Table of Contents

Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:58

Tabular Output Report in Format: HTML

Building: HotelLarge

Environment: RUNPERIOD 1 ** Miami Intl Ap FL USA TMY3 WMO#=722020

Simulation Timestamp: 2023-10-16 08:58:20


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2023-10-16 08:58:20

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [GJ] Energy Per Total Building Area [MJ/m2] Energy Per Conditioned Building Area [MJ/m2]
Total Site Energy 17016.64 1499.89 1499.89
Net Site Energy 17016.64 1499.89 1499.89
Total Source Energy 43723.16 3853.86 3853.86
Net Source Energy 43723.16 3853.86 3853.86


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 1.200
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil No 1 1.050
Fuel Oil No 2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [m2]
Total Building Area 11345.29
Net Conditioned Building Area 11345.29
Unconditioned Building Area 0.00


End Uses

Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating 0.00 468.86 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 5293.72 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 1174.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 262.62 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 1751.30 1788.84 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 679.68 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 1826.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 459.98 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 520.33 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 90.77 2623.98 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 9857.19
Refrigeration 75.79 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 12134.96 4881.68 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 9857.19
Note: Natural gas appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler 0.00 468.86 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 5293.72 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 1174.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 262.62 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 959.56 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Cooking 762.04 1198.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ReachInFreezer 16.27 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ReachInRefrigerator 13.43 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Laundry 0.00 590.20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Transformer 32.92 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLift 616.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLightsFan 30.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  General 1826.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 459.98 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 520.33 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Water Heater 90.77 2623.98 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 5742.51
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 4114.69
Refrigeration General 18.27 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  LowTempRefrigeration 22.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  MedTempRefrigeration 34.87 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Space Type

Space Type Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating Unassigned 0.00 468.86 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling Unassigned 5293.72 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting GENERAL 1174.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Unassigned 262.62 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment GENERAL 1751.30 1788.84 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Unassigned 679.68 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Unassigned 1826.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps Unassigned 459.98 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery Unassigned 520.33 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Unassigned 90.77 2623.98 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 9857.19
Refrigeration Unassigned 75.79 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 126.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 676.15 272.61 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.87
Other 266.82 157.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 1069.60 430.28 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.87


Utility Use Per Total Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 126.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 676.15 272.61 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.87
Other 266.82 157.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 1069.60 430.28 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.87


Electric Loads Satisfied

Electricity [GJ] Percent Electricity [%]
Fuel-Fired Power Generation 0.000 0.00
High Temperature Geothermal* 0.000 0.00
Photovoltaic Power 0.000 0.00
Wind Power 0.000 0.00
Power Conversion 0.000 0.00
Net Decrease in On-Site Storage 0.000 0.00
Total On-Site Electric Sources 0.000 0.00
     
Electricity Coming From Utility 12134.962 100.00
Surplus Electricity Going To Utility 0.000 0.00
Net Electricity From Utility 12134.962 100.00
     
Total On-Site and Utility Electric Sources 12134.962 100.00
Total Electricity End Uses 12134.962 100.00


On-Site Thermal Sources

Heat [GJ] Percent Heat [%]
Water-Side Heat Recovery 0.00 0.00
Air to Air Heat Recovery for Cooling 7902.48 98.99
Air to Air Heat Recovery for Heating 80.71 1.01
High-Temperature Geothermal* 0.00 0.00
Solar Water Thermal 0.00 0.00
Solar Air Thermal 0.00 0.00
Total On-Site Thermal Sources 7983.19 100.00


Water Source Summary

Water [m3] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 9857.19 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 9857.19 100.00
Total Water End Uses 9857.19 100.00


Setpoint Not Met Criteria

Degrees [deltaC]
Tolerance for Zone Heating Setpoint Not Met Time 0.56
Tolerance for Zone Cooling Setpoint Not Met Time 0.56


Comfort and Setpoint Not Met Summary

Facility [Hours]
Time Setpoint Not Met During Occupied Heating 0.00
Time Setpoint Not Met During Occupied Cooling 45.33
Time Not Comfortable Based on Simple ASHRAE 55-2004 6066.83


Note 1: An asterisk (*) indicates that the feature is not yet implemented.

Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Adaptive Comfort Summary
Initialization Summary
Annual Heat Emissions Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
Coil Sizing Details
System Summary
Outdoor Air Summary
Outdoor Air Details
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary
Annual Thermal Resilience Summary
Annual CO2 Resilience Summary
Annual Visual Resilience Summary

NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODENAME IECC

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2012

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

| Environment |

NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE

| Environment |

NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 1A

| Environment |

NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_FL_MIAMI

| Environment |

ZoneCoolingSummaryMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

ZoneHeatingSummaryMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

ZoneElectricSummaryMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

SpaceGainsMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

PeakSpaceGainsMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

SpaceGainComponentsAtCoolingPeakMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

EnergyConsumptionElectricityNaturalGasMonthly

| Meter |

EndUseEnergyConsumptionElectricityMonthly

| Meter |

EndUseEnergyConsumptionNaturalGasMonthly

| Meter |

PeakEnergyEndUseElectricityPart1Monthly

| Meter |

PeakEnergyEndUseElectricityPart2Monthly

| Meter |

ElectricComponentsOfPeakDemandMonthly

| Meter |

PeakEnergyEndUseNaturalGasMonthly

| Meter |

SetpointsNotMetWithTemperaturesMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

ComfortReportSimple55Monthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

OccupantComfortDataSummaryMonthly

| BASEMENT PEOPLE | RETAIL_1_FLR_1 PEOPLE | RETAIL_2_FLR_1 PEOPLE | LAUNDRY_FLR_1 PEOPLE | CAFE_FLR_1 PEOPLE | LOBBY_FLR_1 PEOPLE | ROOM_1_FLR_3 PEOPLE | ROOM_2_FLR_3 PEOPLE | ROOM_3_MULT19_FLR_3 PEOPLE | ROOM_4_MULT19_FLR_3 PEOPLE | ROOM_5_FLR_3 PEOPLE | ROOM_6_FLR_3 PEOPLE | ROOM_1_FLR_6 PEOPLE | ROOM_2_FLR_6 PEOPLE | ROOM_3_MULT9_FLR_6 PEOPLE | BANQUET_FLR_6 PEOPLE | DINING_FLR_6 PEOPLE | KITCHEN_FLR_6 PEOPLE | STORAGE_FLR_1 PEOPLE | CORRIDOR_FLR_3 PEOPLE | CORRIDOR_FLR_6 PEOPLE | MECH_FLR_1 PEOPLE |

ChillerReportMonthly

| COOLSYS1 CHILLER1 |

BoilerReportMonthly

| HEATSYS1 BOILER |

DXReportMonthly

| VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |

WindowReportMonthly

| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |

WindowEnergyReportMonthly

| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |

WindowZoneSummaryMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

WindowEnergyZoneSummaryMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

AverageOutdoorConditionsMonthly

| Environment |

OutdoorConditionsMaximumDryBulbMonthly

| Environment |

OutdoorConditionsMinimumDryBulbMonthly

| Environment |

OutdoorConditionsMaximumWetBulbMonthly

| Environment |

OutdoorConditionsMaximumDewPointMonthly

| Environment |

OutdoorGroundConditionsMonthly

| Environment |

WaterHeaterReportMonthly

| SWH BOOSTER E WATER HEATER | SWH LAUNDRY G WATER HEATER | SWHSYS1 WATER HEATER |

DaylightingReportMonthly

| Environment |

CoilReportMonthly

| VAV WITH REHEAT HEATING COIL | BASEMENT VAV BOX REHEAT COIL | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | MECH_FLR_1 VAV BOX REHEAT COIL | STORAGE_FLR_1 VAV BOX REHEAT COIL | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | CAFE_FLR_1 VAV BOX REHEAT COIL | LOBBY_FLR_1 VAV BOX REHEAT COIL | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | BANQUET_FLR_6 VAV BOX REHEAT COIL | DINING_FLR_6 VAV BOX REHEAT COIL | KITCHEN_FLR_6 VAV BOX REHEAT COIL | FLR_3_DOAS HEATING COIL | ROOM_1_FLR_3 FAN COIL HEATING COIL | ROOM_2_FLR_3 FAN COIL HEATING COIL | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_5_FLR_3 FAN COIL HEATING COIL | ROOM_6_FLR_3 FAN COIL HEATING COIL | ROOM_1_FLR_6 FAN COIL HEATING COIL | ROOM_2_FLR_6 FAN COIL HEATING COIL | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |

PlantLoopDemandReportMonthly

| HEATSYS1 | COOLSYS1 | SWHSYS1 |

FanReportMonthly

| FLR_3_DOAS FAN | VAV WITH REHEAT FAN | LAUNDRY_FLR_1 EXHAUST FAN | LOBBY_FLR_1 EXHAUST FAN | BANQUET_FLR_6 EXHAUST FAN | DINING_FLR_6 EXHAUST FAN | KITCHEN_FLR_6 EXHAUST FAN | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN |

PumpReportMonthly

| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 PUMP | SWHSYS1 PUMP |

CondLoopDemandReportMonthly

| HEATSYS1 | COOLSYS1 | SWHSYS1 |

ZoneTemperatureOscillationReportMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

AirLoopSystemEnergyAndWaterUseMonthly

| VAV WITH REHEAT | FLR_3_DOAS |

AirLoopSystemComponentLoadsMonthly

| VAV WITH REHEAT | FLR_3_DOAS |

AirLoopSystemComponentEnergyUseMonthly

| VAV WITH REHEAT | FLR_3_DOAS |

MechanicalVentilationLoadsMonthly

| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |

HeatEmissionsReportMonthly

| Environment |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2023-10-16 08:58:20

General

Value
Program Version and Build EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:58
RunPeriod RUNPERIOD 1
Weather File Miami Intl Ap FL USA TMY3 WMO#=722020
Latitude [deg] 25.82
Longitude [deg] -80.3
Elevation [m] 11.00
Time Zone -5.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 4559.59 1873.43 406.47 1873.22 406.47
Above Ground Wall Area [m2] 4025.82 1662.30 350.71 1662.10 350.71
Window Opening Area [m2] 1213.79 432.95 85.85 609.15 85.85
Gross Window-Wall Ratio [%] 26.62 23.11 21.12 32.52 21.12
Above Ground Window-Wall Ratio [%] 30.15 26.05 24.48 36.65 24.48


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 4559.59 1873.43 406.47 1873.22 406.47
Above Ground Wall Area [m2] 4025.82 1662.30 350.71 1662.10 350.71
Window Opening Area [m2] 1213.79 432.95 85.85 609.15 85.85
Gross Window-Wall Ratio [%] 26.62 23.11 21.12 32.52 21.12
Above Ground Window-Wall Ratio [%] 30.15 26.05 24.48 36.65 24.48


Skylight-Roof Ratio

Total
Gross Roof Area [m2] 1978.84
Skylight Area [m2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [m3] Multipliers Above Ground Gross Wall Area [m2] Underground Gross Wall Area [m2] Window Glass Area [m2] Opening Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
BASEMENT 1978.83 Yes Yes 4826.41 1.00 0.00 533.77 0.00 0.00 8.7495 18.58 5.3800
RETAIL_1_FLR_1 67.07 Yes Yes 265.76 1.00 68.84 0.00 23.26 23.26 13.0124 6.19 10.7600
RETAIL_2_FLR_1 77.67 Yes Yes 307.76 1.00 26.57 0.00 0.00 0.00 13.0124 6.19 10.7600
MECH_FLR_1 164.24 Yes Yes 650.80 1.00 62.80 0.00 0.00 0.00 10.0642 61.93 5.3800
STORAGE_FLR_1 94.76 Yes Yes 375.47 1.00 36.23 0.00 0.00 0.00 7.3195 46.45 2.6900
LAUNDRY_FLR_1 78.04 Yes Yes 309.22 1.00 85.75 0.00 0.00 0.00 5.4896 9.29 597.5300
CAFE_FLR_1 188.86 Yes Yes 748.35 1.00 152.17 0.00 65.50 65.50 12.8090 1.33 5.3800
LOBBY_FLR_1 1308.19 Yes Yes 5183.56 1.00 434.79 0.00 85.08 85.08 10.0642 3.10 8.0700
ROOM_1_FLR_3 39.02 Yes Yes 118.94 4.00 39.95 0.00 13.18 13.18 10.0642 26.01 6.7500
ROOM_2_FLR_3 39.02 Yes Yes 118.93 4.00 39.95 0.00 13.18 13.18 10.0642 26.01 6.7500
ROOM_3_MULT19_FLR_3 24.52 Yes Yes 74.75 76.00 11.15 0.00 3.68 3.68 10.0642 16.35 10.5200
ROOM_4_MULT19_FLR_3 24.53 Yes Yes 74.77 76.00 11.15 0.00 3.68 3.68 10.0642 16.35 10.5200
ROOM_5_FLR_3 39.02 Yes Yes 118.94 4.00 39.95 0.00 13.18 13.18 10.0642 26.01 6.7500
ROOM_6_FLR_3 39.02 Yes Yes 118.93 4.00 39.95 0.00 13.18 13.18 10.0642 26.01 6.7500
CORRIDOR_FLR_3 389.40 Yes Yes 1186.91 4.00 48.31 0.00 15.94 15.94 3.6597 18.58 0.0000
ROOM_1_FLR_6 39.02 Yes Yes 118.94 1.00 39.95 0.00 13.18 13.18 10.0642 26.01 6.7500
ROOM_2_FLR_6 39.02 Yes Yes 118.93 1.00 39.95 0.00 13.18 13.18 10.0642 26.01 6.7500
ROOM_3_MULT9_FLR_6 24.53 Yes Yes 74.77 9.00 20.44 0.00 6.74 6.74 10.0642 16.35 10.5200
BANQUET_FLR_6 331.66 Yes Yes 1010.89 1.00 97.55 0.00 32.19 32.19 12.8090 1.33 67.8200
DINING_FLR_6 331.66 Yes Yes 1010.89 1.00 97.55 0.00 32.19 32.19 12.8090 1.33 67.8200
KITCHEN_FLR_6 103.30 Yes Yes 314.87 1.00 87.33 0.00 26.37 26.37 10.9792 4.65 2936.4163
CORRIDOR_FLR_6 412.12 Yes Yes 1256.16 1.00 85.47 0.00 28.20 28.20 3.6597 18.58 0.0000
Total 11345.29     35184.81   4025.82 533.77 1213.79 1213.79 8.9207 7.07 41.0885
Conditioned Total 11345.29     35184.81   4025.82 533.77 1213.79 1213.79 8.9207 7.07 41.0885
Unconditioned Total 0.00     0.00   0.00 0.00 0.00 0.00      
Not Part of Total 0.00     0.00   0.00 0.00 0.00 0.00      


Space Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Multipliers Zone Name Space Type Radiant/Solar Enclosure Name Lighting [W/m2] People [m2 per person] Plug and Process [W/m2] Tags
BASEMENT 1978.83 Yes Yes 1.00 BASEMENT GENERAL BASEMENT 8.7495 18.58 5.3800  
RETAIL_1_FLR_1 67.07 Yes Yes 1.00 RETAIL_1_FLR_1 GENERAL RETAIL_1_FLR_1 13.0124 6.19 10.7600  
RETAIL_2_FLR_1 77.67 Yes Yes 1.00 RETAIL_2_FLR_1 GENERAL RETAIL_2_FLR_1 13.0124 6.19 10.7600  
MECH_FLR_1 164.24 Yes Yes 1.00 MECH_FLR_1 GENERAL MECH_FLR_1 10.0642 61.93 5.3800  
STORAGE_FLR_1 94.76 Yes Yes 1.00 STORAGE_FLR_1 GENERAL STORAGE_FLR_1 7.3195 46.45 2.6900  
LAUNDRY_FLR_1 78.04 Yes Yes 1.00 LAUNDRY_FLR_1 GENERAL LAUNDRY_FLR_1 5.4896 9.29 597.5300  
CAFE_FLR_1 188.86 Yes Yes 1.00 CAFE_FLR_1 GENERAL CAFE_FLR_1 12.8090 1.33 5.3800  
LOBBY_FLR_1 1308.19 Yes Yes 1.00 LOBBY_FLR_1 GENERAL LOBBY_FLR_1 10.0642 3.10 8.0700  
ROOM_1_FLR_3 39.02 Yes Yes 4.00 ROOM_1_FLR_3 GENERAL ROOM_1_FLR_3 10.0642 26.01 6.7500  
ROOM_2_FLR_3 39.02 Yes Yes 4.00 ROOM_2_FLR_3 GENERAL ROOM_2_FLR_3 10.0642 26.01 6.7500  
ROOM_3_MULT19_FLR_3 24.52 Yes Yes 76.00 ROOM_3_MULT19_FLR_3 GENERAL ROOM_3_MULT19_FLR_3 10.0642 16.35 10.5200  
ROOM_4_MULT19_FLR_3 24.53 Yes Yes 76.00 ROOM_4_MULT19_FLR_3 GENERAL ROOM_4_MULT19_FLR_3 10.0642 16.35 10.5200  
ROOM_5_FLR_3 39.02 Yes Yes 4.00 ROOM_5_FLR_3 GENERAL ROOM_5_FLR_3 10.0642 26.01 6.7500  
ROOM_6_FLR_3 39.02 Yes Yes 4.00 ROOM_6_FLR_3 GENERAL ROOM_6_FLR_3 10.0642 26.01 6.7500  
CORRIDOR_FLR_3 389.40 Yes Yes 4.00 CORRIDOR_FLR_3 GENERAL CORRIDOR_FLR_3 3.6597 18.58 0.0000  
ROOM_1_FLR_6 39.02 Yes Yes 1.00 ROOM_1_FLR_6 GENERAL ROOM_1_FLR_6 10.0642 26.01 6.7500  
ROOM_2_FLR_6 39.02 Yes Yes 1.00 ROOM_2_FLR_6 GENERAL ROOM_2_FLR_6 10.0642 26.01 6.7500  
ROOM_3_MULT9_FLR_6 24.53 Yes Yes 9.00 ROOM_3_MULT9_FLR_6 GENERAL ROOM_3_MULT9_FLR_6 10.0642 16.35 10.5200  
BANQUET_FLR_6 331.66 Yes Yes 1.00 BANQUET_FLR_6 GENERAL BANQUET_FLR_6 12.8090 1.33 67.8200  
DINING_FLR_6 331.66 Yes Yes 1.00 DINING_FLR_6 GENERAL DINING_FLR_6 12.8090 1.33 67.8200  
KITCHEN_FLR_6 103.30 Yes Yes 1.00 KITCHEN_FLR_6 GENERAL KITCHEN_FLR_6 10.9792 4.65 2936.4163  
CORRIDOR_FLR_6 412.12 Yes Yes 1.00 CORRIDOR_FLR_6 GENERAL CORRIDOR_FLR_6 3.6597 18.58 0.0000  
Total 11345.29             8.9207 3.54 41.0885  
Conditioned Total 11345.29             8.9207 3.54 41.0885  
Unconditioned Total 0.00             0.0000 0.00 0.0000  
Not Part of Total 0.00             0.0000 0.00 0.0000  


Space Type Summary

Total Area [m2] Conditioned Area [m2] Unconditioned Area [m2] Not Part of Total Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
GENERAL 11345.29 11345.29 0.00 0.00 4.6908 8.82 37.2165
Total 11345.29 11345.29 0.00 0.00      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2023-10-16 08:58:20

End Uses

Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Time of Peak 27-JUL-18:10 17-DEC-17:00 - - - - - - - - - - 02-JAN-21:10
Heating 0.00 51148.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 317380.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 82800.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 79617.06 87521.34 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 32686.23 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 72579.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 16647.58 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 16791.79 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 4738.75 214046.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 2934.60 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 626175.88 352716.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Subcategory

Subcategory Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Heating General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler 0.00 51148.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 317380.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 82800.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 49434.66 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Cooking 29240.64 74976.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ReachInFreezer 515.92 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ReachInRefrigerator 425.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Laundry 0.00 12545.23 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Transformer 1560.87 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLift 30153.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLightsFan 972.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  General 72579.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 16647.58 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 16791.79 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Water Heater 4738.75 214046.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 642.84 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  LowTempRefrigeration 1186.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  MedTempRefrigeration 1104.91 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2023-10-16 08:58:20

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [GJ] Source Natural Gas [GJ] Source Gasoline [GJ] Source Diesel [GJ] Source Coal [GJ] Source Fuel Oil No 1 [GJ] Source Fuel Oil No 2 [GJ] Source Propane [GJ] Source Other Fuel 1 [GJ] Source Other Fuel 2 [GJ] Source District Cooling [GJ] Source District Heating [GJ]
Heating 0.00 508.25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 16765.22 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 3718.41 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 831.73 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 5546.36 1939.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 2152.55 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 5784.99 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 1456.75 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 1647.90 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 287.47 2844.39 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 240.03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 38431.43 5291.74 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 44.80 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 1477.73 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 327.75 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 73.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 488.87 170.92 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 189.73 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 509.90 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 128.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 145.25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 25.34 250.71 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 21.16 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 3387.44 466.43 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 44.80 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 1477.73 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 327.75 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 73.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 488.87 170.92 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 189.73 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 509.90 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 128.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 145.25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 25.34 250.71 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 21.16 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 3387.44 466.43 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2023-10-16 08:58:20

AirTerminal:SingleDuct:VAV:Reheat

Design Size Maximum Air Flow Rate [m3/s] Design Size Constant Minimum Air Flow Fraction User-Specified Constant Minimum Air Flow Fraction Design Size Minimum Air Flow Rate [m3/s] Design Size Maximum Flow Fraction during Reheat [] User-Specified Maximum Flow Fraction during Reheat [] Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] Design Size Maximum Reheat Water Flow Rate [m3/s] Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] Design Size Reheat Coil Sizing Inlet Air Temperature [C] Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir]
BASEMENT VAV BOX COMPONENT 2.66 0.566525 0.995000 2.65 1.00 0.500000 0.000673 0.000122 2.65 16.70 0.008000
RETAIL_1_FLR_1 VAV BOX COMPONENT 0.293638 0.174053 0.995000 0.292169 0.995000 0.500000 0.002189 0.000027 0.292169 16.70 0.008000
RETAIL_2_FLR_1 VAV BOX COMPONENT 0.242241 0.244318 0.995000 0.241029 0.995000 0.500000 0.001559 0.000016 0.241029 16.70 0.008000
MECH_FLR_1 VAV BOX COMPONENT 0.261455 0.478680 0.995000 0.260148 1.00 0.500000 0.000796 0.000020 0.260148 16.70 0.008000
STORAGE_FLR_1 VAV BOX COMPONENT 0.130529 0.553183 0.995000 0.129877 1.00 0.500000 0.000689 0.000011 0.129877 16.70 0.008000
LAUNDRY_FLR_1 VAV BOX COMPONENT 3.27 0.072237 0.995000 3.25 0.995000 0.500000 0.020930 0.000161 3.25 16.70 0.008000
CAFE_FLR_1 VAV BOX COMPONENT 1.31 0.109897 0.995000 1.30 0.995000 0.500000 0.003467 0.000094 1.30 16.70 0.008000
LOBBY_FLR_1 VAV BOX COMPONENT 4.56 0.218686 0.995000 4.54 0.995000 0.500000 0.001742 0.000286 4.54 16.70 0.008000
CORRIDOR_FLR_3 VAV BOX COMPONENT 1.10 1.00 0.995000 1.10 1.00 0.500000 0.000353 0.000101 1.10 16.70 0.008000
BANQUET_FLR_6 VAV BOX COMPONENT 2.24 0.112981 0.995000 2.23 0.995000 0.500000 0.003372 0.000135 2.23 16.70 0.008000
DINING_FLR_6 VAV BOX COMPONENT 2.35 0.107669 0.995000 2.34 0.995000 0.500000 0.003539 0.000140 2.34 16.70 0.008000
KITCHEN_FLR_6 VAV BOX COMPONENT 2.25 0.838319 0.995000 2.24 0.995000 0.500000 0.010899 0.000103 2.24 16.70 0.008000
CORRIDOR_FLR_6 VAV BOX COMPONENT 0.663295 0.473453 0.995000 0.659978 1.00 0.500000 0.000805 0.000064 0.659978 16.70 0.008000
User-Specified values were used. Design Size values were used if no User-Specified values were provided. Design Size values may be derived from alternate User-Specified values.

Coil:Heating:Water

Design Size Rated Capacity [W] Design Size Maximum Water Flow Rate [m3/s] Design Size U-Factor Times Area Value [W/K]
BASEMENT VAV BOX REHEAT COIL 13966.41 0.000122 291.25
RETAIL_1_FLR_1 VAV BOX REHEAT COIL 3112.97 0.000027 68.56
RETAIL_2_FLR_1 VAV BOX REHEAT COIL 1773.53 0.000016 37.76
MECH_FLR_1 VAV BOX REHEAT COIL 2296.52 0.000020 49.63
STORAGE_FLR_1 VAV BOX REHEAT COIL 1228.03 0.000011 26.71
LAUNDRY_FLR_1 VAV BOX REHEAT COIL 18443.65 0.000161 386.13
CAFE_FLR_1 VAV BOX REHEAT COIL 10789.68 0.000094 231.87
LOBBY_FLR_1 VAV BOX REHEAT COIL 32731.44 0.000286 695.87
ROOM_1_FLR_3 FAN COIL HEATING COIL 3659.96 0.000032 104.57
ROOM_2_FLR_3 FAN COIL HEATING COIL 3660.18 0.000032 104.58
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL 21298.53 0.000186 608.55
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL 21316.13 0.000186 609.05
ROOM_5_FLR_3 FAN COIL HEATING COIL 3658.99 0.000032 104.55
ROOM_6_FLR_3 FAN COIL HEATING COIL 3659.22 0.000032 104.55
CORRIDOR_FLR_3 VAV BOX REHEAT COIL 11535.77 0.000101 253.72
ROOM_1_FLR_6 FAN COIL HEATING COIL 1124.65 0.000010 32.13
ROOM_2_FLR_6 FAN COIL HEATING COIL 1124.88 0.000010 32.14
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL 5435.88 0.000048 155.31
BANQUET_FLR_6 VAV BOX REHEAT COIL 15438.99 0.000135 327.31
DINING_FLR_6 VAV BOX REHEAT COIL 15947.96 0.000140 337.74
KITCHEN_FLR_6 VAV BOX REHEAT COIL 11816.39 0.000103 246.41
CORRIDOR_FLR_6 VAV BOX REHEAT COIL 7322.43 0.000064 162.01
VAV WITH REHEAT HEATING COIL 61543.58 0.000538 1142.02
FLR_3_DOAS HEATING COIL 5950.05 0.000052 110.41
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:ZoneExhaust

User-Specified Maximum Flow Rate [m3/s]
LOBBY_FLR_1 EXHAUST FAN 0.000000
BANQUET_FLR_6 EXHAUST FAN 0.000000
DINING_FLR_6 EXHAUST FAN 0.000000
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirTerminal:SingleDuct:ConstantVolume:NoReheat

Design Size Maximum Air Flow Rate [m3/s]
ROOM_1_FLR_3 DIRECT AIR 0.061735
ROOM_2_FLR_3 DIRECT AIR 0.061728
ROOM_3_MULT19_FLR_3 DIRECT AIR 0.837072
ROOM_4_MULT19_FLR_3 DIRECT AIR 0.837300
ROOM_5_FLR_3 DIRECT AIR 0.061735
ROOM_6_FLR_3 DIRECT AIR 0.061728
ROOM_1_FLR_6 DIRECT AIR 0.015434
ROOM_2_FLR_6 DIRECT AIR 0.015432
ROOM_3_MULT9_FLR_6 DIRECT AIR 0.099154
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

ZoneHVAC:FourPipeFanCoil

Design Size Maximum Supply Air Flow Rate [m3/s] Design Size Maximum Hot Water Flow [m3/s] Design Size Maximum Cold Water Flow [m3/s]
ROOM_1_FLR_3 FAN COIL 1.05 0.000032 0.000488
ROOM_2_FLR_3 FAN COIL 1.06 0.000032 0.000492
ROOM_3_MULT19_FLR_3 FAN COIL 5.95 0.000186 0.002714
ROOM_4_MULT19_FLR_3 FAN COIL 6.95 0.000186 0.003288
ROOM_5_FLR_3 FAN COIL 0.942610 0.000032 0.000443
ROOM_6_FLR_3 FAN COIL 0.950587 0.000032 0.000447
ROOM_1_FLR_6 FAN COIL 0.280254 0.000010 0.000130
ROOM_2_FLR_6 FAN COIL 0.282749 0.000010 0.000131
ROOM_3_MULT9_FLR_6 FAN COIL 1.17 0.000048 0.000553
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:OnOff

Design Size Maximum Flow Rate [m3/s]
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN 1.05
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN 1.06
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN 5.95
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN 6.95
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN 0.942610
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN 0.950587
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN 0.280254
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN 0.282749
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN 1.17
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Cooling:Water

Design Size Design Inlet Air Temperature [C] Design Size Design Inlet Water Temperature [C] Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] Design Size Design Outlet Air Temperature [C] Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] Design Size Design Water Flow Rate [m3/s] Design Size Design Air Flow Rate [m3/s] Design Size Design Coil Load [W]
ROOM_1_FLR_3 FAN COIL COOLING COIL 22.49 6.70 0.008872 12.80 0.008500 0.000488 1.05  
ROOM_2_FLR_3 FAN COIL COOLING COIL 22.49 6.70 0.008869 12.80 0.008500 0.000492 1.06  
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL 22.49 6.70 0.008785 12.80 0.008500 0.002714 5.95  
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL 22.49 6.70 0.008943 12.80 0.008500 0.003288 6.95  
ROOM_5_FLR_3 FAN COIL COOLING COIL 22.49 6.70 0.008915 12.80 0.008500 0.000443 0.942610  
ROOM_6_FLR_3 FAN COIL COOLING COIL 22.49 6.70 0.008912 12.80 0.008500 0.000447 0.950587  
ROOM_1_FLR_6 FAN COIL COOLING COIL 22.49 6.70 0.008850 12.80 0.008500 0.000130 0.280254  
ROOM_2_FLR_6 FAN COIL COOLING COIL 22.49 6.70 0.008846 12.80 0.008500 0.000131 0.282749  
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL 22.49 6.70 0.008953 12.80 0.008500 0.000553 1.17  
VAV WITH REHEAT COOLING COIL 33.20 6.70 0.017167 11.00 0.008500 0.040895 21.22 1144947.37
FLR_3_DOAS COOLING COIL 33.20 6.70 0.017167 11.94 0.008500 0.003869 2.05 108329.82
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC

Sum of Air Terminal Maximum Heating Flow Rates [m3/s] Sum of Air Terminal Minimum Heating Flow Rates [m3/s] Sum of Air Terminal Maximum Flow Rates [m3/s] Adjusted Heating Design Air Flow Rate [m3/s] Adjusted Cooling Design Air Flow Rate [m3/s] Adjusted Main Design Air Flow Rate [m3/s] User Heating Air Flow Ratio [] Calculated Heating Air Flow Ratio [] Design Supply Air Flow Rate [m3/s]
VAV WITH REHEAT 21.22 21.22 21.32 21.22 21.22 21.22 0.300000 1.00 21.22
FLR_3_DOAS 2.05 2.05 2.05 2.05 2.05 2.05 0.300000 1.00 2.05
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:OutdoorAir

Maximum Outdoor Air Flow Rate [m3/s] Minimum Outdoor Air Flow Rate [m3/s]
VAV WITH REHEAT_OA_CONTROLLER 21.22 21.21
FLR_3_DOAS_OA_CONTROLLER 2.05 2.05
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

HeatExchanger:AirToAir:SensibleAndLatent

Design Size Nominal Supply Air Flow Rate [m3/s]
VAV WITH REHEAT OA HEAT RECOVERY 21.21
FLR_3_DOAS OA HEAT RECOVERY 2.05
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:VariableVolume

Design Size Maximum Flow Rate [m3/s]
VAV WITH REHEAT FAN 21.22
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:WaterCoil

Maximum Actuated Flow [m3/s] Controller Convergence Tolerance
VAV WITH REHEAT_COOLC_CONTROLLER 0.040895 0.000012
VAV WITH REHEAT_HEATC_CONTROLLER 0.000538  
FLR_3_DOAS_COOLC_CONTROLLER 0.003869 0.000123
FLR_3_DOAS_HEATC_CONTROLLER 0.000052  
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:ConstantVolume

User-Specified Maximum Flow Rate [m3/s]
FLR_3_DOAS FAN 2.05
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:VariableSpeed

Design Flow Rate [m3/s] Design Power Consumption [W] Design Minimum Flow Rate [m3/s]
COOLSYS1 PUMP SECONDARY 0.053450 11014.04  
HEATSYS1 PUMP 0.002439 734.63 0.000000
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantLoop

Maximum Loop Flow Rate [m3/s] Plant Loop Volume [m3]
HEATSYS1 0.002439 0.292725
COOLSYS1 0.053450 6.41
SWHSYS1 0.000375 0.045004
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Boiler:HotWater

Design Size Nominal Capacity [W] User-Specified Nominal Capacity [W] Design Size Design Water Flow Rate [m3/s]
HEATSYS1 BOILER 278835.82 278835.82 0.002439
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:ConstantSpeed

Design Flow Rate [m3/s] Design Power Consumption [W]
COOLSYS1 PUMP 0.053450 7625.39
SWHSYS1 PUMP 0.000375 47.91
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Chiller:Electric:EIR

Design Size Reference Chilled Water Flow Rate [m3/s] Design Size Reference Capacity [W] User-Specified Reference Capacity [W] Design Size Reference Condenser Fluid Flow Rate [m3/s]
COOLSYS1 CHILLER1 0.053450 1496454.60 1497043.85 170.66
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

WaterHeater:Mixed

Use Side Design Flow Rate [m3/s]
SWHSYS1 WATER HEATER 0.000375
User-Specified values were used. Design Size values were used if no User-Specified values were provided.


Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2023-10-16 08:58:20

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

Possible Shadow Receivers
RETAIL_1_FLR_1_CEILING ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH |
CAFE_FLR_1_CEILING ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH |
LOBBY_FLR_1_CEILING_2 ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH |


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
RETAIL_1_FLR_1_WALL_SOUTH RETAIL_1_FLR_1_WALL_SOUTH_WINDOW |
RETAIL_2_FLR_1_WALL_WEST RETAIL_2_FLR_1_WALL_WEST_DOOR |
STORAGE_FLR_1_WALL_NORTH STORAGE_FLR_1_WALL_NORTH_ROLLDOOR |
LAUNDRY_FLR_1_WALL_EAST LAUNDRY_FLR_1_WALL_EAST_DOOR |
CAFE_FLR_1_WALL_EAST CAFE_FLR_1_WALL_EAST_DOOR |
CAFE_FLR_1_WALL_SOUTH CAFE_FLR_1_WALL_SOUTH_WINDOW |
LOBBY_FLR_1_WALL_1_NORTH LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 |
LOBBY_FLR_1_WALL_1_SOUTH LOBBY_FLR_1_WALL_SOUTH_WINDOW |
ROOM_1_FLR_3_WALL_SOUTH ROOM_1_FLR_3_WALL_SOUTH_WINDOW |
ROOM_1_FLR_3_WALL_WEST ROOM_1_FLR_3_WALL_WEST_WINDOW |
ROOM_2_FLR_3_WALL_NORTH ROOM_2_FLR_3_WALL_NORTH_WINDOW |
ROOM_2_FLR_3_WALL_WEST ROOM_2_FLR_3_WALL_WEST_WINDOW |
ROOM_3_MULT19_FLR_3_WALL_SOUTH ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW |
ROOM_4_MULT19_FLR_3_WALL_NORTH ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW |
ROOM_5_FLR_3_WALL_EAST ROOM_5_FLR_3_WALL_EAST_WINDOW |
ROOM_5_FLR_3_WALL_SOUTH ROOM_5_FLR_3_WALL_SOUTH_WINDOW |
ROOM_6_FLR_3_WALL_NORTH ROOM_6_FLR_3_WALL_NORTH_WINDOW |
ROOM_6_FLR_3_WALL_EAST ROOM_6_FLR_3_WALL_EAST_WINDOW |
CORRIDOR_FLR_3_WALL_1_NORTH CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW |
CORRIDOR_FLR_3_WALL_2_NORTH CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW |
CORRIDOR_FLR_3_WALL_1_SOUTH CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW |
CORRIDOR_FLR_3_WALL_2_SOUTH CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW |
ROOM_1_FLR_6_WALL_SOUTH ROOM_1_FLR_6_WALL_SOUTH_WINDOW |
ROOM_1_FLR_6_WALL_WEST ROOM_1_FLR_6_WALL_WEST_WINDOW |
ROOM_2_FLR_6_WALL_NORTH ROOM_2_FLR_6_WALL_NORTH_WINDOW |
ROOM_2_FLR_6_WALL_WEST ROOM_2_FLR_6_WALL_WEST_WINDOW |
ROOM_3_MULT9_FLR_6_WALL_SOUTH ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW |
BANQUET_FLR_6_WALL_NORTH BANQUET_FLR_6_WALL_NORTH_WINDOW |
DINING_FLR_6_WALL_NORTH DINING_FLR_6_WALL_NORTH_WINDOW |
KITCHEN_FLR_6_WALL_NORTH KITCHEN_FLR_6_WALL_NORTH_WINDOW |
KITCHEN_FLR_6_WALL_EAST KITCHEN_FLR_6_WALL_EAST_WINDOW |
KITCHEN_FLR_6_WALL_1_SOUTH KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW |
CORRIDOR_FLR_6_WALL_1_NORTH CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW |
CORRIDOR_FLR_6_WALL_2_NORTH CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW |
CORRIDOR_FLR_6_WALL_2_SOUTH CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2023-10-16 08:58:20

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: Initialization Summary

For: Entire Facility

Timestamp: 2023-10-16 08:58:20

Version

Version ID
1 22.1


Timesteps per Hour

#TimeSteps Minutes per TimeStep {minutes}
1 6 10


System Convergence Limits

Minimum System TimeStep {minutes} Max HVAC Iterations Minimum Plant Iterations Maximum Plant Iterations
1 1 20 2 8


Simulation Control

Do Zone Sizing Do System Sizing Do Plant Sizing Do Design Days Do Weather Simulation Do HVAC Sizing Simulation
1 Yes Yes Yes No Yes No


Performance Precision Tradeoffs

Use Coil Direct Simulation Zone Radiant Exchange Algorithm Override Mode Number of Timestep In Hour Force Euler Method Minimum Number of Warmup Days Force Suppress All Begin Environment Resets Minimum System Timestep MaxZoneTempDiff MaxAllowedDelTemp
1 No ScriptF Normal 6 No 1 No 1.0 0.300 2.0000E-003


Output Reporting Tolerances

Tolerance for Time Heating Setpoint Not Met Tolerance for Zone Cooling Setpoint Not Met Time
1 0.556 0.556


Site:GroundTemperature:BuildingSurface

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00


Site:GroundTemperature:FCfactorMethod

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 26.30 23.60 20.30 19.40 20.90 21.60 24.10 26.40 27.70 28.10 28.00 27.50


Site:GroundTemperature:Shallow

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00


Site:GroundTemperature:Deep

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00


Site:GroundReflectance

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:SnowModifier

Normal Daylighting {dimensionless}
1 1.000 1.000


Site:GroundReflectance:Snow

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:Snow:Daylighting

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Environment:Weather Station

Wind Sensor Height Above Ground {m} Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Sensor Height Above Ground {m} Wind Speed Modifier Coefficient-Internal Temperature Modifier Coefficient-Internal
1 10.000 0.140 270.000 1.500 1.586 9.750E-003


Site:Location

Location Name Latitude {N+/S- Deg} Longitude {E+/W- Deg} Time Zone Number {GMT+/-} Elevation {m} Standard Pressure at Elevation {Pa} Standard RhoAir at Elevation
1 Miami Intl Ap FL USA TMY3 WMO#=722020 25.82 -80.30 -5.00 11.00 101193 1.2027


Site Water Mains Temperature Information

Calculation Method{} Water Mains Temperature Schedule Name{} Annual Average Outdoor Air Temperature{C} Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} Fixed Default Water Mains Temperature{C}
1 Correlation NA 24.49 8.70 NA


Building Information

Building Name North Axis {deg} Terrain Loads Convergence Tolerance Value Temperature Convergence Tolerance Value Solar Distribution Maximum Number of Warmup Days Minimum Number of Warmup Days
1 HotelLarge 0.000 City 4.00000E-002 0.20000 FullInteriorAndExterior 25 6


Inside Convection Algorithm

Algorithm {Simple
TARP
CeilingDiffuser
AdaptiveConvectionAlgorithm}
1 TARP


Outside Convection Algorithm

Algorithm {SimpleCombined
TARP
MoWitt
DOE-2
AdaptiveConvectionAlgorithm}
1 DOE-2


Sky Radiance Distribution

Value {Anisotropic}
1 Anisotropic


Zone Air Solution Algorithm

Value {ThirdOrderBackwardDifference
AnalyticalSolution
EulerMethod}
1 ThirdOrderBackwardDifference


Zone Air Carbon Dioxide Balance Simulation

Simulation {Yes/No} Carbon Dioxide Concentration
1 No N/A


Zone Air Generic Contaminant Balance Simulation

Simulation {Yes/No} Generic Contaminant Concentration
1 No N/A


Zone Air Mass Flow Balance Simulation

Enforce Mass Balance



Adjust Zone Mixing and Return {AdjustMixingOnly
AdjustReturnOnly
AdjustMixingThenReturn
AdjustReturnThenMixing
None}
Adjust Zone Infiltration {AddInfiltration
AdjustInfiltration
None}

Infiltration Zones {MixingSourceZonesOnly
AllZones}


1 No N/A N/A N/A


HVACSystemRootFindingAlgorithm

Value {RegulaFalsi
Bisection
BisectionThenRegulaFalsi
RegulaFalsiThenBisection}
1 RegulaFalsi


Environment:Site Atmospheric Variation

Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Gradient Coefficient {K/m}
1 0.330 460.000 6.500000E-003


Surface Geometry

Starting Corner Vertex Input Direction Coordinate System Daylight Reference Point Coordinate System Rectangular (Simple) Surface Coordinate System
1 UpperLeftCorner Counterclockwise RelativeCoordinateSystem RelativeCoordinateSystem RelativeToZoneOrigin


Surface Heat Transfer Algorithm

Value {CTF - ConductionTransferFunction
EMPD - MoisturePenetrationDepthConductionTransferFunction
CondFD - ConductionFiniteDifference
HAMT - CombinedHeatAndMoistureFiniteElement} - Description
Inside Surface Max Temperature Limit{C}


Surface Convection Coefficient Lower Limit {W/m2-K}


Surface Convection Coefficient Upper Limit {W/m2-K}


1 CTF - ConductionTransferFunction 200 0.10 1000.0


Shading Summary

Number of Fixed Detached Shades Number of Building Detached Shades Number of Attached Shades
1 0 0 0


Zone Summary

Number of Zones Number of Zone Surfaces Number of SubSurfaces
1 22 235 36


Zone Information

Zone Name North Axis {deg} Origin X-Coordinate {m} Origin Y-Coordinate {m} Origin Z-Coordinate {m} Centroid X-Coordinate {m} Centroid Y-Coordinate {m} Centroid Z-Coordinate {m} Type Zone Multiplier Zone List Multiplier Minimum X {m} Maximum X {m} Minimum Y {m} Maximum Y {m} Minimum Z {m} Maximum Z {m} Ceiling Height {m} Volume {m3} Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} Floor Area {m2} Exterior Gross Wall Area {m2} Exterior Net Wall Area {m2} Exterior Window Area {m2} Number of Surfaces Number of SubSurfaces Number of Shading SubSurfaces Part of Total Building Area
1 BASEMENT 0.0 0.00 0.00 0.00 41.45 11.51 -1.22 1 1 1 0.00 86.56 0.00 22.86 -2.44 0.00 2.44 4826.41 TARP DOE-2 1978.83 0.00 0.00 0.00 13 0 0 Yes
2 RETAIL_1_FLR_1 0.0 0.00 0.00 0.00 5.79 2.90 1.98 1 1 1 0.00 11.58 0.00 5.79 0.00 3.96 3.96 265.76 TARP DOE-2 67.07 68.84 45.58 23.26 6 1 0 Yes
3 RETAIL_2_FLR_1 0.0 0.00 0.00 0.00 5.79 9.14 1.98 1 1 1 0.00 11.58 5.79 12.50 0.00 3.96 3.96 307.76 TARP DOE-2 77.67 26.57 24.62 0.00 6 1 0 Yes
4 MECH_FLR_1 0.0 0.00 0.00 0.00 61.87 17.68 1.98 1 1 1 53.95 69.80 12.50 22.86 0.00 3.96 3.96 650.80 TARP DOE-2 164.24 62.80 62.80 0.00 6 0 0 Yes
5 STORAGE_FLR_1 0.0 0.00 0.00 0.00 74.37 17.68 1.98 1 1 1 69.80 78.94 12.50 22.86 0.00 3.96 3.96 375.47 TARP DOE-2 94.76 36.23 28.80 0.00 6 1 0 Yes
6 LAUNDRY_FLR_1 0.0 0.00 0.00 0.00 84.28 14.33 1.98 1 1 1 81.99 86.56 5.79 22.86 0.00 3.96 3.96 309.22 TARP DOE-2 78.04 85.75 83.80 0.00 6 1 0 Yes
7 CAFE_FLR_1 0.0 0.00 0.00 0.00 70.26 2.90 1.98 1 1 1 53.95 86.56 0.00 5.79 0.00 3.96 3.96 748.35 TARP DOE-2 188.86 152.17 84.72 65.50 7 2 0 Yes
8 LOBBY_FLR_1 0.0 0.00 0.00 0.00 38.29 12.45 1.98 1 1 1 0.00 81.99 0.00 22.86 0.00 3.96 3.96 5183.56 TARP DOE-2 1308.19 434.79 345.80 85.08 18 3 0 Yes
9 ROOM_1_FLR_3 0.0 0.00 0.00 0.00 2.29 10.06 8.53 1 4 1 0.00 4.57 5.79 14.33 7.01 10.06 3.05 118.94 TARP DOE-2 39.02 39.95 26.77 13.18 6 2 0 Yes
10 ROOM_2_FLR_3 0.0 0.00 0.00 0.00 2.29 18.59 8.53 1 4 1 0.00 4.57 14.33 22.86 7.01 10.06 3.05 118.93 TARP DOE-2 39.02 39.95 26.76 13.18 6 2 0 Yes
11 ROOM_3_MULT19_FLR_3 0.0 0.00 0.00 0.00 8.53 9.14 8.53 1 76 1 6.71 10.36 5.79 12.50 7.01 10.06 3.05 74.75 TARP DOE-2 24.52 11.15 7.47 3.68 6 1 0 Yes
12 ROOM_4_MULT19_FLR_3 0.0 0.00 0.00 0.00 12.19 19.51 8.53 1 76 1 10.36 14.02 16.15 22.86 7.01 10.06 3.05 74.77 TARP DOE-2 24.53 11.15 7.47 3.68 6 1 0 Yes
13 ROOM_5_FLR_3 0.0 0.00 0.00 0.00 84.28 10.06 8.53 1 4 1 81.99 86.56 5.79 14.33 7.01 10.06 3.05 118.94 TARP DOE-2 39.02 39.95 26.77 13.18 6 2 0 Yes
14 ROOM_6_FLR_3 0.0 0.00 0.00 0.00 84.28 18.59 8.53 1 4 1 81.99 86.56 14.33 22.86 7.01 10.06 3.05 118.93 TARP DOE-2 39.02 39.95 26.76 13.18 6 2 0 Yes
15 CORRIDOR_FLR_3 0.0 0.00 0.00 0.00 43.28 14.33 8.53 1 4 1 4.57 81.99 5.79 22.86 7.01 10.06 3.05 1186.91 TARP DOE-2 389.40 48.31 32.37 15.94 20 4 0 Yes
16 ROOM_1_FLR_6 0.0 0.00 0.00 0.00 2.29 10.06 17.68 1 1 1 0.00 4.57 5.79 14.33 16.15 19.20 3.05 118.94 TARP DOE-2 39.02 39.95 26.77 13.18 6 2 0 Yes
17 ROOM_2_FLR_6 0.0 0.00 0.00 0.00 2.29 18.59 17.68 1 1 1 0.00 4.57 14.33 22.86 16.15 19.20 3.05 118.93 TARP DOE-2 39.02 39.95 26.76 13.18 6 2 0 Yes
18 ROOM_3_MULT9_FLR_6 0.0 0.00 0.00 0.00 7.93 7.62 17.68 1 9 1 4.57 11.28 5.79 9.45 16.15 19.20 3.05 74.77 TARP DOE-2 24.53 20.44 13.70 6.74 6 1 0 Yes
19 BANQUET_FLR_6 0.0 0.00 0.00 0.00 26.37 17.68 17.68 1 1 1 10.36 42.37 12.50 22.86 16.15 19.20 3.05 1010.89 TARP DOE-2 331.66 97.55 65.36 32.19 6 1 0 Yes
20 DINING_FLR_6 0.0 0.00 0.00 0.00 63.55 17.68 17.68 1 1 1 47.55 79.55 12.50 22.86 16.15 19.20 3.05 1010.89 TARP DOE-2 331.66 97.55 65.36 32.19 6 1 0 Yes
21 KITCHEN_FLR_6 0.0 0.00 0.00 0.00 82.99 14.11 17.68 1 1 1 79.55 86.56 5.79 22.86 16.15 19.20 3.05 314.87 TARP DOE-2 103.30 87.33 60.96 26.37 8 3 0 Yes
22 CORRIDOR_FLR_6 0.0 0.00 0.00 0.00 41.51 13.35 17.68 1 1 1 4.57 81.99 5.79 22.86 16.15 19.20 3.05 1256.16 TARP DOE-2 412.12 85.47 57.27 28.20 15 3 0 Yes


Zone Internal Gains Nominal

Zone Name Floor Area {m2} # Occupants Area per Occupant {m2/person} Occupant per Area {person/m2} Interior Lighting {W/m2} Electric Load {W/m2} Gas Load {W/m2} Other Load {W/m2} Hot Water Eq {W/m2} Steam Equipment {W/m2} Sum Loads per Area {W/m2} Outdoor Controlled Baseboard Heat
1 BASEMENT 1978.83 106.5 18.581 5.382E-002 8.749 5.380 0.000 0.000 0.000 0.000 14.129 No
2 RETAIL_1_FLR_1 67.07 10.8 6.194 0.161 13.012 10.760 0.000 0.000 0.000 0.000 23.772 No
3 RETAIL_2_FLR_1 77.67 12.5 6.194 0.161 13.012 10.760 0.000 0.000 0.000 0.000 23.772 No
4 MECH_FLR_1 164.24 2.7 61.932 1.615E-002 10.064 5.380 0.000 0.000 0.000 0.000 15.444 No
5 STORAGE_FLR_1 94.76 2.0 46.451 2.153E-002 7.319 2.690 0.000 0.000 0.000 0.000 10.009 No
6 LAUNDRY_FLR_1 78.04 8.4 9.290 0.108 5.490 61.680 535.850 0.000 0.000 0.000 603.020 No
7 CAFE_FLR_1 188.86 142.3 1.327 0.753 12.809 5.380 0.000 0.000 0.000 0.000 18.189 No
8 LOBBY_FLR_1 1308.19 422.4 3.097 0.323 10.064 8.070 0.000 0.000 0.000 0.000 18.134 No
9 ROOM_1_FLR_3 39.02 1.5 26.015 3.844E-002 10.064 6.750 0.000 0.000 0.000 0.000 16.814 No
10 ROOM_2_FLR_3 39.02 1.5 26.012 3.844E-002 10.064 6.750 0.000 0.000 0.000 0.000 16.814 No
11 ROOM_3_MULT19_FLR_3 24.52 1.5 16.349 6.116E-002 10.064 10.520 0.000 0.000 0.000 0.000 20.584 No
12 ROOM_4_MULT19_FLR_3 24.53 1.5 16.354 6.115E-002 10.064 10.520 0.000 0.000 0.000 0.000 20.584 No
13 ROOM_5_FLR_3 39.02 1.5 26.015 3.844E-002 10.064 6.750 0.000 0.000 0.000 0.000 16.814 No
14 ROOM_6_FLR_3 39.02 1.5 26.012 3.844E-002 10.064 6.750 0.000 0.000 0.000 0.000 16.814 No
15 CORRIDOR_FLR_3 389.40 21.0 18.581 5.382E-002 3.660 0.000 0.000 0.000 0.000 0.000 3.660 No
16 ROOM_1_FLR_6 39.02 1.5 26.015 3.844E-002 10.064 6.750 0.000 0.000 0.000 0.000 16.814 No
17 ROOM_2_FLR_6 39.02 1.5 26.012 3.844E-002 10.064 6.750 0.000 0.000 0.000 0.000 16.814 No
18 ROOM_3_MULT9_FLR_6 24.53 1.5 16.354 6.115E-002 10.064 10.520 0.000 0.000 0.000 0.000 20.584 No
19 BANQUET_FLR_6 331.66 249.9 1.327 0.753 12.809 67.820 0.000 0.000 0.000 0.000 80.629 No
20 DINING_FLR_6 331.66 249.9 1.327 0.753 12.809 67.820 0.000 0.000 0.000 0.000 80.629 No
21 KITCHEN_FLR_6 103.30 22.2 4.645 0.215 10.979 517.156 2419.260 0.000 0.000 0.000 2947.395 No
22 CORRIDOR_FLR_6 412.12 22.2 18.581 5.382E-002 3.660 0.000 0.000 0.000 0.000 0.000 3.660 No


People Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Number of People {} People/Floor Area {person/m2} Floor Area per person {m2/person} Fraction Radiant Fraction Convected Sensible Fraction Calculation Activity level ASHRAE 55 Warnings Carbon Dioxide Generation Rate Nominal Minimum Number of People Nominal Maximum Number of People MRT Calculation Type Work Efficiency Clothing Insulation Calculation Method Clothing Insulation Calculation Method Schedule Clothing Air Velocity Fanger Calculation Pierce Calculation KSU Calculation Cooling Effect Calculation Ankle Draft Calculation
1 BASEMENT PEOPLE BLDG_OCC_SCH BASEMENT 1978.83 106.5 106.5 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 106 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
2 RETAIL_1_FLR_1 PEOPLE BLDG_OCC_SCH RETAIL_1_FLR_1 67.07 10.8 10.8 0.161 6.194 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
3 RETAIL_2_FLR_1 PEOPLE BLDG_OCC_SCH RETAIL_2_FLR_1 77.67 12.5 12.5 0.161 6.194 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 13 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
4 LAUNDRY_FLR_1 PEOPLE BLDG_OCC_SCH LAUNDRY_FLR_1 78.04 8.4 8.4 0.108 9.290 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 8 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
5 CAFE_FLR_1 PEOPLE BLDG_OCC_SCH CAFE_FLR_1 188.86 142.3 142.3 0.753 1.327 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 142 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
6 LOBBY_FLR_1 PEOPLE BLDG_OCC_SCH LOBBY_FLR_1 1308.19 422.4 422.4 0.323 3.097 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 422 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
7 ROOM_1_FLR_3 PEOPLE GUESTROOM_OCC_SCH ROOM_1_FLR_3 39.02 1.5 1.5 3.844E-002 26.015 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
8 ROOM_2_FLR_3 PEOPLE GUESTROOM_OCC_SCH ROOM_2_FLR_3 39.02 1.5 1.5 3.844E-002 26.012 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
9 ROOM_3_MULT19_FLR_3 PEOPLE ALWAYS_OFF ROOM_3_MULT19_FLR_3 24.52 1.5 1.5 6.116E-002 16.349 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 0 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
10 ROOM_4_MULT19_FLR_3 PEOPLE GUESTROOM_OCC_SCH ROOM_4_MULT19_FLR_3 24.53 1.5 1.5 6.115E-002 16.354 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
11 ROOM_5_FLR_3 PEOPLE GUESTROOM_OCC_SCH ROOM_5_FLR_3 39.02 1.5 1.5 3.844E-002 26.015 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
12 ROOM_6_FLR_3 PEOPLE GUESTROOM_OCC_SCH ROOM_6_FLR_3 39.02 1.5 1.5 3.844E-002 26.012 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
13 ROOM_1_FLR_6 PEOPLE GUESTROOM_OCC_SCH ROOM_1_FLR_6 39.02 1.5 1.5 3.844E-002 26.015 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
14 ROOM_2_FLR_6 PEOPLE GUESTROOM_OCC_SCH ROOM_2_FLR_6 39.02 1.5 1.5 3.844E-002 26.012 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
15 ROOM_3_MULT9_FLR_6 PEOPLE GUESTROOM_OCC_SCH ROOM_3_MULT9_FLR_6 24.53 1.5 1.5 6.115E-002 16.354 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
16 BANQUET_FLR_6 PEOPLE BLDG_OCC_SCH BANQUET_FLR_6 331.66 249.9 249.9 0.753 1.327 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 250 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
17 DINING_FLR_6 PEOPLE BLDG_OCC_SCH DINING_FLR_6 331.66 249.9 249.9 0.753 1.327 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 250 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
18 KITCHEN_FLR_6 PEOPLE BLDG_OCC_SCH KITCHEN_FLR_6 103.30 22.2 22.2 0.215 4.645 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 22 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
19 STORAGE_FLR_1 PEOPLE BLDG_OCC_SCH STORAGE_FLR_1 94.76 2.0 2.0 2.153E-002 46.451 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
20 CORRIDOR_FLR_3 PEOPLE BLDG_OCC_SCH CORRIDOR_FLR_3 389.40 21.0 21.0 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 21 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
21 CORRIDOR_FLR_6 PEOPLE BLDG_OCC_SCH CORRIDOR_FLR_6 412.12 22.2 22.2 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 22 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
22 MECH_FLR_1 PEOPLE BLDG_OCC_SCH MECH_FLR_1 164.24 2.7 2.7 1.615E-002 61.932 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 3 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No


Lights Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Lighting Level {W} Lights/Floor Area {W/m2} Lights per person {W/person} Fraction Return Air Fraction Radiant Fraction Short Wave Fraction Convected Fraction Replaceable End-Use Category Nominal Minimum Lighting Level {W} Nominal Maximum Lighting Level {W}
1 BASEMENT_LIGHTS LTG_SCH_BASEMENT BASEMENT 1978.83 106.5 17313.725 8.749 162.572 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 17313.725
2 RETAIL_1_FLR_1_LIGHTS LTG_SCH_RETAIL RETAIL_1_FLR_1 67.07 10.8 872.757 13.012 80.594 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 872.757
3 RETAIL_2_FLR_1_LIGHTS LTG_SCH_RETAIL RETAIL_2_FLR_1 77.67 12.5 1010.656 13.012 80.595 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1010.656
4 MECH_FLR_1_LIGHTS LTG_SCH_MECHANIC MECH_FLR_1 164.24 2.7 1652.984 10.064 623.297 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1652.984
5 STORAGE_FLR_1_LIGHTS LTG_SCH_STORAGE STORAGE_FLR_1 94.76 2.0 693.586 7.319 339.993 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 693.586
6 LAUNDRY_FLR_1_LIGHTS LTG_SCH_LAUNDRY LAUNDRY_FLR_1 78.04 8.4 428.405 5.490 51.001 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 428.405
7 CAFE_FLR_1_LIGHTS LTG_SCH_DINING CAFE_FLR_1 188.86 142.3 2419.140 12.809 17.000 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2419.140
8 LOBBY_FLR_1_LIGHTS LTG_SCH_LOBBY LOBBY_FLR_1 1308.19 422.4 13165.908 10.064 31.167 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 13165.908
9 ROOM_1_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_1_FLR_3 39.02 1.5 392.727 10.064 261.818 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 392.727
10 ROOM_2_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_2_FLR_3 39.02 1.5 392.681 10.064 261.787 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 392.681
11 ROOM_3_MULT19_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_3_MULT19_FLR_3 24.52 1.5 246.814 10.064 164.543 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 246.814
12 ROOM_4_MULT19_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_4_MULT19_FLR_3 24.53 1.5 246.881 10.064 164.588 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 246.881
13 ROOM_5_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_5_FLR_3 39.02 1.5 392.727 10.064 261.818 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 392.727
14 ROOM_6_FLR_3_LIGHTS LTG_SCH_GUESTROOM ROOM_6_FLR_3 39.02 1.5 392.681 10.064 261.787 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 392.681
15 CORRIDOR_FLR_3_LIGHTS LTG_SCH_CORRIDOR CORRIDOR_FLR_3 389.40 21.0 1425.114 3.660 68.002 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1425.114
16 ROOM_1_FLR_6_LIGHTS LTG_SCH_GUESTROOM ROOM_1_FLR_6 39.02 1.5 392.727 10.064 261.818 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 392.727
17 ROOM_2_FLR_6_LIGHTS LTG_SCH_GUESTROOM ROOM_2_FLR_6 39.02 1.5 392.681 10.064 261.787 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 392.681
18 ROOM_3_MULT9_FLR_6_LIGHTS LTG_SCH_GUESTROOM ROOM_3_MULT9_FLR_6 24.53 1.5 246.881 10.064 164.588 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 246.881
19 BANQUET_FLR_6_LIGHTS LTG_SCH_DINING BANQUET_FLR_6 331.66 249.9 4248.214 12.809 17.000 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 4248.214
20 DINING_FLR_6_LIGHTS LTG_SCH_DINING DINING_FLR_6 331.66 249.9 4248.214 12.809 17.000 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 4248.214
21 KITCHEN_FLR_6_LIGHTS LTG_SCH_KITCHEN KITCHEN_FLR_6 103.30 22.2 1134.198 10.979 51.003 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1134.198
22 CORRIDOR_FLR_6_LIGHTS LTG_SCH_CORRIDOR CORRIDOR_FLR_6 412.12 22.2 1508.264 3.660 68.001 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1508.264


ElectricEquipment Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Equipment Level {W} Equipment/Floor Area {W/m2} Equipment per person {W/person} Fraction Latent Fraction Radiant Fraction Lost Fraction Convected End-Use SubCategory Nominal Minimum Equipment Level {W} Nominal Maximum Equipment Level {W}
1 BASEMENT_MISCPLUG_EQUIP BASEMENT_EQUIP_SCH BASEMENT 1978.83 106.5 10646.106 5.380 99.964 0.000 0.500 0.000 0.500 MiscPlug 0.000 10646.106
2 RETAIL_1_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH RETAIL_1_FLR_1 67.07 10.8 721.688 10.760 66.644 0.000 0.500 0.000 0.500 MiscPlug 0.000 721.688
3 RETAIL_2_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH RETAIL_2_FLR_1 77.67 12.5 835.717 10.760 66.644 0.000 0.500 0.000 0.500 MiscPlug 0.000 835.717
4 MECH_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH MECH_FLR_1 164.24 2.7 883.628 5.380 333.193 0.000 0.500 0.000 0.500 MiscPlug 0.000 883.628
5 STORAGE_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH STORAGE_FLR_1 94.76 2.0 254.902 2.690 124.952 0.000 0.500 0.000 0.500 MiscPlug 0.000 254.902
6 LAUNDRY_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH LAUNDRY_FLR_1 78.04 8.4 4813.474 61.680 573.033 0.000 0.500 0.000 0.500 MiscPlug 0.000 4813.474
7 CAFE_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH CAFE_FLR_1 188.86 142.3 1016.077 5.380 7.140 0.000 0.500 0.000 0.500 MiscPlug 0.000 1016.077
8 LOBBY_FLR_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH LOBBY_FLR_1 1308.19 422.4 10557.062 8.070 24.991 0.000 0.500 0.000 0.500 MiscPlug 0.000 10557.062
9 ROOM_1_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_BASE ROOM_1_FLR_3 39.02 1.5 263.399 6.750 175.599 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.399
10 ROOM_2_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_BASE ROOM_2_FLR_3 39.02 1.5 263.368 6.750 175.579 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.368
11 ROOM_3_MULT19_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_BASE ROOM_3_MULT19_FLR_3 24.52 1.5 257.991 10.520 171.994 0.000 0.500 0.000 0.500 MiscPlug 0.000 257.991
12 ROOM_4_MULT19_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_BASE ROOM_4_MULT19_FLR_3 24.53 1.5 258.061 10.520 172.041 0.000 0.500 0.000 0.500 MiscPlug 0.000 258.061
13 ROOM_5_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_BASE ROOM_5_FLR_3 39.02 1.5 263.399 6.750 175.599 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.399
14 ROOM_6_FLR_3_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_BASE ROOM_6_FLR_3 39.02 1.5 263.368 6.750 175.579 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.368
15 ROOM_1_FLR_6_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_BASE ROOM_1_FLR_6 39.02 1.5 263.399 6.750 175.599 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.399
16 ROOM_2_FLR_6_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_BASE ROOM_2_FLR_6 39.02 1.5 263.368 6.750 175.579 0.000 0.500 0.000 0.500 MiscPlug 0.000 263.368
17 ROOM_3_MULT9_FLR_6_PLUGMISC_EQUIP GUESTROOM_EQP_SCH_BASE ROOM_3_MULT9_FLR_6 24.53 1.5 258.061 10.520 172.041 0.000 0.500 0.000 0.500 MiscPlug 0.000 258.061
18 BANQUET_FLR_6_MISCPLUG_EQUIP KITCHEN_ELEC_EQUIP_SCH BANQUET_FLR_6 331.66 249.9 22493.008 67.820 90.009 0.000 0.500 0.000 0.500 Cooking 0.000 6747.903
19 DINING_FLR_6_MISCPLUG_EQUIP KITCHEN_ELEC_EQUIP_SCH DINING_FLR_6 331.66 249.9 22493.008 67.820 90.009 0.000 0.500 0.000 0.500 Cooking 0.000 6747.903
20 KITCHEN_FLR_6_MISCELEC_EQUIP KITCHEN_ELEC_EQUIP_SCH KITCHEN_FLR_6 103.30 22.2 52482.799 508.040 2360.050 0.200 0.500 0.100 0.200 Cooking 0.000 15744.840
21 KITCHEN_FLR_6_REACH-IN-FREEZER ALWAYS_ON KITCHEN_FLR_6 103.30 22.2 515.917 4.994 23.200 0.000 0.250 0.000 0.750 ReachInFreezer 515.917 515.917
22 KITCHEN_FLR_6_REACH-IN-REFRIGERATOR ALWAYS_ON KITCHEN_FLR_6 103.30 22.2 425.833 4.122 19.149 0.000 0.250 0.000 0.750 ReachInRefrigerator 425.833 425.833


GasEquipment Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Equipment Level {W} Equipment/Floor Area {W/m2} Equipment per person {W/person} Fraction Latent Fraction Radiant Fraction Lost Fraction Convected End-Use SubCategory Nominal Minimum Equipment Level {W} Nominal Maximum Equipment Level {W}
1 LAUNDRY_FLR_1_MISCGAS_EQUIP BLDG_EQUIP_SCH LAUNDRY_FLR_1 78.04 8.4 41817.449 535.850 4978.268 0.000 0.500 0.000 0.500 Laundry 0.000 41817.449
2 KITCHEN_FLR_6_MISCGAS_EQUIP KITCHEN_GAS_EQUIP_SCH KITCHEN_FLR_6 103.30 22.2 249920.353 2419.260 11238.437 0.100 0.200 0.700 0.000 Cooking 0.000 74976.106


