Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:58
Tabular Output Report in Format: HTML
Building: HotelLarge
Environment: RUNPERIOD 1 ** Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930
Simulation Timestamp: 2023-10-16 08:58:38
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:58:38
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 14091.26 | 1242.04 | 1242.04 |
Net Site Energy | 14091.26 | 1242.04 | 1242.04 |
Total Source Energy | 30137.43 | 2656.38 | 2656.38 |
Net Source Energy | 30137.43 | 2656.38 | 2656.38 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 11345.29 |
Net Conditioned Building Area | 11345.29 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 1928.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 724.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1174.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 261.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1751.30 | 1788.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 679.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1843.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 158.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 376.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 90.78 | 3238.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Refrigeration | 74.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 7135.14 | 6956.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 1928.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 724.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 1174.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 261.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 959.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 762.04 | 1198.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 16.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 13.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 590.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 32.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 616.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 30.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 1843.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 158.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 376.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 90.78 | 3238.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5742.51 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4114.69 | |
Refrigeration | General | 18.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 22.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 33.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 1928.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 724.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 1174.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 261.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 1751.30 | 1788.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 679.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 1843.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 158.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 376.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 90.78 | 3238.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Refrigeration | Unassigned | 74.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 126.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 248.31 | 455.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Other | 254.04 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 628.91 | 613.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 126.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 248.31 | 455.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Other | 254.04 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 628.91 | 613.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 7135.144 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 7135.144 | 100.00 |
Total On-Site and Utility Electric Sources | 7135.144 | 100.00 |
Total Electricity End Uses | 7135.144 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | 0.00 |
Air to Air Heat Recovery for Cooling | 91.07 | 2.37 |
Air to Air Heat Recovery for Heating | 3750.74 | 97.63 |
High-Temperature Geothermal* | 0.00 | 0.00 |
Solar Water Thermal | 0.00 | 0.00 |
Solar Air Thermal | 0.00 | 0.00 |
Total On-Site Thermal Sources | 3841.81 | 100.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 9857.19 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 9857.19 | 100.00 |
Total Water End Uses | 9857.19 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 38.83 |
Time Setpoint Not Met During Occupied Cooling | 9.33 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 6651.17 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2012
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4C
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_SEATTLE
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneHeatingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneElectricSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |PeakSpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ComfortReportSimple55Monthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |OccupantComfortDataSummaryMonthly
| BASEMENT PEOPLE | RETAIL_1_FLR_1 PEOPLE | RETAIL_2_FLR_1 PEOPLE | LAUNDRY_FLR_1 PEOPLE | CAFE_FLR_1 PEOPLE | LOBBY_FLR_1 PEOPLE | ROOM_1_FLR_3 PEOPLE | ROOM_2_FLR_3 PEOPLE | ROOM_3_MULT19_FLR_3 PEOPLE | ROOM_4_MULT19_FLR_3 PEOPLE | ROOM_5_FLR_3 PEOPLE | ROOM_6_FLR_3 PEOPLE | ROOM_1_FLR_6 PEOPLE | ROOM_2_FLR_6 PEOPLE | ROOM_3_MULT9_FLR_6 PEOPLE | BANQUET_FLR_6 PEOPLE | DINING_FLR_6 PEOPLE | KITCHEN_FLR_6 PEOPLE | STORAGE_FLR_1 PEOPLE | CORRIDOR_FLR_3 PEOPLE | CORRIDOR_FLR_6 PEOPLE | MECH_FLR_1 PEOPLE |ChillerReportMonthly
| COOLSYS1 CHILLER1 |BoilerReportMonthly
| HEATSYS1 BOILER |DXReportMonthly
| VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |WindowReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowEnergyReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWH BOOSTER E WATER HEATER | SWH LAUNDRY G WATER HEATER | SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| VAV WITH REHEAT HEATING COIL | BASEMENT VAV BOX REHEAT COIL | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | MECH_FLR_1 VAV BOX REHEAT COIL | STORAGE_FLR_1 VAV BOX REHEAT COIL | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | CAFE_FLR_1 VAV BOX REHEAT COIL | LOBBY_FLR_1 VAV BOX REHEAT COIL | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | BANQUET_FLR_6 VAV BOX REHEAT COIL | DINING_FLR_6 VAV BOX REHEAT COIL | KITCHEN_FLR_6 VAV BOX REHEAT COIL | FLR_3_DOAS HEATING COIL | ROOM_1_FLR_3 FAN COIL HEATING COIL | ROOM_2_FLR_3 FAN COIL HEATING COIL | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_5_FLR_3 FAN COIL HEATING COIL | ROOM_6_FLR_3 FAN COIL HEATING COIL | ROOM_1_FLR_6 FAN COIL HEATING COIL | ROOM_2_FLR_6 FAN COIL HEATING COIL | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1 | SWHSYS1 |FanReportMonthly
| FLR_3_DOAS FAN | VAV WITH REHEAT FAN | LAUNDRY_FLR_1 EXHAUST FAN | LOBBY_FLR_1 EXHAUST FAN | BANQUET_FLR_6 EXHAUST FAN | DINING_FLR_6 EXHAUST FAN | KITCHEN_FLR_6 EXHAUST FAN | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 PUMP | SWHSYS1 PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1 | SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV WITH REHEAT | FLR_3_DOAS |AirLoopSystemComponentLoadsMonthly
| VAV WITH REHEAT | FLR_3_DOAS |AirLoopSystemComponentEnergyUseMonthly
| VAV WITH REHEAT | FLR_3_DOAS |MechanicalVentilationLoadsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:58:38
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:58 |
RunPeriod | RUNPERIOD 1 |
Weather File | Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 |
Latitude [deg] | 47.47 |
Longitude [deg] | -122.3 |
Elevation [m] | 122.00 |
Time Zone | -8.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1213.79 | 432.95 | 85.85 | 609.15 | 85.85 |
Gross Window-Wall Ratio [%] | 26.62 | 23.11 | 21.12 | 32.52 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.15 | 26.05 | 24.48 | 36.65 | 24.48 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1213.79 | 432.95 | 85.85 | 609.15 | 85.85 |
Gross Window-Wall Ratio [%] | 26.62 | 23.11 | 21.12 | 32.52 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.15 | 26.05 | 24.48 | 36.65 | 24.48 |
Total | |
Gross Roof Area [m2] | 1978.84 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 1978.83 | Yes | Yes | 4826.41 | 1.00 | 0.00 | 533.77 | 0.00 | 0.00 | 8.7495 | 18.58 | 5.3800 |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 265.76 | 1.00 | 68.84 | 0.00 | 23.26 | 23.26 | 13.0124 | 6.19 | 10.7600 |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 307.76 | 1.00 | 26.57 | 0.00 | 0.00 | 0.00 | 13.0124 | 6.19 | 10.7600 |
MECH_FLR_1 | 164.24 | Yes | Yes | 650.80 | 1.00 | 62.80 | 0.00 | 0.00 | 0.00 | 10.0642 | 61.93 | 5.3800 |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 375.47 | 1.00 | 36.23 | 0.00 | 0.00 | 0.00 | 7.3195 | 46.45 | 2.6900 |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 309.22 | 1.00 | 85.75 | 0.00 | 0.00 | 0.00 | 5.4896 | 9.29 | 597.5300 |
CAFE_FLR_1 | 188.86 | Yes | Yes | 748.35 | 1.00 | 152.17 | 0.00 | 65.50 | 65.50 | 12.8090 | 1.33 | 5.3800 |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 5183.56 | 1.00 | 434.79 | 0.00 | 85.08 | 85.08 | 10.0642 | 3.10 | 8.0700 |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 10.0642 | 26.01 | 6.7500 |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 10.0642 | 26.01 | 6.7500 |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 74.75 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 10.0642 | 16.35 | 10.5200 |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 74.77 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 10.0642 | 16.35 | 10.5200 |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 10.0642 | 26.01 | 6.7500 |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 10.0642 | 26.01 | 6.7500 |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 1186.91 | 4.00 | 48.31 | 0.00 | 15.94 | 15.94 | 3.6597 | 18.58 | 0.0000 |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 118.94 | 1.00 | 39.95 | 0.00 | 13.18 | 13.18 | 10.0642 | 26.01 | 6.7500 |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 118.93 | 1.00 | 39.95 | 0.00 | 13.18 | 13.18 | 10.0642 | 26.01 | 6.7500 |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 74.77 | 9.00 | 20.44 | 0.00 | 6.74 | 6.74 | 10.0642 | 16.35 | 10.5200 |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.19 | 32.19 | 12.8090 | 1.33 | 67.8200 |
DINING_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.19 | 32.19 | 12.8090 | 1.33 | 67.8200 |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 314.87 | 1.00 | 87.33 | 0.00 | 26.37 | 26.37 | 10.9792 | 4.65 | 2936.4163 |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1256.16 | 1.00 | 85.47 | 0.00 | 28.20 | 28.20 | 3.6597 | 18.58 | 0.0000 |
Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1213.79 | 1213.79 | 8.9207 | 7.07 | 41.0885 | |||
Conditioned Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1213.79 | 1213.79 | 8.9207 | 7.07 | 41.0885 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 1978.83 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 8.7495 | 18.58 | 5.3800 | |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 1.00 | RETAIL_1_FLR_1 | GENERAL | RETAIL_1_FLR_1 | 13.0124 | 6.19 | 10.7600 | |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 1.00 | RETAIL_2_FLR_1 | GENERAL | RETAIL_2_FLR_1 | 13.0124 | 6.19 | 10.7600 | |
MECH_FLR_1 | 164.24 | Yes | Yes | 1.00 | MECH_FLR_1 | GENERAL | MECH_FLR_1 | 10.0642 | 61.93 | 5.3800 | |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 1.00 | STORAGE_FLR_1 | GENERAL | STORAGE_FLR_1 | 7.3195 | 46.45 | 2.6900 | |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 1.00 | LAUNDRY_FLR_1 | GENERAL | LAUNDRY_FLR_1 | 5.4896 | 9.29 | 597.5300 | |
CAFE_FLR_1 | 188.86 | Yes | Yes | 1.00 | CAFE_FLR_1 | GENERAL | CAFE_FLR_1 | 12.8090 | 1.33 | 5.3800 | |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 1.00 | LOBBY_FLR_1 | GENERAL | LOBBY_FLR_1 | 10.0642 | 3.10 | 8.0700 | |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_1_FLR_3 | GENERAL | ROOM_1_FLR_3 | 10.0642 | 26.01 | 6.7500 | |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_2_FLR_3 | GENERAL | ROOM_2_FLR_3 | 10.0642 | 26.01 | 6.7500 | |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 76.00 | ROOM_3_MULT19_FLR_3 | GENERAL | ROOM_3_MULT19_FLR_3 | 10.0642 | 16.35 | 10.5200 | |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 76.00 | ROOM_4_MULT19_FLR_3 | GENERAL | ROOM_4_MULT19_FLR_3 | 10.0642 | 16.35 | 10.5200 | |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_5_FLR_3 | GENERAL | ROOM_5_FLR_3 | 10.0642 | 26.01 | 6.7500 | |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_6_FLR_3 | GENERAL | ROOM_6_FLR_3 | 10.0642 | 26.01 | 6.7500 | |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 4.00 | CORRIDOR_FLR_3 | GENERAL | CORRIDOR_FLR_3 | 3.6597 | 18.58 | 0.0000 | |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 1.00 | ROOM_1_FLR_6 | GENERAL | ROOM_1_FLR_6 | 10.0642 | 26.01 | 6.7500 | |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 1.00 | ROOM_2_FLR_6 | GENERAL | ROOM_2_FLR_6 | 10.0642 | 26.01 | 6.7500 | |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 9.00 | ROOM_3_MULT9_FLR_6 | GENERAL | ROOM_3_MULT9_FLR_6 | 10.0642 | 16.35 | 10.5200 | |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1.00 | BANQUET_FLR_6 | GENERAL | BANQUET_FLR_6 | 12.8090 | 1.33 | 67.8200 | |
DINING_FLR_6 | 331.66 | Yes | Yes | 1.00 | DINING_FLR_6 | GENERAL | DINING_FLR_6 | 12.8090 | 1.33 | 67.8200 | |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 1.00 | KITCHEN_FLR_6 | GENERAL | KITCHEN_FLR_6 | 10.9792 | 4.65 | 2936.4163 | |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1.00 | CORRIDOR_FLR_6 | GENERAL | CORRIDOR_FLR_6 | 3.6597 | 18.58 | 0.0000 | |
Total | 11345.29 | 8.9207 | 3.54 | 41.0885 | |||||||
Conditioned Total | 11345.29 | 8.9207 | 3.54 | 41.0885 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 11345.29 | 11345.29 | 0.00 | 0.00 | 4.6908 | 8.82 | 37.2165 |
Total | 11345.29 | 11345.29 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:58:38
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 10-AUG-18:10 | 16-JAN-17:40 | - | - | - | - | - | - | - | - | - | - | 02-JAN-21:10 |
Heating | 0.00 | 169647.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 202014.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 82800.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 79617.06 | 87521.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 32686.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 75156.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 9887.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 16416.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 4636.22 | 265990.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 2932.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 506147.55 | 523159.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 169647.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 202014.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 82800.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 49434.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 29240.64 | 74976.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 515.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 425.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 12545.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 1560.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 30153.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 972.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 75156.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 9887.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 16416.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 4636.22 | 265990.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 642.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 1186.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 1102.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:58:38
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 2090.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 2293.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 3718.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 828.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 5546.36 | 1939.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 2152.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 5838.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 502.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 1193.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 287.50 | 3510.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 235.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 22597.00 | 7540.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 184.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 202.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 327.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 73.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 488.87 | 170.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 189.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 514.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 44.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 105.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 25.34 | 309.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 20.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1991.75 | 664.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 184.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 202.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 327.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 73.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 488.87 | 170.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 189.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 514.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 44.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 105.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 25.34 | 309.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 20.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1991.75 | 664.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:58:38
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
BASEMENT VAV BOX COMPONENT | 2.54 | 0.594811 | 0.995000 | 2.52 | 1.00 | 0.500000 | 0.000641 | 0.000115 | 2.52 | 16.70 | 0.008000 |
RETAIL_1_FLR_1 VAV BOX COMPONENT | 0.482585 | 0.105905 | 0.995000 | 0.480172 | 0.995000 | 0.500000 | 0.003598 | 0.000042 | 0.480172 | 16.70 | 0.008000 |
RETAIL_2_FLR_1 VAV BOX COMPONENT | 0.241220 | 0.245351 | 0.995000 | 0.240014 | 0.995000 | 0.500000 | 0.001553 | 0.000017 | 0.240014 | 16.70 | 0.008000 |
MECH_FLR_1 VAV BOX COMPONENT | 0.230934 | 0.541944 | 0.995000 | 0.229779 | 1.00 | 0.500000 | 0.000703 | 0.000022 | 0.229779 | 16.70 | 0.008000 |
STORAGE_FLR_1 VAV BOX COMPONENT | 0.114284 | 0.631815 | 0.995000 | 0.113713 | 1.00 | 0.500000 | 0.000603 | 0.000012 | 0.113713 | 16.70 | 0.008000 |
LAUNDRY_FLR_1 VAV BOX COMPONENT | 3.30 | 0.071507 | 0.995000 | 3.28 | 0.995000 | 0.500000 | 0.021143 | 0.000165 | 3.28 | 16.70 | 0.008000 |
CAFE_FLR_1 VAV BOX COMPONENT | 1.89 | 0.076094 | 0.995000 | 1.88 | 0.995000 | 0.500000 | 0.005007 | 0.000137 | 1.88 | 16.70 | 0.008000 |
LOBBY_FLR_1 VAV BOX COMPONENT | 5.23 | 0.190567 | 0.995000 | 5.20 | 0.995000 | 0.500000 | 0.001999 | 0.000354 | 5.20 | 16.70 | 0.008000 |
CORRIDOR_FLR_3 VAV BOX COMPONENT | 1.29 | 0.918927 | 0.995000 | 1.29 | 1.00 | 0.500000 | 0.000415 | 0.000130 | 1.29 | 16.70 | 0.008000 |
BANQUET_FLR_6 VAV BOX COMPONENT | 2.21 | 0.114611 | 0.995000 | 2.19 | 0.995000 | 0.500000 | 0.003324 | 0.000148 | 2.19 | 16.70 | 0.008000 |
DINING_FLR_6 VAV BOX COMPONENT | 2.31 | 0.109260 | 0.995000 | 2.30 | 0.995000 | 0.500000 | 0.003487 | 0.000153 | 2.30 | 16.70 | 0.008000 |
KITCHEN_FLR_6 VAV BOX COMPONENT | 2.33 | 0.811318 | 0.995000 | 2.32 | 0.995000 | 0.500000 | 0.011262 | 0.000113 | 2.32 | 16.70 | 0.008000 |
CORRIDOR_FLR_6 VAV BOX COMPONENT | 0.767096 | 0.409387 | 0.995000 | 0.763260 | 1.00 | 0.500000 | 0.000931 | 0.000085 | 0.763260 | 16.70 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
BASEMENT VAV BOX REHEAT COIL | 13128.07 | 0.000115 | 273.76 |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 4813.58 | 0.000042 | 105.47 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 1983.83 | 0.000017 | 42.67 |
MECH_FLR_1 VAV BOX REHEAT COIL | 2535.33 | 0.000022 | 56.15 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | 1427.35 | 0.000012 | 32.13 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 18839.94 | 0.000165 | 394.97 |
CAFE_FLR_1 VAV BOX REHEAT COIL | 15667.23 | 0.000137 | 337.23 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | 40467.87 | 0.000354 | 866.12 |
ROOM_1_FLR_3 FAN COIL HEATING COIL | 5261.29 | 0.000046 | 150.35 |
ROOM_2_FLR_3 FAN COIL HEATING COIL | 5264.82 | 0.000046 | 150.45 |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | 30250.93 | 0.000265 | 864.48 |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | 30331.96 | 0.000265 | 866.79 |
ROOM_5_FLR_3 FAN COIL HEATING COIL | 5268.99 | 0.000046 | 150.57 |
ROOM_6_FLR_3 FAN COIL HEATING COIL | 5272.51 | 0.000046 | 150.67 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 14846.53 | 0.000130 | 330.62 |
ROOM_1_FLR_6 FAN COIL HEATING COIL | 1644.48 | 0.000014 | 46.99 |
ROOM_2_FLR_6 FAN COIL HEATING COIL | 1646.29 | 0.000014 | 47.04 |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | 7921.49 | 0.000069 | 226.36 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | 16879.03 | 0.000148 | 360.95 |
DINING_FLR_6 VAV BOX REHEAT COIL | 17540.15 | 0.000153 | 374.81 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | 12866.46 | 0.000113 | 269.25 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 9755.86 | 0.000085 | 220.18 |
VAV WITH REHEAT HEATING COIL | 170625.59 | 0.001493 | 2912.96 |
FLR_3_DOAS HEATING COIL | 15340.96 | 0.000134 | 261.90 |
User-Specified Maximum Flow Rate [m3/s] | |
LOBBY_FLR_1 EXHAUST FAN | 0.000000 |
BANQUET_FLR_6 EXHAUST FAN | 0.000000 |
DINING_FLR_6 EXHAUST FAN | 0.000000 |
Design Size Maximum Air Flow Rate [m3/s] | |
ROOM_1_FLR_3 DIRECT AIR | 0.061735 |
ROOM_2_FLR_3 DIRECT AIR | 0.061728 |
ROOM_3_MULT19_FLR_3 DIRECT AIR | 0.837072 |
ROOM_4_MULT19_FLR_3 DIRECT AIR | 0.837300 |
ROOM_5_FLR_3 DIRECT AIR | 0.061735 |
ROOM_6_FLR_3 DIRECT AIR | 0.061728 |
ROOM_1_FLR_6 DIRECT AIR | 0.015434 |
ROOM_2_FLR_6 DIRECT AIR | 0.015432 |
ROOM_3_MULT9_FLR_6 DIRECT AIR | 0.099154 |
Design Size Maximum Supply Air Flow Rate [m3/s] | Design Size Maximum Hot Water Flow [m3/s] | Design Size Maximum Cold Water Flow [m3/s] | |
ROOM_1_FLR_3 FAN COIL | 1.29 | 0.000046 | 0.000550 |
ROOM_2_FLR_3 FAN COIL | 1.17 | 0.000046 | 0.000498 |
ROOM_3_MULT19_FLR_3 FAN COIL | 9.18 | 0.000265 | 0.003862 |
ROOM_4_MULT19_FLR_3 FAN COIL | 6.05 | 0.000265 | 0.002697 |
ROOM_5_FLR_3 FAN COIL | 1.16 | 0.000046 | 0.000495 |
ROOM_6_FLR_3 FAN COIL | 1.06 | 0.000046 | 0.000453 |
ROOM_1_FLR_6 FAN COIL | 0.341617 | 0.000014 | 0.000146 |
ROOM_2_FLR_6 FAN COIL | 0.307209 | 0.000014 | 0.000131 |
ROOM_3_MULT9_FLR_6 FAN COIL | 1.86 | 0.000069 | 0.000800 |
Design Size Maximum Flow Rate [m3/s] | |
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | 1.29 |
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | 1.17 |
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | 9.18 |
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | 6.05 |
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | 1.16 |
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | 1.06 |
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | 0.341617 |
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | 0.307209 |
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | 1.86 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Temperature [C] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | Design Size Design Coil Load [W] | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | 22.51 | 6.70 | 0.008562 | 12.80 | 0.008500 | 0.000550 | 1.29 | |
ROOM_2_FLR_3 FAN COIL COOLING COIL | 22.51 | 6.70 | 0.008569 | 12.80 | 0.008500 | 0.000498 | 1.17 | |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | 22.51 | 6.70 | 0.008504 | 12.80 | 0.008500 | 0.003862 | 9.18 | |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | 22.51 | 6.70 | 0.008738 | 12.80 | 0.008500 | 0.002697 | 6.05 | |
ROOM_5_FLR_3 FAN COIL COOLING COIL | 22.51 | 6.70 | 0.008569 | 12.80 | 0.008500 | 0.000495 | 1.16 | |
ROOM_6_FLR_3 FAN COIL COOLING COIL | 22.51 | 6.70 | 0.008576 | 12.80 | 0.008500 | 0.000453 | 1.06 | |
ROOM_1_FLR_6 FAN COIL COOLING COIL | 22.51 | 6.70 | 0.008559 | 12.80 | 0.008500 | 0.000146 | 0.341617 | |
ROOM_2_FLR_6 FAN COIL COOLING COIL | 22.51 | 6.70 | 0.008565 | 12.80 | 0.008500 | 0.000131 | 0.307209 | |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | 22.51 | 6.70 | 0.008594 | 12.80 | 0.008500 | 0.000800 | 1.86 | |
VAV WITH REHEAT COOLING COIL | 29.40 | 6.70 | 0.008822 | 10.95 | 0.008500 | 0.019008 | 22.82 | 532172.51 |
FLR_3_DOAS COOLING COIL | 29.40 | 6.70 | 0.008822 | 11.92 | 0.008500 | 0.001623 | 2.05 | 45447.84 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV WITH REHEAT | 22.82 | 22.82 | 22.93 | 22.82 | 22.82 | 22.82 | 0.300000 | 1.00 | 22.82 |
FLR_3_DOAS | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 0.300000 | 1.00 | 2.05 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV WITH REHEAT_OA_CONTROLLER | 22.82 | 22.81 |
FLR_3_DOAS_OA_CONTROLLER | 2.05 | 2.05 |
Design Size Nominal Supply Air Flow Rate [m3/s] | |
VAV WITH REHEAT OA HEAT RECOVERY | 22.81 |
Design Size Maximum Flow Rate [m3/s] | |
VAV WITH REHEAT FAN | 22.82 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV WITH REHEAT_COOLC_CONTROLLER | 0.019008 | 0.000025 |
VAV WITH REHEAT_HEATC_CONTROLLER | 0.001493 | |
FLR_3_DOAS_COOLC_CONTROLLER | 0.001623 | 0.000293 |
FLR_3_DOAS_HEATC_CONTROLLER | 0.000134 |
User-Specified Maximum Flow Rate [m3/s] | |
FLR_3_DOAS FAN | 2.05 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.030264 | 6236.24 | |
HEATSYS1 PUMP | 0.003933 | 1184.48 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
HEATSYS1 | 0.003933 | 0.471975 |
COOLSYS1 | 0.030264 | 3.63 |
SWHSYS1 | 0.000375 | 0.045004 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 449580.52 | 449580.52 | 0.003933 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 PUMP | 0.030264 | 4317.56 |
SWHSYS1 PUMP | 0.000375 | 47.91 |
Design Size Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Fluid Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.030264 | 847304.77 | 847934.14 | 96.66 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000375 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:58:38
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesPossible Shadow Receivers | |
RETAIL_1_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
CAFE_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
LOBBY_FLR_1_CEILING_2 | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
Possible Shadow Receivers | |
RETAIL_1_FLR_1_WALL_SOUTH | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | |
RETAIL_2_FLR_1_WALL_WEST | RETAIL_2_FLR_1_WALL_WEST_DOOR | |
STORAGE_FLR_1_WALL_NORTH | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | |
LAUNDRY_FLR_1_WALL_EAST | LAUNDRY_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_EAST | CAFE_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_SOUTH | CAFE_FLR_1_WALL_SOUTH_WINDOW | |
LOBBY_FLR_1_WALL_1_NORTH | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | |
LOBBY_FLR_1_WALL_1_SOUTH | LOBBY_FLR_1_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_SOUTH | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_WEST | ROOM_1_FLR_3_WALL_WEST_WINDOW | |
ROOM_2_FLR_3_WALL_NORTH | ROOM_2_FLR_3_WALL_NORTH_WINDOW | |
ROOM_2_FLR_3_WALL_WEST | ROOM_2_FLR_3_WALL_WEST_WINDOW | |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_4_MULT19_FLR_3_WALL_NORTH | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | |
ROOM_5_FLR_3_WALL_EAST | ROOM_5_FLR_3_WALL_EAST_WINDOW | |
ROOM_5_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_6_FLR_3_WALL_NORTH | ROOM_6_FLR_3_WALL_NORTH_WINDOW | |
ROOM_6_FLR_3_WALL_EAST | ROOM_6_FLR_3_WALL_EAST_WINDOW | |
CORRIDOR_FLR_3_WALL_1_NORTH | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_NORTH | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_SOUTH | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_WEST | ROOM_1_FLR_6_WALL_WEST_WINDOW | |
ROOM_2_FLR_6_WALL_NORTH | ROOM_2_FLR_6_WALL_NORTH_WINDOW | |
ROOM_2_FLR_6_WALL_WEST | ROOM_2_FLR_6_WALL_WEST_WINDOW | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | |
BANQUET_FLR_6_WALL_NORTH | BANQUET_FLR_6_WALL_NORTH_WINDOW | |
DINING_FLR_6_WALL_NORTH | DINING_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_NORTH | KITCHEN_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_EAST | KITCHEN_FLR_6_WALL_EAST_WINDOW | |
KITCHEN_FLR_6_WALL_1_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_6_WALL_1_NORTH | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_NORTH | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:58:38
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:58:38
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 11.40 | 8.10 | 5.40 | 4.50 | 5.80 | 8.30 | 10.90 | 13.00 | 15.60 | 17.70 | 18.80 | 15.10 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 | 47.47 | -122.32 | -8.00 | 122.00 | 99868 | 1.1870 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 11.22 | 14.30 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | HotelLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | DOE-2 |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 22 | 235 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 41.45 | 11.51 | -1.22 | 1 | 1 | 1 | 0.00 | 86.56 | 0.00 | 22.86 | -2.44 | 0.00 | 2.44 | 4826.41 | TARP | DOE-2 | 1978.83 | 0.00 | 0.00 | 0.00 | 13 | 0 | 0 | Yes |
2 | RETAIL_1_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 2.90 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 265.76 | TARP | DOE-2 | 67.07 | 68.84 | 45.58 | 23.26 | 6 | 1 | 0 | Yes |
3 | RETAIL_2_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 9.14 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 5.79 | 12.50 | 0.00 | 3.96 | 3.96 | 307.76 | TARP | DOE-2 | 77.67 | 26.57 | 24.62 | 0.00 | 6 | 1 | 0 | Yes |
4 | MECH_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 61.87 | 17.68 | 1.98 | 1 | 1 | 1 | 53.95 | 69.80 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 650.80 | TARP | DOE-2 | 164.24 | 62.80 | 62.80 | 0.00 | 6 | 0 | 0 | Yes |
5 | STORAGE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 74.37 | 17.68 | 1.98 | 1 | 1 | 1 | 69.80 | 78.94 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 375.47 | TARP | DOE-2 | 94.76 | 36.23 | 28.80 | 0.00 | 6 | 1 | 0 | Yes |
6 | LAUNDRY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 14.33 | 1.98 | 1 | 1 | 1 | 81.99 | 86.56 | 5.79 | 22.86 | 0.00 | 3.96 | 3.96 | 309.22 | TARP | DOE-2 | 78.04 | 85.75 | 83.80 | 0.00 | 6 | 1 | 0 | Yes |
7 | CAFE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 70.26 | 2.90 | 1.98 | 1 | 1 | 1 | 53.95 | 86.56 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 748.35 | TARP | DOE-2 | 188.86 | 152.17 | 84.72 | 65.50 | 7 | 2 | 0 | Yes |
8 | LOBBY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 38.29 | 12.45 | 1.98 | 1 | 1 | 1 | 0.00 | 81.99 | 0.00 | 22.86 | 0.00 | 3.96 | 3.96 | 5183.56 | TARP | DOE-2 | 1308.19 | 434.79 | 345.80 | 85.08 | 18 | 3 | 0 | Yes |
9 | ROOM_1_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
10 | ROOM_2_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
11 | ROOM_3_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 8.53 | 9.14 | 8.53 | 1 | 76 | 1 | 6.71 | 10.36 | 5.79 | 12.50 | 7.01 | 10.06 | 3.05 | 74.75 | TARP | DOE-2 | 24.52 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
12 | ROOM_4_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 12.19 | 19.51 | 8.53 | 1 | 76 | 1 | 10.36 | 14.02 | 16.15 | 22.86 | 7.01 | 10.06 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
13 | ROOM_5_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 10.06 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
14 | ROOM_6_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 18.59 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
15 | CORRIDOR_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 43.28 | 14.33 | 8.53 | 1 | 4 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 7.01 | 10.06 | 3.05 | 1186.91 | TARP | DOE-2 | 389.40 | 48.31 | 32.37 | 15.94 | 20 | 4 | 0 | Yes |
16 | ROOM_1_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 16.15 | 19.20 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
17 | ROOM_2_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 16.15 | 19.20 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
18 | ROOM_3_MULT9_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 7.93 | 7.62 | 17.68 | 1 | 9 | 1 | 4.57 | 11.28 | 5.79 | 9.45 | 16.15 | 19.20 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 20.44 | 13.70 | 6.74 | 6 | 1 | 0 | Yes |
19 | BANQUET_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 26.37 | 17.68 | 17.68 | 1 | 1 | 1 | 10.36 | 42.37 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.36 | 32.19 | 6 | 1 | 0 | Yes |
20 | DINING_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 63.55 | 17.68 | 17.68 | 1 | 1 | 1 | 47.55 | 79.55 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.36 | 32.19 | 6 | 1 | 0 | Yes |
21 | KITCHEN_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 82.99 | 14.11 | 17.68 | 1 | 1 | 1 | 79.55 | 86.56 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 314.87 | TARP | DOE-2 | 103.30 | 87.33 | 60.96 | 26.37 | 8 | 3 | 0 | Yes |
22 | CORRIDOR_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 41.51 | 13.35 | 17.68 | 1 | 1 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 1256.16 | TARP | DOE-2 | 412.12 | 85.47 | 57.27 | 28.20 | 15 | 3 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 1978.83 | 106.5 | 18.581 | 5.382E-002 | 8.749 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 14.129 | No |
2 | RETAIL_1_FLR_1 | 67.07 | 10.8 | 6.194 | 0.161 | 13.012 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 23.772 | No |
3 | RETAIL_2_FLR_1 | 77.67 | 12.5 | 6.194 | 0.161 | 13.012 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 23.772 | No |
4 | MECH_FLR_1 | 164.24 | 2.7 | 61.932 | 1.615E-002 | 10.064 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 15.444 | No |
5 | STORAGE_FLR_1 | 94.76 | 2.0 | 46.451 | 2.153E-002 | 7.319 | 2.690 | 0.000 | 0.000 | 0.000 | 0.000 | 10.009 | No |
6 | LAUNDRY_FLR_1 | 78.04 | 8.4 | 9.290 | 0.108 | 5.490 | 61.680 | 535.850 | 0.000 | 0.000 | 0.000 | 603.020 | No |
7 | CAFE_FLR_1 | 188.86 | 142.3 | 1.327 | 0.753 | 12.809 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 18.189 | No |
8 | LOBBY_FLR_1 | 1308.19 | 422.4 | 3.097 | 0.323 | 10.064 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.134 | No |
9 | ROOM_1_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 10.064 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 16.814 | No |
10 | ROOM_2_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 10.064 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 16.814 | No |
11 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 16.349 | 6.116E-002 | 10.064 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 20.584 | No |
12 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 10.064 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 20.584 | No |
13 | ROOM_5_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 10.064 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 16.814 | No |
14 | ROOM_6_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 10.064 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 16.814 | No |
15 | CORRIDOR_FLR_3 | 389.40 | 21.0 | 18.581 | 5.382E-002 | 3.660 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 3.660 | No |
16 | ROOM_1_FLR_6 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 10.064 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 16.814 | No |
17 | ROOM_2_FLR_6 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 10.064 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 16.814 | No |
18 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 10.064 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 20.584 | No |
19 | BANQUET_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 12.809 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 80.629 | No |
20 | DINING_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 12.809 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 80.629 | No |
21 | KITCHEN_FLR_6 | 103.30 | 22.2 | 4.645 | 0.215 | 10.979 | 517.156 | 2419.260 | 0.000 | 0.000 | 0.000 | 2947.395 | No |
22 | CORRIDOR_FLR_6 | 412.12 | 22.2 | 18.581 | 5.382E-002 | 3.660 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 3.660 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | BASEMENT PEOPLE | BLDG_OCC_SCH | BASEMENT | 1978.83 | 106.5 | 106.5 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 106 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | RETAIL_1_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 10.8 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | RETAIL_2_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 12.5 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 13 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | LAUNDRY_FLR_1 PEOPLE | BLDG_OCC_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 8.4 | 0.108 | 9.290 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 8 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | CAFE_FLR_1 PEOPLE | BLDG_OCC_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 142.3 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 142 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | LOBBY_FLR_1 PEOPLE | BLDG_OCC_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 422.4 | 0.323 | 3.097 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 422 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | ROOM_1_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | ROOM_2_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | ROOM_3_MULT19_FLR_3 PEOPLE | ALWAYS_OFF | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 1.5 | 6.116E-002 | 16.349 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 0 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | ROOM_4_MULT19_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | ROOM_5_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | ROOM_6_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | ROOM_1_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | ROOM_2_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | ROOM_3_MULT9_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | BANQUET_FLR_6 PEOPLE | BLDG_OCC_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | DINING_FLR_6 PEOPLE | BLDG_OCC_SCH | DINING_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | KITCHEN_FLR_6 PEOPLE | BLDG_OCC_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 22.2 | 0.215 | 4.645 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | STORAGE_FLR_1 PEOPLE | BLDG_OCC_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 2.0 | 2.153E-002 | 46.451 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | CORRIDOR_FLR_3 PEOPLE | BLDG_OCC_SCH | CORRIDOR_FLR_3 | 389.40 | 21.0 | 21.0 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 21 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
21 | CORRIDOR_FLR_6 PEOPLE | BLDG_OCC_SCH | CORRIDOR_FLR_6 | 412.12 | 22.2 | 22.2 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
22 | MECH_FLR_1 PEOPLE | BLDG_OCC_SCH | MECH_FLR_1 | 164.24 | 2.7 | 2.7 | 1.615E-002 | 61.932 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 3 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_BASEMENT | BASEMENT | 1978.83 | 106.5 | 17313.725 | 8.749 | 162.572 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 17313.725 |
2 | RETAIL_1_FLR_1_LIGHTS | LTG_SCH_RETAIL | RETAIL_1_FLR_1 | 67.07 | 10.8 | 872.757 | 13.012 | 80.594 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 872.757 |
3 | RETAIL_2_FLR_1_LIGHTS | LTG_SCH_RETAIL | RETAIL_2_FLR_1 | 77.67 | 12.5 | 1010.656 | 13.012 | 80.595 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1010.656 |
4 | MECH_FLR_1_LIGHTS | LTG_SCH_MECHANIC | MECH_FLR_1 | 164.24 | 2.7 | 1652.984 | 10.064 | 623.297 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1652.984 |
5 | STORAGE_FLR_1_LIGHTS | LTG_SCH_STORAGE | STORAGE_FLR_1 | 94.76 | 2.0 | 693.586 | 7.319 | 339.993 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 693.586 |
6 | LAUNDRY_FLR_1_LIGHTS | LTG_SCH_LAUNDRY | LAUNDRY_FLR_1 | 78.04 | 8.4 | 428.405 | 5.490 | 51.001 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 428.405 |
7 | CAFE_FLR_1_LIGHTS | LTG_SCH_DINING | CAFE_FLR_1 | 188.86 | 142.3 | 2419.140 | 12.809 | 17.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2419.140 |
8 | LOBBY_FLR_1_LIGHTS | LTG_SCH_LOBBY | LOBBY_FLR_1 | 1308.19 | 422.4 | 13165.908 | 10.064 | 31.167 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 13165.908 |
9 | ROOM_1_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_1_FLR_3 | 39.02 | 1.5 | 392.727 | 10.064 | 261.818 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 392.727 |
10 | ROOM_2_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_2_FLR_3 | 39.02 | 1.5 | 392.681 | 10.064 | 261.787 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 392.681 |
11 | ROOM_3_MULT19_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 246.814 | 10.064 | 164.543 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 246.814 |
12 | ROOM_4_MULT19_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 246.881 | 10.064 | 164.588 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 246.881 |
13 | ROOM_5_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_5_FLR_3 | 39.02 | 1.5 | 392.727 | 10.064 | 261.818 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 392.727 |
14 | ROOM_6_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_6_FLR_3 | 39.02 | 1.5 | 392.681 | 10.064 | 261.787 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 392.681 |
15 | CORRIDOR_FLR_3_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_FLR_3 | 389.40 | 21.0 | 1425.114 | 3.660 | 68.002 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1425.114 |
16 | ROOM_1_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_1_FLR_6 | 39.02 | 1.5 | 392.727 | 10.064 | 261.818 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 392.727 |
17 | ROOM_2_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_2_FLR_6 | 39.02 | 1.5 | 392.681 | 10.064 | 261.787 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 392.681 |
18 | ROOM_3_MULT9_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 246.881 | 10.064 | 164.588 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 246.881 |
19 | BANQUET_FLR_6_LIGHTS | LTG_SCH_DINING | BANQUET_FLR_6 | 331.66 | 249.9 | 4248.214 | 12.809 | 17.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 4248.214 |
20 | DINING_FLR_6_LIGHTS | LTG_SCH_DINING | DINING_FLR_6 | 331.66 | 249.9 | 4248.214 | 12.809 | 17.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 4248.214 |
21 | KITCHEN_FLR_6_LIGHTS | LTG_SCH_KITCHEN | KITCHEN_FLR_6 | 103.30 | 22.2 | 1134.198 | 10.979 | 51.003 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1134.198 |
22 | CORRIDOR_FLR_6_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_FLR_6 | 412.12 | 22.2 | 1508.264 | 3.660 | 68.001 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1508.264 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | BASEMENT_EQUIP_SCH | BASEMENT | 1978.83 | 106.5 | 10646.106 | 5.380 | 99.964 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10646.106 |
2 | RETAIL_1_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 721.688 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 721.688 |
3 | RETAIL_2_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 835.717 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 835.717 |
4 | MECH_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | MECH_FLR_1 | 164.24 | 2.7 | 883.628 | 5.380 | 333.193 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 883.628 |
5 | STORAGE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 254.902 | 2.690 | 124.952 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 254.902 |
6 | LAUNDRY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 4813.474 | 61.680 | 573.033 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 4813.474 |
7 | CAFE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 1016.077 | 5.380 | 7.140 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1016.077 |
8 | LOBBY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 10557.062 | 8.070 | 24.991 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10557.062 |
9 | ROOM_1_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_1_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
10 | ROOM_2_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_2_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
11 | ROOM_3_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 257.991 | 10.520 | 171.994 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 257.991 |
12 | ROOM_4_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
13 | ROOM_5_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_5_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
14 | ROOM_6_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_6_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
15 | ROOM_1_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_1_FLR_6 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
16 | ROOM_2_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_2_FLR_6 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
17 | ROOM_3_MULT9_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
18 | BANQUET_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
19 | DINING_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | DINING_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
20 | KITCHEN_FLR_6_MISCELEC_EQUIP | KITCHEN_ELEC_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 52482.799 | 508.040 | 2360.050 | 0.200 | 0.500 | 0.100 | 0.200 | Cooking | 0.000 | 15744.840 |
21 | KITCHEN_FLR_6_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 515.917 | 4.994 | 23.200 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 515.917 | 515.917 |
22 | KITCHEN_FLR_6_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 425.833 | 4.122 | 19.149 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 425.833 | 425.833 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LAUNDRY_FLR_1_MISCGAS_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 41817.449 | 535.850 | 4978.268 | 0.000 | 0.500 | 0.000 | 0.500 | Laundry | 0.000 | 41817.449 |
2 | KITCHEN_FLR_6_MISCGAS_EQUIP | KITCHEN_GAS_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 249920.353 | 2419.260 | 11238.437 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 74976.106 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | OVERHEAD DOOR_CON | 2 | 1 | 1 | 0.167 | 1.198 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
3 | INTERIORFURNISHINGS | 3 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 8 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 18 | 3 | 3 | 0.167 | 0.2284 | 0.900 | 0.900 | 0.770 | 0.700 | Rough |
6 | RES_ROOF | 19 | 3 | 3 | 0.167 | 0.2284 | 0.900 | 0.900 | 0.770 | 0.700 | Rough |
7 | NONRES_EXT_WALL_GRD | 21 | 3 | 9 | 0.167 | 0.7376 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | NONRES_EXT_WALL_MID | 22 | 3 | 9 | 0.167 | 1.016 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | NONRES_EXT_WALL_TOP | 23 | 3 | 9 | 0.167 | 1.081 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | RES_EXT_WALL_MID | 25 | 3 | 9 | 0.167 | 1.016 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | RES_EXT_WALL_TOP | 26 | 3 | 9 | 0.167 | 1.081 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | NONRES_FLOOR | 30 | 3 | 7 | 0.167 | 0.1963 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
13 | NONRES_FLOOR_CEILING | 33 | 3 | 7 | 0.167 | 0.1963 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
14 | BASEMENT_FLOOR | 36 | 2 | 7 | 0.333 | 2.705 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
15 | BASEMENT_WALL_NORTH_CFACTOR | 39 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | BASEMENT_WALL_EAST_CFACTOR | 40 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | BASEMENT_WALL_SOUTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
18 | BASEMENT_WALL_WEST_CFACTOR | 42 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8346 |
3 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
10 | RES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
11 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
12 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
13 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.188 |
14 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8173 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7574 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | RES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8173 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
25 | RES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7574 |
26 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
27 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.833 |
28 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
29 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
30 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
31 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
32 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.833 |
33 | M10 200MM CONCRETE BLOCK BASEMENT WALL | 0.2032 | 1.326 | 1842.000 | 912.000 | 0.1532 |
34 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
35 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
36 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
37 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
38 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
39 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
40 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
41 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
42 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
4 | 0 | 1.1981135 | 1.1981135 | 1.1981135 | |
5 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
6 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
7 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
8 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
9 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
10 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
11 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
12 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
13 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
14 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
15 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
16 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
17 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
18 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
19 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
20 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
21 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
22 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
23 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
24 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
25 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
26 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
27 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
28 | 9 | -0.36178815E-14 | 0.27139057E-16 | -0.15868385E-09 | 0.72384540E-16 |
29 | 8 | 0.23132903E-07 | 0.10021651E-12 | 0.39088690E-03 | -0.26302905E-09 |
30 | 7 | -0.12631865E-01 | 0.51350721E-08 | -0.23647662E-01 | 0.14362891E-03 |
31 | 6 | 0.41595524 | 0.17798199E-05 | 0.48111272 | -0.48727686E-02 |
32 | 5 | -5.2940477 | 0.66244475E-04 | -4.5105076 | 0.64467011E-01 |
33 | 4 | 33.460551 | 0.54034224E-03 | 21.710910 | -0.42819988 |
34 | 3 | -112.19991 | 0.11746209E-02 | -56.158897 | 1.5292621 |
35 | 2 | 198.09612 | 0.65921779E-03 | 78.365567 | -2.9160408 |
36 | 1 | -171.52093 | 0.70225444E-04 | -55.397708 | 2.7518339 |
37 | 0 | 57.057407 | 0.39880044E-06 | 15.535293 | |
38 | 9 | -0.27488611E-15 | 0.34931277E-16 | -0.14567168E-09 | -0.34479422E-18 |
39 | 8 | 0.21305634E-07 | 0.13616114E-12 | 0.37179150E-03 | -0.24225240E-09 |
40 | 7 | -0.12062412E-01 | 0.71136536E-08 | -0.22827857E-01 | 0.13715401E-03 |
41 | 6 | 0.40048261 | 0.24848663E-05 | 0.46794369 | -0.46903832E-02 |
42 | 5 | -5.1430590 | 0.93107898E-04 | -4.4094005 | 0.62594814E-01 |
43 | 4 | 32.792724 | 0.76407468E-03 | 21.315792 | -0.41933293 |
44 | 3 | -110.77914 | 0.16699767E-02 | -55.377787 | 1.5087354 |
45 | 2 | 196.68811 | 0.94174532E-03 | 77.649029 | -2.8936813 |
46 | 1 | -171.00089 | 0.10077048E-03 | -55.189078 | 2.7427195 |
47 | 0 | 57.057407 | 0.57514079E-06 | 15.569530 | |
48 | 9 | 0.31336604E-16 | 0.39008580E-16 | -0.14256869E-09 | 0.20136749E-17 |
49 | 8 | 0.20868940E-07 | 0.14443760E-12 | 0.36714717E-03 | -0.23728702E-09 |
50 | 7 | -0.11923636E-01 | 0.75824706E-08 | -0.22627983E-01 | 0.13557608E-03 |
51 | 6 | 0.39671154 | 0.26538398E-05 | 0.46472729 | -0.46459316E-02 |
52 | 5 | -5.1062546 | 0.99607489E-04 | -4.3846760 | 0.62138459E-01 |
53 | 4 | 32.629908 | 0.81865718E-03 | 21.219102 | -0.41717122 |
54 | 3 | -110.43267 | 0.17916944E-02 | -55.186609 | 1.5037299 |
55 | 2 | 196.34465 | 0.10116009E-02 | 77.473776 | -2.8882273 |
56 | 1 | -170.87399 | 0.10836560E-03 | -55.138279 | 2.7404955 |
57 | 0 | 57.057407 | 0.61925266E-06 | 15.578052 | |
58 | 9 | -0.27488611E-15 | 0.34931277E-16 | -0.14567168E-09 | -0.34479422E-18 |
59 | 8 | 0.21305634E-07 | 0.13616114E-12 | 0.37179150E-03 | -0.24225240E-09 |
60 | 7 | -0.12062412E-01 | 0.71136536E-08 | -0.22827857E-01 | 0.13715401E-03 |
61 | 6 | 0.40048261 | 0.24848663E-05 | 0.46794369 | -0.46903832E-02 |
62 | 5 | -5.1430590 | 0.93107898E-04 | -4.4094005 | 0.62594814E-01 |
63 | 4 | 32.792724 | 0.76407468E-03 | 21.315792 | -0.41933293 |
64 | 3 | -110.77914 | 0.16699767E-02 | -55.377787 | 1.5087354 |
65 | 2 | 196.68811 | 0.94174532E-03 | 77.649029 | -2.8936813 |
66 | 1 | -171.00089 | 0.10077048E-03 | -55.189078 | 2.7427195 |
67 | 0 | 57.057407 | 0.57514079E-06 | 15.569530 | |
68 | 9 | 0.31336604E-16 | 0.39008580E-16 | -0.14256869E-09 | 0.20136749E-17 |
69 | 8 | 0.20868940E-07 | 0.14443760E-12 | 0.36714717E-03 | -0.23728702E-09 |
70 | 7 | -0.11923636E-01 | 0.75824706E-08 | -0.22627983E-01 | 0.13557608E-03 |
71 | 6 | 0.39671154 | 0.26538398E-05 | 0.46472729 | -0.46459316E-02 |
72 | 5 | -5.1062546 | 0.99607489E-04 | -4.3846760 | 0.62138459E-01 |
73 | 4 | 32.629908 | 0.81865718E-03 | 21.219102 | -0.41717122 |
74 | 3 | -110.43267 | 0.17916944E-02 | -55.186609 | 1.5037299 |
75 | 2 | 196.34465 | 0.10116009E-02 | 77.473776 | -2.8882273 |
76 | 1 | -170.87399 | 0.10836560E-03 | -55.138279 | 2.7404955 |
77 | 0 | 57.057407 | 0.61925266E-06 | 15.578052 | |
78 | 7 | -0.15963512E-14 | -0.15187529E-16 | -0.22427203E-13 | 0.56155309E-15 |
79 | 6 | 0.17983713E-10 | 0.23594901E-11 | 0.52322926E-09 | -0.18637893E-10 |
80 | 5 | -0.60139213E-07 | 0.11510628E-07 | -0.21924491E-05 | 0.17161312E-06 |
81 | 4 | 0.62746279E-04 | 0.43399923E-05 | 0.17681060E-02 | -0.28244642E-03 |
82 | 3 | -0.90508353E-02 | 0.15320797E-03 | -0.21560640 | 0.43341486E-01 |
83 | 2 | 0.12836503 | 0.66328859E-03 | 2.9007871 | -0.61911613 |
84 | 1 | -0.32478029 | 0.41934727E-03 | -7.1379041 | 1.5697129 |
85 | 0 | 0.20664896 | 0.54311639E-05 | 4.4522013 | |
86 | 7 | -0.22427203E-13 | -0.15187529E-16 | -0.15963512E-14 | 0.56155309E-15 |
87 | 6 | 0.52322926E-09 | 0.23594901E-11 | 0.17983713E-10 | -0.18637893E-10 |
88 | 5 | -0.21924491E-05 | 0.11510628E-07 | -0.60139213E-07 | 0.17161312E-06 |
89 | 4 | 0.17681060E-02 | 0.43399923E-05 | 0.62746279E-04 | -0.28244642E-03 |
90 | 3 | -0.21560640 | 0.15320797E-03 | -0.90508353E-02 | 0.43341486E-01 |
91 | 2 | 2.9007871 | 0.66328859E-03 | 0.12836503 | -0.61911613 |
92 | 1 | -7.1379041 | 0.41934727E-03 | -0.32478029 | 1.5697129 |
93 | 0 | 4.4522013 | 0.54311639E-05 | 0.20664896 | |
94 | 7 | -0.52459208E-15 | -0.63961428E-15 | -0.12292524E-09 | -0.35846135E-17 |
95 | 6 | 0.39860198E-02 | 0.96339020E-07 | 0.40499006E-03 | -0.70890431E-04 |
96 | 5 | -0.20832379 | 0.49172556E-04 | -0.20585669E-01 | 0.38489246E-02 |
97 | 4 | 3.5198270 | 0.18993977E-02 | 0.34924834 | -0.69168259E-01 |
98 | 3 | -23.366787 | 0.13311857E-01 | -2.4329538 | 0.50524779 |
99 | 2 | 64.890127 | 0.19943872E-01 | 7.3672511 | -1.5911358 |
100 | 1 | -76.040094 | 0.56792084E-02 | -9.5568013 | 2.1361271 |
101 | 0 | 31.242244 | 0.96490710E-04 | 4.3344156 | |
102 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
103 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
104 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
105 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
106 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
107 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
108 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
109 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
110 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
111 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
112 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
113 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
114 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
115 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
116 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
117 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
118 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
119 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
120 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
121 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
122 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
123 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
124 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
125 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
126 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
127 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
128 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
129 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
130 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
131 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
132 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
133 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.3856_SHGC_0.4 | 37 | 1 | VerySmooth | 2.191 | 2.191 | 1.000 | 0.401 | ||
2 | RESWINDOW_U_0.3856_SHGC_0.4 | 38 | 1 | VerySmooth | 2.191 | 2.191 | 1.000 | 0.401 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER | SpectralAverage | 3.40174E-002 | 0.31435 | 0.47878 | 0.47878 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11969 | 1.00000 | No | |
2 | RESIDENTIAL WINDOW GLAZING LAYER | SpectralAverage | 3.40174E-002 | 0.31435 | 0.47878 | 0.47878 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11969 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 7 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 1.500 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 3.000 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWH BOOSTER E WATER HEATER | 2.2712E-002 | 8000.0 | 1.240 | 1.1473 |
2 | WaterHeater:Mixed | SWH LAUNDRY G WATER HEATER | 1.1356 | 163316.0 | 0.576 | 0.5074 |
3 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 2.2712 | 175842.6 | 0.260 | 2.5713E-002 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
6 | BASEMENT_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
7 | BASEMENT_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
8 | BASEMENT_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
9 | BASEMENT_CEILING_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
10 | BASEMENT_CEILING_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
11 | BASEMENT_CEILING_6 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
12 | BASEMENT_CEILING_7 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
13 | BASEMENT_CEILING_8 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
14 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
15 | RETAIL_1_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 4 | No | No |
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 1 | No | No |
17 | RETAIL_1_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 3 | No | No |
18 | RETAIL_1_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
19 | RETAIL_1_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
20 | RETAIL_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
21 | RETAIL_1_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
23 | RETAIL_2_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
25 | RETAIL_2_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
26 | RETAIL_2_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
27 | RETAIL_2_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
28 | RETAIL_2_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
29 | RETAIL_2_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
31 | MECH_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
32 | MECH_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
33 | MECH_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
34 | MECH_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
35 | MECH_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
36 | MECH_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
37 | MECH_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
38 | STORAGE_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
40 | STORAGE_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
41 | STORAGE_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
42 | STORAGE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
43 | STORAGE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
44 | STORAGE_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
45 | STORAGE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
46 | LAUNDRY_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
47 | LAUNDRY_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
49 | LAUNDRY_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
50 | LAUNDRY_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
51 | LAUNDRY_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
52 | LAUNDRY_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
54 | CAFE_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 3 | No | No |
55 | CAFE_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
56 | CAFE_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 4 | No | No |
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 1 | No | No |
58 | CAFE_FLR_1_WALL_1_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
59 | CAFE_FLR_1_WALL_2_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
60 | CAFE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
61 | CAFE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
62 | CAFE_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
63 | CAFE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
64 | LOBBY_FLR_1_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
67 | LOBBY_FLR_1_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
68 | LOBBY_FLR_1_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 1 | No | No |
70 | LOBBY_FLR_1_WALL_1_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
71 | LOBBY_FLR_1_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
72 | LOBBY_FLR_1_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
73 | LOBBY_FLR_1_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
74 | LOBBY_FLR_1_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
75 | LOBBY_FLR_1_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
76 | LOBBY_FLR_1_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
77 | LOBBY_FLR_1_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
78 | LOBBY_FLR_1_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
79 | LOBBY_FLR_1_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
80 | LOBBY_FLR_1_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
81 | LOBBY_FLR_1_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
82 | LOBBY_FLR_1_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
83 | LOBBY_FLR_1_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
84 | LOBBY_FLR_1_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
85 | LOBBY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
86 | ROOM_1_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
88 | ROOM_1_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
90 | ROOM_1_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
91 | ROOM_1_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
92 | ROOM_1_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
93 | ROOM_1_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
94 | ROOM_1_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
95 | ROOM_2_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
97 | ROOM_2_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
99 | ROOM_2_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
100 | ROOM_2_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
101 | ROOM_2_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
102 | ROOM_2_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
103 | ROOM_2_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
109 | ROOM_3_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
110 | ROOM_3_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
117 | ROOM_4_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
118 | ROOM_4_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
120 | ROOM_5_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
122 | ROOM_5_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
124 | ROOM_5_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
125 | ROOM_5_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
126 | ROOM_5_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
127 | ROOM_5_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
128 | ROOM_5_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
129 | ROOM_6_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
131 | ROOM_6_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
133 | ROOM_6_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
134 | ROOM_6_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
135 | ROOM_6_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
136 | ROOM_6_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
137 | ROOM_6_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
138 | CORRIDOR_FLR_3_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
147 | CORRIDOR_FLR_3_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
148 | CORRIDOR_FLR_3_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
149 | CORRIDOR_FLR_3_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
150 | CORRIDOR_FLR_3_WALL_4_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
152 | CORRIDOR_FLR_3_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
153 | CORRIDOR_FLR_3_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
154 | CORRIDOR_FLR_3_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
155 | CORRIDOR_FLR_3_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
156 | CORRIDOR_FLR_3_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
157 | CORRIDOR_FLR_3_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
158 | CORRIDOR_FLR_3_FLOOR_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
159 | CORRIDOR_FLR_3_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
160 | CORRIDOR_FLR_3_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
161 | CORRIDOR_FLR_3_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
163 | ROOM_1_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
165 | ROOM_1_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
167 | ROOM_1_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
168 | ROOM_1_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
169 | ROOM_1_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
170 | ROOM_1_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
171 | ROOM_1_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
172 | ROOM_2_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
174 | ROOM_2_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
176 | ROOM_2_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
177 | ROOM_2_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
178 | ROOM_2_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
179 | ROOM_2_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
180 | ROOM_2_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 3 | No | No |
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 2 | No | No |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
186 | ROOM_3_MULT9_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
187 | ROOM_3_MULT9_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
189 | BANQUET_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
191 | BANQUET_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
192 | BANQUET_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
193 | BANQUET_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
194 | BANQUET_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
195 | BANQUET_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
196 | BANQUET_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
197 | DINING_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
198 | DINING_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
199 | DINING_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
200 | DINING_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
201 | DINING_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
202 | DINING_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
203 | DINING_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
204 | DINING_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
205 | KITCHEN_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
207 | KITCHEN_FLR_6_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
212 | KITCHEN_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
213 | KITCHEN_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
214 | KITCHEN_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
215 | KITCHEN_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
216 | KITCHEN_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
217 | CORRIDOR_FLR_6_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
224 | CORRIDOR_FLR_6_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
226 | CORRIDOR_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
227 | CORRIDOR_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
228 | CORRIDOR_FLR_6_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
229 | CORRIDOR_FLR_6_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
230 | CORRIDOR_FLR_6_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
231 | CORRIDOR_FLR_6_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
232 | CORRIDOR_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
233 | CORRIDOR_FLR_6_CEILING_1 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
234 | CORRIDOR_FLR_6_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | RETAIL_1_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 3.921E-002 | 5.846E-004 | 2.885E-004 | 0.531 | 1.000 | 0.000 | 0.000 | 0.000 |
2 | RETAIL_2_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 1.513E-002 | 1.949E-004 | 5.306E-004 | 0.177 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | MECH_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | MECH_FLR_1 | 164.24 | 2.7 | 3.577E-002 | 2.178E-004 | 5.696E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
4 | STORAGE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 2.064E-002 | 2.178E-004 | 4.726E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | LAUNDRY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 4.884E-002 | 6.258E-004 | 5.569E-004 | 0.569 | 1.000 | 0.000 | 0.000 | 0.000 |
6 | CAFE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 8.667E-002 | 4.589E-004 | 2.527E-004 | 0.417 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | LOBBY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 0.248 | 1.893E-004 | 3.620E-004 | 0.172 | 1.000 | 0.000 | 0.000 | 0.000 |
8 | ROOM_1_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | ROOM_2_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
10 | ROOM_3_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 6.349E-003 | 2.589E-004 | 5.696E-004 | 0.306 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | ROOM_4_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 6.350E-003 | 2.589E-004 | 5.696E-004 | 0.306 | 1.000 | 0.000 | 0.000 | 0.000 |
12 | ROOM_5_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | ROOM_6_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
14 | CORRIDOR_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_3 | 389.40 | 21.0 | 2.751E-002 | 7.066E-005 | 5.696E-004 | 8.345E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | ROOM_1_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 2.881E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
16 | ROOM_2_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 2.881E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | ROOM_3_MULT9_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 1.164E-002 | 4.746E-004 | 2.589E-004 | 0.561 | 1.000 | 0.000 | 0.000 | 0.000 |
18 | BANQUET_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 5.556E-002 | 1.675E-004 | 1.295E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | DINING_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | DINING_FLR_6 | 331.66 | 249.9 | 5.556E-002 | 1.675E-004 | 1.295E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
20 | KITCHEN_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 4.974E-002 | 4.815E-004 | 2.609E-004 | 0.569 | 1.000 | 0.000 | 0.000 | 0.000 |
21 | CORRIDOR_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_6 | 412.12 | 22.2 | 4.868E-002 | 1.181E-004 | 9.784E-005 | 0.140 | 1.000 | 0.000 | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | ROOM_1_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
2 | ROOM_2_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
3 | ROOM_3_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
4 | ROOM_4_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
5 | ROOM_5_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_5_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
6 | ROOM_6_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_6_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
7 | ROOM_1_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
8 | ROOM_2_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
9 | ROOM_3_MULT9_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | RETAIL_1_FLR_1 | Mixing/Well-Stirred |
3 | RETAIL_2_FLR_1 | Mixing/Well-Stirred |
4 | MECH_FLR_1 | Mixing/Well-Stirred |
5 | STORAGE_FLR_1 | Mixing/Well-Stirred |
6 | LAUNDRY_FLR_1 | Mixing/Well-Stirred |
7 | CAFE_FLR_1 | Mixing/Well-Stirred |
8 | LOBBY_FLR_1 | Mixing/Well-Stirred |
9 | ROOM_1_FLR_3 | Mixing/Well-Stirred |
10 | ROOM_2_FLR_3 | Mixing/Well-Stirred |
11 | ROOM_3_MULT19_FLR_3 | Mixing/Well-Stirred |
12 | ROOM_4_MULT19_FLR_3 | Mixing/Well-Stirred |
13 | ROOM_5_FLR_3 | Mixing/Well-Stirred |
14 | ROOM_6_FLR_3 | Mixing/Well-Stirred |
15 | CORRIDOR_FLR_3 | Mixing/Well-Stirred |
16 | ROOM_1_FLR_6 | Mixing/Well-Stirred |
17 | ROOM_2_FLR_6 | Mixing/Well-Stirred |
18 | ROOM_3_MULT9_FLR_6 | Mixing/Well-Stirred |
19 | BANQUET_FLR_6 | Mixing/Well-Stirred |
20 | DINING_FLR_6 | Mixing/Well-Stirred |
21 | KITCHEN_FLR_6 | Mixing/Well-Stirred |
22 | CORRIDOR_FLR_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 34392.64964 | 34392.64964 | 2.53504 | 2.53504 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:30:00 | 26.12400 | 8.81626E-003 | 1978.83018 | 106.49900 | 0.85446 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 0.85446 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -4.20000 | 2.69032E-003 | 1978.83018 | 106.49900 | 0.85446 | 0.00000 |
3 | RETAIL_1_FLR_1 | Cooling | 6546.64668 | 6546.64668 | 0.48258 | 0.48258 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 29.05333 | 8.82094E-003 | 67.07136 | 10.82900 | 7.92179E-002 | 0.00000 |
4 | RETAIL_1_FLR_1 | Heating | 2317.04263 | 2317.04263 | 0.10075 | 0.10075 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -4.20000 | 2.69032E-003 | 67.07136 | 10.82900 | 7.92179E-002 | 0.00000 |
5 | RETAIL_2_FLR_1 | Cooling | 3272.25618 | 3272.25618 | 0.24122 | 0.24122 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 29.29600 | 8.82133E-003 | 77.66889 | 12.54000 | 9.17347E-002 | 0.00000 |
6 | RETAIL_2_FLR_1 | Heating | 736.05668 | 736.05668 | 3.20056E-002 | 9.17347E-002 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -4.20000 | 2.69032E-003 | 77.66889 | 12.54000 | 9.17347E-002 | 0.00000 |
7 | MECH_FLR_1 | Cooling | 3133.38825 | 3133.38825 | 0.23093 | 0.23093 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 | 29.19200 | 8.82116E-003 | 164.24319 | 2.65200 | 0.00000 | 0.00000 |
8 | MECH_FLR_1 | Heating | 1341.10952 | 1341.10952 | 5.83146E-002 | 5.83146E-002 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -4.20000 | 2.69032E-003 | 164.24319 | 2.65200 | 0.00000 | 0.00000 |
9 | STORAGE_FLR_1 | Cooling | 1550.63458 | 1550.63458 | 0.11428 | 0.11428 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 29.40000 | 8.82150E-003 | 94.75927 | 2.04000 | 5.77652E-002 | 0.00000 |
10 | STORAGE_FLR_1 | Heating | 836.30520 | 836.30520 | 3.63645E-002 | 5.77652E-002 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -4.20000 | 2.69032E-003 | 94.75927 | 2.04000 | 5.77652E-002 | 0.00000 |
11 | LAUNDRY_FLR_1 | Cooling | 44771.60735 | 44771.60735 | 3.30003 | 3.30003 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 29.40000 | 8.82150E-003 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
12 | LAUNDRY_FLR_1 | Heating | 1776.54046 | 1776.54046 | 7.72458E-002 | 7.72458E-002 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -4.20000 | 2.69032E-003 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
13 | CAFE_FLR_1 | Cooling | 25635.90789 | 25635.90789 | 1.89124 | 1.89124 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 29.05333 | 8.82094E-003 | 188.86188 | 142.30000 | 0.67639 | 0.00000 |
14 | CAFE_FLR_1 | Heating | 5882.08171 | 5882.08171 | 0.25576 | 0.67639 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -4.20000 | 2.69032E-003 | 188.86188 | 142.30000 | 0.67639 | 0.00000 |
15 | LOBBY_FLR_1 | Cooling | 70940.36856 | 70940.36856 | 5.23090 | 5.23090 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 29.14000 | 8.82108E-003 | 1308.18612 | 422.43500 | 1.89399 | 0.00000 |
16 | LOBBY_FLR_1 | Heating | 13407.07203 | 13407.07203 | 0.58297 | 1.89399 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -4.20000 | 2.69032E-003 | 1308.18612 | 422.43500 | 1.89399 | 0.00000 |
17 | ROOM_1_FLR_3 | Cooling | 12966.22967 | 12966.22967 | 1.28784 | 1.28784 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 28.36000 | 8.81983E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
18 | ROOM_1_FLR_3 | Heating | 5261.41974 | 5261.41974 | 0.23011 | 0.23011 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -4.20000 | 2.69032E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
19 | ROOM_2_FLR_3 | Cooling | 11737.27203 | 11737.27203 | 1.16577 | 1.16577 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 16:50:00 | 28.08267 | 8.81938E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
20 | ROOM_2_FLR_3 | Heating | 5264.94097 | 5264.94097 | 0.23027 | 0.23027 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -4.20000 | 2.69032E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
21 | ROOM_3_MULT19_FLR_3 | Cooling | 92477.70323 | 92477.70323 | 9.18468 | 9.18468 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 29.14000 | 8.82108E-003 | 24.52384 | 1.50000 | 0.83707 | 0.00000 |
22 | ROOM_3_MULT19_FLR_3 | Heating | 30251.28166 | 30251.28166 | 1.32312 | 1.32312 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -4.20000 | 2.69032E-003 | 24.52384 | 1.50000 | 0.83707 | 0.00000 |
23 | ROOM_4_MULT19_FLR_3 | Cooling | 60920.91369 | 60920.91369 | 6.05100 | 6.05100 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 29.40000 | 8.82150E-003 | 24.53055 | 1.50000 | 0.83730 | 0.00000 |
24 | ROOM_4_MULT19_FLR_3 | Heating | 30332.30801 | 30332.30801 | 1.32666 | 1.32666 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -4.20000 | 2.69032E-003 | 24.53055 | 1.50000 | 0.83730 | 0.00000 |
25 | ROOM_5_FLR_3 | Cooling | 11665.92379 | 11665.92379 | 1.15869 | 1.15869 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 25.44800 | 8.81519E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
26 | ROOM_5_FLR_3 | Heating | 5269.11236 | 5269.11236 | 0.23045 | 0.23045 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -4.20000 | 2.69032E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
27 | ROOM_6_FLR_3 | Cooling | 10646.82385 | 10646.82385 | 1.05747 | 1.05747 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 23.68000 | 8.81240E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
28 | ROOM_6_FLR_3 | Heating | 5272.63243 | 5272.63243 | 0.23061 | 0.23061 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -4.20000 | 2.69032E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
29 | CORRIDOR_FLR_3 | Cooling | 17523.69073 | 17523.69073 | 1.29162 | 1.29162 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:10:00 | 29.40000 | 8.82150E-003 | 389.40468 | 20.95700 | 0.47476 | 0.00000 |
30 | CORRIDOR_FLR_3 | Heating | 8162.83732 | 8162.83732 | 0.35494 | 0.47476 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -4.20000 | 2.69032E-003 | 389.40468 | 20.95700 | 0.47476 | 0.00000 |
31 | ROOM_1_FLR_6 | Cooling | 3439.47740 | 3439.47740 | 0.34162 | 0.34162 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 28.36000 | 8.81983E-003 | 39.02202 | 1.50000 | 1.54338E-002 | 0.00000 |
32 | ROOM_1_FLR_6 | Heating | 1644.51611 | 1644.51611 | 7.19251E-002 | 7.19251E-002 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -4.20000 | 2.69032E-003 | 39.02202 | 1.50000 | 1.54338E-002 | 0.00000 |
33 | ROOM_2_FLR_6 | Cooling | 3093.05032 | 3093.05032 | 0.30721 | 0.30721 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 16:50:00 | 28.08267 | 8.81938E-003 | 39.01745 | 1.50000 | 1.54319E-002 | 0.00000 |
34 | ROOM_2_FLR_6 | Heating | 1646.32683 | 1646.32683 | 7.20043E-002 | 7.20043E-002 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -4.20000 | 2.69032E-003 | 39.01745 | 1.50000 | 1.54319E-002 | 0.00000 |
35 | ROOM_3_MULT9_FLR_6 | Cooling | 18726.82513 | 18726.82513 | 1.86003 | 1.86003 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 29.22667 | 8.82122E-003 | 24.53055 | 1.50000 | 9.91540E-002 | 0.00000 |
36 | ROOM_3_MULT9_FLR_6 | Heating | 7921.63737 | 7921.63737 | 0.34647 | 0.34647 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -4.20000 | 2.69032E-003 | 24.53055 | 1.50000 | 9.91540E-002 | 0.00000 |
37 | BANQUET_FLR_6 | Cooling | 29879.79409 | 29879.79409 | 2.20505 | 2.20505 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 29.40000 | 8.82150E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
38 | BANQUET_FLR_6 | Heating | 5466.94558 | 5466.94558 | 0.23772 | 1.18780 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -4.20000 | 2.69032E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
39 | DINING_FLR_6 | Cooling | 31343.45407 | 31343.45407 | 2.31303 | 2.31303 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 29.40000 | 8.82150E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
40 | DINING_FLR_6 | Heating | 5569.46240 | 5569.46240 | 0.24217 | 1.18780 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 19:20:00 | -4.20000 | 2.69032E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
41 | KITCHEN_FLR_6 | Cooling | 31486.71744 | 31486.71744 | 2.32682 | 2.32682 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 12:30:00 | 28.46400 | 8.82000E-003 | 103.30446 | 22.23800 | 0.36735 | 0.00000 |
42 | KITCHEN_FLR_6 | Heating | 903.02243 | 903.02243 | 3.92600E-002 | 0.36735 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | -4.20000 | 2.69032E-003 | 103.30446 | 22.23800 | 0.36735 | 0.00000 |
43 | CORRIDOR_FLR_6 | Cooling | 10407.45678 | 10407.45678 | 0.76710 | 0.76710 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 29.40000 | 8.82150E-003 | 412.12471 | 22.18000 | 0.12562 | 0.00000 |
44 | CORRIDOR_FLR_6 | Heating | 5785.46825 | 5785.46825 | 0.25157 | 0.25157 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 19:20:00 | -4.20000 | 2.69032E-003 | 412.12471 | 22.18000 | 0.12562 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV WITH REHEAT | Cooling | Sensible | 451424.00 | 22.81089 | 22.81089 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
2 | VAV WITH REHEAT | Heating | Sensible | 181475.09 | 7.27978 | 7.27978 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 19:20:00 |
3 | FLR_3_DOAS | Cooling | Sensible | 40614.20 | 21.03457 | 2.05125 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
4 | FLR_3_DOAS | Heating | Sensible | 51134.75 | 4.06162 | 2.05125 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.53504 |
2 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.59481 |
3 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.99500 |
4 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.52236 |
5 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
6 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 6.40540E-004 |
8 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.14850E-004 |
9 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.52236 |
10 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
11 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
12 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 13128.06604 |
13 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.14850E-004 |
14 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 273.76319 |
15 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.48258 |
16 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10591 |
17 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.99500 |
18 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.48017 |
19 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.99500 |
20 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
21 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.59755E-003 |
22 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.21113E-005 |
23 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.48017 |
24 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
25 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
26 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 4813.57751 |
27 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.21113E-005 |
28 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 105.47011 |
29 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.24122 |
30 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.24535 |
31 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.99500 |
32 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.24001 |
33 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.99500 |
34 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
35 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.55288E-003 |
36 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.73554E-005 |
37 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.24001 |
38 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
40 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1983.82502 |
41 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.73554E-005 |
42 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 42.67435 |
43 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.23093 |
44 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.54194 |
45 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.99500 |
46 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.22978 |
47 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
48 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
49 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 7.03024E-004 |
50 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.21802E-005 |
51 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.22978 |
52 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
53 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
54 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 2535.32930 |
55 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.21802E-005 |
56 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 56.14594 |
57 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.11428 |
58 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.63182 |
59 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.99500 |
60 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.11371 |
61 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
62 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 6.03024E-004 |
64 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.24871E-005 |
65 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.11371 |
66 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
67 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
68 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1427.35228 |
69 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.24871E-005 |
70 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 32.13344 |
71 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 3.30003 |
72 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 7.15066E-002 |
73 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.99500 |
74 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 3.28352 |
75 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.99500 |
76 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
77 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.11433E-002 |
78 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.64820E-004 |
79 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 3.28352 |
80 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
81 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
82 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 18839.93614 |
83 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.64820E-004 |
84 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 394.97136 |
85 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.89124 |
86 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 7.60945E-002 |
87 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.99500 |
88 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.88178 |
89 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.99500 |
90 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
91 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 5.00694E-003 |
92 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.37064E-004 |
93 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.88178 |
94 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
96 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 15667.23481 |
97 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.37064E-004 |
98 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 337.23059 |
99 | Fan:ZoneExhaust | LOBBY_FLR_1 EXHAUST FAN | User-Specified Maximum Flow Rate [m3/s] | 0.00000 |
100 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.23090 |
101 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.19057 |
102 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.99500 |
103 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 5.20475 |
104 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.99500 |
105 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
106 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.99930E-003 |
107 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.54031E-004 |
108 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 5.20475 |
109 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
110 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
111 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 40467.87151 |
112 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.54031E-004 |
113 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 866.11921 |
114 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_1_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17350E-002 |
115 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.28784 |
116 | Fan:OnOff | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.28784 |
117 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 4.60281E-005 |
118 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 5.49663E-004 |
119 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 22.50801 |
120 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
121 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.56250E-003 |
122 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
123 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
124 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 5.49663E-004 |
125 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.28784 |
126 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 5261.29487 |
127 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.60281E-005 |
128 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 150.35431 |
129 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_2_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17278E-002 |
130 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.16577 |
131 | Fan:OnOff | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.16577 |
132 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 4.60589E-005 |
133 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 4.98351E-004 |
134 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 22.50799 |
135 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
136 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.56876E-003 |
137 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
138 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
139 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.98351E-004 |
140 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.16577 |
141 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 5264.81602 |
142 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.60589E-005 |
143 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 150.45491 |
144 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_3_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.83707 |
145 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 9.18468 |
146 | Fan:OnOff | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 9.18468 |
147 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 2.64648E-004 |
148 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.86239E-003 |
149 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 22.50853 |
150 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
151 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50398E-003 |
152 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
153 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
154 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.86239E-003 |
155 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 9.18468 |
156 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 30250.93170 |
157 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.64648E-004 |
158 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 864.47862 |
159 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_4_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.83730 |
160 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 6.05100 |
161 | Fan:OnOff | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 6.05100 |
162 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 2.65357E-004 |
163 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.69675E-003 |
164 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 22.50730 |
165 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
166 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.73772E-003 |
167 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
168 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
169 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.69675E-003 |
170 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 6.05100 |
171 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 30331.95716 |
172 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.65357E-004 |
173 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 866.79355 |
174 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_5_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17350E-002 |
175 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.15869 |
176 | Fan:OnOff | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.15869 |
177 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 4.60954E-005 |
178 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 4.95413E-004 |
179 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 22.50799 |
180 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
181 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.56949E-003 |
182 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
183 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
184 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.95413E-004 |
185 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.15869 |
186 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 5268.98732 |
187 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.60954E-005 |
188 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 150.57408 |
189 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_6_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17278E-002 |
190 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.05747 |
191 | Fan:OnOff | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.05747 |
192 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 4.61262E-005 |
193 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 4.52875E-004 |
194 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 22.50796 |
195 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
196 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.57598E-003 |
197 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
198 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
199 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.52875E-004 |
200 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.05747 |
201 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 5272.50731 |
202 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.61262E-005 |
203 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 150.67465 |
204 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.29162 |
205 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.91893 |
206 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.99500 |
207 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.28516 |
208 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
209 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
210 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.14614E-004 |
211 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.29884E-004 |
212 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.28516 |
213 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
214 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
215 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 14846.52659 |
216 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.29884E-004 |
217 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 330.62142 |
218 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_1_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.54338E-002 |
219 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.34162 |
220 | Fan:OnOff | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.34162 |
221 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.43866E-005 |
222 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 1.45677E-004 |
223 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 22.50802 |
224 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
225 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.55899E-003 |
226 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
227 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
228 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.45677E-004 |
229 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.34162 |
230 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 1644.47844 |
231 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.43866E-005 |
232 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 46.99235 |
233 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_2_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.54319E-002 |
234 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.30721 |
235 | Fan:OnOff | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.30721 |
236 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.44025E-005 |
237 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 1.31215E-004 |
238 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 22.50800 |
239 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
240 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.56535E-003 |
241 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
242 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
243 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.31215E-004 |
244 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.30721 |
245 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 1646.28912 |
246 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.44025E-005 |
247 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 47.04408 |
248 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_3_MULT9_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 9.91540E-002 |
249 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.86003 |
250 | Fan:OnOff | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.86003 |
251 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 6.93007E-005 |
252 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 8.00170E-004 |
253 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 22.50774 |
254 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
255 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.59396E-003 |
256 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
257 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
258 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 8.00170E-004 |
259 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.86003 |
260 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 7921.49156 |
261 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.93007E-005 |
262 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 226.36127 |
263 | Fan:ZoneExhaust | BANQUET_FLR_6 EXHAUST FAN | User-Specified Maximum Flow Rate [m3/s] | 0.00000 |
264 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.20505 |
265 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11461 |
266 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.99500 |
267 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.19403 |
268 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.99500 |
269 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
270 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.32430E-003 |
271 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.47665E-004 |
272 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.19403 |
