Table of Contents

Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:58

Tabular Output Report in Format: HTML

Building: HotelLarge

Environment: RUNPERIOD 1 ** El Paso International Ap Ut TX USA TMY3 WMO#=722700

Simulation Timestamp: 2023-10-16 08:58:10


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2023-10-16 08:58:10

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [GJ] Energy Per Total Building Area [MJ/m2] Energy Per Conditioned Building Area [MJ/m2]
Total Site Energy 15119.46 1332.66 1332.66
Net Site Energy 15119.46 1332.66 1332.66
Total Source Energy 35528.68 3131.58 3131.58
Net Source Energy 35528.68 3131.58 3131.58


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 1.200
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil No 1 1.050
Fuel Oil No 2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [m2]
Total Building Area 11345.29
Net Conditioned Building Area 11345.29
Unconditioned Building Area 0.00


End Uses

Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating 0.00 1215.20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 2289.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 1174.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 262.44 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 1751.30 1788.84 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 679.68 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 2048.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 253.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 563.76 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 90.78 2927.15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 9857.19
Refrigeration 74.19 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 9188.28 5931.18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 9857.19
Note: Natural gas appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler 0.00 1215.20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 2289.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 1174.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 262.44 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 959.56 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Cooking 762.04 1198.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ReachInFreezer 16.27 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ReachInRefrigerator 13.43 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Laundry 0.00 590.20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Transformer 32.92 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLift 616.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLightsFan 30.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  General 2048.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 253.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 563.76 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Water Heater 90.78 2927.15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 5742.51
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 4114.69
Refrigeration General 18.27 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  LowTempRefrigeration 22.42 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  MedTempRefrigeration 33.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Space Type

Space Type Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating Unassigned 0.00 1215.20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling Unassigned 2289.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting GENERAL 1174.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Unassigned 262.44 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment GENERAL 1751.30 1788.84 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Unassigned 679.68 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Unassigned 2048.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps Unassigned 253.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery Unassigned 563.76 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Unassigned 90.78 2927.15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 9857.19
Refrigeration Unassigned 74.19 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 126.62 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 412.75 365.12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.87
Other 270.50 157.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 809.88 522.79 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.87


Utility Use Per Total Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 126.62 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 412.75 365.12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.87
Other 270.50 157.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 809.88 522.79 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.87


Electric Loads Satisfied

Electricity [GJ] Percent Electricity [%]
Fuel-Fired Power Generation 0.000 0.00
High Temperature Geothermal* 0.000 0.00
Photovoltaic Power 0.000 0.00
Wind Power 0.000 0.00
Power Conversion 0.000 0.00
Net Decrease in On-Site Storage 0.000 0.00
Total On-Site Electric Sources 0.000 0.00
     
Electricity Coming From Utility 9188.278 100.00
Surplus Electricity Going To Utility 0.000 0.00
Net Electricity From Utility 9188.278 100.00
     
Total On-Site and Utility Electric Sources 9188.278 100.00
Total Electricity End Uses 9188.278 100.00


On-Site Thermal Sources

Heat [GJ] Percent Heat [%]
Water-Side Heat Recovery 0.00 0.00
Air to Air Heat Recovery for Cooling 1289.08 39.64
Air to Air Heat Recovery for Heating 1962.95 60.36
High-Temperature Geothermal* 0.00 0.00
Solar Water Thermal 0.00 0.00
Solar Air Thermal 0.00 0.00
Total On-Site Thermal Sources 3252.03 100.00


Water Source Summary

Water [m3] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 9857.19 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 9857.19 100.00
Total Water End Uses 9857.19 100.00


Setpoint Not Met Criteria

Degrees [deltaC]
Tolerance for Zone Heating Setpoint Not Met Time 0.56
Tolerance for Zone Cooling Setpoint Not Met Time 0.56


Comfort and Setpoint Not Met Summary

Facility [Hours]
Time Setpoint Not Met During Occupied Heating 0.00
Time Setpoint Not Met During Occupied Cooling 13.67
Time Not Comfortable Based on Simple ASHRAE 55-2004 7386.50


Note 1: An asterisk (*) indicates that the feature is not yet implemented.

Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Adaptive Comfort Summary
Initialization Summary
Annual Heat Emissions Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
Coil Sizing Details
System Summary
Outdoor Air Summary
Outdoor Air Details
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary
Annual Thermal Resilience Summary
Annual CO2 Resilience Summary
Annual Visual Resilience Summary

NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODENAME IECC

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2012

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

| Environment |

NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE

| Environment |

NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3B

| Environment |

NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_TX_ELPASO

| Environment |

ZoneCoolingSummaryMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

ZoneHeatingSummaryMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

ZoneElectricSummaryMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

SpaceGainsMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

PeakSpaceGainsMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

SpaceGainComponentsAtCoolingPeakMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

EnergyConsumptionElectricityNaturalGasMonthly

| Meter |

EndUseEnergyConsumptionElectricityMonthly

| Meter |

EndUseEnergyConsumptionNaturalGasMonthly

| Meter |

PeakEnergyEndUseElectricityPart1Monthly

| Meter |

PeakEnergyEndUseElectricityPart2Monthly

| Meter |

ElectricComponentsOfPeakDemandMonthly

| Meter |

PeakEnergyEndUseNaturalGasMonthly

| Meter |

SetpointsNotMetWithTemperaturesMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

ComfortReportSimple55Monthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

OccupantComfortDataSummaryMonthly

| BASEMENT PEOPLE | RETAIL_1_FLR_1 PEOPLE | RETAIL_2_FLR_1 PEOPLE | LAUNDRY_FLR_1 PEOPLE | CAFE_FLR_1 PEOPLE | LOBBY_FLR_1 PEOPLE | ROOM_1_FLR_3 PEOPLE | ROOM_2_FLR_3 PEOPLE | ROOM_3_MULT19_FLR_3 PEOPLE | ROOM_4_MULT19_FLR_3 PEOPLE | ROOM_5_FLR_3 PEOPLE | ROOM_6_FLR_3 PEOPLE | ROOM_1_FLR_6 PEOPLE | ROOM_2_FLR_6 PEOPLE | ROOM_3_MULT9_FLR_6 PEOPLE | BANQUET_FLR_6 PEOPLE | DINING_FLR_6 PEOPLE | KITCHEN_FLR_6 PEOPLE | STORAGE_FLR_1 PEOPLE | CORRIDOR_FLR_3 PEOPLE | CORRIDOR_FLR_6 PEOPLE | MECH_FLR_1 PEOPLE |

ChillerReportMonthly

| COOLSYS1 CHILLER1 |

BoilerReportMonthly

| HEATSYS1 BOILER |

DXReportMonthly

| VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |

WindowReportMonthly

| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |

WindowEnergyReportMonthly

| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |

WindowZoneSummaryMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

WindowEnergyZoneSummaryMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

AverageOutdoorConditionsMonthly

| Environment |

OutdoorConditionsMaximumDryBulbMonthly

| Environment |

OutdoorConditionsMinimumDryBulbMonthly

| Environment |

OutdoorConditionsMaximumWetBulbMonthly

| Environment |

OutdoorConditionsMaximumDewPointMonthly

| Environment |

OutdoorGroundConditionsMonthly

| Environment |

WaterHeaterReportMonthly

| SWH BOOSTER E WATER HEATER | SWH LAUNDRY G WATER HEATER | SWHSYS1 WATER HEATER |

DaylightingReportMonthly

| Environment |

CoilReportMonthly

| VAV WITH REHEAT HEATING COIL | BASEMENT VAV BOX REHEAT COIL | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | MECH_FLR_1 VAV BOX REHEAT COIL | STORAGE_FLR_1 VAV BOX REHEAT COIL | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | CAFE_FLR_1 VAV BOX REHEAT COIL | LOBBY_FLR_1 VAV BOX REHEAT COIL | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | BANQUET_FLR_6 VAV BOX REHEAT COIL | DINING_FLR_6 VAV BOX REHEAT COIL | KITCHEN_FLR_6 VAV BOX REHEAT COIL | FLR_3_DOAS HEATING COIL | ROOM_1_FLR_3 FAN COIL HEATING COIL | ROOM_2_FLR_3 FAN COIL HEATING COIL | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_5_FLR_3 FAN COIL HEATING COIL | ROOM_6_FLR_3 FAN COIL HEATING COIL | ROOM_1_FLR_6 FAN COIL HEATING COIL | ROOM_2_FLR_6 FAN COIL HEATING COIL | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |

PlantLoopDemandReportMonthly

| HEATSYS1 | COOLSYS1 | SWHSYS1 |

FanReportMonthly

| FLR_3_DOAS FAN | VAV WITH REHEAT FAN | LAUNDRY_FLR_1 EXHAUST FAN | LOBBY_FLR_1 EXHAUST FAN | BANQUET_FLR_6 EXHAUST FAN | DINING_FLR_6 EXHAUST FAN | KITCHEN_FLR_6 EXHAUST FAN | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN |

PumpReportMonthly

| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 PUMP | SWHSYS1 PUMP |

CondLoopDemandReportMonthly

| HEATSYS1 | COOLSYS1 | SWHSYS1 |

ZoneTemperatureOscillationReportMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

AirLoopSystemEnergyAndWaterUseMonthly

| VAV WITH REHEAT | FLR_3_DOAS |

AirLoopSystemComponentLoadsMonthly

| VAV WITH REHEAT | FLR_3_DOAS |

AirLoopSystemComponentEnergyUseMonthly

| VAV WITH REHEAT | FLR_3_DOAS |

MechanicalVentilationLoadsMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

HeatEmissionsReportMonthly

| Environment |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2023-10-16 08:58:10

General

Value
Program Version and Build EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:58
RunPeriod RUNPERIOD 1
Weather File El Paso International Ap Ut TX USA TMY3 WMO#=722700
Latitude [deg] 31.77
Longitude [deg] -106.5
Elevation [m] 1186.00
Time Zone -7.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 4559.59 1873.43 406.47 1873.22 406.47
Above Ground Wall Area [m2] 4025.82 1662.30 350.71 1662.10 350.71
Window Opening Area [m2] 1213.79 432.95 85.85 609.15 85.85
Gross Window-Wall Ratio [%] 26.62 23.11 21.12 32.52 21.12
Above Ground Window-Wall Ratio [%] 30.15 26.05 24.48 36.65 24.48


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 4559.59 1873.43 406.47 1873.22 406.47
Above Ground Wall Area [m2] 4025.82 1662.30 350.71 1662.10 350.71
Window Opening Area [m2] 1213.79 432.95 85.85 609.15 85.85
Gross Window-Wall Ratio [%] 26.62 23.11 21.12 32.52 21.12
Above Ground Window-Wall Ratio [%] 30.15 26.05 24.48 36.65 24.48


Skylight-Roof Ratio

Total
Gross Roof Area [m2] 1978.84
Skylight Area [m2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [m3] Multipliers Above Ground Gross Wall Area [m2] Underground Gross Wall Area [m2] Window Glass Area [m2] Opening Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
BASEMENT 1978.83 Yes Yes 4826.41 1.00 0.00 533.77 0.00 0.00 8.7495 18.58 5.3800
RETAIL_1_FLR_1 67.07 Yes Yes 265.76 1.00 68.84 0.00 23.26 23.26 13.0124 6.19 10.7600
RETAIL_2_FLR_1 77.67 Yes Yes 307.76 1.00 26.57 0.00 0.00 0.00 13.0124 6.19 10.7600
MECH_FLR_1 164.24 Yes Yes 650.80 1.00 62.80 0.00 0.00 0.00 10.0642 61.93 5.3800
STORAGE_FLR_1 94.76 Yes Yes 375.47 1.00 36.23 0.00 0.00 0.00 7.3195 46.45 2.6900
LAUNDRY_FLR_1 78.04 Yes Yes 309.22 1.00 85.75 0.00 0.00 0.00 5.4896 9.29 597.5300
CAFE_FLR_1 188.86 Yes Yes 748.35 1.00 152.17 0.00 65.50 65.50 12.8090 1.33 5.3800
LOBBY_FLR_1 1308.19 Yes Yes 5183.56 1.00 434.79 0.00 85.08 85.08 10.0642 3.10 8.0700
ROOM_1_FLR_3 39.02 Yes Yes 118.94 4.00 39.95 0.00 13.18 13.18 10.0642 26.01 6.7500
ROOM_2_FLR_3 39.02 Yes Yes 118.93 4.00 39.95 0.00 13.18 13.18 10.0642 26.01 6.7500
ROOM_3_MULT19_FLR_3 24.52 Yes Yes 74.75 76.00 11.15 0.00 3.68 3.68 10.0642 16.35 10.5200
ROOM_4_MULT19_FLR_3 24.53 Yes Yes 74.77 76.00 11.15 0.00 3.68 3.68 10.0642 16.35 10.5200
ROOM_5_FLR_3 39.02 Yes Yes 118.94 4.00 39.95 0.00 13.18 13.18 10.0642 26.01 6.7500
ROOM_6_FLR_3 39.02 Yes Yes 118.93 4.00 39.95 0.00 13.18 13.18 10.0642 26.01 6.7500
CORRIDOR_FLR_3 389.40 Yes Yes 1186.91 4.00 48.31 0.00 15.94 15.94 3.6597 18.58 0.0000
ROOM_1_FLR_6 39.02 Yes Yes 118.94 1.00 39.95 0.00 13.18 13.18 10.0642 26.01 6.7500
ROOM_2_FLR_6 39.02 Yes Yes 118.93 1.00 39.95 0.00 13.18 13.18 10.0642 26.01 6.7500
ROOM_3_MULT9_FLR_6 24.53 Yes Yes 74.77 9.00 20.44 0.00 6.74 6.74 10.0642 16.35 10.5200
BANQUET_FLR_6 331.66 Yes Yes 1010.89 1.00 97.55 0.00 32.19 32.19 12.8090 1.33 67.8200
DINING_FLR_6 331.66 Yes Yes 1010.89 1.00 97.55 0.00 32.19 32.19 12.8090 1.33 67.8200
KITCHEN_FLR_6 103.30 Yes Yes 314.87 1.00 87.33 0.00 26.37 26.37 10.9792 4.65 2936.4163
CORRIDOR_FLR_6 412.12 Yes Yes 1256.16 1.00 85.47 0.00 28.20 28.20 3.6597 18.58 0.0000
Total 11345.29     35184.81   4025.82 533.77 1213.79 1213.79 8.9207 7.07 41.0885
Conditioned Total 11345.29     35184.81   4025.82 533.77 1213.79 1213.79 8.9207 7.07 41.0885
Unconditioned Total 0.00     0.00   0.00 0.00 0.00 0.00      
Not Part of Total 0.00     0.00   0.00 0.00 0.00 0.00      


Space Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Multipliers Zone Name Space Type Radiant/Solar Enclosure Name Lighting [W/m2] People [m2 per person] Plug and Process [W/m2] Tags
BASEMENT 1978.83 Yes Yes 1.00 BASEMENT GENERAL BASEMENT 8.7495 18.58 5.3800  
RETAIL_1_FLR_1 67.07 Yes Yes 1.00 RETAIL_1_FLR_1 GENERAL RETAIL_1_FLR_1 13.0124 6.19 10.7600  
RETAIL_2_FLR_1 77.67 Yes Yes 1.00 RETAIL_2_FLR_1 GENERAL RETAIL_2_FLR_1 13.0124 6.19 10.7600  
MECH_FLR_1 164.24 Yes Yes 1.00 MECH_FLR_1 GENERAL MECH_FLR_1 10.0642 61.93 5.3800  
STORAGE_FLR_1 94.76 Yes Yes 1.00 STORAGE_FLR_1 GENERAL STORAGE_FLR_1 7.3195 46.45 2.6900  
LAUNDRY_FLR_1 78.04 Yes Yes 1.00 LAUNDRY_FLR_1 GENERAL LAUNDRY_FLR_1 5.4896 9.29 597.5300  
CAFE_FLR_1 188.86 Yes Yes 1.00 CAFE_FLR_1 GENERAL CAFE_FLR_1 12.8090 1.33 5.3800  
LOBBY_FLR_1 1308.19 Yes Yes 1.00 LOBBY_FLR_1 GENERAL LOBBY_FLR_1 10.0642 3.10 8.0700  
ROOM_1_FLR_3 39.02 Yes Yes 4.00 ROOM_1_FLR_3 GENERAL ROOM_1_FLR_3 10.0642 26.01 6.7500  
ROOM_2_FLR_3 39.02 Yes Yes 4.00 ROOM_2_FLR_3 GENERAL ROOM_2_FLR_3 10.0642 26.01 6.7500  
ROOM_3_MULT19_FLR_3 24.52 Yes Yes 76.00 ROOM_3_MULT19_FLR_3 GENERAL ROOM_3_MULT19_FLR_3 10.0642 16.35 10.5200  
ROOM_4_MULT19_FLR_3 24.53 Yes Yes 76.00 ROOM_4_MULT19_FLR_3 GENERAL ROOM_4_MULT19_FLR_3 10.0642 16.35 10.5200  
ROOM_5_FLR_3 39.02 Yes Yes 4.00 ROOM_5_FLR_3 GENERAL ROOM_5_FLR_3 10.0642 26.01 6.7500  
ROOM_6_FLR_3 39.02 Yes Yes 4.00 ROOM_6_FLR_3 GENERAL ROOM_6_FLR_3 10.0642 26.01 6.7500  
CORRIDOR_FLR_3 389.40 Yes Yes 4.00 CORRIDOR_FLR_3 GENERAL CORRIDOR_FLR_3 3.6597 18.58 0.0000  
ROOM_1_FLR_6 39.02 Yes Yes 1.00 ROOM_1_FLR_6 GENERAL ROOM_1_FLR_6 10.0642 26.01 6.7500  
ROOM_2_FLR_6 39.02 Yes Yes 1.00 ROOM_2_FLR_6 GENERAL ROOM_2_FLR_6 10.0642 26.01 6.7500  
ROOM_3_MULT9_FLR_6 24.53 Yes Yes 9.00 ROOM_3_MULT9_FLR_6 GENERAL ROOM_3_MULT9_FLR_6 10.0642 16.35 10.5200  
BANQUET_FLR_6 331.66 Yes Yes 1.00 BANQUET_FLR_6 GENERAL BANQUET_FLR_6 12.8090 1.33 67.8200  
DINING_FLR_6 331.66 Yes Yes 1.00 DINING_FLR_6 GENERAL DINING_FLR_6 12.8090 1.33 67.8200  
KITCHEN_FLR_6 103.30 Yes Yes 1.00 KITCHEN_FLR_6 GENERAL KITCHEN_FLR_6 10.9792 4.65 2936.4163  
CORRIDOR_FLR_6 412.12 Yes Yes 1.00 CORRIDOR_FLR_6 GENERAL CORRIDOR_FLR_6 3.6597 18.58 0.0000  
Total 11345.29             8.9207 3.54 41.0885  
Conditioned Total 11345.29             8.9207 3.54 41.0885  
Unconditioned Total 0.00             0.0000 0.00 0.0000  
Not Part of Total 0.00             0.0000 0.00 0.0000  


Space Type Summary

Total Area [m2] Conditioned Area [m2] Unconditioned Area [m2] Not Part of Total Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
GENERAL 11345.29 11345.29 0.00 0.00 4.6908 8.82 37.2165
Total 11345.29 11345.29 0.00 0.00      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2023-10-16 08:58:10

End Uses

Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Time of Peak 05-JUN-19:10 26-DEC-17:19 - - - - - - - - - - 02-JAN-21:10
Heating 0.00 133567.95 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 224284.18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 93091.76 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 16690.39 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 88971.67 89612.21 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 33012.66 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 78213.03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 11289.13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 18015.63 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 3773.80 244320.47 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 2894.03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 570236.28 467500.63 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Subcategory

Subcategory Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Heating General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler 0.00 133567.95 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 224284.18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 93091.76 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 16690.39 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 58789.28 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Cooking 29240.64 74976.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ReachInFreezer 515.92 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ReachInRefrigerator 425.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Laundry 0.00 14636.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Transformer 1887.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLift 30153.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLightsFan 972.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  General 78213.03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 11289.13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 18015.63 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Water Heater 3773.80 244320.47 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 666.93 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  LowTempRefrigeration 1153.12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  MedTempRefrigeration 1073.99 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2023-10-16 08:58:10

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [GJ] Source Natural Gas [GJ] Source Gasoline [GJ] Source Diesel [GJ] Source Coal [GJ] Source Fuel Oil No 1 [GJ] Source Fuel Oil No 2 [GJ] Source Propane [GJ] Source Other Fuel 1 [GJ] Source Other Fuel 2 [GJ] Source District Cooling [GJ] Source District Heating [GJ]
Heating 0.00 1317.27 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 7250.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 3718.41 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 831.16 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 5546.36 1939.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 2152.55 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 6488.70 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 803.37 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 1785.43 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 287.49 3173.03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 234.96 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 29099.28 6429.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 116.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 639.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 327.75 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 73.26 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 488.87 170.92 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 189.73 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 571.93 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 70.81 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 157.37 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 25.34 279.68 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 20.71 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 2564.88 566.70 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 116.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 639.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 327.75 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 73.26 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 488.87 170.92 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 189.73 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 571.93 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 70.81 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 157.37 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 25.34 279.68 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 20.71 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 2564.88 566.70 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2023-10-16 08:58:10

AirTerminal:SingleDuct:VAV:Reheat

Design Size Maximum Air Flow Rate [m3/s] Design Size Constant Minimum Air Flow Fraction User-Specified Constant Minimum Air Flow Fraction Design Size Minimum Air Flow Rate [m3/s] Design Size Maximum Flow Fraction during Reheat [] User-Specified Maximum Flow Fraction during Reheat [] Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] Design Size Maximum Reheat Water Flow Rate [m3/s] Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] Design Size Reheat Coil Sizing Inlet Air Temperature [C] Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir]
BASEMENT VAV BOX COMPONENT 2.86 0.527619 0.995000 2.84 1.00 0.500000 0.000722 0.000114 2.84 16.70 0.008000
RETAIL_1_FLR_1 VAV BOX COMPONENT 0.389359 0.131263 0.995000 0.387412 0.995000 0.500000 0.002903 0.000042 0.387412 16.70 0.008000
RETAIL_2_FLR_1 VAV BOX COMPONENT 0.284214 0.208237 0.995000 0.282793 0.995000 0.500000 0.001830 0.000020 0.282793 16.70 0.008000
MECH_FLR_1 VAV BOX COMPONENT 0.304343 0.411224 0.995000 0.302822 1.00 0.500000 0.000927 0.000028 0.302822 16.70 0.008000
STORAGE_FLR_1 VAV BOX COMPONENT 0.153705 0.469774 0.995000 0.152937 1.00 0.500000 0.000811 0.000016 0.152937 16.70 0.008000
LAUNDRY_FLR_1 VAV BOX COMPONENT 3.79 0.062268 0.995000 3.77 0.995000 0.500000 0.024280 0.000172 3.77 16.70 0.008000
CAFE_FLR_1 VAV BOX COMPONENT 1.66 0.086900 0.995000 1.65 0.995000 0.500000 0.004384 0.000132 1.65 16.70 0.008000
LOBBY_FLR_1 VAV BOX COMPONENT 5.47 0.182216 0.995000 5.44 0.995000 0.500000 0.002091 0.000370 5.44 16.70 0.008000
CORRIDOR_FLR_3 VAV BOX COMPONENT 1.36 0.871557 0.995000 1.36 1.00 0.500000 0.000437 0.000143 1.36 16.70 0.008000
BANQUET_FLR_6 VAV BOX COMPONENT 2.64 0.095713 0.995000 2.63 0.995000 0.500000 0.003981 0.000166 2.63 16.70 0.008000
DINING_FLR_6 VAV BOX COMPONENT 2.77 0.091296 0.995000 2.75 0.995000 0.500000 0.004173 0.000172 2.75 16.70 0.008000
KITCHEN_FLR_6 VAV BOX COMPONENT 2.63 0.716453 0.995000 2.62 0.995000 0.500000 0.012753 0.000122 2.62 16.70 0.008000
CORRIDOR_FLR_6 VAV BOX COMPONENT 0.844250 0.371974 0.995000 0.840029 0.995000 0.500000 0.001024 0.000098 0.840029 16.70 0.008000
User-Specified values were used. Design Size values were used if no User-Specified values were provided. Design Size values may be derived from alternate User-Specified values.

Coil:Heating:Water

Design Size Rated Capacity [W] Design Size Maximum Water Flow Rate [m3/s] Design Size U-Factor Times Area Value [W/K]
BASEMENT VAV BOX REHEAT COIL 13021.18 0.000114 271.53
RETAIL_1_FLR_1 VAV BOX REHEAT COIL 4770.42 0.000042 109.12
RETAIL_2_FLR_1 VAV BOX REHEAT COIL 2266.37 0.000020 49.18
MECH_FLR_1 VAV BOX REHEAT COIL 3192.02 0.000028 71.41
STORAGE_FLR_1 VAV BOX REHEAT COIL 1782.12 0.000016 40.43
LAUNDRY_FLR_1 VAV BOX REHEAT COIL 19667.59 0.000172 413.11
CAFE_FLR_1 VAV BOX REHEAT COIL 15073.10 0.000132 331.54
LOBBY_FLR_1 VAV BOX REHEAT COIL 42329.07 0.000370 915.98
ROOM_1_FLR_3 FAN COIL HEATING COIL 6581.78 0.000058 188.10
ROOM_2_FLR_3 FAN COIL HEATING COIL 6575.24 0.000058 187.91
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL 37721.69 0.000330 1078.03
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL 37617.71 0.000329 1075.06
ROOM_5_FLR_3 FAN COIL HEATING COIL 6569.52 0.000057 187.75
ROOM_6_FLR_3 FAN COIL HEATING COIL 6562.97 0.000057 187.56
CORRIDOR_FLR_3 VAV BOX REHEAT COIL 16345.59 0.000143 372.72
ROOM_1_FLR_6 FAN COIL HEATING COIL 2054.07 0.000018 58.70
ROOM_2_FLR_6 FAN COIL HEATING COIL 2053.25 0.000018 58.68
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL 9915.53 0.000087 283.36
BANQUET_FLR_6 VAV BOX REHEAT COIL 18979.29 0.000166 408.04
DINING_FLR_6 VAV BOX REHEAT COIL 19688.34 0.000172 422.90
KITCHEN_FLR_6 VAV BOX REHEAT COIL 13990.36 0.000122 294.27
CORRIDOR_FLR_6 VAV BOX REHEAT COIL 11230.01 0.000098 260.37
VAV WITH REHEAT HEATING COIL 172635.01 0.001510 2930.66
FLR_3_DOAS HEATING COIL 14143.00 0.000124 240.09
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:ZoneExhaust

User-Specified Maximum Flow Rate [m3/s]
LOBBY_FLR_1 EXHAUST FAN 0.000000
BANQUET_FLR_6 EXHAUST FAN 0.000000
DINING_FLR_6 EXHAUST FAN 0.000000
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirTerminal:SingleDuct:ConstantVolume:NoReheat

Design Size Maximum Air Flow Rate [m3/s]
ROOM_1_FLR_3 DIRECT AIR 0.061735
ROOM_2_FLR_3 DIRECT AIR 0.061728
ROOM_3_MULT19_FLR_3 DIRECT AIR 0.837072
ROOM_4_MULT19_FLR_3 DIRECT AIR 0.837300
ROOM_5_FLR_3 DIRECT AIR 0.061735
ROOM_6_FLR_3 DIRECT AIR 0.061728
ROOM_1_FLR_6 DIRECT AIR 0.015434
ROOM_2_FLR_6 DIRECT AIR 0.015432
ROOM_3_MULT9_FLR_6 DIRECT AIR 0.099154
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

ZoneHVAC:FourPipeFanCoil

Design Size Maximum Supply Air Flow Rate [m3/s] Design Size Maximum Hot Water Flow [m3/s] Design Size Maximum Cold Water Flow [m3/s]
ROOM_1_FLR_3 FAN COIL 1.26 0.000058 0.000476
ROOM_2_FLR_3 FAN COIL 1.25 0.000058 0.000473
ROOM_3_MULT19_FLR_3 FAN COIL 7.66 0.000330 0.002887
ROOM_4_MULT19_FLR_3 FAN COIL 8.25 0.000329 0.003227
ROOM_5_FLR_3 FAN COIL 1.10 0.000057 0.000417
ROOM_6_FLR_3 FAN COIL 1.09 0.000057 0.000414
ROOM_1_FLR_6 FAN COIL 0.340889 0.000018 0.000129
ROOM_2_FLR_6 FAN COIL 0.338090 0.000018 0.000128
ROOM_3_MULT9_FLR_6 FAN COIL 1.54 0.000087 0.000592
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:OnOff

Design Size Maximum Flow Rate [m3/s]
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN 1.26
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN 1.25
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN 7.66
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN 8.25
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN 1.10
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN 1.09
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN 0.340889
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN 0.338090
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN 1.54
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Cooling:Water

Design Size Design Inlet Air Temperature [C] Design Size Design Inlet Water Temperature [C] Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] Design Size Design Outlet Air Temperature [C] Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] Design Size Design Water Flow Rate [m3/s] Design Size Design Air Flow Rate [m3/s] Design Size Design Coil Load [W]
ROOM_1_FLR_3 FAN COIL COOLING COIL 22.70 6.70 0.008518 12.80 0.008500 0.000476 1.26  
ROOM_2_FLR_3 FAN COIL COOLING COIL 22.70 6.70 0.008518 12.80 0.008500 0.000473 1.25  
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL 22.70 6.70 0.008458 12.80 0.008458 0.002887 7.66  
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL 22.70 6.70 0.008653 12.80 0.008500 0.003227 8.25  
ROOM_5_FLR_3 FAN COIL COOLING COIL 22.70 6.70 0.008519 12.80 0.008500 0.000417 1.10  
ROOM_6_FLR_3 FAN COIL COOLING COIL 22.70 6.70 0.008519 12.80 0.008500 0.000414 1.09  
ROOM_1_FLR_6 FAN COIL COOLING COIL 22.70 6.70 0.008516 12.80 0.008500 0.000129 0.340889  
ROOM_2_FLR_6 FAN COIL COOLING COIL 22.70 6.70 0.008517 12.80 0.008500 0.000128 0.338090  
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL 22.70 6.70 0.008576 12.80 0.008500 0.000592 1.54  
VAV WITH REHEAT COOLING COIL 38.10 6.70 0.006871 10.69 0.006871 0.026050 25.04 729331.56
FLR_3_DOAS COOLING COIL 38.10 6.70 0.006871 11.79 0.006871 0.002048 2.05 57348.72
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC

Sum of Air Terminal Maximum Heating Flow Rates [m3/s] Sum of Air Terminal Minimum Heating Flow Rates [m3/s] Sum of Air Terminal Maximum Flow Rates [m3/s] Adjusted Heating Design Air Flow Rate [m3/s] Adjusted Cooling Design Air Flow Rate [m3/s] Adjusted Main Design Air Flow Rate [m3/s] User Heating Air Flow Ratio [] Calculated Heating Air Flow Ratio [] Design Supply Air Flow Rate [m3/s]
VAV WITH REHEAT 25.03 25.03 25.16 25.03 25.04 25.04 0.300000 0.999619 25.04
FLR_3_DOAS 2.05 2.05 2.05 2.05 2.05 2.05 0.300000 1.00 2.05
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:OutdoorAir

Maximum Outdoor Air Flow Rate [m3/s] Minimum Outdoor Air Flow Rate [m3/s]
VAV WITH REHEAT_OA_CONTROLLER 25.04 25.04
FLR_3_DOAS_OA_CONTROLLER 2.05 2.05
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

HeatExchanger:AirToAir:SensibleAndLatent

Design Size Nominal Supply Air Flow Rate [m3/s]
VAV WITH REHEAT OA HEAT RECOVERY 25.04
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:VariableVolume

Design Size Maximum Flow Rate [m3/s]
VAV WITH REHEAT FAN 25.04
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:WaterCoil

Maximum Actuated Flow [m3/s] Controller Convergence Tolerance
VAV WITH REHEAT_COOLC_CONTROLLER 0.026050 0.000018
VAV WITH REHEAT_HEATC_CONTROLLER 0.001510  
FLR_3_DOAS_COOLC_CONTROLLER 0.002048 0.000232
FLR_3_DOAS_HEATC_CONTROLLER 0.000124  
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:ConstantVolume

User-Specified Maximum Flow Rate [m3/s]
FLR_3_DOAS FAN 2.05
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:VariableSpeed

Design Flow Rate [m3/s] Design Power Consumption [W] Design Minimum Flow Rate [m3/s]
COOLSYS1 PUMP SECONDARY 0.036841 7591.54  
HEATSYS1 PUMP 0.004241 1277.18 0.000000
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantLoop

Maximum Loop Flow Rate [m3/s] Plant Loop Volume [m3]
HEATSYS1 0.004241 0.508913
COOLSYS1 0.036841 4.42
SWHSYS1 0.000375 0.045004
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Boiler:HotWater

Design Size Nominal Capacity [W] User-Specified Nominal Capacity [W] Design Size Design Water Flow Rate [m3/s]
HEATSYS1 BOILER 484765.23 484765.23 0.004241
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:ConstantSpeed

Design Flow Rate [m3/s] Design Power Consumption [W]
COOLSYS1 PUMP 0.036841 5255.88
SWHSYS1 PUMP 0.000375 47.91
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Chiller:Electric:EIR

Design Size Reference Chilled Water Flow Rate [m3/s] Design Size Reference Capacity [W] User-Specified Reference Capacity [W] Design Size Reference Condenser Fluid Flow Rate [m3/s]
COOLSYS1 CHILLER1 0.036841 1031447.13 1032120.29 117.66
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

WaterHeater:Mixed

Use Side Design Flow Rate [m3/s]
SWHSYS1 WATER HEATER 0.000375
User-Specified values were used. Design Size values were used if no User-Specified values were provided.


Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2023-10-16 08:58:10

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

Possible Shadow Receivers
RETAIL_1_FLR_1_CEILING ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH |
CAFE_FLR_1_CEILING ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH |
LOBBY_FLR_1_CEILING_2 ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH |


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
RETAIL_1_FLR_1_WALL_SOUTH RETAIL_1_FLR_1_WALL_SOUTH_WINDOW |
RETAIL_2_FLR_1_WALL_WEST RETAIL_2_FLR_1_WALL_WEST_DOOR |
STORAGE_FLR_1_WALL_NORTH STORAGE_FLR_1_WALL_NORTH_ROLLDOOR |
LAUNDRY_FLR_1_WALL_EAST LAUNDRY_FLR_1_WALL_EAST_DOOR |
CAFE_FLR_1_WALL_EAST CAFE_FLR_1_WALL_EAST_DOOR |
CAFE_FLR_1_WALL_SOUTH CAFE_FLR_1_WALL_SOUTH_WINDOW |
LOBBY_FLR_1_WALL_1_NORTH LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 |
LOBBY_FLR_1_WALL_1_SOUTH LOBBY_FLR_1_WALL_SOUTH_WINDOW |
ROOM_1_FLR_3_WALL_SOUTH ROOM_1_FLR_3_WALL_SOUTH_WINDOW |
ROOM_1_FLR_3_WALL_WEST ROOM_1_FLR_3_WALL_WEST_WINDOW |
ROOM_2_FLR_3_WALL_NORTH ROOM_2_FLR_3_WALL_NORTH_WINDOW |
ROOM_2_FLR_3_WALL_WEST ROOM_2_FLR_3_WALL_WEST_WINDOW |
ROOM_3_MULT19_FLR_3_WALL_SOUTH ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW |
ROOM_4_MULT19_FLR_3_WALL_NORTH ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW |
ROOM_5_FLR_3_WALL_EAST ROOM_5_FLR_3_WALL_EAST_WINDOW |
ROOM_5_FLR_3_WALL_SOUTH ROOM_5_FLR_3_WALL_SOUTH_WINDOW |
ROOM_6_FLR_3_WALL_NORTH ROOM_6_FLR_3_WALL_NORTH_WINDOW |
ROOM_6_FLR_3_WALL_EAST ROOM_6_FLR_3_WALL_EAST_WINDOW |
CORRIDOR_FLR_3_WALL_1_NORTH CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW |
CORRIDOR_FLR_3_WALL_2_NORTH CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW |
CORRIDOR_FLR_3_WALL_1_SOUTH CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW |
CORRIDOR_FLR_3_WALL_2_SOUTH CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW |
ROOM_1_FLR_6_WALL_SOUTH ROOM_1_FLR_6_WALL_SOUTH_WINDOW |
ROOM_1_FLR_6_WALL_WEST ROOM_1_FLR_6_WALL_WEST_WINDOW |
ROOM_2_FLR_6_WALL_NORTH ROOM_2_FLR_6_WALL_NORTH_WINDOW |
ROOM_2_FLR_6_WALL_WEST ROOM_2_FLR_6_WALL_WEST_WINDOW |
ROOM_3_MULT9_FLR_6_WALL_SOUTH ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW |
BANQUET_FLR_6_WALL_NORTH BANQUET_FLR_6_WALL_NORTH_WINDOW |
DINING_FLR_6_WALL_NORTH DINING_FLR_6_WALL_NORTH_WINDOW |
KITCHEN_FLR_6_WALL_NORTH KITCHEN_FLR_6_WALL_NORTH_WINDOW |
KITCHEN_FLR_6_WALL_EAST KITCHEN_FLR_6_WALL_EAST_WINDOW |
KITCHEN_FLR_6_WALL_1_SOUTH KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW |
CORRIDOR_FLR_6_WALL_1_NORTH CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW |
CORRIDOR_FLR_6_WALL_2_NORTH CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW |
CORRIDOR_FLR_6_WALL_2_SOUTH CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2023-10-16 08:58:10

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: Initialization Summary

For: Entire Facility

Timestamp: 2023-10-16 08:58:10

Version

Version ID
1 22.1


Timesteps per Hour

#TimeSteps Minutes per TimeStep {minutes}
1 6 10


System Convergence Limits

Minimum System TimeStep {minutes} Max HVAC Iterations Minimum Plant Iterations Maximum Plant Iterations
1 1 20 2 8


Simulation Control

Do Zone Sizing Do System Sizing Do Plant Sizing Do Design Days Do Weather Simulation Do HVAC Sizing Simulation
1 Yes Yes Yes No Yes No


Performance Precision Tradeoffs

Use Coil Direct Simulation Zone Radiant Exchange Algorithm Override Mode Number of Timestep In Hour Force Euler Method Minimum Number of Warmup Days Force Suppress All Begin Environment Resets Minimum System Timestep MaxZoneTempDiff MaxAllowedDelTemp
1 No ScriptF Normal 6 No 1 No 1.0 0.300 2.0000E-003


Output Reporting Tolerances

Tolerance for Time Heating Setpoint Not Met Tolerance for Zone Cooling Setpoint Not Met Time
1 0.556 0.556


Site:GroundTemperature:BuildingSurface

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00


Site:GroundTemperature:FCfactorMethod

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 18.30 11.20 6.80 8.10 10.30 12.50 19.20 23.80 27.90 27.50 26.30 23.40


Site:GroundTemperature:Shallow

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00


Site:GroundTemperature:Deep

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00


Site:GroundReflectance

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:SnowModifier

Normal Daylighting {dimensionless}
1 1.000 1.000


Site:GroundReflectance:Snow

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:Snow:Daylighting

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Environment:Weather Station

Wind Sensor Height Above Ground {m} Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Sensor Height Above Ground {m} Wind Speed Modifier Coefficient-Internal Temperature Modifier Coefficient-Internal
1 10.000 0.140 270.000 1.500 1.586 9.750E-003


Site:Location

Location Name Latitude {N+/S- Deg} Longitude {E+/W- Deg} Time Zone Number {GMT+/-} Elevation {m} Standard Pressure at Elevation {Pa} Standard RhoAir at Elevation
1 El Paso International Ap Ut TX USA TMY3 WMO#=722700 31.77 -106.50 -7.00 1186.00 87865 1.0443


Site Water Mains Temperature Information

Calculation Method{} Water Mains Temperature Schedule Name{} Annual Average Outdoor Air Temperature{C} Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} Fixed Default Water Mains Temperature{C}
1 Correlation NA 17.94 21.10 NA


Building Information

Building Name North Axis {deg} Terrain Loads Convergence Tolerance Value Temperature Convergence Tolerance Value Solar Distribution Maximum Number of Warmup Days Minimum Number of Warmup Days
1 HotelLarge 0.000 City 4.00000E-002 0.20000 FullInteriorAndExterior 25 6


Inside Convection Algorithm

Algorithm {Simple
TARP
CeilingDiffuser
AdaptiveConvectionAlgorithm}
1 TARP


Outside Convection Algorithm

Algorithm {SimpleCombined
TARP
MoWitt
DOE-2
AdaptiveConvectionAlgorithm}
1 DOE-2


Sky Radiance Distribution

Value {Anisotropic}
1 Anisotropic


Zone Air Solution Algorithm

Value {ThirdOrderBackwardDifference
AnalyticalSolution
EulerMethod}
1 ThirdOrderBackwardDifference


Zone Air Carbon Dioxide Balance Simulation

Simulation {Yes/No} Carbon Dioxide Concentration
1 No N/A


Zone Air Generic Contaminant Balance Simulation

Simulation {Yes/No} Generic Contaminant Concentration
1 No N/A


Zone Air Mass Flow Balance Simulation

Enforce Mass Balance



Adjust Zone Mixing and Return {AdjustMixingOnly
AdjustReturnOnly
AdjustMixingThenReturn
AdjustReturnThenMixing
None}
Adjust Zone Infiltration {AddInfiltration
AdjustInfiltration
None}

Infiltration Zones {MixingSourceZonesOnly
AllZones}


1 No N/A N/A N/A


HVACSystemRootFindingAlgorithm

Value {RegulaFalsi
Bisection
BisectionThenRegulaFalsi
RegulaFalsiThenBisection}
1 RegulaFalsi


Environment:Site Atmospheric Variation

Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Gradient Coefficient {K/m}
1 0.330 460.000 6.500000E-003


Surface Geometry

Starting Corner Vertex Input Direction Coordinate System Daylight Reference Point Coordinate System Rectangular (Simple) Surface Coordinate System
1 UpperLeftCorner Counterclockwise RelativeCoordinateSystem RelativeCoordinateSystem RelativeToZoneOrigin


Surface Heat Transfer Algorithm

Value {CTF - ConductionTransferFunction
EMPD - MoisturePenetrationDepthConductionTransferFunction
CondFD - ConductionFiniteDifference
HAMT - CombinedHeatAndMoistureFiniteElement} - Description
Inside Surface Max Temperature Limit{C}


Surface Convection Coefficient Lower Limit {W/m2-K}


Surface Convection Coefficient Upper Limit {W/m2-K}


1 CTF - ConductionTransferFunction 200 0.10 1000.0


Shading Summary

Number of Fixed Detached Shades Number of Building Detached Shades Number of Attached Shades
1 0 0 0


Zone Summary

Number of Zones Number of Zone Surfaces Number of SubSurfaces
1 22 235 36


Zone Information

Zone Name North Axis {deg} Origin X-Coordinate {m} Origin Y-Coordinate {m} Origin Z-Coordinate {m} Centroid X-Coordinate {m} Centroid Y-Coordinate {m} Centroid Z-Coordinate {m} Type Zone Multiplier Zone List Multiplier Minimum X {m} Maximum X {m} Minimum Y {m} Maximum Y {m} Minimum Z {m} Maximum Z {m} Ceiling Height {m} Volume {m3} Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} Floor Area {m2} Exterior Gross Wall Area {m2} Exterior Net Wall Area {m2} Exterior Window Area {m2} Number of Surfaces Number of SubSurfaces Number of Shading SubSurfaces Part of Total Building Area
1 BASEMENT 0.0 0.00 0.00 0.00 41.45 11.51 -1.22 1 1 1 0.00 86.56 0.00 22.86 -2.44 0.00 2.44 4826.41 TARP DOE-2 1978.83 0.00 0.00 0.00 13 0 0 Yes
2 RETAIL_1_FLR_1 0.0 0.00 0.00 0.00 5.79 2.90 1.98 1 1 1 0.00 11.58 0.00 5.79 0.00 3.96 3.96 265.76 TARP DOE-2 67.07 68.84 45.58 23.26 6 1 0 Yes
3 RETAIL_2_FLR_1 0.0 0.00 0.00 0.00 5.79 9.14 1.98 1 1 1 0.00 11.58 5.79 12.50 0.00 3.96 3.96 307.76 TARP DOE-2 77.67 26.57 24.62 0.00 6 1 0 Yes
4 MECH_FLR_1 0.0 0.00 0.00 0.00 61.87 17.68 1.98 1 1 1 53.95 69.80 12.50 22.86 0.00 3.96 3.96 650.80 TARP DOE-2 164.24 62.80 62.80 0.00 6 0 0 Yes
5 STORAGE_FLR_1 0.0 0.00 0.00 0.00 74.37 17.68 1.98 1 1 1 69.80 78.94 12.50 22.86 0.00 3.96 3.96 375.47 TARP DOE-2 94.76 36.23 28.80 0.00 6 1 0 Yes
6 LAUNDRY_FLR_1 0.0 0.00 0.00 0.00 84.28 14.33 1.98 1 1 1 81.99 86.56 5.79 22.86 0.00 3.96 3.96 309.22 TARP DOE-2 78.04 85.75 83.80 0.00 6 1 0 Yes
7 CAFE_FLR_1 0.0 0.00 0.00 0.00 70.26 2.90 1.98 1 1 1 53.95 86.56 0.00 5.79 0.00 3.96 3.96 748.35 TARP DOE-2 188.86 152.17 84.72 65.50 7 2 0 Yes
8 LOBBY_FLR_1 0.0 0.00 0.00 0.00 38.29 12.45 1.98 1 1 1 0.00 81.99 0.00 22.86 0.00 3.96 3.96 5183.56 TARP DOE-2 1308.19 434.79 345.80 85.08 18 3 0 Yes
9 ROOM_1_FLR_3 0.0 0.00 0.00 0.00 2.29 10.06 8.53 1 4 1 0.00 4.57 5.79 14.33 7.01 10.06 3.05 118.94 TARP DOE-2 39.02 39.95 26.77 13.18 6 2 0 Yes
10 ROOM_2_FLR_3 0.0 0.00 0.00 0.00 2.29 18.59 8.53 1 4 1 0.00 4.57 14.33 22.86 7.01 10.06 3.05 118.93 TARP DOE-2 39.02 39.95 26.76 13.18 6 2 0 Yes
11 ROOM_3_MULT19_FLR_3 0.0 0.00 0.00 0.00 8.53 9.14 8.53 1 76 1 6.71 10.36 5.79 12.50 7.01 10.06 3.05 74.75 TARP DOE-2 24.52 11.15 7.47 3.68 6 1 0 Yes
12 ROOM_4_MULT19_FLR_3 0.0 0.00 0.00 0.00 12.19 19.51 8.53 1 76 1 10.36 14.02 16.15 22.86 7.01 10.06 3.05 74.77 TARP DOE-2 24.53 11.15 7.47 3.68 6 1 0 Yes
13 ROOM_5_FLR_3 0.0 0.00 0.00 0.00 84.28 10.06 8.53 1 4 1 81.99 86.56 5.79 14.33 7.01 10.06 3.05 118.94 TARP DOE-2 39.02 39.95 26.77 13.18 6 2 0 Yes
14 ROOM_6_FLR_3 0.0 0.00 0.00 0.00 84.28 18.59 8.53 1 4 1 81.99 86.56 14.33 22.86 7.01 10.06 3.05 118.93 TARP DOE-2 39.02 39.95 26.76 13.18 6 2 0 Yes
15 CORRIDOR_FLR_3 0.0 0.00 0.00 0.00 43.28 14.33 8.53 1 4 1 4.57 81.99 5.79 22.86 7.01 10.06 3.05 1186.91 TARP DOE-2 389.40 48.31 32.37 15.94 20 4 0 Yes
16 ROOM_1_FLR_6 0.0 0.00 0.00 0.00 2.29 10.06 17.68 1 1 1 0.00 4.57 5.79 14.33 16.15 19.20 3.05 118.94 TARP DOE-2 39.02 39.95 26.77 13.18 6 2 0 Yes
17 ROOM_2_FLR_6 0.0 0.00 0.00 0.00 2.29 18.59 17.68 1 1 1 0.00 4.57 14.33 22.86 16.15 19.20 3.05 118.93 TARP DOE-2 39.02 39.95 26.76 13.18 6 2 0 Yes
18 ROOM_3_MULT9_FLR_6 0.0 0.00 0.00 0.00 7.93 7.62 17.68 1 9 1 4.57 11.28 5.79 9.45 16.15 19.20 3.05 74.77 TARP DOE-2 24.53 20.44 13.70 6.74 6 1 0 Yes
19 BANQUET_FLR_6 0.0 0.00 0.00 0.00 26.37 17.68 17.68 1 1 1 10.36 42.37 12.50 22.86 16.15 19.20 3.05 1010.89 TARP DOE-2 331.66 97.55 65.36 32.19 6 1 0 Yes
20 DINING_FLR_6 0.0 0.00 0.00 0.00 63.55 17.68 17.68 1 1 1 47.55 79.55 12.50 22.86 16.15 19.20 3.05 1010.89 TARP DOE-2 331.66 97.55 65.36 32.19 6 1 0 Yes
21 KITCHEN_FLR_6 0.0 0.00 0.00 0.00 82.99 14.11 17.68 1 1 1 79.55 86.56 5.79 22.86 16.15 19.20 3.05 314.87 TARP DOE-2 103.30 87.33 60.96 26.37 8 3 0 Yes
22 CORRIDOR_FLR_6 0.0 0.00 0.00 0.00 41.51 13.35 17.68 1 1 1 4.57 81.99 5.79 22.86 16.15 19.20 3.05 1256.16 TARP DOE-2 412.12 85.47 57.27 28.20 15 3 0 Yes


Zone Internal Gains Nominal

Zone Name Floor Area {m2} # Occupants Area per Occupant {m2/person} Occupant per Area {person/m2} Interior Lighting {W/m2} Electric Load {W/m2} Gas Load {W/m2} Other Load {W/m2} Hot Water Eq {W/m2} Steam Equipment {W/m2} Sum Loads per Area {W/m2} Outdoor Controlled Baseboard Heat
1 BASEMENT 1978.83 106.5 18.581 5.382E-002 8.749 5.380 0.000 0.000 0.000 0.000 14.129 No
2 RETAIL_1_FLR_1 67.07 10.8 6.194 0.161 13.012 10.760 0.000 0.000 0.000 0.000 23.772 No
3 RETAIL_2_FLR_1 77.67 12.5 6.194 0.161 13.012 10.760 0.000 0.000 0.000 0.000 23.772 No
4 MECH_FLR_1 164.24 2.7 61.932 1.615E-002 10.064 5.380 0.000 0.000 0.000 0.000 15.444 No
5 STORAGE_FLR_1 94.76 2.0 46.451 2.153E-002 7.319 2.690 0.000 0.000 0.000 0.000 10.009 No
6 LAUNDRY_FLR_1 78.04 8.4 9.290 0.108 5.490 61.680 535.850 0.000 0.000 0.000 603.020 No
7 CAFE_FLR_1 188.86 142.3 1.327 0.753 12.809 5.380 0.000 0.000 0.000 0.000 18.189 No
8 LOBBY_FLR_1 1308.19 422.4 3.097 0.323 10.064 8.070 0.000 0.000 0.000 0.000 18.134 No
9 ROOM_1_FLR_3 39.02 1.5 26.015 3.844E-002 10.064 6.750 0.000 0.000 0.000 0.000 16.814 No
10 ROOM_2_FLR_3 39.02 1.5 26.012 3.844E-002 10.064 6.750 0.000 0.000 0.000 0.000 16.814 No
11 ROOM_3_MULT19_FLR_3 24.52 1.5 16.349 6.116E-002 10.064 10.520 0.000 0.000 0.000 0.000 20.584 No
12 ROOM_4_MULT19_FLR_3 24.53 1.5 16.354 6.115E-002 10.064 10.520 0.000 0.000 0.000 0.000 20.584 No
13 ROOM_5_FLR_3 39.02 1.5 26.015 3.844E-002 10.064 6.750 0.000 0.000 0.000 0.000 16.814 No
14 ROOM_6_FLR_3 39.02 1.5 26.012 3.844E-002 10.064 6.750 0.000 0.000 0.000 0.000 16.814 No
15 CORRIDOR_FLR_3 389.40 21.0 18.581 5.382E-002 3.660 0.000 0.000 0.000 0.000 0.000 3.660 No
16 ROOM_1_FLR_6 39.02 1.5 26.015 3.844E-002 10.064 6.750 0.000 0.000 0.000 0.000 16.814 No
17 ROOM_2_FLR_6 39.02 1.5 26.012 3.844E-002 10.064 6.750 0.000 0.000 0.000 0.000 16.814 No
18 ROOM_3_MULT9_FLR_6 24.53 1.5 16.354 6.115E-002 10.064 10.520 0.000 0.000 0.000 0.000 20.584 No
19 BANQUET_FLR_6 331.66 249.9 1.327 0.753 12.809 67.820 0.000 0.000 0.000 0.000 80.629 No
20 DINING_FLR_6 331.66 249.9 1.327 0.753 12.809 67.820 0.000 0.000 0.000 0.000 80.629 No
21 KITCHEN_FLR_6 103.30 22.2 4.645 0.215 10.979 517.156 2419.260 0.000 0.000 0.000 2947.395 No
22 CORRIDOR_FLR_6 412.12 22.2 18.581 5.382E-002 3.660 0.000 0.000 0.000 0.000 0.000 3.660 No


People Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Number of People {} People/Floor Area {person/m2} Floor Area per person {m2/person} Fraction Radiant Fraction Convected Sensible Fraction Calculation Activity level ASHRAE 55 Warnings Carbon Dioxide Generation Rate Nominal Minimum Number of People Nominal Maximum Number of People MRT Calculation Type Work Efficiency Clothing Insulation Calculation Method Clothing Insulation Calculation Method Schedule Clothing Air Velocity Fanger Calculation Pierce Calculation KSU Calculation Cooling Effect Calculation Ankle Draft Calculation
1 BASEMENT PEOPLE BLDG_OCC_SCH BASEMENT 1978.83 106.5 106.5 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 106 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
2 RETAIL_1_FLR_1 PEOPLE BLDG_OCC_SCH RETAIL_1_FLR_1 67.07 10.8 10.8 0.161 6.194 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
3 RETAIL_2_FLR_1 PEOPLE BLDG_OCC_SCH RETAIL_2_FLR_1 77.67 12.5 12.5 0.161 6.194 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 13 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
4 LAUNDRY_FLR_1 PEOPLE BLDG_OCC_SCH LAUNDRY_FLR_1 78.04 8.4 8.4 0.108 9.290 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 8 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
5 CAFE_FLR_1 PEOPLE BLDG_OCC_SCH CAFE_FLR_1 188.86 142.3 142.3 0.753 1.327 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 142 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
6 LOBBY_FLR_1 PEOPLE BLDG_OCC_SCH LOBBY_FLR_1 1308.19 422.4 422.4 0.323 3.097 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 422 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
7 ROOM_1_FLR_3 PEOPLE GUESTROOM_OCC_SCH ROOM_1_FLR_3 39.02 1.5 1.5 3.844E-002 26.015 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
8 ROOM_2_FLR_3 PEOPLE GUESTROOM_OCC_SCH ROOM_2_FLR_3 39.02 1.5 1.5 3.844E-002 26.012 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
9 ROOM_3_MULT19_FLR_3 PEOPLE ALWAYS_OFF ROOM_3_MULT19_FLR_3 24.52 1.5 1.5 6.116E-002 16.349 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 0 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
10 ROOM_4_MULT19_FLR_3 PEOPLE GUESTROOM_OCC_SCH ROOM_4_MULT19_FLR_3 24.53 1.5 1.5 6.115E-002 16.354 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
11 ROOM_5_FLR_3 PEOPLE GUESTROOM_OCC_SCH ROOM_5_FLR_3 39.02 1.5 1.5 3.844E-002 26.015 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
12 ROOM_6_FLR_3 PEOPLE GUESTROOM_OCC_SCH ROOM_6_FLR_3 39.02 1.5 1.5 3.844E-002 26.012 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
13 ROOM_1_FLR_6 PEOPLE GUESTROOM_OCC_SCH ROOM_1_FLR_6 39.02 1.5 1.5 3.844E-002 26.015 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
14 ROOM_2_FLR_6 PEOPLE GUESTROOM_OCC_SCH ROOM_2_FLR_6 39.02 1.5 1.5 3.844E-002 26.012 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
15 ROOM_3_MULT9_FLR_6 PEOPLE GUESTROOM_OCC_SCH ROOM_3_MULT9_FLR_6 24.53 1.5 1.5 6.115E-002 16.354 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
16 BANQUET_FLR_6 PEOPLE BLDG_OCC_SCH BANQUET_FLR_6 331.66 249.9 249.9 0.753 1.327 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 250 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
17 DINING_FLR_6 PEOPLE BLDG_OCC_SCH DINING_FLR_6 331.66 249.9 249.9 0.753 1.327 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 250 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
18 KITCHEN_FLR_6 PEOPLE BLDG_OCC_SCH KITCHEN_FLR_6 103.30 22.2 22.2 0.215 4.645 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 22 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
19 STORAGE_FLR_1 PEOPLE BLDG_OCC_SCH STORAGE_FLR_1 94.76 2.0 2.0 2.153E-002 46.451 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
20 CORRIDOR_FLR_3 PEOPLE BLDG_OCC_SCH CORRIDOR_FLR_3 389.40 21.0 21.0 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 21 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
21 CORRIDOR_FLR_6 PEOPLE BLDG_OCC_SCH CORRIDOR_FLR_6 412.12 22.2 22.2 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 22 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
22 MECH_FLR_1 PEOPLE BLDG_OCC_SCH MECH_FLR_1 164.24 2.7 2.7 1.615E-002 61.932 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 3 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No


Lights Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Lighting Level {W} Lights/Floor Area {W/m2} Lights per person {W/person} Fraction Return Air Fraction Radiant Fraction Short Wave Fraction Convected Fraction Replaceable End-Use Category Nominal Minimum Lighting Level {W} Nominal Maximum Lighting Level {W}
1 BASEMENT_LIGHTS LTG_SCH_BASEMENT BASEMENT 1978.83 106.5 17313.725 8.749 162.572 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 17313.725
2 RETAIL_1_FLR_1_LIGHTS LTG_SCH_RETAIL RETAIL_1_FLR_1 67.07 10.8 872.757 13.012 80.594 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 872.757
3 RETAIL_2_FLR_1_LIGHTS LTG_SCH_RETAIL RETAIL_2_FLR_1 77.67 12.5 1010.656 13.012 80.595 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1010.656
4 MECH_FLR_1_LIGHTS LTG_SCH_MECHANIC MECH_FLR_1 164.24 2.7 1652.984 10.064 623.297 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1652.984
5 STORAGE_FLR_1_LIGHTS LTG_SCH_STORAGE STORAGE_FLR_1 94.76 2.0 693.586 7.319 339.993 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 693.586
6 LAUNDRY_FLR_1_LIGHTS LTG_SCH_LAUNDRY LAUNDRY_FLR_1 78.04 8.4 428.405 5.490 51.001 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 428.405
7 CAFE_FLR_1_LIGHTS LTG_SCH_DINING CAFE_FLR_1 188.86 142.3 2419.140 12.809 17.000 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2419.140
8 LOBBY_FLR_1_LIGHTS LTG_SCH_LOBBY LOBBY_FLR_1 1308.19 422.4 13165.908 10.064 31.167 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 13165.908
9 ROOM_1_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_1_FLR_3 39.02 1.5 392.727 10.064 261.818 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 392.727
10 ROOM_2_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_2_FLR_3 39.02 1.5 392.681 10.064 261.787 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 392.681
11 ROOM_3_MULT19_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_3_MULT19_FLR_3 24.52 1.5 246.814 10.064 164.543 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 246.814
12 ROOM_4_MULT19_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_4_MULT19_FLR_3 24.53 1.5 246.881 10.064 164.588 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 246.881
13 ROOM_5_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_5_FLR_3 39.02 1.5 392.727 10.064 261.818 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 392.727
14 ROOM_6_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_6_FLR_3 39.02 1.5 392.681 10.064 261.787 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 392.681
15 CORRIDOR_FLR_3_LIGHTS LTG_SCH_CORRIDOR CORRIDOR_FLR_3 389.40 21.0 1425.114 3.660 68.002 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1425.114
16 ROOM_1_FLR_6_LIGHTS LTG_SCH_GUESTROOM ROOM_1_FLR_6 39.02 1.5 392.727 10.064 261.818 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 392.727
17 ROOM_2_FLR_6_LIGHTS LTG_SCH_GUESTROOM ROOM_2_FLR_6 39.02 1.5 392.681 10.064 261.787 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 392.681
18 ROOM_3_MULT9_FLR_6_LIGHTS LTG_SCH_GUESTROOM ROOM_3_MULT9_FLR_6 24.53 1.5 246.881 10.064 164.588 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 246.881
19 BANQUET_FLR_6_LIGHTS LTG_SCH_DINING BANQUET_FLR_6 331.66 249.9 4248.214 12.809 17.000 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 4248.214
20 DINING_FLR_6_LIGHTS LTG_SCH_DINING DINING_FLR_6 331.66 249.9 4248.214 12.809 17.000 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 4248.214
21 KITCHEN_FLR_6_LIGHTS LTG_SCH_KITCHEN KITCHEN_FLR_6 103.30 22.2 1134.198 10.979 51.003 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1134.198
22 CORRIDOR_FLR_6_LIGHTS LTG_SCH_CORRIDOR CORRIDOR_FLR_6 412.12 22.2 1508.264 3.660 68.001 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1508.264


ElectricEquipment Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Equipment Level {W} Equipment/Floor Area {W/m2} Equipment per person {W/person} Fraction Latent Fraction Radiant Fraction Lost Fraction Convected End-Use SubCategory Nominal Minimum Equipment Level {W} Nominal Maximum Equipment Level {W}
1 BASEMENT_MISCPLUG_EQUIP BASEMENT_EQUIP_SCH BASEMENT 1978.83 106.5 10646.106 5.380 99.964 0.000 0.500 0.000 0.500 MiscPlug 0.000 10646.106
2 RETAIL_1_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH RETAIL_1_FLR_1 67.07 10.8 721.688 10.760 66.644 0.000 0.500 0.000 0.500 MiscPlug 0.000 721.688
3 RETAIL_2_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH RETAIL_2_FLR_1 77.67 12.5 835.717 10.760 66.644 0.000 0.500 0.000 0.500 MiscPlug 0.000 835.717
4 MECH_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH MECH_FLR_1 164.24 2.7 883.628 5.380 333.193 0.000 0.500 0.000 0.500 MiscPlug 0.000 883.628
5 STORAGE_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH STORAGE_FLR_1 94.76 2.0 254.902 2.690 124.952 0.000 0.500 0.000 0.500 MiscPlug 0.000 254.902
6 LAUNDRY_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH LAUNDRY_FLR_1 78.04 8.4 4813.474 61.680 573.033 0.000 0.500 0.000 0.500 MiscPlug 0.000 4813.474
7 CAFE_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH CAFE_FLR_1 188.86 142.3 1016.077 5.380 7.140 0.000 0.500 0.000 0.500 MiscPlug 0.000 1016.077
8 LOBBY_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH LOBBY_FLR_1 1308.19 422.4 10557.062 8.070 24.991 0.000 0.500 0.000 0.500 MiscPlug 0.000 10557.062
9 ROOM_1_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_BASE ROOM_1_FLR_3 39.02 1.5 263.399 6.750 175.599 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.399
10 ROOM_2_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_BASE ROOM_2_FLR_3 39.02 1.5 263.368 6.750 175.579 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.368
11 ROOM_3_MULT19_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_BASE ROOM_3_MULT19_FLR_3 24.52 1.5 257.991 10.520 171.994 0.000 0.500 0.000 0.500 MiscPlug 0.000 257.991
12 ROOM_4_MULT19_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_BASE ROOM_4_MULT19_FLR_3 24.53 1.5 258.061 10.520 172.041 0.000 0.500 0.000 0.500 MiscPlug 0.000 258.061
13 ROOM_5_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_BASE ROOM_5_FLR_3 39.02 1.5 263.399 6.750 175.599 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.399
14 ROOM_6_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_BASE ROOM_6_FLR_3 39.02 1.5 263.368 6.750 175.579 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.368
15 ROOM_1_FLR_6_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_BASE ROOM_1_FLR_6 39.02 1.5 263.399 6.750 175.599 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.399
16 ROOM_2_FLR_6_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_BASE ROOM_2_FLR_6 39.02 1.5 263.368 6.750 175.579 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.368
17 ROOM_3_MULT9_FLR_6_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_BASE ROOM_3_MULT9_FLR_6 24.53 1.5 258.061 10.520 172.041 0.000 0.500 0.000 0.500 MiscPlug 0.000 258.061
18 BANQUET_FLR_6_MISCPLUG_EQUIP KITCHEN_ELEC_EQUIP_SCH BANQUET_FLR_6 331.66 249.9 22493.008 67.820 90.009 0.000 0.500 0.000 0.500 Cooking 0.000 6747.903
19 DINING_FLR_6_MISCPLUG_EQUIP KITCHEN_ELEC_EQUIP_SCH DINING_FLR_6 331.66 249.9 22493.008 67.820 90.009 0.000 0.500 0.000 0.500 Cooking 0.000 6747.903
20 KITCHEN_FLR_6_MISCELEC_EQUIP KITCHEN_ELEC_EQUIP_SCH KITCHEN_FLR_6 103.30 22.2 52482.799 508.040 2360.050 0.200 0.500 0.100 0.200 Cooking 0.000 15744.840
21 KITCHEN_FLR_6_REACH-IN-FREEZER ALWAYS_ON KITCHEN_FLR_6 103.30 22.2 515.917 4.994 23.200 0.000 0.250 0.000 0.750 ReachInFreezer 515.917 515.917
22 KITCHEN_FLR_6_REACH-IN-REFRIGERATOR ALWAYS_ON KITCHEN_FLR_6 103.30 22.2 425.833 4.122 19.149 0.000 0.250 0.000 0.750 ReachInRefrigerator 425.833 425.833


GasEquipment Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Equipment Level {W} Equipment/Floor Area {W/m2} Equipment per person {W/person} Fraction Latent Fraction Radiant Fraction Lost Fraction Convected End-Use SubCategory Nominal Minimum Equipment Level {W} Nominal Maximum Equipment Level {W}
1 LAUNDRY_FLR_1_MISCGAS_EQUIP BLDG_EQUIP_SCH LAUNDRY_FLR_1 78.04 8.4 41817.449 535.850 4978.268 0.000 0.500 0.000 0.500 Laundry 0.000 41817.449
2 KITCHEN_FLR_6_MISCGAS_EQUIP KITCHEN_GAS_EQUIP_SCH KITCHEN_FLR_6 103.30 22.2 249920.353 2419.260 11238.437 0.100 0.200 0.700 0.000 Cooking 0.000 74976.106


Construction CTF

Construction Name Index #Layers #CTFs Time Step {hours} ThermalConductance {w/m2-K} OuterThermalAbsorptance InnerThermalAbsorptance OuterSolarAbsorptance InnerSolarAbsorptance Roughness
1 SWINGING DOOR_CON 1 1 1 0.167 3.464 0.900 0.900 0.700 0.700 MediumRough
2 OVERHEAD DOOR_CON 2 1 1 0.167 1.198 0.900 0.900 0.700 0.700 MediumRough
3 INTERIORFURNISHINGS 3 1 9 0.167 0.8000 0.900 0.900 0.700 0.700 MediumSmooth
4 INT_WALL 8 2 4 0.167 6.299 0.900 0.900 0.700 0.700 Smooth
5 NONRES_ROOF 18 3 3 0.167 0.2832 0.750 0.900 0.450 0.700 Rough
6 RES_ROOF 19 3 3 0.167 0.2832 0.750 0.900 0.450 0.700 Rough
7 NONRES_EXT_WALL_GRD 21 3 9 0.167 0.9686 0.900 0.900 0.700 0.700 MediumRough
8 NONRES_EXT_WALL_MID 22 3 9 0.167 1.265 0.900 0.900 0.700 0.700 MediumRough
9 NONRES_EXT_WALL_TOP 23 3 9 0.167 1.335 0.900 0.900 0.700 0.700 MediumRough
10 RES_EXT_WALL_MID 25 3 9 0.167 1.217 0.900 0.900 0.700 0.700 MediumRough
11 RES_EXT_WALL_TOP 26 3 9 0.167 1.286 0.900 0.900 0.700 0.700 MediumRough
12 NONRES_FLOOR 30 3 7 0.167 0.1963 0.900 0.900 0.700 0.700 MediumSmooth
13 NONRES_FLOOR_CEILING 33 3 7 0.167 0.1963 0.900 0.900 0.700 0.700 VeryRough
14 BASEMENT_FLOOR 36 2 7 0.333 2.705 0.900 0.900 0.700 0.700 MediumRough
15 BASEMENT_WALL_NORTH_CFACTOR 39 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough
16 BASEMENT_WALL_EAST_CFACTOR 40 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough
17 BASEMENT_WALL_SOUTH_CFACTOR 41 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough
18 BASEMENT_WALL_WEST_CFACTOR 42 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough


Material CTF Summary

Material Name Thickness {m} Conductivity {w/m-K} Density {kg/m3} Specific Heat {J/kg-K} ThermalResistance {m2-K/w}
1 OPAQUE DOOR PANEL_CON 0.0000 0.000 0.000 0.000 0.2887
2 OVERHEAD DOOR_CON PANEL 0.0000 0.000 0.000 0.000 0.8346
3 STD WOOD 6INCH 0.1500 0.120 540.000 1210.000 1.250
4 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
5 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
6 F13 BUILT-UP ROOFING 0.0095 0.160 1120.000 1460.000 0.5938E-01
7 NONRES_ROOF_INSULATION 0.0000 0.000 0.000 0.000 3.472
8 F08 METAL SURFACE 0.0008 45.280 7824.000 500.000 0.1767E-04
9 F13 BUILT-UP ROOFING 0.0095 0.160 1120.000 1460.000 0.5938E-01
10 RES_ROOF_INSULATION 0.0000 0.000 0.000 0.000 3.472
11 F08 METAL SURFACE 0.0008 45.280 7824.000 500.000 0.1767E-04
12 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
13 NONRES_EXTERIOR_WALL_INSULATION_GRD 0.0000 0.000 0.000 0.000 0.8651
14 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
15 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
16 NONRES_EXTERIOR_WALL_INSULATION_MID 0.0000 0.000 0.000 0.000 0.6234
17 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
18 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
19 NONRES_EXTERIOR_WALL_INSULATION_TOP 0.0000 0.000 0.000 0.000 0.5819
20 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
21 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
22 RES_EXTERIOR_WALL_INSULATION_MID 0.0000 0.000 0.000 0.000 0.6546
23 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
24 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
25 RES_EXTERIOR_WALL_INSULATION_TOP 0.0000 0.000 0.000 0.000 0.6103
26 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
27 NONRES_FLOOR_INSULATION 0.0000 0.000 0.000 0.000 4.833
28 100MM NORMALWEIGHT CONCRETE FLOOR 0.1016 2.310 2322.000 832.000 0.4398E-01
29 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
30 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
31 100MM NORMALWEIGHT CONCRETE FLOOR 0.1016 2.310 2322.000 832.000 0.4398E-01
32 NONRES_FLOOR_INSULATION 0.0000 0.000 0.000 0.000 4.833
33 M10 200MM CONCRETE BLOCK BASEMENT WALL 0.2032 1.326 1842.000 912.000 0.1532
34 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
35 ~FC_Insulation_1 0.0000 0.000 0.000 0.000 0.9868
36 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
37 ~FC_Insulation_2 0.0000 0.000 0.000 0.000 0.9868
38 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
39 ~FC_Insulation_3 0.0000 0.000 0.000 0.000 0.9868
40 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
41 ~FC_Insulation_4 0.0000 0.000 0.000 0.000 0.9868
42 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01


CTF

Time Outside Cross Inside Flux (except final one)
1 1 0.0000000 0.0000000 -0.0000000 -0.0000000
2 0 3.4637404 3.4637404 3.4637404  
3 1 0.0000000 0.0000000 -0.0000000 -0.0000000
4 0 1.1981135 1.1981135 1.1981135  
5 9 -0.27580628E-02 0.97439125E-12 -0.27580628E-02 0.28516790E-03
6 8 0.73590997E-01 0.21837543E-08 0.73590997E-01 -0.77836043E-02
7 7 -0.82599318 0.23162835E-06 -0.82599318 0.89703933E-01
8 6 5.1113916 0.48671053E-05 5.1113916 -0.57224845
9 5 -19.214933 0.30163627E-04 -19.214933 2.2266322
10 4 45.557404 0.63181060E-04 45.557404 -5.4853312
11 3 -68.275533 0.44785456E-04 -68.275533 8.5710568
12 2 62.555368 0.93952058E-05 62.555368 -8.2111738
13 1 -31.904423 0.39200004E-06 -31.904423 4.3886678
14 0 6.9260389 0.77047546E-09 6.9260389  
15 4 0.68458728E-09 0.26079551E-09 0.68458728E-09 -0.34507121E-18
16 3 -0.72180374E-03 0.24295686E-03 -0.72180374E-03 0.69691454E-09
17 2 0.83054762 0.27682775 0.83054762 -0.35168967E-03
18 1 -12.650482 3.3590720 -12.650482 0.19281313
19 0 16.907513 1.4507143 16.907513  
20 3 -0.61927053E-06 0.12767249E-08 -0.37968499E-05 0.16832131E-17
21 2 0.77611055 0.17315568E-02 1.0534842 -0.72792597E-06
22 1 -21.915918 0.11588205 -6.3286394 0.20197014
23 0 21.365777 0.10835518 5.5011278  
24 3 -0.61927053E-06 0.12767249E-08 -0.37968499E-05 0.16832131E-17
25 2 0.77611055 0.17315568E-02 1.0534842 -0.72792597E-06
26 1 -21.915918 0.11588205 -6.3286394 0.20197014
27 0 21.365777 0.10835518 5.5011278  
28 9 0.28610217E-16 0.32712183E-16 -0.14788665E-09 0.15262255E-17
29 8 0.21617198E-07 0.13019051E-12 0.37508535E-03 -0.24579497E-09
30 7 -0.12160768E-01 0.67781631E-08 -0.22969495E-01 0.13827236E-03
31 6 0.40315523 0.23644201E-05 0.47022156 -0.47218870E-02
32 5 -5.1691419 0.88489975E-04 -4.4269034 0.62918229E-01
33 4 32.908103 0.72540386E-03 21.384224 -0.42086483
34 3 -111.02464 0.15839520E-02 -55.513084 1.5122822
35 2 196.93145 0.89247901E-03 77.773085 -2.8975455
36 1 -171.09078 0.95424204E-04 -55.225093 2.7442950
37 0 57.057407 0.54416031E-06 15.563533  
38 9 0.16021817E-14 0.43623596E-16 -0.13387302E-09 -0.38399267E-17
39 8 0.19641607E-07 0.16693997E-12 0.35391383E-03 -0.22333182E-09
40 7 -0.11527600E-01 0.88905521E-08 -0.22057378E-01 0.13107300E-03
41 6 0.38594887 0.31296587E-05 0.45553223 -0.45190661E-02
42 5 -5.0012033 0.11804975E-03 -4.3139252 0.60835889E-01
43 4 32.165114 0.97455506E-03 20.942266 -0.41100022
44 3 -109.44341 0.21413112E-02 -54.639172 1.4894383
45 2 195.36376 0.12132308E-02 76.972220 -2.8726514
46 1 -170.51151 0.13038514E-03 -54.993414 2.7341426
47 0 57.057407 0.74764616E-06 15.602778  
48 9 0.89845624E-15 0.45148486E-16 -0.13053700E-09 -0.34170761E-17
49 8 0.19169472E-07 0.17528607E-12 0.34874871E-03 -0.21796351E-09
50 7 -0.11372769E-01 0.93896549E-08 -0.21834212E-01 0.12931251E-03
51 6 0.38174081 0.33130355E-05 0.45193069 -0.44694638E-02
52 5 -4.9601253 0.12521571E-03 -4.2861852 0.60326552E-01
53 4 31.983339 0.10355575E-02 20.833661 -0.40858686
54 3 -109.05644 0.22789331E-02 -54.424381 1.4838481
55 2 194.97998 0.12930063E-02 76.775547 -2.8665574
56 1 -170.36965 0.13913733E-03 -54.936825 2.7316564
57 0 57.057407 0.79895123E-06 15.612614  
58 9 0.12430042E-14 0.43603463E-16 -0.13615479E-09 -0.52742981E-17
59 8 0.19963588E-07 0.16114398E-12 0.35741204E-03 -0.22699287E-09
60 7 -0.11632381E-01 0.85488282E-08 -0.22208377E-01 0.13226440E-03
61 6 0.38879653 0.30047059E-05 0.45796739 -0.45526330E-02
62 5 -5.0290001 0.11318598E-03 -4.3326723 0.61180550E-01
63 4 32.288109 0.93328928E-03 21.015642 -0.41263319
64 3 -109.70522 0.20484795E-02 -54.784283 1.4932205
65 2 195.62339 0.11595496E-02 77.105128 -2.8767741
66 1 -170.60747 0.12450863E-03 -55.031726 2.7358244
67 0 57.057407 0.71328115E-06 15.596176  
68 9 0.10418955E-14 0.45554749E-16 -0.13285794E-09 -0.34221686E-17
69 8 0.19498290E-07 0.16949498E-12 0.35235048E-03 -0.22170227E-09
70 7 -0.11480752E-01 0.90423087E-08 -0.21989859E-01 0.13054032E-03
71 6 0.38467563 0.31853038E-05 0.45444290 -0.45040579E-02
72 5 -4.9887746 0.12022067E-03 -4.3055366 0.60681782E-01
73 4 32.110117 0.99300969E-03 20.909427 -0.41027004
74 3 -109.32633 0.21828955E-02 -54.574228 1.4877470
75 2 195.24766 0.12373115E-02 76.912747 -2.8708078
76 1 -170.46860 0.13302463E-03 -54.976289 2.7333905
77 0 57.057407 0.76310210E-06 15.605744  
78 7 -0.15963512E-14 -0.15187529E-16 -0.22427203E-13 0.56155309E-15
79 6 0.17983713E-10 0.23594901E-11 0.52322926E-09 -0.18637893E-10
80 5 -0.60139213E-07 0.11510628E-07 -0.21924491E-05 0.17161312E-06
81 4 0.62746279E-04 0.43399923E-05 0.17681060E-02 -0.28244642E-03
82 3 -0.90508353E-02 0.15320797E-03 -0.21560640 0.43341486E-01
83 2 0.12836503 0.66328859E-03 2.9007871 -0.61911613
84 1 -0.32478029 0.41934727E-03 -7.1379041 1.5697129
85 0 0.20664896 0.54311639E-05 4.4522013  
86 7 -0.22427203E-13 -0.15187529E-16 -0.15963512E-14 0.56155309E-15
87 6 0.52322926E-09 0.23594901E-11 0.17983713E-10 -0.18637893E-10
88 5 -0.21924491E-05 0.11510628E-07 -0.60139213E-07 0.17161312E-06
89 4 0.17681060E-02 0.43399923E-05 0.62746279E-04 -0.28244642E-03
90 3 -0.21560640 0.15320797E-03 -0.90508353E-02 0.43341486E-01
91 2 2.9007871 0.66328859E-03 0.12836503 -0.61911613
92 1 -7.1379041 0.41934727E-03 -0.32478029 1.5697129
93 0 4.4522013 0.54311639E-05 0.20664896  
94 7 -0.52459208E-15 -0.63961428E-15 -0.12292524E-09 -0.35846135E-17
95 6 0.39860198E-02 0.96339020E-07 0.40499006E-03 -0.70890431E-04
96 5 -0.20832379 0.49172556E-04 -0.20585669E-01 0.38489246E-02
97 4 3.5198270 0.18993977E-02 0.34924834 -0.69168259E-01
98 3 -23.366787 0.13311857E-01 -2.4329538 0.50524779
99 2 64.890127 0.19943872E-01 7.3672511 -1.5911358
100 1 -76.040094 0.56792084E-02 -9.5568013 2.1361271
101 0 31.242244 0.96490710E-04 4.3344156  
102 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
103 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
104 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
105 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
106 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
107 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
108 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
109 0 1.0055995 0.48413807E-04 60.838472  
110 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
111 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
112 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
113 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
114 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
115 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
116 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
117 0 1.0055995 0.48413807E-04 60.838472  
118 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
119 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
120 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
121 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
122 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
123 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
124 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
125 0 1.0055995 0.48413807E-04 60.838472  
126 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
127 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
128 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
129 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
130 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
131 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
132 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
133 0 1.0055995 0.48413807E-04 60.838472  


WindowConstruction

Construction Name Index #Layers Roughness Conductance {W/m2-K} Conductance (Before Adjusted) {W/m2-K} Convection Coefficient Adjustment Ratio SHGC Solar Transmittance at Normal Incidence Visible Transmittance at Normal Incidence
1 NONRESWINDOW_U_0.4711_SHGC_0.25 37 1 VerySmooth 2.678 2.678 1.000 0.251    
2 RESWINDOW_U_0.4711_SHGC_0.25 38 1 VerySmooth 2.678 2.678 1.000 0.251    


WindowMaterial:Glazing

Material Name Optical Data Type Spectral Data Set Name Thickness {m} Solar Transmittance Front Solar Reflectance Back Solar Reflectance Visible Transmittance Front Visible Reflectance Back Visible Reflectance Infrared Transmittance Front Thermal Emissivity Back Thermal Emissivity Conductivity {W/m-K} Dirt Factor Solar Diffusing
1 GLAZING LAYER SpectralAverage   2.39142E-002 0.16139 0.61472 0.61472 0.25000 0.16143 0.23877 0.00000 0.84000 0.84000 0.11798 1.00000 No
2 RESIDENTIAL WINDOW GLAZING LAYER SpectralAverage   2.39142E-002 0.16139 0.61472 0.61472 0.25000 0.16143 0.23877 0.00000 0.84000 0.84000 0.11798 1.00000 No


Shadowing/Sun Position Calculations Annual Simulations

Shading Calculation Method Shading Calculation Update Frequency Method Shading Calculation Update Frequency {days} Maximum Figures in Shadow Overlap Calculations {} Polygon Clipping Algorithm Pixel Counting Resolution Sky Diffuse Modeling Algorithm Output External Shading Calculation Results Disable Self-Shading Within Shading Zone Groups Disable Self-Shading From Shading Zone Groups to Other Zones
1 PolygonClipping Periodic 7 15000 SutherlandHodgman 512 SimpleSkyDiffuseModeling No No No


#Refrigeration Compressor Racks

Number of Refrigeration Compressor Racks
1 2


Refrigeration Compressor Rack

Compressor Rack Name # Refrigerated Cases Connected # WalkIn Coolers Connected Heat Rejection Location Condenser Type COP
1 RACK1 1 0 Zone Air-Cooled 1.500
2 RACK2 1 0 Zone Air-Cooled 3.000


Water Heater Information

Type Name Volume {m3} Maximum Capacity {W} Standard Rated Recovery Efficiency Standard Rated Energy Factor
1 WaterHeater:Mixed SWH BOOSTER E WATER HEATER 2.2712E-002 8000.0 1.240 1.1473
2 WaterHeater:Mixed SWH LAUNDRY G WATER HEATER 1.1356 163316.0 0.576 0.5074
3 WaterHeater:Mixed SWHSYS1 WATER HEATER 2.2712 175842.6 0.260 2.5713E-002


Surface Convection Parameters

Surface Name Outside Model Assignment Outside Area [m2] Outside Perimeter [m] Outside Height [m] Inside Model Assignment Inside Height [m] Inside Perimeter Envelope [m] Inside Hydraulic Diameter [m] Window Wall Ratio Window Location Near Radiant {Yes/No} Has Active HVAC {Yes/No}
1 BASEMENT_WALL_NORTH 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
2 BASEMENT_WALL_EAST 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
3 BASEMENT_WALL_SOUTH 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
4 BASEMENT_WALL_WEST 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
5 BASEMENT_FLOOR 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
6 BASEMENT_CEILING_1 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
7 BASEMENT_CEILING_2 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
8 BASEMENT_CEILING_3 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
9 BASEMENT_CEILING_4 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
10 BASEMENT_CEILING_5 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
11 BASEMENT_CEILING_6 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
12 BASEMENT_CEILING_7 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
13 BASEMENT_CEILING_8 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
14 BASEMENT_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
15 RETAIL_1_FLR_1_WALL_SOUTH 0 506.51 211.91 19.20 0 3.96 17.37 7.72 0.34 4 No No
16 RETAIL_1_FLR_1_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.96 17.37 7.72 0.34 1 No No
17 RETAIL_1_FLR_1_WALL_WEST 0 194.63 84.12 19.20 0 3.96 17.37 7.72 0.34 3 No No
18 RETAIL_1_FLR_1_WALL_NORTH 0 0.00 0.00 0.00 0 3.96 17.37 7.72 0.34 0 No No
19 RETAIL_1_FLR_1_WALL_EAST 0 0.00 0.00 0.00 0 3.96 17.37 7.72 0.34 0 No No
20 RETAIL_1_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 17.37 7.72 0.34 0 No No
21 RETAIL_1_FLR_1_CEILING 0 1782.60 293.11 15.24 0 3.96 17.37 7.72 0.34 0 No No
22 RETAIL_1_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 17.37 7.72 0.34 0 No No
23 RETAIL_2_FLR_1_WALL_WEST 0 194.63 84.12 19.20 0 3.96 6.71 8.49 0.00 0 No No
24 RETAIL_2_FLR_1_WALL_WEST_DOOR 0 194.63 84.12 19.20 0 3.96 6.71 8.49 0.00 0 No No
25 RETAIL_2_FLR_1_WALL_SOUTH 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
26 RETAIL_2_FLR_1_WALL_NORTH 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
27 RETAIL_2_FLR_1_WALL_EAST 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
28 RETAIL_2_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
29 RETAIL_2_FLR_1_CEILING 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
30 RETAIL_2_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
31 MECH_FLR_1_WALL_NORTH 0 670.01 217.46 19.20 0 3.96 15.85 12.53 0.00 0 No No
32 MECH_FLR_1_WALL_EAST 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
33 MECH_FLR_1_WALL_SOUTH 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
34 MECH_FLR_1_WALL_WEST 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
35 MECH_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
36 MECH_FLR_1_CEILING 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
37 MECH_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
38 STORAGE_FLR_1_WALL_NORTH 0 670.01 217.46 19.20 0 3.96 9.14 9.72 0.00 0 No No
39 STORAGE_FLR_1_WALL_NORTH_ROLLDOOR 0 670.01 217.46 19.20 0 3.96 9.14 9.72 0.00 0 No No
40 STORAGE_FLR_1_WALL_EAST 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
41 STORAGE_FLR_1_WALL_SOUTH 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
42 STORAGE_FLR_1_WALL_WEST 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
43 STORAGE_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
44 STORAGE_FLR_1_CEILING 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
45 STORAGE_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
46 LAUNDRY_FLR_1_WALL_NORTH 0 670.01 217.46 19.20 0 3.96 21.64 7.21 0.00 0 No No
47 LAUNDRY_FLR_1_WALL_EAST 0 194.63 217.46 19.20 0 3.96 21.64 7.21 0.00 0 No No
48 LAUNDRY_FLR_1_WALL_EAST_DOOR 0 194.63 217.46 19.20 0 3.96 21.64 7.21 0.00 0 No No
49 LAUNDRY_FLR_1_WALL_SOUTH 0 0.00 0.00 0.00 0 3.96 21.64 7.21 0.00 0 No No
50 LAUNDRY_FLR_1_WALL_WEST 0 0.00 0.00 0.00 0 3.96 21.64 7.21 0.00 0 No No
51 LAUNDRY_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 21.64 7.21 0.00 0 No No
52 LAUNDRY_FLR_1_CEILING 0 0.00 0.00 0.00 0 3.96 21.64 7.21 0.00 0 No No
53 LAUNDRY_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 21.64 7.21 0.00 0 No No
54 CAFE_FLR_1_WALL_EAST 0 194.63 217.46 19.20 0 3.96 38.40 9.84 0.43 3 No No
55 CAFE_FLR_1_WALL_EAST_DOOR 0 194.63 217.46 19.20 0 3.96 38.40 9.84 0.43 0 No No
56 CAFE_FLR_1_WALL_SOUTH 0 506.51 211.91 19.20 0 3.96 38.40 9.84 0.43 4 No No
57 CAFE_FLR_1_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.96 38.40 9.84 0.43 1 No No
58 CAFE_FLR_1_WALL_1_NORTH 0 0.00 0.00 0.00 0 3.96 38.40 9.84 0.43 0 No No
59 CAFE_FLR_1_WALL_2_NORTH 0 0.00 0.00 0.00 0 3.96 38.40 9.84 0.43 0 No No
60 CAFE_FLR_1_WALL_WEST 0 0.00 0.00 0.00 0 3.96 38.40 9.84 0.43 0 No No
61 CAFE_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 38.40 9.84 0.43 0 No No
62 CAFE_FLR_1_CEILING 0 1782.60 293.11 15.24 0 3.96 38.40 9.84 0.43 0 No No
63 CAFE_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 38.40 9.84 0.43 0 No No
64 LOBBY_FLR_1_WALL_1_NORTH 0 670.01 217.46 19.20 0 3.96 109.73 24.95 0.20 3 No No
65 LOBBY_FLR_1_WALL_1_NORTH_DOOR1 0 670.01 217.46 19.20 0 3.96 109.73 24.95 0.20 0 No No
66 LOBBY_FLR_1_WALL_1_NORTH_DOOR2 0 670.01 217.46 19.20 0 3.96 109.73 24.95 0.20 0 No No
67 LOBBY_FLR_1_WALL_2_NORTH 0 670.01 217.46 19.20 0 3.96 109.73 24.95 0.20 4 No No
68 LOBBY_FLR_1_WALL_1_SOUTH 0 506.51 211.91 19.20 0 3.96 109.73 24.95 0.20 4 No No
69 LOBBY_FLR_1_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.96 109.73 24.95 0.20 1 No No
70 LOBBY_FLR_1_WALL_1_WEST 0 194.63 84.12 19.20 0 3.96 109.73 24.95 0.20 3 No No
71 LOBBY_FLR_1_WALL_2_SOUTH 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
72 LOBBY_FLR_1_WALL_3_SOUTH 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
73 LOBBY_FLR_1_WALL_2_WEST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
74 LOBBY_FLR_1_WALL_3_WEST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
75 LOBBY_FLR_1_WALL_4_WEST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
76 LOBBY_FLR_1_WALL_3_NORTH 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
77 LOBBY_FLR_1_WALL_4_NORTH 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
78 LOBBY_FLR_1_WALL_1_EAST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
79 LOBBY_FLR_1_WALL_2_EAST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
80 LOBBY_FLR_1_WALL_3_EAST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
81 LOBBY_FLR_1_FLOOR_1 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
82 LOBBY_FLR_1_FLOOR_2 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
83 LOBBY_FLR_1_CEILING_1 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
84 LOBBY_FLR_1_CEILING_2 0 1782.60 293.11 15.24 0 3.96 109.73 24.95 0.20 0 No No
85 LOBBY_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
86 ROOM_1_FLR_3_WALL_SOUTH 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 3 No No
87 ROOM_1_FLR_3_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 2 No No
88 ROOM_1_FLR_3_WALL_WEST 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 3 No No
89 ROOM_1_FLR_3_WALL_WEST_WINDOW 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 2 No No
90 ROOM_1_FLR_3_WALL_NORTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
91 ROOM_1_FLR_3_WALL_EAST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
92 ROOM_1_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
93 ROOM_1_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
94 ROOM_1_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
95 ROOM_2_FLR_3_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 3 No No
96 ROOM_2_FLR_3_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 2 No No
97 ROOM_2_FLR_3_WALL_WEST 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 3 No No
98 ROOM_2_FLR_3_WALL_WEST_WINDOW 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 2 No No
99 ROOM_2_FLR_3_WALL_EAST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
100 ROOM_2_FLR_3_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
101 ROOM_2_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
102 ROOM_2_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
103 ROOM_2_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
104 ROOM_3_MULT19_FLR_3_WALL_SOUTH 0 506.51 211.91 19.20 0 3.05 3.66 4.73 0.33 3 No No
105 ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 3.66 4.73 0.33 2 No No
106 ROOM_3_MULT19_FLR_3_WALL_NORTH 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
107 ROOM_3_MULT19_FLR_3_WALL_EAST 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
108 ROOM_3_MULT19_FLR_3_WALL_WEST 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
109 ROOM_3_MULT19_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
110 ROOM_3_MULT19_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
111 ROOM_3_MULT19_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
112 ROOM_4_MULT19_FLR_3_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 3.66 4.73 0.33 3 No No
113 ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 3.66 4.73 0.33 2 No No
114 ROOM_4_MULT19_FLR_3_WALL_EAST 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
115 ROOM_4_MULT19_FLR_3_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
116 ROOM_4_MULT19_FLR_3_WALL_WEST 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
117 ROOM_4_MULT19_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
118 ROOM_4_MULT19_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
119 ROOM_4_MULT19_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
120 ROOM_5_FLR_3_WALL_EAST 0 194.63 217.46 19.20 0 3.05 13.11 5.95 0.33 3 No No
121 ROOM_5_FLR_3_WALL_EAST_WINDOW 0 194.63 217.46 19.20 0 3.05 13.11 5.95 0.33 2 No No
122 ROOM_5_FLR_3_WALL_SOUTH 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 3 No No
123 ROOM_5_FLR_3_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 2 No No
124 ROOM_5_FLR_3_WALL_NORTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
125 ROOM_5_FLR_3_WALL_WEST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
126 ROOM_5_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
127 ROOM_5_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
128 ROOM_5_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
129 ROOM_6_FLR_3_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 3 No No
130 ROOM_6_FLR_3_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 2 No No
131 ROOM_6_FLR_3_WALL_EAST 0 194.63 217.46 19.20 0 3.05 13.11 5.95 0.33 3 No No
132 ROOM_6_FLR_3_WALL_EAST_WINDOW 0 194.63 217.46 19.20 0 3.05 13.11 5.95 0.33 2 No No
133 ROOM_6_FLR_3_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
134 ROOM_6_FLR_3_WALL_WEST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
135 ROOM_6_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
136 ROOM_6_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
137 ROOM_6_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
138 CORRIDOR_FLR_3_WALL_1_NORTH 0 670.01 217.46 19.20 0 3.05 15.85 8.24 0.33 3 No No
139 CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 15.85 8.24 0.33 2 No No
140 CORRIDOR_FLR_3_WALL_2_NORTH 0 670.01 217.46 19.20 0 3.05 15.85 8.24 0.33 3 No No
141 CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 15.85 8.24 0.33 2 No No
142 CORRIDOR_FLR_3_WALL_1_SOUTH 0 506.51 211.91 19.20 0 3.05 15.85 8.24 0.33 3 No No
143 CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 15.85 8.24 0.33 2 No No
144 CORRIDOR_FLR_3_WALL_2_SOUTH 0 506.51 211.91 19.20 0 3.05 15.85 8.24 0.33 3 No No
145 CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 15.85 8.24 0.33 2 No No
146 CORRIDOR_FLR_3_WALL_3_NORTH 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
147 CORRIDOR_FLR_3_WALL_1_EAST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
148 CORRIDOR_FLR_3_WALL_2_EAST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
149 CORRIDOR_FLR_3_WALL_3_EAST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
150 CORRIDOR_FLR_3_WALL_4_EAST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
151 CORRIDOR_FLR_3_WALL_3_SOUTH 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
152 CORRIDOR_FLR_3_WALL_1_WEST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
153 CORRIDOR_FLR_3_WALL_2_WEST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
154 CORRIDOR_FLR_3_WALL_3_WEST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
155 CORRIDOR_FLR_3_WALL_4_WEST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
156 CORRIDOR_FLR_3_FLOOR_1 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
157 CORRIDOR_FLR_3_FLOOR_2 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
158 CORRIDOR_FLR_3_FLOOR_3 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
159 CORRIDOR_FLR_3_CEILING_1 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
160 CORRIDOR_FLR_3_CEILING_2 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
161 CORRIDOR_FLR_3_CEILING_3 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
162 CORRIDOR_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
163 ROOM_1_FLR_6_WALL_SOUTH 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 3 No No
164 ROOM_1_FLR_6_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 2 No No
165 ROOM_1_FLR_6_WALL_WEST 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 3 No No
166 ROOM_1_FLR_6_WALL_WEST_WINDOW 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 2 No No
167 ROOM_1_FLR_6_WALL_NORTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
168 ROOM_1_FLR_6_WALL_EAST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
169 ROOM_1_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
170 ROOM_1_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 13.11 5.95 0.33 0 No No
171 ROOM_1_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
172 ROOM_2_FLR_6_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 3 No No
173 ROOM_2_FLR_6_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 2 No No
174 ROOM_2_FLR_6_WALL_WEST 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 3 No No
175 ROOM_2_FLR_6_WALL_WEST_WINDOW 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 2 No No
176 ROOM_2_FLR_6_WALL_EAST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
177 ROOM_2_FLR_6_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
178 ROOM_2_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
179 ROOM_2_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 13.11 5.95 0.33 0 No No
180 ROOM_2_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
181 ROOM_3_MULT9_FLR_6_WALL_SOUTH 0 506.51 211.91 19.20 0 3.05 6.71 4.73 0.33 3 No No
182 ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 6.71 4.73 0.33 2 No No
183 ROOM_3_MULT9_FLR_6_WALL_NORTH 0 0.00 0.00 0.00 0 3.05 6.71 4.73 0.33 0 No No
184 ROOM_3_MULT9_FLR_6_WALL_EAST 0 0.00 0.00 0.00 0 3.05 6.71 4.73 0.33 0 No No
185 ROOM_3_MULT9_FLR_6_WALL_WEST 0 0.00 0.00 0.00 0 3.05 6.71 4.73 0.33 0 No No
186 ROOM_3_MULT9_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 6.71 4.73 0.33 0 No No
187 ROOM_3_MULT9_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 6.71 4.73 0.33 0 No No
188 ROOM_3_MULT9_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 6.71 4.73 0.33 0 No No
189 BANQUET_FLR_6_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 32.00 15.66 0.33 3 No No
190 BANQUET_FLR_6_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 32.00 15.66 0.33 2 No No
191 BANQUET_FLR_6_WALL_EAST 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
192 BANQUET_FLR_6_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
193 BANQUET_FLR_6_WALL_WEST 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
194 BANQUET_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
195 BANQUET_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 32.00 15.66 0.33 0 No No
196 BANQUET_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
197 DINING_FLR_6_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 32.00 15.66 0.33 3 No No
198 DINING_FLR_6_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 32.00 15.66 0.33 2 No No
199 DINING_FLR_6_WALL_EAST 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
200 DINING_FLR_6_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
201 DINING_FLR_6_WALL_WEST 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
202 DINING_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
203 DINING_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 32.00 15.66 0.33 0 No No
204 DINING_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
205 KITCHEN_FLR_6_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 28.65 8.58 0.30 3 No No
206 KITCHEN_FLR_6_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 28.65 8.58 0.30 2 No No
207 KITCHEN_FLR_6_WALL_EAST 0 194.63 217.46 19.20 0 3.05 28.65 8.58 0.30 3 No No
208 KITCHEN_FLR_6_WALL_EAST_WINDOW 0 194.63 217.46 19.20 0 3.05 28.65 8.58 0.30 2 No No
209 KITCHEN_FLR_6_WALL_1_SOUTH 0 506.51 211.91 19.20 0 3.05 28.65 8.58 0.30 3 No No
210 KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 28.65 8.58 0.30 2 No No
211 KITCHEN_FLR_6_WALL_2_SOUTH 0 0.00 0.00 0.00 0 3.05 28.65 8.58 0.30 0 No No
212 KITCHEN_FLR_6_WALL_1_WEST 0 0.00 0.00 0.00 0 3.05 28.65 8.58 0.30 0 No No
213 KITCHEN_FLR_6_WALL_2_WEST 0 0.00 0.00 0.00 0 3.05 28.65 8.58 0.30 0 No No
214 KITCHEN_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 28.65 8.58 0.30 0 No No
215 KITCHEN_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 28.65 8.58 0.30 0 No No
216 KITCHEN_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 28.65 8.58 0.30 0 No No
217 CORRIDOR_FLR_6_WALL_1_NORTH 0 670.01 217.46 19.20 0 3.05 28.04 8.72 0.33 3 No No
218 CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 28.04 8.72 0.33 2 No No
219 CORRIDOR_FLR_6_WALL_2_NORTH 0 670.01 217.46 19.20 0 3.05 28.04 8.72 0.33 3 No No
220 CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 28.04 8.72 0.33 2 No No
221 CORRIDOR_FLR_6_WALL_2_SOUTH 0 506.51 211.91 19.20 0 3.05 28.04 8.72 0.33 3 No No
222 CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 28.04 8.72 0.33 2 No No
223 CORRIDOR_FLR_6_WALL_3_NORTH 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
224 CORRIDOR_FLR_6_WALL_4_NORTH 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
225 CORRIDOR_FLR_6_WALL_1_SOUTH 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
226 CORRIDOR_FLR_6_WALL_1_WEST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
227 CORRIDOR_FLR_6_WALL_2_WEST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
228 CORRIDOR_FLR_6_WALL_3_WEST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
229 CORRIDOR_FLR_6_WALL_1_EAST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
230 CORRIDOR_FLR_6_WALL_2_EAST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
231 CORRIDOR_FLR_6_WALL_3_EAST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
232 CORRIDOR_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
233 CORRIDOR_FLR_6_CEILING_1 0 1782.60 293.11 15.24 0 3.05 28.04 8.72 0.33 0 No No
234 CORRIDOR_FLR_6_CEILING_2 0 1782.60 293.11 15.24 0 3.05 28.04 8.72 0.33 0 No No
235 CORRIDOR_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No


ZoneInfiltration Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Design Volume Flow Rate {m3/s} Volume Flow Rate/Floor Area {m3/s-m2} Volume Flow Rate/Exterior Surface Area {m3/s-m2} ACH - Air Changes per Hour Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2}
1 RETAIL_1_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH RETAIL_1_FLR_1 67.07 10.8 7.058E-002 1.052E-003 5.193E-004 0.956 1.000 0.000 0.000 0.000
2 RETAIL_2_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH RETAIL_2_FLR_1 77.67 12.5 2.724E-002 3.507E-004 9.551E-004 0.319 1.000 0.000 0.000 0.000
3 MECH_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH MECH_FLR_1 164.24 2.7 6.438E-002 3.920E-004 1.025E-003 0.356 1.000 0.000 0.000 0.000
4 STORAGE_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH STORAGE_FLR_1 94.76 2.0 3.715E-002 3.920E-004 8.507E-004 0.356 1.000 0.000 0.000 0.000
5 LAUNDRY_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH LAUNDRY_FLR_1 78.04 8.4 8.791E-002 1.127E-003 1.002E-003 1.023 1.000 0.000 0.000 0.000
6 CAFE_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH CAFE_FLR_1 188.86 142.3 0.156 8.261E-004 4.549E-004 0.751 1.000 0.000 0.000 0.000
7 LOBBY_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH LOBBY_FLR_1 1308.19 422.4 0.446 3.407E-004 6.517E-004 0.310 1.000 0.000 0.000 0.000
8 ROOM_1_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_1_FLR_3 39.02 1.5 4.096E-002 1.050E-003 1.025E-003 1.240 1.000 0.000 0.000 0.000
9 ROOM_2_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_2_FLR_3 39.02 1.5 4.095E-002 1.050E-003 1.025E-003 1.240 1.000 0.000 0.000 0.000
10 ROOM_3_MULT19_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_3_MULT19_FLR_3 24.52 1.5 1.143E-002 4.660E-004 1.025E-003 0.550 1.000 0.000 0.000 0.000
11 ROOM_4_MULT19_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_4_MULT19_FLR_3 24.53 1.5 1.143E-002 4.660E-004 1.025E-003 0.550 1.000 0.000 0.000 0.000
12 ROOM_5_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_5_FLR_3 39.02 1.5 4.096E-002 1.050E-003 1.025E-003 1.240 1.000 0.000 0.000 0.000
13 ROOM_6_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_6_FLR_3 39.02 1.5 4.095E-002 1.050E-003 1.025E-003 1.240 1.000 0.000 0.000 0.000
14 CORRIDOR_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH CORRIDOR_FLR_3 389.40 21.0 4.953E-002 1.272E-004 1.025E-003 0.150 1.000 0.000 0.000 0.000
15 ROOM_1_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_1_FLR_6 39.02 1.5 4.096E-002 1.050E-003 5.186E-004 1.240 1.000 0.000 0.000 0.000
16 ROOM_2_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_2_FLR_6 39.02 1.5 4.095E-002 1.050E-003 5.186E-004 1.240 1.000 0.000 0.000 0.000
17 ROOM_3_MULT9_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_3_MULT9_FLR_6 24.53 1.5 2.096E-002 8.543E-004 4.660E-004 1.009 1.000 0.000 0.000 0.000
18 BANQUET_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH BANQUET_FLR_6 331.66 249.9 0.100 3.015E-004 2.330E-004 0.356 1.000 0.000 0.000 0.000
19 DINING_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH DINING_FLR_6 331.66 249.9 0.100 3.015E-004 2.330E-004 0.356 1.000 0.000 0.000 0.000
20 KITCHEN_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH KITCHEN_FLR_6 103.30 22.2 8.953E-002 8.667E-004 4.697E-004 1.024 1.000 0.000 0.000 0.000
21 CORRIDOR_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH CORRIDOR_FLR_6 412.12 22.2 8.763E-002 2.126E-004 1.761E-004 0.251 1.000 0.000 0.000 0.000


ZoneVentilation Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Design Volume Flow Rate {m3/s} Volume Flow Rate/Floor Area {m3/s-m2} Volume Flow Rate/person Area {m3/s-person} ACH - Air Changes per Hour Fan Type {Exhaust;Intake;Natural} Fan Pressure Rise {Pa} Fan Efficiency {} Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2} Minimum Indoor Temperature{C}/Schedule Maximum Indoor Temperature{C}/Schedule Delta Temperature{C}/Schedule Minimum Outdoor Temperature{C}/Schedule Maximum Outdoor Temperature{C}/Schedule Maximum WindSpeed{m/s}
1 ROOM_1_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_1_FLR_3 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
2 ROOM_2_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_2_FLR_3 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
3 ROOM_3_MULT19_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_3_MULT19_FLR_3 24.52 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
4 ROOM_4_MULT19_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_4_MULT19_FLR_3 24.53 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
5 ROOM_5_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_5_FLR_3 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
6 ROOM_6_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_6_FLR_3 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
7 ROOM_1_FLR_6 SLIDING DOOR VENTILATION Constant-0.0 ROOM_1_FLR_6 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
8 ROOM_2_FLR_6 SLIDING DOOR VENTILATION Constant-0.0 ROOM_2_FLR_6 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
9 ROOM_3_MULT9_FLR_6 SLIDING DOOR VENTILATION Constant-0.0 ROOM_3_MULT9_FLR_6 24.53 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00


AirFlow Model

Simple
1 Simple


RoomAir Model

Zone Name Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined
1 BASEMENT Mixing/Well-Stirred
2 RETAIL_1_FLR_1 Mixing/Well-Stirred
3 RETAIL_2_FLR_1 Mixing/Well-Stirred
4 MECH_FLR_1 Mixing/Well-Stirred
5 STORAGE_FLR_1 Mixing/Well-Stirred
6 LAUNDRY_FLR_1 Mixing/Well-Stirred
7 CAFE_FLR_1 Mixing/Well-Stirred
8 LOBBY_FLR_1 Mixing/Well-Stirred
9 ROOM_1_FLR_3 Mixing/Well-Stirred
10 ROOM_2_FLR_3 Mixing/Well-Stirred
11 ROOM_3_MULT19_FLR_3 Mixing/Well-Stirred
12 ROOM_4_MULT19_FLR_3 Mixing/Well-Stirred
13 ROOM_5_FLR_3 Mixing/Well-Stirred
14 ROOM_6_FLR_3 Mixing/Well-Stirred
15 CORRIDOR_FLR_3 Mixing/Well-Stirred
16 ROOM_1_FLR_6 Mixing/Well-Stirred
17 ROOM_2_FLR_6 Mixing/Well-Stirred
18 ROOM_3_MULT9_FLR_6 Mixing/Well-Stirred
19 BANQUET_FLR_6 Mixing/Well-Stirred
20 DINING_FLR_6 Mixing/Well-Stirred
21 KITCHEN_FLR_6 Mixing/Well-Stirred
22 CORRIDOR_FLR_6 Mixing/Well-Stirred


AirflowNetwork Model:Control

No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation
1 NoMultizoneOrDistribution


Zone Volume Capacitance Multiplier

Sensible Heat Capacity Multiplier Moisture Capacity Multiplier Carbon Dioxide Capacity Multiplier Generic Contaminant Capacity Multiplier
1 1.000 1.000 1.000 1.000


Load Timesteps in Zone Design Calculation Averaging Window

Value
1 6


Heating Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Cooling Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Zone Sizing Information

Zone Name Load Type Calc Des Load {W} User Des Load {W} Calc Des Air Flow Rate {m3/s} User Des Air Flow Rate {m3/s} Design Day Name Date/Time of Peak Temperature at Peak {C} Humidity Ratio at Peak {kgWater/kgDryAir} Floor Area {m2} # Occupants Calc Outdoor Air Flow Rate {m3/s} Calc DOAS Heat Addition Rate {W}
1 BASEMENT Cooling 34112.29191 34112.29191 2.85787 2.85787 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 20:50:00 30.62500 6.85962E-003 1978.83018 106.49900 0.85446 0.00000
2 BASEMENT Heating 0.00000 0.00000 0.00000 0.85446 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 -5.20000 2.80840E-003 1978.83018 106.49900 0.85446 0.00000
3 RETAIL_1_FLR_1 Cooling 4647.20312 4647.20312 0.38936 0.38936 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 13:50:00 37.99167 6.87130E-003 67.07136 10.82900 7.92179E-002 0.00000
4 RETAIL_1_FLR_1 Heating 2998.71530 2998.71530 0.14819 0.14819 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 -5.20000 2.80840E-003 67.07136 10.82900 7.92179E-002 0.00000
5 RETAIL_2_FLR_1 Cooling 3392.09922 3392.09922 0.28421 0.28421 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:10:00 36.06333 6.86822E-003 77.66889 12.54000 9.17347E-002 0.00000
6 RETAIL_2_FLR_1 Heating 973.16003 973.16003 4.80952E-002 9.17347E-002 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 -5.20000 2.80840E-003 77.66889 12.54000 9.17347E-002 0.00000
7 MECH_FLR_1 Cooling 3633.18445 3633.18445 0.30434 0.30434 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 34.98000 6.86649E-003 164.24319 2.65200 0.00000 0.00000
8 MECH_FLR_1 Heating 1807.62678 1807.62678 8.93356E-002 8.93356E-002 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 -5.20000 2.80840E-003 164.24319 2.65200 0.00000 0.00000
9 STORAGE_FLR_1 Cooling 1834.88081 1834.88081 0.15371 0.15371 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:10:00 36.06333 6.86822E-003 94.75927 2.04000 5.77652E-002 0.00000
10 STORAGE_FLR_1 Heating 1082.90840 1082.90840 5.35190E-002 5.77652E-002 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 -5.20000 2.80840E-003 94.75927 2.04000 5.77652E-002 0.00000
11 LAUNDRY_FLR_1 Cooling 45235.90091 45235.90091 3.78963 3.78963 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 15:40:00 37.58000 6.87065E-003 78.03947 8.40000 0.00000 0.00000
12 LAUNDRY_FLR_1 Heating 2432.05620 2432.05620 0.12019 0.12019 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 -5.20000 2.80840E-003 78.03947 8.40000 0.00000 0.00000
13 CAFE_FLR_1 Cooling 19748.76616 19748.76616 1.65608 1.65608 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 13:50:00 37.99167 6.87130E-003 188.86188 142.30000 0.67639 0.00000
14 CAFE_FLR_1 Heating 7536.21754 7536.21754 0.37244 0.67639 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 -5.20000 2.80840E-003 188.86188 142.30000 0.67639 0.00000
15 LOBBY_FLR_1 Cooling 65273.02912 65273.02912 5.47065 5.47065 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 14:10:00 38.10000 6.87148E-003 1308.18612 422.43500 1.89399 0.00000
16 LOBBY_FLR_1 Heating 17434.44623 17434.44623 0.86164 1.89399 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 -5.20000 2.80840E-003 1308.18612 422.43500 1.89399 0.00000
17 ROOM_1_FLR_3 Cooling 11139.23111 11139.23111 1.25746 1.25746 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 16:30:00 36.80000 6.86940E-003 39.02202 1.50000 6.17350E-002 0.00000
18 ROOM_1_FLR_3 Heating 6582.01508 6582.01508 0.32718 0.32718 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 -5.20000 2.80840E-003 39.02202 1.50000 6.17350E-002 0.00000
19 ROOM_2_FLR_3 Cooling 11059.32275 11059.32275 1.24844 1.24844 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 16:40:00 36.62667 6.86912E-003 39.01745 1.50000 6.17278E-002 0.00000
20 ROOM_2_FLR_3 Heating 6575.47122 6575.47122 0.32686 0.32686 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 -5.20000 2.80840E-003 39.01745 1.50000 6.17278E-002 0.00000
21 ROOM_3_MULT19_FLR_3 Cooling 67864.35353 67864.35353 7.66073 7.66073 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 14:10:00 38.10000 6.87148E-003 24.52384 1.50000 0.83707 0.00000
22 ROOM_3_MULT19_FLR_3 Heating 37722.34327 37722.34327 1.87523 1.87523 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 -5.20000 2.80840E-003 24.52384 1.50000 0.83707 0.00000
23 ROOM_4_MULT19_FLR_3 Cooling 73041.28219 73041.28219 8.24577 8.24577 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 15:30:00 37.71000 6.87086E-003 24.53055 1.50000 0.83730 0.00000
24 ROOM_4_MULT19_FLR_3 Heating 37618.36298 37618.36298 1.87006 1.87006 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 -5.20000 2.80840E-003 24.53055 1.50000 0.83730 0.00000
25 ROOM_5_FLR_3 Cooling 9753.72736 9753.72736 1.10106 1.10106 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 10:20:00 33.81000 6.86464E-003 39.02202 1.50000 6.17350E-002 0.00000
26 ROOM_5_FLR_3 Heating 6569.75080 6569.75080 0.32658 0.32658 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 -5.20000 2.80840E-003 39.02202 1.50000 6.17350E-002 0.00000
27 ROOM_6_FLR_3 Cooling 9674.26559 9674.26559 1.09209 1.09209 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 10:10:00 33.48500 6.86412E-003 39.01745 1.50000 6.17278E-002 0.00000
28 ROOM_6_FLR_3 Heating 6563.20525 6563.20525 0.32625 0.32625 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 -5.20000 2.80840E-003 39.01745 1.50000 6.17278E-002 0.00000
29 CORRIDOR_FLR_3 Cooling 16255.55042 16255.55042 1.36182 1.36182 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 15:20:00 37.84000 6.87107E-003 389.40468 20.95700 0.47476 0.00000
30 CORRIDOR_FLR_3 Heating 10146.72041 10146.72041 0.50148 0.50148 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 -5.20000 2.80840E-003 389.40468 20.95700 0.47476 0.00000
31 ROOM_1_FLR_6 Cooling 3019.75609 3019.75609 0.34089 0.34089 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 16:30:00 36.80000 6.86940E-003 39.02202 1.50000 1.54338E-002 0.00000
32 ROOM_1_FLR_6 Heating 2054.13890 2054.13890 0.10211 0.10211 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 -5.20000 2.80840E-003 39.02202 1.50000 1.54338E-002 0.00000
33 ROOM_2_FLR_6 Cooling 2994.96289 2994.96289 0.33809 0.33809 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 16:30:00 36.80000 6.86940E-003 39.01745 1.50000 1.54319E-002 0.00000
34 ROOM_2_FLR_6 Heating 2053.31535 2053.31535 0.10207 0.10207 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 -5.20000 2.80840E-003 39.01745 1.50000 1.54319E-002 0.00000
35 ROOM_3_MULT9_FLR_6 Cooling 13659.77070 13659.77070 1.54205 1.54205 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 14:10:00 38.10000 6.87148E-003 24.53055 1.50000 9.91540E-002 0.00000
36 ROOM_3_MULT9_FLR_6 Heating 9915.79626 9915.79626 0.49291 0.49291 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 -5.20000 2.80840E-003 24.53055 1.50000 9.91540E-002 0.00000
37 BANQUET_FLR_6 Cooling 31477.21531 31477.21531 2.64042 2.64042 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 14:50:00 38.10000 6.87148E-003 331.65745 249.89600 1.18780 0.00000
38 BANQUET_FLR_6 Heating 6958.27917 6958.27917 0.34389 1.18780 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 -5.20000 2.80840E-003 331.65745 249.89600 1.18780 0.00000
39 DINING_FLR_6 Cooling 33000.63768 33000.63768 2.76816 2.76816 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 14:50:00 38.10000 6.87148E-003 331.65745 249.89600 1.18780 0.00000
40 DINING_FLR_6 Heating 7085.82715 7085.82715 0.35019 1.18780 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 23:40:00 -5.20000 2.80840E-003 331.65745 249.89600 1.18780 0.00000
41 KITCHEN_FLR_6 Cooling 31366.80312 31366.80312 2.63491 2.63491 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 12:30:00 36.93000 6.86961E-003 103.30446 22.23800 0.36735 0.00000
42 KITCHEN_FLR_6 Heating 2031.67732 2031.67732 0.10039 0.36735 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 23:30:00 -5.20000 2.80840E-003 103.30446 22.23800 0.36735 0.00000
43 CORRIDOR_FLR_6 Cooling 10077.63626 10077.63626 0.84425 0.84425 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 38.10000 6.87148E-003 412.12471 22.18000 0.12562 0.00000
44 CORRIDOR_FLR_6 Heating 7385.91129 7385.91129 0.36502 0.36502 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 23:40:00 -5.20000 2.80840E-003 412.12471 22.18000 0.12562 0.00000


System Sizing Information

System Name Load Type Peak Load Kind User Design Capacity Calc Des Air Flow Rate [m3/s] User Des Air Flow Rate [m3/s] Design Day Name Date/Time of Peak
1 VAV WITH REHEAT Cooling Sensible 664789.32 25.03918 25.03918 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 00:00:00
2 VAV WITH REHEAT Heating Sensible 173318.42 7.54149 7.54149 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00
3 FLR_3_DOAS Cooling Sensible 54460.49 22.38614 2.05125 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 00:00:00
4 FLR_3_DOAS Heating Sensible 47141.68 5.74925 2.05125 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00


