Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:58
Tabular Output Report in Format: HTML
Building: HotelLarge
Environment: RUNPERIOD 1 ** International Falls Intl Ap MN USA TMY3 WMO#=727470
Simulation Timestamp: 2023-10-16 08:58:23
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:58:23
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 17808.78 | 1569.71 | 1569.71 |
Net Site Energy | 17808.78 | 1569.71 | 1569.71 |
Total Source Energy | 35208.79 | 3103.39 | 3103.39 |
Net Source Energy | 35208.79 | 3103.39 | 3103.39 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 11345.29 |
Net Conditioned Building Area | 11345.29 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 4819.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 985.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1174.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 261.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1751.30 | 1788.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 679.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1919.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 189.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 510.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 90.81 | 3565.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Refrigeration | 72.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 7635.18 | 10173.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 4819.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 985.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 1174.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 261.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 959.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 762.04 | 1198.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 16.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 13.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 590.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 32.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 616.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 30.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 1919.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 189.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 510.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 90.81 | 3565.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5742.51 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4114.69 | |
Refrigeration | General | 18.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 21.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 32.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 4819.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 985.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 1174.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 261.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 1751.30 | 1788.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 679.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 1919.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 189.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 510.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 90.81 | 3565.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Refrigeration | Unassigned | 72.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 126.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 280.76 | 739.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Other | 265.67 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 672.98 | 896.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 126.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 280.76 | 739.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Other | 265.67 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 672.98 | 896.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 7635.178 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 7635.178 | 100.00 |
Total On-Site and Utility Electric Sources | 7635.178 | 100.00 |
Total Electricity End Uses | 7635.178 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | 0.00 |
Air to Air Heat Recovery for Cooling | 433.49 | 4.52 |
Air to Air Heat Recovery for Heating | 9161.55 | 95.48 |
High-Temperature Geothermal* | 0.00 | 0.00 |
Solar Water Thermal | 0.00 | 0.00 |
Solar Air Thermal | 0.00 | 0.00 |
Total On-Site Thermal Sources | 9595.04 | 100.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 9857.19 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 9857.19 | 100.00 |
Total Water End Uses | 9857.19 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 1156.83 |
Time Setpoint Not Met During Occupied Cooling | 8.83 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 7327.50 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2012
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 7
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_INTERNATIONALFALLS
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneHeatingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneElectricSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |PeakSpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ComfortReportSimple55Monthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |OccupantComfortDataSummaryMonthly
| BASEMENT PEOPLE | RETAIL_1_FLR_1 PEOPLE | RETAIL_2_FLR_1 PEOPLE | LAUNDRY_FLR_1 PEOPLE | CAFE_FLR_1 PEOPLE | LOBBY_FLR_1 PEOPLE | ROOM_1_FLR_3 PEOPLE | ROOM_2_FLR_3 PEOPLE | ROOM_3_MULT19_FLR_3 PEOPLE | ROOM_4_MULT19_FLR_3 PEOPLE | ROOM_5_FLR_3 PEOPLE | ROOM_6_FLR_3 PEOPLE | ROOM_1_FLR_6 PEOPLE | ROOM_2_FLR_6 PEOPLE | ROOM_3_MULT9_FLR_6 PEOPLE | BANQUET_FLR_6 PEOPLE | DINING_FLR_6 PEOPLE | KITCHEN_FLR_6 PEOPLE | STORAGE_FLR_1 PEOPLE | CORRIDOR_FLR_3 PEOPLE | CORRIDOR_FLR_6 PEOPLE | MECH_FLR_1 PEOPLE |ChillerReportMonthly
| COOLSYS1 CHILLER1 |BoilerReportMonthly
| HEATSYS1 BOILER |DXReportMonthly
| VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |WindowReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowEnergyReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWH BOOSTER E WATER HEATER | SWH LAUNDRY G WATER HEATER | SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| VAV WITH REHEAT HEATING COIL | BASEMENT VAV BOX REHEAT COIL | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | MECH_FLR_1 VAV BOX REHEAT COIL | STORAGE_FLR_1 VAV BOX REHEAT COIL | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | CAFE_FLR_1 VAV BOX REHEAT COIL | LOBBY_FLR_1 VAV BOX REHEAT COIL | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | BANQUET_FLR_6 VAV BOX REHEAT COIL | DINING_FLR_6 VAV BOX REHEAT COIL | KITCHEN_FLR_6 VAV BOX REHEAT COIL | FLR_3_DOAS HEATING COIL | ROOM_1_FLR_3 FAN COIL HEATING COIL | ROOM_2_FLR_3 FAN COIL HEATING COIL | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_5_FLR_3 FAN COIL HEATING COIL | ROOM_6_FLR_3 FAN COIL HEATING COIL | ROOM_1_FLR_6 FAN COIL HEATING COIL | ROOM_2_FLR_6 FAN COIL HEATING COIL | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1 | SWHSYS1 |FanReportMonthly
| FLR_3_DOAS FAN | VAV WITH REHEAT FAN | LAUNDRY_FLR_1 EXHAUST FAN | LOBBY_FLR_1 EXHAUST FAN | BANQUET_FLR_6 EXHAUST FAN | DINING_FLR_6 EXHAUST FAN | KITCHEN_FLR_6 EXHAUST FAN | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 PUMP | SWHSYS1 PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1 | SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV WITH REHEAT | FLR_3_DOAS |AirLoopSystemComponentLoadsMonthly
| VAV WITH REHEAT | FLR_3_DOAS |AirLoopSystemComponentEnergyUseMonthly
| VAV WITH REHEAT | FLR_3_DOAS |MechanicalVentilationLoadsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:58:23
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:58 |
RunPeriod | RUNPERIOD 1 |
Weather File | International Falls Intl Ap MN USA TMY3 WMO#=727470 |
Latitude [deg] | 48.57 |
Longitude [deg] | -93.4 |
Elevation [m] | 359.00 |
Time Zone | -6.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1213.79 | 432.95 | 85.85 | 609.15 | 85.85 |
Gross Window-Wall Ratio [%] | 26.62 | 23.11 | 21.12 | 32.52 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.15 | 26.05 | 24.48 | 36.65 | 24.48 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1213.79 | 432.95 | 85.85 | 609.15 | 85.85 |
Gross Window-Wall Ratio [%] | 26.62 | 23.11 | 21.12 | 32.52 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.15 | 26.05 | 24.48 | 36.65 | 24.48 |
Total | |
Gross Roof Area [m2] | 1978.84 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 1978.83 | Yes | Yes | 4826.41 | 1.00 | 0.00 | 533.77 | 0.00 | 0.00 | 8.7495 | 18.58 | 5.3800 |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 265.76 | 1.00 | 68.84 | 0.00 | 23.26 | 23.26 | 13.0124 | 6.19 | 10.7600 |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 307.76 | 1.00 | 26.57 | 0.00 | 0.00 | 0.00 | 13.0124 | 6.19 | 10.7600 |
MECH_FLR_1 | 164.24 | Yes | Yes | 650.80 | 1.00 | 62.80 | 0.00 | 0.00 | 0.00 | 10.0642 | 61.93 | 5.3800 |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 375.47 | 1.00 | 36.23 | 0.00 | 0.00 | 0.00 | 7.3195 | 46.45 | 2.6900 |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 309.22 | 1.00 | 85.75 | 0.00 | 0.00 | 0.00 | 5.4896 | 9.29 | 597.5300 |
CAFE_FLR_1 | 188.86 | Yes | Yes | 748.35 | 1.00 | 152.17 | 0.00 | 65.50 | 65.50 | 12.8090 | 1.33 | 5.3800 |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 5183.56 | 1.00 | 434.79 | 0.00 | 85.08 | 85.08 | 10.0642 | 3.10 | 8.0700 |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 10.0642 | 26.01 | 6.7500 |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 10.0642 | 26.01 | 6.7500 |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 74.75 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 10.0642 | 16.35 | 10.5200 |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 74.77 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 10.0642 | 16.35 | 10.5200 |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 10.0642 | 26.01 | 6.7500 |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 10.0642 | 26.01 | 6.7500 |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 1186.91 | 4.00 | 48.31 | 0.00 | 15.94 | 15.94 | 3.6597 | 18.58 | 0.0000 |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 118.94 | 1.00 | 39.95 | 0.00 | 13.18 | 13.18 | 10.0642 | 26.01 | 6.7500 |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 118.93 | 1.00 | 39.95 | 0.00 | 13.18 | 13.18 | 10.0642 | 26.01 | 6.7500 |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 74.77 | 9.00 | 20.44 | 0.00 | 6.74 | 6.74 | 10.0642 | 16.35 | 10.5200 |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.19 | 32.19 | 12.8090 | 1.33 | 67.8200 |
DINING_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.19 | 32.19 | 12.8090 | 1.33 | 67.8200 |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 314.87 | 1.00 | 87.33 | 0.00 | 26.37 | 26.37 | 10.9792 | 4.65 | 2936.4163 |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1256.16 | 1.00 | 85.47 | 0.00 | 28.20 | 28.20 | 3.6597 | 18.58 | 0.0000 |
Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1213.79 | 1213.79 | 8.9207 | 7.07 | 41.0885 | |||
Conditioned Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1213.79 | 1213.79 | 8.9207 | 7.07 | 41.0885 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 1978.83 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 8.7495 | 18.58 | 5.3800 | |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 1.00 | RETAIL_1_FLR_1 | GENERAL | RETAIL_1_FLR_1 | 13.0124 | 6.19 | 10.7600 | |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 1.00 | RETAIL_2_FLR_1 | GENERAL | RETAIL_2_FLR_1 | 13.0124 | 6.19 | 10.7600 | |
MECH_FLR_1 | 164.24 | Yes | Yes | 1.00 | MECH_FLR_1 | GENERAL | MECH_FLR_1 | 10.0642 | 61.93 | 5.3800 | |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 1.00 | STORAGE_FLR_1 | GENERAL | STORAGE_FLR_1 | 7.3195 | 46.45 | 2.6900 | |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 1.00 | LAUNDRY_FLR_1 | GENERAL | LAUNDRY_FLR_1 | 5.4896 | 9.29 | 597.5300 | |
CAFE_FLR_1 | 188.86 | Yes | Yes | 1.00 | CAFE_FLR_1 | GENERAL | CAFE_FLR_1 | 12.8090 | 1.33 | 5.3800 | |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 1.00 | LOBBY_FLR_1 | GENERAL | LOBBY_FLR_1 | 10.0642 | 3.10 | 8.0700 | |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_1_FLR_3 | GENERAL | ROOM_1_FLR_3 | 10.0642 | 26.01 | 6.7500 | |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_2_FLR_3 | GENERAL | ROOM_2_FLR_3 | 10.0642 | 26.01 | 6.7500 | |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 76.00 | ROOM_3_MULT19_FLR_3 | GENERAL | ROOM_3_MULT19_FLR_3 | 10.0642 | 16.35 | 10.5200 | |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 76.00 | ROOM_4_MULT19_FLR_3 | GENERAL | ROOM_4_MULT19_FLR_3 | 10.0642 | 16.35 | 10.5200 | |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_5_FLR_3 | GENERAL | ROOM_5_FLR_3 | 10.0642 | 26.01 | 6.7500 | |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_6_FLR_3 | GENERAL | ROOM_6_FLR_3 | 10.0642 | 26.01 | 6.7500 | |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 4.00 | CORRIDOR_FLR_3 | GENERAL | CORRIDOR_FLR_3 | 3.6597 | 18.58 | 0.0000 | |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 1.00 | ROOM_1_FLR_6 | GENERAL | ROOM_1_FLR_6 | 10.0642 | 26.01 | 6.7500 | |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 1.00 | ROOM_2_FLR_6 | GENERAL | ROOM_2_FLR_6 | 10.0642 | 26.01 | 6.7500 | |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 9.00 | ROOM_3_MULT9_FLR_6 | GENERAL | ROOM_3_MULT9_FLR_6 | 10.0642 | 16.35 | 10.5200 | |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1.00 | BANQUET_FLR_6 | GENERAL | BANQUET_FLR_6 | 12.8090 | 1.33 | 67.8200 | |
DINING_FLR_6 | 331.66 | Yes | Yes | 1.00 | DINING_FLR_6 | GENERAL | DINING_FLR_6 | 12.8090 | 1.33 | 67.8200 | |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 1.00 | KITCHEN_FLR_6 | GENERAL | KITCHEN_FLR_6 | 10.9792 | 4.65 | 2936.4163 | |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1.00 | CORRIDOR_FLR_6 | GENERAL | CORRIDOR_FLR_6 | 3.6597 | 18.58 | 0.0000 | |
Total | 11345.29 | 8.9207 | 3.54 | 41.0885 | |||||||
Conditioned Total | 11345.29 | 8.9207 | 3.54 | 41.0885 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 11345.29 | 11345.29 | 0.00 | 0.00 | 4.6908 | 8.82 | 37.2165 |
Total | 11345.29 | 11345.29 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:58:23
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 29-JUN-18:10 | 04-JAN-21:00 | - | - | - | - | - | - | - | - | - | - | 12-JAN-21:10 |
Heating | 0.00 | 1046732.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 293975.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 82800.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 79617.06 | 75123.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 32686.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 78734.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 13182.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 18156.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 4617.14 | 309492.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 2933.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 606703.94 | 1431349.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 1046732.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 293975.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 82800.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 49434.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 29240.64 | 37488.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 515.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 425.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 37635.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 1560.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 30153.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 972.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 78734.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 13182.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 18156.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 4617.14 | 309492.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 642.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 1186.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 1103.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:58:23
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 5224.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 3121.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 3718.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 828.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 5546.36 | 1939.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 2152.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 6077.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 601.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 1616.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 287.59 | 3865.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 230.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 24180.61 | 11028.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 460.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 275.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 327.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 73.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 488.87 | 170.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 189.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 535.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 52.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 142.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 25.35 | 340.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 20.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2131.34 | 972.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 460.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 275.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 327.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 73.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 488.87 | 170.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 189.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 535.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 52.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 142.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 25.35 | 340.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 20.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2131.34 | 972.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:58:23
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
BASEMENT VAV BOX COMPONENT | 2.51 | 0.599713 | 0.994000 | 2.50 | 1.00 | 0.500000 | 0.000635 | 0.000128 | 2.50 | 16.70 | 0.008000 |
RETAIL_1_FLR_1 VAV BOX COMPONENT | 0.461601 | 0.110720 | 0.994000 | 0.458832 | 0.994000 | 0.500000 | 0.003441 | 0.000056 | 0.458832 | 16.70 | 0.008000 |
RETAIL_2_FLR_1 VAV BOX COMPONENT | 0.245889 | 0.240693 | 0.994000 | 0.244413 | 0.994000 | 0.500000 | 0.001583 | 0.000023 | 0.244413 | 16.70 | 0.008000 |
MECH_FLR_1 VAV BOX COMPONENT | 0.239818 | 0.521869 | 0.994000 | 0.238379 | 1.00 | 0.500000 | 0.000730 | 0.000033 | 0.238379 | 16.70 | 0.008000 |
STORAGE_FLR_1 VAV BOX COMPONENT | 0.118899 | 0.607293 | 0.994000 | 0.118186 | 1.00 | 0.500000 | 0.000627 | 0.000019 | 0.118186 | 16.70 | 0.008000 |
LAUNDRY_FLR_1 VAV BOX COMPONENT | 3.40 | 0.069442 | 0.994000 | 3.38 | 0.994000 | 0.500000 | 0.021772 | 0.000179 | 3.38 | 16.70 | 0.008000 |
CAFE_FLR_1 VAV BOX COMPONENT | 1.85 | 0.077950 | 0.994000 | 1.84 | 0.994000 | 0.500000 | 0.004888 | 0.000170 | 1.84 | 16.70 | 0.008000 |
LOBBY_FLR_1 VAV BOX COMPONENT | 5.26 | 0.189419 | 0.994000 | 5.23 | 0.994000 | 0.500000 | 0.002011 | 0.000442 | 5.23 | 16.70 | 0.008000 |
CORRIDOR_FLR_3 VAV BOX COMPONENT | 1.33 | 0.895549 | 0.994000 | 1.32 | 1.00 | 0.500000 | 0.000425 | 0.000183 | 1.32 | 16.70 | 0.008000 |
BANQUET_FLR_6 VAV BOX COMPONENT | 2.28 | 0.111077 | 0.994000 | 2.26 | 0.994000 | 0.500000 | 0.003430 | 0.000180 | 2.26 | 16.70 | 0.008000 |
DINING_FLR_6 VAV BOX COMPONENT | 2.39 | 0.105737 | 0.994000 | 2.38 | 0.994000 | 0.500000 | 0.003603 | 0.000187 | 2.38 | 16.70 | 0.008000 |
KITCHEN_FLR_6 VAV BOX COMPONENT | 2.43 | 0.775962 | 0.994000 | 2.42 | 0.994000 | 0.500000 | 0.011775 | 0.000140 | 2.42 | 16.70 | 0.008000 |
CORRIDOR_FLR_6 VAV BOX COMPONENT | 0.739885 | 0.424443 | 0.994000 | 0.735445 | 1.00 | 0.500000 | 0.000898 | 0.000116 | 0.735445 | 16.70 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
BASEMENT VAV BOX REHEAT COIL | 14586.41 | 0.000128 | 306.62 |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 6391.11 | 0.000056 | 146.74 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 2589.87 | 0.000023 | 57.27 |
MECH_FLR_1 VAV BOX REHEAT COIL | 3767.59 | 0.000033 | 88.42 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | 2223.51 | 0.000019 | 54.12 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 20460.30 | 0.000179 | 431.07 |
CAFE_FLR_1 VAV BOX REHEAT COIL | 19458.84 | 0.000170 | 430.34 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | 50492.89 | 0.000442 | 1105.23 |
ROOM_1_FLR_3 FAN COIL HEATING COIL | 9500.40 | 0.000083 | 271.49 |
ROOM_2_FLR_3 FAN COIL HEATING COIL | 9507.96 | 0.000083 | 271.70 |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | 53726.54 | 0.000470 | 1535.30 |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | 53886.01 | 0.000471 | 1539.86 |
ROOM_5_FLR_3 FAN COIL HEATING COIL | 9516.55 | 0.000083 | 271.95 |
ROOM_6_FLR_3 FAN COIL HEATING COIL | 9524.10 | 0.000083 | 272.16 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 20871.05 | 0.000183 | 490.05 |
ROOM_1_FLR_6 FAN COIL HEATING COIL | 2900.10 | 0.000025 | 82.87 |
ROOM_2_FLR_6 FAN COIL HEATING COIL | 2900.31 | 0.000025 | 82.88 |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | 13843.61 | 0.000121 | 395.58 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | 20629.97 | 0.000180 | 448.98 |
DINING_FLR_6 VAV BOX REHEAT COIL | 21383.05 | 0.000187 | 464.76 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | 15951.90 | 0.000140 | 337.98 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 13257.70 | 0.000116 | 319.57 |
VAV WITH REHEAT HEATING COIL | 397205.34 | 0.003475 | 5528.21 |
FLR_3_DOAS HEATING COIL | 35250.36 | 0.000308 | 490.61 |
User-Specified Maximum Flow Rate [m3/s] | |
LOBBY_FLR_1 EXHAUST FAN | 0.000000 |
BANQUET_FLR_6 EXHAUST FAN | 0.000000 |
DINING_FLR_6 EXHAUST FAN | 0.000000 |
Design Size Maximum Air Flow Rate [m3/s] | |
ROOM_1_FLR_3 DIRECT AIR | 0.061735 |
ROOM_2_FLR_3 DIRECT AIR | 0.061728 |
ROOM_3_MULT19_FLR_3 DIRECT AIR | 0.837072 |
ROOM_4_MULT19_FLR_3 DIRECT AIR | 0.837300 |
ROOM_5_FLR_3 DIRECT AIR | 0.061735 |
ROOM_6_FLR_3 DIRECT AIR | 0.061728 |
ROOM_1_FLR_6 DIRECT AIR | 0.015434 |
ROOM_2_FLR_6 DIRECT AIR | 0.015432 |
ROOM_3_MULT9_FLR_6 DIRECT AIR | 0.099154 |
Design Size Maximum Supply Air Flow Rate [m3/s] | Design Size Maximum Hot Water Flow [m3/s] | Design Size Maximum Cold Water Flow [m3/s] | |
ROOM_1_FLR_3 FAN COIL | 1.36 | 0.000083 | 0.000574 |
ROOM_2_FLR_3 FAN COIL | 1.29 | 0.000083 | 0.000547 |
ROOM_3_MULT19_FLR_3 FAN COIL | 8.81 | 0.000470 | 0.003664 |
ROOM_4_MULT19_FLR_3 FAN COIL | 6.64 | 0.000471 | 0.002924 |
ROOM_5_FLR_3 FAN COIL | 1.24 | 0.000083 | 0.000524 |
ROOM_6_FLR_3 FAN COIL | 1.18 | 0.000083 | 0.000499 |
ROOM_1_FLR_6 FAN COIL | 0.355771 | 0.000025 | 0.000150 |
ROOM_2_FLR_6 FAN COIL | 0.337477 | 0.000025 | 0.000143 |
ROOM_3_MULT9_FLR_6 FAN COIL | 1.74 | 0.000121 | 0.000743 |
Design Size Maximum Flow Rate [m3/s] | |
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | 1.36 |
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | 1.29 |
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | 8.81 |
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | 6.64 |
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | 1.24 |
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | 1.18 |
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | 0.355771 |
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | 0.337477 |
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | 1.74 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Temperature [C] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | Design Size Design Coil Load [W] | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | 22.55 | 6.70 | 0.008622 | 12.80 | 0.008500 | 0.000574 | 1.36 | |
ROOM_2_FLR_3 FAN COIL COOLING COIL | 22.55 | 6.70 | 0.008628 | 12.80 | 0.008500 | 0.000547 | 1.29 | |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | 22.55 | 6.70 | 0.008554 | 12.80 | 0.008500 | 0.003664 | 8.81 | |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | 22.55 | 6.70 | 0.008790 | 12.80 | 0.008500 | 0.002924 | 6.64 | |
ROOM_5_FLR_3 FAN COIL COOLING COIL | 22.55 | 6.70 | 0.008635 | 12.80 | 0.008500 | 0.000524 | 1.24 | |
ROOM_6_FLR_3 FAN COIL COOLING COIL | 22.55 | 6.70 | 0.008642 | 12.80 | 0.008500 | 0.000499 | 1.18 | |
ROOM_1_FLR_6 FAN COIL COOLING COIL | 22.55 | 6.70 | 0.008617 | 12.80 | 0.008500 | 0.000150 | 0.355771 | |
ROOM_2_FLR_6 FAN COIL COOLING COIL | 22.55 | 6.70 | 0.008623 | 12.80 | 0.008500 | 0.000143 | 0.337477 | |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | 22.55 | 6.70 | 0.008658 | 12.80 | 0.008500 | 0.000743 | 1.74 | |
VAV WITH REHEAT COOLING COIL | 30.10 | 6.70 | 0.012726 | 10.91 | 0.008500 | 0.028951 | 23.11 | 810549.86 |
FLR_3_DOAS COOLING COIL | 30.10 | 6.70 | 0.012726 | 11.90 | 0.008500 | 0.002484 | 2.05 | 69550.09 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV WITH REHEAT | 23.11 | 23.11 | 23.25 | 23.11 | 23.11 | 23.11 | 0.300000 | 0.999864 | 23.11 |
FLR_3_DOAS | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 0.300000 | 1.00 | 2.05 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV WITH REHEAT_OA_CONTROLLER | 23.11 | 23.11 |
FLR_3_DOAS_OA_CONTROLLER | 2.05 | 2.05 |
Design Size Nominal Supply Air Flow Rate [m3/s] | |
VAV WITH REHEAT OA HEAT RECOVERY | 23.11 |
FLR_3_DOAS OA HEAT RECOVERY | 2.05 |
Design Size Maximum Flow Rate [m3/s] | |
VAV WITH REHEAT FAN | 23.11 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV WITH REHEAT_COOLC_CONTROLLER | 0.028951 | 0.000016 |
VAV WITH REHEAT_HEATC_CONTROLLER | 0.003475 | |
FLR_3_DOAS_COOLC_CONTROLLER | 0.002484 | 0.000192 |
FLR_3_DOAS_HEATC_CONTROLLER | 0.000308 |
User-Specified Maximum Flow Rate [m3/s] | |
FLR_3_DOAS FAN | 2.05 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.041205 | 8490.73 | |
HEATSYS1 PUMP | 0.007085 | 2133.60 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
HEATSYS1 | 0.007085 | 0.850165 |
COOLSYS1 | 0.041205 | 4.94 |
SWHSYS1 | 0.000375 | 0.045004 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 809825.45 | 809825.45 | 0.007085 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 PUMP | 0.041205 | 5878.42 |
SWHSYS1 PUMP | 0.000375 | 47.91 |
Design Size Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Fluid Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.041205 | 1153617.03 | 1154247.76 | 131.58 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000375 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:58:23
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesPossible Shadow Receivers | |
RETAIL_1_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
CAFE_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
LOBBY_FLR_1_CEILING_2 | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
Possible Shadow Receivers | |
RETAIL_1_FLR_1_WALL_SOUTH | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | |
RETAIL_2_FLR_1_WALL_WEST | RETAIL_2_FLR_1_WALL_WEST_DOOR | |
STORAGE_FLR_1_WALL_NORTH | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | |
LAUNDRY_FLR_1_WALL_EAST | LAUNDRY_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_EAST | CAFE_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_SOUTH | CAFE_FLR_1_WALL_SOUTH_WINDOW | |
LOBBY_FLR_1_WALL_1_NORTH | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | |
LOBBY_FLR_1_WALL_1_SOUTH | LOBBY_FLR_1_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_SOUTH | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_WEST | ROOM_1_FLR_3_WALL_WEST_WINDOW | |
ROOM_2_FLR_3_WALL_NORTH | ROOM_2_FLR_3_WALL_NORTH_WINDOW | |
ROOM_2_FLR_3_WALL_WEST | ROOM_2_FLR_3_WALL_WEST_WINDOW | |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_4_MULT19_FLR_3_WALL_NORTH | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | |
ROOM_5_FLR_3_WALL_EAST | ROOM_5_FLR_3_WALL_EAST_WINDOW | |
ROOM_5_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_6_FLR_3_WALL_NORTH | ROOM_6_FLR_3_WALL_NORTH_WINDOW | |
ROOM_6_FLR_3_WALL_EAST | ROOM_6_FLR_3_WALL_EAST_WINDOW | |
CORRIDOR_FLR_3_WALL_1_NORTH | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_NORTH | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_SOUTH | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_WEST | ROOM_1_FLR_6_WALL_WEST_WINDOW | |
ROOM_2_FLR_6_WALL_NORTH | ROOM_2_FLR_6_WALL_NORTH_WINDOW | |
ROOM_2_FLR_6_WALL_WEST | ROOM_2_FLR_6_WALL_WEST_WINDOW | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | |
BANQUET_FLR_6_WALL_NORTH | BANQUET_FLR_6_WALL_NORTH_WINDOW | |
DINING_FLR_6_WALL_NORTH | DINING_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_NORTH | KITCHEN_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_EAST | KITCHEN_FLR_6_WALL_EAST_WINDOW | |
KITCHEN_FLR_6_WALL_1_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_6_WALL_1_NORTH | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_NORTH | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:58:23
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:58:23
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 5.40 | -2.00 | -14.60 | -16.90 | -11.50 | -6.20 | 4.00 | 13.40 | 18.00 | 19.70 | 17.90 | 12.30 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | International Falls Intl Ap MN USA TMY3 WMO#=727470 | 48.57 | -93.40 | -6.00 | 359.00 | 97086 | 1.1539 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 3.29 | 36.60 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | HotelLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | DOE-2 |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 22 | 235 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 41.45 | 11.51 | -1.22 | 1 | 1 | 1 | 0.00 | 86.56 | 0.00 | 22.86 | -2.44 | 0.00 | 2.44 | 4826.41 | TARP | DOE-2 | 1978.83 | 0.00 | 0.00 | 0.00 | 13 | 0 | 0 | Yes |
2 | RETAIL_1_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 2.90 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 265.76 | TARP | DOE-2 | 67.07 | 68.84 | 45.58 | 23.26 | 6 | 1 | 0 | Yes |
3 | RETAIL_2_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 9.14 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 5.79 | 12.50 | 0.00 | 3.96 | 3.96 | 307.76 | TARP | DOE-2 | 77.67 | 26.57 | 24.62 | 0.00 | 6 | 1 | 0 | Yes |
4 | MECH_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 61.87 | 17.68 | 1.98 | 1 | 1 | 1 | 53.95 | 69.80 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 650.80 | TARP | DOE-2 | 164.24 | 62.80 | 62.80 | 0.00 | 6 | 0 | 0 | Yes |
5 | STORAGE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 74.37 | 17.68 | 1.98 | 1 | 1 | 1 | 69.80 | 78.94 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 375.47 | TARP | DOE-2 | 94.76 | 36.23 | 28.80 | 0.00 | 6 | 1 | 0 | Yes |
6 | LAUNDRY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 14.33 | 1.98 | 1 | 1 | 1 | 81.99 | 86.56 | 5.79 | 22.86 | 0.00 | 3.96 | 3.96 | 309.22 | TARP | DOE-2 | 78.04 | 85.75 | 83.80 | 0.00 | 6 | 1 | 0 | Yes |
7 | CAFE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 70.26 | 2.90 | 1.98 | 1 | 1 | 1 | 53.95 | 86.56 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 748.35 | TARP | DOE-2 | 188.86 | 152.17 | 84.72 | 65.50 | 7 | 2 | 0 | Yes |
8 | LOBBY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 38.29 | 12.45 | 1.98 | 1 | 1 | 1 | 0.00 | 81.99 | 0.00 | 22.86 | 0.00 | 3.96 | 3.96 | 5183.56 | TARP | DOE-2 | 1308.19 | 434.79 | 345.80 | 85.08 | 18 | 3 | 0 | Yes |
9 | ROOM_1_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
10 | ROOM_2_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
11 | ROOM_3_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 8.53 | 9.14 | 8.53 | 1 | 76 | 1 | 6.71 | 10.36 | 5.79 | 12.50 | 7.01 | 10.06 | 3.05 | 74.75 | TARP | DOE-2 | 24.52 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
12 | ROOM_4_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 12.19 | 19.51 | 8.53 | 1 | 76 | 1 | 10.36 | 14.02 | 16.15 | 22.86 | 7.01 | 10.06 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
13 | ROOM_5_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 10.06 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
14 | ROOM_6_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 18.59 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
15 | CORRIDOR_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 43.28 | 14.33 | 8.53 | 1 | 4 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 7.01 | 10.06 | 3.05 | 1186.91 | TARP | DOE-2 | 389.40 | 48.31 | 32.37 | 15.94 | 20 | 4 | 0 | Yes |
16 | ROOM_1_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 16.15 | 19.20 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
17 | ROOM_2_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 16.15 | 19.20 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
18 | ROOM_3_MULT9_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 7.93 | 7.62 | 17.68 | 1 | 9 | 1 | 4.57 | 11.28 | 5.79 | 9.45 | 16.15 | 19.20 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 20.44 | 13.70 | 6.74 | 6 | 1 | 0 | Yes |
19 | BANQUET_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 26.37 | 17.68 | 17.68 | 1 | 1 | 1 | 10.36 | 42.37 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.36 | 32.19 | 6 | 1 | 0 | Yes |
20 | DINING_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 63.55 | 17.68 | 17.68 | 1 | 1 | 1 | 47.55 | 79.55 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.36 | 32.19 | 6 | 1 | 0 | Yes |
21 | KITCHEN_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 82.99 | 14.11 | 17.68 | 1 | 1 | 1 | 79.55 | 86.56 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 314.87 | TARP | DOE-2 | 103.30 | 87.33 | 60.96 | 26.37 | 8 | 3 | 0 | Yes |
22 | CORRIDOR_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 41.51 | 13.35 | 17.68 | 1 | 1 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 1256.16 | TARP | DOE-2 | 412.12 | 85.47 | 57.27 | 28.20 | 15 | 3 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 1978.83 | 106.5 | 18.581 | 5.382E-002 | 8.749 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 14.129 | No |
2 | RETAIL_1_FLR_1 | 67.07 | 10.8 | 6.194 | 0.161 | 13.012 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 23.772 | No |
3 | RETAIL_2_FLR_1 | 77.67 | 12.5 | 6.194 | 0.161 | 13.012 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 23.772 | No |
4 | MECH_FLR_1 | 164.24 | 2.7 | 61.932 | 1.615E-002 | 10.064 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 15.444 | No |
5 | STORAGE_FLR_1 | 94.76 | 2.0 | 46.451 | 2.153E-002 | 7.319 | 2.690 | 0.000 | 0.000 | 0.000 | 0.000 | 10.009 | No |
6 | LAUNDRY_FLR_1 | 78.04 | 8.4 | 9.290 | 0.108 | 5.490 | 61.680 | 535.850 | 0.000 | 0.000 | 0.000 | 603.020 | No |
7 | CAFE_FLR_1 | 188.86 | 142.3 | 1.327 | 0.753 | 12.809 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 18.189 | No |
8 | LOBBY_FLR_1 | 1308.19 | 422.4 | 3.097 | 0.323 | 10.064 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.134 | No |
9 | ROOM_1_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 10.064 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 16.814 | No |
10 | ROOM_2_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 10.064 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 16.814 | No |
11 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 16.349 | 6.116E-002 | 10.064 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 20.584 | No |
12 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 10.064 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 20.584 | No |
13 | ROOM_5_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 10.064 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 16.814 | No |
14 | ROOM_6_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 10.064 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 16.814 | No |
15 | CORRIDOR_FLR_3 | 389.40 | 21.0 | 18.581 | 5.382E-002 | 3.660 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 3.660 | No |
16 | ROOM_1_FLR_6 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 10.064 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 16.814 | No |
17 | ROOM_2_FLR_6 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 10.064 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 16.814 | No |
18 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 10.064 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 20.584 | No |
19 | BANQUET_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 12.809 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 80.629 | No |
20 | DINING_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 12.809 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 80.629 | No |
21 | KITCHEN_FLR_6 | 103.30 | 22.2 | 4.645 | 0.215 | 10.979 | 517.156 | 2419.260 | 0.000 | 0.000 | 0.000 | 2947.395 | No |
22 | CORRIDOR_FLR_6 | 412.12 | 22.2 | 18.581 | 5.382E-002 | 3.660 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 3.660 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | BASEMENT PEOPLE | BLDG_OCC_SCH | BASEMENT | 1978.83 | 106.5 | 106.5 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 106 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | RETAIL_1_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 10.8 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | RETAIL_2_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 12.5 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 13 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | LAUNDRY_FLR_1 PEOPLE | BLDG_OCC_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 8.4 | 0.108 | 9.290 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 8 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | CAFE_FLR_1 PEOPLE | BLDG_OCC_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 142.3 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 142 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | LOBBY_FLR_1 PEOPLE | BLDG_OCC_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 422.4 | 0.323 | 3.097 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 422 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | ROOM_1_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | ROOM_2_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | ROOM_3_MULT19_FLR_3 PEOPLE | ALWAYS_OFF | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 1.5 | 6.116E-002 | 16.349 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 0 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | ROOM_4_MULT19_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | ROOM_5_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | ROOM_6_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | ROOM_1_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | ROOM_2_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | ROOM_3_MULT9_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | BANQUET_FLR_6 PEOPLE | BLDG_OCC_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | DINING_FLR_6 PEOPLE | BLDG_OCC_SCH | DINING_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | KITCHEN_FLR_6 PEOPLE | BLDG_OCC_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 22.2 | 0.215 | 4.645 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | STORAGE_FLR_1 PEOPLE | BLDG_OCC_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 2.0 | 2.153E-002 | 46.451 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | CORRIDOR_FLR_3 PEOPLE | BLDG_OCC_SCH | CORRIDOR_FLR_3 | 389.40 | 21.0 | 21.0 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 21 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
21 | CORRIDOR_FLR_6 PEOPLE | BLDG_OCC_SCH | CORRIDOR_FLR_6 | 412.12 | 22.2 | 22.2 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
22 | MECH_FLR_1 PEOPLE | BLDG_OCC_SCH | MECH_FLR_1 | 164.24 | 2.7 | 2.7 | 1.615E-002 | 61.932 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 3 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_BASEMENT | BASEMENT | 1978.83 | 106.5 | 17313.725 | 8.749 | 162.572 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 17313.725 |
2 | RETAIL_1_FLR_1_LIGHTS | LTG_SCH_RETAIL | RETAIL_1_FLR_1 | 67.07 | 10.8 | 872.757 | 13.012 | 80.594 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 872.757 |
3 | RETAIL_2_FLR_1_LIGHTS | LTG_SCH_RETAIL | RETAIL_2_FLR_1 | 77.67 | 12.5 | 1010.656 | 13.012 | 80.595 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1010.656 |
4 | MECH_FLR_1_LIGHTS | LTG_SCH_MECHANIC | MECH_FLR_1 | 164.24 | 2.7 | 1652.984 | 10.064 | 623.297 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1652.984 |
5 | STORAGE_FLR_1_LIGHTS | LTG_SCH_STORAGE | STORAGE_FLR_1 | 94.76 | 2.0 | 693.586 | 7.319 | 339.993 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 693.586 |
6 | LAUNDRY_FLR_1_LIGHTS | LTG_SCH_LAUNDRY | LAUNDRY_FLR_1 | 78.04 | 8.4 | 428.405 | 5.490 | 51.001 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 428.405 |
7 | CAFE_FLR_1_LIGHTS | LTG_SCH_DINING | CAFE_FLR_1 | 188.86 | 142.3 | 2419.140 | 12.809 | 17.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2419.140 |
8 | LOBBY_FLR_1_LIGHTS | LTG_SCH_LOBBY | LOBBY_FLR_1 | 1308.19 | 422.4 | 13165.908 | 10.064 | 31.167 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 13165.908 |
9 | ROOM_1_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_1_FLR_3 | 39.02 | 1.5 | 392.727 | 10.064 | 261.818 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 392.727 |
10 | ROOM_2_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_2_FLR_3 | 39.02 | 1.5 | 392.681 | 10.064 | 261.787 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 392.681 |
11 | ROOM_3_MULT19_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 246.814 | 10.064 | 164.543 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 246.814 |
12 | ROOM_4_MULT19_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 246.881 | 10.064 | 164.588 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 246.881 |
13 | ROOM_5_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_5_FLR_3 | 39.02 | 1.5 | 392.727 | 10.064 | 261.818 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 392.727 |
14 | ROOM_6_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_6_FLR_3 | 39.02 | 1.5 | 392.681 | 10.064 | 261.787 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 392.681 |
15 | CORRIDOR_FLR_3_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_FLR_3 | 389.40 | 21.0 | 1425.114 | 3.660 | 68.002 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1425.114 |
16 | ROOM_1_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_1_FLR_6 | 39.02 | 1.5 | 392.727 | 10.064 | 261.818 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 392.727 |
17 | ROOM_2_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_2_FLR_6 | 39.02 | 1.5 | 392.681 | 10.064 | 261.787 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 392.681 |
18 | ROOM_3_MULT9_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 246.881 | 10.064 | 164.588 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 246.881 |
19 | BANQUET_FLR_6_LIGHTS | LTG_SCH_DINING | BANQUET_FLR_6 | 331.66 | 249.9 | 4248.214 | 12.809 | 17.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 4248.214 |
20 | DINING_FLR_6_LIGHTS | LTG_SCH_DINING | DINING_FLR_6 | 331.66 | 249.9 | 4248.214 | 12.809 | 17.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 4248.214 |
21 | KITCHEN_FLR_6_LIGHTS | LTG_SCH_KITCHEN | KITCHEN_FLR_6 | 103.30 | 22.2 | 1134.198 | 10.979 | 51.003 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1134.198 |
22 | CORRIDOR_FLR_6_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_FLR_6 | 412.12 | 22.2 | 1508.264 | 3.660 | 68.001 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1508.264 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | BASEMENT_EQUIP_SCH | BASEMENT | 1978.83 | 106.5 | 10646.106 | 5.380 | 99.964 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10646.106 |
2 | RETAIL_1_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 721.688 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 721.688 |
3 | RETAIL_2_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 835.717 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 835.717 |
4 | MECH_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | MECH_FLR_1 | 164.24 | 2.7 | 883.628 | 5.380 | 333.193 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 883.628 |
5 | STORAGE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 254.902 | 2.690 | 124.952 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 254.902 |
6 | LAUNDRY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 4813.474 | 61.680 | 573.033 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 4813.474 |
7 | CAFE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 1016.077 | 5.380 | 7.140 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1016.077 |
8 | LOBBY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 10557.062 | 8.070 | 24.991 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10557.062 |
9 | ROOM_1_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_1_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
10 | ROOM_2_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_2_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
11 | ROOM_3_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 257.991 | 10.520 | 171.994 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 257.991 |
12 | ROOM_4_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
13 | ROOM_5_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_5_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
14 | ROOM_6_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_6_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
15 | ROOM_1_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_1_FLR_6 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
16 | ROOM_2_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_2_FLR_6 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
17 | ROOM_3_MULT9_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
18 | BANQUET_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
19 | DINING_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | DINING_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
20 | KITCHEN_FLR_6_MISCELEC_EQUIP | KITCHEN_ELEC_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 52482.799 | 508.040 | 2360.050 | 0.200 | 0.500 | 0.100 | 0.200 | Cooking | 0.000 | 15744.840 |
21 | KITCHEN_FLR_6_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 515.917 | 4.994 | 23.200 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 515.917 | 515.917 |
22 | KITCHEN_FLR_6_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 425.833 | 4.122 | 19.149 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 425.833 | 425.833 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LAUNDRY_FLR_1_MISCGAS_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 41817.449 | 535.850 | 4978.268 | 0.000 | 0.500 | 0.000 | 0.500 | Laundry | 0.000 | 41817.449 |
2 | KITCHEN_FLR_6_MISCGAS_EQUIP | KITCHEN_GAS_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 249920.353 | 2419.260 | 11238.437 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 74976.106 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | OVERHEAD DOOR_CON | 2 | 1 | 1 | 0.167 | 1.198 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
3 | INTERIORFURNISHINGS | 3 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 8 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 18 | 3 | 3 | 0.167 | 0.1625 | 0.900 | 0.900 | 0.770 | 0.700 | Rough |
6 | RES_ROOF | 19 | 3 | 3 | 0.167 | 0.1625 | 0.900 | 0.900 | 0.770 | 0.700 | Rough |
7 | NONRES_EXT_WALL_GRD | 21 | 3 | 9 | 0.167 | 0.6204 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | NONRES_EXT_WALL_MID | 22 | 3 | 9 | 0.167 | 0.8896 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | NONRES_EXT_WALL_TOP | 23 | 3 | 9 | 0.167 | 0.9532 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | RES_EXT_WALL_MID | 25 | 3 | 9 | 0.167 | 0.8896 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | RES_EXT_WALL_TOP | 26 | 3 | 9 | 0.167 | 0.9532 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | NONRES_FLOOR | 30 | 3 | 7 | 0.167 | 0.1901 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
13 | NONRES_FLOOR_CEILING | 33 | 3 | 7 | 0.167 | 0.1901 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
14 | BASEMENT_FLOOR | 36 | 2 | 7 | 0.333 | 2.705 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
15 | BASEMENT_WALL_NORTH_CFACTOR | 39 | 2 | 7 | 0.167 | 0.3542 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | BASEMENT_WALL_EAST_CFACTOR | 40 | 2 | 7 | 0.167 | 0.3542 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | BASEMENT_WALL_SOUTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.3542 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
18 | BASEMENT_WALL_WEST_CFACTOR | 42 | 2 | 7 | 0.167 | 0.3542 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8346 |
3 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 6.093 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
10 | RES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 6.093 |
11 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
12 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
13 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.444 |
14 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9567 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8818 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | RES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9567 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
25 | RES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8818 |
26 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
27 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.000 |
28 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
29 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
30 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
31 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
32 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.000 |
33 | M10 200MM CONCRETE BLOCK BASEMENT WALL | 0.2032 | 1.326 | 1842.000 | 912.000 | 0.1532 |
34 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
35 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.747 |
36 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
37 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.747 |
38 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
39 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.747 |
40 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
41 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.747 |
42 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
4 | 0 | 1.1981135 | 1.1981135 | 1.1981135 | |
5 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
6 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
7 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
8 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
9 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
10 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
11 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
12 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
13 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
14 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
15 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
16 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
17 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
18 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
19 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
20 | 3 | -0.63083111E-06 | 0.74112372E-09 | -0.38647046E-05 | 0.15329585E-16 |
21 | 2 | 0.78415922 | 0.99752939E-03 | 1.0633801 | -0.74093433E-06 |
22 | 1 | -22.010056 | 0.66447931E-01 | -6.3131541 | 0.20386814 |
23 | 0 | 21.355302 | 0.61958938E-01 | 5.3791822 | |
24 | 3 | -0.63083111E-06 | 0.74112372E-09 | -0.38647046E-05 | 0.15329585E-16 |
25 | 2 | 0.78415922 | 0.99752939E-03 | 1.0633801 | -0.74093433E-06 |
26 | 1 | -22.010056 | 0.66447931E-01 | -6.3131541 | 0.20386814 |
27 | 0 | 21.355302 | 0.61958938E-01 | 5.3791822 | |
28 | 9 | 0.63051269E-15 | -0.32308218E-15 | -0.16410282E-09 | -0.99951010E-17 |
29 | 8 | 0.23891583E-07 | 0.84466640E-13 | 0.39866495E-03 | -0.27165551E-09 |
30 | 7 | -0.12863314E-01 | 0.43064229E-08 | -0.23980710E-01 | 0.14626058E-03 |
31 | 6 | 0.42224327 | 0.14880745E-05 | 0.48645232 | -0.49468897E-02 |
32 | 5 | -5.3554004 | 0.55240760E-04 | -4.5514481 | 0.65227767E-01 |
33 | 4 | 33.731862 | 0.44951640E-03 | 21.870777 | -0.43180224 |
34 | 3 | -112.77696 | 0.97509968E-03 | -56.474881 | 1.5375994 |
35 | 2 | 198.66781 | 0.54620071E-03 | 78.655647 | -2.9251197 |
36 | 1 | -171.73201 | 0.58083407E-04 | -55.482579 | 2.7555333 |
37 | 0 | 57.057407 | 0.32915515E-06 | 15.521699 | |
38 | 9 | -0.23907624E-14 | 0.31597480E-16 | -0.15159381E-09 | 0.44487065E-16 |
39 | 8 | 0.22138174E-07 | 0.12005614E-12 | 0.38055753E-03 | -0.25171865E-09 |
40 | 7 | -0.12324050E-01 | 0.62153905E-08 | -0.23204591E-01 | 0.14012894E-03 |
41 | 6 | 0.40759191 | 0.21632260E-05 | 0.47399999 | -0.47741848E-02 |
42 | 5 | -5.2124386 | 0.80803221E-04 | -4.4559231 | 0.63455088E-01 |
43 | 4 | 33.099615 | 0.66123170E-03 | 21.497653 | -0.42340758 |
44 | 3 | -111.43211 | 0.14415773E-02 | -55.737335 | 1.5181690 |
45 | 2 | 197.33529 | 0.81112906E-03 | 77.978757 | -2.9039585 |
46 | 1 | -171.23995 | 0.86614752E-04 | -55.284900 | 2.7469094 |
47 | 0 | 57.057407 | 0.49323094E-06 | 15.553656 | |
48 | 9 | 0.63796015E-17 | 0.35026513E-16 | -0.14861226E-09 | 0.64921151E-18 |
49 | 8 | 0.21719229E-07 | 0.12822517E-12 | 0.37616054E-03 | -0.24695511E-09 |
50 | 7 | -0.12192862E-01 | 0.66681186E-08 | -0.23015708E-01 | 0.13863728E-03 |
51 | 6 | 0.40402730 | 0.23249961E-05 | 0.47096453 | -0.47321665E-02 |
52 | 5 | -5.1776524 | 0.86981116E-04 | -4.4326110 | 0.63023755E-01 |
53 | 4 | 32.945748 | 0.71278800E-03 | 21.406536 | -0.42136466 |
54 | 3 | -111.10474 | 0.15559249E-02 | -55.557197 | 1.5134395 |
55 | 2 | 197.01084 | 0.87644643E-03 | 77.813538 | -2.8988062 |
56 | 1 | -171.12011 | 0.93686201E-04 | -55.236846 | 2.7448090 |
57 | 0 | 57.057407 | 0.53410260E-06 | 15.561584 | |
58 | 9 | -0.23907624E-14 | 0.31597480E-16 | -0.15159381E-09 | 0.44487065E-16 |
59 | 8 | 0.22138174E-07 | 0.12005614E-12 | 0.38055753E-03 | -0.25171865E-09 |
60 | 7 | -0.12324050E-01 | 0.62153905E-08 | -0.23204591E-01 | 0.14012894E-03 |
61 | 6 | 0.40759191 | 0.21632260E-05 | 0.47399999 | -0.47741848E-02 |
62 | 5 | -5.2124386 | 0.80803221E-04 | -4.4559231 | 0.63455088E-01 |
63 | 4 | 33.099615 | 0.66123170E-03 | 21.497653 | -0.42340758 |
64 | 3 | -111.43211 | 0.14415773E-02 | -55.737335 | 1.5181690 |
65 | 2 | 197.33529 | 0.81112906E-03 | 77.978757 | -2.9039585 |
66 | 1 | -171.23995 | 0.86614752E-04 | -55.284900 | 2.7469094 |
67 | 0 | 57.057407 | 0.49323094E-06 | 15.553656 | |
68 | 9 | 0.63796015E-17 | 0.35026513E-16 | -0.14861226E-09 | 0.64921151E-18 |
69 | 8 | 0.21719229E-07 | 0.12822517E-12 | 0.37616054E-03 | -0.24695511E-09 |
70 | 7 | -0.12192862E-01 | 0.66681186E-08 | -0.23015708E-01 | 0.13863728E-03 |
71 | 6 | 0.40402730 | 0.23249961E-05 | 0.47096453 | -0.47321665E-02 |
72 | 5 | -5.1776524 | 0.86981116E-04 | -4.4326110 | 0.63023755E-01 |
73 | 4 | 32.945748 | 0.71278800E-03 | 21.406536 | -0.42136466 |
74 | 3 | -111.10474 | 0.15559249E-02 | -55.557197 | 1.5134395 |
75 | 2 | 197.01084 | 0.87644643E-03 | 77.813538 | -2.8988062 |
76 | 1 | -171.12011 | 0.93686201E-04 | -55.236846 | 2.7448090 |
77 | 0 | 57.057407 | 0.53410260E-06 | 15.561584 | |
78 | 7 | -0.16359629E-14 | -0.14530353E-16 | -0.22331004E-13 | 0.54056000E-15 |
79 | 6 | 0.18262352E-10 | 0.22801053E-11 | 0.52333849E-09 | -0.18642118E-10 |
80 | 5 | -0.59540244E-07 | 0.11129510E-07 | -0.21928235E-05 | 0.17164558E-06 |
81 | 4 | 0.60861605E-04 | 0.41961443E-05 | 0.17683552E-02 | -0.28248824E-03 |
82 | 3 | -0.87523238E-02 | 0.14809838E-03 | -0.21562890 | 0.43346081E-01 |
83 | 2 | 0.12409989 | 0.64146884E-03 | 2.9009744 | -0.61915653 |
84 | 1 | -0.31397648 | 0.40472017E-03 | -7.1381115 | 1.5697592 |
85 | 0 | 0.19977219 | 0.56546383E-05 | 4.4522022 | |
86 | 7 | -0.22331004E-13 | -0.14530353E-16 | -0.16359629E-14 | 0.54056000E-15 |
87 | 6 | 0.52333849E-09 | 0.22801053E-11 | 0.18262352E-10 | -0.18642118E-10 |
88 | 5 | -0.21928235E-05 | 0.11129510E-07 | -0.59540244E-07 | 0.17164558E-06 |
89 | 4 | 0.17683552E-02 | 0.41961443E-05 | 0.60861605E-04 | -0.28248824E-03 |
90 | 3 | -0.21562890 | 0.14809838E-03 | -0.87523238E-02 | 0.43346081E-01 |
91 | 2 | 2.9009744 | 0.64146884E-03 | 0.12409989 | -0.61915653 |
92 | 1 | -7.1381115 | 0.40472017E-03 | -0.31397648 | 1.5697592 |
93 | 0 | 4.4522022 | 0.56546383E-05 | 0.19977219 | |
94 | 7 | -0.52459208E-15 | -0.63961428E-15 | -0.12292524E-09 | -0.35846135E-17 |
95 | 6 | 0.39860198E-02 | 0.96339020E-07 | 0.40499006E-03 | -0.70890431E-04 |
96 | 5 | -0.20832379 | 0.49172556E-04 | -0.20585669E-01 | 0.38489246E-02 |
97 | 4 | 3.5198270 | 0.18993977E-02 | 0.34924834 | -0.69168259E-01 |
98 | 3 | -23.366787 | 0.13311857E-01 | -2.4329538 | 0.50524779 |
99 | 2 | 64.890127 | 0.19943872E-01 | 7.3672511 | -1.5911358 |
100 | 1 | -76.040094 | 0.56792084E-02 | -9.5568013 | 2.1361271 |
101 | 0 | 31.242244 | 0.96490710E-04 | 4.3344156 | |
102 | 7 | -0.11729247E-08 | -0.12287178E-15 | 0.68000855E-14 | -0.85819789E-16 |
103 | 6 | 0.99010087E-05 | 0.68275672E-08 | 0.31776201E-02 | -0.26656541E-04 |
104 | 5 | -0.71743827E-03 | 0.40498262E-05 | -0.22302824 | 0.19500041E-02 |
105 | 4 | 0.16534150E-01 | 0.18445051E-03 | 4.8179460 | -0.45153479E-01 |
106 | 3 | -0.14527752 | 0.14677644E-02 | -37.955880 | 0.39792938 |
107 | 2 | 0.51595076 | 0.24428280E-02 | 116.35639 | -1.4162330 |
108 | 1 | -0.74475336 | 0.74501918E-03 | -143.83221 | 2.0478056 |
109 | 0 | 0.36311555 | 0.17917760E-04 | 60.838472 | |
110 | 7 | -0.11729247E-08 | -0.12287178E-15 | 0.68000855E-14 | -0.85819789E-16 |
111 | 6 | 0.99010087E-05 | 0.68275672E-08 | 0.31776201E-02 | -0.26656541E-04 |
112 | 5 | -0.71743827E-03 | 0.40498262E-05 | -0.22302824 | 0.19500041E-02 |
113 | 4 | 0.16534150E-01 | 0.18445051E-03 | 4.8179460 | -0.45153479E-01 |
114 | 3 | -0.14527752 | 0.14677644E-02 | -37.955880 | 0.39792938 |
115 | 2 | 0.51595076 | 0.24428280E-02 | 116.35639 | -1.4162330 |
116 | 1 | -0.74475336 | 0.74501918E-03 | -143.83221 | 2.0478056 |
117 | 0 | 0.36311555 | 0.17917760E-04 | 60.838472 | |
118 | 7 | -0.11729247E-08 | -0.12287178E-15 | 0.68000855E-14 | -0.85819789E-16 |
119 | 6 | 0.99010087E-05 | 0.68275672E-08 | 0.31776201E-02 | -0.26656541E-04 |
120 | 5 | -0.71743827E-03 | 0.40498262E-05 | -0.22302824 | 0.19500041E-02 |
121 | 4 | 0.16534150E-01 | 0.18445051E-03 | 4.8179460 | -0.45153479E-01 |
122 | 3 | -0.14527752 | 0.14677644E-02 | -37.955880 | 0.39792938 |
123 | 2 | 0.51595076 | 0.24428280E-02 | 116.35639 | -1.4162330 |
124 | 1 | -0.74475336 | 0.74501918E-03 | -143.83221 | 2.0478056 |
125 | 0 | 0.36311555 | 0.17917760E-04 | 60.838472 | |
126 | 7 | -0.11729247E-08 | -0.12287178E-15 | 0.68000855E-14 | -0.85819789E-16 |
127 | 6 | 0.99010087E-05 | 0.68275672E-08 | 0.31776201E-02 | -0.26656541E-04 |
128 | 5 | -0.71743827E-03 | 0.40498262E-05 | -0.22302824 | 0.19500041E-02 |
129 | 4 | 0.16534150E-01 | 0.18445051E-03 | 4.8179460 | -0.45153479E-01 |
130 | 3 | -0.14527752 | 0.14677644E-02 | -37.955880 | 0.39792938 |
131 | 2 | 0.51595076 | 0.24428280E-02 | 116.35639 | -1.4162330 |
132 | 1 | -0.74475336 | 0.74501918E-03 | -143.83221 | 2.0478056 |
133 | 0 | 0.36311555 | 0.17917760E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.2964_SHGC_0.45 | 37 | 1 | VerySmooth | 1.683 | 1.683 | 1.000 | 0.451 | ||
2 | RESWINDOW_U_0.2964_SHGC_0.45 | 38 | 1 | VerySmooth | 1.683 | 1.683 | 1.000 | 0.451 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER | SpectralAverage | 4.21322E-002 | 0.36619 | 0.44048 | 0.44048 | 0.45000 | 0.13324 | 0.16828 | 0.00000 | 0.84000 | 0.84000 | 0.10036 | 1.00000 | No | |
2 | RESIDENTIAL WINDOW GLAZING LAYER | SpectralAverage | 4.21322E-002 | 0.36619 | 0.44048 | 0.44048 | 0.45000 | 0.13324 | 0.16828 | 0.00000 | 0.84000 | 0.84000 | 0.10036 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 7 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 1.500 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 3.000 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWH BOOSTER E WATER HEATER | 2.2712E-002 | 8000.0 | 1.240 | 1.1473 |
2 | WaterHeater:Mixed | SWH LAUNDRY G WATER HEATER | 1.1356 | 163316.0 | 0.576 | 0.5074 |
3 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 2.2712 | 175842.6 | 0.260 | 2.5713E-002 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
6 | BASEMENT_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
7 | BASEMENT_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
8 | BASEMENT_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
9 | BASEMENT_CEILING_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
10 | BASEMENT_CEILING_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
11 | BASEMENT_CEILING_6 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
12 | BASEMENT_CEILING_7 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
13 | BASEMENT_CEILING_8 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
14 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
15 | RETAIL_1_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 4 | No | No |
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 1 | No | No |
17 | RETAIL_1_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 3 | No | No |
18 | RETAIL_1_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
19 | RETAIL_1_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
20 | RETAIL_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
21 | RETAIL_1_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
23 | RETAIL_2_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
25 | RETAIL_2_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
26 | RETAIL_2_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
27 | RETAIL_2_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
28 | RETAIL_2_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
29 | RETAIL_2_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
31 | MECH_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
32 | MECH_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
33 | MECH_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
34 | MECH_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
35 | MECH_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
36 | MECH_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
37 | MECH_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
38 | STORAGE_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
40 | STORAGE_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
41 | STORAGE_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
42 | STORAGE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
43 | STORAGE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
44 | STORAGE_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
45 | STORAGE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
46 | LAUNDRY_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
47 | LAUNDRY_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
49 | LAUNDRY_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
50 | LAUNDRY_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
51 | LAUNDRY_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
52 | LAUNDRY_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
54 | CAFE_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 3 | No | No |
55 | CAFE_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
56 | CAFE_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 4 | No | No |
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 1 | No | No |
58 | CAFE_FLR_1_WALL_1_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
59 | CAFE_FLR_1_WALL_2_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
60 | CAFE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
61 | CAFE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
62 | CAFE_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
63 | CAFE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
64 | LOBBY_FLR_1_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
67 | LOBBY_FLR_1_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
68 | LOBBY_FLR_1_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 1 | No | No |
70 | LOBBY_FLR_1_WALL_1_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
71 | LOBBY_FLR_1_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
72 | LOBBY_FLR_1_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
73 | LOBBY_FLR_1_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
74 | LOBBY_FLR_1_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
75 | LOBBY_FLR_1_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
76 | LOBBY_FLR_1_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
77 | LOBBY_FLR_1_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
78 | LOBBY_FLR_1_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
79 | LOBBY_FLR_1_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
80 | LOBBY_FLR_1_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
81 | LOBBY_FLR_1_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
82 | LOBBY_FLR_1_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
83 | LOBBY_FLR_1_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
84 | LOBBY_FLR_1_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
85 | LOBBY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
86 | ROOM_1_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
88 | ROOM_1_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
90 | ROOM_1_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
91 | ROOM_1_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
92 | ROOM_1_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
93 | ROOM_1_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
94 | ROOM_1_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
95 | ROOM_2_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
97 | ROOM_2_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
99 | ROOM_2_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
100 | ROOM_2_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
101 | ROOM_2_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
102 | ROOM_2_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
103 | ROOM_2_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
109 | ROOM_3_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
110 | ROOM_3_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
117 | ROOM_4_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
118 | ROOM_4_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
120 | ROOM_5_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
122 | ROOM_5_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
124 | ROOM_5_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
125 | ROOM_5_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
126 | ROOM_5_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
127 | ROOM_5_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
128 | ROOM_5_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
129 | ROOM_6_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
131 | ROOM_6_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
133 | ROOM_6_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
134 | ROOM_6_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
135 | ROOM_6_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
136 | ROOM_6_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
137 | ROOM_6_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
138 | CORRIDOR_FLR_3_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
147 | CORRIDOR_FLR_3_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
148 | CORRIDOR_FLR_3_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
149 | CORRIDOR_FLR_3_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
150 | CORRIDOR_FLR_3_WALL_4_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
152 | CORRIDOR_FLR_3_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
153 | CORRIDOR_FLR_3_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
154 | CORRIDOR_FLR_3_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
155 | CORRIDOR_FLR_3_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
156 | CORRIDOR_FLR_3_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
157 | CORRIDOR_FLR_3_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
158 | CORRIDOR_FLR_3_FLOOR_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
159 | CORRIDOR_FLR_3_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
160 | CORRIDOR_FLR_3_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
161 | CORRIDOR_FLR_3_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
163 | ROOM_1_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
165 | ROOM_1_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
167 | ROOM_1_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
168 | ROOM_1_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
169 | ROOM_1_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
170 | ROOM_1_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
171 | ROOM_1_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
172 | ROOM_2_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
174 | ROOM_2_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
176 | ROOM_2_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
177 | ROOM_2_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
178 | ROOM_2_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
179 | ROOM_2_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
180 | ROOM_2_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 3 | No | No |
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 2 | No | No |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
186 | ROOM_3_MULT9_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
187 | ROOM_3_MULT9_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
189 | BANQUET_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
191 | BANQUET_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
192 | BANQUET_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
193 | BANQUET_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
194 | BANQUET_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
195 | BANQUET_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
196 | BANQUET_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
197 | DINING_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
198 | DINING_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
199 | DINING_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
200 | DINING_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
201 | DINING_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
202 | DINING_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
203 | DINING_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
204 | DINING_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
205 | KITCHEN_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
207 | KITCHEN_FLR_6_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
212 | KITCHEN_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
213 | KITCHEN_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
214 | KITCHEN_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
215 | KITCHEN_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
216 | KITCHEN_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
217 | CORRIDOR_FLR_6_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
224 | CORRIDOR_FLR_6_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
226 | CORRIDOR_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
227 | CORRIDOR_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
228 | CORRIDOR_FLR_6_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
229 | CORRIDOR_FLR_6_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
230 | CORRIDOR_FLR_6_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
231 | CORRIDOR_FLR_6_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
232 | CORRIDOR_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
233 | CORRIDOR_FLR_6_CEILING_1 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
234 | CORRIDOR_FLR_6_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | RETAIL_1_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 3.921E-002 | 5.846E-004 | 2.885E-004 | 0.531 | 1.000 | 0.000 | 0.000 | 0.000 |
2 | RETAIL_2_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 1.513E-002 | 1.949E-004 | 5.306E-004 | 0.177 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | MECH_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | MECH_FLR_1 | 164.24 | 2.7 | 3.577E-002 | 2.178E-004 | 5.696E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
4 | STORAGE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 2.064E-002 | 2.178E-004 | 4.726E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | LAUNDRY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 4.884E-002 | 6.258E-004 | 5.569E-004 | 0.569 | 1.000 | 0.000 | 0.000 | 0.000 |
6 | CAFE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 8.667E-002 | 4.589E-004 | 2.527E-004 | 0.417 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | LOBBY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 0.248 | 1.893E-004 | 3.620E-004 | 0.172 | 1.000 | 0.000 | 0.000 | 0.000 |
8 | ROOM_1_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | ROOM_2_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
10 | ROOM_3_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 6.349E-003 | 2.589E-004 | 5.696E-004 | 0.306 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | ROOM_4_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 6.350E-003 | 2.589E-004 | 5.696E-004 | 0.306 | 1.000 | 0.000 | 0.000 | 0.000 |
12 | ROOM_5_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | ROOM_6_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
14 | CORRIDOR_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_3 | 389.40 | 21.0 | 2.751E-002 | 7.066E-005 | 5.696E-004 | 8.345E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | ROOM_1_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 2.881E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
16 | ROOM_2_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 2.881E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | ROOM_3_MULT9_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 1.164E-002 | 4.746E-004 | 2.589E-004 | 0.561 | 1.000 | 0.000 | 0.000 | 0.000 |
18 | BANQUET_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 5.556E-002 | 1.675E-004 | 1.295E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | DINING_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | DINING_FLR_6 | 331.66 | 249.9 | 5.556E-002 | 1.675E-004 | 1.295E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
20 | KITCHEN_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 4.974E-002 | 4.815E-004 | 2.609E-004 | 0.569 | 1.000 | 0.000 | 0.000 | 0.000 |
21 | CORRIDOR_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_6 | 412.12 | 22.2 | 4.868E-002 | 1.181E-004 | 9.784E-005 | 0.140 | 1.000 | 0.000 | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | ROOM_1_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
2 | ROOM_2_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
3 | ROOM_3_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
4 | ROOM_4_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
5 | ROOM_5_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_5_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
6 | ROOM_6_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_6_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
7 | ROOM_1_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
8 | ROOM_2_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
9 | ROOM_3_MULT9_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | RETAIL_1_FLR_1 | Mixing/Well-Stirred |
3 | RETAIL_2_FLR_1 | Mixing/Well-Stirred |
4 | MECH_FLR_1 | Mixing/Well-Stirred |
5 | STORAGE_FLR_1 | Mixing/Well-Stirred |
6 | LAUNDRY_FLR_1 | Mixing/Well-Stirred |
7 | CAFE_FLR_1 | Mixing/Well-Stirred |
8 | LOBBY_FLR_1 | Mixing/Well-Stirred |
9 | ROOM_1_FLR_3 | Mixing/Well-Stirred |
10 | ROOM_2_FLR_3 | Mixing/Well-Stirred |
11 | ROOM_3_MULT19_FLR_3 | Mixing/Well-Stirred |
12 | ROOM_4_MULT19_FLR_3 | Mixing/Well-Stirred |
13 | ROOM_5_FLR_3 | Mixing/Well-Stirred |
14 | ROOM_6_FLR_3 | Mixing/Well-Stirred |
15 | CORRIDOR_FLR_3 | Mixing/Well-Stirred |
16 | ROOM_1_FLR_6 | Mixing/Well-Stirred |
17 | ROOM_2_FLR_6 | Mixing/Well-Stirred |
18 | ROOM_3_MULT9_FLR_6 | Mixing/Well-Stirred |
19 | BANQUET_FLR_6 | Mixing/Well-Stirred |
20 | DINING_FLR_6 | Mixing/Well-Stirred |
21 | KITCHEN_FLR_6 | Mixing/Well-Stirred |
22 | CORRIDOR_FLR_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 33161.17229 | 33161.17229 | 2.51432 | 2.51432 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 25.26400 | 1.27174E-002 | 1978.83018 | 106.49900 | 0.85446 | 0.00000 |
2 | BASEMENT | Heating | 1941.25412 | 1941.25412 | 8.68308E-002 | 0.85446 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -32.70000 | 1.83376E-004 | 1978.83018 | 106.49900 | 0.85446 | 0.00000 |
3 | RETAIL_1_FLR_1 | Cooling | 6087.26336 | 6087.26336 | 0.46160 | 0.46160 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 29.79000 | 1.27253E-002 | 67.07136 | 10.82900 | 7.92179E-002 | 0.00000 |
4 | RETAIL_1_FLR_1 | Heating | 4072.53235 | 4072.53235 | 0.18214 | 0.18214 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -32.70000 | 1.83376E-004 | 67.07136 | 10.82900 | 7.92179E-002 | 0.00000 |
5 | RETAIL_2_FLR_1 | Cooling | 3242.59948 | 3242.59948 | 0.24589 | 0.24589 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 29.97600 | 1.27256E-002 | 77.66889 | 12.54000 | 9.17347E-002 | 0.00000 |
6 | RETAIL_2_FLR_1 | Heating | 1354.64274 | 1354.64274 | 6.05897E-002 | 9.17347E-002 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -32.70000 | 1.83376E-004 | 77.66889 | 12.54000 | 9.17347E-002 | 0.00000 |
7 | MECH_FLR_1 | Cooling | 3163.21848 | 3163.21848 | 0.23982 | 0.23982 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 29.97600 | 1.27256E-002 | 164.24319 | 2.65200 | 0.00000 | 0.00000 |
8 | MECH_FLR_1 | Heating | 2563.17034 | 2563.17034 | 0.11464 | 0.11464 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -32.70000 | 1.83376E-004 | 164.24319 | 2.65200 | 0.00000 | 0.00000 |
9 | STORAGE_FLR_1 | Cooling | 1568.27739 | 1568.27739 | 0.11890 | 0.11890 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 30.10000 | 1.27259E-002 | 94.75927 | 2.04000 | 5.77652E-002 | 0.00000 |
10 | STORAGE_FLR_1 | Heating | 1626.30330 | 1626.30330 | 7.27400E-002 | 7.27400E-002 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -32.70000 | 1.83376E-004 | 94.75927 | 2.04000 | 5.77652E-002 | 0.00000 |
11 | LAUNDRY_FLR_1 | Cooling | 44816.66814 | 44816.66814 | 3.39814 | 3.39814 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 30.10000 | 1.27259E-002 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
12 | LAUNDRY_FLR_1 | Heating | 3399.00104 | 3399.00104 | 0.15202 | 0.15202 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -32.70000 | 1.83376E-004 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
13 | CAFE_FLR_1 | Cooling | 24327.27922 | 24327.27922 | 1.84623 | 1.84623 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 29.79000 | 1.27253E-002 | 188.86188 | 142.30000 | 0.67639 | 0.00000 |
14 | CAFE_FLR_1 | Heating | 10183.85852 | 10183.85852 | 0.45548 | 0.67639 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -32.70000 | 1.83376E-004 | 188.86188 | 142.30000 | 0.67639 | 0.00000 |
15 | LOBBY_FLR_1 | Cooling | 69380.17004 | 69380.17004 | 5.26259 | 5.26259 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 29.89333 | 1.27255E-002 | 1308.18612 | 422.43500 | 1.89399 | 0.00000 |
16 | LOBBY_FLR_1 | Heating | 24055.32188 | 24055.32188 | 1.07593 | 1.89399 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -32.70000 | 1.83376E-004 | 1308.18612 | 422.43500 | 1.89399 | 0.00000 |
17 | ROOM_1_FLR_3 | Cooling | 13286.86471 | 13286.86471 | 1.35756 | 1.35756 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 28.15733 | 1.27224E-002 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
18 | ROOM_1_FLR_3 | Heating | 9500.54996 | 9500.54996 | 0.42740 | 0.42740 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -32.70000 | 1.83376E-004 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
19 | ROOM_2_FLR_3 | Cooling | 12652.70957 | 12652.70957 | 1.29277 | 1.29277 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 27.95067 | 1.27221E-002 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
20 | ROOM_2_FLR_3 | Heating | 9508.10511 | 9508.10511 | 0.42774 | 0.42774 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -32.70000 | 1.83376E-004 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
21 | ROOM_3_MULT19_FLR_3 | Cooling | 86265.43558 | 86265.43558 | 8.81340 | 8.81340 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 29.89333 | 1.27255E-002 | 24.52384 | 1.50000 | 0.83707 | 0.00000 |
22 | ROOM_3_MULT19_FLR_3 | Heating | 53726.97444 | 53726.97444 | 2.41715 | 2.41715 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -32.70000 | 1.83376E-004 | 24.52384 | 1.50000 | 0.83707 | 0.00000 |
23 | ROOM_4_MULT19_FLR_3 | Cooling | 64992.64296 | 64992.64296 | 6.64057 | 6.64057 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | 24.80933 | 1.27166E-002 | 24.53055 | 1.50000 | 0.83730 | 0.00000 |
24 | ROOM_4_MULT19_FLR_3 | Heating | 53886.44339 | 53886.44339 | 2.42432 | 2.42432 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -32.70000 | 1.83376E-004 | 24.53055 | 1.50000 | 0.83730 | 0.00000 |
25 | ROOM_5_FLR_3 | Cooling | 12097.83120 | 12097.83120 | 1.23608 | 1.23608 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 25.38800 | 1.27176E-002 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
26 | ROOM_5_FLR_3 | Heating | 9516.69250 | 9516.69250 | 0.42812 | 0.42812 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -32.70000 | 1.83376E-004 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
27 | ROOM_6_FLR_3 | Cooling | 11500.89367 | 11500.89367 | 1.17509 | 1.17509 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | 23.63133 | 1.27146E-002 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
28 | ROOM_6_FLR_3 | Heating | 9524.24587 | 9524.24587 | 0.42846 | 0.42846 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -32.70000 | 1.83376E-004 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
29 | CORRIDOR_FLR_3 | Cooling | 17480.08491 | 17480.08491 | 1.32534 | 1.32534 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 30.10000 | 1.27259E-002 | 389.40468 | 20.95700 | 0.47476 | 0.00000 |
30 | CORRIDOR_FLR_3 | Heating | 14210.71289 | 14210.71289 | 0.63562 | 0.63562 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -32.70000 | 1.83376E-004 | 389.40468 | 20.95700 | 0.47476 | 0.00000 |
31 | ROOM_1_FLR_6 | Cooling | 3482.04219 | 3482.04219 | 0.35577 | 0.35577 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 28.36400 | 1.27228E-002 | 39.02202 | 1.50000 | 1.54338E-002 | 0.00000 |
32 | ROOM_1_FLR_6 | Heating | 2900.14057 | 2900.14057 | 0.13047 | 0.13047 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -32.70000 | 1.83376E-004 | 39.02202 | 1.50000 | 1.54338E-002 | 0.00000 |
33 | ROOM_2_FLR_6 | Cooling | 3302.98476 | 3302.98476 | 0.33748 | 0.33748 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 27.95067 | 1.27221E-002 | 39.01745 | 1.50000 | 1.54319E-002 | 0.00000 |
34 | ROOM_2_FLR_6 | Heating | 2900.35299 | 2900.35299 | 0.13048 | 0.13048 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -32.70000 | 1.83376E-004 | 39.01745 | 1.50000 | 1.54319E-002 | 0.00000 |
35 | ROOM_3_MULT9_FLR_6 | Cooling | 17048.28937 | 17048.28937 | 1.74191 | 1.74191 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 29.89333 | 1.27255E-002 | 24.53055 | 1.50000 | 9.91540E-002 | 0.00000 |
36 | ROOM_3_MULT9_FLR_6 | Heating | 13843.76691 | 13843.76691 | 0.62280 | 0.62280 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -32.70000 | 1.83376E-004 | 24.53055 | 1.50000 | 9.91540E-002 | 0.00000 |
37 | BANQUET_FLR_6 | Cooling | 29970.44027 | 29970.44027 | 2.27520 | 2.27520 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 30.10000 | 1.27259E-002 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
38 | BANQUET_FLR_6 | Heating | 9195.48824 | 9195.48824 | 0.41129 | 1.18780 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -32.70000 | 1.83376E-004 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
39 | DINING_FLR_6 | Cooling | 31484.47266 | 31484.47266 | 2.39010 | 2.39010 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 30.10000 | 1.27259E-002 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
40 | DINING_FLR_6 | Heating | 9370.99590 | 9370.99590 | 0.41914 | 1.18780 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -32.70000 | 1.83376E-004 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
41 | KITCHEN_FLR_6 | Cooling | 32003.65374 | 32003.65374 | 2.43284 | 2.43284 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 | 25.03667 | 1.27170E-002 | 103.30446 | 22.23800 | 0.36735 | 0.00000 |
42 | KITCHEN_FLR_6 | Heating | 3747.09614 | 3747.09614 | 0.16758 | 0.36735 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | -32.70000 | 1.83376E-004 | 103.30446 | 22.23800 | 0.36735 | 0.00000 |
43 | CORRIDOR_FLR_6 | Cooling | 9758.50069 | 9758.50069 | 0.73988 | 0.73988 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 30.10000 | 1.27259E-002 | 412.12471 | 22.18000 | 0.12562 | 0.00000 |
44 | CORRIDOR_FLR_6 | Heating | 9538.77166 | 9538.77166 | 0.42665 | 0.42665 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -32.70000 | 1.83376E-004 | 412.12471 | 22.18000 | 0.12562 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV WITH REHEAT | Cooling | Sensible | 463597.48 | 23.11449 | 23.11449 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | VAV WITH REHEAT | Heating | Sensible | 449272.73 | 7.84333 | 7.84333 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 |
3 | FLR_3_DOAS | Cooling | Sensible | 41147.75 | 21.34511 | 2.05125 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | FLR_3_DOAS | Heating | Sensible | 117497.06 | 7.43694 | 2.05125 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.51432 |
2 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.59971 |
3 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.99400 |
4 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.49923 |
5 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
6 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 6.35304E-004 |
8 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.27608E-004 |
9 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.49923 |
10 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
11 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
12 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 14586.41432 |
13 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.27608E-004 |
14 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 306.61519 |
15 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.46160 |
16 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11072 |
17 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.99400 |
18 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.45883 |
19 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.99400 |
20 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
21 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.44112E-003 |
22 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.59122E-005 |
23 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.45883 |
24 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
25 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
26 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 6391.10618 |
27 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.59122E-005 |
28 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 146.73936 |
29 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.24589 |
30 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.24069 |
31 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.99400 |
32 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.24441 |
33 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.99400 |
34 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
35 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.58293E-003 |
36 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.26573E-005 |
37 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.24441 |
38 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
40 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 2589.86605 |
41 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.26573E-005 |
42 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 57.27151 |
43 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.23982 |
44 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.52187 |
45 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.99400 |
46 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.23838 |
47 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
48 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
49 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 7.30069E-004 |
50 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.29606E-005 |
51 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.23838 |
52 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
53 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
54 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 3767.59402 |
55 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.29606E-005 |
56 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 88.42318 |
57 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.11890 |
58 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.60729 |
59 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.99400 |
60 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.11819 |
61 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
62 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 6.27374E-004 |
64 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.94522E-005 |
65 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.11819 |
66 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
67 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
68 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 2223.50711 |
69 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.94522E-005 |
70 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 54.11856 |
71 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 3.39814 |
72 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 6.94421E-002 |
73 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.99400 |
74 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 3.37775 |
75 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.99400 |
76 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
77 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.17719E-002 |
78 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.78996E-004 |
79 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 3.37775 |
80 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
81 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
82 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 20460.29747 |
83 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.78996E-004 |
84 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 431.07328 |
85 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.84623 |
86 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 7.79496E-002 |
87 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.99400 |
88 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.83515 |
89 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.99400 |
90 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
91 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.88777E-003 |
92 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.70234E-004 |
93 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.83515 |
94 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
96 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 19458.83650 |
97 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.70234E-004 |
98 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 430.34065 |
99 | Fan:ZoneExhaust | LOBBY_FLR_1 EXHAUST FAN | User-Specified Maximum Flow Rate [m3/s] | 0.00000 |
100 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.26259 |
101 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.18942 |
102 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.99400 |
103 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 5.23102 |
104 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.99400 |
105 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
106 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.01141E-003 |
107 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.41734E-004 |
108 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 5.23102 |
109 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
110 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
111 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 50492.88661 |
112 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.41734E-004 |
113 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 1105.22990 |
114 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_1_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17350E-002 |
115 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.35756 |
116 | Fan:OnOff | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.35756 |
117 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 8.31137E-005 |
118 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 5.74052E-004 |
119 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 22.54750 |
120 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
121 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.62235E-003 |
122 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
123 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
124 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 5.74052E-004 |
125 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.35756 |
126 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 9500.40415 |
127 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.31137E-005 |
128 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 271.48689 |
129 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_2_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17278E-002 |
130 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.29277 |
131 | Fan:OnOff | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.29277 |
132 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 8.31798E-005 |
133 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 5.47418E-004 |
134 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 22.54748 |
135 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
136 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.62799E-003 |
137 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
138 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
139 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 5.47418E-004 |
140 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.29277 |
141 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 9507.95921 |
142 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.31798E-005 |
143 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 271.70272 |
144 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_3_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.83707 |
145 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 8.81340 |
146 | Fan:OnOff | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 8.81340 |
147 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 4.70023E-004 |
148 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.66406E-003 |
149 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 22.54826 |
150 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
151 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.55413E-003 |
152 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
153 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
154 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.66406E-003 |
155 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 8.81340 |
156 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 53726.54394 |
157 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.70023E-004 |
158 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 1535.30121 |
159 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_4_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.83730 |
160 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 6.64057 |
161 | Fan:OnOff | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 6.64057 |
162 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 4.71418E-004 |
163 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.92428E-003 |
164 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 22.54699 |
165 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
166 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.78964E-003 |
167 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
168 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
169 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.92428E-003 |
170 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 6.64057 |
171 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 53886.01182 |
172 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.71418E-004 |
173 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 1539.85717 |
174 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_5_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17350E-002 |
175 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.23608 |
176 | Fan:OnOff | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.23608 |
177 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 8.32549E-005 |
178 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 5.24307E-004 |
179 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 22.54745 |
180 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
181 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.63491E-003 |
182 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
183 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
184 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 5.24307E-004 |
185 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.23608 |
186 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 9516.54650 |
187 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.32549E-005 |
188 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 271.94806 |
189 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_6_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17278E-002 |
190 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.17509 |
191 | Fan:OnOff | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.17509 |
192 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 8.33210E-005 |
193 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 4.99312E-004 |
194 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 22.54743 |
195 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
196 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.64203E-003 |
197 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
198 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
199 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.99312E-004 |
200 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.17509 |
201 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 9524.09978 |
202 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.33210E-005 |
203 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 272.16384 |
204 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.32534 |
205 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.89555 |
206 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.99400 |
207 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.31739 |
208 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
209 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
210 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.25438E-004 |
211 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.82589E-004 |
212 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.31739 |
213 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
214 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
215 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 20871.04666 |
216 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.82589E-004 |
217 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 490.05004 |
218 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_1_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.54338E-002 |
219 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.35577 |
220 | Fan:OnOff | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.35577 |
221 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 2.53713E-005 |
222 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 1.50229E-004 |
223 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 22.54752 |
224 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
225 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.61667E-003 |
226 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
227 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
228 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.50229E-004 |
229 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.35577 |
230 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 2900.09914 |
231 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.53713E-005 |
232 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 82.87030 |
233 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_2_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.54319E-002 |
234 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.33748 |
235 | Fan:OnOff | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.33748 |
236 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 2.53732E-005 |
237 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 1.42717E-004 |
238 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 22.54750 |
239 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
240 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.62272E-003 |
241 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
242 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
243 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.42717E-004 |
244 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.33748 |
245 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 2900.31157 |
246 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.53732E-005 |
247 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 82.87636 |
248 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_3_MULT9_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 9.91540E-002 |
249 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.74191 |
250 | Fan:OnOff | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.74191 |
251 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.21110E-004 |
252 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 7.43014E-004 |
253 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 22.54729 |
254 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
255 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.65771E-003 |
256 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
257 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
258 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 7.43014E-004 |
259 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.74191 |
260 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 13843.60590 |
261 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.21110E-004 |
262 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 395.57944 |
263 | Fan:ZoneExhaust | BANQUET_FLR_6 EXHAUST FAN | User-Specified Maximum Flow Rate [m3/s] | 0.00000 |
264 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.27520 |
265 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11108 |
266 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.99400 |
267 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.26155 |
268 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.99400 |
269 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
270 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.43005E-003 |
271 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.80480E-004 |
272 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.26155 |
273 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
274 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
275 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 20629.96562 |
276 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.80480E-004 |
277 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 448.97595 |
278 | Fan:ZoneExhaust | DINING_FLR_6 EXHAUST FAN | User-Specified Maximum Flow Rate [m3/s] | 0.00000 |
279 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.39010 |
280 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10574 |
281 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.99400 |
282 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.37576 |
283 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.99400 |
284 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
285 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.60327E-003 |
286 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.87068E-004 |
287 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.37576 |
288 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
289 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
290 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 21383.04545 |
291 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.87068E-004 |
292 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 464.75544 |
293 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.43284 |
294 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.77596 |
295 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.99400 |
