68 0.00 0.00
Minimum of Months 14.04 102.89 52.62 7.82 44.79 0.00 0.00
Maximum of Months 503.01 346.09 443.33 160.82 293.09 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 86.79 88.91 89.13 57.72 31.41 0.00 0.00
February 108.09 87.07 108.16 65.92 42.24 0.00 0.00
March 53.64 71.54 66.76 19.30 47.46 0.00 0.00
April 153.33 62.45 136.84 60.64 76.21 0.00 0.00
May 118.48 54.57 114.72 37.16 77.56 0.00 0.00
June 114.92 40.73 105.90 25.61 80.29 0.00 0.00
July 134.03 37.12 114.15 35.31 78.83 0.00 0.00
August 166.15 40.28 134.07 60.07 74.00 0.00 0.00
September 196.37 52.45 160.66 94.82 65.84 0.00 0.00
October 116.03 69.99 107.20 61.81 45.40 0.00 0.00
November 75.52 83.21 77.42 47.08 30.34 0.00 0.00
December 59.28 92.93 61.43 39.39 22.04 0.00 0.00
               
Annual Sum or Average 115.06 64.98 106.20 50.20 56.00 0.00 0.00
Minimum of Months 53.64 37.12 61.43 19.30 22.04 0.00 0.00
Maximum of Months 196.37 92.93 160.66 94.82 80.29 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 1.26 94.82 15.62 0.00 15.62 0.00 0.00
February 3.93 88.36 24.39 0.00 24.39 0.00 0.00
March 12.36 71.18 33.76 0.00 33.76 0.00 0.00
April 39.68 53.76 55.17 0.37 54.80 0.00 0.00
May 50.37 42.91 68.97 3.52 65.46 0.00 0.00
June 70.88 31.20 75.98 4.75 71.23 0.00 0.00
July 72.54 27.85 72.25 4.25 68.00 0.00 0.00
August 56.69 30.75 56.88 1.06 55.82 0.00 0.00
September 37.08 44.35 43.14 0.03 43.12 0.00 0.00
October 13.27 64.60 27.62 0.00 27.62 0.00 0.00
November 2.10 82.98 16.60 0.00 16.60 0.00 0.00
December 0.07 104.41 11.30 0.00 11.30 0.00 0.00
               
Annual Sum or Average 30.15 61.30 41.89 1.17 40.71 0.00 0.00
Minimum of Months 0.07 27.85 11.30 0.00 11.30 0.00 0.00
Maximum of Months 72.54 104.41 75.98 4.75 71.23 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 147.98 293.41 185.53 101.67 83.86 0.00 0.00
February 208.39 282.52 247.12 124.11 123.01 0.00 0.00
March 142.92 232.12 199.72 47.06 152.66 0.00 0.00
April 519.21 183.83 482.54 221.84 260.70 0.00 0.00
May 485.88 157.10 471.35 189.49 281.86 0.00 0.00
June 504.07 115.37 456.89 161.65 295.24 0.00 0.00
July 551.73 103.54 473.89 184.83 289.07 0.00 0.00
August 580.48 111.93 482.22 225.71 256.51 0.00 0.00
September 567.14 152.23 483.32 268.64 214.68 0.00 0.00
October 270.88 214.44 271.41 134.72 136.69 0.00 0.00
November 136.18 265.04 167.89 83.05 84.84 0.00 0.00
December 97.84 331.55 129.69 69.04 60.65 0.00 0.00
               
Annual Sum or Average 351.35 203.21 337.72 150.85 186.87 0.00 0.00
Minimum of Months 97.84 103.54 129.69 47.06 60.65 0.00 0.00
Maximum of Months 580.48 331.55 483.32 268.64 295.24 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 41.70 302.68 93.62 29.51 64.11 0.00 0.00
February 77.81 285.26 142.39 41.69 100.69 0.00 0.00
March 90.52 232.91 158.45 22.93 135.52 0.00 0.00
April 375.50 181.09 380.40 146.48 233.91 0.00 0.00
May 398.29 152.00 414.13 147.43 266.70 0.00 0.00
June 444.24 112.09 419.46 135.57 283.89 0.00 0.00
July 469.97 100.42 421.48 145.99 275.49 0.00 0.00
August 440.31 109.56 385.70 151.94 233.76 0.00 0.00
September 364.66 149.75 336.37 150.11 186.26 0.00 0.00
October 140.83 213.03 171.91 57.45 114.46 0.00 0.00
November 42.93 266.74 91.84 24.19 67.65 0.00 0.00
December 22.91 335.21 67.01 19.79 47.22 0.00 0.00
               
Annual Sum or Average 243.12 203.01 257.29 89.55 167.74 0.00 0.00
Minimum of Months 22.91 100.42 67.01 19.79 47.22 0.00 0.00
Maximum of Months 469.97 335.21 421.48 151.94 283.89 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 179.32 374.35 226.97 125.06 101.91 0.00 0.00
February 240.94 361.39 287.19 142.83 144.36 0.00 0.00
March 146.91 299.52 217.78 41.81 175.97 0.00 0.00
April 436.44 233.47 416.01 132.17 283.84 0.00 0.00
May 382.79 189.55 397.98 88.14 309.84 0.00 0.00
June 424.13 135.55 394.06 65.79 328.27 0.00 0.00
July 469.76 121.54 403.83 85.72 318.11 0.00 0.00
August 504.65 134.67 413.71 132.46 281.25 0.00 0.00
September 524.80 188.98 441.58 205.51 236.06 0.00 0.00
October 288.78 269.73 292.13 133.92 158.21 0.00 0.00
November 165.63 339.44 203.70 102.01 101.69 0.00 0.00
December 116.31 428.06 157.60 85.35 72.24 0.00 0.00
               
Annual Sum or Average 323.34 255.84 320.85 111.31 209.54 0.00 0.00
Minimum of Months 116.31 121.54 157.60 41.81 72.24 0.00 0.00
Maximum of Months 524.80 428.06 441.58 205.51 328.27 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 148.72 289.95 184.49 96.11 88.38 0.00 0.00
February 236.59 283.27 264.45 137.42 127.02 0.00 0.00
March 144.69 229.94 199.71 46.48 153.23 0.00 0.00
April 474.80 190.34 444.87 184.36 260.51 0.00 0.00
May 477.71 162.39 464.70 177.11 287.59 0.00 0.00
June 529.66 119.86 479.25 174.82 304.44 0.00 0.00
July 577.94 107.98 495.75 199.66 296.09 0.00 0.00
August 555.86 117.29 464.70 203.80 260.90 0.00 0.00
September 514.03 157.25 440.94 227.07 213.87 0.00 0.00
October 260.03 213.45 262.00 123.75 138.25 0.00 0.00
November 136.24 262.85 165.83 79.23 86.60 0.00 0.00
December 81.51 329.17 115.30 57.08 58.22 0.00 0.00
               
Annual Sum or Average 344.95 204.92 331.83 142.02 189.81 0.00 0.00
Minimum of Months 81.51 107.98 115.30 46.48 58.22 0.00 0.00
Maximum of Months 577.94 329.17 495.75 227.07 304.44 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 46.50 303.35 92.58 23.94 68.63 0.00 0.00
February 109.66 288.66 159.71 55.01 104.70 0.00 0.00
March 93.25 231.11 158.44 22.35 136.09 0.00 0.00
April 332.49 187.02 342.73 109.01 233.72 0.00 0.00
May 389.89 155.92 407.47 135.05 272.43 0.00 0.00
June 468.47 114.71 441.82 148.74 293.09 0.00 0.00
July 495.50 103.46 443.33 160.82 282.51 0.00 0.00
August 415.72 113.46 368.18 130.03 238.15 0.00 0.00
September 315.24 155.31 293.99 108.55 185.45 0.00 0.00
October 133.46 213.89 162.50 46.48 116.02 0.00 0.00
November 47.94 268.98 89.79 20.37 69.42 0.00 0.00
December 14.47 341.52 52.62 7.82 44.79 0.00 0.00
               
Annual Sum or Average 239.03 206.05 251.40 80.72 170.68 0.00 0.00
Minimum of Months 14.47 103.46 52.62 7.82 44.79 0.00 0.00
Maximum of Months 495.50 341.52 443.33 160.82 293.09 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 160.11 152.15 163.43 105.83 57.60 0.00 0.00
February 199.21 148.59 198.32 120.87 77.45 0.00 0.00
March 100.09 122.30 122.40 35.38 87.02 0.00 0.00
April 283.13 101.38 250.92 111.18 139.74 0.00 0.00
May 220.50 87.32 210.35 68.14 142.21 0.00 0.00
June 214.72 62.86 194.18 46.96 147.22 0.00 0.00
July 249.37 56.48 209.30 64.75 144.55 0.00 0.00
August 307.15 61.16 245.83 110.14 135.68 0.00 0.00
September 361.61 82.58 294.59 173.87 120.72 0.00 0.00
October 214.73 113.00 196.57 113.33 83.24 0.00 0.00
November 139.69 139.17 141.95 86.32 55.63 0.00 0.00
December 107.00 173.21 112.65 72.23 40.41 0.00 0.00
               
Annual Sum or Average 212.82 108.15 194.74 92.05 102.68 0.00 0.00
Minimum of Months 100.09 56.48 112.65 35.38 40.41 0.00 0.00
Maximum of Months 361.61 173.21 294.59 173.87 147.22 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 9.89 835.58 136.67 0.00 136.67 0.00 0.00
February 30.75 780.02 213.42 0.00 213.42 0.00 0.00
March 105.63 624.85 295.36 0.00 295.36 0.00 0.00
April 343.86 475.44 482.63 3.21 479.42 0.00 0.00
May 435.27 389.09 603.41 30.77 572.64 0.00 0.00
June 617.34 288.80 664.75 41.58 623.17 0.00 0.00
July 634.01 259.60 632.05 37.17 594.87 0.00 0.00
August 497.01 284.36 497.63 9.31 488.32 0.00 0.00
September 325.08 398.28 377.45 0.22 377.22 0.00 0.00
October 114.02 571.60 241.68 0.00 241.68 0.00 0.00
November 16.90 736.03 145.21 0.00 145.21 0.00 0.00
December 0.39 930.31 98.89 0.00 98.89 0.00 0.00
               
Annual Sum or Average 262.03 546.72 366.45 10.26 356.19 0.00 0.00
Minimum of Months 0.39 259.60 98.89 0.00 98.89 0.00 0.00
Maximum of Months 634.01 930.31 664.75 41.58 623.17 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 8.95 851.48 136.67 0.00 136.67 0.00 0.00
February 28.55 795.04 213.42 0.00 213.42 0.00 0.00
March 101.52 638.60 295.36 0.00 295.36 0.00 0.00
April 336.35 486.21 482.63 3.21 479.42 0.00 0.00
May 424.87 398.44 603.41 30.77 572.64 0.00 0.00
June 605.76 297.53 664.75 41.58 623.17 0.00 0.00
July 621.98 268.02 632.05 37.17 594.87 0.00 0.00
August 487.18 294.03 497.63 9.31 488.32 0.00 0.00
September 318.01 409.65 377.45 0.22 377.22 0.00 0.00
October 109.98 585.69 241.68 0.00 241.68 0.00 0.00
November 15.48 752.42 145.21 0.00 145.21 0.00 0.00
December 0.27 947.62 98.89 0.00 98.89 0.00 0.00
               
Annual Sum or Average 256.07 559.28 366.45 10.26 356.19 0.00 0.00
Minimum of Months 0.27 268.02 98.89 0.00 98.89 0.00 0.00
Maximum of Months 621.98 947.62 664.75 41.58 623.17 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 214.49 548.79 279.15 131.18 147.97 0.00 0.00
February 322.48 538.33 389.49 165.80 223.69 0.00 0.00
March 284.89 440.09 358.15 69.98 288.17 0.00 0.00
April 1000.44 355.60 862.89 368.30 494.59 0.00 0.00
May 985.45 318.11 885.43 336.90 548.53 0.00 0.00
June 1063.75 238.43 876.31 297.20 579.11 0.00 0.00
July 1145.56 215.23 895.32 330.79 564.53 0.00 0.00
August 1141.79 225.75 867.87 377.63 490.24 0.00 0.00
September 1037.12 294.20 819.65 418.73 400.92 0.00 0.00
October 471.38 406.78 443.30 192.16 251.13 0.00 0.00
November 206.64 501.09 259.72 107.24 152.48 0.00 0.00
December 136.39 638.33 196.69 88.83 107.87 0.00 0.00
               
Annual Sum or Average 668.62 392.71 594.98 240.38 354.60 0.00 0.00
Minimum of Months 136.39 215.23 196.69 69.98 107.87 0.00 0.00
Maximum of Months 1145.56 638.33 895.32 418.73 579.11 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 392.31 658.05 462.88 269.40 193.48 0.00 0.00
February 512.63 638.08 577.99 307.68 270.31 0.00 0.00
March 290.49 529.70 412.83 90.07 322.76 0.00 0.00
April 857.44 416.60 804.17 284.12 520.05 0.00 0.00
May 722.16 343.67 742.31 184.01 558.31 0.00 0.00
June 773.31 245.85 722.16 133.80 588.37 0.00 0.00
July 869.35 219.57 749.45 177.57 571.88 0.00 0.00
August 973.40 242.04 796.35 283.56 512.79 0.00 0.00
September 1053.65 336.37 879.29 442.68 436.62 0.00 0.00
October 593.58 479.40 583.23 288.48 294.74 0.00 0.00
November 354.92 601.62 411.12 219.74 191.38 0.00 0.00
December 256.71 757.83 320.64 183.87 136.78 0.00 0.00
               
Annual Sum or Average 637.18 454.84 621.33 237.84 383.49 0.00 0.00
Minimum of Months 256.71 219.57 320.64 90.07 136.78 0.00 0.00
Maximum of Months 1053.65 757.83 879.29 442.68 588.37 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.150950E+10 0.135393E+10 0.150959E+10 0.977552E+09 0.532037E+09 0.00 0.00
February 0.169645E+10 0.118136E+10 0.165454E+10 0.100840E+10 0.646136E+09 0.00 0.00
March 0.952353E+09 0.109129E+10 0.113060E+10 0.326821E+09 0.803783E+09 0.00 0.00
April 0.259916E+10 0.862828E+09 0.224291E+10 0.993833E+09 0.124907E+10 0.00 0.00
May 0.211598E+10 0.756874E+09 0.194297E+10 0.629412E+09 0.131355E+10 0.00 0.00
June 0.199607E+10 0.529504E+09 0.173570E+10 0.419778E+09 0.131592E+10 0.00 0.00
July 0.238046E+10 0.493387E+09 0.193326E+10 0.598097E+09 0.133516E+10 0.00 0.00
August 0.290717E+10 0.538967E+09 0.227063E+10 0.101735E+10 0.125328E+10 0.00 0.00
September 0.329708E+10 0.698258E+09 0.263332E+10 0.155420E+10 0.107911E+10 0.00 0.00
October 0.202606E+10 0.994367E+09 0.181568E+10 0.104679E+10 0.768888E+09 0.00 0.00
November 0.127837E+10 0.118943E+10 0.126888E+10 0.771630E+09 0.497246E+09 0.00 0.00
December 0.100740E+10 0.152581E+10 0.104048E+10 0.667184E+09 0.373294E+09 0.00 0.00
               
Annual Sum or Average 0.237661E+11 0.112160E+11 0.211785E+11 0.100111E+11 0.111675E+11 0.00 0.00
Minimum of Months 0.952353E+09 0.493387E+09 0.104048E+10 0.326821E+09 0.373294E+09 0.00 0.00
Maximum of Months 0.329708E+10 0.152581E+10 0.263332E+10 0.155420E+10 0.133516E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.421943E+10 0.384126E+10 0.425090E+10 0.275272E+10 0.149818E+10 0.00 0.00
February 0.474657E+10 0.334406E+10 0.465908E+10 0.283960E+10 0.181948E+10 0.00 0.00
March 0.264551E+10 0.308370E+10 0.318371E+10 0.920306E+09 0.226340E+10 0.00 0.00
April 0.728738E+10 0.241406E+10 0.631588E+10 0.279857E+10 0.351731E+10 0.00 0.00
May 0.592249E+10 0.211695E+10 0.547127E+10 0.177238E+10 0.369888E+10 0.00 0.00
June 0.559043E+10 0.146993E+10 0.488762E+10 0.118207E+10 0.370556E+10 0.00 0.00
July 0.667671E+10 0.136701E+10 0.544392E+10 0.168420E+10 0.375972E+10 0.00 0.00
August 0.816433E+10 0.149469E+10 0.639395E+10 0.286480E+10 0.352915E+10 0.00 0.00
September 0.926222E+10 0.194844E+10 0.741524E+10 0.437654E+10 0.303871E+10 0.00 0.00
October 0.567755E+10 0.280653E+10 0.511283E+10 0.294769E+10 0.216514E+10 0.00 0.00
November 0.357471E+10 0.337808E+10 0.357307E+10 0.217286E+10 0.140021E+10 0.00 0.00
December 0.281308E+10 0.436191E+10 0.292991E+10 0.187874E+10 0.105117E+10 0.00 0.00
               
Annual Sum or Average 0.665804E+11 0.316266E+11 0.596374E+11 0.281905E+11 0.314469E+11 0.00 0.00
Minimum of Months 0.264551E+10 0.136701E+10 0.292991E+10 0.920306E+09 0.105117E+10 0.00 0.00
Maximum of Months 0.926222E+10 0.436191E+10 0.741524E+10 0.437654E+10 0.375972E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.555513E+10 0.514394E+10 0.552217E+10 0.357594E+10 0.194622E+10 0.00 0.00
February 0.625679E+10 0.446012E+10 0.605241E+10 0.368880E+10 0.236360E+10 0.00 0.00
March 0.349494E+10 0.414259E+10 0.413581E+10 0.119553E+10 0.294029E+10 0.00 0.00
April 0.965744E+10 0.320995E+10 0.820468E+10 0.363550E+10 0.456918E+10 0.00 0.00
May 0.786320E+10 0.282640E+10 0.710749E+10 0.230242E+10 0.480506E+10 0.00 0.00
June 0.743315E+10 0.197486E+10 0.634930E+10 0.153557E+10 0.481373E+10 0.00 0.00
July 0.886818E+10 0.183663E+10 0.707196E+10 0.218787E+10 0.488409E+10 0.00 0.00
August 0.108253E+11 0.199545E+10 0.830611E+10 0.372154E+10 0.458457E+10 0.00 0.00
September 0.122663E+11 0.257880E+10 0.963282E+10 0.568537E+10 0.394745E+10 0.00 0.00
October 0.750230E+10 0.374390E+10 0.664185E+10 0.382922E+10 0.281264E+10 0.00 0.00
November 0.470784E+10 0.452412E+10 0.464162E+10 0.282267E+10 0.181896E+10 0.00 0.00
December 0.369496E+10 0.586937E+10 0.380613E+10 0.244060E+10 0.136553E+10 0.00 0.00
               
Annual Sum or Average 0.881255E+11 0.423061E+11 0.774723E+11 0.366210E+11 0.408513E+11 0.00 0.00
Minimum of Months 0.349494E+10 0.183663E+10 0.380613E+10 0.119553E+10 0.136553E+10 0.00 0.00
Maximum of Months 0.122663E+11 0.586937E+10 0.963282E+10 0.568537E+10 0.488409E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.395437E+09 0.790024E+09 0.494133E+09 0.257408E+09 0.236725E+09 0.00 0.00
February 0.571209E+09 0.693819E+09 0.639747E+09 0.332452E+09 0.307294E+09 0.00 0.00
March 0.386497E+09 0.625747E+09 0.534896E+09 0.124489E+09 0.410407E+09 0.00 0.00
April 0.124329E+10 0.496009E+09 0.115310E+10 0.477853E+09 0.675246E+09 0.00 0.00
May 0.129596E+10 0.434444E+09 0.124465E+10 0.474379E+09 0.770273E+09 0.00 0.00
June 0.139207E+10 0.309087E+09 0.124223E+10 0.453123E+09 0.789105E+09 0.00 0.00
July 0.156795E+10 0.287663E+09 0.132781E+10 0.534771E+09 0.793040E+09 0.00 0.00
August 0.150587E+10 0.313820E+09 0.124466E+10 0.545860E+09 0.698800E+09 0.00 0.00
September 0.134403E+10 0.408326E+09 0.114291E+10 0.588565E+09 0.554349E+09 0.00 0.00
October 0.698458E+09 0.579273E+09 0.701746E+09 0.331451E+09 0.370295E+09 0.00 0.00
November 0.351279E+09 0.692409E+09 0.429837E+09 0.205366E+09 0.224470E+09 0.00 0.00
December 0.216310E+09 0.892844E+09 0.308814E+09 0.152870E+09 0.155944E+09 0.00 0.00
               
Annual Sum or Average 0.109684E+11 0.652347E+10 0.104645E+11 0.447859E+10 0.598595E+10 0.00 0.00
Minimum of Months 0.216310E+09 0.287663E+09 0.308814E+09 0.124489E+09 0.155944E+09 0.00 0.00
Maximum of Months 0.156795E+10 0.892844E+09 0.132781E+10 0.588565E+09 0.793040E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.122179E+09 0.826936E+09 0.247957E+09 64128920.97 0.183828E+09 0.00 0.00
February 0.263210E+09 0.708421E+09 0.386375E+09 0.133073E+09 0.253301E+09 0.00 0.00
March 0.247901E+09 0.629485E+09 0.424373E+09 59871685.24 0.364501E+09 0.00 0.00
April 0.873350E+09 0.487984E+09 0.888354E+09 0.282543E+09 0.605811E+09 0.00 0.00
May 0.106022E+10 0.417323E+09 0.109138E+10 0.361707E+09 0.729674E+09 0.00 0.00
June 0.123383E+10 0.295764E+09 0.114520E+10 0.385523E+09 0.759681E+09 0.00 0.00
July 0.134726E+10 0.275568E+09 0.118742E+10 0.430741E+09 0.756678E+09 0.00 0.00
August 0.113035E+10 0.303675E+09 0.986127E+09 0.348272E+09 0.637855E+09 0.00 0.00
September 0.826878E+09 0.404146E+09 0.762029E+09 0.281355E+09 0.480675E+09 0.00 0.00
October 0.357750E+09 0.582064E+09 0.435230E+09 0.124483E+09 0.310747E+09 0.00 0.00
November 0.121839E+09 0.709726E+09 0.232729E+09 52801937.15 0.179927E+09 0.00 0.00
December 37617976.89 0.926958E+09 0.140932E+09 20956149.08 0.119976E+09 0.00 0.00
               
Annual Sum or Average 0.762238E+10 0.656805E+10 0.792811E+10 0.254546E+10 0.538265E+10 0.00 0.00
Minimum of Months 37617976.89 0.275568E+09 0.140932E+09 20956149.08 0.119976E+09 0.00 0.00
Maximum of Months 0.134726E+10 0.926958E+09 0.118742E+10 0.430741E+09 0.759681E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.232469E+09 0.238130E+09 0.238730E+09 0.154592E+09 84137898.18 0.00 0.00
February 0.261501E+09 0.210643E+09 0.261653E+09 0.159471E+09 0.102182E+09 0.00 0.00
March 0.143661E+09 0.191606E+09 0.178797E+09 51684172.32 0.127113E+09 0.00 0.00
April 0.397427E+09 0.161870E+09 0.354700E+09 0.157167E+09 0.197533E+09 0.00 0.00
May 0.317327E+09 0.146168E+09 0.307267E+09 99536592.27 0.207730E+09 0.00 0.00
June 0.297883E+09 0.105569E+09 0.274490E+09 66384623.48 0.208105E+09 0.00 0.00
July 0.358995E+09 99408841.43 0.305732E+09 94584426.86 0.211147E+09 0.00 0.00
August 0.445026E+09 0.107886E+09 0.359085E+09 0.160887E+09 0.198198E+09 0.00 0.00
September 0.508980E+09 0.135952E+09 0.416440E+09 0.245785E+09 0.170655E+09 0.00 0.00
October 0.310766E+09 0.187453E+09 0.287136E+09 0.165542E+09 0.121594E+09 0.00 0.00
November 0.195744E+09 0.215690E+09 0.200663E+09 0.122027E+09 78636007.32 0.00 0.00
December 0.158784E+09 0.248892E+09 0.164544E+09 0.105510E+09 59033741.75 0.00 0.00
               