Construction CTF

Construction Name Index #Layers #CTFs Time Step {hours} ThermalConductance {w/m2-K} OuterThermalAbsorptance InnerThermalAbsorptance OuterSolarAbsorptance InnerSolarAbsorptance Roughness
1 SWINGING DOOR_CON 1 1 1 0.167 3.464 0.900 0.900 0.700 0.700 MediumRough
2 OVERHEAD DOOR_CON 2 1 1 0.167 1.198 0.900 0.900 0.700 0.700 MediumRough
3 INTERIORFURNISHINGS 3 1 9 0.167 0.8000 0.900 0.900 0.700 0.700 MediumSmooth
4 INT_WALL 8 2 4 0.167 6.299 0.900 0.900 0.700 0.700 Smooth
5 NONRES_ROOF 18 3 3 0.167 0.2832 0.750 0.900 0.450 0.700 Rough
6 RES_ROOF 19 3 3 0.167 0.2832 0.750 0.900 0.450 0.700 Rough
7 NONRES_EXT_WALL_GRD 21 3 9 0.167 1.214 0.900 0.900 0.700 0.700 MediumRough
8 NONRES_EXT_WALL_MID 22 3 9 0.167 1.530 0.900 0.900 0.700 0.700 MediumRough
9 NONRES_EXT_WALL_TOP 23 3 9 0.167 1.605 0.900 0.900 0.700 0.700 MediumRough
10 RES_EXT_WALL_MID 25 3 9 0.167 1.530 0.900 0.900 0.700 0.700 MediumRough
11 RES_EXT_WALL_TOP 26 3 9 0.167 1.605 0.900 0.900 0.700 0.700 MediumRough
12 NONRES_FLOOR 30 3 7 0.167 0.4124 0.900 0.900 0.700 0.700 MediumSmooth
13 NONRES_FLOOR_CEILING 33 3 7 0.167 0.4124 0.900 0.900 0.700 0.700 VeryRough
14 BASEMENT_FLOOR 36 2 7 0.333 2.705 0.900 0.900 0.700 0.700 MediumRough
15 BASEMENT_WALL_NORTH_CFACTOR 39 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough
16 BASEMENT_WALL_EAST_CFACTOR 40 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough
17 BASEMENT_WALL_SOUTH_CFACTOR 41 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough
18 BASEMENT_WALL_WEST_CFACTOR 42 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough


Material CTF Summary

Material Name Thickness {m} Conductivity {w/m-K} Density {kg/m3} Specific Heat {J/kg-K} ThermalResistance {m2-K/w}
1 OPAQUE DOOR PANEL_CON 0.0000 0.000 0.000 0.000 0.2887
2 OVERHEAD DOOR_CON PANEL 0.0000 0.000 0.000 0.000 0.8346
3 STD WOOD 6INCH 0.1500 0.120 540.000 1210.000 1.250
4 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
5 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
6 F13 BUILT-UP ROOFING 0.0095 0.160 1120.000 1460.000 0.5938E-01
7 NONRES_ROOF_INSULATION 0.0000 0.000 0.000 0.000 3.472
8 F08 METAL SURFACE 0.0008 45.280 7824.000 500.000 0.1767E-04
9 F13 BUILT-UP ROOFING 0.0095 0.160 1120.000 1460.000 0.5938E-01
10 RES_ROOF_INSULATION 0.0000 0.000 0.000 0.000 3.472
11 F08 METAL SURFACE 0.0008 45.280 7824.000 500.000 0.1767E-04
12 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
13 NONRES_EXTERIOR_WALL_INSULATION_GRD 0.0000 0.000 0.000 0.000 0.6561
14 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
15 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
16 NONRES_EXTERIOR_WALL_INSULATION_MID 0.0000 0.000 0.000 0.000 0.4862
17 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
18 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
19 NONRES_EXTERIOR_WALL_INSULATION_TOP 0.0000 0.000 0.000 0.000 0.4557
20 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
21 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
22 RES_EXTERIOR_WALL_INSULATION_MID 0.0000 0.000 0.000 0.000 0.4862
23 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
24 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
25 RES_EXTERIOR_WALL_INSULATION_TOP 0.0000 0.000 0.000 0.000 0.4557
26 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
27 NONRES_FLOOR_INSULATION 0.0000 0.000 0.000 0.000 2.165
28 100MM NORMALWEIGHT CONCRETE FLOOR 0.1016 2.310 2322.000 832.000 0.4398E-01
29 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
30 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
31 100MM NORMALWEIGHT CONCRETE FLOOR 0.1016 2.310 2322.000 832.000 0.4398E-01
32 NONRES_FLOOR_INSULATION 0.0000 0.000 0.000 0.000 2.165
33 M10 200MM CONCRETE BLOCK BASEMENT WALL 0.2032 1.326 1842.000 912.000 0.1532
34 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
35 ~FC_Insulation_1 0.0000 0.000 0.000 0.000 0.9868
36 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
37 ~FC_Insulation_2 0.0000 0.000 0.000 0.000 0.9868
38 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
39 ~FC_Insulation_3 0.0000 0.000 0.000 0.000 0.9868
40 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
41 ~FC_Insulation_4 0.0000 0.000 0.000 0.000 0.9868
42 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01


CTF

Time Outside Cross Inside Flux (except final one)
1 1 0.0000000 0.0000000 -0.0000000 -0.0000000
2 0 3.4637404 3.4637404 3.4637404  
3 1 0.0000000 0.0000000 -0.0000000 -0.0000000
4 0 1.1981135 1.1981135 1.1981135  
5 9 -0.27580628E-02 0.97439125E-12 -0.27580628E-02 0.28516790E-03
6 8 0.73590997E-01 0.21837543E-08 0.73590997E-01 -0.77836043E-02
7 7 -0.82599318 0.23162835E-06 -0.82599318 0.89703933E-01
8 6 5.1113916 0.48671053E-05 5.1113916 -0.57224845
9 5 -19.214933 0.30163627E-04 -19.214933 2.2266322
10 4 45.557404 0.63181060E-04 45.557404 -5.4853312
11 3 -68.275533 0.44785456E-04 -68.275533 8.5710568
12 2 62.555368 0.93952058E-05 62.555368 -8.2111738
13 1 -31.904423 0.39200004E-06 -31.904423 4.3886678
14 0 6.9260389 0.77047546E-09 6.9260389  
15 4 0.68458728E-09 0.26079551E-09 0.68458728E-09 -0.34507121E-18
16 3 -0.72180374E-03 0.24295686E-03 -0.72180374E-03 0.69691454E-09
17 2 0.83054762 0.27682775 0.83054762 -0.35168967E-03
18 1 -12.650482 3.3590720 -12.650482 0.19281313
19 0 16.907513 1.4507143 16.907513  
20 3 -0.61927053E-06 0.12767249E-08 -0.37968499E-05 0.16832131E-17
21 2 0.77611055 0.17315568E-02 1.0534842 -0.72792597E-06
22 1 -21.915918 0.11588205 -6.3286394 0.20197014
23 0 21.365777 0.10835518 5.5011278  
24 3 -0.61927053E-06 0.12767249E-08 -0.37968499E-05 0.16832131E-17
25 2 0.77611055 0.17315568E-02 1.0534842 -0.72792597E-06
26 1 -21.915918 0.11588205 -6.3286394 0.20197014
27 0 21.365777 0.10835518 5.5011278  
28 9 0.16334608E-14 0.44521285E-16 -0.13626018E-09 -0.55408550E-17
29 8 0.19978482E-07 0.16087698E-12 0.35757339E-03 -0.22716220E-09
30 7 -0.11637212E-01 0.85329953E-08 -0.22215339E-01 0.13231934E-03
31 6 0.38892783 0.29989280E-05 0.45807963 -0.45541807E-02
32 5 -5.0302817 0.11296145E-03 -4.3335362 0.61196441E-01
33 4 32.293780 0.93138689E-03 21.019023 -0.41270848
34 3 -109.71729 0.20442050E-02 -54.790969 1.4933949
35 2 195.63536 0.11570803E-02 77.111252 -2.8769641
36 1 -170.61189 0.12423857E-03 -55.033492 2.7359019
37 0 57.057407 0.71170334E-06 15.595873  
38 9 0.10594392E-14 0.47202510E-16 -0.12114953E-09 -0.13223917E-17
39 8 0.17843092E-07 0.19779160E-12 0.33399960E-03 -0.20288210E-09
40 7 -0.10929829E-01 0.10778020E-07 -0.21195485E-01 0.12427612E-03
41 6 0.36970129 0.38290923E-05 0.44160549 -0.43275484E-02
42 5 -4.8425837 0.14557296E-03 -4.2065674 0.58869135E-01
43 4 31.463113 0.12102446E-02 20.521745 -0.40168017
44 3 -107.94871 0.26756904E-02 -53.807411 1.4678460
45 2 193.88106 0.15243179E-02 76.211002 -2.8491083
46 1 -169.96333 0.16464538E-03 -54.775095 2.7245352
47 0 57.057407 0.94931294E-06 15.641308  
48 9 0.90003388E-15 0.50867187E-16 -0.11754631E-09 -0.30069304E-17
49 8 0.17333232E-07 0.20603527E-12 0.32823068E-03 -0.19708482E-09
50 7 -0.10756240E-01 0.11305735E-07 -0.20945040E-01 0.12230235E-03
51 6 0.36498247 0.40277709E-05 0.43754979 -0.42719257E-02
52 5 -4.7965079 0.15349109E-03 -4.1752560 0.58297839E-01
53 4 31.259149 0.12787761E-02 20.398993 -0.39897233
54 3 -107.51430 0.28324589E-02 -53.564574 1.4615707
55 2 193.44998 0.16162686E-02 75.988960 -2.8422636
56 1 -169.80390 0.17483991E-03 -54.711782 2.7217408
57 0 57.057407 0.10098010E-05 15.652787  
58 9 0.10594392E-14 0.47202510E-16 -0.12114953E-09 -0.13223917E-17
59 8 0.17843092E-07 0.19779160E-12 0.33399960E-03 -0.20288210E-09
60 7 -0.10929829E-01 0.10778020E-07 -0.21195485E-01 0.12427612E-03
61 6 0.36970129 0.38290923E-05 0.44160549 -0.43275484E-02
62 5 -4.8425837 0.14557296E-03 -4.2065674 0.58869135E-01
63 4 31.463113 0.12102446E-02 20.521745 -0.40168017
64 3 -107.94871 0.26756904E-02 -53.807411 1.4678460
65 2 193.88106 0.15243179E-02 76.211002 -2.8491083
66 1 -169.96333 0.16464538E-03 -54.775095 2.7245352
67 0 57.057407 0.94931294E-06 15.641308  
68 9 0.90003388E-15 0.50867187E-16 -0.11754631E-09 -0.30069304E-17
69 8 0.17333232E-07 0.20603527E-12 0.32823068E-03 -0.19708482E-09
70 7 -0.10756240E-01 0.11305735E-07 -0.20945040E-01 0.12230235E-03
71 6 0.36498247 0.40277709E-05 0.43754979 -0.42719257E-02
72 5 -4.7965079 0.15349109E-03 -4.1752560 0.58297839E-01
73 4 31.259149 0.12787761E-02 20.398993 -0.39897233
74 3 -107.51430 0.28324589E-02 -53.564574 1.4615707
75 2 193.44998 0.16162686E-02 75.988960 -2.8422636
76 1 -169.80390 0.17483991E-03 -54.711782 2.7217408
77 0 57.057407 0.10098010E-05 15.652787  
78 7 -0.10696287E-14 0.39031946E-16 -0.22096194E-13 0.53014468E-15
79 6 0.18597363E-10 0.52355087E-11 0.51921923E-09 -0.18483703E-10
80 5 -0.10208356E-06 0.25520809E-07 -0.21786771E-05 0.17041956E-06
81 4 0.13587196E-03 0.96408156E-05 0.17589348E-02 -0.28090751E-03
82 3 -0.20124247E-01 0.34048350E-03 -0.21477792 0.43172268E-01
83 2 0.28586126 0.14813331E-02 2.8938873 -0.61762740
84 1 -0.72340799 0.92453067E-03 -7.1302655 1.5680075
85 0 0.46030979 0.18706506E-04 4.4521723  
86 7 -0.22096194E-13 0.39031946E-16 -0.10696287E-14 0.53014468E-15
87 6 0.51921923E-09 0.52355087E-11 0.18597363E-10 -0.18483703E-10
88 5 -0.21786771E-05 0.25520809E-07 -0.10208356E-06 0.17041956E-06
89 4 0.17589348E-02 0.96408156E-05 0.13587196E-03 -0.28090751E-03
90 3 -0.21477792 0.34048350E-03 -0.20124247E-01 0.43172268E-01
91 2 2.8938873 0.14813331E-02 0.28586126 -0.61762740
92 1 -7.1302655 0.92453067E-03 -0.72340799 1.5680075
93 0 4.4521723 0.18706506E-04 0.46030979  
94 7 -0.52459208E-15 -0.63961428E-15 -0.12292524E-09 -0.35846135E-17
95 6 0.39860198E-02 0.96339020E-07 0.40499006E-03 -0.70890431E-04
96 5 -0.20832379 0.49172556E-04 -0.20585669E-01 0.38489246E-02
97 4 3.5198270 0.18993977E-02 0.34924834 -0.69168259E-01
98 3 -23.366787 0.13311857E-01 -2.4329538 0.50524779
99 2 64.890127 0.19943872E-01 7.3672511 -1.5911358
100 1 -76.040094 0.56792084E-02 -9.5568013 2.1361271
101 0 31.242244 0.96490710E-04 4.3344156  
102 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
103 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
104 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
105 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
106 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
107 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
108 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
109 0 1.0055995 0.48413807E-04 60.838472  
110 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
111 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
112 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
113 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
114 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
115 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
116 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
117 0 1.0055995 0.48413807E-04 60.838472  
118 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
119 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
120 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
121 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
122 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
123 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
124 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
125 0 1.0055995 0.48413807E-04 60.838472  
126 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
127 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
128 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
129 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
130 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
131 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
132 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
133 0 1.0055995 0.48413807E-04 60.838472  


WindowConstruction

Construction Name Index #Layers Roughness Conductance {W/m2-K} Conductance (Before Adjusted) {W/m2-K} Convection Coefficient Adjustment Ratio SHGC Solar Transmittance at Normal Incidence Visible Transmittance at Normal Incidence
1 NONRESWINDOW_U_0.5119_SHGC_0.25 37 1 VerySmooth 2.910 2.910 1.000 0.251    
2 RESWINDOW_U_0.5119_SHGC_0.25 38 1 VerySmooth 2.910 2.910 1.000 0.251    


WindowMaterial:Glazing

Material Name Optical Data Type Spectral Data Set Name Thickness {m} Solar Transmittance Front Solar Reflectance Back Solar Reflectance Visible Transmittance Front Visible Reflectance Back Visible Reflectance Infrared Transmittance Front Thermal Emissivity Back Thermal Emissivity Conductivity {W/m-K} Dirt Factor Solar Diffusing
1 GLAZING LAYER SpectralAverage   1.79780E-002 0.16139 0.60964 0.60964 0.25000 0.16143 0.23877 0.00000 0.84000 0.84000 0.10364 1.00000 No
2 RESIDENTIAL WINDOW GLAZING LAYER SpectralAverage   1.79780E-002 0.16139 0.60964 0.60964 0.25000 0.16143 0.23877 0.00000 0.84000 0.84000 0.10364 1.00000 No


Shadowing/Sun Position Calculations Annual Simulations

Shading Calculation Method Shading Calculation Update Frequency Method Shading Calculation Update Frequency {days} Maximum Figures in Shadow Overlap Calculations {} Polygon Clipping Algorithm Pixel Counting Resolution Sky Diffuse Modeling Algorithm Output External Shading Calculation Results Disable Self-Shading Within Shading Zone Groups Disable Self-Shading From Shading Zone Groups to Other Zones
1 PolygonClipping Periodic 7 15000 SutherlandHodgman 512 SimpleSkyDiffuseModeling No No No


#Refrigeration Compressor Racks

Number of Refrigeration Compressor Racks
1 2


Refrigeration Compressor Rack

Compressor Rack Name # Refrigerated Cases Connected # WalkIn Coolers Connected Heat Rejection Location Condenser Type COP
1 RACK1 1 0 Zone Air-Cooled 1.500
2 RACK2 1 0 Zone Air-Cooled 3.000


Water Heater Information

Type Name Volume {m3} Maximum Capacity {W} Standard Rated Recovery Efficiency Standard Rated Energy Factor
1 WaterHeater:Mixed SWH BOOSTER E WATER HEATER 2.2712E-002 8000.0 1.240 1.1473
2 WaterHeater:Mixed SWH LAUNDRY G WATER HEATER 1.1356 163316.0 0.576 0.5074
3 WaterHeater:Mixed SWHSYS1 WATER HEATER 2.2712 175842.6 0.260 2.5713E-002


Surface Convection Parameters

Surface Name Outside Model Assignment Outside Area [m2] Outside Perimeter [m] Outside Height [m] Inside Model Assignment Inside Height [m] Inside Perimeter Envelope [m] Inside Hydraulic Diameter [m] Window Wall Ratio Window Location Near Radiant {Yes/No} Has Active HVAC {Yes/No}
1 BASEMENT_WALL_NORTH 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
2 BASEMENT_WALL_EAST 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
3 BASEMENT_WALL_SOUTH 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
4 BASEMENT_WALL_WEST 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
5 BASEMENT_FLOOR 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
6 BASEMENT_CEILING_1 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
7 BASEMENT_CEILING_2 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
8 BASEMENT_CEILING_3 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
9 BASEMENT_CEILING_4 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
10 BASEMENT_CEILING_5 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
11 BASEMENT_CEILING_6 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
12 BASEMENT_CEILING_7 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
13 BASEMENT_CEILING_8 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
14 BASEMENT_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.44 0.00 36.17 -999.00 0 No No
15 RETAIL_1_FLR_1_WALL_SOUTH 0 506.51 211.91 19.20 0 3.96 17.37 7.72 0.34 4 No No
16 RETAIL_1_FLR_1_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.96 17.37 7.72 0.34 1 No No
17 RETAIL_1_FLR_1_WALL_WEST 0 194.63 84.12 19.20 0 3.96 17.37 7.72 0.34 3 No No
18 RETAIL_1_FLR_1_WALL_NORTH 0 0.00 0.00 0.00 0 3.96 17.37 7.72 0.34 0 No No
19 RETAIL_1_FLR_1_WALL_EAST 0 0.00 0.00 0.00 0 3.96 17.37 7.72 0.34 0 No No
20 RETAIL_1_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 17.37 7.72 0.34 0 No No
21 RETAIL_1_FLR_1_CEILING 0 1782.60 293.11 15.24 0 3.96 17.37 7.72 0.34 0 No No
22 RETAIL_1_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 17.37 7.72 0.34 0 No No
23 RETAIL_2_FLR_1_WALL_WEST 0 194.63 84.12 19.20 0 3.96 6.71 8.49 0.00 0 No No
24 RETAIL_2_FLR_1_WALL_WEST_DOOR 0 194.63 84.12 19.20 0 3.96 6.71 8.49 0.00 0 No No
25 RETAIL_2_FLR_1_WALL_SOUTH 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
26 RETAIL_2_FLR_1_WALL_NORTH 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
27 RETAIL_2_FLR_1_WALL_EAST 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
28 RETAIL_2_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
29 RETAIL_2_FLR_1_CEILING 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
30 RETAIL_2_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 6.71 8.49 0.00 0 No No
31 MECH_FLR_1_WALL_NORTH 0 670.01 217.46 19.20 0 3.96 15.85 12.53 0.00 0 No No
32 MECH_FLR_1_WALL_EAST 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
33 MECH_FLR_1_WALL_SOUTH 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
34 MECH_FLR_1_WALL_WEST 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
35 MECH_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
36 MECH_FLR_1_CEILING 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
37 MECH_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 15.85 12.53 0.00 0 No No
38 STORAGE_FLR_1_WALL_NORTH 0 670.01 217.46 19.20 0 3.96 9.14 9.72 0.00 0 No No
39 STORAGE_FLR_1_WALL_NORTH_ROLLDOOR 0 670.01 217.46 19.20 0 3.96 9.14 9.72 0.00 0 No No
40 STORAGE_FLR_1_WALL_EAST 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
41 STORAGE_FLR_1_WALL_SOUTH 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
42 STORAGE_FLR_1_WALL_WEST 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
43 STORAGE_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
44 STORAGE_FLR_1_CEILING 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
45 STORAGE_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 9.14 9.72 0.00 0 No No
46 LAUNDRY_FLR_1_WALL_NORTH 0 670.01 217.46 19.20 0 3.96 21.64 7.21 0.00 0 No No
47 LAUNDRY_FLR_1_WALL_EAST 0 194.63 217.46 19.20 0 3.96 21.64 7.21 0.00 0 No No
48 LAUNDRY_FLR_1_WALL_EAST_DOOR 0 194.63 217.46 19.20 0 3.96 21.64 7.21 0.00 0 No No
49 LAUNDRY_FLR_1_WALL_SOUTH 0 0.00 0.00 0.00 0 3.96 21.64 7.21 0.00 0 No No
50 LAUNDRY_FLR_1_WALL_WEST 0 0.00 0.00 0.00 0 3.96 21.64 7.21 0.00 0 No No
51 LAUNDRY_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 21.64 7.21 0.00 0 No No
52 LAUNDRY_FLR_1_CEILING 0 0.00 0.00 0.00 0 3.96 21.64 7.21 0.00 0 No No
53 LAUNDRY_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 21.64 7.21 0.00 0 No No
54 CAFE_FLR_1_WALL_EAST 0 194.63 217.46 19.20 0 3.96 38.40 9.84 0.43 3 No No
55 CAFE_FLR_1_WALL_EAST_DOOR 0 194.63 217.46 19.20 0 3.96 38.40 9.84 0.43 0 No No
56 CAFE_FLR_1_WALL_SOUTH 0 506.51 211.91 19.20 0 3.96 38.40 9.84 0.43 4 No No
57 CAFE_FLR_1_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.96 38.40 9.84 0.43 1 No No
58 CAFE_FLR_1_WALL_1_NORTH 0 0.00 0.00 0.00 0 3.96 38.40 9.84 0.43 0 No No
59 CAFE_FLR_1_WALL_2_NORTH 0 0.00 0.00 0.00 0 3.96 38.40 9.84 0.43 0 No No
60 CAFE_FLR_1_WALL_WEST 0 0.00 0.00 0.00 0 3.96 38.40 9.84 0.43 0 No No
61 CAFE_FLR_1_FLOOR 0 0.00 0.00 0.00 0 3.96 38.40 9.84 0.43 0 No No
62 CAFE_FLR_1_CEILING 0 1782.60 293.11 15.24 0 3.96 38.40 9.84 0.43 0 No No
63 CAFE_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 38.40 9.84 0.43 0 No No
64 LOBBY_FLR_1_WALL_1_NORTH 0 670.01 217.46 19.20 0 3.96 109.73 24.95 0.20 3 No No
65 LOBBY_FLR_1_WALL_1_NORTH_DOOR1 0 670.01 217.46 19.20 0 3.96 109.73 24.95 0.20 0 No No
66 LOBBY_FLR_1_WALL_1_NORTH_DOOR2 0 670.01 217.46 19.20 0 3.96 109.73 24.95 0.20 0 No No
67 LOBBY_FLR_1_WALL_2_NORTH 0 670.01 217.46 19.20 0 3.96 109.73 24.95 0.20 4 No No
68 LOBBY_FLR_1_WALL_1_SOUTH 0 506.51 211.91 19.20 0 3.96 109.73 24.95 0.20 4 No No
69 LOBBY_FLR_1_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.96 109.73 24.95 0.20 1 No No
70 LOBBY_FLR_1_WALL_1_WEST 0 194.63 84.12 19.20 0 3.96 109.73 24.95 0.20 3 No No
71 LOBBY_FLR_1_WALL_2_SOUTH 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
72 LOBBY_FLR_1_WALL_3_SOUTH 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
73 LOBBY_FLR_1_WALL_2_WEST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
74 LOBBY_FLR_1_WALL_3_WEST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
75 LOBBY_FLR_1_WALL_4_WEST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
76 LOBBY_FLR_1_WALL_3_NORTH 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
77 LOBBY_FLR_1_WALL_4_NORTH 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
78 LOBBY_FLR_1_WALL_1_EAST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
79 LOBBY_FLR_1_WALL_2_EAST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
80 LOBBY_FLR_1_WALL_3_EAST 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
81 LOBBY_FLR_1_FLOOR_1 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
82 LOBBY_FLR_1_FLOOR_2 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
83 LOBBY_FLR_1_CEILING_1 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
84 LOBBY_FLR_1_CEILING_2 0 1782.60 293.11 15.24 0 3.96 109.73 24.95 0.20 0 No No
85 LOBBY_FLR_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.96 109.73 24.95 0.20 0 No No
86 ROOM_1_FLR_3_WALL_SOUTH 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 3 No No
87 ROOM_1_FLR_3_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 2 No No
88 ROOM_1_FLR_3_WALL_WEST 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 3 No No
89 ROOM_1_FLR_3_WALL_WEST_WINDOW 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 2 No No
90 ROOM_1_FLR_3_WALL_NORTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
91 ROOM_1_FLR_3_WALL_EAST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
92 ROOM_1_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
93 ROOM_1_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
94 ROOM_1_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
95 ROOM_2_FLR_3_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 3 No No
96 ROOM_2_FLR_3_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 2 No No
97 ROOM_2_FLR_3_WALL_WEST 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 3 No No
98 ROOM_2_FLR_3_WALL_WEST_WINDOW 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 2 No No
99 ROOM_2_FLR_3_WALL_EAST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
100 ROOM_2_FLR_3_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
101 ROOM_2_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
102 ROOM_2_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
103 ROOM_2_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
104 ROOM_3_MULT19_FLR_3_WALL_SOUTH 0 506.51 211.91 19.20 0 3.05 3.66 4.73 0.33 3 No No
105 ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 3.66 4.73 0.33 2 No No
106 ROOM_3_MULT19_FLR_3_WALL_NORTH 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
107 ROOM_3_MULT19_FLR_3_WALL_EAST 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
108 ROOM_3_MULT19_FLR_3_WALL_WEST 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
109 ROOM_3_MULT19_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
110 ROOM_3_MULT19_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
111 ROOM_3_MULT19_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
112 ROOM_4_MULT19_FLR_3_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 3.66 4.73 0.33 3 No No
113 ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 3.66 4.73 0.33 2 No No
114 ROOM_4_MULT19_FLR_3_WALL_EAST 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
115 ROOM_4_MULT19_FLR_3_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
116 ROOM_4_MULT19_FLR_3_WALL_WEST 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
117 ROOM_4_MULT19_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
118 ROOM_4_MULT19_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
119 ROOM_4_MULT19_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 3.66 4.73 0.33 0 No No
120 ROOM_5_FLR_3_WALL_EAST 0 194.63 217.46 19.20 0 3.05 13.11 5.95 0.33 3 No No
121 ROOM_5_FLR_3_WALL_EAST_WINDOW 0 194.63 217.46 19.20 0 3.05 13.11 5.95 0.33 2 No No
122 ROOM_5_FLR_3_WALL_SOUTH 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 3 No No
123 ROOM_5_FLR_3_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 2 No No
124 ROOM_5_FLR_3_WALL_NORTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
125 ROOM_5_FLR_3_WALL_WEST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
126 ROOM_5_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
127 ROOM_5_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
128 ROOM_5_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
129 ROOM_6_FLR_3_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 3 No No
130 ROOM_6_FLR_3_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 2 No No
131 ROOM_6_FLR_3_WALL_EAST 0 194.63 217.46 19.20 0 3.05 13.11 5.95 0.33 3 No No
132 ROOM_6_FLR_3_WALL_EAST_WINDOW 0 194.63 217.46 19.20 0 3.05 13.11 5.95 0.33 2 No No
133 ROOM_6_FLR_3_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
134 ROOM_6_FLR_3_WALL_WEST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
135 ROOM_6_FLR_3_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
136 ROOM_6_FLR_3_CEILING 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
137 ROOM_6_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
138 CORRIDOR_FLR_3_WALL_1_NORTH 0 670.01 217.46 19.20 0 3.05 15.85 8.24 0.33 3 No No
139 CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 15.85 8.24 0.33 2 No No
140 CORRIDOR_FLR_3_WALL_2_NORTH 0 670.01 217.46 19.20 0 3.05 15.85 8.24 0.33 3 No No
141 CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 15.85 8.24 0.33 2 No No
142 CORRIDOR_FLR_3_WALL_1_SOUTH 0 506.51 211.91 19.20 0 3.05 15.85 8.24 0.33 3 No No
143 CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 15.85 8.24 0.33 2 No No
144 CORRIDOR_FLR_3_WALL_2_SOUTH 0 506.51 211.91 19.20 0 3.05 15.85 8.24 0.33 3 No No
145 CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 15.85 8.24 0.33 2 No No
146 CORRIDOR_FLR_3_WALL_3_NORTH 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
147 CORRIDOR_FLR_3_WALL_1_EAST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
148 CORRIDOR_FLR_3_WALL_2_EAST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
149 CORRIDOR_FLR_3_WALL_3_EAST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
150 CORRIDOR_FLR_3_WALL_4_EAST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
151 CORRIDOR_FLR_3_WALL_3_SOUTH 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
152 CORRIDOR_FLR_3_WALL_1_WEST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
153 CORRIDOR_FLR_3_WALL_2_WEST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
154 CORRIDOR_FLR_3_WALL_3_WEST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
155 CORRIDOR_FLR_3_WALL_4_WEST 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
156 CORRIDOR_FLR_3_FLOOR_1 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
157 CORRIDOR_FLR_3_FLOOR_2 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
158 CORRIDOR_FLR_3_FLOOR_3 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
159 CORRIDOR_FLR_3_CEILING_1 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
160 CORRIDOR_FLR_3_CEILING_2 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
161 CORRIDOR_FLR_3_CEILING_3 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
162 CORRIDOR_FLR_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 15.85 8.24 0.33 0 No No
163 ROOM_1_FLR_6_WALL_SOUTH 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 3 No No
164 ROOM_1_FLR_6_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 13.11 5.95 0.33 2 No No
165 ROOM_1_FLR_6_WALL_WEST 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 3 No No
166 ROOM_1_FLR_6_WALL_WEST_WINDOW 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 2 No No
167 ROOM_1_FLR_6_WALL_NORTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
168 ROOM_1_FLR_6_WALL_EAST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
169 ROOM_1_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
170 ROOM_1_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 13.11 5.95 0.33 0 No No
171 ROOM_1_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
172 ROOM_2_FLR_6_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 3 No No
173 ROOM_2_FLR_6_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 13.11 5.95 0.33 2 No No
174 ROOM_2_FLR_6_WALL_WEST 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 3 No No
175 ROOM_2_FLR_6_WALL_WEST_WINDOW 0 194.63 84.12 19.20 0 3.05 13.11 5.95 0.33 2 No No
176 ROOM_2_FLR_6_WALL_EAST 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
177 ROOM_2_FLR_6_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
178 ROOM_2_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
179 ROOM_2_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 13.11 5.95 0.33 0 No No
180 ROOM_2_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 13.11 5.95 0.33 0 No No
181 ROOM_3_MULT9_FLR_6_WALL_SOUTH 0 506.51 211.91 19.20 0 3.05 6.71 4.73 0.33 3 No No
182 ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 6.71 4.73 0.33 2 No No
183 ROOM_3_MULT9_FLR_6_WALL_NORTH 0 0.00 0.00 0.00 0 3.05 6.71 4.73 0.33 0 No No
184 ROOM_3_MULT9_FLR_6_WALL_EAST 0 0.00 0.00 0.00 0 3.05 6.71 4.73 0.33 0 No No
185 ROOM_3_MULT9_FLR_6_WALL_WEST 0 0.00 0.00 0.00 0 3.05 6.71 4.73 0.33 0 No No
186 ROOM_3_MULT9_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 6.71 4.73 0.33 0 No No
187 ROOM_3_MULT9_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 6.71 4.73 0.33 0 No No
188 ROOM_3_MULT9_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 6.71 4.73 0.33 0 No No
189 BANQUET_FLR_6_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 32.00 15.66 0.33 3 No No
190 BANQUET_FLR_6_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 32.00 15.66 0.33 2 No No
191 BANQUET_FLR_6_WALL_EAST 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
192 BANQUET_FLR_6_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
193 BANQUET_FLR_6_WALL_WEST 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
194 BANQUET_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
195 BANQUET_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 32.00 15.66 0.33 0 No No
196 BANQUET_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
197 DINING_FLR_6_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 32.00 15.66 0.33 3 No No
198 DINING_FLR_6_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 32.00 15.66 0.33 2 No No
199 DINING_FLR_6_WALL_EAST 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
200 DINING_FLR_6_WALL_SOUTH 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
201 DINING_FLR_6_WALL_WEST 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
202 DINING_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
203 DINING_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 32.00 15.66 0.33 0 No No
204 DINING_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 32.00 15.66 0.33 0 No No
205 KITCHEN_FLR_6_WALL_NORTH 0 670.01 217.46 19.20 0 3.05 28.65 8.58 0.30 3 No No
206 KITCHEN_FLR_6_WALL_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 28.65 8.58 0.30 2 No No
207 KITCHEN_FLR_6_WALL_EAST 0 194.63 217.46 19.20 0 3.05 28.65 8.58 0.30 3 No No
208 KITCHEN_FLR_6_WALL_EAST_WINDOW 0 194.63 217.46 19.20 0 3.05 28.65 8.58 0.30 2 No No
209 KITCHEN_FLR_6_WALL_1_SOUTH 0 506.51 211.91 19.20 0 3.05 28.65 8.58 0.30 3 No No
210 KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 28.65 8.58 0.30 2 No No
211 KITCHEN_FLR_6_WALL_2_SOUTH 0 0.00 0.00 0.00 0 3.05 28.65 8.58 0.30 0 No No
212 KITCHEN_FLR_6_WALL_1_WEST 0 0.00 0.00 0.00 0 3.05 28.65 8.58 0.30 0 No No
213 KITCHEN_FLR_6_WALL_2_WEST 0 0.00 0.00 0.00 0 3.05 28.65 8.58 0.30 0 No No
214 KITCHEN_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 28.65 8.58 0.30 0 No No
215 KITCHEN_FLR_6_CEILING 0 1782.60 293.11 15.24 0 3.05 28.65 8.58 0.30 0 No No
216 KITCHEN_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 28.65 8.58 0.30 0 No No
217 CORRIDOR_FLR_6_WALL_1_NORTH 0 670.01 217.46 19.20 0 3.05 28.04 8.72 0.33 3 No No
218 CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 28.04 8.72 0.33 2 No No
219 CORRIDOR_FLR_6_WALL_2_NORTH 0 670.01 217.46 19.20 0 3.05 28.04 8.72 0.33 3 No No
220 CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW 0 670.01 217.46 19.20 0 3.05 28.04 8.72 0.33 2 No No
221 CORRIDOR_FLR_6_WALL_2_SOUTH 0 506.51 211.91 19.20 0 3.05 28.04 8.72 0.33 3 No No
222 CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW 0 506.51 211.91 19.20 0 3.05 28.04 8.72 0.33 2 No No
223 CORRIDOR_FLR_6_WALL_3_NORTH 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
224 CORRIDOR_FLR_6_WALL_4_NORTH 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
225 CORRIDOR_FLR_6_WALL_1_SOUTH 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
226 CORRIDOR_FLR_6_WALL_1_WEST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
227 CORRIDOR_FLR_6_WALL_2_WEST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
228 CORRIDOR_FLR_6_WALL_3_WEST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
229 CORRIDOR_FLR_6_WALL_1_EAST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
230 CORRIDOR_FLR_6_WALL_2_EAST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
231 CORRIDOR_FLR_6_WALL_3_EAST 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
232 CORRIDOR_FLR_6_FLOOR 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No
233 CORRIDOR_FLR_6_CEILING_1 0 1782.60 293.11 15.24 0 3.05 28.04 8.72 0.33 0 No No
234 CORRIDOR_FLR_6_CEILING_2 0 1782.60 293.11 15.24 0 3.05 28.04 8.72 0.33 0 No No
235 CORRIDOR_FLR_6_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 28.04 8.72 0.33 0 No No