Component Sizing Information

Component Type Component Name Input Field Description Value
1 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.85787
2 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.52762
3 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.99500
4 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 2.84358
5 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
6 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
7 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 7.22112E-004
8 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.13915E-004
9 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 2.84358
10 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
11 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
12 Coil:Heating:Water BASEMENT VAV BOX REHEAT COIL Design Size Rated Capacity [W] 13021.18313
13 Coil:Heating:Water BASEMENT VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.13915E-004
14 Coil:Heating:Water BASEMENT VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 271.53433
15 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.38936
16 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.13126
17 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.99500
18 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.38741
19 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.99500
20 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
21 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.90257E-003
22 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 4.17337E-005
23 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.38741
24 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
25 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
26 Coil:Heating:Water RETAIL_1_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 4770.42116
27 Coil:Heating:Water RETAIL_1_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 4.17337E-005
28 Coil:Heating:Water RETAIL_1_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 109.12167
29 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.28421
30 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.20824
31 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.99500
32 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.28279
33 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.99500
34 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
35 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.82965E-003
36 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.98272E-005
37 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.28279
38 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
39 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
40 Coil:Heating:Water RETAIL_2_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 2266.37274
41 Coil:Heating:Water RETAIL_2_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.98272E-005
42 Coil:Heating:Water RETAIL_2_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 49.18207
43 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.30434
44 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.41122
45 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.99500
46 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.30282
47 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
48 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
49 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 9.26502E-004
50 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.79252E-005
51 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.30282
52 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
53 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
54 Coil:Heating:Water MECH_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 3192.02289
55 Coil:Heating:Water MECH_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.79252E-005
56 Coil:Heating:Water MECH_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 71.41463
57 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.15371
58 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.46977
59 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.99500
60 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.15294
61 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
62 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
63 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 8.11029E-004
64 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.55907E-005
65 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.15294
66 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
67 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
68 Coil:Heating:Water STORAGE_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 1782.11531
69 Coil:Heating:Water STORAGE_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.55907E-005
70 Coil:Heating:Water STORAGE_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 40.42657
71 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 3.78963
72 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 6.22683E-002
73 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.99500
74 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 3.77068
75 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.99500
76 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
77 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.42802E-002
78 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.72061E-004
79 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 3.77068
80 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
81 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
82 Coil:Heating:Water LAUNDRY_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 19667.58846
83 Coil:Heating:Water LAUNDRY_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.72061E-004
84 Coil:Heating:Water LAUNDRY_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 413.11240
85 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.65608
86 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 8.68996E-002
87 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.99500
88 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.64780
89 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.99500
90 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
91 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 4.38437E-003
92 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.31866E-004
93 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.64780
94 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
95 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
96 Coil:Heating:Water CAFE_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 15073.10390
97 Coil:Heating:Water CAFE_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.31866E-004
98 Coil:Heating:Water CAFE_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 331.53916
99 Fan:ZoneExhaust LOBBY_FLR_1 EXHAUST FAN User-Specified Maximum Flow Rate [m3/s] 0.00000
100 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 5.47065
101 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.18222
102 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.99500
103 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 5.44330
104 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.99500
105 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
106 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.09093E-003
107 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 3.70313E-004
108 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 5.44330
109 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
110 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
111 Coil:Heating:Water LOBBY_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 42329.06585
112 Coil:Heating:Water LOBBY_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 3.70313E-004
113 Coil:Heating:Water LOBBY_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 915.98375
114 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_1_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 6.17350E-002
115 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 1.25746
116 Fan:OnOff ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 1.25746
117 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 5.75803E-005
118 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 4.76020E-004
119 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 22.69931
120 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
121 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.51776E-003
122 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
123 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
124 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 4.76020E-004
125 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 1.25746
126 Coil:Heating:Water ROOM_1_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 6581.78359
127 Coil:Heating:Water ROOM_1_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 5.75803E-005
128 Coil:Heating:Water ROOM_1_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 188.10147
129 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_2_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 6.17278E-002
130 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 1.24844
131 Fan:OnOff ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 1.24844
132 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 5.75231E-005
133 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 4.72617E-004
134 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 22.69931
135 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
136 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.51786E-003
137 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
138 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
139 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 4.72617E-004
140 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 1.24844
141 Coil:Heating:Water ROOM_2_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 6575.23994
142 Coil:Heating:Water ROOM_2_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 5.75231E-005
143 Coil:Heating:Water ROOM_2_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 187.91451
144 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_3_MULT19_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.83707
145 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT19_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 7.66073
146 Fan:OnOff ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 7.66073
147 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT19_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 3.30006E-004
148 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT19_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 2.88700E-003
149 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 22.69972
150 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
151 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.45810E-003
152 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
153 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.45810E-003
154 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 2.88700E-003
155 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 7.66073
156 Coil:Heating:Water ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 37721.68784
157 Coil:Heating:Water ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 3.30006E-004
158 Coil:Heating:Water ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 1078.03274
159 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_4_MULT19_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.83730
160 ZoneHVAC:FourPipeFanCoil ROOM_4_MULT19_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 8.24577
161 Fan:OnOff ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 8.24577
162 ZoneHVAC:FourPipeFanCoil ROOM_4_MULT19_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 3.29096E-004
163 ZoneHVAC:FourPipeFanCoil ROOM_4_MULT19_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 3.22711E-003
164 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 22.69850
165 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
166 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.65314E-003
167 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
168 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
169 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 3.22711E-003
170 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 8.24577
171 Coil:Heating:Water ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 37617.70918
172 Coil:Heating:Water ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 3.29096E-004
173 Coil:Heating:Water ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 1075.06217
174 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_5_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 6.17350E-002
175 ZoneHVAC:FourPipeFanCoil ROOM_5_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 1.10106
176 Fan:OnOff ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 1.10106
177 ZoneHVAC:FourPipeFanCoil ROOM_5_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 5.74730E-005
178 ZoneHVAC:FourPipeFanCoil ROOM_5_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 4.16975E-004
179 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 22.69931
180 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
181 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.51932E-003
182 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
183 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
184 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 4.16975E-004
185 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 1.10106
186 Coil:Heating:Water ROOM_5_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 6569.51970
187 Coil:Heating:Water ROOM_5_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 5.74730E-005
188 Coil:Heating:Water ROOM_5_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 187.75109
189 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_6_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 6.17278E-002
190 ZoneHVAC:FourPipeFanCoil ROOM_6_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 1.09209
191 Fan:OnOff ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 1.09209
192 ZoneHVAC:FourPipeFanCoil ROOM_6_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 5.74158E-005
193 ZoneHVAC:FourPipeFanCoil ROOM_6_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 4.13586E-004
194 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 22.69931
195 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
196 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.51940E-003
197 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
198 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
199 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 4.13586E-004
200 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 1.09209
201 Coil:Heating:Water ROOM_6_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 6562.97436
202 Coil:Heating:Water ROOM_6_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 5.74158E-005
203 Coil:Heating:Water ROOM_6_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 187.56409
204 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.36182
205 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.87156
206 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.99500
207 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.35501
208 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
209 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
210 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 4.37149E-004
211 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.42998E-004
212 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.35501
213 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
214 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
215 Coil:Heating:Water CORRIDOR_FLR_3 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 16345.58728
216 Coil:Heating:Water CORRIDOR_FLR_3 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.42998E-004
217 Coil:Heating:Water CORRIDOR_FLR_3 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 372.71510
218 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_1_FLR_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 1.54338E-002
219 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_6 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 0.34089
220 Fan:OnOff ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 0.34089
221 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_6 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 1.79699E-005
222 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_6 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 1.29002E-004
223 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 22.69931
224 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
225 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.51643E-003
226 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
227 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
228 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 1.29002E-004
229 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 0.34089
230 Coil:Heating:Water ROOM_1_FLR_6 FAN COIL HEATING COIL Design Size Rated Capacity [W] 2054.06943
231 Coil:Heating:Water ROOM_1_FLR_6 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 1.79699E-005
232 Coil:Heating:Water ROOM_1_FLR_6 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 58.69959
233 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_2_FLR_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 1.54319E-002
234 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_6 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 0.33809
235 Fan:OnOff ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 0.33809
236 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_6 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 1.79627E-005
237 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_6 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 1.27947E-004
238 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 22.69931
239 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
240 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.51655E-003
241 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
242 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
243 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 1.27947E-004
244 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 0.33809
245 Coil:Heating:Water ROOM_2_FLR_6 FAN COIL HEATING COIL Design Size Rated Capacity [W] 2053.24590
246 Coil:Heating:Water ROOM_2_FLR_6 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 1.79627E-005
247 Coil:Heating:Water ROOM_2_FLR_6 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 58.67607
248 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_3_MULT9_FLR_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 9.91540E-002
249 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT9_FLR_6 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 1.54205
250 Fan:OnOff ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 1.54205
251 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT9_FLR_6 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 8.67454E-005
252 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT9_FLR_6 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 5.92251E-004
253 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 22.69886
254 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
255 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.57605E-003
256 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
257 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
258 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 5.92251E-004
259 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 1.54205
260 Coil:Heating:Water ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL Design Size Rated Capacity [W] 9915.52688
261 Coil:Heating:Water ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 8.67454E-005
262 Coil:Heating:Water ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 283.35529
263 Fan:ZoneExhaust BANQUET_FLR_6 EXHAUST FAN User-Specified Maximum Flow Rate [m3/s] 0.00000
264 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.64042
265 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 9.57133E-002
266 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.99500
267 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 2.62721
268 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.99500
269 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
270 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.98064E-003
271 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.66039E-004
272 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 2.62721
273 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
274 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
275 Coil:Heating:Water BANQUET_FLR_6 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 18979.28790
276 Coil:Heating:Water BANQUET_FLR_6 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.66039E-004
277 Coil:Heating:Water BANQUET_FLR_6 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 408.03613
278 Fan:ZoneExhaust DINING_FLR_6 EXHAUST FAN User-Specified Maximum Flow Rate [m3/s] 0.00000
279 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.76816
280 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 9.12963E-002
281 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.99500
282 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 2.75432
283 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.99500
284 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
285 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 4.17322E-003
286 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.72242E-004
287 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 2.75432
288 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
289 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
290 Coil:Heating:Water DINING_FLR_6 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 19688.33737
291 Coil:Heating:Water DINING_FLR_6 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.72242E-004
292 Coil:Heating:Water DINING_FLR_6 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 422.90257
293 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.63491
294 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.71645
295 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.99500
296 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 2.62174
297 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.99500
298 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
299 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.27531E-002
300 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.22394E-004
301 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 2.62174
302 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
303 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
304 Coil:Heating:Water KITCHEN_FLR_6 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 13990.36248
305 Coil:Heating:Water KITCHEN_FLR_6 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.22394E-004
306 Coil:Heating:Water KITCHEN_FLR_6 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 294.26821
307 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.84425
308 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.37197
309 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.99500
310 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.84003
311 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.99500
312 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
313 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.02427E-003
314 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 9.82450E-005
315 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.84003
316 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
317 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
318 Coil:Heating:Water CORRIDOR_FLR_6 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 11230.01150
319 Coil:Heating:Water CORRIDOR_FLR_6 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 9.82450E-005
320 Coil:Heating:Water CORRIDOR_FLR_6 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 260.37439
321 AirLoopHVAC VAV WITH REHEAT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 25.02964
322 AirLoopHVAC VAV WITH REHEAT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 25.02964
323 AirLoopHVAC VAV WITH REHEAT Sum of Air Terminal Maximum Flow Rates [m3/s] 25.15541
324 AirLoopHVAC VAV WITH REHEAT Adjusted Heating Design Air Flow Rate [m3/s] 25.02964
325 AirLoopHVAC VAV WITH REHEAT Adjusted Cooling Design Air Flow Rate [m3/s] 25.03918
326 AirLoopHVAC VAV WITH REHEAT Adjusted Main Design Air Flow Rate [m3/s] 25.03918
327 AirLoopHVAC VAV WITH REHEAT User Heating Air Flow Ratio [] 0.30000
328 AirLoopHVAC VAV WITH REHEAT Calculated Heating Air Flow Ratio [] 0.99962
329 AirLoopHVAC FLR_3_DOAS Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 2.05132
330 AirLoopHVAC FLR_3_DOAS Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 2.05132
331 AirLoopHVAC FLR_3_DOAS Sum of Air Terminal Maximum Flow Rates [m3/s] 2.05132
332 AirLoopHVAC FLR_3_DOAS Adjusted Heating Design Air Flow Rate [m3/s] 2.05132
333 AirLoopHVAC FLR_3_DOAS Adjusted Cooling Design Air Flow Rate [m3/s] 2.05132
334 AirLoopHVAC FLR_3_DOAS Adjusted Main Design Air Flow Rate [m3/s] 2.05132
335 AirLoopHVAC FLR_3_DOAS User Heating Air Flow Ratio [] 0.30000
336 AirLoopHVAC FLR_3_DOAS Calculated Heating Air Flow Ratio [] 1.00000
337 AirLoopHVAC VAV WITH REHEAT Design Supply Air Flow Rate [m3/s] 25.03918
338 AirLoopHVAC FLR_3_DOAS Design Supply Air Flow Rate [m3/s] 2.05132
339 Controller:OutdoorAir VAV WITH REHEAT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 25.03918
340 Controller:OutdoorAir VAV WITH REHEAT_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 25.03918
341 HeatExchanger:AirToAir:SensibleAndLatent VAV WITH REHEAT OA HEAT RECOVERY Design Size Nominal Supply Air Flow Rate [m3/s] 25.03918
342 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Inlet Air Temperature [C] 38.10000
343 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
344 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Outlet Air Temperature [C] 10.69161
345 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 6.87148E-003
346 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 6.87148E-003
347 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Coil Load [W] 729331.55542
348 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Water Flow Rate [m3/s] 2.60500E-002
349 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Air Flow Rate [m3/s] 25.03918
350 Coil:Heating:Water VAV WITH REHEAT HEATING COIL Design Size Rated Capacity [W] 172635.01367
351 Coil:Heating:Water VAV WITH REHEAT HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 1.51029E-003
352 Coil:Heating:Water VAV WITH REHEAT HEATING COIL Design Size U-Factor Times Area Value [W/K] 2930.65757
353 Fan:VariableVolume VAV WITH REHEAT FAN Design Size Maximum Flow Rate [m3/s] 25.03918
354 Controller:WaterCoil VAV WITH REHEAT_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 2.60500E-002
355 Controller:WaterCoil VAV WITH REHEAT_COOLC_CONTROLLER Controller Convergence Tolerance 1.82798E-005
356 Controller:WaterCoil VAV WITH REHEAT_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 1.51029E-003
357 Controller:OutdoorAir FLR_3_DOAS_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 2.05132
358 Controller:OutdoorAir FLR_3_DOAS_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 2.05125
359 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Inlet Air Temperature [C] 38.10000
360 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
361 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Outlet Air Temperature [C] 11.79311
362 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 6.87148E-003
363 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 6.87148E-003
364 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Coil Load [W] 57348.72296
365 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Water Flow Rate [m3/s] 2.04836E-003
366 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Air Flow Rate [m3/s] 2.05132
367 Coil:Heating:Water FLR_3_DOAS HEATING COIL Design Size Rated Capacity [W] 14143.00265
368 Coil:Heating:Water FLR_3_DOAS HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 1.23729E-004
369 Coil:Heating:Water FLR_3_DOAS HEATING COIL Design Size U-Factor Times Area Value [W/K] 240.09207
370 Fan:ConstantVolume FLR_3_DOAS FAN User-Specified Maximum Flow Rate [m3/s] 2.05125
371 Controller:WaterCoil FLR_3_DOAS_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 2.04836E-003
372 Controller:WaterCoil FLR_3_DOAS_COOLC_CONTROLLER Controller Convergence Tolerance 2.32474E-004
373 Controller:WaterCoil FLR_3_DOAS_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 1.23729E-004
374 Pump:VariableSpeed COOLSYS1 PUMP SECONDARY Design Flow Rate [m3/s] 3.68409E-002
375 Pump:VariableSpeed COOLSYS1 PUMP SECONDARY Design Power Consumption [W] 7591.54435
376 PlantLoop HEATSYS1 Maximum Loop Flow Rate [m3/s] 4.24094E-003
377 PlantLoop HEATSYS1 Plant Loop Volume [m3] 0.50891
378 Pump:VariableSpeed HEATSYS1 PUMP Design Flow Rate [m3/s] 4.24094E-003
379 Pump:VariableSpeed HEATSYS1 PUMP Design Power Consumption [W] 1277.18420
380 Pump:VariableSpeed HEATSYS1 PUMP Design Minimum Flow Rate [m3/s] 0.00000
381 Boiler:HotWater HEATSYS1 BOILER Design Size Nominal Capacity [W] 484765.23309
382 Boiler:HotWater HEATSYS1 BOILER User-Specified Nominal Capacity [W] 484765.23000
383 Boiler:HotWater HEATSYS1 BOILER Design Size Design Water Flow Rate [m3/s] 4.24094E-003
384 PlantLoop COOLSYS1 Maximum Loop Flow Rate [m3/s] 3.68409E-002
385 PlantLoop COOLSYS1 Plant Loop Volume [m3] 4.42091
386 Pump:ConstantSpeed COOLSYS1 PUMP Design Flow Rate [m3/s] 3.68409E-002
387 Pump:ConstantSpeed COOLSYS1 PUMP Design Power Consumption [W] 5255.88221
388 Chiller:Electric:EIR COOLSYS1 CHILLER1 Design Size Reference Chilled Water Flow Rate [m3/s] 3.68409E-002
389 Chiller:Electric:EIR COOLSYS1 CHILLER1 Design Size Reference Capacity [W] 1031447.12728
390 Chiller:Electric:EIR COOLSYS1 CHILLER1 User-Specified Reference Capacity [W] 1032120.29000
391 Chiller:Electric:EIR COOLSYS1 CHILLER1 Design Size Reference Condenser Fluid Flow Rate [m3/s] 117.66171
392 PlantLoop SWHSYS1 Maximum Loop Flow Rate [m3/s] 3.75036E-004
393 PlantLoop SWHSYS1 Plant Loop Volume [m3] 4.50044E-002
394 Pump:ConstantSpeed SWHSYS1 PUMP Design Flow Rate [m3/s] 3.75036E-004
395 Pump:ConstantSpeed SWHSYS1 PUMP Design Power Consumption [W] 47.90688
396 WaterHeater:Mixed SWHSYS1 WATER HEATER Use Side Design Flow Rate [m3/s] 3.75036E-004


Water Heating Coil Capacity Information

Component Type Name Nominal Total Capacity {W}
1 Coil:Heating:Water BASEMENT VAV BOX REHEAT COIL 13089.25
2 Coil:Heating:Water RETAIL_1_FLR_1 VAV BOX REHEAT COIL 4793.45
3 Coil:Heating:Water RETAIL_2_FLR_1 VAV BOX REHEAT COIL 2277.90
4 Coil:Heating:Water MECH_FLR_1 VAV BOX REHEAT COIL 3207.69
5 Coil:Heating:Water STORAGE_FLR_1 VAV BOX REHEAT COIL 1790.77
6 Coil:Heating:Water LAUNDRY_FLR_1 VAV BOX REHEAT COIL 19769.87
7 Coil:Heating:Water CAFE_FLR_1 VAV BOX REHEAT COIL 15148.05
8 Coil:Heating:Water LOBBY_FLR_1 VAV BOX REHEAT COIL 42544.82
9 Coil:Heating:Water ROOM_1_FLR_3 FAN COIL HEATING COIL 7091.58
10 Coil:Heating:Water ROOM_2_FLR_3 FAN COIL HEATING COIL 7084.54
11 Coil:Heating:Water ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL 40643.29
12 Coil:Heating:Water ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL 40531.28
13 Coil:Heating:Water ROOM_5_FLR_3 FAN COIL HEATING COIL 7078.37
14 Coil:Heating:Water ROOM_6_FLR_3 FAN COIL HEATING COIL 7071.32
15 Coil:Heating:Water CORRIDOR_FLR_3 VAV BOX REHEAT COIL 16424.66
16 Coil:Heating:Water ROOM_1_FLR_6 FAN COIL HEATING COIL 2213.08
17 Coil:Heating:Water ROOM_2_FLR_6 FAN COIL HEATING COIL 2212.20
18 Coil:Heating:Water ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL 10683.09
19 Coil:Heating:Water BANQUET_FLR_6 VAV BOX REHEAT COIL 19076.44
20 Coil:Heating:Water DINING_FLR_6 VAV BOX REHEAT COIL 19789.18
21 Coil:Heating:Water KITCHEN_FLR_6 VAV BOX REHEAT COIL 14063.05
22 Coil:Heating:Water CORRIDOR_FLR_6 VAV BOX REHEAT COIL 11283.70
23 Coil:Heating:Water VAV WITH REHEAT HEATING COIL 130015.88
24 Coil:Heating:Water FLR_3_DOAS HEATING COIL 10651.46


Water Cooling Coil Capacity Information

Component Type Name Nominal Total Capacity {W} Nominal Sensible Capacity {W} Nominal Latent Capacity {W} Nominal Sensible Heat Ratio Nominal Coil UA Value {W/C} Nominal Coil Surface Area {m2}
1 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL 22320.18 16417.25 5902.93 0.74 3335.07 33.83
2 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL 22160.41 16299.61 5860.81 0.74 3311.16 33.58
3 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL 136156.72 100208.05 35948.67 0.74 20698.97 209.94
4 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL 149440.23 108787.81 40652.42 0.73 22036.97 223.51
5 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL 19553.29 14379.68 5173.61 0.74 2923.64 29.65
6 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL 19394.22 14262.62 5131.61 0.74 2899.83 29.41
7 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL 6049.56 4450.12 1599.44 0.74 904.05 9.17
8 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL 6000.01 4413.63 1586.38 0.74 896.64 9.09
9 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL 27624.78 20226.52 7398.26 0.73 4105.57 41.64
10 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL 664290.74 409499.04 254791.70 0.62 70658.82 716.66
11 Coil:Cooling:Water FLR_3_DOAS COOLING COIL 51198.70 32051.32 19147.38 0.63 5018.41 50.90


Chiller Standard Rating Information

Component Type Component Name IPLV in SI Units {W/W} IPLV in IP Units {Btu/W-h}
1 Chiller:Electric:EIR COOLSYS1 CHILLER1 3.72 12.68


Zone Surfaces

Zone Name # Surfaces
1 BASEMENT 14
2 RETAIL_1_FLR_1 8
3 RETAIL_2_FLR_1 8
4 MECH_FLR_1 7
5 STORAGE_FLR_1 8
6 LAUNDRY_FLR_1 8
7 CAFE_FLR_1 10
8 LOBBY_FLR_1 22
9 ROOM_1_FLR_3 9
10 ROOM_2_FLR_3 9
11 ROOM_3_MULT19_FLR_3 8
12 ROOM_4_MULT19_FLR_3 8
13 ROOM_5_FLR_3 9
14 ROOM_6_FLR_3 9
15 CORRIDOR_FLR_3 25
16 ROOM_1_FLR_6 9
17 ROOM_2_FLR_6 9
18 ROOM_3_MULT9_FLR_6 8
19 BANQUET_FLR_6 8
20 DINING_FLR_6 8
21 KITCHEN_FLR_6 12
22 CORRIDOR_FLR_6 19


HeatTransfer Surface

Surface Name Surface Class Base Surface Heat Transfer Algorithm Construction Nominal U (w/o film coefs) {W/m2-K} Nominal U (with film coefs) {W/m2-K} Solar Diffusing Area (Net) {m2} Area (Gross) {m2} Area (Sunlit Calc) {m2} Azimuth {deg} Tilt {deg} ~Width {m} ~Height {m} Reveal {m} ExtBoundCondition ExtConvCoeffCalc IntConvCoeffCalc SunExposure WindExposure ViewFactorToGround ViewFactorToSky ViewFactorToGround-IR ViewFactorToSky-IR #Sides
1 BASEMENT_WALL_NORTH Wall   CTF - ConductionTransferFunction BASEMENT_WALL_NORTH_CFACTOR 0.940 0.824   211.13 211.13 211.13 0.00 90.00 86.56 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
2 BASEMENT_WALL_EAST Wall   CTF - ConductionTransferFunction BASEMENT_WALL_EAST_CFACTOR 0.940 0.824   55.76 55.76 55.76 90.00 90.00 22.86 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
3 BASEMENT_WALL_SOUTH Wall   CTF - ConductionTransferFunction BASEMENT_WALL_SOUTH_CFACTOR 0.940 0.824   211.13 211.13 211.13 180.00 90.00 86.56 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
4 BASEMENT_WALL_WEST Wall   CTF - ConductionTransferFunction BASEMENT_WALL_WEST_CFACTOR 0.940 0.824   55.76 55.76 55.76 270.00 90.00 22.86 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
5 BASEMENT_FLOOR Floor   CTF - ConductionTransferFunction BASEMENT_FLOOR 2.705 1.632   1978.83 1978.83 1978.83 0.00 180.00 86.56 22.86 0.00 BASEMENT_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
6 BASEMENT_CEILING_1 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   67.07 67.07 67.07 180.00 0.00 11.58 5.79 0.00 RETAIL_1_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
7 BASEMENT_CEILING_2 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   77.67 77.67 77.67 180.00 0.00 11.58 6.71 0.00 RETAIL_2_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
8 BASEMENT_CEILING_3 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   164.24 164.24 164.24 180.00 0.00 15.85 10.36 0.00 MECH_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
9 BASEMENT_CEILING_4 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   94.76 94.76 94.76 180.00 0.00 9.14 10.36 0.00 STORAGE_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
10 BASEMENT_CEILING_5 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   78.04 78.04 78.04 180.00 0.00 4.57 17.07 0.00 LAUNDRY_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
11 BASEMENT_CEILING_6 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   188.86 188.86 188.86 180.00 0.00 32.61 5.79 0.00 CAFE_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
12 BASEMENT_CEILING_7 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   1088.56 1088.56 1088.56 180.00 0.00 32.99 32.99 0.00 LOBBY_FLR_1_FLOOR_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 6
13 BASEMENT_CEILING_8 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   219.63 219.63 219.63 90.00 0.00 14.82 14.82 0.00 LOBBY_FLR_1_FLOOR_2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 6
14 BASEMENT_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   3957.66 3957.66 3957.66 0.00 90.00 3957.66 1.00 0.00 BASEMENT_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
15 RETAIL_1_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.969 0.846   22.63 45.89 22.63 180.00 90.00 11.58 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
16 RETAIL_1_FLR_1_WALL_SOUTH_WINDOW Window RETAIL_1_FLR_1_WALL_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.4711_SHGC_0.25 N/A 2.678 No 23.26 23.26 23.26 180.00 90.00 10.92 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
17 RETAIL_1_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.969 0.846   22.95 22.95 22.95 270.00 90.00 5.79 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
18 RETAIL_1_FLR_1_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   45.89 45.89 45.89 0.00 90.00 11.58 3.96 0.00 RETAIL_2_FLR_1_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
19 RETAIL_1_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.95 22.95 22.95 90.00 90.00 5.79 3.96 0.00 LOBBY_FLR_1_WALL_2_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
20 RETAIL_1_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   67.07 67.07 67.07 0.00 180.00 11.58 5.79 0.00 BASEMENT_CEILING_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
21 RETAIL_1_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.283 0.269   67.07 67.07 67.07 180.00 0.00 11.58 5.79 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 7.62E-002 0.92 4
22 RETAIL_1_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   134.14 134.14 134.14 0.00 90.00 134.14 1.00 0.00 RETAIL_1_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
23 RETAIL_2_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.969 0.846   24.62 26.57 24.62 270.00 90.00 6.71 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
24 RETAIL_2_FLR_1_WALL_WEST_DOOR Door RETAIL_2_FLR_1_WALL_WEST CTF - ConductionTransferFunction SWINGING DOOR_CON 3.464 3.464   1.95 1.95 1.95 270.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
25 RETAIL_2_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   45.89 45.89 45.89 180.00 90.00 11.58 3.96 0.00 RETAIL_1_FLR_1_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
26 RETAIL_2_FLR_1_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   45.89 45.89 45.89 0.00 90.00 11.58 3.96 0.00 LOBBY_FLR_1_WALL_2_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
27 RETAIL_2_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.57 26.57 26.57 90.00 90.00 6.71 3.96 0.00 LOBBY_FLR_1_WALL_3_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
28 RETAIL_2_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   77.67 77.67 77.67 0.00 180.00 11.58 6.71 0.00 BASEMENT_CEILING_2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
29 RETAIL_2_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   77.67 77.67 77.67 180.00 0.00 11.58 6.71 0.00 RETAIL_2_FLR_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
30 RETAIL_2_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   155.34 155.34 155.34 0.00 90.00 155.34 1.00 0.00 RETAIL_2_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
31 MECH_FLR_1_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.969 0.846   62.80 62.80 62.80 0.00 90.00 15.85 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
32 MECH_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 90.00 90.00 10.36 3.96 0.00 STORAGE_FLR_1_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
33 MECH_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   62.80 62.80 62.80 180.00 90.00 15.85 3.96 0.00 LOBBY_FLR_1_WALL_3_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
34 MECH_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 270.00 90.00 10.36 3.96 0.00 LOBBY_FLR_1_WALL_1_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
35 MECH_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   164.24 164.24 164.24 0.00 180.00 15.85 10.36 0.00 BASEMENT_CEILING_3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
36 MECH_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   164.24 164.24 164.24 180.00 0.00 15.85 10.36 0.00 MECH_FLR_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
37 MECH_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   328.49 328.49 328.49 0.00 90.00 328.49 1.00 0.00 MECH_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
38 STORAGE_FLR_1_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.969 0.846   28.80 36.23 28.80 0.00 90.00 9.14 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
39 STORAGE_FLR_1_WALL_NORTH_ROLLDOOR Door STORAGE_FLR_1_WALL_NORTH CTF - ConductionTransferFunction OVERHEAD DOOR_CON 1.198 1.198   7.43 7.43 7.43 0.00 90.00 3.05 2.44 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
40 STORAGE_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 90.00 90.00 10.36 3.96 0.00 LOBBY_FLR_1_WALL_4_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
41 STORAGE_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   36.23 36.23 36.23 180.00 90.00 9.14 3.96 0.00 LOBBY_FLR_1_WALL_4_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
42 STORAGE_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 270.00 90.00 10.36 3.96 0.00 MECH_FLR_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
43 STORAGE_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   94.76 94.76 94.76 0.00 180.00 9.14 10.36 0.00 BASEMENT_CEILING_4 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
44 STORAGE_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   94.76 94.76 94.76 180.00 0.00 9.14 10.36 0.00 STORAGE_FLR_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
45 STORAGE_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   189.52 189.52 189.52 0.00 90.00 189.52 1.00 0.00 STORAGE_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
46 LAUNDRY_FLR_1_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.969 0.846   18.12 18.12 18.12 0.00 90.00 4.57 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
47 LAUNDRY_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.969 0.846   65.68 67.63 65.68 90.00 90.00 17.07 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
48 LAUNDRY_FLR_1_WALL_EAST_DOOR Door LAUNDRY_FLR_1_WALL_EAST CTF - ConductionTransferFunction SWINGING DOOR_CON 3.464 3.464   1.95 1.95 1.95 90.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
49 LAUNDRY_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   18.12 18.12 18.12 180.00 90.00 4.57 3.96 0.00 CAFE_FLR_1_WALL_2_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
50 LAUNDRY_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   67.63 67.63 67.63 270.00 90.00 17.07 3.96 0.00 LOBBY_FLR_1_WALL_3_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
51 LAUNDRY_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   78.04 78.04 78.04 0.00 180.00 4.57 17.07 0.00 BASEMENT_CEILING_5 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
52 LAUNDRY_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   78.04 78.04 78.04 180.00 0.00 4.57 17.07 0.00 LAUNDRY_FLR_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
53 LAUNDRY_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   156.08 156.08 156.08 0.00 90.00 156.08 1.00 0.00 LAUNDRY_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
54 CAFE_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.969 0.846   21.00 22.95 21.00 90.00 90.00 5.79 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
55 CAFE_FLR_1_WALL_EAST_DOOR Door CAFE_FLR_1_WALL_EAST CTF - ConductionTransferFunction SWINGING DOOR_CON 3.464 3.464   1.95 1.95 1.95 90.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
56 CAFE_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.969 0.846   63.73 129.23 63.73 180.00 90.00 32.61 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
57 CAFE_FLR_1_WALL_SOUTH_WINDOW Window CAFE_FLR_1_WALL_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.4711_SHGC_0.25 N/A 2.678 No 65.50 65.50 65.50 180.00 90.00 30.75 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
58 CAFE_FLR_1_WALL_1_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.11 111.11 111.11 0.00 90.00 28.04 3.96 0.00 LOBBY_FLR_1_WALL_3_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
59 CAFE_FLR_1_WALL_2_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   18.12 18.12 18.12 0.00 90.00 4.57 3.96 0.00 LAUNDRY_FLR_1_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
60 CAFE_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.95 22.95 22.95 270.00 90.00 5.79 3.96 0.00 LOBBY_FLR_1_WALL_2_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
61 CAFE_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   188.86 188.86 188.86 0.00 180.00 32.61 5.79 0.00 BASEMENT_CEILING_6 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
62 CAFE_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.283 0.269   188.86 188.86 188.86 180.00 0.00 32.61 5.79 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 3.86E-002 0.96 4
63 CAFE_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   377.72 377.72 377.72 0.00 90.00 377.72 1.00 0.00 CAFE_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
64 LOBBY_FLR_1_WALL_1_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.969 0.846   209.87 213.77 209.87 0.00 90.00 53.95 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
65 LOBBY_FLR_1_WALL_1_NORTH_DOOR1 Door LOBBY_FLR_1_WALL_1_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.464 3.464   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
66 LOBBY_FLR_1_WALL_1_NORTH_DOOR2 Door LOBBY_FLR_1_WALL_1_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.464 3.464   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
67 LOBBY_FLR_1_WALL_2_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.969 0.846   12.08 12.08 12.08 0.00 90.00 3.05 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
68 LOBBY_FLR_1_WALL_1_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.969 0.846   82.79 167.88 82.79 180.00 90.00 42.37 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
69 LOBBY_FLR_1_WALL_SOUTH_WINDOW Window LOBBY_FLR_1_WALL_1_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.4711_SHGC_0.25 N/A 2.678 No 85.08 85.08 85.08 180.00 90.00 39.95 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
70 LOBBY_FLR_1_WALL_1_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.969 0.846   41.06 41.06 41.06 270.00 90.00 10.36 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
71 LOBBY_FLR_1_WALL_2_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   45.89 45.89 45.89 180.00 90.00 11.58 3.96 0.00 RETAIL_2_FLR_1_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
72 LOBBY_FLR_1_WALL_3_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.11 111.11 111.11 180.00 90.00 28.04 3.96 0.00 CAFE_FLR_1_WALL_1_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
73 LOBBY_FLR_1_WALL_2_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.95 22.95 22.95 270.00 90.00 5.79 3.96 0.00 RETAIL_1_FLR_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
74 LOBBY_FLR_1_WALL_3_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.57 26.57 26.57 270.00 90.00 6.71 3.96 0.00 RETAIL_2_FLR_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
75 LOBBY_FLR_1_WALL_4_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 270.00 90.00 10.36 3.96 0.00 STORAGE_FLR_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
76 LOBBY_FLR_1_WALL_3_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   62.80 62.80 62.80 0.00 90.00 15.85 3.96 0.00 MECH_FLR_1_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
77 LOBBY_FLR_1_WALL_4_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   36.23 36.23 36.23 0.00 90.00 9.14 3.96 0.00 STORAGE_FLR_1_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
78 LOBBY_FLR_1_WALL_1_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 90.00 90.00 10.36 3.96 0.00 MECH_FLR_1_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
79 LOBBY_FLR_1_WALL_2_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.95 22.95 22.95 90.00 90.00 5.79 3.96 0.00 CAFE_FLR_1_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
80 LOBBY_FLR_1_WALL_3_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   67.63 67.63 67.63 90.00 90.00 17.07 3.96 0.00 LAUNDRY_FLR_1_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
81 LOBBY_FLR_1_FLOOR_1 Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   1088.56 1088.56 1088.56 180.00 180.00 32.99 32.99 0.00 BASEMENT_CEILING_7 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 6
82 LOBBY_FLR_1_FLOOR_2 Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   219.63 219.63 219.63 90.00 180.00 14.82 14.82 0.00 BASEMENT_CEILING_8 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 6
83 LOBBY_FLR_1_CEILING_1 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   1062.83 1062.83 1062.83 270.00 0.00 32.60 32.60 0.00 LOBBY_FLR_1_CEILING_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 10
84 LOBBY_FLR_1_CEILING_2 Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.283 0.269   245.35 245.35 245.35 180.00 0.00 42.37 5.79 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 4.22E-003 1.00 4
85 LOBBY_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   2616.37 2616.37 2616.37 0.00 90.00 2616.37 1.00 0.00 LOBBY_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
86 ROOM_1_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.217 1.029   9.34 13.94 9.34 180.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
87 ROOM_1_FLR_3_WALL_SOUTH_WINDOW Window ROOM_1_FLR_3_WALL_SOUTH Window5 Detailed Fenestration RESWINDOW_U_0.4711_SHGC_0.25 N/A 2.678 No 4.60 4.60 4.60 180.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
88 ROOM_1_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.217 1.029   17.43 26.01 17.43 270.00 90.00 8.54 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
89 ROOM_1_FLR_3_WALL_WEST_WINDOW Window ROOM_1_FLR_3_WALL_WEST Window5 Detailed Fenestration RESWINDOW_U_0.4711_SHGC_0.25 N/A 2.678 No 8.58 8.58 8.58 270.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
90 ROOM_1_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 0.00 90.00 4.57 3.05 0.00 ROOM_2_FLR_3_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
91 ROOM_1_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.54 3.05 0.00 CORRIDOR_FLR_3_WALL_3_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
92 ROOM_1_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   39.02 39.02 39.02 0.00 180.00 4.57 8.54 0.00 ROOM_1_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
93 ROOM_1_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   39.02 39.02 39.02 180.00 0.00 4.57 8.54 0.00 ROOM_1_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
94 ROOM_1_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.04 78.04 78.04 0.00 90.00 78.04 1.00 0.00 ROOM_1_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
95 ROOM_2_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.217 1.029   9.34 13.94 9.34 0.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
96 ROOM_2_FLR_3_WALL_NORTH_WINDOW Window ROOM_2_FLR_3_WALL_NORTH Window5 Detailed Fenestration RESWINDOW_U_0.4711_SHGC_0.25 N/A 2.678 No 4.60 4.60 4.60 0.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
97 ROOM_2_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.217 1.029   17.43 26.01 17.43 270.00 90.00 8.53 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
98 ROOM_2_FLR_3_WALL_WEST_WINDOW Window ROOM_2_FLR_3_WALL_WEST Window5 Detailed Fenestration RESWINDOW_U_0.4711_SHGC_0.25 N/A 2.678 No 8.58 8.58 8.58 270.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
99 ROOM_2_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.53 3.05 0.00 CORRIDOR_FLR_3_WALL_4_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
100 ROOM_2_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 180.00 90.00 4.57 3.05 0.00 ROOM_1_FLR_3_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
101 ROOM_2_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   39.02 39.02 39.02 0.00 180.00 4.57 8.53 0.00 ROOM_2_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
102 ROOM_2_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   39.02 39.02 39.02 180.00 0.00 4.57 8.53 0.00 ROOM_2_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
103 ROOM_2_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.03 78.03 78.03 0.00 90.00 78.03 1.00 0.00 ROOM_2_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
104 ROOM_3_MULT19_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.217 1.029   7.47 11.15 7.47 180.00 90.00 3.66 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
105 ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW Window ROOM_3_MULT19_FLR_3_WALL_SOUTH Window5 Detailed Fenestration RESWINDOW_U_0.4711_SHGC_0.25 N/A 2.678 No 3.68 3.68 3.68 180.00 90.00 3.02 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
106 ROOM_3_MULT19_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 0.00 90.00 3.66 3.05 0.00 ROOM_3_MULT19_FLR_3_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
107 ROOM_3_MULT19_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 90.00 90.00 6.71 3.05 0.00 ROOM_3_MULT19_FLR_3_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
108 ROOM_3_MULT19_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 270.00 90.00 6.71 3.05 0.00 ROOM_3_MULT19_FLR_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
109 ROOM_3_MULT19_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   24.52 24.52 24.52 0.00 180.00 3.66 6.71 0.00 ROOM_3_MULT19_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
110 ROOM_3_MULT19_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   24.52 24.52 24.52 180.00 0.00 3.66 6.71 0.00 ROOM_3_MULT19_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
111 ROOM_3_MULT19_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   49.05 49.05 49.05 0.00 90.00 49.05 1.00 0.00 ROOM_3_MULT19_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
112 ROOM_4_MULT19_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.217 1.029   7.47 11.15 7.47 0.00 90.00 3.66 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
113 ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW Window ROOM_4_MULT19_FLR_3_WALL_NORTH Window5 Detailed Fenestration RESWINDOW_U_0.4711_SHGC_0.25 N/A 2.678 No 3.68 3.68 3.68 0.00 90.00 3.02 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
114 ROOM_4_MULT19_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 90.00 90.00 6.71 3.05 0.00 ROOM_4_MULT19_FLR_3_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
115 ROOM_4_MULT19_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 180.00 90.00 3.66 3.05 0.00 ROOM_4_MULT19_FLR_3_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
116 ROOM_4_MULT19_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 270.00 90.00 6.71 3.05 0.00 ROOM_4_MULT19_FLR_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
117 ROOM_4_MULT19_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   24.53 24.53 24.53 0.00 180.00 3.66 6.71 0.00 ROOM_4_MULT19_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
118 ROOM_4_MULT19_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   24.53 24.53 24.53 180.00 0.00 3.66 6.71 0.00 ROOM_4_MULT19_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
119 ROOM_4_MULT19_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   49.06 49.06 49.06 0.00 90.00 49.06 1.00 0.00 ROOM_4_MULT19_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
120 ROOM_5_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.217 1.029   17.43 26.01 17.43 90.00 90.00 8.54 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
121 ROOM_5_FLR_3_WALL_EAST_WINDOW Window ROOM_5_FLR_3_WALL_EAST Window5 Detailed Fenestration RESWINDOW_U_0.4711_SHGC_0.25 N/A 2.678 No 8.58 8.58 8.58 90.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
122 ROOM_5_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.217 1.029   9.34 13.94 9.34 180.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
123 ROOM_5_FLR_3_WALL_SOUTH_WINDOW Window ROOM_5_FLR_3_WALL_SOUTH Window5 Detailed Fenestration RESWINDOW_U_0.4711_SHGC_0.25 N/A 2.678 No 4.60 4.60 4.60 180.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
124 ROOM_5_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 0.00 90.00 4.57 3.05 0.00 ROOM_6_FLR_3_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
125 ROOM_5_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 270.00 90.00 8.54 3.05 0.00 CORRIDOR_FLR_3_WALL_3_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
126 ROOM_5_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   39.02 39.02 39.02 0.00 180.00 4.57 8.54 0.00 ROOM_5_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
127 ROOM_5_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   39.02 39.02 39.02 180.00 0.00 4.57 8.54 0.00 ROOM_5_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
128 ROOM_5_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.04 78.04 78.04 0.00 90.00 78.04 1.00 0.00 ROOM_5_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
129 ROOM_6_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.217 1.029   9.34 13.94 9.34 0.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
130 ROOM_6_FLR_3_WALL_NORTH_WINDOW Window ROOM_6_FLR_3_WALL_NORTH Window5 Detailed Fenestration RESWINDOW_U_0.4711_SHGC_0.25 N/A 2.678 No 4.60 4.60 4.60 0.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
131 ROOM_6_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.217 1.029   17.43 26.01 17.43 90.00 90.00 8.53 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
132 ROOM_6_FLR_3_WALL_EAST_WINDOW Window ROOM_6_FLR_3_WALL_EAST Window5 Detailed Fenestration RESWINDOW_U_0.4711_SHGC_0.25 N/A 2.678 No 8.58 8.58 8.58 90.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
133 ROOM_6_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 180.00 90.00 4.57 3.05 0.00 ROOM_5_FLR_3_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
134 ROOM_6_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 270.00 90.00 8.53 3.05 0.00 CORRIDOR_FLR_3_WALL_4_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
135 ROOM_6_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   39.02 39.02 39.02 0.00 180.00 4.57 8.53 0.00 ROOM_6_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
136 ROOM_6_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   39.02 39.02 39.02 180.00 0.00 4.57 8.53 0.00 ROOM_6_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
137 ROOM_6_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.03 78.03 78.03 0.00 90.00 78.03 1.00 0.00 ROOM_6_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
138 CORRIDOR_FLR_3_WALL_1_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.265 1.063   11.83 17.65 11.83 0.00 90.00 5.79 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
139 CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW Window CORRIDOR_FLR_3_WALL_1_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.4711_SHGC_0.25 N/A 2.678 No 5.82 5.82 5.82 0.00 90.00 4.78 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
140 CORRIDOR_FLR_3_WALL_2_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.265 1.063   4.35 6.50 4.35 0.00 90.00 2.13 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
141 CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW Window CORRIDOR_FLR_3_WALL_2_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.4711_SHGC_0.25 N/A 2.678 No 2.15 2.15 2.15 0.00 90.00 1.76 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
142 CORRIDOR_FLR_3_WALL_1_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.265 1.063   4.36 6.50 4.36 180.00 90.00 2.13 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
143 CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW Window CORRIDOR_FLR_3_WALL_1_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.4711_SHGC_0.25 N/A 2.678 No 2.15 2.15 2.15 180.00 90.00 1.76 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
144 CORRIDOR_FLR_3_WALL_2_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.265 1.063   11.83 17.65 11.83 180.00 90.00 5.79 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
145 CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW Window CORRIDOR_FLR_3_WALL_2_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.4711_SHGC_0.25 N/A 2.678 No 5.82 5.82 5.82 180.00 90.00 4.78 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
146 CORRIDOR_FLR_3_WALL_3_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   211.82 211.82 211.82 0.00 90.00 69.50 3.05 0.00 CORRIDOR_FLR_3_WALL_3_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
147 CORRIDOR_FLR_3_WALL_1_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 90.00 90.00 6.71 3.05 0.00 CORRIDOR_FLR_3_WALL_1_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
148 CORRIDOR_FLR_3_WALL_2_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 90.00 90.00 6.71 3.05 0.00 CORRIDOR_FLR_3_WALL_2_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
149 CORRIDOR_FLR_3_WALL_3_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.54 3.05 0.00 ROOM_5_FLR_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
150 CORRIDOR_FLR_3_WALL_4_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.53 3.05 0.00 ROOM_6_FLR_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
151 CORRIDOR_FLR_3_WALL_3_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   211.82 211.82 211.82 180.00 90.00 69.49 3.05 0.00 CORRIDOR_FLR_3_WALL_3_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
152 CORRIDOR_FLR_3_WALL_1_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 270.00 90.00 6.71 3.05 0.00 CORRIDOR_FLR_3_WALL_1_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
153 CORRIDOR_FLR_3_WALL_2_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 270.00 90.00 6.71 3.05 0.00 CORRIDOR_FLR_3_WALL_2_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
154 CORRIDOR_FLR_3_WALL_3_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 270.00 90.00 8.54 3.05 0.00 ROOM_1_FLR_3_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
155 CORRIDOR_FLR_3_WALL_4_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 270.00 90.00 8.53 3.05 0.00 ROOM_2_FLR_3_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
156 CORRIDOR_FLR_3_FLOOR_1 Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   74.32 74.32 74.32 180.00 180.00 8.62 8.62 0.00 CORRIDOR_FLR_3_FLOOR_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 6
157 CORRIDOR_FLR_3_FLOOR_2 Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   240.77 240.77 240.77 270.00 180.00 3.66 65.84 0.00 CORRIDOR_FLR_3_FLOOR_2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
158 CORRIDOR_FLR_3_FLOOR_3 Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   74.32 74.32 74.32 90.00 180.00 8.62 8.62 0.00 CORRIDOR_FLR_3_FLOOR_3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 6
159 CORRIDOR_FLR_3_CEILING_1 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   74.32 74.32 74.32 90.00 0.00 8.62 8.62 0.00 CORRIDOR_FLR_3_CEILING_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 6
160 CORRIDOR_FLR_3_CEILING_2 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   240.77 240.77 240.77 90.00 0.00 3.66 65.84 0.00 CORRIDOR_FLR_3_CEILING_2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
161 CORRIDOR_FLR_3_CEILING_3 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.196 0.189   74.32 74.32 74.32 90.00 0.00 8.62 8.62 0.00 CORRIDOR_FLR_3_CEILING_3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 6
162 CORRIDOR_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   778.81 778.81 778.81 0.00 90.00 778.81 1.00 0.00 CORRIDOR_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
163 ROOM_1_FLR_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_TOP 1.286 1.078   9.34 13.94 9.34 180.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
164 ROOM_1_FLR_6_WALL_SOUTH_WINDOW Window ROOM_1_FLR_6_WALL_SOUTH Window5 Detailed Fenestration RESWINDOW_U_0.4711_SHGC_0.25 N/A 2.678 No 4.60 4.60 4.60 180.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
165 ROOM_1_FLR_6_WALL_WEST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_TOP 1.286 1.078   17.43 26.01 17.43 270.00 90.00 8.54 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
166 ROOM_1_FLR_6_WALL_WEST_WINDOW Window ROOM_1_FLR_6_WALL_WEST Window5 Detailed Fenestration RESWINDOW_U_0.4711_SHGC_0.25 N/A 2.678 No 8.58 8.58 8.58 270.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
167 ROOM_1_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 0.00 90.00 4.57 3.05 0.00 ROOM_2_FLR_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
168 ROOM_1_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.54 3.05 0.00 ROOM_1_FLR_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
169 ROOM_1_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   39.02 39.02 39.02 0.00 180.00 4.57 8.54 0.00 ROOM_1_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
170 ROOM_1_FLR_6_CEILING Roof   CTF - ConductionTransferFunction RES_ROOF 0.283 0.269   39.02 39.02 39.02 180.00 0.00 4.57 8.54 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
171 ROOM_1_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.04 78.04 78.04 0.00 90.00 78.04 1.00 0.00 ROOM_1_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
172 ROOM_2_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_TOP 1.286 1.078   9.34 13.94 9.34 0.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
173 ROOM_2_FLR_6_WALL_NORTH_WINDOW Window ROOM_2_FLR_6_WALL_NORTH Window5 Detailed Fenestration RESWINDOW_U_0.4711_SHGC_0.25 N/A 2.678 No 4.60 4.60 4.60 0.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
174 ROOM_2_FLR_6_WALL_WEST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_TOP 1.286 1.078   17.43 26.01 17.43 270.00 90.00 8.53 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
175 ROOM_2_FLR_6_WALL_WEST_WINDOW Window ROOM_2_FLR_6_WALL_WEST Window5 Detailed Fenestration RESWINDOW_U_0.4711_SHGC_0.25 N/A 2.678 No 8.58 8.58 8.58 270.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
176 ROOM_2_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.53 3.05 0.00 ROOM_2_FLR_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
177 ROOM_2_FLR_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 180.00 90.00 4.57 3.05 0.00 ROOM_1_FLR_6_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
178 ROOM_2_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   39.02 39.02 39.02 0.00 180.00 4.57 8.53 0.00 ROOM_2_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
179 ROOM_2_FLR_6_CEILING Roof   CTF - ConductionTransferFunction RES_ROOF 0.283 0.269   39.02 39.02 39.02 180.00 0.00 4.57 8.53 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
180 ROOM_2_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.03 78.03 78.03 0.00 90.00 78.03 1.00 0.00 ROOM_2_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
181 ROOM_3_MULT9_FLR_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_TOP 1.286 1.078   13.70 20.44 13.70 180.00 90.00 6.71 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
182 ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW Window ROOM_3_MULT9_FLR_6_WALL_SOUTH Window5 Detailed Fenestration RESWINDOW_U_0.4711_SHGC_0.25 N/A 2.678 No 6.74 6.74 6.74 180.00 90.00 5.53 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
183 ROOM_3_MULT9_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 0.00 90.00 6.71 3.05 0.00 ROOM_3_MULT9_FLR_6_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
184 ROOM_3_MULT9_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 90.00 90.00 3.66 3.05 0.00 ROOM_3_MULT9_FLR_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
185 ROOM_3_MULT9_FLR_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 270.00 90.00 3.66 3.05 0.00 ROOM_3_MULT9_FLR_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
186 ROOM_3_MULT9_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   24.53 24.53 24.53 0.00 180.00 6.71 3.66 0.00 ROOM_3_MULT9_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
187 ROOM_3_MULT9_FLR_6_CEILING Roof   CTF - ConductionTransferFunction RES_ROOF 0.283 0.269   24.53 24.53 24.53 180.00 0.00 6.71 3.66 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
188 ROOM_3_MULT9_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   49.06 49.06 49.06 0.00 90.00 49.06 1.00 0.00 ROOM_3_MULT9_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
189 BANQUET_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.335 1.112   65.36 97.55 65.36 0.00 90.00 32.00 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
190 BANQUET_FLR_6_WALL_NORTH_WINDOW Window BANQUET_FLR_6_WALL_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.4711_SHGC_0.25 N/A 2.678 No 32.19 32.19 32.19 0.00 90.00 26.40 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
191 BANQUET_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 90.00 90.00 10.36 3.05 0.00 CORRIDOR_FLR_6_WALL_3_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
192 BANQUET_FLR_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   97.55 97.55 97.55 180.00 90.00 32.00 3.05 0.00 CORRIDOR_FLR_6_WALL_3_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
193 BANQUET_FLR_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 270.00 90.00 10.36 3.05 0.00 CORRIDOR_FLR_6_WALL_1_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
194 BANQUET_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   331.66 331.66 331.66 0.00 180.00 32.00 10.36 0.00 BANQUET_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
195 BANQUET_FLR_6_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.283 0.269   331.66 331.66 331.66 180.00 0.00 32.00 10.36 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
196 BANQUET_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   663.31 663.31 663.31 0.00 90.00 663.31 1.00 0.00 BANQUET_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
197 DINING_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.335 1.112   65.36 97.55 65.36 0.00 90.00 32.00 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
198 DINING_FLR_6_WALL_NORTH_WINDOW Window DINING_FLR_6_WALL_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.4711_SHGC_0.25 N/A 2.678 No 32.19 32.19 32.19 0.00 90.00 26.40 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
199 DINING_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 90.00 90.00 10.36 3.05 0.00 KITCHEN_FLR_6_WALL_2_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
200 DINING_FLR_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   97.55 97.55 97.55 180.00 90.00 32.00 3.05 0.00 DINING_FLR_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
201 DINING_FLR_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 270.00 90.00 10.36 3.05 0.00 CORRIDOR_FLR_6_WALL_2_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
202 DINING_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   331.66 331.66 331.66 0.00 180.00 32.00 10.36 0.00 DINING_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
203 DINING_FLR_6_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.283 0.269   331.66 331.66 331.66 180.00 0.00 32.00 10.36 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
204 DINING_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   663.31 663.31 663.31 0.00 90.00 663.31 1.00 0.00 DINING_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
205 KITCHEN_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.335 1.112   16.77 21.37 16.77 0.00 90.00 7.01 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
206 KITCHEN_FLR_6_WALL_NORTH_WINDOW Window KITCHEN_FLR_6_WALL_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.4711_SHGC_0.25 N/A 2.678 No 4.60 4.60 4.60 0.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
207 KITCHEN_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.335 1.112   34.86 52.03 34.86 90.00 90.00 17.07 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
208 KITCHEN_FLR_6_WALL_EAST_WINDOW Window KITCHEN_FLR_6_WALL_EAST Window5 Detailed Fenestration NONRESWINDOW_U_0.4711_SHGC_0.25 N/A 2.678 No 17.17 17.17 17.17 90.00 90.00 14.08 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
209 KITCHEN_FLR_6_WALL_1_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.335 1.112   9.34 13.94 9.34 180.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
210 KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW Window KITCHEN_FLR_6_WALL_1_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.4711_SHGC_0.25 N/A 2.678 No 4.60 4.60 4.60 180.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
211 KITCHEN_FLR_6_WALL_2_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 180.00 90.00 2.44 3.05 0.00 KITCHEN_FLR_6_WALL_2_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
212 KITCHEN_FLR_6_WALL_1_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 270.00 90.00 6.71 3.05 0.00 CORRIDOR_FLR_6_WALL_3_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
213 KITCHEN_FLR_6_WALL_2_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 270.00 90.00 10.36 3.05 0.00 DINING_FLR_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
214 KITCHEN_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   103.30 103.30 103.30 180.00 180.00 10.16 10.16 0.00 KITCHEN_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 6
215 KITCHEN_FLR_6_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.283 0.269   103.30 103.30 103.30 270.00 0.00 10.16 10.16 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 6
216 KITCHEN_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   206.61 206.61 206.61 0.00 90.00 206.61 1.00 0.00 KITCHEN_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
217 CORRIDOR_FLR_6_WALL_1_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.335 1.112   11.83 17.65 11.83 0.00 90.00 5.79 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
218 CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW Window CORRIDOR_FLR_6_WALL_1_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.4711_SHGC_0.25 N/A 2.678 No 5.82 5.82 5.82 0.00 90.00 4.78 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
219 CORRIDOR_FLR_6_WALL_2_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.335 1.112   10.58 15.79 10.58 0.00 90.00 5.18 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
220 CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW Window CORRIDOR_FLR_6_WALL_2_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.4711_SHGC_0.25 N/A 2.678 No 5.21 5.21 5.21 0.00 90.00 4.27 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
221 CORRIDOR_FLR_6_WALL_2_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.335 1.112   34.86 52.03 34.86 180.00 90.00 17.07 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
222 CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW Window CORRIDOR_FLR_6_WALL_2_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.4711_SHGC_0.25 N/A 2.678 No 17.17 17.17 17.17 180.00 90.00 14.08 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
223 CORRIDOR_FLR_6_WALL_3_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   97.55 97.55 97.55 0.00 90.00 32.00 3.05 0.00 BANQUET_FLR_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
224 CORRIDOR_FLR_6_WALL_4_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   104.98 104.98 104.98 0.00 90.00 34.44 3.05 0.00 CORRIDOR_FLR_6_WALL_4_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
225 CORRIDOR_FLR_6_WALL_1_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   183.95 183.95 183.95 180.00 90.00 60.35 3.05 0.00 CORRIDOR_FLR_6_WALL_1_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
226 CORRIDOR_FLR_6_WALL_1_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 270.00 90.00 3.66 3.05 0.00 CORRIDOR_FLR_6_WALL_1_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
227 CORRIDOR_FLR_6_WALL_2_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   40.88 40.88 40.88 270.00 90.00 13.41 3.05 0.00 CORRIDOR_FLR_6_WALL_2_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
228 CORRIDOR_FLR_6_WALL_3_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 270.00 90.00 10.36 3.05 0.00 BANQUET_FLR_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
229 CORRIDOR_FLR_6_WALL_1_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 90.00 90.00 10.36 3.05 0.00 BANQUET_FLR_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
230 CORRIDOR_FLR_6_WALL_2_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 90.00 90.00 10.36 3.05 0.00 DINING_FLR_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
231 CORRIDOR_FLR_6_WALL_3_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 90.00 90.00 6.71 3.05 0.00 KITCHEN_FLR_6_WALL_1_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
232 CORRIDOR_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.196 0.187   412.12 412.12 412.12 180.00 180.00 20.30 20.30 0.00 CORRIDOR_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 12
233 CORRIDOR_FLR_6_CEILING_1 Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.283 0.269   244.71 244.71 244.71 90.00 0.00 15.64 15.64 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 8
234 CORRIDOR_FLR_6_CEILING_2 Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.283 0.269   167.42 167.42 167.42 270.00 0.00 12.94 12.94 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 6
235 CORRIDOR_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   824.25 824.25 824.25 0.00 90.00 824.25 1.00 0.00 CORRIDOR_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0


Environment

Environment Name Environment Type Start Date End Date Start DayOfWeek Duration {#days} Source:Start DayOfWeek Use Daylight Saving Use Holidays Apply Weekend Holiday Rule Use Rain Values Use Snow Values Sky Temperature Model
1 RUNPERIOD 1 WeatherFileRunPeriod 01/01/2017 12/31/2017 Sunday 365 Use RunPeriod Specified Day No No No Yes Yes Clark and Allen


Environment:Special Days

Special Day Name Special Day Type Source Start Date Duration {#days}
1 NEW YEARS DAY Holiday InputFile 01/01 1Environment:Special Days


Environment:Daylight Saving

Daylight Saving Indicator Source Start Date End Date
1 Yes InputFile 03/12 11/05


Tabular Report

Style Unit Conversion
1 Commaandhtml commaandhtml


Warmup Convergence Information

Zone Name Environment Type/Name Average Warmup Temperature Difference {deltaC} Std Dev Warmup Temperature Difference {deltaC} Max Temperature Pass/Fail Convergence Min Temperature Pass/Fail Convergence Average Warmup Load Difference {W} Std Dev Warmup Load Difference {W} Heating Load Pass/Fail Convergence Cooling Load Pass/Fail Convergence
1 BASEMENT RunPeriod: RUNPERIOD 1 7.1627346445E-003 1.4449468564E-002 Pass Pass 1.1619650630E-002 2.9112068282E-002 Pass Pass
2 RETAIL_1_FLR_1 RunPeriod: RUNPERIOD 1 2.4736730873E-002 4.8690502093E-002 Pass Pass 5.6460169280E-002 6.9303574537E-002 Pass Pass
3 RETAIL_2_FLR_1 RunPeriod: RUNPERIOD 1 2.3940668790E-003 4.9803937829E-003 Pass Pass 1.6977095553E-002 3.2129661096E-002 Pass Pass
4 MECH_FLR_1 RunPeriod: RUNPERIOD 1 1.0242988365E-003 6.9923606014E-004 Pass Pass 3.2855212718E-002 5.5999379557E-002 Pass Pass
5 STORAGE_FLR_1 RunPeriod: RUNPERIOD 1 8.7282243137E-004 6.3516588787E-004 Pass Pass 7.4340884512E-002 0.1154057318 Pass Pass
6 LAUNDRY_FLR_1 RunPeriod: RUNPERIOD 1 4.4190340268E-002 0.1389775826 Pass Pass 1.8935268876E-002 5.4653405611E-002 Pass Pass
7 CAFE_FLR_1 RunPeriod: RUNPERIOD 1 3.0136387400E-002 5.8388724095E-002 Pass Pass 2.0754208596E-002 3.8747776313E-002 Pass Pass
8 LOBBY_FLR_1 RunPeriod: RUNPERIOD 1 8.1335662886E-003 1.8033214554E-002 Pass Pass 1.6696811263E-002 3.3467330392E-002 Pass Pass
9 ROOM_1_FLR_3 RunPeriod: RUNPERIOD 1 5.3661216840E-002 0.2000201130 Pass Pass 0.4819856793 3.6146147120 Pass Pass
10 ROOM_2_FLR_3 RunPeriod: RUNPERIOD 1 5.1082002829E-002 0.1761398477 Pass Pass 0.1696866177 0.4203025781 Pass Pass
11 ROOM_3_MULT19_FLR_3 RunPeriod: RUNPERIOD 1 1.3850449947E-002 3.2132994685E-002 Pass Pass 3.3312175590E-002 5.3066114426E-002 Pass Pass
12 ROOM_4_MULT19_FLR_3 RunPeriod: RUNPERIOD 1 2.4810449373E-002 9.2982555616E-002 Pass Pass 8.9444127489E-002 0.1953989576 Pass Pass
13 ROOM_5_FLR_3 RunPeriod: RUNPERIOD 1 4.9184547321E-002 0.1764802445 Pass Pass 0.1418091318 0.4616331697 Pass Pass
14 ROOM_6_FLR_3 RunPeriod: RUNPERIOD 1 3.0523022621E-002 9.9645059761E-002 Pass Pass 0.1186581741 0.2550942098 Pass Pass
15 CORRIDOR_FLR_3 RunPeriod: RUNPERIOD 1 5.4838967491E-004 4.0578428985E-004 Pass Pass 2.5094880089E-002 3.7709929420E-002 Pass Pass
16 ROOM_1_FLR_6 RunPeriod: RUNPERIOD 1 5.9019358353E-002 0.2099447949 Pass Pass 0.1974961534 0.4970917513 Pass Pass
17 ROOM_2_FLR_6 RunPeriod: RUNPERIOD 1 6.3257041607E-002 0.2023234723 Pass Pass 0.1913413924 0.4921483791 Pass Pass
18 ROOM_3_MULT9_FLR_6 RunPeriod: RUNPERIOD 1 7.0715954293E-002 0.2852772487 Pass Pass 0.1895965153 0.5345775664 Pass Pass
19 BANQUET_FLR_6 RunPeriod: RUNPERIOD 1 2.2303176771E-002 6.5571281807E-002 Pass Pass 1.2582857422E-002 3.5054548427E-002 Pass Pass
20 DINING_FLR_6 RunPeriod: RUNPERIOD 1 2.5636486836E-002 6.6436541233E-002 Pass Pass 1.1524388879E-002 3.0304693184E-002 Pass Pass
21 KITCHEN_FLR_6 RunPeriod: RUNPERIOD 1 6.7022397065E-002 0.1170573512 Pass Pass 1.7664089631E-002 3.2757295799E-002 Pass Pass
22 CORRIDOR_FLR_6 RunPeriod: RUNPERIOD 1 1.3351042201E-003 9.1295304683E-004 Pass Pass 0.1709104280 0.4643691168 Pass Pass



Table of Contents

Report: Annual Heat Emissions Summary

For: Entire Facility

Timestamp: 2023-10-16 08:58:10

Heat Emission by Components

Envelope Convection Zone Exfiltration Zone Exhaust Air HVAC Relief Air HVAC Reject Heat Total
Heat Emissions [GJ] 3180.47 66.95 382.79 3828.73 9975.92 17434.87



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2023-10-16 08:58:10

SizingPeriod:DesignDay

Maximum Dry Bulb [C] Daily Temperature Range [deltaC] Humidity Value Humidity Type Wind Speed [m/s] Wind Direction
EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB -5.20 0.00 -5.20 Wetbulb [C] 2.20 20.00
EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 38.10 13.00 18.10 Wetbulb [C] 3.90 280.00


Monthly Precipitation Summary

Monthly Total Precipitation from .epw [mm] Monthly Total Hours of Rain from .epw Monthly Total Precipitation in Site:Precipitation [mm] Monthly Total Roof Irrigation Depth [mm] Monthly Total Rain Collection Volume [m3]
Jan 3.00 6      
Feb 3.00 4      
Mar 0.00 0      
Apr 0.00 0      
May 0.00 0      
Jun 18.00 7      
Jul 27.00 16      
Aug 41.00 15      
Sep 0.00 0      
Oct 23.00 18      
Nov 0.00 0      
Dec 7.00 7      


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2023-10-16 08:58:10

Opaque Exterior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
BASEMENT_WALL_NORTH BASEMENT_WALL_NORTH_CFACTOR 1.00 0.845 0.940 211.13 211.13 0.00 90.00 N
BASEMENT_WALL_EAST BASEMENT_WALL_EAST_CFACTOR 1.00 0.845 0.940 55.76 55.76 90.00 90.00 E
BASEMENT_WALL_SOUTH BASEMENT_WALL_SOUTH_CFACTOR 1.00 0.845 0.940 211.13 211.13 180.00 90.00 S
BASEMENT_WALL_WEST BASEMENT_WALL_WEST_CFACTOR 1.00 0.845 0.940 55.76 55.76 270.00 90.00 W
RETAIL_1_FLR_1_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 0.846 0.969 45.89 22.63 180.00 90.00 S
RETAIL_1_FLR_1_WALL_WEST NONRES_EXT_WALL_GRD 0.30 0.846 0.969 22.95 22.95 270.00 90.00 W
RETAIL_1_FLR_1_CEILING NONRES_ROOF 0.55 0.273 0.283 67.07 67.07 180.00 0.00  
RETAIL_2_FLR_1_WALL_WEST NONRES_EXT_WALL_GRD 0.30 0.846 0.969 26.57 24.62 270.00 90.00 W
MECH_FLR_1_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 0.846 0.969 62.80 62.80 0.00 90.00 N
STORAGE_FLR_1_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 0.846 0.969 36.23 28.80 0.00 90.00 N
LAUNDRY_FLR_1_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 0.846 0.969 18.12 18.12 0.00 90.00 N
LAUNDRY_FLR_1_WALL_EAST NONRES_EXT_WALL_GRD 0.30 0.846 0.969 67.63 65.68 90.00 90.00 E
CAFE_FLR_1_WALL_EAST NONRES_EXT_WALL_GRD 0.30 0.846 0.969 22.95 21.00 90.00 90.00 E
CAFE_FLR_1_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 0.846 0.969 129.23 63.73 180.00 90.00 S
CAFE_FLR_1_CEILING NONRES_ROOF 0.55 0.273 0.283 188.86 188.86 180.00 0.00  
LOBBY_FLR_1_WALL_1_NORTH NONRES_EXT_WALL_GRD 0.30 0.846 0.969 213.77 209.87 0.00 90.00 N
LOBBY_FLR_1_WALL_2_NORTH NONRES_EXT_WALL_GRD 0.30 0.846 0.969 12.08 12.08 0.00 90.00 N
LOBBY_FLR_1_WALL_1_SOUTH NONRES_EXT_WALL_GRD 0.30 0.846 0.969 167.88 82.79 180.00 90.00 S
LOBBY_FLR_1_WALL_1_WEST NONRES_EXT_WALL_GRD 0.30 0.846 0.969 41.06 41.06 270.00 90.00 W
LOBBY_FLR_1_CEILING_2 NONRES_ROOF 0.55 0.273 0.283 245.35 245.35 180.00 0.00  
ROOM_1_FLR_3_WALL_SOUTH RES_EXT_WALL_MID 0.30 1.029 1.217 55.74 37.35 180.00 90.00 S
ROOM_1_FLR_3_WALL_WEST RES_EXT_WALL_MID 0.30 1.029 1.217 104.06 69.72 270.00 90.00 W
ROOM_2_FLR_3_WALL_NORTH RES_EXT_WALL_MID 0.30 1.029 1.217 55.74 37.35 0.00 90.00 N
ROOM_2_FLR_3_WALL_WEST RES_EXT_WALL_MID 0.30 1.029 1.217 104.05 69.71 270.00 90.00 W
ROOM_3_MULT19_FLR_3_WALL_SOUTH RES_EXT_WALL_MID 0.30 1.029 1.217 847.14 567.58 180.00 90.00 S
ROOM_4_MULT19_FLR_3_WALL_NORTH RES_EXT_WALL_MID 0.30 1.029 1.217 847.37 567.71 0.00 90.00 N
ROOM_5_FLR_3_WALL_EAST RES_EXT_WALL_MID 0.30 1.029 1.217 104.06 69.72 90.00 90.00 E
ROOM_5_FLR_3_WALL_SOUTH RES_EXT_WALL_MID 0.30 1.029 1.217 55.74 37.35 180.00 90.00 S
ROOM_6_FLR_3_WALL_NORTH RES_EXT_WALL_MID 0.30 1.029 1.217 55.74 37.35 0.00 90.00 N
ROOM_6_FLR_3_WALL_EAST RES_EXT_WALL_MID 0.30 1.029 1.217 104.05 69.71 90.00 90.00 E
CORRIDOR_FLR_3_WALL_1_NORTH NONRES_EXT_WALL_MID 0.30 1.063 1.265 70.60 47.31 0.00 90.00 N
CORRIDOR_FLR_3_WALL_2_NORTH NONRES_EXT_WALL_MID 0.30 1.063 1.265 26.01 17.42 0.00 90.00 N
CORRIDOR_FLR_3_WALL_1_SOUTH NONRES_EXT_WALL_MID 0.30 1.063 1.265 26.02 17.43 180.00 90.00 S
CORRIDOR_FLR_3_WALL_2_SOUTH NONRES_EXT_WALL_MID 0.30 1.063 1.265 70.60 47.31 180.00 90.00 S
ROOM_1_FLR_6_WALL_SOUTH RES_EXT_WALL_TOP 0.30 1.078 1.286 13.94 9.34 180.00 90.00 S
ROOM_1_FLR_6_WALL_WEST RES_EXT_WALL_TOP 0.30 1.078 1.286 26.01 17.43 270.00 90.00 W
ROOM_1_FLR_6_CEILING RES_ROOF 0.55 0.273 0.283 39.02 39.02 180.00 0.00  
ROOM_2_FLR_6_WALL_NORTH RES_EXT_WALL_TOP 0.30 1.078 1.286 13.94 9.34 0.00 90.00 N
ROOM_2_FLR_6_WALL_WEST RES_EXT_WALL_TOP 0.30 1.078 1.286 26.01 17.43 270.00 90.00 W
ROOM_2_FLR_6_CEILING RES_ROOF 0.55 0.273 0.283 39.02 39.02 180.00 0.00  
ROOM_3_MULT9_FLR_6_WALL_SOUTH RES_EXT_WALL_TOP 0.30 1.078 1.286 183.96 123.26 180.00 90.00 S
ROOM_3_MULT9_FLR_6_CEILING RES_ROOF 0.55 0.273 0.283 220.77 220.77 180.00 0.00  
BANQUET_FLR_6_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 1.112 1.335 97.55 65.36 0.00 90.00 N
BANQUET_FLR_6_CEILING NONRES_ROOF 0.55 0.273 0.283 331.66 331.66 180.00 0.00  
DINING_FLR_6_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 1.112 1.335 97.55 65.36 0.00 90.00 N
DINING_FLR_6_CEILING NONRES_ROOF 0.55 0.273 0.283 331.66 331.66 180.00 0.00  
KITCHEN_FLR_6_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 1.112 1.335 21.37 16.77 0.00 90.00 N
KITCHEN_FLR_6_WALL_EAST NONRES_EXT_WALL_TOP 0.30 1.112 1.335 52.03 34.86 90.00 90.00 E
KITCHEN_FLR_6_WALL_1_SOUTH NONRES_EXT_WALL_TOP 0.30 1.112 1.335 13.94 9.34 180.00 90.00 S
KITCHEN_FLR_6_CEILING NONRES_ROOF 0.55 0.273 0.283 103.30 103.30 270.00 0.00  
CORRIDOR_FLR_6_WALL_1_NORTH NONRES_EXT_WALL_TOP 0.30 1.112 1.335 17.65 11.83 0.00 90.00 N
CORRIDOR_FLR_6_WALL_2_NORTH NONRES_EXT_WALL_TOP 0.30 1.112 1.335 15.79 10.58 0.00 90.00 N
CORRIDOR_FLR_6_WALL_2_SOUTH NONRES_EXT_WALL_TOP 0.30 1.112 1.335 52.03 34.86 180.00 90.00 S
CORRIDOR_FLR_6_CEILING_1 NONRES_ROOF 0.55 0.273 0.283 244.71 244.71 90.00 0.00  
CORRIDOR_FLR_6_CEILING_2 NONRES_ROOF 0.55 0.273 0.283 167.42 167.42 270.00 0.00  


Opaque Interior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
BASEMENT_FLOOR BASEMENT_FLOOR 0.30 1.441 2.705 1978.83 1978.83 0.00 180.00  
BASEMENT_CEILING_1 NONRES_FLOOR_CEILING 0.30 0.186 0.196 67.07 67.07 180.00 0.00  
BASEMENT_CEILING_2 NONRES_FLOOR_CEILING 0.30 0.186 0.196 77.67 77.67 180.00 0.00  
BASEMENT_CEILING_3 NONRES_FLOOR_CEILING 0.30 0.186 0.196 164.24 164.24 180.00 0.00  
BASEMENT_CEILING_4 NONRES_FLOOR_CEILING 0.30 0.186 0.196 94.76 94.76 180.00 0.00  
BASEMENT_CEILING_5 NONRES_FLOOR_CEILING 0.30 0.186 0.196 78.04 78.04 180.00 0.00  
BASEMENT_CEILING_6 NONRES_FLOOR_CEILING 0.30 0.186 0.196 188.86 188.86 180.00 0.00  
BASEMENT_CEILING_7 NONRES_FLOOR_CEILING 0.30 0.186 0.196 1088.56 1088.56 180.00 0.00  
BASEMENT_CEILING_8 NONRES_FLOOR_CEILING 0.30 0.186 0.196 219.63 219.63 90.00 0.00  
RETAIL_1_FLR_1_WALL_NORTH INT_WALL 0.30 2.511 6.299 45.89 45.89 0.00 90.00 N
RETAIL_1_FLR_1_WALL_EAST INT_WALL 0.30 2.511 6.299 22.95 22.95 90.00 90.00 E
RETAIL_1_FLR_1_FLOOR NONRES_FLOOR 0.30 0.186 0.196 67.07 67.07 0.00 180.00  
RETAIL_2_FLR_1_WALL_SOUTH INT_WALL 0.30 2.511 6.299 45.89 45.89 180.00 90.00 S
RETAIL_2_FLR_1_WALL_NORTH INT_WALL 0.30 2.511 6.299 45.89 45.89 0.00 90.00 N
RETAIL_2_FLR_1_WALL_EAST INT_WALL 0.30 2.511 6.299 26.57 26.57 90.00 90.00 E
RETAIL_2_FLR_1_FLOOR NONRES_FLOOR 0.30 0.186 0.196 77.67 77.67 0.00 180.00  
RETAIL_2_FLR_1_CEILING NONRES_FLOOR_CEILING 0.30 0.188 0.196 77.67 77.67 180.00 0.00  
MECH_FLR_1_WALL_EAST INT_WALL 0.30 2.511 6.299 41.06 41.06 90.00 90.00 E
MECH_FLR_1_WALL_SOUTH INT_WALL 0.30 2.511 6.299 62.80 62.80 180.00 90.00 S
MECH_FLR_1_WALL_WEST INT_WALL 0.30 2.511 6.299 41.06 41.06 270.00 90.00 W
MECH_FLR_1_FLOOR NONRES_FLOOR 0.30 0.186 0.196 164.24 164.24 0.00 180.00  
MECH_FLR_1_CEILING NONRES_FLOOR_CEILING 0.30 0.188 0.196 164.24 164.24 180.00 0.00  
STORAGE_FLR_1_WALL_EAST INT_WALL 0.30 2.511 6.299 41.06 41.06 90.00 90.00 E
STORAGE_FLR_1_WALL_SOUTH INT_WALL 0.30 2.511 6.299 36.23 36.23 180.00 90.00 S
STORAGE_FLR_1_WALL_WEST INT_WALL 0.30 2.511 6.299 41.06 41.06 270.00 90.00 W
STORAGE_FLR_1_FLOOR NONRES_FLOOR 0.30 0.186 0.196 94.76 94.76 0.00 180.00  
STORAGE_FLR_1_CEILING NONRES_FLOOR_CEILING 0.30 0.188 0.196 94.76 94.76 180.00 0.00  
LAUNDRY_FLR_1_WALL_SOUTH INT_WALL 0.30 2.511 6.299 18.12 18.12 180.00 90.00 S
LAUNDRY_FLR_1_WALL_WEST INT_WALL 0.30 2.511 6.299 67.63 67.63 270.00 90.00 W
LAUNDRY_FLR_1_FLOOR NONRES_FLOOR 0.30 0.186 0.196 78.04 78.04 0.00 180.00  
LAUNDRY_FLR_1_CEILING NONRES_FLOOR_CEILING 0.30 0.188 0.196 78.04 78.04 180.00 0.00  
CAFE_FLR_1_WALL_1_NORTH INT_WALL 0.30 2.511 6.299 111.11 111.11 0.00 90.00 N
CAFE_FLR_1_WALL_2_NORTH INT_WALL 0.30 2.511 6.299 18.12 18.12 0.00 90.00 N
CAFE_FLR_1_WALL_WEST INT_WALL 0.30 2.511 6.299 22.95 22.95 270.00 90.00 W
CAFE_FLR_1_FLOOR NONRES_FLOOR 0.30 0.186 0.196 188.86 188.86 0.00 180.00  
LOBBY_FLR_1_WALL_2_SOUTH INT_WALL 0.30 2.511 6.299 45.89 45.89 180.00 90.00 S
LOBBY_FLR_1_WALL_3_SOUTH INT_WALL 0.30 2.511 6.299 111.11 111.11 180.00 90.00 S
LOBBY_FLR_1_WALL_2_WEST INT_WALL 0.30 2.511 6.299 22.95 22.95 270.00 90.00 W
LOBBY_FLR_1_WALL_3_WEST INT_WALL 0.30 2.511 6.299 26.57 26.57 270.00 90.00 W
LOBBY_FLR_1_WALL_4_WEST INT_WALL 0.30 2.511 6.299 41.06 41.06 270.00 90.00 W
LOBBY_FLR_1_WALL_3_NORTH INT_WALL 0.30 2.511 6.299 62.80 62.80 0.00 90.00 N
LOBBY_FLR_1_WALL_4_NORTH INT_WALL 0.30 2.511 6.299 36.23 36.23 0.00 90.00 N
LOBBY_FLR_1_WALL_1_EAST INT_WALL 0.30 2.511 6.299 41.06 41.06 90.00 90.00 E
LOBBY_FLR_1_WALL_2_EAST INT_WALL 0.30 2.511 6.299 22.95 22.95 90.00 90.00 E
LOBBY_FLR_1_WALL_3_EAST INT_WALL 0.30 2.511 6.299 67.63 67.63 90.00 90.00 E
LOBBY_FLR_1_FLOOR_1 NONRES_FLOOR 0.30 0.186 0.196 1088.56 1088.56 180.00 180.00  
LOBBY_FLR_1_FLOOR_2 NONRES_FLOOR 0.30 0.186 0.196 219.63 219.63 90.00 180.00  
LOBBY_FLR_1_CEILING_1 NONRES_FLOOR_CEILING 0.30 0.188 0.196 1062.83 1062.83 270.00 0.00  
ROOM_1_FLR_3_WALL_NORTH INT_WALL 0.30 2.511 6.299 55.74 55.74 0.00 90.00 N
ROOM_1_FLR_3_WALL_EAST INT_WALL 0.30 2.511 6.299 104.06 104.06 90.00 90.00 E
ROOM_1_FLR_3_FLOOR NONRES_FLOOR 0.30 0.185 0.196 156.09 156.09 0.00 180.00  
ROOM_1_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 0.188 0.196 156.09 156.09 180.00 0.00  
ROOM_2_FLR_3_WALL_EAST INT_WALL 0.30 2.511 6.299 104.05 104.05 90.00 90.00 E
ROOM_2_FLR_3_WALL_SOUTH INT_WALL 0.30 2.511 6.299 55.74 55.74 180.00 90.00 S
ROOM_2_FLR_3_FLOOR NONRES_FLOOR 0.30 0.185 0.196 156.07 156.07 0.00 180.00  
ROOM_2_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 0.188 0.196 156.07 156.07 180.00 0.00  
ROOM_3_MULT19_FLR_3_WALL_NORTH INT_WALL 0.30 2.511 6.299 847.14 847.14 0.00 90.00 N
ROOM_3_MULT19_FLR_3_WALL_EAST INT_WALL 0.30 2.511 6.299 1553.43 1553.43 90.00 90.00 E
ROOM_3_MULT19_FLR_3_WALL_WEST INT_WALL 0.30 2.511 6.299 1553.43 1553.43 270.00 90.00 W
ROOM_3_MULT19_FLR_3_FLOOR NONRES_FLOOR 0.30 0.185 0.196 1863.81 1863.81 0.00 180.00  
ROOM_3_MULT19_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 0.188 0.196 1863.81 1863.81 180.00 0.00  
ROOM_4_MULT19_FLR_3_WALL_EAST INT_WALL 0.30 2.511 6.299 1553.43 1553.43 90.00 90.00 E
ROOM_4_MULT19_FLR_3_WALL_SOUTH INT_WALL 0.30 2.511 6.299 847.37 847.37 180.00 90.00 S
ROOM_4_MULT19_FLR_3_WALL_WEST INT_WALL 0.30 2.511 6.299 1553.43 1553.43 270.00 90.00 W
ROOM_4_MULT19_FLR_3_FLOOR NONRES_FLOOR 0.30 0.185 0.196 1864.32 1864.32 0.00 180.00  
ROOM_4_MULT19_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 0.188 0.196 1864.32 1864.32 180.00 0.00  
ROOM_5_FLR_3_WALL_NORTH INT_WALL 0.30 2.511 6.299 55.74 55.74 0.00 90.00 N
ROOM_5_FLR_3_WALL_WEST INT_WALL 0.30 2.511 6.299 104.06 104.06 270.00 90.00 W
ROOM_5_FLR_3_FLOOR NONRES_FLOOR 0.30 0.185 0.196 156.09 156.09 0.00 180.00  
ROOM_5_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 0.188 0.196 156.09 156.09 180.00 0.00  
ROOM_6_FLR_3_WALL_SOUTH INT_WALL 0.30 2.511 6.299 55.74 55.74 180.00 90.00 S
ROOM_6_FLR_3_WALL_WEST INT_WALL 0.30 2.511 6.299 104.05 104.05 270.00 90.00 W
ROOM_6_FLR_3_FLOOR NONRES_FLOOR 0.30 0.185 0.196 156.07 156.07 0.00 180.00  
ROOM_6_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 0.188 0.196 156.07 156.07 180.00 0.00  
CORRIDOR_FLR_3_WALL_3_NORTH INT_WALL 0.30 2.511 6.299 847.28 847.28 0.00 90.00 N
CORRIDOR_FLR_3_WALL_1_EAST INT_WALL 0.30 2.511 6.299 81.76 81.76 90.00 90.00 E
CORRIDOR_FLR_3_WALL_2_EAST INT_WALL 0.30 2.511 6.299 81.76 81.76 90.00 90.00 E
CORRIDOR_FLR_3_WALL_3_EAST INT_WALL 0.30 2.511 6.299 104.06 104.06 90.00 90.00 E
CORRIDOR_FLR_3_WALL_4_EAST INT_WALL 0.30 2.511 6.299 104.05 104.05 90.00 90.00 E
CORRIDOR_FLR_3_WALL_3_SOUTH INT_WALL 0.30 2.511 6.299 847.27 847.27 180.00 90.00 S
CORRIDOR_FLR_3_WALL_1_WEST INT_WALL 0.30 2.511 6.299 81.76 81.76 270.00 90.00 W
CORRIDOR_FLR_3_WALL_2_WEST INT_WALL 0.30 2.511 6.299 81.76 81.76 270.00 90.00 W
CORRIDOR_FLR_3_WALL_3_WEST INT_WALL 0.30 2.511 6.299 104.06 104.06 270.00 90.00 W
CORRIDOR_FLR_3_WALL_4_WEST INT_WALL 0.30 2.511 6.299 104.05 104.05 270.00 90.00 W
CORRIDOR_FLR_3_FLOOR_1 NONRES_FLOOR 0.30 0.185 0.196 297.29 297.29 180.00 180.00  
CORRIDOR_FLR_3_FLOOR_2 NONRES_FLOOR 0.30 0.185 0.196 963.06 963.06 270.00 180.00  
CORRIDOR_FLR_3_FLOOR_3 NONRES_FLOOR 0.30 0.185 0.196 297.26 297.26 90.00 180.00  
CORRIDOR_FLR_3_CEILING_1 NONRES_FLOOR_CEILING 0.30 0.188 0.196 297.29 297.29 90.00 0.00  
CORRIDOR_FLR_3_CEILING_2 NONRES_FLOOR_CEILING 0.30 0.188 0.196 963.06 963.06 90.00 0.00  
CORRIDOR_FLR_3_CEILING_3 NONRES_FLOOR_CEILING 0.30 0.188 0.196 297.26 297.26 90.00 0.00  
ROOM_1_FLR_6_WALL_NORTH INT_WALL 0.30 2.511 6.299 13.94 13.94 0.00 90.00 N
ROOM_1_FLR_6_WALL_EAST INT_WALL 0.30 2.511 6.299 26.01 26.01 90.00 90.00 E
ROOM_1_FLR_6_FLOOR NONRES_FLOOR 0.30 0.185 0.196 39.02 39.02 0.00 180.00  
ROOM_2_FLR_6_WALL_EAST INT_WALL 0.30 2.511 6.299 26.01 26.01 90.00 90.00 E
ROOM_2_FLR_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 13.94 13.94 180.00 90.00 S
ROOM_2_FLR_6_FLOOR NONRES_FLOOR 0.30 0.185 0.196 39.02 39.02 0.00 180.00  
ROOM_3_MULT9_FLR_6_WALL_NORTH INT_WALL 0.30 2.511 6.299 183.96 183.96 0.00 90.00 N
ROOM_3_MULT9_FLR_6_WALL_EAST INT_WALL 0.30 2.511 6.299 100.35 100.35 90.00 90.00 E
ROOM_3_MULT9_FLR_6_WALL_WEST INT_WALL 0.30 2.511 6.299 100.35 100.35 270.00 90.00 W
ROOM_3_MULT9_FLR_6_FLOOR NONRES_FLOOR 0.30 0.185 0.196 220.77 220.77 0.00 180.00  
BANQUET_FLR_6_WALL_EAST INT_WALL 0.30 2.511 6.299 31.59 31.59 90.00 90.00 E
BANQUET_FLR_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 97.55 97.55 180.00 90.00 S
BANQUET_FLR_6_WALL_WEST INT_WALL 0.30 2.511 6.299 31.59 31.59 270.00 90.00 W
BANQUET_FLR_6_FLOOR NONRES_FLOOR 0.30 0.185 0.196 331.66 331.66 0.00 180.00  
DINING_FLR_6_WALL_EAST INT_WALL 0.30 2.511 6.299 31.59 31.59 90.00 90.00 E
DINING_FLR_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 97.55 97.55 180.00 90.00 S
DINING_FLR_6_WALL_WEST INT_WALL 0.30 2.511 6.299 31.59 31.59 270.00 90.00 W
DINING_FLR_6_FLOOR NONRES_FLOOR 0.30 0.185 0.196 331.66 331.66 0.00 180.00  
KITCHEN_FLR_6_WALL_2_SOUTH INT_WALL 0.30 2.511 6.299 7.43 7.43 180.00 90.00 S
KITCHEN_FLR_6_WALL_1_WEST INT_WALL 0.30 2.511 6.299 20.44 20.44 270.00 90.00 W
KITCHEN_FLR_6_WALL_2_WEST INT_WALL 0.30 2.511 6.299 31.59 31.59 270.00 90.00 W
KITCHEN_FLR_6_FLOOR NONRES_FLOOR 0.30 0.185 0.196 103.30 103.30 180.00 180.00  
CORRIDOR_FLR_6_WALL_3_NORTH INT_WALL 0.30 2.511 6.299 97.55 97.55 0.00 90.00 N
CORRIDOR_FLR_6_WALL_4_NORTH INT_WALL 0.30 2.511 6.299 104.98 104.98 0.00 90.00 N
CORRIDOR_FLR_6_WALL_1_SOUTH INT_WALL 0.30 2.511 6.299 183.95 183.95 180.00 90.00 S
CORRIDOR_FLR_6_WALL_1_WEST INT_WALL 0.30 2.511 6.299 11.15 11.15 270.00 90.00 W
CORRIDOR_FLR_6_WALL_2_WEST INT_WALL 0.30 2.511 6.299 40.88 40.88 270.00 90.00 W
CORRIDOR_FLR_6_WALL_3_WEST INT_WALL 0.30 2.511 6.299 31.59 31.59 270.00 90.00 W
CORRIDOR_FLR_6_WALL_1_EAST INT_WALL 0.30 2.511 6.299 31.59 31.59 90.00 90.00 E
CORRIDOR_FLR_6_WALL_2_EAST INT_WALL 0.30 2.511 6.299 31.59 31.59 90.00 90.00 E
CORRIDOR_FLR_6_WALL_3_EAST INT_WALL 0.30 2.511 6.299 20.44 20.44 90.00 90.00 E
CORRIDOR_FLR_6_FLOOR NONRES_FLOOR 0.30 0.185 0.196 412.12 412.12 180.00 180.00  
BASEMENT_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 3957.66   0.00 90.00 N
RETAIL_1_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 134.14   0.00 90.00 N
RETAIL_2_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 155.34   0.00 90.00 N
MECH_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 328.49   0.00 90.00 N
STORAGE_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 189.52   0.00 90.00 N
LAUNDRY_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 156.08   0.00 90.00 N
CAFE_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 377.72   0.00 90.00 N
LOBBY_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 2616.37   0.00 90.00 N
ROOM_1_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 312.18   0.00 90.00 N
ROOM_2_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 312.14   0.00 90.00 N
ROOM_3_MULT19_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 3727.63   0.00 90.00 N
ROOM_4_MULT19_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 3728.64   0.00 90.00 N
ROOM_5_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 312.18   0.00 90.00 N
ROOM_6_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 312.14   0.00 90.00 N
CORRIDOR_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 3115.24   0.00 90.00 N
ROOM_1_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 78.04   0.00 90.00 N
ROOM_2_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 78.03   0.00 90.00 N
ROOM_3_MULT9_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 441.55   0.00 90.00 N
BANQUET_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 663.31   0.00 90.00 N
DINING_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 663.31   0.00 90.00 N
KITCHEN_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 206.61   0.00 90.00 N
CORRIDOR_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 824.25   0.00 90.00 N


Exterior Fenestration

Construction Frame and Divider Glass Area [m2] Frame Area [m2] Divider Area [m2] Area of One Opening [m2] Area of Multiplied Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Frame Conductance [W/m2-K] Divider Conductance [W/m2-K] NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW NONRESWINDOW_U_0.4711_SHGC_0.25   23.26 0.00 0.00 23.26 23.26 2.678 0.251 0.251             No RETAIL_1_FLR_1_WALL_SOUTH 180.00 90.00 S
CAFE_FLR_1_WALL_SOUTH_WINDOW NONRESWINDOW_U_0.4711_SHGC_0.25   65.50 0.00 0.00 65.50 65.50 2.678 0.251 0.251             No CAFE_FLR_1_WALL_SOUTH 180.00 90.00 S
LOBBY_FLR_1_WALL_SOUTH_WINDOW NONRESWINDOW_U_0.4711_SHGC_0.25   85.08 0.00 0.00 85.08 85.08 2.678 0.251 0.251             No LOBBY_FLR_1_WALL_1_SOUTH 180.00 90.00 S
ROOM_1_FLR_3_WALL_SOUTH_WINDOW RESWINDOW_U_0.4711_SHGC_0.25   4.60 0.00 0.00 4.60 18.40 2.678 0.251 0.251             No ROOM_1_FLR_3_WALL_SOUTH 180.00 90.00 S
ROOM_1_FLR_3_WALL_WEST_WINDOW RESWINDOW_U_0.4711_SHGC_0.25   8.58 0.00 0.00 8.58 34.34 2.678 0.251 0.251             No ROOM_1_FLR_3_WALL_WEST 270.00 90.00 W
ROOM_2_FLR_3_WALL_NORTH_WINDOW RESWINDOW_U_0.4711_SHGC_0.25   4.60 0.00 0.00 4.60 18.40 2.678 0.251 0.251             No ROOM_2_FLR_3_WALL_NORTH 0.00 90.00 N
ROOM_2_FLR_3_WALL_WEST_WINDOW RESWINDOW_U_0.4711_SHGC_0.25   8.58 0.00 0.00 8.58 34.34 2.678 0.251 0.251             No ROOM_2_FLR_3_WALL_WEST 270.00 90.00 W
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW RESWINDOW_U_0.4711_SHGC_0.25   3.68 0.00 0.00 3.68 279.56 2.678 0.251 0.251             No ROOM_3_MULT19_FLR_3_WALL_SOUTH 180.00 90.00 S
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW RESWINDOW_U_0.4711_SHGC_0.25   3.68 0.00 0.00 3.68 279.65 2.678 0.251 0.251             No ROOM_4_MULT19_FLR_3_WALL_NORTH 0.00 90.00 N
ROOM_5_FLR_3_WALL_EAST_WINDOW RESWINDOW_U_0.4711_SHGC_0.25   8.58 0.00 0.00 8.58 34.34 2.678 0.251 0.251             No ROOM_5_FLR_3_WALL_EAST 90.00 90.00 E
ROOM_5_FLR_3_WALL_SOUTH_WINDOW RESWINDOW_U_0.4711_SHGC_0.25   4.60 0.00 0.00 4.60 18.40 2.678 0.251 0.251             No ROOM_5_FLR_3_WALL_SOUTH 180.00 90.00 S
ROOM_6_FLR_3_WALL_NORTH_WINDOW RESWINDOW_U_0.4711_SHGC_0.25   4.60 0.00 0.00 4.60 18.40 2.678 0.251 0.251             No ROOM_6_FLR_3_WALL_NORTH 0.00 90.00 N
ROOM_6_FLR_3_WALL_EAST_WINDOW RESWINDOW_U_0.4711_SHGC_0.25   8.58 0.00 0.00 8.58 34.34 2.678 0.251 0.251             No ROOM_6_FLR_3_WALL_EAST 90.00 90.00 E
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW NONRESWINDOW_U_0.4711_SHGC_0.25   5.82 0.00 0.00 5.82 23.30 2.678 0.251 0.251             No CORRIDOR_FLR_3_WALL_1_NORTH 0.00 90.00 N
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW NONRESWINDOW_U_0.4711_SHGC_0.25   2.15 0.00 0.00 2.15 8.59 2.678 0.251 0.251             No CORRIDOR_FLR_3_WALL_2_NORTH 0.00 90.00 N
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW NONRESWINDOW_U_0.4711_SHGC_0.25   2.15 0.00 0.00 2.15 8.58 2.678 0.251 0.251             No CORRIDOR_FLR_3_WALL_1_SOUTH 180.00 90.00 S
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW NONRESWINDOW_U_0.4711_SHGC_0.25   5.82 0.00 0.00 5.82 23.30 2.678 0.251 0.251             No CORRIDOR_FLR_3_WALL_2_SOUTH 180.00 90.00 S
ROOM_1_FLR_6_WALL_SOUTH_WINDOW RESWINDOW_U_0.4711_SHGC_0.25   4.60 0.00 0.00 4.60 4.60 2.678 0.251 0.251             No ROOM_1_FLR_6_WALL_SOUTH 180.00 90.00 S
ROOM_1_FLR_6_WALL_WEST_WINDOW RESWINDOW_U_0.4711_SHGC_0.25   8.58 0.00 0.00 8.58 8.58 2.678 0.251 0.251             No ROOM_1_FLR_6_WALL_WEST 270.00 90.00 W
ROOM_2_FLR_6_WALL_NORTH_WINDOW RESWINDOW_U_0.4711_SHGC_0.25   4.60 0.00 0.00 4.60 4.60 2.678 0.251 0.251             No ROOM_2_FLR_6_WALL_NORTH 0.00 90.00 N
ROOM_2_FLR_6_WALL_WEST_WINDOW RESWINDOW_U_0.4711_SHGC_0.25   8.58 0.00 0.00 8.58 8.58 2.678 0.251 0.251             No ROOM_2_FLR_6_WALL_WEST 270.00 90.00 W
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW RESWINDOW_U_0.4711_SHGC_0.25   6.74 0.00 0.00 6.74 60.70 2.678 0.251 0.251             No ROOM_3_MULT9_FLR_6_WALL_SOUTH 180.00 90.00 S
BANQUET_FLR_6_WALL_NORTH_WINDOW NONRESWINDOW_U_0.4711_SHGC_0.25   32.19 0.00 0.00 32.19 32.19 2.678 0.251 0.251             No BANQUET_FLR_6_WALL_NORTH 0.00 90.00 N
DINING_FLR_6_WALL_NORTH_WINDOW NONRESWINDOW_U_0.4711_SHGC_0.25   32.19 0.00 0.00 32.19 32.19 2.678 0.251 0.251             No DINING_FLR_6_WALL_NORTH 0.00 90.00 N
KITCHEN_FLR_6_WALL_NORTH_WINDOW NONRESWINDOW_U_0.4711_SHGC_0.25   4.60 0.00 0.00 4.60 4.60 2.678 0.251 0.251             No KITCHEN_FLR_6_WALL_NORTH 0.00 90.00 N
KITCHEN_FLR_6_WALL_EAST_WINDOW NONRESWINDOW_U_0.4711_SHGC_0.25   17.17 0.00 0.00 17.17 17.17 2.678 0.251 0.251             No KITCHEN_FLR_6_WALL_EAST 90.00 90.00 E
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW NONRESWINDOW_U_0.4711_SHGC_0.25   4.60 0.00 0.00 4.60 4.60 2.678 0.251 0.251             No KITCHEN_FLR_6_WALL_1_SOUTH 180.00 90.00 S
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW NONRESWINDOW_U_0.4711_SHGC_0.25   5.82 0.00 0.00 5.82 5.82 2.678 0.251 0.251             No CORRIDOR_FLR_6_WALL_1_NORTH 0.00 90.00 N
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW NONRESWINDOW_U_0.4711_SHGC_0.25   5.21 0.00 0.00 5.21 5.21 2.678 0.251 0.251             No CORRIDOR_FLR_6_WALL_2_NORTH 0.00 90.00 N
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW NONRESWINDOW_U_0.4711_SHGC_0.25   17.17 0.00 0.00 17.17 17.17 2.678 0.251 0.251             No CORRIDOR_FLR_6_WALL_2_SOUTH 180.00 90.00 S
Total or Average             1213.79 2.678 0.251 0.251                      
North Total or Average             432.95 2.678 0.251 0.251                      
Non-North Total or Average             780.84 2.678 0.251 0.251                      


Exterior Fenestration Shaded State

Frame and Divider Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance
None                


Interior Fenestration

Construction Area of One Opening [m2] Area of Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance
Total or Average     0.00 - - -


Exterior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
RETAIL_2_FLR_1_WALL_WEST_DOOR SWINGING DOOR_CON 2.281 3.464 1.95 RETAIL_2_FLR_1_WALL_WEST
STORAGE_FLR_1_WALL_NORTH_ROLLDOOR OVERHEAD DOOR_CON 1.016 1.198 7.43 STORAGE_FLR_1_WALL_NORTH
LAUNDRY_FLR_1_WALL_EAST_DOOR SWINGING DOOR_CON 2.281 3.464 1.95 LAUNDRY_FLR_1_WALL_EAST
CAFE_FLR_1_WALL_EAST_DOOR SWINGING DOOR_CON 2.281 3.464 1.95 CAFE_FLR_1_WALL_EAST
LOBBY_FLR_1_WALL_1_NORTH_DOOR1 SWINGING DOOR_CON 2.281 3.464 1.95 LOBBY_FLR_1_WALL_1_NORTH
LOBBY_FLR_1_WALL_1_NORTH_DOOR2 SWINGING DOOR_CON 2.281 3.464 1.95 LOBBY_FLR_1_WALL_1_NORTH


Interior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
None          



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2023-10-16 08:58:10

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
CAFE_FLR_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
LOBBY_FLR_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
ROOM_1_FLR_3_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
ROOM_1_FLR_3_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
ROOM_2_FLR_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_3_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
ROOM_5_FLR_3_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
ROOM_5_FLR_3_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
ROOM_6_FLR_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
ROOM_6_FLR_3_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
ROOM_1_FLR_6_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
ROOM_1_FLR_6_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
ROOM_2_FLR_6_WALL_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_6_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
BANQUET_FLR_6_WALL_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
DINING_FLR_6_WALL_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
KITCHEN_FLR_6_WALL_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
KITCHEN_FLR_6_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00


Window Control

Name Type Shaded Construction Control Glare Control
None          



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2023-10-16 08:58:10

Interior Lighting

Zone Name Space Name Space Type Lighting Power Density [W/m2] Space Area [m2] Total Power [W] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [GJ]
BASEMENT_LIGHTS BASEMENT BASEMENT GENERAL 8.7495 1978.83 17313.73 LightsWired LTG_SCH_BASEMENT 50.91 168.00 50.86 0.0000 Y 165.29
RETAIL_1_FLR_1_LIGHTS RETAIL_1_FLR_1 RETAIL_1_FLR_1 GENERAL 13.0124 67.07 872.76 LightsWired LTG_SCH_RETAIL 51.36 168.00 51.30 0.0000 Y 8.40
RETAIL_2_FLR_1_LIGHTS RETAIL_2_FLR_1 RETAIL_2_FLR_1 GENERAL 13.0124 77.67 1010.66 LightsWired LTG_SCH_RETAIL 51.36 168.00 51.30 0.0000 Y 9.73
MECH_FLR_1_LIGHTS MECH_FLR_1 MECH_FLR_1 GENERAL 10.0642 164.24 1652.98 LightsWired LTG_SCH_MECHANIC 58.69 168.00 58.63 0.0000 Y 18.19
STORAGE_FLR_1_LIGHTS STORAGE_FLR_1 STORAGE_FLR_1 GENERAL 7.3195 94.76 693.59 LightsWired LTG_SCH_STORAGE 25.68 168.00 25.65 0.0000 Y 3.34
LAUNDRY_FLR_1_LIGHTS LAUNDRY_FLR_1 LAUNDRY_FLR_1 GENERAL 5.4896 78.04 428.40 LightsWired LTG_SCH_LAUNDRY 51.36 168.00 51.30 0.0000 Y 4.13
CAFE_FLR_1_LIGHTS CAFE_FLR_1 CAFE_FLR_1 GENERAL 12.8090 188.86 2419.14 LightsWired LTG_SCH_DINING 58.69 168.00 58.63 0.0000 Y 26.62
LOBBY_FLR_1_LIGHTS LOBBY_FLR_1 LOBBY_FLR_1 GENERAL 10.0642 1308.19 13165.91 LightsWired LTG_SCH_LOBBY 58.69 168.00 58.63 0.0000 Y 144.89
ROOM_1_FLR_3_LIGHTS ROOM_1_FLR_3 ROOM_1_FLR_3 GENERAL 10.0642 156.09 1570.91 LightsWired LTG_SCH_GUESTROOM 69.03 168.00 69.21 0.0000 Y 20.41
ROOM_2_FLR_3_LIGHTS ROOM_2_FLR_3 ROOM_2_FLR_3 GENERAL 10.0642 156.07 1570.72 LightsWired LTG_SCH_GUESTROOM 69.03 168.00 69.21 0.0000 Y 20.41
ROOM_3_MULT19_FLR_3_LIGHTS ROOM_3_MULT19_FLR_3 ROOM_3_MULT19_FLR_3 GENERAL 10.0642 1863.81 18757.86 LightsWired LTG_SCH_GUESTROOM 69.03 168.00 69.21 0.0000 Y 243.70
ROOM_4_MULT19_FLR_3_LIGHTS ROOM_4_MULT19_FLR_3 ROOM_4_MULT19_FLR_3 GENERAL 10.0642 1864.32 18762.99 LightsWired LTG_SCH_GUESTROOM 69.03 168.00 69.21 0.0000 Y 243.77
ROOM_5_FLR_3_LIGHTS ROOM_5_FLR_3 ROOM_5_FLR_3 GENERAL 10.0642 156.09 1570.91 LightsWired LTG_SCH_GUESTROOM 69.03 168.00 69.21 0.0000 Y 20.41
ROOM_6_FLR_3_LIGHTS ROOM_6_FLR_3 ROOM_6_FLR_3 GENERAL 10.0642 156.07 1570.72 LightsWired LTG_SCH_GUESTROOM 69.03 168.00 69.21 0.0000 Y 20.41
CORRIDOR_FLR_3_LIGHTS CORRIDOR_FLR_3 CORRIDOR_FLR_3 GENERAL 3.6597 1557.62 5700.46 LightsWired LTG_SCH_CORRIDOR 58.69 168.00 58.63 0.0000 Y 62.73
ROOM_1_FLR_6_LIGHTS ROOM_1_FLR_6 ROOM_1_FLR_6 GENERAL 10.0642 39.02 392.73 LightsWired LTG_SCH_GUESTROOM 69.03 168.00 69.21 0.0000 Y 5.10
ROOM_2_FLR_6_LIGHTS ROOM_2_FLR_6 ROOM_2_FLR_6 GENERAL 10.0642 39.02 392.68 LightsWired LTG_SCH_GUESTROOM 69.03 168.00 69.21 0.0000 Y 5.10
ROOM_3_MULT9_FLR_6_LIGHTS ROOM_3_MULT9_FLR_6 ROOM_3_MULT9_FLR_6 GENERAL 10.0642 220.77 2221.93 LightsWired LTG_SCH_GUESTROOM 69.03 168.00 69.21 0.0000 Y 28.87
BANQUET_FLR_6_LIGHTS BANQUET_FLR_6 BANQUET_FLR_6 GENERAL 12.8090 331.66 4248.21 LightsWired LTG_SCH_DINING 58.69 168.00 58.63 0.0000 Y 46.75
DINING_FLR_6_LIGHTS DINING_FLR_6 DINING_FLR_6 GENERAL 12.8090 331.66 4248.21 LightsWired LTG_SCH_DINING 58.69 168.00 58.63 0.0000 Y 46.75
KITCHEN_FLR_6_LIGHTS KITCHEN_FLR_6 KITCHEN_FLR_6 GENERAL 10.9792 103.30 1134.20 LightsWired LTG_SCH_KITCHEN 58.69 168.00 58.63 0.0000 Y 12.48
CORRIDOR_FLR_6_LIGHTS CORRIDOR_FLR_6 CORRIDOR_FLR_6 GENERAL 3.6597 412.12 1508.26 LightsWired LTG_SCH_CORRIDOR 58.69 168.00 58.63 0.0000 Y 16.60
Interior Lighting Total       8.9207 11345.29 101207.97               559.10


Daylighting

Zone Control Name Daylighting Method Control Type Fraction Controlled Lighting Installed in Zone [W] Lighting Controlled [W]
None              


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [GJ]
EXTERIOR FACADE LIGHTING 16690.39 AstronomicalClock -   83.77 83.77 262.44
Exterior Lighting Total 16690.39           262.44



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2023-10-16 08:58:10

Central Plant

Type Reference Capacity [W] Reference Efficiency [W/W] Rated Capacity [W] Rated Efficiency [W/W] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
HEATSYS1 BOILER Boiler:HotWater 484765.23 0.80        
COOLSYS1 CHILLER1 Chiller:Electric:EIR 1032120.29 2.80 1032301.71 2.80 3.72 12.68


Cooling Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Sensible Capacity [W] Nominal Latent Capacity [W] Nominal Sensible Heat Ratio Nominal Efficiency [W/W] Nominal Coil UA Value [W/C] Nominal Coil Surface Area [m2]
ROOM_1_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 13327.53 22320.18 16417.25 5902.93 0.74 - 3335.07 33.83
ROOM_2_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 13232.26 22160.41 16299.61 5860.81 0.74 - 3311.16 33.58
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 80829.74 136156.72 100208.05 35948.67 0.74 - 20698.97 209.94
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 90352.22 149440.23 108787.81 40652.42 0.73 - 22036.97 223.51
ROOM_5_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 11674.40 19553.29 14379.68 5173.61 0.74 - 2923.64 29.65
ROOM_6_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 11579.51 19394.22 14262.62 5131.61 0.74 - 2899.83 29.41
ROOM_1_FLR_6 FAN COIL COOLING COIL Coil:Cooling:Water 3611.78 6049.56 4450.12 1599.44 0.74 - 904.05 9.17
ROOM_2_FLR_6 FAN COIL COOLING COIL Coil:Cooling:Water 3582.23 6000.01 4413.63 1586.38 0.74 - 896.64 9.09
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Coil:Cooling:Water 16581.75 27624.78 20226.52 7398.26 0.73 - 4105.57 41.64
VAV WITH REHEAT COOLING COIL Coil:Cooling:Water 729331.56 664290.74 409499.04 254791.70 0.62 - 70658.82 716.66
FLR_3_DOAS COOLING COIL Coil:Cooling:Water 57348.72 51198.70 32051.32 19147.38 0.63 - 5018.41 50.90
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [W] Standard Rated Net COP [W/W] EER [Btu/W-h] SEER User [Btu/W-h] SEER Standard [Btu/W-h] IEER [Btu/W-h]
None              


DX Cooling Coil ASHRAE 127 Standard Ratings Report

DX Cooling Coil Type Rated Net Cooling Capacity Test A [W] Rated Electric Power Test A [W] Rated Net Cooling Capacity Test B [W] Rated Electric Power Test B [W] Rated Net Cooling Capacity Test C [W] Rated Electric Power Test C [W] Rated Net Cooling Capacity Test D [W] Rated Electric Power Test D [W]
None                  


DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [W] Low Temperature Heating (net) Rating Capacity [W] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Efficiency [W/W]
BASEMENT VAV BOX REHEAT COIL Coil:Heating:Water 13021.18 13089.25 -
RETAIL_1_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 4770.42 4793.45 -
RETAIL_2_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 2266.37 2277.90 -
MECH_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 3192.02 3207.69 -
STORAGE_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 1782.12 1790.77 -
LAUNDRY_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 19667.59 19769.87 -
CAFE_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 15073.10 15148.05 -
LOBBY_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 42329.07 42544.82 -
ROOM_1_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 6581.78 7091.58 -
ROOM_2_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 6575.24 7084.54 -
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 37721.69 40643.29 -
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 37617.71 40531.28 -
ROOM_5_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 6569.52 7078.37 -
ROOM_6_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 6562.97 7071.32 -
CORRIDOR_FLR_3 VAV BOX REHEAT COIL Coil:Heating:Water 16345.59 16424.66 -
ROOM_1_FLR_6 FAN COIL HEATING COIL Coil:Heating:Water 2054.07 2213.08 -
ROOM_2_FLR_6 FAN COIL HEATING COIL Coil:Heating:Water 2053.25 2212.20 -
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL Coil:Heating:Water 9915.53 10683.09 -
BANQUET_FLR_6 VAV BOX REHEAT COIL Coil:Heating:Water 18979.29 19076.44 -
DINING_FLR_6 VAV BOX REHEAT COIL Coil:Heating:Water 19688.34 19789.18 -
KITCHEN_FLR_6 VAV BOX REHEAT COIL Coil:Heating:Water 13990.36 14063.05 -
CORRIDOR_FLR_6 VAV BOX REHEAT COIL Coil:Heating:Water 11230.01 11283.70 -
VAV WITH REHEAT HEATING COIL Coil:Heating:Water 172635.01 130015.88 -
FLR_3_DOAS HEATING COIL Coil:Heating:Water 14143.00 10651.46 -
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

Fans

Type Total Efficiency [W/W] Delta Pressure [pa] Max Air Flow Rate [m3/s] Rated Electricity Rate [W] Rated Power Per Max Air Flow Rate [W-s/m3] Motor Heat In Air Fraction Fan Energy Index End Use Subcategory Design Day Name for Fan Sizing Peak Date/Time for Fan Sizing Peak
LAUNDRY_FLR_1 EXHAUST FAN Fan:ZoneExhaust 0.16 125.00 0.24 184.35 781.25 1.00 1.15 General    
LOBBY_FLR_1 EXHAUST FAN Fan:ZoneExhaust 1.00 0.00 0.00 0.00   1.00 0.00 General    
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.16 270.90 1.26 2129.05 1693.12 1.00 0.48 General EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 16:30:00
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.16 270.90 1.25 2113.77 1693.12 1.00 0.48 General EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 16:40:00
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.16 270.90 7.66 12970.57 1693.12 1.00 0.39 General EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 14:10:00
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.16 270.90 8.25 13961.11 1693.12 1.00 0.39 General EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 15:30:00
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.16 270.90 1.10 1864.23 1693.12 1.00 0.49 General EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 10:20:00
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.16 270.90 1.09 1849.04 1693.12 1.00 0.49 General EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 10:10:00
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.16 270.90 0.34 577.17 1693.12 1.00 0.68 General EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 16:30:00
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.16 270.90 0.34 572.43 1693.12 1.00 0.68 General EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 16:30:00
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.16 270.90 1.54 2610.88 1693.12 1.00 0.46 General EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 14:10:00
BANQUET_FLR_6 EXHAUST FAN Fan:ZoneExhaust 1.00 0.00 0.00 0.00   1.00 0.00 General    
DINING_FLR_6 EXHAUST FAN Fan:ZoneExhaust 1.00 0.00 0.00 0.00   1.00 0.00 General    
KITCHEN_FLR_6 EXHAUST FAN Fan:ZoneExhaust 0.16 125.00 1.89 1474.84 781.25 1.00 0.62 General    
VAV WITH REHEAT FAN Fan:VariableVolume 0.62 1389.42 25.04 56103.75 2240.64 1.00 1.11 General EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00
FLR_3_DOAS FAN Fan:ConstantVolume 0.58 622.50 2.05 2194.93 1070.05 1.00 1.30 General EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00


Pumps

Type Control Head [pa] Water Flow [m3/s] Electricity Rate [W] Power Per Water Flow Rate [W-s/m3] Motor Efficiency [W/W] End Use Subcategory
COOLSYS1 PUMP SECONDARY Pump:VariableSpeed Intermittent 133527.72 0.036841 7591.54 206062.94 0.90 General
HEATSYS1 PUMP Pump:VariableSpeed Intermittent 180705.70 0.004241 1277.18 301156.09 0.90 General
COOLSYS1 PUMP Pump:ConstantSpeed Intermittent 92445.74 0.036841 5255.88 142664.32 0.90 General
SWHSYS1 PUMP Pump:ConstantSpeed Intermittent 29891.00 0.000375 47.91 127739.32 0.30 General


Service Water Heating

Type Storage Volume [m3] Input [W] Thermal Efficiency [W/W] Recovery Efficiency [W/W] Energy Factor
SWH BOOSTER E WATER HEATER WaterHeater:Mixed 0.02 8000.00 1.00 1.24 1.15
SWH LAUNDRY G WATER HEATER WaterHeater:Mixed 1.14 163316.00 0.80 0.58 0.51
SWHSYS1 WATER HEATER WaterHeater:Mixed 2.27 175842.60 0.80 0.26 0.03



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2023-10-16 08:58:10

Zone Sensible Cooling

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
BASEMENT 34112.29 34112.29 17.24 2.858 2.858 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 20:50:00 24.00 24.00 0.00921 30.62 0.00686 0.854 0.00
RETAIL_1_FLR_1 4647.20 4647.20 69.29 0.389 0.389 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 13:50:00 24.00 24.00 0.00894 37.99 0.00687 0.079 0.00
RETAIL_2_FLR_1 3392.10 3392.10 43.67 0.284 0.284 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:10:00 24.00 24.00 0.00928 36.06 0.00687 0.092 0.00
MECH_FLR_1 3633.18 3633.18 22.12 0.304 0.304 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 24.00 24.00 0.00858 34.98 0.00687 0.000 0.00
STORAGE_FLR_1 1834.88 1834.88 19.36 0.154 0.154 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:10:00 24.00 24.00 0.00865 36.06 0.00687 0.058 0.00
LAUNDRY_FLR_1 45235.90 45235.90 579.65 3.790 3.790 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 15:40:00 24.00 24.00 0.00853 37.58 0.00687 0.000 0.00
CAFE_FLR_1 19748.77 19748.77 104.57 1.656 1.656 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 13:50:00 24.00 23.99 0.01006 37.99 0.00687 0.676 0.00
LOBBY_FLR_1 65273.03 65273.03 49.90 5.471 5.471 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 14:10:00 24.00 23.99 0.00991 38.10 0.00687 1.894 0.00
ROOM_1_FLR_3 11139.23 11139.23 285.46 1.257 1.257 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 16:30:00 21.11 21.11 0.00852 36.80 0.00687 0.062 0.00
ROOM_2_FLR_3 11059.32 11059.32 283.45 1.248 1.248 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 16:40:00 21.11 21.11 0.00852 36.63 0.00687 0.062 0.00
ROOM_3_MULT19_FLR_3 67864.35 67864.35 2767.28 7.661 7.661 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 14:10:00 21.11 21.11 0.00846 38.10 0.00687 0.837 0.00
ROOM_4_MULT19_FLR_3 73041.28 73041.28 2977.56 8.246 8.246 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 15:30:00 21.11 21.11 0.00865 37.71 0.00687 0.837 0.00
ROOM_5_FLR_3 9753.73 9753.73 249.95 1.101 1.101 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 10:20:00 21.11 21.11 0.00852 33.81 0.00686 0.062 0.00
ROOM_6_FLR_3 9674.27 9674.27 247.95 1.092 1.092 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 10:10:00 21.11 21.11 0.00852 33.48 0.00686 0.062 0.00
CORRIDOR_FLR_3 16255.55 16255.55 41.74 1.362 1.362 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 15:20:00 24.00 24.00 0.00958 37.84 0.00687 0.475 0.00
ROOM_1_FLR_6 3019.76 3019.76 77.39 0.341 0.341 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 16:30:00 21.11 21.11 0.00852 36.80 0.00687 0.015 0.00
ROOM_2_FLR_6 2994.96 2994.96 76.76 0.338 0.338 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 16:30:00 21.11 21.11 0.00852 36.80 0.00687 0.015 0.00
ROOM_3_MULT9_FLR_6 13659.77 13659.77 556.85 1.542 1.542 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 14:10:00 21.11 21.11 0.00858 38.10 0.00687 0.099 0.00
BANQUET_FLR_6 31477.22 31477.22 94.91 2.640 2.640 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 14:50:00 24.00 23.98 0.01026 38.10 0.00687 1.188 0.00
DINING_FLR_6 33000.64 33000.64 99.50 2.768 2.768 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 14:50:00 24.00 23.98 0.01018 38.10 0.00687 1.188 0.00
KITCHEN_FLR_6 31366.80 31366.80 303.63 2.635 2.635 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 12:30:00 24.00 23.97 0.01002 36.93 0.00687 0.367 0.00
CORRIDOR_FLR_6 10077.64 10077.64 24.45 0.844 0.844 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 24.00 24.00 0.00895 38.10 0.00687 0.126 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

Zone Sensible Heating

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
BASEMENT 0.00 0.00 0.00 0.000 0.854 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.00 23.40 0.00281 -5.20 0.00281 0.854 0.00
RETAIL_1_FLR_1 2998.72 2998.72 44.71 0.148 0.148 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.00 21.00 0.00740 -5.20 0.00281 0.079 0.00
RETAIL_2_FLR_1 973.16 973.16 12.53 0.048 0.092 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.00 21.00 0.00731 -5.20 0.00281 0.092 0.00
MECH_FLR_1 1807.63 1807.63 11.01 0.089 0.089 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.00 21.00 0.00715 -5.20 0.00281 0.000 0.00
STORAGE_FLR_1 1082.91 1082.91 11.43 0.054 0.058 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.00 21.00 0.00717 -5.20 0.00281 0.058 0.00
LAUNDRY_FLR_1 2432.06 2432.06 31.16 0.120 0.120 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.00 21.00 0.00714 -5.20 0.00281 0.000 0.00
CAFE_FLR_1 7536.22 7536.22 39.90 0.372 0.676 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.00 21.00 0.00747 -5.20 0.00281 0.676 0.00
LOBBY_FLR_1 17434.45 17434.45 13.33 0.862 1.894 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.00 21.00 0.00736 -5.20 0.00281 1.894 0.00
ROOM_1_FLR_3 6582.02 6582.02 168.67 0.327 0.327 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.11 21.11 0.00738 -5.20 0.00281 0.062 0.00
ROOM_2_FLR_3 6575.47 6575.47 168.53 0.327 0.327 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.11 21.11 0.00738 -5.20 0.00281 0.062 0.00
ROOM_3_MULT19_FLR_3 37722.34 37722.34 1538.19 1.875 1.875 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.11 21.11 0.00742 -5.20 0.00281 0.837 0.00
ROOM_4_MULT19_FLR_3 37618.36 37618.36 1533.53 1.870 1.870 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.11 21.11 0.00742 -5.20 0.00281 0.837 0.00
ROOM_5_FLR_3 6569.75 6569.75 168.36 0.327 0.327 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.11 21.11 0.00738 -5.20 0.00281 0.062 0.00
ROOM_6_FLR_3 6563.21 6563.21 168.21 0.326 0.326 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.11 21.11 0.00738 -5.20 0.00281 0.062 0.00
CORRIDOR_FLR_3 10146.72 10146.72 26.06 0.501 0.501 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.00 21.00 0.00750 -5.20 0.00281 0.475 0.00
ROOM_1_FLR_6 2054.14 2054.14 52.64 0.102 0.102 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.11 21.11 0.00749 -5.20 0.00281 0.015 0.00
ROOM_2_FLR_6 2053.32 2053.32 52.63 0.102 0.102 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.11 21.11 0.00749 -5.20 0.00281 0.015 0.00
ROOM_3_MULT9_FLR_6 9915.80 9915.80 404.22 0.493 0.493 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.11 21.11 0.00751 -5.20 0.00281 0.099 0.00
BANQUET_FLR_6 6958.28 6958.28 20.98 0.344 1.188 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.00 21.00 0.00762 -5.20 0.00281 1.188 0.00
DINING_FLR_6 7085.83 7085.83 21.36 0.350 1.188 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 23:40:00 21.00 21.00 0.00763 -5.20 0.00281 1.188 0.00
KITCHEN_FLR_6 2031.68 2031.68 19.67 0.100 0.367 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 23:30:00 21.00 21.00 0.00637 -5.20 0.00281 0.367 0.00
CORRIDOR_FLR_6 7385.91 7385.91 17.92 0.365 0.365 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 23:40:00 21.00 21.00 0.00768 -5.20 0.00281 0.126 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

System Design Air Flow Rates

Calculated cooling [m3/s] User cooling [m3/s] Calculated heating [m3/s] User heating [m3/s] Adjusted cooling [m3/s] Adjusted heating [m3/s] Adjusted main [m3/s] Calculated Heating Air Flow Ratio [] User Heating Air Flow Ratio []
VAV WITH REHEAT 25.04 25.04 7.54 7.54 25.0392 25.0296 25.0392 0.9996 0.3000
FLR_3_DOAS 22.39 2.05 5.75 2.05 2.0513 2.0513 2.0513 1.0000 0.3000


Plant Loop Coincident Design Fluid Flow Rate Adjustments

Previous Design Volume Flow Rate [m3/s] Algorithm Volume Flow Rate [m3/s] Coincident Design Volume Flow Rate [m3/s] Coincident Size Adjusted Peak Sizing Period Name Peak Day into Period {TIMESTAMP}[day] Peak Hour Of Day {TIMESTAMP}[hr] Peak Step Start Minute {TIMESTAMP}[min]
None                


Coil Sizing Summary

Coil Type HVAC Type HVAC Name Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Flow Percentage at Ideal Loads Peak [%] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W]
BASEMENT VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT BASEMENT VAV BOX 13021.183 13021.183 2.843585 0.00011391 271.534 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 13021.18 13021.18 2.843585 16.70 11.86 0.00800000 40.00 19.53 0.00800000 -5.20 0.00280840 -5.20 0.0000 21.00 0.00800000 44.8527 0.00 0.00 13094.37 13094.37
RETAIL_1_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT RETAIL_1_FLR_1 VAV BOX 4770.421 4770.421 0.387412 0.00004173 109.122 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 4770.42 4770.42 0.387412 16.70 11.86 0.00800000 40.00 19.53 0.00800000 -5.20 0.00280840 -5.20 0.0000 21.00 0.00740404 41.5530 2998.72 0.00 4796.05 4796.05
RETAIL_2_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT RETAIL_2_FLR_1 VAV BOX 2266.373 2266.373 0.282793 0.00001983 49.182 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 2266.37 2266.37 0.282793 16.70 11.86 0.00800000 40.00 19.53 0.00800000 -5.20 0.00280840 -5.20 0.0000 21.00 0.00730618 41.0087 973.16 0.00 2278.95 2278.95
MECH_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT MECH_FLR_1 VAV BOX 3192.023 3192.023 0.302822 0.00002793 71.415 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 3192.02 3192.02 0.302822 16.70 11.86 0.00800000 40.00 19.53 0.00800000 -5.20 0.00280840 -5.20 0.0000 21.00 0.00714817 40.1319 1807.63 0.00 3209.32 3209.32
STORAGE_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT STORAGE_FLR_1 VAV BOX 1782.115 1782.115 0.152937 0.00001559 40.427 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 1782.12 1782.12 0.152937 16.70 11.86 0.00800000 40.00 19.53 0.00800000 -5.20 0.00280840 -5.20 0.0000 21.00 0.00717464 40.2789 1082.91 0.00 1791.72 1791.72
LAUNDRY_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 19667.588 19667.588 3.770679 0.00017206 413.112 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 19667.59 19667.59 3.770679 16.70 11.86 0.00800000 40.00 19.53 0.00800000 -5.20 0.00280840 -5.20 0.0000 21.00 0.00713766 40.0751 2432.06 0.00 19777.84 19777.84
CAFE_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CAFE_FLR_1 VAV BOX 15073.104 15073.104 1.647800 0.00013187 331.539 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 15073.10 15073.10 1.647800 16.70 11.86 0.00800000 40.00 19.53 0.00800000 -5.20 0.00280840 -5.20 0.0000 21.00 0.00746845 41.9098 7536.22 0.00 15155.32 15155.32
LOBBY_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 42329.066 42329.066 5.443297 0.00037031 915.984 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 42329.07 42329.07 5.443297 16.70 11.86 0.00800000 40.00 19.53 0.00800000 -5.20 0.00280840 -5.20 0.0000 21.00 0.00735889 41.3011 17434.45 0.00 42564.09 42564.09
ROOM_1_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_3 FAN COIL 13327.530 -999.000 1.257465 0.00047602 -999.000 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 16:30:00 unknown 7/21 16:30:00 13327.53 13283.11 1.257465 22.70 14.50 0.00851776 12.80 10.82 0.00850000 36.80 0.00686940 17.78 0.0000 21.11 0.00851776 47.3923 11139.23 0.00 15316.11 14687.96
ROOM_1_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_3 FAN COIL 6581.784 6581.784 0.327185 0.00005758 188.101 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 6581.78 6581.78 0.327185 21.11 12.94 0.00737699 40.00 19.53 0.00800000 -5.20 0.00280840 -5.20 0.0000 21.11 0.00737699 41.1221 6582.02 0.00 7095.27 7095.27
ROOM_2_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_3 FAN COIL 13232.263 -999.000 1.248444 0.00047262 -999.000 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 16:40:00 unknown 7/21 16:40:00 13232.26 13187.91 1.248444 22.70 14.50 0.00851786 12.80 10.82 0.00850000 36.63 0.00686912 17.72 0.0000 21.11 0.00851786 47.3929 11059.32 0.00 15206.60 14582.61
ROOM_2_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_3 FAN COIL 6575.240 6575.240 0.326859 0.00005752 187.915 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 6575.24 6575.24 0.326859 21.11 12.94 0.00737648 40.00 19.53 0.00800000 -5.20 0.00280840 -5.20 0.0000 21.11 0.00737648 41.1193 6575.47 0.00 7088.21 7088.21
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT19_FLR_3 FAN COIL 80829.736 -999.000 7.660726 0.00288700 -999.000 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 14:10:00 unknown 7/21 14:10:00 80829.74 80829.74 7.660726 22.70 14.45 0.00845810 12.80 10.78 0.00845810 38.10 0.00687148 18.17 0.0000 21.11 0.00845810 47.0641 67864.35 0.00 92978.76 89948.01
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT19_FLR_3 FAN COIL 37721.688 37721.688 1.875229 0.00033001 1078.033 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 37721.69 37721.69 1.875229 21.11 12.98 0.00741847 40.00 19.53 0.00800000 -5.20 0.00280840 -5.20 0.0000 21.11 0.00741847 41.3491 37722.34 0.00 40664.98 40664.98
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_4_MULT19_FLR_3 FAN COIL 90352.222 -999.000 8.245766 0.00322711 -999.000 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 15:30:00 unknown 7/21 15:30:00 90352.22 87820.21 8.245766 22.70 14.61 0.00865314 12.80 10.82 0.00850000 37.71 0.00687086 18.05 0.0000 21.11 0.00865314 48.1364 73041.28 0.00 103614.50 96525.49
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_4_MULT19_FLR_3 FAN COIL 37617.709 37617.709 1.870060 0.00032910 1075.062 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 37617.71 37617.71 1.870060 21.11 12.98 0.00741690 40.00 19.53 0.00800000 -5.20 0.00280840 -5.20 0.0000 21.11 0.00741690 41.3404 37618.36 0.00 40552.89 40552.89
ROOM_5_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_5_FLR_3 FAN COIL 11674.396 -999.000 1.101060 0.00041697 -999.000 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 10:20:00 unknown 7/21 10:20:00 11674.40 11632.08 1.101060 22.70 14.50 0.00851932 12.80 10.82 0.00850000 33.81 0.00686464 16.84 0.0000 21.11 0.00851932 47.4009 9753.73 0.00 13419.41 12863.85
ROOM_5_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_5_FLR_3 FAN COIL 6569.520 6569.520 0.326575 0.00005747 187.751 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 6569.52 6569.52 0.326575 21.11 12.94 0.00737596 40.00 19.53 0.00800000 -5.20 0.00280840 -5.20 0.0000 21.11 0.00737596 41.1164 6569.75 0.00 7082.05 7082.05
ROOM_6_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_6_FLR_3 FAN COIL 11579.509 -999.000 1.092090 0.00041359 -999.000 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 10:10:00 unknown 7/21 10:10:00 11579.51 11537.38 1.092090 22.70 14.50 0.00851940 12.80 10.82 0.00850000 33.48 0.00686412 16.74 0.0000 21.11 0.00851940 47.4013 9674.27 0.00 13310.33 12759.07
ROOM_6_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_6_FLR_3 FAN COIL 6562.974 6562.974 0.326250 0.00005742 187.564 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 6562.97 6562.97 0.326250 21.11 12.94 0.00737546 40.00 19.53 0.00800000 -5.20 0.00280840 -5.20 0.0000 21.11 0.00737546 41.1136 6563.21 0.00 7074.99 7074.99
CORRIDOR_FLR_3 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORRIDOR_FLR_3 VAV BOX 16345.587 16345.587 1.355013 0.00014300 372.715 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 16345.59 16345.59 1.355013 16.70 11.86 0.00800000 40.00 19.53 0.00800000 -5.20 0.00280840 -5.20 0.0000 21.00 0.00749556 42.0586 10146.72 0.00 16433.52 16433.52
ROOM_1_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_6 FAN COIL 3611.779 -999.000 0.340889 0.00012900 -999.000 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 16:30:00 unknown 7/21 16:30:00 3611.78 3600.64 0.340889 22.70 14.50 0.00851643 12.80 10.82 0.00850000 36.80 0.00686940 17.78 0.0000 21.11 0.00851643 47.3850 3019.76 0.00 4150.79 3981.71
ROOM_1_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_6 FAN COIL 2054.069 2054.069 0.102109 0.00001797 58.700 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 2054.07 2054.07 0.102109 21.11 13.04 0.00748863 40.00 19.53 0.00800000 -5.20 0.00280840 -5.20 0.0000 21.11 0.00748863 41.7370 2054.14 0.00 2214.32 2214.32
ROOM_2_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_6 FAN COIL 3582.235 -999.000 0.338090 0.00012795 -999.000 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 16:30:00 unknown 7/21 16:30:00 3582.23 3571.11 0.338090 22.70 14.50 0.00851655 12.80 10.82 0.00850000 36.80 0.00686940 17.78 0.0000 21.11 0.00851655 47.3856 2994.96 0.00 4116.82 3949.02
ROOM_2_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_6 FAN COIL 2053.246 2053.246 0.102068 0.00001796 58.676 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 2053.25 2053.25 0.102068 21.11 13.04 0.00748848 40.00 19.53 0.00800000 -5.20 0.00280840 -5.20 0.0000 21.11 0.00748848 41.7362 2053.32 0.00 2213.43 2213.43
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT9_FLR_6 FAN COIL 16581.749 -999.000 1.542050 0.00059225 -999.000 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 14:10:00 unknown 7/21 14:10:00 16581.75 16347.69 1.542050 22.70 14.55 0.00857605 12.80 10.82 0.00850000 38.10 0.00687148 18.17 0.0000 21.11 0.00857605 47.7130 13659.77 0.00 19041.16 18030.84
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT9_FLR_6 FAN COIL 9915.527 9915.527 0.492913 0.00008675 283.355 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 9915.53 9915.53 0.492913 21.11 13.06 0.00750998 40.00 19.53 0.00800000 -5.20 0.00280840 -5.20 0.0000 21.11 0.00750998 41.8540 9915.80 0.00 10689.13 10689.13
BANQUET_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 18979.288 18979.288 2.627215 0.00016604 408.036 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 18979.29 18979.29 2.627215 16.70 11.86 0.00800000 40.00 19.53 0.00800000 -5.20 0.00280840 -5.20 0.0000 21.00 0.00761890 42.7428 6958.28 0.00 19084.87 19084.87
DINING_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 19688.337 19688.337 2.754321 0.00017224 422.903 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 23:40:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 23:40:00 19688.34 19688.34 2.754321 16.70 11.86 0.00800000 40.00 19.53 0.00800000 -5.20 0.00280840 -5.20 0.0000 21.00 0.00762527 42.7783 7085.83 0.00 19797.89 19797.89
KITCHEN_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 13990.362 13990.362 2.621738 0.00012239 294.268 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 23:30:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 23:30:00 13990.36 13990.36 2.621738 16.70 11.86 0.00800000 40.00 19.53 0.00800000 -5.20 0.00280840 -5.20 0.0000 21.00 0.00636664 35.7965 2031.68 0.00 14068.75 14068.75
CORRIDOR_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORRIDOR_FLR_6 VAV BOX 11230.011 11230.011 0.840029 0.00009825 260.374 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 23:40:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 23:40:00 11230.01 11230.01 0.840029 16.70 11.86 0.00800000 40.00 19.53 0.00800000 -5.20 0.00280840 -5.20 0.0000 21.00 0.00768134 43.0887 7385.91 0.00 11290.09 11290.09
VAV WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoopHVAC VAV WITH REHEAT 729331.555 -999.000 25.039179 0.02605003 -999.000 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 729331.56 729331.55 25.039179 38.10 18.17 0.00687148 10.69 8.30 0.00687148 38.10 0.00687148 18.17 100.0000 23.99 0.00961027 44.8090 298671.58 0.00 666374.53 666374.53
VAV WITH REHEAT HEATING COIL Coil:Heating:Water AirLoopHVAC VAV WITH REHEAT 172635.014 172635.014 7.511754 0.00151029 2930.658 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 172635.01 172635.01 7.511754 -5.20 -5.20 0.00280840 16.70 11.86 0.00800000 -5.20 0.00280840 -5.20 333.3333 21.69 0.00613341 33.0624 67206.29 0.00 157216.12 157216.12
FLR_3_DOAS COOLING COIL Coil:Cooling:Water AirLoopHVAC FLR_3_DOAS 57348.723 -999.000 2.051317 0.00204836 -999.000 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 15:20:00 57348.72 57348.72 2.051317 38.10 18.17 0.00687148 11.79 8.78 0.00687148 38.10 0.00687148 18.17 99.9965 21.11 0.00855905 47.6192 198032.57 0.00 51614.51 51614.51
FLR_3_DOAS HEATING COIL Coil:Heating:Water AirLoopHVAC FLR_3_DOAS 14143.003 14143.003 0.615395 0.00012373 240.092 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 14143.00 14143.00 0.615395 -5.20 -5.20 0.00280840 16.70 11.86 0.00800000 -5.20 0.00280840 -5.20 333.3216 21.11 0.00741839 41.3487 115654.40 0.00 12879.82 12879.82