296 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.41824 |
297 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.99400 |
298 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
299 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.17751E-002 |
300 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.39554E-004 |
301 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.41824 |
302 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
303 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
304 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 15951.90144 |
305 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.39554E-004 |
306 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 337.97789 |
307 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.73988 |
308 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.42444 |
309 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.99400 |
310 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.73545 |
311 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
312 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
313 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 8.97647E-004 |
314 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.15984E-004 |
315 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.73545 |
316 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
317 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
318 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 13257.70421 |
319 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.15984E-004 |
320 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 319.56699 |
321 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 23.11135 |
322 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 23.11135 |
323 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 23.25085 |
324 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 23.11135 |
325 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 23.11449 |
326 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 23.11449 |
327 | AirLoopHVAC | VAV WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
328 | AirLoopHVAC | VAV WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.99986 |
329 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.05132 |
330 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.05132 |
331 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.05132 |
332 | AirLoopHVAC | FLR_3_DOAS | Adjusted Heating Design Air Flow Rate [m3/s] | 2.05132 |
333 | AirLoopHVAC | FLR_3_DOAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.05132 |
334 | AirLoopHVAC | FLR_3_DOAS | Adjusted Main Design Air Flow Rate [m3/s] | 2.05132 |
335 | AirLoopHVAC | FLR_3_DOAS | User Heating Air Flow Ratio [] | 0.30000 |
336 | AirLoopHVAC | FLR_3_DOAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
337 | AirLoopHVAC | VAV WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 23.11449 |
338 | AirLoopHVAC | FLR_3_DOAS | Design Supply Air Flow Rate [m3/s] | 2.05132 |
339 | Controller:OutdoorAir | VAV WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 23.11449 |
340 | Controller:OutdoorAir | VAV WITH REHEAT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 23.11449 |
341 | HeatExchanger:AirToAir:SensibleAndLatent | VAV WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 23.11449 |
342 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 30.10000 |
343 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
344 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.91205 |
345 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.27259E-002 |
346 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
347 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 810549.86321 |
348 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.89510E-002 |
349 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 23.11449 |
350 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 397205.34188 |
351 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.47493E-003 |
352 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 5528.20773 |
353 | Fan:VariableVolume | VAV WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 23.11449 |
354 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.89510E-002 |
355 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.64482E-005 |
356 | Controller:WaterCoil | VAV WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 3.47493E-003 |
357 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.05132 |
358 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.05125 |
359 | HeatExchanger:AirToAir:SensibleAndLatent | FLR_3_DOAS OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.05125 |
360 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 30.10000 |
361 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
362 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.89838 |
363 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.27259E-002 |
364 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
365 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Coil Load [W] | 69550.08568 |
366 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.48417E-003 |
367 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 2.05132 |
368 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size Rated Capacity [W] | 35250.35631 |
369 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.08385E-004 |
370 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 490.60592 |
371 | Fan:ConstantVolume | FLR_3_DOAS FAN | User-Specified Maximum Flow Rate [m3/s] | 2.05125 |
372 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.48417E-003 |
373 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.91690E-004 |
374 | Controller:WaterCoil | FLR_3_DOAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 3.08385E-004 |
375 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 4.12045E-002 |
376 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 8490.72592 |
377 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 7.08471E-003 |
378 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 0.85016 |
379 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 7.08471E-003 |
380 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 2133.60242 |
381 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
382 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 809825.45184 |
383 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 809825.45000 |
384 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 7.08471E-003 |
385 | PlantLoop | COOLSYS1 | Maximum Loop Flow Rate [m3/s] | 4.12045E-002 |
386 | PlantLoop | COOLSYS1 | Plant Loop Volume [m3] | 4.94454 |
387 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Flow Rate [m3/s] | 4.12045E-002 |
388 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Power Consumption [W] | 5878.41593 |
389 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 4.12045E-002 |
390 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 1153617.03129 |
391 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 1154247.76000 |
392 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 131.58424 |
393 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 3.75036E-004 |
394 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 4.50044E-002 |
395 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 3.75036E-004 |
396 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 47.90688 |
397 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 3.75036E-004 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | 14661.47 |
2 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 6421.05 |
3 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 2602.44 |
4 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | 3784.90 |
5 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | 2233.24 |
6 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 20565.37 |
7 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | 19553.30 |
8 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | 50744.00 |
9 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | 10233.30 |
10 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | 10241.44 |
11 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | 57871.67 |
12 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | 58043.42 |
13 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | 10250.69 |
14 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | 10258.82 |
15 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 20966.89 |
16 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | 3123.74 |
17 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | 3123.97 |
18 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | 14911.17 |
19 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | 20733.04 |
20 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | 21489.99 |
21 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | 16033.42 |
22 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 13316.28 |
23 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | 227854.93 |
24 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | 20221.20 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | 23917.62 | 18537.40 | 5380.22 | 0.78 | 2807.65 | 28.48 |
2 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | 22796.08 | 17661.88 | 5134.20 | 0.77 | 2675.60 | 27.14 |
3 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | 153621.15 | 119582.96 | 34038.19 | 0.78 | 18066.68 | 183.24 |
4 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | 119989.66 | 92056.54 | 27933.12 | 0.77 | 14028.93 | 142.29 |
5 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | 21819.79 | 16898.13 | 4921.66 | 0.77 | 2560.55 | 25.97 |
6 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | 20766.01 | 16074.89 | 4691.12 | 0.77 | 2436.44 | 24.71 |
7 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | 6262.47 | 4855.48 | 1406.99 | 0.78 | 735.25 | 7.46 |
8 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | 5946.04 | 4608.38 | 1337.66 | 0.78 | 697.99 | 7.08 |
9 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | 30857.07 | 23863.08 | 6993.99 | 0.77 | 3618.96 | 36.71 |
10 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | 699196.44 | 447362.92 | 251833.52 | 0.64 | 85578.34 | 867.98 |
11 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | 60010.76 | 38734.94 | 21275.82 | 0.65 | 6954.16 | 70.53 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | 3.72 | 12.68 |
Zone Name | # Surfaces | |
1 | BASEMENT | 14 |
2 | RETAIL_1_FLR_1 | 8 |
3 | RETAIL_2_FLR_1 | 8 |
4 | MECH_FLR_1 | 7 |
5 | STORAGE_FLR_1 | 8 |
6 | LAUNDRY_FLR_1 | 8 |
7 | CAFE_FLR_1 | 10 |
8 | LOBBY_FLR_1 | 22 |
9 | ROOM_1_FLR_3 | 9 |
10 | ROOM_2_FLR_3 | 9 |
11 | ROOM_3_MULT19_FLR_3 | 8 |
12 | ROOM_4_MULT19_FLR_3 | 8 |
13 | ROOM_5_FLR_3 | 9 |
14 | ROOM_6_FLR_3 | 9 |
15 | CORRIDOR_FLR_3 | 25 |
16 | ROOM_1_FLR_6 | 9 |
17 | ROOM_2_FLR_6 | 9 |
18 | ROOM_3_MULT9_FLR_6 | 8 |
19 | BANQUET_FLR_6 | 8 |
20 | DINING_FLR_6 | 8 |
21 | KITCHEN_FLR_6 | 12 |
22 | CORRIDOR_FLR_6 | 19 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.354 | 0.336 | 211.13 | 211.13 | 211.13 | 0.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.354 | 0.336 | 55.76 | 55.76 | 55.76 | 90.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.354 | 0.336 | 211.13 | 211.13 | 211.13 | 180.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_WEST_CFACTOR | 0.354 | 0.336 | 55.76 | 55.76 | 55.76 | 270.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | BASEMENT_FLOOR | 2.705 | 1.632 | 1978.83 | 1978.83 | 1978.83 | 0.00 | 180.00 | 86.56 | 22.86 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | BASEMENT_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | RETAIL_1_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | BASEMENT_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | BASEMENT_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | BASEMENT_CEILING_4 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_CEILING_5 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
11 | BASEMENT_CEILING_6 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | CAFE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
12 | BASEMENT_CEILING_7 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 0.00 | 32.99 | 32.99 | 0.00 | LOBBY_FLR_1_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
13 | BASEMENT_CEILING_8 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 219.63 | 219.63 | 219.63 | 90.00 | 0.00 | 14.82 | 14.82 | 0.00 | LOBBY_FLR_1_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
14 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 3957.66 | 3957.66 | 3957.66 | 0.00 | 90.00 | 3957.66 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
15 | RETAIL_1_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.620 | 0.568 | 22.63 | 45.89 | 22.63 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | Window | RETAIL_1_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.2964_SHGC_0.45 | N/A | 1.683 | No | 23.26 | 23.26 | 23.26 | 180.00 | 90.00 | 10.92 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
17 | RETAIL_1_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.620 | 0.568 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
18 | RETAIL_1_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | RETAIL_1_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | RETAIL_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 67.07 | 67.07 | 67.07 | 0.00 | 180.00 | 11.58 | 5.79 | 0.00 | BASEMENT_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | RETAIL_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.163 | 0.158 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 7.62E-002 | 0.92 | 4 | ||
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 134.14 | 134.14 | 134.14 | 0.00 | 90.00 | 134.14 | 1.00 | 0.00 | RETAIL_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
23 | RETAIL_2_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.620 | 0.568 | 24.62 | 26.57 | 24.62 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | Door | RETAIL_2_FLR_1_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
25 | RETAIL_2_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
26 | RETAIL_2_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | RETAIL_2_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 90.00 | 90.00 | 6.71 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | RETAIL_2_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 77.67 | 77.67 | 77.67 | 0.00 | 180.00 | 11.58 | 6.71 | 0.00 | BASEMENT_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
29 | RETAIL_2_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 155.34 | 155.34 | 155.34 | 0.00 | 90.00 | 155.34 | 1.00 | 0.00 | RETAIL_2_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
31 | MECH_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.620 | 0.568 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | MECH_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | MECH_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 180.00 | 90.00 | 15.85 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | MECH_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | MECH_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 164.24 | 164.24 | 164.24 | 0.00 | 180.00 | 15.85 | 10.36 | 0.00 | BASEMENT_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | MECH_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | MECH_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 328.49 | 328.49 | 328.49 | 0.00 | 90.00 | 328.49 | 1.00 | 0.00 | MECH_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | STORAGE_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.620 | 0.568 | 28.80 | 36.23 | 28.80 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | Door | STORAGE_FLR_1_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.198 | 1.198 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | STORAGE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
41 | STORAGE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 180.00 | 90.00 | 9.14 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
42 | STORAGE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | STORAGE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 94.76 | 94.76 | 94.76 | 0.00 | 180.00 | 9.14 | 10.36 | 0.00 | BASEMENT_CEILING_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
44 | STORAGE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | STORAGE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 189.52 | 189.52 | 189.52 | 0.00 | 90.00 | 189.52 | 1.00 | 0.00 | STORAGE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
46 | LAUNDRY_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.620 | 0.568 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | LAUNDRY_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.620 | 0.568 | 65.68 | 67.63 | 65.68 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | Door | LAUNDRY_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
49 | LAUNDRY_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 180.00 | 90.00 | 4.57 | 3.96 | 0.00 | CAFE_FLR_1_WALL_2_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | LAUNDRY_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 270.00 | 90.00 | 17.07 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
51 | LAUNDRY_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 78.04 | 78.04 | 78.04 | 0.00 | 180.00 | 4.57 | 17.07 | 0.00 | BASEMENT_CEILING_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
52 | LAUNDRY_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 156.08 | 156.08 | 156.08 | 0.00 | 90.00 | 156.08 | 1.00 | 0.00 | LAUNDRY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
54 | CAFE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.620 | 0.568 | 21.00 | 22.95 | 21.00 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CAFE_FLR_1_WALL_EAST_DOOR | Door | CAFE_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | CAFE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.620 | 0.568 | 63.73 | 129.23 | 63.73 | 180.00 | 90.00 | 32.61 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | Window | CAFE_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.2964_SHGC_0.45 | N/A | 1.683 | No | 65.50 | 65.50 | 65.50 | 180.00 | 90.00 | 30.75 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
58 | CAFE_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 0.00 | 90.00 | 28.04 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | CAFE_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | CAFE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | CAFE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 188.86 | 188.86 | 188.86 | 0.00 | 180.00 | 32.61 | 5.79 | 0.00 | BASEMENT_CEILING_6 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
62 | CAFE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.163 | 0.158 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 3.86E-002 | 0.96 | 4 | ||
63 | CAFE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 377.72 | 377.72 | 377.72 | 0.00 | 90.00 | 377.72 | 1.00 | 0.00 | CAFE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
64 | LOBBY_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.620 | 0.568 | 209.87 | 213.77 | 209.87 | 0.00 | 90.00 | 53.95 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
67 | LOBBY_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.620 | 0.568 | 12.08 | 12.08 | 12.08 | 0.00 | 90.00 | 3.05 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
68 | LOBBY_FLR_1_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.620 | 0.568 | 82.79 | 167.88 | 82.79 | 180.00 | 90.00 | 42.37 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | Window | LOBBY_FLR_1_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.2964_SHGC_0.45 | N/A | 1.683 | No | 85.08 | 85.08 | 85.08 | 180.00 | 90.00 | 39.95 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LOBBY_FLR_1_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.620 | 0.568 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | LOBBY_FLR_1_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | LOBBY_FLR_1_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 180.00 | 90.00 | 28.04 | 3.96 | 0.00 | CAFE_FLR_1_WALL_1_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | LOBBY_FLR_1_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | LOBBY_FLR_1_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | LOBBY_FLR_1_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | LOBBY_FLR_1_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | MECH_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | LOBBY_FLR_1_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
78 | LOBBY_FLR_1_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | LOBBY_FLR_1_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | CAFE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | LOBBY_FLR_1_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | LOBBY_FLR_1_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 180.00 | 32.99 | 32.99 | 0.00 | BASEMENT_CEILING_7 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
82 | LOBBY_FLR_1_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 219.63 | 219.63 | 219.63 | 90.00 | 180.00 | 14.82 | 14.82 | 0.00 | BASEMENT_CEILING_8 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
83 | LOBBY_FLR_1_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 1062.83 | 1062.83 | 1062.83 | 270.00 | 0.00 | 32.60 | 32.60 | 0.00 | LOBBY_FLR_1_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 10 | ||
84 | LOBBY_FLR_1_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.163 | 0.158 | 245.35 | 245.35 | 245.35 | 180.00 | 0.00 | 42.37 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.22E-003 | 1.00 | 4 | ||
85 | LOBBY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 2616.37 | 2616.37 | 2616.37 | 0.00 | 90.00 | 2616.37 | 1.00 | 0.00 | LOBBY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | ROOM_1_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.890 | 0.785 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.2964_SHGC_0.45 | N/A | 1.683 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | ROOM_1_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.890 | 0.785 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | Window | ROOM_1_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.2964_SHGC_0.45 | N/A | 1.683 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | ROOM_1_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | ROOM_1_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | ROOM_1_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
93 | ROOM_1_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
94 | ROOM_1_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
95 | ROOM_2_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.890 | 0.785 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.2964_SHGC_0.45 | N/A | 1.683 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
97 | ROOM_2_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.890 | 0.785 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | Window | ROOM_2_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.2964_SHGC_0.45 | N/A | 1.683 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | ROOM_2_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | ROOM_2_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | ROOM_2_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | ROOM_2_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | ROOM_2_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.890 | 0.785 | 7.47 | 11.15 | 7.47 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.2964_SHGC_0.45 | N/A | 1.683 | No | 3.68 | 3.68 | 3.68 | 180.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | ROOM_3_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 24.52 | 24.52 | 24.52 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
110 | ROOM_3_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 24.52 | 24.52 | 24.52 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.05 | 49.05 | 49.05 | 0.00 | 90.00 | 49.05 | 1.00 | 0.00 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.890 | 0.785 | 7.47 | 11.15 | 7.47 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_4_MULT19_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.2964_SHGC_0.45 | N/A | 1.683 | No | 3.68 | 3.68 | 3.68 | 0.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
117 | ROOM_4_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
118 | ROOM_4_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
120 | ROOM_5_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.890 | 0.785 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | Window | ROOM_5_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.2964_SHGC_0.45 | N/A | 1.683 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
122 | ROOM_5_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.890 | 0.785 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_5_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.2964_SHGC_0.45 | N/A | 1.683 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
124 | ROOM_5_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
125 | ROOM_5_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
126 | ROOM_5_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
127 | ROOM_5_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
128 | ROOM_5_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_5_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
129 | ROOM_6_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.890 | 0.785 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_6_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.2964_SHGC_0.45 | N/A | 1.683 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
131 | ROOM_6_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.890 | 0.785 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | Window | ROOM_6_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.2964_SHGC_0.45 | N/A | 1.683 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
133 | ROOM_6_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
134 | ROOM_6_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
135 | ROOM_6_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
136 | ROOM_6_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
137 | ROOM_6_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_6_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
138 | CORRIDOR_FLR_3_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.890 | 0.785 | 11.83 | 17.65 | 11.83 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.2964_SHGC_0.45 | N/A | 1.683 | No | 5.82 | 5.82 | 5.82 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.890 | 0.785 | 4.35 | 6.50 | 4.35 | 0.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.2964_SHGC_0.45 | N/A | 1.683 | No | 2.15 | 2.15 | 2.15 | 0.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.890 | 0.785 | 4.36 | 6.50 | 4.36 | 180.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.2964_SHGC_0.45 | N/A | 1.683 | No | 2.15 | 2.15 | 2.15 | 180.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.890 | 0.785 | 11.83 | 17.65 | 11.83 | 180.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.2964_SHGC_0.45 | N/A | 1.683 | No | 5.82 | 5.82 | 5.82 | 180.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 0.00 | 90.00 | 69.50 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | CORRIDOR_FLR_3_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | CORRIDOR_FLR_3_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORRIDOR_FLR_3_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | CORRIDOR_FLR_3_WALL_4_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 180.00 | 90.00 | 69.49 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
152 | CORRIDOR_FLR_3_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | CORRIDOR_FLR_3_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | CORRIDOR_FLR_3_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | CORRIDOR_FLR_3_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | CORRIDOR_FLR_3_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 74.32 | 74.32 | 74.32 | 180.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
157 | CORRIDOR_FLR_3_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 240.77 | 240.77 | 240.77 | 270.00 | 180.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | CORRIDOR_FLR_3_FLOOR_3 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 74.32 | 74.32 | 74.32 | 90.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
159 | CORRIDOR_FLR_3_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
160 | CORRIDOR_FLR_3_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 240.77 | 240.77 | 240.77 | 90.00 | 0.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
161 | CORRIDOR_FLR_3_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 778.81 | 778.81 | 778.81 | 0.00 | 90.00 | 778.81 | 1.00 | 0.00 | CORRIDOR_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
163 | ROOM_1_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.953 | 0.834 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.2964_SHGC_0.45 | N/A | 1.683 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
165 | ROOM_1_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.953 | 0.834 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | Window | ROOM_1_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.2964_SHGC_0.45 | N/A | 1.683 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
167 | ROOM_1_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
168 | ROOM_1_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
169 | ROOM_1_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | ROOM_1_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.163 | 0.158 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
171 | ROOM_1_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
172 | ROOM_2_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.953 | 0.834 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.2964_SHGC_0.45 | N/A | 1.683 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
174 | ROOM_2_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.953 | 0.834 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | Window | ROOM_2_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.2964_SHGC_0.45 | N/A | 1.683 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
176 | ROOM_2_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
177 | ROOM_2_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
178 | ROOM_2_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | ROOM_2_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.163 | 0.158 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
180 | ROOM_2_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.953 | 0.834 | 13.70 | 20.44 | 13.70 | 180.00 | 90.00 | 6.71 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.2964_SHGC_0.45 | N/A | 1.683 | No | 6.74 | 6.74 | 6.74 | 180.00 | 90.00 | 5.53 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 0.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 90.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | ROOM_3_MULT9_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 6.71 | 3.66 | 0.00 | ROOM_3_MULT9_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
187 | ROOM_3_MULT9_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.163 | 0.158 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 6.71 | 3.66 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
189 | BANQUET_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.953 | 0.834 | 65.36 | 97.55 | 65.36 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | Window | BANQUET_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.2964_SHGC_0.45 | N/A | 1.683 | No | 32.19 | 32.19 | 32.19 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
191 | BANQUET_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
192 | BANQUET_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
193 | BANQUET_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
194 | BANQUET_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | BANQUET_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
195 | BANQUET_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.163 | 0.158 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
196 | BANQUET_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | BANQUET_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
197 | DINING_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.953 | 0.834 | 65.36 | 97.55 | 65.36 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DINING_FLR_6_WALL_NORTH_WINDOW | Window | DINING_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.2964_SHGC_0.45 | N/A | 1.683 | No | 32.19 | 32.19 | 32.19 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
199 | DINING_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
200 | DINING_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | DINING_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DINING_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DINING_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | DINING_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
203 | DINING_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.163 | 0.158 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
204 | DINING_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | DINING_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
205 | KITCHEN_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.953 | 0.834 | 16.77 | 21.37 | 16.77 | 0.00 | 90.00 | 7.01 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | Window | KITCHEN_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.2964_SHGC_0.45 | N/A | 1.683 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
207 | KITCHEN_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.953 | 0.834 | 34.86 | 52.03 | 34.86 | 90.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | Window | KITCHEN_FLR_6_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.2964_SHGC_0.45 | N/A | 1.683 | No | 17.17 | 17.17 | 17.17 | 90.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.953 | 0.834 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | Window | KITCHEN_FLR_6_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.2964_SHGC_0.45 | N/A | 1.683 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 7.43 | 7.43 | 7.43 | 180.00 | 90.00 | 2.44 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
212 | KITCHEN_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | KITCHEN_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | KITCHEN_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 103.30 | 103.30 | 103.30 | 180.00 | 180.00 | 10.16 | 10.16 | 0.00 | KITCHEN_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
215 | KITCHEN_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.163 | 0.158 | 103.30 | 103.30 | 103.30 | 270.00 | 0.00 | 10.16 | 10.16 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
216 | KITCHEN_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 206.61 | 206.61 | 206.61 | 0.00 | 90.00 | 206.61 | 1.00 | 0.00 | KITCHEN_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
217 | CORRIDOR_FLR_6_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.953 | 0.834 | 11.83 | 17.65 | 11.83 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.2964_SHGC_0.45 | N/A | 1.683 | No | 5.82 | 5.82 | 5.82 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.953 | 0.834 | 10.58 | 15.79 | 10.58 | 0.00 | 90.00 | 5.18 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.2964_SHGC_0.45 | N/A | 1.683 | No | 5.21 | 5.21 | 5.21 | 0.00 | 90.00 | 4.27 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.953 | 0.834 | 34.86 | 52.03 | 34.86 | 180.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.2964_SHGC_0.45 | N/A | 1.683 | No | 17.17 | 17.17 | 17.17 | 180.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
224 | CORRIDOR_FLR_6_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 104.98 | 104.98 | 104.98 | 0.00 | 90.00 | 34.44 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 183.95 | 183.95 | 183.95 | 180.00 | 90.00 | 60.35 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
226 | CORRIDOR_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
227 | CORRIDOR_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 40.88 | 40.88 | 40.88 | 270.00 | 90.00 | 13.41 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
228 | CORRIDOR_FLR_6_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
229 | CORRIDOR_FLR_6_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
230 | CORRIDOR_FLR_6_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
231 | CORRIDOR_FLR_6_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
232 | CORRIDOR_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 412.12 | 412.12 | 412.12 | 180.00 | 180.00 | 20.30 | 20.30 | 0.00 | CORRIDOR_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 12 | ||
233 | CORRIDOR_FLR_6_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.163 | 0.158 | 244.71 | 244.71 | 244.71 | 90.00 | 0.00 | 15.64 | 15.64 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 8 | ||
234 | CORRIDOR_FLR_6_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.163 | 0.158 | 167.42 | 167.42 | 167.42 | 270.00 | 0.00 | 12.94 | 12.94 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 824.25 | 824.25 | 824.25 | 0.00 | 90.00 | 824.25 | 1.00 | 0.00 | CORRIDOR_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 9.4201644265E-002 | 0.2709419364 | Pass | Pass | 0.1228504413 | 0.8185124326 | Pass | Pass |
2 | RETAIL_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 0.2024776241 | 0.5787721473 | Pass | Pass | 0.1593511616 | 0.4841848872 | Pass | Pass |
3 | RETAIL_2_FLR_1 | RunPeriod: RUNPERIOD 1 | 0.1484881351 | 0.3744754504 | Pass | Pass | 5.4045292699E-002 | 0.1673686115 | Pass | Pass |
4 | MECH_FLR_1 | RunPeriod: RUNPERIOD 1 | 9.6399871981E-002 | 0.2125121351 | Pass | Pass | 2.6347839272E-002 | 7.7790261854E-002 | Pass | Pass |
5 | STORAGE_FLR_1 | RunPeriod: RUNPERIOD 1 | 8.5612157151E-002 | 0.1779249862 | Pass | Pass | 2.1478527239E-002 | 5.1516629478E-002 | Pass | Pass |
6 | LAUNDRY_FLR_1 | RunPeriod: RUNPERIOD 1 | 0.2999592990 | 1.2482221258 | Pass | Pass | 4.5454171854E-002 | 0.1289291990 | Pass | Pass |
7 | CAFE_FLR_1 | RunPeriod: RUNPERIOD 1 | 0.1996914022 | 0.7204056851 | Pass | Pass | 0.3845591559 | 2.0688524130 | Pass | Pass |
8 | LOBBY_FLR_1 | RunPeriod: RUNPERIOD 1 | 0.1660235466 | 0.4862645123 | Pass | Pass | 0.1170423184 | 0.3321953831 | Pass | Pass |
9 | ROOM_1_FLR_3 | RunPeriod: RUNPERIOD 1 | 9.9667911246E-002 | 0.3481764414 | Pass | Pass | 0.2215953414 | 1.1151917666 | Pass | Pass |
10 | ROOM_2_FLR_3 | RunPeriod: RUNPERIOD 1 | 9.2718209711E-002 | 0.3542816394 | Pass | Pass | 7.0513188813E-002 | 0.2309828602 | Pass | Pass |
11 | ROOM_3_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 6.2788739090E-002 | 0.1011887907 | Pass | Pass | 0.1151319456 | 0.2765297839 | Pass | Pass |
12 | ROOM_4_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 9.4168905041E-002 | 0.2672762051 | Pass | Pass | 0.2099246552 | 0.8392853295 | Pass | Pass |
13 | ROOM_5_FLR_3 | RunPeriod: RUNPERIOD 1 | 9.2721869907E-002 | 0.3431155412 | Pass | Pass | 0.3469399242 | 2.5918591308 | Pass | Pass |
14 | ROOM_6_FLR_3 | RunPeriod: RUNPERIOD 1 | 9.2709329617E-002 | 0.3517831823 | Pass | Pass | 8.5158296389E-002 | 0.3188626061 | Pass | Pass |
15 | CORRIDOR_FLR_3 | RunPeriod: RUNPERIOD 1 | 5.9891775410E-002 | 0.1467697278 | Pass | Pass | 2.8281753329E-002 | 0.1370181999 | Pass | Pass |
16 | ROOM_1_FLR_6 | RunPeriod: RUNPERIOD 1 | 9.5285102525E-002 | 0.3630413269 | Pass | Pass | 0.1401876120 | 0.4284924177 | Pass | Pass |
17 | ROOM_2_FLR_6 | RunPeriod: RUNPERIOD 1 | 9.2754798255E-002 | 0.3633579168 | Pass | Pass | 6.2467352545E-002 | 0.2023426006 | Pass | Pass |
18 | ROOM_3_MULT9_FLR_6 | RunPeriod: RUNPERIOD 1 | 8.6010545352E-002 | 0.3155441058 | Pass | Pass | 0.4197334038 | 1.5188434516 | Pass | Pass |
19 | BANQUET_FLR_6 | RunPeriod: RUNPERIOD 1 | 0.1749080642 | 0.6471108513 | Pass | Pass | 0.4281761112 | 3.1845810601 | Pass | Pass |
20 | DINING_FLR_6 | RunPeriod: RUNPERIOD 1 | 0.1780042425 | 0.6668732698 | Pass | Pass | 0.1554902650 | 0.6658087662 | Pass | Pass |
21 | KITCHEN_FLR_6 | RunPeriod: RUNPERIOD 1 | 0.2804778584 | 1.0840270593 | Pass | Pass | 3.7288934930E-002 | 9.6764531320E-002 | Pass | Pass |
22 | CORRIDOR_FLR_6 | RunPeriod: RUNPERIOD 1 | 0.1058797574 | 0.2495701132 | Pass | Pass | 2.1096314928E-002 | 5.5004363942E-002 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:58:23
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 3809.41 | 171.00 | 1225.33 | 16094.11 | 5499.66 | 26799.51 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:58:23
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | -32.70 | 0.00 | -32.70 | Wetbulb [C] | 2.40 | 210.00 |
INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 30.10 | 12.40 | 21.10 | Wetbulb [C] | 4.70 | 200.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 12.00 | 13 | |||
Apr | 16.00 | 23 | |||
May | 0.00 | 0 | |||
Jun | 190.00 | 53 | |||
Jul | 136.00 | 41 | |||
Aug | 87.00 | 42 | |||
Sep | 0.00 | 0 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:58:23
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.340 | 0.354 | 211.13 | 211.13 | 0.00 | 90.00 | N |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.340 | 0.354 | 55.76 | 55.76 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.340 | 0.354 | 211.13 | 211.13 | 180.00 | 90.00 | S |
BASEMENT_WALL_WEST | BASEMENT_WALL_WEST_CFACTOR | 1.00 | 0.340 | 0.354 | 55.76 | 55.76 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.568 | 0.620 | 45.89 | 22.63 | 180.00 | 90.00 | S |
RETAIL_1_FLR_1_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.568 | 0.620 | 22.95 | 22.95 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_CEILING | NONRES_ROOF | 0.23 | 0.159 | 0.163 | 67.07 | 67.07 | 180.00 | 0.00 | |
RETAIL_2_FLR_1_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.568 | 0.620 | 26.57 | 24.62 | 270.00 | 90.00 | W |
MECH_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.568 | 0.620 | 62.80 | 62.80 | 0.00 | 90.00 | N |
STORAGE_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.568 | 0.620 | 36.23 | 28.80 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.568 | 0.620 | 18.12 | 18.12 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.568 | 0.620 | 67.63 | 65.68 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.568 | 0.620 | 22.95 | 21.00 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.568 | 0.620 | 129.23 | 63.73 | 180.00 | 90.00 | S |
CAFE_FLR_1_CEILING | NONRES_ROOF | 0.23 | 0.159 | 0.163 | 188.86 | 188.86 | 180.00 | 0.00 | |
LOBBY_FLR_1_WALL_1_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.568 | 0.620 | 213.77 | 209.87 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_2_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.568 | 0.620 | 12.08 | 12.08 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.568 | 0.620 | 167.88 | 82.79 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_1_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.568 | 0.620 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_CEILING_2 | NONRES_ROOF | 0.23 | 0.159 | 0.163 | 245.35 | 245.35 | 180.00 | 0.00 | |
ROOM_1_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.785 | 0.890 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_1_FLR_3_WALL_WEST | RES_EXT_WALL_MID | 0.30 | 0.785 | 0.890 | 104.06 | 69.72 | 270.00 | 90.00 | W |
ROOM_2_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.785 | 0.890 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_2_FLR_3_WALL_WEST | RES_EXT_WALL_MID | 0.30 | 0.785 | 0.890 | 104.05 | 69.71 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.785 | 0.890 | 847.14 | 567.58 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.785 | 0.890 | 847.37 | 567.71 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_EAST | RES_EXT_WALL_MID | 0.30 | 0.785 | 0.890 | 104.06 | 69.72 | 90.00 | 90.00 | E |
ROOM_5_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.785 | 0.890 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.785 | 0.890 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_6_FLR_3_WALL_EAST | RES_EXT_WALL_MID | 0.30 | 0.785 | 0.890 | 104.05 | 69.71 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_1_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.785 | 0.890 | 70.60 | 47.31 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_2_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.785 | 0.890 | 26.01 | 17.42 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.785 | 0.890 | 26.02 | 17.43 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_2_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.785 | 0.890 | 70.60 | 47.31 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_SOUTH | RES_EXT_WALL_TOP | 0.30 | 0.834 | 0.953 | 13.94 | 9.34 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_WEST | RES_EXT_WALL_TOP | 0.30 | 0.834 | 0.953 | 26.01 | 17.43 | 270.00 | 90.00 | W |
ROOM_1_FLR_6_CEILING | RES_ROOF | 0.23 | 0.159 | 0.163 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_2_FLR_6_WALL_NORTH | RES_EXT_WALL_TOP | 0.30 | 0.834 | 0.953 | 13.94 | 9.34 | 0.00 | 90.00 | N |
ROOM_2_FLR_6_WALL_WEST | RES_EXT_WALL_TOP | 0.30 | 0.834 | 0.953 | 26.01 | 17.43 | 270.00 | 90.00 | W |
ROOM_2_FLR_6_CEILING | RES_ROOF | 0.23 | 0.159 | 0.163 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | RES_EXT_WALL_TOP | 0.30 | 0.834 | 0.953 | 183.96 | 123.26 | 180.00 | 90.00 | S |
ROOM_3_MULT9_FLR_6_CEILING | RES_ROOF | 0.23 | 0.159 | 0.163 | 220.77 | 220.77 | 180.00 | 0.00 | |
BANQUET_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.834 | 0.953 | 97.55 | 65.36 | 0.00 | 90.00 | N |
BANQUET_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.159 | 0.163 | 331.66 | 331.66 | 180.00 | 0.00 | |
DINING_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.834 | 0.953 | 97.55 | 65.36 | 0.00 | 90.00 | N |
DINING_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.159 | 0.163 | 331.66 | 331.66 | 180.00 | 0.00 | |
KITCHEN_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.834 | 0.953 | 21.37 | 16.77 | 0.00 | 90.00 | N |
KITCHEN_FLR_6_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.834 | 0.953 | 52.03 | 34.86 | 90.00 | 90.00 | E |
KITCHEN_FLR_6_WALL_1_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.834 | 0.953 | 13.94 | 9.34 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.159 | 0.163 | 103.30 | 103.30 | 270.00 | 0.00 | |
CORRIDOR_FLR_6_WALL_1_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.834 | 0.953 | 17.65 | 11.83 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.834 | 0.953 | 15.79 | 10.58 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.834 | 0.953 | 52.03 | 34.86 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_CEILING_1 | NONRES_ROOF | 0.23 | 0.159 | 0.163 | 244.71 | 244.71 | 90.00 | 0.00 | |
CORRIDOR_FLR_6_CEILING_2 | NONRES_ROOF | 0.23 | 0.159 | 0.163 | 167.42 | 167.42 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_FLOOR | BASEMENT_FLOOR | 0.30 | 1.441 | 2.705 | 1978.83 | 1978.83 | 0.00 | 180.00 | |
BASEMENT_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.181 | 0.190 | 67.07 | 67.07 | 180.00 | 0.00 | |
BASEMENT_CEILING_2 | NONRES_FLOOR_CEILING | 0.30 | 0.181 | 0.190 | 77.67 | 77.67 | 180.00 | 0.00 | |
BASEMENT_CEILING_3 | NONRES_FLOOR_CEILING | 0.30 | 0.181 | 0.190 | 164.24 | 164.24 | 180.00 | 0.00 | |
BASEMENT_CEILING_4 | NONRES_FLOOR_CEILING | 0.30 | 0.181 | 0.190 | 94.76 | 94.76 | 180.00 | 0.00 | |
BASEMENT_CEILING_5 | NONRES_FLOOR_CEILING | 0.30 | 0.181 | 0.190 | 78.04 | 78.04 | 180.00 | 0.00 | |
BASEMENT_CEILING_6 | NONRES_FLOOR_CEILING | 0.30 | 0.181 | 0.190 | 188.86 | 188.86 | 180.00 | 0.00 | |
BASEMENT_CEILING_7 | NONRES_FLOOR_CEILING | 0.30 | 0.181 | 0.190 | 1088.56 | 1088.56 | 180.00 | 0.00 | |
BASEMENT_CEILING_8 | NONRES_FLOOR_CEILING | 0.30 | 0.181 | 0.190 | 219.63 | 219.63 | 90.00 | 0.00 | |
RETAIL_1_FLR_1_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 0.00 | 90.00 | N |
RETAIL_1_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 90.00 | 90.00 | E |
RETAIL_1_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.181 | 0.190 | 67.07 | 67.07 | 0.00 | 180.00 | |
RETAIL_2_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 180.00 | 90.00 | S |
RETAIL_2_FLR_1_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 0.00 | 90.00 | N |
RETAIL_2_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.57 | 26.57 | 90.00 | 90.00 | E |
RETAIL_2_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.181 | 0.190 | 77.67 | 77.67 | 0.00 | 180.00 | |
RETAIL_2_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.183 | 0.190 | 77.67 | 77.67 | 180.00 | 0.00 | |
MECH_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
MECH_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 62.80 | 62.80 | 180.00 | 90.00 | S |
MECH_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
MECH_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.181 | 0.190 | 164.24 | 164.24 | 0.00 | 180.00 | |
MECH_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.183 | 0.190 | 164.24 | 164.24 | 180.00 | 0.00 | |
STORAGE_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
STORAGE_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 36.23 | 36.23 | 180.00 | 90.00 | S |
STORAGE_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
STORAGE_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.181 | 0.190 | 94.76 | 94.76 | 0.00 | 180.00 | |
STORAGE_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.183 | 0.190 | 94.76 | 94.76 | 180.00 | 0.00 | |
LAUNDRY_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 18.12 | 18.12 | 180.00 | 90.00 | S |
LAUNDRY_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 67.63 | 67.63 | 270.00 | 90.00 | W |
LAUNDRY_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.181 | 0.190 | 78.04 | 78.04 | 0.00 | 180.00 | |
LAUNDRY_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.183 | 0.190 | 78.04 | 78.04 | 180.00 | 0.00 | |
CAFE_FLR_1_WALL_1_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.11 | 111.11 | 0.00 | 90.00 | N |
CAFE_FLR_1_WALL_2_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 18.12 | 18.12 | 0.00 | 90.00 | N |
CAFE_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 270.00 | 90.00 | W |
CAFE_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.181 | 0.190 | 188.86 | 188.86 | 0.00 | 180.00 | |
LOBBY_FLR_1_WALL_2_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_3_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.11 | 111.11 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.57 | 26.57 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_4_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 62.80 | 62.80 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_4_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 36.23 | 36.23 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
LOBBY_FLR_1_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 90.00 | 90.00 | E |
LOBBY_FLR_1_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 67.63 | 67.63 | 90.00 | 90.00 | E |
LOBBY_FLR_1_FLOOR_1 | NONRES_FLOOR | 0.30 | 0.181 | 0.190 | 1088.56 | 1088.56 | 180.00 | 180.00 | |
LOBBY_FLR_1_FLOOR_2 | NONRES_FLOOR | 0.30 | 0.181 | 0.190 | 219.63 | 219.63 | 90.00 | 180.00 | |
LOBBY_FLR_1_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.183 | 0.190 | 1062.83 | 1062.83 | 270.00 | 0.00 | |
ROOM_1_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 0.00 | 90.00 | N |
ROOM_1_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 90.00 | 90.00 | E |
ROOM_1_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 156.09 | 156.09 | 0.00 | 180.00 | |
ROOM_1_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.183 | 0.190 | 156.09 | 156.09 | 180.00 | 0.00 | |
ROOM_2_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 90.00 | 90.00 | E |
ROOM_2_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 180.00 | 90.00 | S |
ROOM_2_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 156.07 | 156.07 | 0.00 | 180.00 | |
ROOM_2_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.183 | 0.190 | 156.07 | 156.07 | 180.00 | 0.00 | |
ROOM_3_MULT19_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.14 | 847.14 | 0.00 | 90.00 | N |
ROOM_3_MULT19_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 90.00 | 90.00 | E |
ROOM_3_MULT19_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 1863.81 | 1863.81 | 0.00 | 180.00 | |
ROOM_3_MULT19_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.183 | 0.190 | 1863.81 | 1863.81 | 180.00 | 0.00 | |
ROOM_4_MULT19_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 90.00 | 90.00 | E |
ROOM_4_MULT19_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.37 | 847.37 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 270.00 | 90.00 | W |
ROOM_4_MULT19_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 1864.32 | 1864.32 | 0.00 | 180.00 | |
ROOM_4_MULT19_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.183 | 0.190 | 1864.32 | 1864.32 | 180.00 | 0.00 | |
ROOM_5_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 270.00 | 90.00 | W |
ROOM_5_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 156.09 | 156.09 | 0.00 | 180.00 | |
ROOM_5_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.183 | 0.190 | 156.09 | 156.09 | 180.00 | 0.00 | |
ROOM_6_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 270.00 | 90.00 | W |
ROOM_6_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 156.07 | 156.07 | 0.00 | 180.00 | |
ROOM_6_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.183 | 0.190 | 156.07 | 156.07 | 180.00 | 0.00 | |
CORRIDOR_FLR_3_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.28 | 847.28 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_4_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_3_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.27 | 847.27 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_4_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_FLOOR_1 | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 297.29 | 297.29 | 180.00 | 180.00 | |
CORRIDOR_FLR_3_FLOOR_2 | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 963.06 | 963.06 | 270.00 | 180.00 | |
CORRIDOR_FLR_3_FLOOR_3 | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 297.26 | 297.26 | 90.00 | 180.00 | |
CORRIDOR_FLR_3_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.183 | 0.190 | 297.29 | 297.29 | 90.00 | 0.00 | |
CORRIDOR_FLR_3_CEILING_2 | NONRES_FLOOR_CEILING | 0.30 | 0.183 | 0.190 | 963.06 | 963.06 | 90.00 | 0.00 | |
CORRIDOR_FLR_3_CEILING_3 | NONRES_FLOOR_CEILING | 0.30 | 0.183 | 0.190 | 297.26 | 297.26 | 90.00 | 0.00 | |
ROOM_1_FLR_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 13.94 | 13.94 | 0.00 | 90.00 | N |
ROOM_1_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.01 | 26.01 | 90.00 | 90.00 | E |
ROOM_1_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 39.02 | 39.02 | 0.00 | 180.00 | |
ROOM_2_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.01 | 26.01 | 90.00 | 90.00 | E |
ROOM_2_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 13.94 | 13.94 | 180.00 | 90.00 | S |
ROOM_2_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 39.02 | 39.02 | 0.00 | 180.00 | |
ROOM_3_MULT9_FLR_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 183.96 | 183.96 | 0.00 | 90.00 | N |
ROOM_3_MULT9_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 100.35 | 100.35 | 90.00 | 90.00 | E |
ROOM_3_MULT9_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 100.35 | 100.35 | 270.00 | 90.00 | W |
ROOM_3_MULT9_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 220.77 | 220.77 | 0.00 | 180.00 | |
BANQUET_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
BANQUET_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 180.00 | 90.00 | S |
BANQUET_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
BANQUET_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 331.66 | 331.66 | 0.00 | 180.00 | |
DINING_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
DINING_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 180.00 | 90.00 | S |
DINING_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
DINING_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 331.66 | 331.66 | 0.00 | 180.00 | |
KITCHEN_FLR_6_WALL_2_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 7.43 | 7.43 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 20.44 | 20.44 | 270.00 | 90.00 | W |
KITCHEN_FLR_6_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
KITCHEN_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 103.30 | 103.30 | 180.00 | 180.00 | |
CORRIDOR_FLR_6_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_4_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 104.98 | 104.98 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_1_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 183.95 | 183.95 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 11.15 | 11.15 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 40.88 | 40.88 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 20.44 | 20.44 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.179 | 0.190 | 412.12 | 412.12 | 180.00 | 180.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3957.66 | 0.00 | 90.00 | N | ||
RETAIL_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 134.14 | 0.00 | 90.00 | N | ||
RETAIL_2_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 155.34 | 0.00 | 90.00 | N | ||
MECH_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 328.49 | 0.00 | 90.00 | N | ||
STORAGE_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 189.52 | 0.00 | 90.00 | N | ||
LAUNDRY_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 156.08 | 0.00 | 90.00 | N | ||
CAFE_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 377.72 | 0.00 | 90.00 | N | ||
LOBBY_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 2616.37 | 0.00 | 90.00 | N | ||
ROOM_1_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.18 | 0.00 | 90.00 | N | ||
ROOM_2_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.14 | 0.00 | 90.00 | N | ||
ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3727.63 | 0.00 | 90.00 | N | ||
ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3728.64 | 0.00 | 90.00 | N | ||
ROOM_5_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.18 | 0.00 | 90.00 | N | ||
ROOM_6_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.14 | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3115.24 | 0.00 | 90.00 | N | ||
ROOM_1_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 78.04 | 0.00 | 90.00 | N | ||
ROOM_2_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 78.03 | 0.00 | 90.00 | N | ||
ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 441.55 | 0.00 | 90.00 | N | ||
BANQUET_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 663.31 | 0.00 | 90.00 | N | ||
DINING_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 663.31 | 0.00 | 90.00 | N | ||
KITCHEN_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 206.61 | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 824.25 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.2964_SHGC_0.45 | 23.26 | 0.00 | 0.00 | 23.26 | 23.26 | 1.683 | 0.451 | 0.452 | No | RETAIL_1_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
CAFE_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.2964_SHGC_0.45 | 65.50 | 0.00 | 0.00 | 65.50 | 65.50 | 1.683 | 0.451 | 0.452 | No | CAFE_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
LOBBY_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.2964_SHGC_0.45 | 85.08 | 0.00 | 0.00 | 85.08 | 85.08 | 1.683 | 0.451 | 0.452 | No | LOBBY_FLR_1_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.2964_SHGC_0.45 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 1.683 | 0.451 | 0.452 | No | ROOM_1_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.2964_SHGC_0.45 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 1.683 | 0.451 | 0.452 | No | ROOM_1_FLR_3_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_2_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.2964_SHGC_0.45 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 1.683 | 0.451 | 0.452 | No | ROOM_2_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_2_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.2964_SHGC_0.45 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 1.683 | 0.451 | 0.452 | No | ROOM_2_FLR_3_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.2964_SHGC_0.45 | 3.68 | 0.00 | 0.00 | 3.68 | 279.56 | 1.683 | 0.451 | 0.452 | No | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.2964_SHGC_0.45 | 3.68 | 0.00 | 0.00 | 3.68 | 279.65 | 1.683 | 0.451 | 0.452 | No | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_5_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.2964_SHGC_0.45 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 1.683 | 0.451 | 0.452 | No | ROOM_5_FLR_3_WALL_EAST | 90.00 | 90.00 | E | |||||||
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.2964_SHGC_0.45 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 1.683 | 0.451 | 0.452 | No | ROOM_5_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_6_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.2964_SHGC_0.45 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 1.683 | 0.451 | 0.452 | No | ROOM_6_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_6_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.2964_SHGC_0.45 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 1.683 | 0.451 | 0.452 | No | ROOM_6_FLR_3_WALL_EAST | 90.00 | 90.00 | E | |||||||
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.2964_SHGC_0.45 | 5.82 | 0.00 | 0.00 | 5.82 | 23.30 | 1.683 | 0.451 | 0.452 | No | CORRIDOR_FLR_3_WALL_1_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.2964_SHGC_0.45 | 2.15 | 0.00 | 0.00 | 2.15 | 8.59 | 1.683 | 0.451 | 0.452 | No | CORRIDOR_FLR_3_WALL_2_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.2964_SHGC_0.45 | 2.15 | 0.00 | 0.00 | 2.15 | 8.58 | 1.683 | 0.451 | 0.452 | No | CORRIDOR_FLR_3_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.2964_SHGC_0.45 | 5.82 | 0.00 | 0.00 | 5.82 | 23.30 | 1.683 | 0.451 | 0.452 | No | CORRIDOR_FLR_3_WALL_2_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.2964_SHGC_0.45 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 1.683 | 0.451 | 0.452 | No | ROOM_1_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.2964_SHGC_0.45 | 8.58 | 0.00 | 0.00 | 8.58 | 8.58 | 1.683 | 0.451 | 0.452 | No | ROOM_1_FLR_6_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_2_FLR_6_WALL_NORTH_WINDOW | RESWINDOW_U_0.2964_SHGC_0.45 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 1.683 | 0.451 | 0.452 | No | ROOM_2_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_2_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.2964_SHGC_0.45 | 8.58 | 0.00 | 0.00 | 8.58 | 8.58 | 1.683 | 0.451 | 0.452 | No | ROOM_2_FLR_6_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.2964_SHGC_0.45 | 6.74 | 0.00 | 0.00 | 6.74 | 60.70 | 1.683 | 0.451 | 0.452 | No | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
BANQUET_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.2964_SHGC_0.45 | 32.19 | 0.00 | 0.00 | 32.19 | 32.19 | 1.683 | 0.451 | 0.452 | No | BANQUET_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
DINING_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.2964_SHGC_0.45 | 32.19 | 0.00 | 0.00 | 32.19 | 32.19 | 1.683 | 0.451 | 0.452 | No | DINING_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
KITCHEN_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.2964_SHGC_0.45 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 1.683 | 0.451 | 0.452 | No | KITCHEN_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
KITCHEN_FLR_6_WALL_EAST_WINDOW | NONRESWINDOW_U_0.2964_SHGC_0.45 | 17.17 | 0.00 | 0.00 | 17.17 | 17.17 | 1.683 | 0.451 | 0.452 | No | KITCHEN_FLR_6_WALL_EAST | 90.00 | 90.00 | E | |||||||
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.2964_SHGC_0.45 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 1.683 | 0.451 | 0.452 | No | KITCHEN_FLR_6_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.2964_SHGC_0.45 | 5.82 | 0.00 | 0.00 | 5.82 | 5.82 | 1.683 | 0.451 | 0.452 | No | CORRIDOR_FLR_6_WALL_1_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.2964_SHGC_0.45 | 5.21 | 0.00 | 0.00 | 5.21 | 5.21 | 1.683 | 0.451 | 0.452 | No | CORRIDOR_FLR_6_WALL_2_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.2964_SHGC_0.45 | 17.17 | 0.00 | 0.00 | 17.17 | 17.17 | 1.683 | 0.451 | 0.452 | No | CORRIDOR_FLR_6_WALL_2_SOUTH | 180.00 | 90.00 | S | |||||||
Total or Average | 1213.79 | 1.683 | 0.451 | 0.452 | |||||||||||||||||
North Total or Average | 432.95 | 1.683 | 0.451 | 0.452 | |||||||||||||||||
Non-North Total or Average | 780.84 | 1.683 | 0.451 | 0.452 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
RETAIL_2_FLR_1_WALL_WEST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | RETAIL_2_FLR_1_WALL_WEST |
STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | OVERHEAD DOOR_CON | 1.016 | 1.198 | 7.43 | STORAGE_FLR_1_WALL_NORTH |
LAUNDRY_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | LAUNDRY_FLR_1_WALL_EAST |
CAFE_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | CAFE_FLR_1_WALL_EAST |
LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:58:23
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CAFE_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LOBBY_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
BANQUET_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:58:23
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 8.7495 | 1978.83 | 17313.73 | LightsWired | LTG_SCH_BASEMENT | 50.91 | 168.00 | 50.86 | 0.0000 | Y | 165.29 |
RETAIL_1_FLR_1_LIGHTS | RETAIL_1_FLR_1 | RETAIL_1_FLR_1 | GENERAL | 13.0124 | 67.07 | 872.76 | LightsWired | LTG_SCH_RETAIL | 51.36 | 168.00 | 51.30 | 0.0000 | Y | 8.40 |
RETAIL_2_FLR_1_LIGHTS | RETAIL_2_FLR_1 | RETAIL_2_FLR_1 | GENERAL | 13.0124 | 77.67 | 1010.66 | LightsWired | LTG_SCH_RETAIL | 51.36 | 168.00 | 51.30 | 0.0000 | Y | 9.73 |
MECH_FLR_1_LIGHTS | MECH_FLR_1 | MECH_FLR_1 | GENERAL | 10.0642 | 164.24 | 1652.98 | LightsWired | LTG_SCH_MECHANIC | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 18.19 |
STORAGE_FLR_1_LIGHTS | STORAGE_FLR_1 | STORAGE_FLR_1 | GENERAL | 7.3195 | 94.76 | 693.59 | LightsWired | LTG_SCH_STORAGE | 25.68 | 168.00 | 25.65 | 0.0000 | Y | 3.34 |
LAUNDRY_FLR_1_LIGHTS | LAUNDRY_FLR_1 | LAUNDRY_FLR_1 | GENERAL | 5.4896 | 78.04 | 428.40 | LightsWired | LTG_SCH_LAUNDRY | 51.36 | 168.00 | 51.30 | 0.0000 | Y | 4.13 |
CAFE_FLR_1_LIGHTS | CAFE_FLR_1 | CAFE_FLR_1 | GENERAL | 12.8090 | 188.86 | 2419.14 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 26.62 |
LOBBY_FLR_1_LIGHTS | LOBBY_FLR_1 | LOBBY_FLR_1 | GENERAL | 10.0642 | 1308.19 | 13165.91 | LightsWired | LTG_SCH_LOBBY | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 144.89 |
ROOM_1_FLR_3_LIGHTS | ROOM_1_FLR_3 | ROOM_1_FLR_3 | GENERAL | 10.0642 | 156.09 | 1570.91 | LightsWired | LTG_SCH_GUESTROOM | 69.03 | 168.00 | 69.21 | 0.0000 | Y | 20.41 |
ROOM_2_FLR_3_LIGHTS | ROOM_2_FLR_3 | ROOM_2_FLR_3 | GENERAL | 10.0642 | 156.07 | 1570.72 | LightsWired | LTG_SCH_GUESTROOM | 69.03 | 168.00 | 69.21 | 0.0000 | Y | 20.41 |
ROOM_3_MULT19_FLR_3_LIGHTS | ROOM_3_MULT19_FLR_3 | ROOM_3_MULT19_FLR_3 | GENERAL | 10.0642 | 1863.81 | 18757.86 | LightsWired | LTG_SCH_GUESTROOM | 69.03 | 168.00 | 69.21 | 0.0000 | Y | 243.70 |
ROOM_4_MULT19_FLR_3_LIGHTS | ROOM_4_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | GENERAL | 10.0642 | 1864.32 | 18762.99 | LightsWired | LTG_SCH_GUESTROOM | 69.03 | 168.00 | 69.21 | 0.0000 | Y | 243.77 |
ROOM_5_FLR_3_LIGHTS | ROOM_5_FLR_3 | ROOM_5_FLR_3 | GENERAL | 10.0642 | 156.09 | 1570.91 | LightsWired | LTG_SCH_GUESTROOM | 69.03 | 168.00 | 69.21 | 0.0000 | Y | 20.41 |
ROOM_6_FLR_3_LIGHTS | ROOM_6_FLR_3 | ROOM_6_FLR_3 | GENERAL | 10.0642 | 156.07 | 1570.72 | LightsWired | LTG_SCH_GUESTROOM | 69.03 | 168.00 | 69.21 | 0.0000 | Y | 20.41 |
CORRIDOR_FLR_3_LIGHTS | CORRIDOR_FLR_3 | CORRIDOR_FLR_3 | GENERAL | 3.6597 | 1557.62 | 5700.46 | LightsWired | LTG_SCH_CORRIDOR | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 62.73 |
ROOM_1_FLR_6_LIGHTS | ROOM_1_FLR_6 | ROOM_1_FLR_6 | GENERAL | 10.0642 | 39.02 | 392.73 | LightsWired | LTG_SCH_GUESTROOM | 69.03 | 168.00 | 69.21 | 0.0000 | Y | 5.10 |
ROOM_2_FLR_6_LIGHTS | ROOM_2_FLR_6 | ROOM_2_FLR_6 | GENERAL | 10.0642 | 39.02 | 392.68 | LightsWired | LTG_SCH_GUESTROOM | 69.03 | 168.00 | 69.21 | 0.0000 | Y | 5.10 |
ROOM_3_MULT9_FLR_6_LIGHTS | ROOM_3_MULT9_FLR_6 | ROOM_3_MULT9_FLR_6 | GENERAL | 10.0642 | 220.77 | 2221.93 | LightsWired | LTG_SCH_GUESTROOM | 69.03 | 168.00 | 69.21 | 0.0000 | Y | 28.87 |
BANQUET_FLR_6_LIGHTS | BANQUET_FLR_6 | BANQUET_FLR_6 | GENERAL | 12.8090 | 331.66 | 4248.21 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 46.75 |
DINING_FLR_6_LIGHTS | DINING_FLR_6 | DINING_FLR_6 | GENERAL | 12.8090 | 331.66 | 4248.21 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 46.75 |
KITCHEN_FLR_6_LIGHTS | KITCHEN_FLR_6 | KITCHEN_FLR_6 | GENERAL | 10.9792 | 103.30 | 1134.20 | LightsWired | LTG_SCH_KITCHEN | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 12.48 |
CORRIDOR_FLR_6_LIGHTS | CORRIDOR_FLR_6 | CORRIDOR_FLR_6 | GENERAL | 3.6597 | 412.12 | 1508.26 | LightsWired | LTG_SCH_CORRIDOR | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 16.60 |
Interior Lighting Total | 8.9207 | 11345.29 | 101207.97 | 559.10 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR FACADE LIGHTING | 16690.39 | AstronomicalClock | - | 83.52 | 83.52 | 261.66 | |
Exterior Lighting Total | 16690.39 | 261.66 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:58:23
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
HEATSYS1 BOILER | Boiler:HotWater | 809825.45 | 0.81 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:EIR | 1154247.76 | 2.80 | 1154450.65 | 2.80 | 3.72 | 12.68 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 16072.24 | 23917.62 | 18537.40 | 5380.22 | 0.78 | - | 2807.65 | 28.48 |
ROOM_2_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 15326.53 | 22796.08 | 17661.88 | 5134.20 | 0.77 | - | 2675.60 | 27.14 |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 102585.92 | 153621.15 | 119582.96 | 34038.19 | 0.78 | - | 18066.68 | 183.24 |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 81873.69 | 119989.66 | 92056.54 | 27933.12 | 0.77 | - | 14028.93 | 142.29 |
ROOM_5_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 14679.47 | 21819.79 | 16898.13 | 4921.66 | 0.77 | - | 2560.55 | 25.97 |
ROOM_6_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 13979.67 | 20766.01 | 16074.89 | 4691.12 | 0.77 | - | 2436.44 | 24.71 |
ROOM_1_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 4206.08 | 6262.47 | 4855.48 | 1406.99 | 0.78 | - | 735.25 | 7.46 |
ROOM_2_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 3995.78 | 5946.04 | 4608.38 | 1337.66 | 0.78 | - | 697.99 | 7.08 |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 20802.81 | 30857.07 | 23863.08 | 6993.99 | 0.77 | - | 3618.96 | 36.71 |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | 810549.86 | 699196.44 | 447362.92 | 251833.52 | 0.64 | - | 85578.34 | 867.98 |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | 69550.09 | 60010.76 | 38734.94 | 21275.82 | 0.65 | - | 6954.16 | 70.53 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
BASEMENT VAV BOX REHEAT COIL | Coil:Heating:Water | 14586.41 | 14661.47 | - |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 6391.11 | 6421.05 | - |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 2589.87 | 2602.44 | - |
MECH_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 3767.59 | 3784.90 | - |
STORAGE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 2223.51 | 2233.24 | - |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 20460.30 | 20565.37 | - |
CAFE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 19458.84 | 19553.30 | - |
LOBBY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 50492.89 | 50744.00 | - |
ROOM_1_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 9500.40 | 10233.30 | - |
ROOM_2_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 9507.96 | 10241.44 | - |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 53726.54 | 57871.67 | - |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 53886.01 | 58043.42 | - |
ROOM_5_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 9516.55 | 10250.69 | - |
ROOM_6_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 9524.10 | 10258.82 | - |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 20871.05 | 20966.89 | - |
ROOM_1_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 2900.10 | 3123.74 | - |
ROOM_2_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 2900.31 | 3123.97 | - |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 13843.61 | 14911.17 | - |
BANQUET_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 20629.97 | 20733.04 | - |
DINING_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 21383.05 | 21489.99 | - |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 15951.90 | 16033.42 | - |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 13257.70 | 13316.28 | - |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | 397205.34 | 227854.93 | - |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | 35250.36 | 20221.20 | - |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
LAUNDRY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 0.16 | 125.00 | 0.24 | 184.35 | 781.25 | 1.00 | 1.15 | General | ||
LOBBY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | General | |||
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.16 | 270.90 | 1.36 | 2298.52 | 1693.12 | 1.00 | 0.47 | General | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 |
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.16 | 270.90 | 1.29 | 2188.82 | 1693.12 | 1.00 | 0.47 | General | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 |
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.16 | 270.90 | 8.81 | 14922.19 | 1693.12 | 1.00 | 0.39 | General | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 |
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.16 | 270.90 | 6.64 | 11243.31 | 1693.12 | 1.00 | 0.40 | General | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 |
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.16 | 270.90 | 1.24 | 2092.83 | 1693.12 | 1.00 | 0.48 | General | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 |
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.16 | 270.90 | 1.18 | 1989.57 | 1693.12 | 1.00 | 0.48 | General | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 |
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.16 | 270.90 | 0.36 | 602.37 | 1693.12 | 1.00 | 0.67 | General | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 |
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.16 | 270.90 | 0.34 | 571.39 | 1693.12 | 1.00 | 0.68 | General | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 |
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.16 | 270.90 | 1.74 | 2949.26 | 1693.12 | 1.00 | 0.45 | General | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 |
BANQUET_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | General | |||
DINING_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | General | |||
KITCHEN_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 0.16 | 125.00 | 1.89 | 1474.84 | 781.25 | 1.00 | 0.62 | General | ||
VAV WITH REHEAT FAN | Fan:VariableVolume | 0.62 | 1389.42 | 23.11 | 51791.23 | 2240.64 | 1.00 | 1.11 | General | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 |
FLR_3_DOAS FAN | Fan:ConstantVolume | 0.58 | 622.50 | 2.05 | 2194.93 | 1070.05 | 1.00 | 1.30 | General | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 133527.72 | 0.041205 | 8490.73 | 206062.94 | 0.90 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.007085 | 2133.60 | 301156.09 | 0.90 | General |
COOLSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 92445.74 | 0.041205 | 5878.42 | 142664.32 | 0.90 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000375 | 47.91 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWH BOOSTER E WATER HEATER | WaterHeater:Mixed | 0.02 | 8000.00 | 1.00 | 1.24 | 1.15 |
SWH LAUNDRY G WATER HEATER | WaterHeater:Mixed | 1.14 | 163316.00 | 0.80 | 0.58 | 0.51 |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 2.27 | 175842.60 | 0.80 | 0.26 | 0.03 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:58:23
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 33161.17 | 33161.17 | 16.76 | 2.514 | 2.514 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00923 | 25.26 | 0.01272 | 0.854 | 0.00 |
RETAIL_1_FLR_1 | 6087.26 | 6087.26 | 90.76 | 0.462 | 0.462 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 24.00 | 24.00 | 0.00898 | 29.79 | 0.01273 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 3242.60 | 3242.60 | 41.75 | 0.246 | 0.246 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 24.00 | 24.00 | 0.00942 | 29.98 | 0.01273 | 0.092 | 0.00 |
MECH_FLR_1 | 3163.22 | 3163.22 | 19.26 | 0.240 | 0.240 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 24.00 | 24.00 | 0.00883 | 29.98 | 0.01273 | 0.000 | 0.00 |
STORAGE_FLR_1 | 1568.28 | 1568.28 | 16.55 | 0.119 | 0.119 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 24.00 | 24.00 | 0.00895 | 30.10 | 0.01273 | 0.058 | 0.00 |
LAUNDRY_FLR_1 | 44816.67 | 44816.67 | 574.28 | 3.398 | 3.398 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 24.00 | 24.00 | 0.00856 | 30.10 | 0.01273 | 0.000 | 0.00 |
CAFE_FLR_1 | 24327.28 | 24327.28 | 128.81 | 1.846 | 1.846 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 24.00 | 23.99 | 0.00985 | 29.79 | 0.01273 | 0.676 | 0.00 |
LOBBY_FLR_1 | 69380.17 | 69380.17 | 53.04 | 5.263 | 5.263 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 24.00 | 23.99 | 0.00991 | 29.89 | 0.01273 | 1.894 | 0.00 |
ROOM_1_FLR_3 | 13286.86 | 13286.86 | 340.50 | 1.358 | 1.358 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 21.11 | 21.11 | 0.00862 | 28.16 | 0.01272 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 12652.71 | 12652.71 | 324.28 | 1.293 | 1.293 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 21.11 | 21.11 | 0.00863 | 27.95 | 0.01272 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 86265.44 | 86265.44 | 3517.62 | 8.813 | 8.813 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 21.11 | 21.11 | 0.00855 | 29.89 | 0.01273 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 64992.64 | 64992.64 | 2649.46 | 6.641 | 6.641 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | 21.11 | 21.11 | 0.00879 | 24.81 | 0.01272 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 12097.83 | 12097.83 | 310.03 | 1.236 | 1.236 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 21.11 | 21.11 | 0.00863 | 25.39 | 0.01272 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 11500.89 | 11500.89 | 294.76 | 1.175 | 1.175 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | 21.11 | 21.11 | 0.00864 | 23.63 | 0.01271 | 0.062 | 0.00 |
CORRIDOR_FLR_3 | 17480.08 | 17480.08 | 44.89 | 1.325 | 1.325 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 24.00 | 24.00 | 0.00966 | 30.10 | 0.01273 | 0.475 | 0.00 |
ROOM_1_FLR_6 | 3482.04 | 3482.04 | 89.23 | 0.356 | 0.356 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 21.11 | 21.11 | 0.00862 | 28.36 | 0.01272 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 3302.98 | 3302.98 | 84.65 | 0.337 | 0.337 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 21.11 | 21.11 | 0.00862 | 27.95 | 0.01272 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 17048.29 | 17048.29 | 694.98 | 1.742 | 1.742 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 21.11 | 21.11 | 0.00866 | 29.89 | 0.01273 | 0.099 | 0.00 |
BANQUET_FLR_6 | 29970.44 | 29970.44 | 90.37 | 2.275 | 2.275 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 24.00 | 23.98 | 0.01040 | 30.10 | 0.01273 | 1.188 | 0.00 |
DINING_FLR_6 | 31484.47 | 31484.47 | 94.93 | 2.390 | 2.390 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 24.00 | 23.98 | 0.01031 | 30.10 | 0.01273 | 1.188 | 0.00 |
KITCHEN_FLR_6 | 32003.65 | 32003.65 | 309.80 | 2.433 | 2.433 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 | 24.00 | 23.97 | 0.00996 | 25.04 | 0.01272 | 0.367 | 0.00 |
CORRIDOR_FLR_6 | 9758.50 | 9758.50 | 23.68 | 0.740 | 0.740 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 24.00 | 24.00 | 0.00907 | 30.10 | 0.01273 | 0.126 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 1941.25 | 1941.25 | 0.98 | 0.087 | 0.854 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00799 | -32.70 | 0.00018 | 0.854 | 0.00 |
RETAIL_1_FLR_1 | 4072.53 | 4072.53 | 60.72 | 0.182 | 0.182 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.00 | 21.00 | 0.00752 | -32.70 | 0.00018 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 1354.64 | 1354.64 | 17.44 | 0.061 | 0.092 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.00 | 21.00 | 0.00745 | -32.70 | 0.00018 | 0.092 | 0.00 |
MECH_FLR_1 | 2563.17 | 2563.17 | 15.61 | 0.115 | 0.115 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.00 | 21.00 | 0.00732 | -32.70 | 0.00018 | 0.000 | 0.00 |
STORAGE_FLR_1 | 1626.30 | 1626.30 | 17.16 | 0.073 | 0.073 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.00 | 21.00 | 0.00738 | -32.70 | 0.00018 | 0.058 | 0.00 |
LAUNDRY_FLR_1 | 3399.00 | 3399.00 | 43.55 | 0.152 | 0.152 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.00 | 21.00 | 0.00730 | -32.70 | 0.00018 | 0.000 | 0.00 |
CAFE_FLR_1 | 10183.86 | 10183.86 | 53.92 | 0.455 | 0.676 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.00 | 21.00 | 0.00757 | -32.70 | 0.00018 | 0.676 | 0.00 |
LOBBY_FLR_1 | 24055.32 | 24055.32 | 18.39 | 1.076 | 1.894 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00749 | -32.70 | 0.00018 | 1.894 | 0.00 |
ROOM_1_FLR_3 | 9500.55 | 9500.55 | 243.47 | 0.427 | 0.427 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.11 | 21.11 | 0.00752 | -32.70 | 0.00018 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 9508.11 | 9508.11 | 243.69 | 0.428 | 0.428 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.11 | 21.11 | 0.00752 | -32.70 | 0.00018 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 53726.97 | 53726.97 | 2190.81 | 2.417 | 2.417 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.11 | 21.11 | 0.00755 | -32.70 | 0.00018 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 53886.44 | 53886.44 | 2196.71 | 2.424 | 2.424 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.11 | 21.11 | 0.00755 | -32.70 | 0.00018 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 9516.69 | 9516.69 | 243.88 | 0.428 | 0.428 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.11 | 21.11 | 0.00752 | -32.70 | 0.00018 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 9524.25 | 9524.25 | 244.10 | 0.428 | 0.428 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.11 | 21.11 | 0.00752 | -32.70 | 0.00018 | 0.062 | 0.00 |
CORRIDOR_FLR_3 | 14210.71 | 14210.71 | 36.49 | 0.636 | 0.636 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.00 | 21.00 | 0.00761 | -32.70 | 0.00018 | 0.475 | 0.00 |
ROOM_1_FLR_6 | 2900.14 | 2900.14 | 74.32 | 0.130 | 0.130 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.11 | 21.11 | 0.00761 | -32.70 | 0.00018 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 2900.35 | 2900.35 | 74.33 | 0.130 | 0.130 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.11 | 21.11 | 0.00761 | -32.70 | 0.00018 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 13843.77 | 13843.77 | 564.35 | 0.623 | 0.623 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.11 | 21.11 | 0.00762 | -32.70 | 0.00018 | 0.099 | 0.00 |
BANQUET_FLR_6 | 9195.49 | 9195.49 | 27.73 | 0.411 | 1.188 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.00 | 21.00 | 0.00769 | -32.70 | 0.00018 | 1.188 | 0.00 |
DINING_FLR_6 | 9371.00 | 9371.00 | 28.26 | 0.419 | 1.188 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.00 | 21.00 | 0.00770 | -32.70 | 0.00018 | 1.188 | 0.00 |
KITCHEN_FLR_6 | 3747.10 | 3747.10 | 36.27 | 0.168 | 0.367 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | 21.00 | 21.00 | 0.00706 | -32.70 | 0.00018 | 0.367 | 0.00 |
CORRIDOR_FLR_6 | 9538.77 | 9538.77 | 23.15 | 0.427 | 0.427 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.00 | 21.00 | 0.00774 | -32.70 | 0.00018 | 0.126 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV WITH REHEAT | 23.11 | 23.11 | 7.84 | 7.84 | 23.1145 | 23.1113 | 23.1145 | 0.9999 | 0.3000 |
FLR_3_DOAS | 21.35 | 2.05 | 7.44 | 2.05 | 2.0513 | 2.0513 | 2.0513 | 1.0000 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
BASEMENT VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | 14586.414 | 14586.414 | 2.499231 | 0.00012761 | 306.615 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 14586.41 | 14586.41 | 2.499231 | 16.70 | 12.79 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00799334 | 49.5188 | 1941.25 | 0.00 | 14668.16 | 14668.16 |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | 6391.106 | 6391.106 | 0.458832 | 0.00005591 | 146.739 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 6391.11 | 6391.11 | 0.458832 | 16.70 | 12.79 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00751883 | 46.6193 | 4072.53 | 0.00 | 6425.40 | 6425.40 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | 2589.866 | 2589.866 | 0.244413 | 0.00002266 | 57.272 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 2589.87 | 2589.87 | 0.244413 | 16.70 | 12.79 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00744711 | 46.1768 | 1354.64 | 0.00 | 2603.96 | 2603.96 |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | 3767.594 | 3767.594 | 0.238379 | 0.00003296 | 88.423 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 3767.59 | 3767.59 | 0.238379 | 16.70 | 12.79 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00732135 | 45.4063 | 2563.17 | 0.00 | 3787.68 | 3787.68 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | 2223.507 | 2223.507 | 0.118186 | 0.00001945 | 54.119 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 2223.51 | 2223.51 | 0.118186 | 16.70 | 12.79 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00737801 | 45.7535 | 1626.30 | 0.00 | 2235.07 | 2235.07 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 20460.297 | 20460.297 | 3.377748 | 0.00017900 | 431.073 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 20460.30 | 20460.30 | 3.377748 | 16.70 | 12.79 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00730297 | 45.2968 | 3399.00 | 0.00 | 20574.87 | 20574.87 |
CAFE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | 19458.836 | 19458.836 | 1.835150 | 0.00017023 | 430.341 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 19458.84 | 19458.84 | 1.835150 | 16.70 | 12.79 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00757160 | 46.9416 | 10183.86 | 0.00 | 19564.74 | 19564.74 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 50492.887 | 50492.887 | 5.231018 | 0.00044173 | 1105.230 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 50492.89 | 50492.89 | 5.231018 | 16.70 | 12.79 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00748771 | 46.4260 | 24055.32 | 0.00 | 50772.37 | 50772.37 |
ROOM_1_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 16072.241 | -999.000 | 1.357562 | 0.00057405 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | unknown | 7/21 17:10:00 | 16072.24 | 15660.43 | 1.357562 | 22.55 | 15.55 | 0.00862235 | 12.80 | 11.72 | 0.00850000 | 28.16 | 0.01272245 | 20.56 | 0.0000 | 21.11 | 0.00862235 | 53.0021 | 13286.86 | 0.00 | 16701.50 | 15942.43 |
ROOM_1_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 9500.404 | 9500.404 | 0.427398 | 0.00008311 | 271.487 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 9500.40 | 9500.40 | 0.427398 | 21.11 | 14.04 | 0.00752360 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.11 | 0.00752360 | 46.3322 | 9500.55 | 0.00 | 10241.44 | 10241.44 |
ROOM_2_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 15326.532 | -999.000 | 1.292770 | 0.00054742 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | unknown | 7/21 17:20:00 | 15326.53 | 14916.21 | 1.292770 | 22.55 | 15.55 | 0.00862799 | 12.80 | 11.72 | 0.00850000 | 27.95 | 0.01272209 | 20.50 | 0.0000 | 21.11 | 0.00862799 | 53.0363 | 12652.71 | 0.00 | 15926.18 | 15184.34 |
ROOM_2_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 9507.959 | 9507.959 | 0.427737 | 0.00008318 | 271.703 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 9507.96 | 9507.96 | 0.427737 | 21.11 | 14.04 | 0.00752399 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.11 | 0.00752399 | 46.3346 | 9508.11 | 0.00 | 10249.58 | 10249.58 |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 102585.923 | -999.000 | 8.813400 | 0.00366406 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | unknown | 7/21 13:40:00 | 102585.92 | 101406.29 | 8.813400 | 22.55 | 15.49 | 0.00855413 | 12.80 | 11.72 | 0.00850000 | 29.89 | 0.01272550 | 21.07 | 0.0000 | 21.11 | 0.00855413 | 52.5865 | 86265.44 | 0.00 | 106635.97 | 103270.95 |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 53726.544 | 53726.544 | 2.417149 | 0.00047002 | 1535.301 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 53726.54 | 53726.54 | 2.417149 | 21.11 | 14.07 | 0.00755172 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.11 | 0.00755172 | 46.5003 | 53726.97 | 0.00 | 57918.25 | 57918.25 |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 81873.687 | -999.000 | 6.640568 | 0.00292428 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | unknown | 7/21 19:20:00 | 81873.69 | 77075.36 | 6.640568 | 22.55 | 15.69 | 0.00878964 | 12.80 | 11.72 | 0.00850000 | 24.81 | 0.01271660 | 19.55 | 0.0000 | 21.11 | 0.00878964 | 54.0163 | 64992.64 | 0.00 | 85015.41 | 78395.81 |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 53886.012 | 53886.012 | 2.424323 | 0.00047142 | 1539.857 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 53886.01 | 53886.01 | 2.424323 | 21.11 | 14.07 | 0.00755286 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.11 | 0.00755286 | 46.5072 | 53886.44 | 0.00 | 58090.16 | 58090.16 |
ROOM_5_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 14679.473 | -999.000 | 1.236077 | 0.00052431 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | unknown | 7/21 10:00:00 | 14679.47 | 14265.81 | 1.236077 | 22.55 | 15.56 | 0.00863491 | 12.80 | 11.72 | 0.00850000 | 25.39 | 0.01271761 | 19.73 | 0.0000 | 21.11 | 0.00863491 | 53.0783 | 12097.83 | 0.00 | 15253.32 | 14521.72 |
ROOM_5_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 9516.546 | 9516.546 | 0.428124 | 0.00008325 | 271.948 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 9516.55 | 9516.55 | 0.428124 | 21.11 | 14.04 | 0.00752435 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.11 | 0.00752435 | 46.3368 | 9516.69 | 0.00 | 10258.84 | 10258.84 |
ROOM_6_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 13979.672 | -999.000 | 1.175087 | 0.00049931 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | unknown | 7/21 09:10:00 | 13979.67 | 13565.56 | 1.175087 | 22.55 | 15.56 | 0.00864203 | 12.80 | 11.72 | 0.00850000 | 23.63 | 0.01271456 | 19.19 | 0.0000 | 21.11 | 0.00864203 | 53.1215 | 11500.89 | 0.00 | 14525.69 | 13808.38 |
ROOM_6_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 9524.100 | 9524.100 | 0.428464 | 0.00008332 | 272.164 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 9524.10 | 9524.10 | 0.428464 | 21.11 | 14.04 | 0.00752474 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.11 | 0.00752474 | 46.3392 | 9524.25 | 0.00 | 10266.98 | 10266.98 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | 20871.047 | 20871.047 | 1.317387 | 0.00018259 | 490.050 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 20871.05 | 20871.05 | 1.317387 | 16.70 | 12.79 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00760818 | 47.1624 | 14210.71 | 0.00 | 20982.27 | 20982.27 |
ROOM_1_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 4206.077 | -999.000 | 0.355771 | 0.00015023 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | unknown | 7/21 17:00:00 | 4206.08 | 4103.18 | 0.355771 | 22.55 | 15.54 | 0.00861667 | 12.80 | 11.72 | 0.00850000 | 28.36 | 0.01272282 | 20.62 | 0.0000 | 21.11 | 0.00861667 | 52.9676 | 3482.04 | 0.00 | 4370.87 | 4177.20 |
ROOM_1_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 2900.099 | 2900.099 | 0.130468 | 0.00002537 | 82.870 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 2900.10 | 2900.10 | 0.130468 | 21.11 | 14.12 | 0.00760540 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.11 | 0.00760540 | 46.8297 | 2900.14 | 0.00 | 3126.31 | 3126.31 |
ROOM_2_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 3995.777 | -999.000 | 0.337477 | 0.00014272 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | unknown | 7/21 17:20:00 | 3995.78 | 3893.09 | 0.337477 | 22.55 | 15.55 | 0.00862272 | 12.80 | 11.72 | 0.00850000 | 27.95 | 0.01272209 | 20.50 | 0.0000 | 21.11 | 0.00862272 | 53.0044 | 3302.98 | 0.00 | 4152.21 | 3963.18 |
ROOM_2_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 2900.312 | 2900.312 | 0.130477 | 0.00002537 | 82.876 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 2900.31 | 2900.31 | 0.130477 | 21.11 | 14.12 | 0.00760545 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.11 | 0.00760545 | 46.8301 | 2900.35 | 0.00 | 3126.54 | 3126.54 |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 20802.808 | -999.000 | 1.741905 | 0.00074301 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | unknown | 7/21 13:40:00 | 20802.81 | 20120.76 | 1.741905 | 22.55 | 15.58 | 0.00865771 | 12.80 | 11.72 | 0.00850000 | 29.89 | 0.01272550 | 21.07 | 0.0000 | 21.11 | 0.00865771 | 53.2169 | 17048.29 | 0.00 | 21613.79 | 20479.22 |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 13843.606 | 13843.606 | 0.622801 | 0.00012111 | 395.579 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 13843.61 | 13843.61 | 0.622801 | 21.11 | 14.13 | 0.00761867 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.11 | 0.00761867 | 46.9094 | 13843.77 | 0.00 | 14923.52 | 14923.52 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 20629.966 | 20629.966 | 2.261552 | 0.00018048 | 448.976 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 20629.97 | 20629.97 | 2.261552 | 16.70 | 12.79 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00769083 | 47.6697 | 9195.49 | 0.00 | 20744.33 | 20744.33 |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 21383.045 | 21383.045 | 2.375762 | 0.00018707 | 464.755 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21383.05 | 21383.05 | 2.375762 | 16.70 | 12.79 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00769640 | 47.7038 | 9371.00 | 0.00 | 21501.62 | 21501.62 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 15951.901 | 15951.901 | 2.418242 | 0.00013955 | 337.978 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | 15951.90 | 15951.90 | 2.418242 | 16.70 | 12.79 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00705774 | 43.7970 | 3747.10 | 0.00 | 16041.06 | 16041.06 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | 13257.704 | 13257.704 | 0.735445 | 0.00011598 | 319.567 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 13257.70 | 13257.70 | 0.735445 | 16.70 | 12.79 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00773725 | 47.9532 | 9538.77 | 0.00 | 13326.91 | 13326.91 |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV WITH REHEAT | 810549.863 | -999.000 | 23.114494 | 0.02895096 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 810549.86 | 521927.80 | 23.114494 | 30.10 | 21.13 | 0.01272586 | 10.91 | 10.91 | 0.00850000 | 30.10 | 0.01272586 | 21.13 | 100.0000 | 23.99 | 0.00965630 | 49.7445 | 304598.44 | 0.00 | 828511.55 | 519916.55 |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV WITH REHEAT | 397205.342 | 397205.342 | 6.934348 | 0.00347493 | 5528.208 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 397205.34 | 397205.34 | 6.934348 | -32.70 | -32.70 | 0.00018338 | 16.70 | 12.79 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 333.3333 | 21.00 | 0.00757352 | 46.9416 | 93965.24 | 0.00 | 275188.47 | 275188.47 |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | FLR_3_DOAS | 69550.086 | -999.000 | 2.051317 | 0.00248417 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 69550.09 | 44784.57 | 2.051317 | 30.10 | 21.13 | 0.01272586 | 11.90 | 11.35 | 0.00850000 | 30.10 | 0.01272586 | 21.13 | 99.9965 | 21.11 | 0.00865785 | 53.2163 | 208915.85 | 0.00 | 71097.05 | 44995.87 |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | FLR_3_DOAS | 35250.356 | 35250.356 | 0.615395 | 0.00030839 | 490.606 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 35250.36 | 35250.36 | 0.615395 | -32.70 | -32.70 | 0.00018338 | 16.70 | 12.79 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 333.3216 | 21.11 | 0.00755280 | 46.5069 | 165307.27 | 0.00 | 24421.86 | 24421.86 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:58:23
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
BASEMENT VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | BASEMENT | N/A | N/A | N/A | Yes | Yes | Yes | No | 14586.414 | 14586.414 | 2.499231 | 0.00012761 | 306.615 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 7.08398362 | 54.44 | 82.22 | 27.78 | 826123.51 | 1.7656 | 1.801180 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 14586.41 | 14586.41 | 1.0000 | 2.88392451 | 2.499231 | 16.70 | 12.79 | 0.00800000 | 37036.7 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.12759530 | 60.00 | 32.22 | 27.78 | 0.000 | 14586.41 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.00 | 0.00799334 | 21.00 | 0.00799334 | 49.5188 | 1941.25 | 0.00 | 14668.16 | 14668.16 | 2.88392451 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 21.59 | 15.07 | 0.00800000 | 42020.9 | |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | RETAIL_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6391.106 | 6391.106 | 0.458832 | 0.00005591 | 146.739 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 7.08398362 | 54.44 | 82.22 | 27.78 | 826123.51 | 0.7736 | 0.789196 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 6391.11 | 6391.11 | 1.0000 | 0.52945742 | 0.458832 | 16.70 | 12.79 | 0.00800000 | 37036.7 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.05590648 | 60.00 | 32.22 | 27.78 | 0.000 | 6391.11 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.00 | 0.00751883 | 21.00 | 0.00751883 | 46.6193 | 4072.53 | 0.00 | 6425.40 | 6425.40 | 0.52945742 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 28.50 | 17.53 | 0.00800000 | 49070.6 | |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | RETAIL_2_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2589.866 | 2589.866 | 0.244413 | 0.00002266 | 57.272 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 7.08398362 | 54.44 | 82.22 | 27.78 | 826123.51 | 0.3135 | 0.319805 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 2589.87 | 2589.87 | 1.0000 | 0.28203449 | 0.244413 | 16.70 | 12.79 | 0.00800000 | 37036.7 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.02265497 | 60.00 | 32.22 | 27.78 | 0.000 | 2589.87 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.00 | 0.00744711 | 21.00 | 0.00744711 | 46.1768 | 1354.64 | 0.00 | 2603.96 | 2603.96 | 0.28203449 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 25.65 | 16.55 | 0.00800000 | 46167.5 | |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | MECH_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3767.594 | 3767.594 | 0.238379 | 0.00003296 | 88.423 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 7.08398362 | 54.44 | 82.22 | 27.78 | 826123.51 | 0.4561 | 0.465235 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 3767.59 | 3767.59 | 1.0000 | 0.27507110 | 0.238379 | 16.70 | 12.79 | 0.00800000 | 37036.7 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.03295719 | 60.00 | 32.22 | 27.78 | 0.000 | 3767.59 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.00 | 0.00732135 | 21.00 | 0.00732135 | 45.4063 | 2563.17 | 0.00 | 3787.68 | 3787.68 | 0.27507110 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 30.10 | 18.07 | 0.00800000 | 50704.5 | |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | STORAGE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2223.507 | 2223.507 | 0.118186 | 0.00001945 | 54.119 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 7.08398362 | 54.44 | 82.22 | 27.78 | 826123.51 | 0.2691 | 0.274566 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 2223.51 | 2223.51 | 1.0000 | 0.13637734 | 0.118186 | 16.70 | 12.79 | 0.00800000 | 37036.7 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.01945023 | 60.00 | 32.22 | 27.78 | 0.000 | 2223.51 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.00 | 0.00737801 | 21.00 | 0.00737801 | 45.7535 | 1626.30 | 0.00 | 2235.07 | 2235.07 | 0.13637734 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 32.67 | 18.92 | 0.00800000 | 53323.6 | |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LAUNDRY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 20460.297 | 20460.297 | 3.377748 | 0.00017900 | 431.073 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 7.08398362 | 54.44 | 82.22 | 27.78 | 826123.51 | 2.4767 | 2.526507 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 20460.30 | 20460.30 | 1.0000 | 3.89766750 | 3.377748 | 16.70 | 12.79 | 0.00800000 | 37036.7 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.17897735 | 60.00 | 32.22 | 27.78 | 0.000 | 20460.30 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.00 | 0.00730297 | 21.00 | 0.00730297 | 45.2968 | 3399.00 | 0.00 | 20574.87 | 20574.87 | 3.89766750 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 21.78 | 15.14 | 0.00800000 | 42213.5 | |
CAFE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | CAFE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 19458.836 | 19458.836 | 1.835150 | 0.00017023 | 430.341 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 7.08398362 | 54.44 | 82.22 | 27.78 | 826123.51 | 2.3554 | 2.402843 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 19458.84 | 19458.84 | 1.0000 | 2.11762534 | 1.835150 | 16.70 | 12.79 | 0.00800000 | 37036.7 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.17021702 | 60.00 | 32.22 | 27.78 | 0.000 | 19458.84 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.00 | 0.00757160 | 21.00 | 0.00757160 | 46.9416 | 10183.86 | 0.00 | 19564.74 | 19564.74 | 2.11762534 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 25.66 | 16.55 | 0.00800000 | 46173.7 | |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LOBBY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 50492.887 | 50492.887 | 5.231018 | 0.00044173 | 1105.230 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 7.08398362 | 54.44 | 82.22 | 27.78 | 826123.51 | 6.1120 | 6.235033 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 50492.89 | 50492.89 | 1.0000 | 6.03620225 | 5.231018 | 16.70 | 12.79 | 0.00800000 | 37036.7 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.44168874 | 60.00 | 32.22 | 27.78 | 0.000 | 50492.89 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.00 | 0.00748771 | 21.00 | 0.00748771 | 46.4260 | 24055.32 | 0.00 | 50772.37 | 50772.37 | 6.03620225 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 24.85 | 16.26 | 0.00800000 | 45346.0 | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 16072.241 | -999.000 | 1.357562 | 0.00057405 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8685 | 1004.8586 | 1.1539 | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.357562 | 1.56652479 | 4197.9300 | 999.8980 | 41.20032413 | 13.37 | 6.70 | 6.67 | 1153617.03 | 1.3932 | 1.393178 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | unknown | unknown | unknown | 7/21 17:10:00 | Sensible | 16072.24 | 15660.43 | 1.0000 | 1.56652479 | 1.357562 | 22.55 | 15.55 | 0.00862235 | 44582.0 | 12.80 | 11.72 | 0.00850000 | 34322.2 | 0.57399392 | 6.70 | 13.37 | 6.67 | 0.000 | 16072.24 | 28.16 | 0.01272245 | 20.56 | 0.00000000 | 0.0000 | 21.11 | 0.00862235 | 21.11 | 0.00862235 | 53.0021 | 13286.86 | 0.00 | 16701.50 | 15942.43 | 1.56652479 | 22.55 | 15.98 | 0.00862235 | 44582.0 | 12.58 | 11.94 | 0.00843039 | 33920.5 | |
ROOM_1_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9500.404 | 9500.404 | 0.427398 | 0.00008311 | 271.487 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.357562 | 1.56652479 | 4197.9300 | 999.8980 | 7.08398362 | 54.44 | 82.22 | 27.78 | 826123.51 | 1.1500 | 1.173142 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 9500.40 | 9500.40 | 1.0000 | 0.49318472 | 0.427398 | 21.11 | 14.04 | 0.00752360 | 40322.5 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.08310520 | 60.00 | 32.22 | 27.78 | 0.000 | 9500.40 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.11 | 0.00752360 | 21.11 | 0.00752360 | 46.3322 | 9500.55 | 0.00 | 10241.44 | 10241.44 | 0.49318472 | 16.60 | 12.69 | 0.00752360 | 35728.6 | 36.98 | 19.91 | 0.00752360 | 56494.5 | |
ROOM_2_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 15326.532 | -999.000 | 1.292770 | 0.00054742 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8790 | 1004.8586 | 1.1539 | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.292770 | 1.49175961 | 4197.9300 | 999.8980 | 41.20032413 | 13.37 | 6.70 | 6.67 | 1153617.03 | 1.3286 | 1.328538 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | unknown | unknown | unknown | 7/21 17:20:00 | Sensible | 15326.53 | 14916.21 | 1.0000 | 1.49175961 | 1.292770 | 22.55 | 15.55 | 0.00862799 | 44596.3 | 12.80 | 11.72 | 0.00850000 | 34322.2 | 0.54736216 | 6.70 | 13.37 | 6.67 | 0.000 | 15326.53 | 27.95 | 0.01272209 | 20.50 | 0.00000000 | 0.0000 | 21.11 | 0.00862799 | 21.11 | 0.00862799 | 53.0363 | 12652.71 | 0.00 | 15926.18 | 15184.34 | 1.49175961 | 22.55 | 15.98 | 0.00862799 | 44596.3 | 12.58 | 11.94 | 0.00843099 | 33920.2 | |