273 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
274 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
275 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 16879.02719 |
276 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.47665E-004 |
277 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 360.95133 |
278 | Fan:ZoneExhaust | DINING_FLR_6 EXHAUST FAN | User-Specified Maximum Flow Rate [m3/s] | 0.00000 |
279 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.31303 |
280 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10926 |
281 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.99500 |
282 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.30147 |
283 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.99500 |
284 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
285 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.48708E-003 |
286 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.53449E-004 |
287 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.30147 |
288 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
289 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
290 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 17540.14822 |
291 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.53449E-004 |
292 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 374.81245 |
293 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.32682 |
294 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.81132 |
295 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.99500 |
296 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.31518 |
297 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.99500 |
298 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
299 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.12619E-002 |
300 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.12561E-004 |
301 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.31518 |
302 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
303 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
304 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 12866.46079 |
305 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.12561E-004 |
306 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 269.25366 |
307 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.76710 |
308 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.40939 |
309 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.99500 |
310 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.76326 |
311 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
312 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
313 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 9.30660E-004 |
314 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 8.53485E-005 |
315 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.76326 |
316 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
317 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
318 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 9755.85656 |
319 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.53485E-005 |
320 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 220.18316 |
321 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 22.81520 |
322 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 22.81520 |
323 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 22.92985 |
324 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 22.81520 |
325 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 22.81520 |
326 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 22.81520 |
327 | AirLoopHVAC | VAV WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
328 | AirLoopHVAC | VAV WITH REHEAT | Calculated Heating Air Flow Ratio [] | 1.00000 |
329 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.05132 |
330 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.05132 |
331 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.05132 |
332 | AirLoopHVAC | FLR_3_DOAS | Adjusted Heating Design Air Flow Rate [m3/s] | 2.05132 |
333 | AirLoopHVAC | FLR_3_DOAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.05132 |
334 | AirLoopHVAC | FLR_3_DOAS | Adjusted Main Design Air Flow Rate [m3/s] | 2.05132 |
335 | AirLoopHVAC | FLR_3_DOAS | User Heating Air Flow Ratio [] | 0.30000 |
336 | AirLoopHVAC | FLR_3_DOAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
337 | AirLoopHVAC | VAV WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 22.81520 |
338 | AirLoopHVAC | FLR_3_DOAS | Design Supply Air Flow Rate [m3/s] | 2.05132 |
339 | Controller:OutdoorAir | VAV WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 22.81520 |
340 | Controller:OutdoorAir | VAV WITH REHEAT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 22.81089 |
341 | HeatExchanger:AirToAir:SensibleAndLatent | VAV WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 22.81089 |
342 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 29.40000 |
343 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
344 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.95159 |
345 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.82150E-003 |
346 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
347 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 532172.51099 |
348 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.90080E-002 |
349 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 22.81520 |
350 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 170625.58918 |
351 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.49271E-003 |
352 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 2912.95866 |
353 | Fan:VariableVolume | VAV WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 22.81520 |
354 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.90080E-002 |
355 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 2.50521E-005 |
356 | Controller:WaterCoil | VAV WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.49271E-003 |
357 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.05132 |
358 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.05125 |
359 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 29.40000 |
360 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
361 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.91727 |
362 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.82150E-003 |
363 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
364 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Coil Load [W] | 45447.83718 |
365 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.62329E-003 |
366 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 2.05132 |
367 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size Rated Capacity [W] | 15340.96456 |
368 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.34209E-004 |
369 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 261.90442 |
370 | Fan:ConstantVolume | FLR_3_DOAS FAN | User-Specified Maximum Flow Rate [m3/s] | 2.05125 |
371 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.62329E-003 |
372 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 2.93349E-004 |
373 | Controller:WaterCoil | FLR_3_DOAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.34209E-004 |
374 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 3.02638E-002 |
375 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 6236.23989 |
376 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 3.93313E-003 |
377 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 0.47198 |
378 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 3.93313E-003 |
379 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 1184.48498 |
380 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
381 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 449580.51920 |
382 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 449580.52000 |
383 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 3.93313E-003 |
384 | PlantLoop | COOLSYS1 | Maximum Loop Flow Rate [m3/s] | 3.02638E-002 |
385 | PlantLoop | COOLSYS1 | Plant Loop Volume [m3] | 3.63165 |
386 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Flow Rate [m3/s] | 3.02638E-002 |
387 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Power Consumption [W] | 4317.55921 |
388 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 3.02638E-002 |
389 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 847304.76643 |
390 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 847934.14000 |
391 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 96.66449 |
392 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 3.75036E-004 |
393 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 4.50044E-002 |
394 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 3.75036E-004 |
395 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 47.90688 |
396 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 3.75036E-004 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | 13195.94 |
2 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 4837.38 |
3 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 1993.79 |
4 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | 2547.55 |
5 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | 1434.12 |
6 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 18936.86 |
7 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | 15745.92 |
8 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | 40672.15 |
9 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | 5667.04 |
10 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | 5670.83 |
11 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | 32583.60 |
12 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | 32670.86 |
13 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | 5675.32 |
14 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | 5679.11 |
15 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 14917.71 |
16 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | 1771.24 |
17 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | 1773.19 |
18 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | 8532.07 |
19 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | 16964.30 |
20 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | 17628.82 |
21 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | 12932.77 |
22 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 9802.00 |
23 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | 129964.28 |
24 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | 11685.10 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | 22361.69 | 17662.04 | 4699.65 | 0.79 | 2516.91 | 25.53 |
2 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | 20262.56 | 15997.96 | 4264.60 | 0.79 | 2280.41 | 23.13 |
3 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | 157977.04 | 125227.36 | 32749.68 | 0.79 | 17799.05 | 180.53 |
4 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | 107973.60 | 84404.15 | 23569.45 | 0.78 | 12121.62 | 122.94 |
5 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | 20141.74 | 15901.85 | 4239.88 | 0.79 | 2266.78 | 22.99 |
6 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | 18401.34 | 14522.07 | 3879.27 | 0.79 | 2070.69 | 21.00 |
7 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | 5928.41 | 4683.47 | 1244.94 | 0.79 | 667.31 | 6.77 |
8 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | 5336.75 | 4214.42 | 1122.33 | 0.79 | 600.65 | 6.09 |
9 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | 32459.50 | 25588.79 | 6870.71 | 0.79 | 3651.60 | 37.04 |
10 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | 582088.24 | 401259.64 | 180828.60 | 0.69 | 67759.23 | 687.25 |
11 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | 49660.04 | 34741.99 | 14918.05 | 0.70 | 5487.20 | 55.65 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | 3.72 | 12.68 |
Zone Name | # Surfaces | |
1 | BASEMENT | 14 |
2 | RETAIL_1_FLR_1 | 8 |
3 | RETAIL_2_FLR_1 | 8 |
4 | MECH_FLR_1 | 7 |
5 | STORAGE_FLR_1 | 8 |
6 | LAUNDRY_FLR_1 | 8 |
7 | CAFE_FLR_1 | 10 |
8 | LOBBY_FLR_1 | 22 |
9 | ROOM_1_FLR_3 | 9 |
10 | ROOM_2_FLR_3 | 9 |
11 | ROOM_3_MULT19_FLR_3 | 8 |
12 | ROOM_4_MULT19_FLR_3 | 8 |
13 | ROOM_5_FLR_3 | 9 |
14 | ROOM_6_FLR_3 | 9 |
15 | CORRIDOR_FLR_3 | 25 |
16 | ROOM_1_FLR_6 | 9 |
17 | ROOM_2_FLR_6 | 9 |
18 | ROOM_3_MULT9_FLR_6 | 8 |
19 | BANQUET_FLR_6 | 8 |
20 | DINING_FLR_6 | 8 |
21 | KITCHEN_FLR_6 | 12 |
22 | CORRIDOR_FLR_6 | 19 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.419 | 0.394 | 211.13 | 211.13 | 211.13 | 0.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.419 | 0.394 | 55.76 | 55.76 | 55.76 | 90.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.419 | 0.394 | 211.13 | 211.13 | 211.13 | 180.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_WEST_CFACTOR | 0.419 | 0.394 | 55.76 | 55.76 | 55.76 | 270.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | BASEMENT_FLOOR | 2.705 | 1.632 | 1978.83 | 1978.83 | 1978.83 | 0.00 | 180.00 | 86.56 | 22.86 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | BASEMENT_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | RETAIL_1_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | BASEMENT_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | BASEMENT_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | BASEMENT_CEILING_4 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_CEILING_5 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
11 | BASEMENT_CEILING_6 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | CAFE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
12 | BASEMENT_CEILING_7 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 0.00 | 32.99 | 32.99 | 0.00 | LOBBY_FLR_1_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
13 | BASEMENT_CEILING_8 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 219.63 | 219.63 | 219.63 | 90.00 | 0.00 | 14.82 | 14.82 | 0.00 | LOBBY_FLR_1_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
14 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 3957.66 | 3957.66 | 3957.66 | 0.00 | 90.00 | 3957.66 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
15 | RETAIL_1_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.738 | 0.664 | 22.63 | 45.89 | 22.63 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | Window | RETAIL_1_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 23.26 | 23.26 | 23.26 | 180.00 | 90.00 | 10.92 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
17 | RETAIL_1_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.738 | 0.664 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
18 | RETAIL_1_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | RETAIL_1_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | RETAIL_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 67.07 | 67.07 | 67.07 | 0.00 | 180.00 | 11.58 | 5.79 | 0.00 | BASEMENT_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | RETAIL_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 7.62E-002 | 0.92 | 4 | ||
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 134.14 | 134.14 | 134.14 | 0.00 | 90.00 | 134.14 | 1.00 | 0.00 | RETAIL_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
23 | RETAIL_2_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.738 | 0.664 | 24.62 | 26.57 | 24.62 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | Door | RETAIL_2_FLR_1_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
25 | RETAIL_2_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
26 | RETAIL_2_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | RETAIL_2_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 90.00 | 90.00 | 6.71 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | RETAIL_2_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 77.67 | 77.67 | 77.67 | 0.00 | 180.00 | 11.58 | 6.71 | 0.00 | BASEMENT_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
29 | RETAIL_2_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 155.34 | 155.34 | 155.34 | 0.00 | 90.00 | 155.34 | 1.00 | 0.00 | RETAIL_2_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
31 | MECH_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.738 | 0.664 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | MECH_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | MECH_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 180.00 | 90.00 | 15.85 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | MECH_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | MECH_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 164.24 | 164.24 | 164.24 | 0.00 | 180.00 | 15.85 | 10.36 | 0.00 | BASEMENT_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | MECH_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | MECH_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 328.49 | 328.49 | 328.49 | 0.00 | 90.00 | 328.49 | 1.00 | 0.00 | MECH_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | STORAGE_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.738 | 0.664 | 28.80 | 36.23 | 28.80 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | Door | STORAGE_FLR_1_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.198 | 1.198 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | STORAGE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
41 | STORAGE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 180.00 | 90.00 | 9.14 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
42 | STORAGE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | STORAGE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 94.76 | 94.76 | 94.76 | 0.00 | 180.00 | 9.14 | 10.36 | 0.00 | BASEMENT_CEILING_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
44 | STORAGE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | STORAGE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 189.52 | 189.52 | 189.52 | 0.00 | 90.00 | 189.52 | 1.00 | 0.00 | STORAGE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
46 | LAUNDRY_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.738 | 0.664 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | LAUNDRY_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.738 | 0.664 | 65.68 | 67.63 | 65.68 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | Door | LAUNDRY_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
49 | LAUNDRY_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 180.00 | 90.00 | 4.57 | 3.96 | 0.00 | CAFE_FLR_1_WALL_2_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | LAUNDRY_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 270.00 | 90.00 | 17.07 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
51 | LAUNDRY_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 78.04 | 78.04 | 78.04 | 0.00 | 180.00 | 4.57 | 17.07 | 0.00 | BASEMENT_CEILING_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
52 | LAUNDRY_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 156.08 | 156.08 | 156.08 | 0.00 | 90.00 | 156.08 | 1.00 | 0.00 | LAUNDRY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
54 | CAFE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.738 | 0.664 | 21.00 | 22.95 | 21.00 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CAFE_FLR_1_WALL_EAST_DOOR | Door | CAFE_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | CAFE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.738 | 0.664 | 63.73 | 129.23 | 63.73 | 180.00 | 90.00 | 32.61 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | Window | CAFE_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 65.50 | 65.50 | 65.50 | 180.00 | 90.00 | 30.75 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
58 | CAFE_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 0.00 | 90.00 | 28.04 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | CAFE_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | CAFE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | CAFE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 188.86 | 188.86 | 188.86 | 0.00 | 180.00 | 32.61 | 5.79 | 0.00 | BASEMENT_CEILING_6 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
62 | CAFE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 3.86E-002 | 0.96 | 4 | ||
63 | CAFE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 377.72 | 377.72 | 377.72 | 0.00 | 90.00 | 377.72 | 1.00 | 0.00 | CAFE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
64 | LOBBY_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.738 | 0.664 | 209.87 | 213.77 | 209.87 | 0.00 | 90.00 | 53.95 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
67 | LOBBY_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.738 | 0.664 | 12.08 | 12.08 | 12.08 | 0.00 | 90.00 | 3.05 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
68 | LOBBY_FLR_1_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.738 | 0.664 | 82.79 | 167.88 | 82.79 | 180.00 | 90.00 | 42.37 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | Window | LOBBY_FLR_1_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 85.08 | 85.08 | 85.08 | 180.00 | 90.00 | 39.95 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LOBBY_FLR_1_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.738 | 0.664 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | LOBBY_FLR_1_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | LOBBY_FLR_1_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 180.00 | 90.00 | 28.04 | 3.96 | 0.00 | CAFE_FLR_1_WALL_1_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | LOBBY_FLR_1_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | LOBBY_FLR_1_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | LOBBY_FLR_1_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | LOBBY_FLR_1_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | MECH_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | LOBBY_FLR_1_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
78 | LOBBY_FLR_1_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | LOBBY_FLR_1_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | CAFE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | LOBBY_FLR_1_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | LOBBY_FLR_1_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 180.00 | 32.99 | 32.99 | 0.00 | BASEMENT_CEILING_7 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
82 | LOBBY_FLR_1_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 219.63 | 219.63 | 219.63 | 90.00 | 180.00 | 14.82 | 14.82 | 0.00 | BASEMENT_CEILING_8 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
83 | LOBBY_FLR_1_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 1062.83 | 1062.83 | 1062.83 | 270.00 | 0.00 | 32.60 | 32.60 | 0.00 | LOBBY_FLR_1_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 10 | ||
84 | LOBBY_FLR_1_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 245.35 | 245.35 | 245.35 | 180.00 | 0.00 | 42.37 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.22E-003 | 1.00 | 4 | ||
85 | LOBBY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 2616.37 | 2616.37 | 2616.37 | 0.00 | 90.00 | 2616.37 | 1.00 | 0.00 | LOBBY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | ROOM_1_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.016 | 0.882 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | ROOM_1_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.016 | 0.882 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | Window | ROOM_1_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | ROOM_1_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | ROOM_1_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | ROOM_1_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
93 | ROOM_1_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
94 | ROOM_1_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
95 | ROOM_2_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.016 | 0.882 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
97 | ROOM_2_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.016 | 0.882 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | Window | ROOM_2_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | ROOM_2_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | ROOM_2_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | ROOM_2_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | ROOM_2_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | ROOM_2_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.016 | 0.882 | 7.47 | 11.15 | 7.47 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 3.68 | 3.68 | 3.68 | 180.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | ROOM_3_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 24.52 | 24.52 | 24.52 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
110 | ROOM_3_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 24.52 | 24.52 | 24.52 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.05 | 49.05 | 49.05 | 0.00 | 90.00 | 49.05 | 1.00 | 0.00 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.016 | 0.882 | 7.47 | 11.15 | 7.47 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_4_MULT19_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 3.68 | 3.68 | 3.68 | 0.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
117 | ROOM_4_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
118 | ROOM_4_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
120 | ROOM_5_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.016 | 0.882 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | Window | ROOM_5_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
122 | ROOM_5_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.016 | 0.882 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_5_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
124 | ROOM_5_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
125 | ROOM_5_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
126 | ROOM_5_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
127 | ROOM_5_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
128 | ROOM_5_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_5_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
129 | ROOM_6_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.016 | 0.882 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_6_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
131 | ROOM_6_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.016 | 0.882 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | Window | ROOM_6_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
133 | ROOM_6_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
134 | ROOM_6_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
135 | ROOM_6_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
136 | ROOM_6_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
137 | ROOM_6_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_6_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
138 | CORRIDOR_FLR_3_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.016 | 0.882 | 11.83 | 17.65 | 11.83 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 5.82 | 5.82 | 5.82 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.016 | 0.882 | 4.35 | 6.50 | 4.35 | 0.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 2.15 | 2.15 | 2.15 | 0.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.016 | 0.882 | 4.36 | 6.50 | 4.36 | 180.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 2.15 | 2.15 | 2.15 | 180.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.016 | 0.882 | 11.83 | 17.65 | 11.83 | 180.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 5.82 | 5.82 | 5.82 | 180.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 0.00 | 90.00 | 69.50 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | CORRIDOR_FLR_3_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | CORRIDOR_FLR_3_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORRIDOR_FLR_3_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | CORRIDOR_FLR_3_WALL_4_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 180.00 | 90.00 | 69.49 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
152 | CORRIDOR_FLR_3_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | CORRIDOR_FLR_3_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | CORRIDOR_FLR_3_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | CORRIDOR_FLR_3_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | CORRIDOR_FLR_3_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 74.32 | 74.32 | 74.32 | 180.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
157 | CORRIDOR_FLR_3_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 240.77 | 240.77 | 240.77 | 270.00 | 180.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | CORRIDOR_FLR_3_FLOOR_3 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 74.32 | 74.32 | 74.32 | 90.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
159 | CORRIDOR_FLR_3_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
160 | CORRIDOR_FLR_3_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 240.77 | 240.77 | 240.77 | 90.00 | 0.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
161 | CORRIDOR_FLR_3_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 778.81 | 778.81 | 778.81 | 0.00 | 90.00 | 778.81 | 1.00 | 0.00 | CORRIDOR_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
163 | ROOM_1_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.081 | 0.931 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
165 | ROOM_1_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.081 | 0.931 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | Window | ROOM_1_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
167 | ROOM_1_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
168 | ROOM_1_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
169 | ROOM_1_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | ROOM_1_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.228 | 0.219 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
171 | ROOM_1_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
172 | ROOM_2_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.081 | 0.931 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
174 | ROOM_2_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.081 | 0.931 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | Window | ROOM_2_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
176 | ROOM_2_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
177 | ROOM_2_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
178 | ROOM_2_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | ROOM_2_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.228 | 0.219 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
180 | ROOM_2_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.081 | 0.931 | 13.70 | 20.44 | 13.70 | 180.00 | 90.00 | 6.71 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 6.74 | 6.74 | 6.74 | 180.00 | 90.00 | 5.53 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 0.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 90.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | ROOM_3_MULT9_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 6.71 | 3.66 | 0.00 | ROOM_3_MULT9_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
187 | ROOM_3_MULT9_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.228 | 0.219 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 6.71 | 3.66 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
189 | BANQUET_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.081 | 0.931 | 65.36 | 97.55 | 65.36 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | Window | BANQUET_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 32.19 | 32.19 | 32.19 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
191 | BANQUET_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
192 | BANQUET_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
193 | BANQUET_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
194 | BANQUET_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | BANQUET_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
195 | BANQUET_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
196 | BANQUET_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | BANQUET_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
197 | DINING_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.081 | 0.931 | 65.36 | 97.55 | 65.36 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DINING_FLR_6_WALL_NORTH_WINDOW | Window | DINING_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 32.19 | 32.19 | 32.19 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
199 | DINING_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
200 | DINING_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | DINING_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DINING_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DINING_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | DINING_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
203 | DINING_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
204 | DINING_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | DINING_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
205 | KITCHEN_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.081 | 0.931 | 16.77 | 21.37 | 16.77 | 0.00 | 90.00 | 7.01 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | Window | KITCHEN_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
207 | KITCHEN_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.081 | 0.931 | 34.86 | 52.03 | 34.86 | 90.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | Window | KITCHEN_FLR_6_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 17.17 | 17.17 | 17.17 | 90.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.081 | 0.931 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | Window | KITCHEN_FLR_6_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 7.43 | 7.43 | 7.43 | 180.00 | 90.00 | 2.44 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
212 | KITCHEN_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | KITCHEN_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | KITCHEN_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 103.30 | 103.30 | 103.30 | 180.00 | 180.00 | 10.16 | 10.16 | 0.00 | KITCHEN_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
215 | KITCHEN_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 103.30 | 103.30 | 103.30 | 270.00 | 0.00 | 10.16 | 10.16 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
216 | KITCHEN_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 206.61 | 206.61 | 206.61 | 0.00 | 90.00 | 206.61 | 1.00 | 0.00 | KITCHEN_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
217 | CORRIDOR_FLR_6_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.081 | 0.931 | 11.83 | 17.65 | 11.83 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 5.82 | 5.82 | 5.82 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.081 | 0.931 | 10.58 | 15.79 | 10.58 | 0.00 | 90.00 | 5.18 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 5.21 | 5.21 | 5.21 | 0.00 | 90.00 | 4.27 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.081 | 0.931 | 34.86 | 52.03 | 34.86 | 180.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 17.17 | 17.17 | 17.17 | 180.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
224 | CORRIDOR_FLR_6_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 104.98 | 104.98 | 104.98 | 0.00 | 90.00 | 34.44 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 183.95 | 183.95 | 183.95 | 180.00 | 90.00 | 60.35 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
226 | CORRIDOR_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
227 | CORRIDOR_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 40.88 | 40.88 | 40.88 | 270.00 | 90.00 | 13.41 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
228 | CORRIDOR_FLR_6_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
229 | CORRIDOR_FLR_6_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
230 | CORRIDOR_FLR_6_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
231 | CORRIDOR_FLR_6_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
232 | CORRIDOR_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 412.12 | 412.12 | 412.12 | 180.00 | 180.00 | 20.30 | 20.30 | 0.00 | CORRIDOR_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 12 | ||
233 | CORRIDOR_FLR_6_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 244.71 | 244.71 | 244.71 | 90.00 | 0.00 | 15.64 | 15.64 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 8 | ||
234 | CORRIDOR_FLR_6_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 167.42 | 167.42 | 167.42 | 270.00 | 0.00 | 12.94 | 12.94 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 824.25 | 824.25 | 824.25 | 0.00 | 90.00 | 824.25 | 1.00 | 0.00 | CORRIDOR_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 5.2374784118E-003 | 1.2504168169E-002 | Pass | Pass | 1.3256957935E-002 | 3.1829155319E-002 | Pass | Pass |
2 | RETAIL_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 1.4588147018E-002 | 2.3133940167E-002 | Pass | Pass | 0.1794355338 | 0.3781460679 | Pass | Pass |
3 | RETAIL_2_FLR_1 | RunPeriod: RUNPERIOD 1 | 1.4032999054E-003 | 1.1195873589E-003 | Pass | Pass | 2.3499541916E-002 | 5.2655551766E-002 | Pass | Pass |
4 | MECH_FLR_1 | RunPeriod: RUNPERIOD 1 | 8.7689808518E-004 | 6.9205323113E-004 | Pass | Pass | 4.6051302471E-002 | 8.0284709871E-002 | Pass | Pass |
5 | STORAGE_FLR_1 | RunPeriod: RUNPERIOD 1 | 8.3475834660E-004 | 6.2325964106E-004 | Pass | Pass | 4.2472889508 | 20.6381898206 | Pass | Pass |
6 | LAUNDRY_FLR_1 | RunPeriod: RUNPERIOD 1 | 4.4881588777E-002 | 0.1374422218 | Pass | Pass | 1.9310623875E-002 | 5.5668444484E-002 | Pass | Pass |
7 | CAFE_FLR_1 | RunPeriod: RUNPERIOD 1 | 7.0980602577E-003 | 1.3282741511E-002 | Pass | Pass | 3.0228994836E-002 | 8.1835504725E-002 | Pass | Pass |
8 | LOBBY_FLR_1 | RunPeriod: RUNPERIOD 1 | 1.6790566238E-003 | 1.3553680718E-003 | Pass | Pass | 2.1571728243E-002 | 5.7084073628E-002 | Pass | Pass |
9 | ROOM_1_FLR_3 | RunPeriod: RUNPERIOD 1 | 8.0332111678E-002 | 0.2660518024 | Pass | Pass | 1.0384825187 | 9.8515048152 | Pass | Pass |
10 | ROOM_2_FLR_3 | RunPeriod: RUNPERIOD 1 | 8.0604884157E-002 | 0.2658887598 | Pass | Pass | 0.3234747268 | 1.4325168083 | Pass | Pass |
11 | ROOM_3_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 1.9700596564E-002 | 3.5205395203E-002 | Pass | Pass | 0.1896184867 | 0.7916602486 | Pass | Pass |
12 | ROOM_4_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 2.0093351296E-002 | 7.1496317629E-002 | Pass | Pass | 0.1222336919 | 0.3572110806 | Pass | Pass |
13 | ROOM_5_FLR_3 | RunPeriod: RUNPERIOD 1 | 7.9926250821E-002 | 0.2634945574 | Pass | Pass | 4.0354299156 | 44.3406244225 | Pass | Pass |
14 | ROOM_6_FLR_3 | RunPeriod: RUNPERIOD 1 | 8.0228761264E-002 | 0.2636460893 | Pass | Pass | 0.4119711891 | 1.9889721088 | Pass | Pass |
15 | CORRIDOR_FLR_3 | RunPeriod: RUNPERIOD 1 | 6.9076456369E-004 | 5.6725346567E-004 | Pass | Pass | 0.2000209081 | 0.9750010688 | Pass | Pass |
16 | ROOM_1_FLR_6 | RunPeriod: RUNPERIOD 1 | 9.0312037711E-002 | 0.3098526203 | Pass | Pass | 0.2412880927 | 0.8112824563 | Pass | Pass |
17 | ROOM_2_FLR_6 | RunPeriod: RUNPERIOD 1 | 9.0392385036E-002 | 0.3092930121 | Pass | Pass | 0.2362384689 | 0.8064316898 | Pass | Pass |
18 | ROOM_3_MULT9_FLR_6 | RunPeriod: RUNPERIOD 1 | 6.9255016864E-002 | 0.2349232979 | Pass | Pass | 0.1525531619 | 0.4661422932 | Pass | Pass |
19 | BANQUET_FLR_6 | RunPeriod: RUNPERIOD 1 | 2.7056261683E-002 | 7.0720249768E-002 | Pass | Pass | 1.1537723985E-002 | 3.4604884584E-002 | Pass | Pass |
20 | DINING_FLR_6 | RunPeriod: RUNPERIOD 1 | 2.8778945644E-002 | 7.1493089362E-002 | Pass | Pass | 1.0458780801E-002 | 2.9052303266E-002 | Pass | Pass |
21 | KITCHEN_FLR_6 | RunPeriod: RUNPERIOD 1 | 7.4094216924E-002 | 0.1236272782 | Pass | Pass | 1.7424368730E-002 | 3.2420014657E-002 | Pass | Pass |
22 | CORRIDOR_FLR_6 | RunPeriod: RUNPERIOD 1 | 1.4735137177E-003 | 1.1250897545E-003 | Pass | Pass | 0.2247670326 | 0.3954108398 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:58:38
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 3506.60 | 106.41 | 901.89 | 10381.47 | 3794.44 | 18690.82 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:58:38
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | -4.20 | 0.00 | -4.20 | Wetbulb [C] | 4.30 | 20.00 |
SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 29.40 | 10.40 | 18.30 | Wetbulb [C] | 4.20 | 350.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 22.00 | 23 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 16.00 | 20 | |||
Jul | 0.00 | 0 | |||
Aug | 24.00 | 18 | |||
Sep | 12.00 | 15 | |||
Oct | 61.00 | 41 | |||
Nov | 0.00 | 0 | |||
Dec | 45.00 | 41 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:58:38
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.399 | 0.419 | 211.13 | 211.13 | 0.00 | 90.00 | N |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.399 | 0.419 | 55.76 | 55.76 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.399 | 0.419 | 211.13 | 211.13 | 180.00 | 90.00 | S |
BASEMENT_WALL_WEST | BASEMENT_WALL_WEST_CFACTOR | 1.00 | 0.399 | 0.419 | 55.76 | 55.76 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.664 | 0.738 | 45.89 | 22.63 | 180.00 | 90.00 | S |
RETAIL_1_FLR_1_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.664 | 0.738 | 22.95 | 22.95 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_CEILING | NONRES_ROOF | 0.23 | 0.221 | 0.228 | 67.07 | 67.07 | 180.00 | 0.00 | |
RETAIL_2_FLR_1_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.664 | 0.738 | 26.57 | 24.62 | 270.00 | 90.00 | W |
MECH_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.664 | 0.738 | 62.80 | 62.80 | 0.00 | 90.00 | N |
STORAGE_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.664 | 0.738 | 36.23 | 28.80 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.664 | 0.738 | 18.12 | 18.12 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.664 | 0.738 | 67.63 | 65.68 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.664 | 0.738 | 22.95 | 21.00 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.664 | 0.738 | 129.23 | 63.73 | 180.00 | 90.00 | S |
CAFE_FLR_1_CEILING | NONRES_ROOF | 0.23 | 0.221 | 0.228 | 188.86 | 188.86 | 180.00 | 0.00 | |
LOBBY_FLR_1_WALL_1_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.664 | 0.738 | 213.77 | 209.87 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_2_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.664 | 0.738 | 12.08 | 12.08 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.664 | 0.738 | 167.88 | 82.79 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_1_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.664 | 0.738 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_CEILING_2 | NONRES_ROOF | 0.23 | 0.221 | 0.228 | 245.35 | 245.35 | 180.00 | 0.00 | |
ROOM_1_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.882 | 1.016 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_1_FLR_3_WALL_WEST | RES_EXT_WALL_MID | 0.30 | 0.882 | 1.016 | 104.06 | 69.72 | 270.00 | 90.00 | W |
ROOM_2_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.882 | 1.016 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_2_FLR_3_WALL_WEST | RES_EXT_WALL_MID | 0.30 | 0.882 | 1.016 | 104.05 | 69.71 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.882 | 1.016 | 847.14 | 567.58 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.882 | 1.016 | 847.37 | 567.71 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_EAST | RES_EXT_WALL_MID | 0.30 | 0.882 | 1.016 | 104.06 | 69.72 | 90.00 | 90.00 | E |
ROOM_5_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.882 | 1.016 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.882 | 1.016 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_6_FLR_3_WALL_EAST | RES_EXT_WALL_MID | 0.30 | 0.882 | 1.016 | 104.05 | 69.71 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_1_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.882 | 1.016 | 70.60 | 47.31 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_2_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.882 | 1.016 | 26.01 | 17.42 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.882 | 1.016 | 26.02 | 17.43 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_2_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.882 | 1.016 | 70.60 | 47.31 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_SOUTH | RES_EXT_WALL_TOP | 0.30 | 0.931 | 1.081 | 13.94 | 9.34 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_WEST | RES_EXT_WALL_TOP | 0.30 | 0.931 | 1.081 | 26.01 | 17.43 | 270.00 | 90.00 | W |
ROOM_1_FLR_6_CEILING | RES_ROOF | 0.23 | 0.221 | 0.228 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_2_FLR_6_WALL_NORTH | RES_EXT_WALL_TOP | 0.30 | 0.931 | 1.081 | 13.94 | 9.34 | 0.00 | 90.00 | N |
ROOM_2_FLR_6_WALL_WEST | RES_EXT_WALL_TOP | 0.30 | 0.931 | 1.081 | 26.01 | 17.43 | 270.00 | 90.00 | W |
ROOM_2_FLR_6_CEILING | RES_ROOF | 0.23 | 0.221 | 0.228 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | RES_EXT_WALL_TOP | 0.30 | 0.931 | 1.081 | 183.96 | 123.26 | 180.00 | 90.00 | S |
ROOM_3_MULT9_FLR_6_CEILING | RES_ROOF | 0.23 | 0.221 | 0.228 | 220.77 | 220.77 | 180.00 | 0.00 | |
BANQUET_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.931 | 1.081 | 97.55 | 65.36 | 0.00 | 90.00 | N |
BANQUET_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.221 | 0.228 | 331.66 | 331.66 | 180.00 | 0.00 | |
DINING_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.931 | 1.081 | 97.55 | 65.36 | 0.00 | 90.00 | N |
DINING_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.221 | 0.228 | 331.66 | 331.66 | 180.00 | 0.00 | |
KITCHEN_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.931 | 1.081 | 21.37 | 16.77 | 0.00 | 90.00 | N |
KITCHEN_FLR_6_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.931 | 1.081 | 52.03 | 34.86 | 90.00 | 90.00 | E |
KITCHEN_FLR_6_WALL_1_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.931 | 1.081 | 13.94 | 9.34 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.221 | 0.228 | 103.30 | 103.30 | 270.00 | 0.00 | |
CORRIDOR_FLR_6_WALL_1_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.931 | 1.081 | 17.65 | 11.83 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.931 | 1.081 | 15.79 | 10.58 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.931 | 1.081 | 52.03 | 34.86 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_CEILING_1 | NONRES_ROOF | 0.23 | 0.221 | 0.228 | 244.71 | 244.71 | 90.00 | 0.00 | |
CORRIDOR_FLR_6_CEILING_2 | NONRES_ROOF | 0.23 | 0.221 | 0.228 | 167.42 | 167.42 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_FLOOR | BASEMENT_FLOOR | 0.30 | 1.441 | 2.705 | 1978.83 | 1978.83 | 0.00 | 180.00 | |
BASEMENT_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.186 | 0.196 | 67.07 | 67.07 | 180.00 | 0.00 | |
BASEMENT_CEILING_2 | NONRES_FLOOR_CEILING | 0.30 | 0.186 | 0.196 | 77.67 | 77.67 | 180.00 | 0.00 | |
BASEMENT_CEILING_3 | NONRES_FLOOR_CEILING | 0.30 | 0.186 | 0.196 | 164.24 | 164.24 | 180.00 | 0.00 | |
BASEMENT_CEILING_4 | NONRES_FLOOR_CEILING | 0.30 | 0.186 | 0.196 | 94.76 | 94.76 | 180.00 | 0.00 | |
BASEMENT_CEILING_5 | NONRES_FLOOR_CEILING | 0.30 | 0.186 | 0.196 | 78.04 | 78.04 | 180.00 | 0.00 | |
BASEMENT_CEILING_6 | NONRES_FLOOR_CEILING | 0.30 | 0.186 | 0.196 | 188.86 | 188.86 | 180.00 | 0.00 | |
BASEMENT_CEILING_7 | NONRES_FLOOR_CEILING | 0.30 | 0.186 | 0.196 | 1088.56 | 1088.56 | 180.00 | 0.00 | |
BASEMENT_CEILING_8 | NONRES_FLOOR_CEILING | 0.30 | 0.186 | 0.196 | 219.63 | 219.63 | 90.00 | 0.00 | |
RETAIL_1_FLR_1_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 0.00 | 90.00 | N |
RETAIL_1_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 90.00 | 90.00 | E |
RETAIL_1_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.186 | 0.196 | 67.07 | 67.07 | 0.00 | 180.00 | |
RETAIL_2_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 180.00 | 90.00 | S |
RETAIL_2_FLR_1_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 0.00 | 90.00 | N |
RETAIL_2_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.57 | 26.57 | 90.00 | 90.00 | E |
RETAIL_2_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.186 | 0.196 | 77.67 | 77.67 | 0.00 | 180.00 | |
RETAIL_2_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 77.67 | 77.67 | 180.00 | 0.00 | |
MECH_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
MECH_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 62.80 | 62.80 | 180.00 | 90.00 | S |
MECH_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
MECH_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.186 | 0.196 | 164.24 | 164.24 | 0.00 | 180.00 | |
MECH_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 164.24 | 164.24 | 180.00 | 0.00 | |
STORAGE_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
STORAGE_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 36.23 | 36.23 | 180.00 | 90.00 | S |
STORAGE_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
STORAGE_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.186 | 0.196 | 94.76 | 94.76 | 0.00 | 180.00 | |
STORAGE_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 94.76 | 94.76 | 180.00 | 0.00 | |
LAUNDRY_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 18.12 | 18.12 | 180.00 | 90.00 | S |
LAUNDRY_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 67.63 | 67.63 | 270.00 | 90.00 | W |
LAUNDRY_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.186 | 0.196 | 78.04 | 78.04 | 0.00 | 180.00 | |
LAUNDRY_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 78.04 | 78.04 | 180.00 | 0.00 | |
CAFE_FLR_1_WALL_1_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.11 | 111.11 | 0.00 | 90.00 | N |
CAFE_FLR_1_WALL_2_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 18.12 | 18.12 | 0.00 | 90.00 | N |
CAFE_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 270.00 | 90.00 | W |
CAFE_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.186 | 0.196 | 188.86 | 188.86 | 0.00 | 180.00 | |
LOBBY_FLR_1_WALL_2_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_3_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.11 | 111.11 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.57 | 26.57 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_4_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 62.80 | 62.80 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_4_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 36.23 | 36.23 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
LOBBY_FLR_1_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 90.00 | 90.00 | E |
LOBBY_FLR_1_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 67.63 | 67.63 | 90.00 | 90.00 | E |
LOBBY_FLR_1_FLOOR_1 | NONRES_FLOOR | 0.30 | 0.186 | 0.196 | 1088.56 | 1088.56 | 180.00 | 180.00 | |
LOBBY_FLR_1_FLOOR_2 | NONRES_FLOOR | 0.30 | 0.186 | 0.196 | 219.63 | 219.63 | 90.00 | 180.00 | |
LOBBY_FLR_1_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 1062.83 | 1062.83 | 270.00 | 0.00 | |
ROOM_1_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 0.00 | 90.00 | N |
ROOM_1_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 90.00 | 90.00 | E |
ROOM_1_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 156.09 | 156.09 | 0.00 | 180.00 | |
ROOM_1_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 156.09 | 156.09 | 180.00 | 0.00 | |
ROOM_2_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 90.00 | 90.00 | E |
ROOM_2_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 180.00 | 90.00 | S |
ROOM_2_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 156.07 | 156.07 | 0.00 | 180.00 | |
ROOM_2_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 156.07 | 156.07 | 180.00 | 0.00 | |
ROOM_3_MULT19_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.14 | 847.14 | 0.00 | 90.00 | N |
ROOM_3_MULT19_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 90.00 | 90.00 | E |
ROOM_3_MULT19_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 1863.81 | 1863.81 | 0.00 | 180.00 | |
ROOM_3_MULT19_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 1863.81 | 1863.81 | 180.00 | 0.00 | |
ROOM_4_MULT19_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 90.00 | 90.00 | E |
ROOM_4_MULT19_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.37 | 847.37 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 270.00 | 90.00 | W |
ROOM_4_MULT19_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 1864.32 | 1864.32 | 0.00 | 180.00 | |
ROOM_4_MULT19_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 1864.32 | 1864.32 | 180.00 | 0.00 | |
ROOM_5_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 270.00 | 90.00 | W |
ROOM_5_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 156.09 | 156.09 | 0.00 | 180.00 | |
ROOM_5_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 156.09 | 156.09 | 180.00 | 0.00 | |
ROOM_6_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 270.00 | 90.00 | W |
ROOM_6_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 156.07 | 156.07 | 0.00 | 180.00 | |
ROOM_6_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 156.07 | 156.07 | 180.00 | 0.00 | |
CORRIDOR_FLR_3_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.28 | 847.28 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_4_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_3_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.27 | 847.27 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_4_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_FLOOR_1 | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 297.29 | 297.29 | 180.00 | 180.00 | |
CORRIDOR_FLR_3_FLOOR_2 | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 963.06 | 963.06 | 270.00 | 180.00 | |
CORRIDOR_FLR_3_FLOOR_3 | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 297.26 | 297.26 | 90.00 | 180.00 | |
CORRIDOR_FLR_3_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 297.29 | 297.29 | 90.00 | 0.00 | |
CORRIDOR_FLR_3_CEILING_2 | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 963.06 | 963.06 | 90.00 | 0.00 | |
CORRIDOR_FLR_3_CEILING_3 | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 297.26 | 297.26 | 90.00 | 0.00 | |
ROOM_1_FLR_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 13.94 | 13.94 | 0.00 | 90.00 | N |
ROOM_1_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.01 | 26.01 | 90.00 | 90.00 | E |
ROOM_1_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 39.02 | 39.02 | 0.00 | 180.00 | |
ROOM_2_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.01 | 26.01 | 90.00 | 90.00 | E |
ROOM_2_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 13.94 | 13.94 | 180.00 | 90.00 | S |
ROOM_2_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 39.02 | 39.02 | 0.00 | 180.00 | |
ROOM_3_MULT9_FLR_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 183.96 | 183.96 | 0.00 | 90.00 | N |
ROOM_3_MULT9_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 100.35 | 100.35 | 90.00 | 90.00 | E |
ROOM_3_MULT9_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 100.35 | 100.35 | 270.00 | 90.00 | W |
ROOM_3_MULT9_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 220.77 | 220.77 | 0.00 | 180.00 | |
BANQUET_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
BANQUET_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 180.00 | 90.00 | S |
BANQUET_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
BANQUET_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 331.66 | 331.66 | 0.00 | 180.00 | |
DINING_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
DINING_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 180.00 | 90.00 | S |
DINING_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
DINING_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 331.66 | 331.66 | 0.00 | 180.00 | |
KITCHEN_FLR_6_WALL_2_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 7.43 | 7.43 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 20.44 | 20.44 | 270.00 | 90.00 | W |
KITCHEN_FLR_6_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
KITCHEN_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 103.30 | 103.30 | 180.00 | 180.00 | |
CORRIDOR_FLR_6_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_4_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 104.98 | 104.98 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_1_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 183.95 | 183.95 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 11.15 | 11.15 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 40.88 | 40.88 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 20.44 | 20.44 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 412.12 | 412.12 | 180.00 | 180.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3957.66 | 0.00 | 90.00 | N | ||
RETAIL_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 134.14 | 0.00 | 90.00 | N | ||
RETAIL_2_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 155.34 | 0.00 | 90.00 | N | ||
MECH_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 328.49 | 0.00 | 90.00 | N | ||
STORAGE_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 189.52 | 0.00 | 90.00 | N | ||
LAUNDRY_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 156.08 | 0.00 | 90.00 | N | ||
CAFE_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 377.72 | 0.00 | 90.00 | N | ||
LOBBY_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 2616.37 | 0.00 | 90.00 | N | ||
ROOM_1_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.18 | 0.00 | 90.00 | N | ||
ROOM_2_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.14 | 0.00 | 90.00 | N | ||
ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3727.63 | 0.00 | 90.00 | N | ||
ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3728.64 | 0.00 | 90.00 | N | ||
ROOM_5_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.18 | 0.00 | 90.00 | N | ||
ROOM_6_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.14 | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3115.24 | 0.00 | 90.00 | N | ||
ROOM_1_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 78.04 | 0.00 | 90.00 | N | ||
ROOM_2_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 78.03 | 0.00 | 90.00 | N | ||
ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 441.55 | 0.00 | 90.00 | N | ||
BANQUET_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 663.31 | 0.00 | 90.00 | N | ||
DINING_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 663.31 | 0.00 | 90.00 | N | ||
KITCHEN_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 206.61 | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 824.25 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.3856_SHGC_0.4 | 23.26 | 0.00 | 0.00 | 23.26 | 23.26 | 2.191 | 0.401 | 0.402 | No | RETAIL_1_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
CAFE_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.3856_SHGC_0.4 | 65.50 | 0.00 | 0.00 | 65.50 | 65.50 | 2.191 | 0.401 | 0.402 | No | CAFE_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
LOBBY_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.3856_SHGC_0.4 | 85.08 | 0.00 | 0.00 | 85.08 | 85.08 | 2.191 | 0.401 | 0.402 | No | LOBBY_FLR_1_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.3856_SHGC_0.4 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.191 | 0.401 | 0.402 | No | ROOM_1_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.3856_SHGC_0.4 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.191 | 0.401 | 0.402 | No | ROOM_1_FLR_3_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_2_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.3856_SHGC_0.4 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.191 | 0.401 | 0.402 | No | ROOM_2_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_2_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.3856_SHGC_0.4 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.191 | 0.401 | 0.402 | No | ROOM_2_FLR_3_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.3856_SHGC_0.4 | 3.68 | 0.00 | 0.00 | 3.68 | 279.56 | 2.191 | 0.401 | 0.402 | No | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.3856_SHGC_0.4 | 3.68 | 0.00 | 0.00 | 3.68 | 279.65 | 2.191 | 0.401 | 0.402 | No | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_5_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.3856_SHGC_0.4 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.191 | 0.401 | 0.402 | No | ROOM_5_FLR_3_WALL_EAST | 90.00 | 90.00 | E | |||||||
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.3856_SHGC_0.4 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.191 | 0.401 | 0.402 | No | ROOM_5_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_6_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.3856_SHGC_0.4 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.191 | 0.401 | 0.402 | No | ROOM_6_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_6_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.3856_SHGC_0.4 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.191 | 0.401 | 0.402 | No | ROOM_6_FLR_3_WALL_EAST | 90.00 | 90.00 | E | |||||||
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.3856_SHGC_0.4 | 5.82 | 0.00 | 0.00 | 5.82 | 23.30 | 2.191 | 0.401 | 0.402 | No | CORRIDOR_FLR_3_WALL_1_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.3856_SHGC_0.4 | 2.15 | 0.00 | 0.00 | 2.15 | 8.59 | 2.191 | 0.401 | 0.402 | No | CORRIDOR_FLR_3_WALL_2_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.3856_SHGC_0.4 | 2.15 | 0.00 | 0.00 | 2.15 | 8.58 | 2.191 | 0.401 | 0.402 | No | CORRIDOR_FLR_3_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.3856_SHGC_0.4 | 5.82 | 0.00 | 0.00 | 5.82 | 23.30 | 2.191 | 0.401 | 0.402 | No | CORRIDOR_FLR_3_WALL_2_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.3856_SHGC_0.4 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.191 | 0.401 | 0.402 | No | ROOM_1_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.3856_SHGC_0.4 | 8.58 | 0.00 | 0.00 | 8.58 | 8.58 | 2.191 | 0.401 | 0.402 | No | ROOM_1_FLR_6_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_2_FLR_6_WALL_NORTH_WINDOW | RESWINDOW_U_0.3856_SHGC_0.4 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.191 | 0.401 | 0.402 | No | ROOM_2_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_2_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.3856_SHGC_0.4 | 8.58 | 0.00 | 0.00 | 8.58 | 8.58 | 2.191 | 0.401 | 0.402 | No | ROOM_2_FLR_6_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.3856_SHGC_0.4 | 6.74 | 0.00 | 0.00 | 6.74 | 60.70 | 2.191 | 0.401 | 0.402 | No | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
BANQUET_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.3856_SHGC_0.4 | 32.19 | 0.00 | 0.00 | 32.19 | 32.19 | 2.191 | 0.401 | 0.402 | No | BANQUET_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
DINING_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.3856_SHGC_0.4 | 32.19 | 0.00 | 0.00 | 32.19 | 32.19 | 2.191 | 0.401 | 0.402 | No | DINING_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
KITCHEN_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.3856_SHGC_0.4 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.191 | 0.401 | 0.402 | No | KITCHEN_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
KITCHEN_FLR_6_WALL_EAST_WINDOW | NONRESWINDOW_U_0.3856_SHGC_0.4 | 17.17 | 0.00 | 0.00 | 17.17 | 17.17 | 2.191 | 0.401 | 0.402 | No | KITCHEN_FLR_6_WALL_EAST | 90.00 | 90.00 | E | |||||||
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.3856_SHGC_0.4 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.191 | 0.401 | 0.402 | No | KITCHEN_FLR_6_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.3856_SHGC_0.4 | 5.82 | 0.00 | 0.00 | 5.82 | 5.82 | 2.191 | 0.401 | 0.402 | No | CORRIDOR_FLR_6_WALL_1_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.3856_SHGC_0.4 | 5.21 | 0.00 | 0.00 | 5.21 | 5.21 | 2.191 | 0.401 | 0.402 | No | CORRIDOR_FLR_6_WALL_2_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.3856_SHGC_0.4 | 17.17 | 0.00 | 0.00 | 17.17 | 17.17 | 2.191 | 0.401 | 0.402 | No | CORRIDOR_FLR_6_WALL_2_SOUTH | 180.00 | 90.00 | S | |||||||
Total or Average | 1213.79 | 2.191 | 0.401 | 0.402 | |||||||||||||||||
North Total or Average | 432.95 | 2.191 | 0.401 | 0.402 | |||||||||||||||||
Non-North Total or Average | 780.84 | 2.191 | 0.401 | 0.402 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
RETAIL_2_FLR_1_WALL_WEST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | RETAIL_2_FLR_1_WALL_WEST |
STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | OVERHEAD DOOR_CON | 1.016 | 1.198 | 7.43 | STORAGE_FLR_1_WALL_NORTH |
LAUNDRY_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | LAUNDRY_FLR_1_WALL_EAST |
CAFE_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | CAFE_FLR_1_WALL_EAST |
LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:58:38
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CAFE_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LOBBY_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
BANQUET_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:58:38
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 8.7495 | 1978.83 | 17313.73 | LightsWired | LTG_SCH_BASEMENT | 50.91 | 168.00 | 50.86 | 0.0000 | Y | 165.29 |
RETAIL_1_FLR_1_LIGHTS | RETAIL_1_FLR_1 | RETAIL_1_FLR_1 | GENERAL | 13.0124 | 67.07 | 872.76 | LightsWired | LTG_SCH_RETAIL | 51.36 | 168.00 | 51.30 | 0.0000 | Y | 8.40 |
RETAIL_2_FLR_1_LIGHTS | RETAIL_2_FLR_1 | RETAIL_2_FLR_1 | GENERAL | 13.0124 | 77.67 | 1010.66 | LightsWired | LTG_SCH_RETAIL | 51.36 | 168.00 | 51.30 | 0.0000 | Y | 9.73 |
MECH_FLR_1_LIGHTS | MECH_FLR_1 | MECH_FLR_1 | GENERAL | 10.0642 | 164.24 | 1652.98 | LightsWired | LTG_SCH_MECHANIC | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 18.19 |
STORAGE_FLR_1_LIGHTS | STORAGE_FLR_1 | STORAGE_FLR_1 | GENERAL | 7.3195 | 94.76 | 693.59 | LightsWired | LTG_SCH_STORAGE | 25.68 | 168.00 | 25.65 | 0.0000 | Y | 3.34 |
LAUNDRY_FLR_1_LIGHTS | LAUNDRY_FLR_1 | LAUNDRY_FLR_1 | GENERAL | 5.4896 | 78.04 | 428.40 | LightsWired | LTG_SCH_LAUNDRY | 51.36 | 168.00 | 51.30 | 0.0000 | Y | 4.13 |
CAFE_FLR_1_LIGHTS | CAFE_FLR_1 | CAFE_FLR_1 | GENERAL | 12.8090 | 188.86 | 2419.14 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 26.62 |
LOBBY_FLR_1_LIGHTS | LOBBY_FLR_1 | LOBBY_FLR_1 | GENERAL | 10.0642 | 1308.19 | 13165.91 | LightsWired | LTG_SCH_LOBBY | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 144.89 |
ROOM_1_FLR_3_LIGHTS | ROOM_1_FLR_3 | ROOM_1_FLR_3 | GENERAL | 10.0642 | 156.09 | 1570.91 | LightsWired | LTG_SCH_GUESTROOM | 69.03 | 168.00 | 69.21 | 0.0000 | Y | 20.41 |
ROOM_2_FLR_3_LIGHTS | ROOM_2_FLR_3 | ROOM_2_FLR_3 | GENERAL | 10.0642 | 156.07 | 1570.72 | LightsWired | LTG_SCH_GUESTROOM | 69.03 | 168.00 | 69.21 | 0.0000 | Y | 20.41 |
ROOM_3_MULT19_FLR_3_LIGHTS | ROOM_3_MULT19_FLR_3 | ROOM_3_MULT19_FLR_3 | GENERAL | 10.0642 | 1863.81 | 18757.86 | LightsWired | LTG_SCH_GUESTROOM | 69.03 | 168.00 | 69.21 | 0.0000 | Y | 243.70 |
ROOM_4_MULT19_FLR_3_LIGHTS | ROOM_4_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | GENERAL | 10.0642 | 1864.32 | 18762.99 | LightsWired | LTG_SCH_GUESTROOM | 69.03 | 168.00 | 69.21 | 0.0000 | Y | 243.77 |
ROOM_5_FLR_3_LIGHTS | ROOM_5_FLR_3 | ROOM_5_FLR_3 | GENERAL | 10.0642 | 156.09 | 1570.91 | LightsWired | LTG_SCH_GUESTROOM | 69.03 | 168.00 | 69.21 | 0.0000 | Y | 20.41 |
ROOM_6_FLR_3_LIGHTS | ROOM_6_FLR_3 | ROOM_6_FLR_3 | GENERAL | 10.0642 | 156.07 | 1570.72 | LightsWired | LTG_SCH_GUESTROOM | 69.03 | 168.00 | 69.21 | 0.0000 | Y | 20.41 |
CORRIDOR_FLR_3_LIGHTS | CORRIDOR_FLR_3 | CORRIDOR_FLR_3 | GENERAL | 3.6597 | 1557.62 | 5700.46 | LightsWired | LTG_SCH_CORRIDOR | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 62.73 |
ROOM_1_FLR_6_LIGHTS | ROOM_1_FLR_6 | ROOM_1_FLR_6 | GENERAL | 10.0642 | 39.02 | 392.73 | LightsWired | LTG_SCH_GUESTROOM | 69.03 | 168.00 | 69.21 | 0.0000 | Y | 5.10 |
ROOM_2_FLR_6_LIGHTS | ROOM_2_FLR_6 | ROOM_2_FLR_6 | GENERAL | 10.0642 | 39.02 | 392.68 | LightsWired | LTG_SCH_GUESTROOM | 69.03 | 168.00 | 69.21 | 0.0000 | Y | 5.10 |
ROOM_3_MULT9_FLR_6_LIGHTS | ROOM_3_MULT9_FLR_6 | ROOM_3_MULT9_FLR_6 | GENERAL | 10.0642 | 220.77 | 2221.93 | LightsWired | LTG_SCH_GUESTROOM | 69.03 | 168.00 | 69.21 | 0.0000 | Y | 28.87 |
BANQUET_FLR_6_LIGHTS | BANQUET_FLR_6 | BANQUET_FLR_6 | GENERAL | 12.8090 | 331.66 | 4248.21 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 46.75 |
DINING_FLR_6_LIGHTS | DINING_FLR_6 | DINING_FLR_6 | GENERAL | 12.8090 | 331.66 | 4248.21 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 46.75 |
KITCHEN_FLR_6_LIGHTS | KITCHEN_FLR_6 | KITCHEN_FLR_6 | GENERAL | 10.9792 | 103.30 | 1134.20 | LightsWired | LTG_SCH_KITCHEN | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 12.48 |
CORRIDOR_FLR_6_LIGHTS | CORRIDOR_FLR_6 | CORRIDOR_FLR_6 | GENERAL | 3.6597 | 412.12 | 1508.26 | LightsWired | LTG_SCH_CORRIDOR | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 16.60 |
Interior Lighting Total | 8.9207 | 11345.29 | 101207.97 | 559.10 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR FACADE LIGHTING | 16690.39 | AstronomicalClock | - | 83.55 | 83.55 | 261.75 | |
Exterior Lighting Total | 16690.39 | 261.75 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:58:38
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
HEATSYS1 BOILER | Boiler:HotWater | 449580.52 | 0.80 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:EIR | 847934.14 | 2.80 | 848083.19 | 2.80 | 3.72 | 12.68 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 15389.39 | 22361.69 | 17662.04 | 4699.65 | 0.79 | - | 2516.91 | 25.53 |
ROOM_2_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 13952.77 | 20262.56 | 15997.96 | 4264.60 | 0.79 | - | 2280.41 | 23.13 |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 108138.69 | 157977.04 | 125227.36 | 32749.68 | 0.79 | - | 17799.05 | 180.53 |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 75503.16 | 107973.60 | 84404.15 | 23569.45 | 0.78 | - | 12121.62 | 122.94 |
ROOM_5_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 13870.50 | 20141.74 | 15901.85 | 4239.88 | 0.79 | - | 2266.78 | 22.99 |
ROOM_6_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 12679.52 | 18401.34 | 14522.07 | 3879.27 | 0.79 | - | 2070.69 | 21.00 |
ROOM_1_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 4078.64 | 5928.41 | 4683.47 | 1244.94 | 0.79 | - | 667.31 | 6.77 |
ROOM_2_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 3673.73 | 5336.75 | 4214.42 | 1122.33 | 0.79 | - | 600.65 | 6.09 |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 22403.04 | 32459.50 | 25588.79 | 6870.71 | 0.79 | - | 3651.60 | 37.04 |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | 532172.51 | 582088.24 | 401259.64 | 180828.60 | 0.69 | - | 67759.23 | 687.25 |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | 45447.84 | 49660.04 | 34741.99 | 14918.05 | 0.70 | - | 5487.20 | 55.65 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
BASEMENT VAV BOX REHEAT COIL | Coil:Heating:Water | 13128.07 | 13195.94 | - |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 4813.58 | 4837.38 | - |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1983.83 | 1993.79 | - |
MECH_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 2535.33 | 2547.55 | - |
STORAGE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1427.35 | 1434.12 | - |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 18839.94 | 18936.86 | - |
CAFE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 15667.23 | 15745.92 | - |
LOBBY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 40467.87 | 40672.15 | - |
ROOM_1_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 5261.29 | 5667.04 | - |
ROOM_2_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 5264.82 | 5670.83 | - |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 30250.93 | 32583.60 | - |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 30331.96 | 32670.86 | - |
ROOM_5_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 5268.99 | 5675.32 | - |
ROOM_6_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 5272.51 | 5679.11 | - |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 14846.53 | 14917.71 | - |
ROOM_1_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 1644.48 | 1771.24 | - |
ROOM_2_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 1646.29 | 1773.19 | - |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 7921.49 | 8532.07 | - |
BANQUET_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 16879.03 | 16964.30 | - |
DINING_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 17540.15 | 17628.82 | - |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 12866.46 | 12932.77 | - |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 9755.86 | 9802.00 | - |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | 170625.59 | 129964.28 | - |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | 15340.96 | 11685.10 | - |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
LAUNDRY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 0.16 | 125.00 | 0.24 | 184.35 | 781.25 | 1.00 | 1.15 | General | ||
LOBBY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | General | |||
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.16 | 270.90 | 1.29 | 2180.47 | 1693.12 | 1.00 | 0.47 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 |
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.16 | 270.90 | 1.17 | 1973.80 | 1693.12 | 1.00 | 0.48 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 16:50:00 |
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.16 | 270.90 | 9.18 | 15550.82 | 1693.12 | 1.00 | 0.39 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 |
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.16 | 270.90 | 6.05 | 10245.09 | 1693.12 | 1.00 | 0.40 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 |
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.16 | 270.90 | 1.16 | 1961.80 | 1693.12 | 1.00 | 0.48 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 |
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.16 | 270.90 | 1.06 | 1790.43 | 1693.12 | 1.00 | 0.49 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 |
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.16 | 270.90 | 0.34 | 578.40 | 1693.12 | 1.00 | 0.68 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 |
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.16 | 270.90 | 0.31 | 520.14 | 1693.12 | 1.00 | 0.71 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 16:50:00 |
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.16 | 270.90 | 1.86 | 3149.27 | 1693.12 | 1.00 | 0.45 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 |
BANQUET_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | General | |||
DINING_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | General | |||
KITCHEN_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 0.16 | 125.00 | 1.89 | 1474.84 | 781.25 | 1.00 | 0.62 | General | ||
VAV WITH REHEAT FAN | Fan:VariableVolume | 0.62 | 1389.42 | 22.82 | 51120.62 | 2240.64 | 1.00 | 1.11 | General | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 19:20:00 |
FLR_3_DOAS FAN | Fan:ConstantVolume | 0.58 | 622.50 | 2.05 | 2194.93 | 1070.05 | 1.00 | 1.30 | General | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 133527.72 | 0.030264 | 6236.24 | 206062.94 | 0.90 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.003933 | 1184.48 | 301156.09 | 0.90 | General |
COOLSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 92445.74 | 0.030264 | 4317.56 | 142664.32 | 0.90 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000375 | 47.91 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWH BOOSTER E WATER HEATER | WaterHeater:Mixed | 0.02 | 8000.00 | 1.00 | 1.24 | 1.15 |
SWH LAUNDRY G WATER HEATER | WaterHeater:Mixed | 1.14 | 163316.00 | 0.80 | 0.58 | 0.51 |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 2.27 | 175842.60 | 0.80 | 0.26 | 0.03 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:58:38
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 34392.65 | 34392.65 | 17.38 | 2.535 | 2.535 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:30:00 | 24.00 | 24.00 | 0.00920 | 26.12 | 0.00882 | 0.854 | 0.00 |
RETAIL_1_FLR_1 | 6546.65 | 6546.65 | 97.61 | 0.483 | 0.483 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 24.00 | 24.00 | 0.00887 | 29.05 | 0.00882 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 3272.26 | 3272.26 | 42.13 | 0.241 | 0.241 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 24.00 | 24.00 | 0.00936 | 29.30 | 0.00882 | 0.092 | 0.00 |
MECH_FLR_1 | 3133.39 | 3133.39 | 19.08 | 0.231 | 0.231 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 | 24.00 | 24.00 | 0.00870 | 29.19 | 0.00882 | 0.000 | 0.00 |
STORAGE_FLR_1 | 1550.63 | 1550.63 | 16.36 | 0.114 | 0.114 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 24.00 | 24.00 | 0.00880 | 29.40 | 0.00882 | 0.058 | 0.00 |
LAUNDRY_FLR_1 | 44771.61 | 44771.61 | 573.70 | 3.300 | 3.300 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 24.00 | 24.00 | 0.00854 | 29.40 | 0.00882 | 0.000 | 0.00 |
CAFE_FLR_1 | 25635.91 | 25635.91 | 135.74 | 1.891 | 1.891 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 24.00 | 23.99 | 0.00974 | 29.05 | 0.00882 | 0.676 | 0.00 |
LOBBY_FLR_1 | 70940.37 | 70940.37 | 54.23 | 5.231 | 5.231 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 24.00 | 23.99 | 0.00984 | 29.14 | 0.00882 | 1.894 | 0.00 |
ROOM_1_FLR_3 | 12966.23 | 12966.23 | 332.28 | 1.288 | 1.288 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 21.11 | 21.11 | 0.00856 | 28.36 | 0.00882 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 11737.27 | 11737.27 | 300.82 | 1.166 | 1.166 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 16:50:00 | 21.11 | 21.11 | 0.00857 | 28.08 | 0.00882 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 92477.70 | 92477.70 | 3770.93 | 9.185 | 9.185 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 21.11 | 21.11 | 0.00850 | 29.14 | 0.00882 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 60920.91 | 60920.91 | 2483.47 | 6.051 | 6.051 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 21.11 | 21.11 | 0.00874 | 29.40 | 0.00882 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 11665.92 | 11665.92 | 298.96 | 1.159 | 1.159 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 21.11 | 21.11 | 0.00857 | 25.45 | 0.00882 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 10646.82 | 10646.82 | 272.87 | 1.057 | 1.057 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 21.11 | 21.11 | 0.00858 | 23.68 | 0.00881 | 0.062 | 0.00 |
CORRIDOR_FLR_3 | 17523.69 | 17523.69 | 45.00 | 1.292 | 1.292 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:10:00 | 24.00 | 24.00 | 0.00958 | 29.40 | 0.00882 | 0.475 | 0.00 |
ROOM_1_FLR_6 | 3439.48 | 3439.48 | 88.14 | 0.342 | 0.342 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 21.11 | 21.11 | 0.00856 | 28.36 | 0.00882 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 3093.05 | 3093.05 | 79.27 | 0.307 | 0.307 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 16:50:00 | 21.11 | 21.11 | 0.00857 | 28.08 | 0.00882 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 18726.83 | 18726.83 | 763.41 | 1.860 | 1.860 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 21.11 | 21.11 | 0.00859 | 29.23 | 0.00882 | 0.099 | 0.00 |
BANQUET_FLR_6 | 29879.79 | 29879.79 | 90.09 | 2.205 | 2.205 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 24.00 | 23.99 | 0.01038 | 29.40 | 0.00882 | 1.188 | 0.00 |
DINING_FLR_6 | 31343.45 | 31343.45 | 94.51 | 2.313 | 2.313 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 24.00 | 23.99 | 0.01029 | 29.40 | 0.00882 | 1.188 | 0.00 |
KITCHEN_FLR_6 | 31486.72 | 31486.72 | 304.80 | 2.327 | 2.327 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 12:30:00 | 24.00 | 23.97 | 0.01003 | 28.46 | 0.00882 | 0.367 | 0.00 |
CORRIDOR_FLR_6 | 10407.46 | 10407.46 | 25.25 | 0.767 | 0.767 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 24.00 | 24.00 | 0.00898 | 29.40 | 0.00882 | 0.126 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 0.854 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.99 | 0.00269 | -4.20 | 0.00269 | 0.854 | 0.00 |
RETAIL_1_FLR_1 | 2317.04 | 2317.04 | 34.55 | 0.101 | 0.101 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00749 | -4.20 | 0.00269 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 736.06 | 736.06 | 9.48 | 0.032 | 0.092 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00740 | -4.20 | 0.00269 | 0.092 | 0.00 |
MECH_FLR_1 | 1341.11 | 1341.11 | 8.17 | 0.058 | 0.058 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00724 | -4.20 | 0.00269 | 0.000 | 0.00 |
STORAGE_FLR_1 | 836.31 | 836.31 | 8.83 | 0.036 | 0.058 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00729 | -4.20 | 0.00269 | 0.058 | 0.00 |
LAUNDRY_FLR_1 | 1776.54 | 1776.54 | 22.76 | 0.077 | 0.077 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00722 | -4.20 | 0.00269 | 0.000 | 0.00 |
CAFE_FLR_1 | 5882.08 | 5882.08 | 31.14 | 0.256 | 0.676 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00755 | -4.20 | 0.00269 | 0.676 | 0.00 |
LOBBY_FLR_1 | 13407.07 | 13407.07 | 10.25 | 0.583 | 1.894 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00745 | -4.20 | 0.00269 | 1.894 | 0.00 |
ROOM_1_FLR_3 | 5261.42 | 5261.42 | 134.83 | 0.230 | 0.230 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00749 | -4.20 | 0.00269 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 5264.94 | 5264.94 | 134.94 | 0.230 | 0.230 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00749 | -4.20 | 0.00269 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 30251.28 | 30251.28 | 1233.55 | 1.323 | 1.323 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00752 | -4.20 | 0.00269 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 30332.31 | 30332.31 | 1236.51 | 1.327 | 1.327 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00752 | -4.20 | 0.00269 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 5269.11 | 5269.11 | 135.03 | 0.230 | 0.230 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00749 | -4.20 | 0.00269 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 5272.63 | 5272.63 | 135.14 | 0.231 | 0.231 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00749 | -4.20 | 0.00269 | 0.062 | 0.00 |
CORRIDOR_FLR_3 | 8162.84 | 8162.84 | 20.96 | 0.355 | 0.475 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00759 | -4.20 | 0.00269 | 0.475 | 0.00 |
ROOM_1_FLR_6 | 1644.52 | 1644.52 | 42.14 | 0.072 | 0.072 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00758 | -4.20 | 0.00269 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 1646.33 | 1646.33 | 42.19 | 0.072 | 0.072 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00758 | -4.20 | 0.00269 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 7921.64 | 7921.64 | 322.93 | 0.346 | 0.346 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00760 | -4.20 | 0.00269 | 0.099 | 0.00 |
BANQUET_FLR_6 | 5466.95 | 5466.95 | 16.48 | 0.238 | 1.188 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00768 | -4.20 | 0.00269 | 1.188 | 0.00 |
DINING_FLR_6 | 5569.46 | 5569.46 | 16.79 | 0.242 | 1.188 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 19:20:00 | 21.00 | 21.00 | 0.00769 | -4.20 | 0.00269 | 1.188 | 0.00 |
KITCHEN_FLR_6 | 903.02 | 903.02 | 8.74 | 0.039 | 0.367 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | 21.00 | 21.00 | 0.00462 | -4.20 | 0.00269 | 0.367 | 0.00 |
CORRIDOR_FLR_6 | 5785.47 | 5785.47 | 14.04 | 0.252 | 0.252 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 19:20:00 | 21.00 | 21.00 | 0.00773 | -4.20 | 0.00269 | 0.126 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV WITH REHEAT | 22.81 | 22.81 | 7.28 | 7.28 | 22.8152 | 22.8152 | 22.8152 | 1.0000 | 0.3000 |
FLR_3_DOAS | 21.03 | 2.05 | 4.06 | 2.05 | 2.0513 | 2.0513 | 2.0513 | 1.0000 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
BASEMENT VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | 13128.066 | 13128.066 | 2.522363 | 0.00011485 | 273.763 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 13128.07 | 13128.07 | 2.522363 | 16.70 | 13.06 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00800000 | 50.9797 | 0.00 | 0.00 | 13201.85 | 13201.85 |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | 4813.578 | 4813.578 | 0.480172 | 0.00004211 | 105.470 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 4813.58 | 4813.58 | 0.480172 | 16.70 | 13.06 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00749283 | 47.7877 | 2317.04 | 0.00 | 4840.21 | 4840.21 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | 1983.825 | 1983.825 | 0.240014 | 0.00001736 | 42.674 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 1983.83 | 1983.83 | 0.240014 | 16.70 | 13.06 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00739592 | 47.1759 | 736.06 | 0.00 | 1994.86 | 1994.86 |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | 2535.329 | 2535.329 | 0.229779 | 0.00002218 | 56.146 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 2535.33 | 2535.33 | 0.229779 | 16.70 | 13.06 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00724193 | 46.2050 | 1341.11 | 0.00 | 2549.12 | 2549.12 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | 1427.352 | 1427.352 | 0.113713 | 0.00001249 | 32.133 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 1427.35 | 1427.35 | 0.113713 | 16.70 | 13.06 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00729112 | 46.5152 | 836.31 | 0.00 | 1435.07 | 1435.07 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 18839.936 | 18839.936 | 3.283525 | 0.00016482 | 394.971 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 18839.94 | 18839.94 | 3.283525 | 16.70 | 13.06 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00722235 | 46.0825 | 1776.54 | 0.00 | 18945.62 | 18945.62 |
CAFE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | 15667.235 | 15667.235 | 1.881782 | 0.00013706 | 337.231 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 15667.23 | 15667.23 | 1.881782 | 16.70 | 13.06 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00755285 | 48.1656 | 5882.08 | 0.00 | 15754.36 | 15754.36 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 40467.872 | 40467.872 | 5.204748 | 0.00035403 | 866.119 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 40467.87 | 40467.87 | 5.204748 | 16.70 | 13.06 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00745102 | 47.5233 | 13407.07 | 0.00 | 40693.31 | 40693.31 |
ROOM_1_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 15389.389 | -999.000 | 1.287836 | 0.00054966 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | unknown | 8/21 16:30:00 | 15389.39 | 15177.00 | 1.287836 | 22.51 | 15.76 | 0.00856250 | 12.80 | 11.97 | 0.00850000 | 28.36 | 0.00881983 | 18.00 | 0.0000 | 21.11 | 0.00856250 | 54.1463 | 12966.23 | 0.00 | 15597.20 | 15114.65 |
ROOM_1_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 5261.295 | 5261.295 | 0.230115 | 0.00004603 | 150.354 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 5261.29 | 5261.29 | 0.230115 | 21.11 | 14.28 | 0.00748529 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.11 | 0.00748529 | 47.4161 | 5261.42 | 0.00 | 5671.81 | 5671.81 |
ROOM_2_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 13952.769 | -999.000 | 1.165774 | 0.00049835 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 16:50:00 | unknown | 8/21 16:50:00 | 13952.77 | 13741.21 | 1.165774 | 22.51 | 15.77 | 0.00856876 | 12.80 | 11.97 | 0.00850000 | 28.08 | 0.00881938 | 17.91 | 0.0000 | 21.11 | 0.00856876 | 54.1853 | 11737.27 | 0.00 | 14141.03 | 13685.41 |
ROOM_2_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 5264.816 | 5264.816 | 0.230269 | 0.00004606 | 150.455 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 5264.82 | 5264.82 | 0.230269 | 21.11 | 14.28 | 0.00748564 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.11 | 0.00748564 | 47.4182 | 5264.94 | 0.00 | 5675.60 | 5675.60 |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 108138.694 | -999.000 | 9.184683 | 0.00386239 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | unknown | 8/21 13:30:00 | 108138.69 | 108042.45 | 9.184683 | 22.51 | 15.71 | 0.00850398 | 12.80 | 11.97 | 0.00850000 | 29.14 | 0.00882108 | 18.26 | 0.0000 | 21.11 | 0.00850398 | 53.7800 | 92477.70 | 0.00 | 109610.00 | 107550.23 |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 30250.932 | 30250.932 | 1.323118 | 0.00026465 | 864.479 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 30250.93 | 30250.93 | 1.323118 | 21.11 | 14.31 | 0.00752181 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.11 | 0.00752181 | 47.6436 | 30251.28 | 0.00 | 32611.44 | 32611.44 |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 75503.163 | -999.000 | 6.050996 | 0.00269675 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | unknown | 8/21 15:00:00 | 75503.16 | 71687.15 | 6.050996 | 22.51 | 15.92 | 0.00873772 | 12.80 | 11.97 | 0.00850000 | 29.40 | 0.00882150 | 18.34 | 0.0000 | 21.11 | 0.00873772 | 55.2398 | 60920.91 | 0.00 | 76500.51 | 71483.66 |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 30331.957 | 30331.957 | 1.326662 | 0.00026536 | 866.794 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 30331.96 | 30331.96 | 1.326662 | 21.11 | 14.32 | 0.00752285 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.11 | 0.00752285 | 47.6502 | 30332.31 | 0.00 | 32698.79 | 32698.79 |
ROOM_5_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 13870.500 | -999.000 | 1.158687 | 0.00049541 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | unknown | 8/21 10:00:00 | 13870.50 | 13657.99 | 1.158687 | 22.51 | 15.77 | 0.00856949 | 12.80 | 11.97 | 0.00850000 | 25.45 | 0.00881519 | 17.01 | 0.0000 | 21.11 | 0.00856949 | 54.1899 | 11665.92 | 0.00 | 14057.63 | 13602.60 |
ROOM_5_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 5268.987 | 5268.987 | 0.230451 | 0.00004610 | 150.574 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 5268.99 | 5268.99 | 0.230451 | 21.11 | 14.28 | 0.00748597 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.11 | 0.00748597 | 47.4203 | 5269.11 | 0.00 | 5680.10 | 5680.10 |
ROOM_6_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 12679.524 | -999.000 | 1.057468 | 0.00045287 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | unknown | 8/21 09:00:00 | 12679.52 | 12467.41 | 1.057468 | 22.51 | 15.78 | 0.00857598 | 12.80 | 11.97 | 0.00850000 | 23.68 | 0.00881240 | 16.40 | 0.0000 | 21.11 | 0.00857598 | 54.2304 | 10646.82 | 0.00 | 12850.44 | 12417.46 |
ROOM_6_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 5272.507 | 5272.507 | 0.230605 | 0.00004613 | 150.675 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 5272.51 | 5272.51 | 0.230605 | 21.11 | 14.28 | 0.00748632 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.11 | 0.00748632 | 47.4225 | 5272.63 | 0.00 | 5683.89 | 5683.89 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | 14846.527 | 14846.527 | 1.285163 | 0.00012988 | 330.621 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 14846.53 | 14846.53 | 1.285163 | 16.70 | 13.06 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00758766 | 48.3840 | 8162.84 | 0.00 | 14927.10 | 14927.10 |
ROOM_1_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 4078.641 | -999.000 | 0.341617 | 0.00014568 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | unknown | 8/21 16:30:00 | 4078.64 | 4025.47 | 0.341617 | 22.51 | 15.76 | 0.00855899 | 12.80 | 11.97 | 0.00850000 | 28.36 | 0.00881983 | 18.00 | 0.0000 | 21.11 | 0.00855899 | 54.1244 | 3439.48 | 0.00 | 4133.74 | 4008.83 |
ROOM_1_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 1644.478 | 1644.478 | 0.071925 | 0.00001439 | 46.992 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 1644.48 | 1644.48 | 0.071925 | 21.11 | 14.37 | 0.00758009 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.11 | 0.00758009 | 48.0094 | 1644.52 | 0.00 | 1772.79 | 1772.79 |
ROOM_2_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 3673.731 | -999.000 | 0.307209 | 0.00013121 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 16:50:00 | unknown | 8/21 16:50:00 | 3673.73 | 3620.75 | 0.307209 | 22.51 | 15.77 | 0.00856535 | 12.80 | 11.97 | 0.00850000 | 28.08 | 0.00881938 | 17.91 | 0.0000 | 21.11 | 0.00856535 | 54.1641 | 3093.05 | 0.00 | 3723.32 | 3605.95 |
ROOM_2_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 1646.289 | 1646.289 | 0.072004 | 0.00001440 | 47.044 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 1646.29 | 1646.29 | 0.072004 | 21.11 | 14.37 | 0.00758055 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.11 | 0.00758055 | 48.0122 | 1646.33 | 0.00 | 1774.74 | 1774.74 |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 22403.043 | -999.000 | 1.860033 | 0.00080017 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | unknown | 8/21 13:40:00 | 22403.04 | 21941.43 | 1.860033 | 22.51 | 15.79 | 0.00859396 | 12.80 | 11.97 | 0.00850000 | 29.23 | 0.00882122 | 18.29 | 0.0000 | 21.11 | 0.00859396 | 54.3431 | 18726.83 | 0.00 | 22704.35 | 21856.46 |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 7921.492 | 7921.492 | 0.346467 | 0.00006930 | 226.361 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 7921.49 | 7921.49 | 0.346467 | 21.11 | 14.38 | 0.00759720 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.11 | 0.00759720 | 48.1160 | 7921.64 | 0.00 | 8539.58 | 8539.58 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 16879.027 | 16879.027 | 2.194030 | 0.00014767 | 360.951 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 16879.03 | 16879.03 | 2.194030 | 16.70 | 13.06 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00768322 | 48.9862 | 5466.95 | 0.00 | 16973.08 | 16973.08 |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 17540.148 | 17540.148 | 2.301469 | 0.00015345 | 374.812 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 19:20:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 19:20:00 | 17540.15 | 17540.15 | 2.301469 | 16.70 | 13.06 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00768868 | 49.0210 | 5569.46 | 0.00 | 17637.91 | 17637.91 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 12866.461 | 12866.461 | 2.315184 | 0.00011256 | 269.254 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | 12866.46 | 12866.46 | 2.315184 | 16.70 | 13.06 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00461594 | 29.5816 | 903.02 | 0.00 | 12938.68 | 12938.68 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | 9755.857 | 9755.857 | 0.763260 | 0.00008535 | 220.183 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 19:20:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 19:20:00 | 9755.86 | 9755.86 | 0.763260 | 16.70 | 13.06 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00773497 | 49.3122 | 5785.47 | 0.00 | 9808.53 | 9808.53 |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV WITH REHEAT | 532172.511 | -999.000 | 22.815202 | 0.01900797 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 532172.51 | 509413.61 | 22.815202 | 29.40 | 18.34 | 0.00882150 | 10.95 | 10.95 | 0.00850000 | 29.40 | 0.00882150 | 18.34 | 99.9811 | 23.99 | 0.00960308 | 50.8910 | 309119.76 | 0.00 | 537523.92 | 490538.65 |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV WITH REHEAT | 170625.589 | 170625.589 | 6.844561 | 0.00149271 | 2912.959 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 19:20:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 19:20:00 | 170625.59 | 170625.59 | 6.844561 | -4.20 | -4.20 | 0.00269032 | 16.70 | 13.06 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 333.2703 | 21.36 | 0.00586588 | 36.6976 | 51613.00 | 0.00 | 157193.69 | 157193.69 |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | FLR_3_DOAS | 45447.837 | -999.000 | 2.051317 | 0.00162329 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 45447.84 | 43504.21 | 2.051317 | 29.40 | 18.34 | 0.00882150 | 11.92 | 11.61 | 0.00850000 | 29.40 | 0.00882150 | 18.34 | 99.9965 | 21.11 | 0.00859780 | 54.3661 | 211782.54 | 0.00 | 45923.42 | 42707.30 |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | FLR_3_DOAS | 15340.965 | 15340.965 | 0.615395 | 0.00013421 | 261.904 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 15340.96 | 15340.96 | 0.615395 | -4.20 | -4.20 | 0.00269032 | 16.70 | 13.06 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 333.3216 | 21.11 | 0.00752285 | 47.6501 | 92864.18 | 0.00 | 14133.30 | 14133.30 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:58:38
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
BASEMENT VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | BASEMENT | N/A | N/A | N/A | Yes | Yes | Yes | No | 13128.066 | 13128.066 | 2.522363 | 0.00011485 | 273.763 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.93272529 | 54.44 | 82.22 | 27.78 | 458628.51 | 2.8625 | 2.920070 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 13128.07 | 13128.07 | 1.0000 | 2.99402166 | 2.522363 | 16.70 | 13.06 | 0.00800000 | 37036.7 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.11483833 | 60.00 | 32.22 | 27.78 | 0.000 | 13128.07 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 50.9797 | 0.00 | 0.00 | 13201.85 | 13201.85 | 2.99402166 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 20.92 | 14.82 | 0.00800000 | 41344.1 | |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | RETAIL_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 4813.578 | 4813.578 | 0.480172 | 0.00004211 | 105.470 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.93272529 | 54.44 | 82.22 | 27.78 | 458628.51 | 1.0496 | 1.070682 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 4813.58 | 4813.58 | 1.0000 | 0.56995970 | 0.480172 | 16.70 | 13.06 | 0.00800000 | 37036.7 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.04210698 | 60.00 | 32.22 | 27.78 | 0.000 | 4813.58 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.00 | 0.00749283 | 21.00 | 0.00749283 | 47.7877 | 2317.04 | 0.00 | 4840.21 | 4840.21 | 0.56995970 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 24.93 | 16.29 | 0.00800000 | 45426.9 | |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | RETAIL_2_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1983.825 | 1983.825 | 0.240014 | 0.00001736 | 42.674 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.93272529 | 54.44 | 82.22 | 27.78 | 458628.51 | 0.4326 | 0.441261 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 1983.83 | 1983.83 | 1.0000 | 0.28489450 | 0.240014 | 16.70 | 13.06 | 0.00800000 | 37036.7 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.01735360 | 60.00 | 32.22 | 27.78 | 0.000 | 1983.83 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.00 | 0.00739592 | 21.00 | 0.00739592 | 47.1759 | 736.06 | 0.00 | 1994.86 | 1994.86 | 0.28489450 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 23.47 | 15.76 | 0.00800000 | 43936.8 | |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | MECH_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2535.329 | 2535.329 | 0.229779 | 0.00002218 | 56.146 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.93272529 | 54.44 | 82.22 | 27.78 | 458628.51 | 0.5528 | 0.563932 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 2535.33 | 2535.33 | 1.0000 | 0.27274585 | 0.229779 | 16.70 | 13.06 | 0.00800000 | 37036.7 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.02217790 | 60.00 | 32.22 | 27.78 | 0.000 | 2535.33 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.00 | 0.00724193 | 21.00 | 0.00724193 | 46.2050 | 1341.11 | 0.00 | 2549.12 | 2549.12 | 0.27274585 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 25.77 | 16.58 | 0.00800000 | 46280.9 | |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | STORAGE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1427.352 | 1427.352 | 0.113713 | 0.00001249 | 32.133 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.93272529 | 54.44 | 82.22 | 27.78 | 458628.51 | 0.3112 | 0.317485 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 1427.35 | 1427.35 | 1.0000 | 0.13497615 | 0.113713 | 16.70 | 13.06 | 0.00800000 | 37036.7 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.01248583 | 60.00 | 32.22 | 27.78 | 0.000 | 1427.35 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.00 | 0.00729112 | 21.00 | 0.00729112 | 46.5152 | 836.31 | 0.00 | 1435.07 | 1435.07 | 0.13497615 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 27.03 | 17.03 | 0.00800000 | 47566.7 | |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LAUNDRY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 18839.936 | 18839.936 | 3.283525 | 0.00016482 | 394.971 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.93272529 | 54.44 | 82.22 | 27.78 | 458628.51 | 4.1079 | 4.190559 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 18839.94 | 18839.94 | 1.0000 | 3.89751382 | 3.283525 | 16.70 | 13.06 | 0.00800000 | 37036.7 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.16480317 | 60.00 | 32.22 | 27.78 | 0.000 | 18839.94 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.00 | 0.00722235 | 21.00 | 0.00722235 | 46.0825 | 1776.54 | 0.00 | 18945.62 | 18945.62 | 3.89751382 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 21.37 | 14.99 | 0.00800000 | 41795.7 | |
CAFE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | CAFE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 15667.235 | 15667.235 | 1.881782 | 0.00013706 | 337.231 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.93272529 | 54.44 | 82.22 | 27.78 | 458628.51 | 3.4161 | 3.484856 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 15667.23 | 15667.23 | 1.0000 | 2.23365826 | 1.881782 | 16.70 | 13.06 | 0.00800000 | 37036.7 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.13704982 | 60.00 | 32.22 | 27.78 | 0.000 | 15667.23 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.00 | 0.00755285 | 21.00 | 0.00755285 | 48.1656 | 5882.08 | 0.00 | 15754.36 | 15754.36 | 2.23365826 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 23.52 | 15.78 | 0.00800000 | 43987.9 | |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LOBBY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 40467.872 | 40467.872 | 5.204748 | 0.00035403 | 866.119 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.93272529 | 54.44 | 82.22 | 27.78 | 458628.51 | 8.8237 | 9.001251 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 40467.87 | 40467.87 | 1.0000 | 6.17798815 | 5.204748 | 16.70 | 13.06 | 0.00800000 | 37036.7 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.35399448 | 60.00 | 32.22 | 27.78 | 0.000 | 40467.87 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.00 | 0.00745102 | 21.00 | 0.00745102 | 47.5233 | 13407.07 | 0.00 | 40693.31 | 40693.31 | 6.17798815 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 23.06 | 15.61 | 0.00800000 | 43521.6 | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 15389.389 | -999.000 | 1.287836 | 0.00054966 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7573 | 1004.8586 | 1.1870 | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.287836 | 1.52864962 | 4197.9300 | 999.8980 | 30.26067582 | 13.37 | 6.70 | 6.67 | 847304.77 | 1.8163 | 1.816242 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | unknown | unknown | unknown | 8/21 16:30:00 | Sensible | 15389.39 | 15177.00 | 1.0000 | 1.52864962 | 1.287836 | 22.51 | 15.76 | 0.00856250 | 44389.5 | 12.80 | 11.97 | 0.00850000 | 34322.2 | 0.54960699 | 6.70 | 13.37 | 6.67 | 0.000 | 15389.39 | 28.36 | 0.00881983 | 18.00 | 0.00000000 | 0.0000 | 21.11 | 0.00856250 | 21.11 | 0.00856250 | 54.1463 | 12966.23 | 0.00 | 15597.20 | 15114.65 | 1.52864962 | 22.51 | 15.91 | 0.00856250 | 44389.5 | 12.82 | 12.05 | 0.00843747 | 34186.3 | |
ROOM_1_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5261.295 | 5261.295 | 0.230115 | 0.00004603 | 150.354 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.287836 | 1.52864962 | 4197.9300 | 999.8980 | 3.93272529 | 54.44 | 82.22 | 27.78 | 458628.51 | 1.1472 | 1.170268 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 5261.29 | 5261.29 | 1.0000 | 0.27314430 | 0.230115 | 21.11 | 14.28 | 0.00748529 | 40226.6 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.04602341 | 60.00 | 32.22 | 27.78 | 0.000 | 5261.29 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.11 | 0.00748529 | 21.11 | 0.00748529 | 47.4161 | 5261.42 | 0.00 | 5671.81 | 5671.81 | 0.27314430 | 16.60 | 12.65 | 0.00748529 | 35631.6 | 36.98 | 19.89 | 0.00748529 | 56396.5 | |