Table of Contents

Report: Coil Sizing Details

For: Entire Facility

Timestamp: 2023-10-16 08:58:10

Coils

Coil Type Coil Location HVAC Type HVAC Name Zone Name(s) System Sizing Method Concurrence System Sizing Method Capacity System Sizing Method Air Flow Autosized Coil Capacity? Autosized Coil Airflow? Autosized Coil Water Flow? OA Pretreated prior to coil inlet? Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Terminal Unit Reheat Coil Multiplier DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio Moist Air Heat Capacity [J/kg-K] Dry Air Heat Capacity [J/kg-K] Standard Air Density Adjusted for Elevation [kg/m3] Supply Fan Name for Coil Supply Fan Type for Coil Supply Fan Maximum Air Volume Flow Rate [m3/s] Supply Fan Maximum Air Mass Flow Rate [kg/s] Plant Name for Coil Plant Fluid Specific Heat Capacity [J/kg-K] Plant Fluid Density [kg/m3] Plant Maximum Fluid Mass Flow Rate [kg/s] Plant Design Fluid Return Temperature [C] Plant Design Fluid Supply Temperature [C] Plant Design Fluid Temperature Difference [deltaC] Plant Design Capacity [W] Coil Capacity Percentage of Plant Design Capacity [%] Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Total Ideal Loads Peak Date/Time at Total Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Peak Load Type to Size On Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] Supply Fan Air Heat Gain at Ideal Loads Peak [W] Coil and Fan Net Total Capacity at Ideal Loads Peak [W] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] Outdoor Air Flow Percentage at Ideal Loads Peak [%] System Return Air Drybulb at Ideal Loads Peak [C] System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W] Coil Air Mass Flow Rate at Rating Conditions [kg/s] Coil Entering Air Drybulb at Rating Conditions [C] Coil Entering Air Wetbulb at Rating Conditions [C] Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] Coil Leaving Air Drybulb at Rating Conditions [C] Coil Leaving Air Wetbulb at Rating Conditions [C] Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K]
BASEMENT VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT BASEMENT VAV BOX BASEMENT N/A N/A N/A Yes Yes Yes No 13021.183 13021.183 2.843585 0.00011391 271.534 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0443 unknown unknown -999.0 -999.0   4197.9300 999.8980 4.24050511 54.44 82.22 27.78 494521.33 2.6331 2.686080 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 13021.18 13021.18 1.0000 2.96964566 2.843585 16.70 11.86 0.00800000 37036.7 40.00 19.53 0.00800000 60796.0 0.11390337 60.00 32.22 27.78 0.000 13021.18 -5.20 0.00280840 -5.20 0.00000000 0.0000 21.00 0.00800000 21.00 0.00800000 44.8527 0.00 0.00 13094.37 13094.37 2.96964566 16.60 13.15 0.00800000 36934.7 20.92 14.82 0.00800000 41344.1
RETAIL_1_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT RETAIL_1_FLR_1 VAV BOX RETAIL_1_FLR_1 N/A N/A N/A Yes Yes Yes No 4770.421 4770.421 0.387412 0.00004173 109.122 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0443 unknown unknown -999.0 -999.0   4197.9300 999.8980 4.24050511 54.44 82.22 27.78 494521.33 0.9647 0.984068 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 4770.42 4770.42 1.0000 0.40458635 0.387412 16.70 11.86 0.00800000 37036.7 40.00 19.53 0.00800000 60796.0 0.04172947 60.00 32.22 27.78 0.000 4770.42 -5.20 0.00280840 -5.20 0.00000000 0.0000 21.00 0.00740404 21.00 0.00740404 41.5530 2998.72 0.00 4796.05 4796.05 0.40458635 16.60 13.15 0.00800000 36934.7 28.23 17.44 0.00800000 48789.0
RETAIL_2_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT RETAIL_2_FLR_1 VAV BOX RETAIL_2_FLR_1 N/A N/A N/A Yes Yes Yes No 2266.373 2266.373 0.282793 0.00001983 49.182 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0443 unknown unknown -999.0 -999.0   4197.9300 999.8980 4.24050511 54.44 82.22 27.78 494521.33 0.4583 0.467520 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 2266.37 2266.37 1.0000 0.29532925 0.282793 16.70 11.86 0.00800000 37036.7 40.00 19.53 0.00800000 60796.0 0.01982519 60.00 32.22 27.78 0.000 2266.37 -5.20 0.00280840 -5.20 0.00000000 0.0000 21.00 0.00730618 21.00 0.00730618 41.0087 973.16 0.00 2278.95 2278.95 0.29532925 16.60 13.15 0.00800000 36934.7 24.17 16.02 0.00800000 44651.4
MECH_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT MECH_FLR_1 VAV BOX MECH_FLR_1 N/A N/A N/A Yes Yes Yes No 3192.023 3192.023 0.302822 0.00002793 71.415 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0443 unknown unknown -999.0 -999.0   4197.9300 999.8980 4.24050511 54.44 82.22 27.78 494521.33 0.6455 0.658468 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 3192.02 3192.02 1.0000 0.31624634 0.302822 16.70 11.86 0.00800000 37036.7 40.00 19.53 0.00800000 60796.0 0.02792236 60.00 32.22 27.78 0.000 3192.02 -5.20 0.00280840 -5.20 0.00000000 0.0000 21.00 0.00714817 21.00 0.00714817 40.1319 1807.63 0.00 3209.32 3209.32 0.31624634 16.60 13.15 0.00800000 36934.7 26.55 16.86 0.00800000 47082.9
STORAGE_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT STORAGE_FLR_1 VAV BOX STORAGE_FLR_1 N/A N/A N/A Yes Yes Yes No 1782.115 1782.115 0.152937 0.00001559 40.427 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0443 unknown unknown -999.0 -999.0   4197.9300 999.8980 4.24050511 54.44 82.22 27.78 494521.33 0.3604 0.367624 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 1782.12 1782.12 1.0000 0.15971647 0.152937 16.70 11.86 0.00800000 37036.7 40.00 19.53 0.00800000 60796.0 0.01558913 60.00 32.22 27.78 0.000 1782.12 -5.20 0.00280840 -5.20 0.00000000 0.0000 21.00 0.00717464 21.00 0.00717464 40.2789 1082.91 0.00 1791.72 1791.72 0.15971647 16.60 13.15 0.00800000 36934.7 27.60 17.22 0.00800000 48152.9
LAUNDRY_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown LAUNDRY_FLR_1 N/A N/A N/A Yes Yes Yes No 19667.588 19667.588 3.770679 0.00017206 413.112 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0443 unknown unknown -999.0 -999.0   4197.9300 999.8980 4.24050511 54.44 82.22 27.78 494521.33 3.9771 4.057137 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 19667.59 19667.59 1.0000 3.93783934 3.770679 16.70 11.86 0.00800000 37036.7 40.00 19.53 0.00800000 60796.0 0.17204309 60.00 32.22 27.78 0.000 19667.59 -5.20 0.00280840 -5.20 0.00000000 0.0000 21.00 0.00713766 21.00 0.00713766 40.0751 2432.06 0.00 19777.84 19777.84 3.93783934 16.60 13.15 0.00800000 36934.7 21.53 15.05 0.00800000 41957.2
CAFE_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CAFE_FLR_1 VAV BOX CAFE_FLR_1 N/A N/A N/A Yes Yes Yes No 15073.104 15073.104 1.647800 0.00013187 331.539 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0443 unknown unknown -999.0 -999.0   4197.9300 999.8980 4.24050511 54.44 82.22 27.78 494521.33 3.0480 3.109362 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 15073.10 15073.10 1.0000 1.72084947 1.647800 16.70 11.86 0.00800000 37036.7 40.00 19.53 0.00800000 60796.0 0.13185264 60.00 32.22 27.78 0.000 15073.10 -5.20 0.00280840 -5.20 0.00000000 0.0000 21.00 0.00746845 21.00 0.00746845 41.9098 7536.22 0.00 15155.32 15155.32 1.72084947 16.60 13.15 0.00800000 36934.7 25.24 16.40 0.00800000 45741.6
LOBBY_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown LOBBY_FLR_1 N/A N/A N/A Yes Yes Yes No 42329.066 42329.066 5.443297 0.00037031 915.984 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0443 unknown unknown -999.0 -999.0   4197.9300 999.8980 4.24050511 54.44 82.22 27.78 494521.33 8.5596 8.731869 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 42329.07 42329.07 1.0000 5.68460753 5.443297 16.70 11.86 0.00800000 37036.7 40.00 19.53 0.00800000 60796.0 0.37027536 60.00 32.22 27.78 0.000 42329.07 -5.20 0.00280840 -5.20 0.00000000 0.0000 21.00 0.00735889 21.00 0.00735889 41.3011 17434.45 0.00 42564.09 42564.09 5.68460753 16.60 13.15 0.00800000 36934.7 23.94 15.93 0.00800000 44422.3
ROOM_1_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_3 FAN COIL ROOM_1_FLR_3 N/A N/A N/A Yes Yes Yes No 13327.530 -999.000 1.257465 0.00047602 -999.000 -999.0000 1.00000 1.00000 1020.6741 1004.8586 1.0443 ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 1.257465 1.31321053   4197.9300 999.8980 36.83714336 13.37 6.70 6.67 1031447.13 1.2921 1.292095 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 16:30:00 unknown unknown unknown 7/21 16:30:00 Sensible 13327.53 13283.11 1.0000 1.31321053 1.257465 22.70 14.50 0.00851776 44471.0 12.80 10.82 0.00850000 34322.2 0.47597105 6.70 13.37 6.67 0.000 13327.53 36.80 0.00686940 17.78 0.00000000 0.0000 21.11 0.00851776 21.11 0.00851776 47.3923 11139.23 0.00 15316.11 14687.96 1.31321053 22.70 15.94 0.00851776 44471.0 11.74 11.48 0.00832816 32807.9
ROOM_1_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_3 FAN COIL ROOM_1_FLR_3 N/A N/A N/A Yes Yes Yes No 6581.784 6581.784 0.327185 0.00005758 188.101 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0443 ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 1.257465 1.31321053   4197.9300 999.8980 4.24050511 54.44 82.22 27.78 494521.33 1.3309 1.357726 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 6581.78 6581.78 1.0000 0.34168945 0.327185 21.11 12.94 0.00737699 39950.9 40.00 19.53 0.00800000 60796.0 0.05757444 60.00 32.22 27.78 0.000 6581.78 -5.20 0.00280840 -5.20 0.00000000 0.0000 21.11 0.00737699 21.11 0.00737699 41.1221 6582.02 0.00 7095.27 7095.27 0.34168945 16.60 12.54 0.00737699 35357.4 36.99 19.80 0.00737699 56122.6
ROOM_2_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_3 FAN COIL ROOM_2_FLR_3 N/A N/A N/A Yes Yes Yes No 13232.263 -999.000 1.248444 0.00047262 -999.000 -999.0000 1.00000 1.00000 1020.6743 1004.8586 1.0443 ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 1.248444 1.30379007   4197.9300 999.8980 36.83714336 13.37 6.70 6.67 1031447.13 1.2829 1.282859 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 16:40:00 unknown unknown unknown 7/21 16:40:00 Sensible 13232.26 13187.91 1.0000 1.30379007 1.248444 22.70 14.50 0.00851786 44471.3 12.80 10.82 0.00850000 34322.2 0.47256874 6.70 13.37 6.67 0.000 13232.26 36.63 0.00686912 17.72 0.00000000 0.0000 21.11 0.00851786 21.11 0.00851786 47.3929 11059.32 0.00 15206.60 14582.61 1.30379007 22.70 15.94 0.00851786 44471.3 11.74 11.48 0.00832815 32807.9
ROOM_2_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_3 FAN COIL ROOM_2_FLR_3 N/A N/A N/A Yes Yes Yes No 6575.240 6575.240 0.326859 0.00005752 187.915 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0443 ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 1.248444 1.30379007   4197.9300 999.8980 4.24050511 54.44 82.22 27.78 494521.33 1.3296 1.356376 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 6575.24 6575.24 1.0000 0.34134974 0.326859 21.11 12.94 0.00737648 39949.7 40.00 19.53 0.00800000 60796.0 0.05751720 60.00 32.22 27.78 0.000 6575.24 -5.20 0.00280840 -5.20 0.00000000 0.0000 21.11 0.00737648 21.11 0.00737648 41.1193 6575.47 0.00 7088.21 7088.21 0.34134974 16.60 12.54 0.00737648 35356.1 36.99 19.80 0.00737648 56121.4
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT19_FLR_3 FAN COIL ROOM_3_MULT19_FLR_3 N/A N/A N/A Yes Yes Yes No 80829.736 -999.000 7.660726 0.00288700 -999.000 -999.0000 1.00000 1.00000 1020.5632 1004.8586 1.0443 ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 7.660726 8.00033924   4197.9300 999.8980 36.83714336 13.37 6.70 6.67 1031447.13 7.8365 7.836391 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 14:10:00 unknown unknown unknown 7/21 14:10:00 Sensible 80829.74 80829.74 1.0000 8.00033924 7.660726 22.70 14.45 0.00845810 44319.7 12.80 10.78 0.00845810 34216.4 2.88670248 6.70 13.37 6.67 0.000 80829.74 38.10 0.00687148 18.17 0.00000000 0.0000 21.11 0.00845810 21.11 0.00845810 47.0641 67864.35 0.00 92978.76 89948.01 8.00033924 22.70 15.89 0.00845810 44319.7 11.68 11.44 0.00830793 32697.8
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT19_FLR_3 FAN COIL ROOM_3_MULT19_FLR_3 N/A N/A N/A Yes Yes Yes No 37721.688 37721.688 1.875229 0.00033001 1078.033 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0443 ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 7.660726 8.00033924   4197.9300 999.8980 4.24050511 54.44 82.22 27.78 494521.33 7.6279 7.781434 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 37721.69 37721.69 1.0000 1.95836160 1.875229 21.11 12.98 0.00741847 40056.9 40.00 19.53 0.00800000 60796.0 0.32997212 60.00 32.22 27.78 0.000 37721.69 -5.20 0.00280840 -5.20 0.00000000 0.0000 21.11 0.00741847 21.11 0.00741847 41.3491 37722.34 0.00 40664.98 40664.98 1.95836160 16.60 12.58 0.00741847 35462.4 36.99 19.84 0.00741847 56227.2
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_4_MULT19_FLR_3 FAN COIL ROOM_4_MULT19_FLR_3 N/A N/A N/A Yes Yes Yes No 90352.222 -999.000 8.245766 0.00322711 -999.000 -999.0000 1.00000 1.00000 1020.9258 1004.8586 1.0443 ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 8.245766 8.61131531   4197.9300 999.8980 36.83714336 13.37 6.70 6.67 1031447.13 8.7598 8.759590 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 15:30:00 unknown unknown unknown 7/21 15:30:00 Sensible 90352.22 87820.21 1.0000 8.61131531 8.245766 22.70 14.61 0.00865314 44814.5 12.80 10.82 0.00850000 34322.2 3.22678255 6.70 13.37 6.67 0.000 90352.22 37.71 0.00687086 18.05 0.00000000 0.0000 21.11 0.00865314 21.11 0.00865314 48.1364 73041.28 0.00 103614.50 96525.49 8.61131531 22.70 16.06 0.00865314 44814.5 11.72 11.47 0.00832682 32782.1
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_4_MULT19_FLR_3 FAN COIL ROOM_4_MULT19_FLR_3 N/A N/A N/A Yes Yes Yes No 37617.709 37617.709 1.870060 0.00032910 1075.062 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0443 ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 8.245766 8.61131531   4197.9300 999.8980 4.24050511 54.44 82.22 27.78 494521.33 7.6069 7.759985 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 37617.71 37617.71 1.0000 1.95296345 1.870060 21.11 12.98 0.00741690 40053.0 40.00 19.53 0.00800000 60796.0 0.32906256 60.00 32.22 27.78 0.000 37617.71 -5.20 0.00280840 -5.20 0.00000000 0.0000 21.11 0.00741690 21.11 0.00741690 41.3404 37618.36 0.00 40552.89 40552.89 1.95296345 16.60 12.58 0.00741690 35458.5 36.99 19.83 0.00741690 56223.2
ROOM_5_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_5_FLR_3 FAN COIL ROOM_5_FLR_3 N/A N/A N/A Yes Yes Yes No 11674.396 -999.000 1.101060 0.00041697 -999.000 -999.0000 1.00000 1.00000 1020.6770 1004.8586 1.0443 ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 1.101060 1.14987188   4197.9300 999.8980 36.83714336 13.37 6.70 6.67 1031447.13 1.1318 1.131825 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 10:20:00 unknown unknown unknown 7/21 10:20:00 Sensible 11674.40 11632.08 1.0000 1.14987188 1.101060 22.70 14.50 0.00851932 44475.0 12.80 10.82 0.00850000 34322.2 0.41693207 6.70 13.37 6.67 0.000 11674.40 33.81 0.00686464 16.84 0.00000000 0.0000 21.11 0.00851932 21.11 0.00851932 47.4009 9753.73 0.00 13419.41 12863.85 1.14987188 22.70 15.94 0.00851932 44475.0 11.74 11.48 0.00832780 32804.6
ROOM_5_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_5_FLR_3 FAN COIL ROOM_5_FLR_3 N/A N/A N/A Yes Yes Yes No 6569.520 6569.520 0.326575 0.00005747 187.751 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0443 ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 1.101060 1.14987188   4197.9300 999.8980 4.24050511 54.44 82.22 27.78 494521.33 1.3285 1.355196 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 6569.52 6569.52 1.0000 0.34105278 0.326575 21.11 12.94 0.00737596 39948.3 40.00 19.53 0.00800000 60796.0 0.05746716 60.00 32.22 27.78 0.000 6569.52 -5.20 0.00280840 -5.20 0.00000000 0.0000 21.11 0.00737596 21.11 0.00737596 41.1164 6569.75 0.00 7082.05 7082.05 0.34105278 16.60 12.54 0.00737596 35354.8 36.99 19.80 0.00737596 56120.1
ROOM_6_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_6_FLR_3 FAN COIL ROOM_6_FLR_3 N/A N/A N/A Yes Yes Yes No 11579.509 -999.000 1.092090 0.00041359 -999.000 -999.0000 1.00000 1.00000 1020.6771 1004.8586 1.0443 ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 1.092090 1.14050404   4197.9300 999.8980 36.83714336 13.37 6.70 6.67 1031447.13 1.1226 1.122626 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 10:10:00 unknown unknown unknown 7/21 10:10:00 Sensible 11579.51 11537.38 1.0000 1.14050404 1.092090 22.70 14.50 0.00851940 44475.2 12.80 10.82 0.00850000 34322.2 0.41354333 6.70 13.37 6.67 0.000 11579.51 33.48 0.00686412 16.74 0.00000000 0.0000 21.11 0.00851940 21.11 0.00851940 47.4013 9674.27 0.00 13310.33 12759.07 1.14050404 22.70 15.94 0.00851940 44475.2 11.74 11.48 0.00832780 32804.6
ROOM_6_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_6_FLR_3 FAN COIL ROOM_6_FLR_3 N/A N/A N/A Yes Yes Yes No 6562.974 6562.974 0.326250 0.00005742 187.564 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0443 ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 1.092090 1.14050404   4197.9300 999.8980 4.24050511 54.44 82.22 27.78 494521.33 1.3271 1.353846 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 6562.97 6562.97 1.0000 0.34071298 0.326250 21.11 12.94 0.00737546 39947.1 40.00 19.53 0.00800000 60796.0 0.05740991 60.00 32.22 27.78 0.000 6562.97 -5.20 0.00280840 -5.20 0.00000000 0.0000 21.11 0.00737546 21.11 0.00737546 41.1136 6563.21 0.00 7074.99 7074.99 0.34071298 16.60 12.54 0.00737546 35353.5 36.99 19.80 0.00737546 56118.8
CORRIDOR_FLR_3 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORRIDOR_FLR_3 VAV BOX CORRIDOR_FLR_3 N/A N/A N/A Yes Yes Yes No 16345.587 16345.587 1.355013 0.00014300 372.715 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0443 unknown unknown -999.0 -999.0   4197.9300 999.8980 4.24050511 54.44 82.22 27.78 494521.33 3.3053 3.371856 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 16345.59 16345.59 1.0000 1.41508301 1.355013 16.70 11.86 0.00800000 37036.7 40.00 19.53 0.00800000 60796.0 0.14298374 60.00 32.22 27.78 0.000 16345.59 -5.20 0.00280840 -5.20 0.00000000 0.0000 21.00 0.00749556 21.00 0.00749556 42.0586 10146.72 0.00 16433.52 16433.52 1.41508301 16.60 13.15 0.00800000 36934.7 27.99 17.36 0.00800000 48547.8
ROOM_1_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_6 FAN COIL ROOM_1_FLR_6 N/A N/A N/A Yes Yes Yes No 3611.779 -999.000 0.340889 0.00012900 -999.000 -999.0000 1.00000 1.00000 1020.6716 1004.8586 1.0443 ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.340889 0.35600076   4197.9300 999.8980 36.83714336 13.37 6.70 6.67 1031447.13 0.3502 0.350160 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 16:30:00 unknown unknown unknown 7/21 16:30:00 Sensible 3611.78 3600.64 1.0000 0.35600076 0.340889 22.70 14.50 0.00851643 44467.6 12.80 10.82 0.00850000 34322.2 0.12898882 6.70 13.37 6.67 0.000 3611.78 36.80 0.00686940 17.78 0.00000000 0.0000 21.11 0.00851643 21.11 0.00851643 47.3850 3019.76 0.00 4150.79 3981.71 0.35600076 22.70 15.94 0.00851643 44467.6 11.74 11.48 0.00832817 32808.1
ROOM_1_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_6 FAN COIL ROOM_1_FLR_6 N/A N/A N/A Yes Yes Yes No 2054.069 2054.069 0.102109 0.00001797 58.700 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0443 ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.340889 0.35600076   4197.9300 999.8980 4.24050511 54.44 82.22 27.78 494521.33 0.4154 0.423725 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 2054.07 2054.07 1.0000 0.10663580 0.102109 21.11 13.04 0.00748863 40234.5 40.00 19.53 0.00800000 60796.0 0.01796806 60.00 32.22 27.78 0.000 2054.07 -5.20 0.00280840 -5.20 0.00000000 0.0000 21.11 0.00748863 21.11 0.00748863 41.7370 2054.14 0.00 2214.32 2214.32 0.10663580 16.60 12.65 0.00748863 35640.0 36.98 19.89 0.00748863 56405.3
ROOM_2_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_6 FAN COIL ROOM_2_FLR_6 N/A N/A N/A Yes Yes Yes No 3582.235 -999.000 0.338090 0.00012795 -999.000 -999.0000 1.00000 1.00000 1020.6718 1004.8586 1.0443 ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.338090 0.35307789   4197.9300 999.8980 36.83714336 13.37 6.70 6.67 1031447.13 0.3473 0.347295 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 16:30:00 unknown unknown unknown 7/21 16:30:00 Sensible 3582.23 3571.11 1.0000 0.35307789 0.338090 22.70 14.50 0.00851655 44467.9 12.80 10.82 0.00850000 34322.2 0.12793369 6.70 13.37 6.67 0.000 3582.23 36.80 0.00686940 17.78 0.00000000 0.0000 21.11 0.00851655 21.11 0.00851655 47.3856 2994.96 0.00 4116.82 3949.02 0.35307789 22.70 15.94 0.00851655 44467.9 11.74 11.48 0.00832817 32808.1
ROOM_2_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_6 FAN COIL ROOM_2_FLR_6 N/A N/A N/A Yes Yes Yes No 2053.246 2053.246 0.102068 0.00001796 58.676 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0443 ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.338090 0.35307789   4197.9300 999.8980 4.24050511 54.44 82.22 27.78 494521.33 0.4152 0.423555 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 2053.25 2053.25 1.0000 0.10659305 0.102068 21.11 13.04 0.00748848 40234.2 40.00 19.53 0.00800000 60796.0 0.01796086 60.00 32.22 27.78 0.000 2053.25 -5.20 0.00280840 -5.20 0.00000000 0.0000 21.11 0.00748848 21.11 0.00748848 41.7362 2053.32 0.00 2213.43 2213.43 0.10659305 16.60 12.65 0.00748848 35639.7 36.98 19.89 0.00748848 56404.9
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT9_FLR_6 FAN COIL ROOM_3_MULT9_FLR_6 N/A N/A N/A Yes Yes Yes No 16581.749 -999.000 1.542050 0.00059225 -999.000 -999.0000 1.00000 1.00000 1020.7824 1004.8586 1.0443 ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 1.542050 1.61041201   4197.9300 999.8980 36.83714336 13.37 6.70 6.67 1031447.13 1.6076 1.607590 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 14:10:00 unknown unknown unknown 7/21 14:10:00 Sensible 16581.75 16347.69 1.0000 1.61041201 1.542050 22.70 14.55 0.00857605 44618.8 12.80 10.82 0.00850000 34322.2 0.59219016 6.70 13.37 6.67 0.000 16581.75 38.10 0.00687148 18.17 0.00000000 0.0000 21.11 0.00857605 21.11 0.00857605 47.7130 13659.77 0.00 19041.16 18030.84 1.61041201 22.70 15.99 0.00857605 44618.8 11.73 11.48 0.00832736 32795.0
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT9_FLR_6 FAN COIL ROOM_3_MULT9_FLR_6 N/A N/A N/A Yes Yes Yes No 9915.527 9915.527 0.492913 0.00008675 283.355 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0443 ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 1.542050 1.61041201   4197.9300 999.8980 4.24050511 54.44 82.22 27.78 494521.33 2.0051 2.045429 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 9915.53 9915.53 1.0000 0.51476444 0.492913 21.11 13.06 0.00750998 40289.0 40.00 19.53 0.00800000 60796.0 0.08673651 60.00 32.22 27.78 0.000 9915.53 -5.20 0.00280840 -5.20 0.00000000 0.0000 21.11 0.00750998 21.11 0.00750998 41.8540 9915.80 0.00 10689.13 10689.13 0.51476444 16.60 12.67 0.00750998 35694.1 36.98 19.90 0.00750998 56459.2
BANQUET_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown BANQUET_FLR_6 N/A N/A N/A Yes Yes Yes No 18979.288 18979.288 2.627215 0.00016604 408.036 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0443 unknown unknown -999.0 -999.0   4197.9300 999.8980 4.24050511 54.44 82.22 27.78 494521.33 3.8379 3.915150 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 18979.29 18979.29 1.0000 2.74368389 2.627215 16.70 11.86 0.00800000 37036.7 40.00 19.53 0.00800000 60796.0 0.16602215 60.00 32.22 27.78 0.000 18979.29 -5.20 0.00280840 -5.20 0.00000000 0.0000 21.00 0.00761890 21.00 0.00761890 42.7428 6958.28 0.00 19084.87 19084.87 2.74368389 16.60 13.15 0.00800000 36934.7 23.42 15.75 0.00800000 43890.7
DINING_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown DINING_FLR_6 N/A N/A N/A Yes Yes Yes No 19688.337 19688.337 2.754321 0.00017224 422.903 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0443 unknown unknown -999.0 -999.0   4197.9300 999.8980 4.24050511 54.44 82.22 27.78 494521.33 3.9813 4.061417 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 23:40:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 23:40:00 Sensible 19688.34 19688.34 1.0000 2.87642455 2.754321 16.70 11.86 0.00800000 37036.7 40.00 19.53 0.00800000 60796.0 0.17222459 60.00 32.22 27.78 0.000 19688.34 -5.20 0.00280840 -5.20 0.00000000 0.0000 21.00 0.00762527 21.00 0.00762527 42.7783 7085.83 0.00 19797.89 19797.89 2.87642455 16.60 13.15 0.00800000 36934.7 23.35 15.72 0.00800000 43817.5
KITCHEN_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown KITCHEN_FLR_6 N/A N/A N/A Yes Yes Yes No 13990.362 13990.362 2.621738 0.00012239 294.268 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0443 unknown unknown -999.0 -999.0   4197.9300 999.8980 4.24050511 54.44 82.22 27.78 494521.33 2.8291 2.886008 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 23:30:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 23:30:00 Sensible 13990.36 13990.36 1.0000 2.73796378 2.621738 16.70 11.86 0.00800000 37036.7 40.00 19.53 0.00800000 60796.0 0.12238131 60.00 32.22 27.78 0.000 13990.36 -5.20 0.00280840 -5.20 0.00000000 0.0000 20.53 0.00636664 21.00 0.00636664 35.7965 2031.68 0.00 14068.75 14068.75 2.73796378 16.60 13.15 0.00800000 36934.7 21.64 15.09 0.00800000 42073.1
CORRIDOR_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORRIDOR_FLR_6 VAV BOX CORRIDOR_FLR_6 N/A N/A N/A Yes Yes Yes No 11230.011 11230.011 0.840029 0.00009825 260.374 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0443 unknown unknown -999.0 -999.0   4197.9300 999.8980 4.24050511 54.44 82.22 27.78 494521.33 2.2709 2.316588 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 23:40:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 23:40:00 Sensible 11230.01 11230.01 1.0000 0.87726856 0.840029 16.70 11.86 0.00800000 37036.7 40.00 19.53 0.00800000 60796.0 0.09823502 60.00 32.22 27.78 0.000 11230.01 -5.20 0.00280840 -5.20 0.00000000 0.0000 21.00 0.00768134 21.00 0.00768134 43.0887 7385.91 0.00 11290.09 11290.09 0.87726856 16.60 13.15 0.00800000 36934.7 29.22 17.78 0.00800000 49804.3
VAV WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC VAV WITH REHEAT BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; Coincident CoolingDesignCapacity N/A Yes Yes Yes No 729331.555 -999.000 25.039179 0.02605003 -999.000 -999.0000 1.00000 1.00000 1017.6137 1004.8586 1.0443 VAV WITH REHEAT FAN Fan:VariableVolume 25.039179 26.14920951   4197.9300 999.8980 36.83714336 13.37 6.70 6.67 1031447.13 70.7095 70.709544 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 Sensible 729331.56 729331.55 1.0000 26.14920951 25.039179 38.10 18.17 0.00687148 55956.2 10.69 8.30 0.00687148 28065.1 26.04737592 6.70 13.37 6.67 56103.752 673227.80 38.10 0.00687148 18.17 25.03918000 100.0000 23.99 0.00961308 23.99 0.00961027 44.8090 298671.58 0.00 666374.53 666374.53 26.14920951 38.10 19.77 0.00687148 55956.2 13.06 10.53 0.00687148 30472.7
VAV WITH REHEAT HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC VAV WITH REHEAT BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 172635.014 172635.014 7.511754 0.00151029 2930.658 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.0443 VAV WITH REHEAT FAN Fan:VariableVolume 25.039179 26.14920951   4197.9300 999.8980 4.24050511 54.44 82.22 27.78 494521.33 34.9095 35.612086 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 172635.01 172635.01 1.0000 7.84476285 7.511754 -5.20 -5.20 0.00280840 1771.3 16.70 11.86 0.00800000 37036.7 1.51013234 60.00 32.22 27.78 0.000 172635.01 -5.20 0.00280840 -5.20 25.03918000 333.3333 18.59 0.00689841 21.69 0.00613341 33.0624 67206.29 0.00 157216.12 157216.12 7.84476285 2.80 0.24 0.00280840 9851.8 22.64 10.36 0.00280840 29892.7
FLR_3_DOAS COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC FLR_3_DOAS ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; Coincident CoolingDesignCapacity N/A Yes Yes Yes No 57348.723 -999.000 2.051317 0.00204836 -999.000 -999.0000 1.00000 1.00000 1017.6137 1004.8586 1.0443 FLR_3_DOAS FAN Fan:ConstantVolume 2.051245 2.14218037   4197.9300 999.8980 36.83714336 13.37 6.70 6.67 1031447.13 5.5600 5.560025 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 15:20:00 Sensible 57348.72 57348.72 1.0000 2.14225568 2.051317 38.10 18.17 0.00687148 55956.2 11.79 8.78 0.00687148 29186.0 2.04815455 6.70 13.37 6.67 2195.006 55153.72 38.10 0.00687148 18.17 2.05124512 99.9965 21.11 0.00855189 21.11 0.00855905 47.6192 198032.57 0.00 51614.51 51614.51 2.14225568 38.10 19.77 0.00687148 55956.2 14.42 11.12 0.00687148 31862.7
FLR_3_DOAS HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC FLR_3_DOAS ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 14143.003 14143.003 0.615395 0.00012373 240.092 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.0443 FLR_3_DOAS FAN Fan:ConstantVolume 2.051245 2.14218037   4197.9300 999.8980 4.24050511 54.44 82.22 27.78 494521.33 2.8599 2.917495 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 14143.00 14143.00 1.0000 0.64267671 0.615395 -5.20 -5.20 0.00280840 1771.3 16.70 11.86 0.00800000 37036.7 0.12371654 60.00 32.22 27.78 0.000 14143.00 -5.20 0.00280840 -5.20 2.05124512 333.3216 21.11 0.00741869 21.11 0.00741839 41.3487 115654.40 0.00 12879.82 12879.82 0.64267671 2.80 0.24 0.00280840 9851.8 22.64 10.36 0.00280840 29892.7



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2023-10-16 08:58:10

Economizer

High Limit Shutoff Control Minimum Outdoor Air [m3/s] Maximum Outdoor Air [m3/s] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [C] Outdoor Air Enthalpy Limit [C]
VAV WITH REHEAT_OA_CONTROLLER DifferentialDryBulb 25.04 25.04 -      
FLR_3_DOAS_OA_CONTROLLER DifferentialDryBulb 2.05 2.05 -      


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [m3/s-person] Outdoor Air Per Area [m3/s-m2] Outdoor Air Per Zone [m3/s] Outdoor Air ACH [ach] Outdoor Air Method Outdoor Air Schedule Name Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule Name
BASEMENT VAV WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
RETAIL_1_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.001181 0.000000 0.000000 Flow/Area   1.00 1.00  
RETAIL_2_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.001181 0.000000 0.000000 Flow/Area   1.00 1.00  
MECH_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.000000 0.000000 0.000000 Flow/Area   1.00 1.00  
STORAGE_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.000610 0.000000 0.000000 Flow/Area   1.00 1.00  
LAUNDRY_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.000000 0.000000 0.000000 Flow/Area   1.00 1.00  
CAFE_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.003581 0.000000 0.000000 Flow/Area   1.00 1.00  
LOBBY_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.001448 0.000000 0.000000 Flow/Area   1.00 1.00  
CORRIDOR_FLR_3 VAV WITH REHEAT_DCV 0.000000 0.000305 0.000000 0.000000 Flow/Area   1.00 1.00  
BANQUET_FLR_6 VAV WITH REHEAT_DCV 0.000000 0.003581 0.000000 0.000000 Flow/Area   1.00 1.00  
DINING_FLR_6 VAV WITH REHEAT_DCV 0.000000 0.003581 0.000000 0.000000 Flow/Area   1.00 1.00  
KITCHEN_FLR_6 VAV WITH REHEAT_DCV 0.000000 0.003556 0.000000 0.000000 Flow/Area   1.00 1.00  
CORRIDOR_FLR_6 VAV WITH REHEAT_DCV 0.000000 0.000305 0.000000 0.000000 Flow/Area   1.00 1.00  


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
BASEMENT 728.33 8760.00 728.33
RETAIL_1_FLR_1 969.50 8644.67 943.83
RETAIL_2_FLR_1 53.50 8760.00 53.50
MECH_FLR_1 969.00 8760.00 969.00
STORAGE_FLR_1 1634.00 8760.00 1634.00
LAUNDRY_FLR_1 3719.67 4265.67 1103.33
CAFE_FLR_1 564.50 8636.00 541.17
LOBBY_FLR_1 213.67 8760.00 213.67
ROOM_1_FLR_3 1100.83 8146.33 982.67
ROOM_2_FLR_3 1937.17 8269.67 1861.50
ROOM_3_MULT19_FLR_3 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 849.67 8760.00 849.67
ROOM_5_FLR_3 952.00 8024.83 923.67
ROOM_6_FLR_3 1773.67 8127.00 1745.00
CORRIDOR_FLR_3 903.00 8760.00 903.00
ROOM_1_FLR_6 1907.67 7916.00 1557.17
ROOM_2_FLR_6 2645.67 8035.67 2381.50
ROOM_3_MULT9_FLR_6 692.83 8006.50 564.50
BANQUET_FLR_6 687.67 8450.33 594.33
DINING_FLR_6 781.67 8188.83 567.67
KITCHEN_FLR_6 6865.33 6689.17 5256.50
CORRIDOR_FLR_6 1356.00 8760.00 1356.00
Facility 8020.00 8760.00 7386.50
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
BASEMENT 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 0.00 0.00 0.00 0.00
MECH_FLR_1 0.00 0.00 0.00 0.00
STORAGE_FLR_1 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 0.00 0.00 0.00 0.00
CAFE_FLR_1 0.00 0.00 0.00 0.00
LOBBY_FLR_1 0.00 0.00 0.00 0.00
ROOM_1_FLR_3 0.00 1.67 0.00 1.67
ROOM_2_FLR_3 0.00 1.00 0.00 1.00
ROOM_3_MULT19_FLR_3 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 0.00 2.17 0.00 2.17
ROOM_5_FLR_3 0.00 0.67 0.00 0.67
ROOM_6_FLR_3 0.00 0.50 0.00 0.50
CORRIDOR_FLR_3 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 0.00 7.67 0.00 7.67
ROOM_2_FLR_6 0.00 5.00 0.00 5.00
ROOM_3_MULT9_FLR_6 0.00 6.17 0.00 6.17
BANQUET_FLR_6 0.00 0.00 0.00 0.00
DINING_FLR_6 0.00 0.00 0.00 0.00
KITCHEN_FLR_6 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6 0.00 0.00 0.00 0.00
Facility 0.00 13.67 0.00 13.67
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2023-10-16 08:58:10

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
BASEMENT 61.80 106.50 4826.41 2.141 0.000 0.000 0.000
RETAIL_1_FLR_1 6.28 10.83 265.76 5.297 0.242 0.000 0.000
RETAIL_2_FLR_1 7.28 12.54 307.76 3.339 0.081 0.000 0.000
MECH_FLR_1 1.54 2.65 650.80 1.690 0.090 0.000 0.000
STORAGE_FLR_1 1.18 2.04 375.47 1.479 0.090 0.000 0.000
LAUNDRY_FLR_1 4.87 8.40 309.22 44.343 0.259 0.000 0.000
CAFE_FLR_1 82.58 142.30 748.35 8.010 0.190 0.000 0.000
LOBBY_FLR_1 245.14 422.44 5183.56 3.819 0.078 0.000 0.000
ROOM_1_FLR_3 0.95 1.50 118.94 0.472 0.314 0.000 0.055
ROOM_2_FLR_3 0.95 1.50 118.93 0.472 0.314 0.000 0.055
ROOM_3_MULT19_FLR_3   1.50 74.75        
ROOM_4_MULT19_FLR_3 0.95 1.50 74.77 0.536 0.139 0.000 0.087
ROOM_5_FLR_3 0.95 1.50 118.94 0.472 0.314 0.000 0.055
ROOM_6_FLR_3 0.95 1.50 118.93 0.472 0.314 0.000 0.055
CORRIDOR_FLR_3 12.16 20.96 1186.91 1.038 0.038 0.000 0.000
ROOM_1_FLR_6 0.95 1.50 118.94 0.472 0.314 0.000 0.066
ROOM_2_FLR_6 0.95 1.50 118.93 0.472 0.314 0.000 0.065
ROOM_3_MULT9_FLR_6 0.95 1.50 74.77 0.537 0.256 0.000 0.104
BANQUET_FLR_6 145.01 249.90 1010.89 9.466 0.090 0.000 0.000
DINING_FLR_6 145.01 249.90 1010.89 9.925 0.090 0.000 0.000
KITCHEN_FLR_6 12.90 22.24 314.87 30.522 0.261 0.000 0.000
CORRIDOR_FLR_6 12.87 22.18 1256.16 2.430 0.064 0.000 0.000
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
BASEMENT 61.80 106.50 4826.41 2.091 0.000 0.000 0.000
RETAIL_1_FLR_1 6.28 10.83 265.76 5.173 0.005 0.000 0.000
RETAIL_2_FLR_1 7.28 12.54 307.76 3.261 0.002 0.000 0.000
MECH_FLR_1 1.54 2.65 650.80 1.651 0.002 0.000 0.000
STORAGE_FLR_1 1.18 2.04 375.47 1.445 0.002 0.000 0.000
LAUNDRY_FLR_1 4.87 8.40 309.22 43.275 0.005 0.000 0.000
CAFE_FLR_1 82.58 142.30 748.35 7.815 0.004 0.000 0.000
LOBBY_FLR_1 245.14 422.44 5183.56 3.727 0.002 0.000 0.000
ROOM_1_FLR_3 0.95 1.50 118.94 0.460 0.006 0.000 0.000
ROOM_2_FLR_3 0.95 1.50 118.93 0.459 0.006 0.000 0.000
ROOM_3_MULT19_FLR_3   1.50 74.75        
ROOM_4_MULT19_FLR_3 0.95 1.50 74.77 0.523 0.003 0.000 0.000
ROOM_5_FLR_3 0.95 1.50 118.94 0.461 0.006 0.000 0.000
ROOM_6_FLR_3 0.95 1.50 118.93 0.459 0.006 0.000 0.000
CORRIDOR_FLR_3 12.16 20.96 1186.91 1.013 0.001 0.000 0.000
ROOM_1_FLR_6 0.95 1.50 118.94 0.460 0.006 0.000 0.000
ROOM_2_FLR_6 0.95 1.50 118.93 0.459 0.006 0.000 0.000
ROOM_3_MULT9_FLR_6 0.95 1.50 74.77 0.523 0.005 0.000 0.000
BANQUET_FLR_6 145.01 249.90 1010.89 9.224 0.002 0.000 0.000
DINING_FLR_6 145.01 249.90 1010.89 9.670 0.002 0.000 0.000
KITCHEN_FLR_6 12.90 22.24 314.87 29.682 0.005 0.000 0.000
CORRIDOR_FLR_6 12.87 22.18 1256.16 2.373 0.001 0.000 0.000
Values shown for a single zone without multipliers


Table of Contents

Report: Outdoor Air Details

For: Entire Facility

Timestamp: 2023-10-16 08:58:10

Mechanical Ventilation Parameters by Zone

AirLoop Name Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Zone Area [m2] Design Zone Outdoor Airflow - Voz [m3/s] Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s]
BASEMENT VAV WITH REHEAT 61.80 106.50 4826.41 1978.83 0.0000 0.854
RETAIL_1_FLR_1 VAV WITH REHEAT 6.28 10.83 265.76 67.07 0.0000 0.079
RETAIL_2_FLR_1 VAV WITH REHEAT 7.28 12.54 307.76 77.67 0.0000 0.092
MECH_FLR_1 VAV WITH REHEAT 1.54 2.65 650.80 164.24 0.0000 0.000
STORAGE_FLR_1 VAV WITH REHEAT 1.18 2.04 375.47 94.76 0.0000 0.058
LAUNDRY_FLR_1 VAV WITH REHEAT 4.87 8.40 309.22 78.04 0.0000 0.000
CAFE_FLR_1 VAV WITH REHEAT 82.58 142.30 748.35 188.86 0.0000 0.676
LOBBY_FLR_1 VAV WITH REHEAT 245.14 422.44 5183.56 1308.19 0.0000 1.894
ROOM_1_FLR_3 FLR_3_DOAS 0.95 1.50 118.94 39.02 0.0000 0.062
ROOM_2_FLR_3 FLR_3_DOAS 0.95 1.50 118.93 39.02 0.0000 0.062
ROOM_3_MULT19_FLR_3 FLR_3_DOAS   1.50 74.75 24.52 0.0000 0.837
ROOM_4_MULT19_FLR_3 FLR_3_DOAS 0.95 1.50 74.77 24.53 0.0000 0.837
ROOM_5_FLR_3 FLR_3_DOAS 0.95 1.50 118.94 39.02 0.0000 0.062
ROOM_6_FLR_3 FLR_3_DOAS 0.95 1.50 118.93 39.02 0.0000 0.062
CORRIDOR_FLR_3 VAV WITH REHEAT 12.16 20.96 1186.91 389.40 0.0000 0.475
ROOM_1_FLR_6 FLR_3_DOAS 0.95 1.50 118.94 39.02 0.0000 0.015
ROOM_2_FLR_6 FLR_3_DOAS 0.95 1.50 118.93 39.02 0.0000 0.015
ROOM_3_MULT9_FLR_6 FLR_3_DOAS 0.95 1.50 74.77 24.53 0.0000 0.099
BANQUET_FLR_6 VAV WITH REHEAT 145.01 249.90 1010.89 331.66 0.0000 1.188
DINING_FLR_6 VAV WITH REHEAT 145.01 249.90 1010.89 331.66 0.0000 1.188
KITCHEN_FLR_6 VAV WITH REHEAT 12.90 22.24 314.87 103.30 0.0000 0.367
CORRIDOR_FLR_6 VAV WITH REHEAT 12.87 22.18 1256.16 412.12 0.0000 0.126
Total Facility   873.39 1604.23 35184.81 11345.29 0.0000 137.584


Total Outdoor Air by Zone

Mechanical Ventilation [m3] Natural Ventilation [m3] Total Ventilation [m3] Infiltration [m3] Total Ventilation and Infiltration [m3] Dynamic Target Ventilation - Voz-dyn [m3] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr] Time Above Zero When Unoccupied [hr]
BASEMENT 89673608.61 0.00 89673608.61 0.00 89673608.61 26946214.98 0.00 0.00 8760.00 0.00
RETAIL_1_FLR_1 12217187.64 0.00 12217187.64 557686.98 12774874.62 2498216.28 0.00 0.00 8760.00 0.00
RETAIL_2_FLR_1 8917979.73 0.00 8917979.73 215267.88 9133247.61 2892943.94 0.00 0.00 8760.00 0.00
MECH_FLR_1 9549607.41 0.00 9549607.41 508765.38 10058372.79 0.00 0.00 0.00 8760.00 0.00
STORAGE_FLR_1 4822916.34 0.00 4822916.34 293529.60 5116445.94 1821682.01 0.00 0.00 8760.00 0.00
LAUNDRY_FLR_1 0.12E+09 0.00 0.12E+09 694693.14 0.12E+09 0.00 0.00 0.00 8760.00 0.00
CAFE_FLR_1 51964038.86 0.00 51964038.86 1232798.65 53196837.51 21330615.53 0.00 0.00 8760.00 0.00
LOBBY_FLR_1 0.17E+09 0.00 0.17E+09 3522387.32 0.18E+09 59728886.00 0.00 0.00 8760.00 0.00
ROOM_1_FLR_3 1946875.62 56769.43 2003645.04 323697.46 2327342.51 1946875.62 0.00 7863.83 896.17 0.00
ROOM_2_FLR_3 1946647.51 56308.54 2002956.05 323672.77 2326628.82 1946647.51 0.00 7863.83 896.17 0.00
ROOM_3_MULT19_FLR_3 26397887.27 61287.72 26459174.99 90315.22 26549490.22 26397887.27 0.00 7930.00 830.00 8760.00
ROOM_4_MULT19_FLR_3 26405105.73 56209.41 26461315.13 90339.92 26551655.05 26405105.73 0.00 7958.49 801.51 0.00
ROOM_5_FLR_3 1946875.62 57017.46 2003893.08 323697.46 2327590.54 1946875.62 0.00 7864.00 896.00 0.00
ROOM_6_FLR_3 1946647.51 56543.92 2003191.43 323672.77 2326864.20 1946647.51 0.00 7864.00 896.00 0.00
CORRIDOR_FLR_3 42730889.48 0.00 42730889.48 391415.36 43122304.84 14972100.18 0.00 0.00 8760.00 0.00
ROOM_1_FLR_6 486718.90 67521.47 554240.37 323763.71 878004.08 486718.90 0.00 7860.33 899.67 0.00
ROOM_2_FLR_6 486661.88 66972.80 553634.68 323739.01 877373.69 486661.88 0.00 7860.33 899.67 0.00
ROOM_3_MULT9_FLR_6 3126920.42 67555.70 3194476.11 165648.85 3360124.96 3126920.42 0.00 7860.33 899.67 0.00
BANQUET_FLR_6 82850300.68 0.00 82850300.68 790549.61 83640850.30 37458366.31 0.00 0.00 8760.00 0.00
DINING_FLR_6 86858635.41 0.00 86858635.41 790549.61 87649185.02 37458366.31 0.00 0.00 8760.00 0.00
KITCHEN_FLR_6 82780804.70 0.00 82780804.70 707725.19 83488529.89 11584760.86 0.00 0.00 8760.00 0.00
CORRIDOR_FLR_6 26490647.96 0.00 26490647.96 692681.92 27183329.89 3961413.96 0.00 0.00 8760.00 0.00
Total Facility 0.50E+10 10578834.65 0.50E+10 32619391.61 0.50E+10 0.43E+10 0.00 7996.51 8760.00 8760.00


Average Outdoor Air During Occupancy by Zone - Flow Rates

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Infiltration [m3/s] Total Ventilation and Infiltration [m3/s] Dynamic Target Ventilation - Voz-dyn [m3/s] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr]
BASEMENT 2.8435 0.0000 2.8435 0.0000 2.8435 0.8545 0.00 0.00 8760.00
RETAIL_1_FLR_1 0.3874 0.0000 0.3874 0.0177 0.4051 0.0792 0.00 0.00 8760.00
RETAIL_2_FLR_1 0.2828 0.0000 0.2828 0.0068 0.2896 0.0917 0.00 0.00 8760.00
MECH_FLR_1 0.3028 0.0000 0.3028 0.0161 0.3189 0.0000 0.00 0.00 8760.00
STORAGE_FLR_1 0.1529 0.0000 0.1529 0.0093 0.1622 0.0578 0.00 0.00 8760.00
LAUNDRY_FLR_1 3.7713 0.0000 3.7713 0.0220 3.7934 0.0000 0.00 0.00 8760.00
CAFE_FLR_1 1.6478 0.0000 1.6478 0.0391 1.6869 0.6764 0.00 0.00 8760.00
LOBBY_FLR_1 5.4432 0.0000 5.4432 0.1117 5.5549 1.8940 0.00 0.00 8760.00
ROOM_1_FLR_3 0.0617 0.0018 0.0635 0.0103 0.0738 0.0617 0.00 7863.83 896.17
ROOM_2_FLR_3 0.0617 0.0018 0.0635 0.0103 0.0738 0.0617 0.00 7863.83 896.17
ROOM_4_MULT19_FLR_3 0.8373 0.0018 0.8391 0.0029 0.8419 0.8373 0.00 7958.49 801.51
ROOM_5_FLR_3 0.0617 0.0018 0.0635 0.0103 0.0738 0.0617 0.00 7864.00 896.00
ROOM_6_FLR_3 0.0617 0.0018 0.0635 0.0103 0.0738 0.0617 0.00 7864.00 896.00
CORRIDOR_FLR_3 1.3550 0.0000 1.3550 0.0124 1.3674 0.4748 0.00 0.00 8760.00
ROOM_1_FLR_6 0.0154 0.0021 0.0176 0.0103 0.0278 0.0154 0.00 7860.33 899.67
ROOM_2_FLR_6 0.0154 0.0021 0.0176 0.0103 0.0278 0.0154 0.00 7860.33 899.67
ROOM_3_MULT9_FLR_6 0.0992 0.0021 0.1013 0.0053 0.1065 0.0992 0.00 7860.33 899.67
BANQUET_FLR_6 2.6272 0.0000 2.6272 0.0251 2.6522 1.1878 0.00 0.00 8760.00
DINING_FLR_6 2.7543 0.0000 2.7543 0.0251 2.7793 1.1878 0.00 0.00 8760.00
KITCHEN_FLR_6 2.6250 0.0000 2.6250 0.0224 2.6474 0.3674 0.00 0.00 8760.00
CORRIDOR_FLR_6 0.8400 0.0000 0.8400 0.0220 0.8620 0.1256 0.00 0.00 8760.00
Total Facility 94.6439 0.1878 94.8317 0.8167 95.6484 73.9670 0.00 7996.51 8760.00


Total Outdoor Air by AirLoop

Mechanical Ventilation [m3] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr] Time Above Zero When Unoccupied [hr]
VAV WITH REHEAT 0.86E+09 0.00 0.86E+09 0.22E+09 0.00 0.00 8760.00 0.00
FLR_3_DOAS 70553146.19 546186.43 71099332.62 64690340.46 0.00 0.00 8760.00 0.00


Average Outdoor Air During Occupancy by AirLoop

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr]
VAV WITH REHEAT 27.3019 0.0000 27.3019 6.9969 0.00 0.00 8760.00
FLR_3_DOAS 2.2372 0.0173 2.2545 2.0513 0.00 0.00 8760.00


Outdoor Air Controller Limiting Factors by AirLoop

No Limiting Factor [hr] Limits and Scheduled Limits [hr] Economizer [hr] Exhaust Flow [hr] Mixed Air Flow [hr] High Humidity [hr] Demand Controlled Ventilation [hr] Night Ventilation [hr] Demand Limiting [hr] Energy Management System [hr]
VAV WITH REHEAT 0.00 789.85 0.00 0.00 7970.15 0.00 0.00 0.00 0.00 0.00
FLR_3_DOAS 0.00 8760.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Average Outdoor Air for Limiting Factors During Occupancy

No Limiting Factor [m3/s] Limits and Scheduled Limits [m3/s] Economizer [m3/s] Exhaust Flow [m3/s] Mixed Air Flow [m3/s] High Humidity [m3/s] Demand Controlled Ventilation [m3/s] Night Ventilation [m3/s] Demand Limiting [m3/s] Energy Management System [m3/s]
VAV WITH REHEAT 0.0000 27.3380 0.0000 0.0000 27.3018 0.0000 0.0000 0.0000 0.0000 0.0000
FLR_3_DOAS 0.0000 2.2372 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000



Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2023-10-16 08:58:10

Surfaces by Class

Total Outdoors
Wall 119 44
Floor 25 0
Roof 33 11
Internal Mass 22 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 30 30
Door 6 6
Glass Door 0 0
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 2
Conditioned Zones 22
Unconditioned Zones 0
Supply Plenums 0
Return Plenums 0


Input Fields

Count
IDF Objects 1304
Defaulted Fields 1181
Fields with Defaults 3925
Autosized Fields 349
Autosizable Fields 401
Autocalculated Fields 280
Autocalculatable Fields 539



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2023-10-16 08:58:10

Annual and Peak Values - Electricity

Electricity Annual Value [GJ] Electricity Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Electricity Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
Electricity:Facility 9188.28 144339.86 15-NOV-03:50 570236.28 05-JUN-19:10
Electricity:Building 2943.68 36656.90 02-JAN-02:10 182730.36 02-JAN-20:10
Electricity:Zone:BASEMENT 315.54 3631.19 02-JAN-02:10 23630.80 02-JAN-20:10
Electricity:SpaceType:GENERAL 2925.41 36182.64 02-JAN-02:10 182063.43 02-JAN-20:10
InteriorLights:Electricity 1174.11 10291.59 02-JAN-02:10 93091.76 02-JAN-20:10
InteriorLights:Electricity:Zone:BASEMENT 165.29 1501.97 02-JAN-02:10 13517.00 02-JAN-20:10
InteriorLights:Electricity:SpaceType:GENERAL 1174.11 10291.59 02-JAN-02:10 93091.76 02-JAN-20:10
LightsWired:InteriorLights:Electricity 1174.11 10291.59 02-JAN-02:10 93091.76 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:BASEMENT 165.29 1501.97 02-JAN-02:10 13517.00 02-JAN-20:10
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL 1174.11 10291.59 02-JAN-02:10 93091.76 02-JAN-20:10
Electricity:Zone:RETAIL_1_FLR_1 18.59 220.70 02-JAN-02:10 1372.90 02-JAN-20:10
InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 8.40 76.37 02-JAN-02:10 687.30 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 8.40 76.37 02-JAN-02:10 687.30 02-JAN-20:10
Electricity:Zone:RETAIL_2_FLR_1 21.53 255.58 02-JAN-02:10 1589.82 02-JAN-20:10
InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 9.73 88.43 02-JAN-02:10 795.89 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 9.73 88.43 02-JAN-02:10 795.89 02-JAN-20:10
Electricity:Zone:MECH_FLR_1 30.66 342.02 02-JAN-02:10 2327.13 02-JAN-20:10
InteriorLights:Electricity:Zone:MECH_FLR_1 18.19 165.30 02-JAN-02:10 1487.69 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:MECH_FLR_1 18.19 165.30 02-JAN-02:10 1487.69 02-JAN-20:10
Electricity:Zone:STORAGE_FLR_1 6.94 81.32 02-JAN-02:10 515.26 02-JAN-20:10
InteriorLights:Electricity:Zone:STORAGE_FLR_1 3.34 30.34 02-JAN-02:10 273.10 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:STORAGE_FLR_1 3.34 30.34 02-JAN-02:10 273.10 02-JAN-20:10
Electricity:Zone:LAUNDRY_FLR_1 72.06 1000.18 02-JAN-02:10 4910.17 02-JAN-20:10
InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 4.13 37.49 02-JAN-02:10 337.37 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 4.13 37.49 02-JAN-02:10 337.37 02-JAN-20:10
Electricity:Zone:CAFE_FLR_1 40.96 445.13 02-JAN-02:10 3142.50 02-JAN-20:10
InteriorLights:Electricity:Zone:CAFE_FLR_1 26.62 241.91 02-JAN-02:10 2177.23 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:CAFE_FLR_1 26.62 241.91 02-JAN-02:10 2177.23 02-JAN-20:10
Electricity:Zone:LOBBY_FLR_1 293.89 3428.00 02-JAN-02:10 21878.53 02-JAN-20:10
InteriorLights:Electricity:Zone:LOBBY_FLR_1 144.90 1316.59 02-JAN-02:10 11849.32 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:LOBBY_FLR_1 144.90 1316.59 02-JAN-02:10 11849.32 02-JAN-20:10
Electricity:Zone:ROOM_1_FLR_3 32.70 383.52 01-JAN-02:10 2308.42 01-JAN-21:10
InteriorLights:Electricity:Zone:ROOM_1_FLR_3 20.41 172.80 01-JAN-02:10 1570.91 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_3 20.41 172.80 01-JAN-02:10 1570.91 01-JAN-19:10
Electricity:Zone:ROOM_2_FLR_3 32.70 383.47 01-JAN-02:10 2308.15 01-JAN-21:10
InteriorLights:Electricity:Zone:ROOM_2_FLR_3 20.41 172.78 01-JAN-02:10 1570.72 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_3 20.41 172.78 01-JAN-02:10 1570.72 01-JAN-19:10
Electricity:Zone:ROOM_3_MULT19_FLR_3 472.46 5984.83 01-JAN-02:10 32482.97 01-JAN-21:10
InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 243.71 2063.36 01-JAN-02:10 18757.86 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 243.71 2063.36 01-JAN-02:10 18757.86 01-JAN-19:10
Electricity:Zone:ROOM_4_MULT19_FLR_3 472.59 5986.46 01-JAN-02:10 32491.86 01-JAN-21:10
InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 243.77 2063.93 01-JAN-02:10 18762.99 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 243.77 2063.93 01-JAN-02:10 18762.99 01-JAN-19:10
Electricity:Zone:ROOM_5_FLR_3 32.70 383.52 01-JAN-02:10 2308.42 01-JAN-21:10
InteriorLights:Electricity:Zone:ROOM_5_FLR_3 20.41 172.80 01-JAN-02:10 1570.91 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_5_FLR_3 20.41 172.80 01-JAN-02:10 1570.91 01-JAN-19:10
Electricity:Zone:ROOM_6_FLR_3 32.70 383.47 01-JAN-02:10 2308.15 01-JAN-21:10
InteriorLights:Electricity:Zone:ROOM_6_FLR_3 20.41 172.78 01-JAN-02:10 1570.72 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_6_FLR_3 20.41 172.78 01-JAN-02:10 1570.72 01-JAN-19:10
Electricity:Zone:CORRIDOR_FLR_3 62.74 570.05 02-JAN-02:10 5130.41 02-JAN-20:10
InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 62.74 570.05 02-JAN-02:10 5130.41 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 62.74 570.05 02-JAN-02:10 5130.41 02-JAN-20:10
Electricity:Zone:ROOM_1_FLR_6 8.18 95.88 01-JAN-02:10 577.11 01-JAN-21:10
InteriorLights:Electricity:Zone:ROOM_1_FLR_6 5.10 43.20 01-JAN-02:10 392.73 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_6 5.10 43.20 01-JAN-02:10 392.73 01-JAN-19:10
Electricity:Zone:ROOM_2_FLR_6 8.17 95.87 01-JAN-02:10 577.04 01-JAN-21:10
InteriorLights:Electricity:Zone:ROOM_2_FLR_6 5.10 43.19 01-JAN-02:10 392.68 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_6 5.10 43.19 01-JAN-02:10 392.68 01-JAN-19:10
Electricity:Zone:ROOM_3_MULT9_FLR_6 55.96 708.92 01-JAN-02:10 3847.72 01-JAN-21:10
InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 28.87 244.41 01-JAN-02:10 2221.93 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 28.87 244.41 01-JAN-02:10 2221.93 01-JAN-19:10
Electricity:Zone:BANQUET_FLR_6 222.61 2674.12 02-JAN-02:10 10571.30 02-JAN-20:10
InteriorLights:Electricity:Zone:BANQUET_FLR_6 46.75 424.82 02-JAN-02:10 3823.39 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:BANQUET_FLR_6 46.75 424.82 02-JAN-02:10 3823.39 02-JAN-20:10
Electricity:Zone:DINING_FLR_6 222.61 2674.12 02-JAN-02:10 10571.30 02-JAN-20:10
InteriorLights:Electricity:Zone:DINING_FLR_6 46.75 424.82 02-JAN-02:10 3823.39 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:DINING_FLR_6 46.75 424.82 02-JAN-02:10 3823.39 02-JAN-20:10
Electricity:Zone:KITCHEN_FLR_6 470.78 6777.71 02-JAN-02:10 19298.76 01-JAN-11:10
InteriorLights:Electricity:Zone:KITCHEN_FLR_6 12.48 113.42 02-JAN-02:10 1020.78 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:KITCHEN_FLR_6 12.48 113.42 02-JAN-02:10 1020.78 02-JAN-20:10
Electricity:Zone:CORRIDOR_FLR_6 16.60 150.83 02-JAN-02:10 1357.44 02-JAN-20:10
InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 16.60 150.83 02-JAN-02:10 1357.44 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 16.60 150.83 02-JAN-02:10 1357.44 02-JAN-20:10
InteriorEquipment:Electricity 1751.30 25891.05 02-JAN-02:10 89674.66 02-JAN-07:10
InteriorEquipment:Electricity:Zone:BASEMENT 150.26 2129.22 02-JAN-02:10 10113.80 02-JAN-20:10
InteriorEquipment:Electricity:SpaceType:GENERAL 1751.30 25891.05 02-JAN-02:10 89674.66 02-JAN-07:10
MiscPlug:InteriorEquipment:Electricity 959.56 15202.41 02-JAN-02:10 59492.27 02-JAN-07:10
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT 150.26 2129.22 02-JAN-02:10 10113.80 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL 959.56 15202.41 02-JAN-02:10 59492.27 02-JAN-07:10
InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 10.19 144.34 02-JAN-02:10 685.60 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 10.19 144.34 02-JAN-02:10 685.60 02-JAN-20:10
InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 11.79 167.14 02-JAN-02:10 793.93 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 11.79 167.14 02-JAN-02:10 793.93 02-JAN-20:10
InteriorEquipment:Electricity:Zone:MECH_FLR_1 12.47 176.73 02-JAN-02:10 839.45 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:MECH_FLR_1 12.47 176.73 02-JAN-02:10 839.45 02-JAN-20:10
InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 3.60 50.98 02-JAN-02:10 242.16 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 3.60 50.98 02-JAN-02:10 242.16 02-JAN-20:10
InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 67.94 962.69 02-JAN-02:10 4572.80 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 67.94 962.69 02-JAN-02:10 4572.80 02-JAN-20:10
InteriorEquipment:Electricity:Zone:CAFE_FLR_1 14.34 203.22 02-JAN-02:10 965.27 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:CAFE_FLR_1 14.34 203.22 02-JAN-02:10 965.27 02-JAN-20:10
InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 149.00 2111.41 02-JAN-02:10 10029.21 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 149.00 2111.41 02-JAN-02:10 10029.21 02-JAN-20:10
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 12.29 210.72 01-JAN-00:10 948.23 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 12.29 210.72 01-JAN-00:10 948.23 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 12.29 210.69 01-JAN-00:10 948.12 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 12.29 210.69 01-JAN-00:10 948.12 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 228.75 3921.46 01-JAN-00:10 17646.57 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 228.75 3921.46 01-JAN-00:10 17646.57 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 228.82 3922.53 01-JAN-00:10 17651.40 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 228.82 3922.53 01-JAN-00:10 17651.40 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 12.29 210.72 01-JAN-00:10 948.23 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 12.29 210.72 01-JAN-00:10 948.23 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 12.29 210.69 01-JAN-00:10 948.12 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 12.29 210.69 01-JAN-00:10 948.12 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 3.07 52.68 01-JAN-00:10 237.06 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 3.07 52.68 01-JAN-00:10 237.06 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 3.07 52.67 01-JAN-00:10 237.03 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 3.07 52.67 01-JAN-00:10 237.03 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 27.10 464.51 01-JAN-00:10 2090.30 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 27.10 464.51 01-JAN-00:10 2090.30 01-JAN-08:10
InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 175.86 2249.30 01-JAN-00:10 6747.90 01-JAN-07:10
Cooking:InteriorEquipment:Electricity 762.04 9746.88 01-JAN-00:10 29240.64 01-JAN-07:10
Cooking:InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 175.86 2249.30 01-JAN-00:10 6747.90 01-JAN-07:10
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL 762.04 9746.88 01-JAN-00:10 29240.64 01-JAN-07:10
InteriorEquipment:Electricity:Zone:DINING_FLR_6 175.86 2249.30 01-JAN-00:10 6747.90 01-JAN-07:10
Cooking:InteriorEquipment:Electricity:Zone:DINING_FLR_6 175.86 2249.30 01-JAN-00:10 6747.90 01-JAN-07:10
InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 440.03 6190.03 01-JAN-00:10 16686.59 01-JAN-07:10
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 410.33 5248.28 01-JAN-00:10 15744.84 01-JAN-07:10
ReachInFreezer:InteriorEquipment:Electricity 16.27 515.92 01-JAN-00:10 515.92 01-JAN-00:10
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 16.27 515.92 01-JAN-00:10 515.92 01-JAN-00:10
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL 16.27 515.92 01-JAN-00:10 515.92 01-JAN-00:10
ReachInRefrigerator:InteriorEquipment:Electricity 13.43 425.83 01-JAN-00:10 425.83 01-JAN-00:10
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 13.43 425.83 01-JAN-00:10 425.83 01-JAN-00:10
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL 13.43 425.83 01-JAN-00:10 425.83 01-JAN-00:10
Refrigeration:Electricity 74.19 1239.15 19-DEC-23:30 3639.04 18-AUG-07:00
Refrigeration:Electricity:Zone:KITCHEN_FLR_6 18.27 261.51 02-JAN-11:30 2271.91 01-JAN-11:10
General:Refrigeration:Electricity 18.27 261.51 02-JAN-11:30 2271.91 01-JAN-11:10
General:Refrigeration:Electricity:Zone:KITCHEN_FLR_6 18.27 261.51 02-JAN-11:30 2271.91 01-JAN-11:10
Electricity:Plant 2689.87 2868.48 16-DEC-03:00 266085.86 14-JUN-18:10
LowTempRefrigeration:Refrigeration:Electricity 22.42 0.00 01-JAN-11:10 1894.02 08-JUN-10:50
MedTempRefrigeration:Refrigeration:Electricity 33.50 935.73 18-DEC-03:10 1196.70 19-JUL-13:10
Fans:Electricity 2048.85 59047.52 09-OCT-05:10 87624.42 27-AUG-18:20
Fans:Electricity:Zone:ROOM_1_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_2_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_5_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_5_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_6_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_6_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_1_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_2_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Electricity:HVAC 2645.52 60927.78 11-DEC-11:50 107135.08 27-AUG-18:20
ExteriorEquipment:Electricity 679.68 10574.27 02-JAN-02:20 40537.60 02-JAN-07:20
Transformer:ExteriorEquipment:Electricity 32.92 556.27 02-JAN-02:20 1912.91 02-JAN-21:10
ElectricityPurchased:Facility 9188.28 144339.86 15-NOV-03:50 570236.28 05-JUN-19:10
ElectricityPurchased:Plant 9188.28 144339.86 15-NOV-03:50 570236.28 05-JUN-19:10
Cogeneration:ElectricityPurchased 9188.28 144339.86 15-NOV-03:50 570236.28 05-JUN-19:10
General:Cogeneration:ElectricityPurchased 9188.28 144339.86 15-NOV-03:50 570236.28 05-JUN-19:10
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricityNet:Facility 9188.28 144339.86 15-NOV-03:50 570236.28 05-JUN-19:10
ElectricityNet:Plant 9188.28 144339.86 15-NOV-03:50 570236.28 05-JUN-19:10
Cogeneration:ElectricityNet 9188.28 144339.86 15-NOV-03:50 570236.28 05-JUN-19:10
General:Cogeneration:ElectricityNet 9188.28 144339.86 15-NOV-03:50 570236.28 05-JUN-19:10
General:Fans:Electricity 2048.85 59047.52 09-OCT-05:10 87624.42 27-AUG-18:20
ExteriorLights:Electricity 262.44 0.00 01-JAN-07:20 16690.39 01-JAN-00:10
General:ExteriorLights:Electricity 262.44 0.00 01-JAN-07:20 16690.39 01-JAN-00:10
ElevatorLift:ExteriorEquipment:Electricity 616.11 9046.01 01-JAN-00:10 37691.69 01-JAN-07:10
ElevatorLightsFan:ExteriorEquipment:Electricity 30.65 972.00 01-JAN-00:10 972.00 01-JAN-00:10
HeatRecovery:Electricity 563.76 0.00 01-JAN-11:50 18015.63 01-JAN-08:10
General:HeatRecovery:Electricity 563.76 0.00 01-JAN-11:50 18015.63 01-JAN-08:10
WaterSystems:Electricity 90.78 1087.01 08-JUN-00:30 4739.27 28-MAR-06:10
Water Heater:WaterSystems:Electricity 90.78 1087.01 08-JUN-00:30 4739.27 28-MAR-06:10
Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Boiler Parasitic:Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:Electricity 2289.50 0.00 01-JAN-03:20 247961.71 14-JUN-18:10
General:Cooling:Electricity 2289.50 0.00 01-JAN-03:20 247961.71 14-JUN-18:10
Pumps:Electricity 253.67 210.95 30-NOV-18:10 13002.53 21-JUN-16:40
General:Pumps:Electricity 253.67 210.95 30-NOV-18:10 13002.53 21-JUN-16:40
WIRED_LTG_ELECTRICITY 41.33 0.00 01-JAN-00:10 3276.83 02-JAN-20:20


Annual and Peak Values - Natural Gas

Natural Gas Annual Value [GJ] Natural Gas Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Natural Gas Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
NaturalGas:Facility 5931.18 41863.85 03-JUL-23:30 467500.63 26-DEC-17:20
NaturalGas:Building 1788.84 13361.90 02-JAN-02:10 104248.32 02-JAN-18:10
NaturalGas:Zone:LAUNDRY_FLR_1 590.20 8363.49 02-JAN-02:10 39726.58 02-JAN-20:10
NaturalGas:SpaceType:GENERAL 1788.84 13361.90 02-JAN-02:10 104248.32 02-JAN-18:10
InteriorEquipment:NaturalGas 1788.84 13361.90 02-JAN-02:10 104248.32 02-JAN-18:10
InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 590.20 8363.49 02-JAN-02:10 39726.58 02-JAN-20:10
InteriorEquipment:NaturalGas:SpaceType:GENERAL 1788.84 13361.90 02-JAN-02:10 104248.32 02-JAN-18:10
Laundry:InteriorEquipment:NaturalGas 590.20 8363.49 02-JAN-02:10 39726.58 02-JAN-20:10
Laundry:InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 590.20 8363.49 02-JAN-02:10 39726.58 02-JAN-20:10
Laundry:InteriorEquipment:NaturalGas:SpaceType:GENERAL 590.20 8363.49 02-JAN-02:10 39726.58 02-JAN-20:10
NaturalGas:Zone:KITCHEN_FLR_6 1198.64 4998.41 01-JAN-00:10 74976.11 01-JAN-16:10
InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 1198.64 4998.41 01-JAN-00:10 74976.11 01-JAN-16:10
Cooking:InteriorEquipment:NaturalGas 1198.64 4998.41 01-JAN-00:10 74976.11 01-JAN-16:10
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 1198.64 4998.41 01-JAN-00:10 74976.11 01-JAN-16:10
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL 1198.64 4998.41 01-JAN-00:10 74976.11 01-JAN-16:10
NaturalGas:Plant 4142.35 18762.35 06-AUG-06:30 377888.41 26-DEC-17:20
WaterSystems:NaturalGas 2927.15 18467.44 01-JAN-16:10 251113.69 09-FEB-22:00
Water Heater:WaterSystems:NaturalGas 2927.15 18467.44 01-JAN-16:10 251113.69 09-FEB-22:00
Heating:NaturalGas 1215.20 0.00 03-APR-21:10 201630.34 03-FEB-07:10
Boiler:Heating:NaturalGas 1215.20 0.00 03-APR-21:10 201630.34 03-FEB-07:10


Annual and Peak Values - Cooling

Cooling Annual Value [GJ] Cooling Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Cooling Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
PlantLoopCoolingDemand:Facility 6886.93 0.00 01-JAN-03:20 857575.87 20-JUL-20:40
PlantLoopCoolingDemand:HVAC 6886.93 0.00 01-JAN-03:20 857575.87 20-JUL-20:40
CoolingCoils:PlantLoopCoolingDemand 6886.93 0.00 01-JAN-03:20 857575.87 20-JUL-20:40


Annual and Peak Values - Water

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
Water:Facility 9857.19 0.00 02-JAN-01:10 0.00 02-JAN-21:10
Water:Plant 9857.19 0.00 02-JAN-01:10 0.00 02-JAN-21:10
WaterSystems:Water 9857.19 0.00 02-JAN-01:10 0.00 02-JAN-21:10
Water Heater:WaterSystems:Water 5742.51 0.00 02-JAN-01:10 0.00 02-JAN-19:10
MainsWater:Facility 9857.19 0.00 02-JAN-01:10 0.00 02-JAN-21:10
MainsWater:Plant 9857.19 0.00 02-JAN-01:10 0.00 02-JAN-21:10
WaterSystems:MainsWater 9857.19 0.00 02-JAN-01:10 0.00 02-JAN-21:10
Water Heater:WaterSystems:MainsWater 5742.51 0.00 02-JAN-01:10 0.00 02-JAN-19:10
WaterUse:WaterSystems:Water 4114.69 0.00 02-JAN-01:10 0.00 02-JAN-07:10
WaterUse:WaterSystems:MainsWater 4114.69 0.00 02-JAN-01:10 0.00 02-JAN-07:10


Annual and Peak Values - Other by Weight/Mass

Annual Value [kg] Minimum Value [kg/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [kg/s] Timestamp of Maximum {TIMESTAMP}
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10


Annual and Peak Values - Other Volumetric

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [L] Minimum Value [L] Timestamp of Minimum {TIMESTAMP} Maximum Value [L] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other

Annual Value [GJ] Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
EnergyTransfer:Facility 35415.04 227247.64 30-NOV-11:10 3307153.34 21-JUL-18:10
EnergyTransfer:Building 6409.92 89781.84 15-JAN-16:00 409787.14 15-JUN-18:10
EnergyTransfer:Zone:KITCHEN_FLR_6 753.34 11107.20 27-DEC-04:00 36022.36 02-JUL-10:40
Refrigeration:EnergyTransfer 186.18 3693.59 19-DEC-23:30 10357.17 18-AUG-07:00
Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 93.09 1846.79 19-DEC-23:30 5178.59 18-AUG-07:00
General:Refrigeration:EnergyTransfer 93.09 1846.79 19-DEC-23:30 5178.59 18-AUG-07:00
General:Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 93.09 1846.79 19-DEC-23:30 5178.59 18-AUG-07:00
EnergyTransfer:Plant 18047.26 49330.48 17-FEB-23:20 1979418.87 20-JUL-20:40
LowTempRefrigeration:Refrigeration:EnergyTransfer 25.69 0.00 01-JAN-11:10 2686.44 01-JAN-11:40
MedTempRefrigeration:Refrigeration:EnergyTransfer 67.40 1757.20 18-DEC-03:10 2540.09 19-JUL-13:10
EnergyTransfer:Zone:BASEMENT 469.86 6817.62 27-MAR-11:00 23494.62 07-AUG-18:10
Heating:EnergyTransfer 50.88 0.00 01-JAN-08:30 55935.33 26-DEC-16:10
Heating:EnergyTransfer:Zone:BASEMENT 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer 50.88 0.00 01-JAN-08:30 55935.33 26-DEC-16:10
General:Heating:EnergyTransfer:Zone:BASEMENT 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer 6265.96 86144.95 15-JAN-16:00 406143.54 15-JUN-18:10
Cooling:EnergyTransfer:Zone:BASEMENT 469.86 6817.62 27-MAR-11:00 23494.62 07-AUG-18:10
General:Cooling:EnergyTransfer 6265.96 86144.95 15-JAN-16:00 406143.54 15-JUN-18:10
General:Cooling:EnergyTransfer:Zone:BASEMENT 469.86 6817.62 27-MAR-11:00 23494.62 07-AUG-18:10
EnergyTransfer:Zone:RETAIL_1_FLR_1 51.47 0.00 30-DEC-00:20 3521.49 05-OCT-10:40
Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 0.51 0.00 01-JAN-00:10 1056.41 27-DEC-07:30
General:Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 0.51 0.00 01-JAN-00:10 1056.41 27-DEC-07:30
Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 50.97 0.00 02-JAN-04:00 3521.49 05-OCT-10:40
General:Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 50.97 0.00 02-JAN-04:00 3521.49 05-OCT-10:40
EnergyTransfer:Zone:RETAIL_2_FLR_1 44.81 316.40 26-DEC-11:30 2412.53 15-JUN-18:10
Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 44.81 316.40 26-DEC-11:30 2412.53 15-JUN-18:10
General:Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 44.81 316.40 26-DEC-11:30 2412.53 15-JUN-18:10
EnergyTransfer:Zone:MECH_FLR_1 36.36 0.06 26-DEC-02:30 2585.15 03-JUL-18:10
Heating:EnergyTransfer:Zone:MECH_FLR_1 0.05 0.00 01-JAN-00:10 341.56 27-DEC-05:00
General:Heating:EnergyTransfer:Zone:MECH_FLR_1 0.05 0.00 01-JAN-00:10 341.56 27-DEC-05:00
Cooling:EnergyTransfer:Zone:MECH_FLR_1 36.31 0.00 05-JAN-04:30 2585.15 03-JUL-18:10
General:Cooling:EnergyTransfer:Zone:MECH_FLR_1 36.31 0.00 05-JAN-04:30 2585.15 03-JUL-18:10
EnergyTransfer:Zone:STORAGE_FLR_1 15.68 0.01 03-MAR-02:00 1282.09 03-JUL-18:10
Heating:EnergyTransfer:Zone:STORAGE_FLR_1 0.27 0.00 01-JAN-00:10 293.07 28-JAN-07:10
General:Heating:EnergyTransfer:Zone:STORAGE_FLR_1 0.27 0.00 01-JAN-00:10 293.07 28-JAN-07:10
Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 15.41 0.00 02-JAN-02:20 1282.09 03-JUL-18:10
General:Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 15.41 0.00 02-JAN-02:20 1282.09 03-JUL-18:10
EnergyTransfer:Zone:LAUNDRY_FLR_1 613.72 8717.33 27-DEC-05:00 38342.34 15-JUN-20:00
Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 613.72 8717.33 27-DEC-05:00 38342.34 15-JUN-20:00
General:Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 613.72 8717.33 27-DEC-05:00 38342.34 15-JUN-20:00
EnergyTransfer:Zone:CAFE_FLR_1 290.74 833.66 27-DEC-07:30 14018.07 03-JUL-18:10
Heating:EnergyTransfer:Zone:CAFE_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:CAFE_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:CAFE_FLR_1 290.74 833.66 27-DEC-07:30 14018.07 03-JUL-18:10
General:Cooling:EnergyTransfer:Zone:CAFE_FLR_1 290.74 833.66 27-DEC-07:30 14018.07 03-JUL-18:10
EnergyTransfer:Zone:LOBBY_FLR_1 969.10 8409.06 26-DEC-11:30 46418.08 03-JUL-18:10
Heating:EnergyTransfer:Zone:LOBBY_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:LOBBY_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 969.10 8409.06 26-DEC-11:30 46418.08 03-JUL-18:10
General:Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 969.10 8409.06 26-DEC-11:30 46418.08 03-JUL-18:10
EnergyTransfer:Zone:ROOM_1_FLR_3 78.26 0.06 09-FEB-21:40 12077.92 15-JUN-18:10
Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 5.85 0.00 01-JAN-08:10 4502.53 26-DEC-16:10
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 5.85 0.00 01-JAN-08:10 4502.53 26-DEC-16:10
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 72.41 0.00 01-JAN-00:10 12077.92 15-JUN-18:10
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 72.41 0.00 01-JAN-00:10 12077.92 15-JUN-18:10
EnergyTransfer:Zone:ROOM_2_FLR_3 72.80 0.11 02-MAR-16:50 12360.10 15-JUN-18:10
Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 9.35 0.00 01-JAN-08:10 4815.25 27-DEC-09:10
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 9.35 0.00 01-JAN-08:10 4815.25 27-DEC-09:10
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 63.45 0.00 01-JAN-00:10 12360.10 15-JUN-18:10
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 63.45 0.00 01-JAN-00:10 12360.10 15-JUN-18:10
EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 641.98 20.04 27-DEC-06:00 55907.49 22-OCT-13:20
Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 0.00 0.00 01-JAN-00:10 20.04 27-DEC-06:00
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 0.00 0.00 01-JAN-00:10 20.04 27-DEC-06:00
Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 641.98 0.00 27-DEC-06:00 55907.49 22-OCT-13:20
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 641.98 0.00 27-DEC-06:00 55907.49 22-OCT-13:20
EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 612.87 0.71 29-MAR-05:00 80588.28 15-JUN-18:20
Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 7.21 0.00 01-JAN-00:10 27822.40 26-DEC-16:10
General:Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 7.21 0.00 01-JAN-00:10 27822.40 26-DEC-16:10
Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 605.66 0.00 02-JAN-05:40 80588.28 15-JUN-18:20
General:Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 605.66 0.00 02-JAN-05:40 80588.28 15-JUN-18:20
EnergyTransfer:Zone:ROOM_5_FLR_3 79.05 0.02 11-DEC-22:00 10130.11 15-JUN-08:10
Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 5.93 0.00 01-JAN-08:10 4500.43 26-DEC-16:10
General:Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 5.93 0.00 01-JAN-08:10 4500.43 26-DEC-16:10
Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 73.12 0.00 01-JAN-00:10 10130.11 15-JUN-08:10
General:Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 73.12 0.00 01-JAN-00:10 10130.11 15-JUN-08:10
EnergyTransfer:Zone:ROOM_6_FLR_3 73.14 0.15 10-MAR-23:50 10266.20 15-JUN-08:10
Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 9.20 0.00 01-JAN-08:10 4535.07 26-DEC-16:10
General:Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 9.20 0.00 01-JAN-08:10 4535.07 26-DEC-16:10
Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 63.93 0.00 01-JAN-00:10 10266.20 15-JUN-08:10
General:Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 63.93 0.00 01-JAN-00:10 10266.20 15-JUN-08:10
EnergyTransfer:Zone:CORRIDOR_FLR_3 231.17 0.12 28-NOV-15:00 12977.56 15-JUN-18:10
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 0.06 0.00 01-JAN-00:10 1804.88 27-DEC-07:30
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 0.06 0.00 01-JAN-00:10 1804.88 27-DEC-07:30
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 231.12 0.00 15-JAN-13:20 12977.56 15-JUN-18:10
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 231.12 0.00 15-JAN-13:20 12977.56 15-JUN-18:10
EnergyTransfer:Zone:ROOM_1_FLR_6 22.60 0.03 18-JAN-20:50 3399.15 15-JUN-15:10
Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 2.62 0.00 01-JAN-08:10 1378.34 27-DEC-06:00
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 2.62 0.00 01-JAN-08:10 1378.34 27-DEC-06:00
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 19.98 0.00 01-JAN-00:10 3399.15 15-JUN-15:10
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 19.98 0.00 01-JAN-00:10 3399.15 15-JUN-15:10
EnergyTransfer:Zone:ROOM_2_FLR_6 21.54 0.04 22-FEB-23:50 3458.39 15-JUN-18:10
Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 3.85 0.00 01-JAN-08:10 1459.78 27-DEC-09:10
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 3.85 0.00 01-JAN-08:10 1459.78 27-DEC-09:10
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 17.69 0.00 01-JAN-00:10 3458.39 15-JUN-18:10
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 17.69 0.00 01-JAN-00:10 3458.39 15-JUN-18:10
EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 127.96 0.07 12-JAN-03:50 16505.55 01-OCT-15:10
Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 4.22 0.00 01-JAN-00:10 5777.37 26-DEC-16:10
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 4.22 0.00 01-JAN-00:10 5777.37 26-DEC-16:10
Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 123.74 0.00 01-JAN-04:00 16505.55 01-OCT-15:10
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 123.74 0.00 01-JAN-04:00 16505.55 01-OCT-15:10
EnergyTransfer:Zone:BANQUET_FLR_6 528.87 7926.12 27-DEC-09:20 24154.65 15-JUN-18:10
Heating:EnergyTransfer:Zone:BANQUET_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:BANQUET_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 528.87 7926.12 27-DEC-09:20 24154.65 15-JUN-18:10
General:Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 528.87 7926.12 27-DEC-09:20 24154.65 15-JUN-18:10
EnergyTransfer:Zone:DINING_FLR_6 565.57 9107.61 27-DEC-09:20 25543.76 15-JUN-18:10
Heating:EnergyTransfer:Zone:DINING_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:DINING_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:DINING_FLR_6 565.57 9107.61 27-DEC-09:20 25543.76 15-JUN-18:10
General:Cooling:EnergyTransfer:Zone:DINING_FLR_6 565.57 9107.61 27-DEC-09:20 25543.76 15-JUN-18:10
Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 660.25 8947.94 27-DEC-04:00 30945.42 02-JUL-10:40
General:Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 660.25 8947.94 27-DEC-04:00 30945.42 02-JUL-10:40
EnergyTransfer:Zone:CORRIDOR_FLR_6 109.03 0.04 06-NOV-03:50 7752.60 03-JUL-10:40
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 1.76 0.00 01-JAN-00:10 2683.58 27-DEC-07:30
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 1.76 0.00 01-JAN-00:10 2683.58 27-DEC-07:30
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 107.28 0.00 01-JAN-05:40 7752.60 03-JUL-10:40
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 107.28 0.00 01-JAN-05:40 7752.60 03-JUL-10:40
PlantLoopHeatingDemand:Facility 1467.40 10109.53 04-JUL-00:10 208609.57 03-FEB-07:10
PlantLoopHeatingDemand:Plant 648.50 7205.75 31-JUL-01:10 50235.57 30-JAN-07:10
WaterSystems:PlantLoopHeatingDemand 648.50 7205.75 31-JUL-01:10 50235.57 30-JAN-07:10
General:WaterSystems:PlantLoopHeatingDemand 648.50 7205.75 31-JUL-01:10 50235.57 30-JAN-07:10
EnergyTransfer:HVAC 10957.86 21104.68 15-DEC-23:40 1167960.96 20-JUL-15:20
HeatingCoils:EnergyTransfer 818.90 0.00 03-APR-21:10 158410.10 03-FEB-07:10
PlantLoopHeatingDemand:HVAC 818.90 0.00 03-APR-21:10 158410.10 03-FEB-07:10
HeatingCoils:PlantLoopHeatingDemand 818.90 0.00 03-APR-21:10 158410.10 03-FEB-07:10
CoolingCoils:EnergyTransfer 6886.93 0.00 01-JAN-03:20 857575.87 20-JUL-20:40
HeatRecoveryForHeating:EnergyTransfer 1962.95 0.00 01-JAN-11:30 554643.66 03-FEB-07:00
HeatRecoveryForCooling:EnergyTransfer 1289.08 0.00 01-JAN-00:10 382257.13 21-JUL-18:00
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
WaterSystems:EnergyTransfer 648.50 7205.75 31-JUL-01:10 50235.57 30-JAN-07:10
WaterUse:WaterSystems:EnergyTransfer 648.50 7205.75 31-JUL-01:10 50235.57 30-JAN-07:10
Boilers:EnergyTransfer 812.02 0.00 03-APR-21:10 155354.24 03-FEB-07:10
Chillers:EnergyTransfer 7102.07 0.00 01-JAN-03:20 865326.82 20-JUL-20:40
HeatRejection:EnergyTransfer 9391.57 0.00 01-JAN-03:20 1081774.12 20-JUL-20:40
General:HeatRejection:EnergyTransfer 9391.57 0.00 01-JAN-03:20 1081774.12 20-JUL-20:40



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2023-10-16 08:58:10

Annual Building Sensible Heat Gain Components

HVAC Zone Eq & Other Sensible Air Heating [GJ] HVAC Zone Eq & Other Sensible Air Cooling [GJ] HVAC Terminal Unit Sensible Air Heating [GJ] HVAC Terminal Unit Sensible Air Cooling [GJ] HVAC Input Heated Surface Heating [GJ] HVAC Input Cooled Surface Cooling [GJ] People Sensible Heat Addition [GJ] Lights Sensible Heat Addition [GJ] Equipment Sensible Heat Addition [GJ] Window Heat Addition [GJ] Interzone Air Transfer Heat Addition [GJ] Infiltration Heat Addition [GJ] Opaque Surface Conduction and Other Heat Addition [GJ] Equipment Sensible Heat Removal [GJ] Window Heat Removal [GJ] Interzone Air Transfer Heat Removal [GJ] Infiltration Heat Removal [GJ] Opaque Surface Conduction and Other Heat Removal [GJ]
BASEMENT 0.000 0.000 0.000 -469.861 0.000 0.000 157.405 165.288 150.255 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -3.087
RETAIL_1_FLR_1 0.000 0.000 0.507 -50.966 0.000 0.000 16.105 8.404 10.186 25.117 0.000 1.364 0.267 0.000 -7.586 0.000 -3.399 -0.000
RETAIL_2_FLR_1 0.000 0.000 0.000 -44.813 0.000 0.000 18.568 9.732 11.795 0.000 0.000 0.527 5.501 0.000 0.000 0.000 -1.310 -0.000
MECH_FLR_1 0.000 0.000 0.054 -36.306 0.000 0.000 3.948 18.192 12.471 0.000 0.000 1.269 3.452 0.000 0.000 0.000 -3.080 -0.000
STORAGE_FLR_1 0.000 0.000 0.265 -15.410 0.000 0.000 3.042 3.340 3.598 0.000 0.000 0.739 6.202 0.000 0.000 0.000 -1.776 -0.000
LAUNDRY_FLR_1 0.000 0.000 0.000 -613.724 0.000 0.000 12.209 4.125 658.131 0.000 0.000 1.651 0.000 0.000 0.000 0.000 -4.385 -58.007
CAFE_FLR_1 0.000 0.000 0.000 -290.740 0.000 0.000 209.432 26.624 14.341 70.268 0.000 2.941 0.003 0.000 -21.756 0.000 -7.575 -3.534
LOBBY_FLR_1 0.000 0.000 0.000 -969.106 0.000 0.000 619.925 144.896 148.998 93.713 0.000 8.454 3.607 0.000 -28.774 0.000 -21.712 -0.001
ROOM_1_FLR_3 9.207 -59.259 0.000 -16.504 0.000 0.000 9.679 20.410 12.292 51.205 0.000 2.908 0.001 0.000 -18.013 0.000 -8.629 -3.296
ROOM_2_FLR_3 13.390 -51.274 0.000 -16.214 0.000 0.000 9.711 20.407 12.291 38.872 0.000 2.916 0.000 0.000 -18.589 0.000 -8.428 -3.081
ROOM_3_MULT19_FLR_3 0.145 -375.604 0.000 -266.514 0.000 0.000 0.000 243.708 228.754 287.211 0.000 11.422 51.453 0.000 -111.838 0.000 -68.737 -0.002
ROOM_4_MULT19_FLR_3 35.439 -414.002 0.000 -219.885 0.000 0.000 184.480 243.774 228.817 102.185 0.000 17.316 0.001 0.000 -102.859 0.000 -51.448 -23.817
ROOM_5_FLR_3 9.155 -59.742 0.000 -16.596 0.000 0.000 9.667 20.410 12.292 51.232 0.000 2.901 0.002 0.000 -17.318 0.000 -8.698 -3.303
ROOM_6_FLR_3 13.150 -51.580 0.000 -16.301 0.000 0.000 9.701 20.407 12.291 38.319 0.000 2.904 0.002 0.000 -17.320 0.000 -8.490 -3.081
CORRIDOR_FLR_3 0.000 0.000 0.057 -231.116 0.000 0.000 122.917 62.736 0.000 46.231 0.000 3.512 26.934 0.000 -21.648 0.000 -9.623 -0.001
ROOM_1_FLR_6 3.567 -16.815 0.000 -4.115 0.000 0.000 2.421 5.102 3.073 12.656 0.000 0.723 0.031 0.000 -4.461 0.000 -2.184 -0.000
ROOM_2_FLR_6 4.952 -14.749 0.000 -4.043 0.000 0.000 2.429 5.102 3.073 9.600 0.000 0.724 0.000 0.000 -4.593 0.000 -2.132 -0.361
ROOM_3_MULT9_FLR_6 8.164 -100.837 0.000 -26.840 0.000 0.000 21.722 28.868 27.097 63.769 0.000 3.479 6.241 0.000 -20.759 0.000 -10.903 -0.002
BANQUET_FLR_6 0.000 0.000 0.000 -528.872 0.000 0.000 358.630 46.753 175.857 11.654 0.000 1.754 0.000 0.000 -12.523 0.000 -5.087 -48.166
DINING_FLR_6 0.000 0.000 0.000 -565.570 0.000 0.000 357.455 46.753 175.857 11.374 0.000 1.731 0.001 0.000 -12.879 0.000 -5.112 -9.610
KITCHEN_FLR_6 0.000 0.000 0.000 -660.243 0.000 0.000 30.427 12.482 556.656 23.593 0.000 1.109 50.779 0.000 -9.676 0.000 -5.127 0.000
CORRIDOR_FLR_6 0.000 0.000 1.758 -107.276 0.000 0.000 32.932 16.599 0.000 22.468 0.000 1.640 45.623 0.000 -9.506 0.000 -4.237 -0.000
Total Facility 97.170 -1143.863 2.641 -5171.016 0.000 0.000 2192.805 1174.112 2458.123 959.466 0.000 71.984 200.103 0.000 -440.097 0.000 -242.073 -159.350


Peak Cooling Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
BASEMENT 17-SEP-10:35 0.00 0.00 0.00 -23757.84 0.00 0.00 2617.70 4505.72 4258.44 0.00 0.00 0.00 12375.97 0.00 -0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 05-OCT-10:35 0.00 0.00 0.00 -3560.78 0.00 0.00 167.69 190.92 252.59 3980.61 0.00 100.09 0.00 0.00 -0.00 0.00 0.00 -1131.11
RETAIL_2_FLR_1 15-JUN-18:10 0.00 0.00 0.00 -2435.52 0.00 0.00 724.37 707.46 752.15 0.00 0.00 99.56 151.99 0.00 -0.00 0.00 0.00 0.00
MECH_FLR_1 03-JUL-18:10 0.00 0.00 0.00 -2596.17 0.00 0.00 152.60 1322.39 795.27 0.00 0.00 242.20 83.71 0.00 -0.00 0.00 0.00 0.00
STORAGE_FLR_1 03-JUL-18:10 0.00 0.00 0.00 -1284.50 0.00 0.00 118.04 242.76 229.41 0.00 0.00 141.26 553.03 0.00 -0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 15-JUN-20:00 0.00 0.00 0.00 -38341.71 0.00 0.00 424.17 337.37 44299.38 0.00 0.00 228.89 0.00 0.00 -0.00 0.00 0.00 -6948.10
CAFE_FLR_1 17-SEP-10:35 0.00 0.00 0.00 -14200.64 0.00 0.00 3421.14 725.74 406.43 9556.34 0.00 325.62 0.00 0.00 -0.00 0.00 0.00 -234.63
LOBBY_FLR_1 03-JUL-18:10 0.00 0.00 0.00 -46890.09 0.00 0.00 24441.73 10532.73 9501.36 2880.71 0.00 1673.71 0.00 0.00 -0.00 0.00 0.00 -2140.14
ROOM_1_FLR_3 01-OCT-15:01 0.00 -14947.63 0.00 -639.54 0.00 0.00 130.72 518.40 305.54 8628.52 0.00 415.51 5588.47 0.00 -0.00 0.00 0.00 0.00
ROOM_2_FLR_3 15-JUN-18:02 0.00 -14843.55 0.00 -638.45 0.00 0.00 335.51 1397.95 516.20 6565.27 0.00 543.40 6123.68 0.00 -0.00 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 22-OCT-13:20 0.00 -47001.15 0.00 -8907.49 0.00 0.00 0.00 6190.09 5686.12 52820.54 0.00 580.42 0.00 0.00 -0.00 0.00 0.00 -9368.53
ROOM_4_MULT19_FLR_3 27-AUG-18:01 0.00 -100554.70 0.00 -8810.78 0.00 0.00 5381.10 18762.99 9610.21 6823.21 0.00 2280.14 66507.83 0.00 -0.00 0.00 0.00 0.00
ROOM_5_FLR_3 15-JUN-08:61 0.00 -13171.63 0.00 -643.06 0.00 0.00 87.14 691.20 453.05 7870.83 0.00 296.27 4416.20 0.00 -0.00 0.00 0.00 0.00
ROOM_6_FLR_3 15-JUN-08:61 0.00 -13085.22 0.00 -644.16 0.00 0.00 87.14 691.12 452.99 7988.37 0.00 295.49 4214.26 0.00 -0.00 0.00 0.00 0.00
CORRIDOR_FLR_3 15-JUN-18:10 0.00 0.00 0.00 -13020.91 0.00 0.00 4576.48 4560.37 0.00 3259.57 0.00 675.63 0.00 0.00 -0.00 0.00 0.00 -51.14
ROOM_1_FLR_6 01-OCT-15:01 0.00 -4055.17 0.00 -160.05 0.00 0.00 32.68 129.60 76.39 2130.83 0.00 103.18 1742.55 0.00 -0.00 0.00 0.00 0.00
ROOM_2_FLR_6 15-JUN-18:02 0.00 -4023.58 0.00 -159.81 0.00 0.00 83.88 349.49 129.05 1626.16 0.00 135.14 1859.67 0.00 -0.00 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 01-OCT-15:01 0.00 -18723.02 0.00 -1046.09 0.00 0.00 294.11 733.24 673.54 6563.64 0.00 467.26 11037.32 0.00 -0.00 0.00 0.00 0.00
BANQUET_FLR_6 15-JUN-18:10 0.00 0.00 0.00 -24500.71 0.00 0.00 14133.16 3398.57 6747.90 2271.39 0.00 346.45 0.00 0.00 -0.00 0.00 0.00 -2396.76
DINING_FLR_6 15-JUN-18:10 0.00 0.00 0.00 -25885.11 0.00 0.00 14070.16 3398.57 6747.90 2249.84 0.00 344.73 0.00 0.00 -0.00 0.00 0.00 -926.10
KITCHEN_FLR_6 02-JUL-10:35 0.00 0.00 0.00 -30946.41 0.00 0.00 464.24 340.26 24459.16 2641.99 0.00 184.76 2856.02 0.00 -0.00 0.00 0.00 0.00
CORRIDOR_FLR_6 03-JUL-10:35 0.00 0.00 0.00 -7804.66 0.00 0.00 351.04 377.07 0.00 1930.13 0.00 269.20 4877.21 0.00 -0.00 0.00 0.00 0.00
Total Facility 15-JUN-18:02 0.00 -213537.94 0.00 -239459.02 0.00 0.00 84680.39 82800.17 122526.13 63648.50 0.00 13894.45 85447.32 0.00 0.00 0.00 0.00 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
BASEMENT - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 27-DEC-07:30 0.00 0.00 1056.24 0.00 0.00 0.00 364.14 381.83 433.01 0.00 0.00 0.00 0.00 0.00 -1226.69 0.00 -504.37 -504.17
RETAIL_2_FLR_1 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
MECH_FLR_1 27-DEC-05:00 0.00 0.00 341.55 0.00 0.00 0.00 197.30 165.30 176.73 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -464.20 -416.69
STORAGE_FLR_1 28-JAN-07:10 0.00 0.00 293.05 0.00 0.00 0.00 84.32 91.03 101.96 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -253.30 -317.06
LAUNDRY_FLR_1 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CAFE_FLR_1 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
LOBBY_FLR_1 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_3 28-NOV-16:01 7350.79 284.93 0.00 -284.93 0.00 0.00 290.09 439.85 273.93 0.00 0.00 0.00 0.00 0.00 -562.67 0.00 -376.89 -7415.11
ROOM_2_FLR_3 28-NOV-16:01 7403.70 263.18 0.00 -263.18 0.00 0.00 293.98 439.80 273.90 0.00 0.00 0.00 0.00 0.00 -579.51 0.00 -361.93 -7469.94
ROOM_3_MULT19_FLR_3 27-DEC-06:00 20.04 12299.55 0.00 -12299.55 0.00 0.00 0.00 4126.73 3921.46 0.00 0.00 0.00 12186.57 0.00 -14706.88 0.00 -5547.92 0.00
ROOM_4_MULT19_FLR_3 11-APR-15:03 43372.32 5511.25 0.00 -5511.25 0.00 0.00 4899.30 5253.64 5099.29 2724.06 0.00 0.00 0.00 0.00 -0.00 0.00 -14792.43 -46556.18
ROOM_5_FLR_3 15-JAN-16:01 7052.13 282.57 0.00 -282.57 0.00 0.00 161.41 518.40 305.54 0.00 0.00 0.00 0.00 0.00 -729.24 0.00 -437.92 -6870.32
ROOM_6_FLR_3 19-DEC-16:01 7097.19 259.85 0.00 -259.85 0.00 0.00 293.98 439.80 273.90 0.00 0.00 0.00 0.00 0.00 -1015.38 0.00 -465.86 -6623.62
CORRIDOR_FLR_3 27-DEC-07:30 0.00 0.00 1804.65 0.00 0.00 0.00 2771.46 2850.23 0.00 0.00 0.00 0.00 0.00 0.00 -3668.39 0.00 -1439.39 -2318.55
ROOM_1_FLR_6 28-NOV-16:01 2190.54 67.26 0.00 -67.26 0.00 0.00 73.50 109.96 68.48 0.00 0.00 0.00 0.00 0.00 -127.15 0.00 -92.18 -2223.15
ROOM_2_FLR_6 28-NOV-16:01 2189.36 67.01 0.00 -67.01 0.00 0.00 73.50 109.95 68.48 0.00 0.00 0.00 0.00 0.00 -135.84 0.00 -92.00 -2213.44
ROOM_3_MULT9_FLR_6 15-JAN-16:01 10181.71 493.97 0.00 -493.97 0.00 0.00 357.80 733.24 673.54 0.00 0.00 0.00 0.00 0.00 -828.36 0.00 -526.74 -10591.19
BANQUET_FLR_6 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
DINING_FLR_6 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
KITCHEN_FLR_6 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6 27-DEC-07:30 0.00 0.00 2683.21 0.00 0.00 0.00 738.33 754.13 0.00 0.00 0.00 0.00 0.00 0.00 -1614.80 0.00 -634.44 -1926.44
Total Facility 28-NOV-16:01 -25542.86 117748.85 38.39 -117748.85 0.00 0.00 62257.51 25962.78 77528.99 0.00 0.00 0.00 0.00 0.00 -18448.84 0.00 -10456.77 -111339.21



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2023-10-16 08:58:10

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow - Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
VAV WITH REHEAT 25.1554 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 25.0392 0.0000 1.0000 Not calculated 0.0000 0.0000    
FLR_3_DOAS 2.0513 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 2.0513 0.0000 1.0000 Not calculated 0.0000 0.0000    


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
VAV WITH REHEAT 25.0296 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 25.0296 0.0000 1.0000 Not calculated 0.0000 0.0000    
FLR_3_DOAS 2.0513 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 2.0513 0.0000 1.0000 Not calculated 0.0000 0.0000    


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [m3/s-person] Zone Population - Pz Area Outdoor Air Rate - Ra [m3/s-m2] Zone Floor Area - Az [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [m3/s]
BASEMENT VAV WITH REHEAT 0.000000 106.4990 0.000432 1978.83 0.0000 1.0000 0.0000 1.000 0.0000
RETAIL_1_FLR_1 VAV WITH REHEAT 0.000000 10.8290 0.001181 67.07 0.0000 1.0000 0.0000 1.000 0.0000
RETAIL_2_FLR_1 VAV WITH REHEAT 0.000000 12.5400 0.001181 77.67 0.0000 1.0000 0.0000 1.000 0.0000
MECH_FLR_1 VAV WITH REHEAT 0.000000 2.6520 0.000000 164.24 0.0000 1.0000 0.0000 1.000 0.0000
STORAGE_FLR_1 VAV WITH REHEAT 0.000000 2.0400 0.000610 94.76 0.0000 1.0000 0.0000 1.000 0.0000
LAUNDRY_FLR_1 VAV WITH REHEAT 0.000000 8.4000 0.000000 78.04 0.0000 1.0000 0.0000 1.000 0.0000
CAFE_FLR_1 VAV WITH REHEAT 0.000000 142.3000 0.003581 188.86 0.0000 1.0000 0.0000 1.000 0.0000
LOBBY_FLR_1 VAV WITH REHEAT 0.000000 422.4350 0.001448 1308.19 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_1_FLR_3 FLR_3_DOAS 0.000000 6.0000 0.000396 156.09 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_2_FLR_3 FLR_3_DOAS 0.000000 6.0000 0.000396 156.07 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_3_MULT19_FLR_3 FLR_3_DOAS 0.000000 114.0000 0.000449 1863.81 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_4_MULT19_FLR_3 FLR_3_DOAS 0.000000 114.0000 0.000449 1864.32 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_5_FLR_3 FLR_3_DOAS 0.000000 6.0000 0.000396 156.09 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_6_FLR_3 FLR_3_DOAS 0.000000 6.0000 0.000396 156.07 0.0000 1.0000 0.0000 1.000 0.0000
CORRIDOR_FLR_3 VAV WITH REHEAT 0.000000 83.8280 0.000305 1557.62 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_1_FLR_6 FLR_3_DOAS 0.000000 1.5000 0.000396 39.02 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_2_FLR_6 FLR_3_DOAS 0.000000 1.5000 0.000396 39.02 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_3_MULT9_FLR_6 FLR_3_DOAS 0.000000 13.5000 0.000449 220.77 0.0000 1.0000 0.0000 1.000 0.0000
BANQUET_FLR_6 VAV WITH REHEAT 0.000000 249.8960 0.003581 331.66 0.0000 1.0000 0.0000 1.000 0.0000
DINING_FLR_6 VAV WITH REHEAT 0.000000 249.8960 0.003581 331.66 0.0000 1.0000 0.0000 1.000 0.0000
KITCHEN_FLR_6 VAV WITH REHEAT 0.000000 22.2380 0.003556 103.30 0.0000 1.0000 0.0000 1.000 0.0000
CORRIDOR_FLR_6 VAV WITH REHEAT 0.000000 22.1800 0.000305 412.12 0.0000 1.0000 0.0000 1.000 0.0000


System Ventilation Parameters

People Outdoor Air Rate - Rp [m3/s-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [m3/s-m2] Sum of Zone Floor Area - Az-sum [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Outdoor Airflow - Voz-htg [m3/s]
VAV WITH REHEAT   0.00 0.001045 6694.0231 0.0000 0.0000 0.0000
FLR_3_DOAS   0.00 0.000441 4651.2638 0.0000 0.0000 0.0000


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
BASEMENT VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.8579 2.8579 2.8436 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
RETAIL_1_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.3894 0.3894 0.3874 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
RETAIL_2_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.2842 0.2842 0.2828 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
MECH_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.3043 0.3043 0.3028 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
STORAGE_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1537 0.1537 0.1529 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LAUNDRY_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 3.7896 3.7896 3.7707 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CAFE_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.6561 1.6561 1.6478 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LOBBY_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 5.4707 5.4707 5.4433 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_1_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_2_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_3_MULT19_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.8371 0.8371 0.8371 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_4_MULT19_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.8373 0.8373 0.8373 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_5_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_6_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORRIDOR_FLR_3 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.3618 1.3618 1.3550 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_1_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0154 0.0154 0.0154 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_2_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0154 0.0154 0.0154 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_3_MULT9_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0992 0.0992 0.0992 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
BANQUET_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.6404 2.6404 2.6272 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DINING_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.7682 2.7682 2.7543 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
KITCHEN_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.6349 2.6349 2.6217 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORRIDOR_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.8442 0.8442 0.8400 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Zone Ventilation Efficiency - Evz-min
VAV WITH REHEAT 25.1554 25.0392 25.1554 25.0296 0.0000 1.0000
FLR_3_DOAS 2.0513 2.0513 2.0513 2.0513 0.0000 1.0000


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Heating - Voz-htg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
BASEMENT VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.8436 2.8436 2.8436 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
RETAIL_1_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.3874 0.3874 0.3874 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
RETAIL_2_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.2828 0.2828 0.2828 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
MECH_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.3028 0.3028 0.3028 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
STORAGE_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1529 0.1529 0.1529 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LAUNDRY_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 3.7707 3.7707 3.7707 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CAFE_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.6478 1.6478 1.6478 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LOBBY_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 5.4433 5.4433 5.4433 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_1_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_2_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_3_MULT19_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.8371 0.8371 0.8371 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_4_MULT19_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.8373 0.8373 0.8373 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_5_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_6_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORRIDOR_FLR_3 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.3550 1.3550 1.3550 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_1_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0154 0.0154 0.0154 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_2_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0154 0.0154 0.0154 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_3_MULT9_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0992 0.0992 0.0992 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
BANQUET_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.6272 2.6272 2.6272 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DINING_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.7543 2.7543 2.7543 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
KITCHEN_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.6217 2.6217 2.6217 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORRIDOR_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.8400 0.8400 0.8400 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Zone Ventilation Efficiency - Evz-min
VAV WITH REHEAT 25.0296 25.0296 25.0296 25.0296 0.0000 1.0000
FLR_3_DOAS 2.0513 2.0513 2.0513 2.0513 0.0000 1.0000



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2023-10-16 08:58:10

Sec1.1A-General Information

Data
Weather File RUNPERIOD 1 ** El Paso International Ap Ut TX USA TMY3 WMO#=722700
Total gross floor area [m2] 11345.29
Principal Heating Source Natural Gas


EAp2-1. Space Usage Type

Space Area [m2] Regularly Occupied Area [m2] Unconditioned Area [m2] Typical Hours/Week in Operation [hr/wk]
BASEMENT 1978.83 1978.83 0.00 168.00
RETAIL_1_FLR_1 67.07 67.07 0.00 168.00
RETAIL_2_FLR_1 77.67 77.67 0.00 168.00
MECH_FLR_1 164.24 164.24 0.00 168.00
STORAGE_FLR_1 94.76 94.76 0.00 168.00
LAUNDRY_FLR_1 78.04 78.04 0.00 168.00
CAFE_FLR_1 188.86 188.86 0.00 168.00
LOBBY_FLR_1 1308.19 1308.19 0.00 168.00
ROOM_1_FLR_3 39.02 39.02 0.00 168.00
ROOM_2_FLR_3 39.02 39.02 0.00 168.00
ROOM_3_MULT19_FLR_3 24.52 24.52 0.00 0.00
ROOM_4_MULT19_FLR_3 24.53 24.53 0.00 168.00
ROOM_5_FLR_3 39.02 39.02 0.00 168.00
ROOM_6_FLR_3 39.02 39.02 0.00 168.00
CORRIDOR_FLR_3 389.40 389.40 0.00 168.00
ROOM_1_FLR_6 39.02 39.02 0.00 168.00
ROOM_2_FLR_6 39.02 39.02 0.00 168.00
ROOM_3_MULT9_FLR_6 24.53 24.53 0.00 168.00
BANQUET_FLR_6 331.66 331.66 0.00 168.00
DINING_FLR_6 331.66 331.66 0.00 168.00
KITCHEN_FLR_6 103.30 103.30 0.00 168.00
CORRIDOR_FLR_6 412.12 412.12 0.00 168.00
Totals 11345.29 11345.29 0.00  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 0.00
Number of hours cooling loads not met 13.67
Number of hours not met 13.67


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electricity Energy Use [GJ] Electricity Demand [W] Natural Gas Energy Use [GJ] Natural Gas Demand [W] Gasoline Use [GJ] Gasoline Demand [W] Diesel Use [GJ] Diesel Demand [W] Coal Use [GJ] Coal Demand [W] Fuel Oil No 1 Use [GJ] Fuel Oil No 1 Demand [W] Fuel Oil No 2 Use [GJ] Fuel Oil No 2 Demand [W] Propane Use [GJ] Propane Demand [W] Other Fuel 1 Use [GJ] Other Fuel 1 Demand [W] Other Fuel 2 Use [GJ] Other Fuel 2 Demand [W] District Cooling Use [GJ] District Cooling Demand [W] District Heating Use [GJ] District Heating Demand [W]
Heating -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heating -- Boiler 0.00 0.00 1215.20 201630.34 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heating -- Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling -- General 2289.50 247961.71 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting -- LightsWired 1174.11 93091.76 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting -- General 262.44 16690.39 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- MiscPlug 959.56 59492.27 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- Cooking 762.04 29240.64 1198.64 74976.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- ReachInFreezer 16.27 515.92 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- ReachInRefrigerator 13.43 425.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- Laundry 0.00 0.00 590.20 39726.58 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- Transformer 32.92 1912.91 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- ElevatorLift 616.11 37691.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- ElevatorLightsFan 30.65 972.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- General 2048.85 87624.42 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps -- General 253.67 13002.53 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery -- General 563.76 18015.63 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- Water Heater 90.78 4739.27 2927.15 251113.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- General 18.27 2271.91 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- LowTempRefrigeration 22.42 1894.02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- MedTempRefrigeration 33.50 1196.70 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


EAp2-6. Energy Use Summary

Process Subtotal [GJ] Total Energy Use [GJ]
Electricity 1825.49 9188.28
Natural Gas 1788.84 5931.18
Additional 0.00 0.00
Total 3614.33 15119.46


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [GJ]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [MJ/m2]
Interior Lighting (All) 103.49
Space Heating 0.00
Space Cooling 201.80
Fans (All) 180.59
Service Water Heating 8.00
Receptacle Equipment 154.36
Miscellaneous (All) 809.88
Subtotal 809.88


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [MJ/m2]
Space Heating 107.11
Service Water Heating 258.01
Miscellaneous (All) 522.79
Subtotal 522.79


EAp2-17c. Energy Use Intensity - Additional

Additional [MJ/m2]
Subtotal 0.00
Miscellaneous 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting (All) 7.77
Space Heating 8.04
Space Cooling 15.14
Fans (All) 13.55
Service Water Heating 19.96
Receptacle Equipment 23.41
Miscellaneous 12.13


Schedules-Equivalent Full Load Hours (Schedule Type=Fraction)

Equivalent Full Load Hours of Operation Per Year [hr] Hours > 1% [hr]
LTG_SCH_KITCHEN 3061. 8760.
LTG_SCH_DINING 3061. 8760.
LTG_SCH_BASEMENT 2655. 8760.
LTG_SCH_LOBBY 3061. 8760.
LTG_SCH_STORAGE 1339. 8760.
LTG_SCH_MECHANIC 3061. 8760.
LTG_SCH_LAUNDRY 2678. 8760.
LTG_SCH_GUESTROOM 3599. 8760.
LTG_SCH_CORRIDOR 3061. 8760.
LTG_SCH_RETAIL 2678. 8760.
WALKIN_OCC_LGHT_SCH_1 3061. 8760.
EXTERIOR_LTG_SCH 4380. 4380.
BASEMENT_EQUIP_SCH 3924. 8760.
BLDG_EQUIP_SCH 3924. 8760.
GUESTROOM_EQP_SCH_BASE 3239. 8760.
GUESTROOM_EQP_SCH_ADVA 2762. 8760.
LOBBY_EQP_SCH 3292. 8760.
OFFICE_EQP_SCH 4941. 8760.
EMPLOYEELOUNGE_EQP_SCH 4044. 8760.
LAUNDRYROOM_EQP_ELEC_SCH 2920. 2920.
LAUNDRYROOM_EQP_GAS_SCH 2920. 2920.
MEETINGROOM_EQP_SCH 1336. 4745.
EXERCISEROOM_EQP_SCH 3832. 5840.
KITCHEN_ELEC_EQUIP_SCH 2172. 8760.
KITCHEN_GAS_EQUIP_SCH 1332. 8760.
KITCHEN_EXHAUST_SCH 6205. 6205.
BLDG_ELEVATORS 2270. 8760.
ELEV_LIGHT_FAN_SCH_24_7 8760. 8760.
ELEV_LIGHT_FAN_SCH_ADD_DF 2154. 8760.
BLDG_OCC_SCH 5026. 8760.
GUESTROOM_OCC_SCH 5515. 8760.
LOBBY_OCC_SCH 2304. 8760.
OFFICE_OCC_SCH 3954. 8760.
EMPLOYEELOUNGE_OCC_SCH 948. 5475.
MEETINGROOM_OCC_SCH 1168. 4745.
LAUNDRYROOM_OCC_SCH 427. 2920.
EXERCISEROOM_OCC_SCH 5292. 5840.
INFIL_SCH 8760. 8760.
INFIL_HALF_ON_SCH 4380. 8760.
INFIL_QUARTER_ON_SCH 2190. 8760.
LAUNDRY_SWH_SCH 2555. 2555.
BLDG_SWH_SCH 3301. 8760.
GUESTROOM_SWH_SCH 2899. 8760.
LAUNDRYROOM_SWH_SCH 2920. 2920.
EXTERIOR_LGT_ALWAYS_ON 8760. 8760.
ALWAYS_ON 8760. 8760.
ALWAYS_OFF 0. 0.
FAN_SCH 8760. 8760.
REHEATCOILAVAILSCHED 8760. 8760.
COOLINGCOILAVAILSCHED 8760. 8760.
OCC_GUESTROOM_VENT_CTRL_30MIN 6570. 6570.
OCC_GUESTROOM_VENT_CTRL_20MIN 6327. 6327.
VAC_GUESTROOM_VENTILATION_SCHEDULE 365. 365.
MINOA_MOTORIZEDDAMPER_SCHED 8760. 8760.
MINOA_SCHED 8760. 8760.
WORK_EFF_SCH 0. 0.
ROOM_1_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_1_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_2_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_2_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_5_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_5_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_6_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_6_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_1_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_1_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_2_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_2_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
KITCHEN_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
KITCHEN_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
KITCHEN_FLR_6_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED 2774. 8760.
FLR_3_DOAS_OAMINOAFRACSCHEDULE 8760. 8760.
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE 0. 0.
LAUNDRY_FLR_1 EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE 0. 0.
SLIDING_DOORS_VENTILATION_AVAILABILITY_SCH 3285. 3285.