ROOM_2_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9507.959 | 9507.959 | 0.427737 | 0.00008318 | 271.703 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.292770 | 1.49175961 | 4197.9300 | 999.8980 | 7.08398362 | 54.44 | 82.22 | 27.78 | 826123.51 | 1.1509 | 1.174075 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 9507.96 | 9507.96 | 1.0000 | 0.49357691 | 0.427737 | 21.11 | 14.04 | 0.00752399 | 40323.4 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.08317129 | 60.00 | 32.22 | 27.78 | 0.000 | 9507.96 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.11 | 0.00752399 | 21.11 | 0.00752399 | 46.3346 | 9508.11 | 0.00 | 10249.58 | 10249.58 | 0.49357691 | 16.60 | 12.69 | 0.00752399 | 35729.6 | 36.98 | 19.91 | 0.00752399 | 56495.5 | |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 102585.923 | -999.000 | 8.813400 | 0.00366406 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7417 | 1004.8586 | 1.1539 | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 8.813400 | 10.17000115 | 4197.9300 | 999.8980 | 41.20032413 | 13.37 | 6.70 | 6.67 | 1153617.03 | 8.8925 | 8.892380 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | unknown | unknown | unknown | 7/21 13:40:00 | Sensible | 102585.92 | 101406.29 | 1.0000 | 10.17000115 | 8.813400 | 22.55 | 15.49 | 0.00855413 | 44409.3 | 12.80 | 11.72 | 0.00850000 | 34322.2 | 3.66368928 | 6.70 | 13.37 | 6.67 | 0.000 | 102585.92 | 29.89 | 0.01272550 | 21.07 | 0.00000000 | 0.0000 | 21.11 | 0.00855413 | 21.11 | 0.00855413 | 52.5865 | 86265.44 | 0.00 | 106635.97 | 103270.95 | 10.17000115 | 22.55 | 15.92 | 0.00855413 | 44409.3 | 12.60 | 11.94 | 0.00842305 | 33924.0 | |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 53726.544 | 53726.544 | 2.417149 | 0.00047002 | 1535.301 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 8.813400 | 10.17000115 | 4197.9300 | 999.8980 | 7.08398362 | 54.44 | 82.22 | 27.78 | 826123.51 | 6.5035 | 6.634336 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 53726.54 | 53726.54 | 1.0000 | 2.78920825 | 2.417149 | 21.11 | 14.07 | 0.00755172 | 40395.0 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.46997530 | 60.00 | 32.22 | 27.78 | 0.000 | 53726.54 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.11 | 0.00755172 | 21.11 | 0.00755172 | 46.5003 | 53726.97 | 0.00 | 57918.25 | 57918.25 | 2.78920825 | 16.60 | 12.71 | 0.00755172 | 35799.8 | 36.98 | 19.93 | 0.00755172 | 56564.9 | |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 81873.687 | -999.000 | 6.640568 | 0.00292428 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.1795 | 1004.8586 | 1.1539 | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 6.640568 | 7.66271602 | 4197.9300 | 999.8980 | 41.20032413 | 13.37 | 6.70 | 6.67 | 1153617.03 | 7.0971 | 7.096996 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | unknown | unknown | unknown | 7/21 19:20:00 | Sensible | 81873.69 | 77075.36 | 1.0000 | 7.66271602 | 6.640568 | 22.55 | 15.69 | 0.00878964 | 45006.9 | 12.80 | 11.72 | 0.00850000 | 34322.2 | 2.92398546 | 6.70 | 13.37 | 6.67 | 0.000 | 81873.69 | 24.81 | 0.01271660 | 19.55 | 0.00000000 | 0.0000 | 21.11 | 0.00878964 | 21.11 | 0.00878964 | 54.0163 | 64992.64 | 0.00 | 85015.41 | 78395.81 | 7.66271602 | 22.55 | 16.12 | 0.00878964 | 45006.9 | 12.53 | 11.93 | 0.00844740 | 33912.2 | |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 53886.012 | 53886.012 | 2.424323 | 0.00047142 | 1539.857 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 6.640568 | 7.66271602 | 4197.9300 | 999.8980 | 7.08398362 | 54.44 | 82.22 | 27.78 | 826123.51 | 6.5228 | 6.654028 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 53886.01 | 53886.01 | 1.0000 | 2.79748702 | 2.424323 | 21.11 | 14.07 | 0.00755286 | 40397.9 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.47137025 | 60.00 | 32.22 | 27.78 | 0.000 | 53886.01 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.11 | 0.00755286 | 21.11 | 0.00755286 | 46.5072 | 53886.44 | 0.00 | 58090.16 | 58090.16 | 2.79748702 | 16.60 | 12.71 | 0.00755286 | 35802.7 | 36.98 | 19.94 | 0.00755286 | 56567.8 | |
ROOM_5_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 14679.473 | -999.000 | 1.236077 | 0.00052431 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8919 | 1004.8586 | 1.1539 | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.236077 | 1.42634008 | 4197.9300 | 999.8980 | 41.20032413 | 13.37 | 6.70 | 6.67 | 1153617.03 | 1.2725 | 1.272450 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | unknown | unknown | unknown | 7/21 10:00:00 | Sensible | 14679.47 | 14265.81 | 1.0000 | 1.42634008 | 1.236077 | 22.55 | 15.56 | 0.00863491 | 44613.9 | 12.80 | 11.72 | 0.00850000 | 34322.2 | 0.52425350 | 6.70 | 13.37 | 6.67 | 0.000 | 14679.47 | 25.39 | 0.01271761 | 19.73 | 0.00000000 | 0.0000 | 21.11 | 0.00863491 | 21.11 | 0.00863491 | 53.0783 | 12097.83 | 0.00 | 15253.32 | 14521.72 | 1.42634008 | 22.55 | 15.99 | 0.00863491 | 44613.9 | 12.57 | 11.94 | 0.00843172 | 33919.9 | |
ROOM_5_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9516.546 | 9516.546 | 0.428124 | 0.00008325 | 271.948 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.236077 | 1.42634008 | 4197.9300 | 999.8980 | 7.08398362 | 54.44 | 82.22 | 27.78 | 826123.51 | 1.1520 | 1.175136 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 9516.55 | 9516.55 | 1.0000 | 0.49402270 | 0.428124 | 21.11 | 14.04 | 0.00752435 | 40324.4 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.08324641 | 60.00 | 32.22 | 27.78 | 0.000 | 9516.55 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.11 | 0.00752435 | 21.11 | 0.00752435 | 46.3368 | 9516.69 | 0.00 | 10258.84 | 10258.84 | 0.49402270 | 16.60 | 12.69 | 0.00752435 | 35730.5 | 36.98 | 19.91 | 0.00752435 | 56496.4 | |
ROOM_6_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 13979.672 | -999.000 | 1.175087 | 0.00049931 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9051 | 1004.8586 | 1.1539 | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.175087 | 1.35596239 | 4197.9300 | 999.8980 | 41.20032413 | 13.37 | 6.70 | 6.67 | 1153617.03 | 1.2118 | 1.211790 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | unknown | unknown | unknown | 7/21 09:10:00 | Sensible | 13979.67 | 13565.56 | 1.0000 | 1.35596239 | 1.175087 | 22.55 | 15.56 | 0.00864203 | 44632.0 | 12.80 | 11.72 | 0.00850000 | 34322.2 | 0.49926125 | 6.70 | 13.37 | 6.67 | 0.000 | 13979.67 | 23.63 | 0.01271456 | 19.19 | 0.00000000 | 0.0000 | 21.11 | 0.00864203 | 21.11 | 0.00864203 | 53.1215 | 11500.89 | 0.00 | 14525.69 | 13808.38 | 1.35596239 | 22.55 | 15.99 | 0.00864203 | 44632.0 | 12.57 | 11.94 | 0.00843246 | 33919.5 | |
ROOM_6_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9524.100 | 9524.100 | 0.428464 | 0.00008332 | 272.164 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.175087 | 1.35596239 | 4197.9300 | 999.8980 | 7.08398362 | 54.44 | 82.22 | 27.78 | 826123.51 | 1.1529 | 1.176068 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 9524.10 | 9524.10 | 1.0000 | 0.49441481 | 0.428464 | 21.11 | 14.04 | 0.00752474 | 40325.4 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.08331248 | 60.00 | 32.22 | 27.78 | 0.000 | 9524.10 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.11 | 0.00752474 | 21.11 | 0.00752474 | 46.3392 | 9524.25 | 0.00 | 10266.98 | 10266.98 | 0.49441481 | 16.60 | 12.69 | 0.00752474 | 35731.5 | 36.98 | 19.91 | 0.00752474 | 56497.4 | |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | CORRIDOR_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 20871.047 | 20871.047 | 1.317387 | 0.00018259 | 490.050 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 7.08398362 | 54.44 | 82.22 | 27.78 | 826123.51 | 2.5264 | 2.577228 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 20871.05 | 20871.05 | 1.0000 | 1.52016569 | 1.317387 | 16.70 | 12.79 | 0.00800000 | 37036.7 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.18257039 | 60.00 | 32.22 | 27.78 | 0.000 | 20871.05 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.00 | 0.00760818 | 21.00 | 0.00760818 | 47.1624 | 14210.71 | 0.00 | 20982.27 | 20982.27 | 1.52016569 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 30.14 | 18.08 | 0.00800000 | 50737.4 | |
ROOM_1_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 4206.077 | -999.000 | 0.355771 | 0.00015023 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8580 | 1004.8586 | 1.1539 | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.355771 | 0.41053348 | 4197.9300 | 999.8980 | 41.20032413 | 13.37 | 6.70 | 6.67 | 1153617.03 | 0.3646 | 0.364592 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | unknown | unknown | unknown | 7/21 17:00:00 | Sensible | 4206.08 | 4103.18 | 1.0000 | 0.41053348 | 0.355771 | 22.55 | 15.54 | 0.00861667 | 44567.6 | 12.80 | 11.72 | 0.00850000 | 34322.2 | 0.15021321 | 6.70 | 13.37 | 6.67 | 0.000 | 4206.08 | 28.36 | 0.01272282 | 20.62 | 0.00000000 | 0.0000 | 21.11 | 0.00861667 | 21.11 | 0.00861667 | 52.9676 | 3482.04 | 0.00 | 4370.87 | 4177.20 | 0.41053348 | 22.55 | 15.97 | 0.00861667 | 44567.6 | 12.58 | 11.94 | 0.00842979 | 33920.8 | |
ROOM_1_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2900.099 | 2900.099 | 0.130468 | 0.00002537 | 82.870 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.355771 | 0.41053348 | 4197.9300 | 999.8980 | 7.08398362 | 54.44 | 82.22 | 27.78 | 826123.51 | 0.3510 | 0.358114 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 2900.10 | 2900.10 | 1.0000 | 0.15055020 | 0.130468 | 21.11 | 14.12 | 0.00760540 | 40530.3 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.02536874 | 60.00 | 32.22 | 27.78 | 0.000 | 2900.10 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.11 | 0.00760540 | 21.11 | 0.00760540 | 46.8297 | 2900.14 | 0.00 | 3126.31 | 3126.31 | 0.15055020 | 16.60 | 12.77 | 0.00760540 | 35935.7 | 36.98 | 19.97 | 0.00760540 | 56701.6 | |
ROOM_2_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3995.777 | -999.000 | 0.337477 | 0.00014272 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8692 | 1004.8586 | 1.1539 | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.337477 | 0.38942299 | 4197.9300 | 999.8980 | 41.20032413 | 13.37 | 6.70 | 6.67 | 1153617.03 | 0.3464 | 0.346363 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | unknown | unknown | unknown | 7/21 17:20:00 | Sensible | 3995.78 | 3893.09 | 1.0000 | 0.38942299 | 0.337477 | 22.55 | 15.55 | 0.00862272 | 44583.0 | 12.80 | 11.72 | 0.00850000 | 34322.2 | 0.14270266 | 6.70 | 13.37 | 6.67 | 0.000 | 3995.78 | 27.95 | 0.01272209 | 20.50 | 0.00000000 | 0.0000 | 21.11 | 0.00862272 | 21.11 | 0.00862272 | 53.0044 | 3302.98 | 0.00 | 4152.21 | 3963.18 | 0.38942299 | 22.55 | 15.98 | 0.00862272 | 44583.0 | 12.58 | 11.94 | 0.00843043 | 33920.5 | |
ROOM_2_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2900.312 | 2900.312 | 0.130477 | 0.00002537 | 82.876 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.337477 | 0.38942299 | 4197.9300 | 999.8980 | 7.08398362 | 54.44 | 82.22 | 27.78 | 826123.51 | 0.3511 | 0.358140 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 2900.31 | 2900.31 | 1.0000 | 0.15056123 | 0.130477 | 21.11 | 14.12 | 0.00760545 | 40530.4 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.02537060 | 60.00 | 32.22 | 27.78 | 0.000 | 2900.31 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.11 | 0.00760545 | 21.11 | 0.00760545 | 46.8301 | 2900.35 | 0.00 | 3126.54 | 3126.54 | 0.15056123 | 16.60 | 12.77 | 0.00760545 | 35935.8 | 36.98 | 19.98 | 0.00760545 | 56701.7 | |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 20802.808 | -999.000 | 1.741905 | 0.00074301 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9342 | 1004.8586 | 1.1539 | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.741905 | 2.01002767 | 4197.9300 | 999.8980 | 41.20032413 | 13.37 | 6.70 | 6.67 | 1153617.03 | 1.8033 | 1.803234 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | unknown | unknown | unknown | 7/21 13:40:00 | Sensible | 20802.81 | 20120.76 | 1.0000 | 2.01002767 | 1.741905 | 22.55 | 15.58 | 0.00865771 | 44671.7 | 12.80 | 11.72 | 0.00850000 | 34322.2 | 0.74293841 | 6.70 | 13.37 | 6.67 | 0.000 | 20802.81 | 29.89 | 0.01272550 | 21.07 | 0.00000000 | 0.0000 | 21.11 | 0.00865771 | 21.11 | 0.00865771 | 53.2169 | 17048.29 | 0.00 | 21613.79 | 20479.22 | 2.01002767 | 22.55 | 16.01 | 0.00865771 | 44671.7 | 12.57 | 11.94 | 0.00843410 | 33918.7 | |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 13843.606 | 13843.606 | 0.622801 | 0.00012111 | 395.579 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.741905 | 2.01002767 | 4197.9300 | 999.8980 | 7.08398362 | 54.44 | 82.22 | 27.78 | 826123.51 | 1.6757 | 1.709456 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 13843.61 | 13843.61 | 1.0000 | 0.71866504 | 0.622801 | 21.11 | 14.13 | 0.00761867 | 40564.4 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.12109755 | 60.00 | 32.22 | 27.78 | 0.000 | 13843.61 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.11 | 0.00761867 | 21.11 | 0.00761867 | 46.9094 | 13843.77 | 0.00 | 14923.52 | 14923.52 | 0.71866504 | 16.60 | 12.78 | 0.00761867 | 35969.3 | 36.98 | 19.98 | 0.00761867 | 56734.9 | |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | BANQUET_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 20629.966 | 20629.966 | 2.261552 | 0.00018048 | 448.976 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 7.08398362 | 54.44 | 82.22 | 27.78 | 826123.51 | 2.4972 | 2.547458 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 20629.97 | 20629.97 | 1.0000 | 2.60966162 | 2.261552 | 16.70 | 12.79 | 0.00800000 | 37036.7 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.18046153 | 60.00 | 32.22 | 27.78 | 0.000 | 20629.97 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.00 | 0.00769083 | 21.00 | 0.00769083 | 47.6697 | 9195.49 | 0.00 | 20744.33 | 20744.33 | 2.60966162 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 24.40 | 16.10 | 0.00800000 | 44883.8 | |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | DINING_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 21383.045 | 21383.045 | 2.375762 | 0.00018707 | 464.755 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 7.08398362 | 54.44 | 82.22 | 27.78 | 826123.51 | 2.5884 | 2.640451 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 21383.05 | 21383.05 | 1.0000 | 2.74145082 | 2.375762 | 16.70 | 12.79 | 0.00800000 | 37036.7 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.18704913 | 60.00 | 32.22 | 27.78 | 0.000 | 21383.05 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.00 | 0.00769640 | 21.00 | 0.00769640 | 47.7038 | 9371.00 | 0.00 | 21501.62 | 21501.62 | 2.74145082 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 24.29 | 16.06 | 0.00800000 | 44777.9 | |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | KITCHEN_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 15951.901 | 15951.901 | 2.418242 | 0.00013955 | 337.978 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 7.08398362 | 54.44 | 82.22 | 27.78 | 826123.51 | 1.9309 | 1.969795 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | Sensible | 15951.90 | 15951.90 | 1.0000 | 2.79046911 | 2.418242 | 16.70 | 12.79 | 0.00800000 | 37036.7 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.13953996 | 60.00 | 32.22 | 27.78 | 0.000 | 15951.90 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 20.75 | 0.00705774 | 21.00 | 0.00705774 | 43.7970 | 3747.10 | 0.00 | 16041.06 | 16041.06 | 2.79046911 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 22.24 | 15.31 | 0.00800000 | 42683.2 | |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | CORRIDOR_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 13257.704 | 13257.704 | 0.735445 | 0.00011598 | 319.567 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 7.08398362 | 54.44 | 82.22 | 27.78 | 826123.51 | 1.6048 | 1.637106 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 13257.70 | 13257.70 | 1.0000 | 0.84864864 | 0.735445 | 16.70 | 12.79 | 0.00800000 | 37036.7 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.11597235 | 60.00 | 32.22 | 27.78 | 0.000 | 13257.70 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.00 | 0.00773725 | 21.00 | 0.00773725 | 47.9532 | 9538.77 | 0.00 | 13326.91 | 13326.91 | 0.84864864 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 32.00 | 18.70 | 0.00800000 | 52638.4 | |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 810549.863 | -999.000 | 23.114494 | 0.02895096 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1028.4967 | 1004.8586 | 1.1539 | VAV WITH REHEAT FAN | Fan:VariableVolume | 23.114494 | 26.67238969 | 4197.9300 | 999.8980 | 41.20032413 | 13.37 | 6.70 | 6.67 | 1153617.03 | 70.2616 | 70.261607 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | Sensible | 810549.86 | 521927.80 | 1.0000 | 26.67238969 | 23.114494 | 30.10 | 21.13 | 0.01272586 | 62784.4 | 10.91 | 10.91 | 0.00850000 | 32395.3 | 28.94800976 | 6.70 | 13.37 | 6.67 | 51791.229 | 758758.63 | 30.10 | 0.01272586 | 21.13 | 23.11449000 | 100.0000 | 23.99 | 0.00965437 | 23.99 | 0.00965630 | 49.7445 | 304598.44 | 0.00 | 828511.55 | 519916.55 | 26.67238969 | 30.10 | 21.63 | 0.01272586 | 62784.4 | 11.15 | 11.04 | 0.00813769 | 31721.9 | |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 397205.342 | 397205.342 | 6.934348 | 0.00347493 | 5528.208 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | VAV WITH REHEAT FAN | Fan:VariableVolume | 23.114494 | 26.67238969 | 4197.9300 | 999.8980 | 7.08398362 | 54.44 | 82.22 | 27.78 | 826123.51 | 48.0806 | 49.048266 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 397205.34 | 397205.34 | 1.0000 | 8.00171691 | 6.934348 | -32.70 | -32.70 | 0.00018338 | -32410.8 | 16.70 | 12.79 | 0.00800000 | 37036.7 | 3.47457113 | 60.00 | 32.22 | 27.78 | 0.000 | 397205.34 | -32.70 | 0.00018338 | -32.70 | 23.11449000 | 333.3333 | 20.99 | 0.00759023 | 21.00 | 0.00757352 | 46.9416 | 93965.24 | 0.00 | 275188.47 | 275188.47 | 8.00171691 | 2.80 | -4.17 | 0.00018338 | 3273.1 | 37.01 | 13.61 | 0.00018338 | 37664.3 | |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 69550.086 | -999.000 | 2.051317 | 0.00248417 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1028.4967 | 1004.8586 | 1.1539 | FLR_3_DOAS FAN | Fan:ConstantVolume | 2.051245 | 2.36698273 | 4197.9300 | 999.8980 | 41.20032413 | 13.37 | 6.70 | 6.67 | 1153617.03 | 6.0289 | 6.028871 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | Sensible | 69550.09 | 44784.57 | 1.0000 | 2.36706595 | 2.051317 | 30.10 | 21.13 | 0.01272586 | 62784.4 | 11.90 | 11.35 | 0.00850000 | 33402.0 | 2.48391450 | 6.70 | 13.37 | 6.67 | 2195.006 | 67355.08 | 30.10 | 0.01272586 | 21.13 | 2.05124512 | 99.9965 | 21.11 | 0.00865961 | 21.11 | 0.00865785 | 53.2163 | 208915.85 | 0.00 | 71097.05 | 44995.87 | 2.36706595 | 30.10 | 21.63 | 0.01272586 | 62784.4 | 11.62 | 11.46 | 0.00835454 | 32748.4 | |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 35250.356 | 35250.356 | 0.615395 | 0.00030839 | 490.606 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | FLR_3_DOAS FAN | Fan:ConstantVolume | 2.051245 | 2.36698273 | 4197.9300 | 999.8980 | 7.08398362 | 54.44 | 82.22 | 27.78 | 826123.51 | 4.2670 | 4.352834 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | Sensible | 35250.36 | 35250.36 | 1.0000 | 0.71011979 | 0.615395 | -32.70 | -32.70 | 0.00018338 | -32410.8 | 16.70 | 12.79 | 0.00800000 | 37036.7 | 0.30835404 | 60.00 | 32.22 | 27.78 | 0.000 | 35250.36 | -32.70 | 0.00018338 | -32.70 | 2.05124512 | 333.3216 | 21.11 | 0.00755324 | 21.11 | 0.00755280 | 46.5069 | 165307.27 | 0.00 | 24421.86 | 24421.86 | 0.71011979 | 2.80 | -4.17 | 0.00018338 | 3273.1 | 37.01 | 13.61 | 0.00018338 | 37664.3 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:58:23
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
VAV WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 23.11 | 23.11 | - | |||
FLR_3_DOAS_OA_CONTROLLER | DifferentialDryBulb | 2.05 | 2.05 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
BASEMENT | VAV WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
RETAIL_1_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
RETAIL_2_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
MECH_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
STORAGE_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000610 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
LAUNDRY_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CAFE_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
LOBBY_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001448 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORRIDOR_FLR_3 | VAV WITH REHEAT_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
BANQUET_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
DINING_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
KITCHEN_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003556 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORRIDOR_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 2396.33 | 8760.00 | 2396.33 |
RETAIL_1_FLR_1 | 3361.50 | 8608.83 | 3311.67 |
RETAIL_2_FLR_1 | 2189.50 | 8760.00 | 2189.50 |
MECH_FLR_1 | 3301.17 | 8760.00 | 3301.17 |
STORAGE_FLR_1 | 3878.33 | 8760.00 | 3878.33 |
LAUNDRY_FLR_1 | 3139.33 | 5404.83 | 1403.67 |
CAFE_FLR_1 | 2113.33 | 8578.67 | 2058.50 |
LOBBY_FLR_1 | 1616.67 | 8760.00 | 1616.67 |
ROOM_1_FLR_3 | 3689.67 | 8302.83 | 3534.33 |
ROOM_2_FLR_3 | 4057.50 | 8472.33 | 3973.67 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 3115.83 | 8760.00 | 3115.83 |
ROOM_5_FLR_3 | 3589.83 | 8225.67 | 3476.50 |
ROOM_6_FLR_3 | 3935.33 | 8379.67 | 3906.33 |
CORRIDOR_FLR_3 | 3344.33 | 8760.00 | 3344.33 |
ROOM_1_FLR_6 | 4157.83 | 8188.50 | 3912.33 |
ROOM_2_FLR_6 | 4420.67 | 8363.50 | 4271.17 |
ROOM_3_MULT9_FLR_6 | 3166.00 | 8142.17 | 2926.00 |
BANQUET_FLR_6 | 1373.33 | 8447.33 | 1261.17 |
DINING_FLR_6 | 1268.50 | 8136.00 | 1024.67 |
KITCHEN_FLR_6 | 6318.50 | 6259.50 | 4425.83 |
CORRIDOR_FLR_6 | 3582.50 | 8760.00 | 3582.50 |
Facility | 7911.33 | 8760.00 | 7327.50 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 1074.00 | 0.00 | 1074.00 | 0.00 |
RETAIL_1_FLR_1 | 700.50 | 0.00 | 700.50 | 0.00 |
RETAIL_2_FLR_1 | 719.00 | 0.00 | 719.00 | 0.00 |
MECH_FLR_1 | 968.00 | 0.00 | 968.00 | 0.00 |
STORAGE_FLR_1 | 1077.67 | 0.00 | 1077.67 | 0.00 |
LAUNDRY_FLR_1 | 389.83 | 0.00 | 389.83 | 0.00 |
CAFE_FLR_1 | 496.00 | 0.00 | 496.00 | 0.00 |
LOBBY_FLR_1 | 621.00 | 0.00 | 621.00 | 0.00 |
ROOM_1_FLR_3 | 8.50 | 0.83 | 8.50 | 0.83 |
ROOM_2_FLR_3 | 29.00 | 0.67 | 29.00 | 0.67 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 64.00 | 2.50 | 64.00 | 2.50 |
ROOM_5_FLR_3 | 15.33 | 0.33 | 15.33 | 0.33 |
ROOM_6_FLR_3 | 42.33 | 0.33 | 42.33 | 0.33 |
CORRIDOR_FLR_3 | 840.67 | 0.00 | 840.67 | 0.00 |
ROOM_1_FLR_6 | 2.83 | 4.00 | 2.83 | 4.00 |
ROOM_2_FLR_6 | 11.00 | 2.67 | 11.00 | 2.67 |
ROOM_3_MULT9_FLR_6 | 0.17 | 2.00 | 0.17 | 2.00 |
BANQUET_FLR_6 | 483.67 | 0.00 | 483.67 | 0.00 |
DINING_FLR_6 | 473.17 | 0.00 | 473.17 | 0.00 |
KITCHEN_FLR_6 | 397.33 | 0.00 | 397.33 | 0.00 |
CORRIDOR_FLR_6 | 871.83 | 0.00 | 871.83 | 0.00 |
Facility | 1156.83 | 8.83 | 1156.83 | 8.83 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:58:23
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.78 | 106.50 | 4826.41 | 1.879 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.28 | 10.83 | 265.76 | 6.262 | 0.141 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.27 | 12.54 | 307.76 | 2.882 | 0.047 | 0.000 | 0.000 |
MECH_FLR_1 | 1.54 | 2.65 | 650.80 | 1.329 | 0.053 | 0.000 | 0.000 |
STORAGE_FLR_1 | 1.18 | 2.04 | 375.47 | 1.142 | 0.053 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.87 | 8.40 | 309.22 | 39.643 | 0.151 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.55 | 142.30 | 748.35 | 8.900 | 0.111 | 0.000 | 0.000 |
LOBBY_FLR_1 | 245.05 | 422.44 | 5183.56 | 3.664 | 0.046 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.472 | 0.184 | 0.000 | 0.041 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.472 | 0.184 | 0.000 | 0.039 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.536 | 0.082 | 0.000 | 0.062 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.472 | 0.184 | 0.000 | 0.041 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.472 | 0.184 | 0.000 | 0.039 |
CORRIDOR_FLR_3 | 12.16 | 20.96 | 1186.91 | 1.008 | 0.022 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.472 | 0.184 | 0.000 | 0.048 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.472 | 0.184 | 0.000 | 0.046 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.537 | 0.150 | 0.000 | 0.076 |
BANQUET_FLR_6 | 144.96 | 249.90 | 1010.89 | 8.138 | 0.053 | 0.000 | 0.000 |
DINING_FLR_6 | 144.96 | 249.90 | 1010.89 | 8.550 | 0.053 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.90 | 22.24 | 314.87 | 28.070 | 0.152 | 0.000 | 0.000 |
CORRIDOR_FLR_6 | 12.87 | 22.18 | 1256.16 | 2.124 | 0.037 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.78 | 106.50 | 4826.41 | 1.737 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.28 | 10.83 | 265.76 | 5.672 | 0.002 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.27 | 12.54 | 307.76 | 2.633 | 0.001 | 0.000 | 0.000 |
MECH_FLR_1 | 1.54 | 2.65 | 650.80 | 1.227 | 0.001 | 0.000 | 0.000 |
STORAGE_FLR_1 | 1.18 | 2.04 | 375.47 | 1.055 | 0.001 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.87 | 8.40 | 309.22 | 35.211 | 0.003 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.55 | 142.30 | 748.35 | 8.047 | 0.002 | 0.000 | 0.000 |
LOBBY_FLR_1 | 245.05 | 422.44 | 5183.56 | 3.340 | 0.001 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.454 | 0.003 | 0.000 | 0.000 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.454 | 0.003 | 0.000 | 0.000 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.515 | 0.001 | 0.000 | 0.000 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.454 | 0.003 | 0.000 | 0.000 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.454 | 0.003 | 0.000 | 0.000 |
CORRIDOR_FLR_3 | 12.16 | 20.96 | 1186.91 | 0.951 | 0.000 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.454 | 0.003 | 0.000 | 0.000 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.454 | 0.003 | 0.000 | 0.000 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.516 | 0.003 | 0.000 | 0.000 |
BANQUET_FLR_6 | 144.96 | 249.90 | 1010.89 | 7.388 | 0.001 | 0.000 | 0.000 |
DINING_FLR_6 | 144.96 | 249.90 | 1010.89 | 7.751 | 0.001 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.90 | 22.24 | 314.87 | 24.999 | 0.003 | 0.000 | 0.000 |
CORRIDOR_FLR_6 | 12.87 | 22.18 | 1256.16 | 1.958 | 0.001 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:58:23
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | VAV WITH REHEAT | 61.78 | 106.50 | 4826.41 | 1978.83 | 0.0000 | 0.854 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | 6.28 | 10.83 | 265.76 | 67.07 | 0.0000 | 0.079 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | 7.27 | 12.54 | 307.76 | 77.67 | 0.0000 | 0.092 |
MECH_FLR_1 | VAV WITH REHEAT | 1.54 | 2.65 | 650.80 | 164.24 | 0.0000 | 0.000 |
STORAGE_FLR_1 | VAV WITH REHEAT | 1.18 | 2.04 | 375.47 | 94.76 | 0.0000 | 0.058 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | 4.87 | 8.40 | 309.22 | 78.04 | 0.0000 | 0.000 |
CAFE_FLR_1 | VAV WITH REHEAT | 82.55 | 142.30 | 748.35 | 188.86 | 0.0000 | 0.676 |
LOBBY_FLR_1 | VAV WITH REHEAT | 245.05 | 422.44 | 5183.56 | 1308.19 | 0.0000 | 1.894 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.062 |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.062 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 1.50 | 74.75 | 24.52 | 0.0000 | 0.837 | |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 74.77 | 24.53 | 0.0000 | 0.837 |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.062 |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.062 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | 12.16 | 20.96 | 1186.91 | 389.40 | 0.0000 | 0.475 |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.015 |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.015 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 74.77 | 24.53 | 0.0000 | 0.099 |
BANQUET_FLR_6 | VAV WITH REHEAT | 144.96 | 249.90 | 1010.89 | 331.66 | 0.0000 | 1.188 |
DINING_FLR_6 | VAV WITH REHEAT | 144.96 | 249.90 | 1010.89 | 331.66 | 0.0000 | 1.188 |
KITCHEN_FLR_6 | VAV WITH REHEAT | 12.90 | 22.24 | 314.87 | 103.30 | 0.0000 | 0.367 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | 12.87 | 22.18 | 1256.16 | 412.12 | 0.0000 | 0.126 |
Total Facility | 873.11 | 1604.23 | 35184.81 | 11345.29 | 0.0000 | 137.584 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 78807132.29 | 0.00 | 78807132.29 | 0.00 | 78807132.29 | 26946214.98 | 0.00 | 0.00 | 8760.00 | 0.00 |
RETAIL_1_FLR_1 | 14468138.95 | 0.00 | 14468138.95 | 326761.06 | 14794900.02 | 2498216.28 | 0.00 | 0.00 | 8760.00 | 0.00 |
RETAIL_2_FLR_1 | 7706973.44 | 0.00 | 7706973.44 | 126130.18 | 7833103.62 | 2892943.94 | 0.00 | 0.00 | 8760.00 | 0.00 |
MECH_FLR_1 | 7516689.30 | 0.00 | 7516689.30 | 298096.82 | 7814786.12 | 0.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
STORAGE_FLR_1 | 3726694.96 | 0.00 | 3726694.96 | 171985.45 | 3898680.41 | 1821682.01 | 0.00 | 0.00 | 8760.00 | 0.00 |
LAUNDRY_FLR_1 | 0.11E+09 | 0.00 | 0.11E+09 | 407035.98 | 0.11E+09 | 0.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
CAFE_FLR_1 | 57866972.41 | 0.00 | 57866972.41 | 722323.83 | 58589296.24 | 21330615.53 | 0.00 | 0.00 | 8760.00 | 0.00 |
LOBBY_FLR_1 | 0.16E+09 | 0.00 | 0.16E+09 | 2063844.16 | 0.17E+09 | 59728886.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
ROOM_1_FLR_3 | 1946875.62 | 41659.85 | 1988535.47 | 189663.05 | 2178198.52 | 1946875.62 | 0.00 | 8086.33 | 673.67 | 0.00 |
ROOM_2_FLR_3 | 1946647.51 | 40158.02 | 1986805.53 | 189648.58 | 2176454.11 | 1946647.51 | 0.00 | 8086.33 | 673.67 | 0.00 |
ROOM_3_MULT19_FLR_3 | 26397887.27 | 45844.89 | 26443732.16 | 52918.12 | 26496650.28 | 26397887.27 | 0.00 | 8103.17 | 656.83 | 8760.00 |
ROOM_4_MULT19_FLR_3 | 26405105.73 | 39877.03 | 26444982.76 | 52932.59 | 26497915.35 | 26405105.73 | 0.00 | 8114.87 | 645.13 | 0.00 |
ROOM_5_FLR_3 | 1946875.62 | 41781.82 | 1988657.44 | 189663.05 | 2178320.48 | 1946875.62 | 0.00 | 8086.33 | 673.67 | 0.00 |
ROOM_6_FLR_3 | 1946647.51 | 40245.94 | 1986893.46 | 189648.58 | 2176542.03 | 1946647.51 | 0.00 | 8086.33 | 673.67 | 0.00 |
CORRIDOR_FLR_3 | 41540580.71 | 0.00 | 41540580.71 | 229340.78 | 41769921.49 | 14972100.18 | 0.00 | 0.00 | 8760.00 | 0.00 |
ROOM_1_FLR_6 | 486718.90 | 49143.96 | 535862.86 | 189704.08 | 725566.94 | 486718.90 | 0.00 | 8085.33 | 674.67 | 0.00 |
ROOM_2_FLR_6 | 486661.88 | 47176.89 | 533838.77 | 189689.61 | 723528.37 | 486661.88 | 0.00 | 8085.33 | 674.67 | 0.00 |
ROOM_3_MULT9_FLR_6 | 3126920.42 | 49088.92 | 3176009.33 | 97059.25 | 3273068.58 | 3126920.42 | 0.00 | 8085.33 | 674.67 | 0.00 |
BANQUET_FLR_6 | 71312528.23 | 0.00 | 71312528.23 | 463209.69 | 71775737.91 | 37458366.31 | 0.00 | 0.00 | 8760.00 | 0.00 |
DINING_FLR_6 | 74913846.22 | 0.00 | 74913846.22 | 463209.69 | 75377055.91 | 37458366.31 | 0.00 | 0.00 | 8760.00 | 0.00 |
KITCHEN_FLR_6 | 76332014.33 | 0.00 | 76332014.33 | 414680.06 | 76746694.39 | 11584760.86 | 0.00 | 0.00 | 8760.00 | 0.00 |
CORRIDOR_FLR_6 | 23190470.26 | 0.00 | 23190470.26 | 405865.71 | 23596335.97 | 3961413.96 | 0.00 | 0.00 | 8760.00 | 0.00 |
Total Facility | 0.49E+10 | 7708369.81 | 0.49E+10 | 19112579.17 | 0.50E+10 | 0.43E+10 | 0.00 | 8126.60 | 8760.00 | 8760.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 2.4990 | 0.0000 | 2.4990 | 0.0000 | 2.4990 | 0.8545 | 0.00 | 0.00 | 8760.00 |
RETAIL_1_FLR_1 | 0.4588 | 0.0000 | 0.4588 | 0.0104 | 0.4691 | 0.0792 | 0.00 | 0.00 | 8760.00 |
RETAIL_2_FLR_1 | 0.2444 | 0.0000 | 0.2444 | 0.0040 | 0.2484 | 0.0917 | 0.00 | 0.00 | 8760.00 |
MECH_FLR_1 | 0.2384 | 0.0000 | 0.2384 | 0.0095 | 0.2478 | 0.0000 | 0.00 | 0.00 | 8760.00 |
STORAGE_FLR_1 | 0.1182 | 0.0000 | 0.1182 | 0.0055 | 0.1236 | 0.0578 | 0.00 | 0.00 | 8760.00 |
LAUNDRY_FLR_1 | 3.3782 | 0.0000 | 3.3782 | 0.0129 | 3.3912 | 0.0000 | 0.00 | 0.00 | 8760.00 |
CAFE_FLR_1 | 1.8349 | 0.0000 | 1.8349 | 0.0229 | 1.8579 | 0.6764 | 0.00 | 0.00 | 8760.00 |
LOBBY_FLR_1 | 5.2304 | 0.0000 | 5.2304 | 0.0654 | 5.2959 | 1.8940 | 0.00 | 0.00 | 8760.00 |
ROOM_1_FLR_3 | 0.0617 | 0.0013 | 0.0631 | 0.0060 | 0.0691 | 0.0617 | 0.00 | 8086.33 | 673.67 |
ROOM_2_FLR_3 | 0.0617 | 0.0013 | 0.0630 | 0.0060 | 0.0690 | 0.0617 | 0.00 | 8086.33 | 673.67 |
ROOM_4_MULT19_FLR_3 | 0.8373 | 0.0013 | 0.8386 | 0.0017 | 0.8402 | 0.8373 | 0.00 | 8114.87 | 645.13 |
ROOM_5_FLR_3 | 0.0617 | 0.0013 | 0.0631 | 0.0060 | 0.0691 | 0.0617 | 0.00 | 8086.33 | 673.67 |
ROOM_6_FLR_3 | 0.0617 | 0.0013 | 0.0630 | 0.0060 | 0.0690 | 0.0617 | 0.00 | 8086.33 | 673.67 |
CORRIDOR_FLR_3 | 1.3172 | 0.0000 | 1.3172 | 0.0073 | 1.3245 | 0.4748 | 0.00 | 0.00 | 8760.00 |
ROOM_1_FLR_6 | 0.0154 | 0.0016 | 0.0170 | 0.0060 | 0.0230 | 0.0154 | 0.00 | 8085.33 | 674.67 |
ROOM_2_FLR_6 | 0.0154 | 0.0015 | 0.0169 | 0.0060 | 0.0229 | 0.0154 | 0.00 | 8085.33 | 674.67 |
ROOM_3_MULT9_FLR_6 | 0.0992 | 0.0016 | 0.1007 | 0.0031 | 0.1038 | 0.0992 | 0.00 | 8085.33 | 674.67 |
BANQUET_FLR_6 | 2.2613 | 0.0000 | 2.2613 | 0.0147 | 2.2760 | 1.1878 | 0.00 | 0.00 | 8760.00 |
DINING_FLR_6 | 2.3755 | 0.0000 | 2.3755 | 0.0147 | 2.3902 | 1.1878 | 0.00 | 0.00 | 8760.00 |
KITCHEN_FLR_6 | 2.4205 | 0.0000 | 2.4205 | 0.0131 | 2.4336 | 0.3674 | 0.00 | 0.00 | 8760.00 |
CORRIDOR_FLR_6 | 0.7354 | 0.0000 | 0.7354 | 0.0129 | 0.7482 | 0.1256 | 0.00 | 0.00 | 8760.00 |
Total Facility | 92.6097 | 0.1339 | 92.7436 | 0.4785 | 93.2222 | 73.9670 | 0.00 | 8126.60 | 8760.00 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV WITH REHEAT | 0.97E+09 | 0.00 | 0.97E+09 | 0.22E+09 | 0.00 | 0.00 | 8760.00 | 0.00 |
FLR_3_DOAS | 86137942.48 | 394977.32 | 86532919.81 | 64690340.46 | 0.00 | 0.00 | 8760.00 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV WITH REHEAT | 30.7749 | 0.0000 | 30.7749 | 6.9969 | 0.00 | 0.00 | 8760.00 |
FLR_3_DOAS | 2.7314 | 0.0125 | 2.7439 | 2.0513 | 0.00 | 0.00 | 8760.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV WITH REHEAT | 0.00 | 1871.99 | 468.92 | 0.00 | 6419.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FLR_3_DOAS | 0.00 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV WITH REHEAT | 0.0000 | 30.7942 | 30.8382 | 0.0000 | 30.7742 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
FLR_3_DOAS | 0.0000 | 2.7314 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:58:23
Surfaces by ClassTotal | Outdoors | |
Wall | 119 | 44 |
Floor | 25 | 0 |
Roof | 33 | 11 |
Internal Mass | 22 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 30 | 30 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 22 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 1306 |
Defaulted Fields | 1181 |
Fields with Defaults | 3945 |
Autosized Fields | 350 |
Autosizable Fields | 402 |
Autocalculated Fields | 280 |
Autocalculatable Fields | 539 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:58:23
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 7635.18 | 140043.36 | 22-APR-01:10 | 606703.94 | 29-JUN-18:10 |
Electricity:Building | 2943.68 | 36656.90 | 02-JAN-02:10 | 182730.36 | 02-JAN-20:10 |
Electricity:Zone:BASEMENT | 315.54 | 3631.19 | 02-JAN-02:10 | 23630.80 | 02-JAN-20:10 |
Electricity:SpaceType:GENERAL | 2925.41 | 36182.64 | 02-JAN-02:10 | 182063.43 | 02-JAN-20:10 |
InteriorLights:Electricity | 1174.11 | 10291.59 | 02-JAN-02:10 | 93091.76 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BASEMENT | 165.29 | 1501.97 | 02-JAN-02:10 | 13517.00 | 02-JAN-20:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 1174.11 | 10291.59 | 02-JAN-02:10 | 93091.76 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity | 1174.11 | 10291.59 | 02-JAN-02:10 | 93091.76 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 165.29 | 1501.97 | 02-JAN-02:10 | 13517.00 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 1174.11 | 10291.59 | 02-JAN-02:10 | 93091.76 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_1_FLR_1 | 18.59 | 220.70 | 02-JAN-02:10 | 1372.90 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 8.40 | 76.37 | 02-JAN-02:10 | 687.30 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 8.40 | 76.37 | 02-JAN-02:10 | 687.30 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_2_FLR_1 | 21.53 | 255.58 | 02-JAN-02:10 | 1589.82 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 9.73 | 88.43 | 02-JAN-02:10 | 795.89 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 9.73 | 88.43 | 02-JAN-02:10 | 795.89 | 02-JAN-20:10 |
Electricity:Zone:MECH_FLR_1 | 30.66 | 342.02 | 02-JAN-02:10 | 2327.13 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:MECH_FLR_1 | 18.19 | 165.30 | 02-JAN-02:10 | 1487.69 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:MECH_FLR_1 | 18.19 | 165.30 | 02-JAN-02:10 | 1487.69 | 02-JAN-20:10 |
Electricity:Zone:STORAGE_FLR_1 | 6.94 | 81.32 | 02-JAN-02:10 | 515.26 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 3.34 | 30.34 | 02-JAN-02:10 | 273.10 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 3.34 | 30.34 | 02-JAN-02:10 | 273.10 | 02-JAN-20:10 |
Electricity:Zone:LAUNDRY_FLR_1 | 72.06 | 1000.18 | 02-JAN-02:10 | 4910.17 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 4.13 | 37.49 | 02-JAN-02:10 | 337.37 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 4.13 | 37.49 | 02-JAN-02:10 | 337.37 | 02-JAN-20:10 |
Electricity:Zone:CAFE_FLR_1 | 40.96 | 445.13 | 02-JAN-02:10 | 3142.50 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CAFE_FLR_1 | 26.62 | 241.91 | 02-JAN-02:10 | 2177.23 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CAFE_FLR_1 | 26.62 | 241.91 | 02-JAN-02:10 | 2177.23 | 02-JAN-20:10 |
Electricity:Zone:LOBBY_FLR_1 | 293.89 | 3428.00 | 02-JAN-02:10 | 21878.53 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 144.90 | 1316.59 | 02-JAN-02:10 | 11849.32 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 144.90 | 1316.59 | 02-JAN-02:10 | 11849.32 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_3 | 32.70 | 383.52 | 01-JAN-02:10 | 2308.42 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 20.41 | 172.80 | 01-JAN-02:10 | 1570.91 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 20.41 | 172.80 | 01-JAN-02:10 | 1570.91 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_3 | 32.70 | 383.47 | 01-JAN-02:10 | 2308.15 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 20.41 | 172.78 | 01-JAN-02:10 | 1570.72 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 20.41 | 172.78 | 01-JAN-02:10 | 1570.72 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT19_FLR_3 | 472.46 | 5984.83 | 01-JAN-02:10 | 32482.97 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 243.71 | 2063.36 | 01-JAN-02:10 | 18757.86 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 243.71 | 2063.36 | 01-JAN-02:10 | 18757.86 | 01-JAN-19:10 |
Electricity:Zone:ROOM_4_MULT19_FLR_3 | 472.59 | 5986.46 | 01-JAN-02:10 | 32491.86 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 243.77 | 2063.93 | 01-JAN-02:10 | 18762.99 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 243.77 | 2063.93 | 01-JAN-02:10 | 18762.99 | 01-JAN-19:10 |
Electricity:Zone:ROOM_5_FLR_3 | 32.70 | 383.52 | 01-JAN-02:10 | 2308.42 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 20.41 | 172.80 | 01-JAN-02:10 | 1570.91 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 20.41 | 172.80 | 01-JAN-02:10 | 1570.91 | 01-JAN-19:10 |
Electricity:Zone:ROOM_6_FLR_3 | 32.70 | 383.47 | 01-JAN-02:10 | 2308.15 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 20.41 | 172.78 | 01-JAN-02:10 | 1570.72 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 20.41 | 172.78 | 01-JAN-02:10 | 1570.72 | 01-JAN-19:10 |
Electricity:Zone:CORRIDOR_FLR_3 | 62.74 | 570.05 | 02-JAN-02:10 | 5130.41 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 62.74 | 570.05 | 02-JAN-02:10 | 5130.41 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 62.74 | 570.05 | 02-JAN-02:10 | 5130.41 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_6 | 8.18 | 95.88 | 01-JAN-02:10 | 577.11 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 5.10 | 43.20 | 01-JAN-02:10 | 392.73 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 5.10 | 43.20 | 01-JAN-02:10 | 392.73 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_6 | 8.17 | 95.87 | 01-JAN-02:10 | 577.04 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 5.10 | 43.19 | 01-JAN-02:10 | 392.68 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 5.10 | 43.19 | 01-JAN-02:10 | 392.68 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT9_FLR_6 | 55.96 | 708.92 | 01-JAN-02:10 | 3847.72 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 28.87 | 244.41 | 01-JAN-02:10 | 2221.93 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 28.87 | 244.41 | 01-JAN-02:10 | 2221.93 | 01-JAN-19:10 |
Electricity:Zone:BANQUET_FLR_6 | 222.61 | 2674.12 | 02-JAN-02:10 | 10571.30 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 46.75 | 424.82 | 02-JAN-02:10 | 3823.39 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 46.75 | 424.82 | 02-JAN-02:10 | 3823.39 | 02-JAN-20:10 |
Electricity:Zone:DINING_FLR_6 | 222.61 | 2674.12 | 02-JAN-02:10 | 10571.30 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:DINING_FLR_6 | 46.75 | 424.82 | 02-JAN-02:10 | 3823.39 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:DINING_FLR_6 | 46.75 | 424.82 | 02-JAN-02:10 | 3823.39 | 02-JAN-20:10 |
Electricity:Zone:KITCHEN_FLR_6 | 470.78 | 6777.71 | 02-JAN-02:10 | 19298.76 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 12.48 | 113.42 | 02-JAN-02:10 | 1020.78 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 12.48 | 113.42 | 02-JAN-02:10 | 1020.78 | 02-JAN-20:10 |
Electricity:Zone:CORRIDOR_FLR_6 | 16.60 | 150.83 | 02-JAN-02:10 | 1357.44 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 16.60 | 150.83 | 02-JAN-02:10 | 1357.44 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 16.60 | 150.83 | 02-JAN-02:10 | 1357.44 | 02-JAN-20:10 |
InteriorEquipment:Electricity | 1751.30 | 25891.05 | 02-JAN-02:10 | 89674.66 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 150.26 | 2129.22 | 02-JAN-02:10 | 10113.80 | 02-JAN-20:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 1751.30 | 25891.05 | 02-JAN-02:10 | 89674.66 | 02-JAN-07:10 |
MiscPlug:InteriorEquipment:Electricity | 959.56 | 15202.41 | 02-JAN-02:10 | 59492.27 | 02-JAN-07:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 150.26 | 2129.22 | 02-JAN-02:10 | 10113.80 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 959.56 | 15202.41 | 02-JAN-02:10 | 59492.27 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.79 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.79 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 12.29 | 210.72 | 01-JAN-00:10 | 948.23 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 12.29 | 210.72 | 01-JAN-00:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 12.29 | 210.69 | 01-JAN-00:10 | 948.12 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 12.29 | 210.69 | 01-JAN-00:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 228.75 | 3921.46 | 01-JAN-00:10 | 17646.57 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 228.75 | 3921.46 | 01-JAN-00:10 | 17646.57 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 228.82 | 3922.53 | 01-JAN-00:10 | 17651.40 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 228.82 | 3922.53 | 01-JAN-00:10 | 17651.40 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 12.29 | 210.72 | 01-JAN-00:10 | 948.23 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 12.29 | 210.72 | 01-JAN-00:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 12.29 | 210.69 | 01-JAN-00:10 | 948.12 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 12.29 | 210.69 | 01-JAN-00:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 3.07 | 52.68 | 01-JAN-00:10 | 237.06 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 3.07 | 52.68 | 01-JAN-00:10 | 237.06 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 3.07 | 52.67 | 01-JAN-00:10 | 237.03 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 3.07 | 52.67 | 01-JAN-00:10 | 237.03 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 27.10 | 464.51 | 01-JAN-00:10 | 2090.30 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 27.10 | 464.51 | 01-JAN-00:10 | 2090.30 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 440.03 | 6190.03 | 01-JAN-00:10 | 16686.59 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 410.33 | 5248.28 | 01-JAN-00:10 | 15744.84 | 01-JAN-07:10 |
ReachInFreezer:InteriorEquipment:Electricity | 16.27 | 515.92 | 01-JAN-00:10 | 515.92 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 16.27 | 515.92 | 01-JAN-00:10 | 515.92 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 16.27 | 515.92 | 01-JAN-00:10 | 515.92 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 13.43 | 425.83 | 01-JAN-00:10 | 425.83 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 13.43 | 425.83 | 01-JAN-00:10 | 425.83 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 13.43 | 425.83 | 01-JAN-00:10 | 425.83 | 01-JAN-00:10 |
Refrigeration:Electricity | 72.66 | 566.56 | 06-JAN-04:00 | 3642.16 | 23-JUN-07:00 |
Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 18.27 | 261.51 | 02-JAN-11:30 | 2271.91 | 01-JAN-11:10 |
General:Refrigeration:Electricity | 18.27 | 261.51 | 02-JAN-11:30 | 2271.91 | 01-JAN-11:10 |
General:Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 18.27 | 261.51 | 02-JAN-11:30 | 2271.91 | 01-JAN-11:10 |
Electricity:Plant | 1320.54 | 2820.25 | 21-APR-00:40 | 318013.17 | 29-JUN-16:00 |
LowTempRefrigeration:Refrigeration:Electricity | 21.83 | 0.00 | 01-JAN-11:10 | 1889.44 | 07-JUL-07:20 |
MedTempRefrigeration:Refrigeration:Electricity | 32.56 | -64.91 | 06-JAN-04:10 | 1199.98 | 23-JUN-13:10 |
Fans:Electricity | 1919.11 | 54981.52 | 21-APR-00:40 | 92214.49 | 09-JAN-05:00 |
Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Electricity:HVAC | 2462.52 | 56523.42 | 01-NOV-10:40 | 110927.22 | 09-JAN-05:00 |
ExteriorEquipment:Electricity | 679.68 | 10574.27 | 02-JAN-02:20 | 40537.60 | 02-JAN-07:20 |
Transformer:ExteriorEquipment:Electricity | 32.92 | 556.27 | 07-JAN-04:20 | 1912.91 | 02-JAN-21:10 |
ElectricityPurchased:Facility | 7635.18 | 140043.36 | 22-APR-01:10 | 606703.94 | 29-JUN-18:10 |
ElectricityPurchased:Plant | 7635.18 | 140043.36 | 22-APR-01:10 | 606703.94 | 29-JUN-18:10 |
Cogeneration:ElectricityPurchased | 7635.18 | 140043.36 | 22-APR-01:10 | 606703.94 | 29-JUN-18:10 |
General:Cogeneration:ElectricityPurchased | 7635.18 | 140043.36 | 22-APR-01:10 | 606703.94 | 29-JUN-18:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 7635.18 | 140043.36 | 22-APR-01:10 | 606703.94 | 29-JUN-18:10 |
ElectricityNet:Plant | 7635.18 | 140043.36 | 22-APR-01:10 | 606703.94 | 29-JUN-18:10 |
Cogeneration:ElectricityNet | 7635.18 | 140043.36 | 22-APR-01:10 | 606703.94 | 29-JUN-18:10 |
General:Cogeneration:ElectricityNet | 7635.18 | 140043.36 | 22-APR-01:10 | 606703.94 | 29-JUN-18:10 |
General:Fans:Electricity | 1919.11 | 54981.52 | 21-APR-00:40 | 92214.49 | 09-JAN-05:00 |
ExteriorLights:Electricity | 261.66 | 0.00 | 01-JAN-08:20 | 16690.39 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 261.66 | 0.00 | 01-JAN-08:20 | 16690.39 | 01-JAN-00:10 |
ElevatorLift:ExteriorEquipment:Electricity | 616.11 | 9046.01 | 01-JAN-00:10 | 37691.69 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 30.65 | 972.00 | 01-JAN-00:10 | 972.00 | 01-JAN-00:10 |
HeatRecovery:Electricity | 510.50 | 0.00 | 11-APR-11:50 | 18156.47 | 01-JAN-08:20 |
General:HeatRecovery:Electricity | 510.50 | 0.00 | 11-APR-11:50 | 18156.47 | 01-JAN-08:20 |
WaterSystems:Electricity | 90.81 | 1087.05 | 09-AUG-00:50 | 4755.74 | 06-JAN-07:30 |
Water Heater:WaterSystems:Electricity | 90.81 | 1087.05 | 09-AUG-00:50 | 4755.74 | 06-JAN-07:30 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 985.56 | 0.00 | 01-JAN-00:10 | 301034.78 | 29-JUN-16:00 |
General:Cooling:Electricity | 985.56 | 0.00 | 01-JAN-00:10 | 301034.78 | 29-JUN-16:00 |
Pumps:Electricity | 189.78 | 213.37 | 07-OCT-17:10 | 13486.55 | 23-JUL-10:40 |
General:Pumps:Electricity | 189.78 | 213.37 | 07-OCT-17:10 | 13486.55 | 23-JUL-10:40 |
WIRED_LTG_ELECTRICITY | 41.33 | 0.00 | 01-JAN-00:10 | 3276.83 | 02-JAN-20:20 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 10173.60 | 44358.22 | 08-AUG-23:10 | 1431349.25 | 04-JAN-22:00 |
NaturalGas:Building | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
NaturalGas:SpaceType:GENERAL | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:NaturalGas | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
InteriorEquipment:NaturalGas:SpaceType:GENERAL | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
Laundry:InteriorEquipment:NaturalGas | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
NaturalGas:Plant | 8384.76 | 25956.37 | 26-AUG-23:30 | 1356225.49 | 04-JAN-22:00 |
WaterSystems:NaturalGas | 3565.50 | 18467.44 | 07-JAN-04:10 | 314232.99 | 02-MAR-21:20 |
Water Heater:WaterSystems:NaturalGas | 3565.50 | 18467.44 | 07-JAN-04:10 | 314232.99 | 02-MAR-21:20 |
Heating:NaturalGas | 4819.26 | 138.03 | 29-JUN-21:20 | 1111818.01 | 06-JAN-05:00 |
Boiler:Heating:NaturalGas | 4819.26 | 138.03 | 29-JUN-21:20 | 1111818.01 | 06-JAN-05:00 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 3035.44 | 0.00 | 01-JAN-00:10 | 880372.19 | 29-JUN-18:10 |
PlantLoopCoolingDemand:HVAC | 3035.44 | 0.00 | 01-JAN-00:10 | 880372.19 | 29-JUN-18:10 |
CoolingCoils:PlantLoopCoolingDemand | 3035.44 | 0.00 | 01-JAN-00:10 | 880372.19 | 29-JUN-18:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 12-JAN-21:10 |
Water:Plant | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 12-JAN-21:10 |
WaterSystems:Water | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 12-JAN-21:10 |
Water Heater:WaterSystems:Water | 5742.51 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-19:20 |
MainsWater:Facility | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 12-JAN-21:10 |
MainsWater:Plant | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 12-JAN-21:10 |
WaterSystems:MainsWater | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 12-JAN-21:10 |
Water Heater:WaterSystems:MainsWater | 5742.51 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-19:20 |
WaterUse:WaterSystems:Water | 4114.69 | 0.00 | 02-JAN-01:10 | 0.00 | 04-JAN-07:10 |
WaterUse:WaterSystems:MainsWater | 4114.69 | 0.00 | 02-JAN-01:10 | 0.00 | 04-JAN-07:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 34088.68 | 241274.81 | 07-OCT-11:50 | 3911403.43 | 29-JUN-18:10 |
EnergyTransfer:Building | 5747.37 | 68240.70 | 02-DEC-11:10 | 455420.15 | 25-JAN-20:10 |
EnergyTransfer:Zone:KITCHEN_FLR_6 | 725.86 | 3275.74 | 14-JAN-05:30 | 43033.85 | 25-JAN-20:10 |
Refrigeration:EnergyTransfer | 180.32 | 290.54 | 06-JAN-04:00 | 10374.78 | 23-JUN-07:00 |
Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 90.16 | 145.27 | 06-JAN-04:00 | 5187.39 | 23-JUN-07:00 |
General:Refrigeration:EnergyTransfer | 90.16 | 145.27 | 06-JAN-04:00 | 5187.39 | 23-JUN-07:00 |
General:Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 90.16 | 145.27 | 06-JAN-04:00 | 5187.39 | 23-JUN-07:00 |
EnergyTransfer:Plant | 12018.04 | 42281.35 | 18-NOV-00:10 | 2121259.13 | 29-JUN-18:10 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 25.56 | 0.00 | 01-JAN-11:10 | 2686.44 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 64.60 | -194.74 | 06-JAN-04:10 | 2549.93 | 23-JUN-13:10 |
EnergyTransfer:Zone:BASEMENT | 432.39 | 0.59 | 15-JAN-03:40 | 60690.85 | 14-FEB-07:00 |
Heating:EnergyTransfer | 461.11 | 0.00 | 08-FEB-18:30 | 231507.44 | 07-JAN-04:40 |
Heating:EnergyTransfer:Zone:BASEMENT | 4.57 | 0.00 | 01-JAN-00:30 | 23146.04 | 06-JAN-14:00 |
General:Heating:EnergyTransfer | 461.11 | 0.00 | 08-FEB-18:30 | 231507.44 | 07-JAN-04:40 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 4.57 | 0.00 | 01-JAN-00:30 | 23146.04 | 06-JAN-14:00 |
Cooling:EnergyTransfer | 5196.10 | 0.00 | 07-JAN-04:40 | 407690.77 | 25-JAN-20:10 |
Cooling:EnergyTransfer:Zone:BASEMENT | 427.82 | 0.00 | 01-JAN-00:10 | 60690.85 | 14-FEB-07:00 |
General:Cooling:EnergyTransfer | 5196.10 | 0.00 | 07-JAN-04:40 | 407690.77 | 25-JAN-20:10 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 427.82 | 0.00 | 01-JAN-00:10 | 60690.85 | 14-FEB-07:00 |
EnergyTransfer:Zone:RETAIL_1_FLR_1 | 43.55 | 0.06 | 16-NOV-02:10 | 5447.73 | 07-JAN-04:40 |
Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 6.79 | 0.00 | 01-JAN-00:40 | 5447.73 | 07-JAN-04:40 |
General:Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 6.79 | 0.00 | 01-JAN-00:40 | 5447.73 | 07-JAN-04:40 |
Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 36.76 | 0.00 | 01-JAN-00:10 | 5429.14 | 25-JAN-20:10 |
General:Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 36.76 | 0.00 | 01-JAN-00:10 | 5429.14 | 25-JAN-20:10 |
EnergyTransfer:Zone:RETAIL_2_FLR_1 | 36.58 | 0.03 | 15-DEC-09:40 | 4236.02 | 25-JAN-20:10 |
Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 1.11 | 0.00 | 01-JAN-00:40 | 2996.86 | 06-JAN-13:50 |
General:Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 1.11 | 0.00 | 01-JAN-00:40 | 2996.86 | 06-JAN-13:50 |
Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 35.46 | 0.00 | 01-JAN-00:10 | 4236.02 | 25-JAN-20:10 |
General:Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 35.46 | 0.00 | 01-JAN-00:10 | 4236.02 | 25-JAN-20:10 |
EnergyTransfer:Zone:MECH_FLR_1 | 28.83 | 0.07 | 19-JAN-10:00 | 4000.57 | 06-JAN-14:00 |
Heating:EnergyTransfer:Zone:MECH_FLR_1 | 5.62 | 0.00 | 01-JAN-00:40 | 4000.57 | 06-JAN-14:00 |
General:Heating:EnergyTransfer:Zone:MECH_FLR_1 | 5.62 | 0.00 | 01-JAN-00:40 | 4000.57 | 06-JAN-14:00 |
Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 23.21 | 0.00 | 01-JAN-00:10 | 3379.55 | 25-JAN-20:10 |
General:Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 23.21 | 0.00 | 01-JAN-00:10 | 3379.55 | 25-JAN-20:10 |
EnergyTransfer:Zone:STORAGE_FLR_1 | 13.51 | 0.01 | 01-APR-23:50 | 2252.31 | 06-JAN-14:00 |
Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 5.13 | 0.00 | 01-JAN-00:40 | 2252.31 | 06-JAN-14:00 |
General:Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 5.13 | 0.00 | 01-JAN-00:40 | 2252.31 | 06-JAN-14:00 |
Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 8.38 | 0.00 | 01-JAN-00:10 | 1335.03 | 25-JAN-21:00 |
General:Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 8.38 | 0.00 | 01-JAN-00:10 | 1335.03 | 25-JAN-21:00 |
EnergyTransfer:Zone:LAUNDRY_FLR_1 | 589.80 | 71.68 | 07-JAN-05:10 | 52173.91 | 25-JAN-20:10 |
Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.05 | 0.00 | 01-JAN-00:10 | 7568.20 | 14-JAN-05:00 |
General:Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.05 | 0.00 | 01-JAN-00:10 | 7568.20 | 14-JAN-05:00 |
Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 589.75 | 0.00 | 06-JAN-13:50 | 52173.91 | 25-JAN-20:10 |
General:Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 589.75 | 0.00 | 06-JAN-13:50 | 52173.91 | 25-JAN-20:10 |
EnergyTransfer:Zone:CAFE_FLR_1 | 256.95 | 0.31 | 16-FEB-07:10 | 24963.96 | 25-JAN-20:10 |
Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 2.12 | 0.00 | 01-JAN-00:10 | 14271.43 | 21-DEC-11:10 |
General:Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 2.12 | 0.00 | 01-JAN-00:10 | 14271.43 | 21-DEC-11:10 |
Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 254.83 | 0.00 | 01-JAN-10:50 | 24963.96 | 25-JAN-20:10 |
General:Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 254.83 | 0.00 | 01-JAN-10:50 | 24963.96 | 25-JAN-20:10 |
EnergyTransfer:Zone:LOBBY_FLR_1 | 873.59 | 27.74 | 15-JAN-13:40 | 92936.42 | 25-JAN-20:10 |
Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 10.08 | 0.00 | 01-JAN-00:10 | 48612.62 | 06-JAN-13:50 |
General:Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 10.08 | 0.00 | 01-JAN-00:10 | 48612.62 | 06-JAN-13:50 |
Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 863.50 | 0.00 | 01-JAN-10:40 | 92936.42 | 25-JAN-20:10 |
General:Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 863.50 | 0.00 | 01-JAN-10:40 | 92936.42 | 25-JAN-20:10 |
EnergyTransfer:Zone:ROOM_1_FLR_3 | 80.57 | 0.23 | 17-MAR-19:30 | 14068.37 | 30-JUN-18:10 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 37.19 | 0.00 | 01-JAN-11:10 | 8514.32 | 07-JAN-09:10 |
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 37.19 | 0.00 | 01-JAN-11:10 | 8514.32 | 07-JAN-09:10 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 43.39 | 0.00 | 01-JAN-00:10 | 14068.37 | 30-JUN-18:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 43.39 | 0.00 | 01-JAN-00:10 | 14068.37 | 30-JUN-18:10 |
EnergyTransfer:Zone:ROOM_2_FLR_3 | 80.31 | 0.04 | 19-AUG-00:30 | 13842.18 | 30-JUN-18:10 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 44.53 | 0.00 | 15-JAN-18:10 | 9129.00 | 06-JAN-16:20 |
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 44.53 | 0.00 | 15-JAN-18:10 | 9129.00 | 06-JAN-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 35.78 | 0.00 | 01-JAN-00:10 | 13842.18 | 30-JUN-18:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 35.78 | 0.00 | 01-JAN-00:10 | 13842.18 | 30-JUN-18:10 |
EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 468.81 | 0.46 | 16-MAR-05:00 | 79119.88 | 22-OCT-12:20 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 37.52 | 0.00 | 01-JAN-00:10 | 31212.55 | 09-JAN-05:00 |
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 37.52 | 0.00 | 01-JAN-00:10 | 31212.55 | 09-JAN-05:00 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 431.29 | 0.00 | 01-JAN-02:10 | 79119.88 | 22-OCT-12:20 |
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 431.29 | 0.00 | 01-JAN-02:10 | 79119.88 | 22-OCT-12:20 |
EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 492.95 | 2.26 | 24-MAR-05:20 | 76566.67 | 30-JUN-18:20 |
Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 112.22 | 0.00 | 01-JAN-08:10 | 52744.63 | 06-JAN-16:10 |
General:Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 112.22 | 0.00 | 01-JAN-08:10 | 52744.63 | 06-JAN-16:10 |
Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 380.74 | 0.00 | 01-JAN-00:10 | 76566.67 | 30-JUN-18:20 |
General:Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 380.74 | 0.00 | 01-JAN-00:10 | 76566.67 | 30-JUN-18:20 |
EnergyTransfer:Zone:ROOM_5_FLR_3 | 80.11 | 0.20 | 10-OCT-20:50 | 12166.03 | 29-JUL-08:10 |
Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 37.06 | 0.00 | 01-JAN-11:10 | 8500.92 | 25-DEC-16:10 |
General:Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 37.06 | 0.00 | 01-JAN-11:10 | 8500.92 | 25-DEC-16:10 |
Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 43.05 | 0.00 | 01-JAN-00:10 | 12166.03 | 29-JUL-08:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 43.05 | 0.00 | 01-JAN-00:10 | 12166.03 | 29-JUL-08:10 |
EnergyTransfer:Zone:ROOM_6_FLR_3 | 79.58 | 0.10 | 18-OCT-22:30 | 11906.63 | 29-JUL-08:10 |
Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 44.43 | 0.00 | 02-JAN-11:10 | 9709.04 | 06-JAN-16:10 |
General:Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 44.43 | 0.00 | 02-JAN-11:10 | 9709.04 | 06-JAN-16:10 |
Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 35.15 | 0.00 | 01-JAN-00:10 | 11906.63 | 29-JUL-08:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 35.15 | 0.00 | 01-JAN-00:10 | 11906.63 | 29-JUL-08:10 |
EnergyTransfer:Zone:CORRIDOR_FLR_3 | 202.89 | 0.70 | 01-DEC-10:10 | 23115.16 | 14-FEB-07:00 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 24.65 | 0.00 | 01-JAN-00:40 | 14066.67 | 06-JAN-14:00 |
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 24.65 | 0.00 | 01-JAN-00:40 | 14066.67 | 06-JAN-14:00 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 178.25 | 0.00 | 01-JAN-00:10 | 23115.16 | 14-FEB-07:00 |
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 178.25 | 0.00 | 01-JAN-00:10 | 23115.16 | 14-FEB-07:00 |
EnergyTransfer:Zone:ROOM_1_FLR_6 | 24.33 | 0.01 | 21-MAY-05:50 | 3835.15 | 30-JUN-18:10 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 12.60 | 0.00 | 01-JAN-14:20 | 2471.34 | 04-JAN-19:20 |
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 12.60 | 0.00 | 01-JAN-14:20 | 2471.34 | 04-JAN-19:20 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 11.73 | 0.00 | 01-JAN-00:10 | 3835.15 | 30-JUN-18:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 11.73 | 0.00 | 01-JAN-00:10 | 3835.15 | 30-JUN-18:10 |
EnergyTransfer:Zone:ROOM_2_FLR_6 | 24.55 | 0.02 | 01-NOV-16:20 | 3699.54 | 30-JUN-18:10 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 14.85 | 0.00 | 16-JAN-08:10 | 2528.81 | 18-DEC-16:20 |
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 14.85 | 0.00 | 16-JAN-08:10 | 2528.81 | 18-DEC-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 9.70 | 0.00 | 01-JAN-00:10 | 3699.54 | 30-JUN-18:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 9.70 | 0.00 | 01-JAN-00:10 | 3699.54 | 30-JUN-18:10 |
EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 113.22 | 0.00 | 22-SEP-04:00 | 18668.22 | 25-AUG-15:10 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 35.72 | 0.00 | 01-JAN-09:00 | 10484.01 | 11-DEC-16:20 |
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 35.72 | 0.00 | 01-JAN-09:00 | 10484.01 | 11-DEC-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 77.51 | 0.00 | 01-JAN-00:10 | 18668.22 | 25-AUG-15:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 77.51 | 0.00 | 01-JAN-00:10 | 18668.22 | 25-AUG-15:10 |
EnergyTransfer:Zone:BANQUET_FLR_6 | 484.61 | 3.46 | 14-DEC-10:30 | 37224.65 | 24-FEB-23:00 |
Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 1.10 | 0.00 | 01-JAN-00:10 | 15977.33 | 06-JAN-13:50 |
General:Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 1.10 | 0.00 | 01-JAN-00:10 | 15977.33 | 06-JAN-13:50 |
Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 483.51 | 0.00 | 01-JAN-10:50 | 37224.65 | 24-FEB-23:00 |
General:Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 483.51 | 0.00 | 01-JAN-10:50 | 37224.65 | 24-FEB-23:00 |
EnergyTransfer:Zone:DINING_FLR_6 | 521.14 | 2.85 | 14-FEB-15:00 | 39274.37 | 24-FEB-23:00 |
Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.98 | 0.00 | 01-JAN-00:10 | 16578.82 | 06-JAN-13:50 |
General:Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.98 | 0.00 | 01-JAN-00:10 | 16578.82 | 06-JAN-13:50 |
Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 520.16 | 0.00 | 01-JAN-10:50 | 39274.37 | 24-FEB-23:00 |
General:Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 520.16 | 0.00 | 01-JAN-10:50 | 39274.37 | 24-FEB-23:00 |
Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.02 | 0.00 | 01-JAN-00:10 | 5446.09 | 14-JAN-05:00 |
General:Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.02 | 0.00 | 01-JAN-00:10 | 5446.09 | 14-JAN-05:00 |
Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 635.68 | 0.00 | 07-JAN-04:40 | 39573.89 | 25-JAN-20:10 |
General:Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 635.68 | 0.00 | 07-JAN-04:40 | 39573.89 | 25-JAN-20:10 |
EnergyTransfer:Zone:CORRIDOR_FLR_6 | 93.24 | 0.24 | 04-NOV-13:10 | 12039.26 | 06-JAN-14:00 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 22.77 | 0.00 | 01-JAN-00:40 | 12039.26 | 06-JAN-14:00 |
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 22.77 | 0.00 | 01-JAN-00:40 | 12039.26 | 06-JAN-14:00 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 70.46 | 0.00 | 01-JAN-00:10 | 8455.52 | 25-JAN-20:10 |
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 70.46 | 0.00 | 01-JAN-00:10 | 8455.52 | 25-JAN-20:10 |
PlantLoopHeatingDemand:Facility | 4593.36 | 18046.11 | 22-JUL-00:10 | 971689.19 | 06-JAN-07:10 |
PlantLoopHeatingDemand:Plant | 900.58 | 10715.74 | 29-AUG-02:40 | 66774.68 | 28-FEB-07:20 |
WaterSystems:PlantLoopHeatingDemand | 900.58 | 10715.74 | 29-AUG-02:40 | 66774.68 | 28-FEB-07:20 |
General:WaterSystems:PlantLoopHeatingDemand | 900.58 | 10715.74 | 29-AUG-02:40 | 66774.68 | 28-FEB-07:20 |
EnergyTransfer:HVAC | 16323.26 | 32230.34 | 16-AUG-07:30 | 1411487.72 | 30-JUN-15:30 |
HeatingCoils:EnergyTransfer | 3692.78 | 115.67 | 29-JUN-21:20 | 915745.13 | 06-JAN-05:00 |
PlantLoopHeatingDemand:HVAC | 3692.78 | 115.67 | 29-JUN-21:20 | 915745.13 | 06-JAN-05:00 |
HeatingCoils:PlantLoopHeatingDemand | 3692.78 | 115.67 | 29-JUN-21:20 | 915745.13 | 06-JAN-05:00 |
CoolingCoils:EnergyTransfer | 3035.44 | 0.00 | 01-JAN-00:10 | 880372.19 | 29-JUN-18:10 |
HeatRecoveryForHeating:EnergyTransfer | 9161.55 | 0.00 | 01-JAN-00:40 | 974343.06 | 07-MAR-00:40 |
HeatRecoveryForCooling:EnergyTransfer | 433.49 | 0.00 | 01-JAN-00:10 | 573325.56 | 15-JUL-14:00 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:EnergyTransfer | 900.58 | 10715.74 | 29-AUG-02:40 | 66774.68 | 28-FEB-07:20 |
WaterUse:WaterSystems:EnergyTransfer | 900.58 | 10715.74 | 29-AUG-02:40 | 66774.68 | 28-FEB-07:20 |
Boilers:EnergyTransfer | 3671.05 | 84.22 | 29-JUN-21:20 | 912548.66 | 06-JAN-05:00 |
Chillers:EnergyTransfer | 3185.35 | 0.00 | 01-JAN-00:10 | 890106.19 | 29-JUN-18:10 |
HeatRejection:EnergyTransfer | 4170.91 | 0.00 | 01-JAN-00:10 | 1184082.11 | 29-JUN-18:10 |
General:HeatRejection:EnergyTransfer | 4170.91 | 0.00 | 01-JAN-00:10 | 1184082.11 | 29-JUN-18:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:58:23
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 4.574 | -427.815 | 0.000 | 0.000 | 161.684 | 165.288 | 150.255 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -53.986 |
RETAIL_1_FLR_1 | 0.000 | 0.000 | 6.793 | -36.759 | 0.000 | 0.000 | 16.532 | 8.404 | 10.186 | 29.620 | 0.000 | 0.109 | 0.002 | 0.000 | -12.613 | 0.000 | -6.905 | -15.367 |
RETAIL_2_FLR_1 | 0.000 | 0.000 | 1.114 | -35.464 | 0.000 | 0.000 | 19.051 | 9.732 | 11.795 | 0.000 | 0.000 | 0.044 | 0.000 | 0.000 | 0.000 | 0.000 | -2.681 | -3.592 |
MECH_FLR_1 | 0.000 | 0.000 | 5.624 | -23.207 | 0.000 | 0.000 | 4.041 | 18.192 | 12.471 | 0.000 | 0.000 | 0.105 | 0.001 | 0.000 | 0.000 | 0.000 | -6.335 | -10.891 |
STORAGE_FLR_1 | 0.000 | 0.000 | 5.127 | -8.378 | 0.000 | 0.000 | 3.113 | 3.340 | 3.598 | 0.000 | 0.000 | 0.061 | 0.000 | 0.000 | 0.000 | 0.000 | -3.650 | -3.211 |
LAUNDRY_FLR_1 | 0.000 | 0.000 | 0.052 | -589.752 | 0.000 | 0.000 | 12.509 | 4.125 | 658.131 | 0.000 | 0.000 | 0.136 | 0.001 | 0.000 | 0.000 | 0.000 | -8.673 | -76.528 |
CAFE_FLR_1 | 0.000 | 0.000 | 2.118 | -254.828 | 0.000 | 0.000 | 216.727 | 26.624 | 14.341 | 83.217 | 0.000 | 0.249 | 0.010 | 0.000 | -35.191 | 0.000 | -15.300 | -37.956 |
LOBBY_FLR_1 | 0.000 | 0.000 | 10.082 | -863.506 | 0.000 | 0.000 | 639.690 | 144.896 | 148.998 | 109.686 | 0.000 | 0.723 | 0.013 | 0.000 | -47.218 | 0.000 | -44.001 | -99.349 |
ROOM_1_FLR_3 | 44.732 | -34.485 | 0.000 | -16.445 | 0.000 | 0.000 | 9.767 | 20.410 | 12.292 | 53.033 | 0.000 | 0.244 | 0.000 | 0.000 | -30.998 | 0.000 | -17.212 | -41.338 |
ROOM_2_FLR_3 | 52.566 | -27.634 | 0.000 | -16.182 | 0.000 | 0.000 | 9.792 | 20.407 | 12.291 | 36.666 | 0.000 | 0.241 | 0.000 | 0.000 | -32.710 | 0.000 | -17.101 | -38.337 |
ROOM_3_MULT19_FLR_3 | 80.654 | -228.629 | 0.000 | -245.798 | 0.000 | 0.000 | 0.000 | 243.708 | 228.754 | 346.628 | 0.000 | 0.736 | 0.003 | 0.000 | -170.620 | 0.000 | -108.322 | -147.109 |
ROOM_4_MULT19_FLR_3 | 192.166 | -239.053 | 0.000 | -221.623 | 0.000 | 0.000 | 185.749 | 243.774 | 228.817 | 91.105 | 0.000 | 2.057 | 0.000 | 0.000 | -186.529 | 0.000 | -97.064 | -199.400 |
ROOM_5_FLR_3 | 44.587 | -34.074 | 0.000 | -16.505 | 0.000 | 0.000 | 9.762 | 20.410 | 12.292 | 52.564 | 0.000 | 0.244 | 0.000 | 0.000 | -30.481 | 0.000 | -17.247 | -41.552 |
ROOM_6_FLR_3 | 52.459 | -26.904 | 0.000 | -16.278 | 0.000 | 0.000 | 9.786 | 20.407 | 12.291 | 35.926 | 0.000 | 0.241 | 0.000 | 0.000 | -31.951 | 0.000 | -17.144 | -38.833 |
CORRIDOR_FLR_3 | 0.000 | 0.000 | 24.645 | -178.250 | 0.000 | 0.000 | 126.232 | 62.736 | 0.000 | 49.394 | 0.000 | 0.287 | 0.004 | 0.000 | -37.983 | 0.000 | -19.851 | -27.210 |
ROOM_1_FLR_6 | 14.585 | -9.628 | 0.000 | -4.090 | 0.000 | 0.000 | 2.444 | 5.102 | 3.073 | 13.188 | 0.000 | 0.062 | 0.000 | 0.000 | -7.750 | 0.000 | -4.328 | -12.659 |
ROOM_2_FLR_6 | 16.957 | -7.775 | 0.000 | -4.033 | 0.000 | 0.000 | 2.449 | 5.102 | 3.073 | 9.114 | 0.000 | 0.061 | 0.000 | 0.000 | -8.179 | 0.000 | -4.302 | -12.465 |
ROOM_3_MULT9_FLR_6 | 46.232 | -61.011 | 0.000 | -27.009 | 0.000 | 0.000 | 21.896 | 28.868 | 27.097 | 75.316 | 0.000 | 0.360 | 0.000 | 0.000 | -35.875 | 0.000 | -20.737 | -55.136 |
BANQUET_FLR_6 | 0.000 | 0.000 | 1.101 | -483.508 | 0.000 | 0.000 | 367.541 | 46.753 | 175.857 | 10.697 | 0.000 | 0.142 | 0.001 | 0.000 | -20.709 | 0.000 | -10.143 | -87.732 |
DINING_FLR_6 | 0.000 | 0.000 | 0.981 | -520.158 | 0.000 | 0.000 | 366.321 | 46.753 | 175.857 | 10.544 | 0.000 | 0.137 | 0.006 | 0.000 | -20.996 | 0.000 | -10.165 | -49.274 |
KITCHEN_FLR_6 | 0.000 | 0.000 | 0.016 | -635.673 | 0.000 | 0.000 | 31.634 | 12.482 | 556.656 | 26.216 | 0.000 | 0.055 | 30.855 | 0.000 | -12.786 | 0.000 | -9.455 | -0.003 |
CORRIDOR_FLR_6 | 0.000 | 0.000 | 22.775 | -70.463 | 0.000 | 0.000 | 33.768 | 16.599 | 0.000 | 24.696 | 0.000 | 0.130 | 0.000 | 0.000 | -16.576 | 0.000 | -8.678 | -2.250 |
Total Facility | 544.937 | -669.194 | 85.003 | -4695.725 | 0.000 | 0.000 | 2250.488 | 1174.112 | 2458.123 | 1057.610 | 0.000 | 6.425 | 30.896 | 0.000 | -739.165 | 0.000 | -449.295 | -1054.179 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 25-JAN-20:01 | 0.00 | 0.00 | 0.00 | -61185.08 | 0.00 | 0.00 | 6162.13 | 13517.00 | 10113.80 | 0.00 | 0.00 | 0.00 | 31392.15 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 25-JAN-20:01 | 0.00 | 0.00 | 0.00 | -7530.46 | 0.00 | 0.00 | 626.51 | 687.30 | 685.60 | 0.00 | 0.00 | 0.00 | 7608.37 | 0.00 | -1481.73 | 0.00 | -595.59 | 0.00 |
RETAIL_2_FLR_1 | 25-JAN-20:01 | 0.00 | 0.00 | 0.00 | -4891.16 | 0.00 | 0.00 | 725.55 | 795.89 | 793.93 | 0.00 | 0.00 | 0.00 | 2808.06 | 0.00 | -0.00 | 0.00 | -232.27 | 0.00 |
MECH_FLR_1 | 25-JAN-20:01 | 0.00 | 0.00 | 0.00 | -3681.00 | 0.00 | 0.00 | 153.44 | 1487.69 | 839.45 | 0.00 | 0.00 | 0.00 | 1751.85 | 0.00 | -0.00 | 0.00 | -551.43 | 0.00 |
STORAGE_FLR_1 | 25-JAN-20:01 | 0.00 | 0.00 | 0.00 | -1463.02 | 0.00 | 0.00 | 119.58 | 273.10 | 242.16 | 0.00 | 0.00 | 0.00 | 1144.60 | 0.00 | -0.00 | 0.00 | -316.42 | 0.00 |
LAUNDRY_FLR_1 | 25-JAN-20:01 | 0.00 | 0.00 | 0.00 | -76736.50 | 0.00 | 0.00 | 438.81 | 337.37 | 44299.38 | 0.00 | 0.00 | 0.00 | 32389.97 | 0.00 | -0.00 | 0.00 | -729.03 | 0.00 |
CAFE_FLR_1 | 01-JAN-00:31 | 0.00 | 0.00 | 0.00 | -35201.31 | 0.00 | 0.00 | 8229.27 | 725.74 | 406.43 | 0.00 | 0.00 | 0.00 | 31270.22 | 0.00 | -4124.14 | 0.00 | -1306.22 | 0.00 |
LOBBY_FLR_1 | 25-JAN-20:01 | 0.00 | 0.00 | 0.00 | -108737.91 | 0.00 | 0.00 | 24441.64 | 11849.32 | 10029.21 | 0.00 | 0.00 | 0.00 | 71686.66 | 0.00 | -5475.56 | 0.00 | -3793.35 | 0.00 |
ROOM_1_FLR_3 | 14-MAY-18:01 | 0.00 | -15677.03 | 0.00 | -654.20 | 0.00 | 0.00 | 283.22 | 1570.91 | 516.26 | 10213.70 | 0.00 | 0.00 | 4167.73 | 0.00 | -0.00 | 0.00 | -420.59 | 0.00 |
ROOM_2_FLR_3 | 14-MAY-18:01 | 0.00 | -14967.89 | 0.00 | -655.41 | 0.00 | 0.00 | 283.22 | 1570.72 | 516.20 | 10874.55 | 0.00 | 0.00 | 2872.26 | 0.00 | -0.00 | 0.00 | -493.64 | 0.00 |
ROOM_3_MULT19_FLR_3 | 22-OCT-12:20 | 0.00 | -70572.57 | 0.00 | -8548.54 | 0.00 | 0.00 | 0.00 | 6190.09 | 5686.12 | 102514.53 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -869.64 | -34399.99 |
ROOM_4_MULT19_FLR_3 | 17-JUN-18:02 | 0.00 | -80117.76 | 0.00 | -9793.79 | 0.00 | 0.00 | 5381.12 | 18762.99 | 9610.21 | 18794.64 | 0.00 | 767.91 | 36594.68 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 09-SEP-08:61 | 0.00 | -14426.92 | 0.00 | -516.31 | 0.00 | 0.00 | 130.71 | 879.71 | 653.23 | 12960.00 | 0.00 | 0.00 | 566.15 | 0.00 | -0.00 | 0.00 | -246.57 | 0.00 |
ROOM_6_FLR_3 | 09-SEP-08:61 | 0.00 | -13715.56 | 0.00 | -515.59 | 0.00 | 0.00 | 130.72 | 879.61 | 653.15 | 11669.71 | 0.00 | 0.00 | 1144.27 | 0.00 | -0.00 | 0.00 | -246.31 | 0.00 |
CORRIDOR_FLR_3 | 14-FEB-07:00 | 0.00 | 0.00 | 0.00 | -23114.58 | 0.00 | 0.00 | 5841.91 | 2280.18 | 0.00 | 0.00 | 0.00 | 0.00 | 21543.23 | 0.00 | -4590.98 | 0.00 | -1959.75 | 0.00 |
ROOM_1_FLR_6 | 14-MAY-18:01 | 0.00 | -4119.58 | 0.00 | -164.16 | 0.00 | 0.00 | 70.80 | 392.73 | 129.07 | 2540.81 | 0.00 | 0.00 | 1276.99 | 0.00 | -0.00 | 0.00 | -126.66 | 0.00 |
ROOM_2_FLR_6 | 14-MAY-18:01 | 0.00 | -3918.68 | 0.00 | -164.49 | 0.00 | 0.00 | 70.80 | 392.68 | 129.05 | 2705.19 | 0.00 | 0.00 | 937.07 | 0.00 | -0.00 | 0.00 | -151.62 | 0.00 |
ROOM_3_MULT9_FLR_6 | 13-APR-15:01 | 0.00 | -20381.26 | 0.00 | -1081.92 | 0.00 | 0.00 | 529.40 | 622.14 | 603.86 | 9806.60 | 0.00 | 0.00 | 10731.91 | 0.00 | -0.00 | 0.00 | -830.74 | 0.00 |
BANQUET_FLR_6 | 25-JAN-20:01 | 0.00 | 0.00 | 0.00 | -46968.42 | 0.00 | 0.00 | 14455.85 | 3823.39 | 6747.90 | 0.00 | 0.00 | 0.00 | 24853.36 | 0.00 | -2067.19 | 0.00 | -844.89 | 0.00 |
DINING_FLR_6 | 25-JAN-20:01 | 0.00 | 0.00 | 0.00 | -49517.86 | 0.00 | 0.00 | 14456.24 | 3823.39 | 6747.90 | 0.00 | 0.00 | 0.00 | 27414.08 | 0.00 | -2079.43 | 0.00 | -844.32 | 0.00 |
KITCHEN_FLR_6 | 25-JAN-20:01 | 0.00 | 0.00 | 0.00 | -55695.81 | 0.00 | 0.00 | 1178.47 | 1020.78 | 21959.95 | 0.00 | 0.00 | 0.00 | 33744.04 | 0.00 | -1451.97 | 0.00 | -755.46 | 0.00 |
CORRIDOR_FLR_6 | 25-JAN-20:01 | 0.00 | 0.00 | 0.00 | -9734.01 | 0.00 | 0.00 | 1285.66 | 1357.44 | 0.00 | 0.00 | 0.00 | 0.00 | 9734.13 | 0.00 | -1892.97 | 0.00 | -750.24 | 0.00 |
Total Facility | 25-JAN-20:01 | 0.00 | 82395.45 | 0.00 | -545336.67 | 0.00 | 0.00 | 86905.82 | 93091.76 | 133971.61 | 0.00 | 0.00 | 0.00 | 263621.98 | 0.00 | -79383.08 | 0.00 | -35266.88 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 06-JAN-13:52 | 0.00 | 0.00 | 23725.10 | 0.00 | 0.00 | 0.00 | 2408.65 | 3754.65 | 3726.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -33614.55 |
RETAIL_1_FLR_1 | 14-JAN-04:51 | 0.00 | 0.00 | 5943.47 | 0.00 | 0.00 | 0.00 | 1135.69 | 76.37 | 144.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1031.64 | 0.00 | -431.99 | -5836.23 |
RETAIL_2_FLR_1 | 06-JAN-13:52 | 0.00 | 0.00 | 3049.97 | 0.00 | 0.00 | 0.00 | 282.90 | 221.08 | 292.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -173.48 | -3672.97 |
MECH_FLR_1 | 06-JAN-13:52 | 0.00 | 0.00 | 4041.43 | 0.00 | 0.00 | 0.00 | 60.80 | 413.25 | 309.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -399.05 | -4425.70 |
STORAGE_FLR_1 | 06-JAN-13:52 | 0.00 | 0.00 | 2264.96 | 0.00 | 0.00 | 0.00 | 46.94 | 75.86 | 89.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -228.90 | -2248.08 |
LAUNDRY_FLR_1 | 14-JAN-04:51 | 0.00 | 0.00 | 28474.35 | 0.00 | 0.00 | 0.00 | 906.60 | 37.49 | 9326.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -522.60 | -38222.03 |
CAFE_FLR_1 | 11-JAN-09:51 | 0.00 | 0.00 | 16543.76 | 0.00 | 0.00 | 0.00 | 3176.09 | 967.66 | 508.04 | 12868.33 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -1034.38 | -33029.50 |
LOBBY_FLR_1 | 06-JAN-13:42 | 0.00 | 0.00 | 50656.13 | 0.00 | 0.00 | 0.00 | 9490.00 | 3291.48 | 3694.97 | 24528.27 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -2974.68 | -88686.18 |
ROOM_1_FLR_3 | 07-JAN-09:02 | 10110.95 | 281.19 | 0.00 | -281.19 | 0.00 | 0.00 | 163.33 | 879.71 | 653.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2402.59 | 0.00 | -1227.73 | -8176.89 |
ROOM_2_FLR_3 | 06-JAN-16:13 | 10086.49 | 369.33 | 0.00 | -369.33 | 0.00 | 0.00 | 266.36 | 439.80 | 273.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1947.63 | 0.00 | -1360.05 | -7758.89 |
ROOM_3_MULT19_FLR_3 | 09-JAN-05:00 | 31212.34 | 31576.77 | 0.00 | -31576.77 | 0.00 | 0.00 | 0.00 | 2063.36 | 3921.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -21751.68 | 0.00 | -9015.60 | -6429.89 |
ROOM_4_MULT19_FLR_3 | 06-JAN-16:02 | 54511.47 | 3545.50 | 0.00 | -3545.50 | 0.00 | 0.00 | 5585.73 | 5253.64 | 5099.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -15979.14 | 0.00 | -6927.32 | -47543.68 |
ROOM_5_FLR_3 | 25-DEC-16:02 | 9830.41 | 279.00 | 0.00 | -279.00 | 0.00 | 0.00 | 163.33 | 518.40 | 305.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2182.52 | 0.00 | -1042.46 | -7592.70 |
ROOM_6_FLR_3 | 06-JAN-16:02 | 9916.89 | 265.86 | 0.00 | -265.86 | 0.00 | 0.00 | 293.99 | 439.80 | 273.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2928.54 | 0.00 | -1308.20 | -6687.84 |
CORRIDOR_FLR_3 | 07-JAN-04:31 | 0.00 | 0.00 | 14394.85 | 0.00 | 0.00 | 0.00 | 7772.82 | 570.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3690.01 | 0.00 | -1446.29 | -17601.42 |
ROOM_1_FLR_6 | 25-DEC-16:13 | 2910.43 | 97.50 | 0.00 | -97.50 | 0.00 | 0.00 | 36.99 | 129.60 | 76.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -661.25 | 0.00 | -272.42 | -2219.74 |
ROOM_2_FLR_6 | 25-DEC-16:13 | 2883.70 | 94.99 | 0.00 | -94.99 | 0.00 | 0.00 | 36.99 | 129.58 | 76.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -659.07 | 0.00 | -271.35 | -2196.23 |
ROOM_3_MULT9_FLR_6 | 11-DEC-16:02 | 13823.77 | 462.81 | 0.00 | -462.81 | 0.00 | 0.00 | 661.48 | 622.14 | 603.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2435.00 | 0.00 | -1291.39 | -11984.87 |
BANQUET_FLR_6 | 20-DEC-11:41 | 0.00 | 0.00 | 17685.89 | 0.00 | 0.00 | 0.00 | 5573.08 | 1062.05 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -876.42 | 0.00 | -685.89 | -29506.61 |
DINING_FLR_6 | 20-DEC-11:41 | 0.00 | 0.00 | 18714.36 | 0.00 | 0.00 | 0.00 | 5587.35 | 1062.05 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -867.53 | 0.00 | -683.55 | -30560.58 |
KITCHEN_FLR_6 | 14-JAN-04:51 | 0.00 | 0.00 | 18716.57 | 0.00 | 0.00 | 0.00 | 2371.73 | 113.42 | 5615.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1109.98 | 0.00 | -550.11 | -25156.87 |
CORRIDOR_FLR_6 | 07-JAN-04:31 | 0.00 | 0.00 | 12329.29 | 0.00 | 0.00 | 0.00 | 2237.10 | 150.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1441.10 | 0.00 | -577.42 | -12698.71 |
Total Facility | 07-JAN-04:31 | 102402.79 | 11221.73 | 152888.76 | -11221.73 | 0.00 | 0.00 | 136104.61 | 10291.59 | 33679.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -74842.95 | 0.00 | -32673.22 | -327851.31 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:58:23
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV WITH REHEAT | 23.2509 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 23.1145 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
FLR_3_DOAS | 2.0513 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.0513 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV WITH REHEAT | 23.1113 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 23.1113 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
FLR_3_DOAS | 2.0513 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.0513 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | VAV WITH REHEAT | 0.000000 | 106.4990 | 0.000432 | 1978.83 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | 0.000000 | 10.8290 | 0.001181 | 67.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | 0.000000 | 12.5400 | 0.001181 | 77.67 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
MECH_FLR_1 | VAV WITH REHEAT | 0.000000 | 2.6520 | 0.000000 | 164.24 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | 0.000000 | 2.0400 | 0.000610 | 94.76 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | 0.000000 | 8.4000 | 0.000000 | 78.04 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | 0.000000 | 142.3000 | 0.003581 | 188.86 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | 0.000000 | 422.4350 | 0.001448 | 1308.19 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1863.81 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1864.32 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | 0.000000 | 83.8280 | 0.000305 | 1557.62 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000396 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000396 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.000000 | 13.5000 | 0.000449 | 220.77 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003581 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DINING_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003581 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | 0.000000 | 22.2380 | 0.003556 | 103.30 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | 0.000000 | 22.1800 | 0.000305 | 412.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV WITH REHEAT | 0.00 | 0.001045 | 6694.0231 | 0.0000 | 0.0000 | 0.0000 | |
FLR_3_DOAS | 0.00 | 0.000441 | 4651.2638 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.5143 | 2.5143 | 2.4992 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4616 | 0.4616 | 0.4588 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2459 | 0.2459 | 0.2444 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2398 | 0.2398 | 0.2384 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1189 | 0.1189 | 0.1182 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.3981 | 3.3981 | 3.3777 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.8462 | 1.8462 | 1.8352 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.2626 | 5.2626 | 5.2310 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8371 | 0.8371 | 0.8371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8373 | 0.8373 | 0.8373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3253 | 1.3253 | 1.3174 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0992 | 0.0992 | 0.0992 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.2752 | 2.2752 | 2.2616 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.3901 | 2.3901 | 2.3758 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.4328 | 2.4328 | 2.4182 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7399 | 0.7399 | 0.7354 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV WITH REHEAT | 23.2509 | 23.1145 | 23.2509 | 23.1113 | 0.0000 | 1.0000 |
FLR_3_DOAS | 2.0513 | 2.0513 | 2.0513 | 2.0513 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.4992 | 2.4992 | 2.4992 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4588 | 0.4588 | 0.4588 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2444 | 0.2444 | 0.2444 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2384 | 0.2384 | 0.2384 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1182 | 0.1182 | 0.1182 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.3777 | 3.3777 | 3.3777 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.8352 | 1.8352 | 1.8352 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.2310 | 5.2310 | 5.2310 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8371 | 0.8371 | 0.8371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8373 | 0.8373 | 0.8373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3174 | 1.3174 | 1.3174 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0992 | 0.0992 | 0.0992 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.2616 | 2.2616 | 2.2616 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.3758 | 2.3758 | 2.3758 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.4182 | 2.4182 | 2.4182 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7354 | 0.7354 | 0.7354 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV WITH REHEAT | 23.1113 | 23.1113 | 23.1113 | 23.1113 | 0.0000 | 1.0000 |
FLR_3_DOAS | 2.0513 | 2.0513 | 2.0513 | 2.0513 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:58:23
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** International Falls Intl Ap MN USA TMY3 WMO#=727470 |
Total gross floor area [m2] | 11345.29 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 1978.83 | 1978.83 | 0.00 | 168.00 |
RETAIL_1_FLR_1 | 67.07 | 67.07 | 0.00 | 168.00 |
RETAIL_2_FLR_1 | 77.67 | 77.67 | 0.00 | 168.00 |
MECH_FLR_1 | 164.24 | 164.24 | 0.00 | 168.00 |
STORAGE_FLR_1 | 94.76 | 94.76 | 0.00 | 168.00 |
LAUNDRY_FLR_1 | 78.04 | 78.04 | 0.00 | 168.00 |
CAFE_FLR_1 | 188.86 | 188.86 | 0.00 | 168.00 |
LOBBY_FLR_1 | 1308.19 | 1308.19 | 0.00 | 168.00 |
ROOM_1_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT19_FLR_3 | 24.52 | 24.52 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 24.53 | 24.53 | 0.00 | 168.00 |
ROOM_5_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_6_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
CORRIDOR_FLR_3 | 389.40 | 389.40 | 0.00 | 168.00 |
ROOM_1_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT9_FLR_6 | 24.53 | 24.53 | 0.00 | 168.00 |
BANQUET_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
DINING_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
KITCHEN_FLR_6 | 103.30 | 103.30 | 0.00 | 168.00 |
CORRIDOR_FLR_6 | 412.12 | 412.12 | 0.00 | 168.00 |
Totals | 11345.29 | 11345.29 | 0.00 |
Data | |
Number of hours heating loads not met | 1156.83 |
Number of hours cooling loads not met | 8.83 |
Number of hours not met | 1165.67 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 4819.26 | 1111818.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 985.56 | 301034.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 1174.11 | 93091.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 261.66 | 16690.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 959.56 | 59492.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 762.04 | 29240.64 | 1198.64 | 74976.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 16.27 | 515.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 13.43 | 425.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Laundry | 0.00 | 0.00 | 590.20 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 32.92 | 1912.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 616.11 | 37691.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 30.65 | 972.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 1919.11 | 92214.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 189.78 | 13486.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- General | 510.50 | 18156.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 90.81 | 4755.74 | 3565.50 | 314232.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 18.27 | 2271.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 21.83 | 1889.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 32.56 | 1199.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 1823.96 | 7635.18 |
Natural Gas | 1788.84 | 10173.60 |
Additional | 0.00 | 0.00 |
Total | 3612.80 | 17808.78 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 103.49 |
Space Heating | 0.00 |
Space Cooling | 86.87 |
Fans (All) | 169.15 |
Service Water Heating | 8.00 |
Receptacle Equipment | 154.36 |
Miscellaneous (All) | 672.98 |
Subtotal | 672.98 |
Natural Gas [MJ/m2] | |
Space Heating | 424.78 |
Service Water Heating | 314.27 |
Miscellaneous (All) | 896.73 |
Subtotal | 896.73 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 6.59 |
Space Heating | 27.06 |
Space Cooling | 5.53 |
Fans (All) | 10.78 |
Service Water Heating | 20.53 |
Receptacle Equipment | 19.88 |
Miscellaneous | 9.63 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_KITCHEN | 3061. | 8760. |
LTG_SCH_DINING | 3061. | 8760. |
LTG_SCH_BASEMENT | 2655. | 8760. |
LTG_SCH_LOBBY | 3061. | 8760. |
LTG_SCH_STORAGE | 1339. | 8760. |
LTG_SCH_MECHANIC | 3061. | 8760. |
LTG_SCH_LAUNDRY | 2678. | 8760. |
LTG_SCH_GUESTROOM | 3599. | 8760. |
LTG_SCH_CORRIDOR | 3061. | 8760. |
LTG_SCH_RETAIL | 2678. | 8760. |
WALKIN_OCC_LGHT_SCH_1 | 3061. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
BASEMENT_EQUIP_SCH | 3924. | 8760. |
BLDG_EQUIP_SCH | 3924. | 8760. |
GUESTROOM_EQP_SCH_BASE | 3239. | 8760. |
GUESTROOM_EQP_SCH_ADVA | 2762. | 8760. |
LOBBY_EQP_SCH | 3292. | 8760. |
OFFICE_EQP_SCH | 4941. | 8760. |
EMPLOYEELOUNGE_EQP_SCH | 4044. | 8760. |
LAUNDRYROOM_EQP_ELEC_SCH | 2920. | 2920. |
LAUNDRYROOM_EQP_GAS_SCH | 2920. | 2920. |
MEETINGROOM_EQP_SCH | 1336. | 4745. |
EXERCISEROOM_EQP_SCH | 3832. | 5840. |
KITCHEN_ELEC_EQUIP_SCH | 2172. | 8760. |
KITCHEN_GAS_EQUIP_SCH | 1332. | 8760. |
KITCHEN_EXHAUST_SCH | 6205. | 6205. |
BLDG_ELEVATORS | 2270. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_OCC_SCH | 5026. | 8760. |
GUESTROOM_OCC_SCH | 5515. | 8760. |
LOBBY_OCC_SCH | 2304. | 8760. |
OFFICE_OCC_SCH | 3954. | 8760. |
EMPLOYEELOUNGE_OCC_SCH | 948. | 5475. |
MEETINGROOM_OCC_SCH | 1168. | 4745. |
LAUNDRYROOM_OCC_SCH | 427. | 2920. |
EXERCISEROOM_OCC_SCH | 5292. | 5840. |
INFIL_SCH | 8760. | 8760. |
INFIL_HALF_ON_SCH | 4380. | 8760. |
INFIL_QUARTER_ON_SCH | 2190. | 8760. |
LAUNDRY_SWH_SCH | 2555. | 2555. |
BLDG_SWH_SCH | 3301. | 8760. |
GUESTROOM_SWH_SCH | 2899. | 8760. |
LAUNDRYROOM_SWH_SCH | 2920. | 2920. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
ALWAYS_ON | 8760. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
OCC_GUESTROOM_VENT_CTRL_30MIN | 6570. | 6570. |
OCC_GUESTROOM_VENT_CTRL_20MIN | 6327. | 6327. |
VAC_GUESTROOM_VENTILATION_SCHEDULE | 365. | 365. |
MINOA_MOTORIZEDDAMPER_SCHED | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
ROOM_1_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
FLR_3_DOAS_OAMINOAFRACSCHEDULE | 8760. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 0. | 0. |
LAUNDRY_FLR_1 EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 0. | 0. |
SLIDING_DOORS_VENTILATION_AVAILABILITY_SCH | 3285. | 3285. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
VACGUESTROOM_HTGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 18.89 | 365 | 18.89 | 365 |
VACGUESTROOM_CLGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 23.33 | 365 |
OBCRESET_S_OCCGUESTROOM_HTGSP_SCH_30MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_S_OCCGUESTROOM_CLGSP_SCH_30MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_HTGSP_SCH_30MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_CLGSP_SCH_30MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
HTGSETP_SCH | BASEMENT DUAL SP CONTROL | January | 21.00 | 365 | 21.00 | 365 |
CLGSETP_SCH | BASEMENT DUAL SP CONTROL | July | 24.00 | 365 | 24.00 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:58:23
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Average | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Sum | 192720.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 529331.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 50179.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 59156.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8977.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 5588.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 37203.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 710417.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 2115429.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 100358.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 108269.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 105946.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 2115429.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Average | 288887.05 | 0.00 | 0.00 | 0.00 | 0.00 |
Sum | 6355515.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8759.83 | 0.17 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8759.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 0.17 | 0.00 | 0.00 | 0.00 |
Average | 8759.99 | 0.01 | 0.00 | 0.00 | 0.00 |
Sum | 192719.83 | 0.17 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 529331.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 50179.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 59156.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8977.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 5588.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 37203.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 710417.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 2115429.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 100358.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 108269.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 105946.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 2115429.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Average | 288887.05 | 0.00 | 0.00 | 0.00 | 0.00 |
Sum | 6355515.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:58:23
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:58:23
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2012
For: Environment
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
For: Environment
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 7
For: Environment
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_INTERNATIONALFALLS
For: Environment
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.407084E+11 | 61186.05 | 25-JAN-20:01 | -24.0 | -24.2 | 0.444976E+10 | 3787.43 | 24-JAN-22:10 | -24.0 | -24.2 |
February | 0.303951E+11 | 60690.85 | 14-FEB-07:00 | -33.3 | -33.4 | 0.504982E+10 | 3745.29 | 10-FEB-22:10 | -33.3 | -33.4 |
March | 0.277228E+11 | 57889.85 | 12-MAR-03:51 | -23.9 | -24.1 | 0.599830E+10 | 3669.85 | 01-MAR-22:10 | -23.9 | -24.1 |
April | 0.256067E+11 | 17382.20 | 20-APR-20:00 | 5.60 | 0.14 | 0.590111E+10 | 3617.36 | 26-APR-21:10 | 0.00 | -0.6 |
May | 0.290619E+11 | 18415.59 | 10-MAY-20:00 | 21.10 | 12.38 | 0.610462E+10 | 3637.96 | 09-MAY-21:10 | 21.10 | 12.38 |
June | 0.306494E+11 | 19546.51 | 21-JUN-20:00 | 21.10 | 16.45 | 0.592631E+10 | 3674.48 | 09-JUN-21:10 | 21.10 | 16.45 |
July | 0.362040E+11 | 20718.10 | 20-JUL-19:10 | 26.32 | 20.51 | 0.612267E+10 | 3736.40 | 07-JUL-22:10 | 26.32 | 20.51 |
August | 0.405429E+11 | 21427.79 | 24-AUG-18:03 | 23.35 | 17.47 | 0.620130E+10 | 3815.48 | 17-AUG-21:10 | 23.35 | 17.47 |
September | 0.409971E+11 | 20862.70 | 07-SEP-18:10 | 20.40 | 14.21 | 0.603824E+10 | 3861.02 | 28-SEP-21:10 | 6.70 | 6.21 |
October | 0.427892E+11 | 20232.83 | 19-OCT-18:10 | 16.32 | 11.39 | 0.627363E+10 | 3892.28 | 13-OCT-21:10 | 16.32 | 11.39 |
November | 0.404548E+11 | 19485.91 | 01-NOV-20:00 | 13.30 | 11.34 | 0.605423E+10 | 3891.86 | 10-NOV-22:10 | -5.3 | -7.3 |
December | 0.426833E+11 | 56453.61 | 24-DEC-06:05 | -31.1 | -31.3 | 0.505700E+10 | 3851.62 | 08-DEC-22:10 | -31.1 | -31.3 |
Annual Sum or Average | 0.427816E+12 | 0.691770E+11 | ||||||||
Minimum of Months | 0.256067E+11 | 17382.20 | -33.3 | -33.4 | 0.444976E+10 | 3617.36 | -33.3 | -33.4 | ||
Maximum of Months | 0.427892E+11 | 61186.05 | 26.32 | 20.51 | 0.627363E+10 | 3892.28 | 26.32 | 20.51 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.160494E+10 | 7530.87 | 25-JAN-20:01 | -24.0 | -24.2 | 0.448638E+09 | 364.29 | 18-JAN-04:30 | -24.0 | -24.2 |
February | 0.174792E+10 | 5513.01 | 01-FEB-18:11 | -23.9 | -24.3 | 0.500496E+09 | 364.30 | 07-FEB-03:20 | -8.5 | -8.8 |
March | 0.191169E+10 | 6152.52 | 12-MAR-03:51 | -23.9 | -24.1 | 0.605334E+09 | 364.30 | 02-MAR-03:20 | -23.9 | -24.1 |
April | 0.284562E+10 | 4151.52 | 18-APR-10:35 | 17.57 | 11.16 | 0.602955E+09 | 364.29 | 04-APR-03:30 | 17.57 | 11.16 |
May | 0.440447E+10 | 3938.52 | 18-MAY-15:13 | 28.77 | 16.51 | 0.622584E+09 | 364.29 | 13-MAY-01:19 | 28.77 | 16.51 |
June | 0.472227E+10 | 3975.87 | 30-JUN-15:15 | 32.03 | 24.56 | 0.603020E+09 | 364.33 | 01-JUN-00:00 | 32.03 | 24.56 |
July | 0.550565E+10 | 4263.94 | 23-JUL-10:35 | 27.77 | 23.32 | 0.621640E+09 | 364.27 | 28-JUL-01:00 | 12.20 | 11.93 |
August | 0.521318E+10 | 4378.20 | 25-AUG-10:35 | 24.27 | 17.99 | 0.625408E+09 | 364.29 | 19-AUG-04:19 | 24.27 | 17.99 |
September | 0.402900E+10 | 4336.27 | 01-SEP-10:40 | 22.77 | 18.04 | 0.603949E+09 | 364.30 | 08-SEP-04:10 | 10.00 | 9.44 |
October | 0.248730E+10 | 4718.98 | 22-OCT-10:35 | 15.20 | 11.90 | 0.623414E+09 | 364.31 | 05-OCT-00:40 | 15.20 | 11.90 |
November | 0.106964E+10 | 4102.47 | 17-NOV-11:40 | 8.17 | 2.57 | 0.599851E+09 | 364.31 | 06-NOV-04:10 | 8.17 | 2.57 |
December | 0.121748E+10 | 4958.76 | 23-DEC-21:41 | -23.9 | -24.3 | 0.485398E+09 | 364.29 | 07-DEC-01:00 | -23.9 | -24.3 |
Annual Sum or Average | 0.367592E+11 | 0.694269E+10 | ||||||||
Minimum of Months | 0.106964E+10 | 3938.52 | -24.0 | -24.3 | 0.448638E+09 | 364.27 | -24.0 | -24.3 | ||
Maximum of Months | 0.550565E+10 | 7530.87 | 32.03 | 24.56 | 0.625408E+09 | 364.33 | 32.03 | 24.56 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.227848E+10 | 4891.28 | 25-JAN-20:01 | -24.0 | -24.2 | 0.537046E+09 | 421.70 | 03-JAN-05:40 | -24.0 | -24.2 |
February | 0.194432E+10 | 4286.48 | 24-FEB-22:51 | -23.9 | -24.3 | 0.592759E+09 | 426.34 | 22-FEB-22:10 | -23.9 | -24.3 |
March | 0.235444E+10 | 4565.27 | 12-MAR-03:51 | -23.9 | -24.1 | 0.705736E+09 | 437.44 | 31-MAR-21:19 | 4.83 | 0.87 |
April | 0.288022E+10 | 1956.55 | 13-APR-18:03 | 16.93 | 6.60 | 0.698529E+09 | 451.18 | 13-APR-21:40 | 12.23 | 6.51 |
May | 0.364146E+10 | 2175.52 | 18-MAY-18:10 | 27.25 | 15.75 | 0.728252E+09 | 467.14 | 25-MAY-22:10 | 21.73 | 16.39 |
June | 0.371134E+10 | 2232.21 | 29-JUN-18:10 | 32.52 | 24.04 | 0.708421E+09 | 473.20 | 30-JUN-21:40 | 19.60 | 16.44 |
July | 0.403748E+10 | 2201.56 | 24-JUL-18:10 | 27.85 | 19.74 | 0.731218E+09 | 468.45 | 21-JUL-22:10 | 27.85 | 19.74 |
August | 0.390148E+10 | 2122.78 | 24-AUG-18:10 | 23.35 | 17.47 | 0.732244E+09 | 465.11 | 08-AUG-22:10 | 23.35 | 17.47 |
September | 0.340227E+10 | 1993.48 | 07-SEP-18:01 | 20.40 | 14.21 | 0.701259E+09 | 461.55 | 01-SEP-21:40 | 20.40 | 14.21 |
October | 0.294056E+10 | 1928.42 | 19-OCT-18:10 | 16.32 | 11.39 | 0.720133E+09 | 451.84 | 19-OCT-21:40 | 12.40 | 9.83 |
November | 0.221040E+10 | 1745.50 | 01-NOV-20:00 | 13.30 | 11.34 | 0.694219E+09 | 432.69 | 01-NOV-21:19 | 12.43 | 11.31 |
December | 0.216110E+10 | 4196.26 | 23-DEC-21:41 | -23.9 | -24.3 | 0.582568E+09 | 421.70 | 16-DEC-04:49 | -23.9 | -24.3 |
Annual Sum or Average | 0.354635E+11 | 0.813238E+10 | ||||||||
Minimum of Months | 0.194432E+10 | 1745.50 | -24.0 | -24.3 | 0.537046E+09 | 421.70 | -24.0 | -24.3 | ||
Maximum of Months | 0.403748E+10 | 4891.28 | 32.52 | 24.04 | 0.732244E+09 | 473.20 | 27.85 | 19.74 |
Report: ZoneCoolingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.125135E+10 | 3681.04 | 25-JAN-20:01 | -24.0 | -24.2 | 0.110264E+09 | 89.15 | 25-JAN-04:49 | -24.0 | -24.2 |
February | 0.766884E+09 | 3317.39 | 24-FEB-22:51 | -23.9 | -24.3 | 0.125736E+09 | 89.15 | 07-FEB-04:40 | -23.9 | -24.3 |
March | 0.723055E+09 | 3489.36 | 12-MAR-03:51 | -23.9 | -24.1 | 0.149911E+09 | 89.15 | 17-MAR-02:30 | -5.0 | -6.2 |
April | 0.148465E+10 | 1729.82 | 13-APR-20:00 | 14.40 | 6.82 | 0.147068E+09 | 89.76 | 13-APR-21:10 | 13.03 | 6.68 |
May | 0.281325E+10 | 2057.12 | 25-MAY-18:02 | 29.03 | 19.14 | 0.152494E+09 | 94.30 | 25-MAY-22:10 | 21.73 | 16.39 |
June | 0.320253E+10 | 2161.67 | 29-JUN-18:10 | 32.52 | 24.04 | 0.148361E+09 | 96.46 | 30-JUN-22:10 | 18.85 | 15.86 |
July | 0.358313E+10 | 2120.24 | 24-JUL-18:03 | 27.85 | 19.74 | 0.152851E+09 | 95.28 | 21-JUL-22:10 | 27.85 | 19.74 |
August | 0.329026E+10 | 2045.52 | 09-AUG-18:10 | 26.52 | 20.82 | 0.153173E+09 | 94.35 | 08-AUG-21:19 | 26.52 | 20.82 |
September | 0.253927E+10 | 1890.02 | 01-SEP-18:10 | 23.07 | 17.74 | 0.147172E+09 | 93.31 | 01-SEP-21:10 | 14.82 | 14.12 |
October | 0.169619E+10 | 1729.09 | 19-OCT-20:00 | 13.30 | 10.24 | 0.151775E+09 | 90.06 | 19-OCT-21:10 | 12.70 | 9.80 |
November | 0.755704E+09 | 1554.44 | 01-NOV-20:00 | 13.30 | 11.34 | 0.146741E+09 | 89.15 | 10-NOV-04:40 | -5.7 | -7.6 |
December | 0.110106E+10 | 3183.18 | 02-DEC-00:31 | -23.9 | -24.2 | 0.122647E+09 | 89.15 | 08-DEC-02:00 | -18.3 | -18.7 |
Annual Sum or Average | 0.232073E+11 | 0.170819E+10 | ||||||||
Minimum of Months | 0.723055E+09 | 1554.44 | -24.0 | -24.3 | 0.110264E+09 | 89.15 | -24.0 | -24.3 | ||
Maximum of Months | 0.358313E+10 | 3681.04 | 32.52 | 24.04 | 0.153173E+09 | 96.46 | 27.85 | 20.82 |
Report: ZoneCoolingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.413460E+09 | 1463.03 | 25-JAN-20:01 | -24.0 | -24.2 | 83918582.69 | 68.58 | 21-JAN-04:00 | -24.0 | -24.2 |
February | 0.229918E+09 | 1315.59 | 24-FEB-22:51 | -23.9 | -24.3 | 96190180.85 | 68.58 | 22-FEB-02:39 | -23.9 | -24.3 |
March | 0.125416E+09 | 1418.97 | 12-MAR-03:51 | -23.9 | -24.1 | 0.115350E+09 | 68.58 | 17-MAR-02:20 | -4.6 | -5.9 |
April | 0.347425E+09 | 642.47 | 23-APR-20:00 | 21.70 | 14.26 | 0.113125E+09 | 68.58 | 04-APR-00:40 | 21.70 | 14.26 |
May | 0.109859E+10 | 943.27 | 25-MAY-19:05 | 26.83 | 18.34 | 0.116965E+09 | 70.16 | 25-MAY-22:10 | 21.73 | 16.39 |
June | 0.138190E+10 | 1032.72 | 29-JUN-18:20 | 32.23 | 23.87 | 0.113533E+09 | 71.82 | 29-JUN-22:10 | 26.60 | 23.41 |
July | 0.159823E+10 | 966.13 | 20-JUL-19:10 | 26.32 | 20.51 | 0.116809E+09 | 70.82 | 21-JUL-22:10 | 21.60 | 20.03 |
August | 0.140726E+10 | 910.90 | 09-AUG-19:40 | 24.07 | 20.17 | 0.117230E+09 | 70.15 | 08-AUG-22:10 | 24.07 | 20.17 |
September | 0.934343E+09 | 826.30 | 01-SEP-21:00 | 15.00 | 14.30 | 0.113072E+09 | 68.91 | 01-SEP-21:40 | 14.27 | 13.58 |
October | 0.405077E+09 | 603.94 | 19-OCT-21:00 | 12.80 | 9.78 | 0.116746E+09 | 68.58 | 05-OCT-00:40 | 12.80 | 9.78 |
November | 76296231.24 | 467.77 | 01-NOV-21:00 | 12.80 | 11.56 | 0.112879E+09 | 68.58 | 30-NOV-23:00 | -8.4 | -9.8 |
December | 0.359765E+09 | 1271.89 | 02-DEC-00:31 | -23.9 | -24.2 | 93504631.58 | 68.58 | 01-DEC-05:00 | -23.9 | -24.2 |
Annual Sum or Average | 0.837769E+10 | 0.130932E+10 | ||||||||
Minimum of Months | 76296231.24 | 467.77 | -24.0 | -24.3 | 83918582.69 | 68.58 | -24.0 | -24.3 | ||
Maximum of Months | 0.159823E+10 | 1463.03 | 32.23 | 23.87 | 0.117230E+09 | 71.82 | 26.60 | 23.41 |
Report: ZoneCoolingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.476160E+11 | 76756.90 | 25-JAN-20:01 | -24.0 | -24.2 | 0.374365E+09 | 381.88 | 19-JAN-22:10 | -24.0 | -24.2 |
February | 0.430412E+11 | 57669.52 | 13-FEB-21:21 | -23.9 | -24.3 | 0.409149E+09 | 381.89 | 21-FEB-22:10 | -3.0 | -4.4 |
March | 0.484601E+11 | 54946.36 | 05-MAR-01:41 | -23.8 | -24.0 | 0.496964E+09 | 381.91 | 28-MAR-21:10 | 0.22 | -1.8 |
April | 0.483493E+11 | 36423.53 | 14-APR-20:00 | 10.60 | 5.71 | 0.494660E+09 | 381.91 | 25-APR-21:10 | 4.40 | 2.88 |
May | 0.519001E+11 | 37236.25 | 18-MAY-20:00 | 21.10 | 14.14 | 0.510430E+09 | 384.29 | 19-MAY-21:10 | 12.62 | 10.23 |
June | 0.509997E+11 | 37566.83 | 28-JUN-20:00 | 25.00 | 19.70 | 0.494243E+09 | 382.09 | 16-JUN-21:10 | 25.00 | 19.70 |
July | 0.528707E+11 | 37360.32 | 20-JUL-20:00 | 24.40 | 20.23 | 0.507094E+09 | 382.87 | 17-JUL-21:10 | 24.40 | 20.23 |
August | 0.525695E+11 | 37145.69 | 08-AUG-20:00 | 25.00 | 20.33 | 0.511474E+09 | 382.56 | 02-AUG-21:10 | 25.00 | 20.33 |
September | 0.496963E+11 | 36949.83 | 01-SEP-20:00 | 16.70 | 15.32 | 0.493911E+09 | 382.13 | 08-SEP-21:10 | 11.70 | 7.31 |
October | 0.499137E+11 | 36376.78 | 19-OCT-20:00 | 13.30 | 10.24 | 0.511143E+09 | 382.25 | 19-OCT-21:10 | 12.70 | 9.80 |
November | 0.468788E+11 | 35994.93 | 01-NOV-20:00 | 13.30 | 11.34 | 0.494609E+09 | 381.91 | 21-NOV-22:10 | -0.7 | -2.5 |
December | 0.474551E+11 | 57243.60 | 23-DEC-21:41 | -23.9 | -24.3 | 0.401440E+09 | 381.88 | 05-DEC-22:10 | -23.9 | -24.3 |
Annual Sum or Average | 0.589751E+12 | 0.569948E+10 | ||||||||
Minimum of Months | 0.430412E+11 | 35994.93 | -24.0 | -24.3 | 0.374365E+09 | 381.88 | -24.0 | -24.3 | ||
Maximum of Months | 0.528707E+11 | 76756.90 | 25.00 | 20.33 | 0.511474E+09 | 384.29 | 25.00 | 20.33 |
Report: ZoneCoolingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.155599E+11 | 35204.76 | 01-JAN-00:31 | -24.1 | -24.4 | 0.611664E+10 | 4790.46 | 24-JAN-01:39 | -16.3 | -16.7 |
February | 0.158804E+11 | 27633.55 | 17-FEB-00:01 | -23.8 | -24.1 | 0.664032E+10 | 4791.05 | 13-FEB-05:10 | -23.8 | -24.1 |
March | 0.184930E+11 | 29903.61 | 12-MAR-03:51 | -23.9 | -24.1 | 0.796957E+10 | 4790.75 | 06-MAR-04:00 | -23.9 | -24.1 |
April | 0.214372E+11 | 15264.36 | 22-APR-10:35 | 14.43 | 5.29 | 0.791931E+10 | 4989.11 | 13-APR-21:30 | 14.43 | 5.29 |
May | 0.258584E+11 | 15118.82 | 18-MAY-15:13 | 28.77 | 16.51 | 0.818694E+10 | 5077.10 | 25-MAY-21:30 | 22.35 | 16.43 |
June | 0.261842E+11 | 15167.65 | 30-JUN-15:15 | 32.03 | 24.56 | 0.794028E+10 | 5168.37 | 29-JUN-21:40 | 32.03 | 24.56 |
July | 0.286079E+11 | 15439.26 | 24-JUL-15:13 | 29.23 | 19.07 | 0.818226E+10 | 5105.89 | 21-JUL-21:40 | 29.23 | 19.07 |
August | 0.280338E+11 | 16202.91 | 25-AUG-15:13 | 28.30 | 19.27 | 0.822627E+10 | 5125.97 | 08-AUG-21:30 | 28.30 | 19.27 |
September | 0.245666E+11 | 16218.06 | 23-SEP-10:35 | 12.77 | 8.41 | 0.793110E+10 | 5053.11 | 07-SEP-21:30 | 12.77 | 8.41 |
October | 0.208247E+11 | 17989.07 | 22-OCT-10:35 | 15.20 | 11.90 | 0.818795E+10 | 5054.54 | 19-OCT-21:30 | 15.20 | 11.90 |
November | 0.153963E+11 | 15491.64 | 17-NOV-11:40 | 8.17 | 2.57 | 0.788436E+10 | 4789.92 | 27-NOV-03:49 | -7.1 | -7.5 |
December | 0.139851E+11 | 24869.83 | 23-DEC-21:41 | -23.9 | -24.3 | 0.655610E+10 | 4791.09 | 16-DEC-05:40 | -23.9 | -24.3 |
Annual Sum or Average | 0.254827E+12 | 0.917411E+11 | ||||||||
Minimum of Months | 0.139851E+11 | 15118.82 | -24.1 | -24.4 | 0.611664E+10 | 4789.92 | -23.9 | -24.3 | ||
Maximum of Months | 0.286079E+11 | 35204.76 | 32.03 | 24.56 | 0.822627E+10 | 5168.37 | 32.03 | 24.56 |
Report: ZoneCoolingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.601029E+11 | 108741.35 | 25-JAN-20:01 | -24.0 | -24.2 | 0.183912E+11 | 14327.68 | 19-JAN-22:40 | -24.0 | -24.2 |
February | 0.550738E+11 | 92844.76 | 24-FEB-22:51 | -23.9 | -24.3 | 0.199925E+11 | 14784.44 | 28-FEB-22:40 | -0.4 | -3.3 |
March | 0.637856E+11 | 100723.23 | 12-MAR-03:51 | -23.9 | -24.1 | 0.237956E+11 | 15106.17 | 31-MAR-21:40 | 4.67 | 0.78 |
April | 0.710585E+11 | 41727.87 | 13-APR-18:01 | 16.93 | 6.60 | 0.236215E+11 | 15538.45 | 13-APR-21:40 | 12.23 | 6.51 |
May | 0.831696E+11 | 46025.31 | 18-MAY-18:05 | 27.25 | 15.75 | 0.247319E+11 | 15920.73 | 25-MAY-22:10 | 21.73 | 16.39 |
June | 0.836821E+11 | 47300.08 | 29-JUN-18:10 | 32.52 | 24.04 | 0.241337E+11 | 16134.48 | 29-JUN-22:10 | 26.60 | 23.41 |
July | 0.896038E+11 | 46587.30 | 24-JUL-18:10 | 27.85 | 19.74 | 0.249208E+11 | 16023.34 | 21-JUL-22:10 | 27.85 | 19.74 |
August | 0.878434E+11 | 45024.29 | 24-AUG-18:10 | 23.35 | 17.47 | 0.249899E+11 | 15967.51 | 08-AUG-21:40 | 23.35 | 17.47 |
September | 0.794269E+11 | 42521.59 | 01-SEP-18:10 | 23.07 | 17.74 | 0.238269E+11 | 15821.49 | 01-SEP-21:40 | 14.27 | 13.58 |
October | 0.723906E+11 | 41365.17 | 19-OCT-18:10 | 16.32 | 11.39 | 0.243790E+11 | 15618.48 | 19-OCT-21:40 | 12.40 | 9.83 |
November | 0.594643E+11 | 37453.56 | 01-NOV-20:00 | 13.30 | 11.34 | 0.234315E+11 | 14995.39 | 01-NOV-21:40 | 12.07 | 11.05 |
December | 0.579026E+11 | 90756.25 | 23-DEC-21:41 | -23.9 | -24.3 | 0.198213E+11 | 14337.76 | 05-DEC-22:40 | -23.9 | -24.3 |
Annual Sum or Average | 0.863504E+12 | 0.276036E+12 | ||||||||
Minimum of Months | 0.550738E+11 | 37453.56 | -24.0 | -24.3 | 0.183912E+11 | 14327.68 | -24.0 | -24.3 | ||
Maximum of Months | 0.896038E+11 | 108741.35 | 32.52 | 24.04 | 0.249899E+11 | 16134.48 | 27.85 | 23.41 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 20869061.72 | 1196.06 | 27-JAN-16:01 | -14.8 | -15.9 | 92374468.71 | 56.69 | 14-JAN-05:19 | -14.8 | -15.9 |
February | 96076075.80 | 3917.08 | 27-FEB-16:01 | -7.8 | -10.1 | 84693571.45 | 56.69 | 13-FEB-05:30 | -7.8 | -10.1 |
March | 0.267463E+09 | 3993.26 | 26-MAR-15:01 | 10.68 | 5.32 | 94864833.35 | 56.69 | 07-MAR-05:30 | 10.68 | 5.32 |
April | 0.744660E+09 | 4072.56 | 13-APR-15:01 | 20.00 | 8.11 | 93549041.92 | 56.69 | 13-APR-21:10 | 13.03 | 6.68 |
May | 0.169403E+10 | 4082.78 | 14-MAY-18:01 | 19.63 | 8.56 | 98494189.25 | 56.70 | 25-MAY-22:10 | 21.73 | 16.39 |
June | 0.195119E+10 | 4065.87 | 16-JUN-15:02 | 21.70 | 11.70 | 95459403.96 | 56.70 | 28-JUN-22:10 | 22.20 | 18.74 |
July | 0.242955E+10 | 3887.19 | 04-JUL-15:02 | 23.90 | 20.01 | 98801641.87 | 56.70 | 20-JUL-22:10 | 20.22 | 18.82 |
August | 0.197912E+10 | 3818.70 | 30-AUG-15:02 | 25.50 | 20.16 | 98611328.09 | 56.70 | 25-AUG-21:10 | 25.50 | 20.16 |
September | 0.113689E+10 | 4068.96 | 05-SEP-15:01 | 17.12 | 10.02 | 94709004.39 | 56.69 | 01-SEP-23:49 | 17.12 | 10.02 |