ZoneInfiltration Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Design Volume Flow Rate {m3/s} Volume Flow Rate/Floor Area {m3/s-m2} Volume Flow Rate/Exterior Surface Area {m3/s-m2} ACH - Air Changes per Hour Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2}
1 RETAIL_1_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH RETAIL_1_FLR_1 67.07 10.8 7.058E-002 1.052E-003 5.193E-004 0.956 1.000 0.000 0.000 0.000
2 RETAIL_2_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH RETAIL_2_FLR_1 77.67 12.5 2.724E-002 3.507E-004 9.551E-004 0.319 1.000 0.000 0.000 0.000
3 MECH_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH MECH_FLR_1 164.24 2.7 6.438E-002 3.920E-004 1.025E-003 0.356 1.000 0.000 0.000 0.000
4 STORAGE_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH STORAGE_FLR_1 94.76 2.0 3.715E-002 3.920E-004 8.507E-004 0.356 1.000 0.000 0.000 0.000
5 LAUNDRY_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH LAUNDRY_FLR_1 78.04 8.4 8.791E-002 1.127E-003 1.002E-003 1.023 1.000 0.000 0.000 0.000
6 CAFE_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH CAFE_FLR_1 188.86 142.3 0.156 8.261E-004 4.549E-004 0.751 1.000 0.000 0.000 0.000
7 LOBBY_FLR_1_INFILTRATION INFIL_QUARTER_ON_SCH LOBBY_FLR_1 1308.19 422.4 0.446 3.407E-004 6.517E-004 0.310 1.000 0.000 0.000 0.000
8 ROOM_1_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_1_FLR_3 39.02 1.5 4.096E-002 1.050E-003 1.025E-003 1.240 1.000 0.000 0.000 0.000
9 ROOM_2_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_2_FLR_3 39.02 1.5 4.095E-002 1.050E-003 1.025E-003 1.240 1.000 0.000 0.000 0.000
10 ROOM_3_MULT19_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_3_MULT19_FLR_3 24.52 1.5 1.143E-002 4.660E-004 1.025E-003 0.550 1.000 0.000 0.000 0.000
11 ROOM_4_MULT19_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_4_MULT19_FLR_3 24.53 1.5 1.143E-002 4.660E-004 1.025E-003 0.550 1.000 0.000 0.000 0.000
12 ROOM_5_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_5_FLR_3 39.02 1.5 4.096E-002 1.050E-003 1.025E-003 1.240 1.000 0.000 0.000 0.000
13 ROOM_6_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_6_FLR_3 39.02 1.5 4.095E-002 1.050E-003 1.025E-003 1.240 1.000 0.000 0.000 0.000
14 CORRIDOR_FLR_3_INFILTRATION INFIL_QUARTER_ON_SCH CORRIDOR_FLR_3 389.40 21.0 4.953E-002 1.272E-004 1.025E-003 0.150 1.000 0.000 0.000 0.000
15 ROOM_1_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_1_FLR_6 39.02 1.5 4.096E-002 1.050E-003 5.186E-004 1.240 1.000 0.000 0.000 0.000
16 ROOM_2_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_2_FLR_6 39.02 1.5 4.095E-002 1.050E-003 5.186E-004 1.240 1.000 0.000 0.000 0.000
17 ROOM_3_MULT9_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH ROOM_3_MULT9_FLR_6 24.53 1.5 2.096E-002 8.543E-004 4.660E-004 1.009 1.000 0.000 0.000 0.000
18 BANQUET_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH BANQUET_FLR_6 331.66 249.9 0.100 3.015E-004 2.330E-004 0.356 1.000 0.000 0.000 0.000
19 DINING_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH DINING_FLR_6 331.66 249.9 0.100 3.015E-004 2.330E-004 0.356 1.000 0.000 0.000 0.000
20 KITCHEN_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH KITCHEN_FLR_6 103.30 22.2 8.953E-002 8.667E-004 4.697E-004 1.024 1.000 0.000 0.000 0.000
21 CORRIDOR_FLR_6_INFILTRATION INFIL_QUARTER_ON_SCH CORRIDOR_FLR_6 412.12 22.2 8.763E-002 2.126E-004 1.761E-004 0.251 1.000 0.000 0.000 0.000


ZoneVentilation Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Design Volume Flow Rate {m3/s} Volume Flow Rate/Floor Area {m3/s-m2} Volume Flow Rate/person Area {m3/s-person} ACH - Air Changes per Hour Fan Type {Exhaust;Intake;Natural} Fan Pressure Rise {Pa} Fan Efficiency {} Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2} Minimum Indoor Temperature{C}/Schedule Maximum Indoor Temperature{C}/Schedule Delta Temperature{C}/Schedule Minimum Outdoor Temperature{C}/Schedule Maximum Outdoor Temperature{C}/Schedule Maximum WindSpeed{m/s}
1 ROOM_1_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_1_FLR_3 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
2 ROOM_2_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_2_FLR_3 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
3 ROOM_3_MULT19_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_3_MULT19_FLR_3 24.52 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
4 ROOM_4_MULT19_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_4_MULT19_FLR_3 24.53 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
5 ROOM_5_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_5_FLR_3 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
6 ROOM_6_FLR_3 SLIDING DOOR VENTILATION Constant-0.0 ROOM_6_FLR_3 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
7 ROOM_1_FLR_6 SLIDING DOOR VENTILATION Constant-0.0 ROOM_1_FLR_6 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
8 ROOM_2_FLR_6 SLIDING DOOR VENTILATION Constant-0.0 ROOM_2_FLR_6 39.02 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00
9 ROOM_3_MULT9_FLR_6 SLIDING DOOR VENTILATION Constant-0.0 ROOM_3_MULT9_FLR_6 24.53 1.5 0.000 0.000 0.000 0.000 Natural 0.000 0.0 0.000 0.000 0.000 0.000 18.89 25.56 -100.00 15.56 23.89 40.00


AirFlow Model

Simple
1 Simple


RoomAir Model

Zone Name Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined
1 BASEMENT Mixing/Well-Stirred
2 RETAIL_1_FLR_1 Mixing/Well-Stirred
3 RETAIL_2_FLR_1 Mixing/Well-Stirred
4 MECH_FLR_1 Mixing/Well-Stirred
5 STORAGE_FLR_1 Mixing/Well-Stirred
6 LAUNDRY_FLR_1 Mixing/Well-Stirred
7 CAFE_FLR_1 Mixing/Well-Stirred
8 LOBBY_FLR_1 Mixing/Well-Stirred
9 ROOM_1_FLR_3 Mixing/Well-Stirred
10 ROOM_2_FLR_3 Mixing/Well-Stirred
11 ROOM_3_MULT19_FLR_3 Mixing/Well-Stirred
12 ROOM_4_MULT19_FLR_3 Mixing/Well-Stirred
13 ROOM_5_FLR_3 Mixing/Well-Stirred
14 ROOM_6_FLR_3 Mixing/Well-Stirred
15 CORRIDOR_FLR_3 Mixing/Well-Stirred
16 ROOM_1_FLR_6 Mixing/Well-Stirred
17 ROOM_2_FLR_6 Mixing/Well-Stirred
18 ROOM_3_MULT9_FLR_6 Mixing/Well-Stirred
19 BANQUET_FLR_6 Mixing/Well-Stirred
20 DINING_FLR_6 Mixing/Well-Stirred
21 KITCHEN_FLR_6 Mixing/Well-Stirred
22 CORRIDOR_FLR_6 Mixing/Well-Stirred


AirflowNetwork Model:Control

No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation
1 NoMultizoneOrDistribution


Zone Volume Capacitance Multiplier

Sensible Heat Capacity Multiplier Moisture Capacity Multiplier Carbon Dioxide Capacity Multiplier Generic Contaminant Capacity Multiplier
1 1.000 1.000 1.000 1.000


Load Timesteps in Zone Design Calculation Averaging Window

Value
1 6


Heating Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Cooling Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Zone Sizing Information

Zone Name Load Type Calc Des Load {W} User Des Load {W} Calc Des Air Flow Rate {m3/s} User Des Air Flow Rate {m3/s} Design Day Name Date/Time of Peak Temperature at Peak {C} Humidity Ratio at Peak {kgWater/kgDryAir} Floor Area {m2} # Occupants Calc Outdoor Air Flow Rate {m3/s} Calc DOAS Heat Addition Rate {W}
1 BASEMENT Cooling 36589.01191 36589.01191 2.66161 2.66161 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 20:50:00 29.34750 1.71599E-002 1978.83018 106.49900 0.85446 0.00000
2 BASEMENT Heating 0.00000 0.00000 0.00000 0.85446   00:10:00 8.70000 6.99286E-003 1978.83018 106.49900 0.85446 0.00000
3 RETAIL_1_FLR_1 Cooling 4035.57954 4035.57954 0.29364 0.29364 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:20:00 33.20000 1.71672E-002 67.07136 10.82900 7.92179E-002 0.00000
4 RETAIL_1_FLR_1 Heating 1572.80713 1572.80713 6.74942E-002 7.92179E-002 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 23:40:00 8.70000 6.99286E-003 67.07136 10.82900 7.92179E-002 0.00000
5 RETAIL_2_FLR_1 Cooling 3329.50875 3329.50875 0.24224 0.24224 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:50:00 31.70367 1.71644E-002 77.66889 12.54000 9.17347E-002 0.00000
6 RETAIL_2_FLR_1 Heating 502.99216 502.99216 2.15852E-002 9.17347E-002 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 23:40:00 8.70000 6.99286E-003 77.66889 12.54000 9.17347E-002 0.00000
7 MECH_FLR_1 Cooling 3594.32209 3594.32209 0.26146 0.26146 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:50:00 30.75450 1.71626E-002 164.24319 2.65200 0.00000 0.00000
8 MECH_FLR_1 Heating 925.33319 925.33319 3.97094E-002 3.97094E-002 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 23:40:00 8.70000 6.99286E-003 164.24319 2.65200 0.00000 0.00000
9 STORAGE_FLR_1 Cooling 1794.42221 1794.42221 0.13053 0.13053 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 31.92700 1.71648E-002 94.75927 2.04000 5.77652E-002 0.00000
10 STORAGE_FLR_1 Heating 543.47567 543.47567 2.33225E-002 5.77652E-002 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 23:40:00 8.70000 6.99286E-003 94.75927 2.04000 5.77652E-002 0.00000
11 LAUNDRY_FLR_1 Cooling 44900.51934 44900.51934 3.26667 3.26667 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 15:20:00 33.06600 1.71670E-002 78.03947 8.40000 0.00000 0.00000
12 LAUNDRY_FLR_1 Heating 1311.94393 1311.94393 5.62998E-002 5.62998E-002 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 23:40:00 8.70000 6.99286E-003 78.03947 8.40000 0.00000 0.00000
13 CAFE_FLR_1 Cooling 17983.22870 17983.22870 1.30953 1.30953 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:20:00 33.20000 1.71672E-002 188.86188 142.30000 0.67639 0.00000
14 CAFE_FLR_1 Heating 3920.75997 3920.75997 0.16825 0.67639 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 23:40:00 8.70000 6.99286E-003 188.86188 142.30000 0.67639 0.00000
15 LOBBY_FLR_1 Cooling 62635.18369 62635.18369 4.55831 4.55831 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:40:00 33.20000 1.71672E-002 1308.18612 422.43500 1.89399 0.00000
16 LOBBY_FLR_1 Heating 8822.87733 8822.87733 0.37862 1.89399 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 23:40:00 8.70000 6.99286E-003 1308.18612 422.43500 1.89399 0.00000
17 ROOM_1_FLR_3 Cooling 10694.98336 10694.98336 1.04854 1.04854 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00 32.26200 1.71654E-002 39.02202 1.50000 6.17350E-002 0.00000
18 ROOM_1_FLR_3 Heating 3659.98235 3659.98235 0.15798 0.15798 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 23:40:00 8.70000 6.99286E-003 39.02202 1.50000 6.17350E-002 0.00000
19 ROOM_2_FLR_3 Cooling 10800.34449 10800.34449 1.05887 1.05887 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:10:00 32.15033 1.71652E-002 39.01745 1.50000 6.17278E-002 0.00000
20 ROOM_2_FLR_3 Heating 3660.21081 3660.21081 0.15799 0.15799 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 23:40:00 8.70000 6.99286E-003 39.01745 1.50000 6.17278E-002 0.00000
21 ROOM_3_MULT19_FLR_3 Cooling 60738.62655 60738.62655 5.95398 5.95398 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:50:00 33.20000 1.71672E-002 24.52384 1.50000 0.83707 0.00000
22 ROOM_3_MULT19_FLR_3 Heating 21298.59993 21298.59993 0.91937 0.91937 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 23:40:00 8.70000 6.99286E-003 24.52384 1.50000 0.83707 0.00000
23 ROOM_4_MULT19_FLR_3 Cooling 70888.06309 70888.06309 6.94940 6.94940 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:40:00 31.81533 1.71646E-002 24.53055 1.50000 0.83730 0.00000
24 ROOM_4_MULT19_FLR_3 Heating 21316.20758 21316.20758 0.92013 0.92013 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 23:40:00 8.70000 6.99286E-003 24.53055 1.50000 0.83730 0.00000
25 ROOM_5_FLR_3 Cooling 9614.46511 9614.46511 0.94261 0.94261 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:00:00 30.65400 1.71624E-002 39.02202 1.50000 6.17350E-002 0.00000
26 ROOM_5_FLR_3 Heating 3659.02059 3659.02059 0.15794 0.15794 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 23:40:00 8.70000 6.99286E-003 39.02202 1.50000 6.17350E-002 0.00000
27 ROOM_6_FLR_3 Cooling 9695.83900 9695.83900 0.95059 0.95059 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:00:00 30.65400 1.71624E-002 39.01745 1.50000 6.17278E-002 0.00000
28 ROOM_6_FLR_3 Heating 3659.24905 3659.24905 0.15795 0.15795 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 23:40:00 8.70000 6.99286E-003 39.01745 1.50000 6.17278E-002 0.00000
29 CORRIDOR_FLR_3 Cooling 15134.36803 15134.36803 1.10093 1.10093 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00 32.26200 1.71654E-002 389.40468 20.95700 0.47476 0.00000
30 CORRIDOR_FLR_3 Heating 5760.67018 5760.67018 0.24721 0.47476 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 8.70000 6.99286E-003 389.40468 20.95700 0.47476 0.00000
31 ROOM_1_FLR_6 Cooling 2858.56632 2858.56632 0.28025 0.28025 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00 32.26200 1.71654E-002 39.02202 1.50000 1.54338E-002 0.00000
32 ROOM_1_FLR_6 Heating 1124.66297 1124.66297 4.85464E-002 4.85464E-002 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 23:40:00 8.70000 6.99286E-003 39.02202 1.50000 1.54338E-002 0.00000
33 ROOM_2_FLR_6 Cooling 2884.01452 2884.01452 0.28275 0.28275 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00 32.26200 1.71654E-002 39.01745 1.50000 1.54319E-002 0.00000
34 ROOM_2_FLR_6 Heating 1124.88987 1124.88987 4.85562E-002 4.85562E-002 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 23:40:00 8.70000 6.99286E-003 39.01745 1.50000 1.54319E-002 0.00000
35 ROOM_3_MULT9_FLR_6 Cooling 11887.51615 11887.51615 1.16545 1.16545 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:40:00 33.20000 1.71672E-002 24.53055 1.50000 9.91540E-002 0.00000
36 ROOM_3_MULT9_FLR_6 Heating 5435.91576 5435.91576 0.23464 0.23464 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 23:40:00 8.70000 6.99286E-003 24.53055 1.50000 9.91540E-002 0.00000
37 BANQUET_FLR_6 Cooling 30711.73528 30711.73528 2.23686 2.23686 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:40:00 33.20000 1.71672E-002 331.65745 249.89600 1.18780 0.00000
38 BANQUET_FLR_6 Heating 3704.57566 3704.57566 0.15898 1.18780 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 23:40:00 8.70000 6.99286E-003 331.65745 249.89600 1.18780 0.00000
39 DINING_FLR_6 Cooling 32227.39038 32227.39038 2.34722 2.34722 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:40:00 33.20000 1.71672E-002 331.65745 249.89600 1.18780 0.00000
40 DINING_FLR_6 Heating 3634.68411 3634.68411 0.15598 1.18780 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 04:20:00 8.70000 6.99286E-003 331.65745 249.89600 1.18780 0.00000
41 KITCHEN_FLR_6 Cooling 30873.17563 30873.17563 2.25188 2.25188 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 12:30:00 32.59700 1.71661E-002 103.30446 22.23800 0.36735 0.00000
42 KITCHEN_FLR_6 Heating 0.00000 0.00000 0.00000 0.36735   00:10:00 8.70000 6.99286E-003 103.30446 22.23800 0.36735 0.00000
43 CORRIDOR_FLR_6 Cooling 9118.13863 9118.13863 0.66329 0.66329 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:40:00 33.20000 1.71672E-002 412.12471 22.18000 0.12562 0.00000
44 CORRIDOR_FLR_6 Heating 3842.74498 3842.74498 0.16491 0.16491 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 04:30:00 8.70000 6.99286E-003 412.12471 22.18000 0.12562 0.00000


System Sizing Information

System Name Load Type Peak Load Kind User Design Capacity Calc Des Air Flow Rate [m3/s] User Des Air Flow Rate [m3/s] Design Day Name Date/Time of Peak
1 VAV WITH REHEAT Cooling Sensible 522995.19 21.21247 21.21247 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 00:00:00
2 VAV WITH REHEAT Heating Sensible 68958.03 7.13212 7.13212 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 04:30:00
3 FLR_3_DOAS Cooling Sensible 50573.62 18.18276 2.05125 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 00:00:00
4 FLR_3_DOAS Heating Sensible 19832.79 2.80312 2.05125 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 23:40:00


Component Sizing Information

Component Type Component Name Input Field Description Value
1 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.66161
2 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.56652
3 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.99500
4 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 2.64830
5 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
6 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
7 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 6.72521E-004
8 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.22184E-004
9 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 2.64830
10 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
11 AirTerminal:SingleDuct:VAV:Reheat BASEMENT VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
12 Coil:Heating:Water BASEMENT VAV BOX REHEAT COIL Design Size Rated Capacity [W] 13966.40810
13 Coil:Heating:Water BASEMENT VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.22184E-004
14 Coil:Heating:Water BASEMENT VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 291.24536
15 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.29364
16 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.17405
17 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.99500
18 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.29217
19 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.99500
20 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
21 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.18899E-003
22 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.72336E-005
23 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.29217
24 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
25 AirTerminal:SingleDuct:VAV:Reheat RETAIL_1_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
26 Coil:Heating:Water RETAIL_1_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 3112.96912
27 Coil:Heating:Water RETAIL_1_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.72336E-005
28 Coil:Heating:Water RETAIL_1_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 68.55718
29 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.24224
30 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.24432
31 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.99500
32 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.24103
33 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.99500
34 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
35 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.55944E-003
36 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.55156E-005
37 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.24103
38 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
39 AirTerminal:SingleDuct:VAV:Reheat RETAIL_2_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
40 Coil:Heating:Water RETAIL_2_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 1773.52546
41 Coil:Heating:Water RETAIL_2_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.55156E-005
42 Coil:Heating:Water RETAIL_2_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 37.75893
43 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.26146
44 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.47868
45 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.99500
46 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.26015
47 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
48 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
49 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 7.95939E-004
50 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.00910E-005
51 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.26015
52 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
53 AirTerminal:SingleDuct:VAV:Reheat MECH_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
54 Coil:Heating:Water MECH_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 2296.52015
55 Coil:Heating:Water MECH_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.00910E-005
56 Coil:Heating:Water MECH_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 49.63033
57 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.13053
58 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.55318
59 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.99500
60 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.12988
61 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
62 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
63 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 6.88741E-004
64 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.07434E-005
65 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.12988
66 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
67 AirTerminal:SingleDuct:VAV:Reheat STORAGE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
68 Coil:Heating:Water STORAGE_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 1228.03352
69 Coil:Heating:Water STORAGE_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.07434E-005
70 Coil:Heating:Water STORAGE_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 26.71151
71 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 3.26667
72 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 7.22368E-002
73 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.99500
74 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 3.25034
75 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.99500
76 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
77 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.09296E-002
78 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.61353E-004
79 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 3.25034
80 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
81 AirTerminal:SingleDuct:VAV:Reheat LAUNDRY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
82 Coil:Heating:Water LAUNDRY_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 18443.64925
83 Coil:Heating:Water LAUNDRY_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.61353E-004
84 Coil:Heating:Water LAUNDRY_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 386.13097
85 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.30953
86 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.10990
87 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.99500
88 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.30298
89 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.99500
90 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
91 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.46690E-003
92 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 9.43928E-005
93 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.30298
94 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
95 AirTerminal:SingleDuct:VAV:Reheat CAFE_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
96 Coil:Heating:Water CAFE_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 10789.67552
97 Coil:Heating:Water CAFE_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 9.43928E-005
98 Coil:Heating:Water CAFE_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 231.87490
99 Fan:ZoneExhaust LOBBY_FLR_1 EXHAUST FAN User-Specified Maximum Flow Rate [m3/s] 0.00000
100 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 4.55831
101 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.21869
102 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.99500
103 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 4.53552
104 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.99500
105 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
106 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.74223E-003
107 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.86349E-004
108 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 4.53552
109 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
110 AirTerminal:SingleDuct:VAV:Reheat LOBBY_FLR_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
111 Coil:Heating:Water LOBBY_FLR_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 32731.43609
112 Coil:Heating:Water LOBBY_FLR_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.86349E-004
113 Coil:Heating:Water LOBBY_FLR_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 695.87081
114 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_1_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 6.17350E-002
115 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 1.04854
116 Fan:OnOff ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 1.04854
117 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 3.20189E-005
118 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 4.88014E-004
119 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 22.48737
120 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
121 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.87242E-003
122 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
123 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
124 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 4.88014E-004
125 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 1.04854
126 Coil:Heating:Water ROOM_1_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 3659.95589
127 Coil:Heating:Water ROOM_1_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 3.20189E-005
128 Coil:Heating:Water ROOM_1_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 104.57399
129 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_2_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 6.17278E-002
130 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 1.05887
131 Fan:OnOff ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 1.05887
132 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 3.20209E-005
133 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 4.92391E-004
134 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 22.48738
135 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
136 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.86870E-003
137 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
138 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
139 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 4.92391E-004
140 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 1.05887
141 Coil:Heating:Water ROOM_2_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 3660.18435
142 Coil:Heating:Water ROOM_2_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 3.20209E-005
143 Coil:Heating:Water ROOM_2_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 104.58052
144 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_3_MULT19_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.83707
145 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT19_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 5.95398
146 Fan:OnOff ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 5.95398
147 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT19_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 1.86329E-004
148 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT19_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 2.71443E-003
149 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 22.48878
150 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
151 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.78469E-003
152 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
153 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
154 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 2.71443E-003
155 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 5.95398
156 Coil:Heating:Water ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 21298.52566
157 Coil:Heating:Water ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 1.86329E-004
158 Coil:Heating:Water ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 608.54680
159 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_4_MULT19_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.83730
160 ZoneHVAC:FourPipeFanCoil ROOM_4_MULT19_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 6.94940
161 Fan:OnOff ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 6.94940
162 ZoneHVAC:FourPipeFanCoil ROOM_4_MULT19_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 1.86483E-004
163 ZoneHVAC:FourPipeFanCoil ROOM_4_MULT19_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 3.28815E-003
164 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 22.48777
165 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
166 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.94306E-003
167 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
168 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
169 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 3.28815E-003
170 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 6.94940
171 Coil:Heating:Water ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 21316.13324
172 Coil:Heating:Water ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 1.86483E-004
173 Coil:Heating:Water ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 609.04986
174 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_5_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 6.17350E-002
175 ZoneHVAC:FourPipeFanCoil ROOM_5_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 0.94261
176 Fan:OnOff ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 0.94261
177 ZoneHVAC:FourPipeFanCoil ROOM_5_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 3.20105E-005
178 ZoneHVAC:FourPipeFanCoil ROOM_5_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 4.43087E-004
179 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 22.48723
180 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
181 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.91497E-003
182 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
183 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
184 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 4.43087E-004
185 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 0.94261
186 Coil:Heating:Water ROOM_5_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 3658.99414
187 Coil:Heating:Water ROOM_5_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 3.20105E-005
188 Coil:Heating:Water ROOM_5_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 104.54651
189 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_6_FLR_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 6.17278E-002
190 ZoneHVAC:FourPipeFanCoil ROOM_6_FLR_3 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 0.95059
191 Fan:OnOff ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 0.95059
192 ZoneHVAC:FourPipeFanCoil ROOM_6_FLR_3 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 3.20125E-005
193 ZoneHVAC:FourPipeFanCoil ROOM_6_FLR_3 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 4.46514E-004
194 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 22.48724
195 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
196 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.91185E-003
197 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
198 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
199 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 4.46514E-004
200 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 0.95059
201 Coil:Heating:Water ROOM_6_FLR_3 FAN COIL HEATING COIL Design Size Rated Capacity [W] 3659.22260
202 Coil:Heating:Water ROOM_6_FLR_3 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 3.20125E-005
203 Coil:Heating:Water ROOM_6_FLR_3 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 104.55304
204 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.10093
205 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 1.00000
206 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.99500
207 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.09543
208 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
209 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
210 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.53403E-004
211 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.00920E-004
212 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.09543
213 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
214 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
215 Coil:Heating:Water CORRIDOR_FLR_3 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 11535.77444
216 Coil:Heating:Water CORRIDOR_FLR_3 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.00920E-004
217 Coil:Heating:Water CORRIDOR_FLR_3 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 253.72322
218 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_1_FLR_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 1.54338E-002
219 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_6 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 0.28025
220 Fan:OnOff ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 0.28025
221 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_6 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 9.83897E-006
222 ZoneHVAC:FourPipeFanCoil ROOM_1_FLR_6 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 1.29737E-004
223 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 22.48745
224 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
225 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.84955E-003
226 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
227 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
228 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 1.29737E-004
229 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 0.28025
230 Coil:Heating:Water ROOM_1_FLR_6 FAN COIL HEATING COIL Design Size Rated Capacity [W] 1124.65482
231 Coil:Heating:Water ROOM_1_FLR_6 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 9.83897E-006
232 Coil:Heating:Water ROOM_1_FLR_6 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 32.13355
233 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_2_FLR_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 1.54319E-002
234 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_6 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 0.28275
235 Fan:OnOff ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 0.28275
236 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_6 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 9.84096E-006
237 ZoneHVAC:FourPipeFanCoil ROOM_2_FLR_6 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 1.30788E-004
238 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 22.48745
239 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
240 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.84615E-003
241 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
242 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
243 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 1.30788E-004
244 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 0.28275
245 Coil:Heating:Water ROOM_2_FLR_6 FAN COIL HEATING COIL Design Size Rated Capacity [W] 1124.88172
246 Coil:Heating:Water ROOM_2_FLR_6 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 9.84096E-006
247 Coil:Heating:Water ROOM_2_FLR_6 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 32.14004
248 AirTerminal:SingleDuct:ConstantVolume:NoReheat ROOM_3_MULT9_FLR_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 9.91540E-002
249 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT9_FLR_6 FAN COIL Design Size Maximum Supply Air Flow Rate [m3/s] 1.16545
250 Fan:OnOff ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN Design Size Maximum Flow Rate [m3/s] 1.16545
251 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT9_FLR_6 FAN COIL Design Size Maximum Hot Water Flow [m3/s] 4.75555E-005
252 ZoneHVAC:FourPipeFanCoil ROOM_3_MULT9_FLR_6 FAN COIL Design Size Maximum Cold Water Flow [m3/s] 5.52624E-004
253 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Temperature [C] 22.48724
254 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
255 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.95259E-003
256 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Temperature [C] 12.80000
257 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
258 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Water Flow Rate [m3/s] 5.52624E-004
259 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Design Size Design Air Flow Rate [m3/s] 1.16545
260 Coil:Heating:Water ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL Design Size Rated Capacity [W] 5435.88386
261 Coil:Heating:Water ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 4.75555E-005
262 Coil:Heating:Water ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL Design Size U-Factor Times Area Value [W/K] 155.31309
263 Fan:ZoneExhaust BANQUET_FLR_6 EXHAUST FAN User-Specified Maximum Flow Rate [m3/s] 0.00000
264 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.23686
265 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.11298
266 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.99500
267 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 2.22568
268 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.99500
269 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
270 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.37225E-003
271 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.35067E-004
272 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 2.22568
273 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
274 AirTerminal:SingleDuct:VAV:Reheat BANQUET_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
275 Coil:Heating:Water BANQUET_FLR_6 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 15438.99176
276 Coil:Heating:Water BANQUET_FLR_6 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.35067E-004
277 Coil:Heating:Water BANQUET_FLR_6 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 327.31152
278 Fan:ZoneExhaust DINING_FLR_6 EXHAUST FAN User-Specified Maximum Flow Rate [m3/s] 0.00000
279 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.34722
280 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.10767
281 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.99500
282 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 2.33548
283 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.99500
284 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
285 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.53862E-003
286 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.39520E-004
287 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 2.33548
288 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
289 AirTerminal:SingleDuct:VAV:Reheat DINING_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
290 Coil:Heating:Water DINING_FLR_6 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 15947.95577
291 Coil:Heating:Water DINING_FLR_6 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.39520E-004
292 Coil:Heating:Water DINING_FLR_6 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 337.73531
293 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.25188
294 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.83832
295 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.99500
296 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 2.24062
297 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.99500
298 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
299 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.08992E-002
300 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.03375E-004
301 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 2.24062
302 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
303 AirTerminal:SingleDuct:VAV:Reheat KITCHEN_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
304 Coil:Heating:Water KITCHEN_FLR_6 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 11816.38933
305 Coil:Heating:Water KITCHEN_FLR_6 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.03375E-004
306 Coil:Heating:Water KITCHEN_FLR_6 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 246.41043
307 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.66329
308 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.47345
309 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.99500
310 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.65998
311 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
312 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
313 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 8.04726E-004
314 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 6.40598E-005
315 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.65998
316 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 16.70000
317 AirTerminal:SingleDuct:VAV:Reheat CORRIDOR_FLR_6 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
318 Coil:Heating:Water CORRIDOR_FLR_6 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 7322.42882
319 Coil:Heating:Water CORRIDOR_FLR_6 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 6.40598E-005
320 Coil:Heating:Water CORRIDOR_FLR_6 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 162.01228
321 AirLoopHVAC VAV WITH REHEAT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 21.21755
322 AirLoopHVAC VAV WITH REHEAT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 21.21755
323 AirLoopHVAC VAV WITH REHEAT Sum of Air Terminal Maximum Flow Rates [m3/s] 21.32417
324 AirLoopHVAC VAV WITH REHEAT Adjusted Heating Design Air Flow Rate [m3/s] 21.21755
325 AirLoopHVAC VAV WITH REHEAT Adjusted Cooling Design Air Flow Rate [m3/s] 21.21755
326 AirLoopHVAC VAV WITH REHEAT Adjusted Main Design Air Flow Rate [m3/s] 21.21755
327 AirLoopHVAC VAV WITH REHEAT User Heating Air Flow Ratio [] 0.30000
328 AirLoopHVAC VAV WITH REHEAT Calculated Heating Air Flow Ratio [] 1.00000
329 AirLoopHVAC FLR_3_DOAS Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 2.05132
330 AirLoopHVAC FLR_3_DOAS Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 2.05132
331 AirLoopHVAC FLR_3_DOAS Sum of Air Terminal Maximum Flow Rates [m3/s] 2.05132
332 AirLoopHVAC FLR_3_DOAS Adjusted Heating Design Air Flow Rate [m3/s] 2.05132
333 AirLoopHVAC FLR_3_DOAS Adjusted Cooling Design Air Flow Rate [m3/s] 2.05132
334 AirLoopHVAC FLR_3_DOAS Adjusted Main Design Air Flow Rate [m3/s] 2.05132
335 AirLoopHVAC FLR_3_DOAS User Heating Air Flow Ratio [] 0.30000
336 AirLoopHVAC FLR_3_DOAS Calculated Heating Air Flow Ratio [] 1.00000
337 AirLoopHVAC VAV WITH REHEAT Design Supply Air Flow Rate [m3/s] 21.21755
338 AirLoopHVAC FLR_3_DOAS Design Supply Air Flow Rate [m3/s] 2.05132
339 Controller:OutdoorAir VAV WITH REHEAT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 21.21755
340 Controller:OutdoorAir VAV WITH REHEAT_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 21.21247
341 HeatExchanger:AirToAir:SensibleAndLatent VAV WITH REHEAT OA HEAT RECOVERY Design Size Nominal Supply Air Flow Rate [m3/s] 21.21247
342 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Inlet Air Temperature [C] 33.20000
343 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
344 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Outlet Air Temperature [C] 11.00309
345 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 1.71672E-002
346 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
347 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Coil Load [W] 1144947.37232
348 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Water Flow Rate [m3/s] 4.08949E-002
349 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL Design Size Design Air Flow Rate [m3/s] 21.21755
350 Coil:Heating:Water VAV WITH REHEAT HEATING COIL Design Size Rated Capacity [W] 61543.58415
351 Coil:Heating:Water VAV WITH REHEAT HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 5.38410E-004
352 Coil:Heating:Water VAV WITH REHEAT HEATING COIL Design Size U-Factor Times Area Value [W/K] 1142.02404
353 Fan:VariableVolume VAV WITH REHEAT FAN Design Size Maximum Flow Rate [m3/s] 21.21755
354 Controller:WaterCoil VAV WITH REHEAT_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 4.08949E-002
355 Controller:WaterCoil VAV WITH REHEAT_COOLC_CONTROLLER Controller Convergence Tolerance 1.16443E-005
356 Controller:WaterCoil VAV WITH REHEAT_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 5.38410E-004
357 Controller:OutdoorAir FLR_3_DOAS_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 2.05132
358 Controller:OutdoorAir FLR_3_DOAS_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 2.05125
359 HeatExchanger:AirToAir:SensibleAndLatent FLR_3_DOAS OA HEAT RECOVERY Design Size Nominal Supply Air Flow Rate [m3/s] 2.05125
360 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Inlet Air Temperature [C] 33.20000
361 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Inlet Water Temperature [C] 6.70000
362 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Outlet Air Temperature [C] 11.94186
363 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 1.71672E-002
364 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
365 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Coil Load [W] 108329.82081
366 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Water Flow Rate [m3/s] 3.86929E-003
367 Coil:Cooling:Water FLR_3_DOAS COOLING COIL Design Size Design Air Flow Rate [m3/s] 2.05132
368 Coil:Heating:Water FLR_3_DOAS HEATING COIL Design Size Rated Capacity [W] 5950.04693
369 Coil:Heating:Water FLR_3_DOAS HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 5.20536E-005
370 Coil:Heating:Water FLR_3_DOAS HEATING COIL Design Size U-Factor Times Area Value [W/K] 110.41113
371 Fan:ConstantVolume FLR_3_DOAS FAN User-Specified Maximum Flow Rate [m3/s] 2.05125
372 Controller:WaterCoil FLR_3_DOAS_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 3.86929E-003
373 Controller:WaterCoil FLR_3_DOAS_COOLC_CONTROLLER Controller Convergence Tolerance 1.23069E-004
374 Controller:WaterCoil FLR_3_DOAS_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 5.20536E-005
375 Pump:VariableSpeed COOLSYS1 PUMP SECONDARY Design Flow Rate [m3/s] 5.34499E-002
376 Pump:VariableSpeed COOLSYS1 PUMP SECONDARY Design Power Consumption [W] 11014.04150
377 PlantLoop HEATSYS1 Maximum Loop Flow Rate [m3/s] 2.43938E-003
378 PlantLoop HEATSYS1 Plant Loop Volume [m3] 0.29273
379 Pump:VariableSpeed HEATSYS1 PUMP Design Flow Rate [m3/s] 2.43938E-003
380 Pump:VariableSpeed HEATSYS1 PUMP Design Power Consumption [W] 734.63336
381 Pump:VariableSpeed HEATSYS1 PUMP Design Minimum Flow Rate [m3/s] 0.00000
382 Boiler:HotWater HEATSYS1 BOILER Design Size Nominal Capacity [W] 278835.82468
383 Boiler:HotWater HEATSYS1 BOILER User-Specified Nominal Capacity [W] 278835.82000
384 Boiler:HotWater HEATSYS1 BOILER Design Size Design Water Flow Rate [m3/s] 2.43938E-003
385 PlantLoop COOLSYS1 Maximum Loop Flow Rate [m3/s] 5.34499E-002
386 PlantLoop COOLSYS1 Plant Loop Volume [m3] 6.41399
387 Pump:ConstantSpeed COOLSYS1 PUMP Design Flow Rate [m3/s] 5.34499E-002
388 Pump:ConstantSpeed COOLSYS1 PUMP Design Power Consumption [W] 7625.39242
389 Chiller:Electric:EIR COOLSYS1 CHILLER1 Design Size Reference Chilled Water Flow Rate [m3/s] 5.34499E-002
390 Chiller:Electric:EIR COOLSYS1 CHILLER1 Design Size Reference Capacity [W] 1496454.59945
391 Chiller:Electric:EIR COOLSYS1 CHILLER1 User-Specified Reference Capacity [W] 1497043.85000
392 Chiller:Electric:EIR COOLSYS1 CHILLER1 Design Size Reference Condenser Fluid Flow Rate [m3/s] 170.66300
393 PlantLoop SWHSYS1 Maximum Loop Flow Rate [m3/s] 3.75036E-004
394 PlantLoop SWHSYS1 Plant Loop Volume [m3] 4.50044E-002
395 Pump:ConstantSpeed SWHSYS1 PUMP Design Flow Rate [m3/s] 3.75036E-004
396 Pump:ConstantSpeed SWHSYS1 PUMP Design Power Consumption [W] 47.90688
397 WaterHeater:Mixed SWHSYS1 WATER HEATER Use Side Design Flow Rate [m3/s] 3.75036E-004