ROOM_2_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 13952.769 | -999.000 | 1.165774 | 0.00049835 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7689 | 1004.8586 | 1.1870 | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.165774 | 1.38376330 | 4197.9300 | 999.8980 | 30.26067582 | 13.37 | 6.70 | 6.67 | 847304.77 | 1.6467 | 1.646693 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 16:50:00 | unknown | unknown | unknown | 8/21 16:50:00 | Sensible | 13952.77 | 13741.21 | 1.0000 | 1.38376330 | 1.165774 | 22.51 | 15.77 | 0.00856876 | 44405.4 | 12.80 | 11.97 | 0.00850000 | 34322.2 | 0.49830042 | 6.70 | 13.37 | 6.67 | 0.000 | 13952.77 | 28.08 | 0.00881938 | 17.91 | 0.00000000 | 0.0000 | 21.11 | 0.00856876 | 21.11 | 0.00856876 | 54.1853 | 11737.27 | 0.00 | 14141.03 | 13685.41 | 1.38376330 | 22.51 | 15.91 | 0.00856876 | 44405.4 | 12.82 | 12.05 | 0.00843835 | 34186.1 | |
ROOM_2_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5264.816 | 5264.816 | 0.230269 | 0.00004606 | 150.455 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.165774 | 1.38376330 | 4197.9300 | 999.8980 | 3.93272529 | 54.44 | 82.22 | 27.78 | 458628.51 | 1.1479 | 1.171051 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 5264.82 | 5264.82 | 1.0000 | 0.27332711 | 0.230269 | 21.11 | 14.28 | 0.00748564 | 40227.5 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.04605421 | 60.00 | 32.22 | 27.78 | 0.000 | 5264.82 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.11 | 0.00748564 | 21.11 | 0.00748564 | 47.4182 | 5264.94 | 0.00 | 5675.60 | 5675.60 | 0.27332711 | 16.60 | 12.65 | 0.00748564 | 35632.5 | 36.98 | 19.89 | 0.00748564 | 56397.3 | |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 108138.694 | -999.000 | 9.184683 | 0.00386239 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6485 | 1004.8586 | 1.1870 | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 9.184683 | 10.90213406 | 4197.9300 | 999.8980 | 30.26067582 | 13.37 | 6.70 | 6.67 | 847304.77 | 12.7627 | 12.762430 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | unknown | unknown | unknown | 8/21 13:30:00 | Sensible | 108138.69 | 108042.45 | 1.0000 | 10.90213406 | 9.184683 | 22.51 | 15.71 | 0.00850398 | 44241.2 | 12.80 | 11.97 | 0.00850000 | 34322.2 | 3.86199746 | 6.70 | 13.37 | 6.67 | 0.000 | 108138.69 | 29.14 | 0.00882108 | 18.26 | 0.00000000 | 0.0000 | 21.11 | 0.00850398 | 21.11 | 0.00850398 | 53.7800 | 92477.70 | 0.00 | 109610.00 | 107550.23 | 10.90213406 | 22.51 | 15.86 | 0.00850398 | 44241.2 | 12.84 | 12.05 | 0.00842915 | 34187.2 | |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 30250.932 | 30250.932 | 1.323118 | 0.00026465 | 864.479 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 9.184683 | 10.90213406 | 4197.9300 | 999.8980 | 3.93272529 | 54.44 | 82.22 | 27.78 | 458628.51 | 6.5960 | 6.728702 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 30250.93 | 30250.93 | 1.0000 | 1.57052889 | 1.323118 | 21.11 | 14.31 | 0.00752181 | 40319.7 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.26462135 | 60.00 | 32.22 | 27.78 | 0.000 | 30250.93 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.11 | 0.00752181 | 21.11 | 0.00752181 | 47.6436 | 30251.28 | 0.00 | 32611.44 | 32611.44 | 1.57052889 | 16.60 | 12.68 | 0.00752181 | 35724.0 | 36.98 | 19.91 | 0.00752181 | 56488.7 | |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 75503.163 | -999.000 | 6.050996 | 0.00269675 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.0830 | 1004.8586 | 1.1870 | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 6.050996 | 7.18247659 | 4197.9300 | 999.8980 | 30.26067582 | 13.37 | 6.70 | 6.67 | 847304.77 | 8.9110 | 8.910814 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | unknown | unknown | unknown | 8/21 15:00:00 | Sensible | 75503.16 | 71687.15 | 1.0000 | 7.18247659 | 6.050996 | 22.51 | 15.92 | 0.00873772 | 44834.3 | 12.80 | 11.97 | 0.00850000 | 34322.2 | 2.69647257 | 6.70 | 13.37 | 6.67 | 0.000 | 75503.16 | 29.40 | 0.00882150 | 18.34 | 0.00000000 | 0.0000 | 21.11 | 0.00873772 | 21.11 | 0.00873772 | 55.2398 | 60920.91 | 0.00 | 76500.51 | 71483.66 | 7.18247659 | 22.51 | 16.06 | 0.00873772 | 44834.3 | 12.76 | 12.04 | 0.00846105 | 34183.3 | |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 30331.957 | 30331.957 | 1.326662 | 0.00026536 | 866.794 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 6.050996 | 7.18247659 | 4197.9300 | 999.8980 | 3.93272529 | 54.44 | 82.22 | 27.78 | 458628.51 | 6.6136 | 6.746724 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 30331.96 | 30331.96 | 1.0000 | 1.57473547 | 1.326662 | 21.11 | 14.32 | 0.00752285 | 40322.3 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.26533012 | 60.00 | 32.22 | 27.78 | 0.000 | 30331.96 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.11 | 0.00752285 | 21.11 | 0.00752285 | 47.6502 | 30332.31 | 0.00 | 32698.79 | 32698.79 | 1.57473547 | 16.60 | 12.68 | 0.00752285 | 35726.7 | 36.98 | 19.91 | 0.00752285 | 56491.3 | |
ROOM_5_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 13870.500 | -999.000 | 1.158687 | 0.00049541 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7703 | 1004.8586 | 1.1870 | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.158687 | 1.37535058 | 4197.9300 | 999.8980 | 30.26067582 | 13.37 | 6.70 | 6.67 | 847304.77 | 1.6370 | 1.636984 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | unknown | unknown | unknown | 8/21 10:00:00 | Sensible | 13870.50 | 13657.99 | 1.0000 | 1.37535058 | 1.158687 | 22.51 | 15.77 | 0.00856949 | 44407.3 | 12.80 | 11.97 | 0.00850000 | 34322.2 | 0.49536234 | 6.70 | 13.37 | 6.67 | 0.000 | 13870.50 | 25.45 | 0.00881519 | 17.01 | 0.00000000 | 0.0000 | 21.11 | 0.00856949 | 21.11 | 0.00856949 | 54.1899 | 11665.92 | 0.00 | 14057.63 | 13602.60 | 1.37535058 | 22.51 | 15.92 | 0.00856949 | 44407.3 | 12.82 | 12.05 | 0.00843845 | 34186.1 | |
ROOM_5_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5268.987 | 5268.987 | 0.230451 | 0.00004610 | 150.574 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.158687 | 1.37535058 | 4197.9300 | 999.8980 | 3.93272529 | 54.44 | 82.22 | 27.78 | 458628.51 | 1.1489 | 1.171979 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 5268.99 | 5268.99 | 1.0000 | 0.27354366 | 0.230451 | 21.11 | 14.28 | 0.00748597 | 40228.3 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.04609070 | 60.00 | 32.22 | 27.78 | 0.000 | 5268.99 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.11 | 0.00748597 | 21.11 | 0.00748597 | 47.4203 | 5269.11 | 0.00 | 5680.10 | 5680.10 | 0.27354366 | 16.60 | 12.65 | 0.00748597 | 35633.3 | 36.98 | 19.89 | 0.00748597 | 56398.2 | |
ROOM_6_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12679.524 | -999.000 | 1.057468 | 0.00045287 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7823 | 1004.8586 | 1.1870 | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.057468 | 1.25520525 | 4197.9300 | 999.8980 | 30.26067582 | 13.37 | 6.70 | 6.67 | 847304.77 | 1.4965 | 1.496426 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | unknown | unknown | unknown | 8/21 09:00:00 | Sensible | 12679.52 | 12467.41 | 1.0000 | 1.25520525 | 1.057468 | 22.51 | 15.78 | 0.00857598 | 44423.8 | 12.80 | 11.97 | 0.00850000 | 34322.2 | 0.45282857 | 6.70 | 13.37 | 6.67 | 0.000 | 12679.52 | 23.68 | 0.00881240 | 16.40 | 0.00000000 | 0.0000 | 21.11 | 0.00857598 | 21.11 | 0.00857598 | 54.2304 | 10646.82 | 0.00 | 12850.44 | 12417.46 | 1.25520525 | 22.51 | 15.92 | 0.00857598 | 44423.8 | 12.82 | 12.05 | 0.00843935 | 34186.0 | |
ROOM_6_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5272.507 | 5272.507 | 0.230605 | 0.00004613 | 150.675 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.057468 | 1.25520525 | 4197.9300 | 999.8980 | 3.93272529 | 54.44 | 82.22 | 27.78 | 458628.51 | 1.1496 | 1.172762 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 5272.51 | 5272.51 | 1.0000 | 0.27372640 | 0.230605 | 21.11 | 14.28 | 0.00748632 | 40229.2 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.04612149 | 60.00 | 32.22 | 27.78 | 0.000 | 5272.51 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.11 | 0.00748632 | 21.11 | 0.00748632 | 47.4225 | 5272.63 | 0.00 | 5683.89 | 5683.89 | 0.27372640 | 16.60 | 12.65 | 0.00748632 | 35634.2 | 36.98 | 19.89 | 0.00748632 | 56399.1 | |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | CORRIDOR_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 14846.527 | 14846.527 | 1.285163 | 0.00012988 | 330.621 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.93272529 | 54.44 | 82.22 | 27.78 | 458628.51 | 3.2372 | 3.302306 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 14846.53 | 14846.53 | 1.0000 | 1.52547632 | 1.285163 | 16.70 | 13.06 | 0.00800000 | 37036.7 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.12987064 | 60.00 | 32.22 | 27.78 | 0.000 | 14846.53 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.00 | 0.00758766 | 21.00 | 0.00758766 | 48.3840 | 8162.84 | 0.00 | 14927.10 | 14927.10 | 1.52547632 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 26.20 | 16.74 | 0.00800000 | 46719.9 | |
ROOM_1_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 4078.641 | -999.000 | 0.341617 | 0.00014568 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7507 | 1004.8586 | 1.1870 | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.341617 | 0.40549592 | 4197.9300 | 999.8980 | 30.26067582 | 13.37 | 6.70 | 6.67 | 847304.77 | 0.4814 | 0.481358 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | unknown | unknown | unknown | 8/21 16:30:00 | Sensible | 4078.64 | 4025.47 | 1.0000 | 0.40549592 | 0.341617 | 22.51 | 15.76 | 0.00855899 | 44380.6 | 12.80 | 11.97 | 0.00850000 | 34322.2 | 0.14566204 | 6.70 | 13.37 | 6.67 | 0.000 | 4078.64 | 28.36 | 0.00881983 | 18.00 | 0.00000000 | 0.0000 | 21.11 | 0.00855899 | 21.11 | 0.00855899 | 54.1244 | 3439.48 | 0.00 | 4133.74 | 4008.83 | 0.40549592 | 22.51 | 15.91 | 0.00855899 | 44380.6 | 12.82 | 12.05 | 0.00843698 | 34186.3 | |
ROOM_1_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1644.478 | 1644.478 | 0.071925 | 0.00001439 | 46.992 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.341617 | 0.40549592 | 4197.9300 | 999.8980 | 3.93272529 | 54.44 | 82.22 | 27.78 | 458628.51 | 0.3586 | 0.365781 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 1644.48 | 1644.48 | 1.0000 | 0.08537439 | 0.071925 | 21.11 | 14.37 | 0.00758009 | 40467.4 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.01438515 | 60.00 | 32.22 | 27.78 | 0.000 | 1644.48 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.11 | 0.00758009 | 21.11 | 0.00758009 | 48.0094 | 1644.52 | 0.00 | 1772.79 | 1772.79 | 0.08537439 | 16.60 | 12.74 | 0.00758009 | 35871.6 | 36.98 | 19.96 | 0.00758009 | 56636.5 | |
ROOM_2_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3673.731 | -999.000 | 0.307209 | 0.00013121 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7626 | 1004.8586 | 1.1870 | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.307209 | 0.36465437 | 4197.9300 | 999.8980 | 30.26067582 | 13.37 | 6.70 | 6.67 | 847304.77 | 0.4336 | 0.433570 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 16:50:00 | unknown | unknown | unknown | 8/21 16:50:00 | Sensible | 3673.73 | 3620.75 | 1.0000 | 0.36465437 | 0.307209 | 22.51 | 15.77 | 0.00856535 | 44396.8 | 12.80 | 11.97 | 0.00850000 | 34322.2 | 0.13120131 | 6.70 | 13.37 | 6.67 | 0.000 | 3673.73 | 28.08 | 0.00881938 | 17.91 | 0.00000000 | 0.0000 | 21.11 | 0.00856535 | 21.11 | 0.00856535 | 54.1641 | 3093.05 | 0.00 | 3723.32 | 3605.95 | 0.36465437 | 22.51 | 15.91 | 0.00856535 | 44396.8 | 12.82 | 12.05 | 0.00843787 | 34186.2 | |
ROOM_2_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1646.289 | 1646.289 | 0.072004 | 0.00001440 | 47.044 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.307209 | 0.36465437 | 4197.9300 | 999.8980 | 3.93272529 | 54.44 | 82.22 | 27.78 | 458628.51 | 0.3590 | 0.366183 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 1646.29 | 1646.29 | 1.0000 | 0.08546840 | 0.072004 | 21.11 | 14.37 | 0.00758055 | 40468.5 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.01440099 | 60.00 | 32.22 | 27.78 | 0.000 | 1646.29 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.11 | 0.00758055 | 21.11 | 0.00758055 | 48.0122 | 1646.33 | 0.00 | 1774.74 | 1774.74 | 0.08546840 | 16.60 | 12.74 | 0.00758055 | 35872.8 | 36.98 | 19.96 | 0.00758055 | 56637.6 | |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 22403.043 | -999.000 | 1.860033 | 0.00080017 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8157 | 1004.8586 | 1.1870 | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.860033 | 2.20784215 | 4197.9300 | 999.8980 | 30.26067582 | 13.37 | 6.70 | 6.67 | 847304.77 | 2.6440 | 2.643987 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | unknown | unknown | unknown | 8/21 13:40:00 | Sensible | 22403.04 | 21941.43 | 1.0000 | 2.20784215 | 1.860033 | 22.51 | 15.79 | 0.00859396 | 44469.2 | 12.80 | 11.97 | 0.00850000 | 34322.2 | 0.80008823 | 6.70 | 13.37 | 6.67 | 0.000 | 22403.04 | 29.23 | 0.00882122 | 18.29 | 0.00000000 | 0.0000 | 21.11 | 0.00859396 | 21.11 | 0.00859396 | 54.3431 | 18726.83 | 0.00 | 22704.35 | 21856.46 | 2.20784215 | 22.51 | 15.94 | 0.00859396 | 44469.2 | 12.81 | 12.05 | 0.00844185 | 34185.7 | |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7921.492 | 7921.492 | 0.346467 | 0.00006930 | 226.361 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.860033 | 2.20784215 | 4197.9300 | 999.8980 | 3.93272529 | 54.44 | 82.22 | 27.78 | 458628.51 | 1.7272 | 1.761974 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 7921.49 | 7921.49 | 1.0000 | 0.41125300 | 0.346467 | 21.11 | 14.38 | 0.00759720 | 40510.9 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.06929359 | 60.00 | 32.22 | 27.78 | 0.000 | 7921.49 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.11 | 0.00759720 | 21.11 | 0.00759720 | 48.1160 | 7921.64 | 0.00 | 8539.58 | 8539.58 | 0.41125300 | 16.60 | 12.76 | 0.00759720 | 35914.9 | 36.98 | 19.97 | 0.00759720 | 56679.7 | |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | BANQUET_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 16879.027 | 16879.027 | 2.194030 | 0.00014767 | 360.951 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.93272529 | 54.44 | 82.22 | 27.78 | 458628.51 | 3.6803 | 3.754395 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 16879.03 | 16879.03 | 1.0000 | 2.60429286 | 2.194030 | 16.70 | 13.06 | 0.00800000 | 37036.7 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.14765003 | 60.00 | 32.22 | 27.78 | 0.000 | 16879.03 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.00 | 0.00768322 | 21.00 | 0.00768322 | 48.9862 | 5466.95 | 0.00 | 16973.08 | 16973.08 | 2.60429286 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 22.99 | 15.59 | 0.00800000 | 43452.1 | |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | DINING_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 17540.148 | 17540.148 | 2.301469 | 0.00015345 | 374.812 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.93272529 | 54.44 | 82.22 | 27.78 | 458628.51 | 3.8245 | 3.901448 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 19:20:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 19:20:00 | Sensible | 17540.15 | 17540.15 | 1.0000 | 2.73182275 | 2.301469 | 16.70 | 13.06 | 0.00800000 | 37036.7 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.15343321 | 60.00 | 32.22 | 27.78 | 0.000 | 17540.15 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.00 | 0.00768868 | 21.00 | 0.00768868 | 49.0210 | 5569.46 | 0.00 | 17637.91 | 17637.91 | 2.73182275 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 22.93 | 15.57 | 0.00800000 | 43391.2 | |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | KITCHEN_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12866.461 | 12866.461 | 2.315184 | 0.00011256 | 269.254 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.93272529 | 54.44 | 82.22 | 27.78 | 458628.51 | 2.8054 | 2.861881 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | Sensible | 12866.46 | 12866.46 | 1.0000 | 2.74810236 | 2.315184 | 16.70 | 13.06 | 0.00800000 | 37036.7 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.11254993 | 60.00 | 32.22 | 27.78 | 0.000 | 12866.46 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 19.65 | 0.00461594 | 21.00 | 0.00461594 | 29.5816 | 903.02 | 0.00 | 12938.68 | 12938.68 | 2.74810236 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 21.22 | 14.93 | 0.00800000 | 41643.0 | |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | CORRIDOR_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9755.857 | 9755.857 | 0.763260 | 0.00008535 | 220.183 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.93272529 | 54.44 | 82.22 | 27.78 | 458628.51 | 2.1272 | 2.169991 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 19:20:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 19:20:00 | Sensible | 9755.86 | 9755.86 | 1.0000 | 0.90598268 | 0.763260 | 16.70 | 13.06 | 0.00800000 | 37036.7 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.08533978 | 60.00 | 32.22 | 27.78 | 0.000 | 9755.86 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.00 | 0.00773497 | 21.00 | 0.00773497 | 49.3122 | 5785.47 | 0.00 | 9808.53 | 9808.53 | 0.90598268 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 27.22 | 17.09 | 0.00800000 | 47761.1 | |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 532172.511 | -999.000 | 22.815202 | 0.01900797 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.2387 | 1004.8586 | 1.1870 | VAV WITH REHEAT FAN | Fan:VariableVolume | 22.815202 | 27.08143505 | 4197.9300 | 999.8980 | 30.26067582 | 13.37 | 6.70 | 6.67 | 847304.77 | 62.8077 | 62.807685 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | Sensible | 532172.51 | 509413.61 | 1.0000 | 27.08143505 | 22.815202 | 29.40 | 18.34 | 0.00882150 | 52086.5 | 10.95 | 10.95 | 0.00850000 | 32435.6 | 19.00603003 | 6.70 | 13.37 | 6.67 | 51120.623 | 481051.89 | 29.40 | 0.00882150 | 18.34 | 22.81089000 | 99.9811 | 23.99 | 0.00960563 | 23.99 | 0.00960308 | 50.8910 | 309119.76 | 0.00 | 537523.92 | 490538.65 | 27.08143505 | 29.40 | 18.50 | 0.00882150 | 52086.5 | 11.66 | 11.25 | 0.00813374 | 32238.0 | |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 170625.589 | 170625.589 | 6.844561 | 0.00149271 | 2912.959 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | VAV WITH REHEAT FAN | Fan:VariableVolume | 22.815202 | 27.08143505 | 4197.9300 | 999.8980 | 3.93272529 | 54.44 | 82.22 | 27.78 | 458628.51 | 37.2034 | 37.952176 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 19:20:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 19:20:00 | Sensible | 170625.59 | 170625.59 | 1.0000 | 8.12443052 | 6.844561 | -4.20 | -4.20 | 0.00269032 | 2487.0 | 16.70 | 13.06 | 0.00800000 | 37036.7 | 1.49255482 | 60.00 | 32.22 | 27.78 | 0.000 | 170625.59 | -4.20 | 0.00269032 | -4.20 | 22.81089000 | 333.2703 | 18.45 | 0.00685804 | 21.36 | 0.00586588 | 36.6976 | 51613.00 | 0.00 | 157193.69 | 157193.69 | 8.12443052 | 2.80 | 0.07 | 0.00269032 | 9555.9 | 21.96 | 9.93 | 0.00269032 | 28904.2 | |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 45447.837 | -999.000 | 2.051317 | 0.00162329 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.2387 | 1004.8586 | 1.1870 | FLR_3_DOAS FAN | Fan:ConstantVolume | 2.051245 | 2.43480905 | 4197.9300 | 999.8980 | 30.26067582 | 13.37 | 6.70 | 6.67 | 847304.77 | 5.3638 | 5.363812 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | Sensible | 45447.84 | 43504.21 | 1.0000 | 2.43489466 | 2.051317 | 29.40 | 18.34 | 0.00882150 | 52086.5 | 11.92 | 11.61 | 0.00850000 | 33421.2 | 1.62312585 | 6.70 | 13.37 | 6.67 | 2195.006 | 43252.83 | 29.40 | 0.00882150 | 18.34 | 2.05124512 | 99.9965 | 21.11 | 0.00859547 | 21.11 | 0.00859780 | 54.3661 | 211782.54 | 0.00 | 45923.42 | 42707.30 | 2.43489466 | 29.40 | 18.50 | 0.00882150 | 52086.5 | 12.23 | 11.66 | 0.00829812 | 33225.9 | |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 15340.965 | 15340.965 | 0.615395 | 0.00013421 | 261.904 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | FLR_3_DOAS FAN | Fan:ConstantVolume | 2.051245 | 2.43480905 | 4197.9300 | 999.8980 | 3.93272529 | 54.44 | 82.22 | 27.78 | 458628.51 | 3.3450 | 3.412284 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 15340.96 | 15340.96 | 1.0000 | 0.73046840 | 0.615395 | -4.20 | -4.20 | 0.00269032 | 2487.0 | 16.70 | 13.06 | 0.00800000 | 37036.7 | 0.13419576 | 60.00 | 32.22 | 27.78 | 0.000 | 15340.96 | -4.20 | 0.00269032 | -4.20 | 2.05124512 | 333.3216 | 21.11 | 0.00752249 | 21.11 | 0.00752285 | 47.6501 | 92864.18 | 0.00 | 14133.30 | 14133.30 | 0.73046840 | 2.80 | 0.07 | 0.00269032 | 9555.9 | 21.96 | 9.93 | 0.00269032 | 28904.2 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:58:38
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
VAV WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 22.81 | 22.82 | - | |||
FLR_3_DOAS_OA_CONTROLLER | DifferentialDryBulb | 2.05 | 2.05 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
BASEMENT | VAV WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
RETAIL_1_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
RETAIL_2_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
MECH_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
STORAGE_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000610 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
LAUNDRY_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CAFE_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
LOBBY_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001448 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORRIDOR_FLR_3 | VAV WITH REHEAT_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
BANQUET_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
DINING_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
KITCHEN_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003556 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORRIDOR_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 19.17 | 8760.00 | 19.17 |
RETAIL_1_FLR_1 | 1263.17 | 8666.33 | 1233.50 |
RETAIL_2_FLR_1 | 6.83 | 8760.00 | 6.83 |
MECH_FLR_1 | 183.17 | 8760.00 | 183.17 |
STORAGE_FLR_1 | 451.83 | 8760.00 | 451.83 |
LAUNDRY_FLR_1 | 2799.50 | 4807.17 | 1150.83 |
CAFE_FLR_1 | 116.17 | 8650.83 | 84.50 |
LOBBY_FLR_1 | 0.00 | 8760.00 | 0.00 |
ROOM_1_FLR_3 | 1873.33 | 8409.50 | 1792.33 |
ROOM_2_FLR_3 | 2311.83 | 8582.33 | 2286.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 709.00 | 8760.00 | 709.00 |
ROOM_5_FLR_3 | 1782.00 | 8369.67 | 1770.83 |
ROOM_6_FLR_3 | 2231.67 | 8591.83 | 2226.83 |
CORRIDOR_FLR_3 | 272.17 | 8760.00 | 272.17 |
ROOM_1_FLR_6 | 2610.83 | 8245.00 | 2432.17 |
ROOM_2_FLR_6 | 2947.33 | 8457.50 | 2871.17 |
ROOM_3_MULT9_FLR_6 | 1433.17 | 8136.50 | 1254.50 |
BANQUET_FLR_6 | 27.83 | 8619.67 | 0.00 |
DINING_FLR_6 | 85.17 | 8401.50 | 0.00 |
KITCHEN_FLR_6 | 6535.83 | 6786.83 | 4945.17 |
CORRIDOR_FLR_6 | 643.83 | 8760.00 | 643.83 |
Facility | 7461.83 | 8760.00 | 6651.17 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 35.50 | 0.00 | 35.50 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.50 | 2.00 | 0.50 | 2.00 |
ROOM_2_FLR_3 | 2.17 | 1.17 | 2.17 | 1.17 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 1.33 | 0.67 | 1.33 | 0.67 |
ROOM_5_FLR_3 | 1.17 | 0.00 | 1.17 | 0.00 |
ROOM_6_FLR_3 | 2.83 | 0.00 | 2.83 | 0.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.17 | 6.33 | 0.17 | 6.33 |
ROOM_2_FLR_6 | 0.67 | 5.67 | 0.67 | 5.67 |
ROOM_3_MULT9_FLR_6 | 0.00 | 1.17 | 0.00 | 1.17 |
BANQUET_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 38.83 | 9.33 | 38.83 | 9.33 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:58:38
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.77 | 106.50 | 4826.41 | 1.902 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.28 | 10.83 | 265.76 | 6.574 | 0.137 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.27 | 12.54 | 307.76 | 2.839 | 0.046 | 0.000 | 0.000 |
MECH_FLR_1 | 1.54 | 2.65 | 650.80 | 1.284 | 0.051 | 0.000 | 0.000 |
STORAGE_FLR_1 | 1.18 | 2.04 | 375.47 | 1.102 | 0.051 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.87 | 8.40 | 309.22 | 38.689 | 0.147 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.53 | 142.30 | 748.35 | 9.154 | 0.108 | 0.000 | 0.000 |
LOBBY_FLR_1 | 245.01 | 422.44 | 5183.56 | 3.656 | 0.045 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.473 | 0.179 | 0.000 | 0.042 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.473 | 0.178 | 0.000 | 0.044 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.537 | 0.079 | 0.000 | 0.070 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.473 | 0.179 | 0.000 | 0.042 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.473 | 0.179 | 0.000 | 0.044 |
CORRIDOR_FLR_3 | 12.15 | 20.96 | 1186.91 | 0.985 | 0.022 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.473 | 0.179 | 0.000 | 0.049 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.473 | 0.179 | 0.000 | 0.052 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.538 | 0.145 | 0.000 | 0.079 |
BANQUET_FLR_6 | 144.94 | 249.90 | 1010.89 | 7.921 | 0.051 | 0.000 | 0.000 |
DINING_FLR_6 | 144.94 | 249.90 | 1010.89 | 8.310 | 0.051 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.90 | 22.24 | 314.87 | 26.983 | 0.148 | 0.000 | 0.000 |
CORRIDOR_FLR_6 | 12.86 | 22.18 | 1256.16 | 2.211 | 0.036 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.77 | 106.50 | 4826.41 | 1.851 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.28 | 10.83 | 265.76 | 6.393 | 0.003 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.27 | 12.54 | 307.76 | 2.763 | 0.001 | 0.000 | 0.000 |
MECH_FLR_1 | 1.54 | 2.65 | 650.80 | 1.251 | 0.001 | 0.000 | 0.000 |
STORAGE_FLR_1 | 1.18 | 2.04 | 375.47 | 1.073 | 0.001 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.87 | 8.40 | 309.22 | 37.613 | 0.003 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.53 | 142.30 | 748.35 | 8.908 | 0.002 | 0.000 | 0.000 |
LOBBY_FLR_1 | 245.01 | 422.44 | 5183.56 | 3.557 | 0.001 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.457 | 0.003 | 0.000 | 0.000 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.457 | 0.003 | 0.000 | 0.000 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.520 | 0.002 | 0.000 | 0.000 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.457 | 0.003 | 0.000 | 0.000 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.457 | 0.003 | 0.000 | 0.000 |
CORRIDOR_FLR_3 | 12.15 | 20.96 | 1186.91 | 0.959 | 0.000 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.457 | 0.003 | 0.000 | 0.000 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.457 | 0.003 | 0.000 | 0.000 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.520 | 0.003 | 0.000 | 0.000 |
BANQUET_FLR_6 | 144.94 | 249.90 | 1010.89 | 7.689 | 0.001 | 0.000 | 0.000 |
DINING_FLR_6 | 144.94 | 249.90 | 1010.89 | 8.066 | 0.001 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.90 | 22.24 | 314.87 | 26.132 | 0.003 | 0.000 | 0.000 |
CORRIDOR_FLR_6 | 12.86 | 22.18 | 1256.16 | 2.152 | 0.001 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:58:38
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | VAV WITH REHEAT | 61.77 | 106.50 | 4826.41 | 1978.83 | 0.0000 | 0.854 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | 6.28 | 10.83 | 265.76 | 67.07 | 0.0000 | 0.079 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | 7.27 | 12.54 | 307.76 | 77.67 | 0.0000 | 0.092 |
MECH_FLR_1 | VAV WITH REHEAT | 1.54 | 2.65 | 650.80 | 164.24 | 0.0000 | 0.000 |
STORAGE_FLR_1 | VAV WITH REHEAT | 1.18 | 2.04 | 375.47 | 94.76 | 0.0000 | 0.058 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | 4.87 | 8.40 | 309.22 | 78.04 | 0.0000 | 0.000 |
CAFE_FLR_1 | VAV WITH REHEAT | 82.53 | 142.30 | 748.35 | 188.86 | 0.0000 | 0.676 |
LOBBY_FLR_1 | VAV WITH REHEAT | 245.01 | 422.44 | 5183.56 | 1308.19 | 0.0000 | 1.894 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.062 |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.062 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 1.50 | 74.75 | 24.52 | 0.0000 | 0.837 | |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 74.77 | 24.53 | 0.0000 | 0.837 |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.062 |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.062 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | 12.15 | 20.96 | 1186.91 | 389.40 | 0.0000 | 0.475 |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.015 |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.015 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 74.77 | 24.53 | 0.0000 | 0.099 |
BANQUET_FLR_6 | VAV WITH REHEAT | 144.94 | 249.90 | 1010.89 | 331.66 | 0.0000 | 1.188 |
DINING_FLR_6 | VAV WITH REHEAT | 144.94 | 249.90 | 1010.89 | 331.66 | 0.0000 | 1.188 |
KITCHEN_FLR_6 | VAV WITH REHEAT | 12.90 | 22.24 | 314.87 | 103.30 | 0.0000 | 0.367 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | 12.86 | 22.18 | 1256.16 | 412.12 | 0.0000 | 0.126 |
Total Facility | 872.97 | 1604.23 | 35184.81 | 11345.29 | 0.0000 | 137.584 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 79524033.80 | 0.00 | 79524033.80 | 0.00 | 79524033.80 | 26946214.98 | 0.00 | 0.00 | 8760.00 | 0.00 |
RETAIL_1_FLR_1 | 15138666.16 | 0.00 | 15138666.16 | 316459.92 | 15455126.08 | 2498216.28 | 0.00 | 0.00 | 8760.00 | 0.00 |
RETAIL_2_FLR_1 | 7567066.14 | 0.00 | 7567066.14 | 122153.93 | 7689220.07 | 2892943.94 | 0.00 | 0.00 | 8760.00 | 0.00 |
MECH_FLR_1 | 7244386.64 | 0.00 | 7244386.64 | 288699.32 | 7533085.95 | 0.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
STORAGE_FLR_1 | 3585093.48 | 0.00 | 3585093.48 | 166563.60 | 3751657.09 | 1821682.01 | 0.00 | 0.00 | 8760.00 | 0.00 |
LAUNDRY_FLR_1 | 0.10E+09 | 0.00 | 0.10E+09 | 394204.17 | 0.10E+09 | 0.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
CAFE_FLR_1 | 59328066.17 | 0.00 | 59328066.17 | 699552.56 | 60027618.73 | 21330615.53 | 0.00 | 0.00 | 8760.00 | 0.00 |
LOBBY_FLR_1 | 0.16E+09 | 0.00 | 0.16E+09 | 1998781.45 | 0.17E+09 | 59728886.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
ROOM_1_FLR_3 | 1946875.62 | 43476.29 | 1990351.91 | 183682.98 | 2174034.89 | 1946875.62 | 0.00 | 8064.33 | 695.67 | 0.00 |
ROOM_2_FLR_3 | 1946647.51 | 45603.71 | 1992251.22 | 183668.97 | 2175920.19 | 1946647.51 | 0.00 | 8064.33 | 695.67 | 0.00 |
ROOM_3_MULT19_FLR_3 | 26397887.27 | 47791.30 | 26445678.57 | 51249.61 | 26496928.19 | 26397887.27 | 0.00 | 8081.00 | 679.00 | 8760.00 |
ROOM_4_MULT19_FLR_3 | 26405105.73 | 45277.54 | 26450383.27 | 51263.63 | 26501646.90 | 26405105.73 | 0.00 | 8082.07 | 677.93 | 0.00 |
ROOM_5_FLR_3 | 1946875.62 | 43442.54 | 1990318.16 | 183682.98 | 2174001.14 | 1946875.62 | 0.00 | 8064.33 | 695.67 | 0.00 |
ROOM_6_FLR_3 | 1946647.51 | 45523.13 | 1992170.64 | 183668.97 | 2175839.61 | 1946647.51 | 0.00 | 8064.33 | 695.67 | 0.00 |
CORRIDOR_FLR_3 | 40518087.21 | 0.00 | 40518087.21 | 222109.68 | 40740196.89 | 14972100.18 | 0.00 | 0.00 | 8760.00 | 0.00 |
ROOM_1_FLR_6 | 486718.90 | 50818.03 | 537536.93 | 183721.42 | 721258.35 | 486718.90 | 0.00 | 8062.67 | 697.33 | 0.00 |
ROOM_2_FLR_6 | 486661.88 | 53768.38 | 540430.26 | 183707.41 | 724137.67 | 486661.88 | 0.00 | 8062.67 | 697.33 | 0.00 |
ROOM_3_MULT9_FLR_6 | 3126920.42 | 50728.36 | 3177648.78 | 93998.31 | 3271647.09 | 3126920.42 | 0.00 | 8062.83 | 697.17 | 0.00 |
BANQUET_FLR_6 | 69172470.11 | 0.00 | 69172470.11 | 448601.54 | 69621071.65 | 37458366.31 | 0.00 | 0.00 | 8760.00 | 0.00 |
DINING_FLR_6 | 72559784.09 | 0.00 | 72559784.09 | 448601.54 | 73008385.63 | 37458366.31 | 0.00 | 0.00 | 8760.00 | 0.00 |
KITCHEN_FLR_6 | 73058955.38 | 0.00 | 73058955.38 | 401602.39 | 73460557.77 | 11584760.86 | 0.00 | 0.00 | 8760.00 | 0.00 |
CORRIDOR_FLR_6 | 24063753.00 | 0.00 | 24063753.00 | 393066.01 | 24456819.01 | 3961413.96 | 0.00 | 0.00 | 8760.00 | 0.00 |
Total Facility | 0.49E+10 | 8346556.45 | 0.49E+10 | 18509960.64 | 0.49E+10 | 0.43E+10 | 0.00 | 8095.83 | 8760.00 | 8760.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 2.5217 | 0.0000 | 2.5217 | 0.0000 | 2.5217 | 0.8545 | 0.00 | 0.00 | 8760.00 |
RETAIL_1_FLR_1 | 0.4800 | 0.0000 | 0.4800 | 0.0100 | 0.4901 | 0.0792 | 0.00 | 0.00 | 8760.00 |
RETAIL_2_FLR_1 | 0.2400 | 0.0000 | 0.2400 | 0.0039 | 0.2438 | 0.0917 | 0.00 | 0.00 | 8760.00 |
MECH_FLR_1 | 0.2297 | 0.0000 | 0.2297 | 0.0092 | 0.2389 | 0.0000 | 0.00 | 0.00 | 8760.00 |
STORAGE_FLR_1 | 0.1137 | 0.0000 | 0.1137 | 0.0053 | 0.1190 | 0.0578 | 0.00 | 0.00 | 8760.00 |
LAUNDRY_FLR_1 | 3.2835 | 0.0000 | 3.2835 | 0.0125 | 3.2960 | 0.0000 | 0.00 | 0.00 | 8760.00 |
CAFE_FLR_1 | 1.8813 | 0.0000 | 1.8813 | 0.0222 | 1.9035 | 0.6764 | 0.00 | 0.00 | 8760.00 |
LOBBY_FLR_1 | 5.2034 | 0.0000 | 5.2034 | 0.0634 | 5.2667 | 1.8940 | 0.00 | 0.00 | 8760.00 |
ROOM_1_FLR_3 | 0.0617 | 0.0014 | 0.0631 | 0.0058 | 0.0689 | 0.0617 | 0.00 | 8064.33 | 695.67 |
ROOM_2_FLR_3 | 0.0617 | 0.0014 | 0.0632 | 0.0058 | 0.0690 | 0.0617 | 0.00 | 8064.33 | 695.67 |
ROOM_4_MULT19_FLR_3 | 0.8373 | 0.0014 | 0.8387 | 0.0016 | 0.8404 | 0.8373 | 0.00 | 8082.07 | 677.93 |
ROOM_5_FLR_3 | 0.0617 | 0.0014 | 0.0631 | 0.0058 | 0.0689 | 0.0617 | 0.00 | 8064.33 | 695.67 |
ROOM_6_FLR_3 | 0.0617 | 0.0014 | 0.0632 | 0.0058 | 0.0690 | 0.0617 | 0.00 | 8064.33 | 695.67 |
CORRIDOR_FLR_3 | 1.2848 | 0.0000 | 1.2848 | 0.0070 | 1.2919 | 0.4748 | 0.00 | 0.00 | 8760.00 |
ROOM_1_FLR_6 | 0.0154 | 0.0016 | 0.0170 | 0.0058 | 0.0229 | 0.0154 | 0.00 | 8062.67 | 697.33 |
ROOM_2_FLR_6 | 0.0154 | 0.0017 | 0.0171 | 0.0058 | 0.0230 | 0.0154 | 0.00 | 8062.67 | 697.33 |
ROOM_3_MULT9_FLR_6 | 0.0992 | 0.0016 | 0.1008 | 0.0030 | 0.1037 | 0.0992 | 0.00 | 8062.83 | 697.17 |
BANQUET_FLR_6 | 2.1934 | 0.0000 | 2.1934 | 0.0142 | 2.2077 | 1.1878 | 0.00 | 0.00 | 8760.00 |
DINING_FLR_6 | 2.3009 | 0.0000 | 2.3009 | 0.0142 | 2.3151 | 1.1878 | 0.00 | 0.00 | 8760.00 |
KITCHEN_FLR_6 | 2.3167 | 0.0000 | 2.3167 | 0.0127 | 2.3294 | 0.3674 | 0.00 | 0.00 | 8760.00 |
CORRIDOR_FLR_6 | 0.7631 | 0.0000 | 0.7631 | 0.0125 | 0.7755 | 0.1256 | 0.00 | 0.00 | 8760.00 |
Total Facility | 92.2123 | 0.1495 | 92.3618 | 0.4634 | 92.8252 | 73.9670 | 0.00 | 8095.83 | 8760.00 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV WITH REHEAT | 0.10E+10 | 0.00 | 0.10E+10 | 0.22E+09 | 0.00 | 0.00 | 8760.00 | 0.00 |
FLR_3_DOAS | 91145268.87 | 426429.28 | 91571698.15 | 64690340.46 | 0.00 | 0.00 | 8760.00 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV WITH REHEAT | 32.1410 | 0.0000 | 32.1410 | 6.9969 | 0.00 | 0.00 | 8760.00 |
FLR_3_DOAS | 2.8902 | 0.0135 | 2.9037 | 2.0513 | 0.00 | 0.00 | 8760.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV WITH REHEAT | 0.00 | 7330.89 | 1395.02 | 0.00 | 34.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FLR_3_DOAS | 0.00 | 7286.96 | 1473.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV WITH REHEAT | 0.0000 | 32.1441 | 32.1459 | 0.0000 | 32.2139 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
FLR_3_DOAS | 0.0000 | 2.8906 | 2.8903 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:58:38
Surfaces by ClassTotal | Outdoors | |
Wall | 119 | 44 |
Floor | 25 | 0 |
Roof | 33 | 11 |
Internal Mass | 22 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 30 | 30 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 22 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 1304 |
Defaulted Fields | 1181 |
Fields with Defaults | 3925 |
Autosized Fields | 349 |
Autosizable Fields | 401 |
Autocalculated Fields | 280 |
Autocalculatable Fields | 539 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:58:38
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 7135.14 | 128567.79 | 29-JUL-05:00 | 506147.55 | 10-AUG-18:10 |
Electricity:Building | 2943.68 | 36656.90 | 02-JAN-02:10 | 182730.36 | 02-JAN-20:10 |
Electricity:Zone:BASEMENT | 315.54 | 3631.19 | 02-JAN-02:10 | 23630.80 | 02-JAN-20:10 |
Electricity:SpaceType:GENERAL | 2925.41 | 36182.64 | 02-JAN-02:10 | 182063.43 | 02-JAN-20:10 |
InteriorLights:Electricity | 1174.11 | 10291.59 | 02-JAN-02:10 | 93091.76 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BASEMENT | 165.29 | 1501.97 | 02-JAN-02:10 | 13517.00 | 02-JAN-20:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 1174.11 | 10291.59 | 02-JAN-02:10 | 93091.76 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity | 1174.11 | 10291.59 | 02-JAN-02:10 | 93091.76 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 165.29 | 1501.97 | 02-JAN-02:10 | 13517.00 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 1174.11 | 10291.59 | 02-JAN-02:10 | 93091.76 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_1_FLR_1 | 18.59 | 220.70 | 02-JAN-02:10 | 1372.90 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 8.40 | 76.37 | 02-JAN-02:10 | 687.30 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 8.40 | 76.37 | 02-JAN-02:10 | 687.30 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_2_FLR_1 | 21.53 | 255.58 | 02-JAN-02:10 | 1589.82 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 9.73 | 88.43 | 02-JAN-02:10 | 795.89 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 9.73 | 88.43 | 02-JAN-02:10 | 795.89 | 02-JAN-20:10 |
Electricity:Zone:MECH_FLR_1 | 30.66 | 342.02 | 02-JAN-02:10 | 2327.13 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:MECH_FLR_1 | 18.19 | 165.30 | 02-JAN-02:10 | 1487.69 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:MECH_FLR_1 | 18.19 | 165.30 | 02-JAN-02:10 | 1487.69 | 02-JAN-20:10 |
Electricity:Zone:STORAGE_FLR_1 | 6.94 | 81.32 | 02-JAN-02:10 | 515.26 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 3.34 | 30.34 | 02-JAN-02:10 | 273.10 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 3.34 | 30.34 | 02-JAN-02:10 | 273.10 | 02-JAN-20:10 |
Electricity:Zone:LAUNDRY_FLR_1 | 72.06 | 1000.18 | 02-JAN-02:10 | 4910.17 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 4.13 | 37.49 | 02-JAN-02:10 | 337.37 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 4.13 | 37.49 | 02-JAN-02:10 | 337.37 | 02-JAN-20:10 |
Electricity:Zone:CAFE_FLR_1 | 40.96 | 445.13 | 02-JAN-02:10 | 3142.50 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CAFE_FLR_1 | 26.62 | 241.91 | 02-JAN-02:10 | 2177.23 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CAFE_FLR_1 | 26.62 | 241.91 | 02-JAN-02:10 | 2177.23 | 02-JAN-20:10 |
Electricity:Zone:LOBBY_FLR_1 | 293.89 | 3428.00 | 02-JAN-02:10 | 21878.53 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 144.90 | 1316.59 | 02-JAN-02:10 | 11849.32 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 144.90 | 1316.59 | 02-JAN-02:10 | 11849.32 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_3 | 32.70 | 383.52 | 01-JAN-02:10 | 2308.42 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 20.41 | 172.80 | 01-JAN-02:10 | 1570.91 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 20.41 | 172.80 | 01-JAN-02:10 | 1570.91 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_3 | 32.70 | 383.47 | 01-JAN-02:10 | 2308.15 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 20.41 | 172.78 | 01-JAN-02:10 | 1570.72 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 20.41 | 172.78 | 01-JAN-02:10 | 1570.72 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT19_FLR_3 | 472.46 | 5984.83 | 01-JAN-02:10 | 32482.97 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 243.71 | 2063.36 | 01-JAN-02:10 | 18757.86 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 243.71 | 2063.36 | 01-JAN-02:10 | 18757.86 | 01-JAN-19:10 |
Electricity:Zone:ROOM_4_MULT19_FLR_3 | 472.59 | 5986.46 | 01-JAN-02:10 | 32491.86 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 243.77 | 2063.93 | 01-JAN-02:10 | 18762.99 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 243.77 | 2063.93 | 01-JAN-02:10 | 18762.99 | 01-JAN-19:10 |
Electricity:Zone:ROOM_5_FLR_3 | 32.70 | 383.52 | 01-JAN-02:10 | 2308.42 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 20.41 | 172.80 | 01-JAN-02:10 | 1570.91 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 20.41 | 172.80 | 01-JAN-02:10 | 1570.91 | 01-JAN-19:10 |
Electricity:Zone:ROOM_6_FLR_3 | 32.70 | 383.47 | 01-JAN-02:10 | 2308.15 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 20.41 | 172.78 | 01-JAN-02:10 | 1570.72 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 20.41 | 172.78 | 01-JAN-02:10 | 1570.72 | 01-JAN-19:10 |
Electricity:Zone:CORRIDOR_FLR_3 | 62.74 | 570.05 | 02-JAN-02:10 | 5130.41 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 62.74 | 570.05 | 02-JAN-02:10 | 5130.41 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 62.74 | 570.05 | 02-JAN-02:10 | 5130.41 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_6 | 8.18 | 95.88 | 01-JAN-02:10 | 577.11 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 5.10 | 43.20 | 01-JAN-02:10 | 392.73 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 5.10 | 43.20 | 01-JAN-02:10 | 392.73 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_6 | 8.17 | 95.87 | 01-JAN-02:10 | 577.04 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 5.10 | 43.19 | 01-JAN-02:10 | 392.68 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 5.10 | 43.19 | 01-JAN-02:10 | 392.68 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT9_FLR_6 | 55.96 | 708.92 | 01-JAN-02:10 | 3847.72 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 28.87 | 244.41 | 01-JAN-02:10 | 2221.93 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 28.87 | 244.41 | 01-JAN-02:10 | 2221.93 | 01-JAN-19:10 |
Electricity:Zone:BANQUET_FLR_6 | 222.61 | 2674.12 | 02-JAN-02:10 | 10571.30 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 46.75 | 424.82 | 02-JAN-02:10 | 3823.39 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 46.75 | 424.82 | 02-JAN-02:10 | 3823.39 | 02-JAN-20:10 |
Electricity:Zone:DINING_FLR_6 | 222.61 | 2674.12 | 02-JAN-02:10 | 10571.30 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:DINING_FLR_6 | 46.75 | 424.82 | 02-JAN-02:10 | 3823.39 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:DINING_FLR_6 | 46.75 | 424.82 | 02-JAN-02:10 | 3823.39 | 02-JAN-20:10 |
Electricity:Zone:KITCHEN_FLR_6 | 470.78 | 6777.71 | 02-JAN-02:10 | 19298.76 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 12.48 | 113.42 | 02-JAN-02:10 | 1020.78 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 12.48 | 113.42 | 02-JAN-02:10 | 1020.78 | 02-JAN-20:10 |
Electricity:Zone:CORRIDOR_FLR_6 | 16.60 | 150.83 | 02-JAN-02:10 | 1357.44 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 16.60 | 150.83 | 02-JAN-02:10 | 1357.44 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 16.60 | 150.83 | 02-JAN-02:10 | 1357.44 | 02-JAN-20:10 |
InteriorEquipment:Electricity | 1751.30 | 25891.05 | 02-JAN-02:10 | 89674.66 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 150.26 | 2129.22 | 02-JAN-02:10 | 10113.80 | 02-JAN-20:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 1751.30 | 25891.05 | 02-JAN-02:10 | 89674.66 | 02-JAN-07:10 |
MiscPlug:InteriorEquipment:Electricity | 959.56 | 15202.41 | 02-JAN-02:10 | 59492.27 | 02-JAN-07:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 150.26 | 2129.22 | 02-JAN-02:10 | 10113.80 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 959.56 | 15202.41 | 02-JAN-02:10 | 59492.27 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.79 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.79 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 12.29 | 210.72 | 01-JAN-00:10 | 948.23 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 12.29 | 210.72 | 01-JAN-00:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 12.29 | 210.69 | 01-JAN-00:10 | 948.12 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 12.29 | 210.69 | 01-JAN-00:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 228.75 | 3921.46 | 01-JAN-00:10 | 17646.57 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 228.75 | 3921.46 | 01-JAN-00:10 | 17646.57 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 228.82 | 3922.53 | 01-JAN-00:10 | 17651.40 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 228.82 | 3922.53 | 01-JAN-00:10 | 17651.40 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 12.29 | 210.72 | 01-JAN-00:10 | 948.23 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 12.29 | 210.72 | 01-JAN-00:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 12.29 | 210.69 | 01-JAN-00:10 | 948.12 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 12.29 | 210.69 | 01-JAN-00:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 3.07 | 52.68 | 01-JAN-00:10 | 237.06 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 3.07 | 52.68 | 01-JAN-00:10 | 237.06 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 3.07 | 52.67 | 01-JAN-00:10 | 237.03 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 3.07 | 52.67 | 01-JAN-00:10 | 237.03 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 27.10 | 464.51 | 01-JAN-00:10 | 2090.30 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 27.10 | 464.51 | 01-JAN-00:10 | 2090.30 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 440.03 | 6190.03 | 01-JAN-00:10 | 16686.59 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 410.33 | 5248.28 | 01-JAN-00:10 | 15744.84 | 01-JAN-07:10 |
ReachInFreezer:InteriorEquipment:Electricity | 16.27 | 515.92 | 01-JAN-00:10 | 515.92 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 16.27 | 515.92 | 01-JAN-00:10 | 515.92 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 16.27 | 515.92 | 01-JAN-00:10 | 515.92 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 13.43 | 425.83 | 01-JAN-00:10 | 425.83 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 13.43 | 425.83 | 01-JAN-00:10 | 425.83 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 13.43 | 425.83 | 01-JAN-00:10 | 425.83 | 01-JAN-00:10 |
Refrigeration:Electricity | 74.45 | 1243.43 | 11-FEB-23:30 | 3649.20 | 04-AUG-07:00 |
Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 18.27 | 261.51 | 02-JAN-11:30 | 2271.91 | 01-JAN-11:10 |
General:Refrigeration:Electricity | 18.27 | 261.51 | 02-JAN-11:30 | 2271.91 | 01-JAN-11:10 |
General:Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 18.27 | 261.51 | 02-JAN-11:30 | 2271.91 | 01-JAN-11:10 |
Electricity:Plant | 1029.79 | 2912.41 | 20-APR-00:30 | 218827.95 | 10-AUG-18:10 |
LowTempRefrigeration:Refrigeration:Electricity | 22.39 | 0.00 | 01-JAN-11:10 | 1897.88 | 12-MAY-10:40 |
MedTempRefrigeration:Refrigeration:Electricity | 33.79 | 936.03 | 25-MAR-04:20 | 1199.26 | 04-AUG-13:10 |
Fans:Electricity | 1843.50 | 54557.98 | 03-MAR-00:30 | 78029.57 | 10-AUG-15:20 |
Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Electricity:HVAC | 2253.15 | 55590.24 | 26-OCT-01:50 | 95345.18 | 10-AUG-15:20 |
ExteriorEquipment:Electricity | 679.68 | 10574.27 | 02-JAN-02:20 | 40537.60 | 02-JAN-07:20 |
Transformer:ExteriorEquipment:Electricity | 32.92 | 556.27 | 02-JAN-02:20 | 1912.91 | 02-JAN-21:10 |
ElectricityPurchased:Facility | 7135.14 | 128567.79 | 29-JUL-05:00 | 506147.55 | 10-AUG-18:10 |
ElectricityPurchased:Plant | 7135.14 | 128567.79 | 29-JUL-05:00 | 506147.55 | 10-AUG-18:10 |
Cogeneration:ElectricityPurchased | 7135.14 | 128567.79 | 29-JUL-05:00 | 506147.55 | 10-AUG-18:10 |
General:Cogeneration:ElectricityPurchased | 7135.14 | 128567.79 | 29-JUL-05:00 | 506147.55 | 10-AUG-18:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 7135.14 | 128567.79 | 29-JUL-05:00 | 506147.55 | 10-AUG-18:10 |
ElectricityNet:Plant | 7135.14 | 128567.79 | 29-JUL-05:00 | 506147.55 | 10-AUG-18:10 |
Cogeneration:ElectricityNet | 7135.14 | 128567.79 | 29-JUL-05:00 | 506147.55 | 10-AUG-18:10 |
General:Cogeneration:ElectricityNet | 7135.14 | 128567.79 | 29-JUL-05:00 | 506147.55 | 10-AUG-18:10 |
General:Fans:Electricity | 1843.50 | 54557.98 | 03-MAR-00:30 | 78029.57 | 10-AUG-15:20 |
ExteriorLights:Electricity | 261.75 | 0.00 | 01-JAN-08:10 | 16690.39 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 261.75 | 0.00 | 01-JAN-08:10 | 16690.39 | 01-JAN-00:10 |
ElevatorLift:ExteriorEquipment:Electricity | 616.11 | 9046.01 | 01-JAN-00:10 | 37691.69 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 30.65 | 972.00 | 01-JAN-00:10 | 972.00 | 01-JAN-00:10 |
HeatRecovery:Electricity | 376.74 | 0.00 | 11-JAN-13:50 | 16416.82 | 26-APR-17:10 |
General:HeatRecovery:Electricity | 376.74 | 0.00 | 11-JAN-13:50 | 16416.82 | 26-APR-17:10 |
WaterSystems:Electricity | 90.78 | 1087.05 | 05-MAY-00:30 | 4739.94 | 02-JAN-07:10 |
Water Heater:WaterSystems:Electricity | 90.78 | 1087.05 | 05-MAY-00:30 | 4739.94 | 02-JAN-07:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 724.13 | 0.00 | 01-JAN-00:10 | 202014.87 | 10-AUG-18:10 |
General:Cooling:Electricity | 724.13 | 0.00 | 01-JAN-00:10 | 202014.87 | 10-AUG-18:10 |
Pumps:Electricity | 158.70 | 282.61 | 04-NOV-07:40 | 10071.73 | 08-AUG-10:40 |
General:Pumps:Electricity | 158.70 | 282.61 | 04-NOV-07:40 | 10071.73 | 08-AUG-10:40 |
WIRED_LTG_ELECTRICITY | 41.33 | 0.00 | 01-JAN-00:10 | 3276.83 | 02-JAN-20:20 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 6956.11 | 45701.36 | 29-AUG-23:10 | 523159.42 | 16-JAN-17:40 |
NaturalGas:Building | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
NaturalGas:SpaceType:GENERAL | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:NaturalGas | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
InteriorEquipment:NaturalGas:SpaceType:GENERAL | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
Laundry:InteriorEquipment:NaturalGas | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
NaturalGas:Plant | 5167.27 | 28157.72 | 29-AUG-23:10 | 435638.08 | 16-JAN-17:40 |
WaterSystems:NaturalGas | 3238.81 | 18467.44 | 01-JAN-11:20 | 286401.03 | 14-FEB-21:40 |
Water Heater:WaterSystems:NaturalGas | 3238.81 | 18467.44 | 01-JAN-11:20 | 286401.03 | 14-FEB-21:40 |
Heating:NaturalGas | 1928.47 | 580.41 | 24-AUG-21:10 | 227830.41 | 19-FEB-07:10 |
Boiler:Heating:NaturalGas | 1928.47 | 580.41 | 24-AUG-21:10 | 227830.41 | 19-FEB-07:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 2197.36 | 0.00 | 01-JAN-00:10 | 638601.04 | 10-AUG-18:10 |
PlantLoopCoolingDemand:HVAC | 2197.36 | 0.00 | 01-JAN-00:10 | 638601.04 | 10-AUG-18:10 |
CoolingCoils:PlantLoopCoolingDemand | 2197.36 | 0.00 | 01-JAN-00:10 | 638601.04 | 10-AUG-18:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-21:10 |
Water:Plant | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-21:10 |
WaterSystems:Water | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-21:10 |
Water Heater:WaterSystems:Water | 5742.51 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-19:20 |
MainsWater:Facility | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-21:10 |
MainsWater:Plant | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-21:10 |
WaterSystems:MainsWater | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-21:10 |
Water Heater:WaterSystems:MainsWater | 5742.51 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-19:20 |
WaterUse:WaterSystems:Water | 4114.69 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-07:10 |
WaterUse:WaterSystems:MainsWater | 4114.69 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-07:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 20586.65 | 249092.79 | 21-OCT-12:40 | 2767339.56 | 10-AUG-18:10 |
EnergyTransfer:Building | 5570.95 | 88357.80 | 01-JAN-15:50 | 390674.40 | 10-AUG-18:20 |
EnergyTransfer:Zone:KITCHEN_FLR_6 | 736.36 | 11520.66 | 19-FEB-04:00 | 36070.81 | 08-AUG-10:40 |
Refrigeration:EnergyTransfer | 187.98 | 3719.27 | 11-FEB-23:30 | 10372.86 | 04-AUG-07:00 |
Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 93.99 | 1859.63 | 11-FEB-23:30 | 5186.43 | 04-AUG-07:00 |
General:Refrigeration:EnergyTransfer | 93.99 | 1859.63 | 11-FEB-23:30 | 5186.43 | 04-AUG-07:00 |
General:Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 93.99 | 1859.63 | 11-FEB-23:30 | 5186.43 | 04-AUG-07:00 |
EnergyTransfer:Plant | 7601.95 | 56106.54 | 04-FEB-01:10 | 1534958.39 | 10-AUG-18:10 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 25.74 | 0.00 | 01-JAN-11:10 | 2686.44 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 68.25 | 1758.08 | 25-MAR-04:20 | 2547.77 | 04-AUG-13:10 |
EnergyTransfer:Zone:BASEMENT | 453.43 | 7709.94 | 17-APR-11:00 | 21915.65 | 10-AUG-19:10 |
Heating:EnergyTransfer | 83.05 | 0.00 | 01-JAN-11:40 | 62939.80 | 26-DEC-16:10 |
Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer | 83.05 | 0.00 | 01-JAN-11:40 | 62939.80 | 26-DEC-16:10 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer | 5393.91 | 72292.05 | 26-DEC-11:00 | 386886.12 | 10-AUG-18:20 |
Cooling:EnergyTransfer:Zone:BASEMENT | 453.43 | 7709.94 | 17-APR-11:00 | 21915.65 | 10-AUG-19:10 |
General:Cooling:EnergyTransfer | 5393.91 | 72292.05 | 26-DEC-11:00 | 386886.12 | 10-AUG-18:20 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 453.43 | 7709.94 | 17-APR-11:00 | 21915.65 | 10-AUG-19:10 |
EnergyTransfer:Zone:RETAIL_1_FLR_1 | 36.69 | 0.07 | 11-FEB-07:00 | 4572.22 | 04-OCT-10:40 |
Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 0.43 | 0.00 | 01-JAN-10:00 | 545.95 | 19-FEB-06:00 |
General:Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 0.43 | 0.00 | 01-JAN-10:00 | 545.95 | 19-FEB-06:00 |
Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 36.26 | 0.00 | 01-JAN-00:10 | 4572.22 | 04-OCT-10:40 |
General:Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 36.26 | 0.00 | 01-JAN-00:10 | 4572.22 | 04-OCT-10:40 |
EnergyTransfer:Zone:RETAIL_2_FLR_1 | 37.85 | 263.62 | 26-DEC-12:30 | 2244.11 | 10-AUG-18:10 |
Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 37.85 | 263.62 | 26-DEC-12:30 | 2244.11 | 10-AUG-18:10 |
General:Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 37.85 | 263.62 | 26-DEC-12:30 | 2244.11 | 10-AUG-18:10 |
EnergyTransfer:Zone:MECH_FLR_1 | 26.24 | 0.04 | 20-FEB-03:20 | 2129.60 | 10-AUG-18:10 |
Heating:EnergyTransfer:Zone:MECH_FLR_1 | 0.01 | 0.00 | 01-JAN-00:10 | 107.40 | 16-JAN-15:40 |
General:Heating:EnergyTransfer:Zone:MECH_FLR_1 | 0.01 | 0.00 | 01-JAN-00:10 | 107.40 | 16-JAN-15:40 |
Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 26.23 | 0.00 | 06-JAN-05:00 | 2129.60 | 10-AUG-18:10 |
General:Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 26.23 | 0.00 | 06-JAN-05:00 | 2129.60 | 10-AUG-18:10 |
EnergyTransfer:Zone:STORAGE_FLR_1 | 9.18 | 0.00 | 24-JAN-17:30 | 984.84 | 10-AUG-19:10 |
Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 0.21 | 0.00 | 01-JAN-00:10 | 199.86 | 19-FEB-06:00 |
General:Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 0.21 | 0.00 | 01-JAN-00:10 | 199.86 | 19-FEB-06:00 |
Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 8.97 | 0.00 | 01-JAN-03:00 | 984.84 | 10-AUG-19:10 |
General:Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 8.97 | 0.00 | 01-JAN-03:00 | 984.84 | 10-AUG-19:10 |
EnergyTransfer:Zone:LAUNDRY_FLR_1 | 597.25 | 9034.36 | 17-JAN-05:00 | 37462.14 | 10-AUG-20:00 |
Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 597.25 | 9034.36 | 17-JAN-05:00 | 37462.14 | 10-AUG-20:00 |
General:Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 597.25 | 9034.36 | 17-JAN-05:00 | 37462.14 | 10-AUG-20:00 |
EnergyTransfer:Zone:CAFE_FLR_1 | 259.90 | 805.15 | 26-DEC-12:30 | 16337.32 | 14-SEP-15:20 |
Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 259.90 | 805.15 | 26-DEC-12:30 | 16337.32 | 14-SEP-15:20 |
General:Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 259.90 | 805.15 | 26-DEC-12:30 | 16337.32 | 14-SEP-15:20 |
EnergyTransfer:Zone:LOBBY_FLR_1 | 895.11 | 7411.50 | 26-DEC-14:40 | 47317.78 | 10-AUG-18:20 |
Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 895.11 | 7411.50 | 26-DEC-14:40 | 47317.78 | 10-AUG-18:20 |
General:Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 895.11 | 7411.50 | 26-DEC-14:40 | 47317.78 | 10-AUG-18:20 |
EnergyTransfer:Zone:ROOM_1_FLR_3 | 52.52 | 0.10 | 16-MAR-19:20 | 12707.26 | 10-AUG-18:10 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 11.44 | 0.00 | 01-JAN-08:10 | 4597.31 | 26-DEC-16:10 |
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 11.44 | 0.00 | 01-JAN-08:10 | 4597.31 | 26-DEC-16:10 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 41.08 | 0.00 | 01-JAN-00:10 | 12707.26 | 10-AUG-18:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 41.08 | 0.00 | 01-JAN-00:10 | 12707.26 | 10-AUG-18:10 |
EnergyTransfer:Zone:ROOM_2_FLR_3 | 47.22 | 0.06 | 14-FEB-15:40 | 12208.95 | 10-AUG-18:10 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 14.20 | 0.00 | 01-JAN-08:10 | 4613.59 | 26-DEC-16:20 |
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 14.20 | 0.00 | 01-JAN-08:10 | 4613.59 | 26-DEC-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 33.03 | 0.00 | 01-JAN-00:10 | 12208.95 | 10-AUG-18:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 33.03 | 0.00 | 01-JAN-00:10 | 12208.95 | 10-AUG-18:10 |
EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 470.99 | 1.33 | 19-DEC-16:50 | 68718.72 | 04-OCT-12:30 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 1.72 | 0.00 | 01-JAN-00:10 | 9184.13 | 19-FEB-06:00 |
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 1.72 | 0.00 | 01-JAN-00:10 | 9184.13 | 19-FEB-06:00 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 469.27 | 0.00 | 01-JAN-01:40 | 68718.72 | 04-OCT-12:30 |
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 469.27 | 0.00 | 01-JAN-01:40 | 68718.72 | 04-OCT-12:30 |
EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 446.51 | 0.01 | 14-JAN-10:10 | 68703.74 | 24-JUL-18:20 |
Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 7.12 | 0.00 | 01-JAN-00:10 | 27739.16 | 07-JAN-16:10 |
General:Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 7.12 | 0.00 | 01-JAN-00:10 | 27739.16 | 07-JAN-16:10 |
Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 439.39 | 0.00 | 01-JAN-16:30 | 68703.74 | 24-JUL-18:20 |
General:Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 439.39 | 0.00 | 01-JAN-16:30 | 68703.74 | 24-JUL-18:20 |
EnergyTransfer:Zone:ROOM_5_FLR_3 | 50.88 | 0.00 | 15-MAR-04:10 | 11128.01 | 10-AUG-08:10 |
Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 11.49 | 0.00 | 01-JAN-08:10 | 4563.50 | 26-DEC-16:10 |
General:Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 11.49 | 0.00 | 01-JAN-08:10 | 4563.50 | 26-DEC-16:10 |
Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 39.39 | 0.00 | 01-JAN-00:10 | 11128.01 | 10-AUG-08:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 39.39 | 0.00 | 01-JAN-00:10 | 11128.01 | 10-AUG-08:10 |
EnergyTransfer:Zone:ROOM_6_FLR_3 | 45.07 | 0.01 | 01-MAY-02:40 | 10639.27 | 10-AUG-08:10 |
Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 14.15 | 0.00 | 01-JAN-08:10 | 4597.73 | 26-DEC-16:20 |
General:Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 14.15 | 0.00 | 01-JAN-08:10 | 4597.73 | 26-DEC-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 30.92 | 0.00 | 01-JAN-00:10 | 10639.27 | 10-AUG-08:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 30.92 | 0.00 | 01-JAN-00:10 | 10639.27 | 10-AUG-08:10 |
EnergyTransfer:Zone:CORRIDOR_FLR_3 | 181.55 | 0.17 | 19-FEB-05:50 | 12900.91 | 13-AUG-10:40 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 0.36 | 0.00 | 01-JAN-00:10 | 1573.74 | 26-DEC-15:00 |
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 0.36 | 0.00 | 01-JAN-00:10 | 1573.74 | 26-DEC-15:00 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 181.19 | 0.00 | 01-JAN-13:10 | 12900.91 | 13-AUG-10:40 |
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 181.19 | 0.00 | 01-JAN-13:10 | 12900.91 | 13-AUG-10:40 |
EnergyTransfer:Zone:ROOM_1_FLR_6 | 15.85 | 0.07 | 03-FEB-21:00 | 3666.60 | 10-AUG-18:10 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 4.82 | 0.00 | 01-JAN-08:10 | 1541.68 | 26-DEC-16:20 |
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 4.82 | 0.00 | 01-JAN-08:10 | 1541.68 | 26-DEC-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 11.03 | 0.00 | 01-JAN-00:10 | 3666.60 | 10-AUG-18:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 11.03 | 0.00 | 01-JAN-00:10 | 3666.60 | 10-AUG-18:10 |
EnergyTransfer:Zone:ROOM_2_FLR_6 | 14.62 | 0.01 | 05-MAR-14:00 | 3377.21 | 10-AUG-18:10 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 5.77 | 0.00 | 01-JAN-08:10 | 1548.40 | 26-DEC-16:20 |
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 5.77 | 0.00 | 01-JAN-08:10 | 1548.40 | 26-DEC-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 8.86 | 0.00 | 01-JAN-00:10 | 3377.21 | 10-AUG-18:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 8.86 | 0.00 | 01-JAN-00:10 | 3377.21 | 10-AUG-18:10 |
EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 88.50 | 0.31 | 07-DEC-21:40 | 19412.22 | 14-SEP-15:10 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 9.90 | 0.00 | 01-JAN-08:10 | 7247.84 | 26-DEC-16:20 |
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 9.90 | 0.00 | 01-JAN-08:10 | 7247.84 | 26-DEC-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 78.60 | 0.00 | 01-JAN-00:10 | 19412.22 | 14-SEP-15:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 78.60 | 0.00 | 01-JAN-00:10 | 19412.22 | 14-SEP-15:10 |
EnergyTransfer:Zone:BANQUET_FLR_6 | 496.33 | 7984.85 | 15-JAN-16:00 | 22376.63 | 10-AUG-18:40 |
Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 496.33 | 7984.85 | 15-JAN-16:00 | 22376.63 | 10-AUG-18:40 |
General:Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 496.33 | 7984.85 | 15-JAN-16:00 | 22376.63 | 10-AUG-18:40 |
EnergyTransfer:Zone:DINING_FLR_6 | 533.59 | 9169.44 | 15-JAN-16:00 | 23770.21 | 24-JUL-18:10 |
Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 533.59 | 9169.44 | 15-JAN-16:00 | 23770.21 | 24-JUL-18:10 |
General:Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 533.59 | 9169.44 | 15-JAN-16:00 | 23770.21 | 24-JUL-18:10 |
Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 642.37 | 9338.08 | 19-FEB-04:00 | 30989.51 | 08-AUG-10:40 |
General:Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 642.37 | 9338.08 | 19-FEB-04:00 | 30989.51 | 08-AUG-10:40 |
EnergyTransfer:Zone:CORRIDOR_FLR_6 | 75.30 | 0.00 | 13-DEC-05:30 | 7497.20 | 10-AUG-10:40 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 1.44 | 0.00 | 01-JAN-00:10 | 1643.35 | 19-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 1.44 | 0.00 | 01-JAN-00:10 | 1643.35 | 19-FEB-06:10 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 73.86 | 0.00 | 01-JAN-01:20 | 7497.20 | 10-AUG-10:40 |
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 73.86 | 0.00 | 01-JAN-01:20 | 7497.20 | 10-AUG-10:40 |
PlantLoopHeatingDemand:Facility | 2138.82 | 16942.69 | 10-AUG-22:10 | 221092.30 | 19-FEB-07:10 |
PlantLoopHeatingDemand:Plant | 764.23 | 9491.78 | 15-AUG-03:00 | 54615.41 | 09-FEB-07:10 |
WaterSystems:PlantLoopHeatingDemand | 764.23 | 9491.78 | 15-AUG-03:00 | 54615.41 | 09-FEB-07:10 |
General:WaterSystems:PlantLoopHeatingDemand | 764.23 | 9491.78 | 15-AUG-03:00 | 54615.41 | 09-FEB-07:10 |
EnergyTransfer:HVAC | 7413.75 | 30792.12 | 08-MAR-23:10 | 849301.61 | 10-AUG-18:10 |
HeatingCoils:EnergyTransfer | 1374.59 | 390.88 | 24-AUG-21:10 | 178877.45 | 19-FEB-07:10 |
PlantLoopHeatingDemand:HVAC | 1374.59 | 390.88 | 24-AUG-21:10 | 178877.45 | 19-FEB-07:10 |
HeatingCoils:PlantLoopHeatingDemand | 1374.59 | 390.88 | 24-AUG-21:10 | 178877.45 | 19-FEB-07:10 |
CoolingCoils:EnergyTransfer | 2197.36 | 0.00 | 01-JAN-00:10 | 638601.04 | 10-AUG-18:10 |
HeatRecoveryForHeating:EnergyTransfer | 3750.74 | 0.00 | 11-JAN-13:50 | 564212.85 | 19-FEB-05:00 |
HeatRecoveryForCooling:EnergyTransfer | 91.07 | 0.00 | 01-JAN-00:10 | 217776.60 | 29-AUG-13:00 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:EnergyTransfer | 764.23 | 9491.78 | 15-AUG-03:00 | 54615.41 | 09-FEB-07:10 |
WaterUse:WaterSystems:EnergyTransfer | 764.23 | 9491.78 | 15-AUG-03:00 | 54615.41 | 09-FEB-07:10 |
Boilers:EnergyTransfer | 1363.57 | 348.68 | 24-AUG-21:10 | 176905.30 | 19-FEB-07:10 |
Chillers:EnergyTransfer | 2328.01 | 0.00 | 01-JAN-00:10 | 645991.69 | 10-AUG-18:10 |
HeatRejection:EnergyTransfer | 3052.14 | 0.00 | 01-JAN-00:10 | 848006.56 | 10-AUG-18:10 |
General:HeatRejection:EnergyTransfer | 3052.14 | 0.00 | 01-JAN-00:10 | 848006.56 | 10-AUG-18:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:58:38
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 0.000 | -453.431 | 0.000 | 0.000 | 158.370 | 165.288 | 150.255 | 0.000 | 0.000 | 0.000 | 0.002 | 0.000 | 0.000 | 0.000 | 0.000 | -20.482 |
RETAIL_1_FLR_1 | 0.000 | 0.000 | 0.431 | -36.263 | 0.000 | 0.000 | 16.174 | 8.404 | 10.186 | 23.623 | 0.000 | 0.064 | 0.000 | 0.000 | -9.680 | 0.000 | -3.843 | -9.096 |
RETAIL_2_FLR_1 | 0.000 | 0.000 | 0.000 | -37.848 | 0.000 | 0.000 | 18.664 | 9.732 | 11.795 | 0.000 | 0.000 | 0.026 | 0.000 | 0.000 | 0.000 | 0.000 | -1.490 | -0.880 |
MECH_FLR_1 | 0.000 | 0.000 | 0.006 | -26.231 | 0.000 | 0.000 | 3.957 | 18.192 | 12.471 | 0.000 | 0.000 | 0.062 | 0.000 | 0.000 | 0.000 | 0.000 | -3.510 | -4.946 |
STORAGE_FLR_1 | 0.000 | 0.000 | 0.212 | -8.971 | 0.000 | 0.000 | 3.046 | 3.340 | 3.598 | 0.000 | 0.000 | 0.036 | 0.763 | 0.000 | 0.000 | 0.000 | -2.023 | -0.000 |
LAUNDRY_FLR_1 | 0.000 | 0.000 | 0.000 | -597.254 | 0.000 | 0.000 | 12.195 | 4.125 | 658.131 | 0.000 | 0.000 | 0.079 | 0.000 | 0.000 | 0.000 | 0.000 | -4.978 | -72.298 |
CAFE_FLR_1 | 0.000 | 0.000 | 0.000 | -259.899 | 0.000 | 0.000 | 212.338 | 26.624 | 14.341 | 66.189 | 0.000 | 0.147 | 0.000 | 0.000 | -27.324 | 0.000 | -8.508 | -23.906 |
LOBBY_FLR_1 | 0.000 | 0.000 | 0.000 | -895.113 | 0.000 | 0.000 | 627.731 | 144.896 | 148.998 | 87.631 | 0.000 | 0.427 | 0.000 | 0.000 | -36.561 | 0.000 | -24.428 | -53.581 |
ROOM_1_FLR_3 | 18.093 | -30.355 | 0.000 | -17.382 | 0.000 | 0.000 | 9.742 | 20.410 | 12.292 | 44.080 | 0.000 | 0.154 | 0.000 | 0.000 | -22.867 | 0.000 | -9.771 | -24.397 |
ROOM_2_FLR_3 | 21.504 | -23.244 | 0.000 | -17.089 | 0.000 | 0.000 | 9.769 | 20.407 | 12.291 | 31.053 | 0.000 | 0.158 | 0.000 | 0.000 | -23.104 | 0.000 | -9.684 | -22.060 |
ROOM_3_MULT19_FLR_3 | 12.857 | -212.999 | 0.000 | -267.412 | 0.000 | 0.000 | 0.000 | 243.708 | 228.754 | 273.794 | 0.000 | 0.375 | 0.002 | 0.000 | -134.384 | 0.000 | -73.293 | -71.400 |
ROOM_4_MULT19_FLR_3 | 48.935 | -246.538 | 0.000 | -234.659 | 0.000 | 0.000 | 185.186 | 243.774 | 228.817 | 75.998 | 0.000 | 1.635 | 0.000 | 0.000 | -129.798 | 0.000 | -59.981 | -113.371 |
ROOM_5_FLR_3 | 18.131 | -28.593 | 0.000 | -17.434 | 0.000 | 0.000 | 9.738 | 20.410 | 12.292 | 42.119 | 0.000 | 0.155 | 0.000 | 0.000 | -22.410 | 0.000 | -9.785 | -24.624 |
ROOM_6_FLR_3 | 21.476 | -21.066 | 0.000 | -17.178 | 0.000 | 0.000 | 9.763 | 20.407 | 12.291 | 28.930 | 0.000 | 0.159 | 0.000 | 0.000 | -22.523 | 0.000 | -9.710 | -22.549 |
CORRIDOR_FLR_3 | 0.000 | 0.000 | 0.365 | -181.189 | 0.000 | 0.000 | 124.818 | 62.736 | 0.000 | 41.007 | 0.000 | 0.172 | 0.001 | 0.000 | -28.231 | 0.000 | -10.869 | -8.809 |
ROOM_1_FLR_6 | 6.675 | -8.568 | 0.000 | -4.323 | 0.000 | 0.000 | 2.438 | 5.102 | 3.073 | 10.916 | 0.000 | 0.039 | 0.000 | 0.000 | -5.687 | 0.000 | -2.472 | -7.193 |
ROOM_2_FLR_6 | 7.789 | -6.620 | 0.000 | -4.258 | 0.000 | 0.000 | 2.444 | 5.102 | 3.073 | 7.675 | 0.000 | 0.041 | 0.000 | 0.000 | -5.736 | 0.000 | -2.456 | -7.052 |
ROOM_3_MULT9_FLR_6 | 18.423 | -58.748 | 0.000 | -28.376 | 0.000 | 0.000 | 21.856 | 28.868 | 27.097 | 59.731 | 0.000 | 0.247 | 0.000 | 0.000 | -26.863 | 0.000 | -12.303 | -29.932 |
BANQUET_FLR_6 | 0.000 | 0.000 | 0.000 | -496.336 | 0.000 | 0.000 | 358.019 | 46.753 | 175.857 | 8.733 | 0.000 | 0.082 | 0.000 | 0.000 | -15.527 | 0.000 | -5.804 | -71.777 |
DINING_FLR_6 | 0.000 | 0.000 | 0.000 | -533.590 | 0.000 | 0.000 | 356.447 | 46.753 | 175.857 | 8.543 | 0.000 | 0.079 | 0.000 | 0.000 | -15.939 | 0.000 | -5.841 | -32.308 |
KITCHEN_FLR_6 | 0.000 | 0.000 | 0.000 | -642.363 | 0.000 | 0.000 | 30.576 | 12.482 | 556.656 | 19.981 | 0.000 | 0.026 | 39.577 | 0.000 | -11.175 | 0.000 | -5.760 | 0.000 |
CORRIDOR_FLR_6 | 0.000 | 0.000 | 1.442 | -73.855 | 0.000 | 0.000 | 33.097 | 16.599 | 0.000 | 20.092 | 0.000 | 0.075 | 19.993 | 0.000 | -12.620 | 0.000 | -4.823 | -0.000 |
Total Facility | 173.883 | -636.732 | 2.456 | -4850.453 | 0.000 | 0.000 | 2206.369 | 1174.112 | 2458.123 | 850.095 | 0.000 | 4.237 | 60.338 | 0.000 | -550.429 | 0.000 | -271.332 | -620.661 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 10-AUG-19:10 | 0.00 | 0.00 | 0.00 | -21942.91 | 0.00 | 0.00 | 6162.19 | 13517.00 | 10113.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -7850.08 |
RETAIL_1_FLR_1 | 04-OCT-10:35 | 0.00 | 0.00 | 0.00 | -4633.48 | 0.00 | 0.00 | 171.39 | 190.92 | 252.59 | 6772.98 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -39.30 | -2715.10 |
RETAIL_2_FLR_1 | 10-AUG-18:10 | 0.00 | 0.00 | 0.00 | -2255.19 | 0.00 | 0.00 | 725.50 | 707.46 | 752.15 | 0.00 | 0.00 | 41.06 | 29.02 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 10-AUG-18:10 | 0.00 | 0.00 | 0.00 | -2130.81 | 0.00 | 0.00 | 153.45 | 1322.39 | 795.27 | 0.00 | 0.00 | 98.06 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -238.35 |
STORAGE_FLR_1 | 10-AUG-19:10 | 0.00 | 0.00 | 0.00 | -984.99 | 0.00 | 0.00 | 118.03 | 273.10 | 242.16 | 0.00 | 0.00 | 48.63 | 303.07 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 10-AUG-20:00 | 0.00 | 0.00 | 0.00 | -37464.05 | 0.00 | 0.00 | 421.38 | 337.37 | 44299.38 | 0.00 | 0.00 | 28.40 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -7622.47 |
CAFE_FLR_1 | 04-OCT-10:35 | 0.00 | 0.00 | 0.00 | -17037.05 | 0.00 | 0.00 | 2298.76 | 604.78 | 355.63 | 19059.83 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -73.94 | -5208.01 |
LOBBY_FLR_1 | 10-AUG-18:20 | 0.00 | 0.00 | 0.00 | -47360.06 | 0.00 | 0.00 | 24441.98 | 10532.73 | 9501.36 | 1874.33 | 0.00 | 668.65 | 341.01 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 14-MAY-15:02 | 0.00 | -14709.63 | 0.00 | -728.03 | 0.00 | 0.00 | 130.71 | 518.40 | 305.54 | 11477.14 | 0.00 | 76.16 | 2929.71 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 14-MAY-15:02 | 0.00 | -13326.49 | 0.00 | -727.81 | 0.00 | 0.00 | 130.72 | 518.34 | 305.51 | 10362.47 | 0.00 | 122.95 | 2614.33 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 04-OCT-12:30 | 0.00 | -58288.76 | 0.00 | -10424.24 | 0.00 | 0.00 | 0.00 | 5252.20 | 5097.90 | 87491.54 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -398.80 | -28729.84 |
ROOM_4_MULT19_FLR_3 | 09-JUN-18:02 | 0.00 | -71796.65 | 0.00 | -9974.11 | 0.00 | 0.00 | 6422.19 | 16699.06 | 9610.21 | 12487.08 | 0.00 | 0.00 | 36577.32 | 0.00 | -0.00 | 0.00 | -25.10 | 0.00 |
ROOM_5_FLR_3 | 14-MAY-15:02 | 0.00 | -13046.86 | 0.00 | -717.29 | 0.00 | 0.00 | 130.72 | 518.40 | 305.54 | 3219.31 | 0.00 | 92.37 | 9497.80 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 14-MAY-15:02 | 0.00 | -11904.80 | 0.00 | -716.37 | 0.00 | 0.00 | 130.72 | 518.34 | 305.51 | 2111.97 | 0.00 | 150.87 | 9403.76 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 13-AUG-10:35 | 0.00 | 0.00 | 0.00 | -12944.94 | 0.00 | 0.00 | 2042.30 | 1710.14 | 0.00 | 8022.90 | 0.00 | 91.39 | 1078.21 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 14-MAY-15:02 | 0.00 | -3913.68 | 0.00 | -182.63 | 0.00 | 0.00 | 32.68 | 129.60 | 76.39 | 2847.19 | 0.00 | 19.86 | 990.60 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 14-MAY-18:02 | 0.00 | -3525.61 | 0.00 | -182.52 | 0.00 | 0.00 | 70.80 | 392.68 | 129.05 | 1844.20 | 0.00 | 0.00 | 1294.01 | 0.00 | -0.00 | 0.00 | -22.60 | 0.00 |
ROOM_3_MULT9_FLR_6 | 04-OCT-15:02 | 0.00 | -21468.77 | 0.00 | -1175.92 | 0.00 | 0.00 | 529.41 | 622.14 | 603.86 | 10406.95 | 0.00 | 0.00 | 10765.03 | 0.00 | -0.00 | 0.00 | -282.71 | 0.00 |
BANQUET_FLR_6 | 24-JUL-18:10 | 0.00 | 0.00 | 0.00 | -22733.91 | 0.00 | 0.00 | 14193.27 | 3398.57 | 6747.90 | 1834.71 | 0.00 | 108.88 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -3549.43 |
DINING_FLR_6 | 24-JUL-18:10 | 0.00 | 0.00 | 0.00 | -24140.71 | 0.00 | 0.00 | 14103.32 | 3398.57 | 6747.90 | 1813.37 | 0.00 | 107.18 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2029.64 |
KITCHEN_FLR_6 | 08-AUG-10:35 | 0.00 | 0.00 | 0.00 | -30991.99 | 0.00 | 0.00 | 309.43 | 283.55 | 24459.16 | 4089.06 | 0.00 | 10.34 | 1840.45 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 10-AUG-10:35 | 0.00 | 0.00 | 0.00 | -7544.50 | 0.00 | 0.00 | 362.40 | 377.07 | 0.00 | 3784.71 | 0.00 | 38.23 | 2982.10 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 10-AUG-18:02 | 0.00 | -178637.75 | 0.00 | -241324.44 | 0.00 | 0.00 | 84896.65 | 82800.17 | 122526.13 | 55046.07 | 0.00 | 5349.95 | 69343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 19-FEB-06:00 | 0.00 | 0.00 | 545.94 | 0.00 | 0.00 | 0.00 | 653.17 | 152.73 | 216.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1133.37 | 0.00 | -327.62 | -107.35 |
RETAIL_2_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 16-JAN-15:40 | 0.00 | 0.00 | 107.40 | 0.00 | 0.00 | 0.00 | 43.84 | 330.60 | 265.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -217.14 | -529.79 |
STORAGE_FLR_1 | 19-FEB-06:00 | 0.00 | 0.00 | 199.85 | 0.00 | 0.00 | 0.00 | 118.21 | 60.69 | 76.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -178.22 | -277.00 |
LAUNDRY_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 27-DEC-16:02 | 6458.25 | 380.52 | 0.00 | -380.52 | 0.00 | 0.00 | 293.99 | 439.85 | 273.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1114.27 | 0.00 | -342.53 | -6009.22 |
ROOM_2_FLR_3 | 27-DEC-16:02 | 6278.17 | 379.14 | 0.00 | -379.14 | 0.00 | 0.00 | 293.99 | 439.80 | 273.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1106.67 | 0.00 | -341.98 | -5837.20 |
ROOM_3_MULT19_FLR_3 | 19-FEB-06:00 | 9183.86 | 16443.44 | 0.00 | -16443.44 | 0.00 | 0.00 | 0.00 | 2063.36 | 3921.46 | 0.00 | 0.00 | 0.00 | 2470.35 | 0.00 | -13790.77 | 0.00 | -3848.27 | 0.00 |
ROOM_4_MULT19_FLR_3 | 10-JAN-16:02 | 32422.75 | 5237.97 | 0.00 | -5237.97 | 0.00 | 0.00 | 5233.22 | 5253.64 | 5099.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4338.10 | 0.00 | -1612.60 | -42058.19 |
ROOM_5_FLR_3 | 27-DEC-16:02 | 6264.69 | 379.39 | 0.00 | -379.39 | 0.00 | 0.00 | 293.99 | 439.85 | 273.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1107.38 | 0.00 | -342.09 | -5822.99 |
ROOM_6_FLR_3 | 10-DEC-16:01 | 6128.26 | 326.23 | 0.00 | -326.23 | 0.00 | 0.00 | 159.93 | 518.34 | 305.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -933.57 | 0.00 | -293.43 | -5885.04 |
CORRIDOR_FLR_3 | 26-DEC-15:00 | 0.00 | 0.00 | 1573.78 | 0.00 | 0.00 | 0.00 | 1395.55 | 1425.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1756.99 | 0.00 | -660.19 | -1977.27 |
ROOM_1_FLR_6 | 27-DEC-16:02 | 1917.14 | 95.92 | 0.00 | -95.92 | 0.00 | 0.00 | 73.50 | 109.96 | 68.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -273.53 | 0.00 | -86.39 | -1809.18 |
ROOM_2_FLR_6 | 27-DEC-16:02 | 1863.48 | 95.45 | 0.00 | -95.45 | 0.00 | 0.00 | 73.50 | 109.95 | 68.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -271.20 | 0.00 | -86.20 | -1758.01 |
ROOM_3_MULT9_FLR_6 | 27-DEC-16:02 | 9461.91 | 615.71 | 0.00 | -615.71 | 0.00 | 0.00 | 661.47 | 622.14 | 603.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1307.95 | 0.00 | -397.65 | -9643.79 |
BANQUET_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 19-FEB-06:10 | 0.00 | 0.00 | 1643.31 | 0.00 | 0.00 | 0.00 | 1298.12 | 452.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1499.74 | 0.00 | -417.22 | -1476.94 |
Total Facility | 26-DEC-16:13 | -22014.82 | 115006.44 | 3153.23 | -115006.44 | 0.00 | 0.00 | 62053.85 | 25962.78 | 77528.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -38027.03 | 0.00 | -12200.07 | -96456.93 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:58:38
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV WITH REHEAT | 22.9299 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 22.8152 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
FLR_3_DOAS | 2.0513 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.0513 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV WITH REHEAT | 22.8152 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 22.8152 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
FLR_3_DOAS | 2.0513 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.0513 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | VAV WITH REHEAT | 0.000000 | 106.4990 | 0.000432 | 1978.83 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | 0.000000 | 10.8290 | 0.001181 | 67.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | 0.000000 | 12.5400 | 0.001181 | 77.67 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
MECH_FLR_1 | VAV WITH REHEAT | 0.000000 | 2.6520 | 0.000000 | 164.24 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | 0.000000 | 2.0400 | 0.000610 | 94.76 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | 0.000000 | 8.4000 | 0.000000 | 78.04 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | 0.000000 | 142.3000 | 0.003581 | 188.86 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | 0.000000 | 422.4350 | 0.001448 | 1308.19 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1863.81 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1864.32 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | 0.000000 | 83.8280 | 0.000305 | 1557.62 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000396 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000396 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.000000 | 13.5000 | 0.000449 | 220.77 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003581 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DINING_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003581 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | 0.000000 | 22.2380 | 0.003556 | 103.30 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | 0.000000 | 22.1800 | 0.000305 | 412.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV WITH REHEAT | 0.00 | 0.001045 | 6694.0231 | 0.0000 | 0.0000 | 0.0000 | |
FLR_3_DOAS | 0.00 | 0.000441 | 4651.2638 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.5350 | 2.5350 | 2.5224 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4826 | 0.4826 | 0.4802 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2412 | 0.2412 | 0.2400 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2309 | 0.2309 | 0.2298 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1143 | 0.1143 | 0.1137 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.3000 | 3.3000 | 3.2835 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.8912 | 1.8912 | 1.8818 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.2309 | 5.2309 | 5.2047 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8371 | 0.8371 | 0.8371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8373 | 0.8373 | 0.8373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2916 | 1.2916 | 1.2852 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0992 | 0.0992 | 0.0992 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.2051 | 2.2051 | 2.1940 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.3130 | 2.3130 | 2.3015 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.3268 | 2.3268 | 2.3152 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7671 | 0.7671 | 0.7633 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV WITH REHEAT | 22.9299 | 22.8152 | 22.9299 | 22.8152 | 0.0000 | 1.0000 |
FLR_3_DOAS | 2.0513 | 2.0513 | 2.0513 | 2.0513 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.5224 | 2.5224 | 2.5224 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4802 | 0.4802 | 0.4802 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2400 | 0.2400 | 0.2400 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2298 | 0.2298 | 0.2298 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1137 | 0.1137 | 0.1137 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.2835 | 3.2835 | 3.2835 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.8818 | 1.8818 | 1.8818 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.2047 | 5.2047 | 5.2047 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8371 | 0.8371 | 0.8371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8373 | 0.8373 | 0.8373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2852 | 1.2852 | 1.2852 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0992 | 0.0992 | 0.0992 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.1940 | 2.1940 | 2.1940 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.3015 | 2.3015 | 2.3015 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.3152 | 2.3152 | 2.3152 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7633 | 0.7633 | 0.7633 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV WITH REHEAT | 22.8152 | 22.8152 | 22.8152 | 22.8152 | 0.0000 | 1.0000 |
FLR_3_DOAS | 2.0513 | 2.0513 | 2.0513 | 2.0513 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:58:38
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 |
Total gross floor area [m2] | 11345.29 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 1978.83 | 1978.83 | 0.00 | 168.00 |
RETAIL_1_FLR_1 | 67.07 | 67.07 | 0.00 | 168.00 |
RETAIL_2_FLR_1 | 77.67 | 77.67 | 0.00 | 168.00 |
MECH_FLR_1 | 164.24 | 164.24 | 0.00 | 168.00 |
STORAGE_FLR_1 | 94.76 | 94.76 | 0.00 | 168.00 |
LAUNDRY_FLR_1 | 78.04 | 78.04 | 0.00 | 168.00 |
CAFE_FLR_1 | 188.86 | 188.86 | 0.00 | 168.00 |
LOBBY_FLR_1 | 1308.19 | 1308.19 | 0.00 | 168.00 |
ROOM_1_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT19_FLR_3 | 24.52 | 24.52 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 24.53 | 24.53 | 0.00 | 168.00 |
ROOM_5_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_6_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
CORRIDOR_FLR_3 | 389.40 | 389.40 | 0.00 | 168.00 |
ROOM_1_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT9_FLR_6 | 24.53 | 24.53 | 0.00 | 168.00 |
BANQUET_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
DINING_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
KITCHEN_FLR_6 | 103.30 | 103.30 | 0.00 | 168.00 |
CORRIDOR_FLR_6 | 412.12 | 412.12 | 0.00 | 168.00 |
Totals | 11345.29 | 11345.29 | 0.00 |
Data | |
Number of hours heating loads not met | 38.83 |
Number of hours cooling loads not met | 9.33 |
Number of hours not met | 48.17 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 1928.47 | 227830.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 724.13 | 202014.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 1174.11 | 93091.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 261.75 | 16690.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 959.56 | 59492.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 762.04 | 29240.64 | 1198.64 | 74976.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 16.27 | 515.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 13.43 | 425.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Laundry | 0.00 | 0.00 | 590.20 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 32.92 | 1912.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 616.11 | 37691.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 30.65 | 972.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 1843.50 | 78029.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 158.70 | 10071.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- General | 376.74 | 16416.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 90.78 | 4739.94 | 3238.81 | 286401.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 18.27 | 2271.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 22.39 | 1897.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 33.79 | 1199.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 1825.75 | 7135.14 |
Natural Gas | 1788.84 | 6956.11 |
Additional | 0.00 | 0.00 |
Total | 3614.59 | 14091.26 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 103.49 |
Space Heating | 0.00 |
Space Cooling | 63.83 |
Fans (All) | 162.49 |
Service Water Heating | 8.00 |
Receptacle Equipment | 154.36 |
Miscellaneous (All) | 628.91 |
Subtotal | 628.91 |
Natural Gas [MJ/m2] | |
Space Heating | 169.98 |
Service Water Heating | 285.48 |
Miscellaneous (All) | 613.13 |
Subtotal | 613.13 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 8.33 |
Space Heating | 13.69 |
Space Cooling | 5.14 |
Fans (All) | 13.08 |
Service Water Heating | 23.63 |
Receptacle Equipment | 25.12 |
Miscellaneous | 11.01 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_KITCHEN | 3061. | 8760. |
LTG_SCH_DINING | 3061. | 8760. |
LTG_SCH_BASEMENT | 2655. | 8760. |
LTG_SCH_LOBBY | 3061. | 8760. |
LTG_SCH_STORAGE | 1339. | 8760. |
LTG_SCH_MECHANIC | 3061. | 8760. |
LTG_SCH_LAUNDRY | 2678. | 8760. |
LTG_SCH_GUESTROOM | 3599. | 8760. |
LTG_SCH_CORRIDOR | 3061. | 8760. |
LTG_SCH_RETAIL | 2678. | 8760. |
WALKIN_OCC_LGHT_SCH_1 | 3061. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
BASEMENT_EQUIP_SCH | 3924. | 8760. |
BLDG_EQUIP_SCH | 3924. | 8760. |
GUESTROOM_EQP_SCH_BASE | 3239. | 8760. |
GUESTROOM_EQP_SCH_ADVA | 2762. | 8760. |
LOBBY_EQP_SCH | 3292. | 8760. |
OFFICE_EQP_SCH | 4941. | 8760. |
EMPLOYEELOUNGE_EQP_SCH | 4044. | 8760. |
LAUNDRYROOM_EQP_ELEC_SCH | 2920. | 2920. |
LAUNDRYROOM_EQP_GAS_SCH | 2920. | 2920. |
MEETINGROOM_EQP_SCH | 1336. | 4745. |
EXERCISEROOM_EQP_SCH | 3832. | 5840. |
KITCHEN_ELEC_EQUIP_SCH | 2172. | 8760. |
KITCHEN_GAS_EQUIP_SCH | 1332. | 8760. |
KITCHEN_EXHAUST_SCH | 6205. | 6205. |
BLDG_ELEVATORS | 2270. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_OCC_SCH | 5026. | 8760. |
GUESTROOM_OCC_SCH | 5515. | 8760. |
LOBBY_OCC_SCH | 2304. | 8760. |
OFFICE_OCC_SCH | 3954. | 8760. |
EMPLOYEELOUNGE_OCC_SCH | 948. | 5475. |
MEETINGROOM_OCC_SCH | 1168. | 4745. |
LAUNDRYROOM_OCC_SCH | 427. | 2920. |
EXERCISEROOM_OCC_SCH | 5292. | 5840. |
INFIL_SCH | 8760. | 8760. |
INFIL_HALF_ON_SCH | 4380. | 8760. |
INFIL_QUARTER_ON_SCH | 2190. | 8760. |
LAUNDRY_SWH_SCH | 2555. | 2555. |
BLDG_SWH_SCH | 3301. | 8760. |
GUESTROOM_SWH_SCH | 2899. | 8760. |
LAUNDRYROOM_SWH_SCH | 2920. | 2920. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
ALWAYS_ON | 8760. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
OCC_GUESTROOM_VENT_CTRL_30MIN | 6570. | 6570. |
OCC_GUESTROOM_VENT_CTRL_20MIN | 6327. | 6327. |
VAC_GUESTROOM_VENTILATION_SCHEDULE | 365. | 365. |
MINOA_MOTORIZEDDAMPER_SCHED | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
ROOM_1_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
FLR_3_DOAS_OAMINOAFRACSCHEDULE | 8760. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 0. | 0. |
LAUNDRY_FLR_1 EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 0. | 0. |
SLIDING_DOORS_VENTILATION_AVAILABILITY_SCH | 3285. | 3285. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
VACGUESTROOM_HTGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 18.89 | 365 | 18.89 | 365 |
VACGUESTROOM_CLGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 23.33 | 365 |
OBCRESET_S_OCCGUESTROOM_HTGSP_SCH_30MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_S_OCCGUESTROOM_CLGSP_SCH_30MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_HTGSP_SCH_30MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_CLGSP_SCH_30MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
HTGSETP_SCH | BASEMENT DUAL SP CONTROL | January | 21.00 | 365 | 21.00 | 365 |
CLGSETP_SCH | BASEMENT DUAL SP CONTROL | July | 24.00 | 365 | 24.00 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:58:38
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Average | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Sum | 192720.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 529331.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 50179.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 59156.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8977.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 5588.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 37203.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 710417.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 2115429.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 100358.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 108269.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 105946.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 2115429.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Average | 288887.05 | 0.00 | 0.00 | 0.00 | 0.00 |
Sum | 6355515.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Average | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Sum | 192720.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 529331.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 50179.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 59156.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8977.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 5588.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 37203.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 710417.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 2115429.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 100358.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 108269.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 105946.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 2115429.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Average | 288887.05 | 0.00 | 0.00 | 0.00 | 0.00 |
Sum | 6355515.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:58:38
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:58:38
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2012
For: Environment
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
For: Environment
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4C
For: Environment
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_SEATTLE
For: Environment
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.380834E+11 | 19865.15 | 11-JAN-19:08 | 12.30 | 9.41 | 0.615083E+10 | 3784.17 | 06-JAN-22:10 | 12.30 | 9.41 |
February | 0.331322E+11 | 20053.75 | 23-FEB-19:10 | 12.20 | 11.56 | 0.554876E+10 | 3755.28 | 01-FEB-22:10 | 12.20 | 11.56 |
March | 0.355328E+11 | 19393.65 | 02-MAR-19:03 | 10.22 | 8.41 | 0.615525E+10 | 3759.73 | 09-MAR-22:10 | 13.03 | 11.95 |
April | 0.339123E+11 | 20382.18 | 27-APR-19:05 | 22.23 | 15.14 | 0.592997E+10 | 3714.62 | 28-APR-21:10 | 12.20 | 10.91 |
May | 0.357716E+11 | 20526.96 | 04-MAY-19:10 | 21.73 | 14.27 | 0.613154E+10 | 3717.81 | 17-MAY-21:10 | 6.78 | 5.68 |
June | 0.360189E+11 | 21304.61 | 28-JUN-19:10 | 23.95 | 15.67 | 0.594964E+10 | 3733.81 | 13-JUN-21:10 | 23.95 | 15.67 |
July | 0.385526E+11 | 21596.02 | 24-JUL-19:05 | 27.15 | 17.29 | 0.612771E+10 | 3747.00 | 28-JUL-22:10 | 14.90 | 12.78 |
August | 0.398757E+11 | 21942.15 | 10-AUG-19:10 | 29.18 | 18.39 | 0.616702E+10 | 3803.04 | 02-AUG-21:00 | 29.18 | 18.39 |
September | 0.397010E+11 | 21663.49 | 13-SEP-18:07 | 22.43 | 16.15 | 0.596978E+10 | 3832.03 | 28-SEP-21:49 | 12.88 | 10.36 |
October | 0.418359E+11 | 21085.86 | 12-OCT-18:06 | 12.02 | 8.53 | 0.618919E+10 | 3836.42 | 25-OCT-21:10 | 13.48 | 12.19 |
November | 0.408112E+11 | 20147.70 | 02-NOV-18:45 | 12.62 | 10.38 | 0.600010E+10 | 3841.27 | 30-NOV-22:10 | 4.40 | 3.87 |
December | 0.402026E+11 | 19548.73 | 05-DEC-21:00 | 5.60 | 1.73 | 0.617191E+10 | 3824.35 | 01-DEC-22:10 | 5.60 | 1.73 |
Annual Sum or Average | 0.453430E+12 | 0.724917E+11 | ||||||||
Minimum of Months | 0.331322E+11 | 19393.65 | 5.60 | 1.73 | 0.554876E+10 | 3714.62 | 4.40 | 1.73 | ||
Maximum of Months | 0.418359E+11 | 21942.15 | 29.18 | 18.39 | 0.618919E+10 | 3841.27 | 29.18 | 18.39 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.748273E+09 | 3534.52 | 20-JAN-13:10 | 6.70 | 4.72 | 0.613442E+09 | 364.32 | 12-JAN-05:49 | 6.70 | 4.72 |
February | 0.155469E+10 | 3925.97 | 12-FEB-11:35 | 5.60 | 0.67 | 0.557794E+09 | 364.38 | 27-FEB-04:10 | 12.70 | 7.49 |
March | 0.248474E+10 | 4413.00 | 02-MAR-11:35 | 9.63 | 6.30 | 0.623354E+09 | 364.33 | 04-MAR-05:10 | 5.60 | 5.26 |
April | 0.326995E+10 | 4086.61 | 27-APR-12:00 | 25.00 | 15.46 | 0.601329E+09 | 364.32 | 17-APR-02:39 | 25.00 | 15.46 |
May | 0.388174E+10 | 4006.43 | 04-MAY-13:00 | 22.20 | 15.27 | 0.621396E+09 | 364.30 | 18-MAY-01:19 | 6.10 | 4.99 |
June | 0.413721E+10 | 3617.86 | 28-JUN-12:10 | 23.07 | 15.49 | 0.601971E+09 | 364.27 | 30-JUN-02:00 | 13.90 | 11.64 |
July | 0.501935E+10 | 3990.35 | 31-JUL-15:13 | 28.50 | 19.00 | 0.620116E+09 | 364.28 | 01-JUL-01:10 | 28.50 | 19.00 |
August | 0.524375E+10 | 4555.60 | 24-AUG-10:35 | 24.93 | 18.02 | 0.624098E+09 | 364.27 | 02-AUG-04:00 | 24.93 | 18.02 |
September | 0.438868E+10 | 4558.22 | 10-SEP-10:40 | 18.33 | 13.89 | 0.603166E+09 | 364.33 | 28-SEP-03:20 | 8.50 | 7.83 |
October | 0.315594E+10 | 4633.44 | 04-OCT-10:35 | 18.33 | 11.02 | 0.621372E+09 | 364.31 | 26-OCT-03:49 | 12.88 | 11.68 |
November | 0.140703E+10 | 4129.57 | 04-NOV-10:35 | 17.23 | 14.47 | 0.598594E+09 | 364.35 | 29-NOV-02:49 | 9.40 | 8.05 |
December | 0.971623E+09 | 4003.28 | 05-DEC-11:40 | 9.43 | 5.86 | 0.614234E+09 | 364.32 | 07-DEC-02:00 | 3.90 | 2.46 |
Annual Sum or Average | 0.362630E+11 | 0.730087E+10 | ||||||||
Minimum of Months | 0.748273E+09 | 3534.52 | 5.60 | 0.67 | 0.557794E+09 | 364.27 | 3.90 | 2.46 | ||
Maximum of Months | 0.524375E+10 | 4633.44 | 28.50 | 19.00 | 0.624098E+09 | 364.38 | 28.50 | 19.00 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.242077E+10 | 1732.88 | 11-JAN-21:00 | 11.10 | 10.22 | 0.717515E+09 | 429.75 | 11-JAN-22:19 | 10.53 | 9.73 |
February | 0.242239E+10 | 1824.90 | 27-FEB-20:10 | 13.62 | 10.69 | 0.649457E+09 | 442.00 | 27-FEB-22:19 | 12.20 | 10.16 |
March | 0.298797E+10 | 1865.66 | 14-MAR-20:00 | 14.40 | 9.49 | 0.723041E+09 | 446.30 | 14-MAR-21:19 | 12.60 | 8.62 |
April | 0.318012E+10 | 2138.50 | 27-APR-18:10 | 25.55 | 15.86 | 0.699675E+09 | 459.00 | 27-APR-21:40 | 15.33 | 11.23 |
May | 0.351934E+10 | 2109.04 | 04-MAY-18:10 | 22.70 | 14.48 | 0.725621E+09 | 459.44 | 04-MAY-22:10 | 18.43 | 12.09 |
June | 0.356086E+10 | 2179.71 | 28-JUN-18:03 | 25.40 | 16.48 | 0.705071E+09 | 460.76 | 28-JUN-22:10 | 17.75 | 13.83 |
July | 0.390815E+10 | 2242.32 | 24-JUL-18:10 | 28.72 | 17.86 | 0.728821E+09 | 464.92 | 31-JUL-22:10 | 20.05 | 15.96 |
August | 0.394502E+10 | 2255.18 | 10-AUG-18:10 | 30.57 | 19.31 | 0.733551E+09 | 470.03 | 10-AUG-22:10 | 21.82 | 15.74 |
September | 0.355660E+10 | 2107.67 | 13-SEP-18:10 | 22.43 | 16.15 | 0.703027E+09 | 460.97 | 12-SEP-21:40 | 22.43 | 16.15 |
October | 0.320201E+10 | 1983.61 | 04-OCT-18:10 | 17.52 | 10.01 | 0.721217E+09 | 454.50 | 04-OCT-22:10 | 15.73 | 10.00 |
November | 0.265176E+10 | 1797.73 | 02-NOV-18:45 | 12.62 | 10.38 | 0.694709E+09 | 434.82 | 02-NOV-21:19 | 11.70 | 9.97 |
December | 0.249256E+10 | 1734.17 | 05-DEC-21:00 | 5.60 | 1.73 | 0.717583E+09 | 429.71 | 05-DEC-22:19 | 4.80 | 2.06 |
Annual Sum or Average | 0.378475E+11 | 0.851929E+10 | ||||||||
Minimum of Months | 0.242077E+10 | 1732.88 | 5.60 | 1.73 | 0.649457E+09 | 429.71 | 4.80 | 2.06 | ||
Maximum of Months | 0.394502E+10 | 2255.18 | 30.57 | 19.31 | 0.733551E+09 | 470.03 | 22.43 | 16.15 |
Report: ZoneCoolingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.108822E+10 | 1460.09 | 11-JAN-21:00 | 11.10 | 10.22 | 0.151697E+09 | 89.15 | 12-JAN-03:20 | 7.60 | 7.06 |
February | 0.122890E+10 | 1648.40 | 27-FEB-21:00 | 12.20 | 10.06 | 0.137154E+09 | 89.56 | 27-FEB-22:10 | 12.20 | 10.11 |
March | 0.181467E+10 | 1671.62 | 10-MAR-21:00 | 11.70 | 11.07 | 0.152415E+09 | 90.48 | 09-MAR-22:10 | 11.70 | 11.07 |
April | 0.217600E+10 | 1905.38 | 27-APR-19:00 | 22.80 | 15.42 | 0.147134E+09 | 92.11 | 27-APR-21:10 | 16.73 | 11.41 |
May | 0.265405E+10 | 1900.34 | 15-MAY-18:50 | 20.18 | 12.22 | 0.152310E+09 | 92.87 | 05-MAY-21:10 | 20.18 | 12.22 |
June | 0.290692E+10 | 2009.98 | 28-JUN-18:30 | 25.00 | 16.17 | 0.147937E+09 | 93.33 | 28-JUN-22:10 | 17.75 | 13.83 |
July | 0.328762E+10 | 2107.40 | 24-JUL-18:10 | 28.72 | 17.86 | 0.152551E+09 | 94.62 | 24-JUL-22:10 | 20.40 | 15.71 |
August | 0.336888E+10 | 2130.82 | 10-AUG-18:10 | 30.57 | 19.31 | 0.153375E+09 | 94.94 | 10-AUG-22:10 | 21.82 | 15.74 |
September | 0.273774E+10 | 1913.56 | 14-SEP-18:30 | 21.15 | 15.98 | 0.147354E+09 | 92.72 | 12-SEP-21:10 | 21.15 | 15.98 |
October | 0.219635E+10 | 1769.03 | 04-OCT-19:10 | 16.28 | 9.39 | 0.151817E+09 | 90.88 | 04-OCT-21:10 | 14.27 | 9.23 |
November | 0.158037E+10 | 1619.69 | 03-NOV-20:00 | 15.00 | 14.31 | 0.146743E+09 | 89.31 | 06-NOV-22:10 | 15.10 | 14.35 |
December | 0.119124E+10 | 1412.63 | 29-DEC-21:00 | 9.40 | 7.72 | 0.151697E+09 | 89.15 | 14-DEC-05:00 | 9.40 | 7.72 |
Annual Sum or Average | 0.262309E+11 | 0.179218E+10 | ||||||||
Minimum of Months | 0.108822E+10 | 1412.63 | 9.40 | 7.72 | 0.137154E+09 | 89.15 | 7.60 | 7.06 | ||
Maximum of Months | 0.336888E+10 | 2130.82 | 30.57 | 19.31 | 0.153375E+09 | 94.94 | 21.82 | 15.98 |
Report: ZoneCoolingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.137235E+09 | 419.69 | 11-JAN-22:00 | 11.10 | 10.49 | 0.116691E+09 | 68.57 | 06-JAN-01:39 | 11.10 | 10.49 |
February | 0.242975E+09 | 540.80 | 27-FEB-21:50 | 12.20 | 10.06 | 0.105501E+09 | 68.58 | 27-FEB-03:49 | 12.20 | 10.06 |
March | 0.483989E+09 | 531.04 | 10-MAR-22:00 | 11.70 | 11.07 | 0.117239E+09 | 68.58 | 24-MAR-04:40 | 2.97 | 0.38 |
April | 0.729846E+09 | 763.65 | 27-APR-21:00 | 17.20 | 11.44 | 0.113126E+09 | 68.58 | 01-APR-01:19 | 17.20 | 11.44 |
May | 0.100567E+10 | 804.08 | 05-MAY-21:00 | 18.90 | 12.98 | 0.116938E+09 | 68.81 | 05-MAY-21:40 | 18.17 | 12.81 |
June | 0.118701E+10 | 870.08 | 28-JUN-19:50 | 22.15 | 15.40 | 0.113381E+09 | 69.30 | 28-JUN-22:10 | 17.75 | 13.83 |
July | 0.140871E+10 | 961.71 | 24-JUL-19:05 | 27.15 | 17.29 | 0.116732E+09 | 70.32 | 24-JUL-22:10 | 20.40 | 15.71 |
August | 0.145754E+10 | 984.97 | 10-AUG-19:10 | 29.18 | 18.39 | 0.117292E+09 | 70.58 | 10-AUG-22:10 | 21.82 | 15.74 |
September | 0.107811E+10 | 807.78 | 12-SEP-21:00 | 19.40 | 14.73 | 0.113073E+09 | 68.79 | 12-SEP-21:40 | 18.67 | 14.43 |
October | 0.716619E+09 | 660.72 | 04-OCT-20:10 | 16.65 | 10.41 | 0.116746E+09 | 68.57 | 14-OCT-03:00 | 9.40 | 8.56 |
November | 0.364874E+09 | 527.63 | 04-NOV-20:40 | 15.57 | 13.61 | 0.112879E+09 | 68.58 | 13-NOV-23:40 | 4.43 | 1.21 |
December | 0.157950E+09 | 374.77 | 29-DEC-22:00 | 8.90 | 7.51 | 0.116691E+09 | 68.58 | 13-DEC-04:30 | 8.90 | 7.51 |
Annual Sum or Average | 0.897053E+10 | 0.137629E+10 | ||||||||
Minimum of Months | 0.137235E+09 | 374.77 | 8.90 | 7.51 | 0.105501E+09 | 68.57 | 2.97 | 0.38 | ||
Maximum of Months | 0.145754E+10 | 984.97 | 29.18 | 18.39 | 0.117292E+09 | 70.58 | 21.82 | 15.74 |
Report: ZoneCoolingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.488522E+11 | 35831.19 | 11-JAN-21:00 | 11.10 | 10.22 | 0.511187E+09 | 381.95 | 11-JAN-22:10 | 10.82 | 10.11 |
February | 0.445687E+11 | 36089.18 | 27-FEB-21:00 | 12.20 | 10.06 | 0.462045E+09 | 385.46 | 23-FEB-22:10 | 12.20 | 10.06 |
March | 0.501727E+11 | 36251.33 | 14-MAR-20:00 | 14.40 | 9.49 | 0.513771E+09 | 394.25 | 09-MAR-22:10 | 14.40 | 9.49 |
April | 0.491726E+11 | 36902.23 | 27-APR-20:00 | 19.40 | 13.66 | 0.494050E+09 | 385.62 | 28-APR-21:10 | 12.20 | 10.91 |
May | 0.514422E+11 | 36839.49 | 04-MAY-20:00 | 19.40 | 13.12 | 0.510644E+09 | 383.28 | 02-MAY-21:10 | 19.40 | 13.12 |
June | 0.504319E+11 | 37137.76 | 28-JUN-20:00 | 21.70 | 15.30 | 0.494539E+09 | 382.01 | 14-JUN-21:10 | 21.70 | 15.30 |
July | 0.523160E+11 | 37381.42 | 24-JUL-20:00 | 23.90 | 16.63 | 0.507313E+09 | 381.85 | 28-JUL-21:10 | 15.92 | 13.07 |
August | 0.526891E+11 | 37462.14 | 10-AUG-20:00 | 25.60 | 17.66 | 0.510987E+09 | 381.87 | 04-AUG-21:10 | 25.60 | 17.66 |
September | 0.499847E+11 | 36913.51 | 14-SEP-20:00 | 18.90 | 14.81 | 0.493301E+09 | 392.06 | 19-SEP-21:10 | 12.70 | 10.28 |
October | 0.505661E+11 | 36480.76 | 04-OCT-20:00 | 17.20 | 10.66 | 0.510772E+09 | 392.52 | 06-OCT-21:10 | 12.70 | 10.58 |
November | 0.481155E+11 | 36020.83 | 03-NOV-20:00 | 15.00 | 14.31 | 0.494445E+09 | 381.98 | 02-NOV-21:10 | 15.00 | 14.31 |
December | 0.489414E+11 | 35737.46 | 29-DEC-21:00 | 9.40 | 7.72 | 0.510711E+09 | 381.90 | 05-DEC-22:10 | 9.40 | 7.72 |
Annual Sum or Average | 0.597253E+12 | 0.601376E+10 | ||||||||
Minimum of Months | 0.445687E+11 | 35737.46 | 9.40 | 7.72 | 0.462045E+09 | 381.85 | 9.40 | 7.72 | ||
Maximum of Months | 0.526891E+11 | 37462.14 | 25.60 | 17.66 | 0.513771E+09 | 394.25 | 25.60 | 17.66 |
Report: ZoneCoolingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.153537E+11 | 13458.14 | 20-JAN-13:10 | 6.70 | 4.72 | 0.814235E+10 | 4789.83 | 31-JAN-04:19 | 4.60 | 4.02 |
February | 0.167015E+11 | 15427.71 | 12-FEB-11:35 | 5.60 | 0.67 | 0.736683E+10 | 4790.19 | 18-FEB-04:10 | -1.1 | -2.0 |
March | 0.208116E+11 | 16417.70 | 02-MAR-11:35 | 9.63 | 6.30 | 0.819186E+10 | 4833.78 | 14-MAR-21:19 | 12.60 | 8.62 |
April | 0.223917E+11 | 15398.11 | 27-APR-15:13 | 27.20 | 17.16 | 0.790004E+10 | 4908.96 | 27-APR-21:30 | 15.80 | 11.30 |
May | 0.242852E+11 | 15243.44 | 04-MAY-15:13 | 24.23 | 14.78 | 0.816442E+10 | 4908.42 | 04-MAY-21:30 | 18.35 | 12.20 |
June | 0.245105E+11 | 13592.57 | 28-JUN-15:02 | 26.10 | 15.67 | 0.791250E+10 | 4881.61 | 20-JUN-21:30 | 26.10 | 15.67 |
July | 0.271103E+11 | 15184.06 | 31-JUL-15:13 | 28.50 | 19.00 | 0.814868E+10 | 4985.11 | 24-JUL-21:40 | 28.50 | 19.00 |
August | 0.279009E+11 | 16461.66 | 24-AUG-15:13 | 29.63 | 19.05 | 0.820232E+10 | 5046.97 | 24-AUG-21:30 | 22.80 | 17.46 |
September | 0.252731E+11 | 16489.41 | 14-SEP-15:13 | 24.07 | 16.99 | 0.791825E+10 | 4978.06 | 12-SEP-21:30 | 24.07 | 16.99 |
October | 0.225240E+11 | 17036.87 | 04-OCT-10:35 | 18.33 | 11.02 | 0.816131E+10 | 4927.35 | 04-OCT-21:30 | 15.00 | 9.56 |
November | 0.170621E+11 | 15252.41 | 04-NOV-13:00 | 20.60 | 16.05 | 0.788031E+10 | 4789.78 | 02-NOV-04:00 | 20.60 | 16.05 |
December | 0.159737E+11 | 15059.38 | 02-DEC-11:35 | 11.83 | 6.03 | 0.814164E+10 | 4790.15 | 21-DEC-05:49 | 1.88 | 1.64 |
Annual Sum or Average | 0.259898E+12 | 0.961305E+11 | ||||||||
Minimum of Months | 0.153537E+11 | 13458.14 | 5.60 | 0.67 | 0.736683E+10 | 4789.78 | -1.1 | -2.0 | ||
Maximum of Months | 0.279009E+11 | 17036.87 | 29.63 | 19.05 | 0.820232E+10 | 5046.97 | 28.50 | 19.00 |
Report: ZoneCoolingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.622612E+11 | 37335.70 | 11-JAN-22:00 | 11.10 | 10.49 | 0.242033E+11 | 14806.87 | 11-JAN-22:40 | 9.97 | 8.97 |
February | 0.611484E+11 | 39325.84 | 27-FEB-20:10 | 13.62 | 10.69 | 0.219184E+11 | 15180.65 | 27-FEB-22:40 | 12.20 | 10.25 |
March | 0.728897E+11 | 40053.88 | 14-MAR-20:00 | 14.40 | 9.49 | 0.244213E+11 | 15277.71 | 14-MAR-21:49 | 12.30 | 8.36 |
April | 0.751555E+11 | 44524.89 | 27-APR-18:30 | 24.45 | 15.73 | 0.236362E+11 | 15569.24 | 27-APR-21:40 | 15.33 | 11.23 |
May | 0.808469E+11 | 43757.09 | 04-MAY-18:15 | 22.60 | 14.48 | 0.245244E+11 | 15590.65 | 04-MAY-22:10 | 18.43 | 12.09 |
June | 0.808126E+11 | 45179.54 | 28-JUN-18:30 | 25.00 | 16.17 | 0.238821E+11 | 15616.81 | 28-JUN-22:10 | 17.75 | 13.83 |
July | 0.868800E+11 | 46918.52 | 24-JUL-18:17 | 28.53 | 17.76 | 0.246817E+11 | 15777.60 | 24-JUL-21:49 | 20.97 | 15.91 |
August | 0.882162E+11 | 47357.85 | 10-AUG-18:20 | 30.43 | 19.14 | 0.248838E+11 | 15885.23 | 08-AUG-21:49 | 30.43 | 19.14 |
September | 0.812675E+11 | 44653.54 | 14-SEP-18:02 | 21.52 | 16.29 | 0.238046E+11 | 15700.22 | 12-SEP-21:40 | 21.52 | 16.29 |
October | 0.765659E+11 | 42335.38 | 04-OCT-18:03 | 17.52 | 10.01 | 0.243841E+11 | 15537.05 | 04-OCT-22:10 | 15.73 | 10.00 |
November | 0.654799E+11 | 39409.81 | 02-NOV-18:45 | 12.62 | 10.38 | 0.234516E+11 | 15004.11 | 02-NOV-21:40 | 11.70 | 10.07 |
December | 0.635863E+11 | 37297.97 | 05-DEC-20:50 | 5.87 | 1.94 | 0.242038E+11 | 14789.10 | 05-DEC-22:40 | 4.60 | 2.18 |
Annual Sum or Average | 0.895110E+12 | 0.287995E+12 | ||||||||
Minimum of Months | 0.611484E+11 | 37297.97 | 5.87 | 1.94 | 0.219184E+11 | 14789.10 | 4.60 | 2.18 | ||
Maximum of Months | 0.882162E+11 | 47357.85 | 30.43 | 19.14 | 0.248838E+11 | 15885.23 | 30.43 | 19.14 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 97021884.61 | 2328.35 | 20-JAN-16:02 | 5.40 | 3.78 | 93307078.65 | 56.69 | 11-JAN-22:19 | 5.40 | 3.78 |
February | 0.180652E+09 | 3722.87 | 12-FEB-16:01 | 6.52 | 1.59 | 85534107.87 | 56.69 | 27-FEB-22:10 | 12.20 | 10.11 |
March | 0.376549E+09 | 3756.82 | 18-MAR-15:02 | 20.10 | 10.35 | 96179245.24 | 56.69 | 18-MAR-23:00 | 9.40 | 7.98 |
April | 0.793638E+09 | 3784.18 | 01-APR-18:01 | 25.13 | 11.98 | 94241021.70 | 56.69 | 28-APR-01:10 | 14.03 | 11.94 |
May | 0.124368E+10 | 3859.50 | 14-MAY-15:02 | 23.30 | 12.38 | 98130666.54 | 56.69 | 07-MAY-00:10 | 23.30 | 12.38 |
June | 0.140706E+10 | 3739.09 | 01-JUN-18:02 | 17.70 | 10.65 | 95287251.35 | 56.70 | 20-JUN-21:10 | 19.13 | 13.67 |
July | 0.202250E+10 | 3683.29 | 28-JUL-15:02 | 20.00 | 14.95 | 98607883.02 | 56.70 | 31-JUL-21:49 | 20.53 | 16.28 |