October | 0.440067E+09 | 4008.57 | 26-OCT-15:01 | 14.40 | 8.04 | 95778212.47 | 56.69 | 19-OCT-22:10 | 14.40 | 8.04 |
November | 70637456.38 | 3878.60 | 17-NOV-16:01 | 9.45 | 2.90 | 90786205.27 | 56.69 | 01-NOV-04:49 | 9.45 | 2.90 |
December | 15919243.01 | 614.84 | 28-DEC-16:04 | -2.2 | -3.9 | 92315230.35 | 56.69 | 11-DEC-22:19 | -2.2 | -3.9 |
Annual Sum or Average | 0.108465E+11 | 0.113044E+10 | ||||||||
Minimum of Months | 15919243.01 | 614.84 | -14.8 | -15.9 | 84693571.45 | 56.69 | -14.8 | -15.9 | ||
Maximum of Months | 0.242955E+10 | 4082.78 | 25.50 | 20.16 | 98801641.87 | 56.70 | 25.50 | 20.16 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 7337906.28 | 615.18 | 06-JAN-08:61 | -35.1 | -35.2 | 91886448.57 | 56.69 | 31-JAN-23:00 | -23.2 | -23.6 |
February | 33556348.11 | 3273.07 | 28-FEB-16:02 | 6.02 | 1.46 | 83743179.62 | 56.69 | 01-FEB-00:10 | 6.02 | 1.46 |
March | 0.132415E+09 | 3748.25 | 26-MAR-18:01 | 8.53 | 4.25 | 93655303.19 | 56.69 | 07-MAR-02:09 | 8.53 | 4.25 |
April | 0.497405E+09 | 3837.95 | 13-APR-15:01 | 20.00 | 8.11 | 92693684.20 | 56.69 | 13-APR-21:00 | 11.70 | 6.37 |
May | 0.146525E+10 | 3905.80 | 14-MAY-18:01 | 19.63 | 8.56 | 98243155.74 | 56.70 | 25-MAY-22:10 | 21.73 | 16.39 |
June | 0.181803E+10 | 3870.83 | 16-JUN-15:02 | 21.70 | 11.70 | 95400230.63 | 56.70 | 28-JUN-22:10 | 22.20 | 18.74 |
July | 0.222067E+10 | 3729.95 | 21-JUL-18:02 | 24.90 | 20.99 | 98759381.69 | 56.70 | 21-JUL-21:40 | 21.70 | 20.13 |
August | 0.167582E+10 | 3700.46 | 29-AUG-15:02 | 25.50 | 20.26 | 98457211.86 | 56.70 | 08-AUG-21:10 | 25.50 | 20.26 |
September | 0.817463E+09 | 3868.56 | 06-SEP-15:01 | 20.00 | 11.79 | 94239155.21 | 56.69 | 01-SEP-22:40 | 20.00 | 11.79 |
October | 0.230573E+09 | 3756.15 | 26-OCT-15:01 | 14.40 | 8.04 | 94959974.71 | 56.69 | 20-OCT-21:19 | 14.40 | 8.04 |
November | 40136084.85 | 1858.97 | 17-NOV-16:01 | 9.45 | 2.90 | 89974250.48 | 56.69 | 01-NOV-21:19 | 9.45 | 2.90 |
December | 6777095.27 | 577.81 | 24-DEC-08:61 | -31.1 | -31.3 | 92176629.25 | 56.69 | 12-DEC-22:19 | -31.1 | -31.3 |
Annual Sum or Average | 0.894543E+10 | 0.112419E+10 | ||||||||
Minimum of Months | 6777095.27 | 577.81 | -35.1 | -35.2 | 83743179.62 | 56.69 | -31.1 | -31.3 | ||
Maximum of Months | 0.222067E+10 | 3905.80 | 25.50 | 20.99 | 98759381.69 | 56.70 | 25.50 | 20.26 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 98914360.61 | 377.85 | 05-JAN-11:10 | -29.7 | -29.9 | 0.00 | 0.00 | 01-JAN-00:10 | -29.7 | -29.9 |
February | 0.183131E+09 | 619.33 | 22-FEB-14:00 | -0.6 | -3.9 | 0.00 | 0.00 | 01-FEB-00:10 | -0.6 | -3.9 |
March | 0.287041E+09 | 717.63 | 20-MAR-12:30 | 1.70 | -1.1 | 0.00 | 0.00 | 01-MAR-00:10 | 1.70 | -1.1 |
April | 0.489366E+09 | 784.40 | 13-APR-13:00 | 17.80 | 6.75 | 0.00 | 0.00 | 01-APR-00:10 | 17.80 | 6.75 |
May | 0.713335E+09 | 755.34 | 18-MAY-13:10 | 28.25 | 16.75 | 0.00 | 0.00 | 01-MAY-00:10 | 28.25 | 16.75 |
June | 0.745303E+09 | 741.61 | 30-JUN-13:00 | 31.70 | 24.46 | 0.00 | 0.00 | 01-JUN-00:10 | 31.70 | 24.46 |
July | 0.893385E+09 | 795.74 | 23-JUL-13:20 | 30.00 | 22.71 | 0.00 | 0.00 | 01-JUL-00:10 | 30.00 | 22.71 |
August | 0.847360E+09 | 861.94 | 26-AUG-12:40 | 25.40 | 19.23 | 0.00 | 0.00 | 01-AUG-00:10 | 25.40 | 19.23 |
September | 0.681443E+09 | 871.54 | 01-SEP-13:10 | 24.60 | 17.97 | 0.00 | 0.00 | 01-SEP-00:10 | 24.60 | 17.97 |
October | 0.474430E+09 | 1041.05 | 22-OCT-12:20 | 17.23 | 12.76 | 0.00 | 0.00 | 01-OCT-00:10 | 17.23 | 12.76 |
November | 0.198723E+09 | 676.64 | 17-NOV-12:20 | 9.27 | 3.02 | 0.00 | 0.00 | 01-NOV-00:10 | 9.27 | 3.02 |
December | 62489646.90 | 363.06 | 24-DEC-11:10 | -28.3 | -28.6 | 0.00 | 0.00 | 01-DEC-00:10 | -28.3 | -28.6 |
Annual Sum or Average | 0.567492E+10 | 0.00 | ||||||||
Minimum of Months | 62489646.90 | 363.06 | -29.7 | -29.9 | 0.00 | 0.00 | -29.7 | -29.9 | ||
Maximum of Months | 0.893385E+09 | 1041.05 | 31.70 | 24.46 | 0.00 | 0.00 | 31.70 | 24.46 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 33156010.02 | 444.82 | 06-JAN-08:61 | -35.1 | -35.2 | 92240380.02 | 56.69 | 14-JAN-05:19 | -22.9 | -23.2 |
February | 52457290.97 | 418.87 | 14-FEB-08:61 | -31.2 | -31.4 | 84572151.26 | 56.69 | 15-FEB-22:19 | -11.3 | -11.7 |
March | 0.110174E+09 | 1026.37 | 28-MAR-18:02 | 6.93 | 2.56 | 94586310.35 | 56.69 | 29-MAR-21:10 | 1.60 | 0.74 |
April | 0.331744E+09 | 1095.96 | 14-APR-18:01 | 12.12 | 6.20 | 93072642.90 | 56.69 | 12-APR-21:10 | 12.12 | 6.20 |
May | 0.737490E+09 | 1157.68 | 21-MAY-18:02 | 21.23 | 10.92 | 97806008.02 | 56.69 | 25-MAY-21:30 | 22.35 | 16.43 |
June | 0.885319E+09 | 1183.04 | 17-JUN-18:02 | 23.62 | 13.20 | 95065470.55 | 56.70 | 21-JUN-21:40 | 17.40 | 14.98 |
July | 0.971047E+09 | 1128.46 | 10-JUL-18:02 | 23.12 | 16.54 | 98298399.29 | 56.69 | 24-JUL-21:30 | 19.15 | 17.68 |
August | 0.818532E+09 | 1120.72 | 20-AUG-15:02 | 25.40 | 16.30 | 97952827.42 | 56.69 | 10-AUG-21:10 | 25.40 | 16.30 |
September | 0.576409E+09 | 1127.84 | 04-SEP-18:01 | 14.03 | 8.92 | 94053892.47 | 56.70 | 01-SEP-21:10 | 14.03 | 8.92 |
October | 0.333648E+09 | 1087.22 | 01-OCT-18:01 | 12.12 | 8.05 | 96073619.02 | 56.69 | 03-OCT-21:49 | 2.38 | 1.43 |
November | 0.120238E+09 | 901.62 | 01-NOV-18:03 | 12.02 | 10.48 | 91622561.69 | 56.69 | 01-NOV-21:10 | 12.62 | 11.43 |
December | 39464274.39 | 415.87 | 24-DEC-08:61 | -31.1 | -31.3 | 92822315.31 | 56.69 | 11-DEC-22:19 | -31.1 | -31.3 |
Annual Sum or Average | 0.500968E+10 | 0.112817E+10 | ||||||||
Minimum of Months | 33156010.02 | 415.87 | -35.1 | -35.2 | 84572151.26 | 56.69 | -31.1 | -31.3 | ||
Maximum of Months | 0.971047E+09 | 1183.04 | 25.40 | 16.54 | 98298399.29 | 56.70 | 25.40 | 17.68 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 19632208.64 | 637.12 | 17-JAN-16:04 | -4.2 | -5.3 | 92152637.26 | 56.69 | 07-JAN-04:49 | -4.2 | -5.3 |
February | 80934796.12 | 3368.51 | 28-FEB-16:02 | 6.02 | 1.46 | 84641089.98 | 56.69 | 01-FEB-00:10 | 6.02 | 1.46 |
March | 0.228477E+09 | 3599.99 | 31-MAR-15:01 | 8.40 | 2.82 | 95111582.22 | 56.69 | 07-MAR-02:09 | 8.40 | 2.82 |
April | 0.774415E+09 | 3688.27 | 22-APR-08:62 | 8.77 | 2.60 | 94013388.77 | 56.69 | 13-APR-21:10 | 8.77 | 2.60 |
May | 0.161186E+10 | 3700.96 | 06-MAY-08:62 | 8.77 | 3.63 | 98753876.74 | 56.70 | 25-MAY-21:10 | 22.65 | 16.44 |
June | 0.207609E+10 | 3671.79 | 16-JUN-15:02 | 21.70 | 11.70 | 95728251.46 | 56.70 | 30-JUN-21:30 | 19.85 | 16.50 |
July | 0.242604E+10 | 3663.47 | 24-JUL-08:61 | 23.07 | 18.74 | 98972791.22 | 56.70 | 12-JUL-21:10 | 23.07 | 18.74 |
August | 0.191431E+10 | 3587.96 | 25-AUG-08:62 | 17.77 | 15.74 | 98792811.61 | 56.69 | 08-AUG-21:10 | 17.77 | 15.74 |
September | 0.112210E+10 | 3735.85 | 09-SEP-08:61 | 13.48 | 7.36 | 94772570.65 | 56.69 | 01-SEP-22:00 | 13.48 | 7.36 |
October | 0.407500E+09 | 3633.04 | 21-OCT-15:02 | 20.00 | 11.21 | 95803558.28 | 56.69 | 19-OCT-22:10 | 20.00 | 11.21 |
November | 86113143.37 | 3329.40 | 16-NOV-09:01 | -0.2 | -1.8 | 90713651.70 | 56.69 | 01-NOV-21:19 | -0.2 | -1.8 |
December | 15127053.35 | 777.65 | 28-DEC-09:04 | -3.8 | -4.7 | 92278185.42 | 56.69 | 26-DEC-22:19 | -3.8 | -4.7 |
Annual Sum or Average | 0.107626E+11 | 0.113173E+10 | ||||||||
Minimum of Months | 15127053.35 | 637.12 | -4.2 | -5.3 | 84641089.98 | 56.69 | -4.2 | -5.3 | ||
Maximum of Months | 0.242604E+10 | 3735.85 | 23.07 | 18.74 | 98972791.22 | 56.70 | 23.07 | 18.74 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 7226153.03 | 595.95 | 26-JAN-08:61 | -32.1 | -32.2 | 91579504.73 | 56.69 | 14-JAN-05:19 | -32.1 | -32.2 |
February | 25769738.83 | 948.86 | 28-FEB-09:03 | -9.9 | -10.9 | 83641597.85 | 56.69 | 24-FEB-22:19 | -9.9 | -10.9 |
March | 0.100079E+09 | 3250.25 | 26-MAR-08:61 | -0.9 | -2.8 | 93768245.96 | 56.69 | 07-MAR-05:00 | -0.9 | -2.8 |
April | 0.496225E+09 | 3510.95 | 22-APR-08:62 | 8.77 | 2.60 | 93350923.26 | 56.69 | 13-APR-21:49 | 8.77 | 2.60 |
May | 0.137290E+10 | 3532.18 | 06-MAY-08:62 | 8.77 | 3.63 | 98625412.97 | 56.70 | 25-MAY-21:10 | 22.65 | 16.44 |
June | 0.193484E+10 | 3490.94 | 16-JUN-15:02 | 21.70 | 11.70 | 95707107.68 | 56.70 | 30-JUN-21:30 | 19.85 | 16.50 |
July | 0.221099E+10 | 3507.87 | 24-JUL-08:61 | 23.07 | 18.74 | 98948407.45 | 56.70 | 19-JUL-21:10 | 23.07 | 18.74 |
August | 0.160219E+10 | 3430.85 | 20-AUG-08:62 | 18.68 | 14.97 | 98708946.90 | 56.70 | 08-AUG-21:10 | 18.68 | 14.97 |
September | 0.789987E+09 | 3557.83 | 09-SEP-08:61 | 13.48 | 7.36 | 94463844.72 | 56.69 | 18-SEP-21:10 | 16.10 | 15.44 |
October | 0.198824E+09 | 3344.29 | 01-OCT-15:01 | 15.10 | 9.13 | 95005285.20 | 56.69 | 19-OCT-21:19 | 12.60 | 9.81 |
November | 41003884.32 | 1019.84 | 10-NOV-09:03 | -6.4 | -7.7 | 89949983.46 | 56.69 | 01-NOV-21:19 | -6.4 | -7.7 |
December | 8102675.78 | 576.58 | 24-DEC-08:61 | -31.1 | -31.3 | 92100298.70 | 56.69 | 11-DEC-22:19 | -31.1 | -31.3 |
Annual Sum or Average | 0.878814E+10 | 0.112585E+10 | ||||||||
Minimum of Months | 7226153.03 | 576.58 | -32.1 | -32.2 | 83641597.85 | 56.69 | -32.1 | -32.2 | ||
Maximum of Months | 0.221099E+10 | 3557.83 | 23.07 | 18.74 | 98948407.45 | 56.70 | 23.07 | 18.74 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.255915E+10 | 5698.01 | 26-JAN-07:00 | -33.3 | -33.4 | 0.980074E+09 | 704.50 | 25-JAN-03:30 | -33.3 | -33.4 |
February | 0.158840E+10 | 5778.79 | 14-FEB-07:00 | -33.3 | -33.4 | 0.103429E+10 | 704.50 | 07-FEB-02:39 | -33.3 | -33.4 |
March | 0.184278E+10 | 5173.83 | 05-MAR-03:55 | -28.3 | -28.5 | 0.119304E+10 | 704.52 | 11-MAR-03:20 | -16.5 | -16.7 |
April | 0.347241E+10 | 2744.56 | 23-APR-18:10 | 25.22 | 16.18 | 0.116507E+10 | 727.87 | 13-APR-21:40 | 25.22 | 16.18 |
May | 0.555417E+10 | 3120.04 | 18-MAY-18:10 | 27.25 | 15.75 | 0.122109E+10 | 764.16 | 18-MAY-21:40 | 17.67 | 12.46 |
June | 0.585835E+10 | 3330.71 | 30-JUN-10:40 | 30.73 | 23.70 | 0.119852E+10 | 799.23 | 30-JUN-21:40 | 19.60 | 16.44 |
July | 0.652639E+10 | 3375.35 | 23-JUL-10:35 | 27.77 | 23.32 | 0.125981E+10 | 784.29 | 24-JUL-21:40 | 19.07 | 17.60 |
August | 0.605863E+10 | 3187.72 | 26-AUG-10:35 | 22.43 | 17.42 | 0.123907E+10 | 764.24 | 25-AUG-21:40 | 22.43 | 17.42 |
September | 0.481298E+10 | 3046.16 | 01-SEP-10:40 | 22.77 | 18.04 | 0.117150E+10 | 751.75 | 01-SEP-21:40 | 14.27 | 13.58 |
October | 0.306460E+10 | 2879.70 | 22-OCT-10:35 | 15.20 | 11.90 | 0.120128E+10 | 724.19 | 19-OCT-21:40 | 15.20 | 11.90 |
November | 0.119025E+10 | 1814.21 | 17-NOV-13:30 | 10.30 | 3.32 | 0.115966E+10 | 704.52 | 02-NOV-00:00 | 10.30 | 3.32 |
December | 0.203427E+10 | 4991.32 | 24-DEC-06:00 | -31.1 | -31.3 | 0.104777E+10 | 704.50 | 15-DEC-04:10 | -31.1 | -31.3 |
Annual Sum or Average | 0.445624E+11 | 0.138712E+11 | ||||||||
Minimum of Months | 0.119025E+10 | 1814.21 | -33.3 | -33.4 | 0.980074E+09 | 704.50 | -33.3 | -33.4 | ||
Maximum of Months | 0.652639E+10 | 5778.79 | 30.73 | 23.70 | 0.125981E+10 | 799.23 | 25.22 | 17.60 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 13740613.21 | 982.89 | 17-JAN-16:03 | -4.2 | -5.3 | 92379771.76 | 56.69 | 07-JAN-04:49 | -4.2 | -5.3 |
February | 83116643.48 | 4065.57 | 27-FEB-16:01 | -7.8 | -10.1 | 84331728.61 | 56.69 | 01-FEB-00:10 | -7.8 | -10.1 |
March | 0.257763E+09 | 4165.05 | 26-MAR-15:01 | 10.68 | 5.32 | 94459488.57 | 56.69 | 07-MAR-02:09 | 10.68 | 5.32 |
April | 0.772800E+09 | 4262.96 | 13-APR-15:01 | 20.00 | 8.11 | 93223655.64 | 56.69 | 13-APR-21:10 | 13.03 | 6.68 |
May | 0.186303E+10 | 4283.71 | 14-MAY-18:01 | 19.63 | 8.56 | 98495469.88 | 56.70 | 24-MAY-21:30 | 18.55 | 13.22 |
June | 0.217606E+10 | 4267.24 | 16-JUN-15:02 | 21.70 | 11.70 | 95516834.10 | 56.70 | 21-JUN-21:00 | 17.20 | 14.80 |
July | 0.270227E+10 | 4165.41 | 24-JUL-18:02 | 27.85 | 19.74 | 98815917.52 | 56.70 | 24-JUL-22:10 | 18.43 | 17.18 |
August | 0.218318E+10 | 4052.50 | 07-AUG-15:02 | 22.67 | 19.40 | 98620687.40 | 56.70 | 09-AUG-21:10 | 21.02 | 18.85 |
September | 0.119200E+10 | 4259.23 | 05-SEP-15:01 | 17.12 | 10.02 | 94631895.28 | 56.69 | 01-SEP-23:40 | 17.12 | 10.02 |
October | 0.423716E+09 | 4190.88 | 26-OCT-15:01 | 14.40 | 8.04 | 95379282.46 | 56.69 | 20-OCT-02:30 | 14.40 | 8.04 |
November | 52378416.86 | 4042.84 | 17-NOV-16:01 | 9.45 | 2.90 | 90332290.70 | 56.69 | 01-NOV-02:30 | 9.45 | 2.90 |
December | 10180434.70 | 576.57 | 24-DEC-08:61 | -31.1 | -31.3 | 92240414.85 | 56.69 | 26-DEC-22:19 | -17.9 | -18.7 |
Annual Sum or Average | 0.117302E+11 | 0.112843E+10 | ||||||||
Minimum of Months | 10180434.70 | 576.57 | -31.1 | -31.3 | 84331728.61 | 56.69 | -17.9 | -18.7 | ||
Maximum of Months | 0.270227E+10 | 4283.71 | 27.85 | 19.74 | 98815917.52 | 56.70 | 21.02 | 18.85 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 5206378.39 | 747.79 | 17-JAN-16:04 | -4.2 | -5.3 | 92151568.77 | 56.69 | 31-JAN-23:00 | -23.2 | -23.6 |
February | 21501830.09 | 2094.59 | 28-FEB-16:02 | 6.02 | 1.46 | 83576178.29 | 56.69 | 01-FEB-00:10 | 6.02 | 1.46 |
March | 0.116533E+09 | 3911.62 | 26-MAR-18:01 | 8.53 | 4.25 | 93376543.61 | 56.70 | 31-MAR-21:10 | 4.92 | 0.91 |
April | 0.508327E+09 | 3996.35 | 13-APR-15:01 | 20.00 | 8.11 | 92361540.09 | 56.69 | 13-APR-21:40 | 12.23 | 6.51 |
May | 0.161109E+10 | 4083.14 | 14-MAY-18:01 | 19.63 | 8.56 | 98285387.25 | 56.70 | 18-MAY-21:49 | 17.63 | 12.41 |
June | 0.202813E+10 | 4046.98 | 16-JUN-15:02 | 21.70 | 11.70 | 95487526.63 | 56.70 | 30-JUN-22:40 | 18.10 | 14.50 |
July | 0.247526E+10 | 3972.50 | 24-JUL-18:02 | 27.85 | 19.74 | 98791162.51 | 56.70 | 03-JUL-21:00 | 27.85 | 19.74 |
August | 0.185283E+10 | 3827.96 | 30-AUG-15:02 | 25.50 | 20.16 | 98501451.72 | 56.70 | 09-AUG-21:10 | 25.50 | 20.16 |
September | 0.844933E+09 | 4032.52 | 06-SEP-15:01 | 20.00 | 11.79 | 94194633.50 | 56.69 | 01-SEP-22:40 | 20.00 | 11.79 |
October | 0.208236E+09 | 3904.97 | 01-OCT-15:01 | 15.10 | 9.13 | 94514794.47 | 56.69 | 19-OCT-23:19 | 11.83 | 9.89 |
November | 26211609.19 | 835.76 | 15-NOV-19:04 | 4.32 | 1.54 | 89658973.05 | 56.69 | 01-NOV-03:20 | 4.32 | 1.54 |
December | 4850254.89 | 576.33 | 24-DEC-08:61 | -31.1 | -31.3 | 92199108.90 | 56.69 | 26-DEC-22:19 | -17.9 | -18.7 |
Annual Sum or Average | 0.970311E+10 | 0.112310E+10 | ||||||||
Minimum of Months | 4850254.89 | 576.33 | -31.1 | -31.3 | 83576178.29 | 56.69 | -23.2 | -23.6 | ||
Maximum of Months | 0.247526E+10 | 4083.14 | 27.85 | 20.16 | 98791162.51 | 56.70 | 27.85 | 20.16 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.122018E+09 | 2301.11 | 27-JAN-16:01 | -14.8 | -15.9 | 94014819.39 | 56.69 | 08-JAN-03:20 | -14.8 | -15.9 |
February | 0.265011E+09 | 2315.51 | 27-FEB-16:01 | -7.8 | -10.1 | 86364154.85 | 56.69 | 28-FEB-22:10 | -0.1 | -3.0 |
March | 0.365028E+09 | 2353.23 | 26-MAR-15:01 | 10.68 | 5.32 | 96151873.10 | 56.69 | 28-MAR-21:10 | 0.22 | -1.8 |
April | 0.649928E+09 | 2384.85 | 13-APR-15:01 | 20.00 | 8.11 | 94134382.55 | 56.69 | 17-APR-21:30 | 7.25 | 3.10 |
May | 0.111960E+10 | 2360.49 | 04-MAY-15:02 | 20.98 | 10.71 | 98592582.11 | 56.70 | 24-MAY-21:40 | 18.43 | 13.18 |
June | 0.125199E+10 | 2339.93 | 04-JUN-15:02 | 21.10 | 11.77 | 95493984.20 | 56.70 | 29-JUN-22:00 | 26.10 | 23.67 |
July | 0.153389E+10 | 2227.37 | 24-JUL-18:02 | 27.85 | 19.74 | 98769569.65 | 56.70 | 20-JUL-22:10 | 27.85 | 19.74 |
August | 0.142258E+10 | 2305.03 | 25-AUG-15:02 | 28.30 | 19.24 | 98676824.03 | 56.70 | 11-AUG-21:40 | 28.30 | 19.24 |
September | 0.102255E+10 | 2373.17 | 08-SEP-15:01 | 19.32 | 10.13 | 94996750.66 | 56.70 | 01-SEP-21:49 | 19.32 | 10.13 |
October | 0.583066E+09 | 2380.96 | 26-OCT-15:01 | 14.40 | 8.04 | 96577499.41 | 56.69 | 19-OCT-21:19 | 14.40 | 8.04 |
November | 0.200589E+09 | 2306.70 | 17-NOV-16:01 | 9.45 | 2.90 | 92033962.95 | 56.69 | 17-NOV-22:10 | 2.62 | -1.0 |
December | 75570309.39 | 2259.25 | 02-DEC-16:01 | -18.7 | -19.4 | 93541498.81 | 56.69 | 15-DEC-22:19 | -12.0 | -12.4 |
Annual Sum or Average | 0.861181E+10 | 0.113935E+10 | ||||||||
Minimum of Months | 75570309.39 | 2227.37 | -18.7 | -19.4 | 86364154.85 | 56.69 | -14.8 | -15.9 | ||
Maximum of Months | 0.153389E+10 | 2384.85 | 28.30 | 19.74 | 98769569.65 | 56.70 | 28.30 | 23.67 |
Report: ZoneCoolingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.358322E+11 | 46971.69 | 25-JAN-20:01 | -24.0 | -24.2 | 0.112572E+11 | 9649.25 | 19-JAN-23:10 | -24.0 | -24.2 |
February | 0.320692E+11 | 39959.23 | 24-FEB-22:51 | -23.9 | -24.3 | 0.121168E+11 | 9747.61 | 21-FEB-23:10 | -23.9 | -24.3 |
March | 0.369332E+11 | 43164.45 | 12-MAR-03:51 | -23.9 | -24.1 | 0.147047E+11 | 9978.97 | 31-MAR-22:10 | 4.43 | 0.70 |
April | 0.393827E+11 | 19697.49 | 13-APR-18:10 | 16.93 | 6.60 | 0.149086E+11 | 10264.44 | 13-APR-22:10 | 11.52 | 6.37 |
May | 0.452737E+11 | 22349.57 | 25-MAY-18:10 | 29.03 | 19.14 | 0.159371E+11 | 10692.46 | 25-MAY-22:10 | 21.73 | 16.39 |
June | 0.457299E+11 | 23139.42 | 29-JUN-18:10 | 32.52 | 24.04 | 0.156677E+11 | 10864.76 | 29-JUN-22:10 | 26.60 | 23.41 |
July | 0.479192E+11 | 22509.26 | 24-JUL-18:10 | 27.85 | 19.74 | 0.161587E+11 | 10740.09 | 21-JUL-22:10 | 27.85 | 19.74 |
August | 0.464623E+11 | 21777.17 | 09-AUG-18:10 | 26.52 | 20.82 | 0.161131E+11 | 10640.98 | 08-AUG-22:10 | 26.52 | 20.82 |
September | 0.423185E+11 | 20487.14 | 01-SEP-18:10 | 23.07 | 17.74 | 0.152451E+11 | 10440.52 | 01-SEP-22:10 | 13.90 | 13.22 |
October | 0.403041E+11 | 19378.11 | 19-OCT-22:00 | 12.20 | 9.84 | 0.154051E+11 | 10194.01 | 19-OCT-22:10 | 12.20 | 9.87 |
November | 0.355427E+11 | 19222.30 | 01-NOV-22:00 | 11.70 | 10.79 | 0.145781E+11 | 10116.21 | 01-NOV-22:10 | 11.52 | 10.61 |
December | 0.357388E+11 | 38640.16 | 23-DEC-21:41 | -23.9 | -24.3 | 0.120744E+11 | 9695.67 | 05-DEC-23:10 | -23.9 | -24.3 |
Annual Sum or Average | 0.483507E+12 | 0.174167E+12 | ||||||||
Minimum of Months | 0.320692E+11 | 19222.30 | -24.0 | -24.3 | 0.112572E+11 | 9649.25 | -24.0 | -24.3 | ||
Maximum of Months | 0.479192E+11 | 46971.69 | 32.52 | 24.04 | 0.161587E+11 | 10864.76 | 27.85 | 23.41 |
Report: ZoneCoolingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.385532E+11 | 49521.47 | 25-JAN-20:01 | -24.0 | -24.2 | 0.112654E+11 | 9752.49 | 19-JAN-23:10 | -24.0 | -24.2 |
February | 0.345668E+11 | 42223.65 | 24-FEB-22:51 | -23.9 | -24.3 | 0.121466E+11 | 9846.45 | 21-FEB-23:10 | -23.9 | -24.3 |
March | 0.399300E+11 | 45542.22 | 12-MAR-03:51 | -23.9 | -24.1 | 0.147870E+11 | 10078.18 | 31-MAR-22:10 | 4.43 | 0.70 |
April | 0.424655E+11 | 20995.36 | 13-APR-18:10 | 16.93 | 6.60 | 0.150265E+11 | 10368.78 | 13-APR-22:10 | 11.52 | 6.37 |
May | 0.486071E+11 | 23780.12 | 25-MAY-18:10 | 29.03 | 19.14 | 0.160891E+11 | 10802.82 | 25-MAY-22:10 | 21.73 | 16.39 |
June | 0.490230E+11 | 24583.75 | 29-JUN-18:10 | 32.52 | 24.04 | 0.158257E+11 | 10965.96 | 29-JUN-22:10 | 26.60 | 23.41 |
July | 0.513008E+11 | 23905.86 | 24-JUL-18:10 | 27.85 | 19.74 | 0.163188E+11 | 10847.40 | 21-JUL-22:10 | 27.85 | 19.74 |
August | 0.497980E+11 | 23201.26 | 09-AUG-18:10 | 26.52 | 20.82 | 0.162617E+11 | 10747.23 | 08-AUG-22:10 | 26.52 | 20.82 |
September | 0.454714E+11 | 21813.80 | 01-SEP-18:10 | 23.07 | 17.74 | 0.153759E+11 | 10546.57 | 01-SEP-22:10 | 13.90 | 13.22 |
October | 0.434512E+11 | 20630.50 | 19-OCT-22:00 | 12.20 | 9.84 | 0.155259E+11 | 10293.09 | 19-OCT-22:10 | 12.20 | 9.87 |
November | 0.385156E+11 | 20502.93 | 01-NOV-22:00 | 11.70 | 10.79 | 0.146725E+11 | 10227.57 | 01-NOV-22:10 | 11.52 | 10.61 |
December | 0.384745E+11 | 41112.76 | 23-DEC-21:41 | -23.9 | -24.3 | 0.120920E+11 | 9798.65 | 05-DEC-23:10 | -23.9 | -24.3 |
Annual Sum or Average | 0.520157E+12 | 0.175387E+12 | ||||||||
Minimum of Months | 0.345668E+11 | 20502.93 | -24.0 | -24.3 | 0.112654E+11 | 9752.49 | -24.0 | -24.3 | ||
Maximum of Months | 0.513008E+11 | 49521.47 | 32.52 | 24.04 | 0.163188E+11 | 10965.96 | 27.85 | 23.41 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.481388E+11 | 55704.22 | 25-JAN-20:01 | -24.0 | -24.2 | 0.181929E+11 | 11313.48 | 21-JAN-18:00 | -24.0 | -24.2 |
February | 0.442984E+11 | 46998.31 | 01-FEB-18:11 | -23.9 | -24.3 | 0.166436E+11 | 11319.19 | 04-FEB-18:30 | 4.70 | 0.68 |
March | 0.508392E+11 | 42645.88 | 15-MAR-06:51 | -23.9 | -24.1 | 0.185682E+11 | 11319.62 | 18-MAR-17:19 | -0.2 | -4.6 |
April | 0.524724E+11 | 30021.00 | 18-APR-10:40 | 17.57 | 11.16 | 0.180400E+11 | 11319.74 | 22-APR-17:19 | 17.93 | 7.72 |
May | 0.578844E+11 | 30998.88 | 18-MAY-10:40 | 26.07 | 16.42 | 0.186673E+11 | 11319.75 | 20-MAY-17:19 | 13.43 | 7.88 |
June | 0.578382E+11 | 31833.77 | 25-JUN-10:40 | 27.43 | 22.06 | 0.180774E+11 | 11319.73 | 24-JUN-17:19 | 27.43 | 22.06 |
July | 0.604289E+11 | 31887.92 | 29-JUL-10:40 | 27.43 | 19.77 | 0.186763E+11 | 11319.74 | 01-JUL-17:19 | 27.43 | 19.77 |
August | 0.590939E+11 | 31092.82 | 25-AUG-10:40 | 24.27 | 17.99 | 0.186743E+11 | 11319.75 | 12-AUG-17:19 | 24.27 | 17.99 |
September | 0.547992E+11 | 30844.10 | 01-SEP-10:40 | 22.77 | 18.04 | 0.180545E+11 | 11319.74 | 09-SEP-17:19 | 16.83 | 10.30 |
October | 0.533439E+11 | 29373.41 | 22-OCT-10:40 | 15.20 | 11.90 | 0.186328E+11 | 11319.66 | 21-OCT-17:19 | 15.20 | 11.90 |
November | 0.485547E+11 | 26667.88 | 01-NOV-18:07 | 12.02 | 10.48 | 0.180040E+11 | 11319.43 | 18-NOV-18:30 | 1.65 | -0.7 |
December | 0.479889E+11 | 43270.36 | 23-DEC-21:41 | -23.9 | -24.3 | 0.182707E+11 | 11316.37 | 30-DEC-18:00 | -3.3 | -3.3 |
Annual Sum or Average | 0.635681E+12 | 0.218502E+12 | ||||||||
Minimum of Months | 0.442984E+11 | 26667.88 | -24.0 | -24.3 | 0.166436E+11 | 11313.48 | -24.0 | -24.2 | ||
Maximum of Months | 0.604289E+11 | 55704.22 | 27.43 | 22.06 | 0.186763E+11 | 11319.75 | 27.43 | 22.06 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.262378E+10 | 9734.19 | 25-JAN-20:01 | -24.0 | -24.2 | 0.938899E+09 | 745.71 | 24-JAN-05:00 | -24.0 | -24.2 |
February | 0.184728E+10 | 8243.97 | 01-FEB-18:11 | -23.9 | -24.3 | 0.105185E+10 | 745.73 | 13-FEB-05:10 | -23.4 | -23.8 |
March | 0.198069E+10 | 9022.89 | 12-MAR-03:51 | -23.9 | -24.1 | 0.125201E+10 | 745.75 | 10-MAR-02:09 | -23.9 | -24.1 |
April | 0.464017E+10 | 5583.92 | 13-APR-16:20 | 19.80 | 7.87 | 0.123055E+10 | 745.76 | 10-APR-01:10 | 19.80 | 7.87 |
May | 0.953538E+10 | 6870.30 | 18-MAY-10:35 | 26.07 | 16.42 | 0.127576E+10 | 780.49 | 25-MAY-21:40 | 22.20 | 16.43 |
June | 0.109329E+11 | 7247.16 | 30-JUN-10:40 | 30.73 | 23.70 | 0.124299E+10 | 807.96 | 30-JUN-21:30 | 19.85 | 16.50 |
July | 0.124295E+11 | 7345.69 | 23-JUL-10:35 | 27.77 | 23.32 | 0.128201E+10 | 788.32 | 21-JUL-21:40 | 27.77 | 23.32 |
August | 0.110935E+11 | 6868.53 | 25-AUG-10:35 | 24.27 | 17.99 | 0.128108E+10 | 777.35 | 08-AUG-21:40 | 24.27 | 17.99 |
September | 0.788685E+10 | 6571.30 | 01-SEP-10:40 | 22.77 | 18.04 | 0.123121E+10 | 756.57 | 01-SEP-21:30 | 14.45 | 13.76 |
October | 0.419346E+10 | 5791.85 | 22-OCT-10:35 | 15.20 | 11.90 | 0.126993E+10 | 745.69 | 04-OCT-03:49 | 15.20 | 11.90 |
November | 0.109189E+10 | 3644.81 | 17-NOV-13:10 | 10.10 | 3.25 | 0.122734E+10 | 745.74 | 02-NOV-00:20 | 10.10 | 3.25 |
December | 0.220759E+10 | 7861.97 | 02-DEC-00:31 | -23.9 | -24.2 | 0.102879E+10 | 745.73 | 08-DEC-05:10 | -20.3 | -20.7 |
Annual Sum or Average | 0.704629E+11 | 0.143124E+11 | ||||||||
Minimum of Months | 0.109189E+10 | 3644.81 | -24.0 | -24.3 | 0.938899E+09 | 745.69 | -24.0 | -24.2 | ||
Maximum of Months | 0.124295E+11 | 9734.19 | 30.73 | 23.70 | 0.128201E+10 | 807.96 | 27.77 | 23.32 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.302147E+10 | 23725.07 | 06-JAN-13:52 | -22.8 |
February | 0.168902E+09 | 9633.12 | 14-FEB-10:43 | -23.2 |
March | 2236630.29 | 3647.21 | 05-MAR-08:41 | -22.5 |
April | 0.00 | 0.00 | 01-APR-00:10 | 3.52 |
May | 0.00 | 0.00 | 01-MAY-00:10 | -0.0 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 19.75 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.52 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 3.60 |
December | 0.138167E+10 | 16106.32 | 25-DEC-10:21 | -22.5 |
Annual Sum or Average | 0.457427E+10 | |||
Minimum of Months | 0.00 | 0.00 | -23.2 | |
Maximum of Months | 0.302147E+10 | 23725.07 | 19.75 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.214394E+10 | 5943.42 | 14-JAN-04:51 | -23.3 |
February | 0.118670E+10 | 4765.41 | 17-FEB-09:52 | -22.8 |
March | 0.632982E+09 | 4791.30 | 12-MAR-07:31 | -23.1 |
April | 74217921.35 | 713.83 | 05-APR-06:10 | -13.5 |
May | 139763.46 | 63.92 | 01-MAY-06:10 | -3.5 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 19.75 |
October | 48514927.87 | 822.96 | 30-OCT-06:10 | -9.4 |
November | 0.527663E+09 | 1474.14 | 25-NOV-07:30 | -18.9 |
December | 0.217879E+10 | 5604.08 | 25-DEC-10:12 | -23.0 |
Annual Sum or Average | 0.679294E+10 | |||
Minimum of Months | 0.00 | 0.00 | -23.3 | |
Maximum of Months | 0.217879E+10 | 5943.42 | 19.75 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.504295E+09 | 3049.97 | 06-JAN-13:52 | -22.8 |
February | 0.166749E+09 | 2354.22 | 14-FEB-10:43 | -23.2 |
March | 35787704.63 | 1643.06 | 05-MAR-08:41 | -22.5 |
April | 0.00 | 0.00 | 01-APR-00:10 | 3.52 |
May | 0.00 | 0.00 | 01-MAY-00:10 | -0.0 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 19.75 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.52 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 3.60 |
December | 0.407050E+09 | 2745.72 | 25-DEC-10:13 | -23.0 |
Annual Sum or Average | 0.111388E+10 | |||
Minimum of Months | 0.00 | 0.00 | -23.2 | |
Maximum of Months | 0.504295E+09 | 3049.97 | 19.75 |
Report: ZoneHeatingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.210639E+10 | 4041.43 | 06-JAN-13:52 | -22.8 |
February | 0.115464E+10 | 2709.95 | 14-FEB-10:43 | -23.2 |
March | 0.455550E+09 | 2054.80 | 05-MAR-08:41 | -22.5 |
April | 5840800.07 | 248.10 | 05-APR-04:00 | -12.2 |
May | 0.00 | 0.00 | 01-MAY-00:10 | -0.0 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 19.75 |
October | 989757.99 | 130.28 | 30-OCT-04:00 | -10.0 |
November | 0.122609E+09 | 544.41 | 25-NOV-06:00 | -19.4 |
December | 0.177787E+10 | 3455.33 | 25-DEC-10:21 | -22.5 |
Annual Sum or Average | 0.562388E+10 | |||
Minimum of Months | 0.00 | 0.00 | -23.2 | |
Maximum of Months | 0.210639E+10 | 4041.43 | 19.75 |
Report: ZoneHeatingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.159736E+10 | 2264.96 | 06-JAN-13:52 | -22.8 |
February | 0.105837E+10 | 1576.07 | 14-FEB-10:44 | -23.2 |
March | 0.614789E+09 | 1260.74 | 05-MAR-08:41 | -22.5 |
April | 65086987.43 | 290.34 | 05-APR-03:50 | -12.2 |
May | 94820.36 | 21.70 | 01-MAY-04:00 | -2.8 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 19.75 |
October | 23775172.84 | 225.60 | 30-OCT-03:50 | -9.9 |
November | 0.321941E+09 | 530.37 | 25-NOV-17:00 | -15.6 |
December | 0.144601E+10 | 1961.06 | 25-DEC-10:21 | -22.5 |
Annual Sum or Average | 0.512743E+10 | |||
Minimum of Months | 0.00 | 0.00 | -23.2 | |
Maximum of Months | 0.159736E+10 | 2264.96 | 19.75 |
Report: ZoneHeatingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 27932631.08 | 28473.55 | 14-JAN-04:51 | -23.3 |
February | 6164975.86 | 16462.61 | 14-FEB-10:41 | -23.2 |
March | 4386263.54 | 15792.50 | 05-MAR-08:31 | -23.4 |
April | 0.00 | 0.00 | 01-APR-00:10 | 3.52 |
May | 0.00 | 0.00 | 01-MAY-00:10 | -0.0 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 19.75 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.52 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 3.60 |
December | 13230740.44 | 16912.23 | 25-DEC-10:11 | -23.0 |
Annual Sum or Average | 51714610.92 | |||
Minimum of Months | 0.00 | 0.00 | -23.4 | |
Maximum of Months | 27932631.08 | 28473.55 | 19.75 |
Report: ZoneHeatingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.854408E+09 | 16544.47 | 11-JAN-09:51 | -22.8 |
February | 0.293455E+09 | 14469.66 | 17-FEB-09:51 | -22.8 |
March | 89987063.15 | 14482.24 | 12-MAR-07:31 | -23.1 |
April | 0.00 | 0.00 | 01-APR-00:10 | 3.52 |
May | 0.00 | 0.00 | 01-MAY-00:10 | -0.0 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 19.75 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.52 |
November | 80069.38 | 105.88 | 24-NOV-09:08 | -10.0 |
December | 0.879933E+09 | 16097.68 | 21-DEC-11:02 | -22.9 |
Annual Sum or Average | 0.211786E+10 | |||
Minimum of Months | 0.00 | 0.00 | -23.1 | |
Maximum of Months | 0.879933E+09 | 16544.47 | 19.75 |
Report: ZoneHeatingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.471036E+10 | 50655.83 | 06-JAN-13:42 | -23.1 |
February | 0.129186E+10 | 42544.31 | 14-FEB-10:42 | -23.2 |
March | 0.151899E+09 | 30840.88 | 12-MAR-07:31 | -23.1 |
April | 0.00 | 0.00 | 01-APR-00:10 | 3.52 |
May | 0.00 | 0.00 | 01-MAY-00:10 | -0.0 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 19.75 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.52 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 3.60 |
December | 0.392754E+10 | 50571.63 | 21-DEC-11:02 | -22.9 |
Annual Sum or Average | 0.100817E+11 | |||
Minimum of Months | 0.00 | 0.00 | -23.2 | |
Maximum of Months | 0.471036E+10 | 50655.83 | 19.75 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.263575E+10 | 2527.74 | 07-JAN-09:02 | -20.4 |
February | 0.149323E+10 | 2488.99 | 02-FEB-16:02 | -15.1 |
March | 0.985380E+09 | 2453.87 | 23-MAR-08:61 | -13.2 |
April | 0.273694E+09 | 2432.76 | 04-APR-08:61 | -7.6 |
May | 14582448.66 | 1568.22 | 01-MAY-08:62 | 1.73 |
June | 3555565.40 | 976.60 | 13-JUN-08:03 | 15.18 |
July | 1009809.77 | 935.61 | 09-JUL-08:03 | 13.40 |
August | 3437844.28 | 760.57 | 14-AUG-08:04 | 15.60 |
September | 21468274.96 | 1014.19 | 28-SEP-08:62 | 7.30 |
October | 0.308243E+09 | 2441.78 | 30-OCT-08:61 | -6.1 |
November | 0.102620E+10 | 2462.35 | 29-NOV-09:01 | -13.8 |
December | 0.253024E+10 | 2527.23 | 25-DEC-16:13 | -15.3 |
Annual Sum or Average | 0.929679E+10 | |||
Minimum of Months | 1009809.77 | 760.57 | -20.4 | |
Maximum of Months | 0.263575E+10 | 2527.74 | 15.60 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.309747E+10 | 2521.61 | 06-JAN-16:13 | -22.6 |
February | 0.187219E+10 | 2472.25 | 02-FEB-16:02 | -15.1 |
March | 0.125385E+10 | 2444.74 | 15-MAR-08:62 | -22.3 |
April | 0.354388E+09 | 2415.39 | 05-APR-08:61 | -8.5 |
May | 18618982.07 | 2068.87 | 01-MAY-08:62 | 1.73 |
June | 3315488.12 | 981.58 | 11-JUN-08:03 | 10.78 |
July | 989338.13 | 748.09 | 09-JUL-08:03 | 13.40 |
August | 3830873.58 | 766.39 | 07-AUG-08:03 | 14.50 |
September | 27139261.66 | 1210.22 | 09-SEP-08:03 | 13.48 |
October | 0.385589E+09 | 2423.93 | 30-OCT-08:61 | -6.1 |
November | 0.122595E+10 | 2455.22 | 29-NOV-09:01 | -13.8 |
December | 0.288932E+10 | 2509.93 | 25-DEC-16:13 | -15.3 |
Annual Sum or Average | 0.111326E+11 | |||
Minimum of Months | 989338.13 | 748.09 | -22.6 | |
Maximum of Months | 0.309747E+10 | 2521.61 | 14.50 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.185667E+09 | 410.69 | 09-JAN-05:00 | -33.3 |
February | 54282720.75 | 341.57 | 17-FEB-05:00 | -30.0 |
March | 13812851.84 | 277.01 | 05-MAR-06:00 | -27.2 |
April | 0.00 | 0.00 | 01-APR-00:10 | 3.52 |
May | 0.00 | 0.00 | 01-MAY-00:10 | -0.0 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 19.75 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.52 |
November | 31957903.86 | 254.42 | 25-NOV-06:00 | -19.4 |
December | 0.207936E+09 | 402.56 | 24-DEC-06:00 | -31.1 |
Annual Sum or Average | 0.493656E+09 | |||
Minimum of Months | 0.00 | 0.00 | -33.3 | |
Maximum of Months | 0.207936E+09 | 410.69 | 19.75 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.502522E+09 | 717.25 | 06-JAN-16:02 | -22.4 |
February | 0.283035E+09 | 711.09 | 01-FEB-16:01 | -20.2 |
March | 0.145967E+09 | 704.22 | 15-MAR-15:01 | -11.0 |
April | 8232819.79 | 665.07 | 05-APR-08:61 | -8.5 |
May | 579573.08 | 426.98 | 06-MAY-15:04 | 17.13 |
June | 189906.52 | 361.38 | 02-JUN-08:05 | 11.20 |
July | 106728.25 | 159.66 | 08-JUL-15:06 | 13.90 |
August | 243866.24 | 360.17 | 07-AUG-08:05 | 14.50 |
September | 819805.95 | 395.22 | 05-SEP-15:04 | 17.12 |
October | 2719576.43 | 661.20 | 30-OCT-15:01 | 5.00 |
November | 87391839.48 | 701.30 | 25-NOV-16:02 | -14.2 |
December | 0.444756E+09 | 715.66 | 20-DEC-16:01 | -20.4 |
Annual Sum or Average | 0.147656E+10 | |||
Minimum of Months | 106728.25 | 159.66 | -22.4 | |
Maximum of Months | 0.502522E+09 | 717.25 | 17.13 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.262406E+10 | 2456.10 | 07-JAN-09:02 | -20.4 |
February | 0.148641E+10 | 2427.32 | 02-FEB-16:02 | -15.1 |
March | 0.975093E+09 | 2393.22 | 07-MAR-16:01 | -8.3 |
April | 0.265243E+09 | 2352.37 | 26-APR-15:01 | -0.6 |
May | 17310898.86 | 834.13 | 19-MAY-08:04 | 15.27 |
June | 1344264.99 | 680.24 | 22-JUN-15:04 | 18.40 |
July | 443044.09 | 689.30 | 08-JUL-15:04 | 13.90 |
August | 2707010.09 | 740.75 | 14-AUG-08:04 | 15.60 |
September | 24453362.55 | 911.28 | 22-SEP-18:03 | 12.93 |
October | 0.319367E+09 | 2356.16 | 29-OCT-15:01 | 0.50 |
November | 0.103343E+10 | 2396.33 | 25-NOV-16:02 | -14.2 |
December | 0.251439E+10 | 2457.60 | 25-DEC-16:02 | -15.4 |
Annual Sum or Average | 0.926425E+10 | |||
Minimum of Months | 443044.09 | 680.24 | -20.4 | |
Maximum of Months | 0.262406E+10 | 2457.60 | 18.40 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.309038E+10 | 2479.22 | 06-JAN-16:02 | -22.4 |
February | 0.187057E+10 | 2420.13 | 01-FEB-16:01 | -20.2 |
March | 0.124144E+10 | 2377.48 | 07-MAR-16:01 | -8.3 |
April | 0.336399E+09 | 2326.64 | 03-APR-08:61 | -1.5 |
May | 23368528.84 | 889.76 | 19-MAY-08:04 | 15.27 |
June | 1376841.07 | 704.21 | 22-JUN-15:04 | 18.40 |
July | 479166.13 | 689.30 | 09-JUL-15:04 | 18.48 |
August | 3080195.14 | 729.32 | 31-AUG-18:04 | 24.82 |
September | 33205825.12 | 1055.44 | 28-SEP-08:62 | 7.30 |
October | 0.403947E+09 | 2334.62 | 29-OCT-15:01 | 0.50 |
November | 0.122607E+10 | 2382.80 | 25-NOV-16:02 | -14.2 |
December | 0.287676E+10 | 2459.41 | 20-DEC-16:01 | -20.4 |
Annual Sum or Average | 0.111071E+11 | |||
Minimum of Months | 479166.13 | 689.30 | -22.4 | |
Maximum of Months | 0.309038E+10 | 2479.22 | 24.82 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.243969E+10 | 3598.83 | 07-JAN-04:31 | -23.2 |
February | 0.105256E+10 | 2569.32 | 17-FEB-09:52 | -22.8 |
March | 0.288661E+09 | 2204.55 | 05-MAR-08:41 | -22.5 |
April | 415639.17 | 113.27 | 05-APR-06:10 | -13.5 |
May | 0.00 | 0.00 | 01-MAY-00:10 | -0.0 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 19.75 |
October | 1550767.63 | 209.63 | 30-OCT-06:30 | -9.4 |
November | 0.187780E+09 | 983.49 | 25-NOV-09:07 | -17.6 |
December | 0.219062E+10 | 3307.32 | 25-DEC-10:21 | -22.5 |
Annual Sum or Average | 0.616128E+10 | |||
Minimum of Months | 0.00 | 0.00 | -23.2 | |
Maximum of Months | 0.243969E+10 | 3598.83 | 19.75 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.328266E+10 | 2903.78 | 07-JAN-09:02 | -20.4 |
February | 0.204731E+10 | 2885.14 | 02-FEB-16:02 | -15.1 |
March | 0.143516E+10 | 2847.20 | 15-MAR-08:62 | -22.3 |
April | 0.460042E+09 | 2815.99 | 04-APR-08:61 | -7.6 |
May | 32377616.93 | 2443.34 | 01-MAY-08:62 | 1.73 |
June | 5695028.49 | 889.66 | 11-JUN-08:03 | 10.78 |
July | 941507.13 | 882.00 | 09-JUL-08:03 | 13.40 |
August | 6140057.96 | 826.15 | 07-AUG-08:03 | 14.50 |
September | 50274340.54 | 1650.48 | 28-SEP-08:62 | 7.30 |
October | 0.527902E+09 | 2825.57 | 30-OCT-08:61 | -6.1 |
November | 0.151061E+10 | 2855.11 | 29-NOV-09:01 | -13.8 |
December | 0.323799E+10 | 2910.42 | 25-DEC-16:13 | -15.3 |
Annual Sum or Average | 0.125971E+11 | |||
Minimum of Months | 941507.13 | 826.15 | -22.3 | |
Maximum of Months | 0.328266E+10 | 2910.42 | 14.50 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.381475E+10 | 2871.48 | 07-JAN-09:02 | -20.4 |
February | 0.250729E+10 | 2860.03 | 10-FEB-09:01 | -20.3 |
March | 0.177734E+10 | 2838.24 | 15-MAR-08:62 | -22.3 |
April | 0.572974E+09 | 2788.73 | 05-APR-08:61 | -8.5 |
May | 40624821.01 | 2629.66 | 01-MAY-08:62 | 1.73 |
June | 5206358.57 | 899.43 | 11-JUN-08:03 | 10.78 |
July | 951939.60 | 894.90 | 09-JUL-08:03 | 13.40 |
August | 6727489.97 | 877.96 | 07-AUG-08:03 | 14.50 |
September | 66291855.03 | 1796.48 | 28-SEP-08:62 | 7.30 |
October | 0.646349E+09 | 2798.14 | 30-OCT-08:61 | -6.1 |
November | 0.176929E+10 | 2846.42 | 29-NOV-09:01 | -13.8 |
December | 0.364371E+10 | 2883.69 | 25-DEC-16:13 | -15.3 |
Annual Sum or Average | 0.148515E+11 | |||
Minimum of Months | 951939.60 | 877.96 | -22.3 | |
Maximum of Months | 0.381475E+10 | 2883.69 | 14.50 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.111262E+10 | 1528.92 | 23-JAN-09:02 | -22.1 |
February | 0.622846E+09 | 1517.51 | 16-FEB-16:01 | -14.4 |
March | 0.414271E+09 | 1505.02 | 07-MAR-16:01 | -8.3 |
April | 0.108755E+09 | 1487.25 | 26-APR-15:01 | -0.6 |
May | 5211521.64 | 638.60 | 21-MAY-08:03 | 9.70 |
June | 1446436.61 | 484.62 | 09-JUN-18:04 | 14.32 |
July | 519098.34 | 454.80 | 22-JUL-08:04 | 22.12 |
August | 1054754.70 | 517.24 | 16-AUG-08:03 | 14.87 |
September | 3091018.56 | 482.45 | 16-SEP-08:04 | 11.78 |
October | 0.109539E+09 | 1485.83 | 30-OCT-08:61 | -6.1 |
November | 0.439284E+09 | 1510.90 | 27-NOV-19:01 | -6.1 |
December | 0.114983E+10 | 1535.97 | 11-DEC-16:02 | -17.4 |
Annual Sum or Average | 0.396846E+10 | |||
Minimum of Months | 519098.34 | 454.80 | -22.1 | |
Maximum of Months | 0.114983E+10 | 1535.97 | 22.12 |
Report: ZoneHeatingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.491852E+09 | 17168.20 | 11-JAN-09:51 | -22.8 |
February | 0.116845E+09 | 16077.01 | 14-FEB-10:41 | -23.2 |
March | 5564069.04 | 10052.61 | 12-MAR-07:31 | -23.1 |
April | 0.00 | 0.00 | 01-APR-00:10 | 3.52 |
May | 0.00 | 0.00 | 01-MAY-00:10 | -0.0 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 19.75 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.52 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 3.60 |
December | 0.486895E+09 | 17686.68 | 20-DEC-11:41 | -23.2 |
Annual Sum or Average | 0.110116E+10 | |||
Minimum of Months | 0.00 | 0.00 | -23.2 | |
Maximum of Months | 0.491852E+09 | 17686.68 | 19.75 |
Report: ZoneHeatingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.430036E+09 | 18443.16 | 26-JAN-10:51 | -23.3 |
February | 0.110174E+09 | 17164.78 | 14-FEB-10:41 | -23.2 |
March | 5805537.67 | 10664.97 | 12-MAR-07:31 | -23.1 |
April | 0.00 | 0.00 | 01-APR-00:10 | 3.52 |
May | 0.00 | 0.00 | 01-MAY-00:10 | -0.0 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 19.75 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.52 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 3.60 |
December | 0.435153E+09 | 18715.19 | 20-DEC-11:41 | -23.2 |
Annual Sum or Average | 0.981170E+09 | |||
Minimum of Months | 0.00 | 0.00 | -23.3 | |
Maximum of Months | 0.435153E+09 | 18715.19 | 19.75 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 11844546.04 | 18713.49 | 14-JAN-04:51 | -23.3 |
February | 1057682.78 | 4686.69 | 14-FEB-10:41 | -23.2 |
March | 1525497.37 | 6010.61 | 07-MAR-05:11 | -23.3 |
April | 0.00 | 0.00 | 01-APR-00:10 | 3.52 |
May | 0.00 | 0.00 | 01-MAY-00:10 | -0.0 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 19.75 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.52 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 3.60 |
December | 1715806.71 | 7267.68 | 25-DEC-10:11 | -23.0 |
Annual Sum or Average | 16143532.90 | |||
Minimum of Months | 0.00 | 0.00 | -23.3 | |
Maximum of Months | 11844546.04 | 18713.49 | 19.75 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.771594E+10 | 12329.86 | 07-JAN-04:31 | -23.2 |
February | 0.445115E+10 | 9002.57 | 14-FEB-10:43 | -23.2 |
March | 0.200245E+10 | 7706.78 | 05-MAR-08:41 | -22.5 |
April | 0.120790E+09 | 1955.21 | 05-APR-06:10 | -13.5 |
May | 0.00 | 0.00 | 01-MAY-00:10 | -0.0 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 19.75 |
October | 74996642.00 | 1822.28 | 30-OCT-06:30 | -9.4 |
November | 0.127777E+10 | 3435.49 | 25-NOV-07:10 | -19.2 |
December | 0.713161E+10 | 11319.36 | 25-DEC-10:21 | -22.5 |
Annual Sum or Average | 0.227747E+11 | |||
Minimum of Months | 0.00 | 0.00 | -23.2 | |
Maximum of Months | 0.771594E+10 | 12329.86 | 19.75 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.140333E+11 | 13517.00 | 02-JAN-20:10 | 0.127587E+11 | 10113.80 | 02-JAN-20:10 |
February | 0.126708E+11 | 13517.00 | 01-FEB-20:10 | 0.115208E+11 | 10113.80 | 01-FEB-20:10 |
March | 0.140766E+11 | 13517.00 | 01-MAR-20:10 | 0.127855E+11 | 10113.80 | 01-MAR-20:10 |
April | 0.135575E+11 | 13517.00 | 03-APR-19:10 | 0.123314E+11 | 10113.80 | 03-APR-19:10 |
May | 0.140576E+11 | 13517.00 | 01-MAY-19:10 | 0.127741E+11 | 10113.80 | 01-MAY-19:10 |
June | 0.136197E+11 | 13517.00 | 01-JUN-19:10 | 0.123716E+11 | 10113.80 | 01-JUN-19:10 |
July | 0.139955E+11 | 13517.00 | 03-JUL-19:10 | 0.127338E+11 | 10113.80 | 03-JUL-19:10 |
August | 0.140820E+11 | 13517.00 | 01-AUG-19:10 | 0.127894E+11 | 10113.80 | 01-AUG-19:10 |
September | 0.135629E+11 | 13517.00 | 01-SEP-19:10 | 0.123352E+11 | 10113.80 | 01-SEP-19:10 |
October | 0.140279E+11 | 13517.00 | 02-OCT-19:10 | 0.127549E+11 | 10113.80 | 02-OCT-19:10 |
November | 0.136089E+11 | 13517.00 | 01-NOV-19:10 | 0.123659E+11 | 10113.80 | 01-NOV-19:10 |
December | 0.139955E+11 | 13517.00 | 01-DEC-20:10 | 0.127338E+11 | 10113.80 | 01-DEC-20:10 |
Annual Sum or Average | 0.165288E+12 | 0.150255E+12 | ||||
Minimum of Months | 0.126708E+11 | 13517.00 | 0.115208E+11 | 10113.80 | ||
Maximum of Months | 0.140820E+11 | 13517.00 | 0.127894E+11 | 10113.80 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.713551E+09 | 687.30 | 02-JAN-20:10 | 0.864900E+09 | 685.60 | 02-JAN-20:10 |
February | 0.644271E+09 | 687.30 | 01-FEB-20:10 | 0.780982E+09 | 685.60 | 01-FEB-20:10 |
March | 0.715750E+09 | 687.30 | 01-MAR-20:10 | 0.866718E+09 | 685.60 | 01-MAR-20:10 |
April | 0.689358E+09 | 687.30 | 03-APR-19:10 | 0.835931E+09 | 685.60 | 03-APR-19:10 |
May | 0.714788E+09 | 687.30 | 01-MAY-19:10 | 0.865939E+09 | 685.60 | 01-MAY-19:10 |
June | 0.692519E+09 | 687.30 | 01-JUN-19:10 | 0.838659E+09 | 685.60 | 01-JUN-19:10 |
July | 0.711626E+09 | 687.30 | 03-JUL-19:10 | 0.863211E+09 | 685.60 | 03-JUL-19:10 |
August | 0.716025E+09 | 687.30 | 01-AUG-19:10 | 0.866978E+09 | 685.60 | 01-AUG-19:10 |
September | 0.689633E+09 | 687.30 | 01-SEP-19:10 | 0.836191E+09 | 685.60 | 01-SEP-19:10 |
October | 0.713276E+09 | 687.30 | 02-OCT-19:10 | 0.864640E+09 | 685.60 | 02-OCT-19:10 |
November | 0.691970E+09 | 687.30 | 01-NOV-19:10 | 0.838269E+09 | 685.60 | 01-NOV-19:10 |
December | 0.711626E+09 | 687.30 | 01-DEC-20:10 | 0.863211E+09 | 685.60 | 01-DEC-20:10 |
Annual Sum or Average | 0.840439E+10 | 0.101856E+11 | ||||
Minimum of Months | 0.644271E+09 | 687.30 | 0.780982E+09 | 685.60 | ||
Maximum of Months | 0.716025E+09 | 687.30 | 0.866978E+09 | 685.60 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.826294E+09 | 795.89 | 02-JAN-20:10 | 0.100156E+10 | 793.93 | 02-JAN-20:10 |
February | 0.746069E+09 | 795.89 | 01-FEB-20:10 | 0.904380E+09 | 793.93 | 01-FEB-20:10 |
March | 0.828841E+09 | 795.89 | 01-MAR-20:10 | 0.100366E+10 | 793.93 | 01-MAR-20:10 |
April | 0.798279E+09 | 795.89 | 03-APR-19:10 | 0.968011E+09 | 793.93 | 03-APR-19:10 |
May | 0.827727E+09 | 795.89 | 01-MAY-19:10 | 0.100276E+10 | 793.93 | 01-MAY-19:10 |
June | 0.801940E+09 | 795.89 | 01-JUN-19:10 | 0.971170E+09 | 793.93 | 01-JUN-19:10 |
July | 0.824066E+09 | 795.89 | 03-JUL-19:10 | 0.999601E+09 | 793.93 | 03-JUL-19:10 |
August | 0.829160E+09 | 795.89 | 01-AUG-19:10 | 0.100396E+10 | 793.93 | 01-AUG-19:10 |
September | 0.798597E+09 | 795.89 | 01-SEP-19:10 | 0.968312E+09 | 793.93 | 01-SEP-19:10 |
October | 0.825976E+09 | 795.89 | 02-OCT-19:10 | 0.100126E+10 | 793.93 | 02-OCT-19:10 |
November | 0.801303E+09 | 795.89 | 01-NOV-19:10 | 0.970719E+09 | 793.93 | 01-NOV-19:10 |
December | 0.824066E+09 | 795.89 | 01-DEC-20:10 | 0.999601E+09 | 793.93 | 01-DEC-20:10 |
Annual Sum or Average | 0.973232E+10 | 0.117950E+11 | ||||
Minimum of Months | 0.746069E+09 | 795.89 | 0.904380E+09 | 793.93 | ||
Maximum of Months | 0.829160E+09 | 795.89 | 0.100396E+10 | 793.93 |
Report: ZoneElectricSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.154452E+10 | 1487.69 | 02-JAN-20:10 | 0.105898E+10 | 839.45 | 02-JAN-20:10 |
February | 0.139456E+10 | 1487.69 | 01-FEB-20:10 | 0.956227E+09 | 839.45 | 01-FEB-20:10 |
March | 0.154928E+10 | 1487.69 | 01-MAR-20:10 | 0.106120E+10 | 839.45 | 01-MAR-20:10 |
April | 0.149215E+10 | 1487.69 | 03-APR-19:10 | 0.102351E+10 | 839.45 | 03-APR-19:10 |
May | 0.154719E+10 | 1487.69 | 01-MAY-19:10 | 0.106025E+10 | 839.45 | 01-MAY-19:10 |
June | 0.149899E+10 | 1487.69 | 01-JUN-19:10 | 0.102685E+10 | 839.45 | 01-JUN-19:10 |
July | 0.154035E+10 | 1487.69 | 03-JUL-19:10 | 0.105691E+10 | 839.45 | 03-JUL-19:10 |
August | 0.154987E+10 | 1487.69 | 01-AUG-19:10 | 0.106152E+10 | 839.45 | 01-AUG-19:10 |
September | 0.149274E+10 | 1487.69 | 01-SEP-19:10 | 0.102382E+10 | 839.45 | 01-SEP-19:10 |
October | 0.154392E+10 | 1487.69 | 02-OCT-19:10 | 0.105866E+10 | 839.45 | 02-OCT-19:10 |
November | 0.149780E+10 | 1487.69 | 01-NOV-19:10 | 0.102637E+10 | 839.45 | 01-NOV-19:10 |
December | 0.154035E+10 | 1487.69 | 01-DEC-20:10 | 0.105691E+10 | 839.45 | 01-DEC-20:10 |
Annual Sum or Average | 0.181917E+11 | 0.124712E+11 | ||||
Minimum of Months | 0.139456E+10 | 1487.69 | 0.956227E+09 | 839.45 | ||
Maximum of Months | 0.154987E+10 | 1487.69 | 0.106152E+10 | 839.45 |
Report: ZoneElectricSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.283535E+09 | 273.10 | 02-JAN-20:10 | 0.305485E+09 | 242.16 | 02-JAN-20:10 |
February | 0.256006E+09 | 273.10 | 01-FEB-20:10 | 0.275845E+09 | 242.16 | 01-FEB-20:10 |
March | 0.284409E+09 | 273.10 | 01-MAR-20:10 | 0.306128E+09 | 242.16 | 01-MAR-20:10 |
April | 0.273921E+09 | 273.10 | 03-APR-19:10 | 0.295253E+09 | 242.16 | 03-APR-19:10 |
May | 0.284026E+09 | 273.10 | 01-MAY-19:10 | 0.305852E+09 | 242.16 | 01-MAY-19:10 |
June | 0.275178E+09 | 273.10 | 01-JUN-19:10 | 0.296217E+09 | 242.16 | 01-JUN-19:10 |
July | 0.282770E+09 | 273.10 | 03-JUL-19:10 | 0.304889E+09 | 242.16 | 03-JUL-19:10 |
August | 0.284518E+09 | 273.10 | 01-AUG-19:10 | 0.306219E+09 | 242.16 | 01-AUG-19:10 |
September | 0.274031E+09 | 273.10 | 01-SEP-19:10 | 0.295345E+09 | 242.16 | 01-SEP-19:10 |
October | 0.283425E+09 | 273.10 | 02-OCT-19:10 | 0.305393E+09 | 242.16 | 02-OCT-19:10 |
November | 0.274959E+09 | 273.10 | 01-NOV-19:10 | 0.296079E+09 | 242.16 | 01-NOV-19:10 |
December | 0.282770E+09 | 273.10 | 01-DEC-20:10 | 0.304889E+09 | 242.16 | 01-DEC-20:10 |
Annual Sum or Average | 0.333955E+10 | 0.359760E+10 | ||||
Minimum of Months | 0.256006E+09 | 273.10 | 0.275845E+09 | 242.16 | ||
Maximum of Months | 0.284518E+09 | 273.10 | 0.306219E+09 | 242.16 |
Report: ZoneElectricSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.350256E+09 | 337.37 | 02-JAN-20:10 | 0.576866E+10 | 4572.80 | 02-JAN-20:10 |
February | 0.316249E+09 | 337.37 | 01-FEB-20:10 | 0.520895E+10 | 4572.80 | 01-FEB-20:10 |
March | 0.351336E+09 | 337.37 | 01-MAR-20:10 | 0.578079E+10 | 4572.80 | 01-MAR-20:10 |
April | 0.338381E+09 | 337.37 | 03-APR-19:10 | 0.557545E+10 | 4572.80 | 03-APR-19:10 |
May | 0.350863E+09 | 337.37 | 01-MAY-19:10 | 0.577559E+10 | 4572.80 | 01-MAY-19:10 |
June | 0.339933E+09 | 337.37 | 01-JUN-19:10 | 0.559364E+10 | 4572.80 | 01-JUN-19:10 |
July | 0.349311E+09 | 337.37 | 03-JUL-19:10 | 0.575740E+10 | 4572.80 | 03-JUL-19:10 |
August | 0.351471E+09 | 337.37 | 01-AUG-19:10 | 0.578252E+10 | 4572.80 | 01-AUG-19:10 |
September | 0.338516E+09 | 337.37 | 01-SEP-19:10 | 0.557718E+10 | 4572.80 | 01-SEP-19:10 |
October | 0.350121E+09 | 337.37 | 02-OCT-19:10 | 0.576693E+10 | 4572.80 | 02-OCT-19:10 |
November | 0.339663E+09 | 337.37 | 01-NOV-19:10 | 0.559104E+10 | 4572.80 | 01-NOV-19:10 |
December | 0.349311E+09 | 337.37 | 01-DEC-20:10 | 0.575740E+10 | 4572.80 | 01-DEC-20:10 |
Annual Sum or Average | 0.412541E+10 | 0.679355E+11 | ||||
Minimum of Months | 0.316249E+09 | 337.37 | 0.520895E+10 | 4572.80 | ||
Maximum of Months | 0.351471E+09 | 337.37 | 0.578252E+10 | 4572.80 |
Report: ZoneElectricSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.226040E+10 | 2177.23 | 02-JAN-20:10 | 0.121771E+10 | 965.27 | 02-JAN-20:10 |
February | 0.204093E+10 | 2177.23 | 01-FEB-20:10 | 0.109956E+10 | 965.27 | 01-FEB-20:10 |
March | 0.226736E+10 | 2177.23 | 01-MAR-20:10 | 0.122027E+10 | 965.27 | 01-MAR-20:10 |
April | 0.218376E+10 | 2177.23 | 03-APR-19:10 | 0.117692E+10 | 965.27 | 03-APR-19:10 |
May | 0.226431E+10 | 2177.23 | 01-MAY-19:10 | 0.121917E+10 | 965.27 | 01-MAY-19:10 |
June | 0.219377E+10 | 2177.23 | 01-JUN-19:10 | 0.118076E+10 | 965.27 | 01-JUN-19:10 |
July | 0.225430E+10 | 2177.23 | 03-JUL-19:10 | 0.121533E+10 | 965.27 | 03-JUL-19:10 |
August | 0.226823E+10 | 2177.23 | 01-AUG-19:10 | 0.122063E+10 | 965.27 | 01-AUG-19:10 |
September | 0.218463E+10 | 2177.23 | 01-SEP-19:10 | 0.117729E+10 | 965.27 | 01-SEP-19:10 |
October | 0.225952E+10 | 2177.23 | 02-OCT-19:10 | 0.121734E+10 | 965.27 | 02-OCT-19:10 |
November | 0.219203E+10 | 2177.23 | 01-NOV-19:10 | 0.118021E+10 | 965.27 | 01-NOV-19:10 |
December | 0.225430E+10 | 2177.23 | 01-DEC-20:10 | 0.121533E+10 | 965.27 | 01-DEC-20:10 |
Annual Sum or Average | 0.266236E+11 | 0.143405E+11 | ||||
Minimum of Months | 0.204093E+10 | 2177.23 | 0.109956E+10 | 965.27 | ||
Maximum of Months | 0.226823E+10 | 2177.23 | 0.122063E+10 | 965.27 |
Report: ZoneElectricSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.123020E+11 | 11849.32 | 02-JAN-20:10 | 0.126520E+11 | 10029.21 | 02-JAN-20:10 |
February | 0.111075E+11 | 11849.32 | 01-FEB-20:10 | 0.114244E+11 | 10029.21 | 01-FEB-20:10 |
March | 0.123399E+11 | 11849.32 | 01-MAR-20:10 | 0.126786E+11 | 10029.21 | 01-MAR-20:10 |
April | 0.118849E+11 | 11849.32 | 03-APR-19:10 | 0.122282E+11 | 10029.21 | 03-APR-19:10 |
May | 0.123233E+11 | 11849.32 | 01-MAY-19:10 | 0.126672E+11 | 10029.21 | 01-MAY-19:10 |
June | 0.119394E+11 | 11849.32 | 01-JUN-19:10 | 0.122682E+11 | 10029.21 | 01-JUN-19:10 |
July | 0.122688E+11 | 11849.32 | 03-JUL-19:10 | 0.126273E+11 | 10029.21 | 03-JUL-19:10 |
August | 0.123446E+11 | 11849.32 | 01-AUG-19:10 | 0.126824E+11 | 10029.21 | 01-AUG-19:10 |
September | 0.118896E+11 | 11849.32 | 01-SEP-19:10 | 0.122320E+11 | 10029.21 | 01-SEP-19:10 |
October | 0.122972E+11 | 11849.32 | 02-OCT-19:10 | 0.126482E+11 | 10029.21 | 02-OCT-19:10 |
November | 0.119299E+11 | 11849.32 | 01-NOV-19:10 | 0.122624E+11 | 10029.21 | 01-NOV-19:10 |
December | 0.122688E+11 | 11849.32 | 01-DEC-20:10 | 0.126273E+11 | 10029.21 | 01-DEC-20:10 |
Annual Sum or Average | 0.144896E+12 | 0.148998E+12 | ||||
Minimum of Months | 0.111075E+11 | 11849.32 | 0.114244E+11 | 10029.21 | ||
Maximum of Months | 0.123446E+11 | 11849.32 | 0.126824E+11 | 10029.21 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.434056E+09 | 392.73 | 01-JAN-19:10 | 0.261068E+09 | 237.06 | 01-JAN-08:09 |
February | 0.391995E+09 | 392.73 | 01-FEB-20:10 | 0.235798E+09 | 237.06 | 01-FEB-07:10 |
March | 0.430607E+09 | 392.73 | 01-MAR-20:10 | 0.260708E+09 | 237.06 | 01-MAR-07:10 |
April | 0.420554E+09 | 392.73 | 01-APR-18:10 | 0.252705E+09 | 237.06 | 01-APR-07:10 |
May | 0.432331E+09 | 392.73 | 01-MAY-19:10 | 0.260888E+09 | 237.06 | 01-MAY-06:10 |
June | 0.417218E+09 | 392.73 | 01-JUN-19:10 | 0.252344E+09 | 237.06 | 01-JUN-06:10 |
July | 0.435725E+09 | 392.73 | 01-JUL-18:10 | 0.261248E+09 | 237.06 | 01-JUL-07:10 |
August | 0.430607E+09 | 392.73 | 01-AUG-19:10 | 0.260708E+09 | 237.06 | 01-AUG-06:10 |
September | 0.420667E+09 | 392.73 | 01-SEP-19:10 | 0.252705E+09 | 237.06 | 01-SEP-06:10 |
October | 0.434000E+09 | 392.73 | 01-OCT-18:10 | 0.261068E+09 | 237.06 | 01-OCT-07:10 |
November | 0.418886E+09 | 392.73 | 01-NOV-19:10 | 0.252524E+09 | 237.06 | 01-NOV-06:10 |
December | 0.435781E+09 | 392.73 | 01-DEC-20:10 | 0.261248E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.510243E+10 | 0.307301E+10 | ||||
Minimum of Months | 0.391995E+09 | 392.73 | 0.235798E+09 | 237.06 | ||
Maximum of Months | 0.435781E+09 | 392.73 | 0.261248E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.434005E+09 | 392.68 | 01-JAN-19:10 | 0.261038E+09 | 237.03 | 01-JAN-08:09 |
February | 0.391949E+09 | 392.68 | 01-FEB-20:10 | 0.235770E+09 | 237.03 | 01-FEB-07:10 |
March | 0.430556E+09 | 392.68 | 01-MAR-20:10 | 0.260677E+09 | 237.03 | 01-MAR-07:10 |
April | 0.420505E+09 | 392.68 | 01-APR-18:10 | 0.252675E+09 | 237.03 | 01-APR-07:10 |
May | 0.432281E+09 | 392.68 | 01-MAY-19:10 | 0.260857E+09 | 237.03 | 01-MAY-06:10 |
June | 0.417169E+09 | 392.68 | 01-JUN-19:10 | 0.252315E+09 | 237.03 | 01-JUN-06:10 |
July | 0.435674E+09 | 392.68 | 01-JUL-18:10 | 0.261218E+09 | 237.03 | 01-JUL-07:10 |
August | 0.430556E+09 | 392.68 | 01-AUG-19:10 | 0.260677E+09 | 237.03 | 01-AUG-06:10 |
September | 0.420618E+09 | 392.68 | 01-SEP-19:10 | 0.252675E+09 | 237.03 | 01-SEP-06:10 |
October | 0.433949E+09 | 392.68 | 01-OCT-18:10 | 0.261038E+09 | 237.03 | 01-OCT-07:10 |
November | 0.418837E+09 | 392.68 | 01-NOV-19:10 | 0.252495E+09 | 237.03 | 01-NOV-06:10 |
December | 0.435730E+09 | 392.68 | 01-DEC-20:10 | 0.261218E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.510183E+10 | 0.307265E+10 | ||||
Minimum of Months | 0.391949E+09 | 392.68 | 0.235770E+09 | 237.03 | ||
Maximum of Months | 0.435730E+09 | 392.68 | 0.261218E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.272788E+09 | 246.81 | 01-JAN-19:10 | 0.255708E+09 | 232.19 | 01-JAN-08:09 |
February | 0.246354E+09 | 246.81 | 01-FEB-20:10 | 0.230956E+09 | 232.19 | 01-FEB-07:10 |
March | 0.270620E+09 | 246.81 | 01-MAR-20:10 | 0.255355E+09 | 232.19 | 01-MAR-07:10 |
April | 0.264302E+09 | 246.81 | 01-APR-18:10 | 0.247516E+09 | 232.19 | 01-APR-07:10 |
May | 0.271704E+09 | 246.81 | 01-MAY-19:10 | 0.255532E+09 | 232.19 | 01-MAY-06:10 |
June | 0.262205E+09 | 246.81 | 01-JUN-19:10 | 0.247163E+09 | 232.19 | 01-JUN-06:10 |
July | 0.273836E+09 | 246.81 | 01-JUL-18:10 | 0.255885E+09 | 232.19 | 01-JUL-07:10 |
August | 0.270620E+09 | 246.81 | 01-AUG-19:10 | 0.255355E+09 | 232.19 | 01-AUG-06:10 |
September | 0.264373E+09 | 246.81 | 01-SEP-19:10 | 0.247516E+09 | 232.19 | 01-SEP-06:10 |
October | 0.272752E+09 | 246.81 | 01-OCT-18:10 | 0.255708E+09 | 232.19 | 01-OCT-07:10 |
November | 0.263254E+09 | 246.81 | 01-NOV-19:10 | 0.247340E+09 | 232.19 | 01-NOV-06:10 |
December | 0.273872E+09 | 246.81 | 01-DEC-20:10 | 0.255885E+09 | 232.19 | 01-DEC-07:10 |
Annual Sum or Average | 0.320668E+10 | 0.300992E+10 | ||||
Minimum of Months | 0.246354E+09 | 246.81 | 0.230956E+09 | 232.19 | ||
Maximum of Months | 0.273872E+09 | 246.81 | 0.255885E+09 | 232.19 |
Report: ZoneElectricSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.272862E+09 | 246.88 | 01-JAN-19:10 | 0.255778E+09 | 232.26 | 01-JAN-08:09 |
February | 0.246421E+09 | 246.88 | 01-FEB-20:10 | 0.231020E+09 | 232.26 | 01-FEB-07:10 |
March | 0.270694E+09 | 246.88 | 01-MAR-20:10 | 0.255425E+09 | 232.26 | 01-MAR-07:10 |
April | 0.264375E+09 | 246.88 | 01-APR-18:10 | 0.247584E+09 | 232.26 | 01-APR-07:10 |
May | 0.271778E+09 | 246.88 | 01-MAY-19:10 | 0.255602E+09 | 232.26 | 01-MAY-06:10 |
June | 0.262277E+09 | 246.88 | 01-JUN-19:10 | 0.247231E+09 | 232.26 | 01-JUN-06:10 |
July | 0.273911E+09 | 246.88 | 01-JUL-18:10 | 0.255955E+09 | 232.26 | 01-JUL-07:10 |
August | 0.270694E+09 | 246.88 | 01-AUG-19:10 | 0.255425E+09 | 232.26 | 01-AUG-06:10 |
September | 0.264446E+09 | 246.88 | 01-SEP-19:10 | 0.247584E+09 | 232.26 | 01-SEP-06:10 |
October | 0.272827E+09 | 246.88 | 01-OCT-18:10 | 0.255778E+09 | 232.26 | 01-OCT-07:10 |
November | 0.263326E+09 | 246.88 | 01-NOV-19:10 | 0.247408E+09 | 232.26 | 01-NOV-06:10 |
December | 0.273947E+09 | 246.88 | 01-DEC-20:10 | 0.255955E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.320756E+10 | 0.301074E+10 | ||||
Minimum of Months | 0.246421E+09 | 246.88 | 0.231020E+09 | 232.26 | ||
Maximum of Months | 0.273947E+09 | 246.88 | 0.255955E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.434056E+09 | 392.73 | 01-JAN-19:10 | 0.261068E+09 | 237.06 | 01-JAN-08:09 |
February | 0.391995E+09 | 392.73 | 01-FEB-20:10 | 0.235798E+09 | 237.06 | 01-FEB-07:10 |
March | 0.430607E+09 | 392.73 | 01-MAR-20:10 | 0.260708E+09 | 237.06 | 01-MAR-07:10 |
April | 0.420554E+09 | 392.73 | 01-APR-18:10 | 0.252705E+09 | 237.06 | 01-APR-07:10 |
May | 0.432331E+09 | 392.73 | 01-MAY-19:10 | 0.260888E+09 | 237.06 | 01-MAY-06:10 |
June | 0.417218E+09 | 392.73 | 01-JUN-19:10 | 0.252344E+09 | 237.06 | 01-JUN-06:10 |
July | 0.435725E+09 | 392.73 | 01-JUL-18:10 | 0.261248E+09 | 237.06 | 01-JUL-07:10 |
August | 0.430607E+09 | 392.73 | 01-AUG-19:10 | 0.260708E+09 | 237.06 | 01-AUG-06:10 |
September | 0.420667E+09 | 392.73 | 01-SEP-19:10 | 0.252705E+09 | 237.06 | 01-SEP-06:10 |
October | 0.434000E+09 | 392.73 | 01-OCT-18:10 | 0.261068E+09 | 237.06 | 01-OCT-07:10 |
November | 0.418886E+09 | 392.73 | 01-NOV-19:10 | 0.252524E+09 | 237.06 | 01-NOV-06:10 |
December | 0.435781E+09 | 392.73 | 01-DEC-20:10 | 0.261248E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.510243E+10 | 0.307301E+10 | ||||
Minimum of Months | 0.391995E+09 | 392.73 | 0.235798E+09 | 237.06 | ||
Maximum of Months | 0.435781E+09 | 392.73 | 0.261248E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.434005E+09 | 392.68 | 01-JAN-19:10 | 0.261038E+09 | 237.03 | 01-JAN-08:09 |
February | 0.391949E+09 | 392.68 | 01-FEB-20:10 | 0.235770E+09 | 237.03 | 01-FEB-07:10 |
March | 0.430556E+09 | 392.68 | 01-MAR-20:10 | 0.260677E+09 | 237.03 | 01-MAR-07:10 |
April | 0.420505E+09 | 392.68 | 01-APR-18:10 | 0.252675E+09 | 237.03 | 01-APR-07:10 |
May | 0.432281E+09 | 392.68 | 01-MAY-19:10 | 0.260857E+09 | 237.03 | 01-MAY-06:10 |
June | 0.417169E+09 | 392.68 | 01-JUN-19:10 | 0.252315E+09 | 237.03 | 01-JUN-06:10 |
July | 0.435674E+09 | 392.68 | 01-JUL-18:10 | 0.261218E+09 | 237.03 | 01-JUL-07:10 |
August | 0.430556E+09 | 392.68 | 01-AUG-19:10 | 0.260677E+09 | 237.03 | 01-AUG-06:10 |
September | 0.420618E+09 | 392.68 | 01-SEP-19:10 | 0.252675E+09 | 237.03 | 01-SEP-06:10 |
October | 0.433949E+09 | 392.68 | 01-OCT-18:10 | 0.261038E+09 | 237.03 | 01-OCT-07:10 |
November | 0.418837E+09 | 392.68 | 01-NOV-19:10 | 0.252495E+09 | 237.03 | 01-NOV-06:10 |
December | 0.435730E+09 | 392.68 | 01-DEC-20:10 | 0.261218E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.510183E+10 | 0.307265E+10 | ||||
Minimum of Months | 0.391949E+09 | 392.68 | 0.235770E+09 | 237.03 | ||
Maximum of Months | 0.435730E+09 | 392.68 | 0.261218E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.133160E+10 | 1282.60 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.120231E+10 | 1282.60 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.133570E+10 | 1282.60 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.128645E+10 | 1282.60 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.133391E+10 | 1282.60 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.129235E+10 | 1282.60 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.132801E+10 | 1282.60 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.133622E+10 | 1282.60 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.128696E+10 | 1282.60 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.133109E+10 | 1282.60 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.129132E+10 | 1282.60 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.132801E+10 | 1282.60 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.156839E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.120231E+10 | 1282.60 | 0.00 | 0.00 | |
Maximum of Months | 0.133622E+10 | 1282.60 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.434056E+09 | 392.73 | 01-JAN-19:10 | 0.261068E+09 | 237.06 | 01-JAN-08:09 |
February | 0.391995E+09 | 392.73 | 01-FEB-20:10 | 0.235798E+09 | 237.06 | 01-FEB-07:10 |
March | 0.430607E+09 | 392.73 | 01-MAR-20:10 | 0.260708E+09 | 237.06 | 01-MAR-07:10 |
April | 0.420554E+09 | 392.73 | 01-APR-18:10 | 0.252705E+09 | 237.06 | 01-APR-07:10 |
May | 0.432331E+09 | 392.73 | 01-MAY-19:10 | 0.260888E+09 | 237.06 | 01-MAY-06:10 |
June | 0.417218E+09 | 392.73 | 01-JUN-19:10 | 0.252344E+09 | 237.06 | 01-JUN-06:10 |
July | 0.435725E+09 | 392.73 | 01-JUL-18:10 | 0.261248E+09 | 237.06 | 01-JUL-07:10 |
August | 0.430607E+09 | 392.73 | 01-AUG-19:10 | 0.260708E+09 | 237.06 | 01-AUG-06:10 |
September | 0.420667E+09 | 392.73 | 01-SEP-19:10 | 0.252705E+09 | 237.06 | 01-SEP-06:10 |
October | 0.434000E+09 | 392.73 | 01-OCT-18:10 | 0.261068E+09 | 237.06 | 01-OCT-07:10 |
November | 0.418886E+09 | 392.73 | 01-NOV-19:10 | 0.252524E+09 | 237.06 | 01-NOV-06:10 |
December | 0.435781E+09 | 392.73 | 01-DEC-20:10 | 0.261248E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.510243E+10 | 0.307301E+10 | ||||
Minimum of Months | 0.391995E+09 | 392.73 | 0.235798E+09 | 237.06 | ||
Maximum of Months | 0.435781E+09 | 392.73 | 0.261248E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.434005E+09 | 392.68 | 01-JAN-19:10 | 0.261038E+09 | 237.03 | 01-JAN-08:09 |
February | 0.391949E+09 | 392.68 | 01-FEB-20:10 | 0.235770E+09 | 237.03 | 01-FEB-07:10 |
March | 0.430556E+09 | 392.68 | 01-MAR-20:10 | 0.260677E+09 | 237.03 | 01-MAR-07:10 |
April | 0.420505E+09 | 392.68 | 01-APR-18:10 | 0.252675E+09 | 237.03 | 01-APR-07:10 |
May | 0.432281E+09 | 392.68 | 01-MAY-19:10 | 0.260857E+09 | 237.03 | 01-MAY-06:10 |
June | 0.417169E+09 | 392.68 | 01-JUN-19:10 | 0.252315E+09 | 237.03 | 01-JUN-06:10 |
July | 0.435674E+09 | 392.68 | 01-JUL-18:10 | 0.261218E+09 | 237.03 | 01-JUL-07:10 |
August | 0.430556E+09 | 392.68 | 01-AUG-19:10 | 0.260677E+09 | 237.03 | 01-AUG-06:10 |
September | 0.420618E+09 | 392.68 | 01-SEP-19:10 | 0.252675E+09 | 237.03 | 01-SEP-06:10 |
October | 0.433949E+09 | 392.68 | 01-OCT-18:10 | 0.261038E+09 | 237.03 | 01-OCT-07:10 |
November | 0.418837E+09 | 392.68 | 01-NOV-19:10 | 0.252495E+09 | 237.03 | 01-NOV-06:10 |
December | 0.435730E+09 | 392.68 | 01-DEC-20:10 | 0.261218E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.510183E+10 | 0.307265E+10 | ||||
Minimum of Months | 0.391949E+09 | 392.68 | 0.235770E+09 | 237.03 | ||
Maximum of Months | 0.435730E+09 | 392.68 | 0.261218E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.272862E+09 | 246.88 | 01-JAN-19:10 | 0.255778E+09 | 232.26 | 01-JAN-08:09 |
February | 0.246421E+09 | 246.88 | 01-FEB-20:10 | 0.231020E+09 | 232.26 | 01-FEB-07:10 |
March | 0.270694E+09 | 246.88 | 01-MAR-20:10 | 0.255425E+09 | 232.26 | 01-MAR-07:10 |
April | 0.264375E+09 | 246.88 | 01-APR-18:10 | 0.247584E+09 | 232.26 | 01-APR-07:10 |
May | 0.271778E+09 | 246.88 | 01-MAY-19:10 | 0.255602E+09 | 232.26 | 01-MAY-06:10 |
June | 0.262277E+09 | 246.88 | 01-JUN-19:10 | 0.247231E+09 | 232.26 | 01-JUN-06:10 |
July | 0.273911E+09 | 246.88 | 01-JUL-18:10 | 0.255955E+09 | 232.26 | 01-JUL-07:10 |
August | 0.270694E+09 | 246.88 | 01-AUG-19:10 | 0.255425E+09 | 232.26 | 01-AUG-06:10 |
September | 0.264446E+09 | 246.88 | 01-SEP-19:10 | 0.247584E+09 | 232.26 | 01-SEP-06:10 |
October | 0.272827E+09 | 246.88 | 01-OCT-18:10 | 0.255778E+09 | 232.26 | 01-OCT-07:10 |
November | 0.263326E+09 | 246.88 | 01-NOV-19:10 | 0.247408E+09 | 232.26 | 01-NOV-06:10 |
December | 0.273947E+09 | 246.88 | 01-DEC-20:10 | 0.255955E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.320756E+10 | 0.301074E+10 | ||||
Minimum of Months | 0.246421E+09 | 246.88 | 0.231020E+09 | 232.26 | ||
Maximum of Months | 0.273947E+09 | 246.88 | 0.255955E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.396945E+10 | 3823.39 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.358405E+10 | 3823.39 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.398168E+10 | 3823.39 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.383486E+10 | 3823.39 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.397633E+10 | 3823.39 | 01-MAY-19:10 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.385245E+10 | 3823.39 | 01-JUN-19:10 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.395874E+10 | 3823.39 | 03-JUL-19:10 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.398321E+10 | 3823.39 | 01-AUG-19:10 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.383639E+10 | 3823.39 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.396792E+10 | 3823.39 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.384939E+10 | 3823.39 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.395874E+10 | 3823.39 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.467532E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.358405E+10 | 3823.39 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.398321E+10 | 3823.39 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.396945E+10 | 3823.39 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.358405E+10 | 3823.39 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.398168E+10 | 3823.39 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.383486E+10 | 3823.39 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.397633E+10 | 3823.39 | 01-MAY-19:10 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.385245E+10 | 3823.39 | 01-JUN-19:10 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.395874E+10 | 3823.39 | 03-JUL-19:10 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.398321E+10 | 3823.39 | 01-AUG-19:10 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.383639E+10 | 3823.39 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.396792E+10 | 3823.39 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.384939E+10 | 3823.39 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.395874E+10 | 3823.39 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.467532E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.358405E+10 | 3823.39 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.398321E+10 | 3823.39 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.105977E+10 | 1020.78 | 02-JAN-20:10 | 0.373720E+11 | 16686.59 | 01-JAN-07:10 |
February | 0.956878E+09 | 1020.78 | 01-FEB-20:10 | 0.337554E+11 | 16686.59 | 01-FEB-07:10 |
March | 0.106304E+10 | 1020.78 | 01-MAR-20:10 | 0.373720E+11 | 16686.59 | 01-MAR-07:10 |
April | 0.102384E+10 | 1020.78 | 03-APR-19:10 | 0.361665E+11 | 16686.59 | 01-APR-06:10 |
May | 0.106161E+10 | 1020.78 | 01-MAY-19:10 | 0.373720E+11 | 16686.59 | 01-MAY-06:10 |
June | 0.102854E+10 | 1020.78 | 01-JUN-19:10 | 0.361665E+11 | 16686.59 | 01-JUN-06:10 |
July | 0.105691E+10 | 1020.78 | 03-JUL-19:10 | 0.373720E+11 | 16686.59 | 01-JUL-06:10 |
August | 0.106345E+10 | 1020.78 | 01-AUG-19:10 | 0.373720E+11 | 16686.59 | 01-AUG-06:10 |
September | 0.102425E+10 | 1020.78 | 01-SEP-19:10 | 0.361665E+11 | 16686.59 | 01-SEP-06:10 |
October | 0.105936E+10 | 1020.78 | 02-OCT-19:10 | 0.373720E+11 | 16686.59 | 01-OCT-06:10 |
November | 0.102772E+10 | 1020.78 | 01-NOV-19:10 | 0.361665E+11 | 16686.59 | 01-NOV-06:10 |
December | 0.105691E+10 | 1020.78 | 01-DEC-20:10 | 0.373720E+11 | 16686.59 | 01-DEC-07:10 |
Annual Sum or Average | 0.124823E+11 | 0.440025E+12 | ||||
Minimum of Months | 0.956878E+09 | 1020.78 | 0.337554E+11 | 16686.59 | ||
Maximum of Months | 0.106345E+10 | 1020.78 | 0.373720E+11 | 16686.59 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.140929E+10 | 1357.44 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.127246E+10 | 1357.44 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.141364E+10 | 1357.44 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.136151E+10 | 1357.44 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.141173E+10 | 1357.44 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.136775E+10 | 1357.44 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.140549E+10 | 1357.44 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.141418E+10 | 1357.44 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.136205E+10 | 1357.44 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.140875E+10 | 1357.44 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.136667E+10 | 1357.44 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.140549E+10 | 1357.44 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.165990E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.127246E+10 | 1357.44 | 0.00 | 0.00 | |
Maximum of Months | 0.141418E+10 | 1357.44 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.195762E+11 | 0.140333E+11 | 0.127587E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.176991E+11 | 0.126708E+11 | 0.115208E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.196682E+11 | 0.140766E+11 | 0.127855E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.189781E+11 | 0.135575E+11 | 0.123314E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.196176E+11 | 0.140576E+11 | 0.127741E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.190195E+11 | 0.136197E+11 | 0.123716E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.195762E+11 | 0.139955E+11 | 0.127338E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.196590E+11 | 0.140820E+11 | 0.127894E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.189689E+11 | 0.135629E+11 | 0.123352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.195854E+11 | 0.140279E+11 | 0.127549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.189367E+11 | 0.136089E+11 | 0.123659E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.195762E+11 | 0.139955E+11 | 0.127338E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.230861E+12 | 0.165288E+12 | 0.150255E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.176991E+11 | 0.126708E+11 | 0.115208E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.196682E+11 | 0.140820E+11 | 0.127894E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.199054E+10 | 0.713551E+09 | 0.864900E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120891E+10 |
February | 0.179968E+10 | 0.644271E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.980411E+09 |
March | 0.199990E+10 | 0.715750E+09 | 0.866718E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.911079E+09 |
April | 0.192973E+10 | 0.689358E+09 | 0.835931E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 942925.29 | 0.541192E+09 |
May | 0.199475E+10 | 0.714788E+09 | 0.865939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13153637.97 | 0.256163E+09 |
June | 0.193394E+10 | 0.692519E+09 | 0.838659E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 32616003.58 | 0.125800E+09 |
July | 0.199054E+10 | 0.711626E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 42507406.12 | 88292742.24 |
August | 0.199896E+10 | 0.716025E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18910059.74 | 0.118361E+09 |
September | 0.192879E+10 | 0.689633E+09 | 0.836191E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1289593.01 | 0.271671E+09 |
October | 0.199148E+10 | 0.713276E+09 | 0.864640E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.508777E+09 |
November | 0.192552E+10 | 0.691970E+09 | 0.838269E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.738586E+09 |
December | 0.199054E+10 | 0.711626E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115528E+10 |
Annual Sum or Average | 0.234744E+11 | 0.840439E+10 | 0.101856E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109420E+09 | 0.690452E+10 |
Minimum of Months | 0.179968E+10 | 0.644271E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88292742.24 |
Maximum of Months | 0.199990E+10 | 0.716025E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 42507406.12 | 0.120891E+10 |
Report: SpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.230505E+10 | 0.826294E+09 | 0.100156E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.472298E+09 |
February | 0.208403E+10 | 0.746069E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.381297E+09 |
March | 0.231589E+10 | 0.828841E+09 | 0.100366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.352474E+09 |
April | 0.223463E+10 | 0.798279E+09 | 0.968011E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 418750.27 | 0.208379E+09 |
May | 0.230993E+10 | 0.827727E+09 | 0.100276E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5297752.25 | 99394782.82 |
June | 0.223950E+10 | 0.801940E+09 | 0.971170E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12675398.81 | 49386960.02 |
July | 0.230505E+10 | 0.824066E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16841672.44 | 35159628.23 |
August | 0.231480E+10 | 0.829160E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8189328.98 | 46615969.34 |
September | 0.223354E+10 | 0.798597E+09 | 0.968312E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 733073.36 | 0.104439E+09 |
October | 0.230614E+10 | 0.825976E+09 | 0.100126E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35247.17 | 0.195350E+09 |
November | 0.222975E+10 | 0.801303E+09 | 0.970719E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.284801E+09 |
December | 0.230505E+10 | 0.824066E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.451597E+09 |
Annual Sum or Average | 0.271834E+11 | 0.973232E+10 | 0.117950E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 44191223.27 | 0.268119E+10 |
Minimum of Months | 0.208403E+10 | 0.746069E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35159628.23 |
Maximum of Months | 0.231589E+10 | 0.829160E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16841672.44 | 0.472298E+09 |
Report: SpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.487480E+09 | 0.154452E+10 | 0.105898E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111521E+10 |
February | 0.440737E+09 | 0.139456E+10 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.904234E+09 |
March | 0.489771E+09 | 0.154928E+10 | 0.106120E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.834585E+09 |
April | 0.472586E+09 | 0.149215E+10 | 0.102351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1001031.39 | 0.491684E+09 |
May | 0.488511E+09 | 0.154719E+10 | 0.106025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12633759.19 | 0.233238E+09 |
June | 0.473617E+09 | 0.149899E+10 | 0.102685E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30266156.61 | 0.115366E+09 |
July | 0.487480E+09 | 0.154035E+10 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40090864.15 | 81328686.09 |
August | 0.489542E+09 | 0.154987E+10 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19515266.81 | 0.108376E+09 |
September | 0.472357E+09 | 0.149274E+10 | 0.102382E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1735866.01 | 0.245461E+09 |
October | 0.487709E+09 | 0.154392E+10 | 0.105866E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 83374.87 | 0.461041E+09 |
November | 0.471555E+09 | 0.149780E+10 | 0.102637E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.673007E+09 |
December | 0.487480E+09 | 0.154035E+10 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107134E+10 |
Annual Sum or Average | 0.574883E+10 | 0.181917E+11 | 0.124712E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105326E+09 | 0.633487E+10 |
Minimum of Months | 0.440737E+09 | 0.139456E+10 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81328686.09 |
Maximum of Months | 0.489771E+09 | 0.154987E+10 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40090864.15 | 0.111521E+10 |
Report: SpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.374985E+09 | 0.283535E+09 | 0.305485E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.642208E+09 |
February | 0.339028E+09 | 0.256006E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.520915E+09 |
March | 0.376747E+09 | 0.284409E+09 | 0.306128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.481488E+09 |
April | 0.363528E+09 | 0.273921E+09 | 0.295253E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 577986.18 | 0.283672E+09 |
May | 0.375778E+09 | 0.284026E+09 | 0.305852E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7336019.45 | 0.134310E+09 |
June | 0.364321E+09 | 0.275178E+09 | 0.296217E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17639522.71 | 66199102.88 |
July | 0.374985E+09 | 0.282770E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 23328644.45 | 46423502.46 |
August | 0.376571E+09 | 0.284518E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11353953.72 | 62082970.87 |
September | 0.363352E+09 | 0.274031E+09 | 0.295345E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1002103.52 | 0.141492E+09 |
October | 0.375161E+09 | 0.283425E+09 | 0.305393E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 48081.22 | 0.265992E+09 |
November | 0.362735E+09 | 0.274959E+09 | 0.296079E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.388289E+09 |
December | 0.374985E+09 | 0.282770E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.616919E+09 |
Annual Sum or Average | 0.442217E+10 | 0.333955E+10 | 0.359760E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 61286311.24 | 0.364999E+10 |
Minimum of Months | 0.339028E+09 | 0.256006E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46423502.46 |
Maximum of Months | 0.376747E+09 | 0.284518E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 23328644.45 | 0.642208E+09 |
Report: SpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.154405E+10 | 0.350256E+09 | 0.576866E+10 | 0.501157E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148265E+10 |
February | 0.139600E+10 | 0.316249E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121725E+10 |
March | 0.155131E+10 | 0.351336E+09 | 0.578079E+10 | 0.502211E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114472E+10 |
April | 0.149688E+10 | 0.338381E+09 | 0.557545E+10 | 0.484372E+11 | 0.00 | 0.00 | 0.00 | 1243445.06 | 0.687578E+09 |
May | 0.154732E+10 | 0.350863E+09 | 0.577559E+10 | 0.501759E+11 | 0.00 | 0.00 | 0.00 | 16133969.13 | 0.332169E+09 |
June | 0.150015E+10 | 0.339933E+09 | 0.559364E+10 | 0.485952E+11 | 0.00 | 0.00 | 0.00 | 39250277.98 | 0.168343E+09 |
July | 0.154405E+10 | 0.349311E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 51824217.09 | 0.120290E+09 |
August | 0.155059E+10 | 0.351471E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 25102904.84 | 0.160473E+09 |
September | 0.149615E+10 | 0.338516E+09 | 0.557718E+10 | 0.484522E+11 | 0.00 | 0.00 | 0.00 | 2347156.78 | 0.350430E+09 |
October | 0.154478E+10 | 0.350121E+09 | 0.576693E+10 | 0.501006E+11 | 0.00 | 0.00 | 0.00 | 113623.47 | 0.646794E+09 |
November | 0.149361E+10 | 0.339663E+09 | 0.559104E+10 | 0.485726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.936219E+09 |
December | 0.154405E+10 | 0.349311E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142624E+10 |
Annual Sum or Average | 0.182090E+11 | 0.412541E+10 | 0.679355E+11 | 0.590196E+12 | 0.00 | 0.00 | 0.00 | 0.136016E+09 | 0.867315E+10 |
Minimum of Months | 0.139600E+10 | 0.316249E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120290E+09 |
Maximum of Months | 0.155131E+10 | 0.351471E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 51824217.09 | 0.148265E+10 |
Report: SpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.261570E+11 | 0.226040E+10 | 0.121771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.269155E+10 |
February | 0.236489E+11 | 0.204093E+10 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.217161E+10 |
March | 0.262800E+11 | 0.226736E+10 | 0.122027E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.201487E+10 |
April | 0.253579E+11 | 0.218376E+10 | 0.117692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2221703.13 | 0.119511E+10 |
May | 0.262123E+11 | 0.226431E+10 | 0.121917E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29990925.32 | 0.566050E+09 |
June | 0.254132E+11 | 0.219377E+10 | 0.118076E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 73227244.88 | 0.278679E+09 |
July | 0.261570E+11 | 0.225430E+10 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 96186605.89 | 0.196105E+09 |
August | 0.262677E+11 | 0.226823E+10 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44273419.05 | 0.262261E+09 |
September | 0.253456E+11 | 0.218463E+10 | 0.117729E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3395320.01 | 0.599068E+09 |
October | 0.261693E+11 | 0.225952E+10 | 0.121734E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112313E+10 |
November | 0.253025E+11 | 0.219203E+10 | 0.118021E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163247E+10 |
December | 0.261570E+11 | 0.225430E+10 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.256886E+10 |
Annual Sum or Average | 0.308468E+12 | 0.266236E+11 | 0.143405E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.249295E+09 | 0.152998E+11 |
Minimum of Months | 0.236489E+11 | 0.204093E+10 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.196105E+09 |
Maximum of Months | 0.262800E+11 | 0.226823E+10 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 96186605.89 | 0.269155E+10 |
Report: SpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.776503E+11 | 0.123020E+11 | 0.126520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.775882E+10 |
February | 0.702046E+11 | 0.111075E+11 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.624318E+10 |
March | 0.780153E+11 | 0.123399E+11 | 0.126786E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.576814E+10 |
April | 0.752779E+11 | 0.118849E+11 | 0.122282E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 6892561.10 | 0.341419E+10 |
May | 0.778146E+11 | 0.123233E+11 | 0.126672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 86900467.53 | 0.163611E+10 |
June | 0.754422E+11 | 0.119394E+11 | 0.122682E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.206692E+09 | 0.820198E+09 |
July | 0.776503E+11 | 0.122688E+11 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.275789E+09 | 0.589364E+09 |
August | 0.779788E+11 | 0.123446E+11 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133897E+09 | 0.778165E+09 |
September | 0.752414E+11 | 0.118896E+11 | 0.122320E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 11918113.46 | 0.171882E+10 |
October | 0.776868E+11 | 0.122972E+11 | 0.126482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 468224.86 | 0.320287E+10 |
November | 0.751137E+11 | 0.119299E+11 | 0.122624E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.466252E+10 |
December | 0.776503E+11 | 0.122688E+11 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.740897E+10 |
Annual Sum or Average | 0.915726E+12 | 0.144896E+12 | 0.148998E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.722557E+09 | 0.440013E+11 |
Minimum of Months | 0.702046E+11 | 0.111075E+11 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.589364E+09 |
Maximum of Months | 0.780153E+11 | 0.123446E+11 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.275789E+09 | 0.775882E+10 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.434056E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.766995E+09 |
February | 0.273974E+09 | 0.391995E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.588419E+09 |
March | 0.303685E+09 | 0.430607E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.533794E+09 |
April | 0.293479E+09 | 0.420554E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 436854.34 | 0.319023E+09 |
May | 0.303504E+09 | 0.432331E+09 | 0.260888E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5396903.25 | 0.157545E+09 |
June | 0.293842E+09 | 0.417218E+09 | 0.252344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14350030.62 | 79710503.84 |
July | 0.303141E+09 | 0.435725E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18433088.07 | 56827400.38 |
August | 0.303685E+09 | 0.430607E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7788799.81 | 75916779.54 |
September | 0.293479E+09 | 0.420667E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 497158.61 | 0.165385E+09 |
October | 0.303322E+09 | 0.434000E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17164.47 | 0.296787E+09 |
November | 0.293661E+09 | 0.418886E+09 | 0.252524E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.425335E+09 |
December | 0.303141E+09 | 0.435781E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.717041E+09 |
Annual Sum or Average | 0.357224E+10 | 0.510243E+10 | 0.307301E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46919999.18 | 0.418278E+10 |
Minimum of Months | 0.273974E+09 | 0.391995E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56827400.38 |
Maximum of Months | 0.303685E+09 | 0.435781E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18433088.07 | 0.766995E+09 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.434005E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.765321E+09 |
February | 0.273974E+09 | 0.391949E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.584179E+09 |
March | 0.303685E+09 | 0.430556E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.528571E+09 |
April | 0.293479E+09 | 0.420505E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 437944.88 | 0.315366E+09 |
May | 0.303504E+09 | 0.432281E+09 | 0.260857E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5423965.41 | 0.156548E+09 |
June | 0.293842E+09 | 0.417169E+09 | 0.252315E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14389292.53 | 79482168.53 |
July | 0.303141E+09 | 0.435674E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18517893.65 | 56731052.45 |
August | 0.303685E+09 | 0.430556E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7862974.85 | 75430173.31 |
September | 0.293479E+09 | 0.420618E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 524431.03 | 0.163662E+09 |
October | 0.303322E+09 | 0.433949E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17735.47 | 0.293692E+09 |
November | 0.293661E+09 | 0.418837E+09 | 0.252495E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.421756E+09 |
December | 0.303141E+09 | 0.435730E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.716346E+09 |
Annual Sum or Average | 0.357224E+10 | 0.510183E+10 | 0.307265E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47174237.82 | 0.415708E+10 |
Minimum of Months | 0.273974E+09 | 0.391949E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56731052.45 |
Maximum of Months | 0.303685E+09 | 0.435730E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18517893.65 | 0.765321E+09 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.272788E+09 | 0.255708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.207434E+09 |
February | 0.00 | 0.246354E+09 | 0.230956E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163223E+09 |
March | 0.00 | 0.270620E+09 | 0.255355E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150938E+09 |
April | 0.00 | 0.264302E+09 | 0.247516E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 72140.37 | 96045396.14 |
May | 0.00 | 0.271704E+09 | 0.255532E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1027072.05 | 51619598.90 |
June | 0.00 | 0.262205E+09 | 0.247163E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2786849.72 | 28898998.13 |
July | 0.00 | 0.273836E+09 | 0.255885E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3549518.28 | 22324626.54 |
August | 0.00 | 0.270620E+09 | 0.255355E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1370673.84 | 28717695.22 |
September | 0.00 | 0.264373E+09 | 0.247516E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 77361.59 | 54481837.92 |
October | 0.00 | 0.272752E+09 | 0.255708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90297996.42 |
November | 0.00 | 0.263254E+09 | 0.247340E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119094E+09 |
December | 0.00 | 0.273872E+09 | 0.255885E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192562E+09 |
Annual Sum or Average | 0.00 | 0.320668E+10 | 0.300992E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8883615.85 | 0.120564E+10 |
Minimum of Months | 0.00 | 0.246354E+09 | 0.230956E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22324626.54 |
Maximum of Months | 0.00 | 0.273872E+09 | 0.255885E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3549518.28 | 0.207434E+09 |
Report: SpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.272862E+09 | 0.255778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.214131E+09 |
February | 0.273974E+09 | 0.246421E+09 | 0.231020E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163875E+09 |
March | 0.303685E+09 | 0.270694E+09 | 0.255425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148623E+09 |
April | 0.293479E+09 | 0.264375E+09 | 0.247584E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 137692.58 | 88539637.65 |
May | 0.303504E+09 | 0.271778E+09 | 0.255602E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1627768.43 | 43424890.06 |
June | 0.293842E+09 | 0.262277E+09 | 0.247231E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4126948.56 | 21980300.48 |
July | 0.303141E+09 | 0.273911E+09 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5353137.60 | 15613918.84 |
August | 0.303685E+09 | 0.270694E+09 | 0.255425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2375837.28 | 20777097.00 |
September | 0.293479E+09 | 0.264446E+09 | 0.247584E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 189406.01 | 45611664.74 |
October | 0.303322E+09 | 0.272827E+09 | 0.255778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7137.58 | 83075666.94 |
November | 0.293661E+09 | 0.263326E+09 | 0.247408E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119321E+09 |
December | 0.303141E+09 | 0.273947E+09 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.200644E+09 |
Annual Sum or Average | 0.357224E+10 | 0.320756E+10 | 0.301074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13817928.04 | 0.116562E+10 |
Minimum of Months | 0.273974E+09 | 0.246421E+09 | 0.231020E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15613918.84 |
Maximum of Months | 0.303685E+09 | 0.273947E+09 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5353137.60 | 0.214131E+09 |
Report: SpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.434056E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.766561E+09 |
February | 0.273974E+09 | 0.391995E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.588402E+09 |
March | 0.303685E+09 | 0.430607E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.535449E+09 |
April | 0.293479E+09 | 0.420554E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 444138.59 | 0.320963E+09 |
May | 0.303504E+09 | 0.432331E+09 | 0.260888E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5415015.66 | 0.158374E+09 |
June | 0.293842E+09 | 0.417218E+09 | 0.252344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14341866.49 | 80486358.63 |
July | 0.303141E+09 | 0.435725E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18419061.99 | 57280103.65 |
August | 0.303685E+09 | 0.430607E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7813204.78 | 76402041.42 |
September | 0.293479E+09 | 0.420667E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 501583.27 | 0.165764E+09 |
October | 0.303322E+09 | 0.434000E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17622.06 | 0.297078E+09 |
November | 0.293661E+09 | 0.418886E+09 | 0.252524E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.425033E+09 |
December | 0.303141E+09 | 0.435781E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.716927E+09 |
Annual Sum or Average | 0.357224E+10 | 0.510243E+10 | 0.307301E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46952492.84 | 0.418872E+10 |
Minimum of Months | 0.273974E+09 | 0.391995E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57280103.65 |
Maximum of Months | 0.303685E+09 | 0.435781E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18419061.99 | 0.766561E+09 |
Report: SpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.434005E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.764953E+09 |
February | 0.273974E+09 | 0.391949E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.583947E+09 |
March | 0.303685E+09 | 0.430556E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.529930E+09 |
April | 0.293479E+09 | 0.420505E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 448207.98 | 0.318574E+09 |
May | 0.303504E+09 | 0.432281E+09 | 0.260857E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5426784.56 | 0.157978E+09 |
June | 0.293842E+09 | 0.417169E+09 | 0.252315E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14350131.30 | 80421926.46 |
July | 0.303141E+09 | 0.435674E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18439825.76 | 57218365.27 |
August | 0.303685E+09 | 0.430556E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7844523.85 | 76160768.73 |
September | 0.293479E+09 | 0.420618E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 505519.37 | 0.164818E+09 |
October | 0.303322E+09 | 0.433949E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18181.15 | 0.294203E+09 |
November | 0.293661E+09 | 0.418837E+09 | 0.252495E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.421631E+09 |
December | 0.303141E+09 | 0.435730E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.716283E+09 |
Annual Sum or Average | 0.357224E+10 | 0.510183E+10 | 0.307265E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47033173.98 | 0.416612E+10 |
Minimum of Months | 0.273974E+09 | 0.391949E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57218365.27 |
Maximum of Months | 0.303685E+09 | 0.435730E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18439825.76 | 0.764953E+09 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.385223E+10 | 0.133160E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.891708E+09 |
February | 0.348285E+10 | 0.120231E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.706099E+09 |
March | 0.387034E+10 | 0.133570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.644779E+09 |
April | 0.373454E+10 | 0.128645E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 711266.16 | 0.379647E+09 |
May | 0.386038E+10 | 0.133391E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8828316.19 | 0.181965E+09 |
June | 0.374269E+10 | 0.129235E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20792217.98 | 91182851.21 |
July | 0.385223E+10 | 0.132801E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27002031.99 | 67866471.79 |
August | 0.386853E+10 | 0.133622E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13157443.46 | 86920684.04 |
September | 0.373273E+10 | 0.128696E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1109130.11 | 0.190996E+09 |
October | 0.385404E+10 | 0.133109E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33284.09 | 0.356038E+09 |
November | 0.372639E+10 | 0.129132E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.518740E+09 |
December | 0.385223E+10 | 0.132801E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.846875E+09 |
Annual Sum or Average | 0.454292E+11 | 0.156839E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71633689.98 | 0.496282E+10 |
Minimum of Months | 0.348285E+10 | 0.120231E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67866471.79 |
Maximum of Months | 0.387034E+10 | 0.133622E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27002031.99 | 0.891708E+09 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.434056E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.767975E+09 |
February | 0.273974E+09 | 0.391995E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.588046E+09 |
March | 0.303685E+09 | 0.430607E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.533335E+09 |
April | 0.293479E+09 | 0.420554E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 426145.29 | 0.318971E+09 |
May | 0.303504E+09 | 0.432331E+09 | 0.260888E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5259981.88 | 0.158552E+09 |
June | 0.293842E+09 | 0.417218E+09 | 0.252344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14057420.75 | 80664310.72 |
July | 0.303141E+09 | 0.435725E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18043447.94 | 57583038.87 |
August | 0.303685E+09 | 0.430607E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7572073.60 | 76847828.43 |
September | 0.293479E+09 | 0.420667E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 474565.96 | 0.166202E+09 |
October | 0.303322E+09 | 0.434000E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15363.52 | 0.296424E+09 |
November | 0.293661E+09 | 0.418886E+09 | 0.252524E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.424743E+09 |
December | 0.303141E+09 | 0.435781E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.718020E+09 |
Annual Sum or Average | 0.357224E+10 | 0.510243E+10 | 0.307301E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45848998.95 | 0.418736E+10 |
Minimum of Months | 0.273974E+09 | 0.391995E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57583038.87 |
Maximum of Months | 0.303685E+09 | 0.435781E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18043447.94 | 0.767975E+09 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.434005E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.767111E+09 |
February | 0.273974E+09 | 0.391949E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.584696E+09 |
March | 0.303685E+09 | 0.430556E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.528744E+09 |
April | 0.293479E+09 | 0.420505E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 427987.32 | 0.315288E+09 |
May | 0.303504E+09 | 0.432281E+09 | 0.260857E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5280394.81 | 0.157722E+09 |
June | 0.293842E+09 | 0.417169E+09 | 0.252315E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14076299.99 | 80529474.61 |
July | 0.303141E+09 | 0.435674E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18095975.74 | 57516311.50 |
August | 0.303685E+09 | 0.430556E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7626208.90 | 76472516.71 |
September | 0.293479E+09 | 0.420618E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 481449.55 | 0.164564E+09 |
October | 0.303322E+09 | 0.433949E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16132.61 | 0.293131E+09 |
November | 0.293661E+09 | 0.418837E+09 | 0.252495E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.421690E+09 |
December | 0.303141E+09 | 0.435730E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.717677E+09 |
Annual Sum or Average | 0.357224E+10 | 0.510183E+10 | 0.307265E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46004448.92 | 0.416514E+10 |
Minimum of Months | 0.273974E+09 | 0.391949E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57516311.50 |
Maximum of Months | 0.303685E+09 | 0.435730E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18095975.74 | 0.767111E+09 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.272862E+09 | 0.255778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.397021E+09 |
February | 0.273974E+09 | 0.246421E+09 | 0.231020E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.305213E+09 |
March | 0.303685E+09 | 0.270694E+09 | 0.255425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.276523E+09 |
April | 0.293479E+09 | 0.264375E+09 | 0.247584E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 219951.86 | 0.164996E+09 |
May | 0.303504E+09 | 0.271778E+09 | 0.255602E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2706037.56 | 81311496.43 |
June | 0.293842E+09 | 0.262277E+09 | 0.247231E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7225102.59 | 41260228.23 |
July | 0.303141E+09 | 0.273911E+09 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9252403.71 | 29402058.94 |
August | 0.303685E+09 | 0.270694E+09 | 0.255425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3879801.84 | 39411179.29 |
September | 0.293479E+09 | 0.264446E+09 | 0.247584E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 243284.14 | 85694733.08 |
October | 0.303322E+09 | 0.272827E+09 | 0.255778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5185.60 | 0.153874E+09 |
November | 0.293661E+09 | 0.263326E+09 | 0.247408E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.220646E+09 |
December | 0.303141E+09 | 0.273947E+09 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.370578E+09 |
Annual Sum or Average | 0.357224E+10 | 0.320756E+10 | 0.301074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23531767.30 | 0.216593E+10 |
Minimum of Months | 0.273974E+09 | 0.246421E+09 | 0.231020E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29402058.94 |
Maximum of Months | 0.303685E+09 | 0.273947E+09 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9252403.71 | 0.397021E+09 |
Report: SpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.396945E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175779E+10 |
February | 0.415303E+11 | 0.358405E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141227E+10 |
March | 0.461508E+11 | 0.398168E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131209E+10 |
April | 0.445315E+11 | 0.383486E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1433600.58 | 0.789940E+09 |
May | 0.460320E+11 | 0.397633E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 17135376.25 | 0.396751E+09 |
June | 0.446286E+11 | 0.385245E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 39998001.82 | 0.211167E+09 |
July | 0.459349E+11 | 0.395874E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 54164388.37 | 0.159254E+09 |
August | 0.461292E+11 | 0.398321E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 26352442.57 | 0.203010E+09 |
September | 0.445099E+11 | 0.383639E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2386285.32 | 0.413521E+09 |
October | 0.459565E+11 | 0.396792E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 95192.76 | 0.743493E+09 |
November | 0.444343E+11 | 0.384939E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106550E+10 |
December | 0.459349E+11 | 0.395874E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.167826E+10 |
Annual Sum or Average | 0.541708E+12 | 0.467532E+11 | 0.175857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141565E+09 | 0.101430E+11 |
Minimum of Months | 0.415303E+11 | 0.358405E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159254E+09 |
Maximum of Months | 0.461508E+11 | 0.398321E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 54164388.37 | 0.175779E+10 |
Report: SpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.396945E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175587E+10 |
February | 0.415303E+11 | 0.358405E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141222E+10 |
March | 0.461508E+11 | 0.398168E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131376E+10 |
April | 0.445315E+11 | 0.383486E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1419039.62 | 0.792751E+09 |
May | 0.460320E+11 | 0.397633E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 16575646.21 | 0.400181E+09 |
June | 0.446286E+11 | 0.385245E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 38785711.74 | 0.214238E+09 |
July | 0.459349E+11 | 0.395874E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 52565101.22 | 0.162070E+09 |
August | 0.461292E+11 | 0.398321E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 25450286.93 | 0.206019E+09 |
September | 0.445099E+11 | 0.383639E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2312597.08 | 0.416708E+09 |
October | 0.459565E+11 | 0.396792E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 86160.11 | 0.746346E+09 |
November | 0.444343E+11 | 0.384939E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106760E+10 |
December | 0.459349E+11 | 0.395874E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.167724E+10 |
Annual Sum or Average | 0.541708E+12 | 0.467532E+11 | 0.175857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137195E+09 | 0.101650E+11 |
Minimum of Months | 0.415303E+11 | 0.358405E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162070E+09 |
Maximum of Months | 0.461508E+11 | 0.398321E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 52565101.22 | 0.175587E+10 |
Report: SpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.408770E+10 | 0.105977E+10 | 0.338870E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156367E+10 |
February | 0.369574E+10 | 0.956878E+09 | 0.306077E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128544E+10 |
March | 0.410691E+10 | 0.106304E+10 | 0.338870E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121970E+10 |
April | 0.396281E+10 | 0.102384E+10 | 0.327939E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 388853.58 | 0.759131E+09 |
May | 0.409635E+10 | 0.106161E+10 | 0.338870E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 6007073.94 | 0.395531E+09 |
June | 0.397146E+10 | 0.102854E+10 | 0.327939E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 18726988.24 | 0.217732E+09 |
July | 0.408770E+10 | 0.105691E+10 | 0.338870E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 21865214.95 | 0.162236E+09 |
August | 0.410499E+10 | 0.106345E+10 | 0.338870E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 7709702.69 | 0.213402E+09 |
September | 0.396089E+10 | 0.102425E+10 | 0.327939E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 306739.06 | 0.417235E+09 |
October | 0.408962E+10 | 0.105936E+10 | 0.338870E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.716537E+09 |
November | 0.395417E+10 | 0.102772E+10 | 0.327939E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100148E+10 |
December | 0.408770E+10 | 0.105691E+10 | 0.338870E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150300E+10 |
Annual Sum or Average | 0.482060E+11 | 0.124823E+11 | 0.398993E+12 | 0.359593E+12 | 0.00 | 0.00 | 0.00 | 55004572.46 | 0.945510E+10 |
Minimum of Months | 0.369574E+10 | 0.956878E+09 | 0.306077E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162236E+09 |
Maximum of Months | 0.410691E+10 | 0.106345E+10 | 0.338870E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 21865214.95 | 0.156367E+10 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.407704E+10 | 0.140929E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153112E+10 |
February | 0.368610E+10 | 0.127246E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123558E+10 |
March | 0.409620E+10 | 0.141364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114004E+10 |
April | 0.395248E+10 | 0.136151E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1281292.11 | 0.673622E+09 |
May | 0.408566E+10 | 0.141173E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15711752.80 | 0.320887E+09 |
June | 0.396110E+10 | 0.136775E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37763054.54 | 0.159131E+09 |
July | 0.407704E+10 | 0.140549E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49962627.27 | 0.112682E+09 |
August | 0.409429E+10 | 0.141418E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23549886.40 | 0.149894E+09 |
September | 0.395056E+10 | 0.136205E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1955213.76 | 0.338244E+09 |
October | 0.407896E+10 | 0.140875E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59926.56 | 0.632079E+09 |
November | 0.394385E+10 | 0.136667E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.920372E+09 |
December | 0.407704E+10 | 0.140549E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146470E+10 |
Annual Sum or Average | 0.480803E+11 | 0.165990E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130284E+09 | 0.867835E+10 |
Minimum of Months | 0.368610E+10 | 0.127246E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112682E+09 |