Schedules-SetPoints (Schedule Type=Temperature)

First Object Used Month Assumed 11am First Wednesday [C] Days with Same 11am Value 11pm First Wednesday [C] Days with Same 11pm Value
VACGUESTROOM_HTGSP_SCH VACGUESTROOM THERMOSTAT DUAL SP CONTROL January 18.89 365 18.89 365
VACGUESTROOM_CLGSP_SCH VACGUESTROOM THERMOSTAT DUAL SP CONTROL July 23.33 365 23.33 365
OBCRESET_S_OCCGUESTROOM_HTGSP_SCH_30MIN S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL January 21.11 365 21.11 365
OBCRESET_S_OCCGUESTROOM_CLGSP_SCH_30MIN S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL July 23.33 365 21.11 365
OBCRESET_N_OCCGUESTROOM_HTGSP_SCH_30MIN N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL January 21.11 365 21.11 365
OBCRESET_N_OCCGUESTROOM_CLGSP_SCH_30MIN N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL July 23.33 365 21.11 365
HTGSETP_SCH BASEMENT DUAL SP CONTROL January 21.00 365 21.00 365
CLGSETP_SCH BASEMENT DUAL SP CONTROL July 24.00 365 24.00 365



Table of Contents

Report: Annual Thermal Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 08:58:10

Heat Index Hours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
BASEMENT 8760.00 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 8760.00 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 8760.00 0.00 0.00 0.00 0.00
MECH_FLR_1 8760.00 0.00 0.00 0.00 0.00
STORAGE_FLR_1 8760.00 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 8760.00 0.00 0.00 0.00 0.00
CAFE_FLR_1 8760.00 0.00 0.00 0.00 0.00
LOBBY_FLR_1 8760.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_5_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_6_FLR_3 8760.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 8760.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_6 8760.00 0.00 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 8760.00 0.00 0.00 0.00 0.00
BANQUET_FLR_6 8760.00 0.00 0.00 0.00 0.00
DINING_FLR_6 8760.00 0.00 0.00 0.00 0.00
KITCHEN_FLR_6 8760.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6 8760.00 0.00 0.00 0.00 0.00
Min 8760.00 0.00 0.00 0.00 0.00
Max 8760.00 0.00 0.00 0.00 0.00
Average 8760.00 0.00 0.00 0.00 0.00
Sum 192720.00 0.00 0.00 0.00 0.00


Heat Index OccupantHours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
BASEMENT 529331.00 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 50179.00 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 59156.00 0.00 0.00 0.00 0.00
MECH_FLR_1 8977.00 0.00 0.00 0.00 0.00
STORAGE_FLR_1 5588.00 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 37203.00 0.00 0.00 0.00 0.00
CAFE_FLR_1 710417.00 0.00 0.00 0.00 0.00
LOBBY_FLR_1 2115429.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 0.00 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_5_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_6_FLR_3 4154.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3 100358.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 4154.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_6 4154.00 0.00 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 4154.00 0.00 0.00 0.00 0.00
BANQUET_FLR_6 1245715.00 0.00 0.00 0.00 0.00
DINING_FLR_6 1245715.00 0.00 0.00 0.00 0.00
KITCHEN_FLR_6 108269.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6 105946.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 2115429.00 0.00 0.00 0.00 0.00
Average 288887.05 0.00 0.00 0.00 0.00
Sum 6355515.00 0.00 0.00 0.00 0.00


Humidex Hours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
BASEMENT 8760.00 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 8760.00 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 8760.00 0.00 0.00 0.00 0.00
MECH_FLR_1 8760.00 0.00 0.00 0.00 0.00
STORAGE_FLR_1 8760.00 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 8760.00 0.00 0.00 0.00 0.00
CAFE_FLR_1 8760.00 0.00 0.00 0.00 0.00
LOBBY_FLR_1 8760.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_5_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_6_FLR_3 8760.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 8760.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_6 8760.00 0.00 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 8760.00 0.00 0.00 0.00 0.00
BANQUET_FLR_6 8760.00 0.00 0.00 0.00 0.00
DINING_FLR_6 8760.00 0.00 0.00 0.00 0.00
KITCHEN_FLR_6 8760.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6 8760.00 0.00 0.00 0.00 0.00
Min 8760.00 0.00 0.00 0.00 0.00
Max 8760.00 0.00 0.00 0.00 0.00
Average 8760.00 0.00 0.00 0.00 0.00
Sum 192720.00 0.00 0.00 0.00 0.00


Humidex OccupantHours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
BASEMENT 529331.00 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 50179.00 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 59156.00 0.00 0.00 0.00 0.00
MECH_FLR_1 8977.00 0.00 0.00 0.00 0.00
STORAGE_FLR_1 5588.00 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 37203.00 0.00 0.00 0.00 0.00
CAFE_FLR_1 710417.00 0.00 0.00 0.00 0.00
LOBBY_FLR_1 2115429.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 0.00 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_5_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_6_FLR_3 4154.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3 100358.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 4154.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_6 4154.00 0.00 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 4154.00 0.00 0.00 0.00 0.00
BANQUET_FLR_6 1245715.00 0.00 0.00 0.00 0.00
DINING_FLR_6 1245715.00 0.00 0.00 0.00 0.00
KITCHEN_FLR_6 108269.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6 105946.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 2115429.00 0.00 0.00 0.00 0.00
Average 288887.05 0.00 0.00 0.00 0.00
Sum 6355515.00 0.00 0.00 0.00 0.00


Heating SET Hours

SET ≤ 12.2°C Hours (°C) SET ≤ 12.2°C OccupantHours (°C) Longest SET ≤ 12.2°C Duration [hr] Start Time of the Longest SET ≤ 12.2°C Duration
None        


Cooling SET Hours

SET > 30°C Hours (°C) SET > 30°C OccupantHours (°C) Longest SET > 30°C Duration [hr] Start Time of the Longest SET > 30°C Duration
None        



Table of Contents

Report: Annual CO2 Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 08:58:10

CO2 Level Hours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      


CO2 Level OccupantHours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      



Table of Contents

Report: Annual Visual Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 08:58:10

Illuminance Level Hours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
None        


Illuminance Level OccupantHours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
None        



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR

For: Environment

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 8.136
February 10.272
March 12.546
April 19.230
May 23.842
June 27.856
July 27.543
August 26.276
September 23.380
October 18.301
November 11.185
December 6.787
   
Annual Sum or Average 17.982
Minimum of Months 6.787
Maximum of Months 27.856



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC

For: Environment

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 8.136
February 10.272
March 12.546
April 19.230
May 23.842
June 27.856
July 27.543
August 26.276
September 23.380
October 18.301
November 11.185
December 6.787
   
Annual Sum or Average 17.982
Minimum of Months 6.787
Maximum of Months 27.856



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2012

For: Environment

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 8.136
February 10.272
March 12.546
April 19.230
May 23.842
June 27.856
July 27.543
August 26.276
September 23.380
October 18.301
November 11.185
December 6.787
   
Annual Sum or Average 17.982
Minimum of Months 6.787
Maximum of Months 27.856



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

For: Environment

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 8.136
February 10.272
March 12.546
April 19.230
May 23.842
June 27.856
July 27.543
August 26.276
September 23.380
October 18.301
November 11.185
December 6.787
   
Annual Sum or Average 17.982
Minimum of Months 6.787
Maximum of Months 27.856



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE

For: Environment

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 8.136
February 10.272
March 12.546
April 19.230
May 23.842
June 27.856
July 27.543
August 26.276
September 23.380
October 18.301
November 11.185
December 6.787
   
Annual Sum or Average 17.982
Minimum of Months 6.787
Maximum of Months 27.856



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

For: Environment

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 8.136
February 10.272
March 12.546
April 19.230
May 23.842
June 27.856
July 27.543
August 26.276
September 23.380
October 18.301
November 11.185
December 6.787
   
Annual Sum or Average 17.982
Minimum of Months 6.787
Maximum of Months 27.856



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

For: Environment

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 8.136
February 10.272
March 12.546
April 19.230
May 23.842
June 27.856
July 27.543
August 26.276
September 23.380
October 18.301
November 11.185
December 6.787
   
Annual Sum or Average 17.982
Minimum of Months 6.787
Maximum of Months 27.856



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3B

For: Environment

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 8.136
February 10.272
March 12.546
April 19.230
May 23.842
June 27.856
July 27.543
August 26.276
September 23.380
October 18.301
November 11.185
December 6.787
   
Annual Sum or Average 17.982
Minimum of Months 6.787
Maximum of Months 27.856



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_TX_ELPASO

For: Environment

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 8.136
February 10.272
March 12.546
April 19.230
May 23.842
June 27.856
July 27.543
August 26.276
September 23.380
October 18.301
November 11.185
December 6.787
   
Annual Sum or Average 17.982
Minimum of Months 6.787
Maximum of Months 27.856



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.399783E+11 19555.90 12-JAN-19:10 15.03 8.30 0.617557E+10 3831.50 06-JAN-22:10 15.03 8.30
February 0.295875E+11 18758.35 22-FEB-20:10 15.18 5.09 0.552790E+10 3761.35 01-FEB-22:10 15.18 5.09
March 0.279918E+11 17799.84 01-MAR-21:00 1.70 -3.0 0.610529E+10 3657.91 01-MAR-22:10 1.02 -3.3
April 0.284020E+11 18271.64 07-APR-20:00 18.90 8.36 0.588692E+10 3620.15 06-APR-21:10 18.90 8.36
May 0.318967E+11 19358.14 11-MAY-20:00 26.70 12.64 0.609305E+10 3646.77 05-MAY-22:10 26.70 12.64
June 0.335022E+11 20361.87 08-JUN-20:00 27.80 15.60 0.591341E+10 3675.58 23-JUN-22:10 23.40 15.27
July 0.414790E+11 22386.27 26-JUL-18:50 31.23 19.55 0.614611E+10 3793.76 07-JUL-22:10 31.23 19.55
August 0.464708E+11 23534.96 07-AUG-18:10 33.95 18.47 0.629621E+10 3898.89 16-AUG-21:10 17.80 16.68
September 0.487767E+11 23757.44 17-SEP-10:35 29.47 15.71 0.623020E+10 4012.25 29-SEP-22:10 18.77 9.00
October 0.497275E+11 23308.91 01-OCT-10:35 26.67 14.26 0.648348E+10 4046.41 13-OCT-21:10 12.70 11.69
November 0.466973E+11 21752.54 09-NOV-19:10 20.50 11.67 0.626630E+10 4042.90 01-NOV-21:10 20.50 11.67
December 0.453498E+11 20408.78 01-DEC-21:00 6.70 2.22 0.633229E+10 3985.99 01-DEC-22:10 7.12 2.19
                     
Annual Sum or Average 0.469860E+12         0.734567E+11        
Minimum of Months 0.279918E+11 17799.84   1.70 -3.0 0.552790E+10 3620.15   1.02 -3.3
Maximum of Months 0.497275E+11 23757.44   33.95 19.55 0.648348E+10 4046.41   31.23 19.55



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.244750E+10 3022.90 01-JAN-11:35 13.87 8.54 0.621948E+09 364.26 03-JAN-02:00 2.80 0.09
February 0.256139E+10 3122.37 07-FEB-11:35 19.63 9.18 0.562773E+09 364.27 11-FEB-05:49 4.68 0.24
March 0.300656E+10 2938.03 05-MAR-11:35 16.83 7.89 0.623913E+09 364.26 11-MAR-02:49 12.02 9.75
April 0.407903E+10 2815.06 04-APR-10:35 22.97 9.90 0.602287E+09 382.30 19-APR-21:40 27.57 11.97
May 0.503807E+10 3042.50 31-MAY-18:02 30.92 15.25 0.622754E+09 392.49 19-MAY-21:40 30.92 15.25
June 0.582936E+10 3338.82 15-JUN-18:10 35.92 14.47 0.610220E+09 403.95 16-JUN-21:00 31.10 15.68
July 0.602315E+10 3323.83 26-JUL-18:10 33.77 19.75 0.626660E+09 400.18 25-JUL-21:49 33.77 19.75
August 0.593716E+10 3369.31 27-AUG-10:35 32.03 15.07 0.630767E+09 405.63 07-AUG-21:40 32.03 15.07
September 0.569432E+10 3489.09 17-SEP-10:35 29.47 15.71 0.611655E+09 394.65 20-SEP-22:10 26.52 16.85
October 0.489134E+10 3559.87 05-OCT-10:35 27.60 18.63 0.629965E+09 387.65 05-OCT-21:30 23.05 16.20
November 0.325898E+10 3458.94 10-NOV-11:35 20.93 12.02 0.605176E+09 364.94 09-NOV-22:19 20.93 12.02
December 0.219908E+10 2909.21 09-DEC-11:40 16.10 7.03 0.621276E+09 364.26 18-DEC-04:10 5.40 -1.6
                     
Annual Sum or Average 0.509659E+11         0.736939E+10        
Minimum of Months 0.219908E+10 2815.06   13.87 7.03 0.562773E+09 364.26   2.80 -1.6
Maximum of Months 0.602315E+10 3559.87   35.92 19.75 0.630767E+09 405.63   33.77 19.75



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.285831E+10 1847.61 12-JAN-21:00 12.80 7.31 0.718694E+09 438.18 12-JAN-22:19 9.47 5.03
February 0.275726E+10 1916.25 21-FEB-21:00 15.00 4.44 0.650473E+09 445.65 21-FEB-22:19 12.93 3.71
March 0.328319E+10 2002.14 16-MAR-18:01 19.82 7.14 0.725096E+09 450.64 16-MAR-21:40 16.47 6.01
April 0.375348E+10 2217.48 19-APR-18:10 29.90 13.60 0.705989E+09 467.22 19-APR-22:10 26.93 11.76
May 0.428642E+10 2302.72 31-MAY-18:10 30.92 15.25 0.737979E+09 477.92 19-MAY-22:10 30.92 15.25
June 0.451008E+10 2435.52 15-JUN-18:10 35.92 14.47 0.726458E+09 487.88 16-JUN-22:10 30.92 15.69
July 0.462676E+10 2419.51 26-JUL-18:10 33.77 19.75 0.744456E+09 483.42 25-JUL-22:10 33.77 19.75
August 0.455716E+10 2399.11 07-AUG-18:10 33.95 18.47 0.746270E+09 482.63 07-AUG-21:49 29.45 17.70
September 0.432334E+10 2311.02 20-SEP-18:10 31.05 16.15 0.715584E+09 476.68 20-SEP-22:10 26.52 16.85
October 0.397260E+10 2238.59 05-OCT-18:10 27.15 16.93 0.729173E+09 470.60 05-OCT-22:10 22.98 16.25
November 0.316893E+10 2021.03 09-NOV-19:10 20.50 11.67 0.697610E+09 452.94 09-NOV-22:19 18.17 10.78
December 0.271562E+10 1818.49 15-DEC-21:00 14.40 4.76 0.718021E+09 435.53 15-DEC-22:19 14.23 4.60
                     
Annual Sum or Average 0.448132E+11         0.861580E+10        
Minimum of Months 0.271562E+10 1818.49   12.80 4.44 0.650473E+09 435.53   9.47 3.71
Maximum of Months 0.462676E+10 2435.52   35.92 19.75 0.746270E+09 487.88   33.77 19.75



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.122882E+10 1563.50 03-JAN-21:00 14.40 6.79 0.151697E+09 89.15 17-JAN-04:40 5.60 3.88
February 0.143565E+10 1778.86 07-FEB-20:50 15.78 7.73 0.137151E+09 89.16 24-FEB-04:00 5.60 0.21
March 0.205179E+10 1965.52 16-MAR-20:00 17.20 5.94 0.152415E+09 89.80 16-MAR-21:10 17.02 5.96
April 0.311739E+10 2228.19 19-APR-19:10 29.22 13.15 0.147414E+09 93.75 21-APR-21:19 24.80 9.48
May 0.416103E+10 2442.52 31-MAY-18:10 30.92 15.25 0.153397E+09 96.30 19-MAY-22:10 30.92 15.25
June 0.477983E+10 2587.17 15-JUN-18:10 35.92 14.47 0.150781E+09 99.20 16-JUN-22:10 30.92 15.69
July 0.489703E+10 2596.05 03-JUL-18:10 36.28 18.94 0.154676E+09 97.96 03-JUL-22:10 25.82 18.63
August 0.462066E+10 2526.66 07-AUG-18:10 33.95 18.47 0.154549E+09 97.54 07-AUG-22:10 28.52 18.18
September 0.401764E+10 2395.61 20-SEP-18:02 31.05 16.15 0.148063E+09 95.05 22-SEP-21:19 25.00 17.90
October 0.317317E+10 2288.28 05-OCT-18:20 26.50 16.93 0.152049E+09 93.59 03-OCT-21:10 26.50 16.93
November 0.179613E+10 1986.67 09-NOV-21:00 20.00 11.27 0.146747E+09 90.12 09-NOV-22:10 18.53 10.92
December 0.102693E+10 1480.93 15-DEC-21:00 14.40 4.76 0.151697E+09 89.16 20-DEC-04:00 8.30 -1.0
                     
Annual Sum or Average 0.363061E+11         0.180064E+10        
Minimum of Months 0.102693E+10 1480.93   14.40 4.76 0.137151E+09 89.15   5.60 -1.0
Maximum of Months 0.489703E+10 2596.05   36.28 18.94 0.154676E+09 99.20   30.92 18.63



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.236821E+09 482.31 03-JAN-21:10 14.13 6.70 0.116691E+09 68.58 07-JAN-04:40 -1.3 -4.4
February 0.392934E+09 603.96 07-FEB-22:00 15.00 7.49 0.105501E+09 68.58 14-FEB-01:00 11.10 8.31
March 0.665757E+09 720.48 15-MAR-21:00 20.00 7.66 0.117239E+09 68.58 11-MAR-02:49 20.00 7.66
April 0.131565E+10 1023.00 21-APR-20:00 26.10 11.77 0.113143E+09 69.82 21-APR-22:10 24.13 8.96
May 0.193191E+10 1151.80 31-MAY-19:10 29.90 14.49 0.117209E+09 71.81 19-MAY-22:10 29.90 14.49
June 0.233656E+10 1284.12 15-JUN-18:10 35.92 14.47 0.114804E+09 73.89 16-JUN-22:10 30.92 15.69
July 0.239291E+10 1284.44 03-JUL-18:10 36.28 18.94 0.117824E+09 72.79 03-JUL-22:10 25.82 18.63
August 0.222077E+10 1231.30 07-AUG-18:20 33.50 18.31 0.117873E+09 72.65 07-AUG-21:49 29.45 17.70
September 0.186352E+10 1092.51 21-SEP-20:00 25.60 16.42 0.113222E+09 70.83 22-SEP-22:10 24.90 17.87
October 0.133440E+10 1026.04 05-OCT-20:00 23.90 16.65 0.116768E+09 69.77 05-OCT-22:10 22.98 16.25
November 0.546487E+09 752.97 09-NOV-22:00 18.90 11.06 0.112879E+09 68.58 08-NOV-01:10 18.90 11.06
December 0.172537E+09 458.27 15-DEC-22:00 14.40 4.62 0.116691E+09 68.58 20-DEC-04:30 8.05 -1.0
                     
Annual Sum or Average 0.154103E+11         0.137985E+10        
Minimum of Months 0.172537E+09 458.27   14.13 4.62 0.105501E+09 68.58   -1.3 -4.4
Maximum of Months 0.239291E+10 1284.44   36.28 18.94 0.117873E+09 73.89   30.92 18.63



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.491929E+11 35924.14 03-JAN-21:00 14.40 6.79 0.510315E+09 381.72 20-JAN-22:10 10.40 4.96
February 0.450817E+11 36275.22 21-FEB-21:00 15.00 4.44 0.461433E+09 381.74 14-FEB-22:10 15.00 4.44
March 0.507675E+11 36418.54 21-MAR-20:00 16.70 5.61 0.513072E+09 381.77 03-MAR-22:10 16.70 5.61
April 0.507980E+11 37455.04 19-APR-20:00 28.30 12.40 0.493079E+09 381.73 11-APR-21:10 28.30 12.40
May 0.538274E+11 37787.26 31-MAY-20:00 29.40 14.60 0.509182E+09 381.72 05-MAY-21:10 29.40 14.60
June 0.532481E+11 38342.34 15-JUN-20:00 33.90 14.00 0.492810E+09 381.63 30-JUN-21:10 28.83 15.17
July 0.547057E+11 38198.40 26-JUL-20:00 29.40 19.17 0.505715E+09 381.60 07-JUL-21:10 29.40 19.17
August 0.545148E+11 38120.41 07-AUG-20:00 31.70 17.36 0.509843E+09 381.64 25-AUG-21:10 27.62 14.77
September 0.520501E+11 37647.42 20-SEP-20:00 25.60 15.27 0.491867E+09 381.70 26-SEP-21:10 20.55 11.34
October 0.520921E+11 37405.15 05-OCT-20:00 23.90 16.65 0.509071E+09 381.80 10-OCT-21:10 14.13 9.16
November 0.486277E+11 36481.70 09-NOV-21:00 20.00 11.27 0.493735E+09 381.72 17-NOV-22:10 11.02 3.83
December 0.488149E+11 35799.25 15-DEC-21:00 14.40 4.76 0.510015E+09 381.72 05-DEC-22:10 14.40 4.76
                     
Annual Sum or Average 0.613721E+12         0.600014E+10        
Minimum of Months 0.450817E+11 35799.25   14.40 4.44 0.461433E+09 381.60   10.40 3.83
Maximum of Months 0.547057E+11 38342.34   33.90 19.17 0.513072E+09 381.80   29.40 19.17



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.204569E+11 12726.90 01-JAN-11:35 13.87 8.54 0.818808E+10 5092.46 03-JAN-22:19 12.07 5.91
February 0.194137E+11 13089.37 19-FEB-11:35 19.03 7.40 0.741896E+10 5267.39 06-FEB-22:30 19.03 7.40
March 0.217415E+11 12405.00 05-MAR-11:35 16.83 7.89 0.824614E+10 5245.91 15-MAR-21:40 19.60 7.41
April 0.235954E+11 12875.44 19-APR-18:03 29.90 13.60 0.807998E+10 5517.48 19-APR-21:40 27.57 11.97
May 0.259589E+11 13365.11 31-MAY-18:10 30.92 15.25 0.846592E+10 5594.55 19-MAY-22:10 30.92 15.25
June 0.272956E+11 14106.58 14-JUN-18:10 37.02 14.90 0.838694E+10 5677.92 16-JUN-22:10 30.92 15.69
July 0.282494E+11 14111.07 03-JUL-18:10 36.28 18.94 0.861314E+10 5640.40 25-JUL-21:40 30.57 17.35
August 0.282619E+11 14049.84 07-AUG-18:10 33.95 18.47 0.865954E+10 5686.68 07-AUG-21:40 29.90 17.57
September 0.275901E+11 14200.35 17-SEP-10:35 29.47 15.71 0.831695E+10 5606.79 20-SEP-22:10 26.52 16.85
October 0.264077E+11 14157.01 22-OCT-10:35 22.23 13.01 0.847823E+10 5544.87 05-OCT-21:40 22.23 13.01
November 0.221888E+11 13773.93 11-NOV-11:35 16.83 7.74 0.800994E+10 5374.14 09-NOV-22:19 16.83 7.74
December 0.195785E+11 12324.52 10-DEC-11:35 15.93 7.48 0.817206E+10 5069.40 15-DEC-22:30 14.15 4.60
                     
Annual Sum or Average 0.290739E+12         0.990359E+11        
Minimum of Months 0.194137E+11 12324.52   13.87 7.40 0.741896E+10 5069.40   12.07 4.60
Maximum of Months 0.282619E+11 14200.35   37.02 18.94 0.865954E+10 5686.68   30.92 17.57



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.697421E+11 37038.98 12-JAN-19:10 15.03 8.30 0.244070E+11 15432.38 03-JAN-22:40 15.03 8.30
February 0.654859E+11 37963.05 22-FEB-19:03 17.75 6.22 0.221368E+11 15695.37 06-FEB-22:40 17.75 6.22
March 0.744255E+11 39314.42 16-MAR-18:10 19.82 7.14 0.247386E+11 15817.53 16-MAR-21:40 16.47 6.01
April 0.794426E+11 43050.52 19-APR-18:10 29.90 13.60 0.242778E+11 16309.70 19-APR-22:10 26.93 11.76
May 0.875451E+11 44823.93 31-MAY-18:10 30.92 15.25 0.254906E+11 16613.08 19-MAY-22:10 30.92 15.25
June 0.906914E+11 46864.58 15-JUN-18:10 35.92 14.47 0.251185E+11 16862.21 16-JUN-22:10 30.92 15.69
July 0.935526E+11 46885.37 03-JUL-18:10 36.28 18.94 0.257739E+11 16715.74 25-JUL-22:10 30.00 17.07
August 0.927357E+11 46323.01 07-AUG-18:10 33.95 18.47 0.258506E+11 16745.18 07-AUG-21:49 29.45 17.70
September 0.887692E+11 44736.94 20-SEP-18:10 31.05 16.15 0.247195E+11 16526.22 22-SEP-22:10 24.90 17.87
October 0.854536E+11 43560.26 05-OCT-18:10 27.15 16.93 0.251388E+11 16395.09 05-OCT-22:10 22.98 16.25
November 0.734748E+11 39725.35 09-NOV-19:10 20.50 11.67 0.238037E+11 15946.74 09-NOV-22:40 17.43 10.49
December 0.677825E+11 36331.62 15-DEC-21:00 14.40 4.76 0.243458E+11 15407.33 15-DEC-22:40 14.07 4.59
                     
Annual Sum or Average 0.969101E+12         0.295802E+12        
Minimum of Months 0.654859E+11 36331.62   14.40 4.76 0.221368E+11 15407.33   14.07 4.59
Maximum of Months 0.935526E+11 46885.37   36.28 18.94 0.258506E+11 16862.21   30.92 17.87



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.291010E+09 3759.58 12-JAN-16:01 18.72 10.12 96034064.25 56.69 03-JAN-22:10 18.72 10.12
February 0.414130E+09 3836.15 20-FEB-16:01 23.12 8.59 87307297.40 56.69 06-FEB-22:40 23.12 8.59
March 0.701934E+09 3824.56 16-MAR-15:01 22.70 8.66 97443760.05 56.69 07-MAR-22:10 22.70 8.66
April 0.149638E+10 3861.25 30-APR-15:01 30.10 12.65 95193008.76 56.70 28-APR-21:30 30.10 12.65
May 0.223455E+10 3885.84 20-MAY-15:01 32.20 15.53 98835530.41 56.70 23-MAY-22:10 20.92 15.65
June 0.280348E+10 3885.67 15-JUN-18:02 35.92 14.47 95915397.02 56.70 16-JUN-21:49 31.38 15.54
July 0.279262E+10 3519.24 19-JUL-18:02 28.72 20.94 99033318.08 56.70 24-JUL-21:10 29.63 17.48
August 0.261629E+10 3888.00 23-AUG-15:01 33.30 16.20 99038719.64 56.70 04-AUG-21:10 33.30 16.20
September 0.234044E+10 3887.91 11-SEP-15:01 29.40 13.84 95704577.47 56.70 22-SEP-23:00 21.70 19.30
October 0.156026E+10 3896.79 01-OCT-15:01 32.62 15.84 98375869.30 56.70 18-OCT-21:30 21.40 16.61
November 0.637583E+09 3840.31 09-NOV-16:01 23.22 12.98 93997934.52 56.69 09-NOV-22:00 16.70 10.18
December 0.213944E+09 3706.74 17-DEC-16:01 15.32 4.54 95720405.98 56.69 13-DEC-00:10 15.32 4.54
                     
Annual Sum or Average 0.181026E+11         0.115260E+10        
Minimum of Months 0.213944E+09 3519.24   15.32 4.54 87307297.40 56.69   15.32 4.54
Maximum of Months 0.280348E+10 3896.79   35.92 20.94 99038719.64 56.70   33.30 19.30



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.112700E+09 3612.50 12-JAN-16:01 18.72 10.12 94351268.31 56.69 03-JAN-22:19 18.72 10.12
February 0.204049E+09 3759.91 20-FEB-16:01 23.12 8.59 86017634.41 56.69 06-FEB-22:19 23.12 8.59
March 0.475679E+09 3755.94 16-MAR-15:01 22.70 8.66 96545582.05 56.69 16-MAR-21:30 16.65 6.00
April 0.131458E+10 3825.68 30-APR-15:01 30.10 12.65 94927066.23 56.69 17-APR-01:10 30.10 12.65
May 0.218520E+10 3857.13 20-MAY-15:01 32.20 15.53 98801041.11 56.70 23-MAY-22:10 20.92 15.65
June 0.281738E+10 3870.47 15-JUN-18:02 35.92 14.47 95934944.41 56.70 28-JUN-00:20 20.17 17.30
July 0.277963E+10 3500.64 30-JUL-18:02 28.80 20.02 99044750.90 56.70 24-JUL-21:10 28.80 20.02
August 0.248230E+10 3848.93 23-AUG-15:01 33.30 16.20 99007546.72 56.70 04-AUG-21:10 33.30 16.20
September 0.200325E+10 3834.31 11-SEP-15:01 29.40 13.84 95564081.23 56.70 15-SEP-21:49 22.38 17.21
October 0.112035E+10 3830.17 01-OCT-15:01 32.62 15.84 97760995.97 56.70 04-OCT-22:10 23.72 17.31
November 0.282604E+09 3767.81 09-NOV-16:01 23.22 12.98 92705462.41 56.69 09-NOV-22:10 18.53 10.92
December 84319218.93 3460.05 16-DEC-16:02 14.72 4.08 93943541.86 56.69 13-DEC-00:10 14.72 4.08
                     
Annual Sum or Average 0.158620E+11         0.114460E+10        
Minimum of Months 84319218.93 3460.05   14.72 4.08 86017634.41 56.69   14.72 4.08
Maximum of Months 0.281738E+10 3870.47   35.92 20.02 99044750.90 56.70   33.30 20.02



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.500266E+09 609.96 12-JAN-14:30 18.60 9.87 0.00 0.00 01-JAN-00:10 18.60 9.87
February 0.474835E+09 599.57 20-FEB-14:10 22.38 8.53 0.00 0.00 01-FEB-00:10 22.38 8.53
March 0.480837E+09 503.71 16-MAR-13:30 22.50 9.16 0.00 0.00 01-MAR-00:10 22.50 9.16
April 0.615775E+09 492.06 03-APR-14:00 26.70 11.71 0.00 0.00 01-APR-00:10 26.70 11.71
May 0.741915E+09 512.18 19-MAY-20:20 30.73 14.26 0.00 0.00 01-MAY-00:10 30.73 14.26
June 0.878804E+09 560.98 15-JUN-20:20 33.70 13.91 0.00 0.00 01-JUN-00:10 33.70 13.91
July 0.923284E+09 573.47 02-JUL-20:50 32.98 17.29 0.00 0.00 01-JUL-00:10 32.98 17.29
August 0.926030E+09 577.40 06-AUG-19:05 34.63 17.82 0.00 0.00 01-AUG-00:10 34.63 17.82
September 0.946650E+09 668.56 19-SEP-13:30 33.35 16.80 0.00 0.00 01-SEP-00:10 33.35 16.80
October 0.852397E+09 735.62 22-OCT-13:20 25.97 14.61 0.00 0.00 01-OCT-00:10 25.97 14.61
November 0.639842E+09 683.34 09-NOV-13:50 23.22 12.39 0.00 0.00 01-NOV-00:10 23.22 12.39
December 0.466444E+09 543.88 16-DEC-13:40 14.63 4.10 0.00 0.00 01-DEC-00:10 14.63 4.10
                     
Annual Sum or Average 0.844708E+10         0.00        
Minimum of Months 0.466444E+09 492.06   14.63 4.10 0.00 0.00   14.63 4.10
Maximum of Months 0.946650E+09 735.62   34.63 17.82 0.00 0.00   34.63 17.82



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.193106E+09 1237.57 13-JAN-19:02 13.12 6.39 95349766.29 56.69 03-JAN-22:00 13.12 6.39
February 0.253903E+09 1305.91 20-FEB-16:01 23.12 8.59 86529316.73 56.69 23-FEB-22:10 11.93 4.94
March 0.400229E+09 1357.97 15-MAR-18:01 21.60 8.24 96480864.72 56.69 03-MAR-22:10 21.60 8.24
April 0.693938E+09 1430.39 28-APR-18:01 28.03 14.00 94454876.77 56.69 06-APR-21:49 28.03 14.00
May 0.983606E+09 1438.17 13-MAY-18:01 31.42 15.36 98438927.33 56.69 29-MAY-00:49 18.80 14.41
June 0.117155E+10 1437.32 17-JUN-18:02 35.45 16.60 95732159.98 56.70 22-JUN-21:40 23.30 16.17
July 0.119575E+10 1335.10 15-JUL-15:02 32.80 18.56 98842887.19 56.70 21-JUL-21:40 23.90 20.77
August 0.108109E+10 1439.01 27-AUG-18:01 33.12 16.39 98698823.53 56.70 02-AUG-21:00 33.12 16.39
September 0.885854E+09 1431.17 17-SEP-18:01 29.95 14.68 95133334.79 56.69 07-SEP-21:10 29.95 14.68
October 0.652720E+09 1429.37 01-OCT-18:01 29.82 14.44 97295919.23 56.69 04-OCT-21:10 25.32 17.67
November 0.297898E+09 1324.44 08-NOV-19:01 20.92 10.67 92889171.32 56.69 02-NOV-21:10 20.92 10.67
December 0.159631E+09 1276.22 09-DEC-09:01 14.40 6.77 95019223.60 56.69 13-DEC-22:10 7.80 4.56
                     
Annual Sum or Average 0.796927E+10         0.114487E+10        
Minimum of Months 0.159631E+09 1237.57   13.12 6.39 86529316.73 56.69   7.80 4.56
Maximum of Months 0.119575E+10 1439.01   35.45 18.56 98842887.19 56.70   33.12 20.77



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.274171E+09 3310.05 12-JAN-16:01 18.72 10.12 96118899.68 56.69 03-JAN-22:10 18.72 10.12
February 0.455966E+09 3362.24 20-FEB-16:01 23.12 8.59 87726407.39 56.69 06-FEB-23:10 23.12 8.59
March 0.712228E+09 3360.55 16-MAR-15:01 22.70 8.66 97871812.85 56.69 06-MAR-22:10 22.70 8.66
April 0.155353E+10 3406.27 21-APR-15:01 32.02 15.38 95691315.21 56.70 28-APR-21:40 22.07 12.89
May 0.226249E+10 3437.47 30-MAY-08:61 26.78 12.99 99153022.86 56.70 24-MAY-21:00 26.78 12.99
June 0.286530E+10 3453.68 15-JUN-08:61 29.78 13.66 96019535.39 56.70 20-JUN-21:10 27.02 16.19
July 0.285107E+10 3199.63 09-JUL-08:61 24.68 18.54 99118072.33 56.70 14-JUL-21:10 27.33 20.00
August 0.266347E+10 3427.25 23-AUG-15:01 33.30 16.20 99156042.68 56.70 09-AUG-21:10 33.30 16.20
September 0.234031E+10 3409.22 11-SEP-15:01 29.40 13.84 95901315.46 56.70 13-SEP-00:49 23.90 17.48
October 0.146487E+10 3423.87 01-OCT-15:01 32.62 15.84 98515872.05 56.70 03-OCT-22:10 20.10 18.04
November 0.606318E+09 3373.31 09-NOV-16:01 23.22 12.98 94289220.23 56.69 09-NOV-23:10 16.70 10.07
December 0.229294E+09 3288.81 09-DEC-09:01 14.40 6.77 95802214.83 56.69 13-DEC-00:10 6.47 5.55
                     
Annual Sum or Average 0.182790E+11         0.115536E+10        
Minimum of Months 0.229294E+09 3199.63   14.40 6.77 87726407.39 56.69   6.47 5.55
Maximum of Months 0.286530E+10 3453.68   33.30 18.54 99156042.68 56.70   33.30 20.00



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 98970386.78 2270.82 31-JAN-09:02 10.78 4.13 94272920.95 56.69 03-JAN-22:19 10.78 4.13
February 0.227766E+09 3276.96 20-FEB-09:01 11.23 4.20 86322396.75 56.69 06-FEB-22:19 11.23 4.20
March 0.479639E+09 3300.11 22-MAR-15:01 23.90 8.87 96937660.79 56.69 16-MAR-22:40 23.90 8.87
April 0.136197E+10 3370.34 21-APR-15:01 32.02 15.38 95530553.71 56.69 28-APR-21:19 22.43 12.87
May 0.220991E+10 3415.24 30-MAY-08:61 26.78 12.99 99148123.80 56.70 24-MAY-21:00 26.78 12.99
June 0.287962E+10 3432.35 15-JUN-08:61 29.78 13.66 96021125.42 56.70 20-JUN-21:10 27.02 16.19
July 0.283793E+10 3175.56 09-JUL-08:61 24.68 18.54 99118416.09 56.70 14-JUL-21:10 27.33 20.00
August 0.252612E+10 3389.82 23-AUG-15:01 33.30 16.20 99145490.54 56.70 04-AUG-21:00 33.30 16.20
September 0.199157E+10 3363.17 18-SEP-18:01 30.55 13.88 95866109.18 56.70 08-SEP-21:49 30.55 13.88
October 0.101415E+10 3361.38 01-OCT-15:01 32.62 15.84 98021283.60 56.70 04-OCT-21:00 23.90 17.47
November 0.268382E+09 3265.24 11-NOV-09:01 11.65 7.11 92634849.61 56.69 09-NOV-22:10 11.65 7.11
December 87426467.33 3068.81 09-DEC-09:01 14.40 6.77 93930757.62 56.69 13-DEC-00:10 6.47 5.55
                     
Annual Sum or Average 0.159835E+11         0.114695E+10        
Minimum of Months 87426467.33 2270.82   10.78 4.13 86322396.75 56.69   6.47 4.13
Maximum of Months 0.287962E+10 3432.35   33.30 18.54 99148123.80 56.70   33.30 20.00



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.272649E+10 2019.50 12-JAN-21:10 12.43 7.05 0.119883E+10 706.46 03-JAN-22:30 12.43 7.05
February 0.301152E+10 2223.02 21-FEB-17:20 21.67 7.52 0.108454E+10 718.77 06-FEB-22:40 21.67 7.52
March 0.386106E+10 2443.30 16-MAR-18:10 19.82 7.14 0.120634E+10 727.33 16-MAR-21:40 16.47 6.01
April 0.508803E+10 2790.56 30-APR-10:35 24.07 13.08 0.118305E+10 759.82 21-APR-21:49 24.07 13.08
May 0.602453E+10 2988.55 31-MAY-18:10 30.92 15.25 0.126758E+10 790.94 19-MAY-22:10 30.92 15.25
June 0.644376E+10 3255.23 15-JUN-18:10 35.92 14.47 0.128919E+10 826.08 16-JUN-22:10 30.92 15.69
July 0.658709E+10 3202.42 03-JUL-18:10 36.28 18.94 0.131633E+10 810.70 27-JUL-21:49 28.40 18.33
August 0.646313E+10 3195.71 07-AUG-18:10 33.95 18.47 0.131241E+10 819.29 07-AUG-21:49 29.45 17.70
September 0.607490E+10 3036.52 20-SEP-18:10 31.05 16.15 0.124814E+10 799.73 21-SEP-22:10 26.02 17.91
October 0.541014E+10 2919.31 05-OCT-10:35 27.60 18.63 0.123252E+10 783.42 05-OCT-21:49 22.88 16.22
November 0.368785E+10 2532.30 10-NOV-11:35 20.93 12.02 0.116217E+10 733.48 09-NOV-22:40 20.93 12.02
December 0.240032E+10 1917.06 15-DEC-22:03 14.32 4.61 0.119882E+10 704.52 20-DEC-04:40 8.13 -1.0
                     
Annual Sum or Average 0.577788E+11         0.146999E+11        
Minimum of Months 0.240032E+10 1917.06   12.43 4.61 0.108454E+10 704.52   8.13 -1.0
Maximum of Months 0.658709E+10 3255.23   36.28 18.94 0.131633E+10 826.08   30.92 18.33



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.248610E+09 4050.02 12-JAN-16:01 18.72 10.12 95577812.88 56.69 03-JAN-22:19 18.72 10.12
February 0.390109E+09 4134.16 20-FEB-16:01 23.12 8.59 87042066.83 56.69 20-FEB-01:10 23.12 8.59
March 0.703454E+09 4127.26 14-MAR-15:01 23.98 9.90 97281698.01 56.69 16-MAR-22:10 15.27 5.99
April 0.165512E+10 4185.30 30-APR-15:01 30.10 12.65 95186459.95 56.70 25-APR-04:19 30.10 12.65
May 0.251895E+10 4206.83 20-MAY-15:01 32.20 15.53 98862823.56 56.70 23-MAY-21:49 21.28 15.82
June 0.320649E+10 4203.83 15-JUN-15:02 38.22 15.87 95942424.46 56.70 19-JUN-01:39 24.80 16.53
July 0.321434E+10 3706.06 26-JUL-08:61 29.08 18.80 99064124.72 56.70 06-JUL-21:10 29.08 18.80
August 0.298239E+10 4206.00 23-AUG-15:01 33.30 16.20 99070432.45 56.70 07-AUG-21:49 33.30 16.20
September 0.261398E+10 4210.81 11-SEP-15:01 29.40 13.84 95710199.37 56.70 07-SEP-22:10 29.40 13.84
October 0.165992E+10 4215.21 01-OCT-15:01 32.62 15.84 98327146.24 56.70 04-OCT-22:40 23.17 16.85
November 0.614909E+09 4141.38 09-NOV-16:01 23.22 12.98 93750898.77 56.69 09-NOV-22:40 17.43 10.49
December 0.174374E+09 3980.47 17-DEC-16:01 15.32 4.54 95249776.99 56.69 15-DEC-22:19 15.32 4.54
                     
Annual Sum or Average 0.199826E+11         0.115107E+10        
Minimum of Months 0.174374E+09 3706.06   15.32 4.54 87042066.83 56.69   15.27 4.54
Maximum of Months 0.321434E+10 4215.21   38.22 18.80 99070432.45 56.70   33.30 18.80



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 88467892.38 3905.56 12-JAN-16:01 18.72 10.12 93855983.55 56.69 04-JAN-00:20 18.72 10.12
February 0.185794E+09 4041.96 20-FEB-16:01 23.12 8.59 85733302.50 56.69 06-FEB-22:40 23.12 8.59
March 0.469378E+09 4036.89 16-MAR-15:01 22.70 8.66 96401922.21 56.69 15-MAR-21:10 22.70 8.66
April 0.145822E+10 4142.67 30-APR-15:01 30.10 12.65 94981929.43 56.70 26-APR-02:30 30.10 12.65
May 0.246559E+10 4171.66 20-MAY-15:01 32.20 15.53 98844529.41 56.70 02-MAY-02:49 32.20 15.53
June 0.322086E+10 4183.35 15-JUN-18:02 35.92 14.47 95962329.46 56.70 16-JUN-22:10 30.92 15.69
July 0.320034E+10 3690.46 26-JUL-08:61 29.08 18.80 99076531.03 56.70 27-JUL-21:10 28.80 18.36
August 0.283914E+10 4159.28 23-AUG-15:01 33.30 16.20 99051490.59 56.70 07-AUG-21:49 33.30 16.20
September 0.225231E+10 4147.11 11-SEP-15:01 29.40 13.84 95588524.86 56.70 13-SEP-21:00 21.70 17.53
October 0.118511E+10 4136.31 01-OCT-15:01 32.62 15.84 97811138.60 56.70 10-OCT-01:39 13.90 9.09
November 0.259538E+09 4052.63 09-NOV-16:01 23.22 12.98 92442734.17 56.69 09-NOV-01:39 23.22 12.98
December 64245030.83 3451.10 16-DEC-16:02 14.72 4.08 93454623.04 56.69 13-DEC-00:10 14.72 4.08
                     
Annual Sum or Average 0.176890E+11         0.114321E+10        
Minimum of Months 64245030.83 3451.10   14.72 4.08 85733302.50 56.69   13.90 4.08
Maximum of Months 0.322086E+10 4183.35   35.92 18.80 99076531.03 56.70   33.30 18.36



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.590227E+09 2144.90 12-JAN-16:01 18.72 10.12 97522172.46 56.69 20-JAN-22:19 10.20 4.85
February 0.615629E+09 2163.14 20-FEB-16:01 23.12 8.59 88407106.27 56.69 06-FEB-22:10 23.12 8.59
March 0.658002E+09 2163.13 14-MAR-15:01 23.98 9.90 98009783.40 56.69 16-MAR-21:00 16.10 6.03
April 0.101502E+10 2159.09 03-APR-15:01 26.88 11.50 95291983.39 56.69 28-APR-22:10 21.52 12.87
May 0.132144E+10 2157.59 20-MAY-15:01 32.20 15.53 98826960.97 56.69 22-MAY-22:00 22.80 14.76
June 0.164706E+10 2155.36 12-JUN-15:01 33.98 15.96 95899522.66 56.70 07-JUN-21:10 33.98 15.96
July 0.171716E+10 1981.99 23-JUL-18:02 31.02 18.90 99029496.64 56.70 26-JUL-21:00 27.20 18.25
August 0.169997E+10 1972.67 31-AUG-18:01 27.52 16.76 99053274.08 56.70 03-AUG-21:40 27.52 16.76
September 0.167679E+10 2180.20 30-SEP-15:01 28.30 13.14 95752774.77 56.70 20-SEP-22:10 28.30 13.14
October 0.139255E+10 2196.57 01-OCT-15:01 32.62 15.84 98619859.56 56.70 18-OCT-21:10 21.60 16.55
November 0.876308E+09 2171.97 09-NOV-16:01 23.22 12.98 94877090.60 56.69 09-NOV-22:00 16.70 10.18
December 0.538285E+09 2113.72 30-DEC-16:01 12.02 4.39 97423062.39 56.69 05-DEC-22:19 12.02 4.39
                     
Annual Sum or Average 0.137484E+11         0.115871E+10        
Minimum of Months 0.538285E+09 1972.67   12.02 4.39 88407106.27 56.69   10.20 4.39
Maximum of Months 0.171716E+10 2196.57   33.98 18.90 99053274.08 56.70   33.98 18.25



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.383879E+11 19070.69 03-JAN-22:20 12.07 5.91 0.149050E+11 9769.05 03-JAN-22:19 12.07 5.91
February 0.359952E+11 19607.35 07-FEB-23:00 15.60 8.35 0.135697E+11 9970.03 06-FEB-23:10 15.60 8.35
March 0.416247E+11 20039.51 15-MAR-22:00 19.40 7.29 0.152631E+11 10134.44 15-MAR-22:10 19.32 7.27
April 0.442123E+11 22065.71 19-APR-18:10 29.90 13.60 0.150953E+11 10476.51 19-APR-22:10 26.93 11.76
May 0.486655E+11 23213.15 31-MAY-18:10 30.92 15.25 0.159465E+11 10687.16 19-MAY-22:10 30.92 15.25
June 0.499971E+11 24499.85 15-JUN-18:10 35.92 14.47 0.157937E+11 10850.30 16-JUN-22:10 30.92 15.69
July 0.514189E+11 24280.63 03-JUL-18:10 36.28 18.94 0.161822E+11 10748.27 25-JUL-22:10 30.00 17.07
August 0.503507E+11 23987.51 07-AUG-18:10 33.95 18.47 0.161545E+11 10754.53 07-AUG-21:40 29.90 17.57
September 0.468881E+11 22615.40 20-SEP-18:10 31.05 16.15 0.153062E+11 10521.10 22-SEP-22:10 24.90 17.87
October 0.448065E+11 21917.29 05-OCT-18:10 27.15 16.93 0.154801E+11 10373.23 04-OCT-22:10 27.15 16.93
November 0.389784E+11 19951.85 09-NOV-22:20 18.17 10.78 0.145649E+11 10054.29 09-NOV-22:30 17.80 10.64
December 0.375444E+11 19120.60 15-DEC-23:00 13.90 4.56 0.148163E+11 9809.55 15-DEC-23:10 13.80 4.57
                     
Annual Sum or Average 0.528870E+12         0.183077E+12        
Minimum of Months 0.359952E+11 19070.69   12.07 4.56 0.135697E+11 9769.05   12.07 4.57
Maximum of Months 0.514189E+11 24499.85   36.28 18.94 0.161822E+11 10850.30   30.92 17.87



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.413369E+11 20251.88 03-JAN-22:10 12.43 6.06 0.149783E+11 9857.13 03-JAN-22:19 12.07 5.91
February 0.387138E+11 20815.43 07-FEB-23:00 15.60 8.35 0.136433E+11 10056.22 06-FEB-23:10 15.60 8.35
March 0.447170E+11 21290.66 22-MAR-18:10 20.22 7.33 0.153570E+11 10229.01 15-MAR-22:10 20.22 7.33
April 0.473129E+11 23417.60 19-APR-18:10 29.90 13.60 0.152086E+11 10572.79 19-APR-22:10 26.93 11.76
May 0.519392E+11 24608.28 31-MAY-18:10 30.92 15.25 0.160784E+11 10781.93 19-MAY-22:10 30.92 15.25
June 0.531142E+11 25884.23 15-JUN-18:10 35.92 14.47 0.159033E+11 10926.48 16-JUN-22:10 30.92 15.69
July 0.546406E+11 25630.03 03-JUL-18:10 36.28 18.94 0.162967E+11 10828.41 25-JUL-22:10 30.00 17.07
August 0.535582E+11 25318.51 07-AUG-18:10 33.95 18.47 0.162667E+11 10816.24 07-AUG-21:40 29.90 17.57
September 0.499603E+11 23921.91 20-SEP-18:10 31.05 16.15 0.154127E+11 10604.98 22-SEP-22:10 24.90 17.87
October 0.479125E+11 23218.87 05-OCT-18:10 27.15 16.93 0.155777E+11 10459.05 04-OCT-22:10 27.15 16.93
November 0.418798E+11 21178.26 09-NOV-22:10 18.53 10.92 0.146431E+11 10144.33 09-NOV-22:19 18.17 10.78
December 0.404819E+11 20297.43 15-DEC-23:00 13.90 4.56 0.148866E+11 9895.48 15-DEC-23:10 13.80 4.57
                     
Annual Sum or Average 0.565567E+12         0.184253E+12        
Minimum of Months 0.387138E+11 20251.88   12.43 4.56 0.136433E+11 9857.13   12.07 4.57
Maximum of Months 0.546406E+11 25884.23   36.28 18.94 0.162967E+11 10926.48   30.92 17.87



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.509864E+11 26380.58 01-JAN-11:50 14.13 8.64 0.186232E+11 11319.39 21-JAN-18:19 9.83 5.36
February 0.471125E+11 27731.00 20-FEB-11:50 20.73 8.30 0.168317E+11 11319.48 04-FEB-18:19 20.73 8.30
March 0.534071E+11 27865.57 19-MAR-10:50 19.03 7.15 0.186483E+11 11319.55 18-MAR-17:19 19.03 7.15
April 0.547888E+11 29809.53 30-APR-10:40 24.07 13.08 0.180644E+11 11319.65 15-APR-17:19 24.07 13.08
May 0.588731E+11 30087.43 21-MAY-10:50 30.03 14.61 0.186812E+11 11319.66 06-MAY-17:19 30.03 14.61
June 0.590953E+11 30779.39 18-JUN-10:50 32.62 16.28 0.180923E+11 11319.65 24-JUN-17:19 31.67 16.29
July 0.609821E+11 30956.25 02-JUL-10:40 32.23 20.13 0.186883E+11 11319.66 15-JUL-17:19 32.20 17.96
August 0.603074E+11 30809.68 06-AUG-10:40 31.67 18.03 0.186901E+11 11319.65 19-AUG-17:19 31.33 15.73
September 0.573197E+11 30236.51 17-SEP-10:40 29.47 15.71 0.180761E+11 11319.65 30-SEP-17:19 26.47 12.09
October 0.561406E+11 29612.84 05-OCT-10:50 27.70 18.68 0.186595E+11 11319.63 21-OCT-17:19 24.83 12.12
November 0.508316E+11 27587.58 10-NOV-11:50 21.02 12.06 0.180344E+11 11319.48 18-NOV-18:19 13.90 3.79
December 0.504082E+11 26419.78 10-DEC-11:50 16.32 7.64 0.186188E+11 11319.39 16-DEC-18:19 9.43 2.03
                     
Annual Sum or Average 0.660253E+12         0.219708E+12        
Minimum of Months 0.471125E+11 26380.58   14.13 7.15 0.168317E+11 11319.39   9.43 2.03
Maximum of Months 0.609821E+11 30956.25   32.62 20.13 0.186901E+11 11319.66   32.20 17.96



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.288691E+10 4769.52 12-JAN-14:30 18.60 9.87 0.126879E+10 745.75 26-JAN-05:30 1.40 -1.1
February 0.382025E+10 5042.60 22-FEB-13:00 20.60 7.49 0.114713E+10 745.80 24-FEB-05:10 5.40 0.22
March 0.546427E+10 5530.53 14-MAR-15:50 24.32 10.24 0.127478E+10 745.74 01-MAR-05:49 24.32 10.24
April 0.927115E+10 6616.80 30-APR-10:35 24.07 13.08 0.123278E+10 772.25 19-APR-22:10 24.07 13.08
May 0.124422E+11 7067.27 21-MAY-10:35 29.47 14.38 0.128380E+10 799.90 19-MAY-22:10 29.47 14.38
June 0.146214E+11 7698.13 17-JUN-17:13 36.10 16.68 0.128851E+10 832.68 16-JUN-22:10 36.10 16.68
July 0.150368E+11 7803.58 03-JUL-10:35 34.07 18.96 0.131954E+10 832.94 02-JUL-23:19 34.07 18.96
August 0.143496E+11 7618.31 07-AUG-17:13 35.93 18.20 0.131399E+10 836.10 07-AUG-21:49 29.45 17.70
September 0.126279E+11 7168.64 03-SEP-10:35 26.10 18.93 0.124843E+10 793.66 22-SEP-22:10 24.90 17.87
October 0.959752E+10 6950.49 05-OCT-10:35 27.60 18.63 0.127471E+10 776.67 01-OCT-23:19 27.60 18.63
November 0.486700E+10 5517.56 03-NOV-15:50 23.80 13.47 0.122746E+10 745.74 27-NOV-22:10 1.83 -0.3
December 0.229145E+10 3806.48 16-DEC-13:40 14.63 4.10 0.126875E+10 745.76 01-DEC-00:40 14.63 4.10
                     
Annual Sum or Average 0.107276E+12         0.151487E+11        
Minimum of Months 0.229145E+10 3806.48   14.63 4.10 0.114713E+10 745.74   1.40 -1.1
Maximum of Months 0.150368E+11 7803.58   36.10 18.96 0.131954E+10 836.10   36.10 18.96



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 6.70
February 0.00 0.00 01-FEB-00:03 6.42
March 0.00 0.00 01-MAR-00:03 7.32
April 0.00 0.00 01-APR-00:10 11.18
May 0.00 0.00 01-MAY-00:10 20.40
June 0.00 0.00 01-JUN-00:10 25.03
July 0.00 0.00 01-JUL-00:10 27.63
August 0.00 0.00 01-AUG-00:10 27.32
September 0.00 0.00 01-SEP-00:10 22.63
October 0.00 0.00 01-OCT-00:10 16.02
November 0.00 0.00 01-NOV-00:10 10.60
December 0.00 0.00 01-DEC-00:03 8.95
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   6.42
Maximum of Months 0.00 0.00   27.63



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.109949E+09 887.86 27-JAN-07:30 -4.2
February 78823572.08 909.12 03-FEB-07:10 -5.1
March 43243123.36 764.55 02-MAR-05:00 -3.9
April 410897.60 130.00 12-APR-06:10 3.87
May 0.00 0.00 01-MAY-00:10 20.40
June 0.00 0.00 01-JUN-00:10 25.03
July 0.00 0.00 01-JUL-00:10 27.63
August 0.00 0.00 01-AUG-00:10 27.32
September 0.00 0.00 01-SEP-00:10 22.63
October 0.00 0.00 01-OCT-00:10 16.02
November 43883777.54 723.12 28-NOV-05:00 -0.6
December 0.230933E+09 1056.41 27-DEC-07:30 -4.2
         
Annual Sum or Average 0.507243E+09      
Minimum of Months 0.00 0.00   -5.1
Maximum of Months 0.230933E+09 1056.41   27.63



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 6.70
February 0.00 0.00 01-FEB-00:03 6.42
March 0.00 0.00 01-MAR-00:03 7.32
April 0.00 0.00 01-APR-00:10 11.18
May 0.00 0.00 01-MAY-00:10 20.40
June 0.00 0.00 01-JUN-00:10 25.03
July 0.00 0.00 01-JUL-00:10 27.63
August 0.00 0.00 01-AUG-00:10 27.32
September 0.00 0.00 01-SEP-00:10 22.63
October 0.00 0.00 01-OCT-00:10 16.02
November 0.00 0.00 01-NOV-00:10 10.60
December 0.00 0.00 01-DEC-00:03 8.95
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   6.42
Maximum of Months 0.00 0.00   27.63



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 9041394.52 316.27 28-JAN-06:00 -3.3
February 7626893.52 292.36 03-FEB-05:00 -3.9
March 2288372.44 236.54 02-MAR-04:50 -3.7
April 0.00 0.00 01-APR-00:10 11.18
May 0.00 0.00 01-MAY-00:10 20.40
June 0.00 0.00 01-JUN-00:10 25.03
July 0.00 0.00 01-JUL-00:10 27.63
August 0.00 0.00 01-AUG-00:10 27.32
September 0.00 0.00 01-SEP-00:10 22.63
October 0.00 0.00 01-OCT-00:10 16.02
November 1845520.06 182.30 28-NOV-04:50 -0.6
December 33057533.53 341.56 27-DEC-05:00 -3.9
         
Annual Sum or Average 53859714.07      
Minimum of Months 0.00 0.00   -3.9
Maximum of Months 33057533.53 341.56   27.63



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 61964931.08 293.07 28-JAN-07:10 -2.9
February 42402309.65 276.72 03-FEB-07:10 -5.1
March 11546376.21 251.75 02-MAR-05:00 -3.9
April 0.00 0.00 01-APR-00:10 11.18
May 0.00 0.00 01-MAY-00:10 20.40
June 0.00 0.00 01-JUN-00:10 25.03
July 0.00 0.00 01-JUL-00:10 27.63
August 0.00 0.00 01-AUG-00:10 27.32
September 0.00 0.00 01-SEP-00:10 22.63
October 0.00 0.00 01-OCT-00:10 16.02
November 18870964.07 209.23 28-NOV-04:40 -0.6
December 0.130343E+09 292.99 27-DEC-05:00 -3.9
         
Annual Sum or Average 0.265127E+09      
Minimum of Months 0.00 0.00   -5.1
Maximum of Months 0.130343E+09 293.07   27.63



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 6.70
February 0.00 0.00 01-FEB-00:03 6.42
March 0.00 0.00 01-MAR-00:03 7.32
April 0.00 0.00 01-APR-00:10 11.18
May 0.00 0.00 01-MAY-00:10 20.40
June 0.00 0.00 01-JUN-00:10 25.03
July 0.00 0.00 01-JUL-00:10 27.63
August 0.00 0.00 01-AUG-00:10 27.32
September 0.00 0.00 01-SEP-00:10 22.63
October 0.00 0.00 01-OCT-00:10 16.02
November 0.00 0.00 01-NOV-00:10 10.60
December 0.00 0.00 01-DEC-00:03 8.95
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   6.42
Maximum of Months 0.00 0.00   27.63



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 6.70
February 0.00 0.00 01-FEB-00:03 6.42
March 0.00 0.00 01-MAR-00:03 7.32
April 0.00 0.00 01-APR-00:10 11.18
May 0.00 0.00 01-MAY-00:10 20.40
June 0.00 0.00 01-JUN-00:10 25.03
July 0.00 0.00 01-JUL-00:10 27.63
August 0.00 0.00 01-AUG-00:10 27.32
September 0.00 0.00 01-SEP-00:10 22.63
October 0.00 0.00 01-OCT-00:10 16.02
November 0.00 0.00 01-NOV-00:10 10.60
December 0.00 0.00 01-DEC-00:03 8.95
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   6.42
Maximum of Months 0.00 0.00   27.63



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 6.70
February 0.00 0.00 01-FEB-00:03 6.42
March 0.00 0.00 01-MAR-00:03 7.32
April 0.00 0.00 01-APR-00:10 11.18
May 0.00 0.00 01-MAY-00:10 20.40
June 0.00 0.00 01-JUN-00:10 25.03
July 0.00 0.00 01-JUL-00:10 27.63
August 0.00 0.00 01-AUG-00:10 27.32
September 0.00 0.00 01-SEP-00:10 22.63
October 0.00 0.00 01-OCT-00:10 16.02
November 0.00 0.00 01-NOV-00:10 10.60
December 0.00 0.00 01-DEC-00:03 8.95
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   6.42
Maximum of Months 0.00 0.00   27.63



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.372014E+09 1834.88 15-JAN-16:01 10.00
February 0.238582E+09 1760.62 13-FEB-16:02 12.30
March 0.134316E+09 1769.65 29-MAR-08:62 8.87
April 15805829.56 1704.16 11-APR-08:62 6.88
May 1103260.87 861.17 10-MAY-08:03 20.78
June 590973.94 456.99 25-JUN-08:04 22.67
July 836993.26 628.07 18-JUL-08:04 24.08
August 961951.66 632.87 12-AUG-08:04 22.57
September 931535.85 660.76 27-SEP-08:03 19.27
October 3262557.52 954.51 30-OCT-08:03 15.37
November 0.190436E+09 1837.69 28-NOV-16:01 11.52
December 0.504449E+09 1803.68 02-DEC-16:02 8.12
         
Annual Sum or Average 0.146329E+10      
Minimum of Months 590973.94 456.99   6.88
Maximum of Months 0.504449E+09 1837.69   24.08



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.609341E+09 1836.66 15-JAN-16:01 10.00
February 0.385902E+09 1806.27 04-FEB-09:01 7.25
March 0.201214E+09 1782.63 29-MAR-08:62 8.87
April 20993663.65 1706.50 11-APR-08:62 6.88
May 1038264.67 805.11 08-MAY-08:03 20.23
June 547324.30 424.04 23-JUN-08:04 21.97
July 776307.87 666.56 21-JUL-08:04 22.30
August 1087888.33 669.98 23-AUG-08:04 24.27
September 1169681.80 865.29 11-SEP-08:03 21.57
October 7878178.48 1079.32 25-OCT-08:62 11.15
November 0.308103E+09 1850.92 28-NOV-16:01 11.52
December 0.799465E+09 1826.37 13-DEC-09:01 9.40
         
Annual Sum or Average 0.233752E+10      
Minimum of Months 547324.30 424.04   6.88
Maximum of Months 0.799465E+09 1850.92   24.27



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 6.70
February 0.00 0.00 01-FEB-00:03 6.42
March 0.00 0.00 01-MAR-00:03 7.32
April 0.00 0.00 01-APR-00:10 11.18
May 0.00 0.00 01-MAY-00:10 20.40
June 0.00 0.00 01-JUN-00:10 25.03
July 0.00 0.00 01-JUL-00:10 27.63
August 0.00 0.00 01-AUG-00:10 27.32
September 0.00 0.00 01-SEP-00:10 22.63
October 0.00 0.00 01-OCT-00:10 16.02
November 0.00 0.00 01-NOV-00:10 10.60
December 158.21 0.26 27-DEC-06:00 -3.3
         
Annual Sum or Average 158.21      
Minimum of Months 0.00 0.00   -3.3
Maximum of Months 158.21 0.26   27.63



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 20620800.19 562.86 27-JAN-16:02 9.50
February 15412684.98 559.35 02-FEB-16:02 10.60
March 4292490.97 553.50 02-MAR-16:01 12.30
April 1313522.46 570.71 11-APR-15:03 16.78
May 368181.41 435.19 23-MAY-08:04 23.27
June 124752.00 312.83 23-JUN-08:04 21.97
July 55170.03 302.99 05-JUL-08:05 22.57
August 210156.17 449.70 24-AUG-08:04 21.60
September 402359.53 430.32 21-SEP-08:04 23.17
October 1151771.59 407.55 24-OCT-15:03 17.88
November 5531134.35 558.91 28-NOV-16:01 11.52
December 45383597.97 569.54 28-DEC-16:01 10.50
         
Annual Sum or Average 94866621.66      
Minimum of Months 55170.03 302.99   9.50
Maximum of Months 45383597.97 570.71   23.27



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.388024E+09 1763.03 15-JAN-16:01 10.00
February 0.223333E+09 1692.49 13-FEB-16:02 12.30
March 0.135824E+09 1658.66 24-MAR-08:62 6.05
April 15177785.98 705.99 20-APR-08:04 20.78
May 283197.87 567.54 23-MAY-08:04 23.27
June 71840.83 329.22 22-JUN-08:04 21.88
July 95548.58 601.59 07-JUL-08:04 23.80
August 338927.49 584.48 24-AUG-08:04 21.60
September 177162.37 522.55 22-SEP-08:04 23.12
October 6324389.23 889.98 15-OCT-18:03 18.72
November 0.205461E+09 1758.61 28-NOV-16:01 11.52
December 0.507900E+09 1724.51 02-DEC-16:02 8.12
         
Annual Sum or Average 0.148301E+10      
Minimum of Months 71840.83 329.22   6.05
Maximum of Months 0.507900E+09 1763.03   23.80



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.618835E+09 1764.71 15-JAN-16:01 10.00
February 0.345937E+09 1738.62 01-FEB-16:01 9.90
March 0.196390E+09 1724.68 02-MAR-16:01 12.30
April 20312461.23 1116.00 11-APR-15:03 16.78
May 371351.74 584.71 23-MAY-08:04 23.27
June 71858.18 332.75 22-JUN-08:04 21.88
July 103677.60 609.08 07-JUL-08:04 23.80
August 387822.54 652.62 17-AUG-18:04 25.50
September 412101.99 604.36 22-SEP-08:04 23.12
October 15222719.72 931.85 31-OCT-18:03 16.97
November 0.315941E+09 1771.41 28-NOV-16:01 11.52
December 0.786364E+09 1774.29 19-DEC-16:01 9.22
         
Annual Sum or Average 0.230035E+10      
Minimum of Months 71858.18 332.75   9.22
Maximum of Months 0.786364E+09 1774.29   25.50



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 1305670.51 222.73 27-JAN-07:30 -4.2
February 889388.26 206.56 02-FEB-07:10 -4.0
March 339432.62 104.14 02-MAR-09:08 0.47
April 0.00 0.00 01-APR-00:10 11.18
May 0.00 0.00 01-MAY-00:10 20.40
June 0.00 0.00 01-JUN-00:10 25.03
July 0.00 0.00 01-JUL-00:10 27.63
August 0.00 0.00 01-AUG-00:10 27.32
September 0.00 0.00 01-SEP-00:10 22.63
October 0.00 0.00 01-OCT-00:10 16.02
November 1632361.19 147.62 27-NOV-09:07 3.98
December 10059523.70 451.22 27-DEC-07:30 -4.2
         
Annual Sum or Average 14226376.28      
Minimum of Months 0.00 0.00   -4.2
Maximum of Months 10059523.70 451.22   27.63



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.657972E+09 2187.86 15-JAN-16:01 10.00
February 0.432493E+09 2103.37 13-FEB-16:02 12.30
March 0.266924E+09 2115.94 29-MAR-08:62 8.87
April 37599693.35 2097.14 12-APR-08:61 11.15
May 1076156.05 811.87 10-MAY-08:03 20.78
June 285618.66 321.41 25-JUN-08:04 22.67
July 447841.87 630.40 21-JUL-08:04 22.30
August 732829.66 646.93 30-AUG-08:03 21.47
September 976969.43 715.31 26-SEP-08:03 20.78
October 14095507.31 1021.35 28-OCT-08:03 13.68
November 0.350652E+09 2190.53 28-NOV-16:01 11.52
December 0.856455E+09 2158.30 02-DEC-16:02 8.12
         
Annual Sum or Average 0.261971E+10      
Minimum of Months 285618.66 321.41   8.12
Maximum of Months 0.856455E+09 2190.53   22.67



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.985178E+09 2185.17 15-JAN-16:01 10.00
February 0.638292E+09 2162.85 04-FEB-09:01 7.25
March 0.362838E+09 2130.69 29-MAR-08:62 8.87
April 45907394.94 2102.64 12-APR-08:61 11.15
May 1085330.04 824.32 10-MAY-08:03 20.78
June 229874.38 372.85 30-JUN-08:04 22.38
July 403380.42 668.13 21-JUL-08:04 22.30
August 815084.68 776.17 30-AUG-08:03 21.47
September 1485978.68 796.97 12-SEP-08:03 22.15
October 29190069.47 2056.06 25-OCT-08:62 11.15
November 0.530826E+09 2189.36 28-NOV-16:01 11.52
December 0.125169E+10 2178.64 13-DEC-09:01 9.40
         
Annual Sum or Average 0.384794E+10      
Minimum of Months 229874.38 372.85   7.25
Maximum of Months 0.125169E+10 2189.36   22.38



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.108530E+09 1131.30 15-JAN-16:01 10.00
February 72922663.11 997.65 02-FEB-09:02 1.38
March 50396396.88 1075.18 24-MAR-08:62 6.05
April 7223194.65 759.75 11-APR-08:62 6.88
May 815201.69 462.70 19-MAY-08:04 24.27
June 613680.94 426.22 27-JUN-08:04 23.58
July 658238.61 463.51 07-JUL-08:04 23.80
August 655625.51 434.94 02-AUG-08:04 24.18
September 518580.02 401.95 22-SEP-08:04 23.12
October 643224.79 434.49 15-OCT-08:04 13.90
November 60387807.52 1115.61 28-NOV-16:01 11.52
December 0.165579E+09 1092.42 02-DEC-16:02 8.12
         
Annual Sum or Average 0.468944E+09      
Minimum of Months 518580.02 401.95   1.38
Maximum of Months 0.165579E+09 1131.30   24.27



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 6.70
February 0.00 0.00 01-FEB-00:03 6.42
March 0.00 0.00 01-MAR-00:03 7.32
April 0.00 0.00 01-APR-00:10 11.18
May 0.00 0.00 01-MAY-00:10 20.40
June 0.00 0.00 01-JUN-00:10 25.03
July 0.00 0.00 01-JUL-00:10 27.63
August 0.00 0.00 01-AUG-00:10 27.32
September 0.00 0.00 01-SEP-00:10 22.63
October 0.00 0.00 01-OCT-00:10 16.02
November 0.00 0.00 01-NOV-00:10 10.60
December 0.00 0.00 01-DEC-00:03 8.95
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   6.42
Maximum of Months 0.00 0.00   27.63



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 6.70
February 0.00 0.00 01-FEB-00:03 6.42
March 0.00 0.00 01-MAR-00:03 7.32
April 0.00 0.00 01-APR-00:10 11.18
May 0.00 0.00 01-MAY-00:10 20.40
June 0.00 0.00 01-JUN-00:10 25.03
July 0.00 0.00 01-JUL-00:10 27.63
August 0.00 0.00 01-AUG-00:10 27.32
September 0.00 0.00 01-SEP-00:10 22.63
October 0.00 0.00 01-OCT-00:10 16.02
November 0.00 0.00 01-NOV-00:10 10.60
December 0.00 0.00 01-DEC-00:03 8.95
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   6.42
Maximum of Months 0.00 0.00   27.63



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 6.70
February 0.00 0.00 01-FEB-00:03 6.42
March 0.00 0.00 01-MAR-00:03 7.32
April 0.00 0.00 01-APR-00:10 11.18
May 0.00 0.00 01-MAY-00:10 20.40
June 0.00 0.00 01-JUN-00:10 25.03
July 0.00 0.00 01-JUL-00:10 27.63
August 0.00 0.00 01-AUG-00:10 27.32
September 0.00 0.00 01-SEP-00:10 22.63
October 0.00 0.00 01-OCT-00:10 16.02
November 0.00 0.00 01-NOV-00:10 10.60
December 0.00 0.00 01-DEC-00:03 8.95
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   6.42
Maximum of Months 0.00 0.00   27.63



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.387985E+09 2457.07 27-JAN-07:30 -4.2
February 0.265251E+09 2591.29 03-FEB-07:30 -4.2
March 0.128233E+09 2190.29 02-MAR-07:10 -1.6
April 1833503.41 502.23 12-APR-06:10 3.87
May 0.00 0.00 01-MAY-00:10 20.40
June 0.00 0.00 01-JUN-00:10 25.03
July 0.00 0.00 01-JUL-00:10 27.63
August 0.00 0.00 01-AUG-00:10 27.32
September 0.00 0.00 01-SEP-00:10 22.63
October 0.00 0.00 01-OCT-00:10 16.02
November 0.170181E+09 1663.81 28-NOV-06:10 1.02
December 0.804114E+09 2683.58 27-DEC-07:30 -4.2
         
Annual Sum or Average 0.175760E+10      
Minimum of Months 0.00 0.00   -4.2
Maximum of Months 0.804114E+09 2683.58   27.63



Table of Contents

Report: ZoneElectricSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.140333E+11 13517.00 02-JAN-20:10 0.127587E+11 10113.80 02-JAN-20:10
February 0.126708E+11 13517.00 01-FEB-20:10 0.115208E+11 10113.80 01-FEB-20:10
March 0.140766E+11 13517.00 01-MAR-20:10 0.127855E+11 10113.80 01-MAR-20:10
April 0.135575E+11 13517.00 03-APR-19:10 0.123314E+11 10113.80 03-APR-19:10
May 0.140576E+11 13517.00 01-MAY-19:10 0.127741E+11 10113.80 01-MAY-19:10
June 0.136197E+11 13517.00 01-JUN-19:10 0.123716E+11 10113.80 01-JUN-19:10
July 0.139955E+11 13517.00 03-JUL-19:10 0.127338E+11 10113.80 03-JUL-19:10
August 0.140820E+11 13517.00 01-AUG-19:10 0.127894E+11 10113.80 01-AUG-19:10
September 0.135629E+11 13517.00 01-SEP-19:10 0.123352E+11 10113.80 01-SEP-19:10
October 0.140279E+11 13517.00 02-OCT-19:10 0.127549E+11 10113.80 02-OCT-19:10
November 0.136089E+11 13517.00 01-NOV-19:10 0.123659E+11 10113.80 01-NOV-19:10
December 0.139955E+11 13517.00 01-DEC-20:10 0.127338E+11 10113.80 01-DEC-20:10
             
Annual Sum or Average 0.165288E+12     0.150255E+12    
Minimum of Months 0.126708E+11 13517.00   0.115208E+11 10113.80  
Maximum of Months 0.140820E+11 13517.00   0.127894E+11 10113.80  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.713551E+09 687.30 02-JAN-20:10 0.864900E+09 685.60 02-JAN-20:10
February 0.644271E+09 687.30 01-FEB-20:10 0.780982E+09 685.60 01-FEB-20:10
March 0.715750E+09 687.30 01-MAR-20:10 0.866718E+09 685.60 01-MAR-20:10
April 0.689358E+09 687.30 03-APR-19:10 0.835931E+09 685.60 03-APR-19:10
May 0.714788E+09 687.30 01-MAY-19:10 0.865939E+09 685.60 01-MAY-19:10
June 0.692519E+09 687.30 01-JUN-19:10 0.838659E+09 685.60 01-JUN-19:10
July 0.711626E+09 687.30 03-JUL-19:10 0.863211E+09 685.60 03-JUL-19:10
August 0.716025E+09 687.30 01-AUG-19:10 0.866978E+09 685.60 01-AUG-19:10
September 0.689633E+09 687.30 01-SEP-19:10 0.836191E+09 685.60 01-SEP-19:10
October 0.713276E+09 687.30 02-OCT-19:10 0.864640E+09 685.60 02-OCT-19:10
November 0.691970E+09 687.30 01-NOV-19:10 0.838269E+09 685.60 01-NOV-19:10
December 0.711626E+09 687.30 01-DEC-20:10 0.863211E+09 685.60 01-DEC-20:10
             
Annual Sum or Average 0.840439E+10     0.101856E+11    
Minimum of Months 0.644271E+09 687.30   0.780982E+09 685.60  
Maximum of Months 0.716025E+09 687.30   0.866978E+09 685.60  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.826294E+09 795.89 02-JAN-20:10 0.100156E+10 793.93 02-JAN-20:10
February 0.746069E+09 795.89 01-FEB-20:10 0.904380E+09 793.93 01-FEB-20:10
March 0.828841E+09 795.89 01-MAR-20:10 0.100366E+10 793.93 01-MAR-20:10
April 0.798279E+09 795.89 03-APR-19:10 0.968011E+09 793.93 03-APR-19:10
May 0.827727E+09 795.89 01-MAY-19:10 0.100276E+10 793.93 01-MAY-19:10
June 0.801940E+09 795.89 01-JUN-19:10 0.971170E+09 793.93 01-JUN-19:10
July 0.824066E+09 795.89 03-JUL-19:10 0.999601E+09 793.93 03-JUL-19:10
August 0.829160E+09 795.89 01-AUG-19:10 0.100396E+10 793.93 01-AUG-19:10
September 0.798597E+09 795.89 01-SEP-19:10 0.968312E+09 793.93 01-SEP-19:10
October 0.825976E+09 795.89 02-OCT-19:10 0.100126E+10 793.93 02-OCT-19:10
November 0.801303E+09 795.89 01-NOV-19:10 0.970719E+09 793.93 01-NOV-19:10
December 0.824066E+09 795.89 01-DEC-20:10 0.999601E+09 793.93 01-DEC-20:10
             
Annual Sum or Average 0.973232E+10     0.117950E+11    
Minimum of Months 0.746069E+09 795.89   0.904380E+09 793.93  
Maximum of Months 0.829160E+09 795.89   0.100396E+10 793.93  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.154452E+10 1487.69 02-JAN-20:10 0.105898E+10 839.45 02-JAN-20:10
February 0.139456E+10 1487.69 01-FEB-20:10 0.956227E+09 839.45 01-FEB-20:10
March 0.154928E+10 1487.69 01-MAR-20:10 0.106120E+10 839.45 01-MAR-20:10
April 0.149215E+10 1487.69 03-APR-19:10 0.102351E+10 839.45 03-APR-19:10
May 0.154719E+10 1487.69 01-MAY-19:10 0.106025E+10 839.45 01-MAY-19:10
June 0.149899E+10 1487.69 01-JUN-19:10 0.102685E+10 839.45 01-JUN-19:10
July 0.154035E+10 1487.69 03-JUL-19:10 0.105691E+10 839.45 03-JUL-19:10
August 0.154987E+10 1487.69 01-AUG-19:10 0.106152E+10 839.45 01-AUG-19:10
September 0.149274E+10 1487.69 01-SEP-19:10 0.102382E+10 839.45 01-SEP-19:10
October 0.154392E+10 1487.69 02-OCT-19:10 0.105866E+10 839.45 02-OCT-19:10
November 0.149780E+10 1487.69 01-NOV-19:10 0.102637E+10 839.45 01-NOV-19:10
December 0.154035E+10 1487.69 01-DEC-20:10 0.105691E+10 839.45 01-DEC-20:10
             
Annual Sum or Average 0.181917E+11     0.124712E+11    
Minimum of Months 0.139456E+10 1487.69   0.956227E+09 839.45  
Maximum of Months 0.154987E+10 1487.69   0.106152E+10 839.45  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.283535E+09 273.10 02-JAN-20:10 0.305485E+09 242.16 02-JAN-20:10
February 0.256006E+09 273.10 01-FEB-20:10 0.275845E+09 242.16 01-FEB-20:10
March 0.284409E+09 273.10 01-MAR-20:10 0.306128E+09 242.16 01-MAR-20:10
April 0.273921E+09 273.10 03-APR-19:10 0.295253E+09 242.16 03-APR-19:10
May 0.284026E+09 273.10 01-MAY-19:10 0.305852E+09 242.16 01-MAY-19:10
June 0.275178E+09 273.10 01-JUN-19:10 0.296217E+09 242.16 01-JUN-19:10
July 0.282770E+09 273.10 03-JUL-19:10 0.304889E+09 242.16 03-JUL-19:10
August 0.284518E+09 273.10 01-AUG-19:10 0.306219E+09 242.16 01-AUG-19:10
September 0.274031E+09 273.10 01-SEP-19:10 0.295345E+09 242.16 01-SEP-19:10
October 0.283425E+09 273.10 02-OCT-19:10 0.305393E+09 242.16 02-OCT-19:10
November 0.274959E+09 273.10 01-NOV-19:10 0.296079E+09 242.16 01-NOV-19:10
December 0.282770E+09 273.10 01-DEC-20:10 0.304889E+09 242.16 01-DEC-20:10
             
Annual Sum or Average 0.333955E+10     0.359760E+10    
Minimum of Months 0.256006E+09 273.10   0.275845E+09 242.16  
Maximum of Months 0.284518E+09 273.10   0.306219E+09 242.16  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.350256E+09 337.37 02-JAN-20:10 0.576866E+10 4572.80 02-JAN-20:10
February 0.316249E+09 337.37 01-FEB-20:10 0.520895E+10 4572.80 01-FEB-20:10
March 0.351336E+09 337.37 01-MAR-20:10 0.578079E+10 4572.80 01-MAR-20:10
April 0.338381E+09 337.37 03-APR-19:10 0.557545E+10 4572.80 03-APR-19:10
May 0.350863E+09 337.37 01-MAY-19:10 0.577559E+10 4572.80 01-MAY-19:10
June 0.339933E+09 337.37 01-JUN-19:10 0.559364E+10 4572.80 01-JUN-19:10
July 0.349311E+09 337.37 03-JUL-19:10 0.575740E+10 4572.80 03-JUL-19:10
August 0.351471E+09 337.37 01-AUG-19:10 0.578252E+10 4572.80 01-AUG-19:10
September 0.338516E+09 337.37 01-SEP-19:10 0.557718E+10 4572.80 01-SEP-19:10
October 0.350121E+09 337.37 02-OCT-19:10 0.576693E+10 4572.80 02-OCT-19:10
November 0.339663E+09 337.37 01-NOV-19:10 0.559104E+10 4572.80 01-NOV-19:10
December 0.349311E+09 337.37 01-DEC-20:10 0.575740E+10 4572.80 01-DEC-20:10
             
Annual Sum or Average 0.412541E+10     0.679355E+11    
Minimum of Months 0.316249E+09 337.37   0.520895E+10 4572.80  
Maximum of Months 0.351471E+09 337.37   0.578252E+10 4572.80  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.226040E+10 2177.23 02-JAN-20:10 0.121771E+10 965.27 02-JAN-20:10
February 0.204093E+10 2177.23 01-FEB-20:10 0.109956E+10 965.27 01-FEB-20:10
March 0.226736E+10 2177.23 01-MAR-20:10 0.122027E+10 965.27 01-MAR-20:10
April 0.218376E+10 2177.23 03-APR-19:10 0.117692E+10 965.27 03-APR-19:10
May 0.226431E+10 2177.23 01-MAY-19:10 0.121917E+10 965.27 01-MAY-19:10
June 0.219377E+10 2177.23 01-JUN-19:10 0.118076E+10 965.27 01-JUN-19:10
July 0.225430E+10 2177.23 03-JUL-19:10 0.121533E+10 965.27 03-JUL-19:10
August 0.226823E+10 2177.23 01-AUG-19:10 0.122063E+10 965.27 01-AUG-19:10
September 0.218463E+10 2177.23 01-SEP-19:10 0.117729E+10 965.27 01-SEP-19:10
October 0.225952E+10 2177.23 02-OCT-19:10 0.121734E+10 965.27 02-OCT-19:10
November 0.219203E+10 2177.23 01-NOV-19:10 0.118021E+10 965.27 01-NOV-19:10
December 0.225430E+10 2177.23 01-DEC-20:10 0.121533E+10 965.27 01-DEC-20:10
             
Annual Sum or Average 0.266236E+11     0.143405E+11    
Minimum of Months 0.204093E+10 2177.23   0.109956E+10 965.27  
Maximum of Months 0.226823E+10 2177.23   0.122063E+10 965.27  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.123020E+11 11849.32 02-JAN-20:10 0.126520E+11 10029.21 02-JAN-20:10
February 0.111075E+11 11849.32 01-FEB-20:10 0.114244E+11 10029.21 01-FEB-20:10
March 0.123399E+11 11849.32 01-MAR-20:10 0.126786E+11 10029.21 01-MAR-20:10
April 0.118849E+11 11849.32 03-APR-19:10 0.122282E+11 10029.21 03-APR-19:10
May 0.123233E+11 11849.32 01-MAY-19:10 0.126672E+11 10029.21 01-MAY-19:10
June 0.119394E+11 11849.32 01-JUN-19:10 0.122682E+11 10029.21 01-JUN-19:10
July 0.122688E+11 11849.32 03-JUL-19:10 0.126273E+11 10029.21 03-JUL-19:10
August 0.123446E+11 11849.32 01-AUG-19:10 0.126824E+11 10029.21 01-AUG-19:10
September 0.118896E+11 11849.32 01-SEP-19:10 0.122320E+11 10029.21 01-SEP-19:10
October 0.122972E+11 11849.32 02-OCT-19:10 0.126482E+11 10029.21 02-OCT-19:10
November 0.119299E+11 11849.32 01-NOV-19:10 0.122624E+11 10029.21 01-NOV-19:10
December 0.122688E+11 11849.32 01-DEC-20:10 0.126273E+11 10029.21 01-DEC-20:10
             
Annual Sum or Average 0.144896E+12     0.148998E+12    
Minimum of Months 0.111075E+11 11849.32   0.114244E+11 10029.21  
Maximum of Months 0.123446E+11 11849.32   0.126824E+11 10029.21  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.434056E+09 392.73 01-JAN-19:10 0.261068E+09 237.06 01-JAN-08:09
February 0.391995E+09 392.73 01-FEB-20:10 0.235798E+09 237.06 01-FEB-07:10
March 0.430607E+09 392.73 01-MAR-20:10 0.260708E+09 237.06 01-MAR-07:10
April 0.420554E+09 392.73 01-APR-18:10 0.252705E+09 237.06 01-APR-07:10
May 0.432331E+09 392.73 01-MAY-19:10 0.260888E+09 237.06 01-MAY-06:10
June 0.417218E+09 392.73 01-JUN-19:10 0.252344E+09 237.06 01-JUN-06:10
July 0.435725E+09 392.73 01-JUL-18:10 0.261248E+09 237.06 01-JUL-07:10
August 0.430607E+09 392.73 01-AUG-19:10 0.260708E+09 237.06 01-AUG-06:10
September 0.420667E+09 392.73 01-SEP-19:10 0.252705E+09 237.06 01-SEP-06:10
October 0.434000E+09 392.73 01-OCT-18:10 0.261068E+09 237.06 01-OCT-07:10
November 0.418886E+09 392.73 01-NOV-19:10 0.252524E+09 237.06 01-NOV-06:10
December 0.435781E+09 392.73 01-DEC-20:10 0.261248E+09 237.06 01-DEC-07:10
             
Annual Sum or Average 0.510243E+10     0.307301E+10    
Minimum of Months 0.391995E+09 392.73   0.235798E+09 237.06  
Maximum of Months 0.435781E+09 392.73   0.261248E+09 237.06  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.434005E+09 392.68 01-JAN-19:10 0.261038E+09 237.03 01-JAN-08:09
February 0.391949E+09 392.68 01-FEB-20:10 0.235770E+09 237.03 01-FEB-07:10
March 0.430556E+09 392.68 01-MAR-20:10 0.260677E+09 237.03 01-MAR-07:10
April 0.420505E+09 392.68 01-APR-18:10 0.252675E+09 237.03 01-APR-07:10
May 0.432281E+09 392.68 01-MAY-19:10 0.260857E+09 237.03 01-MAY-06:10
June 0.417169E+09 392.68 01-JUN-19:10 0.252315E+09 237.03 01-JUN-06:10
July 0.435674E+09 392.68 01-JUL-18:10 0.261218E+09 237.03 01-JUL-07:10
August 0.430556E+09 392.68 01-AUG-19:10 0.260677E+09 237.03 01-AUG-06:10
September 0.420618E+09 392.68 01-SEP-19:10 0.252675E+09 237.03 01-SEP-06:10
October 0.433949E+09 392.68 01-OCT-18:10 0.261038E+09 237.03 01-OCT-07:10
November 0.418837E+09 392.68 01-NOV-19:10 0.252495E+09 237.03 01-NOV-06:10
December 0.435730E+09 392.68 01-DEC-20:10 0.261218E+09 237.03 01-DEC-07:10
             
Annual Sum or Average 0.510183E+10     0.307265E+10    
Minimum of Months 0.391949E+09 392.68   0.235770E+09 237.03  
Maximum of Months 0.435730E+09 392.68   0.261218E+09 237.03  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.272788E+09 246.81 01-JAN-19:10 0.255708E+09 232.19 01-JAN-08:09
February 0.246354E+09 246.81 01-FEB-20:10 0.230956E+09 232.19 01-FEB-07:10
March 0.270620E+09 246.81 01-MAR-20:10 0.255355E+09 232.19 01-MAR-07:10
April 0.264302E+09 246.81 01-APR-18:10 0.247516E+09 232.19 01-APR-07:10
May 0.271704E+09 246.81 01-MAY-19:10 0.255532E+09 232.19 01-MAY-06:10
June 0.262205E+09 246.81 01-JUN-19:10 0.247163E+09 232.19 01-JUN-06:10
July 0.273836E+09 246.81 01-JUL-18:10 0.255885E+09 232.19 01-JUL-07:10
August 0.270620E+09 246.81 01-AUG-19:10 0.255355E+09 232.19 01-AUG-06:10
September 0.264373E+09 246.81 01-SEP-19:10 0.247516E+09 232.19 01-SEP-06:10
October 0.272752E+09 246.81 01-OCT-18:10 0.255708E+09 232.19 01-OCT-07:10
November 0.263254E+09 246.81 01-NOV-19:10 0.247340E+09 232.19 01-NOV-06:10
December 0.273872E+09 246.81 01-DEC-20:10 0.255885E+09 232.19 01-DEC-07:10
             
Annual Sum or Average 0.320668E+10     0.300992E+10    
Minimum of Months 0.246354E+09 246.81   0.230956E+09 232.19  
Maximum of Months 0.273872E+09 246.81   0.255885E+09 232.19  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.272862E+09 246.88 01-JAN-19:10 0.255778E+09 232.26 01-JAN-08:09
February 0.246421E+09 246.88 01-FEB-20:10 0.231020E+09 232.26 01-FEB-07:10
March 0.270694E+09 246.88 01-MAR-20:10 0.255425E+09 232.26 01-MAR-07:10
April 0.264375E+09 246.88 01-APR-18:10 0.247584E+09 232.26 01-APR-07:10
May 0.271778E+09 246.88 01-MAY-19:10 0.255602E+09 232.26 01-MAY-06:10
June 0.262277E+09 246.88 01-JUN-19:10 0.247231E+09 232.26 01-JUN-06:10
July 0.273911E+09 246.88 01-JUL-18:10 0.255955E+09 232.26 01-JUL-07:10
August 0.270694E+09 246.88 01-AUG-19:10 0.255425E+09 232.26 01-AUG-06:10
September 0.264446E+09 246.88 01-SEP-19:10 0.247584E+09 232.26 01-SEP-06:10
October 0.272827E+09 246.88 01-OCT-18:10 0.255778E+09 232.26 01-OCT-07:10
November 0.263326E+09 246.88 01-NOV-19:10 0.247408E+09 232.26 01-NOV-06:10
December 0.273947E+09 246.88 01-DEC-20:10 0.255955E+09 232.26 01-DEC-07:10
             
Annual Sum or Average 0.320756E+10     0.301074E+10    
Minimum of Months 0.246421E+09 246.88   0.231020E+09 232.26  
Maximum of Months 0.273947E+09 246.88   0.255955E+09 232.26  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.434056E+09 392.73 01-JAN-19:10 0.261068E+09 237.06 01-JAN-08:09
February 0.391995E+09 392.73 01-FEB-20:10 0.235798E+09 237.06 01-FEB-07:10
March 0.430607E+09 392.73 01-MAR-20:10 0.260708E+09 237.06 01-MAR-07:10
April 0.420554E+09 392.73 01-APR-18:10 0.252705E+09 237.06 01-APR-07:10
May 0.432331E+09 392.73 01-MAY-19:10 0.260888E+09 237.06 01-MAY-06:10
June 0.417218E+09 392.73 01-JUN-19:10 0.252344E+09 237.06 01-JUN-06:10
July 0.435725E+09 392.73 01-JUL-18:10 0.261248E+09 237.06 01-JUL-07:10
August 0.430607E+09 392.73 01-AUG-19:10 0.260708E+09 237.06 01-AUG-06:10
September 0.420667E+09 392.73 01-SEP-19:10 0.252705E+09 237.06 01-SEP-06:10
October 0.434000E+09 392.73 01-OCT-18:10 0.261068E+09 237.06 01-OCT-07:10
November 0.418886E+09 392.73 01-NOV-19:10 0.252524E+09 237.06 01-NOV-06:10
December 0.435781E+09 392.73 01-DEC-20:10 0.261248E+09 237.06 01-DEC-07:10
             
Annual Sum or Average 0.510243E+10     0.307301E+10    
Minimum of Months 0.391995E+09 392.73   0.235798E+09 237.06  
Maximum of Months 0.435781E+09 392.73   0.261248E+09 237.06  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.434005E+09 392.68 01-JAN-19:10 0.261038E+09 237.03 01-JAN-08:09
February 0.391949E+09 392.68 01-FEB-20:10 0.235770E+09 237.03 01-FEB-07:10
March 0.430556E+09 392.68 01-MAR-20:10 0.260677E+09 237.03 01-MAR-07:10
April 0.420505E+09 392.68 01-APR-18:10 0.252675E+09 237.03 01-APR-07:10
May 0.432281E+09 392.68 01-MAY-19:10 0.260857E+09 237.03 01-MAY-06:10
June 0.417169E+09 392.68 01-JUN-19:10 0.252315E+09 237.03 01-JUN-06:10
July 0.435674E+09 392.68 01-JUL-18:10 0.261218E+09 237.03 01-JUL-07:10
August 0.430556E+09 392.68 01-AUG-19:10 0.260677E+09 237.03 01-AUG-06:10
September 0.420618E+09 392.68 01-SEP-19:10 0.252675E+09 237.03 01-SEP-06:10
October 0.433949E+09 392.68 01-OCT-18:10 0.261038E+09 237.03 01-OCT-07:10
November 0.418837E+09 392.68 01-NOV-19:10 0.252495E+09 237.03 01-NOV-06:10
December 0.435730E+09 392.68 01-DEC-20:10 0.261218E+09 237.03 01-DEC-07:10
             
Annual Sum or Average 0.510183E+10     0.307265E+10    
Minimum of Months 0.391949E+09 392.68   0.235770E+09 237.03  
Maximum of Months 0.435730E+09 392.68   0.261218E+09 237.03  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY []
January 0.133160E+10 1282.60 02-JAN-20:10 0.00 0.00
February 0.120231E+10 1282.60 01-FEB-20:10 0.00 0.00
March 0.133570E+10 1282.60 01-MAR-20:10 0.00 0.00
April 0.128645E+10 1282.60 03-APR-19:10 0.00 0.00
May 0.133391E+10 1282.60 01-MAY-19:10 0.00 0.00
June 0.129235E+10 1282.60 01-JUN-19:10 0.00 0.00
July 0.132801E+10 1282.60 03-JUL-19:10 0.00 0.00
August 0.133622E+10 1282.60 01-AUG-19:10 0.00 0.00
September 0.128696E+10 1282.60 01-SEP-19:10 0.00 0.00
October 0.133109E+10 1282.60 02-OCT-19:10 0.00 0.00
November 0.129132E+10 1282.60 01-NOV-19:10 0.00 0.00
December 0.132801E+10 1282.60 01-DEC-20:10 0.00 0.00
           
Annual Sum or Average 0.156839E+11     0.00 0.00
Minimum of Months 0.120231E+10 1282.60   0.00 0.00
Maximum of Months 0.133622E+10 1282.60   0.00 0.00



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.434056E+09 392.73 01-JAN-19:10 0.261068E+09 237.06 01-JAN-08:09
February 0.391995E+09 392.73 01-FEB-20:10 0.235798E+09 237.06 01-FEB-07:10
March 0.430607E+09 392.73 01-MAR-20:10 0.260708E+09 237.06 01-MAR-07:10
April 0.420554E+09 392.73 01-APR-18:10 0.252705E+09 237.06 01-APR-07:10
May 0.432331E+09 392.73 01-MAY-19:10 0.260888E+09 237.06 01-MAY-06:10
June 0.417218E+09 392.73 01-JUN-19:10 0.252344E+09 237.06 01-JUN-06:10
July 0.435725E+09 392.73 01-JUL-18:10 0.261248E+09 237.06 01-JUL-07:10
August 0.430607E+09 392.73 01-AUG-19:10 0.260708E+09 237.06 01-AUG-06:10
September 0.420667E+09 392.73 01-SEP-19:10 0.252705E+09 237.06 01-SEP-06:10
October 0.434000E+09 392.73 01-OCT-18:10 0.261068E+09 237.06 01-OCT-07:10
November 0.418886E+09 392.73 01-NOV-19:10 0.252524E+09 237.06 01-NOV-06:10
December 0.435781E+09 392.73 01-DEC-20:10 0.261248E+09 237.06 01-DEC-07:10
             
Annual Sum or Average 0.510243E+10     0.307301E+10    
Minimum of Months 0.391995E+09 392.73   0.235798E+09 237.06  
Maximum of Months 0.435781E+09 392.73   0.261248E+09 237.06  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.434005E+09 392.68 01-JAN-19:10 0.261038E+09 237.03 01-JAN-08:09
February 0.391949E+09 392.68 01-FEB-20:10 0.235770E+09 237.03 01-FEB-07:10
March 0.430556E+09 392.68 01-MAR-20:10 0.260677E+09 237.03 01-MAR-07:10
April 0.420505E+09 392.68 01-APR-18:10 0.252675E+09 237.03 01-APR-07:10
May 0.432281E+09 392.68 01-MAY-19:10 0.260857E+09 237.03 01-MAY-06:10
June 0.417169E+09 392.68 01-JUN-19:10 0.252315E+09 237.03 01-JUN-06:10
July 0.435674E+09 392.68 01-JUL-18:10 0.261218E+09 237.03 01-JUL-07:10
August 0.430556E+09 392.68 01-AUG-19:10 0.260677E+09 237.03 01-AUG-06:10
September 0.420618E+09 392.68 01-SEP-19:10 0.252675E+09 237.03 01-SEP-06:10
October 0.433949E+09 392.68 01-OCT-18:10 0.261038E+09 237.03 01-OCT-07:10
November 0.418837E+09 392.68 01-NOV-19:10 0.252495E+09 237.03 01-NOV-06:10
December 0.435730E+09 392.68 01-DEC-20:10 0.261218E+09 237.03 01-DEC-07:10
             
Annual Sum or Average 0.510183E+10     0.307265E+10    
Minimum of Months 0.391949E+09 392.68   0.235770E+09 237.03  
Maximum of Months 0.435730E+09 392.68   0.261218E+09 237.03  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.272862E+09 246.88 01-JAN-19:10 0.255778E+09 232.26 01-JAN-08:09
February 0.246421E+09 246.88 01-FEB-20:10 0.231020E+09 232.26 01-FEB-07:10
March 0.270694E+09 246.88 01-MAR-20:10 0.255425E+09 232.26 01-MAR-07:10
April 0.264375E+09 246.88 01-APR-18:10 0.247584E+09 232.26 01-APR-07:10
May 0.271778E+09 246.88 01-MAY-19:10 0.255602E+09 232.26 01-MAY-06:10
June 0.262277E+09 246.88 01-JUN-19:10 0.247231E+09 232.26 01-JUN-06:10
July 0.273911E+09 246.88 01-JUL-18:10 0.255955E+09 232.26 01-JUL-07:10
August 0.270694E+09 246.88 01-AUG-19:10 0.255425E+09 232.26 01-AUG-06:10
September 0.264446E+09 246.88 01-SEP-19:10 0.247584E+09 232.26 01-SEP-06:10
October 0.272827E+09 246.88 01-OCT-18:10 0.255778E+09 232.26 01-OCT-07:10
November 0.263326E+09 246.88 01-NOV-19:10 0.247408E+09 232.26 01-NOV-06:10
December 0.273947E+09 246.88 01-DEC-20:10 0.255955E+09 232.26 01-DEC-07:10
             
Annual Sum or Average 0.320756E+10     0.301074E+10    
Minimum of Months 0.246421E+09 246.88   0.231020E+09 232.26  
Maximum of Months 0.273947E+09 246.88   0.255955E+09 232.26  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.396945E+10 3823.39 02-JAN-20:10 0.149358E+11 6747.90 01-JAN-07:10
February 0.358405E+10 3823.39 01-FEB-20:10 0.134904E+11 6747.90 01-FEB-07:10
March 0.398168E+10 3823.39 01-MAR-20:10 0.149358E+11 6747.90 01-MAR-07:10
April 0.383486E+10 3823.39 03-APR-19:10 0.144540E+11 6747.90 01-APR-06:10
May 0.397633E+10 3823.39 01-MAY-19:10 0.149358E+11 6747.90 01-MAY-06:10
June 0.385245E+10 3823.39 01-JUN-19:10 0.144540E+11 6747.90 01-JUN-06:10
July 0.395874E+10 3823.39 03-JUL-19:10 0.149358E+11 6747.90 01-JUL-06:10
August 0.398321E+10 3823.39 01-AUG-19:10 0.149358E+11 6747.90 01-AUG-06:10
September 0.383639E+10 3823.39 01-SEP-19:10 0.144540E+11 6747.90 01-SEP-06:10
October 0.396792E+10 3823.39 02-OCT-19:10 0.149358E+11 6747.90 01-OCT-06:10
November 0.384939E+10 3823.39 01-NOV-19:10 0.144540E+11 6747.90 01-NOV-06:10
December 0.395874E+10 3823.39 01-DEC-20:10 0.149358E+11 6747.90 01-DEC-07:10
             
Annual Sum or Average 0.467532E+11     0.175857E+12    
Minimum of Months 0.358405E+10 3823.39   0.134904E+11 6747.90  
Maximum of Months 0.398321E+10 3823.39   0.149358E+11 6747.90  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.396945E+10 3823.39 02-JAN-20:10 0.149358E+11 6747.90 01-JAN-07:10
February 0.358405E+10 3823.39 01-FEB-20:10 0.134904E+11 6747.90 01-FEB-07:10
March 0.398168E+10 3823.39 01-MAR-20:10 0.149358E+11 6747.90 01-MAR-07:10
April 0.383486E+10 3823.39 03-APR-19:10 0.144540E+11 6747.90 01-APR-06:10
May 0.397633E+10 3823.39 01-MAY-19:10 0.149358E+11 6747.90 01-MAY-06:10
June 0.385245E+10 3823.39 01-JUN-19:10 0.144540E+11 6747.90 01-JUN-06:10
July 0.395874E+10 3823.39 03-JUL-19:10 0.149358E+11 6747.90 01-JUL-06:10
August 0.398321E+10 3823.39 01-AUG-19:10 0.149358E+11 6747.90 01-AUG-06:10
September 0.383639E+10 3823.39 01-SEP-19:10 0.144540E+11 6747.90 01-SEP-06:10
October 0.396792E+10 3823.39 02-OCT-19:10 0.149358E+11 6747.90 01-OCT-06:10
November 0.384939E+10 3823.39 01-NOV-19:10 0.144540E+11 6747.90 01-NOV-06:10
December 0.395874E+10 3823.39 01-DEC-20:10 0.149358E+11 6747.90 01-DEC-07:10
             
Annual Sum or Average 0.467532E+11     0.175857E+12    
Minimum of Months 0.358405E+10 3823.39   0.134904E+11 6747.90  
Maximum of Months 0.398321E+10 3823.39   0.149358E+11 6747.90  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.105977E+10 1020.78 02-JAN-20:10 0.373720E+11 16686.59 01-JAN-07:10
February 0.956878E+09 1020.78 01-FEB-20:10 0.337554E+11 16686.59 01-FEB-07:10
March 0.106304E+10 1020.78 01-MAR-20:10 0.373720E+11 16686.59 01-MAR-07:10
April 0.102384E+10 1020.78 03-APR-19:10 0.361665E+11 16686.59 01-APR-06:10
May 0.106161E+10 1020.78 01-MAY-19:10 0.373720E+11 16686.59 01-MAY-06:10
June 0.102854E+10 1020.78 01-JUN-19:10 0.361665E+11 16686.59 01-JUN-06:10
July 0.105691E+10 1020.78 03-JUL-19:10 0.373720E+11 16686.59 01-JUL-06:10
August 0.106345E+10 1020.78 01-AUG-19:10 0.373720E+11 16686.59 01-AUG-06:10
September 0.102425E+10 1020.78 01-SEP-19:10 0.361665E+11 16686.59 01-SEP-06:10
October 0.105936E+10 1020.78 02-OCT-19:10 0.373720E+11 16686.59 01-OCT-06:10
November 0.102772E+10 1020.78 01-NOV-19:10 0.361665E+11 16686.59 01-NOV-06:10
December 0.105691E+10 1020.78 01-DEC-20:10 0.373720E+11 16686.59 01-DEC-07:10
             
Annual Sum or Average 0.124823E+11     0.440025E+12    
Minimum of Months 0.956878E+09 1020.78   0.337554E+11 16686.59  
Maximum of Months 0.106345E+10 1020.78   0.373720E+11 16686.59  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY []
January 0.140929E+10 1357.44 02-JAN-20:10 0.00 0.00
February 0.127246E+10 1357.44 01-FEB-20:10 0.00 0.00
March 0.141364E+10 1357.44 01-MAR-20:10 0.00 0.00
April 0.136151E+10 1357.44 03-APR-19:10 0.00 0.00
May 0.141173E+10 1357.44 01-MAY-19:10 0.00 0.00
June 0.136775E+10 1357.44 01-JUN-19:10 0.00 0.00
July 0.140549E+10 1357.44 03-JUL-19:10 0.00 0.00
August 0.141418E+10 1357.44 01-AUG-19:10 0.00 0.00
September 0.136205E+10 1357.44 01-SEP-19:10 0.00 0.00
October 0.140875E+10 1357.44 02-OCT-19:10 0.00 0.00
November 0.136667E+10 1357.44 01-NOV-19:10 0.00 0.00
December 0.140549E+10 1357.44 01-DEC-20:10 0.00 0.00
           
Annual Sum or Average 0.165990E+11     0.00 0.00
Minimum of Months 0.127246E+10 1357.44   0.00 0.00
Maximum of Months 0.141418E+10 1357.44   0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.195762E+11 0.140333E+11 0.127587E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.176991E+11 0.126708E+11 0.115208E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.196682E+11 0.140766E+11 0.127855E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.189781E+11 0.135575E+11 0.123314E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.196176E+11 0.140576E+11 0.127741E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.190195E+11 0.136197E+11 0.123716E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.195762E+11 0.139955E+11 0.127338E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.196590E+11 0.140820E+11 0.127894E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.189689E+11 0.135629E+11 0.123352E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.195854E+11 0.140279E+11 0.127549E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.189367E+11 0.136089E+11 0.123659E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.195762E+11 0.139955E+11 0.127338E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.230861E+12 0.165288E+12 0.150255E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.176991E+11 0.126708E+11 0.115208E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.196682E+11 0.140820E+11 0.127894E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.199054E+10 0.713551E+09 0.864900E+09 0.00 0.00 0.00 0.00 0.00 0.676322E+09
February 0.179968E+10 0.644271E+09 0.780982E+09 0.00 0.00 0.00 0.00 925812.25 0.510842E+09
March 0.199990E+10 0.715750E+09 0.866718E+09 0.00 0.00 0.00 0.00 5776564.93 0.446511E+09
April 0.192973E+10 0.689358E+09 0.835931E+09 0.00 0.00 0.00 0.00 80533318.49 0.174918E+09
May 0.199475E+10 0.714788E+09 0.865939E+09 0.00 0.00 0.00 0.00 0.187954E+09 54598748.50
June 0.193394E+10 0.692519E+09 0.838659E+09 0.00 0.00 0.00 0.00 0.320220E+09 8398096.28
July 0.199054E+10 0.711626E+09 0.863211E+09 0.00 0.00 0.00 0.00 0.312766E+09 2329491.67
August 0.199896E+10 0.716025E+09 0.866978E+09 0.00 0.00 0.00 0.00 0.258924E+09 12205082.74
September 0.192879E+10 0.689633E+09 0.836191E+09 0.00 0.00 0.00 0.00 0.151987E+09 56128756.09
October 0.199148E+10 0.713276E+09 0.864640E+09 0.00 0.00 0.00 0.00 43940146.17 0.198406E+09
November 0.192552E+10 0.691970E+09 0.838269E+09 0.00 0.00 0.00 0.00 856605.89 0.506288E+09
December 0.199054E+10 0.711626E+09 0.863211E+09 0.00 0.00 0.00 0.00 0.00 0.751760E+09
                   
Annual Sum or Average 0.234744E+11 0.840439E+10 0.101856E+11 0.00 0.00 0.00 0.00 0.136388E+10 0.339871E+10
Minimum of Months 0.179968E+10 0.644271E+09 0.780982E+09 0.00 0.00 0.00 0.00 0.00 2329491.67
Maximum of Months 0.199990E+10 0.716025E+09 0.866978E+09 0.00 0.00 0.00 0.00 0.320220E+09 0.751760E+09



Table of Contents

Report: SpaceGainsMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.230505E+10 0.826294E+09 0.100156E+10 0.00 0.00 0.00 0.00 0.00 0.259622E+09
February 0.208403E+10 0.746069E+09 0.904380E+09 0.00 0.00 0.00 0.00 757922.16 0.196163E+09
March 0.231589E+10 0.828841E+09 0.100366E+10 0.00 0.00 0.00 0.00 2662628.53 0.172610E+09
April 0.223463E+10 0.798279E+09 0.968011E+09 0.00 0.00 0.00 0.00 31130899.29 68424718.20
May 0.230993E+10 0.827727E+09 0.100276E+10 0.00 0.00 0.00 0.00 70813171.13 21838428.85
June 0.223950E+10 0.801940E+09 0.971170E+09 0.00 0.00 0.00 0.00 0.121229E+09 3539559.89
July 0.230505E+10 0.824066E+09 0.999601E+09 0.00 0.00 0.00 0.00 0.118460E+09 1105184.86
August 0.231480E+10 0.829160E+09 0.100396E+10 0.00 0.00 0.00 0.00 98948530.83 5020139.45
September 0.223354E+10 0.798597E+09 0.968312E+09 0.00 0.00 0.00 0.00 61505644.19 22880568.97
October 0.230614E+10 0.825976E+09 0.100126E+10 0.00 0.00 0.00 0.00 20778271.90 77061205.15
November 0.222975E+10 0.801303E+09 0.970719E+09 0.00 0.00 0.00 0.00 764372.58 0.192625E+09
December 0.230505E+10 0.824066E+09 0.999601E+09 0.00 0.00 0.00 0.00 0.00 0.289058E+09
                   
Annual Sum or Average 0.271834E+11 0.973232E+10 0.117950E+11 0.00 0.00 0.00 0.00 0.527050E+09 0.130995E+10
Minimum of Months 0.208403E+10 0.746069E+09 0.904380E+09 0.00 0.00 0.00 0.00 0.00 1105184.86
Maximum of Months 0.231589E+10 0.829160E+09 0.100396E+10 0.00 0.00 0.00 0.00 0.121229E+09 0.289058E+09



Table of Contents

Report: SpaceGainsMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.487480E+09 0.154452E+10 0.105898E+10 0.00 0.00 0.00 0.00 0.00 0.613000E+09
February 0.440737E+09 0.139456E+10 0.956227E+09 0.00 0.00 0.00 0.00 1791553.99 0.462790E+09
March 0.489771E+09 0.154928E+10 0.106120E+10 0.00 0.00 0.00 0.00 6308762.60 0.406132E+09
April 0.472586E+09 0.149215E+10 0.102351E+10 0.00 0.00 0.00 0.00 75099786.17 0.159652E+09
May 0.488511E+09 0.154719E+10 0.106025E+10 0.00 0.00 0.00 0.00 0.170638E+09 49990819.41
June 0.473617E+09 0.149899E+10 0.102685E+10 0.00 0.00 0.00 0.00 0.290809E+09 7721008.84
July 0.487480E+09 0.154035E+10 0.105691E+10 0.00 0.00 0.00 0.00 0.284542E+09 2248780.98
August 0.489542E+09 0.154987E+10 0.106152E+10 0.00 0.00 0.00 0.00 0.239162E+09 11177131.70
September 0.472357E+09 0.149274E+10 0.102382E+10 0.00 0.00 0.00 0.00 0.148779E+09 51407920.61
October 0.487709E+09 0.154392E+10 0.105866E+10 0.00 0.00 0.00 0.00 49987164.44 0.178872E+09
November 0.471555E+09 0.149780E+10 0.102637E+10 0.00 0.00 0.00 0.00 1806815.80 0.453686E+09
December 0.487480E+09 0.154035E+10 0.105691E+10 0.00 0.00 0.00 0.00 0.00 0.682851E+09
                   
Annual Sum or Average 0.574883E+10 0.181917E+11 0.124712E+11 0.00 0.00 0.00 0.00 0.126893E+10 0.307953E+10
Minimum of Months 0.440737E+09 0.139456E+10 0.956227E+09 0.00 0.00 0.00 0.00 0.00 2248780.98
Maximum of Months 0.489771E+09 0.154987E+10 0.106152E+10 0.00 0.00 0.00 0.00 0.290809E+09 0.682851E+09



Table of Contents

Report: SpaceGainsMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.374985E+09 0.283535E+09 0.305485E+09 0.00 0.00 0.00 0.00 0.00 0.353668E+09
February 0.339028E+09 0.256006E+09 0.275845E+09 0.00 0.00 0.00 0.00 1033682.38 0.267005E+09
March 0.376747E+09 0.284409E+09 0.306128E+09 0.00 0.00 0.00 0.00 3639527.29 0.234313E+09
April 0.363528E+09 0.273921E+09 0.295253E+09 0.00 0.00 0.00 0.00 43625523.35 92044161.82
May 0.375778E+09 0.284026E+09 0.305852E+09 0.00 0.00 0.00 0.00 99485102.33 28735893.13
June 0.364321E+09 0.275178E+09 0.296217E+09 0.00 0.00 0.00 0.00 0.169541E+09 4423125.79
July 0.374985E+09 0.282770E+09 0.304889E+09 0.00 0.00 0.00 0.00 0.165893E+09 1239335.84
August 0.376571E+09 0.284518E+09 0.306219E+09 0.00 0.00 0.00 0.00 0.139474E+09 6420844.09
September 0.363352E+09 0.274031E+09 0.295345E+09 0.00 0.00 0.00 0.00 86651025.79 29493092.65
October 0.375161E+09 0.283425E+09 0.305393E+09 0.00 0.00 0.00 0.00 29011944.07 0.103096E+09
November 0.362735E+09 0.274959E+09 0.296079E+09 0.00 0.00 0.00 0.00 1042468.51 0.261747E+09
December 0.374985E+09 0.282770E+09 0.304889E+09 0.00 0.00 0.00 0.00 0.00 0.393969E+09
                   
Annual Sum or Average 0.442217E+10 0.333955E+10 0.359760E+10 0.00 0.00 0.00 0.00 0.739397E+09 0.177615E+10
Minimum of Months 0.339028E+09 0.256006E+09 0.275845E+09 0.00 0.00 0.00 0.00 0.00 1239335.84
Maximum of Months 0.376747E+09 0.284518E+09 0.306219E+09 0.00 0.00 0.00 0.00 0.169541E+09 0.393969E+09



Table of Contents

Report: SpaceGainsMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.154405E+10 0.350256E+09 0.576866E+10 0.501157E+11 0.00 0.00 0.00 0.00 0.864294E+09
February 0.139600E+10 0.316249E+09 0.520895E+10 0.452532E+11 0.00 0.00 0.00 2443059.54 0.656389E+09
March 0.155131E+10 0.351336E+09 0.578079E+10 0.502211E+11 0.00 0.00 0.00 8376298.50 0.581222E+09
April 0.149688E+10 0.338381E+09 0.557545E+10 0.484372E+11 0.00 0.00 0.00 92699347.45 0.230920E+09
May 0.154732E+10 0.350863E+09 0.577559E+10 0.501759E+11 0.00 0.00 0.00 0.217527E+09 72639823.35
June 0.150015E+10 0.339933E+09 0.559364E+10 0.485952E+11 0.00 0.00 0.00 0.384955E+09 11001004.02
July 0.154405E+10 0.349311E+09 0.575740E+10 0.500179E+11 0.00 0.00 0.00 0.376041E+09 3846046.83
August 0.155059E+10 0.351471E+09 0.578252E+10 0.502361E+11 0.00 0.00 0.00 0.311947E+09 17836158.36
September 0.149615E+10 0.338516E+09 0.557718E+10 0.484522E+11 0.00 0.00 0.00 0.190265E+09 77009283.53
October 0.154478E+10 0.350121E+09 0.576693E+10 0.501006E+11 0.00 0.00 0.00 64125733.20 0.264287E+09
November 0.149361E+10 0.339663E+09 0.559104E+10 0.485726E+11 0.00 0.00 0.00 2439865.78 0.645630E+09
December 0.154405E+10 0.349311E+09 0.575740E+10 0.500179E+11 0.00 0.00 0.00 0.00 0.959736E+09
                   
Annual Sum or Average 0.182090E+11 0.412541E+10 0.679355E+11 0.590196E+12 0.00 0.00 0.00 0.165082E+10 0.438481E+10
Minimum of Months 0.139600E+10 0.316249E+09 0.520895E+10 0.452532E+11 0.00 0.00 0.00 0.00 3846046.83
Maximum of Months 0.155131E+10 0.351471E+09 0.578252E+10 0.502361E+11 0.00 0.00 0.00 0.384955E+09 0.959736E+09



Table of Contents

Report: SpaceGainsMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.261570E+11 0.226040E+10 0.121771E+10 0.00 0.00 0.00 0.00 0.00 0.149468E+10
February 0.236489E+11 0.204093E+10 0.109956E+10 0.00 0.00 0.00 0.00 2768250.28 0.113001E+10
March 0.262800E+11 0.226736E+10 0.122027E+10 0.00 0.00 0.00 0.00 13772942.01 0.990308E+09
April 0.253579E+11 0.218376E+10 0.117692E+10 0.00 0.00 0.00 0.00 0.175916E+09 0.395818E+09
May 0.262123E+11 0.226431E+10 0.121917E+10 0.00 0.00 0.00 0.00 0.402778E+09 0.128973E+09
June 0.254132E+11 0.219377E+10 0.118076E+10 0.00 0.00 0.00 0.00 0.685292E+09 21914976.38
July 0.261570E+11 0.225430E+10 0.121533E+10 0.00 0.00 0.00 0.00 0.667679E+09 8480608.66
August 0.262677E+11 0.226823E+10 0.122063E+10 0.00 0.00 0.00 0.00 0.553714E+09 32737818.67
September 0.253456E+11 0.218463E+10 0.117729E+10 0.00 0.00 0.00 0.00 0.335806E+09 0.138265E+09
October 0.261693E+11 0.225952E+10 0.121734E+10 0.00 0.00 0.00 0.00 0.101069E+09 0.452157E+09
November 0.253025E+11 0.219203E+10 0.118021E+10 0.00 0.00 0.00 0.00 2447086.60 0.112024E+10
December 0.261570E+11 0.225430E+10 0.121533E+10 0.00 0.00 0.00 0.00 0.00 0.166155E+10
                   
Annual Sum or Average 0.308468E+12 0.266236E+11 0.143405E+11 0.00 0.00 0.00 0.00 0.294124E+10 0.757513E+10
Minimum of Months 0.236489E+11 0.204093E+10 0.109956E+10 0.00 0.00 0.00 0.00 0.00 8480608.66
Maximum of Months 0.262800E+11 0.226823E+10 0.122063E+10 0.00 0.00 0.00 0.00 0.685292E+09 0.166155E+10



Table of Contents

Report: SpaceGainsMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.776503E+11 0.123020E+11 0.126520E+11 0.00 0.00 0.00 0.00 0.00 0.426479E+10
February 0.702046E+11 0.111075E+11 0.114244E+11 0.00 0.00 0.00 0.00 12395668.02 0.322851E+10
March 0.780153E+11 0.123399E+11 0.126786E+11 0.00 0.00 0.00 0.00 43450353.63 0.284955E+10
April 0.752779E+11 0.118849E+11 0.122282E+11 0.00 0.00 0.00 0.00 0.503252E+09 0.115278E+10
May 0.778146E+11 0.123233E+11 0.126672E+11 0.00 0.00 0.00 0.00 0.113847E+10 0.387000E+09
June 0.754422E+11 0.119394E+11 0.122682E+11 0.00 0.00 0.00 0.00 0.194515E+10 70232721.01
July 0.776503E+11 0.122688E+11 0.126273E+11 0.00 0.00 0.00 0.00 0.189190E+10 27461293.41
August 0.779788E+11 0.123446E+11 0.126824E+11 0.00 0.00 0.00 0.00 0.158124E+10 0.100682E+09
September 0.752414E+11 0.118896E+11 0.122320E+11 0.00 0.00 0.00 0.00 0.991811E+09 0.409557E+09
October 0.776868E+11 0.122972E+11 0.126482E+11 0.00 0.00 0.00 0.00 0.333870E+09 0.130160E+10
November 0.751137E+11 0.119299E+11 0.122624E+11 0.00 0.00 0.00 0.00 12469033.76 0.317698E+10
December 0.776503E+11 0.122688E+11 0.126273E+11 0.00 0.00 0.00 0.00 0.00 0.474335E+10
                   
Annual Sum or Average 0.915726E+12 0.144896E+12 0.148998E+12 0.00 0.00 0.00 0.00 0.845402E+10 0.217125E+11
Minimum of Months 0.702046E+11 0.111075E+11 0.114244E+11 0.00 0.00 0.00 0.00 0.00 27461293.41
Maximum of Months 0.780153E+11 0.123446E+11 0.126824E+11 0.00 0.00 0.00 0.00 0.194515E+10 0.474335E+10



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.434056E+09 0.261068E+09 0.00 0.00 0.00 0.00 0.00 0.398306E+09
February 0.273974E+09 0.391995E+09 0.235798E+09 0.00 0.00 0.00 0.00 264122.38 0.303786E+09
March 0.303685E+09 0.430607E+09 0.260708E+09 0.00 0.00 0.00 0.00 1539162.34 0.269842E+09
April 0.293479E+09 0.420554E+09 0.252705E+09 0.00 0.00 0.00 0.00 36521020.31 0.108077E+09
May 0.303504E+09 0.432331E+09 0.260888E+09 0.00 0.00 0.00 0.00 92398096.72 34642764.83
June 0.293842E+09 0.417218E+09 0.252344E+09 0.00 0.00 0.00 0.00 0.169060E+09 5642296.53
July 0.303141E+09 0.435725E+09 0.261248E+09 0.00 0.00 0.00 0.00 0.163369E+09 1780158.62
August 0.303685E+09 0.430607E+09 0.260708E+09 0.00 0.00 0.00 0.00 0.135127E+09 8778245.71
September 0.293479E+09 0.420667E+09 0.252705E+09 0.00 0.00 0.00 0.00 77982880.00 35382264.97
October 0.303322E+09 0.434000E+09 0.261068E+09 0.00 0.00 0.00 0.00 22415339.23 0.123259E+09
November 0.293661E+09 0.418886E+09 0.252524E+09 0.00 0.00 0.00 0.00 343130.97 0.300999E+09
December 0.303141E+09 0.435781E+09 0.261248E+09 0.00 0.00 0.00 0.00 0.00 0.441400E+09
                   
Annual Sum or Average 0.357224E+10 0.510243E+10 0.307301E+10 0.00 0.00 0.00 0.00 0.699020E+09 0.203190E+10
Minimum of Months 0.273974E+09 0.391995E+09 0.235798E+09 0.00 0.00 0.00 0.00 0.00 1780158.62
Maximum of Months 0.303685E+09 0.435781E+09 0.261248E+09 0.00 0.00 0.00 0.00 0.169060E+09 0.441400E+09



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.434005E+09 0.261038E+09 0.00 0.00 0.00 0.00 0.00 0.387777E+09
February 0.273974E+09 0.391949E+09 0.235770E+09 0.00 0.00 0.00 0.00 291984.44 0.295999E+09
March 0.303685E+09 0.430556E+09 0.260677E+09 0.00 0.00 0.00 0.00 1753161.86 0.264387E+09
April 0.293479E+09 0.420505E+09 0.252675E+09 0.00 0.00 0.00 0.00 37078055.55 0.106920E+09
May 0.303504E+09 0.432281E+09 0.260857E+09 0.00 0.00 0.00 0.00 92524344.28 34505418.70
June 0.293842E+09 0.417169E+09 0.252315E+09 0.00 0.00 0.00 0.00 0.169006E+09 5665906.39
July 0.303141E+09 0.435674E+09 0.261218E+09 0.00 0.00 0.00 0.00 0.163335E+09 1790942.10
August 0.303685E+09 0.430556E+09 0.260677E+09 0.00 0.00 0.00 0.00 0.135262E+09 8708972.27
September 0.293479E+09 0.420618E+09 0.252675E+09 0.00 0.00 0.00 0.00 78487249.06 35110092.65
October 0.303322E+09 0.433949E+09 0.261038E+09 0.00 0.00 0.00 0.00 23054741.83 0.120316E+09
November 0.293661E+09 0.418837E+09 0.252495E+09 0.00 0.00 0.00 0.00 356227.59 0.293460E+09
December 0.303141E+09 0.435730E+09 0.261218E+09 0.00 0.00 0.00 0.00 0.00 0.430324E+09
                   
Annual Sum or Average 0.357224E+10 0.510183E+10 0.307265E+10 0.00 0.00 0.00 0.00 0.701149E+09 0.198496E+10
Minimum of Months 0.273974E+09 0.391949E+09 0.235770E+09 0.00 0.00 0.00 0.00 0.00 1790942.10
Maximum of Months 0.303685E+09 0.435730E+09 0.261218E+09 0.00 0.00 0.00 0.00 0.169006E+09 0.430324E+09