Water Heating Coil Capacity Information

Component Type Name Nominal Total Capacity {W}
1 Coil:Heating:Water BASEMENT VAV BOX REHEAT COIL 14038.54
2 Coil:Heating:Water RETAIL_1_FLR_1 VAV BOX REHEAT COIL 3128.03
3 Coil:Heating:Water RETAIL_2_FLR_1 VAV BOX REHEAT COIL 1782.51
4 Coil:Heating:Water MECH_FLR_1 VAV BOX REHEAT COIL 2307.99
5 Coil:Heating:Water STORAGE_FLR_1 VAV BOX REHEAT COIL 1234.13
6 Coil:Heating:Water LAUNDRY_FLR_1 VAV BOX REHEAT COIL 18538.55
7 Coil:Heating:Water CAFE_FLR_1 VAV BOX REHEAT COIL 10843.85
8 Coil:Heating:Water LOBBY_FLR_1 VAV BOX REHEAT COIL 32897.42
9 Coil:Heating:Water ROOM_1_FLR_3 FAN COIL HEATING COIL 3941.71
10 Coil:Heating:Water ROOM_2_FLR_3 FAN COIL HEATING COIL 3941.96
11 Coil:Heating:Water ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL 22938.09
12 Coil:Heating:Water ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL 22957.06
13 Coil:Heating:Water ROOM_5_FLR_3 FAN COIL HEATING COIL 3940.68
14 Coil:Heating:Water ROOM_6_FLR_3 FAN COIL HEATING COIL 3940.92
15 Coil:Heating:Water CORRIDOR_FLR_3 VAV BOX REHEAT COIL 11591.66
16 Coil:Heating:Water ROOM_1_FLR_6 FAN COIL HEATING COIL 1211.22
17 Coil:Heating:Water ROOM_2_FLR_6 FAN COIL HEATING COIL 1211.47
18 Coil:Heating:Water ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL 5854.28
19 Coil:Heating:Water BANQUET_FLR_6 VAV BOX REHEAT COIL 15517.49
20 Coil:Heating:Water DINING_FLR_6 VAV BOX REHEAT COIL 16029.13
21 Coil:Heating:Water KITCHEN_FLR_6 VAV BOX REHEAT COIL 11877.42
22 Coil:Heating:Water CORRIDOR_FLR_6 VAV BOX REHEAT COIL 7357.68
23 Coil:Heating:Water VAV WITH REHEAT HEATING COIL 55098.44
24 Coil:Heating:Water FLR_3_DOAS HEATING COIL 5326.93


Water Cooling Coil Capacity Information

Component Type Name Nominal Total Capacity {W} Nominal Sensible Capacity {W} Nominal Latent Capacity {W} Nominal Sensible Heat Ratio Nominal Coil UA Value {W/C} Nominal Coil Surface Area {m2}
1 Coil:Cooling:Water ROOM_1_FLR_3 FAN COIL COOLING COIL 19045.41 14862.37 4183.04 0.78 2098.68 21.29
2 Coil:Cooling:Water ROOM_2_FLR_3 FAN COIL COOLING COIL 19222.62 15003.60 4219.01 0.78 2118.25 21.48
3 Coil:Cooling:Water ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL 106764.62 83705.91 23058.71 0.78 11771.74 119.40
4 Coil:Cooling:Water ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL 127516.44 99143.27 28373.17 0.78 14045.78 142.46
5 Coil:Cooling:Water ROOM_5_FLR_3 FAN COIL COOLING COIL 17226.59 13413.16 3813.43 0.78 1897.78 19.25
6 Coil:Cooling:Water ROOM_6_FLR_3 FAN COIL COOLING COIL 17364.64 13522.84 3841.80 0.78 1913.02 19.40
7 Coil:Cooling:Water ROOM_1_FLR_6 FAN COIL COOLING COIL 5073.53 3964.00 1109.53 0.78 559.15 5.67
8 Coil:Cooling:Water ROOM_2_FLR_6 FAN COIL COOLING COIL 5116.16 3998.03 1118.13 0.78 563.86 5.72
9 Coil:Cooling:Water ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL 21413.41 16640.84 4772.57 0.78 2358.57 23.92
10 Coil:Cooling:Water VAV WITH REHEAT COOLING COIL 715419.77 456961.22 258458.55 0.64 89905.40 911.87
11 Coil:Cooling:Water FLR_3_DOAS COOLING COIL 67803.65 43510.62 24293.03 0.64 8145.92 82.62


Chiller Standard Rating Information

Component Type Component Name IPLV in SI Units {W/W} IPLV in IP Units {Btu/W-h}
1 Chiller:Electric:EIR COOLSYS1 CHILLER1 3.72 12.68


Zone Surfaces

Zone Name # Surfaces
1 BASEMENT 14
2 RETAIL_1_FLR_1 8
3 RETAIL_2_FLR_1 8
4 MECH_FLR_1 7
5 STORAGE_FLR_1 8
6 LAUNDRY_FLR_1 8
7 CAFE_FLR_1 10
8 LOBBY_FLR_1 22
9 ROOM_1_FLR_3 9
10 ROOM_2_FLR_3 9
11 ROOM_3_MULT19_FLR_3 8
12 ROOM_4_MULT19_FLR_3 8
13 ROOM_5_FLR_3 9
14 ROOM_6_FLR_3 9
15 CORRIDOR_FLR_3 25
16 ROOM_1_FLR_6 9
17 ROOM_2_FLR_6 9
18 ROOM_3_MULT9_FLR_6 8
19 BANQUET_FLR_6 8
20 DINING_FLR_6 8
21 KITCHEN_FLR_6 12
22 CORRIDOR_FLR_6 19


HeatTransfer Surface

Surface Name Surface Class Base Surface Heat Transfer Algorithm Construction Nominal U (w/o film coefs) {W/m2-K} Nominal U (with film coefs) {W/m2-K} Solar Diffusing Area (Net) {m2} Area (Gross) {m2} Area (Sunlit Calc) {m2} Azimuth {deg} Tilt {deg} ~Width {m} ~Height {m} Reveal {m} ExtBoundCondition ExtConvCoeffCalc IntConvCoeffCalc SunExposure WindExposure ViewFactorToGround ViewFactorToSky ViewFactorToGround-IR ViewFactorToSky-IR #Sides
1 BASEMENT_WALL_NORTH Wall   CTF - ConductionTransferFunction BASEMENT_WALL_NORTH_CFACTOR 0.940 0.824   211.13 211.13 211.13 0.00 90.00 86.56 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
2 BASEMENT_WALL_EAST Wall   CTF - ConductionTransferFunction BASEMENT_WALL_EAST_CFACTOR 0.940 0.824   55.76 55.76 55.76 90.00 90.00 22.86 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
3 BASEMENT_WALL_SOUTH Wall   CTF - ConductionTransferFunction BASEMENT_WALL_SOUTH_CFACTOR 0.940 0.824   211.13 211.13 211.13 180.00 90.00 86.56 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
4 BASEMENT_WALL_WEST Wall   CTF - ConductionTransferFunction BASEMENT_WALL_WEST_CFACTOR 0.940 0.824   55.76 55.76 55.76 270.00 90.00 22.86 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
5 BASEMENT_FLOOR Floor   CTF - ConductionTransferFunction BASEMENT_FLOOR 2.705 1.632   1978.83 1978.83 1978.83 0.00 180.00 86.56 22.86 0.00 BASEMENT_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
6 BASEMENT_CEILING_1 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.412 0.383   67.07 67.07 67.07 180.00 0.00 11.58 5.79 0.00 RETAIL_1_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
7 BASEMENT_CEILING_2 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.412 0.383   77.67 77.67 77.67 180.00 0.00 11.58 6.71 0.00 RETAIL_2_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
8 BASEMENT_CEILING_3 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.412 0.383   164.24 164.24 164.24 180.00 0.00 15.85 10.36 0.00 MECH_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
9 BASEMENT_CEILING_4 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.412 0.383   94.76 94.76 94.76 180.00 0.00 9.14 10.36 0.00 STORAGE_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
10 BASEMENT_CEILING_5 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.412 0.383   78.04 78.04 78.04 180.00 0.00 4.57 17.07 0.00 LAUNDRY_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
11 BASEMENT_CEILING_6 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.412 0.383   188.86 188.86 188.86 180.00 0.00 32.61 5.79 0.00 CAFE_FLR_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
12 BASEMENT_CEILING_7 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.412 0.383   1088.56 1088.56 1088.56 180.00 0.00 32.99 32.99 0.00 LOBBY_FLR_1_FLOOR_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 6
13 BASEMENT_CEILING_8 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.412 0.383   219.63 219.63 219.63 90.00 0.00 14.82 14.82 0.00 LOBBY_FLR_1_FLOOR_2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 6
14 BASEMENT_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   3957.66 3957.66 3957.66 0.00 90.00 3957.66 1.00 0.00 BASEMENT_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
15 RETAIL_1_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.214 1.028   22.63 45.89 22.63 180.00 90.00 11.58 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
16 RETAIL_1_FLR_1_WALL_SOUTH_WINDOW Window RETAIL_1_FLR_1_WALL_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.5119_SHGC_0.25 N/A 2.910 No 23.26 23.26 23.26 180.00 90.00 10.92 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
17 RETAIL_1_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.214 1.028   22.95 22.95 22.95 270.00 90.00 5.79 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
18 RETAIL_1_FLR_1_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   45.89 45.89 45.89 0.00 90.00 11.58 3.96 0.00 RETAIL_2_FLR_1_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
19 RETAIL_1_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.95 22.95 22.95 90.00 90.00 5.79 3.96 0.00 LOBBY_FLR_1_WALL_2_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
20 RETAIL_1_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.412 0.375   67.07 67.07 67.07 0.00 180.00 11.58 5.79 0.00 BASEMENT_CEILING_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
21 RETAIL_1_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.283 0.269   67.07 67.07 67.07 180.00 0.00 11.58 5.79 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 7.62E-002 0.92 4
22 RETAIL_1_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   134.14 134.14 134.14 0.00 90.00 134.14 1.00 0.00 RETAIL_1_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
23 RETAIL_2_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.214 1.028   24.62 26.57 24.62 270.00 90.00 6.71 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
24 RETAIL_2_FLR_1_WALL_WEST_DOOR Door RETAIL_2_FLR_1_WALL_WEST CTF - ConductionTransferFunction SWINGING DOOR_CON 3.464 3.464   1.95 1.95 1.95 270.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
25 RETAIL_2_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   45.89 45.89 45.89 180.00 90.00 11.58 3.96 0.00 RETAIL_1_FLR_1_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
26 RETAIL_2_FLR_1_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   45.89 45.89 45.89 0.00 90.00 11.58 3.96 0.00 LOBBY_FLR_1_WALL_2_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
27 RETAIL_2_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.57 26.57 26.57 90.00 90.00 6.71 3.96 0.00 LOBBY_FLR_1_WALL_3_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
28 RETAIL_2_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.412 0.375   77.67 77.67 77.67 0.00 180.00 11.58 6.71 0.00 BASEMENT_CEILING_2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
29 RETAIL_2_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.412 0.383   77.67 77.67 77.67 180.00 0.00 11.58 6.71 0.00 RETAIL_2_FLR_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
30 RETAIL_2_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   155.34 155.34 155.34 0.00 90.00 155.34 1.00 0.00 RETAIL_2_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
31 MECH_FLR_1_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.214 1.028   62.80 62.80 62.80 0.00 90.00 15.85 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
32 MECH_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 90.00 90.00 10.36 3.96 0.00 STORAGE_FLR_1_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
33 MECH_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   62.80 62.80 62.80 180.00 90.00 15.85 3.96 0.00 LOBBY_FLR_1_WALL_3_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
34 MECH_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 270.00 90.00 10.36 3.96 0.00 LOBBY_FLR_1_WALL_1_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
35 MECH_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.412 0.375   164.24 164.24 164.24 0.00 180.00 15.85 10.36 0.00 BASEMENT_CEILING_3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
36 MECH_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.412 0.383   164.24 164.24 164.24 180.00 0.00 15.85 10.36 0.00 MECH_FLR_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
37 MECH_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   328.49 328.49 328.49 0.00 90.00 328.49 1.00 0.00 MECH_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
38 STORAGE_FLR_1_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.214 1.028   28.80 36.23 28.80 0.00 90.00 9.14 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
39 STORAGE_FLR_1_WALL_NORTH_ROLLDOOR Door STORAGE_FLR_1_WALL_NORTH CTF - ConductionTransferFunction OVERHEAD DOOR_CON 1.198 1.198   7.43 7.43 7.43 0.00 90.00 3.05 2.44 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
40 STORAGE_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 90.00 90.00 10.36 3.96 0.00 LOBBY_FLR_1_WALL_4_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
41 STORAGE_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   36.23 36.23 36.23 180.00 90.00 9.14 3.96 0.00 LOBBY_FLR_1_WALL_4_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
42 STORAGE_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 270.00 90.00 10.36 3.96 0.00 MECH_FLR_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
43 STORAGE_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.412 0.375   94.76 94.76 94.76 0.00 180.00 9.14 10.36 0.00 BASEMENT_CEILING_4 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
44 STORAGE_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.412 0.383   94.76 94.76 94.76 180.00 0.00 9.14 10.36 0.00 STORAGE_FLR_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
45 STORAGE_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   189.52 189.52 189.52 0.00 90.00 189.52 1.00 0.00 STORAGE_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
46 LAUNDRY_FLR_1_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.214 1.028   18.12 18.12 18.12 0.00 90.00 4.57 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
47 LAUNDRY_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.214 1.028   65.68 67.63 65.68 90.00 90.00 17.07 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
48 LAUNDRY_FLR_1_WALL_EAST_DOOR Door LAUNDRY_FLR_1_WALL_EAST CTF - ConductionTransferFunction SWINGING DOOR_CON 3.464 3.464   1.95 1.95 1.95 90.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
49 LAUNDRY_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   18.12 18.12 18.12 180.00 90.00 4.57 3.96 0.00 CAFE_FLR_1_WALL_2_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
50 LAUNDRY_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   67.63 67.63 67.63 270.00 90.00 17.07 3.96 0.00 LOBBY_FLR_1_WALL_3_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
51 LAUNDRY_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.412 0.375   78.04 78.04 78.04 0.00 180.00 4.57 17.07 0.00 BASEMENT_CEILING_5 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
52 LAUNDRY_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.412 0.383   78.04 78.04 78.04 180.00 0.00 4.57 17.07 0.00 LAUNDRY_FLR_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
53 LAUNDRY_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   156.08 156.08 156.08 0.00 90.00 156.08 1.00 0.00 LAUNDRY_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
54 CAFE_FLR_1_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.214 1.028   21.00 22.95 21.00 90.00 90.00 5.79 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
55 CAFE_FLR_1_WALL_EAST_DOOR Door CAFE_FLR_1_WALL_EAST CTF - ConductionTransferFunction SWINGING DOOR_CON 3.464 3.464   1.95 1.95 1.95 90.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
56 CAFE_FLR_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.214 1.028   63.73 129.23 63.73 180.00 90.00 32.61 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
57 CAFE_FLR_1_WALL_SOUTH_WINDOW Window CAFE_FLR_1_WALL_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.5119_SHGC_0.25 N/A 2.910 No 65.50 65.50 65.50 180.00 90.00 30.75 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
58 CAFE_FLR_1_WALL_1_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.11 111.11 111.11 0.00 90.00 28.04 3.96 0.00 LOBBY_FLR_1_WALL_3_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
59 CAFE_FLR_1_WALL_2_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   18.12 18.12 18.12 0.00 90.00 4.57 3.96 0.00 LAUNDRY_FLR_1_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
60 CAFE_FLR_1_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.95 22.95 22.95 270.00 90.00 5.79 3.96 0.00 LOBBY_FLR_1_WALL_2_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
61 CAFE_FLR_1_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.412 0.375   188.86 188.86 188.86 0.00 180.00 32.61 5.79 0.00 BASEMENT_CEILING_6 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
62 CAFE_FLR_1_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.283 0.269   188.86 188.86 188.86 180.00 0.00 32.61 5.79 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 3.86E-002 0.96 4
63 CAFE_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   377.72 377.72 377.72 0.00 90.00 377.72 1.00 0.00 CAFE_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
64 LOBBY_FLR_1_WALL_1_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.214 1.028   209.87 213.77 209.87 0.00 90.00 53.95 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
65 LOBBY_FLR_1_WALL_1_NORTH_DOOR1 Door LOBBY_FLR_1_WALL_1_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.464 3.464   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
66 LOBBY_FLR_1_WALL_1_NORTH_DOOR2 Door LOBBY_FLR_1_WALL_1_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.464 3.464   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
67 LOBBY_FLR_1_WALL_2_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.214 1.028   12.08 12.08 12.08 0.00 90.00 3.05 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
68 LOBBY_FLR_1_WALL_1_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.214 1.028   82.79 167.88 82.79 180.00 90.00 42.37 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
69 LOBBY_FLR_1_WALL_SOUTH_WINDOW Window LOBBY_FLR_1_WALL_1_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.5119_SHGC_0.25 N/A 2.910 No 85.08 85.08 85.08 180.00 90.00 39.95 2.13 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
70 LOBBY_FLR_1_WALL_1_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.214 1.028   41.06 41.06 41.06 270.00 90.00 10.36 3.96 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
71 LOBBY_FLR_1_WALL_2_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   45.89 45.89 45.89 180.00 90.00 11.58 3.96 0.00 RETAIL_2_FLR_1_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
72 LOBBY_FLR_1_WALL_3_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   111.11 111.11 111.11 180.00 90.00 28.04 3.96 0.00 CAFE_FLR_1_WALL_1_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
73 LOBBY_FLR_1_WALL_2_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.95 22.95 22.95 270.00 90.00 5.79 3.96 0.00 RETAIL_1_FLR_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
74 LOBBY_FLR_1_WALL_3_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.57 26.57 26.57 270.00 90.00 6.71 3.96 0.00 RETAIL_2_FLR_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
75 LOBBY_FLR_1_WALL_4_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 270.00 90.00 10.36 3.96 0.00 STORAGE_FLR_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
76 LOBBY_FLR_1_WALL_3_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   62.80 62.80 62.80 0.00 90.00 15.85 3.96 0.00 MECH_FLR_1_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
77 LOBBY_FLR_1_WALL_4_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   36.23 36.23 36.23 0.00 90.00 9.14 3.96 0.00 STORAGE_FLR_1_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
78 LOBBY_FLR_1_WALL_1_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   41.06 41.06 41.06 90.00 90.00 10.36 3.96 0.00 MECH_FLR_1_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
79 LOBBY_FLR_1_WALL_2_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   22.95 22.95 22.95 90.00 90.00 5.79 3.96 0.00 CAFE_FLR_1_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
80 LOBBY_FLR_1_WALL_3_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   67.63 67.63 67.63 90.00 90.00 17.07 3.96 0.00 LAUNDRY_FLR_1_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
81 LOBBY_FLR_1_FLOOR_1 Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.412 0.375   1088.56 1088.56 1088.56 180.00 180.00 32.99 32.99 0.00 BASEMENT_CEILING_7 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 6
82 LOBBY_FLR_1_FLOOR_2 Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.412 0.375   219.63 219.63 219.63 90.00 180.00 14.82 14.82 0.00 BASEMENT_CEILING_8 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 6
83 LOBBY_FLR_1_CEILING_1 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.412 0.383   1062.83 1062.83 1062.83 270.00 0.00 32.60 32.60 0.00 LOBBY_FLR_1_CEILING_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 10
84 LOBBY_FLR_1_CEILING_2 Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.283 0.269   245.35 245.35 245.35 180.00 0.00 42.37 5.79 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 4.22E-003 1.00 4
85 LOBBY_FLR_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   2616.37 2616.37 2616.37 0.00 90.00 2616.37 1.00 0.00 LOBBY_FLR_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
86 ROOM_1_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.530 1.245   9.34 13.94 9.34 180.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
87 ROOM_1_FLR_3_WALL_SOUTH_WINDOW Window ROOM_1_FLR_3_WALL_SOUTH Window5 Detailed Fenestration RESWINDOW_U_0.5119_SHGC_0.25 N/A 2.910 No 4.60 4.60 4.60 180.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
88 ROOM_1_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.530 1.245   17.43 26.01 17.43 270.00 90.00 8.54 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
89 ROOM_1_FLR_3_WALL_WEST_WINDOW Window ROOM_1_FLR_3_WALL_WEST Window5 Detailed Fenestration RESWINDOW_U_0.5119_SHGC_0.25 N/A 2.910 No 8.58 8.58 8.58 270.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
90 ROOM_1_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 0.00 90.00 4.57 3.05 0.00 ROOM_2_FLR_3_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
91 ROOM_1_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.54 3.05 0.00 CORRIDOR_FLR_3_WALL_3_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
92 ROOM_1_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.412 0.375   39.02 39.02 39.02 0.00 180.00 4.57 8.54 0.00 ROOM_1_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
93 ROOM_1_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.412 0.383   39.02 39.02 39.02 180.00 0.00 4.57 8.54 0.00 ROOM_1_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
94 ROOM_1_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.04 78.04 78.04 0.00 90.00 78.04 1.00 0.00 ROOM_1_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
95 ROOM_2_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.530 1.245   9.34 13.94 9.34 0.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
96 ROOM_2_FLR_3_WALL_NORTH_WINDOW Window ROOM_2_FLR_3_WALL_NORTH Window5 Detailed Fenestration RESWINDOW_U_0.5119_SHGC_0.25 N/A 2.910 No 4.60 4.60 4.60 0.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
97 ROOM_2_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.530 1.245   17.43 26.01 17.43 270.00 90.00 8.53 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
98 ROOM_2_FLR_3_WALL_WEST_WINDOW Window ROOM_2_FLR_3_WALL_WEST Window5 Detailed Fenestration RESWINDOW_U_0.5119_SHGC_0.25 N/A 2.910 No 8.58 8.58 8.58 270.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
99 ROOM_2_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.53 3.05 0.00 CORRIDOR_FLR_3_WALL_4_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
100 ROOM_2_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 180.00 90.00 4.57 3.05 0.00 ROOM_1_FLR_3_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
101 ROOM_2_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.412 0.375   39.02 39.02 39.02 0.00 180.00 4.57 8.53 0.00 ROOM_2_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
102 ROOM_2_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.412 0.383   39.02 39.02 39.02 180.00 0.00 4.57 8.53 0.00 ROOM_2_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
103 ROOM_2_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.03 78.03 78.03 0.00 90.00 78.03 1.00 0.00 ROOM_2_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
104 ROOM_3_MULT19_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.530 1.245   7.47 11.15 7.47 180.00 90.00 3.66 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
105 ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW Window ROOM_3_MULT19_FLR_3_WALL_SOUTH Window5 Detailed Fenestration RESWINDOW_U_0.5119_SHGC_0.25 N/A 2.910 No 3.68 3.68 3.68 180.00 90.00 3.02 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
106 ROOM_3_MULT19_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 0.00 90.00 3.66 3.05 0.00 ROOM_3_MULT19_FLR_3_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
107 ROOM_3_MULT19_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 90.00 90.00 6.71 3.05 0.00 ROOM_3_MULT19_FLR_3_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
108 ROOM_3_MULT19_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 270.00 90.00 6.71 3.05 0.00 ROOM_3_MULT19_FLR_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
109 ROOM_3_MULT19_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.412 0.375   24.52 24.52 24.52 0.00 180.00 3.66 6.71 0.00 ROOM_3_MULT19_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
110 ROOM_3_MULT19_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.412 0.383   24.52 24.52 24.52 180.00 0.00 3.66 6.71 0.00 ROOM_3_MULT19_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
111 ROOM_3_MULT19_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   49.05 49.05 49.05 0.00 90.00 49.05 1.00 0.00 ROOM_3_MULT19_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
112 ROOM_4_MULT19_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.530 1.245   7.47 11.15 7.47 0.00 90.00 3.66 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
113 ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW Window ROOM_4_MULT19_FLR_3_WALL_NORTH Window5 Detailed Fenestration RESWINDOW_U_0.5119_SHGC_0.25 N/A 2.910 No 3.68 3.68 3.68 0.00 90.00 3.02 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
114 ROOM_4_MULT19_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 90.00 90.00 6.71 3.05 0.00 ROOM_4_MULT19_FLR_3_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
115 ROOM_4_MULT19_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 180.00 90.00 3.66 3.05 0.00 ROOM_4_MULT19_FLR_3_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
116 ROOM_4_MULT19_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 270.00 90.00 6.71 3.05 0.00 ROOM_4_MULT19_FLR_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
117 ROOM_4_MULT19_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.412 0.375   24.53 24.53 24.53 0.00 180.00 3.66 6.71 0.00 ROOM_4_MULT19_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
118 ROOM_4_MULT19_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.412 0.383   24.53 24.53 24.53 180.00 0.00 3.66 6.71 0.00 ROOM_4_MULT19_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
119 ROOM_4_MULT19_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   49.06 49.06 49.06 0.00 90.00 49.06 1.00 0.00 ROOM_4_MULT19_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
120 ROOM_5_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.530 1.245   17.43 26.01 17.43 90.00 90.00 8.54 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
121 ROOM_5_FLR_3_WALL_EAST_WINDOW Window ROOM_5_FLR_3_WALL_EAST Window5 Detailed Fenestration RESWINDOW_U_0.5119_SHGC_0.25 N/A 2.910 No 8.58 8.58 8.58 90.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
122 ROOM_5_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.530 1.245   9.34 13.94 9.34 180.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
123 ROOM_5_FLR_3_WALL_SOUTH_WINDOW Window ROOM_5_FLR_3_WALL_SOUTH Window5 Detailed Fenestration RESWINDOW_U_0.5119_SHGC_0.25 N/A 2.910 No 4.60 4.60 4.60 180.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
124 ROOM_5_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 0.00 90.00 4.57 3.05 0.00 ROOM_6_FLR_3_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
125 ROOM_5_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 270.00 90.00 8.54 3.05 0.00 CORRIDOR_FLR_3_WALL_3_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
126 ROOM_5_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.412 0.375   39.02 39.02 39.02 0.00 180.00 4.57 8.54 0.00 ROOM_5_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
127 ROOM_5_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.412 0.383   39.02 39.02 39.02 180.00 0.00 4.57 8.54 0.00 ROOM_5_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
128 ROOM_5_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.04 78.04 78.04 0.00 90.00 78.04 1.00 0.00 ROOM_5_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
129 ROOM_6_FLR_3_WALL_NORTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.530 1.245   9.34 13.94 9.34 0.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
130 ROOM_6_FLR_3_WALL_NORTH_WINDOW Window ROOM_6_FLR_3_WALL_NORTH Window5 Detailed Fenestration RESWINDOW_U_0.5119_SHGC_0.25 N/A 2.910 No 4.60 4.60 4.60 0.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
131 ROOM_6_FLR_3_WALL_EAST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_MID 1.530 1.245   17.43 26.01 17.43 90.00 90.00 8.53 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
132 ROOM_6_FLR_3_WALL_EAST_WINDOW Window ROOM_6_FLR_3_WALL_EAST Window5 Detailed Fenestration RESWINDOW_U_0.5119_SHGC_0.25 N/A 2.910 No 8.58 8.58 8.58 90.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
133 ROOM_6_FLR_3_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 180.00 90.00 4.57 3.05 0.00 ROOM_5_FLR_3_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
134 ROOM_6_FLR_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 270.00 90.00 8.53 3.05 0.00 CORRIDOR_FLR_3_WALL_4_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
135 ROOM_6_FLR_3_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.412 0.375   39.02 39.02 39.02 0.00 180.00 4.57 8.53 0.00 ROOM_6_FLR_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
136 ROOM_6_FLR_3_CEILING Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.412 0.383   39.02 39.02 39.02 180.00 0.00 4.57 8.53 0.00 ROOM_6_FLR_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
137 ROOM_6_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.03 78.03 78.03 0.00 90.00 78.03 1.00 0.00 ROOM_6_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
138 CORRIDOR_FLR_3_WALL_1_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.530 1.245   11.83 17.65 11.83 0.00 90.00 5.79 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
139 CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW Window CORRIDOR_FLR_3_WALL_1_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.5119_SHGC_0.25 N/A 2.910 No 5.82 5.82 5.82 0.00 90.00 4.78 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
140 CORRIDOR_FLR_3_WALL_2_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.530 1.245   4.35 6.50 4.35 0.00 90.00 2.13 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
141 CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW Window CORRIDOR_FLR_3_WALL_2_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.5119_SHGC_0.25 N/A 2.910 No 2.15 2.15 2.15 0.00 90.00 1.76 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
142 CORRIDOR_FLR_3_WALL_1_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.530 1.245   4.36 6.50 4.36 180.00 90.00 2.13 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
143 CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW Window CORRIDOR_FLR_3_WALL_1_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.5119_SHGC_0.25 N/A 2.910 No 2.15 2.15 2.15 180.00 90.00 1.76 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
144 CORRIDOR_FLR_3_WALL_2_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.530 1.245   11.83 17.65 11.83 180.00 90.00 5.79 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
145 CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW Window CORRIDOR_FLR_3_WALL_2_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.5119_SHGC_0.25 N/A 2.910 No 5.82 5.82 5.82 180.00 90.00 4.78 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
146 CORRIDOR_FLR_3_WALL_3_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   211.82 211.82 211.82 0.00 90.00 69.50 3.05 0.00 CORRIDOR_FLR_3_WALL_3_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
147 CORRIDOR_FLR_3_WALL_1_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 90.00 90.00 6.71 3.05 0.00 CORRIDOR_FLR_3_WALL_1_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
148 CORRIDOR_FLR_3_WALL_2_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 90.00 90.00 6.71 3.05 0.00 CORRIDOR_FLR_3_WALL_2_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
149 CORRIDOR_FLR_3_WALL_3_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.54 3.05 0.00 ROOM_5_FLR_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
150 CORRIDOR_FLR_3_WALL_4_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.53 3.05 0.00 ROOM_6_FLR_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
151 CORRIDOR_FLR_3_WALL_3_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   211.82 211.82 211.82 180.00 90.00 69.49 3.05 0.00 CORRIDOR_FLR_3_WALL_3_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
152 CORRIDOR_FLR_3_WALL_1_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 270.00 90.00 6.71 3.05 0.00 CORRIDOR_FLR_3_WALL_1_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
153 CORRIDOR_FLR_3_WALL_2_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 270.00 90.00 6.71 3.05 0.00 CORRIDOR_FLR_3_WALL_2_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
154 CORRIDOR_FLR_3_WALL_3_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 270.00 90.00 8.54 3.05 0.00 ROOM_1_FLR_3_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
155 CORRIDOR_FLR_3_WALL_4_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 270.00 90.00 8.53 3.05 0.00 ROOM_2_FLR_3_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
156 CORRIDOR_FLR_3_FLOOR_1 Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.412 0.375   74.32 74.32 74.32 180.00 180.00 8.62 8.62 0.00 CORRIDOR_FLR_3_FLOOR_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 6
157 CORRIDOR_FLR_3_FLOOR_2 Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.412 0.375   240.77 240.77 240.77 270.00 180.00 3.66 65.84 0.00 CORRIDOR_FLR_3_FLOOR_2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
158 CORRIDOR_FLR_3_FLOOR_3 Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.412 0.375   74.32 74.32 74.32 90.00 180.00 8.62 8.62 0.00 CORRIDOR_FLR_3_FLOOR_3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 6
159 CORRIDOR_FLR_3_CEILING_1 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.412 0.383   74.32 74.32 74.32 90.00 0.00 8.62 8.62 0.00 CORRIDOR_FLR_3_CEILING_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 6
160 CORRIDOR_FLR_3_CEILING_2 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.412 0.383   240.77 240.77 240.77 90.00 0.00 3.66 65.84 0.00 CORRIDOR_FLR_3_CEILING_2 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
161 CORRIDOR_FLR_3_CEILING_3 Roof   CTF - ConductionTransferFunction NONRES_FLOOR_CEILING 0.412 0.383   74.32 74.32 74.32 90.00 0.00 8.62 8.62 0.00 CORRIDOR_FLR_3_CEILING_3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 6
162 CORRIDOR_FLR_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   778.81 778.81 778.81 0.00 90.00 778.81 1.00 0.00 CORRIDOR_FLR_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
163 ROOM_1_FLR_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_TOP 1.605 1.294   9.34 13.94 9.34 180.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
164 ROOM_1_FLR_6_WALL_SOUTH_WINDOW Window ROOM_1_FLR_6_WALL_SOUTH Window5 Detailed Fenestration RESWINDOW_U_0.5119_SHGC_0.25 N/A 2.910 No 4.60 4.60 4.60 180.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
165 ROOM_1_FLR_6_WALL_WEST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_TOP 1.605 1.294   17.43 26.01 17.43 270.00 90.00 8.54 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
166 ROOM_1_FLR_6_WALL_WEST_WINDOW Window ROOM_1_FLR_6_WALL_WEST Window5 Detailed Fenestration RESWINDOW_U_0.5119_SHGC_0.25 N/A 2.910 No 8.58 8.58 8.58 270.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
167 ROOM_1_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 0.00 90.00 4.57 3.05 0.00 ROOM_2_FLR_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
168 ROOM_1_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.54 3.05 0.00 ROOM_1_FLR_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
169 ROOM_1_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.412 0.375   39.02 39.02 39.02 0.00 180.00 4.57 8.54 0.00 ROOM_1_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
170 ROOM_1_FLR_6_CEILING Roof   CTF - ConductionTransferFunction RES_ROOF 0.283 0.269   39.02 39.02 39.02 180.00 0.00 4.57 8.54 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
171 ROOM_1_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.04 78.04 78.04 0.00 90.00 78.04 1.00 0.00 ROOM_1_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
172 ROOM_2_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_TOP 1.605 1.294   9.34 13.94 9.34 0.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
173 ROOM_2_FLR_6_WALL_NORTH_WINDOW Window ROOM_2_FLR_6_WALL_NORTH Window5 Detailed Fenestration RESWINDOW_U_0.5119_SHGC_0.25 N/A 2.910 No 4.60 4.60 4.60 0.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
174 ROOM_2_FLR_6_WALL_WEST Wall   CTF - ConductionTransferFunction RES_EXT_WALL_TOP 1.605 1.294   17.43 26.01 17.43 270.00 90.00 8.53 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
175 ROOM_2_FLR_6_WALL_WEST_WINDOW Window ROOM_2_FLR_6_WALL_WEST Window5 Detailed Fenestration RESWINDOW_U_0.5119_SHGC_0.25 N/A 2.910 No 8.58 8.58 8.58 270.00 90.00 7.04 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
176 ROOM_2_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   26.01 26.01 26.01 90.00 90.00 8.53 3.05 0.00 ROOM_2_FLR_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
177 ROOM_2_FLR_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   13.94 13.94 13.94 180.00 90.00 4.57 3.05 0.00 ROOM_1_FLR_6_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
178 ROOM_2_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.412 0.375   39.02 39.02 39.02 0.00 180.00 4.57 8.53 0.00 ROOM_2_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
179 ROOM_2_FLR_6_CEILING Roof   CTF - ConductionTransferFunction RES_ROOF 0.283 0.269   39.02 39.02 39.02 180.00 0.00 4.57 8.53 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
180 ROOM_2_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   78.03 78.03 78.03 0.00 90.00 78.03 1.00 0.00 ROOM_2_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
181 ROOM_3_MULT9_FLR_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction RES_EXT_WALL_TOP 1.605 1.294   13.70 20.44 13.70 180.00 90.00 6.71 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
182 ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW Window ROOM_3_MULT9_FLR_6_WALL_SOUTH Window5 Detailed Fenestration RESWINDOW_U_0.5119_SHGC_0.25 N/A 2.910 No 6.74 6.74 6.74 180.00 90.00 5.53 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
183 ROOM_3_MULT9_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 0.00 90.00 6.71 3.05 0.00 ROOM_3_MULT9_FLR_6_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
184 ROOM_3_MULT9_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 90.00 90.00 3.66 3.05 0.00 ROOM_3_MULT9_FLR_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
185 ROOM_3_MULT9_FLR_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 270.00 90.00 3.66 3.05 0.00 ROOM_3_MULT9_FLR_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
186 ROOM_3_MULT9_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.412 0.375   24.53 24.53 24.53 0.00 180.00 6.71 3.66 0.00 ROOM_3_MULT9_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
187 ROOM_3_MULT9_FLR_6_CEILING Roof   CTF - ConductionTransferFunction RES_ROOF 0.283 0.269   24.53 24.53 24.53 180.00 0.00 6.71 3.66 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
188 ROOM_3_MULT9_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   49.06 49.06 49.06 0.00 90.00 49.06 1.00 0.00 ROOM_3_MULT9_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
189 BANQUET_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.605 1.294   65.36 97.55 65.36 0.00 90.00 32.00 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
190 BANQUET_FLR_6_WALL_NORTH_WINDOW Window BANQUET_FLR_6_WALL_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.5119_SHGC_0.25 N/A 2.910 No 32.19 32.19 32.19 0.00 90.00 26.40 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
191 BANQUET_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 90.00 90.00 10.36 3.05 0.00 CORRIDOR_FLR_6_WALL_3_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
192 BANQUET_FLR_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   97.55 97.55 97.55 180.00 90.00 32.00 3.05 0.00 CORRIDOR_FLR_6_WALL_3_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
193 BANQUET_FLR_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 270.00 90.00 10.36 3.05 0.00 CORRIDOR_FLR_6_WALL_1_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
194 BANQUET_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.412 0.375   331.66 331.66 331.66 0.00 180.00 32.00 10.36 0.00 BANQUET_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
195 BANQUET_FLR_6_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.283 0.269   331.66 331.66 331.66 180.00 0.00 32.00 10.36 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
196 BANQUET_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   663.31 663.31 663.31 0.00 90.00 663.31 1.00 0.00 BANQUET_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
197 DINING_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.605 1.294   65.36 97.55 65.36 0.00 90.00 32.00 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
198 DINING_FLR_6_WALL_NORTH_WINDOW Window DINING_FLR_6_WALL_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.5119_SHGC_0.25 N/A 2.910 No 32.19 32.19 32.19 0.00 90.00 26.40 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
199 DINING_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 90.00 90.00 10.36 3.05 0.00 KITCHEN_FLR_6_WALL_2_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
200 DINING_FLR_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   97.55 97.55 97.55 180.00 90.00 32.00 3.05 0.00 DINING_FLR_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
201 DINING_FLR_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 270.00 90.00 10.36 3.05 0.00 CORRIDOR_FLR_6_WALL_2_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
202 DINING_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.412 0.375   331.66 331.66 331.66 0.00 180.00 32.00 10.36 0.00 DINING_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
203 DINING_FLR_6_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.283 0.269   331.66 331.66 331.66 180.00 0.00 32.00 10.36 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
204 DINING_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   663.31 663.31 663.31 0.00 90.00 663.31 1.00 0.00 DINING_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
205 KITCHEN_FLR_6_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.605 1.294   16.77 21.37 16.77 0.00 90.00 7.01 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
206 KITCHEN_FLR_6_WALL_NORTH_WINDOW Window KITCHEN_FLR_6_WALL_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.5119_SHGC_0.25 N/A 2.910 No 4.60 4.60 4.60 0.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
207 KITCHEN_FLR_6_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.605 1.294   34.86 52.03 34.86 90.00 90.00 17.07 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
208 KITCHEN_FLR_6_WALL_EAST_WINDOW Window KITCHEN_FLR_6_WALL_EAST Window5 Detailed Fenestration NONRESWINDOW_U_0.5119_SHGC_0.25 N/A 2.910 No 17.17 17.17 17.17 90.00 90.00 14.08 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
209 KITCHEN_FLR_6_WALL_1_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.605 1.294   9.34 13.94 9.34 180.00 90.00 4.57 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
210 KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW Window KITCHEN_FLR_6_WALL_1_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.5119_SHGC_0.25 N/A 2.910 No 4.60 4.60 4.60 180.00 90.00 3.77 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
211 KITCHEN_FLR_6_WALL_2_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   7.43 7.43 7.43 180.00 90.00 2.44 3.05 0.00 KITCHEN_FLR_6_WALL_2_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
212 KITCHEN_FLR_6_WALL_1_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 270.00 90.00 6.71 3.05 0.00 CORRIDOR_FLR_6_WALL_3_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
213 KITCHEN_FLR_6_WALL_2_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 270.00 90.00 10.36 3.05 0.00 DINING_FLR_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
214 KITCHEN_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.412 0.375   103.30 103.30 103.30 180.00 180.00 10.16 10.16 0.00 KITCHEN_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 6
215 KITCHEN_FLR_6_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.283 0.269   103.30 103.30 103.30 270.00 0.00 10.16 10.16 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 6
216 KITCHEN_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   206.61 206.61 206.61 0.00 90.00 206.61 1.00 0.00 KITCHEN_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
217 CORRIDOR_FLR_6_WALL_1_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.605 1.294   11.83 17.65 11.83 0.00 90.00 5.79 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
218 CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW Window CORRIDOR_FLR_6_WALL_1_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.5119_SHGC_0.25 N/A 2.910 No 5.82 5.82 5.82 0.00 90.00 4.78 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
219 CORRIDOR_FLR_6_WALL_2_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.605 1.294   10.58 15.79 10.58 0.00 90.00 5.18 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
220 CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW Window CORRIDOR_FLR_6_WALL_2_NORTH Window5 Detailed Fenestration NONRESWINDOW_U_0.5119_SHGC_0.25 N/A 2.910 No 5.21 5.21 5.21 0.00 90.00 4.27 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
221 CORRIDOR_FLR_6_WALL_2_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.605 1.294   34.86 52.03 34.86 180.00 90.00 17.07 3.05 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
222 CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW Window CORRIDOR_FLR_6_WALL_2_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.5119_SHGC_0.25 N/A 2.910 No 17.17 17.17 17.17 180.00 90.00 14.08 1.22 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
223 CORRIDOR_FLR_6_WALL_3_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   97.55 97.55 97.55 0.00 90.00 32.00 3.05 0.00 BANQUET_FLR_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
224 CORRIDOR_FLR_6_WALL_4_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   104.98 104.98 104.98 0.00 90.00 34.44 3.05 0.00 CORRIDOR_FLR_6_WALL_4_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
225 CORRIDOR_FLR_6_WALL_1_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   183.95 183.95 183.95 180.00 90.00 60.35 3.05 0.00 CORRIDOR_FLR_6_WALL_1_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
226 CORRIDOR_FLR_6_WALL_1_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   11.15 11.15 11.15 270.00 90.00 3.66 3.05 0.00 CORRIDOR_FLR_6_WALL_1_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
227 CORRIDOR_FLR_6_WALL_2_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   40.88 40.88 40.88 270.00 90.00 13.41 3.05 0.00 CORRIDOR_FLR_6_WALL_2_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
228 CORRIDOR_FLR_6_WALL_3_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 270.00 90.00 10.36 3.05 0.00 BANQUET_FLR_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
229 CORRIDOR_FLR_6_WALL_1_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 90.00 90.00 10.36 3.05 0.00 BANQUET_FLR_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
230 CORRIDOR_FLR_6_WALL_2_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   31.59 31.59 31.59 90.00 90.00 10.36 3.05 0.00 DINING_FLR_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
231 CORRIDOR_FLR_6_WALL_3_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   20.44 20.44 20.44 90.00 90.00 6.71 3.05 0.00 KITCHEN_FLR_6_WALL_1_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
232 CORRIDOR_FLR_6_FLOOR Floor   CTF - ConductionTransferFunction NONRES_FLOOR 0.412 0.375   412.12 412.12 412.12 180.00 180.00 20.30 20.30 0.00 CORRIDOR_FLR_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 12
233 CORRIDOR_FLR_6_CEILING_1 Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.283 0.269   244.71 244.71 244.71 90.00 0.00 15.64 15.64 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 8
234 CORRIDOR_FLR_6_CEILING_2 Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.283 0.269   167.42 167.42 167.42 270.00 0.00 12.94 12.94 0.00 ExternalEnvironment DOE-2 ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 6
235 CORRIDOR_FLR_6_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   824.25 824.25 824.25 0.00 90.00 824.25 1.00 0.00 CORRIDOR_FLR_6_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0