Maximum of Months | 0.409620E+10 | 0.141418E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49962627.27 | 0.153112E+10 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 11501.89 | 02-JAN-00:10 | 13517.00 | 02-JAN-20:10 | 10113.80 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 11501.89 | 01-FEB-00:10 | 13517.00 | 01-FEB-20:10 | 10113.80 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 11501.89 | 01-MAR-00:10 | 13517.00 | 01-MAR-20:10 | 10113.80 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 11501.89 | 01-APR-00:10 | 13517.00 | 03-APR-19:10 | 10113.80 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 11501.89 | 01-MAY-00:10 | 13517.00 | 01-MAY-19:10 | 10113.80 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 11501.89 | 01-JUN-00:10 | 13517.00 | 01-JUN-19:10 | 10113.80 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 11501.89 | 01-JUL-00:10 | 13517.00 | 03-JUL-19:10 | 10113.80 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 11501.89 | 01-AUG-00:10 | 13517.00 | 01-AUG-19:10 | 10113.80 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 11501.89 | 01-SEP-00:10 | 13517.00 | 01-SEP-19:10 | 10113.80 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 11501.89 | 01-OCT-23:10 | 13517.00 | 02-OCT-19:10 | 10113.80 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 11501.89 | 01-NOV-00:10 | 13517.00 | 01-NOV-19:10 | 10113.80 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 11501.89 | 01-DEC-00:10 | 13517.00 | 01-DEC-20:10 | 10113.80 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 11501.89 | 13517.00 | 10113.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 11501.89 | 13517.00 | 10113.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1169.53 | 02-JAN-00:10 | 687.30 | 02-JAN-20:10 | 685.60 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 599.54 | 27-JAN-20:55 |
February | 1169.53 | 01-FEB-00:10 | 687.30 | 01-FEB-20:10 | 685.60 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 602.18 | 24-FEB-22:23 |
March | 1169.53 | 01-MAR-00:10 | 687.30 | 01-MAR-20:10 | 685.60 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 600.99 | 12-MAR-03:41 |
April | 1169.53 | 01-APR-00:10 | 687.30 | 03-APR-19:10 | 685.60 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.39 | 23-APR-16:00 | 451.49 | 05-APR-06:00 |
May | 1169.53 | 01-MAY-00:10 | 687.30 | 01-MAY-19:10 | 685.60 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 92.44 | 25-MAY-18:00 | 312.15 | 01-MAY-06:00 |
June | 1169.53 | 01-JUN-00:10 | 687.30 | 01-JUN-19:10 | 685.60 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 151.25 | 29-JUN-16:00 | 242.38 | 04-JUN-05:00 |
July | 1169.53 | 01-JUL-00:10 | 687.30 | 03-JUL-19:10 | 685.60 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 108.10 | 15-JUL-15:00 | 176.82 | 02-JUL-05:00 |
August | 1169.53 | 01-AUG-00:10 | 687.30 | 01-AUG-19:10 | 685.60 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 103.64 | 08-AUG-16:00 | 199.92 | 19-AUG-04:10 |
September | 1169.53 | 01-SEP-00:10 | 687.30 | 01-SEP-19:10 | 685.60 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.53 | 01-SEP-16:00 | 242.65 | 06-SEP-04:40 |
October | 1169.53 | 01-OCT-23:10 | 687.30 | 02-OCT-19:10 | 685.60 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 398.43 | 30-OCT-04:00 |
November | 1169.53 | 01-NOV-00:10 | 687.30 | 01-NOV-19:10 | 685.60 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 553.02 | 29-NOV-06:00 |
December | 1169.53 | 01-DEC-00:10 | 687.30 | 01-DEC-20:10 | 685.60 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 600.24 | 01-DEC-23:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1169.53 | 687.30 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 176.82 | |||||
Maximum of Months | 1169.53 | 687.30 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 151.25 | 602.18 |
Report: PeakSpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1354.32 | 02-JAN-00:10 | 795.89 | 02-JAN-20:10 | 793.93 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 232.27 | 25-JAN-20:01 |
February | 1354.32 | 01-FEB-00:10 | 795.89 | 01-FEB-20:10 | 793.93 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 233.79 | 24-FEB-22:31 |
March | 1354.32 | 01-MAR-00:10 | 795.89 | 01-MAR-20:10 | 793.93 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 233.03 | 12-MAR-03:41 |
April | 1354.32 | 01-APR-00:10 | 795.89 | 03-APR-19:10 | 793.93 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.04 | 23-APR-16:00 | 174.30 | 05-APR-06:00 |
May | 1354.32 | 01-MAY-00:10 | 795.89 | 01-MAY-19:10 | 793.93 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.68 | 25-MAY-18:00 | 120.48 | 01-MAY-06:00 |
June | 1354.32 | 01-JUN-00:10 | 795.89 | 01-JUN-19:10 | 793.93 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 58.41 | 29-JUN-16:00 | 93.53 | 04-JUN-05:00 |
July | 1354.32 | 01-JUL-00:10 | 795.89 | 03-JUL-19:10 | 793.93 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.61 | 15-JUL-14:00 | 68.26 | 02-JUL-05:00 |
August | 1354.32 | 01-AUG-00:10 | 795.89 | 01-AUG-19:10 | 793.93 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 41.04 | 08-AUG-15:03 | 77.14 | 19-AUG-04:30 |
September | 1354.32 | 01-SEP-00:10 | 795.89 | 01-SEP-19:10 | 793.93 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.92 | 01-SEP-15:20 | 93.65 | 06-SEP-04:20 |
October | 1354.32 | 01-OCT-23:10 | 795.89 | 02-OCT-19:10 | 793.93 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.26 | 19-OCT-15:00 | 153.80 | 30-OCT-04:00 |
November | 1354.32 | 01-NOV-00:10 | 795.89 | 01-NOV-19:10 | 793.93 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 213.46 | 29-NOV-06:00 |
December | 1354.32 | 01-DEC-00:10 | 795.89 | 01-DEC-20:10 | 793.93 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 232.61 | 02-DEC-00:02 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1354.32 | 795.89 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.26 | |||||
Maximum of Months | 1354.32 | 795.89 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 58.41 | 233.79 |
Report: PeakSpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 286.42 | 02-JAN-00:10 | 1487.69 | 02-JAN-20:10 | 839.45 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 583.39 | 26-JAN-07:00 |
February | 286.42 | 01-FEB-00:10 | 1487.69 | 01-FEB-20:10 | 839.45 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 591.46 | 14-FEB-07:00 |
March | 286.42 | 01-MAR-00:10 | 1487.69 | 01-MAR-20:10 | 839.45 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 560.20 | 05-MAR-03:55 |
April | 286.42 | 01-APR-00:10 | 1487.69 | 03-APR-19:10 | 839.45 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.81 | 23-APR-16:00 | 411.93 | 05-APR-06:00 |
May | 286.42 | 01-MAY-00:10 | 1487.69 | 01-MAY-19:10 | 839.45 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 84.31 | 25-MAY-18:00 | 284.76 | 01-MAY-06:00 |
June | 286.42 | 01-JUN-00:10 | 1487.69 | 01-JUN-19:10 | 839.45 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 138.06 | 29-JUN-16:00 | 221.07 | 04-JUN-05:00 |
July | 286.42 | 01-JUL-00:10 | 1487.69 | 03-JUL-19:10 | 839.45 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 100.74 | 15-JUL-14:00 | 161.32 | 02-JUL-05:00 |
August | 286.42 | 01-AUG-00:10 | 1487.69 | 01-AUG-19:10 | 839.45 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 97.01 | 08-AUG-15:00 | 182.30 | 19-AUG-04:10 |
September | 286.42 | 01-SEP-00:10 | 1487.69 | 01-SEP-19:10 | 839.45 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.80 | 01-SEP-15:30 | 221.33 | 06-SEP-04:30 |
October | 286.42 | 01-OCT-23:10 | 1487.69 | 02-OCT-19:10 | 839.45 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.42 | 19-OCT-15:00 | 363.45 | 30-OCT-04:00 |
November | 286.42 | 01-NOV-00:10 | 1487.69 | 01-NOV-19:10 | 839.45 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 504.47 | 29-NOV-06:00 |
December | 286.42 | 01-DEC-00:10 | 1487.69 | 01-DEC-20:10 | 839.45 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 560.86 | 24-DEC-06:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 286.42 | 1487.69 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 161.32 | |||||
Maximum of Months | 286.42 | 1487.69 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 138.06 | 591.46 |
Report: PeakSpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 220.32 | 02-JAN-00:10 | 273.10 | 02-JAN-20:10 | 242.16 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 339.28 | 26-JAN-07:00 |
February | 220.32 | 01-FEB-00:10 | 273.10 | 01-FEB-20:10 | 242.16 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 343.97 | 14-FEB-07:00 |
March | 220.32 | 01-MAR-00:10 | 273.10 | 01-MAR-20:10 | 242.16 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 325.86 | 05-MAR-03:55 |
April | 220.32 | 01-APR-00:10 | 273.10 | 03-APR-19:10 | 242.16 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.77 | 23-APR-16:00 | 237.65 | 05-APR-06:00 |
May | 220.32 | 01-MAY-00:10 | 273.10 | 01-MAY-19:10 | 242.16 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.65 | 25-MAY-18:00 | 164.29 | 01-MAY-06:00 |
June | 220.32 | 01-JUN-00:10 | 273.10 | 01-JUN-19:10 | 242.16 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.65 | 29-JUN-16:00 | 127.55 | 04-JUN-05:00 |
July | 220.32 | 01-JUL-00:10 | 273.10 | 03-JUL-19:10 | 242.16 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 58.12 | 15-JUL-14:00 | 93.07 | 02-JUL-05:00 |
August | 220.32 | 01-AUG-00:10 | 273.10 | 01-AUG-19:10 | 242.16 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 55.96 | 08-AUG-15:15 | 105.18 | 19-AUG-04:30 |
September | 220.32 | 01-SEP-00:10 | 273.10 | 01-SEP-19:10 | 242.16 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.89 | 01-SEP-15:30 | 127.69 | 06-SEP-04:50 |
October | 220.32 | 01-OCT-23:10 | 273.10 | 02-OCT-19:10 | 242.16 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.16 | 19-OCT-15:00 | 209.69 | 30-OCT-04:00 |
November | 220.32 | 01-NOV-00:10 | 273.10 | 01-NOV-19:10 | 242.16 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 291.05 | 29-NOV-06:00 |
December | 220.32 | 01-DEC-00:10 | 273.10 | 01-DEC-20:10 | 242.16 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 326.24 | 24-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 220.32 | 273.10 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.07 | |||||
Maximum of Months | 220.32 | 273.10 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 79.65 | 343.97 |
Report: PeakSpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 907.20 | 02-JAN-00:10 | 337.37 | 02-JAN-20:10 | 4572.80 | 02-JAN-20:10 | 39726.58 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 795.02 | 27-JAN-20:50 |
February | 907.20 | 01-FEB-00:10 | 337.37 | 01-FEB-20:10 | 4572.80 | 01-FEB-20:10 | 39726.58 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 793.80 | 13-FEB-20:50 |
March | 907.20 | 01-MAR-00:10 | 337.37 | 01-MAR-20:10 | 4572.80 | 01-MAR-20:10 | 39726.58 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 747.19 | 12-MAR-07:40 |
April | 907.20 | 01-APR-00:10 | 337.37 | 03-APR-19:10 | 4572.80 | 03-APR-19:10 | 39726.58 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 77.44 | 23-APR-16:00 | 562.45 | 05-APR-06:00 |
May | 907.20 | 01-MAY-00:10 | 337.37 | 01-MAY-19:10 | 4572.80 | 01-MAY-19:10 | 39726.58 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 115.03 | 25-MAY-18:00 | 388.79 | 01-MAY-06:00 |
June | 907.20 | 01-JUN-00:10 | 337.37 | 01-JUN-19:10 | 4572.80 | 01-JUN-19:10 | 39726.58 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 188.36 | 29-JUN-16:00 | 301.64 | 04-JUN-05:00 |
July | 907.20 | 01-JUL-00:10 | 337.37 | 03-JUL-19:10 | 4572.80 | 03-JUL-19:10 | 39726.58 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 137.52 | 15-JUL-14:10 | 220.37 | 02-JUL-05:00 |
August | 907.20 | 01-AUG-00:10 | 337.37 | 01-AUG-19:10 | 4572.80 | 01-AUG-19:10 | 39726.58 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 132.57 | 08-AUG-15:50 | 249.05 | 19-AUG-04:00 |
September | 907.20 | 01-SEP-00:10 | 337.37 | 01-SEP-19:10 | 4572.80 | 01-SEP-19:10 | 39726.58 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 70.79 | 01-SEP-15:05 | 302.38 | 06-SEP-04:10 |
October | 907.20 | 01-OCT-23:10 | 337.37 | 02-OCT-19:10 | 4572.80 | 02-OCT-19:10 | 39726.58 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 16.85 | 19-OCT-15:00 | 496.20 | 30-OCT-04:00 |
November | 907.20 | 01-NOV-00:10 | 337.37 | 01-NOV-19:10 | 4572.80 | 01-NOV-19:10 | 39726.58 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 688.77 | 29-NOV-06:00 |
December | 907.20 | 01-DEC-00:10 | 337.37 | 01-DEC-20:10 | 4572.80 | 01-DEC-20:10 | 39726.58 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 794.64 | 01-DEC-21:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 907.20 | 337.37 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 220.37 | ||||||
Maximum of Months | 907.20 | 337.37 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 188.36 | 795.02 |
Report: PeakSpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 15368.40 | 02-JAN-00:10 | 2177.23 | 02-JAN-20:10 | 965.27 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 1327.46 | 27-JAN-21:03 |
February | 15368.40 | 01-FEB-00:10 | 2177.23 | 01-FEB-20:10 | 965.27 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 1335.84 | 24-FEB-22:23 |
March | 15368.40 | 01-MAR-00:10 | 2177.23 | 01-MAR-20:10 | 965.27 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 1327.82 | 12-MAR-03:41 |
April | 15368.40 | 01-APR-00:10 | 2177.23 | 03-APR-19:10 | 965.27 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 137.55 | 23-APR-16:00 | 998.30 | 05-APR-06:00 |
May | 15368.40 | 01-MAY-00:10 | 2177.23 | 01-MAY-19:10 | 965.27 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 204.37 | 25-MAY-18:00 | 690.03 | 01-MAY-06:00 |
June | 15368.40 | 01-JUN-00:10 | 2177.23 | 01-JUN-19:10 | 965.27 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 334.49 | 29-JUN-16:00 | 535.87 | 04-JUN-05:00 |
July | 15368.40 | 01-JUL-00:10 | 2177.23 | 03-JUL-19:10 | 965.27 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 242.74 | 15-JUL-15:00 | 390.94 | 02-JUL-05:00 |
August | 15368.40 | 01-AUG-00:10 | 2177.23 | 01-AUG-19:10 | 965.27 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 232.61 | 08-AUG-16:00 | 441.97 | 19-AUG-04:20 |
September | 15368.40 | 01-SEP-00:10 | 2177.23 | 01-SEP-19:10 | 965.27 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 114.28 | 01-SEP-16:00 | 536.42 | 06-SEP-04:00 |
October | 15368.40 | 01-OCT-23:10 | 2177.23 | 02-OCT-19:10 | 965.27 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 880.93 | 30-OCT-04:00 |
November | 15368.40 | 01-NOV-00:10 | 2177.23 | 01-NOV-19:10 | 965.27 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1222.75 | 29-NOV-06:00 |
December | 15368.40 | 01-DEC-00:10 | 2177.23 | 01-DEC-20:10 | 965.27 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 1331.61 | 19-DEC-16:25 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 15368.40 | 2177.23 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 390.94 | |||||
Maximum of Months | 15368.40 | 2177.23 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 334.49 | 1335.84 |
Report: PeakSpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 45622.98 | 02-JAN-00:10 | 11849.32 | 02-JAN-20:10 | 10029.21 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 3796.58 | 27-JAN-21:03 |
February | 45622.98 | 01-FEB-00:10 | 11849.32 | 01-FEB-20:10 | 10029.21 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 3824.35 | 24-FEB-22:31 |
March | 45622.98 | 01-MAR-00:10 | 11849.32 | 01-MAR-20:10 | 10029.21 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 3811.63 | 12-MAR-03:41 |
April | 45622.98 | 01-APR-00:10 | 11849.32 | 03-APR-19:10 | 10029.21 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 393.18 | 23-APR-16:00 | 2852.01 | 05-APR-06:00 |
May | 45622.98 | 01-MAY-00:10 | 11849.32 | 01-MAY-19:10 | 10029.21 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 583.95 | 25-MAY-18:00 | 1971.53 | 01-MAY-06:00 |
June | 45622.98 | 01-JUN-00:10 | 11849.32 | 01-JUN-19:10 | 10029.21 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 955.68 | 29-JUN-16:00 | 1530.70 | 04-JUN-05:00 |
July | 45622.98 | 01-JUL-00:10 | 11849.32 | 03-JUL-19:10 | 10029.21 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 697.30 | 15-JUL-14:00 | 1117.10 | 02-JUL-05:00 |
August | 45622.98 | 01-AUG-00:10 | 11849.32 | 01-AUG-19:10 | 10029.21 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 671.52 | 08-AUG-15:50 | 1262.33 | 19-AUG-05:00 |
September | 45622.98 | 01-SEP-00:10 | 11849.32 | 01-SEP-19:10 | 10029.21 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 358.49 | 01-SEP-16:00 | 1535.84 | 06-SEP-04:40 |
October | 45622.98 | 01-OCT-23:10 | 11849.32 | 02-OCT-19:10 | 10029.21 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 74.94 | 19-OCT-15:00 | 2516.59 | 30-OCT-04:00 |
November | 45622.98 | 01-NOV-00:10 | 11849.32 | 01-NOV-19:10 | 10029.21 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3492.87 | 29-NOV-06:00 |
December | 45622.98 | 01-DEC-00:10 | 11849.32 | 01-DEC-20:10 | 10029.21 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 3808.67 | 02-DEC-00:02 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 45622.98 | 11849.32 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1117.10 | |||||
Maximum of Months | 45622.98 | 11849.32 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 955.68 | 3824.35 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 392.73 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 460.90 | 06-JAN-08:00 |
February | 180.00 | 01-FEB-00:10 | 392.73 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 445.48 | 14-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 392.73 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 400.09 | 05-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 392.73 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.17 | 23-APR-16:00 | 263.23 | 05-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 392.73 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.43 | 25-MAY-17:00 | 182.29 | 01-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 392.73 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 86.87 | 29-JUN-16:00 | 141.73 | 04-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 392.73 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.73 | 15-JUL-15:08 | 103.69 | 02-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 392.73 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.72 | 08-AUG-15:10 | 117.05 | 19-AUG-04:00 |
September | 180.00 | 01-SEP-00:10 | 392.73 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.96 | 01-SEP-15:10 | 141.89 | 06-SEP-04:00 |
October | 180.00 | 01-OCT-00:10 | 392.73 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.34 | 19-OCT-15:10 | 232.39 | 30-OCT-04:00 |
November | 180.00 | 01-NOV-00:10 | 392.73 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 322.16 | 29-NOV-06:00 |
December | 180.00 | 01-DEC-00:10 | 392.73 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 427.49 | 24-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 392.73 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.69 | |||||
Maximum of Months | 180.00 | 392.73 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 86.87 | 460.90 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 392.68 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 455.84 | 06-JAN-08:00 |
February | 180.00 | 01-FEB-00:10 | 392.68 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 445.46 | 14-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 392.68 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 400.06 | 05-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 392.68 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.16 | 23-APR-16:00 | 263.21 | 05-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 392.68 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.42 | 25-MAY-17:00 | 182.28 | 01-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 392.68 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 86.86 | 29-JUN-16:00 | 141.72 | 04-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 392.68 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.73 | 15-JUL-15:08 | 103.68 | 02-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 392.68 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.72 | 08-AUG-15:10 | 117.04 | 19-AUG-04:00 |
September | 180.00 | 01-SEP-00:10 | 392.68 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.96 | 01-SEP-15:10 | 141.88 | 06-SEP-04:00 |
October | 180.00 | 01-OCT-00:10 | 392.68 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.34 | 19-OCT-15:08 | 232.37 | 30-OCT-04:00 |
November | 180.00 | 01-NOV-00:10 | 392.68 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 322.13 | 29-NOV-06:00 |
December | 180.00 | 01-DEC-00:10 | 392.68 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 427.46 | 24-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 392.68 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.68 | |||||
Maximum of Months | 180.00 | 392.68 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 86.86 | 455.84 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 01-JAN-00:10 | 246.81 | 01-JAN-19:10 | 232.19 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 126.45 | 06-JAN-09:00 |
February | 0.00 | 01-FEB-00:10 | 246.81 | 01-FEB-20:10 | 232.19 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 119.23 | 14-FEB-07:00 |
March | 0.00 | 01-MAR-00:10 | 246.81 | 01-MAR-20:10 | 232.19 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 106.68 | 05-MAR-07:00 |
April | 0.00 | 01-APR-00:10 | 246.81 | 01-APR-18:10 | 232.19 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.88 | 23-APR-16:00 | 72.68 | 05-APR-06:00 |
May | 0.00 | 01-MAY-00:10 | 246.81 | 01-MAY-19:10 | 232.19 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.73 | 25-MAY-18:00 | 53.05 | 01-MAY-06:00 |
June | 0.00 | 01-JUN-00:10 | 246.81 | 01-JUN-19:10 | 232.19 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.35 | 29-JUN-16:00 | 41.75 | 04-JUN-05:00 |
July | 0.00 | 01-JUL-00:10 | 246.81 | 01-JUL-18:10 | 232.19 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.67 | 15-JUL-14:00 | 32.64 | 02-JUL-05:00 |
August | 0.00 | 01-AUG-00:10 | 246.81 | 01-AUG-19:10 | 232.19 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.96 | 08-AUG-15:00 | 35.20 | 19-AUG-04:00 |
September | 0.00 | 01-SEP-00:10 | 246.81 | 01-SEP-19:10 | 232.19 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.91 | 01-SEP-15:30 | 43.10 | 06-SEP-04:30 |
October | 0.00 | 01-OCT-00:10 | 246.81 | 01-OCT-18:10 | 232.19 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 62.46 | 30-OCT-07:00 |
November | 0.00 | 01-NOV-00:10 | 246.81 | 01-NOV-19:10 | 232.19 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 85.10 | 29-NOV-06:00 |
December | 0.00 | 01-DEC-00:10 | 246.81 | 01-DEC-20:10 | 232.19 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 114.21 | 24-DEC-08:17 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 0.00 | 246.81 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.64 | |||||
Maximum of Months | 0.00 | 246.81 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 20.35 | 126.45 |
Report: PeakSpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 246.88 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 127.38 | 06-JAN-08:00 |
February | 180.00 | 01-FEB-00:10 | 246.88 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 124.10 | 14-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 246.88 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 111.66 | 05-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 246.88 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.81 | 23-APR-16:00 | 73.46 | 05-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 246.88 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.35 | 25-MAY-17:00 | 50.88 | 01-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 246.88 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.24 | 29-JUN-16:00 | 39.56 | 04-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 246.88 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.23 | 15-JUL-15:10 | 28.94 | 02-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 246.88 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.95 | 08-AUG-15:10 | 32.67 | 19-AUG-04:00 |
September | 180.00 | 01-SEP-00:10 | 246.88 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.92 | 01-SEP-15:08 | 39.60 | 06-SEP-04:50 |
October | 180.00 | 01-OCT-00:10 | 246.88 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.77 | 19-OCT-15:07 | 64.86 | 30-OCT-04:00 |
November | 180.00 | 01-NOV-00:10 | 246.88 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 89.91 | 29-NOV-06:00 |
December | 180.00 | 01-DEC-00:10 | 246.88 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 119.05 | 24-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 246.88 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.94 | |||||
Maximum of Months | 180.00 | 246.88 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 24.24 | 127.38 |
Report: PeakSpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 392.73 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 463.58 | 06-JAN-09:10 |
February | 180.00 | 01-FEB-00:10 | 392.73 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 445.49 | 14-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 392.73 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 400.09 | 05-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 392.73 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.17 | 23-APR-16:00 | 263.23 | 05-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 392.73 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.42 | 25-MAY-17:00 | 182.29 | 01-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 392.73 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 86.86 | 29-JUN-16:00 | 141.73 | 04-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 392.73 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.73 | 15-JUL-15:10 | 103.69 | 02-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 392.73 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.73 | 08-AUG-15:08 | 117.05 | 19-AUG-04:00 |
September | 180.00 | 01-SEP-00:10 | 392.73 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.96 | 01-SEP-15:08 | 141.89 | 06-SEP-04:00 |
October | 180.00 | 01-OCT-00:10 | 392.73 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.34 | 19-OCT-15:10 | 232.39 | 30-OCT-04:00 |
November | 180.00 | 01-NOV-00:10 | 392.73 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 322.15 | 29-NOV-06:00 |
December | 180.00 | 01-DEC-00:10 | 392.73 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 427.49 | 24-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 392.73 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.69 | |||||
Maximum of Months | 180.00 | 392.73 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 86.86 | 463.58 |
Report: PeakSpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 392.68 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 456.04 | 06-JAN-09:10 |
February | 180.00 | 01-FEB-00:10 | 392.68 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 445.47 | 14-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 392.68 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 400.06 | 05-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 392.68 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.17 | 23-APR-16:00 | 263.21 | 05-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 392.68 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.42 | 25-MAY-17:00 | 182.28 | 01-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 392.68 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 86.86 | 29-JUN-16:00 | 141.72 | 04-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 392.68 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.73 | 15-JUL-15:10 | 103.68 | 02-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 392.68 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.72 | 08-AUG-15:10 | 117.04 | 19-AUG-04:00 |
September | 180.00 | 01-SEP-00:10 | 392.68 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.96 | 01-SEP-15:08 | 141.88 | 06-SEP-04:20 |
October | 180.00 | 01-OCT-00:10 | 392.68 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.34 | 19-OCT-15:08 | 232.36 | 30-OCT-04:00 |
November | 180.00 | 01-NOV-00:10 | 392.68 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 322.13 | 29-NOV-06:00 |
December | 180.00 | 01-DEC-00:10 | 392.68 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 426.86 | 24-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 392.68 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.68 | |||||
Maximum of Months | 180.00 | 392.68 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 86.86 | 456.04 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2263.36 | 02-JAN-00:10 | 1282.60 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 485.37 | 26-JAN-07:00 |
February | 2263.36 | 01-FEB-00:10 | 1282.60 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 489.94 | 14-FEB-07:00 |
March | 2263.36 | 01-MAR-00:10 | 1282.60 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 447.93 | 05-MAR-07:00 |
April | 2263.36 | 01-APR-00:10 | 1282.60 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.88 | 23-APR-16:00 | 317.31 | 05-APR-06:00 |
May | 2263.36 | 01-MAY-00:10 | 1282.60 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.26 | 25-MAY-18:00 | 219.45 | 01-MAY-06:00 |
June | 2263.36 | 01-JUN-00:10 | 1282.60 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.49 | 29-JUN-16:00 | 170.44 | 04-JUN-05:00 |
July | 2263.36 | 01-JUL-00:10 | 1282.60 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.35 | 15-JUL-14:00 | 127.56 | 02-JUL-05:00 |
August | 2263.36 | 01-AUG-00:10 | 1282.60 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.46 | 08-AUG-16:00 | 140.61 | 19-AUG-04:00 |
September | 2263.36 | 01-SEP-00:10 | 1282.60 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.25 | 01-SEP-16:00 | 170.64 | 06-SEP-04:20 |
October | 2263.36 | 01-OCT-23:10 | 1282.60 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.23 | 19-OCT-15:00 | 280.01 | 30-OCT-04:00 |
November | 2263.36 | 01-NOV-00:10 | 1282.60 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 388.53 | 29-NOV-06:00 |
December | 2263.36 | 01-DEC-00:10 | 1282.60 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 462.61 | 24-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 2263.36 | 1282.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 127.56 | ||||
Maximum of Months | 2263.36 | 1282.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.49 | 489.94 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 392.73 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 466.12 | 06-JAN-07:10 |
February | 180.00 | 01-FEB-00:10 | 392.73 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 446.08 | 14-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 392.73 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 400.66 | 05-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 392.73 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.79 | 23-APR-16:00 | 263.74 | 05-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 392.73 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.04 | 25-MAY-17:00 | 182.76 | 01-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 392.73 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 86.51 | 29-JUN-16:00 | 142.18 | 04-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 392.73 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.37 | 15-JUL-15:10 | 104.12 | 02-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 392.73 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.35 | 08-AUG-15:10 | 117.49 | 19-AUG-04:00 |
September | 180.00 | 01-SEP-00:10 | 392.73 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.57 | 01-SEP-16:00 | 142.34 | 06-SEP-05:00 |
October | 180.00 | 01-OCT-00:10 | 392.73 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.95 | 19-OCT-15:10 | 232.88 | 30-OCT-04:00 |
November | 180.00 | 01-NOV-00:10 | 392.73 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 322.69 | 29-NOV-06:00 |
December | 180.00 | 01-DEC-00:10 | 392.73 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 428.08 | 24-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 392.73 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.12 | |||||
Maximum of Months | 180.00 | 392.73 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 86.51 | 466.12 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 392.68 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 463.29 | 06-JAN-08:00 |
February | 180.00 | 01-FEB-00:10 | 392.68 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 446.06 | 14-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 392.68 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 400.63 | 05-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 392.68 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.80 | 23-APR-16:00 | 263.71 | 05-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 392.68 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.05 | 25-MAY-17:00 | 182.75 | 01-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 392.68 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 86.50 | 29-JUN-16:00 | 142.17 | 04-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 392.68 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.36 | 15-JUL-15:10 | 104.11 | 02-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 392.68 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.35 | 08-AUG-15:10 | 117.47 | 19-AUG-04:00 |
September | 180.00 | 01-SEP-00:10 | 392.68 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.58 | 01-SEP-15:10 | 142.33 | 06-SEP-05:00 |
October | 180.00 | 01-OCT-00:10 | 392.68 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.95 | 19-OCT-15:08 | 232.86 | 30-OCT-04:00 |
November | 180.00 | 01-NOV-00:10 | 392.68 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 322.67 | 29-NOV-06:00 |
December | 180.00 | 01-DEC-00:10 | 392.68 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 428.05 | 24-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 392.68 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.11 | |||||
Maximum of Months | 180.00 | 392.68 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 86.50 | 463.29 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 246.88 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 238.48 | 06-JAN-07:10 |
February | 180.00 | 01-FEB-00:10 | 246.88 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 228.23 | 14-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 246.88 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 204.99 | 05-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 246.88 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.80 | 23-APR-16:00 | 134.94 | 05-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 246.88 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.12 | 25-MAY-17:00 | 93.51 | 01-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 246.88 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.26 | 29-JUN-16:00 | 72.75 | 04-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 246.88 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.40 | 15-JUL-15:10 | 53.27 | 02-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 246.88 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.88 | 08-AUG-15:10 | 60.11 | 19-AUG-04:00 |
September | 180.00 | 01-SEP-00:10 | 246.88 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.16 | 01-SEP-15:50 | 72.83 | 06-SEP-04:20 |
October | 180.00 | 01-OCT-00:10 | 246.88 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.91 | 19-OCT-15:40 | 119.15 | 30-OCT-04:00 |
November | 180.00 | 01-NOV-00:10 | 246.88 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 165.10 | 29-NOV-06:00 |
December | 180.00 | 01-DEC-00:10 | 246.88 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 219.01 | 24-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 246.88 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.27 | |||||
Maximum of Months | 180.00 | 246.88 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 44.26 | 238.48 |
Report: PeakSpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 3823.39 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 854.13 | 27-JAN-21:08 |
February | 26988.77 | 01-FEB-00:10 | 3823.39 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 867.58 | 24-FEB-22:20 |
March | 26988.77 | 01-MAR-00:10 | 3823.39 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 856.41 | 12-MAR-03:41 |
April | 26988.77 | 01-APR-00:10 | 3823.39 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 86.66 | 23-APR-16:00 | 646.61 | 05-APR-06:00 |
May | 26988.77 | 01-MAY-00:10 | 3823.39 | 01-MAY-19:10 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 121.94 | 25-MAY-18:00 | 457.56 | 01-MAY-06:00 |
June | 26988.77 | 01-JUN-00:10 | 3823.39 | 01-JUN-19:10 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 201.82 | 29-JUN-16:00 | 351.38 | 04-JUN-05:00 |
July | 26988.77 | 01-JUL-00:10 | 3823.39 | 03-JUL-19:10 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 146.58 | 29-JUL-16:00 | 263.48 | 02-JUL-05:00 |
August | 26988.77 | 01-AUG-00:10 | 3823.39 | 01-AUG-19:10 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 143.46 | 08-AUG-15:00 | 302.08 | 19-AUG-04:00 |
September | 26988.77 | 01-SEP-00:10 | 3823.39 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 73.68 | 01-SEP-15:00 | 361.65 | 06-SEP-04:30 |
October | 26988.77 | 01-OCT-23:10 | 3823.39 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.64 | 19-OCT-15:00 | 574.11 | 30-OCT-04:20 |
November | 26988.77 | 01-NOV-00:10 | 3823.39 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 788.24 | 29-NOV-06:00 |
December | 26988.77 | 01-DEC-00:10 | 3823.39 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 861.31 | 01-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26988.77 | 3823.39 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 263.48 | |||||
Maximum of Months | 26988.77 | 3823.39 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 201.82 | 867.58 |
Report: PeakSpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 3823.39 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 854.10 | 27-JAN-21:10 |
February | 26988.77 | 01-FEB-00:10 | 3823.39 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 869.41 | 24-FEB-22:20 |
March | 26988.77 | 01-MAR-00:10 | 3823.39 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 856.26 | 12-MAR-03:41 |
April | 26988.77 | 01-APR-00:10 | 3823.39 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 86.69 | 23-APR-16:00 | 647.70 | 05-APR-06:00 |
May | 26988.77 | 01-MAY-00:10 | 3823.39 | 01-MAY-19:10 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 119.94 | 25-MAY-18:00 | 458.91 | 01-MAY-06:00 |
June | 26988.77 | 01-JUN-00:10 | 3823.39 | 01-JUN-19:10 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 200.21 | 29-JUN-16:00 | 352.44 | 04-JUN-05:00 |
July | 26988.77 | 01-JUL-00:10 | 3823.39 | 03-JUL-19:10 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 144.70 | 29-JUL-16:00 | 264.42 | 02-JUL-05:00 |
August | 26988.77 | 01-AUG-00:10 | 3823.39 | 01-AUG-19:10 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 141.77 | 08-AUG-15:00 | 302.85 | 19-AUG-04:00 |
September | 26988.77 | 01-SEP-00:10 | 3823.39 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 72.11 | 01-SEP-15:00 | 362.27 | 06-SEP-04:30 |
October | 26988.77 | 01-OCT-23:10 | 3823.39 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.40 | 19-OCT-15:00 | 574.75 | 30-OCT-04:20 |
November | 26988.77 | 01-NOV-00:10 | 3823.39 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 788.85 | 29-NOV-06:00 |
December | 26988.77 | 01-DEC-00:10 | 3823.39 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 862.96 | 01-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26988.77 | 3823.39 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 264.42 | |||||
Maximum of Months | 26988.77 | 3823.39 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 200.21 | 869.41 |
Report: PeakSpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2401.70 | 02-JAN-00:10 | 1020.78 | 02-JAN-20:10 | 15112.11 | 01-JAN-07:10 | 22492.83 | 01-JAN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 796.50 | 31-JAN-18:50 |
February | 2401.70 | 01-FEB-00:10 | 1020.78 | 01-FEB-20:10 | 15112.11 | 01-FEB-07:10 | 22492.83 | 01-FEB-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 793.75 | 13-FEB-20:50 |
March | 2401.70 | 01-MAR-00:10 | 1020.78 | 01-MAR-20:10 | 15112.11 | 01-MAR-07:10 | 22492.83 | 01-MAR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 774.82 | 15-MAR-08:00 |
April | 2401.70 | 01-APR-00:10 | 1020.78 | 03-APR-19:10 | 15112.11 | 01-APR-06:10 | 22492.83 | 01-APR-15:09 | 0.00 | 0.00 | 0.00 | 36.15 | 23-APR-16:00 | 582.86 | 05-APR-06:00 |
May | 2401.70 | 01-MAY-00:10 | 1020.78 | 01-MAY-19:10 | 15112.11 | 01-MAY-06:10 | 22492.83 | 01-MAY-15:09 | 0.00 | 0.00 | 0.00 | 74.14 | 25-MAY-18:00 | 417.30 | 01-MAY-06:00 |
June | 2401.70 | 01-JUN-00:10 | 1020.78 | 01-JUN-19:10 | 15112.11 | 01-JUN-06:10 | 22492.83 | 01-JUN-15:09 | 0.00 | 0.00 | 0.00 | 149.65 | 29-JUN-16:00 | 309.24 | 04-JUN-05:00 |
July | 2401.70 | 01-JUL-00:10 | 1020.78 | 03-JUL-19:10 | 15112.11 | 01-JUL-06:10 | 22492.83 | 01-JUL-15:09 | 0.00 | 0.00 | 0.00 | 97.15 | 15-JUL-14:00 | 225.96 | 02-JUL-05:00 |
August | 2401.70 | 01-AUG-00:10 | 1020.78 | 01-AUG-19:10 | 15112.11 | 01-AUG-06:10 | 22492.83 | 01-AUG-15:09 | 0.00 | 0.00 | 0.00 | 91.50 | 08-AUG-15:40 | 257.54 | 19-AUG-05:20 |
September | 2401.70 | 01-SEP-00:10 | 1020.78 | 01-SEP-19:10 | 15112.11 | 01-SEP-06:10 | 22492.83 | 01-SEP-15:09 | 0.00 | 0.00 | 0.00 | 28.39 | 01-SEP-15:40 | 314.18 | 06-SEP-05:20 |
October | 2401.70 | 01-OCT-23:10 | 1020.78 | 02-OCT-19:10 | 15112.11 | 01-OCT-06:10 | 22492.83 | 01-OCT-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 512.39 | 30-OCT-07:00 |
November | 2401.70 | 01-NOV-00:10 | 1020.78 | 01-NOV-19:10 | 15112.11 | 01-NOV-06:10 | 22492.83 | 01-NOV-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 703.49 | 29-NOV-06:00 |
December | 2401.70 | 01-DEC-00:10 | 1020.78 | 01-DEC-20:10 | 15112.11 | 01-DEC-07:10 | 22492.83 | 01-DEC-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 792.41 | 23-DEC-21:20 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 2401.70 | 1020.78 | 15112.11 | 22492.83 | 0.00 | 0.00 | 0.00 | 0.00 | 225.96 | ||||||
Maximum of Months | 2401.70 | 1020.78 | 15112.11 | 22492.83 | 0.00 | 0.00 | 0.00 | 149.65 | 796.50 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2395.44 | 02-JAN-00:10 | 1357.44 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 778.23 | 26-JAN-07:00 |
February | 2395.44 | 01-FEB-00:10 | 1357.44 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 789.57 | 14-FEB-07:00 |
March | 2395.44 | 01-MAR-00:10 | 1357.44 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 751.93 | 12-MAR-03:41 |
April | 2395.44 | 01-APR-00:10 | 1357.44 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.37 | 23-APR-16:00 | 562.51 | 05-APR-06:00 |
May | 2395.44 | 01-MAY-00:10 | 1357.44 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 110.15 | 25-MAY-18:00 | 389.34 | 01-MAY-06:00 |
June | 2395.44 | 01-JUN-00:10 | 1357.44 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 176.85 | 29-JUN-16:00 | 302.52 | 04-JUN-05:00 |
July | 2395.44 | 01-JUL-00:10 | 1357.44 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 128.77 | 15-JUL-14:00 | 221.16 | 02-JUL-05:00 |
August | 2395.44 | 01-AUG-00:10 | 1357.44 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 123.70 | 08-AUG-16:00 | 249.73 | 19-AUG-04:00 |
September | 2395.44 | 01-SEP-00:10 | 1357.44 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.85 | 01-SEP-16:00 | 302.89 | 06-SEP-04:50 |
October | 2395.44 | 01-OCT-23:10 | 1357.44 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.73 | 19-OCT-15:00 | 496.51 | 30-OCT-04:00 |
November | 2395.44 | 01-NOV-00:10 | 1357.44 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 688.61 | 29-NOV-06:00 |
December | 2395.44 | 01-DEC-00:10 | 1357.44 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 752.43 | 24-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 2395.44 | 1357.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 221.16 | ||||
Maximum of Months | 2395.44 | 1357.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 176.85 | 789.57 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 61186.05 | 25-JAN-20:01 | 89459.16 | 135169.98 | 101138.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 60690.85 | 14-FEB-07:00 | 8945.92 | 6007.52 | 5323.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 57889.85 | 12-MAR-03:51 | 89459.16 | 30037.58 | 31938.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 17382.20 | 20-APR-20:00 | 8945.92 | 13517.00 | 10113.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 18415.59 | 10-MAY-20:00 | 8945.92 | 13517.00 | 10113.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 19546.51 | 21-JUN-20:00 | 8945.92 | 13517.00 | 10113.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 20718.10 | 20-JUL-19:10 | 17891.83 | 27034.00 | 20227.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 21427.79 | 24-AUG-18:03 | 53675.50 | 72090.20 | 57488.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 20862.70 | 07-SEP-18:10 | 62621.41 | 84105.23 | 67070.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 20232.83 | 19-OCT-18:10 | 62621.41 | 84105.23 | 67070.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 19485.91 | 01-NOV-20:00 | 8945.92 | 13517.00 | 10113.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 56453.61 | 24-DEC-06:05 | 17891.83 | 9011.45 | 8516.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 17382.20 | 8945.92 | 6007.52 | 5323.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 61186.05 | 89459.16 | 135169.98 | 101138.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7530.87 | 25-JAN-20:01 | 9096.36 | 6872.96 | 6856.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 595.59 |
February | 5513.01 | 01-FEB-18:11 | 6497.40 | 4581.97 | 5051.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 549.71 |
March | 6152.52 | 12-MAR-03:51 | 9096.36 | 1527.32 | 2165.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 565.03 |
April | 4151.52 | 18-APR-10:35 | 519.79 | 381.83 | 505.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.16 |
May | 3938.52 | 18-MAY-15:13 | 1949.22 | 572.75 | 757.77 | 0.00 | 0.00 | 0.00 | 0.00 | 78.47 | 0.00 |
June | 3975.87 | 30-JUN-15:15 | 1299.48 | 381.83 | 505.18 | 0.00 | 0.00 | 0.00 | 0.00 | 113.47 | 0.00 |
July | 4263.94 | 23-JUL-10:35 | 779.69 | 458.20 | 577.35 | 0.00 | 0.00 | 0.00 | 0.00 | 74.90 | 0.00 |
August | 4378.20 | 25-AUG-10:35 | 519.79 | 381.83 | 505.18 | 0.00 | 0.00 | 0.00 | 0.00 | 34.03 | 0.00 |
September | 4336.27 | 01-SEP-10:40 | 259.90 | 190.92 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 16.76 | 0.00 |
October | 4718.98 | 22-OCT-10:35 | 779.69 | 458.20 | 577.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.37 |
November | 4102.47 | 17-NOV-11:40 | 259.90 | 190.92 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 166.76 |
December | 4958.76 | 23-DEC-21:41 | 9096.36 | 5345.64 | 5773.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 533.82 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3938.52 | 259.90 | 190.92 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7530.87 | 9096.36 | 6872.96 | 6856.04 | 0.00 | 0.00 | 0.00 | 0.00 | 113.47 | 595.59 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4891.28 | 25-JAN-20:01 | 10533.60 | 7958.91 | 7939.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 232.27 |
February | 4286.48 | 24-FEB-22:51 | 13543.20 | 5305.94 | 5850.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 223.81 |
March | 4565.27 | 12-MAR-03:51 | 10533.60 | 1768.65 | 2507.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 228.03 |
April | 1956.55 | 13-APR-18:03 | 7373.52 | 4952.21 | 5265.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.71 |
May | 2175.52 | 18-MAY-18:10 | 6320.16 | 4244.75 | 4512.87 | 0.00 | 0.00 | 0.00 | 0.00 | 26.47 | 0.00 |
June | 2232.21 | 29-JUN-18:10 | 6320.16 | 4244.75 | 4512.87 | 0.00 | 0.00 | 0.00 | 0.00 | 47.85 | 0.00 |
July | 2201.56 | 24-JUL-18:10 | 6320.16 | 4244.75 | 4512.87 | 0.00 | 0.00 | 0.00 | 0.00 | 28.94 | 0.00 |
August | 2122.78 | 24-AUG-18:10 | 6320.16 | 4244.75 | 4512.87 | 0.00 | 0.00 | 0.00 | 0.00 | 9.81 | 0.00 |
September | 1993.48 | 07-SEP-18:01 | 7373.52 | 4952.21 | 5265.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.61 |
October | 1928.42 | 19-OCT-18:10 | 7373.52 | 4952.21 | 5265.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.18 |
November | 1745.50 | 01-NOV-20:00 | 1053.36 | 795.89 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.37 |
December | 4196.26 | 23-DEC-21:41 | 10533.60 | 6190.27 | 6685.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 220.92 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1745.50 | 1053.36 | 795.89 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4891.28 | 13543.20 | 7958.91 | 7939.31 | 0.00 | 0.00 | 0.00 | 0.00 | 47.85 | 232.27 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3681.04 | 25-JAN-20:01 | 2227.68 | 14876.86 | 8394.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 551.43 |
February | 3317.39 | 24-FEB-22:51 | 2864.16 | 9917.90 | 6185.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 541.55 |
March | 3489.36 | 12-MAR-03:51 | 2227.68 | 3305.97 | 2650.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 546.99 |
April | 1729.82 | 13-APR-20:00 | 222.77 | 1487.69 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.56 |
May | 2057.12 | 25-MAY-18:02 | 1336.61 | 7934.32 | 4771.59 | 0.00 | 0.00 | 0.00 | 0.00 | 80.74 | 0.00 |
June | 2161.67 | 29-JUN-18:10 | 1336.61 | 7934.32 | 4771.59 | 0.00 | 0.00 | 0.00 | 0.00 | 113.61 | 0.00 |
July | 2120.24 | 24-JUL-18:03 | 1336.61 | 7934.32 | 4771.59 | 0.00 | 0.00 | 0.00 | 0.00 | 69.40 | 0.00 |
August | 2045.52 | 09-AUG-18:10 | 1336.61 | 7934.32 | 4771.59 | 0.00 | 0.00 | 0.00 | 0.00 | 56.10 | 0.00 |
September | 1890.02 | 01-SEP-18:10 | 1336.61 | 7934.32 | 4771.59 | 0.00 | 0.00 | 0.00 | 0.00 | 20.84 | 0.00 |
October | 1729.09 | 19-OCT-20:00 | 222.77 | 1487.69 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.77 |
November | 1554.44 | 01-NOV-20:00 | 222.77 | 1487.69 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.81 |
December | 3183.18 | 02-DEC-00:31 | 2864.16 | 3305.97 | 2650.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 532.82 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1554.44 | 222.77 | 1487.69 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3681.04 | 2864.16 | 14876.86 | 8394.47 | 0.00 | 0.00 | 0.00 | 0.00 | 113.61 | 551.43 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1463.03 | 25-JAN-20:01 | 1713.60 | 2730.99 | 2421.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 316.42 |
February | 1315.59 | 24-FEB-22:51 | 2203.20 | 1820.66 | 1784.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 312.41 |
March | 1418.97 | 12-MAR-03:51 | 1713.60 | 606.89 | 764.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 316.50 |
April | 642.47 | 23-APR-20:00 | 146.88 | 242.76 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 4.08 | 0.00 |
May | 943.27 | 25-MAY-19:05 | 342.72 | 546.20 | 484.31 | 0.00 | 0.00 | 0.00 | 0.00 | 34.07 | 0.00 |
June | 1032.72 | 29-JUN-18:20 | 514.08 | 728.27 | 688.24 | 0.00 | 0.00 | 0.00 | 0.00 | 64.39 | 0.00 |
July | 966.13 | 20-JUL-19:10 | 342.72 | 546.20 | 484.31 | 0.00 | 0.00 | 0.00 | 0.00 | 31.29 | 0.00 |
August | 910.90 | 09-AUG-19:40 | 171.36 | 273.10 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 18.17 | 0.00 |
September | 826.30 | 01-SEP-21:00 | 195.84 | 242.76 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.64 |
October | 603.94 | 19-OCT-21:00 | 195.84 | 242.76 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.76 |
November | 467.77 | 01-NOV-21:00 | 195.84 | 242.76 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.74 |
December | 1271.89 | 02-DEC-00:31 | 2203.20 | 606.89 | 764.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 308.56 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 467.77 | 146.88 | 242.76 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1463.03 | 2203.20 | 2730.99 | 2421.57 | 0.00 | 0.00 | 0.00 | 0.00 | 64.39 | 316.50 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 76756.90 | 25-JAN-20:01 | 7056.00 | 3373.69 | 45728.01 | 397265.76 | 0.00 | 0.00 | 0.00 | 0.00 | 729.03 |
February | 57669.52 | 13-FEB-21:21 | 8064.00 | 2998.83 | 43321.27 | 376357.04 | 0.00 | 0.00 | 0.00 | 0.00 | 664.04 |
March | 54946.36 | 05-MAR-01:41 | 7056.00 | 1124.56 | 19253.90 | 167269.80 | 0.00 | 0.00 | 0.00 | 0.00 | 699.01 |
April | 36423.53 | 14-APR-20:00 | 705.60 | 337.37 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 194.41 |
May | 37236.25 | 18-MAY-20:00 | 705.60 | 337.37 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 37.44 |
June | 37566.83 | 28-JUN-20:00 | 705.60 | 337.37 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 19.20 | 0.00 |
July | 37360.32 | 20-JUL-20:00 | 705.60 | 337.37 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 10.57 | 0.00 |
August | 37145.69 | 08-AUG-20:00 | 705.60 | 337.37 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 14.43 | 0.00 |
September | 36949.83 | 01-SEP-20:00 | 705.60 | 337.37 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 104.44 |
October | 36376.78 | 19-OCT-20:00 | 705.60 | 337.37 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 156.05 |
November | 35994.93 | 01-NOV-20:00 | 705.60 | 337.37 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 153.05 |
December | 57243.60 | 23-DEC-21:41 | 7056.00 | 2623.98 | 38507.80 | 334539.59 | 0.00 | 0.00 | 0.00 | 0.00 | 649.69 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 35994.93 | 705.60 | 337.37 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 76756.90 | 8064.00 | 3373.69 | 45728.01 | 397265.76 | 0.00 | 0.00 | 0.00 | 19.20 | 729.03 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 35204.76 | 01-JAN-00:31 | 119532.00 | 7257.42 | 4064.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1306.22 |
February | 27633.55 | 17-FEB-00:01 | 153684.00 | 4838.28 | 3048.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1313.96 |
March | 29903.61 | 12-MAR-03:51 | 119532.00 | 4838.28 | 3048.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1244.47 |
April | 15264.36 | 22-APR-10:35 | 10245.60 | 1209.57 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 171.13 |
May | 15118.82 | 18-MAY-15:13 | 25614.00 | 1814.35 | 1066.88 | 0.00 | 0.00 | 0.00 | 0.00 | 180.76 | 0.00 |
June | 15167.65 | 30-JUN-15:15 | 17076.00 | 1209.57 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 259.08 | 0.00 |
July | 15439.26 | 24-JUL-15:13 | 25614.00 | 1814.35 | 1066.88 | 0.00 | 0.00 | 0.00 | 0.00 | 189.25 | 0.00 |
August | 16202.91 | 25-AUG-15:13 | 25614.00 | 1814.35 | 1066.88 | 0.00 | 0.00 | 0.00 | 0.00 | 156.26 | 0.00 |
September | 16218.06 | 23-SEP-10:35 | 10245.60 | 1209.57 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 217.81 |
October | 17989.07 | 22-OCT-10:35 | 10245.60 | 1451.48 | 812.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 175.90 |
November | 15491.64 | 17-NOV-11:40 | 3415.20 | 604.78 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 357.28 |
December | 24869.83 | 23-DEC-21:41 | 119532.00 | 16933.98 | 8128.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1171.96 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 15118.82 | 3415.20 | 604.78 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 35204.76 | 153684.00 | 16933.98 | 8128.62 | 0.00 | 0.00 | 0.00 | 0.00 | 259.08 | 1313.96 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 108741.35 | 25-JAN-20:01 | 354845.40 | 118493.17 | 100292.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3793.35 |
February | 92844.76 | 24-FEB-22:51 | 456229.80 | 78995.45 | 73899.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3613.11 |
March | 100723.23 | 12-MAR-03:51 | 354845.40 | 26331.82 | 31671.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3709.46 |
April | 41727.87 | 13-APR-18:01 | 248391.78 | 73729.08 | 66509.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 289.68 |
May | 46025.31 | 18-MAY-18:05 | 212907.24 | 63196.36 | 57008.13 | 0.00 | 0.00 | 0.00 | 0.00 | 439.38 | 0.00 |
June | 47300.08 | 29-JUN-18:10 | 212907.24 | 63196.36 | 57008.13 | 0.00 | 0.00 | 0.00 | 0.00 | 788.34 | 0.00 |
July | 46587.30 | 24-JUL-18:10 | 212907.24 | 63196.36 | 57008.13 | 0.00 | 0.00 | 0.00 | 0.00 | 479.83 | 0.00 |
August | 45024.29 | 24-AUG-18:10 | 212907.24 | 63196.36 | 57008.13 | 0.00 | 0.00 | 0.00 | 0.00 | 165.39 | 0.00 |
September | 42521.59 | 01-SEP-18:10 | 212907.24 | 63196.36 | 57008.13 | 0.00 | 0.00 | 0.00 | 0.00 | 132.63 | 0.00 |
October | 41365.17 | 19-OCT-18:10 | 248391.78 | 73729.08 | 66509.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 347.41 |
November | 37453.56 | 01-NOV-20:00 | 35484.54 | 11849.32 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 563.36 |
December | 90756.25 | 23-DEC-21:41 | 354845.40 | 92161.35 | 84456.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3564.15 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 37453.56 | 35484.54 | 11849.32 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 108741.35 | 456229.80 | 118493.17 | 100292.09 | 0.00 | 0.00 | 0.00 | 0.00 | 788.34 | 3793.35 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1196.06 | 27-JAN-16:01 | 680.40 | 769.75 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 272.52 |
February | 3917.08 | 27-FEB-16:01 | 680.40 | 769.75 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 223.73 |
March | 3993.26 | 26-MAR-15:01 | 378.00 | 907.20 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.29 |
April | 4072.56 | 13-APR-15:01 | 680.40 | 769.75 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.64 |
May | 4082.78 | 14-MAY-18:01 | 819.00 | 2749.09 | 903.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.70 |
June | 4065.87 | 16-JUN-15:02 | 583.20 | 659.78 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.34 |
July | 3887.19 | 04-JUL-15:02 | 324.00 | 777.60 | 458.31 | 0.00 | 0.00 | 0.00 | 0.00 | 8.93 | 0.00 |
August | 3818.70 | 30-AUG-15:02 | 583.20 | 659.78 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 19.94 | 0.00 |
September | 4068.96 | 05-SEP-15:01 | 680.40 | 769.75 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.73 |
October | 4008.57 | 26-OCT-15:01 | 680.40 | 769.75 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.34 |
November | 3878.60 | 17-NOV-16:01 | 680.40 | 769.75 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.37 |
December | 614.84 | 28-DEC-16:04 | 680.40 | 769.75 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 167.82 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 614.84 | 324.00 | 659.78 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4082.78 | 819.00 | 2749.09 | 903.46 | 0.00 | 0.00 | 0.00 | 0.00 | 19.94 | 272.52 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 615.18 | 06-JAN-08:61 | 541.80 | 1209.46 | 792.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 450.21 |
February | 3273.07 | 28-FEB-16:02 | 583.20 | 659.70 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.20 |
March | 3748.25 | 26-MAR-18:01 | 819.00 | 2748.77 | 903.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.50 |
April | 3837.95 | 13-APR-15:01 | 680.40 | 769.66 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.81 |
May | 3905.80 | 14-MAY-18:01 | 819.00 | 2748.77 | 903.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.82 |
June | 3870.83 | 16-JUN-15:02 | 583.20 | 659.70 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.14 |
July | 3729.95 | 21-JUL-18:02 | 831.60 | 2096.92 | 774.30 | 0.00 | 0.00 | 0.00 | 0.00 | 15.36 | 0.00 |
August | 3700.46 | 29-AUG-15:02 | 583.20 | 659.70 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 19.34 | 0.00 |
September | 3868.56 | 06-SEP-15:01 | 680.40 | 769.66 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.50 |
October | 3756.15 | 26-OCT-15:01 | 680.40 | 769.66 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.16 |
November | 1858.97 | 17-NOV-16:01 | 680.40 | 769.66 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.48 |
December | 577.81 | 24-DEC-08:61 | 667.80 | 1539.31 | 1659.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 421.56 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 577.81 | 541.80 | 659.70 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3905.80 | 831.60 | 2748.77 | 1659.22 | 0.00 | 0.00 | 0.00 | 0.00 | 19.34 | 450.21 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 377.85 | 05-JAN-11:10 | 0.00 | 552.86 | 536.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.92 |
February | 619.33 | 22-FEB-14:00 | 0.00 | 69.11 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.50 |
March | 717.63 | 20-MAR-12:30 | 0.00 | 69.11 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.48 |
April | 784.40 | 13-APR-13:00 | 0.00 | 69.11 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.17 |
May | 755.34 | 18-MAY-13:10 | 0.00 | 69.11 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 8.78 | 0.00 |
June | 741.61 | 30-JUN-13:00 | 0.00 | 69.11 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 14.72 | 0.00 |
July | 795.74 | 23-JUL-13:20 | 0.00 | 81.45 | 74.82 | 0.00 | 0.00 | 0.00 | 0.00 | 11.81 | 0.00 |
August | 861.94 | 26-AUG-12:40 | 0.00 | 81.45 | 74.82 | 0.00 | 0.00 | 0.00 | 0.00 | 3.69 | 0.00 |
September | 871.54 | 01-SEP-13:10 | 0.00 | 69.11 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 2.22 | 0.00 |
October | 1041.05 | 22-OCT-12:20 | 0.00 | 81.45 | 74.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.44 |
November | 676.64 | 17-NOV-12:20 | 0.00 | 69.11 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.10 |
December | 363.06 | 24-DEC-11:10 | 0.00 | 651.59 | 598.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.77 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 363.06 | 0.00 | 69.11 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1041.05 | 0.00 | 651.59 | 598.54 | 0.00 | 0.00 | 0.00 | 0.00 | 14.72 | 109.92 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 444.82 | 06-JAN-08:61 | 541.80 | 760.39 | 776.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.75 |
February | 418.87 | 14-FEB-08:61 | 619.20 | 869.02 | 887.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 117.99 |
March | 1026.37 | 28-MAR-18:02 | 831.60 | 1318.35 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.62 |
April | 1095.96 | 14-APR-18:01 | 970.20 | 1538.07 | 885.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.89 |
May | 1157.68 | 21-MAY-18:02 | 702.00 | 1481.29 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.42 |
June | 1183.04 | 17-JUN-18:02 | 702.00 | 1481.29 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 1.45 | 0.00 |
July | 1128.46 | 10-JUL-18:02 | 831.60 | 1318.35 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.51 | 0.00 |
August | 1120.72 | 20-AUG-15:02 | 324.00 | 488.83 | 449.03 | 0.00 | 0.00 | 0.00 | 0.00 | 5.12 | 0.00 |
September | 1127.84 | 04-SEP-18:01 | 819.00 | 1728.17 | 885.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.15 |
October | 1087.22 | 01-OCT-18:01 | 819.00 | 1728.17 | 885.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.90 |
November | 901.62 | 01-NOV-18:03 | 415.80 | 659.17 | 379.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.30 |
December | 415.87 | 24-DEC-08:61 | 667.80 | 967.78 | 1625.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.30 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 415.87 | 324.00 | 488.83 | 379.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1183.04 | 970.20 | 1728.17 | 1625.79 | 0.00 | 0.00 | 0.00 | 0.00 | 5.12 | 126.75 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 637.12 | 17-JAN-16:04 | 680.40 | 769.75 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 182.12 |
February | 3368.51 | 28-FEB-16:02 | 583.20 | 659.78 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.65 |
March | 3599.99 | 31-MAR-15:01 | 680.40 | 769.75 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.95 |
April | 3688.27 | 22-APR-08:62 | 324.00 | 1319.56 | 979.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.75 |
May | 3700.96 | 06-MAY-08:62 | 324.00 | 1319.56 | 979.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.99 |
June | 3671.79 | 16-JUN-15:02 | 583.20 | 659.78 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.45 |
July | 3663.47 | 24-JUL-08:61 | 252.00 | 1209.60 | 792.83 | 0.00 | 0.00 | 0.00 | 0.00 | 1.88 | 0.00 |
August | 3587.96 | 25-AUG-08:62 | 216.00 | 1036.80 | 679.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.71 |
September | 3735.85 | 09-SEP-08:61 | 378.00 | 1539.49 | 1143.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.64 |
October | 3633.04 | 21-OCT-15:02 | 324.00 | 777.60 | 458.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.22 |
November | 3329.40 | 16-NOV-09:01 | 252.00 | 1209.60 | 792.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 153.82 |
December | 777.65 | 28-DEC-09:04 | 252.00 | 1209.60 | 792.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 179.95 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 637.12 | 216.00 | 659.78 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3735.85 | 680.40 | 1539.49 | 1143.15 | 0.00 | 0.00 | 0.00 | 0.00 | 1.88 | 182.12 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 595.95 | 26-JAN-08:61 | 619.20 | 1382.24 | 905.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 426.88 |
February | 948.86 | 28-FEB-09:03 | 252.00 | 1209.46 | 792.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 231.30 |
March | 3250.25 | 26-MAR-08:61 | 378.00 | 1539.31 | 1143.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 158.24 |
April | 3510.95 | 22-APR-08:62 | 324.00 | 1319.41 | 979.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.65 |
May | 3532.18 | 06-MAY-08:62 | 324.00 | 1319.41 | 979.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.07 |
June | 3490.94 | 16-JUN-15:02 | 583.20 | 659.70 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.25 |
July | 3507.87 | 24-JUL-08:61 | 252.00 | 1209.46 | 792.74 | 0.00 | 0.00 | 0.00 | 0.00 | 1.68 | 0.00 |
August | 3430.85 | 20-AUG-08:62 | 324.00 | 1319.41 | 979.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.53 |
September | 3557.83 | 09-SEP-08:61 | 378.00 | 1539.31 | 1143.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.58 |
October | 3344.29 | 01-OCT-15:01 | 378.00 | 907.09 | 534.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.17 |
November | 1019.84 | 10-NOV-09:03 | 252.00 | 1209.46 | 792.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 200.24 |
December | 576.58 | 24-DEC-08:61 | 667.80 | 1539.31 | 1659.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 421.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 576.58 | 252.00 | 659.70 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3557.83 | 667.80 | 1539.31 | 1659.22 | 0.00 | 0.00 | 0.00 | 0.00 | 1.68 | 426.88 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5698.01 | 26-JAN-07:00 | 1760.39 | 570.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 485.37 |
February | 5778.79 | 14-FEB-07:00 | 1760.39 | 570.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 489.94 |
March | 5173.83 | 05-MAR-03:55 | 3520.78 | 570.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 447.66 |
April | 2744.56 | 23-APR-18:10 | 10562.33 | 6983.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.47 | 0.00 |
May | 3120.04 | 18-MAY-18:10 | 10562.33 | 6840.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.01 | 0.00 |
June | 3330.71 | 30-JUN-10:40 | 502.97 | 356.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.91 | 0.00 |
July | 3375.35 | 23-JUL-10:35 | 1508.90 | 855.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.05 | 0.00 |
August | 3187.72 | 26-AUG-10:35 | 1508.90 | 712.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 0.00 |
September | 3046.16 | 01-SEP-10:40 | 502.97 | 356.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.81 | 0.00 |
October | 2879.70 | 22-OCT-10:35 | 1508.90 | 855.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.88 |
November | 1814.21 | 17-NOV-13:30 | 502.97 | 356.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.94 |
December | 4991.32 | 24-DEC-06:00 | 1760.39 | 285.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 462.61 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 1814.21 | 502.97 | 285.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5778.79 | 10562.33 | 6983.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.91 | 489.94 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 982.89 | 17-JAN-16:03 | 680.40 | 769.75 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 182.59 |
February | 4065.57 | 27-FEB-16:01 | 680.40 | 769.75 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 223.68 |
March | 4165.05 | 26-MAR-15:01 | 378.00 | 907.20 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.52 |
April | 4262.96 | 13-APR-15:01 | 680.40 | 769.75 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.11 |
May | 4283.71 | 14-MAY-18:01 | 819.00 | 2749.09 | 903.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.32 |
June | 4267.24 | 16-JUN-15:02 | 583.20 | 659.78 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.98 |
July | 4165.41 | 24-JUL-18:02 | 831.60 | 2097.16 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 32.58 | 0.00 |
August | 4052.50 | 07-AUG-15:02 | 583.20 | 659.78 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.69 | 0.00 |
September | 4259.23 | 05-SEP-15:01 | 680.40 | 769.75 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.19 |
October | 4190.88 | 26-OCT-15:01 | 680.40 | 769.75 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.72 |
November | 4042.84 | 17-NOV-16:01 | 680.40 | 769.75 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.57 |
December | 576.57 | 24-DEC-08:61 | 667.80 | 1539.49 | 1659.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 421.59 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 576.57 | 378.00 | 659.78 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4283.71 | 831.60 | 2749.09 | 1659.41 | 0.00 | 0.00 | 0.00 | 0.00 | 32.58 | 421.59 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 747.79 | 17-JAN-16:04 | 680.40 | 769.66 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 182.57 |
February | 2094.59 | 28-FEB-16:02 | 583.20 | 659.70 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.96 |
March | 3911.62 | 26-MAR-18:01 | 819.00 | 2748.77 | 903.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.02 |
April | 3996.35 | 13-APR-15:01 | 680.40 | 769.66 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.18 |
May | 4083.14 | 14-MAY-18:01 | 819.00 | 2748.77 | 903.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.46 |
June | 4046.98 | 16-JUN-15:02 | 583.20 | 659.70 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.78 |
July | 3972.50 | 24-JUL-18:02 | 831.60 | 2096.92 | 774.30 | 0.00 | 0.00 | 0.00 | 0.00 | 32.36 | 0.00 |
August | 3827.96 | 30-AUG-15:02 | 583.20 | 659.70 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 19.58 | 0.00 |
September | 4032.52 | 06-SEP-15:01 | 680.40 | 769.66 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.94 |
October | 3904.97 | 01-OCT-15:01 | 378.00 | 907.09 | 534.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.85 |
November | 835.76 | 15-NOV-19:04 | 970.20 | 2446.40 | 903.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.15 |
December | 576.33 | 24-DEC-08:61 | 667.80 | 1539.31 | 1659.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 421.48 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 576.33 | 378.00 | 659.70 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4083.14 | 970.20 | 2748.77 | 1659.22 | 0.00 | 0.00 | 0.00 | 0.00 | 32.36 | 421.48 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2301.11 | 27-JAN-16:01 | 680.40 | 483.89 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 144.72 |
February | 2315.51 | 27-FEB-16:01 | 680.40 | 483.89 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 115.58 |
March | 2353.23 | 26-MAR-15:01 | 378.00 | 570.30 | 523.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.47 |
April | 2384.85 | 13-APR-15:01 | 680.40 | 483.89 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.10 |
May | 2360.49 | 04-MAY-15:02 | 583.20 | 414.76 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.45 |
June | 2339.93 | 04-JUN-15:02 | 324.00 | 488.83 | 449.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.77 |
July | 2227.37 | 24-JUL-18:02 | 831.60 | 1318.35 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 17.44 | 0.00 |
August | 2305.03 | 25-AUG-15:02 | 583.20 | 414.76 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 17.96 | 0.00 |
September | 2373.17 | 08-SEP-15:01 | 680.40 | 483.89 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.34 |
October | 2380.96 | 26-OCT-15:01 | 680.40 | 483.89 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.96 |
November | 2306.70 | 17-NOV-16:01 | 680.40 | 483.89 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.91 |
December | 2259.25 | 02-DEC-16:01 | 378.00 | 570.30 | 523.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 162.74 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2227.37 | 324.00 | 414.76 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2384.85 | 831.60 | 1318.35 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 17.96 | 162.74 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 46971.69 | 25-JAN-20:01 | 209912.64 | 38233.93 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 844.89 |
February | 39959.23 | 24-FEB-22:51 | 269887.68 | 25489.28 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 803.47 |
March | 43164.45 | 12-MAR-03:51 | 209912.64 | 8496.43 | 22493.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 823.68 |
April | 19697.49 | 13-APR-18:10 | 146938.85 | 23790.00 | 47235.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.30 |
May | 22349.57 | 25-MAY-18:10 | 125947.58 | 20391.43 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 108.61 | 0.00 |
June | 23139.42 | 29-JUN-18:10 | 125947.58 | 20391.43 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 159.87 | 0.00 |
July | 22509.26 | 24-JUL-18:10 | 125947.58 | 20391.43 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 92.17 | 0.00 |
August | 21777.17 | 09-AUG-18:10 | 125947.58 | 20391.43 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 71.62 | 0.00 |
September | 20487.14 | 01-SEP-18:10 | 125947.58 | 20391.43 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 15.64 | 0.00 |
October | 19378.11 | 19-OCT-22:00 | 26988.77 | 2548.93 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 180.07 |
November | 19222.30 | 01-NOV-22:00 | 26988.77 | 2548.93 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 183.68 |
December | 38640.16 | 23-DEC-21:41 | 209912.64 | 29737.50 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 789.49 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 19222.30 | 26988.77 | 2548.93 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 46971.69 | 269887.68 | 38233.93 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 159.87 | 844.89 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 49521.47 | 25-JAN-20:01 | 209912.64 | 38233.93 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 844.32 |
February | 42223.65 | 24-FEB-22:51 | 269887.68 | 25489.28 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 803.38 |
March | 45542.22 | 12-MAR-03:51 | 209912.64 | 8496.43 | 22493.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 823.25 |
April | 20995.36 | 13-APR-18:10 | 146938.85 | 23790.00 | 47235.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.06 |
May | 23780.12 | 25-MAY-18:10 | 125947.58 | 20391.43 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 106.92 | 0.00 |
June | 24583.75 | 29-JUN-18:10 | 125947.58 | 20391.43 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 158.35 | 0.00 |
July | 23905.86 | 24-JUL-18:10 | 125947.58 | 20391.43 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 90.70 | 0.00 |
August | 23201.26 | 09-AUG-18:10 | 125947.58 | 20391.43 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 69.78 | 0.00 |
September | 21813.80 | 01-SEP-18:10 | 125947.58 | 20391.43 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 13.98 | 0.00 |
October | 20630.50 | 19-OCT-22:00 | 26988.77 | 2548.93 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 181.72 |
November | 20502.93 | 01-NOV-22:00 | 26988.77 | 2548.93 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 185.50 |
December | 41112.76 | 23-DEC-21:41 | 209912.64 | 29737.50 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 791.31 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 20502.93 | 26988.77 | 2548.93 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 49521.47 | 269887.68 | 38233.93 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 158.35 | 844.32 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 55704.22 | 25-JAN-20:01 | 18679.92 | 10207.78 | 151121.06 | 149952.21 | 0.00 | 0.00 | 0.00 | 0.00 | 755.46 |
February | 46998.31 | 01-FEB-18:11 | 13342.80 | 6805.19 | 151121.06 | 224928.32 | 0.00 | 0.00 | 0.00 | 0.00 | 709.25 |
March | 42645.88 | 15-MAR-06:51 | 10674.24 | 5670.99 | 151121.06 | 112464.16 | 0.00 | 0.00 | 0.00 | 0.00 | 675.71 |
April | 30021.00 | 18-APR-10:40 | 1067.42 | 567.10 | 30224.21 | 37488.05 | 0.00 | 0.00 | 0.00 | 0.00 | 93.82 |
May | 30998.88 | 18-MAY-10:40 | 1067.42 | 567.10 | 30224.21 | 37488.05 | 0.00 | 0.00 | 0.00 | 28.04 | 0.00 |
June | 31833.77 | 25-JUN-10:40 | 1601.14 | 680.52 | 30224.21 | 37488.05 | 0.00 | 0.00 | 0.00 | 47.09 | 0.00 |
July | 31887.92 | 29-JUL-10:40 | 1601.14 | 567.10 | 30224.21 | 37488.05 | 0.00 | 0.00 | 0.00 | 46.76 | 0.00 |
August | 31092.82 | 25-AUG-10:40 | 1067.42 | 567.10 | 30224.21 | 37488.05 | 0.00 | 0.00 | 0.00 | 2.45 | 0.00 |
September | 30844.10 | 01-SEP-10:40 | 533.71 | 283.55 | 15112.11 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 18.94 |
October | 29373.41 | 22-OCT-10:40 | 1601.14 | 680.52 | 30224.21 | 37488.05 | 0.00 | 0.00 | 0.00 | 0.00 | 130.73 |
November | 26667.88 | 01-NOV-18:07 | 5603.98 | 2722.08 | 45336.32 | 44985.66 | 0.00 | 0.00 | 0.00 | 0.00 | 176.95 |
December | 43270.36 | 23-DEC-21:41 | 18679.92 | 7939.39 | 151121.06 | 112464.16 | 0.00 | 0.00 | 0.00 | 0.00 | 684.01 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 26667.88 | 533.71 | 283.55 | 15112.11 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 55704.22 | 18679.92 | 10207.78 | 151121.06 | 224928.32 | 0.00 | 0.00 | 0.00 | 47.09 | 755.46 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 9734.19 | 25-JAN-20:01 | 18631.20 | 13574.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 750.24 |
February | 8243.97 | 01-FEB-18:11 | 13308.00 | 9049.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 727.17 |
March | 9022.89 | 12-MAR-03:51 | 18631.20 | 3016.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 741.85 |
April | 5583.92 | 13-APR-16:20 | 1330.80 | 377.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.58 |
May | 6870.30 | 18-MAY-10:35 | 1064.64 | 754.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.48 | 0.00 |
June | 7247.16 | 30-JUN-10:40 | 532.32 | 377.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 125.83 | 0.00 |
July | 7345.69 | 23-JUL-10:35 | 1596.96 | 904.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.16 | 0.00 |
August | 6868.53 | 25-AUG-10:35 | 1064.64 | 754.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.29 | 0.00 |
September | 6571.30 | 01-SEP-10:40 | 532.32 | 377.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.09 | 0.00 |
October | 5791.85 | 22-OCT-10:35 | 1596.96 | 904.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.96 |
November | 3644.81 | 17-NOV-13:10 | 532.32 | 377.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 161.36 |
December | 7861.97 | 02-DEC-00:31 | 23954.40 | 3016.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 718.27 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 3644.81 | 532.32 | 377.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 9734.19 | 23954.40 | 13574.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 125.83 | 750.24 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.578248E+12 | 340215.45 | 04-JAN-20:49 | 0.177804E+13 | 1431349.25 | 04-JAN-21:00 |
February | 0.513695E+12 | 330748.39 | 01-FEB-20:10 | 0.119241E+13 | 1356290.07 | 01-FEB-21:00 |
March | 0.564377E+12 | 340714.74 | 28-MAR-19:10 | 0.962343E+12 | 1185620.77 | 05-MAR-07:19 |
April | 0.570492E+12 | 449350.33 | 23-APR-19:10 | 0.625336E+12 | 531475.62 | 04-APR-17:00 |
May | 0.677993E+12 | 502656.04 | 25-MAY-18:10 | 0.566163E+12 | 452043.10 | 08-MAY-17:49 |
June | 0.763322E+12 | 606703.94 | 29-JUN-18:10 | 0.526762E+12 | 435744.59 | 09-JUN-17:19 |
July | 0.848852E+12 | 541239.95 | 03-JUL-18:10 | 0.517640E+12 | 425656.28 | 30-JUL-16:49 |
August | 0.782328E+12 | 525656.27 | 08-AUG-18:10 | 0.508984E+12 | 414600.08 | 03-AUG-16:49 |
September | 0.627700E+12 | 451045.74 | 01-SEP-18:10 | 0.509741E+12 | 424284.74 | 10-SEP-16:00 |
October | 0.585432E+12 | 358782.78 | 19-OCT-18:10 | 0.591391E+12 | 485918.88 | 29-OCT-18:10 |
November | 0.546747E+12 | 333608.65 | 01-NOV-19:49 | 0.764914E+12 | 735166.63 | 25-NOV-17:30 |
December | 0.575994E+12 | 336133.95 | 19-DEC-20:19 | 0.162988E+13 | 1385150.07 | 19-DEC-21:00 |
Annual Sum or Average | 0.763518E+13 | 0.101736E+14 | ||||
Minimum of Months | 0.513695E+12 | 330748.39 | 0.508984E+12 | 414600.08 | ||
Maximum of Months | 0.848852E+12 | 606703.94 | 0.177804E+13 | 1431349.25 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [J] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.997859E+11 | 0.287108E+11 | 0.148746E+12 | 0.577258E+11 | 0.175294E+12 | 0.538857E+10 | 0.00 | 0.606589E+09 | 0.00 | 0.00 | 0.486303E+11 | 0.772078E+10 | 0.00 |
February | 0.901073E+11 | 0.235835E+11 | 0.134341E+12 | 0.521396E+11 | 0.147628E+12 | 0.656922E+10 | 0.00 | 0.305286E+10 | 0.00 | 0.00 | 0.439241E+11 | 0.696978E+10 | 0.00 |
March | 0.995228E+11 | 0.229226E+11 | 0.148757E+12 | 0.577286E+11 | 0.157598E+12 | 0.850874E+10 | 0.00 | 0.686519E+10 | 0.00 | 0.00 | 0.486303E+11 | 0.770823E+10 | 0.00 |
April | 0.965474E+11 | 0.189770E+11 | 0.143913E+12 | 0.558635E+11 | 0.151355E+12 | 0.147726E+11 | 0.00 | 0.319486E+11 | 0.00 | 0.00 | 0.436242E+11 | 0.746798E+10 | 0.00 |
May | 0.996636E+11 | 0.167238E+11 | 0.148757E+12 | 0.577273E+11 | 0.162077E+12 | 0.240250E+11 | 0.00 | 0.116688E+12 | 0.00 | 0.00 | 0.383075E+11 | 0.770714E+10 | 0.00 |
June | 0.963626E+11 | 0.146208E+11 | 0.143963E+12 | 0.558662E+11 | 0.159857E+12 | 0.265713E+11 | 0.00 | 0.216462E+12 | 0.00 | 0.00 | 0.359659E+11 | 0.745933E+10 | 0.00 |
July | 0.998551E+11 | 0.158425E+11 | 0.148708E+12 | 0.577246E+11 | 0.167287E+12 | 0.291350E+11 | 0.00 | 0.278505E+12 | 0.00 | 0.00 | 0.376775E+11 | 0.771482E+10 | 0.00 |
August | 0.995413E+11 | 0.183160E+11 | 0.148768E+12 | 0.577287E+11 | 0.164171E+12 | 0.274221E+11 | 0.00 | 0.216492E+12 | 0.00 | 0.00 | 0.357628E+11 | 0.770699E+10 | 0.00 |
September | 0.965794E+11 | 0.207795E+11 | 0.143924E+12 | 0.558636E+11 | 0.154422E+12 | 0.216180E+11 | 0.00 | 0.847201E+11 | 0.00 | 0.00 | 0.361773E+11 | 0.746907E+10 | 0.00 |
October | 0.997606E+11 | 0.247952E+11 | 0.148735E+12 | 0.577257E+11 | 0.155327E+12 | 0.140065E+11 | 0.00 | 0.247582E+11 | 0.00 | 0.00 | 0.463548E+11 | 0.770655E+10 | 0.00 |
November | 0.965244E+11 | 0.269082E+11 | 0.143978E+12 | 0.558644E+11 | 0.151174E+12 | 0.693827E+10 | 0.00 | 0.510845E+10 | 0.00 | 0.00 | 0.468136E+11 | 0.745273E+10 | 0.00 |
December | 0.998619E+11 | 0.294819E+11 | 0.148708E+12 | 0.577246E+11 | 0.172920E+12 | 0.482637E+10 | 0.00 | 0.354536E+09 | 0.00 | 0.00 | 0.486303E+11 | 0.772608E+10 | 0.00 |
Annual Sum or Average | 0.117411E+13 | 0.261662E+12 | 0.175130E+13 | 0.679683E+12 | 0.191911E+13 | 0.189782E+12 | 0.00 | 0.985562E+12 | 0.00 | 0.00 | 0.510499E+12 | 0.908095E+11 | 0.00 |
Minimum of Months | 0.901073E+11 | 0.146208E+11 | 0.134341E+12 | 0.521396E+11 | 0.147628E+12 | 0.482637E+10 | 0.00 | 0.354536E+09 | 0.00 | 0.00 | 0.357628E+11 | 0.696978E+10 | 0.00 |
Maximum of Months | 0.998619E+11 | 0.294819E+11 | 0.148768E+12 | 0.577287E+11 | 0.175294E+12 | 0.291350E+11 | 0.00 | 0.278505E+12 | 0.00 | 0.00 | 0.486303E+11 | 0.772608E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.151918E+12 | 0.00 | 0.130967E+13 | 0.00 | 0.316453E+12 | 0.00 | 0.00 |
February | 0.137204E+12 | 0.00 | 0.767097E+12 | 0.00 | 0.288111E+12 | 0.00 | 0.00 |
March | 0.152024E+12 | 0.00 | 0.491779E+12 | 0.00 | 0.318541E+12 | 0.00 | 0.00 |
April | 0.146956E+12 | 0.00 | 0.173602E+12 | 0.00 | 0.304778E+12 | 0.00 | 0.00 |
May | 0.151978E+12 | 0.00 | 0.104980E+12 | 0.00 | 0.309205E+12 | 0.00 | 0.00 |
June | 0.147114E+12 | 0.00 | 0.904985E+11 | 0.00 | 0.289150E+12 | 0.00 | 0.00 |
July | 0.151820E+12 | 0.00 | 0.777551E+11 | 0.00 | 0.288064E+12 | 0.00 | 0.00 |
August | 0.152039E+12 | 0.00 | 0.743733E+11 | 0.00 | 0.282572E+12 | 0.00 | 0.00 |
September | 0.146971E+12 | 0.00 | 0.884135E+11 | 0.00 | 0.274357E+12 | 0.00 | 0.00 |
October | 0.151903E+12 | 0.00 | 0.148850E+12 | 0.00 | 0.290637E+12 | 0.00 | 0.00 |
November | 0.147091E+12 | 0.00 | 0.325256E+12 | 0.00 | 0.292567E+12 | 0.00 | 0.00 |
December | 0.151820E+12 | 0.00 | 0.116699E+13 | 0.00 | 0.311069E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.178884E+13 | 0.00 | 0.481926E+13 | 0.00 | 0.356550E+13 | 0.00 | 0.00 |
Minimum of Months | 0.137204E+12 | 0.00 | 0.743733E+11 | 0.00 | 0.274357E+12 | 0.00 | 0.00 |
Maximum of Months | 0.152039E+12 | 0.00 | 0.130967E+13 | 0.00 | 0.318541E+12 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 93091.76 | 02-JAN-20:10 | 16690.39 | 01-JAN-00:10 | 89674.66 | 02-JAN-07:10 | 40537.60 | 02-JAN-07:19 | 92214.49 | 09-JAN-04:00 | 8478.96 | 27-JAN-14:00 | 0.00 | 01-JAN-00:10 |
February | 93091.76 | 01-FEB-20:10 | 16690.39 | 01-FEB-00:10 | 89674.66 | 01-FEB-07:10 | 40537.60 | 01-FEB-07:19 | 86947.39 | 17-FEB-05:00 | 9002.26 | 22-FEB-16:10 | 0.00 | 01-FEB-00:10 |
March | 93091.76 | 01-MAR-20:10 | 16690.39 | 01-MAR-00:10 | 89674.66 | 01-MAR-07:10 | 40537.60 | 01-MAR-07:19 | 81168.42 | 05-MAR-04:00 | 9272.18 | 19-MAR-15:09 | 0.00 | 01-MAR-00:10 |
April | 93091.76 | 03-APR-19:10 | 16690.39 | 01-APR-00:10 | 89674.66 | 03-APR-06:10 | 40537.60 | 03-APR-06:19 | 74023.35 | 23-APR-15:09 | 12371.80 | 23-APR-15:30 | 0.00 | 01-APR-00:10 |
May | 93091.76 | 01-MAY-19:10 | 16690.39 | 01-MAY-00:10 | 89674.66 | 01-MAY-06:10 | 40537.60 | 01-MAY-06:19 | 78174.36 | 18-MAY-15:20 | 12735.77 | 18-MAY-16:49 | 0.00 | 01-MAY-00:10 |
June | 93091.76 | 01-JUN-19:10 | 16690.39 | 01-JUN-00:10 | 89674.66 | 01-JUN-06:10 | 40537.60 | 01-JUN-06:19 | 80453.57 | 29-JUN-15:20 | 13448.70 | 30-JUN-10:39 | 0.00 | 01-JUN-00:10 |
July | 93091.76 | 03-JUL-19:10 | 16690.39 | 01-JUL-00:10 | 89674.66 | 03-JUL-06:10 | 40537.60 | 03-JUL-06:19 | 79871.57 | 24-JUL-15:20 | 13486.55 | 23-JUL-10:39 | 0.00 | 01-JUL-00:10 |
August | 93091.76 | 01-AUG-19:10 | 16690.39 | 01-AUG-00:10 | 89674.66 | 01-AUG-06:10 | 40537.60 | 01-AUG-06:19 | 79378.90 | 25-AUG-15:09 | 13124.08 | 08-AUG-10:39 | 0.00 | 01-AUG-00:10 |
September | 93091.76 | 01-SEP-19:10 | 16690.39 | 01-SEP-00:10 | 89674.66 | 01-SEP-06:10 | 40537.60 | 01-SEP-06:19 | 78683.42 | 01-SEP-15:20 | 12845.15 | 01-SEP-10:39 | 0.00 | 01-SEP-00:10 |
October | 93091.76 | 02-OCT-19:10 | 16690.39 | 01-OCT-00:10 | 89674.66 | 02-OCT-06:10 | 40537.60 | 02-OCT-06:19 | 74523.47 | 19-OCT-15:09 | 12333.73 | 19-OCT-15:30 | 0.00 | 01-OCT-00:10 |
November | 93091.76 | 01-NOV-19:10 | 16690.39 | 01-NOV-00:10 | 89674.66 | 01-NOV-06:10 | 40537.60 | 01-NOV-06:19 | 73345.24 | 25-NOV-16:10 | 9758.83 | 01-NOV-15:09 | 0.00 | 01-NOV-00:10 |
December | 93091.76 | 01-DEC-20:10 | 16690.39 | 01-DEC-00:10 | 89674.66 | 01-DEC-07:10 | 40537.60 | 01-DEC-07:19 | 91578.60 | 24-DEC-05:00 | 8340.07 | 02-DEC-14:30 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 93091.76 | 16690.39 | 89674.66 | 40537.60 | 73345.24 | 8340.07 | 0.00 | |||||||
Maximum of Months | 93091.76 | 16690.39 | 89674.66 | 40537.60 | 92214.49 | 13486.55 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY {Maximum} [W] | HEATRECOVERY:ELECTRICITY {TIMESTAMP} | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 9230.14 | 27-JAN-14:39 | 0.00 | 0.00 | 18156.47 | 01-JAN-08:20 | 4755.74 | 06-JAN-07:30 | 0.00 |
February | 25485.10 | 22-FEB-16:10 | 0.00 | 0.00 | 18156.47 | 01-FEB-09:20 | 4754.07 | 14-FEB-07:19 | 0.00 |
March | 30556.61 | 31-MAR-15:09 | 0.00 | 0.00 | 18156.47 | 01-MAR-00:10 | 4740.24 | 15-MAR-06:40 | 0.00 |
April | 139667.71 | 23-APR-18:10 | 0.00 | 0.00 | 18156.47 | 01-APR-22:10 | 4739.10 | 11-APR-06:10 | 0.00 |
May | 193320.02 | 25-MAY-18:10 | 0.00 | 0.00 | 18156.47 | 01-MAY-07:19 | 4739.30 | 10-MAY-06:10 | 0.00 |
June | 301034.78 | 29-JUN-15:00 | 0.00 | 0.00 | 18156.47 | 01-JUN-22:10 | 4738.72 | 30-JUN-06:10 | 0.00 |
July | 263178.15 | 15-JUL-15:09 | 0.00 | 0.00 | 18156.47 | 01-JUL-05:10 | 4738.84 | 19-JUL-06:10 | 0.00 |
August | 250841.04 | 08-AUG-15:20 | 0.00 | 0.00 | 18156.47 | 01-AUG-22:00 | 4738.98 | 02-AUG-06:19 | 0.00 |
September | 162885.15 | 01-SEP-15:30 | 0.00 | 0.00 | 18156.47 | 01-SEP-15:09 | 4738.65 | 26-SEP-06:10 | 0.00 |
October | 117001.13 | 19-OCT-15:09 | 0.00 | 0.00 | 18156.47 | 01-OCT-07:19 | 4739.88 | 11-OCT-06:10 | 0.00 |
November | 61832.74 | 01-NOV-15:09 | 0.00 | 0.00 | 18156.47 | 01-NOV-07:10 | 4739.24 | 29-NOV-07:40 | 0.00 |
December | 6716.74 | 02-DEC-14:30 | 0.00 | 0.00 | 18156.47 | 01-DEC-09:09 | 4753.44 | 20-DEC-07:10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6716.74 | 0.00 | 0.00 | 18156.47 | 4738.65 | 0.00 | |||
Maximum of Months | 301034.78 | 0.00 | 0.00 | 18156.47 | 4755.74 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 340215.45 | 04-JAN-20:49 | 93091.76 | 88971.67 | 16690.39 | 33025.38 | 82073.56 | 2219.94 | 0.00 | 0.00 | 0.00 |
February | 330748.39 | 01-FEB-20:10 | 93091.76 | 88971.67 | 16690.39 | 33012.66 | 72711.49 | 2094.42 | 0.00 | 0.00 | 0.00 |
March | 340714.74 | 28-MAR-19:10 | 93091.76 | 88971.67 | 16690.39 | 33012.66 | 60711.23 | 8250.82 | 0.00 | 15557.60 | 0.00 |
April | 449350.33 | 23-APR-19:10 | 87949.43 | 87485.24 | 16690.39 | 32961.22 | 67821.78 | 12024.64 | 0.00 | 120280.21 | 0.00 |
May | 502656.04 | 25-MAY-18:10 | 82800.17 | 79617.06 | 0.00 | 32686.23 | 76028.77 | 12556.96 | 0.00 | 193320.02 | 0.00 |
June | 606703.94 | 29-JUN-18:10 | 82800.17 | 79617.06 | 0.00 | 32686.23 | 78734.71 | 13182.75 | 0.00 | 293975.92 | 0.00 |
July | 541239.95 | 03-JUL-18:10 | 82800.17 | 79617.06 | 0.00 | 32686.23 | 73315.71 | 12933.08 | 0.00 | 234056.70 | 0.00 |
August | 525656.27 | 08-AUG-18:10 | 82800.17 | 79617.06 | 0.00 | 32686.23 | 74270.14 | 12685.49 | 0.00 | 218398.38 | 0.00 |
September | 451045.74 | 01-SEP-18:10 | 82800.17 | 79617.06 | 0.00 | 32686.23 | 72607.02 | 12183.54 | 0.00 | 146136.64 | 0.00 |
October | 358782.78 | 19-OCT-18:10 | 82800.17 | 79617.06 | 16690.39 | 32686.23 | 64362.63 | 10856.43 | 0.00 | 64310.67 | 0.00 |
November | 333608.65 | 01-NOV-19:49 | 93091.76 | 88971.67 | 16690.39 | 33025.38 | 58475.28 | 7383.59 | 0.00 | 11163.10 | 0.00 |
December | 336133.95 | 19-DEC-20:19 | 93091.76 | 88971.67 | 16690.39 | 33025.38 | 78304.26 | 2191.59 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 330748.39 | 82800.17 | 79617.06 | 0.00 | 32686.23 | 58475.28 | 2094.42 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 606703.94 | 93091.76 | 88971.67 | 16690.39 | 33025.38 | 82073.56 | 13182.75 | 0.00 | 293975.92 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 104248.32 | 02-JAN-18:10 | 0.00 | 1111818.01 | 06-JAN-04:00 | 0.00 | 313153.50 | 31-JAN-21:40 | 0.00 |
February | 104248.32 | 01-FEB-18:10 | 0.00 | 1078877.55 | 17-FEB-05:00 | 0.00 | 314208.85 | 28-FEB-21:00 | 0.00 |
March | 104248.32 | 01-MAR-18:10 | 0.00 | 1036261.82 | 05-MAR-06:00 | 0.00 | 314232.99 | 02-MAR-21:19 | 0.00 |
April | 104248.32 | 01-APR-17:10 | 0.00 | 285493.13 | 05-APR-06:10 | 0.00 | 311583.11 | 03-APR-20:30 | 0.00 |
May | 104248.32 | 01-MAY-17:10 | 0.00 | 113217.36 | 09-MAY-10:39 | 0.00 | 306145.19 | 02-MAY-20:49 | 0.00 |
June | 104248.32 | 01-JUN-17:10 | 0.00 | 107970.26 | 13-JUN-10:39 | 0.00 | 298159.15 | 01-JUN-20:40 | 0.00 |
July | 104248.32 | 01-JUL-17:10 | 0.00 | 106280.65 | 10-JUL-10:39 | 0.00 | 288955.60 | 03-JUL-20:40 | 0.00 |
August | 104248.32 | 01-AUG-17:10 | 0.00 | 112304.31 | 18-AUG-10:39 | 0.00 | 276994.60 | 18-AUG-20:10 | 0.00 |
September | 104248.32 | 01-SEP-17:10 | 0.00 | 111852.62 | 29-SEP-10:39 | 0.00 | 279450.34 | 18-SEP-20:49 | 0.00 |
October | 104248.32 | 02-OCT-17:10 | 0.00 | 234091.06 | 30-OCT-08:09 | 0.00 | 291904.01 | 31-OCT-20:49 | 0.00 |
November | 104248.32 | 01-NOV-17:10 | 0.00 | 427739.81 | 25-NOV-07:10 | 0.00 | 300573.39 | 30-NOV-21:00 | 0.00 |
December | 104248.32 | 01-DEC-18:10 | 0.00 | 1078410.47 | 24-DEC-05:00 | 0.00 | 307866.58 | 29-DEC-21:40 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 104248.32 | 0.00 | 106280.65 | 0.00 | 276994.60 | 0.00 | |||
Maximum of Months | 104248.32 | 0.00 | 1111818.01 | 0.00 | 314232.99 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 462.83 | 16.02 | 462.83 | 16.02 | 0.00 | 16.02 | 0.00 | 16.02 |
February | 210.17 | 18.31 | 210.17 | 18.31 | 0.00 | 18.31 | 0.00 | 18.31 |
March | 65.00 | 19.01 | 65.00 | 19.01 | 0.00 | 19.01 | 0.00 | 19.01 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 336.00 | 16.79 | 336.00 | 16.79 | 0.00 | 16.79 | 0.00 | 16.79 |
Annual Sum or Average | 1074.00 | 16.89 | 1074.00 | 16.89 | 0.00 | 16.89 | 0.00 | 16.89 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 462.83 | 19.01 | 462.83 | 19.01 | 0.00 | 19.01 | 0.00 | 19.01 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 303.67 | 12.55 | 303.67 | 12.55 | 0.00 | 12.55 | 0.00 | 12.55 |
February | 112.00 | 13.91 | 112.00 | 13.91 | 0.00 | 13.91 | 0.00 | 13.91 |
March | 30.50 | 14.07 | 30.50 | 14.07 | 0.00 | 14.07 | 0.00 | 14.07 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 254.33 | 13.41 | 254.33 | 13.41 | 0.00 | 13.41 | 0.00 | 13.41 |
Annual Sum or Average | 700.50 | 13.15 | 700.50 | 13.15 | 0.00 | 13.15 | 0.00 | 13.15 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 303.67 | 14.07 | 303.67 | 14.07 | 0.00 | 14.07 | 0.00 | 14.07 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 315.00 | 13.77 | 315.00 | 13.77 | 0.00 | 13.77 | 0.00 | 13.77 |
February | 117.83 | 15.69 | 117.83 | 15.69 | 0.00 | 15.69 | 0.00 | 15.69 |
March | 29.17 | 16.27 | 29.17 | 16.27 | 0.00 | 16.27 | 0.00 | 16.27 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 257.00 | 14.62 | 257.00 | 14.62 | 0.00 | 14.62 | 0.00 | 14.62 |
Annual Sum or Average | 719.00 | 14.49 | 719.00 | 14.49 | 0.00 | 14.49 | 0.00 | 14.49 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 315.00 | 16.27 | 315.00 | 16.27 | 0.00 | 16.27 | 0.00 | 16.27 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 428.50 | 15.58 | 428.50 | 15.58 | 0.00 | 15.58 | 0.00 | 15.58 |
February | 171.50 | 17.81 | 171.50 | 17.81 | 0.00 | 17.81 | 0.00 | 17.81 |
March | 33.00 | 18.02 | 33.00 | 18.02 | 0.00 | 18.02 | 0.00 | 18.02 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 335.00 | 16.35 | 335.00 | 16.35 | 0.00 | 16.35 | 0.00 | 16.35 |
Annual Sum or Average | 968.00 | 16.32 | 968.00 | 16.32 | 0.00 | 16.32 | 0.00 | 16.32 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 428.50 | 18.02 | 428.50 | 18.02 | 0.00 | 18.02 | 0.00 | 18.02 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 457.83 | 15.80 | 457.83 | 15.80 | 0.00 | 15.80 | 0.00 | 15.80 |
February | 205.67 | 18.17 | 205.67 | 18.17 | 0.00 | 18.17 | 0.00 | 18.17 |
March | 40.50 | 18.55 | 40.50 | 18.55 | 0.00 | 18.55 | 0.00 | 18.55 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 373.67 | 16.68 | 373.67 | 16.68 | 0.00 | 16.68 | 0.00 | 16.68 |
Annual Sum or Average | 1077.67 | 16.66 | 1077.67 | 16.66 | 0.00 | 16.66 | 0.00 | 16.66 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 457.83 | 18.55 | 457.83 | 18.55 | 0.00 | 18.55 | 0.00 | 18.55 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 168.17 | 3.13 | 168.17 | 3.13 | 0.00 | 3.13 | 0.00 | 3.13 |
February | 64.83 | 4.93 | 64.83 | 4.93 | 0.00 | 4.93 | 0.00 | 4.93 |
March | 21.00 | 5.94 | 21.00 | 5.94 | 0.00 | 5.94 | 0.00 | 5.94 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 135.83 | 4.53 | 135.83 | 4.53 | 0.00 | 4.53 | 0.00 | 4.53 |
Annual Sum or Average | 389.83 | 4.07 | 389.83 | 4.07 | 0.00 | 4.07 | 0.00 | 4.07 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 168.17 | 5.94 | 168.17 | 5.94 | 0.00 | 5.94 | 0.00 | 5.94 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 209.83 | 9.58 | 209.83 | 9.58 | 0.00 | 9.58 | 0.00 | 9.58 |
February | 78.67 | 11.32 | 78.67 | 11.32 | 0.00 | 11.32 | 0.00 | 11.32 |
March | 23.67 | 12.44 | 23.67 | 12.44 | 0.00 | 12.44 | 0.00 | 12.44 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 183.83 | 11.20 | 183.83 | 11.20 | 0.00 | 11.20 | 0.00 | 11.20 |
Annual Sum or Average | 496.00 | 10.59 | 496.00 | 10.59 | 0.00 | 10.59 | 0.00 | 10.59 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 209.83 | 12.44 | 209.83 | 12.44 | 0.00 | 12.44 | 0.00 | 12.44 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 272.83 | 13.00 | 272.83 | 13.00 | 0.00 | 13.00 | 0.00 | 13.00 |
February | 100.83 | 14.89 | 100.83 | 14.89 | 0.00 | 14.89 | 0.00 | 14.89 |
March | 23.67 | 14.85 | 23.67 | 14.85 | 0.00 | 14.85 | 0.00 | 14.85 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 223.67 | 13.93 | 223.67 | 13.93 | 0.00 | 13.93 | 0.00 | 13.93 |
Annual Sum or Average | 621.00 | 13.71 | 621.00 | 13.71 | 0.00 | 13.71 | 0.00 | 13.71 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 272.83 | 14.89 | 272.83 | 14.89 | 0.00 | 14.89 | 0.00 | 14.89 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 6.67 | 20.37 | 6.67 | 20.37 | 0.00 | 20.37 | 0.00 | 20.37 |
February | 0.33 | 20.52 | 0.33 | 20.52 | 0.00 | 20.52 | 0.00 | 20.52 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.69 | 0.17 | 21.69 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.80 | 0.50 | 21.80 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.70 | 0.17 | 21.70 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1.50 | 20.42 | 1.50 | 20.42 | 0.00 | 20.42 | 0.00 | 20.42 |
Annual Sum or Average | 8.50 | 20.39 | 8.50 | 20.39 | 0.83 | 20.45 | 0.83 | 20.51 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 6.67 | 20.52 | 6.67 | 20.52 | 0.50 | 21.80 | 0.50 | 21.80 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 24.50 | 20.16 | 24.50 | 20.16 | 0.00 | 20.16 | 0.00 | 20.16 |
February | 0.83 | 20.40 | 0.83 | 20.40 | 0.00 | 20.40 | 0.00 | 20.40 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.82 | 0.67 | 21.82 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 3.67 | 20.28 | 3.67 | 20.28 | 0.00 | 20.28 | 0.00 | 20.28 |
Annual Sum or Average | 29.00 | 20.18 | 29.00 | 20.18 | 0.67 | 20.20 | 0.67 | 20.22 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 24.50 | 20.40 | 24.50 | 20.40 | 0.67 | 21.82 | 0.67 | 21.82 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 44.67 | 20.07 | 44.67 | 20.07 | 0.00 | 20.07 | 0.00 | 20.07 |
February | 3.83 | 20.25 | 3.83 | 20.25 | 0.00 | 20.25 | 0.00 | 20.25 |
March | 0.50 | 20.52 | 0.50 | 20.52 | 0.00 | 20.52 | 0.00 | 20.52 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.67 | 0.17 | 21.67 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 21.71 | 1.83 | 21.71 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.68 | 0.50 | 21.68 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.17 | 20.42 | 0.17 | 20.42 | 0.00 | 20.42 | 0.00 | 20.42 |
December | 14.83 | 20.31 | 14.83 | 20.31 | 0.00 | 20.31 | 0.00 | 20.31 |
Annual Sum or Average | 64.00 | 20.14 | 64.00 | 20.14 | 2.50 | 20.17 | 2.50 | 20.20 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 44.67 | 20.52 | 44.67 | 20.52 | 1.83 | 21.71 | 1.83 | 21.71 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 14.17 | 20.28 | 14.17 | 20.28 | 0.00 | 20.28 | 0.00 | 20.28 |
February | 0.17 | 20.55 | 0.17 | 20.55 | 0.00 | 20.55 | 0.00 | 20.55 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.80 | 0.33 | 21.80 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1.00 | 20.46 | 1.00 | 20.46 | 0.00 | 20.46 | 0.00 | 20.46 |
Annual Sum or Average | 15.33 | 20.30 | 15.33 | 20.30 | 0.33 | 20.31 | 0.33 | 20.33 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 14.17 | 20.55 | 14.17 | 20.55 | 0.33 | 21.80 | 0.33 | 21.80 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 34.00 | 20.03 | 34.00 | 20.03 | 0.00 | 20.03 | 0.00 | 20.03 |
February | 0.33 | 20.44 | 0.33 | 20.44 | 0.00 | 20.44 | 0.00 | 20.44 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.87 | 0.33 | 21.87 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 8.00 | 20.44 | 8.00 | 20.44 | 0.00 | 20.44 | 0.00 | 20.44 |
Annual Sum or Average | 42.33 | 20.11 | 42.33 | 20.11 | 0.33 | 20.11 | 0.33 | 20.12 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 34.00 | 20.44 | 34.00 | 20.44 | 0.33 | 21.87 | 0.33 | 21.87 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 384.50 | 17.44 | 384.50 | 17.44 | 0.00 | 17.44 | 0.00 | 17.44 |
February | 112.67 | 18.60 | 112.67 | 18.60 | 0.00 | 18.60 | 0.00 | 18.60 |
March | 23.83 | 18.79 | 23.83 | 18.79 | 0.00 | 18.79 | 0.00 | 18.79 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 319.67 | 18.09 | 319.67 | 18.09 | 0.00 | 18.09 | 0.00 | 18.09 |
Annual Sum or Average | 840.67 | 17.88 | 840.67 | 17.88 | 0.00 | 17.88 | 0.00 | 17.88 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 384.50 | 18.79 | 384.50 | 18.79 | 0.00 | 18.79 | 0.00 | 18.79 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.33 | 20.33 | 1.33 | 20.33 | 0.00 | 20.33 | 0.00 | 20.33 |
February | 0.17 | 20.55 | 0.17 | 20.55 | 0.00 | 20.55 | 0.00 | 20.55 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.75 | 1.00 | 21.75 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 21.90 | 1.17 | 21.90 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.70 | 0.50 | 21.70 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.71 | 1.00 | 21.71 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.84 | 0.33 | 21.84 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1.33 | 20.48 | 1.33 | 20.48 | 0.00 | 20.48 | 0.00 | 20.48 |
Annual Sum or Average | 2.83 | 20.41 | 2.83 | 20.41 | 4.00 | 20.98 | 4.00 | 21.22 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.33 | 20.55 | 1.33 | 20.55 | 1.17 | 21.90 | 1.17 | 21.90 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 7.17 | 20.28 | 7.17 | 20.28 | 0.00 | 20.28 | 0.00 | 20.28 |
February | 1.00 | 20.45 | 1.00 | 20.45 | 0.00 | 20.45 | 0.00 | 20.45 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.70 | 0.67 | 21.70 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 21.88 | 1.67 | 21.88 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.72 | 0.33 | 21.72 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 2.83 | 20.31 | 2.83 | 20.31 | 0.00 | 20.31 | 0.00 | 20.31 |
Annual Sum or Average | 11.00 | 20.30 | 11.00 | 20.30 | 2.67 | 20.47 | 2.67 | 20.60 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 7.17 | 20.45 | 7.17 | 20.45 | 1.67 | 21.88 | 1.67 | 21.88 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 20.54 | 0.17 | 20.54 | 0.00 | 20.54 | 0.00 | 20.54 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.70 | 0.17 | 21.70 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.73 | 0.17 | 21.73 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.83 | 0.83 | 21.83 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.85 | 0.83 | 21.85 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.17 | 20.54 | 0.17 | 20.54 | 2.00 | 21.64 | 2.00 | 21.72 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 20.54 | 0.17 | 20.54 | 0.83 | 21.85 | 0.83 | 21.85 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 207.83 | 11.03 | 207.83 | 11.03 | 0.00 | 11.03 | 0.00 | 11.03 |
February | 75.83 | 13.00 | 75.83 | 13.00 | 0.00 | 13.00 | 0.00 | 13.00 |
March | 20.83 | 13.71 | 20.83 | 13.71 | 0.00 | 13.71 | 0.00 | 13.71 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 179.17 | 12.63 | 179.17 | 12.63 | 0.00 | 12.63 | 0.00 | 12.63 |
Annual Sum or Average | 483.67 | 12.05 | 483.67 | 12.05 | 0.00 | 12.05 | 0.00 | 12.05 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 207.83 | 13.71 | 207.83 | 13.71 | 0.00 | 13.71 | 0.00 | 13.71 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 201.67 | 10.54 | 201.67 | 10.54 | 0.00 | 10.54 | 0.00 | 10.54 |
February | 75.00 | 12.69 | 75.00 | 12.69 | 0.00 | 12.69 | 0.00 | 12.69 |
March | 20.83 | 13.48 | 20.83 | 13.48 | 0.00 | 13.48 | 0.00 | 13.48 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 175.67 | 12.29 | 175.67 | 12.29 | 0.00 | 12.29 | 0.00 | 12.29 |
Annual Sum or Average | 473.17 | 11.66 | 473.17 | 11.66 | 0.00 | 11.66 | 0.00 | 11.66 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 201.67 | 13.48 | 201.67 | 13.48 | 0.00 | 13.48 | 0.00 | 13.48 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 173.00 | 5.32 | 173.00 | 5.32 | 0.00 | 5.32 | 0.00 | 5.32 |
February | 63.83 | 6.98 | 63.83 | 6.98 | 0.00 | 6.98 | 0.00 | 6.98 |
March | 20.83 | 8.08 | 20.83 | 8.08 | 0.00 | 8.08 | 0.00 | 8.08 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 139.67 | 6.67 | 139.67 | 6.67 | 0.00 | 6.67 | 0.00 | 6.67 |
Annual Sum or Average | 397.33 | 6.20 | 397.33 | 6.20 | 0.00 | 6.20 | 0.00 | 6.20 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 173.00 | 8.08 | 173.00 | 8.08 | 0.00 | 8.08 | 0.00 | 8.08 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 384.00 | 15.33 | 384.00 | 15.33 | 0.00 | 15.33 | 0.00 | 15.33 |
February | 144.17 | 17.26 | 144.17 | 17.26 | 0.00 | 17.26 | 0.00 | 17.26 |
March | 32.33 | 17.55 | 32.33 | 17.55 | 0.00 | 17.55 | 0.00 | 17.55 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 311.33 | 16.11 | 311.33 | 16.11 | 0.00 | 16.11 | 0.00 | 16.11 |
Annual Sum or Average | 871.83 | 16.01 | 871.83 | 16.01 | 0.00 | 16.01 | 0.00 | 16.01 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 384.00 | 17.55 | 384.00 | 17.55 | 0.00 | 17.55 | 0.00 | 17.55 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 17.90 | 641.17 | 17.67 | 641.17 | 17.58 |
February | 672.00 | 20.15 | 492.00 | 20.00 | 492.00 | 19.95 |
March | 744.00 | 20.80 | 442.33 | 20.75 | 442.33 | 20.72 |
April | 720.00 | 20.98 | 259.67 | 20.97 | 259.67 | 20.97 |
May | 744.00 | 20.99 | 40.00 | 20.98 | 40.00 | 20.98 |
June | 720.00 | 21.00 | 0.00 | 21.00 | 0.00 | 21.00 |
July | 744.00 | 21.03 | 0.00 | 21.03 | 0.00 | 21.03 |
August | 744.00 | 21.09 | 0.00 | 21.09 | 0.00 | 21.09 |
September | 720.00 | 21.16 | 0.00 | 21.16 | 0.00 | 21.16 |
October | 744.00 | 21.20 | 0.00 | 21.20 | 0.00 | 21.20 |
November | 720.00 | 21.19 | 14.50 | 21.18 | 14.50 | 21.18 |
December | 744.00 | 19.13 | 506.67 | 18.75 | 506.67 | 18.59 |
Annual Sum or Average | 8760.00 | 20.55 | 2396.33 | 20.24 | 2396.33 | 20.05 |
Minimum of Months | 672.00 | 17.90 | 0.00 | 17.67 | 0.00 | 17.58 |