August | 0.196150E+10 | 3655.09 | 29-AUG-18:02 | 30.20 | 18.77 | 98637065.30 | 56.70 | 24-AUG-22:10 | 30.20 | 18.77 |
September | 0.136938E+10 | 3632.42 | 13-SEP-18:02 | 22.43 | 16.15 | 94835004.79 | 56.69 | 12-SEP-23:00 | 22.43 | 16.15 |
October | 0.565034E+09 | 3850.67 | 04-OCT-15:02 | 21.60 | 11.48 | 96650711.08 | 56.69 | 04-OCT-21:10 | 14.27 | 9.23 |
November | 0.155498E+09 | 3659.13 | 11-NOV-16:01 | 6.42 | 5.03 | 91500728.60 | 56.69 | 04-NOV-23:40 | 6.42 | 5.03 |
December | 97610546.23 | 3528.21 | 05-DEC-16:02 | 6.10 | 4.53 | 93701427.28 | 56.69 | 29-DEC-00:20 | 9.40 | 9.05 |
Annual Sum or Average | 0.102701E+11 | 0.113661E+10 | ||||||||
Minimum of Months | 97021884.61 | 2328.35 | 5.40 | 1.59 | 85534107.87 | 56.69 | 5.40 | 3.78 | ||
Maximum of Months | 0.202250E+10 | 3859.50 | 30.20 | 18.77 | 98637065.30 | 56.70 | 30.20 | 18.77 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 69621729.03 | 520.39 | 11-JAN-19:05 | 12.30 | 9.41 | 92763203.75 | 56.69 | 11-JAN-22:19 | 10.53 | 9.73 |
February | 0.106111E+09 | 2769.52 | 06-FEB-16:01 | 7.70 | 4.98 | 84669145.37 | 56.69 | 27-FEB-23:19 | 12.20 | 10.44 |
March | 0.218536E+09 | 3388.09 | 01-MAR-16:01 | 12.20 | 6.79 | 95221101.80 | 56.69 | 18-MAR-23:30 | 10.00 | 8.01 |
April | 0.576560E+09 | 3482.76 | 02-APR-15:01 | 20.60 | 11.87 | 93574190.66 | 56.69 | 28-APR-21:10 | 12.20 | 10.91 |
May | 0.104851E+10 | 3513.70 | 14-MAY-15:02 | 23.30 | 12.38 | 97802454.78 | 56.69 | 30-MAY-21:10 | 13.90 | 12.05 |
June | 0.126020E+10 | 3433.72 | 01-JUN-18:02 | 17.70 | 10.65 | 95050858.95 | 56.69 | 20-JUN-21:10 | 19.13 | 13.67 |
July | 0.180344E+10 | 3402.32 | 26-JUL-15:02 | 22.30 | 16.93 | 98443961.41 | 56.70 | 31-JUL-21:49 | 20.53 | 16.28 |
August | 0.166534E+10 | 3372.65 | 10-AUG-18:02 | 30.57 | 19.31 | 98422456.81 | 56.70 | 09-AUG-21:49 | 30.57 | 19.31 |
September | 0.100696E+10 | 3321.89 | 23-SEP-15:02 | 23.30 | 17.17 | 94399099.01 | 56.69 | 15-SEP-21:40 | 23.30 | 17.17 |
October | 0.324475E+09 | 3461.01 | 04-OCT-15:02 | 21.60 | 11.48 | 95705941.06 | 56.69 | 04-OCT-22:10 | 15.73 | 10.00 |
November | 0.108670E+09 | 3154.07 | 04-NOV-15:02 | 20.92 | 15.94 | 90850386.36 | 56.69 | 06-NOV-22:19 | 15.20 | 14.40 |
December | 68332315.81 | 595.34 | 28-DEC-19:05 | 10.60 | 9.36 | 92965588.40 | 56.69 | 29-DEC-00:20 | 9.40 | 9.05 |
Annual Sum or Average | 0.825676E+10 | 0.112987E+10 | ||||||||
Minimum of Months | 68332315.81 | 520.39 | 7.70 | 4.98 | 84669145.37 | 56.69 | 9.40 | 8.01 | ||
Maximum of Months | 0.180344E+10 | 3513.70 | 30.57 | 19.31 | 98443961.41 | 56.70 | 30.57 | 19.31 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.226825E+09 | 190.99 | 07-JAN-08:50 | -3.4 | -3.6 | 0.00 | 0.00 | 01-JAN-00:10 | -3.4 | -3.6 |
February | 0.316278E+09 | 620.12 | 08-FEB-13:50 | 6.60 | 3.81 | 0.00 | 0.00 | 01-FEB-00:10 | 6.60 | 3.81 |
March | 0.452935E+09 | 766.14 | 02-MAR-13:00 | 12.20 | 7.34 | 0.00 | 0.00 | 01-MAR-00:10 | 12.20 | 7.34 |
April | 0.535201E+09 | 734.75 | 27-APR-13:00 | 26.10 | 16.28 | 0.00 | 0.00 | 01-APR-00:10 | 26.10 | 16.28 |
May | 0.595584E+09 | 713.57 | 04-MAY-13:20 | 22.77 | 15.31 | 0.00 | 0.00 | 01-MAY-00:10 | 22.77 | 15.31 |
June | 0.609420E+09 | 567.52 | 28-JUN-13:10 | 24.50 | 15.71 | 0.00 | 0.00 | 01-JUN-00:10 | 24.50 | 15.71 |
July | 0.754424E+09 | 679.24 | 31-JUL-13:20 | 27.57 | 18.47 | 0.00 | 0.00 | 01-JUL-00:10 | 27.57 | 18.47 |
August | 0.819527E+09 | 820.42 | 24-AUG-13:00 | 28.90 | 19.37 | 0.00 | 0.00 | 01-AUG-00:10 | 28.90 | 19.37 |
September | 0.734250E+09 | 866.44 | 23-SEP-13:30 | 22.75 | 17.56 | 0.00 | 0.00 | 01-SEP-00:10 | 22.75 | 17.56 |
October | 0.560303E+09 | 904.19 | 04-OCT-12:30 | 20.60 | 11.38 | 0.00 | 0.00 | 01-OCT-00:10 | 20.60 | 11.38 |
November | 0.313035E+09 | 760.92 | 04-NOV-13:30 | 20.85 | 16.00 | 0.00 | 0.00 | 01-NOV-00:10 | 20.85 | 16.00 |
December | 0.256842E+09 | 604.17 | 05-DEC-12:30 | 10.30 | 6.13 | 0.00 | 0.00 | 01-DEC-00:10 | 10.30 | 6.13 |
Annual Sum or Average | 0.617462E+10 | 0.00 | ||||||||
Minimum of Months | 0.226825E+09 | 190.99 | -3.4 | -3.6 | 0.00 | 0.00 | -3.4 | -3.6 | ||
Maximum of Months | 0.819527E+09 | 904.19 | 28.90 | 19.37 | 0.00 | 0.00 | 28.90 | 19.37 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.186384E+09 | 871.20 | 28-JAN-09:02 | 6.78 | 5.21 | 94500866.59 | 56.69 | 11-JAN-22:19 | 6.78 | 5.21 |
February | 0.219468E+09 | 915.85 | 25-FEB-09:02 | 11.88 | 10.94 | 85874423.57 | 56.69 | 24-FEB-22:10 | 11.88 | 10.94 |
March | 0.360315E+09 | 967.32 | 18-MAR-15:02 | 20.10 | 10.35 | 96168228.97 | 56.69 | 18-MAR-23:00 | 9.40 | 7.98 |
April | 0.492623E+09 | 1047.92 | 01-APR-18:01 | 25.13 | 11.98 | 93736404.25 | 56.69 | 26-APR-21:30 | 14.20 | 10.54 |
May | 0.648912E+09 | 1067.26 | 14-MAY-18:02 | 21.83 | 11.88 | 97501152.57 | 56.69 | 26-MAY-22:10 | 10.92 | 10.92 |
June | 0.728745E+09 | 1075.92 | 09-JUN-18:02 | 22.70 | 13.21 | 94607718.45 | 56.69 | 12-JUN-21:10 | 15.00 | 13.00 |
July | 0.824471E+09 | 1057.22 | 30-JUL-18:02 | 26.32 | 17.50 | 97794196.57 | 56.69 | 24-JUL-21:00 | 26.32 | 17.50 |
August | 0.805213E+09 | 1045.16 | 08-AUG-15:02 | 30.25 | 18.18 | 97815712.33 | 56.69 | 28-AUG-21:10 | 20.03 | 15.28 |
September | 0.605679E+09 | 1024.32 | 14-SEP-18:02 | 21.52 | 16.29 | 94021524.53 | 56.69 | 25-SEP-21:30 | 13.90 | 13.52 |
October | 0.438101E+09 | 989.52 | 02-OCT-18:01 | 14.32 | 8.97 | 96442490.55 | 56.69 | 26-OCT-21:10 | 11.70 | 10.71 |
November | 0.286162E+09 | 912.26 | 05-NOV-08:62 | 12.88 | 12.19 | 92435331.10 | 56.69 | 07-NOV-22:10 | 10.60 | 9.77 |
December | 0.185354E+09 | 932.08 | 03-DEC-09:02 | 7.98 | 3.60 | 94676086.20 | 56.69 | 28-DEC-22:19 | 9.77 | 8.96 |
Annual Sum or Average | 0.578143E+10 | 0.113557E+10 | ||||||||
Minimum of Months | 0.185354E+09 | 871.20 | 6.78 | 3.60 | 85874423.57 | 56.69 | 6.78 | 5.21 | ||
Maximum of Months | 0.824471E+09 | 1075.92 | 30.25 | 18.18 | 97815712.33 | 56.69 | 26.32 | 17.50 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 98894117.85 | 676.41 | 10-JAN-09:03 | 5.78 | 3.12 | 93224610.83 | 56.69 | 11-JAN-22:19 | 10.53 | 9.73 |
February | 0.175870E+09 | 3120.73 | 08-FEB-16:02 | 7.12 | 3.76 | 85551249.54 | 56.69 | 27-FEB-22:49 | 12.20 | 10.30 |
March | 0.373133E+09 | 3427.26 | 02-MAR-09:02 | 4.78 | 3.27 | 96370456.81 | 56.69 | 18-MAR-23:40 | 9.80 | 8.00 |
April | 0.813930E+09 | 3414.16 | 01-APR-18:01 | 25.13 | 11.98 | 94603411.75 | 56.69 | 28-APR-01:10 | 14.03 | 11.94 |
May | 0.110768E+10 | 3441.11 | 14-MAY-15:02 | 23.30 | 12.38 | 98209121.08 | 56.69 | 07-MAY-01:10 | 23.30 | 12.38 |
June | 0.148675E+10 | 3380.80 | 08-JUN-18:01 | 18.72 | 11.48 | 95531233.09 | 56.69 | 26-JUN-21:40 | 14.97 | 12.74 |
July | 0.177948E+10 | 3334.36 | 13-JUL-15:02 | 22.20 | 15.22 | 98715511.44 | 56.70 | 24-JUL-21:49 | 20.97 | 15.91 |
August | 0.192709E+10 | 3386.79 | 24-AUG-08:62 | 20.48 | 16.29 | 98819718.55 | 56.70 | 09-AUG-21:40 | 20.48 | 16.29 |
September | 0.125864E+10 | 3366.51 | 14-SEP-08:61 | 15.87 | 14.39 | 94808993.78 | 56.69 | 22-SEP-21:40 | 16.33 | 14.44 |
October | 0.556941E+09 | 3433.26 | 04-OCT-15:02 | 21.60 | 11.48 | 96782672.87 | 56.69 | 04-OCT-21:10 | 14.27 | 9.23 |
November | 0.161930E+09 | 3155.30 | 04-NOV-15:02 | 20.92 | 15.94 | 91463276.64 | 56.69 | 06-NOV-22:10 | 15.10 | 14.35 |
December | 0.106283E+09 | 1844.92 | 02-DEC-09:02 | 8.58 | 4.35 | 93615646.52 | 56.69 | 29-DEC-00:20 | 9.40 | 9.05 |
Annual Sum or Average | 0.984662E+10 | 0.113770E+10 | ||||||||
Minimum of Months | 98894117.85 | 676.41 | 4.78 | 3.12 | 85551249.54 | 56.69 | 9.40 | 8.00 | ||
Maximum of Months | 0.192709E+10 | 3441.11 | 25.13 | 16.29 | 98819718.55 | 56.70 | 23.30 | 16.29 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 63661058.30 | 575.94 | 10-JAN-09:05 | 5.78 | 3.12 | 92721307.48 | 56.69 | 11-JAN-00:20 | 9.07 | 5.86 |
February | 0.103258E+09 | 1980.14 | 27-FEB-16:01 | 19.32 | 12.38 | 84611736.93 | 56.69 | 27-FEB-22:19 | 12.20 | 10.16 |
March | 0.203613E+09 | 3020.08 | 02-MAR-09:02 | 4.78 | 3.27 | 95399184.54 | 56.69 | 18-MAR-23:10 | 10.40 | 8.02 |
April | 0.583089E+09 | 3150.57 | 02-APR-15:01 | 20.60 | 11.87 | 94050883.22 | 56.69 | 29-APR-23:00 | 15.00 | 12.75 |
May | 0.906369E+09 | 3155.40 | 14-MAY-15:02 | 23.30 | 12.38 | 97971929.32 | 56.69 | 07-MAY-01:10 | 23.30 | 12.38 |
June | 0.132684E+10 | 3140.19 | 01-JUN-15:01 | 18.12 | 10.68 | 95438984.28 | 56.69 | 26-JUN-21:40 | 14.97 | 12.74 |
July | 0.155313E+10 | 3088.73 | 24-JUL-18:02 | 28.72 | 17.86 | 98643128.93 | 56.70 | 24-JUL-21:00 | 20.60 | 15.77 |
August | 0.161906E+10 | 3127.81 | 08-AUG-08:62 | 20.10 | 16.33 | 98706648.77 | 56.70 | 23-AUG-21:10 | 21.53 | 16.21 |
September | 0.885774E+09 | 3062.88 | 10-SEP-08:61 | 14.68 | 12.94 | 94449901.54 | 56.69 | 13-SEP-22:40 | 17.97 | 14.51 |
October | 0.311043E+09 | 3056.37 | 04-OCT-15:02 | 21.60 | 11.48 | 95851186.31 | 56.69 | 04-OCT-21:19 | 14.63 | 9.40 |
November | 0.106898E+09 | 2163.05 | 04-NOV-15:02 | 20.92 | 15.94 | 90808531.38 | 56.69 | 06-NOV-22:19 | 15.20 | 14.40 |
December | 67729284.74 | 596.26 | 03-DEC-09:04 | 7.98 | 3.60 | 92886075.49 | 56.69 | 29-DEC-00:10 | 9.40 | 9.10 |
Annual Sum or Average | 0.773046E+10 | 0.113154E+10 | ||||||||
Minimum of Months | 63661058.30 | 575.94 | 4.78 | 3.12 | 84611736.93 | 56.69 | 9.07 | 5.86 | ||
Maximum of Months | 0.161906E+10 | 3155.40 | 28.72 | 17.86 | 98706648.77 | 56.70 | 23.30 | 16.21 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.127899E+10 | 1547.28 | 11-JAN-22:03 | 10.82 | 10.11 | 0.119882E+10 | 704.49 | 06-JAN-00:00 | 10.82 | 10.11 |
February | 0.195980E+10 | 2225.47 | 27-FEB-16:30 | 19.15 | 12.30 | 0.108388E+10 | 706.96 | 27-FEB-22:40 | 12.20 | 10.25 |
March | 0.320098E+10 | 2558.88 | 18-MAR-17:13 | 19.03 | 9.50 | 0.120462E+10 | 711.34 | 14-MAR-21:40 | 19.03 | 9.50 |
April | 0.410546E+10 | 2951.64 | 27-APR-18:10 | 25.55 | 15.86 | 0.116457E+10 | 737.93 | 27-APR-21:40 | 15.33 | 11.23 |
May | 0.494082E+10 | 2961.15 | 06-MAY-10:35 | 20.93 | 16.16 | 0.120665E+10 | 735.52 | 04-MAY-21:49 | 20.93 | 16.16 |
June | 0.529764E+10 | 3012.18 | 28-JUN-18:10 | 25.40 | 16.48 | 0.117407E+10 | 742.92 | 28-JUN-21:40 | 17.77 | 13.93 |
July | 0.593402E+10 | 3177.92 | 24-JUL-18:10 | 28.72 | 17.86 | 0.122095E+10 | 761.14 | 24-JUL-21:40 | 21.33 | 16.04 |
August | 0.604159E+10 | 3236.03 | 13-AUG-10:35 | 24.17 | 17.28 | 0.123665E+10 | 773.29 | 10-AUG-21:40 | 24.17 | 17.28 |
September | 0.506000E+10 | 3050.00 | 14-SEP-10:40 | 19.43 | 16.41 | 0.117505E+10 | 754.70 | 14-SEP-21:40 | 17.57 | 14.62 |
October | 0.381497E+10 | 2854.00 | 04-OCT-10:35 | 18.33 | 11.02 | 0.120093E+10 | 731.72 | 04-OCT-21:49 | 15.73 | 9.88 |
November | 0.214517E+10 | 2420.61 | 04-NOV-16:20 | 19.63 | 15.46 | 0.115969E+10 | 704.48 | 29-NOV-05:10 | 8.30 | 6.37 |
December | 0.151774E+10 | 1685.58 | 03-DEC-13:00 | 12.20 | 6.58 | 0.119877E+10 | 704.49 | 20-DEC-02:30 | 3.05 | 2.30 |
Annual Sum or Average | 0.452972E+11 | 0.142246E+11 | ||||||||
Minimum of Months | 0.127899E+10 | 1547.28 | 10.82 | 6.58 | 0.108388E+10 | 704.48 | 3.05 | 2.30 | ||
Maximum of Months | 0.604159E+10 | 3236.03 | 28.72 | 17.86 | 0.123665E+10 | 773.29 | 24.17 | 17.28 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 64461969.95 | 2039.56 | 20-JAN-16:02 | 5.40 | 3.78 | 92841126.55 | 56.69 | 30-JAN-00:10 | 9.50 | 6.03 |
February | 0.149024E+09 | 3916.48 | 12-FEB-16:01 | 6.52 | 1.59 | 85116863.94 | 56.69 | 27-FEB-23:49 | 12.20 | 10.59 |
March | 0.360308E+09 | 3974.28 | 01-MAR-16:01 | 12.20 | 6.79 | 95840680.86 | 56.69 | 15-MAR-00:49 | 9.50 | 8.20 |
April | 0.824598E+09 | 4006.20 | 01-APR-18:01 | 25.13 | 11.98 | 94134244.01 | 56.69 | 28-APR-01:10 | 14.03 | 11.94 |
May | 0.135830E+10 | 4096.43 | 14-MAY-15:02 | 23.30 | 12.38 | 98150562.81 | 56.69 | 06-MAY-23:49 | 23.30 | 12.38 |
June | 0.157466E+10 | 3952.37 | 01-JUN-18:02 | 17.70 | 10.65 | 95359350.51 | 56.70 | 22-JUN-21:10 | 17.43 | 13.85 |
July | 0.229105E+10 | 4005.03 | 31-JUL-18:02 | 26.42 | 18.31 | 98638973.45 | 56.70 | 20-JUL-21:10 | 26.42 | 18.31 |
August | 0.219287E+10 | 3999.07 | 10-AUG-18:02 | 30.57 | 19.31 | 98673388.42 | 56.70 | 23-AUG-21:40 | 21.33 | 16.18 |
September | 0.147798E+10 | 3813.32 | 14-SEP-18:02 | 21.52 | 16.29 | 94823507.26 | 56.69 | 08-SEP-04:40 | 21.52 | 16.29 |
October | 0.539157E+09 | 4079.01 | 04-OCT-15:02 | 21.60 | 11.48 | 96384603.07 | 56.69 | 04-OCT-21:10 | 14.27 | 9.23 |
November | 0.132373E+09 | 3879.92 | 11-NOV-16:01 | 6.42 | 5.03 | 91016332.64 | 56.69 | 04-NOV-23:19 | 6.42 | 5.03 |
December | 68025560.64 | 3727.56 | 05-DEC-16:02 | 6.10 | 4.53 | 93265178.26 | 56.69 | 16-DEC-00:20 | 7.40 | 6.86 |
Annual Sum or Average | 0.110328E+11 | 0.113424E+10 | ||||||||
Minimum of Months | 64461969.95 | 2039.56 | 5.40 | 1.59 | 85116863.94 | 56.69 | 6.42 | 5.03 | ||
Maximum of Months | 0.229105E+10 | 4096.43 | 30.57 | 19.31 | 98673388.42 | 56.70 | 26.42 | 18.31 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 34909933.45 | 655.57 | 05-JAN-16:04 | 5.73 | 4.38 | 92459840.60 | 56.69 | 10-JAN-22:19 | 9.63 | 5.74 |
February | 77399233.98 | 2778.72 | 26-FEB-16:01 | 14.40 | 10.25 | 84284567.99 | 56.69 | 27-FEB-23:19 | 12.20 | 10.44 |
March | 0.196846E+09 | 3550.28 | 01-MAR-16:01 | 12.20 | 6.79 | 94849145.64 | 56.69 | 18-MAR-23:10 | 10.40 | 8.02 |
April | 0.591867E+09 | 3635.76 | 01-APR-18:01 | 25.13 | 11.98 | 93495956.55 | 56.69 | 27-APR-21:40 | 15.33 | 11.23 |
May | 0.114185E+10 | 3708.11 | 14-MAY-18:02 | 21.83 | 11.88 | 97902186.84 | 56.69 | 30-MAY-21:10 | 13.90 | 12.05 |
June | 0.140715E+10 | 3610.99 | 01-JUN-18:02 | 17.70 | 10.65 | 95228707.33 | 56.70 | 22-JUN-21:30 | 16.70 | 13.38 |
July | 0.204906E+10 | 3611.96 | 31-JUL-18:02 | 26.42 | 18.31 | 98564837.11 | 56.70 | 11-JUL-21:10 | 26.42 | 18.31 |
August | 0.186712E+10 | 3636.10 | 24-AUG-18:02 | 27.77 | 18.38 | 98541604.18 | 56.70 | 24-AUG-22:10 | 21.62 | 17.07 |
September | 0.107336E+10 | 3501.39 | 13-SEP-18:02 | 22.43 | 16.15 | 94487420.15 | 56.69 | 12-SEP-22:40 | 22.43 | 16.15 |
October | 0.294485E+09 | 3636.41 | 04-OCT-15:02 | 21.60 | 11.48 | 95412692.38 | 56.69 | 04-OCT-21:19 | 14.63 | 9.40 |
November | 81660185.51 | 3305.11 | 04-NOV-15:02 | 20.92 | 15.94 | 90395433.81 | 56.69 | 04-NOV-23:19 | 13.30 | 12.93 |
December | 40337916.62 | 707.90 | 03-DEC-16:03 | 10.92 | 4.95 | 92589184.53 | 56.69 | 12-DEC-04:10 | 1.52 | 1.52 |
Annual Sum or Average | 0.885604E+10 | 0.112821E+10 | ||||||||
Minimum of Months | 34909933.45 | 655.57 | 5.73 | 4.38 | 84284567.99 | 56.69 | 1.52 | 1.52 | ||
Maximum of Months | 0.204906E+10 | 3708.11 | 27.77 | 18.38 | 98564837.11 | 56.70 | 26.42 | 18.31 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.143187E+09 | 2452.36 | 07-JAN-16:01 | 2.70 | 1.25 | 94497054.58 | 56.69 | 11-JAN-22:19 | 10.53 | 9.73 |
February | 0.323102E+09 | 2449.42 | 12-FEB-16:01 | 6.52 | 1.59 | 86630651.06 | 56.69 | 27-FEB-22:10 | 12.20 | 10.11 |
March | 0.520958E+09 | 2463.08 | 18-MAR-15:02 | 20.10 | 10.35 | 97046236.49 | 56.69 | 14-MAR-22:10 | 20.10 | 10.35 |
April | 0.739314E+09 | 2442.36 | 01-APR-18:01 | 25.13 | 11.98 | 94751307.49 | 56.69 | 28-APR-21:30 | 12.20 | 10.91 |
May | 0.907064E+09 | 2443.43 | 20-MAY-15:01 | 17.80 | 10.39 | 98281483.14 | 56.69 | 08-MAY-21:49 | 17.80 | 10.39 |
June | 0.100657E+10 | 2363.78 | 08-JUN-18:01 | 18.72 | 11.48 | 95393977.98 | 56.69 | 28-JUN-23:40 | 14.27 | 12.18 |
July | 0.130443E+10 | 2362.07 | 24-JUL-18:02 | 28.72 | 17.86 | 98609100.19 | 56.70 | 24-JUL-21:40 | 21.33 | 16.04 |
August | 0.141288E+10 | 2374.50 | 24-AUG-15:02 | 29.62 | 19.18 | 98685898.81 | 56.70 | 09-AUG-22:10 | 29.62 | 19.18 |
September | 0.117827E+10 | 2436.43 | 14-SEP-15:02 | 23.98 | 16.97 | 95073887.33 | 56.70 | 12-SEP-21:30 | 23.98 | 16.97 |
October | 0.731917E+09 | 2516.15 | 04-OCT-15:02 | 21.60 | 11.48 | 97476402.76 | 56.69 | 25-OCT-21:30 | 13.85 | 12.44 |
November | 0.257831E+09 | 2430.60 | 11-NOV-16:01 | 6.42 | 5.03 | 92511596.29 | 56.69 | 06-NOV-22:40 | 6.42 | 5.03 |
December | 0.207662E+09 | 2445.35 | 06-DEC-16:01 | 2.93 | 2.59 | 94794396.02 | 56.69 | 29-DEC-22:19 | 8.90 | 7.59 |
Annual Sum or Average | 0.873319E+10 | 0.114375E+10 | ||||||||
Minimum of Months | 0.143187E+09 | 2362.07 | 2.70 | 1.25 | 86630651.06 | 56.69 | 6.42 | 5.03 | ||
Maximum of Months | 0.141288E+10 | 2516.15 | 29.62 | 19.18 | 98685898.81 | 56.70 | 29.62 | 19.18 |
Report: ZoneCoolingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.373985E+11 | 18815.09 | 11-JAN-23:00 | 9.40 | 8.23 | 0.151362E+11 | 9994.67 | 11-JAN-23:10 | 9.22 | 8.15 |
February | 0.348396E+11 | 19173.72 | 27-FEB-23:00 | 12.20 | 10.35 | 0.137614E+11 | 10128.35 | 27-FEB-23:10 | 12.20 | 10.40 |
March | 0.405898E+11 | 19318.41 | 08-MAR-23:15 | 13.33 | 9.21 | 0.154966E+11 | 10222.41 | 08-MAR-23:40 | 12.77 | 9.10 |
April | 0.412567E+11 | 21388.68 | 27-APR-18:10 | 25.55 | 15.86 | 0.150938E+11 | 10408.36 | 27-APR-21:40 | 15.33 | 11.23 |
May | 0.444471E+11 | 21302.88 | 31-MAY-18:10 | 20.40 | 14.89 | 0.158074E+11 | 10490.27 | 05-MAY-22:10 | 20.40 | 14.89 |
June | 0.443760E+11 | 22243.77 | 28-JUN-18:10 | 25.40 | 16.48 | 0.154979E+11 | 10559.73 | 28-JUN-22:10 | 17.75 | 13.83 |
July | 0.467516E+11 | 22733.26 | 24-JUL-18:10 | 28.72 | 17.86 | 0.160304E+11 | 10649.11 | 24-JUL-21:40 | 21.33 | 16.04 |
August | 0.466070E+11 | 22726.22 | 10-AUG-18:10 | 30.57 | 19.31 | 0.161067E+11 | 10671.86 | 10-AUG-22:10 | 21.82 | 15.74 |
September | 0.428827E+11 | 20841.51 | 13-SEP-18:10 | 22.43 | 16.15 | 0.152728E+11 | 10455.32 | 20-SEP-21:49 | 12.88 | 11.23 |
October | 0.414530E+11 | 19508.23 | 25-OCT-21:10 | 13.48 | 12.19 | 0.155204E+11 | 10250.61 | 04-OCT-22:10 | 13.48 | 12.19 |
November | 0.380382E+11 | 19275.97 | 06-NOV-23:00 | 15.60 | 14.58 | 0.148253E+11 | 10128.59 | 06-NOV-23:10 | 15.40 | 14.28 |
December | 0.376944E+11 | 18665.37 | 29-DEC-23:00 | 8.90 | 7.76 | 0.151401E+11 | 9948.75 | 29-DEC-23:10 | 8.72 | 7.62 |
Annual Sum or Average | 0.496335E+12 | 0.183689E+12 | ||||||||
Minimum of Months | 0.348396E+11 | 18665.37 | 8.90 | 7.76 | 0.137614E+11 | 9948.75 | 8.72 | 7.62 | ||
Maximum of Months | 0.467516E+11 | 22733.26 | 30.57 | 19.31 | 0.161067E+11 | 10671.86 | 21.82 | 16.04 |
Report: ZoneCoolingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.404638E+11 | 20046.80 | 11-JAN-23:00 | 9.40 | 8.23 | 0.152422E+11 | 10106.17 | 11-JAN-23:10 | 9.22 | 8.15 |
February | 0.376100E+11 | 20406.45 | 27-FEB-23:00 | 12.20 | 10.35 | 0.138612E+11 | 10234.57 | 27-FEB-23:10 | 12.20 | 10.40 |
March | 0.437051E+11 | 20571.87 | 08-MAR-23:15 | 13.33 | 9.21 | 0.156208E+11 | 10336.02 | 08-MAR-23:40 | 12.77 | 9.10 |
April | 0.443281E+11 | 22731.97 | 27-APR-18:10 | 25.55 | 15.86 | 0.152260E+11 | 10515.97 | 27-APR-21:40 | 15.33 | 11.23 |
May | 0.476710E+11 | 22687.01 | 31-MAY-18:10 | 20.40 | 14.89 | 0.159593E+11 | 10611.14 | 05-MAY-22:10 | 20.40 | 14.89 |
June | 0.475569E+11 | 23651.00 | 28-JUN-18:10 | 25.40 | 16.48 | 0.156546E+11 | 10678.03 | 28-JUN-22:10 | 17.75 | 13.83 |
July | 0.500285E+11 | 24140.07 | 24-JUL-18:10 | 28.72 | 17.86 | 0.161946E+11 | 10759.28 | 24-JUL-22:10 | 20.40 | 15.71 |
August | 0.498775E+11 | 24089.40 | 10-AUG-18:10 | 30.57 | 19.31 | 0.162591E+11 | 10775.31 | 08-AUG-22:10 | 30.57 | 19.31 |
September | 0.459741E+11 | 22146.77 | 13-SEP-18:10 | 22.43 | 16.15 | 0.154061E+11 | 10564.74 | 20-SEP-21:49 | 12.88 | 11.23 |
October | 0.445806E+11 | 20763.73 | 25-OCT-21:10 | 13.48 | 12.19 | 0.156468E+11 | 10352.51 | 04-OCT-22:10 | 13.48 | 12.19 |
November | 0.410317E+11 | 20522.08 | 06-NOV-23:00 | 15.60 | 14.58 | 0.149419E+11 | 10239.87 | 03-NOV-22:10 | 15.60 | 14.58 |
December | 0.407616E+11 | 19894.03 | 29-DEC-23:00 | 8.90 | 7.76 | 0.152481E+11 | 10061.60 | 29-DEC-23:10 | 8.72 | 7.62 |
Annual Sum or Average | 0.533589E+12 | 0.185261E+12 | ||||||||
Minimum of Months | 0.376100E+11 | 19894.03 | 8.90 | 7.76 | 0.138612E+11 | 10061.60 | 8.72 | 7.62 | ||
Maximum of Months | 0.500285E+11 | 24140.07 | 30.57 | 19.31 | 0.162591E+11 | 10775.31 | 30.57 | 19.31 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.504075E+11 | 26621.61 | 11-JAN-19:08 | 12.30 | 9.41 | 0.186138E+11 | 11319.58 | 28-JAN-18:19 | 6.50 | 5.45 |
February | 0.465461E+11 | 27160.63 | 27-FEB-11:50 | 16.23 | 10.66 | 0.168233E+11 | 11319.58 | 11-FEB-18:19 | 16.23 | 10.66 |
March | 0.531410E+11 | 28567.51 | 14-MAR-10:50 | 11.42 | 8.58 | 0.186434E+11 | 11319.70 | 18-MAR-17:19 | 19.03 | 9.50 |
April | 0.532483E+11 | 30036.29 | 27-APR-10:50 | 20.73 | 13.65 | 0.180510E+11 | 11332.89 | 15-APR-17:30 | 20.73 | 13.65 |
May | 0.562944E+11 | 30174.96 | 14-MAY-10:50 | 20.32 | 12.80 | 0.186617E+11 | 11323.18 | 27-MAY-17:49 | 12.30 | 8.83 |
June | 0.558251E+11 | 30444.86 | 10-JUN-10:40 | 20.20 | 14.80 | 0.180705E+11 | 11319.73 | 24-JUN-17:19 | 19.23 | 11.83 |
July | 0.583642E+11 | 30921.54 | 24-JUL-10:40 | 25.93 | 17.48 | 0.186707E+11 | 11319.76 | 29-JUL-17:19 | 23.17 | 15.48 |
August | 0.586396E+11 | 30999.26 | 08-AUG-10:40 | 24.80 | 18.03 | 0.186778E+11 | 11319.75 | 05-AUG-17:19 | 24.80 | 18.03 |
September | 0.548839E+11 | 30263.43 | 10-SEP-10:50 | 18.62 | 13.97 | 0.180603E+11 | 11319.73 | 09-SEP-17:19 | 18.62 | 13.97 |
October | 0.540591E+11 | 29022.69 | 04-OCT-10:50 | 18.62 | 11.03 | 0.186449E+11 | 11334.90 | 21-OCT-17:19 | 12.43 | 9.46 |
November | 0.502664E+11 | 28309.07 | 04-NOV-10:50 | 17.52 | 14.63 | 0.180256E+11 | 11319.64 | 04-NOV-17:19 | 17.60 | 14.26 |
December | 0.506957E+11 | 26378.81 | 03-DEC-11:50 | 11.52 | 5.93 | 0.186163E+11 | 11319.58 | 09-DEC-18:19 | 5.40 | 4.28 |
Annual Sum or Average | 0.642371E+12 | 0.219559E+12 | ||||||||
Minimum of Months | 0.465461E+11 | 26378.81 | 11.42 | 5.93 | 0.168233E+11 | 11319.58 | 5.40 | 4.28 | ||
Maximum of Months | 0.586396E+11 | 30999.26 | 25.93 | 18.03 | 0.186778E+11 | 11334.90 | 24.80 | 18.03 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.904604E+09 | 3123.34 | 20-JAN-13:30 | 6.70 | 4.72 | 0.126863E+10 | 745.72 | 27-JAN-01:49 | 7.80 | 6.74 |
February | 0.217035E+10 | 5059.06 | 27-FEB-14:30 | 19.15 | 11.80 | 0.114692E+10 | 745.76 | 08-FEB-03:00 | 19.15 | 11.80 |
March | 0.440069E+10 | 5722.74 | 14-MAR-15:40 | 16.83 | 10.74 | 0.127489E+10 | 745.76 | 24-MAR-04:00 | 2.80 | -0.2 |
April | 0.652661E+10 | 6759.97 | 27-APR-17:12 | 26.10 | 16.52 | 0.123080E+10 | 746.61 | 27-APR-21:19 | 16.27 | 11.36 |
May | 0.865227E+10 | 6726.22 | 15-MAY-17:12 | 23.30 | 12.91 | 0.127312E+10 | 746.78 | 04-MAY-21:19 | 23.30 | 12.91 |
June | 0.984667E+10 | 6988.68 | 28-JUN-18:10 | 25.40 | 16.48 | 0.123475E+10 | 755.31 | 28-JUN-21:30 | 17.50 | 13.87 |
July | 0.115139E+11 | 7434.89 | 24-JUL-10:35 | 25.93 | 17.48 | 0.127398E+10 | 773.30 | 24-JUL-21:40 | 21.33 | 16.04 |
August | 0.115146E+11 | 7543.52 | 10-AUG-10:35 | 23.93 | 17.55 | 0.128182E+10 | 783.23 | 10-AUG-21:40 | 22.67 | 16.07 |
September | 0.886235E+10 | 6737.13 | 14-SEP-17:12 | 23.90 | 16.69 | 0.123265E+10 | 748.97 | 12-SEP-21:30 | 23.90 | 16.69 |
October | 0.572311E+10 | 5991.19 | 04-OCT-15:30 | 21.40 | 11.45 | 0.126969E+10 | 745.70 | 11-OCT-01:10 | 8.12 | 6.26 |
November | 0.258639E+10 | 5553.96 | 04-NOV-15:15 | 20.73 | 15.94 | 0.122742E+10 | 745.74 | 14-NOV-05:00 | 5.60 | 1.76 |
December | 0.115375E+10 | 3457.40 | 05-DEC-12:40 | 10.40 | 6.15 | 0.126875E+10 | 745.79 | 13-DEC-04:10 | 4.90 | 1.16 |
Annual Sum or Average | 0.738552E+11 | 0.149834E+11 | ||||||||
Minimum of Months | 0.904604E+09 | 3123.34 | 6.70 | 4.72 | 0.114692E+10 | 745.70 | 2.80 | -0.2 | ||
Maximum of Months | 0.115146E+11 | 7543.52 | 26.10 | 17.55 | 0.128182E+10 | 783.23 | 23.90 | 16.69 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 5.92 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 4.40 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.40 | |
Maximum of Months | 0.00 | 0.00 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.164779E+09 | 414.30 | 16-JAN-06:00 | -2.2 |
February | 67273253.19 | 545.95 | 19-FEB-06:00 | -5.6 |
March | 4077502.14 | 129.30 | 05-MAR-18:00 | 5.60 |
April | 212841.67 | 36.22 | 18-APR-06:10 | 3.40 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
October | 65300.76 | 22.60 | 28-OCT-06:50 | 7.80 |
November | 35560841.04 | 282.99 | 30-NOV-16:00 | 4.40 |
December | 0.159308E+09 | 532.96 | 26-DEC-10:30 | 0.05 |
Annual Sum or Average | 0.431277E+09 | |||
Minimum of Months | 0.00 | 0.00 | -5.6 | |
Maximum of Months | 0.164779E+09 | 545.95 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 5.92 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 4.40 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.40 | |
Maximum of Months | 0.00 | 0.00 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 4145432.08 | 107.40 | 16-JAN-15:40 | 2.20 |
February | 756710.19 | 69.14 | 19-FEB-06:00 | -5.6 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 |
December | 1134042.19 | 64.70 | 26-DEC-04:40 | -0.8 |
Annual Sum or Average | 6036184.46 | |||
Minimum of Months | 0.00 | 0.00 | -5.6 | |
Maximum of Months | 4145432.08 | 107.40 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 94772835.67 | 198.38 | 16-JAN-17:00 | 1.70 |
February | 51236924.87 | 199.86 | 19-FEB-06:00 | -5.6 |
March | 866511.40 | 54.25 | 05-MAR-15:50 | 6.02 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 10392592.09 | 83.95 | 12-NOV-18:00 | 3.30 |
December | 54614747.81 | 196.30 | 26-DEC-12:50 | 0.53 |
Annual Sum or Average | 0.211884E+09 | |||
Minimum of Months | 0.00 | 0.00 | -5.6 | |
Maximum of Months | 94772835.67 | 199.86 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 5.92 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 4.40 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.40 | |
Maximum of Months | 0.00 | 0.00 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 5.92 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 4.40 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.40 | |
Maximum of Months | 0.00 | 0.00 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 5.92 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 4.40 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.40 | |
Maximum of Months | 0.00 | 0.00 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.822959E+09 | 1605.69 | 02-JAN-16:02 | 7.98 |
February | 0.471013E+09 | 1598.48 | 15-FEB-16:02 | 11.02 |
March | 0.211252E+09 | 1565.84 | 05-MAR-16:02 | 6.02 |
April | 74320430.99 | 1515.38 | 19-APR-08:62 | 5.87 |
May | 16887471.23 | 1481.48 | 18-MAY-08:62 | 6.28 |
June | 3257992.99 | 974.93 | 04-JUN-08:03 | 12.38 |
July | 1672446.22 | 913.15 | 13-JUL-08:03 | 15.18 |
August | 1825584.54 | 776.94 | 21-AUG-08:03 | 15.53 |
September | 6155275.70 | 923.85 | 26-SEP-18:04 | 12.12 |
October | 88595389.95 | 1560.48 | 27-OCT-15:02 | 10.82 |
November | 0.418287E+09 | 1594.09 | 26-NOV-16:02 | 6.78 |
December | 0.742771E+09 | 1614.56 | 27-DEC-16:02 | 7.62 |
Annual Sum or Average | 0.285900E+10 | |||
Minimum of Months | 1672446.22 | 776.94 | 5.87 | |
Maximum of Months | 0.822959E+09 | 1614.56 | 15.53 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.961418E+09 | 1564.59 | 10-JAN-16:02 | 10.00 |
February | 0.613919E+09 | 1561.35 | 15-FEB-16:02 | 11.02 |
March | 0.296623E+09 | 1529.91 | 05-MAR-16:02 | 6.02 |
April | 0.100507E+09 | 1501.80 | 06-APR-08:62 | 9.18 |
May | 20504427.18 | 1441.23 | 18-MAY-08:62 | 6.28 |
June | 3276696.00 | 922.29 | 18-JUN-08:03 | 12.57 |
July | 1416595.48 | 880.86 | 16-JUL-15:04 | 17.80 |
August | 1934745.89 | 729.32 | 29-AUG-08:03 | 20.88 |
September | 7562709.60 | 1182.64 | 28-SEP-08:62 | 10.28 |
October | 0.135915E+09 | 1523.03 | 31-OCT-15:02 | 10.82 |
November | 0.520906E+09 | 1553.41 | 17-NOV-16:02 | 10.00 |
December | 0.885301E+09 | 1569.54 | 27-DEC-16:02 | 7.62 |
Annual Sum or Average | 0.354928E+10 | |||
Minimum of Months | 1416595.48 | 729.32 | 6.02 | |
Maximum of Months | 0.961418E+09 | 1569.54 | 20.88 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 7023694.22 | 71.46 | 19-JAN-05:00 | 2.80 |
February | 4862132.21 | 120.84 | 19-FEB-06:00 | -5.6 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 |
December | 10691868.69 | 91.81 | 26-DEC-04:10 | -1.0 |
Annual Sum or Average | 22577695.12 | |||
Minimum of Months | 0.00 | 0.00 | -5.6 | |
Maximum of Months | 10691868.69 | 120.84 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 41215487.97 | 426.61 | 10-JAN-16:02 | 10.00 |
February | 21595773.76 | 422.32 | 15-FEB-16:02 | 11.02 |
March | 1117256.95 | 405.32 | 03-MAR-16:02 | 9.90 |
April | 786680.40 | 307.81 | 19-APR-18:04 | 10.82 |
May | 512307.61 | 302.85 | 04-MAY-08:05 | 15.37 |
June | 201467.14 | 258.72 | 04-JUN-15:06 | 17.12 |
July | 183310.16 | 243.44 | 14-JUL-08:06 | 15.18 |
August | 174093.67 | 389.86 | 21-AUG-08:05 | 15.53 |
September | 666920.39 | 420.11 | 30-SEP-15:04 | 17.70 |
October | 954311.82 | 421.38 | 01-OCT-15:05 | 16.70 |
November | 4881175.29 | 418.27 | 17-NOV-16:02 | 10.00 |
December | 21444204.34 | 421.82 | 10-DEC-16:01 | 9.72 |
Annual Sum or Average | 93732989.48 | |||
Minimum of Months | 174093.67 | 243.44 | 9.72 | |
Maximum of Months | 41215487.97 | 426.61 | 17.70 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.829193E+09 | 1560.00 | 02-JAN-16:02 | 7.98 |
February | 0.471992E+09 | 1550.26 | 15-FEB-16:02 | 11.02 |
March | 0.203775E+09 | 1515.95 | 05-MAR-16:02 | 6.02 |
April | 70151363.78 | 1459.18 | 18-APR-08:62 | 4.50 |
May | 21309879.92 | 1437.14 | 18-MAY-08:62 | 6.28 |
June | 3594158.84 | 818.84 | 23-JUN-15:04 | 16.88 |
July | 1307763.15 | 827.63 | 29-JUL-08:04 | 15.68 |
August | 1495984.19 | 732.99 | 27-AUG-15:04 | 18.42 |
September | 7893501.17 | 785.45 | 16-SEP-08:04 | 11.10 |
October | 91136732.19 | 1515.90 | 31-OCT-15:02 | 10.82 |
November | 0.422087E+09 | 1547.06 | 26-NOV-16:02 | 6.78 |
December | 0.748551E+09 | 1566.17 | 27-DEC-16:02 | 7.62 |
Annual Sum or Average | 0.287249E+10 | |||
Minimum of Months | 1307763.15 | 732.99 | 4.50 | |
Maximum of Months | 0.829193E+09 | 1566.17 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.965769E+09 | 1523.38 | 25-JAN-16:02 | 8.22 |
February | 0.613659E+09 | 1517.18 | 15-FEB-16:02 | 11.02 |
March | 0.278051E+09 | 1493.46 | 03-MAR-16:02 | 9.90 |
April | 93791624.00 | 1420.84 | 18-APR-08:62 | 4.50 |
May | 26903528.41 | 1400.43 | 18-MAY-08:62 | 6.28 |
June | 4123676.15 | 760.24 | 23-JUN-15:04 | 16.88 |
July | 1647275.97 | 863.07 | 29-JUL-08:04 | 15.68 |
August | 1574123.89 | 876.75 | 02-AUG-15:04 | 18.37 |
September | 10616724.74 | 1026.32 | 30-SEP-15:03 | 17.70 |
October | 0.137930E+09 | 1484.18 | 31-OCT-15:02 | 10.82 |
November | 0.517799E+09 | 1515.25 | 17-NOV-16:02 | 10.00 |
December | 0.886188E+09 | 1532.07 | 10-DEC-16:01 | 9.72 |
Annual Sum or Average | 0.353805E+10 | |||
Minimum of Months | 1574123.89 | 760.24 | 4.50 | |
Maximum of Months | 0.965769E+09 | 1532.07 | 18.37 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 31374723.01 | 360.69 | 16-JAN-16:00 | 2.20 |
February | 6087009.69 | 269.12 | 17-FEB-10:20 | 0.97 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 6851360.32 | 265.38 | 30-NOV-14:50 | 4.90 |
December | 46833046.89 | 393.43 | 26-DEC-15:00 | 2.20 |
Annual Sum or Average | 91146139.91 | |||
Minimum of Months | 0.00 | 0.00 | 0.97 | |
Maximum of Months | 46833046.89 | 393.43 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.128292E+10 | 1898.58 | 02-JAN-16:02 | 7.98 |
February | 0.780750E+09 | 1897.10 | 15-FEB-16:02 | 11.02 |
March | 0.412519E+09 | 1867.04 | 05-MAR-16:02 | 6.02 |
April | 0.160499E+09 | 1817.72 | 06-APR-08:62 | 9.18 |
May | 46056966.41 | 1769.97 | 18-MAY-08:62 | 6.28 |
June | 7398929.34 | 860.41 | 04-JUN-08:03 | 12.38 |
July | 1764668.89 | 1076.38 | 09-JUL-08:03 | 14.40 |
August | 1606473.27 | 983.92 | 20-AUG-08:03 | 14.38 |
September | 16756787.00 | 1238.66 | 28-SEP-08:62 | 10.28 |
October | 0.201526E+09 | 1859.61 | 27-OCT-15:02 | 10.82 |
November | 0.726419E+09 | 1897.44 | 17-NOV-16:02 | 10.00 |
December | 0.117794E+10 | 1917.14 | 27-DEC-16:02 | 7.62 |
Annual Sum or Average | 0.481615E+10 | |||
Minimum of Months | 1606473.27 | 860.41 | 6.02 | |
Maximum of Months | 0.128292E+10 | 1917.14 | 14.40 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.145831E+10 | 1855.14 | 10-JAN-16:02 | 10.00 |
February | 0.971766E+09 | 1846.36 | 15-FEB-16:02 | 11.02 |
March | 0.534622E+09 | 1830.38 | 03-MAR-16:02 | 9.90 |
April | 0.204117E+09 | 1785.53 | 06-APR-08:62 | 9.18 |
May | 54333060.60 | 1722.64 | 18-MAY-08:62 | 6.28 |
June | 8156014.92 | 867.40 | 30-JUN-08:03 | 15.18 |
July | 1462878.92 | 854.18 | 09-JUL-08:03 | 14.40 |
August | 1711234.54 | 925.66 | 20-AUG-08:03 | 14.38 |
September | 22282840.01 | 1769.52 | 28-SEP-08:62 | 10.28 |
October | 0.288218E+09 | 1816.81 | 31-OCT-15:02 | 10.82 |
November | 0.858398E+09 | 1851.69 | 17-NOV-16:02 | 10.00 |
December | 0.136354E+10 | 1863.48 | 27-DEC-16:02 | 7.62 |
Annual Sum or Average | 0.576692E+10 | |||
Minimum of Months | 1462878.92 | 854.18 | 6.28 | |
Maximum of Months | 0.145831E+10 | 1863.48 | 15.18 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.348667E+09 | 1045.34 | 02-JAN-16:02 | 7.98 |
February | 0.177993E+09 | 1030.09 | 15-FEB-16:02 | 11.02 |
March | 57738181.23 | 1005.48 | 05-MAR-16:02 | 6.02 |
April | 21282347.24 | 975.19 | 18-APR-08:62 | 4.50 |
May | 5082166.78 | 958.34 | 18-MAY-08:62 | 6.28 |
June | 1412487.37 | 634.61 | 30-JUN-08:03 | 15.18 |
July | 913876.94 | 601.59 | 13-JUL-08:03 | 15.18 |
August | 895167.41 | 579.26 | 21-AUG-08:03 | 15.53 |
September | 2434783.33 | 634.75 | 18-SEP-15:04 | 16.10 |
October | 15008325.81 | 1005.27 | 27-OCT-15:02 | 10.82 |
November | 0.145245E+09 | 1026.98 | 26-NOV-16:02 | 6.78 |
December | 0.322929E+09 | 1051.32 | 27-DEC-16:02 | 7.62 |
Annual Sum or Average | 0.109960E+10 | |||
Minimum of Months | 895167.41 | 579.26 | 4.50 | |
Maximum of Months | 0.348667E+09 | 1051.32 | 16.10 |
Report: ZoneHeatingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 5.92 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 4.40 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.40 | |
Maximum of Months | 0.00 | 0.00 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 5.92 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 4.40 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.40 | |
Maximum of Months | 0.00 | 0.00 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 5.92 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 4.40 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.40 | |
Maximum of Months | 0.00 | 0.00 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.597170E+09 | 1500.57 | 16-JAN-06:00 | -2.2 |
February | 0.291555E+09 | 1643.35 | 19-FEB-06:10 | -5.5 |
March | 8867333.24 | 437.82 | 01-MAR-07:10 | -0.1 |
April | 160500.55 | 96.31 | 18-APR-06:10 | 3.40 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 91727829.81 | 991.59 | 24-NOV-07:10 | 1.20 |
December | 0.452812E+09 | 1512.27 | 26-DEC-10:20 | 0.03 |
Annual Sum or Average | 0.144229E+10 | |||
Minimum of Months | 0.00 | 0.00 | -5.5 | |
Maximum of Months | 0.597170E+09 | 1643.35 | 17.17 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.140333E+11 | 13517.00 | 02-JAN-20:10 | 0.127587E+11 | 10113.80 | 02-JAN-20:10 |
February | 0.126708E+11 | 13517.00 | 01-FEB-20:10 | 0.115208E+11 | 10113.80 | 01-FEB-20:10 |
March | 0.140766E+11 | 13517.00 | 01-MAR-20:10 | 0.127855E+11 | 10113.80 | 01-MAR-20:10 |
April | 0.135575E+11 | 13517.00 | 03-APR-19:10 | 0.123314E+11 | 10113.80 | 03-APR-19:10 |
May | 0.140576E+11 | 13517.00 | 01-MAY-19:10 | 0.127741E+11 | 10113.80 | 01-MAY-19:10 |
June | 0.136197E+11 | 13517.00 | 01-JUN-19:10 | 0.123716E+11 | 10113.80 | 01-JUN-19:10 |
July | 0.139955E+11 | 13517.00 | 03-JUL-19:10 | 0.127338E+11 | 10113.80 | 03-JUL-19:10 |
August | 0.140820E+11 | 13517.00 | 01-AUG-19:10 | 0.127894E+11 | 10113.80 | 01-AUG-19:10 |
September | 0.135629E+11 | 13517.00 | 01-SEP-19:10 | 0.123352E+11 | 10113.80 | 01-SEP-19:10 |
October | 0.140279E+11 | 13517.00 | 02-OCT-19:10 | 0.127549E+11 | 10113.80 | 02-OCT-19:10 |
November | 0.136089E+11 | 13517.00 | 01-NOV-19:10 | 0.123659E+11 | 10113.80 | 01-NOV-19:10 |
December | 0.139955E+11 | 13517.00 | 01-DEC-20:10 | 0.127338E+11 | 10113.80 | 01-DEC-20:10 |
Annual Sum or Average | 0.165288E+12 | 0.150255E+12 | ||||
Minimum of Months | 0.126708E+11 | 13517.00 | 0.115208E+11 | 10113.80 | ||
Maximum of Months | 0.140820E+11 | 13517.00 | 0.127894E+11 | 10113.80 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.713551E+09 | 687.30 | 02-JAN-20:10 | 0.864900E+09 | 685.60 | 02-JAN-20:10 |
February | 0.644271E+09 | 687.30 | 01-FEB-20:10 | 0.780982E+09 | 685.60 | 01-FEB-20:10 |
March | 0.715750E+09 | 687.30 | 01-MAR-20:10 | 0.866718E+09 | 685.60 | 01-MAR-20:10 |
April | 0.689358E+09 | 687.30 | 03-APR-19:10 | 0.835931E+09 | 685.60 | 03-APR-19:10 |
May | 0.714788E+09 | 687.30 | 01-MAY-19:10 | 0.865939E+09 | 685.60 | 01-MAY-19:10 |
June | 0.692519E+09 | 687.30 | 01-JUN-19:10 | 0.838659E+09 | 685.60 | 01-JUN-19:10 |
July | 0.711626E+09 | 687.30 | 03-JUL-19:10 | 0.863211E+09 | 685.60 | 03-JUL-19:10 |
August | 0.716025E+09 | 687.30 | 01-AUG-19:10 | 0.866978E+09 | 685.60 | 01-AUG-19:10 |
September | 0.689633E+09 | 687.30 | 01-SEP-19:10 | 0.836191E+09 | 685.60 | 01-SEP-19:10 |
October | 0.713276E+09 | 687.30 | 02-OCT-19:10 | 0.864640E+09 | 685.60 | 02-OCT-19:10 |
November | 0.691970E+09 | 687.30 | 01-NOV-19:10 | 0.838269E+09 | 685.60 | 01-NOV-19:10 |
December | 0.711626E+09 | 687.30 | 01-DEC-20:10 | 0.863211E+09 | 685.60 | 01-DEC-20:10 |
Annual Sum or Average | 0.840439E+10 | 0.101856E+11 | ||||
Minimum of Months | 0.644271E+09 | 687.30 | 0.780982E+09 | 685.60 | ||
Maximum of Months | 0.716025E+09 | 687.30 | 0.866978E+09 | 685.60 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.826294E+09 | 795.89 | 02-JAN-20:10 | 0.100156E+10 | 793.93 | 02-JAN-20:10 |
February | 0.746069E+09 | 795.89 | 01-FEB-20:10 | 0.904380E+09 | 793.93 | 01-FEB-20:10 |
March | 0.828841E+09 | 795.89 | 01-MAR-20:10 | 0.100366E+10 | 793.93 | 01-MAR-20:10 |
April | 0.798279E+09 | 795.89 | 03-APR-19:10 | 0.968011E+09 | 793.93 | 03-APR-19:10 |
May | 0.827727E+09 | 795.89 | 01-MAY-19:10 | 0.100276E+10 | 793.93 | 01-MAY-19:10 |
June | 0.801940E+09 | 795.89 | 01-JUN-19:10 | 0.971170E+09 | 793.93 | 01-JUN-19:10 |
July | 0.824066E+09 | 795.89 | 03-JUL-19:10 | 0.999601E+09 | 793.93 | 03-JUL-19:10 |
August | 0.829160E+09 | 795.89 | 01-AUG-19:10 | 0.100396E+10 | 793.93 | 01-AUG-19:10 |
September | 0.798597E+09 | 795.89 | 01-SEP-19:10 | 0.968312E+09 | 793.93 | 01-SEP-19:10 |
October | 0.825976E+09 | 795.89 | 02-OCT-19:10 | 0.100126E+10 | 793.93 | 02-OCT-19:10 |
November | 0.801303E+09 | 795.89 | 01-NOV-19:10 | 0.970719E+09 | 793.93 | 01-NOV-19:10 |
December | 0.824066E+09 | 795.89 | 01-DEC-20:10 | 0.999601E+09 | 793.93 | 01-DEC-20:10 |
Annual Sum or Average | 0.973232E+10 | 0.117950E+11 | ||||
Minimum of Months | 0.746069E+09 | 795.89 | 0.904380E+09 | 793.93 | ||
Maximum of Months | 0.829160E+09 | 795.89 | 0.100396E+10 | 793.93 |
Report: ZoneElectricSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.154452E+10 | 1487.69 | 02-JAN-20:10 | 0.105898E+10 | 839.45 | 02-JAN-20:10 |
February | 0.139456E+10 | 1487.69 | 01-FEB-20:10 | 0.956227E+09 | 839.45 | 01-FEB-20:10 |
March | 0.154928E+10 | 1487.69 | 01-MAR-20:10 | 0.106120E+10 | 839.45 | 01-MAR-20:10 |
April | 0.149215E+10 | 1487.69 | 03-APR-19:10 | 0.102351E+10 | 839.45 | 03-APR-19:10 |
May | 0.154719E+10 | 1487.69 | 01-MAY-19:10 | 0.106025E+10 | 839.45 | 01-MAY-19:10 |
June | 0.149899E+10 | 1487.69 | 01-JUN-19:10 | 0.102685E+10 | 839.45 | 01-JUN-19:10 |
July | 0.154035E+10 | 1487.69 | 03-JUL-19:10 | 0.105691E+10 | 839.45 | 03-JUL-19:10 |
August | 0.154987E+10 | 1487.69 | 01-AUG-19:10 | 0.106152E+10 | 839.45 | 01-AUG-19:10 |
September | 0.149274E+10 | 1487.69 | 01-SEP-19:10 | 0.102382E+10 | 839.45 | 01-SEP-19:10 |
October | 0.154392E+10 | 1487.69 | 02-OCT-19:10 | 0.105866E+10 | 839.45 | 02-OCT-19:10 |
November | 0.149780E+10 | 1487.69 | 01-NOV-19:10 | 0.102637E+10 | 839.45 | 01-NOV-19:10 |
December | 0.154035E+10 | 1487.69 | 01-DEC-20:10 | 0.105691E+10 | 839.45 | 01-DEC-20:10 |
Annual Sum or Average | 0.181917E+11 | 0.124712E+11 | ||||
Minimum of Months | 0.139456E+10 | 1487.69 | 0.956227E+09 | 839.45 | ||
Maximum of Months | 0.154987E+10 | 1487.69 | 0.106152E+10 | 839.45 |
Report: ZoneElectricSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.283535E+09 | 273.10 | 02-JAN-20:10 | 0.305485E+09 | 242.16 | 02-JAN-20:10 |
February | 0.256006E+09 | 273.10 | 01-FEB-20:10 | 0.275845E+09 | 242.16 | 01-FEB-20:10 |
March | 0.284409E+09 | 273.10 | 01-MAR-20:10 | 0.306128E+09 | 242.16 | 01-MAR-20:10 |
April | 0.273921E+09 | 273.10 | 03-APR-19:10 | 0.295253E+09 | 242.16 | 03-APR-19:10 |
May | 0.284026E+09 | 273.10 | 01-MAY-19:10 | 0.305852E+09 | 242.16 | 01-MAY-19:10 |
June | 0.275178E+09 | 273.10 | 01-JUN-19:10 | 0.296217E+09 | 242.16 | 01-JUN-19:10 |
July | 0.282770E+09 | 273.10 | 03-JUL-19:10 | 0.304889E+09 | 242.16 | 03-JUL-19:10 |
August | 0.284518E+09 | 273.10 | 01-AUG-19:10 | 0.306219E+09 | 242.16 | 01-AUG-19:10 |
September | 0.274031E+09 | 273.10 | 01-SEP-19:10 | 0.295345E+09 | 242.16 | 01-SEP-19:10 |
October | 0.283425E+09 | 273.10 | 02-OCT-19:10 | 0.305393E+09 | 242.16 | 02-OCT-19:10 |
November | 0.274959E+09 | 273.10 | 01-NOV-19:10 | 0.296079E+09 | 242.16 | 01-NOV-19:10 |
December | 0.282770E+09 | 273.10 | 01-DEC-20:10 | 0.304889E+09 | 242.16 | 01-DEC-20:10 |
Annual Sum or Average | 0.333955E+10 | 0.359760E+10 | ||||
Minimum of Months | 0.256006E+09 | 273.10 | 0.275845E+09 | 242.16 | ||
Maximum of Months | 0.284518E+09 | 273.10 | 0.306219E+09 | 242.16 |
Report: ZoneElectricSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.350256E+09 | 337.37 | 02-JAN-20:10 | 0.576866E+10 | 4572.80 | 02-JAN-20:10 |
February | 0.316249E+09 | 337.37 | 01-FEB-20:10 | 0.520895E+10 | 4572.80 | 01-FEB-20:10 |
March | 0.351336E+09 | 337.37 | 01-MAR-20:10 | 0.578079E+10 | 4572.80 | 01-MAR-20:10 |
April | 0.338381E+09 | 337.37 | 03-APR-19:10 | 0.557545E+10 | 4572.80 | 03-APR-19:10 |
May | 0.350863E+09 | 337.37 | 01-MAY-19:10 | 0.577559E+10 | 4572.80 | 01-MAY-19:10 |
June | 0.339933E+09 | 337.37 | 01-JUN-19:10 | 0.559364E+10 | 4572.80 | 01-JUN-19:10 |
July | 0.349311E+09 | 337.37 | 03-JUL-19:10 | 0.575740E+10 | 4572.80 | 03-JUL-19:10 |
August | 0.351471E+09 | 337.37 | 01-AUG-19:10 | 0.578252E+10 | 4572.80 | 01-AUG-19:10 |
September | 0.338516E+09 | 337.37 | 01-SEP-19:10 | 0.557718E+10 | 4572.80 | 01-SEP-19:10 |
October | 0.350121E+09 | 337.37 | 02-OCT-19:10 | 0.576693E+10 | 4572.80 | 02-OCT-19:10 |
November | 0.339663E+09 | 337.37 | 01-NOV-19:10 | 0.559104E+10 | 4572.80 | 01-NOV-19:10 |
December | 0.349311E+09 | 337.37 | 01-DEC-20:10 | 0.575740E+10 | 4572.80 | 01-DEC-20:10 |
Annual Sum or Average | 0.412541E+10 | 0.679355E+11 | ||||
Minimum of Months | 0.316249E+09 | 337.37 | 0.520895E+10 | 4572.80 | ||
Maximum of Months | 0.351471E+09 | 337.37 | 0.578252E+10 | 4572.80 |
Report: ZoneElectricSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.226040E+10 | 2177.23 | 02-JAN-20:10 | 0.121771E+10 | 965.27 | 02-JAN-20:10 |
February | 0.204093E+10 | 2177.23 | 01-FEB-20:10 | 0.109956E+10 | 965.27 | 01-FEB-20:10 |
March | 0.226736E+10 | 2177.23 | 01-MAR-20:10 | 0.122027E+10 | 965.27 | 01-MAR-20:10 |
April | 0.218376E+10 | 2177.23 | 03-APR-19:10 | 0.117692E+10 | 965.27 | 03-APR-19:10 |
May | 0.226431E+10 | 2177.23 | 01-MAY-19:10 | 0.121917E+10 | 965.27 | 01-MAY-19:10 |
June | 0.219377E+10 | 2177.23 | 01-JUN-19:10 | 0.118076E+10 | 965.27 | 01-JUN-19:10 |
July | 0.225430E+10 | 2177.23 | 03-JUL-19:10 | 0.121533E+10 | 965.27 | 03-JUL-19:10 |
August | 0.226823E+10 | 2177.23 | 01-AUG-19:10 | 0.122063E+10 | 965.27 | 01-AUG-19:10 |
September | 0.218463E+10 | 2177.23 | 01-SEP-19:10 | 0.117729E+10 | 965.27 | 01-SEP-19:10 |
October | 0.225952E+10 | 2177.23 | 02-OCT-19:10 | 0.121734E+10 | 965.27 | 02-OCT-19:10 |
November | 0.219203E+10 | 2177.23 | 01-NOV-19:10 | 0.118021E+10 | 965.27 | 01-NOV-19:10 |
December | 0.225430E+10 | 2177.23 | 01-DEC-20:10 | 0.121533E+10 | 965.27 | 01-DEC-20:10 |
Annual Sum or Average | 0.266236E+11 | 0.143405E+11 | ||||
Minimum of Months | 0.204093E+10 | 2177.23 | 0.109956E+10 | 965.27 | ||
Maximum of Months | 0.226823E+10 | 2177.23 | 0.122063E+10 | 965.27 |
Report: ZoneElectricSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.123020E+11 | 11849.32 | 02-JAN-20:10 | 0.126520E+11 | 10029.21 | 02-JAN-20:10 |
February | 0.111075E+11 | 11849.32 | 01-FEB-20:10 | 0.114244E+11 | 10029.21 | 01-FEB-20:10 |
March | 0.123399E+11 | 11849.32 | 01-MAR-20:10 | 0.126786E+11 | 10029.21 | 01-MAR-20:10 |
April | 0.118849E+11 | 11849.32 | 03-APR-19:10 | 0.122282E+11 | 10029.21 | 03-APR-19:10 |
May | 0.123233E+11 | 11849.32 | 01-MAY-19:10 | 0.126672E+11 | 10029.21 | 01-MAY-19:10 |
June | 0.119394E+11 | 11849.32 | 01-JUN-19:10 | 0.122682E+11 | 10029.21 | 01-JUN-19:10 |
July | 0.122688E+11 | 11849.32 | 03-JUL-19:10 | 0.126273E+11 | 10029.21 | 03-JUL-19:10 |
August | 0.123446E+11 | 11849.32 | 01-AUG-19:10 | 0.126824E+11 | 10029.21 | 01-AUG-19:10 |
September | 0.118896E+11 | 11849.32 | 01-SEP-19:10 | 0.122320E+11 | 10029.21 | 01-SEP-19:10 |
October | 0.122972E+11 | 11849.32 | 02-OCT-19:10 | 0.126482E+11 | 10029.21 | 02-OCT-19:10 |
November | 0.119299E+11 | 11849.32 | 01-NOV-19:10 | 0.122624E+11 | 10029.21 | 01-NOV-19:10 |
December | 0.122688E+11 | 11849.32 | 01-DEC-20:10 | 0.126273E+11 | 10029.21 | 01-DEC-20:10 |
Annual Sum or Average | 0.144896E+12 | 0.148998E+12 | ||||
Minimum of Months | 0.111075E+11 | 11849.32 | 0.114244E+11 | 10029.21 | ||
Maximum of Months | 0.123446E+11 | 11849.32 | 0.126824E+11 | 10029.21 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.434056E+09 | 392.73 | 01-JAN-19:10 | 0.261068E+09 | 237.06 | 01-JAN-08:09 |
February | 0.391995E+09 | 392.73 | 01-FEB-20:10 | 0.235798E+09 | 237.06 | 01-FEB-07:10 |
March | 0.430607E+09 | 392.73 | 01-MAR-20:10 | 0.260708E+09 | 237.06 | 01-MAR-07:10 |
April | 0.420554E+09 | 392.73 | 01-APR-18:10 | 0.252705E+09 | 237.06 | 01-APR-07:10 |
May | 0.432331E+09 | 392.73 | 01-MAY-19:10 | 0.260888E+09 | 237.06 | 01-MAY-06:10 |
June | 0.417218E+09 | 392.73 | 01-JUN-19:10 | 0.252344E+09 | 237.06 | 01-JUN-06:10 |
July | 0.435725E+09 | 392.73 | 01-JUL-18:10 | 0.261248E+09 | 237.06 | 01-JUL-07:10 |
August | 0.430607E+09 | 392.73 | 01-AUG-19:10 | 0.260708E+09 | 237.06 | 01-AUG-06:10 |
September | 0.420667E+09 | 392.73 | 01-SEP-19:10 | 0.252705E+09 | 237.06 | 01-SEP-06:10 |
October | 0.434000E+09 | 392.73 | 01-OCT-18:10 | 0.261068E+09 | 237.06 | 01-OCT-07:10 |
November | 0.418886E+09 | 392.73 | 01-NOV-19:10 | 0.252524E+09 | 237.06 | 01-NOV-06:10 |
December | 0.435781E+09 | 392.73 | 01-DEC-20:10 | 0.261248E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.510243E+10 | 0.307301E+10 | ||||
Minimum of Months | 0.391995E+09 | 392.73 | 0.235798E+09 | 237.06 | ||
Maximum of Months | 0.435781E+09 | 392.73 | 0.261248E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.434005E+09 | 392.68 | 01-JAN-19:10 | 0.261038E+09 | 237.03 | 01-JAN-08:09 |
February | 0.391949E+09 | 392.68 | 01-FEB-20:10 | 0.235770E+09 | 237.03 | 01-FEB-07:10 |
March | 0.430556E+09 | 392.68 | 01-MAR-20:10 | 0.260677E+09 | 237.03 | 01-MAR-07:10 |
April | 0.420505E+09 | 392.68 | 01-APR-18:10 | 0.252675E+09 | 237.03 | 01-APR-07:10 |
May | 0.432281E+09 | 392.68 | 01-MAY-19:10 | 0.260857E+09 | 237.03 | 01-MAY-06:10 |
June | 0.417169E+09 | 392.68 | 01-JUN-19:10 | 0.252315E+09 | 237.03 | 01-JUN-06:10 |
July | 0.435674E+09 | 392.68 | 01-JUL-18:10 | 0.261218E+09 | 237.03 | 01-JUL-07:10 |
August | 0.430556E+09 | 392.68 | 01-AUG-19:10 | 0.260677E+09 | 237.03 | 01-AUG-06:10 |
September | 0.420618E+09 | 392.68 | 01-SEP-19:10 | 0.252675E+09 | 237.03 | 01-SEP-06:10 |
October | 0.433949E+09 | 392.68 | 01-OCT-18:10 | 0.261038E+09 | 237.03 | 01-OCT-07:10 |
November | 0.418837E+09 | 392.68 | 01-NOV-19:10 | 0.252495E+09 | 237.03 | 01-NOV-06:10 |
December | 0.435730E+09 | 392.68 | 01-DEC-20:10 | 0.261218E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.510183E+10 | 0.307265E+10 | ||||
Minimum of Months | 0.391949E+09 | 392.68 | 0.235770E+09 | 237.03 | ||
Maximum of Months | 0.435730E+09 | 392.68 | 0.261218E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.272788E+09 | 246.81 | 01-JAN-19:10 | 0.255708E+09 | 232.19 | 01-JAN-08:09 |
February | 0.246354E+09 | 246.81 | 01-FEB-20:10 | 0.230956E+09 | 232.19 | 01-FEB-07:10 |
March | 0.270620E+09 | 246.81 | 01-MAR-20:10 | 0.255355E+09 | 232.19 | 01-MAR-07:10 |
April | 0.264302E+09 | 246.81 | 01-APR-18:10 | 0.247516E+09 | 232.19 | 01-APR-07:10 |
May | 0.271704E+09 | 246.81 | 01-MAY-19:10 | 0.255532E+09 | 232.19 | 01-MAY-06:10 |
June | 0.262205E+09 | 246.81 | 01-JUN-19:10 | 0.247163E+09 | 232.19 | 01-JUN-06:10 |
July | 0.273836E+09 | 246.81 | 01-JUL-18:10 | 0.255885E+09 | 232.19 | 01-JUL-07:10 |
August | 0.270620E+09 | 246.81 | 01-AUG-19:10 | 0.255355E+09 | 232.19 | 01-AUG-06:10 |
September | 0.264373E+09 | 246.81 | 01-SEP-19:10 | 0.247516E+09 | 232.19 | 01-SEP-06:10 |
October | 0.272752E+09 | 246.81 | 01-OCT-18:10 | 0.255708E+09 | 232.19 | 01-OCT-07:10 |
November | 0.263254E+09 | 246.81 | 01-NOV-19:10 | 0.247340E+09 | 232.19 | 01-NOV-06:10 |
December | 0.273872E+09 | 246.81 | 01-DEC-20:10 | 0.255885E+09 | 232.19 | 01-DEC-07:10 |
Annual Sum or Average | 0.320668E+10 | 0.300992E+10 | ||||
Minimum of Months | 0.246354E+09 | 246.81 | 0.230956E+09 | 232.19 | ||
Maximum of Months | 0.273872E+09 | 246.81 | 0.255885E+09 | 232.19 |
Report: ZoneElectricSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.272862E+09 | 246.88 | 01-JAN-19:10 | 0.255778E+09 | 232.26 | 01-JAN-08:09 |
February | 0.246421E+09 | 246.88 | 01-FEB-20:10 | 0.231020E+09 | 232.26 | 01-FEB-07:10 |
March | 0.270694E+09 | 246.88 | 01-MAR-20:10 | 0.255425E+09 | 232.26 | 01-MAR-07:10 |
April | 0.264375E+09 | 246.88 | 01-APR-18:10 | 0.247584E+09 | 232.26 | 01-APR-07:10 |
May | 0.271778E+09 | 246.88 | 01-MAY-19:10 | 0.255602E+09 | 232.26 | 01-MAY-06:10 |
June | 0.262277E+09 | 246.88 | 01-JUN-19:10 | 0.247231E+09 | 232.26 | 01-JUN-06:10 |
July | 0.273911E+09 | 246.88 | 01-JUL-18:10 | 0.255955E+09 | 232.26 | 01-JUL-07:10 |
August | 0.270694E+09 | 246.88 | 01-AUG-19:10 | 0.255425E+09 | 232.26 | 01-AUG-06:10 |
September | 0.264446E+09 | 246.88 | 01-SEP-19:10 | 0.247584E+09 | 232.26 | 01-SEP-06:10 |
October | 0.272827E+09 | 246.88 | 01-OCT-18:10 | 0.255778E+09 | 232.26 | 01-OCT-07:10 |
November | 0.263326E+09 | 246.88 | 01-NOV-19:10 | 0.247408E+09 | 232.26 | 01-NOV-06:10 |
December | 0.273947E+09 | 246.88 | 01-DEC-20:10 | 0.255955E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.320756E+10 | 0.301074E+10 | ||||
Minimum of Months | 0.246421E+09 | 246.88 | 0.231020E+09 | 232.26 | ||
Maximum of Months | 0.273947E+09 | 246.88 | 0.255955E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.434056E+09 | 392.73 | 01-JAN-19:10 | 0.261068E+09 | 237.06 | 01-JAN-08:09 |
February | 0.391995E+09 | 392.73 | 01-FEB-20:10 | 0.235798E+09 | 237.06 | 01-FEB-07:10 |
March | 0.430607E+09 | 392.73 | 01-MAR-20:10 | 0.260708E+09 | 237.06 | 01-MAR-07:10 |
April | 0.420554E+09 | 392.73 | 01-APR-18:10 | 0.252705E+09 | 237.06 | 01-APR-07:10 |
May | 0.432331E+09 | 392.73 | 01-MAY-19:10 | 0.260888E+09 | 237.06 | 01-MAY-06:10 |
June | 0.417218E+09 | 392.73 | 01-JUN-19:10 | 0.252344E+09 | 237.06 | 01-JUN-06:10 |
July | 0.435725E+09 | 392.73 | 01-JUL-18:10 | 0.261248E+09 | 237.06 | 01-JUL-07:10 |
August | 0.430607E+09 | 392.73 | 01-AUG-19:10 | 0.260708E+09 | 237.06 | 01-AUG-06:10 |
September | 0.420667E+09 | 392.73 | 01-SEP-19:10 | 0.252705E+09 | 237.06 | 01-SEP-06:10 |
October | 0.434000E+09 | 392.73 | 01-OCT-18:10 | 0.261068E+09 | 237.06 | 01-OCT-07:10 |
November | 0.418886E+09 | 392.73 | 01-NOV-19:10 | 0.252524E+09 | 237.06 | 01-NOV-06:10 |
December | 0.435781E+09 | 392.73 | 01-DEC-20:10 | 0.261248E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.510243E+10 | 0.307301E+10 | ||||
Minimum of Months | 0.391995E+09 | 392.73 | 0.235798E+09 | 237.06 | ||
Maximum of Months | 0.435781E+09 | 392.73 | 0.261248E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.434005E+09 | 392.68 | 01-JAN-19:10 | 0.261038E+09 | 237.03 | 01-JAN-08:09 |
February | 0.391949E+09 | 392.68 | 01-FEB-20:10 | 0.235770E+09 | 237.03 | 01-FEB-07:10 |
March | 0.430556E+09 | 392.68 | 01-MAR-20:10 | 0.260677E+09 | 237.03 | 01-MAR-07:10 |
April | 0.420505E+09 | 392.68 | 01-APR-18:10 | 0.252675E+09 | 237.03 | 01-APR-07:10 |
May | 0.432281E+09 | 392.68 | 01-MAY-19:10 | 0.260857E+09 | 237.03 | 01-MAY-06:10 |
June | 0.417169E+09 | 392.68 | 01-JUN-19:10 | 0.252315E+09 | 237.03 | 01-JUN-06:10 |
July | 0.435674E+09 | 392.68 | 01-JUL-18:10 | 0.261218E+09 | 237.03 | 01-JUL-07:10 |
August | 0.430556E+09 | 392.68 | 01-AUG-19:10 | 0.260677E+09 | 237.03 | 01-AUG-06:10 |
September | 0.420618E+09 | 392.68 | 01-SEP-19:10 | 0.252675E+09 | 237.03 | 01-SEP-06:10 |
October | 0.433949E+09 | 392.68 | 01-OCT-18:10 | 0.261038E+09 | 237.03 | 01-OCT-07:10 |
November | 0.418837E+09 | 392.68 | 01-NOV-19:10 | 0.252495E+09 | 237.03 | 01-NOV-06:10 |
December | 0.435730E+09 | 392.68 | 01-DEC-20:10 | 0.261218E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.510183E+10 | 0.307265E+10 | ||||
Minimum of Months | 0.391949E+09 | 392.68 | 0.235770E+09 | 237.03 | ||
Maximum of Months | 0.435730E+09 | 392.68 | 0.261218E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.133160E+10 | 1282.60 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.120231E+10 | 1282.60 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.133570E+10 | 1282.60 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.128645E+10 | 1282.60 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.133391E+10 | 1282.60 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.129235E+10 | 1282.60 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.132801E+10 | 1282.60 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.133622E+10 | 1282.60 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.128696E+10 | 1282.60 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.133109E+10 | 1282.60 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.129132E+10 | 1282.60 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.132801E+10 | 1282.60 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.156839E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.120231E+10 | 1282.60 | 0.00 | 0.00 | |
Maximum of Months | 0.133622E+10 | 1282.60 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.434056E+09 | 392.73 | 01-JAN-19:10 | 0.261068E+09 | 237.06 | 01-JAN-08:09 |
February | 0.391995E+09 | 392.73 | 01-FEB-20:10 | 0.235798E+09 | 237.06 | 01-FEB-07:10 |
March | 0.430607E+09 | 392.73 | 01-MAR-20:10 | 0.260708E+09 | 237.06 | 01-MAR-07:10 |
April | 0.420554E+09 | 392.73 | 01-APR-18:10 | 0.252705E+09 | 237.06 | 01-APR-07:10 |
May | 0.432331E+09 | 392.73 | 01-MAY-19:10 | 0.260888E+09 | 237.06 | 01-MAY-06:10 |
June | 0.417218E+09 | 392.73 | 01-JUN-19:10 | 0.252344E+09 | 237.06 | 01-JUN-06:10 |
July | 0.435725E+09 | 392.73 | 01-JUL-18:10 | 0.261248E+09 | 237.06 | 01-JUL-07:10 |
August | 0.430607E+09 | 392.73 | 01-AUG-19:10 | 0.260708E+09 | 237.06 | 01-AUG-06:10 |
September | 0.420667E+09 | 392.73 | 01-SEP-19:10 | 0.252705E+09 | 237.06 | 01-SEP-06:10 |
October | 0.434000E+09 | 392.73 | 01-OCT-18:10 | 0.261068E+09 | 237.06 | 01-OCT-07:10 |
November | 0.418886E+09 | 392.73 | 01-NOV-19:10 | 0.252524E+09 | 237.06 | 01-NOV-06:10 |
December | 0.435781E+09 | 392.73 | 01-DEC-20:10 | 0.261248E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.510243E+10 | 0.307301E+10 | ||||
Minimum of Months | 0.391995E+09 | 392.73 | 0.235798E+09 | 237.06 | ||
Maximum of Months | 0.435781E+09 | 392.73 | 0.261248E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.434005E+09 | 392.68 | 01-JAN-19:10 | 0.261038E+09 | 237.03 | 01-JAN-08:09 |
February | 0.391949E+09 | 392.68 | 01-FEB-20:10 | 0.235770E+09 | 237.03 | 01-FEB-07:10 |
March | 0.430556E+09 | 392.68 | 01-MAR-20:10 | 0.260677E+09 | 237.03 | 01-MAR-07:10 |
April | 0.420505E+09 | 392.68 | 01-APR-18:10 | 0.252675E+09 | 237.03 | 01-APR-07:10 |
May | 0.432281E+09 | 392.68 | 01-MAY-19:10 | 0.260857E+09 | 237.03 | 01-MAY-06:10 |
June | 0.417169E+09 | 392.68 | 01-JUN-19:10 | 0.252315E+09 | 237.03 | 01-JUN-06:10 |
July | 0.435674E+09 | 392.68 | 01-JUL-18:10 | 0.261218E+09 | 237.03 | 01-JUL-07:10 |
August | 0.430556E+09 | 392.68 | 01-AUG-19:10 | 0.260677E+09 | 237.03 | 01-AUG-06:10 |
September | 0.420618E+09 | 392.68 | 01-SEP-19:10 | 0.252675E+09 | 237.03 | 01-SEP-06:10 |
October | 0.433949E+09 | 392.68 | 01-OCT-18:10 | 0.261038E+09 | 237.03 | 01-OCT-07:10 |
November | 0.418837E+09 | 392.68 | 01-NOV-19:10 | 0.252495E+09 | 237.03 | 01-NOV-06:10 |
December | 0.435730E+09 | 392.68 | 01-DEC-20:10 | 0.261218E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.510183E+10 | 0.307265E+10 | ||||
Minimum of Months | 0.391949E+09 | 392.68 | 0.235770E+09 | 237.03 | ||
Maximum of Months | 0.435730E+09 | 392.68 | 0.261218E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.272862E+09 | 246.88 | 01-JAN-19:10 | 0.255778E+09 | 232.26 | 01-JAN-08:09 |
February | 0.246421E+09 | 246.88 | 01-FEB-20:10 | 0.231020E+09 | 232.26 | 01-FEB-07:10 |
March | 0.270694E+09 | 246.88 | 01-MAR-20:10 | 0.255425E+09 | 232.26 | 01-MAR-07:10 |
April | 0.264375E+09 | 246.88 | 01-APR-18:10 | 0.247584E+09 | 232.26 | 01-APR-07:10 |
May | 0.271778E+09 | 246.88 | 01-MAY-19:10 | 0.255602E+09 | 232.26 | 01-MAY-06:10 |
June | 0.262277E+09 | 246.88 | 01-JUN-19:10 | 0.247231E+09 | 232.26 | 01-JUN-06:10 |
July | 0.273911E+09 | 246.88 | 01-JUL-18:10 | 0.255955E+09 | 232.26 | 01-JUL-07:10 |
August | 0.270694E+09 | 246.88 | 01-AUG-19:10 | 0.255425E+09 | 232.26 | 01-AUG-06:10 |
September | 0.264446E+09 | 246.88 | 01-SEP-19:10 | 0.247584E+09 | 232.26 | 01-SEP-06:10 |
October | 0.272827E+09 | 246.88 | 01-OCT-18:10 | 0.255778E+09 | 232.26 | 01-OCT-07:10 |
November | 0.263326E+09 | 246.88 | 01-NOV-19:10 | 0.247408E+09 | 232.26 | 01-NOV-06:10 |
December | 0.273947E+09 | 246.88 | 01-DEC-20:10 | 0.255955E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.320756E+10 | 0.301074E+10 | ||||
Minimum of Months | 0.246421E+09 | 246.88 | 0.231020E+09 | 232.26 | ||
Maximum of Months | 0.273947E+09 | 246.88 | 0.255955E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.396945E+10 | 3823.39 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.358405E+10 | 3823.39 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.398168E+10 | 3823.39 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.383486E+10 | 3823.39 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.397633E+10 | 3823.39 | 01-MAY-19:10 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.385245E+10 | 3823.39 | 01-JUN-19:10 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.395874E+10 | 3823.39 | 03-JUL-19:10 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.398321E+10 | 3823.39 | 01-AUG-19:10 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.383639E+10 | 3823.39 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.396792E+10 | 3823.39 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.384939E+10 | 3823.39 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.395874E+10 | 3823.39 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.467532E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.358405E+10 | 3823.39 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.398321E+10 | 3823.39 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.396945E+10 | 3823.39 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.358405E+10 | 3823.39 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.398168E+10 | 3823.39 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.383486E+10 | 3823.39 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.397633E+10 | 3823.39 | 01-MAY-19:10 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.385245E+10 | 3823.39 | 01-JUN-19:10 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.395874E+10 | 3823.39 | 03-JUL-19:10 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.398321E+10 | 3823.39 | 01-AUG-19:10 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.383639E+10 | 3823.39 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.396792E+10 | 3823.39 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.384939E+10 | 3823.39 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.395874E+10 | 3823.39 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.467532E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.358405E+10 | 3823.39 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.398321E+10 | 3823.39 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.105977E+10 | 1020.78 | 02-JAN-20:10 | 0.373720E+11 | 16686.59 | 01-JAN-07:10 |
February | 0.956878E+09 | 1020.78 | 01-FEB-20:10 | 0.337554E+11 | 16686.59 | 01-FEB-07:10 |
March | 0.106304E+10 | 1020.78 | 01-MAR-20:10 | 0.373720E+11 | 16686.59 | 01-MAR-07:10 |
April | 0.102384E+10 | 1020.78 | 03-APR-19:10 | 0.361665E+11 | 16686.59 | 01-APR-06:10 |
May | 0.106161E+10 | 1020.78 | 01-MAY-19:10 | 0.373720E+11 | 16686.59 | 01-MAY-06:10 |
June | 0.102854E+10 | 1020.78 | 01-JUN-19:10 | 0.361665E+11 | 16686.59 | 01-JUN-06:10 |
July | 0.105691E+10 | 1020.78 | 03-JUL-19:10 | 0.373720E+11 | 16686.59 | 01-JUL-06:10 |
August | 0.106345E+10 | 1020.78 | 01-AUG-19:10 | 0.373720E+11 | 16686.59 | 01-AUG-06:10 |
September | 0.102425E+10 | 1020.78 | 01-SEP-19:10 | 0.361665E+11 | 16686.59 | 01-SEP-06:10 |
October | 0.105936E+10 | 1020.78 | 02-OCT-19:10 | 0.373720E+11 | 16686.59 | 01-OCT-06:10 |
November | 0.102772E+10 | 1020.78 | 01-NOV-19:10 | 0.361665E+11 | 16686.59 | 01-NOV-06:10 |
December | 0.105691E+10 | 1020.78 | 01-DEC-20:10 | 0.373720E+11 | 16686.59 | 01-DEC-07:10 |
Annual Sum or Average | 0.124823E+11 | 0.440025E+12 | ||||
Minimum of Months | 0.956878E+09 | 1020.78 | 0.337554E+11 | 16686.59 | ||
Maximum of Months | 0.106345E+10 | 1020.78 | 0.373720E+11 | 16686.59 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.140929E+10 | 1357.44 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.127246E+10 | 1357.44 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.141364E+10 | 1357.44 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.136151E+10 | 1357.44 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.141173E+10 | 1357.44 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.136775E+10 | 1357.44 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.140549E+10 | 1357.44 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.141418E+10 | 1357.44 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.136205E+10 | 1357.44 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.140875E+10 | 1357.44 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.136667E+10 | 1357.44 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.140549E+10 | 1357.44 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.165990E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.127246E+10 | 1357.44 | 0.00 | 0.00 | |
Maximum of Months | 0.141418E+10 | 1357.44 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.195762E+11 | 0.140333E+11 | 0.127587E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.176991E+11 | 0.126708E+11 | 0.115208E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.196682E+11 | 0.140766E+11 | 0.127855E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.189781E+11 | 0.135575E+11 | 0.123314E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.196176E+11 | 0.140576E+11 | 0.127741E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.190195E+11 | 0.136197E+11 | 0.123716E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.195762E+11 | 0.139955E+11 | 0.127338E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.196590E+11 | 0.140820E+11 | 0.127894E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.189689E+11 | 0.135629E+11 | 0.123352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.195854E+11 | 0.140279E+11 | 0.127549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.189367E+11 | 0.136089E+11 | 0.123659E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.195762E+11 | 0.139955E+11 | 0.127338E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.230861E+12 | 0.165288E+12 | 0.150255E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.176991E+11 | 0.126708E+11 | 0.115208E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.196682E+11 | 0.140820E+11 | 0.127894E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.199054E+10 | 0.713551E+09 | 0.864900E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.547176E+09 |
February | 0.179968E+10 | 0.644271E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.451761E+09 |
March | 0.199990E+10 | 0.715750E+09 | 0.866718E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.417410E+09 |
April | 0.192973E+10 | 0.689358E+09 | 0.835931E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3123677.31 | 0.325116E+09 |
May | 0.199475E+10 | 0.714788E+09 | 0.865939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2841885.45 | 0.264249E+09 |
June | 0.193394E+10 | 0.692519E+09 | 0.838659E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5820326.33 | 0.174783E+09 |
July | 0.199054E+10 | 0.711626E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18381632.21 | 0.126914E+09 |
August | 0.199896E+10 | 0.716025E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 31394489.31 | 0.105341E+09 |
September | 0.192879E+10 | 0.689633E+09 | 0.836191E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2540681.60 | 0.190080E+09 |
October | 0.199148E+10 | 0.713276E+09 | 0.864640E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.312363E+09 |
November | 0.192552E+10 | 0.691970E+09 | 0.838269E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.412361E+09 |
December | 0.199054E+10 | 0.711626E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.515097E+09 |
Annual Sum or Average | 0.234744E+11 | 0.840439E+10 | 0.101856E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 64102692.21 | 0.384265E+10 |
Minimum of Months | 0.179968E+10 | 0.644271E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105341E+09 |
Maximum of Months | 0.199990E+10 | 0.716025E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 31394489.31 | 0.547176E+09 |
Report: SpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.230505E+10 | 0.826294E+09 | 0.100156E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.212404E+09 |
February | 0.208403E+10 | 0.746069E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174722E+09 |
March | 0.231589E+10 | 0.828841E+09 | 0.100366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160979E+09 |
April | 0.223463E+10 | 0.798279E+09 | 0.968011E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1348243.83 | 0.125803E+09 |
May | 0.230993E+10 | 0.827727E+09 | 0.100276E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1211787.88 | 0.102615E+09 |
June | 0.223950E+10 | 0.801940E+09 | 0.971170E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2251635.57 | 68304851.54 |
July | 0.230505E+10 | 0.824066E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7207034.40 | 50070225.41 |
August | 0.231480E+10 | 0.829160E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12469742.08 | 41635845.02 |
September | 0.223354E+10 | 0.798597E+09 | 0.968312E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1469281.03 | 73633416.24 |
October | 0.230614E+10 | 0.825976E+09 | 0.100126E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13112.30 | 0.120327E+09 |
November | 0.222975E+10 | 0.801303E+09 | 0.970719E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1881.27 | 0.159363E+09 |
December | 0.230505E+10 | 0.824066E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.199967E+09 |
Annual Sum or Average | 0.271834E+11 | 0.973232E+10 | 0.117950E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 25972718.36 | 0.148982E+10 |
Minimum of Months | 0.208403E+10 | 0.746069E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41635845.02 |
Maximum of Months | 0.231589E+10 | 0.829160E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12469742.08 | 0.212404E+09 |
Report: SpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.487480E+09 | 0.154452E+10 | 0.105898E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.501936E+09 |
February | 0.440737E+09 | 0.139456E+10 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.412692E+09 |
March | 0.489771E+09 | 0.154928E+10 | 0.106120E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.379830E+09 |
April | 0.472586E+09 | 0.149215E+10 | 0.102351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3204000.26 | 0.296296E+09 |
May | 0.488511E+09 | 0.154719E+10 | 0.106025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2874418.21 | 0.241117E+09 |
June | 0.473617E+09 | 0.149899E+10 | 0.102685E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5375384.95 | 0.160081E+09 |
July | 0.487480E+09 | 0.154035E+10 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17187562.42 | 0.116601E+09 |
August | 0.489542E+09 | 0.154987E+10 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29851118.42 | 96727557.40 |
September | 0.472357E+09 | 0.149274E+10 | 0.102382E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3483754.81 | 0.172425E+09 |
October | 0.487709E+09 | 0.154392E+10 | 0.105866E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31044.64 | 0.283501E+09 |
November | 0.471555E+09 | 0.149780E+10 | 0.102637E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4457.37 | 0.376416E+09 |
December | 0.487480E+09 | 0.154035E+10 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.472525E+09 |
Annual Sum or Average | 0.574883E+10 | 0.181917E+11 | 0.124712E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 62011741.08 | 0.351015E+10 |
Minimum of Months | 0.440737E+09 | 0.139456E+10 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96727557.40 |
Maximum of Months | 0.489771E+09 | 0.154987E+10 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29851118.42 | 0.501936E+09 |
Report: SpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.374985E+09 | 0.283535E+09 | 0.305485E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.289590E+09 |
February | 0.339028E+09 | 0.256006E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.238099E+09 |
March | 0.376747E+09 | 0.284409E+09 | 0.306128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219138E+09 |
April | 0.363528E+09 | 0.273921E+09 | 0.295253E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1849731.44 | 0.170896E+09 |
May | 0.375778E+09 | 0.284026E+09 | 0.305852E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1659791.90 | 0.138903E+09 |
June | 0.364321E+09 | 0.275178E+09 | 0.296217E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3120332.60 | 91986381.16 |
July | 0.374985E+09 | 0.282770E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10000511.03 | 66782664.51 |
August | 0.376571E+09 | 0.284518E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17463261.03 | 55413407.03 |
September | 0.363352E+09 | 0.274031E+09 | 0.295345E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2011340.86 | 99221706.10 |
October | 0.375161E+09 | 0.283425E+09 | 0.305393E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17919.21 | 0.163530E+09 |
November | 0.362735E+09 | 0.274959E+09 | 0.296079E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2558.37 | 0.217171E+09 |
December | 0.374985E+09 | 0.282770E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.272621E+09 |
Annual Sum or Average | 0.442217E+10 | 0.333955E+10 | 0.359760E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36125446.42 | 0.202335E+10 |
Minimum of Months | 0.339028E+09 | 0.256006E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55413407.03 |
Maximum of Months | 0.376747E+09 | 0.284518E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17463261.03 | 0.289590E+09 |
Report: SpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.154405E+10 | 0.350256E+09 | 0.576866E+10 | 0.501157E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.703383E+09 |
February | 0.139600E+10 | 0.316249E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.579533E+09 |
March | 0.155131E+10 | 0.351336E+09 | 0.578079E+10 | 0.502211E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.536369E+09 |
April | 0.149688E+10 | 0.338381E+09 | 0.557545E+10 | 0.484372E+11 | 0.00 | 0.00 | 0.00 | 4103081.00 | 0.420239E+09 |
May | 0.154732E+10 | 0.350863E+09 | 0.577559E+10 | 0.501759E+11 | 0.00 | 0.00 | 0.00 | 3806810.55 | 0.344877E+09 |
June | 0.150015E+10 | 0.339933E+09 | 0.559364E+10 | 0.485952E+11 | 0.00 | 0.00 | 0.00 | 6722008.93 | 0.232226E+09 |
July | 0.154405E+10 | 0.349311E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 21881577.54 | 0.170872E+09 |
August | 0.155059E+10 | 0.351471E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 37463301.45 | 0.142442E+09 |
September | 0.149615E+10 | 0.338516E+09 | 0.557718E+10 | 0.484522E+11 | 0.00 | 0.00 | 0.00 | 4694928.29 | 0.250193E+09 |
October | 0.154478E+10 | 0.350121E+09 | 0.576693E+10 | 0.501006E+11 | 0.00 | 0.00 | 0.00 | 41881.37 | 0.404064E+09 |
November | 0.149361E+10 | 0.339663E+09 | 0.559104E+10 | 0.485726E+11 | 0.00 | 0.00 | 0.00 | 5708.89 | 0.531093E+09 |
December | 0.154405E+10 | 0.349311E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.663007E+09 |
Annual Sum or Average | 0.182090E+11 | 0.412541E+10 | 0.679355E+11 | 0.590196E+12 | 0.00 | 0.00 | 0.00 | 78719298.02 | 0.497830E+10 |
Minimum of Months | 0.139600E+10 | 0.316249E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142442E+09 |
Maximum of Months | 0.155131E+10 | 0.351471E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 37463301.45 | 0.703383E+09 |
Report: SpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.261570E+11 | 0.226040E+10 | 0.121771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121623E+10 |
February | 0.236489E+11 | 0.204093E+10 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100107E+10 |
March | 0.262800E+11 | 0.226736E+10 | 0.122027E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.922321E+09 |
April | 0.253579E+11 | 0.218376E+10 | 0.117692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7234711.56 | 0.718332E+09 |
May | 0.262123E+11 | 0.226431E+10 | 0.121917E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6685908.09 | 0.583907E+09 |
June | 0.254132E+11 | 0.219377E+10 | 0.118076E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13092459.29 | 0.386553E+09 |
July | 0.261570E+11 | 0.225430E+10 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41721184.94 | 0.280737E+09 |
August | 0.262677E+11 | 0.226823E+10 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 71422913.51 | 0.233160E+09 |
September | 0.253456E+11 | 0.218463E+10 | 0.117729E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6490097.56 | 0.418853E+09 |
October | 0.261693E+11 | 0.225952E+10 | 0.121734E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.689313E+09 |
November | 0.253025E+11 | 0.219203E+10 | 0.118021E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.912754E+09 |
December | 0.261570E+11 | 0.225430E+10 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114473E+10 |
Annual Sum or Average | 0.308468E+12 | 0.266236E+11 | 0.143405E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146647E+09 | 0.850796E+10 |
Minimum of Months | 0.236489E+11 | 0.204093E+10 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.233160E+09 |
Maximum of Months | 0.262800E+11 | 0.226823E+10 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 71422913.51 | 0.121623E+10 |
Report: SpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.776503E+11 | 0.123020E+11 | 0.126520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.347725E+10 |
February | 0.702046E+11 | 0.111075E+11 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.286103E+10 |
March | 0.780153E+11 | 0.123399E+11 | 0.126786E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.263730E+10 |
April | 0.752779E+11 | 0.118849E+11 | 0.122282E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 22110119.84 | 0.206173E+10 |
May | 0.778146E+11 | 0.123233E+11 | 0.126672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 19868887.41 | 0.168282E+10 |
June | 0.754422E+11 | 0.119394E+11 | 0.122682E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 37112375.96 | 0.112415E+10 |
July | 0.776503E+11 | 0.122688E+11 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118703E+09 | 0.826038E+09 |
August | 0.779788E+11 | 0.123446E+11 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.204961E+09 | 0.690303E+09 |
September | 0.752414E+11 | 0.118896E+11 | 0.122320E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 23981965.19 | 0.121059E+10 |
October | 0.776868E+11 | 0.122972E+11 | 0.126482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 170239.09 | 0.197324E+10 |
November | 0.751137E+11 | 0.119299E+11 | 0.122624E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 25633.35 | 0.261018E+10 |
December | 0.776503E+11 | 0.122688E+11 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.327368E+10 |
Annual Sum or Average | 0.915726E+12 | 0.144896E+12 | 0.148998E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.426933E+09 | 0.244283E+11 |
Minimum of Months | 0.702046E+11 | 0.111075E+11 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.690303E+09 |
Maximum of Months | 0.780153E+11 | 0.123446E+11 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.204961E+09 | 0.347725E+10 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.434056E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.314252E+09 |
February | 0.273974E+09 | 0.391995E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.262858E+09 |
March | 0.303685E+09 | 0.430607E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.246505E+09 |
April | 0.293479E+09 | 0.420554E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1325986.60 | 0.196697E+09 |
May | 0.303504E+09 | 0.432331E+09 | 0.260888E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 780000.61 | 0.163575E+09 |
June | 0.293842E+09 | 0.417218E+09 | 0.252344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1833867.84 | 0.111660E+09 |
July | 0.303141E+09 | 0.435725E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7295076.58 | 82944680.68 |
August | 0.303685E+09 | 0.430607E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13836818.78 | 68310565.13 |
September | 0.293479E+09 | 0.420667E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1066757.67 | 0.118893E+09 |
October | 0.303322E+09 | 0.434000E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4111.69 | 0.187236E+09 |
November | 0.293661E+09 | 0.418886E+09 | 0.252524E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.238824E+09 |
December | 0.303141E+09 | 0.435781E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.297270E+09 |
Annual Sum or Average | 0.357224E+10 | 0.510243E+10 | 0.307301E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26142619.77 | 0.228903E+10 |
Minimum of Months | 0.273974E+09 | 0.391995E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68310565.13 |
Maximum of Months | 0.303685E+09 | 0.435781E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13836818.78 | 0.314252E+09 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.434005E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.311786E+09 |
February | 0.273974E+09 | 0.391949E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.259206E+09 |
March | 0.303685E+09 | 0.430556E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.242610E+09 |
April | 0.293479E+09 | 0.420505E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1365244.53 | 0.194025E+09 |
May | 0.303504E+09 | 0.432281E+09 | 0.260857E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 785186.67 | 0.162222E+09 |
June | 0.293842E+09 | 0.417169E+09 | 0.252315E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1832678.80 | 0.110695E+09 |
July | 0.303141E+09 | 0.435674E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7337252.82 | 82336670.01 |
August | 0.303685E+09 | 0.430556E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13989428.53 | 67617636.99 |
September | 0.293479E+09 | 0.420618E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1078687.71 | 0.117204E+09 |
October | 0.303322E+09 | 0.433949E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4419.60 | 0.183556E+09 |
November | 0.293661E+09 | 0.418837E+09 | 0.252495E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.236121E+09 |
December | 0.303141E+09 | 0.435730E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.294154E+09 |
Annual Sum or Average | 0.357224E+10 | 0.510183E+10 | 0.307265E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26392898.65 | 0.226153E+10 |
Minimum of Months | 0.273974E+09 | 0.391949E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67617636.99 |
Maximum of Months | 0.303685E+09 | 0.435730E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13989428.53 | 0.311786E+09 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.272788E+09 | 0.255708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82168222.99 |
February | 0.00 | 0.246354E+09 | 0.230956E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73757970.97 |
March | 0.00 | 0.270620E+09 | 0.255355E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75826067.20 |
April | 0.00 | 0.264302E+09 | 0.247516E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 237975.97 | 62698562.79 |
May | 0.00 | 0.271704E+09 | 0.255532E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 51802.44 | 53866372.44 |
June | 0.00 | 0.262205E+09 | 0.247163E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 187482.99 | 39091012.83 |
July | 0.00 | 0.273836E+09 | 0.255885E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1246158.25 | 30788049.21 |
August | 0.00 | 0.270620E+09 | 0.255355E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2647816.48 | 26317233.05 |
September | 0.00 | 0.264373E+09 | 0.247516E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 58409.68 | 41566999.12 |
October | 0.00 | 0.272752E+09 | 0.255708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61264949.06 |
November | 0.00 | 0.263254E+09 | 0.247340E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69914154.56 |
December | 0.00 | 0.273872E+09 | 0.255885E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80064536.82 |
Annual Sum or Average | 0.00 | 0.320668E+10 | 0.300992E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4429645.82 | 0.697324E+09 |
Minimum of Months | 0.00 | 0.246354E+09 | 0.230956E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26317233.05 |
Maximum of Months | 0.00 | 0.273872E+09 | 0.255885E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2647816.48 | 82168222.99 |
Report: SpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.272862E+09 | 0.255778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88806218.61 |
February | 0.273974E+09 | 0.246421E+09 | 0.231020E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73522138.42 |
March | 0.303685E+09 | 0.270694E+09 | 0.255425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68685797.79 |
April | 0.293479E+09 | 0.264375E+09 | 0.247584E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 444940.29 | 54411409.89 |
May | 0.303504E+09 | 0.271778E+09 | 0.255602E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 253704.27 | 45051880.04 |
June | 0.293842E+09 | 0.262277E+09 | 0.247231E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 562867.06 | 30558650.48 |
July | 0.303141E+09 | 0.273911E+09 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2215389.26 | 22552867.93 |
August | 0.303685E+09 | 0.270694E+09 | 0.255425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4195505.75 | 18599230.04 |
September | 0.293479E+09 | 0.264446E+09 | 0.247584E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 360759.85 | 32481748.62 |
October | 0.303322E+09 | 0.272827E+09 | 0.255778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1300.47 | 51924972.39 |
November | 0.293661E+09 | 0.263326E+09 | 0.247408E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67476721.53 |
December | 0.303141E+09 | 0.273947E+09 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83817189.91 |
Annual Sum or Average | 0.357224E+10 | 0.320756E+10 | 0.301074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8034466.95 | 0.637889E+09 |
Minimum of Months | 0.273974E+09 | 0.246421E+09 | 0.231020E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18599230.04 |
Maximum of Months | 0.303685E+09 | 0.273947E+09 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4195505.75 | 88806218.61 |
Report: SpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.434056E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.313955E+09 |
February | 0.273974E+09 | 0.391995E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.262985E+09 |
March | 0.303685E+09 | 0.430607E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.247560E+09 |
April | 0.293479E+09 | 0.420554E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1345831.68 | 0.198228E+09 |
May | 0.303504E+09 | 0.432331E+09 | 0.260888E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 798503.92 | 0.164051E+09 |
June | 0.293842E+09 | 0.417218E+09 | 0.252344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1859906.15 | 0.112564E+09 |
July | 0.303141E+09 | 0.435725E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7359236.83 | 83379841.59 |
August | 0.303685E+09 | 0.430607E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13851757.37 | 68895361.45 |
September | 0.293479E+09 | 0.420667E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1086094.26 | 0.119004E+09 |
October | 0.303322E+09 | 0.434000E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4440.72 | 0.187859E+09 |
November | 0.293661E+09 | 0.418886E+09 | 0.252524E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.238694E+09 |
December | 0.303141E+09 | 0.435781E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.296924E+09 |
Annual Sum or Average | 0.357224E+10 | 0.510243E+10 | 0.307301E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26305770.92 | 0.229410E+10 |
Minimum of Months | 0.273974E+09 | 0.391995E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68895361.45 |
Maximum of Months | 0.303685E+09 | 0.435781E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13851757.37 | 0.313955E+09 |
Report: SpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.434005E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.311623E+09 |
February | 0.273974E+09 | 0.391949E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.259071E+09 |
March | 0.303685E+09 | 0.430556E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.243836E+09 |
April | 0.293479E+09 | 0.420505E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1381544.19 | 0.196247E+09 |
May | 0.303504E+09 | 0.432281E+09 | 0.260857E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 804266.25 | 0.163184E+09 |
June | 0.293842E+09 | 0.417169E+09 | 0.252315E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1864730.87 | 0.112231E+09 |
July | 0.303141E+09 | 0.435674E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7378792.42 | 83175787.60 |
August | 0.303685E+09 | 0.430556E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13887504.76 | 68540395.89 |
September | 0.293479E+09 | 0.420618E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1104259.63 | 0.117830E+09 |
October | 0.303322E+09 | 0.433949E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4560.70 | 0.184467E+09 |
November | 0.293661E+09 | 0.418837E+09 | 0.252495E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235962E+09 |
December | 0.303141E+09 | 0.435730E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.293791E+09 |
Annual Sum or Average | 0.357224E+10 | 0.510183E+10 | 0.307265E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26425658.81 | 0.226996E+10 |
Minimum of Months | 0.273974E+09 | 0.391949E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68540395.89 |
Maximum of Months | 0.303685E+09 | 0.435730E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13887504.76 | 0.311623E+09 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.385223E+10 | 0.133160E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.387164E+09 |
February | 0.348285E+10 | 0.120231E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.318402E+09 |
March | 0.387034E+10 | 0.133570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.293243E+09 |
April | 0.373454E+10 | 0.128645E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2323335.09 | 0.229067E+09 |
May | 0.386038E+10 | 0.133391E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1960532.95 | 0.186742E+09 |
June | 0.374269E+10 | 0.129235E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3773053.41 | 0.124460E+09 |
July | 0.385223E+10 | 0.132801E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12055800.90 | 91879093.72 |
August | 0.386853E+10 | 0.133622E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20914109.41 | 77195545.92 |
September | 0.373273E+10 | 0.128696E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1999144.50 | 0.134682E+09 |
October | 0.385404E+10 | 0.133109E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2285.27 | 0.219291E+09 |
November | 0.372639E+10 | 0.129132E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.290560E+09 |
December | 0.385223E+10 | 0.132801E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.364513E+09 |
Annual Sum or Average | 0.454292E+11 | 0.156839E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43028261.54 | 0.271720E+10 |
Minimum of Months | 0.348285E+10 | 0.120231E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77195545.92 |
Maximum of Months | 0.387034E+10 | 0.133622E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20914109.41 | 0.387164E+09 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.434056E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.313641E+09 |
February | 0.273974E+09 | 0.391995E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.262386E+09 |
March | 0.303685E+09 | 0.430607E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.246429E+09 |
April | 0.293479E+09 | 0.420554E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1292615.58 | 0.197455E+09 |
May | 0.303504E+09 | 0.432331E+09 | 0.260888E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 721213.71 | 0.164774E+09 |
June | 0.293842E+09 | 0.417218E+09 | 0.252344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1763792.49 | 0.112968E+09 |
July | 0.303141E+09 | 0.435725E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7106294.13 | 84008140.21 |
August | 0.303685E+09 | 0.430607E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13521708.01 | 69258194.69 |
September | 0.293479E+09 | 0.420667E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1014977.96 | 0.119919E+09 |
October | 0.303322E+09 | 0.434000E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3040.11 | 0.187434E+09 |
November | 0.293661E+09 | 0.418886E+09 | 0.252524E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.238162E+09 |
December | 0.303141E+09 | 0.435781E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.296863E+09 |
Annual Sum or Average | 0.357224E+10 | 0.510243E+10 | 0.307301E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25423642.00 | 0.229330E+10 |
Minimum of Months | 0.273974E+09 | 0.391995E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69258194.69 |
Maximum of Months | 0.303685E+09 | 0.435781E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13521708.01 | 0.313641E+09 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.434005E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.311834E+09 |
February | 0.273974E+09 | 0.391949E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258823E+09 |
March | 0.303685E+09 | 0.430556E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.242367E+09 |
April | 0.293479E+09 | 0.420505E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1315418.10 | 0.194882E+09 |
May | 0.303504E+09 | 0.432281E+09 | 0.260857E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 733805.30 | 0.163777E+09 |
June | 0.293842E+09 | 0.417169E+09 | 0.252315E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1758807.48 | 0.112435E+09 |
July | 0.303141E+09 | 0.435674E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7110037.82 | 83738151.36 |
August | 0.303685E+09 | 0.430556E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13589800.17 | 68826091.49 |
September | 0.293479E+09 | 0.420618E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1036877.57 | 0.118637E+09 |
October | 0.303322E+09 | 0.433949E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3306.63 | 0.183635E+09 |
November | 0.293661E+09 | 0.418837E+09 | 0.252495E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235541E+09 |
December | 0.303141E+09 | 0.435730E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.293967E+09 |
Annual Sum or Average | 0.357224E+10 | 0.510183E+10 | 0.307265E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25548053.06 | 0.226846E+10 |
Minimum of Months | 0.273974E+09 | 0.391949E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68826091.49 |
Maximum of Months | 0.303685E+09 | 0.435730E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13589800.17 | 0.311834E+09 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.272862E+09 | 0.255778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163821E+09 |
February | 0.273974E+09 | 0.246421E+09 | 0.231020E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137102E+09 |
March | 0.303685E+09 | 0.270694E+09 | 0.255425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128381E+09 |
April | 0.293479E+09 | 0.264375E+09 | 0.247584E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 666032.01 | 0.102186E+09 |
May | 0.303504E+09 | 0.271778E+09 | 0.255602E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 386155.86 | 84598845.30 |
June | 0.293842E+09 | 0.262277E+09 | 0.247231E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 915779.71 | 57918801.53 |
July | 0.303141E+09 | 0.273911E+09 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3669036.92 | 42971815.11 |
August | 0.303685E+09 | 0.270694E+09 | 0.255425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6940575.82 | 35499848.91 |
September | 0.293479E+09 | 0.264446E+09 | 0.247584E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 526128.21 | 61841277.70 |
October | 0.303322E+09 | 0.272827E+09 | 0.255778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1533.63 | 97805920.79 |
November | 0.293661E+09 | 0.263326E+09 | 0.247408E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124749E+09 |
December | 0.303141E+09 | 0.273947E+09 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154844E+09 |
Annual Sum or Average | 0.357224E+10 | 0.320756E+10 | 0.301074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13105242.16 | 0.119172E+10 |
Minimum of Months | 0.273974E+09 | 0.246421E+09 | 0.231020E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35499848.91 |
Maximum of Months | 0.303685E+09 | 0.273947E+09 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6940575.82 | 0.163821E+09 |
Report: SpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.396945E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.801910E+09 |
February | 0.415303E+11 | 0.358405E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.662690E+09 |
March | 0.461508E+11 | 0.398168E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.618224E+09 |
April | 0.445315E+11 | 0.383486E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 4393709.68 | 0.490146E+09 |
May | 0.460320E+11 | 0.397633E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 3534227.87 | 0.409248E+09 |
June | 0.446286E+11 | 0.385245E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 6425338.70 | 0.284254E+09 |
July | 0.459349E+11 | 0.395874E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 22322253.87 | 0.216973E+09 |
August | 0.461292E+11 | 0.398321E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 40639150.51 | 0.183578E+09 |
September | 0.445099E+11 | 0.383639E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 4423080.29 | 0.300358E+09 |
October | 0.459565E+11 | 0.396792E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 12409.37 | 0.470111E+09 |
November | 0.444343E+11 | 0.384939E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.609945E+09 |
December | 0.459349E+11 | 0.395874E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.756489E+09 |
Annual Sum or Average | 0.541708E+12 | 0.467532E+11 | 0.175857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 81750170.29 | 0.580393E+10 |
Minimum of Months | 0.415303E+11 | 0.358405E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183578E+09 |
Maximum of Months | 0.461508E+11 | 0.398321E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 40639150.51 | 0.801910E+09 |
Report: SpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.396945E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.804308E+09 |
February | 0.415303E+11 | 0.358405E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.665009E+09 |
March | 0.461508E+11 | 0.398168E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.621181E+09 |
April | 0.445315E+11 | 0.383486E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 4258674.50 | 0.493377E+09 |
May | 0.460320E+11 | 0.397633E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 3268693.19 | 0.413059E+09 |
June | 0.446286E+11 | 0.385245E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 5973807.44 | 0.288082E+09 |
July | 0.459349E+11 | 0.395874E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 21423080.66 | 0.220712E+09 |
August | 0.461292E+11 | 0.398321E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 39628271.85 | 0.186697E+09 |
September | 0.445099E+11 | 0.383639E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 4183164.09 | 0.303569E+09 |
October | 0.459565E+11 | 0.396792E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 7936.66 | 0.473166E+09 |
November | 0.444343E+11 | 0.384939E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.612707E+09 |
December | 0.459349E+11 | 0.395874E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.758961E+09 |
Annual Sum or Average | 0.541708E+12 | 0.467532E+11 | 0.175857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 78743628.40 | 0.584083E+10 |
Minimum of Months | 0.415303E+11 | 0.358405E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.186697E+09 |
Maximum of Months | 0.461508E+11 | 0.398321E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 39628271.85 | 0.804308E+09 |
Report: SpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.408770E+10 | 0.105977E+10 | 0.338870E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.769093E+09 |
February | 0.369574E+10 | 0.956878E+09 | 0.306077E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.641269E+09 |
March | 0.410691E+10 | 0.106304E+10 | 0.338870E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.606959E+09 |
April | 0.396281E+10 | 0.102384E+10 | 0.327939E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 1284427.21 | 0.488907E+09 |
May | 0.409635E+10 | 0.106161E+10 | 0.338870E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 83540.55 | 0.415593E+09 |
June | 0.397146E+10 | 0.102854E+10 | 0.327939E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 692146.07 | 0.298689E+09 |
July | 0.408770E+10 | 0.105691E+10 | 0.338870E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 7258667.13 | 0.230726E+09 |
August | 0.410499E+10 | 0.106345E+10 | 0.338870E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 16222288.35 | 0.194068E+09 |
September | 0.396089E+10 | 0.102425E+10 | 0.327939E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 106705.62 | 0.316114E+09 |
October | 0.408962E+10 | 0.105936E+10 | 0.338870E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.474018E+09 |
November | 0.395417E+10 | 0.102772E+10 | 0.327939E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.595843E+09 |
December | 0.408770E+10 | 0.105691E+10 | 0.338870E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.729049E+09 |
Annual Sum or Average | 0.482060E+11 | 0.124823E+11 | 0.398993E+12 | 0.359593E+12 | 0.00 | 0.00 | 0.00 | 25647774.92 | 0.576033E+10 |
Minimum of Months | 0.369574E+10 | 0.956878E+09 | 0.306077E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.194068E+09 |
Maximum of Months | 0.410691E+10 | 0.106345E+10 | 0.338870E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 16222288.35 | 0.769093E+09 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.407704E+10 | 0.140929E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.687579E+09 |
February | 0.368610E+10 | 0.127246E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.565614E+09 |
March | 0.409620E+10 | 0.141364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.521385E+09 |
April | 0.395248E+10 | 0.136151E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3946075.22 | 0.407294E+09 |
May | 0.408566E+10 | 0.141173E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3170256.84 | 0.332056E+09 |
June | 0.396110E+10 | 0.136775E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6236438.21 | 0.220934E+09 |
July | 0.407704E+10 | 0.140549E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20840005.37 | 0.161212E+09 |
August | 0.409429E+10 | 0.141418E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37458929.51 | 0.133844E+09 |
September | 0.395056E+10 | 0.136205E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3399033.23 | 0.238413E+09 |
October | 0.407896E+10 | 0.140875E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1886.73 | 0.390162E+09 |
November | 0.394385E+10 | 0.136667E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.516574E+09 |
December | 0.407704E+10 | 0.140549E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.647542E+09 |
Annual Sum or Average | 0.480803E+11 | 0.165990E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75052625.11 | 0.482261E+10 |
Minimum of Months | 0.368610E+10 | 0.127246E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133844E+09 |
Maximum of Months | 0.409620E+10 | 0.141418E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37458929.51 | 0.687579E+09 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 11501.89 | 02-JAN-00:10 | 13517.00 | 02-JAN-20:10 | 10113.80 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 11501.89 | 01-FEB-00:10 | 13517.00 | 01-FEB-20:10 | 10113.80 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 11501.89 | 01-MAR-00:10 | 13517.00 | 01-MAR-20:10 | 10113.80 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 11501.89 | 01-APR-00:10 | 13517.00 | 03-APR-19:10 | 10113.80 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 11501.89 | 01-MAY-00:10 | 13517.00 | 01-MAY-19:10 | 10113.80 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 11501.89 | 01-JUN-00:10 | 13517.00 | 01-JUN-19:10 | 10113.80 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 11501.89 | 01-JUL-00:10 | 13517.00 | 03-JUL-19:10 | 10113.80 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 11501.89 | 01-AUG-00:10 | 13517.00 | 01-AUG-19:10 | 10113.80 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 11501.89 | 01-SEP-00:10 | 13517.00 | 01-SEP-19:10 | 10113.80 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 11501.89 | 01-OCT-23:10 | 13517.00 | 02-OCT-19:10 | 10113.80 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 11501.89 | 01-NOV-00:10 | 13517.00 | 01-NOV-19:10 | 10113.80 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 11501.89 | 01-DEC-00:10 | 13517.00 | 01-DEC-20:10 | 10113.80 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 11501.89 | 13517.00 | 10113.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 11501.89 | 13517.00 | 10113.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1169.53 | 02-JAN-00:10 | 687.30 | 02-JAN-20:10 | 685.60 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 316.10 | 15-JAN-08:00 |
February | 1169.53 | 01-FEB-00:10 | 687.30 | 01-FEB-20:10 | 685.60 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 328.03 | 19-FEB-05:00 |
March | 1169.53 | 01-MAR-00:10 | 687.30 | 01-MAR-20:10 | 685.60 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 275.18 | 01-MAR-07:00 |
April | 1169.53 | 01-APR-00:10 | 687.30 | 03-APR-19:10 | 685.60 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 70.72 | 27-APR-16:00 | 243.90 | 19-APR-05:00 |
May | 1169.53 | 01-MAY-00:10 | 687.30 | 01-MAY-19:10 | 685.60 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.11 | 05-MAY-16:00 | 206.19 | 11-MAY-03:30 |
June | 1169.53 | 01-JUN-00:10 | 687.30 | 01-JUN-19:10 | 685.60 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 65.49 | 28-JUN-17:00 | 155.07 | 15-JUN-03:10 |