Environment

Environment Name Environment Type Start Date End Date Start DayOfWeek Duration {#days} Source:Start DayOfWeek Use Daylight Saving Use Holidays Apply Weekend Holiday Rule Use Rain Values Use Snow Values Sky Temperature Model
1 RUNPERIOD 1 WeatherFileRunPeriod 01/01/2017 12/31/2017 Sunday 365 Use RunPeriod Specified Day No No No Yes Yes Clark and Allen


Environment:Special Days

Special Day Name Special Day Type Source Start Date Duration {#days}
1 NEW YEARS DAY Holiday InputFile 01/01 1Environment:Special Days


Environment:Daylight Saving

Daylight Saving Indicator Source Start Date End Date
1 Yes InputFile 03/12 11/05


Tabular Report

Style Unit Conversion
1 Commaandhtml commaandhtml


Warmup Convergence Information

Zone Name Environment Type/Name Average Warmup Temperature Difference {deltaC} Std Dev Warmup Temperature Difference {deltaC} Max Temperature Pass/Fail Convergence Min Temperature Pass/Fail Convergence Average Warmup Load Difference {W} Std Dev Warmup Load Difference {W} Heating Load Pass/Fail Convergence Cooling Load Pass/Fail Convergence
1 BASEMENT RunPeriod: RUNPERIOD 1 1.0123312565E-002 1.5529076649E-002 Pass Pass 8.6574210045E-003 2.2650915352E-002 Pass Pass
2 RETAIL_1_FLR_1 RunPeriod: RUNPERIOD 1 4.3552702111E-002 5.8683237315E-002 Pass Pass 1.8515056031E-002 2.3357103678E-002 Pass Pass
3 RETAIL_2_FLR_1 RunPeriod: RUNPERIOD 1 8.4917147630E-003 1.5502544456E-002 Pass Pass 1.1276603747E-002 2.2836817766E-002 Pass Pass
4 MECH_FLR_1 RunPeriod: RUNPERIOD 1 2.9532623579E-003 8.6627287479E-003 Pass Pass 1.1925706467E-002 2.2383726876E-002 Pass Pass
5 STORAGE_FLR_1 RunPeriod: RUNPERIOD 1 6.0317837553E-004 4.3770986779E-004 Pass Pass 1.1330029339E-002 1.4342601135E-002 Pass Pass
6 LAUNDRY_FLR_1 RunPeriod: RUNPERIOD 1 3.7637726636E-002 0.1096346367 Pass Pass 1.8076855435E-002 5.1573298257E-002 Pass Pass
7 CAFE_FLR_1 RunPeriod: RUNPERIOD 1 5.3090473637E-002 7.2367070385E-002 Pass Pass 1.3900089421E-002 2.4300555522E-002 Pass Pass
8 LOBBY_FLR_1 RunPeriod: RUNPERIOD 1 2.1490973824E-002 3.1012427834E-002 Pass Pass 1.2372048961E-002 2.4844367818E-002 Pass Pass
9 ROOM_1_FLR_3 RunPeriod: RUNPERIOD 1 9.2612131110E-002 0.3211222880 Pass Pass 0.1428757758 0.5931658979 Pass Pass
10 ROOM_2_FLR_3 RunPeriod: RUNPERIOD 1 8.5108449817E-002 0.2884979086 Pass Pass 0.1141694445 0.4257993122 Pass Pass
11 ROOM_3_MULT19_FLR_3 RunPeriod: RUNPERIOD 1 1.8434824650E-003 1.0351463163E-002 Pass Pass 2.7708955834E-002 4.0711076908E-002 Pass Pass
12 ROOM_4_MULT19_FLR_3 RunPeriod: RUNPERIOD 1 8.2285904259E-002 0.2555802670 Pass Pass 9.7869218042E-002 0.3460607637 Pass Pass
13 ROOM_5_FLR_3 RunPeriod: RUNPERIOD 1 9.2609247687E-002 0.3339123405 Pass Pass 0.1230183642 0.4555168833 Pass Pass
14 ROOM_6_FLR_3 RunPeriod: RUNPERIOD 1 9.2618757535E-002 0.3204904740 Pass Pass 0.1575519771 0.6141555660 Pass Pass
15 CORRIDOR_FLR_3 RunPeriod: RUNPERIOD 1 1.2273396069E-002 1.2959152209E-002 Pass Pass 8.9996154084E-003 2.2894102470E-002 Pass Pass
16 ROOM_1_FLR_6 RunPeriod: RUNPERIOD 1 9.2531510247E-002 0.3263119625 Pass Pass 0.1453278347 0.6314684240 Pass Pass
17 ROOM_2_FLR_6 RunPeriod: RUNPERIOD 1 8.3356975547E-002 0.2897883641 Pass Pass 0.1231118583 0.4613293596 Pass Pass
18 ROOM_3_MULT9_FLR_6 RunPeriod: RUNPERIOD 1 9.2615876950E-002 0.3256685305 Pass Pass 9.6684721077E-002 0.3208063377 Pass Pass
19 BANQUET_FLR_6 RunPeriod: RUNPERIOD 1 3.5873902405E-002 7.4037139510E-002 Pass Pass 1.0231946703E-002 2.3922717946E-002 Pass Pass
20 DINING_FLR_6 RunPeriod: RUNPERIOD 1 4.0845416108E-002 7.4862360589E-002 Pass Pass 1.0039172855E-002 2.1354536174E-002 Pass Pass
21 KITCHEN_FLR_6 RunPeriod: RUNPERIOD 1 5.2635936707E-002 0.1278310293 Pass Pass 1.6818114953E-002 2.7936700986E-002 Pass Pass
22 CORRIDOR_FLR_6 RunPeriod: RUNPERIOD 1 1.4746275878E-002 2.2881448847E-002 Pass Pass 1.6040857542E-002 2.3937498104E-002 Pass Pass



Table of Contents

Report: Annual Heat Emissions Summary

For: Entire Facility

Timestamp: 2023-10-16 08:58:20

Heat Emission by Components

Envelope Convection Zone Exfiltration Zone Exhaust Air HVAC Relief Air HVAC Reject Heat Total
Heat Emissions [GJ] 3139.16 -214.1 -681.0 -12035.9 22433.28 12641.43



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2023-10-16 08:58:20

SizingPeriod:DesignDay

Maximum Dry Bulb [C] Daily Temperature Range [deltaC] Humidity Value Humidity Type Wind Speed [m/s] Wind Direction
MIAMI INTL AP ANN HTG 99.6% CONDNS DB 8.70 0.00 8.70 Wetbulb [C] 3.80 340.00
MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 33.20 6.70 25.30 Wetbulb [C] 4.50 140.00


Monthly Precipitation Summary

Monthly Total Precipitation from .epw [mm] Monthly Total Hours of Rain from .epw Monthly Total Precipitation in Site:Precipitation [mm] Monthly Total Roof Irrigation Depth [mm] Monthly Total Rain Collection Volume [m3]
Jan 65.00 29      
Feb 0.00 0      
Mar 0.00 0      
Apr 38.00 14      
May 0.00 0      
Jun 0.00 0      
Jul 0.00 0      
Aug 391.00 83      
Sep 0.00 0      
Oct 225.00 40      
Nov 0.00 0      
Dec 5.00 10      


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2023-10-16 08:58:20

Opaque Exterior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
BASEMENT_WALL_NORTH BASEMENT_WALL_NORTH_CFACTOR 1.00 0.845 0.940 211.13 211.13 0.00 90.00 N
BASEMENT_WALL_EAST BASEMENT_WALL_EAST_CFACTOR 1.00 0.845 0.940 55.76 55.76 90.00 90.00 E
BASEMENT_WALL_SOUTH BASEMENT_WALL_SOUTH_CFACTOR 1.00 0.845 0.940 211.13 211.13 180.00 90.00 S
BASEMENT_WALL_WEST BASEMENT_WALL_WEST_CFACTOR 1.00 0.845 0.940 55.76 55.76 270.00 90.00 W
RETAIL_1_FLR_1_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 1.028 1.214 45.89 22.63 180.00 90.00 S
RETAIL_1_FLR_1_WALL_WEST NONRES_EXT_WALL_GRD 0.30 1.028 1.214 22.95 22.95 270.00 90.00 W
RETAIL_1_FLR_1_CEILING NONRES_ROOF 0.55 0.273 0.283 67.07 67.07 180.00 0.00  
RETAIL_2_FLR_1_WALL_WEST NONRES_EXT_WALL_GRD 0.30 1.028 1.214 26.57 24.62 270.00 90.00 W
MECH_FLR_1_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 1.028 1.214 62.80 62.80 0.00 90.00 N
STORAGE_FLR_1_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 1.028 1.214 36.23 28.80 0.00 90.00 N
LAUNDRY_FLR_1_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 1.028 1.214 18.12 18.12 0.00 90.00 N
LAUNDRY_FLR_1_WALL_EAST NONRES_EXT_WALL_GRD 0.30 1.028 1.214 67.63 65.68 90.00 90.00 E
CAFE_FLR_1_WALL_EAST NONRES_EXT_WALL_GRD 0.30 1.028 1.214 22.95 21.00 90.00 90.00 E
CAFE_FLR_1_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 1.028 1.214 129.23 63.73 180.00 90.00 S
CAFE_FLR_1_CEILING NONRES_ROOF 0.55 0.273 0.283 188.86 188.86 180.00 0.00  
LOBBY_FLR_1_WALL_1_NORTH NONRES_EXT_WALL_GRD 0.30 1.028 1.214 213.77 209.87 0.00 90.00 N
LOBBY_FLR_1_WALL_2_NORTH NONRES_EXT_WALL_GRD 0.30 1.028 1.214 12.08 12.08 0.00 90.00 N
LOBBY_FLR_1_WALL_1_SOUTH NONRES_EXT_WALL_GRD 0.30 1.028 1.214 167.88 82.79 180.00 90.00 S
LOBBY_FLR_1_WALL_1_WEST NONRES_EXT_WALL_GRD 0.30 1.028 1.214 41.06 41.06 270.00 90.00 W
LOBBY_FLR_1_CEILING_2 NONRES_ROOF 0.55 0.273 0.283 245.35 245.35 180.00 0.00  
ROOM_1_FLR_3_WALL_SOUTH RES_EXT_WALL_MID 0.30 1.245 1.530 55.74 37.35 180.00 90.00 S
ROOM_1_FLR_3_WALL_WEST RES_EXT_WALL_MID 0.30 1.245 1.530 104.06 69.72 270.00 90.00 W
ROOM_2_FLR_3_WALL_NORTH RES_EXT_WALL_MID 0.30 1.245 1.530 55.74 37.35 0.00 90.00 N
ROOM_2_FLR_3_WALL_WEST RES_EXT_WALL_MID 0.30 1.245 1.530 104.05 69.71 270.00 90.00 W
ROOM_3_MULT19_FLR_3_WALL_SOUTH RES_EXT_WALL_MID 0.30 1.245 1.530 847.14 567.58 180.00 90.00 S
ROOM_4_MULT19_FLR_3_WALL_NORTH RES_EXT_WALL_MID 0.30 1.245 1.530 847.37 567.71 0.00 90.00 N
ROOM_5_FLR_3_WALL_EAST RES_EXT_WALL_MID 0.30 1.245 1.530 104.06 69.72 90.00 90.00 E
ROOM_5_FLR_3_WALL_SOUTH RES_EXT_WALL_MID 0.30 1.245 1.530 55.74 37.35 180.00 90.00 S
ROOM_6_FLR_3_WALL_NORTH RES_EXT_WALL_MID 0.30 1.245 1.530 55.74 37.35 0.00 90.00 N
ROOM_6_FLR_3_WALL_EAST RES_EXT_WALL_MID 0.30 1.245 1.530 104.05 69.71 90.00 90.00 E
CORRIDOR_FLR_3_WALL_1_NORTH NONRES_EXT_WALL_MID 0.30 1.245 1.530 70.60 47.31 0.00 90.00 N
CORRIDOR_FLR_3_WALL_2_NORTH NONRES_EXT_WALL_MID 0.30 1.245 1.530 26.01 17.42 0.00 90.00 N
CORRIDOR_FLR_3_WALL_1_SOUTH NONRES_EXT_WALL_MID 0.30 1.245 1.530 26.02 17.43 180.00 90.00 S
CORRIDOR_FLR_3_WALL_2_SOUTH NONRES_EXT_WALL_MID 0.30 1.245 1.530 70.60 47.31 180.00 90.00 S
ROOM_1_FLR_6_WALL_SOUTH RES_EXT_WALL_TOP 0.30 1.294 1.605 13.94 9.34 180.00 90.00 S
ROOM_1_FLR_6_WALL_WEST RES_EXT_WALL_TOP 0.30 1.294 1.605 26.01 17.43 270.00 90.00 W
ROOM_1_FLR_6_CEILING RES_ROOF 0.55 0.273 0.283 39.02 39.02 180.00 0.00  
ROOM_2_FLR_6_WALL_NORTH RES_EXT_WALL_TOP 0.30 1.294 1.605 13.94 9.34 0.00 90.00 N
ROOM_2_FLR_6_WALL_WEST RES_EXT_WALL_TOP 0.30 1.294 1.605 26.01 17.43 270.00 90.00 W
ROOM_2_FLR_6_CEILING RES_ROOF 0.55 0.273 0.283 39.02 39.02 180.00 0.00  
ROOM_3_MULT9_FLR_6_WALL_SOUTH RES_EXT_WALL_TOP 0.30 1.294 1.605 183.96 123.26 180.00 90.00 S
ROOM_3_MULT9_FLR_6_CEILING RES_ROOF 0.55 0.273 0.283 220.77 220.77 180.00 0.00  
BANQUET_FLR_6_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 1.294 1.605 97.55 65.36 0.00 90.00 N
BANQUET_FLR_6_CEILING NONRES_ROOF 0.55 0.273 0.283 331.66 331.66 180.00 0.00  
DINING_FLR_6_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 1.294 1.605 97.55 65.36 0.00 90.00 N
DINING_FLR_6_CEILING NONRES_ROOF 0.55 0.273 0.283 331.66 331.66 180.00 0.00  
KITCHEN_FLR_6_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 1.294 1.605 21.37 16.77 0.00 90.00 N
KITCHEN_FLR_6_WALL_EAST NONRES_EXT_WALL_TOP 0.30 1.294 1.605 52.03 34.86 90.00 90.00 E
KITCHEN_FLR_6_WALL_1_SOUTH NONRES_EXT_WALL_TOP 0.30 1.294 1.605 13.94 9.34 180.00 90.00 S
KITCHEN_FLR_6_CEILING NONRES_ROOF 0.55 0.273 0.283 103.30 103.30 270.00 0.00  
CORRIDOR_FLR_6_WALL_1_NORTH NONRES_EXT_WALL_TOP 0.30 1.294 1.605 17.65 11.83 0.00 90.00 N
CORRIDOR_FLR_6_WALL_2_NORTH NONRES_EXT_WALL_TOP 0.30 1.294 1.605 15.79 10.58 0.00 90.00 N
CORRIDOR_FLR_6_WALL_2_SOUTH NONRES_EXT_WALL_TOP 0.30 1.294 1.605 52.03 34.86 180.00 90.00 S
CORRIDOR_FLR_6_CEILING_1 NONRES_ROOF 0.55 0.273 0.283 244.71 244.71 90.00 0.00  
CORRIDOR_FLR_6_CEILING_2 NONRES_ROOF 0.55 0.273 0.283 167.42 167.42 270.00 0.00  