Annual Sum or Average 0.362856E+10 0.204927E+10 0.334924E+10 0.158317E+10 0.176607E+10 0.00 0.00
Minimum of Months 0.143661E+09 99408841.43 0.164544E+09 51684172.32 59033741.75 0.00 0.00
Maximum of Months 0.508980E+09 0.248892E+09 0.416440E+09 0.245785E+09 0.211147E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 3383701.88 0.253966E+09 41842464.75 0.00 41842464.75 0.00 0.00
February 9510838.88 0.213762E+09 59015680.35 0.00 59015680.35 0.00 0.00
March 33113323.56 0.190646E+09 90426079.04 611.18 90425467.87 0.00 0.00
April 0.102841E+09 0.139358E+09 0.142993E+09 950366.37 0.142043E+09 0.00 0.00
May 0.134907E+09 0.114931E+09 0.184736E+09 9420490.59 0.175316E+09 0.00 0.00
June 0.183716E+09 80865322.40 0.196951E+09 12319448.80 0.184631E+09 0.00 0.00
July 0.194284E+09 74587656.09 0.193505E+09 11381086.97 0.182124E+09 0.00 0.00
August 0.151839E+09 82370167.36 0.152351E+09 2849117.93 0.149502E+09 0.00 0.00
September 96100804.10 0.114947E+09 0.111830E+09 66094.90 0.111764E+09 0.00 0.00
October 35529048.83 0.173023E+09 73990137.15 0.00 73990137.15 0.00 0.00
November 5443946.53 0.215092E+09 43022945.85 0.00 43022945.85 0.00 0.00
December 186279.94 0.279647E+09 30275127.60 0.00 30275127.60 0.00 0.00
               
Annual Sum or Average 0.950856E+09 0.193320E+10 0.132094E+10 36987216.73 0.128395E+10 0.00 0.00
Minimum of Months 186279.94 74587656.09 30275127.60 0.00 30275127.60 0.00 0.00
Maximum of Months 0.194284E+09 0.279647E+09 0.196951E+09 12319448.80 0.184631E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.396343E+09 0.785869E+09 0.496934E+09 0.272321E+09 0.224613E+09 0.00 0.00
February 0.504133E+09 0.683481E+09 0.597830E+09 0.300245E+09 0.297585E+09 0.00 0.00
March 0.382799E+09 0.621714E+09 0.534921E+09 0.126033E+09 0.408888E+09 0.00 0.00
April 0.134579E+10 0.476488E+09 0.125073E+10 0.574996E+09 0.675737E+09 0.00 0.00
May 0.130139E+10 0.420764E+09 0.126247E+10 0.507539E+09 0.754926E+09 0.00 0.00
June 0.130654E+10 0.299050E+09 0.118426E+10 0.418994E+09 0.765270E+09 0.00 0.00
July 0.147775E+10 0.277318E+09 0.126927E+10 0.495041E+09 0.774234E+09 0.00 0.00
August 0.155477E+10 0.299797E+09 0.129158E+10 0.604548E+09 0.687035E+09 0.00 0.00
September 0.147003E+10 0.394587E+09 0.125276E+10 0.696307E+09 0.556457E+09 0.00 0.00
October 0.725514E+09 0.574343E+09 0.726948E+09 0.360841E+09 0.366107E+09 0.00 0.00
November 0.352975E+09 0.686976E+09 0.435166E+09 0.215271E+09 0.219895E+09 0.00 0.00
December 0.262053E+09 0.888034E+09 0.347365E+09 0.184917E+09 0.162448E+09 0.00 0.00
               
Annual Sum or Average 0.110801E+11 0.640842E+10 0.106502E+11 0.475705E+10 0.589319E+10 0.00 0.00
Minimum of Months 0.262053E+09 0.277318E+09 0.347365E+09 0.126033E+09 0.162448E+09 0.00 0.00
Maximum of Months 0.155477E+10 0.888034E+09 0.129158E+10 0.696307E+09 0.774234E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.111694E+09 0.810688E+09 0.250758E+09 79042420.23 0.171716E+09 0.00 0.00
February 0.188239E+09 0.690093E+09 0.344458E+09 0.100866E+09 0.243592E+09 0.00 0.00
March 0.242440E+09 0.623815E+09 0.424398E+09 61415498.09 0.362983E+09 0.00 0.00
April 0.973304E+09 0.469391E+09 0.985989E+09 0.379686E+09 0.606302E+09 0.00 0.00
May 0.106678E+10 0.407109E+09 0.110919E+10 0.394867E+09 0.714327E+09 0.00 0.00
June 0.115147E+10 0.290540E+09 0.108724E+10 0.351394E+09 0.735845E+09 0.00 0.00
July 0.125877E+10 0.268968E+09 0.112888E+10 0.391012E+09 0.737872E+09 0.00 0.00
August 0.117932E+10 0.293458E+09 0.103305E+10 0.406961E+09 0.626091E+09 0.00 0.00
September 0.945199E+09 0.388155E+09 0.871879E+09 0.389097E+09 0.482782E+09 0.00 0.00
October 0.377190E+09 0.570570E+09 0.460432E+09 0.153873E+09 0.306559E+09 0.00 0.00
November 0.111275E+09 0.691380E+09 0.238058E+09 62706204.31 0.175352E+09 0.00 0.00
December 61355376.08 0.897830E+09 0.179483E+09 53003264.31 0.126480E+09 0.00 0.00
               
Annual Sum or Average 0.766704E+10 0.640200E+10 0.811382E+10 0.282392E+10 0.528990E+10 0.00 0.00
Minimum of Months 61355376.08 0.268968E+09 0.179483E+09 53003264.31 0.126480E+09 0.00 0.00
Maximum of Months 0.125877E+10 0.897830E+09 0.112888E+10 0.406961E+09 0.737872E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.480299E+09 0.100266E+10 0.607907E+09 0.334959E+09 0.272948E+09 0.00 0.00
February 0.582872E+09 0.874268E+09 0.694778E+09 0.345530E+09 0.349248E+09 0.00 0.00
March 0.393487E+09 0.802235E+09 0.583296E+09 0.111987E+09 0.471310E+09 0.00 0.00
April 0.113124E+10 0.605159E+09 0.107831E+10 0.342596E+09 0.735711E+09 0.00 0.00
May 0.102527E+10 0.507682E+09 0.106596E+10 0.236076E+09 0.829887E+09 0.00 0.00
June 0.109935E+10 0.351356E+09 0.102140E+10 0.170525E+09 0.850879E+09 0.00 0.00
July 0.125819E+10 0.325521E+09 0.108163E+10 0.229593E+09 0.852038E+09 0.00 0.00
August 0.135165E+10 0.360713E+09 0.110808E+10 0.354769E+09 0.753311E+09 0.00 0.00
September 0.136028E+10 0.489840E+09 0.114457E+10 0.532692E+09 0.611878E+09 0.00 0.00
October 0.773469E+09 0.722434E+09 0.782431E+09 0.358683E+09 0.423749E+09 0.00 0.00
November 0.429308E+09 0.879841E+09 0.527984E+09 0.264399E+09 0.263584E+09 0.00 0.00
December 0.311529E+09 0.114651E+10 0.422106E+09 0.228611E+09 0.193496E+09 0.00 0.00
               
Annual Sum or Average 0.101969E+11 0.806822E+10 0.101185E+11 0.351042E+10 0.660804E+10 0.00 0.00
Minimum of Months 0.311529E+09 0.325521E+09 0.422106E+09 0.111987E+09 0.193496E+09 0.00 0.00
Maximum of Months 0.136028E+10 0.114651E+10 0.114457E+10 0.532692E+09 0.852038E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.398322E+09 0.776598E+09 0.494133E+09 0.257408E+09 0.236725E+09 0.00 0.00
February 0.572352E+09 0.685284E+09 0.639747E+09 0.332452E+09 0.307294E+09 0.00 0.00
March 0.387545E+09 0.615863E+09 0.534896E+09 0.124489E+09 0.410407E+09 0.00 0.00
April 0.123068E+10 0.493357E+09 0.115310E+10 0.477853E+09 0.675246E+09 0.00 0.00
May 0.127949E+10 0.434958E+09 0.124465E+10 0.474379E+09 0.770273E+09 0.00 0.00
June 0.137288E+10 0.310690E+09 0.124223E+10 0.453123E+09 0.789105E+09 0.00 0.00
July 0.154796E+10 0.289203E+09 0.132781E+10 0.534771E+09 0.793040E+09 0.00 0.00
August 0.148882E+10 0.314159E+09 0.124466E+10 0.545860E+09 0.698800E+09 0.00 0.00
September 0.133236E+10 0.407590E+09 0.114291E+10 0.588565E+09 0.554349E+09 0.00 0.00
October 0.696451E+09 0.571714E+09 0.701746E+09 0.331451E+09 0.370295E+09 0.00 0.00
November 0.353124E+09 0.681299E+09 0.429837E+09 0.205366E+09 0.224470E+09 0.00 0.00
December 0.218304E+09 0.881640E+09 0.308814E+09 0.152870E+09 0.155944E+09 0.00 0.00
               
Annual Sum or Average 0.108783E+11 0.646235E+10 0.104645E+11 0.447859E+10 0.598595E+10 0.00 0.00
Minimum of Months 0.218304E+09 0.289203E+09 0.308814E+09 0.124489E+09 0.155944E+09 0.00 0.00
Maximum of Months 0.154796E+10 0.881640E+09 0.132781E+10 0.588565E+09 0.793040E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.124544E+09 0.812483E+09 0.247957E+09 64128920.97 0.183828E+09 0.00 0.00
February 0.265286E+09 0.698337E+09 0.386375E+09 0.133073E+09 0.253301E+09 0.00 0.00
March 0.249763E+09 0.619006E+09 0.424373E+09 59871685.24 0.364501E+09 0.00 0.00
April 0.861819E+09 0.484745E+09 0.888354E+09 0.282543E+09 0.605811E+09 0.00 0.00
May 0.104429E+10 0.417611E+09 0.109138E+10 0.361707E+09 0.729674E+09 0.00 0.00
June 0.121426E+10 0.297337E+09 0.114520E+10 0.385523E+09 0.759681E+09 0.00 0.00
July 0.132714E+10 0.277108E+09 0.118742E+10 0.430741E+09 0.756678E+09 0.00 0.00
August 0.111345E+10 0.303898E+09 0.986127E+09 0.348272E+09 0.637855E+09 0.00 0.00
September 0.817090E+09 0.402570E+09 0.762029E+09 0.281355E+09 0.480675E+09 0.00 0.00
October 0.357447E+09 0.572874E+09 0.435230E+09 0.124483E+09 0.310747E+09 0.00 0.00
November 0.124256E+09 0.697205E+09 0.232729E+09 52801937.15 0.179927E+09 0.00 0.00
December 38762453.79 0.914739E+09 0.140932E+09 20956149.08 0.119976E+09 0.00 0.00
               
Annual Sum or Average 0.753812E+10 0.649791E+10 0.792811E+10 0.254546E+10 0.538265E+10 0.00 0.00
Minimum of Months 38762453.79 0.277108E+09 0.140932E+09 20956149.08 0.119976E+09 0.00 0.00
Maximum of Months 0.132714E+10 0.914739E+09 0.118742E+10 0.430741E+09 0.759681E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.428844E+09 0.407517E+09 0.437738E+09 0.283462E+09 0.154276E+09 0.00 0.00
February 0.481938E+09 0.359469E+09 0.479770E+09 0.292408E+09 0.187362E+09 0.00 0.00
March 0.268093E+09 0.327567E+09 0.327844E+09 94768591.74 0.233075E+09 0.00 0.00
April 0.733872E+09 0.262774E+09 0.650381E+09 0.288183E+09 0.362198E+09 0.00 0.00
May 0.590598E+09 0.233879E+09 0.563408E+09 0.182511E+09 0.380897E+09 0.00 0.00
June 0.556560E+09 0.162928E+09 0.503307E+09 0.121723E+09 0.381584E+09 0.00 0.00
July 0.667907E+09 0.151275E+09 0.560592E+09 0.173431E+09 0.387162E+09 0.00 0.00
August 0.822674E+09 0.163813E+09 0.658421E+09 0.295003E+09 0.363418E+09 0.00 0.00
September 0.937304E+09 0.214043E+09 0.763588E+09 0.450674E+09 0.312914E+09 0.00 0.00
October 0.575133E+09 0.302648E+09 0.526495E+09 0.303539E+09 0.222957E+09 0.00 0.00
November 0.362076E+09 0.360724E+09 0.367938E+09 0.223750E+09 0.144188E+09 0.00 0.00
December 0.286580E+09 0.463935E+09 0.301709E+09 0.193464E+09 0.108245E+09 0.00 0.00
               
Annual Sum or Average 0.671158E+10 0.341057E+10 0.614119E+10 0.290292E+10 0.323827E+10 0.00 0.00
Minimum of Months 0.268093E+09 0.151275E+09 0.301709E+09 94768591.74 0.108245E+09 0.00 0.00
Maximum of Months 0.937304E+09 0.463935E+09 0.763588E+09 0.450674E+09 0.387162E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 26497778.32 0.223801E+10 0.366059E+09 0.00 0.366059E+09 0.00 0.00
February 74382455.92 0.188701E+10 0.516299E+09 0.00 0.516299E+09 0.00 0.00
March 0.282911E+09 0.167360E+10 0.791093E+09 5346.90 0.791088E+09 0.00 0.00
April 0.891290E+09 0.123233E+10 0.125098E+10 8314288.68 0.124266E+10 0.00 0.00
May 0.116584E+10 0.104214E+10 0.161617E+10 82415246.22 0.153375E+10 0.00 0.00
June 0.160015E+10 0.748582E+09 0.172303E+10 0.107777E+09 0.161525E+10 0.00 0.00
July 0.169814E+10 0.695319E+09 0.169288E+10 99567541.14 0.159331E+10 0.00 0.00
August 0.133119E+10 0.761643E+09 0.133284E+10 24925533.69 0.130792E+10 0.00 0.00
September 0.842619E+09 0.103235E+10 0.978343E+09 578231.83 0.977764E+09 0.00 0.00
October 0.305403E+09 0.153098E+10 0.647303E+09 0.00 0.647303E+09 0.00 0.00
November 43798847.09 0.190778E+10 0.376387E+09 0.00 0.376387E+09 0.00 0.00
December 1050216.35 0.249173E+10 0.264862E+09 0.00 0.264862E+09 0.00 0.00
               
Annual Sum or Average 0.826327E+10 0.172415E+11 0.115562E+11 0.323583E+09 0.112327E+11 0.00 0.00
Minimum of Months 1050216.35 0.695319E+09 0.264862E+09 0.00 0.264862E+09 0.00 0.00
Maximum of Months 0.169814E+10 0.249173E+10 0.172303E+10 0.107777E+09 0.161525E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 23962966.92 0.228060E+10 0.366059E+09 0.00 0.366059E+09 0.00 0.00
February 69061034.79 0.192336E+10 0.516299E+09 0.00 0.516299E+09 0.00 0.00
March 0.271905E+09 0.171042E+10 0.791093E+09 5346.90 0.791088E+09 0.00 0.00
April 0.871816E+09 0.126026E+10 0.125098E+10 8314288.68 0.124266E+10 0.00 0.00
May 0.113799E+10 0.106719E+10 0.161617E+10 82415246.22 0.153375E+10 0.00 0.00
June 0.157013E+10 0.771208E+09 0.172303E+10 0.107777E+09 0.161525E+10 0.00 0.00
July 0.166592E+10 0.717867E+09 0.169288E+10 99567541.14 0.159331E+10 0.00 0.00
August 0.130486E+10 0.787524E+09 0.133284E+10 24925533.69 0.130792E+10 0.00 0.00
September 0.824276E+09 0.106183E+10 0.978343E+09 578231.83 0.977764E+09 0.00 0.00
October 0.294559E+09 0.156870E+10 0.647303E+09 0.00 0.647303E+09 0.00 0.00
November 40115672.81 0.195028E+10 0.376387E+09 0.00 0.376387E+09 0.00 0.00
December 720839.11 0.253811E+10 0.264862E+09 0.00 0.264862E+09 0.00 0.00
               
Annual Sum or Average 0.807531E+10 0.176373E+11 0.115562E+11 0.323583E+09 0.112327E+11 0.00 0.00
Minimum of Months 720839.11 0.717867E+09 0.264862E+09 0.00 0.264862E+09 0.00 0.00
Maximum of Months 0.166592E+10 0.253811E+10 0.172303E+10 0.107777E+09 0.161525E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.574489E+09 0.146987E+10 0.747665E+09 0.351352E+09 0.396312E+09 0.00 0.00
February 0.780138E+09 0.130232E+10 0.942249E+09 0.401097E+09 0.541152E+09 0.00 0.00
March 0.763044E+09 0.117874E+10 0.959275E+09 0.187440E+09 0.771835E+09 0.00 0.00
April 0.259313E+10 0.921720E+09 0.223661E+10 0.954629E+09 0.128198E+10 0.00 0.00
May 0.263943E+10 0.852034E+09 0.237153E+10 0.902352E+09 0.146918E+10 0.00 0.00
June 0.275723E+10 0.618012E+09 0.227138E+10 0.770339E+09 0.150104E+10 0.00 0.00
July 0.306827E+10 0.576464E+09 0.239803E+10 0.885999E+09 0.151203E+10 0.00 0.00
August 0.305818E+10 0.604639E+09 0.232452E+10 0.101145E+10 0.131306E+10 0.00 0.00
September 0.268821E+10 0.762561E+09 0.212454E+10 0.108535E+10 0.103919E+10 0.00 0.00
October 0.126253E+10 0.108953E+10 0.118733E+10 0.514692E+09 0.672635E+09 0.00 0.00
November 0.535609E+09 0.129882E+10 0.673197E+09 0.277968E+09 0.395230E+09 0.00 0.00
December 0.365317E+09 0.170971E+10 0.526828E+09 0.237913E+09 0.288915E+09 0.00 0.00
               
Annual Sum or Average 0.210856E+11 0.123844E+11 0.187632E+11 0.758058E+10 0.111826E+11 0.00 0.00
Minimum of Months 0.365317E+09 0.576464E+09 0.526828E+09 0.187440E+09 0.288915E+09 0.00 0.00
Maximum of Months 0.306827E+10 0.170971E+10 0.239803E+10 0.108535E+10 0.151203E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.105077E+10 0.176252E+10 0.123977E+10 0.721568E+09 0.518204E+09 0.00 0.00
February 0.124016E+10 0.154363E+10 0.139827E+10 0.744341E+09 0.653928E+09 0.00 0.00
March 0.778059E+09 0.141874E+10 0.110573E+10 0.241240E+09 0.864492E+09 0.00 0.00
April 0.222247E+10 0.107984E+10 0.208442E+10 0.736435E+09 0.134798E+10 0.00 0.00
May 0.193424E+10 0.920479E+09 0.198821E+10 0.492844E+09 0.149537E+10 0.00 0.00
June 0.200443E+10 0.637239E+09 0.187185E+10 0.346800E+09 0.152505E+10 0.00 0.00
July 0.232846E+10 0.588090E+09 0.200734E+10 0.475610E+09 0.153173E+10 0.00 0.00
August 0.260716E+10 0.648287E+09 0.213295E+10 0.759491E+09 0.137346E+10 0.00 0.00
September 0.273105E+10 0.871869E+09 0.227913E+10 0.114741E+10 0.113172E+10 0.00 0.00
October 0.158984E+10 0.128402E+10 0.156212E+10 0.772674E+09 0.789445E+09 0.00 0.00
November 0.919945E+09 0.155941E+10 0.106563E+10 0.569569E+09 0.496064E+09 0.00 0.00
December 0.687564E+09 0.202978E+10 0.858811E+09 0.492473E+09 0.366338E+09 0.00 0.00
               
Annual Sum or Average 0.200941E+11 0.143439E+11 0.195942E+11 0.750046E+10 0.120938E+11 0.00 0.00
Minimum of Months 0.687564E+09 0.588090E+09 0.858811E+09 0.241240E+09 0.366338E+09 0.00 0.00
Maximum of Months 0.273105E+10 0.202978E+10 0.227913E+10 0.114741E+10 0.153173E+10 0.00 0.00



Table of Contents

Report: AverageOutdoorConditionsMonthly

For: Environment

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] SITE OUTDOOR AIR WETBULB TEMPERATURE [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] SITE WIND SPEED [m/s] SITE SKY TEMPERATURE [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] SITE RAIN STATUS []
January 4.18 3.23 2.03 1.05 -4.0 28.28 62.93 0.00
February 4.25 3.55 2.74 1.60 -5.0 43.80 86.73 0.02
March 5.90 4.45 2.76 1.18 -1.9 68.95 35.00 0.00
April 8.96 6.24 3.38 1.56 -0.7 96.13 186.12 0.00
May 9.99 8.07 6.28 3.35 -0.9 110.92 199.68 0.02
June 13.31 11.27 9.70 3.33 3.35 121.69 199.28 0.00
July 15.02 12.39 10.49 3.21 4.49 111.91 220.83 0.00
August 15.65 12.75 10.65 2.92 3.95 91.47 211.91 0.00
September 13.43 11.01 9.10 2.64 1.43 68.72 198.32 0.01
October 9.33 8.03 6.81 1.97 -1.0 48.92 91.86 0.04
November 6.66 5.66 4.54 2.05 -2.3 30.27 53.24 0.04
December 4.10 3.14 1.95 2.36 -5.1 20.52 40.74 0.04
                 
Annual Sum or Average 9.26 7.50 5.89 2.27 -0.6 70.25 132.30 0.02
Minimum of Months 4.10 3.14 1.95 1.05 -5.1 20.52 35.00 0.00
Maximum of Months 15.65 12.75 10.65 3.35 4.49 121.69 220.83 0.04



Table of Contents

Report: OutdoorConditionsMaximumDryBulbMonthly

For: Environment

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 14.00 29-JAN-05:00 9.37 5.00 3.60 8.35 0.00 0.00
February 11.00 07-FEB-14:00 9.86 9.00 2.10 6.35 138.00 225.00
March 14.00 25-MAR-12:00 11.22 9.00 2.60 7.35 287.00 93.00
April 24.00 30-APR-14:00 13.13 4.00 1.50 7.75 167.50 716.00
May 24.00 22-MAY-14:00 16.08 11.00 2.60 9.33 159.00 769.00
June 27.00 13-JUN-16:00 17.53 12.00 3.10 12.41 141.50 652.50
July 30.00 22-JUL-17:00 16.80 8.00 0.00 14.28 122.00 407.00
August 27.00 14-AUG-17:19 14.18 3.33 2.60 10.37 133.00 358.83
September 23.00 11-SEP-16:00 16.22 12.00 2.60 8.74 108.00 325.50
October 19.00 07-OCT-14:00 10.10 1.00 1.50 2.22 131.00 540.50
November 16.00 24-NOV-11:00 12.01 9.00 4.10 9.33 61.50 0.00
December 13.00 23-DEC-10:00 7.64 2.00 7.70 6.75 70.50 0.00
                 
Annual Sum or Average                
Minimum of Months 11.00   7.64 1.00 0.00 2.22 0.00 0.00
Maximum of Months 30.00   17.53 12.00 7.70 14.28 287.00 769.00



Table of Contents

Report: OutdoorConditionsMinimumDryBulbMonthly

For: Environment

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January -6.0 10-JAN-07:00 -7.0 -9.0 0.00 -20.0 0.00 0.00
February -4.0 17-FEB-06:00 -4.0 -4.0 0.00 -20.5 0.00 0.00
March -1.0 08-MAR-06:00 -1.4 -2.0 0.00 -14.4 17.50 184.50
April 0.00 08-APR-04:00 -0.9 -2.0 0.00 -12.7 0.00 0.00
May 2.00 06-MAY-04:00 1.57 1.00 3.60 -13.7 12.50 117.00
June 6.00 01-JUN-03:00 5.05 4.00 0.00 -9.2 0.00 0.00
July 7.00 05-JUL-04:00 6.47 6.00 3.10 -7.8 28.00 155.00
August 8.00 20-AUG-04:00 7.45 7.00 0.00 -6.6 0.00 0.00
September 5.00 20-SEP-03:00 5.00 5.00 2.60 -10.0 0.00 0.00
October 2.00 07-OCT-03:00 2.00 2.00 0.00 -13.4 0.00 0.00
November -2.0 29-NOV-01:00 -2.0 -2.0 3.10 -10.7 0.00 0.00
December -3.0 29-DEC-20:00 -4.5 -7.0 3.60 -20.2 0.00 0.00
                 