July | 1169.53 | 01-JUL-00:10 | 687.30 | 03-JUL-19:10 | 685.60 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 105.69 | 24-JUL-15:00 | 120.45 | 07-JUL-05:00 |
August | 1169.53 | 01-AUG-00:10 | 687.30 | 01-AUG-19:10 | 685.60 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 120.92 | 10-AUG-17:00 | 121.81 | 21-AUG-05:00 |
September | 1169.53 | 01-SEP-00:10 | 687.30 | 01-SEP-19:10 | 685.60 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.17 | 14-SEP-17:00 | 169.93 | 27-SEP-05:00 |
October | 1169.53 | 01-OCT-23:10 | 687.30 | 02-OCT-19:10 | 685.60 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 190.22 | 13-OCT-05:00 |
November | 1169.53 | 01-NOV-00:10 | 687.30 | 01-NOV-19:10 | 685.60 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 264.99 | 11-NOV-08:00 |
December | 1169.53 | 01-DEC-00:10 | 687.30 | 01-DEC-20:10 | 685.60 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 284.06 | 26-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1169.53 | 687.30 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 120.45 | |||||
Maximum of Months | 1169.53 | 687.30 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 120.92 | 328.03 |
Report: PeakSpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1354.32 | 02-JAN-00:10 | 795.89 | 02-JAN-20:10 | 793.93 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 124.80 | 15-JAN-08:00 |
February | 1354.32 | 01-FEB-00:10 | 795.89 | 01-FEB-20:10 | 793.93 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 130.87 | 19-FEB-06:00 |
March | 1354.32 | 01-MAR-00:10 | 795.89 | 01-MAR-20:10 | 793.93 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 106.34 | 01-MAR-07:00 |
April | 1354.32 | 01-APR-00:10 | 795.89 | 03-APR-19:10 | 793.93 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.31 | 27-APR-15:20 | 94.16 | 19-APR-05:00 |
May | 1354.32 | 01-MAY-00:10 | 795.89 | 01-MAY-19:10 | 793.93 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.79 | 05-MAY-16:00 | 79.59 | 11-MAY-03:20 |
June | 1354.32 | 01-JUN-00:10 | 795.89 | 01-JUN-19:10 | 793.93 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.26 | 28-JUN-17:00 | 59.84 | 15-JUN-03:20 |
July | 1354.32 | 01-JUL-00:10 | 795.89 | 03-JUL-19:10 | 793.93 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 41.85 | 24-JUL-15:00 | 46.51 | 07-JUL-05:00 |
August | 1354.32 | 01-AUG-00:10 | 795.89 | 01-AUG-19:10 | 793.93 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.67 | 10-AUG-17:00 | 47.00 | 21-AUG-05:00 |
September | 1354.32 | 01-SEP-00:10 | 795.89 | 01-SEP-19:10 | 793.93 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.82 | 14-SEP-17:00 | 65.58 | 27-SEP-05:00 |
October | 1354.32 | 01-OCT-23:10 | 795.89 | 02-OCT-19:10 | 793.93 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.12 | 04-OCT-15:00 | 73.44 | 13-OCT-05:00 |
November | 1354.32 | 01-NOV-00:10 | 795.89 | 01-NOV-19:10 | 793.93 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.44 | 04-NOV-14:10 | 102.27 | 11-NOV-07:00 |
December | 1354.32 | 01-DEC-00:10 | 795.89 | 01-DEC-20:10 | 793.93 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 112.45 | 26-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1354.32 | 795.89 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.51 | |||||
Maximum of Months | 1354.32 | 795.89 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 46.67 | 130.87 |
Report: PeakSpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 286.42 | 02-JAN-00:10 | 1487.69 | 02-JAN-20:10 | 839.45 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 294.93 | 15-JAN-08:00 |
February | 286.42 | 01-FEB-00:10 | 1487.69 | 01-FEB-20:10 | 839.45 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 309.28 | 19-FEB-06:00 |
March | 286.42 | 01-MAR-00:10 | 1487.69 | 01-MAR-20:10 | 839.45 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 251.30 | 01-MAR-07:00 |
April | 286.42 | 01-APR-00:10 | 1487.69 | 03-APR-19:10 | 839.45 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 64.54 | 27-APR-15:30 | 222.52 | 19-APR-05:00 |
May | 286.42 | 01-MAY-00:10 | 1487.69 | 01-MAY-19:10 | 839.45 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.06 | 05-MAY-16:00 | 188.08 | 11-MAY-03:00 |
June | 286.42 | 01-JUN-00:10 | 1487.69 | 01-JUN-19:10 | 839.45 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 59.73 | 28-JUN-17:00 | 141.40 | 15-JUN-03:40 |
July | 286.42 | 01-JUL-00:10 | 1487.69 | 03-JUL-19:10 | 839.45 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 98.92 | 24-JUL-15:00 | 109.93 | 07-JUL-05:00 |
August | 286.42 | 01-AUG-00:10 | 1487.69 | 01-AUG-19:10 | 839.45 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 110.30 | 10-AUG-17:00 | 111.10 | 21-AUG-05:00 |
September | 286.42 | 01-SEP-00:10 | 1487.69 | 01-SEP-19:10 | 839.45 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.15 | 14-SEP-17:00 | 154.99 | 27-SEP-05:00 |
October | 286.42 | 01-OCT-23:10 | 1487.69 | 02-OCT-19:10 | 839.45 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.37 | 04-OCT-15:00 | 173.57 | 13-OCT-05:00 |
November | 286.42 | 01-NOV-00:10 | 1487.69 | 01-NOV-19:10 | 839.45 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.05 | 04-NOV-14:00 | 241.68 | 11-NOV-07:20 |
December | 286.42 | 01-DEC-00:10 | 1487.69 | 01-DEC-20:10 | 839.45 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 265.75 | 26-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 286.42 | 1487.69 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.93 | |||||
Maximum of Months | 286.42 | 1487.69 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 110.30 | 309.28 |
Report: PeakSpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 220.32 | 02-JAN-00:10 | 273.10 | 02-JAN-20:10 | 242.16 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 170.17 | 15-JAN-08:00 |
February | 220.32 | 01-FEB-00:10 | 273.10 | 01-FEB-20:10 | 242.16 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 178.22 | 19-FEB-06:00 |
March | 220.32 | 01-MAR-00:10 | 273.10 | 01-MAR-20:10 | 242.16 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 144.98 | 01-MAR-07:00 |
April | 220.32 | 01-APR-00:10 | 273.10 | 03-APR-19:10 | 242.16 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.24 | 27-APR-15:00 | 128.38 | 19-APR-05:00 |
May | 220.32 | 01-MAY-00:10 | 273.10 | 01-MAY-19:10 | 242.16 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.26 | 05-MAY-16:00 | 108.51 | 11-MAY-03:40 |
June | 220.32 | 01-JUN-00:10 | 273.10 | 01-JUN-19:10 | 242.16 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.45 | 28-JUN-17:00 | 81.58 | 15-JUN-03:20 |
July | 220.32 | 01-JUL-00:10 | 273.10 | 03-JUL-19:10 | 242.16 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 57.08 | 24-JUL-15:00 | 63.42 | 07-JUL-05:00 |
August | 220.32 | 01-AUG-00:10 | 273.10 | 01-AUG-19:10 | 242.16 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 63.63 | 10-AUG-17:00 | 64.09 | 21-AUG-05:00 |
September | 220.32 | 01-SEP-00:10 | 273.10 | 01-SEP-19:10 | 242.16 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.31 | 14-SEP-17:00 | 89.43 | 27-SEP-05:00 |
October | 220.32 | 01-OCT-23:10 | 273.10 | 02-OCT-19:10 | 242.16 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.26 | 04-OCT-15:00 | 100.13 | 13-OCT-05:00 |
November | 220.32 | 01-NOV-00:10 | 273.10 | 01-NOV-19:10 | 242.16 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 | 04-NOV-14:50 | 139.45 | 11-NOV-07:10 |
December | 220.32 | 01-DEC-00:10 | 273.10 | 01-DEC-20:10 | 242.16 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 153.31 | 26-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 220.32 | 273.10 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.42 | |||||
Maximum of Months | 220.32 | 273.10 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 63.63 | 178.22 |
Report: PeakSpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 907.20 | 02-JAN-00:10 | 337.37 | 02-JAN-20:10 | 4572.80 | 02-JAN-20:10 | 39726.58 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 402.80 | 15-JAN-08:00 |
February | 907.20 | 01-FEB-00:10 | 337.37 | 01-FEB-20:10 | 4572.80 | 01-FEB-20:10 | 39726.58 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 422.22 | 19-FEB-05:50 |
March | 907.20 | 01-MAR-00:10 | 337.37 | 01-MAR-20:10 | 4572.80 | 01-MAR-20:10 | 39726.58 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 343.01 | 01-MAR-07:00 |
April | 907.20 | 01-APR-00:10 | 337.37 | 03-APR-19:10 | 4572.80 | 03-APR-19:10 | 39726.58 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 88.27 | 27-APR-15:00 | 303.79 | 19-APR-05:00 |
May | 907.20 | 01-MAY-00:10 | 337.37 | 01-MAY-19:10 | 4572.80 | 01-MAY-19:10 | 39726.58 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 57.61 | 05-MAY-16:00 | 263.22 | 17-MAY-21:00 |
June | 907.20 | 01-JUN-00:10 | 337.37 | 01-JUN-19:10 | 4572.80 | 01-JUN-19:10 | 39726.58 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 81.54 | 28-JUN-17:00 | 210.22 | 13-JUN-21:00 |
July | 907.20 | 01-JUL-00:10 | 337.37 | 03-JUL-19:10 | 4572.80 | 03-JUL-19:10 | 39726.58 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 135.03 | 24-JUL-15:00 | 159.85 | 03-JUL-21:00 |
August | 907.20 | 01-AUG-00:10 | 337.37 | 01-AUG-19:10 | 4572.80 | 01-AUG-19:10 | 39726.58 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 150.54 | 10-AUG-17:00 | 157.26 | 02-AUG-21:00 |
September | 907.20 | 01-SEP-00:10 | 337.37 | 01-SEP-19:10 | 4572.80 | 01-SEP-19:10 | 39726.58 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 57.60 | 14-SEP-17:00 | 212.32 | 27-SEP-21:00 |
October | 907.20 | 01-OCT-23:10 | 337.37 | 02-OCT-19:10 | 4572.80 | 02-OCT-19:10 | 39726.58 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 10.05 | 04-OCT-15:00 | 253.92 | 31-OCT-21:00 |
November | 907.20 | 01-NOV-00:10 | 337.37 | 01-NOV-19:10 | 4572.80 | 01-NOV-19:10 | 39726.58 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 1.41 | 04-NOV-15:00 | 340.51 | 11-NOV-21:00 |
December | 907.20 | 01-DEC-00:10 | 337.37 | 01-DEC-20:10 | 4572.80 | 01-DEC-20:10 | 39726.58 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 380.62 | 21-DEC-22:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 907.20 | 337.37 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 157.26 | ||||||
Maximum of Months | 907.20 | 337.37 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 150.54 | 422.22 |
Report: PeakSpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 15368.40 | 02-JAN-00:10 | 2177.23 | 02-JAN-20:10 | 965.27 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 714.77 | 15-JAN-08:00 |
February | 15368.40 | 01-FEB-00:10 | 2177.23 | 01-FEB-20:10 | 965.27 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 749.62 | 19-FEB-05:50 |
March | 15368.40 | 01-MAR-00:10 | 2177.23 | 01-MAR-20:10 | 965.27 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 608.98 | 01-MAR-07:00 |
April | 15368.40 | 01-APR-00:10 | 2177.23 | 03-APR-19:10 | 965.27 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 156.25 | 27-APR-16:00 | 539.52 | 19-APR-05:00 |
May | 15368.40 | 01-MAY-00:10 | 2177.23 | 01-MAY-19:10 | 965.27 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 101.80 | 05-MAY-16:00 | 455.91 | 11-MAY-03:30 |
June | 15368.40 | 01-JUN-00:10 | 2177.23 | 01-JUN-19:10 | 965.27 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 144.66 | 28-JUN-17:00 | 342.80 | 15-JUN-04:00 |
July | 15368.40 | 01-JUL-00:10 | 2177.23 | 03-JUL-19:10 | 965.27 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 239.62 | 24-JUL-15:00 | 266.41 | 07-JUL-05:00 |
August | 15368.40 | 01-AUG-00:10 | 2177.23 | 01-AUG-19:10 | 965.27 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 267.22 | 10-AUG-17:00 | 269.36 | 21-AUG-05:00 |
September | 15368.40 | 01-SEP-00:10 | 2177.23 | 01-SEP-19:10 | 965.27 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 101.97 | 14-SEP-17:00 | 375.67 | 27-SEP-05:00 |
October | 15368.40 | 01-OCT-23:10 | 2177.23 | 02-OCT-19:10 | 965.27 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 420.72 | 13-OCT-05:00 |
November | 15368.40 | 01-NOV-00:10 | 2177.23 | 01-NOV-19:10 | 965.27 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 585.89 | 11-NOV-07:30 |
December | 15368.40 | 01-DEC-00:10 | 2177.23 | 01-DEC-20:10 | 965.27 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 644.15 | 26-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 15368.40 | 2177.23 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 266.41 | |||||
Maximum of Months | 15368.40 | 2177.23 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 267.22 | 749.62 |
Report: PeakSpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 45622.98 | 02-JAN-00:10 | 11849.32 | 02-JAN-20:10 | 10029.21 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2041.99 | 15-JAN-08:00 |
February | 45622.98 | 01-FEB-00:10 | 11849.32 | 01-FEB-20:10 | 10029.21 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 2141.78 | 19-FEB-06:00 |
March | 45622.98 | 01-MAR-00:10 | 11849.32 | 01-MAR-20:10 | 10029.21 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 1739.99 | 01-MAR-07:00 |
April | 45622.98 | 01-APR-00:10 | 11849.32 | 03-APR-19:10 | 10029.21 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 446.86 | 27-APR-15:30 | 1540.74 | 19-APR-05:00 |
May | 45622.98 | 01-MAY-00:10 | 11849.32 | 01-MAY-19:10 | 10029.21 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 291.03 | 05-MAY-16:00 | 1302.34 | 11-MAY-03:30 |
June | 45622.98 | 01-JUN-00:10 | 11849.32 | 01-JUN-19:10 | 10029.21 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 413.30 | 28-JUN-17:00 | 979.23 | 15-JUN-04:00 |
July | 45622.98 | 01-JUL-00:10 | 11849.32 | 03-JUL-19:10 | 10029.21 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 684.85 | 24-JUL-15:00 | 773.52 | 07-JUL-05:00 |
August | 45622.98 | 01-AUG-00:10 | 11849.32 | 01-AUG-19:10 | 10029.21 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 763.58 | 10-AUG-17:00 | 770.25 | 21-AUG-05:00 |
September | 45622.98 | 01-SEP-00:10 | 11849.32 | 01-SEP-19:10 | 10029.21 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 291.79 | 14-SEP-17:00 | 1073.33 | 27-SEP-05:00 |
October | 45622.98 | 01-OCT-23:10 | 11849.32 | 02-OCT-19:10 | 10029.21 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 45.57 | 04-OCT-15:00 | 1201.54 | 13-OCT-05:00 |
November | 45622.98 | 01-NOV-00:10 | 11849.32 | 01-NOV-19:10 | 10029.21 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.19 | 04-NOV-15:00 | 1673.58 | 11-NOV-07:10 |
December | 45622.98 | 01-DEC-00:10 | 11849.32 | 01-DEC-20:10 | 10029.21 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 1839.96 | 26-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 45622.98 | 11849.32 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 770.25 | |||||
Maximum of Months | 45622.98 | 11849.32 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 763.58 | 2141.78 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 392.73 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 188.80 | 15-JAN-08:00 |
February | 180.00 | 01-FEB-00:10 | 392.73 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 197.91 | 19-FEB-06:00 |
March | 180.00 | 01-MAR-00:10 | 392.73 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 161.02 | 01-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 392.73 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.04 | 27-APR-15:10 | 142.69 | 19-APR-05:00 |
May | 180.00 | 01-MAY-00:10 | 392.73 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.73 | 05-MAY-16:00 | 120.76 | 11-MAY-04:00 |
June | 180.00 | 01-JUN-00:10 | 392.73 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.97 | 28-JUN-17:00 | 91.04 | 15-JUN-04:00 |
July | 180.00 | 01-JUL-00:10 | 392.73 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.14 | 24-JUL-15:10 | 71.02 | 07-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 392.73 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 69.16 | 10-AUG-17:00 | 76.69 | 01-AUG-08:00 |
September | 180.00 | 01-SEP-00:10 | 392.73 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.78 | 14-SEP-17:00 | 99.70 | 27-SEP-05:00 |
October | 180.00 | 01-OCT-00:10 | 392.73 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.98 | 04-OCT-15:10 | 111.52 | 13-OCT-05:00 |
November | 180.00 | 01-NOV-00:10 | 392.73 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 154.88 | 11-NOV-07:30 |
December | 180.00 | 01-DEC-00:10 | 392.73 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 170.21 | 26-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 392.73 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.02 | |||||
Maximum of Months | 180.00 | 392.73 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 69.16 | 197.91 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 392.68 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 188.79 | 15-JAN-08:00 |
February | 180.00 | 01-FEB-00:10 | 392.68 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 197.89 | 19-FEB-06:00 |
March | 180.00 | 01-MAR-00:10 | 392.68 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 161.01 | 01-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 392.68 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.04 | 27-APR-15:10 | 142.68 | 19-APR-05:00 |
May | 180.00 | 01-MAY-00:10 | 392.68 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.73 | 05-MAY-16:00 | 120.75 | 11-MAY-04:00 |
June | 180.00 | 01-JUN-00:10 | 392.68 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.97 | 28-JUN-17:00 | 91.03 | 15-JUN-04:00 |
July | 180.00 | 01-JUL-00:10 | 392.68 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.13 | 24-JUL-15:10 | 71.01 | 07-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 392.68 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 69.17 | 10-AUG-17:00 | 75.87 | 01-AUG-08:00 |
September | 180.00 | 01-SEP-00:10 | 392.68 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.78 | 14-SEP-17:00 | 99.69 | 27-SEP-05:00 |
October | 180.00 | 01-OCT-00:10 | 392.68 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.98 | 04-OCT-15:08 | 111.51 | 13-OCT-05:00 |
November | 180.00 | 01-NOV-00:10 | 392.68 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 154.87 | 11-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 392.68 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 170.19 | 26-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 392.68 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.01 | |||||
Maximum of Months | 180.00 | 392.68 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 69.17 | 197.89 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 01-JAN-00:10 | 246.81 | 01-JAN-19:10 | 232.19 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 48.01 | 15-JAN-08:00 |
February | 0.00 | 01-FEB-00:10 | 246.81 | 01-FEB-20:10 | 232.19 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 50.64 | 19-FEB-06:00 |
March | 0.00 | 01-MAR-00:10 | 246.81 | 01-MAR-20:10 | 232.19 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 45.39 | 01-MAR-07:00 |
April | 0.00 | 01-APR-00:10 | 246.81 | 01-APR-18:10 | 232.19 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.06 | 27-APR-15:05 | 39.43 | 19-APR-05:20 |
May | 0.00 | 01-MAY-00:10 | 246.81 | 01-MAY-19:10 | 232.19 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.03 | 05-MAY-16:00 | 35.44 | 11-MAY-03:00 |
June | 0.00 | 01-JUN-00:10 | 246.81 | 01-JUN-19:10 | 232.19 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.18 | 28-JUN-17:00 | 28.10 | 01-JUN-05:10 |
July | 0.00 | 01-JUL-00:10 | 246.81 | 01-JUL-18:10 | 232.19 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.21 | 24-JUL-15:00 | 23.83 | 19-JUL-05:00 |
August | 0.00 | 01-AUG-00:10 | 246.81 | 01-AUG-19:10 | 232.19 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.27 | 10-AUG-17:00 | 23.77 | 06-AUG-05:00 |
September | 0.00 | 01-SEP-00:10 | 246.81 | 01-SEP-19:10 | 232.19 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.03 | 14-SEP-17:00 | 29.49 | 27-SEP-04:00 |
October | 0.00 | 01-OCT-00:10 | 246.81 | 01-OCT-18:10 | 232.19 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 34.46 | 12-OCT-07:00 |
November | 0.00 | 01-NOV-00:10 | 246.81 | 01-NOV-19:10 | 232.19 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 44.22 | 11-NOV-23:00 |
December | 0.00 | 01-DEC-00:10 | 246.81 | 01-DEC-20:10 | 232.19 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 45.64 | 06-DEC-21:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 0.00 | 246.81 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.77 | |||||
Maximum of Months | 0.00 | 246.81 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 15.27 | 50.64 |
Report: PeakSpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 246.88 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 52.69 | 15-JAN-08:00 |
February | 180.00 | 01-FEB-00:10 | 246.88 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 55.23 | 19-FEB-06:00 |
March | 180.00 | 01-MAR-00:10 | 246.88 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 44.94 | 01-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 246.88 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.17 | 27-APR-15:08 | 39.82 | 19-APR-05:00 |
May | 180.00 | 01-MAY-00:10 | 246.88 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.18 | 05-MAY-16:00 | 33.70 | 11-MAY-04:00 |
June | 180.00 | 01-JUN-00:10 | 246.88 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.32 | 28-JUN-17:00 | 25.41 | 15-JUN-04:00 |
July | 180.00 | 01-JUL-00:10 | 246.88 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.78 | 24-JUL-15:10 | 19.87 | 04-JUL-07:20 |
August | 180.00 | 01-AUG-00:10 | 246.88 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.31 | 10-AUG-17:00 | 21.07 | 01-AUG-07:20 |
September | 180.00 | 01-SEP-00:10 | 246.88 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.20 | 14-SEP-17:00 | 27.83 | 27-SEP-05:00 |
October | 180.00 | 01-OCT-00:10 | 246.88 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 04-OCT-15:07 | 31.12 | 13-OCT-05:00 |
November | 180.00 | 01-NOV-00:10 | 246.88 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 43.22 | 11-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 246.88 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 47.50 | 26-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 246.88 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.87 | |||||
Maximum of Months | 180.00 | 246.88 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 19.31 | 55.23 |
Report: PeakSpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 392.73 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 188.80 | 15-JAN-08:00 |
February | 180.00 | 01-FEB-00:10 | 392.73 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 197.91 | 19-FEB-06:00 |
March | 180.00 | 01-MAR-00:10 | 392.73 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 161.02 | 01-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 392.73 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.04 | 27-APR-15:08 | 142.69 | 19-APR-05:00 |
May | 180.00 | 01-MAY-00:10 | 392.73 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.73 | 05-MAY-16:00 | 120.76 | 11-MAY-04:00 |
June | 180.00 | 01-JUN-00:10 | 392.73 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.97 | 28-JUN-17:00 | 91.04 | 15-JUN-04:00 |
July | 180.00 | 01-JUL-00:10 | 392.73 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.13 | 24-JUL-15:10 | 71.02 | 07-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 392.73 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 69.18 | 10-AUG-17:00 | 81.65 | 01-AUG-07:50 |
September | 180.00 | 01-SEP-00:10 | 392.73 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.78 | 14-SEP-17:00 | 99.70 | 27-SEP-05:00 |
October | 180.00 | 01-OCT-00:10 | 392.73 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.98 | 04-OCT-15:08 | 111.52 | 13-OCT-05:00 |
November | 180.00 | 01-NOV-00:10 | 392.73 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 154.88 | 11-NOV-07:20 |
December | 180.00 | 01-DEC-00:10 | 392.73 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 170.21 | 26-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 392.73 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.02 | |||||
Maximum of Months | 180.00 | 392.73 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 69.18 | 197.91 |
Report: PeakSpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 392.68 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 188.79 | 15-JAN-08:00 |
February | 180.00 | 01-FEB-00:10 | 392.68 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 197.89 | 19-FEB-06:00 |
March | 180.00 | 01-MAR-00:10 | 392.68 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 161.01 | 01-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 392.68 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.04 | 27-APR-15:10 | 142.68 | 19-APR-05:00 |
May | 180.00 | 01-MAY-00:10 | 392.68 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.73 | 05-MAY-16:00 | 120.75 | 11-MAY-04:00 |
June | 180.00 | 01-JUN-00:10 | 392.68 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.97 | 28-JUN-17:00 | 91.03 | 15-JUN-04:00 |
July | 180.00 | 01-JUL-00:10 | 392.68 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.13 | 24-JUL-15:08 | 71.01 | 07-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 392.68 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 69.17 | 10-AUG-17:00 | 81.15 | 01-AUG-08:00 |
September | 180.00 | 01-SEP-00:10 | 392.68 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.78 | 14-SEP-17:00 | 99.69 | 27-SEP-05:00 |
October | 180.00 | 01-OCT-00:10 | 392.68 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.98 | 04-OCT-15:08 | 111.51 | 13-OCT-05:00 |
November | 180.00 | 01-NOV-00:10 | 392.68 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 154.87 | 11-NOV-07:40 |
December | 180.00 | 01-DEC-00:10 | 392.68 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 170.19 | 26-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 392.68 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.01 | |||||
Maximum of Months | 180.00 | 392.68 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 69.17 | 197.89 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2263.36 | 02-JAN-00:10 | 1282.60 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 227.32 | 15-JAN-08:00 |
February | 2263.36 | 01-FEB-00:10 | 1282.60 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 238.34 | 19-FEB-06:00 |
March | 2263.36 | 01-MAR-00:10 | 1282.60 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 193.73 | 01-MAR-07:00 |
April | 2263.36 | 01-APR-00:10 | 1282.60 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.02 | 01-APR-16:00 | 171.57 | 19-APR-05:00 |
May | 2263.36 | 01-MAY-00:10 | 1282.60 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.97 | 05-MAY-16:00 | 145.08 | 11-MAY-03:30 |
June | 2263.36 | 01-JUN-00:10 | 1282.60 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.38 | 28-JUN-17:00 | 109.15 | 15-JUN-03:00 |
July | 2263.36 | 01-JUL-00:10 | 1282.60 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.53 | 24-JUL-15:00 | 85.02 | 07-JUL-05:00 |
August | 2263.36 | 01-AUG-00:10 | 1282.60 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.44 | 10-AUG-17:00 | 85.84 | 21-AUG-05:00 |
September | 2263.36 | 01-SEP-00:10 | 1282.60 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.05 | 22-SEP-16:00 | 119.61 | 27-SEP-05:00 |
October | 2263.36 | 01-OCT-23:10 | 1282.60 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.76 | 04-OCT-15:00 | 133.90 | 13-OCT-05:00 |
November | 2263.36 | 01-NOV-00:10 | 1282.60 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 186.33 | 11-NOV-07:20 |
December | 2263.36 | 01-DEC-00:10 | 1282.60 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 204.83 | 26-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 2263.36 | 1282.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.02 | ||||
Maximum of Months | 2263.36 | 1282.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.44 | 238.34 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 392.73 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 189.29 | 15-JAN-08:00 |
February | 180.00 | 01-FEB-00:10 | 392.73 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 198.38 | 19-FEB-06:00 |
March | 180.00 | 01-MAR-00:10 | 392.73 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 161.50 | 01-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 392.73 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.66 | 27-APR-16:00 | 143.16 | 19-APR-05:00 |
May | 180.00 | 01-MAY-00:10 | 392.73 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.34 | 05-MAY-16:00 | 121.22 | 11-MAY-04:00 |
June | 180.00 | 01-JUN-00:10 | 392.73 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.59 | 28-JUN-17:00 | 91.48 | 15-JUN-04:00 |
July | 180.00 | 01-JUL-00:10 | 392.73 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 59.75 | 24-JUL-15:10 | 71.45 | 07-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 392.73 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 68.80 | 10-AUG-17:00 | 76.76 | 01-AUG-08:00 |
September | 180.00 | 01-SEP-00:10 | 392.73 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.39 | 14-SEP-17:00 | 100.15 | 27-SEP-05:00 |
October | 180.00 | 01-OCT-00:10 | 392.73 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.58 | 04-OCT-15:10 | 111.97 | 13-OCT-05:00 |
November | 180.00 | 01-NOV-00:10 | 392.73 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 155.35 | 11-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 392.73 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 170.68 | 26-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 392.73 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.45 | |||||
Maximum of Months | 180.00 | 392.73 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 68.80 | 198.38 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 392.68 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 189.28 | 15-JAN-08:00 |
February | 180.00 | 01-FEB-00:10 | 392.68 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 198.38 | 19-FEB-06:00 |
March | 180.00 | 01-MAR-00:10 | 392.68 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 161.48 | 01-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 392.68 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.65 | 27-APR-15:10 | 143.15 | 19-APR-05:00 |
May | 180.00 | 01-MAY-00:10 | 392.68 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.34 | 05-MAY-16:00 | 121.21 | 11-MAY-04:00 |
June | 180.00 | 01-JUN-00:10 | 392.68 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.56 | 28-JUN-17:00 | 91.47 | 15-JUN-04:00 |
July | 180.00 | 01-JUL-00:10 | 392.68 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 59.75 | 24-JUL-15:10 | 71.45 | 07-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 392.68 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 68.80 | 10-AUG-17:00 | 75.97 | 01-AUG-08:00 |
September | 180.00 | 01-SEP-00:10 | 392.68 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.38 | 14-SEP-17:00 | 100.14 | 27-SEP-05:00 |
October | 180.00 | 01-OCT-00:10 | 392.68 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.58 | 04-OCT-15:10 | 111.96 | 13-OCT-05:00 |
November | 180.00 | 01-NOV-00:10 | 392.68 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 155.34 | 11-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 392.68 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 170.67 | 26-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 392.68 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.45 | |||||
Maximum of Months | 180.00 | 392.68 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 68.80 | 198.38 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 246.88 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 96.85 | 15-JAN-08:00 |
February | 180.00 | 01-FEB-00:10 | 246.88 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 101.50 | 19-FEB-06:00 |
March | 180.00 | 01-MAR-00:10 | 246.88 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 82.63 | 01-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 246.88 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.29 | 27-APR-15:30 | 73.24 | 19-APR-05:00 |
May | 180.00 | 01-MAY-00:10 | 246.88 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.97 | 05-MAY-16:00 | 62.02 | 11-MAY-04:00 |
June | 180.00 | 01-JUN-00:10 | 246.88 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.72 | 28-JUN-17:00 | 46.80 | 15-JUN-04:00 |
July | 180.00 | 01-JUL-00:10 | 246.88 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.57 | 24-JUL-15:10 | 36.56 | 07-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 246.88 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.20 | 10-AUG-17:00 | 39.22 | 01-AUG-08:00 |
September | 180.00 | 01-SEP-00:10 | 246.88 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.99 | 14-SEP-17:00 | 51.24 | 27-SEP-05:00 |
October | 180.00 | 01-OCT-00:10 | 246.88 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.32 | 04-OCT-15:10 | 57.29 | 13-OCT-05:00 |
November | 180.00 | 01-NOV-00:10 | 246.88 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 79.48 | 11-NOV-08:00 |
December | 180.00 | 01-DEC-00:10 | 246.88 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 87.33 | 26-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 246.88 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.56 | |||||
Maximum of Months | 180.00 | 246.88 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 35.20 | 101.50 |
Report: PeakSpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 3823.39 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 466.65 | 15-JAN-08:00 |
February | 26988.77 | 01-FEB-00:10 | 3823.39 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 482.51 | 19-FEB-06:00 |
March | 26988.77 | 01-MAR-00:10 | 3823.39 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 403.36 | 01-MAR-07:00 |
April | 26988.77 | 01-APR-00:10 | 3823.39 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 98.42 | 01-APR-16:00 | 360.97 | 19-APR-05:00 |
May | 26988.77 | 01-MAY-00:10 | 3823.39 | 01-MAY-19:10 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 55.32 | 05-MAY-16:00 | 310.05 | 11-MAY-03:00 |
June | 26988.77 | 01-JUN-00:10 | 3823.39 | 01-JUN-19:10 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 83.78 | 28-JUN-17:00 | 239.17 | 15-JUN-03:00 |
July | 26988.77 | 01-JUL-00:10 | 3823.39 | 03-JUL-19:10 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 144.99 | 24-JUL-15:00 | 194.65 | 07-JUL-05:00 |
August | 26988.77 | 01-AUG-00:10 | 3823.39 | 01-AUG-19:10 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 161.81 | 10-AUG-17:00 | 193.25 | 21-AUG-05:00 |
September | 26988.77 | 01-SEP-00:10 | 3823.39 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 59.12 | 14-SEP-17:00 | 258.59 | 27-SEP-05:00 |
October | 26988.77 | 01-OCT-23:10 | 3823.39 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.13 | 04-OCT-15:00 | 286.65 | 13-OCT-05:00 |
November | 26988.77 | 01-NOV-00:10 | 3823.39 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 387.94 | 11-NOV-08:00 |
December | 26988.77 | 01-DEC-00:10 | 3823.39 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 420.74 | 26-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26988.77 | 3823.39 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 193.25 | |||||
Maximum of Months | 26988.77 | 3823.39 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 161.81 | 482.51 |
Report: PeakSpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 3823.39 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 467.90 | 15-JAN-08:00 |
February | 26988.77 | 01-FEB-00:10 | 3823.39 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 482.61 | 19-FEB-06:00 |
March | 26988.77 | 01-MAR-00:10 | 3823.39 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 404.55 | 01-MAR-07:00 |
April | 26988.77 | 01-APR-00:10 | 3823.39 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 98.49 | 01-APR-16:00 | 361.70 | 19-APR-05:00 |
May | 26988.77 | 01-MAY-00:10 | 3823.39 | 01-MAY-19:10 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 53.21 | 05-MAY-16:00 | 310.93 | 11-MAY-03:00 |
June | 26988.77 | 01-JUN-00:10 | 3823.39 | 01-JUN-19:10 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 81.71 | 28-JUN-17:00 | 240.07 | 15-JUN-03:00 |
July | 26988.77 | 01-JUL-00:10 | 3823.39 | 03-JUL-19:10 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 143.21 | 24-JUL-15:00 | 195.55 | 07-JUL-05:00 |
August | 26988.77 | 01-AUG-00:10 | 3823.39 | 01-AUG-19:10 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 160.22 | 10-AUG-17:00 | 194.06 | 21-AUG-05:00 |
September | 26988.77 | 01-SEP-00:10 | 3823.39 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 57.38 | 14-SEP-17:00 | 259.35 | 27-SEP-05:00 |
October | 26988.77 | 01-OCT-23:10 | 3823.39 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.62 | 04-OCT-15:00 | 287.30 | 13-OCT-05:00 |
November | 26988.77 | 01-NOV-00:10 | 3823.39 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 389.30 | 11-NOV-08:00 |
December | 26988.77 | 01-DEC-00:10 | 3823.39 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 421.93 | 26-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26988.77 | 3823.39 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 194.06 | |||||
Maximum of Months | 26988.77 | 3823.39 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 160.22 | 482.61 |
Report: PeakSpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2401.70 | 02-JAN-00:10 | 1020.78 | 02-JAN-20:10 | 15112.11 | 01-JAN-07:10 | 22492.83 | 01-JAN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 429.24 | 15-JAN-08:00 |
February | 2401.70 | 01-FEB-00:10 | 1020.78 | 01-FEB-20:10 | 15112.11 | 01-FEB-07:10 | 22492.83 | 01-FEB-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 442.35 | 19-FEB-08:00 |
March | 2401.70 | 01-MAR-00:10 | 1020.78 | 01-MAR-20:10 | 15112.11 | 01-MAR-07:10 | 22492.83 | 01-MAR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 364.12 | 01-MAR-07:00 |
April | 2401.70 | 01-APR-00:10 | 1020.78 | 03-APR-19:10 | 15112.11 | 01-APR-06:10 | 22492.83 | 01-APR-15:09 | 0.00 | 0.00 | 0.00 | 45.02 | 27-APR-15:40 | 319.64 | 19-APR-06:00 |
May | 2401.70 | 01-MAY-00:10 | 1020.78 | 01-MAY-19:10 | 15112.11 | 01-MAY-06:10 | 22492.83 | 01-MAY-15:09 | 0.00 | 0.00 | 0.00 | 13.27 | 05-MAY-16:00 | 265.58 | 18-MAY-08:00 |
June | 2401.70 | 01-JUN-00:10 | 1020.78 | 01-JUN-19:10 | 15112.11 | 01-JUN-06:10 | 22492.83 | 01-JUN-15:09 | 0.00 | 0.00 | 0.00 | 38.00 | 28-JUN-17:00 | 209.62 | 13-JUN-10:00 |
July | 2401.70 | 01-JUL-00:10 | 1020.78 | 03-JUL-19:10 | 15112.11 | 01-JUL-06:10 | 22492.83 | 01-JUL-15:09 | 0.00 | 0.00 | 0.00 | 93.23 | 24-JUL-15:00 | 182.46 | 04-JUL-21:00 |
August | 2401.70 | 01-AUG-00:10 | 1020.78 | 01-AUG-19:10 | 15112.11 | 01-AUG-06:10 | 22492.83 | 01-AUG-15:09 | 0.00 | 0.00 | 0.00 | 109.52 | 10-AUG-17:00 | 194.78 | 01-AUG-06:50 |
September | 2401.70 | 01-SEP-00:10 | 1020.78 | 01-SEP-19:10 | 15112.11 | 01-SEP-06:10 | 22492.83 | 01-SEP-15:09 | 0.00 | 0.00 | 0.00 | 13.30 | 14-SEP-17:00 | 224.33 | 27-SEP-08:00 |
October | 2401.70 | 01-OCT-23:10 | 1020.78 | 02-OCT-19:10 | 15112.11 | 01-OCT-06:10 | 22492.83 | 01-OCT-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 273.88 | 13-OCT-07:10 |
November | 2401.70 | 01-NOV-00:10 | 1020.78 | 01-NOV-19:10 | 15112.11 | 01-NOV-06:10 | 22492.83 | 01-NOV-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 359.92 | 11-NOV-08:07 |
December | 2401.70 | 01-DEC-00:10 | 1020.78 | 01-DEC-20:10 | 15112.11 | 01-DEC-07:10 | 22492.83 | 01-DEC-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 408.17 | 25-DEC-19:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 2401.70 | 1020.78 | 15112.11 | 22492.83 | 0.00 | 0.00 | 0.00 | 0.00 | 182.46 | ||||||
Maximum of Months | 2401.70 | 1020.78 | 15112.11 | 22492.83 | 0.00 | 0.00 | 0.00 | 109.52 | 442.35 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2395.44 | 02-JAN-00:10 | 1357.44 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 402.55 | 15-JAN-08:00 |
February | 2395.44 | 01-FEB-00:10 | 1357.44 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 419.35 | 19-FEB-05:00 |
March | 2395.44 | 01-MAR-00:10 | 1357.44 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 343.78 | 01-MAR-07:00 |
April | 2395.44 | 01-APR-00:10 | 1357.44 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.27 | 01-APR-16:00 | 304.56 | 19-APR-05:00 |
May | 2395.44 | 01-MAY-00:10 | 1357.44 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.80 | 05-MAY-16:00 | 257.67 | 11-MAY-03:10 |
June | 2395.44 | 01-JUN-00:10 | 1357.44 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.90 | 28-JUN-17:00 | 194.07 | 15-JUN-03:50 |
July | 2395.44 | 01-JUL-00:10 | 1357.44 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 123.07 | 24-JUL-15:00 | 151.19 | 07-JUL-05:00 |
August | 2395.44 | 01-AUG-00:10 | 1357.44 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 140.43 | 10-AUG-17:00 | 152.82 | 21-AUG-05:00 |
September | 2395.44 | 01-SEP-00:10 | 1357.44 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.78 | 14-SEP-17:00 | 212.63 | 27-SEP-05:00 |
October | 2395.44 | 01-OCT-23:10 | 1357.44 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.86 | 04-OCT-15:00 | 237.85 | 13-OCT-05:00 |
November | 2395.44 | 01-NOV-00:10 | 1357.44 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 330.69 | 11-NOV-07:50 |
December | 2395.44 | 01-DEC-00:10 | 1357.44 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 363.44 | 26-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 2395.44 | 1357.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 151.19 | ||||
Maximum of Months | 2395.44 | 1357.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 140.43 | 419.35 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 19865.15 | 11-JAN-19:08 | 35783.66 | 48060.13 | 38325.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 20053.75 | 23-FEB-19:10 | 44729.58 | 60075.16 | 47907.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 19393.65 | 02-MAR-19:03 | 62621.41 | 84105.23 | 67070.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 20382.18 | 27-APR-19:05 | 17891.83 | 27034.00 | 20227.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 20526.96 | 04-MAY-19:10 | 17891.83 | 27034.00 | 20227.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 21304.61 | 28-JUN-19:10 | 17891.83 | 27034.00 | 20227.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 21596.02 | 24-JUL-19:05 | 17891.83 | 27034.00 | 20227.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 21942.15 | 10-AUG-19:10 | 17891.83 | 27034.00 | 20227.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 21663.49 | 13-SEP-18:07 | 53675.50 | 72090.20 | 57488.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 21085.86 | 12-OCT-18:06 | 62621.41 | 84105.23 | 67070.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 20147.70 | 02-NOV-18:45 | 17891.83 | 24030.07 | 19162.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 19548.73 | 05-DEC-21:00 | 8945.92 | 13517.00 | 10113.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 19393.65 | 8945.92 | 13517.00 | 10113.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21942.15 | 62621.41 | 84105.23 | 67070.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3534.52 | 20-JAN-13:10 | 259.90 | 190.92 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 186.62 |
February | 3925.97 | 12-FEB-11:35 | 779.69 | 458.20 | 577.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 191.74 |
March | 4413.00 | 02-MAR-11:35 | 519.79 | 381.83 | 505.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 148.95 |
April | 4086.61 | 27-APR-12:00 | 259.90 | 190.92 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 38.44 | 0.00 |
May | 4006.43 | 04-MAY-13:00 | 259.90 | 190.92 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 2.42 | 0.00 |
June | 3617.86 | 28-JUN-12:10 | 259.90 | 190.92 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 23.76 | 0.00 |
July | 3990.35 | 31-JUL-15:13 | 1949.22 | 572.75 | 757.77 | 0.00 | 0.00 | 0.00 | 0.00 | 82.65 | 0.00 |
August | 4555.60 | 24-AUG-10:35 | 519.79 | 381.83 | 505.18 | 0.00 | 0.00 | 0.00 | 0.00 | 44.93 | 0.00 |
September | 4558.22 | 10-SEP-10:40 | 389.84 | 229.10 | 288.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.72 |
October | 4633.44 | 04-OCT-10:35 | 519.79 | 381.83 | 505.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.30 |
November | 4129.57 | 04-NOV-10:35 | 779.69 | 381.83 | 505.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.79 |
December | 4003.28 | 05-DEC-11:40 | 259.90 | 190.92 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 145.01 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3534.52 | 259.90 | 190.92 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4633.44 | 1949.22 | 572.75 | 757.77 | 0.00 | 0.00 | 0.00 | 0.00 | 82.65 | 191.74 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1732.88 | 11-JAN-21:00 | 1053.36 | 795.89 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.22 |
February | 1824.90 | 27-FEB-20:10 | 1053.36 | 795.89 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.69 |
March | 1865.66 | 14-MAR-20:00 | 1053.36 | 795.89 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.01 |
April | 2138.50 | 27-APR-18:10 | 6320.16 | 4244.75 | 4512.87 | 0.00 | 0.00 | 0.00 | 0.00 | 19.99 | 0.00 |
May | 2109.04 | 04-MAY-18:10 | 6320.16 | 4244.75 | 4512.87 | 0.00 | 0.00 | 0.00 | 0.00 | 7.55 | 0.00 |
June | 2179.71 | 28-JUN-18:03 | 6320.16 | 4244.75 | 4512.87 | 0.00 | 0.00 | 0.00 | 0.00 | 19.56 | 0.00 |
July | 2242.32 | 24-JUL-18:10 | 6320.16 | 4244.75 | 4512.87 | 0.00 | 0.00 | 0.00 | 0.00 | 33.75 | 0.00 |
August | 2255.18 | 10-AUG-18:10 | 6320.16 | 4244.75 | 4512.87 | 0.00 | 0.00 | 0.00 | 0.00 | 41.06 | 0.00 |
September | 2107.67 | 13-SEP-18:10 | 6320.16 | 4244.75 | 4512.87 | 0.00 | 0.00 | 0.00 | 0.00 | 6.19 | 0.00 |
October | 1983.61 | 04-OCT-18:10 | 7373.52 | 4952.21 | 5265.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.96 |
November | 1797.73 | 02-NOV-18:45 | 2106.72 | 1414.92 | 1504.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.18 |
December | 1734.17 | 05-DEC-21:00 | 1053.36 | 795.89 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.77 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1732.88 | 1053.36 | 795.89 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2255.18 | 7373.52 | 4952.21 | 5265.02 | 0.00 | 0.00 | 0.00 | 0.00 | 41.06 | 72.77 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1460.09 | 11-JAN-21:00 | 222.77 | 1487.69 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.05 |
February | 1648.40 | 27-FEB-21:00 | 222.77 | 1487.69 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.39 |
March | 1671.62 | 10-MAR-21:00 | 222.77 | 1487.69 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.36 |
April | 1905.38 | 27-APR-19:00 | 222.77 | 1322.39 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 18.89 | 0.00 |
May | 1900.34 | 15-MAY-18:50 | 222.77 | 1322.39 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.75 |
June | 2009.98 | 28-JUN-18:30 | 222.77 | 1322.39 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 42.07 | 0.00 |
July | 2107.40 | 24-JUL-18:10 | 1336.61 | 7934.32 | 4771.59 | 0.00 | 0.00 | 0.00 | 0.00 | 80.01 | 0.00 |
August | 2130.82 | 10-AUG-18:10 | 1336.61 | 7934.32 | 4771.59 | 0.00 | 0.00 | 0.00 | 0.00 | 98.06 | 0.00 |
September | 1913.56 | 14-SEP-18:30 | 222.77 | 1322.39 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 1.57 | 0.00 |
October | 1769.03 | 04-OCT-19:10 | 222.77 | 1487.69 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.84 |
November | 1619.69 | 03-NOV-20:00 | 222.77 | 1487.69 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.78 |
December | 1412.63 | 29-DEC-21:00 | 222.77 | 1487.69 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 129.92 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1412.63 | 222.77 | 1322.39 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2130.82 | 1336.61 | 7934.32 | 4771.59 | 0.00 | 0.00 | 0.00 | 0.00 | 98.06 | 129.92 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 419.69 | 11-JAN-22:00 | 195.84 | 242.76 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.80 |
February | 540.80 | 27-FEB-21:50 | 195.84 | 242.76 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.03 |
March | 531.04 | 10-MAR-22:00 | 195.84 | 242.76 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.06 |
April | 763.65 | 27-APR-21:00 | 195.84 | 242.76 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.58 |
May | 804.08 | 05-MAY-21:00 | 195.84 | 242.76 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.05 |
June | 870.08 | 28-JUN-19:50 | 171.36 | 273.10 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 7.05 | 0.00 |
July | 961.71 | 24-JUL-19:05 | 342.72 | 546.20 | 484.31 | 0.00 | 0.00 | 0.00 | 0.00 | 36.98 | 0.00 |
August | 984.97 | 10-AUG-19:10 | 342.72 | 546.20 | 484.31 | 0.00 | 0.00 | 0.00 | 0.00 | 48.63 | 0.00 |
September | 807.78 | 12-SEP-21:00 | 195.84 | 242.76 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.91 |
October | 660.72 | 04-OCT-20:10 | 195.84 | 242.76 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.98 |
November | 527.63 | 04-NOV-20:40 | 171.36 | 212.41 | 203.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.12 |
December | 374.77 | 29-DEC-22:00 | 195.84 | 242.76 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.32 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 374.77 | 171.36 | 212.41 | 203.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 984.97 | 342.72 | 546.20 | 484.31 | 0.00 | 0.00 | 0.00 | 0.00 | 48.63 | 78.32 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 35831.19 | 11-JAN-21:00 | 705.60 | 337.37 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 194.48 |
February | 36089.18 | 27-FEB-21:00 | 705.60 | 337.37 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 179.92 |
March | 36251.33 | 14-MAR-20:00 | 705.60 | 337.37 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 143.18 |
April | 36902.23 | 27-APR-20:00 | 705.60 | 337.37 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 64.08 |
May | 36839.49 | 04-MAY-20:00 | 705.60 | 337.37 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 64.87 |
June | 37137.76 | 28-JUN-20:00 | 705.60 | 337.37 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 28.74 |
July | 37381.42 | 24-JUL-20:00 | 705.60 | 337.37 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 4.25 | 0.00 |
August | 37462.14 | 10-AUG-20:00 | 705.60 | 337.37 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 28.40 | 0.00 |
September | 36913.51 | 14-SEP-20:00 | 705.60 | 337.37 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 72.32 |
October | 36480.76 | 04-OCT-20:00 | 705.60 | 337.37 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 99.20 |
November | 36020.83 | 03-NOV-20:00 | 705.60 | 337.37 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 134.68 |
December | 35737.46 | 29-DEC-21:00 | 705.60 | 337.37 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 223.32 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 35737.46 | 705.60 | 337.37 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 37462.14 | 705.60 | 337.37 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 28.40 | 223.32 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 13458.14 | 20-JAN-13:10 | 3415.20 | 604.78 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 407.71 |
February | 15427.71 | 12-FEB-11:35 | 10245.60 | 1451.48 | 812.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 424.29 |
March | 16417.70 | 02-MAR-11:35 | 6830.40 | 1209.57 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 318.75 |
April | 15398.11 | 27-APR-15:13 | 25614.00 | 1814.35 | 1066.88 | 0.00 | 0.00 | 0.00 | 0.00 | 150.03 | 0.00 |
May | 15243.44 | 04-MAY-15:13 | 25614.00 | 1814.35 | 1066.88 | 0.00 | 0.00 | 0.00 | 0.00 | 76.55 | 0.00 |
June | 13592.57 | 28-JUN-15:02 | 51228.00 | 3628.71 | 2133.76 | 0.00 | 0.00 | 0.00 | 0.00 | 129.68 | 0.00 |
July | 15184.06 | 31-JUL-15:13 | 25614.00 | 1814.35 | 1066.88 | 0.00 | 0.00 | 0.00 | 0.00 | 187.82 | 0.00 |
August | 16461.66 | 24-AUG-15:13 | 25614.00 | 1814.35 | 1066.88 | 0.00 | 0.00 | 0.00 | 0.00 | 202.28 | 0.00 |
September | 16489.41 | 14-SEP-15:13 | 25614.00 | 1814.35 | 1066.88 | 0.00 | 0.00 | 0.00 | 0.00 | 59.35 | 0.00 |
October | 17036.87 | 04-OCT-10:35 | 6830.40 | 1209.57 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.94 |
November | 15252.41 | 04-NOV-13:00 | 5122.80 | 604.78 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.88 |
December | 15059.38 | 02-DEC-11:35 | 10245.60 | 1209.57 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 250.89 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 13458.14 | 3415.20 | 604.78 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17036.87 | 51228.00 | 3628.71 | 2133.76 | 0.00 | 0.00 | 0.00 | 0.00 | 202.28 | 424.29 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 37335.70 | 11-JAN-22:00 | 40553.76 | 10532.73 | 9501.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 772.45 |
February | 39325.84 | 27-FEB-20:10 | 35484.54 | 11849.32 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 564.36 |
March | 40053.88 | 14-MAR-20:00 | 35484.54 | 11849.32 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 518.69 |
April | 44524.89 | 27-APR-18:30 | 35484.54 | 10532.73 | 9501.36 | 0.00 | 0.00 | 0.00 | 0.00 | 249.99 | 0.00 |
May | 43757.09 | 04-MAY-18:15 | 70969.08 | 21065.45 | 19002.71 | 0.00 | 0.00 | 0.00 | 0.00 | 117.47 | 0.00 |
June | 45179.54 | 28-JUN-18:30 | 35484.54 | 10532.73 | 9501.36 | 0.00 | 0.00 | 0.00 | 0.00 | 291.47 | 0.00 |
July | 46918.52 | 24-JUL-18:17 | 106453.62 | 31598.18 | 28504.07 | 0.00 | 0.00 | 0.00 | 0.00 | 541.05 | 0.00 |
August | 47357.85 | 10-AUG-18:20 | 106453.62 | 31598.18 | 28504.07 | 0.00 | 0.00 | 0.00 | 0.00 | 668.65 | 0.00 |
September | 44653.54 | 14-SEP-18:02 | 212907.24 | 63196.36 | 57008.13 | 0.00 | 0.00 | 0.00 | 0.00 | 37.87 | 0.00 |
October | 42335.38 | 04-OCT-18:03 | 248391.78 | 73729.08 | 66509.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 258.48 |
November | 39409.81 | 02-NOV-18:45 | 70969.08 | 21065.45 | 19002.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 641.14 |
December | 37297.97 | 05-DEC-20:50 | 35484.54 | 11849.32 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1167.39 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 37297.97 | 35484.54 | 10532.73 | 9501.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 47357.85 | 248391.78 | 73729.08 | 66509.49 | 0.00 | 0.00 | 0.00 | 0.00 | 668.65 | 1167.39 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2328.35 | 20-JAN-16:02 | 583.20 | 659.78 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 114.48 |
February | 3722.87 | 12-FEB-16:01 | 378.00 | 907.20 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.56 |
March | 3756.82 | 18-MAR-15:02 | 324.00 | 777.60 | 458.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.61 |
April | 3784.18 | 01-APR-18:01 | 819.00 | 2749.09 | 903.46 | 0.00 | 0.00 | 0.00 | 0.00 | 17.94 | 0.00 |
May | 3859.50 | 14-MAY-15:02 | 324.00 | 777.60 | 458.31 | 0.00 | 0.00 | 0.00 | 0.00 | 4.54 | 0.00 |
June | 3739.09 | 01-JUN-18:02 | 831.60 | 2097.16 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.50 |
July | 3683.29 | 28-JUL-15:02 | 583.20 | 659.78 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.91 |
August | 3655.09 | 29-AUG-18:02 | 831.60 | 2097.16 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 50.52 | 0.00 |
September | 3632.42 | 13-SEP-18:02 | 831.60 | 2097.16 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.16 | 0.00 |
October | 3850.67 | 04-OCT-15:02 | 583.20 | 659.78 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.76 |
November | 3659.13 | 11-NOV-16:01 | 378.00 | 907.20 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.25 |
December | 3528.21 | 05-DEC-16:02 | 583.20 | 659.78 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 110.44 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2328.35 | 324.00 | 659.78 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3859.50 | 831.60 | 2749.09 | 903.46 | 0.00 | 0.00 | 0.00 | 0.00 | 50.52 | 114.48 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 520.39 | 11-JAN-19:05 | 554.40 | 1397.95 | 516.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.74 |
February | 2769.52 | 06-FEB-16:01 | 680.40 | 769.66 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.18 |
March | 3388.09 | 01-MAR-16:01 | 680.40 | 769.66 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.16 |
April | 3482.76 | 02-APR-15:01 | 378.00 | 907.09 | 534.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.16 |
May | 3513.70 | 14-MAY-15:02 | 324.00 | 777.51 | 458.26 | 0.00 | 0.00 | 0.00 | 0.00 | 4.54 | 0.00 |
June | 3433.72 | 01-JUN-18:02 | 831.60 | 2096.92 | 774.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.10 |
July | 3402.32 | 26-JUL-15:02 | 583.20 | 659.70 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.91 |
August | 3372.65 | 10-AUG-18:02 | 831.60 | 2096.92 | 774.30 | 0.00 | 0.00 | 0.00 | 0.00 | 50.33 | 0.00 |
September | 3321.89 | 23-SEP-15:02 | 324.00 | 777.51 | 458.26 | 0.00 | 0.00 | 0.00 | 0.00 | 4.89 | 0.00 |
October | 3461.01 | 04-OCT-15:02 | 583.20 | 659.70 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.95 |
November | 3154.07 | 04-NOV-15:02 | 324.00 | 777.51 | 458.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.18 |
December | 595.34 | 28-DEC-19:05 | 831.60 | 2096.92 | 774.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.18 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 520.39 | 324.00 | 659.70 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3513.70 | 831.60 | 2096.92 | 774.30 | 0.00 | 0.00 | 0.00 | 0.00 | 50.33 | 97.18 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 190.99 | 07-JAN-08:50 | 0.00 | 138.22 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.56 |
February | 620.12 | 08-FEB-13:50 | 0.00 | 69.11 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.54 |
March | 766.14 | 02-MAR-13:00 | 0.00 | 69.11 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.86 |
April | 734.75 | 27-APR-13:00 | 0.00 | 69.11 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 5.05 | 0.00 |
May | 713.57 | 04-MAY-13:20 | 0.00 | 69.11 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.16 |
June | 567.52 | 28-JUN-13:10 | 0.00 | 69.11 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 2.10 | 0.00 |
July | 679.24 | 31-JUL-13:20 | 0.00 | 69.11 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 7.79 | 0.00 |
August | 820.42 | 24-AUG-13:00 | 0.00 | 69.11 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 10.17 | 0.00 |
September | 866.44 | 23-SEP-13:30 | 0.00 | 81.45 | 74.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.18 |
October | 904.19 | 04-OCT-12:30 | 0.00 | 69.11 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.25 |
November | 760.92 | 04-NOV-13:30 | 0.00 | 81.45 | 74.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.81 |
December | 604.17 | 05-DEC-12:30 | 0.00 | 69.11 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 190.99 | 0.00 | 69.11 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 904.19 | 0.00 | 138.22 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 10.17 | 46.56 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 871.20 | 28-JAN-09:02 | 324.00 | 829.52 | 959.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.27 |
February | 915.85 | 25-FEB-09:02 | 216.00 | 553.01 | 639.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.49 |
March | 967.32 | 18-MAR-15:02 | 324.00 | 488.83 | 449.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.47 |
April | 1047.92 | 01-APR-18:01 | 819.00 | 1728.17 | 885.15 | 0.00 | 0.00 | 0.00 | 0.00 | 5.19 | 0.00 |
May | 1067.26 | 14-MAY-18:02 | 702.00 | 1481.29 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.48 |
June | 1075.92 | 09-JUN-18:02 | 831.60 | 1318.35 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
July | 1057.22 | 30-JUL-18:02 | 702.00 | 1481.29 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 6.48 | 0.00 |
August | 1045.16 | 08-AUG-15:02 | 583.20 | 414.76 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 13.69 | 0.00 |
September | 1024.32 | 14-SEP-18:02 | 831.60 | 1318.35 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.75 |
October | 989.52 | 02-OCT-18:01 | 970.20 | 1538.07 | 885.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.01 |
November | 912.26 | 05-NOV-08:62 | 270.00 | 691.27 | 799.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.78 |
December | 932.08 | 03-DEC-09:02 | 270.00 | 691.27 | 799.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.20 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 871.20 | 216.00 | 414.76 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1075.92 | 970.20 | 1728.17 | 959.99 | 0.00 | 0.00 | 0.00 | 0.00 | 13.69 | 28.27 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 676.41 | 10-JAN-09:03 | 216.00 | 1036.80 | 679.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 110.85 |
February | 3120.73 | 08-FEB-16:02 | 583.20 | 659.78 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.78 |
March | 3427.26 | 02-MAR-09:02 | 216.00 | 1036.80 | 679.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.98 |
April | 3414.16 | 01-APR-18:01 | 819.00 | 2749.09 | 903.46 | 0.00 | 0.00 | 0.00 | 0.00 | 18.15 | 0.00 |
May | 3441.11 | 14-MAY-15:02 | 324.00 | 777.60 | 458.31 | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 0.00 |
June | 3380.80 | 08-JUN-18:01 | 970.20 | 2446.69 | 903.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.99 |
July | 3334.36 | 13-JUL-15:02 | 583.20 | 659.78 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.65 |
August | 3386.79 | 24-AUG-08:62 | 216.00 | 1036.80 | 679.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.21 |
September | 3366.51 | 14-SEP-08:61 | 252.00 | 1209.60 | 792.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.51 |
October | 3433.26 | 04-OCT-15:02 | 583.20 | 659.78 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.80 |
November | 3155.30 | 04-NOV-15:02 | 324.00 | 777.60 | 458.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.21 |
December | 1844.92 | 02-DEC-09:02 | 324.00 | 1319.56 | 979.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 676.41 | 216.00 | 659.78 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3441.11 | 970.20 | 2749.09 | 979.84 | 0.00 | 0.00 | 0.00 | 0.00 | 18.15 | 126.98 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 575.94 | 10-JAN-09:05 | 216.00 | 1036.68 | 679.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 110.86 |
February | 1980.14 | 27-FEB-16:01 | 680.40 | 769.66 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.94 |
March | 3020.08 | 02-MAR-09:02 | 216.00 | 1036.68 | 679.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 122.89 |
April | 3150.57 | 02-APR-15:01 | 378.00 | 907.09 | 534.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.60 |
May | 3155.40 | 14-MAY-15:02 | 324.00 | 777.51 | 458.26 | 0.00 | 0.00 | 0.00 | 0.00 | 5.57 | 0.00 |
June | 3140.19 | 01-JUN-15:01 | 680.40 | 769.66 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.30 |
July | 3088.73 | 24-JUL-18:02 | 831.60 | 2096.92 | 774.30 | 0.00 | 0.00 | 0.00 | 0.00 | 40.32 | 0.00 |
August | 3127.81 | 08-AUG-08:62 | 216.00 | 1036.68 | 679.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.23 |
September | 3062.88 | 10-SEP-08:61 | 378.00 | 1539.31 | 1143.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.07 |
October | 3056.37 | 04-OCT-15:02 | 583.20 | 659.70 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 |
November | 2163.05 | 04-NOV-15:02 | 324.00 | 777.51 | 458.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.12 |
December | 596.26 | 03-DEC-09:04 | 270.00 | 1099.51 | 816.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.30 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 575.94 | 216.00 | 659.70 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3155.40 | 831.60 | 2096.92 | 1143.02 | 0.00 | 0.00 | 0.00 | 0.00 | 40.32 | 122.89 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1547.28 | 11-JAN-22:03 | 6790.07 | 2565.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.58 |
February | 2225.47 | 27-FEB-16:30 | 1257.42 | 356.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.90 |
March | 2558.88 | 18-MAR-17:13 | 4526.71 | 2565.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.61 |
April | 2951.64 | 27-APR-18:10 | 10562.33 | 6840.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.19 | 0.00 |
May | 2961.15 | 06-MAY-10:35 | 1508.90 | 712.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.95 |
June | 3012.18 | 28-JUN-18:10 | 10562.33 | 6840.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.22 | 0.00 |
July | 3177.92 | 24-JUL-18:10 | 10562.33 | 6840.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.45 | 0.00 |
August | 3236.03 | 13-AUG-10:35 | 1508.90 | 855.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.85 | 0.00 |
September | 3050.00 | 14-SEP-10:40 | 502.97 | 356.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.98 |
October | 2854.00 | 04-OCT-10:35 | 1005.94 | 712.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.62 |
November | 2420.61 | 04-NOV-16:20 | 1257.42 | 356.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.76 |
December | 1685.58 | 03-DEC-13:00 | 754.45 | 427.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.58 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 1547.28 | 502.97 | 356.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3236.03 | 10562.33 | 6840.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.45 | 86.58 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2039.56 | 20-JAN-16:02 | 583.20 | 659.78 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 114.85 |
February | 3916.48 | 12-FEB-16:01 | 378.00 | 907.20 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.65 |
March | 3974.28 | 01-MAR-16:01 | 680.40 | 769.75 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.10 |
April | 4006.20 | 01-APR-18:01 | 819.00 | 2749.09 | 903.46 | 0.00 | 0.00 | 0.00 | 0.00 | 17.49 | 0.00 |
May | 4096.43 | 14-MAY-15:02 | 324.00 | 777.60 | 458.31 | 0.00 | 0.00 | 0.00 | 0.00 | 3.92 | 0.00 |
June | 3952.37 | 01-JUN-18:02 | 831.60 | 2097.16 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.86 |
July | 4005.03 | 31-JUL-18:02 | 831.60 | 2097.16 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 23.95 | 0.00 |
August | 3999.07 | 10-AUG-18:02 | 831.60 | 2097.16 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 50.02 | 0.00 |
September | 3813.32 | 14-SEP-18:02 | 831.60 | 2097.16 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.29 |
October | 4079.01 | 04-OCT-15:02 | 583.20 | 659.78 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.26 |
November | 3879.92 | 11-NOV-16:01 | 378.00 | 907.20 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 113.19 |
December | 3727.56 | 05-DEC-16:02 | 583.20 | 659.78 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.06 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2039.56 | 324.00 | 659.78 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4096.43 | 831.60 | 2749.09 | 903.46 | 0.00 | 0.00 | 0.00 | 0.00 | 50.02 | 114.85 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 655.57 | 05-JAN-16:04 | 680.40 | 769.66 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 110.63 |
February | 2778.72 | 26-FEB-16:01 | 378.00 | 907.09 | 534.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.82 |
March | 3550.28 | 01-MAR-16:01 | 680.40 | 769.66 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.37 |
April | 3635.76 | 01-APR-18:01 | 819.00 | 2748.77 | 903.35 | 0.00 | 0.00 | 0.00 | 0.00 | 17.28 | 0.00 |
May | 3708.11 | 14-MAY-18:02 | 702.00 | 2356.09 | 774.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.04 |
June | 3610.99 | 01-JUN-18:02 | 831.60 | 2096.92 | 774.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.54 |
July | 3611.96 | 31-JUL-18:02 | 831.60 | 2096.92 | 774.30 | 0.00 | 0.00 | 0.00 | 0.00 | 23.33 | 0.00 |
August | 3636.10 | 24-AUG-18:02 | 831.60 | 2096.92 | 774.30 | 0.00 | 0.00 | 0.00 | 0.00 | 32.41 | 0.00 |
September | 3501.39 | 13-SEP-18:02 | 831.60 | 2096.92 | 774.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 |
October | 3636.41 | 04-OCT-15:02 | 583.20 | 659.70 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.34 |
November | 3305.11 | 04-NOV-15:02 | 324.00 | 777.51 | 458.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.51 |
December | 707.90 | 03-DEC-16:03 | 378.00 | 907.09 | 534.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.14 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 655.57 | 324.00 | 659.70 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3708.11 | 831.60 | 2748.77 | 903.35 | 0.00 | 0.00 | 0.00 | 0.00 | 32.41 | 110.63 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2452.36 | 07-JAN-16:01 | 378.00 | 570.30 | 523.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.30 |
February | 2449.42 | 12-FEB-16:01 | 378.00 | 570.30 | 523.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.82 |
March | 2463.08 | 18-MAR-15:02 | 324.00 | 488.83 | 449.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.57 |
April | 2442.36 | 01-APR-18:01 | 819.00 | 1728.17 | 885.15 | 0.00 | 0.00 | 0.00 | 0.00 | 9.11 | 0.00 |
May | 2443.43 | 20-MAY-15:01 | 378.00 | 570.30 | 523.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.67 |
June | 2363.78 | 08-JUN-18:01 | 970.20 | 1538.07 | 885.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.04 |
July | 2362.07 | 24-JUL-18:02 | 831.60 | 1318.35 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 20.95 | 0.00 |
August | 2374.50 | 24-AUG-15:02 | 583.20 | 414.76 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 22.85 | 0.00 |
September | 2436.43 | 14-SEP-15:02 | 583.20 | 414.76 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 3.97 | 0.00 |
October | 2516.15 | 04-OCT-15:02 | 583.20 | 414.76 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.93 |
November | 2430.60 | 11-NOV-16:01 | 378.00 | 570.30 | 523.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.73 |
December | 2445.35 | 06-DEC-16:01 | 680.40 | 483.89 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.79 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2362.07 | 324.00 | 414.76 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2516.15 | 970.20 | 1728.17 | 885.15 | 0.00 | 0.00 | 0.00 | 0.00 | 22.85 | 73.30 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 18815.09 | 11-JAN-23:00 | 26988.77 | 2548.93 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 229.84 |
February | 19173.72 | 27-FEB-23:00 | 26988.77 | 2548.93 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 183.56 |
March | 19318.41 | 08-MAR-23:15 | 53977.54 | 2548.93 | 13495.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 162.33 |
April | 21388.68 | 27-APR-18:10 | 125947.58 | 20391.43 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 60.62 | 0.00 |
May | 21302.88 | 31-MAY-18:10 | 125947.58 | 20391.43 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.45 |
June | 22243.77 | 28-JUN-18:10 | 125947.58 | 20391.43 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 55.99 | 0.00 |
July | 22733.26 | 24-JUL-18:10 | 125947.58 | 20391.43 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 108.88 | 0.00 |
August | 22726.22 | 10-AUG-18:10 | 125947.58 | 20391.43 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 136.63 | 0.00 |
September | 20841.51 | 13-SEP-18:10 | 125947.58 | 20391.43 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 11.40 | 0.00 |
October | 19508.23 | 25-OCT-21:10 | 107955.07 | 10195.71 | 26991.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 156.02 |
November | 19275.97 | 06-NOV-23:00 | 26988.77 | 2548.93 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 121.35 |
December | 18665.37 | 29-DEC-23:00 | 26988.77 | 2548.93 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 241.15 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 18665.37 | 26988.77 | 2548.93 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22733.26 | 125947.58 | 20391.43 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 136.63 | 241.15 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 20046.80 | 11-JAN-23:00 | 26988.77 | 2548.93 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 231.77 |
February | 20406.45 | 27-FEB-23:00 | 26988.77 | 2548.93 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 185.38 |
March | 20571.87 | 08-MAR-23:15 | 53977.54 | 2548.93 | 13495.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 164.22 |
April | 22731.97 | 27-APR-18:10 | 125947.58 | 20391.43 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 58.89 | 0.00 |
May | 22687.01 | 31-MAY-18:10 | 125947.58 | 20391.43 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.50 |
June | 23651.00 | 28-JUN-18:10 | 125947.58 | 20391.43 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 54.12 | 0.00 |
July | 24140.07 | 24-JUL-18:10 | 125947.58 | 20391.43 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 107.18 | 0.00 |
August | 24089.40 | 10-AUG-18:10 | 125947.58 | 20391.43 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 135.20 | 0.00 |
September | 22146.77 | 13-SEP-18:10 | 125947.58 | 20391.43 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 9.71 | 0.00 |
October | 20763.73 | 25-OCT-21:10 | 107955.07 | 10195.71 | 26991.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 157.83 |
November | 20522.08 | 06-NOV-23:00 | 26988.77 | 2548.93 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 123.15 |
December | 19894.03 | 29-DEC-23:00 | 26988.77 | 2548.93 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 243.13 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 19894.03 | 26988.77 | 2548.93 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 24140.07 | 125947.58 | 20391.43 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 135.20 | 243.13 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 26621.61 | 11-JAN-19:08 | 7471.97 | 3629.43 | 60448.42 | 59980.88 | 0.00 | 0.00 | 0.00 | 0.00 | 180.76 |
February | 27160.63 | 27-FEB-11:50 | 533.71 | 283.55 | 15112.11 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 117.54 |
March | 28567.51 | 14-MAR-10:50 | 533.71 | 283.55 | 15112.11 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 195.66 |
April | 30036.29 | 27-APR-10:50 | 533.71 | 283.55 | 15112.11 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 49.91 |
May | 30174.96 | 14-MAY-10:50 | 800.57 | 340.26 | 15112.11 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 56.10 |
June | 30444.86 | 10-JUN-10:40 | 1601.14 | 567.10 | 30224.21 | 37488.05 | 0.00 | 0.00 | 0.00 | 0.00 | 58.21 |
July | 30921.54 | 24-JUL-10:40 | 1067.42 | 567.10 | 30224.21 | 37488.05 | 0.00 | 0.00 | 0.00 | 26.79 | 0.00 |
August | 30999.26 | 08-AUG-10:40 | 1067.42 | 567.10 | 30224.21 | 37488.05 | 0.00 | 0.00 | 0.00 | 10.41 | 0.00 |
September | 30263.43 | 10-SEP-10:50 | 800.57 | 340.26 | 15112.11 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 81.97 |
October | 29022.69 | 04-OCT-10:50 | 533.71 | 283.55 | 15112.11 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 81.81 |
November | 28309.07 | 04-NOV-10:50 | 1601.14 | 567.10 | 30224.21 | 37488.05 | 0.00 | 0.00 | 0.00 | 0.00 | 99.21 |
December | 26378.81 | 03-DEC-11:50 | 800.57 | 340.26 | 15112.11 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 190.55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 26378.81 | 533.71 | 283.55 | 15112.11 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 30999.26 | 7471.97 | 3629.43 | 60448.42 | 59980.88 | 0.00 | 0.00 | 0.00 | 26.79 | 195.66 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3123.34 | 20-JAN-13:30 | 532.32 | 377.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 222.18 |
February | 5059.06 | 27-FEB-14:30 | 532.32 | 377.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.02 |
March | 5722.74 | 14-MAR-15:40 | 1330.80 | 377.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.62 |
April | 6759.97 | 27-APR-17:12 | 5323.20 | 3619.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.27 | 0.00 |
May | 6726.22 | 15-MAY-17:12 | 5323.20 | 3619.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.70 | 0.00 |
June | 6988.68 | 28-JUN-18:10 | 11178.72 | 7239.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.51 | 0.00 |
July | 7434.89 | 24-JUL-10:35 | 1064.64 | 754.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.94 | 0.00 |
August | 7543.52 | 10-AUG-10:35 | 1064.64 | 754.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.23 | 0.00 |
September | 6737.13 | 14-SEP-17:12 | 5323.20 | 3619.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.83 | 0.00 |
October | 5991.19 | 04-OCT-15:30 | 1330.80 | 377.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.26 |
November | 5553.96 | 04-NOV-15:15 | 1596.96 | 754.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.70 |
December | 3457.40 | 05-DEC-12:40 | 532.32 | 377.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 160.22 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 3123.34 | 532.32 | 377.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7543.52 | 11178.72 | 7239.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.27 | 222.18 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.553785E+12 | 325490.89 | 11-JAN-20:00 | 0.710393E+12 | 523159.42 | 16-JAN-17:40 |
February | 0.503917E+12 | 342619.51 | 27-FEB-20:30 | 0.608672E+12 | 516202.86 | 18-FEB-17:00 |
March | 0.565350E+12 | 348474.26 | 14-MAR-19:10 | 0.624736E+12 | 456732.06 | 05-MAR-17:49 |
April | 0.572420E+12 | 439707.28 | 27-APR-19:10 | 0.568323E+12 | 445479.46 | 03-APR-17:40 |
May | 0.612570E+12 | 423141.21 | 05-MAY-18:10 | 0.556616E+12 | 423541.66 | 28-MAY-16:00 |
June | 0.621356E+12 | 440838.94 | 28-JUN-18:10 | 0.510513E+12 | 411935.14 | 06-JUN-17:00 |
July | 0.688408E+12 | 480429.05 | 24-JUL-18:10 | 0.505487E+12 | 401782.75 | 16-JUL-16:40 |
August | 0.718861E+12 | 506147.55 | 10-AUG-18:10 | 0.499862E+12 | 400369.97 | 27-AUG-16:49 |
September | 0.616311E+12 | 428493.34 | 13-SEP-18:30 | 0.502429E+12 | 407196.18 | 17-SEP-16:19 |
October | 0.584540E+12 | 369395.55 | 04-OCT-19:00 | 0.568122E+12 | 423459.73 | 31-OCT-17:00 |
November | 0.541729E+12 | 351229.72 | 03-NOV-19:00 | 0.613217E+12 | 463677.65 | 26-NOV-17:19 |
December | 0.555897E+12 | 324513.60 | 05-DEC-20:30 | 0.687741E+12 | 514594.68 | 25-DEC-17:49 |
Annual Sum or Average | 0.713514E+13 | 0.695611E+13 | ||||
Minimum of Months | 0.503917E+12 | 324513.60 | 0.499862E+12 | 400369.97 | ||
Maximum of Months | 0.718861E+12 | 506147.55 | 0.710393E+12 | 523159.42 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [J] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.997859E+11 | 0.284605E+11 | 0.148746E+12 | 0.577258E+11 | 0.155817E+12 | 0.395441E+10 | 0.00 | 0.153879E+10 | 0.00 | 0.00 | 0.438034E+11 | 0.770814E+10 | 0.00 |
February | 0.901073E+11 | 0.234634E+11 | 0.134341E+12 | 0.521396E+11 | 0.139469E+12 | 0.638585E+10 | 0.00 | 0.744644E+10 | 0.00 | 0.00 | 0.379426E+11 | 0.696512E+10 | 0.00 |
March | 0.995228E+11 | 0.229026E+11 | 0.148757E+12 | 0.577286E+11 | 0.152872E+12 | 0.107170E+11 | 0.00 | 0.173945E+11 | 0.00 | 0.00 | 0.414649E+11 | 0.770647E+10 | 0.00 |
April | 0.965474E+11 | 0.190771E+11 | 0.143913E+12 | 0.558635E+11 | 0.150159E+12 | 0.145409E+11 | 0.00 | 0.438364E+11 | 0.00 | 0.00 | 0.349097E+11 | 0.746775E+10 | 0.00 |
May | 0.996636E+11 | 0.169441E+11 | 0.148757E+12 | 0.577273E+11 | 0.157369E+12 | 0.174842E+11 | 0.00 | 0.718651E+11 | 0.00 | 0.00 | 0.287040E+11 | 0.770729E+10 | 0.00 |
June | 0.963626E+11 | 0.149112E+11 | 0.143963E+12 | 0.558662E+11 | 0.154070E+12 | 0.188461E+11 | 0.00 | 0.104694E+12 | 0.00 | 0.00 | 0.190131E+11 | 0.745943E+10 | 0.00 |
July | 0.998551E+11 | 0.160929E+11 | 0.148708E+12 | 0.577246E+11 | 0.161758E+12 | 0.208862E+11 | 0.00 | 0.153796E+12 | 0.00 | 0.00 | 0.155040E+11 | 0.771500E+10 | 0.00 |
August | 0.995413E+11 | 0.184763E+11 | 0.148768E+12 | 0.577287E+11 | 0.161721E+12 | 0.213227E+11 | 0.00 | 0.180509E+12 | 0.00 | 0.00 | 0.166729E+11 | 0.770691E+10 | 0.00 |
September | 0.965794E+11 | 0.208196E+11 | 0.143924E+12 | 0.558636E+11 | 0.153420E+12 | 0.180120E+11 | 0.00 | 0.941065E+11 | 0.00 | 0.00 | 0.199300E+11 | 0.746888E+10 | 0.00 |
October | 0.997606E+11 | 0.247051E+11 | 0.148735E+12 | 0.577257E+11 | 0.154210E+12 | 0.144082E+11 | 0.00 | 0.363726E+11 | 0.00 | 0.00 | 0.345870E+11 | 0.770632E+10 | 0.00 |
November | 0.965244E+11 | 0.267080E+11 | 0.143978E+12 | 0.558644E+11 | 0.147474E+12 | 0.750074E+10 | 0.00 | 0.990403E+10 | 0.00 | 0.00 | 0.402376E+11 | 0.745229E+10 | 0.00 |
December | 0.998619E+11 | 0.291915E+11 | 0.148708E+12 | 0.577246E+11 | 0.155156E+12 | 0.464037E+10 | 0.00 | 0.267117E+10 | 0.00 | 0.00 | 0.439708E+11 | 0.771624E+10 | 0.00 |
Annual Sum or Average | 0.117411E+13 | 0.261752E+12 | 0.175130E+13 | 0.679683E+12 | 0.184350E+13 | 0.158699E+12 | 0.00 | 0.724135E+12 | 0.00 | 0.00 | 0.376740E+12 | 0.907798E+11 | 0.00 |
Minimum of Months | 0.901073E+11 | 0.149112E+11 | 0.134341E+12 | 0.521396E+11 | 0.139469E+12 | 0.395441E+10 | 0.00 | 0.153879E+10 | 0.00 | 0.00 | 0.155040E+11 | 0.696512E+10 | 0.00 |
Maximum of Months | 0.998619E+11 | 0.291915E+11 | 0.148768E+12 | 0.577287E+11 | 0.161758E+12 | 0.213227E+11 | 0.00 | 0.180509E+12 | 0.00 | 0.00 | 0.439708E+11 | 0.771624E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.151918E+12 | 0.00 | 0.271327E+12 | 0.00 | 0.287148E+12 | 0.00 | 0.00 |
February | 0.137204E+12 | 0.00 | 0.210886E+12 | 0.00 | 0.260582E+12 | 0.00 | 0.00 |
March | 0.152024E+12 | 0.00 | 0.186283E+12 | 0.00 | 0.286429E+12 | 0.00 | 0.00 |
April | 0.146956E+12 | 0.00 | 0.149215E+12 | 0.00 | 0.272152E+12 | 0.00 | 0.00 |
May | 0.151978E+12 | 0.00 | 0.130235E+12 | 0.00 | 0.274402E+12 | 0.00 | 0.00 |
June | 0.147114E+12 | 0.00 | 0.104198E+12 | 0.00 | 0.259202E+12 | 0.00 | 0.00 |
July | 0.151820E+12 | 0.00 | 0.905574E+11 | 0.00 | 0.263109E+12 | 0.00 | 0.00 |
August | 0.152039E+12 | 0.00 | 0.860834E+11 | 0.00 | 0.261740E+12 | 0.00 | 0.00 |
September | 0.146971E+12 | 0.00 | 0.100059E+12 | 0.00 | 0.255399E+12 | 0.00 | 0.00 |
October | 0.151903E+12 | 0.00 | 0.147093E+12 | 0.00 | 0.269126E+12 | 0.00 | 0.00 |
November | 0.147091E+12 | 0.00 | 0.199101E+12 | 0.00 | 0.267026E+12 | 0.00 | 0.00 |
December | 0.151820E+12 | 0.00 | 0.253428E+12 | 0.00 | 0.282493E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.178884E+13 | 0.00 | 0.192847E+13 | 0.00 | 0.323881E+13 | 0.00 | 0.00 |
Minimum of Months | 0.137204E+12 | 0.00 | 0.860834E+11 | 0.00 | 0.255399E+12 | 0.00 | 0.00 |
Maximum of Months | 0.152039E+12 | 0.00 | 0.271327E+12 | 0.00 | 0.287148E+12 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 93091.76 | 02-JAN-20:10 | 16690.39 | 01-JAN-00:10 | 89674.66 | 02-JAN-07:10 | 40537.60 | 02-JAN-07:19 | 75562.05 | 16-JAN-16:10 | 5738.23 | 11-JAN-19:10 | 0.00 | 01-JAN-00:10 |
February | 93091.76 | 01-FEB-20:10 | 16690.39 | 01-FEB-00:10 | 89674.66 | 01-FEB-07:10 | 40537.60 | 01-FEB-07:19 | 72155.62 | 13-FEB-16:10 | 9148.43 | 27-FEB-16:30 | 0.00 | 01-FEB-00:10 |
March | 93091.76 | 01-MAR-20:10 | 16690.39 | 01-MAR-00:10 | 89674.66 | 01-MAR-07:10 | 40537.60 | 01-MAR-07:19 | 68692.53 | 14-MAR-15:09 | 8932.20 | 18-MAR-15:00 | 0.00 | 01-MAR-00:10 |
April | 93091.76 | 03-APR-19:10 | 16690.39 | 01-APR-00:10 | 89674.66 | 03-APR-06:10 | 40537.60 | 03-APR-06:19 | 73382.26 | 27-APR-15:09 | 9854.36 | 26-APR-16:00 | 0.00 | 01-APR-00:10 |
May | 93091.76 | 01-MAY-19:10 | 16690.39 | 01-MAY-00:10 | 89674.66 | 01-MAY-06:10 | 40537.60 | 01-MAY-06:19 | 76673.59 | 15-MAY-15:09 | 9974.69 | 14-MAY-10:50 | 0.00 | 01-MAY-00:10 |
June | 93091.76 | 01-JUN-19:10 | 16690.39 | 01-JUN-00:10 | 89674.66 | 01-JUN-06:10 | 40537.60 | 01-JUN-06:19 | 75200.54 | 27-JUN-18:19 | 9958.35 | 09-JUN-16:19 | 0.00 | 01-JUN-00:10 |
July | 93091.76 | 03-JUL-19:10 | 16690.39 | 01-JUL-00:10 | 89674.66 | 03-JUL-06:10 | 40537.60 | 03-JUL-06:19 | 76605.63 | 24-JUL-18:19 | 10046.79 | 31-JUL-10:39 | 0.00 | 01-JUL-00:10 |
August | 93091.76 | 01-AUG-19:10 | 16690.39 | 01-AUG-00:10 | 89674.66 | 01-AUG-06:10 | 40537.60 | 01-AUG-06:19 | 78029.57 | 10-AUG-15:20 | 10071.73 | 08-AUG-10:39 | 0.00 | 01-AUG-00:10 |
September | 93091.76 | 01-SEP-19:10 | 16690.39 | 01-SEP-00:10 | 89674.66 | 01-SEP-06:10 | 40537.60 | 01-SEP-06:19 | 75308.84 | 13-SEP-15:20 | 9895.13 | 14-SEP-10:50 | 0.00 | 01-SEP-00:10 |
October | 93091.76 | 02-OCT-19:10 | 16690.39 | 01-OCT-00:10 | 89674.66 | 02-OCT-06:10 | 40537.60 | 02-OCT-06:19 | 71219.53 | 04-OCT-15:09 | 9358.42 | 08-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 93091.76 | 01-NOV-19:10 | 16690.39 | 01-NOV-00:10 | 89674.66 | 01-NOV-06:10 | 40537.60 | 01-NOV-06:19 | 71075.91 | 30-NOV-16:10 | 9156.76 | 04-NOV-15:30 | 0.00 | 01-NOV-00:10 |
December | 93091.76 | 01-DEC-20:10 | 16690.39 | 01-DEC-00:10 | 89674.66 | 01-DEC-07:10 | 40537.60 | 01-DEC-07:19 | 76668.43 | 26-DEC-16:10 | 6812.14 | 05-DEC-11:50 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 93091.76 | 16690.39 | 89674.66 | 40537.60 | 68692.53 | 5738.23 | 0.00 | |||||||
Maximum of Months | 93091.76 | 16690.39 | 89674.66 | 40537.60 | 78029.57 | 10071.73 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY {Maximum} [W] | HEATRECOVERY:ELECTRICITY {TIMESTAMP} | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 8757.61 | 11-JAN-21:00 | 0.00 | 0.00 | 16416.82 | 01-JAN-00:10 | 4739.94 | 02-JAN-07:10 | 0.00 |
February | 75692.38 | 27-FEB-16:10 | 0.00 | 0.00 | 16416.82 | 01-FEB-00:10 | 4738.64 | 14-FEB-19:10 | 0.00 |
March | 85691.12 | 18-MAR-15:09 | 0.00 | 0.00 | 16416.82 | 01-MAR-00:10 | 4739.22 | 22-MAR-06:10 | 0.00 |
April | 142560.38 | 27-APR-15:20 | 0.00 | 0.00 | 16416.82 | 26-APR-17:10 | 4739.32 | 18-APR-06:10 | 0.00 |
May | 126494.47 | 05-MAY-18:10 | 0.00 | 0.00 | 16416.82 | 03-MAY-17:10 | 4738.79 | 31-MAY-06:10 | 0.00 |
June | 140409.38 | 28-JUN-18:10 | 0.00 | 0.00 | 16416.82 | 09-JUN-17:10 | 4738.95 | 28-JUN-06:19 | 0.00 |
July | 179461.72 | 24-JUL-15:20 | 0.00 | 0.00 | 16416.82 | 06-JUL-17:10 | 4738.89 | 28-JUL-06:10 | 0.00 |
August | 202014.87 | 10-AUG-18:10 | 0.00 | 0.00 | 16416.82 | 05-AUG-17:10 | 4738.70 | 11-AUG-06:10 | 0.00 |
September | 139074.42 | 14-SEP-15:20 | 0.00 | 0.00 | 16416.82 | 08-SEP-17:10 | 4738.87 | 06-SEP-06:10 | 0.00 |
October | 106557.72 | 04-OCT-15:09 | 0.00 | 0.00 | 16416.82 | 01-OCT-19:49 | 4739.56 | 11-OCT-06:10 | 0.00 |
November | 98438.43 | 04-NOV-15:09 | 0.00 | 0.00 | 16416.82 | 01-NOV-00:10 | 4739.72 | 08-NOV-07:10 | 0.00 |
December | 19254.43 | 05-DEC-12:30 | 0.00 | 0.00 | 16416.82 | 01-DEC-00:10 | 4738.76 | 18-DEC-07:00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 8757.61 | 0.00 | 0.00 | 16416.82 | 4738.64 | 0.00 | |||
Maximum of Months | 202014.87 | 0.00 | 0.00 | 16416.82 | 4739.94 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 325490.89 | 11-JAN-20:00 | 93091.76 | 88971.67 | 16690.39 | 33025.38 | 57511.65 | 5576.45 | 0.00 | 7308.54 | 0.00 |
February | 342619.51 | 27-FEB-20:30 | 93091.76 | 88971.67 | 16690.39 | 33025.38 | 60944.67 | 6921.97 | 0.00 | 19822.67 | 0.00 |
March | 348474.26 | 14-MAR-19:10 | 93091.76 | 88971.67 | 16690.39 | 33012.66 | 62064.05 | 7713.69 | 0.00 | 40713.58 | 0.00 |
April | 439707.28 | 27-APR-19:10 | 93091.76 | 88971.67 | 16690.39 | 33012.66 | 66646.97 | 9226.45 | 0.00 | 108934.27 | 0.00 |
May | 423141.21 | 05-MAY-18:10 | 82800.17 | 79617.06 | 0.00 | 32686.23 | 68736.92 | 9276.50 | 0.00 | 126494.47 | 0.00 |
June | 440838.94 | 28-JUN-18:10 | 82800.17 | 79617.06 | 0.00 | 32686.23 | 72209.37 | 9464.85 | 0.00 | 140409.38 | 0.00 |
July | 480429.05 | 24-JUL-18:10 | 82800.17 | 79617.06 | 0.00 | 32686.23 | 75548.41 | 9711.38 | 0.00 | 176092.21 | 0.00 |
August | 506147.55 | 10-AUG-18:10 | 82800.17 | 79617.06 | 0.00 | 32686.23 | 75156.48 | 9887.44 | 0.00 | 202014.87 | 0.00 |
September | 428493.34 | 13-SEP-18:30 | 82800.17 | 79617.06 | 16690.39 | 32707.97 | 67497.72 | 9275.78 | 0.00 | 115813.30 | 0.00 |
October | 369395.55 | 04-OCT-19:00 | 93091.76 | 88971.67 | 16690.39 | 33025.38 | 61512.10 | 8133.90 | 0.00 | 61345.05 | 0.00 |
November | 351229.72 | 03-NOV-19:00 | 93091.76 | 88971.67 | 16690.39 | 33025.38 | 58803.36 | 7456.81 | 0.00 | 47255.83 | 0.00 |
December | 324513.60 | 05-DEC-20:30 | 93091.76 | 88971.67 | 16690.39 | 33025.38 | 58129.11 | 5719.43 | 0.00 | 6184.30 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 324513.60 | 82800.17 | 79617.06 | 0.00 | 32686.23 | 57511.65 | 5576.45 | 0.00 | 6184.30 | 0.00 | |
Maximum of Months | 506147.55 | 93091.76 | 88971.67 | 16690.39 | 33025.38 | 75548.41 | 9887.44 | 0.00 | 202014.87 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 104248.32 | 02-JAN-18:10 | 0.00 | 214862.75 | 07-JAN-09:09 | 0.00 | 285443.89 | 18-JAN-21:40 | 0.00 |
February | 104248.32 | 01-FEB-18:10 | 0.00 | 227830.41 | 19-FEB-07:10 | 0.00 | 286401.03 | 14-FEB-21:40 | 0.00 |
March | 104248.32 | 01-MAR-18:10 | 0.00 | 152454.62 | 05-MAR-16:10 | 0.00 | 285885.15 | 01-MAR-21:00 | 0.00 |
April | 104248.32 | 01-APR-17:10 | 0.00 | 132040.15 | 17-APR-10:39 | 0.00 | 273031.58 | 04-APR-20:00 | 0.00 |
May | 104248.32 | 01-MAY-17:10 | 0.00 | 123120.11 | 18-MAY-10:39 | 0.00 | 259401.87 | 01-MAY-20:19 | 0.00 |
June | 104248.32 | 01-JUN-17:10 | 0.00 | 121468.32 | 13-JUN-10:39 | 0.00 | 249913.20 | 02-JUN-20:00 | 0.00 |
July | 104248.32 | 01-JUL-17:10 | 0.00 | 111796.52 | 12-JUL-10:39 | 0.00 | 248894.48 | 03-JUL-20:40 | 0.00 |
August | 104248.32 | 01-AUG-17:10 | 0.00 | 109438.87 | 01-AUG-10:39 | 0.00 | 248466.74 | 31-AUG-20:19 | 0.00 |
September | 104248.32 | 01-SEP-17:10 | 0.00 | 118826.63 | 18-SEP-10:39 | 0.00 | 249082.57 | 29-SEP-20:30 | 0.00 |
October | 104248.32 | 02-OCT-17:10 | 0.00 | 121764.65 | 18-OCT-10:39 | 0.00 | 250201.62 | 31-OCT-20:00 | 0.00 |
November | 104248.32 | 01-NOV-17:10 | 0.00 | 158764.41 | 26-NOV-16:10 | 0.00 | 269959.52 | 28-NOV-21:00 | 0.00 |
December | 104248.32 | 01-DEC-18:10 | 0.00 | 219008.52 | 26-DEC-09:09 | 0.00 | 283071.87 | 27-DEC-21:00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 104248.32 | 0.00 | 109438.87 | 0.00 | 248466.74 | 0.00 | |||
Maximum of Months | 104248.32 | 0.00 | 227830.41 | 0.00 | 286401.03 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 12.33 | 20.39 | 12.33 | 20.39 | 0.00 | 20.39 | 0.00 | 20.39 |
February | 9.00 | 20.28 | 9.00 | 20.28 | 0.00 | 20.28 | 0.00 | 20.28 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 14.17 | 20.28 | 14.17 | 20.28 | 0.00 | 20.28 | 0.00 | 20.28 |
Annual Sum or Average | 35.50 | 20.32 | 35.50 | 20.32 | 0.00 | 20.32 | 0.00 | 20.32 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 14.17 | 20.39 | 14.17 | 20.39 | 0.00 | 20.39 | 0.00 | 20.39 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 20.55 | 0.17 | 20.55 | 0.00 | 20.55 | 0.00 | 20.55 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.67 | 0.17 | 21.67 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.80 | 0.50 | 21.80 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.69 | 0.17 | 21.69 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.72 | 0.83 | 21.72 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.69 | 0.33 | 21.69 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.33 | 20.52 | 0.33 | 20.52 | 0.00 | 20.52 | 0.00 | 20.52 |
Annual Sum or Average | 0.50 | 20.53 | 0.50 | 20.53 | 2.00 | 21.33 | 2.00 | 21.49 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.33 | 20.55 | 0.33 | 20.55 | 0.83 | 21.80 | 0.83 | 21.80 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.17 | 20.51 | 1.17 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 |
February | 0.17 | 20.51 | 0.17 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.84 | 0.17 | 21.84 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.71 | 0.83 | 21.71 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.72 | 0.17 | 21.72 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.83 | 20.52 | 0.83 | 20.52 | 0.00 | 20.52 | 0.00 | 20.52 |
Annual Sum or Average | 2.17 | 20.52 | 2.17 | 20.52 | 1.17 | 20.77 | 1.17 | 20.94 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.17 | 20.52 | 1.17 | 20.52 | 0.83 | 21.84 | 0.83 | 21.84 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.83 | 20.36 | 0.83 | 20.36 | 0.00 | 20.36 | 0.00 | 20.36 |
February | 0.33 | 20.50 | 0.33 | 20.50 | 0.00 | 20.50 | 0.00 | 20.50 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.70 | 0.33 | 21.70 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.68 | 0.33 | 21.68 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.17 | 20.19 | 0.17 | 20.19 | 0.00 | 20.19 | 0.00 | 20.19 |
Annual Sum or Average | 1.33 | 20.37 | 1.33 | 20.37 | 0.67 | 20.64 | 0.67 | 20.81 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.83 | 20.50 | 0.83 | 20.50 | 0.33 | 21.70 | 0.33 | 21.70 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.50 | 20.54 | 0.50 | 20.54 | 0.00 | 20.54 | 0.00 | 20.54 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.67 | 20.52 | 0.67 | 20.52 | 0.00 | 20.52 | 0.00 | 20.52 |
Annual Sum or Average | 1.17 | 20.53 | 1.17 | 20.53 | 0.00 | 20.53 | 0.00 | 20.53 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.67 | 20.54 | 0.67 | 20.54 | 0.00 | 20.54 | 0.00 | 20.54 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.67 | 20.53 | 1.67 | 20.53 | 0.00 | 20.53 | 0.00 | 20.53 |
February | 0.33 | 20.55 | 0.33 | 20.55 | 0.00 | 20.55 | 0.00 | 20.55 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.83 | 20.50 | 0.83 | 20.50 | 0.00 | 20.50 | 0.00 | 20.50 |
Annual Sum or Average | 2.83 | 20.52 | 2.83 | 20.52 | 0.00 | 20.52 | 0.00 | 20.52 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.67 | 20.55 | 1.67 | 20.55 | 0.00 | 20.55 | 0.00 | 20.55 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.75 | 0.33 | 21.75 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 21.85 | 1.50 | 21.85 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.70 | 0.33 | 21.70 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.77 | 1.00 | 21.77 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 21.78 | 2.17 | 21.78 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.82 | 1.00 | 21.82 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.17 | 20.53 | 0.17 | 20.53 | 0.00 | 20.53 | 0.00 | 20.53 |
Annual Sum or Average | 0.17 | 20.53 | 0.17 | 20.53 | 6.33 | 21.73 | 6.33 | 21.76 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 20.53 | 0.17 | 20.53 | 2.17 | 21.85 | 2.17 | 21.85 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.33 | 20.52 | 0.33 | 20.52 | 0.00 | 20.52 | 0.00 | 20.52 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.82 | 1.00 | 21.82 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.71 | 1.00 | 21.71 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 21.77 | 2.17 | 21.77 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 21.78 | 1.50 | 21.78 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.33 | 20.51 | 0.33 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 |
Annual Sum or Average | 0.67 | 20.52 | 0.67 | 20.52 | 5.67 | 21.53 | 5.67 | 21.64 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.33 | 20.52 | 0.33 | 20.52 | 2.17 | 21.82 | 2.17 | 21.82 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.69 | 0.17 | 21.69 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.70 | 0.17 | 21.70 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.67 | 0.33 | 21.67 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.71 | 0.50 | 21.71 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 1.17 | 21.69 | 1.17 | 21.69 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.71 | 0.50 | 21.71 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.06 | 0.00 | 21.06 | 0.00 | 21.06 |
February | 672.00 | 21.05 | 4.33 | 21.05 | 4.33 | 21.05 |
March | 744.00 | 21.04 | 14.83 | 21.04 | 14.83 | 21.04 |
April | 720.00 | 21.02 | 0.00 | 21.02 | 0.00 | 21.02 |
May | 744.00 | 21.02 | 0.00 | 21.02 | 0.00 | 21.02 |
June | 720.00 | 21.03 | 0.00 | 21.03 | 0.00 | 21.03 |
July | 744.00 | 21.04 | 0.00 | 21.04 | 0.00 | 21.04 |
August | 744.00 | 21.05 | 0.00 | 21.05 | 0.00 | 21.05 |
September | 720.00 | 21.07 | 0.00 | 21.07 | 0.00 | 21.07 |
October | 744.00 | 21.10 | 0.00 | 21.10 | 0.00 | 21.10 |
November | 720.00 | 21.12 | 0.00 | 21.12 | 0.00 | 21.12 |
December | 744.00 | 21.09 | 0.00 | 21.09 | 0.00 | 21.09 |
Annual Sum or Average | 8760.00 | 21.06 | 19.17 | 21.06 | 19.17 | 21.06 |
Minimum of Months | 672.00 | 21.02 | 0.00 | 21.02 | 0.00 | 21.02 |
Maximum of Months | 744.00 | 21.12 | 14.83 | 21.12 | 14.83 | 21.12 |
Report: ComfortReportSimple55Monthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.91 | 411.17 | 20.88 | 411.17 | 20.87 |
February | 672.00 | 20.98 | 209.00 | 20.95 | 209.00 | 20.94 |
March | 737.50 | 21.02 | 62.00 | 21.02 | 62.00 | 21.02 |
April | 717.67 | 21.02 | 11.83 | 21.02 | 11.83 | 21.02 |
May | 742.00 | 21.02 | 0.00 | 21.02 | 0.00 | 21.02 |
June | 720.00 | 21.00 | 0.00 | 21.00 | 0.00 | 21.00 |
July | 743.00 | 21.02 | 0.00 | 21.02 | 0.00 | 21.02 |
August | 714.83 | 21.03 | 6.50 | 21.04 | 0.00 | 21.04 |
September | 680.83 | 21.03 | 20.17 | 21.07 | 0.00 | 21.07 |
October | 734.17 | 21.03 | 1.00 | 21.04 | 0.00 | 21.04 |
November | 716.33 | 20.99 | 158.67 | 20.98 | 156.67 | 20.97 |
December | 744.00 | 20.91 | 382.83 | 20.88 | 382.83 | 20.87 |
Annual Sum or Average | 8666.33 | 21.00 | 1263.17 | 20.98 | 1233.50 | 20.97 |
Minimum of Months | 672.00 | 20.91 | 0.00 | 20.88 | 0.00 | 20.87 |
Maximum of Months | 744.00 | 21.03 | 411.17 | 21.07 | 411.17 | 21.07 |
Report: ComfortReportSimple55Monthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.00 | 6.83 | 21.00 | 6.83 | 21.00 |
February | 672.00 | 21.01 | 0.00 | 21.01 | 0.00 | 21.01 |
March | 744.00 | 21.02 | 0.00 | 21.02 | 0.00 | 21.02 |
April | 720.00 | 21.04 | 0.00 | 21.04 | 0.00 | 21.04 |
May | 744.00 | 21.06 | 0.00 | 21.06 | 0.00 | 21.06 |
June | 720.00 | 21.07 | 0.00 | 21.07 | 0.00 | 21.07 |
July | 744.00 | 21.10 | 0.00 | 21.10 | 0.00 | 21.10 |
August | 744.00 | 21.12 | 0.00 | 21.12 | 0.00 | 21.12 |
September | 720.00 | 21.07 | 0.00 | 21.07 | 0.00 | 21.07 |
October | 744.00 | 21.03 | 0.00 | 21.03 | 0.00 | 21.03 |
November | 720.00 | 21.01 | 0.00 | 21.01 | 0.00 | 21.01 |
December | 744.00 | 21.00 | 0.00 | 21.00 | 0.00 | 21.00 |
Annual Sum or Average | 8760.00 | 21.05 | 6.83 | 21.05 | 6.83 | 21.05 |
Minimum of Months | 672.00 | 21.00 | 0.00 | 21.00 | 0.00 | 21.00 |
Maximum of Months | 744.00 | 21.12 | 6.83 | 21.12 | 6.83 | 21.12 |
Report: ComfortReportSimple55Monthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.00 | 69.67 | 21.00 | 69.67 | 21.00 |
February | 672.00 | 21.00 | 70.00 | 21.00 | 70.00 | 21.00 |
March | 744.00 | 21.00 | 38.83 | 21.00 | 38.83 | 21.00 |
April | 720.00 | 21.00 | 0.00 | 21.00 | 0.00 | 21.00 |
May | 744.00 | 21.01 | 0.00 | 21.01 | 0.00 | 21.01 |
June | 720.00 | 21.02 | 0.00 | 21.02 | 0.00 | 21.02 |
July | 744.00 | 21.04 | 0.00 | 21.04 | 0.00 | 21.04 |
August | 744.00 | 21.04 | 0.00 | 21.04 | 0.00 | 21.04 |
September | 720.00 | 21.02 | 0.00 | 21.02 | 0.00 | 21.02 |
October | 744.00 | 21.00 | 0.00 | 21.00 | 0.00 | 21.00 |
November | 720.00 | 21.00 | 0.00 | 21.00 | 0.00 | 21.00 |
December | 744.00 | 21.00 | 4.67 | 21.00 | 4.67 | 21.00 |
Annual Sum or Average | 8760.00 | 21.01 | 183.17 | 21.01 | 183.17 | 21.01 |
Minimum of Months | 672.00 | 21.00 | 0.00 | 21.00 | 0.00 | 21.00 |
Maximum of Months | 744.00 | 21.04 | 70.00 | 21.04 | 70.00 | 21.04 |
Report: ComfortReportSimple55Monthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.00 | 164.17 | 21.00 | 164.17 | 21.00 |
February | 672.00 | 21.00 | 150.67 | 21.00 | 150.67 | 21.00 |
March | 744.00 | 21.00 | 63.50 | 21.00 | 63.50 | 21.00 |
April | 720.00 | 21.00 | 0.00 | 21.00 | 0.00 | 21.00 |
May | 744.00 | 21.00 | 0.00 | 21.00 | 0.00 | 21.00 |
June | 720.00 | 21.00 | 0.00 | 21.00 | 0.00 | 21.00 |
July | 744.00 | 21.00 | 0.00 | 21.00 | 0.00 | 21.00 |
August | 744.00 | 21.01 | 0.00 | 21.01 | 0.00 | 21.01 |
September | 720.00 | 21.00 | 0.00 | 21.00 | 0.00 | 21.00 |
October | 744.00 | 21.00 | 0.00 | 21.00 | 0.00 | 21.00 |
November | 720.00 | 21.00 | 11.50 | 21.00 | 11.50 | 21.00 |
December | 744.00 | 21.00 | 62.00 | 21.00 | 62.00 | 21.00 |
Annual Sum or Average | 8760.00 | 21.00 | 451.83 | 21.00 | 451.83 | 21.00 |
Minimum of Months | 672.00 | 21.00 | 0.00 | 21.00 | 0.00 | 21.00 |
Maximum of Months | 744.00 | 21.01 | 164.17 | 21.01 | 164.17 | 21.01 |
Report: ComfortReportSimple55Monthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 556.17 | 21.39 | 164.17 | 21.74 | 81.50 | 21.94 |
February | 475.83 | 21.43 | 159.83 | 21.77 | 78.17 | 21.98 |
March | 514.50 | 21.48 | 181.50 | 21.81 | 95.17 | 22.03 |
April | 431.33 | 21.55 | 202.00 | 21.84 | 95.00 | 22.05 |
May | 377.67 | 21.67 | 242.17 | 21.90 | 103.50 | 22.12 |
June | 301.83 | 21.82 | 271.67 | 21.93 | 103.83 | 22.16 |
July | 240.33 | 22.00 | 317.17 | 21.93 | 104.00 | 22.15 |
August | 202.83 | 22.27 | 373.83 | 21.96 | 110.00 | 22.18 |
September | 255.67 | 21.98 | 311.67 | 21.95 | 104.00 | 22.18 |
October | 450.83 | 21.57 | 221.67 | 21.85 | 101.33 | 22.07 |
November | 463.83 | 21.51 | 191.33 | 21.83 | 91.50 | 22.05 |
December | 536.33 | 21.41 | 162.50 | 21.76 | 82.83 | 21.96 |
Annual Sum or Average | 4807.17 | 21.60 | 2799.50 | 21.85 | 1150.83 | 22.07 |
Minimum of Months | 202.83 | 21.39 | 159.83 | 21.74 | 78.17 | 21.94 |
Maximum of Months | 556.17 | 22.27 | 373.83 | 21.96 | 110.00 | 22.18 |
Report: ComfortReportSimple55Monthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.00 | 37.50 | 21.00 | 37.50 | 21.00 |
February | 671.50 | 21.02 | 25.83 | 21.01 | 25.83 | 21.01 |
March | 735.33 | 21.02 | 0.50 | 21.02 | 0.50 | 21.02 |
April | 715.17 | 21.01 | 0.00 | 21.01 | 0.00 | 21.01 |
May | 741.83 | 21.01 | 0.00 | 21.01 | 0.00 | 21.01 |
June | 720.00 | 21.00 | 0.00 | 21.00 | 0.00 | 21.00 |
July | 742.83 | 21.01 | 0.00 | 21.01 | 0.00 | 21.01 |
August | 712.67 | 21.02 | 5.50 | 21.02 | 0.00 | 21.02 |
September | 676.83 | 21.02 | 21.83 | 21.05 | 0.00 | 21.05 |
October | 730.83 | 21.02 | 1.33 | 21.02 | 0.00 | 21.02 |
November | 715.83 | 21.00 | 4.00 | 21.01 | 1.00 | 21.01 |
December | 744.00 | 21.00 | 19.67 | 20.99 | 19.67 | 20.99 |
Annual Sum or Average | 8650.83 | 21.01 | 116.17 | 21.01 | 84.50 | 21.01 |
Minimum of Months | 671.50 | 21.00 | 0.00 | 20.99 | 0.00 | 20.99 |
Maximum of Months | 744.00 | 21.02 | 37.50 | 21.05 | 37.50 | 21.05 |
Report: ComfortReportSimple55Monthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.01 | 0.00 | 21.01 | 0.00 | 21.01 |
February | 672.00 | 21.02 | 0.00 | 21.02 | 0.00 | 21.02 |
March | 744.00 | 21.04 | 0.00 | 21.04 | 0.00 | 21.04 |
April | 720.00 | 21.06 | 0.00 | 21.06 | 0.00 | 21.06 |
May | 744.00 | 21.08 | 0.00 | 21.08 | 0.00 | 21.08 |
June | 720.00 | 21.11 | 0.00 | 21.11 | 0.00 | 21.11 |
July | 744.00 | 21.13 | 0.00 | 21.13 | 0.00 | 21.13 |
August | 744.00 | 21.16 | 0.00 | 21.16 | 0.00 | 21.16 |
September | 720.00 | 21.10 | 0.00 | 21.10 | 0.00 | 21.10 |
October | 744.00 | 21.05 | 0.00 | 21.05 | 0.00 | 21.05 |
November | 720.00 | 21.02 | 0.00 | 21.02 | 0.00 | 21.02 |
December | 744.00 | 21.01 | 0.00 | 21.01 | 0.00 | 21.01 |
Annual Sum or Average | 8760.00 | 21.07 | 0.00 | 21.07 | 0.00 | 21.07 |
Minimum of Months | 672.00 | 21.01 | 0.00 | 21.01 | 0.00 | 21.01 |
Maximum of Months | 744.00 | 21.16 | 0.00 | 21.16 | 0.00 | 21.16 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.69 | 589.33 | 20.64 | 589.33 | 20.62 |
February | 670.33 | 20.97 | 303.67 | 20.86 | 303.67 | 20.80 |
March | 741.17 | 21.21 | 104.17 | 21.13 | 104.17 | 21.06 |
April | 703.50 | 21.41 | 11.67 | 21.41 | 9.17 | 21.40 |
May | 703.17 | 21.47 | 6.50 | 21.49 | 0.83 | 21.49 |
June | 682.83 | 21.53 | 4.00 | 21.54 | 0.00 | 21.54 |
July | 656.50 | 21.45 | 22.33 | 21.52 | 0.00 | 21.52 |
August | 656.83 | 21.44 | 29.50 | 21.52 | 0.00 | 21.52 |
September | 657.33 | 21.39 | 17.00 | 21.44 | 0.00 | 21.44 |
October | 732.17 | 21.30 | 8.50 | 21.28 | 8.50 | 21.27 |
November | 717.67 | 20.92 | 271.83 | 20.81 | 271.83 | 20.75 |
December | 744.00 | 20.78 | 504.83 | 20.69 | 504.83 | 20.66 |
Annual Sum or Average | 8409.50 | 21.20 | 1873.33 | 21.11 | 1792.33 | 21.03 |
Minimum of Months | 656.50 | 20.69 | 4.00 | 20.64 | 0.00 | 20.62 |
Maximum of Months | 744.00 | 21.53 | 589.33 | 21.54 | 589.33 | 21.54 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.57 | 654.00 | 20.53 | 654.00 | 20.52 |
February | 672.00 | 20.76 | 422.67 | 20.68 | 422.67 | 20.64 |
March | 744.00 | 21.01 | 182.67 | 20.92 | 182.67 | 20.86 |
April | 713.67 | 21.29 | 19.33 | 21.27 | 19.33 | 21.25 |
May | 722.17 | 21.45 | 1.50 | 21.45 | 0.83 | 21.45 |
June | 698.00 | 21.51 | 1.83 | 21.52 | 0.00 | 21.52 |
July | 688.83 | 21.50 | 12.17 | 21.54 | 0.00 | 21.54 |
August | 694.83 | 21.49 | 10.83 | 21.52 | 0.00 | 21.52 |