Opaque Interior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
BASEMENT_FLOOR BASEMENT_FLOOR 0.30 1.441 2.705 1978.83 1978.83 0.00 180.00  
BASEMENT_CEILING_1 NONRES_FLOOR_CEILING 0.30 0.371 0.412 67.07 67.07 180.00 0.00  
BASEMENT_CEILING_2 NONRES_FLOOR_CEILING 0.30 0.371 0.412 77.67 77.67 180.00 0.00  
BASEMENT_CEILING_3 NONRES_FLOOR_CEILING 0.30 0.371 0.412 164.24 164.24 180.00 0.00  
BASEMENT_CEILING_4 NONRES_FLOOR_CEILING 0.30 0.371 0.412 94.76 94.76 180.00 0.00  
BASEMENT_CEILING_5 NONRES_FLOOR_CEILING 0.30 0.371 0.412 78.04 78.04 180.00 0.00  
BASEMENT_CEILING_6 NONRES_FLOOR_CEILING 0.30 0.371 0.412 188.86 188.86 180.00 0.00  
BASEMENT_CEILING_7 NONRES_FLOOR_CEILING 0.30 0.371 0.412 1088.56 1088.56 180.00 0.00  
BASEMENT_CEILING_8 NONRES_FLOOR_CEILING 0.30 0.371 0.412 219.63 219.63 90.00 0.00  
RETAIL_1_FLR_1_WALL_NORTH INT_WALL 0.30 2.511 6.299 45.89 45.89 0.00 90.00 N
RETAIL_1_FLR_1_WALL_EAST INT_WALL 0.30 2.511 6.299 22.95 22.95 90.00 90.00 E
RETAIL_1_FLR_1_FLOOR NONRES_FLOOR 0.30 0.371 0.412 67.07 67.07 0.00 180.00  
RETAIL_2_FLR_1_WALL_SOUTH INT_WALL 0.30 2.511 6.299 45.89 45.89 180.00 90.00 S
RETAIL_2_FLR_1_WALL_NORTH INT_WALL 0.30 2.511 6.299 45.89 45.89 0.00 90.00 N
RETAIL_2_FLR_1_WALL_EAST INT_WALL 0.30 2.511 6.299 26.57 26.57 90.00 90.00 E
RETAIL_2_FLR_1_FLOOR NONRES_FLOOR 0.30 0.371 0.412 77.67 77.67 0.00 180.00  
RETAIL_2_FLR_1_CEILING NONRES_FLOOR_CEILING 0.30 0.379 0.412 77.67 77.67 180.00 0.00  
MECH_FLR_1_WALL_EAST INT_WALL 0.30 2.511 6.299 41.06 41.06 90.00 90.00 E
MECH_FLR_1_WALL_SOUTH INT_WALL 0.30 2.511 6.299 62.80 62.80 180.00 90.00 S
MECH_FLR_1_WALL_WEST INT_WALL 0.30 2.511 6.299 41.06 41.06 270.00 90.00 W
MECH_FLR_1_FLOOR NONRES_FLOOR 0.30 0.371 0.412 164.24 164.24 0.00 180.00  
MECH_FLR_1_CEILING NONRES_FLOOR_CEILING 0.30 0.379 0.412 164.24 164.24 180.00 0.00  
STORAGE_FLR_1_WALL_EAST INT_WALL 0.30 2.511 6.299 41.06 41.06 90.00 90.00 E
STORAGE_FLR_1_WALL_SOUTH INT_WALL 0.30 2.511 6.299 36.23 36.23 180.00 90.00 S
STORAGE_FLR_1_WALL_WEST INT_WALL 0.30 2.511 6.299 41.06 41.06 270.00 90.00 W
STORAGE_FLR_1_FLOOR NONRES_FLOOR 0.30 0.371 0.412 94.76 94.76 0.00 180.00  
STORAGE_FLR_1_CEILING NONRES_FLOOR_CEILING 0.30 0.379 0.412 94.76 94.76 180.00 0.00  
LAUNDRY_FLR_1_WALL_SOUTH INT_WALL 0.30 2.511 6.299 18.12 18.12 180.00 90.00 S
LAUNDRY_FLR_1_WALL_WEST INT_WALL 0.30 2.511 6.299 67.63 67.63 270.00 90.00 W
LAUNDRY_FLR_1_FLOOR NONRES_FLOOR 0.30 0.371 0.412 78.04 78.04 0.00 180.00  
LAUNDRY_FLR_1_CEILING NONRES_FLOOR_CEILING 0.30 0.379 0.412 78.04 78.04 180.00 0.00  
CAFE_FLR_1_WALL_1_NORTH INT_WALL 0.30 2.511 6.299 111.11 111.11 0.00 90.00 N
CAFE_FLR_1_WALL_2_NORTH INT_WALL 0.30 2.511 6.299 18.12 18.12 0.00 90.00 N
CAFE_FLR_1_WALL_WEST INT_WALL 0.30 2.511 6.299 22.95 22.95 270.00 90.00 W
CAFE_FLR_1_FLOOR NONRES_FLOOR 0.30 0.371 0.412 188.86 188.86 0.00 180.00  
LOBBY_FLR_1_WALL_2_SOUTH INT_WALL 0.30 2.511 6.299 45.89 45.89 180.00 90.00 S
LOBBY_FLR_1_WALL_3_SOUTH INT_WALL 0.30 2.511 6.299 111.11 111.11 180.00 90.00 S
LOBBY_FLR_1_WALL_2_WEST INT_WALL 0.30 2.511 6.299 22.95 22.95 270.00 90.00 W
LOBBY_FLR_1_WALL_3_WEST INT_WALL 0.30 2.511 6.299 26.57 26.57 270.00 90.00 W
LOBBY_FLR_1_WALL_4_WEST INT_WALL 0.30 2.511 6.299 41.06 41.06 270.00 90.00 W
LOBBY_FLR_1_WALL_3_NORTH INT_WALL 0.30 2.511 6.299 62.80 62.80 0.00 90.00 N
LOBBY_FLR_1_WALL_4_NORTH INT_WALL 0.30 2.511 6.299 36.23 36.23 0.00 90.00 N
LOBBY_FLR_1_WALL_1_EAST INT_WALL 0.30 2.511 6.299 41.06 41.06 90.00 90.00 E
LOBBY_FLR_1_WALL_2_EAST INT_WALL 0.30 2.511 6.299 22.95 22.95 90.00 90.00 E
LOBBY_FLR_1_WALL_3_EAST INT_WALL 0.30 2.511 6.299 67.63 67.63 90.00 90.00 E
LOBBY_FLR_1_FLOOR_1 NONRES_FLOOR 0.30 0.371 0.412 1088.56 1088.56 180.00 180.00  
LOBBY_FLR_1_FLOOR_2 NONRES_FLOOR 0.30 0.371 0.412 219.63 219.63 90.00 180.00  
LOBBY_FLR_1_CEILING_1 NONRES_FLOOR_CEILING 0.30 0.379 0.412 1062.83 1062.83 270.00 0.00  
ROOM_1_FLR_3_WALL_NORTH INT_WALL 0.30 2.511 6.299 55.74 55.74 0.00 90.00 N
ROOM_1_FLR_3_WALL_EAST INT_WALL 0.30 2.511 6.299 104.06 104.06 90.00 90.00 E
ROOM_1_FLR_3_FLOOR NONRES_FLOOR 0.30 0.364 0.412 156.09 156.09 0.00 180.00  
ROOM_1_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 0.379 0.412 156.09 156.09 180.00 0.00  
ROOM_2_FLR_3_WALL_EAST INT_WALL 0.30 2.511 6.299 104.05 104.05 90.00 90.00 E
ROOM_2_FLR_3_WALL_SOUTH INT_WALL 0.30 2.511 6.299 55.74 55.74 180.00 90.00 S
ROOM_2_FLR_3_FLOOR NONRES_FLOOR 0.30 0.364 0.412 156.07 156.07 0.00 180.00  
ROOM_2_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 0.379 0.412 156.07 156.07 180.00 0.00  
ROOM_3_MULT19_FLR_3_WALL_NORTH INT_WALL 0.30 2.511 6.299 847.14 847.14 0.00 90.00 N
ROOM_3_MULT19_FLR_3_WALL_EAST INT_WALL 0.30 2.511 6.299 1553.43 1553.43 90.00 90.00 E
ROOM_3_MULT19_FLR_3_WALL_WEST INT_WALL 0.30 2.511 6.299 1553.43 1553.43 270.00 90.00 W
ROOM_3_MULT19_FLR_3_FLOOR NONRES_FLOOR 0.30 0.364 0.412 1863.81 1863.81 0.00 180.00  
ROOM_3_MULT19_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 0.379 0.412 1863.81 1863.81 180.00 0.00  
ROOM_4_MULT19_FLR_3_WALL_EAST INT_WALL 0.30 2.511 6.299 1553.43 1553.43 90.00 90.00 E
ROOM_4_MULT19_FLR_3_WALL_SOUTH INT_WALL 0.30 2.511 6.299 847.37 847.37 180.00 90.00 S
ROOM_4_MULT19_FLR_3_WALL_WEST INT_WALL 0.30 2.511 6.299 1553.43 1553.43 270.00 90.00 W
ROOM_4_MULT19_FLR_3_FLOOR NONRES_FLOOR 0.30 0.364 0.412 1864.32 1864.32 0.00 180.00  
ROOM_4_MULT19_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 0.379 0.412 1864.32 1864.32 180.00 0.00  
ROOM_5_FLR_3_WALL_NORTH INT_WALL 0.30 2.511 6.299 55.74 55.74 0.00 90.00 N
ROOM_5_FLR_3_WALL_WEST INT_WALL 0.30 2.511 6.299 104.06 104.06 270.00 90.00 W
ROOM_5_FLR_3_FLOOR NONRES_FLOOR 0.30 0.364 0.412 156.09 156.09 0.00 180.00  
ROOM_5_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 0.379 0.412 156.09 156.09 180.00 0.00  
ROOM_6_FLR_3_WALL_SOUTH INT_WALL 0.30 2.511 6.299 55.74 55.74 180.00 90.00 S
ROOM_6_FLR_3_WALL_WEST INT_WALL 0.30 2.511 6.299 104.05 104.05 270.00 90.00 W
ROOM_6_FLR_3_FLOOR NONRES_FLOOR 0.30 0.364 0.412 156.07 156.07 0.00 180.00  
ROOM_6_FLR_3_CEILING NONRES_FLOOR_CEILING 0.30 0.379 0.412 156.07 156.07 180.00 0.00  
CORRIDOR_FLR_3_WALL_3_NORTH INT_WALL 0.30 2.511 6.299 847.28 847.28 0.00 90.00 N
CORRIDOR_FLR_3_WALL_1_EAST INT_WALL 0.30 2.511 6.299 81.76 81.76 90.00 90.00 E
CORRIDOR_FLR_3_WALL_2_EAST INT_WALL 0.30 2.511 6.299 81.76 81.76 90.00 90.00 E
CORRIDOR_FLR_3_WALL_3_EAST INT_WALL 0.30 2.511 6.299 104.06 104.06 90.00 90.00 E
CORRIDOR_FLR_3_WALL_4_EAST INT_WALL 0.30 2.511 6.299 104.05 104.05 90.00 90.00 E
CORRIDOR_FLR_3_WALL_3_SOUTH INT_WALL 0.30 2.511 6.299 847.27 847.27 180.00 90.00 S
CORRIDOR_FLR_3_WALL_1_WEST INT_WALL 0.30 2.511 6.299 81.76 81.76 270.00 90.00 W
CORRIDOR_FLR_3_WALL_2_WEST INT_WALL 0.30 2.511 6.299 81.76 81.76 270.00 90.00 W
CORRIDOR_FLR_3_WALL_3_WEST INT_WALL 0.30 2.511 6.299 104.06 104.06 270.00 90.00 W
CORRIDOR_FLR_3_WALL_4_WEST INT_WALL 0.30 2.511 6.299 104.05 104.05 270.00 90.00 W
CORRIDOR_FLR_3_FLOOR_1 NONRES_FLOOR 0.30 0.364 0.412 297.29 297.29 180.00 180.00  
CORRIDOR_FLR_3_FLOOR_2 NONRES_FLOOR 0.30 0.364 0.412 963.06 963.06 270.00 180.00  
CORRIDOR_FLR_3_FLOOR_3 NONRES_FLOOR 0.30 0.364 0.412 297.26 297.26 90.00 180.00  
CORRIDOR_FLR_3_CEILING_1 NONRES_FLOOR_CEILING 0.30 0.379 0.412 297.29 297.29 90.00 0.00  
CORRIDOR_FLR_3_CEILING_2 NONRES_FLOOR_CEILING 0.30 0.379 0.412 963.06 963.06 90.00 0.00  
CORRIDOR_FLR_3_CEILING_3 NONRES_FLOOR_CEILING 0.30 0.379 0.412 297.26 297.26 90.00 0.00  
ROOM_1_FLR_6_WALL_NORTH INT_WALL 0.30 2.511 6.299 13.94 13.94 0.00 90.00 N
ROOM_1_FLR_6_WALL_EAST INT_WALL 0.30 2.511 6.299 26.01 26.01 90.00 90.00 E
ROOM_1_FLR_6_FLOOR NONRES_FLOOR 0.30 0.364 0.412 39.02 39.02 0.00 180.00  
ROOM_2_FLR_6_WALL_EAST INT_WALL 0.30 2.511 6.299 26.01 26.01 90.00 90.00 E
ROOM_2_FLR_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 13.94 13.94 180.00 90.00 S
ROOM_2_FLR_6_FLOOR NONRES_FLOOR 0.30 0.364 0.412 39.02 39.02 0.00 180.00  
ROOM_3_MULT9_FLR_6_WALL_NORTH INT_WALL 0.30 2.511 6.299 183.96 183.96 0.00 90.00 N
ROOM_3_MULT9_FLR_6_WALL_EAST INT_WALL 0.30 2.511 6.299 100.35 100.35 90.00 90.00 E
ROOM_3_MULT9_FLR_6_WALL_WEST INT_WALL 0.30 2.511 6.299 100.35 100.35 270.00 90.00 W
ROOM_3_MULT9_FLR_6_FLOOR NONRES_FLOOR 0.30 0.364 0.412 220.77 220.77 0.00 180.00  
BANQUET_FLR_6_WALL_EAST INT_WALL 0.30 2.511 6.299 31.59 31.59 90.00 90.00 E
BANQUET_FLR_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 97.55 97.55 180.00 90.00 S
BANQUET_FLR_6_WALL_WEST INT_WALL 0.30 2.511 6.299 31.59 31.59 270.00 90.00 W
BANQUET_FLR_6_FLOOR NONRES_FLOOR 0.30 0.364 0.412 331.66 331.66 0.00 180.00  
DINING_FLR_6_WALL_EAST INT_WALL 0.30 2.511 6.299 31.59 31.59 90.00 90.00 E
DINING_FLR_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 97.55 97.55 180.00 90.00 S
DINING_FLR_6_WALL_WEST INT_WALL 0.30 2.511 6.299 31.59 31.59 270.00 90.00 W
DINING_FLR_6_FLOOR NONRES_FLOOR 0.30 0.364 0.412 331.66 331.66 0.00 180.00  
KITCHEN_FLR_6_WALL_2_SOUTH INT_WALL 0.30 2.511 6.299 7.43 7.43 180.00 90.00 S
KITCHEN_FLR_6_WALL_1_WEST INT_WALL 0.30 2.511 6.299 20.44 20.44 270.00 90.00 W
KITCHEN_FLR_6_WALL_2_WEST INT_WALL 0.30 2.511 6.299 31.59 31.59 270.00 90.00 W
KITCHEN_FLR_6_FLOOR NONRES_FLOOR 0.30 0.364 0.412 103.30 103.30 180.00 180.00  
CORRIDOR_FLR_6_WALL_3_NORTH INT_WALL 0.30 2.511 6.299 97.55 97.55 0.00 90.00 N
CORRIDOR_FLR_6_WALL_4_NORTH INT_WALL 0.30 2.511 6.299 104.98 104.98 0.00 90.00 N
CORRIDOR_FLR_6_WALL_1_SOUTH INT_WALL 0.30 2.511 6.299 183.95 183.95 180.00 90.00 S
CORRIDOR_FLR_6_WALL_1_WEST INT_WALL 0.30 2.511 6.299 11.15 11.15 270.00 90.00 W
CORRIDOR_FLR_6_WALL_2_WEST INT_WALL 0.30 2.511 6.299 40.88 40.88 270.00 90.00 W
CORRIDOR_FLR_6_WALL_3_WEST INT_WALL 0.30 2.511 6.299 31.59 31.59 270.00 90.00 W
CORRIDOR_FLR_6_WALL_1_EAST INT_WALL 0.30 2.511 6.299 31.59 31.59 90.00 90.00 E
CORRIDOR_FLR_6_WALL_2_EAST INT_WALL 0.30 2.511 6.299 31.59 31.59 90.00 90.00 E
CORRIDOR_FLR_6_WALL_3_EAST INT_WALL 0.30 2.511 6.299 20.44 20.44 90.00 90.00 E
CORRIDOR_FLR_6_FLOOR NONRES_FLOOR 0.30 0.364 0.412 412.12 412.12 180.00 180.00  
BASEMENT_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 3957.66   0.00 90.00 N
RETAIL_1_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 134.14   0.00 90.00 N
RETAIL_2_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 155.34   0.00 90.00 N
MECH_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 328.49   0.00 90.00 N
STORAGE_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 189.52   0.00 90.00 N
LAUNDRY_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 156.08   0.00 90.00 N
CAFE_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 377.72   0.00 90.00 N
LOBBY_FLR_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 2616.37   0.00 90.00 N
ROOM_1_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 312.18   0.00 90.00 N
ROOM_2_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 312.14   0.00 90.00 N
ROOM_3_MULT19_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 3727.63   0.00 90.00 N
ROOM_4_MULT19_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 3728.64   0.00 90.00 N
ROOM_5_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 312.18   0.00 90.00 N
ROOM_6_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 312.14   0.00 90.00 N
CORRIDOR_FLR_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 3115.24   0.00 90.00 N
ROOM_1_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 78.04   0.00 90.00 N
ROOM_2_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 78.03   0.00 90.00 N
ROOM_3_MULT9_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 441.55   0.00 90.00 N
BANQUET_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 663.31   0.00 90.00 N
DINING_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 663.31   0.00 90.00 N
KITCHEN_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 206.61   0.00 90.00 N
CORRIDOR_FLR_6_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 824.25   0.00 90.00 N


Exterior Fenestration

Construction Frame and Divider Glass Area [m2] Frame Area [m2] Divider Area [m2] Area of One Opening [m2] Area of Multiplied Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Frame Conductance [W/m2-K] Divider Conductance [W/m2-K] NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW NONRESWINDOW_U_0.5119_SHGC_0.25   23.26 0.00 0.00 23.26 23.26 2.910 0.251 0.251             No RETAIL_1_FLR_1_WALL_SOUTH 180.00 90.00 S
CAFE_FLR_1_WALL_SOUTH_WINDOW NONRESWINDOW_U_0.5119_SHGC_0.25   65.50 0.00 0.00 65.50 65.50 2.910 0.251 0.251             No CAFE_FLR_1_WALL_SOUTH 180.00 90.00 S
LOBBY_FLR_1_WALL_SOUTH_WINDOW NONRESWINDOW_U_0.5119_SHGC_0.25   85.08 0.00 0.00 85.08 85.08 2.910 0.251 0.251             No LOBBY_FLR_1_WALL_1_SOUTH 180.00 90.00 S
ROOM_1_FLR_3_WALL_SOUTH_WINDOW RESWINDOW_U_0.5119_SHGC_0.25   4.60 0.00 0.00 4.60 18.40 2.910 0.251 0.251             No ROOM_1_FLR_3_WALL_SOUTH 180.00 90.00 S
ROOM_1_FLR_3_WALL_WEST_WINDOW RESWINDOW_U_0.5119_SHGC_0.25   8.58 0.00 0.00 8.58 34.34 2.910 0.251 0.251             No ROOM_1_FLR_3_WALL_WEST 270.00 90.00 W
ROOM_2_FLR_3_WALL_NORTH_WINDOW RESWINDOW_U_0.5119_SHGC_0.25   4.60 0.00 0.00 4.60 18.40 2.910 0.251 0.251             No ROOM_2_FLR_3_WALL_NORTH 0.00 90.00 N
ROOM_2_FLR_3_WALL_WEST_WINDOW RESWINDOW_U_0.5119_SHGC_0.25   8.58 0.00 0.00 8.58 34.34 2.910 0.251 0.251             No ROOM_2_FLR_3_WALL_WEST 270.00 90.00 W
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW RESWINDOW_U_0.5119_SHGC_0.25   3.68 0.00 0.00 3.68 279.56 2.910 0.251 0.251             No ROOM_3_MULT19_FLR_3_WALL_SOUTH 180.00 90.00 S
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW RESWINDOW_U_0.5119_SHGC_0.25   3.68 0.00 0.00 3.68 279.65 2.910 0.251 0.251             No ROOM_4_MULT19_FLR_3_WALL_NORTH 0.00 90.00 N
ROOM_5_FLR_3_WALL_EAST_WINDOW RESWINDOW_U_0.5119_SHGC_0.25   8.58 0.00 0.00 8.58 34.34 2.910 0.251 0.251             No ROOM_5_FLR_3_WALL_EAST 90.00 90.00 E
ROOM_5_FLR_3_WALL_SOUTH_WINDOW RESWINDOW_U_0.5119_SHGC_0.25   4.60 0.00 0.00 4.60 18.40 2.910 0.251 0.251             No ROOM_5_FLR_3_WALL_SOUTH 180.00 90.00 S
ROOM_6_FLR_3_WALL_NORTH_WINDOW RESWINDOW_U_0.5119_SHGC_0.25   4.60 0.00 0.00 4.60 18.40 2.910 0.251 0.251             No ROOM_6_FLR_3_WALL_NORTH 0.00 90.00 N
ROOM_6_FLR_3_WALL_EAST_WINDOW RESWINDOW_U_0.5119_SHGC_0.25   8.58 0.00 0.00 8.58 34.34 2.910 0.251 0.251             No ROOM_6_FLR_3_WALL_EAST 90.00 90.00 E
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW NONRESWINDOW_U_0.5119_SHGC_0.25   5.82 0.00 0.00 5.82 23.30 2.910 0.251 0.251             No CORRIDOR_FLR_3_WALL_1_NORTH 0.00 90.00 N
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW NONRESWINDOW_U_0.5119_SHGC_0.25   2.15 0.00 0.00 2.15 8.59 2.910 0.251 0.251             No CORRIDOR_FLR_3_WALL_2_NORTH 0.00 90.00 N
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW NONRESWINDOW_U_0.5119_SHGC_0.25   2.15 0.00 0.00 2.15 8.58 2.910 0.251 0.251             No CORRIDOR_FLR_3_WALL_1_SOUTH 180.00 90.00 S
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW NONRESWINDOW_U_0.5119_SHGC_0.25   5.82 0.00 0.00 5.82 23.30 2.910 0.251 0.251             No CORRIDOR_FLR_3_WALL_2_SOUTH 180.00 90.00 S
ROOM_1_FLR_6_WALL_SOUTH_WINDOW RESWINDOW_U_0.5119_SHGC_0.25   4.60 0.00 0.00 4.60 4.60 2.910 0.251 0.251             No ROOM_1_FLR_6_WALL_SOUTH 180.00 90.00 S
ROOM_1_FLR_6_WALL_WEST_WINDOW RESWINDOW_U_0.5119_SHGC_0.25   8.58 0.00 0.00 8.58 8.58 2.910 0.251 0.251             No ROOM_1_FLR_6_WALL_WEST 270.00 90.00 W
ROOM_2_FLR_6_WALL_NORTH_WINDOW RESWINDOW_U_0.5119_SHGC_0.25   4.60 0.00 0.00 4.60 4.60 2.910 0.251 0.251             No ROOM_2_FLR_6_WALL_NORTH 0.00 90.00 N
ROOM_2_FLR_6_WALL_WEST_WINDOW RESWINDOW_U_0.5119_SHGC_0.25   8.58 0.00 0.00 8.58 8.58 2.910 0.251 0.251             No ROOM_2_FLR_6_WALL_WEST 270.00 90.00 W
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW RESWINDOW_U_0.5119_SHGC_0.25   6.74 0.00 0.00 6.74 60.70 2.910 0.251 0.251             No ROOM_3_MULT9_FLR_6_WALL_SOUTH 180.00 90.00 S
BANQUET_FLR_6_WALL_NORTH_WINDOW NONRESWINDOW_U_0.5119_SHGC_0.25   32.19 0.00 0.00 32.19 32.19 2.910 0.251 0.251             No BANQUET_FLR_6_WALL_NORTH 0.00 90.00 N
DINING_FLR_6_WALL_NORTH_WINDOW NONRESWINDOW_U_0.5119_SHGC_0.25   32.19 0.00 0.00 32.19 32.19 2.910 0.251 0.251             No DINING_FLR_6_WALL_NORTH 0.00 90.00 N
KITCHEN_FLR_6_WALL_NORTH_WINDOW NONRESWINDOW_U_0.5119_SHGC_0.25   4.60 0.00 0.00 4.60 4.60 2.910 0.251 0.251             No KITCHEN_FLR_6_WALL_NORTH 0.00 90.00 N
KITCHEN_FLR_6_WALL_EAST_WINDOW NONRESWINDOW_U_0.5119_SHGC_0.25   17.17 0.00 0.00 17.17 17.17 2.910 0.251 0.251             No KITCHEN_FLR_6_WALL_EAST 90.00 90.00 E
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW NONRESWINDOW_U_0.5119_SHGC_0.25   4.60 0.00 0.00 4.60 4.60 2.910 0.251 0.251             No KITCHEN_FLR_6_WALL_1_SOUTH 180.00 90.00 S
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW NONRESWINDOW_U_0.5119_SHGC_0.25   5.82 0.00 0.00 5.82 5.82 2.910 0.251 0.251             No CORRIDOR_FLR_6_WALL_1_NORTH 0.00 90.00 N
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW NONRESWINDOW_U_0.5119_SHGC_0.25   5.21 0.00 0.00 5.21 5.21 2.910 0.251 0.251             No CORRIDOR_FLR_6_WALL_2_NORTH 0.00 90.00 N
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW NONRESWINDOW_U_0.5119_SHGC_0.25   17.17 0.00 0.00 17.17 17.17 2.910 0.251 0.251             No CORRIDOR_FLR_6_WALL_2_SOUTH 180.00 90.00 S
Total or Average             1213.79 2.910 0.251 0.251                      
North Total or Average             432.95 2.910 0.251 0.251                      
Non-North Total or Average             780.84 2.910 0.251 0.251                      


Exterior Fenestration Shaded State

Frame and Divider Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance
None                


Interior Fenestration

Construction Area of One Opening [m2] Area of Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance
Total or Average     0.00 - - -


Exterior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
RETAIL_2_FLR_1_WALL_WEST_DOOR SWINGING DOOR_CON 2.281 3.464 1.95 RETAIL_2_FLR_1_WALL_WEST
STORAGE_FLR_1_WALL_NORTH_ROLLDOOR OVERHEAD DOOR_CON 1.016 1.198 7.43 STORAGE_FLR_1_WALL_NORTH
LAUNDRY_FLR_1_WALL_EAST_DOOR SWINGING DOOR_CON 2.281 3.464 1.95 LAUNDRY_FLR_1_WALL_EAST
CAFE_FLR_1_WALL_EAST_DOOR SWINGING DOOR_CON 2.281 3.464 1.95 CAFE_FLR_1_WALL_EAST
LOBBY_FLR_1_WALL_1_NORTH_DOOR1 SWINGING DOOR_CON 2.281 3.464 1.95 LOBBY_FLR_1_WALL_1_NORTH
LOBBY_FLR_1_WALL_1_NORTH_DOOR2 SWINGING DOOR_CON 2.281 3.464 1.95 LOBBY_FLR_1_WALL_1_NORTH


Interior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
None          



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2023-10-16 08:58:20

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
CAFE_FLR_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
LOBBY_FLR_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
ROOM_1_FLR_3_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
ROOM_1_FLR_3_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
ROOM_2_FLR_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
ROOM_2_FLR_3_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
ROOM_5_FLR_3_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
ROOM_5_FLR_3_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
ROOM_6_FLR_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
ROOM_6_FLR_3_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
ROOM_1_FLR_6_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
ROOM_1_FLR_6_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
ROOM_2_FLR_6_WALL_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
ROOM_2_FLR_6_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
BANQUET_FLR_6_WALL_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
DINING_FLR_6_WALL_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
KITCHEN_FLR_6_WALL_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
KITCHEN_FLR_6_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00


Window Control

Name Type Shaded Construction Control Glare Control
None          



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2023-10-16 08:58:20

Interior Lighting

Zone Name Space Name Space Type Lighting Power Density [W/m2] Space Area [m2] Total Power [W] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [GJ]
BASEMENT_LIGHTS BASEMENT BASEMENT GENERAL 8.7495 1978.83 17313.73 LightsWired LTG_SCH_BASEMENT 50.91 168.00 50.86 0.0000 Y 165.29
RETAIL_1_FLR_1_LIGHTS RETAIL_1_FLR_1 RETAIL_1_FLR_1 GENERAL 13.0124 67.07 872.76 LightsWired LTG_SCH_RETAIL 51.36 168.00 51.30 0.0000 Y 8.40
RETAIL_2_FLR_1_LIGHTS RETAIL_2_FLR_1 RETAIL_2_FLR_1 GENERAL 13.0124 77.67 1010.66 LightsWired LTG_SCH_RETAIL 51.36 168.00 51.30 0.0000 Y 9.73
MECH_FLR_1_LIGHTS MECH_FLR_1 MECH_FLR_1 GENERAL 10.0642 164.24 1652.98 LightsWired LTG_SCH_MECHANIC 58.69 168.00 58.63 0.0000 Y 18.19
STORAGE_FLR_1_LIGHTS STORAGE_FLR_1 STORAGE_FLR_1 GENERAL 7.3195 94.76 693.59 LightsWired LTG_SCH_STORAGE 25.68 168.00 25.65 0.0000 Y 3.34
LAUNDRY_FLR_1_LIGHTS LAUNDRY_FLR_1 LAUNDRY_FLR_1 GENERAL 5.4896 78.04 428.40 LightsWired LTG_SCH_LAUNDRY 51.36 168.00 51.30 0.0000 Y 4.13
CAFE_FLR_1_LIGHTS CAFE_FLR_1 CAFE_FLR_1 GENERAL 12.8090 188.86 2419.14 LightsWired LTG_SCH_DINING 58.69 168.00 58.63 0.0000 Y 26.62
LOBBY_FLR_1_LIGHTS LOBBY_FLR_1 LOBBY_FLR_1 GENERAL 10.0642 1308.19 13165.91 LightsWired LTG_SCH_LOBBY 58.69 168.00 58.63 0.0000 Y 144.89
ROOM_1_FLR_3_LIGHTS ROOM_1_FLR_3 ROOM_1_FLR_3 GENERAL 10.0642 156.09 1570.91 LightsWired LTG_SCH_GUESTROOM 69.03 168.00 69.21 0.0000 Y 20.41
ROOM_2_FLR_3_LIGHTS ROOM_2_FLR_3 ROOM_2_FLR_3 GENERAL 10.0642 156.07 1570.72 LightsWired LTG_SCH_GUESTROOM 69.03 168.00 69.21 0.0000 Y 20.41
ROOM_3_MULT19_FLR_3_LIGHTS ROOM_3_MULT19_FLR_3 ROOM_3_MULT19_FLR_3 GENERAL 10.0642 1863.81 18757.86 LightsWired LTG_SCH_GUESTROOM 69.03 168.00 69.21 0.0000 Y 243.70
ROOM_4_MULT19_FLR_3_LIGHTS ROOM_4_MULT19_FLR_3 ROOM_4_MULT19_FLR_3 GENERAL 10.0642 1864.32 18762.99 LightsWired LTG_SCH_GUESTROOM 69.03 168.00 69.21 0.0000 Y 243.77
ROOM_5_FLR_3_LIGHTS ROOM_5_FLR_3 ROOM_5_FLR_3 GENERAL 10.0642 156.09 1570.91 LightsWired LTG_SCH_GUESTROOM 69.03 168.00 69.21 0.0000 Y 20.41
ROOM_6_FLR_3_LIGHTS ROOM_6_FLR_3 ROOM_6_FLR_3 GENERAL 10.0642 156.07 1570.72 LightsWired LTG_SCH_GUESTROOM 69.03 168.00 69.21 0.0000 Y 20.41
CORRIDOR_FLR_3_LIGHTS CORRIDOR_FLR_3 CORRIDOR_FLR_3 GENERAL 3.6597 1557.62 5700.46 LightsWired LTG_SCH_CORRIDOR 58.69 168.00 58.63 0.0000 Y 62.73
ROOM_1_FLR_6_LIGHTS ROOM_1_FLR_6 ROOM_1_FLR_6 GENERAL 10.0642 39.02 392.73 LightsWired LTG_SCH_GUESTROOM 69.03 168.00 69.21 0.0000 Y 5.10
ROOM_2_FLR_6_LIGHTS ROOM_2_FLR_6 ROOM_2_FLR_6 GENERAL 10.0642 39.02 392.68 LightsWired LTG_SCH_GUESTROOM 69.03 168.00 69.21 0.0000 Y 5.10
ROOM_3_MULT9_FLR_6_LIGHTS ROOM_3_MULT9_FLR_6 ROOM_3_MULT9_FLR_6 GENERAL 10.0642 220.77 2221.93 LightsWired LTG_SCH_GUESTROOM 69.03 168.00 69.21 0.0000 Y 28.87
BANQUET_FLR_6_LIGHTS BANQUET_FLR_6 BANQUET_FLR_6 GENERAL 12.8090 331.66 4248.21 LightsWired LTG_SCH_DINING 58.69 168.00 58.63 0.0000 Y 46.75
DINING_FLR_6_LIGHTS DINING_FLR_6 DINING_FLR_6 GENERAL 12.8090 331.66 4248.21 LightsWired LTG_SCH_DINING 58.69 168.00 58.63 0.0000 Y 46.75
KITCHEN_FLR_6_LIGHTS KITCHEN_FLR_6 KITCHEN_FLR_6 GENERAL 10.9792 103.30 1134.20 LightsWired LTG_SCH_KITCHEN 58.69 168.00 58.63 0.0000 Y 12.48
CORRIDOR_FLR_6_LIGHTS CORRIDOR_FLR_6 CORRIDOR_FLR_6 GENERAL 3.6597 412.12 1508.26 LightsWired LTG_SCH_CORRIDOR 58.69 168.00 58.63 0.0000 Y 16.60
Interior Lighting Total       8.9207 11345.29 101207.97               559.10


Daylighting

Zone Control Name Daylighting Method Control Type Fraction Controlled Lighting Installed in Zone [W] Lighting Controlled [W]
None              