Annual Sum or Average                
Minimum of Months -6.0   -7.0 -9.0 0.00 -20.5 0.00 0.00
Maximum of Months 8.00   7.45 7.00 3.60 -6.6 28.00 184.50



Table of Contents

Report: OutdoorConditionsMaximumWetBulbMonthly

For: Environment

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

SITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 12.44 29-JAN-04:00 13.00 12.00 0.00 9.13 0.00 0.00
February 9.86 07-FEB-14:00 11.00 9.00 2.10 6.35 138.00 225.00
March 12.00 19-MAR-11:00 12.00 12.00 2.60 8.15 131.00 0.00
April 15.39 28-APR-07:00 16.00 15.00 0.00 5.54 119.50 626.00
May 16.08 22-MAY-14:00 24.00 11.00 2.60 9.33 159.00 769.00
June 19.93 25-JUN-17:00 22.00 19.00 0.00 15.94 136.50 360.50
July 17.31 22-JUL-09:00 26.00 12.00 4.60 11.46 224.50 619.50
August 17.06 14-AUG-12:00 24.00 13.00 2.60 9.91 205.50 669.50
September 16.54 10-SEP-15:00 21.00 14.00 3.60 8.54 160.50 483.00
October 13.58 17-OCT-14:00 16.00 12.00 0.00 12.03 144.00 44.50
November 12.01 24-NOV-11:00 16.00 9.00 4.10 9.33 61.50 0.00
December 7.93 02-DEC-12:00 9.00 7.00 0.00 2.01 135.50 84.00
                 
Annual Sum or Average                
Minimum of Months 7.93   9.00 7.00 0.00 2.01 0.00 0.00
Maximum of Months 19.93   26.00 19.00 4.60 15.94 224.50 769.00



Table of Contents

Report: OutdoorConditionsMaximumDewPointMonthly

For: Environment

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

SITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 12.00 29-JAN-04:00 13.00 12.44 0.00 9.13 0.00 0.00
February 9.00 07-FEB-14:00 11.00 9.86 2.10 6.35 138.00 225.00
March 12.00 19-MAR-11:00 12.00 12.00 2.60 8.15 131.00 0.00
April 15.00 28-APR-07:00 16.00 15.39 0.00 5.54 119.50 626.00
May 12.00 23-MAY-07:00 17.00 13.95 3.10 5.13 112.00 719.50
June 19.00 25-JUN-17:00 22.00 19.93 0.00 15.94 136.50 360.50
July 14.00 17-JUL-17:00 18.00 15.45 3.60 9.91 120.00 0.00
August 16.00 08-AUG-12:00 18.00 16.70 1.50 11.46 154.00 0.00
September 14.00 10-SEP-15:00 21.00 16.54 3.60 8.54 160.50 483.00
October 13.00 17-OCT-18:00 13.00 13.00 2.60 9.33 0.00 0.00
November 12.00 08-NOV-14:00 12.00 12.00 0.00 8.15 93.00 106.00
December 7.00 02-DEC-11:00 8.00 7.45 3.10 1.16 144.50 146.50
                 
Annual Sum or Average                
Minimum of Months 7.00   8.00 7.45 0.00 1.16 0.00 0.00
Maximum of Months 19.00   22.00 19.93 3.60 15.94 160.50 719.50



Table of Contents

Report: OutdoorGroundConditionsMonthly

For: Environment

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

SITE GROUND TEMPERATURE [C] SITE SURFACE GROUND TEMPERATURE [C] SITE DEEP GROUND TEMPERATURE [C] SITE MAINS WATER TEMPERATURE [C] SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] SITE SNOW ON GROUND STATUS []
January 18.00 13.00 16.00 10.33 8.85 0.00
February 18.00 13.00 16.00 10.00 14.79 0.00
March 18.00 13.00 16.00 10.33 17.09 0.00
April 18.00 13.00 16.00 11.26 40.86 0.00
May 18.00 13.00 16.00 12.54 47.73 0.00
June 18.00 13.00 16.00 13.82 50.98 0.00
July 18.00 13.00 16.00 14.77 51.67 0.00
August 18.00 13.00 16.00 15.12 44.67 0.00
September 18.00 13.00 16.00 14.78 34.25 0.00
October 18.00 13.00 16.00 13.84 17.71 0.00
November 18.00 13.00 16.00 12.55 9.34 0.00
December 18.00 13.00 16.00 11.27 6.14 0.00
             
Annual Sum or Average 18.00 13.00 16.00 12.57 28.73 0.00
Minimum of Months 18.00 13.00 16.00 10.00 6.14 0.00
Maximum of Months 18.00 13.00 16.00 15.12 51.67 0.00



Table of Contents

Report: WaterHeaterReportMonthly

For: SWH BOOSTER E WATER HEATER

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] WATER HEATER BURNER HEATING ENERGY [] WATER HEATER GAS CONSUMPTION [] WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] WATER HEATER LOSS DEMAND ENERGY [] WATER HEATER HEAT LOSS ENERGY [J] WATER HEATER TANK TEMPERATURE [C] WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] WATER HEATER SOURCE ENERGY []
January 0.770802E+10 -0.754278E+10 0.00 0.00 744.00 0.00 -165241720.9 81.21 0.00 0.00
February 0.696509E+10 -0.681596E+10 0.00 0.00 672.00 0.00 -149127059.3 81.21 0.00 0.00
March 0.770646E+10 -0.754146E+10 0.00 0.00 744.00 0.00 -164995997.1 81.21 0.00 0.00
April 0.746765E+10 -0.730859E+10 0.00 0.00 720.00 0.00 -159058282.7 81.21 0.00 0.00
May 0.770711E+10 -0.754280E+10 0.00 0.00 744.00 0.00 -164309066.2 81.21 0.00 0.00
June 0.745937E+10 -0.730053E+10 0.00 0.00 720.00 0.00 -158838996.1 81.21 0.00 0.00
July 0.771492E+10 -0.755085E+10 0.00 0.00 744.00 0.00 -164064555.5 81.21 0.00 0.00
August 0.770688E+10 -0.754281E+10 0.00 0.00 744.00 0.00 -164073399.8 81.21 0.00 0.00
September 0.746885E+10 -0.730994E+10 0.00 0.00 720.00 0.00 -158912387.4 81.21 0.00 0.00
October 0.770619E+10 -0.754143E+10 0.00 0.00 744.00 0.00 -164753699.7 81.21 0.00 0.00
November 0.745224E+10 -0.729243E+10 0.00 0.00 720.00 0.00 -159806288.1 81.21 0.00 0.00
December 0.771626E+10 -0.755084E+10 0.00 0.00 744.00 0.00 -165416589.7 81.21 0.00 0.00
                     
Annual Sum or Average 0.907790E+11 -0.888404E+11 0.00 0.00 8760.00 0.00 -0.193860E+10 81.21 0.00 0.00
Minimum of Months 0.696509E+10 -0.755085E+10 0.00 0.00 672.00 0.00 -165416589.7 81.21 0.00 0.00
Maximum of Months 0.771626E+10 -0.681596E+10 0.00 0.00 744.00 0.00 -149127059.3 81.21 0.00 0.00



Table of Contents

Report: WaterHeaterReportMonthly

For: SWH LAUNDRY G WATER HEATER

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] WATER HEATER BURNER HEATING ENERGY [] WATER HEATER GAS CONSUMPTION [] WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] WATER HEATER LOSS DEMAND ENERGY [] WATER HEATER HEAT LOSS ENERGY [J] WATER HEATER TANK TEMPERATURE [C] WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] WATER HEATER SOURCE ENERGY []
January 0.121962E+12 -0.120147E+12 0.00 0.00 744.00 0.00 -0.181494E+10 81.27 0.00 0.00
February 0.110675E+12 -0.109035E+12 0.00 0.00 672.00 0.00 -0.163971E+10 81.28 0.00 0.00
March 0.121954E+12 -0.120138E+12 0.00 0.00 744.00 0.00 -0.181573E+10 81.28 0.00 0.00
April 0.116483E+12 -0.114726E+12 0.00 0.00 720.00 0.00 -0.175717E+10 81.27 0.00 0.00
May 0.118180E+12 -0.116364E+12 0.00 0.00 744.00 0.00 -0.181575E+10 81.27 0.00 0.00
June 0.112245E+12 -0.110488E+12 0.00 0.00 720.00 0.00 -0.175700E+10 81.26 0.00 0.00
July 0.114376E+12 -0.112561E+12 0.00 0.00 744.00 0.00 -0.181520E+10 81.26 0.00 0.00
August 0.113773E+12 -0.111958E+12 0.00 0.00 744.00 0.00 -0.181503E+10 81.26 0.00 0.00
September 0.110669E+12 -0.108914E+12 0.00 0.00 720.00 0.00 -0.175563E+10 81.26 0.00 0.00
October 0.115963E+12 -0.114149E+12 0.00 0.00 744.00 0.00 -0.181380E+10 81.26 0.00 0.00
November 0.114338E+12 -0.112583E+12 0.00 0.00 720.00 0.00 -0.175489E+10 81.26 0.00 0.00
December 0.120338E+12 -0.118524E+12 0.00 0.00 744.00 0.00 -0.181399E+10 81.27 0.00 0.00
                     
Annual Sum or Average 0.139096E+13 -0.136959E+13 0.00 0.00 8760.00 0.00 -0.213688E+11 81.27 0.00 0.00
Minimum of Months 0.110669E+12 -0.120147E+12 0.00 0.00 672.00 0.00 -0.181575E+10 81.26 0.00 0.00
Maximum of Months 0.121962E+12 -0.108914E+12 0.00 0.00 744.00 0.00 -0.163971E+10 81.28 0.00 0.00



Table of Contents

Report: WaterHeaterReportMonthly

For: SWHSYS1 WATER HEATER

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] WATER HEATER BURNER HEATING ENERGY [] WATER HEATER GAS CONSUMPTION [] WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] WATER HEATER LOSS DEMAND ENERGY [] WATER HEATER HEAT LOSS ENERGY [J] WATER HEATER TANK TEMPERATURE [C] WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] WATER HEATER SOURCE ENERGY []
January 0.726773E+11 -0.710927E+11 0.00 0.00 744.00 0.00 -0.158463E+10 58.98 0.00 0.00
February 0.660875E+11 -0.646558E+11 0.00 0.00 672.00 0.00 -0.143172E+10 58.98 0.00 0.00
March 0.727345E+11 -0.711489E+11 0.00 0.00 744.00 0.00 -0.158555E+10 58.98 0.00 0.00
April 0.690414E+11 -0.675066E+11 0.00 0.00 720.00 0.00 -0.153481E+10 58.98 0.00 0.00
May 0.694824E+11 -0.678964E+11 0.00 0.00 744.00 0.00 -0.158595E+10 58.98 0.00 0.00
June 0.654454E+11 -0.639107E+11 0.00 0.00 720.00 0.00 -0.153466E+10 58.98 0.00 0.00
July 0.661807E+11 -0.645952E+11 0.00 0.00 744.00 0.00 -0.158551E+10 58.98 0.00 0.00
August 0.657282E+11 -0.641431E+11 0.00 0.00 744.00 0.00 -0.158510E+10 58.98 0.00 0.00
September 0.640599E+11 -0.625269E+11 0.00 0.00 720.00 0.00 -0.153300E+10 58.98 0.00 0.00
October 0.675416E+11 -0.659583E+11 0.00 0.00 744.00 0.00 -0.158330E+10 58.98 0.00 0.00
November 0.671790E+11 -0.656473E+11 0.00 0.00 720.00 0.00 -0.153172E+10 58.98 0.00 0.00
December 0.712900E+11 -0.697065E+11 0.00 0.00 744.00 0.00 -0.158356E+10 58.98 0.00 0.00
                     
Annual Sum or Average 0.817448E+12 -0.798788E+12 0.00 0.00 8760.00 0.00 -0.186595E+11 58.98 0.00 0.00
Minimum of Months 0.640599E+11 -0.711489E+11 0.00 0.00 672.00 0.00 -0.158595E+10 58.98 0.00 0.00
Maximum of Months 0.727345E+11 -0.625269E+11 0.00 0.00 744.00 0.00 -0.143172E+10 58.98 0.00 0.00



Table of Contents

Report: DaylightingReportMonthly

For: Environment

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER [] DAYLIGHTING LIGHTING POWER MULTIPLIER [] DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME []
January 195.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 217.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 215.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 359.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 417.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 410.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 429.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 396.33 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 337.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 234.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 171.33 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 131.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average 3515.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 131.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 429.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: VAV WITH REHEAT HEATING COIL

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.686782E+10 68711.33 10-JAN-08:00 0.00 0.00 0.00 0.00 0.00
February 0.113908E+10 46783.60 17-FEB-07:10 0.00 0.00 0.00 0.00 0.00
March 31443508.14 13966.71 08-MAR-07:10 0.00 0.00 0.00 0.00 0.00
April 0.198026E+09 15902.93 21-APR-13:10 0.00 0.00 0.00 0.00 0.00
May 0.276652E+09 15970.40 12-MAY-12:50 0.00 0.00 0.00 0.00 0.00
June 0.446125E+09 18330.89 19-JUN-10:04 0.00 0.00 0.00 0.00 0.00
July 0.418641E+09 20753.95 20-JUL-21:30 0.00 0.00 0.00 0.00 0.00
August 0.175606E+09 16219.05 31-AUG-09:10 0.00 0.00 0.00 0.00 0.00
September 0.340002E+09 16312.18 19-SEP-14:50 0.00 0.00 0.00 0.00 0.00
October 0.254979E+09 16024.61 08-OCT-11:10 0.00 0.00 0.00 0.00 0.00
November 0.197647E+09 19534.77 29-NOV-07:20 0.00 0.00 0.00 0.00 0.00
December 0.129531E+10 34697.09 29-DEC-24:00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.116413E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 31443508.14 13966.71   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.686782E+10 68711.33   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: BASEMENT VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.693226E+10 9556.66 17-JAN-11:40 0.00 0.00 0.00 0.00 0.00
February 0.732253E+10 9586.18 22-FEB-11:40 0.00 0.00 0.00 0.00 0.00
March 0.956065E+10 9623.84 25-MAR-10:40 0.00 0.00 0.00 0.00 0.00
April 0.101910E+11 9798.90 30-APR-10:35 0.00 0.00 0.00 0.00 0.00
May 0.106198E+11 9783.08 23-MAY-10:50 0.00 0.00 0.00 0.00 0.00
June 0.997001E+10 9804.17 25-JUN-10:40 0.00 0.00 0.00 0.00 0.00
July 0.914503E+10 9837.67 23-JUL-10:35 0.00 0.00 0.00 0.00 0.00
August 0.846993E+10 9786.66 19-AUG-10:35 0.00 0.00 0.00 0.00 0.00
September 0.615982E+10 9758.75 12-SEP-10:35 0.00 0.00 0.00 0.00 0.00
October 0.464832E+10 9500.98 02-OCT-10:50 0.00 0.00 0.00 0.00 0.00
November 0.383588E+10 7706.50 13-NOV-11:40 0.00 0.00 0.00 0.00 0.00
December 0.492672E+10 7881.80 18-DEC-11:40 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.917820E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.383588E+10 7706.50   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.106198E+11 9837.67   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: RETAIL_1_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.722602E+10 3198.33 29-JAN-11:40 0.00 0.00 0.00 0.00 0.00
February 0.620384E+10 3194.50 26-FEB-11:40 0.00 0.00 0.00 0.00 0.00
March 0.727964E+10 3218.29 19-MAR-10:40 0.00 0.00 0.00 0.00 0.00
April 0.498856E+10 3189.34 10-APR-10:40 0.00 0.00 0.00 0.00 0.00
May 0.532488E+10 3210.16 05-MAY-07:40 0.00 0.00 0.00 0.00 0.00
June 0.465367E+10 3171.14 07-JUN-10:40 0.00 0.00 0.00 0.00 0.00
July 0.437251E+10 2893.34 08-JUL-10:40 0.00 0.00 0.00 0.00 0.00
August 0.403985E+10 2958.74 08-AUG-10:40 0.00 0.00 0.00 0.00 0.00
September 0.403149E+10 3130.09 08-SEP-10:40 0.00 0.00 0.00 0.00 0.00
October 0.600001E+10 3199.83 09-OCT-10:40 0.00 0.00 0.00 0.00 0.00
November 0.685349E+10 3196.47 07-NOV-11:40 0.00 0.00 0.00 0.00 0.00
December 0.780803E+10 3187.52 24-DEC-11:40 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.687820E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.403149E+10 2893.34   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.780803E+10 3218.29   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: RETAIL_2_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.163593E+10 1259.06 04-JAN-11:40 0.00 0.00 0.00 0.00 0.00
February 0.139777E+10 1254.03 27-FEB-11:40 0.00 0.00 0.00 0.00 0.00
March 0.152474E+10 1270.52 13-MAR-10:40 0.00 0.00 0.00 0.00 0.00
April 0.102881E+10 1228.61 11-APR-10:35 0.00 0.00 0.00 0.00 0.00
May 0.103255E+10 1274.42 05-MAY-10:40 0.00 0.00 0.00 0.00 0.00
June 0.814986E+09 1207.71 09-JUN-10:40 0.00 0.00 0.00 0.00 0.00
July 0.766441E+09 1236.20 05-JUL-10:35 0.00 0.00 0.00 0.00 0.00
August 0.724180E+09 1142.02 24-AUG-10:35 0.00 0.00 0.00 0.00 0.00
September 0.780776E+09 1176.43 07-SEP-10:40 0.00 0.00 0.00 0.00 0.00
October 0.124145E+10 1216.10 17-OCT-10:40 0.00 0.00 0.00 0.00 0.00
November 0.148329E+10 1241.10 30-NOV-11:40 0.00 0.00 0.00 0.00 0.00
December 0.182527E+10 1269.63 29-DEC-11:40 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.142562E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.724180E+09 1142.02   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.182527E+10 1274.42   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: MECH_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.278716E+10 1629.69 12-JAN-05:00 0.00 0.00 0.00 0.00 0.00
February 0.246070E+10 1525.83 17-FEB-11:40 0.00 0.00 0.00 0.00 0.00
March 0.244416E+10 1478.71 13-MAR-10:40 0.00 0.00 0.00 0.00 0.00
April 0.186591E+10 1439.07 08-APR-10:40 0.00 0.00 0.00 0.00 0.00
May 0.178137E+10 1442.50 06-MAY-10:35 0.00 0.00 0.00 0.00 0.00
June 0.129441E+10 1253.64 02-JUN-10:40 0.00 0.00 0.00 0.00 0.00
July 0.118836E+10 1254.93 01-JUL-10:40 0.00 0.00 0.00 0.00 0.00
August 0.119701E+10 1200.19 12-AUG-10:35 0.00 0.00 0.00 0.00 0.00
September 0.142747E+10 1271.95 07-SEP-10:40 0.00 0.00 0.00 0.00 0.00
October 0.207755E+10 1375.49 23-OCT-10:40 0.00 0.00 0.00 0.00 0.00
November 0.241702E+10 1460.12 29-NOV-11:40 0.00 0.00 0.00 0.00 0.00
December 0.292372E+10 1553.91 30-DEC-06:00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.238648E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.118836E+10 1200.19   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.292372E+10 1629.69   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: STORAGE_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.185251E+10 948.99 10-JAN-11:40 0.00 0.00 0.00 0.00 0.00
February 0.163611E+10 873.51 18-FEB-11:40 0.00 0.00 0.00 0.00 0.00
March 0.165183E+10 851.29 15-MAR-10:40 0.00 0.00 0.00 0.00 0.00
April 0.126673E+10 801.24 08-APR-10:40 0.00 0.00 0.00 0.00 0.00
May 0.121502E+10 810.14 05-MAY-10:50 0.00 0.00 0.00 0.00 0.00
June 0.892815E+09 698.29 06-JUN-10:40 0.00 0.00 0.00 0.00 0.00
July 0.815959E+09 698.72 01-JUL-10:40 0.00 0.00 0.00 0.00 0.00
August 0.824829E+09 650.56 12-AUG-10:35 0.00 0.00 0.00 0.00 0.00
September 0.984713E+09 709.68 21-SEP-10:35 0.00 0.00 0.00 0.00 0.00
October 0.141957E+10 780.51 23-OCT-10:40 0.00 0.00 0.00 0.00 0.00
November 0.162697E+10 882.38 29-NOV-11:40 0.00 0.00 0.00 0.00 0.00
December 0.193252E+10 909.47 30-DEC-11:40 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.161196E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.815959E+09 650.56   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.193252E+10 948.99   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: LAUNDRY_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.131726E+11 12193.52 09-JAN-05:00 0.00 0.00 0.00 0.00 0.00
February 0.118772E+11 12013.26 18-FEB-06:00 0.00 0.00 0.00 0.00 0.00
March 0.129970E+11 12290.18 25-MAR-10:40 0.00 0.00 0.00 0.00 0.00
April 0.127814E+11 12891.53 30-APR-10:35 0.00 0.00 0.00 0.00 0.00
May 0.131276E+11 12870.70 23-MAY-10:50 0.00 0.00 0.00 0.00 0.00
June 0.128092E+11 12898.46 25-JUN-10:40 0.00 0.00 0.00 0.00 0.00
July 0.133377E+11 12942.53 23-JUL-10:35 0.00 0.00 0.00 0.00 0.00
August 0.133365E+11 12875.41 19-AUG-10:35 0.00 0.00 0.00 0.00 0.00
September 0.127008E+11 12838.70 12-SEP-10:35 0.00 0.00 0.00 0.00 0.00
October 0.128401E+11 12743.23 07-OCT-10:35 0.00 0.00 0.00 0.00 0.00
November 0.125194E+11 12105.42 27-NOV-05:00 0.00 0.00 0.00 0.00 0.00
December 0.133626E+11 12105.51 11-DEC-04:50 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.154862E+12     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.118772E+11 12013.26   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.133626E+11 12942.53   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CAFE_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.161788E+11 10402.20 24-JAN-11:40 0.00 0.00 0.00 0.00 0.00
February 0.135413E+11 10391.59 07-FEB-11:40 0.00 0.00 0.00 0.00 0.00
March 0.162787E+11 10477.69 19-MAR-10:40 0.00 0.00 0.00 0.00 0.00
April 0.101959E+11 10384.19 10-APR-10:40 0.00 0.00 0.00 0.00 0.00
May 0.112301E+11 10500.41 18-MAY-10:40 0.00 0.00 0.00 0.00 0.00
June 0.986658E+10 10480.44 05-JUN-10:40 0.00 0.00 0.00 0.00 0.00
July 0.909917E+10 9453.84 08-JUL-10:40 0.00 0.00 0.00 0.00 0.00
August 0.789875E+10 10510.06 08-AUG-10:40 0.00 0.00 0.00 0.00 0.00
September 0.762753E+10 10488.96 08-SEP-10:40 0.00 0.00 0.00 0.00 0.00
October 0.127336E+11 10440.52 13-OCT-10:40 0.00 0.00 0.00 0.00 0.00
November 0.152277E+11 10406.86 07-NOV-11:40 0.00 0.00 0.00 0.00 0.00
December 0.181373E+11 10364.80 23-DEC-11:40 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.148015E+12     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.762753E+10 9453.84   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.181373E+11 10510.06   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: LOBBY_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.264640E+11 26086.53 04-JAN-11:40 0.00 0.00 0.00 0.00 0.00
February 0.222360E+11 25332.02 16-FEB-11:40 0.00 0.00 0.00 0.00 0.00
March 0.255013E+11 25575.15 15-MAR-10:40 0.00 0.00 0.00 0.00 0.00
April 0.164778E+11 24821.39 10-APR-10:40 0.00 0.00 0.00 0.00 0.00
May 0.176483E+11 24896.30 16-MAY-10:40 0.00 0.00 0.00 0.00 0.00
June 0.150301E+11 24569.31 07-JUN-10:40 0.00 0.00 0.00 0.00 0.00
July 0.142178E+11 23818.86 03-JUL-10:35 0.00 0.00 0.00 0.00 0.00
August 0.126456E+11 23422.08 08-AUG-10:40 0.00 0.00 0.00 0.00 0.00
September 0.119546E+11 24611.35 08-SEP-10:40 0.00 0.00 0.00 0.00 0.00
October 0.197355E+11 24805.47 17-OCT-10:40 0.00 0.00 0.00 0.00 0.00
November 0.241383E+11 25528.37 30-NOV-11:40 0.00 0.00 0.00 0.00 0.00
December 0.298389E+11 25942.57 01-DEC-11:40 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.235888E+12     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.119546E+11 23422.08   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.298389E+11 26086.53   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORRIDOR_FLR_3 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.151141E+11 9541.79 04-JAN-11:40 0.00 0.00 0.00 0.00 0.00
February 0.124121E+11 9079.80 16-FEB-11:40 0.00 0.00 0.00 0.00 0.00
March 0.133575E+11 8784.29 15-MAR-10:40 0.00 0.00 0.00 0.00 0.00
April 0.513912E+10 7357.65 10-APR-10:40 0.00 0.00 0.00 0.00 0.00
May 0.480774E+10 6633.08 17-MAY-10:40 0.00 0.00 0.00 0.00 0.00
June 0.230535E+10 6006.36 07-JUN-10:40 0.00 0.00 0.00 0.00 0.00
July 0.155512E+10 4623.03 08-JUL-10:40 0.00 0.00 0.00 0.00 0.00
August 0.108504E+10 5152.54 09-AUG-10:40 0.00 0.00 0.00 0.00 0.00
September 0.220649E+10 6373.79 08-SEP-10:40 0.00 0.00 0.00 0.00 0.00
October 0.923466E+10 8086.14 20-OCT-10:40 0.00 0.00 0.00 0.00 0.00
November 0.135478E+11 9296.34 30-NOV-15:00 0.00 0.00 0.00 0.00 0.00
December 0.176683E+11 9553.84 15-DEC-11:40 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.984333E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.108504E+10 4623.03   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.176683E+11 9553.84   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORRIDOR_FLR_6 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.127674E+11 6570.81 09-JAN-07:10 0.00 0.00 0.00 0.00 0.00
February 0.108094E+11 6571.01 17-FEB-07:10 0.00 0.00 0.00 0.00 0.00
March 0.113013E+11 6033.24 16-MAR-06:10 0.00 0.00 0.00 0.00 0.00
April 0.691168E+10 5395.02 09-APR-05:00 0.00 0.00 0.00 0.00 0.00
May 0.665957E+10 4800.70 07-MAY-04:40 0.00 0.00 0.00 0.00 0.00
June 0.465581E+10 4465.09 07-JUN-10:40 0.00 0.00 0.00 0.00 0.00
July 0.402596E+10 3978.80 09-JUL-04:30 0.00 0.00 0.00 0.00 0.00
August 0.412631E+10 3740.67 24-AUG-06:05 0.00 0.00 0.00 0.00 0.00
September 0.535783E+10 4612.37 21-SEP-06:10 0.00 0.00 0.00 0.00 0.00
October 0.934364E+10 5462.88 23-OCT-06:05 0.00 0.00 0.00 0.00 0.00
November 0.113298E+11 6387.92 29-NOV-09:02 0.00 0.00 0.00 0.00 0.00
December 0.137273E+11 6571.78 31-DEC-05:50 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.101016E+12     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.402596E+10 3740.67   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.137273E+11 6571.78   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: BANQUET_FLR_6 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.353535E+10 7411.95 10-JAN-11:40 0.00 0.00 0.00 0.00 0.00
February 0.274671E+10 6984.39 17-FEB-11:40 0.00 0.00 0.00 0.00 0.00
March 0.242548E+10 6252.53 13-MAR-10:40 0.00 0.00 0.00 0.00 0.00
April 0.120027E+10 6564.03 14-APR-10:40 0.00 0.00 0.00 0.00 0.00
May 0.101998E+10 6517.85 05-MAY-10:50 0.00 0.00 0.00 0.00 0.00
June 0.581029E+09 5845.61 06-JUN-10:40 0.00 0.00 0.00 0.00 0.00
July 0.459100E+09 5881.67 31-JUL-10:50 0.00 0.00 0.00 0.00 0.00
August 0.680552E+09 6081.30 23-AUG-10:35 0.00 0.00 0.00 0.00 0.00
September 0.103323E+10 6626.28 21-SEP-10:35 0.00 0.00 0.00 0.00 0.00
October 0.205568E+10 6821.00 04-OCT-10:35 0.00 0.00 0.00 0.00 0.00
November 0.286822E+10 6639.31 03-NOV-10:40 0.00 0.00 0.00 0.00 0.00
December 0.381757E+10 6764.53 26-DEC-11:40 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.224232E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.459100E+09 5845.61   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.381757E+10 7411.95   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: DINING_FLR_6 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.286924E+10 7003.54 10-JAN-11:40 0.00 0.00 0.00 0.00 0.00
February 0.217374E+10 6497.26 17-FEB-11:40 0.00 0.00 0.00 0.00 0.00
March 0.181745E+10 5762.22 13-MAR-10:40 0.00 0.00 0.00 0.00 0.00
April 0.753934E+09 6092.75 14-APR-10:40 0.00 0.00 0.00 0.00 0.00
May 0.599382E+09 5940.97 05-MAY-10:45 0.00 0.00 0.00 0.00 0.00
June 0.282071E+09 5274.90 06-JUN-10:40 0.00 0.00 0.00 0.00 0.00
July 0.220545E+09 5307.30 31-JUL-10:40 0.00 0.00 0.00 0.00 0.00
August 0.362076E+09 5440.09 21-AUG-10:35 0.00 0.00 0.00 0.00 0.00
September 0.617871E+09 6063.05 21-SEP-10:40 0.00 0.00 0.00 0.00 0.00
October 0.150350E+10 6390.29 04-OCT-10:35 0.00 0.00 0.00 0.00 0.00
November 0.228350E+10 6201.21 03-NOV-10:40 0.00 0.00 0.00 0.00 0.00
December 0.310587E+10 6354.58 26-DEC-11:40 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.165892E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.220545E+09 5274.90   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.310587E+10 7003.54   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: KITCHEN_FLR_6 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.202129E+10 5553.66 10-JAN-04:00 0.00 0.00 0.00 0.00 0.00
February 0.182651E+10 5313.83 26-FEB-04:00 0.00 0.00 0.00 0.00 0.00
March 0.180255E+10 4796.78 16-MAR-03:00 0.00 0.00 0.00 0.00 0.00
April 0.140907E+10 4372.55 01-APR-03:00 0.00 0.00 0.00 0.00 0.00
May 0.134174E+10 4223.49 05-MAY-03:00 0.00 0.00 0.00 0.00 0.00
June 0.100363E+10 3832.16 08-JUN-03:00 0.00 0.00 0.00 0.00 0.00
July 0.964620E+09 3498.68 09-JUL-03:00 0.00 0.00 0.00 0.00 0.00
August 0.935764E+09 3324.34 23-AUG-03:00 0.00 0.00 0.00 0.00 0.00
September 0.109156E+10 3750.75 17-SEP-03:00 0.00 0.00 0.00 0.00 0.00
October 0.154651E+10 4445.70 23-OCT-03:00 0.00 0.00 0.00 0.00 0.00
November 0.179307E+10 5189.26 29-NOV-04:00 0.00 0.00 0.00 0.00 0.00
December 0.213102E+10 5553.65 30-DEC-04:00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.178673E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.935764E+09 3324.34   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.213102E+10 5553.66   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLR_3_DOAS HEATING COIL