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.272788E+09 0.255708E+09 0.00 0.00 0.00 0.00 0.00 0.123130E+09
February 0.00 0.246354E+09 0.230956E+09 0.00 0.00 0.00 0.00 0.00 96017416.72
March 0.00 0.270620E+09 0.255355E+09 0.00 0.00 0.00 0.00 117008.82 87381939.55
April 0.00 0.264302E+09 0.247516E+09 0.00 0.00 0.00 0.00 7206972.41 39803731.48
May 0.00 0.271704E+09 0.255532E+09 0.00 0.00 0.00 0.00 19265271.24 16111073.19
June 0.00 0.262205E+09 0.247163E+09 0.00 0.00 0.00 0.00 37713626.27 4361473.16
July 0.00 0.273836E+09 0.255885E+09 0.00 0.00 0.00 0.00 35085530.13 2699133.52
August 0.00 0.270620E+09 0.255355E+09 0.00 0.00 0.00 0.00 28639751.76 6238688.27
September 0.00 0.264373E+09 0.247516E+09 0.00 0.00 0.00 0.00 16409772.58 17090862.22
October 0.00 0.272752E+09 0.255708E+09 0.00 0.00 0.00 0.00 4181379.08 46020083.01
November 0.00 0.263254E+09 0.247340E+09 0.00 0.00 0.00 0.00 7785.19 95561926.51
December 0.00 0.273872E+09 0.255885E+09 0.00 0.00 0.00 0.00 0.00 0.133371E+09
                   
Annual Sum or Average 0.00 0.320668E+10 0.300992E+10 0.00 0.00 0.00 0.00 0.148627E+09 0.667787E+09
Minimum of Months 0.00 0.246354E+09 0.230956E+09 0.00 0.00 0.00 0.00 0.00 2699133.52
Maximum of Months 0.00 0.273872E+09 0.255885E+09 0.00 0.00 0.00 0.00 37713626.27 0.133371E+09



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.272862E+09 0.255778E+09 0.00 0.00 0.00 0.00 0.00 0.109706E+09
February 0.273974E+09 0.246421E+09 0.231020E+09 0.00 0.00 0.00 0.00 165703.90 83426817.27
March 0.303685E+09 0.270694E+09 0.255425E+09 0.00 0.00 0.00 0.00 704167.97 74096215.14
April 0.293479E+09 0.264375E+09 0.247584E+09 0.00 0.00 0.00 0.00 10932081.37 29781092.54
May 0.303504E+09 0.271778E+09 0.255602E+09 0.00 0.00 0.00 0.00 26337935.70 9570329.06
June 0.293842E+09 0.262277E+09 0.247231E+09 0.00 0.00 0.00 0.00 47463381.16 1554785.35
July 0.303141E+09 0.273911E+09 0.255955E+09 0.00 0.00 0.00 0.00 45878455.56 492597.97
August 0.303685E+09 0.270694E+09 0.255425E+09 0.00 0.00 0.00 0.00 38176357.49 2377175.20
September 0.293479E+09 0.264446E+09 0.247584E+09 0.00 0.00 0.00 0.00 22539063.03 9771217.93
October 0.303322E+09 0.272827E+09 0.255778E+09 0.00 0.00 0.00 0.00 7049592.93 33532185.03
November 0.293661E+09 0.263326E+09 0.247408E+09 0.00 0.00 0.00 0.00 205109.05 82176968.41
December 0.303141E+09 0.273947E+09 0.255955E+09 0.00 0.00 0.00 0.00 0.00 0.121677E+09
                   
Annual Sum or Average 0.357224E+10 0.320756E+10 0.301074E+10 0.00 0.00 0.00 0.00 0.199452E+09 0.558162E+09
Minimum of Months 0.273974E+09 0.246421E+09 0.231020E+09 0.00 0.00 0.00 0.00 0.00 492597.97
Maximum of Months 0.303685E+09 0.273947E+09 0.255955E+09 0.00 0.00 0.00 0.00 47463381.16 0.121677E+09



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.434056E+09 0.261068E+09 0.00 0.00 0.00 0.00 0.00 0.398972E+09
February 0.273974E+09 0.391995E+09 0.235798E+09 0.00 0.00 0.00 0.00 263998.67 0.306095E+09
March 0.303685E+09 0.430607E+09 0.260708E+09 0.00 0.00 0.00 0.00 1565727.83 0.272972E+09
April 0.293479E+09 0.420554E+09 0.252705E+09 0.00 0.00 0.00 0.00 36421964.03 0.110700E+09
May 0.303504E+09 0.432331E+09 0.260888E+09 0.00 0.00 0.00 0.00 92114621.99 35829764.95
June 0.293842E+09 0.417218E+09 0.252344E+09 0.00 0.00 0.00 0.00 0.168698E+09 5888174.32
July 0.303141E+09 0.435725E+09 0.261248E+09 0.00 0.00 0.00 0.00 0.162965E+09 1871266.99
August 0.303685E+09 0.430607E+09 0.260708E+09 0.00 0.00 0.00 0.00 0.134833E+09 9106491.86
September 0.293479E+09 0.420667E+09 0.252705E+09 0.00 0.00 0.00 0.00 77866806.10 36098441.63
October 0.303322E+09 0.434000E+09 0.261068E+09 0.00 0.00 0.00 0.00 22447549.40 0.124130E+09
November 0.293661E+09 0.418886E+09 0.252524E+09 0.00 0.00 0.00 0.00 343592.58 0.302399E+09
December 0.303141E+09 0.435781E+09 0.261248E+09 0.00 0.00 0.00 0.00 0.00 0.441806E+09
                   
Annual Sum or Average 0.357224E+10 0.510243E+10 0.307301E+10 0.00 0.00 0.00 0.00 0.697521E+09 0.204587E+10
Minimum of Months 0.273974E+09 0.391995E+09 0.235798E+09 0.00 0.00 0.00 0.00 0.00 1871266.99
Maximum of Months 0.303685E+09 0.435781E+09 0.261248E+09 0.00 0.00 0.00 0.00 0.168698E+09 0.441806E+09



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.434005E+09 0.261038E+09 0.00 0.00 0.00 0.00 0.00 0.387591E+09
February 0.273974E+09 0.391949E+09 0.235770E+09 0.00 0.00 0.00 0.00 322407.84 0.297869E+09
March 0.303685E+09 0.430556E+09 0.260677E+09 0.00 0.00 0.00 0.00 1746614.10 0.267827E+09
April 0.293479E+09 0.420505E+09 0.252675E+09 0.00 0.00 0.00 0.00 36495465.66 0.109830E+09
May 0.303504E+09 0.432281E+09 0.260857E+09 0.00 0.00 0.00 0.00 92124112.27 35817459.80
June 0.293842E+09 0.417169E+09 0.252315E+09 0.00 0.00 0.00 0.00 0.168667E+09 5893344.85
July 0.303141E+09 0.435674E+09 0.261218E+09 0.00 0.00 0.00 0.00 0.162946E+09 1872891.76
August 0.303685E+09 0.430556E+09 0.260677E+09 0.00 0.00 0.00 0.00 0.134866E+09 9056105.89
September 0.293479E+09 0.420618E+09 0.252675E+09 0.00 0.00 0.00 0.00 77990913.16 36001996.50
October 0.303322E+09 0.433949E+09 0.261038E+09 0.00 0.00 0.00 0.00 22769611.30 0.121933E+09
November 0.293661E+09 0.418837E+09 0.252495E+09 0.00 0.00 0.00 0.00 472506.74 0.293069E+09
December 0.303141E+09 0.435730E+09 0.261218E+09 0.00 0.00 0.00 0.00 0.00 0.430184E+09
                   
Annual Sum or Average 0.357224E+10 0.510183E+10 0.307265E+10 0.00 0.00 0.00 0.00 0.698402E+09 0.199694E+10
Minimum of Months 0.273974E+09 0.391949E+09 0.235770E+09 0.00 0.00 0.00 0.00 0.00 1872891.76
Maximum of Months 0.303685E+09 0.435730E+09 0.261218E+09 0.00 0.00 0.00 0.00 0.168667E+09 0.430184E+09



Table of Contents

Report: SpaceGainsMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.385223E+10 0.133160E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.473177E+09
February 0.348285E+10 0.120231E+10 0.00 0.00 0.00 0.00 0.00 1272788.75 0.357505E+09
March 0.387034E+10 0.133570E+10 0.00 0.00 0.00 0.00 0.00 4639540.79 0.314159E+09
April 0.373454E+10 0.128645E+10 0.00 0.00 0.00 0.00 0.00 55119898.31 0.125628E+09
May 0.386038E+10 0.133391E+10 0.00 0.00 0.00 0.00 0.00 0.120940E+09 43016798.41
June 0.374269E+10 0.129235E+10 0.00 0.00 0.00 0.00 0.00 0.200896E+09 9047488.29
July 0.385223E+10 0.132801E+10 0.00 0.00 0.00 0.00 0.00 0.195427E+09 3520098.54
August 0.386853E+10 0.133622E+10 0.00 0.00 0.00 0.00 0.00 0.163112E+09 11899861.10
September 0.373273E+10 0.128696E+10 0.00 0.00 0.00 0.00 0.00 0.101073E+09 47233435.26
October 0.385404E+10 0.133109E+10 0.00 0.00 0.00 0.00 0.00 34215877.89 0.142529E+09
November 0.372639E+10 0.129132E+10 0.00 0.00 0.00 0.00 0.00 1224747.91 0.351036E+09
December 0.385223E+10 0.132801E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.526927E+09
                   
Annual Sum or Average 0.454292E+11 0.156839E+11 0.00 0.00 0.00 0.00 0.00 0.877920E+09 0.240568E+10
Minimum of Months 0.348285E+10 0.120231E+10 0.00 0.00 0.00 0.00 0.00 0.00 3520098.54
Maximum of Months 0.387034E+10 0.133622E+10 0.00 0.00 0.00 0.00 0.00 0.200896E+09 0.526927E+09



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.434056E+09 0.261068E+09 0.00 0.00 0.00 0.00 0.00 0.397635E+09
February 0.273974E+09 0.391995E+09 0.235798E+09 0.00 0.00 0.00 0.00 247048.61 0.304004E+09
March 0.303685E+09 0.430607E+09 0.260708E+09 0.00 0.00 0.00 0.00 1467769.04 0.270745E+09
April 0.293479E+09 0.420554E+09 0.252705E+09 0.00 0.00 0.00 0.00 35825459.10 0.109168E+09
May 0.303504E+09 0.432331E+09 0.260888E+09 0.00 0.00 0.00 0.00 91149858.38 35306646.05
June 0.293842E+09 0.417218E+09 0.252344E+09 0.00 0.00 0.00 0.00 0.167504E+09 5876552.45
July 0.303141E+09 0.435725E+09 0.261248E+09 0.00 0.00 0.00 0.00 0.161609E+09 1897393.85
August 0.303685E+09 0.430607E+09 0.260708E+09 0.00 0.00 0.00 0.00 0.133569E+09 9140995.94
September 0.293479E+09 0.420667E+09 0.252705E+09 0.00 0.00 0.00 0.00 76814317.21 35944744.67
October 0.303322E+09 0.434000E+09 0.261068E+09 0.00 0.00 0.00 0.00 21981197.94 0.124398E+09
November 0.293661E+09 0.418886E+09 0.252524E+09 0.00 0.00 0.00 0.00 325592.12 0.301506E+09
December 0.303141E+09 0.435781E+09 0.261248E+09 0.00 0.00 0.00 0.00 0.00 0.440733E+09
                   
Annual Sum or Average 0.357224E+10 0.510243E+10 0.307301E+10 0.00 0.00 0.00 0.00 0.690493E+09 0.203635E+10
Minimum of Months 0.273974E+09 0.391995E+09 0.235798E+09 0.00 0.00 0.00 0.00 0.00 1897393.85
Maximum of Months 0.303685E+09 0.435781E+09 0.261248E+09 0.00 0.00 0.00 0.00 0.167504E+09 0.440733E+09



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.434005E+09 0.261038E+09 0.00 0.00 0.00 0.00 0.00 0.386761E+09
February 0.273974E+09 0.391949E+09 0.235770E+09 0.00 0.00 0.00 0.00 265678.78 0.296053E+09
March 0.303685E+09 0.430556E+09 0.260677E+09 0.00 0.00 0.00 0.00 1606520.27 0.265288E+09
April 0.293479E+09 0.420505E+09 0.252675E+09 0.00 0.00 0.00 0.00 36043172.75 0.108055E+09
May 0.303504E+09 0.432281E+09 0.260857E+09 0.00 0.00 0.00 0.00 91183706.15 35180507.70
June 0.293842E+09 0.417169E+09 0.252315E+09 0.00 0.00 0.00 0.00 0.167447E+09 5902593.40
July 0.303141E+09 0.435674E+09 0.261218E+09 0.00 0.00 0.00 0.00 0.161568E+09 1907034.96
August 0.303685E+09 0.430556E+09 0.260677E+09 0.00 0.00 0.00 0.00 0.133646E+09 9091976.20
September 0.293479E+09 0.420618E+09 0.252675E+09 0.00 0.00 0.00 0.00 77171890.98 35685032.66
October 0.303322E+09 0.433949E+09 0.261038E+09 0.00 0.00 0.00 0.00 22293962.60 0.121683E+09
November 0.293661E+09 0.418837E+09 0.252495E+09 0.00 0.00 0.00 0.00 327818.92 0.293845E+09
December 0.303141E+09 0.435730E+09 0.261218E+09 0.00 0.00 0.00 0.00 0.00 0.429391E+09
                   
Annual Sum or Average 0.357224E+10 0.510183E+10 0.307265E+10 0.00 0.00 0.00 0.00 0.691553E+09 0.198884E+10
Minimum of Months 0.273974E+09 0.391949E+09 0.235770E+09 0.00 0.00 0.00 0.00 0.00 1907034.96
Maximum of Months 0.303685E+09 0.435730E+09 0.261218E+09 0.00 0.00 0.00 0.00 0.167447E+09 0.429391E+09



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.272862E+09 0.255778E+09 0.00 0.00 0.00 0.00 0.00 0.208938E+09
February 0.273974E+09 0.246421E+09 0.231020E+09 0.00 0.00 0.00 0.00 125250.54 0.159395E+09
March 0.303685E+09 0.270694E+09 0.255425E+09 0.00 0.00 0.00 0.00 751653.49 0.140950E+09
April 0.293479E+09 0.264375E+09 0.247584E+09 0.00 0.00 0.00 0.00 18345391.12 56310260.10
May 0.303504E+09 0.271778E+09 0.255602E+09 0.00 0.00 0.00 0.00 46732682.74 18063545.41
June 0.293842E+09 0.262277E+09 0.247231E+09 0.00 0.00 0.00 0.00 85811239.96 2975924.53
July 0.303141E+09 0.273911E+09 0.255955E+09 0.00 0.00 0.00 0.00 82806313.09 965436.76
August 0.303685E+09 0.270694E+09 0.255425E+09 0.00 0.00 0.00 0.00 68397580.23 4675498.63
September 0.293479E+09 0.264446E+09 0.247584E+09 0.00 0.00 0.00 0.00 39280288.98 18482974.75
October 0.303322E+09 0.272827E+09 0.255778E+09 0.00 0.00 0.00 0.00 11205646.60 64421048.18
November 0.293661E+09 0.263326E+09 0.247408E+09 0.00 0.00 0.00 0.00 162160.10 0.157074E+09
December 0.303141E+09 0.273947E+09 0.255955E+09 0.00 0.00 0.00 0.00 0.00 0.231635E+09
                   
Annual Sum or Average 0.357224E+10 0.320756E+10 0.301074E+10 0.00 0.00 0.00 0.00 0.353618E+09 0.106389E+10
Minimum of Months 0.273974E+09 0.246421E+09 0.231020E+09 0.00 0.00 0.00 0.00 0.00 965436.76
Maximum of Months 0.303685E+09 0.273947E+09 0.255955E+09 0.00 0.00 0.00 0.00 85811239.96 0.231635E+09



Table of Contents

Report: SpaceGainsMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.459349E+11 0.396945E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.00 0.979619E+09
February 0.415303E+11 0.358405E+10 0.134904E+11 0.00 0.00 0.00 0.00 2460964.79 0.746141E+09
March 0.461508E+11 0.398168E+10 0.149358E+11 0.00 0.00 0.00 0.00 8831754.25 0.665992E+09
April 0.445315E+11 0.383486E+10 0.144540E+11 0.00 0.00 0.00 0.00 0.104900E+09 0.281915E+09
May 0.460320E+11 0.397633E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.235646E+09 0.103665E+09
June 0.446286E+11 0.385245E+10 0.144540E+11 0.00 0.00 0.00 0.00 0.403696E+09 22743231.37
July 0.459349E+11 0.395874E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.389401E+09 11515494.72
August 0.461292E+11 0.398321E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.327109E+09 31778545.91
September 0.445099E+11 0.383639E+10 0.144540E+11 0.00 0.00 0.00 0.00 0.208809E+09 0.108431E+09
October 0.459565E+11 0.396792E+10 0.149358E+11 0.00 0.00 0.00 0.00 70230596.24 0.314508E+09
November 0.444343E+11 0.384939E+10 0.144540E+11 0.00 0.00 0.00 0.00 2520020.90 0.735435E+09
December 0.459349E+11 0.395874E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.00 0.108547E+10
                   
Annual Sum or Average 0.541708E+12 0.467532E+11 0.175857E+12 0.00 0.00 0.00 0.00 0.175360E+10 0.508721E+10
Minimum of Months 0.415303E+11 0.358405E+10 0.134904E+11 0.00 0.00 0.00 0.00 0.00 11515494.72
Maximum of Months 0.461508E+11 0.398321E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.403696E+09 0.108547E+10



Table of Contents

Report: SpaceGainsMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.459349E+11 0.396945E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.00 0.982141E+09
February 0.415303E+11 0.358405E+10 0.134904E+11 0.00 0.00 0.00 0.00 2429573.76 0.748694E+09
March 0.461508E+11 0.398168E+10 0.149358E+11 0.00 0.00 0.00 0.00 8632181.71 0.669139E+09
April 0.445315E+11 0.383486E+10 0.144540E+11 0.00 0.00 0.00 0.00 0.103148E+09 0.284654E+09
May 0.460320E+11 0.397633E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.231818E+09 0.105495E+09
June 0.446286E+11 0.385245E+10 0.144540E+11 0.00 0.00 0.00 0.00 0.399285E+09 23338657.35
July 0.459349E+11 0.395874E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.384583E+09 11963708.66
August 0.461292E+11 0.398321E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.323049E+09 32672038.09
September 0.445099E+11 0.383639E+10 0.144540E+11 0.00 0.00 0.00 0.00 0.206142E+09 0.110276E+09
October 0.459565E+11 0.396792E+10 0.149358E+11 0.00 0.00 0.00 0.00 69278547.17 0.317292E+09
November 0.444343E+11 0.384939E+10 0.144540E+11 0.00 0.00 0.00 0.00 2461910.35 0.738159E+09
December 0.459349E+11 0.395874E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.00 0.108788E+10
                   
Annual Sum or Average 0.541708E+12 0.467532E+11 0.175857E+12 0.00 0.00 0.00 0.00 0.173083E+10 0.511171E+10
Minimum of Months 0.415303E+11 0.358405E+10 0.134904E+11 0.00 0.00 0.00 0.00 0.00 11963708.66
Maximum of Months 0.461508E+11 0.398321E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.399285E+09 0.108788E+10



Table of Contents

Report: SpaceGainsMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.408770E+10 0.105977E+10 0.338870E+11 0.305408E+11 0.00 0.00 0.00 0.00 0.969728E+09
February 0.369574E+10 0.956878E+09 0.306077E+11 0.275852E+11 0.00 0.00 0.00 0.00 0.751502E+09
March 0.410691E+10 0.106304E+10 0.338870E+11 0.305408E+11 0.00 0.00 0.00 332953.60 0.681621E+09
April 0.396281E+10 0.102384E+10 0.327939E+11 0.295556E+11 0.00 0.00 0.00 46250382.58 0.291930E+09
May 0.409635E+10 0.106161E+10 0.338870E+11 0.305408E+11 0.00 0.00 0.00 0.138741E+09 0.104289E+09
June 0.397146E+10 0.102854E+10 0.327939E+11 0.295556E+11 0.00 0.00 0.00 0.289561E+09 21839677.70
July 0.408770E+10 0.105691E+10 0.338870E+11 0.305408E+11 0.00 0.00 0.00 0.272415E+09 11168887.87
August 0.410499E+10 0.106345E+10 0.338870E+11 0.305408E+11 0.00 0.00 0.00 0.219859E+09 35536673.19
September 0.396089E+10 0.102425E+10 0.327939E+11 0.295556E+11 0.00 0.00 0.00 0.113722E+09 0.107902E+09
October 0.408962E+10 0.105936E+10 0.338870E+11 0.305408E+11 0.00 0.00 0.00 27819112.60 0.337693E+09
November 0.395417E+10 0.102772E+10 0.327939E+11 0.295556E+11 0.00 0.00 0.00 9317.60 0.748027E+09
December 0.408770E+10 0.105691E+10 0.338870E+11 0.305408E+11 0.00 0.00 0.00 0.00 0.106561E+10
                   
Annual Sum or Average 0.482060E+11 0.124823E+11 0.398993E+12 0.359593E+12 0.00 0.00 0.00 0.110871E+10 0.512685E+10
Minimum of Months 0.369574E+10 0.956878E+09 0.306077E+11 0.275852E+11 0.00 0.00 0.00 0.00 11168887.87
Maximum of Months 0.410691E+10 0.106345E+10 0.338870E+11 0.305408E+11 0.00 0.00 0.00 0.289561E+09 0.106561E+10



Table of Contents

Report: SpaceGainsMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.407704E+10 0.140929E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.841216E+09
February 0.368610E+10 0.127246E+10 0.00 0.00 0.00 0.00 0.00 2193266.67 0.635784E+09
March 0.409620E+10 0.141364E+10 0.00 0.00 0.00 0.00 0.00 7991797.78 0.558857E+09
April 0.395248E+10 0.136151E+10 0.00 0.00 0.00 0.00 0.00 98699854.65 0.220903E+09
May 0.408566E+10 0.141173E+10 0.00 0.00 0.00 0.00 0.00 0.225319E+09 69895115.85
June 0.396110E+10 0.136775E+10 0.00 0.00 0.00 0.00 0.00 0.375385E+09 11099680.51
July 0.407704E+10 0.140549E+10 0.00 0.00 0.00 0.00 0.00 0.366913E+09 3411936.69
August 0.409429E+10 0.141418E+10 0.00 0.00 0.00 0.00 0.00 0.307922E+09 16142153.34
September 0.395056E+10 0.136205E+10 0.00 0.00 0.00 0.00 0.00 0.190565E+09 71958690.85
October 0.407896E+10 0.140875E+10 0.00 0.00 0.00 0.00 0.00 63144148.21 0.247807E+09
November 0.394385E+10 0.136667E+10 0.00 0.00 0.00 0.00 0.00 2186535.41 0.623876E+09
December 0.407704E+10 0.140549E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.936343E+09
                   
Annual Sum or Average 0.480803E+11 0.165990E+11 0.00 0.00 0.00 0.00 0.00 0.164032E+10 0.423730E+10
Minimum of Months 0.368610E+10 0.127246E+10 0.00 0.00 0.00 0.00 0.00 0.00 3411936.69
Maximum of Months 0.409620E+10 0.141418E+10 0.00 0.00 0.00 0.00 0.00 0.375385E+09 0.936343E+09



Table of Contents

Report: PeakSpaceGainsMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 11501.89 02-JAN-00:10 13517.00 02-JAN-20:10 10113.80 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 0.00
February 11501.89 01-FEB-00:10 13517.00 01-FEB-20:10 10113.80 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 0.00
March 11501.89 01-MAR-00:10 13517.00 01-MAR-20:10 10113.80 01-MAR-20:10 0.00 0.00 0.00 0.00 0.00 0.00
April 11501.89 01-APR-00:10 13517.00 03-APR-19:10 10113.80 03-APR-19:10 0.00 0.00 0.00 0.00 0.00 0.00
May 11501.89 01-MAY-00:10 13517.00 01-MAY-19:10 10113.80 01-MAY-19:10 0.00 0.00 0.00 0.00 0.00 0.00
June 11501.89 01-JUN-00:10 13517.00 01-JUN-19:10 10113.80 01-JUN-19:10 0.00 0.00 0.00 0.00 0.00 0.00
July 11501.89 01-JUL-00:10 13517.00 03-JUL-19:10 10113.80 03-JUL-19:10 0.00 0.00 0.00 0.00 0.00 0.00
August 11501.89 01-AUG-00:10 13517.00 01-AUG-19:10 10113.80 01-AUG-19:10 0.00 0.00 0.00 0.00 0.00 0.00
September 11501.89 01-SEP-00:10 13517.00 01-SEP-19:10 10113.80 01-SEP-19:10 0.00 0.00 0.00 0.00 0.00 0.00
October 11501.89 01-OCT-23:10 13517.00 02-OCT-19:10 10113.80 02-OCT-19:10 0.00 0.00 0.00 0.00 0.00 0.00
November 11501.89 01-NOV-00:10 13517.00 01-NOV-19:10 10113.80 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 0.00
December 11501.89 01-DEC-00:10 13517.00 01-DEC-20:10 10113.80 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 11501.89   13517.00   10113.80   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 11501.89   13517.00   10113.80   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1169.53 02-JAN-00:10 687.30 02-JAN-20:10 685.60 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 515.20 27-JAN-07:00
February 1169.53 01-FEB-00:10 687.30 01-FEB-20:10 685.60 01-FEB-20:10 0.00 0.00 0.00 0.00 32.96 22-FEB-16:00 541.35 03-FEB-07:00
March 1169.53 01-MAR-00:10 687.30 01-MAR-20:10 685.60 01-MAR-20:10 0.00 0.00 0.00 0.00 69.95 21-MAR-16:00 509.39 02-MAR-06:00
April 1169.53 01-APR-00:10 687.30 03-APR-19:10 685.60 03-APR-19:10 0.00 0.00 0.00 0.00 188.64 21-APR-15:00 346.79 12-APR-06:00
May 1169.53 01-MAY-00:10 687.30 01-MAY-19:10 685.60 01-MAY-19:10 0.00 0.00 0.00 0.00 246.00 19-MAY-16:00 222.39 02-MAY-06:00
June 1169.53 01-JUN-00:10 687.30 01-JUN-19:10 685.60 01-JUN-19:10 0.00 0.00 0.00 0.00 309.47 02-JUN-17:00 113.48 13-JUN-05:00
July 1169.53 01-JUL-00:10 687.30 03-JUL-19:10 685.60 03-JUL-19:10 0.00 0.00 0.00 0.00 300.53 03-JUL-17:00 60.06 05-JUL-06:00
August 1169.53 01-AUG-00:10 687.30 01-AUG-19:10 685.60 01-AUG-19:10 0.00 0.00 0.00 0.00 274.86 07-AUG-16:00 81.45 31-AUG-06:00
September 1169.53 01-SEP-00:10 687.30 01-SEP-19:10 685.60 01-SEP-19:10 0.00 0.00 0.00 0.00 209.82 19-SEP-16:30 245.77 30-SEP-06:00
October 1169.53 01-OCT-23:10 687.30 02-OCT-19:10 685.60 02-OCT-19:10 0.00 0.00 0.00 0.00 180.18 01-OCT-15:00 279.79 25-OCT-06:00
November 1169.53 01-NOV-00:10 687.30 01-NOV-19:10 685.60 01-NOV-19:10 0.00 0.00 0.00 0.00 38.45 08-NOV-15:40 436.69 28-NOV-05:00
December 1169.53 01-DEC-00:10 687.30 01-DEC-20:10 685.60 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 512.89 27-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1169.53   687.30   685.60   0.00 0.00 0.00 0.00 0.00   60.06  
Maximum of Months 1169.53   687.30   685.60   0.00 0.00 0.00 0.00 309.47   541.35  



Table of Contents

Report: PeakSpaceGainsMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1354.32 02-JAN-00:10 795.89 02-JAN-20:10 793.93 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 198.87 27-JAN-07:00
February 1354.32 01-FEB-00:10 795.89 01-FEB-20:10 793.93 01-FEB-20:10 0.00 0.00 0.00 0.00 16.41 20-FEB-15:00 208.98 03-FEB-07:00
March 1354.32 01-MAR-00:10 795.89 01-MAR-20:10 793.93 01-MAR-20:10 0.00 0.00 0.00 0.00 28.00 21-MAR-16:00 196.60 02-MAR-05:40
April 1354.32 01-APR-00:10 795.89 03-APR-19:10 793.93 03-APR-19:10 0.00 0.00 0.00 0.00 76.79 21-APR-14:00 133.83 12-APR-06:00
May 1354.32 01-MAY-00:10 795.89 01-MAY-19:10 793.93 01-MAY-19:10 0.00 0.00 0.00 0.00 95.81 21-MAY-14:00 85.87 02-MAY-06:00
June 1354.32 01-JUN-00:10 795.89 01-JUN-19:10 793.93 01-JUN-19:10 0.00 0.00 0.00 0.00 120.74 02-JUN-16:00 45.84 13-JUN-05:00
July 1354.32 01-JUL-00:10 795.89 03-JUL-19:10 793.93 03-JUL-19:10 0.00 0.00 0.00 0.00 117.16 02-JUL-16:00 23.19 05-JUL-06:00
August 1354.32 01-AUG-00:10 795.89 01-AUG-19:10 793.93 01-AUG-19:10 0.00 0.00 0.00 0.00 110.06 07-AUG-16:00 32.54 31-AUG-06:00
September 1354.32 01-SEP-00:10 795.89 01-SEP-19:10 793.93 01-SEP-19:10 0.00 0.00 0.00 0.00 88.38 19-SEP-14:00 94.85 30-SEP-06:00
October 1354.32 01-OCT-23:10 795.89 02-OCT-19:10 793.93 02-OCT-19:10 0.00 0.00 0.00 0.00 81.32 01-OCT-15:00 108.00 25-OCT-06:00
November 1354.32 01-NOV-00:10 795.89 01-NOV-19:10 793.93 01-NOV-19:10 0.00 0.00 0.00 0.00 20.53 08-NOV-15:00 168.55 28-NOV-05:00
December 1354.32 01-DEC-00:10 795.89 01-DEC-20:10 793.93 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 199.58 27-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1354.32   795.89   793.93   0.00 0.00 0.00 0.00 0.00   23.19  
Maximum of Months 1354.32   795.89   793.93   0.00 0.00 0.00 0.00 120.74   208.98  



Table of Contents

Report: PeakSpaceGainsMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 286.42 02-JAN-00:10 1487.69 02-JAN-20:10 839.45 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 470.02 27-JAN-07:00
February 286.42 01-FEB-00:10 1487.69 01-FEB-20:10 839.45 01-FEB-20:10 0.00 0.00 0.00 0.00 38.77 20-FEB-15:00 493.87 03-FEB-07:00
March 286.42 01-MAR-00:10 1487.69 01-MAR-20:10 839.45 01-MAR-20:10 0.00 0.00 0.00 0.00 66.25 21-MAR-16:00 464.64 02-MAR-05:10
April 286.42 01-APR-00:10 1487.69 03-APR-19:10 839.45 03-APR-19:10 0.00 0.00 0.00 0.00 181.45 21-APR-14:00 316.29 12-APR-06:00
May 286.42 01-MAY-00:10 1487.69 01-MAY-19:10 839.45 01-MAY-19:10 0.00 0.00 0.00 0.00 226.45 21-MAY-14:00 202.94 02-MAY-06:00
June 286.42 01-JUN-00:10 1487.69 01-JUN-19:10 839.45 01-JUN-19:10 0.00 0.00 0.00 0.00 285.34 02-JUN-16:00 103.50 13-JUN-05:00
July 286.42 01-JUL-00:10 1487.69 03-JUL-19:10 839.45 03-JUL-19:10 0.00 0.00 0.00 0.00 276.89 02-JUL-16:00 54.82 05-JUL-06:00
August 286.42 01-AUG-00:10 1487.69 01-AUG-19:10 839.45 01-AUG-19:10 0.00 0.00 0.00 0.00 260.10 07-AUG-16:00 74.33 31-AUG-06:00
September 286.42 01-SEP-00:10 1487.69 01-SEP-19:10 839.45 01-SEP-19:10 0.00 0.00 0.00 0.00 208.89 19-SEP-14:00 224.16 30-SEP-06:00
October 286.42 01-OCT-23:10 1487.69 02-OCT-19:10 839.45 02-OCT-19:10 0.00 0.00 0.00 0.00 192.17 01-OCT-15:00 255.24 25-OCT-06:00
November 286.42 01-NOV-00:10 1487.69 01-NOV-19:10 839.45 01-NOV-19:10 0.00 0.00 0.00 0.00 48.52 08-NOV-15:00 398.33 28-NOV-05:00
December 286.42 01-DEC-00:10 1487.69 01-DEC-20:10 839.45 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 471.70 27-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 286.42   1487.69   839.45   0.00 0.00 0.00 0.00 0.00   54.82  
Maximum of Months 286.42   1487.69   839.45   0.00 0.00 0.00 0.00 285.34   493.87  



Table of Contents

Report: PeakSpaceGainsMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 220.32 02-JAN-00:10 273.10 02-JAN-20:10 242.16 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 271.16 27-JAN-07:00
February 220.32 01-FEB-00:10 273.10 01-FEB-20:10 242.16 01-FEB-20:10 0.00 0.00 0.00 0.00 22.36 20-FEB-15:40 284.93 03-FEB-07:00
March 220.32 01-MAR-00:10 273.10 01-MAR-20:10 242.16 01-MAR-20:10 0.00 0.00 0.00 0.00 38.20 21-MAR-16:00 268.07 02-MAR-06:00
April 220.32 01-APR-00:10 273.10 03-APR-19:10 242.16 03-APR-19:10 0.00 0.00 0.00 0.00 104.71 21-APR-14:00 182.48 12-APR-06:00
May 220.32 01-MAY-00:10 273.10 01-MAY-19:10 242.16 01-MAY-19:10 0.00 0.00 0.00 0.00 130.65 21-MAY-14:00 117.06 02-MAY-06:00
June 220.32 01-JUN-00:10 273.10 01-JUN-19:10 242.16 01-JUN-19:10 0.00 0.00 0.00 0.00 164.64 02-JUN-16:00 59.70 13-JUN-05:00
July 220.32 01-JUL-00:10 273.10 03-JUL-19:10 242.16 03-JUL-19:10 0.00 0.00 0.00 0.00 159.74 02-JUL-16:00 31.63 05-JUL-06:00
August 220.32 01-AUG-00:10 273.10 01-AUG-19:10 242.16 01-AUG-19:10 0.00 0.00 0.00 0.00 150.07 07-AUG-16:00 42.87 31-AUG-06:00
September 220.32 01-SEP-00:10 273.10 01-SEP-19:10 242.16 01-SEP-19:10 0.00 0.00 0.00 0.00 120.51 19-SEP-14:00 129.30 30-SEP-06:00
October 220.32 01-OCT-23:10 273.10 02-OCT-19:10 242.16 02-OCT-19:10 0.00 0.00 0.00 0.00 110.86 01-OCT-15:00 147.26 25-OCT-06:00
November 220.32 01-NOV-00:10 273.10 01-NOV-19:10 242.16 01-NOV-19:10 0.00 0.00 0.00 0.00 28.01 08-NOV-15:00 229.81 28-NOV-05:00
December 220.32 01-DEC-00:10 273.10 01-DEC-20:10 242.16 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 272.17 27-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 220.32   273.10   242.16   0.00 0.00 0.00 0.00 0.00   31.63  
Maximum of Months 220.32   273.10   242.16   0.00 0.00 0.00 0.00 164.64   284.93  



Table of Contents

Report: PeakSpaceGainsMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 907.20 02-JAN-00:10 337.37 02-JAN-20:10 4572.80 02-JAN-20:10 39726.58 02-JAN-20:10 0.00 0.00 0.00 0.00 01-JAN-00:05 642.16 27-JAN-07:10
February 907.20 01-FEB-00:10 337.37 01-FEB-20:10 4572.80 01-FEB-20:10 39726.58 01-FEB-20:10 0.00 0.00 0.00 53.29 20-FEB-16:00 674.18 03-FEB-07:00
March 907.20 01-MAR-00:10 337.37 01-MAR-20:10 4572.80 01-MAR-20:10 39726.58 01-MAR-20:10 0.00 0.00 0.00 90.35 21-MAR-16:00 634.43 02-MAR-05:30
April 907.20 01-APR-00:10 337.37 03-APR-19:10 4572.80 03-APR-19:10 39726.58 03-APR-19:10 0.00 0.00 0.00 247.72 21-APR-14:40 432.10 12-APR-06:00
May 907.20 01-MAY-00:10 337.37 01-MAY-19:10 4572.80 01-MAY-19:10 39726.58 01-MAY-19:10 0.00 0.00 0.00 309.43 21-MAY-14:00 277.31 02-MAY-06:00
June 907.20 01-JUN-00:10 337.37 01-JUN-19:10 4572.80 01-JUN-19:10 39726.58 01-JUN-19:10 0.00 0.00 0.00 389.61 02-JUN-16:00 141.14 13-JUN-05:00
July 907.20 01-JUL-00:10 337.37 03-JUL-19:10 4572.80 03-JUL-19:10 39726.58 03-JUL-19:10 0.00 0.00 0.00 378.27 02-JUL-16:00 93.31 18-JUL-21:00
August 907.20 01-AUG-00:10 337.37 01-AUG-19:10 4572.80 01-AUG-19:10 39726.58 01-AUG-19:10 0.00 0.00 0.00 355.46 07-AUG-16:00 145.98 16-AUG-21:00
September 907.20 01-SEP-00:10 337.37 01-SEP-19:10 4572.80 01-SEP-19:10 39726.58 01-SEP-19:10 0.00 0.00 0.00 285.20 19-SEP-14:00 306.23 30-SEP-06:00
October 907.20 01-OCT-23:10 337.37 02-OCT-19:10 4572.80 02-OCT-19:10 39726.58 02-OCT-19:10 0.00 0.00 0.00 262.12 01-OCT-15:00 351.00 25-OCT-06:10
November 907.20 01-NOV-00:10 337.37 01-NOV-19:10 4572.80 01-NOV-19:10 39726.58 01-NOV-19:10 0.00 0.00 0.00 66.31 03-NOV-16:00 567.29 27-NOV-23:00
December 907.20 01-DEC-00:10 337.37 01-DEC-20:10 4572.80 01-DEC-20:10 39726.58 01-DEC-20:10 0.00 0.00 0.00 0.00 01-DEC-00:03 644.12 27-DEC-07:00
                               
Annual Sum or Average                 0.00 0.00 0.00        
Minimum of Months 907.20   337.37   4572.80   39726.58   0.00 0.00 0.00 0.00   93.31  
Maximum of Months 907.20   337.37   4572.80   39726.58   0.00 0.00 0.00 389.61   674.18  



Table of Contents

Report: PeakSpaceGainsMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 15368.40 02-JAN-00:10 2177.23 02-JAN-20:10 965.27 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 1139.05 27-JAN-07:00
February 15368.40 01-FEB-00:10 2177.23 01-FEB-20:10 965.27 01-FEB-20:10 0.00 0.00 0.00 0.00 76.18 20-FEB-16:00 1196.73 03-FEB-07:00
March 15368.40 01-MAR-00:10 2177.23 01-MAR-20:10 965.27 01-MAR-20:10 0.00 0.00 0.00 0.00 148.21 21-MAR-16:00 1126.31 02-MAR-05:40
April 15368.40 01-APR-00:10 2177.23 03-APR-19:10 965.27 03-APR-19:10 0.00 0.00 0.00 0.00 429.29 21-APR-15:00 766.61 12-APR-06:00
May 15368.40 01-MAY-00:10 2177.23 01-MAY-19:10 965.27 01-MAY-19:10 0.00 0.00 0.00 0.00 547.18 21-MAY-14:00 491.90 02-MAY-06:00
June 15368.40 01-JUN-00:10 2177.23 01-JUN-19:10 965.27 01-JUN-19:10 0.00 0.00 0.00 0.00 689.04 02-JUN-16:20 269.19 13-JUN-05:00
July 15368.40 01-JUL-00:10 2177.23 03-JUL-19:10 965.27 03-JUL-19:10 0.00 0.00 0.00 0.00 670.85 02-JUL-16:00 132.91 05-JUL-06:00
August 15368.40 01-AUG-00:10 2177.23 01-AUG-19:10 965.27 01-AUG-19:10 0.00 0.00 0.00 0.00 619.51 07-AUG-16:00 182.74 31-AUG-06:00
September 15368.40 01-SEP-00:10 2177.23 01-SEP-19:10 965.27 01-SEP-19:10 0.00 0.00 0.00 0.00 476.44 19-SEP-16:30 543.37 30-SEP-06:00
October 15368.40 01-OCT-23:10 2177.23 02-OCT-19:10 965.27 02-OCT-19:10 0.00 0.00 0.00 0.00 428.57 01-OCT-15:00 618.78 25-OCT-06:00
November 15368.40 01-NOV-00:10 2177.23 01-NOV-19:10 965.27 01-NOV-19:10 0.00 0.00 0.00 0.00 96.94 08-NOV-15:40 965.45 28-NOV-05:00
December 15368.40 01-DEC-00:10 2177.23 01-DEC-20:10 965.27 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 1143.40 27-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 15368.40   2177.23   965.27   0.00 0.00 0.00 0.00 0.00   132.91  
Maximum of Months 15368.40   2177.23   965.27   0.00 0.00 0.00 0.00 689.04   1196.73  



Table of Contents

Report: PeakSpaceGainsMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 45622.98 02-JAN-00:10 11849.32 02-JAN-20:10 10029.21 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 3254.09 27-JAN-07:00
February 45622.98 01-FEB-00:10 11849.32 01-FEB-20:10 10029.21 01-FEB-20:10 0.00 0.00 0.00 0.00 268.47 20-FEB-15:50 3419.98 03-FEB-07:00
March 45622.98 01-MAR-00:10 11849.32 01-MAR-20:10 10029.21 01-MAR-20:10 0.00 0.00 0.00 0.00 458.22 21-MAR-16:00 3217.26 02-MAR-06:00
April 45622.98 01-APR-00:10 11849.32 03-APR-19:10 10029.21 03-APR-19:10 0.00 0.00 0.00 0.00 1256.15 21-APR-14:00 2189.80 12-APR-06:00
May 45622.98 01-MAY-00:10 11849.32 01-MAY-19:10 10029.21 01-MAY-19:10 0.00 0.00 0.00 0.00 1567.59 21-MAY-14:00 1412.35 02-MAY-06:00
June 45622.98 01-JUN-00:10 11849.32 01-JUN-19:10 10029.21 01-JUN-19:10 0.00 0.00 0.00 0.00 1975.47 02-JUN-16:00 804.21 13-JUN-05:00
July 45622.98 01-JUL-00:10 11849.32 03-JUL-19:10 10029.21 03-JUL-19:10 0.00 0.00 0.00 0.00 1916.98 02-JUL-16:00 425.77 05-JUL-06:00
August 45622.98 01-AUG-00:10 11849.32 01-AUG-19:10 10029.21 01-AUG-19:10 0.00 0.00 0.00 0.00 1800.60 07-AUG-16:00 571.06 31-AUG-06:00
September 45622.98 01-SEP-00:10 11849.32 01-SEP-19:10 10029.21 01-SEP-19:10 0.00 0.00 0.00 0.00 1444.02 19-SEP-16:00 1564.16 30-SEP-06:00
October 45622.98 01-OCT-23:10 11849.32 02-OCT-19:10 10029.21 02-OCT-19:10 0.00 0.00 0.00 0.00 1330.36 01-OCT-15:00 1767.77 25-OCT-06:00
November 45622.98 01-NOV-00:10 11849.32 01-NOV-19:10 10029.21 01-NOV-19:10 0.00 0.00 0.00 0.00 336.00 08-NOV-15:00 2758.11 28-NOV-05:00
December 45622.98 01-DEC-00:10 11849.32 01-DEC-20:10 10029.21 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 3266.12 27-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 45622.98   11849.32   10029.21   0.00 0.00 0.00 0.00 0.00   425.77  
Maximum of Months 45622.98   11849.32   10029.21   0.00 0.00 0.00 0.00 1975.47   3419.98  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 392.73 01-JAN-19:10 237.06 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 300.81 27-JAN-07:00
February 180.00 01-FEB-00:10 392.73 01-FEB-20:10 237.06 01-FEB-07:10 0.00 0.00 0.00 0.00 21.04 20-FEB-16:09 316.02 03-FEB-07:00
March 180.00 01-MAR-00:10 392.73 01-MAR-20:10 237.06 01-MAR-07:10 0.00 0.00 0.00 0.00 40.51 21-MAR-16:00 297.41 02-MAR-05:00
April 180.00 01-APR-00:10 392.73 01-APR-18:10 237.06 01-APR-07:10 0.00 0.00 0.00 0.00 111.91 21-APR-15:10 202.97 12-APR-06:00
May 180.00 01-MAY-00:10 392.73 01-MAY-19:10 237.06 01-MAY-06:10 0.00 0.00 0.00 0.00 141.97 19-MAY-16:00 130.81 02-MAY-06:00
June 180.00 01-JUN-00:10 392.73 01-JUN-19:10 237.06 01-JUN-06:10 0.00 0.00 0.00 0.00 179.98 02-JUN-16:00 67.52 13-JUN-05:00
July 180.00 01-JUL-00:10 392.73 01-JUL-18:10 237.06 01-JUL-07:10 0.00 0.00 0.00 0.00 174.59 02-JUL-16:00 36.55 05-JUL-06:00
August 180.00 01-AUG-00:10 392.73 01-AUG-19:10 237.06 01-AUG-06:10 0.00 0.00 0.00 0.00 163.94 07-AUG-16:00 48.97 31-AUG-06:00
September 180.00 01-SEP-00:10 392.73 01-SEP-19:10 237.06 01-SEP-06:10 0.00 0.00 0.00 0.00 131.02 19-SEP-16:00 144.33 30-SEP-06:00
October 180.00 01-OCT-00:10 392.73 01-OCT-18:10 237.06 01-OCT-07:10 0.00 0.00 0.00 0.00 118.83 01-OCT-15:10 164.14 25-OCT-06:00
November 180.00 01-NOV-00:10 392.73 01-NOV-19:10 237.06 01-NOV-06:10 0.00 0.00 0.00 0.00 29.22 03-NOV-16:00 255.22 28-NOV-05:00
December 180.00 01-DEC-00:10 392.73 01-DEC-20:10 237.06 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 301.94 27-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   392.73   237.06   0.00 0.00 0.00 0.00 0.00   36.55  
Maximum of Months 180.00   392.73   237.06   0.00 0.00 0.00 0.00 179.98   316.02  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 392.68 01-JAN-19:10 237.03 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 300.77 27-JAN-07:00
February 180.00 01-FEB-00:10 392.68 01-FEB-20:10 237.03 01-FEB-07:10 0.00 0.00 0.00 0.00 21.04 20-FEB-16:09 315.99 03-FEB-07:00
March 180.00 01-MAR-00:10 392.68 01-MAR-20:10 237.03 01-MAR-07:10 0.00 0.00 0.00 0.00 40.51 21-MAR-16:00 297.38 02-MAR-06:00
April 180.00 01-APR-00:10 392.68 01-APR-18:10 237.03 01-APR-07:10 0.00 0.00 0.00 0.00 111.90 21-APR-15:10 202.95 12-APR-06:00
May 180.00 01-MAY-00:10 392.68 01-MAY-19:10 237.03 01-MAY-06:10 0.00 0.00 0.00 0.00 141.95 19-MAY-16:00 130.80 02-MAY-06:00
June 180.00 01-JUN-00:10 392.68 01-JUN-19:10 237.03 01-JUN-06:10 0.00 0.00 0.00 0.00 179.97 02-JUN-16:00 67.52 13-JUN-05:00
July 180.00 01-JUL-00:10 392.68 01-JUL-18:10 237.03 01-JUL-07:10 0.00 0.00 0.00 0.00 174.58 02-JUL-16:00 36.55 05-JUL-06:00
August 180.00 01-AUG-00:10 392.68 01-AUG-19:10 237.03 01-AUG-06:10 0.00 0.00 0.00 0.00 163.92 07-AUG-16:00 48.96 31-AUG-06:00
September 180.00 01-SEP-00:10 392.68 01-SEP-19:10 237.03 01-SEP-06:10 0.00 0.00 0.00 0.00 131.12 19-SEP-16:00 144.31 30-SEP-06:00
October 180.00 01-OCT-00:10 392.68 01-OCT-18:10 237.03 01-OCT-07:10 0.00 0.00 0.00 0.00 118.82 01-OCT-15:10 164.12 25-OCT-06:00
November 180.00 01-NOV-00:10 392.68 01-NOV-19:10 237.03 01-NOV-06:10 0.00 0.00 0.00 0.00 29.22 03-NOV-16:00 255.20 28-NOV-05:00
December 180.00 01-DEC-00:10 392.68 01-DEC-20:10 237.03 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 301.92 27-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   392.68   237.03   0.00 0.00 0.00 0.00 0.00   36.55  
Maximum of Months 180.00   392.68   237.03   0.00 0.00 0.00 0.00 179.97   315.99  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 01-JAN-00:10 246.81 01-JAN-19:10 232.19 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 80.82 27-JAN-07:20
February 0.00 01-FEB-00:10 246.81 01-FEB-20:10 232.19 01-FEB-07:10 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 85.08 03-FEB-07:00
March 0.00 01-MAR-00:10 246.81 01-MAR-20:10 232.19 01-MAR-07:10 0.00 0.00 0.00 0.00 4.77 21-MAR-16:00 78.67 02-MAR-05:00
April 0.00 01-APR-00:10 246.81 01-APR-18:10 232.19 01-APR-07:10 0.00 0.00 0.00 0.00 25.38 21-APR-14:00 58.82 12-APR-06:00
May 0.00 01-MAY-00:10 246.81 01-MAY-19:10 232.19 01-MAY-06:10 0.00 0.00 0.00 0.00 33.38 21-MAY-14:00 42.87 02-MAY-06:00
June 0.00 01-JUN-00:10 246.81 01-JUN-19:10 232.19 01-JUN-06:10 0.00 0.00 0.00 0.00 43.93 02-JUN-16:00 25.64 13-JUN-05:00
July 0.00 01-JUL-00:10 246.81 01-JUL-18:10 232.19 01-JUL-07:10 0.00 0.00 0.00 0.00 42.40 02-JUL-16:00 16.92 05-JUL-06:00
August 0.00 01-AUG-00:10 246.81 01-AUG-19:10 232.19 01-AUG-06:10 0.00 0.00 0.00 0.00 39.41 07-AUG-16:00 20.33 31-AUG-06:00
September 0.00 01-SEP-00:10 246.81 01-SEP-19:10 232.19 01-SEP-06:10 0.00 0.00 0.00 0.00 30.25 19-SEP-14:00 47.02 30-SEP-06:00
October 0.00 01-OCT-00:10 246.81 01-OCT-18:10 232.19 01-OCT-07:10 0.00 0.00 0.00 0.00 27.24 01-OCT-15:00 51.62 11-OCT-06:00
November 0.00 01-NOV-00:10 246.81 01-NOV-19:10 232.19 01-NOV-06:10 0.00 0.00 0.00 0.00 1.55 08-NOV-15:00 72.03 17-NOV-04:00
December 0.00 01-DEC-00:10 246.81 01-DEC-20:10 232.19 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 81.07 19-DEC-04:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 0.00   246.81   232.19   0.00 0.00 0.00 0.00 0.00   16.92  
Maximum of Months 0.00   246.81   232.19   0.00 0.00 0.00 0.00 43.93   85.08  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 246.88 01-JAN-19:10 232.26 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 83.95 27-JAN-07:00
February 180.00 01-FEB-00:10 246.88 01-FEB-20:10 232.26 01-FEB-07:10 0.00 0.00 0.00 0.00 5.87 20-FEB-16:07 88.20 03-FEB-07:00
March 180.00 01-MAR-00:10 246.88 01-MAR-20:10 232.26 01-MAR-07:10 0.00 0.00 0.00 0.00 11.31 21-MAR-16:00 83.00 02-MAR-05:00
April 180.00 01-APR-00:10 246.88 01-APR-18:10 232.26 01-APR-07:10 0.00 0.00 0.00 0.00 31.23 21-APR-15:10 56.65 12-APR-06:00
May 180.00 01-MAY-00:10 246.88 01-MAY-19:10 232.26 01-MAY-06:10 0.00 0.00 0.00 0.00 39.62 19-MAY-16:00 36.51 02-MAY-06:00
June 180.00 01-JUN-00:10 246.88 01-JUN-19:10 232.26 01-JUN-06:10 0.00 0.00 0.00 0.00 50.23 02-JUN-16:00 18.84 13-JUN-05:00
July 180.00 01-JUL-00:10 246.88 01-JUL-18:10 232.26 01-JUL-07:10 0.00 0.00 0.00 0.00 48.73 02-JUL-16:00 10.20 05-JUL-06:00
August 180.00 01-AUG-00:10 246.88 01-AUG-19:10 232.26 01-AUG-06:10 0.00 0.00 0.00 0.00 45.75 07-AUG-16:00 13.67 31-AUG-06:00
September 180.00 01-SEP-00:10 246.88 01-SEP-19:10 232.26 01-SEP-06:10 0.00 0.00 0.00 0.00 36.60 19-SEP-16:00 40.28 30-SEP-06:00
October 180.00 01-OCT-00:10 246.88 01-OCT-18:10 232.26 01-OCT-07:10 0.00 0.00 0.00 0.00 33.17 01-OCT-15:07 45.81 25-OCT-06:00
November 180.00 01-NOV-00:10 246.88 01-NOV-19:10 232.26 01-NOV-06:10 0.00 0.00 0.00 0.00 8.16 03-NOV-16:00 71.23 28-NOV-05:00
December 180.00 01-DEC-00:10 246.88 01-DEC-20:10 232.26 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 84.27 27-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   246.88   232.26   0.00 0.00 0.00 0.00 0.00   10.20  
Maximum of Months 180.00   246.88   232.26   0.00 0.00 0.00 0.00 50.23   88.20  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 392.73 01-JAN-19:10 237.06 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 300.80 27-JAN-07:00
February 180.00 01-FEB-00:10 392.73 01-FEB-20:10 237.06 01-FEB-07:10 0.00 0.00 0.00 0.00 21.04 20-FEB-16:09 316.01 03-FEB-07:00
March 180.00 01-MAR-00:10 392.73 01-MAR-20:10 237.06 01-MAR-07:10 0.00 0.00 0.00 0.00 40.51 21-MAR-16:00 297.41 02-MAR-06:00
April 180.00 01-APR-00:10 392.73 01-APR-18:10 237.06 01-APR-07:10 0.00 0.00 0.00 0.00 111.91 21-APR-15:10 202.97 12-APR-06:00
May 180.00 01-MAY-00:10 392.73 01-MAY-19:10 237.06 01-MAY-06:10 0.00 0.00 0.00 0.00 141.95 19-MAY-16:00 130.81 02-MAY-06:00
June 180.00 01-JUN-00:10 392.73 01-JUN-19:10 237.06 01-JUN-06:10 0.00 0.00 0.00 0.00 179.98 02-JUN-16:00 67.52 13-JUN-05:00
July 180.00 01-JUL-00:10 392.73 01-JUL-18:10 237.06 01-JUL-07:10 0.00 0.00 0.00 0.00 174.59 02-JUL-16:00 37.44 05-JUL-07:10
August 180.00 01-AUG-00:10 392.73 01-AUG-19:10 237.06 01-AUG-06:10 0.00 0.00 0.00 0.00 163.94 07-AUG-16:00 50.74 30-AUG-07:10
September 180.00 01-SEP-00:10 392.73 01-SEP-19:10 237.06 01-SEP-06:10 0.00 0.00 0.00 0.00 131.13 19-SEP-16:00 144.33 30-SEP-06:00
October 180.00 01-OCT-00:10 392.73 01-OCT-18:10 237.06 01-OCT-07:10 0.00 0.00 0.00 0.00 118.83 01-OCT-15:07 164.13 25-OCT-06:00
November 180.00 01-NOV-00:10 392.73 01-NOV-19:10 237.06 01-NOV-06:10 0.00 0.00 0.00 0.00 29.22 03-NOV-16:00 255.22 28-NOV-05:00
December 180.00 01-DEC-00:10 392.73 01-DEC-20:10 237.06 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 301.94 27-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   392.73   237.06   0.00 0.00 0.00 0.00 0.00   37.44  
Maximum of Months 180.00   392.73   237.06   0.00 0.00 0.00 0.00 179.98   316.01  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 392.68 01-JAN-19:10 237.03 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 300.79 27-JAN-07:00
February 180.00 01-FEB-00:10 392.68 01-FEB-20:10 237.03 01-FEB-07:10 0.00 0.00 0.00 0.00 21.04 20-FEB-16:07 316.00 03-FEB-07:00
March 180.00 01-MAR-00:10 392.68 01-MAR-20:10 237.03 01-MAR-07:10 0.00 0.00 0.00 0.00 40.51 21-MAR-16:00 297.39 02-MAR-05:20
April 180.00 01-APR-00:10 392.68 01-APR-18:10 237.03 01-APR-07:10 0.00 0.00 0.00 0.00 111.90 21-APR-15:10 202.95 12-APR-06:00
May 180.00 01-MAY-00:10 392.68 01-MAY-19:10 237.03 01-MAY-06:10 0.00 0.00 0.00 0.00 141.96 19-MAY-16:00 130.80 02-MAY-06:00
June 180.00 01-JUN-00:10 392.68 01-JUN-19:10 237.03 01-JUN-06:10 0.00 0.00 0.00 0.00 179.97 02-JUN-16:00 67.51 13-JUN-05:00
July 180.00 01-JUL-00:10 392.68 01-JUL-18:10 237.03 01-JUL-07:10 0.00 0.00 0.00 0.00 174.58 02-JUL-16:00 38.01 05-JUL-07:10
August 180.00 01-AUG-00:10 392.68 01-AUG-19:10 237.03 01-AUG-06:10 0.00 0.00 0.00 0.00 163.93 07-AUG-16:00 49.90 30-AUG-07:10
September 180.00 01-SEP-00:10 392.68 01-SEP-19:10 237.03 01-SEP-06:10 0.00 0.00 0.00 0.00 131.13 19-SEP-16:00 144.31 30-SEP-06:00
October 180.00 01-OCT-00:10 392.68 01-OCT-18:10 237.03 01-OCT-07:10 0.00 0.00 0.00 0.00 118.83 01-OCT-15:10 164.12 25-OCT-06:00
November 180.00 01-NOV-00:10 392.68 01-NOV-19:10 237.03 01-NOV-06:10 0.00 0.00 0.00 0.00 29.22 03-NOV-16:00 255.20 28-NOV-05:00
December 180.00 01-DEC-00:10 392.68 01-DEC-20:10 237.03 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 301.91 27-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   392.68   237.03   0.00 0.00 0.00 0.00 0.00   38.01  
Maximum of Months 180.00   392.68   237.03   0.00 0.00 0.00 0.00 179.97   316.00  



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2263.36 02-JAN-00:10 1282.60 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 362.20 27-JAN-07:00
February 2263.36 01-FEB-00:10 1282.60 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 27.90 20-FEB-16:00 380.57 03-FEB-07:00
March 2263.36 01-MAR-00:10 1282.60 01-MAR-20:10 0.00 0.00 0.00 0.00 0.00 50.05 21-MAR-16:00 358.08 02-MAR-05:10
April 2263.36 01-APR-00:10 1282.60 03-APR-19:10 0.00 0.00 0.00 0.00 0.00 134.09 21-APR-14:00 243.94 12-APR-06:00
May 2263.36 01-MAY-00:10 1282.60 01-MAY-19:10 0.00 0.00 0.00 0.00 0.00 164.98 19-MAY-14:00 156.69 02-MAY-06:00
June 2263.36 01-JUN-00:10 1282.60 01-JUN-19:10 0.00 0.00 0.00 0.00 0.00 208.58 02-JUN-16:00 91.26 13-JUN-05:00
July 2263.36 01-JUL-00:10 1282.60 03-JUL-19:10 0.00 0.00 0.00 0.00 0.00 202.81 02-JUL-16:00 51.66 05-JUL-06:00
August 2263.36 01-AUG-00:10 1282.60 01-AUG-19:10 0.00 0.00 0.00 0.00 0.00 186.28 07-AUG-16:00 65.63 31-AUG-06:00
September 2263.36 01-SEP-00:10 1282.60 01-SEP-19:10 0.00 0.00 0.00 0.00 0.00 148.94 19-SEP-16:00 175.54 30-SEP-06:00
October 2263.36 01-OCT-23:10 1282.60 02-OCT-19:10 0.00 0.00 0.00 0.00 0.00 139.39 01-OCT-15:00 196.97 25-OCT-06:00
November 2263.36 01-NOV-00:10 1282.60 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 35.00 08-NOV-15:00 307.05 28-NOV-05:00
December 2263.36 01-DEC-00:10 1282.60 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 363.56 27-DEC-07:00
                           
Annual Sum or Average         0.00 0.00 0.00 0.00 0.00        
Minimum of Months 2263.36   1282.60   0.00 0.00 0.00 0.00 0.00 0.00   51.66  
Maximum of Months 2263.36   1282.60   0.00 0.00 0.00 0.00 0.00 208.58   380.57  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 392.73 01-JAN-19:10 237.06 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 301.57 27-JAN-07:00
February 180.00 01-FEB-00:10 392.73 01-FEB-20:10 237.06 01-FEB-07:10 0.00 0.00 0.00 0.00 20.40 20-FEB-16:06 316.79 03-FEB-07:00
March 180.00 01-MAR-00:10 392.73 01-MAR-20:10 237.06 01-MAR-07:10 0.00 0.00 0.00 0.00 39.89 21-MAR-16:00 298.18 02-MAR-06:00
April 180.00 01-APR-00:10 392.73 01-APR-18:10 237.06 01-APR-07:10 0.00 0.00 0.00 0.00 111.32 21-APR-15:07 203.69 12-APR-06:00
May 180.00 01-MAY-00:10 392.73 01-MAY-19:10 237.06 01-MAY-06:10 0.00 0.00 0.00 0.00 141.36 19-MAY-16:00 131.49 02-MAY-06:00
June 180.00 01-JUN-00:10 392.73 01-JUN-19:10 237.06 01-JUN-06:10 0.00 0.00 0.00 0.00 179.42 02-JUN-16:00 68.18 13-JUN-05:00
July 180.00 01-JUL-00:10 392.73 01-JUL-18:10 237.06 01-JUL-07:10 0.00 0.00 0.00 0.00 173.85 02-JUL-16:00 37.21 05-JUL-06:00
August 180.00 01-AUG-00:10 392.73 01-AUG-19:10 237.06 01-AUG-06:10 0.00 0.00 0.00 0.00 163.30 07-AUG-16:00 49.63 31-AUG-06:00
September 180.00 01-SEP-00:10 392.73 01-SEP-19:10 237.06 01-SEP-06:10 0.00 0.00 0.00 0.00 126.88 19-SEP-16:00 145.02 30-SEP-06:00
October 180.00 01-OCT-00:10 392.73 01-OCT-18:10 237.06 01-OCT-07:10 0.00 0.00 0.00 0.00 118.24 01-OCT-15:10 164.84 25-OCT-06:00
November 180.00 01-NOV-00:10 392.73 01-NOV-19:10 237.06 01-NOV-06:10 0.00 0.00 0.00 0.00 28.59 03-NOV-16:00 255.96 28-NOV-05:00
December 180.00 01-DEC-00:10 392.73 01-DEC-20:10 237.06 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 302.71 27-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   392.73   237.06   0.00 0.00 0.00 0.00 0.00   37.21  
Maximum of Months 180.00   392.73   237.06   0.00 0.00 0.00 0.00 179.42   316.79  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 392.68 01-JAN-19:10 237.03 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 301.55 27-JAN-07:00
February 180.00 01-FEB-00:10 392.68 01-FEB-20:10 237.03 01-FEB-07:10 0.00 0.00 0.00 0.00 20.40 20-FEB-16:09 316.77 03-FEB-07:00
March 180.00 01-MAR-00:10 392.68 01-MAR-20:10 237.03 01-MAR-07:10 0.00 0.00 0.00 0.00 39.89 21-MAR-16:00 298.16 02-MAR-05:00
April 180.00 01-APR-00:10 392.68 01-APR-18:10 237.03 01-APR-07:10 0.00 0.00 0.00 0.00 111.31 21-APR-15:06 203.67 12-APR-06:00
May 180.00 01-MAY-00:10 392.68 01-MAY-19:10 237.03 01-MAY-06:10 0.00 0.00 0.00 0.00 141.36 19-MAY-16:00 131.48 02-MAY-06:00
June 180.00 01-JUN-00:10 392.68 01-JUN-19:10 237.03 01-JUN-06:10 0.00 0.00 0.00 0.00 179.41 02-JUN-16:00 68.18 13-JUN-05:00
July 180.00 01-JUL-00:10 392.68 01-JUL-18:10 237.03 01-JUL-07:10 0.00 0.00 0.00 0.00 173.78 02-JUL-16:00 37.20 05-JUL-06:00
August 180.00 01-AUG-00:10 392.68 01-AUG-19:10 237.03 01-AUG-06:10 0.00 0.00 0.00 0.00 163.31 07-AUG-16:00 49.63 31-AUG-06:00
September 180.00 01-SEP-00:10 392.68 01-SEP-19:10 237.03 01-SEP-06:10 0.00 0.00 0.00 0.00 130.51 19-SEP-16:00 145.01 30-SEP-06:00
October 180.00 01-OCT-00:10 392.68 01-OCT-18:10 237.03 01-OCT-07:10 0.00 0.00 0.00 0.00 118.23 01-OCT-15:07 164.83 25-OCT-06:00
November 180.00 01-NOV-00:10 392.68 01-NOV-19:10 237.03 01-NOV-06:10 0.00 0.00 0.00 0.00 28.59 03-NOV-16:00 255.95 28-NOV-05:00
December 180.00 01-DEC-00:10 392.68 01-DEC-20:10 237.03 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 302.68 27-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   392.68   237.03   0.00 0.00 0.00 0.00 0.00   37.20  
Maximum of Months 180.00   392.68   237.03   0.00 0.00 0.00 0.00 179.41   316.77  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 246.88 01-JAN-19:10 232.26 01-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 154.29 27-JAN-07:00
February 180.00 01-FEB-00:10 246.88 01-FEB-20:10 232.26 01-FEB-07:10 0.00 0.00 0.00 0.00 10.44 20-FEB-16:09 162.08 03-FEB-07:00
March 180.00 01-MAR-00:10 246.88 01-MAR-20:10 232.26 01-MAR-07:10 0.00 0.00 0.00 0.00 20.41 21-MAR-16:00 152.56 02-MAR-06:00
April 180.00 01-APR-00:10 246.88 01-APR-18:10 232.26 01-APR-07:10 0.00 0.00 0.00 0.00 56.95 21-APR-15:07 104.21 12-APR-06:00
May 180.00 01-MAY-00:10 246.88 01-MAY-19:10 232.26 01-MAY-06:10 0.00 0.00 0.00 0.00 72.34 19-MAY-16:00 67.28 02-MAY-06:00
June 180.00 01-JUN-00:10 246.88 01-JUN-19:10 232.26 01-JUN-06:10 0.00 0.00 0.00 0.00 91.80 02-JUN-16:00 34.88 13-JUN-05:00
July 180.00 01-JUL-00:10 246.88 01-JUL-18:10 232.26 01-JUL-07:10 0.00 0.00 0.00 0.00 89.03 02-JUL-16:00 19.04 05-JUL-06:00
August 180.00 01-AUG-00:10 246.88 01-AUG-19:10 232.26 01-AUG-06:10 0.00 0.00 0.00 0.00 83.58 07-AUG-16:00 25.39 31-AUG-06:00
September 180.00 01-SEP-00:10 246.88 01-SEP-19:10 232.26 01-SEP-06:10 0.00 0.00 0.00 0.00 66.40 19-SEP-16:00 74.20 30-SEP-06:00
October 180.00 01-OCT-00:10 246.88 01-OCT-18:10 232.26 01-OCT-07:10 0.00 0.00 0.00 0.00 60.49 01-OCT-15:10 84.34 25-OCT-06:00
November 180.00 01-NOV-00:10 246.88 01-NOV-19:10 232.26 01-NOV-06:10 0.00 0.00 0.00 0.00 14.62 03-NOV-16:00 130.96 28-NOV-05:00
December 180.00 01-DEC-00:10 246.88 01-DEC-20:10 232.26 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 154.87 27-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   246.88   232.26   0.00 0.00 0.00 0.00 0.00   19.04  
Maximum of Months 180.00   246.88   232.26   0.00 0.00 0.00 0.00 91.80   162.08  



Table of Contents

Report: PeakSpaceGainsMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 26988.77 02-JAN-00:10 3823.39 02-JAN-20:10 6747.90 01-JAN-07:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 733.38 27-JAN-07:00
February 26988.77 01-FEB-00:10 3823.39 01-FEB-20:10 6747.90 01-FEB-07:10 0.00 0.00 0.00 0.00 57.51 20-FEB-15:20 770.65 03-FEB-07:00
March 26988.77 01-MAR-00:10 3823.39 01-MAR-20:10 6747.90 01-MAR-07:10 0.00 0.00 0.00 0.00 99.71 22-MAR-13:00 728.27 02-MAR-05:20
April 26988.77 01-APR-00:10 3823.39 03-APR-19:10 6747.90 01-APR-06:10 0.00 0.00 0.00 0.00 276.90 21-APR-14:00 505.85 12-APR-06:00
May 26988.77 01-MAY-00:10 3823.39 01-MAY-19:10 6747.90 01-MAY-06:10 0.00 0.00 0.00 0.00 341.62 19-MAY-14:00 339.24 02-MAY-06:00
June 26988.77 01-JUN-00:10 3823.39 01-JUN-19:10 6747.90 01-JUN-06:10 0.00 0.00 0.00 0.00 428.46 02-JUN-16:30 198.26 13-JUN-05:00
July 26988.77 01-JUL-00:10 3823.39 03-JUL-19:10 6747.90 01-JUL-06:10 0.00 0.00 0.00 0.00 426.09 02-JUL-16:00 118.22 05-JUL-06:00
August 26988.77 01-AUG-00:10 3823.39 01-AUG-19:10 6747.90 01-AUG-06:10 0.00 0.00 0.00 0.00 386.19 07-AUG-16:00 152.23 16-AUG-22:53
September 26988.77 01-SEP-00:10 3823.39 01-SEP-19:10 6747.90 01-SEP-06:10 0.00 0.00 0.00 0.00 316.82 19-SEP-14:00 370.16 30-SEP-06:00
October 26988.77 01-OCT-23:10 3823.39 02-OCT-19:10 6747.90 01-OCT-06:10 0.00 0.00 0.00 0.00 295.89 01-OCT-15:00 413.13 25-OCT-06:00
November 26988.77 01-NOV-00:10 3823.39 01-NOV-19:10 6747.90 01-NOV-06:10 0.00 0.00 0.00 0.00 72.64 08-NOV-15:00 631.18 27-NOV-23:00
December 26988.77 01-DEC-00:10 3823.39 01-DEC-20:10 6747.90 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 736.19 27-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 26988.77   3823.39   6747.90   0.00 0.00 0.00 0.00 0.00   118.22  
Maximum of Months 26988.77   3823.39   6747.90   0.00 0.00 0.00 0.00 428.46   770.65  



Table of Contents

Report: PeakSpaceGainsMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 26988.77 02-JAN-00:10 3823.39 02-JAN-20:10 6747.90 01-JAN-07:10 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 733.56 27-JAN-07:00
February 26988.77 01-FEB-00:10 3823.39 01-FEB-20:10 6747.90 01-FEB-07:10 0.00 0.00 0.00 0.00 57.63 20-FEB-15:10 770.49 03-FEB-07:00
March 26988.77 01-MAR-00:10 3823.39 01-MAR-20:10 6747.90 01-MAR-07:10 0.00 0.00 0.00 0.00 99.62 22-MAR-13:00 728.94 02-MAR-05:20
April 26988.77 01-APR-00:10 3823.39 03-APR-19:10 6747.90 01-APR-06:10 0.00 0.00 0.00 0.00 274.04 21-APR-14:00 507.39 12-APR-06:00
May 26988.77 01-MAY-00:10 3823.39 01-MAY-19:10 6747.90 01-MAY-06:10 0.00 0.00 0.00 0.00 338.70 19-MAY-14:00 340.96 02-MAY-06:00
June 26988.77 01-JUN-00:10 3823.39 01-JUN-19:10 6747.90 01-JUN-06:10 0.00 0.00 0.00 0.00 426.27 02-JUN-16:30 199.22 13-JUN-05:00
July 26988.77 01-JUL-00:10 3823.39 03-JUL-19:10 6747.90 01-JUL-06:10 0.00 0.00 0.00 0.00 423.77 02-JUL-16:00 119.48 05-JUL-06:00
August 26988.77 01-AUG-00:10 3823.39 01-AUG-19:10 6747.90 01-AUG-06:10 0.00 0.00 0.00 0.00 384.65 07-AUG-16:00 154.73 16-AUG-22:53
September 26988.77 01-SEP-00:10 3823.39 01-SEP-19:10 6747.90 01-SEP-06:10 0.00 0.00 0.00 0.00 314.68 19-SEP-14:00 371.63 30-SEP-06:00
October 26988.77 01-OCT-23:10 3823.39 02-OCT-19:10 6747.90 01-OCT-06:10 0.00 0.00 0.00 0.00 295.78 01-OCT-15:00 414.47 25-OCT-06:00
November 26988.77 01-NOV-00:10 3823.39 01-NOV-19:10 6747.90 01-NOV-06:10 0.00 0.00 0.00 0.00 72.60 08-NOV-15:00 633.79 27-NOV-23:00
December 26988.77 01-DEC-00:10 3823.39 01-DEC-20:10 6747.90 01-DEC-07:10 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 735.93 27-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 26988.77   3823.39   6747.90   0.00 0.00 0.00 0.00 0.00   119.48  
Maximum of Months 26988.77   3823.39   6747.90   0.00 0.00 0.00 0.00 426.27   770.49  



Table of Contents

Report: PeakSpaceGainsMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2401.70 02-JAN-00:10 1020.78 02-JAN-20:10 15112.11 01-JAN-07:10 22492.83 01-JAN-16:10 0.00 0.00 0.00 0.00 01-JAN-00:05 695.06 27-JAN-08:00
February 2401.70 01-FEB-00:10 1020.78 01-FEB-20:10 15112.11 01-FEB-07:10 22492.83 01-FEB-16:10 0.00 0.00 0.00 0.00 01-FEB-00:03 716.01 03-FEB-07:00
March 2401.70 01-MAR-00:10 1020.78 01-MAR-20:10 15112.11 01-MAR-07:10 22492.83 01-MAR-16:10 0.00 0.00 0.00 23.86 22-MAR-13:20 649.37 02-MAR-05:40
April 2401.70 01-APR-00:10 1020.78 03-APR-19:10 15112.11 01-APR-06:10 22492.83 01-APR-15:09 0.00 0.00 0.00 184.88 21-APR-14:00 463.80 12-APR-06:00
May 2401.70 01-MAY-00:10 1020.78 01-MAY-19:10 15112.11 01-MAY-06:10 22492.83 01-MAY-15:09 0.00 0.00 0.00 245.38 21-MAY-14:00 330.52 02-MAY-06:00
June 2401.70 01-JUN-00:10 1020.78 01-JUN-19:10 15112.11 01-JUN-06:10 22492.83 01-JUN-15:09 0.00 0.00 0.00 328.51 02-JUN-16:00 181.15 13-JUN-05:20
July 2401.70 01-JUL-00:10 1020.78 03-JUL-19:10 15112.11 01-JUL-06:10 22492.83 01-JUL-15:09 0.00 0.00 0.00 316.43 02-JUL-16:00 114.27 05-JUL-06:00
August 2401.70 01-AUG-00:10 1020.78 01-AUG-19:10 15112.11 01-AUG-06:10 22492.83 01-AUG-15:09 0.00 0.00 0.00 292.98 07-AUG-16:00 150.12 16-AUG-22:40
September 2401.70 01-SEP-00:10 1020.78 01-SEP-19:10 15112.11 01-SEP-06:10 22492.83 01-SEP-15:09 0.00 0.00 0.00 220.88 19-SEP-14:00 337.07 30-SEP-06:00
October 2401.70 01-OCT-23:10 1020.78 02-OCT-19:10 15112.11 01-OCT-06:10 22492.83 01-OCT-15:09 0.00 0.00 0.00 197.28 01-OCT-15:00 378.27 25-OCT-06:00
November 2401.70 01-NOV-00:10 1020.78 01-NOV-19:10 15112.11 01-NOV-06:10 22492.83 01-NOV-15:09 0.00 0.00 0.00 7.46 08-NOV-15:00 578.37 27-NOV-23:00
December 2401.70 01-DEC-00:10 1020.78 01-DEC-20:10 15112.11 01-DEC-07:10 22492.83 01-DEC-16:10 0.00 0.00 0.00 0.00 01-DEC-00:03 669.87 27-DEC-07:30
                               
Annual Sum or Average                 0.00 0.00 0.00        
Minimum of Months 2401.70   1020.78   15112.11   22492.83   0.00 0.00 0.00 0.00   114.27  
Maximum of Months 2401.70   1020.78   15112.11   22492.83   0.00 0.00 0.00 328.51   716.01  



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2395.44 02-JAN-00:10 1357.44 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 642.51 27-JAN-07:00
February 2395.44 01-FEB-00:10 1357.44 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 50.44 20-FEB-16:00 675.02 03-FEB-07:00
March 2395.44 01-MAR-00:10 1357.44 01-MAR-20:10 0.00 0.00 0.00 0.00 0.00 87.82 21-MAR-16:00 635.24 02-MAR-05:50
April 2395.44 01-APR-00:10 1357.44 03-APR-19:10 0.00 0.00 0.00 0.00 0.00 236.94 21-APR-15:00 433.12 12-APR-06:00
May 2395.44 01-MAY-00:10 1357.44 01-MAY-19:10 0.00 0.00 0.00 0.00 0.00 295.16 19-MAY-16:00 278.74 02-MAY-06:00
June 2395.44 01-JUN-00:10 1357.44 01-JUN-19:10 0.00 0.00 0.00 0.00 0.00 369.97 02-JUN-16:40 143.34 13-JUN-05:00
July 2395.44 01-JUL-00:10 1357.44 03-JUL-19:10 0.00 0.00 0.00 0.00 0.00 356.71 01-JUL-17:00 77.04 05-JUL-06:00
August 2395.44 01-AUG-00:10 1357.44 01-AUG-19:10 0.00 0.00 0.00 0.00 0.00 328.55 07-AUG-16:00 103.62 31-AUG-06:00
September 2395.44 01-SEP-00:10 1357.44 01-SEP-19:10 0.00 0.00 0.00 0.00 0.00 265.53 19-SEP-16:00 307.66 30-SEP-06:00
October 2395.44 01-OCT-23:10 1357.44 02-OCT-19:10 0.00 0.00 0.00 0.00 0.00 243.30 01-OCT-15:00 350.00 25-OCT-06:00
November 2395.44 01-NOV-00:10 1357.44 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 63.67 08-NOV-15:00 544.87 28-NOV-05:00
December 2395.44 01-DEC-00:10 1357.44 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:03 643.62 27-DEC-07:00
                           
Annual Sum or Average         0.00 0.00 0.00 0.00 0.00        
Minimum of Months 2395.44   1357.44   0.00 0.00 0.00 0.00 0.00 0.00   77.04  
Maximum of Months 2395.44   1357.44   0.00 0.00 0.00 0.00 0.00 369.97   675.02  



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 19555.90 12-JAN-19:10 53675.50 72090.20 57488.97 0.00 0.00 0.00 0.00 0.00 0.00
February 18758.35 22-FEB-20:10 8945.92 13517.00 10113.80 0.00 0.00 0.00 0.00 0.00 0.00
March 17799.84 01-MAR-21:00 8945.92 13517.00 10113.80 0.00 0.00 0.00 0.00 0.00 0.00
April 18271.64 07-APR-20:00 8945.92 13517.00 10113.80 0.00 0.00 0.00 0.00 0.00 0.00
May 19358.14 11-MAY-20:00 8945.92 13517.00 10113.80 0.00 0.00 0.00 0.00 0.00 0.00
June 20361.87 08-JUN-20:00 8945.92 13517.00 10113.80 0.00 0.00 0.00 0.00 0.00 0.00
July 22386.27 26-JUL-18:50 8945.92 12015.03 9581.50 0.00 0.00 0.00 0.00 0.00 0.00
August 23534.96 07-AUG-18:10 53675.50 72090.20 57488.97 0.00 0.00 0.00 0.00 0.00 0.00
September 23757.44 17-SEP-10:35 7667.93 9011.45 8516.89 0.00 0.00 0.00 0.00 0.00 0.00
October 23308.91 01-OCT-10:35 7667.93 9011.45 8516.89 0.00 0.00 0.00 0.00 0.00 0.00
November 21752.54 09-NOV-19:10 62621.41 84105.23 67070.47 0.00 0.00 0.00 0.00 0.00 0.00
December 20408.78 01-DEC-21:00 8945.92 13517.00 10113.80 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 17799.84   7667.93 9011.45 8516.89 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 23757.44   62621.41 84105.23 67070.47 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 3022.90 01-JAN-11:35 779.69 458.20 577.35 0.00 0.00 0.00 0.00 0.00 153.21
February 3122.37 07-FEB-11:35 519.79 381.83 505.18 0.00 0.00 0.00 0.00 0.00 41.65
March 2938.03 05-MAR-11:35 779.69 458.20 577.35 0.00 0.00 0.00 0.00 0.00 85.67
April 2815.06 04-APR-10:35 519.79 381.83 505.18 0.00 0.00 0.00 0.00 35.87 0.00
May 3042.50 31-MAY-18:02 5457.82 3665.58 3897.11 0.00 0.00 0.00 0.00 177.89 0.00
June 3338.82 15-JUN-18:10 5457.82 3665.58 3897.11 0.00 0.00 0.00 0.00 257.78 0.00
July 3323.83 26-JUL-18:10 5457.82 3665.58 3897.11 0.00 0.00 0.00 0.00 223.27 0.00
August 3369.31 27-AUG-10:35 779.69 458.20 577.35 0.00 0.00 0.00 0.00 191.49 0.00
September 3489.09 17-SEP-10:35 779.69 458.20 577.35 0.00 0.00 0.00 0.00 140.68 0.00
October 3559.87 05-OCT-10:35 519.79 381.83 505.18 0.00 0.00 0.00 0.00 100.09 0.00
November 3458.94 10-NOV-11:35 519.79 381.83 505.18 0.00 0.00 0.00 0.00 0.00 29.85
December 2909.21 09-DEC-11:40 389.84 190.92 252.59 0.00 0.00 0.00 0.00 0.00 101.52
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2815.06   389.84 190.92 252.59 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3559.87   5457.82 3665.58 3897.11 0.00 0.00 0.00 0.00 257.78 153.21



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1847.61 12-JAN-21:00 1053.36 795.89 793.93 0.00 0.00 0.00 0.00 0.00 62.31
February 1916.25 21-FEB-21:00 1053.36 795.89 793.93 0.00 0.00 0.00 0.00 0.00 46.32
March 2002.14 16-MAR-18:01 7373.52 4952.21 5265.02 0.00 0.00 0.00 0.00 0.00 8.46
April 2217.48 19-APR-18:10 7373.52 4952.21 5265.02 0.00 0.00 0.00 0.00 61.37 0.00
May 2302.72 31-MAY-18:10 6320.16 4244.75 4512.87 0.00 0.00 0.00 0.00 67.92 0.00
June 2435.52 15-JUN-18:10 6320.16 4244.75 4512.87 0.00 0.00 0.00 0.00 99.56 0.00
July 2419.51 26-JUL-18:10 6320.16 4244.75 4512.87 0.00 0.00 0.00 0.00 86.35 0.00
August 2399.11 07-AUG-18:10 6320.16 4244.75 4512.87 0.00 0.00 0.00 0.00 87.30 0.00
September 2311.02 20-SEP-18:10 6320.16 4244.75 4512.87 0.00 0.00 0.00 0.00 68.06 0.00
October 2238.59 05-OCT-18:10 7373.52 4952.21 5265.02 0.00 0.00 0.00 0.00 41.99 0.00
November 2021.03 09-NOV-19:10 7373.52 4952.21 5265.02 0.00 0.00 0.00 0.00 0.00 3.69
December 1818.49 15-DEC-21:00 1053.36 795.89 793.93 0.00 0.00 0.00 0.00 0.00 49.22
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1818.49   1053.36 795.89 793.93 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 2435.52   7373.52 4952.21 5265.02 0.00 0.00 0.00 0.00 99.56 62.31



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1563.50 03-JAN-21:00 222.77 1487.69 839.45 0.00 0.00 0.00 0.00 0.00 113.59
February 1778.86 07-FEB-20:50 222.77 1487.69 839.45 0.00 0.00 0.00 0.00 0.00 88.97
March 1965.52 16-MAR-20:00 222.77 1487.69 839.45 0.00 0.00 0.00 0.00 0.00 64.92
April 2228.19 19-APR-19:10 445.54 2975.37 1678.89 0.00 0.00 0.00 0.00 134.08 0.00
May 2442.52 31-MAY-18:10 1336.61 7934.32 4771.59 0.00 0.00 0.00 0.00 161.65 0.00
June 2587.17 15-JUN-18:10 1336.61 7934.32 4771.59 0.00 0.00 0.00 0.00 236.30 0.00
July 2596.05 03-JUL-18:10 1336.61 7934.32 4771.59 0.00 0.00 0.00 0.00 242.20 0.00
August 2526.66 07-AUG-18:10 1336.61 7934.32 4771.59 0.00 0.00 0.00 0.00 208.34 0.00
September 2395.61 20-SEP-18:02 1336.61 7934.32 4771.59 0.00 0.00 0.00 0.00 164.07 0.00
October 2288.28 05-OCT-18:20 445.54 2644.77 1590.53 0.00 0.00 0.00 0.00 91.26 0.00
November 1986.67 09-NOV-21:00 222.77 1487.69 839.45 0.00 0.00 0.00 0.00 0.00 17.36
December 1480.93 15-DEC-21:00 222.77 1487.69 839.45 0.00 0.00 0.00 0.00 0.00 114.07
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1480.93   222.77 1487.69 839.45 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 2596.05   1336.61 7934.32 4771.59 0.00 0.00 0.00 0.00 242.20 114.07



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 482.31 03-JAN-21:10 195.84 242.76 229.41 0.00 0.00 0.00 0.00 0.00 68.24
February 603.96 07-FEB-22:00 195.84 242.76 229.41 0.00 0.00 0.00 0.00 0.00 59.20
March 720.48 15-MAR-21:00 195.84 242.76 229.41 0.00 0.00 0.00 0.00 0.00 9.78
April 1023.00 21-APR-20:00 171.36 273.10 242.16 0.00 0.00 0.00 0.00 48.44 0.00
May 1151.80 31-MAY-19:10 342.72 546.20 484.31 0.00 0.00 0.00 0.00 84.22 0.00
June 1284.12 15-JUN-18:10 1028.16 1456.53 1376.47 0.00 0.00 0.00 0.00 137.62 0.00
July 1284.44 03-JUL-18:10 1028.16 1456.53 1376.47 0.00 0.00 0.00 0.00 141.26 0.00
August 1231.30 07-AUG-18:20 342.72 485.51 458.82 0.00 0.00 0.00 0.00 117.10 0.00
September 1092.51 21-SEP-20:00 171.36 273.10 242.16 0.00 0.00 0.00 0.00 44.15 0.00
October 1026.04 05-OCT-20:00 171.36 273.10 242.16 0.00 0.00 0.00 0.00 27.97 0.00
November 752.97 09-NOV-22:00 195.84 242.76 229.41 0.00 0.00 0.00 0.00 0.00 20.58
December 458.27 15-DEC-22:00 195.84 242.76 229.41 0.00 0.00 0.00 0.00 0.00 65.81
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 458.27   171.36 242.76 229.41 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 1284.44   1028.16 1456.53 1376.47 0.00 0.00 0.00 0.00 141.26 68.24



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 35924.14 03-JAN-21:00 705.60 337.37 4572.80 39726.58 0.00 0.00 0.00 0.00 225.52
February 36275.22 21-FEB-21:00 705.60 337.37 4572.80 39726.58 0.00 0.00 0.00 0.00 212.38
March 36418.54 21-MAR-20:00 705.60 337.37 4572.80 39726.58 0.00 0.00 0.00 0.00 169.37
April 37455.04 19-APR-20:00 705.60 337.37 4572.80 39726.58 0.00 0.00 0.00 103.77 0.00
May 37787.26 31-MAY-20:00 705.60 337.37 4572.80 39726.58 0.00 0.00 0.00 130.74 0.00
June 38342.34 15-JUN-20:00 705.60 337.37 4572.80 39726.58 0.00 0.00 0.00 228.89 0.00
July 38198.40 26-JUL-20:00 705.60 337.37 4572.80 39726.58 0.00 0.00 0.00 132.92 0.00
August 38120.41 07-AUG-20:00 705.60 337.37 4572.80 39726.58 0.00 0.00 0.00 183.34 0.00
September 37647.42 20-SEP-20:00 705.60 337.37 4572.80 39726.58 0.00 0.00 0.00 44.03 0.00
October 37405.15 05-OCT-20:00 705.60 337.37 4572.80 39726.58 0.00 0.00 0.00 4.37 0.00
November 36481.70 09-NOV-21:00 705.60 337.37 4572.80 39726.58 0.00 0.00 0.00 0.00 91.31
December 35799.25 15-DEC-21:00 705.60 337.37 4572.80 39726.58 0.00 0.00 0.00 0.00 226.50
                       
Annual Sum or Average             0.00 0.00 0.00    
Minimum of Months 35799.25   705.60 337.37 4572.80 39726.58 0.00 0.00 0.00 0.00 0.00
Maximum of Months 38342.34   705.60 337.37 4572.80 39726.58 0.00 0.00 0.00 228.89 226.50



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 12726.90 01-JAN-11:35 10245.60 1451.48 812.86 0.00 0.00 0.00 0.00 0.00 335.36
February 13089.37 19-FEB-11:35 10245.60 1451.48 812.86 0.00 0.00 0.00 0.00 0.00 105.62
March 12405.00 05-MAR-11:35 10245.60 1451.48 812.86 0.00 0.00 0.00 0.00 0.00 187.03
April 12875.44 19-APR-18:03 83672.40 13547.18 6401.28 0.00 0.00 0.00 0.00 352.93 0.00
May 13365.11 31-MAY-18:10 71719.20 11611.87 5486.82 0.00 0.00 0.00 0.00 390.38 0.00
June 14106.58 14-JUN-18:10 71719.20 11611.87 5486.82 0.00 0.00 0.00 0.00 613.64 0.00
July 14111.07 03-JUL-18:10 71719.20 11611.87 5486.82 0.00 0.00 0.00 0.00 587.75 0.00
August 14049.84 07-AUG-18:10 71719.20 11611.87 5486.82 0.00 0.00 0.00 0.00 498.76 0.00
September 14200.35 17-SEP-10:35 10245.60 1451.48 812.86 0.00 0.00 0.00 0.00 325.62 0.00
October 14157.01 22-OCT-10:35 10245.60 1451.48 812.86 0.00 0.00 0.00 0.00 18.16 0.00
November 13773.93 11-NOV-11:35 10245.60 1451.48 812.86 0.00 0.00 0.00 0.00 0.00 219.33
December 12324.52 10-DEC-11:35 10245.60 1451.48 812.86 0.00 0.00 0.00 0.00 0.00 235.07
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 12324.52   10245.60 1451.48 812.86 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 14200.35   83672.40 13547.18 6401.28 0.00 0.00 0.00 0.00 613.64 335.36



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 37038.98 12-JAN-19:10 212907.24 63196.36 57008.13 0.00 0.00 0.00 0.00 0.00 724.64
February 37963.05 22-FEB-19:03 212907.24 63196.36 57008.13 0.00 0.00 0.00 0.00 0.00 384.03
March 39314.42 16-MAR-18:10 248391.78 73729.08 66509.49 0.00 0.00 0.00 0.00 0.00 151.54
April 43050.52 19-APR-18:10 248391.78 73729.08 66509.49 0.00 0.00 0.00 0.00 997.34 0.00
May 44823.93 31-MAY-18:10 212907.24 63196.36 57008.13 0.00 0.00 0.00 0.00 1102.03 0.00
June 46864.58 15-JUN-18:10 212907.24 63196.36 57008.13 0.00 0.00 0.00 0.00 1629.82 0.00
July 46885.37 03-JUL-18:10 212907.24 63196.36 57008.13 0.00 0.00 0.00 0.00 1673.71 0.00
August 46323.01 07-AUG-18:10 212907.24 63196.36 57008.13 0.00 0.00 0.00 0.00 1426.27 0.00
September 44736.94 20-SEP-18:10 212907.24 63196.36 57008.13 0.00 0.00 0.00 0.00 1109.14 0.00
October 43560.26 05-OCT-18:10 248391.78 73729.08 66509.49 0.00 0.00 0.00 0.00 678.18 0.00
November 39725.35 09-NOV-19:10 248391.78 73729.08 66509.49 0.00 0.00 0.00 0.00 0.00 76.74
December 36331.62 15-DEC-21:00 35484.54 11849.32 10029.21 0.00 0.00 0.00 0.00 0.00 832.53
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 36331.62   35484.54 11849.32 10029.21 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 46885.37   248391.78 73729.08 66509.49 0.00 0.00 0.00 0.00 1673.71 832.53



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 3759.58 12-JAN-16:01 680.40 769.75 479.39 0.00 0.00 0.00 0.00 0.00 38.80
February 3836.15 20-FEB-16:01 378.00 907.20 534.70 0.00 0.00 0.00 0.00 7.10 0.00
March 3824.56 16-MAR-15:01 680.40 769.75 479.39 0.00 0.00 0.00 0.00 2.99 0.00
April 3861.25 30-APR-15:01 378.00 907.20 534.70 0.00 0.00 0.00 0.00 79.45 0.00
May 3885.84 20-MAY-15:01 378.00 907.20 534.70 0.00 0.00 0.00 0.00 99.76 0.00
June 3885.67 15-JUN-18:02 831.60 2097.16 774.39 0.00 0.00 0.00 0.00 136.20 0.00
July 3519.24 19-JUL-18:02 831.60 2097.16 774.39 0.00 0.00 0.00 0.00 65.59 0.00
August 3888.00 23-AUG-15:01 680.40 769.75 479.39 0.00 0.00 0.00 0.00 111.01 0.00
September 3887.91 11-SEP-15:01 680.40 769.75 479.39 0.00 0.00 0.00 0.00 71.43 0.00
October 3896.79 01-OCT-15:01 378.00 907.20 534.70 0.00 0.00 0.00 0.00 103.88 0.00
November 3840.31 09-NOV-16:01 680.40 769.75 479.39 0.00 0.00 0.00 0.00 8.31 0.00
December 3706.74 17-DEC-16:01 378.00 907.20 534.70 0.00 0.00 0.00 0.00 0.00 75.79
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 3519.24   378.00 769.75 479.39 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3896.79   831.60 2097.16 774.39 0.00 0.00 0.00 0.00 136.20 75.79



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 3612.50 12-JAN-16:01 680.40 769.66 479.33 0.00 0.00 0.00 0.00 0.00 34.24
February 3759.91 20-FEB-16:01 378.00 907.09 534.64 0.00 0.00 0.00 0.00 8.64 0.00
March 3755.94 16-MAR-15:01 680.40 769.66 479.33 0.00 0.00 0.00 0.00 4.29 0.00
April 3825.68 30-APR-15:01 378.00 907.09 534.64 0.00 0.00 0.00 0.00 79.71 0.00
May 3857.13 20-MAY-15:01 378.00 907.09 534.64 0.00 0.00 0.00 0.00 99.82 0.00
June 3870.47 15-JUN-18:02 831.60 2096.92 774.30 0.00 0.00 0.00 0.00 135.85 0.00
July 3500.64 30-JUL-18:02 702.00 2356.09 774.30 0.00 0.00 0.00 0.00 67.60 0.00
August 3848.93 23-AUG-15:01 680.40 769.66 479.33 0.00 0.00 0.00 0.00 111.37 0.00
September 3834.31 11-SEP-15:01 680.40 769.66 479.33 0.00 0.00 0.00 0.00 72.24 0.00
October 3830.17 01-OCT-15:01 378.00 907.09 534.64 0.00 0.00 0.00 0.00 105.05 0.00
November 3767.81 09-NOV-16:01 680.40 769.66 479.33 0.00 0.00 0.00 0.00 9.72 0.00
December 3460.05 16-DEC-16:02 324.00 777.51 458.26 0.00 0.00 0.00 0.00 0.00 74.55
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 3460.05   324.00 769.66 458.26 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3870.47   831.60 2356.09 774.30 0.00 0.00 0.00 0.00 135.85 74.55



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 609.96 12-JAN-14:30 0.00 69.11 67.08 0.00 0.00 0.00 0.00 0.00 14.57
February 599.57 20-FEB-14:10 0.00 81.45 74.82 0.00 0.00 0.00 0.00 0.00 2.99
March 503.71 16-MAR-13:30 0.00 69.11 67.08 0.00 0.00 0.00 0.00 0.00 2.60
April 492.06 03-APR-14:00 0.00 69.11 67.08 0.00 0.00 0.00 0.00 9.77 0.00
May 512.18 19-MAY-20:20 0.00 219.66 180.59 0.00 0.00 0.00 0.00 21.31 0.00
June 560.98 15-JUN-20:20 0.00 219.66 180.59 0.00 0.00 0.00 0.00 29.55 0.00
July 573.47 02-JUL-20:50 0.00 246.81 180.59 0.00 0.00 0.00 0.00 27.76 0.00
August 577.40 06-AUG-19:05 0.00 493.63 340.55 0.00 0.00 0.00 0.00 32.38 0.00
September 668.56 19-SEP-13:30 0.00 69.11 67.08 0.00 0.00 0.00 0.00 28.72 0.00
October 735.62 22-OCT-13:20 0.00 81.45 74.82 0.00 0.00 0.00 0.00 7.64 0.00
November 683.34 09-NOV-13:50 0.00 69.11 67.08 0.00 0.00 0.00 0.00 0.00 0.48
December 543.88 16-DEC-13:40 0.00 81.45 74.82 0.00 0.00 0.00 0.00 0.00 27.05
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 492.06   0.00 69.11 67.08 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 735.62   0.00 493.63 340.55 0.00 0.00 0.00 0.00 32.38 27.05



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1237.57 13-JAN-19:02 831.60 1318.35 758.70 0.00 0.00 0.00 0.00 0.00 25.19
February 1305.91 20-FEB-16:01 378.00 570.30 523.86 0.00 0.00 0.00 0.00 4.96 0.00
March 1357.97 15-MAR-18:01 970.20 1538.07 885.15 0.00 0.00 0.00 0.00 0.00 1.19
April 1430.39 28-APR-18:01 970.20 1538.07 885.15 0.00 0.00 0.00 0.00 15.70 0.00
May 1438.17 13-MAY-18:01 819.00 1728.17 885.15 0.00 0.00 0.00 0.00 25.09 0.00
June 1437.32 17-JUN-18:02 702.00 1481.29 758.70 0.00 0.00 0.00 0.00 36.49 0.00
July 1335.10 15-JUL-15:02 324.00 488.83 449.03 0.00 0.00 0.00 0.00 29.29 0.00
August 1439.01 27-AUG-18:01 819.00 1728.17 885.15 0.00 0.00 0.00 0.00 30.00 0.00
September 1431.17 17-SEP-18:01 819.00 1728.17 885.15 0.00 0.00 0.00 0.00 21.14 0.00
October 1429.37 01-OCT-18:01 819.00 1728.17 885.15 0.00 0.00 0.00 0.00 20.86 0.00
November 1324.44 08-NOV-19:01 970.20 1538.07 885.15 0.00 0.00 0.00 0.00 0.00 2.16
December 1276.22 09-DEC-09:01 378.00 967.78 1119.99 0.00 0.00 0.00 0.00 0.00 21.76
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1237.57   324.00 488.83 449.03 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 1439.01   970.20 1728.17 1119.99 0.00 0.00 0.00 0.00 36.49 25.19



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 3310.05 12-JAN-16:01 680.40 769.75 479.39 0.00 0.00 0.00 0.00 0.00 38.78
February 3362.24 20-FEB-16:01 378.00 907.20 534.70 0.00 0.00 0.00 0.00 7.72 0.00
March 3360.55 16-MAR-15:01 680.40 769.75 479.39 0.00 0.00 0.00 0.00 3.31 0.00
April 3406.27 21-APR-15:01 680.40 769.75 479.39 0.00 0.00 0.00 0.00 97.91 0.00
May 3437.47 30-MAY-08:61 252.00 1209.60 792.83 0.00 0.00 0.00 0.00 44.17 0.00
June 3453.68 15-JUN-08:61 252.00 1209.60 792.83 0.00 0.00 0.00 0.00 74.07 0.00
July 3199.63 09-JUL-08:61 378.00 1539.49 1143.15 0.00 0.00 0.00 0.00 21.76 0.00
August 3427.25 23-AUG-15:01 680.40 769.75 479.39 0.00 0.00 0.00 0.00 110.96 0.00
September 3409.22 11-SEP-15:01 680.40 769.75 479.39 0.00 0.00 0.00 0.00 72.00 0.00
October 3423.87 01-OCT-15:01 378.00 907.20 534.70 0.00 0.00 0.00 0.00 104.20 0.00
November 3373.31 09-NOV-16:01 680.40 769.75 479.39 0.00 0.00 0.00 0.00 8.68 0.00
December 3288.81 09-DEC-09:01 378.00 1539.49 1143.15 0.00 0.00 0.00 0.00 0.00 86.91
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 3199.63   252.00 769.75 479.39 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3453.68   680.40 1539.49 1143.15 0.00 0.00 0.00 0.00 110.96 86.91



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2270.82 31-JAN-09:02 216.00 1036.68 679.49 0.00 0.00 0.00 0.00 0.00 115.38
February 3276.96 20-FEB-09:01 378.00 1539.31 1143.02 0.00 0.00 0.00 0.00 0.00 123.99
March 3300.11 22-MAR-15:01 680.40 769.66 479.33 0.00 0.00 0.00 0.00 17.04 0.00
April 3370.34 21-APR-15:01 680.40 769.66 479.33 0.00 0.00 0.00 0.00 98.22 0.00
May 3415.24 30-MAY-08:61 252.00 1209.46 792.74 0.00 0.00 0.00 0.00 44.01 0.00
June 3432.35 15-JUN-08:61 252.00 1209.46 792.74 0.00 0.00 0.00 0.00 73.87 0.00
July 3175.56 09-JUL-08:61 378.00 1539.31 1143.02 0.00 0.00 0.00 0.00 21.57 0.00
August 3389.82 23-AUG-15:01 680.40 769.66 479.33 0.00 0.00 0.00 0.00 111.32 0.00
September 3363.17 18-SEP-18:01 970.20 2446.40 903.35 0.00 0.00 0.00 0.00 84.12 0.00
October 3361.38 01-OCT-15:01 378.00 907.09 534.64 0.00 0.00 0.00 0.00 105.41 0.00
November 3265.24 11-NOV-09:01 378.00 1539.31 1143.02 0.00 0.00 0.00 0.00 0.00 118.18
December 3068.81 09-DEC-09:01 378.00 1539.31 1143.02 0.00 0.00 0.00 0.00 0.00 77.66
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2270.82   216.00 769.66 479.33 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3432.35   970.20 2446.40 1143.02 0.00 0.00 0.00 0.00 111.32 123.99



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2019.50 12-JAN-21:10 2011.87 1140.09 0.00 0.00 0.00 0.00 0.00 0.00 116.35
February 2223.02 21-FEB-17:20 1257.42 356.28 0.00 0.00 0.00 0.00 0.00 7.20 0.00
March 2443.30 16-MAR-18:10 12322.72 7980.64 0.00 0.00 0.00 0.00 0.00 0.00 17.26
April 2790.56 30-APR-10:35 1508.90 855.07 0.00 0.00 0.00 0.00 0.00 37.77 0.00
May 2988.55 31-MAY-18:10 10562.33 6840.55 0.00 0.00 0.00 0.00 0.00 114.94 0.00
June 3255.23 15-JUN-18:10 10562.33 6840.55 0.00 0.00 0.00 0.00 0.00 168.91 0.00
July 3202.42 03-JUL-18:10 10562.33 6840.55 0.00 0.00 0.00 0.00 0.00 175.68 0.00
August 3195.71 07-AUG-18:10 10562.33 6840.55 0.00 0.00 0.00 0.00 0.00 147.06 0.00
September 3036.52 20-SEP-18:10 10562.33 6840.55 0.00 0.00 0.00 0.00 0.00 113.94 0.00
October 2919.31 05-OCT-10:35 1005.94 712.56 0.00 0.00 0.00 0.00 0.00 76.59 0.00
November 2532.30 10-NOV-11:35 1005.94 712.56 0.00 0.00 0.00 0.00 0.00 0.00 3.69
December 1917.06 15-DEC-22:03 6790.07 2565.21 0.00 0.00 0.00 0.00 0.00 0.00 89.45
                       
Annual Sum or Average         0.00 0.00 0.00 0.00 0.00    
Minimum of Months 1917.06   1005.94 356.28 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3255.23   12322.72 7980.64 0.00 0.00 0.00 0.00 0.00 175.68 116.35



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 4050.02 12-JAN-16:01 680.40 769.75 479.39 0.00 0.00 0.00 0.00 0.00 39.03
February 4134.16 20-FEB-16:01 378.00 907.20 534.70 0.00 0.00 0.00 0.00 6.80 0.00
March 4127.26 14-MAR-15:01 680.40 769.75 479.39 0.00 0.00 0.00 0.00 16.17 0.00
April 4185.30 30-APR-15:01 378.00 907.20 534.70 0.00 0.00 0.00 0.00 78.51 0.00
May 4206.83 20-MAY-15:01 378.00 907.20 534.70 0.00 0.00 0.00 0.00 98.97 0.00
June 4203.83 15-JUN-15:02 583.20 659.78 410.90 0.00 0.00 0.00 0.00 157.99 0.00
July 3706.06 26-JUL-08:61 252.00 1209.60 792.83 0.00 0.00 0.00 0.00 70.45 0.00
August 4206.00 23-AUG-15:01 680.40 769.75 479.39 0.00 0.00 0.00 0.00 110.31 0.00
September 4210.81 11-SEP-15:01 680.40 769.75 479.39 0.00 0.00 0.00 0.00 70.58 0.00
October 4215.21 01-OCT-15:01 378.00 907.20 534.70 0.00 0.00 0.00 0.00 103.18 0.00
November 4141.38 09-NOV-16:01 680.40 769.75 479.39 0.00 0.00 0.00 0.00 7.93 0.00
December 3980.47 17-DEC-16:01 378.00 907.20 534.70 0.00 0.00 0.00 0.00 0.00 75.60
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 3706.06   252.00 659.78 410.90 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 4215.21   680.40 1209.60 792.83 0.00 0.00 0.00 0.00 157.99 75.60



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 3905.56 12-JAN-16:01 680.40 769.66 479.33 0.00 0.00 0.00 0.00 0.00 35.33
February 4041.96 20-FEB-16:01 378.00 907.09 534.64 0.00 0.00 0.00 0.00 8.51 0.00
March 4036.89 16-MAR-15:01 680.40 769.66 479.33 0.00 0.00 0.00 0.00 4.18 0.00
April 4142.67 30-APR-15:01 378.00 907.09 534.64 0.00 0.00 0.00 0.00 78.77 0.00
May 4171.66 20-MAY-15:01 378.00 907.09 534.64 0.00 0.00 0.00 0.00 99.02 0.00
June 4183.35 15-JUN-18:02 831.60 2096.92 774.30 0.00 0.00 0.00 0.00 135.14 0.00
July 3690.46 26-JUL-08:61 252.00 1209.46 792.74 0.00 0.00 0.00 0.00 70.33 0.00
August 4159.28 23-AUG-15:01 680.40 769.66 479.33 0.00 0.00 0.00 0.00 110.67 0.00
September 4147.11 11-SEP-15:01 680.40 769.66 479.33 0.00 0.00 0.00 0.00 71.43 0.00
October 4136.31 01-OCT-15:01 378.00 907.09 534.64 0.00 0.00 0.00 0.00 104.43 0.00
November 4052.63 09-NOV-16:01 680.40 769.66 479.33 0.00 0.00 0.00 0.00 9.53 0.00
December 3451.10 16-DEC-16:02 324.00 777.51 458.26 0.00 0.00 0.00 0.00 0.00 74.09
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 3451.10   252.00 769.66 458.26 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 4183.35   831.60 2096.92 792.74 0.00 0.00 0.00 0.00 135.14 74.09



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2144.90 12-JAN-16:01 680.40 483.89 469.67 0.00 0.00 0.00 0.00 0.00 21.95
February 2163.14 20-FEB-16:01 378.00 570.30 523.86 0.00 0.00 0.00 0.00 2.34 0.00
March 2163.13 14-MAR-15:01 680.40 483.89 469.67 0.00 0.00 0.00 0.00 7.04 0.00
April 2159.09 03-APR-15:01 680.40 483.89 469.67 0.00 0.00 0.00 0.00 22.76 0.00
May 2157.59 20-MAY-15:01 378.00 570.30 523.86 0.00 0.00 0.00 0.00 50.71 0.00
June 2155.36 12-JUN-15:01 680.40 483.89 469.67 0.00 0.00 0.00 0.00 60.06 0.00
July 1981.99 23-JUL-18:02 702.00 1481.29 758.70 0.00 0.00 0.00 0.00 45.38 0.00
August 1972.67 31-AUG-18:01 970.20 1538.07 885.15 0.00 0.00 0.00 0.00 26.49 0.00
September 2180.20 30-SEP-15:01 378.00 570.30 523.86 0.00 0.00 0.00 0.00 29.66 0.00
October 2196.57 01-OCT-15:01 378.00 570.30 523.86 0.00 0.00 0.00 0.00 51.92 0.00
November 2171.97 09-NOV-16:01 680.40 483.89 469.67 0.00 0.00 0.00 0.00 2.79 0.00
December 2113.72 30-DEC-16:01 378.00 570.30 523.86 0.00 0.00 0.00 0.00 0.00 60.12
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1972.67   378.00 483.89 469.67 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 2196.57   970.20 1538.07 885.15 0.00 0.00 0.00 0.00 60.06 60.12



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 19070.69 03-JAN-22:20 26988.77 2548.93 6747.90 0.00 0.00 0.00 0.00 0.00 282.64
February 19607.35 07-FEB-23:00 26988.77 2548.93 6747.90 0.00 0.00 0.00 0.00 0.00 189.15
March 20039.51 15-MAR-22:00 26988.77 2548.93 6747.90 0.00 0.00 0.00 0.00 0.00 92.52
April 22065.71 19-APR-18:10 146938.85 23790.00 47235.32 0.00 0.00 0.00 0.00 209.56 0.00
May 23213.15 31-MAY-18:10 125947.58 20391.43 40487.42 0.00 0.00 0.00 0.00 230.46 0.00
June 24499.85 15-JUN-18:10 125947.58 20391.43 40487.42 0.00 0.00 0.00 0.00 346.45 0.00
July 24280.63 03-JUL-18:10 125947.58 20391.43 40487.42 0.00 0.00 0.00 0.00 358.55 0.00
August 23987.51 07-AUG-18:10 125947.58 20391.43 40487.42 0.00 0.00 0.00 0.00 303.07 0.00
September 22615.40 20-SEP-18:10 125947.58 20391.43 40487.42 0.00 0.00 0.00 0.00 237.14 0.00
October 21917.29 05-OCT-18:10 146938.85 23790.00 47235.32 0.00 0.00 0.00 0.00 141.46 0.00
November 19951.85 09-NOV-22:20 26988.77 2548.93 6747.90 0.00 0.00 0.00 0.00 0.00 123.53
December 19120.60 15-DEC-23:00 26988.77 2548.93 6747.90 0.00 0.00 0.00 0.00 0.00 233.54
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 19070.69   26988.77 2548.93 6747.90 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 24499.85   146938.85 23790.00 47235.32 0.00 0.00 0.00 0.00 358.55 282.64



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 20251.88 03-JAN-22:10 80966.30 7646.79 20243.71 0.00 0.00 0.00 0.00 0.00 274.83
February 20815.43 07-FEB-23:00 26988.77 2548.93 6747.90 0.00 0.00 0.00 0.00 0.00 191.52
March 21290.66 22-MAR-18:10 125947.58 20391.43 40487.42 0.00 0.00 0.00 0.00 0.00 37.82
April 23417.60 19-APR-18:10 146938.85 23790.00 47235.32 0.00 0.00 0.00 0.00 207.07 0.00
May 24608.28 31-MAY-18:10 125947.58 20391.43 40487.42 0.00 0.00 0.00 0.00 228.08 0.00
June 25884.23 15-JUN-18:10 125947.58 20391.43 40487.42 0.00 0.00 0.00 0.00 344.73 0.00
July 25630.03 03-JUL-18:10 125947.58 20391.43 40487.42 0.00 0.00 0.00 0.00 357.06 0.00
August 25318.51 07-AUG-18:10 125947.58 20391.43 40487.42 0.00 0.00 0.00 0.00 301.61 0.00
September 23921.91 20-SEP-18:10 125947.58 20391.43 40487.42 0.00 0.00 0.00 0.00 235.30 0.00
October 23218.87 05-OCT-18:10 146938.85 23790.00 47235.32 0.00 0.00 0.00 0.00 139.34 0.00
November 21178.26 09-NOV-22:10 80966.30 7646.79 20243.71 0.00 0.00 0.00 0.00 0.00 116.10
December 20297.43 15-DEC-23:00 26988.77 2548.93 6747.90 0.00 0.00 0.00 0.00 0.00 235.88
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 20251.88   26988.77 2548.93 6747.90 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 25884.23   146938.85 23790.00 47235.32 0.00 0.00 0.00 0.00 357.06 274.83



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 26380.58 01-JAN-11:50 800.57 340.26 15112.11 18744.03 0.00 0.00 0.00 0.00 240.36
February 27731.00 20-FEB-11:50 800.57 340.26 15112.11 18744.03 0.00 0.00 0.00 0.00 79.43
March 27865.57 19-MAR-10:50 800.57 340.26 15112.11 18744.03 0.00 0.00 0.00 0.00 118.93
April 29809.53 30-APR-10:40 1601.14 680.52 30224.21 37488.05 0.00 0.00 0.00 0.00 0.62
May 30087.43 21-MAY-10:50 800.57 340.26 15112.11 18744.03 0.00 0.00 0.00 135.60 0.00
June 30779.39 18-JUN-10:50 800.57 340.26 15112.11 18744.03 0.00 0.00 0.00 193.89 0.00
July 30956.25 02-JUL-10:40 1601.14 680.52 30224.21 37488.05 0.00 0.00 0.00 184.85 0.00
August 30809.68 06-AUG-10:40 1601.14 680.52 30224.21 37488.05 0.00 0.00 0.00 172.76 0.00
September 30236.51 17-SEP-10:40 1601.14 680.52 30224.21 37488.05 0.00 0.00 0.00 123.27 0.00
October 29612.84 05-OCT-10:50 533.71 283.55 15112.11 18744.03 0.00 0.00 0.00 83.11 0.00
November 27587.58 10-NOV-11:50 533.71 283.55 15112.11 18744.03 0.00 0.00 0.00 0.00 71.82
December 26419.78 10-DEC-11:50 800.57 340.26 15112.11 18744.03 0.00 0.00 0.00 0.00 184.93
                       
Annual Sum or Average             0.00 0.00 0.00    
Minimum of Months 26380.58   533.71 283.55 15112.11 18744.03 0.00 0.00 0.00 0.00 0.00
Maximum of Months 30956.25   1601.14 680.52 30224.21 37488.05 0.00 0.00 0.00 193.89 240.36



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 4769.52 12-JAN-14:30 532.32 377.07 0.00 0.00 0.00 0.00 0.00 0.00 58.56
February 5042.60 22-FEB-13:00 532.32 377.07 0.00 0.00 0.00 0.00 0.00 0.00 12.05
March 5530.53 14-MAR-15:50 1330.80 377.07 0.00 0.00 0.00 0.00 0.00 71.88 0.00
April 6616.80 30-APR-10:35 1596.96 904.96 0.00 0.00 0.00 0.00 0.00 67.66 0.00
May 7067.27 21-MAY-10:35 1596.96 904.96 0.00 0.00 0.00 0.00 0.00 182.77 0.00
June 7698.13 17-JUN-17:13 4790.88 2714.87 0.00 0.00 0.00 0.00 0.00 308.76 0.00
July 7803.58 03-JUL-10:35 1064.64 754.13 0.00 0.00 0.00 0.00 0.00 269.20 0.00
August 7618.31 07-AUG-17:13 3992.40 2714.87 0.00 0.00 0.00 0.00 0.00 304.91 0.00
September 7168.64 03-SEP-10:35 1596.96 904.96 0.00 0.00 0.00 0.00 0.00 107.02 0.00
October 6950.49 05-OCT-10:35 1064.64 754.13 0.00 0.00 0.00 0.00 0.00 141.34 0.00
November 5517.56 03-NOV-15:50 1330.80 377.07 0.00 0.00 0.00 0.00 0.00 59.89 0.00
December 3806.48 16-DEC-13:40 798.48 377.07 0.00 0.00 0.00 0.00 0.00 0.00 153.51
                       
Annual Sum or Average         0.00 0.00 0.00 0.00 0.00    
Minimum of Months 3806.48   532.32 377.07 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 7803.58   4790.88 2714.87 0.00 0.00 0.00 0.00 0.00 308.76 153.51



Table of Contents

Report: EnergyConsumptionElectricityNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ELECTRICITY:FACILITY [J] ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} NATURALGAS:FACILITY [J] NATURALGAS:FACILITY {Maximum} [W] NATURALGAS:FACILITY {TIMESTAMP}
January 0.593837E+12 364668.70 03-JAN-20:19 0.605208E+12 438449.10 15-JAN-17:40
February 0.563166E+12 402264.60 06-FEB-20:10 0.530227E+12 418140.36 02-FEB-17:00
March 0.649162E+12 431822.64 14-MAR-18:10 0.562212E+12 417357.35 01-MAR-18:49
April 0.744868E+12 494438.02 19-APR-19:10 0.485892E+12 392706.64 10-APR-17:00
May 0.869859E+12 526758.56 19-MAY-19:10 0.467047E+12 381032.59 07-MAY-17:30
June 0.935561E+12 570236.28 05-JUN-19:10 0.429508E+12 355246.73 04-JUN-16:10
July 0.102281E+13 561057.63 25-JUL-19:10 0.426603E+12 352573.67 09-JUL-16:19
August 0.960188E+12 549445.33 04-AUG-19:10 0.421637E+12 348345.42 20-AUG-16:00
September 0.878788E+12 511671.41 22-SEP-19:10 0.411730E+12 347325.69 04-SEP-16:49
October 0.763599E+12 511672.60 04-OCT-19:10 0.457615E+12 370254.31 15-OCT-16:00
November 0.617259E+12 422211.34 09-NOV-20:00 0.519277E+12 428661.83 27-NOV-17:40
December 0.589177E+12 360842.04 15-DEC-20:10 0.614229E+12 467500.63 26-DEC-17:19
             
Annual Sum or Average 0.918828E+13     0.593118E+13    
Minimum of Months 0.563166E+12 360842.04   0.411730E+12 347325.69  
Maximum of Months 0.102281E+13 570236.28   0.614229E+12 467500.63  



Table of Contents

Report: EndUseEnergyConsumptionElectricityMonthly

For: Meter

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY [J] EXTERIORLIGHTS:ELECTRICITY [J] INTERIOREQUIPMENT:ELECTRICITY [J] EXTERIOREQUIPMENT:ELECTRICITY [J] FANS:ELECTRICITY [J] PUMPS:ELECTRICITY [J] HEATING:ELECTRICITY [J] COOLING:ELECTRICITY [J] HEATREJECTION:ELECTRICITY [] HUMIDIFIER:ELECTRICITY [] HEATRECOVERY:ELECTRICITY [J] WATERSYSTEMS:ELECTRICITY [J] COGENERATION:ELECTRICITY []
January 0.997859E+11 0.257766E+11 0.148746E+12 0.577258E+11 0.167485E+12 0.112232E+11 0.00 0.209948E+11 0.00 0.00 0.481696E+11 0.770782E+10 0.00
February 0.901073E+11 0.220513E+11 0.134341E+12 0.521396E+11 0.151388E+12 0.131565E+11 0.00 0.444274E+11 0.00 0.00 0.429734E+11 0.696494E+10 0.00
March 0.995228E+11 0.226622E+11 0.148757E+12 0.577286E+11 0.167230E+12 0.169368E+11 0.00 0.752798E+11 0.00 0.00 0.471151E+11 0.770634E+10 0.00
April 0.965474E+11 0.201687E+11 0.143913E+12 0.558635E+11 0.166397E+12 0.228219E+11 0.00 0.179566E+12 0.00 0.00 0.460731E+11 0.746749E+10 0.00
May 0.996636E+11 0.193275E+11 0.148757E+12 0.577273E+11 0.177247E+12 0.267390E+11 0.00 0.278388E+12 0.00 0.00 0.479846E+11 0.770691E+10 0.00
June 0.963626E+11 0.179455E+11 0.143963E+12 0.558662E+11 0.177209E+12 0.279264E+11 0.00 0.355970E+12 0.00 0.00 0.466965E+11 0.745903E+10 0.00
July 0.998551E+11 0.188768E+11 0.148708E+12 0.577246E+11 0.182968E+12 0.297785E+11 0.00 0.422527E+12 0.00 0.00 0.482531E+11 0.771469E+10 0.00
August 0.995413E+11 0.201687E+11 0.148768E+12 0.577287E+11 0.181010E+12 0.290189E+11 0.00 0.361581E+12 0.00 0.00 0.482494E+11 0.770671E+10 0.00
September 0.965794E+11 0.211501E+11 0.143924E+12 0.558636E+11 0.173202E+12 0.270992E+11 0.00 0.300733E+12 0.00 0.00 0.465730E+11 0.746864E+10 0.00
October 0.997606E+11 0.236937E+11 0.148735E+12 0.577257E+11 0.173246E+12 0.237453E+11 0.00 0.175237E+12 0.00 0.00 0.474067E+11 0.770589E+10 0.00
November 0.965244E+11 0.244648E+11 0.143978E+12 0.558644E+11 0.163241E+12 0.148856E+11 0.00 0.586973E+11 0.00 0.00 0.461197E+11 0.745204E+10 0.00
December 0.998619E+11 0.261572E+11 0.148708E+12 0.577246E+11 0.168222E+12 0.103367E+11 0.00 0.161009E+11 0.00 0.00 0.481468E+11 0.771610E+10 0.00
                           
Annual Sum or Average 0.117411E+13 0.262443E+12 0.175130E+13 0.679683E+12 0.204885E+13 0.253668E+12 0.00 0.228950E+13 0.00 0.00 0.563761E+12 0.907766E+11 0.00
Minimum of Months 0.901073E+11 0.179455E+11 0.134341E+12 0.521396E+11 0.151388E+12 0.103367E+11 0.00 0.161009E+11 0.00 0.00 0.429734E+11 0.696494E+10 0.00
Maximum of Months 0.998619E+11 0.261572E+11 0.148768E+12 0.577287E+11 0.182968E+12 0.297785E+11 0.00 0.422527E+12 0.00 0.00 0.482531E+11 0.771610E+10 0.00



Table of Contents

Report: EndUseEnergyConsumptionNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS [J] EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS [J] COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS [J] COGENERATION:NATURALGAS [] HUMIDIFIER:NATURALGAS []
January 0.151918E+12 0.00 0.180679E+12 0.00 0.272610E+12 0.00 0.00
February 0.137204E+12 0.00 0.146903E+12 0.00 0.246120E+12 0.00 0.00
March 0.152024E+12 0.00 0.143946E+12 0.00 0.266243E+12 0.00 0.00
April 0.146956E+12 0.00 0.920208E+11 0.00 0.246916E+12 0.00 0.00
May 0.151978E+12 0.00 0.727320E+11 0.00 0.242336E+12 0.00 0.00
June 0.147114E+12 0.00 0.586329E+11 0.00 0.223761E+12 0.00 0.00
July 0.151820E+12 0.00 0.500492E+11 0.00 0.224733E+12 0.00 0.00
August 0.152039E+12 0.00 0.447590E+11 0.00 0.224839E+12 0.00 0.00
September 0.146971E+12 0.00 0.409287E+11 0.00 0.223831E+12 0.00 0.00
October 0.151903E+12 0.00 0.632874E+11 0.00 0.242424E+12 0.00 0.00
November 0.147091E+12 0.00 0.125142E+12 0.00 0.247043E+12 0.00 0.00
December 0.151820E+12 0.00 0.196115E+12 0.00 0.266293E+12 0.00 0.00
               
Annual Sum or Average 0.178884E+13 0.00 0.121520E+13 0.00 0.292715E+13 0.00 0.00
Minimum of Months 0.137204E+12 0.00 0.409287E+11 0.00 0.223761E+12 0.00 0.00
Maximum of Months 0.152039E+12 0.00 0.196115E+12 0.00 0.272610E+12 0.00 0.00