Maximum of Months | 744.00 | 21.20 | 641.17 | 21.20 | 641.17 | 21.20 |
Report: ComfortReportSimple55Monthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 17.53 | 701.83 | 17.42 | 701.83 | 17.39 |
February | 669.50 | 19.83 | 509.00 | 19.65 | 509.00 | 19.58 |
March | 743.50 | 20.76 | 478.17 | 20.68 | 478.17 | 20.64 |
April | 711.17 | 21.06 | 223.33 | 21.05 | 223.33 | 21.04 |
May | 735.33 | 21.05 | 20.33 | 21.05 | 20.33 | 21.04 |
June | 714.50 | 21.03 | 1.33 | 21.04 | 0.00 | 21.04 |
July | 722.67 | 21.04 | 6.50 | 21.05 | 0.00 | 21.05 |
August | 704.50 | 21.04 | 18.33 | 21.08 | 0.00 | 21.08 |
September | 686.67 | 21.05 | 5.83 | 21.06 | 0.00 | 21.06 |
October | 713.00 | 21.03 | 191.17 | 21.07 | 173.33 | 21.06 |
November | 720.00 | 21.03 | 488.67 | 21.02 | 488.67 | 21.01 |
December | 744.00 | 18.38 | 717.00 | 18.33 | 717.00 | 18.31 |
Annual Sum or Average | 8608.83 | 20.39 | 3361.50 | 20.10 | 3311.67 | 19.93 |
Minimum of Months | 669.50 | 17.53 | 1.33 | 17.42 | 0.00 | 17.39 |
Maximum of Months | 744.00 | 21.06 | 717.00 | 21.08 | 717.00 | 21.08 |
Report: ComfortReportSimple55Monthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 17.92 | 655.67 | 17.72 | 655.67 | 17.65 |
February | 672.00 | 20.06 | 441.50 | 19.87 | 441.50 | 19.78 |
March | 744.00 | 20.81 | 290.33 | 20.73 | 290.33 | 20.68 |
April | 720.00 | 21.03 | 23.50 | 21.03 | 23.50 | 21.03 |
May | 744.00 | 21.08 | 0.00 | 21.08 | 0.00 | 21.08 |
June | 720.00 | 21.10 | 0.00 | 21.10 | 0.00 | 21.10 |
July | 744.00 | 21.12 | 0.00 | 21.12 | 0.00 | 21.12 |
August | 744.00 | 21.11 | 0.00 | 21.11 | 0.00 | 21.11 |
September | 720.00 | 21.06 | 0.00 | 21.06 | 0.00 | 21.06 |
October | 744.00 | 21.02 | 2.50 | 21.02 | 2.50 | 21.02 |
November | 720.00 | 21.00 | 149.50 | 21.00 | 149.50 | 21.00 |
December | 744.00 | 18.78 | 626.50 | 18.58 | 626.50 | 18.51 |
Annual Sum or Average | 8760.00 | 20.51 | 2189.50 | 20.17 | 2189.50 | 19.95 |
Minimum of Months | 672.00 | 17.92 | 0.00 | 17.72 | 0.00 | 17.65 |
Maximum of Months | 744.00 | 21.12 | 655.67 | 21.12 | 655.67 | 21.12 |
Report: ComfortReportSimple55Monthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 17.86 | 732.83 | 17.83 | 732.83 | 17.83 |
February | 672.00 | 20.15 | 623.83 | 20.12 | 623.83 | 20.11 |
March | 744.00 | 20.86 | 520.17 | 20.83 | 520.17 | 20.82 |
April | 720.00 | 21.00 | 227.33 | 21.00 | 227.33 | 21.00 |
May | 744.00 | 21.02 | 24.67 | 21.02 | 24.67 | 21.02 |
June | 720.00 | 21.04 | 0.00 | 21.04 | 0.00 | 21.04 |
July | 744.00 | 21.05 | 0.00 | 21.05 | 0.00 | 21.05 |
August | 744.00 | 21.04 | 0.00 | 21.04 | 0.00 | 21.04 |
September | 720.00 | 21.01 | 0.00 | 21.01 | 0.00 | 21.01 |
October | 744.00 | 21.00 | 32.67 | 21.00 | 32.67 | 21.00 |
November | 720.00 | 21.00 | 429.83 | 21.00 | 429.83 | 21.00 |
December | 744.00 | 18.88 | 709.83 | 18.83 | 709.83 | 18.81 |
Annual Sum or Average | 8760.00 | 20.49 | 3301.17 | 20.25 | 3301.17 | 20.11 |
Minimum of Months | 672.00 | 17.86 | 0.00 | 17.83 | 0.00 | 17.83 |
Maximum of Months | 744.00 | 21.05 | 732.83 | 21.05 | 732.83 | 21.05 |
Report: ComfortReportSimple55Monthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 17.79 | 744.00 | 17.79 | 744.00 | 17.79 |
February | 672.00 | 20.11 | 668.17 | 20.10 | 668.17 | 20.10 |
March | 744.00 | 20.86 | 630.17 | 20.85 | 630.17 | 20.84 |
April | 720.00 | 21.00 | 385.00 | 21.00 | 385.00 | 21.00 |
May | 744.00 | 21.00 | 45.00 | 21.00 | 45.00 | 21.00 |
June | 720.00 | 21.01 | 0.00 | 21.01 | 0.00 | 21.01 |
July | 744.00 | 21.01 | 0.00 | 21.01 | 0.00 | 21.01 |
August | 744.00 | 21.00 | 0.00 | 21.00 | 0.00 | 21.00 |
September | 720.00 | 21.00 | 0.00 | 21.00 | 0.00 | 21.00 |
October | 744.00 | 21.00 | 114.83 | 21.00 | 114.83 | 21.00 |
November | 720.00 | 21.00 | 559.33 | 21.00 | 559.33 | 21.00 |
December | 744.00 | 18.81 | 731.83 | 18.79 | 731.83 | 18.79 |
Annual Sum or Average | 8760.00 | 20.46 | 3878.33 | 20.25 | 3878.33 | 20.14 |
Minimum of Months | 672.00 | 17.79 | 0.00 | 17.79 | 0.00 | 17.79 |
Maximum of Months | 744.00 | 21.01 | 744.00 | 21.01 | 744.00 | 21.01 |
Report: ComfortReportSimple55Monthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 654.67 | 16.34 | 281.33 | 14.58 | 228.17 | 13.22 |
February | 563.33 | 19.30 | 182.33 | 18.59 | 115.00 | 17.81 |
March | 602.33 | 20.79 | 158.83 | 20.82 | 89.50 | 20.69 |
April | 529.33 | 21.39 | 143.00 | 21.74 | 77.33 | 21.93 |
May | 400.67 | 21.60 | 238.67 | 21.84 | 96.67 | 22.05 |
June | 228.50 | 22.08 | 363.33 | 21.89 | 104.83 | 22.11 |
July | 175.00 | 22.39 | 483.17 | 21.79 | 108.33 | 22.00 |
August | 191.33 | 22.38 | 429.33 | 21.91 | 111.17 | 22.13 |
September | 348.50 | 21.72 | 264.67 | 21.89 | 103.33 | 22.12 |
October | 509.00 | 21.47 | 176.33 | 21.80 | 91.33 | 22.02 |
November | 560.17 | 21.34 | 145.67 | 21.70 | 69.33 | 21.88 |
December | 642.00 | 17.47 | 272.67 | 16.17 | 208.67 | 15.05 |
Annual Sum or Average | 5404.83 | 20.16 | 3139.33 | 20.05 | 1403.67 | 19.73 |
Minimum of Months | 175.00 | 16.34 | 143.00 | 14.58 | 69.33 | 13.22 |
Maximum of Months | 654.67 | 22.39 | 483.17 | 21.91 | 228.17 | 22.13 |
Report: ComfortReportSimple55Monthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 17.77 | 616.83 | 17.47 | 616.83 | 17.36 |
February | 665.33 | 19.88 | 379.17 | 19.56 | 379.17 | 19.41 |
March | 737.00 | 20.76 | 214.83 | 20.60 | 214.83 | 20.50 |
April | 708.33 | 21.04 | 16.00 | 21.04 | 15.50 | 21.04 |
May | 735.00 | 21.04 | 0.00 | 21.04 | 0.00 | 21.04 |
June | 715.33 | 21.03 | 0.00 | 21.03 | 0.00 | 21.03 |
July | 722.17 | 21.03 | 6.17 | 21.04 | 0.00 | 21.04 |
August | 699.83 | 21.03 | 19.00 | 21.06 | 0.00 | 21.06 |
September | 681.00 | 21.03 | 9.33 | 21.05 | 0.00 | 21.05 |
October | 708.17 | 21.02 | 31.83 | 21.07 | 12.00 | 21.07 |
November | 718.50 | 21.02 | 200.17 | 21.02 | 200.17 | 21.02 |
December | 744.00 | 18.57 | 620.00 | 18.35 | 620.00 | 18.27 |
Annual Sum or Average | 8578.67 | 20.42 | 2113.33 | 20.06 | 2058.50 | 19.81 |
Minimum of Months | 665.33 | 17.77 | 0.00 | 17.47 | 0.00 | 17.36 |
Maximum of Months | 744.00 | 21.04 | 620.00 | 21.07 | 620.00 | 21.07 |
Report: ComfortReportSimple55Monthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 18.06 | 571.33 | 17.67 | 571.33 | 17.52 |
February | 672.00 | 20.08 | 342.33 | 19.78 | 342.33 | 19.63 |
March | 744.00 | 20.82 | 131.50 | 20.68 | 131.50 | 20.57 |
April | 720.00 | 21.05 | 0.00 | 21.05 | 0.00 | 21.05 |
May | 744.00 | 21.13 | 0.00 | 21.13 | 0.00 | 21.13 |
June | 720.00 | 21.17 | 0.00 | 21.17 | 0.00 | 21.17 |
July | 744.00 | 21.19 | 0.00 | 21.19 | 0.00 | 21.19 |
August | 744.00 | 21.18 | 0.00 | 21.18 | 0.00 | 21.18 |
September | 720.00 | 21.11 | 0.00 | 21.11 | 0.00 | 21.11 |
October | 744.00 | 21.05 | 0.00 | 21.05 | 0.00 | 21.05 |
November | 720.00 | 21.02 | 61.00 | 21.01 | 61.00 | 21.01 |
December | 744.00 | 18.87 | 510.50 | 18.47 | 510.50 | 18.30 |
Annual Sum or Average | 8760.00 | 20.56 | 1616.67 | 20.19 | 1616.67 | 19.92 |
Minimum of Months | 672.00 | 18.06 | 0.00 | 17.67 | 0.00 | 17.52 |
Maximum of Months | 744.00 | 21.19 | 571.33 | 21.19 | 571.33 | 21.19 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.51 | 739.17 | 20.51 | 739.17 | 20.51 |
February | 672.00 | 20.80 | 577.00 | 20.74 | 577.00 | 20.72 |
March | 744.00 | 20.95 | 518.17 | 20.85 | 518.17 | 20.81 |
April | 708.83 | 21.29 | 184.50 | 21.20 | 182.17 | 21.14 |
May | 689.00 | 21.50 | 20.00 | 21.54 | 5.33 | 21.53 |
June | 633.50 | 21.43 | 27.83 | 21.51 | 0.33 | 21.52 |
July | 606.33 | 21.34 | 56.67 | 21.51 | 0.17 | 21.51 |
August | 635.00 | 21.36 | 45.17 | 21.49 | 0.00 | 21.49 |
September | 675.17 | 21.41 | 7.33 | 21.43 | 0.00 | 21.43 |
October | 731.00 | 21.11 | 195.33 | 21.02 | 193.50 | 20.96 |
November | 720.00 | 20.80 | 574.67 | 20.75 | 574.67 | 20.73 |
December | 744.00 | 20.50 | 743.83 | 20.50 | 743.83 | 20.50 |
Annual Sum or Average | 8302.83 | 21.07 | 3689.67 | 20.96 | 3534.33 | 20.89 |
Minimum of Months | 606.33 | 20.50 | 7.33 | 20.50 | 0.00 | 20.50 |
Maximum of Months | 744.00 | 21.50 | 743.83 | 21.54 | 743.83 | 21.53 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.43 | 744.00 | 20.43 | 744.00 | 20.43 |
February | 672.00 | 20.56 | 651.50 | 20.55 | 651.50 | 20.54 |
March | 744.00 | 20.68 | 632.17 | 20.63 | 632.17 | 20.62 |
April | 717.67 | 21.11 | 271.50 | 21.01 | 270.33 | 20.96 |
May | 710.17 | 21.50 | 16.33 | 21.51 | 9.50 | 21.50 |
June | 655.50 | 21.48 | 17.00 | 21.53 | 0.17 | 21.53 |
July | 636.50 | 21.42 | 36.83 | 21.52 | 0.17 | 21.52 |
August | 675.67 | 21.44 | 20.83 | 21.50 | 0.00 | 21.50 |
September | 708.83 | 21.40 | 2.50 | 21.40 | 1.00 | 21.40 |
October | 744.00 | 20.98 | 270.50 | 20.88 | 270.50 | 20.83 |
November | 720.00 | 20.61 | 650.33 | 20.59 | 650.33 | 20.58 |
December | 744.00 | 20.47 | 744.00 | 20.47 | 744.00 | 20.47 |
Annual Sum or Average | 8472.33 | 20.99 | 4057.50 | 20.86 | 3973.67 | 20.79 |
Minimum of Months | 636.50 | 20.43 | 2.50 | 20.43 | 0.00 | 20.43 |
Maximum of Months | 744.00 | 21.50 | 744.00 | 21.53 | 744.00 | 21.53 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.53 | 728.33 | 20.53 | 728.33 | 20.52 |
February | 672.00 | 20.73 | 622.67 | 20.71 | 622.67 | 20.71 |
March | 744.00 | 20.89 | 512.17 | 20.84 | 512.17 | 20.82 |
April | 720.00 | 21.21 | 92.00 | 21.18 | 92.00 | 21.16 |
May | 744.00 | 21.50 | 0.00 | 21.50 | 0.00 | 21.50 |
June | 720.00 | 21.58 | 0.33 | 21.58 | 0.33 | 21.58 |
July | 744.00 | 21.61 | 0.33 | 21.61 | 0.33 | 21.61 |
August | 744.00 | 21.52 | 0.00 | 21.52 | 0.00 | 21.52 |
September | 720.00 | 21.41 | 0.00 | 21.41 | 0.00 | 21.41 |
October | 744.00 | 21.19 | 16.33 | 21.19 | 16.33 | 21.18 |
November | 720.00 | 20.92 | 430.17 | 20.88 | 430.17 | 20.85 |
December | 744.00 | 20.60 | 713.50 | 20.58 | 713.50 | 20.58 |
Annual Sum or Average | 8760.00 | 21.14 | 3115.83 | 21.02 | 3115.83 | 20.94 |
Minimum of Months | 672.00 | 20.53 | 0.00 | 20.53 | 0.00 | 20.52 |
Maximum of Months | 744.00 | 21.61 | 728.33 | 21.61 | 728.33 | 21.61 |
Report: ComfortReportSimple55Monthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.49 | 740.17 | 20.49 | 740.17 | 20.49 |
February | 672.00 | 20.80 | 577.33 | 20.74 | 577.33 | 20.72 |
March | 744.00 | 21.04 | 494.33 | 20.92 | 494.33 | 20.87 |
April | 712.00 | 21.40 | 161.17 | 21.31 | 161.17 | 21.24 |
May | 690.33 | 21.55 | 4.83 | 21.56 | 2.67 | 21.55 |
June | 597.33 | 21.37 | 27.17 | 21.46 | 0.17 | 21.46 |
July | 584.50 | 21.29 | 54.00 | 21.46 | 0.17 | 21.46 |
August | 622.00 | 21.35 | 27.17 | 21.43 | 0.00 | 21.43 |
September | 663.83 | 21.40 | 4.50 | 21.41 | 1.33 | 21.41 |
October | 731.67 | 21.13 | 190.33 | 21.04 | 190.33 | 20.98 |
November | 720.00 | 20.79 | 569.33 | 20.74 | 569.33 | 20.72 |
December | 744.00 | 20.49 | 739.50 | 20.49 | 739.50 | 20.49 |
Annual Sum or Average | 8225.67 | 21.08 | 3589.83 | 20.96 | 3476.50 | 20.88 |
Minimum of Months | 584.50 | 20.49 | 4.50 | 20.49 | 0.00 | 20.49 |
Maximum of Months | 744.00 | 21.55 | 740.17 | 21.56 | 740.17 | 21.55 |
Report: ComfortReportSimple55Monthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.42 | 744.00 | 20.42 | 744.00 | 20.42 |
February | 672.00 | 20.54 | 658.67 | 20.54 | 658.67 | 20.54 |
March | 744.00 | 20.75 | 606.33 | 20.70 | 606.33 | 20.68 |
April | 719.83 | 21.29 | 236.83 | 21.19 | 236.83 | 21.13 |
May | 707.83 | 21.57 | 7.17 | 21.57 | 6.83 | 21.57 |
June | 623.83 | 21.45 | 8.00 | 21.47 | 0.17 | 21.47 |
July | 595.17 | 21.32 | 16.83 | 21.38 | 0.00 | 21.38 |
August | 653.67 | 21.43 | 3.50 | 21.44 | 0.00 | 21.44 |
September | 711.33 | 21.48 | 3.00 | 21.48 | 2.50 | 21.47 |
October | 744.00 | 21.01 | 268.17 | 20.92 | 268.17 | 20.86 |
November | 720.00 | 20.60 | 638.83 | 20.58 | 638.83 | 20.57 |
December | 744.00 | 20.46 | 744.00 | 20.46 | 744.00 | 20.46 |
Annual Sum or Average | 8379.67 | 21.01 | 3935.33 | 20.87 | 3906.33 | 20.79 |
Minimum of Months | 595.17 | 20.42 | 3.00 | 20.42 | 0.00 | 20.42 |
Maximum of Months | 744.00 | 21.57 | 744.00 | 21.57 | 744.00 | 21.57 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 19.14 | 744.00 | 19.14 | 744.00 | 19.14 |
February | 672.00 | 20.57 | 628.17 | 20.56 | 628.17 | 20.55 |
March | 744.00 | 20.93 | 515.50 | 20.91 | 515.50 | 20.91 |
April | 720.00 | 21.02 | 178.67 | 21.02 | 178.67 | 21.02 |
May | 744.00 | 21.14 | 14.00 | 21.13 | 14.00 | 21.13 |
June | 720.00 | 21.24 | 0.00 | 21.24 | 0.00 | 21.24 |
July | 744.00 | 21.43 | 0.00 | 21.43 | 0.00 | 21.43 |
August | 744.00 | 21.24 | 0.00 | 21.24 | 0.00 | 21.24 |
September | 720.00 | 21.08 | 0.00 | 21.08 | 0.00 | 21.08 |
October | 744.00 | 21.02 | 60.17 | 21.02 | 60.17 | 21.02 |
November | 720.00 | 21.00 | 478.67 | 21.00 | 478.67 | 21.00 |
December | 744.00 | 19.73 | 725.17 | 19.71 | 725.17 | 19.70 |
Annual Sum or Average | 8760.00 | 20.79 | 3344.33 | 20.63 | 3344.33 | 20.54 |
Minimum of Months | 672.00 | 19.14 | 0.00 | 19.14 | 0.00 | 19.14 |
Maximum of Months | 744.00 | 21.43 | 744.00 | 21.43 | 744.00 | 21.43 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.49 | 742.83 | 20.49 | 742.83 | 20.49 |
February | 672.00 | 20.71 | 611.67 | 20.67 | 611.67 | 20.65 |
March | 743.83 | 20.86 | 579.33 | 20.77 | 579.33 | 20.74 |
April | 702.17 | 21.20 | 294.50 | 21.09 | 291.67 | 21.03 |
May | 671.17 | 21.46 | 31.83 | 21.51 | 11.00 | 21.50 |
June | 604.00 | 21.38 | 50.83 | 21.53 | 2.17 | 21.53 |
July | 582.83 | 21.30 | 90.33 | 21.57 | 1.33 | 21.57 |
August | 615.33 | 21.32 | 71.17 | 21.52 | 1.17 | 21.52 |
September | 661.00 | 21.36 | 16.33 | 21.39 | 5.00 | 21.38 |
October | 728.17 | 21.02 | 303.83 | 20.91 | 301.00 | 20.85 |
November | 720.00 | 20.71 | 621.17 | 20.66 | 621.17 | 20.65 |
December | 744.00 | 20.48 | 744.00 | 20.48 | 744.00 | 20.48 |
Annual Sum or Average | 8188.50 | 21.00 | 4157.83 | 20.92 | 3912.33 | 20.84 |
Minimum of Months | 582.83 | 20.48 | 16.33 | 20.48 | 1.17 | 20.48 |
Maximum of Months | 744.00 | 21.46 | 744.00 | 21.57 | 744.00 | 21.57 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.45 | 744.00 | 20.45 | 744.00 | 20.45 |
February | 672.00 | 20.52 | 660.50 | 20.51 | 660.50 | 20.51 |
March | 744.00 | 20.63 | 665.17 | 20.59 | 665.17 | 20.57 |
April | 716.67 | 21.04 | 382.83 | 20.93 | 381.33 | 20.88 |
May | 694.83 | 21.47 | 29.83 | 21.50 | 16.00 | 21.49 |
June | 626.17 | 21.43 | 34.33 | 21.52 | 1.83 | 21.53 |
July | 606.83 | 21.35 | 60.67 | 21.53 | 1.17 | 21.53 |
August | 651.00 | 21.39 | 39.33 | 21.50 | 1.83 | 21.50 |
September | 700.33 | 21.37 | 11.33 | 21.38 | 6.67 | 21.37 |
October | 743.67 | 20.89 | 375.17 | 20.78 | 375.17 | 20.73 |
November | 720.00 | 20.54 | 673.50 | 20.53 | 673.50 | 20.52 |
December | 744.00 | 20.46 | 744.00 | 20.46 | 744.00 | 20.46 |
Annual Sum or Average | 8363.50 | 20.94 | 4420.67 | 20.83 | 4271.17 | 20.75 |
Minimum of Months | 606.83 | 20.45 | 11.33 | 20.45 | 1.17 | 20.45 |
Maximum of Months | 744.00 | 21.47 | 744.00 | 21.53 | 744.00 | 21.53 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 743.00 | 20.88 | 650.83 | 20.79 | 650.83 | 20.76 |
February | 656.33 | 21.14 | 459.17 | 21.01 | 459.17 | 20.96 |
March | 724.00 | 21.17 | 412.33 | 21.04 | 412.33 | 20.98 |
April | 680.00 | 21.34 | 141.33 | 21.26 | 138.33 | 21.21 |
May | 680.83 | 21.50 | 23.33 | 21.55 | 4.50 | 21.54 |
June | 621.33 | 21.40 | 31.50 | 21.49 | 1.83 | 21.49 |
July | 613.50 | 21.35 | 67.00 | 21.54 | 2.50 | 21.55 |
August | 629.67 | 21.36 | 69.00 | 21.55 | 0.50 | 21.56 |
September | 638.67 | 21.37 | 31.67 | 21.46 | 0.00 | 21.46 |
October | 701.00 | 21.18 | 162.33 | 21.17 | 138.50 | 21.12 |
November | 709.83 | 21.03 | 437.17 | 20.93 | 437.17 | 20.89 |
December | 744.00 | 20.78 | 680.33 | 20.71 | 680.33 | 20.69 |
Annual Sum or Average | 8142.17 | 21.20 | 3166.00 | 21.13 | 2926.00 | 21.05 |
Minimum of Months | 613.50 | 20.78 | 23.33 | 20.71 | 0.00 | 20.69 |
Maximum of Months | 744.00 | 21.50 | 680.33 | 21.55 | 680.33 | 21.56 |
Report: ComfortReportSimple55Monthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 18.29 | 477.83 | 17.65 | 477.83 | 17.37 |
February | 672.00 | 20.24 | 265.50 | 19.80 | 265.50 | 19.56 |
March | 744.00 | 21.09 | 88.50 | 20.89 | 88.50 | 20.74 |
April | 720.00 | 21.48 | 0.00 | 21.48 | 0.00 | 21.48 |
May | 718.00 | 21.70 | 5.00 | 21.71 | 0.00 | 21.71 |
June | 628.83 | 21.71 | 33.00 | 21.78 | 0.00 | 21.78 |
July | 630.33 | 21.72 | 37.67 | 21.80 | 0.00 | 21.80 |
August | 673.33 | 21.70 | 32.17 | 21.76 | 0.00 | 21.76 |
September | 708.83 | 21.64 | 4.33 | 21.65 | 0.00 | 21.65 |
October | 744.00 | 21.49 | 0.00 | 21.49 | 0.00 | 21.49 |
November | 720.00 | 21.34 | 4.50 | 21.33 | 4.50 | 21.33 |
December | 744.00 | 19.08 | 424.83 | 18.49 | 424.83 | 18.22 |
Annual Sum or Average | 8447.33 | 20.93 | 1373.33 | 20.52 | 1261.17 | 20.18 |
Minimum of Months | 628.83 | 18.29 | 0.00 | 17.65 | 0.00 | 17.37 |
Maximum of Months | 744.00 | 21.72 | 477.83 | 21.80 | 477.83 | 21.80 |
Report: ComfortReportSimple55Monthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 18.25 | 421.83 | 17.43 | 421.83 | 17.05 |
February | 672.00 | 20.24 | 202.00 | 19.70 | 202.00 | 19.36 |
March | 744.00 | 21.12 | 54.83 | 20.92 | 54.83 | 20.74 |
April | 719.17 | 21.55 | 0.00 | 21.55 | 0.00 | 21.55 |
May | 688.50 | 21.75 | 13.50 | 21.78 | 0.00 | 21.78 |
June | 559.33 | 21.72 | 71.33 | 21.87 | 0.00 | 21.87 |
July | 519.83 | 21.67 | 90.17 | 21.87 | 0.00 | 21.87 |
August | 596.67 | 21.68 | 61.17 | 21.81 | 0.00 | 21.81 |
September | 685.83 | 21.68 | 7.67 | 21.70 | 0.00 | 21.70 |
October | 743.83 | 21.55 | 0.00 | 21.55 | 0.00 | 21.55 |
November | 718.83 | 21.38 | 0.00 | 21.38 | 0.00 | 21.38 |
December | 744.00 | 19.06 | 346.00 | 18.27 | 346.00 | 17.86 |
Annual Sum or Average | 8136.00 | 20.92 | 1268.50 | 20.51 | 1024.67 | 20.13 |
Minimum of Months | 519.83 | 18.25 | 0.00 | 17.43 | 0.00 | 17.05 |
Maximum of Months | 744.00 | 21.75 | 421.83 | 21.87 | 421.83 | 21.87 |
Report: ComfortReportSimple55Monthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 447.00 | 15.25 | 465.83 | 15.77 | 239.83 | 14.62 |
February | 403.33 | 19.69 | 427.00 | 20.16 | 210.83 | 19.82 |
March | 488.33 | 21.93 | 508.83 | 22.29 | 289.17 | 22.34 |
April | 566.83 | 22.90 | 514.50 | 23.20 | 385.50 | 23.35 |
May | 621.67 | 23.20 | 565.67 | 23.41 | 478.67 | 23.53 |
June | 579.17 | 23.46 | 584.17 | 23.51 | 499.83 | 23.61 |
July | 564.33 | 23.64 | 620.33 | 23.58 | 521.83 | 23.66 |
August | 570.33 | 23.52 | 602.00 | 23.52 | 511.50 | 23.61 |
September | 583.67 | 23.16 | 550.33 | 23.33 | 452.67 | 23.46 |
October | 559.33 | 22.82 | 536.83 | 23.10 | 379.00 | 23.25 |
November | 444.17 | 22.45 | 491.17 | 22.82 | 245.83 | 22.98 |
December | 431.33 | 16.75 | 451.83 | 17.28 | 211.17 | 16.32 |
Annual Sum or Average | 6259.50 | 21.84 | 6318.50 | 22.06 | 4425.83 | 22.09 |
Minimum of Months | 403.33 | 15.25 | 427.00 | 15.77 | 210.83 | 14.62 |
Maximum of Months | 621.67 | 23.64 | 620.33 | 23.58 | 521.83 | 23.66 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 18.05 | 744.00 | 18.05 | 744.00 | 18.05 |
February | 672.00 | 20.17 | 628.33 | 20.14 | 628.33 | 20.13 |
March | 744.00 | 20.85 | 559.17 | 20.83 | 559.17 | 20.82 |
April | 720.00 | 21.01 | 228.33 | 21.01 | 228.33 | 21.01 |
May | 744.00 | 21.04 | 17.17 | 21.04 | 17.17 | 21.04 |
June | 720.00 | 21.09 | 0.00 | 21.09 | 0.00 | 21.09 |
July | 744.00 | 21.12 | 0.00 | 21.12 | 0.00 | 21.12 |
August | 744.00 | 21.08 | 0.00 | 21.08 | 0.00 | 21.08 |
September | 720.00 | 21.03 | 0.00 | 21.03 | 0.00 | 21.03 |
October | 744.00 | 21.01 | 116.50 | 21.01 | 116.50 | 21.01 |
November | 720.00 | 21.00 | 551.67 | 21.00 | 551.67 | 21.00 |
December | 744.00 | 18.92 | 737.33 | 18.91 | 737.33 | 18.91 |
Annual Sum or Average | 8760.00 | 20.53 | 3582.50 | 20.31 | 3582.50 | 20.19 |
Minimum of Months | 672.00 | 18.05 | 0.00 | 18.05 | 0.00 | 18.05 |
Maximum of Months | 744.00 | 21.12 | 744.00 | 21.12 | 744.00 | 21.12 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT PEOPLE
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 17.90362 | 11.10873 | -1.2887 | 39.55091 |
February | 672.00000 | 20.14501 | 13.07643 | -0.7706 | 19.75630 |
March | 744.00000 | 20.79977 | 17.22921 | -0.6030 | 13.17568 |
April | 720.00000 | 20.97934 | 22.67813 | -0.5310 | 10.98836 |
May | 744.00000 | 20.98721 | 37.17906 | -1.6450 | 58.76605 |
June | 720.00000 | 20.99930 | 52.87619 | -1.5397 | 53.06285 |
July | 744.00000 | 21.03089 | 59.74358 | -1.4697 | 49.26639 |
August | 744.00000 | 21.08963 | 58.76930 | -1.4357 | 47.45132 |
September | 720.00000 | 21.15521 | 45.84372 | -1.4790 | 49.82390 |
October | 744.00000 | 21.20232 | 31.92026 | -0.3735 | 8.00295 |
November | 720.00000 | 21.18824 | 21.42982 | -0.4409 | 9.17459 |
December | 744.00000 | 19.12531 | 12.49916 | -0.9887 | 29.54965 |
Annual Sum or Average | 8760.00000 | 20.54801 | 32.14494 | -1.0500 | 32.50224 |
Minimum of Months | 672.00000 | 17.90362 | 11.10873 | -1.6450 | 8.00295 |
Maximum of Months | 744.00000 | 21.20232 | 59.74358 | -0.3735 | 58.76605 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_1_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 17.52591 | 10.08970 | -1.4629 | 39.28667 |
February | 672.00000 | 19.84530 | 12.05053 | -0.8738 | 22.99236 |
March | 744.00000 | 20.76155 | 16.20118 | -0.6128 | 14.55945 |
April | 720.00000 | 21.07959 | 21.62518 | -0.4428 | 9.86076 |
May | 744.00000 | 21.05953 | 36.13073 | -1.4403 | 48.08565 |
June | 720.00000 | 21.04108 | 52.03050 | -1.3297 | 42.20793 |
July | 744.00000 | 21.07029 | 58.97218 | -1.2433 | 37.94499 |
August | 744.00000 | 21.10411 | 57.99124 | -1.2555 | 38.84292 |
September | 720.00000 | 21.11706 | 45.09047 | -1.3860 | 45.62501 |
October | 744.00000 | 21.11253 | 31.09398 | -0.4016 | 9.45822 |
November | 720.00000 | 21.02766 | 20.64937 | -0.5684 | 12.29601 |
December | 744.00000 | 18.37961 | 11.58570 | -1.2848 | 35.35255 |
Annual Sum or Average | 8760.00000 | 20.42479 | 31.24188 | -1.0274 | 29.78883 |
Minimum of Months | 672.00000 | 17.52591 | 10.08970 | -1.4629 | 9.45822 |
Maximum of Months | 744.00000 | 21.11706 | 58.97218 | -0.4016 | 48.08565 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_2_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 17.91608 | 11.09445 | -1.3031 | 37.13651 |
February | 672.00000 | 20.06082 | 13.26095 | -0.7882 | 20.69399 |
March | 744.00000 | 20.81334 | 17.48501 | -0.5675 | 12.61055 |
April | 720.00000 | 21.02927 | 22.93380 | -0.4572 | 9.48405 |
May | 744.00000 | 21.08320 | 37.30354 | -1.5001 | 50.96493 |
June | 720.00000 | 21.10477 | 53.01155 | -1.3930 | 45.24337 |
July | 744.00000 | 21.12302 | 59.94755 | -1.3349 | 42.15915 |
August | 744.00000 | 21.10506 | 59.17026 | -1.3531 | 43.10650 |
September | 720.00000 | 21.05769 | 46.43639 | -1.4615 | 48.88447 |
October | 744.00000 | 21.02263 | 32.53573 | -0.4044 | 8.51007 |
November | 720.00000 | 21.00338 | 21.92489 | -0.4985 | 10.28918 |
December | 744.00000 | 18.77573 | 12.65017 | -1.0988 | 32.10032 |
Annual Sum or Average | 8760.00000 | 20.50566 | 32.42820 | -1.0159 | 30.19368 |
Minimum of Months | 672.00000 | 17.91608 | 11.09445 | -1.5001 | 8.51007 |
Maximum of Months | 744.00000 | 21.12302 | 59.94755 | -0.4044 | 50.96493 |
Report: OccupantComfortDataSummaryMonthly
For: LAUNDRY_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 17.05246 | 9.40247 | -0.9050 | 28.94275 |
February | 672.00000 | 19.77572 | 11.10529 | -0.2608 | 16.51784 |
March | 744.00000 | 21.00989 | 15.03207 | 0.06866 | 10.83958 |
April | 720.00000 | 21.42076 | 20.35787 | 0.22574 | 8.70944 |
May | 744.00000 | 21.40291 | 34.53624 | -0.5334 | 16.28839 |
June | 720.00000 | 21.39177 | 49.97185 | -0.4258 | 13.94599 |
July | 744.00000 | 21.36929 | 56.89316 | -0.3854 | 12.83443 |
August | 744.00000 | 21.40140 | 55.99789 | -0.3915 | 13.33566 |
September | 720.00000 | 21.41199 | 43.38300 | -0.4917 | 15.33333 |
October | 744.00000 | 21.43002 | 29.69801 | 0.28148 | 9.32400 |
November | 720.00000 | 21.43570 | 19.32367 | 0.19121 | 8.51475 |
December | 744.00000 | 18.13265 | 10.73885 | -0.6508 | 25.35504 |
Annual Sum or Average | 8760.00000 | 20.60078 | 29.81726 | -0.2748 | 15.01951 |
Minimum of Months | 672.00000 | 17.05246 | 9.40247 | -0.9050 | 8.51475 |
Maximum of Months | 744.00000 | 21.43570 | 56.89316 | 0.28148 | 28.94275 |
Report: OccupantComfortDataSummaryMonthly
For: CAFE_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 17.77149 | 11.91318 | -1.3110 | 34.54367 |
February | 672.00000 | 19.90733 | 14.29476 | -0.7549 | 19.92133 |
March | 744.00000 | 20.77236 | 18.62750 | -0.5029 | 12.07487 |
April | 720.00000 | 21.05897 | 24.10444 | -0.3452 | 8.08292 |
May | 744.00000 | 21.04256 | 38.58439 | -1.3228 | 41.90738 |
June | 720.00000 | 21.03228 | 54.38121 | -1.2121 | 36.21405 |
July | 744.00000 | 21.05025 | 61.30957 | -1.1337 | 32.49777 |
August | 744.00000 | 21.07596 | 60.41311 | -1.1439 | 33.22487 |
September | 720.00000 | 21.08600 | 47.55577 | -1.2678 | 39.43639 |
October | 744.00000 | 21.08981 | 33.58257 | -0.3039 | 7.79878 |
November | 720.00000 | 21.02435 | 23.09858 | -0.4599 | 9.86905 |
December | 744.00000 | 18.57390 | 13.56514 | -1.1438 | 31.05657 |
Annual Sum or Average | 8760.00000 | 20.45512 | 33.56798 | -0.9107 | 25.62217 |
Minimum of Months | 672.00000 | 17.77149 | 11.91318 | -1.3228 | 7.79878 |
Maximum of Months | 744.00000 | 21.08981 | 61.30957 | -0.3039 | 41.90738 |
Report: OccupantComfortDataSummaryMonthly
For: LOBBY_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 18.05694 | 12.11128 | -1.2394 | 34.87221 |
February | 672.00000 | 20.08403 | 14.50285 | -0.7374 | 19.26897 |
March | 744.00000 | 20.81787 | 18.80083 | -0.5201 | 11.64064 |
April | 720.00000 | 21.05202 | 24.24704 | -0.4044 | 8.54277 |
May | 744.00000 | 21.13126 | 38.53154 | -1.4203 | 46.71441 |
June | 720.00000 | 21.17217 | 54.10096 | -1.3048 | 40.67863 |
July | 744.00000 | 21.19374 | 60.97697 | -1.2446 | 37.56762 |
August | 744.00000 | 21.18402 | 60.20119 | -1.2596 | 38.33100 |
September | 720.00000 | 21.10966 | 47.61496 | -1.3779 | 44.45327 |
October | 744.00000 | 21.05477 | 33.80620 | -0.3512 | 7.71602 |
November | 720.00000 | 21.01535 | 23.24247 | -0.4543 | 9.42465 |
December | 744.00000 | 18.86679 | 13.76265 | -1.0471 | 30.27409 |
Annual Sum or Average | 8760.00000 | 20.55972 | 33.60590 | -0.9492 | 27.54276 |
Minimum of Months | 672.00000 | 18.05694 | 12.11128 | -1.4203 | 7.71602 |
Maximum of Months | 744.00000 | 21.19374 | 60.97697 | -0.3512 | 46.71441 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.51189 | 17.60878 | -0.8694 | 21.49418 |
February | 672.00000 | 20.79896 | 19.54612 | -0.7172 | 16.76850 |
March | 744.00000 | 20.95312 | 23.69979 | -0.6002 | 13.66381 |
April | 720.00000 | 21.31899 | 28.48493 | -0.3999 | 9.51876 |
May | 744.00000 | 21.63660 | 39.90880 | -1.2665 | 40.07938 |
June | 720.00000 | 21.65773 | 51.74216 | -1.1588 | 34.89486 |
July | 744.00000 | 21.69985 | 54.81897 | -1.0825 | 31.56642 |
August | 744.00000 | 21.64726 | 55.94924 | -1.1395 | 34.07336 |
September | 720.00000 | 21.53072 | 49.19209 | -1.3038 | 41.76521 |
October | 744.00000 | 21.15022 | 38.31746 | -0.4161 | 9.65273 |
November | 720.00000 | 20.80367 | 28.35991 | -0.6464 | 14.49205 |
December | 744.00000 | 20.49685 | 19.21929 | -0.8633 | 21.25753 |
Annual Sum or Average | 8760.00000 | 21.18541 | 35.65988 | -0.8732 | 24.15083 |
Minimum of Months | 672.00000 | 20.49685 | 17.60878 | -1.3038 | 9.51876 |
Maximum of Months | 744.00000 | 21.69985 | 55.94924 | -0.3999 | 41.76521 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.43352 | 17.68685 | -0.9241 | 23.69606 |
February | 672.00000 | 20.55771 | 19.80813 | -0.8144 | 19.62775 |
March | 744.00000 | 20.68321 | 24.01868 | -0.6983 | 16.07691 |
April | 720.00000 | 21.11713 | 28.74707 | -0.4761 | 10.63764 |
May | 744.00000 | 21.58071 | 40.11681 | -1.3094 | 41.95119 |
June | 720.00000 | 21.64242 | 51.91630 | -1.1771 | 35.53965 |
July | 744.00000 | 21.68974 | 55.32535 | -1.1040 | 32.29516 |
August | 744.00000 | 21.61603 | 56.92084 | -1.1767 | 35.47756 |
September | 720.00000 | 21.43093 | 49.72762 | -1.3742 | 44.88216 |
October | 744.00000 | 20.98375 | 38.67226 | -0.4819 | 10.46660 |
November | 720.00000 | 20.60970 | 28.62801 | -0.7135 | 16.29693 |
December | 744.00000 | 20.46539 | 19.27209 | -0.8991 | 22.70014 |
Annual Sum or Average | 8760.00000 | 21.07026 | 35.99342 | -0.9299 | 25.84340 |
Minimum of Months | 672.00000 | 20.43352 | 17.68685 | -1.3742 | 10.46660 |
Maximum of Months | 744.00000 | 21.68974 | 56.92084 | -0.4761 | 44.88216 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT19_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 0.00000 | ||||
Minimum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_4_MULT19_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.53253 | 16.28507 | -0.7763 | 18.36239 |
February | 672.00000 | 20.72627 | 18.47731 | -0.6957 | 15.61160 |
March | 744.00000 | 20.88539 | 22.63895 | -0.6075 | 13.07737 |
April | 720.00000 | 21.21313 | 27.33115 | -0.4520 | 9.48693 |
May | 744.00000 | 21.50269 | 38.96551 | -1.4031 | 46.06956 |
June | 720.00000 | 21.57606 | 50.34614 | -1.2815 | 39.91069 |
July | 744.00000 | 21.60721 | 54.72211 | -1.2360 | 37.72938 |
August | 744.00000 | 21.52300 | 55.04354 | -1.2877 | 40.10051 |
September | 720.00000 | 21.40574 | 47.30001 | -1.4108 | 46.29663 |
October | 744.00000 | 21.19295 | 36.97950 | -0.4010 | 8.48391 |
November | 720.00000 | 20.92309 | 27.00881 | -0.5678 | 12.08783 |
December | 744.00000 | 20.59553 | 17.89101 | -0.7468 | 17.34362 |
Annual Sum or Average | 8760.00000 | 21.14218 | 34.50752 | -0.9070 | 25.44317 |
Minimum of Months | 672.00000 | 20.53253 | 16.28507 | -1.4108 | 8.48391 |
Maximum of Months | 744.00000 | 21.60721 | 55.04354 | -0.4010 | 46.29663 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_5_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.49103 | 17.60294 | -0.8730 | 21.65589 |
February | 672.00000 | 20.79662 | 19.52687 | -0.7179 | 16.68948 |
March | 744.00000 | 21.03744 | 23.61074 | -0.5815 | 13.28887 |
April | 720.00000 | 21.42424 | 28.43147 | -0.3690 | 9.16590 |
May | 744.00000 | 21.68050 | 39.75696 | -1.2572 | 39.65163 |
June | 720.00000 | 21.70277 | 51.17164 | -1.1296 | 33.68262 |
July | 744.00000 | 21.72598 | 54.21670 | -1.0746 | 31.31483 |
August | 744.00000 | 21.67268 | 55.61439 | -1.1368 | 33.97244 |
September | 720.00000 | 21.55166 | 49.23575 | -1.2979 | 41.52260 |
October | 744.00000 | 21.16531 | 38.27386 | -0.4165 | 9.64256 |
November | 720.00000 | 20.78713 | 28.36411 | -0.6492 | 14.54324 |
December | 744.00000 | 20.49130 | 19.21459 | -0.8630 | 21.28480 |
Annual Sum or Average | 8760.00000 | 21.21225 | 35.50640 | -0.8651 | 23.91747 |
Minimum of Months | 672.00000 | 20.49103 | 17.60294 | -1.2979 | 9.16590 |
Maximum of Months | 744.00000 | 21.72598 | 55.61439 | -0.3690 | 41.52260 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_6_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.41647 | 17.66784 | -0.9282 | 23.91330 |
February | 672.00000 | 20.54292 | 19.79659 | -0.8184 | 19.71342 |
March | 744.00000 | 20.75290 | 23.89225 | -0.6835 | 15.56821 |
April | 720.00000 | 21.29382 | 28.56443 | -0.4309 | 9.87541 |
May | 744.00000 | 21.65874 | 39.90360 | -1.2905 | 41.04713 |
June | 720.00000 | 21.69885 | 51.36962 | -1.1444 | 34.17366 |
July | 744.00000 | 21.72149 | 54.74250 | -1.0941 | 31.97382 |
August | 744.00000 | 21.65766 | 56.50772 | -1.1691 | 35.18105 |
September | 720.00000 | 21.49796 | 49.58730 | -1.3553 | 44.00611 |
October | 744.00000 | 21.01090 | 38.56926 | -0.4809 | 10.42962 |
November | 720.00000 | 20.60264 | 28.61257 | -0.7145 | 16.38003 |
December | 744.00000 | 20.46255 | 19.25382 | -0.8994 | 22.75233 |
Annual Sum or Average | 8760.00000 | 21.11261 | 35.79444 | -0.9183 | 25.45715 |
Minimum of Months | 672.00000 | 20.41647 | 17.66784 | -1.3553 | 9.87541 |
Maximum of Months | 744.00000 | 21.72149 | 56.50772 | -0.4309 | 44.00611 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.49042 | 17.79689 | -0.9186 | 23.31172 |
February | 672.00000 | 20.70927 | 19.78344 | -0.7848 | 18.95433 |
March | 744.00000 | 20.86326 | 24.02627 | -0.6588 | 15.41836 |
April | 720.00000 | 21.25379 | 28.83395 | -0.4326 | 10.41708 |
May | 744.00000 | 21.63874 | 40.08409 | -1.2534 | 39.74911 |
June | 720.00000 | 21.66973 | 51.83842 | -1.1322 | 33.99130 |
July | 744.00000 | 21.70460 | 54.89616 | -1.0544 | 30.64846 |
August | 744.00000 | 21.65126 | 56.17261 | -1.1182 | 33.38660 |
September | 720.00000 | 21.51731 | 49.76726 | -1.3083 | 42.21581 |
October | 744.00000 | 21.06823 | 38.93128 | -0.4578 | 10.69239 |
November | 720.00000 | 20.70594 | 28.80194 | -0.7108 | 16.40575 |
December | 744.00000 | 20.47743 | 19.41483 | -0.9165 | 23.25386 |
Annual Sum or Average | 8760.00000 | 21.14788 | 35.95115 | -0.8964 | 24.90930 |
Minimum of Months | 672.00000 | 20.47743 | 17.79689 | -1.3083 | 10.41708 |
Maximum of Months | 744.00000 | 21.70460 | 56.17261 | -0.4326 | 42.21581 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.45137 | 17.84593 | -0.9667 | 25.32835 |
February | 672.00000 | 20.51778 | 20.01769 | -0.8749 | 21.79409 |
March | 744.00000 | 20.62526 | 24.32542 | -0.7539 | 17.88175 |
April | 720.00000 | 21.05057 | 29.10835 | -0.5124 | 11.68283 |
May | 744.00000 | 21.59257 | 40.28211 | -1.2955 | 41.52534 |
June | 720.00000 | 21.66110 | 51.97786 | -1.1493 | 34.55022 |
July | 744.00000 | 21.69801 | 55.38822 | -1.0756 | 31.31950 |
August | 744.00000 | 21.62745 | 57.13544 | -1.1546 | 34.70458 |
September | 720.00000 | 21.42374 | 50.31270 | -1.3804 | 45.38004 |
October | 744.00000 | 20.89091 | 39.32832 | -0.5290 | 11.67093 |
November | 720.00000 | 20.54039 | 29.05165 | -0.7742 | 18.27701 |
December | 744.00000 | 20.46324 | 19.44958 | -0.9496 | 24.65605 |
Annual Sum or Average | 8760.00000 | 21.04818 | 36.27512 | -0.9519 | 26.59348 |
Minimum of Months | 672.00000 | 20.45137 | 17.84593 | -1.3804 | 11.67093 |
Maximum of Months | 744.00000 | 21.69801 | 57.13544 | -0.5124 | 45.38004 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT9_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.88550 | 19.13028 | -0.7110 | 16.99524 |
February | 672.00000 | 21.18743 | 21.01503 | -0.5631 | 13.51670 |
March | 744.00000 | 21.23086 | 24.97322 | -0.4962 | 11.82891 |
April | 720.00000 | 21.44647 | 29.52773 | -0.3538 | 9.08095 |
May | 744.00000 | 21.65721 | 40.31394 | -1.2782 | 40.80806 |
June | 720.00000 | 21.66467 | 51.51894 | -1.1822 | 36.08687 |
July | 744.00000 | 21.69572 | 54.63247 | -1.1153 | 33.15791 |
August | 744.00000 | 21.66067 | 54.96534 | -1.1433 | 34.47552 |
September | 720.00000 | 21.59010 | 48.66080 | -1.2640 | 40.19680 |
October | 744.00000 | 21.29996 | 38.80636 | -0.3500 | 8.94123 |
November | 720.00000 | 21.06185 | 29.33339 | -0.5467 | 12.55511 |
December | 744.00000 | 20.78413 | 20.70659 | -0.7417 | 17.74186 |
Annual Sum or Average | 8760.00000 | 21.34733 | 36.21650 | -0.8139 | 23.00951 |
Minimum of Months | 672.00000 | 20.78413 | 19.13028 | -1.2782 | 8.94123 |
Maximum of Months | 744.00000 | 21.69572 | 54.96534 | -0.3500 | 40.80806 |
Report: OccupantComfortDataSummaryMonthly
For: BANQUET_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 18.28698 | 13.14230 | -1.1617 | 32.41197 |
February | 672.00000 | 20.23729 | 15.69857 | -0.6785 | 17.98479 |
March | 744.00000 | 21.08639 | 19.94441 | -0.4224 | 10.16759 |
April | 720.00000 | 21.48499 | 25.18909 | -0.2501 | 6.69405 |
May | 744.00000 | 21.74816 | 38.77619 | -1.1103 | 31.75414 |
June | 720.00000 | 21.86103 | 53.53066 | -0.9530 | 25.05388 |
July | 744.00000 | 21.88969 | 60.07303 | -0.8929 | 22.52638 |
August | 744.00000 | 21.81253 | 59.59145 | -0.9456 | 24.58406 |
September | 720.00000 | 21.65698 | 47.65810 | -1.1112 | 31.66278 |
October | 744.00000 | 21.49103 | 34.49722 | -0.1963 | 6.18369 |
November | 720.00000 | 21.33642 | 24.28105 | -0.3357 | 7.76790 |
December | 744.00000 | 19.07846 | 14.85738 | -0.9643 | 27.92624 |
Annual Sum or Average | 8760.00000 | 20.99731 | 34.04567 | -0.7534 | 20.44139 |
Minimum of Months | 672.00000 | 18.28698 | 13.14230 | -1.1617 | 6.18369 |
Maximum of Months | 744.00000 | 21.88969 | 60.07303 | -0.1963 | 32.41197 |
Report: OccupantComfortDataSummaryMonthly
For: DINING_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 18.25236 | 12.92737 | -1.1371 | 31.61527 |
February | 672.00000 | 20.23843 | 15.45275 | -0.6463 | 17.36428 |
March | 744.00000 | 21.12251 | 19.67224 | -0.3812 | 9.60926 |
April | 720.00000 | 21.54886 | 24.88206 | -0.2022 | 6.27338 |
May | 744.00000 | 21.83859 | 38.35803 | -1.0335 | 28.43148 |
June | 720.00000 | 21.96279 | 53.00367 | -0.8723 | 21.98596 |
July | 744.00000 | 21.99183 | 59.50208 | -0.8127 | 19.65375 |
August | 744.00000 | 21.90215 | 59.06586 | -0.8696 | 21.71600 |
September | 720.00000 | 21.73284 | 47.23157 | -1.0397 | 28.54973 |
October | 744.00000 | 21.55362 | 34.15716 | -0.1489 | 5.87265 |
November | 720.00000 | 21.38314 | 23.99414 | -0.2913 | 7.22601 |
December | 744.00000 | 19.06104 | 14.62394 | -0.9355 | 27.20584 |
Annual Sum or Average | 8760.00000 | 21.04902 | 33.68090 | -0.6990 | 18.83420 |
Minimum of Months | 672.00000 | 18.25236 | 12.92737 | -1.1371 | 5.87265 |
Maximum of Months | 744.00000 | 21.99183 | 59.50208 | -0.1489 | 31.61527 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 18.13335 | 17.69907 | -0.5384 | 30.71869 |
February | 672.00000 | 20.83088 | 17.69072 | 0.12114 | 21.37161 |
March | 744.00000 | 22.17168 | 20.60358 | 0.49447 | 19.48661 |
April | 720.00000 | 22.83392 | 24.92986 | 0.74476 | 22.43899 |
May | 744.00000 | 23.02033 | 37.12209 | 0.29813 | 19.14551 |
June | 720.00000 | 23.09032 | 50.74916 | 0.45466 | 21.08821 |
July | 744.00000 | 23.10093 | 56.76578 | 0.51479 | 22.31506 |
August | 744.00000 | 23.04204 | 56.23335 | 0.45085 | 20.79236 |
September | 720.00000 | 22.94057 | 45.30521 | 0.28252 | 17.95681 |
October | 744.00000 | 22.74875 | 33.44559 | 0.75832 | 22.30636 |
November | 720.00000 | 22.52146 | 24.40284 | 0.58430 | 16.94449 |
December | 744.00000 | 19.14984 | 18.33929 | -0.2966 | 26.83002 |
Annual Sum or Average | 8760.00000 | 21.96501 | 33.70801 | 0.32194 | 21.81012 |
Minimum of Months | 672.00000 | 18.13335 | 17.69072 | -0.5384 | 16.94449 |
Maximum of Months | 744.00000 | 23.10093 | 56.76578 | 0.75832 | 30.71869 |
Report: OccupantComfortDataSummaryMonthly
For: STORAGE_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 17.78968 | 10.03346 | -1.3969 | 42.96526 |
February | 672.00000 | 20.10606 | 11.79053 | -0.8559 | 22.58994 |
March | 744.00000 | 20.85724 | 15.85879 | -0.6429 | 14.17027 |
April | 720.00000 | 21.00013 | 21.33854 | -0.5454 | 11.32339 |
May | 744.00000 | 21.00154 | 35.92037 | -1.6279 | 57.83834 |
June | 720.00000 | 21.00907 | 51.94477 | -1.5155 | 51.75577 |
July | 744.00000 | 21.00643 | 59.12680 | -1.4654 | 49.03318 |
August | 744.00000 | 21.00252 | 58.16050 | -1.4831 | 49.98625 |
September | 720.00000 | 21.00019 | 45.07079 | -1.5818 | 55.37604 |
October | 744.00000 | 21.00013 | 30.99227 | -0.4845 | 9.96776 |
November | 720.00000 | 21.00016 | 20.30019 | -0.5744 | 12.00722 |
December | 744.00000 | 18.81226 | 11.40860 | -1.1565 | 35.29913 |
Annual Sum or Average | 8760.00000 | 20.46252 | 31.11312 | -1.1136 | 34.47522 |
Minimum of Months | 672.00000 | 17.78968 | 10.03346 | -1.6279 | 9.96776 |
Maximum of Months | 744.00000 | 21.00907 | 59.12680 | -0.4845 | 57.83834 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 19.13565 | 11.65991 | -1.0599 | 31.55160 |
February | 672.00000 | 20.57099 | 13.78338 | -0.7112 | 16.67485 |
March | 744.00000 | 20.92555 | 18.00818 | -0.5910 | 12.55352 |
April | 720.00000 | 21.02392 | 23.44313 | -0.5131 | 10.60283 |
May | 744.00000 | 21.13561 | 37.65406 | -1.5688 | 54.65995 |
June | 720.00000 | 21.23923 | 53.10313 | -1.4373 | 47.60838 |
July | 744.00000 | 21.43487 | 59.46149 | -1.3259 | 41.67412 |
August | 744.00000 | 21.24349 | 59.24897 | -1.4000 | 45.55955 |
September | 720.00000 | 21.07838 | 46.92222 | -1.5424 | 53.24238 |
October | 744.00000 | 21.01888 | 33.07938 | -0.4643 | 9.58642 |
November | 720.00000 | 21.00048 | 22.44343 | -0.5569 | 11.57738 |
December | 744.00000 | 19.72628 | 13.21632 | -0.9203 | 25.43232 |
Annual Sum or Average | 8760.00000 | 20.79309 | 32.78211 | -1.0100 | 30.16265 |
Minimum of Months | 672.00000 | 19.13565 | 11.65991 | -1.5688 | 9.58642 |
Maximum of Months | 744.00000 | 21.43487 | 59.46149 | -0.4643 | 54.65995 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 18.05232 | 10.41779 | -1.3523 | 40.57766 |
February | 672.00000 | 20.17104 | 12.38962 | -0.8411 | 22.10737 |
March | 744.00000 | 20.84761 | 16.54681 | -0.6332 | 14.08157 |
April | 720.00000 | 21.00865 | 22.00597 | -0.5172 | 10.72559 |
May | 744.00000 | 21.04372 | 36.43005 | -1.5572 | 54.03976 |
June | 720.00000 | 21.09268 | 52.10463 | -1.4269 | 47.05931 |
July | 744.00000 | 21.12314 | 59.02516 | -1.3618 | 43.58875 |
August | 744.00000 | 21.07506 | 58.34105 | -1.3997 | 45.56872 |
September | 720.00000 | 21.02503 | 45.59301 | -1.5285 | 52.50082 |
October | 744.00000 | 21.00905 | 31.61911 | -0.4672 | 9.67817 |
November | 720.00000 | 21.00050 | 20.98722 | -0.5772 | 12.10221 |
December | 744.00000 | 18.92120 | 11.89718 | -1.1478 | 34.44797 |
Annual Sum or Average | 8760.00000 | 20.52830 | 31.56226 | -1.0700 | 32.30714 |
Minimum of Months | 672.00000 | 18.05232 | 10.41779 | -1.5572 | 9.67817 |
Maximum of Months | 744.00000 | 21.12314 | 59.02516 | -0.4672 | 54.03976 |
Report: OccupantComfortDataSummaryMonthly
For: MECH_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 17.85864 | 9.77471 | -1.3617 | 41.50033 |
February | 672.00000 | 20.15457 | 11.52456 | -0.8222 | 21.47633 |
March | 744.00000 | 20.85883 | 15.61539 | -0.6163 | 13.49157 |
April | 720.00000 | 21.00033 | 21.09410 | -0.5222 | 10.80103 |
May | 744.00000 | 21.02027 | 35.61403 | -1.5935 | 55.98531 |
June | 720.00000 | 21.04363 | 51.53937 | -1.4790 | 49.79232 |
July | 744.00000 | 21.04975 | 58.65639 | -1.4268 | 46.96776 |
August | 744.00000 | 21.03576 | 57.75013 | -1.4462 | 48.00907 |
September | 720.00000 | 21.00816 | 44.78623 | -1.5494 | 53.62100 |
October | 744.00000 | 21.00035 | 30.74015 | -0.4614 | 9.50673 |
November | 720.00000 | 21.00008 | 20.05991 | -0.5473 | 11.36106 |
December | 744.00000 | 18.87933 | 11.13709 | -1.1199 | 33.89212 |
Annual Sum or Average | 8760.00000 | 20.48955 | 30.80822 | -1.0815 | 33.14668 |
Minimum of Months | 672.00000 | 17.85864 | 9.77471 | -1.5935 | 9.50673 |
Maximum of Months | 744.00000 | 21.04975 | 58.65639 | -0.4614 | 55.98531 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.606589E+09 | 10845.71 | 17-JAN-19:04 | 49.09 | 0.178792E+10 | 0.00 | 0.239451E+10 | 0.19 | 2.95 | 01-JAN-14:50 | 0.00 | 0.00 |
February | 0.305286E+10 | 33516.79 | 22-FEB-16:05 | 148.57 | 0.899830E+10 | 0.00 | 0.120512E+11 | 0.65 | 2.95 | 01-FEB-12:20 | 0.00 | 0.00 |
March | 0.686519E+10 | 43028.79 | 19-MAR-15:03 | 246.76 | 0.202352E+11 | 0.00 | 0.271003E+11 | 0.98 | 2.95 | 02-MAR-16:03 | 0.00 | 0.00 |
April | 0.319486E+11 | 152200.39 | 23-APR-18:03 | 507.36 | 0.934423E+11 | 0.00 | 0.125391E+12 | 2.07 | 3.53 | 13-APR-15:01 | 0.00 | 0.00 |
May | 0.116688E+12 | 204274.12 | 25-MAY-18:03 | 735.53 | 0.351223E+12 | 0.00 | 0.467911E+12 | 2.92 | 3.85 | 26-MAY-18:03 | 0.00 | 0.00 |
June | 0.216462E+12 | 304761.01 | 29-JUN-18:03 | 719.94 | 0.707759E+12 | 0.00 | 0.924221E+12 | 3.13 | 4.19 | 18-JUN-18:03 | 0.00 | 0.00 |
July | 0.278505E+12 | 277055.13 | 15-JUL-15:03 | 744.00 | 0.944100E+12 | 0.00 | 0.122261E+13 | 3.25 | 4.18 | 25-JUL-18:03 | 0.00 | 0.00 |
August | 0.216492E+12 | 262065.57 | 08-AUG-15:03 | 743.81 | 0.714305E+12 | 0.00 | 0.930796E+12 | 3.14 | 4.12 | 28-AUG-18:02 | 0.00 | 0.00 |
September | 0.847201E+11 | 171032.51 | 01-SEP-15:03 | 704.44 | 0.254731E+12 | 0.00 | 0.339451E+12 | 2.88 | 4.17 | 18-SEP-18:01 | 0.00 | 0.00 |
October | 0.247582E+11 | 128019.64 | 19-OCT-15:02 | 503.71 | 0.729220E+11 | 0.00 | 0.976802E+11 | 1.99 | 3.65 | 21-OCT-15:02 | 0.00 | 0.00 |
November | 0.510845E+10 | 77768.92 | 01-NOV-15:03 | 212.17 | 0.147987E+11 | 0.00 | 0.199072E+11 | 0.87 | 2.95 | 01-NOV-22:50 | 0.00 | 0.00 |
December | 0.354536E+09 | 9826.04 | 28-DEC-09:04 | 32.48 | 0.104500E+10 | 0.00 | 0.139953E+10 | 0.13 | 2.95 | 02-DEC-10:24 | 0.00 | 0.00 |
Annual Sum or Average | 0.985562E+12 | 5347.88 | 0.318535E+13 | 0.00 | 0.417091E+13 | 1.86 | 0.00 | 0.00 | ||||
Minimum of Months | 0.354536E+09 | 9826.04 | 32.48 | 0.104500E+10 | 0.00 | 0.139953E+10 | 0.13 | 2.95 | 0.00 | 0.00 | ||
Maximum of Months | 0.278505E+12 | 304761.01 | 744.00 | 0.944100E+12 | 0.00 | 0.122261E+13 | 3.25 | 4.19 | 0.00 | 0.00 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.104887E+13 | 0.00 | 744.00 | 914305.51 | 06-JAN-08:04 | 0.00 | 35.88 | 60.01 | 3.71 | 0.00 | 0.48 | 1.13 | 06-JAN-08:04 |
February | 0.604299E+12 | 0.00 | 672.00 | 882236.19 | 17-FEB-06:00 | 0.00 | 36.55 | 60.00 | 2.43 | 0.00 | 0.31 | 1.09 | 17-FEB-06:00 |
March | 0.373906E+12 | 0.00 | 744.00 | 844161.73 | 05-MAR-07:00 | 0.00 | 36.52 | 60.00 | 1.38 | 0.00 | 0.17 | 1.04 | 05-MAR-07:00 |
April | 0.114505E+12 | 0.00 | 720.00 | 257571.25 | 05-APR-08:61 | 0.00 | 35.09 | 60.00 | 0.44 | 0.00 | 0.05 | 0.32 | 05-APR-08:61 |
May | 0.647179E+11 | 0.00 | 744.00 | 92865.93 | 01-MAY-08:03 | 0.00 | 31.58 | 60.00 | 0.21 | 0.00 | 0.03 | 0.11 | 01-MAY-08:03 |
June | 0.556820E+11 | 0.00 | 720.00 | 84398.22 | 02-JUN-08:05 | 0.00 | 30.92 | 60.00 | 0.19 | 0.00 | 0.03 | 0.10 | 02-JUN-08:05 |
July | 0.477673E+11 | 0.00 | 744.00 | 75881.11 | 10-JUL-10:35 | 0.00 | 29.64 | 60.00 | 0.15 | 0.00 | 0.02 | 0.09 | 10-JUL-10:35 |
August | 0.457278E+11 | 0.00 | 744.00 | 92138.16 | 07-AUG-08:05 | 0.00 | 28.96 | 60.00 | 0.14 | 0.00 | 0.02 | 0.11 | 07-AUG-08:05 |
September | 0.544661E+11 | 0.00 | 720.00 | 86484.04 | 27-SEP-15:05 | 0.00 | 29.59 | 60.00 | 0.17 | 0.00 | 0.03 | 0.11 | 27-SEP-15:05 |
October | 0.954347E+11 | 0.00 | 744.00 | 246978.18 | 30-OCT-08:61 | 0.00 | 34.73 | 60.00 | 0.36 | 0.00 | 0.04 | 0.30 | 30-OCT-08:61 |
November | 0.235136E+12 | 0.00 | 720.00 | 369447.12 | 25-NOV-09:03 | 0.00 | 36.86 | 60.00 | 0.93 | 0.00 | 0.11 | 0.46 | 25-NOV-09:03 |
December | 0.930533E+12 | 0.00 | 744.00 | 881821.79 | 24-DEC-06:00 | 0.00 | 36.41 | 60.01 | 3.36 | 0.00 | 0.43 | 1.09 | 24-DEC-06:00 |
Annual Sum or Average | 0.367105E+13 | 0.00 | 8760.00 | 0.00 | 33.54 | 60.00 | 1.12 | 0.00 | 0.14 | ||||
Minimum of Months | 0.457278E+11 | 0.00 | 672.00 | 75881.11 | 0.00 | 28.96 | 60.00 | 0.14 | 0.00 | 0.02 | 0.09 | ||
Maximum of Months | 0.104887E+13 | 0.00 | 744.00 | 914305.51 | 0.00 | 36.86 | 60.01 | 3.71 | 0.00 | 0.48 | 1.13 |
Report: DXReportMonthly
For: VAV WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 |
April | 0.284230E+11 | 0.00 | 76.03 | 0.284230E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 280174.90 | 23-APR-18:10 | 280174.90 | 23-APR-18:10 | 0.00 | 0.00 | 0.00 |
May | 0.193467E+12 | 0.00 | 373.33 | 0.187838E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 427274.18 | 26-MAY-10:35 | 333311.75 | 25-MAY-18:10 | 0.00 | 0.00 | 0.00 |
June | 0.485694E+12 | 0.00 | 547.00 | 0.336951E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 651274.61 | 19-JUN-18:30 | 376452.23 | 29-JUN-17:12 | 0.00 | 0.00 | 0.00 |
July | 0.664927E+12 | 0.00 | 641.50 | 0.426354E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 654318.98 | 23-JUL-10:35 | 340076.30 | 23-JUL-10:35 | 0.00 | 0.00 | 0.00 |
August | 0.486034E+12 | 0.00 | 625.67 | 0.332034E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 560575.35 | 08-AUG-17:13 | 329758.13 | 08-AUG-16:20 | 0.00 | 0.00 | 0.00 |
September | 0.129382E+12 | 0.00 | 284.00 | 0.105940E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 413057.24 | 01-SEP-10:40 | 284767.94 | 01-SEP-16:00 | 0.00 | 0.00 | 0.00 |
October | 0.182107E+11 | 0.00 | 54.98 | 0.182107E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 230822.19 | 19-OCT-15:40 | 230822.19 | 19-OCT-15:40 | 0.00 | 0.00 | 0.00 |
November | 0.291286E+10 | 0.00 | 11.50 | 0.290003E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 125198.68 | 01-NOV-15:00 | 125198.68 | 01-NOV-15:00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.200905E+13 | 0.00 | 2614.00 | 0.143865E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.664927E+12 | 0.00 | 641.50 | 0.426354E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 654318.98 | 376452.23 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: FLR_3_DOAS COOLING COIL
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 |
April | 0.220642E+10 | 0.00 | 63.83 | 0.220642E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28765.73 | 23-APR-18:00 | 28765.73 | 23-APR-18:00 | 0.00 | 0.00 | 0.00 |
May | 0.180867E+11 | 0.00 | 313.00 | 0.173404E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 41735.47 | 26-MAY-13:10 | 31392.69 | 25-MAY-18:00 | 0.00 | 0.00 | 0.00 |
June | 0.470980E+11 | 0.00 | 495.67 | 0.325974E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 64926.26 | 19-JUN-17:25 | 34823.67 | 29-JUN-15:02 | 0.00 | 0.00 | 0.00 |
July | 0.659880E+11 | 0.00 | 611.33 | 0.421316E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 70530.37 | 04-JUL-02:50 | 32902.88 | 15-JUL-14:00 | 0.00 | 0.00 | 0.00 |
August | 0.467551E+11 | 0.00 | 576.33 | 0.315323E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 57886.29 | 30-AUG-08:50 | 32381.07 | 08-AUG-15:00 | 0.00 | 0.00 | 0.00 |
September | 0.106497E+11 | 0.00 | 226.83 | 0.879579E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41432.33 | 01-SEP-10:25 | 29123.67 | 01-SEP-15:02 | 0.00 | 0.00 | 0.00 |
October | 0.144271E+10 | 0.00 | 42.00 | 0.144271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24823.32 | 19-OCT-15:00 | 24823.32 | 19-OCT-15:00 | 0.00 | 0.00 | 0.00 |
November | 0.223309E+09 | 0.00 | 8.83 | 0.223309E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12273.97 | 01-NOV-15:00 | 12273.97 | 01-NOV-15:00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.192450E+12 | 0.00 | 2337.83 | 0.136270E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.659880E+11 | 0.00 | 611.33 | 0.421316E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 70530.37 | 34823.67 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 1719532.54 | 0.00 | 0.42 | 1719532.54 | 0.00 | 0.00 | 0.00 | 0.00 | 5074.43 | 27-JAN-16:01 | 5074.43 | 27-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.197438E+09 | 0.00 | 25.30 | 0.197438E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19208.77 | 04-FEB-16:01 | 19208.77 | 04-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.816027E+09 | 0.00 | 81.04 | 0.816027E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19224.97 | 28-MAR-18:02 | 19224.97 | 28-MAR-18:02 | 0.00 | 0.00 | 0.00 |
April | 0.266526E+10 | 0.00 | 256.48 | 0.255612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19237.10 | 18-APR-15:02 | 19237.10 | 18-APR-15:02 | 0.00 | 0.00 | 0.00 |
May | 0.654952E+10 | 0.00 | 578.76 | 0.493466E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20130.28 | 26-MAY-08:61 | 19239.12 | 11-MAY-15:01 | 0.00 | 0.00 | 0.00 |
June | 0.813006E+10 | 0.00 | 611.41 | 0.494509E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23076.56 | 19-JUN-18:01 | 19237.94 | 16-JUN-15:02 | 0.00 | 0.00 | 0.00 |
July | 0.106873E+11 | 0.00 | 684.61 | 0.616527E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22820.45 | 23-JUL-08:62 | 18498.71 | 04-JUL-15:02 | 0.00 | 0.00 | 0.00 |
August | 0.845207E+10 | 0.00 | 641.60 | 0.459793E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22330.11 | 30-AUG-08:62 | 18347.10 | 16-AUG-15:02 | 0.00 | 0.00 | 0.00 |
September | 0.422706E+10 | 0.00 | 485.38 | 0.257206E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22041.15 | 18-SEP-18:01 | 19237.30 | 04-SEP-15:01 | 0.00 | 0.00 | 0.00 |
October | 0.136382E+10 | 0.00 | 183.93 | 0.996476E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19237.50 | 21-OCT-15:02 | 19237.50 | 21-OCT-15:02 | 0.00 | 0.00 | 0.00 |
November | 46317255.19 | 0.00 | 14.37 | 43704134.24 | 0.00 | 0.00 | 0.00 | 0.00 | 19203.89 | 17-NOV-16:01 | 19203.89 | 17-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 245870.86 | 0.00 | 0.05 | 245870.86 | 0.00 | 0.00 | 0.00 | 0.00 | 2346.62 | 28-DEC-16:04 | 2346.62 | 28-DEC-16:04 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.431369E+11 | 0.00 | 3563.34 | 0.278267E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 245870.86 | 0.00 | 0.05 | 245870.86 | 0.00 | 0.00 | 0.00 | 0.00 | 2346.62 | 2346.62 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.106873E+11 | 0.00 | 684.61 | 0.616527E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23076.56 | 19239.12 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 180638.34 | 0.00 | 0.02 | 180638.34 | 0.00 | 0.00 | 0.00 | 0.00 | 2107.45 | 17-JAN-16:04 | 2107.45 | 17-JAN-16:04 | 0.00 | 0.00 | 0.00 |
February | 35570615.21 | 0.00 | 7.03 | 35570615.21 | 0.00 | 0.00 | 0.00 | 0.00 | 16403.43 | 28-FEB-16:02 | 16403.43 | 28-FEB-16:02 | 0.00 | 0.00 | 0.00 |
March | 0.338035E+09 | 0.00 | 43.90 | 0.338035E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18318.19 | 28-MAR-18:02 | 18318.19 | 28-MAR-18:02 | 0.00 | 0.00 | 0.00 |
April | 0.164754E+10 | 0.00 | 178.10 | 0.156369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18328.81 | 18-APR-15:02 | 18328.81 | 18-APR-15:02 | 0.00 | 0.00 | 0.00 |
May | 0.552891E+10 | 0.00 | 528.82 | 0.407177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19074.30 | 26-MAY-08:61 | 18331.55 | 11-MAY-15:01 | 0.00 | 0.00 | 0.00 |
June | 0.751055E+10 | 0.00 | 593.64 | 0.455893E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21536.28 | 25-JUN-08:61 | 18330.38 | 16-JUN-15:02 | 0.00 | 0.00 | 0.00 |
July | 0.969528E+10 | 0.00 | 670.90 | 0.552347E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21706.09 | 23-JUL-08:62 | 17677.99 | 21-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.697450E+10 | 0.00 | 612.58 | 0.360807E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20998.89 | 30-AUG-08:62 | 17665.86 | 12-AUG-15:02 | 0.00 | 0.00 | 0.00 |
September | 0.280449E+10 | 0.00 | 395.05 | 0.163644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20932.48 | 18-SEP-18:01 | 18332.20 | 06-SEP-15:01 | 0.00 | 0.00 | 0.00 |
October | 0.538034E+09 | 0.00 | 87.33 | 0.413026E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18329.52 | 21-OCT-15:02 | 18329.52 | 21-OCT-15:02 | 0.00 | 0.00 | 0.00 |
November | 6995961.74 | 0.00 | 2.60 | 5340435.15 | 0.00 | 0.00 | 0.00 | 0.00 | 8523.12 | 17-NOV-16:01 | 8523.12 | 17-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.350801E+11 | 0.00 | 3119.97 | 0.217545E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.969528E+10 | 0.00 | 670.90 | 0.552347E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21706.09 | 18332.20 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.143624E+09 | 0.00 | 6.00 | 0.143624E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14028.50 | 27-JAN-15:00 | 14028.50 | 27-JAN-15:00 | 0.00 | 0.00 | 0.00 |
February | 0.324991E+10 | 0.00 | 59.08 | 0.324991E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43602.61 | 22-FEB-14:00 | 43602.61 | 22-FEB-14:00 | 0.00 | 0.00 | 0.00 |
March | 0.764897E+10 | 0.00 | 124.67 | 0.764897E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51687.18 | 20-MAR-12:30 | 51687.18 | 20-MAR-12:30 | 0.00 | 0.00 | 0.00 |
April | 0.210919E+11 | 0.00 | 308.92 | 0.206590E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 57688.11 | 13-APR-13:00 | 57688.11 | 13-APR-13:00 | 0.00 | 0.00 | 0.00 |
May | 0.367091E+11 | 0.00 | 587.85 | 0.282477E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 53825.10 | 18-MAY-13:00 | 51526.70 | 06-MAY-13:00 | 0.00 | 0.00 | 0.00 |
June | 0.400986E+11 | 0.00 | 602.61 | 0.233313E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 56619.27 | 30-JUN-13:00 | 49577.88 | 30-JUN-13:00 | 0.00 | 0.00 | 0.00 |
July | 0.529749E+11 | 0.00 | 691.50 | 0.272267E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 63353.81 | 23-JUL-14:10 | 52014.97 | 29-JUL-12:30 | 0.00 | 0.00 | 0.00 |
August | 0.494592E+11 | 0.00 | 667.66 | 0.262223E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 63644.99 | 26-AUG-14:50 | 52380.49 | 22-AUG-13:30 | 0.00 | 0.00 | 0.00 |
September | 0.359257E+11 | 0.00 | 540.28 | 0.260231E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 63178.39 | 01-SEP-15:30 | 62051.40 | 04-SEP-12:30 | 0.00 | 0.00 | 0.00 |
October | 0.196049E+11 | 0.00 | 250.08 | 0.182957E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 79891.34 | 22-OCT-12:20 | 75601.68 | 22-OCT-12:20 | 0.00 | 0.00 | 0.00 |
November | 0.322766E+10 | 0.00 | 55.14 | 0.322766E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 48309.57 | 17-NOV-12:20 | 48309.57 | 17-NOV-12:20 | 0.00 | 0.00 | 0.00 |
December | 38192706.26 | 0.00 | 2.17 | 38192706.26 | 0.00 | 0.00 | 0.00 | 0.00 | 7776.16 | 02-DEC-14:30 | 7776.16 | 02-DEC-14:30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.270173E+12 | 0.00 | 3895.95 | 0.184314E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 38192706.26 | 0.00 | 2.17 | 38192706.26 | 0.00 | 0.00 | 0.00 | 0.00 | 7776.16 | 7776.16 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.529749E+11 | 0.00 | 691.50 | 0.282477E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 79891.34 | 75601.68 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 29386826.18 | 0.00 | 2.62 | 29386826.18 | 0.00 | 0.00 | 0.00 | 0.00 | 27450.00 | 17-JAN-19:04 | 27450.00 | 17-JAN-19:04 | 0.00 | 0.00 | 0.00 |
February | 0.253043E+09 | 0.00 | 20.65 | 0.253043E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 28428.29 | 22-FEB-19:03 | 28428.29 | 22-FEB-19:03 | 0.00 | 0.00 | 0.00 |
March | 0.215104E+10 | 0.00 | 92.30 | 0.215104E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 87868.49 | 28-MAR-18:02 | 87868.49 | 28-MAR-18:02 | 0.00 | 0.00 | 0.00 |
April | 0.144450E+11 | 0.00 | 344.60 | 0.138085E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 92057.38 | 23-APR-08:61 | 92057.38 | 23-APR-08:61 | 0.00 | 0.00 | 0.00 |
May | 0.458117E+11 | 0.00 | 528.40 | 0.371421E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 99208.62 | 26-MAY-18:02 | 94840.60 | 20-MAY-18:01 | 0.00 | 0.00 | 0.00 |
June | 0.636034E+11 | 0.00 | 536.73 | 0.438954E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 114062.34 | 25-JUN-08:61 | 95716.04 | 17-JUN-18:02 | 0.00 | 0.00 | 0.00 |
July | 0.736189E+11 | 0.00 | 567.73 | 0.477755E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 114035.75 | 25-JUL-18:02 | 91477.01 | 17-JUL-15:02 | 0.00 | 0.00 | 0.00 |
August | 0.599045E+11 | 0.00 | 531.88 | 0.359310E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 108631.79 | 07-AUG-18:02 | 91294.25 | 20-AUG-15:02 | 0.00 | 0.00 | 0.00 |
September | 0.352240E+11 | 0.00 | 507.68 | 0.217533E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 106055.18 | 18-SEP-18:01 | 94159.84 | 04-SEP-18:01 | 0.00 | 0.00 | 0.00 |
October | 0.132828E+11 | 0.00 | 394.87 | 0.983406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 91486.05 | 01-OCT-18:01 | 91486.05 | 01-OCT-18:01 | 0.00 | 0.00 | 0.00 |
November | 0.241318E+10 | 0.00 | 114.60 | 0.176633E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 80444.06 | 01-NOV-18:03 | 77910.72 | 01-NOV-18:03 | 0.00 | 0.00 | 0.00 |
December | 45356364.01 | 0.00 | 3.08 | 45356364.01 | 0.00 | 0.00 | 0.00 | 0.00 | 27832.60 | 28-DEC-19:04 | 27832.60 | 28-DEC-19:04 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.310782E+12 | 0.00 | 3645.14 | 0.214385E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 29386826.18 | 0.00 | 2.62 | 29386826.18 | 0.00 | 0.00 | 0.00 | 0.00 | 27450.00 | 27450.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.736189E+11 | 0.00 | 567.73 | 0.477755E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 114062.34 | 95716.04 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_5_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 719509.79 | 0.00 | 0.10 | 719509.79 | 0.00 | 0.00 | 0.00 | 0.00 | 2442.24 | 17-JAN-16:04 | 2442.24 | 17-JAN-16:04 | 0.00 | 0.00 | 0.00 |
February | 0.107861E+09 | 0.00 | 21.40 | 0.107861E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16814.63 | 28-FEB-16:02 | 16814.63 | 28-FEB-16:02 | 0.00 | 0.00 | 0.00 |
March | 0.596770E+09 | 0.00 | 94.40 | 0.596770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17523.57 | 26-MAR-15:01 | 17523.57 | 26-MAR-15:01 | 0.00 | 0.00 | 0.00 |
April | 0.274582E+10 | 0.00 | 296.35 | 0.263858E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17540.14 | 18-APR-08:62 | 17540.14 | 18-APR-08:62 | 0.00 | 0.00 | 0.00 |
May | 0.617685E+10 | 0.00 | 587.66 | 0.457882E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18291.06 | 26-MAY-08:61 | 17540.45 | 11-MAY-15:01 | 0.00 | 0.00 | 0.00 |
June | 0.872326E+10 | 0.00 | 640.86 | 0.542873E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21062.05 | 19-JUN-18:01 | 17539.49 | 16-JUN-15:02 | 0.00 | 0.00 | 0.00 |
July | 0.107483E+11 | 0.00 | 699.82 | 0.625034E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21021.17 | 25-JUL-18:02 | 16896.67 | 24-JUL-08:61 | 0.00 | 0.00 | 0.00 |
August | 0.818791E+10 | 0.00 | 652.42 | 0.443746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20486.83 | 30-AUG-08:62 | 16911.31 | 25-AUG-08:62 | 0.00 | 0.00 | 0.00 |
September | 0.415777E+10 | 0.00 | 480.48 | 0.250020E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19611.18 | 18-SEP-18:01 | 17541.01 | 09-SEP-08:61 | 0.00 | 0.00 | 0.00 |
October | 0.123828E+10 | 0.00 | 170.02 | 0.876598E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17539.11 | 21-OCT-15:02 | 17539.11 | 21-OCT-15:02 | 0.00 | 0.00 | 0.00 |
November | 0.113828E+09 | 0.00 | 17.08 | 0.111542E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16408.70 | 16-NOV-09:01 | 16408.70 | 16-NOV-09:01 | 0.00 | 0.00 | 0.00 |
December | 289380.13 | 0.00 | 0.11 | 289380.13 | 0.00 | 0.00 | 0.00 | 0.00 | 3067.84 | 28-DEC-09:04 | 3067.84 | 28-DEC-09:04 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.427977E+11 | 0.00 | 3660.69 | 0.275279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 289380.13 | 0.00 | 0.10 | 289380.13 | 0.00 | 0.00 | 0.00 | 0.00 | 2442.24 | 2442.24 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.107483E+11 | 0.00 | 699.82 | 0.625034E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21062.05 | 17541.01 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_6_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 |
February | 5440157.14 | 0.00 | 2.56 | 5440157.14 | 0.00 | 0.00 | 0.00 | 0.00 | 3823.86 | 28-FEB-09:03 | 3823.86 | 28-FEB-09:03 | 0.00 | 0.00 | 0.00 |
March | 0.163858E+09 | 0.00 | 33.17 | 0.163858E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15974.99 | 26-MAR-08:61 | 15974.99 | 26-MAR-08:61 | 0.00 | 0.00 | 0.00 |
April | 0.155927E+10 | 0.00 | 218.00 | 0.148776E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16687.34 | 18-APR-08:62 | 16687.34 | 18-APR-08:62 | 0.00 | 0.00 | 0.00 |
May | 0.511031E+10 | 0.00 | 554.07 | 0.367060E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17320.37 | 26-MAY-08:61 | 16686.14 | 10-MAY-08:62 | 0.00 | 0.00 | 0.00 |
June | 0.806652E+10 | 0.00 | 635.81 | 0.498479E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19420.49 | 19-JUN-18:01 | 16686.12 | 16-JUN-15:02 | 0.00 | 0.00 | 0.00 |
July | 0.972260E+10 | 0.00 | 694.49 | 0.554978E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19732.22 | 22-JUL-08:61 | 16135.06 | 23-JUL-15:02 | 0.00 | 0.00 | 0.00 |
August | 0.667011E+10 | 0.00 | 639.93 | 0.338908E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19258.13 | 30-AUG-08:62 | 16069.39 | 20-AUG-08:62 | 0.00 | 0.00 | 0.00 |
September | 0.267612E+10 | 0.00 | 405.07 | 0.151355E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18601.65 | 18-SEP-18:01 | 16687.57 | 06-SEP-15:01 | 0.00 | 0.00 | 0.00 |
October | 0.414063E+09 | 0.00 | 71.23 | 0.277199E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16304.04 | 01-OCT-15:01 | 16304.04 | 01-OCT-15:01 | 0.00 | 0.00 | 0.00 |
November | 12281386.68 | 0.00 | 7.23 | 10560932.42 | 0.00 | 0.00 | 0.00 | 0.00 | 4120.84 | 10-NOV-09:03 | 4120.84 | 10-NOV-09:03 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.344006E+11 | 0.00 | 3261.56 | 0.210526E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.972260E+10 | 0.00 | 694.49 | 0.554978E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19732.22 | 16687.57 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 636514.09 | 0.00 | 0.47 | 636514.09 | 0.00 | 0.00 | 0.00 | 0.00 | 997.22 | 17-JAN-16:03 | 997.22 | 17-JAN-16:03 | 0.00 | 0.00 | 0.00 |
February | 48749922.94 | 0.00 | 21.43 | 48749922.94 | 0.00 | 0.00 | 0.00 | 0.00 | 5030.97 | 04-FEB-16:01 | 5030.97 | 04-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.209808E+09 | 0.00 | 72.21 | 0.209780E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5035.10 | 28-MAR-18:02 | 5035.10 | 28-MAR-18:02 | 0.00 | 0.00 | 0.00 |
April | 0.714528E+09 | 0.00 | 236.13 | 0.685206E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5038.32 | 18-APR-15:02 | 5038.32 | 18-APR-15:02 | 0.00 | 0.00 | 0.00 |
May | 0.184891E+10 | 0.00 | 557.08 | 0.141824E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5368.48 | 26-MAY-08:61 | 5038.97 | 11-MAY-15:01 | 0.00 | 0.00 | 0.00 |
June | 0.231464E+10 | 0.00 | 605.57 | 0.147221E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6123.41 | 19-JUN-18:01 | 5038.80 | 16-JUN-15:02 | 0.00 | 0.00 | 0.00 |
July | 0.301288E+10 | 0.00 | 688.12 | 0.181631E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6119.71 | 22-JUL-08:61 | 4855.37 | 24-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.237326E+10 | 0.00 | 642.86 | 0.136824E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6023.32 | 30-AUG-08:62 | 4846.11 | 07-AUG-15:02 | 0.00 | 0.00 | 0.00 |
September | 0.113912E+10 | 0.00 | 448.52 | 0.726649E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5822.45 | 18-SEP-18:01 | 5038.61 | 25-SEP-18:01 | 0.00 | 0.00 | 0.00 |
October | 0.346179E+09 | 0.00 | 145.28 | 0.263745E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5038.53 | 21-OCT-15:02 | 5038.53 | 21-OCT-15:02 | 0.00 | 0.00 | 0.00 |
November | 9727771.89 | 0.00 | 8.08 | 9439859.85 | 0.00 | 0.00 | 0.00 | 0.00 | 5029.72 | 17-NOV-16:01 | 5029.72 | 17-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 189426.49 | 0.00 | 0.28 | 189426.49 | 0.00 | 0.00 | 0.00 | 0.00 | 514.73 | 28-DEC-16:04 | 514.73 | 28-DEC-16:04 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.120186E+11 | 0.00 | 3426.02 | 0.801939E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 189426.49 | 0.00 | 0.28 | 189426.49 | 0.00 | 0.00 | 0.00 | 0.00 | 514.73 | 514.73 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.301288E+10 | 0.00 | 688.12 | 0.181631E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6123.41 | 5038.97 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 156991.87 | 0.00 | 0.15 | 156991.87 | 0.00 | 0.00 | 0.00 | 0.00 | 732.63 | 17-JAN-16:04 | 732.63 | 17-JAN-16:04 | 0.00 | 0.00 | 0.00 |
February | 6367175.92 | 0.00 | 6.18 | 6367175.92 | 0.00 | 0.00 | 0.00 | 0.00 | 2434.91 | 28-FEB-16:02 | 2434.91 | 28-FEB-16:02 | 0.00 | 0.00 | 0.00 |
March | 82746700.58 | 0.00 | 39.78 | 82729639.85 | 0.00 | 0.00 | 0.00 | 0.00 | 4779.34 | 28-MAR-18:02 | 4779.34 | 28-MAR-18:02 | 0.00 | 0.00 | 0.00 |
April | 0.440938E+09 | 0.00 | 157.33 | 0.420414E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4782.18 | 18-APR-15:02 | 4782.18 | 18-APR-15:02 | 0.00 | 0.00 | 0.00 |
May | 0.156692E+10 | 0.00 | 515.79 | 0.117649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5066.74 | 26-MAY-08:61 | 4782.84 | 11-MAY-15:01 | 0.00 | 0.00 | 0.00 |
June | 0.214269E+10 | 0.00 | 596.87 | 0.135909E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5709.01 | 25-JUN-08:61 | 4782.53 | 16-JUN-15:02 | 0.00 | 0.00 | 0.00 |
July | 0.274271E+10 | 0.00 | 681.98 | 0.162196E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5823.48 | 22-JUL-08:61 | 4622.07 | 18-JUL-15:02 | 0.00 | 0.00 | 0.00 |
August | 0.197105E+10 | 0.00 | 627.55 | 0.107760E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5644.09 | 30-AUG-08:62 | 4592.10 | 30-AUG-15:02 | 0.00 | 0.00 | 0.00 |
September | 0.754992E+09 | 0.00 | 358.51 | 0.464082E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5519.97 | 18-SEP-18:01 | 4782.91 | 06-SEP-15:01 | 0.00 | 0.00 | 0.00 |
October | 0.131387E+09 | 0.00 | 71.20 | 0.104339E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4782.28 | 21-OCT-15:02 | 4782.28 | 21-OCT-15:02 | 0.00 | 0.00 | 0.00 |
November | 1961849.86 | 0.00 | 1.41 | 1631576.94 | 0.00 | 0.00 | 0.00 | 0.00 | 827.19 | 15-NOV-19:04 | 827.19 | 15-NOV-19:04 | 0.00 | 0.00 | 0.00 |
December | 4014.15 | 0.00 | 0.02 | 4014.15 | 0.00 | 0.00 | 0.00 | 0.00 | 46.83 | 17-DEC-09:04 | 46.83 | 17-DEC-09:04 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.984192E+10 | 0.00 | 3056.77 | 0.631485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 4014.15 | 0.00 | 0.02 | 4014.15 | 0.00 | 0.00 | 0.00 | 0.00 | 46.83 | 46.83 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.274271E+10 | 0.00 | 681.98 | 0.162196E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5823.48 | 4782.91 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.632935E+09 | 0.00 | 46.58 | 0.632935E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 24716.07 | 27-JAN-16:01 | 24716.07 | 27-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.196386E+10 | 0.00 | 137.03 | 0.196386E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24757.59 | 21-FEB-16:02 | 24757.59 | 21-FEB-16:02 | 0.00 | 0.00 | 0.00 |
March | 0.279005E+10 | 0.00 | 185.13 | 0.279005E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24760.39 | 26-MAR-18:01 | 24760.39 | 26-MAR-18:01 | 0.00 | 0.00 | 0.00 |
April | 0.523213E+10 | 0.00 | 348.60 | 0.504739E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24776.45 | 18-APR-15:02 | 24776.45 | 18-APR-15:02 | 0.00 | 0.00 | 0.00 |
May | 0.950798E+10 | 0.00 | 600.50 | 0.715071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26000.20 | 26-MAY-08:61 | 24772.36 | 09-MAY-15:01 | 0.00 | 0.00 | 0.00 |
June | 0.115555E+11 | 0.00 | 632.41 | 0.694249E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31464.36 | 19-JUN-18:01 | 24776.73 | 04-JUN-15:02 | 0.00 | 0.00 | 0.00 |
July | 0.150538E+11 | 0.00 | 683.74 | 0.878655E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30995.45 | 25-JUL-18:02 | 23702.89 | 06-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.137940E+11 | 0.00 | 657.65 | 0.807845E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29463.18 | 30-AUG-08:62 | 23936.58 | 12-AUG-18:01 | 0.00 | 0.00 | 0.00 |
September | 0.889837E+10 | 0.00 | 542.64 | 0.592335E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28151.74 | 18-SEP-18:01 | 24778.30 | 23-SEP-15:02 | 0.00 | 0.00 | 0.00 |
October | 0.463353E+10 | 0.00 | 303.34 | 0.371179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24776.29 | 01-OCT-15:01 | 24776.29 | 01-OCT-15:01 | 0.00 | 0.00 | 0.00 |
November | 0.132545E+10 | 0.00 | 106.49 | 0.130276E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24740.36 | 16-NOV-16:02 | 24740.36 | 16-NOV-16:02 | 0.00 | 0.00 | 0.00 |
December | 0.321599E+09 | 0.00 | 29.28 | 0.321599E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 24714.64 | 02-DEC-16:01 | 24714.64 | 02-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.757092E+11 | 0.00 | 4273.39 | 0.526519E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.321599E+09 | 0.00 | 29.28 | 0.321599E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 24714.64 | 23702.89 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.150538E+11 | 0.00 | 683.74 | 0.878655E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31464.36 | 24778.30 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 957.48 | 666.94 | 290.54 | 856.91 | 774.24 | 0.00 | 0.00 | 0.00 |
February | 1196.15 | 804.58 | 391.58 | 1163.50 | 689.46 | 0.00 | 0.00 | 0.00 |
March | 1052.49 | 662.62 | 389.87 | 1041.81 | 578.49 | 0.00 | 0.00 | 0.00 |
April | 962.07 | 522.14 | 439.93 | 1037.15 | 374.03 | 0.00 | 0.00 | 0.00 |
May | 823.67 | 291.34 | 532.33 | 986.24 | 186.41 | 0.00 | 0.00 | 0.00 |
June | 723.78 | 191.46 | 532.32 | 931.80 | 113.29 | 0.00 | 0.00 | 0.00 |
July | 796.43 | 254.27 | 542.17 | 1062.37 | 97.18 | 0.00 | 0.00 | 0.00 |
August | 844.86 | 351.86 | 493.00 | 1085.21 | 117.02 | 0.00 | 0.00 | 0.00 |
September | 890.64 | 466.29 | 424.35 | 1051.44 | 216.63 | 0.00 | 0.00 | 0.00 |
October | 791.15 | 471.57 | 319.58 | 826.77 | 359.09 | 0.00 | 0.00 | 0.00 |
November | 690.53 | 432.74 | 257.79 | 635.02 | 543.83 | 0.00 | 0.00 | 0.00 |
December | 735.39 | 482.18 | 253.21 | 610.99 | 766.29 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 870.00 | 464.41 | 405.58 | 939.23 | 399.94 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 690.53 | 191.46 | 253.21 | 610.99 | 97.18 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1196.15 | 804.58 | 542.17 | 1163.50 | 774.24 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2696.21 | 1878.05 | 818.15 | 2402.63 | 2182.39 | 0.00 | 0.00 | 0.00 |
February | 3368.29 | 2265.64 | 1102.65 | 3264.61 | 1932.60 | 0.00 | 0.00 | 0.00 |
March | 2963.73 | 1865.90 | 1097.84 | 2923.11 | 1618.89 | 0.00 | 0.00 | 0.00 |
April | 2709.13 | 1470.30 | 1238.82 | 2912.60 | 1040.11 | 0.00 | 0.00 | 0.00 |
May | 2319.39 | 820.40 | 1499.00 | 2774.26 | 508.75 | 0.00 | 0.00 | 0.00 |
June | 2038.11 | 539.13 | 1498.98 | 2622.93 | 305.65 | 0.00 | 0.00 | 0.00 |
July | 2242.71 | 716.00 | 1526.70 | 2993.06 | 258.52 | 0.00 | 0.00 | 0.00 |
August | 2379.07 | 990.81 | 1388.26 | 3055.11 | 314.34 | 0.00 | 0.00 | 0.00 |
September | 2507.98 | 1313.05 | 1194.93 | 2956.56 | 594.79 | 0.00 | 0.00 | 0.00 |
October | 2227.83 | 1327.92 | 899.92 | 2321.10 | 999.19 | 0.00 | 0.00 | 0.00 |
November | 1944.49 | 1218.58 | 725.91 | 1778.77 | 1524.25 | 0.00 | 0.00 | 0.00 |
December | 2070.81 | 1357.79 | 713.02 | 1712.07 | 2158.08 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2449.85 | 1307.76 | 1142.09 | 2638.79 | 1115.90 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1944.49 | 539.13 | 713.02 | 1712.07 | 258.52 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3368.29 | 2265.64 | 1526.70 | 3264.61 | 2182.39 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 3502.53 | 2439.70 | 1062.83 | 3154.22 | 2934.83 | 0.00 | 0.00 | 0.00 |
February | 4375.60 | 2943.19 | 1432.41 | 4292.46 | 2584.62 | 0.00 | 0.00 | 0.00 |
March | 3850.06 | 2423.91 | 1426.15 | 3848.17 | 2156.97 | 0.00 | 0.00 | 0.00 |
April | 3519.31 | 1910.01 | 1609.30 | 3843.13 | 1384.22 | 0.00 | 0.00 | 0.00 |
May | 3013.03 | 1065.74 | 1947.28 | 3665.76 | 686.11 | 0.00 | 0.00 | 0.00 |
June | 2647.62 | 700.36 | 1947.26 | 3464.90 | 419.22 | 0.00 | 0.00 | 0.00 |
July | 2913.40 | 930.13 | 1983.28 | 3953.83 | 356.45 | 0.00 | 0.00 | 0.00 |
August | 3090.54 | 1287.11 | 1803.43 | 4036.08 | 428.92 | 0.00 | 0.00 | 0.00 |
September | 3258.00 | 1705.72 | 1552.28 | 3904.33 | 796.71 | 0.00 | 0.00 | 0.00 |
October | 2894.08 | 1725.04 | 1169.04 | 3061.82 | 1333.31 | 0.00 | 0.00 | 0.00 |
November | 2526.00 | 1583.00 | 943.00 | 2338.66 | 2037.83 | 0.00 | 0.00 | 0.00 |
December | 2690.10 | 1763.84 | 926.26 | 2241.29 | 2909.88 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3182.50 | 1698.85 | 1483.64 | 3478.13 | 1497.29 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 2526.00 | 700.36 | 926.26 | 2241.29 | 356.45 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4375.60 | 2943.19 | 1983.28 | 4292.46 | 2934.83 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 189.31 | 131.87 | 57.45 | 165.35 | 173.66 | 0.00 | 0.00 | 0.00 |
February | 236.50 | 159.08 | 77.42 | 228.36 | 145.57 | 0.00 | 0.00 | 0.00 |
March | 208.10 | 131.01 | 77.08 | 205.83 | 119.01 | 0.00 | 0.00 | 0.00 |
April | 190.22 | 103.24 | 86.98 | 203.64 | 76.93 | 0.00 | 0.00 | 0.00 |
May | 162.85 | 57.60 | 105.25 | 191.40 | 38.84 | 0.00 | 0.00 | 0.00 |
June | 143.10 | 37.85 | 105.25 | 180.69 | 23.62 | 0.00 | 0.00 | 0.00 |
July | 157.47 | 50.27 | 107.20 | 206.44 | 20.45 | 0.00 | 0.00 | 0.00 |
August | 167.04 | 69.57 | 97.48 | 211.62 | 24.36 | 0.00 | 0.00 | 0.00 |
September | 176.09 | 92.19 | 83.90 | 206.08 | 44.75 | 0.00 | 0.00 | 0.00 |
October | 156.42 | 93.24 | 63.19 | 163.59 | 72.68 | 0.00 | 0.00 | 0.00 |
November | 136.53 | 85.56 | 50.97 | 125.99 | 109.68 | 0.00 | 0.00 | 0.00 |
December | 145.40 | 95.34 | 50.06 | 117.73 | 168.09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 172.01 | 91.82 | 80.19 | 183.58 | 84.54 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 136.53 | 37.85 | 50.06 | 117.73 | 20.45 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 236.50 | 159.08 | 107.20 | 228.36 | 173.66 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 114.71 | 48.59 | 66.11 | 52.02 | 371.59 | 0.00 | 0.00 | 0.00 |
February | 185.50 | 85.16 | 100.34 | 123.98 | 299.30 | 0.00 | 0.00 | 0.00 |
March | 243.24 | 124.74 | 118.51 | 196.78 | 232.27 | 0.00 | 0.00 | 0.00 |
April | 310.38 | 157.39 | 152.99 | 301.13 | 140.83 | 0.00 | 0.00 | 0.00 |
May | 381.67 | 182.52 | 199.15 | 437.14 | 70.59 | 0.00 | 0.00 | 0.00 |
June | 366.76 | 158.34 | 208.43 | 448.02 | 43.38 | 0.00 | 0.00 | 0.00 |
July | 392.11 | 182.30 | 209.81 | 492.81 | 37.81 | 0.00 | 0.00 | 0.00 |
August | 321.88 | 145.81 | 176.06 | 392.44 | 45.14 | 0.00 | 0.00 | 0.00 |
September | 252.67 | 113.39 | 139.28 | 275.14 | 83.00 | 0.00 | 0.00 | 0.00 |
October | 159.86 | 64.33 | 95.53 | 137.42 | 140.04 | 0.00 | 0.00 | 0.00 |
November | 97.31 | 33.11 | 64.20 | 52.64 | 222.70 | 0.00 | 0.00 | 0.00 |
December | 85.79 | 29.76 | 56.03 | 29.05 | 359.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 242.97 | 110.61 | 132.37 | 245.61 | 169.97 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 85.79 | 29.76 | 56.03 | 29.05 | 37.81 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 392.11 | 182.52 | 209.81 | 492.81 | 371.59 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 27.33 | 0.00 | 27.33 | 0.45 | 214.48 | 0.00 | 0.00 | 0.00 |
February | 41.98 | 0.00 | 41.98 | 4.48 | 169.63 | 0.00 | 0.00 | 0.00 |
March | 51.66 | 0.00 | 51.66 | 11.69 | 129.70 | 0.00 | 0.00 | 0.00 |
April | 67.94 | 0.71 | 67.23 | 37.10 | 75.75 | 0.00 | 0.00 | 0.00 |
May | 95.31 | 5.09 | 90.21 | 91.96 | 35.18 | 0.00 | 0.00 | 0.00 |
June | 106.53 | 11.91 | 94.62 | 124.38 | 21.88 | 0.00 | 0.00 | 0.00 |
July | 101.84 | 8.99 | 92.85 | 123.87 | 19.15 | 0.00 | 0.00 | 0.00 |
August | 77.31 | 1.48 | 75.82 | 86.15 | 23.35 | 0.00 | 0.00 | 0.00 |
September | 60.18 | 0.06 | 60.12 | 51.39 | 44.62 | 0.00 | 0.00 | 0.00 |
October | 41.72 | 0.00 | 41.72 | 19.79 | 76.31 | 0.00 | 0.00 | 0.00 |
November | 27.62 | 0.00 | 27.62 | 3.48 | 124.15 | 0.00 | 0.00 | 0.00 |
December | 23.15 | 0.00 | 23.15 | 0.03 | 205.63 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 60.30 | 2.36 | 57.94 | 46.49 | 94.68 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 23.15 | 0.00 | 23.15 | 0.03 | 19.15 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 106.53 | 11.91 | 94.62 | 124.38 | 214.48 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 114.71 | 48.59 | 66.11 | 53.57 | 369.66 | 0.00 | 0.00 | 0.00 |
February | 185.50 | 85.16 | 100.34 | 128.10 | 296.55 | 0.00 | 0.00 | 0.00 |
March | 243.24 | 124.74 | 118.51 | 201.21 | 229.63 | 0.00 | 0.00 | 0.00 |
April | 310.38 | 157.39 | 152.99 | 305.57 | 139.45 | 0.00 | 0.00 | 0.00 |
May | 381.67 | 182.52 | 199.15 | 439.27 | 70.09 | 0.00 | 0.00 | 0.00 |
June | 366.76 | 158.34 | 208.43 | 449.14 | 43.10 | 0.00 | 0.00 | 0.00 |
July | 392.11 | 182.30 | 209.81 | 494.23 | 37.43 | 0.00 | 0.00 | 0.00 |
August | 321.88 | 145.81 | 176.06 | 394.61 | 44.56 | 0.00 | 0.00 | 0.00 |
September | 252.67 | 113.39 | 139.28 | 278.34 | 82.02 | 0.00 | 0.00 | 0.00 |
October | 159.86 | 64.33 | 95.53 | 140.53 | 138.49 | 0.00 | 0.00 | 0.00 |
November | 97.31 | 33.11 | 64.20 | 55.13 | 220.77 | 0.00 | 0.00 | 0.00 |
December | 85.79 | 29.76 | 56.03 | 30.01 | 358.06 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 242.97 | 110.61 | 132.37 | 248.19 | 168.63 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 85.79 | 29.76 | 56.03 | 30.01 | 37.43 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 392.11 | 182.52 | 209.81 | 494.23 | 369.66 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 151.42 | 105.47 | 45.95 | 130.92 | 137.77 | 0.00 | 0.00 | 0.00 |
February | 189.16 | 127.24 | 61.93 | 180.46 | 118.51 | 0.00 | 0.00 | 0.00 |
March | 166.44 | 104.79 | 61.65 | 162.52 | 98.79 | 0.00 | 0.00 | 0.00 |
April | 152.14 | 82.57 | 69.57 | 160.00 | 67.56 | 0.00 | 0.00 | 0.00 |
May | 130.26 | 46.07 | 84.18 | 150.82 | 35.92 | 0.00 | 0.00 | 0.00 |
June | 114.46 | 30.28 | 84.18 | 141.86 | 23.11 | 0.00 | 0.00 | 0.00 |
July | 125.95 | 40.21 | 85.74 | 163.10 | 20.31 | 0.00 | 0.00 | 0.00 |
August | 133.61 | 55.64 | 77.97 | 167.01 | 24.49 | 0.00 | 0.00 | 0.00 |
September | 140.85 | 73.74 | 67.11 | 161.91 | 42.17 | 0.00 | 0.00 | 0.00 |
October | 125.12 | 74.58 | 50.54 | 127.59 | 65.11 | 0.00 | 0.00 | 0.00 |
November | 109.20 | 68.43 | 40.77 | 98.87 | 90.74 | 0.00 | 0.00 | 0.00 |
December | 116.30 | 76.25 | 40.04 | 93.40 | 132.38 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 137.58 | 73.44 | 64.14 | 144.62 | 71.19 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 109.20 | 30.28 | 40.04 | 93.40 | 20.31 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 189.16 | 127.24 | 85.74 | 180.46 | 137.77 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 21.87 | 0.00 | 21.87 | 0.23 | 177.75 | 0.00 | 0.00 | 0.00 |
February | 33.59 | 0.00 | 33.59 | 3.08 | 139.97 | 0.00 | 0.00 | 0.00 |
March | 41.33 | 0.00 | 41.33 | 8.84 | 106.27 | 0.00 | 0.00 | 0.00 |
April | 54.36 | 0.56 | 53.79 | 30.14 | 61.50 | 0.00 | 0.00 | 0.00 |
May | 76.25 | 4.07 | 72.18 | 76.03 | 27.87 | 0.00 | 0.00 | 0.00 |
June | 85.24 | 9.53 | 75.71 | 102.11 | 17.16 | 0.00 | 0.00 | 0.00 |
July | 81.48 | 7.19 | 74.29 | 102.26 | 14.63 | 0.00 | 0.00 | 0.00 |
August | 61.85 | 1.19 | 60.67 | 71.37 | 18.18 | 0.00 | 0.00 | 0.00 |
September | 48.15 | 0.05 | 48.10 | 42.13 | 35.79 | 0.00 | 0.00 | 0.00 |
October | 33.38 | 0.00 | 33.38 | 15.10 | 63.19 | 0.00 | 0.00 | 0.00 |
November | 22.10 | 0.00 | 22.10 | 2.27 | 104.03 | 0.00 | 0.00 | 0.00 |
December | 18.53 | 0.00 | 18.53 | 0.00 | 170.60 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 48.25 | 1.89 | 46.36 | 38.01 | 77.83 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 18.53 | 0.00 | 18.53 | 0.00 | 14.63 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 85.24 | 9.53 | 75.71 | 102.26 | 177.75 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 111.63 | 46.33 | 65.30 | 44.96 | 366.43 | 0.00 | 0.00 | 0.00 |
February | 177.32 | 76.29 | 101.03 | 106.50 | 289.36 | 0.00 | 0.00 | 0.00 |
March | 240.89 | 121.07 | 119.82 | 185.96 | 224.63 | 0.00 | 0.00 | 0.00 |
April | 331.70 | 178.76 | 152.95 | 323.08 | 135.36 | 0.00 | 0.00 | 0.00 |
May | 360.29 | 158.83 | 201.46 | 405.95 | 66.13 | 0.00 | 0.00 | 0.00 |
June | 406.53 | 194.36 | 212.17 | 497.25 | 41.47 | 0.00 | 0.00 | 0.00 |
July | 399.08 | 187.66 | 211.42 | 499.38 | 35.76 | 0.00 | 0.00 | 0.00 |
August | 307.20 | 134.19 | 173.01 | 371.07 | 43.57 | 0.00 | 0.00 | 0.00 |
September | 246.70 | 110.66 | 136.04 | 265.32 | 80.46 | 0.00 | 0.00 | 0.00 |
October | 148.58 | 55.87 | 92.70 | 119.89 | 136.60 | 0.00 | 0.00 | 0.00 |
November | 95.22 | 31.74 | 63.47 | 47.18 | 218.58 | 0.00 | 0.00 | 0.00 |
December | 87.56 | 32.91 | 54.65 | 28.40 | 355.45 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 242.96 | 110.81 | 132.16 | 241.89 | 165.66 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 87.56 | 31.74 | 54.65 | 28.40 | 35.76 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 406.53 | 194.36 | 212.17 | 499.38 | 366.43 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 189.31 | 131.87 | 57.45 | 165.20 | 173.44 | 0.00 | 0.00 | 0.00 |
February | 236.50 | 159.08 | 77.42 | 228.05 | 145.23 | 0.00 | 0.00 | 0.00 |
March | 208.10 | 131.01 | 77.08 | 204.82 | 118.56 | 0.00 | 0.00 | 0.00 |
April | 190.22 | 103.24 | 86.98 | 202.23 | 76.57 | 0.00 | 0.00 | 0.00 |
May | 162.85 | 57.60 | 105.25 | 190.87 | 38.38 | 0.00 | 0.00 | 0.00 |
June | 143.10 | 37.85 | 105.25 | 179.44 | 23.31 | 0.00 | 0.00 | 0.00 |
July | 157.47 | 50.27 | 107.20 | 205.74 | 19.98 | 0.00 | 0.00 | 0.00 |
August | 167.04 | 69.57 | 97.48 | 211.26 | 24.01 | 0.00 | 0.00 | 0.00 |
September | 176.09 | 92.19 | 83.90 | 205.60 | 44.32 | 0.00 | 0.00 | 0.00 |
October | 156.42 | 93.24 | 63.19 | 163.36 | 72.34 | 0.00 | 0.00 | 0.00 |
November | 136.53 | 85.56 | 50.97 | 125.88 | 109.51 | 0.00 | 0.00 | 0.00 |
December | 145.40 | 95.34 | 50.06 | 117.57 | 167.99 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 172.01 | 91.82 | 80.19 | 183.02 | 84.20 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 136.53 | 37.85 | 50.06 | 117.57 | 19.98 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 236.50 | 159.08 | 107.20 | 228.05 | 173.44 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 27.33 | 0.00 | 27.33 | 0.44 | 214.37 | 0.00 | 0.00 | 0.00 |
February | 41.98 | 0.00 | 41.98 | 4.29 | 169.45 | 0.00 | 0.00 | 0.00 |
March | 51.66 | 0.00 | 51.66 | 11.04 | 129.50 | 0.00 | 0.00 | 0.00 |
April | 67.94 | 0.71 | 67.23 | 35.63 | 75.80 | 0.00 | 0.00 | 0.00 |
May | 95.31 | 5.09 | 90.21 | 91.33 | 34.86 | 0.00 | 0.00 | 0.00 |
June | 106.53 | 11.91 | 94.62 | 123.12 | 21.67 | 0.00 | 0.00 | 0.00 |
July | 101.84 | 8.99 | 92.85 | 123.21 | 18.79 | 0.00 | 0.00 | 0.00 |
August | 77.31 | 1.48 | 75.82 | 85.67 | 23.02 | 0.00 | 0.00 | 0.00 |
September | 60.18 | 0.06 | 60.12 | 50.65 | 44.26 | 0.00 | 0.00 | 0.00 |
October | 41.72 | 0.00 | 41.72 | 19.39 | 75.89 | 0.00 | 0.00 | 0.00 |
November | 27.62 | 0.00 | 27.62 | 3.37 | 124.09 | 0.00 | 0.00 | 0.00 |
December | 23.15 | 0.00 | 23.15 | 0.03 | 205.52 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 60.30 | 2.36 | 57.94 | 45.94 | 94.46 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 23.15 | 0.00 | 23.15 | 0.03 | 18.79 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 106.53 | 11.91 | 94.62 | 123.21 | 214.37 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 111.63 | 46.33 | 65.30 | 45.91 | 363.83 | 0.00 | 0.00 | 0.00 |
February | 177.32 | 76.29 | 101.03 | 109.46 | 285.37 | 0.00 | 0.00 | 0.00 |
March | 240.89 | 121.07 | 119.82 | 189.81 | 221.13 | 0.00 | 0.00 | 0.00 |
April | 331.70 | 178.76 | 152.95 | 326.69 | 133.85 | 0.00 | 0.00 | 0.00 |
May | 360.29 | 158.83 | 201.46 | 407.80 | 65.64 | 0.00 | 0.00 | 0.00 |
June | 406.53 | 194.36 | 212.17 | 498.33 | 41.24 | 0.00 | 0.00 | 0.00 |
July | 399.08 | 187.66 | 211.42 | 500.79 | 35.43 | 0.00 | 0.00 | 0.00 |
August | 307.20 | 134.19 | 173.01 | 373.08 | 42.99 | 0.00 | 0.00 | 0.00 |
September | 246.70 | 110.66 | 136.04 | 268.00 | 79.44 | 0.00 | 0.00 | 0.00 |
October | 148.58 | 55.87 | 92.70 | 122.71 | 134.80 | 0.00 | 0.00 | 0.00 |
November | 95.22 | 31.74 | 63.47 | 48.63 | 215.74 | 0.00 | 0.00 | 0.00 |
December | 87.56 | 32.91 | 54.65 | 28.94 | 353.60 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 242.96 | 110.81 | 132.16 | 243.98 | 163.94 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 87.56 | 31.74 | 54.65 | 28.94 | 35.43 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 406.53 | 194.36 | 212.17 | 500.79 | 363.83 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.61 | 0.00 | 34.61 | 0.30 | 273.10 | 0.00 | 0.00 | 0.00 |
February | 53.16 | 0.00 | 53.16 | 4.31 | 223.62 | 0.00 | 0.00 | 0.00 |
March | 65.42 | 0.00 | 65.42 | 13.21 | 171.23 | 0.00 | 0.00 | 0.00 |
April | 86.04 | 0.89 | 85.14 | 47.96 | 97.88 | 0.00 | 0.00 | 0.00 |
May | 120.70 | 6.45 | 114.25 | 123.12 | 43.91 | 0.00 | 0.00 | 0.00 |
June | 134.92 | 15.08 | 119.83 | 165.00 | 26.87 | 0.00 | 0.00 | 0.00 |
July | 128.98 | 11.38 | 117.59 | 164.40 | 23.55 | 0.00 | 0.00 | 0.00 |
August | 97.90 | 1.88 | 96.02 | 115.42 | 28.84 | 0.00 | 0.00 | 0.00 |
September | 76.21 | 0.08 | 76.13 | 68.30 | 56.41 | 0.00 | 0.00 | 0.00 |
October | 52.83 | 0.00 | 52.83 | 24.08 | 100.42 | 0.00 | 0.00 | 0.00 |
November | 34.98 | 0.00 | 34.98 | 3.46 | 167.91 | 0.00 | 0.00 | 0.00 |
December | 29.32 | 0.00 | 29.32 | 0.00 | 266.19 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 76.37 | 2.99 | 73.38 | 61.15 | 122.90 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 29.32 | 0.00 | 29.32 | 0.00 | 23.55 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 134.92 | 15.08 | 119.83 | 165.00 | 273.10 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 12.76 | 0.00 | 12.76 | 0.11 | 100.68 | 0.00 | 0.00 | 0.00 |
February | 19.60 | 0.00 | 19.60 | 1.59 | 82.43 | 0.00 | 0.00 | 0.00 |
March | 24.12 | 0.00 | 24.12 | 4.87 | 63.12 | 0.00 | 0.00 | 0.00 |
April | 31.72 | 0.33 | 31.39 | 17.68 | 36.08 | 0.00 | 0.00 | 0.00 |
May | 44.49 | 2.38 | 42.12 | 45.39 | 16.19 | 0.00 | 0.00 | 0.00 |
June | 49.74 | 5.56 | 44.18 | 60.83 | 9.91 | 0.00 | 0.00 | 0.00 |
July | 47.55 | 4.20 | 43.35 | 60.60 | 8.68 | 0.00 | 0.00 | 0.00 |
August | 36.09 | 0.69 | 35.40 | 42.55 | 10.63 | 0.00 | 0.00 | 0.00 |
September | 28.10 | 0.03 | 28.07 | 25.18 | 20.79 | 0.00 | 0.00 | 0.00 |
October | 19.48 | 0.00 | 19.48 | 8.88 | 37.02 | 0.00 | 0.00 | 0.00 |
November | 12.90 | 0.00 | 12.90 | 1.28 | 61.90 | 0.00 | 0.00 | 0.00 |
December | 10.81 | 0.00 | 10.81 | 0.00 | 98.13 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 28.15 | 1.10 | 27.05 | 22.54 | 45.31 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 10.81 | 0.00 | 10.81 | 0.00 | 8.68 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 49.74 | 5.56 | 44.18 | 60.83 | 100.68 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 88.33 | 61.53 | 26.80 | 77.48 | 80.34 | 0.00 | 0.00 | 0.00 |
February | 110.35 | 74.23 | 36.12 | 106.56 | 69.34 | 0.00 | 0.00 | 0.00 |
March | 97.10 | 61.13 | 35.97 | 96.27 | 56.95 | 0.00 | 0.00 | 0.00 |
April | 88.76 | 48.17 | 40.59 | 96.33 | 36.18 | 0.00 | 0.00 | 0.00 |
May | 75.99 | 26.88 | 49.11 | 92.08 | 17.70 | 0.00 | 0.00 | 0.00 |
June | 66.77 | 17.66 | 49.11 | 87.15 | 10.66 | 0.00 | 0.00 | 0.00 |
July | 73.47 | 23.46 | 50.02 | 99.28 | 9.22 | 0.00 | 0.00 | 0.00 |
August | 77.94 | 32.46 | 45.48 | 101.52 | 10.94 | 0.00 | 0.00 | 0.00 |
September | 82.17 | 43.02 | 39.15 | 98.13 | 20.61 | 0.00 | 0.00 | 0.00 |
October | 72.99 | 43.50 | 29.48 | 76.86 | 34.74 | 0.00 | 0.00 | 0.00 |
November | 63.70 | 39.92 | 23.78 | 58.37 | 53.52 | 0.00 | 0.00 | 0.00 |
December | 67.84 | 44.48 | 23.36 | 54.76 | 79.24 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 80.26 | 42.84 | 37.42 | 86.93 | 39.82 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 63.70 | 17.66 | 23.36 | 54.76 | 9.22 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 110.35 | 74.23 | 50.02 | 106.56 | 80.34 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 239.75 | 167.00 | 72.75 | 210.30 | 218.05 | 0.00 | 0.00 | 0.00 |
February | 299.51 | 201.46 | 98.05 | 289.23 | 188.21 | 0.00 | 0.00 | 0.00 |
March | 263.54 | 165.92 | 97.62 | 261.31 | 154.58 | 0.00 | 0.00 | 0.00 |
April | 240.90 | 130.74 | 110.16 | 261.45 | 98.20 | 0.00 | 0.00 | 0.00 |
May | 206.24 | 72.95 | 133.29 | 249.93 | 48.03 | 0.00 | 0.00 | 0.00 |
June | 181.23 | 47.94 | 133.29 | 236.53 | 28.92 | 0.00 | 0.00 | 0.00 |
July | 199.43 | 63.67 | 135.76 | 269.46 | 25.02 | 0.00 | 0.00 | 0.00 |
August | 211.55 | 88.10 | 123.45 | 275.56 | 29.70 | 0.00 | 0.00 | 0.00 |
September | 223.01 | 116.76 | 106.26 | 266.33 | 55.94 | 0.00 | 0.00 | 0.00 |
October | 198.10 | 118.08 | 80.02 | 208.62 | 94.29 | 0.00 | 0.00 | 0.00 |
November | 172.91 | 108.36 | 64.55 | 158.42 | 145.27 | 0.00 | 0.00 | 0.00 |
December | 184.14 | 120.74 | 63.40 | 148.64 | 215.07 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 217.84 | 116.29 | 101.56 | 235.94 | 108.07 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 172.91 | 47.94 | 63.40 | 148.64 | 25.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 299.51 | 201.46 | 135.76 | 289.23 | 218.05 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 189.31 | 131.87 | 57.45 | 164.78 | 174.22 | 0.00 | 0.00 | 0.00 |
February | 236.50 | 159.08 | 77.42 | 227.77 | 145.42 | 0.00 | 0.00 | 0.00 |
March | 208.10 | 131.01 | 77.08 | 205.51 | 118.71 | 0.00 | 0.00 | 0.00 |
April | 190.22 | 103.24 | 86.98 | 202.94 | 76.75 | 0.00 | 0.00 | 0.00 |
May | 162.85 | 57.60 | 105.25 | 189.97 | 38.99 | 0.00 | 0.00 | 0.00 |
June | 143.10 | 37.85 | 105.25 | 179.21 | 23.74 | 0.00 | 0.00 | 0.00 |
July | 157.47 | 50.27 | 107.20 | 204.96 | 20.57 | 0.00 | 0.00 | 0.00 |
August | 167.04 | 69.57 | 97.48 | 210.15 | 24.54 | 0.00 | 0.00 | 0.00 |
September | 176.09 | 92.19 | 83.90 | 204.97 | 44.86 | 0.00 | 0.00 | 0.00 |
October | 156.42 | 93.24 | 63.19 | 163.33 | 72.24 | 0.00 | 0.00 | 0.00 |
November | 136.53 | 85.56 | 50.97 | 125.94 | 109.10 | 0.00 | 0.00 | 0.00 |
December | 145.40 | 95.34 | 50.06 | 117.30 | 168.48 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 172.01 | 91.82 | 80.19 | 182.75 | 84.54 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 136.53 | 37.85 | 50.06 | 117.30 | 20.57 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 236.50 | 159.08 | 107.20 | 227.77 | 174.22 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 114.71 | 48.59 | 66.11 | 51.64 | 373.10 | 0.00 | 0.00 | 0.00 |
February | 185.50 | 85.16 | 100.34 | 123.60 | 299.23 | 0.00 | 0.00 | 0.00 |
March | 243.24 | 124.74 | 118.51 | 196.30 | 231.65 | 0.00 | 0.00 | 0.00 |
April | 310.38 | 157.39 | 152.99 | 299.73 | 140.40 | 0.00 | 0.00 | 0.00 |
May | 381.67 | 182.52 | 199.15 | 434.28 | 70.75 | 0.00 | 0.00 | 0.00 |
June | 366.76 | 158.34 | 208.43 | 445.02 | 43.56 | 0.00 | 0.00 | 0.00 |
July | 392.11 | 182.30 | 209.81 | 489.75 | 37.97 | 0.00 | 0.00 | 0.00 |
August | 321.88 | 145.81 | 176.06 | 389.80 | 45.43 | 0.00 | 0.00 | 0.00 |
September | 252.67 | 113.39 | 139.28 | 273.28 | 83.09 | 0.00 | 0.00 | 0.00 |
October | 159.86 | 64.33 | 95.53 | 137.16 | 139.11 | 0.00 | 0.00 | 0.00 |
November | 97.31 | 33.11 | 64.20 | 52.88 | 221.57 | 0.00 | 0.00 | 0.00 |
December | 85.79 | 29.76 | 56.03 | 28.85 | 360.61 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 242.97 | 110.61 | 132.37 | 244.24 | 170.01 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 85.79 | 29.76 | 56.03 | 28.85 | 37.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 392.11 | 182.52 | 209.81 | 489.75 | 373.10 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 27.33 | 0.00 | 27.33 | 0.44 | 215.29 | 0.00 | 0.00 | 0.00 |
February | 41.98 | 0.00 | 41.98 | 4.57 | 169.54 | 0.00 | 0.00 | 0.00 |
March | 51.66 | 0.00 | 51.66 | 11.78 | 129.45 | 0.00 | 0.00 | 0.00 |
April | 67.94 | 0.71 | 67.23 | 37.01 | 75.56 | 0.00 | 0.00 | 0.00 |
May | 95.31 | 5.09 | 90.21 | 90.78 | 35.30 | 0.00 | 0.00 | 0.00 |
June | 106.53 | 11.91 | 94.62 | 123.10 | 22.00 | 0.00 | 0.00 | 0.00 |
July | 101.84 | 8.99 | 92.85 | 122.69 | 19.27 | 0.00 | 0.00 | 0.00 |
August | 77.31 | 1.48 | 75.82 | 85.17 | 23.50 | 0.00 | 0.00 | 0.00 |
September | 60.18 | 0.06 | 60.12 | 50.89 | 44.66 | 0.00 | 0.00 | 0.00 |
October | 41.72 | 0.00 | 41.72 | 20.04 | 75.71 | 0.00 | 0.00 | 0.00 |
November | 27.62 | 0.00 | 27.62 | 3.63 | 123.38 | 0.00 | 0.00 | 0.00 |
December | 23.15 | 0.00 | 23.15 | 0.03 | 206.16 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 60.30 | 2.36 | 57.94 | 46.10 | 94.68 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 23.15 | 0.00 | 23.15 | 0.03 | 19.27 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 106.53 | 11.91 | 94.62 | 123.10 | 215.29 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 114.71 | 48.59 | 66.11 | 53.17 | 371.37 | 0.00 | 0.00 | 0.00 |
February | 185.50 | 85.16 | 100.34 | 127.69 | 296.57 | 0.00 | 0.00 | 0.00 |
March | 243.24 | 124.74 | 118.51 | 200.82 | 229.05 | 0.00 | 0.00 | 0.00 |
April | 310.38 | 157.39 | 152.99 | 304.47 | 138.91 | 0.00 | 0.00 | 0.00 |
May | 381.67 | 182.52 | 199.15 | 436.42 | 70.23 | 0.00 | 0.00 | 0.00 |
June | 366.76 | 158.34 | 208.43 | 446.13 | 43.27 | 0.00 | 0.00 | 0.00 |
July | 392.11 | 182.30 | 209.81 | 491.18 | 37.59 | 0.00 | 0.00 | 0.00 |
August | 321.88 | 145.81 | 176.06 | 391.98 | 44.82 | 0.00 | 0.00 | 0.00 |
September | 252.67 | 113.39 | 139.28 | 276.63 | 82.02 | 0.00 | 0.00 | 0.00 |
October | 159.86 | 64.33 | 95.53 | 140.59 | 137.38 | 0.00 | 0.00 | 0.00 |
November | 97.31 | 33.11 | 64.20 | 55.40 | 219.74 | 0.00 | 0.00 | 0.00 |
December | 85.79 | 29.76 | 56.03 | 29.80 | 359.38 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 242.97 | 110.61 | 132.37 | 246.90 | 168.68 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 85.79 | 29.76 | 56.03 | 29.80 | 37.59 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 392.11 | 182.52 | 209.81 | 491.18 | 371.37 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 277.64 | 193.39 | 84.25 | 234.82 | 261.67 | 0.00 | 0.00 | 0.00 |
February | 346.85 | 233.30 | 113.55 | 326.42 | 219.15 | 0.00 | 0.00 | 0.00 |
March | 305.19 | 192.14 | 113.05 | 295.98 | 178.25 | 0.00 | 0.00 | 0.00 |
April | 278.97 | 151.40 | 127.57 | 294.67 | 113.94 | 0.00 | 0.00 | 0.00 |
May | 238.84 | 84.48 | 154.36 | 279.49 | 56.48 | 0.00 | 0.00 | 0.00 |
June | 209.88 | 55.52 | 154.36 | 264.61 | 34.16 | 0.00 | 0.00 | 0.00 |
July | 230.94 | 73.73 | 157.21 | 302.76 | 29.15 | 0.00 | 0.00 | 0.00 |
August | 244.99 | 102.03 | 142.96 | 309.00 | 35.46 | 0.00 | 0.00 | 0.00 |
September | 258.26 | 135.21 | 123.05 | 299.11 | 66.32 | 0.00 | 0.00 | 0.00 |
October | 229.41 | 136.74 | 92.67 | 236.01 | 108.94 | 0.00 | 0.00 | 0.00 |
November | 200.23 | 125.48 | 74.75 | 179.84 | 165.18 | 0.00 | 0.00 | 0.00 |
December | 213.24 | 139.82 | 73.42 | 166.80 | 253.01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 252.27 | 134.67 | 117.61 | 265.36 | 126.40 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 200.23 | 55.52 | 73.42 | 166.80 | 29.15 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 346.85 | 233.30 | 157.21 | 326.42 | 261.67 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 191.29 | 0.00 | 191.29 | 1.72 | 1416.07 | 0.00 | 0.00 | 0.00 |
February | 293.84 | 0.00 | 293.84 | 25.42 | 1177.52 | 0.00 | 0.00 | 0.00 |
March | 361.60 | 0.01 | 361.59 | 74.86 | 918.78 | 0.00 | 0.00 | 0.00 |
April | 475.54 | 4.94 | 470.60 | 266.71 | 535.05 | 0.00 | 0.00 | 0.00 |
May | 667.11 | 35.64 | 631.47 | 679.82 | 246.03 | 0.00 | 0.00 | 0.00 |
June | 745.70 | 83.37 | 662.33 | 910.86 | 154.45 | 0.00 | 0.00 | 0.00 |
July | 712.87 | 62.93 | 649.95 | 914.29 | 132.17 | 0.00 | 0.00 | 0.00 |
August | 541.12 | 10.39 | 530.73 | 641.26 | 163.42 | 0.00 | 0.00 | 0.00 |
September | 421.24 | 0.44 | 420.80 | 378.58 | 312.34 | 0.00 | 0.00 | 0.00 |
October | 292.01 | 0.00 | 292.01 | 134.35 | 546.40 | 0.00 | 0.00 | 0.00 |
November | 193.35 | 0.00 | 193.35 | 19.36 | 911.52 | 0.00 | 0.00 | 0.00 |
December | 162.08 | 0.00 | 162.08 | 0.01 | 1393.62 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 422.12 | 16.55 | 405.57 | 339.21 | 656.67 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 162.08 | 0.00 | 162.08 | 0.01 | 132.17 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 745.70 | 83.37 | 662.33 | 914.29 | 1416.07 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 191.29 | 0.00 | 191.29 | 1.55 | 1424.97 | 0.00 | 0.00 | 0.00 |
February | 293.84 | 0.00 | 293.84 | 24.32 | 1187.38 | 0.00 | 0.00 | 0.00 |
March | 361.60 | 0.01 | 361.59 | 72.67 | 929.70 | 0.00 | 0.00 | 0.00 |
April | 475.54 | 4.94 | 470.60 | 261.27 | 544.70 | 0.00 | 0.00 | 0.00 |
May | 667.11 | 35.64 | 631.47 | 670.56 | 252.88 | 0.00 | 0.00 | 0.00 |
June | 745.70 | 83.37 | 662.33 | 900.29 | 160.62 | 0.00 | 0.00 | 0.00 |
July | 712.87 | 62.93 | 649.95 | 904.11 | 138.33 | 0.00 | 0.00 | 0.00 |
August | 541.12 | 10.39 | 530.73 | 632.78 | 170.95 | 0.00 | 0.00 | 0.00 |
September | 421.24 | 0.44 | 420.80 | 372.32 | 321.57 | 0.00 | 0.00 | 0.00 |
October | 292.01 | 0.00 | 292.01 | 130.67 | 557.57 | 0.00 | 0.00 | 0.00 |
November | 193.35 | 0.00 | 193.35 | 18.39 | 924.60 | 0.00 | 0.00 | 0.00 |
December | 162.08 | 0.00 | 162.08 | 0.00 | 1403.64 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 422.12 | 16.55 | 405.57 | 334.33 | 665.78 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 162.08 | 0.00 | 162.08 | 0.00 | 138.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 745.70 | 83.37 | 662.33 | 904.11 | 1424.97 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 27.33 | 0.00 | 27.33 | 1.71 | 161.89 | 0.00 | 0.00 | 0.00 |
February | 41.98 | 0.00 | 41.98 | 9.56 | 138.86 | 0.00 | 0.00 | 0.00 |
March | 51.66 | 0.00 | 51.66 | 20.67 | 109.64 | 0.00 | 0.00 | 0.00 |
April | 67.94 | 0.71 | 67.23 | 56.23 | 65.87 | 0.00 | 0.00 | 0.00 |
May | 95.31 | 5.09 | 90.21 | 125.32 | 31.30 | 0.00 | 0.00 | 0.00 |
June | 106.53 | 11.91 | 94.62 | 159.95 | 19.64 | 0.00 | 0.00 | 0.00 |
July | 101.84 | 8.99 | 92.85 | 161.25 | 16.27 | 0.00 | 0.00 | 0.00 |
August | 77.31 | 1.48 | 75.82 | 119.72 | 18.65 | 0.00 | 0.00 | 0.00 |
September | 60.18 | 0.06 | 60.12 | 76.43 | 35.44 | 0.00 | 0.00 | 0.00 |
October | 41.72 | 0.00 | 41.72 | 34.54 | 61.78 | 0.00 | 0.00 | 0.00 |
November | 27.62 | 0.00 | 27.62 | 8.49 | 103.98 | 0.00 | 0.00 | 0.00 |
December | 23.15 | 0.00 | 23.15 | 0.78 | 159.23 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 60.30 | 2.36 | 57.94 | 64.89 | 76.60 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 23.15 | 0.00 | 23.15 | 0.78 | 16.27 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 106.53 | 11.91 | 94.62 | 161.25 | 161.89 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 223.25 | 92.66 | 130.59 | 129.30 | 562.94 | 0.00 | 0.00 | 0.00 |
February | 354.62 | 152.58 | 202.05 | 265.30 | 480.22 | 0.00 | 0.00 | 0.00 |
March | 481.75 | 242.13 | 239.62 | 433.27 | 383.24 | 0.00 | 0.00 | 0.00 |
April | 663.36 | 357.49 | 305.87 | 741.69 | 238.53 | 0.00 | 0.00 | 0.00 |
May | 720.53 | 317.64 | 402.89 | 941.86 | 117.21 | 0.00 | 0.00 | 0.00 |
June | 813.01 | 388.69 | 424.32 | 1132.44 | 73.68 | 0.00 | 0.00 | 0.00 |
July | 798.10 | 375.29 | 422.81 | 1143.46 | 61.01 | 0.00 | 0.00 | 0.00 |
August | 614.36 | 268.36 | 346.00 | 873.55 | 69.93 | 0.00 | 0.00 | 0.00 |
September | 493.36 | 221.30 | 272.06 | 638.85 | 131.00 | 0.00 | 0.00 | 0.00 |
October | 297.13 | 111.73 | 185.40 | 312.26 | 224.80 | 0.00 | 0.00 | 0.00 |
November | 190.42 | 63.48 | 126.94 | 129.64 | 367.67 | 0.00 | 0.00 | 0.00 |
December | 175.11 | 65.81 | 109.30 | 86.53 | 558.65 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 485.89 | 221.60 | 264.30 | 570.50 | 271.46 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 175.11 | 63.48 | 109.30 | 86.53 | 61.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 813.01 | 388.69 | 424.32 | 1143.46 | 562.94 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 189.31 | 131.87 | 57.45 | 185.08 | 136.64 | 0.00 | 0.00 | 0.00 |
February | 236.50 | 159.08 | 77.42 | 247.21 | 123.13 | 0.00 | 0.00 | 0.00 |
March | 208.10 | 131.01 | 77.08 | 223.99 | 102.42 | 0.00 | 0.00 | 0.00 |
April | 190.22 | 103.24 | 86.98 | 226.87 | 66.28 | 0.00 | 0.00 | 0.00 |
May | 162.85 | 57.60 | 105.25 | 224.63 | 32.92 | 0.00 | 0.00 | 0.00 |
June | 143.10 | 37.85 | 105.25 | 215.88 | 20.45 | 0.00 | 0.00 | 0.00 |
July | 157.47 | 50.27 | 107.20 | 243.96 | 16.80 | 0.00 | 0.00 | 0.00 |
August | 167.04 | 69.57 | 97.48 | 245.86 | 18.84 | 0.00 | 0.00 | 0.00 |
September | 176.09 | 92.19 | 83.90 | 234.02 | 35.40 | 0.00 | 0.00 | 0.00 |
October | 156.42 | 93.24 | 63.19 | 184.09 | 59.98 | 0.00 | 0.00 | 0.00 |
November | 136.53 | 85.56 | 50.97 | 139.43 | 94.48 | 0.00 | 0.00 | 0.00 |
December | 145.40 | 95.34 | 50.06 | 133.83 | 135.14 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 172.01 | 91.82 | 80.19 | 208.47 | 69.95 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 136.53 | 37.85 | 50.06 | 133.83 | 16.80 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 236.50 | 159.08 | 107.20 | 247.21 | 136.64 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.61 | 0.00 | 34.61 | 0.26 | 264.42 | 0.00 | 0.00 | 0.00 |
February | 53.16 | 0.00 | 53.16 | 4.03 | 221.43 | 0.00 | 0.00 | 0.00 |
March | 65.42 | 0.00 | 65.42 | 12.43 | 171.78 | 0.00 | 0.00 | 0.00 |
April | 86.04 | 0.89 | 85.14 | 46.35 | 98.67 | 0.00 | 0.00 | 0.00 |
May | 120.70 | 6.45 | 114.25 | 120.95 | 44.22 | 0.00 | 0.00 | 0.00 |
June | 134.92 | 15.08 | 119.83 | 162.96 | 27.03 | 0.00 | 0.00 | 0.00 |
July | 128.98 | 11.38 | 117.59 | 163.14 | 23.18 | 0.00 | 0.00 | 0.00 |
August | 97.90 | 1.88 | 96.02 | 113.67 | 28.95 | 0.00 | 0.00 | 0.00 |
September | 76.21 | 0.08 | 76.13 | 66.59 | 57.13 | 0.00 | 0.00 | 0.00 |
October | 52.83 | 0.00 | 52.83 | 22.97 | 101.41 | 0.00 | 0.00 | 0.00 |
November | 34.98 | 0.00 | 34.98 | 3.23 | 169.46 | 0.00 | 0.00 | 0.00 |
December | 29.32 | 0.00 | 29.32 | 0.00 | 260.30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 76.37 | 2.99 | 73.38 | 60.06 | 121.89 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 29.32 | 0.00 | 29.32 | 0.00 | 23.18 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 134.92 | 15.08 | 119.83 | 163.14 | 264.42 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 30.97 | 0.00 | 30.97 | 0.24 | 236.53 | 0.00 | 0.00 | 0.00 |
February | 47.57 | 0.00 | 47.57 | 3.60 | 198.11 | 0.00 | 0.00 | 0.00 |
March | 58.53 | 0.00 | 58.53 | 11.12 | 153.70 | 0.00 | 0.00 | 0.00 |
April | 76.98 | 0.80 | 76.18 | 41.47 | 88.28 | 0.00 | 0.00 | 0.00 |
May | 107.99 | 5.77 | 102.22 | 108.21 | 39.56 | 0.00 | 0.00 | 0.00 |
June | 120.71 | 13.50 | 107.21 | 145.80 | 24.18 | 0.00 | 0.00 | 0.00 |
July | 115.40 | 10.19 | 105.21 | 145.96 | 20.74 | 0.00 | 0.00 | 0.00 |
August | 87.59 | 1.68 | 85.91 | 101.70 | 25.90 | 0.00 | 0.00 | 0.00 |
September | 68.19 | 0.07 | 68.12 | 59.58 | 51.12 | 0.00 | 0.00 | 0.00 |
October | 47.27 | 0.00 | 47.27 | 20.55 | 90.73 | 0.00 | 0.00 | 0.00 |
November | 31.30 | 0.00 | 31.30 | 2.89 | 151.61 | 0.00 | 0.00 | 0.00 |
December | 26.24 | 0.00 | 26.24 | 0.00 | 232.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 68.33 | 2.68 | 65.65 | 53.74 | 109.05 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 26.24 | 0.00 | 26.24 | 0.00 | 20.74 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 120.71 | 13.50 | 107.21 | 145.96 | 236.53 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 706.75 | 492.29 | 214.46 | 623.86 | 624.03 | 0.00 | 0.00 | 0.00 |
February | 882.93 | 593.89 | 289.04 | 848.92 | 548.91 | 0.00 | 0.00 | 0.00 |
March | 776.88 | 489.11 | 287.78 | 764.94 | 456.13 | 0.00 | 0.00 | 0.00 |
April | 710.14 | 385.41 | 324.73 | 763.88 | 291.68 | 0.00 | 0.00 | 0.00 |
May | 607.98 | 215.05 | 392.93 | 729.26 | 142.79 | 0.00 | 0.00 | 0.00 |
June | 534.25 | 141.32 | 392.93 | 690.30 | 86.02 | 0.00 | 0.00 | 0.00 |
July | 587.88 | 187.68 | 400.20 | 789.17 | 72.68 | 0.00 | 0.00 | 0.00 |
August | 623.62 | 259.72 | 363.91 | 805.19 | 88.14 | 0.00 | 0.00 | 0.00 |
September | 657.42 | 344.19 | 313.23 | 777.99 | 167.33 | 0.00 | 0.00 | 0.00 |
October | 583.98 | 348.09 | 235.90 | 609.57 | 280.67 | 0.00 | 0.00 | 0.00 |
November | 509.71 | 319.42 | 190.28 | 462.57 | 431.41 | 0.00 | 0.00 | 0.00 |
December | 542.82 | 355.92 | 186.90 | 440.69 | 621.39 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 642.18 | 342.80 | 299.38 | 691.11 | 316.50 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 509.71 | 141.32 | 186.90 | 440.69 | 72.68 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 882.93 | 593.89 | 400.20 | 848.92 | 624.03 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.256452E+10 | 0.178633E+10 | 0.778194E+09 | 0.229515E+10 | 0.207373E+10 |