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.445327E+09 5100.86 10-JAN-08:10 0.00 0.00 0.00 0.00 0.00
February 0.120929E+09 3317.51 17-FEB-07:00 0.00 0.00 0.00 0.00 0.00
March 3005469.02 764.00 08-MAR-07:00 0.00 0.00 0.00 0.00 0.00
April 17644.25 0.84 30-APR-19:05 0.00 0.00 0.00 0.00 0.00
May 11118.50 0.91 21-MAY-20:03 0.00 0.00 0.00 0.00 0.00
June 26777.63 0.91 21-JUN-07:02 0.00 0.00 0.00 0.00 0.00
July 46328.27 0.90 16-JUL-14:10 0.00 0.00 0.00 0.00 0.00
August 58125.16 0.90 17-AUG-18:30 0.00 0.00 0.00 0.00 0.00
September 23299.16 0.83 19-SEP-15:40 0.00 0.00 0.00 0.00 0.00
October 2014.16 0.78 11-OCT-13:50 0.00 0.00 0.00 0.00 0.00
November 8384552.07 954.61 29-NOV-02:00 0.00 0.00 0.00 0.00 0.00
December 0.230384E+09 2779.90 29-DEC-24:00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.808216E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 2014.16 0.78   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.445327E+09 5100.86   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_1_FLR_3 FAN COIL HEATING COIL

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.272163E+10 5401.05 04-JAN-09:02 0.00 0.00 0.00 0.00 0.00
February 0.198932E+10 5381.60 01-FEB-16:02 0.00 0.00 0.00 0.00 0.00
March 0.186531E+10 5400.38 15-MAR-15:02 0.00 0.00 0.00 0.00 0.00
April 0.403980E+09 5239.10 10-APR-15:02 0.00 0.00 0.00 0.00 0.00
May 0.293063E+09 5194.18 05-MAY-08:62 0.00 0.00 0.00 0.00 0.00
June 32588910.88 3688.78 18-JUN-08:03 0.00 0.00 0.00 0.00 0.00
July 41000164.72 3557.60 30-JUL-08:03 0.00 0.00 0.00 0.00 0.00
August 10527395.61 3395.02 12-AUG-08:03 0.00 0.00 0.00 0.00 0.00
September 94755200.65 3123.80 06-SEP-18:03 0.00 0.00 0.00 0.00 0.00
October 0.944164E+09 5323.19 19-OCT-15:02 0.00 0.00 0.00 0.00 0.00
November 0.210312E+10 5400.91 30-NOV-16:02 0.00 0.00 0.00 0.00 0.00
December 0.374330E+10 5401.53 16-DEC-16:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.142428E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 10527395.61 3123.80   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.374330E+10 5401.53   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_2_FLR_3 FAN COIL HEATING COIL

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.352297E+10 5313.76 06-JAN-09:02 0.00 0.00 0.00 0.00 0.00
February 0.263464E+10 5314.38 01-FEB-16:02 0.00 0.00 0.00 0.00 0.00
March 0.218354E+10 5312.96 15-MAR-15:02 0.00 0.00 0.00 0.00 0.00
April 0.595344E+09 5178.38 10-APR-15:02 0.00 0.00 0.00 0.00 0.00
May 0.360585E+09 5120.78 05-MAY-08:62 0.00 0.00 0.00 0.00 0.00
June 39207596.75 2869.74 17-JUN-18:04 0.00 0.00 0.00 0.00 0.00
July 45301955.65 3410.02 04-JUL-08:03 0.00 0.00 0.00 0.00 0.00
August 15965955.29 3342.98 12-AUG-08:03 0.00 0.00 0.00 0.00 0.00
September 0.177248E+09 3266.00 10-SEP-08:03 0.00 0.00 0.00 0.00 0.00
October 0.131421E+10 5245.70 27-OCT-15:02 0.00 0.00 0.00 0.00 0.00
November 0.267791E+10 5313.81 21-NOV-16:02 0.00 0.00 0.00 0.00 0.00
December 0.432379E+10 5314.39 02-DEC-16:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.178907E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 15965955.29 2869.74   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.432379E+10 5314.39   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:03 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:03 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.611320E+09 7584.66 17-DEC-04:40 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.611320E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.611320E+09 7584.66   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.537774E+10 29610.85 11-JAN-16:01 0.00 0.00 0.00 0.00 0.00
February 0.334415E+10 28866.68 17-FEB-16:02 0.00 0.00 0.00 0.00 0.00
March 0.112234E+10 28797.21 15-MAR-15:02 0.00 0.00 0.00 0.00 0.00
April 0.154683E+09 22612.69 01-APR-18:04 0.00 0.00 0.00 0.00 0.00
May 72336306.11 19741.39 26-MAY-08:05 0.00 0.00 0.00 0.00 0.00
June 27269480.67 18785.57 27-JUN-08:06 0.00 0.00 0.00 0.00 0.00
July 35504588.01 20724.67 13-JUL-08:06 0.00 0.00 0.00 0.00 0.00
August 32501804.47 25558.68 04-AUG-08:05 0.00 0.00 0.00 0.00 0.00
September 64658019.16 25854.05 29-SEP-15:04 0.00 0.00 0.00 0.00 0.00
October 0.234207E+09 19829.28 06-OCT-18:04 0.00 0.00 0.00 0.00 0.00
November 0.223689E+10 29256.84 29-NOV-16:02 0.00 0.00 0.00 0.00 0.00
December 0.648457E+10 29394.40 27-DEC-16:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.191868E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 27269480.67 18785.57   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.648457E+10 29610.85   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_5_FLR_3 FAN COIL HEATING COIL

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.277472E+10 5311.65 04-JAN-09:02 0.00 0.00 0.00 0.00 0.00
February 0.212645E+10 5307.08 01-FEB-16:02 0.00 0.00 0.00 0.00 0.00
March 0.191520E+10 5310.95 15-MAR-15:02 0.00 0.00 0.00 0.00 0.00
April 0.390223E+09 5133.34 10-APR-15:02 0.00 0.00 0.00 0.00 0.00
May 0.304573E+09 2733.06 14-MAY-15:04 0.00 0.00 0.00 0.00 0.00
June 58507511.81 3146.89 03-JUN-15:04 0.00 0.00 0.00 0.00 0.00
July 31792508.65 2876.28 02-JUL-15:04 0.00 0.00 0.00 0.00 0.00
August 9574386.79 2967.44 26-AUG-15:04 0.00 0.00 0.00 0.00 0.00
September 75798001.03 2550.42 08-SEP-15:04 0.00 0.00 0.00 0.00 0.00
October 0.958645E+09 5239.26 27-OCT-15:02 0.00 0.00 0.00 0.00 0.00
November 0.214492E+10 5311.50 30-NOV-16:02 0.00 0.00 0.00 0.00 0.00
December 0.364919E+10 5312.13 16-DEC-16:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.144396E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 9574386.79 2550.42   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.364919E+10 5312.13   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_6_FLR_3 FAN COIL HEATING COIL

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.353819E+10 5225.95 04-JAN-09:02 0.00 0.00 0.00 0.00 0.00
February 0.281377E+10 5226.74 01-FEB-16:02 0.00 0.00 0.00 0.00 0.00
March 0.222934E+10 5225.21 15-MAR-15:02 0.00 0.00 0.00 0.00 0.00
April 0.555341E+09 5071.95 10-APR-15:02 0.00 0.00 0.00 0.00 0.00
May 0.381070E+09 2923.91 04-MAY-08:63 0.00 0.00 0.00 0.00 0.00
June 75998564.20 3206.09 17-JUN-15:04 0.00 0.00 0.00 0.00 0.00
July 40157225.28 2730.75 07-JUL-15:04 0.00 0.00 0.00 0.00 0.00
August 19632641.35 2674.59 22-AUG-15:05 0.00 0.00 0.00 0.00 0.00
September 0.155493E+09 3548.84 29-SEP-18:03 0.00 0.00 0.00 0.00 0.00
October 0.130437E+10 5163.44 27-OCT-15:02 0.00 0.00 0.00 0.00 0.00
November 0.269280E+10 5226.13 21-NOV-16:02 0.00 0.00 0.00 0.00 0.00
December 0.418289E+10 5226.67 02-DEC-16:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.179890E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 19632641.35 2674.59   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.418289E+10 5226.74   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_1_FLR_6 FAN COIL HEATING COIL

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.108008E+10 1674.58 14-JAN-09:02 0.00 0.00 0.00 0.00 0.00
February 0.797625E+09 1674.82 01-FEB-09:02 0.00 0.00 0.00 0.00 0.00
March 0.752785E+09 1674.41 16-MAR-08:62 0.00 0.00 0.00 0.00 0.00
April 0.193784E+09 1643.08 10-APR-15:02 0.00 0.00 0.00 0.00 0.00
May 0.139148E+09 1626.30 05-MAY-08:62 0.00 0.00 0.00 0.00 0.00
June 21428835.43 906.44 03-JUN-08:03 0.00 0.00 0.00 0.00 0.00
July 21359725.24 939.39 30-JUL-08:03 0.00 0.00 0.00 0.00 0.00
August 5903973.57 819.98 03-AUG-08:03 0.00 0.00 0.00 0.00 0.00
September 53648764.18 872.26 02-SEP-08:03 0.00 0.00 0.00 0.00 0.00
October 0.421755E+09 1674.60 19-OCT-15:02 0.00 0.00 0.00 0.00 0.00
November 0.847078E+09 1674.96 24-NOV-16:02 0.00 0.00 0.00 0.00 0.00
December 0.140450E+10 1674.79 05-DEC-09:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.573910E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 5903973.57 819.98   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.140450E+10 1674.96   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_2_FLR_6 FAN COIL HEATING COIL

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.133645E+10 1640.83 23-JAN-09:02 0.00 0.00 0.00 0.00 0.00
February 0.100758E+10 1641.09 01-FEB-09:02 0.00 0.00 0.00 0.00 0.00
March 0.858257E+09 1640.62 16-MAR-08:62 0.00 0.00 0.00 0.00 0.00
April 0.263473E+09 1618.69 10-APR-15:02 0.00 0.00 0.00 0.00 0.00
May 0.165748E+09 1596.69 05-MAY-08:62 0.00 0.00 0.00 0.00 0.00
June 25909419.05 869.18 18-JUN-08:03 0.00 0.00 0.00 0.00 0.00
July 23130384.30 920.47 30-JUL-08:03 0.00 0.00 0.00 0.00 0.00
August 11407807.26 810.19 26-AUG-15:04 0.00 0.00 0.00 0.00 0.00
September 93115162.24 1572.28 20-SEP-08:62 0.00 0.00 0.00 0.00 0.00
October 0.554014E+09 1640.99 16-OCT-15:02 0.00 0.00 0.00 0.00 0.00
November 0.103300E+10 1641.20 24-NOV-16:02 0.00 0.00 0.00 0.00 0.00
December 0.158705E+10 1641.02 05-DEC-09:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.695914E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 11407807.26 810.19   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.158705E+10 1641.20   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.246528E+10 8256.34 04-JAN-16:02 0.00 0.00 0.00 0.00 0.00
February 0.178202E+10 8156.73 02-FEB-09:02 0.00 0.00 0.00 0.00 0.00
March 0.185833E+10 8214.03 15-MAR-15:02 0.00 0.00 0.00 0.00 0.00
April 0.340286E+09 5820.14 10-APR-15:02 0.00 0.00 0.00 0.00 0.00
May 0.305775E+09 4505.89 24-MAY-08:03 0.00 0.00 0.00 0.00 0.00
June 46547069.21 5040.16 20-JUN-08:03 0.00 0.00 0.00 0.00 0.00
July 31210456.06 4815.72 12-JUL-08:03 0.00 0.00 0.00 0.00 0.00
August 8929691.04 5029.63 04-AUG-08:03 0.00 0.00 0.00 0.00 0.00
September 42138440.10 4193.54 17-SEP-08:03 0.00 0.00 0.00 0.00 0.00
October 0.696526E+09 8085.60 27-OCT-15:02 0.00 0.00 0.00 0.00 0.00
November 0.175585E+10 8257.14 30-NOV-16:02 0.00 0.00 0.00 0.00 0.00
December 0.387065E+10 8258.07 16-DEC-16:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.132035E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 8929691.04 4193.54   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.387065E+10 8258.07   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: VAV WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 6818783.35 6818783.35 6819.07 29-JAN-06:00 6819.07 0.00
February 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 0.00 0.00
March 0.00 0.00 4067563.16 4067563.16 6762.51 25-MAR-13:00 6762.51 0.00
April 0.00 0.00 0.309439E+11 0.308306E+11 279294.24 30-APR-18:10 279294.24 0.04
May 0.00 0.00 0.333113E+11 0.333113E+11 257668.21 22-MAY-15:30 257668.21 0.11
June 0.00 0.00 0.103271E+12 0.969350E+11 487407.05 25-JUN-18:17 236831.18 0.41
July 0.00 0.00 0.177173E+12 0.169732E+12 380312.18 22-JUL-10:35 317906.95 0.61
August 0.00 0.00 0.210060E+12 0.201853E+12 349922.15 14-AUG-10:35 271817.17 0.69
September 0.00 0.00 0.113591E+12 0.110409E+12 293907.01 10-SEP-16:00 225845.66 0.44
October 0.00 0.00 0.809054E+10 0.809054E+10 149490.71 07-OCT-15:20 149490.71 0.03
November 0.00 0.00 0.223888E+09 0.223888E+09 68230.25 24-NOV-11:50 68230.25 0.00
December 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 0.00 0.00
                 
Annual Sum or Average 0.00 0.00 0.676676E+12 0.651396E+12       0.19
Minimum of Months 0.00 0.00 0.00 0.00 0.00   0.00 0.00
Maximum of Months 0.00 0.00 0.210060E+12 0.201853E+12 487407.05   317906.95 0.69



Table of Contents

Report: CoilReportMonthly

For: FLR_3_DOAS COOLING COIL

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 01-MAR-00:03 0.00 0.00
April 0.00 0.00 0.246108E+10 0.245921E+10 28621.53 30-APR-18:02 28621.53 0.03
May 0.00 0.00 0.246348E+10 0.246348E+10 28400.77 22-MAY-15:00 28400.77 0.08
June 0.00 0.00 0.833263E+10 0.762647E+10 45838.53 25-JUN-18:00 20538.48 0.27
July 0.00 0.00 0.147069E+11 0.139146E+11 34524.85 23-JUL-16:00 24929.04 0.47
August 0.00 0.00 0.178711E+11 0.169080E+11 34502.27 17-AUG-15:00 25039.96 0.56
September 0.00 0.00 0.919189E+10 0.876880E+10 32609.72 12-SEP-14:00 22710.87 0.33
October 0.00 0.00 0.434540E+09 0.434540E+09 15105.80 07-OCT-15:00 15105.80 0.01
November 0.00 0.00 6967953.45 6967953.45 4049.57 24-NOV-12:00 4049.57 0.00
December 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 0.00 0.00
                 
Annual Sum or Average 0.00 0.00 0.554687E+11 0.525820E+11       0.15
Minimum of Months 0.00 0.00 0.00 0.00 0.00   0.00 0.00
Maximum of Months 0.00 0.00 0.178711E+11 0.169080E+11 45838.53   28621.53 0.56



Table of Contents

Report: CoilReportMonthly

For: ROOM_1_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 49961726.72 27665834.08 13848.27 25-JAN-16:01 13848.27 0.02
February 0.00 0.00 0.251777E+09 0.223900E+09 17442.06 09-FEB-16:01 17442.06 0.02
March 0.00 0.00 0.148833E+09 0.125953E+09 17019.93 20-MAR-18:02 17019.93 0.02
April 0.00 0.00 0.310788E+10 0.235885E+10 17443.39 16-APR-18:01 17443.39 0.35
May 0.00 0.00 0.366562E+10 0.242128E+10 17442.63 29-MAY-18:02 17442.63 0.51
June 0.00 0.00 0.541757E+10 0.314633E+10 19084.52 27-JUN-08:62 14668.52 0.77
July 0.00 0.00 0.677845E+10 0.395179E+10 18424.54 18-JUL-15:02 15926.88 0.80
August 0.00 0.00 0.631989E+10 0.348576E+10 19014.40 11-AUG-15:01 15263.67 0.87
September 0.00 0.00 0.463672E+10 0.261315E+10 18403.18 19-SEP-15:02 15366.04 0.71
October 0.00 0.00 0.110357E+10 0.707337E+09 17438.84 07-OCT-15:02 17438.84 0.21
November 0.00 0.00 62416711.75 40049363.14 17371.64 03-NOV-15:01 17371.64 0.02
December 0.00 0.00 1333379.28 727366.99 1758.17 20-DEC-19:05 625.37 0.00
                 
Annual Sum or Average 0.00 0.00 0.315440E+11 0.191028E+11       0.36
Minimum of Months 0.00 0.00 1333379.28 727366.99 1758.17   625.37 0.00
Maximum of Months 0.00 0.00 0.677845E+10 0.395179E+10 19084.52   17443.39 0.87