Table of Contents

Report: PeakEnergyEndUseElectricityPart1Monthly

For: Meter

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY {Maximum} [W] INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} FANS:ELECTRICITY {Maximum} [W] FANS:ELECTRICITY {TIMESTAMP} PUMPS:ELECTRICITY {Maximum} [W] PUMPS:ELECTRICITY {TIMESTAMP} HEATING:ELECTRICITY {Maximum} [W] HEATING:ELECTRICITY {TIMESTAMP}
January 93091.76 02-JAN-20:10 16690.39 01-JAN-00:10 89674.66 02-JAN-07:10 40537.60 02-JAN-07:19 73400.67 27-JAN-09:09 9414.08 03-JAN-14:39 0.00 01-JAN-00:10
February 93091.76 01-FEB-20:10 16690.39 01-FEB-00:10 89674.66 01-FEB-07:10 40537.60 01-FEB-07:19 72537.27 20-FEB-16:10 10621.74 20-FEB-16:30 0.00 01-FEB-00:10
March 93091.76 01-MAR-20:10 16690.39 01-MAR-00:10 89674.66 01-MAR-07:10 40537.60 01-MAR-07:19 73100.41 16-MAR-15:09 10740.56 22-MAR-16:19 0.00 01-MAR-00:10
April 93091.76 03-APR-19:10 16690.39 01-APR-00:10 89674.66 03-APR-06:10 40537.60 03-APR-06:19 81622.77 29-APR-15:20 11927.90 27-APR-10:39 0.00 01-APR-00:10
May 93091.76 01-MAY-19:10 16690.39 01-MAY-00:10 89674.66 01-MAY-06:10 40537.60 01-MAY-06:19 86650.16 19-MAY-18:19 12552.66 19-MAY-15:00 0.00 01-MAY-00:10
June 93091.76 01-JUN-19:10 16690.39 01-JUN-00:10 89674.66 01-JUN-06:10 40537.60 01-JUN-06:19 87145.13 07-JUN-18:19 13002.53 21-JUN-16:40 0.00 01-JUN-00:10
July 93091.76 03-JUL-19:10 16690.39 01-JUL-00:10 89674.66 03-JUL-06:10 40537.60 03-JUL-06:19 86735.41 02-JUL-18:19 12882.73 06-JUL-15:50 0.00 01-JUL-00:10
August 93091.76 01-AUG-19:10 16690.39 01-AUG-00:10 89674.66 01-AUG-06:10 40537.60 01-AUG-06:19 87624.42 27-AUG-18:19 12510.07 23-AUG-18:30 0.00 01-AUG-00:10
September 93091.76 01-SEP-19:10 16690.39 01-SEP-00:10 89674.66 01-SEP-06:10 40537.60 01-SEP-06:19 85020.94 17-SEP-15:20 12541.67 19-SEP-16:00 0.00 01-SEP-00:10
October 93091.76 02-OCT-19:10 16690.39 01-OCT-00:10 89674.66 02-OCT-06:10 40537.60 02-OCT-06:19 81668.23 05-OCT-15:20 11976.42 01-OCT-10:39 0.00 01-OCT-00:10
November 93091.76 01-NOV-19:10 16690.39 01-NOV-00:10 89674.66 01-NOV-06:10 40537.60 01-NOV-06:19 74502.30 03-NOV-15:09 11367.59 03-NOV-16:19 0.00 01-NOV-00:10
December 93091.76 01-DEC-20:10 16690.39 01-DEC-00:10 89674.66 01-DEC-07:10 40537.60 01-DEC-07:19 76891.68 26-DEC-16:10 8700.68 09-DEC-11:39 0.00 01-DEC-00:10
                             
Annual Sum or Average                            
Minimum of Months 93091.76   16690.39   89674.66   40537.60   72537.27   8700.68   0.00  
Maximum of Months 93091.76   16690.39   89674.66   40537.60   87624.42   13002.53   0.00  



Table of Contents

Report: PeakEnergyEndUseElectricityPart2Monthly

For: Meter

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

COOLING:ELECTRICITY {Maximum} [W] COOLING:ELECTRICITY {TIMESTAMP} HEATREJECTION:ELECTRICITY [] HUMIDIFIER:ELECTRICITY [] HEATRECOVERY:ELECTRICITY {Maximum} [W] HEATRECOVERY:ELECTRICITY {TIMESTAMP} WATERSYSTEMS:ELECTRICITY {Maximum} [W] WATERSYSTEMS:ELECTRICITY {TIMESTAMP} COGENERATION:ELECTRICITY []
January 83237.47 03-JAN-14:00 0.00 0.00 18015.63 01-JAN-08:09 4738.97 02-JAN-07:40 0.00
February 109998.80 20-FEB-16:10 0.00 0.00 18015.63 01-FEB-00:10 4739.05 07-FEB-07:10 0.00
March 114217.20 21-MAR-15:09 0.00 0.00 18015.63 01-MAR-00:10 4739.27 28-MAR-06:10 0.00
April 175066.99 21-APR-15:09 0.00 0.00 18015.63 01-APR-07:10 4738.71 10-APR-06:30 0.00
May 204587.12 19-MAY-15:20 0.00 0.00 18015.63 01-MAY-07:10 4739.21 31-MAY-06:10 0.00
June 247961.71 14-JUN-18:10 0.00 0.00 18015.63 01-JUN-07:19 4738.66 20-JUN-06:10 0.00
July 247848.57 26-JUL-15:20 0.00 0.00 18015.63 01-JUL-10:20 4738.75 03-JUL-18:10 0.00
August 231520.94 07-AUG-16:19 0.00 0.00 18015.63 01-AUG-05:10 4738.76 29-AUG-06:10 0.00
September 201133.57 20-SEP-15:20 0.00 0.00 18015.63 01-SEP-05:10 4738.92 19-SEP-06:10 0.00
October 192295.32 04-OCT-15:20 0.00 0.00 18015.63 01-OCT-07:19 4739.02 11-OCT-06:10 0.00
November 113466.06 03-NOV-15:00 0.00 0.00 18015.63 01-NOV-15:09 4739.21 21-NOV-07:10 0.00
December 66113.46 23-DEC-14:00 0.00 0.00 18015.63 01-DEC-00:10 4738.60 18-DEC-07:00 0.00
                   
Annual Sum or Average     0.00 0.00         0.00
Minimum of Months 66113.46   0.00 0.00 18015.63   4738.60   0.00
Maximum of Months 247961.71   0.00 0.00 18015.63   4739.27   0.00



Table of Contents

Report: ElectricComponentsOfPeakDemandMonthly

For: Meter

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] FANS:ELECTRICITY {AT MAX/MIN} [W] PUMPS:ELECTRICITY {AT MAX/MIN} [W] HEATING:ELECTRICITY {AT MAX/MIN} [W] COOLING:ELECTRICITY {AT MAX/MIN} [W] HEATREJECTION:ELECTRICITY []
January 364668.70 03-JAN-20:19 93091.76 88971.67 16690.39 33025.38 65319.99 8168.19 0.00 35051.77 0.00
February 402264.60 06-FEB-20:10 93091.76 88971.67 16690.39 33012.66 64704.76 9197.62 0.00 71983.27 0.00
March 431822.64 14-MAR-18:10 82800.17 79617.06 16690.39 32686.23 71699.44 10466.48 0.00 112796.53 0.00
April 494438.02 19-APR-19:10 93091.76 88971.67 16690.39 33012.66 72889.54 10977.64 0.00 154316.14 0.00
May 526758.56 19-MAY-19:10 93091.76 88971.67 16690.39 33012.66 78710.18 11084.27 0.00 180974.91 0.00
June 570236.28 05-JUN-19:10 93091.76 88971.67 16690.39 33012.66 78213.03 11289.13 0.00 224284.18 0.00
July 561057.63 25-JUL-19:10 93091.76 88971.67 16690.39 33012.66 77907.72 11388.66 0.00 215759.11 0.00
August 549445.33 04-AUG-19:10 93091.76 88971.67 16690.39 33012.66 77545.25 11414.11 0.00 204482.65 0.00
September 511671.41 22-SEP-19:10 93091.76 88971.67 16690.39 33012.66 74381.77 11290.75 0.00 169762.01 0.00
October 511672.60 04-OCT-19:10 93091.76 88971.67 16690.39 33012.66 73553.29 11328.72 0.00 170450.36 0.00
November 422211.34 09-NOV-20:00 93091.76 88971.67 16690.39 33025.38 67394.10 10055.49 0.00 88360.43 0.00
December 360842.04 15-DEC-20:10 93091.76 88971.67 16690.39 33012.66 64593.55 7950.83 0.00 32416.19 0.00
                       
Annual Sum or Average                     0.00
Minimum of Months 360842.04   82800.17 79617.06 16690.39 32686.23 64593.55 7950.83 0.00 32416.19 0.00
Maximum of Months 570236.28   93091.76 88971.67 16690.39 33025.38 78710.18 11414.11 0.00 224284.18 0.00



Table of Contents

Report: PeakEnergyEndUseNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS {Maximum} [W] INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS {Maximum} [W] HEATING:NATURALGAS {TIMESTAMP} COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS {Maximum} [W] WATERSYSTEMS:NATURALGAS {TIMESTAMP} COGENERATION:NATURALGAS []
January 104248.32 02-JAN-18:10 0.00 183744.30 27-JAN-07:19 0.00 251045.32 18-JAN-21:00 0.00
February 104248.32 01-FEB-18:10 0.00 201630.34 03-FEB-07:10 0.00 251113.69 09-FEB-21:00 0.00
March 104248.32 01-MAR-18:10 0.00 167591.07 02-MAR-09:09 0.00 249835.28 02-MAR-21:40 0.00
April 104248.32 01-APR-17:10 0.00 115174.10 11-APR-10:39 0.00 248120.02 03-APR-20:00 0.00
May 104248.32 01-MAY-17:10 0.00 96298.93 02-MAY-10:39 0.00 245809.75 04-MAY-20:49 0.00
June 104248.32 01-JUN-17:10 0.00 86050.42 29-JUN-10:39 0.00 221707.07 01-JUN-19:10 0.00
July 104248.32 01-JUL-17:10 0.00 91155.07 21-JUL-10:39 0.00 215426.47 03-JUL-20:19 0.00
August 104248.32 01-AUG-17:10 0.00 89051.04 17-AUG-10:39 0.00 215591.47 31-AUG-20:49 0.00
September 104248.32 01-SEP-17:10 0.00 84085.49 01-SEP-10:39 0.00 223409.05 30-SEP-21:40 0.00
October 104248.32 02-OCT-17:10 0.00 93012.78 24-OCT-10:39 0.00 246067.24 31-OCT-20:19 0.00
November 104248.32 01-NOV-17:10 0.00 151473.99 27-NOV-09:09 0.00 248267.69 30-NOV-21:49 0.00
December 104248.32 01-DEC-18:10 0.00 197805.94 27-DEC-07:10 0.00 249772.14 28-DEC-21:19 0.00
                   
Annual Sum or Average     0.00     0.00     0.00
Minimum of Months 104248.32   0.00 84085.49   0.00 215426.47   0.00
Maximum of Months 104248.32   0.00 201630.34   0.00 251113.69   0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.17 21.90 0.17 21.90
July 0.00 0.00 0.00 0.00 0.17 21.68 0.17 21.68
August 0.00 0.00 0.00 0.00 0.50 21.72 0.50 21.72
September 0.00 0.00 0.00 0.00 0.83 21.88 0.83 21.88
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   1.67 21.81 1.67 21.81
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.83 21.90 0.83 21.90



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.17 21.68 0.17 21.68
June 0.00 0.00 0.00 0.00 0.33 21.82 0.33 21.82
July 0.00 0.00 0.00 0.00 0.17 21.68 0.17 21.68
August 0.00 0.00 0.00 0.00 0.17 21.68 0.17 21.68
September 0.00 0.00 0.00 0.00 0.17 21.71 0.17 21.71
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   1.00 21.73 1.00 21.73
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.33 21.82 0.33 21.82



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.50 21.71 0.50 21.71
June 0.00 0.00 0.00 0.00 1.33 21.74 1.33 21.74
July 0.00 0.00 0.00 0.00 0.33 21.70 0.33 21.70
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   2.17 21.73 2.17 21.73
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 1.33 21.74 1.33 21.74



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.50 21.71 0.50 21.71
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.17 21.71 0.17 21.71
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.67 21.71 0.67 21.71
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.50 21.71 0.50 21.71



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.50 21.75 0.50 21.75
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.50 21.75 0.50 21.75
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.50 21.75 0.50 21.75



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 1.00 21.74 1.00 21.74
June 0.00 0.00 0.00 0.00 1.17 21.70 1.17 21.70
July 0.00 0.00 0.00 0.00 0.83 21.81 0.83 21.81
August 0.00 0.00 0.00 0.00 2.17 21.78 2.17 21.78
September 0.00 0.00 0.00 0.00 2.33 21.89 2.33 21.89
October 0.00 0.00 0.00 0.00 0.17 21.75 0.17 21.75
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   7.67 21.80 7.67 21.80
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 2.33 21.89 2.33 21.89



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 1.00 21.75 1.00 21.75
June 0.00 0.00 0.00 0.00 1.33 21.73 1.33 21.73
July 0.00 0.00 0.00 0.00 0.67 21.85 0.67 21.85
August 0.00 0.00 0.00 0.00 1.50 21.76 1.50 21.76
September 0.00 0.00 0.00 0.00 0.50 21.79 0.50 21.79
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   5.00 21.76 5.00 21.76
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 1.50 21.85 1.50 21.85



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.33 21.76 0.33 21.76
July 0.00 0.00 0.00 0.00 0.33 21.67 0.33 21.67
August 0.00 0.00 0.00 0.00 0.83 21.82 0.83 21.82
September 0.00 0.00 0.00 0.00 2.83 21.87 2.83 21.87
October 0.00 0.00 0.00 0.00 1.67 21.81 1.67 21.81
November 0.00 0.00 0.00 0.00 0.17 21.88 0.17 21.88
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   6.17 21.83 6.17 21.83
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 2.83 21.88 2.83 21.88



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: BASEMENT

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.09 26.67 21.09 26.67 21.09
February 672.00 21.02 116.50 21.02 116.50 21.01
March 744.00 20.95 305.00 20.93 305.00 20.92
April 720.00 20.94 230.83 20.93 230.83 20.93
May 744.00 20.96 33.50 20.96 33.50 20.96
June 720.00 20.97 6.83 20.97 6.83 20.96
July 744.00 21.06 0.00 21.06 0.00 21.06
August 744.00 21.20 0.00 21.20 0.00 21.20
September 720.00 21.41 0.00 21.41 0.00 21.41
October 744.00 21.49 0.00 21.49 0.00 21.49
November 720.00 21.48 0.00 21.48 0.00 21.48
December 744.00 21.28 9.00 21.28 9.00 21.27
             
Annual Sum or Average 8760.00 21.15 728.33 21.14 728.33 21.12
Minimum of Months 672.00 20.94 0.00 20.93 0.00 20.92
Maximum of Months 744.00 21.49 305.00 21.49 305.00 21.49



Table of Contents

Report: ComfortReportSimple55Monthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.09 169.67 21.07 169.67 21.06
February 672.00 21.10 157.50 21.08 157.50 21.07
March 744.00 21.05 163.33 21.04 163.33 21.04
April 720.00 21.05 55.00 21.05 55.00 21.05
May 744.00 21.04 6.50 21.04 6.50 21.04
June 720.00 21.12 0.00 21.12 0.00 21.12
July 744.00 21.11 0.00 21.11 0.00 21.11
August 743.33 21.16 0.00 21.16 0.00 21.16
September 673.17 21.20 7.67 21.22 0.00 21.22
October 686.67 21.16 18.00 21.20 0.00 21.20
November 709.50 21.19 122.00 21.16 122.00 21.14
December 744.00 21.06 269.83 21.05 269.83 21.04
             
Annual Sum or Average 8644.67 21.11 969.50 21.10 943.83 21.09
Minimum of Months 672.00 21.04 0.00 21.04 0.00 21.04
Maximum of Months 744.00 21.20 269.83 21.22 269.83 21.22



Table of Contents

Report: ComfortReportSimple55Monthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.01 20.33 21.01 20.33 21.01
February 672.00 21.02 0.00 21.02 0.00 21.02
March 744.00 21.04 0.83 21.04 0.83 21.04
April 720.00 21.10 0.00 21.10 0.00 21.10
May 744.00 21.17 0.00 21.17 0.00 21.17
June 720.00 21.27 0.00 21.27 0.00 21.27
July 744.00 21.24 0.00 21.24 0.00 21.24
August 744.00 21.23 0.00 21.23 0.00 21.23
September 720.00 21.19 0.00 21.19 0.00 21.19
October 744.00 21.10 0.00 21.10 0.00 21.10
November 720.00 21.03 0.00 21.03 0.00 21.03
December 744.00 21.01 32.33 21.01 32.33 21.01
             
Annual Sum or Average 8760.00 21.12 53.50 21.12 53.50 21.12
Minimum of Months 672.00 21.01 0.00 21.01 0.00 21.01
Maximum of Months 744.00 21.27 32.33 21.27 32.33 21.27



Table of Contents

Report: ComfortReportSimple55Monthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.00 221.50 21.00 221.50 21.00
February 672.00 21.00 202.33 21.00 202.33 21.00
March 744.00 21.00 136.17 21.00 136.17 21.00
April 720.00 21.02 31.83 21.01 31.83 21.01
May 744.00 21.06 0.00 21.06 0.00 21.06
June 720.00 21.15 0.00 21.15 0.00 21.15
July 744.00 21.13 0.00 21.13 0.00 21.13
August 744.00 21.10 0.00 21.10 0.00 21.10
September 720.00 21.05 0.00 21.05 0.00 21.05
October 744.00 21.01 0.00 21.01 0.00 21.01
November 720.00 21.00 107.50 21.00 107.50 21.00
December 744.00 21.00 269.67 21.00 269.67 21.00
             
Annual Sum or Average 8760.00 21.04 969.00 21.04 969.00 21.04
Minimum of Months 672.00 21.00 0.00 21.00 0.00 21.00
Maximum of Months 744.00 21.15 269.67 21.15 269.67 21.15



Table of Contents

Report: ComfortReportSimple55Monthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.00 297.33 21.00 297.33 21.00
February 672.00 21.00 343.00 21.00 343.00 21.00
March 744.00 21.00 254.50 21.00 254.50 21.00
April 720.00 21.00 102.50 21.00 102.50 21.00
May 744.00 21.01 7.67 21.01 7.67 21.01
June 720.00 21.08 0.00 21.08 0.00 21.08
July 744.00 21.06 0.00 21.06 0.00 21.06
August 744.00 21.04 0.00 21.04 0.00 21.04
September 720.00 21.01 0.00 21.01 0.00 21.01
October 744.00 21.00 1.83 21.00 1.83 21.00
November 720.00 21.00 200.67 21.00 200.67 21.00
December 744.00 21.00 426.50 21.00 426.50 21.00
             
Annual Sum or Average 8760.00 21.02 1634.00 21.01 1634.00 21.01
Minimum of Months 672.00 21.00 0.00 21.00 0.00 21.00
Maximum of Months 744.00 21.08 426.50 21.08 426.50 21.08



Table of Contents

Report: ComfortReportSimple55Monthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 550.00 21.38 152.50 21.72 77.00 21.92
February 493.00 21.37 136.17 21.72 68.00 21.92
March 545.50 21.40 149.67 21.75 82.67 21.95
April 432.83 21.49 177.00 21.80 84.17 22.01
May 304.50 21.79 290.67 21.88 103.00 22.09
June 182.17 22.26 401.67 21.85 103.33 22.06
July 112.17 23.08 653.00 21.65 111.33 21.83
August 128.83 22.93 582.67 21.75 111.33 21.95
September 152.50 22.57 515.67 21.77 106.00 21.97
October 299.00 21.83 352.00 21.84 104.83 22.05
November 490.83 21.44 162.83 21.78 81.83 21.98
December 574.33 21.33 145.83 21.68 69.83 21.86
             
Annual Sum or Average 4265.67 21.63 3719.67 21.76 1103.33 21.96
Minimum of Months 112.17 21.33 136.17 21.65 68.00 21.83
Maximum of Months 574.33 23.08 653.00 21.88 111.33 22.09



Table of Contents

Report: ComfortReportSimple55Monthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 743.33 21.08 20.00 21.08 20.00 21.08
February 672.00 21.10 16.50 21.10 16.50 21.10
March 744.00 21.07 10.50 21.07 10.50 21.07
April 720.00 21.16 0.00 21.16 0.00 21.16
May 744.00 21.23 3.67 21.23 3.67 21.23
June 720.00 21.37 25.67 21.38 25.67 21.39
July 738.33 21.35 147.17 21.43 147.17 21.49
August 741.67 21.38 115.00 21.44 114.83 21.48
September 678.83 21.38 126.83 21.43 123.00 21.47
October 683.00 21.30 52.00 21.34 32.67 21.36
November 706.83 21.19 3.67 21.19 3.67 21.19
December 744.00 21.06 43.50 21.06 43.50 21.06
             
Annual Sum or Average 8636.00 21.22 564.50 21.25 541.17 21.27
Minimum of Months 672.00 21.06 0.00 21.06 0.00 21.06
Maximum of Months 744.00 21.38 147.17 21.44 147.17 21.49



Table of Contents

Report: ComfortReportSimple55Monthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.06 0.00 21.06 0.00 21.06
February 672.00 21.08 0.00 21.08 0.00 21.08
March 744.00 21.12 0.00 21.12 0.00 21.12
April 720.00 21.23 0.00 21.23 0.00 21.23
May 744.00 21.33 2.33 21.33 2.33 21.33
June 720.00 21.44 7.83 21.44 7.83 21.44
July 744.00 21.42 67.00 21.45 67.00 21.48
August 744.00 21.41 50.17 21.43 50.17 21.45
September 720.00 21.35 70.50 21.39 70.50 21.42
October 744.00 21.25 15.83 21.26 15.83 21.27
November 720.00 21.11 0.00 21.11 0.00 21.11
December 744.00 21.05 0.00 21.05 0.00 21.05
             
Annual Sum or Average 8760.00 21.24 213.67 21.25 213.67 21.26
Minimum of Months 672.00 21.05 0.00 21.05 0.00 21.05
Maximum of Months 744.00 21.44 70.50 21.45 70.50 21.48



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.24 213.17 21.14 213.17 21.09
February 672.00 21.34 164.33 21.27 164.33 21.22
March 744.00 21.44 112.33 21.37 112.33 21.32
April 708.83 21.59 17.67 21.57 17.67 21.56
May 686.67 21.55 0.00 21.55 0.00 21.55
June 632.50 21.51 6.50 21.53 0.00 21.53
July 598.17 21.34 58.67 21.51 12.17 21.53
August 617.33 21.39 34.17 21.47 6.00 21.47
September 593.83 21.37 32.00 21.46 4.50 21.47
October 691.50 21.49 12.67 21.52 3.17 21.52
November 713.50 21.40 128.50 21.32 128.50 21.26
December 744.00 21.19 320.83 21.10 320.83 21.05
             
Annual Sum or Average 8146.33 21.40 1100.83 21.38 982.67 21.33
Minimum of Months 593.83 21.19 0.00 21.10 0.00 21.05
Maximum of Months 744.00 21.59 320.83 21.57 320.83 21.56



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 20.88 444.33 20.81 444.33 20.78
February 672.00 21.05 323.67 20.98 323.67 20.94
March 744.00 21.24 188.50 21.17 188.50 21.12
April 715.50 21.54 28.67 21.52 28.67 21.50
May 691.83 21.56 0.00 21.56 0.00 21.56
June 635.67 21.52 7.33 21.54 0.00 21.54
July 601.83 21.36 55.50 21.51 12.17 21.54
August 638.00 21.44 24.00 21.49 6.33 21.49
September 635.33 21.46 14.67 21.49 8.50 21.49
October 727.50 21.46 7.67 21.46 6.50 21.46
November 720.00 21.16 243.33 21.07 243.33 21.02
December 744.00 20.82 599.50 20.78 599.50 20.77
             
Annual Sum or Average 8269.67 21.28 1937.17 21.21 1861.50 21.14
Minimum of Months 601.83 20.82 0.00 20.78 0.00 20.77
Maximum of Months 744.00 21.56 599.50 21.56 599.50 21.56



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.06 216.17 21.03 216.17 21.01
February 672.00 21.15 148.00 21.11 148.00 21.08
March 744.00 21.25 59.17 21.23 59.17 21.22
April 720.00 21.47 0.00 21.47 0.00 21.47
May 744.00 21.61 0.00 21.61 0.00 21.61
June 720.00 21.69 0.00 21.69 0.00 21.69
July 744.00 21.70 7.67 21.71 7.67 21.72
August 744.00 21.65 0.33 21.65 0.33 21.65
September 720.00 21.60 1.67 21.60 1.67 21.60
October 744.00 21.42 0.00 21.42 0.00 21.42
November 720.00 21.17 76.17 21.15 76.17 21.14
December 744.00 21.01 340.50 20.96 340.50 20.94
             
Annual Sum or Average 8760.00 21.40 849.67 21.36 849.67 21.32
Minimum of Months 672.00 21.01 0.00 20.96 0.00 20.94
Maximum of Months 744.00 21.70 340.50 21.71 340.50 21.72



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.26 211.83 21.18 211.83 21.14
February 672.00 21.43 132.67 21.37 132.67 21.33
March 744.00 21.54 101.67 21.48 101.67 21.43
April 711.50 21.69 14.83 21.68 14.83 21.67
May 693.33 21.62 0.33 21.63 0.00 21.63
June 598.00 21.43 3.17 21.44 0.00 21.44
July 558.67 21.23 21.67 21.29 8.00 21.31
August 580.00 21.29 11.00 21.31 6.17 21.31
September 574.67 21.34 7.17 21.36 1.17 21.37
October 685.00 21.51 5.33 21.51 5.00 21.50
November 719.67 21.47 128.50 21.38 128.50 21.31
December 744.00 21.20 313.83 21.13 313.83 21.08
             
Annual Sum or Average 8024.83 21.42 952.00 21.38 923.67 21.35
Minimum of Months 558.67 21.20 0.33 21.13 0.00 21.08
Maximum of Months 744.00 21.69 313.83 21.68 313.83 21.67



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 20.88 463.17 20.83 463.17 20.81
February 672.00 21.12 280.50 21.06 280.50 21.02
March 744.00 21.36 154.50 21.29 154.50 21.25
April 716.67 21.67 20.67 21.65 20.67 21.64
May 696.00 21.63 0.33 21.63 0.00 21.63
June 598.50 21.43 5.00 21.45 0.00 21.45
July 558.17 21.22 23.17 21.30 8.00 21.32
August 590.17 21.32 11.50 21.34 6.67 21.34
September 612.50 21.45 7.17 21.47 4.00 21.47
October 731.00 21.53 8.50 21.53 8.33 21.53
November 720.00 21.14 216.17 21.08 216.17 21.04
December 744.00 20.82 583.00 20.78 583.00 20.77
             
Annual Sum or Average 8127.00 21.29 1773.67 21.22 1745.00 21.16
Minimum of Months 558.17 20.82 0.33 20.78 0.00 20.77
Maximum of Months 744.00 21.67 583.00 21.65 583.00 21.64



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.00 204.00 21.00 204.00 21.00
February 672.00 21.01 182.67 21.00 182.67 21.00
March 744.00 21.01 145.33 21.01 145.33 21.01
April 720.00 21.14 54.17 21.13 54.17 21.12
May 744.00 21.45 1.33 21.45 1.33 21.45
June 720.00 21.90 0.00 21.90 0.00 21.90
July 744.00 21.83 27.17 21.82 27.17 21.82
August 744.00 21.76 0.00 21.76 0.00 21.76
September 720.00 21.64 6.17 21.64 6.17 21.64
October 744.00 21.23 0.00 21.23 0.00 21.23
November 720.00 21.02 67.50 21.02 67.50 21.02
December 744.00 21.00 214.67 21.00 214.67 21.00
             
Annual Sum or Average 8760.00 21.33 903.00 21.30 903.00 21.28
Minimum of Months 672.00 21.00 0.00 21.00 0.00 21.00
Maximum of Months 744.00 21.90 214.67 21.90 214.67 21.90



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.15 359.83 21.04 359.83 20.99
February 672.00 21.29 255.00 21.19 255.00 21.13
March 744.00 21.41 193.67 21.31 193.67 21.25
April 689.17 21.54 42.67 21.51 41.50 21.49
May 652.00 21.47 15.33 21.51 0.00 21.51
June 579.17 21.36 37.50 21.48 0.00 21.48
July 568.17 21.26 121.83 21.61 15.00 21.62
August 580.67 21.29 92.33 21.54 10.17 21.54
September 564.33 21.29 98.50 21.56 13.67 21.57
October 667.17 21.42 30.17 21.48 7.83 21.48
November 711.33 21.35 199.00 21.24 198.67 21.17
December 744.00 21.11 461.83 21.01 461.83 20.97
             
Annual Sum or Average 7916.00 21.33 1907.67 21.33 1557.17 21.27
Minimum of Months 564.33 21.11 15.33 21.01 0.00 20.97
Maximum of Months 744.00 21.54 461.83 21.61 461.83 21.62



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 20.79 580.67 20.74 580.67 20.72
February 672.00 20.99 406.17 20.91 406.17 20.87
March 744.00 21.22 274.33 21.12 274.33 21.07
April 701.17 21.52 49.50 21.49 49.50 21.46
May 659.17 21.48 14.33 21.52 0.67 21.52
June 582.17 21.37 36.00 21.49 0.00 21.49
July 569.33 21.27 112.33 21.59 14.17 21.61
August 592.33 21.32 72.50 21.51 10.17 21.51
September 596.83 21.36 64.67 21.51 17.50 21.52
October 710.67 21.43 20.67 21.44 13.83 21.43
November 720.00 21.11 320.83 21.01 320.83 20.96
December 744.00 20.73 693.67 20.71 693.67 20.70
             
Annual Sum or Average 8035.67 21.20 2645.67 21.16 2381.50 21.09
Minimum of Months 569.33 20.73 14.33 20.71 0.00 20.70
Maximum of Months 744.00 21.52 693.67 21.59 693.67 21.61



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 729.17 21.47 97.83 21.41 97.83 21.35
February 659.50 21.54 86.33 21.48 86.33 21.44
March 744.00 21.57 89.17 21.51 89.17 21.46
April 708.00 21.62 22.83 21.60 22.83 21.59
May 707.17 21.61 0.00 21.61 0.00 21.61
June 644.67 21.54 0.00 21.54 0.00 21.54
July 597.00 21.34 19.67 21.38 10.83 21.40
August 605.83 21.35 12.67 21.39 2.83 21.39
September 571.83 21.31 73.50 21.53 4.33 21.54
October 630.50 21.37 39.17 21.48 1.50 21.48
November 666.00 21.42 71.67 21.39 68.83 21.35
December 742.83 21.50 180.00 21.40 180.00 21.33
             
Annual Sum or Average 8006.50 21.48 692.83 21.48 564.50 21.45
Minimum of Months 571.83 21.31 0.00 21.38 0.00 21.33
Maximum of Months 744.00 21.62 180.00 21.61 180.00 21.61



Table of Contents

Report: ComfortReportSimple55Monthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.27 0.00 21.27 0.00 21.27
February 672.00 21.31 0.00 21.31 0.00 21.31
March 744.00 21.39 0.00 21.39 0.00 21.39
April 718.17 21.57 0.00 21.57 0.00 21.57
May 719.83 21.71 11.67 21.72 11.17 21.74
June 620.00 21.77 68.00 21.87 40.50 21.91
July 657.00 21.81 232.33 22.02 194.33 22.13
August 675.50 21.75 165.83 21.91 146.00 22.00
September 699.67 21.66 164.83 21.78 158.83 21.86
October 736.17 21.51 45.00 21.56 43.50 21.59
November 720.00 21.33 0.00 21.33 0.00 21.33
December 744.00 21.23 0.00 21.23 0.00 21.23
             
Annual Sum or Average 8450.33 21.52 687.67 21.60 594.33 21.65
Minimum of Months 620.00 21.23 0.00 21.23 0.00 21.23
Maximum of Months 744.00 21.81 232.33 22.02 194.33 22.13



Table of Contents

Report: ComfortReportSimple55Monthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.30 0.00 21.30 0.00 21.30
February 672.00 21.35 0.00 21.35 0.00 21.35
March 744.00 21.44 0.00 21.44 0.00 21.44
April 711.17 21.63 0.00 21.63 0.00 21.63
May 686.50 21.74 22.83 21.77 9.00 21.79
June 550.67 21.77 94.33 21.93 38.00 21.96
July 586.67 21.84 257.67 22.10 184.67 22.20
August 625.83 21.77 187.83 21.98 140.83 22.07
September 675.00 21.70 169.83 21.84 153.00 21.91
October 729.00 21.56 49.17 21.61 42.17 21.64
November 720.00 21.37 0.00 21.37 0.00 21.37
December 744.00 21.26 0.00 21.26 0.00 21.26
             
Annual Sum or Average 8188.83 21.55 781.67 21.64 567.67 21.69
Minimum of Months 550.67 21.26 0.00 21.26 0.00 21.26
Maximum of Months 744.00 21.84 257.67 22.10 184.67 22.20



Table of Contents

Report: ComfortReportSimple55Monthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 540.67 22.70 519.50 23.02 342.00 23.17
February 515.83 22.81 475.00 23.12 338.67 23.28
March 588.00 22.90 526.50 23.21 398.83 23.36
April 601.67 23.13 530.33 23.39 443.33 23.53
May 617.33 23.35 578.33 23.51 499.00 23.62
June 539.50 23.74 612.33 23.63 506.33 23.72
July 532.33 23.88 715.17 23.52 532.33 23.63
August 536.67 23.81 676.33 23.56 525.83 23.65
September 540.50 23.65 622.67 23.53 501.67 23.63
October 593.83 23.24 579.17 23.37 475.00 23.49
November 562.17 22.85 515.33 23.15 378.67 23.30
December 520.67 22.63 514.67 22.98 314.83 23.14
             
Annual Sum or Average 6689.17 23.22 6865.33 23.34 5256.50 23.48
Minimum of Months 515.83 22.63 475.00 22.98 314.83 23.14
Maximum of Months 617.33 23.88 715.17 23.63 532.33 23.72



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.00 244.17 21.00 244.17 21.00
February 672.00 21.00 255.83 21.00 255.83 21.00
March 744.00 21.00 208.17 21.00 208.17 21.00
April 720.00 21.03 78.00 21.03 78.00 21.03
May 744.00 21.10 11.67 21.10 11.67 21.10
June 720.00 21.42 0.00 21.42 0.00 21.42
July 744.00 21.38 0.00 21.38 0.00 21.38
August 744.00 21.30 0.00 21.30 0.00 21.30
September 720.00 21.18 0.00 21.18 0.00 21.18
October 744.00 21.06 0.00 21.06 0.00 21.06
November 720.00 21.00 164.67 21.00 164.67 21.00
December 744.00 21.00 393.50 21.00 393.50 21.00
             
Annual Sum or Average 8760.00 21.12 1356.00 21.11 1356.00 21.09
Minimum of Months 672.00 21.00 0.00 21.00 0.00 21.00
Maximum of Months 744.00 21.42 393.50 21.42 393.50 21.42



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: BASEMENT PEOPLE

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.09147 24.30796 -0.4523 9.35966
February 672.00000 21.02205 21.25327 -0.5091 10.48377
March 744.00000 20.94993 20.20812 -0.5461 11.28493
April 720.00000 20.94067 24.20740 -0.5228 10.83063
May 744.00000 20.95643 35.44579 -1.6535 59.21950
June 720.00000 20.96748 43.99070 -1.5891 55.73653
July 744.00000 21.05561 59.28584 -1.4402 47.67899
August 744.00000 21.19952 55.69429 -1.3925 45.15873
September 720.00000 21.40859 52.30954 -1.3253 41.70326
October 744.00000 21.48767 43.55234 -0.2175 6.16003
November 720.00000 21.48494 25.26539 -0.3307 7.41430
December 744.00000 21.28044 21.01728 -0.4118 8.63860
           
Annual Sum or Average 8760.00000 21.15430 35.65245 -0.8680 26.23726
Minimum of Months 672.00000 20.94067 20.20812 -1.6535 6.16003
Maximum of Months 744.00000 21.48767 59.28584 -0.2175 59.21950



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: RETAIL_1_FLR_1 PEOPLE

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.08597 23.74003 -0.4454 9.71589
February 672.00000 21.10154 20.63403 -0.4420 9.62894
March 744.00000 21.05003 19.55892 -0.4516 9.61581
April 720.00000 21.05192 23.50960 -0.3804 8.40617
May 744.00000 21.03671 34.72715 -1.4281 47.13228
June 720.00000 21.12426 43.12092 -1.2984 40.32484
July 744.00000 21.11407 59.07381 -1.2074 35.77417
August 744.00000 21.16385 55.50771 -1.2151 36.30304
September 720.00000 21.28079 52.41485 -1.1909 35.70132
October 744.00000 21.27993 43.63105 -0.1778 6.59792
November 720.00000 21.20758 25.12160 -0.3665 8.76625
December 744.00000 21.06349 20.68677 -0.4833 10.38945
           
Annual Sum or Average 8760.00000 21.12985 35.25329 -0.7593 21.60809
Minimum of Months 672.00000 21.03671 19.55892 -1.4281 6.59792
Maximum of Months 744.00000 21.28079 59.07381 -0.1778 47.13228



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: RETAIL_2_FLR_1 PEOPLE

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.01269 24.62156 -0.4532 9.35552
February 672.00000 21.01970 21.48947 -0.4621 9.51942
March 744.00000 21.03983 20.35535 -0.4550 9.37414
April 720.00000 21.09724 24.23620 -0.3989 8.49004
May 744.00000 21.16805 35.26522 -1.4535 48.47127
June 720.00000 21.26906 43.51864 -1.3541 43.23972
July 744.00000 21.24317 59.15419 -1.2723 38.99824
August 744.00000 21.22996 55.95556 -1.2986 40.33651
September 720.00000 21.18642 53.33449 -1.3291 41.93655
October 744.00000 21.10220 44.77351 -0.2720 6.71960
November 720.00000 21.03493 26.12087 -0.4220 8.81730
December 744.00000 21.00660 21.53711 -0.4781 9.81213
           
Annual Sum or Average 8760.00000 21.11797 35.97137 -0.8061 23.00313
Minimum of Months 672.00000 21.00660 20.35535 -1.4535 6.71960
Maximum of Months 744.00000 21.26906 59.15419 -0.2720 48.47127



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: LAUNDRY_FLR_1 PEOPLE

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.42272 22.28409 0.22310 8.63341
February 672.00000 21.42312 19.23562 0.21952 8.56980
March 744.00000 21.42510 18.12181 0.22891 8.68980
April 720.00000 21.39535 22.02038 0.27719 9.13345
May 744.00000 21.38485 33.00992 -0.4987 15.25044
June 720.00000 21.37131 41.49303 -0.4225 13.47079
July 744.00000 21.35200 56.83143 -0.3452 11.80797
August 744.00000 21.37867 53.64860 -0.3625 12.39819
September 720.00000 21.37915 50.91968 -0.3926 12.89039
October 744.00000 21.39822 42.23340 0.38976 10.66482
November 720.00000 21.42132 23.74849 0.25162 8.95413
December 744.00000 21.42003 19.24331 0.19880 8.39461
           
Annual Sum or Average 8760.00000 21.39751 33.67286 -0.0208 10.75187
Minimum of Months 672.00000 21.35200 18.12181 -0.4987 8.39461
Maximum of Months 744.00000 21.42510 56.83143 0.38976 15.25044



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CAFE_FLR_1 PEOPLE

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.08244 26.39085 -0.3475 7.97567
February 672.00000 21.10142 23.28107 -0.3452 7.91112
March 744.00000 21.06982 22.19320 -0.3559 7.91356
April 720.00000 21.15716 26.03922 -0.2754 6.90758
May 744.00000 21.22895 37.03838 -1.2699 38.96598
June 720.00000 21.37047 45.17330 -1.1285 32.12569
July 744.00000 21.36154 60.60819 -1.0375 27.96968
August 744.00000 21.38591 57.33774 -1.0488 28.49560
September 720.00000 21.41246 54.51924 -1.0483 28.78048
October 744.00000 21.36495 46.01554 -0.0755 5.78046
November 720.00000 21.21147 27.75793 -0.2716 7.27805
December 744.00000 21.06103 23.34950 -0.3833 8.48501
           
Annual Sum or Average 8760.00000 21.23447 37.58218 -0.6341 17.44501
Minimum of Months 672.00000 21.06103 22.19320 -1.2699 5.78046
Maximum of Months 744.00000 21.41246 60.60819 -0.0755 38.96598



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: LOBBY_FLR_1 PEOPLE

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.06344 26.05289 -0.3994 8.41195
February 672.00000 21.08357 22.91852 -0.4053 8.51034
March 744.00000 21.11821 21.78223 -0.3991 8.40397
April 720.00000 21.22542 25.58948 -0.3333 7.52847
May 744.00000 21.32741 36.48670 -1.3545 43.29257
June 720.00000 21.43825 44.61256 -1.2470 37.89254
July 744.00000 21.42241 59.99501 -1.1608 33.64728
August 744.00000 21.41030 56.86345 -1.1866 34.86661
September 720.00000 21.34954 54.30684 -1.2225 36.61894
October 744.00000 21.24896 45.89836 -0.1965 6.03058
November 720.00000 21.11496 27.50474 -0.3611 7.86263
December 744.00000 21.04772 22.99008 -0.4262 8.84595
           
Annual Sum or Average 8760.00000 21.23829 37.18975 -0.7262 20.22968
Minimum of Months 672.00000 21.04772 21.78223 -1.3545 6.03058
Maximum of Months 744.00000 21.43825 59.99501 -0.1965 43.29257



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_1_FLR_3 PEOPLE

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.23690 27.62346 -0.4659 10.22334
February 672.00000 21.34347 24.50994 -0.4364 9.69681
March 744.00000 21.43735 23.36572 -0.3907 8.95853
April 720.00000 21.61392 26.77437 -0.2624 7.41543
May 744.00000 21.68946 35.26326 -1.2333 38.21449
June 720.00000 21.73033 40.70284 -1.1299 33.28081
July 744.00000 21.73198 51.81354 -1.0709 30.69165
August 744.00000 21.71701 49.92010 -1.1024 32.09561
September 720.00000 21.71254 48.80460 -1.1216 33.12072
October 744.00000 21.62276 44.57508 -0.1484 6.36346
November 720.00000 21.42030 29.08235 -0.3681 8.88536
December 744.00000 21.19144 24.40330 -0.5110 11.10294
           
Annual Sum or Average 8760.00000 21.53798 35.65233 -0.6884 19.23214
Minimum of Months 672.00000 21.19144 23.36572 -1.2333 6.36346
Maximum of Months 744.00000 21.73198 51.81354 -0.1484 38.21449



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_2_FLR_3 PEOPLE

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 20.88444 28.10506 -0.5918 12.72906
February 672.00000 21.05160 24.85206 -0.5449 11.68501
March 744.00000 21.24418 23.60320 -0.4632 10.02561
April 720.00000 21.55290 26.87170 -0.2924 7.65010
May 744.00000 21.68006 35.28526 -1.2416 38.56995
June 720.00000 21.73269 40.67957 -1.1277 33.16384
July 744.00000 21.73312 51.85282 -1.0715 30.69000
August 744.00000 21.70951 50.20867 -1.1171 32.65940
September 720.00000 21.68432 49.57392 -1.1635 34.82733
October 744.00000 21.49964 45.39743 -0.2102 6.58298
November 720.00000 21.15718 29.49377 -0.4771 10.40413
December 744.00000 20.82222 24.85004 -0.6419 13.99462
           
Annual Sum or Average 8760.00000 21.39733 35.98028 -0.7467 20.30505
Minimum of Months 672.00000 20.82222 23.60320 -1.2416 6.58298
Maximum of Months 744.00000 21.73312 51.85282 -0.2102 38.56995



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_3_MULT19_FLR_3 PEOPLE

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 0.00000 0.00000 0.00000 0.00000 0.00000
February 0.00000 0.00000 0.00000 0.00000 0.00000
March 0.00000 0.00000 0.00000 0.00000 0.00000
April 0.00000 0.00000 0.00000 0.00000 0.00000
May 0.00000 0.00000 0.00000 0.00000 0.00000
June 0.00000 0.00000 0.00000 0.00000 0.00000
July 0.00000 0.00000 0.00000 0.00000 0.00000
August 0.00000 0.00000 0.00000 0.00000 0.00000
September 0.00000 0.00000 0.00000 0.00000 0.00000
October 0.00000 0.00000 0.00000 0.00000 0.00000
November 0.00000 0.00000 0.00000 0.00000 0.00000
December 0.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 0.00000        
Minimum of Months 0.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 0.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_4_MULT19_FLR_3 PEOPLE

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.05966 26.75396 -0.5157 10.72624
February 672.00000 21.14587 23.54763 -0.4996 10.38047
March 744.00000 21.25138 22.44592 -0.4614 9.57719
April 720.00000 21.46832 25.87732 -0.3539 7.99969
May 744.00000 21.60726 34.57012 -1.3613 44.02245
June 720.00000 21.69077 40.25964 -1.2681 39.38127
July 744.00000 21.69538 52.15259 -1.1972 36.03163
August 744.00000 21.64928 49.96961 -1.2431 38.11090
September 720.00000 21.59768 49.09072 -1.2886 40.31506
October 744.00000 21.41548 44.03211 -0.2657 6.76533
November 720.00000 21.17395 28.32167 -0.4598 9.56467
December 744.00000 21.00785 23.54261 -0.5556 11.60994
           
Annual Sum or Average 8760.00000 21.39803 35.13230 -0.7910 22.11131
Minimum of Months 672.00000 21.00785 22.44592 -1.3613 6.76533
Maximum of Months 744.00000 21.69538 52.15259 -0.2657 44.02245



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_5_FLR_3 PEOPLE

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.25815 27.57862 -0.4639 10.04868
February 672.00000 21.42830 24.39954 -0.4092 9.24548
March 744.00000 21.54171 23.25527 -0.3635 8.62725
April 720.00000 21.70974 26.64570 -0.2320 7.20315
May 744.00000 21.74036 35.07551 -1.2098 37.13654
June 720.00000 21.75227 40.65066 -1.1133 32.63559
July 744.00000 21.74927 51.66964 -1.0576 30.19763
August 744.00000 21.73861 49.75837 -1.0886 31.57083
September 720.00000 21.74215 48.46666 -1.1103 32.67618
October 744.00000 21.65102 44.63139 -0.1478 6.40980
November 720.00000 21.46829 29.02077 -0.3606 8.76393
December 744.00000 21.20395 24.36444 -0.5065 10.88232
           
Annual Sum or Average 8760.00000 21.58231 35.54255 -0.6737 18.84467
Minimum of Months 672.00000 21.20395 23.25527 -1.2098 6.40980
Maximum of Months 744.00000 21.75227 51.66964 -0.1478 37.13654



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_6_FLR_3 PEOPLE

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 20.87683 28.07860 -0.5960 12.70910
February 672.00000 21.11846 24.73091 -0.5205 11.06954
March 744.00000 21.36042 23.45945 -0.4338 9.46748
April 720.00000 21.67645 26.70506 -0.2564 7.33586
May 744.00000 21.73945 35.09794 -1.2157 37.37499
June 720.00000 21.75315 40.66519 -1.1115 32.53768
July 744.00000 21.74955 51.76339 -1.0583 30.20019
August 744.00000 21.73535 50.01219 -1.1021 32.08270
September 720.00000 21.73404 48.94718 -1.1475 34.17508
October 744.00000 21.56475 45.22090 -0.2038 6.58078
November 720.00000 21.13773 29.50192 -0.4826 10.33292
December 744.00000 20.81642 24.81031 -0.6407 13.94200
           
Annual Sum or Average 8760.00000 21.43968 35.83225 -0.7323 19.87525
Minimum of Months 672.00000 20.81642 23.45945 -1.2157 6.58078
Maximum of Months 744.00000 21.75315 51.76339 -0.2038 37.37499



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_1_FLR_6 PEOPLE

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.15199 27.99619 -0.5180 11.46959
February 672.00000 21.29051 24.74951 -0.4737 10.62198
March 744.00000 21.40940 23.52746 -0.4125 9.56873
April 720.00000 21.61788 26.86498 -0.2518 7.58386
May 744.00000 21.69755 35.30806 -1.1999 36.94414
June 720.00000 21.73767 40.68105 -1.0833 31.53894
July 744.00000 21.73997 51.38045 -1.0259 29.06246
August 744.00000 21.72599 49.76044 -1.0613 30.61255
September 720.00000 21.71608 48.87165 -1.0913 32.15635
October 744.00000 21.61679 44.91902 -0.1442 6.55601
November 720.00000 21.37710 29.36386 -0.3983 9.66067
December 744.00000 21.10630 24.69150 -0.5682 12.53236
           
Annual Sum or Average 8760.00000 21.51639 35.75756 -0.6872 19.08145
Minimum of Months 672.00000 21.10630 23.52746 -1.1999 6.55601
Maximum of Months 744.00000 21.73997 51.38045 -0.1442 36.94414



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_2_FLR_6 PEOPLE

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 20.78756 28.50792 -0.6497 14.33483
February 672.00000 20.99283 25.10492 -0.5866 12.83918
March 744.00000 21.21889 23.76741 -0.4869 10.69843
April 720.00000 21.57072 26.94427 -0.2797 7.78198
May 744.00000 21.69180 35.32996 -1.2072 37.23364
June 720.00000 21.74022 40.66149 -1.0810 31.41457
July 744.00000 21.74131 51.39866 -1.0265 29.05282
August 744.00000 21.72125 50.02860 -1.0753 31.11335
September 720.00000 21.69360 49.59931 -1.1327 33.75412
October 744.00000 21.51304 45.74500 -0.2044 6.74634
November 720.00000 21.11016 29.79038 -0.5129 11.34488
December 744.00000 20.72768 25.15994 -0.7038 15.81296
           
Annual Sum or Average 8760.00000 21.37723 36.08456 -0.7468 20.22774
Minimum of Months 672.00000 20.72768 23.76741 -1.2072 6.74634
Maximum of Months 744.00000 21.74131 51.39866 -0.2044 37.23364



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_3_MULT9_FLR_6 PEOPLE

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.51025 28.40566 -0.3472 8.80212
February 672.00000 21.56985 25.32026 -0.3362 8.57519
March 744.00000 21.56931 24.15561 -0.3434 8.56191
April 720.00000 21.64807 27.61817 -0.2595 7.53613
May 744.00000 21.69076 36.06216 -1.2680 39.90752
June 720.00000 21.72757 41.43659 -1.1710 35.20167
July 744.00000 21.73115 51.91378 -1.1036 32.18755
August 744.00000 21.72180 49.78078 -1.1204 33.03261
September 720.00000 21.72392 48.60970 -1.1170 33.23012
October 744.00000 21.67087 44.29408 -0.1145 6.46688
November 720.00000 21.56707 29.75655 -0.2837 8.16031
December 744.00000 21.50503 25.29357 -0.3775 9.30834
           
Annual Sum or Average 8760.00000 21.63652 36.13335 -0.6555 19.31569
Minimum of Months 672.00000 21.50503 24.15561 -1.2680 6.46688
Maximum of Months 744.00000 21.73115 51.91378 -0.1145 39.90752



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: BANQUET_FLR_6 PEOPLE

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.26528 26.66394 -0.3216 7.38585
February 672.00000 21.31201 23.53182 -0.3121 7.29116
March 744.00000 21.39299 22.38872 -0.2800 6.87634
April 720.00000 21.57787 26.06050 -0.1708 6.00747
May 744.00000 21.75058 36.61912 -1.0783 30.16520
June 720.00000 21.93306 44.36712 -0.9254 23.84131
July 744.00000 21.90552 59.18206 -0.8469 20.78562
August 744.00000 21.83932 56.38717 -0.9035 22.90532
September 720.00000 21.69355 54.09286 -0.9941 26.50868
October 744.00000 21.52572 46.06487 -0.0719 5.54842
November 720.00000 21.33241 28.08113 -0.2755 6.87956
December 744.00000 21.22666 23.66164 -0.3588 7.86355
           
Annual Sum or Average 8760.00000 21.56420 37.36146 -0.5463 14.38001
Minimum of Months 672.00000 21.22666 22.38872 -1.0783 5.54842
Maximum of Months 744.00000 21.93306 59.18206 -0.0719 30.16520



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: DINING_FLR_6 PEOPLE

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.29951 26.42840 -0.2822 6.91699
February 672.00000 21.35119 23.29786 -0.2716 6.82521
March 744.00000 21.43936 22.14885 -0.2376 6.44893
April 720.00000 21.64362 25.78408 -0.1242 5.74593
May 744.00000 21.83209 36.26774 -1.0065 27.10659
June 720.00000 22.00838 43.99401 -0.8577 21.29711
July 744.00000 21.98178 58.73441 -0.7787 18.43638
August 744.00000 21.91080 55.97205 -0.8368 20.45824
September 720.00000 21.76036 53.70066 -0.9288 23.90713
October 744.00000 21.57822 45.74227 -0.0292 5.48350
November 720.00000 21.37171 27.83391 -0.2352 6.47942
December 744.00000 21.25914 23.43315 -0.3194 7.33337
           
Annual Sum or Average 8760.00000 21.62105 37.04727 -0.4937 13.07314
Minimum of Months 672.00000 21.25914 22.14885 -1.0065 5.48350
Maximum of Months 744.00000 22.00838 58.73441 -0.0292 27.10659



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: KITCHEN_FLR_6 PEOPLE

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 22.68392 26.38521 0.65091 18.99511
February 672.00000 22.77875 23.51065 0.67991 20.01074
March 744.00000 22.84798 22.36422 0.71466 21.24991
April 720.00000 23.01520 25.57177 0.83730 25.54931
May 744.00000 23.10856 35.08927 0.33780 19.08382
June 720.00000 23.17763 42.62625 0.46486 20.28481
July 744.00000 23.16288 56.15785 0.54163 21.57354
August 744.00000 23.14024 53.46182 0.49691 20.69194
September 720.00000 23.10037 51.13803 0.44127 20.10801
October 744.00000 22.96924 43.76715 0.92845 28.36706
November 720.00000 22.79665 27.53865 0.71712 21.22993
December 744.00000 22.65283 23.70266 0.61567 18.02481
           
Annual Sum or Average 8760.00000 22.95352 36.03647 0.61841 21.26859
Minimum of Months 672.00000 22.65283 22.36422 0.33780 18.02481
Maximum of Months 744.00000 23.17763 56.15785 0.92845 28.36706



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: STORAGE_FLR_1 PEOPLE

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.00012 23.19187 -0.5357 11.07120
February 672.00000 21.00013 20.05601 -0.5457 11.29397
March 744.00000 21.00015 18.95775 -0.5415 11.17122
April 720.00000 21.00104 22.92222 -0.4942 10.22152
May 744.00000 21.01448 34.10409 -1.5928 55.94226
June 720.00000 21.08219 42.48748 -1.4997 50.89869
July 744.00000 21.06352 58.74147 -1.4123 46.18389
August 744.00000 21.03740 55.28578 -1.4492 48.16235
September 720.00000 21.00834 52.65068 -1.4855 50.14919
October 744.00000 21.00130 43.65668 -0.3730 8.03217
November 720.00000 21.00013 24.73200 -0.5120 10.56023
December 744.00000 21.00014 20.08094 -0.5587 11.56906
           
Annual Sum or Average 8760.00000 21.01749 34.84908 -0.9189 27.19785
Minimum of Months 672.00000 21.00012 18.95775 -1.5928 8.03217
Maximum of Months 744.00000 21.08219 58.74147 -0.3730 55.94226



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORRIDOR_FLR_3 PEOPLE

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.00053 25.36225 -0.5156 10.61439
February 672.00000 21.00554 22.21158 -0.5257 10.82988
March 744.00000 21.01144 21.11799 -0.5251 10.79663
April 720.00000 21.13520 24.90241 -0.4616 9.59347
May 744.00000 21.44929 35.37029 -1.4733 49.51047
June 720.00000 21.89922 42.73231 -1.2702 38.83900
July 744.00000 21.82869 58.05847 -1.2016 35.37675
August 744.00000 21.75840 55.07887 -1.2453 37.59162
September 720.00000 21.63515 52.76772 -1.3010 40.44484
October 744.00000 21.23136 45.17090 -0.3165 7.28632
November 720.00000 21.01991 26.85485 -0.4904 10.10626
December 744.00000 21.00043 22.26759 -0.5372 11.06613
           
Annual Sum or Average 8760.00000 21.33294 36.09551 -0.8237 22.74591
Minimum of Months 672.00000 21.00043 21.11799 -1.4733 7.28632
Maximum of Months 744.00000 21.89922 58.05847 -0.3165 49.51047



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORRIDOR_FLR_6 PEOPLE

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.00053 23.83993 -0.5300 10.95946
February 672.00000 21.00079 20.70471 -0.5328 11.01696
March 744.00000 21.00092 19.58945 -0.5248 10.82015
April 720.00000 21.03217 23.50660 -0.4552 9.52173
May 744.00000 21.10307 34.56012 -1.5125 51.61975
June 720.00000 21.41867 42.38890 -1.3281 41.84120
July 744.00000 21.37818 57.95888 -1.2500 37.85815
August 744.00000 21.30374 54.94477 -1.3018 40.51418
September 720.00000 21.18437 52.55319 -1.3715 44.16686
October 744.00000 21.05857 44.08086 -0.3284 7.46525
November 720.00000 21.00247 25.36620 -0.4970 10.28157
December 744.00000 21.00012 20.74387 -0.5583 11.57932
           
Annual Sum or Average 8760.00000 21.12425 35.12721 -0.8511 24.04964
Minimum of Months 672.00000 21.00012 19.58945 -1.5125 7.46525
Maximum of Months 744.00000 21.41867 57.95888 -0.3284 51.61975



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: MECH_FLR_1 PEOPLE

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.00010 23.01065 -0.5155 10.62566
February 672.00000 21.00010 19.87506 -0.5259 10.84866
March 744.00000 21.00026 18.77128 -0.5217 10.72878
April 720.00000 21.01554 22.71621 -0.4722 9.78489
May 744.00000 21.05887 33.83098 -1.5533 53.81118
June 720.00000 21.15471 42.13586 -1.4529 48.40056
July 744.00000 21.13300 58.24297 -1.3672 43.82167
August 744.00000 21.09640 54.88717 -1.4066 45.90497
September 720.00000 21.04740 52.30921 -1.4479 48.13818
October 744.00000 21.01188 43.43142 -0.3520 7.72531
November 720.00000 21.00031 24.54824 -0.4924 10.14919
December 744.00000 21.00007 19.90165 -0.5379 11.09099
           
Annual Sum or Average 8760.00000 21.04345 34.58122 -0.8892 26.00798
Minimum of Months 672.00000 21.00007 18.77128 -1.5533 7.72531
Maximum of Months 744.00000 21.15471 58.24297 -0.3520 53.81118



Table of Contents

Report: ChillerReportMonthly

For: COOLSYS1 CHILLER1

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

CHILLER ELECTRICITY ENERGY [J] CHILLER ELECTRICITY RATE {Maximum} [W] CHILLER ELECTRICITY RATE {TIMESTAMP} CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] CHILLER EVAPORATOR COOLING ENERGY [J] CHILLER EVAPORATOR COOLING RATE [] CHILLER CONDENSER HEAT TRANSFER ENERGY [J] CHILLER COP [W/W] CHILLER COP {Maximum} [W/W] CHILLER COP {TIMESTAMP} CHILLER PART LOAD RATIO [] CHILLER PART LOAD RATIO []
January 0.209948E+11 93871.28 03-JAN-16:01 437.64 0.604071E+11 0.00 0.814019E+11 1.72 3.36 03-JAN-16:01 0.00 0.00
February 0.444274E+11 129766.38 20-FEB-16:01 495.22 0.129965E+12 0.00 0.174392E+12 2.15 3.71 19-FEB-19:01 0.00 0.00
March 0.752798E+11 136163.13 21-MAR-15:01 612.53 0.221399E+12 0.00 0.296679E+12 2.40 3.75 22-MAR-18:02 0.00 0.00
April 0.179566E+12 200145.02 21-APR-15:03 706.32 0.543500E+12 0.00 0.723066E+12 2.92 3.73 12-APR-18:01 0.00 0.00
May 0.278388E+12 211448.92 19-MAY-15:03 744.00 0.843371E+12 0.00 0.112176E+13 3.01 3.81 28-MAY-19:00 0.00 0.00
June 0.355970E+12 269287.56 14-JUN-18:03 720.00 0.105431E+13 0.00 0.141028E+13 3.00 3.85 28-JUN-08:62 0.00 0.00
July 0.422527E+12 259215.32 21-JUL-18:03 744.00 0.136388E+13 0.00 0.178640E+13 3.25 4.18 18-JUL-21:00 0.00 0.00
August 0.361581E+12 241415.11 04-AUG-15:15 744.00 0.113868E+13 0.00 0.150026E+13 3.17 4.13 16-AUG-18:02 0.00 0.00
September 0.300733E+12 214043.22 01-SEP-15:03 720.00 0.980422E+12 0.00 0.128115E+13 3.23 4.30 23-SEP-18:03 0.00 0.00
October 0.175237E+12 210469.25 01-OCT-15:03 743.50 0.548418E+12 0.00 0.723655E+12 3.03 3.94 04-OCT-08:62 0.00 0.00
November 0.586973E+11 131370.30 09-NOV-16:01 538.52 0.171513E+12 0.00 0.230210E+12 2.18 3.76 09-NOV-19:01 0.00 0.00
December 0.161009E+11 73879.01 10-DEC-16:01 406.95 0.462090E+11 0.00 0.623099E+11 1.60 3.03 10-DEC-16:01 0.00 0.00
                         
Annual Sum or Average 0.228950E+13     7612.68 0.710207E+13 0.00 0.939157E+13 2.64     0.00 0.00
Minimum of Months 0.161009E+11 73879.01   406.95 0.462090E+11 0.00 0.623099E+11 1.60 3.03   0.00 0.00
Maximum of Months 0.422527E+12 269287.56   744.00 0.136388E+13 0.00 0.178640E+13 3.25 4.30   0.00 0.00



Table of Contents

Report: BoilerReportMonthly

For: HEATSYS1 BOILER

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

BOILER HEATING ENERGY [J] BOILER GAS CONSUMPTION [] BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] BOILER HEATING RATE {Maximum} [W] BOILER HEATING RATE {TIMESTAMP} BOILER GAS CONSUMPTION RATE [] BOILER INLET TEMPERATURE [C] BOILER OUTLET TEMPERATURE [C] BOILER MASS FLOW RATE [kg/s] BOILER ANCILLARY ELECTRICITY RATE [W] BOILER PART LOAD RATIO [] BOILER PART LOAD RATIO {Maximum} [] BOILER PART LOAD RATIO {TIMESTAMP}
January 0.126721E+12 0.00 744.00 160680.34 27-JAN-09:02 0.00 35.12 60.00 0.48 0.00 0.10 0.33 27-JAN-09:02
February 0.101869E+12 0.00 672.00 155354.24 03-FEB-07:10 0.00 34.34 60.00 0.42 0.00 0.09 0.32 03-FEB-07:10
March 0.979744E+11 0.00 744.00 155356.75 02-MAR-09:02 0.00 33.93 60.00 0.36 0.00 0.08 0.32 02-MAR-09:02
April 0.586368E+11 0.00 713.17 91791.34 11-APR-08:62 0.00 32.84 59.73 0.21 0.00 0.05 0.19 11-APR-08:62
May 0.450340E+11 0.00 716.06 78325.35 23-MAY-08:04 0.00 32.72 58.96 0.15 0.00 0.03 0.16 23-MAY-08:04
June 0.360485E+11 0.00 663.14 68798.46 23-JUN-08:04 0.00 33.39 57.85 0.13 0.00 0.03 0.14 23-JUN-08:04
July 0.308091E+11 0.00 660.14 69610.16 21-JUL-10:35 0.00 31.24 56.56 0.10 0.00 0.02 0.14 21-JUL-10:35
August 0.273493E+11 0.00 667.00 66339.21 18-AUG-10:35 0.00 30.08 56.70 0.08 0.00 0.02 0.14 18-AUG-10:35
September 0.248923E+11 0.00 677.89 69422.63 15-SEP-08:04 0.00 29.91 58.21 0.08 0.00 0.02 0.14 15-SEP-08:04
October 0.390698E+11 0.00 735.81 88051.01 13-OCT-08:05 0.00 29.56 59.67 0.12 0.00 0.03 0.18 13-OCT-08:05
November 0.842367E+11 0.00 720.00 148981.37 28-NOV-09:02 0.00 32.95 60.00 0.32 0.00 0.07 0.31 28-NOV-09:02
December 0.139381E+12 0.00 744.00 156975.75 27-DEC-09:02 0.00 35.54 60.00 0.54 0.00 0.11 0.32 27-DEC-09:02
                           
Annual Sum or Average 0.812022E+12 0.00 8457.19     0.00 32.62 58.96 0.25 0.00 0.05    
Minimum of Months 0.248923E+11 0.00 660.14 66339.21   0.00 29.56 56.56 0.08 0.00 0.02 0.14  
Maximum of Months 0.139381E+12 0.00 744.00 160680.34   0.00 35.54 60.00 0.54 0.00 0.11 0.33  



Table of Contents

Report: DXReportMonthly

For: VAV WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.201108E+11 0.00 95.22 0.201108E+11 0.00 0.00 0.00 0.00 192380.40 03-JAN-17:00 192380.40 03-JAN-17:00 0.00 0.00 0.00
February 0.759769E+11 0.00 199.86 0.759769E+11 0.00 0.00 0.00 0.00 233415.98 20-FEB-11:50 233415.98 20-FEB-11:50 0.00 0.00 0.00
March 0.145448E+12 0.00 327.59 0.145448E+12 0.00 0.00 0.00 0.00 260781.39 14-MAR-17:13 260781.39 14-MAR-17:13 0.00 0.00 0.00
April 0.382942E+12 0.00 588.06 0.382942E+12 0.00 0.00 0.00 0.00 333076.85 19-APR-18:10 333076.85 19-APR-18:10 0.00 0.00 0.00
May 0.597793E+12 0.00 726.83 0.591323E+12 0.00 0.00 0.00 0.00 410770.20 28-MAY-10:35 365786.80 19-MAY-17:12 0.00 0.00 0.00
June 0.736192E+12 0.00 720.00 0.720033E+12 0.00 0.00 0.00 0.00 450614.15 19-JUN-18:10 408064.65 02-JUN-17:13 0.00 0.00 0.00
July 0.981701E+12 0.00 744.00 0.745816E+12 0.00 0.00 0.00 0.00 677044.84 21-JUL-06:30 406142.32 03-JUL-17:13 0.00 0.00 0.00
August 0.808393E+12 0.00 744.00 0.700978E+12 0.00 0.00 0.00 0.00 593511.92 01-AUG-21:00 390034.35 07-AUG-17:13 0.00 0.00 0.00
September 0.694503E+12 0.00 699.50 0.565639E+12 0.00 0.00 0.00 0.00 536772.07 22-SEP-02:00 355672.63 19-SEP-16:20 0.00 0.00 0.00
October 0.364337E+12 0.00 591.47 0.340216E+12 0.00 0.00 0.00 0.00 466255.17 03-OCT-20:30 326774.47 05-OCT-16:00 0.00 0.00 0.00
November 0.944464E+11 0.00 266.29 0.944464E+11 0.00 0.00 0.00 0.00 247738.69 03-NOV-16:00 247738.69 03-NOV-16:00 0.00 0.00 0.00
December 0.146740E+11 0.00 98.38 0.146740E+11 0.00 0.00 0.00 0.00 127386.92 10-DEC-15:00 127386.92 10-DEC-15:00 0.00 0.00 0.00
                               
Annual Sum or Average 0.491652E+13 0.00 5801.20 0.439760E+13 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.146740E+11 0.00 95.22 0.146740E+11 0.00 0.00 0.00 0.00 127386.92   127386.92   0.00 0.00 0.00
Maximum of Months 0.981701E+12 0.00 744.00 0.745816E+12 0.00 0.00 0.00 0.00 677044.84   408064.65   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: FLR_3_DOAS COOLING COIL

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.122869E+10 0.00 63.67 0.122869E+10 0.00 0.00 0.00 0.00 18651.05 03-JAN-15:00 18651.05 03-JAN-15:00 0.00 0.00 0.00
February 0.621055E+10 0.00 159.50 0.621055E+10 0.00 0.00 0.00 0.00 24890.15 20-FEB-15:00 24890.15 20-FEB-15:00 0.00 0.00 0.00
March 0.124469E+11 0.00 278.00 0.124469E+11 0.00 0.00 0.00 0.00 28566.40 21-MAR-16:00 28566.40 21-MAR-16:00 0.00 0.00 0.00
April 0.399969E+11 0.00 548.50 0.399969E+11 0.00 0.00 0.00 0.00 44409.17 21-APR-15:00 44409.17 21-APR-15:00 0.00 0.00 0.00
May 0.693058E+11 0.00 713.33 0.674714E+11 0.00 0.00 0.00 0.00 50585.42 19-MAY-14:00 50585.42 19-MAY-14:00 0.00 0.00 0.00
June 0.932452E+11 0.00 720.00 0.894911E+11 0.00 0.00 0.00 0.00 58655.85 02-JUN-17:00 58655.85 02-JUN-17:00 0.00 0.00 0.00
July 0.127410E+12 0.00 744.00 0.896819E+11 0.00 0.00 0.00 0.00 65741.82 20-JUL-16:00 54269.30 06-JUL-16:00 0.00 0.00 0.00
August 0.102279E+12 0.00 744.00 0.830713E+11 0.00 0.00 0.00 0.00 58860.95 02-AUG-12:00 55376.52 07-AUG-16:00 0.00 0.00 0.00
September 0.814589E+11 0.00 692.83 0.629435E+11 0.00 0.00 0.00 0.00 55192.93 14-SEP-10:00 48186.26 19-SEP-14:00 0.00 0.00 0.00
October 0.377637E+11 0.00 534.83 0.336702E+11 0.00 0.00 0.00 0.00 52564.31 03-OCT-14:00 45726.84 01-OCT-15:00 0.00 0.00 0.00
November 0.755815E+10 0.00 211.33 0.755815E+10 0.00 0.00 0.00 0.00 26388.16 03-NOV-16:00 26388.16 03-NOV-16:00 0.00 0.00 0.00
December 0.724489E+09 0.00 54.00 0.724489E+09 0.00 0.00 0.00 0.00 11238.20 10-DEC-15:00 11238.20 10-DEC-15:00 0.00 0.00 0.00
                               
Annual Sum or Average 0.579628E+12 0.00 5464.00 0.494495E+12 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.724489E+09 0.00 54.00 0.724489E+09 0.00 0.00 0.00 0.00 11238.20   11238.20   0.00 0.00 0.00
Maximum of Months 0.127410E+12 0.00 744.00 0.896819E+11 0.00 0.00 0.00 0.00 65741.82   58655.85   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_1_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.722115E+09 0.00 158.78 0.720641E+09 0.00 0.00 0.00 0.00 18116.34 01-JAN-16:02 18116.34 01-JAN-16:02 0.00 0.00 0.00
February 0.120688E+10 0.00 205.68 0.120552E+10 0.00 0.00 0.00 0.00 18089.20 18-FEB-16:01 18089.20 18-FEB-16:01 0.00 0.00 0.00
March 0.226720E+10 0.00 325.77 0.225421E+10 0.00 0.00 0.00 0.00 18096.24 12-MAR-15:01 18096.24 12-MAR-15:01 0.00 0.00 0.00
April 0.546037E+10 0.00 569.21 0.512260E+10 0.00 0.00 0.00 0.00 18122.49 17-APR-18:01 18122.49 17-APR-18:01 0.00 0.00 0.00
May 0.876234E+10 0.00 678.24 0.753288E+10 0.00 0.00 0.00 0.00 18730.83 28-MAY-08:61 18122.69 31-MAY-15:02 0.00 0.00 0.00
June 0.115697E+11 0.00 682.51 0.920445E+10 0.00 0.00 0.00 0.00 18607.62 28-JUN-08:62 18122.56 21-JUN-15:02 0.00 0.00 0.00
July 0.127687E+11 0.00 707.05 0.777143E+10 0.00 0.00 0.00 0.00 21980.88 19-JUL-08:62 16925.78 30-JUL-18:02 0.00 0.00 0.00
August 0.113529E+11 0.00 693.06 0.718810E+10 0.00 0.00 0.00 0.00 20204.96 02-AUG-08:61 18121.92 23-AUG-15:01 0.00 0.00 0.00
September 0.100953E+11 0.00 672.88 0.634610E+10 0.00 0.00 0.00 0.00 20228.89 09-SEP-08:61 18122.45 18-SEP-18:01 0.00 0.00 0.00
October 0.608411E+10 0.00 605.17 0.415205E+10 0.00 0.00 0.00 0.00 19090.18 04-OCT-08:62 18121.16 19-OCT-15:01 0.00 0.00 0.00
November 0.206946E+10 0.00 324.78 0.188067E+10 0.00 0.00 0.00 0.00 18123.27 04-NOV-15:01 18123.27 04-NOV-15:01 0.00 0.00 0.00
December 0.415065E+09 0.00 114.52 0.415065E+09 0.00 0.00 0.00 0.00 18086.00 07-DEC-16:01 18086.00 07-DEC-16:01 0.00 0.00 0.00
                               
Annual Sum or Average 0.727741E+11 0.00 5737.65 0.537937E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.415065E+09 0.00 114.52 0.415065E+09 0.00 0.00 0.00 0.00 18086.00   16925.78   0.00 0.00 0.00
Maximum of Months 0.127687E+11 0.00 707.05 0.920445E+10 0.00 0.00 0.00 0.00 21980.88   18123.27   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_2_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.127140E+09 0.00 39.62 0.126798E+09 0.00 0.00 0.00 0.00 17677.89 12-JAN-16:01 17677.89 12-JAN-16:01 0.00 0.00 0.00
February 0.423650E+09 0.00 98.91 0.422969E+09 0.00 0.00 0.00 0.00 17958.79 18-FEB-16:01 17958.79 18-FEB-16:01 0.00 0.00 0.00
March 0.136437E+10 0.00 231.75 0.135368E+10 0.00 0.00 0.00 0.00 17961.97 12-MAR-15:01 17961.97 12-MAR-15:01 0.00 0.00 0.00
April 0.466002E+10 0.00 523.87 0.436151E+10 0.00 0.00 0.00 0.00 17992.74 17-APR-18:01 17992.74 17-APR-18:01 0.00 0.00 0.00
May 0.854167E+10 0.00 670.25 0.733311E+10 0.00 0.00 0.00 0.00 18575.57 28-MAY-08:61 17992.86 31-MAY-15:02 0.00 0.00 0.00
June 0.116408E+11 0.00 683.84 0.929468E+10 0.00 0.00 0.00 0.00 18500.58 28-JUN-08:62 17992.70 21-JUN-15:02 0.00 0.00 0.00
July 0.127116E+11 0.00 707.57 0.776970E+10 0.00 0.00 0.00 0.00 21770.64 19-JUL-08:62 16867.14 30-JUL-18:02 0.00 0.00 0.00
August 0.107086E+11 0.00 686.92 0.667650E+10 0.00 0.00 0.00 0.00 20137.60 02-AUG-08:61 17992.21 23-AUG-15:01 0.00 0.00 0.00
September 0.847497E+10 0.00 650.85 0.499668E+10 0.00 0.00 0.00 0.00 20082.86 23-SEP-18:01 17993.12 18-SEP-18:01 0.00 0.00 0.00
October 0.406830E+10 0.00 504.51 0.259372E+10 0.00 0.00 0.00 0.00 18881.85 04-OCT-08:62 17992.66 25-OCT-15:01 0.00 0.00 0.00
November 0.656897E+09 0.00 159.03 0.558419E+09 0.00 0.00 0.00 0.00 17991.11 09-NOV-16:01 17991.11 09-NOV-16:01 0.00 0.00 0.00
December 49598812.63 0.00 17.24 49598812.63 0.00 0.00 0.00 0.00 17361.38 16-DEC-16:02 17361.38 16-DEC-16:02 0.00 0.00 0.00
                               
Annual Sum or Average 0.634276E+11 0.00 4974.38 0.455374E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 49598812.63 0.00 17.24 49598812.63 0.00 0.00 0.00 0.00 17361.38   16867.14   0.00 0.00 0.00
Maximum of Months 0.127116E+11 0.00 707.57 0.929468E+10 0.00 0.00 0.00 0.00 21770.64   17993.12   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.187338E+11 0.00 329.06 0.187338E+11 0.00 0.00 0.00 0.00 42039.10 12-JAN-14:30 42039.10 12-JAN-14:30 0.00 0.00 0.00
February 0.186891E+11 0.00 354.31 0.186666E+11 0.00 0.00 0.00 0.00 40287.64 07-FEB-13:40 40287.64 07-FEB-13:40 0.00 0.00 0.00
March 0.178191E+11 0.00 390.81 0.176597E+11 0.00 0.00 0.00 0.00 32128.75 16-MAR-13:30 32128.75 16-MAR-13:30 0.00 0.00 0.00
April 0.286378E+11 0.00 544.85 0.275079E+11 0.00 0.00 0.00 0.00 31143.23 03-APR-14:00 31143.23 03-APR-14:00 0.00 0.00 0.00
May 0.372407E+11 0.00 673.42 0.314968E+11 0.00 0.00 0.00 0.00 32772.64 19-MAY-20:20 32772.64 19-MAY-20:20 0.00 0.00 0.00
June 0.490596E+11 0.00 710.42 0.377855E+11 0.00 0.00 0.00 0.00 37380.51 17-JUN-18:25 37380.51 17-JUN-18:25 0.00 0.00 0.00
July 0.582359E+11 0.00 743.17 0.294422E+11 0.00 0.00 0.00 0.00 40363.45 02-JUL-20:40 40363.45 02-JUL-20:40 0.00 0.00 0.00
August 0.552429E+11 0.00 730.19 0.324876E+11 0.00 0.00 0.00 0.00 40451.04 06-AUG-19:05 37638.48 27-AUG-13:50 0.00 0.00 0.00
September 0.589986E+11 0.00 698.89 0.396780E+11 0.00 0.00 0.00 0.00 50495.60 19-SEP-13:10 45036.56 17-SEP-13:20 0.00 0.00 0.00
October 0.499915E+11 0.00 653.11 0.393898E+11 0.00 0.00 0.00 0.00 54374.54 22-OCT-13:40 49921.86 29-OCT-13:00 0.00 0.00 0.00
November 0.320013E+11 0.00 426.31 0.310643E+11 0.00 0.00 0.00 0.00 48108.55 09-NOV-13:50 48108.55 09-NOV-13:50 0.00 0.00 0.00
December 0.142146E+11 0.00 293.92 0.142146E+11 0.00 0.00 0.00 0.00 38082.67 16-DEC-13:40 38082.67 16-DEC-13:40 0.00 0.00 0.00
                               
Annual Sum or Average 0.438865E+12 0.00 6548.44 0.338127E+12 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.142146E+11 0.00 293.92 0.142146E+11 0.00 0.00 0.00 0.00 31143.23   31143.23   0.00 0.00 0.00
Maximum of Months 0.589986E+11 0.00 743.17 0.396780E+11 0.00 0.00 0.00 0.00 54374.54   49921.86   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.500924E+10 0.00 185.85 0.470017E+10 0.00 0.00 0.00 0.00 109209.76 13-JAN-19:02 109209.76 13-JAN-19:02 0.00 0.00 0.00
February 0.952481E+10 0.00 272.78 0.888985E+10 0.00 0.00 0.00 0.00 112954.08 20-FEB-09:01 112954.08 20-FEB-09:01 0.00 0.00 0.00
March 0.182443E+11 0.00 406.39 0.178289E+11 0.00 0.00 0.00 0.00 115105.18 15-MAR-18:01 115105.18 15-MAR-18:01 0.00 0.00 0.00
April 0.405932E+11 0.00 508.40 0.383877E+11 0.00 0.00 0.00 0.00 120021.63 28-APR-18:01 120021.63 28-APR-18:01 0.00 0.00 0.00
May 0.650000E+11 0.00 586.99 0.570325E+11 0.00 0.00 0.00 0.00 120151.00 28-MAY-08:61 120053.67 08-MAY-18:01 0.00 0.00 0.00
June 0.833085E+11 0.00 630.28 0.686231E+11 0.00 0.00 0.00 0.00 120394.27 28-JUN-08:62 120045.06 21-JUN-15:02 0.00 0.00 0.00
July 0.951723E+11 0.00 655.87 0.627338E+11 0.00 0.00 0.00 0.00 144018.26 19-JUL-08:62 112770.98 28-JUL-18:02 0.00 0.00 0.00
August 0.805664E+11 0.00 616.90 0.533239E+11 0.00 0.00 0.00 0.00 130555.13 02-AUG-08:61 120062.95 27-AUG-18:01 0.00 0.00 0.00
September 0.635069E+11 0.00 558.06 0.400279E+11 0.00 0.00 0.00 0.00 134191.44 23-SEP-18:01 120060.29 17-SEP-18:01 0.00 0.00 0.00
October 0.408900E+11 0.00 529.25 0.266324E+11 0.00 0.00 0.00 0.00 122745.68 04-OCT-08:62 120029.34 01-OCT-18:01 0.00 0.00 0.00
November 0.116994E+11 0.00 324.31 0.996162E+10 0.00 0.00 0.00 0.00 113548.45 11-NOV-09:01 113548.45 11-NOV-09:01 0.00 0.00 0.00
December 0.336045E+10 0.00 139.40 0.336045E+10 0.00 0.00 0.00 0.00 111643.78 09-DEC-09:01 111643.78 09-DEC-09:01 0.00 0.00 0.00
                               
Annual Sum or Average 0.516875E+12 0.00 5414.47 0.391502E+12 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.336045E+10 0.00 139.40 0.336045E+10 0.00 0.00 0.00 0.00 109209.76   109209.76   0.00 0.00 0.00
Maximum of Months 0.951723E+11 0.00 655.87 0.686231E+11 0.00 0.00 0.00 0.00 144018.26   120062.95   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_5_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.609955E+09 0.00 143.21 0.606864E+09 0.00 0.00 0.00 0.00 15862.15 12-JAN-16:01 15862.15 12-JAN-16:01 0.00 0.00 0.00
February 0.132023E+10 0.00 241.57 0.131359E+10 0.00 0.00 0.00 0.00 15875.09 08-FEB-09:01 15875.09 08-FEB-09:01 0.00 0.00 0.00
March 0.226342E+10 0.00 368.39 0.225232E+10 0.00 0.00 0.00 0.00 15859.33 07-MAR-09:01 15859.33 07-MAR-09:01 0.00 0.00 0.00
April 0.567944E+10 0.00 613.27 0.532430E+10 0.00 0.00 0.00 0.00 15874.38 28-APR-18:01 15874.38 28-APR-18:01 0.00 0.00 0.00
May 0.888487E+10 0.00 714.57 0.763547E+10 0.00 0.00 0.00 0.00 15875.28 31-MAY-15:02 15875.28 31-MAY-15:02 0.00 0.00 0.00
June 0.118750E+11 0.00 704.83 0.952314E+10 0.00 0.00 0.00 0.00 16515.28 28-JUN-08:62 15875.61 21-JUN-15:02 0.00 0.00 0.00
July 0.130746E+11 0.00 725.33 0.807924E+10 0.00 0.00 0.00 0.00 19223.52 19-JUL-08:62 14872.21 13-JUL-08:61 0.00 0.00 0.00
August 0.115969E+11 0.00 716.02 0.739006E+10 0.00 0.00 0.00 0.00 17340.53 18-AUG-08:62 15875.29 23-AUG-15:01 0.00 0.00 0.00
September 0.101459E+11 0.00 693.18 0.640534E+10 0.00 0.00 0.00 0.00 17531.86 23-SEP-18:01 15874.26 18-SEP-18:01 0.00 0.00 0.00
October 0.564508E+10 0.00 593.13 0.389281E+10 0.00 0.00 0.00 0.00 17124.40 09-OCT-08:62 15875.17 25-OCT-15:01 0.00 0.00 0.00
November 0.190716E+10 0.00 325.73 0.176934E+10 0.00 0.00 0.00 0.00 15873.57 09-NOV-16:01 15873.57 09-NOV-16:01 0.00 0.00 0.00
December 0.436861E+09 0.00 108.43 0.436861E+09 0.00 0.00 0.00 0.00 15857.54 09-DEC-09:01 15857.54 09-DEC-09:01 0.00 0.00 0.00
                               
Annual Sum or Average 0.734393E+11 0.00 5947.66 0.546294E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.436861E+09 0.00 108.43 0.436861E+09 0.00 0.00 0.00 0.00 15857.54   14872.21   0.00 0.00 0.00
Maximum of Months 0.130746E+11 0.00 725.33 0.952314E+10 0.00 0.00 0.00 0.00 19223.52   15875.61   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_6_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 59193127.27 0.00 27.69 58573583.11 0.00 0.00 0.00 0.00 10552.22 31-JAN-09:02 10552.22 31-JAN-09:02 0.00 0.00 0.00
February 0.469791E+09 0.00 111.19 0.464288E+09 0.00 0.00 0.00 0.00 15725.79 19-FEB-09:01 15725.79 19-FEB-09:01 0.00 0.00 0.00
March 0.130087E+10 0.00 247.94 0.129413E+10 0.00 0.00 0.00 0.00 15730.28 07-MAR-09:01 15730.28 07-MAR-09:01 0.00 0.00 0.00
April 0.483194E+10 0.00 564.52 0.450165E+10 0.00 0.00 0.00 0.00 15745.13 28-APR-18:01 15745.13 28-APR-18:01 0.00 0.00 0.00
May 0.864751E+10 0.00 711.20 0.741971E+10 0.00 0.00 0.00 0.00 15746.09 31-MAY-15:02 15746.09 31-MAY-15:02 0.00 0.00 0.00
June 0.119435E+11 0.00 705.56 0.962191E+10 0.00 0.00 0.00 0.00 16208.19 28-JUN-08:62 15746.38 21-JUN-15:02 0.00 0.00 0.00
July 0.130094E+11 0.00 725.56 0.805837E+10 0.00 0.00 0.00 0.00 19021.43 19-JUL-08:62 14724.07 09-JUL-08:61 0.00 0.00 0.00
August 0.109444E+11 0.00 710.78 0.685094E+10 0.00 0.00 0.00 0.00 17179.76 18-AUG-08:62 15745.36 27-AUG-15:02 0.00 0.00 0.00
September 0.849771E+10 0.00 679.95 0.507713E+10 0.00 0.00 0.00 0.00 17570.65 23-SEP-18:01 15745.60 11-SEP-08:62 0.00 0.00 0.00
October 0.360323E+10 0.00 476.94 0.231320E+10 0.00 0.00 0.00 0.00 16961.32 09-OCT-08:62 15743.68 01-OCT-18:01 0.00 0.00 0.00
November 0.585874E+09 0.00 139.24 0.514753E+09 0.00 0.00 0.00 0.00 15738.93 11-NOV-09:01 15738.93 11-NOV-09:01 0.00 0.00 0.00
December 42956447.95 0.00 18.30 42956447.95 0.00 0.00 0.00 0.00 14941.11 09-DEC-09:01 14941.11 09-DEC-09:01 0.00 0.00 0.00
                               
Annual Sum or Average 0.639364E+11 0.00 5118.86 0.462176E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 42956447.95 0.00 18.30 42956447.95 0.00 0.00 0.00 0.00 10552.22   10552.22   0.00 0.00 0.00
Maximum of Months 0.130094E+11 0.00 725.56 0.962191E+10 0.00 0.00 0.00 0.00 19021.43   15746.38   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_1_FLR_6 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.154784E+09 0.00 115.90 0.154121E+09 0.00 0.00 0.00 0.00 4910.70 01-JAN-16:02 4910.70 01-JAN-16:02 0.00 0.00 0.00
February 0.294475E+09 0.00 166.92 0.294142E+09 0.00 0.00 0.00 0.00 4903.32 18-FEB-16:01 4903.32 18-FEB-16:01 0.00 0.00 0.00
March 0.588547E+09 0.00 293.32 0.585991E+09 0.00 0.00 0.00 0.00 4905.26 12-MAR-15:01 4905.26 12-MAR-15:01 0.00 0.00 0.00
April 0.155247E+10 0.00 553.43 0.146061E+10 0.00 0.00 0.00 0.00 4912.21 17-APR-18:01 4912.21 17-APR-18:01 0.00 0.00 0.00
May 0.252069E+10 0.00 682.72 0.218838E+10 0.00 0.00 0.00 0.00 5153.34 28-MAY-08:61 4912.37 31-MAY-15:02 0.00 0.00 0.00
June 0.336670E+10 0.00 689.85 0.271700E+10 0.00 0.00 0.00 0.00 5157.48 28-JUN-08:62 4912.57 05-JUN-18:02 0.00 0.00 0.00
July 0.371169E+10 0.00 713.59 0.236371E+10 0.00 0.00 0.00 0.00 6142.55 19-JUL-08:62 4527.84 04-JUL-18:02 0.00 0.00 0.00
August 0.328258E+10 0.00 703.38 0.215465E+10 0.00 0.00 0.00 0.00 5554.53 02-AUG-08:61 4912.25 23-AUG-15:01 0.00 0.00 0.00
September 0.285224E+10 0.00 671.97 0.186364E+10 0.00 0.00 0.00 0.00 5617.95 09-SEP-08:61 4912.41 18-SEP-18:01 0.00 0.00 0.00
October 0.165147E+10 0.00 569.37 0.115670E+10 0.00 0.00 0.00 0.00 5258.38 04-OCT-08:62 4912.05 19-OCT-15:01 0.00 0.00 0.00
November 0.511879E+09 0.00 281.68 0.466981E+09 0.00 0.00 0.00 0.00 4912.59 04-NOV-15:01 4912.59 04-NOV-15:01 0.00 0.00 0.00
December 84102887.94 0.00 76.42 84102887.94 0.00 0.00 0.00 0.00 4908.03 04-DEC-16:01 4908.03 04-DEC-16:01 0.00 0.00 0.00
                               
Annual Sum or Average 0.205716E+11 0.00 5518.55 0.154900E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 84102887.94 0.00 76.42 84102887.94 0.00 0.00 0.00 0.00 4903.32   4527.84   0.00 0.00 0.00
Maximum of Months 0.371169E+10 0.00 713.59 0.271700E+10 0.00 0.00 0.00 0.00 6142.55   4912.59   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_2_FLR_6 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 23238703.27 0.00 26.83 23161350.58 0.00 0.00 0.00 0.00 4823.13 12-JAN-16:01 4823.13 12-JAN-16:01 0.00 0.00 0.00
February 99472589.74 0.00 80.72 99344177.58 0.00 0.00 0.00 0.00 4862.94 18-FEB-16:01 4862.94 18-FEB-16:01 0.00 0.00 0.00
March 0.348853E+09 0.00 204.33 0.346933E+09 0.00 0.00 0.00 0.00 4863.71 04-MAR-16:01 4863.71 04-MAR-16:01 0.00 0.00 0.00
April 0.133726E+10 0.00 518.73 0.125408E+10 0.00 0.00 0.00 0.00 4871.93 28-APR-18:01 4871.93 28-APR-18:01 0.00 0.00 0.00
May 0.246120E+10 0.00 676.97 0.213130E+10 0.00 0.00 0.00 0.00 5099.76 28-MAY-08:61 4872.09 31-MAY-15:02 0.00 0.00 0.00
June 0.338670E+10 0.00 691.07 0.274237E+10 0.00 0.00 0.00 0.00 5131.39 28-JUN-08:62 4872.28 05-JUN-18:02 0.00 0.00 0.00
July 0.369689E+10 0.00 713.79 0.236125E+10 0.00 0.00 0.00 0.00 6076.02 19-JUL-08:62 4491.99 04-JUL-18:02 0.00 0.00 0.00
August 0.311223E+10 0.00 699.58 0.200664E+10 0.00 0.00 0.00 0.00 5543.01 02-AUG-08:61 4871.94 23-AUG-15:01 0.00 0.00 0.00
September 0.241963E+10 0.00 656.21 0.148379E+10 0.00 0.00 0.00 0.00 5544.28 09-SEP-08:61 4872.06 18-SEP-18:01 0.00 0.00 0.00
October 0.111096E+10 0.00 463.96 0.727581E+09 0.00 0.00 0.00 0.00 4954.38 03-OCT-18:01 4872.18 25-OCT-15:01 0.00 0.00 0.00
November 0.158680E+09 0.00 128.22 0.135959E+09 0.00 0.00 0.00 0.00 4871.62 09-NOV-16:01 4871.62 09-NOV-16:01 0.00 0.00 0.00
December 8212687.31 0.00 10.45 8212687.31 0.00 0.00 0.00 0.00 4345.74 16-DEC-16:02 4345.74 16-DEC-16:02 0.00 0.00 0.00
                               
Annual Sum or Average 0.181633E+11 0.00 4870.86 0.133206E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 8212687.31 0.00 10.45 8212687.31 0.00 0.00 0.00 0.00 4345.74   4345.74   0.00 0.00 0.00
Maximum of Months 0.369689E+10 0.00 713.79 0.274237E+10 0.00 0.00 0.00 0.00 6076.02   4872.28   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.457271E+10 0.00 356.79 0.453936E+10 0.00 0.00 0.00 0.00 22324.09 01-JAN-16:02 22324.09 01-JAN-16:02 0.00 0.00 0.00
February 0.479250E+10 0.00 380.88 0.476592E+10 0.00 0.00 0.00 0.00 22304.13 14-FEB-16:01 22304.13 14-FEB-16:01 0.00 0.00 0.00
March 0.498379E+10 0.00 445.57 0.494855E+10 0.00 0.00 0.00 0.00 22299.62 12-MAR-15:01 22299.62 12-MAR-15:01 0.00 0.00 0.00
April 0.817043E+10 0.00 594.13 0.766155E+10 0.00 0.00 0.00 0.00 22325.97 26-APR-18:01 22325.97 26-APR-18:01 0.00 0.00 0.00
May 0.112351E+11 0.00 680.83 0.947273E+10 0.00 0.00 0.00 0.00 23009.17 28-MAY-08:61 22326.83 20-MAY-18:02 0.00 0.00 0.00
June 0.149190E+11 0.00 680.07 0.116596E+11 0.00 0.00 0.00 0.00 22861.68 28-JUN-08:62 22327.98 05-JUN-15:02 0.00 0.00 0.00
July 0.174206E+11 0.00 705.32 0.106592E+11 0.00 0.00 0.00 0.00 27818.64 19-JUL-08:62 20900.83 23-JUL-18:02 0.00 0.00 0.00
August 0.164532E+11 0.00 699.36 0.107000E+11 0.00 0.00 0.00 0.00 25022.47 02-AUG-08:61 20868.80 24-AUG-18:02 0.00 0.00 0.00
September 0.162297E+11 0.00 681.58 0.110664E+11 0.00 0.00 0.00 0.00 25483.19 23-SEP-18:01 22321.41 24-SEP-15:01 0.00 0.00 0.00
October 0.126282E+11 0.00 653.01 0.956996E+10 0.00 0.00 0.00 0.00 23681.13 04-OCT-08:62 22327.04 25-OCT-18:01 0.00 0.00 0.00
November 0.730636E+10 0.00 444.86 0.695177E+10 0.00 0.00 0.00 0.00 22327.19 09-NOV-16:01 22327.19 09-NOV-16:01 0.00 0.00 0.00
December 0.402041E+10 0.00 333.00 0.401746E+10 0.00 0.00 0.00 0.00 22311.90 04-DEC-16:01 22311.90 04-DEC-16:01 0.00 0.00 0.00
                               
Annual Sum or Average 0.122732E+12 0.00 6655.40 0.960124E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.402041E+10 0.00 333.00 0.401746E+10 0.00 0.00 0.00 0.00 22299.62   20868.80   0.00 0.00 0.00
Maximum of Months 0.174206E+11 0.00 705.32 0.116596E+11 0.00 0.00 0.00 0.00 27818.64   22327.98   0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 706.15 535.07 171.08 966.31 488.35 0.00 0.00 0.00
February 664.38 471.17 193.21 931.83 426.84 0.00 0.00 0.00
March 519.74 294.46 225.28 759.87 366.80 0.00 0.00 0.00
April 362.15 135.95 226.20 624.30 193.52 0.00 0.00 0.00
May 257.00 37.69 219.31 529.28 91.56 0.00 0.00 0.00
June 219.82 13.83 205.99 578.17 31.64 0.00 0.00 0.00
July 223.23 19.79 203.44 587.73 16.67 0.00 0.00 0.00
August 281.79 71.59 210.20 662.86 35.29 0.00 0.00 0.00
September 446.25 231.85 214.40 885.96 106.12 0.00 0.00 0.00
October 612.55 416.17 196.38 1011.44 209.50 0.00 0.00 0.00
November 737.24 563.91 173.33 1059.97 399.52 0.00 0.00 0.00
December 724.95 544.65 180.31 971.49 531.20 0.00 0.00 0.00
                 
Annual Sum or Average 478.50 276.88 201.63 796.44 240.54 0.00 0.00 0.00
Minimum of Months 219.82 13.83 171.08 529.28 16.67 0.00 0.00 0.00
Maximum of Months 737.24 563.91 226.20 1059.97 531.20 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CAFE_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 1988.48 1506.73 481.75 2704.81 1387.38 0.00 0.00 0.00
February 1870.85 1326.79 544.06 2607.58 1212.38 0.00 0.00 0.00
March 1463.55 829.18 634.37 2123.50 1041.07 0.00 0.00 0.00
April 1019.80 382.82 636.98 1744.59 557.35 0.00 0.00 0.00
May 723.68 106.13 617.55 1474.27 272.00 0.00 0.00 0.00
June 618.99 38.95 580.04 1609.26 101.92 0.00 0.00 0.00
July 628.60 55.73 572.87 1634.91 58.32 0.00 0.00 0.00
August 793.51 201.60 591.90 1852.27 115.73 0.00 0.00 0.00
September 1256.61 652.87 603.74 2491.96 314.76 0.00 0.00 0.00
October 1724.89 1171.91 552.99 2840.22 605.20 0.00 0.00 0.00
November 2076.02 1587.93 488.09 2971.59 1135.58 0.00 0.00 0.00
December 2041.42 1533.69 507.73 2716.87 1506.63 0.00 0.00 0.00
                 
Annual Sum or Average 1347.44 779.68 567.76 2228.18 689.89 0.00 0.00 0.00
Minimum of Months 618.99 38.95 481.75 1474.27 58.32 0.00 0.00 0.00
Maximum of Months 2076.02 1587.93 636.98 2971.59 1506.63 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: LOBBY_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 2583.15 1957.32 625.82 3583.68 1839.21 0.00 0.00 0.00
February 2430.34 1723.58 706.76 3461.38 1605.98 0.00 0.00 0.00
March 1901.24 1077.15 824.09 2821.64 1385.91 0.00 0.00 0.00
April 1324.78 497.31 827.47 2331.15 742.00 0.00 0.00 0.00
May 940.11 137.87 802.24 1977.06 364.15 0.00 0.00 0.00
June 804.10 50.59 753.51 2164.92 134.32 0.00 0.00 0.00
July 816.59 72.40 744.19 2197.35 75.81 0.00 0.00 0.00
August 1030.81 261.90 768.91 2487.83 149.09 0.00 0.00 0.00
September 1632.41 848.12 784.29 3337.86 406.25 0.00 0.00 0.00
October 2240.73 1522.37 718.36 3793.06 787.66 0.00 0.00 0.00
November 2696.87 2062.81 634.06 3951.91 1496.97 0.00 0.00 0.00
December 2651.92 1992.35 659.58 3595.64 2000.72 0.00 0.00 0.00
                 
Annual Sum or Average 1750.40 1012.84 737.56 2971.61 912.42 0.00 0.00 0.00
Minimum of Months 804.10 50.59 625.82 1977.06 75.81 0.00 0.00 0.00
Maximum of Months 2696.87 2062.81 827.47 3951.91 2000.72 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 139.62 105.79 33.83 189.77 99.30 0.00 0.00 0.00
February 131.36 93.16 38.20 182.58 87.08 0.00 0.00 0.00
March 102.76 58.22 44.54 146.71 75.62 0.00 0.00 0.00
April 71.60 26.88 44.73 119.50 39.98 0.00 0.00 0.00
May 50.81 7.45 43.36 101.00 18.69 0.00 0.00 0.00
June 43.46 2.73 40.73 112.55 6.46 0.00 0.00 0.00
July 44.14 3.91 40.22 113.72 3.57 0.00 0.00 0.00
August 55.72 14.16 41.56 128.68 7.24 0.00 0.00 0.00
September 88.23 45.84 42.39 173.13 21.71 0.00 0.00 0.00
October 121.11 82.28 38.83 198.36 42.85 0.00 0.00 0.00
November 145.77 111.49 34.27 208.64 81.15 0.00 0.00 0.00
December 143.34 107.69 35.65 191.91 107.57 0.00 0.00 0.00
                 
Annual Sum or Average 94.61 54.74 39.87 155.35 49.09 0.00 0.00 0.00
Minimum of Months 43.46 2.73 33.83 101.00 3.57 0.00 0.00 0.00
Maximum of Months 145.77 111.49 44.73 208.64 107.57 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_1_FLR_3_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 107.40 60.54 46.87 114.77 204.95 0.00 0.00 0.00
February 120.90 64.15 56.75 140.05 179.43 0.00 0.00 0.00
March 164.97 88.46 76.51 214.04 146.42 0.00 0.00 0.00
April 189.31 102.11 87.19 295.74 73.78 0.00 0.00 0.00
May 204.29 109.33 94.96 363.41 34.54 0.00 0.00 0.00
June 198.79 106.74 92.05 410.06 11.98 0.00 0.00 0.00
July 176.54 87.72 88.82 370.09 6.45 0.00 0.00 0.00
August 170.94 87.09 83.85 340.68 13.39 0.00 0.00 0.00
September 175.49 97.97 77.52 319.63 41.01 0.00 0.00 0.00
October 151.21 88.52 62.68 235.09 83.90 0.00 0.00 0.00
November 126.16 76.76 49.40 154.89 167.74 0.00 0.00 0.00
December 101.75 55.25 46.51 102.71 225.76 0.00 0.00 0.00
                 
Annual Sum or Average 157.45 85.45 72.00 255.61 98.73 0.00 0.00 0.00
Minimum of Months 101.75 55.25 46.51 102.71 6.45 0.00 0.00 0.00
Maximum of Months 204.29 109.33 94.96 410.06 225.76 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_2_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 20.40 0.00 20.40 4.65 110.42 0.00 0.00 0.00
February 24.91 0.00 24.91 12.32 96.23 0.00 0.00 0.00
March 32.60 0.00 32.60 24.85 79.01 0.00 0.00 0.00
April 37.86 0.48 37.38 50.35 38.54 0.00 0.00 0.00
May 44.72 3.30 41.43 84.87 17.26 0.00 0.00 0.00
June 47.56 5.93 41.63 119.11 6.23 0.00 0.00 0.00
July 43.94 4.31 39.63 111.30 3.41 0.00 0.00 0.00
August 37.16 0.88 36.28 87.76 6.90 0.00 0.00 0.00
September 32.33 0.04 32.29 63.32 21.44 0.00 0.00 0.00
October 26.80 0.00 26.80 33.78 44.22 0.00 0.00 0.00
November 21.63 0.00 21.63 9.22 90.16 0.00 0.00 0.00
December 20.24 0.00 20.24 3.31 122.02 0.00 0.00 0.00
                 
Annual Sum or Average 32.55 1.25 31.30 50.61 52.78 0.00 0.00 0.00
Minimum of Months 20.24 0.00 20.24 3.31 3.41 0.00 0.00 0.00
Maximum of Months 47.56 5.93 41.63 119.11 122.02 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_2_FLR_3_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 107.40 60.54 46.87 121.32 198.72 0.00 0.00 0.00
February 120.90 64.15 56.75 146.43 174.50 0.00 0.00 0.00
March 164.97 88.46 76.51 219.22 143.72 0.00 0.00 0.00
April 189.31 102.11 87.19 298.34 72.90 0.00 0.00 0.00
May 204.29 109.33 94.96 364.01 34.40 0.00 0.00 0.00
June 198.79 106.74 92.05 409.91 11.99 0.00 0.00 0.00
July 176.54 87.72 88.82 370.21 6.43 0.00 0.00 0.00
August 170.94 87.09 83.85 341.94 13.17 0.00 0.00 0.00
September 175.49 97.97 77.52 322.60 39.96 0.00 0.00 0.00
October 151.21 88.52 62.68 239.97 81.45 0.00 0.00 0.00
November 126.16 76.76 49.40 161.33 162.71 0.00 0.00 0.00
December 101.75 55.25 46.51 109.09 219.17 0.00 0.00 0.00
                 
Annual Sum or Average 157.45 85.45 72.00 259.19 96.22 0.00 0.00 0.00
Minimum of Months 101.75 55.25 46.51 109.09 6.43 0.00 0.00 0.00
Maximum of Months 204.29 109.33 94.96 409.91 219.17 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 111.67 84.62 27.06 146.49 90.53 0.00 0.00 0.00
February 105.07 74.51 30.55 140.85 80.39 0.00 0.00 0.00
March 82.19 46.57 35.63 112.69 69.56 0.00 0.00 0.00
April 57.27 21.50 35.77 92.09 39.61 0.00 0.00 0.00
May 40.64 5.96 34.68 77.25 20.47 0.00 0.00 0.00
June 34.76 2.19 32.58 85.74 8.32 0.00 0.00 0.00
July 35.30 3.13 32.17 86.17 5.84 0.00 0.00 0.00
August 44.56 11.32 33.24 98.52 9.88 0.00 0.00 0.00
September 70.57 36.67 33.91 135.45 23.59 0.00 0.00 0.00
October 96.87 65.81 31.06 154.43 42.97 0.00 0.00 0.00
November 116.59 89.18 27.41 162.15 74.95 0.00 0.00 0.00
December 114.65 86.13 28.51 148.10 95.80 0.00 0.00 0.00
                 
Annual Sum or Average 75.67 43.79 31.89 119.83 46.66 0.00 0.00 0.00
Minimum of Months 34.76 2.19 27.06 77.25 5.84 0.00 0.00 0.00
Maximum of Months 116.59 89.18 35.77 162.15 95.80 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 16.32 0.00 16.32 3.19 92.12 0.00 0.00 0.00
February 19.93 0.00 19.93 9.75 79.56 0.00 0.00 0.00
March 26.09 0.00 26.09 20.52 64.10 0.00 0.00 0.00
April 30.29 0.39 29.91 42.81 30.27 0.00 0.00 0.00
May 35.78 2.64 33.15 71.80 12.97 0.00 0.00 0.00
June 38.05 4.74 33.31 100.35 4.30 0.00 0.00 0.00
July 35.16 3.45 31.71 93.80 2.20 0.00 0.00 0.00
August 29.73 0.71 29.03 74.60 4.84 0.00 0.00 0.00
September 25.87 0.03 25.84 54.20 15.96 0.00 0.00 0.00
October 21.44 0.00 21.44 28.85 34.85 0.00 0.00 0.00
November 17.31 0.00 17.31 7.49 73.85 0.00 0.00 0.00
December 16.19 0.00 16.19 2.18 101.99 0.00 0.00 0.00
                 
Annual Sum or Average 26.04 1.00 25.04 42.64 42.92 0.00 0.00 0.00
Minimum of Months 16.19 0.00 16.19 2.18 2.20 0.00 0.00 0.00
Maximum of Months 38.05 4.74 33.31 100.35 101.99 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_5_FLR_3_WALL_EAST_WINDOW

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 101.70 55.11 46.60 95.91 194.30 0.00 0.00 0.00
February 136.50 77.83 58.67 153.65 166.90 0.00 0.00 0.00
March 168.25 92.64 75.61 209.70 134.88 0.00 0.00 0.00
April 202.82 112.49 90.33 311.73 66.80 0.00 0.00 0.00
May 209.08 113.58 95.50 369.84 31.44 0.00 0.00 0.00
June 209.17 116.31 92.86 427.67 11.17 0.00 0.00 0.00
July 187.70 98.13 89.57 389.18 6.21 0.00 0.00 0.00
August 178.80 91.56 87.24 354.66 12.60 0.00 0.00 0.00
September 177.40 101.30 76.10 318.84 37.51 0.00 0.00 0.00
October 135.78 73.14 62.64 202.60 78.58 0.00 0.00 0.00
November 121.58 70.62 50.96 134.96 156.22 0.00 0.00 0.00
December 101.78 53.93 47.85 91.56 213.42 0.00 0.00 0.00
                 
Annual Sum or Average 160.90 88.01 72.89 255.38 92.16 0.00 0.00 0.00
Minimum of Months 101.70 53.93 46.60 91.56 6.21 0.00 0.00 0.00
Maximum of Months 209.17 116.31 95.50 427.67 213.42 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 139.62 105.79 33.83 189.18 98.71 0.00 0.00 0.00
February 131.36 93.16 38.20 180.95 86.88 0.00 0.00 0.00
March 102.76 58.22 44.54 144.93 75.14 0.00 0.00 0.00
April 71.60 26.88 44.73 117.84 39.89 0.00 0.00 0.00
May 50.81 7.45 43.36 99.88 18.49 0.00 0.00 0.00
June 43.46 2.73 40.73 111.67 6.28 0.00 0.00 0.00
July 44.14 3.91 40.22 113.01 3.43 0.00 0.00 0.00
August 55.72 14.16 41.56 128.04 7.10 0.00 0.00 0.00
September 88.23 45.84 42.39 172.43 21.40 0.00 0.00 0.00
October 121.11 82.28 38.83 197.81 42.09 0.00 0.00 0.00
November 145.77 111.49 34.27 207.78 80.52 0.00 0.00 0.00
December 143.34 107.69 35.65 191.26 107.17 0.00 0.00 0.00
                 
Annual Sum or Average 94.61 54.74 39.87 154.37 48.74 0.00 0.00 0.00
Minimum of Months 43.46 2.73 33.83 99.88 3.43 0.00 0.00 0.00
Maximum of Months 145.77 111.49 44.73 207.78 107.17 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_6_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 20.40 0.00 20.40 4.36 110.03 0.00 0.00 0.00
February 24.91 0.00 24.91 11.52 96.73 0.00 0.00 0.00
March 32.60 0.00 32.60 23.60 79.17 0.00 0.00 0.00
April 37.86 0.48 37.38 48.59 38.61 0.00 0.00 0.00
May 44.72 3.30 41.43 83.60 16.98 0.00 0.00 0.00
June 47.56 5.93 41.63 118.32 6.06 0.00 0.00 0.00
July 43.94 4.31 39.63 110.64 3.28 0.00 0.00 0.00
August 37.16 0.88 36.28 87.04 6.75 0.00 0.00 0.00
September 32.33 0.04 32.29 62.48 21.23 0.00 0.00 0.00
October 26.80 0.00 26.80 33.08 43.61 0.00 0.00 0.00
November 21.63 0.00 21.63 8.79 89.52 0.00 0.00 0.00
December 20.24 0.00 20.24 2.98 121.94 0.00 0.00 0.00
                 
Annual Sum or Average 32.55 1.25 31.30 49.79 52.62 0.00 0.00 0.00
Minimum of Months 20.24 0.00 20.24 2.98 3.28 0.00 0.00 0.00
Maximum of Months 47.56 5.93 41.63 118.32 121.94 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_6_FLR_3_WALL_EAST_WINDOW

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 101.70 55.11 46.60 101.06 186.36 0.00 0.00 0.00
February 136.50 77.83 58.67 159.46 161.32 0.00 0.00 0.00
March 168.25 92.64 75.61 214.45 131.99 0.00 0.00 0.00
April 202.82 112.49 90.33 313.94 65.97 0.00 0.00 0.00
May 209.08 113.58 95.50 370.36 31.31 0.00 0.00 0.00
June 209.17 116.31 92.86 427.61 11.19 0.00 0.00 0.00
July 187.70 98.13 89.57 389.36 6.19 0.00 0.00 0.00
August 178.80 91.56 87.24 355.85 12.39 0.00 0.00 0.00
September 177.40 101.30 76.10 321.56 36.54 0.00 0.00 0.00
October 135.78 73.14 62.64 207.08 76.15 0.00 0.00 0.00
November 121.58 70.62 50.96 141.18 150.14 0.00 0.00 0.00
December 101.78 53.93 47.85 95.83 204.63 0.00 0.00 0.00
                 
Annual Sum or Average 160.90 88.01 72.89 258.49 89.18 0.00 0.00 0.00
Minimum of Months 101.70 53.93 46.60 95.83 6.19 0.00 0.00 0.00
Maximum of Months 209.17 116.31 95.50 427.61 204.63 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 25.83 0.00 25.83 4.73 147.79 0.00 0.00 0.00
February 31.55 0.00 31.55 15.53 126.70 0.00 0.00 0.00
March 41.29 0.00 41.29 33.74 100.80 0.00 0.00 0.00
April 47.95 0.61 47.34 71.78 46.99 0.00 0.00 0.00
May 56.64 4.17 52.47 118.32 20.63 0.00 0.00 0.00
June 60.23 7.51 52.73 160.57 7.76 0.00 0.00 0.00
July 55.65 5.46 50.19 150.71 4.10 0.00 0.00 0.00
August 47.06 1.12 45.94 120.03 8.49 0.00 0.00 0.00
September 40.94 0.05 40.89 87.92 26.64 0.00 0.00 0.00
October 33.94 0.00 33.94 47.37 54.96 0.00 0.00 0.00
November 27.40 0.00 27.40 11.88 117.47 0.00 0.00 0.00
December 25.63 0.00 25.63 3.20 164.57 0.00 0.00 0.00
                 
Annual Sum or Average 41.22 1.58 39.64 69.10 68.64 0.00 0.00 0.00
Minimum of Months 25.63 0.00 25.63 3.20 4.10 0.00 0.00 0.00
Maximum of Months 60.23 7.51 52.73 160.57 164.57 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 9.52 0.00 9.52 1.74 54.48 0.00 0.00 0.00
February 11.63 0.00 11.63 5.73 46.71 0.00 0.00 0.00
March 15.22 0.00 15.22 12.44 37.16 0.00 0.00 0.00
April 17.68 0.23 17.45 26.46 17.32 0.00 0.00 0.00
May 20.88 1.54 19.34 43.62 7.61 0.00 0.00 0.00
June 22.20 2.77 19.44 59.19 2.86 0.00 0.00 0.00
July 20.51 2.01 18.50 55.56 1.51 0.00 0.00 0.00
August 17.35 0.41 16.94 44.25 3.13 0.00 0.00 0.00
September 15.09 0.02 15.07 32.41 9.82 0.00 0.00 0.00
October 12.51 0.00 12.51 17.46 20.26 0.00 0.00 0.00
November 10.10 0.00 10.10 4.38 43.31 0.00 0.00 0.00
December 9.45 0.00 9.45 1.18 60.67 0.00 0.00 0.00
                 
Annual Sum or Average 15.20 0.58 14.61 25.47 25.30 0.00 0.00 0.00
Minimum of Months 9.45 0.00 9.45 1.18 1.51 0.00 0.00 0.00
Maximum of Months 22.20 2.77 19.44 59.19 60.67 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 65.15 49.36 15.78 89.51 47.27 0.00 0.00 0.00
February 61.29 43.47 17.82 86.59 40.97 0.00 0.00 0.00
March 47.95 27.17 20.78 70.49 34.92 0.00 0.00 0.00
April 33.41 12.54 20.87 59.32 17.75 0.00 0.00 0.00
May 23.71 3.48 20.23 51.27 8.22 0.00 0.00 0.00
June 20.28 1.28 19.00 56.06 2.98 0.00 0.00 0.00
July 20.59 1.83 18.77 56.65 1.57 0.00 0.00 0.00
August 26.00 6.60 19.39 63.58 3.25 0.00 0.00 0.00
September 41.17 21.39 19.78 84.27 9.71 0.00 0.00 0.00
October 56.51 38.39 18.12 95.57 19.16 0.00 0.00 0.00
November 68.01 52.02 15.99 99.25 37.86 0.00 0.00 0.00
December 66.88 50.25 16.63 90.17 51.40 0.00 0.00 0.00
                 
Annual Sum or Average 44.14 25.54 18.60 75.14 22.84 0.00 0.00 0.00
Minimum of Months 20.28 1.28 15.78 51.27 1.57 0.00 0.00 0.00
Maximum of Months 68.01 52.02 20.87 99.25 51.40 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 176.82 133.98 42.84 242.94 128.31 0.00 0.00 0.00
February 166.36 117.98 48.38 235.02 111.20 0.00 0.00 0.00
March 130.14 73.73 56.41 191.34 94.78 0.00 0.00 0.00
April 90.68 34.04 56.64 161.01 48.18 0.00 0.00 0.00
May 64.35 9.44 54.91 139.16 22.32 0.00 0.00 0.00
June 55.04 3.46 51.58 152.16 8.08 0.00 0.00 0.00
July 55.90 4.96 50.94 153.76 4.27 0.00 0.00 0.00
August 70.56 17.93 52.63 172.56 8.81 0.00 0.00 0.00
September 111.74 58.05 53.69 228.72 26.36 0.00 0.00 0.00
October 153.38 104.21 49.17 259.41 52.00 0.00 0.00 0.00
November 184.60 141.20 43.40 269.39 102.76 0.00 0.00 0.00
December 181.53 136.38 45.15 244.74 139.51 0.00 0.00 0.00
                 
Annual Sum or Average 119.82 69.33 50.49 203.94 61.99 0.00 0.00 0.00
Minimum of Months 55.04 3.46 42.84 139.16 4.27 0.00 0.00 0.00
Maximum of Months 184.60 141.20 56.64 269.39 139.51 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 139.62 105.79 33.83 188.69 98.21 0.00 0.00 0.00
February 131.36 93.16 38.20 181.24 86.23 0.00 0.00 0.00
March 102.76 58.22 44.54 144.98 75.06 0.00 0.00 0.00
April 71.60 26.88 44.73 117.48 39.77 0.00 0.00 0.00
May 50.81 7.45 43.36 99.33 18.50 0.00 0.00 0.00
June 43.46 2.73 40.73 111.11 6.38 0.00 0.00 0.00
July 44.14 3.91 40.22 111.86 3.60 0.00 0.00 0.00
August 55.72 14.16 41.56 126.70 7.25 0.00 0.00 0.00
September 88.23 45.84 42.39 170.84 21.66 0.00 0.00 0.00
October 121.11 82.28 38.83 196.19 42.75 0.00 0.00 0.00
November 145.77 111.49 34.27 207.20 80.41 0.00 0.00 0.00
December 143.34 107.69 35.65 191.33 106.21 0.00 0.00 0.00
                 
Annual Sum or Average 94.61 54.74 39.87 153.71 48.66 0.00 0.00 0.00
Minimum of Months 43.46 2.73 33.83 99.33 3.60 0.00 0.00 0.00
Maximum of Months 145.77 111.49 44.73 207.20 106.21 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_1_FLR_6_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 107.40 60.54 46.87 113.78 202.34 0.00 0.00 0.00
February 120.90 64.15 56.75 138.45 177.33 0.00 0.00 0.00
March 164.97 88.46 76.51 211.12 144.99 0.00 0.00 0.00
April 189.31 102.11 87.19 291.54 73.28 0.00 0.00 0.00
May 204.29 109.33 94.96 358.63 34.16 0.00 0.00 0.00
June 198.79 106.74 92.05 405.59 11.88 0.00 0.00 0.00
July 176.54 87.72 88.82 365.35 6.51 0.00 0.00 0.00
August 170.94 87.09 83.85 336.25 13.43 0.00 0.00 0.00
September 175.49 97.97 77.52 315.51 40.92 0.00 0.00 0.00
October 151.21 88.52 62.68 232.02 83.52 0.00 0.00 0.00
November 126.16 76.76 49.40 153.16 165.83 0.00 0.00 0.00
December 101.75 55.25 46.51 102.29 222.28 0.00 0.00 0.00
                 
Annual Sum or Average 157.45 85.45 72.00 252.47 97.66 0.00 0.00 0.00
Minimum of Months 101.75 55.25 46.51 102.29 6.51 0.00 0.00 0.00
Maximum of Months 204.29 109.33 94.96 405.59 222.28 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_2_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 20.40 0.00 20.40 4.89 108.88 0.00 0.00 0.00
February 24.91 0.00 24.91 12.36 94.99 0.00 0.00 0.00
March 32.60 0.00 32.60 24.51 78.27 0.00 0.00 0.00
April 37.86 0.48 37.38 49.09 38.34 0.00 0.00 0.00
May 44.72 3.30 41.43 83.31 17.09 0.00 0.00 0.00
June 47.56 5.93 41.63 117.43 6.17 0.00 0.00 0.00
July 43.94 4.31 39.63 109.36 3.44 0.00 0.00 0.00
August 37.16 0.88 36.28 86.13 6.91 0.00 0.00 0.00
September 32.33 0.04 32.29 61.83 21.38 0.00 0.00 0.00
October 26.80 0.00 26.80 32.87 44.02 0.00 0.00 0.00
November 21.63 0.00 21.63 9.18 89.13 0.00 0.00 0.00
December 20.24 0.00 20.24 3.55 120.06 0.00 0.00 0.00
                 
Annual Sum or Average 32.55 1.25 31.30 49.74 52.19 0.00 0.00 0.00
Minimum of Months 20.24 0.00 20.24 3.55 3.44 0.00 0.00 0.00
Maximum of Months 47.56 5.93 41.63 117.43 120.06 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_2_FLR_6_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 107.40 60.54 46.87 120.99 195.92 0.00 0.00 0.00
February 120.90 64.15 56.75 145.37 172.18 0.00 0.00 0.00
March 164.97 88.46 76.51 216.62 142.17 0.00 0.00 0.00
April 189.31 102.11 87.19 294.06 72.38 0.00 0.00 0.00
May 204.29 109.33 94.96 359.19 34.03 0.00 0.00 0.00
June 198.79 106.74 92.05 405.43 11.89 0.00 0.00 0.00
July 176.54 87.72 88.82 365.45 6.49 0.00 0.00 0.00
August 170.94 87.09 83.85 337.47 13.20 0.00 0.00 0.00
September 175.49 97.97 77.52 318.46 39.83 0.00 0.00 0.00
October 151.21 88.52 62.68 236.94 80.94 0.00 0.00 0.00
November 126.16 76.76 49.40 160.14 160.42 0.00 0.00 0.00
December 101.75 55.25 46.51 109.31 215.65 0.00 0.00 0.00
                 
Annual Sum or Average 157.45 85.45 72.00 256.27 95.06 0.00 0.00 0.00
Minimum of Months 101.75 55.25 46.51 109.31 6.49 0.00 0.00 0.00
Maximum of Months 204.29 109.33 94.96 405.43 215.65 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 204.76 155.16 49.61 268.88 151.08 0.00 0.00 0.00
February 192.65 136.63 56.02 259.24 131.84 0.00 0.00 0.00
March 150.71 85.38 65.33 208.97 112.06 0.00 0.00 0.00
April 105.01 39.42 65.59 173.42 57.45 0.00 0.00 0.00
May 74.52 10.93 63.59 150.44 25.74 0.00 0.00 0.00
June 63.74 4.01 59.73 169.60 8.35 0.00 0.00 0.00
July 64.73 5.74 58.99 170.03 4.52 0.00 0.00 0.00
August 81.71 20.76 60.95 190.26 9.84 0.00 0.00 0.00
September 129.40 67.23 62.17 252.26 30.80 0.00 0.00 0.00
October 177.62 120.68 56.94 286.04 63.51 0.00 0.00 0.00
November 213.78 163.52 50.26 298.39 122.48 0.00 0.00 0.00
December 210.22 157.93 52.28 271.78 163.29 0.00 0.00 0.00
                 
Annual Sum or Average 138.75 80.29 58.47 224.68 73.14 0.00 0.00 0.00
Minimum of Months 63.74 4.01 49.61 150.44 4.52 0.00 0.00 0.00
Maximum of Months 213.78 163.52 65.59 298.39 163.29 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: BANQUET_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 142.78 0.00 142.78 22.01 833.95 0.00 0.00 0.00
February 174.35 0.00 174.35 78.75 719.40 0.00 0.00 0.00
March 228.22 0.01 228.21 172.70 582.26 0.00 0.00 0.00
April 265.01 3.38 261.64 376.51 287.99 0.00 0.00 0.00
May 313.05 23.07 289.98 630.36 135.37 0.00 0.00 0.00
June 332.91 41.48 291.42 869.43 54.64 0.00 0.00 0.00
July 307.56 30.17 277.39 810.61 33.78 0.00 0.00 0.00
August 260.12 6.19 253.93 648.77 61.88 0.00 0.00 0.00
September 226.30 0.29 226.02 480.93 161.47 0.00 0.00 0.00
October 187.59 0.00 187.59 251.87 326.31 0.00 0.00 0.00
November 151.44 0.00 151.44 59.23 667.75 0.00 0.00 0.00
December 141.68 0.00 141.68 15.24 918.11 0.00 0.00 0.00
                 
Annual Sum or Average 227.84 8.76 219.09 369.55 397.10 0.00 0.00 0.00
Minimum of Months 141.68 0.00 141.68 15.24 33.78 0.00 0.00 0.00
Maximum of Months 332.91 41.48 291.42 869.43 918.11 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: DINING_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 142.78 0.00 142.78 19.89 850.73 0.00 0.00 0.00
February 174.35 0.00 174.35 75.05 735.06 0.00 0.00 0.00
March 228.22 0.01 228.21 166.72 596.59 0.00 0.00 0.00
April 265.01 3.38 261.64 366.52 299.43 0.00 0.00 0.00
May 313.05 23.07 289.98 616.07 143.68 0.00 0.00 0.00
June 332.91 41.48 291.42 853.20 59.27 0.00 0.00 0.00
July 307.56 30.17 277.39 794.30 38.23 0.00 0.00 0.00
August 260.12 6.19 253.93 634.14 67.82 0.00 0.00 0.00
September 226.30 0.29 226.02 470.36 170.73 0.00 0.00 0.00
October 187.59 0.00 187.59 244.52 338.74 0.00 0.00 0.00
November 151.44 0.00 151.44 55.69 683.34 0.00 0.00 0.00
December 141.68 0.00 141.68 13.80 935.16 0.00 0.00 0.00
                 