February | 0.289374E+10 | 0.194644E+10 | 0.947301E+09 | 0.281474E+10 | 0.166795E+10 |
March | 0.281898E+10 | 0.177477E+10 | 0.104422E+10 | 0.279038E+10 | 0.154944E+10 |
April | 0.249369E+10 | 0.135338E+10 | 0.114031E+10 | 0.268828E+10 | 0.969482E+09 |
May | 0.220611E+10 | 0.780327E+09 | 0.142579E+10 | 0.264156E+10 | 0.499287E+09 |
June | 0.187603E+10 | 0.496257E+09 | 0.137978E+10 | 0.241521E+10 | 0.293658E+09 |
July | 0.213317E+10 | 0.681032E+09 | 0.145214E+10 | 0.284545E+10 | 0.260282E+09 |
August | 0.226287E+10 | 0.942414E+09 | 0.132045E+10 | 0.290663E+10 | 0.313414E+09 |
September | 0.230853E+10 | 0.120863E+10 | 0.109990E+10 | 0.272532E+10 | 0.561508E+09 |
October | 0.211902E+10 | 0.126306E+10 | 0.855962E+09 | 0.221441E+10 | 0.961778E+09 |
November | 0.178985E+10 | 0.112167E+10 | 0.668184E+09 | 0.164596E+10 | 0.140961E+10 |
December | 0.196967E+10 | 0.129147E+10 | 0.678197E+09 | 0.163648E+10 | 0.205244E+10 |
Annual Sum or Average | 0.274362E+11 | 0.146458E+11 | 0.127904E+11 | 0.296196E+11 | 0.126126E+11 |
Minimum of Months | 0.178985E+10 | 0.496257E+09 | 0.668184E+09 | 0.163648E+10 | 0.260282E+09 |
Maximum of Months | 0.289374E+10 | 0.194644E+10 | 0.145214E+10 | 0.290663E+10 | 0.207373E+10 |
Report: WindowEnergyReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.722152E+10 | 0.503018E+10 | 0.219134E+10 | 0.643519E+10 | 0.584530E+10 |
February | 0.814857E+10 | 0.548103E+10 | 0.266754E+10 | 0.789775E+10 | 0.467534E+10 |
March | 0.793806E+10 | 0.499762E+10 | 0.294044E+10 | 0.782926E+10 | 0.433604E+10 |
April | 0.702205E+10 | 0.381102E+10 | 0.321103E+10 | 0.754947E+10 | 0.269598E+10 |
May | 0.621227E+10 | 0.219735E+10 | 0.401492E+10 | 0.743057E+10 | 0.136264E+10 |
June | 0.528278E+10 | 0.139743E+10 | 0.388536E+10 | 0.679864E+10 | 0.792257E+09 |
July | 0.600687E+10 | 0.191774E+10 | 0.408912E+10 | 0.801661E+10 | 0.692415E+09 |
August | 0.637209E+10 | 0.265378E+10 | 0.371831E+10 | 0.818281E+10 | 0.841931E+09 |
September | 0.650068E+10 | 0.340342E+10 | 0.309726E+10 | 0.766341E+10 | 0.154171E+10 |
October | 0.596703E+10 | 0.355670E+10 | 0.241033E+10 | 0.621683E+10 | 0.267623E+10 |
November | 0.504011E+10 | 0.315855E+10 | 0.188156E+10 | 0.461057E+10 | 0.395086E+10 |
December | 0.554646E+10 | 0.363670E+10 | 0.190976E+10 | 0.458562E+10 | 0.578020E+10 |
Annual Sum or Average | 0.772585E+11 | 0.412415E+11 | 0.360170E+11 | 0.832167E+11 | 0.351909E+11 |
Minimum of Months | 0.504011E+10 | 0.139743E+10 | 0.188156E+10 | 0.458562E+10 | 0.692415E+09 |
Maximum of Months | 0.814857E+10 | 0.548103E+10 | 0.408912E+10 | 0.818281E+10 | 0.584530E+10 |
Report: WindowEnergyReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.938116E+10 | 0.653449E+10 | 0.284668E+10 | 0.844826E+10 | 0.786066E+10 |
February | 0.105855E+11 | 0.712017E+10 | 0.346528E+10 | 0.103843E+11 | 0.625271E+10 |
March | 0.103120E+11 | 0.649219E+10 | 0.381980E+10 | 0.103069E+11 | 0.577723E+10 |
April | 0.912205E+10 | 0.495073E+10 | 0.417132E+10 | 0.996140E+10 | 0.358791E+10 |
May | 0.807009E+10 | 0.285448E+10 | 0.521561E+10 | 0.981838E+10 | 0.183769E+10 |
June | 0.686263E+10 | 0.181534E+10 | 0.504730E+10 | 0.898103E+10 | 0.108661E+10 |
July | 0.780326E+10 | 0.249126E+10 | 0.531200E+10 | 0.105899E+11 | 0.954711E+09 |
August | 0.827770E+10 | 0.344741E+10 | 0.483030E+10 | 0.108102E+11 | 0.114882E+10 |
September | 0.844475E+10 | 0.442123E+10 | 0.402351E+10 | 0.101200E+11 | 0.206508E+10 |
October | 0.775151E+10 | 0.462035E+10 | 0.313116E+10 | 0.820079E+10 | 0.357113E+10 |
November | 0.654739E+10 | 0.410313E+10 | 0.244426E+10 | 0.606181E+10 | 0.528207E+10 |
December | 0.720517E+10 | 0.472428E+10 | 0.248089E+10 | 0.600307E+10 | 0.779381E+10 |
Annual Sum or Average | 0.100363E+12 | 0.535751E+11 | 0.467881E+11 | 0.109686E+12 | 0.472184E+11 |
Minimum of Months | 0.654739E+10 | 0.181534E+10 | 0.244426E+10 | 0.600307E+10 | 0.954711E+09 |
Maximum of Months | 0.105855E+11 | 0.712017E+10 | 0.531200E+10 | 0.108102E+11 | 0.786066E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.507050E+09 | 0.353187E+09 | 0.153863E+09 | 0.442871E+09 | 0.465140E+09 |
February | 0.572142E+09 | 0.384844E+09 | 0.187299E+09 | 0.552446E+09 | 0.352154E+09 |
March | 0.557363E+09 | 0.350902E+09 | 0.206461E+09 | 0.551298E+09 | 0.318746E+09 |
April | 0.493047E+09 | 0.267586E+09 | 0.225461E+09 | 0.527836E+09 | 0.199407E+09 |
May | 0.436189E+09 | 0.154284E+09 | 0.281905E+09 | 0.512656E+09 | 0.104018E+09 |
June | 0.370926E+09 | 98118509.68 | 0.272808E+09 | 0.468343E+09 | 61217137.34 |
July | 0.421767E+09 | 0.134652E+09 | 0.287115E+09 | 0.552928E+09 | 54782976.26 |
August | 0.447410E+09 | 0.186331E+09 | 0.261079E+09 | 0.566792E+09 | 65249735.39 |
September | 0.456438E+09 | 0.238967E+09 | 0.217472E+09 | 0.534165E+09 | 0.115995E+09 |
October | 0.418968E+09 | 0.249729E+09 | 0.169239E+09 | 0.438147E+09 | 0.194676E+09 |
November | 0.353885E+09 | 0.221773E+09 | 0.132112E+09 | 0.326561E+09 | 0.284297E+09 |
December | 0.389438E+09 | 0.255346E+09 | 0.134092E+09 | 0.315321E+09 | 0.450225E+09 |
Annual Sum or Average | 0.542462E+10 | 0.289572E+10 | 0.252891E+10 | 0.578936E+10 | 0.266591E+10 |
Minimum of Months | 0.353885E+09 | 98118509.68 | 0.132112E+09 | 0.315321E+09 | 54782976.26 |
Maximum of Months | 0.572142E+09 | 0.384844E+09 | 0.287115E+09 | 0.566792E+09 | 0.465140E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.307231E+09 | 0.130149E+09 | 0.177082E+09 | 0.139320E+09 | 0.995257E+09 |
February | 0.448761E+09 | 0.206014E+09 | 0.242747E+09 | 0.299934E+09 | 0.724069E+09 |
March | 0.651502E+09 | 0.334092E+09 | 0.317410E+09 | 0.527057E+09 | 0.622119E+09 |
April | 0.804500E+09 | 0.407943E+09 | 0.396557E+09 | 0.780537E+09 | 0.365038E+09 |
May | 0.102228E+10 | 0.488871E+09 | 0.533405E+09 | 0.117084E+10 | 0.189072E+09 |
June | 0.950654E+09 | 0.410413E+09 | 0.540241E+09 | 0.116127E+10 | 0.112453E+09 |
July | 0.105023E+10 | 0.488269E+09 | 0.561960E+09 | 0.131995E+10 | 0.101261E+09 |
August | 0.862115E+09 | 0.390544E+09 | 0.471571E+09 | 0.105110E+10 | 0.120907E+09 |
September | 0.654928E+09 | 0.293903E+09 | 0.361025E+09 | 0.713155E+09 | 0.215135E+09 |
October | 0.428161E+09 | 0.172305E+09 | 0.255855E+09 | 0.368056E+09 | 0.375090E+09 |
November | 0.252239E+09 | 85826290.04 | 0.166413E+09 | 0.136438E+09 | 0.577245E+09 |
December | 0.229790E+09 | 79717529.27 | 0.150073E+09 | 77820277.44 | 0.962449E+09 |
Annual Sum or Average | 0.766239E+10 | 0.348805E+10 | 0.417434E+10 | 0.774548E+10 | 0.536009E+10 |
Minimum of Months | 0.229790E+09 | 79717529.27 | 0.150073E+09 | 77820277.44 | 0.101261E+09 |
Maximum of Months | 0.105023E+10 | 0.488871E+09 | 0.561960E+09 | 0.131995E+10 | 0.995257E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 73196226.91 | 0.00 | 73196226.91 | 1199887.89 | 0.574457E+09 |
February | 0.101554E+09 | 0.00 | 0.101554E+09 | 10849979.04 | 0.410375E+09 |
March | 0.138364E+09 | 5398.29 | 0.138358E+09 | 31308924.10 | 0.347387E+09 |
April | 0.176094E+09 | 1829975.10 | 0.174264E+09 | 96153028.49 | 0.196347E+09 |
May | 0.255266E+09 | 13638445.42 | 0.241628E+09 | 0.246308E+09 | 94218900.25 |
June | 0.276133E+09 | 30872694.36 | 0.245260E+09 | 0.322402E+09 | 56707603.97 |
July | 0.272775E+09 | 24077951.73 | 0.248697E+09 | 0.331784E+09 | 51289213.32 |
August | 0.207056E+09 | 3976857.93 | 0.203080E+09 | 0.230734E+09 | 62549628.47 |
September | 0.155985E+09 | 163465.80 | 0.155821E+09 | 0.133209E+09 | 0.115651E+09 |
October | 0.111735E+09 | 0.00 | 0.111735E+09 | 53012119.30 | 0.204398E+09 |
November | 71596193.86 | 0.00 | 71596193.86 | 9015073.52 | 0.321803E+09 |
December | 62017652.81 | 0.00 | 62017652.81 | 92835.85 | 0.550747E+09 |
Annual Sum or Average | 0.190177E+10 | 74564788.63 | 0.182721E+10 | 0.146607E+10 | 0.298593E+10 |
Minimum of Months | 62017652.81 | 0.00 | 62017652.81 | 92835.85 | 51289213.32 |
Maximum of Months | 0.276133E+09 | 30872694.36 | 0.248697E+09 | 0.331784E+09 | 0.574457E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.307231E+09 | 0.130149E+09 | 0.177082E+09 | 0.143484E+09 | 0.990087E+09 |
February | 0.448761E+09 | 0.206014E+09 | 0.242747E+09 | 0.309903E+09 | 0.717412E+09 |
March | 0.651502E+09 | 0.334092E+09 | 0.317410E+09 | 0.538917E+09 | 0.615050E+09 |
April | 0.804500E+09 | 0.407943E+09 | 0.396557E+09 | 0.792042E+09 | 0.361455E+09 |
May | 0.102228E+10 | 0.488871E+09 | 0.533405E+09 | 0.117654E+10 | 0.187735E+09 |
June | 0.950654E+09 | 0.410413E+09 | 0.540241E+09 | 0.116417E+10 | 0.111702E+09 |
July | 0.105023E+10 | 0.488269E+09 | 0.561960E+09 | 0.132374E+10 | 0.100255E+09 |
August | 0.862115E+09 | 0.390544E+09 | 0.471571E+09 | 0.105692E+10 | 0.119345E+09 |
September | 0.654928E+09 | 0.293903E+09 | 0.361025E+09 | 0.721457E+09 | 0.212607E+09 |
October | 0.428161E+09 | 0.172305E+09 | 0.255855E+09 | 0.376404E+09 | 0.370937E+09 |
November | 0.252239E+09 | 85826290.04 | 0.166413E+09 | 0.142890E+09 | 0.572226E+09 |
December | 0.229790E+09 | 79717529.27 | 0.150073E+09 | 80379449.66 | 0.959024E+09 |
Annual Sum or Average | 0.766239E+10 | 0.348805E+10 | 0.417434E+10 | 0.782685E+10 | 0.531784E+10 |
Minimum of Months | 0.229790E+09 | 79717529.27 | 0.150073E+09 | 80379449.66 | 0.100255E+09 |
Maximum of Months | 0.105023E+10 | 0.488871E+09 | 0.561960E+09 | 0.132374E+10 | 0.990087E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.405560E+09 | 0.282494E+09 | 0.123066E+09 | 0.350644E+09 | 0.368994E+09 |
February | 0.457623E+09 | 0.307814E+09 | 0.149809E+09 | 0.436566E+09 | 0.286710E+09 |
March | 0.445801E+09 | 0.280665E+09 | 0.165136E+09 | 0.435299E+09 | 0.264606E+09 |
April | 0.394359E+09 | 0.214026E+09 | 0.180333E+09 | 0.414711E+09 | 0.175117E+09 |
May | 0.348882E+09 | 0.123403E+09 | 0.225479E+09 | 0.403944E+09 | 96209639.31 |
June | 0.296682E+09 | 78479200.34 | 0.218203E+09 | 0.367714E+09 | 59911379.90 |
July | 0.337347E+09 | 0.107700E+09 | 0.229647E+09 | 0.436860E+09 | 54409748.66 |
August | 0.357857E+09 | 0.149035E+09 | 0.208822E+09 | 0.447325E+09 | 65583945.47 |
September | 0.365078E+09 | 0.191135E+09 | 0.173943E+09 | 0.419673E+09 | 0.109307E+09 |
October | 0.335108E+09 | 0.199743E+09 | 0.135365E+09 | 0.341735E+09 | 0.174386E+09 |
November | 0.283052E+09 | 0.177383E+09 | 0.105669E+09 | 0.256259E+09 | 0.235194E+09 |
December | 0.311488E+09 | 0.204236E+09 | 0.107252E+09 | 0.250161E+09 | 0.354567E+09 |
Annual Sum or Average | 0.433884E+10 | 0.231611E+10 | 0.202272E+10 | 0.456089E+10 | 0.224500E+10 |
Minimum of Months | 0.283052E+09 | 78479200.34 | 0.105669E+09 | 0.250161E+09 | 54409748.66 |
Maximum of Months | 0.457623E+09 | 0.307814E+09 | 0.229647E+09 | 0.447325E+09 | 0.368994E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 58564743.59 | 0.00 | 58564743.59 | 622665.40 | 0.476076E+09 |
February | 81254233.52 | 0.00 | 81254233.52 | 7462055.86 | 0.338611E+09 |
March | 0.110706E+09 | 4319.21 | 0.110701E+09 | 23685849.52 | 0.284633E+09 |
April | 0.140894E+09 | 1464174.14 | 0.139430E+09 | 78130635.36 | 0.159416E+09 |
May | 0.204240E+09 | 10912202.62 | 0.193328E+09 | 0.203633E+09 | 74659799.57 |
June | 0.220936E+09 | 24701429.37 | 0.196234E+09 | 0.264657E+09 | 44470279.75 |
July | 0.218249E+09 | 19264914.72 | 0.198984E+09 | 0.273882E+09 | 39183449.02 |
August | 0.165667E+09 | 3181908.07 | 0.162485E+09 | 0.191151E+09 | 48689803.90 |
September | 0.124804E+09 | 130789.97 | 0.124674E+09 | 0.109211E+09 | 92759677.40 |
October | 89399861.49 | 0.00 | 89399861.49 | 40435324.73 | 0.169256E+09 |
November | 57284547.47 | 0.00 | 57284547.47 | 5874299.74 | 0.269643E+09 |
December | 49620698.88 | 0.00 | 49620698.88 | 10999.54 | 0.456931E+09 |
Annual Sum or Average | 0.152162E+10 | 59659738.10 | 0.146196E+10 | 0.119876E+10 | 0.245433E+10 |
Minimum of Months | 49620698.88 | 0.00 | 49620698.88 | 10999.54 | 39183449.02 |
Maximum of Months | 0.220936E+09 | 24701429.37 | 0.198984E+09 | 0.273882E+09 | 0.476076E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.299000E+09 | 0.124099E+09 | 0.174901E+09 | 0.120425E+09 | 0.981459E+09 |
February | 0.428982E+09 | 0.184569E+09 | 0.244413E+09 | 0.257647E+09 | 0.700026E+09 |
March | 0.645207E+09 | 0.324279E+09 | 0.320927E+09 | 0.498080E+09 | 0.601641E+09 |
April | 0.859773E+09 | 0.463340E+09 | 0.396434E+09 | 0.837436E+09 | 0.350854E+09 |
May | 0.964998E+09 | 0.425408E+09 | 0.539590E+09 | 0.108731E+10 | 0.177125E+09 |
June | 0.105373E+10 | 0.503777E+09 | 0.549953E+09 | 0.128886E+10 | 0.107487E+09 |
July | 0.106889E+10 | 0.502619E+09 | 0.566270E+09 | 0.133753E+10 | 95773630.59 |
August | 0.822805E+09 | 0.359411E+09 | 0.463394E+09 | 0.993882E+09 | 0.116706E+09 |
September | 0.639440E+09 | 0.286824E+09 | 0.352616E+09 | 0.687708E+09 | 0.208558E+09 |
October | 0.397946E+09 | 0.149645E+09 | 0.248301E+09 | 0.321102E+09 | 0.365879E+09 |
November | 0.246803E+09 | 82278208.38 | 0.164525E+09 | 0.122283E+09 | 0.566558E+09 |
December | 0.234521E+09 | 88133196.08 | 0.146388E+09 | 76054748.71 | 0.952034E+09 |
Annual Sum or Average | 0.766209E+10 | 0.349438E+10 | 0.416771E+10 | 0.762831E+10 | 0.522410E+10 |
Minimum of Months | 0.234521E+09 | 82278208.38 | 0.146388E+09 | 76054748.71 | 95773630.59 |
Maximum of Months | 0.106889E+10 | 0.503777E+09 | 0.566270E+09 | 0.133753E+10 | 0.981459E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.507050E+09 | 0.353187E+09 | 0.153863E+09 | 0.442479E+09 | 0.464548E+09 |
February | 0.572142E+09 | 0.384844E+09 | 0.187299E+09 | 0.551688E+09 | 0.351344E+09 |
March | 0.557363E+09 | 0.350902E+09 | 0.206461E+09 | 0.548584E+09 | 0.317538E+09 |
April | 0.493047E+09 | 0.267586E+09 | 0.225461E+09 | 0.524193E+09 | 0.198479E+09 |
May | 0.436189E+09 | 0.154284E+09 | 0.281905E+09 | 0.511214E+09 | 0.102808E+09 |
June | 0.370926E+09 | 98118509.68 | 0.272808E+09 | 0.465113E+09 | 60426660.05 |
July | 0.421767E+09 | 0.134652E+09 | 0.287115E+09 | 0.551066E+09 | 53518985.09 |
August | 0.447410E+09 | 0.186331E+09 | 0.261079E+09 | 0.565837E+09 | 64308641.12 |
September | 0.456438E+09 | 0.238967E+09 | 0.217472E+09 | 0.532917E+09 | 0.114885E+09 |
October | 0.418968E+09 | 0.249729E+09 | 0.169239E+09 | 0.437537E+09 | 0.193767E+09 |
November | 0.353885E+09 | 0.221773E+09 | 0.132112E+09 | 0.326285E+09 | 0.283860E+09 |
December | 0.389438E+09 | 0.255346E+09 | 0.134092E+09 | 0.314902E+09 | 0.449948E+09 |
Annual Sum or Average | 0.542462E+10 | 0.289572E+10 | 0.252891E+10 | 0.577182E+10 | 0.265543E+10 |
Minimum of Months | 0.353885E+09 | 98118509.68 | 0.132112E+09 | 0.314902E+09 | 53518985.09 |
Maximum of Months | 0.572142E+09 | 0.384844E+09 | 0.287115E+09 | 0.565837E+09 | 0.464548E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 73196226.91 | 0.00 | 73196226.91 | 1176803.20 | 0.574157E+09 |
February | 0.101554E+09 | 0.00 | 0.101554E+09 | 10373051.74 | 0.409923E+09 |
March | 0.138364E+09 | 5398.29 | 0.138358E+09 | 29567446.64 | 0.346850E+09 |
April | 0.176094E+09 | 1829975.10 | 0.174264E+09 | 92342037.45 | 0.196462E+09 |
May | 0.255266E+09 | 13638445.42 | 0.241628E+09 | 0.244614E+09 | 93363547.88 |
June | 0.276133E+09 | 30872694.36 | 0.245260E+09 | 0.319118E+09 | 56176673.84 |
July | 0.272775E+09 | 24077951.73 | 0.248697E+09 | 0.329993E+09 | 50330054.70 |
August | 0.207056E+09 | 3976857.93 | 0.203080E+09 | 0.229460E+09 | 61653610.18 |
September | 0.155985E+09 | 163465.80 | 0.155821E+09 | 0.131276E+09 | 0.114713E+09 |
October | 0.111735E+09 | 0.00 | 0.111735E+09 | 51939017.54 | 0.203252E+09 |
November | 71596193.86 | 0.00 | 71596193.86 | 8742673.89 | 0.321635E+09 |
December | 62017652.81 | 0.00 | 62017652.81 | 88468.19 | 0.550474E+09 |
Annual Sum or Average | 0.190177E+10 | 74564788.63 | 0.182721E+10 | 0.144869E+10 | 0.297899E+10 |
Minimum of Months | 62017652.81 | 0.00 | 62017652.81 | 88468.19 | 50330054.70 |
Maximum of Months | 0.276133E+09 | 30872694.36 | 0.248697E+09 | 0.329993E+09 | 0.574157E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.299000E+09 | 0.124099E+09 | 0.174901E+09 | 0.122960E+09 | 0.974490E+09 |
February | 0.428982E+09 | 0.184569E+09 | 0.244413E+09 | 0.264812E+09 | 0.690367E+09 |
March | 0.645207E+09 | 0.324279E+09 | 0.320927E+09 | 0.508379E+09 | 0.592269E+09 |
April | 0.859773E+09 | 0.463340E+09 | 0.396434E+09 | 0.846785E+09 | 0.346950E+09 |
May | 0.964998E+09 | 0.425408E+09 | 0.539590E+09 | 0.109225E+10 | 0.175812E+09 |
June | 0.105373E+10 | 0.503777E+09 | 0.549953E+09 | 0.129167E+10 | 0.106896E+09 |
July | 0.106889E+10 | 0.502619E+09 | 0.566270E+09 | 0.134132E+10 | 94903536.57 |
August | 0.822805E+09 | 0.359411E+09 | 0.463394E+09 | 0.999256E+09 | 0.115157E+09 |
September | 0.639440E+09 | 0.286824E+09 | 0.352616E+09 | 0.694659E+09 | 0.205899E+09 |
October | 0.397946E+09 | 0.149645E+09 | 0.248301E+09 | 0.328655E+09 | 0.361054E+09 |
November | 0.246803E+09 | 82278208.38 | 0.164525E+09 | 0.126039E+09 | 0.559188E+09 |
December | 0.234521E+09 | 88133196.08 | 0.146388E+09 | 77508344.29 | 0.947080E+09 |
Annual Sum or Average | 0.766209E+10 | 0.349438E+10 | 0.416771E+10 | 0.769429E+10 | 0.517007E+10 |
Minimum of Months | 0.234521E+09 | 82278208.38 | 0.146388E+09 | 77508344.29 | 94903536.57 |
Maximum of Months | 0.106889E+10 | 0.503777E+09 | 0.566270E+09 | 0.134132E+10 | 0.974490E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 92698402.95 | 0.00 | 92698402.95 | 803697.59 | 0.731464E+09 |
February | 0.128612E+09 | 0.00 | 0.128612E+09 | 10435796.16 | 0.540971E+09 |
March | 0.175229E+09 | 6836.60 | 0.175222E+09 | 35378970.29 | 0.458614E+09 |
April | 0.223012E+09 | 2317548.00 | 0.220694E+09 | 0.124308E+09 | 0.253697E+09 |
May | 0.323279E+09 | 17272230.58 | 0.306006E+09 | 0.329768E+09 | 0.117622E+09 |
June | 0.349705E+09 | 39098319.45 | 0.310607E+09 | 0.427690E+09 | 69647974.72 |
July | 0.345452E+09 | 30493206.63 | 0.314959E+09 | 0.440319E+09 | 63079381.64 |
August | 0.262224E+09 | 5036439.64 | 0.257187E+09 | 0.309151E+09 | 77245457.66 |
September | 0.197545E+09 | 207019.12 | 0.197338E+09 | 0.177037E+09 | 0.146213E+09 |
October | 0.141505E+09 | 0.00 | 0.141505E+09 | 64484765.94 | 0.268969E+09 |
November | 90672062.05 | 0.00 | 90672062.05 | 8974771.68 | 0.435234E+09 |
December | 78541444.19 | 0.00 | 78541444.19 | 3271.55 | 0.712969E+09 |
Annual Sum or Average | 0.240847E+10 | 94431600.03 | 0.231404E+10 | 0.192835E+10 | 0.387573E+10 |
Minimum of Months | 78541444.19 | 0.00 | 78541444.19 | 3271.55 | 63079381.64 |
Maximum of Months | 0.349705E+09 | 39098319.45 | 0.314959E+09 | 0.440319E+09 | 0.731464E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 34172469.67 | 0.00 | 34172469.67 | 296276.21 | 0.269648E+09 |
February | 47411764.49 | 0.00 | 47411764.49 | 3847066.58 | 0.199424E+09 |
March | 64596683.78 | 2520.25 | 64594163.53 | 13042153.38 | 0.169064E+09 |
April | 82211369.81 | 854344.16 | 81357025.66 | 45825067.02 | 93523363.91 |
May | 0.119174E+09 | 6367259.38 | 0.112807E+09 | 0.121566E+09 | 43360273.51 |
June | 0.128916E+09 | 14413259.48 | 0.114502E+09 | 0.157664E+09 | 25675127.38 |
July | 0.127348E+09 | 11241058.59 | 0.116107E+09 | 0.162320E+09 | 23253671.99 |
August | 96666571.17 | 1856640.19 | 94809930.98 | 0.113966E+09 | 28475874.18 |
September | 72823244.90 | 76315.82 | 72746929.08 | 65263125.89 | 53900050.73 |
October | 52164730.31 | 0.00 | 52164730.31 | 23771754.83 | 99153038.82 |
November | 33425476.51 | 0.00 | 33425476.51 | 3308472.46 | 0.160445E+09 |
December | 28953628.47 | 0.00 | 28953628.47 | 1206.03 | 0.262830E+09 |
Annual Sum or Average | 0.887864E+09 | 34811397.87 | 0.853052E+09 | 0.710871E+09 | 0.142875E+10 |
Minimum of Months | 28953628.47 | 0.00 | 28953628.47 | 1206.03 | 23253671.99 |
Maximum of Months | 0.128916E+09 | 14413259.48 | 0.116107E+09 | 0.162320E+09 | 0.269648E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.236588E+09 | 0.164796E+09 | 71791813.57 | 0.207521E+09 | 0.215175E+09 |
February | 0.266959E+09 | 0.179566E+09 | 87392835.18 | 0.257797E+09 | 0.167756E+09 |
March | 0.260063E+09 | 0.163729E+09 | 96333865.29 | 0.257859E+09 | 0.152544E+09 |
April | 0.230054E+09 | 0.124855E+09 | 0.105199E+09 | 0.249676E+09 | 93782388.13 |
May | 0.203524E+09 | 71988297.24 | 0.131536E+09 | 0.246629E+09 | 47399572.28 |
June | 0.173073E+09 | 45781701.23 | 0.127291E+09 | 0.225884E+09 | 27618766.71 |
July | 0.196795E+09 | 62827971.53 | 0.133967E+09 | 0.265909E+09 | 24688758.72 |
August | 0.208760E+09 | 86941480.81 | 0.121818E+09 | 0.271923E+09 | 29308426.70 |
September | 0.212972E+09 | 0.111501E+09 | 0.101471E+09 | 0.254342E+09 | 53421723.31 |
October | 0.195489E+09 | 0.116523E+09 | 78966456.61 | 0.205864E+09 | 93048648.76 |
November | 0.165121E+09 | 0.103479E+09 | 61642963.96 | 0.151289E+09 | 0.138725E+09 |
December | 0.181710E+09 | 0.119144E+09 | 62566686.01 | 0.146674E+09 | 0.212230E+09 |
Annual Sum or Average | 0.253111E+10 | 0.135113E+10 | 0.117998E+10 | 0.274137E+10 | 0.125570E+10 |
Minimum of Months | 0.165121E+09 | 45781701.23 | 61642963.96 | 0.146674E+09 | 24688758.72 |
Maximum of Months | 0.266959E+09 | 0.179566E+09 | 0.133967E+09 | 0.271923E+09 | 0.215175E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.642147E+09 | 0.447290E+09 | 0.194858E+09 | 0.563255E+09 | 0.584030E+09 |
February | 0.724582E+09 | 0.487380E+09 | 0.237202E+09 | 0.699714E+09 | 0.455323E+09 |
March | 0.705864E+09 | 0.444395E+09 | 0.261470E+09 | 0.699883E+09 | 0.414036E+09 |
April | 0.624412E+09 | 0.338881E+09 | 0.285532E+09 | 0.677672E+09 | 0.254545E+09 |
May | 0.552406E+09 | 0.195391E+09 | 0.357015E+09 | 0.669400E+09 | 0.128652E+09 |
June | 0.469755E+09 | 0.124261E+09 | 0.345494E+09 | 0.613094E+09 | 74962982.14 |
July | 0.534142E+09 | 0.170528E+09 | 0.363614E+09 | 0.721731E+09 | 67010341.15 |
August | 0.566617E+09 | 0.235977E+09 | 0.330640E+09 | 0.738053E+09 | 79549064.98 |
September | 0.578050E+09 | 0.302636E+09 | 0.275414E+09 | 0.690337E+09 | 0.144997E+09 |
October | 0.530597E+09 | 0.316266E+09 | 0.214331E+09 | 0.558758E+09 | 0.252553E+09 |
November | 0.448173E+09 | 0.280862E+09 | 0.167312E+09 | 0.410630E+09 | 0.376527E+09 |
December | 0.493199E+09 | 0.323380E+09 | 0.169819E+09 | 0.398104E+09 | 0.576037E+09 |
Annual Sum or Average | 0.686994E+10 | 0.366725E+10 | 0.320270E+10 | 0.744063E+10 | 0.340822E+10 |
Minimum of Months | 0.448173E+09 | 0.124261E+09 | 0.167312E+09 | 0.398104E+09 | 67010341.15 |
Maximum of Months | 0.724582E+09 | 0.487380E+09 | 0.363614E+09 | 0.738053E+09 | 0.584030E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.507050E+09 | 0.353187E+09 | 0.153863E+09 | 0.441336E+09 | 0.466621E+09 |
February | 0.572142E+09 | 0.384844E+09 | 0.187299E+09 | 0.551033E+09 | 0.351809E+09 |
March | 0.557363E+09 | 0.350902E+09 | 0.206461E+09 | 0.550432E+09 | 0.317953E+09 |
April | 0.493047E+09 | 0.267586E+09 | 0.225461E+09 | 0.526010E+09 | 0.198946E+09 |
May | 0.436189E+09 | 0.154284E+09 | 0.281905E+09 | 0.508802E+09 | 0.104432E+09 |
June | 0.370926E+09 | 98118509.68 | 0.272808E+09 | 0.464506E+09 | 61542788.20 |
July | 0.421767E+09 | 0.134652E+09 | 0.287115E+09 | 0.548952E+09 | 55082346.97 |
August | 0.447410E+09 | 0.186331E+09 | 0.261079E+09 | 0.562876E+09 | 65716297.35 |
September | 0.456438E+09 | 0.238967E+09 | 0.217472E+09 | 0.531273E+09 | 0.116272E+09 |
October | 0.418968E+09 | 0.249729E+09 | 0.169239E+09 | 0.437474E+09 | 0.193476E+09 |
November | 0.353885E+09 | 0.221773E+09 | 0.132112E+09 | 0.326430E+09 | 0.282799E+09 |
December | 0.389438E+09 | 0.255346E+09 | 0.134092E+09 | 0.314184E+09 | 0.451269E+09 |
Annual Sum or Average | 0.542462E+10 | 0.289572E+10 | 0.252891E+10 | 0.576331E+10 | 0.266592E+10 |
Minimum of Months | 0.353885E+09 | 98118509.68 | 0.132112E+09 | 0.314184E+09 | 55082346.97 |
Maximum of Months | 0.572142E+09 | 0.384844E+09 | 0.287115E+09 | 0.562876E+09 | 0.466621E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.307231E+09 | 0.130149E+09 | 0.177082E+09 | 0.138307E+09 | 0.999321E+09 |
February | 0.448761E+09 | 0.206014E+09 | 0.242747E+09 | 0.299020E+09 | 0.723893E+09 |
March | 0.651502E+09 | 0.334092E+09 | 0.317410E+09 | 0.525769E+09 | 0.620456E+09 |
April | 0.804500E+09 | 0.407943E+09 | 0.396557E+09 | 0.776907E+09 | 0.363920E+09 |
May | 0.102228E+10 | 0.488871E+09 | 0.533405E+09 | 0.116317E+10 | 0.189503E+09 |
June | 0.950654E+09 | 0.410413E+09 | 0.540241E+09 | 0.115350E+10 | 0.112902E+09 |
July | 0.105023E+10 | 0.488269E+09 | 0.561960E+09 | 0.131175E+10 | 0.101703E+09 |
August | 0.862115E+09 | 0.390544E+09 | 0.471571E+09 | 0.104403E+10 | 0.121680E+09 |
September | 0.654928E+09 | 0.293903E+09 | 0.361025E+09 | 0.708344E+09 | 0.215362E+09 |
October | 0.428161E+09 | 0.172305E+09 | 0.255855E+09 | 0.367373E+09 | 0.372599E+09 |
November | 0.252239E+09 | 85826290.04 | 0.166413E+09 | 0.137055E+09 | 0.574320E+09 |
December | 0.229790E+09 | 79717529.27 | 0.150073E+09 | 77259590.40 | 0.965857E+09 |
Annual Sum or Average | 0.766239E+10 | 0.348805E+10 | 0.417434E+10 | 0.770248E+10 | 0.536152E+10 |
Minimum of Months | 0.229790E+09 | 79717529.27 | 0.150073E+09 | 77259590.40 | 0.101703E+09 |
Maximum of Months | 0.105023E+10 | 0.488871E+09 | 0.561960E+09 | 0.131175E+10 | 0.999321E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 73196226.91 | 0.00 | 73196226.91 | 1186441.75 | 0.576623E+09 |
February | 0.101554E+09 | 0.00 | 0.101554E+09 | 11054803.20 | 0.410155E+09 |
March | 0.138364E+09 | 5398.29 | 0.138358E+09 | 31546738.63 | 0.346713E+09 |
April | 0.176094E+09 | 1829975.10 | 0.174264E+09 | 95935842.30 | 0.195844E+09 |
May | 0.255266E+09 | 13638445.42 | 0.241628E+09 | 0.243154E+09 | 94544777.82 |
June | 0.276133E+09 | 30872694.36 | 0.245260E+09 | 0.319071E+09 | 57019313.42 |
July | 0.272775E+09 | 24077951.73 | 0.248697E+09 | 0.328616E+09 | 51602809.27 |
August | 0.207056E+09 | 3976857.93 | 0.203080E+09 | 0.228127E+09 | 62944570.65 |
September | 0.155985E+09 | 163465.80 | 0.155821E+09 | 0.131905E+09 | 0.115752E+09 |
October | 0.111735E+09 | 0.00 | 0.111735E+09 | 53663778.06 | 0.202772E+09 |
November | 71596193.86 | 0.00 | 71596193.86 | 9398022.84 | 0.319788E+09 |
December | 62017652.81 | 0.00 | 62017652.81 | 92414.68 | 0.552190E+09 |
Annual Sum or Average | 0.190177E+10 | 74564788.63 | 0.182721E+10 | 0.145375E+10 | 0.298595E+10 |
Minimum of Months | 62017652.81 | 0.00 | 62017652.81 | 92414.68 | 51602809.27 |
Maximum of Months | 0.276133E+09 | 30872694.36 | 0.248697E+09 | 0.328616E+09 | 0.576623E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.307231E+09 | 0.130149E+09 | 0.177082E+09 | 0.142414E+09 | 0.994667E+09 |
February | 0.448761E+09 | 0.206014E+09 | 0.242747E+09 | 0.308910E+09 | 0.717472E+09 |
March | 0.651502E+09 | 0.334092E+09 | 0.317410E+09 | 0.537874E+09 | 0.613491E+09 |
April | 0.804500E+09 | 0.407943E+09 | 0.396557E+09 | 0.789193E+09 | 0.360067E+09 |
May | 0.102228E+10 | 0.488871E+09 | 0.533405E+09 | 0.116891E+10 | 0.188102E+09 |
June | 0.950654E+09 | 0.410413E+09 | 0.540241E+09 | 0.115636E+10 | 0.112164E+09 |
July | 0.105023E+10 | 0.488269E+09 | 0.561960E+09 | 0.131557E+10 | 0.100690E+09 |
August | 0.862115E+09 | 0.390544E+09 | 0.471571E+09 | 0.104987E+10 | 0.120055E+09 |
September | 0.654928E+09 | 0.293903E+09 | 0.361025E+09 | 0.717013E+09 | 0.212586E+09 |
October | 0.428161E+09 | 0.172305E+09 | 0.255855E+09 | 0.376553E+09 | 0.367958E+09 |
November | 0.252239E+09 | 85826290.04 | 0.166413E+09 | 0.143595E+09 | 0.569557E+09 |
December | 0.229790E+09 | 79717529.27 | 0.150073E+09 | 79829551.67 | 0.962563E+09 |
Annual Sum or Average | 0.766239E+10 | 0.348805E+10 | 0.417434E+10 | 0.778610E+10 | 0.531937E+10 |
Minimum of Months | 0.229790E+09 | 79717529.27 | 0.150073E+09 | 79829551.67 | 0.100690E+09 |
Maximum of Months | 0.105023E+10 | 0.488871E+09 | 0.561960E+09 | 0.131557E+10 | 0.994667E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.743638E+09 | 0.517983E+09 | 0.225655E+09 | 0.628946E+09 | 0.700859E+09 |
February | 0.839102E+09 | 0.564410E+09 | 0.274692E+09 | 0.789671E+09 | 0.530178E+09 |
March | 0.817426E+09 | 0.514631E+09 | 0.302795E+09 | 0.792744E+09 | 0.477426E+09 |
April | 0.723100E+09 | 0.392440E+09 | 0.330660E+09 | 0.763782E+09 | 0.295338E+09 |
May | 0.639713E+09 | 0.226272E+09 | 0.413441E+09 | 0.748596E+09 | 0.151285E+09 |
June | 0.543999E+09 | 0.143900E+09 | 0.400099E+09 | 0.685865E+09 | 88540385.28 |
July | 0.618562E+09 | 0.197480E+09 | 0.421082E+09 | 0.810909E+09 | 78072724.66 |
August | 0.656170E+09 | 0.273273E+09 | 0.382897E+09 | 0.827613E+09 | 94970146.65 |
September | 0.669410E+09 | 0.350467E+09 | 0.318943E+09 | 0.775295E+09 | 0.171904E+09 |
October | 0.614457E+09 | 0.366251E+09 | 0.248206E+09 | 0.632119E+09 | 0.291777E+09 |
November | 0.519007E+09 | 0.325252E+09 | 0.193755E+09 | 0.466138E+09 | 0.428154E+09 |
December | 0.571148E+09 | 0.374490E+09 | 0.196658E+09 | 0.446760E+09 | 0.677651E+09 |
Annual Sum or Average | 0.795573E+10 | 0.424685E+10 | 0.370888E+10 | 0.836844E+10 | 0.398616E+10 |
Minimum of Months | 0.519007E+09 | 0.143900E+09 | 0.193755E+09 | 0.446760E+09 | 78072724.66 |
Maximum of Months | 0.839102E+09 | 0.564410E+09 | 0.421082E+09 | 0.827613E+09 | 0.700859E+09 |
Report: WindowEnergyReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.512354E+09 | 0.00 | 0.512354E+09 | 4602716.08 | 0.379279E+10 |
February | 0.710853E+09 | 0.00 | 0.710853E+09 | 61494005.09 | 0.284867E+10 |
March | 0.968510E+09 | 37786.62 | 0.968472E+09 | 0.200508E+09 | 0.246087E+10 |
April | 0.123261E+10 | 12809340.58 | 0.121980E+10 | 0.691315E+09 | 0.138685E+10 |
May | 0.178680E+10 | 95465502.22 | 0.169133E+10 | 0.182082E+10 | 0.658962E+09 |
June | 0.193286E+10 | 0.216101E+09 | 0.171676E+10 | 0.236096E+10 | 0.400347E+09 |
July | 0.190935E+10 | 0.168539E+09 | 0.174081E+10 | 0.244885E+10 | 0.354004E+09 |
August | 0.144934E+10 | 27836951.19 | 0.142150E+10 | 0.171756E+10 | 0.437697E+09 |
September | 0.109185E+10 | 1144217.24 | 0.109071E+10 | 0.981284E+09 | 0.809585E+09 |
October | 0.782115E+09 | 0.00 | 0.782115E+09 | 0.359830E+09 | 0.146348E+10 |
November | 0.501154E+09 | 0.00 | 0.501154E+09 | 50173944.60 | 0.236267E+10 |
December | 0.434107E+09 | 0.00 | 0.434107E+09 | 22293.05 | 0.373267E+10 |
Annual Sum or Average | 0.133119E+11 | 0.521934E+09 | 0.127900E+11 | 0.106974E+11 | 0.207086E+11 |
Minimum of Months | 0.434107E+09 | 0.00 | 0.434107E+09 | 22293.05 | 0.354004E+09 |
Maximum of Months | 0.193286E+10 | 0.216101E+09 | 0.174081E+10 | 0.244885E+10 | 0.379279E+10 |
Report: WindowEnergyReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.512354E+09 | 0.00 | 0.512354E+09 | 4155899.97 | 0.381665E+10 |
February | 0.710853E+09 | 0.00 | 0.710853E+09 | 58831800.90 | 0.287250E+10 |
March | 0.968510E+09 | 37786.62 | 0.968472E+09 | 0.194630E+09 | 0.249010E+10 |
April | 0.123261E+10 | 12809340.58 | 0.121980E+10 | 0.677203E+09 | 0.141186E+10 |
May | 0.178680E+10 | 95465502.22 | 0.169133E+10 | 0.179603E+10 | 0.677304E+09 |
June | 0.193286E+10 | 0.216101E+09 | 0.171676E+10 | 0.233356E+10 | 0.416324E+09 |
July | 0.190935E+10 | 0.168539E+09 | 0.174081E+10 | 0.242158E+10 | 0.370502E+09 |
August | 0.144934E+10 | 27836951.19 | 0.142150E+10 | 0.169484E+10 | 0.457861E+09 |
September | 0.109185E+10 | 1144217.24 | 0.109071E+10 | 0.965046E+09 | 0.833517E+09 |
October | 0.782115E+09 | 0.00 | 0.782115E+09 | 0.349982E+09 | 0.149340E+10 |
November | 0.501154E+09 | 0.00 | 0.501154E+09 | 47667047.41 | 0.239656E+10 |
December | 0.434107E+09 | 0.00 | 0.434107E+09 | 7099.44 | 0.375952E+10 |
Annual Sum or Average | 0.133119E+11 | 0.521934E+09 | 0.127900E+11 | 0.105435E+11 | 0.209961E+11 |
Minimum of Months | 0.434107E+09 | 0.00 | 0.434107E+09 | 7099.44 | 0.370502E+09 |
Maximum of Months | 0.193286E+10 | 0.216101E+09 | 0.174081E+10 | 0.242158E+10 | 0.381665E+10 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 73196226.91 | 0.00 | 73196226.91 | 4568337.16 | 0.433616E+09 |
February | 0.101554E+09 | 0.00 | 0.101554E+09 | 23134846.68 | 0.335924E+09 |
March | 0.138364E+09 | 5398.29 | 0.138358E+09 | 55369169.60 | 0.293660E+09 |
April | 0.176094E+09 | 1829975.10 | 0.174264E+09 | 0.145745E+09 | 0.170731E+09 |
May | 0.255266E+09 | 13638445.42 | 0.241628E+09 | 0.335652E+09 | 83843408.46 |
June | 0.276133E+09 | 30872694.36 | 0.245260E+09 | 0.414603E+09 | 50903513.16 |
July | 0.272775E+09 | 24077951.73 | 0.248697E+09 | 0.431881E+09 | 43568229.09 |
August | 0.207056E+09 | 3976857.93 | 0.203080E+09 | 0.320650E+09 | 49945524.17 |
September | 0.155985E+09 | 163465.80 | 0.155821E+09 | 0.198106E+09 | 91872944.95 |
October | 0.111735E+09 | 0.00 | 0.111735E+09 | 92518692.08 | 0.165481E+09 |
November | 71596193.86 | 0.00 | 71596193.86 | 22008138.60 | 0.269527E+09 |
December | 62017652.81 | 0.00 | 62017652.81 | 2076642.66 | 0.426492E+09 |
Annual Sum or Average | 0.190177E+10 | 74564788.63 | 0.182721E+10 | 0.204631E+10 | 0.241557E+10 |
Minimum of Months | 62017652.81 | 0.00 | 62017652.81 | 2076642.66 | 43568229.09 |
Maximum of Months | 0.276133E+09 | 30872694.36 | 0.248697E+09 | 0.431881E+09 | 0.433616E+09 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.597957E+09 | 0.248180E+09 | 0.349777E+09 | 0.346321E+09 | 0.150779E+10 |
February | 0.857902E+09 | 0.369112E+09 | 0.488791E+09 | 0.641825E+09 | 0.116175E+10 |
March | 0.129032E+10 | 0.648513E+09 | 0.641809E+09 | 0.116046E+10 | 0.102646E+10 |
April | 0.171942E+10 | 0.926613E+09 | 0.792812E+09 | 0.192246E+10 | 0.618267E+09 |
May | 0.192986E+10 | 0.850756E+09 | 0.107910E+10 | 0.252269E+10 | 0.313937E+09 |
June | 0.210731E+10 | 0.100748E+10 | 0.109983E+10 | 0.293529E+10 | 0.190966E+09 |
July | 0.213763E+10 | 0.100517E+10 | 0.113246E+10 | 0.306263E+10 | 0.163406E+09 |
August | 0.164549E+10 | 0.718770E+09 | 0.926722E+09 | 0.233972E+10 | 0.187299E+09 |
September | 0.127879E+10 | 0.573607E+09 | 0.705182E+09 | 0.165589E+10 | 0.339565E+09 |
October | 0.795836E+09 | 0.299270E+09 | 0.496566E+09 | 0.836361E+09 | 0.602106E+09 |
November | 0.493571E+09 | 0.164545E+09 | 0.329026E+09 | 0.336021E+09 | 0.953007E+09 |
December | 0.469008E+09 | 0.176254E+09 | 0.292755E+09 | 0.231759E+09 | 0.149629E+10 |
Annual Sum or Average | 0.153231E+11 | 0.698827E+10 | 0.833483E+10 | 0.179914E+11 | 0.856085E+10 |
Minimum of Months | 0.469008E+09 | 0.164545E+09 | 0.292755E+09 | 0.231759E+09 | 0.163406E+09 |
Maximum of Months | 0.213763E+10 | 0.100748E+10 | 0.113246E+10 | 0.306263E+10 | 0.150779E+10 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.507050E+09 | 0.353187E+09 | 0.153863E+09 | 0.495731E+09 | 0.365970E+09 |
February | 0.572142E+09 | 0.384844E+09 | 0.187299E+09 | 0.598060E+09 | 0.297878E+09 |
March | 0.557363E+09 | 0.350902E+09 | 0.206461E+09 | 0.599928E+09 | 0.274330E+09 |
April | 0.493047E+09 | 0.267586E+09 | 0.225461E+09 | 0.588048E+09 | 0.171798E+09 |
May | 0.436189E+09 | 0.154284E+09 | 0.281905E+09 | 0.601654E+09 | 88171957.39 |
June | 0.370926E+09 | 98118509.68 | 0.272808E+09 | 0.559572E+09 | 53006043.68 |
July | 0.421767E+09 | 0.134652E+09 | 0.287115E+09 | 0.653431E+09 | 44992612.65 |
August | 0.447410E+09 | 0.186331E+09 | 0.261079E+09 | 0.658509E+09 | 50450461.68 |
September | 0.456438E+09 | 0.238967E+09 | 0.217472E+09 | 0.606578E+09 | 91751333.99 |
October | 0.418968E+09 | 0.249729E+09 | 0.169239E+09 | 0.493078E+09 | 0.160640E+09 |
November | 0.353885E+09 | 0.221773E+09 | 0.132112E+09 | 0.361399E+09 | 0.244894E+09 |
December | 0.389438E+09 | 0.255346E+09 | 0.134092E+09 | 0.358437E+09 | 0.361962E+09 |
Annual Sum or Average | 0.542462E+10 | 0.289572E+10 | 0.252891E+10 | 0.657442E+10 | 0.220584E+10 |
Minimum of Months | 0.353885E+09 | 98118509.68 | 0.132112E+09 | 0.358437E+09 | 44992612.65 |
Maximum of Months | 0.572142E+09 | 0.384844E+09 | 0.287115E+09 | 0.658509E+09 | 0.365970E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 92698402.95 | 0.00 | 92698402.95 | 703889.00 | 0.708216E+09 |
February | 0.128612E+09 | 0.00 | 0.128612E+09 | 9744680.82 | 0.535688E+09 |
March | 0.175229E+09 | 6836.60 | 0.175222E+09 | 33291525.41 | 0.460104E+09 |
April | 0.223012E+09 | 2317548.00 | 0.220694E+09 | 0.120136E+09 | 0.255754E+09 |
May | 0.323279E+09 | 17272230.58 | 0.306006E+09 | 0.323946E+09 | 0.118432E+09 |
June | 0.349705E+09 | 39098319.45 | 0.310607E+09 | 0.422393E+09 | 70056842.72 |
July | 0.345452E+09 | 30493206.63 | 0.314959E+09 | 0.436947E+09 | 62083046.19 |
August | 0.262224E+09 | 5036439.64 | 0.257187E+09 | 0.304442E+09 | 77544983.74 |
September | 0.197545E+09 | 207019.12 | 0.197338E+09 | 0.172600E+09 | 0.148083E+09 |
October | 0.141505E+09 | 0.00 | 0.141505E+09 | 61511177.71 | 0.271606E+09 |
November | 90672062.05 | 0.00 | 90672062.05 | 8378206.17 | 0.439245E+09 |
December | 78541444.19 | 0.00 | 78541444.19 | 1147.16 | 0.697177E+09 |
Annual Sum or Average | 0.240847E+10 | 94431600.03 | 0.231404E+10 | 0.189409E+10 | 0.384399E+10 |
Minimum of Months | 78541444.19 | 0.00 | 78541444.19 | 1147.16 | 62083046.19 |
Maximum of Months | 0.349705E+09 | 39098319.45 | 0.314959E+09 | 0.436947E+09 | 0.708216E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 82937612.36 | 0.00 | 82937612.36 | 629772.15 | 0.633521E+09 |
February | 0.115070E+09 | 0.00 | 0.115070E+09 | 8718602.85 | 0.479273E+09 |
March | 0.156778E+09 | 6116.73 | 0.156772E+09 | 29786053.92 | 0.411657E+09 |
April | 0.199529E+09 | 2073518.98 | 0.197456E+09 | 0.107486E+09 | 0.228824E+09 |
May | 0.289239E+09 | 15453530.15 | 0.273785E+09 | 0.289836E+09 | 0.105962E+09 |
June | 0.312882E+09 | 34981414.56 | 0.277901E+09 | 0.377916E+09 | 62680122.63 |
July | 0.309078E+09 | 27282387.51 | 0.281795E+09 | 0.390938E+09 | 55545936.66 |
August | 0.234613E+09 | 4506121.63 | 0.230107E+09 | 0.272385E+09 | 69379790.77 |
September | 0.176744E+09 | 185220.79 | 0.176559E+09 | 0.154426E+09 | 0.132491E+09 |
October | 0.126605E+09 | 0.00 | 0.126605E+09 | 55034283.77 | 0.243007E+09 |
November | 81124637.48 | 0.00 | 81124637.48 | 7496012.81 | 0.392970E+09 |
December | 70271327.71 | 0.00 | 70271327.71 | 1026.37 | 0.623685E+09 |
Annual Sum or Average | 0.215487E+10 | 84488310.34 | 0.207038E+10 | 0.169465E+10 | 0.343899E+10 |
Minimum of Months | 70271327.71 | 0.00 | 70271327.71 | 1026.37 | 55545936.66 |
Maximum of Months | 0.312882E+09 | 34981414.56 | 0.281795E+09 | 0.390938E+09 | 0.633521E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.189297E+10 | 0.131855E+10 | 0.574416E+09 | 0.167096E+10 | 0.167141E+10 |
February | 0.213598E+10 | 0.143674E+10 | 0.699242E+09 | 0.205370E+10 | 0.132791E+10 |
March | 0.208080E+10 | 0.131002E+10 | 0.770780E+09 | 0.204881E+10 | 0.122170E+10 |
April | 0.184069E+10 | 0.998978E+09 | 0.841712E+09 | 0.197998E+10 | 0.756034E+09 |
May | 0.162842E+10 | 0.575988E+09 | 0.105243E+10 | 0.195326E+10 | 0.382454E+09 |
June | 0.138478E+10 | 0.366306E+09 | 0.101847E+10 | 0.178924E+10 | 0.222970E+09 |
July | 0.157458E+10 | 0.502695E+09 | 0.107189E+10 | 0.211370E+10 | 0.194675E+09 |
August | 0.167032E+10 | 0.695631E+09 | 0.974685E+09 | 0.215663E+10 | 0.236065E+09 |
September | 0.170402E+10 | 0.892134E+09 | 0.811886E+09 | 0.201654E+10 | 0.433722E+09 |
October | 0.156413E+10 | 0.932313E+09 | 0.631821E+09 | 0.163268E+10 | 0.751738E+09 |
November | 0.132116E+10 | 0.827946E+09 | 0.493214E+09 | 0.119899E+10 | 0.111821E+10 |
December | 0.145389E+10 | 0.953284E+09 | 0.500605E+09 | 0.118035E+10 | 0.166432E+10 |
Annual Sum or Average | 0.202517E+11 | 0.108106E+11 | 0.944116E+10 | 0.217948E+11 | 0.998122E+10 |
Minimum of Months | 0.132116E+10 | 0.366306E+09 | 0.493214E+09 | 0.118035E+10 | 0.194675E+09 |
Maximum of Months | 0.213598E+10 | 0.143674E+10 | 0.107189E+10 | 0.215663E+10 | 0.167141E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 856.91 | 774.24 | 957.48 | 666.94 | 290.54 | 0.00 | 0.00 |
February | 1163.50 | 689.46 | 1196.15 | 804.58 | 391.58 | 0.00 | 0.00 |
March | 1041.81 | 578.49 | 1052.49 | 662.62 | 389.87 | 0.00 | 0.00 |
April | 1037.15 | 374.03 | 962.07 | 522.14 | 439.93 | 0.00 | 0.00 |
May | 986.24 | 186.41 | 823.67 | 291.34 | 532.33 | 0.00 | 0.00 |
June | 931.80 | 113.29 | 723.78 | 191.46 | 532.32 | 0.00 | 0.00 |
July | 1062.37 | 97.18 | 796.43 | 254.27 | 542.17 | 0.00 | 0.00 |
August | 1085.21 | 117.02 | 844.86 | 351.86 | 493.00 | 0.00 | 0.00 |
September | 1051.44 | 216.63 | 890.64 | 466.29 | 424.35 | 0.00 | 0.00 |
October | 826.77 | 359.09 | 791.15 | 471.57 | 319.58 | 0.00 | 0.00 |
November | 635.02 | 543.83 | 690.53 | 432.74 | 257.79 | 0.00 | 0.00 |
December | 610.99 | 766.29 | 735.39 | 482.18 | 253.21 | 0.00 | 0.00 |
Annual Sum or Average | 939.23 | 399.94 | 870.00 | 464.41 | 405.58 | 0.00 | 0.00 |
Minimum of Months | 610.99 | 97.18 | 690.53 | 191.46 | 253.21 | 0.00 | 0.00 |
Maximum of Months | 1163.50 | 774.24 | 1196.15 | 804.58 | 542.17 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2402.63 | 2182.39 | 2696.21 | 1878.05 | 818.15 | 0.00 | 0.00 |
February | 3264.61 | 1932.60 | 3368.29 | 2265.64 | 1102.65 | 0.00 | 0.00 |
March | 2923.11 | 1618.89 | 2963.73 | 1865.90 | 1097.84 | 0.00 | 0.00 |
April | 2912.60 | 1040.11 | 2709.13 | 1470.30 | 1238.82 | 0.00 | 0.00 |
May | 2774.26 | 508.75 | 2319.39 | 820.40 | 1499.00 | 0.00 | 0.00 |
June | 2622.93 | 305.65 | 2038.11 | 539.13 | 1498.98 | 0.00 | 0.00 |
July | 2993.06 | 258.52 | 2242.71 | 716.00 | 1526.70 | 0.00 | 0.00 |
August | 3055.11 | 314.34 | 2379.07 | 990.81 | 1388.26 | 0.00 | 0.00 |
September | 2956.56 | 594.79 | 2507.98 | 1313.05 | 1194.93 | 0.00 | 0.00 |
October | 2321.10 | 999.19 | 2227.83 | 1327.92 | 899.92 | 0.00 | 0.00 |
November | 1778.77 | 1524.25 | 1944.49 | 1218.58 | 725.91 | 0.00 | 0.00 |
December | 1712.07 | 2158.08 | 2070.81 | 1357.79 | 713.02 | 0.00 | 0.00 |
Annual Sum or Average | 2638.79 | 1115.90 | 2449.85 | 1307.76 | 1142.09 | 0.00 | 0.00 |
Minimum of Months | 1712.07 | 258.52 | 1944.49 | 539.13 | 713.02 | 0.00 | 0.00 |
Maximum of Months | 3264.61 | 2182.39 | 3368.29 | 2265.64 | 1526.70 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3154.22 | 2934.83 | 3502.53 | 2439.70 | 1062.83 | 0.00 | 0.00 |
February | 4292.46 | 2584.62 | 4375.60 | 2943.19 | 1432.41 | 0.00 | 0.00 |
March | 3848.17 | 2156.97 | 3850.06 | 2423.91 | 1426.15 | 0.00 | 0.00 |
April | 3843.13 | 1384.22 | 3519.31 | 1910.01 | 1609.30 | 0.00 | 0.00 |
May | 3665.76 | 686.11 | 3013.03 | 1065.74 | 1947.28 | 0.00 | 0.00 |
June | 3464.90 | 419.22 | 2647.62 | 700.36 | 1947.26 | 0.00 | 0.00 |
July | 3953.83 | 356.45 | 2913.40 | 930.13 | 1983.28 | 0.00 | 0.00 |
August | 4036.08 | 428.92 | 3090.54 | 1287.11 | 1803.43 | 0.00 | 0.00 |
September | 3904.33 | 796.71 | 3258.00 | 1705.72 | 1552.28 | 0.00 | 0.00 |
October | 3061.82 | 1333.31 | 2894.08 | 1725.04 | 1169.04 | 0.00 | 0.00 |
November | 2338.66 | 2037.83 | 2526.00 | 1583.00 | 943.00 | 0.00 | 0.00 |
December | 2241.29 | 2909.88 | 2690.10 | 1763.84 | 926.26 | 0.00 | 0.00 |
Annual Sum or Average | 3478.13 | 1497.29 | 3182.50 | 1698.85 | 1483.64 | 0.00 | 0.00 |
Minimum of Months | 2241.29 | 356.45 | 2526.00 | 700.36 | 926.26 | 0.00 | 0.00 |
Maximum of Months | 4292.46 | 2934.83 | 4375.60 | 2943.19 | 1983.28 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 185.08 | 512.96 | 304.02 | 180.46 | 123.56 | 0.00 | 0.00 |
February | 334.00 | 426.53 | 422.00 | 244.24 | 177.76 | 0.00 | 0.00 |
March | 393.14 | 341.80 | 451.34 | 255.75 | 195.59 | 0.00 | 0.00 |
April | 501.39 | 214.38 | 500.60 | 260.62 | 239.98 | 0.00 | 0.00 |
May | 627.62 | 108.50 | 544.53 | 240.13 | 304.40 | 0.00 | 0.00 |
June | 628.29 | 66.58 | 509.87 | 196.19 | 313.68 | 0.00 | 0.00 |
July | 699.04 | 58.04 | 549.58 | 232.57 | 317.01 | 0.00 | 0.00 |
August | 603.84 | 69.29 | 488.92 | 215.38 | 273.54 | 0.00 | 0.00 |
September | 480.35 | 126.89 | 428.77 | 205.58 | 223.19 | 0.00 | 0.00 |
October | 298.31 | 210.03 | 316.28 | 157.57 | 158.71 | 0.00 | 0.00 |
November | 169.58 | 323.34 | 233.84 | 118.67 | 115.17 | 0.00 | 0.00 |
December | 119.16 | 499.81 | 231.19 | 125.10 | 106.09 | 0.00 | 0.00 |
Annual Sum or Average | 420.42 | 245.73 | 414.99 | 202.43 | 212.56 | 0.00 | 0.00 |
Minimum of Months | 119.16 | 58.04 | 231.19 | 118.67 | 106.09 | 0.00 | 0.00 |
Maximum of Months | 699.04 | 512.96 | 549.58 | 260.62 | 317.01 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 42.16 | 572.28 | 142.04 | 48.59 | 93.44 | 0.00 | 0.00 |
February | 123.73 | 457.32 | 227.48 | 85.16 | 142.32 | 0.00 | 0.00 |
March | 206.76 | 353.19 | 294.90 | 124.74 | 170.16 | 0.00 | 0.00 |
April | 340.70 | 213.23 | 378.32 | 158.09 | 220.22 | 0.00 | 0.00 |
May | 529.67 | 103.71 | 476.98 | 187.62 | 289.36 | 0.00 | 0.00 |
June | 572.09 | 63.54 | 473.30 | 170.25 | 303.05 | 0.00 | 0.00 |
July | 617.01 | 55.49 | 493.95 | 191.29 | 302.66 | 0.00 | 0.00 |
August | 480.39 | 67.55 | 399.18 | 147.30 | 251.89 | 0.00 | 0.00 |
September | 329.09 | 126.00 | 312.85 | 113.45 | 199.40 | 0.00 | 0.00 |
October | 158.82 | 213.30 | 201.57 | 64.33 | 137.24 | 0.00 | 0.00 |
November | 54.40 | 340.72 | 124.94 | 33.11 | 91.82 | 0.00 | 0.00 |
December | 21.39 | 555.03 | 108.95 | 29.76 | 79.19 | 0.00 | 0.00 |
Annual Sum or Average | 290.67 | 259.31 | 303.28 | 112.97 | 190.31 | 0.00 | 0.00 |
Minimum of Months | 21.39 | 55.49 | 108.95 | 29.76 | 79.19 | 0.00 | 0.00 |
Maximum of Months | 617.01 | 572.28 | 493.95 | 191.29 | 303.05 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 130.92 | 137.77 | 151.42 | 105.47 | 45.95 | 0.00 | 0.00 |
February | 180.46 | 118.51 | 189.16 | 127.24 | 61.93 | 0.00 | 0.00 |
March | 162.52 | 98.79 | 166.44 | 104.79 | 61.65 | 0.00 | 0.00 |
April | 160.00 | 67.56 | 152.14 | 82.57 | 69.57 | 0.00 | 0.00 |
May | 150.82 | 35.92 | 130.26 | 46.07 | 84.18 | 0.00 | 0.00 |
June | 141.86 | 23.11 | 114.46 | 30.28 | 84.18 | 0.00 | 0.00 |
July | 163.10 | 20.31 | 125.95 | 40.21 | 85.74 | 0.00 | 0.00 |
August | 167.01 | 24.49 | 133.61 | 55.64 | 77.97 | 0.00 | 0.00 |
September | 161.91 | 42.17 | 140.85 | 73.74 | 67.11 | 0.00 | 0.00 |
October | 127.59 | 65.11 | 125.12 | 74.58 | 50.54 | 0.00 | 0.00 |
November | 98.87 | 90.74 | 109.20 | 68.43 | 40.77 | 0.00 | 0.00 |
December | 93.40 | 132.38 | 116.30 | 76.25 | 40.04 | 0.00 | 0.00 |
Annual Sum or Average | 144.62 | 71.19 | 137.58 | 73.44 | 64.14 | 0.00 | 0.00 |
Minimum of Months | 93.40 | 20.31 | 109.20 | 30.28 | 40.04 | 0.00 | 0.00 |
Maximum of Months | 180.46 | 137.77 | 189.16 | 127.24 | 85.74 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.23 | 177.75 | 21.87 | 0.00 | 21.87 | 0.00 | 0.00 |
February | 3.08 | 139.97 | 33.59 | 0.00 | 33.59 | 0.00 | 0.00 |
March | 8.84 | 106.27 | 41.33 | 0.00 | 41.33 | 0.00 | 0.00 |
April | 30.14 | 61.50 | 54.36 | 0.56 | 53.79 | 0.00 | 0.00 |
May | 76.03 | 27.87 | 76.25 | 4.07 | 72.18 | 0.00 | 0.00 |
June | 102.11 | 17.16 | 85.24 | 9.53 | 75.71 | 0.00 | 0.00 |
July | 102.26 | 14.63 | 81.48 | 7.19 | 74.29 | 0.00 | 0.00 |
August | 71.37 | 18.18 | 61.85 | 1.19 | 60.67 | 0.00 | 0.00 |
September | 42.13 | 35.79 | 48.15 | 0.05 | 48.10 | 0.00 | 0.00 |
October | 15.10 | 63.19 | 33.38 | 0.00 | 33.38 | 0.00 | 0.00 |
November | 2.27 | 104.03 | 22.10 | 0.00 | 22.10 | 0.00 | 0.00 |
December | 0.00 | 170.60 | 18.53 | 0.00 | 18.53 | 0.00 | 0.00 |
Annual Sum or Average | 38.01 | 77.83 | 48.25 | 1.89 | 46.36 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 14.63 | 18.53 | 0.00 | 18.53 | 0.00 | 0.00 |
Maximum of Months | 102.26 | 177.75 | 85.24 | 9.53 | 75.71 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 180.25 | 509.96 | 300.94 | 178.20 | 122.75 | 0.00 | 0.00 |
February | 319.45 | 419.50 | 413.82 | 235.37 | 178.45 | 0.00 | 0.00 |
March | 381.93 | 334.33 | 448.99 | 252.08 | 196.90 | 0.00 | 0.00 |
April | 520.81 | 207.43 | 521.92 | 281.99 | 239.93 | 0.00 | 0.00 |
May | 594.15 | 101.85 | 523.14 | 216.43 | 306.71 | 0.00 | 0.00 |
June | 675.61 | 63.71 | 549.64 | 232.21 | 317.42 | 0.00 | 0.00 |
July | 704.34 | 54.96 | 556.55 | 237.93 | 318.62 | 0.00 | 0.00 |
August | 581.65 | 66.90 | 474.24 | 203.76 | 270.49 | 0.00 | 0.00 |
September | 469.63 | 123.50 | 422.79 | 202.85 | 219.94 | 0.00 | 0.00 |
October | 281.78 | 207.49 | 305.00 | 149.11 | 155.89 | 0.00 | 0.00 |
November | 164.74 | 319.78 | 231.75 | 117.30 | 114.44 | 0.00 | 0.00 |
December | 121.87 | 499.35 | 232.96 | 128.24 | 104.72 | 0.00 | 0.00 |
Annual Sum or Average | 416.69 | 241.64 | 414.98 | 202.63 | 212.35 | 0.00 | 0.00 |
Minimum of Months | 121.87 | 54.96 | 231.75 | 117.30 | 104.72 | 0.00 | 0.00 |
Maximum of Months | 704.34 | 509.96 | 556.55 | 281.99 | 318.62 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 32.57 | 564.42 | 138.96 | 46.33 | 92.63 | 0.00 | 0.00 |
February | 101.51 | 442.57 | 219.30 | 76.29 | 143.01 | 0.00 | 0.00 |
March | 191.13 | 340.91 | 292.55 | 121.07 | 171.48 | 0.00 | 0.00 |
April | 357.74 | 205.08 | 399.64 | 179.46 | 220.18 | 0.00 | 0.00 |
May | 498.01 | 99.38 | 455.59 | 163.92 | 291.67 | 0.00 | 0.00 |
June | 620.76 | 62.23 | 513.06 | 206.27 | 306.80 | 0.00 | 0.00 |
July | 623.64 | 53.87 | 500.92 | 196.65 | 304.27 | 0.00 | 0.00 |
August | 458.45 | 65.71 | 384.51 | 135.67 | 248.83 | 0.00 | 0.00 |
September | 317.05 | 122.10 | 306.88 | 110.72 | 196.16 | 0.00 | 0.00 |
October | 139.58 | 208.17 | 190.29 | 55.87 | 134.42 | 0.00 | 0.00 |
November | 47.04 | 334.87 | 122.84 | 31.74 | 91.10 | 0.00 | 0.00 |
December | 18.97 | 549.12 | 110.71 | 32.91 | 77.81 | 0.00 | 0.00 |
Annual Sum or Average | 284.80 | 253.29 | 303.27 | 113.17 | 190.10 | 0.00 | 0.00 |
Minimum of Months | 18.97 | 53.87 | 110.71 | 31.74 | 77.81 | 0.00 | 0.00 |
Maximum of Months | 623.64 | 564.42 | 513.06 | 206.27 | 306.80 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 232.65 | 616.62 | 375.45 | 228.53 | 146.92 | 0.00 | 0.00 |
February | 369.05 | 530.95 | 482.62 | 275.69 | 206.94 | 0.00 | 0.00 |
March | 361.45 | 431.68 | 450.18 | 227.05 | 223.13 | 0.00 | 0.00 |
April | 421.79 | 266.73 | 447.41 | 180.13 | 267.28 | 0.00 | 0.00 |
May | 507.59 | 122.91 | 447.42 | 108.65 | 338.77 | 0.00 | 0.00 |
June | 547.26 | 74.10 | 432.66 | 86.25 | 346.41 | 0.00 | 0.00 |
July | 592.18 | 64.90 | 449.42 | 102.71 | 346.72 | 0.00 | 0.00 |
August | 534.44 | 79.50 | 423.49 | 123.14 | 300.35 | 0.00 | 0.00 |
September | 457.60 | 153.41 | 409.49 | 159.88 | 249.60 | 0.00 | 0.00 |
October | 314.50 | 262.54 | 343.40 | 161.58 | 181.81 | 0.00 | 0.00 |
November | 203.58 | 410.65 | 284.49 | 148.28 | 136.21 | 0.00 | 0.00 |
December | 156.62 | 611.85 | 292.12 | 165.22 | 126.90 | 0.00 | 0.00 |
Annual Sum or Average | 391.57 | 301.11 | 402.63 | 163.23 | 239.40 | 0.00 | 0.00 |
Minimum of Months | 156.62 | 64.90 | 284.49 | 86.25 | 126.90 | 0.00 | 0.00 |
Maximum of Months | 592.18 | 616.62 | 482.62 | 275.69 | 346.72 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 183.91 | 514.82 | 304.02 | 180.46 | 123.56 | 0.00 | 0.00 |
February | 332.98 | 426.26 | 422.00 | 244.24 | 177.76 | 0.00 | 0.00 |
March | 392.41 | 340.96 | 451.34 | 255.75 | 195.59 | 0.00 | 0.00 |
April | 499.24 | 213.72 | 500.60 | 260.62 | 239.98 | 0.00 | 0.00 |
May | 623.25 | 108.75 | 544.53 | 240.13 | 304.40 | 0.00 | 0.00 |
June | 623.78 | 66.85 | 509.87 | 196.19 | 313.68 | 0.00 | 0.00 |
July | 694.47 | 58.30 | 549.58 | 232.57 | 317.01 | 0.00 | 0.00 |
August | 599.71 | 69.73 | 488.92 | 215.38 | 273.54 | 0.00 | 0.00 |
September | 477.35 | 127.05 | 428.77 | 205.58 | 223.19 | 0.00 | 0.00 |
October | 297.86 | 208.72 | 316.28 | 157.57 | 158.71 | 0.00 | 0.00 |
November | 169.90 | 321.76 | 233.84 | 118.67 | 115.17 | 0.00 | 0.00 |
December | 118.43 | 501.38 | 231.19 | 125.10 | 106.09 | 0.00 | 0.00 |
Annual Sum or Average | 418.20 | 245.75 | 414.99 | 202.43 | 212.56 | 0.00 | 0.00 |
Minimum of Months | 118.43 | 58.30 | 231.19 | 118.67 | 106.09 | 0.00 | 0.00 |
Maximum of Months | 694.47 | 514.82 | 549.58 | 260.62 | 317.01 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 41.79 | 574.83 | 142.04 | 48.59 | 93.44 | 0.00 | 0.00 |
February | 123.46 | 457.31 | 227.48 | 85.16 | 142.32 | 0.00 | 0.00 |
March | 206.45 | 352.35 | 294.90 | 124.74 | 170.16 | 0.00 | 0.00 |
April | 339.46 | 212.45 | 378.32 | 158.09 | 220.22 | 0.00 | 0.00 |
May | 525.65 | 103.97 | 476.98 | 187.62 | 289.36 | 0.00 | 0.00 |
June | 567.80 | 63.85 | 473.30 | 170.25 | 303.05 | 0.00 | 0.00 |
July | 612.79 | 55.78 | 493.95 | 191.29 | 302.66 | 0.00 | 0.00 |
August | 476.79 | 67.96 | 399.18 | 147.30 | 251.89 | 0.00 | 0.00 |
September | 326.83 | 125.99 | 312.85 | 113.45 | 199.40 | 0.00 | 0.00 |
October | 159.11 | 211.57 | 201.57 | 64.33 | 137.24 | 0.00 | 0.00 |
November | 54.94 | 339.03 | 124.94 | 33.11 | 91.82 | 0.00 | 0.00 |
December | 21.21 | 556.91 | 108.95 | 29.76 | 79.19 | 0.00 | 0.00 |
Annual Sum or Average | 289.00 | 259.37 | 303.28 | 112.97 | 190.31 | 0.00 | 0.00 |
Minimum of Months | 21.21 | 55.78 | 108.95 | 29.76 | 79.19 | 0.00 | 0.00 |
Maximum of Months | 612.79 | 574.83 | 493.95 | 191.29 | 303.05 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 234.82 | 261.67 | 277.64 | 193.39 | 84.25 | 0.00 | 0.00 |
February | 326.42 | 219.15 | 346.85 | 233.30 | 113.55 | 0.00 | 0.00 |
March | 295.98 | 178.25 | 305.19 | 192.14 | 113.05 | 0.00 | 0.00 |
April | 294.67 | 113.94 | 278.97 | 151.40 | 127.57 | 0.00 | 0.00 |
May | 279.49 | 56.48 | 238.84 | 84.48 | 154.36 | 0.00 | 0.00 |
June | 264.61 | 34.16 | 209.88 | 55.52 | 154.36 | 0.00 | 0.00 |
July | 302.76 | 29.15 | 230.94 | 73.73 | 157.21 | 0.00 | 0.00 |
August | 309.00 | 35.46 | 244.99 | 102.03 | 142.96 | 0.00 | 0.00 |
September | 299.11 | 66.32 | 258.26 | 135.21 | 123.05 | 0.00 | 0.00 |
October | 236.01 | 108.94 | 229.41 | 136.74 | 92.67 | 0.00 | 0.00 |
November | 179.84 | 165.18 | 200.23 | 125.48 | 74.75 | 0.00 | 0.00 |
December | 166.80 | 253.01 | 213.24 | 139.82 | 73.42 | 0.00 | 0.00 |
Annual Sum or Average | 265.36 | 126.40 | 252.27 | 134.67 | 117.61 | 0.00 | 0.00 |
Minimum of Months | 166.80 | 29.15 | 200.23 | 55.52 | 73.42 | 0.00 | 0.00 |
Maximum of Months | 326.42 | 261.67 | 346.85 | 233.30 | 157.21 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1.72 | 1416.07 | 191.29 | 0.00 | 191.29 | 0.00 | 0.00 |
February | 25.42 | 1177.52 | 293.84 | 0.00 | 293.84 | 0.00 | 0.00 |
March | 74.86 | 918.78 | 361.60 | 0.01 | 361.59 | 0.00 | 0.00 |
April | 266.71 | 535.05 | 475.54 | 4.94 | 470.60 | 0.00 | 0.00 |
May | 679.82 | 246.03 | 667.11 | 35.64 | 631.47 | 0.00 | 0.00 |
June | 910.86 | 154.45 | 745.70 | 83.37 | 662.33 | 0.00 | 0.00 |
July | 914.29 | 132.17 | 712.87 | 62.93 | 649.95 | 0.00 | 0.00 |
August | 641.26 | 163.42 | 541.12 | 10.39 | 530.73 | 0.00 | 0.00 |
September | 378.58 | 312.34 | 421.24 | 0.44 | 420.80 | 0.00 | 0.00 |
October | 134.35 | 546.40 | 292.01 | 0.00 | 292.01 | 0.00 | 0.00 |
November | 19.36 | 911.52 | 193.35 | 0.00 | 193.35 | 0.00 | 0.00 |
December | 0.01 | 1393.62 | 162.08 | 0.00 | 162.08 | 0.00 | 0.00 |
Annual Sum or Average | 339.21 | 656.67 | 422.12 | 16.55 | 405.57 | 0.00 | 0.00 |
Minimum of Months | 0.01 | 132.17 | 162.08 | 0.00 | 162.08 | 0.00 | 0.00 |
Maximum of Months | 914.29 | 1416.07 | 745.70 | 83.37 | 662.33 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1.55 | 1424.97 | 191.29 | 0.00 | 191.29 | 0.00 | 0.00 |
February | 24.32 | 1187.38 | 293.84 | 0.00 | 293.84 | 0.00 | 0.00 |
March | 72.67 | 929.70 | 361.60 | 0.01 | 361.59 | 0.00 | 0.00 |
April | 261.27 | 544.70 | 475.54 | 4.94 | 470.60 | 0.00 | 0.00 |
May | 670.56 | 252.88 | 667.11 | 35.64 | 631.47 | 0.00 | 0.00 |
June | 900.29 | 160.62 | 745.70 | 83.37 | 662.33 | 0.00 | 0.00 |
July | 904.11 | 138.33 | 712.87 | 62.93 | 649.95 | 0.00 | 0.00 |
August | 632.78 | 170.95 | 541.12 | 10.39 | 530.73 | 0.00 | 0.00 |
September | 372.32 | 321.57 | 421.24 | 0.44 | 420.80 | 0.00 | 0.00 |
October | 130.67 | 557.57 | 292.01 | 0.00 | 292.01 | 0.00 | 0.00 |
November | 18.39 | 924.60 | 193.35 | 0.00 | 193.35 | 0.00 | 0.00 |
December | 0.00 | 1403.64 | 162.08 | 0.00 | 162.08 | 0.00 | 0.00 |
Annual Sum or Average | 334.33 | 665.78 | 422.12 | 16.55 | 405.57 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 138.33 | 162.08 | 0.00 | 162.08 | 0.00 | 0.00 |
Maximum of Months | 904.11 | 1424.97 | 745.70 | 83.37 | 662.33 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 268.10 | 813.48 | 439.89 | 224.52 | 215.37 | 0.00 | 0.00 |
February | 496.50 | 716.63 | 633.10 | 311.65 | 321.45 | 0.00 | 0.00 |
March | 665.59 | 582.97 | 741.51 | 373.14 | 368.36 | 0.00 | 0.00 |
April | 1019.63 | 365.52 | 921.51 | 461.43 | 460.08 | 0.00 | 0.00 |
May | 1289.86 | 179.48 | 978.69 | 380.33 | 598.36 | 0.00 | 0.00 |
June | 1507.39 | 112.87 | 1062.64 | 438.45 | 624.19 | 0.00 | 0.00 |
July | 1548.10 | 93.51 | 1057.41 | 434.55 | 622.86 | 0.00 | 0.00 |
August | 1238.89 | 107.17 | 858.71 | 339.41 | 519.30 | 0.00 | 0.00 |
September | 948.37 | 200.92 | 729.63 | 313.56 | 416.08 | 0.00 | 0.00 |
October | 529.06 | 344.73 | 495.27 | 204.97 | 290.30 | 0.00 | 0.00 |
November | 265.04 | 553.62 | 354.57 | 149.04 | 205.53 | 0.00 | 0.00 |
December | 180.11 | 812.00 | 343.66 | 161.14 | 182.52 | 0.00 | 0.00 |
Annual Sum or Average | 831.30 | 405.44 | 718.21 | 315.78 | 402.43 | 0.00 | 0.00 |
Minimum of Months | 180.11 | 93.51 | 343.66 | 149.04 | 182.52 | 0.00 | 0.00 |
Maximum of Months | 1548.10 | 813.48 | 1062.64 | 461.43 | 624.19 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 547.32 | 1047.93 | 772.33 | 492.29 | 280.04 | 0.00 | 0.00 |
February | 809.07 | 920.97 | 983.66 | 593.89 | 389.77 | 0.00 | 0.00 |
March | 767.16 | 760.28 | 900.84 | 489.11 | 411.73 | 0.00 | 0.00 |
April | 849.20 | 476.13 | 873.16 | 387.10 | 486.06 | 0.00 | 0.00 |
May | 953.41 | 221.56 | 836.67 | 227.27 | 609.40 | 0.00 | 0.00 |
June | 994.53 | 132.70 | 789.88 | 169.90 | 619.98 | 0.00 | 0.00 |
July | 1095.21 | 113.55 | 832.26 | 209.26 | 623.00 | 0.00 | 0.00 |
August | 1019.45 | 141.89 | 809.12 | 263.28 | 545.84 | 0.00 | 0.00 |
September | 903.61 | 275.03 | 801.82 | 344.34 | 457.48 | 0.00 | 0.00 |
October | 647.06 | 466.77 | 684.08 | 348.09 | 336.00 | 0.00 | 0.00 |
November | 441.47 | 725.26 | 575.99 | 319.42 | 256.56 | 0.00 | 0.00 |
December | 374.03 | 1047.88 | 598.38 | 355.92 | 242.46 | 0.00 | 0.00 |
Annual Sum or Average | 783.10 | 525.64 | 786.88 | 348.47 | 438.41 | 0.00 | 0.00 |
Minimum of Months | 374.03 | 113.55 | 575.99 | 169.90 | 242.46 | 0.00 | 0.00 |
Maximum of Months | 1095.21 | 1047.93 | 983.66 | 593.89 | 623.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.229515E+10 | 0.207373E+10 | 0.256452E+10 | 0.178633E+10 | 0.778194E+09 | 0.00 | 0.00 |
February | 0.281474E+10 | 0.166795E+10 | 0.289374E+10 | 0.194644E+10 | 0.947301E+09 | 0.00 | 0.00 |
March | 0.279038E+10 | 0.154944E+10 | 0.281898E+10 | 0.177477E+10 | 0.104422E+10 | 0.00 | 0.00 |
April | 0.268828E+10 | 0.969482E+09 | 0.249369E+10 | 0.135338E+10 | 0.114031E+10 | 0.00 | 0.00 |
May | 0.264156E+10 | 0.499287E+09 | 0.220611E+10 | 0.780327E+09 | 0.142579E+10 | 0.00 | 0.00 |
June | 0.241521E+10 | 0.293658E+09 | 0.187603E+10 | 0.496257E+09 | 0.137978E+10 | 0.00 | 0.00 |
July | 0.284545E+10 | 0.260282E+09 | 0.213317E+10 | 0.681032E+09 | 0.145214E+10 | 0.00 | 0.00 |
August | 0.290663E+10 | 0.313414E+09 | 0.226287E+10 | 0.942414E+09 | 0.132045E+10 | 0.00 | 0.00 |
September | 0.272532E+10 | 0.561508E+09 | 0.230853E+10 | 0.120863E+10 | 0.109990E+10 | 0.00 | 0.00 |
October | 0.221441E+10 | 0.961778E+09 | 0.211902E+10 | 0.126306E+10 | 0.855962E+09 | 0.00 | 0.00 |
November | 0.164596E+10 | 0.140961E+10 | 0.178985E+10 | 0.112167E+10 | 0.668184E+09 | 0.00 | 0.00 |
December | 0.163648E+10 | 0.205244E+10 | 0.196967E+10 | 0.129147E+10 | 0.678197E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.296196E+11 | 0.126126E+11 | 0.274362E+11 | 0.146458E+11 | 0.127904E+11 | 0.00 | 0.00 |
Minimum of Months | 0.163648E+10 | 0.260282E+09 | 0.178985E+10 | 0.496257E+09 | 0.668184E+09 | 0.00 | 0.00 |
Maximum of Months | 0.290663E+10 | 0.207373E+10 | 0.289374E+10 | 0.194644E+10 | 0.145214E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.643519E+10 | 0.584530E+10 | 0.722152E+10 | 0.503018E+10 | 0.219134E+10 | 0.00 | 0.00 |
February | 0.789775E+10 | 0.467534E+10 | 0.814857E+10 | 0.548103E+10 | 0.266754E+10 | 0.00 | 0.00 |
March | 0.782926E+10 | 0.433604E+10 | 0.793806E+10 | 0.499762E+10 | 0.294044E+10 | 0.00 | 0.00 |
April | 0.754947E+10 | 0.269598E+10 | 0.702205E+10 | 0.381102E+10 | 0.321103E+10 | 0.00 | 0.00 |
May | 0.743057E+10 | 0.136264E+10 | 0.621227E+10 | 0.219735E+10 | 0.401492E+10 | 0.00 | 0.00 |
June | 0.679864E+10 | 0.792257E+09 | 0.528278E+10 | 0.139743E+10 | 0.388536E+10 | 0.00 | 0.00 |
July | 0.801661E+10 | 0.692415E+09 | 0.600687E+10 | 0.191774E+10 | 0.408912E+10 | 0.00 | 0.00 |
August | 0.818281E+10 | 0.841931E+09 | 0.637209E+10 | 0.265378E+10 | 0.371831E+10 | 0.00 | 0.00 |
September | 0.766341E+10 | 0.154171E+10 | 0.650068E+10 | 0.340342E+10 | 0.309726E+10 | 0.00 | 0.00 |
October | 0.621683E+10 | 0.267623E+10 | 0.596703E+10 | 0.355670E+10 | 0.241033E+10 | 0.00 | 0.00 |
November | 0.461057E+10 | 0.395086E+10 | 0.504011E+10 | 0.315855E+10 | 0.188156E+10 | 0.00 | 0.00 |
December | 0.458562E+10 | 0.578020E+10 | 0.554646E+10 | 0.363670E+10 | 0.190976E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.832167E+11 | 0.351909E+11 | 0.772585E+11 | 0.412415E+11 | 0.360170E+11 | 0.00 | 0.00 |
Minimum of Months | 0.458562E+10 | 0.692415E+09 | 0.504011E+10 | 0.139743E+10 | 0.188156E+10 | 0.00 | 0.00 |
Maximum of Months | 0.818281E+10 | 0.584530E+10 | 0.814857E+10 | 0.548103E+10 | 0.408912E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.844826E+10 | 0.786066E+10 | 0.938116E+10 | 0.653449E+10 | 0.284668E+10 | 0.00 | 0.00 |
February | 0.103843E+11 | 0.625271E+10 | 0.105855E+11 | 0.712017E+10 | 0.346528E+10 | 0.00 | 0.00 |
March | 0.103069E+11 | 0.577723E+10 | 0.103120E+11 | 0.649219E+10 | 0.381980E+10 | 0.00 | 0.00 |
April | 0.996140E+10 | 0.358791E+10 | 0.912205E+10 | 0.495073E+10 | 0.417132E+10 | 0.00 | 0.00 |
May | 0.981838E+10 | 0.183769E+10 | 0.807009E+10 | 0.285448E+10 | 0.521561E+10 | 0.00 | 0.00 |
June | 0.898103E+10 | 0.108661E+10 | 0.686263E+10 | 0.181534E+10 | 0.504730E+10 | 0.00 | 0.00 |
July | 0.105899E+11 | 0.954711E+09 | 0.780326E+10 | 0.249126E+10 | 0.531200E+10 | 0.00 | 0.00 |
August | 0.108102E+11 | 0.114882E+10 | 0.827770E+10 | 0.344741E+10 | 0.483030E+10 | 0.00 | 0.00 |
September | 0.101200E+11 | 0.206508E+10 | 0.844475E+10 | 0.442123E+10 | 0.402351E+10 | 0.00 | 0.00 |
October | 0.820079E+10 | 0.357113E+10 | 0.775151E+10 | 0.462035E+10 | 0.313116E+10 | 0.00 | 0.00 |
November | 0.606181E+10 | 0.528207E+10 | 0.654739E+10 | 0.410313E+10 | 0.244426E+10 | 0.00 | 0.00 |
December | 0.600307E+10 | 0.779381E+10 | 0.720517E+10 | 0.472428E+10 | 0.248089E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.109686E+12 | 0.472184E+11 | 0.100363E+12 | 0.535751E+11 | 0.467881E+11 | 0.00 | 0.00 |
Minimum of Months | 0.600307E+10 | 0.954711E+09 | 0.654739E+10 | 0.181534E+10 | 0.244426E+10 | 0.00 | 0.00 |
Maximum of Months | 0.108102E+11 | 0.786066E+10 | 0.105855E+11 | 0.712017E+10 | 0.531200E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.495706E+09 | 0.137391E+10 | 0.814281E+09 | 0.483337E+09 | 0.330945E+09 | 0.00 | 0.00 |
February | 0.808012E+09 | 0.103185E+10 | 0.102090E+10 | 0.590858E+09 | 0.430046E+09 | 0.00 | 0.00 |
March | 0.105298E+10 | 0.915490E+09 | 0.120886E+10 | 0.684993E+09 | 0.523871E+09 | 0.00 | 0.00 |
April | 0.129960E+10 | 0.555670E+09 | 0.129755E+10 | 0.675529E+09 | 0.622018E+09 | 0.00 | 0.00 |
May | 0.168102E+10 | 0.290613E+09 | 0.145847E+10 | 0.643155E+09 | 0.815310E+09 | 0.00 | 0.00 |
June | 0.162853E+10 | 0.172582E+09 | 0.132158E+10 | 0.508531E+09 | 0.813049E+09 | 0.00 | 0.00 |
July | 0.187230E+10 | 0.155464E+09 | 0.147200E+10 | 0.622921E+09 | 0.849075E+09 | 0.00 | 0.00 |
August | 0.161733E+10 | 0.185591E+09 | 0.130952E+10 | 0.576875E+09 | 0.732650E+09 | 0.00 | 0.00 |
September | 0.124508E+10 | 0.328888E+09 | 0.111137E+10 | 0.532870E+09 | 0.578497E+09 | 0.00 | 0.00 |
October | 0.798984E+09 | 0.562546E+09 | 0.847129E+09 | 0.422034E+09 | 0.425095E+09 | 0.00 | 0.00 |
November | 0.439545E+09 | 0.838088E+09 | 0.606125E+09 | 0.307600E+09 | 0.298525E+09 | 0.00 | 0.00 |
December | 0.319168E+09 | 0.133870E+10 | 0.619228E+09 | 0.335064E+09 | 0.284165E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.132582E+11 | 0.774940E+10 | 0.130870E+11 | 0.638377E+10 | 0.670324E+10 | 0.00 | 0.00 |
Minimum of Months | 0.319168E+09 | 0.155464E+09 | 0.606125E+09 | 0.307600E+09 | 0.284165E+09 | 0.00 | 0.00 |
Maximum of Months | 0.187230E+10 | 0.137391E+10 | 0.147200E+10 | 0.684993E+09 | 0.849075E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.112926E+09 | 0.153279E+10 | 0.380427E+09 | 0.130149E+09 | 0.250278E+09 | 0.00 | 0.00 |
February | 0.299320E+09 | 0.110635E+10 | 0.550316E+09 | 0.206014E+09 | 0.344302E+09 | 0.00 | 0.00 |
March | 0.553783E+09 | 0.945994E+09 | 0.789866E+09 | 0.334097E+09 | 0.455769E+09 | 0.00 | 0.00 |
April | 0.883088E+09 | 0.552696E+09 | 0.980594E+09 | 0.409773E+09 | 0.570821E+09 | 0.00 | 0.00 |
May | 0.141868E+10 | 0.277786E+09 | 0.127754E+10 | 0.502510E+09 | 0.775033E+09 | 0.00 | 0.00 |
June | 0.148285E+10 | 0.164686E+09 | 0.122679E+10 | 0.441285E+09 | 0.785501E+09 | 0.00 | 0.00 |
July | 0.165260E+10 | 0.148621E+09 | 0.132300E+10 | 0.512347E+09 | 0.810657E+09 | 0.00 | 0.00 |
August | 0.128668E+10 | 0.180916E+09 | 0.106917E+10 | 0.394521E+09 | 0.674650E+09 | 0.00 | 0.00 |
September | 0.852995E+09 | 0.326586E+09 | 0.810913E+09 | 0.294067E+09 | 0.516847E+09 | 0.00 | 0.00 |
October | 0.425375E+09 | 0.571294E+09 | 0.539896E+09 | 0.172305E+09 | 0.367590E+09 | 0.00 | 0.00 |
November | 0.141012E+09 | 0.883136E+09 | 0.323835E+09 | 85826290.04 | 0.238009E+09 | 0.00 | 0.00 |
December | 57293580.34 | 0.148659E+10 | 0.291808E+09 | 79717529.27 | 0.212090E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.916660E+10 | 0.817745E+10 | 0.956416E+10 | 0.356261E+10 | 0.600155E+10 | 0.00 | 0.00 |
Minimum of Months | 57293580.34 | 0.148621E+09 | 0.291808E+09 | 79717529.27 | 0.212090E+09 | 0.00 | 0.00 |
Maximum of Months | 0.165260E+10 | 0.153279E+10 | 0.132300E+10 | 0.512347E+09 | 0.810657E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.350644E+09 | 0.368994E+09 | 0.405560E+09 | 0.282494E+09 | 0.123066E+09 | 0.00 | 0.00 |
February | 0.436566E+09 | 0.286710E+09 | 0.457623E+09 | 0.307814E+09 | 0.149809E+09 | 0.00 | 0.00 |
March | 0.435299E+09 | 0.264606E+09 | 0.445801E+09 | 0.280665E+09 | 0.165136E+09 | 0.00 | 0.00 |
April | 0.414711E+09 | 0.175117E+09 | 0.394359E+09 | 0.214026E+09 | 0.180333E+09 | 0.00 | 0.00 |
May | 0.403944E+09 | 96209639.31 | 0.348882E+09 | 0.123403E+09 | 0.225479E+09 | 0.00 | 0.00 |
June | 0.367714E+09 | 59911379.90 | 0.296682E+09 | 78479200.34 | 0.218203E+09 | 0.00 | 0.00 |
July | 0.436860E+09 | 54409748.66 | 0.337347E+09 | 0.107700E+09 | 0.229647E+09 | 0.00 | 0.00 |
August | 0.447325E+09 | 65583945.47 | 0.357857E+09 | 0.149035E+09 | 0.208822E+09 | 0.00 | 0.00 |
September | 0.419673E+09 | 0.109307E+09 | 0.365078E+09 | 0.191135E+09 | 0.173943E+09 | 0.00 | 0.00 |
October | 0.341735E+09 | 0.174386E+09 | 0.335108E+09 | 0.199743E+09 | 0.135365E+09 | 0.00 | 0.00 |
November | 0.256259E+09 | 0.235194E+09 | 0.283052E+09 | 0.177383E+09 | 0.105669E+09 | 0.00 | 0.00 |
December | 0.250161E+09 | 0.354567E+09 | 0.311488E+09 | 0.204236E+09 | 0.107252E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.456089E+10 | 0.224500E+10 | 0.433884E+10 | 0.231611E+10 | 0.202272E+10 | 0.00 | 0.00 |
Minimum of Months | 0.250161E+09 | 54409748.66 | 0.283052E+09 | 78479200.34 | 0.105669E+09 | 0.00 | 0.00 |
Maximum of Months | 0.447325E+09 | 0.368994E+09 | 0.457623E+09 | 0.307814E+09 | 0.229647E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 622665.40 | 0.476076E+09 | 58564743.59 | 0.00 | 58564743.59 | 0.00 | 0.00 |
February | 7462055.86 | 0.338611E+09 | 81254233.52 | 0.00 | 81254233.52 | 0.00 | 0.00 |
March | 23685849.52 | 0.284633E+09 | 0.110706E+09 | 4319.21 | 0.110701E+09 | 0.00 | 0.00 |
April | 78130635.36 | 0.159416E+09 | 0.140894E+09 | 1464174.14 | 0.139430E+09 | 0.00 | 0.00 |
May | 0.203633E+09 | 74659799.57 | 0.204240E+09 | 10912202.62 | 0.193328E+09 | 0.00 | 0.00 |
June | 0.264657E+09 | 44470279.75 | 0.220936E+09 | 24701429.37 | 0.196234E+09 | 0.00 | 0.00 |
July | 0.273882E+09 | 39183449.02 | 0.218249E+09 | 19264914.72 | 0.198984E+09 | 0.00 | 0.00 |
August | 0.191151E+09 | 48689803.90 | 0.165667E+09 | 3181908.07 | 0.162485E+09 | 0.00 | 0.00 |
September | 0.109211E+09 | 92759677.40 | 0.124804E+09 | 130789.97 | 0.124674E+09 | 0.00 | 0.00 |
October | 40435324.73 | 0.169256E+09 | 89399861.49 | 0.00 | 89399861.49 | 0.00 | 0.00 |
November | 5874299.74 | 0.269643E+09 | 57284547.47 | 0.00 | 57284547.47 | 0.00 | 0.00 |
December | 10999.54 | 0.456931E+09 | 49620698.88 | 0.00 | 49620698.88 | 0.00 | 0.00 |
Annual Sum or Average | 0.119876E+10 | 0.245433E+10 | 0.152162E+10 | 59659738.10 | 0.146196E+10 | 0.00 | 0.00 |
Minimum of Months | 10999.54 | 39183449.02 | 49620698.88 | 0.00 | 49620698.88 | 0.00 | 0.00 |
Maximum of Months | 0.273882E+09 | 0.476076E+09 | 0.220936E+09 | 24701429.37 | 0.198984E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.482772E+09 | 0.136587E+10 | 0.806050E+09 | 0.477286E+09 | 0.328764E+09 | 0.00 | 0.00 |
February | 0.772813E+09 | 0.101485E+10 | 0.100112E+10 | 0.569413E+09 | 0.431711E+09 | 0.00 | 0.00 |
March | 0.102296E+10 | 0.895474E+09 | 0.120257E+10 | 0.675181E+09 | 0.527388E+09 | 0.00 | 0.00 |
April | 0.134994E+10 | 0.537649E+09 | 0.135282E+10 | 0.730925E+09 | 0.621895E+09 | 0.00 | 0.00 |
May | 0.159137E+10 | 0.272783E+09 | 0.140119E+10 | 0.579692E+09 | 0.821495E+09 | 0.00 | 0.00 |
June | 0.175119E+10 | 0.165126E+09 | 0.142466E+10 | 0.601896E+09 | 0.822761E+09 | 0.00 | 0.00 |
July | 0.188650E+10 | 0.147202E+09 | 0.149066E+10 | 0.637271E+09 | 0.853385E+09 | 0.00 | 0.00 |
August | 0.155788E+10 | 0.179176E+09 | 0.127021E+10 | 0.545742E+09 | 0.724473E+09 | 0.00 | 0.00 |
September | 0.121729E+10 | 0.320111E+09 | 0.109588E+10 | 0.525791E+09 | 0.570088E+09 | 0.00 | 0.00 |
October | 0.754732E+09 | 0.555739E+09 | 0.816915E+09 | 0.399374E+09 | 0.417540E+09 | 0.00 | 0.00 |
November | 0.427010E+09 | 0.828859E+09 | 0.600688E+09 | 0.304052E+09 | 0.296637E+09 | 0.00 | 0.00 |
December | 0.326425E+09 | 0.133745E+10 | 0.623959E+09 | 0.343479E+09 | 0.280479E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.131409E+11 | 0.762029E+10 | 0.130867E+11 | 0.639010E+10 | 0.669662E+10 | 0.00 | 0.00 |
Minimum of Months | 0.326425E+09 | 0.147202E+09 | 0.600688E+09 | 0.304052E+09 | 0.280479E+09 | 0.00 | 0.00 |
Maximum of Months | 0.188650E+10 | 0.136587E+10 | 0.149066E+10 | 0.730925E+09 | 0.853385E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 87246488.30 | 0.151176E+10 | 0.372196E+09 | 0.124099E+09 | 0.248097E+09 | 0.00 | 0.00 |
February | 0.245567E+09 | 0.107067E+10 | 0.530536E+09 | 0.184569E+09 | 0.345967E+09 | 0.00 | 0.00 |
March | 0.511930E+09 | 0.913101E+09 | 0.783570E+09 | 0.324285E+09 | 0.459286E+09 | 0.00 | 0.00 |
April | 0.927272E+09 | 0.531557E+09 | 0.103587E+10 | 0.465169E+09 | 0.570698E+09 | 0.00 | 0.00 |
May | 0.133386E+10 | 0.266174E+09 | 0.122026E+10 | 0.439047E+09 | 0.781218E+09 | 0.00 | 0.00 |
June | 0.160902E+10 | 0.161299E+09 | 0.132986E+10 | 0.534650E+09 | 0.795214E+09 | 0.00 | 0.00 |
July | 0.167036E+10 | 0.144290E+09 | 0.134166E+10 | 0.526697E+09 | 0.814967E+09 | 0.00 | 0.00 |
August | 0.122792E+10 | 0.176010E+09 | 0.102986E+10 | 0.363387E+09 | 0.666474E+09 | 0.00 | 0.00 |
September | 0.821802E+09 | 0.316479E+09 | 0.795425E+09 | 0.286988E+09 | 0.508437E+09 | 0.00 | 0.00 |
October | 0.373856E+09 | 0.557568E+09 | 0.509681E+09 | 0.149645E+09 | 0.360036E+09 | 0.00 | 0.00 |
November | 0.121940E+09 | 0.867982E+09 | 0.318399E+09 | 82278208.38 | 0.236121E+09 | 0.00 | 0.00 |
December | 50802525.19 | 0.147076E+10 | 0.296539E+09 | 88133196.08 | 0.208405E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.898158E+10 | 0.798765E+10 | 0.956387E+10 | 0.356895E+10 | 0.599492E+10 | 0.00 | 0.00 |
Minimum of Months | 50802525.19 | 0.144290E+09 | 0.296539E+09 | 82278208.38 | 0.208405E+09 | 0.00 | 0.00 |
Maximum of Months | 0.167036E+10 | 0.151176E+10 | 0.134166E+10 | 0.534650E+09 | 0.814967E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.623126E+09 | 0.165157E+10 | 0.100561E+10 | 0.612085E+09 | 0.393520E+09 | 0.00 | 0.00 |
February | 0.892806E+09 | 0.128449E+10 | 0.116757E+10 | 0.666947E+09 | 0.500619E+09 | 0.00 | 0.00 |
March | 0.968106E+09 | 0.115620E+10 | 0.120575E+10 | 0.608133E+09 | 0.597620E+09 | 0.00 | 0.00 |
April | 0.109329E+10 | 0.691355E+09 | 0.115969E+10 | 0.466907E+09 | 0.692782E+09 | 0.00 | 0.00 |
May | 0.135953E+10 | 0.329202E+09 | 0.119838E+10 | 0.291019E+09 | 0.907363E+09 | 0.00 | 0.00 |
June | 0.141849E+10 | 0.192065E+09 | 0.112145E+10 | 0.223554E+09 | 0.897894E+09 | 0.00 | 0.00 |
July | 0.158608E+10 | 0.173836E+09 | 0.120374E+10 | 0.275090E+09 | 0.928647E+09 | 0.00 | 0.00 |
August | 0.143145E+10 | 0.212936E+09 | 0.113427E+10 | 0.329812E+09 | 0.804455E+09 | 0.00 | 0.00 |
September | 0.118609E+10 | 0.397647E+09 | 0.106139E+10 | 0.414420E+09 | 0.646970E+09 | 0.00 | 0.00 |
October | 0.842347E+09 | 0.703192E+09 | 0.919756E+09 | 0.432788E+09 | 0.486968E+09 | 0.00 | 0.00 |
November | 0.527686E+09 | 0.106441E+10 | 0.737393E+09 | 0.384340E+09 | 0.353052E+09 | 0.00 | 0.00 |
December | 0.419497E+09 | 0.163878E+10 | 0.782404E+09 | 0.442523E+09 | 0.339881E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.123485E+11 | 0.949568E+10 | 0.126974E+11 | 0.514762E+10 | 0.754977E+10 | 0.00 | 0.00 |
Minimum of Months | 0.419497E+09 | 0.173836E+09 | 0.737393E+09 | 0.223554E+09 | 0.339881E+09 | 0.00 | 0.00 |
Maximum of Months | 0.158608E+10 | 0.165157E+10 | 0.120575E+10 | 0.666947E+09 | 0.928647E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.492592E+09 | 0.137889E+10 | 0.814281E+09 | 0.483337E+09 | 0.330945E+09 | 0.00 | 0.00 |
February | 0.805549E+09 | 0.103120E+10 | 0.102090E+10 | 0.590858E+09 | 0.430046E+09 | 0.00 | 0.00 |
March | 0.105103E+10 | 0.913237E+09 | 0.120886E+10 | 0.684993E+09 | 0.523871E+09 | 0.00 | 0.00 |
April | 0.129402E+10 | 0.553966E+09 | 0.129755E+10 | 0.675529E+09 | 0.622018E+09 | 0.00 | 0.00 |
May | 0.166931E+10 | 0.291278E+09 | 0.145847E+10 | 0.643155E+09 | 0.815310E+09 | 0.00 | 0.00 |
June | 0.161683E+10 | 0.173269E+09 | 0.132158E+10 | 0.508531E+09 | 0.813049E+09 | 0.00 | 0.00 |
July | 0.186006E+10 | 0.156142E+09 | 0.147200E+10 | 0.622921E+09 | 0.849075E+09 | 0.00 | 0.00 |
August | 0.160628E+10 | 0.186766E+09 | 0.130952E+10 | 0.576875E+09 | 0.732650E+09 | 0.00 | 0.00 |
September | 0.123729E+10 | 0.329309E+09 | 0.111137E+10 | 0.532870E+09 | 0.578497E+09 | 0.00 | 0.00 |
October | 0.797798E+09 | 0.559026E+09 | 0.847129E+09 | 0.422034E+09 | 0.425095E+09 | 0.00 | 0.00 |
November | 0.440369E+09 | 0.834003E+09 | 0.606125E+09 | 0.307600E+09 | 0.298525E+09 | 0.00 | 0.00 |
December | 0.317208E+09 | 0.134289E+10 | 0.619228E+09 | 0.335064E+09 | 0.284165E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.131883E+11 | 0.774998E+10 | 0.130870E+11 | 0.638377E+10 | 0.670324E+10 | 0.00 | 0.00 |
Minimum of Months | 0.317208E+09 | 0.156142E+09 | 0.606125E+09 | 0.307600E+09 | 0.284165E+09 | 0.00 | 0.00 |
Maximum of Months | 0.186006E+10 | 0.137889E+10 | 0.147200E+10 | 0.684993E+09 | 0.849075E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.111940E+09 | 0.153963E+10 | 0.380427E+09 | 0.130149E+09 | 0.250278E+09 | 0.00 | 0.00 |
February | 0.298662E+09 | 0.110632E+10 | 0.550316E+09 | 0.206014E+09 | 0.344302E+09 | 0.00 | 0.00 |
March | 0.552946E+09 | 0.943729E+09 | 0.789866E+09 | 0.334097E+09 | 0.455769E+09 | 0.00 | 0.00 |
April | 0.879888E+09 | 0.550671E+09 | 0.980594E+09 | 0.409773E+09 | 0.570821E+09 | 0.00 | 0.00 |
May | 0.140789E+10 | 0.278470E+09 | 0.127754E+10 | 0.502510E+09 | 0.775033E+09 | 0.00 | 0.00 |
June | 0.147174E+10 | 0.165498E+09 | 0.122679E+10 | 0.441285E+09 | 0.785501E+09 | 0.00 | 0.00 |
July | 0.164129E+10 | 0.149401E+09 | 0.132300E+10 | 0.512347E+09 | 0.810657E+09 | 0.00 | 0.00 |
August | 0.127702E+10 | 0.182024E+09 | 0.106917E+10 | 0.394521E+09 | 0.674650E+09 | 0.00 | 0.00 |
September | 0.847143E+09 | 0.326563E+09 | 0.810913E+09 | 0.294067E+09 | 0.516847E+09 | 0.00 | 0.00 |
October | 0.426168E+09 | 0.566680E+09 | 0.539896E+09 | 0.172305E+09 | 0.367590E+09 | 0.00 | 0.00 |
November | 0.142417E+09 | 0.878768E+09 | 0.323835E+09 | 85826290.04 | 0.238009E+09 | 0.00 | 0.00 |
December | 56804164.39 | 0.149164E+10 | 0.291808E+09 | 79717529.27 | 0.212090E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.911392E+10 | 0.817939E+10 | 0.956416E+10 | 0.356261E+10 | 0.600155E+10 | 0.00 | 0.00 |
Minimum of Months | 56804164.39 | 0.149401E+09 | 0.291808E+09 | 79717529.27 | 0.212090E+09 | 0.00 | 0.00 |
Maximum of Months | 0.164129E+10 | 0.153963E+10 | 0.132300E+10 | 0.512347E+09 | 0.810657E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.628946E+09 | 0.700859E+09 | 0.743638E+09 | 0.517983E+09 | 0.225655E+09 | 0.00 | 0.00 |
February | 0.789671E+09 | 0.530178E+09 | 0.839102E+09 | 0.564410E+09 | 0.274692E+09 | 0.00 | 0.00 |
March | 0.792744E+09 | 0.477426E+09 | 0.817426E+09 | 0.514631E+09 | 0.302795E+09 | 0.00 | 0.00 |
April | 0.763782E+09 | 0.295338E+09 | 0.723100E+09 | 0.392440E+09 | 0.330660E+09 | 0.00 | 0.00 |
May | 0.748596E+09 | 0.151285E+09 | 0.639713E+09 | 0.226272E+09 | 0.413441E+09 | 0.00 | 0.00 |
June | 0.685865E+09 | 88540385.28 | 0.543999E+09 | 0.143900E+09 | 0.400099E+09 | 0.00 | 0.00 |
July | 0.810909E+09 | 78072724.66 | 0.618562E+09 | 0.197480E+09 | 0.421082E+09 | 0.00 | 0.00 |
August | 0.827613E+09 | 94970146.65 | 0.656170E+09 | 0.273273E+09 | 0.382897E+09 | 0.00 | 0.00 |
September | 0.775295E+09 | 0.171904E+09 | 0.669410E+09 | 0.350467E+09 | 0.318943E+09 | 0.00 | 0.00 |
October | 0.632119E+09 | 0.291777E+09 | 0.614457E+09 | 0.366251E+09 | 0.248206E+09 | 0.00 | 0.00 |
November | 0.466138E+09 | 0.428154E+09 | 0.519007E+09 | 0.325252E+09 | 0.193755E+09 | 0.00 | 0.00 |
December | 0.446760E+09 | 0.677651E+09 | 0.571148E+09 | 0.374490E+09 | 0.196658E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.836844E+10 | 0.398616E+10 | 0.795573E+10 | 0.424685E+10 | 0.370888E+10 | 0.00 | 0.00 |
Minimum of Months | 0.446760E+09 | 78072724.66 | 0.519007E+09 | 0.143900E+09 | 0.193755E+09 | 0.00 | 0.00 |
Maximum of Months | 0.827613E+09 | 0.700859E+09 | 0.839102E+09 | 0.564410E+09 | 0.421082E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 4602716.08 | 0.379279E+10 | 0.512354E+09 | 0.00 | 0.512354E+09 | 0.00 | 0.00 |
February | 61494005.09 | 0.284867E+10 | 0.710853E+09 | 0.00 | 0.710853E+09 | 0.00 | 0.00 |
March | 0.200508E+09 | 0.246087E+10 | 0.968510E+09 | 37786.62 | 0.968472E+09 | 0.00 | 0.00 |
April | 0.691315E+09 | 0.138685E+10 | 0.123261E+10 | 12809340.58 | 0.121980E+10 | 0.00 | 0.00 |
May | 0.182082E+10 | 0.658962E+09 | 0.178680E+10 | 95465502.22 | 0.169133E+10 | 0.00 | 0.00 |
June | 0.236096E+10 | 0.400347E+09 | 0.193286E+10 | 0.216101E+09 | 0.171676E+10 | 0.00 | 0.00 |
July | 0.244885E+10 | 0.354004E+09 | 0.190935E+10 | 0.168539E+09 | 0.174081E+10 | 0.00 | 0.00 |
August | 0.171756E+10 | 0.437697E+09 | 0.144934E+10 | 27836951.19 | 0.142150E+10 | 0.00 | 0.00 |
September | 0.981284E+09 | 0.809585E+09 | 0.109185E+10 | 1144217.24 | 0.109071E+10 | 0.00 | 0.00 |
October | 0.359830E+09 | 0.146348E+10 | 0.782115E+09 | 0.00 | 0.782115E+09 | 0.00 | 0.00 |
November | 50173944.60 | 0.236267E+10 | 0.501154E+09 | 0.00 | 0.501154E+09 | 0.00 | 0.00 |
December | 22293.05 | 0.373267E+10 | 0.434107E+09 | 0.00 | 0.434107E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.106974E+11 | 0.207086E+11 | 0.133119E+11 | 0.521934E+09 | 0.127900E+11 | 0.00 | 0.00 |
Minimum of Months | 22293.05 | 0.354004E+09 | 0.434107E+09 | 0.00 | 0.434107E+09 | 0.00 | 0.00 |
Maximum of Months | 0.244885E+10 | 0.379279E+10 | 0.193286E+10 | 0.216101E+09 | 0.174081E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 4155899.97 | 0.381665E+10 | 0.512354E+09 | 0.00 | 0.512354E+09 | 0.00 | 0.00 |
February | 58831800.90 | 0.287250E+10 | 0.710853E+09 | 0.00 | 0.710853E+09 | 0.00 | 0.00 |
March | 0.194630E+09 | 0.249010E+10 | 0.968510E+09 | 37786.62 | 0.968472E+09 | 0.00 | 0.00 |
April | 0.677203E+09 | 0.141186E+10 | 0.123261E+10 | 12809340.58 | 0.121980E+10 | 0.00 | 0.00 |
May | 0.179603E+10 | 0.677304E+09 | 0.178680E+10 | 95465502.22 | 0.169133E+10 | 0.00 | 0.00 |
June | 0.233356E+10 | 0.416324E+09 | 0.193286E+10 | 0.216101E+09 | 0.171676E+10 | 0.00 | 0.00 |
July | 0.242158E+10 | 0.370502E+09 | 0.190935E+10 | 0.168539E+09 | 0.174081E+10 | 0.00 | 0.00 |
August | 0.169484E+10 | 0.457861E+09 | 0.144934E+10 | 27836951.19 | 0.142150E+10 | 0.00 | 0.00 |
September | 0.965046E+09 | 0.833517E+09 | 0.109185E+10 | 1144217.24 | 0.109071E+10 | 0.00 | 0.00 |
October | 0.349982E+09 | 0.149340E+10 | 0.782115E+09 | 0.00 | 0.782115E+09 | 0.00 | 0.00 |
November | 47667047.41 | 0.239656E+10 | 0.501154E+09 | 0.00 | 0.501154E+09 | 0.00 | 0.00 |
December | 7099.44 | 0.375952E+10 | 0.434107E+09 | 0.00 | 0.434107E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.105435E+11 | 0.209961E+11 | 0.133119E+11 | 0.521934E+09 | 0.127900E+11 | 0.00 | 0.00 |
Minimum of Months | 7099.44 | 0.370502E+09 | 0.434107E+09 | 0.00 | 0.434107E+09 | 0.00 | 0.00 |
Maximum of Months | 0.242158E+10 | 0.381665E+10 | 0.193286E+10 | 0.216101E+09 | 0.174081E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.718066E+09 | 0.217882E+10 | 0.117820E+10 | 0.601368E+09 | 0.576836E+09 | 0.00 | 0.00 |
February | 0.120113E+10 | 0.173366E+10 | 0.153160E+10 | 0.753955E+09 | 0.777644E+09 | 0.00 | 0.00 |
March | 0.178272E+10 | 0.156142E+10 | 0.198605E+10 | 0.999420E+09 | 0.986628E+09 | 0.00 | 0.00 |
April | 0.264288E+10 | 0.947423E+09 | 0.238857E+10 | 0.119603E+10 | 0.119254E+10 | 0.00 | 0.00 |
May | 0.345477E+10 | 0.480728E+09 | 0.262131E+10 | 0.101868E+10 | 0.160264E+10 | 0.00 | 0.00 |
June | 0.390716E+10 | 0.292567E+09 | 0.275437E+10 | 0.113647E+10 | 0.161790E+10 | 0.00 | 0.00 |
July | 0.414643E+10 | 0.250455E+09 | 0.283217E+10 | 0.116390E+10 | 0.166827E+10 | 0.00 | 0.00 |
August | 0.331823E+10 | 0.287048E+09 | 0.229996E+10 | 0.909078E+09 | 0.139088E+10 | 0.00 | 0.00 |
September | 0.245817E+10 | 0.520784E+09 | 0.189121E+10 | 0.812738E+09 | 0.107847E+10 | 0.00 | 0.00 |
October | 0.141705E+10 | 0.923316E+09 | 0.132654E+10 | 0.548999E+09 | 0.777541E+09 | 0.00 | 0.00 |
November | 0.686989E+09 | 0.143499E+10 | 0.919052E+09 | 0.386318E+09 | 0.532734E+09 | 0.00 | 0.00 |
December | 0.482395E+09 | 0.217487E+10 | 0.920464E+09 | 0.431600E+09 | 0.488864E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.262160E+11 | 0.127861E+11 | 0.226495E+11 | 0.995855E+10 | 0.126909E+11 | 0.00 | 0.00 |
Minimum of Months | 0.482395E+09 | 0.250455E+09 | 0.919052E+09 | 0.386318E+09 | 0.488864E+09 | 0.00 | 0.00 |
Maximum of Months | 0.414643E+10 | 0.217882E+10 | 0.283217E+10 | 0.119603E+10 | 0.166827E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.146593E+10 | 0.280679E+10 | 0.206861E+10 | 0.131855E+10 | 0.750052E+09 | 0.00 | 0.00 |
February | 0.195730E+10 | 0.222802E+10 | 0.237966E+10 | 0.143674E+10 | 0.942924E+09 | 0.00 | 0.00 |
March | 0.205476E+10 | 0.203634E+10 | 0.241281E+10 | 0.131003E+10 | 0.110277E+10 | 0.00 | 0.00 |
April | 0.220113E+10 | 0.123414E+10 | 0.226323E+10 | 0.100337E+10 | 0.125986E+10 | 0.00 | 0.00 |
May | 0.255362E+10 | 0.593420E+09 | 0.224094E+10 | 0.608714E+09 | 0.163223E+10 | 0.00 | 0.00 |
June | 0.257781E+10 | 0.343965E+09 | 0.204737E+10 | 0.440385E+09 | 0.160698E+10 | 0.00 | 0.00 |
July | 0.293342E+10 | 0.304140E+09 | 0.222911E+10 | 0.560471E+09 | 0.166864E+10 | 0.00 | 0.00 |
August | 0.273050E+10 | 0.380029E+09 | 0.216715E+10 | 0.705173E+09 | 0.146198E+10 | 0.00 | 0.00 |
September | 0.234215E+10 | 0.712877E+09 | 0.207831E+10 | 0.892526E+09 | 0.118578E+10 | 0.00 | 0.00 |
October | 0.173308E+10 | 0.125021E+10 | 0.183224E+10 | 0.932313E+09 | 0.899932E+09 | 0.00 | 0.00 |
November | 0.114429E+10 | 0.187986E+10 | 0.149296E+10 | 0.827946E+09 | 0.665010E+09 | 0.00 | 0.00 |
December | 0.100181E+10 | 0.280665E+10 | 0.160270E+10 | 0.953284E+09 | 0.649417E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.246958E+11 | 0.165764E+11 | 0.248151E+11 | 0.109895E+11 | 0.138256E+11 | 0.00 | 0.00 |
Minimum of Months | 0.100181E+10 | 0.304140E+09 | 0.149296E+10 | 0.440385E+09 | 0.649417E+09 | 0.00 | 0.00 |
Maximum of Months | 0.293342E+10 | 0.280679E+10 | 0.241281E+10 | 0.143674E+10 | 0.166864E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -16.9 | -17.4 | -20.0 | 3.73 | -31.9 | 33.25 | 98.18 | 0.00 |
February | -11.6 | -12.7 | -16.7 | 4.33 | -26.7 | 48.91 | 138.70 | 0.00 |
March | -6.2 | -7.6 | -10.8 | 3.55 | -19.4 | 56.69 | 163.76 | 0.01 |
April | 3.97 | 0.41 | -4.8 | 4.72 | -9.1 | 70.41 | 207.70 | 0.01 |
May | 13.43 | 8.45 | 3.53 | 3.60 | 2.20 | 102.27 | 202.62 | 0.00 |
June | 18.03 | 14.19 | 11.55 | 3.74 | 7.84 | 104.36 | 210.60 | 0.06 |
July | 19.67 | 16.51 | 14.78 | 3.14 | 8.97 | 101.67 | 223.82 | 0.04 |
August | 17.94 | 15.20 | 13.59 | 3.45 | 8.99 | 87.39 | 175.79 | 0.04 |
September | 12.29 | 9.87 | 7.80 | 3.78 | 3.34 | 70.27 | 143.96 | 0.00 |
October | 5.42 | 3.47 | 1.07 | 3.53 | -4.7 | 51.74 | 90.11 | 0.00 |
November | -2.0 | -3.6 | -6.9 | 4.42 | -13.7 | 34.68 | 65.95 | 0.00 |
December | -14.6 | -15.1 | -18.1 | 3.91 | -28.3 | 29.58 | 68.99 | 0.00 |
Annual Sum or Average | 3.36 | 1.04 | -2.0 | 3.82 | -8.4 | 66.03 | 149.18 | 0.01 |
Minimum of Months | -16.9 | -17.4 | -20.0 | 3.14 | -31.9 | 29.58 | 65.95 | 0.00 |
Maximum of Months | 19.67 | 16.51 | 14.78 | 4.72 | 8.99 | 104.36 | 223.82 | 0.06 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 1.10 | 29-JAN-14:00 | -1.0 | -4.4 | 2.60 | -11.4 | 145.00 | 110.00 |
February | 8.90 | 20-FEB-15:00 | 2.87 | -6.7 | 8.80 | -9.0 | 49.00 | 646.00 |
March | 11.10 | 26-MAR-15:00 | 5.48 | -1.1 | 5.20 | -5.7 | 53.00 | 842.00 |
April | 26.70 | 23-APR-15:00 | 16.95 | 11.10 | 11.30 | 12.03 | 75.50 | 811.00 |
May | 29.40 | 25-MAY-17:00 | 19.26 | 13.90 | 1.50 | 16.49 | 47.50 | 582.00 |
June | 35.00 | 29-JUN-15:00 | 24.72 | 21.10 | 6.70 | 24.66 | 132.00 | 705.00 |
July | 31.10 | 15-JUL-14:20 | 25.35 | 23.33 | 8.07 | 19.93 | 299.67 | 518.33 |
August | 30.60 | 08-AUG-14:00 | 23.36 | 20.60 | 6.70 | 17.93 | 163.50 | 672.50 |
September | 26.10 | 01-SEP-14:00 | 17.82 | 13.30 | 3.60 | 14.28 | 112.00 | 751.50 |
October | 22.20 | 19-OCT-14:00 | 13.62 | 7.20 | 6.70 | 8.15 | 35.50 | 701.50 |
November | 18.30 | 01-NOV-14:00 | 13.44 | 10.00 | 3.10 | 11.84 | 105.00 | 30.50 |
December | 1.10 | 28-DEC-02:00 | 0.43 | -0.6 | 4.60 | -5.5 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 1.10 | -1.0 | -6.7 | 1.50 | -11.4 | 0.00 | 0.00 | |
Maximum of Months | 35.00 | 25.35 | 23.33 | 11.30 | 24.66 | 299.67 | 842.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -35.6 | 06-JAN-08:00 | -35.7 | -37.8 | 0.00 | -57.8 | 27.00 | 381.00 |
February | -33.3 | 14-FEB-06:00 | -33.4 | -36.7 | 0.00 | -55.6 | 0.00 | 0.00 |
March | -28.9 | 05-MAR-06:00 | -29.1 | -32.2 | 1.50 | -50.6 | 27.00 | 41.50 |
April | -13.9 | 05-APR-05:00 | -14.4 | -16.1 | 0.00 | -32.5 | 14.50 | 199.00 |
May | -3.9 | 01-MAY-05:00 | -6.2 | -12.2 | 0.00 | -22.4 | 35.00 | 415.00 |
June | 1.10 | 04-JUN-04:00 | 0.62 | 0.00 | 0.00 | -14.9 | 37.00 | 169.50 |
July | 6.10 | 02-JUL-04:00 | 6.10 | 6.10 | 0.00 | -8.8 | 33.50 | 204.50 |
August | 4.40 | 19-AUG-03:00 | 4.40 | 4.40 | 0.00 | -10.7 | 0.00 | 0.00 |
September | 1.10 | 06-SEP-03:00 | 1.10 | 1.10 | 0.00 | -14.7 | 0.00 | 0.00 |
October | -10.0 | 30-OCT-03:00 | -10.7 | -12.8 | 1.50 | -28.2 | 0.00 | 0.00 |
November | -20.6 | 29-NOV-05:00 | -20.8 | -22.2 | 2.10 | -37.8 | 0.00 | 0.00 |
December | -31.1 | 24-DEC-06:19 | -31.3 | -35.1 | 3.33 | -53.1 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -35.6 | -35.7 | -37.8 | 0.00 | -57.8 | 0.00 | 0.00 | |
Maximum of Months | 6.10 | 6.10 | 6.10 | 3.33 | -8.8 | 37.00 | 415.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -0.5 | 16-JAN-12:00 | 0.00 | -1.1 | 5.70 | -6.6 | 172.50 | 3.00 |
February | 3.34 | 21-FEB-12:00 | 6.70 | -1.1 | 7.70 | -6.0 | 270.00 | 303.00 |
March | 5.48 | 26-MAR-15:00 | 11.10 | -1.1 | 5.20 | -5.7 | 53.00 | 842.00 |
April | 16.95 | 23-APR-15:00 | 26.70 | 11.10 | 11.30 | 12.03 | 75.50 | 811.00 |
May | 19.91 | 26-MAY-11:00 | 25.60 | 17.20 | 6.20 | 22.64 | 300.50 | 6.00 |
June | 24.72 | 29-JUN-15:00 | 35.00 | 21.10 | 6.70 | 24.66 | 132.00 | 705.00 |
July | 25.76 | 15-JUL-13:00 | 31.10 | 23.90 | 7.70 | 18.99 | 333.00 | 421.00 |
August | 23.36 | 08-AUG-14:00 | 30.60 | 20.60 | 6.70 | 17.93 | 163.50 | 672.50 |
September | 18.67 | 01-SEP-00:00 | 19.00 | 17.50 | 2.80 | 16.30 | 0.00 | 0.00 |
October | 13.72 | 19-OCT-13:00 | 21.70 | 7.80 | 5.70 | 7.75 | 54.50 | 739.00 |
November | 14.29 | 21-NOV-12:00 | 15.00 | 13.90 | 5.20 | 11.46 | 134.50 | 25.50 |
December | 0.43 | 28-DEC-02:00 | 1.10 | -0.6 | 4.60 | -5.5 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -0.5 | 0.00 | -1.1 | 2.80 | -6.6 | 0.00 | 0.00 | |
Maximum of Months | 25.76 | 35.00 | 23.90 | 11.30 | 24.66 | 333.00 | 842.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -1.1 | 16-JAN-11:00 | -0.6 | -0.8 | 5.70 | -7.3 | 164.50 | 5.00 |
February | -0.6 | 21-FEB-08:00 | 4.40 | 2.25 | 8.80 | -6.6 | 123.00 | 89.50 |
March | 0.00 | 29-MAR-20:00 | 1.70 | 0.95 | 1.50 | -4.8 | 0.00 | 0.00 |
April | 11.10 | 23-APR-13:00 | 24.40 | 16.08 | 10.80 | 9.72 | 98.50 | 903.50 |
May | 17.20 | 26-MAY-11:00 | 25.60 | 19.91 | 6.20 | 22.64 | 300.50 | 6.00 |
June | 22.80 | 29-JUN-23:19 | 26.30 | 23.71 | 5.20 | 14.28 | 0.00 | 0.00 |
July | 23.90 | 15-JUL-13:00 | 31.10 | 25.76 | 7.70 | 18.99 | 333.00 | 421.00 |
August | 20.60 | 08-AUG-14:00 | 30.60 | 23.36 | 6.70 | 17.93 | 163.50 | 672.50 |
September | 17.92 | 01-SEP-00:10 | 19.75 | 18.15 | 3.22 | 13.23 | 0.00 | 0.00 |
October | 12.20 | 07-OCT-12:20 | 14.47 | 13.17 | 3.43 | 9.20 | 163.17 | 18.50 |
November | 13.90 | 21-NOV-12:00 | 15.00 | 14.29 | 5.20 | 11.46 | 134.50 | 25.50 |
December | -0.0 | 05-DEC-17:00 | 0.00 | -0.0 | 1.50 | -6.4 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -1.1 | -0.6 | -0.8 | 1.50 | -7.3 | 0.00 | 0.00 | |
Maximum of Months | 23.90 | 31.10 | 25.76 | 10.80 | 22.64 | 333.00 | 903.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 1.89 | 11.66 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 0.58 | 19.92 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 0.81 | 26.63 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 2.58 | 37.52 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 5.43 | 45.25 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 8.61 | 47.76 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 11.25 | 48.86 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 12.66 | 38.94 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 12.41 | 29.23 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 10.60 | 17.37 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 7.72 | 10.89 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 4.55 | 9.11 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 6.63 | 28.63 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 0.58 | 9.11 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 12.66 | 48.86 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH BOOSTER E WATER HEATER
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.772071E+10 | -0.754279E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -177919659.2 | 81.21 | 0.00 | 0.00 |
February | 0.696980E+10 | -0.681596E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -153835771.8 | 81.21 | 0.00 | 0.00 |
March | 0.770801E+10 | -0.754146E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -166545565.7 | 81.21 | 0.00 | 0.00 |
April | 0.746796E+10 | -0.730859E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -159370599.9 | 81.21 | 0.00 | 0.00 |
May | 0.770696E+10 | -0.754280E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164157564.4 | 81.21 | 0.00 | 0.00 |
June | 0.745920E+10 | -0.730053E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -158668636.8 | 81.21 | 0.00 | 0.00 |
July | 0.771478E+10 | -0.755086E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -163927004.2 | 81.21 | 0.00 | 0.00 |
August | 0.770690E+10 | -0.754281E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164094276.6 | 81.21 | 0.00 | 0.00 |
September | 0.746903E+10 | -0.730994E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -159081683.9 | 81.21 | 0.00 | 0.00 |
October | 0.770636E+10 | -0.754144E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164924647.2 | 81.21 | 0.00 | 0.00 |
November | 0.745264E+10 | -0.729242E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -160218302.3 | 81.21 | 0.00 | 0.00 |
December | 0.772592E+10 | -0.755086E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -175057823.3 | 81.21 | 0.00 | 0.00 |
Annual Sum or Average | 0.908083E+11 | -0.888405E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.196780E+10 | 81.21 | 0.00 | 0.00 |
Minimum of Months | 0.696980E+10 | -0.755086E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -177919659.2 | 81.21 | 0.00 | 0.00 |
Maximum of Months | 0.772592E+10 | -0.681596E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -153835771.8 | 81.21 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH LAUNDRY G WATER HEATER
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.129408E+12 | -0.127534E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.187454E+10 | 80.09 | 0.00 | 0.00 |
February | 0.117010E+12 | -0.115387E+12 | 0.00 | 0.00 | 672.00 | 0.00 | -0.162293E+10 | 79.75 | 0.00 | 0.00 |
March | 0.129498E+12 | -0.127719E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.177904E+10 | 79.82 | 0.00 | 0.00 |
April | 0.125072E+12 | -0.123342E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.172994E+10 | 80.28 | 0.00 | 0.00 |
May | 0.128832E+12 | -0.127022E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.181003E+10 | 81.03 | 0.00 | 0.00 |
June | 0.121030E+12 | -0.119271E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.175922E+10 | 81.31 | 0.00 | 0.00 |
July | 0.120380E+12 | -0.118564E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.181590E+10 | 81.27 | 0.00 | 0.00 |
August | 0.117971E+12 | -0.116158E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.181384E+10 | 81.26 | 0.00 | 0.00 |
September | 0.114575E+12 | -0.112822E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.175348E+10 | 81.27 | 0.00 | 0.00 |
October | 0.121504E+12 | -0.119693E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.181076E+10 | 81.27 | 0.00 | 0.00 |
November | 0.122588E+12 | -0.120834E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.175424E+10 | 81.32 | 0.00 | 0.00 |
December | 0.129004E+12 | -0.127145E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.185883E+10 | 80.79 | 0.00 | 0.00 |
Annual Sum or Average | 0.147687E+13 | -0.145549E+13 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.213827E+11 | 80.80 | 0.00 | 0.00 |
Minimum of Months | 0.114575E+12 | -0.127719E+12 | 0.00 | 0.00 | 672.00 | 0.00 | -0.187454E+10 | 79.75 | 0.00 | 0.00 |
Maximum of Months | 0.129498E+12 | -0.112822E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.162293E+10 | 81.32 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.851474E+11 | -0.834307E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.171667E+10 | 58.99 | 0.00 | 0.00 |
February | 0.785731E+11 | -0.771072E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.146596E+10 | 58.99 | 0.00 | 0.00 |
March | 0.866810E+11 | -0.850854E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.159566E+10 | 58.99 | 0.00 | 0.00 |
April | 0.813362E+11 | -0.797993E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.153691E+10 | 58.99 | 0.00 | 0.00 |
May | 0.798780E+11 | -0.782902E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.158778E+10 | 58.98 | 0.00 | 0.00 |
June | 0.728299E+11 | -0.712939E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.153605E+10 | 58.98 | 0.00 | 0.00 |
July | 0.713250E+11 | -0.697391E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.158593E+10 | 58.98 | 0.00 | 0.00 |
August | 0.693369E+11 | -0.677535E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.158344E+10 | 58.98 | 0.00 | 0.00 |
September | 0.674136E+11 | -0.658839E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.152971E+10 | 58.98 | 0.00 | 0.00 |
October | 0.722766E+11 | -0.706979E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.157874E+10 | 58.98 | 0.00 | 0.00 |
November | 0.740177E+11 | -0.724893E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.152841E+10 | 58.98 | 0.00 | 0.00 |
December | 0.812100E+11 | -0.795444E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.166559E+10 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.920026E+12 | -0.901115E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.189108E+11 | 58.98 | 0.00 | 0.00 |
Minimum of Months | 0.674136E+11 | -0.850854E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.171667E+10 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.866810E+11 | -0.658839E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.146596E+10 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 243.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 265.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 254.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 296.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 437.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 401.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 409.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 352.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 344.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 299.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 255.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 226.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3785.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 226.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 437.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.567976E+12 | 512883.64 | 06-JAN-09:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.319930E+12 | 502587.20 | 14-FEB-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.174748E+12 | 482514.74 | 05-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.154465E+11 | 138388.97 | 05-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.148045E+09 | 38679.79 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 8383946.74 | 10049.98 | 03-JUN-09:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 2270258.03 | 3783.76 | 08-JUL-20:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 4201101.32 | 4129.32 | 02-AUG-20:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 21490004.68 | 12834.05 | 19-SEP-16:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.502683E+10 | 98310.69 | 30-OCT-06:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.789943E+11 | 194658.71 | 25-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.490773E+12 | 492611.75 | 24-DEC-23:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.165308E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 2270258.03 | 3783.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.567976E+12 | 512883.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BASEMENT VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.229735E+11 | 14793.31 | 06-JAN-09:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.170287E+11 | 14490.59 | 14-FEB-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.176723E+11 | 13900.47 | 05-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.162960E+11 | 9922.82 | 22-APR-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.157216E+11 | 9970.29 | 18-MAY-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.137236E+11 | 10025.12 | 25-JUN-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.103213E+11 | 10028.69 | 29-JUL-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.568052E+10 | 9975.74 | 25-AUG-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.304674E+10 | 9954.10 | 01-SEP-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.190134E+10 | 6587.62 | 19-OCT-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.205011E+10 | 5323.55 | 17-NOV-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.188539E+11 | 14197.33 | 24-DEC-23:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.145270E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.190134E+10 | 5323.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.229735E+11 | 14793.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.111355E+11 | 6525.94 | 06-JAN-09:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.772565E+10 | 6390.19 | 14-FEB-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.699772E+10 | 6126.02 | 05-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.505833E+10 | 3594.97 | 05-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.391943E+10 | 2949.28 | 01-MAY-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.348085E+10 | 2751.58 | 04-JUN-04:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.309103E+10 | 2678.23 | 08-JUL-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.329113E+10 | 2754.19 | 15-AUG-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.400000E+10 | 2735.95 | 21-SEP-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.563289E+10 | 3709.28 | 30-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.703420E+10 | 4172.17 | 25-NOV-03:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.109387E+11 | 6258.84 | 24-DEC-23:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.723054E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.309103E+10 | 2678.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.111355E+11 | 6525.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_2_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.416762E+10 | 2636.88 | 06-JAN-09:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.278569E+10 | 2582.41 | 14-FEB-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.213091E+10 | 2476.32 | 05-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.125509E+10 | 1361.61 | 04-APR-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.812724E+09 | 1298.35 | 01-MAY-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.707853E+09 | 1208.42 | 14-JUN-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.584641E+09 | 1172.81 | 10-JUL-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.631430E+09 | 1137.40 | 19-AUG-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.832497E+09 | 1156.38 | 29-SEP-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.129193E+10 | 1211.14 | 13-OCT-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.180899E+10 | 1383.18 | 26-NOV-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.386269E+10 | 2529.67 | 24-DEC-23:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.208721E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.584641E+09 | 1137.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.416762E+10 | 2636.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: MECH_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.660634E+10 | 3853.52 | 06-JAN-09:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.489991E+10 | 3773.05 | 14-FEB-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.410436E+10 | 3616.51 | 05-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.253168E+10 | 1942.95 | 05-APR-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.148172E+10 | 1599.34 | 01-MAY-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.106105E+10 | 1250.43 | 04-JUN-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.867605E+09 | 1215.02 | 10-JUL-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.107640E+10 | 1308.94 | 19-AUG-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.155295E+10 | 1348.77 | 23-SEP-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.241430E+10 | 1629.31 | 30-OCT-03:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.328319E+10 | 2041.17 | 25-NOV-05:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.623040E+10 | 3695.20 | 24-DEC-23:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.361099E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.867605E+09 | 1215.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.660634E+10 | 3853.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: STORAGE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.400982E+10 | 2280.32 | 06-JAN-09:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.304930E+10 | 2232.39 | 14-FEB-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.265622E+10 | 2139.22 | 05-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.170593E+10 | 1136.35 | 05-APR-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.102398E+10 | 922.61 | 01-MAY-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.719551E+09 | 700.02 | 04-JUN-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.592333E+09 | 645.72 | 10-JUL-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.745353E+09 | 710.31 | 19-AUG-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.109170E+10 | 758.08 | 23-SEP-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.165604E+10 | 968.99 | 30-OCT-03:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.218725E+10 | 1272.05 | 25-NOV-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.381484E+10 | 2186.05 | 24-DEC-23:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.232523E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.592333E+09 | 645.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.400982E+10 | 2280.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LAUNDRY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.254797E+11 | 20754.26 | 06-JAN-09:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.173406E+11 | 20329.38 | 14-FEB-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.151281E+11 | 19501.15 | 05-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.128004E+11 | 13919.58 | 22-APR-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.130332E+11 | 13986.45 | 18-MAY-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.130112E+11 | 14063.38 | 25-JUN-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.136071E+11 | 14068.39 | 29-JUL-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.132194E+11 | 13994.11 | 25-AUG-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.124674E+11 | 13963.75 | 01-SEP-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.128941E+11 | 12745.54 | 21-OCT-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.130920E+11 | 12838.09 | 25-NOV-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.234498E+11 | 19917.78 | 24-DEC-23:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.185523E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.124674E+11 | 12745.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.254797E+11 | 20754.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAFE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.290884E+11 | 19812.21 | 06-JAN-09:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.178908E+11 | 19402.91 | 14-FEB-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.147789E+11 | 18605.82 | 05-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.978387E+10 | 10372.27 | 27-APR-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.735830E+10 | 9057.48 | 12-MAY-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.659816E+10 | 9504.62 | 09-JUN-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.568245E+10 | 9069.65 | 03-JUL-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.584056E+10 | 9843.82 | 15-AUG-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.739459E+10 | 9545.91 | 19-SEP-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.113480E+11 | 10286.76 | 06-OCT-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.149037E+11 | 11635.94 | 24-NOV-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.279210E+11 | 19006.67 | 24-DEC-23:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.158589E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.568245E+10 | 9057.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.290884E+11 | 19812.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LOBBY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.740919E+11 | 51372.21 | 06-JAN-09:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.442535E+11 | 50312.96 | 14-FEB-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.317083E+11 | 48249.69 | 05-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.178444E+11 | 24801.54 | 27-APR-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.129902E+11 | 22984.11 | 09-MAY-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.120151E+11 | 22521.95 | 13-JUN-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.105295E+11 | 21691.64 | 10-JUL-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.105177E+11 | 22329.05 | 18-AUG-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.120747E+11 | 23184.98 | 29-SEP-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.187610E+11 | 23940.01 | 06-OCT-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.267848E+11 | 26929.50 | 26-NOV-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.677453E+11 | 49287.35 | 24-DEC-23:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.339316E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.105177E+11 | 21691.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.740919E+11 | 51372.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.365360E+11 | 21347.79 | 06-JAN-09:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.243356E+11 | 20901.94 | 14-FEB-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.182225E+11 | 20034.67 | 05-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.837995E+10 | 8730.04 | 05-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.201318E+10 | 5670.74 | 09-MAY-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.932885E+09 | 4919.52 | 10-JUN-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.113228E+09 | 4077.09 | 09-JUL-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.779609E+09 | 5605.71 | 18-AUG-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.365924E+10 | 6690.33 | 21-SEP-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.105444E+11 | 9122.43 | 30-OCT-06:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.176380E+11 | 12196.92 | 25-NOV-09:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.347854E+11 | 20470.66 | 24-DEC-23:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.157940E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.113228E+09 | 4077.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.365360E+11 | 21347.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.232776E+11 | 13586.62 | 06-JAN-09:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.165576E+11 | 13301.53 | 14-FEB-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.134837E+11 | 12747.26 | 05-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.787337E+10 | 6575.21 | 05-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.377189E+10 | 4588.97 | 01-MAY-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.233369E+10 | 4013.34 | 04-JUN-04:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.147498E+10 | 3277.84 | 08-JUL-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.247233E+10 | 3700.99 | 19-AUG-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.477805E+10 | 3903.65 | 28-SEP-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.858105E+10 | 6446.63 | 30-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.122690E+11 | 8049.92 | 25-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.221523E+11 | 13025.85 | 24-DEC-23:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.119026E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.147498E+10 | 3277.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.232776E+11 | 13586.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BANQUET_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.222827E+11 | 20979.78 | 06-JAN-09:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.114314E+11 | 20547.66 | 14-FEB-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.621774E+10 | 19705.85 | 05-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.204644E+10 | 8146.96 | 05-APR-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.713565E+09 | 6847.48 | 01-MAY-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.433227E+09 | 5496.42 | 16-JUN-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.381175E+09 | 5729.02 | 31-JUL-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.587098E+09 | 5965.35 | 25-AUG-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.104300E+10 | 6592.26 | 13-SEP-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.222802E+10 | 6926.46 | 18-OCT-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.397263E+10 | 7255.29 | 29-NOV-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.188886E+11 | 20129.23 | 24-DEC-23:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.702255E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.381175E+09 | 5496.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.222827E+11 | 20979.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: DINING_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.221542E+11 | 21743.40 | 06-JAN-09:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.111250E+11 | 21295.65 | 14-FEB-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.566673E+10 | 20423.40 | 05-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.151312E+10 | 7668.89 | 05-APR-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.375088E+09 | 6324.81 | 01-MAY-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.206983E+09 | 4875.85 | 16-JUN-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.203375E+09 | 5135.01 | 31-JUL-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.297764E+09 | 5477.55 | 25-AUG-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.626984E+09 | 6036.12 | 13-SEP-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.169323E+10 | 6493.88 | 18-OCT-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.332971E+10 | 6886.31 | 29-NOV-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.187064E+11 | 20862.09 | 24-DEC-23:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.658986E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.203375E+09 | 4875.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.221542E+11 | 21743.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: KITCHEN_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.124190E+11 | 16188.25 | 06-JAN-09:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.620382E+10 | 15856.49 | 14-FEB-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.356798E+10 | 15209.86 | 05-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.180854E+10 | 5785.00 | 05-APR-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.111457E+10 | 4451.82 | 01-MAY-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.774229E+09 | 3850.24 | 04-JUN-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.671468E+09 | 3379.56 | 10-JUL-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.779340E+09 | 3793.10 | 19-AUG-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115271E+10 | 4019.51 | 21-SEP-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.176219E+10 | 5698.11 | 30-OCT-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.242326E+10 | 6819.66 | 29-NOV-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.105235E+11 | 15535.13 | 24-DEC-23:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.432006E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.671468E+09 | 3379.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.124190E+11 | 16188.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: FLR_3_DOAS HEATING COIL