Table of Contents

Report: CoilReportMonthly

For: ROOM_2_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 6353835.19 2612811.09 10034.87 19-JAN-16:01 9265.00 0.00
February 0.00 0.00 70422738.66 61249054.75 14748.13 19-FEB-16:02 14748.13 0.01
March 0.00 0.00 77928660.08 68066188.26 14838.60 20-MAR-18:02 14838.60 0.01
April 0.00 0.00 0.195476E+10 0.148247E+10 15607.82 17-APR-15:02 15607.82 0.25
May 0.00 0.00 0.287266E+10 0.194040E+10 15607.24 29-MAY-18:02 15607.24 0.42
June 0.00 0.00 0.478536E+10 0.286091E+10 17046.44 27-JUN-08:62 13062.12 0.71
July 0.00 0.00 0.584941E+10 0.346332E+10 16557.58 18-JUL-15:02 14212.55 0.75
August 0.00 0.00 0.470072E+10 0.255919E+10 16878.89 11-AUG-18:02 14066.66 0.76
September 0.00 0.00 0.266203E+10 0.144750E+10 16248.04 02-SEP-18:02 13826.67 0.53
October 0.00 0.00 0.429624E+09 0.290441E+09 15602.71 07-OCT-15:02 15602.71 0.09
November 0.00 0.00 11172250.42 7899018.29 8992.55 10-NOV-16:02 8808.01 0.00
December 0.00 0.00 100458.08 30120.70 858.75 02-DEC-09:05 206.31 0.00
                 
Annual Sum or Average 0.00 0.00 0.234205E+11 0.141841E+11       0.30
Minimum of Months 0.00 0.00 100458.08 30120.70 858.75   206.31 0.00
Maximum of Months 0.00 0.00 0.584941E+10 0.346332E+10 17046.44   15607.82 0.76



Table of Contents

Report: CoilReportMonthly

For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.483953E+10 0.443967E+10 40129.05 21-JAN-11:25 40129.05 0.03
February 0.00 0.00 0.518336E+10 0.490526E+10 35724.21 04-FEB-14:00 35724.21 0.02
March 0.00 0.00 0.266107E+09 0.218088E+09 12965.78 25-MAR-11:40 12965.78 0.01
April 0.00 0.00 0.279663E+11 0.259005E+11 50667.71 30-APR-12:30 50460.94 0.12
May 0.00 0.00 0.219573E+11 0.152986E+11 41368.51 23-MAY-13:00 28397.59 0.34
June 0.00 0.00 0.265572E+11 0.116983E+11 40575.61 13-JUN-13:10 28245.03 0.68
July 0.00 0.00 0.333793E+11 0.154748E+11 47050.33 22-JUL-13:10 38555.30 0.76
August 0.00 0.00 0.400160E+11 0.217659E+11 51889.83 19-AUG-12:50 43061.14 0.79
September 0.00 0.00 0.458117E+11 0.293918E+11 64095.34 23-SEP-14:30 52094.47 0.72
October 0.00 0.00 0.186119E+11 0.147188E+11 59066.09 07-OCT-13:10 59066.09 0.22
November 0.00 0.00 0.375125E+10 0.335427E+10 38365.73 11-NOV-13:30 38365.73 0.02
December 0.00 0.00 0.193796E+09 0.193796E+09 12782.98 26-DEC-14:30 12782.98 0.00
                 
Annual Sum or Average 0.00 0.00 0.228534E+12 0.147360E+12       0.31
Minimum of Months 0.00 0.00 0.193796E+09 0.193796E+09 12782.98   12782.98 0.00
Maximum of Months 0.00 0.00 0.458117E+11 0.293918E+11 64095.34   59066.09 0.79



Table of Contents

Report: CoilReportMonthly

For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.397135E+10 0.203052E+10 68115.58 29-JAN-19:02 68115.58 0.20
February 0.00 0.00 0.368559E+10 0.229004E+10 73288.34 12-FEB-09:02 73288.34 0.16
March 0.00 0.00 0.102947E+11 0.740858E+10 76155.67 11-MAR-09:02 76155.67 0.27
April 0.00 0.00 0.233654E+11 0.183338E+11 79550.06 22-APR-15:02 79550.06 0.45
May 0.00 0.00 0.314232E+11 0.219693E+11 80746.96 23-MAY-15:02 74400.30 0.64
June 0.00 0.00 0.457088E+11 0.306776E+11 89052.07 26-JUN-18:02 70853.90 0.70
July 0.00 0.00 0.504623E+11 0.337060E+11 84684.00 25-JUL-15:02 73220.53 0.71
August 0.00 0.00 0.439096E+11 0.274162E+11 86170.75 11-AUG-15:01 70262.26 0.70
September 0.00 0.00 0.319454E+11 0.192857E+11 84855.17 16-SEP-08:62 68510.90 0.70
October 0.00 0.00 0.155821E+11 0.828760E+10 80430.89 09-OCT-08:62 72738.18 0.58
November 0.00 0.00 0.648716E+10 0.329906E+10 77258.89 08-NOV-19:03 70513.10 0.31
December 0.00 0.00 0.205604E+10 0.112322E+10 62577.53 02-DEC-09:02 62577.53 0.11
                 
Annual Sum or Average 0.00 0.00 0.268892E+12 0.175828E+12       0.46
Minimum of Months 0.00 0.00 0.205604E+10 0.112322E+10 62577.53   62577.53 0.11
Maximum of Months 0.00 0.00 0.504623E+11 0.337060E+11 89052.07   79550.06 0.71



Table of Contents

Report: CoilReportMonthly

For: ROOM_5_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.108374E+09 55059275.29 9839.28 21-JAN-16:02 9078.73 0.02
February 0.00 0.00 0.179290E+09 0.121510E+09 14973.91 04-FEB-16:01 14973.91 0.03
March 0.00 0.00 0.121181E+09 81728651.96 13338.00 20-MAR-15:01 13338.00 0.02
April 0.00 0.00 0.350823E+10 0.267003E+10 15850.09 17-APR-15:02 15850.09 0.37
May 0.00 0.00 0.366563E+10 0.226648E+10 15848.97 02-MAY-15:02 15848.97 0.56
June 0.00 0.00 0.503741E+10 0.281164E+10 17451.68 27-JUN-08:62 13327.95 0.77
July 0.00 0.00 0.633149E+10 0.356296E+10 16843.18 28-JUL-15:01 14472.07 0.84
August 0.00 0.00 0.663048E+10 0.370201E+10 17293.30 11-AUG-15:01 13966.24 0.89
September 0.00 0.00 0.519220E+10 0.296899E+10 16866.72 02-SEP-08:62 13792.29 0.77
October 0.00 0.00 0.118751E+10 0.742591E+09 15845.66 07-OCT-15:02 15845.66 0.22
November 0.00 0.00 0.105128E+09 62226146.73 14714.48 03-NOV-15:01 14714.48 0.02
December 0.00 0.00 29268839.52 15325714.17 2894.65 06-DEC-09:03 1730.63 0.01
                 
Annual Sum or Average 0.00 0.00 0.320962E+11 0.190606E+11       0.38
Minimum of Months 0.00 0.00 29268839.52 15325714.17 2894.65   1730.63 0.01
Maximum of Months 0.00 0.00 0.663048E+10 0.370201E+10 17451.68   15850.09 0.89



Table of Contents

Report: CoilReportMonthly

For: ROOM_6_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 9111572.95 2573627.78 2640.41 19-JAN-09:03 1468.00 0.01
February 0.00 0.00 36580418.67 20076180.46 9308.76 20-FEB-09:02 9048.45 0.02
March 0.00 0.00 42920641.72 24623906.10 3786.21 10-MAR-09:02 2989.37 0.02
April 0.00 0.00 0.221858E+10 0.164160E+10 14298.66 20-APR-08:62 14298.66 0.31
May 0.00 0.00 0.280307E+10 0.176907E+10 14555.62 23-MAY-15:02 13323.61 0.48
June 0.00 0.00 0.436619E+10 0.251687E+10 15726.88 27-JUN-08:62 11962.07 0.70
July 0.00 0.00 0.533014E+10 0.305281E+10 15238.34 25-JUL-15:02 13002.45 0.81
August 0.00 0.00 0.489475E+10 0.266871E+10 15455.62 11-AUG-15:01 12357.88 0.84
September 0.00 0.00 0.303582E+10 0.166491E+10 15108.36 02-SEP-08:62 12218.01 0.60
October 0.00 0.00 0.437056E+09 0.250412E+09 13700.19 07-OCT-15:02 13700.19 0.11
November 0.00 0.00 14554033.57 5069846.51 4560.61 11-NOV-09:02 3984.60 0.01
December 0.00 0.00 1223460.61 481602.79 1850.75 11-DEC-09:05 835.35 0.00
                 
Annual Sum or Average 0.00 0.00 0.231900E+11 0.136172E+11       0.33
Minimum of Months 0.00 0.00 1223460.61 481602.79 1850.75   835.35 0.00
Maximum of Months 0.00 0.00 0.533014E+10 0.305281E+10 15726.88   14298.66 0.84



Table of Contents

Report: CoilReportMonthly

For: ROOM_1_FLR_6 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 9907519.64 5915679.90 3686.22 25-JAN-16:01 3686.22 0.01
February 0.00 0.00 64342783.93 59044578.05 4669.85 09-FEB-16:01 4669.85 0.01
March 0.00 0.00 33232519.72 29251211.92 4623.00 20-MAR-18:02 4623.00 0.01
April 0.00 0.00 0.894364E+09 0.714605E+09 4670.34 06-APR-18:01 4670.34 0.30
May 0.00 0.00 0.103773E+10 0.722846E+09 4670.04 29-MAY-18:02 4670.04 0.46
June 0.00 0.00 0.155390E+10 0.960143E+09 5271.68 27-JUN-08:62 3837.36 0.74
July 0.00 0.00 0.195809E+10 0.120627E+10 5029.43 18-JUL-08:62 3894.66 0.81
August 0.00 0.00 0.179425E+10 0.105276E+10 5138.51 11-AUG-15:01 4158.28 0.86
September 0.00 0.00 0.125693E+10 0.750021E+09 4999.27 02-SEP-08:62 3818.87 0.67
October 0.00 0.00 0.282028E+09 0.192192E+09 4669.02 07-OCT-15:02 4669.02 0.16
November 0.00 0.00 13681357.36 9405639.54 4623.13 03-NOV-15:01 4623.13 0.01
December 0.00 0.00 80784.45 65021.44 333.51 26-DEC-16:05 333.51 0.00
                 
Annual Sum or Average 0.00 0.00 0.889854E+10 0.570251E+10       0.34
Minimum of Months 0.00 0.00 80784.45 65021.44 333.51   333.51 0.00
Maximum of Months 0.00 0.00 0.195809E+10 0.120627E+10 5271.68   4670.34 0.86



Table of Contents

Report: CoilReportMonthly

For: ROOM_2_FLR_6 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 1060553.34 476762.93 1438.13 19-JAN-16:01 1354.96 0.00
February 0.00 0.00 13041292.02 10858633.35 3402.17 19-FEB-16:02 3402.17 0.00
March 0.00 0.00 16727962.15 14704498.11 3981.05 20-MAR-18:02 3981.05 0.01
April 0.00 0.00 0.572491E+09 0.456072E+09 4150.31 17-APR-15:02 4150.31 0.22
May 0.00 0.00 0.812806E+09 0.581077E+09 4150.09 29-MAY-18:02 4150.09 0.38
June 0.00 0.00 0.137083E+10 0.870226E+09 4678.84 27-JUN-08:62 3393.30 0.69
July 0.00 0.00 0.169168E+10 0.105812E+10 4460.58 18-JUL-08:62 3442.46 0.77
August 0.00 0.00 0.134067E+10 0.779053E+09 4518.44 11-AUG-15:01 3616.36 0.75
September 0.00 0.00 0.718698E+09 0.416298E+09 4310.13 02-SEP-18:02 3695.48 0.48
October 0.00 0.00 0.106560E+09 77854850.43 4148.92 07-OCT-15:02 4148.92 0.07
November 0.00 0.00 1408423.27 707075.90 1699.14 10-NOV-16:02 1296.42 0.00
December 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 0.00 0.00
                 
Annual Sum or Average 0.00 0.00 0.664598E+10 0.426545E+10       0.28
Minimum of Months 0.00 0.00 0.00 0.00 0.00   0.00 0.00
Maximum of Months 0.00 0.00 0.169168E+10 0.105812E+10 4678.84   4150.31 0.77



Table of Contents

Report: CoilReportMonthly

For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.151551E+10 0.994676E+09 25972.16 01-JAN-16:01 25972.16 0.16
February 0.00 0.00 0.187154E+10 0.150479E+10 25980.12 05-FEB-16:01 25980.12 0.14
March 0.00 0.00 0.695490E+09 0.528520E+09 25974.45 20-MAR-15:01 25974.45 0.08
April 0.00 0.00 0.687770E+10 0.537162E+10 25979.53 27-APR-18:02 25979.53 0.44
May 0.00 0.00 0.587780E+10 0.343414E+10 25978.99 06-MAY-15:02 25978.99 0.61
June 0.00 0.00 0.774384E+10 0.404928E+10 28636.45 26-JUN-18:02 23195.00 0.82
July 0.00 0.00 0.100107E+11 0.546686E+10 27034.59 24-JUL-18:02 23943.85 0.84
August 0.00 0.00 0.115311E+11 0.670179E+10 28673.92 11-AUG-15:01 23104.73 0.90
September 0.00 0.00 0.111078E+11 0.720371E+10 27647.58 19-SEP-15:02 23591.63 0.85
October 0.00 0.00 0.432570E+10 0.279127E+10 25978.39 07-OCT-18:02 25978.39 0.43
November 0.00 0.00 0.124368E+10 0.834309E+09 25974.12 19-NOV-16:01 25974.12 0.14
December 0.00 0.00 0.432071E+09 0.362869E+09 25539.83 18-DEC-16:02 25539.83 0.03
                 
Annual Sum or Average 0.00 0.00 0.632330E+11 0.392438E+11       0.45
Minimum of Months 0.00 0.00 0.432071E+09 0.362869E+09 25539.83   23104.73 0.03
Maximum of Months 0.00 0.00 0.115311E+11 0.720371E+10 28673.92   25980.12 0.90



Table of Contents

Report: PlantLoopDemandReportMonthly

For: HEATSYS1

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:05 52811.01 181124.91 10-JAN-09:02
February 0.00 0.00 01-FEB-00:03 46879.00 124686.34 13-FEB-09:02
March 0.00 0.00 01-MAR-00:03 44692.09 115676.90 04-MAR-16:02
April 0.00 0.00 01-APR-00:10 29565.75 86853.70 11-APR-10:35
May 0.00 0.00 01-MAY-00:10 29144.84 90019.11 05-MAY-10:35
June 0.00 0.00 01-JUN-00:10 24850.32 88889.83 06-JUN-10:35
July 0.00 0.00 01-JUL-00:10 22537.95 88642.58 03-JUL-10:35
August 0.00 0.00 01-AUG-00:10 20968.71 84660.74 01-AUG-10:35
September 0.00 0.00 01-SEP-00:10 21841.26 86469.58 08-SEP-10:40
October 0.00 0.00 01-OCT-00:10 33712.49 102972.85 19-OCT-08:03
November 0.00 0.00 01-NOV-00:10 44221.10 119859.29 29-NOV-09:02
December 0.00 0.00 01-DEC-00:03 56475.49 147074.25 27-DEC-09:03
             
Annual Sum or Average 0.00     35609.82    
Minimum of Months 0.00 0.00   20968.71 84660.74  
Maximum of Months 0.00 0.00   56475.49 181124.91  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: COOLSYS1

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 5507.15 66236.67 21-JAN-16:03 0.00 0.00 01-JAN-00:05
February 6450.60 72503.24 09-FEB-16:03 0.00 0.00 01-FEB-00:03
March 6316.32 66091.29 20-MAR-18:02 0.00 0.00 01-MAR-00:03
April 44412.29 480953.75 30-APR-18:03 0.00 0.00 01-APR-00:10
May 45421.38 475015.75 22-MAY-15:03 0.00 0.00 01-MAY-00:10
June 87673.43 696306.66 25-JUN-18:20 0.00 0.00 01-JUN-00:10
July 122532.78 586470.04 23-JUL-18:03 0.00 0.00 01-JUL-00:10
August 135904.85 526326.30 14-AUG-18:03 0.00 0.00 01-AUG-00:10
September 93568.15 504083.82 11-SEP-18:03 0.00 0.00 01-SEP-00:10
October 22256.18 357903.45 07-OCT-15:02 0.00 0.00 01-OCT-00:10
November 6544.53 78007.89 03-NOV-15:03 0.00 0.00 01-NOV-00:10
December 1904.07 27364.55 25-DEC-09:02 0.00 0.00 01-DEC-00:03
             
Annual Sum or Average 48443.00     0.00    
Minimum of Months 1904.07 27364.55   0.00 0.00  
Maximum of Months 135904.85 696306.66   0.00 0.00  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:05 28107.74 57262.29 30-JAN-07:10
February 0.00 0.00 01-FEB-00:03 28290.00 57352.02 10-FEB-07:10
March 0.00 0.00 01-MAR-00:03 28129.52 57271.83 01-MAR-07:10
April 0.00 0.00 01-APR-00:10 27610.44 56427.23 03-APR-06:10
May 0.00 0.00 01-MAY-00:10 26917.24 55165.04 02-MAY-06:20
June 0.00 0.00 01-JUN-00:10 26226.60 53659.01 01-JUN-06:20
July 0.00 0.00 01-JUL-00:10 25687.17 52256.62 03-JUL-07:00
August 0.00 0.00 01-AUG-00:10 25519.24 51551.10 31-AUG-06:30
September 0.00 0.00 01-SEP-00:10 25693.35 52266.40 29-SEP-06:10
October 0.00 0.00 01-OCT-00:10 26195.49 53631.83 31-OCT-06:10
November 0.00 0.00 01-NOV-00:10 26894.27 55137.63 30-NOV-08:00
December 0.00 0.00 01-DEC-00:03 27591.49 56408.98 29-DEC-07:40
             
Annual Sum or Average 0.00     26897.11    
Minimum of Months 0.00 0.00   25519.24 51551.10  
Maximum of Months 0.00 0.00   28290.00 57352.02  



Table of Contents

Report: FanReportMonthly

For: FLR_3_DOAS FAN

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.587890E+10 0.89 2194.93 01-JAN-00:05 0.89
February 0.530997E+10 0.89 2194.93 01-FEB-00:03 0.88
March 0.587890E+10 0.89 2194.93 01-MAR-00:03 0.88
April 0.568926E+10 0.89 2194.93 01-APR-00:10 0.89
May 0.587890E+10 0.88 2194.93 01-MAY-00:10 0.88
June 0.568926E+10 0.88 2194.93 01-JUN-00:10 0.88
July 0.587890E+10 0.88 2194.93 01-JUL-00:10 0.88
August 0.587890E+10 0.88 2194.93 01-AUG-00:10 0.88
September 0.568926E+10 0.88 2194.93 01-SEP-00:10 0.88
October 0.587890E+10 0.88 2194.93 01-OCT-00:10 0.88
November 0.568926E+10 0.88 2194.93 01-NOV-00:10 0.89
December 0.587890E+10 0.89 2194.93 01-DEC-00:03 0.88
           
Annual Sum or Average 0.692193E+11 0.88      
Minimum of Months 0.530997E+10 0.88 2194.93   0.88
Maximum of Months 0.587890E+10 0.89 2194.93   0.89



Table of Contents

Report: FanReportMonthly

For: VAV WITH REHEAT FAN

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.135338E+12 1.85 50529.57 01-JAN-00:05 1.85
February 0.122241E+12 1.85 50529.57 01-FEB-00:03 1.85
March 0.135338E+12 1.85 50529.57 01-MAR-00:03 1.85
April 0.130972E+12 1.85 50529.57 01-APR-00:10 1.86
May 0.135337E+12 1.85 50529.57 01-MAY-00:10 1.85
June 0.130970E+12 1.84 50529.57 01-JUN-00:10 1.85
July 0.135337E+12 1.84 50529.57 01-JUL-00:10 1.85
August 0.135338E+12 1.84 50529.57 01-AUG-00:10 1.85
September 0.130971E+12 1.85 50529.57 01-SEP-00:10 1.84
October 0.135337E+12 1.85 50529.57 01-OCT-00:10 1.85
November 0.130973E+12 1.85 50529.57 01-NOV-00:10 1.85
December 0.135338E+12 1.85 50529.57 01-DEC-00:03 1.85
           
Annual Sum or Average 0.159349E+13 1.85      
Minimum of Months 0.122241E+12 1.84 50529.57   1.84
Maximum of Months 0.135338E+12 1.85 50529.57   1.86



Table of Contents

Report: FanReportMonthly

For: LAUNDRY_FLR_1 EXHAUST FAN

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.493775E+09 0.65 184.35 01-JAN-00:05 0.65
February 0.445990E+09 0.65 184.35 01-FEB-00:03 0.65
March 0.493775E+09 0.65 184.35 01-MAR-00:03 0.65
April 0.477847E+09 0.65 184.35 01-APR-00:10 0.65
May 0.493775E+09 0.65 184.35 01-MAY-00:10 0.65
June 0.477847E+09 0.64 184.35 01-JUN-00:10 0.65
July 0.493775E+09 0.64 184.35 01-JUL-00:10 0.64
August 0.493775E+09 0.64 184.35 01-AUG-00:10 0.64
September 0.477847E+09 0.64 184.35 01-SEP-00:10 0.64
October 0.493775E+09 0.64 184.35 01-OCT-00:10 0.65
November 0.477847E+09 0.65 184.35 01-NOV-00:10 0.65
December 0.493775E+09 0.65 184.35 01-DEC-00:03 0.65
           
Annual Sum or Average 0.581380E+10 0.65      
Minimum of Months 0.445990E+09 0.64 184.35   0.64
Maximum of Months 0.493775E+09 0.65 184.35   0.65



Table of Contents

Report: FanReportMonthly

For: LOBBY_FLR_1 EXHAUST FAN

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.00 0.00 0.00 01-JAN-00:05 0.00
February 0.00 0.00 0.00 01-FEB-00:03 0.00
March 0.00 0.00 0.00 01-MAR-00:03 0.00
April 0.00 0.00 0.00 01-APR-00:10 0.00
May 0.00 0.00 0.00 01-MAY-00:10 0.00
June 0.00 0.00 0.00 01-JUN-00:10 0.00
July 0.00 0.00 0.00 01-JUL-00:10 0.00
August 0.00 0.00 0.00 01-AUG-00:10 0.00
September 0.00 0.00 0.00 01-SEP-00:10 0.00
October 0.00 0.00 0.00 01-OCT-00:10 0.00
November 0.00 0.00 0.00 01-NOV-00:10 0.00
December 0.00 0.00 0.00 01-DEC-00:03 0.00
           
Annual Sum or Average 0.00 0.00      
Minimum of Months 0.00 0.00 0.00   0.00
Maximum of Months 0.00 0.00 0.00   0.00



Table of Contents

Report: FanReportMonthly

For: BANQUET_FLR_6 EXHAUST FAN

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.00 0.00 0.00 01-JAN-00:05 0.00
February 0.00 0.00 0.00 01-FEB-00:03 0.00
March 0.00 0.00 0.00 01-MAR-00:03 0.00
April 0.00 0.00 0.00 01-APR-00:10 0.00
May 0.00 0.00 0.00 01-MAY-00:10 0.00
June 0.00 0.00 0.00 01-JUN-00:10 0.00
July 0.00 0.00 0.00 01-JUL-00:10 0.00
August 0.00 0.00 0.00 01-AUG-00:10 0.00
September 0.00 0.00 0.00 01-SEP-00:10 0.00
October 0.00 0.00 0.00 01-OCT-00:10 0.00
November 0.00 0.00 0.00 01-NOV-00:10 0.00
December 0.00 0.00 0.00 01-DEC-00:03 0.00
           
Annual Sum or Average 0.00 0.00      
Minimum of Months 0.00 0.00 0.00   0.00
Maximum of Months 0.00 0.00 0.00   0.00