September | 696.83 | 21.40 | 0.33 | 21.40 | 0.00 | 21.40 |
October | 744.00 | 21.13 | 23.33 | 21.10 | 23.33 | 21.07 |
November | 720.00 | 20.78 | 346.83 | 20.68 | 346.83 | 20.63 |
December | 744.00 | 20.62 | 636.33 | 20.58 | 636.33 | 20.57 |
Annual Sum or Average | 8582.33 | 21.12 | 2311.83 | 21.00 | 2286.00 | 20.92 |
Minimum of Months | 672.00 | 20.57 | 0.33 | 20.53 | 0.00 | 20.52 |
Maximum of Months | 744.00 | 21.51 | 654.00 | 21.54 | 654.00 | 21.54 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.90 | 268.83 | 20.82 | 268.83 | 20.77 |
February | 672.00 | 21.01 | 209.00 | 20.94 | 209.00 | 20.89 |
March | 744.00 | 21.19 | 17.00 | 21.19 | 17.00 | 21.18 |
April | 720.00 | 21.34 | 0.00 | 21.34 | 0.00 | 21.34 |
May | 744.00 | 21.45 | 0.00 | 21.45 | 0.00 | 21.45 |
June | 720.00 | 21.49 | 0.00 | 21.49 | 0.00 | 21.49 |
July | 744.00 | 21.52 | 0.00 | 21.52 | 0.00 | 21.52 |
August | 744.00 | 21.50 | 0.00 | 21.50 | 0.00 | 21.50 |
September | 720.00 | 21.40 | 0.00 | 21.40 | 0.00 | 21.40 |
October | 744.00 | 21.26 | 0.00 | 21.26 | 0.00 | 21.26 |
November | 720.00 | 21.08 | 56.50 | 21.04 | 56.50 | 21.00 |
December | 744.00 | 20.94 | 157.67 | 20.85 | 157.67 | 20.78 |
Annual Sum or Average | 8760.00 | 21.26 | 709.00 | 21.21 | 709.00 | 21.16 |
Minimum of Months | 672.00 | 20.90 | 0.00 | 20.82 | 0.00 | 20.77 |
Maximum of Months | 744.00 | 21.52 | 268.83 | 21.52 | 268.83 | 21.52 |
Report: ComfortReportSimple55Monthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.68 | 594.00 | 20.63 | 594.00 | 20.61 |
February | 672.00 | 20.98 | 300.33 | 20.88 | 300.33 | 20.83 |
March | 744.00 | 21.27 | 84.00 | 21.20 | 84.00 | 21.14 |
April | 704.17 | 21.50 | 7.50 | 21.49 | 7.50 | 21.48 |
May | 702.33 | 21.50 | 0.83 | 21.50 | 0.83 | 21.49 |
June | 661.83 | 21.53 | 0.00 | 21.53 | 0.00 | 21.53 |
July | 646.67 | 21.45 | 2.33 | 21.45 | 0.00 | 21.45 |
August | 638.50 | 21.42 | 8.33 | 21.44 | 0.00 | 21.44 |
September | 656.17 | 21.39 | 0.50 | 21.39 | 0.00 | 21.39 |
October | 738.00 | 21.35 | 7.33 | 21.33 | 7.33 | 21.32 |
November | 718.00 | 20.91 | 273.50 | 20.81 | 273.50 | 20.75 |
December | 744.00 | 20.76 | 503.33 | 20.69 | 503.33 | 20.65 |
Annual Sum or Average | 8369.67 | 21.22 | 1782.00 | 21.11 | 1770.83 | 21.03 |
Minimum of Months | 638.50 | 20.68 | 0.00 | 20.63 | 0.00 | 20.61 |
Maximum of Months | 744.00 | 21.53 | 594.00 | 21.53 | 594.00 | 21.53 |
Report: ComfortReportSimple55Monthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.56 | 651.17 | 20.52 | 651.17 | 20.51 |
February | 672.00 | 20.76 | 431.17 | 20.68 | 431.17 | 20.65 |
March | 744.00 | 21.07 | 127.17 | 21.01 | 127.17 | 20.96 |
April | 719.50 | 21.42 | 13.33 | 21.42 | 13.33 | 21.41 |
May | 736.17 | 21.53 | 0.83 | 21.53 | 0.83 | 21.53 |
June | 695.17 | 21.59 | 0.00 | 21.59 | 0.00 | 21.59 |
July | 696.17 | 21.57 | 1.83 | 21.57 | 0.00 | 21.57 |
August | 674.83 | 21.50 | 3.00 | 21.51 | 0.00 | 21.51 |
September | 702.00 | 21.44 | 0.00 | 21.44 | 0.00 | 21.44 |
October | 744.00 | 21.18 | 16.83 | 21.16 | 16.83 | 21.13 |
November | 720.00 | 20.77 | 358.67 | 20.67 | 358.67 | 20.62 |
December | 744.00 | 20.60 | 627.67 | 20.56 | 627.67 | 20.54 |
Annual Sum or Average | 8591.83 | 21.16 | 2231.67 | 21.03 | 2226.83 | 20.94 |
Minimum of Months | 672.00 | 20.56 | 0.00 | 20.52 | 0.00 | 20.51 |
Maximum of Months | 744.00 | 21.59 | 651.17 | 21.59 | 651.17 | 21.59 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.00 | 111.33 | 21.00 | 111.33 | 21.00 |
February | 672.00 | 21.00 | 99.50 | 21.00 | 99.50 | 21.00 |
March | 744.00 | 21.00 | 33.83 | 21.00 | 33.83 | 21.00 |
April | 720.00 | 21.02 | 0.00 | 21.02 | 0.00 | 21.02 |
May | 744.00 | 21.04 | 0.00 | 21.04 | 0.00 | 21.04 |
June | 720.00 | 21.06 | 0.00 | 21.06 | 0.00 | 21.06 |
July | 744.00 | 21.14 | 0.00 | 21.14 | 0.00 | 21.14 |
August | 744.00 | 21.22 | 0.00 | 21.22 | 0.00 | 21.22 |
September | 720.00 | 21.10 | 0.00 | 21.10 | 0.00 | 21.10 |
October | 744.00 | 21.01 | 0.00 | 21.01 | 0.00 | 21.01 |
November | 720.00 | 21.00 | 0.00 | 21.00 | 0.00 | 21.00 |
December | 744.00 | 21.00 | 27.50 | 21.00 | 27.50 | 21.00 |
Annual Sum or Average | 8760.00 | 21.05 | 272.17 | 21.05 | 272.17 | 21.05 |
Minimum of Months | 672.00 | 21.00 | 0.00 | 21.00 | 0.00 | 21.00 |
Maximum of Months | 744.00 | 21.22 | 111.33 | 21.22 | 111.33 | 21.22 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.60 | 697.33 | 20.58 | 697.33 | 20.57 |
February | 670.00 | 20.88 | 408.00 | 20.78 | 408.00 | 20.73 |
March | 738.83 | 21.13 | 222.50 | 21.03 | 222.50 | 20.96 |
April | 695.17 | 21.37 | 50.83 | 21.36 | 43.67 | 21.33 |
May | 680.50 | 21.42 | 20.50 | 21.47 | 3.33 | 21.46 |
June | 651.00 | 21.46 | 15.83 | 21.51 | 0.00 | 21.51 |
July | 614.33 | 21.35 | 49.83 | 21.49 | 0.00 | 21.49 |
August | 624.67 | 21.37 | 54.83 | 21.53 | 0.00 | 21.53 |
September | 640.17 | 21.34 | 32.33 | 21.43 | 0.00 | 21.43 |
October | 725.17 | 21.22 | 37.33 | 21.17 | 37.17 | 21.12 |
November | 717.17 | 20.82 | 396.83 | 20.73 | 395.50 | 20.68 |
December | 744.00 | 20.70 | 624.67 | 20.64 | 624.67 | 20.62 |
Annual Sum or Average | 8245.00 | 21.12 | 2610.83 | 21.04 | 2432.17 | 20.96 |
Minimum of Months | 614.33 | 20.60 | 15.83 | 20.58 | 0.00 | 20.57 |
Maximum of Months | 744.00 | 21.46 | 697.33 | 21.53 | 697.33 | 21.53 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.50 | 726.17 | 20.50 | 726.17 | 20.49 |
February | 672.00 | 20.68 | 499.17 | 20.61 | 499.17 | 20.59 |
March | 744.00 | 20.93 | 332.67 | 20.84 | 332.67 | 20.80 |
April | 709.67 | 21.26 | 65.67 | 21.23 | 63.17 | 21.20 |
May | 706.17 | 21.43 | 10.00 | 21.45 | 3.67 | 21.44 |
June | 678.50 | 21.51 | 7.00 | 21.52 | 0.00 | 21.52 |
July | 651.67 | 21.44 | 26.67 | 21.51 | 0.00 | 21.51 |
August | 664.00 | 21.45 | 26.67 | 21.52 | 0.00 | 21.52 |
September | 680.17 | 21.37 | 7.00 | 21.39 | 0.00 | 21.39 |
October | 743.67 | 21.07 | 83.50 | 20.99 | 83.50 | 20.92 |
November | 719.67 | 20.68 | 459.00 | 20.61 | 459.00 | 20.57 |
December | 744.00 | 20.55 | 703.83 | 20.53 | 703.83 | 20.53 |
Annual Sum or Average | 8457.50 | 21.06 | 2947.33 | 20.94 | 2871.17 | 20.86 |
Minimum of Months | 651.67 | 20.50 | 7.00 | 20.50 | 0.00 | 20.49 |
Maximum of Months | 744.00 | 21.51 | 726.17 | 21.52 | 726.17 | 21.52 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 739.50 | 20.92 | 444.50 | 20.82 | 444.50 | 20.78 |
February | 651.50 | 21.14 | 207.00 | 21.04 | 207.00 | 20.98 |
March | 718.50 | 21.32 | 44.00 | 21.29 | 40.00 | 21.26 |
April | 676.67 | 21.45 | 11.17 | 21.46 | 4.67 | 21.45 |
May | 681.50 | 21.45 | 13.17 | 21.48 | 0.67 | 21.48 |
June | 650.17 | 21.47 | 2.17 | 21.48 | 0.00 | 21.48 |
July | 629.33 | 21.37 | 25.17 | 21.45 | 0.00 | 21.45 |
August | 631.83 | 21.38 | 54.67 | 21.53 | 0.00 | 21.53 |
September | 633.17 | 21.37 | 53.33 | 21.52 | 0.00 | 21.52 |
October | 687.00 | 21.32 | 16.50 | 21.37 | 0.17 | 21.37 |
November | 705.00 | 21.08 | 178.00 | 21.00 | 174.00 | 20.94 |
December | 732.33 | 20.96 | 383.50 | 20.85 | 383.50 | 20.79 |
Annual Sum or Average | 8136.50 | 21.26 | 1433.17 | 21.22 | 1254.50 | 21.16 |
Minimum of Months | 629.33 | 20.92 | 2.17 | 20.82 | 0.00 | 20.78 |
Maximum of Months | 739.50 | 21.47 | 444.50 | 21.53 | 444.50 | 21.53 |
Report: ComfortReportSimple55Monthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.37 | 0.00 | 21.37 | 0.00 | 21.37 |
February | 672.00 | 21.41 | 0.00 | 21.41 | 0.00 | 21.41 |
March | 744.00 | 21.50 | 0.00 | 21.50 | 0.00 | 21.50 |
April | 719.83 | 21.58 | 0.00 | 21.58 | 0.00 | 21.58 |
May | 739.17 | 21.68 | 0.00 | 21.68 | 0.00 | 21.68 |
June | 698.00 | 21.73 | 0.00 | 21.73 | 0.00 | 21.73 |
July | 701.00 | 21.75 | 10.67 | 21.77 | 0.00 | 21.77 |
August | 689.33 | 21.71 | 17.17 | 21.75 | 0.00 | 21.75 |
September | 704.50 | 21.64 | 0.00 | 21.64 | 0.00 | 21.64 |
October | 744.00 | 21.55 | 0.00 | 21.55 | 0.00 | 21.55 |
November | 719.83 | 21.45 | 0.00 | 21.45 | 0.00 | 21.45 |
December | 744.00 | 21.37 | 0.00 | 21.37 | 0.00 | 21.37 |
Annual Sum or Average | 8619.67 | 21.56 | 27.83 | 21.57 | 0.00 | 21.57 |
Minimum of Months | 672.00 | 21.37 | 0.00 | 21.37 | 0.00 | 21.37 |
Maximum of Months | 744.00 | 21.75 | 17.17 | 21.77 | 0.00 | 21.77 |
Report: ComfortReportSimple55Monthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.42 | 0.00 | 21.42 | 0.00 | 21.42 |
February | 672.00 | 21.46 | 0.00 | 21.46 | 0.00 | 21.46 |
March | 740.83 | 21.56 | 0.00 | 21.56 | 0.00 | 21.56 |
April | 712.83 | 21.64 | 0.00 | 21.64 | 0.00 | 21.64 |
May | 715.83 | 21.73 | 0.00 | 21.73 | 0.00 | 21.73 |
June | 657.33 | 21.77 | 10.17 | 21.79 | 0.00 | 21.79 |
July | 644.33 | 21.78 | 28.67 | 21.84 | 0.00 | 21.84 |
August | 633.33 | 21.73 | 36.33 | 21.81 | 0.00 | 21.81 |
September | 678.83 | 21.68 | 10.00 | 21.70 | 0.00 | 21.70 |
October | 742.17 | 21.61 | 0.00 | 21.61 | 0.00 | 21.61 |
November | 716.00 | 21.51 | 0.00 | 21.51 | 0.00 | 21.51 |
December | 744.00 | 21.42 | 0.00 | 21.42 | 0.00 | 21.42 |
Annual Sum or Average | 8401.50 | 21.60 | 85.17 | 21.62 | 0.00 | 21.62 |
Minimum of Months | 633.33 | 21.42 | 0.00 | 21.42 | 0.00 | 21.42 |
Maximum of Months | 744.00 | 21.78 | 36.33 | 21.84 | 0.00 | 21.84 |
Report: ComfortReportSimple55Monthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 490.50 | 22.57 | 525.33 | 22.89 | 296.83 | 23.05 |
February | 485.00 | 22.73 | 480.33 | 23.02 | 315.50 | 23.17 |
March | 574.67 | 22.87 | 540.00 | 23.15 | 396.00 | 23.30 |
April | 592.00 | 23.04 | 533.83 | 23.28 | 431.33 | 23.42 |
May | 620.17 | 23.12 | 563.67 | 23.35 | 465.67 | 23.48 |
June | 607.17 | 23.24 | 554.67 | 23.43 | 475.00 | 23.55 |
July | 613.50 | 23.33 | 581.83 | 23.47 | 499.17 | 23.58 |
August | 596.00 | 23.42 | 591.00 | 23.51 | 507.00 | 23.61 |
September | 591.00 | 23.21 | 556.83 | 23.37 | 466.00 | 23.50 |
October | 594.17 | 22.97 | 554.17 | 23.21 | 430.17 | 23.35 |
November | 523.83 | 22.76 | 524.67 | 23.03 | 353.00 | 23.17 |
December | 498.83 | 22.61 | 529.50 | 22.92 | 309.50 | 23.08 |
Annual Sum or Average | 6786.83 | 23.01 | 6535.83 | 23.23 | 4945.17 | 23.37 |
Minimum of Months | 485.00 | 22.57 | 480.33 | 22.89 | 296.83 | 23.05 |
Maximum of Months | 620.17 | 23.42 | 591.00 | 23.51 | 507.00 | 23.61 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.00 | 241.33 | 21.00 | 241.33 | 21.00 |
February | 672.00 | 21.00 | 184.67 | 21.00 | 184.67 | 21.00 |
March | 744.00 | 21.00 | 41.50 | 21.00 | 41.50 | 21.00 |
April | 720.00 | 21.01 | 0.00 | 21.01 | 0.00 | 21.01 |
May | 744.00 | 21.02 | 0.00 | 21.02 | 0.00 | 21.02 |
June | 720.00 | 21.03 | 0.00 | 21.03 | 0.00 | 21.03 |
July | 744.00 | 21.06 | 0.00 | 21.06 | 0.00 | 21.06 |
August | 744.00 | 21.08 | 0.00 | 21.08 | 0.00 | 21.08 |
September | 720.00 | 21.05 | 0.00 | 21.05 | 0.00 | 21.05 |
October | 744.00 | 21.01 | 0.00 | 21.01 | 0.00 | 21.01 |
November | 720.00 | 21.00 | 26.33 | 21.00 | 26.33 | 21.00 |
December | 744.00 | 21.00 | 150.00 | 21.00 | 150.00 | 21.00 |
Annual Sum or Average | 8760.00 | 21.02 | 643.83 | 21.02 | 643.83 | 21.02 |
Minimum of Months | 672.00 | 21.00 | 0.00 | 21.00 | 0.00 | 21.00 |
Maximum of Months | 744.00 | 21.08 | 241.33 | 21.08 | 241.33 | 21.08 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT PEOPLE
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.06451 | 32.21193 | -0.4187 | 8.70933 |
February | 672.00000 | 21.04964 | 33.87905 | -0.4175 | 8.72293 |
March | 744.00000 | 21.03699 | 35.14177 | -0.4171 | 8.69840 |
April | 720.00000 | 21.02444 | 39.80972 | -0.3961 | 8.35906 |
May | 744.00000 | 21.02487 | 45.03355 | -1.5590 | 54.11260 |
June | 720.00000 | 21.03096 | 48.35804 | -1.5313 | 52.60853 |
July | 744.00000 | 21.03536 | 52.84642 | -1.4972 | 50.75698 |
August | 744.00000 | 21.05030 | 57.14114 | -1.4616 | 48.83391 |
September | 720.00000 | 21.07405 | 53.88450 | -1.4655 | 49.08008 |
October | 744.00000 | 21.10306 | 43.88025 | -0.3305 | 7.33538 |
November | 720.00000 | 21.12235 | 40.41612 | -0.3451 | 7.56782 |
December | 744.00000 | 21.08780 | 34.13281 | -0.3955 | 8.31657 |
Annual Sum or Average | 8760.00000 | 21.05872 | 43.10874 | -0.8556 | 26.19826 |
Minimum of Months | 672.00000 | 21.02444 | 32.21193 | -1.5590 | 7.33538 |
Maximum of Months | 744.00000 | 21.12235 | 57.14114 | -0.3305 | 54.11260 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_1_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.91050 | 31.49587 | -0.5435 | 11.44643 |
February | 672.00000 | 20.98018 | 33.04362 | -0.4628 | 10.00240 |
March | 744.00000 | 21.03301 | 34.21240 | -0.4026 | 8.80681 |
April | 720.00000 | 21.02702 | 38.87597 | -0.3342 | 7.78661 |
May | 744.00000 | 21.02099 | 44.12639 | -1.4409 | 47.96401 |
June | 720.00000 | 21.00463 | 47.53388 | -1.4018 | 45.76895 |
July | 744.00000 | 21.02319 | 51.98442 | -1.3272 | 42.02744 |
August | 744.00000 | 21.06572 | 56.19123 | -1.2794 | 39.86253 |
September | 720.00000 | 21.09397 | 52.91325 | -1.3303 | 42.78477 |
October | 744.00000 | 21.05359 | 43.09507 | -0.3170 | 7.57895 |
November | 720.00000 | 20.99292 | 39.73972 | -0.4353 | 9.34010 |
December | 744.00000 | 20.91485 | 33.50022 | -0.5222 | 11.03123 |
Annual Sum or Average | 8760.00000 | 21.01008 | 42.27365 | -0.8187 | 23.78279 |
Minimum of Months | 672.00000 | 20.91050 | 31.49587 | -1.4409 | 7.57895 |
Maximum of Months | 744.00000 | 21.09397 | 56.19123 | -0.3170 | 47.96401 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_2_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.00207 | 32.68546 | -0.4339 | 8.96875 |
February | 672.00000 | 21.00934 | 34.32551 | -0.4102 | 8.61105 |
March | 744.00000 | 21.02138 | 35.56079 | -0.3865 | 8.18477 |
April | 720.00000 | 21.03981 | 40.17153 | -0.3435 | 7.57428 |
May | 744.00000 | 21.06074 | 45.34797 | -1.4684 | 49.21733 |
June | 720.00000 | 21.07444 | 48.65410 | -1.4364 | 47.50097 |
July | 744.00000 | 21.10177 | 53.06577 | -1.3886 | 44.97499 |
August | 744.00000 | 21.11534 | 57.35733 | -1.3581 | 43.37064 |
September | 720.00000 | 21.07332 | 54.29885 | -1.4024 | 45.72510 |
October | 744.00000 | 21.03209 | 44.45369 | -0.3234 | 7.22528 |
November | 720.00000 | 21.00795 | 41.04521 | -0.3701 | 7.94184 |
December | 744.00000 | 21.00266 | 34.66304 | -0.4194 | 8.70174 |
Annual Sum or Average | 8760.00000 | 21.04533 | 43.51606 | -0.8142 | 24.09130 |
Minimum of Months | 672.00000 | 21.00207 | 32.68546 | -1.4684 | 7.22528 |
Maximum of Months | 744.00000 | 21.11534 | 57.35733 | -0.3234 | 49.21733 |
Report: OccupantComfortDataSummaryMonthly
For: LAUNDRY_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.43597 | 29.75734 | 0.25826 | 9.06058 |
February | 672.00000 | 21.43352 | 31.38466 | 0.27820 | 9.34365 |
March | 744.00000 | 21.43600 | 32.58839 | 0.30205 | 9.61907 |
April | 720.00000 | 21.41049 | 37.22241 | 0.33715 | 9.94516 |
May | 744.00000 | 21.40544 | 42.34392 | -0.5013 | 15.40886 |
June | 720.00000 | 21.39585 | 45.62606 | -0.4666 | 14.67523 |
July | 744.00000 | 21.37239 | 50.11068 | -0.4405 | 13.84055 |
August | 744.00000 | 21.39198 | 54.31942 | -0.4019 | 13.35873 |
September | 720.00000 | 21.40039 | 51.15532 | -0.4432 | 14.17687 |
October | 744.00000 | 21.42356 | 41.33895 | 0.35904 | 10.27446 |
November | 720.00000 | 21.43268 | 37.93693 | 0.32259 | 9.85169 |
December | 744.00000 | 21.43091 | 31.70907 | 0.27110 | 9.13929 |
Annual Sum or Average | 8760.00000 | 21.41398 | 40.50464 | -0.0122 | 11.56942 |
Minimum of Months | 672.00000 | 21.37239 | 29.75734 | -0.5013 | 9.06058 |
Maximum of Months | 744.00000 | 21.43600 | 54.31942 | 0.35904 | 15.40886 |
Report: OccupantComfortDataSummaryMonthly
For: CAFE_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.99978 | 33.74942 | -0.4191 | 8.82982 |
February | 672.00000 | 21.01653 | 35.37789 | -0.3519 | 7.96427 |
March | 744.00000 | 21.02753 | 36.61952 | -0.3037 | 7.26303 |
April | 720.00000 | 21.01673 | 41.28315 | -0.2416 | 6.57210 |
May | 744.00000 | 21.01177 | 46.52345 | -1.3226 | 41.74218 |
June | 720.00000 | 21.00393 | 49.90555 | -1.2830 | 39.58952 |
July | 744.00000 | 21.00996 | 54.37906 | -1.2187 | 36.50648 |
August | 744.00000 | 21.04017 | 58.62608 | -1.1715 | 34.39924 |
September | 720.00000 | 21.06107 | 55.37244 | -1.2200 | 37.07938 |
October | 744.00000 | 21.03675 | 45.49701 | -0.2240 | 6.41278 |
November | 720.00000 | 21.00979 | 42.09032 | -0.3292 | 7.57325 |
December | 744.00000 | 20.99688 | 35.74152 | -0.3999 | 8.55971 |
Annual Sum or Average | 8760.00000 | 21.01922 | 44.64478 | -0.7093 | 20.28093 |
Minimum of Months | 672.00000 | 20.99688 | 33.74942 | -1.3226 | 6.41278 |
Maximum of Months | 744.00000 | 21.06107 | 58.62608 | -0.2240 | 41.74218 |
Report: OccupantComfortDataSummaryMonthly
For: LOBBY_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.01038 | 33.97704 | -0.3950 | 8.30126 |
February | 672.00000 | 21.02048 | 35.60391 | -0.3651 | 7.89457 |
March | 744.00000 | 21.03702 | 36.84034 | -0.3380 | 7.45812 |
April | 720.00000 | 21.05583 | 41.44141 | -0.2933 | 6.91155 |
May | 744.00000 | 21.07875 | 46.60528 | -1.4016 | 45.64542 |
June | 720.00000 | 21.10594 | 49.87109 | -1.3635 | 43.63666 |
July | 744.00000 | 21.13103 | 54.27585 | -1.3157 | 41.16492 |
August | 744.00000 | 21.15541 | 58.52258 | -1.2789 | 39.28367 |
September | 720.00000 | 21.10274 | 55.50233 | -1.3288 | 41.87205 |
October | 744.00000 | 21.05362 | 45.69541 | -0.2719 | 6.59831 |
November | 720.00000 | 21.02074 | 42.31524 | -0.3275 | 7.34044 |
December | 744.00000 | 21.01058 | 35.95903 | -0.3797 | 8.04761 |
Annual Sum or Average | 8760.00000 | 21.06551 | 44.76425 | -0.7573 | 22.09684 |
Minimum of Months | 672.00000 | 21.01038 | 33.97704 | -1.4016 | 6.59831 |
Maximum of Months | 744.00000 | 21.15541 | 58.52258 | -0.2719 | 45.64542 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.69179 | 36.63501 | -0.6189 | 13.43948 |
February | 672.00000 | 20.97469 | 37.91018 | -0.5039 | 11.13081 |
March | 744.00000 | 21.21480 | 39.27731 | -0.3949 | 8.90521 |
April | 720.00000 | 21.45400 | 43.19478 | -0.2632 | 7.34987 |
May | 744.00000 | 21.57518 | 47.49260 | -1.2920 | 41.14695 |
June | 720.00000 | 21.62236 | 50.34921 | -1.2341 | 38.18145 |
July | 744.00000 | 21.67229 | 51.80490 | -1.1507 | 34.53485 |
August | 744.00000 | 21.65790 | 54.59498 | -1.1479 | 34.37641 |
September | 720.00000 | 21.55282 | 54.49750 | -1.2392 | 38.60933 |
October | 744.00000 | 21.32905 | 48.15850 | -0.2897 | 7.46319 |
November | 720.00000 | 20.92315 | 45.09340 | -0.4774 | 10.41597 |
December | 744.00000 | 20.78308 | 38.60296 | -0.5790 | 12.60787 |
Annual Sum or Average | 8760.00000 | 21.28906 | 45.66873 | -0.7676 | 21.57549 |
Minimum of Months | 672.00000 | 20.69179 | 36.63501 | -1.2920 | 7.34987 |
Maximum of Months | 744.00000 | 21.67229 | 54.59498 | -0.2632 | 41.14695 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.56514 | 36.88438 | -0.6630 | 14.69305 |
February | 672.00000 | 20.76346 | 38.30878 | -0.5773 | 12.63928 |
March | 744.00000 | 21.00942 | 39.67392 | -0.4671 | 9.90416 |
April | 720.00000 | 21.30521 | 43.60008 | -0.3197 | 7.75753 |
May | 744.00000 | 21.50280 | 47.75137 | -1.3379 | 43.14741 |
June | 720.00000 | 21.56881 | 50.55858 | -1.2683 | 39.59437 |
July | 744.00000 | 21.63717 | 52.15838 | -1.1839 | 35.79110 |
August | 744.00000 | 21.61185 | 55.37767 | -1.1903 | 36.01325 |
September | 720.00000 | 21.45828 | 55.64637 | -1.3071 | 41.48541 |
October | 744.00000 | 21.13252 | 48.69614 | -0.3632 | 8.09590 |
November | 720.00000 | 20.77745 | 45.51420 | -0.5270 | 11.35931 |
December | 744.00000 | 20.62064 | 38.93819 | -0.6339 | 13.85743 |
Annual Sum or Average | 8760.00000 | 21.16475 | 46.12631 | -0.8215 | 22.92156 |
Minimum of Months | 672.00000 | 20.56514 | 36.88438 | -1.3379 | 7.75753 |
Maximum of Months | 744.00000 | 21.63717 | 55.64637 | -0.3197 | 43.14741 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT19_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 0.00000 | ||||
Minimum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_4_MULT19_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.89890 | 34.31458 | -0.5205 | 10.90085 |
February | 672.00000 | 21.00878 | 35.83200 | -0.4730 | 10.02808 |
March | 744.00000 | 21.19259 | 37.28344 | -0.3968 | 8.39122 |
April | 720.00000 | 21.34139 | 41.48119 | -0.3166 | 7.31074 |
May | 744.00000 | 21.45111 | 45.79462 | -1.3959 | 45.52599 |
June | 720.00000 | 21.48982 | 48.27888 | -1.3491 | 43.10501 |
July | 744.00000 | 21.51988 | 50.86263 | -1.3119 | 41.27507 |
August | 744.00000 | 21.49990 | 53.59405 | -1.3067 | 40.99014 |
September | 720.00000 | 21.39839 | 52.81222 | -1.3764 | 44.45011 |
October | 744.00000 | 21.26404 | 46.16060 | -0.3175 | 7.17847 |
November | 720.00000 | 21.08314 | 42.59762 | -0.4050 | 8.64553 |
December | 744.00000 | 20.94123 | 36.39507 | -0.4962 | 10.30015 |
Annual Sum or Average | 8760.00000 | 21.25870 | 43.82178 | -0.8076 | 23.25355 |
Minimum of Months | 672.00000 | 20.89890 | 34.31458 | -1.3959 | 7.17847 |
Maximum of Months | 744.00000 | 21.51988 | 53.59405 | -0.3166 | 45.52599 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_5_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.67638 | 36.65833 | -0.6224 | 13.50816 |
February | 672.00000 | 20.98166 | 37.88756 | -0.5028 | 11.00238 |
March | 744.00000 | 21.26998 | 39.18547 | -0.3808 | 8.68207 |
April | 720.00000 | 21.53619 | 43.01515 | -0.2398 | 7.19285 |
May | 744.00000 | 21.59936 | 47.40873 | -1.2975 | 41.43131 |
June | 720.00000 | 21.67107 | 49.74078 | -1.2094 | 37.14821 |
July | 744.00000 | 21.69219 | 51.74367 | -1.1659 | 35.24379 |
August | 744.00000 | 21.68863 | 54.05609 | -1.1410 | 34.12771 |
September | 720.00000 | 21.55763 | 54.49742 | -1.2499 | 39.14962 |
October | 744.00000 | 21.36209 | 48.03755 | -0.2828 | 7.43725 |
November | 720.00000 | 20.91605 | 45.09770 | -0.4785 | 10.40674 |
December | 744.00000 | 20.76484 | 38.63780 | -0.5830 | 12.62813 |
Annual Sum or Average | 8760.00000 | 21.31116 | 45.53134 | -0.7646 | 21.56110 |
Minimum of Months | 672.00000 | 20.67638 | 36.65833 | -1.2975 | 7.19285 |
Maximum of Months | 744.00000 | 21.69219 | 54.49742 | -0.2398 | 41.43131 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_6_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.55663 | 36.89874 | -0.6657 | 14.79904 |
February | 672.00000 | 20.75506 | 38.31181 | -0.5794 | 12.60696 |
March | 744.00000 | 21.07350 | 39.54960 | -0.4514 | 9.51005 |
April | 720.00000 | 21.42593 | 43.28763 | -0.2888 | 7.43855 |
May | 744.00000 | 21.55314 | 47.57720 | -1.3366 | 43.09827 |
June | 720.00000 | 21.65268 | 49.84889 | -1.2336 | 38.11206 |
July | 744.00000 | 21.68036 | 52.10237 | -1.1923 | 36.24036 |
August | 744.00000 | 21.66753 | 54.70690 | -1.1763 | 35.46653 |
September | 720.00000 | 21.49167 | 55.54613 | -1.3106 | 41.73852 |
October | 744.00000 | 21.18102 | 48.54144 | -0.3532 | 7.95762 |
November | 720.00000 | 20.76873 | 45.54414 | -0.5282 | 11.39335 |
December | 744.00000 | 20.60148 | 38.97819 | -0.6381 | 13.97849 |
Annual Sum or Average | 8760.00000 | 21.20284 | 45.94115 | -0.8145 | 22.75625 |
Minimum of Months | 672.00000 | 20.55663 | 36.89874 | -1.3366 | 7.43855 |
Maximum of Months | 744.00000 | 21.68036 | 55.54613 | -0.2888 | 43.09827 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.59654 | 37.24290 | -0.6805 | 15.20784 |
February | 672.00000 | 20.88429 | 38.55075 | -0.5576 | 12.49673 |
March | 744.00000 | 21.14854 | 39.92043 | -0.4316 | 9.73884 |
April | 720.00000 | 21.43595 | 43.70244 | -0.2745 | 7.72654 |
May | 744.00000 | 21.58135 | 47.92877 | -1.2832 | 41.07591 |
June | 720.00000 | 21.63857 | 50.62445 | -1.2108 | 37.41635 |
July | 744.00000 | 21.68000 | 51.99720 | -1.1205 | 33.54067 |
August | 744.00000 | 21.66682 | 54.88492 | -1.1208 | 33.50589 |
September | 720.00000 | 21.55207 | 55.11864 | -1.2305 | 38.52527 |
October | 744.00000 | 21.27820 | 48.96968 | -0.3157 | 7.98582 |
November | 720.00000 | 20.82511 | 45.96573 | -0.5295 | 11.70049 |
December | 744.00000 | 20.69875 | 39.22967 | -0.6372 | 14.17718 |
Annual Sum or Average | 8760.00000 | 21.25059 | 46.21134 | -0.7842 | 21.98127 |
Minimum of Months | 672.00000 | 20.59654 | 37.24290 | -1.2832 | 7.72654 |
Maximum of Months | 744.00000 | 21.68000 | 55.11864 | -0.2745 | 41.07591 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.50402 | 37.43811 | -0.7190 | 16.40136 |
February | 672.00000 | 20.67817 | 38.96724 | -0.6319 | 14.15669 |
March | 744.00000 | 20.93438 | 40.34453 | -0.5083 | 10.88702 |
April | 720.00000 | 21.29372 | 44.11394 | -0.3319 | 8.14440 |
May | 744.00000 | 21.52785 | 48.15730 | -1.3253 | 42.83991 |
June | 720.00000 | 21.60958 | 50.77803 | -1.2390 | 38.52127 |
July | 744.00000 | 21.66546 | 52.39864 | -1.1477 | 34.50727 |
August | 744.00000 | 21.63974 | 55.60328 | -1.1590 | 34.89832 |
September | 720.00000 | 21.47995 | 56.26369 | -1.2951 | 41.19308 |
October | 744.00000 | 21.07540 | 49.55203 | -0.3938 | 8.73114 |
November | 720.00000 | 20.68371 | 46.40037 | -0.5794 | 12.73553 |
December | 744.00000 | 20.54758 | 39.55875 | -0.6910 | 15.51938 |
Annual Sum or Average | 8760.00000 | 21.13897 | 46.66410 | -0.8365 | 23.26447 |
Minimum of Months | 672.00000 | 20.50402 | 37.43811 | -1.3253 | 8.14440 |
Maximum of Months | 744.00000 | 21.66546 | 56.26369 | -0.3319 | 42.83991 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT9_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.93679 | 36.91621 | -0.5398 | 11.85621 |
February | 672.00000 | 21.20884 | 38.17521 | -0.4155 | 9.88608 |
March | 744.00000 | 21.38603 | 39.51156 | -0.3255 | 8.28289 |
April | 720.00000 | 21.55960 | 43.27481 | -0.2238 | 7.25363 |
May | 744.00000 | 21.60998 | 47.54939 | -1.2873 | 41.18000 |
June | 720.00000 | 21.65011 | 50.13702 | -1.2323 | 38.35559 |
July | 744.00000 | 21.67528 | 51.68056 | -1.1730 | 35.79169 |
August | 744.00000 | 21.67114 | 53.85517 | -1.1483 | 34.68970 |
September | 720.00000 | 21.60381 | 53.48134 | -1.2073 | 37.55545 |
October | 744.00000 | 21.47703 | 47.81734 | -0.2232 | 7.14832 |
November | 720.00000 | 21.13177 | 44.83210 | -0.4058 | 9.36148 |
December | 744.00000 | 21.00048 | 38.83658 | -0.5020 | 11.34997 |
Annual Sum or Average | 8760.00000 | 21.41004 | 45.53927 | -0.7257 | 21.12837 |
Minimum of Months | 672.00000 | 20.93679 | 36.91621 | -1.2873 | 7.14832 |
Maximum of Months | 744.00000 | 21.67528 | 53.85517 | -0.2232 | 41.18000 |
Report: OccupantComfortDataSummaryMonthly
For: BANQUET_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.36536 | 34.91965 | -0.2611 | 6.73467 |
February | 672.00000 | 21.40704 | 36.42222 | -0.2279 | 6.51092 |
March | 744.00000 | 21.50057 | 37.53082 | -0.1749 | 5.99556 |
April | 720.00000 | 21.58009 | 41.90554 | -0.1065 | 5.59135 |
May | 744.00000 | 21.68510 | 46.73572 | -1.0980 | 30.89319 |
June | 720.00000 | 21.77417 | 49.71614 | -1.0276 | 27.86460 |
July | 744.00000 | 21.82358 | 53.89749 | -0.9708 | 25.48572 |
August | 744.00000 | 21.81009 | 58.08168 | -0.9544 | 24.86128 |
September | 720.00000 | 21.67288 | 55.40466 | -1.0518 | 28.89232 |
October | 744.00000 | 21.54508 | 46.07765 | -0.1025 | 5.54859 |
November | 720.00000 | 21.45505 | 42.91289 | -0.1688 | 5.99938 |
December | 744.00000 | 21.37063 | 36.87678 | -0.2454 | 6.50890 |
Annual Sum or Average | 8760.00000 | 21.58350 | 45.08414 | -0.5343 | 15.12219 |
Minimum of Months | 672.00000 | 21.36536 | 34.91965 | -1.0980 | 5.54859 |
Maximum of Months | 744.00000 | 21.82358 | 58.08168 | -0.1025 | 30.89319 |
Report: OccupantComfortDataSummaryMonthly
For: DINING_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.41644 | 34.59778 | -0.2157 | 6.32271 |
February | 672.00000 | 21.46221 | 36.08620 | -0.1822 | 6.16079 |
March | 744.00000 | 21.56431 | 37.17748 | -0.1275 | 5.73008 |
April | 720.00000 | 21.65575 | 41.51127 | -0.0567 | 5.44797 |
May | 744.00000 | 21.77445 | 46.28543 | -1.0227 | 27.63553 |
June | 720.00000 | 21.87203 | 49.22722 | -0.9492 | 24.66563 |
July | 744.00000 | 21.92677 | 53.36777 | -0.8911 | 22.39518 |
August | 744.00000 | 21.90243 | 57.55963 | -0.8784 | 21.95804 |
September | 720.00000 | 21.75149 | 54.94009 | -0.9805 | 25.91894 |
October | 744.00000 | 21.61178 | 45.68648 | -0.0548 | 5.42276 |
November | 720.00000 | 21.51644 | 42.54378 | -0.1216 | 5.74950 |
December | 744.00000 | 21.42319 | 36.54785 | -0.1997 | 6.12047 |
Annual Sum or Average | 8760.00000 | 21.65757 | 44.67118 | -0.4751 | 13.66874 |
Minimum of Months | 672.00000 | 21.41644 | 34.59778 | -1.0227 | 5.42276 |
Maximum of Months | 744.00000 | 21.92677 | 57.55963 | -0.0548 | 27.63553 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.58293 | 34.14490 | 0.65674 | 18.64241 |
February | 672.00000 | 22.68603 | 35.34295 | 0.71301 | 20.71657 |
March | 744.00000 | 22.79644 | 36.30845 | 0.77881 | 22.87483 |
April | 720.00000 | 22.91532 | 40.10485 | 0.86967 | 26.45099 |
May | 744.00000 | 22.97616 | 44.49843 | 0.27750 | 18.24137 |
June | 720.00000 | 23.04257 | 47.29914 | 0.35655 | 19.19678 |
July | 744.00000 | 23.05815 | 51.08189 | 0.40611 | 20.29629 |
August | 744.00000 | 23.06834 | 54.84930 | 0.43643 | 20.49892 |
September | 720.00000 | 22.98118 | 52.33266 | 0.33735 | 18.67122 |
October | 744.00000 | 22.84815 | 43.98732 | 0.85659 | 25.48055 |
November | 720.00000 | 22.69252 | 41.25738 | 0.75901 | 21.93796 |
December | 744.00000 | 22.60583 | 35.87023 | 0.67820 | 19.27705 |
Annual Sum or Average | 8760.00000 | 22.85527 | 43.12981 | 0.59299 | 21.02035 |
Minimum of Months | 672.00000 | 22.58293 | 34.14490 | 0.27750 | 18.24137 |
Maximum of Months | 744.00000 | 23.06834 | 54.84930 | 0.86967 | 26.45099 |
Report: OccupantComfortDataSummaryMonthly
For: STORAGE_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.00009 | 31.07202 | -0.5018 | 10.30237 |
February | 672.00000 | 21.00008 | 32.73332 | -0.4840 | 9.98982 |
March | 744.00000 | 21.00012 | 33.99382 | -0.4643 | 9.55914 |
April | 720.00000 | 21.00013 | 38.66347 | -0.4272 | 8.89499 |
May | 744.00000 | 21.00016 | 43.92675 | -1.5876 | 55.66744 |
June | 720.00000 | 21.00056 | 47.28437 | -1.5557 | 53.93150 |
July | 744.00000 | 21.00224 | 51.83334 | -1.5188 | 51.92649 |
August | 744.00000 | 21.00576 | 56.19322 | -1.4908 | 50.40506 |
September | 720.00000 | 21.00021 | 52.98708 | -1.5286 | 52.48805 |
October | 744.00000 | 21.00014 | 42.96803 | -0.4033 | 8.41892 |
November | 720.00000 | 21.00013 | 39.48027 | -0.4386 | 9.09117 |
December | 744.00000 | 21.00007 | 33.04096 | -0.4877 | 9.99838 |
Annual Sum or Average | 8760.00000 | 21.00082 | 42.06263 | -0.9100 | 27.66164 |
Minimum of Months | 672.00000 | 21.00007 | 31.07202 | -1.5876 | 8.41892 |
Maximum of Months | 744.00000 | 21.00576 | 56.19322 | -0.4033 | 55.66744 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.00040 | 33.24375 | -0.4941 | 10.13095 |
February | 672.00000 | 21.00067 | 34.88156 | -0.4706 | 9.70797 |
March | 744.00000 | 21.00219 | 36.14232 | -0.4491 | 9.25842 |
April | 720.00000 | 21.01805 | 40.74568 | -0.4080 | 8.56607 |
May | 744.00000 | 21.03640 | 45.94291 | -1.5643 | 54.40223 |
June | 720.00000 | 21.05915 | 49.22124 | -1.5298 | 52.52708 |
July | 744.00000 | 21.14469 | 53.46571 | -1.4693 | 49.26199 |
August | 744.00000 | 21.22097 | 57.56213 | -1.4183 | 46.53928 |
September | 720.00000 | 21.09933 | 54.75234 | -1.4864 | 50.22040 |
October | 744.00000 | 21.01278 | 45.05158 | -0.3885 | 8.17120 |
November | 720.00000 | 21.00105 | 41.61860 | -0.4317 | 8.96209 |
December | 744.00000 | 20.99948 | 35.20975 | -0.4803 | 9.84467 |
Annual Sum or Average | 8760.00000 | 21.05006 | 44.03283 | -0.8850 | 26.56428 |
Minimum of Months | 672.00000 | 20.99948 | 33.24375 | -1.5643 | 8.17120 |
Maximum of Months | 744.00000 | 21.22097 | 57.56213 | -0.3885 | 54.40223 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.99953 | 31.66216 | -0.5148 | 10.59096 |
February | 672.00000 | 20.99926 | 33.32038 | -0.4836 | 10.01638 |
March | 744.00000 | 21.00263 | 34.56232 | -0.4493 | 9.28455 |
April | 720.00000 | 21.01194 | 39.19580 | -0.3968 | 8.41796 |
May | 744.00000 | 21.02395 | 44.40419 | -1.5305 | 52.58242 |
June | 720.00000 | 21.02909 | 47.74503 | -1.4882 | 50.28982 |
July | 744.00000 | 21.06311 | 52.14247 | -1.4336 | 47.38725 |
August | 744.00000 | 21.07974 | 56.43375 | -1.4041 | 45.82815 |
September | 720.00000 | 21.04503 | 53.35399 | -1.4644 | 49.06423 |
October | 744.00000 | 21.00517 | 43.49635 | -0.3838 | 8.11612 |
November | 720.00000 | 21.00168 | 40.03574 | -0.4396 | 9.14774 |
December | 744.00000 | 20.99981 | 33.63593 | -0.4995 | 10.25436 |
Annual Sum or Average | 8760.00000 | 21.02193 | 42.54614 | -0.8764 | 26.00934 |
Minimum of Months | 672.00000 | 20.99926 | 31.66216 | -1.5305 | 8.11612 |
Maximum of Months | 744.00000 | 21.07974 | 56.43375 | -0.3838 | 52.58242 |
Report: OccupantComfortDataSummaryMonthly
For: MECH_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.00008 | 30.81496 | -0.4778 | 9.80894 |
February | 672.00000 | 21.00018 | 32.47768 | -0.4613 | 9.53748 |
March | 744.00000 | 21.00029 | 33.73188 | -0.4430 | 9.15712 |
April | 720.00000 | 21.00328 | 38.39375 | -0.4062 | 8.53370 |
May | 744.00000 | 21.01260 | 43.62759 | -1.5553 | 53.91344 |
June | 720.00000 | 21.02464 | 46.95076 | -1.5209 | 52.04209 |
July | 744.00000 | 21.03666 | 51.45526 | -1.4817 | 49.92411 |
August | 744.00000 | 21.04405 | 55.79264 | -1.4526 | 48.35067 |
September | 720.00000 | 21.01621 | 52.66588 | -1.4955 | 50.69349 |
October | 744.00000 | 21.00215 | 42.69861 | -0.3823 | 8.07558 |
November | 720.00000 | 21.00014 | 39.21785 | -0.4164 | 8.69188 |
December | 744.00000 | 21.00008 | 32.78468 | -0.4641 | 9.52863 |
Annual Sum or Average | 8760.00000 | 21.01180 | 41.76520 | -0.8823 | 26.62301 |
Minimum of Months | 672.00000 | 21.00008 | 30.81496 | -1.5553 | 8.07558 |
Maximum of Months | 744.00000 | 21.04405 | 55.79264 | -0.3823 | 53.91344 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.153879E+10 | 12382.53 | 11-JAN-19:03 | 136.79 | 0.453093E+10 | 0.00 | 0.606973E+10 | 0.54 | 2.95 | 03-JAN-06:05 | 0.00 | 0.00 |
February | 0.744644E+10 | 85297.66 | 27-FEB-16:01 | 275.98 | 0.220652E+11 | 0.00 | 0.295117E+11 | 1.21 | 3.64 | 27-FEB-16:01 | 0.00 | 0.00 |
March | 0.173945E+11 | 101855.46 | 18-MAR-15:02 | 487.79 | 0.514468E+11 | 0.00 | 0.688413E+11 | 1.93 | 3.87 | 18-MAR-18:01 | 0.00 | 0.00 |
April | 0.438364E+11 | 155200.65 | 27-APR-15:03 | 635.58 | 0.135691E+12 | 0.00 | 0.179527E+12 | 2.62 | 3.87 | 02-APR-18:01 | 0.00 | 0.00 |
May | 0.718651E+11 | 138701.79 | 05-MAY-18:03 | 722.24 | 0.227591E+12 | 0.00 | 0.299456E+12 | 2.91 | 4.07 | 06-MAY-18:01 | 0.00 | 0.00 |
June | 0.104694E+12 | 152038.28 | 28-JUN-18:03 | 717.50 | 0.333505E+12 | 0.00 | 0.438199E+12 | 3.02 | 4.05 | 02-JUN-18:01 | 0.00 | 0.00 |
July | 0.153796E+12 | 186157.18 | 24-JUL-15:03 | 744.00 | 0.506634E+12 | 0.00 | 0.660430E+12 | 3.12 | 4.13 | 16-JUL-18:03 | 0.00 | 0.00 |
August | 0.180509E+12 | 214844.98 | 10-AUG-18:03 | 744.00 | 0.595753E+12 | 0.00 | 0.776262E+12 | 3.15 | 4.16 | 30-AUG-08:62 | 0.00 | 0.00 |
September | 0.941065E+11 | 150199.27 | 14-SEP-15:02 | 713.25 | 0.305120E+12 | 0.00 | 0.399226E+12 | 3.01 | 4.09 | 23-SEP-18:02 | 0.00 | 0.00 |
October | 0.363726E+11 | 120070.60 | 04-OCT-15:02 | 646.85 | 0.107908E+12 | 0.00 | 0.144281E+12 | 2.56 | 3.88 | 04-OCT-18:01 | 0.00 | 0.00 |
November | 0.990403E+10 | 112842.31 | 04-NOV-15:02 | 339.03 | 0.298883E+11 | 0.00 | 0.397924E+11 | 1.39 | 3.87 | 04-NOV-15:02 | 0.00 | 0.00 |
December | 0.267117E+10 | 19254.43 | 05-DEC-12:30 | 176.15 | 0.787329E+10 | 0.00 | 0.105445E+11 | 0.70 | 2.95 | 02-DEC-20:30 | 0.00 | 0.00 |
Annual Sum or Average | 0.724135E+12 | 6339.16 | 0.232801E+13 | 0.00 | 0.305214E+13 | 2.18 | 0.00 | 0.00 | ||||
Minimum of Months | 0.153879E+10 | 12382.53 | 136.79 | 0.453093E+10 | 0.00 | 0.606973E+10 | 0.54 | 2.95 | 0.00 | 0.00 | ||
Maximum of Months | 0.180509E+12 | 214844.98 | 744.00 | 0.595753E+12 | 0.00 | 0.776262E+12 | 3.15 | 4.16 | 0.00 | 0.00 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.203385E+12 | 0.00 | 744.00 | 179625.81 | 07-JAN-09:02 | 0.00 | 37.30 | 60.00 | 0.81 | 0.00 | 0.17 | 0.40 | 07-JAN-09:02 |
February | 0.155289E+12 | 0.00 | 672.00 | 176905.30 | 19-FEB-07:10 | 0.00 | 36.02 | 60.00 | 0.66 | 0.00 | 0.14 | 0.39 | 19-FEB-07:10 |
March | 0.132943E+12 | 0.00 | 744.00 | 135273.25 | 05-MAR-16:02 | 0.00 | 34.83 | 60.00 | 0.49 | 0.00 | 0.11 | 0.30 | 05-MAR-16:02 |
April | 0.103387E+12 | 0.00 | 720.00 | 113328.25 | 18-APR-08:62 | 0.00 | 33.23 | 60.00 | 0.37 | 0.00 | 0.09 | 0.25 | 18-APR-08:62 |
May | 0.878913E+11 | 0.00 | 744.00 | 98794.85 | 18-MAY-08:62 | 0.00 | 32.22 | 60.00 | 0.29 | 0.00 | 0.07 | 0.22 | 18-MAY-08:62 |
June | 0.683007E+11 | 0.00 | 720.00 | 92990.85 | 13-JUN-10:40 | 0.00 | 31.13 | 60.00 | 0.23 | 0.00 | 0.06 | 0.21 | 13-JUN-10:40 |
July | 0.578525E+11 | 0.00 | 744.00 | 85028.31 | 12-JUL-10:40 | 0.00 | 30.67 | 60.00 | 0.19 | 0.00 | 0.05 | 0.19 | 12-JUL-10:40 |
August | 0.549559E+11 | 0.00 | 744.00 | 83049.82 | 01-AUG-10:40 | 0.00 | 30.72 | 60.00 | 0.18 | 0.00 | 0.05 | 0.18 | 01-AUG-10:40 |
September | 0.653651E+11 | 0.00 | 720.00 | 90880.64 | 18-SEP-10:40 | 0.00 | 30.84 | 60.00 | 0.22 | 0.00 | 0.06 | 0.20 | 18-SEP-10:40 |
October | 0.101085E+12 | 0.00 | 744.00 | 101402.09 | 30-OCT-08:03 | 0.00 | 32.88 | 60.00 | 0.35 | 0.00 | 0.08 | 0.23 | 30-OCT-08:03 |
November | 0.144451E+12 | 0.00 | 720.00 | 141485.34 | 26-NOV-16:03 | 0.00 | 35.81 | 60.00 | 0.57 | 0.00 | 0.12 | 0.31 | 26-NOV-16:03 |
December | 0.188669E+12 | 0.00 | 744.00 | 178456.61 | 26-DEC-09:06 | 0.00 | 37.19 | 60.00 | 0.75 | 0.00 | 0.16 | 0.40 | 26-DEC-09:06 |
Annual Sum or Average | 0.136357E+13 | 0.00 | 8760.00 | 0.00 | 33.56 | 60.00 | 0.42 | 0.00 | 0.10 | ||||
Minimum of Months | 0.549559E+11 | 0.00 | 672.00 | 83049.82 | 0.00 | 30.67 | 60.00 | 0.18 | 0.00 | 0.05 | 0.18 | ||
Maximum of Months | 0.203385E+12 | 0.00 | 744.00 | 179625.81 | 0.00 | 37.30 | 60.00 | 0.81 | 0.00 | 0.17 | 0.40 |
Report: DXReportMonthly
For: VAV WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.149079E+09 | 0.00 | 2.97 | 0.149079E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18069.79 | 11-JAN-14:00 | 18069.79 | 11-JAN-14:00 | 0.00 | 0.00 | 0.00 |
February | 0.463944E+10 | 0.00 | 30.65 | 0.463944E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 172102.26 | 27-FEB-15:00 | 172102.26 | 27-FEB-15:00 | 0.00 | 0.00 | 0.00 |
March | 0.100727E+11 | 0.00 | 42.89 | 0.100727E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 206927.54 | 18-MAR-16:00 | 206927.54 | 18-MAR-16:00 | 0.00 | 0.00 | 0.00 |
April | 0.568250E+11 | 0.00 | 153.69 | 0.568250E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 301180.27 | 27-APR-18:10 | 301180.27 | 27-APR-18:10 | 0.00 | 0.00 | 0.00 |
May | 0.113180E+12 | 0.00 | 301.21 | 0.110831E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 345747.00 | 06-MAY-10:40 | 273848.55 | 04-MAY-18:10 | 0.00 | 0.00 | 0.00 |
June | 0.194846E+12 | 0.00 | 466.31 | 0.193848E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 318742.20 | 28-JUN-18:10 | 304983.94 | 28-JUN-18:10 | 0.00 | 0.00 | 0.00 |
July | 0.317725E+12 | 0.00 | 628.56 | 0.302034E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 424245.15 | 31-JUL-10:35 | 339915.23 | 24-JUL-18:10 | 0.00 | 0.00 | 0.00 |
August | 0.389455E+12 | 0.00 | 661.50 | 0.362819E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 438238.59 | 29-AUG-10:35 | 356442.60 | 10-AUG-18:10 | 0.00 | 0.00 | 0.00 |
September | 0.167291E+12 | 0.00 | 432.01 | 0.157644E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 386279.48 | 14-SEP-10:50 | 278939.53 | 14-SEP-17:00 | 0.00 | 0.00 | 0.00 |
October | 0.373890E+11 | 0.00 | 158.61 | 0.371777E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 231342.92 | 04-OCT-15:30 | 231342.92 | 04-OCT-15:30 | 0.00 | 0.00 | 0.00 |
November | 0.851776E+10 | 0.00 | 39.64 | 0.825098E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 219123.82 | 04-NOV-16:00 | 205810.52 | 04-NOV-15:03 | 0.00 | 0.00 | 0.00 |
December | 793.93 | 0.00 | 0.31 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.74 | 05-DEC-19:05 | 0.74 | 05-DEC-19:05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.130009E+13 | 0.00 | 2918.33 | 0.124429E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 793.93 | 0.00 | 0.31 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.74 | 0.74 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.389455E+12 | 0.00 | 661.50 | 0.362819E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 438238.59 | 356442.60 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: FLR_3_DOAS COOLING COIL
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 |
February | 0.332454E+09 | 0.00 | 10.50 | 0.332454E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18783.03 | 27-FEB-15:00 | 18783.03 | 27-FEB-15:00 | 0.00 | 0.00 | 0.00 |
March | 0.656261E+09 | 0.00 | 31.17 | 0.656261E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20929.09 | 18-MAR-16:00 | 20929.09 | 18-MAR-16:00 | 0.00 | 0.00 | 0.00 |
April | 0.509175E+10 | 0.00 | 108.33 | 0.509043E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38901.17 | 27-APR-15:00 | 37978.19 | 27-APR-15:00 | 0.00 | 0.00 | 0.00 |
May | 0.995405E+10 | 0.00 | 217.50 | 0.940109E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40101.20 | 06-MAY-13:00 | 32567.56 | 05-MAY-16:00 | 0.00 | 0.00 | 0.00 |
June | 0.171572E+11 | 0.00 | 379.00 | 0.171322E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 36703.11 | 28-JUN-17:00 | 36703.11 | 28-JUN-17:00 | 0.00 | 0.00 | 0.00 |
July | 0.325768E+11 | 0.00 | 540.17 | 0.295800E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 48686.52 | 31-JUL-16:00 | 45203.20 | 24-JUL-15:00 | 0.00 | 0.00 | 0.00 |
August | 0.432885E+11 | 0.00 | 594.67 | 0.381817E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 52757.23 | 29-AUG-13:00 | 47609.99 | 10-AUG-17:01 | 0.00 | 0.00 | 0.00 |
September | 0.149007E+11 | 0.00 | 332.00 | 0.134871E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 42472.65 | 23-SEP-14:00 | 32581.29 | 22-SEP-16:00 | 0.00 | 0.00 | 0.00 |
October | 0.254401E+10 | 0.00 | 106.17 | 0.253777E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24147.80 | 04-OCT-15:00 | 24147.80 | 04-OCT-15:00 | 0.00 | 0.00 | 0.00 |
November | 0.658445E+09 | 0.00 | 21.50 | 0.579603E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 28029.87 | 04-NOV-13:50 | 22855.29 | 04-NOV-15:00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.127160E+12 | 0.00 | 2341.00 | 0.116979E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.432885E+11 | 0.00 | 594.67 | 0.381817E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 52757.23 | 47609.99 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 7995779.41 | 0.00 | 1.57 | 7213503.43 | 0.00 | 0.00 | 0.00 | 0.00 | 10598.30 | 20-JAN-16:02 | 10598.30 | 20-JAN-16:02 | 0.00 | 0.00 | 0.00 |
February | 0.257225E+09 | 0.00 | 60.56 | 0.169827E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18054.12 | 06-FEB-16:01 | 18054.12 | 06-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.992121E+09 | 0.00 | 160.56 | 0.853128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18062.86 | 17-MAR-15:02 | 18062.86 | 17-MAR-15:02 | 0.00 | 0.00 | 0.00 |
April | 0.265297E+10 | 0.00 | 345.81 | 0.188160E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18696.57 | 30-APR-08:62 | 18063.59 | 02-APR-18:01 | 0.00 | 0.00 | 0.00 |
May | 0.454257E+10 | 0.00 | 500.70 | 0.286637E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18315.48 | 05-MAY-18:02 | 18063.19 | 14-MAY-15:02 | 0.00 | 0.00 | 0.00 |
June | 0.518647E+10 | 0.00 | 575.51 | 0.296430E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19780.01 | 12-JUN-15:01 | 18062.67 | 01-JUN-18:02 | 0.00 | 0.00 | 0.00 |
July | 0.815897E+10 | 0.00 | 668.84 | 0.491990E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19713.86 | 16-JUL-15:01 | 17647.66 | 28-JUL-15:02 | 0.00 | 0.00 | 0.00 |
August | 0.795174E+10 | 0.00 | 651.26 | 0.470166E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19419.48 | 26-AUG-08:62 | 17500.60 | 29-AUG-18:02 | 0.00 | 0.00 | 0.00 |
September | 0.527319E+10 | 0.00 | 544.42 | 0.293080E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19238.24 | 23-SEP-08:61 | 17597.98 | 03-SEP-15:02 | 0.00 | 0.00 | 0.00 |
October | 0.169402E+10 | 0.00 | 279.07 | 0.989663E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19128.88 | 01-OCT-15:02 | 18063.16 | 29-OCT-15:02 | 0.00 | 0.00 | 0.00 |
November | 0.218572E+09 | 0.00 | 51.80 | 97952419.50 | 0.00 | 0.00 | 0.00 | 0.00 | 18223.42 | 05-NOV-15:01 | 17846.22 | 11-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 29381548.42 | 0.00 | 12.07 | 27704213.62 | 0.00 | 0.00 | 0.00 | 0.00 | 17544.64 | 05-DEC-16:02 | 17544.64 | 05-DEC-16:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.369652E+11 | 0.00 | 3852.16 | 0.224101E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 7995779.41 | 0.00 | 1.57 | 7213503.43 | 0.00 | 0.00 | 0.00 | 0.00 | 10598.30 | 10598.30 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.815897E+10 | 0.00 | 668.84 | 0.491990E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19780.01 | 18063.59 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 1234250.36 | 0.00 | 0.41 | 829518.82 | 0.00 | 0.00 | 0.00 | 0.00 | 1899.11 | 11-JAN-19:05 | 1792.70 | 29-JAN-19:05 | 0.00 | 0.00 | 0.00 |
February | 72187748.34 | 0.00 | 25.76 | 36124874.55 | 0.00 | 0.00 | 0.00 | 0.00 | 13393.94 | 06-FEB-16:01 | 13393.94 | 06-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.414196E+09 | 0.00 | 90.75 | 0.364389E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16358.46 | 02-MAR-16:02 | 16358.46 | 02-MAR-16:02 | 0.00 | 0.00 | 0.00 |
April | 0.175539E+10 | 0.00 | 260.65 | 0.124472E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16903.51 | 30-APR-08:62 | 16363.68 | 02-APR-15:01 | 0.00 | 0.00 | 0.00 |
May | 0.367400E+10 | 0.00 | 446.86 | 0.235060E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16645.45 | 05-MAY-18:02 | 16361.25 | 14-MAY-15:02 | 0.00 | 0.00 | 0.00 |
June | 0.452053E+10 | 0.00 | 526.39 | 0.266188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17855.63 | 12-JUN-15:01 | 16363.00 | 01-JUN-15:01 | 0.00 | 0.00 | 0.00 |
July | 0.714134E+10 | 0.00 | 624.86 | 0.440867E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17804.19 | 16-JUL-15:01 | 15981.23 | 26-JUL-15:02 | 0.00 | 0.00 | 0.00 |
August | 0.654420E+10 | 0.00 | 604.80 | 0.380323E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17615.22 | 26-AUG-08:62 | 15869.07 | 30-AUG-15:02 | 0.00 | 0.00 | 0.00 |
September | 0.356622E+10 | 0.00 | 471.48 | 0.187636E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17823.02 | 24-SEP-15:01 | 15729.61 | 11-SEP-18:02 | 0.00 | 0.00 | 0.00 |
October | 0.758790E+09 | 0.00 | 163.73 | 0.437479E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17621.43 | 01-OCT-15:02 | 16358.56 | 11-OCT-15:02 | 0.00 | 0.00 | 0.00 |
November | 83486680.11 | 0.00 | 25.72 | 32058970.49 | 0.00 | 0.00 | 0.00 | 0.00 | 16844.07 | 04-NOV-15:02 | 15241.55 | 04-NOV-15:02 | 0.00 | 0.00 | 0.00 |
December | 2055805.48 | 0.00 | 0.52 | 1475950.67 | 0.00 | 0.00 | 0.00 | 0.00 | 2279.93 | 28-DEC-19:05 | 1940.55 | 01-DEC-16:03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.285336E+11 | 0.00 | 3241.92 | 0.172178E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 1234250.36 | 0.00 | 0.41 | 829518.82 | 0.00 | 0.00 | 0.00 | 0.00 | 1899.11 | 1792.70 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.714134E+10 | 0.00 | 624.86 | 0.440867E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17855.63 | 16363.68 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 13122006.87 | 0.00 | 1.33 | 13122006.87 | 0.00 | 0.00 | 0.00 | 0.00 | 3918.32 | 08-JAN-14:50 | 3918.32 | 08-JAN-14:50 | 0.00 | 0.00 | 0.00 |
February | 0.461951E+10 | 0.00 | 85.83 | 0.414785E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41405.66 | 08-FEB-14:30 | 41405.66 | 08-FEB-14:30 | 0.00 | 0.00 | 0.00 |
March | 0.129596E+11 | 0.00 | 225.31 | 0.127892E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 55439.84 | 02-MAR-13:00 | 55439.84 | 02-MAR-13:00 | 0.00 | 0.00 | 0.00 |
April | 0.215672E+11 | 0.00 | 424.15 | 0.171832E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 50696.10 | 27-APR-13:30 | 46885.49 | 02-APR-13:30 | 0.00 | 0.00 | 0.00 |
May | 0.265287E+11 | 0.00 | 503.05 | 0.177316E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 50509.58 | 04-MAY-13:10 | 43007.60 | 04-MAY-13:20 | 0.00 | 0.00 | 0.00 |
June | 0.277870E+11 | 0.00 | 553.58 | 0.134572E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 36977.71 | 28-JUN-13:00 | 32228.19 | 09-JUN-12:40 | 0.00 | 0.00 | 0.00 |
July | 0.387622E+11 | 0.00 | 634.83 | 0.194244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 49029.23 | 31-JUL-13:10 | 39224.72 | 31-JUL-13:20 | 0.00 | 0.00 | 0.00 |
August | 0.442249E+11 | 0.00 | 649.99 | 0.238116E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 64574.12 | 24-AUG-14:40 | 54826.90 | 23-AUG-13:20 | 0.00 | 0.00 | 0.00 |
September | 0.397958E+11 | 0.00 | 580.19 | 0.223528E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 65125.25 | 23-SEP-14:40 | 54669.99 | 09-SEP-13:50 | 0.00 | 0.00 | 0.00 |
October | 0.243317E+11 | 0.00 | 392.18 | 0.184958E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 65959.58 | 04-OCT-12:30 | 65959.58 | 04-OCT-12:30 | 0.00 | 0.00 | 0.00 |
November | 0.392785E+10 | 0.00 | 78.72 | 0.244784E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 56349.42 | 04-NOV-13:30 | 49959.06 | 04-NOV-13:30 | 0.00 | 0.00 | 0.00 |
December | 0.219222E+10 | 0.00 | 40.31 | 0.218552E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42121.65 | 05-DEC-12:30 | 42121.65 | 05-DEC-12:30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.246710E+12 | 0.00 | 4169.47 | 0.154040E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 13122006.87 | 0.00 | 1.33 | 13122006.87 | 0.00 | 0.00 | 0.00 | 0.00 | 3918.32 | 3918.32 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.442249E+11 | 0.00 | 649.99 | 0.238116E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 65959.58 | 65959.58 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.185637E+10 | 0.00 | 91.70 | 0.119957E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 71396.72 | 28-JAN-09:02 | 71396.72 | 28-JAN-09:02 | 0.00 | 0.00 | 0.00 |
February | 0.525760E+10 | 0.00 | 158.82 | 0.283402E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 81242.00 | 25-FEB-09:02 | 78617.60 | 25-FEB-09:02 | 0.00 | 0.00 | 0.00 |
March | 0.124520E+11 | 0.00 | 346.48 | 0.945383E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 81115.27 | 19-MAR-18:02 | 81115.27 | 19-MAR-18:02 | 0.00 | 0.00 | 0.00 |
April | 0.241707E+11 | 0.00 | 453.90 | 0.181049E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 85694.50 | 30-APR-15:02 | 83653.51 | 01-APR-18:01 | 0.00 | 0.00 | 0.00 |
May | 0.381423E+11 | 0.00 | 518.71 | 0.268465E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 88398.79 | 05-MAY-18:02 | 86181.63 | 21-MAY-18:01 | 0.00 | 0.00 | 0.00 |
June | 0.462391E+11 | 0.00 | 510.25 | 0.323576E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 92440.23 | 12-JUN-15:01 | 85940.96 | 09-JUN-18:02 | 0.00 | 0.00 | 0.00 |
July | 0.552718E+11 | 0.00 | 529.45 | 0.378622E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 91602.61 | 16-JUL-18:03 | 84274.95 | 30-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.547346E+11 | 0.00 | 529.76 | 0.354067E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 94139.30 | 30-AUG-08:62 | 83566.80 | 08-AUG-15:02 | 0.00 | 0.00 | 0.00 |
September | 0.380006E+11 | 0.00 | 507.57 | 0.223965E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 91004.22 | 24-SEP-15:01 | 82117.08 | 14-SEP-18:02 | 0.00 | 0.00 | 0.00 |
October | 0.203716E+11 | 0.00 | 490.09 | 0.118118E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 88607.90 | 01-OCT-15:02 | 82095.92 | 02-OCT-18:01 | 0.00 | 0.00 | 0.00 |
November | 0.901369E+10 | 0.00 | 273.70 | 0.450944E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 86809.99 | 03-NOV-18:03 | 78001.60 | 04-NOV-08:62 | 0.00 | 0.00 | 0.00 |
December | 0.173674E+10 | 0.00 | 101.85 | 0.108704E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 78853.78 | 03-DEC-09:02 | 78853.78 | 03-DEC-09:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.307247E+12 | 0.00 | 4512.28 | 0.203870E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.173674E+10 | 0.00 | 91.70 | 0.108704E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 71396.72 | 71396.72 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.552718E+11 | 0.00 | 529.76 | 0.378622E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 94139.30 | 86181.63 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_5_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 6082869.53 | 0.00 | 2.76 | 5245904.74 | 0.00 | 0.00 | 0.00 | 0.00 | 2365.22 | 10-JAN-09:03 | 2365.22 | 10-JAN-09:03 | 0.00 | 0.00 | 0.00 |
February | 0.221620E+09 | 0.00 | 56.48 | 0.147343E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15337.87 | 08-FEB-16:02 | 15337.87 | 08-FEB-16:02 | 0.00 | 0.00 | 0.00 |
March | 0.937937E+09 | 0.00 | 176.90 | 0.786982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16260.43 | 02-MAR-16:02 | 16260.43 | 02-MAR-16:02 | 0.00 | 0.00 | 0.00 |
April | 0.270521E+10 | 0.00 | 375.57 | 0.186484E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16866.75 | 30-APR-08:62 | 16263.05 | 20-APR-08:62 | 0.00 | 0.00 | 0.00 |
May | 0.393121E+10 | 0.00 | 493.46 | 0.233067E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16812.01 | 07-MAY-08:62 | 16263.54 | 14-MAY-15:02 | 0.00 | 0.00 | 0.00 |
June | 0.558550E+10 | 0.00 | 603.00 | 0.322998E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17931.47 | 12-JUN-15:01 | 16205.61 | 08-JUN-18:01 | 0.00 | 0.00 | 0.00 |
July | 0.703150E+10 | 0.00 | 675.52 | 0.403159E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17484.33 | 16-JUL-15:01 | 15894.54 | 13-JUL-15:02 | 0.00 | 0.00 | 0.00 |
August | 0.784902E+10 | 0.00 | 659.78 | 0.459410E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17974.22 | 26-AUG-08:62 | 15834.30 | 07-AUG-08:62 | 0.00 | 0.00 | 0.00 |
September | 0.477217E+10 | 0.00 | 530.74 | 0.262790E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17893.92 | 24-SEP-15:01 | 15808.74 | 14-SEP-08:61 | 0.00 | 0.00 | 0.00 |
October | 0.166026E+10 | 0.00 | 287.42 | 0.962868E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17283.48 | 01-OCT-15:02 | 16260.79 | 11-OCT-15:02 | 0.00 | 0.00 | 0.00 |
November | 0.235544E+09 | 0.00 | 57.53 | 96594406.98 | 0.00 | 0.00 | 0.00 | 0.00 | 16612.56 | 04-NOV-15:02 | 15220.46 | 04-NOV-15:02 | 0.00 | 0.00 | 0.00 |
December | 66885212.35 | 0.00 | 14.66 | 62611015.38 | 0.00 | 0.00 | 0.00 | 0.00 | 8441.91 | 02-DEC-09:02 | 8441.91 | 02-DEC-09:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.350030E+11 | 0.00 | 3933.81 | 0.207407E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 6082869.53 | 0.00 | 2.76 | 5245904.74 | 0.00 | 0.00 | 0.00 | 0.00 | 2365.22 | 2365.22 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.784902E+10 | 0.00 | 675.52 | 0.459410E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17974.22 | 16263.54 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_6_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 1350191.13 | 0.00 | 0.33 | 864873.81 | 0.00 | 0.00 | 0.00 | 0.00 | 2004.79 | 10-JAN-19:05 | 2004.79 | 10-JAN-19:05 | 0.00 | 0.00 | 0.00 |
February | 39235768.09 | 0.00 | 20.03 | 14632698.80 | 0.00 | 0.00 | 0.00 | 0.00 | 9714.03 | 27-FEB-16:01 | 9094.36 | 27-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.295483E+09 | 0.00 | 92.10 | 0.239515E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14353.91 | 02-MAR-09:02 | 14353.91 | 02-MAR-09:02 | 0.00 | 0.00 | 0.00 |
April | 0.173367E+10 | 0.00 | 282.62 | 0.115920E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15376.50 | 30-APR-08:62 | 14855.50 | 02-APR-15:01 | 0.00 | 0.00 | 0.00 |
May | 0.304219E+10 | 0.00 | 439.13 | 0.180735E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15374.64 | 07-MAY-08:62 | 14855.37 | 21-MAY-15:01 | 0.00 | 0.00 | 0.00 |
June | 0.486205E+10 | 0.00 | 574.39 | 0.289040E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16390.98 | 12-JUN-15:01 | 14854.78 | 01-JUN-15:01 | 0.00 | 0.00 | 0.00 |
July | 0.597353E+10 | 0.00 | 656.95 | 0.345842E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15885.74 | 16-JUL-15:01 | 14426.27 | 22-JUL-15:02 | 0.00 | 0.00 | 0.00 |
August | 0.639180E+10 | 0.00 | 632.97 | 0.362510E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16454.63 | 26-AUG-08:62 | 14502.44 | 12-AUG-15:02 | 0.00 | 0.00 | 0.00 |
September | 0.303072E+10 | 0.00 | 454.54 | 0.153298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15838.77 | 24-SEP-15:01 | 14396.54 | 11-SEP-18:02 | 0.00 | 0.00 | 0.00 |
October | 0.687525E+09 | 0.00 | 157.72 | 0.372441E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15257.39 | 01-OCT-15:02 | 14627.01 | 04-OCT-15:02 | 0.00 | 0.00 | 0.00 |
November | 65397147.58 | 0.00 | 30.17 | 16800306.35 | 0.00 | 0.00 | 0.00 | 0.00 | 11397.45 | 04-NOV-15:02 | 8592.08 | 04-NOV-15:02 | 0.00 | 0.00 | 0.00 |
December | 3303809.76 | 0.00 | 1.94 | 2490451.05 | 0.00 | 0.00 | 0.00 | 0.00 | 2268.16 | 28-DEC-19:05 | 2182.55 | 03-DEC-09:04 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.261263E+11 | 0.00 | 3342.89 | 0.151202E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 1350191.13 | 0.00 | 0.33 | 864873.81 | 0.00 | 0.00 | 0.00 | 0.00 | 2004.79 | 2004.79 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.639180E+10 | 0.00 | 656.95 | 0.362510E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16454.63 | 14855.50 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 1179814.33 | 0.00 | 1.10 | 1072532.42 | 0.00 | 0.00 | 0.00 | 0.00 | 2301.09 | 20-JAN-16:02 | 2301.09 | 20-JAN-16:02 | 0.00 | 0.00 | 0.00 |
February | 61779019.93 | 0.00 | 42.65 | 43642820.50 | 0.00 | 0.00 | 0.00 | 0.00 | 4787.17 | 06-FEB-16:01 | 4787.17 | 06-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.253556E+09 | 0.00 | 134.45 | 0.224861E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4789.46 | 17-MAR-15:02 | 4789.46 | 17-MAR-15:02 | 0.00 | 0.00 | 0.00 |
April | 0.721167E+09 | 0.00 | 312.32 | 0.540503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5102.73 | 30-APR-08:62 | 4789.65 | 02-APR-18:01 | 0.00 | 0.00 | 0.00 |
May | 0.129121E+10 | 0.00 | 475.17 | 0.858337E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5014.79 | 07-MAY-08:62 | 4789.48 | 14-MAY-15:02 | 0.00 | 0.00 | 0.00 |
June | 0.150421E+10 | 0.00 | 567.20 | 0.914958E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5289.38 | 12-JUN-15:01 | 4789.30 | 01-JUN-18:02 | 0.00 | 0.00 | 0.00 |
July | 0.236282E+10 | 0.00 | 670.57 | 0.150518E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5224.71 | 16-JUL-15:01 | 4654.09 | 31-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.227144E+10 | 0.00 | 652.09 | 0.141087E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5259.67 | 26-AUG-08:62 | 4648.13 | 24-AUG-18:02 | 0.00 | 0.00 | 0.00 |
September | 0.146187E+10 | 0.00 | 525.15 | 0.867944E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5299.37 | 23-SEP-08:61 | 4624.94 | 14-SEP-18:02 | 0.00 | 0.00 | 0.00 |
October | 0.426565E+09 | 0.00 | 231.15 | 0.264509E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4962.97 | 01-OCT-15:02 | 4789.58 | 29-OCT-15:02 | 0.00 | 0.00 | 0.00 |
November | 52383725.29 | 0.00 | 36.38 | 26158483.90 | 0.00 | 0.00 | 0.00 | 0.00 | 4886.13 | 05-NOV-15:01 | 4771.10 | 11-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 4732181.24 | 0.00 | 5.70 | 4405715.62 | 0.00 | 0.00 | 0.00 | 0.00 | 4681.10 | 05-DEC-16:02 | 4681.10 | 05-DEC-16:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.104129E+11 | 0.00 | 3653.93 | 0.666244E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 1179814.33 | 0.00 | 1.10 | 1072532.42 | 0.00 | 0.00 | 0.00 | 0.00 | 2301.09 | 2301.09 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.236282E+10 | 0.00 | 670.57 | 0.150518E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5299.37 | 4789.65 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 203335.38 | 0.00 | 0.18 | 170612.49 | 0.00 | 0.00 | 0.00 | 0.00 | 572.28 | 05-JAN-16:04 | 572.28 | 05-JAN-16:04 | 0.00 | 0.00 | 0.00 |
February | 15491672.17 | 0.00 | 15.24 | 7514371.58 | 0.00 | 0.00 | 0.00 | 0.00 | 3482.26 | 26-FEB-16:01 | 3482.26 | 26-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 98281255.55 | 0.00 | 67.65 | 89638645.76 | 0.00 | 0.00 | 0.00 | 0.00 | 4309.21 | 02-MAR-16:02 | 4309.21 | 02-MAR-16:02 | 0.00 | 0.00 | 0.00 |
April | 0.478747E+09 | 0.00 | 230.05 | 0.357628E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4453.48 | 30-APR-08:62 | 4309.34 | 25-APR-18:01 | 0.00 | 0.00 | 0.00 |
May | 0.104712E+10 | 0.00 | 430.91 | 0.707380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4499.83 | 07-MAY-08:62 | 4310.29 | 14-MAY-15:02 | 0.00 | 0.00 | 0.00 |
June | 0.131639E+10 | 0.00 | 536.07 | 0.821253E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4763.86 | 12-JUN-15:01 | 4310.06 | 01-JUN-18:02 | 0.00 | 0.00 | 0.00 |
July | 0.208094E+10 | 0.00 | 650.95 | 0.133511E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4704.87 | 16-JUL-15:01 | 4199.53 | 28-JUL-15:02 | 0.00 | 0.00 | 0.00 |
August | 0.188578E+10 | 0.00 | 623.93 | 0.115501E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4756.73 | 26-AUG-08:62 | 4188.27 | 24-AUG-18:02 | 0.00 | 0.00 | 0.00 |
September | 0.986030E+09 | 0.00 | 450.21 | 0.560049E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4723.37 | 23-SEP-08:61 | 4188.83 | 13-SEP-18:02 | 0.00 | 0.00 | 0.00 |
October | 0.183156E+09 | 0.00 | 131.63 | 0.114357E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4652.00 | 01-OCT-15:02 | 4309.21 | 11-OCT-15:02 | 0.00 | 0.00 | 0.00 |
November | 18701622.66 | 0.00 | 14.24 | 8394456.14 | 0.00 | 0.00 | 0.00 | 0.00 | 4443.93 | 04-NOV-15:02 | 4011.29 | 04-NOV-15:02 | 0.00 | 0.00 | 0.00 |
December | 401673.48 | 0.00 | 0.35 | 264507.05 | 0.00 | 0.00 | 0.00 | 0.00 | 689.76 | 03-DEC-16:03 | 689.76 | 03-DEC-16:03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.811124E+10 | 0.00 | 3151.41 | 0.515676E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 203335.38 | 0.00 | 0.18 | 170612.49 | 0.00 | 0.00 | 0.00 | 0.00 | 572.28 | 572.28 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.208094E+10 | 0.00 | 650.95 | 0.133511E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4763.86 | 4310.29 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.413314E+09 | 0.00 | 50.89 | 0.392951E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 26172.40 | 20-JAN-16:02 | 26172.40 | 20-JAN-16:02 | 0.00 | 0.00 | 0.00 |
February | 0.195788E+10 | 0.00 | 174.48 | 0.158343E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26182.83 | 03-FEB-16:01 | 26182.83 | 03-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.372079E+10 | 0.00 | 310.23 | 0.313103E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26182.41 | 23-MAR-15:01 | 26182.41 | 23-MAR-15:01 | 0.00 | 0.00 | 0.00 |
April | 0.579260E+10 | 0.00 | 444.33 | 0.409786E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26978.85 | 30-APR-15:02 | 26183.03 | 02-APR-18:01 | 0.00 | 0.00 | 0.00 |
May | 0.736092E+10 | 0.00 | 552.60 | 0.436540E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27106.26 | 06-MAY-18:01 | 26182.97 | 20-MAY-15:01 | 0.00 | 0.00 | 0.00 |
June | 0.831283E+10 | 0.00 | 611.09 | 0.451504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29002.71 | 12-JUN-15:01 | 25807.74 | 08-JUN-18:01 | 0.00 | 0.00 | 0.00 |
July | 0.116428E+11 | 0.00 | 671.98 | 0.654657E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28598.35 | 16-JUL-15:01 | 25342.60 | 24-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.129468E+11 | 0.00 | 667.82 | 0.772409E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27876.30 | 26-AUG-18:01 | 25597.08 | 31-AUG-15:02 | 0.00 | 0.00 | 0.00 |
September | 0.105653E+11 | 0.00 | 589.16 | 0.646724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27767.45 | 23-SEP-08:61 | 25269.39 | 30-SEP-18:01 | 0.00 | 0.00 | 0.00 |
October | 0.573345E+10 | 0.00 | 440.41 | 0.364641E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27646.14 | 01-OCT-08:62 | 26180.98 | 11-OCT-18:01 | 0.00 | 0.00 | 0.00 |
November | 0.147695E+10 | 0.00 | 158.02 | 0.949244E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 26181.10 | 10-NOV-16:01 | 26181.10 | 10-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 0.107244E+10 | 0.00 | 96.83 | 0.100771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26178.16 | 06-DEC-16:01 | 26178.16 | 06-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.709961E+11 | 0.00 | 4767.83 | 0.444270E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.413314E+09 | 0.00 | 50.89 | 0.392951E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 26172.40 | 25269.39 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.129468E+11 | 0.00 | 671.98 | 0.772409E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29002.71 | 26183.03 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 438.55 | 260.88 | 177.67 | 389.72 | 505.09 | 0.00 | 0.00 | 0.00 |
February | 674.87 | 418.72 | 256.15 | 683.34 | 443.41 | 0.00 | 0.00 | 0.00 |
March | 715.89 | 378.50 | 337.40 | 764.96 | 365.82 | 0.00 | 0.00 | 0.00 |
April | 756.46 | 324.65 | 431.81 | 864.78 | 291.17 | 0.00 | 0.00 | 0.00 |
May | 704.79 | 214.87 | 489.92 | 829.77 | 228.20 | 0.00 | 0.00 | 0.00 |
June | 637.68 | 170.67 | 467.01 | 778.14 | 165.34 | 0.00 | 0.00 | 0.00 |
July | 692.81 | 251.56 | 441.25 | 919.41 | 139.97 | 0.00 | 0.00 | 0.00 |
August | 738.59 | 339.38 | 399.21 | 999.23 | 131.99 | 0.00 | 0.00 | 0.00 |
September | 819.19 | 448.04 | 371.15 | 1027.33 | 208.96 | 0.00 | 0.00 | 0.00 |
October | 741.03 | 453.68 | 287.34 | 847.63 | 306.36 | 0.00 | 0.00 | 0.00 |
November | 443.48 | 253.85 | 189.63 | 428.70 | 398.60 | 0.00 | 0.00 | 0.00 |
December | 464.15 | 300.16 | 163.99 | 453.10 | 506.55 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 651.97 | 317.29 | 334.69 | 749.10 | 306.96 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 438.55 | 170.67 | 163.99 | 389.72 | 131.99 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 819.19 | 453.68 | 489.92 | 1027.33 | 506.55 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1234.93 | 734.63 | 500.29 | 1085.33 | 1441.38 | 0.00 | 0.00 | 0.00 |
February | 1900.38 | 1179.08 | 721.29 | 1910.22 | 1257.49 | 0.00 | 0.00 | 0.00 |
March | 2015.91 | 1065.82 | 950.09 | 2141.64 | 1032.72 | 0.00 | 0.00 | 0.00 |
April | 2130.15 | 914.20 | 1215.94 | 2422.72 | 817.23 | 0.00 | 0.00 | 0.00 |
May | 1984.66 | 605.06 | 1379.59 | 2325.24 | 636.40 | 0.00 | 0.00 | 0.00 |
June | 1795.66 | 480.59 | 1315.07 | 2179.64 | 459.50 | 0.00 | 0.00 | 0.00 |
July | 1950.90 | 708.37 | 1242.53 | 2581.25 | 385.81 | 0.00 | 0.00 | 0.00 |
August | 2079.83 | 955.67 | 1124.16 | 2807.19 | 365.19 | 0.00 | 0.00 | 0.00 |
September | 2306.78 | 1261.66 | 1045.13 | 2885.57 | 581.71 | 0.00 | 0.00 | 0.00 |
October | 2086.69 | 1277.54 | 809.14 | 2376.39 | 864.04 | 0.00 | 0.00 | 0.00 |
November | 1248.82 | 714.83 | 533.99 | 1196.26 | 1132.17 | 0.00 | 0.00 | 0.00 |
December | 1307.01 | 845.22 | 461.79 | 1265.65 | 1446.25 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1835.92 | 893.47 | 942.45 | 2098.84 | 866.45 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1234.93 | 480.59 | 461.79 | 1085.33 | 365.19 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2306.78 | 1277.54 | 1379.59 | 2885.57 | 1446.25 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1604.24 | 954.33 | 649.91 | 1426.89 | 1936.34 | 0.00 | 0.00 | 0.00 |
February | 2468.70 | 1531.69 | 937.00 | 2520.06 | 1678.68 | 0.00 | 0.00 | 0.00 |
March | 2618.78 | 1384.56 | 1234.22 | 2832.01 | 1375.44 | 0.00 | 0.00 | 0.00 |
April | 2767.18 | 1187.60 | 1579.58 | 3210.15 | 1087.56 | 0.00 | 0.00 | 0.00 |
May | 2578.18 | 786.01 | 1792.17 | 3086.61 | 850.97 | 0.00 | 0.00 | 0.00 |
June | 2332.66 | 624.32 | 1708.35 | 2897.36 | 618.06 | 0.00 | 0.00 | 0.00 |
July | 2534.33 | 920.22 | 1614.12 | 3427.06 | 519.31 | 0.00 | 0.00 | 0.00 |
August | 2701.82 | 1241.47 | 1460.35 | 3725.01 | 490.82 | 0.00 | 0.00 | 0.00 |
September | 2996.64 | 1638.96 | 1357.68 | 3822.67 | 773.23 | 0.00 | 0.00 | 0.00 |
October | 2710.73 | 1659.60 | 1051.12 | 3142.38 | 1148.94 | 0.00 | 0.00 | 0.00 |
November | 1622.29 | 928.61 | 693.68 | 1577.40 | 1518.88 | 0.00 | 0.00 | 0.00 |
December | 1697.88 | 1097.99 | 599.89 | 1665.11 | 1943.53 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2384.96 | 1160.66 | 1224.30 | 2778.76 | 1159.34 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1604.24 | 624.32 | 599.89 | 1426.89 | 490.82 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2996.64 | 1659.60 | 1792.17 | 3822.67 | 1943.53 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 86.71 | 51.58 | 35.13 | 77.77 | 102.51 | 0.00 | 0.00 | 0.00 |
February | 133.43 | 82.79 | 50.64 | 135.03 | 90.22 | 0.00 | 0.00 | 0.00 |
March | 141.54 | 74.84 | 66.71 | 150.28 | 75.11 | 0.00 | 0.00 | 0.00 |
April | 149.57 | 64.19 | 85.38 | 167.96 | 60.87 | 0.00 | 0.00 | 0.00 |
May | 139.35 | 42.48 | 96.87 | 159.57 | 48.09 | 0.00 | 0.00 | 0.00 |
June | 126.08 | 33.74 | 92.34 | 149.06 | 34.79 | 0.00 | 0.00 | 0.00 |
July | 136.98 | 49.74 | 87.24 | 176.70 | 29.67 | 0.00 | 0.00 | 0.00 |
August | 146.03 | 67.10 | 78.93 | 193.70 | 27.62 | 0.00 | 0.00 | 0.00 |
September | 161.97 | 88.59 | 73.38 | 201.35 | 43.35 | 0.00 | 0.00 | 0.00 |
October | 146.51 | 89.70 | 56.81 | 166.33 | 62.60 | 0.00 | 0.00 | 0.00 |
November | 87.68 | 50.19 | 37.49 | 85.00 | 80.65 | 0.00 | 0.00 | 0.00 |
December | 91.77 | 59.35 | 32.42 | 90.05 | 102.21 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 128.91 | 62.73 | 66.17 | 146.11 | 63.01 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 86.71 | 33.74 | 32.42 | 77.77 | 27.62 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 161.97 | 89.70 | 96.87 | 201.35 | 102.51 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 62.25 | 18.52 | 43.73 | 27.12 | 206.02 | 0.00 | 0.00 | 0.00 |
February | 111.04 | 41.69 | 69.36 | 76.98 | 178.89 | 0.00 | 0.00 | 0.00 |
March | 155.56 | 52.59 | 102.96 | 131.38 | 142.84 | 0.00 | 0.00 | 0.00 |
April | 236.38 | 90.26 | 146.12 | 240.03 | 110.95 | 0.00 | 0.00 | 0.00 |
May | 304.75 | 124.07 | 180.68 | 339.67 | 87.18 | 0.00 | 0.00 | 0.00 |
June | 292.45 | 113.33 | 179.11 | 335.85 | 63.07 | 0.00 | 0.00 | 0.00 |
July | 361.52 | 189.97 | 171.55 | 449.82 | 53.93 | 0.00 | 0.00 | 0.00 |
August | 299.20 | 152.61 | 146.59 | 377.56 | 50.86 | 0.00 | 0.00 | 0.00 |
September | 244.45 | 117.59 | 126.86 | 285.14 | 80.84 | 0.00 | 0.00 | 0.00 |
October | 139.79 | 57.47 | 82.32 | 130.58 | 120.39 | 0.00 | 0.00 | 0.00 |
November | 69.23 | 19.68 | 49.55 | 40.18 | 158.98 | 0.00 | 0.00 | 0.00 |
December | 58.44 | 20.29 | 38.15 | 31.47 | 204.32 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 195.10 | 83.49 | 111.61 | 206.32 | 121.25 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 58.44 | 18.52 | 38.15 | 27.12 | 50.86 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 361.52 | 189.97 | 180.68 | 449.82 | 206.02 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.55 | 0.00 | 19.55 | 1.03 | 113.58 | 0.00 | 0.00 | 0.00 |
February | 30.42 | 0.00 | 30.42 | 7.18 | 98.38 | 0.00 | 0.00 | 0.00 |
March | 44.83 | 0.00 | 44.83 | 21.64 | 77.42 | 0.00 | 0.00 | 0.00 |
April | 63.66 | 0.39 | 63.27 | 44.86 | 58.98 | 0.00 | 0.00 | 0.00 |
May | 81.67 | 2.45 | 79.22 | 70.95 | 45.10 | 0.00 | 0.00 | 0.00 |
June | 85.95 | 5.75 | 80.20 | 83.59 | 31.94 | 0.00 | 0.00 | 0.00 |
July | 81.81 | 6.59 | 75.22 | 88.76 | 27.12 | 0.00 | 0.00 | 0.00 |
August | 66.31 | 1.99 | 64.32 | 74.33 | 25.57 | 0.00 | 0.00 | 0.00 |
September | 51.33 | 0.04 | 51.29 | 44.30 | 43.09 | 0.00 | 0.00 | 0.00 |
October | 35.14 | 0.00 | 35.14 | 19.18 | 64.68 | 0.00 | 0.00 | 0.00 |
November | 22.14 | 0.00 | 22.14 | 4.47 | 86.33 | 0.00 | 0.00 | 0.00 |
December | 16.61 | 0.00 | 16.61 | 0.61 | 110.88 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 50.05 | 1.44 | 48.60 | 38.60 | 65.09 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 16.61 | 0.00 | 16.61 | 0.61 | 25.57 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 85.95 | 6.59 | 80.20 | 88.76 | 113.58 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 62.25 | 18.52 | 43.73 | 28.80 | 204.14 | 0.00 | 0.00 | 0.00 |
February | 111.04 | 41.69 | 69.36 | 80.46 | 176.17 | 0.00 | 0.00 | 0.00 |
March | 155.56 | 52.59 | 102.96 | 135.65 | 140.70 | 0.00 | 0.00 | 0.00 |
April | 236.38 | 90.26 | 146.12 | 244.03 | 109.64 | 0.00 | 0.00 | 0.00 |
May | 304.75 | 124.07 | 180.68 | 342.22 | 86.51 | 0.00 | 0.00 | 0.00 |
June | 292.45 | 113.33 | 179.11 | 337.85 | 62.59 | 0.00 | 0.00 | 0.00 |
July | 361.52 | 189.97 | 171.55 | 451.97 | 53.39 | 0.00 | 0.00 | 0.00 |
August | 299.20 | 152.61 | 146.59 | 380.33 | 50.10 | 0.00 | 0.00 | 0.00 |
September | 244.45 | 117.59 | 126.86 | 288.79 | 79.43 | 0.00 | 0.00 | 0.00 |
October | 139.79 | 57.47 | 82.32 | 134.92 | 118.16 | 0.00 | 0.00 | 0.00 |
November | 69.23 | 19.68 | 49.55 | 42.29 | 157.00 | 0.00 | 0.00 | 0.00 |
December | 58.44 | 20.29 | 38.15 | 33.50 | 202.07 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 195.10 | 83.49 | 111.61 | 209.24 | 119.72 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 58.44 | 18.52 | 38.15 | 28.80 | 50.10 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 361.52 | 189.97 | 180.68 | 451.97 | 204.14 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 69.35 | 41.26 | 28.10 | 61.93 | 79.58 | 0.00 | 0.00 | 0.00 |
February | 106.72 | 66.22 | 40.51 | 106.24 | 74.98 | 0.00 | 0.00 | 0.00 |
March | 113.21 | 59.86 | 53.36 | 116.74 | 68.79 | 0.00 | 0.00 | 0.00 |
April | 119.63 | 51.34 | 68.29 | 130.64 | 56.78 | 0.00 | 0.00 | 0.00 |
May | 111.46 | 33.98 | 77.48 | 124.53 | 45.63 | 0.00 | 0.00 | 0.00 |
June | 100.84 | 26.99 | 73.85 | 115.82 | 34.43 | 0.00 | 0.00 | 0.00 |
July | 109.56 | 39.78 | 69.78 | 138.91 | 29.79 | 0.00 | 0.00 | 0.00 |
August | 116.80 | 53.67 | 63.13 | 152.16 | 28.51 | 0.00 | 0.00 | 0.00 |
September | 129.55 | 70.85 | 58.69 | 157.85 | 42.47 | 0.00 | 0.00 | 0.00 |
October | 117.19 | 71.75 | 45.44 | 128.98 | 60.38 | 0.00 | 0.00 | 0.00 |
November | 70.13 | 40.14 | 29.99 | 65.53 | 70.69 | 0.00 | 0.00 | 0.00 |
December | 73.40 | 47.47 | 25.93 | 71.14 | 82.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 103.11 | 50.18 | 52.93 | 114.24 | 56.07 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 69.35 | 26.99 | 25.93 | 61.93 | 28.51 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 129.55 | 71.75 | 77.48 | 157.85 | 82.00 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 15.64 | 0.00 | 15.64 | 0.51 | 96.95 | 0.00 | 0.00 | 0.00 |
February | 24.34 | 0.00 | 24.34 | 4.97 | 82.84 | 0.00 | 0.00 | 0.00 |
March | 35.87 | 0.00 | 35.87 | 16.66 | 64.49 | 0.00 | 0.00 | 0.00 |
April | 50.93 | 0.31 | 50.62 | 36.56 | 48.13 | 0.00 | 0.00 | 0.00 |
May | 65.34 | 1.96 | 63.38 | 58.70 | 36.24 | 0.00 | 0.00 | 0.00 |
June | 68.77 | 4.60 | 64.17 | 69.11 | 25.40 | 0.00 | 0.00 | 0.00 |
July | 65.45 | 5.27 | 60.19 | 74.43 | 20.98 | 0.00 | 0.00 | 0.00 |
August | 53.06 | 1.59 | 51.46 | 62.43 | 19.79 | 0.00 | 0.00 | 0.00 |
September | 41.07 | 0.03 | 41.04 | 36.99 | 34.23 | 0.00 | 0.00 | 0.00 |
October | 28.12 | 0.00 | 28.12 | 14.98 | 53.79 | 0.00 | 0.00 | 0.00 |
November | 17.71 | 0.00 | 17.71 | 2.93 | 73.91 | 0.00 | 0.00 | 0.00 |
December | 13.29 | 0.00 | 13.29 | 0.26 | 94.77 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 40.04 | 1.16 | 38.89 | 31.71 | 54.16 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 13.29 | 0.00 | 13.29 | 0.26 | 19.79 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 68.77 | 5.27 | 64.17 | 74.43 | 96.95 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 58.42 | 14.64 | 43.78 | 20.53 | 203.79 | 0.00 | 0.00 | 0.00 |
February | 107.62 | 38.12 | 69.50 | 69.42 | 175.53 | 0.00 | 0.00 | 0.00 |
March | 161.29 | 58.49 | 102.80 | 134.18 | 138.34 | 0.00 | 0.00 | 0.00 |
April | 249.11 | 103.37 | 145.74 | 251.96 | 106.75 | 0.00 | 0.00 | 0.00 |
May | 265.24 | 92.35 | 172.89 | 285.50 | 84.62 | 0.00 | 0.00 | 0.00 |
June | 317.46 | 138.17 | 179.29 | 367.56 | 60.66 | 0.00 | 0.00 | 0.00 |
July | 296.07 | 133.11 | 162.96 | 359.77 | 49.59 | 0.00 | 0.00 | 0.00 |
August | 290.63 | 145.38 | 145.25 | 363.07 | 47.56 | 0.00 | 0.00 | 0.00 |
September | 215.23 | 99.44 | 115.79 | 241.62 | 77.40 | 0.00 | 0.00 | 0.00 |
October | 140.73 | 60.13 | 80.60 | 129.49 | 117.49 | 0.00 | 0.00 | 0.00 |
November | 68.87 | 19.50 | 49.37 | 37.89 | 156.64 | 0.00 | 0.00 | 0.00 |
December | 56.34 | 18.11 | 38.23 | 25.87 | 200.63 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 185.93 | 76.91 | 109.02 | 191.19 | 117.97 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 56.34 | 14.64 | 38.23 | 20.53 | 47.56 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 317.46 | 145.38 | 179.29 | 367.56 | 203.79 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 86.71 | 51.58 | 35.13 | 77.74 | 102.36 | 0.00 | 0.00 | 0.00 |
February | 133.43 | 82.79 | 50.64 | 134.76 | 89.97 | 0.00 | 0.00 | 0.00 |
March | 141.54 | 74.84 | 66.71 | 149.48 | 74.89 | 0.00 | 0.00 | 0.00 |
April | 149.57 | 64.19 | 85.38 | 166.73 | 60.63 | 0.00 | 0.00 | 0.00 |
May | 139.35 | 42.48 | 96.87 | 159.37 | 47.45 | 0.00 | 0.00 | 0.00 |
June | 126.08 | 33.74 | 92.34 | 147.80 | 34.49 | 0.00 | 0.00 | 0.00 |
July | 136.98 | 49.74 | 87.24 | 176.70 | 28.85 | 0.00 | 0.00 | 0.00 |
August | 146.03 | 67.10 | 78.93 | 193.08 | 27.19 | 0.00 | 0.00 | 0.00 |
September | 161.97 | 88.59 | 73.38 | 201.17 | 42.61 | 0.00 | 0.00 | 0.00 |
October | 146.51 | 89.70 | 56.81 | 165.78 | 62.30 | 0.00 | 0.00 | 0.00 |
November | 87.68 | 50.19 | 37.49 | 84.88 | 80.50 | 0.00 | 0.00 | 0.00 |
December | 91.77 | 59.35 | 32.42 | 90.02 | 102.02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 128.91 | 62.73 | 66.17 | 145.67 | 62.64 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 86.71 | 33.74 | 32.42 | 77.74 | 27.19 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 161.97 | 89.70 | 96.87 | 201.17 | 102.36 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.55 | 0.00 | 19.55 | 0.99 | 113.51 | 0.00 | 0.00 | 0.00 |
February | 30.42 | 0.00 | 30.42 | 7.04 | 98.17 | 0.00 | 0.00 | 0.00 |
March | 44.83 | 0.00 | 44.83 | 20.91 | 77.30 | 0.00 | 0.00 | 0.00 |
April | 63.66 | 0.39 | 63.27 | 43.58 | 59.01 | 0.00 | 0.00 | 0.00 |
May | 81.67 | 2.45 | 79.22 | 70.63 | 44.55 | 0.00 | 0.00 | 0.00 |
June | 85.95 | 5.75 | 80.20 | 82.08 | 31.69 | 0.00 | 0.00 | 0.00 |
July | 81.81 | 6.59 | 75.22 | 88.73 | 26.39 | 0.00 | 0.00 | 0.00 |
August | 66.31 | 1.99 | 64.32 | 73.44 | 25.13 | 0.00 | 0.00 | 0.00 |
September | 51.33 | 0.04 | 51.29 | 43.95 | 42.41 | 0.00 | 0.00 | 0.00 |
October | 35.14 | 0.00 | 35.14 | 18.56 | 64.40 | 0.00 | 0.00 | 0.00 |
November | 22.14 | 0.00 | 22.14 | 4.30 | 86.13 | 0.00 | 0.00 | 0.00 |
December | 16.61 | 0.00 | 16.61 | 0.54 | 110.71 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 50.05 | 1.44 | 48.60 | 38.09 | 64.79 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 16.61 | 0.00 | 16.61 | 0.54 | 25.13 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 85.95 | 6.59 | 80.20 | 88.73 | 113.51 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 58.42 | 14.64 | 43.78 | 21.34 | 201.15 | 0.00 | 0.00 | 0.00 |
February | 107.62 | 38.12 | 69.50 | 71.82 | 171.49 | 0.00 | 0.00 | 0.00 |
March | 161.29 | 58.49 | 102.80 | 138.11 | 135.93 | 0.00 | 0.00 | 0.00 |
April | 249.11 | 103.37 | 145.74 | 255.42 | 105.37 | 0.00 | 0.00 | 0.00 |
May | 265.24 | 92.35 | 172.89 | 287.74 | 83.90 | 0.00 | 0.00 | 0.00 |
June | 317.46 | 138.17 | 179.29 | 369.16 | 60.21 | 0.00 | 0.00 | 0.00 |
July | 296.07 | 133.11 | 162.96 | 361.72 | 49.04 | 0.00 | 0.00 | 0.00 |
August | 290.63 | 145.38 | 145.25 | 365.53 | 46.84 | 0.00 | 0.00 | 0.00 |
September | 215.23 | 99.44 | 115.79 | 244.92 | 75.89 | 0.00 | 0.00 | 0.00 |
October | 140.73 | 60.13 | 80.60 | 133.48 | 115.02 | 0.00 | 0.00 | 0.00 |
November | 68.87 | 19.50 | 49.37 | 39.36 | 153.98 | 0.00 | 0.00 | 0.00 |
December | 56.34 | 18.11 | 38.23 | 26.95 | 197.39 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 185.93 | 76.91 | 109.02 | 193.58 | 116.09 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 56.34 | 14.64 | 38.23 | 21.34 | 46.84 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 317.46 | 145.38 | 179.29 | 369.16 | 201.15 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 24.76 | 0.00 | 24.76 | 0.73 | 156.36 | 0.00 | 0.00 | 0.00 |
February | 38.53 | 0.00 | 38.53 | 7.84 | 133.10 | 0.00 | 0.00 | 0.00 |
March | 56.77 | 0.00 | 56.77 | 26.87 | 101.78 | 0.00 | 0.00 | 0.00 |
April | 80.62 | 0.50 | 80.12 | 59.84 | 75.32 | 0.00 | 0.00 | 0.00 |
May | 103.43 | 3.11 | 100.32 | 96.55 | 56.31 | 0.00 | 0.00 | 0.00 |
June | 108.85 | 7.28 | 101.57 | 113.81 | 39.20 | 0.00 | 0.00 | 0.00 |
July | 103.60 | 8.34 | 95.26 | 122.02 | 32.52 | 0.00 | 0.00 | 0.00 |
August | 83.98 | 2.52 | 81.46 | 102.08 | 31.04 | 0.00 | 0.00 | 0.00 |
September | 65.00 | 0.05 | 64.95 | 60.51 | 53.60 | 0.00 | 0.00 | 0.00 |
October | 44.51 | 0.00 | 44.51 | 24.52 | 84.39 | 0.00 | 0.00 | 0.00 |
November | 28.03 | 0.00 | 28.03 | 4.82 | 117.54 | 0.00 | 0.00 | 0.00 |
December | 21.04 | 0.00 | 21.04 | 0.36 | 152.53 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 63.38 | 1.83 | 61.55 | 51.94 | 85.92 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 21.04 | 0.00 | 21.04 | 0.36 | 31.04 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 108.85 | 8.34 | 101.57 | 122.02 | 156.36 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 9.13 | 0.00 | 9.13 | 0.27 | 57.64 | 0.00 | 0.00 | 0.00 |
February | 14.20 | 0.00 | 14.20 | 2.89 | 49.07 | 0.00 | 0.00 | 0.00 |
March | 20.93 | 0.00 | 20.93 | 9.91 | 37.52 | 0.00 | 0.00 | 0.00 |
April | 29.72 | 0.18 | 29.54 | 22.06 | 27.77 | 0.00 | 0.00 | 0.00 |
May | 38.13 | 1.14 | 36.98 | 35.59 | 20.76 | 0.00 | 0.00 | 0.00 |
June | 40.13 | 2.68 | 37.44 | 41.96 | 14.45 | 0.00 | 0.00 | 0.00 |
July | 38.19 | 3.07 | 35.12 | 44.98 | 11.99 | 0.00 | 0.00 | 0.00 |
August | 30.96 | 0.93 | 30.03 | 37.63 | 11.44 | 0.00 | 0.00 | 0.00 |
September | 23.96 | 0.02 | 23.94 | 22.31 | 19.76 | 0.00 | 0.00 | 0.00 |
October | 16.41 | 0.00 | 16.41 | 9.04 | 31.11 | 0.00 | 0.00 | 0.00 |
November | 10.33 | 0.00 | 10.33 | 1.78 | 43.33 | 0.00 | 0.00 | 0.00 |
December | 7.76 | 0.00 | 7.76 | 0.13 | 56.23 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 23.37 | 0.67 | 22.69 | 19.15 | 31.67 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 7.76 | 0.00 | 7.76 | 0.13 | 11.44 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 40.13 | 3.07 | 37.44 | 44.98 | 57.64 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 40.46 | 24.07 | 16.39 | 35.62 | 50.81 | 0.00 | 0.00 | 0.00 |
February | 62.26 | 38.63 | 23.63 | 63.05 | 43.90 | 0.00 | 0.00 | 0.00 |
March | 66.04 | 34.92 | 31.13 | 70.96 | 35.80 | 0.00 | 0.00 | 0.00 |
April | 69.79 | 29.95 | 39.84 | 80.36 | 28.24 | 0.00 | 0.00 | 0.00 |
May | 65.02 | 19.82 | 45.20 | 77.38 | 21.88 | 0.00 | 0.00 | 0.00 |
June | 58.83 | 15.74 | 43.08 | 72.81 | 15.61 | 0.00 | 0.00 | 0.00 |
July | 63.91 | 23.21 | 40.71 | 86.30 | 12.98 | 0.00 | 0.00 | 0.00 |
August | 68.14 | 31.31 | 36.83 | 93.84 | 12.16 | 0.00 | 0.00 | 0.00 |
September | 75.57 | 41.33 | 34.24 | 96.48 | 19.53 | 0.00 | 0.00 | 0.00 |
October | 68.36 | 41.85 | 26.51 | 78.90 | 29.52 | 0.00 | 0.00 | 0.00 |
November | 40.91 | 23.42 | 17.49 | 39.57 | 39.65 | 0.00 | 0.00 | 0.00 |
December | 42.82 | 27.69 | 15.13 | 41.81 | 50.66 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 60.15 | 29.27 | 30.88 | 69.78 | 29.99 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 40.46 | 15.74 | 15.13 | 35.62 | 12.16 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 75.57 | 41.85 | 45.20 | 96.48 | 50.81 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 109.81 | 65.32 | 44.49 | 96.67 | 137.92 | 0.00 | 0.00 | 0.00 |
February | 168.98 | 104.85 | 64.14 | 171.12 | 119.15 | 0.00 | 0.00 | 0.00 |
March | 179.26 | 94.77 | 84.48 | 192.61 | 97.18 | 0.00 | 0.00 | 0.00 |
April | 189.42 | 81.29 | 108.12 | 218.12 | 76.64 | 0.00 | 0.00 | 0.00 |
May | 176.48 | 53.80 | 122.68 | 210.02 | 59.37 | 0.00 | 0.00 | 0.00 |
June | 159.67 | 42.73 | 116.94 | 197.63 | 42.36 | 0.00 | 0.00 | 0.00 |
July | 173.48 | 62.99 | 110.49 | 234.23 | 35.22 | 0.00 | 0.00 | 0.00 |
August | 184.94 | 84.98 | 99.96 | 254.71 | 33.01 | 0.00 | 0.00 | 0.00 |
September | 205.12 | 112.19 | 92.93 | 261.86 | 53.01 | 0.00 | 0.00 | 0.00 |
October | 185.55 | 113.60 | 71.95 | 214.15 | 80.11 | 0.00 | 0.00 | 0.00 |
November | 111.05 | 63.56 | 47.48 | 107.41 | 107.61 | 0.00 | 0.00 | 0.00 |
December | 116.22 | 75.16 | 41.06 | 113.47 | 137.50 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 163.25 | 79.45 | 83.80 | 189.41 | 81.41 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 109.81 | 42.73 | 41.06 | 96.67 | 33.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 205.12 | 113.60 | 122.68 | 261.86 | 137.92 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 86.71 | 51.58 | 35.13 | 77.86 | 101.69 | 0.00 | 0.00 | 0.00 |
February | 133.43 | 82.79 | 50.64 | 134.76 | 89.54 | 0.00 | 0.00 | 0.00 |
March | 141.54 | 74.84 | 66.71 | 149.54 | 74.70 | 0.00 | 0.00 | 0.00 |
April | 149.57 | 64.19 | 85.38 | 166.35 | 60.99 | 0.00 | 0.00 | 0.00 |
May | 139.35 | 42.48 | 96.87 | 157.44 | 48.39 | 0.00 | 0.00 | 0.00 |
June | 126.08 | 33.74 | 92.34 | 146.72 | 35.10 | 0.00 | 0.00 | 0.00 |
July | 136.98 | 49.74 | 87.24 | 174.27 | 30.03 | 0.00 | 0.00 | 0.00 |
August | 146.03 | 67.10 | 78.93 | 191.57 | 27.87 | 0.00 | 0.00 | 0.00 |
September | 161.97 | 88.59 | 73.38 | 199.85 | 43.44 | 0.00 | 0.00 | 0.00 |
October | 146.51 | 89.70 | 56.81 | 165.43 | 62.18 | 0.00 | 0.00 | 0.00 |
November | 87.68 | 50.19 | 37.49 | 85.00 | 79.77 | 0.00 | 0.00 | 0.00 |
December | 91.77 | 59.35 | 32.42 | 90.12 | 101.16 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 128.91 | 62.73 | 66.17 | 144.94 | 62.77 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 86.71 | 33.74 | 32.42 | 77.86 | 27.87 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 161.97 | 89.70 | 96.87 | 199.85 | 101.69 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 62.25 | 18.52 | 43.73 | 27.43 | 203.98 | 0.00 | 0.00 | 0.00 |
February | 111.04 | 41.69 | 69.36 | 76.83 | 177.17 | 0.00 | 0.00 | 0.00 |
March | 155.56 | 52.59 | 102.96 | 130.40 | 141.72 | 0.00 | 0.00 | 0.00 |
April | 236.38 | 90.26 | 146.12 | 237.05 | 111.00 | 0.00 | 0.00 | 0.00 |
May | 304.75 | 124.07 | 180.68 | 335.21 | 87.54 | 0.00 | 0.00 | 0.00 |
June | 292.45 | 113.33 | 179.11 | 331.01 | 63.45 | 0.00 | 0.00 | 0.00 |
July | 361.52 | 189.97 | 171.55 | 444.56 | 54.42 | 0.00 | 0.00 | 0.00 |
August | 299.20 | 152.61 | 146.59 | 373.34 | 51.19 | 0.00 | 0.00 | 0.00 |
September | 244.45 | 117.59 | 126.86 | 282.29 | 80.83 | 0.00 | 0.00 | 0.00 |
October | 139.79 | 57.47 | 82.32 | 129.42 | 119.32 | 0.00 | 0.00 | 0.00 |
November | 69.23 | 19.68 | 49.55 | 40.37 | 156.80 | 0.00 | 0.00 | 0.00 |
December | 58.44 | 20.29 | 38.15 | 31.66 | 201.57 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 195.10 | 83.49 | 111.61 | 204.13 | 120.48 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 58.44 | 18.52 | 38.15 | 27.43 | 51.19 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 361.52 | 189.97 | 180.68 | 444.56 | 203.98 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.55 | 0.00 | 19.55 | 1.11 | 112.32 | 0.00 | 0.00 | 0.00 |
February | 30.42 | 0.00 | 30.42 | 7.34 | 97.39 | 0.00 | 0.00 | 0.00 |
March | 44.83 | 0.00 | 44.83 | 21.66 | 76.74 | 0.00 | 0.00 | 0.00 |
April | 63.66 | 0.39 | 63.27 | 44.10 | 58.88 | 0.00 | 0.00 | 0.00 |
May | 81.67 | 2.45 | 79.22 | 69.33 | 45.26 | 0.00 | 0.00 | 0.00 |
June | 85.95 | 5.75 | 80.20 | 81.63 | 32.12 | 0.00 | 0.00 | 0.00 |
July | 81.81 | 6.59 | 75.22 | 86.79 | 27.38 | 0.00 | 0.00 | 0.00 |
August | 66.31 | 1.99 | 64.32 | 72.80 | 25.72 | 0.00 | 0.00 | 0.00 |
September | 51.33 | 0.04 | 51.29 | 43.29 | 43.10 | 0.00 | 0.00 | 0.00 |
October | 35.14 | 0.00 | 35.14 | 19.17 | 63.94 | 0.00 | 0.00 | 0.00 |
November | 22.14 | 0.00 | 22.14 | 4.63 | 85.02 | 0.00 | 0.00 | 0.00 |
December | 16.61 | 0.00 | 16.61 | 0.71 | 109.24 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 50.05 | 1.44 | 48.60 | 37.90 | 64.60 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 16.61 | 0.00 | 16.61 | 0.71 | 25.72 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 85.95 | 6.59 | 80.20 | 86.79 | 112.32 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 62.25 | 18.52 | 43.73 | 29.06 | 202.31 | 0.00 | 0.00 | 0.00 |
February | 111.04 | 41.69 | 69.36 | 80.58 | 174.48 | 0.00 | 0.00 | 0.00 |
March | 155.56 | 52.59 | 102.96 | 135.03 | 139.40 | 0.00 | 0.00 | 0.00 |
April | 236.38 | 90.26 | 146.12 | 241.24 | 109.57 | 0.00 | 0.00 | 0.00 |
May | 304.75 | 124.07 | 180.68 | 337.68 | 86.85 | 0.00 | 0.00 | 0.00 |
June | 292.45 | 113.33 | 179.11 | 332.82 | 62.98 | 0.00 | 0.00 | 0.00 |
July | 361.52 | 189.97 | 171.55 | 446.54 | 53.90 | 0.00 | 0.00 | 0.00 |
August | 299.20 | 152.61 | 146.59 | 376.00 | 50.43 | 0.00 | 0.00 | 0.00 |
September | 244.45 | 117.59 | 126.86 | 285.90 | 79.34 | 0.00 | 0.00 | 0.00 |
October | 139.79 | 57.47 | 82.32 | 134.13 | 116.83 | 0.00 | 0.00 | 0.00 |
November | 69.23 | 19.68 | 49.55 | 42.62 | 154.83 | 0.00 | 0.00 | 0.00 |
December | 58.44 | 20.29 | 38.15 | 33.86 | 199.43 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 195.10 | 83.49 | 111.61 | 207.11 | 118.93 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 58.44 | 18.52 | 38.15 | 29.06 | 50.43 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 361.52 | 189.97 | 180.68 | 446.54 | 202.31 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 127.17 | 75.65 | 51.52 | 109.69 | 155.37 | 0.00 | 0.00 | 0.00 |
February | 195.69 | 121.42 | 74.28 | 192.20 | 136.85 | 0.00 | 0.00 | 0.00 |
March | 207.59 | 109.75 | 97.84 | 215.07 | 113.67 | 0.00 | 0.00 | 0.00 |
April | 219.35 | 94.14 | 125.21 | 241.50 | 91.06 | 0.00 | 0.00 | 0.00 |
May | 204.37 | 62.31 | 142.06 | 231.07 | 70.90 | 0.00 | 0.00 | 0.00 |
June | 184.91 | 49.49 | 135.42 | 216.01 | 51.07 | 0.00 | 0.00 | 0.00 |
July | 200.90 | 72.94 | 127.95 | 257.67 | 42.82 | 0.00 | 0.00 | 0.00 |
August | 214.17 | 98.41 | 115.76 | 281.92 | 40.10 | 0.00 | 0.00 | 0.00 |
September | 237.54 | 129.92 | 107.62 | 291.98 | 64.05 | 0.00 | 0.00 | 0.00 |
October | 214.88 | 131.56 | 83.32 | 238.61 | 94.86 | 0.00 | 0.00 | 0.00 |
November | 128.60 | 73.61 | 54.99 | 120.77 | 122.76 | 0.00 | 0.00 | 0.00 |
December | 134.59 | 87.04 | 47.55 | 128.08 | 154.73 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 189.05 | 92.00 | 97.05 | 210.45 | 94.65 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 127.17 | 49.49 | 47.55 | 109.69 | 40.10 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 237.54 | 131.56 | 142.06 | 291.98 | 155.37 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 136.86 | 0.00 | 136.86 | 3.41 | 875.25 | 0.00 | 0.00 | 0.00 |
February | 212.96 | 0.00 | 212.96 | 39.93 | 747.37 | 0.00 | 0.00 | 0.00 |
March | 313.79 | 0.00 | 313.79 | 141.35 | 579.72 | 0.00 | 0.00 | 0.00 |
April | 445.58 | 2.74 | 442.84 | 317.73 | 436.18 | 0.00 | 0.00 | 0.00 |
May | 571.66 | 17.16 | 554.50 | 513.73 | 332.97 | 0.00 | 0.00 | 0.00 |
June | 601.63 | 40.25 | 561.38 | 604.61 | 240.14 | 0.00 | 0.00 | 0.00 |
July | 572.63 | 46.10 | 526.53 | 653.30 | 202.40 | 0.00 | 0.00 | 0.00 |
August | 464.18 | 13.94 | 450.24 | 550.59 | 192.99 | 0.00 | 0.00 | 0.00 |
September | 359.27 | 0.27 | 359.00 | 325.82 | 312.86 | 0.00 | 0.00 | 0.00 |
October | 245.99 | 0.00 | 245.99 | 129.04 | 485.29 | 0.00 | 0.00 | 0.00 |
November | 154.95 | 0.00 | 154.95 | 24.07 | 665.65 | 0.00 | 0.00 | 0.00 |
December | 116.30 | 0.00 | 116.30 | 1.71 | 852.01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 350.33 | 10.11 | 340.21 | 276.91 | 492.36 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 116.30 | 0.00 | 116.30 | 1.71 | 192.99 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 601.63 | 46.10 | 561.38 | 653.30 | 875.25 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 136.86 | 0.00 | 136.86 | 2.99 | 892.63 | 0.00 | 0.00 | 0.00 |
February | 212.96 | 0.00 | 212.96 | 37.69 | 763.11 | 0.00 | 0.00 | 0.00 |
March | 313.79 | 0.00 | 313.79 | 136.86 | 593.91 | 0.00 | 0.00 | 0.00 |
April | 445.58 | 2.74 | 442.84 | 310.34 | 448.12 | 0.00 | 0.00 | 0.00 |
May | 571.66 | 17.16 | 554.50 | 503.91 | 343.11 | 0.00 | 0.00 | 0.00 |
June | 601.63 | 40.25 | 561.38 | 593.05 | 249.23 | 0.00 | 0.00 | 0.00 |
July | 572.63 | 46.10 | 526.53 | 641.66 | 211.44 | 0.00 | 0.00 | 0.00 |
August | 464.18 | 13.94 | 450.24 | 539.97 | 202.45 | 0.00 | 0.00 | 0.00 |
September | 359.27 | 0.27 | 359.00 | 318.71 | 324.39 | 0.00 | 0.00 | 0.00 |
October | 245.99 | 0.00 | 245.99 | 124.40 | 499.60 | 0.00 | 0.00 | 0.00 |
November | 154.95 | 0.00 | 154.95 | 22.35 | 682.39 | 0.00 | 0.00 | 0.00 |
December | 116.30 | 0.00 | 116.30 | 1.39 | 869.57 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 350.33 | 10.11 | 340.21 | 270.89 | 505.44 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 116.30 | 0.00 | 116.30 | 1.39 | 202.45 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 601.63 | 46.10 | 561.38 | 641.66 | 892.63 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.55 | 0.00 | 19.55 | 1.89 | 110.37 | 0.00 | 0.00 | 0.00 |
February | 30.42 | 0.00 | 30.42 | 10.08 | 96.39 | 0.00 | 0.00 | 0.00 |
March | 44.83 | 0.00 | 44.83 | 27.66 | 75.90 | 0.00 | 0.00 | 0.00 |
April | 63.66 | 0.39 | 63.27 | 55.91 | 58.86 | 0.00 | 0.00 | 0.00 |
May | 81.67 | 2.45 | 79.22 | 87.36 | 45.98 | 0.00 | 0.00 | 0.00 |
June | 85.95 | 5.75 | 80.20 | 101.68 | 34.17 | 0.00 | 0.00 | 0.00 |
July | 81.81 | 6.59 | 75.22 | 109.48 | 28.49 | 0.00 | 0.00 | 0.00 |
August | 66.31 | 1.99 | 64.32 | 93.72 | 26.88 | 0.00 | 0.00 | 0.00 |
September | 51.33 | 0.04 | 51.29 | 59.34 | 40.17 | 0.00 | 0.00 | 0.00 |
October | 35.14 | 0.00 | 35.14 | 25.84 | 62.75 | 0.00 | 0.00 | 0.00 |
November | 22.14 | 0.00 | 22.14 | 7.55 | 83.06 | 0.00 | 0.00 | 0.00 |
December | 16.61 | 0.00 | 16.61 | 1.66 | 107.28 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 50.05 | 1.44 | 48.60 | 48.75 | 64.04 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 16.61 | 0.00 | 16.61 | 1.66 | 26.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 85.95 | 6.59 | 80.20 | 109.48 | 110.37 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 116.83 | 29.28 | 87.55 | 50.96 | 397.42 | 0.00 | 0.00 | 0.00 |
February | 215.22 | 76.23 | 138.99 | 161.16 | 342.71 | 0.00 | 0.00 | 0.00 |
March | 322.56 | 116.96 | 205.59 | 307.48 | 272.37 | 0.00 | 0.00 | 0.00 |
April | 498.18 | 206.73 | 291.45 | 563.59 | 215.28 | 0.00 | 0.00 | 0.00 |
May | 530.45 | 184.69 | 345.75 | 639.26 | 173.44 | 0.00 | 0.00 | 0.00 |
June | 634.88 | 276.32 | 358.55 | 811.90 | 129.46 | 0.00 | 0.00 | 0.00 |
July | 592.09 | 266.20 | 325.89 | 801.52 | 106.25 | 0.00 | 0.00 | 0.00 |
August | 581.22 | 290.74 | 290.48 | 808.17 | 100.90 | 0.00 | 0.00 | 0.00 |
September | 430.43 | 198.86 | 231.56 | 552.20 | 147.81 | 0.00 | 0.00 | 0.00 |
October | 281.45 | 120.26 | 161.19 | 300.44 | 229.18 | 0.00 | 0.00 | 0.00 |
November | 137.73 | 39.00 | 98.73 | 95.33 | 303.31 | 0.00 | 0.00 | 0.00 |
December | 112.67 | 36.21 | 76.46 | 64.24 | 390.09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 371.83 | 153.80 | 218.03 | 431.06 | 233.51 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 112.67 | 29.28 | 76.46 | 50.96 | 100.90 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 634.88 | 290.74 | 358.55 | 811.90 | 397.42 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 86.71 | 51.58 | 35.13 | 82.12 | 100.99 | 0.00 | 0.00 | 0.00 |
February | 133.43 | 82.79 | 50.64 | 142.91 | 88.88 | 0.00 | 0.00 | 0.00 |
March | 141.54 | 74.84 | 66.71 | 160.67 | 73.65 | 0.00 | 0.00 | 0.00 |
April | 149.57 | 64.19 | 85.38 | 181.66 | 60.38 | 0.00 | 0.00 | 0.00 |
May | 139.35 | 42.48 | 96.87 | 176.71 | 47.92 | 0.00 | 0.00 | 0.00 |
June | 126.08 | 33.74 | 92.34 | 167.37 | 36.17 | 0.00 | 0.00 | 0.00 |
July | 136.98 | 49.74 | 87.24 | 197.56 | 29.89 | 0.00 | 0.00 | 0.00 |
August | 146.03 | 67.10 | 78.93 | 214.10 | 27.85 | 0.00 | 0.00 | 0.00 |
September | 161.97 | 88.59 | 73.38 | 219.56 | 39.97 | 0.00 | 0.00 | 0.00 |
October | 146.51 | 89.70 | 56.81 | 177.86 | 61.21 | 0.00 | 0.00 | 0.00 |
November | 87.68 | 50.19 | 37.49 | 91.48 | 78.73 | 0.00 | 0.00 | 0.00 |
December | 91.77 | 59.35 | 32.42 | 95.43 | 100.43 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 128.91 | 62.73 | 66.17 | 159.02 | 62.04 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 86.71 | 33.74 | 32.42 | 82.12 | 27.85 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 161.97 | 89.70 | 96.87 | 219.56 | 100.99 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 24.76 | 0.00 | 24.76 | 0.64 | 157.88 | 0.00 | 0.00 | 0.00 |
February | 38.53 | 0.00 | 38.53 | 7.22 | 134.78 | 0.00 | 0.00 | 0.00 |
March | 56.77 | 0.00 | 56.77 | 25.35 | 103.14 | 0.00 | 0.00 | 0.00 |
April | 80.62 | 0.50 | 80.12 | 57.44 | 76.49 | 0.00 | 0.00 | 0.00 |
May | 103.43 | 3.11 | 100.32 | 93.37 | 57.29 | 0.00 | 0.00 | 0.00 |
June | 108.85 | 7.28 | 101.57 | 110.32 | 39.98 | 0.00 | 0.00 | 0.00 |
July | 103.60 | 8.34 | 95.26 | 118.63 | 33.03 | 0.00 | 0.00 | 0.00 |
August | 83.98 | 2.52 | 81.46 | 99.51 | 31.23 | 0.00 | 0.00 | 0.00 |
September | 65.00 | 0.05 | 64.95 | 58.16 | 54.26 | 0.00 | 0.00 | 0.00 |
October | 44.51 | 0.00 | 44.51 | 23.06 | 85.58 | 0.00 | 0.00 | 0.00 |
November | 28.03 | 0.00 | 28.03 | 4.37 | 119.13 | 0.00 | 0.00 | 0.00 |
December | 21.04 | 0.00 | 21.04 | 0.28 | 153.68 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 63.38 | 1.83 | 61.55 | 50.13 | 86.98 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 21.04 | 0.00 | 21.04 | 0.28 | 31.23 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 108.85 | 8.34 | 101.57 | 118.63 | 157.88 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 22.15 | 0.00 | 22.15 | 0.57 | 141.25 | 0.00 | 0.00 | 0.00 |
February | 34.47 | 0.00 | 34.47 | 6.46 | 120.59 | 0.00 | 0.00 | 0.00 |
March | 50.79 | 0.00 | 50.79 | 22.68 | 92.28 | 0.00 | 0.00 | 0.00 |
April | 72.13 | 0.44 | 71.69 | 51.39 | 68.44 | 0.00 | 0.00 | 0.00 |
May | 92.54 | 2.78 | 89.76 | 83.54 | 51.26 | 0.00 | 0.00 | 0.00 |
June | 97.39 | 6.52 | 90.87 | 98.71 | 35.77 | 0.00 | 0.00 | 0.00 |
July | 92.70 | 7.46 | 85.23 | 106.14 | 29.55 | 0.00 | 0.00 | 0.00 |
August | 75.14 | 2.26 | 72.88 | 89.03 | 27.95 | 0.00 | 0.00 | 0.00 |
September | 58.16 | 0.04 | 58.11 | 52.04 | 48.55 | 0.00 | 0.00 | 0.00 |
October | 39.82 | 0.00 | 39.82 | 20.63 | 76.57 | 0.00 | 0.00 | 0.00 |
November | 25.08 | 0.00 | 25.08 | 3.91 | 106.59 | 0.00 | 0.00 | 0.00 |
December | 18.83 | 0.00 | 18.83 | 0.25 | 137.48 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 56.71 | 1.64 | 55.07 | 44.85 | 77.82 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 18.83 | 0.00 | 18.83 | 0.25 | 27.95 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 97.39 | 7.46 | 90.87 | 106.14 | 141.25 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 323.71 | 192.57 | 131.14 | 281.51 | 411.06 | 0.00 | 0.00 | 0.00 |
February | 498.14 | 309.07 | 189.07 | 498.45 | 355.06 | 0.00 | 0.00 | 0.00 |
March | 528.43 | 279.38 | 249.05 | 560.40 | 290.92 | 0.00 | 0.00 | 0.00 |
April | 558.37 | 239.64 | 318.74 | 632.92 | 230.26 | 0.00 | 0.00 | 0.00 |
May | 520.24 | 158.60 | 361.63 | 607.61 | 178.92 | 0.00 | 0.00 | 0.00 |
June | 470.70 | 125.98 | 344.72 | 570.52 | 128.11 | 0.00 | 0.00 | 0.00 |
July | 511.39 | 185.68 | 325.71 | 678.25 | 106.07 | 0.00 | 0.00 | 0.00 |
August | 545.19 | 250.51 | 294.68 | 740.65 | 98.54 | 0.00 | 0.00 | 0.00 |
September | 604.68 | 330.72 | 273.96 | 762.99 | 158.65 | 0.00 | 0.00 | 0.00 |
October | 546.98 | 334.88 | 212.10 | 623.60 | 240.15 | 0.00 | 0.00 | 0.00 |
November | 327.35 | 187.38 | 139.97 | 312.52 | 322.00 | 0.00 | 0.00 | 0.00 |
December | 342.61 | 221.56 | 121.05 | 331.35 | 409.01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 481.25 | 234.20 | 247.05 | 550.27 | 243.53 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 323.71 | 125.98 | 121.05 | 281.51 | 98.54 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 604.68 | 334.88 | 361.63 | 762.99 | 411.06 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.117461E+10 | 0.698752E+09 | 0.475859E+09 | 0.104383E+10 | 0.135284E+10 |
February | 0.163263E+10 | 0.101296E+10 | 0.619672E+09 | 0.165313E+10 | 0.107269E+10 |
March | 0.191745E+10 | 0.101376E+10 | 0.903689E+09 | 0.204887E+10 | 0.979813E+09 |
April | 0.196075E+10 | 0.841503E+09 | 0.111925E+10 | 0.224151E+10 | 0.754723E+09 |
May | 0.188772E+10 | 0.575512E+09 | 0.131221E+10 | 0.222245E+10 | 0.611206E+09 |
June | 0.165286E+10 | 0.442373E+09 | 0.121049E+10 | 0.201693E+10 | 0.428567E+09 |
July | 0.185562E+10 | 0.673775E+09 | 0.118184E+10 | 0.246254E+10 | 0.374888E+09 |
August | 0.197825E+10 | 0.908995E+09 | 0.106925E+10 | 0.267633E+10 | 0.353522E+09 |
September | 0.212334E+10 | 0.116132E+10 | 0.962015E+09 | 0.266284E+10 | 0.541634E+09 |
October | 0.198477E+10 | 0.121515E+10 | 0.769624E+09 | 0.227028E+10 | 0.820556E+09 |
November | 0.114951E+10 | 0.657987E+09 | 0.491521E+09 | 0.111119E+10 | 0.103316E+10 |
December | 0.124317E+10 | 0.803942E+09 | 0.439232E+09 | 0.121358E+10 | 0.135673E+10 |
Annual Sum or Average | 0.205607E+11 | 0.100060E+11 | 0.105547E+11 | 0.236235E+11 | 0.968034E+10 |
Minimum of Months | 0.114951E+10 | 0.442373E+09 | 0.439232E+09 | 0.104383E+10 | 0.353522E+09 |
Maximum of Months | 0.212334E+10 | 0.121515E+10 | 0.131221E+10 | 0.267633E+10 | 0.135673E+10 |
Report: WindowEnergyReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.330763E+10 | 0.196764E+10 | 0.133999E+10 | 0.290694E+10 | 0.386059E+10 |
February | 0.459739E+10 | 0.285244E+10 | 0.174495E+10 | 0.462119E+10 | 0.304213E+10 |
March | 0.539941E+10 | 0.285469E+10 | 0.254473E+10 | 0.573616E+10 | 0.276603E+10 |
April | 0.552134E+10 | 0.236962E+10 | 0.315172E+10 | 0.627970E+10 | 0.211825E+10 |
May | 0.531570E+10 | 0.162060E+10 | 0.369510E+10 | 0.622793E+10 | 0.170453E+10 |
June | 0.465435E+10 | 0.124569E+10 | 0.340866E+10 | 0.564962E+10 | 0.119103E+10 |
July | 0.522529E+10 | 0.189731E+10 | 0.332799E+10 | 0.691361E+10 | 0.103336E+10 |
August | 0.557061E+10 | 0.255967E+10 | 0.301095E+10 | 0.751878E+10 | 0.978136E+09 |
September | 0.597918E+10 | 0.327021E+10 | 0.270897E+10 | 0.747940E+10 | 0.150779E+10 |
October | 0.558898E+10 | 0.342177E+10 | 0.216721E+10 | 0.636492E+10 | 0.231425E+10 |
November | 0.323694E+10 | 0.185285E+10 | 0.138409E+10 | 0.310071E+10 | 0.293458E+10 |
December | 0.350069E+10 | 0.226385E+10 | 0.123685E+10 | 0.338991E+10 | 0.387365E+10 |
Annual Sum or Average | 0.578975E+11 | 0.281763E+11 | 0.297212E+11 | 0.661889E+11 | 0.273243E+11 |
Minimum of Months | 0.323694E+10 | 0.124569E+10 | 0.123685E+10 | 0.290694E+10 | 0.978136E+09 |
Maximum of Months | 0.597918E+10 | 0.342177E+10 | 0.369510E+10 | 0.751878E+10 | 0.387365E+10 |
Report: WindowEnergyReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.429680E+10 | 0.255608E+10 | 0.174072E+10 | 0.382177E+10 | 0.518628E+10 |
February | 0.597227E+10 | 0.370548E+10 | 0.226679E+10 | 0.609654E+10 | 0.406107E+10 |
March | 0.701415E+10 | 0.370840E+10 | 0.330575E+10 | 0.758525E+10 | 0.368397E+10 |
April | 0.717253E+10 | 0.307827E+10 | 0.409427E+10 | 0.832070E+10 | 0.281895E+10 |
May | 0.690540E+10 | 0.210526E+10 | 0.480014E+10 | 0.826718E+10 | 0.227924E+10 |
June | 0.604627E+10 | 0.161823E+10 | 0.442804E+10 | 0.750996E+10 | 0.160202E+10 |
July | 0.678795E+10 | 0.246471E+10 | 0.432325E+10 | 0.917904E+10 | 0.139091E+10 |
August | 0.723654E+10 | 0.332516E+10 | 0.391139E+10 | 0.997706E+10 | 0.131462E+10 |
September | 0.776730E+10 | 0.424819E+10 | 0.351911E+10 | 0.990836E+10 | 0.200422E+10 |
October | 0.726041E+10 | 0.444508E+10 | 0.281533E+10 | 0.841654E+10 | 0.307732E+10 |
November | 0.420497E+10 | 0.240696E+10 | 0.179801E+10 | 0.408863E+10 | 0.393692E+10 |
December | 0.454760E+10 | 0.294087E+10 | 0.160674E+10 | 0.445984E+10 | 0.520554E+10 |
Annual Sum or Average | 0.752122E+11 | 0.366027E+11 | 0.386095E+11 | 0.876309E+11 | 0.365611E+11 |
Minimum of Months | 0.420497E+10 | 0.161823E+10 | 0.160674E+10 | 0.382177E+10 | 0.131462E+10 |
Maximum of Months | 0.776730E+10 | 0.444508E+10 | 0.480014E+10 | 0.997706E+10 | 0.520554E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.232241E+09 | 0.138155E+09 | 94085984.75 | 0.208296E+09 | 0.274561E+09 |
February | 0.322800E+09 | 0.200280E+09 | 0.122520E+09 | 0.326668E+09 | 0.218256E+09 |
March | 0.379114E+09 | 0.200438E+09 | 0.178676E+09 | 0.402497E+09 | 0.201183E+09 |
April | 0.387675E+09 | 0.166380E+09 | 0.221296E+09 | 0.435352E+09 | 0.157782E+09 |
May | 0.373237E+09 | 0.113789E+09 | 0.259449E+09 | 0.427395E+09 | 0.128806E+09 |
June | 0.326802E+09 | 87464675.02 | 0.239337E+09 | 0.386355E+09 | 90187447.24 |
July | 0.366890E+09 | 0.133217E+09 | 0.233673E+09 | 0.473274E+09 | 79461120.31 |