Annual Sum or Average 227.84 8.76 219.09 360.68 408.39 0.00 0.00 0.00
Minimum of Months 141.68 0.00 141.68 13.80 38.23 0.00 0.00 0.00
Maximum of Months 332.91 41.48 291.42 853.20 935.16 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: KITCHEN_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 20.40 0.00 20.40 3.46 120.72 0.00 0.00 0.00
February 24.91 0.00 24.91 12.11 105.56 0.00 0.00 0.00
March 32.60 0.00 32.60 25.08 87.00 0.00 0.00 0.00
April 37.86 0.48 37.38 55.84 44.84 0.00 0.00 0.00
May 44.72 3.30 41.43 92.74 22.58 0.00 0.00 0.00
June 47.56 5.93 41.63 128.76 9.23 0.00 0.00 0.00
July 43.94 4.31 39.63 121.35 6.42 0.00 0.00 0.00
August 37.16 0.88 36.28 97.88 10.76 0.00 0.00 0.00
September 32.33 0.04 32.29 74.31 24.97 0.00 0.00 0.00
October 26.80 0.00 26.80 38.84 49.61 0.00 0.00 0.00
November 21.63 0.00 21.63 9.45 97.76 0.00 0.00 0.00
December 20.24 0.00 20.24 2.53 131.04 0.00 0.00 0.00
                 
Annual Sum or Average 32.55 1.25 31.30 55.42 58.99 0.00 0.00 0.00
Minimum of Months 20.24 0.00 20.24 2.53 6.42 0.00 0.00 0.00
Maximum of Months 47.56 5.93 41.63 128.76 131.04 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: KITCHEN_FLR_6_WALL_EAST_WINDOW

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 203.40 110.21 93.19 200.52 412.25 0.00 0.00 0.00
February 272.98 155.65 117.32 325.67 358.06 0.00 0.00 0.00
March 336.47 185.26 151.21 440.90 295.05 0.00 0.00 0.00
April 405.62 224.97 180.65 658.12 157.66 0.00 0.00 0.00
May 418.14 227.15 190.99 774.57 84.02 0.00 0.00 0.00
June 418.31 232.60 185.71 892.04 34.52 0.00 0.00 0.00
July 375.38 196.25 179.13 816.06 24.56 0.00 0.00 0.00
August 357.58 183.11 174.47 750.73 40.43 0.00 0.00 0.00
September 354.77 202.59 152.18 688.93 89.92 0.00 0.00 0.00
October 271.54 146.27 125.28 437.90 176.80 0.00 0.00 0.00
November 243.14 141.22 101.92 288.57 332.49 0.00 0.00 0.00
December 203.55 107.86 95.69 193.47 445.74 0.00 0.00 0.00
                 
Annual Sum or Average 321.77 176.00 145.77 539.69 203.58 0.00 0.00 0.00
Minimum of Months 203.40 107.86 93.19 193.47 24.56 0.00 0.00 0.00
Maximum of Months 418.31 232.60 190.99 892.04 445.74 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 139.62 105.79 33.83 193.84 105.81 0.00 0.00 0.00
February 131.36 93.16 38.20 186.89 93.68 0.00 0.00 0.00
March 102.76 58.22 44.54 150.51 81.50 0.00 0.00 0.00
April 71.60 26.88 44.73 125.63 45.51 0.00 0.00 0.00
May 50.81 7.45 43.36 108.01 23.73 0.00 0.00 0.00
June 43.46 2.73 40.73 121.53 9.36 0.00 0.00 0.00
July 44.14 3.91 40.22 123.38 6.54 0.00 0.00 0.00
August 55.72 14.16 41.56 139.27 10.93 0.00 0.00 0.00
September 88.23 45.84 42.39 185.62 24.83 0.00 0.00 0.00
October 121.11 82.28 38.83 207.15 47.20 0.00 0.00 0.00
November 145.77 111.49 34.27 215.11 86.22 0.00 0.00 0.00
December 143.34 107.69 35.65 196.65 112.92 0.00 0.00 0.00
                 
Annual Sum or Average 94.61 54.74 39.87 162.61 53.83 0.00 0.00 0.00
Minimum of Months 43.46 2.73 33.83 108.01 6.54 0.00 0.00 0.00
Maximum of Months 145.77 111.49 44.73 215.11 112.92 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 25.83 0.00 25.83 4.04 149.15 0.00 0.00 0.00
February 31.55 0.00 31.55 14.36 127.64 0.00 0.00 0.00
March 41.29 0.00 41.29 31.98 101.49 0.00 0.00 0.00
April 47.95 0.61 47.34 69.50 47.02 0.00 0.00 0.00
May 56.64 4.17 52.47 117.32 19.72 0.00 0.00 0.00
June 60.23 7.51 52.73 160.28 6.91 0.00 0.00 0.00
July 55.65 5.46 50.19 149.89 3.57 0.00 0.00 0.00
August 47.06 1.12 45.94 119.48 7.70 0.00 0.00 0.00
September 40.94 0.05 40.89 86.85 25.07 0.00 0.00 0.00
October 33.94 0.00 33.94 45.61 54.82 0.00 0.00 0.00
November 27.40 0.00 27.40 10.68 118.40 0.00 0.00 0.00
December 25.63 0.00 25.63 2.81 165.33 0.00 0.00 0.00
                 
Annual Sum or Average 41.22 1.58 39.64 68.02 68.63 0.00 0.00 0.00
Minimum of Months 25.63 0.00 25.63 2.81 3.57 0.00 0.00 0.00
Maximum of Months 60.23 7.51 52.73 160.28 165.33 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 23.11 0.00 23.11 3.62 133.45 0.00 0.00 0.00
February 28.22 0.00 28.22 12.85 114.20 0.00 0.00 0.00
March 36.94 0.00 36.94 28.61 90.80 0.00 0.00 0.00
April 42.90 0.55 42.35 62.18 42.07 0.00 0.00 0.00
May 50.68 3.73 46.94 104.96 17.64 0.00 0.00 0.00
June 53.89 6.72 47.17 143.40 6.18 0.00 0.00 0.00
July 49.79 4.88 44.90 134.11 3.20 0.00 0.00 0.00
August 42.11 1.00 41.11 106.90 6.89 0.00 0.00 0.00
September 36.63 0.05 36.59 77.70 22.43 0.00 0.00 0.00
October 30.37 0.00 30.37 40.81 49.05 0.00 0.00 0.00
November 24.51 0.00 24.51 9.55 105.94 0.00 0.00 0.00
December 22.93 0.00 22.93 2.51 147.92 0.00 0.00 0.00
                 
Annual Sum or Average 36.88 1.42 35.46 60.86 61.41 0.00 0.00 0.00
Minimum of Months 22.93 0.00 22.93 2.51 3.20 0.00 0.00 0.00
Maximum of Months 53.89 6.72 47.17 143.40 147.92 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 521.24 394.96 126.28 706.57 379.97 0.00 0.00 0.00
February 490.41 347.79 142.61 683.01 329.63 0.00 0.00 0.00
March 383.64 217.35 166.29 553.33 281.15 0.00 0.00 0.00
April 267.32 100.35 166.97 464.96 142.38 0.00 0.00 0.00
May 189.70 27.82 161.88 406.70 63.27 0.00 0.00 0.00
June 162.26 10.21 152.05 448.20 21.22 0.00 0.00 0.00
July 164.78 14.61 150.17 450.84 11.08 0.00 0.00 0.00
August 208.00 52.85 155.16 505.48 23.66 0.00 0.00 0.00
September 329.40 171.14 158.26 668.32 73.31 0.00 0.00 0.00
October 452.15 307.19 144.96 754.91 153.04 0.00 0.00 0.00
November 544.19 416.24 127.94 784.50 304.18 0.00 0.00 0.00
December 535.12 402.02 133.09 713.65 411.26 0.00 0.00 0.00
                 
Annual Sum or Average 353.20 204.38 148.83 594.35 182.16 0.00 0.00 0.00
Minimum of Months 162.26 10.21 126.28 406.70 11.08 0.00 0.00 0.00
Maximum of Months 544.19 416.24 166.97 784.50 411.26 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyReportMonthly

For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.189136E+10 0.143314E+10 0.458222E+09 0.258816E+10 0.130800E+10
February 0.160727E+10 0.113986E+10 0.467406E+09 0.225428E+10 0.103261E+10
March 0.139207E+10 0.788679E+09 0.603391E+09 0.203523E+10 0.982449E+09
April 0.938702E+09 0.352379E+09 0.586322E+09 0.161818E+10 0.501597E+09
May 0.688337E+09 0.100947E+09 0.587390E+09 0.141762E+10 0.245247E+09
June 0.569764E+09 35850177.24 0.533914E+09 0.149862E+10 82013881.80
July 0.597898E+09 53010019.83 0.544888E+09 0.157418E+10 44653482.94
August 0.754750E+09 0.191758E+09 0.562992E+09 0.177540E+10 94511521.45
September 0.115668E+10 0.600953E+09 0.555729E+09 0.229640E+10 0.275052E+09
October 0.164065E+10 0.111467E+10 0.525978E+09 0.270903E+10 0.561119E+09
November 0.191093E+10 0.146165E+10 0.449279E+09 0.274745E+10 0.103556E+10
December 0.194172E+10 0.145878E+10 0.482936E+09 0.260205E+10 0.142276E+10
           
Annual Sum or Average 0.150901E+11 0.873168E+10 0.635845E+10 0.251166E+11 0.758558E+10
Minimum of Months 0.569764E+09 35850177.24 0.449279E+09 0.141762E+10 44653482.94
Maximum of Months 0.194172E+10 0.146165E+10 0.603391E+09 0.274745E+10 0.142276E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: CAFE_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.532594E+10 0.403562E+10 0.129032E+10 0.724458E+10 0.371595E+10
February 0.452597E+10 0.320978E+10 0.131618E+10 0.630826E+10 0.293298E+10
March 0.391998E+10 0.222087E+10 0.169911E+10 0.568757E+10 0.278840E+10
April 0.264332E+10 0.992277E+09 0.165105E+10 0.452198E+10 0.144465E+10
May 0.193831E+10 0.284261E+09 0.165405E+10 0.394869E+10 0.728519E+09
June 0.160442E+10 0.100952E+09 0.150347E+10 0.417120E+10 0.264166E+09
July 0.168364E+10 0.149273E+09 0.153437E+10 0.437894E+10 0.156202E+09
August 0.212533E+10 0.539978E+09 0.158535E+10 0.496111E+10 0.309958E+09
September 0.325714E+10 0.169224E+10 0.156490E+10 0.645915E+10 0.815853E+09
October 0.461996E+10 0.313884E+10 0.148112E+10 0.760725E+10 0.162097E+10
November 0.538106E+10 0.411592E+10 0.126514E+10 0.770236E+10 0.294343E+10
December 0.546774E+10 0.410783E+10 0.135992E+10 0.727685E+10 0.403535E+10
           
Annual Sum or Average 0.424928E+11 0.245878E+11 0.179050E+11 0.702679E+11 0.217564E+11
Minimum of Months 0.160442E+10 0.100952E+09 0.126514E+10 0.394869E+10 0.156202E+09
Maximum of Months 0.546774E+10 0.411592E+10 0.169911E+10 0.770236E+10 0.403535E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: LOBBY_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.691870E+10 0.524250E+10 0.167620E+10 0.959853E+10 0.492615E+10
February 0.587949E+10 0.416969E+10 0.170980E+10 0.837378E+10 0.388520E+10
March 0.509227E+10 0.288503E+10 0.220724E+10 0.755747E+10 0.371203E+10
April 0.343383E+10 0.128902E+10 0.214480E+10 0.604235E+10 0.192327E+10
May 0.251798E+10 0.369271E+09 0.214871E+10 0.529535E+10 0.975347E+09
June 0.208423E+10 0.131142E+09 0.195309E+10 0.561147E+10 0.348151E+09
July 0.218715E+10 0.193914E+09 0.199323E+10 0.588539E+10 0.203047E+09
August 0.276092E+10 0.701462E+09 0.205946E+10 0.666340E+10 0.399334E+09
September 0.423121E+10 0.219832E+10 0.203289E+10 0.865174E+10 0.105299E+10
October 0.600158E+10 0.407753E+10 0.192406E+10 0.101593E+11 0.210967E+10
November 0.699030E+10 0.534681E+10 0.164349E+10 0.102434E+11 0.388016E+10
December 0.710291E+10 0.533630E+10 0.176661E+10 0.963056E+10 0.535873E+10
           
Annual Sum or Average 0.552006E+11 0.319410E+11 0.232596E+11 0.937127E+11 0.287741E+11
Minimum of Months 0.208423E+10 0.131142E+09 0.164349E+10 0.529535E+10 0.203047E+09
Maximum of Months 0.710291E+10 0.534681E+10 0.220724E+10 0.102434E+11 0.535873E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.373955E+09 0.283356E+09 90599047.15 0.508271E+09 0.265975E+09
February 0.317786E+09 0.225371E+09 92415031.30 0.441696E+09 0.210668E+09
March 0.275237E+09 0.155935E+09 0.119302E+09 0.392950E+09 0.202528E+09
April 0.185599E+09 69671463.64 0.115927E+09 0.309751E+09 0.103634E+09
May 0.136098E+09 19958985.63 0.116139E+09 0.270522E+09 50062393.52
June 0.112654E+09 7088195.76 0.105566E+09 0.291726E+09 16753099.85
July 0.118216E+09 10480991.36 0.107735E+09 0.304593E+09 9567278.48
August 0.149228E+09 37913864.16 0.111315E+09 0.344646E+09 19390097.41
September 0.228697E+09 0.118819E+09 0.109878E+09 0.448758E+09 56262493.37
October 0.324385E+09 0.220389E+09 0.103996E+09 0.531284E+09 0.114781E+09
November 0.377825E+09 0.288994E+09 88830943.98 0.540785E+09 0.210345E+09
December 0.383911E+09 0.288426E+09 95485408.74 0.514012E+09 0.288112E+09
           
Annual Sum or Average 0.298359E+10 0.172640E+10 0.125719E+10 0.489899E+10 0.154808E+10
Minimum of Months 0.112654E+09 7088195.76 88830943.98 0.270522E+09 9567278.48
Maximum of Months 0.383911E+09 0.288994E+09 0.119302E+09 0.540785E+09 0.288112E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_1_FLR_3_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.287674E+09 0.162146E+09 0.125527E+09 0.307411E+09 0.548951E+09
February 0.292474E+09 0.155192E+09 0.137282E+09 0.338817E+09 0.434077E+09
March 0.441845E+09 0.236918E+09 0.204927E+09 0.573288E+09 0.392160E+09
April 0.490686E+09 0.264679E+09 0.226007E+09 0.766568E+09 0.191250E+09
May 0.547180E+09 0.292832E+09 0.254348E+09 0.973346E+09 92506060.41
June 0.515254E+09 0.276659E+09 0.238595E+09 0.106288E+10 31054631.99
July 0.472844E+09 0.234945E+09 0.237900E+09 0.991248E+09 17279522.59
August 0.457839E+09 0.233254E+09 0.224585E+09 0.912480E+09 35851187.08
September 0.454872E+09 0.253932E+09 0.200940E+09 0.828485E+09 0.106296E+09
October 0.404989E+09 0.237094E+09 0.167895E+09 0.629678E+09 0.224729E+09
November 0.327016E+09 0.198972E+09 0.128044E+09 0.401485E+09 0.434769E+09
December 0.272539E+09 0.147971E+09 0.124568E+09 0.275101E+09 0.604667E+09
           
Annual Sum or Average 0.496521E+10 0.269459E+10 0.227062E+10 0.806078E+10 0.311359E+10
Minimum of Months 0.272539E+09 0.147971E+09 0.124568E+09 0.275101E+09 17279522.59
Maximum of Months 0.547180E+09 0.292832E+09 0.254348E+09 0.106288E+10 0.604667E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_2_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 54635219.79 0.00 54635219.79 12456338.71 0.295746E+09
February 60259072.44 0.00 60259072.44 29807186.92 0.232806E+09
March 87327152.96 3456.98 87323695.98 66565134.46 0.211612E+09
April 98134921.78 1250183.62 96884738.16 0.130495E+09 99904764.61
May 0.119788E+09 8827959.99 0.110960E+09 0.227309E+09 46229148.27
June 0.123276E+09 15361483.16 0.107914E+09 0.308742E+09 16149571.49
July 0.117686E+09 11543657.45 0.106142E+09 0.298100E+09 9132226.64
August 99533259.29 2367984.07 97165275.22 0.235058E+09 18473178.00
September 83800633.79 105909.72 83694724.07 0.164123E+09 55570941.11
October 71778804.06 0.00 71778804.06 90489365.94 0.118435E+09
November 56077421.72 0.00 56077421.72 23885947.42 0.233700E+09
December 54212081.06 0.00 54212081.06 8862810.98 0.326813E+09
           
Annual Sum or Average 0.102651E+10 39460634.99 0.987047E+09 0.159589E+10 0.166457E+10
Minimum of Months 54212081.06 0.00 54212081.06 8862810.98 9132226.64
Maximum of Months 0.123276E+09 15361483.16 0.110960E+09 0.308742E+09 0.326813E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_2_FLR_3_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.287674E+09 0.162146E+09 0.125527E+09 0.324951E+09 0.532255E+09
February 0.292474E+09 0.155192E+09 0.137282E+09 0.354255E+09 0.422159E+09
March 0.441845E+09 0.236918E+09 0.204927E+09 0.587163E+09 0.384934E+09
April 0.490686E+09 0.264679E+09 0.226007E+09 0.773299E+09 0.188959E+09
May 0.547180E+09 0.292832E+09 0.254348E+09 0.974969E+09 92124443.53
June 0.515254E+09 0.276659E+09 0.238595E+09 0.106250E+10 31077433.16
July 0.472844E+09 0.234945E+09 0.237900E+09 0.991558E+09 17219117.19
August 0.457839E+09 0.233254E+09 0.224585E+09 0.915843E+09 35262350.48
September 0.454872E+09 0.253932E+09 0.200940E+09 0.836177E+09 0.103565E+09
October 0.404989E+09 0.237094E+09 0.167895E+09 0.642727E+09 0.218155E+09
November 0.327016E+09 0.198972E+09 0.128044E+09 0.418159E+09 0.421743E+09
December 0.272539E+09 0.147971E+09 0.124568E+09 0.292187E+09 0.587020E+09
           
Annual Sum or Average 0.496521E+10 0.269459E+10 0.227062E+10 0.817379E+10 0.303447E+10
Minimum of Months 0.272539E+09 0.147971E+09 0.124568E+09 0.292187E+09 17219117.19
Maximum of Months 0.547180E+09 0.292832E+09 0.254348E+09 0.106250E+10 0.587020E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.299104E+09 0.226640E+09 72464826.42 0.392345E+09 0.242469E+09
February 0.254178E+09 0.180261E+09 73917324.87 0.340752E+09 0.194475E+09
March 0.220146E+09 0.124724E+09 95422629.83 0.301824E+09 0.186310E+09
April 0.148450E+09 55726088.50 92723544.22 0.238688E+09 0.102672E+09
May 0.108857E+09 15964013.69 92892545.85 0.206902E+09 54827301.07
June 90105188.78 5669429.11 84435759.67 0.222227E+09 21556791.11
July 94554156.30 8383125.91 86171030.39 0.230796E+09 15651122.90
August 0.119359E+09 30325060.49 89033931.16 0.263875E+09 26472808.71
September 0.182921E+09 95036114.58 87885276.20 0.351092E+09 61150568.20
October 0.259457E+09 0.176276E+09 83180150.54 0.413633E+09 0.115086E+09
November 0.302200E+09 0.231149E+09 71050625.13 0.420291E+09 0.194276E+09
December 0.307068E+09 0.230695E+09 76373138.43 0.396671E+09 0.256603E+09
           
Annual Sum or Average 0.238640E+10 0.138085E+10 0.100555E+10 0.377909E+10 0.147155E+10
Minimum of Months 90105188.78 5669429.11 71050625.13 0.206902E+09 15651122.90
Maximum of Months 0.307068E+09 0.231149E+09 95422629.83 0.420291E+09 0.256603E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 43713969.60 0.00 43713969.60 8540331.93 0.246730E+09
February 48213648.10 0.00 48213648.10 23580161.30 0.192480E+09
March 69870982.94 2765.95 69868216.99 54959432.08 0.171676E+09
April 78518344.10 1000279.47 77518064.63 0.110964E+09 78461667.44
May 95843144.60 7063304.15 88779840.45 0.192312E+09 34732635.61
June 98633813.54 12290815.53 86342998.01 0.260101E+09 11158549.39
July 94160895.41 9236150.10 84924745.31 0.251240E+09 5897204.96
August 79637162.39 1894638.37 77742524.03 0.199808E+09 12967140.09
September 67049393.63 84739.01 66964654.62 0.140499E+09 41355941.49
October 57430655.00 0.00 57430655.00 77280343.79 93349095.14
November 44867884.08 0.00 44867884.08 19424185.98 0.191420E+09
December 43375413.74 0.00 43375413.74 5836933.57 0.273183E+09
           
Annual Sum or Average 0.821315E+09 31572692.58 0.789743E+09 0.134455E+10 0.135341E+10
Minimum of Months 43375413.74 0.00 43375413.74 5836933.57 5897204.96
Maximum of Months 98633813.54 12290815.53 88779840.45 0.260101E+09 0.273183E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_5_FLR_3_WALL_EAST_WINDOW

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.272406E+09 0.147604E+09 0.124803E+09 0.256882E+09 0.520408E+09
February 0.330219E+09 0.188293E+09 0.141926E+09 0.371702E+09 0.403759E+09
March 0.450634E+09 0.248122E+09 0.202511E+09 0.561662E+09 0.361266E+09
April 0.525720E+09 0.291582E+09 0.234138E+09 0.808000E+09 0.173156E+09
May 0.560008E+09 0.304221E+09 0.255786E+09 0.990592E+09 84197288.95
June 0.542173E+09 0.301473E+09 0.240700E+09 0.110851E+10 28959251.99
July 0.502747E+09 0.262839E+09 0.239908E+09 0.104238E+10 16628024.76
August 0.478911E+09 0.245239E+09 0.233671E+09 0.949913E+09 33743195.45
September 0.459814E+09 0.262571E+09 0.197243E+09 0.826435E+09 97230984.79
October 0.363675E+09 0.195894E+09 0.167781E+09 0.542644E+09 0.210482E+09
November 0.315129E+09 0.183035E+09 0.132093E+09 0.349813E+09 0.404922E+09
December 0.272612E+09 0.144459E+09 0.128153E+09 0.245240E+09 0.571621E+09
           
Annual Sum or Average 0.507405E+10 0.277533E+10 0.229871E+10 0.805377E+10 0.290637E+10
Minimum of Months 0.272406E+09 0.144459E+09 0.124803E+09 0.245240E+09 16628024.76
Maximum of Months 0.560008E+09 0.304221E+09 0.255786E+09 0.110851E+10 0.571621E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.373955E+09 0.283356E+09 90599047.15 0.506693E+09 0.264396E+09
February 0.317786E+09 0.225371E+09 92415031.30 0.437743E+09 0.210173E+09
March 0.275237E+09 0.155935E+09 0.119302E+09 0.388187E+09 0.201265E+09
April 0.185599E+09 69671463.64 0.115927E+09 0.305440E+09 0.103389E+09
May 0.136098E+09 19958985.63 0.116139E+09 0.267531E+09 49522068.02
June 0.112654E+09 7088195.76 0.105566E+09 0.289460E+09 16286581.56
July 0.118216E+09 10480991.36 0.107735E+09 0.302690E+09 9187510.80
August 0.149228E+09 37913864.16 0.111315E+09 0.342930E+09 19018163.46
September 0.228697E+09 0.118819E+09 0.109878E+09 0.446929E+09 55458465.34
October 0.324385E+09 0.220389E+09 0.103996E+09 0.529815E+09 0.112743E+09
November 0.377825E+09 0.288994E+09 88830943.98 0.538562E+09 0.208696E+09
December 0.383911E+09 0.288426E+09 95485408.74 0.512271E+09 0.287035E+09
           
Annual Sum or Average 0.298359E+10 0.172640E+10 0.125719E+10 0.486825E+10 0.153717E+10
Minimum of Months 0.112654E+09 7088195.76 88830943.98 0.267531E+09 9187510.80
Maximum of Months 0.383911E+09 0.288994E+09 0.119302E+09 0.538562E+09 0.287035E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_6_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 54635219.79 0.00 54635219.79 11665091.39 0.294694E+09
February 60259072.44 0.00 60259072.44 27857895.55 0.234019E+09
March 87327152.96 3456.98 87323695.98 63211731.87 0.212058E+09
April 98134921.78 1250183.62 96884738.16 0.125950E+09 0.100077E+09
May 0.119788E+09 8827959.99 0.110960E+09 0.223921E+09 45487642.84
June 0.123276E+09 15361483.16 0.107914E+09 0.306679E+09 15708092.15
July 0.117686E+09 11543657.45 0.106142E+09 0.296329E+09 8788916.03
August 99533259.29 2367984.07 97165275.22 0.233120E+09 18066326.44
September 83800633.79 105909.72 83694724.07 0.161949E+09 55023213.21
October 71778804.06 0.00 71778804.06 88610149.52 0.116816E+09
November 56077421.72 0.00 56077421.72 22773676.11 0.232030E+09
December 54212081.06 0.00 54212081.06 7988188.11 0.326610E+09
           
Annual Sum or Average 0.102651E+10 39460634.99 0.987047E+09 0.157005E+10 0.165938E+10
Minimum of Months 54212081.06 0.00 54212081.06 7988188.11 8788916.03
Maximum of Months 0.123276E+09 15361483.16 0.110960E+09 0.306679E+09 0.326610E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_6_FLR_3_WALL_EAST_WINDOW

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.272406E+09 0.147604E+09 0.124803E+09 0.270666E+09 0.499141E+09
February 0.330219E+09 0.188293E+09 0.141926E+09 0.385770E+09 0.390260E+09
March 0.450634E+09 0.248122E+09 0.202511E+09 0.574377E+09 0.353534E+09
April 0.525720E+09 0.291582E+09 0.234138E+09 0.813721E+09 0.170985E+09
May 0.560008E+09 0.304221E+09 0.255786E+09 0.991977E+09 83852554.07
June 0.542173E+09 0.301473E+09 0.240700E+09 0.110837E+10 28998944.25
July 0.502747E+09 0.262839E+09 0.239908E+09 0.104285E+10 16589053.28
August 0.478911E+09 0.245239E+09 0.233671E+09 0.953116E+09 33192377.89
September 0.459814E+09 0.262571E+09 0.197243E+09 0.833495E+09 94718429.72
October 0.363675E+09 0.195894E+09 0.167781E+09 0.554639E+09 0.203947E+09
November 0.315129E+09 0.183035E+09 0.132093E+09 0.365936E+09 0.389151E+09
December 0.272612E+09 0.144459E+09 0.128153E+09 0.256663E+09 0.548083E+09
           
Annual Sum or Average 0.507405E+10 0.277533E+10 0.229871E+10 0.815158E+10 0.281245E+10
Minimum of Months 0.272406E+09 0.144459E+09 0.124803E+09 0.256663E+09 16589053.28
Maximum of Months 0.560008E+09 0.304221E+09 0.255786E+09 0.110837E+10 0.548083E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 69192058.57 0.00 69192058.57 12665987.41 0.395840E+09
February 76314313.11 0.00 76314313.11 37576296.85 0.306502E+09
March 0.110594E+09 4378.05 0.110590E+09 90362184.48 0.269992E+09
April 0.124282E+09 1583278.67 0.122698E+09 0.186051E+09 0.121799E+09
May 0.151704E+09 11180054.31 0.140524E+09 0.316898E+09 55259276.93
June 0.156121E+09 19454349.17 0.136667E+09 0.416193E+09 20113469.49
July 0.149041E+09 14619313.80 0.134422E+09 0.403654E+09 10972293.11
August 0.126053E+09 2998902.41 0.123054E+09 0.321483E+09 22742528.21
September 0.106128E+09 134127.98 0.105994E+09 0.227878E+09 69050987.09
October 90903326.35 0.00 90903326.35 0.126876E+09 0.147194E+09
November 71018516.32 0.00 71018516.32 30782769.37 0.304489E+09
December 68656180.07 0.00 68656180.07 8564463.53 0.440771E+09
           
Annual Sum or Average 0.130001E+10 49974404.39 0.125003E+10 0.217898E+10 0.216473E+10
Minimum of Months 68656180.07 0.00 68656180.07 8564463.53 10972293.11
Maximum of Months 0.156121E+09 19454349.17 0.140524E+09 0.416193E+09 0.440771E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 25507057.81 0.00 25507057.81 4669207.42 0.145923E+09
February 28132615.74 0.00 28132615.74 13852178.93 0.112989E+09
March 40769649.09 1613.93 40768035.16 33311242.80 99530367.87
April 45815375.73 583662.08 45231713.65 68586148.55 44900312.74
May 55924379.60 4121430.95 51802948.65 0.116822E+09 20370857.58
June 57552732.16 7171678.64 50381053.51 0.153426E+09 7414657.69
July 54942788.87 5389284.40 49553504.47 0.148804E+09 4044841.57
August 46468205.09 1105519.60 45362685.49 0.118512E+09 8383837.59
September 39123254.53 49445.13 39073809.41 84005265.53 25455053.02
October 33510730.10 0.00 33510730.10 46771731.75 54261707.59
November 26180365.76 0.00 26180365.76 11347803.41 0.112247E+09
December 25309510.80 0.00 25309510.80 3157215.88 0.162487E+09
           
Annual Sum or Average 0.479237E+09 18422634.73 0.460814E+09 0.803264E+09 0.798008E+09
Minimum of Months 25309510.80 0.00 25309510.80 3157215.88 4044841.57
Maximum of Months 57552732.16 7171678.64 51802948.65 0.153426E+09 0.162487E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.174486E+09 0.132213E+09 42273150.31 0.239732E+09 0.126616E+09
February 0.148278E+09 0.105157E+09 43120481.20 0.209474E+09 99115687.37
March 0.128425E+09 72758842.37 55665836.43 0.188811E+09 93533600.58
April 86599719.45 32508424.18 54091295.27 0.153758E+09 46007024.84
May 63502666.49 9312782.27 54189884.22 0.137329E+09 22027258.69
June 52563848.94 3307323.58 49256525.36 0.145309E+09 7719518.49
July 55159202.88 4890388.33 50268814.55 0.151731E+09 4211016.55
August 69629375.31 17690456.23 51938919.07 0.170285E+09 8692911.82
September 0.106709E+09 55440358.52 51268838.62 0.218419E+09 25174941.92
October 0.151357E+09 0.102833E+09 48524052.02 0.255986E+09 51312988.10
November 0.176291E+09 0.134843E+09 41448160.50 0.257259E+09 98133961.42
December 0.179131E+09 0.134578E+09 44553106.94 0.241512E+09 0.137672E+09
           
Annual Sum or Average 0.139213E+10 0.805533E+09 0.586599E+09 0.236960E+10 0.720216E+09
Minimum of Months 52563848.94 3307323.58 41448160.50 0.137329E+09 4211016.55
Maximum of Months 0.179131E+09 0.134843E+09 55665836.43 0.257259E+09 0.137672E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.473590E+09 0.358852E+09 0.114738E+09 0.650681E+09 0.343661E+09
February 0.402456E+09 0.285418E+09 0.117038E+09 0.568554E+09 0.269020E+09
March 0.348571E+09 0.197482E+09 0.151088E+09 0.512472E+09 0.253869E+09
April 0.235049E+09 88234512.68 0.146815E+09 0.417330E+09 0.124873E+09
May 0.172359E+09 25276795.96 0.147082E+09 0.372738E+09 59786485.66
June 0.142669E+09 8976752.69 0.133692E+09 0.394399E+09 20952352.17
July 0.149713E+09 13273514.24 0.136440E+09 0.411829E+09 11429560.27
August 0.188988E+09 48015516.72 0.140973E+09 0.462190E+09 23594340.77
September 0.289631E+09 0.150476E+09 0.139154E+09 0.592833E+09 68329941.80
October 0.410813E+09 0.279109E+09 0.131704E+09 0.694798E+09 0.139274E+09
November 0.478491E+09 0.365992E+09 0.112499E+09 0.698252E+09 0.266356E+09
December 0.486199E+09 0.365273E+09 0.120926E+09 0.655514E+09 0.373669E+09
           
Annual Sum or Average 0.377853E+10 0.218638E+10 0.159215E+10 0.643159E+10 0.195481E+10
Minimum of Months 0.142669E+09 8976752.69 0.112499E+09 0.372738E+09 11429560.27
Maximum of Months 0.486199E+09 0.365992E+09 0.151088E+09 0.698252E+09 0.373669E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.373955E+09 0.283356E+09 90599047.15 0.505381E+09 0.263044E+09
February 0.317786E+09 0.225371E+09 92415031.30 0.438454E+09 0.208610E+09
March 0.275237E+09 0.155935E+09 0.119302E+09 0.388320E+09 0.201036E+09
April 0.185599E+09 69671463.64 0.115927E+09 0.304519E+09 0.103074E+09
May 0.136098E+09 19958985.63 0.116139E+09 0.266049E+09 49556093.97
June 0.112654E+09 7088195.76 0.105566E+09 0.288004E+09 16530343.82
July 0.118216E+09 10480991.36 0.107735E+09 0.299617E+09 9643297.91
August 0.149228E+09 37913864.16 0.111315E+09 0.339346E+09 19413502.97
September 0.228697E+09 0.118819E+09 0.109878E+09 0.442817E+09 56137432.45
October 0.324385E+09 0.220389E+09 0.103996E+09 0.525471E+09 0.114512E+09
November 0.377825E+09 0.288994E+09 88830943.98 0.537059E+09 0.208419E+09
December 0.383911E+09 0.288426E+09 95485408.74 0.512464E+09 0.284463E+09
           
Annual Sum or Average 0.298359E+10 0.172640E+10 0.125719E+10 0.484750E+10 0.153444E+10
Minimum of Months 0.112654E+09 7088195.76 88830943.98 0.266049E+09 9643297.91
Maximum of Months 0.383911E+09 0.288994E+09 0.119302E+09 0.537059E+09 0.284463E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_1_FLR_6_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.287674E+09 0.162146E+09 0.125527E+09 0.304742E+09 0.541946E+09
February 0.292474E+09 0.155192E+09 0.137282E+09 0.334941E+09 0.428991E+09
March 0.441845E+09 0.236918E+09 0.204927E+09 0.565463E+09 0.388354E+09
April 0.490686E+09 0.264679E+09 0.226007E+09 0.755660E+09 0.189934E+09
May 0.547180E+09 0.292832E+09 0.254348E+09 0.960549E+09 91499874.81
June 0.515254E+09 0.276659E+09 0.238595E+09 0.105129E+10 30798247.87
July 0.472844E+09 0.234945E+09 0.237900E+09 0.978554E+09 17435870.30
August 0.457839E+09 0.233254E+09 0.224585E+09 0.900600E+09 35959164.71
September 0.454872E+09 0.253932E+09 0.200940E+09 0.817798E+09 0.106069E+09
October 0.404989E+09 0.237094E+09 0.167895E+09 0.621448E+09 0.223703E+09
November 0.327016E+09 0.198972E+09 0.128044E+09 0.396991E+09 0.429833E+09
December 0.272539E+09 0.147971E+09 0.124568E+09 0.273966E+09 0.595344E+09
           
Annual Sum or Average 0.496521E+10 0.269459E+10 0.227062E+10 0.796200E+10 0.307987E+10
Minimum of Months 0.272539E+09 0.147971E+09 0.124568E+09 0.273966E+09 17435870.30
Maximum of Months 0.547180E+09 0.292832E+09 0.254348E+09 0.105129E+10 0.595344E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_2_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 54635219.79 0.00 54635219.79 13090082.78 0.291620E+09
February 60259072.44 0.00 60259072.44 29891877.29 0.229809E+09
March 87327152.96 3456.98 87323695.98 65653702.20 0.209630E+09
April 98134921.78 1250183.62 96884738.16 0.127232E+09 99369693.50
May 0.119788E+09 8827959.99 0.110960E+09 0.223147E+09 45786589.22
June 0.123276E+09 15361483.16 0.107914E+09 0.304368E+09 16005483.82
July 0.117686E+09 11543657.45 0.106142E+09 0.292911E+09 9219139.32
August 99533259.29 2367984.07 97165275.22 0.230692E+09 18516185.21
September 83800633.79 105909.72 83694724.07 0.160268E+09 55428339.08
October 71778804.06 0.00 71778804.06 88047376.92 0.117915E+09
November 56077421.72 0.00 56077421.72 23802646.18 0.231026E+09
December 54212081.06 0.00 54212081.06 9518369.81 0.321568E+09
           
Annual Sum or Average 0.102651E+10 39460634.99 0.987047E+09 0.156862E+10 0.164589E+10
Minimum of Months 54212081.06 0.00 54212081.06 9518369.81 9219139.32
Maximum of Months 0.123276E+09 15361483.16 0.110960E+09 0.304368E+09 0.321568E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_2_FLR_6_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.287674E+09 0.162146E+09 0.125527E+09 0.324073E+09 0.524739E+09
February 0.292474E+09 0.155192E+09 0.137282E+09 0.351681E+09 0.416538E+09
March 0.441845E+09 0.236918E+09 0.204927E+09 0.580192E+09 0.380784E+09
April 0.490686E+09 0.264679E+09 0.226007E+09 0.762195E+09 0.187607E+09
May 0.547180E+09 0.292832E+09 0.254348E+09 0.962059E+09 91133723.35
June 0.515254E+09 0.276659E+09 0.238595E+09 0.105088E+10 30824805.72
July 0.472844E+09 0.234945E+09 0.237900E+09 0.978831E+09 17379968.53
August 0.457839E+09 0.233254E+09 0.224585E+09 0.903873E+09 35363549.89
September 0.454872E+09 0.253932E+09 0.200940E+09 0.825443E+09 0.103227E+09
October 0.404989E+09 0.237094E+09 0.167895E+09 0.634615E+09 0.216780E+09
November 0.327016E+09 0.198972E+09 0.128044E+09 0.415071E+09 0.415819E+09
December 0.272539E+09 0.147971E+09 0.124568E+09 0.292782E+09 0.577590E+09
           
Annual Sum or Average 0.496521E+10 0.269459E+10 0.227062E+10 0.808169E+10 0.299779E+10
Minimum of Months 0.272539E+09 0.147971E+09 0.124568E+09 0.292782E+09 17379968.53
Maximum of Months 0.547180E+09 0.292832E+09 0.254348E+09 0.105088E+10 0.577590E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.548441E+09 0.415568E+09 0.132872E+09 0.720156E+09 0.404646E+09
February 0.466063E+09 0.330528E+09 0.135536E+09 0.627146E+09 0.318940E+09
March 0.403662E+09 0.228694E+09 0.174968E+09 0.559695E+09 0.300140E+09
April 0.272199E+09 0.102180E+09 0.170019E+09 0.449515E+09 0.148917E+09
May 0.199600E+09 29271767.90 0.170329E+09 0.402926E+09 68947983.96
June 0.165218E+09 10395519.34 0.154822E+09 0.439594E+09 21655569.63
July 0.173375E+09 15371379.69 0.158004E+09 0.455420E+09 12116833.16
August 0.218858E+09 55604320.39 0.163253E+09 0.509593E+09 26349933.25
September 0.335406E+09 0.174259E+09 0.161147E+09 0.653871E+09 79835313.53
October 0.475742E+09 0.323222E+09 0.152520E+09 0.766136E+09 0.170114E+09
November 0.554116E+09 0.423837E+09 0.130279E+09 0.773419E+09 0.317477E+09
December 0.563043E+09 0.423004E+09 0.140039E+09 0.727935E+09 0.437361E+09
           
Annual Sum or Average 0.437572E+10 0.253194E+10 0.184379E+10 0.708540E+10 0.230650E+10
Minimum of Months 0.165218E+09 10395519.34 0.130279E+09 0.402926E+09 12116833.16
Maximum of Months 0.563043E+09 0.423837E+09 0.174968E+09 0.773419E+09 0.437361E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: BANQUET_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.382432E+09 0.00 0.382432E+09 58951849.05 0.223366E+10
February 0.421798E+09 0.00 0.421798E+09 0.190511E+09 0.174036E+10
March 0.611267E+09 24197.95 0.611243E+09 0.462566E+09 0.155953E+10
April 0.686918E+09 8750953.90 0.678167E+09 0.975923E+09 0.746464E+09
May 0.838485E+09 61793379.53 0.776691E+09 0.168836E+10 0.362580E+09
June 0.862899E+09 0.107526E+09 0.755372E+09 0.225356E+10 0.141621E+09
July 0.823767E+09 80802541.81 0.742965E+09 0.217115E+10 90480253.71
August 0.696706E+09 16575260.69 0.680131E+09 0.173765E+10 0.165738E+09
September 0.586582E+09 741339.97 0.585841E+09 0.124658E+10 0.418525E+09
October 0.502433E+09 0.00 0.502433E+09 0.674602E+09 0.873986E+09
November 0.392527E+09 0.00 0.392527E+09 0.153535E+09 0.173080E+10
December 0.379470E+09 0.00 0.379470E+09 40832122.20 0.245907E+10
           
Annual Sum or Average 0.718528E+10 0.276214E+09 0.690907E+10 0.116542E+11 0.125228E+11
Minimum of Months 0.379470E+09 0.00 0.379470E+09 40832122.20 90480253.71
Maximum of Months 0.862899E+09 0.107526E+09 0.776691E+09 0.225356E+10 0.245907E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: DINING_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.382432E+09 0.00 0.382432E+09 53267786.88 0.227861E+10
February 0.421798E+09 0.00 0.421798E+09 0.181553E+09 0.177825E+10
March 0.611267E+09 24197.95 0.611243E+09 0.446543E+09 0.159791E+10
April 0.686918E+09 8750953.90 0.678167E+09 0.950032E+09 0.776114E+09
May 0.838485E+09 61793379.53 0.776691E+09 0.165009E+10 0.384845E+09
June 0.862899E+09 0.107526E+09 0.755372E+09 0.221150E+10 0.153627E+09
July 0.823767E+09 80802541.81 0.742965E+09 0.212746E+10 0.102383E+09
August 0.696706E+09 16575260.69 0.680131E+09 0.169849E+10 0.181652E+09
September 0.586582E+09 741339.97 0.585841E+09 0.121917E+10 0.442545E+09
October 0.502433E+09 0.00 0.502433E+09 0.654921E+09 0.907268E+09
November 0.392527E+09 0.00 0.392527E+09 0.144338E+09 0.177121E+10
December 0.379470E+09 0.00 0.379470E+09 36967489.12 0.250473E+10
           
Annual Sum or Average 0.718528E+10 0.276214E+09 0.690907E+10 0.113743E+11 0.128791E+11
Minimum of Months 0.379470E+09 0.00 0.379470E+09 36967489.12 0.102383E+09
Maximum of Months 0.862899E+09 0.107526E+09 0.776691E+09 0.221150E+10 0.250473E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: KITCHEN_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 54635219.79 0.00 54635219.79 9266987.71 0.323329E+09
February 60259072.44 0.00 60259072.44 29297062.30 0.255381E+09
March 87327152.96 3456.98 87323695.98 67169779.51 0.233027E+09
April 98134921.78 1250183.62 96884738.16 0.144742E+09 0.116220E+09
May 0.119788E+09 8827959.99 0.110960E+09 0.248394E+09 60469918.49
June 0.123276E+09 15361483.16 0.107914E+09 0.333752E+09 23919131.35
July 0.117686E+09 11543657.45 0.106142E+09 0.325028E+09 17206397.57
August 99533259.29 2367984.07 97165275.22 0.262167E+09 28826847.36
September 83800633.79 105909.72 83694724.07 0.192616E+09 64732002.01
October 71778804.06 0.00 71778804.06 0.104040E+09 0.132888E+09
November 56077421.72 0.00 56077421.72 24491332.48 0.253392E+09
December 54212081.06 0.00 54212081.06 6787997.48 0.350976E+09
           
Annual Sum or Average 0.102651E+10 39460634.99 0.987047E+09 0.174775E+10 0.186037E+10
Minimum of Months 54212081.06 0.00 54212081.06 6787997.48 17206397.57
Maximum of Months 0.123276E+09 15361483.16 0.110960E+09 0.333752E+09 0.350976E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: KITCHEN_FLR_6_WALL_EAST_WINDOW

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.544774E+09 0.295186E+09 0.249587E+09 0.537065E+09 0.110416E+10
February 0.660391E+09 0.376560E+09 0.283831E+09 0.787873E+09 0.866230E+09
March 0.901204E+09 0.496210E+09 0.404994E+09 0.118089E+10 0.790269E+09
April 0.105137E+10 0.583122E+09 0.468243E+09 0.170585E+10 0.408656E+09
May 0.111994E+10 0.608399E+09 0.511536E+09 0.207462E+10 0.225027E+09
June 0.108427E+10 0.602903E+09 0.481366E+09 0.231218E+10 89477376.49
July 0.100542E+10 0.525641E+09 0.479782E+09 0.218573E+10 65784221.29
August 0.957753E+09 0.490444E+09 0.467309E+09 0.201075E+10 0.108284E+09
September 0.919563E+09 0.525105E+09 0.394458E+09 0.178571E+10 0.233071E+09
October 0.727299E+09 0.391760E+09 0.335538E+09 0.117287E+10 0.473539E+09
November 0.630213E+09 0.366045E+09 0.264168E+09 0.747975E+09 0.861810E+09
December 0.545185E+09 0.288898E+09 0.256287E+09 0.518186E+09 0.119386E+10
           
Annual Sum or Average 0.101474E+11 0.555027E+10 0.459710E+10 0.170197E+11 0.642017E+10
Minimum of Months 0.544774E+09 0.288898E+09 0.249587E+09 0.518186E+09 65784221.29
Maximum of Months 0.111994E+10 0.608399E+09 0.511536E+09 0.231218E+10 0.119386E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.373955E+09 0.283356E+09 90599047.15 0.519182E+09 0.283393E+09
February 0.317786E+09 0.225371E+09 92415031.30 0.452129E+09 0.226622E+09
March 0.275237E+09 0.155935E+09 0.119302E+09 0.403136E+09 0.218277E+09
April 0.185599E+09 69671463.64 0.115927E+09 0.325628E+09 0.117974E+09
May 0.136098E+09 19958985.63 0.116139E+09 0.289282E+09 63565526.86
June 0.112654E+09 7088195.76 0.105566E+09 0.315013E+09 24257247.86
July 0.118216E+09 10480991.36 0.107735E+09 0.330449E+09 17513876.95
August 0.149228E+09 37913864.16 0.111315E+09 0.373012E+09 29274860.25
September 0.228697E+09 0.118819E+09 0.109878E+09 0.481127E+09 64357464.44
October 0.324385E+09 0.220389E+09 0.103996E+09 0.554834E+09 0.126427E+09
November 0.377825E+09 0.288994E+09 88830943.98 0.557566E+09 0.223493E+09
December 0.383911E+09 0.288426E+09 95485408.74 0.526694E+09 0.302443E+09
           
Annual Sum or Average 0.298359E+10 0.172640E+10 0.125719E+10 0.512805E+10 0.169760E+10
Minimum of Months 0.112654E+09 7088195.76 88830943.98 0.289282E+09 17513876.95
Maximum of Months 0.383911E+09 0.288994E+09 0.119302E+09 0.557566E+09 0.302443E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 69192058.57 0.00 69192058.57 10824474.14 0.399484E+09
February 76314313.11 0.00 76314313.11 34734121.61 0.308780E+09
March 0.110594E+09 4378.05 0.110590E+09 85646602.25 0.271829E+09
April 0.124282E+09 1583278.67 0.122698E+09 0.180146E+09 0.121881E+09
May 0.151704E+09 11180054.31 0.140524E+09 0.314224E+09 52811703.49
June 0.156121E+09 19454349.17 0.136667E+09 0.415444E+09 17913761.79
July 0.149041E+09 14619313.80 0.134422E+09 0.401478E+09 9569400.25
August 0.126053E+09 2998902.41 0.123054E+09 0.320015E+09 20611547.23
September 0.106128E+09 134127.98 0.105994E+09 0.225111E+09 64993246.29
October 90903326.35 0.00 90903326.35 0.122171E+09 0.146841E+09
November 71018516.32 0.00 71018516.32 27677806.78 0.306901E+09
December 68656180.07 0.00 68656180.07 7528341.98 0.442821E+09
           
Annual Sum or Average 0.130001E+10 49974404.39 0.125003E+10 0.214500E+10 0.216444E+10
Minimum of Months 68656180.07 0.00 68656180.07 7528341.98 9569400.25
Maximum of Months 0.156121E+09 19454349.17 0.140524E+09 0.415444E+09 0.442821E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 61906396.97 0.00 61906396.97 9684698.02 0.357420E+09
February 68278705.09 0.00 68278705.09 31076750.21 0.276267E+09
March 98949165.36 3917.06 98945248.31 76628339.55 0.243207E+09
April 0.111195E+09 1416565.43 0.109779E+09 0.161177E+09 0.109048E+09
May 0.135730E+09 10002836.96 0.125727E+09 0.281137E+09 47250831.21
June 0.139682E+09 17405879.91 0.122276E+09 0.371700E+09 16027510.55
July 0.133348E+09 13079955.45 0.120268E+09 0.359204E+09 8561778.67
August 0.112780E+09 2683129.35 0.110097E+09 0.286319E+09 18441229.40
September 94953316.23 120004.81 94833311.42 0.201407E+09 58149703.71
October 81331550.52 0.00 81331550.52 0.109307E+09 0.131379E+09
November 63540535.64 0.00 63540535.64 24763438.60 0.274585E+09
December 61426944.44 0.00 61426944.44 6735636.09 0.396177E+09
           
Annual Sum or Average 0.116312E+10 44712288.96 0.111841E+10 0.191914E+10 0.193651E+10
Minimum of Months 61426944.44 0.00 61426944.44 6735636.09 8561778.67
Maximum of Months 0.139682E+09 17405879.91 0.125727E+09 0.371700E+09 0.396177E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.139608E+10 0.105785E+10 0.338233E+09 0.189247E+10 0.101771E+10
February 0.118639E+10 0.841376E+09 0.345013E+09 0.165235E+10 0.797446E+09
March 0.102754E+10 0.582153E+09 0.445390E+09 0.148205E+10 0.753030E+09
April 0.692896E+09 0.260104E+09 0.432792E+09 0.120518E+10 0.369040E+09
May 0.508093E+09 74512840.84 0.433581E+09 0.108929E+10 0.169469E+09
June 0.420571E+09 26462346.95 0.394108E+09 0.116174E+10 55003997.19
July 0.441336E+09 39128663.92 0.402208E+09 0.120752E+10 29674140.16
August 0.557114E+09 0.141544E+09 0.415570E+09 0.135387E+10 63374026.53
September 0.853795E+09 0.443586E+09 0.410209E+09 0.173228E+10 0.190008E+09
October 0.121103E+10 0.822779E+09 0.388248E+09 0.202195E+10 0.409899E+09
November 0.141053E+10 0.107890E+10 0.331632E+09 0.203341E+10 0.788431E+09
December 0.143326E+10 0.107678E+10 0.356475E+09 0.191144E+10 0.110152E+10
           
Annual Sum or Average 0.111386E+11 0.644518E+10 0.469346E+10 0.187435E+11 0.574461E+10
Minimum of Months 0.420571E+09 26462346.95 0.331632E+09 0.108929E+10 29674140.16
Maximum of Months 0.143326E+10 0.107890E+10 0.445390E+09 0.203341E+10 0.110152E+10



Table of Contents

Report: WindowZoneSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 966.31 488.35 706.15 535.07 171.08 0.00 0.00
February 931.83 426.84 664.38 471.17 193.21 0.00 0.00
March 759.87 366.80 519.74 294.46 225.28 0.00 0.00
April 624.30 193.52 362.15 135.95 226.20 0.00 0.00
May 529.28 91.56 257.00 37.69 219.31 0.00 0.00
June 578.17 31.64 219.82 13.83 205.99 0.00 0.00
July 587.73 16.67 223.23 19.79 203.44 0.00 0.00
August 662.86 35.29 281.79 71.59 210.20 0.00 0.00
September 885.96 106.12 446.25 231.85 214.40 0.00 0.00
October 1011.44 209.50 612.55 416.17 196.38 0.00 0.00
November 1059.97 399.52 737.24 563.91 173.33 0.00 0.00
December 971.49 531.20 724.95 544.65 180.31 0.00 0.00
               
Annual Sum or Average 796.44 240.54 478.50 276.88 201.63 0.00 0.00
Minimum of Months 529.28 16.67 219.82 13.83 171.08 0.00 0.00
Maximum of Months 1059.97 531.20 737.24 563.91 226.20 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 2704.81 1387.38 1988.48 1506.73 481.75 0.00 0.00
February 2607.58 1212.38 1870.85 1326.79 544.06 0.00 0.00
March 2123.50 1041.07 1463.55 829.18 634.37 0.00 0.00
April 1744.59 557.35 1019.80 382.82 636.98 0.00 0.00
May 1474.27 272.00 723.68 106.13 617.55 0.00 0.00
June 1609.26 101.92 618.99 38.95 580.04 0.00 0.00
July 1634.91 58.32 628.60 55.73 572.87 0.00 0.00
August 1852.27 115.73 793.51 201.60 591.90 0.00 0.00
September 2491.96 314.76 1256.61 652.87 603.74 0.00 0.00
October 2840.22 605.20 1724.89 1171.91 552.99 0.00 0.00
November 2971.59 1135.58 2076.02 1587.93 488.09 0.00 0.00
December 2716.87 1506.63 2041.42 1533.69 507.73 0.00 0.00
               
Annual Sum or Average 2228.18 689.89 1347.44 779.68 567.76 0.00 0.00
Minimum of Months 1474.27 58.32 618.99 38.95 481.75 0.00 0.00
Maximum of Months 2971.59 1506.63 2076.02 1587.93 636.98 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 3583.68 1839.21 2583.15 1957.32 625.82 0.00 0.00
February 3461.38 1605.98 2430.34 1723.58 706.76 0.00 0.00
March 2821.64 1385.91 1901.24 1077.15 824.09 0.00 0.00
April 2331.15 742.00 1324.78 497.31 827.47 0.00 0.00
May 1977.06 364.15 940.11 137.87 802.24 0.00 0.00
June 2164.92 134.32 804.10 50.59 753.51 0.00 0.00
July 2197.35 75.81 816.59 72.40 744.19 0.00 0.00
August 2487.83 149.09 1030.81 261.90 768.91 0.00 0.00
September 3337.86 406.25 1632.41 848.12 784.29 0.00 0.00
October 3793.06 787.66 2240.73 1522.37 718.36 0.00 0.00
November 3951.91 1496.97 2696.87 2062.81 634.06 0.00 0.00
December 3595.64 2000.72 2651.92 1992.35 659.58 0.00 0.00
               
Annual Sum or Average 2971.61 912.42 1750.40 1012.84 737.56 0.00 0.00
Minimum of Months 1977.06 75.81 804.10 50.59 625.82 0.00 0.00
Maximum of Months 3951.91 2000.72 2696.87 2062.81 827.47 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 290.34 290.06 247.02 166.33 80.69 0.00 0.00
February 311.83 255.71 252.26 157.31 94.95 0.00 0.00
March 356.39 217.67 267.73 146.67 121.05 0.00 0.00
April 414.31 112.83 260.91 128.99 131.92 0.00 0.00
May 464.33 53.16 255.11 116.78 138.32 0.00 0.00
June 522.61 18.44 242.25 109.47 132.78 0.00 0.00
July 483.75 9.96 220.68 91.63 129.05 0.00 0.00
August 469.31 20.58 226.65 101.24 125.41 0.00 0.00
September 492.56 62.51 263.72 143.81 119.91 0.00 0.00
October 431.38 124.68 272.32 170.80 101.51 0.00 0.00
November 353.23 238.59 271.93 188.26 83.67 0.00 0.00
December 277.09 315.79 245.09 162.93 82.16 0.00 0.00
               
Annual Sum or Average 405.93 142.79 252.05 140.19 111.87 0.00 0.00
Minimum of Months 277.09 9.96 220.68 91.63 80.69 0.00 0.00
Maximum of Months 522.61 315.79 272.32 188.26 138.32 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 121.86 305.03 127.80 60.54 67.26 0.00 0.00
February 155.68 267.66 145.81 64.15 81.66 0.00 0.00
March 241.90 220.55 197.57 88.46 109.11 0.00 0.00
April 348.04 110.80 227.17 102.60 124.57 0.00 0.00
May 448.18 50.95 249.02 112.63 136.39 0.00 0.00
June 528.75 17.94 246.35 112.66 133.68 0.00 0.00
July 481.34 9.67 220.48 92.03 128.45 0.00 0.00
August 429.54 19.91 208.10 87.97 120.13 0.00 0.00
September 385.88 61.36 207.82 98.01 109.81 0.00 0.00
October 273.22 125.14 178.00 88.52 89.48 0.00 0.00
November 167.52 249.84 147.80 76.76 71.03 0.00 0.00
December 107.55 336.34 121.99 55.25 66.75 0.00 0.00
               
Annual Sum or Average 308.15 147.37 190.00 86.70 103.30 0.00 0.00
Minimum of Months 107.55 9.67 121.99 55.25 66.75 0.00 0.00
Maximum of Months 528.75 336.34 249.02 112.66 136.39 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 146.49 90.53 111.67 84.62 27.06 0.00 0.00
February 140.85 80.39 105.07 74.51 30.55 0.00 0.00
March 112.69 69.56 82.19 46.57 35.63 0.00 0.00
April 92.09 39.61 57.27 21.50 35.77 0.00 0.00
May 77.25 20.47 40.64 5.96 34.68 0.00 0.00
June 85.74 8.32 34.76 2.19 32.58 0.00 0.00
July 86.17 5.84 35.30 3.13 32.17 0.00 0.00
August 98.52 9.88 44.56 11.32 33.24 0.00 0.00
September 135.45 23.59 70.57 36.67 33.91 0.00 0.00
October 154.43 42.97 96.87 65.81 31.06 0.00 0.00
November 162.15 74.95 116.59 89.18 27.41 0.00 0.00
December 148.10 95.80 114.65 86.13 28.51 0.00 0.00
               
Annual Sum or Average 119.83 46.66 75.67 43.79 31.89 0.00 0.00
Minimum of Months 77.25 5.84 34.76 2.19 27.06 0.00 0.00
Maximum of Months 162.15 95.80 116.59 89.18 35.77 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 3.19 92.12 16.32 0.00 16.32 0.00 0.00
February 9.75 79.56 19.93 0.00 19.93 0.00 0.00
March 20.52 64.10 26.09 0.00 26.09 0.00 0.00
April 42.81 30.27 30.29 0.39 29.91 0.00 0.00
May 71.80 12.97 35.78 2.64 33.15 0.00 0.00
June 100.35 4.30 38.05 4.74 33.31 0.00 0.00
July 93.80 2.20 35.16 3.45 31.71 0.00 0.00
August 74.60 4.84 29.73 0.71 29.03 0.00 0.00
September 54.20 15.96 25.87 0.03 25.84 0.00 0.00
October 28.85 34.85 21.44 0.00 21.44 0.00 0.00
November 7.49 73.85 17.31 0.00 17.31 0.00 0.00
December 2.18 101.99 16.19 0.00 16.19 0.00 0.00
               
Annual Sum or Average 42.64 42.92 26.04 1.00 25.04 0.00 0.00
Minimum of Months 2.18 2.20 16.19 0.00 16.19 0.00 0.00
Maximum of Months 100.35 101.99 38.05 4.74 33.31 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 276.76 284.69 241.32 160.90 80.42 0.00 0.00
February 329.19 248.38 267.86 170.99 96.87 0.00 0.00
March 349.94 205.33 271.01 150.86 120.15 0.00 0.00
April 425.54 102.66 274.43 139.37 135.06 0.00 0.00
May 468.05 48.24 259.90 121.04 138.86 0.00 0.00
June 539.06 17.18 252.63 119.04 133.59 0.00 0.00
July 502.08 9.53 231.84 102.05 129.80 0.00 0.00
August 482.34 19.35 234.52 105.72 128.80 0.00 0.00
September 489.94 57.58 265.63 147.14 118.49 0.00 0.00
October 399.54 119.80 256.89 155.42 101.47 0.00 0.00
November 337.52 231.52 267.34 182.11 85.23 0.00 0.00
December 271.62 309.38 245.12 161.62 83.50 0.00 0.00
               
Annual Sum or Average 406.14 137.28 255.51 142.75 112.76 0.00 0.00
Minimum of Months 271.62 9.53 231.84 102.05 80.42 0.00 0.00
Maximum of Months 539.06 309.38 274.43 182.11 138.86 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 96.22 287.20 122.10 55.11 66.99 0.00 0.00
February 161.11 248.18 161.41 77.83 83.58 0.00 0.00
March 230.31 203.43 200.85 92.64 108.21 0.00 0.00
April 359.17 101.22 240.68 112.98 127.71 0.00 0.00
May 453.64 47.97 253.81 116.88 136.93 0.00 0.00
June 545.91 17.23 256.73 122.24 134.50 0.00 0.00
July 499.94 9.42 231.64 102.44 129.20 0.00 0.00
August 442.81 19.06 215.97 92.45 123.52 0.00 0.00
September 382.46 56.19 209.73 101.34 108.39 0.00 0.00
October 237.40 117.00 162.58 73.14 89.44 0.00 0.00
November 141.67 231.36 143.21 70.62 72.60 0.00 0.00
December 87.73 315.49 122.02 53.93 68.09 0.00 0.00
               
Annual Sum or Average 303.77 137.30 193.45 89.26 104.19 0.00 0.00
Minimum of Months 87.73 9.42 122.02 53.93 66.99 0.00 0.00
Maximum of Months 545.91 315.49 256.73 122.24 136.93 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 317.97 356.90 277.32 183.34 93.98 0.00 0.00
February 328.00 310.71 270.83 161.45 109.38 0.00 0.00
March 303.71 263.38 234.60 100.90 133.70 0.00 0.00
April 318.15 129.82 189.72 47.42 142.30 0.00 0.00
May 351.50 57.91 165.58 18.63 146.95 0.00 0.00
June 427.65 21.35 157.76 15.01 142.75 0.00 0.00
July 416.45 11.22 152.65 14.25 138.40 0.00 0.00
August 400.25 23.51 160.97 26.06 134.90 0.00 0.00
September 433.10 72.33 208.95 79.51 129.43 0.00 0.00
October 417.62 144.18 256.34 142.60 113.74 0.00 0.00
November 370.72 287.23 290.12 193.22 96.89 0.00 0.00
December 311.75 388.61 283.49 186.62 96.87 0.00 0.00
               
Annual Sum or Average 366.49 171.61 220.38 97.04 123.34 0.00 0.00
Minimum of Months 303.71 11.22 152.65 14.25 93.98 0.00 0.00
Maximum of Months 433.10 388.61 290.12 193.22 146.95 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 288.77 286.86 247.02 166.33 80.69 0.00 0.00
February 309.24 253.10 252.26 157.31 94.95 0.00 0.00
March 351.81 215.76 267.73 146.67 121.05 0.00 0.00
April 408.06 112.08 260.91 128.99 131.92 0.00 0.00
May 457.88 52.58 255.11 116.78 138.32 0.00 0.00
June 516.70 18.26 242.25 109.47 132.78 0.00 0.00
July 477.14 10.04 220.68 91.63 129.05 0.00 0.00
August 462.89 20.62 226.65 101.24 125.41 0.00 0.00
September 486.15 62.38 263.72 143.81 119.91 0.00 0.00
October 426.23 124.29 272.32 170.80 101.51 0.00 0.00
November 350.41 236.29 271.93 188.26 83.67 0.00 0.00
December 276.79 311.65 245.09 162.93 82.16 0.00 0.00
               
Annual Sum or Average 401.33 141.46 252.05 140.19 111.87 0.00 0.00
Minimum of Months 276.79 10.04 220.68 91.63 80.69 0.00 0.00
Maximum of Months 516.70 311.65 272.32 188.26 138.32 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 121.93 300.84 127.80 60.54 67.26 0.00 0.00
February 154.73 264.17 145.81 64.15 81.66 0.00 0.00
March 238.92 218.23 197.57 88.46 109.11 0.00 0.00
April 342.47 110.04 227.17 102.60 124.57 0.00 0.00
May 441.82 50.43 249.02 112.63 136.39 0.00 0.00
June 522.59 17.80 246.35 112.66 133.68 0.00 0.00
July 474.65 9.77 220.48 92.03 128.45 0.00 0.00
August 423.44 19.96 208.10 87.97 120.13 0.00 0.00
September 380.25 61.17 207.82 98.01 109.81 0.00 0.00
October 269.24 124.39 178.00 88.52 89.48 0.00 0.00
November 166.29 246.52 147.80 76.76 71.03 0.00 0.00
December 108.29 331.13 121.99 55.25 66.75 0.00 0.00
               
Annual Sum or Average 304.40 145.64 190.00 86.70 103.30 0.00 0.00
Minimum of Months 108.29 9.77 121.99 55.25 66.75 0.00 0.00
Maximum of Months 522.59 331.13 249.02 112.66 136.39 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 268.88 151.08 204.76 155.16 49.61 0.00 0.00
February 259.24 131.84 192.65 136.63 56.02 0.00 0.00
March 208.97 112.06 150.71 85.38 65.33 0.00 0.00
April 173.42 57.45 105.01 39.42 65.59 0.00 0.00
May 150.44 25.74 74.52 10.93 63.59 0.00 0.00
June 169.60 8.35 63.74 4.01 59.73 0.00 0.00
July 170.03 4.52 64.73 5.74 58.99 0.00 0.00
August 190.26 9.84 81.71 20.76 60.95 0.00 0.00
September 252.26 30.80 129.40 67.23 62.17 0.00 0.00
October 286.04 63.51 177.62 120.68 56.94 0.00 0.00
November 298.39 122.48 213.78 163.52 50.26 0.00 0.00
December 271.78 163.29 210.22 157.93 52.28 0.00 0.00
               
Annual Sum or Average 224.68 73.14 138.75 80.29 58.47 0.00 0.00
Minimum of Months 150.44 4.52 63.74 4.01 49.61 0.00 0.00
Maximum of Months 298.39 163.29 213.78 163.52 65.59 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 22.01 833.95 142.78 0.00 142.78 0.00 0.00
February 78.75 719.40 174.35 0.00 174.35 0.00 0.00
March 172.70 582.26 228.22 0.01 228.21 0.00 0.00
April 376.51 287.99 265.01 3.38 261.64 0.00 0.00
May 630.36 135.37 313.05 23.07 289.98 0.00 0.00
June 869.43 54.64 332.91 41.48 291.42 0.00 0.00
July 810.61 33.78 307.56 30.17 277.39 0.00 0.00
August 648.77 61.88 260.12 6.19 253.93 0.00 0.00
September 480.93 161.47 226.30 0.29 226.02 0.00 0.00
October 251.87 326.31 187.59 0.00 187.59 0.00 0.00
November 59.23 667.75 151.44 0.00 151.44 0.00 0.00
December 15.24 918.11 141.68 0.00 141.68 0.00 0.00
               
Annual Sum or Average 369.55 397.10 227.84 8.76 219.09 0.00 0.00
Minimum of Months 15.24 33.78 141.68 0.00 141.68 0.00 0.00
Maximum of Months 869.43 918.11 332.91 41.48 291.42 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 19.89 850.73 142.78 0.00 142.78 0.00 0.00
February 75.05 735.06 174.35 0.00 174.35 0.00 0.00
March 166.72 596.59 228.22 0.01 228.21 0.00 0.00
April 366.52 299.43 265.01 3.38 261.64 0.00 0.00
May 616.07 143.68 313.05 23.07 289.98 0.00 0.00
June 853.20 59.27 332.91 41.48 291.42 0.00 0.00
July 794.30 38.23 307.56 30.17 277.39 0.00 0.00
August 634.14 67.82 260.12 6.19 253.93 0.00 0.00
September 470.36 170.73 226.30 0.29 226.02 0.00 0.00
October 244.52 338.74 187.59 0.00 187.59 0.00 0.00
November 55.69 683.34 151.44 0.00 151.44 0.00 0.00
December 13.80 935.16 141.68 0.00 141.68 0.00 0.00
               
Annual Sum or Average 360.68 408.39 227.84 8.76 219.09 0.00 0.00
Minimum of Months 13.80 38.23 141.68 0.00 141.68 0.00 0.00
Maximum of Months 853.20 935.16 332.91 41.48 291.42 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 373.39 614.35 363.41 216.00 147.41 0.00 0.00
February 506.30 538.93 429.25 248.81 180.43 0.00 0.00
March 604.21 451.28 471.84 243.48 228.35 0.00 0.00
April 833.58 242.00 515.08 252.33 262.75 0.00 0.00
May 973.62 128.63 513.67 237.90 275.77 0.00 0.00
June 1142.12 52.89 509.34 241.26 268.07 0.00 0.00
July 1060.72 37.46 463.46 204.47 258.98 0.00 0.00
August 987.64 61.88 450.46 198.15 252.31 0.00 0.00
September 947.04 137.90 475.33 248.47 226.86 0.00 0.00
October 680.67 270.39 419.45 228.55 190.90 0.00 0.00
November 497.82 501.16 410.54 252.72 157.82 0.00 0.00
December 360.86 657.91 367.13 215.55 151.58 0.00 0.00
               
Annual Sum or Average 748.13 306.81 448.93 231.99 216.94 0.00 0.00
Minimum of Months 360.86 37.46 363.41 198.15 147.41 0.00 0.00
Maximum of Months 1142.12 657.91 515.08 252.72 275.77 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 682.86 631.20 570.18 394.96 175.23 0.00 0.00
February 687.85 549.10 550.17 347.79 202.38 0.00 0.00
March 607.20 466.72 461.88 217.35 244.52 0.00 0.00
April 595.96 230.79 358.17 101.51 256.66 0.00 0.00
May 627.46 99.11 297.02 35.73 261.29 0.00 0.00
June 751.33 33.76 276.38 24.43 251.95 0.00 0.00
July 734.45 17.46 270.21 24.95 245.26 0.00 0.00
August 731.58 37.97 297.17 54.97 242.20 0.00 0.00
September 832.55 120.50 406.97 171.23 235.74 0.00 0.00
October 838.00 253.58 516.45 307.19 209.26 0.00 0.00
November 783.25 507.04 596.10 416.24 179.86 0.00 0.00
December 678.22 683.75 583.68 402.02 181.66 0.00 0.00
               
Annual Sum or Average 712.45 301.43 431.31 207.38 223.93 0.00 0.00
Minimum of Months 595.96 17.46 270.21 24.43 175.23 0.00 0.00
Maximum of Months 838.00 683.75 596.10 416.24 261.29 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.258816E+10 0.130800E+10 0.189136E+10 0.143314E+10 0.458222E+09 0.00 0.00
February 0.225428E+10 0.103261E+10 0.160727E+10 0.113986E+10 0.467406E+09 0.00 0.00
March 0.203523E+10 0.982449E+09 0.139207E+10 0.788679E+09 0.603391E+09 0.00 0.00
April 0.161818E+10 0.501597E+09 0.938702E+09 0.352379E+09 0.586322E+09 0.00 0.00
May 0.141762E+10 0.245247E+09 0.688337E+09 0.100947E+09 0.587390E+09 0.00 0.00
June 0.149862E+10 82013881.80 0.569764E+09 35850177.24 0.533914E+09 0.00 0.00
July 0.157418E+10 44653482.94 0.597898E+09 53010019.83 0.544888E+09 0.00 0.00
August 0.177540E+10 94511521.45 0.754750E+09 0.191758E+09 0.562992E+09 0.00 0.00
September 0.229640E+10 0.275052E+09 0.115668E+10 0.600953E+09 0.555729E+09 0.00 0.00
October 0.270903E+10 0.561119E+09 0.164065E+10 0.111467E+10 0.525978E+09 0.00 0.00
November 0.274745E+10 0.103556E+10 0.191093E+10 0.146165E+10 0.449279E+09 0.00 0.00
December 0.260205E+10 0.142276E+10 0.194172E+10 0.145878E+10 0.482936E+09 0.00 0.00
               
Annual Sum or Average 0.251166E+11 0.758558E+10 0.150901E+11 0.873168E+10 0.635845E+10 0.00 0.00
Minimum of Months 0.141762E+10 44653482.94 0.569764E+09 35850177.24 0.449279E+09 0.00 0.00
Maximum of Months 0.274745E+10 0.142276E+10 0.194172E+10 0.146165E+10 0.603391E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.724458E+10 0.371595E+10 0.532594E+10 0.403562E+10 0.129032E+10 0.00 0.00
February 0.630826E+10 0.293298E+10 0.452597E+10 0.320978E+10 0.131618E+10 0.00 0.00
March 0.568757E+10 0.278840E+10 0.391998E+10 0.222087E+10 0.169911E+10 0.00 0.00
April 0.452198E+10 0.144465E+10 0.264332E+10 0.992277E+09 0.165105E+10 0.00 0.00
May 0.394869E+10 0.728519E+09 0.193831E+10 0.284261E+09 0.165405E+10 0.00 0.00
June 0.417120E+10 0.264166E+09 0.160442E+10 0.100952E+09 0.150347E+10 0.00 0.00
July 0.437894E+10 0.156202E+09 0.168364E+10 0.149273E+09 0.153437E+10 0.00 0.00
August 0.496111E+10 0.309958E+09 0.212533E+10 0.539978E+09 0.158535E+10 0.00 0.00
September 0.645915E+10 0.815853E+09 0.325714E+10 0.169224E+10 0.156490E+10 0.00 0.00
October 0.760725E+10 0.162097E+10 0.461996E+10 0.313884E+10 0.148112E+10 0.00 0.00
November 0.770236E+10 0.294343E+10 0.538106E+10 0.411592E+10 0.126514E+10 0.00 0.00
December 0.727685E+10 0.403535E+10 0.546774E+10 0.410783E+10 0.135992E+10 0.00 0.00
               
Annual Sum or Average 0.702679E+11 0.217564E+11 0.424928E+11 0.245878E+11 0.179050E+11 0.00 0.00
Minimum of Months 0.394869E+10 0.156202E+09 0.160442E+10 0.100952E+09 0.126514E+10 0.00 0.00
Maximum of Months 0.770236E+10 0.403535E+10 0.546774E+10 0.411592E+10 0.169911E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.959853E+10 0.492615E+10 0.691870E+10 0.524250E+10 0.167620E+10 0.00 0.00
February 0.837378E+10 0.388520E+10 0.587949E+10 0.416969E+10 0.170980E+10 0.00 0.00
March 0.755747E+10 0.371203E+10 0.509227E+10 0.288503E+10 0.220724E+10 0.00 0.00
April 0.604235E+10 0.192327E+10 0.343383E+10 0.128902E+10 0.214480E+10 0.00 0.00
May 0.529535E+10 0.975347E+09 0.251798E+10 0.369271E+09 0.214871E+10 0.00 0.00
June 0.561147E+10 0.348151E+09 0.208423E+10 0.131142E+09 0.195309E+10 0.00 0.00
July 0.588539E+10 0.203047E+09 0.218715E+10 0.193914E+09 0.199323E+10 0.00 0.00
August 0.666340E+10 0.399334E+09 0.276092E+10 0.701462E+09 0.205946E+10 0.00 0.00
September 0.865174E+10 0.105299E+10 0.423121E+10 0.219832E+10 0.203289E+10 0.00 0.00
October 0.101593E+11 0.210967E+10 0.600158E+10 0.407753E+10 0.192406E+10 0.00 0.00
November 0.102434E+11 0.388016E+10 0.699030E+10 0.534681E+10 0.164349E+10 0.00 0.00
December 0.963056E+10 0.535873E+10 0.710291E+10 0.533630E+10 0.176661E+10 0.00 0.00
               
Annual Sum or Average 0.937127E+11 0.287741E+11 0.552006E+11 0.319410E+11 0.232596E+11 0.00 0.00
Minimum of Months 0.529535E+10 0.203047E+09 0.208423E+10 0.131142E+09 0.164349E+10 0.00 0.00
Maximum of Months 0.102434E+11 0.535873E+10 0.710291E+10 0.534681E+10 0.220724E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.777656E+09 0.776900E+09 0.661628E+09 0.445502E+09 0.216126E+09 0.00 0.00
February 0.754379E+09 0.618611E+09 0.610259E+09 0.380562E+09 0.229697E+09 0.00 0.00
March 0.954559E+09 0.583008E+09 0.717083E+09 0.392853E+09 0.324229E+09 0.00 0.00
April 0.107389E+10 0.292456E+09 0.676285E+09 0.334351E+09 0.341935E+09 0.00 0.00
May 0.124367E+10 0.142373E+09 0.683278E+09 0.312791E+09 0.370487E+09 0.00 0.00
June 0.135460E+10 47804370.03 0.627908E+09 0.283748E+09 0.344161E+09 0.00 0.00
July 0.129567E+10 26676857.38 0.591061E+09 0.245426E+09 0.345635E+09 0.00 0.00
August 0.125700E+10 55119578.42 0.607067E+09 0.271168E+09 0.335899E+09 0.00 0.00
September 0.127672E+10 0.162033E+09 0.683569E+09 0.372750E+09 0.310819E+09 0.00 0.00
October 0.115540E+10 0.333952E+09 0.729374E+09 0.457483E+09 0.271891E+09 0.00 0.00
November 0.915579E+09 0.618423E+09 0.704840E+09 0.487965E+09 0.216875E+09 0.00 0.00
December 0.742150E+09 0.845817E+09 0.656450E+09 0.436397E+09 0.220053E+09 0.00 0.00
               
Annual Sum or Average 0.128013E+11 0.450317E+10 0.794880E+10 0.442100E+10 0.352781E+10 0.00 0.00
Minimum of Months 0.742150E+09 26676857.38 0.591061E+09 0.245426E+09 0.216126E+09 0.00 0.00
Maximum of Months 0.135460E+10 0.845817E+09 0.729374E+09 0.487965E+09 0.370487E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.326400E+09 0.816994E+09 0.342309E+09 0.162146E+09 0.180162E+09 0.00 0.00
February 0.376631E+09 0.647534E+09 0.352733E+09 0.155192E+09 0.197541E+09 0.00 0.00
March 0.647905E+09 0.590722E+09 0.529172E+09 0.236921E+09 0.292251E+09 0.00 0.00
April 0.902129E+09 0.287199E+09 0.588821E+09 0.265930E+09 0.322892E+09 0.00 0.00
May 0.120040E+10 0.136474E+09 0.666968E+09 0.301660E+09 0.365308E+09 0.00 0.00
June 0.137052E+10 46503904.38 0.638530E+09 0.292021E+09 0.346509E+09 0.00 0.00
July 0.128922E+10 25909399.17 0.590530E+09 0.246488E+09 0.344041E+09 0.00 0.00
August 0.115049E+10 53322181.28 0.557372E+09 0.235622E+09 0.321750E+09 0.00 0.00
September 0.100020E+10 0.159038E+09 0.538673E+09 0.254037E+09 0.284635E+09 0.00 0.00
October 0.731800E+09 0.335173E+09 0.476768E+09 0.237094E+09 0.239674E+09 0.00 0.00
November 0.434199E+09 0.647597E+09 0.383093E+09 0.198972E+09 0.184121E+09 0.00 0.00
December 0.288057E+09 0.900841E+09 0.326751E+09 0.147971E+09 0.178780E+09 0.00 0.00
               
Annual Sum or Average 0.971794E+10 0.464731E+10 0.599172E+10 0.273405E+10 0.325767E+10 0.00 0.00
Minimum of Months 0.288057E+09 25909399.17 0.326751E+09 0.147971E+09 0.178780E+09 0.00 0.00
Maximum of Months 0.137052E+10 0.900841E+09 0.666968E+09 0.301660E+09 0.365308E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.392345E+09 0.242469E+09 0.299104E+09 0.226640E+09 72464826.42 0.00 0.00
February 0.340752E+09 0.194475E+09 0.254178E+09 0.180261E+09 73917324.87 0.00 0.00
March 0.301824E+09 0.186310E+09 0.220146E+09 0.124724E+09 95422629.83 0.00 0.00
April 0.238688E+09 0.102672E+09 0.148450E+09 55726088.50 92723544.22 0.00 0.00
May 0.206902E+09 54827301.07 0.108857E+09 15964013.69 92892545.85 0.00 0.00
June 0.222227E+09 21556791.11 90105188.78 5669429.11 84435759.67 0.00 0.00
July 0.230796E+09 15651122.90 94554156.30 8383125.91 86171030.39 0.00 0.00
August 0.263875E+09 26472808.71 0.119359E+09 30325060.49 89033931.16 0.00 0.00
September 0.351092E+09 61150568.20 0.182921E+09 95036114.58 87885276.20 0.00 0.00
October 0.413633E+09 0.115086E+09 0.259457E+09 0.176276E+09 83180150.54 0.00 0.00
November 0.420291E+09 0.194276E+09 0.302200E+09 0.231149E+09 71050625.13 0.00 0.00
December 0.396671E+09 0.256603E+09 0.307068E+09 0.230695E+09 76373138.43 0.00 0.00
               
Annual Sum or Average 0.377909E+10 0.147155E+10 0.238640E+10 0.138085E+10 0.100555E+10 0.00 0.00
Minimum of Months 0.206902E+09 15651122.90 90105188.78 5669429.11 71050625.13 0.00 0.00
Maximum of Months 0.420291E+09 0.256603E+09 0.307068E+09 0.231149E+09 95422629.83 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 8540331.93 0.246730E+09 43713969.60 0.00 43713969.60 0.00 0.00
February 23580161.30 0.192480E+09 48213648.10 0.00 48213648.10 0.00 0.00
March 54959432.08 0.171676E+09 69870982.94 2765.95 69868216.99 0.00 0.00
April 0.110964E+09 78461667.44 78518344.10 1000279.47 77518064.63 0.00 0.00
May 0.192312E+09 34732635.61 95843144.60 7063304.15 88779840.45 0.00 0.00
June 0.260101E+09 11158549.39 98633813.54 12290815.53 86342998.01 0.00 0.00
July 0.251240E+09 5897204.96 94160895.41 9236150.10 84924745.31 0.00 0.00
August 0.199808E+09 12967140.09 79637162.39 1894638.37 77742524.03 0.00 0.00
September 0.140499E+09 41355941.49 67049393.63 84739.01 66964654.62 0.00 0.00
October 77280343.79 93349095.14 57430655.00 0.00 57430655.00 0.00 0.00
November 19424185.98 0.191420E+09 44867884.08 0.00 44867884.08 0.00 0.00
December 5836933.57 0.273183E+09 43375413.74 0.00 43375413.74 0.00 0.00
               
Annual Sum or Average 0.134455E+10 0.135341E+10 0.821315E+09 31572692.58 0.789743E+09 0.00 0.00
Minimum of Months 5836933.57 5897204.96 43375413.74 0.00 43375413.74 0.00 0.00
Maximum of Months 0.260101E+09 0.273183E+09 98633813.54 12290815.53 88779840.45 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.741281E+09 0.762511E+09 0.646361E+09 0.430960E+09 0.215402E+09 0.00 0.00
February 0.796386E+09 0.600872E+09 0.648005E+09 0.413664E+09 0.234341E+09 0.00 0.00
March 0.937278E+09 0.549960E+09 0.725871E+09 0.404058E+09 0.321813E+09 0.00 0.00
April 0.110299E+10 0.266096E+09 0.711319E+09 0.361253E+09 0.350066E+09 0.00 0.00
May 0.125361E+10 0.129211E+09 0.696105E+09 0.324180E+09 0.371925E+09 0.00 0.00
June 0.139725E+10 44522584.02 0.654827E+09 0.308561E+09 0.346266E+09 0.00 0.00
July 0.134478E+10 25523471.83 0.620963E+09 0.273320E+09 0.347643E+09 0.00 0.00
August 0.129190E+10 51822824.60 0.628139E+09 0.283153E+09 0.344986E+09 0.00 0.00
September 0.126993E+10 0.149255E+09 0.688511E+09 0.381390E+09 0.307121E+09 0.00 0.00
October 0.107012E+10 0.320885E+09 0.688060E+09 0.416283E+09 0.271777E+09 0.00 0.00
November 0.874857E+09 0.600100E+09 0.692953E+09 0.472029E+09 0.220924E+09 0.00 0.00
December 0.727509E+09 0.828653E+09 0.656523E+09 0.432885E+09 0.223638E+09 0.00 0.00
               
Annual Sum or Average 0.128079E+11 0.432941E+10 0.805764E+10 0.450174E+10 0.355590E+10 0.00 0.00
Minimum of Months 0.727509E+09 25523471.83 0.620963E+09 0.273320E+09 0.215402E+09 0.00 0.00
Maximum of Months 0.139725E+10 0.828653E+09 0.725871E+09 0.472029E+09 0.371925E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.257721E+09 0.769225E+09 0.327041E+09 0.147604E+09 0.179438E+09 0.00 0.00
February 0.389757E+09 0.600408E+09 0.390478E+09 0.188293E+09 0.202185E+09 0.00 0.00
March 0.616863E+09 0.544867E+09 0.537961E+09 0.248126E+09 0.289835E+09 0.00 0.00
April 0.930979E+09 0.262371E+09 0.623855E+09 0.292832E+09 0.331023E+09 0.00 0.00
May 0.121503E+10 0.128475E+09 0.679796E+09 0.313049E+09 0.366746E+09 0.00 0.00
June 0.141501E+10 44665985.22 0.665449E+09 0.316834E+09 0.348614E+09 0.00 0.00
July 0.133904E+10 25240192.30 0.620433E+09 0.274383E+09 0.346050E+09 0.00 0.00
August 0.118602E+10 51040455.05 0.578444E+09 0.247607E+09 0.330837E+09 0.00 0.00
September 0.991337E+09 0.145635E+09 0.543615E+09 0.262677E+09 0.280938E+09 0.00 0.00
October 0.635857E+09 0.313370E+09 0.435454E+09 0.195894E+09 0.239560E+09 0.00 0.00
November 0.367207E+09 0.599679E+09 0.371206E+09 0.183035E+09 0.188171E+09 0.00 0.00
December 0.234966E+09 0.845007E+09 0.326824E+09 0.144459E+09 0.182365E+09 0.00 0.00
               
Annual Sum or Average 0.957979E+10 0.432998E+10 0.610055E+10 0.281479E+10 0.328576E+10 0.00 0.00
Minimum of Months 0.234966E+09 25240192.30 0.326824E+09 0.144459E+09 0.179438E+09 0.00 0.00
Maximum of Months 0.141501E+10 0.845007E+09 0.679796E+09 0.316834E+09 0.366746E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.851641E+09 0.955933E+09 0.742775E+09 0.491065E+09 0.251710E+09 0.00 0.00
February 0.793493E+09 0.751664E+09 0.655180E+09 0.390575E+09 0.264605E+09 0.00 0.00
March 0.813455E+09 0.705424E+09 0.628360E+09 0.270247E+09 0.358112E+09 0.00 0.00
April 0.824638E+09 0.336492E+09 0.491746E+09 0.122910E+09 0.368836E+09 0.00 0.00
May 0.941448E+09 0.155105E+09 0.443490E+09 49891063.49 0.393599E+09 0.00 0.00
June 0.110847E+10 55338327.15 0.408907E+09 38910104.08 0.369997E+09 0.00 0.00
July 0.111542E+10 30060320.72 0.408857E+09 38172500.78 0.370684E+09 0.00 0.00
August 0.107203E+10 62971833.76 0.431139E+09 69810394.97 0.361328E+09 0.00 0.00
September 0.112261E+10 0.187482E+09 0.541591E+09 0.206100E+09 0.335491E+09 0.00 0.00
October 0.111856E+10 0.386175E+09 0.686584E+09 0.381942E+09 0.304642E+09 0.00 0.00
November 0.960907E+09 0.744491E+09 0.751982E+09 0.500836E+09 0.251146E+09 0.00 0.00
December 0.834998E+09 0.104085E+10 0.759297E+09 0.499852E+09 0.259445E+09 0.00 0.00
               
Annual Sum or Average 0.115577E+11 0.541199E+10 0.694991E+10 0.306031E+10 0.388960E+10 0.00 0.00
Minimum of Months 0.793493E+09 30060320.72 0.408857E+09 38172500.78 0.251146E+09 0.00 0.00
Maximum of Months 0.112261E+10 0.104085E+10 0.759297E+09 0.500836E+09 0.393599E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.773455E+09 0.768323E+09 0.661628E+09 0.445502E+09 0.216126E+09 0.00 0.00
February 0.748102E+09 0.612308E+09 0.610259E+09 0.380562E+09 0.229697E+09 0.00 0.00
March 0.942279E+09 0.577886E+09 0.717083E+09 0.392853E+09 0.324229E+09 0.00 0.00
April 0.105768E+10 0.290513E+09 0.676285E+09 0.334351E+09 0.341935E+09 0.00 0.00
May 0.122638E+10 0.140842E+09 0.683278E+09 0.312791E+09 0.370487E+09 0.00 0.00
June 0.133929E+10 47323254.57 0.627908E+09 0.283748E+09 0.344161E+09 0.00 0.00
July 0.127798E+10 26890249.03 0.591061E+09 0.245426E+09 0.345635E+09 0.00 0.00
August 0.123981E+10 55241381.62 0.607067E+09 0.271168E+09 0.335899E+09 0.00 0.00
September 0.126010E+10 0.161695E+09 0.683569E+09 0.372750E+09 0.310819E+09 0.00 0.00
October 0.114160E+10 0.332899E+09 0.729374E+09 0.457483E+09 0.271891E+09 0.00 0.00
November 0.908258E+09 0.612459E+09 0.704840E+09 0.487965E+09 0.216875E+09 0.00 0.00
December 0.741351E+09 0.834727E+09 0.656450E+09 0.436397E+09 0.220053E+09 0.00 0.00
               
Annual Sum or Average 0.126563E+11 0.446111E+10 0.794880E+10 0.442100E+10 0.352781E+10 0.00 0.00
Minimum of Months 0.741351E+09 26890249.03 0.591061E+09 0.245426E+09 0.216126E+09 0.00 0.00
Maximum of Months 0.133929E+10 0.834727E+09 0.729374E+09 0.487965E+09 0.370487E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.326587E+09 0.805783E+09 0.342309E+09 0.162146E+09 0.180162E+09 0.00 0.00
February 0.374315E+09 0.639089E+09 0.352733E+09 0.155192E+09 0.197541E+09 0.00 0.00
March 0.639932E+09 0.584501E+09 0.529172E+09 0.236921E+09 0.292251E+09 0.00 0.00
April 0.887684E+09 0.285233E+09 0.588821E+09 0.265930E+09 0.322892E+09 0.00 0.00
May 0.118336E+10 0.135075E+09 0.666968E+09 0.301660E+09 0.365308E+09 0.00 0.00
June 0.135455E+10 46128656.68 0.638530E+09 0.292021E+09 0.346509E+09 0.00 0.00
July 0.127130E+10 26160011.87 0.590530E+09 0.246488E+09 0.344041E+09 0.00 0.00
August 0.113415E+10 53466799.00 0.557372E+09 0.235622E+09 0.321750E+09 0.00 0.00
September 0.985603E+09 0.158548E+09 0.538673E+09 0.254037E+09 0.284635E+09 0.00 0.00
October 0.721145E+09 0.333178E+09 0.476768E+09 0.237094E+09 0.239674E+09 0.00 0.00
November 0.431014E+09 0.638986E+09 0.383093E+09 0.198972E+09 0.184121E+09 0.00 0.00
December 0.290046E+09 0.886904E+09 0.326751E+09 0.147971E+09 0.178780E+09 0.00 0.00
               
Annual Sum or Average 0.959969E+10 0.459305E+10 0.599172E+10 0.273405E+10 0.325767E+10 0.00 0.00
Minimum of Months 0.290046E+09 26160011.87 0.326751E+09 0.147971E+09 0.178780E+09 0.00 0.00
Maximum of Months 0.135455E+10 0.886904E+09 0.666968E+09 0.301660E+09 0.365308E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.720156E+09 0.404646E+09 0.548441E+09 0.415568E+09 0.132872E+09 0.00 0.00
February 0.627146E+09 0.318940E+09 0.466063E+09 0.330528E+09 0.135536E+09 0.00 0.00
March 0.559695E+09 0.300140E+09 0.403662E+09 0.228694E+09 0.174968E+09 0.00 0.00
April 0.449515E+09 0.148917E+09 0.272199E+09 0.102180E+09 0.170019E+09 0.00 0.00
May 0.402926E+09 68947983.96 0.199600E+09 29271767.90 0.170329E+09 0.00 0.00
June 0.439594E+09 21655569.63 0.165218E+09 10395519.34 0.154822E+09 0.00 0.00
July 0.455420E+09 12116833.16 0.173375E+09 15371379.69 0.158004E+09 0.00 0.00
August 0.509593E+09 26349933.25 0.218858E+09 55604320.39 0.163253E+09 0.00 0.00
September 0.653871E+09 79835313.53 0.335406E+09 0.174259E+09 0.161147E+09 0.00 0.00
October 0.766136E+09 0.170114E+09 0.475742E+09 0.323222E+09 0.152520E+09 0.00 0.00
November 0.773419E+09 0.317477E+09 0.554116E+09 0.423837E+09 0.130279E+09 0.00 0.00
December 0.727935E+09 0.437361E+09 0.563043E+09 0.423004E+09 0.140039E+09 0.00 0.00
               
Annual Sum or Average 0.708540E+10 0.230650E+10 0.437572E+10 0.253194E+10 0.184379E+10 0.00 0.00
Minimum of Months 0.402926E+09 12116833.16 0.165218E+09 10395519.34 0.130279E+09 0.00 0.00
Maximum of Months 0.773419E+09 0.437361E+09 0.563043E+09 0.423837E+09 0.174968E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 58951849.05 0.223366E+10 0.382432E+09 0.00 0.382432E+09 0.00 0.00
February 0.190511E+09 0.174036E+10 0.421798E+09 0.00 0.421798E+09 0.00 0.00
March 0.462566E+09 0.155953E+10 0.611267E+09 24197.95 0.611243E+09 0.00 0.00
April 0.975923E+09 0.746464E+09 0.686918E+09 8750953.90 0.678167E+09 0.00 0.00
May 0.168836E+10 0.362580E+09 0.838485E+09 61793379.53 0.776691E+09 0.00 0.00
June 0.225356E+10 0.141621E+09 0.862899E+09 0.107526E+09 0.755372E+09 0.00 0.00
July 0.217115E+10 90480253.71 0.823767E+09 80802541.81 0.742965E+09 0.00 0.00
August 0.173765E+10 0.165738E+09 0.696706E+09 16575260.69 0.680131E+09 0.00 0.00
September 0.124658E+10 0.418525E+09 0.586582E+09 741339.97 0.585841E+09 0.00 0.00
October 0.674602E+09 0.873986E+09 0.502433E+09 0.00 0.502433E+09 0.00 0.00
November 0.153535E+09 0.173080E+10 0.392527E+09 0.00 0.392527E+09 0.00 0.00
December 40832122.20 0.245907E+10 0.379470E+09 0.00 0.379470E+09 0.00 0.00
               
Annual Sum or Average 0.116542E+11 0.125228E+11 0.718528E+10 0.276214E+09 0.690907E+10 0.00 0.00
Minimum of Months 40832122.20 90480253.71 0.379470E+09 0.00 0.379470E+09 0.00 0.00
Maximum of Months 0.225356E+10 0.245907E+10 0.862899E+09 0.107526E+09 0.776691E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 53267786.88 0.227861E+10 0.382432E+09 0.00 0.382432E+09 0.00 0.00
February 0.181553E+09 0.177825E+10 0.421798E+09 0.00 0.421798E+09 0.00 0.00
March 0.446543E+09 0.159791E+10 0.611267E+09 24197.95 0.611243E+09 0.00 0.00
April 0.950032E+09 0.776114E+09 0.686918E+09 8750953.90 0.678167E+09 0.00 0.00
May 0.165009E+10 0.384845E+09 0.838485E+09 61793379.53 0.776691E+09 0.00 0.00
June 0.221150E+10 0.153627E+09 0.862899E+09 0.107526E+09 0.755372E+09 0.00 0.00
July 0.212746E+10 0.102383E+09 0.823767E+09 80802541.81 0.742965E+09 0.00 0.00
August 0.169849E+10 0.181652E+09 0.696706E+09 16575260.69 0.680131E+09 0.00 0.00
September 0.121917E+10 0.442545E+09 0.586582E+09 741339.97 0.585841E+09 0.00 0.00
October 0.654921E+09 0.907268E+09 0.502433E+09 0.00 0.502433E+09 0.00 0.00
November 0.144338E+09 0.177121E+10 0.392527E+09 0.00 0.392527E+09 0.00 0.00
December 36967489.12 0.250473E+10 0.379470E+09 0.00 0.379470E+09 0.00 0.00
               
Annual Sum or Average 0.113743E+11 0.128791E+11 0.718528E+10 0.276214E+09 0.690907E+10 0.00 0.00
Minimum of Months 36967489.12 0.102383E+09 0.379470E+09 0.00 0.379470E+09 0.00 0.00
Maximum of Months 0.221150E+10 0.250473E+10 0.862899E+09 0.107526E+09 0.776691E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.100010E+10 0.164547E+10 0.973364E+09 0.578542E+09 0.394822E+09 0.00 0.00
February 0.122485E+10 0.130379E+10 0.103844E+10 0.601931E+09 0.436505E+09 0.00 0.00
March 0.161832E+10 0.120870E+10 0.126377E+10 0.652149E+09 0.611620E+09 0.00 0.00
April 0.216064E+10 0.627271E+09 0.133510E+10 0.654044E+09 0.681055E+09 0.00 0.00
May 0.260774E+10 0.344511E+09 0.137582E+10 0.637186E+09 0.738635E+09 0.00 0.00
June 0.296038E+10 0.137089E+09 0.132020E+10 0.625352E+09 0.694846E+09 0.00 0.00
July 0.284103E+10 0.100327E+09 0.124132E+10 0.547666E+09 0.693659E+09 0.00 0.00
August 0.264528E+10 0.165745E+09 0.120652E+10 0.530726E+09 0.675789E+09 0.00 0.00
September 0.245474E+10 0.357446E+09 0.123206E+10 0.644030E+09 0.588031E+09 0.00 0.00
October 0.182311E+10 0.724219E+09 0.112346E+10 0.612150E+09 0.511313E+09 0.00 0.00
November 0.129034E+10 0.129900E+10 0.106411E+10 0.655039E+09 0.409076E+09 0.00 0.00
December 0.966518E+09 0.176213E+10 0.983308E+09 0.577324E+09 0.405984E+09 0.00 0.00
               
Annual Sum or Average 0.235930E+11 0.967570E+10 0.141575E+11 0.731614E+10 0.684134E+10 0.00 0.00
Minimum of Months 0.966518E+09 0.100327E+09 0.973364E+09 0.530726E+09 0.394822E+09 0.00 0.00
Maximum of Months 0.296038E+10 0.176213E+10 0.137582E+10 0.655039E+09 0.738635E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.182898E+10 0.169062E+10 0.152718E+10 0.105785E+10 0.469332E+09 0.00 0.00
February 0.166405E+10 0.132839E+10 0.133098E+10 0.841376E+09 0.489606E+09 0.00 0.00
March 0.162631E+10 0.125006E+10 0.123709E+10 0.582162E+09 0.654925E+09 0.00 0.00
April 0.154473E+10 0.598200E+09 0.928373E+09 0.263104E+09 0.665269E+09 0.00 0.00
May 0.168059E+10 0.265465E+09 0.795528E+09 95695732.11 0.699832E+09 0.00 0.00
June 0.194744E+10 87505084.95 0.716374E+09 63322576.03 0.653051E+09 0.00 0.00
July 0.196716E+10 46765894.13 0.723725E+09 66827933.17 0.656897E+09 0.00 0.00
August 0.195947E+10 0.101702E+09 0.795946E+09 0.147226E+09 0.648721E+09 0.00 0.00
September 0.215798E+10 0.312329E+09 0.105488E+10 0.443840E+09 0.611036E+09 0.00 0.00
October 0.224449E+10 0.679177E+09 0.138326E+10 0.822779E+09 0.560482E+09 0.00 0.00
November 0.203019E+10 0.131426E+10 0.154509E+10 0.107890E+10 0.466191E+09 0.00 0.00
December 0.181655E+10 0.183137E+10 0.156334E+10 0.107678E+10 0.486559E+09 0.00 0.00
               
Annual Sum or Average 0.224680E+11 0.950583E+10 0.136018E+11 0.653986E+10 0.706190E+10 0.00 0.00
Minimum of Months 0.154473E+10 46765894.13 0.716374E+09 63322576.03 0.466191E+09 0.00 0.00
Maximum of Months 0.224449E+10 0.183137E+10 0.156334E+10 0.107890E+10 0.699832E+09 0.00 0.00



Table of Contents

Report: AverageOutdoorConditionsMonthly

For: Environment

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] SITE OUTDOOR AIR WETBULB TEMPERATURE [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] SITE WIND SPEED [m/s] SITE SKY TEMPERATURE [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] SITE RAIN STATUS []
January 8.14 3.28 -3.0 3.49 -5.4 41.12 223.64 0.00
February 10.27 3.71 -4.6 3.82 -5.0 51.61 245.22 0.00
March 12.55 4.68 -5.5 4.62 -3.1 72.41 273.25 0.00
April 19.23 8.50 -2.7 4.72 3.38 79.21 314.56 0.00
May 23.84 12.23 2.64 5.25 8.38 86.83 326.20 0.00
June 27.86 15.03 5.88 4.15 14.09 80.19 344.14 0.01
July 27.54 18.92 14.64 3.53 17.44 86.25 283.04 0.01
August 26.28 17.11 12.00 3.28 15.48 80.55 269.68 0.02
September 23.38 15.82 11.20 2.23 11.29 66.71 294.09 0.00
October 18.30 12.02 7.27 3.24 6.21 54.59 257.93 0.01
November 11.18 5.22 -1.5 3.40 -3.3 40.23 258.80 0.00
December 6.79 1.84 -4.8 2.82 -8.9 42.65 217.21 0.00
                 
Annual Sum or Average 17.98 9.90 2.67 3.71 4.26 65.29 275.60 0.00
Minimum of Months 6.79 1.84 -5.5 2.23 -8.9 40.23 217.21 0.00
Maximum of Months 27.86 18.92 14.64 5.25 17.44 86.83 344.14 0.02



Table of Contents

Report: OutdoorConditionsMaximumDryBulbMonthly

For: Environment

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 20.60 03-JAN-14:00 8.39 -5.0 9.80 2.22 118.50 530.50
February 23.30 20-FEB-14:00 8.88 -7.8 4.10 4.10 55.00 955.00
March 25.00 21-MAR-15:00 9.53 -8.3 6.20 5.54 50.00 873.00
April 32.20 21-APR-13:00 15.21 2.80 13.90 18.28 265.50 638.50
May 35.00 19-MAY-13:00 17.23 6.10 10.30 21.78 145.00 874.50
June 38.90 02-JUN-15:00 16.22 -1.1 4.60 20.40 234.50 284.00
July 38.30 01-JUL-16:00 19.19 8.90 3.60 26.81 165.50 256.50
August 37.20 07-AUG-15:00 17.89 6.70 5.70 24.66 143.50 615.00
September 33.90 19-SEP-13:00 16.85 6.70 3.10 17.75 113.00 912.00
October 32.80 01-OCT-14:00 15.90 4.40 5.70 16.12 127.50 736.50
November 23.90 03-NOV-15:00 13.45 6.10 5.70 12.22 48.50 648.50
December 18.30 10-DEC-14:00 7.97 -2.8 7.20 4.10 123.00 52.50
                 
Annual Sum or Average                
Minimum of Months 18.30   7.97 -8.3 3.10 2.22 48.50 52.50
Maximum of Months 38.90   19.19 8.90 13.90 26.81 265.50 955.00



Table of Contents

Report: OutdoorConditionsMinimumDryBulbMonthly

For: Environment

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January -4.4 27-JAN-06:00 -7.5 -15.0 3.60 -23.6 0.00 0.00
February -5.6 03-FEB-06:00 -7.5 -11.7 1.50 -23.9 0.00 0.00
March -3.9 02-MAR-04:00 -6.5 -12.8 1.50 -21.3 0.00 0.00
April 3.30 12-APR-05:00 -1.8 -9.4 2.10 -14.9 37.00 217.50
May 9.40 02-MAY-05:00 3.98 -2.2 3.60 -7.6 51.00 277.50
June 15.00 13-JUN-04:00 4.43 -10.6 2.10 -4.3 0.00 0.00
July 17.80 05-JUL-05:00 15.98 15.00 4.10 4.31 39.00 249.00
August 16.70 31-AUG-05:00 13.89 12.20 4.10 2.64 36.00 126.50
September 8.30 30-SEP-05:00 5.77 3.30 1.50 -7.3 0.00 0.00
October 6.70 11-OCT-05:00 5.82 5.00 1.50 -5.5 0.00 0.00
November -0.6 17-NOV-03:00 -3.1 -6.7 1.50 -18.1 0.00 0.00
December -4.4 27-DEC-06:00 -5.1 -6.1 2.10 -18.6 0.00 0.00
                 
Annual Sum or Average                
Minimum of Months -5.6   -7.5 -15.0 1.50 -23.9 0.00 0.00
Maximum of Months 17.80   15.98 15.00 4.10 4.31 51.00 277.50



Table of Contents

Report: OutdoorConditionsMaximumWetBulbMonthly

For: Environment

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

SITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 10.18 12-JAN-15:00 18.90 2.80 3.60 6.15 70.50 491.50
February 11.42 13-FEB-16:00 12.80 10.60 4.10 6.55 34.00 18.50
March 10.75 10-MAR-18:00 13.30 8.90 1.50 8.54 0.00 0.00
April 15.74 29-APR-13:00 30.00 6.70 4.10 18.28 336.50 432.50
May 19.12 24-MAY-12:00 27.80 15.00 5.20 17.57 188.50 862.00
June 20.21 03-JUN-14:00 33.90 13.90 8.80 23.66 264.50 316.00
July 22.88 20-JUL-15:39 25.53 21.87 2.93 18.99 184.00 15.83
August 21.18 02-AUG-11:00 30.60 17.20 3.60 20.75 154.50 850.00
September 20.65 14-SEP-09:00 25.00 18.90 2.10 14.47 126.50 835.50
October 19.64 03-OCT-13:00 32.80 13.30 2.60 21.44 224.50 577.50
November 13.57 03-NOV-14:00 23.30 7.20 0.00 10.88 72.50 802.00
December 8.30 10-DEC-12:00 17.20 -0.6 5.70 1.58 198.50 507.50
                 
Annual Sum or Average                
Minimum of Months 8.30   12.80 -0.6 0.00 1.58 0.00 0.00
Maximum of Months 22.88   33.90 21.87 8.80 23.66 336.50 862.00



Table of Contents

Report: OutdoorConditionsMaximumDewPointMonthly

For: Environment

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

SITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 9.00 16-JAN-01:00 9.00 9.00 2.10 4.51 0.00 0.00
February 10.60 13-FEB-13:09 12.20 11.24 5.53 5.71 147.33 0.00
March 10.00 11-MAR-00:00 10.60 10.24 2.10 6.15 0.00 0.00
April 10.60 17-APR-01:00 17.80 13.38 7.20 3.48 0.00 0.00
May 15.00 24-MAY-10:00 25.60 18.41 7.20 15.39 171.00 872.50
June 17.20 19-JUN-17:00 23.90 19.20 3.60 15.39 86.00 324.00
July 22.20 20-JUL-14:00 24.40 22.82 4.60 17.93 283.00 59.50
August 18.90 01-AUG-20:00 22.20 19.91 4.60 17.75 0.00 0.00
September 19.40 22-SEP-01:00 20.60 19.76 1.50 16.30 0.00 0.00
October 17.20 03-OCT-19:00 23.30 19.11 4.60 18.46 0.00 0.00
November 10.00 01-NOV-09:00 13.30 11.28 3.10 8.94 123.50 0.00
December 6.10 13-DEC-00:00 8.30 7.10 7.70 3.06 0.00 0.00
                 
Annual Sum or Average                
Minimum of Months 6.10   8.30 7.10 1.50 3.06 0.00 0.00
Maximum of Months 22.20   25.60 22.82 7.70 18.46 283.00 872.50



Table of Contents

Report: OutdoorGroundConditionsMonthly

For: Environment

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

SITE GROUND TEMPERATURE [C] SITE SURFACE GROUND TEMPERATURE [C] SITE DEEP GROUND TEMPERATURE [C] SITE MAINS WATER TEMPERATURE [C] SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] SITE SNOW ON GROUND STATUS []
January 18.00 13.00 16.00 15.16 28.38 0.00
February 18.00 13.00 16.00 15.21 35.58 0.00
March 18.00 13.00 16.00 16.80 47.71 0.00
April 18.00 13.00 16.00 19.62 58.45 0.00
May 18.00 13.00 16.00 22.88 63.58 0.00
June 18.00 13.00 16.00 25.71 66.73 0.00
July 18.00 13.00 16.00 27.35 58.19 0.00
August 18.00 13.00 16.00 27.33 54.44 0.00
September 18.00 13.00 16.00 25.68 50.89 0.00
October 18.00 13.00 16.00 22.83 39.37 0.00
November 18.00 13.00 16.00 19.57 32.11 0.00
December 18.00 13.00 16.00 16.77 26.90 0.00
             
Annual Sum or Average 18.00 13.00 16.00 21.28 46.90 0.00
Minimum of Months 18.00 13.00 16.00 15.16 26.90 0.00
Maximum of Months 18.00 13.00 16.00 27.35 66.73 0.00



Table of Contents

Report: WaterHeaterReportMonthly

For: SWH BOOSTER E WATER HEATER

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] WATER HEATER BURNER HEATING ENERGY [] WATER HEATER GAS CONSUMPTION [] WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] WATER HEATER LOSS DEMAND ENERGY [] WATER HEATER HEAT LOSS ENERGY [J] WATER HEATER TANK TEMPERATURE [C] WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] WATER HEATER SOURCE ENERGY []
January 0.770788E+10 -0.754278E+10 0.00 0.00 744.00 0.00 -165107042.0 81.21 0.00 0.00
February 0.696485E+10 -0.681596E+10 0.00 0.00 672.00 0.00 -148888144.3 81.21 0.00 0.00
March 0.770612E+10 -0.754148E+10 0.00 0.00 744.00 0.00 -164647419.1 81.21 0.00 0.00
April 0.746747E+10 -0.730860E+10 0.00 0.00 720.00 0.00 -158876340.3 81.21 0.00 0.00
May 0.770670E+10 -0.754280E+10 0.00 0.00 744.00 0.00 -163906296.1 81.21 0.00 0.00
June 0.745896E+10 -0.730053E+10 0.00 0.00 720.00 0.00 -158429655.3 81.21 0.00 0.00
July 0.771461E+10 -0.755086E+10 0.00 0.00 744.00 0.00 -163754766.4 81.21 0.00 0.00
August 0.770662E+10 -0.754281E+10 0.00 0.00 744.00 0.00 -163819213.2 81.21 0.00 0.00
September 0.746858E+10 -0.730994E+10 0.00 0.00 720.00 0.00 -158641711.8 81.21 0.00 0.00
October 0.770574E+10 -0.754144E+10 0.00 0.00 744.00 0.00 -164304341.2 81.21 0.00 0.00
November 0.745192E+10 -0.729244E+10 0.00 0.00 720.00 0.00 -159475520.3 81.21 0.00 0.00
December 0.771604E+10 -0.755085E+10 0.00 0.00 744.00 0.00 -165192497.5 81.21 0.00 0.00
                     
Annual Sum or Average 0.907755E+11 -0.888405E+11 0.00 0.00 8760.00 0.00 -0.193504E+10 81.21 0.00 0.00
Minimum of Months 0.696485E+10 -0.755086E+10 0.00 0.00 672.00 0.00 -165192497.5 81.21 0.00 0.00
Maximum of Months 0.771604E+10 -0.681596E+10 0.00 0.00 744.00 0.00 -148888144.3 81.21 0.00 0.00



Table of Contents

Report: WaterHeaterReportMonthly

For: SWH LAUNDRY G WATER HEATER

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] WATER HEATER BURNER HEATING ENERGY [] WATER HEATER GAS CONSUMPTION [] WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] WATER HEATER LOSS DEMAND ENERGY [] WATER HEATER HEAT LOSS ENERGY [J] WATER HEATER TANK TEMPERATURE [C] WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] WATER HEATER SOURCE ENERGY []
January 0.113706E+12 -0.111892E+12 0.00 0.00 744.00 0.00 -0.181371E+10 81.26 0.00 0.00
February 0.102637E+12 -0.100997E+12 0.00 0.00 672.00 0.00 -0.164004E+10 81.26 0.00 0.00
March 0.110924E+12 -0.109106E+12 0.00 0.00 744.00 0.00 -0.181791E+10 81.26 0.00 0.00
April 0.102723E+12 -0.100964E+12 0.00 0.00 720.00 0.00 -0.175950E+10 81.26 0.00 0.00
May 0.100614E+12 -0.987969E+11 0.00 0.00 744.00 0.00 -0.181743E+10 81.25 0.00 0.00
June 0.927220E+11 -0.909636E+11 0.00 0.00 720.00 0.00 -0.175846E+10 81.25 0.00 0.00
July 0.930444E+11 -0.912300E+11 0.00 0.00 744.00 0.00 -0.181443E+10 81.25 0.00 0.00
August 0.930633E+11 -0.912531E+11 0.00 0.00 744.00 0.00 -0.181017E+10 81.25 0.00 0.00
September 0.927696E+11 -0.910241E+11 0.00 0.00 720.00 0.00 -0.174545E+10 81.24 0.00 0.00
October 0.100683E+12 -0.988820E+11 0.00 0.00 744.00 0.00 -0.180148E+10 81.25 0.00 0.00
November 0.102789E+12 -0.101046E+12 0.00 0.00 720.00 0.00 -0.174354E+10 81.25 0.00 0.00
December 0.110975E+12 -0.109168E+12 0.00 0.00 744.00 0.00 -0.180773E+10 81.25 0.00 0.00
                     
Annual Sum or Average 0.121665E+13 -0.119532E+13 0.00 0.00 8760.00 0.00 -0.213299E+11 81.25 0.00 0.00
Minimum of Months 0.927220E+11 -0.111892E+12 0.00 0.00 672.00 0.00 -0.181791E+10 81.24 0.00 0.00
Maximum of Months 0.113706E+12 -0.909636E+11 0.00 0.00 744.00 0.00 -0.164004E+10 81.26 0.00 0.00



Table of Contents

Report: WaterHeaterReportMonthly

For: SWHSYS1 WATER HEATER

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] WATER HEATER BURNER HEATING ENERGY [] WATER HEATER GAS CONSUMPTION [] WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] WATER HEATER LOSS DEMAND ENERGY [] WATER HEATER HEAT LOSS ENERGY [J] WATER HEATER TANK TEMPERATURE [C] WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] WATER HEATER SOURCE ENERGY []
January 0.656074E+11 -0.640241E+11 0.00 0.00 744.00 0.00 -0.158332E+10 58.98 0.00 0.00
February 0.592152E+11 -0.577825E+11 0.00 0.00 672.00 0.00 -0.143270E+10 58.98 0.00 0.00
March 0.632684E+11 -0.616793E+11 0.00 0.00 744.00 0.00 -0.158914E+10 58.98 0.00 0.00
April 0.572105E+11 -0.556723E+11 0.00 0.00 720.00 0.00 -0.153823E+10 58.98 0.00 0.00
May 0.543520E+11 -0.527631E+11 0.00 0.00 744.00 0.00 -0.158882E+10 58.98 0.00 0.00
June 0.486047E+11 -0.470677E+11 0.00 0.00 720.00 0.00 -0.153708E+10 58.98 0.00 0.00
July 0.477891E+11 -0.462044E+11 0.00 0.00 744.00 0.00 -0.158462E+10 58.98 0.00 0.00
August 0.478502E+11 -0.462716E+11 0.00 0.00 744.00 0.00 -0.157859E+10 58.98 0.00 0.00
September 0.486177E+11 -0.470985E+11 0.00 0.00 720.00 0.00 -0.151922E+10 58.98 0.00 0.00
October 0.543729E+11 -0.528062E+11 0.00 0.00 744.00 0.00 -0.156663E+10 58.98 0.00 0.00
November 0.572361E+11 -0.557199E+11 0.00 0.00 720.00 0.00 -0.151623E+10 58.98 0.00 0.00
December 0.632484E+11 -0.616730E+11 0.00 0.00 744.00 0.00 -0.157535E+10 58.98 0.00 0.00
                     
Annual Sum or Average 0.667373E+12 -0.648763E+12 0.00 0.00 8760.00 0.00 -0.186099E+11 58.98 0.00 0.00
Minimum of Months 0.477891E+11 -0.640241E+11 0.00 0.00 672.00 0.00 -0.158914E+10 58.98 0.00 0.00
Maximum of Months 0.656074E+11 -0.462044E+11 0.00 0.00 744.00 0.00 -0.143270E+10 58.98 0.00 0.00



Table of Contents

Report: DaylightingReportMonthly

For: Environment

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER [] DAYLIGHTING LIGHTING POWER MULTIPLIER [] DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME []
January 276.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 268.33 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 351.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 373.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 408.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 398.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 400.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 377.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 365.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 318.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 295.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 289.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average 4125.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 268.33 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 408.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: VAV WITH REHEAT HEATING COIL