Table of Contents

Report: FanReportMonthly

For: DINING_FLR_6 EXHAUST FAN

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.00 0.00 0.00 01-JAN-00:05 0.00
February 0.00 0.00 0.00 01-FEB-00:03 0.00
March 0.00 0.00 0.00 01-MAR-00:03 0.00
April 0.00 0.00 0.00 01-APR-00:10 0.00
May 0.00 0.00 0.00 01-MAY-00:10 0.00
June 0.00 0.00 0.00 01-JUN-00:10 0.00
July 0.00 0.00 0.00 01-JUL-00:10 0.00
August 0.00 0.00 0.00 01-AUG-00:10 0.00
September 0.00 0.00 0.00 01-SEP-00:10 0.00
October 0.00 0.00 0.00 01-OCT-00:10 0.00
November 0.00 0.00 0.00 01-NOV-00:10 0.00
December 0.00 0.00 0.00 01-DEC-00:03 0.00
           
Annual Sum or Average 0.00 0.00      
Minimum of Months 0.00 0.00 0.00   0.00
Maximum of Months 0.00 0.00 0.00   0.00



Table of Contents

Report: FanReportMonthly

For: KITCHEN_FLR_6 EXHAUST FAN

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.279806E+10 0.46 1474.84 01-JAN-07:10 0.64
February 0.252728E+10 0.46 1474.84 01-FEB-07:05 0.64
March 0.279806E+10 0.46 1474.84 01-MAR-07:05 0.65
April 0.270780E+10 0.46 1474.84 01-APR-06:10 0.65
May 0.279806E+10 0.46 1474.84 01-MAY-06:05 0.65
June 0.270780E+10 0.45 1474.84 01-JUN-06:05 0.64
July 0.279806E+10 0.45 1474.84 01-JUL-06:10 0.64
August 0.279806E+10 0.45 1474.84 01-AUG-06:05 0.64
September 0.270780E+10 0.45 1474.84 01-SEP-06:05 0.64
October 0.279806E+10 0.46 1474.84 01-OCT-06:10 0.64
November 0.270780E+10 0.46 1474.84 01-NOV-06:05 0.64
December 0.279806E+10 0.46 1474.84 01-DEC-07:05 0.65
           
Annual Sum or Average 0.329449E+11 0.46      
Minimum of Months 0.252728E+10 0.45 1474.84   0.64
Maximum of Months 0.279806E+10 0.46 1474.84   0.65



Table of Contents

Report: FanReportMonthly

For: ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.686875E+09 1.02 2107.83 01-JAN-09:02 1.40
February 0.551645E+09 1.01 2107.83 01-FEB-09:02 1.39
March 0.534991E+09 0.99 2107.83 01-MAR-09:02 1.40
April 0.574812E+09 1.14 2107.83 01-APR-15:01 1.40
May 0.591030E+09 1.12 2107.83 01-MAY-15:02 1.40
June 0.678324E+09 1.17 2107.83 01-JUN-15:01 1.39
July 0.821854E+09 1.21 2107.83 01-JUL-15:01 1.39
August 0.755775E+09 1.23 2107.83 01-AUG-15:02 1.39
September 0.615815E+09 1.19 2107.83 01-SEP-15:02 1.39
October 0.453592E+09 1.05 2107.83 01-OCT-15:02 1.40
November 0.571880E+09 1.01 2107.83 01-NOV-08:62 1.40
December 0.874192E+09 1.09 2107.83 01-DEC-09:02 1.40
           
Annual Sum or Average 0.771078E+10 1.10      
Minimum of Months 0.453592E+09 0.99 2107.83   1.39
Maximum of Months 0.874192E+09 1.23 2107.83   1.40



Table of Contents

Report: FanReportMonthly

For: ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.760745E+09 1.06 1884.60 01-JAN-09:02 1.40
February 0.597503E+09 1.00 1884.60 01-FEB-09:02 1.39
March 0.542267E+09 1.00 1884.60 01-MAR-09:02 1.40
April 0.455395E+09 1.05 1884.60 01-APR-15:01 1.40
May 0.498527E+09 1.06 1884.60 01-MAY-15:02 1.40
June 0.602547E+09 1.11 1884.60 01-JUN-15:01 1.39
July 0.716699E+09 1.13 1884.60 01-JUL-15:01 1.39
August 0.573652E+09 1.11 1884.60 01-AUG-15:02 1.39
September 0.403828E+09 1.05 1884.60 01-SEP-15:02 1.39
October 0.423510E+09 1.00 1884.60 01-OCT-15:02 1.40
November 0.620410E+09 1.01 1884.60 01-NOV-08:62 1.40
December 0.903388E+09 1.14 1884.60 01-DEC-09:02 1.40
           
Annual Sum or Average 0.709847E+10 1.06      
Minimum of Months 0.403828E+09 1.00 1884.60   1.39
Maximum of Months 0.903388E+09 1.14 1884.60   1.40



Table of Contents

Report: FanReportMonthly

For: ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.637088E+09 0.22 3928.14 21-JAN-11:25 1.40
February 0.682036E+09 0.27 3591.16 04-FEB-14:00 1.40
March 56397748.29 0.05 1726.95 25-MAR-11:30 1.40
April 0.332395E+10 0.86 5035.51 30-APR-12:30 1.40
May 0.274609E+10 0.80 3760.98 23-MAY-13:10 1.39
June 0.315642E+10 0.99 3747.41 13-JUN-13:20 1.39
July 0.378074E+10 1.09 4324.70 22-JUL-13:30 1.40
August 0.433260E+10 1.13 4601.33 20-AUG-13:00 1.40
September 0.505645E+10 1.11 8541.75 25-SEP-13:30 1.40
October 0.221315E+10 0.54 8084.70 03-OCT-12:50 1.40
November 0.504873E+09 0.18 3792.54 11-NOV-13:30 1.40
December 0.286190E+09 0.14 2262.57 17-DEC-04:40 1.40
           
Annual Sum or Average 0.267760E+11 0.62      
Minimum of Months 56397748.29 0.05 1726.95   1.39
Maximum of Months 0.505645E+10 1.13 8541.75   1.40



Table of Contents

Report: FanReportMonthly

For: ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.198331E+10 0.99 9741.33 01-JAN-09:02 1.40
February 0.155444E+10 0.99 9741.33 01-FEB-16:02 1.40
March 0.183285E+10 0.99 9741.33 03-MAR-16:02 1.40
April 0.305906E+10 0.99 9741.33 01-APR-08:62 1.40
May 0.380199E+10 0.99 9741.33 01-MAY-08:62 1.40
June 0.512419E+10 0.99 9741.33 01-JUN-08:62 1.40
July 0.550248E+10 0.99 9741.33 01-JUL-08:62 1.39
August 0.464409E+10 0.99 9741.33 01-AUG-08:62 1.39
September 0.351380E+10 0.99 9741.33 01-SEP-15:02 1.39
October 0.207581E+10 0.99 9741.33 01-OCT-08:62 1.40
November 0.159507E+10 0.99 9741.33 06-NOV-16:02 1.40
December 0.204453E+10 0.99 9741.33 01-DEC-16:02 1.40
           
Annual Sum or Average 0.367316E+11 0.99      
Minimum of Months 0.155444E+10 0.99 9741.33   1.39
Maximum of Months 0.550248E+10 0.99 9741.33   1.40



Table of Contents

Report: FanReportMonthly

For: ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.651541E+09 1.02 1914.04 01-JAN-16:01 1.40
February 0.527540E+09 0.99 1914.04 01-FEB-09:02 1.39
March 0.502582E+09 0.99 1914.04 01-MAR-09:02 1.40
April 0.589341E+09 1.20 1914.04 01-APR-15:01 1.40
May 0.574706E+09 1.19 1914.04 01-MAY-15:02 1.40
June 0.620521E+09 1.21 1914.04 01-JUN-08:62 1.40
July 0.739810E+09 1.26 1914.04 01-JUL-08:62 1.39
August 0.767579E+09 1.27 1914.04 01-AUG-08:62 1.39
September 0.655749E+09 1.26 1914.04 01-SEP-15:02 1.39
October 0.438673E+09 1.06 1914.04 01-OCT-08:62 1.39
November 0.542925E+09 1.00 1914.04 01-NOV-08:62 1.40
December 0.798065E+09 1.08 1914.04 01-DEC-09:02 1.40
           
Annual Sum or Average 0.740903E+10 1.13      
Minimum of Months 0.438673E+09 0.99 1914.04   1.39
Maximum of Months 0.798065E+09 1.27 1914.04   1.40



Table of Contents

Report: FanReportMonthly

For: ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.717888E+09 1.07 1725.45 01-JAN-09:02 1.40
February 0.582476E+09 1.00 1725.45 01-FEB-09:02 1.39
March 0.510996E+09 0.99 1725.45 01-MAR-09:02 1.40
April 0.454505E+09 1.08 1725.45 03-APR-08:62 1.40
May 0.475709E+09 1.10 1725.45 01-MAY-15:02 1.40
June 0.545709E+09 1.16 1725.45 01-JUN-08:62 1.40
July 0.633057E+09 1.23 1725.45 01-JUL-08:62 1.39
August 0.586702E+09 1.23 1725.45 01-AUG-08:62 1.39
September 0.429556E+09 1.13 1725.45 01-SEP-15:02 1.39
October 0.394940E+09 0.99 1725.45 01-OCT-08:62 1.39
November 0.582053E+09 1.01 1725.45 01-NOV-08:62 1.40
December 0.823606E+09 1.13 1725.45 01-DEC-09:02 1.40
           
Annual Sum or Average 0.673720E+10 1.09      
Minimum of Months 0.394940E+09 0.99 1725.45   1.39
Maximum of Months 0.823606E+09 1.23 1725.45   1.40



Table of Contents

Report: FanReportMonthly

For: ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.225261E+09 1.08 564.59 01-JAN-09:02 1.40
February 0.179355E+09 1.04 564.59 01-FEB-09:02 1.39
March 0.174125E+09 1.01 564.59 01-MAR-09:02 1.40
April 0.176399E+09 1.16 564.59 01-APR-08:62 1.40
May 0.176460E+09 1.15 564.59 01-MAY-15:02 1.40
June 0.197068E+09 1.21 564.59 01-JUN-15:01 1.39
July 0.240630E+09 1.24 564.59 01-JUL-15:01 1.39
August 0.214961E+09 1.25 564.59 01-AUG-15:02 1.39
September 0.173549E+09 1.21 564.59 01-SEP-15:02 1.39
October 0.146486E+09 1.06 564.59 01-OCT-15:02 1.40
November 0.188209E+09 1.03 564.59 01-NOV-08:62 1.40
December 0.277884E+09 1.17 564.59 01-DEC-09:02 1.40
           
Annual Sum or Average 0.237039E+10 1.14      
Minimum of Months 0.146486E+09 1.01 564.59   1.39
Maximum of Months 0.277884E+09 1.25 564.59   1.40



Table of Contents

Report: FanReportMonthly

For: ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.248479E+09 1.16 501.34 01-JAN-09:02 1.40
February 0.189787E+09 1.07 501.34 01-FEB-09:02 1.39
March 0.174011E+09 1.01 501.34 01-MAR-09:02 1.40
April 0.143661E+09 1.07 501.34 01-APR-08:62 1.40
May 0.150769E+09 1.09 501.34 01-MAY-15:02 1.40
June 0.176966E+09 1.16 501.34 01-JUN-15:01 1.39
July 0.210731E+09 1.19 501.34 01-JUL-15:01 1.39
August 0.165064E+09 1.17 501.34 01-AUG-15:02 1.39
September 0.118133E+09 1.07 501.34 01-SEP-15:02 1.39
October 0.137865E+09 1.00 501.34 01-OCT-15:02 1.40
November 0.199396E+09 1.09 501.34 01-NOV-08:62 1.40
December 0.283910E+09 1.29 501.34 01-DEC-09:02 1.40
           
Annual Sum or Average 0.219877E+10 1.11      
Minimum of Months 0.118133E+09 1.00 501.34   1.39
Maximum of Months 0.283910E+09 1.29 501.34   1.40



Table of Contents

Report: FanReportMonthly

For: ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.865065E+09 1.10 3128.09 01-JAN-16:01 1.40
February 0.741443E+09 1.09 3128.09 01-FEB-09:02 1.39
March 0.648256E+09 1.01 3128.09 01-MAR-09:02 1.40
April 0.100433E+10 1.22 3128.09 01-APR-15:01 1.40
May 0.859611E+09 1.18 3128.09 01-MAY-15:02 1.40
June 0.921698E+09 1.21 3128.09 01-JUN-15:01 1.39
July 0.113433E+10 1.23 3128.09 01-JUL-08:62 1.39
August 0.127847E+10 1.25 3128.09 01-AUG-15:02 1.39
September 0.128818E+10 1.26 3128.09 01-SEP-15:02 1.39
October 0.787954E+09 1.13 3128.09 01-OCT-08:62 1.39
November 0.688681E+09 1.07 3128.09 01-NOV-15:02 1.40
December 0.101356E+10 1.08 3128.09 01-DEC-09:02 1.40
           
Annual Sum or Average 0.112316E+11 1.15      
Minimum of Months 0.648256E+09 1.01 3128.09   1.39
Maximum of Months 0.128818E+10 1.26 3128.09   1.40



Table of Contents

Report: PumpReportMonthly

For: HEATSYS1 PUMP

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.118418E+10 0.106576E+10 837.44 10-JAN-09:02 753.69 753.69 32.78 1.59
February 0.949456E+09 0.854511E+09 757.57 26-FEB-16:02 681.81 681.81 38.01 1.26
March 0.101404E+10 0.912640E+09 739.29 04-MAR-16:02 665.36 665.36 36.97 1.20
April 0.631779E+09 0.568601E+09 640.97 10-APR-10:40 576.87 576.87 38.59 0.94
May 0.612770E+09 0.551493E+09 631.46 18-MAY-10:40 568.32 568.32 36.90 0.91
June 0.494033E+09 0.444629E+09 626.19 07-JUN-10:40 563.57 563.57 36.90 0.90
July 0.461327E+09 0.415194E+09 586.74 03-JUL-10:40 528.07 528.07 36.39 0.82
August 0.427984E+09 0.385186E+09 592.95 08-AUG-10:40 533.65 533.65 35.86 0.83
September 0.435561E+09 0.392005E+09 614.31 08-SEP-10:40 552.88 552.88 36.40 0.88
October 0.737352E+09 0.663617E+09 672.13 19-OCT-08:03 604.91 604.91 35.68 1.01
November 0.961729E+09 0.865556E+09 762.45 26-NOV-16:02 686.21 686.21 38.01 1.28
December 0.126690E+10 0.114021E+10 803.09 27-DEC-09:03 722.78 722.78 35.43 1.43
                 
Annual Sum or Average 0.917712E+10 0.825941E+10            
Minimum of Months 0.427984E+09 0.385186E+09 586.74   528.07 528.07 32.78 0.82
Maximum of Months 0.126690E+10 0.114021E+10 837.44   753.69 753.69 38.59 1.59



Table of Contents

Report: PumpReportMonthly

For: COOLSYS1 PUMP SECONDARY

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.692987E+09 0.623688E+09 2241.16 21-JAN-16:03 2017.04 2017.04 6.73 4.30
February 0.740198E+09 0.666178E+09 2426.81 20-FEB-09:02 2184.13 2184.13 6.73 4.80
March 0.805722E+09 0.725149E+09 2479.27 31-MAR-15:01 2231.34 2231.34 6.73 4.95
April 0.365244E+10 0.328719E+10 4649.55 30-APR-19:20 4184.60 4184.60 6.73 21.42
May 0.385123E+10 0.346611E+10 4382.53 21-MAY-18:03 3944.28 3944.28 6.73 18.62
June 0.522536E+10 0.470282E+10 5063.48 25-JUN-18:03 4557.13 4557.13 6.73 23.99
July 0.650999E+10 0.585899E+10 5194.57 22-JUL-18:02 4675.12 4675.12 6.73 24.60
August 0.699429E+10 0.629486E+10 4901.80 14-AUG-17:00 4411.62 4411.62 6.73 23.13
September 0.553174E+10 0.497857E+10 4839.94 27-SEP-15:13 4355.95 4355.95 6.73 22.76
October 0.226243E+10 0.203618E+10 3991.54 07-OCT-15:02 3592.39 3592.39 6.73 12.67
November 0.777213E+09 0.699492E+09 2724.27 05-NOV-15:02 2451.84 2451.84 6.73 5.68
December 0.230368E+09 0.207332E+09 1485.51 02-DEC-09:02 1336.96 1336.96 6.73 2.57
                 
Annual Sum or Average 0.372740E+11 0.335466E+11            
Minimum of Months 0.230368E+09 0.207332E+09 1485.51   1336.96 1336.96 6.73 2.57
Maximum of Months 0.699429E+10 0.629486E+10 5194.57   4675.12 4675.12 6.73 24.60



Table of Contents

Report: PumpReportMonthly

For: COOLSYS1 PUMP

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.400961E+10 0.360865E+10 3681.07 01-JAN-09:00 3312.97 3312.97 6.76 25.80
February 0.398167E+10 0.358350E+10 3681.07 01-FEB-00:03 3312.97 3312.97 6.74 25.80
March 0.499106E+10 0.449195E+10 3681.07 01-MAR-06:10 3312.97 3312.97 6.75 25.80
April 0.889476E+10 0.800528E+10 3681.07 01-APR-00:10 3312.97 3312.97 6.75 25.80
May 0.926828E+10 0.834145E+10 3681.07 01-MAY-00:10 3312.97 3312.97 7.05 25.80
June 0.948244E+10 0.853420E+10 3681.07 01-JUN-00:10 3312.97 3312.97 6.90 25.80
July 0.985810E+10 0.887229E+10 3681.07 01-JUL-00:10 3312.97 3312.97 6.88 25.80
August 0.985939E+10 0.887345E+10 3681.07 01-AUG-00:10 3312.97 3312.97 6.95 25.80
September 0.948281E+10 0.853453E+10 3681.07 01-SEP-00:10 3312.97 3312.97 6.96 25.80
October 0.776854E+10 0.699168E+10 3681.07 01-OCT-00:10 3312.97 3312.97 6.84 25.80
November 0.482596E+10 0.434336E+10 3681.07 01-NOV-00:10 3312.97 3312.97 6.75 25.80
December 0.242086E+10 0.217877E+10 3681.07 01-DEC-06:50 3312.97 3312.97 6.74 25.80
                 
Annual Sum or Average 0.848435E+11 0.763591E+11            
Minimum of Months 0.242086E+10 0.217877E+10 3681.07   3312.97 3312.97 6.74 25.80
Maximum of Months 0.985939E+10 0.887345E+10 3681.07   3312.97 3312.97 7.05 25.80



Table of Contents

Report: PumpReportMonthly

For: SWHSYS1 PUMP

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.128314E+09 38494137.67 47.91 01-JAN-00:05 14.37 14.37 48.13 0.37
February 0.115896E+09 34768898.54 47.91 01-FEB-00:03 14.37 14.37 48.79 0.37
March 0.128314E+09 38494137.67 47.91 01-MAR-00:03 14.37 14.37 48.79 0.37
April 0.124175E+09 37252391.29 47.91 01-APR-00:10 14.37 14.37 51.15 0.37
May 0.128314E+09 38494137.67 47.91 01-MAY-00:10 14.37 14.37 51.58 0.37
June 0.124175E+09 37252391.29 47.91 01-JUN-00:10 14.37 14.37 52.25 0.37
July 0.128314E+09 38494137.67 47.91 01-JUL-00:10 14.37 14.37 52.44 0.37
August 0.128314E+09 38494137.67 47.91 01-AUG-00:10 14.37 14.37 52.32 0.37
September 0.124175E+09 37252391.29 47.91 01-SEP-00:10 14.37 14.37 52.38 0.37
October 0.128314E+09 38494137.67 47.91 01-OCT-00:10 14.37 14.37 51.50 0.37
November 0.124175E+09 37252391.29 47.91 01-NOV-00:10 14.37 14.37 52.26 0.37
December 0.128314E+09 38494137.67 47.91 01-DEC-00:03 14.37 14.37 48.85 0.37
                 
Annual Sum or Average 0.151079E+10 0.453237E+09            
Minimum of Months 0.115896E+09 34768898.54 47.91   14.37 14.37 48.13 0.37
Maximum of Months 0.128314E+09 38494137.67 47.91   14.37 14.37 52.44 0.37



Table of Contents

Report: CondLoopDemandReportMonthly

For: HEATSYS1

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:05 39.65 60.00 52811.01 181124.91 10-JAN-09:02
February 0.00 0.00 01-FEB-00:03 38.06 60.00 46879.00 124686.34 13-FEB-09:02
March 0.00 0.00 01-MAR-00:03 39.40 60.00 44692.09 115676.90 04-MAR-16:02
April 0.00 0.00 01-APR-00:10 37.82 60.00 29565.75 86853.70 11-APR-10:35
May 0.00 0.00 01-MAY-00:10 28.39 60.00 29144.84 90019.11 05-MAY-10:35
June 0.00 0.00 01-JUN-00:10 28.94 60.00 24850.32 88889.83 06-JUN-10:35
July 0.00 0.00 01-JUL-00:10 30.55 60.00 22537.95 88642.58 03-JUL-10:35
August 0.00 0.00 01-AUG-00:10 28.88 60.00 20968.71 84660.74 01-AUG-10:35
September 0.00 0.00 01-SEP-00:10 28.93 60.00 21841.26 86469.58 08-SEP-10:40
October 0.00 0.00 01-OCT-00:10 31.32 60.00 33712.49 102972.85 19-OCT-08:03
November 0.00 0.00 01-NOV-00:10 36.91 60.00 44221.10 119859.29 29-NOV-09:02
December 0.00 0.00 01-DEC-00:03 39.58 60.00 56475.49 147074.25 27-DEC-09:03
                 
Annual Sum or Average 0.00         35609.82    
Minimum of Months 0.00 0.00   28.39 60.00 20968.71 84660.74  
Maximum of Months 0.00 0.00   39.65 60.00 56475.49 181124.91  



Table of Contents

Report: CondLoopDemandReportMonthly

For: COOLSYS1

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 5507.15 66236.67 21-JAN-16:03 7.31 6.70 0.00 0.00 01-JAN-00:05
February 6450.60 72503.24 09-FEB-16:03 7.37 6.70 0.00 0.00 01-FEB-00:03
March 6316.32 66091.29 20-MAR-18:02 7.31 6.70 0.00 0.00 01-MAR-00:03
April 44412.29 480953.75 30-APR-18:03 11.15 6.70 0.00 0.00 01-APR-00:10
May 45421.38 475015.75 22-MAY-15:03 11.09 6.70 0.00 0.00 01-MAY-00:10
June 87673.43 696306.66 25-JUN-18:20 13.15 6.70 0.00 0.00 01-JUN-00:10
July 122532.78 586470.04 23-JUL-18:03 12.13 6.70 0.00 0.00 01-JUL-00:10
August 135904.85 526326.30 14-AUG-18:03 11.57 6.70 0.00 0.00 01-AUG-00:10
September 93568.15 504083.82 11-SEP-18:03 11.36 6.70 0.00 0.00 01-SEP-00:10
October 22256.18 357903.45 07-OCT-15:02 10.01 6.70 0.00 0.00 01-OCT-00:10
November 6544.53 78007.89 03-NOV-15:03 7.42 6.70 0.00 0.00 01-NOV-00:10
December 1904.07 27364.55 25-DEC-09:02 6.95 6.70 0.00 0.00 01-DEC-00:03
                 
Annual Sum or Average 48443.00         0.00    
Minimum of Months 1904.07 27364.55   6.95 6.70 0.00 0.00  
Maximum of Months 135904.85 696306.66   13.15 6.70 0.00 0.00  