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.487227E+11 | 45518.63 | 06-JAN-09:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.268877E+11 | 44604.81 | 14-FEB-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145431E+11 | 42823.35 | 05-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.125033E+10 | 9740.81 | 05-APR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 15028082.90 | 1609.75 | 01-MAY-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 24892.06 | 0.46 | 08-JUN-19:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 25079.47 | 0.46 | 18-JUL-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 29610.65 | 0.46 | 20-AUG-17:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 14716.18 | 0.46 | 17-SEP-18:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.425335E+09 | 7538.95 | 30-OCT-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.739218E+10 | 15790.30 | 29-NOV-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.428840E+11 | 43719.47 | 24-DEC-23:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.142120E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 14716.18 | 0.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.487227E+11 | 45518.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.105312E+11 | 8922.75 | 16-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.603041E+10 | 8920.87 | 12-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.402375E+10 | 8921.55 | 04-MAR-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.124227E+10 | 8919.60 | 04-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.102066E+09 | 5917.96 | 01-MAY-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 22978329.62 | 3684.97 | 13-JUN-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 4529407.67 | 3535.58 | 09-JUL-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 24029772.83 | 2905.96 | 14-AUG-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.162215E+09 | 4093.40 | 28-SEP-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.142250E+10 | 8920.09 | 30-OCT-15:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.411789E+10 | 8921.87 | 06-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.100481E+11 | 8923.20 | 17-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.377319E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 4529407.67 | 2905.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.105312E+11 | 8923.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.120677E+11 | 8827.67 | 16-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.740762E+10 | 8825.97 | 08-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.504046E+10 | 8826.87 | 22-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.158035E+10 | 8825.43 | 06-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.129944E+09 | 7694.92 | 01-MAY-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 22209812.80 | 3731.18 | 11-JUN-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 4575329.55 | 2902.13 | 10-JUL-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 26761483.97 | 2934.56 | 07-AUG-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.215511E+09 | 4673.92 | 28-SEP-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.176855E+10 | 8824.95 | 30-OCT-15:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.488807E+10 | 8827.83 | 09-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.112845E+11 | 8828.12 | 17-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.444363E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 4575329.55 | 2902.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.120677E+11 | 8828.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.262512E+11 | 48559.85 | 09-JAN-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.878252E+10 | 46462.56 | 17-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.234327E+10 | 39442.69 | 05-MAR-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.314152E+10 | 19406.54 | 25-NOV-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.265473E+11 | 46817.69 | 24-DEC-03:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.670658E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.265473E+11 | 48559.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.534821E+11 | 48803.11 | 11-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.299712E+11 | 48805.23 | 01-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.170856E+11 | 48797.93 | 15-MAR-15:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.206756E+10 | 47069.17 | 05-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 74800143.69 | 32037.66 | 06-MAY-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 27223190.36 | 29237.18 | 02-JUN-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 17765770.00 | 17251.95 | 24-JUL-08:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 39432381.23 | 29193.17 | 07-AUG-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 88915515.03 | 30170.28 | 05-SEP-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.102520E+10 | 47020.93 | 30-OCT-15:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.111792E+11 | 48801.50 | 25-NOV-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.466879E+11 | 48811.94 | 27-DEC-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.161747E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 17765770.00 | 17251.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.534821E+11 | 48811.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.105445E+11 | 8739.14 | 16-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.603361E+10 | 8737.20 | 12-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.400755E+10 | 8737.91 | 04-MAR-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.121212E+10 | 8706.69 | 26-APR-15:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.122787E+09 | 3230.97 | 19-MAY-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 13441488.36 | 2775.37 | 22-JUN-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 3511337.09 | 2764.19 | 22-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 20195272.48 | 2873.58 | 14-AUG-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.185325E+09 | 3707.11 | 28-SEP-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.149753E+10 | 8699.59 | 29-OCT-18:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.418245E+10 | 8738.23 | 06-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.100525E+11 | 8739.62 | 17-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.378755E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 3511337.09 | 2764.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.105445E+11 | 8739.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.121487E+11 | 8673.14 | 06-JAN-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.744392E+10 | 8633.09 | 09-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.504066E+10 | 8633.95 | 01-MAR-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.150746E+10 | 8618.46 | 03-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.158226E+09 | 3450.30 | 19-MAY-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 14295950.40 | 2874.62 | 22-JUN-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 4140870.71 | 2822.36 | 09-JUL-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 23321225.85 | 3041.30 | 31-AUG-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.249672E+09 | 4291.03 | 28-SEP-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.187267E+10 | 8632.03 | 30-OCT-15:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.493326E+10 | 8634.03 | 06-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.112960E+11 | 8635.45 | 17-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.446923E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 4140870.71 | 2822.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.121487E+11 | 8673.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.323130E+10 | 2625.53 | 16-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.201339E+10 | 2625.13 | 09-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.142165E+10 | 2625.40 | 22-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.485862E+09 | 2625.27 | 26-APR-18:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 48288006.31 | 2325.21 | 01-MAY-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 10374267.01 | 850.85 | 11-JUN-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 1124345.90 | 843.45 | 09-JUL-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 9562580.69 | 786.53 | 07-AUG-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 74735504.47 | 1624.04 | 28-SEP-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.564987E+09 | 2625.62 | 13-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.147960E+10 | 2625.88 | 20-NOV-16:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.316776E+10 | 2625.75 | 06-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.125086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 1124345.90 | 786.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.323130E+10 | 2625.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.366973E+10 | 2589.93 | 16-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.242964E+10 | 2589.66 | 05-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.174696E+10 | 2590.33 | 21-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.601204E+09 | 2589.70 | 10-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 59163758.09 | 2528.14 | 01-MAY-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 10162738.53 | 864.09 | 11-JUN-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 1149590.41 | 859.44 | 09-JUL-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 10385256.14 | 841.54 | 07-AUG-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.100043E+09 | 1783.49 | 28-SEP-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.688525E+09 | 2590.20 | 14-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172499E+10 | 2590.41 | 20-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.349852E+10 | 2590.16 | 06-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.145405E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 1149590.41 | 841.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.366973E+10 | 2590.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.110390E+11 | 12610.33 | 17-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.614465E+10 | 12607.61 | 03-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.413107E+10 | 12609.32 | 02-MAR-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.123961E+10 | 12507.80 | 26-APR-15:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.106907E+09 | 5537.83 | 21-MAY-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 23841386.18 | 4278.69 | 09-JUN-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5957462.71 | 4349.33 | 22-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 17664996.61 | 4573.19 | 16-AUG-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 98896077.21 | 4273.22 | 16-SEP-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.128269E+10 | 12481.71 | 30-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.424776E+10 | 12609.98 | 27-NOV-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.111191E+11 | 12611.14 | 05-DEC-16:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.394571E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 5957462.71 | 4273.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.111191E+11 | 12611.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.284230E+11 | 0.284230E+11 | 280174.90 | 23-APR-18:10 | 280174.90 | 0.02 |
May | 0.00 | 0.00 | 0.193467E+12 | 0.187838E+12 | 427274.18 | 26-MAY-10:35 | 276056.15 | 0.32 |
June | 0.00 | 0.00 | 0.485694E+12 | 0.336951E+12 | 651274.61 | 19-JUN-18:30 | 248217.98 | 0.64 |
July | 0.00 | 0.00 | 0.664927E+12 | 0.426354E+12 | 654318.98 | 23-JUL-10:35 | 340076.30 | 0.86 |
August | 0.00 | 0.00 | 0.486034E+12 | 0.332034E+12 | 560575.35 | 08-AUG-17:13 | 326809.55 | 0.84 |
September | 0.00 | 0.00 | 0.129382E+12 | 0.105940E+12 | 413057.24 | 01-SEP-10:40 | 280904.59 | 0.29 |
October | 0.00 | 0.00 | 0.182107E+11 | 0.182107E+11 | 230822.19 | 19-OCT-15:40 | 230822.19 | 0.03 |
November | 0.00 | 0.00 | 0.291286E+10 | 0.290003E+10 | 125198.68 | 01-NOV-15:00 | 125198.68 | 0.02 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.200905E+13 | 0.143865E+13 | 0.25 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.664927E+12 | 0.426354E+12 | 654318.98 | 340076.30 | 0.86 |
Report: CoilReportMonthly
For: FLR_3_DOAS COOLING COIL
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.220642E+10 | 0.220642E+10 | 28765.73 | 23-APR-18:00 | 28765.73 | 0.02 |
May | 0.00 | 0.00 | 0.180867E+11 | 0.173404E+11 | 41735.47 | 26-MAY-13:10 | 27380.14 | 0.29 |
June | 0.00 | 0.00 | 0.470980E+11 | 0.325974E+11 | 64926.26 | 19-JUN-17:25 | 26688.87 | 0.59 |
July | 0.00 | 0.00 | 0.659880E+11 | 0.421316E+11 | 70530.37 | 04-JUL-02:50 | 24247.67 | 0.82 |
August | 0.00 | 0.00 | 0.467551E+11 | 0.315323E+11 | 57886.29 | 30-AUG-08:50 | 24525.57 | 0.77 |
September | 0.00 | 0.00 | 0.106497E+11 | 0.879579E+10 | 41432.33 | 01-SEP-10:25 | 25771.45 | 0.22 |
October | 0.00 | 0.00 | 0.144271E+10 | 0.144271E+10 | 24823.32 | 19-OCT-15:00 | 24823.32 | 0.03 |
November | 0.00 | 0.00 | 0.223309E+09 | 0.223309E+09 | 12273.97 | 01-NOV-15:00 | 12273.97 | 0.01 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.192450E+12 | 0.136270E+12 | 0.23 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.659880E+11 | 0.421316E+11 | 70530.37 | 28765.73 | 0.82 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 1719532.54 | 1719532.54 | 5074.43 | 27-JAN-16:01 | 5074.43 | 0.00 |
February | 0.00 | 0.00 | 0.197438E+09 | 0.197438E+09 | 19208.77 | 04-FEB-16:01 | 19208.77 | 0.00 |
March | 0.00 | 0.00 | 0.816027E+09 | 0.816027E+09 | 19224.97 | 28-MAR-18:02 | 19224.97 | 0.00 |
April | 0.00 | 0.00 | 0.266526E+10 | 0.255612E+10 | 19237.10 | 18-APR-15:02 | 19237.10 | 0.04 |
May | 0.00 | 0.00 | 0.654952E+10 | 0.493466E+10 | 20130.28 | 26-MAY-08:61 | 17582.98 | 0.48 |
June | 0.00 | 0.00 | 0.813006E+10 | 0.494509E+10 | 23076.56 | 19-JUN-18:01 | 15969.75 | 0.80 |
July | 0.00 | 0.00 | 0.106873E+11 | 0.616527E+10 | 22820.45 | 23-JUL-08:62 | 16118.11 | 0.92 |
August | 0.00 | 0.00 | 0.845207E+10 | 0.459793E+10 | 22330.11 | 30-AUG-08:62 | 15327.97 | 0.86 |
September | 0.00 | 0.00 | 0.422706E+10 | 0.257206E+10 | 22041.15 | 18-SEP-18:01 | 16331.54 | 0.59 |
October | 0.00 | 0.00 | 0.136382E+10 | 0.996476E+09 | 19237.50 | 21-OCT-15:02 | 19237.50 | 0.16 |
November | 0.00 | 0.00 | 46317255.19 | 43704134.24 | 19203.89 | 17-NOV-16:01 | 19203.89 | 0.00 |
December | 0.00 | 0.00 | 245870.86 | 245870.86 | 2346.62 | 28-DEC-16:04 | 2346.62 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.431369E+11 | 0.278267E+11 | 0.32 | |||
Minimum of Months | 0.00 | 0.00 | 245870.86 | 245870.86 | 2346.62 | 2346.62 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.106873E+11 | 0.616527E+10 | 23076.56 | 19237.50 | 0.92 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 180638.34 | 180638.34 | 2107.45 | 17-JAN-16:04 | 2107.45 | 0.00 |
February | 0.00 | 0.00 | 35570615.21 | 35570615.21 | 16403.43 | 28-FEB-16:02 | 16403.43 | 0.00 |
March | 0.00 | 0.00 | 0.338035E+09 | 0.338035E+09 | 18318.19 | 28-MAR-18:02 | 18318.19 | 0.00 |
April | 0.00 | 0.00 | 0.164754E+10 | 0.156369E+10 | 18328.81 | 18-APR-15:02 | 18328.81 | 0.03 |
May | 0.00 | 0.00 | 0.552891E+10 | 0.407177E+10 | 19074.30 | 26-MAY-08:61 | 16810.75 | 0.45 |
June | 0.00 | 0.00 | 0.751055E+10 | 0.455893E+10 | 21536.28 | 25-JUN-08:61 | 15476.79 | 0.78 |
July | 0.00 | 0.00 | 0.969528E+10 | 0.552347E+10 | 21706.09 | 23-JUL-08:62 | 15382.22 | 0.90 |
August | 0.00 | 0.00 | 0.697450E+10 | 0.360807E+10 | 20998.89 | 30-AUG-08:62 | 14585.83 | 0.82 |
September | 0.00 | 0.00 | 0.280449E+10 | 0.163644E+10 | 20932.48 | 18-SEP-18:01 | 15395.66 | 0.47 |
October | 0.00 | 0.00 | 0.538034E+09 | 0.413026E+09 | 18329.52 | 21-OCT-15:02 | 18329.52 | 0.07 |
November | 0.00 | 0.00 | 6995961.74 | 5340435.15 | 8523.12 | 17-NOV-16:01 | 8523.12 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.350801E+11 | 0.217545E+11 | 0.30 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.969528E+10 | 0.552347E+10 | 21706.09 | 18329.52 | 0.90 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.143624E+09 | 0.143624E+09 | 14028.50 | 27-JAN-15:00 | 14028.50 | 0.00 |
February | 0.00 | 0.00 | 0.324991E+10 | 0.324991E+10 | 43602.61 | 22-FEB-14:00 | 43602.61 | 0.00 |
March | 0.00 | 0.00 | 0.764897E+10 | 0.764897E+10 | 51687.18 | 20-MAR-12:30 | 51687.18 | 0.00 |
April | 0.00 | 0.00 | 0.210919E+11 | 0.206590E+11 | 57688.11 | 13-APR-13:00 | 57688.11 | 0.02 |
May | 0.00 | 0.00 | 0.367091E+11 | 0.282477E+11 | 53825.10 | 18-MAY-13:00 | 51158.08 | 0.36 |
June | 0.00 | 0.00 | 0.400986E+11 | 0.233313E+11 | 56619.27 | 30-JUN-13:00 | 49577.88 | 0.69 |
July | 0.00 | 0.00 | 0.529749E+11 | 0.272267E+11 | 63353.81 | 23-JUL-14:10 | 50267.88 | 0.93 |
August | 0.00 | 0.00 | 0.494592E+11 | 0.262223E+11 | 63644.99 | 26-AUG-14:50 | 50682.51 | 0.90 |
September | 0.00 | 0.00 | 0.359257E+11 | 0.260231E+11 | 63178.39 | 01-SEP-15:30 | 50270.17 | 0.49 |
October | 0.00 | 0.00 | 0.196049E+11 | 0.182957E+11 | 79891.34 | 22-OCT-12:20 | 75601.68 | 0.08 |
November | 0.00 | 0.00 | 0.322766E+10 | 0.322766E+10 | 48309.57 | 17-NOV-12:20 | 48309.57 | 0.00 |
December | 0.00 | 0.00 | 38192706.26 | 38192706.26 | 7776.16 | 02-DEC-14:30 | 7776.16 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.270173E+12 | 0.184314E+12 | 0.29 | |||
Minimum of Months | 0.00 | 0.00 | 38192706.26 | 38192706.26 | 7776.16 | 7776.16 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.529749E+11 | 0.282477E+11 | 79891.34 | 75601.68 | 0.93 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 29386826.18 | 29386826.18 | 27450.00 | 17-JAN-19:04 | 27450.00 | 0.00 |
February | 0.00 | 0.00 | 0.253043E+09 | 0.253043E+09 | 28428.29 | 22-FEB-19:03 | 28428.29 | 0.00 |
March | 0.00 | 0.00 | 0.215104E+10 | 0.215104E+10 | 87868.49 | 28-MAR-18:02 | 87868.49 | 0.00 |
April | 0.00 | 0.00 | 0.144450E+11 | 0.138085E+11 | 92057.38 | 23-APR-08:61 | 92057.38 | 0.04 |
May | 0.00 | 0.00 | 0.458117E+11 | 0.371421E+11 | 99208.62 | 26-MAY-18:02 | 86795.73 | 0.38 |
June | 0.00 | 0.00 | 0.636034E+11 | 0.438954E+11 | 114062.34 | 25-JUN-08:61 | 80354.30 | 0.69 |
July | 0.00 | 0.00 | 0.736189E+11 | 0.477755E+11 | 114035.75 | 25-JUL-18:02 | 77605.61 | 0.76 |
August | 0.00 | 0.00 | 0.599045E+11 | 0.359310E+11 | 108631.79 | 07-AUG-18:02 | 82815.55 | 0.71 |
September | 0.00 | 0.00 | 0.352240E+11 | 0.217533E+11 | 106055.18 | 18-SEP-18:01 | 76485.74 | 0.64 |
October | 0.00 | 0.00 | 0.132828E+11 | 0.983406E+10 | 91486.05 | 01-OCT-18:01 | 91486.05 | 0.27 |
November | 0.00 | 0.00 | 0.241318E+10 | 0.176633E+10 | 80444.06 | 01-NOV-18:03 | 77910.72 | 0.06 |
December | 0.00 | 0.00 | 45356364.01 | 45356364.01 | 27832.60 | 28-DEC-19:04 | 27832.60 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.310782E+12 | 0.214385E+12 | 0.30 | |||
Minimum of Months | 0.00 | 0.00 | 29386826.18 | 29386826.18 | 27450.00 | 27450.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.736189E+11 | 0.477755E+11 | 114062.34 | 92057.38 | 0.76 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 719509.79 | 719509.79 | 2442.24 | 17-JAN-16:04 | 2442.24 | 0.00 |
February | 0.00 | 0.00 | 0.107861E+09 | 0.107861E+09 | 16814.63 | 28-FEB-16:02 | 16814.63 | 0.00 |
March | 0.00 | 0.00 | 0.596770E+09 | 0.596770E+09 | 17523.57 | 26-MAR-15:01 | 17523.57 | 0.00 |
April | 0.00 | 0.00 | 0.274582E+10 | 0.263858E+10 | 17540.14 | 18-APR-08:62 | 17540.14 | 0.04 |
May | 0.00 | 0.00 | 0.617685E+10 | 0.457882E+10 | 18291.06 | 26-MAY-08:61 | 16072.41 | 0.48 |
June | 0.00 | 0.00 | 0.872326E+10 | 0.542873E+10 | 21062.05 | 19-JUN-18:01 | 14553.75 | 0.84 |
July | 0.00 | 0.00 | 0.107483E+11 | 0.625034E+10 | 21021.17 | 25-JUL-18:02 | 14578.50 | 0.94 |
August | 0.00 | 0.00 | 0.818791E+10 | 0.443746E+10 | 20486.83 | 30-AUG-08:62 | 14817.72 | 0.88 |
September | 0.00 | 0.00 | 0.415777E+10 | 0.250020E+10 | 19611.18 | 18-SEP-18:01 | 13833.31 | 0.59 |
October | 0.00 | 0.00 | 0.123828E+10 | 0.876598E+09 | 17539.11 | 21-OCT-15:02 | 17539.11 | 0.15 |
November | 0.00 | 0.00 | 0.113828E+09 | 0.111542E+09 | 16408.70 | 16-NOV-09:01 | 16408.70 | 0.00 |
December | 0.00 | 0.00 | 289380.13 | 289380.13 | 3067.84 | 28-DEC-09:04 | 3067.84 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.427977E+11 | 0.275279E+11 | 0.33 | |||
Minimum of Months | 0.00 | 0.00 | 289380.13 | 289380.13 | 2442.24 | 2442.24 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.107483E+11 | 0.625034E+10 | 21062.05 | 17540.14 | 0.94 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 5440157.14 | 5440157.14 | 3823.86 | 28-FEB-09:03 | 3823.86 | 0.00 |
March | 0.00 | 0.00 | 0.163858E+09 | 0.163858E+09 | 15974.99 | 26-MAR-08:61 | 15974.99 | 0.00 |
April | 0.00 | 0.00 | 0.155927E+10 | 0.148776E+10 | 16687.34 | 18-APR-08:62 | 16687.34 | 0.03 |
May | 0.00 | 0.00 | 0.511031E+10 | 0.367060E+10 | 17320.37 | 26-MAY-08:61 | 15334.72 | 0.47 |
June | 0.00 | 0.00 | 0.806652E+10 | 0.498479E+10 | 19420.49 | 19-JUN-18:01 | 14193.33 | 0.83 |
July | 0.00 | 0.00 | 0.972260E+10 | 0.554978E+10 | 19732.22 | 22-JUL-08:61 | 14020.46 | 0.93 |
August | 0.00 | 0.00 | 0.667011E+10 | 0.338908E+10 | 19258.13 | 30-AUG-08:62 | 14156.49 | 0.86 |
September | 0.00 | 0.00 | 0.267612E+10 | 0.151355E+10 | 18601.65 | 18-SEP-18:01 | 12982.99 | 0.49 |
October | 0.00 | 0.00 | 0.414063E+09 | 0.277199E+09 | 16304.04 | 01-OCT-15:01 | 16304.04 | 0.07 |
November | 0.00 | 0.00 | 12281386.68 | 10560932.42 | 4120.84 | 10-NOV-09:03 | 4120.84 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.344006E+11 | 0.210526E+11 | 0.31 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.972260E+10 | 0.554978E+10 | 19732.22 | 16687.34 | 0.93 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 636514.09 | 636514.09 | 997.22 | 17-JAN-16:03 | 997.22 | 0.00 |
February | 0.00 | 0.00 | 48749922.94 | 48749922.94 | 5030.97 | 04-FEB-16:01 | 5030.97 | 0.00 |
March | 0.00 | 0.00 | 0.209808E+09 | 0.209780E+09 | 5035.10 | 28-MAR-18:02 | 5035.10 | 0.00 |
April | 0.00 | 0.00 | 0.714528E+09 | 0.685206E+09 | 5038.32 | 18-APR-15:02 | 5038.32 | 0.04 |
May | 0.00 | 0.00 | 0.184891E+10 | 0.141824E+10 | 5368.48 | 26-MAY-08:61 | 4554.49 | 0.48 |
June | 0.00 | 0.00 | 0.231464E+10 | 0.147221E+10 | 6123.41 | 19-JUN-18:01 | 4136.99 | 0.79 |
July | 0.00 | 0.00 | 0.301288E+10 | 0.181631E+10 | 6119.71 | 22-JUL-08:61 | 4140.78 | 0.92 |
August | 0.00 | 0.00 | 0.237326E+10 | 0.136824E+10 | 6023.32 | 30-AUG-08:62 | 3912.51 | 0.86 |
September | 0.00 | 0.00 | 0.113912E+10 | 0.726649E+09 | 5822.45 | 18-SEP-18:01 | 4305.23 | 0.54 |
October | 0.00 | 0.00 | 0.346179E+09 | 0.263745E+09 | 5038.53 | 21-OCT-15:02 | 5038.53 | 0.13 |
November | 0.00 | 0.00 | 9727771.89 | 9439859.85 | 5029.72 | 17-NOV-16:01 | 5029.72 | 0.00 |
December | 0.00 | 0.00 | 189426.49 | 189426.49 | 514.73 | 28-DEC-16:04 | 514.73 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.120186E+11 | 0.801939E+10 | 0.32 | |||
Minimum of Months | 0.00 | 0.00 | 189426.49 | 189426.49 | 514.73 | 514.73 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.301288E+10 | 0.181631E+10 | 6123.41 | 5038.53 | 0.92 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 156991.87 | 156991.87 | 732.63 | 17-JAN-16:04 | 732.63 | 0.00 |
February | 0.00 | 0.00 | 6367175.92 | 6367175.92 | 2434.91 | 28-FEB-16:02 | 2434.91 | 0.00 |
March | 0.00 | 0.00 | 82746700.58 | 82729639.85 | 4779.34 | 28-MAR-18:02 | 4779.34 | 0.00 |
April | 0.00 | 0.00 | 0.440938E+09 | 0.420414E+09 | 4782.18 | 18-APR-15:02 | 4782.18 | 0.03 |
May | 0.00 | 0.00 | 0.156692E+10 | 0.117649E+10 | 5066.74 | 26-MAY-08:61 | 4338.57 | 0.46 |
June | 0.00 | 0.00 | 0.214269E+10 | 0.135909E+10 | 5709.01 | 25-JUN-08:61 | 3986.86 | 0.78 |
July | 0.00 | 0.00 | 0.274271E+10 | 0.162196E+10 | 5823.48 | 22-JUL-08:61 | 3922.70 | 0.92 |
August | 0.00 | 0.00 | 0.197105E+10 | 0.107760E+10 | 5644.09 | 30-AUG-08:62 | 3717.62 | 0.84 |
September | 0.00 | 0.00 | 0.754992E+09 | 0.464082E+09 | 5519.97 | 18-SEP-18:01 | 4073.93 | 0.42 |
October | 0.00 | 0.00 | 0.131387E+09 | 0.104339E+09 | 4782.28 | 21-OCT-15:02 | 4782.28 | 0.05 |
November | 0.00 | 0.00 | 1961849.86 | 1631576.94 | 827.19 | 15-NOV-19:04 | 827.19 | 0.00 |
December | 0.00 | 0.00 | 4014.15 | 4014.15 | 46.83 | 17-DEC-09:04 | 46.83 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.984192E+10 | 0.631485E+10 | 0.29 | |||
Minimum of Months | 0.00 | 0.00 | 4014.15 | 4014.15 | 46.83 | 46.83 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.274271E+10 | 0.162196E+10 | 5823.48 | 4782.28 | 0.92 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.632935E+09 | 0.632935E+09 | 24716.07 | 27-JAN-16:01 | 24716.07 | 0.00 |
February | 0.00 | 0.00 | 0.196386E+10 | 0.196386E+10 | 24757.59 | 21-FEB-16:02 | 24757.59 | 0.00 |
March | 0.00 | 0.00 | 0.279005E+10 | 0.279005E+10 | 24760.39 | 26-MAR-18:01 | 24760.39 | 0.00 |
April | 0.00 | 0.00 | 0.523213E+10 | 0.504739E+10 | 24776.45 | 18-APR-15:02 | 24776.45 | 0.05 |
May | 0.00 | 0.00 | 0.950798E+10 | 0.715071E+10 | 26000.20 | 26-MAY-08:61 | 22026.32 | 0.49 |
June | 0.00 | 0.00 | 0.115555E+11 | 0.694249E+10 | 31464.36 | 19-JUN-18:01 | 19609.19 | 0.83 |
July | 0.00 | 0.00 | 0.150538E+11 | 0.878655E+10 | 30995.45 | 25-JUL-18:02 | 19785.63 | 0.92 |
August | 0.00 | 0.00 | 0.137940E+11 | 0.807845E+10 | 29463.18 | 30-AUG-08:62 | 19398.81 | 0.88 |
September | 0.00 | 0.00 | 0.889837E+10 | 0.592335E+10 | 28151.74 | 18-SEP-18:01 | 20050.95 | 0.69 |
October | 0.00 | 0.00 | 0.463353E+10 | 0.371179E+10 | 24776.29 | 01-OCT-15:01 | 24776.29 | 0.27 |
November | 0.00 | 0.00 | 0.132545E+10 | 0.130276E+10 | 24740.36 | 16-NOV-16:02 | 24740.36 | 0.01 |
December | 0.00 | 0.00 | 0.321599E+09 | 0.321599E+09 | 24714.64 | 02-DEC-16:01 | 24714.64 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.757092E+11 | 0.526519E+11 | 0.35 | |||
Minimum of Months | 0.00 | 0.00 | 0.321599E+09 | 0.321599E+09 | 24714.64 | 19398.81 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.150538E+11 | 0.878655E+10 | 31464.36 | 24776.45 | 0.92 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 391604.00 | 914305.51 | 06-JAN-08:04 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 249793.08 | 882236.19 | 17-FEB-06:00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 139600.48 | 844161.73 | 05-MAR-07:00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 44176.44 | 257571.25 | 05-APR-08:61 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 24162.91 | 92865.93 | 01-MAY-08:03 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 21482.24 | 84398.22 | 02-JUN-08:05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 17834.27 | 75881.11 | 10-JUL-10:35 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17072.81 | 92138.16 | 07-AUG-08:05 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21013.16 | 86484.04 | 27-SEP-15:05 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 35631.23 | 246978.18 | 30-OCT-08:61 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 90715.91 | 369447.12 | 25-NOV-09:03 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 347421.06 | 881821.79 | 24-DEC-06:00 |
Annual Sum or Average | 0.00 | 116408.13 | ||||
Minimum of Months | 0.00 | 0.00 | 17072.81 | 75881.11 | ||
Maximum of Months | 0.00 | 0.00 | 391604.00 | 914305.51 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 667.53 | 31967.76 | 17-JAN-19:04 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 3719.53 | 98790.80 | 22-FEB-16:05 | 0.00 | 0.00 | 01-FEB-00:05 |
March | 7554.94 | 126827.44 | 19-MAR-15:03 | 0.00 | 0.00 | 01-MAR-00:03 |
April | 36050.26 | 517132.47 | 23-APR-18:03 | 0.00 | 0.00 | 01-APR-00:10 |
May | 131131.63 | 662270.36 | 25-MAY-18:03 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 273055.24 | 923898.96 | 29-JUN-18:03 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 352486.64 | 877457.52 | 15-JUL-15:03 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 266690.85 | 835003.60 | 08-AUG-15:03 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 98275.96 | 625920.37 | 18-SEP-18:01 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 27225.95 | 448645.08 | 19-OCT-15:02 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 5709.38 | 212310.83 | 01-NOV-15:03 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 390.16 | 28962.27 | 28-DEC-09:04 | 0.00 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 101006.72 | 0.00 | ||||
Minimum of Months | 390.16 | 28962.27 | 0.00 | 0.00 | ||
Maximum of Months | 352486.64 | 923898.96 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 32705.48 | 67628.49 | 31-JAN-07:40 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 33428.40 | 68316.98 | 27-FEB-07:20 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 33322.78 | 68249.26 | 01-MAR-07:50 |
April | 0.00 | 0.00 | 01-APR-00:10 | 32343.54 | 66885.38 | 03-APR-06:50 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 30790.40 | 64292.63 | 01-MAY-06:15 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 29068.78 | 60594.67 | 01-JUN-06:50 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27603.39 | 57003.83 | 03-JUL-06:10 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 26863.78 | 54769.27 | 01-AUG-06:40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26985.13 | 55243.73 | 29-SEP-06:10 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 27960.99 | 58128.93 | 31-OCT-06:10 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 29528.79 | 61675.50 | 30-NOV-08:00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 31256.99 | 65010.23 | 29-DEC-07:40 |
Annual Sum or Average | 0.00 | 30135.34 | ||||
Minimum of Months | 0.00 | 0.00 | 26863.78 | 54769.27 | ||
Maximum of Months | 0.00 | 0.00 | 33428.40 | 68316.98 |
Report: FanReportMonthly
For: FLR_3_DOAS FAN
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.587890E+10 | 0.92 | 2194.93 | 01-JAN-00:10 | 0.92 |
February | 0.530997E+10 | 0.92 | 2194.93 | 01-FEB-00:05 | 0.92 |
March | 0.587890E+10 | 0.92 | 2194.93 | 01-MAR-00:03 | 0.92 |
April | 0.568926E+10 | 0.92 | 2194.93 | 01-APR-00:10 | 0.92 |
May | 0.587890E+10 | 0.91 | 2194.93 | 01-MAY-00:10 | 0.92 |
June | 0.568926E+10 | 0.91 | 2194.93 | 01-JUN-00:10 | 0.91 |
July | 0.587890E+10 | 0.91 | 2194.93 | 01-JUL-00:10 | 0.91 |
August | 0.587890E+10 | 0.91 | 2194.93 | 01-AUG-00:10 | 0.91 |
September | 0.568926E+10 | 0.91 | 2194.93 | 01-SEP-00:10 | 0.91 |
October | 0.587890E+10 | 0.91 | 2194.93 | 01-OCT-00:10 | 0.91 |
November | 0.568926E+10 | 0.92 | 2194.93 | 01-NOV-00:10 | 0.92 |
December | 0.587890E+10 | 0.92 | 2194.93 | 01-DEC-00:05 | 0.92 |
Annual Sum or Average | 0.692193E+11 | 0.91 | |||
Minimum of Months | 0.530997E+10 | 0.91 | 2194.93 | 0.91 | |
Maximum of Months | 0.587890E+10 | 0.92 | 2194.93 | 0.92 |
Report: FanReportMonthly
For: VAV WITH REHEAT FAN
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.138611E+12 | 1.93 | 51770.51 | 02-JAN-20:10 | 1.93 |
February | 0.125199E+12 | 1.92 | 51770.51 | 03-FEB-20:10 | 1.93 |
March | 0.138618E+12 | 1.92 | 51770.51 | 01-MAR-11:35 | 1.92 |
April | 0.134154E+12 | 1.92 | 51770.51 | 01-APR-10:35 | 1.92 |
May | 0.138632E+12 | 1.91 | 51770.51 | 01-MAY-07:40 | 1.92 |
June | 0.134163E+12 | 1.90 | 51770.51 | 01-JUN-07:15 | 1.91 |
July | 0.138637E+12 | 1.90 | 51770.51 | 01-JUL-07:04 | 1.90 |
August | 0.138634E+12 | 1.90 | 51770.51 | 01-AUG-07:05 | 1.90 |
September | 0.134157E+12 | 1.91 | 51770.51 | 01-SEP-06:40 | 1.90 |
October | 0.138622E+12 | 1.91 | 51770.51 | 01-OCT-09:10 | 1.91 |
November | 0.134145E+12 | 1.92 | 51770.51 | 01-NOV-10:35 | 1.90 |
December | 0.138611E+12 | 1.93 | 51770.51 | 01-DEC-11:40 | 1.93 |
Annual Sum or Average | 0.163218E+13 | 1.91 | |||
Minimum of Months | 0.125199E+12 | 1.90 | 51770.51 | 1.90 | |
Maximum of Months | 0.138637E+12 | 1.93 | 51770.51 | 1.93 |
Report: FanReportMonthly
For: LAUNDRY_FLR_1 EXHAUST FAN
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.493775E+09 | 0.67 | 184.35 | 01-JAN-00:10 | 0.67 |
February | 0.445990E+09 | 0.67 | 184.35 | 01-FEB-00:05 | 0.67 |
March | 0.493775E+09 | 0.67 | 184.35 | 01-MAR-00:03 | 0.67 |
April | 0.477847E+09 | 0.67 | 184.35 | 01-APR-00:10 | 0.67 |
May | 0.493775E+09 | 0.67 | 184.35 | 01-MAY-00:10 | 0.67 |
June | 0.477847E+09 | 0.66 | 184.35 | 01-JUN-00:10 | 0.67 |
July | 0.493775E+09 | 0.66 | 184.35 | 01-JUL-00:10 | 0.66 |
August | 0.493775E+09 | 0.66 | 184.35 | 01-AUG-00:10 | 0.66 |
September | 0.477847E+09 | 0.66 | 184.35 | 01-SEP-00:10 | 0.66 |
October | 0.493775E+09 | 0.67 | 184.35 | 01-OCT-00:10 | 0.67 |
November | 0.477847E+09 | 0.67 | 184.35 | 01-NOV-00:10 | 0.67 |
December | 0.493775E+09 | 0.67 | 184.35 | 01-DEC-00:05 | 0.67 |
Annual Sum or Average | 0.581380E+10 | 0.67 | |||
Minimum of Months | 0.445990E+09 | 0.66 | 184.35 | 0.66 | |
Maximum of Months | 0.493775E+09 | 0.67 | 184.35 | 0.67 |
Report: FanReportMonthly
For: LOBBY_FLR_1 EXHAUST FAN
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: BANQUET_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: DINING_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.279806E+10 | 0.47 | 1474.84 | 01-JAN-07:05 | 0.67 |
February | 0.252728E+10 | 0.47 | 1474.84 | 01-FEB-07:10 | 0.67 |
March | 0.279806E+10 | 0.47 | 1474.84 | 01-MAR-07:05 | 0.67 |
April | 0.270780E+10 | 0.47 | 1474.84 | 01-APR-06:10 | 0.67 |
May | 0.279806E+10 | 0.47 | 1474.84 | 01-MAY-06:05 | 0.67 |
June | 0.270780E+10 | 0.47 | 1474.84 | 01-JUN-06:05 | 0.66 |
July | 0.279806E+10 | 0.47 | 1474.84 | 01-JUL-06:10 | 0.66 |
August | 0.279806E+10 | 0.47 | 1474.84 | 01-AUG-06:05 | 0.66 |
September | 0.270780E+10 | 0.47 | 1474.84 | 01-SEP-06:05 | 0.66 |
October | 0.279806E+10 | 0.47 | 1474.84 | 01-OCT-06:10 | 0.67 |
November | 0.270780E+10 | 0.47 | 1474.84 | 01-NOV-06:05 | 0.66 |
December | 0.279806E+10 | 0.47 | 1474.84 | 01-DEC-07:10 | 0.67 |
Annual Sum or Average | 0.329449E+11 | 0.47 | |||
Minimum of Months | 0.252728E+10 | 0.47 | 1474.84 | 0.66 | |
Maximum of Months | 0.279806E+10 | 0.47 | 1474.84 | 0.67 |
Report: FanReportMonthly
For: ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.202288E+10 | 1.33 | 2298.52 | 01-JAN-09:02 | 1.45 |
February | 0.108419E+10 | 1.18 | 2298.52 | 01-FEB-09:02 | 1.45 |
March | 0.839819E+09 | 1.13 | 2298.52 | 01-MAR-09:01 | 1.45 |
April | 0.626028E+09 | 1.14 | 2298.52 | 02-APR-08:61 | 1.45 |
May | 0.850853E+09 | 1.26 | 2298.52 | 01-MAY-15:02 | 1.45 |
June | 0.958180E+09 | 1.27 | 2298.52 | 01-JUN-15:02 | 1.44 |
July | 0.116568E+10 | 1.32 | 2298.52 | 01-JUL-08:61 | 1.43 |
August | 0.939965E+09 | 1.27 | 2298.52 | 01-AUG-15:02 | 1.44 |
September | 0.584779E+09 | 1.20 | 2298.52 | 01-SEP-15:02 | 1.44 |
October | 0.515775E+09 | 1.10 | 2298.52 | 01-OCT-15:01 | 1.44 |
November | 0.761451E+09 | 1.12 | 2298.52 | 01-NOV-08:62 | 1.44 |
December | 0.184428E+10 | 1.36 | 2298.52 | 01-DEC-09:02 | 1.45 |
Annual Sum or Average | 0.121939E+11 | 1.22 | |||
Minimum of Months | 0.515775E+09 | 1.10 | 2298.52 | 1.43 | |
Maximum of Months | 0.202288E+10 | 1.36 | 2298.52 | 1.45 |
Report: FanReportMonthly
For: ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.237434E+10 | 1.41 | 2188.82 | 01-JAN-09:02 | 1.45 |
February | 0.127372E+10 | 1.29 | 2188.82 | 01-FEB-09:02 | 1.45 |
March | 0.912878E+09 | 1.19 | 2188.82 | 01-MAR-09:01 | 1.45 |
April | 0.549494E+09 | 1.07 | 2188.82 | 02-APR-08:61 | 1.45 |
May | 0.734806E+09 | 1.19 | 2188.82 | 01-MAY-15:02 | 1.45 |
June | 0.889337E+09 | 1.23 | 2188.82 | 01-JUN-15:02 | 1.44 |
July | 0.106025E+10 | 1.30 | 2188.82 | 01-JUL-08:61 | 1.43 |
August | 0.786278E+09 | 1.22 | 2188.82 | 01-AUG-15:02 | 1.44 |
September | 0.430136E+09 | 1.10 | 2188.82 | 01-SEP-15:02 | 1.44 |
October | 0.465922E+09 | 1.05 | 2188.82 | 01-OCT-15:01 | 1.44 |
November | 0.840381E+09 | 1.19 | 2188.82 | 01-NOV-08:62 | 1.44 |
December | 0.207661E+10 | 1.41 | 2188.82 | 01-DEC-09:02 | 1.45 |
Annual Sum or Average | 0.123942E+11 | 1.22 | |||
Minimum of Months | 0.430136E+09 | 1.05 | 2188.82 | 1.43 | |
Maximum of Months | 0.237434E+10 | 1.41 | 2188.82 | 1.45 |
Report: FanReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.532279E+10 | 0.92 | 14230.12 | 09-JAN-05:00 | 1.46 |
February | 0.203944E+10 | 0.52 | 9771.55 | 17-FEB-06:00 | 1.46 |
March | 0.137308E+10 | 0.35 | 8729.13 | 05-MAR-05:00 | 1.46 |
April | 0.238571E+10 | 0.62 | 6812.38 | 13-APR-13:00 | 1.45 |
May | 0.419150E+10 | 1.14 | 4860.66 | 18-MAY-13:10 | 1.44 |
June | 0.424210E+10 | 1.20 | 4806.52 | 30-JUN-13:00 | 1.44 |
July | 0.521754E+10 | 1.33 | 6912.41 | 24-JUL-12:50 | 1.44 |
August | 0.502141E+10 | 1.29 | 7447.42 | 13-AUG-13:30 | 1.44 |
September | 0.412590E+10 | 1.08 | 8619.59 | 04-SEP-12:10 | 1.44 |
October | 0.229998E+10 | 0.49 | 9590.63 | 20-OCT-12:00 | 1.44 |
November | 0.111426E+10 | 0.37 | 4532.72 | 17-NOV-12:20 | 1.45 |
December | 0.541586E+10 | 1.09 | 13820.18 | 24-DEC-06:00 | 1.46 |
Annual Sum or Average | 0.427496E+11 | 0.87 | |||
Minimum of Months | 0.111426E+10 | 0.35 | 4532.72 | 1.44 | |
Maximum of Months | 0.541586E+10 | 1.33 | 14230.12 | 1.46 |
Report: FanReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.103838E+11 | 1.21 | 11243.31 | 01-JAN-02:65 | 1.45 |
February | 0.551743E+10 | 1.09 | 11243.31 | 01-FEB-09:02 | 1.45 |
March | 0.348516E+10 | 1.03 | 11243.31 | 01-MAR-09:01 | 1.45 |
April | 0.240541E+10 | 1.03 | 11243.31 | 03-APR-15:01 | 1.45 |
May | 0.543172E+10 | 1.04 | 11243.31 | 01-MAY-15:02 | 1.45 |
June | 0.702516E+10 | 1.07 | 11243.31 | 01-JUN-08:62 | 1.44 |
July | 0.768640E+10 | 1.10 | 11243.31 | 01-JUL-08:61 | 1.43 |
August | 0.607458E+10 | 1.03 | 11243.31 | 01-AUG-08:62 | 1.43 |
September | 0.390371E+10 | 1.02 | 11243.31 | 01-SEP-08:62 | 1.43 |
October | 0.212907E+10 | 1.02 | 11243.31 | 01-OCT-08:61 | 1.44 |
November | 0.250668E+10 | 1.03 | 11243.31 | 03-NOV-15:01 | 1.45 |
December | 0.901593E+10 | 1.19 | 11243.31 | 01-DEC-09:02 | 1.45 |
Annual Sum or Average | 0.655650E+11 | 1.07 | |||
Minimum of Months | 0.212907E+10 | 1.02 | 11243.31 | 1.43 | |
Maximum of Months | 0.103838E+11 | 1.21 | 11243.31 | 1.45 |
Report: FanReportMonthly
For: ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.196099E+10 | 1.33 | 2092.83 | 01-JAN-09:02 | 1.45 |
February | 0.102390E+10 | 1.14 | 2092.83 | 01-FEB-09:02 | 1.45 |
March | 0.767389E+09 | 1.12 | 2092.83 | 01-MAR-09:01 | 1.45 |
April | 0.603965E+09 | 1.18 | 2092.83 | 02-APR-08:61 | 1.45 |
May | 0.785636E+09 | 1.30 | 2092.83 | 01-MAY-08:62 | 1.45 |
June | 0.985483E+09 | 1.32 | 2092.83 | 01-JUN-08:62 | 1.44 |
July | 0.112985E+10 | 1.36 | 2092.83 | 01-JUL-08:61 | 1.44 |
August | 0.879029E+09 | 1.29 | 2092.83 | 01-AUG-15:02 | 1.44 |
September | 0.572542E+09 | 1.21 | 2092.83 | 01-SEP-08:62 | 1.43 |
October | 0.489781E+09 | 1.11 | 2092.83 | 01-OCT-08:61 | 1.44 |
November | 0.727398E+09 | 1.11 | 2092.83 | 02-NOV-08:62 | 1.44 |
December | 0.177561E+10 | 1.37 | 2092.83 | 01-DEC-09:02 | 1.45 |
Annual Sum or Average | 0.117016E+11 | 1.24 | |||
Minimum of Months | 0.489781E+09 | 1.11 | 2092.83 | 1.43 | |
Maximum of Months | 0.196099E+10 | 1.37 | 2092.83 | 1.45 |
Report: FanReportMonthly
For: ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.225916E+10 | 1.41 | 1989.57 | 01-JAN-09:02 | 1.45 |
February | 0.122968E+10 | 1.29 | 1989.57 | 01-FEB-09:02 | 1.45 |
March | 0.832665E+09 | 1.16 | 1989.57 | 01-MAR-09:01 | 1.45 |
April | 0.501252E+09 | 1.10 | 1989.57 | 01-APR-18:02 | 1.45 |
May | 0.672127E+09 | 1.26 | 1989.57 | 01-MAY-08:62 | 1.45 |
June | 0.920460E+09 | 1.32 | 1989.57 | 01-JUN-08:62 | 1.44 |
July | 0.102759E+10 | 1.35 | 1989.57 | 01-JUL-08:61 | 1.44 |
August | 0.727836E+09 | 1.27 | 1989.57 | 01-AUG-15:02 | 1.44 |
September | 0.414376E+09 | 1.14 | 1989.57 | 01-SEP-08:62 | 1.43 |
October | 0.441617E+09 | 1.03 | 1989.57 | 01-OCT-08:61 | 1.44 |
November | 0.794649E+09 | 1.20 | 1989.57 | 01-NOV-08:62 | 1.44 |
December | 0.200596E+10 | 1.41 | 1989.57 | 01-DEC-09:02 | 1.45 |
Annual Sum or Average | 0.118274E+11 | 1.24 | |||
Minimum of Months | 0.414376E+09 | 1.03 | 1989.57 | 1.43 | |
Maximum of Months | 0.225916E+10 | 1.41 | 1989.57 | 1.45 |
Report: FanReportMonthly
For: ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.561111E+09 | 1.37 | 602.37 | 01-JAN-09:02 | 1.45 |
February | 0.328503E+09 | 1.24 | 602.37 | 01-FEB-09:02 | 1.45 |
March | 0.256122E+09 | 1.19 | 602.37 | 01-MAR-09:01 | 1.45 |
April | 0.184916E+09 | 1.16 | 602.37 | 02-APR-08:61 | 1.45 |
May | 0.243756E+09 | 1.27 | 602.37 | 01-MAY-15:02 | 1.45 |
June | 0.274430E+09 | 1.28 | 602.37 | 01-JUN-15:02 | 1.44 |
July | 0.333587E+09 | 1.33 | 602.37 | 01-JUL-08:61 | 1.43 |
August | 0.266386E+09 | 1.28 | 602.37 | 01-AUG-15:02 | 1.44 |
September | 0.162078E+09 | 1.21 | 602.37 | 01-SEP-15:02 | 1.44 |
October | 0.157771E+09 | 1.12 | 602.37 | 01-OCT-15:01 | 1.44 |
November | 0.237657E+09 | 1.19 | 602.37 | 01-NOV-08:62 | 1.44 |
December | 0.518556E+09 | 1.39 | 602.37 | 01-DEC-09:02 | 1.45 |
Annual Sum or Average | 0.352487E+10 | 1.25 | |||
Minimum of Months | 0.157771E+09 | 1.12 | 602.37 | 1.43 | |
Maximum of Months | 0.561111E+09 | 1.39 | 602.37 | 1.45 |
Report: FanReportMonthly
For: ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.662115E+09 | 1.43 | 571.39 | 01-JAN-09:02 | 1.45 |
February | 0.384505E+09 | 1.36 | 571.39 | 01-FEB-09:02 | 1.45 |
March | 0.277059E+09 | 1.26 | 571.39 | 01-MAR-09:01 | 1.45 |
April | 0.165313E+09 | 1.11 | 571.39 | 01-APR-18:02 | 1.45 |
May | 0.211881E+09 | 1.22 | 571.39 | 01-MAY-08:62 | 1.45 |
June | 0.255642E+09 | 1.26 | 571.39 | 01-JUN-15:02 | 1.44 |
July | 0.304987E+09 | 1.32 | 571.39 | 01-JUL-08:61 | 1.43 |
August | 0.223658E+09 | 1.25 | 571.39 | 01-AUG-15:02 | 1.44 |
September | 0.121847E+09 | 1.12 | 571.39 | 01-SEP-15:02 | 1.44 |
October | 0.146757E+09 | 1.08 | 571.39 | 01-OCT-15:01 | 1.44 |
November | 0.262338E+09 | 1.28 | 571.39 | 01-NOV-08:62 | 1.44 |
December | 0.598565E+09 | 1.43 | 571.39 | 01-DEC-09:02 | 1.45 |
Annual Sum or Average | 0.361467E+10 | 1.26 | |||
Minimum of Months | 0.121847E+09 | 1.08 | 571.39 | 1.43 | |
Maximum of Months | 0.662115E+09 | 1.43 | 571.39 | 1.45 |
Report: FanReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.196493E+10 | 1.23 | 2949.26 | 01-JAN-09:02 | 1.45 |
February | 0.126442E+10 | 1.22 | 2949.26 | 01-FEB-09:02 | 1.45 |
March | 0.106479E+10 | 1.19 | 2949.26 | 01-MAR-09:01 | 1.45 |
April | 0.903451E+09 | 1.21 | 2949.26 | 02-APR-08:61 | 1.45 |
May | 0.115138E+10 | 1.28 | 2949.26 | 01-MAY-15:02 | 1.45 |
June | 0.126855E+10 | 1.28 | 2949.26 | 01-JUN-15:02 | 1.44 |
July | 0.155382E+10 | 1.32 | 2949.26 | 01-JUL-08:61 | 1.43 |
August | 0.144806E+10 | 1.28 | 2949.26 | 01-AUG-15:02 | 1.44 |
September | 0.107542E+10 | 1.22 | 2949.26 | 01-SEP-08:62 | 1.43 |
October | 0.887372E+09 | 1.12 | 2949.26 | 01-OCT-08:61 | 1.44 |
November | 0.910161E+09 | 1.15 | 2949.26 | 02-NOV-15:01 | 1.45 |
December | 0.188719E+10 | 1.26 | 2949.26 | 01-DEC-09:02 | 1.45 |
Annual Sum or Average | 0.153796E+11 | 1.23 | |||
Minimum of Months | 0.887372E+09 | 1.12 | 2949.26 | 1.43 | |
Maximum of Months | 0.196493E+10 | 1.32 | 2949.26 | 1.45 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.417253E+10 | 0.375528E+10 | 2204.65 | 05-JAN-03:00 | 1984.18 | 1984.18 | 29.87 | 7.05 |
February | 0.297939E+10 | 0.268145E+10 | 2197.64 | 14-FEB-04:10 | 1977.88 | 1977.88 | 30.54 | 7.03 |
March | 0.233979E+10 | 0.210581E+10 | 2178.87 | 05-MAR-02:30 | 1960.98 | 1960.98 | 32.20 | 6.98 |
April | 0.986887E+09 | 0.888199E+09 | 1320.06 | 05-APR-06:10 | 1188.05 | 1188.05 | 35.08 | 2.13 |
May | 0.531040E+09 | 0.477936E+09 | 671.31 | 01-MAY-08:03 | 604.18 | 604.18 | 32.58 | 0.81 |
June | 0.448593E+09 | 0.403734E+09 | 581.05 | 02-JUN-08:05 | 522.95 | 522.95 | 30.43 | 0.68 |
July | 0.371204E+09 | 0.334083E+09 | 569.32 | 10-JUL-10:35 | 512.39 | 512.39 | 32.75 | 0.67 |
August | 0.343153E+09 | 0.308837E+09 | 583.49 | 07-AUG-08:05 | 525.14 | 525.14 | 27.90 | 0.69 |
September | 0.421562E+09 | 0.379406E+09 | 586.79 | 27-SEP-15:05 | 528.12 | 528.12 | 30.05 | 0.69 |
October | 0.847294E+09 | 0.762565E+09 | 1282.22 | 30-OCT-08:61 | 1154.00 | 1154.00 | 30.77 | 2.02 |
November | 0.180918E+10 | 0.162826E+10 | 1613.25 | 25-NOV-07:10 | 1451.93 | 1451.93 | 37.16 | 3.55 |
December | 0.398434E+10 | 0.358590E+10 | 2197.38 | 24-DEC-03:40 | 1977.64 | 1977.64 | 30.38 | 7.03 |
Annual Sum or Average | 0.192350E+11 | 0.173115E+11 | ||||||
Minimum of Months | 0.343153E+09 | 0.308837E+09 | 569.32 | 512.39 | 512.39 | 27.90 | 0.67 | |
Maximum of Months | 0.417253E+10 | 0.375528E+10 | 2204.65 | 1984.18 | 1984.18 | 37.16 | 7.05 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 48940764.26 | 44046687.83 | 1554.71 | 17-JAN-19:04 | 1399.24 | 1399.24 | 6.73 | 2.54 |
February | 0.329775E+09 | 0.296798E+09 | 3121.74 | 22-FEB-16:05 | 2809.56 | 2809.56 | 6.73 | 5.75 |
March | 0.818586E+09 | 0.736727E+09 | 3865.49 | 29-MAR-15:02 | 3478.94 | 3478.94 | 6.73 | 7.64 |
April | 0.292471E+10 | 0.263224E+10 | 6229.88 | 23-APR-18:01 | 5606.89 | 5606.89 | 6.73 | 18.71 |
May | 0.780017E+10 | 0.702016E+10 | 6659.61 | 18-MAY-18:03 | 5993.65 | 5993.65 | 6.73 | 24.27 |
June | 0.107629E+11 | 0.968660E+10 | 7241.54 | 29-JUN-18:03 | 6517.38 | 6517.38 | 6.73 | 32.57 |
July | 0.128907E+11 | 0.116017E+11 | 7145.39 | 23-JUL-10:35 | 6430.85 | 6430.85 | 6.73 | 31.56 |
August | 0.112099E+11 | 0.100889E+11 | 6843.51 | 08-AUG-15:15 | 6159.16 | 6159.16 | 6.73 | 27.39 |
September | 0.616458E+10 | 0.554813E+10 | 6447.44 | 01-SEP-10:40 | 5802.70 | 5802.70 | 6.73 | 21.13 |
October | 0.237115E+10 | 0.213403E+10 | 6326.22 | 19-OCT-15:02 | 5693.60 | 5693.60 | 6.73 | 19.69 |
November | 0.514870E+09 | 0.463383E+09 | 4186.88 | 01-NOV-15:03 | 3768.19 | 3768.19 | 6.73 | 8.57 |
December | 26338021.25 | 23704219.12 | 1479.48 | 28-DEC-19:04 | 1331.53 | 1331.53 | 6.73 | 2.41 |
Annual Sum or Average | 0.558627E+11 | 0.502764E+11 | ||||||
Minimum of Months | 26338021.25 | 23704219.12 | 1479.48 | 1331.53 | 1331.53 | 6.73 | 2.41 | |
Maximum of Months | 0.128907E+11 | 0.116017E+11 | 7241.54 | 6517.38 | 6517.38 | 6.73 | 32.57 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.103878E+10 | 0.934905E+09 | 5878.42 | 01-JAN-10:31 | 5290.57 | 5290.57 | 6.74 | 41.20 |
February | 0.314416E+10 | 0.282975E+10 | 5878.42 | 01-FEB-10:35 | 5290.57 | 5290.57 | 6.73 | 41.20 |
March | 0.522205E+10 | 0.469984E+10 | 5878.42 | 01-MAR-09:03 | 5290.57 | 5290.57 | 6.74 | 41.20 |
April | 0.107369E+11 | 0.966318E+10 | 5878.42 | 01-APR-00:10 | 5290.57 | 5290.57 | 6.74 | 41.20 |
May | 0.155655E+11 | 0.140089E+11 | 5878.42 | 01-MAY-00:10 | 5290.57 | 5290.57 | 6.76 | 41.20 |
June | 0.152357E+11 | 0.137121E+11 | 5878.42 | 01-JUN-00:10 | 5290.57 | 5290.57 | 6.82 | 41.20 |
July | 0.157447E+11 | 0.141703E+11 | 5878.42 | 01-JUL-00:10 | 5290.57 | 5290.57 | 7.50 | 41.20 |
August | 0.157408E+11 | 0.141667E+11 | 5878.42 | 01-AUG-00:10 | 5290.57 | 5290.57 | 7.81 | 41.20 |
September | 0.149077E+11 | 0.134169E+11 | 5878.42 | 01-SEP-00:10 | 5290.57 | 5290.57 | 9.28 | 41.20 |
October | 0.106598E+11 | 0.959378E+10 | 5878.42 | 01-OCT-00:10 | 5290.57 | 5290.57 | 6.84 | 41.20 |
November | 0.449005E+10 | 0.404105E+10 | 5878.42 | 01-NOV-05:10 | 5290.57 | 5290.57 | 6.76 | 41.20 |
December | 0.687381E+09 | 0.618643E+09 | 5878.42 | 01-DEC-09:03 | 5290.57 | 5290.57 | 6.74 | 41.20 |
Annual Sum or Average | 0.113173E+12 | 0.101856E+12 | ||||||
Minimum of Months | 0.687381E+09 | 0.618643E+09 | 5878.42 | 5290.57 | 5290.57 | 6.73 | 41.20 | |
Maximum of Months | 0.157447E+11 | 0.141703E+11 | 5878.42 | 5290.57 | 5290.57 | 9.28 | 41.20 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.128314E+09 | 38494137.67 | 47.91 | 01-JAN-00:10 | 14.37 | 14.37 | 46.53 | 0.37 |
February | 0.115896E+09 | 34768898.54 | 47.91 | 01-FEB-00:05 | 14.37 | 14.37 | 46.57 | 0.37 |
March | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAR-00:03 | 14.37 | 14.37 | 46.78 | 0.37 |
April | 0.124175E+09 | 37252391.29 | 47.91 | 01-APR-00:10 | 14.37 | 14.37 | 50.32 | 0.37 |
May | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAY-00:10 | 14.37 | 14.37 | 50.39 | 0.37 |
June | 0.124175E+09 | 37252391.29 | 47.91 | 01-JUN-00:10 | 14.37 | 14.37 | 51.26 | 0.37 |
July | 0.128314E+09 | 38494137.67 | 47.91 | 01-JUL-00:10 | 14.37 | 14.37 | 51.05 | 0.37 |
August | 0.128314E+09 | 38494137.67 | 47.91 | 01-AUG-00:10 | 14.37 | 14.37 | 51.96 | 0.37 |
September | 0.124175E+09 | 37252391.29 | 47.91 | 01-SEP-00:10 | 14.37 | 14.37 | 52.19 | 0.37 |
October | 0.128314E+09 | 38494137.67 | 47.91 | 01-OCT-00:10 | 14.37 | 14.37 | 50.96 | 0.37 |
November | 0.124175E+09 | 37252391.29 | 47.91 | 01-NOV-00:10 | 14.37 | 14.37 | 51.44 | 0.37 |
December | 0.128314E+09 | 38494137.67 | 47.91 | 01-DEC-00:05 | 14.37 | 14.37 | 47.93 | 0.37 |
Annual Sum or Average | 0.151079E+10 | 0.453237E+09 | ||||||
Minimum of Months | 0.115896E+09 | 34768898.54 | 47.91 | 14.37 | 14.37 | 46.53 | 0.37 | |
Maximum of Months | 0.128314E+09 | 38494137.67 | 47.91 | 14.37 | 14.37 | 52.19 | 0.37 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 39.95 | 60.00 | 391604.00 | 914305.51 | 06-JAN-08:04 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 38.52 | 60.00 | 249793.08 | 882236.19 | 17-FEB-06:00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 41.43 | 60.00 | 139600.48 | 844161.73 | 05-MAR-07:00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 37.53 | 60.00 | 44176.44 | 257571.25 | 05-APR-08:61 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 38.44 | 60.00 | 24162.91 | 92865.93 | 01-MAY-08:03 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 27.79 | 60.00 | 21482.24 | 84398.22 | 02-JUN-08:05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 28.89 | 60.00 | 17834.27 | 75881.11 | 10-JUL-10:35 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 26.64 | 60.00 | 17072.81 | 92138.16 | 07-AUG-08:05 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.78 | 60.00 | 21013.16 | 86484.04 | 27-SEP-15:05 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 24.94 | 60.00 | 35631.23 | 246978.18 | 30-OCT-08:61 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 41.49 | 60.00 | 90715.91 | 369447.12 | 25-NOV-09:03 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 36.33 | 60.00 | 347421.06 | 881821.79 | 24-DEC-06:00 |
Annual Sum or Average | 0.00 | 116408.13 | ||||||
Minimum of Months | 0.00 | 0.00 | 24.94 | 60.00 | 17072.81 | 75881.11 | ||
Maximum of Months | 0.00 | 0.00 | 41.49 | 60.00 | 391604.00 | 914305.51 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 667.53 | 31967.76 | 17-JAN-19:04 | 6.88 | 6.70 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 3719.53 | 98790.80 | 22-FEB-16:05 | 7.27 | 6.70 | 0.00 | 0.00 | 01-FEB-00:05 |
March | 7554.94 | 126827.44 | 19-MAR-15:03 | 7.43 | 6.70 | 0.00 | 0.00 | 01-MAR-00:03 |
April | 36050.26 | 517132.47 | 23-APR-18:03 | 9.69 | 6.70 | 0.00 | 0.00 | 01-APR-00:10 |
May | 131131.63 | 662270.36 | 25-MAY-18:03 | 10.54 | 6.70 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 273055.24 | 923898.96 | 29-JUN-18:03 | 12.05 | 6.70 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 352486.64 | 877457.52 | 15-JUL-15:03 | 11.78 | 6.70 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 266690.85 | 835003.60 | 08-AUG-15:03 | 11.54 | 6.70 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 98275.96 | 625920.37 | 18-SEP-18:01 | 10.33 | 6.70 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 27225.95 | 448645.08 | 19-OCT-15:02 | 9.30 | 6.70 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 5709.38 | 212310.83 | 01-NOV-15:03 | 7.93 | 6.70 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 390.16 | 28962.27 | 28-DEC-09:04 | 6.87 | 6.70 | 0.00 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 101006.72 | 0.00 | ||||||
Minimum of Months | 390.16 | 28962.27 | 6.87 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 352486.64 | 923898.96 | 12.05 | 6.70 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 46.53 | 59.32 | 32705.48 | 67628.49 | 31-JAN-07:40 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 46.57 | 58.47 | 33428.40 | 68316.98 | 27-FEB-07:20 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 46.78 | 59.42 | 33322.78 | 68249.26 | 01-MAR-07:50 |
April | 0.00 | 0.00 | 01-APR-00:10 | 50.32 | 59.40 | 32343.54 | 66885.38 | 03-APR-06:50 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 50.39 | 58.86 | 30790.40 | 64292.63 | 01-MAY-06:15 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 51.26 | 59.53 | 29068.78 | 60594.67 | 01-JUN-06:50 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 51.05 | 58.39 | 27603.39 | 57003.83 | 03-JUL-06:10 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 51.96 | 59.34 | 26863.78 | 54769.27 | 01-AUG-06:40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 52.19 | 59.62 | 26985.13 | 55243.73 | 29-SEP-06:10 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 50.96 | 59.31 | 27960.99 | 58128.93 | 31-OCT-06:10 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 51.44 | 59.28 | 29528.79 | 61675.50 | 30-NOV-08:00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 47.93 | 58.83 | 31256.99 | 65010.23 | 29-DEC-07:40 |
Annual Sum or Average | 0.00 | 30135.34 | ||||||
Minimum of Months | 0.00 | 0.00 | 46.53 | 58.39 | 26863.78 | 54769.27 | ||
Maximum of Months | 0.00 | 0.00 | 52.19 | 59.62 | 33428.40 | 68316.98 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.862198E+12 | 0.00 | 0.00 | 0.138611E+12 | 0.00 | 0.00 |
February | 0.504557E+12 | 0.00 | 0.00 | 0.125199E+12 | 0.00 | 0.00 |
March | 0.317084E+12 | 0.00 | 0.00 | 0.138618E+12 | 0.00 | 0.00 |
April | 0.104344E+12 | 0.00 | 0.284230E+11 | 0.134154E+12 | 0.00 | 0.00 |
May | 0.644774E+11 | 0.00 | 0.193467E+12 | 0.138632E+12 | 0.00 | 0.00 |
June | 0.560067E+11 | 0.00 | 0.485694E+12 | 0.134163E+12 | 0.00 | 0.00 |
July | 0.481225E+11 | 0.00 | 0.664927E+12 | 0.138637E+12 | 0.00 | 0.00 |
August | 0.459227E+11 | 0.00 | 0.486034E+12 | 0.138634E+12 | 0.00 | 0.00 |
September | 0.537420E+11 | 0.00 | 0.129382E+12 | 0.134157E+12 | 0.00 | 0.00 |
October | 0.857353E+11 | 0.00 | 0.182107E+11 | 0.138622E+12 | 0.00 | 0.00 |
November | 0.189771E+12 | 0.00 | 0.291286E+10 | 0.134145E+12 | 0.00 | 0.00 |
December | 0.758646E+12 | 0.00 | 0.00 | 0.138611E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.309061E+13 | 0.00 | 0.200905E+13 | 0.163218E+13 | 0.00 | 0.00 |
Minimum of Months | 0.459227E+11 | 0.00 | 0.00 | 0.125199E+12 | 0.00 | 0.00 |
Maximum of Months | 0.862198E+12 | 0.00 | 0.664927E+12 | 0.138637E+12 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.487227E+11 | 0.00 | 0.00 | 0.587890E+10 | 0.00 | 0.00 |
February | 0.268877E+11 | 0.00 | 0.00 | 0.530997E+10 | 0.00 | 0.00 |
March | 0.145431E+11 | 0.00 | 0.00 | 0.587890E+10 | 0.00 | 0.00 |
April | 0.125033E+10 | 0.00 | 0.220642E+10 | 0.568926E+10 | 0.00 | 0.00 |
May | 15028082.90 | 0.00 | 0.180867E+11 | 0.587890E+10 | 0.00 | 0.00 |
June | 24892.06 | 0.00 | 0.470980E+11 | 0.568926E+10 | 0.00 | 0.00 |
July | 25079.47 | 0.00 | 0.659880E+11 | 0.587890E+10 | 0.00 | 0.00 |
August | 29610.65 | 0.00 | 0.467551E+11 | 0.587890E+10 | 0.00 | 0.00 |
September | 14716.18 | 0.00 | 0.106497E+11 | 0.568926E+10 | 0.00 | 0.00 |
October | 0.425335E+09 | 0.00 | 0.144271E+10 | 0.587890E+10 | 0.00 | 0.00 |
November | 0.739218E+10 | 0.00 | 0.223309E+09 | 0.568926E+10 | 0.00 | 0.00 |
December | 0.428840E+11 | 0.00 | 0.00 | 0.587890E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.142120E+12 | 0.00 | 0.192450E+12 | 0.692193E+11 | 0.00 | 0.00 |
Minimum of Months | 14716.18 | 0.00 | 0.00 | 0.530997E+10 | 0.00 | 0.00 |
Maximum of Months | 0.487227E+11 | 0.00 | 0.659880E+11 | 0.587890E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.138611E+12 | 0.00 | 0.862198E+12 | 0.131244E+13 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.125199E+12 | 0.00 | 0.504557E+12 | 0.126347E+13 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.138618E+12 | 0.00 | 0.317084E+12 | 0.131238E+13 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.134154E+12 | 0.284230E+11 | 0.104344E+12 | 0.760491E+12 | 0.123664E+10 | 0.00 | 0.00 | 0.00 |
May | 0.138632E+12 | 0.193467E+12 | 0.644774E+11 | 0.233864E+12 | 0.186568E+11 | 0.00 | 0.00 | 0.00 |
June | 0.134163E+12 | 0.485694E+12 | 0.560067E+11 | 0.630764E+11 | 0.118144E+12 | 0.00 | 0.00 | 0.00 |
July | 0.138637E+12 | 0.664927E+12 | 0.481225E+11 | 0.289207E+11 | 0.175963E+12 | 0.00 | 0.00 | 0.00 |
August | 0.138634E+12 | 0.486034E+12 | 0.459227E+11 | 0.328074E+11 | 0.789174E+11 | 0.00 | 0.00 | 0.00 |
September | 0.134157E+12 | 0.129382E+12 | 0.537420E+11 | 0.218807E+12 | 0.361075E+10 | 0.00 | 0.00 | 0.00 |
October | 0.138622E+12 | 0.182107E+11 | 0.857353E+11 | 0.675881E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.134145E+12 | 0.291286E+10 | 0.189771E+12 | 0.111322E+13 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.138611E+12 | 0.00 | 0.758646E+12 | 0.132677E+13 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.163218E+13 | 0.200905E+13 | 0.309061E+13 | 0.834212E+13 | 0.396528E+12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.125199E+12 | 0.00 | 0.459227E+11 | 0.289207E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.138637E+12 | 0.664927E+12 | 0.862198E+12 | 0.132677E+13 | 0.175963E+12 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.587890E+10 | 0.00 | 0.487227E+11 | 0.125830E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.530997E+10 | 0.00 | 0.268877E+11 | 0.121647E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.587890E+10 | 0.00 | 0.145431E+11 | 0.127122E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.568926E+10 | 0.220642E+10 | 0.125033E+10 | 0.762122E+11 | 0.134523E+09 | 0.00 | 0.00 | 0.00 |
May | 0.587890E+10 | 0.180867E+11 | 15028082.90 | 0.257074E+11 | 0.174894E+10 | 0.00 | 0.00 | 0.00 |
June | 0.568926E+10 | 0.470980E+11 | 24892.06 | 0.737229E+10 | 0.111346E+11 | 0.00 | 0.00 | 0.00 |
July | 0.587890E+10 | 0.659880E+11 | 25079.47 | 0.343469E+10 | 0.165607E+11 | 0.00 | 0.00 | 0.00 |
August | 0.587890E+10 | 0.467551E+11 | 29610.65 | 0.413115E+10 | 0.708522E+10 | 0.00 | 0.00 | 0.00 |
September | 0.568926E+10 | 0.106497E+11 | 14716.18 | 0.245658E+11 | 0.301558E+09 | 0.00 | 0.00 | 0.00 |
October | 0.587890E+10 | 0.144271E+10 | 0.425335E+09 | 0.690233E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.568926E+10 | 0.223309E+09 | 0.739218E+10 | 0.107969E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.587890E+10 | 0.00 | 0.428840E+11 | 0.126408E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.692193E+11 | 0.192450E+12 | 0.142120E+12 | 0.819423E+12 | 0.369656E+11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.530997E+10 | 0.00 | 14716.18 | 0.343469E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.587890E+10 | 0.659880E+11 | 0.487227E+11 | 0.127122E+12 | 0.165607E+11 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.138611E+12 | 0.862198E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.125199E+12 | 0.504557E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.138618E+12 | 0.317084E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.134154E+12 | 0.104344E+12 | 0.284230E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.138632E+12 | 0.644774E+11 | 0.193467E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.134163E+12 | 0.560067E+11 | 0.485694E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.138637E+12 | 0.481225E+11 | 0.664927E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.138634E+12 | 0.459227E+11 | 0.486034E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.134157E+12 | 0.537420E+11 | 0.129382E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.138622E+12 | 0.857353E+11 | 0.182107E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.134145E+12 | 0.189771E+12 | 0.291286E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.138611E+12 | 0.758646E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.163218E+13 | 0.309061E+13 | 0.200905E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.125199E+12 | 0.459227E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.138637E+12 | 0.862198E+12 | 0.664927E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.587890E+10 | 0.487227E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.530997E+10 | 0.268877E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.587890E+10 | 0.145431E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.568926E+10 | 0.125033E+10 | 0.220642E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.587890E+10 | 15028082.90 | 0.180867E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.568926E+10 | 24892.06 | 0.470980E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.587890E+10 | 25079.47 | 0.659880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.587890E+10 | 29610.65 | 0.467551E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.568926E+10 | 14716.18 | 0.106497E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.587890E+10 | 0.425335E+09 | 0.144271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.568926E+10 | 0.739218E+10 | 0.223309E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.587890E+10 | 0.428840E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.692193E+11 | 0.142120E+12 | 0.192450E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.530997E+10 | 14716.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.587890E+10 | 0.487227E+11 | 0.659880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.338224E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110717E+12 | 0.00 | 0.00 | 1.85 |
February | 0.517231E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.510264E+11 | 0.00 | 0.00 | 1.87 |
March | 0.698356E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.197570E+11 | 0.00 | 0.00 | 1.87 |
April | 0.656436E+11 | 0.00 | 5215030.50 | 0.00 | 43496356.24 | 0.619231E+09 | 0.00 | 241768.12 | 1.88 |
May | 0.520972E+11 | 0.00 | 24295936.59 | 0.00 | 0.917680E+09 | 0.140900E+09 | 0.00 | 468932.98 | 1.89 |
June | 0.309965E+11 | 0.00 | 80699706.10 | 0.00 | 0.120045E+11 | 2672327.75 | 0.00 | 236297.39 | 1.89 |
July | 0.225346E+11 | 0.00 | 0.00 | 0.00 | 0.198503E+11 | 0.00 | 0.00 | 0.00 | 1.90 |
August | 0.302755E+11 | 0.00 | 0.00 | 0.00 | 0.932792E+10 | 0.00 | 0.00 | 0.00 | 1.89 |
September | 0.559068E+11 | 0.00 | 0.00 | 0.00 | 0.645366E+09 | 0.00 | 0.00 | 0.00 | 1.89 |
October | 0.683771E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.88 |
November | 0.745451E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.89 |
December | 0.506220E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.830399E+11 | 0.00 | 0.00 | 1.85 |
Annual Sum or Average | 0.606380E+12 | 0.00 | 0.110211E+09 | 0.00 | 0.427893E+11 | 0.265303E+12 | 0.00 | 946998.50 | 1.88 |
Minimum of Months | 0.225346E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.85 |
Maximum of Months | 0.745451E+11 | 0.00 | 80699706.10 | 0.00 | 0.198503E+11 | 0.110717E+12 | 0.00 | 468932.98 | 1.90 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.153741E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.249984E+11 | 0.00 | 0.00 | 6.17 |
February | 0.463085E+10 | 0.00 | 0.00 | 67205.40 | 0.00 | 0.140183E+11 | 0.214491E+09 | 0.00 | 6.22 |
March | 0.762542E+10 | 0.00 | 0.00 | 57874.09 | 0.00 | 0.856099E+10 | 0.261783E+09 | 0.00 | 6.24 |
April | 0.100561E+11 | 3387283.61 | 0.00 | 117908.47 | 5599987.29 | 0.183069E+10 | 0.278259E+09 | 0.00 | 6.27 |
May | 0.949717E+10 | 26128732.37 | 0.00 | 13581.23 | 0.146894E+09 | 30563853.11 | 62595175.76 | 0.00 | 6.29 |
June | 0.569112E+10 | 90257824.84 | 0.00 | 0.00 | 0.212851E+10 | 0.00 | 0.00 | 0.00 | 6.32 |
July | 0.413506E+10 | 0.184648E+09 | 0.00 | 884.24 | 0.345966E+10 | 0.00 | 2056423.86 | 0.00 | 6.33 |
August | 0.555040E+10 | 0.162811E+09 | 0.00 | 27066.57 | 0.154969E+10 | 0.00 | 7838739.39 | 0.00 | 6.31 |
September | 0.998277E+10 | 17869479.18 | 0.00 | 224514.46 | 0.100613E+09 | 0.00 | 0.280901E+09 | 0.00 | 6.31 |
October | 0.108967E+11 | 0.00 | 0.00 | 419037.47 | 0.00 | 0.130672E+10 | 0.349496E+09 | 0.00 | 6.26 |
November | 0.664389E+10 | 0.00 | 0.00 | 20299.55 | 0.00 | 0.693197E+10 | 0.109807E+09 | 0.00 | 6.28 |
December | 0.119351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.233454E+11 | 0.00 | 0.00 | 6.16 |
Annual Sum or Average | 0.774403E+11 | 0.485102E+09 | 0.00 | 948371.47 | 0.739097E+10 | 0.810230E+11 | 0.156723E+10 | 0.00 | 6.26 |
Minimum of Months | 0.119351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.16 |
Maximum of Months | 0.108967E+11 | 0.184648E+09 | 0.00 | 419037.47 | 0.345966E+10 | 0.249984E+11 | 0.349496E+09 | 0.00 | 6.33 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.430670E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.982857E+10 | 0.00 | 0.00 | 2.84 |
February | 0.594587E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.410256E+10 | 0.00 | 0.00 | 2.86 |
March | 0.753160E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123015E+10 | 0.00 | 0.00 | 2.87 |
April | 0.648020E+10 | 0.00 | 0.00 | 0.00 | 4787392.37 | 0.00 | 0.00 | 0.00 | 2.88 |
May | 0.510864E+10 | 0.00 | 0.00 | 0.00 | 92166744.68 | 0.00 | 0.00 | 0.00 | 2.90 |
June | 0.303158E+10 | 0.00 | 0.00 | 0.00 | 0.118190E+10 | 0.00 | 0.00 | 0.00 | 2.91 |
July | 0.220378E+10 | 0.00 | 0.00 | 0.00 | 0.194127E+10 | 0.00 | 0.00 | 0.00 | 2.91 |
August | 0.296081E+10 | 0.00 | 0.00 | 0.00 | 0.912228E+09 | 0.00 | 0.00 | 0.00 | 2.90 |
September | 0.546743E+10 | 0.00 | 0.00 | 0.00 | 63113845.93 | 0.00 | 0.00 | 0.00 | 2.90 |
October | 0.668696E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.88 |
November | 0.729017E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.89 |
December | 0.513607E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.793545E+10 | 0.00 | 0.00 | 2.84 |
Annual Sum or Average | 0.621498E+11 | 0.00 | 0.00 | 0.00 | 0.419547E+10 | 0.230967E+11 | 0.00 | 0.00 | 2.88 |
Minimum of Months | 0.220378E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.84 |
Maximum of Months | 0.753160E+10 | 0.00 | 0.00 | 0.00 | 0.194127E+10 | 0.982857E+10 | 0.00 | 0.00 | 2.91 |
Report: MechanicalVentilationLoadsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.658043E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131282E+11 | 0.00 | 0.00 | 1.31 |
February | 0.157649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.822385E+10 | 0.00 | 0.00 | 1.32 |
March | 0.386783E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.467759E+10 | 0.00 | 0.00 | 1.32 |
April | 0.610958E+10 | 0.00 | 0.00 | 0.00 | 4669192.30 | 0.210629E+09 | 0.00 | 0.00 | 1.33 |
May | 0.498251E+10 | 0.00 | 0.00 | 0.00 | 89891160.15 | 0.00 | 0.00 | 0.00 | 1.33 |
June | 0.295673E+10 | 0.00 | 0.00 | 0.00 | 0.115272E+10 | 0.00 | 0.00 | 0.00 | 1.34 |
July | 0.214937E+10 | 0.00 | 0.00 | 0.00 | 0.189334E+10 | 0.00 | 0.00 | 0.00 | 1.34 |
August | 0.288771E+10 | 0.00 | 0.00 | 0.00 | 0.889705E+09 | 0.00 | 0.00 | 0.00 | 1.34 |
September | 0.533244E+10 | 0.00 | 0.00 | 0.00 | 61555573.57 | 0.00 | 0.00 | 0.00 | 1.34 |
October | 0.647734E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44522987.54 | 0.00 | 0.00 | 1.33 |
November | 0.512291E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.198726E+10 | 0.00 | 0.00 | 1.33 |
December | 0.912226E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118366E+11 | 0.00 | 0.00 | 1.31 |
Annual Sum or Average | 0.430332E+11 | 0.00 | 0.00 | 0.00 | 0.409188E+10 | 0.401086E+11 | 0.00 | 0.00 | 1.33 |
Minimum of Months | 0.658043E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.31 |
Maximum of Months | 0.647734E+10 | 0.00 | 0.00 | 0.00 | 0.189334E+10 | 0.131282E+11 | 0.00 | 0.00 | 1.34 |
Report: MechanicalVentilationLoadsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 8859681.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.682622E+10 | 0.00 | 0.00 | 1.12 |
February | 0.116793E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.474211E+10 | 0.00 | 0.00 | 1.13 |
March | 0.565193E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.367154E+10 | 0.00 | 0.00 | 1.14 |
April | 0.222055E+10 | 0.00 | 0.00 | 0.00 | 2314936.10 | 0.912937E+09 | 0.00 | 0.00 | 1.14 |
May | 0.245950E+10 | 0.00 | 0.00 | 0.00 | 44567085.34 | 10777253.31 | 0.00 | 0.00 | 1.15 |
June | 0.146591E+10 | 0.00 | 0.00 | 0.00 | 0.571508E+09 | 0.00 | 0.00 | 0.00 | 1.15 |
July | 0.106564E+10 | 0.00 | 0.00 | 0.00 | 0.938698E+09 | 0.00 | 0.00 | 0.00 | 1.15 |
August | 0.143169E+10 | 0.00 | 0.00 | 0.00 | 0.441106E+09 | 0.00 | 0.00 | 0.00 | 1.15 |
September | 0.264377E+10 | 0.00 | 0.00 | 0.00 | 30518601.56 | 0.00 | 0.00 | 0.00 | 1.15 |
October | 0.273508E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.498393E+09 | 0.00 | 0.00 | 1.14 |
November | 0.904475E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.262068E+10 | 0.00 | 0.00 | 1.14 |
December | 14605245.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.630611E+10 | 0.00 | 0.00 | 1.12 |
Annual Sum or Average | 0.156321E+11 | 0.00 | 0.00 | 0.00 | 0.202871E+10 | 0.255888E+11 | 0.00 | 0.00 | 1.14 |
Minimum of Months | 8859681.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.12 |
Maximum of Months | 0.273508E+10 | 0.00 | 0.00 | 0.00 | 0.938698E+09 | 0.682622E+10 | 0.00 | 0.00 | 1.15 |
Report: MechanicalVentilationLoadsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.106455E+11 | 0.00 | 0.00 | 40438380.13 | 0.00 | 0.854515E+11 | 0.992287E+11 | 0.00 | 38.94 |
February | 0.531621E+10 | 0.00 | 0.00 | 47383363.12 | 0.00 | 0.339199E+11 | 0.996098E+11 | 0.00 | 39.32 |
March | 0.377263E+10 | 0.00 | 0.00 | 61148714.81 | 0.00 | 0.111160E+11 | 0.106179E+12 | 0.00 | 39.53 |
April | 0.160545E+10 | 61807565.22 | 0.00 | 62566869.94 | 4353362.37 | 0.00 | 0.879221E+11 | 0.00 | 39.69 |
May | 0.116542E+10 | 0.121780E+10 | 0.00 | 61782345.07 | 55925166.42 | 0.00 | 0.693969E+11 | 0.00 | 39.85 |
June | 0.850268E+09 | 0.158216E+11 | 0.00 | 42182750.98 | 0.514870E+09 | 0.00 | 0.410149E+11 | 0.00 | 40.01 |
July | 0.522674E+09 | 0.258162E+11 | 0.00 | 32036835.20 | 0.101607E+10 | 0.00 | 0.299057E+11 | 0.00 | 40.09 |
August | 0.593357E+09 | 0.121200E+11 | 0.00 | 43080563.87 | 0.490290E+09 | 0.00 | 0.402923E+11 | 0.00 | 39.96 |
September | 0.934747E+09 | 0.828326E+09 | 0.00 | 62855222.51 | 43896630.26 | 0.00 | 0.745912E+11 | 0.00 | 39.94 |
October | 0.115665E+10 | 0.00 | 0.00 | 65372365.26 | 0.00 | 0.00 | 0.912285E+11 | 0.00 | 39.65 |
November | 0.253013E+10 | 0.00 | 0.00 | 61486997.97 | 0.00 | 0.00 | 0.981952E+11 | 0.00 | 39.80 |
December | 0.102142E+11 | 0.00 | 0.00 | 43878167.82 | 0.00 | 0.687708E+11 | 0.101639E+12 | 0.00 | 38.93 |
Annual Sum or Average | 0.393073E+11 | 0.558657E+11 | 0.00 | 0.624213E+09 | 0.212541E+10 | 0.199258E+12 | 0.939204E+12 | 0.00 | 39.64 |
Minimum of Months | 0.522674E+09 | 0.00 | 0.00 | 32036835.20 | 0.00 | 0.00 | 0.299057E+11 | 0.00 | 38.93 |
Maximum of Months | 0.106455E+11 | 0.258162E+11 | 0.00 | 65372365.26 | 0.101607E+10 | 0.854515E+11 | 0.106179E+12 | 0.00 | 40.09 |
Report: MechanicalVentilationLoadsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.458607E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.602724E+11 | 0.00 | 0.00 | 8.77 |
February | 0.509628E+11 | 0.00 | 0.00 | 515905.48 | 0.00 | 0.225390E+11 | 0.194524E+10 | 0.00 | 8.84 |
March | 0.561917E+11 | 0.00 | 0.00 | 539624.58 | 0.00 | 0.777143E+10 | 0.182295E+10 | 0.00 | 8.87 |
April | 0.466713E+11 | 13547827.27 | 0.00 | 689818.34 | 22397788.06 | 0.00 | 0.198393E+10 | 0.00 | 8.90 |
May | 0.373734E+11 | 0.162046E+09 | 0.00 | 185714.35 | 0.529978E+09 | 0.00 | 0.984080E+09 | 0.00 | 8.94 |
June | 0.224412E+11 | 0.133134E+10 | 0.00 | 29693.32 | 0.754286E+10 | 0.00 | 0.321009E+09 | 0.00 | 8.98 |
July | 0.161835E+11 | 0.174910E+10 | 0.00 | 42430.35 | 0.128267E+11 | 0.00 | 0.363269E+09 | 0.00 | 9.00 |
August | 0.218524E+11 | 0.112549E+10 | 0.00 | 229810.78 | 0.572388E+10 | 0.00 | 0.378267E+09 | 0.00 | 8.97 |
September | 0.391707E+11 | 93739587.20 | 0.00 | 1090922.89 | 0.380144E+09 | 0.00 | 0.187986E+10 | 0.00 | 8.96 |
October | 0.481447E+11 | 0.00 | 0.00 | 1558374.36 | 0.00 | 0.00 | 0.206208E+10 | 0.00 | 8.90 |
November | 0.537279E+11 | 0.00 | 0.00 | 204431.89 | 0.00 | 61252953.50 | 0.948096E+09 | 0.00 | 8.93 |
December | 0.483905E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.497556E+11 | 0.00 | 0.00 | 8.76 |
Annual Sum or Average | 0.486971E+12 | 0.447526E+10 | 0.00 | 5086726.34 | 0.270260E+11 | 0.140400E+12 | 0.126888E+11 | 0.00 | 8.90 |
Minimum of Months | 0.161835E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.76 |
Maximum of Months | 0.561917E+11 | 0.174910E+10 | 0.00 | 1558374.36 | 0.128267E+11 | 0.602724E+11 | 0.206208E+10 | 0.00 | 9.00 |
Report: MechanicalVentilationLoadsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.120009E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182519E+12 | 0.00 | 0.00 | 3.61 |
February | 0.146535E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.685247E+11 | 0.00 | 0.00 | 3.64 |
March | 0.166591E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.209315E+11 | 0.00 | 0.00 | 3.65 |
April | 0.138692E+12 | 0.00 | 0.00 | 0.00 | 0.102461E+09 | 0.00 | 0.00 | 0.00 | 3.66 |
May | 0.109337E+12 | 0.00 | 0.00 | 0.00 | 0.197259E+10 | 0.00 | 0.00 | 0.00 | 3.68 |
June | 0.648829E+11 | 0.00 | 0.00 | 0.00 | 0.252955E+11 | 0.00 | 0.00 | 0.00 | 3.70 |
July | 0.471661E+11 | 0.00 | 0.00 | 0.00 | 0.415478E+11 | 0.00 | 0.00 | 0.00 | 3.70 |
August | 0.633682E+11 | 0.00 | 0.00 | 0.00 | 0.195238E+11 | 0.00 | 0.00 | 0.00 | 3.69 |
September | 0.117016E+12 | 0.00 | 0.00 | 0.00 | 0.135078E+10 | 0.00 | 0.00 | 0.00 | 3.69 |
October | 0.143117E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.66 |
November | 0.156027E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 |
December | 0.131147E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148614E+12 | 0.00 | 0.00 | 3.61 |
Annual Sum or Average | 0.140389E+13 | 0.00 | 0.00 | 0.00 | 0.897929E+11 | 0.420589E+12 | 0.00 | 0.00 | 3.66 |
Minimum of Months | 0.471661E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.61 |
Maximum of Months | 0.166591E+12 | 0.00 | 0.00 | 0.00 | 0.415478E+11 | 0.182519E+12 | 0.00 | 0.00 | 3.70 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.216829E+09 | 0.00 | 0.00 | 25642.62 | 0.00 | 0.370037E+10 | 2704107.42 | 0.00 | 0.47 |
February | 0.336924E+09 | 0.00 | 0.00 | 777851.09 | 0.00 | 0.211555E+10 | 78872243.84 | 0.00 | 0.47 |
March | 0.386017E+09 | 0.00 | 0.00 | 2752126.53 | 0.00 | 0.148325E+10 | 0.228275E+09 | 0.00 | 0.47 |
April | 0.336265E+09 | 1758161.52 | 0.00 | 7186599.73 | 16938.22 | 0.636760E+09 | 0.654195E+09 | 0.00 | 0.47 |
May | 0.182764E+09 | 27406279.66 | 12396.32 | 13058938.69 | 1584048.86 | 85318944.50 | 0.106184E+10 | 2168.19 | 0.47 |
June | 99959632.02 | 0.303431E+09 | 263277.11 | 9789141.73 | 22993946.95 | 13220251.99 | 0.631368E+09 | 19483.50 | 0.48 |
July | 41297680.47 | 0.536472E+09 | 323916.66 | 7379166.22 | 29947170.46 | 564884.33 | 0.416972E+09 | 17531.85 | 0.48 |
August | 86576870.40 | 0.261439E+09 | 211573.17 | 8511904.00 | 21035809.63 | 14914290.79 | 0.556891E+09 | 11067.66 | 0.48 |
September | 0.232794E+09 | 16659058.91 | 27716.26 | 10130181.21 | 1053449.37 | 0.158139E+09 | 0.994328E+09 | 3126.40 | 0.48 |
October | 0.383002E+09 | 0.00 | 0.00 | 4102976.73 | 0.00 | 0.748841E+09 | 0.532282E+09 | 0.00 | 0.47 |
November | 0.360810E+09 | 0.00 | 0.00 | 359880.19 | 0.00 | 0.125042E+10 | 61787788.69 | 0.00 | 0.47 |
December | 0.174456E+09 | 0.00 | 0.00 | 3153.60 | 0.00 | 0.330042E+10 | 120997.29 | 0.00 | 0.47 |
Annual Sum or Average | 0.283770E+10 | 0.114717E+10 | 838879.52 | 64077562.34 | 76631363.48 | 0.135078E+11 | 0.521963E+10 | 53377.59 | 0.47 |
Minimum of Months | 41297680.47 | 0.00 | 0.00 | 3153.60 | 0.00 | 564884.33 | 120997.29 | 0.00 | 0.47 |
Maximum of Months | 0.386017E+09 | 0.536472E+09 | 323916.66 | 13058938.69 | 29947170.46 | 0.370037E+10 | 0.106184E+10 | 19483.50 | 0.48 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 77115314.63 | 0.00 | 0.00 | 2556.66 | 0.00 | 0.384223E+10 | 113663.11 | 0.00 | 0.47 |
February | 0.208324E+09 | 0.00 | 0.00 | 179337.92 | 0.00 | 0.230320E+10 | 20124548.84 | 0.00 | 0.47 |
March | 0.327354E+09 | 0.00 | 0.00 | 1232095.83 | 0.00 | 0.164211E+10 | 0.129355E+09 | 0.00 | 0.47 |
April | 0.414358E+09 | 1716610.18 | 0.00 | 4735740.46 | 58281.58 | 0.744504E+09 | 0.470618E+09 | 0.00 | 0.47 |
May | 0.239029E+09 | 26960217.19 | 11333.62 | 11401954.53 | 2026714.69 | 0.110102E+09 | 0.982289E+09 | 3229.18 | 0.47 |
June | 0.109680E+09 | 0.300653E+09 | 300412.10 | 9219982.47 | 25694493.92 | 12499022.35 | 0.622849E+09 | 21368.35 | 0.48 |
July | 43953382.74 | 0.531445E+09 | 460686.28 | 6956761.17 | 34768500.29 | 486099.57 | 0.414763E+09 | 20814.40 | 0.48 |
August | 92819401.47 | 0.253774E+09 | 279910.29 | 7463676.97 | 28595371.71 | 16193372.68 | 0.550339E+09 | 14798.91 | 0.48 |
September | 0.308138E+09 | 15389045.50 | 26890.34 | 7239695.66 | 2321387.50 | 0.207498E+09 | 0.872352E+09 | 3948.71 | 0.48 |
October | 0.438661E+09 | 0.00 | 0.00 | 1996268.79 | 0.00 | 0.890725E+09 | 0.336650E+09 | 0.00 | 0.47 |
November | 0.298612E+09 | 0.00 | 0.00 | 85219.56 | 0.00 | 0.135936E+10 | 15121109.85 | 0.00 | 0.47 |
December | 66619387.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.340798E+10 | 0.00 | 0.00 | 0.47 |
Annual Sum or Average | 0.262466E+10 | 0.112994E+10 | 1079232.63 | 50513290.03 | 93464749.69 | 0.145369E+11 | 0.441458E+10 | 64159.55 | 0.47 |
Minimum of Months | 43953382.74 | 0.00 | 0.00 | 0.00 | 0.00 | 486099.57 | 0.00 | 0.00 | 0.47 |
Maximum of Months | 0.438661E+09 | 0.531445E+09 | 460686.28 | 11401954.53 | 34768500.29 | 0.384223E+10 | 0.982289E+09 | 21368.35 | 0.48 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.205982E+11 | 0.00 | 0.00 | 631556.05 | 0.00 | 0.321328E+11 | 0.419073E+09 | 0.00 | 0.53 |
February | 0.199515E+11 | 0.00 | 0.00 | 9858184.83 | 0.00 | 0.119538E+11 | 0.241808E+10 | 0.00 | 0.53 |
March | 0.214986E+11 | 0.00 | 0.00 | 23398402.75 | 0.00 | 0.264324E+10 | 0.431292E+10 | 0.00 | 0.53 |
April | 0.111303E+11 | 24068760.44 | 0.00 | 61724207.86 | 0.00 | 0.00 | 0.109691E+11 | 0.00 | 0.54 |
May | 0.341500E+10 | 0.393280E+09 | 0.00 | 95308988.15 | 0.00 | 0.00 | 0.146993E+11 | 0.00 | 0.54 |
June | 0.174784E+10 | 0.442045E+10 | 0.00 | 68621577.52 | 9416885.14 | 0.00 | 0.841166E+10 | 0.00 | 0.54 |
July | 0.353057E+09 | 0.768333E+10 | 0.00 | 50555715.13 | 1442871.44 | 0.00 | 0.591783E+10 | 0.00 | 0.54 |
August | 0.698124E+09 | 0.383312E+10 | 0.00 | 67599455.89 | 0.00 | 0.00 | 0.827676E+10 | 0.00 | 0.54 |
September | 0.351018E+10 | 0.240584E+09 | 0.00 | 0.102564E+09 | 0.00 | 0.00 | 0.153075E+11 | 0.00 | 0.54 |
October | 0.131012E+11 | 0.00 | 0.00 | 58757709.73 | 0.00 | 0.00 | 0.945971E+10 | 0.00 | 0.54 |
November | 0.164680E+11 | 0.00 | 0.00 | 9752437.94 | 0.00 | 0.413201E+10 | 0.207968E+10 | 0.00 | 0.54 |
December | 0.145437E+11 | 0.00 | 0.00 | 170698.90 | 0.00 | 0.324426E+11 | 0.131468E+09 | 0.00 | 0.53 |
Annual Sum or Average | 0.127016E+12 | 0.165948E+11 | 0.00 | 0.548943E+09 | 10859756.58 | 0.833045E+11 | 0.824031E+11 | 0.00 | 0.54 |
Minimum of Months | 0.353057E+09 | 0.00 | 0.00 | 170698.90 | 0.00 | 0.00 | 0.131468E+09 | 0.00 | 0.53 |
Maximum of Months | 0.214986E+11 | 0.768333E+10 | 0.00 | 0.102564E+09 | 9416885.14 | 0.324426E+11 | 0.153075E+11 | 0.00 | 0.54 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.610443E+10 | 0.00 | 0.00 | 824694.05 | 0.00 | 0.461886E+11 | 0.871376E+09 | 0.00 | 0.53 |
February | 0.704430E+10 | 0.00 | 0.00 | 2566285.77 | 0.00 | 0.251346E+11 | 0.216121E+10 | 0.00 | 0.53 |
March | 0.704511E+10 | 0.00 | 0.00 | 11176019.00 | 0.00 | 0.151498E+11 | 0.627987E+10 | 0.00 | 0.53 |
April | 0.627500E+10 | 13551918.71 | 61259.57 | 50258345.09 | 10459065.49 | 0.175460E+10 | 0.140873E+11 | 3098.23 | 0.54 |
May | 0.425000E+10 | 0.276325E+09 | 24341.29 | 0.116857E+09 | 0.117034E+09 | 32891267.49 | 0.138148E+11 | 4377.67 | 0.54 |
June | 0.195089E+10 | 0.368398E+10 | 1873153.16 | 96364209.40 | 0.745173E+09 | 9979259.07 | 0.817369E+10 | 46817.79 | 0.54 |
July | 0.922495E+09 | 0.652856E+10 | 1387804.27 | 68345025.68 | 0.115688E+10 | 3611802.31 | 0.532872E+10 | 41826.09 | 0.54 |
August | 0.154287E+10 | 0.272232E+10 | 2784964.71 | 79218227.18 | 0.110901E+10 | 7469944.01 | 0.741540E+10 | 60748.54 | 0.54 |
September | 0.494623E+10 | 0.160024E+09 | 249406.03 | 93421678.19 | 80376454.79 | 44778258.91 | 0.138410E+11 | 141.97 | 0.54 |
October | 0.627263E+10 | 0.00 | 0.00 | 49436553.81 | 0.00 | 0.441429E+09 | 0.158624E+11 | 0.00 | 0.54 |
November | 0.615402E+10 | 0.00 | 0.00 | 12759348.28 | 0.00 | 0.893718E+10 | 0.759169E+10 | 0.00 | 0.54 |
December | 0.723546E+10 | 0.00 | 0.00 | 1013815.76 | 0.00 | 0.388924E+11 | 0.100191E+10 | 0.00 | 0.53 |
Annual Sum or Average | 0.597434E+11 | 0.133848E+11 | 6380929.04 | 0.582241E+09 | 0.321893E+10 | 0.136597E+12 | 0.964294E+11 | 157010.29 | 0.54 |
Minimum of Months | 0.922495E+09 | 0.00 | 0.00 | 824694.05 | 0.00 | 3611802.31 | 0.871376E+09 | 0.00 | 0.53 |
Maximum of Months | 0.723546E+10 | 0.652856E+10 | 2784964.71 | 0.116857E+09 | 0.115688E+10 | 0.461886E+11 | 0.158624E+11 | 60748.54 | 0.54 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.202864E+09 | 0.00 | 0.00 | 8696.94 | 0.00 | 0.371573E+10 | 1321610.15 | 0.00 | 0.47 |
February | 0.383417E+09 | 0.00 | 0.00 | 404929.90 | 0.00 | 0.207404E+10 | 74255929.62 | 0.00 | 0.47 |
March | 0.389154E+09 | 0.00 | 0.00 | 1951608.61 | 0.00 | 0.143048E+10 | 0.278710E+09 | 0.00 | 0.47 |
April | 0.284243E+09 | 1625507.49 | 3178.26 | 7574196.67 | 145340.49 | 0.603650E+09 | 0.738940E+09 | 1073.50 | 0.47 |
May | 0.140727E+09 | 27994697.34 | 4493.04 | 13001537.04 | 1004887.30 | 0.108728E+09 | 0.108052E+10 | 815.34 | 0.47 |
June | 48948497.24 | 0.310132E+09 | 189985.39 | 12041118.40 | 16377115.29 | 7139202.54 | 0.686208E+09 | 8643.79 | 0.48 |
July | 28649837.70 | 0.545813E+09 | 243773.58 | 8308511.50 | 20697770.93 | 410549.33 | 0.428845E+09 | 5990.47 | 0.48 |
August | 69934697.31 | 0.262517E+09 | 293078.58 | 8974915.17 | 19869642.77 | 13130928.70 | 0.574853E+09 | 17367.51 | 0.48 |
September | 0.217192E+09 | 16936963.59 | 26629.08 | 10273807.27 | 775544.70 | 0.177442E+09 | 0.990483E+09 | 4213.58 | 0.48 |
October | 0.375270E+09 | 0.00 | 0.00 | 3860633.69 | 0.00 | 0.784058E+09 | 0.505039E+09 | 0.00 | 0.47 |
November | 0.363863E+09 | 0.00 | 0.00 | 415382.08 | 0.00 | 0.124010E+10 | 68992153.97 | 0.00 | 0.47 |
December | 0.162222E+09 | 0.00 | 0.00 | 4720.34 | 0.00 | 0.330975E+10 | 3028856.30 | 0.00 | 0.47 |
Annual Sum or Average | 0.266649E+10 | 0.116502E+10 | 761137.92 | 66820057.61 | 58870301.47 | 0.134647E+11 | 0.543120E+10 | 38104.19 | 0.47 |
Minimum of Months | 28649837.70 | 0.00 | 0.00 | 4720.34 | 0.00 | 410549.33 | 1321610.15 | 0.00 | 0.47 |
Maximum of Months | 0.389154E+09 | 0.545813E+09 | 293078.58 | 13001537.04 | 20697770.93 | 0.371573E+10 | 0.108052E+10 | 17367.51 | 0.48 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 74880298.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.384459E+10 | 0.00 | 0.00 | 0.47 |
February | 0.216314E+09 | 0.00 | 0.00 | 50186.95 | 0.00 | 0.230035E+10 | 15116328.45 | 0.00 | 0.47 |
March | 0.369891E+09 | 0.00 | 0.00 | 564542.70 | 0.00 | 0.160286E+10 | 0.126739E+09 | 0.00 | 0.47 |
April | 0.379038E+09 | 1589511.48 | 11409.69 | 4738364.88 | 171571.26 | 0.690431E+09 | 0.560008E+09 | 2399.33 | 0.47 |
May | 0.182387E+09 | 27550438.73 | 3854.18 | 11229012.10 | 1445748.20 | 0.133685E+09 | 0.101552E+10 | 1453.57 | 0.47 |
June | 52848533.45 | 0.308902E+09 | 174260.51 | 11434219.75 | 17586141.92 | 7157570.62 | 0.682808E+09 | 7320.17 | 0.48 |
July | 32275372.13 | 0.542588E+09 | 270372.60 | 7853118.18 | 23831533.59 | 406433.60 | 0.425625E+09 | 5182.88 | 0.48 |
August | 73636584.11 | 0.255390E+09 | 432218.30 | 7859828.14 | 26817102.35 | 13560723.49 | 0.571758E+09 | 25012.42 | 0.48 |
September | 0.261567E+09 | 15508887.09 | 59396.02 | 7189140.66 | 2168485.47 | 0.240385E+09 | 0.886087E+09 | 4503.47 | 0.48 |
October | 0.457134E+09 | 0.00 | 0.00 | 1494827.98 | 0.00 | 0.933185E+09 | 0.276219E+09 | 0.00 | 0.47 |
November | 0.277940E+09 | 0.00 | 0.00 | 99221.67 | 0.00 | 0.136656E+10 | 28580809.38 | 0.00 | 0.47 |
December | 80852435.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.339375E+10 | 0.00 | 0.00 | 0.47 |
Annual Sum or Average | 0.245876E+10 | 0.115153E+10 | 951511.31 | 52512463.01 | 72020582.79 | 0.145269E+11 | 0.458846E+10 | 45871.84 | 0.47 |
Minimum of Months | 32275372.13 | 0.00 | 0.00 | 0.00 | 0.00 | 406433.60 | 0.00 | 0.00 | 0.47 |
Maximum of Months | 0.457134E+09 | 0.542588E+09 | 432218.30 | 11434219.75 | 26817102.35 | 0.384459E+10 | 0.101552E+10 | 25012.42 | 0.48 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.331502E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.728740E+11 | 0.00 | 0.00 | 1.00 |
February | 0.166891E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.374719E+11 | 0.00 | 0.00 | 1.00 |
March | 0.316423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155836E+11 | 0.00 | 0.00 | 1.00 |
April | 0.347806E+11 | 0.00 | 0.00 | 0.00 | 25804041.10 | 0.147633E+09 | 0.00 | 0.00 | 1.01 |
May | 0.275356E+11 | 0.00 | 0.00 | 0.00 | 0.496779E+09 | 0.00 | 0.00 | 0.00 | 1.01 |
June | 0.163402E+11 | 0.00 | 0.00 | 0.00 | 0.637046E+10 | 0.00 | 0.00 | 0.00 | 1.02 |
July | 0.118784E+11 | 0.00 | 0.00 | 0.00 | 0.104634E+11 | 0.00 | 0.00 | 0.00 | 1.02 |
August | 0.159587E+11 | 0.00 | 0.00 | 0.00 | 0.491691E+10 | 0.00 | 0.00 | 0.00 | 1.01 |
September | 0.294694E+11 | 0.00 | 0.00 | 0.00 | 0.340184E+09 | 0.00 | 0.00 | 0.00 | 1.01 |
October | 0.357487E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.293977E+09 | 0.00 | 0.00 | 1.01 |
November | 0.297730E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.952100E+10 | 0.00 | 0.00 | 1.01 |
December | 0.382964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.666258E+11 | 0.00 | 0.00 | 0.99 |
Annual Sum or Average | 0.256961E+12 | 0.00 | 0.00 | 0.00 | 0.226136E+11 | 0.202518E+12 | 0.00 | 0.00 | 1.01 |
Minimum of Months | 0.331502E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.99 |
Maximum of Months | 0.357487E+11 | 0.00 | 0.00 | 0.00 | 0.104634E+11 | 0.728740E+11 | 0.00 | 0.00 | 1.02 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 35244023.73 | 0.00 | 0.00 | 8598.35 | 0.00 | 0.944214E+09 | 514805.75 | 0.00 | 0.47 |
February | 63774603.89 | 0.00 | 0.00 | 180059.02 | 0.00 | 0.555880E+09 | 13196059.21 | 0.00 | 0.47 |
March | 82206516.25 | 0.00 | 0.00 | 693777.03 | 0.00 | 0.395081E+09 | 47092886.99 | 0.00 | 0.47 |
April | 82098945.44 | 439540.38 | 0.00 | 1879430.95 | 4234.55 | 0.183148E+09 | 0.141476E+09 | 0.00 | 0.47 |
May | 42905859.97 | 6911737.52 | 2078.50 | 3518547.86 | 337171.70 | 36182682.05 | 0.253138E+09 | 235.53 | 0.47 |
June | 20761703.22 | 77273091.44 | 64306.30 | 2667993.63 | 4335982.26 | 4525491.45 | 0.160629E+09 | 3567.33 | 0.48 |
July | 10275550.63 | 0.135146E+09 | 89635.34 | 1952399.12 | 6451631.17 | 146663.91 | 0.104179E+09 | 3075.43 | 0.48 |
August | 21116184.33 | 66317133.77 | 39978.88 | 2247673.67 | 4315857.38 | 7176257.46 | 0.136183E+09 | 1334.90 | 0.48 |
September | 57507334.36 | 4209168.10 | 2770.81 | 2649710.59 | 223516.81 | 58242428.53 | 0.230448E+09 | 382.01 | 0.48 |
October | 91606615.38 | 0.00 | 0.00 | 1017106.05 | 0.00 | 0.216348E+09 | 0.108085E+09 | 0.00 | 0.47 |
November | 70703913.91 | 0.00 | 0.00 | 83853.60 | 0.00 | 0.338903E+09 | 8652384.20 | 0.00 | 0.47 |
December | 26911403.25 | 0.00 | 0.00 | 3011.32 | 0.00 | 0.841611E+09 | 225638.67 | 0.00 | 0.47 |
Annual Sum or Average | 0.605113E+09 | 0.290297E+09 | 198769.84 | 16902161.17 | 15668393.87 | 0.358146E+10 | 0.120382E+10 | 8595.20 | 0.47 |
Minimum of Months | 10275550.63 | 0.00 | 0.00 | 3011.32 | 0.00 | 146663.91 | 225638.67 | 0.00 | 0.47 |
Maximum of Months | 91606615.38 | 0.135146E+09 | 89635.34 | 3518547.86 | 6451631.17 | 0.944214E+09 | 0.253138E+09 | 3567.33 | 0.48 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 12102727.83 | 0.00 | 0.00 | 2066.97 | 0.00 | 0.967664E+09 | 98298.40 | 0.00 | 0.47 |
February | 30250755.19 | 0.00 | 0.00 | 34638.32 | 0.00 | 0.598122E+09 | 4548962.34 | 0.00 | 0.47 |
March | 57895720.21 | 0.00 | 0.00 | 294657.61 | 0.00 | 0.440650E+09 | 26172612.24 | 0.00 | 0.47 |
April | 95937350.99 | 439488.88 | 0.00 | 1230765.70 | 4234.06 | 0.211553E+09 | 99833088.11 | 0.00 | 0.47 |
May | 55927480.20 | 6817659.50 | 3270.74 | 3068852.30 | 429073.47 | 44866934.48 | 0.231842E+09 | 369.96 | 0.47 |
June | 24158883.18 | 76754305.18 | 57910.08 | 2512674.17 | 4851319.35 | 4386876.79 | 0.157504E+09 | 3843.07 | 0.48 |
July | 10647941.76 | 0.134262E+09 | 88912.96 | 1840076.58 | 7318519.19 | 139011.79 | 0.103913E+09 | 3786.95 | 0.48 |
August | 22583772.90 | 64958355.87 | 45361.12 | 1973164.09 | 5660082.12 | 7667024.91 | 0.134480E+09 | 2225.29 | 0.48 |
September | 74900601.38 | 4067782.57 | 6859.74 | 1872558.68 | 359825.68 | 80113637.69 | 0.191920E+09 | 850.02 | 0.48 |
October | 0.106037E+09 | 0.00 | 0.00 | 464657.35 | 0.00 | 0.257958E+09 | 52548277.74 | 0.00 | 0.47 |
November | 47836834.56 | 0.00 | 0.00 | 24489.42 | 0.00 | 0.368165E+09 | 2267679.23 | 0.00 | 0.47 |
December | 11308161.44 | 0.00 | 0.00 | 216.50 | 0.00 | 0.857319E+09 | 22158.08 | 0.00 | 0.47 |
Annual Sum or Average | 0.549588E+09 | 0.287300E+09 | 202314.64 | 13318817.69 | 18623053.88 | 0.383860E+10 | 0.100515E+10 | 11075.29 | 0.47 |
Minimum of Months | 10647941.76 | 0.00 | 0.00 | 216.50 | 0.00 | 139011.79 | 22158.08 | 0.00 | 0.47 |
Maximum of Months | 0.106037E+09 | 0.134262E+09 | 88912.96 | 3068852.30 | 7318519.19 | 0.967664E+09 | 0.231842E+09 | 3843.07 | 0.48 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.730220E+09 | 0.00 | 0.00 | 2270206.73 | 0.00 | 0.520008E+10 | 0.363307E+09 | 0.00 | 0.53 |
February | 0.501835E+09 | 0.00 | 0.00 | 5426741.19 | 0.00 | 0.293152E+10 | 0.628114E+09 | 0.00 | 0.53 |
March | 0.501258E+09 | 0.00 | 0.00 | 7731565.62 | 0.00 | 0.201310E+10 | 0.851243E+09 | 0.00 | 0.53 |
April | 0.401934E+09 | 2762608.61 | 0.00 | 13138070.79 | 88418.74 | 0.763154E+09 | 0.144683E+10 | 0.00 | 0.54 |
May | 0.248291E+09 | 44413869.18 | 13500.94 | 18784971.17 | 2156670.87 | 0.103440E+09 | 0.178647E+10 | 1365.54 | 0.54 |
June | 0.130067E+09 | 0.489507E+09 | 285327.58 | 13937162.23 | 34919991.03 | 17937213.17 | 0.104962E+10 | 20797.18 | 0.54 |
July | 66367716.61 | 0.861806E+09 | 625555.95 | 9993714.97 | 47831037.63 | 763988.14 | 0.671671E+09 | 25135.35 | 0.54 |
August | 0.123629E+09 | 0.429287E+09 | 313666.56 | 13074926.43 | 24434881.42 | 13068802.74 | 0.921340E+09 | 11136.93 | 0.54 |
September | 0.338591E+09 | 27267090.43 | 18298.76 | 19958564.52 | 1210646.54 | 83394065.21 | 0.179923E+10 | 1956.53 | 0.54 |
October | 0.563159E+09 | 0.00 | 0.00 | 12279292.20 | 0.00 | 0.815063E+09 | 0.128888E+10 | 0.00 | 0.54 |
November | 0.486119E+09 | 0.00 | 0.00 | 3692385.26 | 0.00 | 0.169094E+10 | 0.506890E+09 | 0.00 | 0.54 |
December | 0.582313E+09 | 0.00 | 0.00 | 1480100.38 | 0.00 | 0.472707E+10 | 0.270422E+09 | 0.00 | 0.53 |
Annual Sum or Average | 0.467378E+10 | 0.185504E+10 | 1256349.80 | 0.121768E+09 | 0.110642E+09 | 0.183595E+11 | 0.115840E+11 | 60391.54 | 0.54 |
Minimum of Months | 66367716.61 | 0.00 | 0.00 | 1480100.38 | 0.00 | 763988.14 | 0.270422E+09 | 0.00 | 0.53 |
Maximum of Months | 0.730220E+09 | 0.861806E+09 | 625555.95 | 19958564.52 | 47831037.63 | 0.520008E+10 | 0.179923E+10 | 25135.35 | 0.54 |
Report: MechanicalVentilationLoadsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.569242E+11 | 0.00 | 0.00 | 794170.82 | 0.00 | 0.668420E+11 | 0.702644E+10 | 0.00 | 8.02 |
February | 0.560674E+11 | 0.00 | 0.00 | 1637811.53 | 0.00 | 0.257528E+11 | 0.111561E+11 | 0.00 | 8.07 |
March | 0.516025E+11 | 0.00 | 0.00 | 4290195.87 | 0.00 | 0.747315E+10 | 0.219924E+11 | 0.00 | 8.10 |
April | 0.316683E+11 | 0.00 | 0.00 | 8806072.51 | 44297681.40 | 0.00 | 0.282842E+11 | 0.00 | 8.14 |
May | 0.165698E+11 | 0.252547E+09 | 0.00 | 17186772.43 | 0.600271E+09 | 0.00 | 0.306832E+11 | 0.00 | 8.18 |
June | 0.661326E+10 | 0.567879E+10 | 0.00 | 14965700.37 | 0.525736E+10 | 0.00 | 0.214229E+11 | 0.00 | 8.22 |
July | 0.367028E+10 | 0.101672E+11 | 0.00 | 13518804.55 | 0.779536E+10 | 0.00 | 0.167078E+11 | 0.00 | 8.23 |
August | 0.587173E+10 | 0.365135E+10 | 0.00 | 15595923.72 | 0.478948E+10 | 0.00 | 0.215090E+11 | 0.00 | 8.20 |
September | 0.204007E+11 | 0.197770E+09 | 0.00 | 13698673.75 | 0.386221E+09 | 0.00 | 0.301756E+11 | 0.00 | 8.20 |
October | 0.333110E+11 | 0.00 | 0.00 | 9232817.65 | 0.00 | 0.00 | 0.285541E+11 | 0.00 | 8.13 |
November | 0.439717E+11 | 0.00 | 0.00 | 5272208.40 | 0.00 | 0.00 | 0.234789E+11 | 0.00 | 8.16 |
December | 0.567813E+11 | 0.00 | 0.00 | 1031018.36 | 0.00 | 0.559310E+11 | 0.823722E+10 | 0.00 | 8.01 |
Annual Sum or Average | 0.383452E+12 | 0.199476E+11 | 0.00 | 0.106030E+09 | 0.188730E+11 | 0.155999E+12 | 0.249228E+12 | 0.00 | 8.14 |
Minimum of Months | 0.367028E+10 | 0.00 | 0.00 | 794170.82 | 0.00 | 0.00 | 0.702644E+10 | 0.00 | 8.01 |
Maximum of Months | 0.569242E+11 | 0.101672E+11 | 0.00 | 17186772.43 | 0.779536E+10 | 0.668420E+11 | 0.306832E+11 | 0.00 | 8.23 |
Report: MechanicalVentilationLoadsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.587312E+11 | 0.00 | 0.00 | 1284868.92 | 0.00 | 0.693837E+11 | 0.928240E+10 | 0.00 | 8.42 |
February | 0.569343E+11 | 0.00 | 0.00 | 2405265.07 | 0.00 | 0.268718E+11 | 0.138649E+11 | 0.00 | 8.48 |
March | 0.494335E+11 | 0.00 | 0.00 | 6126845.83 | 0.00 | 0.785408E+10 | 0.278729E+11 | 0.00 | 8.51 |
April | 0.290861E+11 | 0.00 | 0.00 | 11904390.95 | 46534736.25 | 0.00 | 0.338912E+11 | 0.00 | 8.55 |
May | 0.148214E+11 | 0.309058E+09 | 0.00 | 22009601.86 | 0.586828E+09 | 0.00 | 0.348140E+11 | 0.00 | 8.60 |
June | 0.593405E+10 | 0.743086E+10 | 0.00 | 18788553.21 | 0.405756E+10 | 0.00 | 0.235149E+11 | 0.00 | 8.63 |
July | 0.318180E+10 | 0.127705E+11 | 0.00 | 16791469.54 | 0.609914E+10 | 0.00 | 0.182228E+11 | 0.00 | 8.65 |
August | 0.512167E+10 | 0.449447E+10 | 0.00 | 19560189.71 | 0.437262E+10 | 0.00 | 0.236386E+11 | 0.00 | 8.62 |
September | 0.179373E+11 | 0.227590E+09 | 0.00 | 17795925.73 | 0.385894E+09 | 0.00 | 0.351898E+11 | 0.00 | 8.61 |
October | 0.309471E+11 | 0.00 | 0.00 | 12298259.97 | 0.00 | 0.00 | 0.340397E+11 | 0.00 | 8.54 |
November | 0.433820E+11 | 0.00 | 0.00 | 7312037.97 | 0.00 | 0.00 | 0.274731E+11 | 0.00 | 8.57 |
December | 0.563672E+11 | 0.00 | 0.00 | 1678384.25 | 0.00 | 0.580587E+11 | 0.126311E+11 | 0.00 | 8.41 |
Annual Sum or Average | 0.371878E+12 | 0.252325E+11 | 0.00 | 0.137956E+09 | 0.155486E+11 | 0.162168E+12 | 0.294435E+12 | 0.00 | 8.55 |
Minimum of Months | 0.318180E+10 | 0.00 | 0.00 | 1284868.92 | 0.00 | 0.00 | 0.928240E+10 | 0.00 | 8.41 |
Maximum of Months | 0.587312E+11 | 0.127705E+11 | 0.00 | 22009601.86 | 0.609914E+10 | 0.693837E+11 | 0.351898E+11 | 0.00 | 8.65 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.336868E+10 | 0.00 | 0.00 | 54078108.47 | 0.00 | 0.639402E+11 | 0.724936E+11 | 0.00 | 27.53 |
February | 0.218091E+10 | 0.00 | 0.00 | 66769686.63 | 0.00 | 0.242237E+11 | 0.729561E+11 | 0.00 | 27.79 |
March | 0.519664E+09 | 0.00 | 0.00 | 92303746.52 | 0.00 | 0.791609E+10 | 0.781893E+11 | 0.00 | 27.95 |
April | 0.00 | 47505937.87 | 0.00 | 0.101474E+09 | 0.00 | 0.00 | 0.640779E+11 | 0.00 | 28.11 |
May | 0.00 | 0.915745E+09 | 0.00 | 0.105158E+09 | 0.00 | 0.00 | 0.504986E+11 | 0.00 | 28.26 |
June | 0.00 | 0.117316E+11 | 0.00 | 75462341.53 | 0.00 | 0.00 | 0.299507E+11 | 0.00 | 28.39 |
July | 0.00 | 0.192680E+11 | 0.00 | 56095995.52 | 0.00 | 0.00 | 0.217657E+11 | 0.00 | 28.46 |
August | 0.00 | 0.905641E+10 | 0.00 | 71727961.47 | 0.00 | 0.00 | 0.292445E+11 | 0.00 | 28.34 |
September | 0.00 | 0.626615E+09 | 0.00 | 0.103312E+09 | 0.00 | 0.00 | 0.540494E+11 | 0.00 | 28.30 |
October | 0.00 | 0.00 | 0.00 | 99175332.14 | 0.00 | 0.00 | 0.661110E+11 | 0.00 | 28.06 |
November | 33031240.26 | 0.00 | 0.00 | 88706440.49 | 0.00 | 0.00 | 0.720246E+11 | 0.00 | 28.13 |
December | 0.328356E+10 | 0.00 | 0.00 | 57929694.81 | 0.00 | 0.513794E+11 | 0.746110E+11 | 0.00 | 27.51 |
Annual Sum or Average | 0.938584E+10 | 0.416459E+11 | 0.00 | 0.972194E+09 | 0.00 | 0.147459E+12 | 0.685973E+12 | 0.00 | 28.07 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 54078108.47 | 0.00 | 0.00 | 0.217657E+11 | 0.00 | 27.51 |
Maximum of Months | 0.336868E+10 | 0.192680E+11 | 0.00 | 0.105158E+09 | 0.00 | 0.639402E+11 | 0.781893E+11 | 0.00 | 28.46 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.213937E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.423194E+11 | 0.00 | 0.00 | 2.09 |
February | 0.413063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.261053E+11 | 0.00 | 0.00 | 2.11 |
March | 0.961768E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.167466E+11 | 0.00 | 0.00 | 2.12 |
April | 0.171480E+11 | 0.00 | 0.00 | 0.00 | 14405379.93 | 0.235109E+10 | 0.00 | 0.00 | 2.12 |
May | 0.153720E+11 | 0.00 | 0.00 | 0.00 | 0.277332E+09 | 0.00 | 0.00 | 0.00 | 2.13 |
June | 0.912209E+10 | 0.00 | 0.00 | 0.00 | 0.355638E+10 | 0.00 | 0.00 | 0.00 | 2.14 |
July | 0.663123E+10 | 0.00 | 0.00 | 0.00 | 0.584133E+10 | 0.00 | 0.00 | 0.00 | 2.15 |
August | 0.890914E+10 | 0.00 | 0.00 | 0.00 | 0.274492E+10 | 0.00 | 0.00 | 0.00 | 2.14 |
September | 0.164516E+11 | 0.00 | 0.00 | 0.00 | 0.189911E+09 | 0.00 | 0.00 | 0.00 | 2.14 |
October | 0.185140E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160723E+10 | 0.00 | 0.00 | 2.12 |
November | 0.994104E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119953E+11 | 0.00 | 0.00 | 2.13 |
December | 0.135059E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.391975E+11 | 0.00 | 0.00 | 2.09 |
Annual Sum or Average | 0.116186E+12 | 0.00 | 0.00 | 0.00 | 0.126243E+11 | 0.140322E+12 | 0.00 | 0.00 | 2.12 |
Minimum of Months | 0.135059E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.09 |
Maximum of Months | 0.185140E+11 | 0.00 | 0.00 | 0.00 | 0.584133E+10 | 0.423194E+11 | 0.00 | 0.00 | 2.15 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:58:23
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.138226E+12 | 0.302359E+11 | 0.195475E+12 | 0.272631E+13 | 0.278002E+12 |
February | 0.228675E+12 | 0.246130E+11 | 0.162571E+12 | 0.227460E+13 | 0.188972E+12 |
March | 0.328186E+12 | 0.232335E+11 | 0.160118E+12 | 0.219925E+13 | 0.160393E+12 |
April | 0.442759E+12 | 0.145233E+11 | 0.106412E+12 | 0.141750E+13 | 0.198553E+12 |
May | 0.497044E+12 | 0.738971E+10 | 0.596542E+11 | 0.720445E+12 | 0.523602E+12 |
June | 0.518949E+12 | 0.141058E+10 | 0.194981E+11 | 0.132560E+12 | 0.974599E+12 |
July | 0.528396E+12 | -0.129735E+10 | 0.198531E+10 | -0.118555E+12 | 0.126899E+13 |
August | 0.437403E+12 | 0.145036E+10 | 0.222102E+11 | 0.157219E+12 | 0.975376E+12 |
September | 0.328964E+12 | 0.766263E+10 | 0.639301E+11 | 0.753858E+12 | 0.388008E+12 |
October | 0.175161E+12 | 0.137015E+11 | 0.104812E+12 | 0.134955E+13 | 0.165532E+12 |
November | 0.897958E+11 | 0.191004E+11 | 0.138130E+12 | 0.184850E+13 | 0.124374E+12 |
December | 0.958510E+11 | 0.289765E+11 | 0.190532E+12 | 0.263208E+13 | 0.253199E+12 |
Annual Sum or Average | 0.380941E+13 | 0.171000E+12 | 0.122533E+13 | 0.160933E+14 | 0.549960E+13 |
Minimum of Months | 0.897958E+11 | -0.129735E+10 | 0.198531E+10 | -0.118555E+12 | 0.124374E+12 |
Maximum of Months | 0.528396E+12 | 0.302359E+11 | 0.195475E+12 | 0.272631E+13 | 0.126899E+13 |