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.390826E+09 39201.22 27-JAN-07:10 0.00 0.00 0.00 0.00 0.00
February 0.492491E+09 47495.08 03-FEB-07:10 0.00 0.00 0.00 0.00 0.00
March 72578409.28 17221.48 10-MAR-08:40 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 1609.64 2.68 13-SEP-18:30 0.00 0.00 0.00 0.00 0.00
October 17083817.29 14287.08 06-OCT-07:17 0.00 0.00 0.00 0.00 0.00
November 8994225.67 16126.68 30-NOV-19:08 0.00 0.00 0.00 0.00 0.00
December 0.831826E+09 39686.52 27-DEC-07:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.181380E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.831826E+09 47495.08   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: BASEMENT VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.471418E+10 8490.97 02-JAN-11:40 0.00 0.00 0.00 0.00 0.00
February 0.105238E+11 8753.52 20-FEB-11:50 0.00 0.00 0.00 0.00 0.00
March 0.163009E+11 8761.88 19-MAR-10:50 0.00 0.00 0.00 0.00 0.00
April 0.156756E+11 8867.44 30-APR-10:35 0.00 0.00 0.00 0.00 0.00
May 0.149304E+11 8888.95 21-MAY-10:50 0.00 0.00 0.00 0.00 0.00
June 0.132534E+11 8925.38 17-JUN-10:50 0.00 0.00 0.00 0.00 0.00
July 0.748279E+10 8930.98 02-JUL-10:35 0.00 0.00 0.00 0.00 0.00
August 0.323694E+10 8894.53 07-AUG-10:50 0.00 0.00 0.00 0.00 0.00
September 0.411664E+09 6877.51 01-SEP-10:35 0.00 0.00 0.00 0.00 0.00
October 60947743.65 4535.33 05-OCT-10:40 0.00 0.00 0.00 0.00 0.00
November 10684294.40 2344.55 06-NOV-11:50 0.00 0.00 0.00 0.00 0.00
December 0.718548E+09 3793.54 10-DEC-11:40 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.873197E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 10684294.40 2344.55   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.163009E+11 8930.98   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: RETAIL_1_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.374278E+10 3093.05 27-JAN-07:30 0.00 0.00 0.00 0.00 0.00
February 0.305924E+10 3114.29 03-FEB-07:10 0.00 0.00 0.00 0.00 0.00
March 0.317947E+10 2971.02 02-MAR-05:00 0.00 0.00 0.00 0.00 0.00
April 0.204381E+10 2335.66 12-APR-06:05 0.00 0.00 0.00 0.00 0.00
May 0.142931E+10 1805.00 02-MAY-07:40 0.00 0.00 0.00 0.00 0.00
June 0.707313E+09 1300.78 30-JUN-07:35 0.00 0.00 0.00 0.00 0.00
July 0.712130E+09 1385.79 19-JUL-10:40 0.00 0.00 0.00 0.00 0.00
August 0.794169E+09 1645.27 16-AUG-10:40 0.00 0.00 0.00 0.00 0.00
September 0.868491E+09 1725.14 25-SEP-06:05 0.00 0.00 0.00 0.00 0.00
October 0.166009E+10 2052.38 25-OCT-06:05 0.00 0.00 0.00 0.00 0.00
November 0.285093E+10 2936.12 28-NOV-05:00 0.00 0.00 0.00 0.00 0.00
December 0.406719E+10 3115.02 28-DEC-07:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.251149E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.707313E+09 1300.78   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.406719E+10 3115.02   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: RETAIL_2_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.152282E+10 1271.69 17-JAN-11:40 0.00 0.00 0.00 0.00 0.00
February 0.123018E+10 1256.21 16-FEB-11:40 0.00 0.00 0.00 0.00 0.00
March 0.119413E+10 1322.08 29-MAR-10:40 0.00 0.00 0.00 0.00 0.00
April 0.752235E+09 1299.82 11-APR-10:40 0.00 0.00 0.00 0.00 0.00
May 0.541585E+09 1135.37 02-MAY-10:40 0.00 0.00 0.00 0.00 0.00
June 0.375947E+09 1034.84 30-JUN-10:35 0.00 0.00 0.00 0.00 0.00
July 0.395558E+09 1100.00 05-JUL-10:40 0.00 0.00 0.00 0.00 0.00
August 0.411374E+09 1106.49 17-AUG-10:40 0.00 0.00 0.00 0.00 0.00
September 0.394780E+09 1081.06 05-SEP-10:35 0.00 0.00 0.00 0.00 0.00
October 0.667922E+09 1115.74 24-OCT-10:40 0.00 0.00 0.00 0.00 0.00
November 0.112662E+10 1279.64 27-NOV-11:40 0.00 0.00 0.00 0.00 0.00
December 0.164589E+10 1301.35 26-DEC-11:33 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.102590E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.375947E+09 1034.84   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.164589E+10 1322.08   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: MECH_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.345891E+10 2039.28 28-JAN-06:00 0.00 0.00 0.00 0.00 0.00
February 0.282485E+10 2016.69 03-FEB-05:00 0.00 0.00 0.00 0.00 0.00
March 0.270890E+10 1961.27 02-MAR-04:50 0.00 0.00 0.00 0.00 0.00
April 0.163730E+10 1672.34 11-APR-10:40 0.00 0.00 0.00 0.00 0.00
May 0.912333E+09 1364.86 02-MAY-10:40 0.00 0.00 0.00 0.00 0.00
June 0.353874E+09 1103.31 29-JUN-10:50 0.00 0.00 0.00 0.00 0.00
July 0.383047E+09 1040.13 21-JUL-10:50 0.00 0.00 0.00 0.00 0.00
August 0.581378E+09 1230.50 17-AUG-10:50 0.00 0.00 0.00 0.00 0.00
September 0.915684E+09 1353.98 25-SEP-10:35 0.00 0.00 0.00 0.00 0.00
October 0.171558E+10 1524.66 25-OCT-10:40 0.00 0.00 0.00 0.00 0.00
November 0.277467E+10 1911.15 28-NOV-05:00 0.00 0.00 0.00 0.00 0.00
December 0.366910E+10 2068.88 27-DEC-05:00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.219356E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.353874E+09 1040.13   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.366910E+10 2068.88   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: STORAGE_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.218804E+10 1163.14 28-JAN-07:10 0.00 0.00 0.00 0.00 0.00
February 0.179734E+10 1147.35 03-FEB-05:00 0.00 0.00 0.00 0.00 0.00
March 0.174891E+10 1122.39 02-MAR-05:00 0.00 0.00 0.00 0.00 0.00
April 0.107961E+10 961.75 11-APR-10:40 0.00 0.00 0.00 0.00 0.00
May 0.611136E+09 773.22 02-MAY-10:40 0.00 0.00 0.00 0.00 0.00
June 0.225693E+09 612.53 29-JUN-10:40 0.00 0.00 0.00 0.00 0.00
July 0.243463E+09 554.70 05-JUL-10:35 0.00 0.00 0.00 0.00 0.00
August 0.380792E+09 669.04 17-AUG-10:40 0.00 0.00 0.00 0.00 0.00
September 0.611577E+09 735.48 25-SEP-10:40 0.00 0.00 0.00 0.00 0.00
October 0.113004E+10 845.83 25-OCT-10:40 0.00 0.00 0.00 0.00 0.00
November 0.177980E+10 1082.45 28-NOV-05:00 0.00 0.00 0.00 0.00 0.00
December 0.231278E+10 1163.49 28-DEC-06:00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.141092E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.225693E+09 554.70   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.231278E+10 1163.49   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: LAUNDRY_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.136023E+11 12629.16 28-JAN-06:00 0.00 0.00 0.00 0.00 0.00
February 0.119713E+11 12438.01 02-FEB-04:40 0.00 0.00 0.00 0.00 0.00
March 0.130385E+11 12437.87 02-MAR-04:50 0.00 0.00 0.00 0.00 0.00
April 0.123451E+11 13363.58 29-APR-10:50 0.00 0.00 0.00 0.00 0.00
May 0.128487E+11 13418.48 30-MAY-10:50 0.00 0.00 0.00 0.00 0.00
June 0.129311E+11 13484.27 17-JUN-10:50 0.00 0.00 0.00 0.00 0.00
July 0.133956E+11 13484.49 03-JUL-10:50 0.00 0.00 0.00 0.00 0.00
August 0.133067E+11 13451.60 04-AUG-10:50 0.00 0.00 0.00 0.00 0.00
September 0.128412E+11 13412.23 02-SEP-10:50 0.00 0.00 0.00 0.00 0.00
October 0.129473E+11 13370.96 05-OCT-10:50 0.00 0.00 0.00 0.00 0.00
November 0.126406E+11 12535.86 28-NOV-05:00 0.00 0.00 0.00 0.00 0.00
December 0.137511E+11 12816.47 04-DEC-05:00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.155620E+12     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.119713E+11 12437.87   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.137511E+11 13484.49   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CAFE_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.541119E+10 7890.41 17-JAN-10:30 0.00 0.00 0.00 0.00 0.00
February 0.417828E+10 7887.99 03-FEB-07:20 0.00 0.00 0.00 0.00 0.00
March 0.450203E+10 7430.58 24-MAR-10:40 0.00 0.00 0.00 0.00 0.00
April 0.294557E+10 6427.71 11-APR-08:04 0.00 0.00 0.00 0.00 0.00
May 0.247607E+10 5846.65 03-MAY-10:40 0.00 0.00 0.00 0.00 0.00
June 0.165531E+10 5584.86 29-JUN-10:40 0.00 0.00 0.00 0.00 0.00
July 0.159408E+10 5810.27 19-JUL-10:40 0.00 0.00 0.00 0.00 0.00
August 0.144487E+10 6529.62 16-AUG-10:40 0.00 0.00 0.00 0.00 0.00
September 0.951414E+09 4352.25 25-SEP-06:05 0.00 0.00 0.00 0.00 0.00
October 0.188446E+10 6621.13 13-OCT-10:50 0.00 0.00 0.00 0.00 0.00
November 0.365369E+10 8233.99 27-NOV-11:40 0.00 0.00 0.00 0.00 0.00
December 0.610264E+10 8576.67 27-DEC-07:20 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.367996E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.951414E+09 4352.25   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.610264E+10 8576.67   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: LOBBY_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.154165E+11 21698.37 17-JAN-11:40 0.00 0.00 0.00 0.00 0.00
February 0.121979E+11 20710.07 13-FEB-11:40 0.00 0.00 0.00 0.00 0.00
March 0.130102E+11 20974.05 24-MAR-10:40 0.00 0.00 0.00 0.00 0.00
April 0.924512E+10 21066.66 11-APR-10:40 0.00 0.00 0.00 0.00 0.00
May 0.790243E+10 19373.22 02-MAY-10:40 0.00 0.00 0.00 0.00 0.00
June 0.595254E+10 18603.69 30-JUN-10:35 0.00 0.00 0.00 0.00 0.00
July 0.596978E+10 18579.10 05-JUL-10:40 0.00 0.00 0.00 0.00 0.00
August 0.576620E+10 17854.83 16-AUG-10:40 0.00 0.00 0.00 0.00 0.00
September 0.455636E+10 16846.41 05-SEP-10:40 0.00 0.00 0.00 0.00 0.00
October 0.619831E+10 18861.53 16-OCT-10:40 0.00 0.00 0.00 0.00 0.00
November 0.104497E+11 22499.17 27-NOV-11:40 0.00 0.00 0.00 0.00 0.00
December 0.168490E+11 22683.39 26-DEC-11:20 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.113514E+12     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.455636E+10 16846.41   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.168490E+11 22683.39   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORRIDOR_FLR_3 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.100449E+11 8599.62 27-JAN-07:10 0.00 0.00 0.00 0.00 0.00
February 0.701599E+10 8543.01 02-FEB-07:10 0.00 0.00 0.00 0.00 0.00
March 0.590443E+10 8124.41 02-MAR-07:10 0.00 0.00 0.00 0.00 0.00
April 0.138405E+10 5680.82 11-APR-10:40 0.00 0.00 0.00 0.00 0.00
May 0.127262E+09 3325.13 02-MAY-10:40 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 13200557.49 2303.38 17-AUG-10:40 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.110075E+10 5280.23 14-OCT-10:40 0.00 0.00 0.00 0.00 0.00
November 0.578413E+10 8407.62 27-NOV-11:40 0.00 0.00 0.00 0.00 0.00
December 0.113130E+11 9528.78 27-DEC-07:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.426878E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.113130E+11 9528.78   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORRIDOR_FLR_6 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.104812E+11 7234.58 27-JAN-07:20 0.00 0.00 0.00 0.00 0.00
February 0.824485E+10 7333.68 03-FEB-07:10 0.00 0.00 0.00 0.00 0.00
March 0.786649E+10 6971.84 02-MAR-07:10 0.00 0.00 0.00 0.00 0.00
April 0.396083E+10 5286.33 12-APR-06:10 0.00 0.00 0.00 0.00 0.00
May 0.174029E+10 3634.88 02-MAY-07:40 0.00 0.00 0.00 0.00 0.00
June 0.234675E+09 1742.81 30-JUN-07:35 0.00 0.00 0.00 0.00 0.00
July 0.202830E+09 1897.24 19-JUL-10:40 0.00 0.00 0.00 0.00 0.00
August 0.582786E+09 2902.00 16-AUG-10:40 0.00 0.00 0.00 0.00 0.00
September 0.137866E+10 3850.28 25-SEP-06:05 0.00 0.00 0.00 0.00 0.00
October 0.407826E+10 4686.32 25-OCT-06:05 0.00 0.00 0.00 0.00 0.00
November 0.798337E+10 6461.23 28-NOV-06:05 0.00 0.00 0.00 0.00 0.00
December 0.114479E+11 7335.57 28-DEC-07:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.582022E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.202830E+09 1742.81   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.114479E+11 7335.57   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: BANQUET_FLR_6 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.423580E+10 7796.21 27-JAN-11:40 0.00 0.00 0.00 0.00 0.00
February 0.305171E+10 7544.31 03-FEB-11:40 0.00 0.00 0.00 0.00 0.00
March 0.263965E+10 7709.60 29-MAR-10:40 0.00 0.00 0.00 0.00 0.00
April 0.115275E+10 7201.09 11-APR-10:40 0.00 0.00 0.00 0.00 0.00
May 0.586579E+09 6242.49 02-MAY-10:40 0.00 0.00 0.00 0.00 0.00
June 0.260948E+09 4892.28 26-JUN-10:35 0.00 0.00 0.00 0.00 0.00
July 0.276881E+09 4901.05 24-JUL-10:40 0.00 0.00 0.00 0.00 0.00
August 0.441987E+09 5438.90 22-AUG-10:35 0.00 0.00 0.00 0.00 0.00
September 0.678210E+09 6265.51 25-SEP-10:35 0.00 0.00 0.00 0.00 0.00
October 0.152350E+10 6799.41 25-OCT-10:40 0.00 0.00 0.00 0.00 0.00
November 0.311306E+10 7286.58 17-NOV-11:40 0.00 0.00 0.00 0.00 0.00
December 0.465287E+10 7673.84 07-DEC-11:40 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.226139E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.260948E+09 4892.28   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.465287E+10 7796.21   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: DINING_FLR_6 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.361455E+10 7440.27 30-JAN-11:40 0.00 0.00 0.00 0.00 0.00
February 0.249665E+10 7189.49 03-FEB-11:40 0.00 0.00 0.00 0.00 0.00
March 0.204837E+10 7253.69 29-MAR-10:40 0.00 0.00 0.00 0.00 0.00
April 0.741507E+09 6793.28 11-APR-10:40 0.00 0.00 0.00 0.00 0.00
May 0.331959E+09 5703.49 02-MAY-10:40 0.00 0.00 0.00 0.00 0.00
June 0.144866E+09 4542.08 30-JUN-10:40 0.00 0.00 0.00 0.00 0.00
July 0.155180E+09 4554.23 24-JUL-10:40 0.00 0.00 0.00 0.00 0.00
August 0.252626E+09 4924.17 22-AUG-10:40 0.00 0.00 0.00 0.00 0.00
September 0.414266E+09 5858.41 25-SEP-10:40 0.00 0.00 0.00 0.00 0.00
October 0.106925E+10 6459.20 25-OCT-10:40 0.00 0.00 0.00 0.00 0.00
November 0.254328E+10 7007.09 17-NOV-11:40 0.00 0.00 0.00 0.00 0.00
December 0.400872E+10 7329.60 07-DEC-11:40 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.178212E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.144866E+09 4542.08   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.400872E+10 7440.27   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: KITCHEN_FLR_6 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.216207E+10 5775.16 28-JAN-04:00 0.00 0.00 0.00 0.00 0.00
February 0.176562E+10 5841.47 03-FEB-04:00 0.00 0.00 0.00 0.00 0.00
March 0.166254E+10 5907.01 02-MAR-04:00 0.00 0.00 0.00 0.00 0.00
April 0.956283E+09 4424.71 11-APR-03:00 0.00 0.00 0.00 0.00 0.00
May 0.576081E+09 3319.17 02-MAY-03:00 0.00 0.00 0.00 0.00 0.00
June 0.246315E+09 2228.39 29-JUN-03:00 0.00 0.00 0.00 0.00 0.00
July 0.231411E+09 2228.40 05-JUL-03:00 0.00 0.00 0.00 0.00 0.00
August 0.313589E+09 2796.20 17-AUG-03:00 0.00 0.00 0.00 0.00 0.00
September 0.516262E+09 3419.34 25-SEP-03:00 0.00 0.00 0.00 0.00 0.00
October 0.101477E+10 4166.47 25-OCT-03:00 0.00 0.00 0.00 0.00 0.00
November 0.179501E+10 5775.52 28-NOV-04:00 0.00 0.00 0.00 0.00 0.00
December 0.235702E+10 6035.96 27-DEC-04:00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.135970E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.231411E+09 2228.39   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.235702E+10 6035.96   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLR_3_DOAS HEATING COIL

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.273843E+11 15911.02 27-JAN-07:00 0.00 0.00 0.00 0.00 0.00
February 0.190765E+11 16182.58 03-FEB-07:00 0.00 0.00 0.00 0.00 0.00
March 0.159141E+11 15798.57 02-MAR-05:00 0.00 0.00 0.00 0.00 0.00
April 0.437768E+10 14148.07 12-APR-06:00 0.00 0.00 0.00 0.00 0.00
May 0.346645E+09 11023.85 02-MAY-06:00 0.00 0.00 0.00 0.00 0.00
June 38046.70 0.50 13-JUN-10:25 0.00 0.00 0.00 0.00 0.00
July 11380.94 0.51 12-JUL-04:30 0.00 0.00 0.00 0.00 0.00
August 25201.66 0.51 20-AUG-19:05 0.00 0.00 0.00 0.00 0.00
September 0.490805E+09 12984.10 30-SEP-06:00 0.00 0.00 0.00 0.00 0.00
October 0.380166E+10 13361.51 11-OCT-06:00 0.00 0.00 0.00 0.00 0.00
November 0.185253E+11 15049.80 28-NOV-01:00 0.00 0.00 0.00 0.00 0.00
December 0.290885E+11 15913.62 27-DEC-07:00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.119006E+12     0.00 0.00 0.00 0.00 0.00
Minimum of Months 11380.94 0.50   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.290885E+11 16182.58   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_1_FLR_3 FAN COIL HEATING COIL

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.183203E+10 6409.43 27-JAN-09:02 0.00 0.00 0.00 0.00 0.00
February 0.123680E+10 6389.56 02-FEB-09:02 0.00 0.00 0.00 0.00 0.00
March 0.758726E+09 6409.67 02-MAR-09:02 0.00 0.00 0.00 0.00 0.00
April 0.103129E+09 6214.73 11-APR-08:62 0.00 0.00 0.00 0.00 0.00
May 5036699.98 3326.09 10-MAY-08:03 0.00 0.00 0.00 0.00 0.00
June 2907576.20 1946.66 25-JUN-08:04 0.00 0.00 0.00 0.00 0.00
July 3785026.63 2497.61 18-JUL-08:04 0.00 0.00 0.00 0.00 0.00
August 4419717.58 2567.67 12-AUG-08:04 0.00 0.00 0.00 0.00 0.00
September 4083784.92 2594.20 27-SEP-08:03 0.00 0.00 0.00 0.00 0.00
October 36106183.83 3537.95 30-OCT-08:03 0.00 0.00 0.00 0.00 0.00
November 0.980392E+09 6410.53 27-NOV-09:02 0.00 0.00 0.00 0.00 0.00
December 0.245764E+10 6411.18 28-DEC-09:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.742506E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 2907576.20 1946.66   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.245764E+10 6411.18   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_2_FLR_3 FAN COIL HEATING COIL

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.274974E+10 6396.11 26-JAN-09:02 0.00 0.00 0.00 0.00 0.00
February 0.182309E+10 6396.48 09-FEB-09:02 0.00 0.00 0.00 0.00 0.00
March 0.104340E+10 6396.41 01-MAR-09:02 0.00 0.00 0.00 0.00 0.00
April 0.128993E+09 6219.41 11-APR-08:62 0.00 0.00 0.00 0.00 0.00
May 5012107.92 3130.48 08-MAY-08:03 0.00 0.00 0.00 0.00 0.00
June 2696169.75 1833.26 23-JUN-08:04 0.00 0.00 0.00 0.00 0.00
July 3579497.58 2600.56 21-JUL-08:04 0.00 0.00 0.00 0.00 0.00
August 4876744.91 2688.88 23-AUG-08:04 0.00 0.00 0.00 0.00 0.00
September 5472231.14 3361.62 11-SEP-08:03 0.00 0.00 0.00 0.00 0.00
October 78523069.87 4198.04 25-OCT-08:62 0.00 0.00 0.00 0.00 0.00
November 0.148247E+10 6397.78 28-NOV-09:02 0.00 0.00 0.00 0.00 0.00
December 0.358153E+10 6398.18 05-DEC-09:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.109094E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 2696169.75 1833.26   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.358153E+10 6398.18   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:03 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:03 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.113784E+09 10141.45 27-DEC-05:00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.113784E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.113784E+09 10141.45   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.681306E+10 36847.95 27-JAN-09:02 0.00 0.00 0.00 0.00 0.00
February 0.463926E+10 36621.25 02-FEB-09:02 0.00 0.00 0.00 0.00 0.00
March 0.193555E+10 36487.98 02-MAR-09:02 0.00 0.00 0.00 0.00 0.00
April 0.143712E+09 34831.61 11-APR-15:03 0.00 0.00 0.00 0.00 0.00
May 35197189.76 31073.08 23-MAY-08:04 0.00 0.00 0.00 0.00 0.00
June 16461998.84 26152.06 23-JUN-08:04 0.00 0.00 0.00 0.00 0.00
July 12937310.18 25754.65 05-JUL-08:05 0.00 0.00 0.00 0.00 0.00
August 25980006.53 32128.64 24-AUG-08:04 0.00 0.00 0.00 0.00 0.00
September 44411384.69 30917.69 21-SEP-08:04 0.00 0.00 0.00 0.00 0.00
October 0.107190E+09 28234.88 24-OCT-15:03 0.00 0.00 0.00 0.00 0.00
November 0.300322E+10 36251.64 27-NOV-16:02 0.00 0.00 0.00 0.00 0.00
December 0.110873E+11 37147.39 26-DEC-16:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.278643E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 12937310.18 25754.65   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.110873E+11 37147.39   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_5_FLR_3 FAN COIL HEATING COIL

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.190443E+10 6188.60 15-JAN-16:01 0.00 0.00 0.00 0.00 0.00
February 0.116794E+10 6073.13 27-FEB-09:02 0.00 0.00 0.00 0.00 0.00
March 0.762834E+09 6177.00 02-MAR-09:02 0.00 0.00 0.00 0.00 0.00
April 98787588.36 2830.91 20-APR-08:04 0.00 0.00 0.00 0.00 0.00
May 2389726.19 2372.37 23-MAY-08:04 0.00 0.00 0.00 0.00 0.00
June 353328.58 1521.37 22-JUN-08:04 0.00 0.00 0.00 0.00 0.00
July 479573.89 2471.48 07-JUL-08:04 0.00 0.00 0.00 0.00 0.00
August 1664357.02 2431.76 24-AUG-08:04 0.00 0.00 0.00 0.00 0.00
September 1468500.56 2163.43 22-SEP-08:04 0.00 0.00 0.00 0.00 0.00
October 63351801.66 3454.34 15-OCT-18:03 0.00 0.00 0.00 0.00 0.00
November 0.104653E+10 6224.09 27-NOV-09:02 0.00 0.00 0.00 0.00 0.00
December 0.248189E+10 6228.32 26-DEC-19:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.753213E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 353328.58 1521.37   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.248189E+10 6228.32   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_6_FLR_3 FAN COIL HEATING COIL

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.282500E+10 6209.65 26-JAN-19:02 0.00 0.00 0.00 0.00 0.00
February 0.168251E+10 6153.86 01-FEB-19:02 0.00 0.00 0.00 0.00 0.00
March 0.101237E+10 6206.36 02-MAR-09:02 0.00 0.00 0.00 0.00 0.00
April 0.124237E+09 3839.98 11-APR-15:03 0.00 0.00 0.00 0.00 0.00
May 3111393.01 2435.20 23-MAY-08:04 0.00 0.00 0.00 0.00 0.00
June 330030.06 1534.24 22-JUN-08:04 0.00 0.00 0.00 0.00 0.00
July 489985.29 2499.42 07-JUL-08:04 0.00 0.00 0.00 0.00 0.00
August 1877198.88 2675.02 17-AUG-18:04 0.00 0.00 0.00 0.00 0.00
September 4415368.15 2457.17 22-SEP-08:04 0.00 0.00 0.00 0.00 0.00
October 0.129076E+09 3554.57 31-OCT-18:03 0.00 0.00 0.00 0.00 0.00
November 0.153638E+10 6213.27 27-NOV-19:01 0.00 0.00 0.00 0.00 0.00
December 0.356594E+10 6213.59 03-DEC-16:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.108857E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 330030.06 1534.24   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.356594E+10 6213.59   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_1_FLR_6 FAN COIL HEATING COIL

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.722460E+09 1944.64 15-JAN-16:01 0.00 0.00 0.00 0.00 0.00
February 0.491164E+09 1943.07 09-FEB-09:02 0.00 0.00 0.00 0.00 0.00
March 0.316681E+09 1943.13 01-MAR-09:02 0.00 0.00 0.00 0.00 0.00
April 49305713.66 1905.38 11-APR-08:62 0.00 0.00 0.00 0.00 0.00
May 2179858.55 791.88 10-MAY-08:03 0.00 0.00 0.00 0.00 0.00
June 406689.73 370.60 25-JUN-08:04 0.00 0.00 0.00 0.00 0.00
July 593231.16 619.73 21-JUL-08:04 0.00 0.00 0.00 0.00 0.00
August 873012.70 643.99 30-AUG-08:03 0.00 0.00 0.00 0.00 0.00
September 1703395.15 708.01 26-SEP-08:03 0.00 0.00 0.00 0.00 0.00
October 25705464.46 949.97 28-OCT-08:03 0.00 0.00 0.00 0.00 0.00
November 0.397406E+09 1943.50 28-NOV-09:02 0.00 0.00 0.00 0.00 0.00
December 0.939057E+09 1943.78 03-DEC-09:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.294754E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 406689.73 370.60   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.939057E+09 1944.64   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_2_FLR_6 FAN COIL HEATING COIL

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.102940E+10 1940.52 15-JAN-16:01 0.00 0.00 0.00 0.00 0.00
February 0.684877E+09 1939.36 17-FEB-09:02 0.00 0.00 0.00 0.00 0.00
March 0.410280E+09 1939.10 01-MAR-09:02 0.00 0.00 0.00 0.00 0.00
April 59403912.41 1906.43 11-APR-08:62 0.00 0.00 0.00 0.00 0.00
May 2239393.97 803.40 10-MAY-08:03 0.00 0.00 0.00 0.00 0.00
June 340077.35 416.28 30-JUN-08:04 0.00 0.00 0.00 0.00 0.00
July 545722.22 653.23 21-JUL-08:04 0.00 0.00 0.00 0.00 0.00
August 956577.61 764.48 30-AUG-08:03 0.00 0.00 0.00 0.00 0.00
September 2852158.21 781.41 12-SEP-08:03 0.00 0.00 0.00 0.00 0.00
October 48114159.32 1871.63 25-OCT-08:62 0.00 0.00 0.00 0.00 0.00
November 0.578366E+09 1939.74 30-NOV-09:01 0.00 0.00 0.00 0.00 0.00
December 0.130236E+10 1939.69 14-DEC-09:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.411973E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 340077.35 416.28   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.130236E+10 1940.52   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.154729E+10 9104.82 15-JAN-16:01 0.00 0.00 0.00 0.00 0.00
February 0.107487E+10 8754.12 02-FEB-09:02 0.00 0.00 0.00 0.00 0.00
March 0.783393E+09 9158.67 02-MAR-09:02 0.00 0.00 0.00 0.00 0.00
April 0.135345E+09 6619.06 11-APR-08:62 0.00 0.00 0.00 0.00 0.00
May 10216121.59 4314.50 19-MAY-08:04 0.00 0.00 0.00 0.00 0.00
June 6373056.73 4023.64 27-JUN-08:04 0.00 0.00 0.00 0.00 0.00
July 6656137.65 4294.53 07-JUL-08:04 0.00 0.00 0.00 0.00 0.00
August 6921374.13 3976.89 02-AUG-08:04 0.00 0.00 0.00 0.00 0.00
September 5543709.83 3804.68 13-SEP-08:04 0.00 0.00 0.00 0.00 0.00
October 21320459.34 3790.55 15-OCT-08:04 0.00 0.00 0.00 0.00 0.00
November 0.886317E+09 9142.63 27-NOV-09:02 0.00 0.00 0.00 0.00 0.00
December 0.220624E+10 9244.17 26-DEC-19:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.669049E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 5543709.83 3790.55   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.220624E+10 9244.17   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: VAV WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.201108E+11 0.201108E+11 192380.40 03-JAN-17:00 192380.40 0.00
February 0.00 0.00 0.759769E+11 0.759769E+11 233415.98 20-FEB-11:50 233415.98 0.00
March 0.00 0.00 0.145448E+12 0.145448E+12 260781.39 14-MAR-17:13 260781.39 0.00
April 0.00 0.00 0.382942E+12 0.382942E+12 333076.85 19-APR-18:10 333076.85 0.09
May 0.00 0.00 0.597793E+12 0.591323E+12 410770.20 28-MAY-10:35 314247.27 0.28
June 0.00 0.00 0.736192E+12 0.720033E+12 450614.15 19-JUN-18:10 294508.50 0.57
July 0.00 0.00 0.981701E+12 0.745816E+12 677044.84 21-JUL-06:30 218290.62 0.99
August 0.00 0.00 0.808393E+12 0.700978E+12 593511.92 01-AUG-21:00 250046.73 0.94
September 0.00 0.00 0.694503E+12 0.565639E+12 536772.07 22-SEP-02:00 191855.83 0.81
October 0.00 0.00 0.364337E+12 0.340216E+12 466255.17 03-OCT-20:30 245848.47 0.48
November 0.00 0.00 0.944464E+11 0.944464E+11 247738.69 03-NOV-16:00 247738.69 0.04
December 0.00 0.00 0.146740E+11 0.146740E+11 127386.92 10-DEC-15:00 127386.92 0.00
                 
Annual Sum or Average 0.00 0.00 0.491652E+13 0.439760E+13       0.35
Minimum of Months 0.00 0.00 0.146740E+11 0.146740E+11 127386.92   127386.92 0.00
Maximum of Months 0.00 0.00 0.981701E+12 0.745816E+12 677044.84   333076.85 0.99



Table of Contents

Report: CoilReportMonthly

For: FLR_3_DOAS COOLING COIL

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.122869E+10 0.122869E+10 18651.05 03-JAN-15:00 18651.05 0.00
February 0.00 0.00 0.621055E+10 0.621055E+10 24890.15 20-FEB-15:00 24890.15 0.00
March 0.00 0.00 0.124469E+11 0.124469E+11 28566.40 21-MAR-16:00 28566.40 0.00
April 0.00 0.00 0.399969E+11 0.399969E+11 44409.17 21-APR-15:00 44409.17 0.08
May 0.00 0.00 0.693058E+11 0.674714E+11 50585.42 19-MAY-14:00 50585.42 0.26
June 0.00 0.00 0.932452E+11 0.894911E+11 58655.85 02-JUN-17:00 58655.85 0.50
July 0.00 0.00 0.127410E+12 0.896819E+11 65741.82 20-JUL-16:00 26241.67 0.98
August 0.00 0.00 0.102279E+12 0.830713E+11 58860.95 02-AUG-12:00 38266.78 0.88
September 0.00 0.00 0.814589E+11 0.629435E+11 55192.93 14-SEP-10:00 26667.06 0.78
October 0.00 0.00 0.377637E+11 0.336702E+11 52564.31 03-OCT-14:00 44755.97 0.42
November 0.00 0.00 0.755815E+10 0.755815E+10 26388.16 03-NOV-16:00 26388.16 0.02
December 0.00 0.00 0.724489E+09 0.724489E+09 11238.20 10-DEC-15:00 11238.20 0.00
                 
Annual Sum or Average 0.00 0.00 0.579628E+12 0.494495E+12       0.33
Minimum of Months 0.00 0.00 0.724489E+09 0.724489E+09 11238.20   11238.20 0.00
Maximum of Months 0.00 0.00 0.127410E+12 0.896819E+11 65741.82   58655.85 0.98



Table of Contents

Report: CoilReportMonthly

For: ROOM_1_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.722115E+09 0.720641E+09 18116.34 01-JAN-16:02 18116.34 0.00
February 0.00 0.00 0.120688E+10 0.120552E+10 18089.20 18-FEB-16:01 18089.20 0.00
March 0.00 0.00 0.226720E+10 0.225421E+10 18096.24 12-MAR-15:01 18096.24 0.01
April 0.00 0.00 0.546037E+10 0.512260E+10 18122.49 17-APR-18:01 18122.49 0.12
May 0.00 0.00 0.876234E+10 0.753288E+10 18730.83 28-MAY-08:61 15791.43 0.32
June 0.00 0.00 0.115697E+11 0.920445E+10 18607.62 28-JUN-08:62 14858.64 0.59
July 0.00 0.00 0.127687E+11 0.777143E+10 21980.88 19-JUL-08:62 13086.78 0.95
August 0.00 0.00 0.113529E+11 0.718810E+10 20204.96 02-AUG-08:61 15063.62 0.91
September 0.00 0.00 0.100953E+11 0.634610E+10 20228.89 09-SEP-08:61 15043.87 0.86
October 0.00 0.00 0.608411E+10 0.415205E+10 19090.18 04-OCT-08:62 14556.48 0.56
November 0.00 0.00 0.206946E+10 0.188067E+10 18123.27 04-NOV-15:01 18123.27 0.08
December 0.00 0.00 0.415065E+09 0.415065E+09 18086.00 07-DEC-16:01 18086.00 0.00
                 
Annual Sum or Average 0.00 0.00 0.727741E+11 0.537937E+11       0.37
Minimum of Months 0.00 0.00 0.415065E+09 0.415065E+09 18086.00   13086.78 0.00
Maximum of Months 0.00 0.00 0.127687E+11 0.920445E+10 21980.88   18123.27 0.95



Table of Contents

Report: CoilReportMonthly

For: ROOM_2_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.127140E+09 0.126798E+09 17677.89 12-JAN-16:01 17677.89 0.00
February 0.00 0.00 0.423650E+09 0.422969E+09 17958.79 18-FEB-16:01 17958.79 0.00
March 0.00 0.00 0.136437E+10 0.135368E+10 17961.97 12-MAR-15:01 17961.97 0.01
April 0.00 0.00 0.466002E+10 0.436151E+10 17992.74 17-APR-18:01 17992.74 0.12
May 0.00 0.00 0.854167E+10 0.733311E+10 18575.57 28-MAY-08:61 15765.81 0.32
June 0.00 0.00 0.116408E+11 0.929468E+10 18500.58 28-JUN-08:62 14940.58 0.59
July 0.00 0.00 0.127116E+11 0.776970E+10 21770.64 19-JUL-08:62 13007.86 0.95
August 0.00 0.00 0.107086E+11 0.667650E+10 20137.60 02-AUG-08:61 14912.58 0.90
September 0.00 0.00 0.847497E+10 0.499668E+10 20082.86 23-SEP-18:01 14542.33 0.83
October 0.00 0.00 0.406830E+10 0.259372E+10 18881.85 04-OCT-08:62 14216.10 0.48
November 0.00 0.00 0.656897E+09 0.558419E+09 17991.11 09-NOV-16:01 17991.11 0.05
December 0.00 0.00 49598812.63 49598812.63 17361.38 16-DEC-16:02 17361.38 0.00
                 
Annual Sum or Average 0.00 0.00 0.634276E+11 0.455374E+11       0.36
Minimum of Months 0.00 0.00 49598812.63 49598812.63 17361.38   13007.86 0.00
Maximum of Months 0.00 0.00 0.127116E+11 0.929468E+10 21770.64   17992.74 0.95



Table of Contents

Report: CoilReportMonthly

For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.187338E+11 0.187338E+11 42039.10 12-JAN-14:30 42039.10 0.00
February 0.00 0.00 0.186891E+11 0.186666E+11 40287.64 07-FEB-13:40 40287.64 0.00
March 0.00 0.00 0.178191E+11 0.176597E+11 32128.75 16-MAR-13:30 32128.75 0.01
April 0.00 0.00 0.286378E+11 0.275079E+11 31143.23 03-APR-14:00 31143.23 0.07
May 0.00 0.00 0.372407E+11 0.314968E+11 32772.64 19-MAY-20:20 32772.64 0.25
June 0.00 0.00 0.490596E+11 0.377855E+11 37380.51 17-JUN-18:25 37380.51 0.50
July 0.00 0.00 0.582359E+11 0.294422E+11 40363.45 02-JUL-20:40 40363.45 0.99
August 0.00 0.00 0.552429E+11 0.324876E+11 40451.04 06-AUG-19:05 36600.03 0.88
September 0.00 0.00 0.589986E+11 0.396780E+11 50495.60 19-SEP-13:10 39667.71 0.78
October 0.00 0.00 0.499915E+11 0.393898E+11 54374.54 22-OCT-13:40 46505.12 0.48
November 0.00 0.00 0.320013E+11 0.310643E+11 48108.55 09-NOV-13:50 48108.55 0.06
December 0.00 0.00 0.142146E+11 0.142146E+11 38082.67 16-DEC-13:40 38082.67 0.00
                 
Annual Sum or Average 0.00 0.00 0.438865E+12 0.338127E+12       0.34
Minimum of Months 0.00 0.00 0.142146E+11 0.142146E+11 31143.23   31143.23 0.00
Maximum of Months 0.00 0.00 0.589986E+11 0.396780E+11 54374.54   48108.55 0.99



Table of Contents

Report: CoilReportMonthly

For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.500924E+10 0.470017E+10 109209.76 13-JAN-19:02 109209.76 0.02
February 0.00 0.00 0.952481E+10 0.888985E+10 112954.08 20-FEB-09:01 112954.08 0.05
March 0.00 0.00 0.182443E+11 0.178289E+11 115105.18 15-MAR-18:01 115105.18 0.02
April 0.00 0.00 0.405932E+11 0.383877E+11 120021.63 28-APR-18:01 120021.63 0.10
May 0.00 0.00 0.650000E+11 0.570325E+11 120151.00 28-MAY-08:61 107700.72 0.27
June 0.00 0.00 0.833085E+11 0.686231E+11 120394.27 28-JUN-08:62 99367.24 0.53
July 0.00 0.00 0.951723E+11 0.627338E+11 144018.26 19-JUL-08:62 87423.24 0.88
August 0.00 0.00 0.805664E+11 0.533239E+11 130555.13 02-AUG-08:61 100805.18 0.80
September 0.00 0.00 0.635069E+11 0.400279E+11 134191.44 23-SEP-18:01 93536.45 0.69
October 0.00 0.00 0.408900E+11 0.266324E+11 122745.68 04-OCT-08:62 97013.02 0.49
November 0.00 0.00 0.116994E+11 0.996162E+10 113548.45 11-NOV-09:01 113548.45 0.10
December 0.00 0.00 0.336045E+10 0.336045E+10 111643.78 09-DEC-09:01 111643.78 0.00
                 
Annual Sum or Average 0.00 0.00 0.516875E+12 0.391502E+12       0.33
Minimum of Months 0.00 0.00 0.336045E+10 0.336045E+10 109209.76   87423.24 0.00
Maximum of Months 0.00 0.00 0.951723E+11 0.686231E+11 144018.26   120021.63 0.88



Table of Contents

Report: CoilReportMonthly

For: ROOM_5_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.609955E+09 0.606864E+09 15862.15 12-JAN-16:01 15862.15 0.00
February 0.00 0.00 0.132023E+10 0.131359E+10 15875.09 08-FEB-09:01 15875.09 0.00
March 0.00 0.00 0.226342E+10 0.225232E+10 15859.33 07-MAR-09:01 15859.33 0.01
April 0.00 0.00 0.567944E+10 0.532430E+10 15874.38 28-APR-18:01 15874.38 0.13
May 0.00 0.00 0.888487E+10 0.763547E+10 15875.28 31-MAY-15:02 15875.28 0.33
June 0.00 0.00 0.118750E+11 0.952314E+10 16515.28 28-JUN-08:62 13847.20 0.62
July 0.00 0.00 0.130746E+11 0.807924E+10 19223.52 19-JUL-08:62 11380.51 0.97
August 0.00 0.00 0.115969E+11 0.739006E+10 17340.53 18-AUG-08:62 13382.53 0.94
September 0.00 0.00 0.101459E+11 0.640534E+10 17531.86 23-SEP-18:01 13278.85 0.89
October 0.00 0.00 0.564508E+10 0.389281E+10 17124.40 09-OCT-08:62 12718.95 0.55
November 0.00 0.00 0.190716E+10 0.176934E+10 15873.57 09-NOV-16:01 15873.57 0.07
December 0.00 0.00 0.436861E+09 0.436861E+09 15857.54 09-DEC-09:01 15857.54 0.00
                 
Annual Sum or Average 0.00 0.00 0.734393E+11 0.546294E+11       0.38
Minimum of Months 0.00 0.00 0.436861E+09 0.436861E+09 15857.54   11380.51 0.00
Maximum of Months 0.00 0.00 0.130746E+11 0.952314E+10 19223.52   15875.28 0.97



Table of Contents

Report: CoilReportMonthly

For: ROOM_6_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 59193127.27 58573583.11 10552.22 31-JAN-09:02 10552.22 0.00
February 0.00 0.00 0.469791E+09 0.464288E+09 15725.79 19-FEB-09:01 15725.79 0.00
March 0.00 0.00 0.130087E+10 0.129413E+10 15730.28 07-MAR-09:01 15730.28 0.01
April 0.00 0.00 0.483194E+10 0.450165E+10 15745.13 28-APR-18:01 15745.13 0.12
May 0.00 0.00 0.864751E+10 0.741971E+10 15746.09 31-MAY-15:02 15746.09 0.34
June 0.00 0.00 0.119435E+11 0.962191E+10 16208.19 28-JUN-08:62 13827.34 0.62
July 0.00 0.00 0.130094E+11 0.805837E+10 19021.43 19-JUL-08:62 11300.26 0.98
August 0.00 0.00 0.109444E+11 0.685094E+10 17179.76 18-AUG-08:62 13283.23 0.93
September 0.00 0.00 0.849771E+10 0.507713E+10 17570.65 23-SEP-18:01 12809.35 0.87
October 0.00 0.00 0.360323E+10 0.231320E+10 16961.32 09-OCT-08:62 12250.01 0.47
November 0.00 0.00 0.585874E+09 0.514753E+09 15738.93 11-NOV-09:01 15738.93 0.04
December 0.00 0.00 42956447.95 42956447.95 14941.11 09-DEC-09:01 14941.11 0.00
                 
Annual Sum or Average 0.00 0.00 0.639364E+11 0.462176E+11       0.37
Minimum of Months 0.00 0.00 42956447.95 42956447.95 10552.22   10552.22 0.00
Maximum of Months 0.00 0.00 0.130094E+11 0.962191E+10 19021.43   15746.09 0.98



Table of Contents

Report: CoilReportMonthly

For: ROOM_1_FLR_6 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.154784E+09 0.154121E+09 4910.70 01-JAN-16:02 4910.70 0.00
February 0.00 0.00 0.294475E+09 0.294142E+09 4903.32 18-FEB-16:01 4903.32 0.00
March 0.00 0.00 0.588547E+09 0.585991E+09 4905.26 12-MAR-15:01 4905.26 0.01
April 0.00 0.00 0.155247E+10 0.146061E+10 4912.21 17-APR-18:01 4912.21 0.12
May 0.00 0.00 0.252069E+10 0.218838E+10 5153.34 28-MAY-08:61 4252.16 0.32
June 0.00 0.00 0.336670E+10 0.271700E+10 5157.48 28-JUN-08:62 3976.40 0.60
July 0.00 0.00 0.371169E+10 0.236371E+10 6142.55 19-JUL-08:62 3436.52 0.96
August 0.00 0.00 0.328258E+10 0.215465E+10 5554.53 02-AUG-08:61 4039.46 0.92
September 0.00 0.00 0.285224E+10 0.186364E+10 5617.95 09-SEP-08:61 4001.36 0.86
October 0.00 0.00 0.165147E+10 0.115670E+10 5258.38 04-OCT-08:62 3869.90 0.53
November 0.00 0.00 0.511879E+09 0.466981E+09 4912.59 04-NOV-15:01 4912.59 0.07
December 0.00 0.00 84102887.94 84102887.94 4908.03 04-DEC-16:01 4908.03 0.00
                 
Annual Sum or Average 0.00 0.00 0.205716E+11 0.154900E+11       0.37
Minimum of Months 0.00 0.00 84102887.94 84102887.94 4903.32   3436.52 0.00
Maximum of Months 0.00 0.00 0.371169E+10 0.271700E+10 6142.55   4912.59 0.96



Table of Contents

Report: CoilReportMonthly

For: ROOM_2_FLR_6 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 23238703.27 23161350.58 4823.13 12-JAN-16:01 4823.13 0.00
February 0.00 0.00 99472589.74 99344177.58 4862.94 18-FEB-16:01 4862.94 0.00
March 0.00 0.00 0.348853E+09 0.346933E+09 4863.71 04-MAR-16:01 4863.71 0.01
April 0.00 0.00 0.133726E+10 0.125408E+10 4871.93 28-APR-18:01 4871.93 0.12
May 0.00 0.00 0.246120E+10 0.213130E+10 5099.76 28-MAY-08:61 4231.25 0.32
June 0.00 0.00 0.338670E+10 0.274237E+10 5131.39 28-JUN-08:62 3998.39 0.60
July 0.00 0.00 0.369689E+10 0.236125E+10 6076.02 19-JUL-08:62 3414.32 0.96
August 0.00 0.00 0.311223E+10 0.200664E+10 5543.01 02-AUG-08:61 3987.28 0.92
September 0.00 0.00 0.241963E+10 0.148379E+10 5544.28 09-SEP-08:61 3961.24 0.84
October 0.00 0.00 0.111096E+10 0.727581E+09 4954.38 03-OCT-18:01 4308.88 0.44
November 0.00 0.00 0.158680E+09 0.135959E+09 4871.62 09-NOV-16:01 4871.62 0.05
December 0.00 0.00 8212687.31 8212687.31 4345.74 16-DEC-16:02 4345.74 0.00
                 
Annual Sum or Average 0.00 0.00 0.181633E+11 0.133206E+11       0.36
Minimum of Months 0.00 0.00 8212687.31 8212687.31 4345.74   3414.32 0.00
Maximum of Months 0.00 0.00 0.369689E+10 0.274237E+10 6076.02   4871.93 0.96



Table of Contents

Report: CoilReportMonthly

For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.457271E+10 0.453936E+10 22324.09 01-JAN-16:02 22324.09 0.01
February 0.00 0.00 0.479250E+10 0.476592E+10 22304.13 14-FEB-16:01 22304.13 0.02
March 0.00 0.00 0.498379E+10 0.494855E+10 22299.62 12-MAR-15:01 22299.62 0.01
April 0.00 0.00 0.817043E+10 0.766155E+10 22325.97 26-APR-18:01 22325.97 0.13
May 0.00 0.00 0.112351E+11 0.947273E+10 23009.17 28-MAY-08:61 19625.03 0.35
June 0.00 0.00 0.149190E+11 0.116596E+11 22861.68 28-JUN-08:62 17933.58 0.62
July 0.00 0.00 0.174206E+11 0.106592E+11 27818.64 19-JUL-08:62 15683.33 0.95
August 0.00 0.00 0.164532E+11 0.107000E+11 25022.47 02-AUG-08:61 18548.79 0.93
September 0.00 0.00 0.162297E+11 0.110664E+11 25483.19 23-SEP-18:01 18283.10 0.87
October 0.00 0.00 0.126282E+11 0.956996E+10 23681.13 04-OCT-08:62 18206.80 0.62
November 0.00 0.00 0.730636E+10 0.695177E+10 22327.19 09-NOV-16:01 22327.19 0.11
December 0.00 0.00 0.402041E+10 0.401746E+10 22311.90 04-DEC-16:01 22311.90 0.00
                 
Annual Sum or Average 0.00 0.00 0.122732E+12 0.960124E+11       0.39
Minimum of Months 0.00 0.00 0.402041E+10 0.401746E+10 22299.62   15683.33 0.00
Maximum of Months 0.00 0.00 0.174206E+11 0.116596E+11 27818.64   22327.19 0.95



Table of Contents

Report: PlantLoopDemandReportMonthly

For: HEATSYS1

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:05 47312.08 160680.34 27-JAN-09:02
February 0.00 0.00 01-FEB-00:03 42108.64 155354.24 03-FEB-07:10
March 0.00 0.00 01-MAR-00:03 36579.44 155356.75 02-MAR-09:02
April 0.00 0.00 01-APR-00:10 22622.22 91791.34 11-APR-08:62
May 0.00 0.00 01-MAY-00:10 16813.78 78325.35 23-MAY-08:04
June 0.00 0.00 01-JUN-00:10 13907.61 68798.46 23-JUN-08:04
July 0.00 0.00 01-JUL-00:10 11502.78 69610.16 21-JUL-10:35
August 0.00 0.00 01-AUG-00:10 10211.06 66339.21 18-AUG-10:35
September 0.00 0.00 01-SEP-00:10 9603.50 69422.63 15-SEP-08:04
October 0.00 0.00 01-OCT-00:10 14586.99 88051.01 13-OCT-08:05
November 0.00 0.00 01-NOV-00:10 32498.72 148981.37 28-NOV-09:02
December 0.00 0.00 01-DEC-00:03 52039.07 156975.75 27-DEC-09:02
             
Annual Sum or Average 0.00     25749.05    
Minimum of Months 0.00 0.00   9603.50 66339.21  
Maximum of Months 0.00 0.00   52039.07 160680.34  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: COOLSYS1

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 22553.43 314961.77 03-JAN-16:01 0.00 0.00 01-JAN-00:05
February 53722.21 463141.95 20-FEB-16:01 0.00 0.00 01-FEB-00:03
March 82660.88 481240.13 15-MAR-18:01 0.00 0.00 01-MAR-00:03
April 209683.57 605429.93 19-APR-18:03 0.00 0.00 01-APR-00:10
May 314878.61 640072.46 21-MAY-18:03 0.00 0.00 01-MAY-00:10
June 406754.43 738298.13 19-JUN-18:03 0.00 0.00 01-JUN-00:10
July 509212.93 943292.64 19-JUL-08:62 0.00 0.00 01-JUL-00:10
August 425135.68 802634.21 02-AUG-18:03 0.00 0.00 01-AUG-00:10
September 378249.18 713539.79 03-SEP-18:03 0.00 0.00 01-SEP-00:10
October 204755.95 698127.49 04-OCT-18:03 0.00 0.00 01-OCT-00:10
November 66170.14 469389.97 09-NOV-16:01 0.00 0.00 01-NOV-00:10
December 17252.46 223789.65 10-DEC-16:01 0.00 0.00 01-DEC-00:03
             
Annual Sum or Average 225205.18     0.00    
Minimum of Months 17252.46 223789.65   0.00 0.00  
Maximum of Months 509212.93 943292.64   0.00 0.00  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:05 25474.12 51727.49 30-JAN-07:50
February 0.00 0.00 01-FEB-00:03 25455.78 51721.75 01-FEB-07:50
March 0.00 0.00 01-MAR-00:03 24601.52 50754.91 01-MAR-07:20
April 0.00 0.00 01-APR-00:10 23055.20 47839.30 03-APR-06:40
May 0.00 0.00 01-MAY-00:10 21280.26 44486.96 01-MAY-06:20
June 0.00 0.00 01-JUN-00:10 19743.58 40782.56 01-JUN-06:15
July 0.00 0.00 01-JUL-00:10 18838.55 38099.17 03-JUL-06:15
August 0.00 0.00 01-AUG-00:10 18863.50 38237.61 31-AUG-06:40
September 0.00 0.00 01-SEP-00:10 19756.74 40797.67 29-SEP-06:15
October 0.00 0.00 01-OCT-00:10 21296.80 44533.53 31-OCT-06:50
November 0.00 0.00 01-NOV-00:10 23074.28 48075.30 30-NOV-08:00
December 0.00 0.00 01-DEC-00:03 24599.56 50643.54 29-DEC-08:00
             
Annual Sum or Average 0.00     22151.34    
Minimum of Months 0.00 0.00   18838.55 38099.17  
Maximum of Months 0.00 0.00   25474.12 51727.49  



Table of Contents

Report: FanReportMonthly

For: FLR_3_DOAS FAN

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.587890E+10 1.01 2194.93 01-JAN-00:05 1.01
February 0.530997E+10 1.01 2194.93 01-FEB-00:03 1.01
March 0.587890E+10 1.01 2194.93 01-MAR-00:03 1.01
April 0.568926E+10 1.01 2194.93 01-APR-00:10 1.02
May 0.587890E+10 1.01 2194.93 01-MAY-00:10 1.01
June 0.568926E+10 1.01 2194.93 01-JUN-00:10 1.01
July 0.587890E+10 1.00 2194.93 01-JUL-00:10 1.00
August 0.587890E+10 1.00 2194.93 01-AUG-00:10 1.00
September 0.568926E+10 1.00 2194.93 01-SEP-00:10 1.00
October 0.587890E+10 1.01 2194.93 01-OCT-00:10 1.01
November 0.568926E+10 1.01 2194.93 01-NOV-00:10 1.01
December 0.587890E+10 1.01 2194.93 01-DEC-00:03 1.01
           
Annual Sum or Average 0.692193E+11 1.01      
Minimum of Months 0.530997E+10 1.00 2194.93   1.00
Maximum of Months 0.587890E+10 1.01 2194.93   1.02



Table of Contents

Report: FanReportMonthly

For: VAV WITH REHEAT FAN

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.150076E+12 2.12 56081.31 01-JAN-11:50 2.11
February 0.135562E+12 2.12 56081.31 01-FEB-19:07 2.13
March 0.150094E+12 2.12 56081.31 01-MAR-19:07 2.13
April 0.145271E+12 2.12 56081.31 01-APR-09:20 2.12
May 0.150126E+12 2.11 56081.31 01-MAY-09:20 2.12
June 0.145296E+12 2.10 56081.31 01-JUN-07:45 2.12
July 0.150136E+12 2.09 56081.31 01-JUL-08:00 2.09
August 0.150131E+12 2.10 56081.31 01-AUG-06:30 2.09
September 0.145286E+12 2.10 56081.31 01-SEP-06:40 2.09
October 0.150108E+12 2.10 56081.31 01-OCT-10:01 2.11
November 0.145246E+12 2.12 56081.31 01-NOV-10:35 2.10
December 0.150073E+12 2.12 56081.31 01-DEC-19:06 2.12
           
Annual Sum or Average 0.176740E+13 2.11      
Minimum of Months 0.135562E+12 2.09 56081.31   2.09
Maximum of Months 0.150136E+12 2.12 56081.31   2.13



Table of Contents

Report: FanReportMonthly

For: LAUNDRY_FLR_1 EXHAUST FAN

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.493775E+09 0.74 184.35 01-JAN-00:05 0.74
February 0.445990E+09 0.74 184.35 01-FEB-00:03 0.74
March 0.493775E+09 0.74 184.35 01-MAR-00:03 0.74
April 0.477847E+09 0.74 184.35 01-APR-00:10 0.74
May 0.493775E+09 0.74 184.35 01-MAY-00:10 0.74
June 0.477847E+09 0.73 184.35 01-JUN-00:10 0.74
July 0.493775E+09 0.73 184.35 01-JUL-00:10 0.73
August 0.493775E+09 0.73 184.35 01-AUG-00:10 0.73
September 0.477847E+09 0.73 184.35 01-SEP-00:10 0.73
October 0.493775E+09 0.73 184.35 01-OCT-00:10 0.74
November 0.477847E+09 0.74 184.35 01-NOV-00:10 0.74
December 0.493775E+09 0.74 184.35 01-DEC-00:03 0.74
           
Annual Sum or Average 0.581380E+10 0.74      
Minimum of Months 0.445990E+09 0.73 184.35   0.73
Maximum of Months 0.493775E+09 0.74 184.35   0.74



Table of Contents

Report: FanReportMonthly

For: LOBBY_FLR_1 EXHAUST FAN

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.00 0.00 0.00 01-JAN-00:05 0.00
February 0.00 0.00 0.00 01-FEB-00:03 0.00
March 0.00 0.00 0.00 01-MAR-00:03 0.00
April 0.00 0.00 0.00 01-APR-00:10 0.00
May 0.00 0.00 0.00 01-MAY-00:10 0.00
June 0.00 0.00 0.00 01-JUN-00:10 0.00
July 0.00 0.00 0.00 01-JUL-00:10 0.00
August 0.00 0.00 0.00 01-AUG-00:10 0.00
September 0.00 0.00 0.00 01-SEP-00:10 0.00
October 0.00 0.00 0.00 01-OCT-00:10 0.00
November 0.00 0.00 0.00 01-NOV-00:10 0.00
December 0.00 0.00 0.00 01-DEC-00:03 0.00
           
Annual Sum or Average 0.00 0.00      
Minimum of Months 0.00 0.00 0.00   0.00
Maximum of Months 0.00 0.00 0.00   0.00



Table of Contents

Report: FanReportMonthly

For: BANQUET_FLR_6 EXHAUST FAN

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.00 0.00 0.00 01-JAN-00:05 0.00
February 0.00 0.00 0.00 01-FEB-00:03 0.00
March 0.00 0.00 0.00 01-MAR-00:03 0.00
April 0.00 0.00 0.00 01-APR-00:10 0.00
May 0.00 0.00 0.00 01-MAY-00:10 0.00
June 0.00 0.00 0.00 01-JUN-00:10 0.00
July 0.00 0.00 0.00 01-JUL-00:10 0.00
August 0.00 0.00 0.00 01-AUG-00:10 0.00
September 0.00 0.00 0.00 01-SEP-00:10 0.00
October 0.00 0.00 0.00 01-OCT-00:10 0.00
November 0.00 0.00 0.00 01-NOV-00:10 0.00
December 0.00 0.00 0.00 01-DEC-00:03 0.00
           
Annual Sum or Average 0.00 0.00      
Minimum of Months 0.00 0.00 0.00   0.00
Maximum of Months 0.00 0.00 0.00   0.00



Table of Contents

Report: FanReportMonthly

For: DINING_FLR_6 EXHAUST FAN

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.00 0.00 0.00 01-JAN-00:05 0.00
February 0.00 0.00 0.00 01-FEB-00:03 0.00
March 0.00 0.00 0.00 01-MAR-00:03 0.00
April 0.00 0.00 0.00 01-APR-00:10 0.00
May 0.00 0.00 0.00 01-MAY-00:10 0.00
June 0.00 0.00 0.00 01-JUN-00:10 0.00
July 0.00 0.00 0.00 01-JUL-00:10 0.00
August 0.00 0.00 0.00 01-AUG-00:10 0.00
September 0.00 0.00 0.00 01-SEP-00:10 0.00
October 0.00 0.00 0.00 01-OCT-00:10 0.00
November 0.00 0.00 0.00 01-NOV-00:10 0.00
December 0.00 0.00 0.00 01-DEC-00:03 0.00
           
Annual Sum or Average 0.00 0.00      
Minimum of Months 0.00 0.00 0.00   0.00
Maximum of Months 0.00 0.00 0.00   0.00



Table of Contents

Report: FanReportMonthly

For: KITCHEN_FLR_6 EXHAUST FAN

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.279806E+10 0.52 1474.84 01-JAN-07:10 0.74
February 0.252728E+10 0.52 1474.84 01-FEB-07:10 0.74
March 0.279806E+10 0.52 1474.84 01-MAR-07:10 0.74
April 0.270780E+10 0.52 1474.84 01-APR-06:10 0.74
May 0.279806E+10 0.52 1474.84 01-MAY-06:05 0.74
June 0.270780E+10 0.52 1474.84 01-JUN-06:05 0.74
July 0.279806E+10 0.52 1474.84 01-JUL-06:10 0.73
August 0.279806E+10 0.52 1474.84 01-AUG-06:05 0.73
September 0.270780E+10 0.52 1474.84 01-SEP-06:05 0.73
October 0.279806E+10 0.52 1474.84 01-OCT-06:10 0.73
November 0.270780E+10 0.52 1474.84 01-NOV-06:05 0.73
December 0.279806E+10 0.52 1474.84 01-DEC-07:05 0.74
           
Annual Sum or Average 0.329449E+11 0.52      
Minimum of Months 0.252728E+10 0.52 1474.84   0.73
Maximum of Months 0.279806E+10 0.52 1474.84   0.74



Table of Contents

Report: FanReportMonthly

For: ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.540703E+09 1.19 2129.05 01-JAN-16:02 1.59
February 0.465066E+09 1.23 2129.05 01-FEB-09:02 1.60
March 0.501955E+09 1.26 2129.05 01-MAR-09:02 1.60
April 0.715629E+09 1.39 2129.05 01-APR-15:01 1.60
May 0.105698E+10 1.46 2129.05 01-MAY-15:01 1.60
June 0.134764E+10 1.51 2129.05 01-JUN-08:61 1.60
July 0.134748E+10 1.51 2129.05 01-JUL-08:61 1.58
August 0.125599E+10 1.48 2129.05 01-AUG-08:61 1.58
September 0.112016E+10 1.49 2129.05 01-SEP-08:62 1.58
October 0.731670E+09 1.38 2129.05 01-OCT-08:62 1.59
November 0.521232E+09 1.30 2129.05 02-NOV-15:01 1.59
December 0.608036E+09 1.19 2129.05 02-DEC-09:02 1.60
           
Annual Sum or Average 0.102125E+11 1.37      
Minimum of Months 0.465066E+09 1.19 2129.05   1.58
Maximum of Months 0.134764E+10 1.51 2129.05   1.60



Table of Contents

Report: FanReportMonthly

For: ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.637136E+09 1.15 2113.77 01-JAN-16:02 1.59
February 0.484885E+09 1.16 2113.77 01-FEB-09:02 1.60
March 0.456437E+09 1.17 2113.77 01-MAR-09:02 1.60
April 0.629013E+09 1.32 2113.77 01-APR-15:01 1.60
May 0.103214E+10 1.44 2113.77 01-MAY-15:01 1.60
June 0.135869E+10 1.51 2113.77 01-JUN-08:61 1.60
July 0.134328E+10 1.51 2113.77 01-JUL-08:61 1.58
August 0.118166E+10 1.47 2113.77 01-AUG-08:61 1.58
September 0.949617E+09 1.44 2113.77 01-SEP-08:62 1.58
October 0.517759E+09 1.26 2113.77 01-OCT-15:01 1.59
November 0.461066E+09 1.17 2113.77 02-NOV-08:62 1.59
December 0.762239E+09 1.18 2113.77 01-DEC-09:02 1.60
           
Annual Sum or Average 0.981391E+10 1.32      
Minimum of Months 0.456437E+09 1.15 2113.77   1.58
Maximum of Months 0.135869E+10 1.51 2113.77   1.60



Table of Contents

Report: FanReportMonthly

For: ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.206039E+10 0.71 3973.35 12-JAN-14:30 1.60
February 0.207588E+10 0.85 3829.45 07-FEB-13:40 1.60
March 0.205961E+10 0.84 3150.58 16-MAR-13:30 1.60
April 0.320742E+10 1.21 3066.36 04-APR-13:30 1.60
May 0.405904E+10 1.45 3195.96 19-MAY-20:20 1.60
June 0.510173E+10 1.57 3652.29 18-JUN-20:03 1.59
July 0.542736E+10 1.58 3938.37 02-JUL-19:40 1.59
August 0.538554E+10 1.56 3872.80 06-AUG-19:05 1.59
September 0.569742E+10 1.54 6724.91 19-SEP-13:10 1.59
October 0.514611E+10 1.40 7324.17 22-OCT-13:20 1.59
November 0.334255E+10 0.95 6568.71 10-NOV-11:35 1.59
December 0.164376E+10 0.65 3653.81 16-DEC-13:40 1.61
           
Annual Sum or Average 0.452068E+11 1.19      
Minimum of Months 0.164376E+10 0.65 3066.36   1.59
Maximum of Months 0.569742E+10 1.58 7324.17   1.61



Table of Contents

Report: FanReportMonthly

For: ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.266236E+10 1.13 13961.11 05-JAN-09:02 1.61
February 0.255771E+10 1.13 13961.11 01-FEB-09:02 1.60
March 0.297381E+10 1.13 13961.11 01-MAR-16:01 1.61
April 0.492843E+10 1.15 13961.11 01-APR-08:62 1.60
May 0.776848E+10 1.26 13961.11 01-MAY-15:01 1.60
June 0.987675E+10 1.39 13961.11 01-JUN-08:61 1.60
July 0.101578E+11 1.40 13961.11 01-JUL-08:61 1.59
August 0.887603E+10 1.32 13961.11 01-AUG-08:61 1.58
September 0.685595E+10 1.23 13961.11 01-SEP-08:62 1.58
October 0.461932E+10 1.14 13961.11 01-OCT-08:62 1.59
November 0.253393E+10 1.13 13961.11 03-NOV-15:02 1.59
December 0.333189E+10 1.13 13961.11 02-DEC-16:02 1.60
           
Annual Sum or Average 0.671425E+11 1.21      
Minimum of Months 0.253393E+10 1.13 13961.11   1.58
Maximum of Months 0.101578E+11 1.40 13961.11   1.61



Table of Contents

Report: FanReportMonthly

For: ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.490110E+09 1.14 1864.23 01-JAN-16:02 1.59
February 0.429992E+09 1.23 1864.23 01-FEB-19:02 1.60
March 0.475939E+09 1.31 1864.23 01-MAR-19:02 1.60
April 0.720706E+09 1.48 1864.23 01-APR-08:62 1.60
May 0.105510E+10 1.54 1864.23 01-MAY-08:62 1.60
June 0.139904E+10 1.56 1864.23 01-JUN-08:61 1.60
July 0.138785E+10 1.55 1864.23 01-JUL-08:61 1.59
August 0.128276E+10 1.53 1864.23 01-AUG-08:61 1.58
September 0.110928E+10 1.53 1864.23 01-SEP-08:62 1.58
October 0.680801E+09 1.41 1864.23 01-OCT-08:62 1.59
November 0.484420E+09 1.30 1864.23 02-NOV-15:01 1.59
December 0.558495E+09 1.15 1864.23 02-DEC-16:02 1.60
           
Annual Sum or Average 0.100745E+11 1.39      
Minimum of Months 0.429992E+09 1.14 1864.23   1.58
Maximum of Months 0.139904E+10 1.56 1864.23   1.60



Table of Contents

Report: FanReportMonthly

For: ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.584721E+09 1.13 1849.04 04-JAN-19:02 1.60
February 0.425193E+09 1.14 1849.04 01-FEB-09:02 1.60
March 0.409004E+09 1.14 1849.04 01-MAR-16:01 1.61
April 0.631275E+09 1.40 1849.04 01-APR-08:62 1.60
May 0.103003E+10 1.53 1849.04 01-MAY-08:62 1.60
June 0.140935E+10 1.56 1849.04 01-JUN-08:61 1.60
July 0.138521E+10 1.55 1849.04 01-JUL-08:61 1.59
August 0.120916E+10 1.52 1849.04 01-AUG-08:61 1.58
September 0.924760E+09 1.51 1849.04 01-SEP-08:62 1.58
October 0.466593E+09 1.26 1849.04 01-OCT-08:62 1.59
November 0.421857E+09 1.14 1849.04 02-NOV-08:62 1.59
December 0.703675E+09 1.16 1849.04 01-DEC-16:01 1.60
           
Annual Sum or Average 0.960083E+10 1.34      
Minimum of Months 0.409004E+09 1.13 1849.04   1.58
Maximum of Months 0.140935E+10 1.56 1849.04   1.61



Table of Contents

Report: FanReportMonthly

For: ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.170737E+09 1.21 577.17 01-JAN-16:02 1.59
February 0.143466E+09 1.23 577.17 01-FEB-09:02 1.60
March 0.150400E+09 1.27 577.17 01-MAR-09:02 1.60
April 0.205474E+09 1.41 577.17 01-APR-15:01 1.60
May 0.304140E+09 1.48 577.17 01-MAY-15:01 1.60
June 0.396985E+09 1.53 577.17 01-JUN-08:61 1.60
July 0.397311E+09 1.52 577.17 01-JUL-08:61 1.58
August 0.368654E+09 1.50 577.17 01-AUG-08:61 1.58
September 0.319263E+09 1.49 577.17 01-SEP-08:62 1.58
October 0.203095E+09 1.40 577.17 01-OCT-08:62 1.59
November 0.153975E+09 1.31 577.17 02-NOV-08:62 1.59
December 0.196482E+09 1.20 577.17 02-DEC-09:02 1.60
           
Annual Sum or Average 0.300998E+10 1.38      
Minimum of Months 0.143466E+09 1.20 577.17   1.58
Maximum of Months 0.397311E+09 1.53 577.17   1.60



Table of Contents

Report: FanReportMonthly

For: ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.205875E+09 1.20 572.43 01-JAN-09:02 1.59
February 0.154713E+09 1.17 572.43 01-FEB-09:02 1.60
March 0.139580E+09 1.19 572.43 01-MAR-09:02 1.60
April 0.183744E+09 1.37 572.43 01-APR-15:01 1.60
May 0.298234E+09 1.47 572.43 01-MAY-15:01 1.60
June 0.400965E+09 1.53 572.43 01-JUN-08:61 1.60
July 0.395975E+09 1.52 572.43 01-JUL-08:61 1.58
August 0.348812E+09 1.49 572.43 01-AUG-08:61 1.58
September 0.272634E+09 1.47 572.43 01-SEP-08:62 1.58
October 0.148302E+09 1.28 572.43 01-OCT-15:01 1.59
November 0.146275E+09 1.20 572.43 02-NOV-08:62 1.59
December 0.248806E+09 1.23 572.43 01-DEC-09:02 1.60
           
Annual Sum or Average 0.294391E+10 1.34      
Minimum of Months 0.139580E+09 1.17 572.43   1.58
Maximum of Months 0.400965E+09 1.53 572.43   1.60



Table of Contents

Report: FanReportMonthly

For: ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.886654E+09 1.37 2610.88 01-JAN-16:02 1.59
February 0.806345E+09 1.38 2610.88 01-FEB-16:01 1.61
March 0.799120E+09 1.36 2610.88 01-MAR-16:01 1.60
April 0.102961E+10 1.43 2610.88 01-APR-15:01 1.60
May 0.134636E+10 1.47 2610.88 01-MAY-15:01 1.60
June 0.174725E+10 1.50 2610.88 01-JUN-08:61 1.60
July 0.181920E+10 1.50 2610.88 01-JUL-08:61 1.58
August 0.179914E+10 1.49 2610.88 01-AUG-08:61 1.58
September 0.179273E+10 1.50 2610.88 01-SEP-08:62 1.58
October 0.145419E+10 1.45 2610.88 01-OCT-08:62 1.59
November 0.105525E+10 1.40 2610.88 02-NOV-15:01 1.59
December 0.924601E+09 1.36 2610.88 01-DEC-16:01 1.60
           
Annual Sum or Average 0.154605E+11 1.44      
Minimum of Months 0.799120E+09 1.36 2610.88   1.58
Maximum of Months 0.181920E+10 1.50 2610.88   1.61



Table of Contents

Report: PumpReportMonthly

For: HEATSYS1 PUMP

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.102359E+10 0.921227E+09 843.97 27-JAN-07:10 759.57 759.57 36.97 1.46
February 0.816573E+09 0.734915E+09 870.94 03-FEB-07:10 783.84 783.84 36.27 1.57
March 0.794822E+09 0.715340E+09 836.65 02-MAR-09:03 752.99 752.99 34.10 1.43
April 0.479087E+09 0.431178E+09 602.55 11-APR-08:04 542.29 542.29 33.37 0.82
May 0.373849E+09 0.336464E+09 511.06 23-MAY-08:04 459.95 459.95 31.47 0.66
June 0.310579E+09 0.279521E+09 469.90 30-JUN-10:40 422.91 422.91 35.38 0.59
July 0.249368E+09 0.224431E+09 470.20 05-JUL-10:40 423.18 423.18 34.09 0.59
August 0.211009E+09 0.189908E+09 453.55 24-AUG-08:04 408.19 408.19 32.59 0.56
September 0.192054E+09 0.172849E+09 410.32 01-SEP-10:40 369.29 369.29 31.77 0.50
October 0.296780E+09 0.267102E+09 513.12 13-OCT-08:05 461.81 461.81 28.12 0.66
November 0.686247E+09 0.617622E+09 822.48 27-NOV-09:02 740.23 740.23 34.22 1.38
December 0.111620E+10 0.100458E+10 886.32 27-DEC-07:10 797.69 797.69 37.69 1.63
                 
Annual Sum or Average 0.655016E+10 0.589514E+10            
Minimum of Months 0.192054E+09 0.172849E+09 410.32   369.29 369.29 28.12 0.50
Maximum of Months 0.111620E+10 0.100458E+10 886.32   797.69 797.69 37.69 1.63



Table of Contents

Report: PumpReportMonthly

For: COOLSYS1 PUMP SECONDARY

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.179055E+10 0.161150E+10 4443.38 03-JAN-16:01 3999.04 3999.04 6.73 10.07
February 0.285382E+10 0.256844E+10 5306.36 20-FEB-16:01 4775.72 4775.72 6.73 14.56
March 0.442394E+10 0.398155E+10 5413.53 15-MAR-18:01 4872.18 4872.18 6.73 15.36
April 0.885420E+10 0.796878E+10 6216.86 30-APR-10:40 5595.17 5595.17 6.73 26.01
May 0.121595E+11 0.109435E+11 7072.91 30-MAY-18:03 6365.62 6365.62 6.73 33.44
June 0.138684E+11 0.124816E+11 7628.85 06-JUN-18:03 6865.96 6865.96 6.73 36.01
July 0.153235E+11 0.137911E+11 7404.16 02-JUL-18:50 6663.74 6663.74 6.73 35.07
August 0.146022E+11 0.131420E+11 7205.74 23-AUG-18:30 6485.17 6485.17 6.73 34.14
September 0.131598E+11 0.118438E+11 7076.96 19-SEP-17:00 6369.26 6369.26 6.73 33.47
October 0.925235E+10 0.832712E+10 6421.35 01-OCT-10:40 5779.21 5779.21 6.73 28.58
November 0.388578E+10 0.349720E+10 5980.17 03-NOV-15:02 5382.15 5382.15 6.73 22.13
December 0.139212E+10 0.125291E+10 3782.95 09-DEC-16:01 3404.65 3404.65 6.73 7.78
                 
Annual Sum or Average 0.101566E+12 0.914095E+11            
Minimum of Months 0.139212E+10 0.125291E+10 3782.95   3404.65 3404.65 6.73 7.78
Maximum of Months 0.153235E+11 0.137911E+11 7628.85   6865.96 6865.96 6.73 36.01



Table of Contents

Report: PumpReportMonthly

For: COOLSYS1 PUMP

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.828072E+10 0.745265E+10 5255.88 01-JAN-00:05 4730.29 4730.29 6.75 36.84
February 0.937019E+10 0.843317E+10 5255.88 01-FEB-09:03 4730.29 4730.29 6.76 36.84
March 0.115897E+11 0.104308E+11 5255.88 01-MAR-00:03 4730.29 4730.29 6.76 36.84
April 0.133644E+11 0.120280E+11 5255.88 01-APR-00:10 4730.29 4730.29 6.79 36.84
May 0.140774E+11 0.126696E+11 5255.88 01-MAY-00:10 4730.29 4730.29 8.35 36.84
June 0.136232E+11 0.122609E+11 5255.88 01-JUN-00:10 4730.29 4730.29 8.93 36.84
July 0.140774E+11 0.126696E+11 5255.88 01-JUL-00:10 4730.29 4730.29 9.15 36.84
August 0.140774E+11 0.126696E+11 5255.88 01-AUG-00:10 4730.29 4730.29 9.51 36.84
September 0.136232E+11 0.122609E+11 5255.88 01-SEP-00:10 4730.29 4730.29 9.20 36.84
October 0.140679E+11 0.126611E+11 5255.88 01-OCT-00:10 4730.29 4730.29 7.46 36.84
November 0.101894E+11 0.917042E+10 5255.88 01-NOV-00:10 4730.29 4730.29 6.83 36.84
December 0.770002E+10 0.693002E+10 5255.88 01-DEC-00:03 4730.29 4730.29 6.76 36.84
                 
Annual Sum or Average 0.144041E+12 0.129637E+12            
Minimum of Months 0.770002E+10 0.693002E+10 5255.88   4730.29 4730.29 6.75 36.84
Maximum of Months 0.140774E+11 0.126696E+11 5255.88   4730.29 4730.29 9.51 36.84



Table of Contents

Report: PumpReportMonthly

For: SWHSYS1 PUMP

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.128314E+09 38494137.67 47.91 01-JAN-00:05 14.37 14.37 49.20 0.37
February 0.115896E+09 34768898.54 47.91 01-FEB-00:03 14.37 14.37 49.55 0.37
March 0.128314E+09 38494137.67 47.91 01-MAR-00:03 14.37 14.37 49.81 0.37
April 0.124175E+09 37252391.29 47.91 01-APR-00:10 14.37 14.37 52.92 0.37
May 0.128314E+09 38494137.67 47.91 01-MAY-00:10 14.37 14.37 53.37 0.37
June 0.124175E+09 37252391.29 47.91 01-JUN-00:10 14.37 14.37 53.40 0.37
July 0.128314E+09 38494137.67 47.91 01-JUL-00:10 14.37 14.37 54.41 0.37
August 0.128314E+09 38494137.67 47.91 01-AUG-00:10 14.37 14.37 54.26 0.37
September 0.124175E+09 37252391.29 47.91 01-SEP-00:10 14.37 14.37 54.27 0.37
October 0.128314E+09 38494137.67 47.91 01-OCT-00:10 14.37 14.37 53.26 0.37
November 0.124175E+09 37252391.29 47.91 01-NOV-00:10 14.37 14.37 52.66 0.37
December 0.128314E+09 38494137.67 47.91 01-DEC-00:03 14.37 14.37 50.42 0.37
                 
Annual Sum or Average 0.151079E+10 0.453237E+09            
Minimum of Months 0.115896E+09 34768898.54 47.91   14.37 14.37 49.20 0.37
Maximum of Months 0.128314E+09 38494137.67 47.91   14.37 14.37 54.41 0.37



Table of Contents

Report: CondLoopDemandReportMonthly

For: HEATSYS1

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:05 36.75 60.00 47312.08 160680.34 27-JAN-09:02
February 0.00 0.00 01-FEB-00:03 38.18 60.00 42108.64 155354.24 03-FEB-07:10
March 0.00 0.00 01-MAR-00:03 38.02 60.00 36579.44 155356.75 02-MAR-09:02
April 0.00 0.00 01-APR-00:10 32.34 60.00 22622.22 91791.34 11-APR-08:62
May 0.00 0.00 01-MAY-00:10 31.29 60.00 16813.78 78325.35 23-MAY-08:04
June 0.00 0.00 01-JUN-00:10 30.15 60.00 13907.61 68798.46 23-JUN-08:04
July 0.00 0.00 01-JUL-00:10 29.62 60.00 11502.78 69610.16 21-JUL-10:35
August 0.00 0.00 01-AUG-00:10 29.27 60.00 10211.06 66339.21 18-AUG-10:35
September 0.00 0.00 01-SEP-00:10 28.46 60.00 9603.50 69422.63 15-SEP-08:04
October 0.00 0.00 01-OCT-00:10 25.23 60.00 14586.99 88051.01 13-OCT-08:05
November 0.00 0.00 01-NOV-00:10 31.89 60.00 32498.72 148981.37 28-NOV-09:02
December 0.00 0.00 01-DEC-00:03 37.36 60.00 52039.07 156975.75 27-DEC-09:02
                 
Annual Sum or Average 0.00         25749.05    
Minimum of Months 0.00 0.00   25.23 60.00 9603.50 66339.21  
Maximum of Months 0.00 0.00   38.18 60.00 52039.07 160680.34  



Table of Contents

Report: CondLoopDemandReportMonthly

For: COOLSYS1

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 22553.43 314961.77 03-JAN-16:01 8.74 6.70 0.00 0.00 01-JAN-00:05
February 53722.21 463141.95 20-FEB-16:01 9.70 6.70 0.00 0.00 01-FEB-00:03
March 82660.88 481240.13 15-MAR-18:01 9.82 6.70 0.00 0.00 01-MAR-00:03
April 209683.57 605429.93 19-APR-18:03 10.62 6.70 0.00 0.00 01-APR-00:10
May 314878.61 640072.46 21-MAY-18:03 10.85 6.70 0.00 0.00 01-MAY-00:10
June 406754.43 738298.13 19-JUN-18:03 11.48 6.70 0.00 0.00 01-JUN-00:10
July 509212.93 943292.64 19-JUL-08:62 12.81 6.70 0.00 0.00 01-JUL-00:10
August 425135.68 802634.21 02-AUG-18:03 11.90 6.70 0.00 0.00 01-AUG-00:10
September 378249.18 713539.79 03-SEP-18:03 11.32 6.70 0.00 0.00 01-SEP-00:10
October 204755.95 698127.49 04-OCT-18:03 11.22 6.70 0.00 0.00 01-OCT-00:10
November 66170.14 469389.97 09-NOV-16:01 9.74 6.70 0.00 0.00 01-NOV-00:10
December 17252.46 223789.65 10-DEC-16:01 8.15 6.70 0.00 0.00 01-DEC-00:03
                 
Annual Sum or Average 225205.18         0.00    
Minimum of Months 17252.46 223789.65   8.15 6.70 0.00 0.00  
Maximum of Months 509212.93 943292.64   12.81 6.70 0.00 0.00  



Table of Contents

Report: CondLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:05 49.20 59.72 25474.12 51727.49 30-JAN-07:50
February 0.00 0.00 01-FEB-00:03 49.55 58.79 25455.78 51721.75 01-FEB-07:50
March 0.00 0.00 01-MAR-00:03 49.81 58.90 24601.52 50754.91 01-MAR-07:20
April 0.00 0.00 01-APR-00:10 52.92 59.47 23055.20 47839.30 03-APR-06:40
May 0.00 0.00 01-MAY-00:10 53.37 59.42 21280.26 44486.96 01-MAY-06:20
June 0.00 0.00 01-JUN-00:10 53.40 58.57 19743.58 40782.56 01-JUN-06:15
July 0.00 0.00 01-JUL-00:10 54.41 59.72 18838.55 38099.17 03-JUL-06:15
August 0.00 0.00 01-AUG-00:10 54.26 59.04 18863.50 38237.61 31-AUG-06:40
September 0.00 0.00 01-SEP-00:10 54.27 59.39 19756.74 40797.67 29-SEP-06:15
October 0.00 0.00 01-OCT-00:10 53.26 59.44 21296.80 44533.53 31-OCT-06:50
November 0.00 0.00 01-NOV-00:10 52.66 58.32 23074.28 48075.30 30-NOV-08:00
December 0.00 0.00 01-DEC-00:03 50.42 59.81 24599.56 50643.54 29-DEC-08:00
                 
Annual Sum or Average 0.00         22151.34    
Minimum of Months 0.00 0.00   49.20 58.32 18838.55 38099.17  
Maximum of Months 0.00 0.00   54.41 59.81 25474.12 51727.49  



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: VAV WITH REHEAT

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.809861E+11 0.00 0.201108E+11 0.150076E+12 0.00 0.00
February 0.708501E+11 0.00 0.759769E+11 0.135562E+12 0.00 0.00
March 0.758770E+11 0.00 0.145448E+12 0.150094E+12 0.00 0.00
April 0.539197E+11 0.00 0.382942E+12 0.145271E+12 0.00 0.00
May 0.450141E+11 0.00 0.597793E+12 0.150126E+12 0.00 0.00
June 0.363420E+11 0.00 0.736192E+12 0.145296E+12 0.00 0.00
July 0.310427E+11 0.00 0.981701E+12 0.150136E+12 0.00 0.00
August 0.275266E+11 0.00 0.808393E+12 0.150131E+12 0.00 0.00
September 0.245386E+11 0.00 0.694503E+12 0.145286E+12 0.00 0.00
October 0.350683E+11 0.00 0.364337E+12 0.150108E+12 0.00 0.00
November 0.565146E+11 0.00 0.944464E+11 0.145246E+12 0.00 0.00
December 0.837277E+11 0.00 0.146740E+11 0.150073E+12 0.00 0.00
             
Annual Sum or Average 0.621408E+12 0.00 0.491652E+13 0.176740E+13 0.00 0.00
Minimum of Months 0.245386E+11 0.00 0.146740E+11 0.135562E+12 0.00 0.00
Maximum of Months 0.837277E+11 0.00 0.981701E+12 0.150136E+12 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: FLR_3_DOAS

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.273843E+11 0.00 0.122869E+10 0.587890E+10 0.00 0.00
February 0.190765E+11 0.00 0.621055E+10 0.530997E+10 0.00 0.00
March 0.159141E+11 0.00 0.124469E+11 0.587890E+10 0.00 0.00
April 0.437768E+10 0.00 0.399969E+11 0.568926E+10 0.00 0.00
May 0.346645E+09 0.00 0.693058E+11 0.587890E+10 0.00 0.00
June 38046.70 0.00 0.932452E+11 0.568926E+10 0.00 0.00
July 11380.94 0.00 0.127410E+12 0.587890E+10 0.00 0.00
August 25201.66 0.00 0.102279E+12 0.587890E+10 0.00 0.00
September 0.490805E+09 0.00 0.814589E+11 0.568926E+10 0.00 0.00
October 0.380166E+10 0.00 0.377637E+11 0.587890E+10 0.00 0.00
November 0.185253E+11 0.00 0.755815E+10 0.568926E+10 0.00 0.00
December 0.290885E+11 0.00 0.724489E+09 0.587890E+10 0.00 0.00
             
Annual Sum or Average 0.119006E+12 0.00 0.579628E+12 0.692193E+11 0.00 0.00
Minimum of Months 11380.94 0.00 0.724489E+09 0.530997E+10 0.00 0.00
Maximum of Months 0.290885E+11 0.00 0.127410E+12 0.587890E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: VAV WITH REHEAT

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.150076E+12 0.201108E+11 0.809861E+11 0.447916E+12 0.00 0.00 0.00 0.00
February 0.135562E+12 0.759769E+11 0.708501E+11 0.314634E+12 0.316773E+09 0.00 0.00 0.00
March 0.150094E+12 0.145448E+12 0.758770E+11 0.238212E+12 0.242167E+10 0.00 0.00 0.00
April 0.145271E+12 0.382942E+12 0.539197E+11 0.564316E+11 0.517158E+11 0.00 0.00 0.00
May 0.150126E+12 0.597793E+12 0.450141E+11 0.136527E+11 0.130575E+12 0.00 0.00 0.00
June 0.145296E+12 0.736192E+12 0.363420E+11 0.131832E+11 0.241434E+12 0.00 0.00 0.00
July 0.150136E+12 0.981701E+12 0.310427E+11 0.656806E+09 0.409835E+12 0.00 0.00 0.00
August 0.150131E+12 0.808393E+12 0.275266E+11 0.452285E+10 0.251293E+12 0.00 0.00 0.00
September 0.145286E+12 0.694503E+12 0.245386E+11 0.812478E+10 0.159961E+12 0.00 0.00 0.00
October 0.150108E+12 0.364337E+12 0.350683E+11 0.364697E+11 0.408133E+11 0.00 0.00 0.00
November 0.145246E+12 0.944464E+11 0.565146E+11 0.281688E+12 0.716029E+09 0.00 0.00 0.00
December 0.150073E+12 0.146740E+11 0.837277E+11 0.547459E+12 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.176740E+13 0.491652E+13 0.621408E+12 0.196295E+13 0.128908E+13 0.00 0.00 0.00
Minimum of Months 0.135562E+12 0.146740E+11 0.245386E+11 0.656806E+09 0.00 0.00 0.00 0.00
Maximum of Months 0.150136E+12 0.981701E+12 0.837277E+11 0.547459E+12 0.409835E+12 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: FLR_3_DOAS

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.587890E+10 0.122869E+10 0.273843E+11 0.00 0.00 0.00 0.00 0.00
February 0.530997E+10 0.621055E+10 0.190765E+11 0.00 0.00 0.00 0.00 0.00
March 0.587890E+10 0.124469E+11 0.159141E+11 0.00 0.00 0.00 0.00 0.00
April 0.568926E+10 0.399969E+11 0.437768E+10 0.00 0.00 0.00 0.00 0.00
May 0.587890E+10 0.693058E+11 0.346645E+09 0.00 0.00 0.00 0.00 0.00
June 0.568926E+10 0.932452E+11 38046.70 0.00 0.00 0.00 0.00 0.00
July 0.587890E+10 0.127410E+12 11380.94 0.00 0.00 0.00 0.00 0.00
August 0.587890E+10 0.102279E+12 25201.66 0.00 0.00 0.00 0.00 0.00
September 0.568926E+10 0.814589E+11 0.490805E+09 0.00 0.00 0.00 0.00 0.00
October 0.587890E+10 0.377637E+11 0.380166E+10 0.00 0.00 0.00 0.00 0.00
November 0.568926E+10 0.755815E+10 0.185253E+11 0.00 0.00 0.00 0.00 0.00
December 0.587890E+10 0.724489E+09 0.290885E+11 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.692193E+11 0.579628E+12 0.119006E+12 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.530997E+10 0.724489E+09 11380.94 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.587890E+10 0.127410E+12 0.290885E+11 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: VAV WITH REHEAT

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.150076E+12 0.809861E+11 0.201108E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.135562E+12 0.708501E+11 0.759769E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.150094E+12 0.758770E+11 0.145448E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.145271E+12 0.539197E+11 0.382942E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.150126E+12 0.450141E+11 0.597793E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.145296E+12 0.363420E+11 0.736192E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.150136E+12 0.310427E+11 0.981701E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.150131E+12 0.275266E+11 0.808393E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.145286E+12 0.245386E+11 0.694503E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.150108E+12 0.350683E+11 0.364337E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.145246E+12 0.565146E+11 0.944464E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.150073E+12 0.837277E+11 0.146740E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.176740E+13 0.621408E+12 0.491652E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.135562E+12 0.245386E+11 0.146740E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.150136E+12 0.837277E+11 0.981701E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: FLR_3_DOAS

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.587890E+10 0.273843E+11 0.122869E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.530997E+10 0.190765E+11 0.621055E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.587890E+10 0.159141E+11 0.124469E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.568926E+10 0.437768E+10 0.399969E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.587890E+10 0.346645E+09 0.693058E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.568926E+10 38046.70 0.932452E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.587890E+10 11380.94 0.127410E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.587890E+10 25201.66 0.102279E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.568926E+10 0.490805E+09 0.814589E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.587890E+10 0.380166E+10 0.377637E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.568926E+10 0.185253E+11 0.755815E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.587890E+10 0.290885E+11 0.724489E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.692193E+11 0.119006E+12 0.579628E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.530997E+10 11380.94 0.724489E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.587890E+10 0.290885E+11 0.127410E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.704897E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2.14
February 0.574923E+11 0.00 0.00 0.00 1016797.94 0.00 0.00 0.00 2.13
March 0.568749E+11 0.00 1294454.31 0.00 47443850.07 0.569601E+09 0.00 234232.17 2.14
April 0.319406E+11 0.00 0.213700E+09 0.00 0.172750E+10 77481966.95 0.00 3957304.73 2.14
May 0.157247E+11 0.00 0.264044E+09 0.00 0.530600E+10 9258254.07 0.00 3288028.95 2.14
June 0.479149E+10 0.00 0.217923E+09 0.00 0.102459E+11 0.00 0.00 1966999.47 2.15
July 0.304615E+09 0.00 4035668.78 0.00 0.307897E+11 0.00 0.00 17538.11 2.15
August 0.310689E+10 0.00 0.00 0.00 0.147104E+11 0.00 0.00 0.00 2.15
September 0.106773E+11 0.00 0.00 0.00 0.127392E+11 0.00 0.00 0.00 2.16
October 0.375426E+11 0.00 0.00 0.00 0.233539E+10 0.00 0.00 0.00 2.15
November 0.608677E+11 0.00 0.00 0.00 22241198.04 0.00 0.00 0.00 2.13
December 0.710390E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2.13
                   
Annual Sum or Average 0.420852E+12 0.00 0.700997E+09 0.00 0.779247E+11 0.656341E+09 0.00 9464103.42 2.14
Minimum of Months 0.304615E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2.13
Maximum of Months 0.710390E+11 0.00 0.264044E+09 0.00 0.307897E+11 0.569601E+09 0.00 3957304.73 2.16



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.752765E+10 0.00 0.00 9000.29 0.00 0.202965E+10 46253076.58 0.00 5.28
February 0.678453E+10 32325.87 0.00 13034.30 106203.31 0.103099E+10 17248973.45 0.00 5.28
March 0.714882E+10 0.00 0.00 0.00 6672048.53 0.677455E+09 0.00 0.00 5.29
April 0.432476E+10 0.00 0.00 0.00 0.265009E+09 37406733.77 0.00 0.00 5.29
May 0.214361E+10 0.00 0.00 0.00 0.759314E+09 0.00 0.00 0.00 5.31
June 0.652796E+09 0.00 0.00 0.00 0.142586E+10 0.00 0.00 0.00 5.31
July 41500931.64 0.00 0.00 0.00 0.419536E+10 0.00 0.00 0.00 5.32
August 0.423284E+09 3304997.79 0.00 0.00 0.200085E+10 0.00 0.00 0.00 5.31
September 0.145468E+10 0.188536E+09 0.00 0.00 0.154706E+10 0.00 0.00 0.00 5.33
October 0.509679E+10 95678875.07 0.00 118187.94 0.222497E+09 0.00 17915952.95 0.00 5.31
November 0.732532E+10 2618586.88 0.00 93935.73 411567.63 0.828086E+09 0.139152E+09 0.00 5.27
December 0.704450E+10 0.00 0.00 0.00 0.00 0.263390E+10 0.00 0.00 5.26
                   
Annual Sum or Average 0.499682E+11 0.290171E+09 0.00 234158.26 0.104231E+11 0.723750E+10 0.220570E+09 0.00 5.30
Minimum of Months 41500931.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 5.26
Maximum of Months 0.752765E+10 0.188536E+09 0.00 118187.94 0.419536E+10 0.263390E+10 0.139152E+09 0.00 5.33



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.701016E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3.33
February 0.571757E+10 0.00 0.00 0.00 101119.87 0.00 0.00 0.00 3.33
March 0.571282E+10 0.00 0.00 0.00 4870285.64 0.00 0.00 0.00 3.34
April 0.318418E+10 0.00 0.00 0.00 0.193444E+09 0.00 0.00 0.00 3.33
May 0.156474E+10 0.00 0.00 0.00 0.554264E+09 0.00 0.00 0.00 3.35
June 0.476511E+09 0.00 0.00 0.00 0.104081E+10 0.00 0.00 0.00 3.35
July 30293753.19 0.00 0.00 0.00 0.306241E+10 0.00 0.00 0.00 3.35
August 0.308978E+09 0.00 0.00 0.00 0.146294E+10 0.00 0.00 0.00 3.35
September 0.106185E+10 0.00 0.00 0.00 0.126691E+10 0.00 0.00 0.00 3.36
October 0.373358E+10 0.00 0.00 0.00 0.232253E+09 0.00 0.00 0.00 3.34
November 0.605325E+10 0.00 0.00 0.00 2211872.10 0.00 0.00 0.00 3.32
December 0.706478E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3.32
                   
Annual Sum or Average 0.419187E+11 0.00 0.00 0.00 0.782022E+10 0.00 0.00 0.00 3.34
Minimum of Months 30293753.19 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3.32
Maximum of Months 0.706478E+10 0.00 0.00 0.00 0.306241E+10 0.00 0.00 0.00 3.36



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.722559E+10 0.00 0.00 0.00 0.00 0.281070E+09 0.00 0.00 1.69
February 0.591008E+10 0.00 0.00 0.00 108281.82 0.212443E+09 0.00 0.00 1.68
March 0.605552E+10 0.00 0.00 0.00 5215230.04 61914420.34 0.00 0.00 1.69
April 0.340970E+10 0.00 0.00 0.00 0.207145E+09 0.00 0.00 0.00 1.69
May 0.167556E+10 0.00 0.00 0.00 0.593520E+09 0.00 0.00 0.00 1.69
June 0.510260E+09 0.00 0.00 0.00 0.111453E+10 0.00 0.00 0.00 1.69
July 32439348.22 0.00 0.00 0.00 0.327931E+10 0.00 0.00 0.00 1.70
August 0.330862E+09 0.00 0.00 0.00 0.156655E+10 0.00 0.00 0.00 1.70
September 0.113706E+10 0.00 0.00 0.00 0.135664E+10 0.00 0.00 0.00 1.70
October 0.399802E+10 0.00 0.00 0.00 0.248703E+09 0.00 0.00 0.00 1.69
November 0.641512E+10 0.00 0.00 0.00 2368530.86 66858506.02 0.00 0.00 1.68
December 0.668588E+10 0.00 0.00 0.00 0.00 0.879272E+09 0.00 0.00 1.68
                   
Annual Sum or Average 0.433861E+11 0.00 0.00 0.00 0.837409E+10 0.150156E+10 0.00 0.00 1.69
Minimum of Months 32439348.22 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.68
Maximum of Months 0.722559E+10 0.00 0.00 0.00 0.327931E+10 0.879272E+09 0.00 0.00 1.70



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.255061E+10 0.00 0.00 0.00 0.00 0.124054E+10 0.00 0.00 1.48
February 0.241884E+10 0.00 0.00 0.00 54686.45 0.673268E+09 0.00 0.00 1.47
March 0.284468E+10 0.00 0.00 0.00 2633890.29 0.244865E+09 0.00 0.00 1.48
April 0.172203E+10 0.00 0.00 0.00 0.104616E+09 0.00 0.00 0.00 1.48
May 0.846221E+09 0.00 0.00 0.00 0.299750E+09 0.00 0.00 0.00 1.48
June 0.257701E+09 0.00 0.00 0.00 0.562880E+09 0.00 0.00 0.00 1.48
July 16383109.37 0.00 0.00 0.00 0.165618E+10 0.00 0.00 0.00 1.49
August 0.167098E+09 0.00 0.00 0.00 0.791169E+09 0.00 0.00 0.00 1.48
September 0.574257E+09 0.00 0.00 0.00 0.685153E+09 0.00 0.00 0.00 1.49
October 0.201915E+10 0.00 0.00 0.00 0.125604E+09 0.00 0.00 0.00 1.48
November 0.283627E+10 0.00 0.00 0.00 1196198.51 0.437381E+09 0.00 0.00 1.47
December 0.207272E+10 0.00 0.00 0.00 0.00 0.174798E+10 0.00 0.00 1.47
                   
Annual Sum or Average 0.183260E+11 0.00 0.00 0.00 0.422924E+10 0.434403E+10 0.00 0.00 1.48
Minimum of Months 16383109.37 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.47
Maximum of Months 0.284468E+10 0.00 0.00 0.00 0.165618E+10 0.174798E+10 0.00 0.00 1.49



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.175162E+10 0.00 0.00 65693493.32 0.00 0.00 0.916844E+11 0.00 44.24
February 0.119385E+10 1348304.61 0.00 60066590.20 0.00 0.00 0.750083E+11 0.00 44.23
March 0.812177E+09 62903586.44 0.00 68028185.65 2035468.06 0.00 0.753219E+11 0.00 44.31
April 0.362258E+09 0.247668E+10 0.00 53394594.37 0.102684E+09 0.00 0.420513E+11 0.00 44.26
May 88971891.39 0.705758E+10 0.00 40363667.28 0.332946E+09 0.00 0.207365E+11 0.00 44.44
June 20757754.67 0.134005E+11 0.00 21684573.39 0.477899E+09 0.00 0.631128E+10 0.00 44.44
July 0.00 0.396654E+11 0.00 2983725.95 0.117139E+10 0.00 0.400945E+09 0.00 44.51
August 3258641.85 0.189151E+11 0.00 14245036.79 0.593580E+09 0.00 0.410259E+10 0.00 44.47
September 46902003.15 0.163757E+11 0.00 25776173.05 0.517921E+09 0.00 0.140872E+11 0.00 44.60
October 0.505848E+09 0.300384E+10 0.00 57105694.22 93543585.73 0.00 0.492334E+11 0.00 44.41
November 0.126608E+10 29129822.81 0.00 65580130.08 362673.88 0.00 0.794090E+11 0.00 44.11
December 0.201411E+10 0.00 0.00 64919938.63 0.00 0.00 0.921487E+11 0.00 44.09
                   
Annual Sum or Average 0.806583E+10 0.100988E+12 0.00 0.539842E+09 0.329237E+10 0.00 0.550495E+12 0.00 44.34
Minimum of Months 0.00 0.00 0.00 2983725.95 0.00 0.00 0.400945E+09 0.00 44.09
Maximum of Months 0.201411E+10 0.396654E+11 0.00 68028185.65 0.117139E+10 0.00 0.921487E+11 0.00 44.60



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.396207E+11 0.00 0.00 208494.68 0.00 0.00 0.122642E+10 0.00 7.98
February 0.324196E+11 240750.86 0.00 337787.53 348462.94 0.00 0.895736E+09 0.00 7.98
March 0.326038E+11 3716910.38 0.00 76466.69 24661682.07 0.00 0.684106E+09 0.00 8.00
April 0.170507E+11 45149509.57 0.00 578528.01 0.108203E+10 0.00 0.150252E+10 0.00 7.99
May 0.713753E+10 59637835.29 0.00 1401925.64 0.316999E+10 0.00 0.197860E+10 0.00 8.03
June 0.136139E+10 0.715679E+09 0.00 2087792.70 0.534902E+10 0.00 0.141309E+10 0.00 8.03
July 73214552.46 0.490114E+10 0.00 441497.05 0.129432E+11 0.00 0.102862E+09 0.00 8.05
August 0.785340E+09 0.210664E+10 0.00 1224656.97 0.641773E+10 0.00 0.101381E+10 0.00 8.04
September 0.446965E+10 0.256650E+10 0.00 1084889.84 0.481562E+10 0.00 0.171654E+10 0.00 8.06
October 0.184618E+11 0.688666E+09 0.00 1629377.82 0.664647E+09 0.00 0.329177E+10 0.00 8.02
November 0.325557E+11 11543759.37 0.00 940319.75 1344564.16 0.00 0.271495E+10 0.00 7.97
December 0.402402E+11 0.00 0.00 109474.36 0.00 0.00 0.925331E+09 0.00 7.96
                   
Annual Sum or Average 0.226780E+12 0.110989E+11 0.00 10121211.05 0.344686E+11 0.00 0.174657E+11 0.00 8.01
Minimum of Months 73214552.46 0.00 0.00 76466.69 0.00 0.00 0.102862E+09 0.00 7.96
Maximum of Months 0.402402E+11 0.490114E+10 0.00 2087792.70 0.129432E+11 0.00 0.329177E+10 0.00 8.06



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.134934E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3.81
February 0.110054E+12 0.00 0.00 0.00 1946392.90 0.00 0.00 0.00 3.81
March 0.109963E+12 0.00 0.00 0.00 93745073.42 0.00 0.00 0.00 3.81
April 0.612903E+11 0.00 0.00 0.00 0.372349E+10 0.00 0.00 0.00 3.81
May 0.301058E+11 0.00 0.00 9746.61 0.106687E+11 0.00 12796771.78 0.00 3.83
June 0.914006E+10 0.128712E+09 0.00 44932.26 0.199052E+11 0.00 31953369.90 0.00 3.83
July 0.581228E+09 0.222759E+09 0.00 3204.21 0.587237E+11 0.00 1874603.28 0.00 3.84
August 0.594103E+10 81522703.83 0.00 5556.88 0.280777E+11 0.00 6281044.87 0.00 3.83
September 0.204389E+11 22681356.67 0.00 0.00 0.243632E+11 0.00 0.00 0.00 3.84
October 0.718654E+11 0.00 0.00 0.00 0.447050E+10 0.00 0.00 0.00 3.83
November 0.116515E+12 0.00 0.00 0.00 42574938.75 0.00 0.00 0.00 3.80
December 0.135986E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3.79
                   
Annual Sum or Average 0.806814E+12 0.455675E+09 0.00 63439.96 0.150071E+12 0.00 52905789.83 0.00 3.82
Minimum of Months 0.581228E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3.79
Maximum of Months 0.135986E+12 0.222759E+09 0.00 44932.26 0.587237E+11 0.00 31953369.90 0.00 3.84



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.542632E+09 0.00 0.00 2730288.05 0.00 0.156521E+10 0.577636E+09 0.00 0.47
February 0.391044E+09 0.00 0.00 3710534.97 0.00 0.109856E+10 0.605074E+09 0.00 0.47
March 0.323244E+09 2260543.40 438.58 6243855.52 28969.00 0.822827E+09 0.787779E+09 160.66 0.47
April 0.120079E+09 0.122589E+09 27180.79 7187642.83 4227700.86 0.144393E+09 0.641340E+09 2260.66 0.47
May 28905605.30 0.420357E+09 130319.40 5898791.18 17889871.51 320919.13 0.326284E+09 13782.52 0.47
June 1855261.39 0.907237E+09 345884.90 1737874.99 29512497.85 35237.60 54145827.23 24149.83 0.47
July 0.00 0.196697E+10 1511534.50 18633.64 88170806.10 0.00 95340.02 38380.51 0.47
August 2506562.88 0.118744E+10 820140.89 1006148.82 54150119.51 54046.84 26519333.26 36262.41 0.47
September 14359107.83 0.831863E+09 491199.85 3903211.89 38786985.03 215941.25 0.202204E+09 27291.17 0.47
October 0.125675E+09 0.200567E+09 174420.39 8176159.61 9653150.28 46067326.71 0.769295E+09 4863.97 0.47
November 0.328840E+09 1250661.69 0.00 5845015.70 0.00 0.930610E+09 0.833550E+09 0.00 0.47
December 0.584198E+09 0.00 0.00 1879083.29 0.00 0.184788E+10 0.468683E+09 0.00 0.47
                   
Annual Sum or Average 0.246334E+10 0.564053E+10 3501119.31 48337240.47 0.242420E+09 0.645617E+10 0.529261E+10 147151.73 0.47
Minimum of Months 0.00 0.00 0.00 18633.64 0.00 0.00 95340.02 0.00 0.47
Maximum of Months 0.584198E+09 0.196697E+10 1511534.50 8176159.61 88170806.10 0.184788E+10 0.833550E+09 38380.51 0.47



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.582478E+09 0.00 0.00 740015.22 0.00 0.193695E+10 0.167725E+09 0.00 0.47
February 0.425227E+09 0.00 0.00 1562667.20 0.00 0.140141E+10 0.269945E+09 0.00 0.47
March 0.362255E+09 2071701.89 4609.60 4041050.39 212080.76 0.103554E+10 0.538027E+09 1451.08 0.47
April 0.131868E+09 0.117647E+09 43201.84 6301396.86 9136615.98 0.167669E+09 0.607054E+09 4031.35 0.47
May 29872050.44 0.418324E+09 175588.11 5790288.48 19826355.16 320881.53 0.325384E+09 13907.94 0.47
June 1791706.20 0.907336E+09 311791.91 1774510.99 29339602.23 21327.21 54179887.72 22582.35 0.47
July 0.00 0.196839E+10 1408962.23 19394.29 86622660.81 0.00 94566.02 35566.25 0.47
August 2524855.31 0.117961E+10 846012.52 965444.67 61797843.19 61289.64 26530977.15 39840.78 0.47
September 16232329.93 0.818273E+09 534654.27 3297857.81 52230302.65 281279.60 0.200845E+09 28223.51 0.47
October 0.157244E+09 0.185527E+09 213980.40 5386291.74 24621510.90 0.112002E+09 0.674471E+09 11602.97 0.47
November 0.400964E+09 944925.70 0.00 2428459.44 305589.46 0.123761E+10 0.457594E+09 0.00 0.47
December 0.589588E+09 0.00 0.00 392135.63 0.00 0.221984E+10 92478176.01 0.00 0.47
                   
Annual Sum or Average 0.270004E+10 0.559812E+10 3538800.87 32699512.72 0.284093E+09 0.811171E+10 0.341433E+10 157206.24 0.47
Minimum of Months 0.00 0.00 0.00 19394.29 0.00 0.00 94566.02 0.00 0.47
Maximum of Months 0.589588E+09 0.196839E+10 1408962.23 6301396.86 86622660.81 0.221984E+10 0.674471E+09 39840.78 0.47



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.219859E+11 0.00 0.00 56825739.85 0.00 0.00 0.144070E+11 0.00 0.54
February 0.153731E+11 0.00 0.00 59889846.55 0.00 0.00 0.130193E+11 0.00 0.54
March 0.149061E+11 31051860.03 0.00 58096017.64 0.00 0.00 0.113418E+11 0.00 0.54
April 0.476821E+10 0.171992E+10 0.00 52306088.42 0.00 0.00 0.755894E+10 0.00 0.54
May 0.737532E+09 0.594419E+10 0.00 37199165.22 0.00 0.00 0.412566E+10 0.00 0.54
June 16646598.14 0.127065E+11 0.00 10965885.02 0.00 0.00 0.755754E+09 0.00 0.54
July 0.00 0.278869E+11 0.00 108086.04 0.00 0.00 1437294.56 0.00 0.54
August 10079560.39 0.168464E+11 0.00 7145526.63 0.00 0.00 0.390715E+09 0.00 0.54
September 90761303.67 0.118113E+11 0.00 31213930.72 1001403.44 0.00 0.287028E+10 0.00 0.54
October 0.178212E+10 0.285282E+10 0.00 94283409.92 0.00 0.00 0.109941E+11 0.00 0.54
November 0.136458E+11 16957850.79 0.00 93508601.92 0.00 0.00 0.147191E+11 0.00 0.54
December 0.253194E+11 0.00 0.00 45408955.60 0.00 13599587.27 0.139788E+11 0.00 0.53
                   
Annual Sum or Average 0.986357E+11 0.798160E+11 0.00 0.546951E+09 1001403.44 13599587.27 0.941628E+11 0.00 0.54
Minimum of Months 0.00 0.00 0.00 108086.04 0.00 0.00 1437294.56 0.00 0.53
Maximum of Months 0.253194E+11 0.278869E+11 0.00 94283409.92 1001403.44 13599587.27 0.147191E+11 0.00 0.54



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.823249E+10 0.00 0.00 24254265.87 0.00 0.789779E+10 0.203051E+11 0.00 0.53
February 0.603625E+10 0.00 0.00 35661559.96 0.00 0.540043E+10 0.169877E+11 0.00 0.53
March 0.514496E+10 24125556.89 165000.90 59481858.59 6714154.33 0.140747E+10 0.197012E+11 55638.98 0.54
April 0.199085E+10 0.111432E+10 3501293.18 77254870.25 0.602251E+09 35344778.25 0.102794E+11 317017.97 0.54
May 0.440679E+09 0.496674E+10 2478905.26 64491488.01 0.976353E+09 1819181.74 0.439474E+10 244235.63 0.54
June 25731269.04 0.116231E+11 3132214.15 18571593.63 0.108362E+10 135299.81 0.739142E+09 100231.63 0.54
July 0.00 0.255000E+11 6105094.02 256522.40 0.238847E+10 0.00 1289280.77 42118.36 0.54
August 34444617.09 0.148629E+11 4789719.50 11349151.53 0.198316E+10 526936.42 0.361731E+09 155884.51 0.54
September 0.271203E+09 0.974999E+10 7237279.40 36927121.18 0.205803E+10 2371128.31 0.268257E+10 244363.64 0.54
October 0.233159E+10 0.204097E+10 3008029.81 71234460.36 0.809429E+09 28482551.72 0.104427E+11 190059.16 0.54
November 0.574231E+10 3647610.54 0.00 42824578.25 13314877.35 0.242349E+10 0.202576E+11 0.00 0.53
December 0.880341E+10 0.00 0.00 17959705.48 0.00 0.134742E+11 0.170724E+11 0.00 0.53
                   
Annual Sum or Average 0.390539E+11 0.698858E+11 30417536.22 0.460267E+09 0.992134E+10 0.306721E+11 0.123226E+12 1349549.87 0.54
Minimum of Months 0.00 0.00 0.00 256522.40 0.00 0.00 1289280.77 0.00 0.53
Maximum of Months 0.880341E+10 0.255000E+11 7237279.40 77254870.25 0.238847E+10 0.134742E+11 0.203051E+11 317017.97 0.54



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.591497E+09 0.00 0.00 2254587.55 0.00 0.153997E+10 0.554490E+09 0.00 0.47
February 0.383770E+09 0.00 0.00 4240990.60 0.00 0.999054E+09 0.711323E+09 0.00 0.47
March 0.281545E+09 2234999.75 17947.32 6487133.35 34935.61 0.796437E+09 0.855625E+09 2228.97 0.47
April 66940133.15 0.122097E+09 218005.61 8917545.31 4516959.76 0.136173E+09 0.700969E+09 13486.31 0.47
May 10250340.29 0.424284E+09 178608.24 7113873.26 13918663.53 55353.74 0.343990E+09 10170.71 0.47
June 958341.65 0.919782E+09 8274.16 2013595.13 17328378.49 21329.71 54780934.72 1288.97 0.47
July 0.00 0.200675E+10 87030.76 27458.52 49855404.08 0.00 86515.14 4373.05 0.47
August 1612476.87 0.121158E+10 292591.13 1168881.22 30556205.12 45181.64 27259552.06 11627.41 0.47
September 7196756.83 0.848651E+09 145148.49 4412984.62 22366976.66 24143.43 0.209049E+09 5061.15 0.47
October 99529925.17 0.201377E+09 238734.00 8529349.86 8774988.62 89392431.97 0.751762E+09 8135.31 0.47
November 0.307291E+09 1250661.69 0.00 5985834.46 0.00 0.925234E+09 0.860333E+09 0.00 0.47
December 0.633815E+09 0.00 0.00 1727320.37 0.00 0.179407E+10 0.473028E+09 0.00 0.47
                   
Annual Sum or Average 0.238441E+10 0.573801E+10 1186339.71 52879554.25 0.147353E+09 0.628048E+10 0.554270E+10 56371.88 0.47
Minimum of Months 0.00 0.00 0.00 27458.52 0.00 0.00 86515.14 0.00 0.47
Maximum of Months 0.633815E+09 0.200675E+10 292591.13 8917545.31 49855404.08 0.179407E+10 0.860333E+09 13486.31 0.47



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.606919E+09 0.00 0.00 385258.22 0.00 0.189744E+10 0.183153E+09 0.00 0.47
February 0.441904E+09 0.00 0.00 1736706.41 0.00 0.127397E+10 0.380529E+09 0.00 0.47
March 0.368197E+09 1925487.83 9366.96 3995512.91 351319.47 0.936276E+09 0.631398E+09 3669.06 0.47
April 0.106181E+09 0.120653E+09 464433.30 7848382.77 5684155.31 0.152140E+09 0.646723E+09 28936.73 0.47
May 10385951.61 0.424314E+09 237337.72 6991488.57 13775276.57 55347.25 0.343935E+09 13296.61 0.47
June 915930.38 0.920043E+09 8260.61 2059077.66 16957527.03 21327.21 54771096.87 1301.41 0.47
July 0.00 0.200611E+10 86640.32 28150.21 50252227.64 0.00 85810.09 4752.78 0.47
August 1641542.72 0.120801E+10 290564.80 1123117.82 33979328.73 45176.35 27272729.88 13618.10 0.47
September 8344585.94 0.842337E+09 387069.42 3736753.88 28331955.99 1782156.09 0.206793E+09 10556.37 0.47
October 0.145555E+09 0.191888E+09 444660.69 5481441.81 18015071.23 0.174169E+09 0.623897E+09 26954.93 0.47
November 0.419169E+09 260240.15 8653.10 2126209.08 981604.59 0.120399E+10 0.473314E+09 17.31 0.47
December 0.610483E+09 0.00 0.00 296824.47 0.00 0.215931E+10 0.132206E+09 0.00 0.47
                   
Annual Sum or Average 0.271970E+10 0.571554E+10 1936986.92 35808923.82 0.168328E+09 0.779921E+10 0.370408E+10 103103.29 0.47
Minimum of Months 0.00 0.00 0.00 28150.21 0.00 0.00 85810.09 0.00 0.47
Maximum of Months 0.610483E+09 0.200611E+10 464433.30 7848382.77 50252227.64 0.215931E+10 0.646723E+09 28936.73 0.47



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.333359E+11 0.00 0.00 0.00 0.00 0.253533E+09 0.00 0.00 1.03
February 0.272998E+11 0.00 0.00 0.00 484520.26 96215046.83 0.00 0.00 1.03
March 0.272948E+11 0.00 0.00 0.00 23336186.41 78429087.91 0.00 0.00 1.04
April 0.152571E+11 0.00 0.00 0.00 0.926897E+09 0.00 0.00 0.00 1.04
May 0.749750E+10 0.00 0.00 0.00 0.265578E+10 0.00 0.00 0.00 1.04
June 0.228322E+10 0.00 0.00 0.00 0.498710E+10 0.00 0.00 0.00 1.04
July 0.145154E+09 0.00 0.00 0.00 0.146737E+11 0.00 0.00 0.00 1.04
August 0.148048E+10 0.00 0.00 0.00 0.700973E+10 0.00 0.00 0.00 1.04
September 0.508790E+10 0.00 0.00 0.00 0.607044E+10 0.00 0.00 0.00 1.05
October 0.178896E+11 0.00 0.00 0.00 0.111285E+10 0.00 0.00 0.00 1.04
November 0.287882E+11 0.00 0.00 0.00 10598281.82 0.216215E+09 0.00 0.00 1.03
December 0.329681E+11 0.00 0.00 0.00 0.00 0.883131E+09 0.00 0.00 1.03
                   
Annual Sum or Average 0.199328E+12 0.00 0.00 0.00 0.374709E+11 0.152752E+10 0.00 0.00 1.04
Minimum of Months 0.145154E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.03
Maximum of Months 0.333359E+11 0.00 0.00 0.00 0.146737E+11 0.883131E+09 0.00 0.00 1.05



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.132440E+09 0.00 0.00 589623.28 0.00 0.439722E+09 99301224.72 0.00 0.47
February 97046008.22 0.00 0.00 866875.23 0.00 0.325136E+09 0.101549E+09 0.00 0.47
March 79691198.91 566251.34 0.00 1547175.39 6276.57 0.257452E+09 0.146333E+09 0.00 0.47
April 29065039.68 30903744.14 1982.08 1831106.88 805695.95 49771719.88 0.147582E+09 34.42 0.47
May 6870973.56 0.105904E+09 22956.67 1495525.25 3668889.52 1470252.01 80515685.15 1764.13 0.47
June 460562.62 0.228673E+09 54201.98 430202.11 5549699.06 8809.40 13543976.18 2588.36 0.47
July 0.00 0.496313E+09 327869.22 4209.24 17528238.99 0.00 24284.18 5085.43 0.47
August 631287.79 0.300044E+09 160940.33 244812.77 10399579.46 15324.21 6630098.18 5797.82 0.47
September 3593187.95 0.209765E+09 119618.45 957204.05 7901938.02 627885.69 49992327.56 5330.70 0.47
October 29659656.17 50608807.43 14856.43 2048025.90 1974885.59 34970621.69 0.170625E+09 1193.79 0.47
November 79497088.02 312665.42 0.00 1385383.28 0.00 0.273893E+09 0.169936E+09 0.00 0.47
December 0.140610E+09 0.00 0.00 381487.97 0.00 0.516580E+09 68088328.12 0.00 0.47
                   
Annual Sum or Average 0.599565E+09 0.142309E+10 702425.16 11781631.35 47835203.16 0.189965E+10 0.105412E+10 21794.66 0.47
Minimum of Months 0.00 0.00 0.00 4209.24 0.00 0.00 24284.18 0.00 0.47
Maximum of Months 0.140610E+09 0.496313E+09 327869.22 2048025.90 17528238.99 0.516580E+09 0.170625E+09 5797.82 0.47



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.130141E+09 0.00 0.00 136440.79 0.00 0.518848E+09 22848037.80 0.00 0.47
February 0.100434E+09 0.00 0.00 351940.45 0.00 0.377533E+09 46216908.24 0.00 0.47
March 87771839.99 530173.47 102.87 991035.94 42150.36 0.291458E+09 0.104746E+09 34.14 0.47
April 32438130.95 30471208.58 2797.63 1602305.65 1233525.41 58871903.72 0.135311E+09 209.51 0.47
May 7317462.67 0.105746E+09 22727.92 1465416.70 3814961.30 1794313.35 79764657.15 1761.79 0.47
June 448222.24 0.228798E+09 37223.33 438840.11 5414750.01 5331.80 13549463.89 2094.66 0.47
July 0.00 0.496323E+09 298738.25 4313.04 17487593.54 0.00 24177.04 4565.26 0.47
August 631213.83 0.298617E+09 167798.05 234754.05 11782756.18 15322.41 6639351.40 6308.15 0.47
September 3904410.70 0.206839E+09 107702.01 802905.33 10813663.05 3433651.19 47023173.98 5808.03 0.47
October 38203247.38 47969648.51 36387.81 1316541.86 4586262.35 60033009.47 0.137723E+09 1281.75 0.47
November 93888389.60 248847.11 0.00 552241.71 63781.68 0.354262E+09 75947060.41 0.00 0.47
December 0.126135E+09 0.00 0.00 66891.62 0.00 0.587940E+09 11433626.08 0.00 0.47
                   
Annual Sum or Average 0.621312E+09 0.141554E+10 673477.86 7963627.25 55239443.87 0.225419E+10 0.681226E+09 22063.28 0.47
Minimum of Months 0.00 0.00 0.00 4313.04 0.00 0.00 24177.04 0.00 0.47
Maximum of Months 0.130141E+09 0.496323E+09 298738.25 1602305.65 17487593.54 0.587940E+09 0.137723E+09 6308.15 0.47



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.552081E+09 0.00 0.00 12409182.75 0.00 0.167389E+10 0.207922E+10 0.00 0.54
February 0.389811E+09 0.00 0.00 12681291.15 0.00 0.114497E+10 0.182280E+10 0.00 0.54
March 0.384853E+09 3623486.55 0.00 12808593.14 54712.92 0.908937E+09 0.180943E+10 0.00 0.54
April 0.163067E+09 0.196466E+09 59076.22 10989127.11 7200873.62 0.194355E+09 0.109798E+10 3911.88 0.54
May 42578244.49 0.668697E+09 223797.74 8161473.08 35154363.19 2891381.28 0.526837E+09 34907.62 0.54
June 3005512.84 0.144950E+10 643903.86 2299123.98 54925106.77 34258.12 87453540.04 59641.21 0.54
July 0.00 0.315472E+10 2272082.26 26791.67 0.146246E+09 0.00 156263.97 67629.10 0.54
August 4025846.62 0.191445E+10 1285242.24 1508406.04 79716224.37 78209.08 42709482.28 63632.02 0.54
September 22609586.27 0.135241E+10 799390.71 6303523.11 45950318.27 261546.73 0.325268E+09 42588.27 0.54
October 0.162516E+09 0.329173E+09 92275.45 17485635.93 8658375.25 5000801.94 0.133955E+10 3268.87 0.54
November 0.384367E+09 2008715.67 0.00 18415273.99 0.00 0.961762E+09 0.200646E+10 0.00 0.53
December 0.610523E+09 0.00 0.00 11180334.40 0.00 0.203605E+10 0.200425E+10 0.00 0.53
                   
Annual Sum or Average 0.271944E+10 0.907105E+10 5375768.47 0.114269E+09 0.377906E+09 0.692823E+10 0.131421E+11 275578.98 0.54
Minimum of Months 0.00 0.00 0.00 26791.67 0.00 0.00 156263.97 0.00 0.53
Maximum of Months 0.610523E+09 0.315472E+10 2272082.26 18415273.99 0.146246E+09 0.203605E+10 0.207922E+10 67629.10 0.54



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.382661E+11 0.00 0.00 5642412.84 0.00 0.00 0.268544E+11 0.00 9.43
February 0.282856E+11 0.00 0.00 6361877.81 939429.29 0.00 0.248258E+11 0.00 9.43
March 0.241267E+11 4300223.20 0.00 9530805.60 40945969.52 0.00 0.289374E+11 0.00 9.45
April 0.945879E+10 0.477316E+09 0.00 14475801.06 0.131983E+10 0.00 0.201086E+11 0.00 9.45
May 0.217058E+10 0.204437E+10 0.00 19091886.75 0.310488E+10 0.00 0.123471E+11 0.00 9.49
June 0.236768E+09 0.572026E+10 0.00 16138106.19 0.394916E+10 0.00 0.417400E+10 0.00 9.50
July 9561112.55 0.192540E+11 0.00 2785666.61 0.919661E+10 0.00 0.269090E+09 0.00 9.52
August 0.191136E+09 0.771821E+10 0.00 9676038.11 0.587286E+10 0.00 0.266967E+10 0.00 9.50
September 0.175605E+10 0.629365E+10 0.00 9960346.48 0.547623E+10 0.00 0.809884E+10 0.00 9.53
October 0.117667E+11 0.777677E+09 0.00 12330482.81 0.138002E+10 0.00 0.229069E+11 0.00 9.48
November 0.291744E+11 0.00 0.00 7392373.02 20548854.61 0.00 0.270545E+11 0.00 9.41
December 0.409080E+11 0.00 0.00 4541406.01 0.00 0.00 0.247211E+11 0.00 9.40
                   
Annual Sum or Average 0.186350E+12 0.422898E+11 0.00 0.117927E+09 0.303620E+11 0.00 0.202967E+12 0.00 9.47
Minimum of Months 9561112.55 0.00 0.00 2785666.61 0.00 0.00 0.269090E+09 0.00 9.40
Maximum of Months 0.409080E+11 0.192540E+11 0.00 19091886.75 0.919661E+10 0.00 0.289374E+11 0.00 9.53



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.380289E+11 0.00 0.00 7536976.33 0.00 0.00 0.302406E+11 0.00 9.89
February 0.271802E+11 0.00 0.00 8421470.90 984879.31 0.00 0.284990E+11 0.00 9.89
March 0.215402E+11 4832978.27 0.00 12539288.94 42602245.57 0.00 0.340886E+11 0.00 9.91
April 0.789076E+10 0.788989E+09 0.00 17997670.63 0.109510E+10 0.00 0.231043E+11 0.00 9.91
May 0.177563E+10 0.303451E+10 0.00 22819760.56 0.236387E+10 0.00 0.134416E+11 0.00 9.96
June 0.189281E+09 0.782403E+10 0.00 18616122.62 0.231320E+10 0.00 0.443318E+10 0.00 9.96
July 8934307.43 0.230734E+11 0.00 3170537.96 0.675363E+10 0.00 0.282948E+09 0.00 9.98
August 0.149271E+09 0.978196E+10 0.00 11276319.57 0.446665E+10 0.00 0.284881E+10 0.00 9.97
September 0.147074E+10 0.781628E+10 0.00 11913652.71 0.452304E+10 0.00 0.885946E+10 0.00 9.99
October 0.102028E+11 0.925725E+09 0.00 15553528.25 0.133636E+10 0.00 0.261457E+11 0.00 9.94
November 0.280126E+11 0.00 0.00 9666461.12 21543017.41 0.00 0.309347E+11 0.00 9.86
December 0.403997E+11 0.00 0.00 6285361.29 0.00 0.00 0.284030E+11 0.00 9.86
                   
Annual Sum or Average 0.176849E+12 0.532498E+11 0.00 0.145797E+09 0.229170E+11 0.00 0.231282E+12 0.00 9.93
Minimum of Months 8934307.43 0.00 0.00 3170537.96 0.00 0.00 0.282948E+09 0.00 9.86
Maximum of Months 0.403997E+11 0.230734E+11 0.00 22819760.56 0.675363E+10 0.00 0.340886E+11 0.00 9.99



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.00 0.00 0.00 94977107.03 0.00 0.00 0.649206E+11 0.00 30.39
February 0.00 937470.74 0.00 88863366.71 0.00 0.00 0.529449E+11 0.00 30.40
March 0.00 45186808.59 0.00 0.100995E+09 0.00 0.00 0.528890E+11 0.00 30.47
April 0.00 0.179847E+10 0.00 76373912.52 0.00 0.00 0.294565E+11 0.00 30.47
May 0.00 0.515480E+10 0.00 53364917.94 0.00 0.00 0.144574E+11 0.00 30.62
June 0.00 0.968284E+10 0.00 31077791.00 0.00 0.00 0.438727E+10 0.00 30.65
July 0.00 0.284561E+11 0.00 3732646.90 0.00 0.00 0.277135E+09 0.00 30.69
August 0.00 0.135986E+11 0.00 19372751.48 0.00 0.00 0.284549E+10 0.00 30.65
September 0.00 0.117722E+11 0.00 33500898.87 0.00 0.00 0.981368E+10 0.00 30.73
October 0.00 0.215877E+10 0.00 85659495.91 0.00 0.00 0.345432E+11 0.00 30.57
November 0.00 20525026.38 0.00 98406143.22 0.00 0.00 0.560503E+11 0.00 30.32
December 0.00 0.00 0.00 93431722.54 0.00 0.00 0.654263E+11 0.00 30.29
                   
Annual Sum or Average 0.00 0.726884E+11 0.00 0.779756E+09 0.00 0.00 0.388012E+12 0.00 30.52
Minimum of Months 0.00 0.00 0.00 3732646.90 0.00 0.00 0.277135E+09 0.00 30.29
Maximum of Months 0.00 0.284561E+11 0.00 0.100995E+09 0.00 0.00 0.654263E+11 0.00 30.73



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.154018E+11 0.00 0.00 0.00 0.00 0.542172E+10 0.00 0.00 2.42
February 0.140599E+11 0.00 0.00 0.00 300374.18 0.292402E+10 0.00 0.00 2.42
March 0.149973E+11 0.00 0.00 0.00 14467068.36 0.197248E+10 0.00 0.00 2.43
April 0.938079E+10 0.00 0.00 0.00 0.574622E+09 77737743.16 0.00 0.00 2.42
May 0.464801E+10 0.00 0.00 0.00 0.164643E+10 0.00 0.00 0.00 2.44
June 0.141546E+10 0.00 0.00 0.00 0.309171E+10 0.00 0.00 0.00 2.44
July 89986877.73 0.00 0.00 0.00 0.909683E+10 0.00 0.00 0.00 2.44
August 0.917811E+09 0.00 0.00 0.00 0.434562E+10 0.00 0.00 0.00 2.44
September 0.315420E+10 0.00 0.00 0.00 0.376332E+10 0.00 0.00 0.00 2.44
October 0.110905E+11 0.00 0.00 0.00 0.689903E+09 0.00 0.00 0.00 2.43
November 0.151321E+11 0.00 0.00 0.00 6570313.79 0.284896E+10 0.00 0.00 2.42
December 0.135154E+11 0.00 0.00 0.00 0.00 0.747035E+10 0.00 0.00 2.41
                   
Annual Sum or Average 0.103803E+12 0.00 0.00 0.00 0.232298E+11 0.207153E+11 0.00 0.00 2.43
Minimum of Months 89986877.73 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2.41
Maximum of Months 0.154018E+11 0.00 0.00 0.00 0.909683E+10 0.747035E+10 0.00 0.00 2.44



Table of Contents

Report: HeatEmissionsReportMonthly

For: Environment

Timestamp: 2023-10-16 08:58:10

Custom Monthly Report

SITE TOTAL SURFACE HEAT EMISSION TO AIR [J] SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J]
January 0.189099E+12 0.183042E+11 0.797357E+11 0.109797E+13 0.149805E+12
February 0.196158E+12 0.142762E+11 0.622894E+11 0.846446E+12 0.232359E+12
March 0.315088E+12 0.130853E+11 0.588030E+11 0.767540E+12 0.357047E+12
April 0.325824E+12 0.520145E+10 0.300491E+11 0.286220E+12 0.771129E+12
May 0.356766E+12 96615653.85 0.112203E+11 -0.200461E+11 0.116536E+13
June 0.338943E+12 -0.422232E+10 -0.633785E+10 -0.281023E+12 0.144865E+13
July 0.327833E+12 -0.110673E+11 -0.292418E+11 -0.696658E+12 0.182212E+13
August 0.297900E+12 -0.574660E+10 -0.816995E+10 -0.360902E+12 0.153401E+13
September 0.255024E+12 -0.271310E+10 0.232373E+10 -0.174417E+12 0.131313E+13
October 0.239520E+12 0.539958E+10 0.327787E+11 0.317544E+12 0.763479E+12
November 0.185123E+12 0.142014E+11 0.636573E+11 0.842253E+12 0.285331E+12
December 0.153192E+12 0.201368E+11 0.856823E+11 0.120364E+13 0.133499E+12
           
Annual Sum or Average 0.318047E+13 0.669523E+11 0.382790E+12 0.382857E+13 0.997591E+13
Minimum of Months 0.153192E+12 -0.110673E+11 -0.292418E+11 -0.696658E+12 0.133499E+12
Maximum of Months 0.356766E+12 0.201368E+11 0.856823E+11 0.120364E+13 0.182212E+13