Table of Contents

Report: CondLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:05 48.13 59.70 28107.74 57262.29 30-JAN-07:10
February 0.00 0.00 01-FEB-00:03 48.79 59.67 28290.00 57352.02 10-FEB-07:10
March 0.00 0.00 01-MAR-00:03 48.79 59.19 28129.52 57271.83 01-MAR-07:10
April 0.00 0.00 01-APR-00:10 51.15 58.43 27610.44 56427.23 03-APR-06:10
May 0.00 0.00 01-MAY-00:10 51.58 58.71 26917.24 55165.04 02-MAY-06:20
June 0.00 0.00 01-JUN-00:10 52.25 59.60 26226.60 53659.01 01-JUN-06:20
July 0.00 0.00 01-JUL-00:10 52.44 59.63 25687.17 52256.62 03-JUL-07:00
August 0.00 0.00 01-AUG-00:10 52.32 59.16 25519.24 51551.10 31-AUG-06:30
September 0.00 0.00 01-SEP-00:10 52.38 59.28 25693.35 52266.40 29-SEP-06:10
October 0.00 0.00 01-OCT-00:10 51.50 59.42 26195.49 53631.83 31-OCT-06:10
November 0.00 0.00 01-NOV-00:10 52.26 59.62 26894.27 55137.63 30-NOV-08:00
December 0.00 0.00 01-DEC-00:03 48.85 59.57 27591.49 56408.98 29-DEC-07:40
                 
Annual Sum or Average 0.00         26897.11    
Minimum of Months 0.00 0.00   48.13 58.43 25519.24 51551.10  
Maximum of Months 0.00 0.00   52.44 59.70 28290.00 57352.02  



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: VAV WITH REHEAT

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.119424E+12 0.00 6818783.35 0.135338E+12 0.00 0.00
February 0.977830E+11 0.00 0.00 0.122241E+12 0.00 0.00
March 0.107974E+12 0.00 4067563.16 0.135338E+12 0.00 0.00
April 0.744082E+11 0.00 0.309439E+11 0.130972E+12 0.00 0.00
May 0.766847E+11 0.00 0.333113E+11 0.135337E+12 0.00 0.00
June 0.646058E+11 0.00 0.103271E+12 0.130970E+12 0.00 0.00
July 0.605870E+11 0.00 0.177173E+12 0.135337E+12 0.00 0.00
August 0.565020E+11 0.00 0.210060E+12 0.135338E+12 0.00 0.00
September 0.563141E+11 0.00 0.113591E+12 0.130971E+12 0.00 0.00
October 0.846351E+11 0.00 0.809054E+10 0.135337E+12 0.00 0.00
November 0.100122E+12 0.00 0.223888E+09 0.130973E+12 0.00 0.00
December 0.122500E+12 0.00 0.00 0.135338E+12 0.00 0.00
             
Annual Sum or Average 0.102154E+13 0.00 0.676676E+12 0.159349E+13 0.00 0.00
Minimum of Months 0.563141E+11 0.00 0.00 0.122241E+12 0.00 0.00
Maximum of Months 0.122500E+12 0.00 0.210060E+12 0.135338E+12 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: FLR_3_DOAS

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.445327E+09 0.00 0.00 0.587890E+10 0.00 0.00
February 0.120929E+09 0.00 0.00 0.530997E+10 0.00 0.00
March 3005469.02 0.00 0.00 0.587890E+10 0.00 0.00
April 17644.25 0.00 0.246108E+10 0.568926E+10 0.00 0.00
May 11118.50 0.00 0.246348E+10 0.587890E+10 0.00 0.00
June 26777.63 0.00 0.833263E+10 0.568926E+10 0.00 0.00
July 46328.27 0.00 0.147069E+11 0.587890E+10 0.00 0.00
August 58125.16 0.00 0.178711E+11 0.587890E+10 0.00 0.00
September 23299.16 0.00 0.919189E+10 0.568926E+10 0.00 0.00
October 2014.16 0.00 0.434540E+09 0.587890E+10 0.00 0.00
November 8384552.07 0.00 6967953.45 0.568926E+10 0.00 0.00
December 0.230384E+09 0.00 0.00 0.587890E+10 0.00 0.00
             
Annual Sum or Average 0.808216E+09 0.00 0.554687E+11 0.692193E+11 0.00 0.00
Minimum of Months 2014.16 0.00 0.00 0.530997E+10 0.00 0.00
Maximum of Months 0.445327E+09 0.00 0.178711E+11 0.587890E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: VAV WITH REHEAT

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.135338E+12 6818783.35 0.119424E+12 0.766710E+12 0.00 0.00 0.00 0.00
February 0.122241E+12 0.00 0.977830E+11 0.695434E+12 0.00 0.00 0.00 0.00
March 0.135338E+12 4067563.16 0.107974E+12 0.637306E+12 0.00 0.00 0.00 0.00
April 0.130972E+12 0.309439E+11 0.744082E+11 0.401432E+12 0.474939E+09 0.00 0.00 0.00
May 0.135337E+12 0.333113E+11 0.766847E+11 0.331592E+12 0.255735E+09 0.00 0.00 0.00
June 0.130970E+12 0.103271E+12 0.646058E+11 0.127765E+12 0.485386E+10 0.00 0.00 0.00
July 0.135337E+12 0.177173E+12 0.605870E+11 0.707958E+11 0.717496E+10 0.00 0.00 0.00
August 0.135338E+12 0.210060E+12 0.565020E+11 0.466020E+11 0.160124E+10 0.00 0.00 0.00
September 0.130971E+12 0.113591E+12 0.563141E+11 0.133973E+12 0.311521E+09 0.00 0.00 0.00
October 0.135337E+12 0.809054E+10 0.846351E+11 0.367665E+12 0.00 0.00 0.00 0.00
November 0.130973E+12 0.223888E+09 0.100122E+12 0.557551E+12 0.00 0.00 0.00 0.00
December 0.135338E+12 0.00 0.122500E+12 0.782085E+12 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.159349E+13 0.676676E+12 0.102154E+13 0.491891E+13 0.146723E+11 0.00 0.00 0.00
Minimum of Months 0.122241E+12 0.00 0.563141E+11 0.466020E+11 0.00 0.00 0.00 0.00
Maximum of Months 0.135338E+12 0.210060E+12 0.122500E+12 0.782085E+12 0.717496E+10 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: FLR_3_DOAS

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.587890E+10 0.00 0.445327E+09 0.793321E+11 0.00 0.00 0.00 0.00
February 0.530997E+10 0.00 0.120929E+09 0.716573E+11 0.00 0.00 0.00 0.00
March 0.587890E+10 0.00 3005469.02 0.673759E+11 0.00 0.00 0.00 0.00
April 0.568926E+10 0.246108E+10 17644.25 0.449408E+11 0.00 0.00 0.00 0.00
May 0.587890E+10 0.246348E+10 11118.50 0.380947E+11 13945159.25 0.00 0.00 0.00
June 0.568926E+10 0.833263E+10 26777.63 0.165152E+11 0.342164E+09 0.00 0.00 0.00
July 0.587890E+10 0.147069E+11 46328.27 0.964576E+10 0.571837E+09 0.00 0.00 0.00
August 0.587890E+10 0.178711E+11 58125.16 0.675595E+10 78418695.79 0.00 0.00 0.00
September 0.568926E+10 0.919189E+10 23299.16 0.168176E+11 55694609.05 0.00 0.00 0.00
October 0.587890E+10 0.434540E+09 2014.16 0.415926E+11 0.00 0.00 0.00 0.00
November 0.568926E+10 6967953.45 8384552.07 0.593737E+11 0.00 0.00 0.00 0.00
December 0.587890E+10 0.00 0.230384E+09 0.810898E+11 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.692193E+11 0.554687E+11 0.808216E+09 0.533192E+12 0.106206E+10 0.00 0.00 0.00
Minimum of Months 0.530997E+10 0.00 2014.16 0.675595E+10 0.00 0.00 0.00 0.00
Maximum of Months 0.587890E+10 0.178711E+11 0.445327E+09 0.810898E+11 0.571837E+09 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: VAV WITH REHEAT

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.135338E+12 0.119424E+12 6818783.35 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.122241E+12 0.977830E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.135338E+12 0.107974E+12 4067563.16 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.130972E+12 0.744082E+11 0.309439E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.135337E+12 0.766847E+11 0.333113E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.130970E+12 0.646058E+11 0.103271E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.135337E+12 0.605870E+11 0.177173E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.135338E+12 0.565020E+11 0.210060E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.130971E+12 0.563141E+11 0.113591E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.135337E+12 0.846351E+11 0.809054E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.130973E+12 0.100122E+12 0.223888E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.135338E+12 0.122500E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.159349E+13 0.102154E+13 0.676676E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.122241E+12 0.563141E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.135338E+12 0.122500E+12 0.210060E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: FLR_3_DOAS

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.587890E+10 0.445327E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.530997E+10 0.120929E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.587890E+10 3005469.02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.568926E+10 17644.25 0.246108E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.587890E+10 11118.50 0.246348E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.568926E+10 26777.63 0.833263E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.587890E+10 46328.27 0.147069E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.587890E+10 58125.16 0.178711E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.568926E+10 23299.16 0.919189E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.587890E+10 2014.16 0.434540E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.568926E+10 8384552.07 6967953.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.587890E+10 0.230384E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.692193E+11 0.808216E+09 0.554687E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.530997E+10 2014.16 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.587890E+10 0.445327E+09 0.178711E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.700418E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.85
February 0.628221E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.86
March 0.699146E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.85
April 0.658817E+11 0.00 0.00 0.00 9090229.39 53276.64 0.00 0.00 1.86
May 0.681840E+11 0.00 0.00 0.00 9623476.77 0.00 0.00 0.00 1.85
June 0.597148E+11 0.00 357642.44 0.00 0.364356E+09 0.00 0.00 6049.63 1.86
July 0.543777E+11 0.00 0.00 0.00 0.352539E+09 0.00 0.00 0.00 1.86
August 0.505511E+11 0.00 0.00 0.00 99911815.45 0.00 0.00 0.00 1.86
September 0.577099E+11 0.00 0.00 0.00 21118657.50 0.00 0.00 0.00 1.86
October 0.695927E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.86
November 0.673714E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.85
December 0.692839E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.86
                   
Annual Sum or Average 0.765446E+12 0.00 357642.44 0.00 0.856639E+09 53276.64 0.00 6049.63 1.86
Minimum of Months 0.505511E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.85
Maximum of Months 0.700418E+11 0.00 357642.44 0.00 0.364356E+09 53276.64 0.00 6049.63 1.86



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.891042E+10 0.00 0.00 0.00 0.00 0.450465E+10 0.00 0.00 6.43
February 0.910874E+10 0.00 0.00 4872.19 0.00 0.288802E+10 35529408.13 0.00 6.47
March 0.109041E+11 0.00 0.00 0.00 0.00 0.248665E+10 0.00 0.00 6.44
April 0.124280E+11 0.00 0.00 10070.72 1741048.43 0.139554E+09 50787651.05 0.00 6.45
May 0.130593E+11 0.00 0.00 0.00 1843181.11 0.00 0.00 0.00 6.44
June 0.114372E+11 0.00 0.00 0.00 69854591.59 0.00 0.00 0.00 6.47
July 0.104149E+11 0.00 0.00 0.00 67521744.97 0.00 0.00 0.00 6.46
August 0.967498E+10 403040.08 0.00 4337.45 18733034.65 0.00 7059503.83 0.00 6.47
September 0.108526E+11 990774.79 0.00 176960.26 3054074.23 0.00 0.200401E+09 0.00 6.47
October 0.130350E+11 0.00 0.00 27867.57 0.00 0.152338E+09 0.141699E+09 0.00 6.47
November 0.104591E+11 0.00 0.00 0.00 0.00 0.244453E+10 0.00 0.00 6.42
December 0.564145E+10 0.00 0.00 0.00 0.00 0.762847E+10 0.00 0.00 6.47
                   
Annual Sum or Average 0.125926E+12 1393814.87 0.00 224108.19 0.162748E+09 0.202442E+11 0.435476E+09 0.00 6.45
Minimum of Months 0.564145E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 6.42
Maximum of Months 0.130593E+11 990774.79 0.00 176960.26 69854591.59 0.762847E+10 0.200401E+09 0.00 6.47



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.670810E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2.78
February 0.601665E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2.79
March 0.669592E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2.78
April 0.630968E+10 0.00 0.00 0.00 870597.37 0.00 0.00 0.00 2.79
May 0.653018E+10 0.00 0.00 0.00 921668.00 0.00 0.00 0.00 2.78
June 0.571906E+10 0.00 0.00 0.00 34930231.07 0.00 0.00 0.00 2.79
July 0.520791E+10 0.00 0.00 0.00 33763709.73 0.00 0.00 0.00 2.79
August 0.484143E+10 0.00 0.00 0.00 9568841.46 0.00 0.00 0.00 2.79
September 0.552704E+10 0.00 0.00 0.00 2022594.47 0.00 0.00 0.00 2.80
October 0.666509E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2.79
November 0.645235E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2.77
December 0.663552E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2.80
                   
Annual Sum or Average 0.733089E+11 0.00 0.00 0.00 82077642.11 0.00 0.00 0.00 2.79
Minimum of Months 0.484143E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2.77
Maximum of Months 0.670810E+10 0.00 0.00 0.00 34930231.07 0.00 0.00 0.00 2.80



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.601085E+10 0.00 0.00 0.00 0.00 0.283769E+09 0.00 0.00 1.23
February 0.562391E+10 0.00 0.00 0.00 0.00 21879456.79 0.00 0.00 1.24
March 0.628319E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.23
April 0.592076E+10 0.00 0.00 0.00 816934.21 0.00 0.00 0.00 1.24
May 0.612766E+10 0.00 0.00 0.00 864856.87 0.00 0.00 0.00 1.23
June 0.536654E+10 0.00 0.00 0.00 32777149.98 0.00 0.00 0.00 1.24
July 0.488689E+10 0.00 0.00 0.00 31682532.40 0.00 0.00 0.00 1.24
August 0.454300E+10 0.00 0.00 0.00 8979023.10 0.00 0.00 0.00 1.24
September 0.518636E+10 0.00 0.00 0.00 1897922.81 0.00 0.00 0.00 1.24
October 0.625426E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.24
November 0.604735E+10 0.00 0.00 0.00 0.00 7285286.66 0.00 0.00 1.23
December 0.607117E+10 0.00 0.00 0.00 0.00 0.155332E+09 0.00 0.00 1.24
                   
Annual Sum or Average 0.683219E+11 0.00 0.00 0.00 77018419.37 0.468265E+09 0.00 0.00 1.24
Minimum of Months 0.454300E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.23
Maximum of Months 0.628319E+10 0.00 0.00 0.00 32777149.98 0.283769E+09 0.00 0.00 1.24



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.185328E+10 0.00 0.00 0.00 0.00 0.123744E+10 0.00 0.00 1.05
February 0.179810E+10 0.00 0.00 0.00 0.00 0.974038E+09 0.00 0.00 1.05
March 0.276307E+10 0.00 0.00 0.00 0.00 0.322028E+09 0.00 0.00 1.05
April 0.290715E+10 0.00 0.00 0.00 401122.01 0.00 0.00 0.00 1.05
May 0.300874E+10 0.00 0.00 0.00 424652.47 0.00 0.00 0.00 1.05
June 0.263502E+10 0.00 0.00 0.00 16093874.00 0.00 0.00 0.00 1.05
July 0.239951E+10 0.00 0.00 0.00 15556406.97 0.00 0.00 0.00 1.05
August 0.223066E+10 0.00 0.00 0.00 4408780.71 0.00 0.00 0.00 1.05
September 0.254655E+10 0.00 0.00 0.00 931897.09 0.00 0.00 0.00 1.06
October 0.307090E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.05
November 0.248166E+10 0.00 0.00 0.00 0.00 0.491215E+09 0.00 0.00 1.05
December 0.122164E+10 0.00 0.00 0.00 0.00 0.183563E+10 0.00 0.00 1.06
                   
Annual Sum or Average 0.289163E+11 0.00 0.00 0.00 37816733.24 0.486035E+10 0.00 0.00 1.05
Minimum of Months 0.122164E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.05
Maximum of Months 0.307090E+10 0.00 0.00 0.00 16093874.00 0.183563E+10 0.00 0.00 1.06



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.179042E+10 0.00 0.00 63374050.32 0.00 0.00 0.908899E+11 0.00 38.26
February 0.125076E+10 0.00 0.00 57482686.19 0.00 0.00 0.818759E+11 0.00 38.47
March 0.107275E+10 0.00 0.00 63756092.31 0.00 0.00 0.914428E+11 0.00 38.31
April 0.172908E+10 11506129.63 0.00 63111295.77 526532.62 0.00 0.854427E+11 0.00 38.38
May 0.166456E+10 12274803.99 0.00 65733630.28 463713.44 0.00 0.885518E+11 0.00 38.28
June 0.154547E+10 0.454504E+09 0.00 62434395.01 28272363.05 0.00 0.774582E+11 0.00 38.46
July 0.160272E+10 0.438090E+09 0.00 64564072.16 28563594.84 0.00 0.703267E+11 0.00 38.42
August 0.140899E+10 0.127028E+09 0.00 66872459.87 5224391.93 0.00 0.654558E+11 0.00 38.47
September 0.137564E+10 27189651.24 0.00 65015329.42 764942.84 0.00 0.749730E+11 0.00 38.49
October 0.111591E+10 0.00 0.00 64887678.93 0.00 0.00 0.909694E+11 0.00 38.47
November 0.131342E+10 0.00 0.00 62062287.56 0.00 0.00 0.878337E+11 0.00 38.20
December 0.201360E+10 0.00 0.00 63081604.07 0.00 0.00 0.896615E+11 0.00 38.51
                   
Annual Sum or Average 0.178833E+11 0.107059E+10 0.00 0.762376E+09 63815538.71 0.00 0.994881E+12 0.00 38.39
Minimum of Months 0.107275E+10 0.00 0.00 57482686.19 0.00 0.00 0.654558E+11 0.00 38.20
Maximum of Months 0.201360E+10 0.454504E+09 0.00 66872459.87 28563594.84 0.00 0.914428E+11 0.00 38.51



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.525029E+11 0.00 0.00 16011.40 0.00 0.219377E+09 0.156315E+09 0.00 9.01
February 0.469707E+11 0.00 0.00 82615.13 0.00 21224036.76 0.436116E+09 0.00 9.06
March 0.527782E+11 0.00 0.00 0.00 0.00 4439413.77 0.00 0.00 9.02
April 0.489022E+11 2936677.87 0.00 180364.72 3926071.03 0.00 0.835634E+09 0.00 9.04
May 0.514761E+11 0.00 0.00 0.00 7265328.71 0.00 0.00 0.00 9.01
June 0.450822E+11 0.00 0.00 0.00 0.275348E+09 0.00 0.00 0.00 9.06
July 0.410330E+11 20606986.12 0.00 152.72 0.245546E+09 0.00 19941096.53 0.00 9.05
August 0.379839E+11 16066842.19 0.00 97899.04 59362464.51 0.00 0.180006E+09 0.00 9.06
September 0.419785E+11 3938101.57 0.00 948988.86 12005615.26 0.00 0.158919E+10 0.00 9.06
October 0.515440E+11 0.00 0.00 220766.58 0.00 0.00 0.995369E+09 0.00 9.06
November 0.506530E+11 0.00 0.00 9202.91 0.00 58673829.08 0.150952E+09 0.00 8.99
December 0.516915E+11 0.00 0.00 0.00 0.00 0.614995E+09 0.00 0.00 9.07
                   
Annual Sum or Average 0.572596E+12 43548607.75 0.00 1556001.35 0.603453E+09 0.918709E+09 0.436352E+10 0.00 9.04
Minimum of Months 0.379839E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 8.99
Maximum of Months 0.527782E+11 20606986.12 0.00 948988.86 0.275348E+09 0.614995E+09 0.158919E+10 0.00 9.07



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.145902E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3.59
February 0.130863E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3.61
March 0.145637E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3.59
April 0.137236E+12 0.00 0.00 0.00 18935585.57 0.00 0.00 0.00 3.60
May 0.142032E+12 0.00 0.00 0.00 20046377.27 0.00 0.00 0.00 3.59
June 0.124390E+12 0.00 0.00 0.00 0.759736E+09 0.00 0.00 0.00 3.61
July 0.113273E+12 0.00 0.00 0.00 0.734364E+09 0.00 0.00 0.00 3.61
August 0.105302E+12 0.00 0.00 0.00 0.208123E+09 0.00 0.00 0.00 3.61
September 0.120214E+12 0.00 0.00 0.00 43991645.19 0.00 0.00 0.00 3.61
October 0.144966E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3.61
November 0.140339E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3.58
December 0.144323E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3.61
                   
Annual Sum or Average 0.159448E+13 0.00 0.00 0.00 0.178520E+10 0.00 0.00 0.00 3.60
Minimum of Months 0.105302E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3.58
Maximum of Months 0.145902E+12 0.00 0.00 0.00 0.759736E+09 0.00 0.00 0.00 3.61



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.420974E+09 0.00 0.00 400268.10 0.00 0.114437E+10 84133594.62 0.00 0.47
February 0.387120E+09 0.00 0.00 1144435.61 0.00 0.945472E+09 0.175599E+09 0.00 0.47
March 0.460462E+09 0.00 0.00 658331.81 0.00 0.101065E+10 0.180131E+09 0.00 0.47
April 0.296418E+09 0.00 0.00 9494474.63 102828.01 0.374554E+09 0.100749E+10 0.00 0.47
May 0.317217E+09 242828.13 0.00 10672420.69 0.00 0.277805E+09 0.111675E+10 0.00 0.47
June 0.209937E+09 13298488.67 0.00 13136120.22 229585.62 25118211.85 0.121393E+10 0.00 0.47
July 0.167889E+09 9055703.11 2189.95 15198931.84 614468.58 37074417.37 0.109040E+10 2201.37 0.47
August 0.106764E+09 6183879.28 0.00 14965937.29 413628.23 1784607.60 0.110641E+10 0.00 0.47
September 0.195213E+09 4300203.21 0.00 11445444.93 50701.70 94707703.22 0.114423E+10 0.00 0.47
October 0.395706E+09 0.00 0.00 3638592.73 0.00 0.716105E+09 0.617318E+09 0.00 0.47
November 0.425483E+09 0.00 0.00 448980.26 0.00 0.107068E+10 0.119146E+09 0.00 0.47
December 0.336819E+09 0.00 0.00 22166.33 0.00 0.115444E+10 8286891.75 0.00 0.47
                   
Annual Sum or Average 0.372000E+10 33081102.40 2189.95 81226104.44 1411212.13 0.685276E+10 0.786382E+10 2201.37 0.47
Minimum of Months 0.106764E+09 0.00 0.00 22166.33 0.00 1784607.60 8286891.75 0.00 0.47
Maximum of Months 0.460462E+09 13298488.67 2189.95 15198931.84 614468.58 0.115444E+10 0.121393E+10 2201.37 0.47



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.394377E+09 0.00 0.00 73501.08 0.00 0.124186E+10 13376032.43 0.00 0.47
February 0.420245E+09 0.00 0.00 367254.36 0.00 0.103538E+10 53163244.81 0.00 0.47
March 0.461701E+09 0.00 0.00 381280.55 0.00 0.107681E+10 0.112809E+09 0.00 0.47
April 0.416152E+09 0.00 0.00 6667451.46 102815.96 0.493560E+09 0.771376E+09 0.00 0.47
May 0.406651E+09 242799.68 0.00 8864222.21 0.00 0.329058E+09 0.977665E+09 0.00 0.47
June 0.282108E+09 13259484.74 0.00 12003472.28 267004.54 25811733.64 0.114203E+10 0.00 0.47
July 0.231096E+09 8845676.24 1514.28 13641900.32 823362.44 42282950.88 0.102339E+10 2876.53 0.47
August 0.174736E+09 4729655.24 0.00 11981296.40 1867079.28 2440497.43 0.104062E+10 0.00 0.47
September 0.303005E+09 4109350.54 0.00 7342590.58 241044.59 0.172698E+09 0.962380E+09 0.00 0.47
October 0.476114E+09 0.00 0.00 1708817.51 0.00 0.925422E+09 0.329320E+09 0.00 0.47
November 0.427656E+09 0.00 0.00 114705.35 0.00 0.116152E+10 26284762.65 0.00 0.47
December 0.300714E+09 0.00 0.00 5491.64 0.00 0.119736E+10 1311687.02 0.00 0.47
                   
Annual Sum or Average 0.429455E+10 31186966.44 1514.28 63151983.75 3301306.81 0.770420E+10 0.645373E+10 2876.53 0.47
Minimum of Months 0.174736E+09 0.00 0.00 5491.64 0.00 2440497.43 1311687.02 0.00 0.47
Maximum of Months 0.476114E+09 13259484.74 1514.28 13641900.32 1867079.28 0.124186E+10 0.114203E+10 2876.53 0.47