August | 0.391136E+09 | 0.179724E+09 | 0.211412E+09 | 0.518801E+09 | 73988007.71 |
September | 0.419822E+09 | 0.229614E+09 | 0.190208E+09 | 0.521906E+09 | 0.112368E+09 |
October | 0.392424E+09 | 0.240255E+09 | 0.152169E+09 | 0.445498E+09 | 0.167668E+09 |
November | 0.227278E+09 | 0.130095E+09 | 97182520.67 | 0.220331E+09 | 0.209045E+09 |
December | 0.245797E+09 | 0.158953E+09 | 86844037.59 | 0.241202E+09 | 0.273751E+09 |
Annual Sum or Average | 0.406522E+10 | 0.197836E+10 | 0.208685E+10 | 0.460758E+10 | 0.198706E+10 |
Minimum of Months | 0.227278E+09 | 87464675.02 | 86844037.59 | 0.208296E+09 | 73988007.71 |
Maximum of Months | 0.419822E+09 | 0.240255E+09 | 0.259449E+09 | 0.521906E+09 | 0.274561E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.166731E+09 | 49599010.86 | 0.117132E+09 | 72627690.66 | 0.551803E+09 |
February | 0.268637E+09 | 0.100850E+09 | 0.167787E+09 | 0.186238E+09 | 0.432781E+09 |
March | 0.416644E+09 | 0.140864E+09 | 0.275781E+09 | 0.351897E+09 | 0.382582E+09 |
April | 0.612687E+09 | 0.233947E+09 | 0.378739E+09 | 0.622159E+09 | 0.287595E+09 |
May | 0.816233E+09 | 0.332303E+09 | 0.483930E+09 | 0.909759E+09 | 0.233507E+09 |
June | 0.758024E+09 | 0.293758E+09 | 0.464266E+09 | 0.870533E+09 | 0.163466E+09 |
July | 0.968308E+09 | 0.508828E+09 | 0.459480E+09 | 0.120479E+10 | 0.144442E+09 |
August | 0.801373E+09 | 0.408746E+09 | 0.392627E+09 | 0.101126E+10 | 0.136217E+09 |
September | 0.633602E+09 | 0.304787E+09 | 0.328815E+09 | 0.739075E+09 | 0.209524E+09 |
October | 0.374415E+09 | 0.153917E+09 | 0.220498E+09 | 0.349733E+09 | 0.322466E+09 |
November | 0.179442E+09 | 51011659.85 | 0.128430E+09 | 0.104159E+09 | 0.412072E+09 |
December | 0.156513E+09 | 54332932.01 | 0.102180E+09 | 84281337.62 | 0.547263E+09 |
Annual Sum or Average | 0.615261E+10 | 0.263294E+10 | 0.351966E+10 | 0.650651E+10 | 0.382372E+10 |
Minimum of Months | 0.156513E+09 | 49599010.86 | 0.102180E+09 | 72627690.66 | 0.136217E+09 |
Maximum of Months | 0.968308E+09 | 0.508828E+09 | 0.483930E+09 | 0.120479E+10 | 0.551803E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 52368466.14 | 0.00 | 52368466.14 | 2752224.61 | 0.304213E+09 |
February | 73600977.77 | 0.00 | 73600977.77 | 17363530.11 | 0.237994E+09 |
March | 0.120069E+09 | 391.48 | 0.120069E+09 | 57960197.56 | 0.207349E+09 |
April | 0.164999E+09 | 1015143.42 | 0.163984E+09 | 0.116274E+09 | 0.152869E+09 |
May | 0.218743E+09 | 6567927.74 | 0.212175E+09 | 0.190026E+09 | 0.120807E+09 |
June | 0.222782E+09 | 14903905.08 | 0.207878E+09 | 0.216672E+09 | 82777260.64 |
July | 0.219114E+09 | 17639237.34 | 0.201475E+09 | 0.237725E+09 | 72647424.13 |
August | 0.177614E+09 | 5334198.86 | 0.172280E+09 | 0.199081E+09 | 68479679.26 |
September | 0.133037E+09 | 99658.47 | 0.132938E+09 | 0.114826E+09 | 0.111685E+09 |
October | 94124964.10 | 0.00 | 94124964.10 | 51359475.77 | 0.173237E+09 |
November | 57376818.73 | 0.00 | 57376818.73 | 11575818.33 | 0.223776E+09 |
December | 44499694.93 | 0.00 | 44499694.93 | 1622266.97 | 0.296988E+09 |
Annual Sum or Average | 0.157833E+10 | 45560462.39 | 0.153277E+10 | 0.121724E+10 | 0.205282E+10 |
Minimum of Months | 44499694.93 | 0.00 | 44499694.93 | 1622266.97 | 68479679.26 |
Maximum of Months | 0.222782E+09 | 17639237.34 | 0.212175E+09 | 0.237725E+09 | 0.304213E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.166731E+09 | 49599010.86 | 0.117132E+09 | 77138890.88 | 0.546766E+09 |
February | 0.268637E+09 | 0.100850E+09 | 0.167787E+09 | 0.194655E+09 | 0.426199E+09 |
March | 0.416644E+09 | 0.140864E+09 | 0.275781E+09 | 0.363331E+09 | 0.376855E+09 |
April | 0.612687E+09 | 0.233947E+09 | 0.378739E+09 | 0.632536E+09 | 0.284174E+09 |
May | 0.816233E+09 | 0.332303E+09 | 0.483930E+09 | 0.916591E+09 | 0.231699E+09 |
June | 0.758024E+09 | 0.293758E+09 | 0.464266E+09 | 0.875712E+09 | 0.162222E+09 |
July | 0.968308E+09 | 0.508828E+09 | 0.459480E+09 | 0.121055E+10 | 0.143008E+09 |
August | 0.801373E+09 | 0.408746E+09 | 0.392627E+09 | 0.101868E+10 | 0.134201E+09 |
September | 0.633602E+09 | 0.304787E+09 | 0.328815E+09 | 0.748532E+09 | 0.205874E+09 |
October | 0.374415E+09 | 0.153917E+09 | 0.220498E+09 | 0.361361E+09 | 0.316486E+09 |
November | 0.179442E+09 | 51011659.85 | 0.128430E+09 | 0.109620E+09 | 0.406943E+09 |
December | 0.156513E+09 | 54332932.01 | 0.102180E+09 | 89737739.73 | 0.541215E+09 |
Annual Sum or Average | 0.615261E+10 | 0.263294E+10 | 0.351966E+10 | 0.659845E+10 | 0.377564E+10 |
Minimum of Months | 0.156513E+09 | 49599010.86 | 0.102180E+09 | 77138890.88 | 0.134201E+09 |
Maximum of Months | 0.968308E+09 | 0.508828E+09 | 0.483930E+09 | 0.121055E+10 | 0.546766E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.185756E+09 | 0.110502E+09 | 75253821.84 | 0.165881E+09 | 0.213142E+09 |
February | 0.258189E+09 | 0.160192E+09 | 97996810.64 | 0.257007E+09 | 0.181384E+09 |
March | 0.303231E+09 | 0.160319E+09 | 0.142912E+09 | 0.312665E+09 | 0.184251E+09 |
April | 0.310079E+09 | 0.133077E+09 | 0.177001E+09 | 0.338608E+09 | 0.147170E+09 |
May | 0.298531E+09 | 91012766.08 | 0.207518E+09 | 0.333549E+09 | 0.122207E+09 |
June | 0.261389E+09 | 69957827.29 | 0.191432E+09 | 0.300214E+09 | 89242842.14 |
July | 0.293453E+09 | 0.106552E+09 | 0.186901E+09 | 0.372059E+09 | 79802763.21 |
August | 0.312846E+09 | 0.143750E+09 | 0.169096E+09 | 0.407534E+09 | 76366525.99 |
September | 0.335791E+09 | 0.183654E+09 | 0.152136E+09 | 0.409158E+09 | 0.110069E+09 |
October | 0.313877E+09 | 0.192166E+09 | 0.121711E+09 | 0.345465E+09 | 0.161719E+09 |
November | 0.181786E+09 | 0.104056E+09 | 77730558.02 | 0.169862E+09 | 0.183231E+09 |
December | 0.196599E+09 | 0.127137E+09 | 69461416.07 | 0.190548E+09 | 0.219622E+09 |
Annual Sum or Average | 0.325153E+10 | 0.158238E+10 | 0.166915E+10 | 0.360255E+10 | 0.176821E+10 |
Minimum of Months | 0.181786E+09 | 69957827.29 | 69461416.07 | 0.165881E+09 | 76366525.99 |
Maximum of Months | 0.335791E+09 | 0.192166E+09 | 0.207518E+09 | 0.409158E+09 | 0.219622E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 41900326.30 | 0.00 | 41900326.30 | 1357923.88 | 0.259658E+09 |
February | 58888587.20 | 0.00 | 58888587.20 | 12027352.62 | 0.200410E+09 |
March | 96068061.79 | 313.23 | 96067748.57 | 44621358.87 | 0.172735E+09 |
April | 0.132017E+09 | 812222.38 | 0.131204E+09 | 94763316.46 | 0.124749E+09 |
May | 0.175017E+09 | 5255038.69 | 0.169762E+09 | 0.157224E+09 | 97056131.92 |
June | 0.178249E+09 | 11924704.54 | 0.166324E+09 | 0.179129E+09 | 65829956.66 |
July | 0.175314E+09 | 14113260.42 | 0.161201E+09 | 0.199363E+09 | 56205483.19 |
August | 0.142110E+09 | 4267924.75 | 0.137842E+09 | 0.167215E+09 | 53009554.26 |
September | 0.106444E+09 | 79737.34 | 0.106364E+09 | 95873385.14 | 88721832.00 |
October | 75309952.72 | 0.00 | 75309952.72 | 40111702.74 | 0.144080E+09 |
November | 45907539.48 | 0.00 | 45907539.48 | 7587569.98 | 0.191577E+09 |
December | 35604474.90 | 0.00 | 35604474.90 | 703712.71 | 0.253839E+09 |
Annual Sum or Average | 0.126283E+10 | 36453201.35 | 0.122638E+10 | 0.999978E+09 | 0.170787E+10 |
Minimum of Months | 35604474.90 | 0.00 | 35604474.90 | 703712.71 | 53009554.26 |
Maximum of Months | 0.178249E+09 | 14113260.42 | 0.169762E+09 | 0.199363E+09 | 0.259658E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.156474E+09 | 39212816.39 | 0.117262E+09 | 54978284.18 | 0.545826E+09 |
February | 0.260353E+09 | 92217704.15 | 0.168135E+09 | 0.167941E+09 | 0.424638E+09 |
March | 0.431998E+09 | 0.156650E+09 | 0.275348E+09 | 0.359397E+09 | 0.370539E+09 |
April | 0.645692E+09 | 0.267941E+09 | 0.377750E+09 | 0.653068E+09 | 0.276700E+09 |
May | 0.710424E+09 | 0.247357E+09 | 0.463067E+09 | 0.764676E+09 | 0.226640E+09 |
June | 0.822858E+09 | 0.358142E+09 | 0.464716E+09 | 0.952725E+09 | 0.157223E+09 |
July | 0.792984E+09 | 0.356523E+09 | 0.436461E+09 | 0.963614E+09 | 0.132810E+09 |
August | 0.778426E+09 | 0.389384E+09 | 0.389042E+09 | 0.972446E+09 | 0.127392E+09 |
September | 0.557872E+09 | 0.257746E+09 | 0.300126E+09 | 0.626274E+09 | 0.200616E+09 |
October | 0.376944E+09 | 0.161062E+09 | 0.215882E+09 | 0.346838E+09 | 0.314688E+09 |
November | 0.178516E+09 | 50551984.52 | 0.127964E+09 | 98198519.12 | 0.406014E+09 |
December | 0.150900E+09 | 48501623.07 | 0.102398E+09 | 69293877.53 | 0.537368E+09 |
Annual Sum or Average | 0.586344E+10 | 0.242529E+10 | 0.343815E+10 | 0.602945E+10 | 0.372045E+10 |
Minimum of Months | 0.150900E+09 | 39212816.39 | 0.102398E+09 | 54978284.18 | 0.127392E+09 |
Maximum of Months | 0.822858E+09 | 0.389384E+09 | 0.464716E+09 | 0.972446E+09 | 0.545826E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.232241E+09 | 0.138155E+09 | 94085984.75 | 0.208227E+09 | 0.274154E+09 |
February | 0.322800E+09 | 0.200280E+09 | 0.122520E+09 | 0.326016E+09 | 0.217666E+09 |
March | 0.379114E+09 | 0.200438E+09 | 0.178676E+09 | 0.400364E+09 | 0.200595E+09 |
April | 0.387675E+09 | 0.166380E+09 | 0.221296E+09 | 0.432163E+09 | 0.157164E+09 |
May | 0.373237E+09 | 0.113789E+09 | 0.259449E+09 | 0.426869E+09 | 0.127089E+09 |
June | 0.326802E+09 | 87464675.02 | 0.239337E+09 | 0.383096E+09 | 89390932.62 |
July | 0.366890E+09 | 0.133217E+09 | 0.233673E+09 | 0.473263E+09 | 77278275.37 |
August | 0.391136E+09 | 0.179724E+09 | 0.211412E+09 | 0.517146E+09 | 72823270.79 |
September | 0.419822E+09 | 0.229614E+09 | 0.190208E+09 | 0.521425E+09 | 0.110438E+09 |
October | 0.392424E+09 | 0.240255E+09 | 0.152169E+09 | 0.444036E+09 | 0.166855E+09 |
November | 0.227278E+09 | 0.130095E+09 | 97182520.67 | 0.220003E+09 | 0.208662E+09 |
December | 0.245797E+09 | 0.158953E+09 | 86844037.59 | 0.241106E+09 | 0.273263E+09 |
Annual Sum or Average | 0.406522E+10 | 0.197836E+10 | 0.208685E+10 | 0.459371E+10 | 0.197538E+10 |
Minimum of Months | 0.227278E+09 | 87464675.02 | 86844037.59 | 0.208227E+09 | 72823270.79 |
Maximum of Months | 0.419822E+09 | 0.240255E+09 | 0.259449E+09 | 0.521425E+09 | 0.274154E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 52368466.14 | 0.00 | 52368466.14 | 2656998.83 | 0.304024E+09 |
February | 73600977.77 | 0.00 | 73600977.77 | 17028968.58 | 0.237483E+09 |
March | 0.120069E+09 | 391.48 | 0.120069E+09 | 56000882.73 | 0.207045E+09 |
April | 0.164999E+09 | 1015143.42 | 0.163984E+09 | 0.112970E+09 | 0.152942E+09 |
May | 0.218743E+09 | 6567927.74 | 0.212175E+09 | 0.189181E+09 | 0.119311E+09 |
June | 0.222782E+09 | 14903905.08 | 0.207878E+09 | 0.212749E+09 | 82128548.71 |
July | 0.219114E+09 | 17639237.34 | 0.201475E+09 | 0.237646E+09 | 70687814.16 |
August | 0.177614E+09 | 5334198.86 | 0.172280E+09 | 0.196703E+09 | 67301037.25 |
September | 0.133037E+09 | 99658.47 | 0.132938E+09 | 0.113918E+09 | 0.109928E+09 |
October | 94124964.10 | 0.00 | 94124964.10 | 49720508.87 | 0.172494E+09 |
November | 57376818.73 | 0.00 | 57376818.73 | 11137495.53 | 0.223255E+09 |
December | 44499694.93 | 0.00 | 44499694.93 | 1450172.89 | 0.296537E+09 |
Annual Sum or Average | 0.157833E+10 | 45560462.39 | 0.153277E+10 | 0.120116E+10 | 0.204314E+10 |
Minimum of Months | 44499694.93 | 0.00 | 44499694.93 | 1450172.89 | 67301037.25 |
Maximum of Months | 0.222782E+09 | 17639237.34 | 0.212175E+09 | 0.237646E+09 | 0.304024E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.156474E+09 | 39212816.39 | 0.117262E+09 | 57162662.71 | 0.538747E+09 |
February | 0.260353E+09 | 92217704.15 | 0.168135E+09 | 0.173756E+09 | 0.414861E+09 |
March | 0.431998E+09 | 0.156650E+09 | 0.275348E+09 | 0.369914E+09 | 0.364066E+09 |
April | 0.645692E+09 | 0.267941E+09 | 0.377750E+09 | 0.662045E+09 | 0.273108E+09 |
May | 0.710424E+09 | 0.247357E+09 | 0.463067E+09 | 0.770680E+09 | 0.224716E+09 |
June | 0.822858E+09 | 0.358142E+09 | 0.464716E+09 | 0.956864E+09 | 0.156070E+09 |
July | 0.792984E+09 | 0.356523E+09 | 0.436461E+09 | 0.968839E+09 | 0.131359E+09 |
August | 0.778426E+09 | 0.389384E+09 | 0.389042E+09 | 0.979024E+09 | 0.125449E+09 |
September | 0.557872E+09 | 0.257746E+09 | 0.300126E+09 | 0.634822E+09 | 0.196714E+09 |
October | 0.376944E+09 | 0.161062E+09 | 0.215882E+09 | 0.357518E+09 | 0.308074E+09 |
November | 0.178516E+09 | 50551984.52 | 0.127964E+09 | 0.102013E+09 | 0.399111E+09 |
December | 0.150900E+09 | 48501623.07 | 0.102398E+09 | 72191728.56 | 0.528698E+09 |
Annual Sum or Average | 0.586344E+10 | 0.242529E+10 | 0.343815E+10 | 0.610483E+10 | 0.366097E+10 |
Minimum of Months | 0.150900E+09 | 39212816.39 | 0.102398E+09 | 57162662.71 | 0.125449E+09 |
Maximum of Months | 0.822858E+09 | 0.389384E+09 | 0.464716E+09 | 0.979024E+09 | 0.538747E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 66321358.09 | 0.00 | 66321358.09 | 1954156.99 | 0.418783E+09 |
February | 93210994.38 | 0.00 | 93210994.38 | 18972889.68 | 0.321998E+09 |
March | 0.152060E+09 | 495.79 | 0.152060E+09 | 71973924.38 | 0.272611E+09 |
April | 0.208961E+09 | 1285615.09 | 0.207675E+09 | 0.155117E+09 | 0.195237E+09 |
May | 0.277024E+09 | 8317866.07 | 0.268706E+09 | 0.258600E+09 | 0.150811E+09 |
June | 0.282139E+09 | 18874855.40 | 0.263264E+09 | 0.295004E+09 | 0.101614E+09 |
July | 0.277494E+09 | 22338981.12 | 0.255155E+09 | 0.326827E+09 | 87108737.21 |
August | 0.224937E+09 | 6755426.29 | 0.218182E+09 | 0.273416E+09 | 83130471.26 |
September | 0.168483E+09 | 126211.16 | 0.168357E+09 | 0.156836E+09 | 0.138920E+09 |
October | 0.119203E+09 | 0.00 | 0.119203E+09 | 65680122.67 | 0.226022E+09 |
November | 72664120.65 | 0.00 | 72664120.65 | 12497468.90 | 0.304659E+09 |
December | 56356055.86 | 0.00 | 56356055.86 | 963586.24 | 0.408542E+09 |
Annual Sum or Average | 0.199885E+10 | 57699450.91 | 0.194115E+10 | 0.163784E+10 | 0.270944E+10 |
Minimum of Months | 56356055.86 | 0.00 | 56356055.86 | 963586.24 | 83130471.26 |
Maximum of Months | 0.282139E+09 | 22338981.12 | 0.268706E+09 | 0.326827E+09 | 0.418783E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 24448798.74 | 0.00 | 24448798.74 | 720383.18 | 0.154381E+09 |
February | 34361432.09 | 0.00 | 34361432.09 | 6994192.74 | 0.118702E+09 |
March | 56055618.56 | 182.77 | 56055435.79 | 26532568.73 | 0.100496E+09 |
April | 77031535.71 | 473930.95 | 76557604.76 | 57182465.32 | 71972532.25 |
May | 0.102122E+09 | 3066309.85 | 99056130.07 | 95330662.08 | 55595067.61 |
June | 0.104008E+09 | 6958053.25 | 97050039.40 | 0.108751E+09 | 37458972.71 |
July | 0.102296E+09 | 8235073.42 | 94060683.56 | 0.120482E+09 | 32111887.43 |
August | 82921087.56 | 2490329.85 | 80430757.71 | 0.100792E+09 | 30645333.87 |
September | 62109917.75 | 46526.66 | 62063391.09 | 57816167.77 | 51211624.26 |
October | 43943282.55 | 0.00 | 43943282.55 | 24212412.82 | 83321018.22 |
November | 26787003.65 | 0.00 | 26787003.65 | 4607084.52 | 0.112310E+09 |
December | 20775175.71 | 0.00 | 20775175.71 | 355217.79 | 0.150606E+09 |
Annual Sum or Average | 0.736860E+09 | 21270406.75 | 0.715590E+09 | 0.603776E+09 | 0.998810E+09 |
Minimum of Months | 20775175.71 | 0.00 | 20775175.71 | 355217.79 | 30645333.87 |
Maximum of Months | 0.104008E+09 | 8235073.42 | 99056130.07 | 0.120482E+09 | 0.154381E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.108363E+09 | 64462737.30 | 43900141.34 | 95391505.02 | 0.136102E+09 |
February | 0.150617E+09 | 93449879.22 | 57167513.00 | 0.152522E+09 | 0.106196E+09 |
March | 0.176893E+09 | 93523610.87 | 83369497.89 | 0.190066E+09 | 95897309.22 |
April | 0.180888E+09 | 77632025.32 | 0.103256E+09 | 0.208302E+09 | 73185250.55 |
May | 0.174151E+09 | 53093294.10 | 0.121058E+09 | 0.207250E+09 | 58590467.31 |
June | 0.152484E+09 | 40810664.91 | 0.111674E+09 | 0.188735E+09 | 40449336.17 |
July | 0.171189E+09 | 62158441.70 | 0.109031E+09 | 0.231142E+09 | 34758210.46 |
August | 0.182502E+09 | 83858412.51 | 98643882.84 | 0.251346E+09 | 32572681.11 |
September | 0.195887E+09 | 0.107137E+09 | 88750420.26 | 0.250073E+09 | 50624486.41 |
October | 0.183104E+09 | 0.112102E+09 | 71001357.22 | 0.211326E+09 | 79054710.78 |
November | 0.106047E+09 | 60701964.75 | 45344972.53 | 0.102575E+09 | 0.102765E+09 |
December | 0.114688E+09 | 74166869.16 | 40521077.98 | 0.111977E+09 | 0.135691E+09 |
Annual Sum or Average | 0.189681E+10 | 0.923097E+09 | 0.973717E+09 | 0.220071E+10 | 0.945886E+09 |
Minimum of Months | 0.106047E+09 | 40810664.91 | 40521077.98 | 95391505.02 | 32572681.11 |
Maximum of Months | 0.195887E+09 | 0.112102E+09 | 0.121058E+09 | 0.251346E+09 | 0.136102E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.294119E+09 | 0.174965E+09 | 0.119154E+09 | 0.258912E+09 | 0.369409E+09 |
February | 0.408806E+09 | 0.253642E+09 | 0.155164E+09 | 0.413977E+09 | 0.288237E+09 |
March | 0.480124E+09 | 0.253842E+09 | 0.226282E+09 | 0.515879E+09 | 0.260285E+09 |
April | 0.490966E+09 | 0.210709E+09 | 0.280257E+09 | 0.565375E+09 | 0.198640E+09 |
May | 0.472682E+09 | 0.144106E+09 | 0.328576E+09 | 0.562519E+09 | 0.159027E+09 |
June | 0.413874E+09 | 0.110768E+09 | 0.303105E+09 | 0.512265E+09 | 0.109788E+09 |
July | 0.464643E+09 | 0.168711E+09 | 0.295932E+09 | 0.627368E+09 | 94340892.83 |
August | 0.495349E+09 | 0.227609E+09 | 0.267740E+09 | 0.682204E+09 | 88408889.60 |
September | 0.531678E+09 | 0.290791E+09 | 0.240887E+09 | 0.678749E+09 | 0.137405E+09 |
October | 0.496980E+09 | 0.304268E+09 | 0.192712E+09 | 0.573583E+09 | 0.214571E+09 |
November | 0.287833E+09 | 0.164758E+09 | 0.123076E+09 | 0.278410E+09 | 0.278926E+09 |
December | 0.311287E+09 | 0.201304E+09 | 0.109982E+09 | 0.303928E+09 | 0.368293E+09 |
Annual Sum or Average | 0.514834E+10 | 0.250547E+10 | 0.264287E+10 | 0.597317E+10 | 0.256733E+10 |
Minimum of Months | 0.287833E+09 | 0.110768E+09 | 0.109982E+09 | 0.258912E+09 | 88408889.60 |
Maximum of Months | 0.531678E+09 | 0.304268E+09 | 0.328576E+09 | 0.682204E+09 | 0.369409E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.232241E+09 | 0.138155E+09 | 94085984.75 | 0.208552E+09 | 0.272374E+09 |
February | 0.322800E+09 | 0.200280E+09 | 0.122520E+09 | 0.326023E+09 | 0.216604E+09 |
March | 0.379114E+09 | 0.200438E+09 | 0.178676E+09 | 0.400523E+09 | 0.200085E+09 |
April | 0.387675E+09 | 0.166380E+09 | 0.221296E+09 | 0.431167E+09 | 0.158094E+09 |
May | 0.373237E+09 | 0.113789E+09 | 0.259449E+09 | 0.421675E+09 | 0.129605E+09 |
June | 0.326802E+09 | 87464675.02 | 0.239337E+09 | 0.380289E+09 | 90966425.55 |
July | 0.366890E+09 | 0.133217E+09 | 0.233673E+09 | 0.466753E+09 | 80440562.58 |
August | 0.391136E+09 | 0.179724E+09 | 0.211412E+09 | 0.513105E+09 | 74647952.92 |
September | 0.419822E+09 | 0.229614E+09 | 0.190208E+09 | 0.518011E+09 | 0.112604E+09 |
October | 0.392424E+09 | 0.240255E+09 | 0.152169E+09 | 0.443097E+09 | 0.166553E+09 |
November | 0.227278E+09 | 0.130095E+09 | 97182520.67 | 0.220315E+09 | 0.206760E+09 |
December | 0.245797E+09 | 0.158953E+09 | 86844037.59 | 0.241378E+09 | 0.270934E+09 |
Annual Sum or Average | 0.406522E+10 | 0.197836E+10 | 0.208685E+10 | 0.457089E+10 | 0.197967E+10 |
Minimum of Months | 0.227278E+09 | 87464675.02 | 86844037.59 | 0.208552E+09 | 74647952.92 |
Maximum of Months | 0.419822E+09 | 0.240255E+09 | 0.259449E+09 | 0.518011E+09 | 0.272374E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.166731E+09 | 49599010.86 | 0.117132E+09 | 73478298.50 | 0.546353E+09 |
February | 0.268637E+09 | 0.100850E+09 | 0.167787E+09 | 0.185857E+09 | 0.428601E+09 |
March | 0.416644E+09 | 0.140864E+09 | 0.275781E+09 | 0.349258E+09 | 0.379587E+09 |
April | 0.612687E+09 | 0.233947E+09 | 0.378739E+09 | 0.614442E+09 | 0.287700E+09 |
May | 0.816233E+09 | 0.332303E+09 | 0.483930E+09 | 0.897822E+09 | 0.234474E+09 |
June | 0.758024E+09 | 0.293758E+09 | 0.464266E+09 | 0.857983E+09 | 0.164456E+09 |
July | 0.968308E+09 | 0.508828E+09 | 0.459480E+09 | 0.119071E+10 | 0.145749E+09 |
August | 0.801373E+09 | 0.408746E+09 | 0.392627E+09 | 0.999965E+09 | 0.137099E+09 |
September | 0.633602E+09 | 0.304787E+09 | 0.328815E+09 | 0.731695E+09 | 0.209520E+09 |
October | 0.374415E+09 | 0.153917E+09 | 0.220498E+09 | 0.346652E+09 | 0.319581E+09 |
November | 0.179442E+09 | 51011659.85 | 0.128430E+09 | 0.104639E+09 | 0.406424E+09 |
December | 0.156513E+09 | 54332932.01 | 0.102180E+09 | 84792570.53 | 0.539888E+09 |
Annual Sum or Average | 0.615261E+10 | 0.263294E+10 | 0.351966E+10 | 0.643729E+10 | 0.379943E+10 |
Minimum of Months | 0.156513E+09 | 49599010.86 | 0.102180E+09 | 73478298.50 | 0.137099E+09 |
Maximum of Months | 0.968308E+09 | 0.508828E+09 | 0.483930E+09 | 0.119071E+10 | 0.546353E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 52368466.14 | 0.00 | 52368466.14 | 2978619.47 | 0.300851E+09 |
February | 73600977.77 | 0.00 | 73600977.77 | 17758828.29 | 0.235610E+09 |
March | 0.120069E+09 | 391.48 | 0.120069E+09 | 58007023.19 | 0.205542E+09 |
April | 0.164999E+09 | 1015143.42 | 0.163984E+09 | 0.114303E+09 | 0.152623E+09 |
May | 0.218743E+09 | 6567927.74 | 0.212175E+09 | 0.185699E+09 | 0.121219E+09 |
June | 0.222782E+09 | 14903905.08 | 0.207878E+09 | 0.211591E+09 | 83267178.89 |
July | 0.219114E+09 | 17639237.34 | 0.201475E+09 | 0.232445E+09 | 73339943.84 |
August | 0.177614E+09 | 5334198.86 | 0.172280E+09 | 0.194996E+09 | 68885674.79 |
September | 0.133037E+09 | 99658.47 | 0.132938E+09 | 0.112214E+09 | 0.111714E+09 |
October | 94124964.10 | 0.00 | 94124964.10 | 51345532.91 | 0.171246E+09 |
November | 57376818.73 | 0.00 | 57376818.73 | 12002466.83 | 0.220384E+09 |
December | 44499694.93 | 0.00 | 44499694.93 | 1892947.76 | 0.292593E+09 |
Annual Sum or Average | 0.157833E+10 | 45560462.39 | 0.153277E+10 | 0.119523E+10 | 0.203727E+10 |
Minimum of Months | 44499694.93 | 0.00 | 44499694.93 | 1892947.76 | 68885674.79 |
Maximum of Months | 0.222782E+09 | 17639237.34 | 0.212175E+09 | 0.232445E+09 | 0.300851E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.166731E+09 | 49599010.86 | 0.117132E+09 | 77827501.27 | 0.541869E+09 |
February | 0.268637E+09 | 0.100850E+09 | 0.167787E+09 | 0.194929E+09 | 0.422103E+09 |
March | 0.416644E+09 | 0.140864E+09 | 0.275781E+09 | 0.361673E+09 | 0.373359E+09 |
April | 0.612687E+09 | 0.233947E+09 | 0.378739E+09 | 0.625290E+09 | 0.283999E+09 |
May | 0.816233E+09 | 0.332303E+09 | 0.483930E+09 | 0.904450E+09 | 0.232620E+09 |
June | 0.758024E+09 | 0.293758E+09 | 0.464266E+09 | 0.862666E+09 | 0.163241E+09 |
July | 0.968308E+09 | 0.508828E+09 | 0.459480E+09 | 0.119600E+10 | 0.144358E+09 |
August | 0.801373E+09 | 0.408746E+09 | 0.392627E+09 | 0.100707E+10 | 0.135065E+09 |
September | 0.633602E+09 | 0.304787E+09 | 0.328815E+09 | 0.741060E+09 | 0.205642E+09 |
October | 0.374415E+09 | 0.153917E+09 | 0.220498E+09 | 0.359247E+09 | 0.312904E+09 |
November | 0.179442E+09 | 51011659.85 | 0.128430E+09 | 0.110482E+09 | 0.401330E+09 |
December | 0.156513E+09 | 54332932.01 | 0.102180E+09 | 90677835.58 | 0.534153E+09 |
Annual Sum or Average | 0.615261E+10 | 0.263294E+10 | 0.351966E+10 | 0.653138E+10 | 0.375064E+10 |
Minimum of Months | 0.156513E+09 | 49599010.86 | 0.102180E+09 | 77827501.27 | 0.135065E+09 |
Maximum of Months | 0.968308E+09 | 0.508828E+09 | 0.483930E+09 | 0.119600E+10 | 0.541869E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.340604E+09 | 0.202618E+09 | 0.137986E+09 | 0.293784E+09 | 0.416143E+09 |
February | 0.473418E+09 | 0.293730E+09 | 0.179688E+09 | 0.464981E+09 | 0.331078E+09 |
March | 0.556007E+09 | 0.293962E+09 | 0.262045E+09 | 0.576035E+09 | 0.304463E+09 |
April | 0.568563E+09 | 0.244012E+09 | 0.324552E+09 | 0.625966E+09 | 0.236016E+09 |
May | 0.547388E+09 | 0.166882E+09 | 0.380507E+09 | 0.618895E+09 | 0.189905E+09 |
June | 0.479286E+09 | 0.128275E+09 | 0.351011E+09 | 0.559898E+09 | 0.132369E+09 |
July | 0.538079E+09 | 0.195375E+09 | 0.342704E+09 | 0.690148E+09 | 0.114683E+09 |
August | 0.573638E+09 | 0.263582E+09 | 0.310056E+09 | 0.755106E+09 | 0.107398E+09 |
September | 0.615709E+09 | 0.336751E+09 | 0.278959E+09 | 0.756801E+09 | 0.166021E+09 |
October | 0.575528E+09 | 0.352358E+09 | 0.223170E+09 | 0.639083E+09 | 0.254078E+09 |
November | 0.333325E+09 | 0.190797E+09 | 0.142527E+09 | 0.313043E+09 | 0.318185E+09 |
December | 0.360485E+09 | 0.233120E+09 | 0.127365E+09 | 0.343054E+09 | 0.414428E+09 |
Annual Sum or Average | 0.596203E+10 | 0.290146E+10 | 0.306057E+10 | 0.663680E+10 | 0.298477E+10 |
Minimum of Months | 0.333325E+09 | 0.128275E+09 | 0.127365E+09 | 0.293784E+09 | 0.107398E+09 |
Maximum of Months | 0.615709E+09 | 0.352358E+09 | 0.380507E+09 | 0.756801E+09 | 0.416143E+09 |
Report: WindowEnergyReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.366565E+09 | 0.00 | 0.366565E+09 | 9129162.55 | 0.234427E+10 |
February | 0.515187E+09 | 0.00 | 0.515187E+09 | 96590080.30 | 0.180803E+10 |
March | 0.840452E+09 | 2740.29 | 0.840450E+09 | 0.378602E+09 | 0.155272E+10 |
April | 0.115495E+10 | 7105734.80 | 0.114784E+10 | 0.823555E+09 | 0.113058E+10 |
May | 0.153114E+10 | 45973752.97 | 0.148517E+10 | 0.137598E+10 | 0.891823E+09 |
June | 0.155941E+10 | 0.104323E+09 | 0.145509E+10 | 0.156716E+10 | 0.622449E+09 |
July | 0.153374E+10 | 0.123470E+09 | 0.141027E+10 | 0.174980E+10 | 0.542100E+09 |
August | 0.124325E+10 | 37337977.86 | 0.120591E+10 | 0.147470E+10 | 0.516894E+09 |
September | 0.931226E+09 | 697582.85 | 0.930528E+09 | 0.844538E+09 | 0.810922E+09 |
October | 0.658850E+09 | 0.00 | 0.658850E+09 | 0.345612E+09 | 0.129981E+10 |
November | 0.401623E+09 | 0.00 | 0.401623E+09 | 62377569.25 | 0.172536E+10 |
December | 0.311486E+09 | 0.00 | 0.311486E+09 | 4573642.85 | 0.228203E+10 |
Annual Sum or Average | 0.110479E+11 | 0.318911E+09 | 0.107290E+11 | 0.873262E+10 | 0.155270E+11 |
Minimum of Months | 0.311486E+09 | 0.00 | 0.311486E+09 | 4573642.85 | 0.516894E+09 |
Maximum of Months | 0.155941E+10 | 0.123470E+09 | 0.148517E+10 | 0.174980E+10 | 0.234427E+10 |
Report: WindowEnergyReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.366565E+09 | 0.00 | 0.366565E+09 | 7997344.56 | 0.239081E+10 |
February | 0.515187E+09 | 0.00 | 0.515187E+09 | 91182762.62 | 0.184612E+10 |
March | 0.840452E+09 | 2740.29 | 0.840450E+09 | 0.366566E+09 | 0.159072E+10 |
April | 0.115495E+10 | 7105734.80 | 0.114784E+10 | 0.804409E+09 | 0.116152E+10 |
May | 0.153114E+10 | 45973752.97 | 0.148517E+10 | 0.134968E+10 | 0.918981E+09 |
June | 0.155941E+10 | 0.104323E+09 | 0.145509E+10 | 0.153718E+10 | 0.646010E+09 |
July | 0.153374E+10 | 0.123470E+09 | 0.141027E+10 | 0.171862E+10 | 0.566321E+09 |
August | 0.124325E+10 | 37337977.86 | 0.120591E+10 | 0.144625E+10 | 0.542237E+09 |
September | 0.931226E+09 | 697582.85 | 0.930528E+09 | 0.826104E+09 | 0.840821E+09 |
October | 0.658850E+09 | 0.00 | 0.658850E+09 | 0.333181E+09 | 0.133812E+10 |
November | 0.401623E+09 | 0.00 | 0.401623E+09 | 57920830.71 | 0.176874E+10 |
December | 0.311486E+09 | 0.00 | 0.311486E+09 | 3720636.73 | 0.232905E+10 |
Annual Sum or Average | 0.110479E+11 | 0.318911E+09 | 0.107290E+11 | 0.854281E+10 | 0.159394E+11 |
Minimum of Months | 0.311486E+09 | 0.00 | 0.311486E+09 | 3720636.73 | 0.542237E+09 |
Maximum of Months | 0.155941E+10 | 0.123470E+09 | 0.148517E+10 | 0.171862E+10 | 0.239081E+10 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 52368466.14 | 0.00 | 52368466.14 | 5053191.05 | 0.295625E+09 |
February | 73600977.77 | 0.00 | 73600977.77 | 24376946.81 | 0.233191E+09 |
March | 0.120069E+09 | 391.48 | 0.120069E+09 | 74074588.17 | 0.203292E+09 |
April | 0.164999E+09 | 1015143.42 | 0.163984E+09 | 0.144909E+09 | 0.152553E+09 |
May | 0.218743E+09 | 6567927.74 | 0.212175E+09 | 0.233985E+09 | 0.123140E+09 |
June | 0.222782E+09 | 14903905.08 | 0.207878E+09 | 0.263545E+09 | 88563851.89 |
July | 0.219114E+09 | 17639237.34 | 0.201475E+09 | 0.293227E+09 | 76303143.75 |
August | 0.177614E+09 | 5334198.86 | 0.172280E+09 | 0.251027E+09 | 71984216.94 |
September | 0.133037E+09 | 99658.47 | 0.132938E+09 | 0.153811E+09 | 0.104116E+09 |
October | 94124964.10 | 0.00 | 94124964.10 | 69201123.62 | 0.168069E+09 |
November | 57376818.73 | 0.00 | 57376818.73 | 19574825.41 | 0.215282E+09 |
December | 44499694.93 | 0.00 | 44499694.93 | 4437612.63 | 0.287341E+09 |
Annual Sum or Average | 0.157833E+10 | 45560462.39 | 0.153277E+10 | 0.153722E+10 | 0.201946E+10 |
Minimum of Months | 44499694.93 | 0.00 | 44499694.93 | 4437612.63 | 71984216.94 |
Maximum of Months | 0.222782E+09 | 17639237.34 | 0.212175E+09 | 0.293227E+09 | 0.295625E+09 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.312927E+09 | 78420063.57 | 0.234506E+09 | 0.136496E+09 | 0.106445E+10 |
February | 0.520668E+09 | 0.184422E+09 | 0.336246E+09 | 0.389884E+09 | 0.829080E+09 |
March | 0.863935E+09 | 0.313278E+09 | 0.550657E+09 | 0.823560E+09 | 0.729504E+09 |
April | 0.129129E+10 | 0.535845E+09 | 0.755447E+09 | 0.146083E+10 | 0.558018E+09 |
May | 0.142075E+10 | 0.494678E+09 | 0.926068E+09 | 0.171219E+10 | 0.464553E+09 |
June | 0.164560E+10 | 0.716233E+09 | 0.929366E+09 | 0.210444E+10 | 0.335562E+09 |
July | 0.158586E+10 | 0.712996E+09 | 0.872859E+09 | 0.214679E+10 | 0.284571E+09 |
August | 0.155674E+10 | 0.778713E+09 | 0.778028E+09 | 0.216459E+10 | 0.270255E+09 |
September | 0.111566E+10 | 0.515455E+09 | 0.600209E+09 | 0.143131E+10 | 0.383128E+09 |
October | 0.753835E+09 | 0.322102E+09 | 0.431733E+09 | 0.804698E+09 | 0.613828E+09 |
November | 0.357007E+09 | 0.101097E+09 | 0.255910E+09 | 0.247104E+09 | 0.786192E+09 |
December | 0.301778E+09 | 96996357.68 | 0.204782E+09 | 0.172049E+09 | 0.104480E+10 |
Annual Sum or Average | 0.117260E+11 | 0.485024E+10 | 0.687581E+10 | 0.135939E+11 | 0.736395E+10 |
Minimum of Months | 0.301778E+09 | 78420063.57 | 0.204782E+09 | 0.136496E+09 | 0.270255E+09 |
Maximum of Months | 0.164560E+10 | 0.778713E+09 | 0.929366E+09 | 0.216459E+10 | 0.106445E+10 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.232241E+09 | 0.138155E+09 | 94085984.75 | 0.219957E+09 | 0.270488E+09 |
February | 0.322800E+09 | 0.200280E+09 | 0.122520E+09 | 0.345723E+09 | 0.215007E+09 |
March | 0.379114E+09 | 0.200438E+09 | 0.178676E+09 | 0.430347E+09 | 0.197255E+09 |
April | 0.387675E+09 | 0.166380E+09 | 0.221296E+09 | 0.470853E+09 | 0.156515E+09 |
May | 0.373237E+09 | 0.113789E+09 | 0.259449E+09 | 0.473294E+09 | 0.128351E+09 |
June | 0.326802E+09 | 87464675.02 | 0.239337E+09 | 0.433811E+09 | 93764017.23 |
July | 0.366890E+09 | 0.133217E+09 | 0.233673E+09 | 0.529153E+09 | 80052276.48 |
August | 0.391136E+09 | 0.179724E+09 | 0.211412E+09 | 0.573453E+09 | 74580703.43 |
September | 0.419822E+09 | 0.229614E+09 | 0.190208E+09 | 0.569093E+09 | 0.103599E+09 |
October | 0.392424E+09 | 0.240255E+09 | 0.152169E+09 | 0.476388E+09 | 0.163941E+09 |
November | 0.227278E+09 | 0.130095E+09 | 97182520.67 | 0.237108E+09 | 0.204070E+09 |
December | 0.245797E+09 | 0.158953E+09 | 86844037.59 | 0.255604E+09 | 0.268998E+09 |
Annual Sum or Average | 0.406522E+10 | 0.197836E+10 | 0.208685E+10 | 0.501478E+10 | 0.195662E+10 |
Minimum of Months | 0.227278E+09 | 87464675.02 | 86844037.59 | 0.219957E+09 | 74580703.43 |
Maximum of Months | 0.419822E+09 | 0.240255E+09 | 0.259449E+09 | 0.573453E+09 | 0.270488E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 66321358.09 | 0.00 | 66321358.09 | 1707186.76 | 0.422874E+09 |
February | 93210994.38 | 0.00 | 93210994.38 | 17469578.67 | 0.326056E+09 |
March | 0.152060E+09 | 495.79 | 0.152060E+09 | 67884478.78 | 0.276253E+09 |
April | 0.208961E+09 | 1285615.09 | 0.207675E+09 | 0.148884E+09 | 0.198271E+09 |
May | 0.277024E+09 | 8317866.07 | 0.268706E+09 | 0.250083E+09 | 0.153459E+09 |
June | 0.282139E+09 | 18874855.40 | 0.263264E+09 | 0.285961E+09 | 0.103636E+09 |
July | 0.277494E+09 | 22338981.12 | 0.255155E+09 | 0.317750E+09 | 88456962.55 |
August | 0.224937E+09 | 6755426.29 | 0.218182E+09 | 0.266521E+09 | 83657654.05 |
September | 0.168483E+09 | 126211.16 | 0.168357E+09 | 0.150752E+09 | 0.140652E+09 |
October | 0.119203E+09 | 0.00 | 0.119203E+09 | 61770887.17 | 0.229219E+09 |
November | 72664120.65 | 0.00 | 72664120.65 | 11321823.76 | 0.308797E+09 |
December | 56356055.86 | 0.00 | 56356055.86 | 746615.37 | 0.411607E+09 |
Annual Sum or Average | 0.199885E+10 | 57699450.91 | 0.194115E+10 | 0.158085E+10 | 0.274294E+10 |
Minimum of Months | 56356055.86 | 0.00 | 56356055.86 | 746615.37 | 83657654.05 |
Maximum of Months | 0.282139E+09 | 22338981.12 | 0.268706E+09 | 0.317750E+09 | 0.422874E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 59337970.38 | 0.00 | 59337970.38 | 1527426.46 | 0.378322E+09 |
February | 83396229.85 | 0.00 | 83396229.85 | 15630098.23 | 0.291722E+09 |
March | 0.136049E+09 | 443.59 | 0.136048E+09 | 60736500.38 | 0.247164E+09 |
April | 0.186958E+09 | 1150244.69 | 0.185808E+09 | 0.133207E+09 | 0.177394E+09 |
May | 0.247854E+09 | 7442026.29 | 0.240412E+09 | 0.223750E+09 | 0.137300E+09 |
June | 0.252431E+09 | 16887404.64 | 0.235543E+09 | 0.255850E+09 | 92723730.41 |
July | 0.248275E+09 | 19986771.05 | 0.228288E+09 | 0.284292E+09 | 79142779.56 |
August | 0.201252E+09 | 6044105.50 | 0.195208E+09 | 0.238457E+09 | 74848820.06 |
September | 0.150743E+09 | 112921.60 | 0.150630E+09 | 0.134879E+09 | 0.125842E+09 |
October | 0.106652E+09 | 0.00 | 0.106652E+09 | 55266646.80 | 0.205083E+09 |
November | 65012864.06 | 0.00 | 65012864.06 | 10129678.62 | 0.276271E+09 |
December | 50421976.71 | 0.00 | 50421976.71 | 667999.60 | 0.368216E+09 |
Annual Sum or Average | 0.178838E+10 | 51623917.35 | 0.173676E+10 | 0.141439E+10 | 0.245403E+10 |
Minimum of Months | 50421976.71 | 0.00 | 50421976.71 | 667999.60 | 74848820.06 |
Maximum of Months | 0.252431E+09 | 19986771.05 | 0.240412E+09 | 0.284292E+09 | 0.378322E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.867026E+09 | 0.515775E+09 | 0.351251E+09 | 0.753983E+09 | 0.110099E+10 |
February | 0.120511E+10 | 0.747705E+09 | 0.457405E+09 | 0.120585E+10 | 0.858952E+09 |
March | 0.141535E+10 | 0.748295E+09 | 0.667051E+09 | 0.150098E+10 | 0.779198E+09 |
April | 0.144731E+10 | 0.621144E+09 | 0.826163E+09 | 0.164052E+10 | 0.596846E+09 |
May | 0.139341E+10 | 0.424807E+09 | 0.968600E+09 | 0.162743E+10 | 0.479215E+09 |
June | 0.122005E+10 | 0.326532E+09 | 0.893516E+09 | 0.147879E+10 | 0.332051E+09 |
July | 0.136971E+10 | 0.497338E+09 | 0.872371E+09 | 0.181663E+10 | 0.284100E+09 |
August | 0.146023E+10 | 0.670963E+09 | 0.789263E+09 | 0.198377E+10 | 0.263935E+09 |
September | 0.156732E+10 | 0.857216E+09 | 0.710104E+09 | 0.197768E+10 | 0.411228E+09 |
October | 0.146504E+10 | 0.896945E+09 | 0.568092E+09 | 0.167025E+10 | 0.643213E+09 |
November | 0.848496E+09 | 0.485685E+09 | 0.362811E+09 | 0.810061E+09 | 0.834617E+09 |
December | 0.917634E+09 | 0.593419E+09 | 0.324215E+09 | 0.887498E+09 | 0.109550E+10 |
Annual Sum or Average | 0.151767E+11 | 0.738582E+10 | 0.779084E+10 | 0.173535E+11 | 0.767984E+10 |
Minimum of Months | 0.848496E+09 | 0.326532E+09 | 0.324215E+09 | 0.753983E+09 | 0.263935E+09 |
Maximum of Months | 0.156732E+10 | 0.896945E+09 | 0.968600E+09 | 0.198377E+10 | 0.110099E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 389.72 | 505.09 | 438.55 | 260.88 | 177.67 | 0.00 | 0.00 |
February | 683.34 | 443.41 | 674.87 | 418.72 | 256.15 | 0.00 | 0.00 |
March | 764.96 | 365.82 | 715.89 | 378.50 | 337.40 | 0.00 | 0.00 |
April | 864.78 | 291.17 | 756.46 | 324.65 | 431.81 | 0.00 | 0.00 |
May | 829.77 | 228.20 | 704.79 | 214.87 | 489.92 | 0.00 | 0.00 |
June | 778.14 | 165.34 | 637.68 | 170.67 | 467.01 | 0.00 | 0.00 |
July | 919.41 | 139.97 | 692.81 | 251.56 | 441.25 | 0.00 | 0.00 |
August | 999.23 | 131.99 | 738.59 | 339.38 | 399.21 | 0.00 | 0.00 |
September | 1027.33 | 208.96 | 819.19 | 448.04 | 371.15 | 0.00 | 0.00 |
October | 847.63 | 306.36 | 741.03 | 453.68 | 287.34 | 0.00 | 0.00 |
November | 428.70 | 398.60 | 443.48 | 253.85 | 189.63 | 0.00 | 0.00 |
December | 453.10 | 506.55 | 464.15 | 300.16 | 163.99 | 0.00 | 0.00 |
Annual Sum or Average | 749.10 | 306.96 | 651.97 | 317.29 | 334.69 | 0.00 | 0.00 |
Minimum of Months | 389.72 | 131.99 | 438.55 | 170.67 | 163.99 | 0.00 | 0.00 |
Maximum of Months | 1027.33 | 506.55 | 819.19 | 453.68 | 489.92 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1085.33 | 1441.38 | 1234.93 | 734.63 | 500.29 | 0.00 | 0.00 |
February | 1910.22 | 1257.49 | 1900.38 | 1179.08 | 721.29 | 0.00 | 0.00 |
March | 2141.64 | 1032.72 | 2015.91 | 1065.82 | 950.09 | 0.00 | 0.00 |
April | 2422.72 | 817.23 | 2130.15 | 914.20 | 1215.94 | 0.00 | 0.00 |
May | 2325.24 | 636.40 | 1984.66 | 605.06 | 1379.59 | 0.00 | 0.00 |
June | 2179.64 | 459.50 | 1795.66 | 480.59 | 1315.07 | 0.00 | 0.00 |
July | 2581.25 | 385.81 | 1950.90 | 708.37 | 1242.53 | 0.00 | 0.00 |
August | 2807.19 | 365.19 | 2079.83 | 955.67 | 1124.16 | 0.00 | 0.00 |
September | 2885.57 | 581.71 | 2306.78 | 1261.66 | 1045.13 | 0.00 | 0.00 |
October | 2376.39 | 864.04 | 2086.69 | 1277.54 | 809.14 | 0.00 | 0.00 |
November | 1196.26 | 1132.17 | 1248.82 | 714.83 | 533.99 | 0.00 | 0.00 |
December | 1265.65 | 1446.25 | 1307.01 | 845.22 | 461.79 | 0.00 | 0.00 |
Annual Sum or Average | 2098.84 | 866.45 | 1835.92 | 893.47 | 942.45 | 0.00 | 0.00 |
Minimum of Months | 1085.33 | 365.19 | 1234.93 | 480.59 | 461.79 | 0.00 | 0.00 |
Maximum of Months | 2885.57 | 1446.25 | 2306.78 | 1277.54 | 1379.59 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1426.89 | 1936.34 | 1604.24 | 954.33 | 649.91 | 0.00 | 0.00 |
February | 2520.06 | 1678.68 | 2468.70 | 1531.69 | 937.00 | 0.00 | 0.00 |
March | 2832.01 | 1375.44 | 2618.78 | 1384.56 | 1234.22 | 0.00 | 0.00 |
April | 3210.15 | 1087.56 | 2767.18 | 1187.60 | 1579.58 | 0.00 | 0.00 |
May | 3086.61 | 850.97 | 2578.18 | 786.01 | 1792.17 | 0.00 | 0.00 |
June | 2897.36 | 618.06 | 2332.66 | 624.32 | 1708.35 | 0.00 | 0.00 |
July | 3427.06 | 519.31 | 2534.33 | 920.22 | 1614.12 | 0.00 | 0.00 |
August | 3725.01 | 490.82 | 2701.82 | 1241.47 | 1460.35 | 0.00 | 0.00 |
September | 3822.67 | 773.23 | 2996.64 | 1638.96 | 1357.68 | 0.00 | 0.00 |
October | 3142.38 | 1148.94 | 2710.73 | 1659.60 | 1051.12 | 0.00 | 0.00 |
November | 1577.40 | 1518.88 | 1622.29 | 928.61 | 693.68 | 0.00 | 0.00 |
December | 1665.11 | 1943.53 | 1697.88 | 1097.99 | 599.89 | 0.00 | 0.00 |
Annual Sum or Average | 2778.76 | 1159.34 | 2384.96 | 1160.66 | 1224.30 | 0.00 | 0.00 |
Minimum of Months | 1426.89 | 490.82 | 1604.24 | 624.32 | 599.89 | 0.00 | 0.00 |
Maximum of Months | 3822.67 | 1943.53 | 2996.64 | 1659.60 | 1792.17 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 96.88 | 300.52 | 148.96 | 70.10 | 78.86 | 0.00 | 0.00 |
February | 205.19 | 262.29 | 244.48 | 124.48 | 120.00 | 0.00 | 0.00 |
March | 279.02 | 215.31 | 297.10 | 127.43 | 169.67 | 0.00 | 0.00 |
April | 406.44 | 170.28 | 385.94 | 154.45 | 231.50 | 0.00 | 0.00 |
May | 498.16 | 134.20 | 444.10 | 166.55 | 277.55 | 0.00 | 0.00 |
June | 484.20 | 97.15 | 418.53 | 147.08 | 271.45 | 0.00 | 0.00 |
July | 625.92 | 83.00 | 498.51 | 239.71 | 258.79 | 0.00 | 0.00 |
August | 570.91 | 78.13 | 445.23 | 219.71 | 225.52 | 0.00 | 0.00 |
September | 485.63 | 123.33 | 406.41 | 206.17 | 200.24 | 0.00 | 0.00 |
October | 294.66 | 180.75 | 286.30 | 147.17 | 139.14 | 0.00 | 0.00 |
November | 121.22 | 235.66 | 156.91 | 69.87 | 87.04 | 0.00 | 0.00 |
December | 114.34 | 299.35 | 150.21 | 79.63 | 70.57 | 0.00 | 0.00 |
Annual Sum or Average | 349.44 | 181.28 | 324.01 | 146.22 | 177.78 | 0.00 | 0.00 |
Minimum of Months | 96.88 | 78.13 | 148.96 | 69.87 | 70.57 | 0.00 | 0.00 |
Maximum of Months | 625.92 | 300.52 | 498.51 | 239.71 | 277.55 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 26.58 | 314.47 | 81.80 | 18.52 | 63.28 | 0.00 | 0.00 |
February | 84.50 | 271.41 | 141.47 | 41.69 | 99.78 | 0.00 | 0.00 |
March | 155.55 | 216.37 | 200.39 | 52.59 | 147.79 | 0.00 | 0.00 |
April | 287.99 | 167.71 | 300.03 | 90.65 | 209.38 | 0.00 | 0.00 |
May | 412.06 | 130.51 | 386.42 | 126.52 | 259.90 | 0.00 | 0.00 |
June | 419.90 | 92.97 | 378.40 | 119.08 | 259.31 | 0.00 | 0.00 |
July | 539.42 | 79.21 | 443.33 | 196.56 | 246.77 | 0.00 | 0.00 |
August | 453.76 | 74.77 | 365.51 | 154.60 | 210.91 | 0.00 | 0.00 |
September | 332.47 | 121.90 | 295.77 | 117.63 | 178.15 | 0.00 | 0.00 |
October | 152.79 | 181.54 | 174.93 | 57.47 | 117.47 | 0.00 | 0.00 |
November | 45.01 | 241.58 | 91.37 | 19.68 | 71.68 | 0.00 | 0.00 |
December | 31.61 | 310.45 | 75.05 | 20.29 | 54.76 | 0.00 | 0.00 |
Annual Sum or Average | 246.17 | 183.15 | 245.15 | 84.93 | 160.21 | 0.00 | 0.00 |
Minimum of Months | 26.58 | 74.77 | 75.05 | 18.52 | 54.76 | 0.00 | 0.00 |
Maximum of Months | 539.42 | 314.47 | 443.33 | 196.56 | 259.90 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 61.93 | 79.58 | 69.35 | 41.26 | 28.10 | 0.00 | 0.00 |
February | 106.24 | 74.98 | 106.72 | 66.22 | 40.51 | 0.00 | 0.00 |
March | 116.74 | 68.79 | 113.21 | 59.86 | 53.36 | 0.00 | 0.00 |
April | 130.64 | 56.78 | 119.63 | 51.34 | 68.29 | 0.00 | 0.00 |
May | 124.53 | 45.63 | 111.46 | 33.98 | 77.48 | 0.00 | 0.00 |
June | 115.82 | 34.43 | 100.84 | 26.99 | 73.85 | 0.00 | 0.00 |
July | 138.91 | 29.79 | 109.56 | 39.78 | 69.78 | 0.00 | 0.00 |
August | 152.16 | 28.51 | 116.80 | 53.67 | 63.13 | 0.00 | 0.00 |
September | 157.85 | 42.47 | 129.55 | 70.85 | 58.69 | 0.00 | 0.00 |
October | 128.98 | 60.38 | 117.19 | 71.75 | 45.44 | 0.00 | 0.00 |
November | 65.53 | 70.69 | 70.13 | 40.14 | 29.99 | 0.00 | 0.00 |
December | 71.14 | 82.00 | 73.40 | 47.47 | 25.93 | 0.00 | 0.00 |
Annual Sum or Average | 114.24 | 56.07 | 103.11 | 50.18 | 52.93 | 0.00 | 0.00 |
Minimum of Months | 61.93 | 28.51 | 69.35 | 26.99 | 25.93 | 0.00 | 0.00 |
Maximum of Months | 157.85 | 82.00 | 129.55 | 71.75 | 77.48 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.51 | 96.95 | 15.64 | 0.00 | 15.64 | 0.00 | 0.00 |
February | 4.97 | 82.84 | 24.34 | 0.00 | 24.34 | 0.00 | 0.00 |
March | 16.66 | 64.49 | 35.87 | 0.00 | 35.87 | 0.00 | 0.00 |
April | 36.56 | 48.13 | 50.93 | 0.31 | 50.62 | 0.00 | 0.00 |
May | 58.70 | 36.24 | 65.34 | 1.96 | 63.38 | 0.00 | 0.00 |
June | 69.11 | 25.40 | 68.77 | 4.60 | 64.17 | 0.00 | 0.00 |
July | 74.43 | 20.98 | 65.45 | 5.27 | 60.19 | 0.00 | 0.00 |
August | 62.43 | 19.79 | 53.06 | 1.59 | 51.46 | 0.00 | 0.00 |
September | 36.99 | 34.23 | 41.07 | 0.03 | 41.04 | 0.00 | 0.00 |
October | 14.98 | 53.79 | 28.12 | 0.00 | 28.12 | 0.00 | 0.00 |
November | 2.93 | 73.91 | 17.71 | 0.00 | 17.71 | 0.00 | 0.00 |
December | 0.26 | 94.77 | 13.29 | 0.00 | 13.29 | 0.00 | 0.00 |
Annual Sum or Average | 31.71 | 54.16 | 40.04 | 1.16 | 38.89 | 0.00 | 0.00 |
Minimum of Months | 0.26 | 19.79 | 13.29 | 0.00 | 13.29 | 0.00 | 0.00 |
Maximum of Months | 74.43 | 96.95 | 68.77 | 5.27 | 64.17 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 91.03 | 298.91 | 145.13 | 66.22 | 78.91 | 0.00 | 0.00 |
February | 198.79 | 260.11 | 241.05 | 120.91 | 120.15 | 0.00 | 0.00 |
March | 281.61 | 211.18 | 302.83 | 133.32 | 169.51 | 0.00 | 0.00 |
April | 415.88 | 164.58 | 398.68 | 167.56 | 231.11 | 0.00 | 0.00 |
May | 443.29 | 130.49 | 404.59 | 134.84 | 269.76 | 0.00 | 0.00 |
June | 513.90 | 93.69 | 443.54 | 171.92 | 271.63 | 0.00 | 0.00 |
July | 535.11 | 77.08 | 433.05 | 182.85 | 250.20 | 0.00 | 0.00 |
August | 554.57 | 73.17 | 436.66 | 212.48 | 224.18 | 0.00 | 0.00 |
September | 441.38 | 118.60 | 377.20 | 188.02 | 189.17 | 0.00 | 0.00 |
October | 293.80 | 178.31 | 287.25 | 149.83 | 137.41 | 0.00 | 0.00 |
November | 119.45 | 233.83 | 156.56 | 69.69 | 86.86 | 0.00 | 0.00 |
December | 109.88 | 296.65 | 148.11 | 77.45 | 70.65 | 0.00 | 0.00 |
Annual Sum or Average | 333.90 | 177.65 | 314.84 | 139.64 | 175.20 | 0.00 | 0.00 |
Minimum of Months | 91.03 | 73.17 | 145.13 | 66.22 | 70.65 | 0.00 | 0.00 |
Maximum of Months | 554.57 | 298.91 | 443.54 | 212.48 | 271.63 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 18.52 | 310.84 | 77.97 | 14.64 | 63.33 | 0.00 | 0.00 |
February | 74.06 | 264.85 | 138.04 | 38.12 | 99.92 | 0.00 | 0.00 |
March | 155.39 | 209.60 | 206.12 | 58.49 | 147.63 | 0.00 | 0.00 |
April | 296.43 | 161.80 | 312.77 | 103.76 | 209.00 | 0.00 | 0.00 |
May | 357.56 | 127.64 | 346.91 | 94.80 | 252.11 | 0.00 | 0.00 |
June | 450.63 | 91.29 | 403.41 | 143.92 | 259.49 | 0.00 | 0.00 |
July | 449.65 | 74.63 | 377.87 | 139.70 | 238.18 | 0.00 | 0.00 |
August | 438.57 | 71.56 | 356.94 | 147.37 | 209.57 | 0.00 | 0.00 |
September | 287.06 | 116.50 | 266.55 | 99.48 | 167.08 | 0.00 | 0.00 |
October | 149.46 | 176.84 | 175.88 | 60.13 | 115.74 | 0.00 | 0.00 |
November | 41.16 | 237.62 | 91.01 | 19.50 | 71.51 | 0.00 | 0.00 |
December | 23.69 | 304.30 | 72.95 | 18.11 | 54.85 | 0.00 | 0.00 |
Annual Sum or Average | 229.34 | 178.55 | 235.98 | 78.35 | 157.63 | 0.00 | 0.00 |
Minimum of Months | 18.52 | 71.56 | 72.95 | 14.64 | 54.85 | 0.00 | 0.00 |
Maximum of Months | 450.63 | 310.84 | 403.41 | 147.37 | 259.49 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 117.64 | 387.09 | 184.16 | 89.39 | 94.77 | 0.00 | 0.00 |
February | 233.07 | 333.38 | 283.98 | 143.47 | 140.50 | 0.00 | 0.00 |
March | 297.71 | 269.65 | 323.00 | 129.69 | 193.31 | 0.00 | 0.00 |
April | 379.99 | 207.55 | 369.54 | 111.92 | 257.62 | 0.00 | 0.00 |
May | 417.78 | 156.55 | 383.06 | 77.88 | 305.18 | 0.00 | 0.00 |
June | 424.14 | 109.54 | 367.48 | 68.45 | 299.03 | 0.00 | 0.00 |
July | 485.61 | 90.79 | 379.19 | 97.61 | 281.58 | 0.00 | 0.00 |
August | 486.98 | 86.37 | 368.02 | 119.74 | 248.28 | 0.00 | 0.00 |
September | 440.79 | 145.53 | 369.66 | 153.59 | 216.07 | 0.00 | 0.00 |
October | 323.54 | 222.05 | 314.83 | 155.45 | 159.37 | 0.00 | 0.00 |
November | 145.86 | 300.40 | 190.33 | 86.98 | 103.35 | 0.00 | 0.00 |
December | 141.89 | 383.04 | 187.84 | 102.85 | 84.99 | 0.00 | 0.00 |
Annual Sum or Average | 325.08 | 223.80 | 310.15 | 111.22 | 198.93 | 0.00 | 0.00 |
Minimum of Months | 117.64 | 86.37 | 184.16 | 68.45 | 84.99 | 0.00 | 0.00 |
Maximum of Months | 486.98 | 387.09 | 383.06 | 155.45 | 305.18 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 97.48 | 297.86 | 148.96 | 70.10 | 78.86 | 0.00 | 0.00 |
February | 204.97 | 260.08 | 244.48 | 124.48 | 120.00 | 0.00 | 0.00 |
March | 277.34 | 213.83 | 297.10 | 127.43 | 169.67 | 0.00 | 0.00 |
April | 401.81 | 170.40 | 385.94 | 154.45 | 231.50 | 0.00 | 0.00 |
May | 491.49 | 134.78 | 444.10 | 166.55 | 277.55 | 0.00 | 0.00 |
June | 476.97 | 97.78 | 418.53 | 147.08 | 271.45 | 0.00 | 0.00 |
July | 618.16 | 83.78 | 498.51 | 239.71 | 258.79 | 0.00 | 0.00 |
August | 564.52 | 78.66 | 445.23 | 219.71 | 225.52 | 0.00 | 0.00 |
September | 481.24 | 123.38 | 406.41 | 206.17 | 200.24 | 0.00 | 0.00 |
October | 292.69 | 179.33 | 286.30 | 147.17 | 139.14 | 0.00 | 0.00 |
November | 121.55 | 232.75 | 156.91 | 69.87 | 87.04 | 0.00 | 0.00 |
December | 114.89 | 295.83 | 150.21 | 79.63 | 70.57 | 0.00 | 0.00 |
Annual Sum or Average | 346.14 | 180.32 | 324.01 | 146.22 | 177.78 | 0.00 | 0.00 |
Minimum of Months | 97.48 | 78.66 | 148.96 | 69.87 | 70.57 | 0.00 | 0.00 |
Maximum of Months | 618.16 | 297.86 | 498.51 | 239.71 | 277.55 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 27.04 | 311.51 | 81.80 | 18.52 | 63.28 | 0.00 | 0.00 |
February | 84.90 | 268.85 | 141.47 | 41.69 | 99.78 | 0.00 | 0.00 |
March | 154.91 | 214.36 | 200.39 | 52.59 | 147.79 | 0.00 | 0.00 |
April | 284.37 | 167.49 | 300.03 | 90.65 | 209.38 | 0.00 | 0.00 |
May | 405.90 | 130.99 | 386.42 | 126.52 | 259.90 | 0.00 | 0.00 |
June | 412.92 | 93.57 | 378.40 | 119.08 | 259.31 | 0.00 | 0.00 |
July | 532.02 | 79.97 | 443.33 | 196.56 | 246.77 | 0.00 | 0.00 |
August | 447.90 | 75.25 | 365.51 | 154.60 | 210.91 | 0.00 | 0.00 |
September | 328.52 | 121.76 | 295.77 | 117.63 | 178.15 | 0.00 | 0.00 |
October | 151.97 | 179.44 | 174.93 | 57.47 | 117.47 | 0.00 | 0.00 |
November | 45.61 | 238.21 | 91.37 | 19.68 | 71.68 | 0.00 | 0.00 |
December | 32.21 | 306.32 | 75.05 | 20.29 | 54.76 | 0.00 | 0.00 |
Annual Sum or Average | 243.37 | 181.89 | 245.15 | 84.93 | 160.21 | 0.00 | 0.00 |
Minimum of Months | 27.04 | 75.25 | 75.05 | 18.52 | 54.76 | 0.00 | 0.00 |
Maximum of Months | 532.02 | 311.51 | 443.33 | 196.56 | 259.90 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 109.69 | 155.37 | 127.17 | 75.65 | 51.52 | 0.00 | 0.00 |
February | 192.20 | 136.85 | 195.69 | 121.42 | 74.28 | 0.00 | 0.00 |
March | 215.07 | 113.67 | 207.59 | 109.75 | 97.84 | 0.00 | 0.00 |
April | 241.50 | 91.06 | 219.35 | 94.14 | 125.21 | 0.00 | 0.00 |
May | 231.07 | 70.90 | 204.37 | 62.31 | 142.06 | 0.00 | 0.00 |
June | 216.01 | 51.07 | 184.91 | 49.49 | 135.42 | 0.00 | 0.00 |
July | 257.67 | 42.82 | 200.90 | 72.94 | 127.95 | 0.00 | 0.00 |
August | 281.92 | 40.10 | 214.17 | 98.41 | 115.76 | 0.00 | 0.00 |
September | 291.98 | 64.05 | 237.54 | 129.92 | 107.62 | 0.00 | 0.00 |
October | 238.61 | 94.86 | 214.88 | 131.56 | 83.32 | 0.00 | 0.00 |
November | 120.77 | 122.76 | 128.60 | 73.61 | 54.99 | 0.00 | 0.00 |
December | 128.08 | 154.73 | 134.59 | 87.04 | 47.55 | 0.00 | 0.00 |
Annual Sum or Average | 210.45 | 94.65 | 189.05 | 92.00 | 97.05 | 0.00 | 0.00 |
Minimum of Months | 109.69 | 40.10 | 127.17 | 49.49 | 47.55 | 0.00 | 0.00 |
Maximum of Months | 291.98 | 155.37 | 237.54 | 131.56 | 142.06 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3.41 | 875.25 | 136.86 | 0.00 | 136.86 | 0.00 | 0.00 |
February | 39.93 | 747.37 | 212.96 | 0.00 | 212.96 | 0.00 | 0.00 |
March | 141.35 | 579.72 | 313.79 | 0.00 | 313.79 | 0.00 | 0.00 |
April | 317.73 | 436.18 | 445.58 | 2.74 | 442.84 | 0.00 | 0.00 |
May | 513.73 | 332.97 | 571.66 | 17.16 | 554.50 | 0.00 | 0.00 |
June | 604.61 | 240.14 | 601.63 | 40.25 | 561.38 | 0.00 | 0.00 |
July | 653.30 | 202.40 | 572.63 | 46.10 | 526.53 | 0.00 | 0.00 |
August | 550.59 | 192.99 | 464.18 | 13.94 | 450.24 | 0.00 | 0.00 |
September | 325.82 | 312.86 | 359.27 | 0.27 | 359.00 | 0.00 | 0.00 |
October | 129.04 | 485.29 | 245.99 | 0.00 | 245.99 | 0.00 | 0.00 |
November | 24.07 | 665.65 | 154.95 | 0.00 | 154.95 | 0.00 | 0.00 |
December | 1.71 | 852.01 | 116.30 | 0.00 | 116.30 | 0.00 | 0.00 |
Annual Sum or Average | 276.91 | 492.36 | 350.33 | 10.11 | 340.21 | 0.00 | 0.00 |
Minimum of Months | 1.71 | 192.99 | 116.30 | 0.00 | 116.30 | 0.00 | 0.00 |
Maximum of Months | 653.30 | 875.25 | 601.63 | 46.10 | 561.38 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2.99 | 892.63 | 136.86 | 0.00 | 136.86 | 0.00 | 0.00 |
February | 37.69 | 763.11 | 212.96 | 0.00 | 212.96 | 0.00 | 0.00 |
March | 136.86 | 593.91 | 313.79 | 0.00 | 313.79 | 0.00 | 0.00 |
April | 310.34 | 448.12 | 445.58 | 2.74 | 442.84 | 0.00 | 0.00 |
May | 503.91 | 343.11 | 571.66 | 17.16 | 554.50 | 0.00 | 0.00 |
June | 593.05 | 249.23 | 601.63 | 40.25 | 561.38 | 0.00 | 0.00 |
July | 641.66 | 211.44 | 572.63 | 46.10 | 526.53 | 0.00 | 0.00 |
August | 539.97 | 202.45 | 464.18 | 13.94 | 450.24 | 0.00 | 0.00 |
September | 318.71 | 324.39 | 359.27 | 0.27 | 359.00 | 0.00 | 0.00 |
October | 124.40 | 499.60 | 245.99 | 0.00 | 245.99 | 0.00 | 0.00 |
November | 22.35 | 682.39 | 154.95 | 0.00 | 154.95 | 0.00 | 0.00 |
December | 1.39 | 869.57 | 116.30 | 0.00 | 116.30 | 0.00 | 0.00 |
Annual Sum or Average | 270.89 | 505.44 | 350.33 | 10.11 | 340.21 | 0.00 | 0.00 |
Minimum of Months | 1.39 | 202.45 | 116.30 | 0.00 | 116.30 | 0.00 | 0.00 |
Maximum of Months | 641.66 | 892.63 | 601.63 | 46.10 | 561.38 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 119.42 | 593.23 | 223.09 | 80.86 | 142.23 | 0.00 | 0.00 |
February | 302.80 | 516.63 | 379.08 | 159.02 | 220.06 | 0.00 | 0.00 |
March | 491.60 | 417.70 | 508.93 | 191.80 | 317.13 | 0.00 | 0.00 |
April | 797.64 | 331.01 | 711.41 | 271.31 | 440.10 | 0.00 | 0.00 |
May | 901.44 | 265.45 | 751.47 | 229.63 | 521.84 | 0.00 | 0.00 |
June | 1079.18 | 198.05 | 846.91 | 315.82 | 531.09 | 0.00 | 0.00 |
July | 1107.01 | 163.07 | 810.88 | 322.53 | 488.35 | 0.00 | 0.00 |
August | 1114.83 | 154.46 | 793.57 | 359.83 | 433.74 | 0.00 | 0.00 |
September | 829.47 | 226.32 | 643.72 | 287.49 | 356.23 | 0.00 | 0.00 |
October | 501.54 | 350.54 | 463.11 | 209.96 | 253.15 | 0.00 | 0.00 |
November | 188.06 | 458.80 | 247.55 | 89.19 | 158.36 | 0.00 | 0.00 |
December | 149.62 | 586.09 | 221.06 | 95.56 | 125.49 | 0.00 | 0.00 |
Annual Sum or Average | 633.58 | 354.35 | 550.79 | 217.98 | 332.81 | 0.00 | 0.00 |
Minimum of Months | 119.42 | 154.46 | 221.06 | 80.86 | 125.49 | 0.00 | 0.00 |
Maximum of Months | 1114.83 | 593.23 | 846.91 | 359.83 | 531.09 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 259.29 | 686.77 | 370.63 | 192.57 | 178.06 | 0.00 | 0.00 |
February | 494.00 | 592.29 | 571.15 | 309.07 | 262.08 | 0.00 | 0.00 |
March | 604.33 | 482.25 | 636.00 | 279.38 | 356.62 | 0.00 | 0.00 |
April | 741.11 | 374.56 | 711.12 | 240.58 | 470.54 | 0.00 | 0.00 |
May | 781.28 | 284.23 | 716.21 | 164.49 | 551.72 | 0.00 | 0.00 |
June | 775.38 | 199.69 | 676.94 | 139.77 | 537.16 | 0.00 | 0.00 |
July | 899.11 | 164.72 | 707.69 | 201.49 | 506.20 | 0.00 | 0.00 |
August | 926.91 | 155.45 | 704.31 | 255.29 | 449.02 | 0.00 | 0.00 |
September | 872.62 | 260.89 | 727.83 | 330.81 | 397.03 | 0.00 | 0.00 |
October | 662.52 | 397.52 | 631.31 | 334.88 | 296.43 | 0.00 | 0.00 |
November | 308.89 | 535.81 | 380.47 | 187.38 | 193.09 | 0.00 | 0.00 |
December | 310.97 | 679.25 | 382.47 | 221.56 | 160.91 | 0.00 | 0.00 |
Annual Sum or Average | 637.12 | 400.19 | 601.34 | 237.67 | 363.67 | 0.00 | 0.00 |
Minimum of Months | 259.29 | 155.45 | 370.63 | 139.77 | 160.91 | 0.00 | 0.00 |
Maximum of Months | 926.91 | 686.77 | 727.83 | 334.88 | 551.72 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.104383E+10 | 0.135284E+10 | 0.117461E+10 | 0.698752E+09 | 0.475859E+09 | 0.00 | 0.00 |
February | 0.165313E+10 | 0.107269E+10 | 0.163263E+10 | 0.101296E+10 | 0.619672E+09 | 0.00 | 0.00 |
March | 0.204887E+10 | 0.979813E+09 | 0.191745E+10 | 0.101376E+10 | 0.903689E+09 | 0.00 | 0.00 |
April | 0.224151E+10 | 0.754723E+09 | 0.196075E+10 | 0.841503E+09 | 0.111925E+10 | 0.00 | 0.00 |
May | 0.222245E+10 | 0.611206E+09 | 0.188772E+10 | 0.575512E+09 | 0.131221E+10 | 0.00 | 0.00 |
June | 0.201693E+10 | 0.428567E+09 | 0.165286E+10 | 0.442373E+09 | 0.121049E+10 | 0.00 | 0.00 |
July | 0.246254E+10 | 0.374888E+09 | 0.185562E+10 | 0.673775E+09 | 0.118184E+10 | 0.00 | 0.00 |
August | 0.267633E+10 | 0.353522E+09 | 0.197825E+10 | 0.908995E+09 | 0.106925E+10 | 0.00 | 0.00 |
September | 0.266284E+10 | 0.541634E+09 | 0.212334E+10 | 0.116132E+10 | 0.962015E+09 | 0.00 | 0.00 |
October | 0.227028E+10 | 0.820556E+09 | 0.198477E+10 | 0.121515E+10 | 0.769624E+09 | 0.00 | 0.00 |
November | 0.111119E+10 | 0.103316E+10 | 0.114951E+10 | 0.657987E+09 | 0.491521E+09 | 0.00 | 0.00 |
December | 0.121358E+10 | 0.135673E+10 | 0.124317E+10 | 0.803942E+09 | 0.439232E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.236235E+11 | 0.968034E+10 | 0.205607E+11 | 0.100060E+11 | 0.105547E+11 | 0.00 | 0.00 |
Minimum of Months | 0.104383E+10 | 0.353522E+09 | 0.114951E+10 | 0.442373E+09 | 0.439232E+09 | 0.00 | 0.00 |
Maximum of Months | 0.267633E+10 | 0.135673E+10 | 0.212334E+10 | 0.121515E+10 | 0.131221E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.290694E+10 | 0.386059E+10 | 0.330763E+10 | 0.196764E+10 | 0.133999E+10 | 0.00 | 0.00 |
February | 0.462119E+10 | 0.304213E+10 | 0.459739E+10 | 0.285244E+10 | 0.174495E+10 | 0.00 | 0.00 |
March | 0.573616E+10 | 0.276603E+10 | 0.539941E+10 | 0.285469E+10 | 0.254473E+10 | 0.00 | 0.00 |
April | 0.627970E+10 | 0.211825E+10 | 0.552134E+10 | 0.236962E+10 | 0.315172E+10 | 0.00 | 0.00 |
May | 0.622793E+10 | 0.170453E+10 | 0.531570E+10 | 0.162060E+10 | 0.369510E+10 | 0.00 | 0.00 |
June | 0.564962E+10 | 0.119103E+10 | 0.465435E+10 | 0.124569E+10 | 0.340866E+10 | 0.00 | 0.00 |
July | 0.691361E+10 | 0.103336E+10 | 0.522529E+10 | 0.189731E+10 | 0.332799E+10 | 0.00 | 0.00 |
August | 0.751878E+10 | 0.978136E+09 | 0.557061E+10 | 0.255967E+10 | 0.301095E+10 | 0.00 | 0.00 |
September | 0.747940E+10 | 0.150779E+10 | 0.597918E+10 | 0.327021E+10 | 0.270897E+10 | 0.00 | 0.00 |
October | 0.636492E+10 | 0.231425E+10 | 0.558898E+10 | 0.342177E+10 | 0.216721E+10 | 0.00 | 0.00 |
November | 0.310071E+10 | 0.293458E+10 | 0.323694E+10 | 0.185285E+10 | 0.138409E+10 | 0.00 | 0.00 |
December | 0.338991E+10 | 0.387365E+10 | 0.350069E+10 | 0.226385E+10 | 0.123685E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.661889E+11 | 0.273243E+11 | 0.578975E+11 | 0.281763E+11 | 0.297212E+11 | 0.00 | 0.00 |
Minimum of Months | 0.290694E+10 | 0.978136E+09 | 0.323694E+10 | 0.124569E+10 | 0.123685E+10 | 0.00 | 0.00 |
Maximum of Months | 0.751878E+10 | 0.387365E+10 | 0.597918E+10 | 0.342177E+10 | 0.369510E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.382177E+10 | 0.518628E+10 | 0.429680E+10 | 0.255608E+10 | 0.174072E+10 | 0.00 | 0.00 |
February | 0.609654E+10 | 0.406107E+10 | 0.597227E+10 | 0.370548E+10 | 0.226679E+10 | 0.00 | 0.00 |
March | 0.758525E+10 | 0.368397E+10 | 0.701415E+10 | 0.370840E+10 | 0.330575E+10 | 0.00 | 0.00 |
April | 0.832070E+10 | 0.281895E+10 | 0.717253E+10 | 0.307827E+10 | 0.409427E+10 | 0.00 | 0.00 |
May | 0.826718E+10 | 0.227924E+10 | 0.690540E+10 | 0.210526E+10 | 0.480014E+10 | 0.00 | 0.00 |
June | 0.750996E+10 | 0.160202E+10 | 0.604627E+10 | 0.161823E+10 | 0.442804E+10 | 0.00 | 0.00 |
July | 0.917904E+10 | 0.139091E+10 | 0.678795E+10 | 0.246471E+10 | 0.432325E+10 | 0.00 | 0.00 |
August | 0.997706E+10 | 0.131462E+10 | 0.723654E+10 | 0.332516E+10 | 0.391139E+10 | 0.00 | 0.00 |
September | 0.990836E+10 | 0.200422E+10 | 0.776730E+10 | 0.424819E+10 | 0.351911E+10 | 0.00 | 0.00 |
October | 0.841654E+10 | 0.307732E+10 | 0.726041E+10 | 0.444508E+10 | 0.281533E+10 | 0.00 | 0.00 |
November | 0.408863E+10 | 0.393692E+10 | 0.420497E+10 | 0.240696E+10 | 0.179801E+10 | 0.00 | 0.00 |
December | 0.445984E+10 | 0.520554E+10 | 0.454760E+10 | 0.294087E+10 | 0.160674E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.876309E+11 | 0.365611E+11 | 0.752122E+11 | 0.366027E+11 | 0.386095E+11 | 0.00 | 0.00 |
Minimum of Months | 0.382177E+10 | 0.131462E+10 | 0.420497E+10 | 0.161823E+10 | 0.160674E+10 | 0.00 | 0.00 |
Maximum of Months | 0.997706E+10 | 0.520554E+10 | 0.776730E+10 | 0.444508E+10 | 0.480014E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.259474E+09 | 0.804915E+09 | 0.398972E+09 | 0.187754E+09 | 0.211218E+09 | 0.00 | 0.00 |
February | 0.496404E+09 | 0.634537E+09 | 0.591438E+09 | 0.301130E+09 | 0.290308E+09 | 0.00 | 0.00 |
March | 0.747325E+09 | 0.576696E+09 | 0.795758E+09 | 0.341302E+09 | 0.454457E+09 | 0.00 | 0.00 |
April | 0.105350E+10 | 0.441369E+09 | 0.100036E+10 | 0.400327E+09 | 0.600035E+09 | 0.00 | 0.00 |
May | 0.133428E+10 | 0.359444E+09 | 0.118947E+10 | 0.446091E+09 | 0.743379E+09 | 0.00 | 0.00 |
June | 0.125505E+10 | 0.251815E+09 | 0.108483E+10 | 0.381223E+09 | 0.703603E+09 | 0.00 | 0.00 |
July | 0.167647E+10 | 0.222304E+09 | 0.133520E+10 | 0.642045E+09 | 0.693153E+09 | 0.00 | 0.00 |
August | 0.152913E+10 | 0.209273E+09 | 0.119251E+10 | 0.588470E+09 | 0.604039E+09 | 0.00 | 0.00 |
September | 0.125876E+10 | 0.319672E+09 | 0.105342E+10 | 0.534400E+09 | 0.519023E+09 | 0.00 | 0.00 |
October | 0.789229E+09 | 0.484131E+09 | 0.766839E+09 | 0.394173E+09 | 0.372666E+09 | 0.00 | 0.00 |
November | 0.314207E+09 | 0.610834E+09 | 0.406719E+09 | 0.181107E+09 | 0.225612E+09 | 0.00 | 0.00 |
December | 0.306250E+09 | 0.801781E+09 | 0.402310E+09 | 0.213286E+09 | 0.189024E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.110201E+11 | 0.571677E+10 | 0.102178E+11 | 0.461131E+10 | 0.560652E+10 | 0.00 | 0.00 |
Minimum of Months | 0.259474E+09 | 0.209273E+09 | 0.398972E+09 | 0.181107E+09 | 0.189024E+09 | 0.00 | 0.00 |
Maximum of Months | 0.167647E+10 | 0.804915E+09 | 0.133520E+10 | 0.642045E+09 | 0.743379E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 71201958.48 | 0.842290E+09 | 0.219099E+09 | 49599010.86 | 0.169500E+09 | 0.00 | 0.00 |
February | 0.204422E+09 | 0.656597E+09 | 0.342238E+09 | 0.100850E+09 | 0.241388E+09 | 0.00 | 0.00 |
March | 0.416613E+09 | 0.579526E+09 | 0.536713E+09 | 0.140864E+09 | 0.395849E+09 | 0.00 | 0.00 |
April | 0.746471E+09 | 0.434704E+09 | 0.777685E+09 | 0.234962E+09 | 0.542723E+09 | 0.00 | 0.00 |
May | 0.110366E+10 | 0.349549E+09 | 0.103498E+10 | 0.338871E+09 | 0.696105E+09 | 0.00 | 0.00 |
June | 0.108837E+10 | 0.240984E+09 | 0.980806E+09 | 0.308662E+09 | 0.672144E+09 | 0.00 | 0.00 |
July | 0.144477E+10 | 0.212154E+09 | 0.118742E+10 | 0.526467E+09 | 0.660954E+09 | 0.00 | 0.00 |
August | 0.121534E+10 | 0.200260E+09 | 0.978987E+09 | 0.414081E+09 | 0.564907E+09 | 0.00 | 0.00 |
September | 0.861757E+09 | 0.315958E+09 | 0.766639E+09 | 0.304886E+09 | 0.461753E+09 | 0.00 | 0.00 |
October | 0.409245E+09 | 0.486248E+09 | 0.468540E+09 | 0.153917E+09 | 0.314622E+09 | 0.00 | 0.00 |
November | 0.116664E+09 | 0.626187E+09 | 0.236818E+09 | 51011659.85 | 0.185807E+09 | 0.00 | 0.00 |
December | 84672366.13 | 0.831516E+09 | 0.201013E+09 | 54332932.01 | 0.146680E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.776319E+10 | 0.577597E+10 | 0.773094E+10 | 0.267850E+10 | 0.505243E+10 | 0.00 | 0.00 |
Minimum of Months | 71201958.48 | 0.200260E+09 | 0.201013E+09 | 49599010.86 | 0.146680E+09 | 0.00 | 0.00 |
Maximum of Months | 0.144477E+10 | 0.842290E+09 | 0.118742E+10 | 0.526467E+09 | 0.696105E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.165881E+09 | 0.213142E+09 | 0.185756E+09 | 0.110502E+09 | 75253821.84 | 0.00 | 0.00 |
February | 0.257007E+09 | 0.181384E+09 | 0.258189E+09 | 0.160192E+09 | 97996810.64 | 0.00 | 0.00 |
March | 0.312665E+09 | 0.184251E+09 | 0.303231E+09 | 0.160319E+09 | 0.142912E+09 | 0.00 | 0.00 |
April | 0.338608E+09 | 0.147170E+09 | 0.310079E+09 | 0.133077E+09 | 0.177001E+09 | 0.00 | 0.00 |
May | 0.333549E+09 | 0.122207E+09 | 0.298531E+09 | 91012766.08 | 0.207518E+09 | 0.00 | 0.00 |
June | 0.300214E+09 | 89242842.14 | 0.261389E+09 | 69957827.29 | 0.191432E+09 | 0.00 | 0.00 |
July | 0.372059E+09 | 79802763.21 | 0.293453E+09 | 0.106552E+09 | 0.186901E+09 | 0.00 | 0.00 |
August | 0.407534E+09 | 76366525.99 | 0.312846E+09 | 0.143750E+09 | 0.169096E+09 | 0.00 | 0.00 |
September | 0.409158E+09 | 0.110069E+09 | 0.335791E+09 | 0.183654E+09 | 0.152136E+09 | 0.00 | 0.00 |
October | 0.345465E+09 | 0.161719E+09 | 0.313877E+09 | 0.192166E+09 | 0.121711E+09 | 0.00 | 0.00 |
November | 0.169862E+09 | 0.183231E+09 | 0.181786E+09 | 0.104056E+09 | 77730558.02 | 0.00 | 0.00 |
December | 0.190548E+09 | 0.219622E+09 | 0.196599E+09 | 0.127137E+09 | 69461416.07 | 0.00 | 0.00 |
Annual Sum or Average | 0.360255E+10 | 0.176821E+10 | 0.325153E+10 | 0.158238E+10 | 0.166915E+10 | 0.00 | 0.00 |
Minimum of Months | 0.165881E+09 | 76366525.99 | 0.181786E+09 | 69957827.29 | 69461416.07 | 0.00 | 0.00 |
Maximum of Months | 0.409158E+09 | 0.219622E+09 | 0.335791E+09 | 0.192166E+09 | 0.207518E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 1357923.88 | 0.259658E+09 | 41900326.30 | 0.00 | 41900326.30 | 0.00 | 0.00 |
February | 12027352.62 | 0.200410E+09 | 58888587.20 | 0.00 | 58888587.20 | 0.00 | 0.00 |
March | 44621358.87 | 0.172735E+09 | 96068061.79 | 313.23 | 96067748.57 | 0.00 | 0.00 |
April | 94763316.46 | 0.124749E+09 | 0.132017E+09 | 812222.38 | 0.131204E+09 | 0.00 | 0.00 |
May | 0.157224E+09 | 97056131.92 | 0.175017E+09 | 5255038.69 | 0.169762E+09 | 0.00 | 0.00 |
June | 0.179129E+09 | 65829956.66 | 0.178249E+09 | 11924704.54 | 0.166324E+09 | 0.00 | 0.00 |
July | 0.199363E+09 | 56205483.19 | 0.175314E+09 | 14113260.42 | 0.161201E+09 | 0.00 | 0.00 |
August | 0.167215E+09 | 53009554.26 | 0.142110E+09 | 4267924.75 | 0.137842E+09 | 0.00 | 0.00 |
September | 95873385.14 | 88721832.00 | 0.106444E+09 | 79737.34 | 0.106364E+09 | 0.00 | 0.00 |
October | 40111702.74 | 0.144080E+09 | 75309952.72 | 0.00 | 75309952.72 | 0.00 | 0.00 |
November | 7587569.98 | 0.191577E+09 | 45907539.48 | 0.00 | 45907539.48 | 0.00 | 0.00 |
December | 703712.71 | 0.253839E+09 | 35604474.90 | 0.00 | 35604474.90 | 0.00 | 0.00 |
Annual Sum or Average | 0.999978E+09 | 0.170787E+10 | 0.126283E+10 | 36453201.35 | 0.122638E+10 | 0.00 | 0.00 |
Minimum of Months | 703712.71 | 53009554.26 | 35604474.90 | 0.00 | 35604474.90 | 0.00 | 0.00 |
Maximum of Months | 0.199363E+09 | 0.259658E+09 | 0.178249E+09 | 14113260.42 | 0.169762E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.243816E+09 | 0.800591E+09 | 0.388716E+09 | 0.177368E+09 | 0.211348E+09 | 0.00 | 0.00 |
February | 0.480901E+09 | 0.629247E+09 | 0.583153E+09 | 0.292498E+09 | 0.290655E+09 | 0.00 | 0.00 |
March | 0.754254E+09 | 0.565627E+09 | 0.811112E+09 | 0.357088E+09 | 0.454024E+09 | 0.00 | 0.00 |
April | 0.107796E+10 | 0.426589E+09 | 0.103337E+10 | 0.434321E+09 | 0.599046E+09 | 0.00 | 0.00 |
May | 0.118731E+10 | 0.349495E+09 | 0.108366E+10 | 0.361145E+09 | 0.722516E+09 | 0.00 | 0.00 |
June | 0.133204E+10 | 0.242835E+09 | 0.114966E+10 | 0.445607E+09 | 0.704053E+09 | 0.00 | 0.00 |
July | 0.143323E+10 | 0.206442E+09 | 0.115987E+10 | 0.489740E+09 | 0.670134E+09 | 0.00 | 0.00 |
August | 0.148536E+10 | 0.195988E+09 | 0.116956E+10 | 0.569108E+09 | 0.600453E+09 | 0.00 | 0.00 |
September | 0.114405E+10 | 0.307405E+09 | 0.977694E+09 | 0.487360E+09 | 0.490334E+09 | 0.00 | 0.00 |
October | 0.786925E+09 | 0.477594E+09 | 0.769368E+09 | 0.401318E+09 | 0.368051E+09 | 0.00 | 0.00 |
November | 0.309603E+09 | 0.606077E+09 | 0.405794E+09 | 0.180647E+09 | 0.225147E+09 | 0.00 | 0.00 |
December | 0.294313E+09 | 0.794544E+09 | 0.396697E+09 | 0.207455E+09 | 0.189242E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.105298E+11 | 0.560243E+10 | 0.992866E+10 | 0.440365E+10 | 0.552500E+10 | 0.00 | 0.00 |
Minimum of Months | 0.243816E+09 | 0.195988E+09 | 0.388716E+09 | 0.177368E+09 | 0.189242E+09 | 0.00 | 0.00 |
Maximum of Months | 0.148536E+10 | 0.800591E+09 | 0.116956E+10 | 0.569108E+09 | 0.722516E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 49614159.59 | 0.832566E+09 | 0.208843E+09 | 39212816.39 | 0.169630E+09 | 0.00 | 0.00 |
February | 0.179169E+09 | 0.640728E+09 | 0.333954E+09 | 92217704.15 | 0.241736E+09 | 0.00 | 0.00 |
March | 0.416184E+09 | 0.561380E+09 | 0.552067E+09 | 0.156651E+09 | 0.395417E+09 | 0.00 | 0.00 |
April | 0.768358E+09 | 0.419394E+09 | 0.810690E+09 | 0.268956E+09 | 0.541734E+09 | 0.00 | 0.00 |
May | 0.957702E+09 | 0.341867E+09 | 0.929166E+09 | 0.253925E+09 | 0.675242E+09 | 0.00 | 0.00 |
June | 0.116803E+10 | 0.236618E+09 | 0.104564E+10 | 0.373046E+09 | 0.672594E+09 | 0.00 | 0.00 |
July | 0.120433E+10 | 0.199894E+09 | 0.101210E+10 | 0.374162E+09 | 0.637935E+09 | 0.00 | 0.00 |
August | 0.117465E+10 | 0.191677E+09 | 0.956040E+09 | 0.394718E+09 | 0.561321E+09 | 0.00 | 0.00 |
September | 0.744055E+09 | 0.301958E+09 | 0.690909E+09 | 0.257846E+09 | 0.433063E+09 | 0.00 | 0.00 |
October | 0.400317E+09 | 0.473646E+09 | 0.471069E+09 | 0.161062E+09 | 0.310007E+09 | 0.00 | 0.00 |
November | 0.106685E+09 | 0.615900E+09 | 0.235893E+09 | 50551984.52 | 0.185341E+09 | 0.00 | 0.00 |
December | 63439082.75 | 0.815032E+09 | 0.195400E+09 | 48501623.07 | 0.146898E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.723254E+10 | 0.563066E+10 | 0.744177E+10 | 0.247085E+10 | 0.497092E+10 | 0.00 | 0.00 |
Minimum of Months | 49614159.59 | 0.191677E+09 | 0.195400E+09 | 39212816.39 | 0.146898E+09 | 0.00 | 0.00 |
Maximum of Months | 0.120433E+10 | 0.832566E+09 | 0.104564E+10 | 0.394718E+09 | 0.675242E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.315087E+09 | 0.103678E+10 | 0.493252E+09 | 0.239428E+09 | 0.253824E+09 | 0.00 | 0.00 |
February | 0.563848E+09 | 0.806513E+09 | 0.686996E+09 | 0.347092E+09 | 0.339904E+09 | 0.00 | 0.00 |
March | 0.797393E+09 | 0.722230E+09 | 0.865133E+09 | 0.347366E+09 | 0.517766E+09 | 0.00 | 0.00 |
April | 0.984923E+09 | 0.537981E+09 | 0.957846E+09 | 0.290101E+09 | 0.667746E+09 | 0.00 | 0.00 |
May | 0.111899E+10 | 0.419316E+09 | 0.102598E+10 | 0.208584E+09 | 0.817395E+09 | 0.00 | 0.00 |
June | 0.109937E+10 | 0.283924E+09 | 0.952505E+09 | 0.177412E+09 | 0.775093E+09 | 0.00 | 0.00 |
July | 0.130066E+10 | 0.243163E+09 | 0.101562E+10 | 0.261443E+09 | 0.754179E+09 | 0.00 | 0.00 |
August | 0.130433E+10 | 0.231328E+09 | 0.985709E+09 | 0.320713E+09 | 0.664996E+09 | 0.00 | 0.00 |
September | 0.114253E+10 | 0.377218E+09 | 0.958159E+09 | 0.398101E+09 | 0.560058E+09 | 0.00 | 0.00 |
October | 0.866574E+09 | 0.594740E+09 | 0.843231E+09 | 0.416370E+09 | 0.426860E+09 | 0.00 | 0.00 |
November | 0.378057E+09 | 0.778628E+09 | 0.493331E+09 | 0.225460E+09 | 0.267872E+09 | 0.00 | 0.00 |
December | 0.380034E+09 | 0.102594E+10 | 0.503106E+09 | 0.275471E+09 | 0.227635E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.102518E+11 | 0.705777E+10 | 0.978087E+10 | 0.350754E+10 | 0.627333E+10 | 0.00 | 0.00 |
Minimum of Months | 0.315087E+09 | 0.231328E+09 | 0.493252E+09 | 0.177412E+09 | 0.227635E+09 | 0.00 | 0.00 |
Maximum of Months | 0.130433E+10 | 0.103678E+10 | 0.102598E+10 | 0.416370E+09 | 0.817395E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.261090E+09 | 0.797787E+09 | 0.398972E+09 | 0.187754E+09 | 0.211218E+09 | 0.00 | 0.00 |
February | 0.495852E+09 | 0.629177E+09 | 0.591438E+09 | 0.301130E+09 | 0.290308E+09 | 0.00 | 0.00 |
March | 0.742822E+09 | 0.572713E+09 | 0.795758E+09 | 0.341302E+09 | 0.454457E+09 | 0.00 | 0.00 |
April | 0.104150E+10 | 0.441685E+09 | 0.100036E+10 | 0.400327E+09 | 0.600035E+09 | 0.00 | 0.00 |
May | 0.131642E+10 | 0.361002E+09 | 0.118947E+10 | 0.446091E+09 | 0.743379E+09 | 0.00 | 0.00 |
June | 0.123630E+10 | 0.253445E+09 | 0.108483E+10 | 0.381223E+09 | 0.703603E+09 | 0.00 | 0.00 |
July | 0.165568E+10 | 0.224408E+09 | 0.133520E+10 | 0.642045E+09 | 0.693153E+09 | 0.00 | 0.00 |
August | 0.151201E+10 | 0.210691E+09 | 0.119251E+10 | 0.588470E+09 | 0.604039E+09 | 0.00 | 0.00 |
September | 0.124738E+10 | 0.319797E+09 | 0.105342E+10 | 0.534400E+09 | 0.519023E+09 | 0.00 | 0.00 |
October | 0.783938E+09 | 0.480323E+09 | 0.766839E+09 | 0.394173E+09 | 0.372666E+09 | 0.00 | 0.00 |
November | 0.315049E+09 | 0.603279E+09 | 0.406719E+09 | 0.181107E+09 | 0.225612E+09 | 0.00 | 0.00 |
December | 0.307713E+09 | 0.792364E+09 | 0.402310E+09 | 0.213286E+09 | 0.189024E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.109158E+11 | 0.568667E+10 | 0.102178E+11 | 0.461131E+10 | 0.560652E+10 | 0.00 | 0.00 |
Minimum of Months | 0.261090E+09 | 0.210691E+09 | 0.398972E+09 | 0.181107E+09 | 0.189024E+09 | 0.00 | 0.00 |
Maximum of Months | 0.165568E+10 | 0.797787E+09 | 0.133520E+10 | 0.642045E+09 | 0.743379E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 72431804.45 | 0.834346E+09 | 0.219099E+09 | 49599010.86 | 0.169500E+09 | 0.00 | 0.00 |
February | 0.205380E+09 | 0.650405E+09 | 0.342238E+09 | 0.100850E+09 | 0.241388E+09 | 0.00 | 0.00 |
March | 0.414911E+09 | 0.574132E+09 | 0.536713E+09 | 0.140864E+09 | 0.395849E+09 | 0.00 | 0.00 |
April | 0.737097E+09 | 0.434126E+09 | 0.777685E+09 | 0.234962E+09 | 0.542723E+09 | 0.00 | 0.00 |
May | 0.108715E+10 | 0.350839E+09 | 0.103498E+10 | 0.338871E+09 | 0.696105E+09 | 0.00 | 0.00 |
June | 0.107028E+10 | 0.242530E+09 | 0.980806E+09 | 0.308662E+09 | 0.672144E+09 | 0.00 | 0.00 |
July | 0.142496E+10 | 0.214205E+09 | 0.118742E+10 | 0.526467E+09 | 0.660954E+09 | 0.00 | 0.00 |
August | 0.119965E+10 | 0.201537E+09 | 0.978987E+09 | 0.414081E+09 | 0.564907E+09 | 0.00 | 0.00 |
September | 0.851528E+09 | 0.315610E+09 | 0.766639E+09 | 0.304886E+09 | 0.461753E+09 | 0.00 | 0.00 |
October | 0.407050E+09 | 0.480608E+09 | 0.468540E+09 | 0.153917E+09 | 0.314622E+09 | 0.00 | 0.00 |
November | 0.118211E+09 | 0.617440E+09 | 0.236818E+09 | 51011659.85 | 0.185807E+09 | 0.00 | 0.00 |
December | 86268633.91 | 0.820444E+09 | 0.201013E+09 | 54332932.01 | 0.146680E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.767492E+10 | 0.573622E+10 | 0.773094E+10 | 0.267850E+10 | 0.505243E+10 | 0.00 | 0.00 |
Minimum of Months | 72431804.45 | 0.201537E+09 | 0.201013E+09 | 49599010.86 | 0.146680E+09 | 0.00 | 0.00 |
Maximum of Months | 0.142496E+10 | 0.834346E+09 | 0.118742E+10 | 0.526467E+09 | 0.696105E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.293784E+09 | 0.416143E+09 | 0.340604E+09 | 0.202618E+09 | 0.137986E+09 | 0.00 | 0.00 |
February | 0.464981E+09 | 0.331078E+09 | 0.473418E+09 | 0.293730E+09 | 0.179688E+09 | 0.00 | 0.00 |
March | 0.576035E+09 | 0.304463E+09 | 0.556007E+09 | 0.293962E+09 | 0.262045E+09 | 0.00 | 0.00 |
April | 0.625966E+09 | 0.236016E+09 | 0.568563E+09 | 0.244012E+09 | 0.324552E+09 | 0.00 | 0.00 |
May | 0.618895E+09 | 0.189905E+09 | 0.547388E+09 | 0.166882E+09 | 0.380507E+09 | 0.00 | 0.00 |
June | 0.559898E+09 | 0.132369E+09 | 0.479286E+09 | 0.128275E+09 | 0.351011E+09 | 0.00 | 0.00 |
July | 0.690148E+09 | 0.114683E+09 | 0.538079E+09 | 0.195375E+09 | 0.342704E+09 | 0.00 | 0.00 |
August | 0.755106E+09 | 0.107398E+09 | 0.573638E+09 | 0.263582E+09 | 0.310056E+09 | 0.00 | 0.00 |
September | 0.756801E+09 | 0.166021E+09 | 0.615709E+09 | 0.336751E+09 | 0.278959E+09 | 0.00 | 0.00 |
October | 0.639083E+09 | 0.254078E+09 | 0.575528E+09 | 0.352358E+09 | 0.223170E+09 | 0.00 | 0.00 |
November | 0.313043E+09 | 0.318185E+09 | 0.333325E+09 | 0.190797E+09 | 0.142527E+09 | 0.00 | 0.00 |
December | 0.343054E+09 | 0.414428E+09 | 0.360485E+09 | 0.233120E+09 | 0.127365E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.663680E+10 | 0.298477E+10 | 0.596203E+10 | 0.290146E+10 | 0.306057E+10 | 0.00 | 0.00 |
Minimum of Months | 0.293784E+09 | 0.107398E+09 | 0.333325E+09 | 0.128275E+09 | 0.127365E+09 | 0.00 | 0.00 |
Maximum of Months | 0.756801E+09 | 0.416143E+09 | 0.615709E+09 | 0.352358E+09 | 0.380507E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 9129162.55 | 0.234427E+10 | 0.366565E+09 | 0.00 | 0.366565E+09 | 0.00 | 0.00 |
February | 96590080.30 | 0.180803E+10 | 0.515187E+09 | 0.00 | 0.515187E+09 | 0.00 | 0.00 |
March | 0.378602E+09 | 0.155272E+10 | 0.840452E+09 | 2740.29 | 0.840450E+09 | 0.00 | 0.00 |
April | 0.823555E+09 | 0.113058E+10 | 0.115495E+10 | 7105734.80 | 0.114784E+10 | 0.00 | 0.00 |
May | 0.137598E+10 | 0.891823E+09 | 0.153114E+10 | 45973752.97 | 0.148517E+10 | 0.00 | 0.00 |
June | 0.156716E+10 | 0.622449E+09 | 0.155941E+10 | 0.104323E+09 | 0.145509E+10 | 0.00 | 0.00 |
July | 0.174980E+10 | 0.542100E+09 | 0.153374E+10 | 0.123470E+09 | 0.141027E+10 | 0.00 | 0.00 |
August | 0.147470E+10 | 0.516894E+09 | 0.124325E+10 | 37337977.86 | 0.120591E+10 | 0.00 | 0.00 |
September | 0.844538E+09 | 0.810922E+09 | 0.931226E+09 | 697582.85 | 0.930528E+09 | 0.00 | 0.00 |
October | 0.345612E+09 | 0.129981E+10 | 0.658850E+09 | 0.00 | 0.658850E+09 | 0.00 | 0.00 |
November | 62377569.25 | 0.172536E+10 | 0.401623E+09 | 0.00 | 0.401623E+09 | 0.00 | 0.00 |
December | 4573642.85 | 0.228203E+10 | 0.311486E+09 | 0.00 | 0.311486E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.873262E+10 | 0.155270E+11 | 0.110479E+11 | 0.318911E+09 | 0.107290E+11 | 0.00 | 0.00 |
Minimum of Months | 4573642.85 | 0.516894E+09 | 0.311486E+09 | 0.00 | 0.311486E+09 | 0.00 | 0.00 |
Maximum of Months | 0.174980E+10 | 0.234427E+10 | 0.155941E+10 | 0.123470E+09 | 0.148517E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 7997344.56 | 0.239081E+10 | 0.366565E+09 | 0.00 | 0.366565E+09 | 0.00 | 0.00 |
February | 91182762.62 | 0.184612E+10 | 0.515187E+09 | 0.00 | 0.515187E+09 | 0.00 | 0.00 |
March | 0.366566E+09 | 0.159072E+10 | 0.840452E+09 | 2740.29 | 0.840450E+09 | 0.00 | 0.00 |
April | 0.804409E+09 | 0.116152E+10 | 0.115495E+10 | 7105734.80 | 0.114784E+10 | 0.00 | 0.00 |
May | 0.134968E+10 | 0.918981E+09 | 0.153114E+10 | 45973752.97 | 0.148517E+10 | 0.00 | 0.00 |
June | 0.153718E+10 | 0.646010E+09 | 0.155941E+10 | 0.104323E+09 | 0.145509E+10 | 0.00 | 0.00 |
July | 0.171862E+10 | 0.566321E+09 | 0.153374E+10 | 0.123470E+09 | 0.141027E+10 | 0.00 | 0.00 |
August | 0.144625E+10 | 0.542237E+09 | 0.124325E+10 | 37337977.86 | 0.120591E+10 | 0.00 | 0.00 |
September | 0.826104E+09 | 0.840821E+09 | 0.931226E+09 | 697582.85 | 0.930528E+09 | 0.00 | 0.00 |
October | 0.333181E+09 | 0.133812E+10 | 0.658850E+09 | 0.00 | 0.658850E+09 | 0.00 | 0.00 |
November | 57920830.71 | 0.176874E+10 | 0.401623E+09 | 0.00 | 0.401623E+09 | 0.00 | 0.00 |
December | 3720636.73 | 0.232905E+10 | 0.311486E+09 | 0.00 | 0.311486E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.854281E+10 | 0.159394E+11 | 0.110479E+11 | 0.318911E+09 | 0.107290E+11 | 0.00 | 0.00 |
Minimum of Months | 3720636.73 | 0.542237E+09 | 0.311486E+09 | 0.00 | 0.311486E+09 | 0.00 | 0.00 |
Maximum of Months | 0.171862E+10 | 0.239081E+10 | 0.155941E+10 | 0.123470E+09 | 0.148517E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.319846E+09 | 0.158890E+10 | 0.597536E+09 | 0.216575E+09 | 0.380961E+09 | 0.00 | 0.00 |
February | 0.732537E+09 | 0.124983E+10 | 0.917070E+09 | 0.384702E+09 | 0.532367E+09 | 0.00 | 0.00 |
March | 0.131669E+10 | 0.111876E+10 | 0.136312E+10 | 0.513717E+09 | 0.849402E+09 | 0.00 | 0.00 |
April | 0.206748E+10 | 0.857978E+09 | 0.184397E+10 | 0.703239E+09 | 0.114073E+10 | 0.00 | 0.00 |
May | 0.241442E+10 | 0.710995E+09 | 0.201273E+10 | 0.615035E+09 | 0.139769E+10 | 0.00 | 0.00 |
June | 0.279724E+10 | 0.513337E+09 | 0.219518E+10 | 0.818602E+09 | 0.137658E+10 | 0.00 | 0.00 |
July | 0.296500E+10 | 0.436765E+09 | 0.217186E+10 | 0.863852E+09 | 0.130801E+10 | 0.00 | 0.00 |
August | 0.298596E+10 | 0.413707E+09 | 0.212549E+10 | 0.963771E+09 | 0.116172E+10 | 0.00 | 0.00 |
September | 0.215000E+10 | 0.586627E+09 | 0.166852E+10 | 0.745168E+09 | 0.923355E+09 | 0.00 | 0.00 |
October | 0.134334E+10 | 0.938889E+09 | 0.124038E+10 | 0.562357E+09 | 0.678027E+09 | 0.00 | 0.00 |
November | 0.487449E+09 | 0.118921E+10 | 0.641662E+09 | 0.231192E+09 | 0.410470E+09 | 0.00 | 0.00 |
December | 0.400742E+09 | 0.156979E+10 | 0.592075E+09 | 0.255949E+09 | 0.336126E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.199807E+11 | 0.111748E+11 | 0.173696E+11 | 0.687416E+10 | 0.104954E+11 | 0.00 | 0.00 |
Minimum of Months | 0.319846E+09 | 0.413707E+09 | 0.592075E+09 | 0.216575E+09 | 0.336126E+09 | 0.00 | 0.00 |
Maximum of Months | 0.298596E+10 | 0.158890E+10 | 0.219518E+10 | 0.963771E+09 | 0.139769E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.694485E+09 | 0.183945E+10 | 0.992685E+09 | 0.515775E+09 | 0.476910E+09 | 0.00 | 0.00 |
February | 0.119508E+10 | 0.143286E+10 | 0.138172E+10 | 0.747705E+09 | 0.634012E+09 | 0.00 | 0.00 |
March | 0.161864E+10 | 0.129165E+10 | 0.170345E+10 | 0.748296E+09 | 0.955158E+09 | 0.00 | 0.00 |
April | 0.192095E+10 | 0.970847E+09 | 0.184323E+10 | 0.623580E+09 | 0.121965E+10 | 0.00 | 0.00 |
May | 0.209258E+10 | 0.761284E+09 | 0.191828E+10 | 0.440567E+09 | 0.147772E+10 | 0.00 | 0.00 |
June | 0.200978E+10 | 0.517592E+09 | 0.175462E+10 | 0.362294E+09 | 0.139232E+10 | 0.00 | 0.00 |
July | 0.240817E+10 | 0.441195E+09 | 0.189548E+10 | 0.539664E+09 | 0.135581E+10 | 0.00 | 0.00 |
August | 0.248265E+10 | 0.416344E+09 | 0.188641E+10 | 0.683762E+09 | 0.120265E+10 | 0.00 | 0.00 |
September | 0.226182E+10 | 0.676229E+09 | 0.188655E+10 | 0.857456E+09 | 0.102909E+10 | 0.00 | 0.00 |
October | 0.177451E+10 | 0.106473E+10 | 0.169089E+10 | 0.896945E+09 | 0.793947E+09 | 0.00 | 0.00 |
November | 0.800638E+09 | 0.138881E+10 | 0.986173E+09 | 0.485685E+09 | 0.500488E+09 | 0.00 | 0.00 |
December | 0.832898E+09 | 0.181931E+10 | 0.102441E+10 | 0.593419E+09 | 0.430993E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.200922E+11 | 0.126203E+11 | 0.189639E+11 | 0.749515E+10 | 0.114688E+11 | 0.00 | 0.00 |
Minimum of Months | 0.694485E+09 | 0.416344E+09 | 0.986173E+09 | 0.362294E+09 | 0.430993E+09 | 0.00 | 0.00 |
Maximum of Months | 0.248265E+10 | 0.183945E+10 | 0.191828E+10 | 0.896945E+09 | 0.147772E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 4.50 | 3.10 | 1.22 | 3.91 | -4.2 | 29.50 | 44.23 | 0.00 |
February | 5.82 | 4.07 | 1.77 | 3.94 | -3.8 | 43.80 | 82.64 | 0.00 |
March | 8.33 | 5.86 | 2.94 | 3.85 | -1.4 | 65.55 | 100.60 | 0.02 |
April | 10.85 | 8.04 | 5.25 | 4.23 | 1.22 | 89.73 | 150.02 | 0.00 |
May | 12.97 | 10.02 | 7.49 | 3.85 | 3.75 | 114.98 | 168.60 | 0.00 |
June | 15.59 | 11.80 | 8.88 | 4.02 | 5.93 | 107.53 | 199.74 | 0.01 |
July | 17.66 | 13.41 | 10.38 | 3.76 | 8.02 | 92.25 | 247.81 | 0.00 |
August | 18.80 | 14.57 | 11.86 | 3.84 | 8.90 | 79.20 | 215.47 | 0.01 |
September | 15.09 | 12.55 | 10.74 | 2.23 | 5.47 | 68.06 | 162.11 | 0.01 |
October | 11.43 | 9.19 | 7.19 | 4.02 | 2.10 | 48.18 | 106.36 | 0.04 |
November | 8.07 | 6.72 | 5.29 | 3.86 | 0.13 | 33.26 | 46.10 | 0.00 |
December | 5.42 | 4.09 | 2.46 | 3.51 | -3.8 | 24.03 | 50.49 | 0.04 |
Annual Sum or Average | 11.24 | 8.64 | 6.31 | 3.75 | 1.89 | 66.43 | 131.49 | 0.01 |
Minimum of Months | 4.50 | 3.10 | 1.22 | 2.23 | -4.2 | 24.03 | 44.23 | 0.00 |
Maximum of Months | 18.80 | 14.57 | 11.86 | 4.23 | 8.90 | 114.98 | 247.81 | 0.04 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 14.40 | 11-JAN-14:20 | 10.49 | 7.20 | 8.40 | 3.89 | 99.17 | 130.33 |
February | 20.00 | 27-FEB-14:00 | 12.17 | 5.60 | 2.60 | 5.54 | 87.00 | 691.00 |
March | 20.60 | 18-MAR-15:00 | 10.43 | 0.00 | 6.20 | 6.55 | 111.50 | 465.50 |
April | 27.20 | 27-APR-15:09 | 17.22 | 11.02 | 4.10 | 12.63 | 151.33 | 598.33 |
May | 25.00 | 05-MAY-15:00 | 17.36 | 12.80 | 2.60 | 18.99 | 208.50 | 29.50 |
June | 26.70 | 28-JUN-16:00 | 16.74 | 10.60 | 3.10 | 11.84 | 131.50 | 527.00 |
July | 30.60 | 24-JUL-14:00 | 18.78 | 12.20 | 3.10 | 20.75 | 267.00 | 383.50 |
August | 31.80 | 10-AUG-16:00 | 18.70 | 11.10 | 2.60 | 16.85 | 50.50 | 750.50 |
September | 25.00 | 14-SEP-16:00 | 16.69 | 11.70 | 3.10 | 13.54 | 100.50 | 235.00 |
October | 21.70 | 04-OCT-14:00 | 11.49 | 1.70 | 5.20 | 4.92 | 56.50 | 783.50 |
November | 21.10 | 04-NOV-13:00 | 15.94 | 12.80 | 0.00 | 6.95 | 52.50 | 729.00 |
December | 13.30 | 14-DEC-11:00 | 8.44 | 3.60 | 13.90 | 5.33 | 127.50 | 85.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 13.30 | 8.44 | 0.00 | 0.00 | 3.89 | 50.50 | 29.50 | |
Maximum of Months | 31.80 | 18.78 | 12.80 | 13.90 | 20.75 | 267.00 | 783.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -3.9 | 07-JAN-07:00 | -3.9 | -3.9 | 2.10 | -14.4 | 0.00 | 0.00 |
February | -5.6 | 19-FEB-05:10 | -6.1 | -7.3 | 3.77 | -22.8 | 0.00 | 0.00 |
March | -0.6 | 01-MAR-06:00 | -2.0 | -3.9 | 1.50 | -17.3 | 16.50 | 102.00 |
April | 1.70 | 19-APR-04:00 | 1.21 | 0.60 | 3.10 | -11.9 | 0.00 | 0.00 |
May | 4.40 | 11-MAY-02:00 | 3.92 | 3.30 | 3.10 | -10.9 | 0.00 | 0.00 |
June | 8.30 | 15-JUN-02:00 | 7.50 | 6.70 | 3.10 | -3.2 | 0.00 | 0.00 |
July | 11.10 | 03-JUL-03:00 | 8.19 | 5.00 | 2.60 | 5.54 | 0.00 | 0.00 |
August | 11.00 | 06-AUG-04:00 | 10.57 | 10.20 | 2.60 | -3.2 | 11.00 | 135.50 |
September | 7.20 | 27-SEP-04:49 | 6.72 | 6.20 | 0.25 | -4.0 | 0.00 | 0.00 |
October | 5.60 | 13-OCT-04:00 | 4.51 | 3.30 | 2.10 | -8.5 | 0.00 | 0.00 |
November | 0.00 | 11-NOV-06:00 | -0.2 | -0.6 | 2.10 | -16.0 | 0.00 | 0.00 |
December | -1.7 | 26-DEC-06:00 | -1.7 | -1.7 | 2.10 | -15.7 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -5.6 | -6.1 | -7.3 | 0.25 | -22.8 | 0.00 | 0.00 | |
Maximum of Months | 11.10 | 10.57 | 10.20 | 3.77 | 5.54 | 16.50 | 135.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.49 | 11-JAN-13:00 | 14.40 | 7.20 | 8.20 | 2.85 | 105.50 | 249.00 |
February | 12.42 | 27-FEB-15:00 | 19.40 | 6.70 | 2.60 | 6.35 | 88.00 | 342.50 |
March | 12.45 | 09-MAR-11:00 | 17.20 | 8.90 | 2.10 | 12.41 | 178.00 | 40.00 |
April | 17.29 | 27-APR-14:00 | 27.20 | 11.10 | 4.10 | 12.41 | 147.50 | 646.00 |
May | 17.58 | 06-MAY-12:00 | 23.90 | 13.90 | 5.20 | 15.57 | 365.50 | 282.50 |
June | 16.74 | 28-JUN-16:00 | 26.70 | 10.60 | 3.10 | 11.84 | 131.50 | 527.00 |
July | 19.18 | 31-JUL-15:00 | 28.90 | 13.90 | 4.10 | 14.65 | 45.00 | 848.50 |
August | 20.13 | 29-AUG-12:00 | 28.90 | 15.70 | 2.60 | 17.39 | 136.50 | 655.00 |
September | 17.97 | 23-SEP-13:00 | 23.30 | 15.00 | 2.10 | 9.72 | 148.00 | 670.50 |
October | 15.15 | 01-OCT-11:00 | 17.20 | 13.90 | 4.60 | 13.73 | 236.50 | 63.50 |
November | 16.05 | 04-NOV-12:00 | 20.60 | 13.30 | 0.00 | 7.95 | 62.00 | 746.50 |
December | 10.71 | 16-DEC-11:00 | 11.70 | 10.00 | 6.70 | 7.35 | 89.50 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.49 | 11.70 | 6.70 | 0.00 | 2.85 | 45.00 | 0.00 | |
Maximum of Months | 20.13 | 28.90 | 15.70 | 8.20 | 17.39 | 365.50 | 848.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.00 | 11-JAN-21:00 | 11.10 | 10.49 | 4.60 | 6.75 | 0.00 | 0.00 |
February | 11.70 | 24-FEB-00:00 | 12.80 | 12.15 | 4.10 | 8.74 | 0.00 | 0.00 |
March | 11.70 | 09-MAR-16:00 | 12.80 | 12.15 | 2.10 | 8.74 | 37.50 | 0.00 |
April | 12.80 | 28-APR-12:00 | 16.70 | 14.35 | 4.10 | 8.35 | 265.50 | 596.00 |
May | 13.90 | 05-MAY-16:00 | 22.80 | 17.10 | 2.60 | 19.17 | 111.50 | 27.50 |
June | 13.90 | 12-JUN-12:00 | 16.70 | 15.00 | 3.60 | 13.16 | 263.50 | 0.00 |
July | 15.00 | 11-JUL-09:20 | 16.13 | 15.49 | 4.60 | 12.91 | 204.17 | 28.17 |
August | 16.40 | 30-AUG-07:00 | 17.40 | 16.77 | 5.20 | 12.41 | 168.50 | 34.50 |
September | 15.00 | 14-SEP-11:20 | 20.37 | 16.93 | 2.10 | 6.89 | 152.83 | 748.17 |
October | 13.90 | 01-OCT-10:00 | 16.70 | 15.01 | 4.10 | 13.16 | 184.50 | 0.00 |
November | 13.90 | 03-NOV-19:00 | 15.00 | 14.31 | 4.60 | 11.46 | 0.00 | 0.00 |
December | 10.00 | 16-DEC-10:00 | 11.10 | 10.48 | 7.70 | 6.75 | 81.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.00 | 11.10 | 10.48 | 2.10 | 6.75 | 0.00 | 0.00 | |
Maximum of Months | 16.40 | 22.80 | 17.10 | 7.70 | 19.17 | 265.50 | 748.17 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 11.48 | 8.35 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 11.14 | 14.81 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 11.69 | 23.26 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 12.99 | 36.00 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 14.72 | 45.46 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 16.40 | 49.26 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 17.58 | 51.50 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 17.95 | 42.11 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 17.39 | 30.76 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 16.06 | 18.91 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 14.32 | 9.65 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 12.65 | 7.39 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 14.55 | 28.19 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 11.14 | 7.39 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 17.95 | 51.50 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH BOOSTER E WATER HEATER
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.770817E+10 | -0.754278E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -165386684.3 | 81.21 | 0.00 | 0.00 |
February | 0.696508E+10 | -0.681596E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -149122756.3 | 81.21 | 0.00 | 0.00 |
March | 0.770626E+10 | -0.754146E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164791951.1 | 81.21 | 0.00 | 0.00 |
April | 0.746776E+10 | -0.730861E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -159150330.1 | 81.21 | 0.00 | 0.00 |
May | 0.770708E+10 | -0.754280E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164284638.3 | 81.21 | 0.00 | 0.00 |
June | 0.745933E+10 | -0.730053E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -158798254.2 | 81.21 | 0.00 | 0.00 |
July | 0.771490E+10 | -0.755086E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164049159.9 | 81.21 | 0.00 | 0.00 |
August | 0.770682E+10 | -0.754280E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164019364.2 | 81.21 | 0.00 | 0.00 |
September | 0.746891E+10 | -0.730994E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -158966605.2 | 81.21 | 0.00 | 0.00 |
October | 0.770609E+10 | -0.754144E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164646754.5 | 81.21 | 0.00 | 0.00 |
November | 0.745219E+10 | -0.729243E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -159756530.8 | 81.21 | 0.00 | 0.00 |
December | 0.771617E+10 | -0.755084E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -165325208.2 | 81.21 | 0.00 | 0.00 |
Annual Sum or Average | 0.907788E+11 | -0.888405E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.193830E+10 | 81.21 | 0.00 | 0.00 |
Minimum of Months | 0.696508E+10 | -0.755086E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -165386684.3 | 81.21 | 0.00 | 0.00 |
Maximum of Months | 0.771617E+10 | -0.681596E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -149122756.3 | 81.21 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH LAUNDRY G WATER HEATER
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.119994E+12 | -0.118179E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.181481E+10 | 81.27 | 0.00 | 0.00 |
February | 0.108896E+12 | -0.107257E+12 | 0.00 | 0.00 | 672.00 | 0.00 | -0.163955E+10 | 81.27 | 0.00 | 0.00 |
March | 0.119635E+12 | -0.117820E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.181566E+10 | 81.27 | 0.00 | 0.00 |
April | 0.113617E+12 | -0.111860E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.175731E+10 | 81.27 | 0.00 | 0.00 |
May | 0.114461E+12 | -0.112645E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.181570E+10 | 81.26 | 0.00 | 0.00 |
June | 0.108002E+12 | -0.106245E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.175696E+10 | 81.26 | 0.00 | 0.00 |
July | 0.109597E+12 | -0.107781E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.181528E+10 | 81.26 | 0.00 | 0.00 |
August | 0.108977E+12 | -0.107162E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.181493E+10 | 81.26 | 0.00 | 0.00 |
September | 0.106385E+12 | -0.104629E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.175564E+10 | 81.26 | 0.00 | 0.00 |
October | 0.112187E+12 | -0.110374E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.181336E+10 | 81.26 | 0.00 | 0.00 |
November | 0.111419E+12 | -0.109665E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.175421E+10 | 81.26 | 0.00 | 0.00 |
December | 0.117982E+12 | -0.116169E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.181378E+10 | 81.26 | 0.00 | 0.00 |
Annual Sum or Average | 0.135115E+13 | -0.132979E+13 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.213672E+11 | 81.26 | 0.00 | 0.00 |
Minimum of Months | 0.106385E+12 | -0.118179E+12 | 0.00 | 0.00 | 672.00 | 0.00 | -0.181570E+10 | 81.26 | 0.00 | 0.00 |
Maximum of Months | 0.119994E+12 | -0.104629E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.163955E+10 | 81.27 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.710012E+11 | -0.694167E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.158450E+10 | 58.98 | 0.00 | 0.00 |
February | 0.645801E+11 | -0.631484E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.143171E+10 | 58.98 | 0.00 | 0.00 |
March | 0.707570E+11 | -0.691713E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.158566E+10 | 58.98 | 0.00 | 0.00 |
April | 0.665877E+11 | -0.650527E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.153500E+10 | 58.98 | 0.00 | 0.00 |
May | 0.662894E+11 | -0.647033E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.158612E+10 | 58.98 | 0.00 | 0.00 |
June | 0.617923E+11 | -0.602576E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.153469E+10 | 58.98 | 0.00 | 0.00 |
July | 0.620651E+11 | -0.604794E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.158563E+10 | 58.98 | 0.00 | 0.00 |
August | 0.615941E+11 | -0.600091E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.158501E+10 | 58.98 | 0.00 | 0.00 |
September | 0.603698E+11 | -0.588369E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.153291E+10 | 58.98 | 0.00 | 0.00 |
October | 0.642950E+11 | -0.627122E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.158281E+10 | 58.98 | 0.00 | 0.00 |
November | 0.646737E+11 | -0.631427E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.153100E+10 | 58.98 | 0.00 | 0.00 |
December | 0.692747E+11 | -0.676912E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.158349E+10 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.783280E+12 | -0.764622E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.186585E+11 | 58.98 | 0.00 | 0.00 |
Minimum of Months | 0.603698E+11 | -0.694167E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.158612E+10 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.710012E+11 | -0.588369E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.143171E+10 | 58.98 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 237.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 259.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 247.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 379.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 427.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 375.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 471.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 366.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 301.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 245.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 242.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 160.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3714.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 160.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 471.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.292916E+10 | 48840.17 | 07-JAN-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.241602E+10 | 59629.82 | 19-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.149757E+09 | 16948.03 | 21-MAR-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.233886E+09 | 16997.42 | 20-APR-12:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.301266E+09 | 18505.51 | 22-MAY-10:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.176889E+09 | 17511.07 | 04-JUN-08:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 70084933.44 | 11759.36 | 10-JUL-06:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.109507E+09 | 17985.96 | 03-AUG-09:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.331823E+09 | 17362.16 | 19-SEP-08:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.378358E+09 | 17196.72 | 19-OCT-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.198433E+09 | 16994.70 | 01-NOV-11:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.649415E+09 | 24351.42 | 26-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.794460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 70084933.44 | 11759.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.292916E+10 | 59629.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BASEMENT VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.666352E+10 | 8706.30 | 30-JAN-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.736143E+10 | 8791.59 | 27-FEB-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.966417E+10 | 8860.69 | 14-MAR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.104755E+11 | 8946.96 | 27-APR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.107155E+11 | 8957.49 | 14-MAY-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.966075E+10 | 8967.59 | 10-JUN-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.913834E+10 | 8996.88 | 24-JUL-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.804253E+10 | 9001.11 | 10-AUG-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.583904E+10 | 8957.66 | 10-SEP-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.416990E+10 | 8889.42 | 04-OCT-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.327634E+10 | 8151.59 | 04-NOV-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.478219E+10 | 8055.92 | 04-DEC-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.897892E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.327634E+10 | 8055.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.107155E+11 | 9001.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.769246E+10 | 3181.06 | 29-JAN-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.612078E+10 | 3180.58 | 22-FEB-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.611368E+10 | 3190.68 | 12-MAR-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.518119E+10 | 3140.59 | 18-APR-03:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.495883E+10 | 3057.67 | 17-MAY-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.451620E+10 | 3012.66 | 14-JUN-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.403750E+10 | 2947.73 | 12-JUL-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.389934E+10 | 2871.39 | 22-AUG-07:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.430748E+10 | 3211.51 | 18-SEP-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.552130E+10 | 3196.21 | 21-OCT-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.682294E+10 | 3190.20 | 01-NOV-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.747922E+10 | 3179.30 | 24-DEC-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.666509E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.389934E+10 | 2871.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.769246E+10 | 3211.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_2_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.178843E+10 | 1303.93 | 17-JAN-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.140248E+10 | 1284.51 | 17-FEB-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130079E+10 | 1229.81 | 24-MAR-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.105549E+10 | 1267.15 | 19-APR-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.932484E+09 | 1227.33 | 18-MAY-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.819028E+09 | 1214.68 | 09-JUN-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.682197E+09 | 1203.23 | 18-JUL-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.665905E+09 | 1167.20 | 22-AUG-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.776553E+09 | 1151.88 | 18-SEP-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.112052E+10 | 1187.95 | 18-OCT-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.145722E+10 | 1213.35 | 30-NOV-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.172161E+10 | 1293.54 | 26-DEC-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.137227E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.665905E+09 | 1151.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.178843E+10 | 1303.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: MECH_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.294261E+10 | 1615.62 | 07-JAN-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.242597E+10 | 1639.82 | 19-FEB-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.227373E+10 | 1563.74 | 25-MAR-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.185087E+10 | 1508.07 | 19-APR-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.157015E+10 | 1357.17 | 20-MAY-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124828E+10 | 1255.74 | 07-JUN-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.105632E+10 | 1213.58 | 05-JUL-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.990085E+09 | 1202.88 | 05-AUG-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.136741E+10 | 1275.21 | 28-SEP-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.191772E+10 | 1358.57 | 16-OCT-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.234615E+10 | 1474.50 | 13-NOV-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.284090E+10 | 1557.13 | 26-DEC-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.228302E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.990085E+09 | 1202.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.294261E+10 | 1639.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: STORAGE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.195021E+10 | 943.60 | 07-JAN-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.161654E+10 | 950.41 | 19-FEB-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.154007E+10 | 881.61 | 25-MAR-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.126186E+10 | 859.10 | 19-APR-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.108026E+10 | 785.57 | 18-MAY-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.860789E+09 | 720.82 | 07-JUN-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.728397E+09 | 656.14 | 05-JUL-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.685579E+09 | 661.48 | 04-AUG-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.947778E+09 | 725.85 | 27-SEP-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.131862E+10 | 777.16 | 30-OCT-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.158864E+10 | 868.57 | 13-NOV-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.189147E+10 | 931.75 | 26-DEC-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.154702E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.685579E+09 | 656.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.195021E+10 | 950.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LAUNDRY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.133256E+11 | 12275.70 | 17-JAN-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.118146E+11 | 12098.72 | 21-FEB-04:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.128906E+11 | 12718.03 | 14-MAR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.125691E+11 | 12842.02 | 27-APR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.131098E+11 | 12857.08 | 14-MAY-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.127797E+11 | 12871.77 | 10-JUN-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.133387E+11 | 12913.82 | 24-JUL-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.133165E+11 | 12919.90 | 10-AUG-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.126519E+11 | 12857.49 | 10-SEP-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.127202E+11 | 12759.23 | 04-OCT-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.124564E+11 | 12502.27 | 04-NOV-10:45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.132453E+11 | 12276.17 | 26-DEC-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.154218E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.118146E+11 | 12098.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.133387E+11 | 12919.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAFE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.176364E+11 | 10348.29 | 29-JAN-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.133293E+11 | 10428.21 | 24-FEB-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.128552E+11 | 10443.19 | 09-MAR-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.106858E+11 | 10388.03 | 03-APR-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.103250E+11 | 10398.70 | 17-MAY-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.941829E+10 | 10386.06 | 14-JUN-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.832422E+10 | 10463.00 | 12-JUL-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.779680E+10 | 10192.27 | 01-AUG-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.863314E+10 | 10461.59 | 01-SEP-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.113990E+11 | 10406.71 | 10-OCT-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.151675E+11 | 10390.93 | 03-NOV-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.170345E+11 | 10332.75 | 17-DEC-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.142605E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.779680E+10 | 10192.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.176364E+11 | 10463.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LOBBY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.291894E+11 | 25825.03 | 17-JAN-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.219957E+11 | 25604.95 | 17-FEB-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.204121E+11 | 24720.77 | 07-MAR-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.169909E+11 | 24893.29 | 17-APR-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.160318E+11 | 24134.24 | 01-MAY-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.147165E+11 | 24251.79 | 14-JUN-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.131931E+11 | 23264.43 | 12-JUL-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.124877E+11 | 22807.03 | 01-AUG-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.132146E+11 | 25139.54 | 18-SEP-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.175686E+11 | 24260.28 | 17-OCT-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.238663E+11 | 25582.57 | 30-NOV-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.279660E+11 | 26383.17 | 26-DEC-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.227633E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.124877E+11 | 22807.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.291894E+11 | 26383.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.175362E+11 | 9687.87 | 17-JAN-09:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.126304E+11 | 9555.24 | 17-FEB-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.100799E+11 | 8324.13 | 05-MAR-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.617180E+10 | 7475.95 | 11-APR-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.397591E+10 | 6418.31 | 18-MAY-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.220379E+10 | 6028.36 | 14-JUN-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.102714E+10 | 5118.95 | 12-JUL-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.969284E+09 | 4813.90 | 20-AUG-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.307046E+10 | 6928.04 | 26-SEP-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.780547E+10 | 7734.62 | 27-OCT-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.134181E+11 | 9441.07 | 30-NOV-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.166640E+11 | 9690.36 | 17-DEC-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.955525E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.969284E+09 | 4813.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.175362E+11 | 9690.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.130663E+11 | 6368.49 | 06-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.102572E+11 | 6368.41 | 18-FEB-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.919517E+10 | 5386.10 | 01-MAR-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.687172E+10 | 5057.91 | 18-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.540909E+10 | 4488.42 | 18-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.396853E+10 | 4049.01 | 14-JUN-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.298335E+10 | 3659.63 | 12-JUL-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.305562E+10 | 3481.51 | 22-AUG-07:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.484472E+10 | 4489.01 | 27-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.795116E+10 | 4804.83 | 16-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.105519E+11 | 5949.36 | 24-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.126879E+11 | 6369.00 | 26-DEC-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.908428E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.298335E+10 | 3481.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.130663E+11 | 6369.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BANQUET_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.369552E+10 | 7146.51 | 20-JAN-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.271035E+10 | 6987.80 | 09-FEB-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.205656E+10 | 7000.03 | 14-MAR-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.121633E+10 | 6474.70 | 25-APR-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.730569E+09 | 5884.28 | 11-MAY-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.524506E+09 | 5496.06 | 19-JUN-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.396314E+09 | 5541.46 | 31-JUL-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.543199E+09 | 5841.19 | 22-AUG-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.904802E+09 | 6025.95 | 08-SEP-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174984E+10 | 6557.64 | 03-OCT-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.263728E+10 | 6467.95 | 15-NOV-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.347871E+10 | 6821.76 | 05-DEC-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.206440E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.396314E+09 | 5496.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.369552E+10 | 7146.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: DINING_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.302021E+10 | 6706.77 | 20-JAN-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.214750E+10 | 6618.86 | 09-FEB-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.150118E+10 | 6518.95 | 14-MAR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.767452E+09 | 5930.61 | 19-APR-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.382440E+09 | 5279.06 | 11-MAY-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.246342E+09 | 4883.66 | 19-JUN-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.196129E+09 | 4924.25 | 31-JUL-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.269431E+09 | 5273.79 | 22-AUG-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.523575E+09 | 5548.12 | 08-SEP-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.123262E+10 | 6109.35 | 03-OCT-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.207607E+10 | 6025.23 | 15-NOV-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.281656E+10 | 6329.80 | 05-DEC-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.151795E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.196129E+09 | 4883.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.302021E+10 | 6706.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: KITCHEN_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.210222E+10 | 5544.84 | 16-JAN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.176506E+10 | 5660.41 | 19-FEB-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.162138E+10 | 4581.57 | 05-MAR-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.133984E+10 | 4438.54 | 18-APR-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.117235E+10 | 4063.76 | 18-MAY-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.892372E+09 | 3662.03 | 15-JUN-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.808225E+09 | 3139.71 | 04-JUL-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.721647E+09 | 3230.20 | 03-AUG-02:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.949832E+09 | 3906.55 | 27-SEP-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.137744E+10 | 4291.84 | 31-OCT-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.168026E+10 | 4789.12 | 13-NOV-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.203650E+10 | 5305.38 | 26-DEC-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.164671E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.721647E+09 | 3139.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.210222E+10 | 5660.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: FLR_3_DOAS HEATING COIL