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.177363E+11 0.00 0.00 17303730.59 0.00 0.00 0.461725E+10 0.00 0.53
February 0.151128E+11 0.00 0.00 18866992.44 0.00 0.00 0.533360E+10 0.00 0.54
March 0.204923E+11 0.00 0.00 2832414.74 0.00 0.00 0.190311E+10 0.00 0.54
April 0.747969E+10 1394255.52 0.00 89805666.49 0.00 0.00 0.153176E+11 0.00 0.54
May 0.805206E+10 3292531.65 0.00 75217431.75 0.00 0.00 0.152275E+11 0.00 0.54
June 0.426935E+10 0.183429E+09 0.00 85512053.41 0.00 0.00 0.154702E+11 0.00 0.54
July 0.291922E+10 0.131178E+09 0.00 97865355.70 0.00 0.00 0.147530E+11 0.00 0.54
August 0.160477E+10 89456284.70 0.00 0.120074E+09 0.00 0.00 0.149518E+11 0.00 0.54
September 0.264711E+10 58994368.23 0.00 0.129853E+09 0.00 0.00 0.168240E+11 0.00 0.54
October 0.124251E+11 0.00 0.00 57645857.82 0.00 0.00 0.110121E+11 0.00 0.54
November 0.180046E+11 0.00 0.00 12933941.72 0.00 0.00 0.389072E+10 0.00 0.53
December 0.192551E+11 0.00 0.00 726945.30 0.00 0.777077E+09 0.299877E+09 0.00 0.54
                   
Annual Sum or Average 0.129998E+12 0.467744E+09 0.00 0.708638E+09 0.00 0.777077E+09 0.119601E+12 0.00 0.54
Minimum of Months 0.160477E+10 0.00 0.00 726945.30 0.00 0.00 0.299877E+09 0.00 0.53
Maximum of Months 0.204923E+11 0.183429E+09 0.00 0.129853E+09 0.00 0.777077E+09 0.168240E+11 0.00 0.54



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.610905E+10 0.00 0.00 21713866.71 0.00 0.373019E+10 0.125161E+11 0.00 0.53
February 0.570470E+10 0.00 0.00 20637159.96 0.00 0.204623E+10 0.126993E+11 0.00 0.54
March 0.626495E+10 0.00 0.00 40887872.94 0.00 0.142380E+09 0.159562E+11 0.00 0.53
April 0.655318E+10 0.00 0.00 82255216.98 1394636.78 57505517.97 0.162004E+11 0.00 0.54
May 0.674308E+10 705419.07 0.00 0.101094E+09 2588012.92 47707513.84 0.164693E+11 0.00 0.53
June 0.519064E+10 0.118279E+09 0.00 0.125204E+09 65199625.23 20158958.26 0.144945E+11 0.00 0.54
July 0.428597E+10 91004533.98 0.00 0.130196E+09 40209734.11 15410241.48 0.133434E+11 0.00 0.54
August 0.333212E+10 26785440.03 0.00 0.115757E+09 62695306.32 13786118.33 0.132196E+11 0.00 0.54
September 0.472163E+10 35696907.07 0.00 92513325.51 23313593.07 36187881.50 0.147560E+11 0.00 0.54
October 0.663968E+10 0.00 0.00 55520896.92 0.00 82467027.91 0.167235E+11 0.00 0.54
November 0.604847E+10 0.00 0.00 30469908.75 0.00 0.121337E+10 0.146219E+11 0.00 0.53
December 0.547271E+10 0.00 0.00 14552493.39 0.00 0.487943E+10 0.997164E+10 0.00 0.54
                   
Annual Sum or Average 0.670662E+11 0.272471E+09 0.00 0.830803E+09 0.195401E+09 0.122848E+11 0.170972E+12 0.00 0.54
Minimum of Months 0.333212E+10 0.00 0.00 14552493.39 0.00 13786118.33 0.997164E+10 0.00 0.53
Maximum of Months 0.674308E+10 0.118279E+09 0.00 0.130196E+09 65199625.23 0.487943E+10 0.167235E+11 0.00 0.54



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.428312E+09 0.00 0.00 374045.43 0.00 0.112950E+10 91691218.20 0.00 0.47
February 0.420614E+09 0.00 0.00 687917.72 0.00 0.960011E+09 0.128022E+09 0.00 0.47
March 0.459721E+09 0.00 0.00 508484.35 0.00 0.100208E+10 0.189592E+09 0.00 0.47
April 0.209479E+09 102828.01 0.00 10459665.32 0.00 0.357078E+09 0.111094E+10 0.00 0.47
May 0.226075E+09 242828.13 0.00 10712050.31 0.00 0.282704E+09 0.120295E+10 0.00 0.47
June 0.169831E+09 12959612.22 0.00 12539615.00 568462.07 46007197.97 0.123375E+10 0.00 0.47
July 0.109279E+09 9346068.78 0.00 14228743.13 328494.24 20692522.39 0.116636E+10 0.00 0.47
August 78647596.98 6451127.58 0.00 15892269.52 146379.93 1814584.97 0.113357E+10 0.00 0.47
September 0.130780E+09 4232500.66 50.18 13468965.32 118293.23 69384597.13 0.123196E+10 60.83 0.47
October 0.376498E+09 0.00 0.00 3749482.40 0.00 0.716297E+09 0.636224E+09 0.00 0.47
November 0.434965E+09 0.00 0.00 434419.02 0.00 0.106590E+10 0.114456E+09 0.00 0.47
December 0.341149E+09 0.00 0.00 110761.04 0.00 0.112374E+10 34568352.18 0.00 0.47
                   
Annual Sum or Average 0.338535E+10 33334965.37 50.18 83166418.57 1161629.47 0.677521E+10 0.827408E+10 60.83 0.47
Minimum of Months 78647596.98 0.00 0.00 110761.04 0.00 1814584.97 34568352.18 0.00 0.47
Maximum of Months 0.459721E+09 12959612.22 50.18 15892269.52 568462.07 0.112950E+10 0.123375E+10 60.83 0.47



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.385245E+09 0.00 0.00 84067.18 0.00 0.122931E+10 35041962.34 0.00 0.47
February 0.420564E+09 0.00 0.00 191252.21 0.00 0.103484E+10 53558947.17 0.00 0.47
March 0.461323E+09 0.00 0.00 243410.99 0.00 0.108406E+10 0.106079E+09 0.00 0.47
April 0.351475E+09 102815.96 0.00 7224660.36 0.00 0.453260E+09 0.875796E+09 0.00 0.47
May 0.342309E+09 242799.68 0.00 8669989.60 0.00 0.339966E+09 0.103129E+10 0.00 0.47
June 0.226668E+09 12864653.67 0.00 11303313.02 661835.61 54906829.65 0.116907E+10 0.00 0.47
July 0.127728E+09 9235257.07 0.00 12646039.01 438172.43 27977979.80 0.114206E+10 0.00 0.47
August 99199714.33 6417126.22 1115.42 12776928.26 178477.43 7301165.94 0.111050E+10 15.45 0.47
September 0.228278E+09 4144157.94 19748.01 8845205.50 185578.27 0.157128E+09 0.105117E+10 910.91 0.47
October 0.488682E+09 0.00 0.00 1540554.83 0.00 0.905828E+09 0.336515E+09 0.00 0.47
November 0.429567E+09 0.00 0.00 122300.41 0.00 0.114120E+10 44677570.49 0.00 0.47
December 0.305708E+09 0.00 0.00 22990.41 0.00 0.118952E+10 4143811.80 0.00 0.47
                   
Annual Sum or Average 0.386675E+10 33006810.54 20863.43 63670711.76 1464063.73 0.762530E+10 0.695992E+10 926.36 0.47
Minimum of Months 99199714.33 0.00 0.00 22990.41 0.00 7301165.94 4143811.80 0.00 0.47
Maximum of Months 0.488682E+09 12864653.67 19748.01 12776928.26 661835.61 0.122931E+10 0.116907E+10 910.91 0.47



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.333629E+11 0.00 0.00 0.00 0.00 0.197751E+10 0.00 0.00 0.95
February 0.311353E+11 0.00 0.00 0.00 0.00 0.562299E+09 0.00 0.00 0.95
March 0.349902E+11 0.00 0.00 0.00 0.00 0.286036E+09 0.00 0.00 0.95
April 0.332414E+11 0.00 0.00 0.00 4586582.39 0.00 0.00 0.00 0.95
May 0.344031E+11 0.00 0.00 0.00 4855638.64 0.00 0.00 0.00 0.95
June 0.301298E+11 0.00 0.00 0.00 0.184024E+09 0.00 0.00 0.00 0.95
July 0.274369E+11 0.00 0.00 0.00 0.177878E+09 0.00 0.00 0.00 0.95
August 0.255062E+11 0.00 0.00 0.00 50411684.18 0.00 0.00 0.00 0.95
September 0.291182E+11 0.00 0.00 0.00 10655667.58 0.00 0.00 0.00 0.95
October 0.351138E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.95
November 0.333605E+11 0.00 0.00 0.00 0.00 0.632555E+09 0.00 0.00 0.95
December 0.301858E+11 0.00 0.00 0.00 0.00 0.477220E+10 0.00 0.00 0.96
                   
Annual Sum or Average 0.377984E+12 0.00 0.00 0.00 0.432411E+09 0.823060E+10 0.00 0.00 0.95
Minimum of Months 0.255062E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.95
Maximum of Months 0.351138E+11 0.00 0.00 0.00 0.184024E+09 0.477220E+10 0.00 0.00 0.96



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 93803126.07 0.00 0.00 79640.05 0.00 0.310322E+09 8264889.62 0.00 0.47
February 93632999.62 0.00 0.00 269194.81 0.00 0.256644E+09 26787538.59 0.00 0.47
March 0.112339E+09 0.00 0.00 139693.56 0.00 0.277272E+09 23223581.78 0.00 0.47
April 69171838.18 0.00 0.00 2615184.55 25707.00 0.128662E+09 0.221540E+09 0.00 0.47
May 72874344.05 60707.03 0.00 2898264.55 0.00 0.102166E+09 0.252671E+09 0.00 0.47
June 44443152.91 3334144.17 0.00 3606771.69 47874.40 18865563.02 0.298615E+09 0.00 0.47
July 35319420.80 2303183.77 664.05 4221859.29 114359.15 21474878.42 0.266625E+09 433.78 0.47
August 23967654.65 1560081.33 0.00 4111318.98 89295.55 3664036.68 0.275738E+09 0.00 0.47
September 42437630.71 1080740.07 0.00 2996195.75 6986.16 50647165.37 0.265318E+09 0.00 0.47
October 98569110.99 0.00 0.00 882880.15 0.00 0.224609E+09 0.109131E+09 0.00 0.47
November 0.102396E+09 0.00 0.00 92902.84 0.00 0.289768E+09 11682942.81 0.00 0.47
December 62856289.90 0.00 0.00 1145.49 0.00 0.311954E+09 80598.90 0.00 0.47
                   
Annual Sum or Average 0.851811E+09 8338856.37 664.05 21915051.70 284222.26 0.199605E+10 0.175968E+10 433.78 0.47
Minimum of Months 23967654.65 0.00 0.00 1145.49 0.00 3664036.68 80598.90 0.00 0.47
Maximum of Months 0.112339E+09 3334144.17 664.05 4221859.29 114359.15 0.311954E+09 0.298615E+09 433.78 0.47



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 74206790.37 0.00 0.00 12511.77 0.00 0.336273E+09 1928943.90 0.00 0.47
February 93763384.35 0.00 0.00 64208.96 0.00 0.273865E+09 9596865.07 0.00 0.47
March 0.111678E+09 0.00 0.00 79508.52 0.00 0.285173E+09 15994969.29 0.00 0.47
April 97100313.71 0.00 0.00 1858496.99 25703.99 0.159683E+09 0.163297E+09 0.00 0.47
May 93088884.26 60699.92 0.00 2408911.89 0.00 0.118031E+09 0.217031E+09 0.00 0.47
June 55790989.16 3327596.78 0.00 3302808.63 54025.54 23006875.72 0.283387E+09 0.00 0.47
July 44937102.31 2256994.08 554.62 3808717.93 160265.59 22833893.35 0.256023E+09 543.08 0.47
August 34416473.37 1499905.81 0.00 3313867.12 149277.82 8452313.74 0.261263E+09 0.00 0.47
September 71401398.48 1070189.23 0.00 1900202.49 17409.55 84885024.46 0.203170E+09 0.00 0.47
October 0.118734E+09 0.00 0.00 403912.46 0.00 0.261974E+09 52029366.45 0.00 0.47
November 95840089.30 0.00 0.00 16759.06 0.00 0.304997E+09 3039284.19 0.00 0.47
December 39647168.56 0.00 0.00 191.28 0.00 0.335135E+09 65212.29 0.00 0.47
                   
Annual Sum or Average 0.930605E+09 8215385.82 554.62 17170097.10 406682.49 0.221431E+10 0.146683E+10 543.08 0.47
Minimum of Months 34416473.37 0.00 0.00 191.28 0.00 8452313.74 65212.29 0.00 0.47
Maximum of Months 0.118734E+09 3327596.78 554.62 3808717.93 160265.59 0.336273E+09 0.283387E+09 543.08 0.47



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.528911E+09 0.00 0.00 4524936.58 0.00 0.137635E+10 0.740119E+09 0.00 0.53
February 0.487105E+09 0.00 0.00 5469641.61 0.00 0.109702E+10 0.834582E+09 0.00 0.54
March 0.688851E+09 0.00 0.00 2526529.01 0.00 0.122654E+10 0.735230E+09 0.00 0.54
April 0.309826E+09 0.00 0.00 18542468.80 165154.36 0.346360E+09 0.203633E+10 0.00 0.54
May 0.404790E+09 390011.68 0.00 16008756.78 0.00 0.319440E+09 0.202621E+10 0.00 0.54
June 0.281765E+09 21066493.42 0.00 18055153.19 661248.86 38533860.63 0.200999E+10 0.00 0.54
July 0.229370E+09 14792811.60 3836.97 21190147.59 738667.13 5759858.73 0.184861E+10 3216.04 0.54
August 0.160141E+09 10252043.94 0.00 24976189.96 344360.24 2648306.73 0.178764E+10 0.00 0.54
September 0.220314E+09 6906652.42 0.00 25044509.45 81433.13 27947293.60 0.204850E+10 0.00 0.54
October 0.488234E+09 0.00 0.00 11713737.11 0.00 0.614843E+09 0.166825E+10 0.00 0.54
November 0.553221E+09 0.00 0.00 3817744.09 0.00 0.117675E+10 0.861324E+09 0.00 0.53
December 0.525883E+09 0.00 0.00 1284212.29 0.00 0.159044E+10 0.290876E+09 0.00 0.54
                   
Annual Sum or Average 0.487841E+10 53408013.06 3836.97 0.153154E+09 1990863.71 0.782264E+10 0.168877E+11 3216.04 0.54
Minimum of Months 0.160141E+09 0.00 0.00 1284212.29 0.00 2648306.73 0.290876E+09 0.00 0.53
Maximum of Months 0.688851E+09 21066493.42 3836.97 25044509.45 738667.13 0.159044E+10 0.204850E+10 3216.04 0.54



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.374970E+11 0.00 0.00 5244079.60 0.00 0.00 0.244287E+11 0.00 7.82
February 0.328190E+11 0.00 0.00 5141284.54 0.00 0.00 0.227232E+11 0.00 7.87
March 0.345046E+11 0.00 0.00 7407099.08 0.00 0.00 0.273064E+11 0.00 7.84
April 0.288966E+11 0.00 0.00 9676223.55 8037577.94 0.00 0.293464E+11 0.00 7.85
May 0.291916E+11 0.00 0.00 11922520.14 8509075.10 0.00 0.310847E+11 0.00 7.84
June 0.197633E+11 0.142667E+09 0.00 15160436.58 0.179818E+09 0.00 0.330213E+11 0.00 7.88
July 0.164298E+11 0.101505E+09 0.00 16346143.63 0.210210E+09 0.00 0.316345E+11 0.00 7.87
August 0.136318E+11 8882584.44 0.00 15862289.20 79459411.03 0.00 0.310496E+11 0.00 7.88
September 0.217498E+11 876431.78 0.00 11692472.28 17796678.48 0.00 0.292656E+11 0.00 7.88
October 0.341878E+11 0.00 0.00 8424911.64 0.00 0.00 0.273376E+11 0.00 7.87
November 0.348677E+11 0.00 0.00 6563888.59 0.00 0.00 0.246955E+11 0.00 7.81
December 0.367752E+11 0.00 0.00 4946370.16 0.00 0.00 0.244806E+11 0.00 7.87
                   
Annual Sum or Average 0.340314E+12 0.253931E+09 0.00 0.118388E+09 0.503830E+09 0.00 0.336374E+12 0.00 7.86
Minimum of Months 0.136318E+11 0.00 0.00 4946370.16 0.00 0.00 0.227232E+11 0.00 7.81
Maximum of Months 0.374970E+11 0.142667E+09 0.00 16346143.63 0.210210E+09 0.00 0.330213E+11 0.00 7.88



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.371611E+11 0.00 0.00 7395802.37 0.00 0.00 0.277960E+11 0.00 8.21
February 0.328960E+11 0.00 0.00 7135616.15 0.00 0.00 0.253650E+11 0.00 8.25
March 0.330129E+11 0.00 0.00 10130040.27 0.00 0.00 0.318235E+11 0.00 8.22
April 0.261226E+11 1268614.08 0.00 13250594.67 7162668.73 0.00 0.349702E+11 0.00 8.24
May 0.254766E+11 4836618.45 0.00 16036876.63 4089256.89 0.00 0.377488E+11 0.00 8.22
June 0.170275E+11 0.185420E+09 0.00 19963325.29 0.152861E+09 0.00 0.383387E+11 0.00 8.27
July 0.141041E+11 0.194075E+09 0.00 21367080.06 0.132909E+09 0.00 0.363104E+11 0.00 8.26
August 0.110347E+11 13977214.50 0.00 20667736.88 78692039.05 0.00 0.358313E+11 0.00 8.26
September 0.189145E+11 919362.06 0.00 15458161.60 18668413.60 0.00 0.345965E+11 0.00 8.27
October 0.320776E+11 0.00 0.00 11385368.19 0.00 0.00 0.324590E+11 0.00 8.26
November 0.344973E+11 0.00 0.00 8950336.09 0.00 0.00 0.279815E+11 0.00 8.20
December 0.368385E+11 0.00 0.00 7050588.11 0.00 0.00 0.274159E+11 0.00 8.26
                   
Annual Sum or Average 0.319163E+12 0.400497E+09 0.00 0.158792E+09 0.394382E+09 0.00 0.390637E+12 0.00 8.24
Minimum of Months 0.110347E+11 0.00 0.00 7050588.11 0.00 0.00 0.253650E+11 0.00 8.20
Maximum of Months 0.371611E+11 0.194075E+09 0.00 21367080.06 0.152861E+09 0.00 0.383387E+11 0.00 8.27



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.00 0.00 0.00 93060648.41 0.00 0.00 0.653249E+11 0.00 26.66
February 0.00 0.00 0.00 85526289.23 0.00 0.00 0.585938E+11 0.00 26.81
March 0.00 0.00 0.00 91566451.75 0.00 0.00 0.652212E+11 0.00 26.71
April 0.00 8516949.01 0.00 0.107921E+09 0.00 0.00 0.614697E+11 0.00 26.79
May 0.00 9010002.49 0.00 0.112179E+09 0.00 0.00 0.636175E+11 0.00 26.73
June 0.00 0.341761E+09 0.00 0.109378E+09 0.00 0.00 0.557037E+11 0.00 26.86
July 0.00 0.330359E+09 0.00 0.115140E+09 0.00 0.00 0.507091E+11 0.00 26.85
August 0.00 93606999.33 0.00 0.118733E+09 0.00 0.00 0.471259E+11 0.00 26.87
September 0.00 19779330.33 0.00 0.113657E+09 0.00 0.00 0.538220E+11 0.00 26.88
October 0.00 0.00 0.00 98666764.05 0.00 0.00 0.649248E+11 0.00 26.83
November 0.00 0.00 0.00 90575558.30 0.00 0.00 0.628379E+11 0.00 26.62
December 0.00 0.00 0.00 92391266.24 0.00 0.00 0.646117E+11 0.00 26.82
                   
Annual Sum or Average 0.00 0.803034E+09 0.00 0.122879E+10 0.00 0.00 0.713962E+12 0.00 26.79
Minimum of Months 0.00 0.00 0.00 85526289.23 0.00 0.00 0.471259E+11 0.00 26.62
Maximum of Months 0.00 0.341761E+09 0.00 0.118733E+09 0.00 0.00 0.653249E+11 0.00 26.88



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.135707E+11 0.00 0.00 0.00 0.00 0.821175E+10 0.00 0.00 2.21
February 0.147175E+11 0.00 0.00 0.00 0.00 0.481968E+10 0.00 0.00 2.22
March 0.187439E+11 0.00 0.00 0.00 0.00 0.299897E+10 0.00 0.00 2.21
April 0.202525E+11 0.00 0.00 0.00 2826990.90 0.236184E+09 0.00 0.00 2.22
May 0.212047E+11 0.00 0.00 0.00 2992826.71 0.00 0.00 0.00 2.21
June 0.185708E+11 0.00 0.00 0.00 0.113425E+09 0.00 0.00 0.00 2.22
July 0.169110E+11 0.00 0.00 0.00 0.109637E+09 0.00 0.00 0.00 2.22
August 0.157210E+11 0.00 0.00 0.00 31071800.42 0.00 0.00 0.00 2.22
September 0.179473E+11 0.00 0.00 0.00 6567738.84 0.00 0.00 0.00 2.22
October 0.212769E+11 0.00 0.00 0.00 0.00 0.365865E+09 0.00 0.00 2.22
November 0.173370E+11 0.00 0.00 0.00 0.00 0.361501E+10 0.00 0.00 2.21
December 0.933035E+10 0.00 0.00 0.00 0.00 0.122164E+11 0.00 0.00 2.22
                   
Annual Sum or Average 0.205584E+12 0.00 0.00 0.00 0.266521E+09 0.324639E+11 0.00 0.00 2.22
Minimum of Months 0.933035E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2.21
Maximum of Months 0.212769E+11 0.00 0.00 0.00 0.113425E+09 0.122164E+11 0.00 0.00 2.22



Table of Contents

Report: HeatEmissionsReportMonthly

For: Environment

Timestamp: 2023-10-16 08:58:31

Custom Monthly Report

SITE TOTAL SURFACE HEAT EMISSION TO AIR [J] SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J]
January 0.801437E+11 0.150263E+11 0.116977E+12 0.144662E+13 0.892820E+11
February 0.129607E+12 0.134904E+11 0.104535E+12 0.130767E+13 0.812122E+11
March 0.166277E+12 0.135705E+11 0.106184E+12 0.131539E+13 0.867639E+11
April 0.419850E+12 0.107476E+11 0.850502E+11 0.104256E+13 0.204634E+12
May 0.546322E+12 0.102403E+11 0.835440E+11 0.990307E+12 0.215549E+12
June 0.552776E+12 0.711185E+10 0.630491E+11 0.689759E+12 0.347706E+12
July 0.553774E+12 0.609857E+10 0.556507E+11 0.577942E+12 0.477745E+12
August 0.443516E+12 0.574459E+10 0.515821E+11 0.525734E+12 0.521709E+12
September 0.323649E+12 0.711435E+10 0.617036E+11 0.687067E+12 0.364561E+12
October 0.147247E+12 0.106151E+11 0.873177E+11 0.103877E+13 0.137557E+12
November 0.589574E+11 0.124852E+11 0.100032E+12 0.120835E+13 0.857424E+11
December 0.211363E+11 0.149881E+11 0.117229E+12 0.145154E+13 0.791816E+11
           
Annual Sum or Average 0.344326E+13 0.127233E+12 0.103285E+13 0.122817E+14 0.269164E+13
Minimum of Months 0.211363E+11 0.574459E+10 0.515821E+11 0.525734E+12 0.791816E+11
Maximum of Months 0.553774E+12 0.150263E+11 0.117229E+12 0.145154E+13 0.521709E+12