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.399465E+11 | 17252.96 | 07-JAN-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.324164E+11 | 17671.02 | 19-FEB-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.323836E+11 | 16431.91 | 01-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.237749E+11 | 15856.35 | 19-APR-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.167172E+11 | 15174.12 | 11-MAY-03:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.658003E+10 | 14178.50 | 15-JUN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.227446E+10 | 8711.93 | 07-JUL-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.176384E+10 | 8977.60 | 21-AUG-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.701031E+10 | 14460.88 | 27-SEP-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.217068E+11 | 14868.26 | 13-OCT-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.308037E+11 | 16283.32 | 11-NOV-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.389756E+11 | 16707.64 | 26-DEC-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.254353E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.176384E+10 | 8711.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.399465E+11 | 17671.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.388035E+10 | 5489.00 | 01-JAN-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.239701E+10 | 5488.54 | 16-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.125404E+10 | 5467.95 | 05-MAR-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.516818E+09 | 5386.57 | 18-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.161874E+09 | 5323.35 | 18-MAY-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 31885046.40 | 3583.01 | 04-JUN-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6720242.68 | 3371.54 | 13-JUL-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 8034594.79 | 2909.59 | 21-AUG-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 58051950.41 | 3400.38 | 26-SEP-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.558826E+09 | 5344.40 | 27-OCT-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.208417E+10 | 5488.86 | 30-NOV-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.350214E+10 | 5489.90 | 16-DEC-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144599E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 6720242.68 | 2909.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.388035E+10 | 5489.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.447628E+10 | 5410.21 | 03-JAN-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.300067E+10 | 5409.96 | 15-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.163828E+10 | 5408.97 | 05-MAR-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.667410E+09 | 5314.29 | 18-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.195595E+09 | 5248.43 | 18-MAY-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 37306950.18 | 3462.73 | 18-JUN-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5897461.86 | 3399.87 | 16-JUL-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 9388517.19 | 2953.25 | 29-AUG-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 80201995.21 | 4319.99 | 28-SEP-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.815521E+09 | 5290.94 | 30-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.250814E+10 | 5409.96 | 30-NOV-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.409255E+10 | 5411.04 | 16-DEC-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.175273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 5897461.86 | 2953.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.447628E+10 | 5411.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.414695E+10 | 14804.52 | 16-JAN-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.173169E+10 | 21184.10 | 19-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.130196E+09 | 4391.00 | 30-NOV-16:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.373314E+10 | 15750.97 | 26-DEC-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.974198E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.414695E+10 | 21184.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.132650E+11 | 30385.85 | 15-JAN-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.911529E+10 | 30250.25 | 13-FEB-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.207381E+10 | 29358.54 | 05-MAR-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.501143E+09 | 22848.65 | 19-APR-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 75426298.89 | 22455.76 | 04-MAY-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 30121412.49 | 20385.44 | 04-JUN-15:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 27696868.45 | 20792.01 | 14-JUL-08:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 29604583.41 | 25636.38 | 21-AUG-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 74621308.77 | 28396.05 | 30-SEP-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.210591E+09 | 28043.16 | 01-OCT-15:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.418333E+10 | 29976.35 | 30-NOV-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.102485E+11 | 30513.78 | 26-DEC-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.398352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 27696868.45 | 20385.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.132650E+11 | 30513.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.395245E+10 | 5408.55 | 23-JAN-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.243153E+10 | 5407.72 | 16-FEB-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.123764E+10 | 5378.84 | 05-MAR-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.500947E+09 | 5298.32 | 18-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.200939E+09 | 5241.77 | 18-MAY-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 35508703.84 | 3157.54 | 23-JUN-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6291603.58 | 3132.72 | 29-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 9684141.61 | 2908.43 | 20-AUG-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 75167273.65 | 2964.71 | 16-SEP-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.585068E+09 | 5268.10 | 31-OCT-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.212496E+10 | 5408.36 | 30-NOV-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.357311E+10 | 5409.44 | 16-DEC-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.147333E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 6291603.58 | 2908.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.395245E+10 | 5409.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.454488E+10 | 5331.09 | 25-JAN-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.302676E+10 | 5330.02 | 16-FEB-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.157740E+10 | 5324.11 | 05-MAR-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.636225E+09 | 5227.30 | 18-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.244666E+09 | 5168.06 | 18-MAY-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 43053708.22 | 2985.87 | 23-JUN-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 8617024.31 | 3294.51 | 29-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 12248846.26 | 3437.78 | 02-AUG-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.112268E+09 | 3571.22 | 30-SEP-15:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.839695E+09 | 5220.14 | 30-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.252795E+10 | 5330.70 | 30-NOV-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.414880E+10 | 5331.82 | 16-DEC-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.177226E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 8617024.31 | 2985.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.454488E+10 | 5331.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.140286E+10 | 1672.77 | 03-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.893804E+09 | 1672.68 | 15-FEB-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.503556E+09 | 1672.25 | 05-MAR-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.217061E+09 | 1663.24 | 18-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 77365611.80 | 1641.11 | 18-MAY-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16289358.57 | 805.68 | 04-JUN-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 1958069.37 | 991.91 | 09-JUL-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 2858188.82 | 912.88 | 20-AUG-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 30371858.66 | 1132.10 | 28-SEP-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.255810E+09 | 1649.97 | 27-OCT-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.806025E+09 | 1672.65 | 17-NOV-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.128232E+10 | 1672.80 | 16-DEC-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.549028E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 1958069.37 | 805.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.140286E+10 | 1672.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.158363E+10 | 1643.83 | 03-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.108746E+10 | 1643.78 | 22-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.632192E+09 | 1643.55 | 05-MAR-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.271712E+09 | 1635.94 | 18-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 89773099.69 | 1612.94 | 18-MAY-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 19000343.83 | 822.45 | 30-JUN-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 2009182.78 | 804.32 | 09-JUL-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 3817704.09 | 873.52 | 20-AUG-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 41554387.11 | 1590.05 | 28-SEP-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.353346E+09 | 1627.91 | 30-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.945066E+09 | 1643.80 | 20-NOV-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.147365E+10 | 1643.85 | 16-DEC-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.650322E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 2009182.78 | 804.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.158363E+10 | 1643.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.425497E+10 | 8213.50 | 01-JAN-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.243200E+10 | 8212.31 | 17-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.107749E+10 | 8087.00 | 05-MAR-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.472785E+09 | 8014.80 | 18-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.152165E+09 | 7926.77 | 18-MAY-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 26107389.01 | 5317.98 | 30-JUN-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 8854307.65 | 5060.17 | 13-JUL-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 9188114.53 | 4884.66 | 21-AUG-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 44404726.55 | 5314.02 | 18-SEP-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.343881E+09 | 7920.32 | 27-OCT-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.197826E+10 | 8213.23 | 29-NOV-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.386868E+10 | 8213.40 | 27-DEC-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.146688E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 8854307.65 | 4884.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.425497E+10 | 8213.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.149079E+09 | 0.149079E+09 | 18069.79 | 11-JAN-14:00 | 18069.79 | 0.00 |
February | 0.00 | 0.00 | 0.463944E+10 | 0.463944E+10 | 172102.26 | 27-FEB-15:00 | 172102.26 | 0.04 |
March | 0.00 | 0.00 | 0.100727E+11 | 0.100727E+11 | 206927.54 | 18-MAR-16:00 | 206927.54 | 0.02 |
April | 0.00 | 0.00 | 0.568250E+11 | 0.568250E+11 | 301180.27 | 27-APR-18:10 | 301180.27 | 0.08 |
May | 0.00 | 0.00 | 0.113180E+12 | 0.110831E+12 | 345747.00 | 06-MAY-10:40 | 259745.60 | 0.26 |
June | 0.00 | 0.00 | 0.194846E+12 | 0.193848E+12 | 318742.20 | 28-JUN-18:10 | 304983.94 | 0.56 |
July | 0.00 | 0.00 | 0.317725E+12 | 0.302034E+12 | 424245.15 | 31-JUL-10:35 | 307997.83 | 0.79 |
August | 0.00 | 0.00 | 0.389455E+12 | 0.362819E+12 | 438238.59 | 29-AUG-10:35 | 317681.08 | 0.89 |
September | 0.00 | 0.00 | 0.167291E+12 | 0.157644E+12 | 386279.48 | 14-SEP-10:50 | 227775.41 | 0.60 |
October | 0.00 | 0.00 | 0.373890E+11 | 0.371777E+11 | 231342.92 | 04-OCT-15:30 | 231342.92 | 0.14 |
November | 0.00 | 0.00 | 0.851776E+10 | 0.825098E+10 | 219123.82 | 04-NOV-16:00 | 190732.99 | 0.05 |
December | 0.00 | 0.00 | 793.93 | 793.93 | 0.74 | 05-DEC-19:05 | 0.74 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.130009E+13 | 0.124429E+13 | 0.29 | |||
Minimum of Months | 0.00 | 0.00 | 793.93 | 793.93 | 0.74 | 0.74 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.389455E+12 | 0.362819E+12 | 438238.59 | 317681.08 | 0.89 |
Report: CoilReportMonthly
For: FLR_3_DOAS COOLING COIL
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.332454E+09 | 0.332454E+09 | 18783.03 | 27-FEB-15:00 | 18783.03 | 0.01 |
March | 0.00 | 0.00 | 0.656261E+09 | 0.656261E+09 | 20929.09 | 18-MAR-16:00 | 20929.09 | 0.02 |
April | 0.00 | 0.00 | 0.509175E+10 | 0.509043E+10 | 38901.17 | 27-APR-15:00 | 37978.19 | 0.06 |
May | 0.00 | 0.00 | 0.995405E+10 | 0.940109E+10 | 40101.20 | 06-MAY-13:00 | 29867.61 | 0.20 |
June | 0.00 | 0.00 | 0.171572E+11 | 0.171322E+11 | 36703.11 | 28-JUN-17:00 | 36703.11 | 0.45 |
July | 0.00 | 0.00 | 0.325768E+11 | 0.295800E+11 | 48686.52 | 31-JUL-16:00 | 40484.84 | 0.68 |
August | 0.00 | 0.00 | 0.432885E+11 | 0.381817E+11 | 52757.23 | 29-AUG-13:00 | 39142.88 | 0.80 |
September | 0.00 | 0.00 | 0.149007E+11 | 0.134871E+11 | 42472.65 | 23-SEP-14:00 | 28243.81 | 0.46 |
October | 0.00 | 0.00 | 0.254401E+10 | 0.253777E+10 | 24147.80 | 04-OCT-15:00 | 24147.80 | 0.09 |
November | 0.00 | 0.00 | 0.658445E+09 | 0.579603E+09 | 28029.87 | 04-NOV-13:50 | 22649.57 | 0.03 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.127160E+12 | 0.116979E+12 | 0.23 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.432885E+11 | 0.381817E+11 | 52757.23 | 40484.84 | 0.80 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 7995779.41 | 7213503.43 | 10598.30 | 20-JAN-16:02 | 10598.30 | 0.00 |
February | 0.00 | 0.00 | 0.257225E+09 | 0.169827E+09 | 18054.12 | 06-FEB-16:01 | 18054.12 | 0.06 |
March | 0.00 | 0.00 | 0.992121E+09 | 0.853128E+09 | 18062.86 | 17-MAR-15:02 | 18062.86 | 0.09 |
April | 0.00 | 0.00 | 0.265297E+10 | 0.188160E+10 | 18696.57 | 30-APR-08:62 | 15480.01 | 0.34 |
May | 0.00 | 0.00 | 0.454257E+10 | 0.286637E+10 | 18315.48 | 05-MAY-18:02 | 16975.00 | 0.63 |
June | 0.00 | 0.00 | 0.518647E+10 | 0.296430E+10 | 19780.01 | 12-JUN-15:01 | 15776.93 | 0.79 |
July | 0.00 | 0.00 | 0.815897E+10 | 0.491990E+10 | 19713.86 | 16-JUL-15:01 | 16213.29 | 0.90 |
August | 0.00 | 0.00 | 0.795174E+10 | 0.470166E+10 | 19419.48 | 26-AUG-08:62 | 14928.39 | 0.88 |
September | 0.00 | 0.00 | 0.527319E+10 | 0.293080E+10 | 19238.24 | 23-SEP-08:61 | 15519.81 | 0.76 |
October | 0.00 | 0.00 | 0.169402E+10 | 0.989663E+09 | 19128.88 | 01-OCT-15:02 | 16533.46 | 0.34 |
November | 0.00 | 0.00 | 0.218572E+09 | 97952419.50 | 18223.42 | 05-NOV-15:01 | 16643.17 | 0.07 |
December | 0.00 | 0.00 | 29381548.42 | 27704213.62 | 17544.64 | 05-DEC-16:02 | 17544.64 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.369652E+11 | 0.224101E+11 | 0.40 | |||
Minimum of Months | 0.00 | 0.00 | 7995779.41 | 7213503.43 | 10598.30 | 10598.30 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.815897E+10 | 0.491990E+10 | 19780.01 | 18062.86 | 0.90 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 1234250.36 | 829518.82 | 1899.11 | 11-JAN-19:05 | 757.96 | 0.00 |
February | 0.00 | 0.00 | 72187748.34 | 36124874.55 | 13393.94 | 06-FEB-16:01 | 13393.94 | 0.03 |
March | 0.00 | 0.00 | 0.414196E+09 | 0.364389E+09 | 16358.46 | 02-MAR-16:02 | 16358.46 | 0.05 |
April | 0.00 | 0.00 | 0.175539E+10 | 0.124472E+10 | 16903.51 | 30-APR-08:62 | 13817.56 | 0.26 |
May | 0.00 | 0.00 | 0.367400E+10 | 0.235060E+10 | 16645.45 | 05-MAY-18:02 | 15348.06 | 0.56 |
June | 0.00 | 0.00 | 0.452053E+10 | 0.266188E+10 | 17855.63 | 12-JUN-15:01 | 14182.40 | 0.72 |
July | 0.00 | 0.00 | 0.714134E+10 | 0.440867E+10 | 17804.19 | 16-JUL-15:01 | 14584.45 | 0.84 |
August | 0.00 | 0.00 | 0.654420E+10 | 0.380323E+10 | 17615.22 | 26-AUG-08:62 | 13453.82 | 0.81 |
September | 0.00 | 0.00 | 0.356622E+10 | 0.187636E+10 | 17823.02 | 24-SEP-15:01 | 14707.65 | 0.65 |
October | 0.00 | 0.00 | 0.758790E+09 | 0.437479E+09 | 17621.43 | 01-OCT-15:02 | 14817.42 | 0.19 |
November | 0.00 | 0.00 | 83486680.11 | 32058970.49 | 16844.07 | 04-NOV-15:02 | 15241.55 | 0.04 |
December | 0.00 | 0.00 | 2055805.48 | 1475950.67 | 2279.93 | 28-DEC-19:05 | 945.34 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.285336E+11 | 0.172178E+11 | 0.35 | |||
Minimum of Months | 0.00 | 0.00 | 1234250.36 | 829518.82 | 1899.11 | 757.96 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.714134E+10 | 0.440867E+10 | 17855.63 | 16358.46 | 0.84 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 13122006.87 | 13122006.87 | 3918.32 | 08-JAN-14:50 | 3918.32 | 0.00 |
February | 0.00 | 0.00 | 0.461951E+10 | 0.414785E+10 | 41405.66 | 08-FEB-14:30 | 41405.66 | 0.03 |
March | 0.00 | 0.00 | 0.129596E+11 | 0.127892E+11 | 55439.84 | 02-MAR-13:00 | 55439.84 | 0.01 |
April | 0.00 | 0.00 | 0.215672E+11 | 0.171832E+11 | 50696.10 | 27-APR-13:30 | 45173.90 | 0.25 |
May | 0.00 | 0.00 | 0.265287E+11 | 0.177316E+11 | 50509.58 | 04-MAY-13:10 | 42984.85 | 0.44 |
June | 0.00 | 0.00 | 0.277870E+11 | 0.134572E+11 | 36977.71 | 28-JUN-13:00 | 24732.04 | 0.69 |
July | 0.00 | 0.00 | 0.387622E+11 | 0.194244E+11 | 49029.23 | 31-JUL-13:10 | 39102.30 | 0.80 |
August | 0.00 | 0.00 | 0.442249E+11 | 0.238116E+11 | 64574.12 | 24-AUG-14:40 | 53138.18 | 0.87 |
September | 0.00 | 0.00 | 0.397958E+11 | 0.223528E+11 | 65125.25 | 23-SEP-14:40 | 53064.59 | 0.80 |
October | 0.00 | 0.00 | 0.243317E+11 | 0.184958E+11 | 65959.58 | 04-OCT-12:30 | 65959.58 | 0.31 |
November | 0.00 | 0.00 | 0.392785E+10 | 0.244784E+10 | 56349.42 | 04-NOV-13:30 | 49959.06 | 0.08 |
December | 0.00 | 0.00 | 0.219222E+10 | 0.218552E+10 | 42121.65 | 05-DEC-12:30 | 42121.65 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.246710E+12 | 0.154040E+12 | 0.36 | |||
Minimum of Months | 0.00 | 0.00 | 13122006.87 | 13122006.87 | 3918.32 | 3918.32 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.442249E+11 | 0.238116E+11 | 65959.58 | 65959.58 | 0.87 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.185637E+10 | 0.119957E+10 | 71396.72 | 28-JAN-09:02 | 71396.72 | 0.07 |
February | 0.00 | 0.00 | 0.525760E+10 | 0.283402E+10 | 81242.00 | 25-FEB-09:02 | 78617.60 | 0.19 |
March | 0.00 | 0.00 | 0.124520E+11 | 0.945383E+10 | 81115.27 | 19-MAR-18:02 | 81115.27 | 0.23 |
April | 0.00 | 0.00 | 0.241707E+11 | 0.181049E+11 | 85694.50 | 30-APR-15:02 | 76457.75 | 0.42 |
May | 0.00 | 0.00 | 0.381423E+11 | 0.268465E+11 | 88398.79 | 05-MAY-18:02 | 80029.56 | 0.63 |
June | 0.00 | 0.00 | 0.462391E+11 | 0.323576E+11 | 92440.23 | 12-JUN-15:01 | 75412.49 | 0.69 |
July | 0.00 | 0.00 | 0.552718E+11 | 0.378622E+11 | 91602.61 | 16-JUL-18:03 | 69288.37 | 0.71 |
August | 0.00 | 0.00 | 0.547346E+11 | 0.354067E+11 | 94139.30 | 30-AUG-08:62 | 67403.55 | 0.71 |
September | 0.00 | 0.00 | 0.380006E+11 | 0.223965E+11 | 91004.22 | 24-SEP-15:01 | 73773.76 | 0.70 |
October | 0.00 | 0.00 | 0.203716E+11 | 0.118118E+11 | 88607.90 | 01-OCT-15:02 | 74607.66 | 0.60 |
November | 0.00 | 0.00 | 0.901369E+10 | 0.450944E+10 | 86809.99 | 03-NOV-18:03 | 72644.24 | 0.32 |
December | 0.00 | 0.00 | 0.173674E+10 | 0.108704E+10 | 78853.78 | 03-DEC-09:02 | 78853.78 | 0.07 |
Annual Sum or Average | 0.00 | 0.00 | 0.307247E+12 | 0.203870E+12 | 0.45 | |||
Minimum of Months | 0.00 | 0.00 | 0.173674E+10 | 0.108704E+10 | 71396.72 | 67403.55 | 0.07 | |
Maximum of Months | 0.00 | 0.00 | 0.552718E+11 | 0.378622E+11 | 94139.30 | 81115.27 | 0.71 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 6082869.53 | 5245904.74 | 2365.22 | 10-JAN-09:03 | 2365.22 | 0.00 |
February | 0.00 | 0.00 | 0.221620E+09 | 0.147343E+09 | 15337.87 | 08-FEB-16:02 | 15337.87 | 0.06 |
March | 0.00 | 0.00 | 0.937937E+09 | 0.786982E+09 | 16260.43 | 02-MAR-16:02 | 16260.43 | 0.09 |
April | 0.00 | 0.00 | 0.270521E+10 | 0.186484E+10 | 16866.75 | 30-APR-08:62 | 13931.54 | 0.37 |
May | 0.00 | 0.00 | 0.393121E+10 | 0.233067E+10 | 16812.01 | 07-MAY-08:62 | 15024.29 | 0.62 |
June | 0.00 | 0.00 | 0.558550E+10 | 0.322998E+10 | 17931.47 | 12-JUN-15:01 | 14496.53 | 0.83 |
July | 0.00 | 0.00 | 0.703150E+10 | 0.403159E+10 | 17484.33 | 16-JUL-15:01 | 14148.60 | 0.91 |
August | 0.00 | 0.00 | 0.784902E+10 | 0.459410E+10 | 17974.22 | 26-AUG-08:62 | 14473.71 | 0.89 |
September | 0.00 | 0.00 | 0.477217E+10 | 0.262790E+10 | 17893.92 | 24-SEP-15:01 | 14521.09 | 0.74 |
October | 0.00 | 0.00 | 0.166026E+10 | 0.962868E+09 | 17283.48 | 01-OCT-15:02 | 14394.63 | 0.35 |
November | 0.00 | 0.00 | 0.235544E+09 | 96594406.98 | 16612.56 | 04-NOV-15:02 | 15220.46 | 0.07 |
December | 0.00 | 0.00 | 66885212.35 | 62611015.38 | 8441.91 | 02-DEC-09:02 | 8441.91 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.350030E+11 | 0.207407E+11 | 0.41 | |||
Minimum of Months | 0.00 | 0.00 | 6082869.53 | 5245904.74 | 2365.22 | 2365.22 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.784902E+10 | 0.459410E+10 | 17974.22 | 16260.43 | 0.91 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 1350191.13 | 864873.81 | 2004.79 | 10-JAN-19:05 | 2004.79 | 0.00 |
February | 0.00 | 0.00 | 39235768.09 | 14632698.80 | 9714.03 | 27-FEB-16:01 | 9094.36 | 0.03 |
March | 0.00 | 0.00 | 0.295483E+09 | 0.239515E+09 | 14353.91 | 02-MAR-09:02 | 14353.91 | 0.04 |
April | 0.00 | 0.00 | 0.173367E+10 | 0.115920E+10 | 15376.50 | 30-APR-08:62 | 12541.23 | 0.30 |
May | 0.00 | 0.00 | 0.304219E+10 | 0.180735E+10 | 15374.64 | 07-MAY-08:62 | 13711.55 | 0.55 |
June | 0.00 | 0.00 | 0.486205E+10 | 0.289040E+10 | 16390.98 | 12-JUN-15:01 | 13233.61 | 0.79 |
July | 0.00 | 0.00 | 0.597353E+10 | 0.345842E+10 | 15885.74 | 16-JUL-15:01 | 12790.84 | 0.88 |
August | 0.00 | 0.00 | 0.639180E+10 | 0.362510E+10 | 16454.63 | 26-AUG-08:62 | 13198.99 | 0.85 |
September | 0.00 | 0.00 | 0.303072E+10 | 0.153298E+10 | 15838.77 | 24-SEP-15:01 | 12458.87 | 0.63 |
October | 0.00 | 0.00 | 0.687525E+09 | 0.372441E+09 | 15257.39 | 01-OCT-15:02 | 12343.72 | 0.19 |
November | 0.00 | 0.00 | 65397147.58 | 16800306.35 | 11397.45 | 04-NOV-15:02 | 8592.08 | 0.04 |
December | 0.00 | 0.00 | 3303809.76 | 2490451.05 | 2268.16 | 28-DEC-19:05 | 987.10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.261263E+11 | 0.151202E+11 | 0.36 | |||
Minimum of Months | 0.00 | 0.00 | 1350191.13 | 864873.81 | 2004.79 | 987.10 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.639180E+10 | 0.362510E+10 | 16454.63 | 14353.91 | 0.88 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 1179814.33 | 1072532.42 | 2301.09 | 20-JAN-16:02 | 2301.09 | 0.00 |
February | 0.00 | 0.00 | 61779019.93 | 43642820.50 | 4787.17 | 06-FEB-16:01 | 4787.17 | 0.04 |
March | 0.00 | 0.00 | 0.253556E+09 | 0.224861E+09 | 4789.46 | 17-MAR-15:02 | 4789.46 | 0.07 |
April | 0.00 | 0.00 | 0.721167E+09 | 0.540503E+09 | 5102.73 | 30-APR-08:62 | 3910.33 | 0.30 |
May | 0.00 | 0.00 | 0.129121E+10 | 0.858337E+09 | 5014.79 | 07-MAY-08:62 | 4059.15 | 0.59 |
June | 0.00 | 0.00 | 0.150421E+10 | 0.914958E+09 | 5289.38 | 12-JUN-15:01 | 4263.26 | 0.78 |
July | 0.00 | 0.00 | 0.236282E+10 | 0.150518E+10 | 5224.71 | 16-JUL-15:01 | 4300.55 | 0.90 |
August | 0.00 | 0.00 | 0.227144E+10 | 0.141087E+10 | 5259.67 | 26-AUG-08:62 | 3859.52 | 0.88 |
September | 0.00 | 0.00 | 0.146187E+10 | 0.867944E+09 | 5299.37 | 23-SEP-08:61 | 3950.36 | 0.73 |
October | 0.00 | 0.00 | 0.426565E+09 | 0.264509E+09 | 4962.97 | 01-OCT-15:02 | 4443.42 | 0.27 |
November | 0.00 | 0.00 | 52383725.29 | 26158483.90 | 4886.13 | 05-NOV-15:01 | 4476.49 | 0.04 |
December | 0.00 | 0.00 | 4732181.24 | 4405715.62 | 4681.10 | 05-DEC-16:02 | 4681.10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.104129E+11 | 0.666244E+10 | 0.39 | |||
Minimum of Months | 0.00 | 0.00 | 1179814.33 | 1072532.42 | 2301.09 | 2301.09 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.236282E+10 | 0.150518E+10 | 5299.37 | 4789.46 | 0.90 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 203335.38 | 170612.49 | 572.28 | 05-JAN-16:04 | 572.28 | 0.00 |
February | 0.00 | 0.00 | 15491672.17 | 7514371.58 | 3482.26 | 26-FEB-16:01 | 3482.26 | 0.02 |
March | 0.00 | 0.00 | 98281255.55 | 89638645.76 | 4309.21 | 02-MAR-16:02 | 4309.21 | 0.03 |
April | 0.00 | 0.00 | 0.478747E+09 | 0.357628E+09 | 4453.48 | 30-APR-08:62 | 3308.24 | 0.22 |
May | 0.00 | 0.00 | 0.104712E+10 | 0.707380E+09 | 4499.83 | 07-MAY-08:62 | 3620.78 | 0.53 |
June | 0.00 | 0.00 | 0.131639E+10 | 0.821253E+09 | 4763.86 | 12-JUN-15:01 | 3834.97 | 0.73 |
July | 0.00 | 0.00 | 0.208094E+10 | 0.133511E+10 | 4704.87 | 16-JUL-15:01 | 3868.89 | 0.87 |
August | 0.00 | 0.00 | 0.188578E+10 | 0.115501E+10 | 4756.73 | 26-AUG-08:62 | 3460.66 | 0.84 |
September | 0.00 | 0.00 | 0.986030E+09 | 0.560049E+09 | 4723.37 | 23-SEP-08:61 | 3390.67 | 0.63 |
October | 0.00 | 0.00 | 0.183156E+09 | 0.114357E+09 | 4652.00 | 01-OCT-15:02 | 3897.42 | 0.15 |
November | 0.00 | 0.00 | 18701622.66 | 8394456.14 | 4443.93 | 04-NOV-15:02 | 4011.29 | 0.02 |
December | 0.00 | 0.00 | 401673.48 | 264507.05 | 689.76 | 03-DEC-16:03 | 689.76 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.811124E+10 | 0.515676E+10 | 0.34 | |||
Minimum of Months | 0.00 | 0.00 | 203335.38 | 170612.49 | 572.28 | 572.28 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.208094E+10 | 0.133511E+10 | 4763.86 | 4309.21 | 0.87 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.413314E+09 | 0.392951E+09 | 26172.40 | 20-JAN-16:02 | 26172.40 | 0.01 |
February | 0.00 | 0.00 | 0.195788E+10 | 0.158343E+10 | 26182.83 | 03-FEB-16:01 | 26182.83 | 0.12 |
March | 0.00 | 0.00 | 0.372079E+10 | 0.313103E+10 | 26182.41 | 23-MAR-15:01 | 26182.41 | 0.21 |
April | 0.00 | 0.00 | 0.579260E+10 | 0.409786E+10 | 26978.85 | 30-APR-15:02 | 23670.33 | 0.45 |
May | 0.00 | 0.00 | 0.736092E+10 | 0.436540E+10 | 27106.26 | 06-MAY-18:01 | 24308.45 | 0.70 |
June | 0.00 | 0.00 | 0.831283E+10 | 0.451504E+10 | 29002.71 | 12-JUN-15:01 | 23268.66 | 0.84 |
July | 0.00 | 0.00 | 0.116428E+11 | 0.654657E+10 | 28598.35 | 16-JUL-15:01 | 23498.71 | 0.90 |
August | 0.00 | 0.00 | 0.129468E+11 | 0.772409E+10 | 27876.30 | 26-AUG-18:01 | 23883.82 | 0.90 |
September | 0.00 | 0.00 | 0.105653E+11 | 0.646724E+10 | 27767.45 | 23-SEP-08:61 | 23947.29 | 0.82 |
October | 0.00 | 0.00 | 0.573345E+10 | 0.364641E+10 | 27646.14 | 01-OCT-08:62 | 22561.45 | 0.55 |
November | 0.00 | 0.00 | 0.147695E+10 | 0.949244E+09 | 26181.10 | 10-NOV-16:01 | 26181.10 | 0.17 |
December | 0.00 | 0.00 | 0.107244E+10 | 0.100771E+10 | 26178.16 | 06-DEC-16:01 | 26178.16 | 0.02 |
Annual Sum or Average | 0.00 | 0.00 | 0.709961E+11 | 0.444270E+11 | 0.48 | |||
Minimum of Months | 0.00 | 0.00 | 0.413314E+09 | 0.392951E+09 | 26172.40 | 22561.45 | 0.01 | |
Maximum of Months | 0.00 | 0.00 | 0.129468E+11 | 0.772409E+10 | 29002.71 | 26182.83 | 0.90 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 75935.08 | 179625.81 | 07-JAN-09:02 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 64190.16 | 176905.30 | 19-FEB-07:10 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 49635.16 | 135273.25 | 05-MAR-16:02 |
April | 0.00 | 0.00 | 01-APR-00:10 | 39886.86 | 113328.25 | 18-APR-08:62 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 32814.85 | 98794.85 | 18-MAY-08:62 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 26350.58 | 92990.85 | 13-JUN-10:40 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21599.64 | 85028.31 | 12-JUL-10:40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 20518.17 | 83049.82 | 01-AUG-10:40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 25218.03 | 90880.64 | 18-SEP-10:40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 37740.64 | 101402.09 | 30-OCT-08:03 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 55729.42 | 141485.34 | 26-NOV-16:03 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 70441.11 | 178456.61 | 26-DEC-09:06 |
Annual Sum or Average | 0.00 | 43238.62 | ||||
Minimum of Months | 0.00 | 0.00 | 20518.17 | 83049.82 | ||
Maximum of Months | 0.00 | 0.00 | 75935.08 | 179625.81 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 1691.66 | 36497.52 | 11-JAN-19:03 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 9120.88 | 310178.07 | 27-FEB-16:01 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 19208.05 | 390315.07 | 18-MAR-15:02 | 0.00 | 0.00 | 01-MAR-00:03 |
April | 52349.95 | 535018.93 | 27-APR-15:03 | 0.00 | 0.00 | 01-APR-00:10 |
May | 84972.76 | 532344.26 | 05-MAY-18:03 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 128666.93 | 550881.28 | 28-JUN-18:03 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 189155.52 | 641251.82 | 27-JUL-18:03 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 222428.78 | 688924.49 | 10-AUG-18:03 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 117716.06 | 571543.65 | 23-SEP-18:02 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 40288.21 | 463203.29 | 04-OCT-15:02 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 11530.99 | 436477.98 | 04-NOV-15:02 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 2939.55 | 56752.47 | 05-DEC-12:30 | 0.00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 73820.61 | 0.00 | ||||
Minimum of Months | 1691.66 | 36497.52 | 0.00 | 0.00 | ||
Maximum of Months | 222428.78 | 688924.49 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 27483.16 | 55995.21 | 31-JAN-07:30 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 27669.51 | 56071.13 | 07-FEB-07:10 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 27391.73 | 55882.10 | 02-MAR-07:20 |
April | 0.00 | 0.00 | 01-APR-00:10 | 26665.40 | 54631.00 | 03-APR-06:40 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 25727.82 | 52937.77 | 01-MAY-06:30 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 24820.54 | 50885.09 | 01-JUN-06:20 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 24155.32 | 49140.30 | 03-JUL-06:10 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23979.87 | 48416.82 | 31-AUG-06:20 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 24273.47 | 49481.13 | 29-SEP-06:15 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 24986.48 | 51356.97 | 31-OCT-06:30 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25930.22 | 53374.03 | 30-NOV-07:10 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 26840.76 | 54992.97 | 29-DEC-07:50 |
Annual Sum or Average | 0.00 | 25816.31 | ||||
Minimum of Months | 0.00 | 0.00 | 23979.87 | 48416.82 | ||
Maximum of Months | 0.00 | 0.00 | 27669.51 | 56071.13 |
Report: FanReportMonthly
For: FLR_3_DOAS FAN
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.587890E+10 | 0.89 | 2194.93 | 01-JAN-00:05 | 0.89 |
February | 0.530997E+10 | 0.89 | 2194.93 | 01-FEB-00:03 | 0.89 |
March | 0.587890E+10 | 0.89 | 2194.93 | 01-MAR-00:03 | 0.89 |
April | 0.568926E+10 | 0.89 | 2194.93 | 01-APR-00:10 | 0.89 |
May | 0.587890E+10 | 0.89 | 2194.93 | 01-MAY-00:10 | 0.89 |
June | 0.568926E+10 | 0.89 | 2194.93 | 01-JUN-00:10 | 0.89 |
July | 0.587890E+10 | 0.88 | 2194.93 | 01-JUL-00:10 | 0.88 |
August | 0.587890E+10 | 0.88 | 2194.93 | 01-AUG-00:10 | 0.88 |
September | 0.568926E+10 | 0.88 | 2194.93 | 01-SEP-00:10 | 0.88 |
October | 0.587890E+10 | 0.89 | 2194.93 | 01-OCT-00:10 | 0.88 |
November | 0.568926E+10 | 0.89 | 2194.93 | 01-NOV-00:10 | 0.89 |
December | 0.587890E+10 | 0.89 | 2194.93 | 01-DEC-00:03 | 0.89 |
Annual Sum or Average | 0.692193E+11 | 0.89 | |||
Minimum of Months | 0.530997E+10 | 0.88 | 2194.93 | 0.88 | |
Maximum of Months | 0.587890E+10 | 0.89 | 2194.93 | 0.89 |
Report: FanReportMonthly
For: VAV WITH REHEAT FAN
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.136867E+12 | 1.86 | 51100.18 | 01-JAN-11:35 | 1.86 |
February | 0.123621E+12 | 1.86 | 51100.18 | 01-FEB-11:40 | 1.86 |
March | 0.136866E+12 | 1.86 | 51100.18 | 01-MAR-10:40 | 1.87 |
April | 0.132451E+12 | 1.86 | 51100.18 | 01-APR-09:10 | 1.86 |
May | 0.136866E+12 | 1.85 | 51100.18 | 01-MAY-10:40 | 1.85 |
June | 0.132451E+12 | 1.85 | 51100.18 | 01-JUN-07:30 | 1.85 |
July | 0.136867E+12 | 1.85 | 51100.18 | 01-JUL-10:40 | 1.85 |
August | 0.136867E+12 | 1.85 | 51100.18 | 01-AUG-06:20 | 1.85 |
September | 0.132451E+12 | 1.85 | 51100.18 | 01-SEP-07:05 | 1.84 |
October | 0.136866E+12 | 1.86 | 51100.18 | 01-OCT-10:40 | 1.85 |
November | 0.132451E+12 | 1.86 | 51100.18 | 01-NOV-10:35 | 1.85 |
December | 0.136867E+12 | 1.86 | 51100.18 | 01-DEC-11:35 | 1.86 |
Annual Sum or Average | 0.161149E+13 | 1.86 | |||
Minimum of Months | 0.123621E+12 | 1.85 | 51100.18 | 1.84 | |
Maximum of Months | 0.136867E+12 | 1.86 | 51100.18 | 1.87 |
Report: FanReportMonthly
For: LAUNDRY_FLR_1 EXHAUST FAN
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.493775E+09 | 0.65 | 184.35 | 01-JAN-00:05 | 0.65 |
February | 0.445990E+09 | 0.65 | 184.35 | 01-FEB-00:03 | 0.65 |
March | 0.493775E+09 | 0.65 | 184.35 | 01-MAR-00:03 | 0.65 |
April | 0.477847E+09 | 0.65 | 184.35 | 01-APR-00:10 | 0.65 |
May | 0.493775E+09 | 0.65 | 184.35 | 01-MAY-00:10 | 0.65 |
June | 0.477847E+09 | 0.65 | 184.35 | 01-JUN-00:10 | 0.65 |
July | 0.493775E+09 | 0.65 | 184.35 | 01-JUL-00:10 | 0.65 |
August | 0.493775E+09 | 0.64 | 184.35 | 01-AUG-00:10 | 0.64 |
September | 0.477847E+09 | 0.65 | 184.35 | 01-SEP-00:10 | 0.65 |
October | 0.493775E+09 | 0.65 | 184.35 | 01-OCT-00:10 | 0.65 |
November | 0.477847E+09 | 0.65 | 184.35 | 01-NOV-00:10 | 0.65 |
December | 0.493775E+09 | 0.65 | 184.35 | 01-DEC-00:03 | 0.65 |
Annual Sum or Average | 0.581380E+10 | 0.65 | |||
Minimum of Months | 0.445990E+09 | 0.64 | 184.35 | 0.64 | |
Maximum of Months | 0.493775E+09 | 0.65 | 184.35 | 0.65 |
Report: FanReportMonthly
For: LOBBY_FLR_1 EXHAUST FAN
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: BANQUET_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: DINING_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.279806E+10 | 0.46 | 1474.84 | 01-JAN-07:10 | 0.65 |
February | 0.252728E+10 | 0.46 | 1474.84 | 01-FEB-07:05 | 0.65 |
March | 0.279806E+10 | 0.46 | 1474.84 | 01-MAR-07:05 | 0.65 |
April | 0.270780E+10 | 0.46 | 1474.84 | 01-APR-06:10 | 0.65 |
May | 0.279806E+10 | 0.46 | 1474.84 | 01-MAY-06:05 | 0.65 |
June | 0.270780E+10 | 0.46 | 1474.84 | 01-JUN-06:05 | 0.65 |
July | 0.279806E+10 | 0.46 | 1474.84 | 01-JUL-06:10 | 0.65 |
August | 0.279806E+10 | 0.46 | 1474.84 | 01-AUG-06:05 | 0.64 |
September | 0.270780E+10 | 0.46 | 1474.84 | 01-SEP-06:05 | 0.64 |
October | 0.279806E+10 | 0.46 | 1474.84 | 01-OCT-06:10 | 0.64 |
November | 0.270780E+10 | 0.46 | 1474.84 | 01-NOV-06:05 | 0.64 |
December | 0.279806E+10 | 0.46 | 1474.84 | 01-DEC-07:05 | 0.65 |
Annual Sum or Average | 0.329449E+11 | 0.46 | |||
Minimum of Months | 0.252728E+10 | 0.46 | 1474.84 | 0.64 | |
Maximum of Months | 0.279806E+10 | 0.46 | 1474.84 | 0.65 |
Report: FanReportMonthly
For: ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.904098E+09 | 1.07 | 2180.47 | 01-JAN-09:02 | 1.40 |
February | 0.632822E+09 | 1.05 | 2180.47 | 01-FEB-09:02 | 1.40 |
March | 0.510644E+09 | 1.04 | 2180.47 | 01-MAR-09:02 | 1.41 |
April | 0.525723E+09 | 1.10 | 2180.47 | 01-APR-15:02 | 1.40 |
May | 0.655099E+09 | 1.17 | 2180.47 | 01-MAY-15:02 | 1.40 |
June | 0.673415E+09 | 1.19 | 2180.47 | 01-JUN-15:01 | 1.40 |
July | 0.973812E+09 | 1.26 | 2180.47 | 01-JUL-08:62 | 1.40 |
August | 0.923895E+09 | 1.23 | 2180.47 | 01-AUG-08:62 | 1.40 |
September | 0.655831E+09 | 1.17 | 2180.47 | 01-SEP-15:02 | 1.40 |
October | 0.430055E+09 | 1.07 | 2180.47 | 01-OCT-15:02 | 1.39 |
November | 0.583837E+09 | 1.03 | 2180.47 | 02-NOV-15:01 | 1.40 |
December | 0.843314E+09 | 1.08 | 2180.47 | 01-DEC-09:02 | 1.40 |
Annual Sum or Average | 0.831254E+10 | 1.12 | |||
Minimum of Months | 0.430055E+09 | 1.03 | 2180.47 | 1.39 | |
Maximum of Months | 0.973812E+09 | 1.26 | 2180.47 | 1.41 |
Report: FanReportMonthly
For: ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.942645E+09 | 1.14 | 1973.80 | 01-JAN-09:02 | 1.40 |
February | 0.680578E+09 | 1.07 | 1973.80 | 01-FEB-09:02 | 1.40 |
March | 0.486666E+09 | 1.00 | 1973.80 | 01-MAR-09:02 | 1.41 |
April | 0.433192E+09 | 1.04 | 1973.80 | 01-APR-15:02 | 1.40 |
May | 0.549029E+09 | 1.10 | 1973.80 | 01-MAY-15:02 | 1.40 |
June | 0.590855E+09 | 1.11 | 1973.80 | 01-JUN-15:01 | 1.40 |
July | 0.855826E+09 | 1.18 | 1973.80 | 01-JUL-08:62 | 1.40 |
August | 0.766969E+09 | 1.15 | 1973.80 | 01-AUG-08:62 | 1.40 |
September | 0.468354E+09 | 1.07 | 1973.80 | 01-SEP-15:02 | 1.40 |
October | 0.363522E+09 | 1.00 | 1973.80 | 01-OCT-15:02 | 1.39 |
November | 0.606447E+09 | 1.03 | 1973.80 | 01-NOV-08:62 | 1.40 |
December | 0.884837E+09 | 1.12 | 1973.80 | 01-DEC-09:02 | 1.40 |
Annual Sum or Average | 0.762892E+10 | 1.08 | |||
Minimum of Months | 0.363522E+09 | 1.00 | 1973.80 | 1.39 | |
Maximum of Months | 0.942645E+09 | 1.18 | 1973.80 | 1.41 |
Report: FanReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.135470E+10 | 0.42 | 3497.09 | 16-JAN-06:00 | 1.41 |
February | 0.106444E+10 | 0.34 | 4443.97 | 19-FEB-06:00 | 1.41 |
March | 0.155887E+10 | 0.43 | 5099.10 | 02-MAR-13:00 | 1.41 |
April | 0.267751E+10 | 0.83 | 4689.76 | 27-APR-13:10 | 1.40 |
May | 0.325002E+10 | 0.95 | 4617.63 | 15-MAY-13:10 | 1.40 |
June | 0.346744E+10 | 1.08 | 3538.32 | 28-JUN-13:10 | 1.40 |
July | 0.436008E+10 | 1.19 | 4396.94 | 31-JUL-13:20 | 1.40 |
August | 0.470627E+10 | 1.22 | 7347.31 | 24-AUG-12:40 | 1.40 |
September | 0.444133E+10 | 1.13 | 7898.10 | 10-SEP-12:40 | 1.40 |
October | 0.292207E+10 | 0.74 | 8316.29 | 07-OCT-12:30 | 1.40 |
November | 0.519647E+09 | 0.18 | 4915.56 | 04-NOV-13:30 | 1.40 |
December | 0.146733E+10 | 0.45 | 4093.39 | 05-DEC-12:30 | 1.41 |
Annual Sum or Average | 0.317897E+11 | 0.75 | |||
Minimum of Months | 0.519647E+09 | 0.18 | 3497.09 | 1.40 | |
Maximum of Months | 0.470627E+10 | 1.22 | 8316.29 | 1.41 |
Report: FanReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.316856E+10 | 1.00 | 10245.09 | 01-JAN-09:02 | 1.40 |
February | 0.270232E+10 | 0.99 | 10245.09 | 02-FEB-09:02 | 1.40 |
March | 0.225712E+10 | 0.99 | 10245.09 | 02-MAR-09:02 | 1.41 |
April | 0.310556E+10 | 0.99 | 10245.09 | 01-APR-08:62 | 1.40 |
May | 0.451525E+10 | 0.99 | 10245.09 | 01-MAY-08:63 | 1.40 |
June | 0.532653E+10 | 0.99 | 10245.09 | 01-JUN-08:62 | 1.40 |
July | 0.616480E+10 | 1.00 | 10245.09 | 01-JUL-08:62 | 1.40 |
August | 0.577825E+10 | 1.00 | 10245.09 | 01-AUG-08:62 | 1.40 |
September | 0.399725E+10 | 0.99 | 10245.09 | 01-SEP-15:02 | 1.40 |
October | 0.261287E+10 | 0.99 | 10245.09 | 01-OCT-08:62 | 1.39 |
November | 0.221237E+10 | 0.99 | 10245.09 | 02-NOV-15:01 | 1.40 |
December | 0.268433E+10 | 0.99 | 10245.09 | 01-DEC-09:02 | 1.40 |
Annual Sum or Average | 0.445252E+11 | 0.99 | |||
Minimum of Months | 0.221237E+10 | 0.99 | 10245.09 | 1.39 | |
Maximum of Months | 0.616480E+10 | 1.00 | 10245.09 | 1.41 |
Report: FanReportMonthly
For: ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.843233E+09 | 1.07 | 1961.80 | 01-JAN-09:02 | 1.40 |
February | 0.585118E+09 | 1.03 | 1961.80 | 01-FEB-09:02 | 1.40 |
March | 0.467804E+09 | 1.05 | 1961.80 | 01-MAR-09:02 | 1.41 |
April | 0.507504E+09 | 1.15 | 1961.80 | 01-APR-08:62 | 1.40 |
May | 0.570752E+09 | 1.19 | 1961.80 | 01-MAY-15:02 | 1.40 |
June | 0.693597E+09 | 1.25 | 1961.80 | 01-JUN-08:62 | 1.40 |
July | 0.811412E+09 | 1.28 | 1961.80 | 01-JUL-08:62 | 1.40 |
August | 0.878221E+09 | 1.26 | 1961.80 | 01-AUG-08:62 | 1.40 |
September | 0.585858E+09 | 1.18 | 1961.80 | 01-SEP-15:02 | 1.40 |
October | 0.414008E+09 | 1.10 | 1961.80 | 01-OCT-15:02 | 1.39 |
November | 0.546838E+09 | 1.03 | 1961.80 | 02-NOV-15:01 | 1.40 |
December | 0.793091E+09 | 1.08 | 1961.80 | 01-DEC-09:02 | 1.40 |
Annual Sum or Average | 0.769744E+10 | 1.14 | |||
Minimum of Months | 0.414008E+09 | 1.03 | 1961.80 | 1.39 | |
Maximum of Months | 0.878221E+09 | 1.28 | 1961.80 | 1.41 |
Report: FanReportMonthly
For: ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.912818E+09 | 1.17 | 1790.43 | 01-JAN-09:02 | 1.40 |
February | 0.629567E+09 | 1.05 | 1790.43 | 01-FEB-09:02 | 1.40 |
March | 0.426629E+09 | 0.99 | 1790.43 | 02-MAR-09:02 | 1.41 |
April | 0.406607E+09 | 1.04 | 1790.43 | 01-APR-08:62 | 1.40 |
May | 0.471041E+09 | 1.13 | 1790.43 | 01-MAY-15:02 | 1.40 |
June | 0.611015E+09 | 1.21 | 1790.43 | 01-JUN-08:62 | 1.40 |
July | 0.698805E+09 | 1.26 | 1790.43 | 01-JUL-08:62 | 1.40 |
August | 0.723034E+09 | 1.22 | 1790.43 | 01-AUG-08:62 | 1.40 |
September | 0.408689E+09 | 1.10 | 1790.43 | 01-SEP-15:02 | 1.40 |
October | 0.337367E+09 | 1.00 | 1790.43 | 01-OCT-15:02 | 1.39 |
November | 0.564291E+09 | 1.03 | 1790.43 | 07-NOV-16:02 | 1.40 |
December | 0.830310E+09 | 1.13 | 1790.43 | 01-DEC-09:02 | 1.40 |
Annual Sum or Average | 0.702017E+10 | 1.11 | |||
Minimum of Months | 0.337367E+09 | 0.99 | 1790.43 | 1.39 | |
Maximum of Months | 0.912818E+09 | 1.26 | 1790.43 | 1.41 |
Report: FanReportMonthly
For: ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.281601E+09 | 1.17 | 578.40 | 01-JAN-09:02 | 1.40 |
February | 0.199468E+09 | 1.09 | 578.40 | 01-FEB-09:02 | 1.40 |
March | 0.158413E+09 | 1.05 | 578.40 | 01-MAR-09:02 | 1.41 |
April | 0.154309E+09 | 1.12 | 578.40 | 01-APR-15:02 | 1.40 |
May | 0.191298E+09 | 1.19 | 578.40 | 01-MAY-15:02 | 1.40 |
June | 0.195527E+09 | 1.22 | 578.40 | 01-JUN-15:01 | 1.40 |
July | 0.284564E+09 | 1.27 | 578.40 | 01-JUL-08:62 | 1.40 |
August | 0.267105E+09 | 1.25 | 578.40 | 01-AUG-08:62 | 1.39 |
September | 0.186784E+09 | 1.19 | 578.40 | 01-SEP-15:02 | 1.40 |
October | 0.130842E+09 | 1.08 | 578.40 | 01-OCT-15:02 | 1.39 |
November | 0.186824E+09 | 1.06 | 578.40 | 01-NOV-08:62 | 1.40 |
December | 0.263264E+09 | 1.16 | 578.40 | 01-DEC-09:02 | 1.40 |
Annual Sum or Average | 0.250000E+10 | 1.16 | |||
Minimum of Months | 0.130842E+09 | 1.05 | 578.40 | 1.39 | |
Maximum of Months | 0.284564E+09 | 1.27 | 578.40 | 1.41 |
Report: FanReportMonthly
For: ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.300600E+09 | 1.27 | 520.14 | 01-JAN-09:02 | 1.40 |
February | 0.214204E+09 | 1.14 | 520.14 | 01-FEB-09:02 | 1.40 |
March | 0.150878E+09 | 1.01 | 520.14 | 01-MAR-09:02 | 1.41 |
April | 0.130211E+09 | 1.05 | 520.14 | 01-APR-08:62 | 1.40 |
May | 0.161695E+09 | 1.14 | 520.14 | 01-MAY-15:02 | 1.40 |
June | 0.175387E+09 | 1.17 | 520.14 | 01-JUN-15:01 | 1.40 |
July | 0.255970E+09 | 1.24 | 520.14 | 01-JUL-08:62 | 1.40 |
August | 0.224625E+09 | 1.21 | 520.14 | 01-AUG-08:62 | 1.39 |
September | 0.133643E+09 | 1.11 | 520.14 | 01-SEP-15:02 | 1.40 |
October | 0.114776E+09 | 1.01 | 520.14 | 01-OCT-15:02 | 1.39 |
November | 0.192728E+09 | 1.11 | 520.14 | 01-NOV-08:62 | 1.40 |
December | 0.274280E+09 | 1.22 | 520.14 | 01-DEC-09:02 | 1.40 |
Annual Sum or Average | 0.232900E+10 | 1.14 | |||
Minimum of Months | 0.114776E+09 | 1.01 | 520.14 | 1.39 | |
Maximum of Months | 0.300600E+09 | 1.27 | 520.14 | 1.41 |
Report: FanReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.107165E+10 | 1.06 | 3149.27 | 01-JAN-09:02 | 1.40 |
February | 0.855917E+09 | 1.11 | 3149.27 | 01-FEB-16:02 | 1.40 |
March | 0.817796E+09 | 1.13 | 3149.27 | 01-MAR-16:01 | 1.41 |
April | 0.892843E+09 | 1.18 | 3149.27 | 01-APR-15:02 | 1.40 |
May | 0.968107E+09 | 1.21 | 3149.27 | 01-MAY-15:02 | 1.40 |
June | 0.101011E+10 | 1.22 | 3149.27 | 01-JUN-15:01 | 1.40 |
July | 0.131574E+10 | 1.26 | 3149.27 | 01-JUL-08:62 | 1.40 |
August | 0.141478E+10 | 1.26 | 3149.27 | 01-AUG-08:62 | 1.40 |
September | 0.121690E+10 | 1.20 | 3149.27 | 01-SEP-15:02 | 1.40 |
October | 0.848371E+09 | 1.15 | 3149.27 | 01-OCT-08:62 | 1.39 |
November | 0.735639E+09 | 1.06 | 3149.27 | 02-NOV-15:01 | 1.40 |
December | 0.107766E+10 | 1.11 | 3149.27 | 01-DEC-09:02 | 1.40 |
Annual Sum or Average | 0.122255E+11 | 1.16 | |||
Minimum of Months | 0.735639E+09 | 1.06 | 3149.27 | 1.39 | |
Maximum of Months | 0.141478E+10 | 1.26 | 3149.27 | 1.41 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.151393E+10 | 0.136253E+10 | 857.83 | 16-JAN-16:13 | 772.05 | 772.05 | 37.79 | 1.70 |
February | 0.116446E+10 | 0.104802E+10 | 855.72 | 19-FEB-07:10 | 770.15 | 770.15 | 35.00 | 1.69 |
March | 0.103246E+10 | 0.929212E+09 | 808.38 | 05-MAR-16:02 | 727.54 | 727.54 | 37.75 | 1.45 |
April | 0.795583E+09 | 0.716025E+09 | 692.59 | 18-APR-08:62 | 623.33 | 623.33 | 34.60 | 1.07 |
May | 0.674846E+09 | 0.607362E+09 | 632.07 | 18-MAY-10:40 | 568.87 | 568.87 | 35.40 | 0.92 |
June | 0.520003E+09 | 0.468003E+09 | 634.21 | 13-JUN-10:40 | 570.79 | 570.79 | 35.86 | 0.92 |
July | 0.443012E+09 | 0.398710E+09 | 596.81 | 12-JUL-10:40 | 537.13 | 537.13 | 35.76 | 0.84 |
August | 0.421485E+09 | 0.379336E+09 | 577.34 | 01-AUG-10:40 | 519.61 | 519.61 | 35.14 | 0.80 |
September | 0.493933E+09 | 0.444540E+09 | 640.58 | 18-SEP-10:40 | 576.52 | 576.52 | 36.78 | 0.94 |
October | 0.779355E+09 | 0.701420E+09 | 653.10 | 30-OCT-08:03 | 587.79 | 587.79 | 34.90 | 0.97 |
November | 0.112615E+10 | 0.101354E+10 | 812.14 | 26-NOV-16:03 | 730.93 | 730.93 | 37.00 | 1.47 |
December | 0.143805E+10 | 0.129425E+10 | 876.49 | 26-DEC-11:00 | 788.84 | 788.84 | 39.12 | 1.82 |
Annual Sum or Average | 0.104033E+11 | 0.936294E+10 | ||||||
Minimum of Months | 0.421485E+09 | 0.379336E+09 | 577.34 | 519.61 | 519.61 | 34.60 | 0.80 | |
Maximum of Months | 0.151393E+10 | 0.136253E+10 | 876.49 | 788.84 | 788.84 | 39.12 | 1.82 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.185988E+09 | 0.167389E+09 | 1792.44 | 11-JAN-19:03 | 1613.20 | 1613.20 | 6.73 | 3.12 |
February | 0.815825E+09 | 0.734243E+09 | 4791.88 | 27-FEB-16:01 | 4312.70 | 4312.70 | 6.73 | 16.28 |
March | 0.197447E+10 | 0.177702E+10 | 4505.58 | 18-MAR-15:02 | 4055.02 | 4055.02 | 6.73 | 13.10 |
April | 0.374219E+10 | 0.336797E+10 | 5291.69 | 26-APR-18:03 | 4762.52 | 4762.52 | 6.73 | 23.65 |
May | 0.545503E+10 | 0.490953E+10 | 5241.56 | 03-MAY-18:02 | 4717.40 | 4717.40 | 6.73 | 23.11 |
June | 0.704971E+10 | 0.634474E+10 | 5268.08 | 09-JUN-16:20 | 4741.28 | 4741.28 | 6.73 | 23.40 |
July | 0.875069E+10 | 0.787562E+10 | 5322.54 | 24-JUL-18:03 | 4790.28 | 4790.28 | 6.73 | 23.96 |
August | 0.920876E+10 | 0.828788E+10 | 5561.81 | 10-AUG-18:03 | 5005.63 | 5005.63 | 6.73 | 25.94 |
September | 0.630770E+10 | 0.567693E+10 | 5084.82 | 14-SEP-10:50 | 4576.34 | 4576.34 | 6.73 | 21.04 |
October | 0.344642E+10 | 0.310178E+10 | 4748.94 | 04-OCT-15:02 | 4274.05 | 4274.05 | 6.73 | 15.69 |
November | 0.980831E+09 | 0.882748E+09 | 4751.98 | 04-NOV-15:02 | 4276.78 | 4276.78 | 6.73 | 15.73 |
December | 0.336019E+09 | 0.302417E+09 | 2081.16 | 05-DEC-12:30 | 1873.04 | 1873.04 | 6.73 | 3.74 |
Annual Sum or Average | 0.482536E+11 | 0.434283E+11 | ||||||
Minimum of Months | 0.185988E+09 | 0.167389E+09 | 1792.44 | 1613.20 | 1613.20 | 6.73 | 3.12 | |
Maximum of Months | 0.920876E+10 | 0.828788E+10 | 5561.81 | 5005.63 | 5005.63 | 6.73 | 25.94 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.212618E+10 | 0.191356E+10 | 4317.56 | 01-JAN-09:02 | 3885.80 | 3885.80 | 6.92 | 30.26 |
February | 0.428967E+10 | 0.386070E+10 | 4317.56 | 01-FEB-06:10 | 3885.80 | 3885.80 | 6.76 | 30.26 |
March | 0.758176E+10 | 0.682359E+10 | 4317.56 | 01-MAR-00:03 | 3885.80 | 3885.80 | 6.77 | 30.26 |
April | 0.987892E+10 | 0.889103E+10 | 4317.56 | 01-APR-00:10 | 3885.80 | 3885.80 | 6.76 | 30.26 |
May | 0.112260E+11 | 0.101034E+11 | 4317.56 | 01-MAY-00:10 | 3885.80 | 3885.80 | 6.83 | 30.26 |
June | 0.111523E+11 | 0.100370E+11 | 4317.56 | 01-JUN-00:10 | 3885.80 | 3885.80 | 6.98 | 30.26 |
July | 0.115642E+11 | 0.104077E+11 | 4317.56 | 01-JUL-00:10 | 3885.80 | 3885.80 | 7.42 | 30.26 |
August | 0.115642E+11 | 0.104077E+11 | 4317.56 | 01-AUG-00:10 | 3885.80 | 3885.80 | 7.99 | 30.26 |
September | 0.110862E+11 | 0.997758E+10 | 4317.56 | 01-SEP-00:10 | 3885.80 | 3885.80 | 7.61 | 30.26 |
October | 0.100541E+11 | 0.904868E+10 | 4317.56 | 01-OCT-00:10 | 3885.80 | 3885.80 | 7.03 | 30.26 |
November | 0.526958E+10 | 0.474262E+10 | 4317.56 | 01-NOV-00:10 | 3885.80 | 3885.80 | 6.76 | 30.26 |
December | 0.273798E+10 | 0.246418E+10 | 4317.56 | 01-DEC-09:05 | 3885.80 | 3885.80 | 6.78 | 30.26 |
Annual Sum or Average | 0.985309E+11 | 0.886778E+11 | ||||||
Minimum of Months | 0.212618E+10 | 0.191356E+10 | 4317.56 | 3885.80 | 3885.80 | 6.76 | 30.26 | |
Maximum of Months | 0.115642E+11 | 0.104077E+11 | 4317.56 | 3885.80 | 3885.80 | 7.99 | 30.26 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.128314E+09 | 38494137.67 | 47.91 | 01-JAN-00:05 | 14.37 | 14.37 | 48.33 | 0.37 |
February | 0.115896E+09 | 34768898.54 | 47.91 | 01-FEB-00:03 | 14.37 | 14.37 | 48.79 | 0.37 |
March | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAR-00:03 | 14.37 | 14.37 | 48.50 | 0.37 |
April | 0.124175E+09 | 37252391.29 | 47.91 | 01-APR-00:10 | 14.37 | 14.37 | 51.74 | 0.37 |
May | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAY-00:10 | 14.37 | 14.37 | 52.28 | 0.37 |
June | 0.124175E+09 | 37252391.29 | 47.91 | 01-JUN-00:10 | 14.37 | 14.37 | 52.00 | 0.37 |
July | 0.128314E+09 | 38494137.67 | 47.91 | 01-JUL-00:10 | 14.37 | 14.37 | 52.69 | 0.37 |
August | 0.128314E+09 | 38494137.67 | 47.91 | 01-AUG-00:10 | 14.37 | 14.37 | 53.01 | 0.37 |
September | 0.124175E+09 | 37252391.29 | 47.91 | 01-SEP-00:10 | 14.37 | 14.37 | 52.32 | 0.37 |
October | 0.128314E+09 | 38494137.67 | 47.91 | 01-OCT-00:10 | 14.37 | 14.37 | 51.59 | 0.37 |
November | 0.124175E+09 | 37252391.29 | 47.91 | 01-NOV-00:10 | 14.37 | 14.37 | 52.56 | 0.37 |
December | 0.128314E+09 | 38494137.67 | 47.91 | 01-DEC-00:03 | 14.37 | 14.37 | 49.43 | 0.37 |
Annual Sum or Average | 0.151079E+10 | 0.453237E+09 | ||||||
Minimum of Months | 0.115896E+09 | 34768898.54 | 47.91 | 14.37 | 14.37 | 48.33 | 0.37 | |
Maximum of Months | 0.128314E+09 | 38494137.67 | 47.91 | 14.37 | 14.37 | 53.01 | 0.37 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 38.43 | 60.00 | 75935.08 | 179625.81 | 07-JAN-09:02 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 38.21 | 60.00 | 64190.16 | 176905.30 | 19-FEB-07:10 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 36.15 | 60.00 | 49635.16 | 135273.25 | 05-MAR-16:02 |
April | 0.00 | 0.00 | 01-APR-00:10 | 36.11 | 60.00 | 39886.86 | 113328.25 | 18-APR-08:62 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 33.31 | 60.00 | 32814.85 | 98794.85 | 18-MAY-08:62 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.06 | 60.00 | 26350.58 | 92990.85 | 13-JUN-10:40 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 28.40 | 60.00 | 21599.64 | 85028.31 | 12-JUL-10:40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 28.19 | 60.00 | 20518.17 | 83049.82 | 01-AUG-10:40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 28.91 | 60.00 | 25218.03 | 90880.64 | 18-SEP-10:40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.04 | 60.00 | 37740.64 | 101402.09 | 30-OCT-08:03 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 36.55 | 60.00 | 55729.42 | 141485.34 | 26-NOV-16:03 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 39.35 | 60.00 | 70441.11 | 178456.61 | 26-DEC-09:06 |
Annual Sum or Average | 0.00 | 43238.62 | ||||||
Minimum of Months | 0.00 | 0.00 | 28.04 | 60.00 | 20518.17 | 83049.82 | ||
Maximum of Months | 0.00 | 0.00 | 39.35 | 60.00 | 75935.08 | 179625.81 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 1691.66 | 36497.52 | 11-JAN-19:03 | 6.99 | 6.70 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 9120.88 | 310178.07 | 27-FEB-16:01 | 9.15 | 6.70 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 19208.05 | 390315.07 | 18-MAR-15:02 | 9.78 | 6.70 | 0.00 | 0.00 | 01-MAR-00:03 |
April | 52349.95 | 535018.93 | 27-APR-15:03 | 10.92 | 6.70 | 0.00 | 0.00 | 01-APR-00:10 |
May | 84972.76 | 532344.26 | 05-MAY-18:03 | 10.90 | 6.70 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 128666.93 | 550881.28 | 28-JUN-18:03 | 11.05 | 6.70 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 189155.52 | 641251.82 | 27-JUL-18:03 | 11.76 | 6.70 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 222428.78 | 688924.49 | 10-AUG-18:03 | 12.14 | 6.70 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 117716.06 | 571543.65 | 23-SEP-18:02 | 11.21 | 6.70 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 40288.21 | 463203.29 | 04-OCT-15:02 | 10.35 | 6.70 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 11530.99 | 436477.98 | 04-NOV-15:02 | 10.14 | 6.70 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 2939.55 | 56752.47 | 05-DEC-12:30 | 7.15 | 6.70 | 0.00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 73820.61 | 0.00 | ||||||
Minimum of Months | 1691.66 | 36497.52 | 6.99 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 222428.78 | 688924.49 | 12.14 | 6.70 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 48.33 | 59.70 | 27483.16 | 55995.21 | 31-JAN-07:30 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 48.79 | 58.83 | 27669.51 | 56071.13 | 07-FEB-07:10 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 48.50 | 58.43 | 27391.73 | 55882.10 | 02-MAR-07:20 |
April | 0.00 | 0.00 | 01-APR-00:10 | 51.74 | 58.89 | 26665.40 | 54631.00 | 03-APR-06:40 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 52.28 | 59.47 | 25727.82 | 52937.77 | 01-MAY-06:30 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 52.00 | 58.60 | 24820.54 | 50885.09 | 01-JUN-06:20 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 52.69 | 59.26 | 24155.32 | 49140.30 | 03-JUL-06:10 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 53.01 | 59.66 | 23979.87 | 48416.82 | 31-AUG-06:20 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 52.32 | 58.50 | 24273.47 | 49481.13 | 29-SEP-06:15 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 51.59 | 58.90 | 24986.48 | 51356.97 | 31-OCT-06:30 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 52.56 | 59.60 | 25930.22 | 53374.03 | 30-NOV-07:10 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 49.43 | 59.80 | 26840.76 | 54992.97 | 29-DEC-07:50 |
Annual Sum or Average | 0.00 | 25816.31 | ||||||
Minimum of Months | 0.00 | 0.00 | 48.33 | 58.43 | 23979.87 | 48416.82 | ||
Maximum of Months | 0.00 | 0.00 | 53.01 | 59.80 | 27669.51 | 56071.13 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.123538E+12 | 0.00 | 0.149079E+09 | 0.136867E+12 | 0.00 | 0.00 |
February | 0.979933E+11 | 0.00 | 0.463944E+10 | 0.123621E+12 | 0.00 | 0.00 |
March | 0.916542E+11 | 0.00 | 0.100727E+11 | 0.136866E+12 | 0.00 | 0.00 |
April | 0.766718E+11 | 0.00 | 0.568250E+11 | 0.132451E+12 | 0.00 | 0.00 |
May | 0.706955E+11 | 0.00 | 0.113180E+12 | 0.136866E+12 | 0.00 | 0.00 |
June | 0.620320E+11 | 0.00 | 0.194846E+12 | 0.132451E+12 | 0.00 | 0.00 |
July | 0.559800E+11 | 0.00 | 0.317725E+12 | 0.136867E+12 | 0.00 | 0.00 |
August | 0.535531E+11 | 0.00 | 0.389455E+12 | 0.136867E+12 | 0.00 | 0.00 |
September | 0.583631E+11 | 0.00 | 0.167291E+12 | 0.132451E+12 | 0.00 | 0.00 |
October | 0.762307E+11 | 0.00 | 0.373890E+11 | 0.136866E+12 | 0.00 | 0.00 |
November | 0.975436E+11 | 0.00 | 0.851776E+10 | 0.132451E+12 | 0.00 | 0.00 |
December | 0.115294E+12 | 0.00 | 793.93 | 0.136867E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.979550E+12 | 0.00 | 0.130009E+13 | 0.161149E+13 | 0.00 | 0.00 |
Minimum of Months | 0.535531E+11 | 0.00 | 793.93 | 0.123621E+12 | 0.00 | 0.00 |
Maximum of Months | 0.123538E+12 | 0.00 | 0.389455E+12 | 0.136867E+12 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.399465E+11 | 0.00 | 0.00 | 0.587890E+10 | 0.00 | 0.00 |
February | 0.324164E+11 | 0.00 | 0.332454E+09 | 0.530997E+10 | 0.00 | 0.00 |
March | 0.323836E+11 | 0.00 | 0.656261E+09 | 0.587890E+10 | 0.00 | 0.00 |
April | 0.237749E+11 | 0.00 | 0.509175E+10 | 0.568926E+10 | 0.00 | 0.00 |
May | 0.167172E+11 | 0.00 | 0.995405E+10 | 0.587890E+10 | 0.00 | 0.00 |
June | 0.658003E+10 | 0.00 | 0.171572E+11 | 0.568926E+10 | 0.00 | 0.00 |
July | 0.227446E+10 | 0.00 | 0.325768E+11 | 0.587890E+10 | 0.00 | 0.00 |
August | 0.176384E+10 | 0.00 | 0.432885E+11 | 0.587890E+10 | 0.00 | 0.00 |
September | 0.701031E+10 | 0.00 | 0.149007E+11 | 0.568926E+10 | 0.00 | 0.00 |
October | 0.217068E+11 | 0.00 | 0.254401E+10 | 0.587890E+10 | 0.00 | 0.00 |
November | 0.308037E+11 | 0.00 | 0.658445E+09 | 0.568926E+10 | 0.00 | 0.00 |
December | 0.389756E+11 | 0.00 | 0.00 | 0.587890E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.254353E+12 | 0.00 | 0.127160E+12 | 0.692193E+11 | 0.00 | 0.00 |
Minimum of Months | 0.176384E+10 | 0.00 | 0.00 | 0.530997E+10 | 0.00 | 0.00 |
Maximum of Months | 0.399465E+11 | 0.00 | 0.432885E+11 | 0.587890E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.136867E+12 | 0.149079E+09 | 0.123538E+12 | 0.750522E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.123621E+12 | 0.463944E+10 | 0.979933E+11 | 0.584593E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.136866E+12 | 0.100727E+11 | 0.916542E+11 | 0.451391E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.132451E+12 | 0.568250E+11 | 0.766718E+11 | 0.289158E+12 | 0.329506E+10 | 0.00 | 0.00 | 0.00 |
May | 0.136866E+12 | 0.113180E+12 | 0.706955E+11 | 0.175348E+12 | 0.256836E+10 | 0.00 | 0.00 | 0.00 |
June | 0.132451E+12 | 0.194846E+12 | 0.620320E+11 | 0.545198E+11 | 0.372616E+10 | 0.00 | 0.00 | 0.00 |
July | 0.136867E+12 | 0.317725E+12 | 0.559800E+11 | 0.148156E+11 | 0.263292E+11 | 0.00 | 0.00 | 0.00 |
August | 0.136867E+12 | 0.389455E+12 | 0.535531E+11 | 0.129530E+11 | 0.501274E+11 | 0.00 | 0.00 | 0.00 |
September | 0.132451E+12 | 0.167291E+12 | 0.583631E+11 | 0.549256E+11 | 0.502729E+10 | 0.00 | 0.00 | 0.00 |
October | 0.136866E+12 | 0.373890E+11 | 0.762307E+11 | 0.225877E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132451E+12 | 0.851776E+10 | 0.975436E+11 | 0.456386E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.136867E+12 | 793.93 | 0.115294E+12 | 0.680251E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.161149E+13 | 0.130009E+13 | 0.979550E+12 | 0.375074E+13 | 0.910734E+11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.123621E+12 | 793.93 | 0.535531E+11 | 0.129530E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.136867E+12 | 0.389455E+12 | 0.123538E+12 | 0.750522E+12 | 0.501274E+11 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.587890E+10 | 0.00 | 0.399465E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.530997E+10 | 0.332454E+09 | 0.324164E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.587890E+10 | 0.656261E+09 | 0.323836E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.568926E+10 | 0.509175E+10 | 0.237749E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.587890E+10 | 0.995405E+10 | 0.167172E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.568926E+10 | 0.171572E+11 | 0.658003E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.587890E+10 | 0.325768E+11 | 0.227446E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.587890E+10 | 0.432885E+11 | 0.176384E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.568926E+10 | 0.149007E+11 | 0.701031E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.587890E+10 | 0.254401E+10 | 0.217068E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.568926E+10 | 0.658445E+09 | 0.308037E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.587890E+10 | 0.00 | 0.389756E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.692193E+11 | 0.127160E+12 | 0.254353E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.530997E+10 | 0.00 | 0.176384E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.587890E+10 | 0.432885E+11 | 0.399465E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.136867E+12 | 0.123538E+12 | 0.149079E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.123621E+12 | 0.979933E+11 | 0.463944E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.136866E+12 | 0.916542E+11 | 0.100727E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.132451E+12 | 0.766718E+11 | 0.568250E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.136866E+12 | 0.706955E+11 | 0.113180E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.132451E+12 | 0.620320E+11 | 0.194846E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.136867E+12 | 0.559800E+11 | 0.317725E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.136867E+12 | 0.535531E+11 | 0.389455E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.132451E+12 | 0.583631E+11 | 0.167291E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.136866E+12 | 0.762307E+11 | 0.373890E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132451E+12 | 0.975436E+11 | 0.851776E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.136867E+12 | 0.115294E+12 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.161149E+13 | 0.979550E+12 | 0.130009E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.123621E+12 | 0.535531E+11 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.136867E+12 | 0.123538E+12 | 0.389455E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.587890E+10 | 0.399465E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.530997E+10 | 0.324164E+11 | 0.332454E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.587890E+10 | 0.323836E+11 | 0.656261E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.568926E+10 | 0.237749E+11 | 0.509175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.587890E+10 | 0.167172E+11 | 0.995405E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.568926E+10 | 0.658003E+10 | 0.171572E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.587890E+10 | 0.227446E+10 | 0.325768E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.587890E+10 | 0.176384E+10 | 0.432885E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.568926E+10 | 0.701031E+10 | 0.149007E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.587890E+10 | 0.217068E+11 | 0.254401E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.568926E+10 | 0.308037E+11 | 0.658445E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.587890E+10 | 0.389756E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.692193E+11 | 0.254353E+12 | 0.127160E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.530997E+10 | 0.176384E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.587890E+10 | 0.399465E+11 | 0.432885E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.707877E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.90 |
February | 0.637400E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.91 |
March | 0.705275E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.90 |
April | 0.640991E+11 | 0.00 | 117170.37 | 0.00 | 0.108252E+09 | 2854279.58 | 0.00 | 3239.87 | 1.90 |
May | 0.611789E+11 | 0.00 | 81893.70 | 0.00 | 0.106398E+09 | 5561321.20 | 0.00 | 11454.99 | 1.90 |
June | 0.506813E+11 | 0.00 | 0.00 | 0.00 | 95247942.61 | 202399.65 | 0.00 | 0.00 | 1.90 |
July | 0.415278E+11 | 0.00 | 997831.82 | 0.00 | 0.146031E+10 | 0.00 | 0.00 | 3915.18 | 1.90 |
August | 0.353126E+11 | 0.00 | 624896.87 | 0.00 | 0.286748E+10 | 0.00 | 0.00 | 6.00 | 1.91 |
September | 0.534733E+11 | 0.00 | 0.00 | 0.00 | 0.419840E+09 | 0.00 | 0.00 | 0.00 | 1.91 |
October | 0.680282E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.91 |
November | 0.679481E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.90 |
December | 0.706075E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.89 |
Annual Sum or Average | 0.717912E+12 | 0.00 | 1821792.76 | 0.00 | 0.505753E+10 | 8618000.43 | 0.00 | 18616.04 | 1.90 |
Minimum of Months | 0.353126E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.89 |
Maximum of Months | 0.707877E+11 | 0.00 | 997831.82 | 0.00 | 0.286748E+10 | 5561321.20 | 0.00 | 11454.99 | 1.91 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.752080E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.595476E+10 | 0.00 | 0.00 | 6.55 |
February | 0.971770E+10 | 0.00 | 0.00 | 6991.14 | 0.00 | 0.234674E+10 | 69482608.35 | 0.00 | 6.59 |
March | 0.128084E+11 | 0.00 | 0.00 | 56699.58 | 0.00 | 0.452175E+09 | 0.165370E+09 | 0.00 | 6.56 |
April | 0.121529E+11 | 10148456.53 | 0.00 | 0.00 | 10481999.07 | 49918107.32 | 0.00 | 0.00 | 6.57 |
May | 0.116472E+11 | 9912.72 | 0.00 | 5289.15 | 20262435.55 | 0.00 | 198669.02 | 0.00 | 6.57 |
June | 0.964803E+10 | 0.00 | 0.00 | 0.00 | 18131962.59 | 0.00 | 0.00 | 0.00 | 6.58 |
July | 0.790547E+10 | 4162570.52 | 0.00 | 0.00 | 0.274022E+09 | 0.00 | 0.00 | 0.00 | 6.58 |
August | 0.672231E+10 | 0.127573E+09 | 0.00 | 0.00 | 0.418416E+09 | 0.00 | 0.00 | 0.00 | 6.60 |
September | 0.101294E+11 | 38272415.55 | 0.00 | 82330.18 | 41650853.61 | 0.00 | 50023272.05 | 0.00 | 6.59 |
October | 0.127830E+11 | 0.00 | 0.00 | 99948.49 | 0.00 | 18692358.29 | 0.148441E+09 | 0.00 | 6.59 |
November | 0.108349E+11 | 0.00 | 0.00 | 16923.45 | 0.00 | 0.208930E+10 | 10733830.32 | 0.00 | 6.56 |
December | 0.791244E+10 | 0.00 | 0.00 | 108.71 | 0.00 | 0.552319E+10 | 5639389.11 | 0.00 | 6.54 |
Annual Sum or Average | 0.119783E+12 | 0.180167E+09 | 0.00 | 268290.69 | 0.782966E+09 | 0.164348E+11 | 0.449890E+09 | 0.00 | 6.57 |
Minimum of Months | 0.672231E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.54 |
Maximum of Months | 0.128084E+11 | 0.127573E+09 | 0.00 | 99948.49 | 0.418416E+09 | 0.595476E+10 | 0.165370E+09 | 0.00 | 6.60 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.673576E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 |
February | 0.606515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.85 |
March | 0.671101E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 |
April | 0.609958E+10 | 0.00 | 0.00 | 0.00 | 10312138.49 | 0.00 | 0.00 | 0.00 | 2.84 |
May | 0.582197E+10 | 0.00 | 0.00 | 0.00 | 10133138.45 | 0.00 | 0.00 | 0.00 | 2.84 |
June | 0.482257E+10 | 0.00 | 0.00 | 0.00 | 9063266.12 | 0.00 | 0.00 | 0.00 | 2.84 |
July | 0.395155E+10 | 0.00 | 0.00 | 0.00 | 0.139051E+09 | 0.00 | 0.00 | 0.00 | 2.84 |
August | 0.336015E+10 | 0.00 | 0.00 | 0.00 | 0.272913E+09 | 0.00 | 0.00 | 0.00 | 2.85 |
September | 0.508822E+10 | 0.00 | 0.00 | 0.00 | 39949666.46 | 0.00 | 0.00 | 0.00 | 2.84 |
October | 0.647319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.84 |
November | 0.646556E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 |
December | 0.671862E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 |
Annual Sum or Average | 0.683133E+11 | 0.00 | 0.00 | 0.00 | 0.481422E+09 | 0.00 | 0.00 | 0.00 | 2.84 |
Minimum of Months | 0.336015E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 |
Maximum of Months | 0.673576E+10 | 0.00 | 0.00 | 0.00 | 0.272913E+09 | 0.00 | 0.00 | 0.00 | 2.85 |
Report: MechanicalVentilationLoadsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.626958E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178949E+09 | 0.00 | 0.00 | 1.28 |
February | 0.573586E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 70651952.42 | 0.00 | 0.00 | 1.29 |
March | 0.642483E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.28 |
April | 0.583948E+10 | 0.00 | 0.00 | 0.00 | 9872401.92 | 0.00 | 0.00 | 0.00 | 1.28 |
May | 0.557371E+10 | 0.00 | 0.00 | 0.00 | 9701034.91 | 0.00 | 0.00 | 0.00 | 1.28 |
June | 0.461692E+10 | 0.00 | 0.00 | 0.00 | 8676784.74 | 0.00 | 0.00 | 0.00 | 1.29 |
July | 0.378305E+10 | 0.00 | 0.00 | 0.00 | 0.133121E+09 | 0.00 | 0.00 | 0.00 | 1.29 |
August | 0.321686E+10 | 0.00 | 0.00 | 0.00 | 0.261275E+09 | 0.00 | 0.00 | 0.00 | 1.29 |
September | 0.487125E+10 | 0.00 | 0.00 | 0.00 | 38246108.15 | 0.00 | 0.00 | 0.00 | 1.29 |
October | 0.619715E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.29 |
November | 0.618985E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.28 |
December | 0.636282E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 69293899.03 | 0.00 | 0.00 | 1.28 |
Annual Sum or Average | 0.650814E+11 | 0.00 | 0.00 | 0.00 | 0.460893E+09 | 0.318894E+09 | 0.00 | 0.00 | 1.28 |
Minimum of Months | 0.321686E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.28 |
Maximum of Months | 0.642483E+10 | 0.00 | 0.00 | 0.00 | 0.261275E+09 | 0.178949E+09 | 0.00 | 0.00 | 1.29 |
Report: MechanicalVentilationLoadsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.174735E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144389E+10 | 0.00 | 0.00 | 1.10 |
February | 0.196328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.910238E+09 | 0.00 | 0.00 | 1.11 |
March | 0.315290E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26612571.56 | 0.00 | 0.00 | 1.10 |
April | 0.288984E+10 | 0.00 | 0.00 | 0.00 | 4885642.57 | 0.00 | 0.00 | 0.00 | 1.10 |
May | 0.275831E+10 | 0.00 | 0.00 | 0.00 | 4800836.67 | 0.00 | 0.00 | 0.00 | 1.10 |
June | 0.228482E+10 | 0.00 | 0.00 | 0.00 | 4293956.96 | 0.00 | 0.00 | 0.00 | 1.10 |
July | 0.187215E+10 | 0.00 | 0.00 | 0.00 | 65878897.16 | 0.00 | 0.00 | 0.00 | 1.10 |
August | 0.159196E+10 | 0.00 | 0.00 | 0.00 | 0.129300E+09 | 0.00 | 0.00 | 0.00 | 1.11 |
September | 0.241068E+10 | 0.00 | 0.00 | 0.00 | 18927188.72 | 0.00 | 0.00 | 0.00 | 1.10 |
October | 0.306684E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.10 |
November | 0.269956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.363663E+09 | 0.00 | 0.00 | 1.10 |
December | 0.196369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121943E+10 | 0.00 | 0.00 | 1.10 |
Annual Sum or Average | 0.284014E+11 | 0.00 | 0.00 | 0.00 | 0.228086E+09 | 0.396383E+10 | 0.00 | 0.00 | 1.10 |
Minimum of Months | 0.159196E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.10 |
Maximum of Months | 0.315290E+10 | 0.00 | 0.00 | 0.00 | 0.129300E+09 | 0.144389E+10 | 0.00 | 0.00 | 1.11 |
Report: MechanicalVentilationLoadsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.217083E+10 | 0.00 | 0.00 | 63599854.78 | 0.00 | 0.00 | 0.899436E+11 | 0.00 | 38.57 |
February | 0.151677E+10 | 0.00 | 0.00 | 57867331.88 | 0.00 | 0.00 | 0.814267E+11 | 0.00 | 38.81 |
March | 0.107283E+10 | 0.00 | 0.00 | 65251081.35 | 0.00 | 0.00 | 0.907040E+11 | 0.00 | 38.62 |
April | 0.118356E+10 | 0.133330E+09 | 0.00 | 62968625.45 | 7745384.58 | 0.00 | 0.822249E+11 | 0.00 | 38.66 |
May | 0.125611E+10 | 0.134635E+09 | 0.00 | 65902606.38 | 3992248.46 | 0.00 | 0.783498E+11 | 0.00 | 38.69 |
June | 0.144706E+10 | 0.117457E+09 | 0.00 | 63551621.86 | 6533809.77 | 0.00 | 0.644806E+11 | 0.00 | 38.73 |
July | 0.108165E+10 | 0.179953E+10 | 0.00 | 57200275.93 | 0.102794E+09 | 0.00 | 0.529294E+11 | 0.00 | 38.71 |
August | 0.735157E+09 | 0.353304E+10 | 0.00 | 53162445.26 | 0.200664E+09 | 0.00 | 0.451896E+11 | 0.00 | 38.83 |
September | 0.959907E+09 | 0.529292E+09 | 0.00 | 61355482.54 | 17241393.00 | 0.00 | 0.686067E+11 | 0.00 | 38.76 |
October | 0.105492E+10 | 0.00 | 0.00 | 65927381.88 | 0.00 | 0.00 | 0.874644E+11 | 0.00 | 38.78 |
November | 0.112758E+10 | 0.00 | 0.00 | 62737185.28 | 0.00 | 0.00 | 0.872908E+11 | 0.00 | 38.62 |
December | 0.192160E+10 | 0.00 | 0.00 | 63438392.92 | 0.00 | 0.00 | 0.899576E+11 | 0.00 | 38.52 |
Annual Sum or Average | 0.155280E+11 | 0.624729E+10 | 0.00 | 0.742962E+09 | 0.338971E+09 | 0.00 | 0.918568E+12 | 0.00 | 38.69 |
Minimum of Months | 0.735157E+09 | 0.00 | 0.00 | 53162445.26 | 0.00 | 0.00 | 0.451896E+11 | 0.00 | 38.52 |
Maximum of Months | 0.217083E+10 | 0.353304E+10 | 0.00 | 65927381.88 | 0.200664E+09 | 0.00 | 0.907040E+11 | 0.00 | 38.83 |
Report: MechanicalVentilationLoadsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.526025E+11 | 0.00 | 0.00 | 8700.89 | 0.00 | 92592774.94 | 0.115331E+09 | 0.00 | 9.13 |
February | 0.468363E+11 | 0.00 | 0.00 | 142267.51 | 0.00 | 28396265.33 | 0.687740E+09 | 0.00 | 9.18 |
March | 0.514918E+11 | 0.00 | 0.00 | 365900.79 | 0.00 | 0.00 | 0.112408E+10 | 0.00 | 9.14 |
April | 0.476665E+11 | 54924306.85 | 0.00 | 25200.01 | 25925949.17 | 0.00 | 0.156026E+09 | 0.00 | 9.15 |
May | 0.454735E+11 | 1988593.17 | 0.00 | 53203.62 | 77458248.89 | 0.00 | 0.172448E+09 | 0.00 | 9.15 |
June | 0.378104E+11 | 0.00 | 0.00 | 0.00 | 71058722.39 | 0.00 | 0.00 | 0.00 | 9.16 |
July | 0.309124E+11 | 34805358.59 | 0.00 | 9680.77 | 0.105539E+10 | 0.00 | 68923904.63 | 0.00 | 9.16 |
August | 0.260783E+11 | 0.695428E+09 | 0.00 | 59050.79 | 0.144429E+10 | 0.00 | 0.266254E+09 | 0.00 | 9.19 |
September | 0.391179E+11 | 0.186620E+09 | 0.00 | 426605.65 | 0.126597E+09 | 0.00 | 0.774848E+09 | 0.00 | 9.17 |
October | 0.494909E+11 | 0.00 | 0.00 | 502709.49 | 0.00 | 0.00 | 0.126033E+10 | 0.00 | 9.17 |
November | 0.503439E+11 | 0.00 | 0.00 | 138576.62 | 0.00 | 38670701.95 | 0.309198E+09 | 0.00 | 9.14 |
December | 0.518525E+11 | 0.00 | 0.00 | 39765.96 | 0.00 | 0.534570E+09 | 0.288867E+09 | 0.00 | 9.11 |
Annual Sum or Average | 0.529677E+12 | 0.973766E+09 | 0.00 | 1771662.10 | 0.280073E+10 | 0.694229E+09 | 0.522405E+10 | 0.00 | 9.15 |
Minimum of Months | 0.260783E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.11 |
Maximum of Months | 0.526025E+11 | 0.695428E+09 | 0.00 | 502709.49 | 0.144429E+10 | 0.534570E+09 | 0.126033E+10 | 0.00 | 9.19 |
Report: MechanicalVentilationLoadsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.146066E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.64 |
February | 0.131524E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 |
March | 0.145529E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.65 |
April | 0.132271E+12 | 0.00 | 0.00 | 0.00 | 0.223621E+09 | 0.00 | 0.00 | 0.00 | 3.65 |
May | 0.126250E+12 | 0.00 | 0.00 | 0.00 | 0.219739E+09 | 0.00 | 0.00 | 0.00 | 3.66 |
June | 0.104578E+12 | 0.00 | 0.00 | 0.00 | 0.196539E+09 | 0.00 | 0.00 | 0.00 | 3.66 |
July | 0.856901E+11 | 0.00 | 0.00 | 0.00 | 0.301534E+10 | 0.00 | 0.00 | 0.00 | 3.66 |
August | 0.728654E+11 | 0.00 | 0.00 | 0.00 | 0.591817E+10 | 0.00 | 0.00 | 0.00 | 3.67 |
September | 0.110339E+12 | 0.00 | 0.00 | 0.00 | 0.866316E+09 | 0.00 | 0.00 | 0.00 | 3.66 |
October | 0.140372E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.66 |
November | 0.140207E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.65 |
December | 0.145694E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.64 |
Annual Sum or Average | 0.148139E+13 | 0.00 | 0.00 | 0.00 | 0.104397E+11 | 0.00 | 0.00 | 0.00 | 3.66 |
Minimum of Months | 0.728654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.64 |
Maximum of Months | 0.146066E+12 | 0.00 | 0.00 | 0.00 | 0.591817E+10 | 0.00 | 0.00 | 0.00 | 3.67 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.852331E+09 | 0.00 | 0.00 | 110614.84 | 0.00 | 0.261168E+10 | 34987453.49 | 0.00 | 0.47 |
February | 0.730369E+09 | 0.00 | 0.00 | 1163552.48 | 0.00 | 0.188797E+10 | 0.416732E+09 | 0.00 | 0.47 |
March | 0.672703E+09 | 0.00 | 0.00 | 3507792.61 | 0.00 | 0.147457E+10 | 0.858391E+09 | 0.00 | 0.47 |
April | 0.484516E+09 | 9281325.17 | 0.00 | 6979029.02 | 76848.14 | 0.706861E+09 | 0.127212E+10 | 0.00 | 0.47 |
May | 0.317788E+09 | 9879322.60 | 0.00 | 11589612.93 | 580013.44 | 0.229772E+09 | 0.154122E+10 | 0.00 | 0.47 |
June | 0.213756E+09 | 8475570.78 | 0.00 | 12331325.92 | 439709.44 | 38060150.67 | 0.123764E+10 | 0.00 | 0.47 |
July | 0.108797E+09 | 0.117967E+09 | 1228.66 | 12682568.05 | 2782048.78 | 1961187.14 | 0.953483E+09 | 1657.24 | 0.47 |
August | 99812725.76 | 0.240651E+09 | 47515.44 | 9247605.81 | 8767008.59 | 1773374.59 | 0.728430E+09 | 9285.94 | 0.48 |
September | 0.255787E+09 | 33429295.76 | 3199.28 | 10683428.82 | 973286.05 | 69753465.79 | 0.116026E+10 | 977.12 | 0.47 |
October | 0.501020E+09 | 0.00 | 0.00 | 5342469.67 | 0.00 | 0.792061E+09 | 0.112258E+10 | 0.00 | 0.47 |
November | 0.708087E+09 | 475486.06 | 0.00 | 720575.47 | 0.00 | 0.183554E+10 | 0.305675E+09 | 0.00 | 0.47 |
December | 0.746833E+09 | 0.00 | 0.00 | 275204.18 | 0.00 | 0.247751E+10 | 0.143831E+09 | 0.00 | 0.47 |
Annual Sum or Average | 0.569180E+10 | 0.420159E+09 | 51943.38 | 74633779.80 | 13618914.44 | 0.121275E+11 | 0.977536E+10 | 11920.30 | 0.47 |
Minimum of Months | 99812725.76 | 0.00 | 0.00 | 110614.84 | 0.00 | 1773374.59 | 34987453.49 | 0.00 | 0.47 |
Maximum of Months | 0.852331E+09 | 0.240651E+09 | 47515.44 | 12682568.05 | 8767008.59 | 0.261168E+10 | 0.154122E+10 | 9285.94 | 0.48 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.738123E+09 | 0.00 | 0.00 | 23257.38 | 0.00 | 0.274683E+10 | 13720174.11 | 0.00 | 0.47 |
February | 0.724462E+09 | 0.00 | 0.00 | 431245.87 | 0.00 | 0.213603E+10 | 0.174957E+09 | 0.00 | 0.47 |
March | 0.751591E+09 | 0.00 | 0.00 | 1750000.11 | 0.00 | 0.175781E+10 | 0.497671E+09 | 0.00 | 0.47 |
April | 0.566079E+09 | 8951953.30 | 0.00 | 4957042.09 | 405123.56 | 0.879931E+09 | 0.101922E+10 | 0.00 | 0.47 |
May | 0.398144E+09 | 9816200.44 | 15042.38 | 9874513.34 | 626096.00 | 0.290895E+09 | 0.140121E+10 | 771.76 | 0.47 |
June | 0.269127E+09 | 8441112.72 | 0.00 | 11084346.89 | 473122.94 | 43297984.83 | 0.117810E+10 | 0.00 | 0.47 |
July | 0.136323E+09 | 0.116538E+09 | 937.60 | 11480384.01 | 4196537.11 | 1781405.77 | 0.927213E+09 | 1947.96 | 0.47 |
August | 0.121420E+09 | 0.231379E+09 | 81691.68 | 8144644.97 | 17972168.33 | 1804240.96 | 0.707796E+09 | 13420.91 | 0.48 |
September | 0.306714E+09 | 29475126.34 | 16890.34 | 8001944.42 | 4905970.47 | 96179545.99 | 0.108541E+10 | 4739.81 | 0.47 |
October | 0.585706E+09 | 0.00 | 0.00 | 2836621.51 | 0.00 | 0.105306E+10 | 0.779120E+09 | 0.00 | 0.47 |
November | 0.714021E+09 | 389141.31 | 7843.11 | 307274.98 | 78129.63 | 0.196707E+10 | 0.168288E+09 | 316.29 | 0.47 |
December | 0.705757E+09 | 0.00 | 0.00 | 35668.80 | 0.00 | 0.265023E+10 | 12029937.49 | 0.00 | 0.47 |
Annual Sum or Average | 0.601747E+10 | 0.404990E+09 | 122405.12 | 58926944.37 | 28657148.04 | 0.136249E+11 | 0.796475E+10 | 21196.73 | 0.47 |
Minimum of Months | 0.121420E+09 | 0.00 | 0.00 | 23257.38 | 0.00 | 1781405.77 | 12029937.49 | 0.00 | 0.47 |
Maximum of Months | 0.751591E+09 | 0.231379E+09 | 81691.68 | 11480384.01 | 17972168.33 | 0.274683E+10 | 0.140121E+10 | 13420.91 | 0.48 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.421796E+11 | 0.00 | 0.00 | 224099.14 | 0.00 | 0.495922E+10 | 0.305722E+09 | 0.00 | 0.53 |
February | 0.329761E+11 | 0.00 | 0.00 | 15825781.96 | 0.00 | 0.192524E+10 | 0.625140E+10 | 0.00 | 0.54 |
March | 0.277809E+11 | 0.00 | 0.00 | 40929605.99 | 0.00 | 0.00 | 0.129798E+11 | 0.00 | 0.54 |
April | 0.143219E+11 | 0.126888E+09 | 0.00 | 67757399.19 | 0.00 | 0.00 | 0.191078E+11 | 0.00 | 0.54 |
May | 0.891355E+10 | 0.141819E+09 | 0.00 | 84400708.91 | 0.00 | 0.00 | 0.194812E+11 | 0.00 | 0.54 |
June | 0.392593E+10 | 0.120883E+09 | 0.00 | 93684027.41 | 0.00 | 0.00 | 0.163433E+11 | 0.00 | 0.54 |
July | 0.148894E+10 | 0.163728E+10 | 0.00 | 90124752.12 | 0.00 | 0.00 | 0.130231E+11 | 0.00 | 0.54 |
August | 0.136679E+10 | 0.338266E+10 | 0.00 | 70903590.17 | 0.00 | 0.00 | 0.994197E+10 | 0.00 | 0.54 |
September | 0.353758E+10 | 0.466525E+09 | 0.00 | 99855982.91 | 0.00 | 0.00 | 0.166535E+11 | 0.00 | 0.54 |
October | 0.141642E+11 | 0.00 | 0.00 | 76153591.50 | 0.00 | 0.00 | 0.185864E+11 | 0.00 | 0.54 |
November | 0.340349E+11 | 6447164.50 | 0.00 | 11834084.09 | 0.00 | 0.00 | 0.459693E+10 | 0.00 | 0.54 |
December | 0.370869E+11 | 0.00 | 0.00 | 7446672.09 | 0.00 | 0.542506E+10 | 0.315366E+10 | 0.00 | 0.53 |
Annual Sum or Average | 0.221777E+12 | 0.588251E+10 | 0.00 | 0.659140E+09 | 0.00 | 0.123095E+11 | 0.140425E+12 | 0.00 | 0.54 |
Minimum of Months | 0.136679E+10 | 0.00 | 0.00 | 224099.14 | 0.00 | 0.00 | 0.305722E+09 | 0.00 | 0.53 |
Maximum of Months | 0.421796E+11 | 0.338266E+10 | 0.00 | 99855982.91 | 0.00 | 0.542506E+10 | 0.194812E+11 | 0.00 | 0.54 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.123729E+11 | 0.00 | 0.00 | 17263333.74 | 0.00 | 0.134378E+11 | 0.216298E+11 | 0.00 | 0.53 |
February | 0.105431E+11 | 0.00 | 0.00 | 25347340.03 | 0.00 | 0.929447E+10 | 0.213169E+11 | 0.00 | 0.54 |
March | 0.103125E+11 | 0.00 | 0.00 | 51661826.14 | 0.00 | 0.136496E+09 | 0.303122E+11 | 0.00 | 0.54 |
April | 0.811291E+10 | 61225176.25 | 0.00 | 79910128.44 | 65697958.04 | 76996292.79 | 0.252368E+11 | 0.00 | 0.54 |
May | 0.656693E+10 | 96631780.12 | 0.00 | 0.112302E+09 | 45226216.06 | 57043264.02 | 0.217507E+11 | 0.00 | 0.54 |
June | 0.458319E+10 | 94279211.55 | 0.00 | 0.126708E+09 | 26632814.26 | 21519680.82 | 0.156371E+11 | 4233.31 | 0.54 |
July | 0.258931E+10 | 0.111314E+10 | 0.00 | 0.115276E+09 | 0.524584E+09 | 13960724.88 | 0.118876E+11 | 0.00 | 0.54 |
August | 0.203290E+10 | 0.209504E+10 | 1069854.91 | 93594189.79 | 0.128747E+10 | 8454608.27 | 0.924783E+10 | 12694.82 | 0.54 |
September | 0.470983E+10 | 0.229087E+09 | 200836.26 | 95066135.04 | 0.237357E+09 | 44492244.97 | 0.154471E+11 | 7640.10 | 0.54 |
October | 0.820246E+10 | 0.00 | 0.00 | 67707823.44 | 0.00 | 0.104630E+09 | 0.244609E+11 | 0.00 | 0.54 |
November | 0.101263E+11 | 3828137.28 | 0.00 | 36607523.17 | 2620790.19 | 0.171790E+10 | 0.267735E+11 | 0.00 | 0.54 |
December | 0.117501E+11 | 0.00 | 0.00 | 18509670.09 | 0.00 | 0.952345E+10 | 0.243935E+11 | 0.00 | 0.53 |
Annual Sum or Average | 0.919024E+11 | 0.369323E+10 | 1270691.17 | 0.839953E+09 | 0.218959E+10 | 0.344373E+11 | 0.248094E+12 | 24568.23 | 0.54 |
Minimum of Months | 0.203290E+10 | 0.00 | 0.00 | 17263333.74 | 0.00 | 8454608.27 | 0.924783E+10 | 0.00 | 0.53 |
Maximum of Months | 0.123729E+11 | 0.209504E+10 | 1069854.91 | 0.126708E+09 | 0.128747E+10 | 0.134378E+11 | 0.303122E+11 | 12694.82 | 0.54 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.853038E+09 | 0.00 | 0.00 | 77819.51 | 0.00 | 0.259240E+10 | 53590166.82 | 0.00 | 0.47 |
February | 0.764197E+09 | 0.00 | 0.00 | 897888.60 | 0.00 | 0.189791E+10 | 0.373229E+09 | 0.00 | 0.47 |
March | 0.655353E+09 | 0.00 | 0.00 | 3234038.71 | 0.00 | 0.145786E+10 | 0.892730E+09 | 0.00 | 0.47 |
April | 0.403705E+09 | 9112252.93 | 0.00 | 7521425.27 | 245920.37 | 0.681354E+09 | 0.137790E+10 | 0.00 | 0.47 |
May | 0.275028E+09 | 9859064.55 | 14848.72 | 10456617.11 | 584455.50 | 0.292332E+09 | 0.152256E+10 | 967.27 | 0.47 |
June | 0.155243E+09 | 7916424.25 | 0.00 | 14045038.32 | 998855.97 | 51202048.24 | 0.128130E+10 | 0.00 | 0.47 |
July | 91477032.80 | 0.115545E+09 | 58510.17 | 12542888.61 | 5145109.36 | 1674011.39 | 0.971229E+09 | 2815.73 | 0.47 |
August | 76533021.98 | 0.242197E+09 | 46968.87 | 10285025.92 | 7225656.94 | 1466336.07 | 0.750979E+09 | 5740.74 | 0.48 |
September | 0.244715E+09 | 32436734.99 | 19349.52 | 10419450.26 | 1948390.54 | 83749308.61 | 0.115760E+10 | 2283.16 | 0.47 |
October | 0.455912E+09 | 0.00 | 0.00 | 5272104.98 | 0.00 | 0.811576E+09 | 0.114825E+10 | 0.00 | 0.47 |
November | 0.724656E+09 | 467325.70 | 7996.02 | 735554.00 | 0.00 | 0.181661E+10 | 0.308013E+09 | 164.34 | 0.47 |
December | 0.762452E+09 | 0.00 | 0.00 | 264250.92 | 0.00 | 0.247456E+10 | 0.131171E+09 | 0.00 | 0.47 |
Annual Sum or Average | 0.546231E+10 | 0.417534E+09 | 147673.31 | 75752102.20 | 16148388.68 | 0.121627E+11 | 0.996854E+10 | 11971.25 | 0.47 |
Minimum of Months | 76533021.98 | 0.00 | 0.00 | 77819.51 | 0.00 | 1466336.07 | 53590166.82 | 0.00 | 0.47 |
Maximum of Months | 0.853038E+09 | 0.242197E+09 | 58510.17 | 14045038.32 | 7225656.94 | 0.259240E+10 | 0.152256E+10 | 5740.74 | 0.48 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.696680E+09 | 0.00 | 0.00 | 25628.41 | 0.00 | 0.278819E+10 | 13807090.02 | 0.00 | 0.47 |
February | 0.730786E+09 | 0.00 | 0.00 | 260535.72 | 0.00 | 0.210510E+10 | 0.199732E+09 | 0.00 | 0.47 |
March | 0.760259E+09 | 0.00 | 0.00 | 1244743.04 | 0.00 | 0.166640E+10 | 0.580919E+09 | 0.00 | 0.47 |
April | 0.546408E+09 | 8741364.61 | 14453.00 | 5194377.78 | 599915.96 | 0.819499E+09 | 0.109909E+10 | 1343.29 | 0.47 |
May | 0.352974E+09 | 9722352.04 | 55260.59 | 8596926.27 | 676745.70 | 0.369632E+09 | 0.136893E+10 | 3752.24 | 0.47 |
June | 0.182707E+09 | 7862002.93 | 15719.98 | 12704425.91 | 1036114.57 | 55623426.41 | 0.125058E+10 | 398.18 | 0.47 |
July | 0.101799E+09 | 0.114323E+09 | 154036.82 | 11282470.82 | 6251368.47 | 1847652.33 | 0.961868E+09 | 8949.58 | 0.47 |
August | 97555725.48 | 0.238632E+09 | 61630.31 | 9084132.49 | 10746630.63 | 1637288.67 | 0.730888E+09 | 5416.26 | 0.48 |
September | 0.291284E+09 | 30104515.34 | 105002.93 | 7481667.21 | 4185890.02 | 0.133727E+09 | 0.106381E+10 | 7318.67 | 0.47 |
October | 0.593322E+09 | 0.00 | 0.00 | 2470624.10 | 0.00 | 0.106069E+10 | 0.764238E+09 | 0.00 | 0.47 |
November | 0.712538E+09 | 276113.40 | 3469.25 | 307924.90 | 193210.92 | 0.193549E+10 | 0.201353E+09 | 2636.78 | 0.47 |
December | 0.694478E+09 | 0.00 | 0.00 | 53577.55 | 0.00 | 0.263034E+10 | 43174876.64 | 0.00 | 0.47 |
Annual Sum or Average | 0.576079E+10 | 0.409662E+09 | 409572.88 | 58707034.20 | 23689876.27 | 0.135682E+11 | 0.827839E+10 | 29815.00 | 0.47 |
Minimum of Months | 97555725.48 | 0.00 | 0.00 | 25628.41 | 0.00 | 1637288.67 | 13807090.02 | 0.00 | 0.47 |
Maximum of Months | 0.760259E+09 | 0.238632E+09 | 154036.82 | 12704425.91 | 10746630.63 | 0.278819E+10 | 0.136893E+10 | 8949.58 | 0.48 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.324178E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.364902E+10 | 0.00 | 0.00 | 0.98 |
February | 0.316751E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.800886E+09 | 0.00 | 0.00 | 0.99 |
March | 0.359343E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.98 |
April | 0.326604E+11 | 0.00 | 0.00 | 0.00 | 55216661.11 | 0.00 | 0.00 | 0.00 | 0.98 |
May | 0.311739E+11 | 0.00 | 0.00 | 0.00 | 54258199.91 | 0.00 | 0.00 | 0.00 | 0.99 |
June | 0.258226E+11 | 0.00 | 0.00 | 0.00 | 48529535.79 | 0.00 | 0.00 | 0.00 | 0.99 |
July | 0.211587E+11 | 0.00 | 0.00 | 0.00 | 0.744552E+09 | 0.00 | 0.00 | 0.00 | 0.99 |
August | 0.179920E+11 | 0.00 | 0.00 | 0.00 | 0.146132E+10 | 0.00 | 0.00 | 0.00 | 0.99 |
September | 0.272451E+11 | 0.00 | 0.00 | 0.00 | 0.213912E+09 | 0.00 | 0.00 | 0.00 | 0.99 |
October | 0.346609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.99 |
November | 0.337949E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.825108E+09 | 0.00 | 0.00 | 0.98 |
December | 0.322914E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.368367E+10 | 0.00 | 0.00 | 0.98 |
Annual Sum or Average | 0.356827E+12 | 0.00 | 0.00 | 0.00 | 0.257779E+10 | 0.895868E+10 | 0.00 | 0.00 | 0.99 |
Minimum of Months | 0.179920E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.98 |
Maximum of Months | 0.359343E+11 | 0.00 | 0.00 | 0.00 | 0.146132E+10 | 0.368367E+10 | 0.00 | 0.00 | 0.99 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.152803E+09 | 0.00 | 0.00 | 14970.48 | 0.00 | 0.719970E+09 | 1989132.95 | 0.00 | 0.47 |
February | 0.159647E+09 | 0.00 | 0.00 | 253706.59 | 0.00 | 0.539763E+09 | 59394045.56 | 0.00 | 0.47 |
March | 0.166731E+09 | 0.00 | 0.00 | 862162.05 | 0.00 | 0.434044E+09 | 0.150656E+09 | 0.00 | 0.47 |
April | 0.117355E+09 | 2326466.45 | 0.00 | 1802783.70 | 13076.87 | 0.231342E+09 | 0.267120E+09 | 0.00 | 0.47 |
May | 73077218.22 | 2503877.52 | 0.00 | 3148777.22 | 110956.49 | 0.108477E+09 | 0.340390E+09 | 0.00 | 0.47 |
June | 47194670.74 | 2141837.59 | 0.00 | 3409130.84 | 86982.46 | 21682642.97 | 0.303161E+09 | 0.00 | 0.47 |
July | 25770280.48 | 29621159.59 | 240.16 | 3475758.68 | 565977.81 | 482211.97 | 0.239503E+09 | 481.32 | 0.47 |
August | 23064199.14 | 60687528.90 | 12930.66 | 2446887.98 | 1667093.96 | 441204.92 | 0.183864E+09 | 1269.69 | 0.48 |
September | 61414173.79 | 8412329.76 | 1021.52 | 2832260.72 | 188315.70 | 37347381.99 | 0.272527E+09 | 22.58 | 0.47 |
October | 0.124864E+09 | 0.00 | 0.00 | 1297619.07 | 0.00 | 0.268311E+09 | 0.210779E+09 | 0.00 | 0.47 |
November | 0.163393E+09 | 118871.51 | 0.00 | 147278.03 | 0.00 | 0.508395E+09 | 40568635.96 | 0.00 | 0.47 |
December | 0.144492E+09 | 0.00 | 0.00 | 48183.57 | 0.00 | 0.683368E+09 | 14203442.00 | 0.00 | 0.47 |
Annual Sum or Average | 0.125981E+10 | 0.105812E+09 | 14192.34 | 19739518.94 | 2632403.30 | 0.355362E+10 | 0.208415E+10 | 1773.58 | 0.47 |
Minimum of Months | 23064199.14 | 0.00 | 0.00 | 14970.48 | 0.00 | 441204.92 | 1989132.95 | 0.00 | 0.47 |
Maximum of Months | 0.166731E+09 | 60687528.90 | 12930.66 | 3475758.68 | 1667093.96 | 0.719970E+09 | 0.340390E+09 | 1269.69 | 0.48 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 99480173.18 | 0.00 | 0.00 | 2904.06 | 0.00 | 0.774658E+09 | 533554.48 | 0.00 | 0.47 |
February | 0.140156E+09 | 0.00 | 0.00 | 82625.33 | 0.00 | 0.593288E+09 | 25442741.71 | 0.00 | 0.47 |
March | 0.184741E+09 | 0.00 | 0.00 | 400161.14 | 0.00 | 0.482945E+09 | 84119324.73 | 0.00 | 0.47 |
April | 0.138326E+09 | 2297214.31 | 0.00 | 1275454.88 | 42054.91 | 0.271988E+09 | 0.205958E+09 | 0.00 | 0.47 |
May | 89091246.97 | 2477704.96 | 0.00 | 2695085.13 | 136822.68 | 0.122393E+09 | 0.310853E+09 | 0.00 | 0.47 |
June | 55654809.02 | 2137445.92 | 0.00 | 3090846.92 | 91112.99 | 25045291.92 | 0.291613E+09 | 0.00 | 0.47 |
July | 28514164.36 | 29450569.99 | 162.51 | 3172575.15 | 733030.55 | 478782.06 | 0.237034E+09 | 558.88 | 0.47 |
August | 26530783.30 | 59577457.76 | 11912.50 | 2165134.06 | 2769859.35 | 487242.66 | 0.180608E+09 | 2286.18 | 0.48 |
September | 71541357.91 | 8141194.93 | 4871.87 | 2113301.87 | 454079.27 | 51699686.39 | 0.248722E+09 | 535.67 | 0.47 |
October | 0.145894E+09 | 0.00 | 0.00 | 659515.04 | 0.00 | 0.336136E+09 | 0.122491E+09 | 0.00 | 0.47 |
November | 0.150821E+09 | 102260.91 | 0.00 | 50634.95 | 16596.67 | 0.542381E+09 | 19168362.39 | 0.00 | 0.47 |
December | 0.115161E+09 | 0.00 | 0.00 | 5050.91 | 0.00 | 0.726166E+09 | 680468.31 | 0.00 | 0.47 |
Annual Sum or Average | 0.124591E+10 | 0.104184E+09 | 16946.88 | 15713289.42 | 4243556.43 | 0.392767E+10 | 0.172722E+10 | 3380.73 | 0.47 |
Minimum of Months | 26530783.30 | 0.00 | 0.00 | 2904.06 | 0.00 | 478782.06 | 533554.48 | 0.00 | 0.47 |
Maximum of Months | 0.184741E+09 | 59577457.76 | 11912.50 | 3172575.15 | 2769859.35 | 0.774658E+09 | 0.310853E+09 | 2286.18 | 0.48 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.127114E+10 | 0.00 | 0.00 | 1730511.79 | 0.00 | 0.361641E+10 | 0.730723E+09 | 0.00 | 0.54 |
February | 0.911537E+09 | 0.00 | 0.00 | 5840514.88 | 0.00 | 0.234907E+10 | 0.161011E+10 | 0.00 | 0.54 |
March | 0.826566E+09 | 0.00 | 0.00 | 10664635.38 | 0.00 | 0.144165E+10 | 0.255422E+10 | 0.00 | 0.54 |
April | 0.579756E+09 | 14768531.52 | 0.00 | 14245525.05 | 261839.64 | 0.648187E+09 | 0.272571E+10 | 0.00 | 0.54 |
May | 0.430022E+09 | 15995128.34 | 0.00 | 17935098.06 | 803844.90 | 0.193167E+09 | 0.273233E+10 | 0.00 | 0.54 |
June | 0.286956E+09 | 13203512.88 | 0.00 | 19599455.69 | 1115517.81 | 17353547.34 | 0.208815E+10 | 0.00 | 0.54 |
July | 0.169416E+09 | 0.188083E+09 | 2668.70 | 18446063.40 | 5853894.72 | 3042346.29 | 0.153877E+10 | 1966.40 | 0.54 |
August | 0.145718E+09 | 0.390038E+09 | 36553.27 | 14825961.80 | 10610220.40 | 2605975.02 | 0.118481E+10 | 3141.53 | 0.54 |
September | 0.366985E+09 | 53952547.34 | 0.00 | 20038126.96 | 1308915.52 | 61281911.35 | 0.195523E+10 | 0.00 | 0.54 |
October | 0.615157E+09 | 0.00 | 0.00 | 15255824.79 | 0.00 | 0.536720E+09 | 0.272130E+10 | 0.00 | 0.54 |
November | 0.102838E+10 | 763688.78 | 0.00 | 3940905.70 | 0.00 | 0.212051E+10 | 0.142465E+10 | 0.00 | 0.54 |
December | 0.107369E+10 | 0.00 | 0.00 | 3310014.70 | 0.00 | 0.331581E+10 | 0.101733E+10 | 0.00 | 0.53 |
Annual Sum or Average | 0.770531E+10 | 0.676804E+09 | 39221.97 | 0.145833E+09 | 19954232.99 | 0.143058E+11 | 0.222833E+11 | 5107.93 | 0.54 |
Minimum of Months | 0.145718E+09 | 0.00 | 0.00 | 1730511.79 | 0.00 | 2605975.02 | 0.730723E+09 | 0.00 | 0.53 |
Maximum of Months | 0.127114E+10 | 0.390038E+09 | 36553.27 | 20038126.96 | 10610220.40 | 0.361641E+10 | 0.273233E+10 | 3141.53 | 0.54 |
Report: MechanicalVentilationLoadsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.372297E+11 | 0.00 | 0.00 | 5767218.18 | 0.00 | 0.00 | 0.243378E+11 | 0.00 | 7.89 |
February | 0.320258E+11 | 0.00 | 0.00 | 6128636.34 | 0.00 | 0.00 | 0.234111E+11 | 0.00 | 7.94 |
March | 0.331218E+11 | 0.00 | 0.00 | 9053348.91 | 0.00 | 0.00 | 0.282161E+11 | 0.00 | 7.90 |
April | 0.270151E+11 | 16604979.38 | 0.00 | 10743934.46 | 77660893.05 | 0.00 | 0.287321E+11 | 0.00 | 7.91 |
May | 0.217728E+11 | 24928717.55 | 0.00 | 14273661.51 | 67700870.13 | 0.00 | 0.314330E+11 | 0.00 | 7.92 |
June | 0.141883E+11 | 43307821.66 | 0.00 | 16908026.87 | 39541791.82 | 0.00 | 0.298792E+11 | 0.00 | 7.94 |
July | 0.866617E+10 | 0.514257E+09 | 0.00 | 18097422.00 | 0.756842E+09 | 0.00 | 0.274379E+11 | 0.00 | 7.93 |
August | 0.761848E+10 | 0.719501E+09 | 0.00 | 18137724.56 | 0.177527E+10 | 0.00 | 0.230793E+11 | 0.00 | 7.96 |
September | 0.181498E+11 | 97897619.65 | 0.00 | 13767280.37 | 0.267292E+09 | 0.00 | 0.283492E+11 | 0.00 | 7.94 |
October | 0.304519E+11 | 0.00 | 0.00 | 10355355.93 | 0.00 | 0.00 | 0.287108E+11 | 0.00 | 7.94 |
November | 0.333157E+11 | 0.00 | 0.00 | 7778176.40 | 0.00 | 0.00 | 0.257798E+11 | 0.00 | 7.90 |
December | 0.360852E+11 | 0.00 | 0.00 | 5662519.89 | 0.00 | 0.00 | 0.253257E+11 | 0.00 | 7.88 |
Annual Sum or Average | 0.299641E+12 | 0.141650E+10 | 0.00 | 0.136673E+09 | 0.298430E+10 | 0.00 | 0.324692E+12 | 0.00 | 7.92 |
Minimum of Months | 0.761848E+10 | 0.00 | 0.00 | 5662519.89 | 0.00 | 0.00 | 0.230793E+11 | 0.00 | 7.88 |
Maximum of Months | 0.372297E+11 | 0.719501E+09 | 0.00 | 18137724.56 | 0.177527E+10 | 0.00 | 0.314330E+11 | 0.00 | 7.96 |
Report: MechanicalVentilationLoadsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.371071E+11 | 0.00 | 0.00 | 7973227.57 | 0.00 | 0.00 | 0.274735E+11 | 0.00 | 8.28 |
February | 0.316388E+11 | 0.00 | 0.00 | 8383835.21 | 0.00 | 0.00 | 0.265108E+11 | 0.00 | 8.33 |
March | 0.306103E+11 | 0.00 | 0.00 | 12181839.87 | 0.00 | 0.00 | 0.337286E+11 | 0.00 | 8.29 |
April | 0.238727E+11 | 33939317.89 | 0.00 | 14400062.78 | 64942669.99 | 0.00 | 0.346012E+11 | 0.00 | 8.30 |
May | 0.188069E+11 | 62729581.05 | 0.00 | 18853902.99 | 34435994.68 | 0.00 | 0.370005E+11 | 0.00 | 8.31 |
June | 0.120713E+11 | 47354641.56 | 0.00 | 21928583.15 | 39552043.38 | 0.00 | 0.341499E+11 | 0.00 | 8.33 |
July | 0.738922E+10 | 0.695943E+09 | 0.00 | 23136472.66 | 0.637400E+09 | 0.00 | 0.304787E+11 | 0.00 | 8.32 |
August | 0.628045E+10 | 0.101550E+10 | 0.00 | 22749301.67 | 0.160143E+10 | 0.00 | 0.259169E+11 | 0.00 | 8.35 |
September | 0.163221E+11 | 0.130041E+09 | 0.00 | 17789956.02 | 0.253032E+09 | 0.00 | 0.324506E+11 | 0.00 | 8.33 |
October | 0.282245E+11 | 0.00 | 0.00 | 13726006.12 | 0.00 | 0.00 | 0.338324E+11 | 0.00 | 8.33 |
November | 0.325495E+11 | 0.00 | 0.00 | 10394397.21 | 0.00 | 0.00 | 0.294377E+11 | 0.00 | 8.29 |
December | 0.364308E+11 | 0.00 | 0.00 | 7903591.83 | 0.00 | 0.00 | 0.279854E+11 | 0.00 | 8.27 |
Annual Sum or Average | 0.281304E+12 | 0.198551E+10 | 0.00 | 0.179421E+09 | 0.263079E+10 | 0.00 | 0.373566E+12 | 0.00 | 8.31 |
Minimum of Months | 0.628045E+10 | 0.00 | 0.00 | 7903591.83 | 0.00 | 0.00 | 0.259169E+11 | 0.00 | 8.27 |
Maximum of Months | 0.371071E+11 | 0.101550E+10 | 0.00 | 23136472.66 | 0.160143E+10 | 0.00 | 0.370005E+11 | 0.00 | 8.35 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 92913676.83 | 0.00 | 0.00 | 0.648967E+11 | 0.00 | 26.86 |
February | 0.00 | 0.00 | 0.00 | 85109455.64 | 0.00 | 0.00 | 0.584424E+11 | 0.00 | 27.04 |
March | 0.00 | 0.00 | 0.00 | 97775342.63 | 0.00 | 0.00 | 0.646791E+11 | 0.00 | 26.92 |
April | 0.00 | 99820383.72 | 0.00 | 0.100629E+09 | 0.00 | 0.00 | 0.587857E+11 | 0.00 | 26.97 |
May | 0.00 | 98068045.81 | 0.00 | 0.109884E+09 | 0.00 | 0.00 | 0.560990E+11 | 0.00 | 27.00 |
June | 0.00 | 87725032.97 | 0.00 | 0.112070E+09 | 0.00 | 0.00 | 0.464487E+11 | 0.00 | 27.05 |
July | 0.00 | 0.134599E+10 | 0.00 | 99128017.69 | 0.00 | 0.00 | 0.380453E+11 | 0.00 | 27.04 |
August | 0.00 | 0.264181E+10 | 0.00 | 84355513.19 | 0.00 | 0.00 | 0.323482E+11 | 0.00 | 27.12 |
September | 0.00 | 0.386698E+09 | 0.00 | 0.100971E+09 | 0.00 | 0.00 | 0.490177E+11 | 0.00 | 27.05 |
October | 0.00 | 0.00 | 0.00 | 0.101153E+09 | 0.00 | 0.00 | 0.623834E+11 | 0.00 | 27.04 |
November | 0.00 | 0.00 | 0.00 | 91010089.11 | 0.00 | 0.00 | 0.623007E+11 | 0.00 | 26.90 |
December | 0.00 | 0.00 | 0.00 | 93366737.67 | 0.00 | 0.00 | 0.647331E+11 | 0.00 | 26.82 |
Annual Sum or Average | 0.00 | 0.466011E+10 | 0.00 | 0.116837E+10 | 0.00 | 0.00 | 0.658180E+12 | 0.00 | 26.98 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 84355513.19 | 0.00 | 0.00 | 0.323482E+11 | 0.00 | 26.82 |
Maximum of Months | 0.00 | 0.264181E+10 | 0.00 | 0.112070E+09 | 0.00 | 0.00 | 0.648967E+11 | 0.00 | 27.12 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.127634E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.865671E+10 | 0.00 | 0.00 | 2.20 |
February | 0.145962E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.469134E+10 | 0.00 | 0.00 | 2.22 |
March | 0.208785E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.462954E+09 | 0.00 | 0.00 | 2.21 |
April | 0.193699E+11 | 0.00 | 0.00 | 0.00 | 32793258.18 | 27191048.14 | 0.00 | 0.00 | 2.21 |
May | 0.185142E+11 | 0.00 | 0.00 | 0.00 | 32224026.63 | 0.00 | 0.00 | 0.00 | 2.21 |
June | 0.153361E+11 | 0.00 | 0.00 | 0.00 | 28821764.38 | 0.00 | 0.00 | 0.00 | 2.21 |
July | 0.125662E+11 | 0.00 | 0.00 | 0.00 | 0.442190E+09 | 0.00 | 0.00 | 0.00 | 2.21 |
August | 0.106855E+11 | 0.00 | 0.00 | 0.00 | 0.867881E+09 | 0.00 | 0.00 | 0.00 | 2.22 |
September | 0.161809E+11 | 0.00 | 0.00 | 0.00 | 0.127042E+09 | 0.00 | 0.00 | 0.00 | 2.22 |
October | 0.205851E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.22 |
November | 0.178961E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.266480E+10 | 0.00 | 0.00 | 2.21 |
December | 0.133589E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.800673E+10 | 0.00 | 0.00 | 2.20 |
Annual Sum or Average | 0.192731E+12 | 0.00 | 0.00 | 0.00 | 0.153095E+10 | 0.245097E+11 | 0.00 | 0.00 | 2.21 |
Minimum of Months | 0.106855E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.20 |
Maximum of Months | 0.208785E+11 | 0.00 | 0.00 | 0.00 | 0.867881E+09 | 0.865671E+10 | 0.00 | 0.00 | 2.22 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:58:38
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.600800E+11 | 0.144708E+11 | 0.114541E+12 | 0.141457E+13 | 0.890544E+11 |
February | 0.131618E+12 | 0.120278E+11 | 0.964230E+11 | 0.118605E+13 | 0.983154E+11 |
March | 0.250106E+12 | 0.113591E+11 | 0.923782E+11 | 0.111997E+13 | 0.136511E+12 |
April | 0.402913E+12 | 0.911301E+10 | 0.757998E+11 | 0.893398E+12 | 0.239586E+12 |
May | 0.528531E+12 | 0.776232E+10 | 0.663620E+11 | 0.751815E+12 | 0.356890E+12 |
June | 0.543824E+12 | 0.563767E+10 | 0.515794E+11 | 0.529326E+12 | 0.489277E+12 |
July | 0.565446E+12 | 0.389567E+10 | 0.400375E+11 | 0.366099E+12 | 0.708961E+12 |
August | 0.444999E+12 | 0.285574E+10 | 0.329474E+11 | 0.266202E+12 | 0.823336E+12 |
September | 0.282773E+12 | 0.565725E+10 | 0.534346E+11 | 0.547357E+12 | 0.448842E+12 |
October | 0.188261E+12 | 0.883166E+10 | 0.761816E+11 | 0.868374E+12 | 0.204800E+12 |
November | 0.698852E+11 | 0.111018E+11 | 0.927661E+11 | 0.109450E+13 | 0.108556E+12 |
December | 0.381693E+11 | 0.136988E+11 | 0.109437E+12 | 0.134365E+13 | 0.903001E+11 |
Annual Sum or Average | 0.350660E+13 | 0.106412E+12 | 0.901888E+12 | 0.103813E+14 | 0.379443E+13 |
Minimum of Months | 0.381693E+11 | 0.285574E+10 | 0.329474E+11 | 0.266202E+12 | 0.890544E+11 |
Maximum of Months | 0.565446E+12 | 0.144708E+11 | 0.114541E+12 | 0.141457E+13 | 0.823336E+12 |