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [GJ]
EXTERIOR FACADE LIGHTING 16690.39 AstronomicalClock -   83.82 83.82 262.62
Exterior Lighting Total 16690.39           262.62



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2023-10-16 08:58:20

Central Plant

Type Reference Capacity [W] Reference Efficiency [W/W] Rated Capacity [W] Rated Efficiency [W/W] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
HEATSYS1 BOILER Boiler:HotWater 278835.82 0.80        
COOLSYS1 CHILLER1 Chiller:Electric:EIR 1497043.85 2.80 1497306.99 2.80 3.72 12.68


Cooling Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Sensible Capacity [W] Nominal Latent Capacity [W] Nominal Sensible Heat Ratio Nominal Efficiency [W/W] Nominal Coil UA Value [W/C] Nominal Coil Surface Area [m2]
ROOM_1_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 13663.36 19045.41 14862.37 4183.04 0.78 - 2098.68 21.29
ROOM_2_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 13785.91 19222.62 15003.60 4219.01 0.78 - 2118.25 21.48
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 75998.17 106764.62 83705.91 23058.71 0.78 - 11771.74 119.40
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 92061.17 127516.44 99143.27 28373.17 0.78 - 14045.78 142.46
ROOM_5_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 12405.48 17226.59 13413.16 3813.43 0.78 - 1897.78 19.25
ROOM_6_FLR_3 FAN COIL COOLING COIL Coil:Cooling:Water 12501.43 17364.64 13522.84 3841.80 0.78 - 1913.02 19.40
ROOM_1_FLR_6 FAN COIL COOLING COIL Coil:Cooling:Water 3632.37 5073.53 3964.00 1109.53 0.78 - 559.15 5.67
ROOM_2_FLR_6 FAN COIL COOLING COIL Coil:Cooling:Water 3661.77 5116.16 3998.03 1118.13 0.78 - 563.86 5.72
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL Coil:Cooling:Water 15472.29 21413.41 16640.84 4772.57 0.78 - 2358.57 23.92
VAV WITH REHEAT COOLING COIL Coil:Cooling:Water 1144947.37 715419.77 456961.22 258458.55 0.64 - 89905.40 911.87
FLR_3_DOAS COOLING COIL Coil:Cooling:Water 108329.82 67803.65 43510.62 24293.03 0.64 - 8145.92 82.62
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [W] Standard Rated Net COP [W/W] EER [Btu/W-h] SEER User [Btu/W-h] SEER Standard [Btu/W-h] IEER [Btu/W-h]
None              


DX Cooling Coil ASHRAE 127 Standard Ratings Report

DX Cooling Coil Type Rated Net Cooling Capacity Test A [W] Rated Electric Power Test A [W] Rated Net Cooling Capacity Test B [W] Rated Electric Power Test B [W] Rated Net Cooling Capacity Test C [W] Rated Electric Power Test C [W] Rated Net Cooling Capacity Test D [W] Rated Electric Power Test D [W]
None                  


DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [W] Low Temperature Heating (net) Rating Capacity [W] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Efficiency [W/W]
BASEMENT VAV BOX REHEAT COIL Coil:Heating:Water 13966.41 14038.54 -
RETAIL_1_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 3112.97 3128.03 -
RETAIL_2_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 1773.53 1782.51 -
MECH_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 2296.52 2307.99 -
STORAGE_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 1228.03 1234.13 -
LAUNDRY_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 18443.65 18538.55 -
CAFE_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 10789.68 10843.85 -
LOBBY_FLR_1 VAV BOX REHEAT COIL Coil:Heating:Water 32731.44 32897.42 -
ROOM_1_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 3659.96 3941.71 -
ROOM_2_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 3660.18 3941.96 -
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 21298.53 22938.09 -
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 21316.13 22957.06 -
ROOM_5_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 3658.99 3940.68 -
ROOM_6_FLR_3 FAN COIL HEATING COIL Coil:Heating:Water 3659.22 3940.92 -
CORRIDOR_FLR_3 VAV BOX REHEAT COIL Coil:Heating:Water 11535.77 11591.66 -
ROOM_1_FLR_6 FAN COIL HEATING COIL Coil:Heating:Water 1124.65 1211.22 -
ROOM_2_FLR_6 FAN COIL HEATING COIL Coil:Heating:Water 1124.88 1211.47 -
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL Coil:Heating:Water 5435.88 5854.28 -
BANQUET_FLR_6 VAV BOX REHEAT COIL Coil:Heating:Water 15438.99 15517.49 -
DINING_FLR_6 VAV BOX REHEAT COIL Coil:Heating:Water 15947.96 16029.13 -
KITCHEN_FLR_6 VAV BOX REHEAT COIL Coil:Heating:Water 11816.39 11877.42 -
CORRIDOR_FLR_6 VAV BOX REHEAT COIL Coil:Heating:Water 7322.43 7357.68 -
VAV WITH REHEAT HEATING COIL Coil:Heating:Water 61543.58 55098.44 -
FLR_3_DOAS HEATING COIL Coil:Heating:Water 5950.05 5326.93 -
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

Fans

Type Total Efficiency [W/W] Delta Pressure [pa] Max Air Flow Rate [m3/s] Rated Electricity Rate [W] Rated Power Per Max Air Flow Rate [W-s/m3] Motor Heat In Air Fraction Fan Energy Index End Use Subcategory Design Day Name for Fan Sizing Peak Date/Time for Fan Sizing Peak
LAUNDRY_FLR_1 EXHAUST FAN Fan:ZoneExhaust 0.16 125.00 0.24 184.35 781.25 1.00 1.15 General    
LOBBY_FLR_1 EXHAUST FAN Fan:ZoneExhaust 1.00 0.00 0.00 0.00   1.00 0.00 General    
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.16 270.90 1.05 1775.31 1693.12 1.00 0.49 General MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.16 270.90 1.06 1792.80 1693.12 1.00 0.49 General MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:10:00
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.16 270.90 5.95 10080.83 1693.12 1.00 0.40 General MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:50:00
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.16 270.90 6.95 11766.20 1693.12 1.00 0.39 General MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:40:00
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.16 270.90 0.94 1595.96 1693.12 1.00 0.50 General MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:00:00
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.16 270.90 0.95 1609.46 1693.12 1.00 0.50 General MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:00:00
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.16 270.90 0.28 474.51 1693.12 1.00 0.73 General MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.16 270.90 0.28 478.73 1693.12 1.00 0.73 General MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.16 270.90 1.17 1973.24 1693.12 1.00 0.48 General MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:40:00
BANQUET_FLR_6 EXHAUST FAN Fan:ZoneExhaust 1.00 0.00 0.00 0.00   1.00 0.00 General    
DINING_FLR_6 EXHAUST FAN Fan:ZoneExhaust 1.00 0.00 0.00 0.00   1.00 0.00 General    
KITCHEN_FLR_6 EXHAUST FAN Fan:ZoneExhaust 0.16 125.00 1.89 1474.84 781.25 1.00 0.62 General    
VAV WITH REHEAT FAN Fan:VariableVolume 0.62 1389.42 21.22 47540.86 2240.64 1.00 1.11 General MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 04:30:00
FLR_3_DOAS FAN Fan:ConstantVolume 0.58 622.50 2.05 2194.93 1070.05 1.00 1.30 General MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 23:40:00


Pumps

Type Control Head [pa] Water Flow [m3/s] Electricity Rate [W] Power Per Water Flow Rate [W-s/m3] Motor Efficiency [W/W] End Use Subcategory
COOLSYS1 PUMP SECONDARY Pump:VariableSpeed Intermittent 133527.72 0.053450 11014.04 206062.94 0.90 General
HEATSYS1 PUMP Pump:VariableSpeed Intermittent 180705.70 0.002439 734.63 301156.09 0.90 General
COOLSYS1 PUMP Pump:ConstantSpeed Intermittent 92445.74 0.053450 7625.39 142664.32 0.90 General
SWHSYS1 PUMP Pump:ConstantSpeed Intermittent 29891.00 0.000375 47.91 127739.32 0.30 General


Service Water Heating

Type Storage Volume [m3] Input [W] Thermal Efficiency [W/W] Recovery Efficiency [W/W] Energy Factor
SWH BOOSTER E WATER HEATER WaterHeater:Mixed 0.02 8000.00 1.00 1.24 1.15
SWH LAUNDRY G WATER HEATER WaterHeater:Mixed 1.14 163316.00 0.80 0.58 0.51
SWHSYS1 WATER HEATER WaterHeater:Mixed 2.27 175842.60 0.80 0.26 0.03



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2023-10-16 08:58:20

Zone Sensible Cooling

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
BASEMENT 36589.01 36589.01 18.49 2.662 2.662 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 20:50:00 24.00 24.00 0.00916 29.35 0.01716 0.854 0.00
RETAIL_1_FLR_1 4035.58 4035.58 60.17 0.294 0.294 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:20:00 24.00 24.00 0.00953 33.20 0.01717 0.079 0.00
RETAIL_2_FLR_1 3329.51 3329.51 42.87 0.242 0.242 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:50:00 24.00 24.00 0.00955 31.70 0.01716 0.092 0.00
MECH_FLR_1 3594.32 3594.32 21.88 0.261 0.261 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:50:00 24.00 24.00 0.00913 30.75 0.01716 0.000 0.00
STORAGE_FLR_1 1794.42 1794.42 18.94 0.131 0.131 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 24.00 24.00 0.00928 31.93 0.01716 0.058 0.00
LAUNDRY_FLR_1 44900.52 44900.52 575.36 3.267 3.267 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 15:20:00 24.00 24.00 0.00860 33.07 0.01717 0.000 0.00
CAFE_FLR_1 17983.23 17983.23 95.22 1.310 1.310 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:20:00 24.00 23.99 0.01047 33.20 0.01717 0.676 0.00
LOBBY_FLR_1 62635.18 62635.18 47.88 4.558 4.558 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:40:00 24.00 23.99 0.01019 33.20 0.01717 1.894 0.00
ROOM_1_FLR_3 10694.98 10694.98 274.08 1.049 1.049 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00 21.11 21.11 0.00887 32.26 0.01717 0.062 0.00
ROOM_2_FLR_3 10800.34 10800.34 276.81 1.059 1.059 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:10:00 21.11 21.11 0.00887 32.15 0.01717 0.062 0.00
ROOM_3_MULT19_FLR_3 60738.63 60738.63 2476.72 5.954 5.954 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:50:00 21.11 21.11 0.00878 33.20 0.01717 0.837 0.00
ROOM_4_MULT19_FLR_3 70888.06 70888.06 2889.79 6.949 6.949 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:40:00 21.11 21.11 0.00894 31.82 0.01716 0.837 0.00
ROOM_5_FLR_3 9614.47 9614.47 246.39 0.943 0.943 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:00:00 21.11 21.11 0.00891 30.65 0.01716 0.062 0.00
ROOM_6_FLR_3 9695.84 9695.84 248.50 0.951 0.951 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:00:00 21.11 21.11 0.00891 30.65 0.01716 0.062 0.00
CORRIDOR_FLR_3 15134.37 15134.37 38.87 1.101 1.101 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00 24.00 24.00 0.01006 32.26 0.01717 0.475 0.00
ROOM_1_FLR_6 2858.57 2858.57 73.26 0.280 0.280 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00 21.11 21.11 0.00885 32.26 0.01717 0.015 0.00
ROOM_2_FLR_6 2884.01 2884.01 73.92 0.283 0.283 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00 21.11 21.11 0.00885 32.26 0.01717 0.015 0.00
ROOM_3_MULT9_FLR_6 11887.52 11887.52 484.60 1.165 1.165 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:40:00 21.11 21.11 0.00895 33.20 0.01717 0.099 0.00
BANQUET_FLR_6 30711.74 30711.74 92.60 2.237 2.237 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:40:00 24.00 23.98 0.01041 33.20 0.01717 1.188 0.00
DINING_FLR_6 32227.39 32227.39 97.17 2.347 2.347 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:40:00 24.00 23.98 0.01032 33.20 0.01717 1.188 0.00
KITCHEN_FLR_6 30873.18 30873.18 298.86 2.252 2.252 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 12:30:00 24.00 23.97 0.01014 32.60 0.01717 0.367 0.00
CORRIDOR_FLR_6 9118.14 9118.14 22.12 0.663 0.663 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:40:00 24.00 24.00 0.00930 33.20 0.01717 0.126 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

Zone Sensible Heating

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
BASEMENT 0.00 0.00 0.00 0.000 0.854   00:10:00 21.00 23.64 0.00699 8.70 0.00699 0.854 0.00
RETAIL_1_FLR_1 1572.81 1572.81 23.45 0.067 0.079 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 23:40:00 21.00 21.00 0.00779 8.70 0.00699 0.079 0.00
RETAIL_2_FLR_1 502.99 502.99 6.48 0.022 0.092 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 23:40:00 21.00 21.00 0.00775 8.70 0.00699 0.092 0.00
MECH_FLR_1 925.33 925.33 5.63 0.040 0.040 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 23:40:00 21.00 21.00 0.00770 8.70 0.00699 0.000 0.00
STORAGE_FLR_1 543.48 543.48 5.74 0.023 0.058 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 23:40:00 21.00 21.00 0.00771 8.70 0.00699 0.058 0.00
LAUNDRY_FLR_1 1311.94 1311.94 16.81 0.056 0.056 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 23:40:00 21.00 21.00 0.00771 8.70 0.00699 0.000 0.00
CAFE_FLR_1 3920.76 3920.76 20.76 0.168 0.676 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 23:40:00 21.00 21.00 0.00781 8.70 0.00699 0.676 0.00
LOBBY_FLR_1 8822.88 8822.88 6.74 0.379 1.894 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 23:40:00 21.00 21.00 0.00777 8.70 0.00699 1.894 0.00
ROOM_1_FLR_3 3659.98 3659.98 93.79 0.158 0.158 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 23:40:00 21.11 21.11 0.00779 8.70 0.00699 0.062 0.00
ROOM_2_FLR_3 3660.21 3660.21 93.81 0.158 0.158 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 23:40:00 21.11 21.11 0.00779 8.70 0.00699 0.062 0.00
ROOM_3_MULT19_FLR_3 21298.60 21298.60 868.49 0.919 0.919 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 23:40:00 21.11 21.11 0.00780 8.70 0.00699 0.837 0.00
ROOM_4_MULT19_FLR_3 21316.21 21316.21 868.97 0.920 0.920 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 23:40:00 21.11 21.11 0.00780 8.70 0.00699 0.837 0.00
ROOM_5_FLR_3 3659.02 3659.02 93.77 0.158 0.158 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 23:40:00 21.11 21.11 0.00779 8.70 0.00699 0.062 0.00
ROOM_6_FLR_3 3659.25 3659.25 93.78 0.158 0.158 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 23:40:00 21.11 21.11 0.00779 8.70 0.00699 0.062 0.00
CORRIDOR_FLR_3 5760.67 5760.67 14.79 0.247 0.475 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.00 21.00 0.00783 8.70 0.00699 0.475 0.00
ROOM_1_FLR_6 1124.66 1124.66 28.82 0.049 0.049 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 23:40:00 21.11 21.11 0.00782 8.70 0.00699 0.015 0.00
ROOM_2_FLR_6 1124.89 1124.89 28.83 0.049 0.049 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 23:40:00 21.11 21.11 0.00782 8.70 0.00699 0.015 0.00
ROOM_3_MULT9_FLR_6 5435.92 5435.92 221.60 0.235 0.235 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 23:40:00 21.11 21.11 0.00783 8.70 0.00699 0.099 0.00
BANQUET_FLR_6 3704.58 3704.58 11.17 0.159 1.188 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 23:40:00 21.00 21.00 0.00786 8.70 0.00699 1.188 0.00
DINING_FLR_6 3634.68 3634.68 10.96 0.156 1.188 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 04:20:00 21.00 21.00 0.00786 8.70 0.00699 1.188 0.00
KITCHEN_FLR_6 0.00 0.00 0.00 0.000 0.367   00:10:00 21.00 23.42 0.00675 8.70 0.00699 0.367 0.00
CORRIDOR_FLR_6 3842.74 3842.74 9.32 0.165 0.165 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 04:30:00 21.00 21.00 0.00788 8.70 0.00699 0.126 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

System Design Air Flow Rates

Calculated cooling [m3/s] User cooling [m3/s] Calculated heating [m3/s] User heating [m3/s] Adjusted cooling [m3/s] Adjusted heating [m3/s] Adjusted main [m3/s] Calculated Heating Air Flow Ratio [] User Heating Air Flow Ratio []
VAV WITH REHEAT 21.21 21.21 7.13 7.13 21.2175 21.2175 21.2175 1.0000 0.3000
FLR_3_DOAS 18.18 2.05 2.80 2.05 2.0513 2.0513 2.0513 1.0000 0.3000


Plant Loop Coincident Design Fluid Flow Rate Adjustments

Previous Design Volume Flow Rate [m3/s] Algorithm Volume Flow Rate [m3/s] Coincident Design Volume Flow Rate [m3/s] Coincident Size Adjusted Peak Sizing Period Name Peak Day into Period {TIMESTAMP}[day] Peak Hour Of Day {TIMESTAMP}[hr] Peak Step Start Minute {TIMESTAMP}[min]
None                


Coil Sizing Summary

Coil Type HVAC Type HVAC Name Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Flow Percentage at Ideal Loads Peak [%] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W]
BASEMENT VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT BASEMENT VAV BOX 13966.408 13966.408 2.648302 0.00012218 291.245   1/21 00:10:00   1/21 00:10:00 13966.41 13966.41 2.648302 16.70 13.18 0.00800000 40.00 21.17 0.00800000 8.70 0.00699286 8.70 0.0000 21.00 0.00800000 51.6560 0.00 0.00 14044.90 14044.90
RETAIL_1_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT RETAIL_1_FLR_1 VAV BOX 3112.969 3112.969 0.292169 0.00002723 68.557 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 23:40:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 23:40:00 3112.97 3112.97 0.292169 16.70 13.18 0.00800000 40.00 21.17 0.00800000 8.70 0.00699286 8.70 0.0000 21.00 0.00778658 50.2955 1572.81 0.00 3129.94 3129.94
RETAIL_2_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT RETAIL_2_FLR_1 VAV BOX 1773.525 1773.525 0.241029 0.00001552 37.759 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 23:40:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 23:40:00 1773.53 1773.53 0.241029 16.70 13.18 0.00800000 40.00 21.17 0.00800000 8.70 0.00699286 8.70 0.0000 21.00 0.00775321 50.0823 502.99 0.00 1783.42 1783.42
MECH_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT MECH_FLR_1 VAV BOX 2296.520 2296.520 0.260148 0.00002009 49.630 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 23:40:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 23:40:00 2296.52 2296.52 0.260148 16.70 13.18 0.00800000 40.00 21.17 0.00800000 8.70 0.00699286 8.70 0.0000 21.00 0.00770362 49.7659 925.33 0.00 2309.28 2309.28
STORAGE_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT STORAGE_FLR_1 VAV BOX 1228.034 1228.034 0.129877 0.00001074 26.712 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 23:40:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 23:40:00 1228.03 1228.03 0.129877 16.70 13.18 0.00800000 40.00 21.17 0.00800000 8.70 0.00699286 8.70 0.0000 21.00 0.00770734 49.7896 543.48 0.00 1234.84 1234.84
LAUNDRY_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 18443.649 18443.649 3.250336 0.00016135 386.131 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 23:40:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 23:40:00 18443.65 18443.65 3.250336 16.70 13.18 0.00800000 40.00 21.17 0.00800000 8.70 0.00699286 8.70 0.0000 21.00 0.00771145 49.8162 1311.94 0.00 18547.16 18547.16
CAFE_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CAFE_FLR_1 VAV BOX 10789.676 10789.676 1.302981 0.00009439 231.875 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 23:40:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 23:40:00 10789.68 10789.68 1.302981 16.70 13.18 0.00800000 40.00 21.17 0.00800000 8.70 0.00699286 8.70 0.0000 21.00 0.00780610 50.4199 3920.76 0.00 10849.71 10849.71
LOBBY_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 32731.436 32731.436 4.535523 0.00028635 695.871 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 23:40:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 23:40:00 32731.44 32731.44 4.535523 16.70 13.18 0.00800000 40.00 21.17 0.00800000 8.70 0.00699286 8.70 0.0000 21.00 0.00776594 50.1635 8822.88 0.00 32914.17 32914.17
ROOM_1_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_3 FAN COIL 13663.360 -999.000 1.048541 0.00048801 -999.000 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00 unknown 7/21 17:00:00 13663.36 12592.17 1.048541 22.49 16.16 0.00887242 12.80 12.09 0.00850000 32.26 0.01716543 25.09 0.0000 21.11 0.00887242 56.8280 10694.98 0.00 13687.30 12460.69
ROOM_1_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_3 FAN COIL 3659.956 3659.956 0.157984 0.00003202 104.574 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 23:40:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 23:40:00 3659.96 3659.96 0.157984 21.11 14.69 0.00778795 40.00 21.17 0.00800000 8.70 0.00699286 8.70 0.0000 21.11 0.00778795 49.9624 3659.98 0.00 3945.55 3945.55
ROOM_2_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_3 FAN COIL 13785.907 -999.000 1.058870 0.00049239 -999.000 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:10:00 unknown 7/21 17:10:00 13785.91 12715.09 1.058870 22.49 16.16 0.00886870 12.80 12.09 0.00850000 32.15 0.01716522 25.06 0.0000 21.11 0.00886870 56.8045 10800.34 0.00 13810.07 12581.76
ROOM_2_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_3 FAN COIL 3660.184 3660.184 0.157994 0.00003202 104.581 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 23:40:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 23:40:00 3660.18 3660.18 0.157994 21.11 14.69 0.00778797 40.00 21.17 0.00800000 8.70 0.00699286 8.70 0.0000 21.11 0.00778797 49.9626 3660.21 0.00 3945.80 3945.80
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT19_FLR_3 FAN COIL 75998.167 -999.000 5.953979 0.00271443 -999.000 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:50:00 unknown 7/21 14:50:00 75998.17 71358.40 5.953979 22.49 16.08 0.00878469 12.80 12.09 0.00850000 33.20 0.01716721 25.32 0.0000 21.11 0.00878469 56.2698 60738.63 0.00 76133.27 70537.47
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT19_FLR_3 FAN COIL 21298.526 21298.526 0.919369 0.00018633 608.547 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 23:40:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 23:40:00 21298.53 21298.53 0.919369 21.11 14.70 0.00780313 40.00 21.17 0.00800000 8.70 0.00699286 8.70 0.0000 21.11 0.00780313 50.0583 21298.60 0.00 22960.55 22960.55
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_4_MULT19_FLR_3 FAN COIL 92061.169 -999.000 6.949400 0.00328815 -999.000 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:40:00 unknown 7/21 17:40:00 92061.17 83600.84 6.949400 22.49 16.22 0.00894306 12.80 12.09 0.00850000 31.82 0.01716457 24.97 0.0000 21.11 0.00894306 57.2720 70888.06 0.00 92220.62 82796.81
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_4_MULT19_FLR_3 FAN COIL 21316.133 21316.133 0.920129 0.00018648 609.050 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 23:40:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 23:40:00 21316.13 21316.13 0.920129 21.11 14.70 0.00780322 40.00 21.17 0.00800000 8.70 0.00699286 8.70 0.0000 21.11 0.00780322 50.0589 21316.21 0.00 22979.53 22979.53
ROOM_5_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_5_FLR_3 FAN COIL 12405.479 -999.000 0.942610 0.00044309 -999.000 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:00:00 unknown 7/21 10:00:00 12405.48 11331.41 0.942610 22.49 16.20 0.00891497 12.80 12.09 0.00850000 30.65 0.01716236 24.67 0.0000 21.11 0.00891497 57.0968 9614.47 0.00 12427.06 11218.75
ROOM_5_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_5_FLR_3 FAN COIL 3658.994 3658.994 0.157943 0.00003201 104.547 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 23:40:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 23:40:00 3658.99 3658.99 0.157943 21.11 14.69 0.00778790 40.00 21.17 0.00800000 8.70 0.00699286 8.70 0.0000 21.11 0.00778790 49.9622 3659.02 0.00 3944.52 3944.52
ROOM_6_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_6_FLR_3 FAN COIL 12501.428 -999.000 0.950587 0.00044651 -999.000 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:00:00 unknown 7/21 10:00:00 12501.43 11426.47 0.950587 22.49 16.19 0.00891185 12.80 12.09 0.00850000 30.65 0.01716236 24.67 0.0000 21.11 0.00891185 57.0771 9695.84 0.00 12523.19 11312.46
ROOM_6_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_6_FLR_3 FAN COIL 3659.223 3659.223 0.157953 0.00003201 104.553 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 23:40:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 23:40:00 3659.22 3659.22 0.157953 21.11 14.69 0.00778793 40.00 21.17 0.00800000 8.70 0.00699286 8.70 0.0000 21.11 0.00778793 49.9623 3659.25 0.00 3944.76 3944.76
CORRIDOR_FLR_3 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORRIDOR_FLR_3 VAV BOX 11535.774 11535.774 1.095430 0.00010092 253.723 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 11535.77 11535.77 1.095430 16.70 13.18 0.00800000 40.00 21.17 0.00800000 8.70 0.00699286 8.70 0.0000 21.00 0.00782775 50.5578 5760.67 0.00 11598.70 11598.70
ROOM_1_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_6 FAN COIL 3632.372 -999.000 0.280254 0.00012974 -999.000 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00 unknown 7/21 17:00:00 3632.37 3363.80 0.280254 22.49 16.14 0.00884955 12.80 12.09 0.00850000 32.26 0.01716543 25.09 0.0000 21.11 0.00884955 56.6835 2858.57 0.00 3638.76 3327.75
ROOM_1_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_6 FAN COIL 1124.655 1124.655 0.048546 0.00000984 32.134 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 23:40:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 23:40:00 1124.65 1124.65 0.048546 21.11 14.72 0.00782040 40.00 21.17 0.00800000 8.70 0.00699286 8.70 0.0000 21.11 0.00782040 50.1681 1124.66 0.00 1212.41 1212.41
ROOM_2_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_6 FAN COIL 3661.774 -999.000 0.282749 0.00013079 -999.000 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00 unknown 7/21 17:00:00 3661.77 3393.46 0.282749 22.49 16.14 0.00884615 12.80 12.09 0.00850000 32.26 0.01716543 25.09 0.0000 21.11 0.00884615 56.6621 2884.01 0.00 3668.22 3356.97
ROOM_2_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_6 FAN COIL 1124.882 1124.882 0.048556 0.00000984 32.140 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 23:40:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 23:40:00 1124.88 1124.88 0.048556 21.11 14.72 0.00782044 40.00 21.17 0.00800000 8.70 0.00699286 8.70 0.0000 21.11 0.00782044 50.1683 1124.89 0.00 1212.66 1212.66
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT9_FLR_6 FAN COIL 15472.292 -999.000 1.165445 0.00055262 -999.000 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:40:00 unknown 7/21 14:40:00 15472.29 14022.61 1.165445 22.49 16.23 0.00895259 12.80 12.09 0.00850000 33.20 0.01716721 25.32 0.0000 21.11 0.00895259 57.3340 11887.52 0.00 15499.05 13889.27
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT9_FLR_6 FAN COIL 5435.884 5435.884 0.234644 0.00004756 155.313 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 23:40:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 23:40:00 5435.88 5435.88 0.234644 21.11 14.72 0.00782744 40.00 21.17 0.00800000 8.70 0.00699286 8.70 0.0000 21.11 0.00782744 50.2126 5435.92 0.00 5860.06 5860.06
BANQUET_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 15438.992 15438.992 2.225678 0.00013507 327.312 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 23:40:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 23:40:00 15438.99 15438.99 2.225678 16.70 13.18 0.00800000 40.00 21.17 0.00800000 8.70 0.00699286 8.70 0.0000 21.00 0.00785972 50.7617 3704.58 0.00 15525.26 15525.26
DINING_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 15947.956 15947.956 2.335481 0.00013952 337.735 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 04:20:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 04:20:00 15947.96 15947.96 2.335481 16.70 13.18 0.00800000 40.00 21.17 0.00800000 8.70 0.00699286 8.70 0.0000 21.00 0.00785734 50.7466 3634.68 0.00 16037.10 16037.10
KITCHEN_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown 11816.389 11816.389 2.240617 0.00010337 246.410   1/21 00:10:00   1/21 00:10:00 11816.39 11816.39 2.240617 16.70 13.18 0.00800000 40.00 21.17 0.00800000 8.70 0.00699286 8.70 0.0000 21.00 0.00800000 51.6560 0.00 0.00 11882.80 11882.80
CORRIDOR_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORRIDOR_FLR_6 VAV BOX 7322.429 7322.429 0.659978 0.00006406 162.012 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 04:30:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 04:30:00 7322.43 7322.43 0.659978 16.70 13.18 0.00800000 40.00 21.17 0.00800000 8.70 0.00699286 8.70 0.0000 21.00 0.00787883 50.8838 3842.74 0.00 7362.27 7362.27
VAV WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoopHVAC VAV WITH REHEAT 1144947.372 -999.000 21.217549 0.04089487 -999.000 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:50:00 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:50:00 1144947.37 570594.23 21.217549 33.20 25.32 0.01716721 11.00 11.00 0.00850000 33.20 0.01716721 25.32 99.9761 23.99 0.00983433 52.7915 291395.06 0.00 1146407.07 577418.59
VAV WITH REHEAT HEATING COIL Coil:Heating:Water AirLoopHVAC VAV WITH REHEAT 61543.584 61543.584 6.365265 0.00053841 1142.024 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 04:30:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 04:30:00 61543.58 61543.58 6.365265 8.70 8.70 0.00699286 16.70 13.18 0.00800000 8.70 0.00699286 8.70 333.2535 22.68 0.00711736 41.5360 34496.53 0.00 66715.09 66715.09
FLR_3_DOAS COOLING COIL Coil:Cooling:Water AirLoopHVAC FLR_3_DOAS 108329.821 -999.000 2.051317 0.00386929 -999.000 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 16:40:00 108329.82 53987.08 2.051317 33.20 25.32 0.01716721 11.94 11.73 0.00850000 33.20 0.01716721 25.32 99.9965 21.11 0.00887395 56.8347 184267.17 0.00 108457.34 54776.98
FLR_3_DOAS HEATING COIL Coil:Heating:Water AirLoopHVAC FLR_3_DOAS 5950.047 5950.047 0.615395 0.00005205 110.411 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 23:40:00 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 23:40:00 5950.05 5950.05 0.615395 8.70 8.70 0.00699286 16.70 13.18 0.00800000 8.70 0.00699286 8.70 333.3216 21.11 0.00780327 50.0592 64938.74 0.00 6450.03 6450.03



Table of Contents

Report: Coil Sizing Details

For: Entire Facility

Timestamp: 2023-10-16 08:58:20

Coils

Coil Type Coil Location HVAC Type HVAC Name Zone Name(s) System Sizing Method Concurrence System Sizing Method Capacity System Sizing Method Air Flow Autosized Coil Capacity? Autosized Coil Airflow? Autosized Coil Water Flow? OA Pretreated prior to coil inlet? Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Terminal Unit Reheat Coil Multiplier DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio Moist Air Heat Capacity [J/kg-K] Dry Air Heat Capacity [J/kg-K] Standard Air Density Adjusted for Elevation [kg/m3] Supply Fan Name for Coil Supply Fan Type for Coil Supply Fan Maximum Air Volume Flow Rate [m3/s] Supply Fan Maximum Air Mass Flow Rate [kg/s] Plant Name for Coil Plant Fluid Specific Heat Capacity [J/kg-K] Plant Fluid Density [kg/m3] Plant Maximum Fluid Mass Flow Rate [kg/s] Plant Design Fluid Return Temperature [C] Plant Design Fluid Supply Temperature [C] Plant Design Fluid Temperature Difference [deltaC] Plant Design Capacity [W] Coil Capacity Percentage of Plant Design Capacity [%] Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Total Ideal Loads Peak Date/Time at Total Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Peak Load Type to Size On Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] Supply Fan Air Heat Gain at Ideal Loads Peak [W] Coil and Fan Net Total Capacity at Ideal Loads Peak [W] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] Outdoor Air Flow Percentage at Ideal Loads Peak [%] System Return Air Drybulb at Ideal Loads Peak [C] System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W] Coil Air Mass Flow Rate at Rating Conditions [kg/s] Coil Entering Air Drybulb at Rating Conditions [C] Coil Entering Air Wetbulb at Rating Conditions [C] Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] Coil Leaving Air Drybulb at Rating Conditions [C] Coil Leaving Air Wetbulb at Rating Conditions [C] Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K]
BASEMENT VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT BASEMENT VAV BOX BASEMENT N/A N/A N/A Yes Yes Yes No 13966.408 13966.408 2.648302 0.00012218 291.245 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.43912859 54.44 82.22 27.78 284447.51 4.9100 5.008828   1/21 00:10:00 unknown unknown   1/21 00:10:00 Sensible 13966.41 13966.41 1.0000 3.18521618 2.648302 16.70 13.18 0.00800000 37036.7 40.00 21.17 0.00800000 60796.0 0.12217177 60.00 32.22 27.78 0.000 13966.41 8.70 0.00699286 8.70 0.00000000 0.0000 21.00 0.00800000 21.00 0.00800000 51.6560 0.00 0.00 14044.90 14044.90 3.18521618 16.60 13.15 0.00800000 36934.7 20.92 14.82 0.00800000 41344.1
RETAIL_1_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT RETAIL_1_FLR_1 VAV BOX RETAIL_1_FLR_1 N/A N/A N/A Yes Yes Yes No 3112.969 3112.969 0.292169 0.00002723 68.557 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.43912859 54.44 82.22 27.78 284447.51 1.0944 1.116416 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 23:40:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 23:40:00 Sensible 3112.97 3112.97 1.0000 0.35140350 0.292169 16.70 13.18 0.00800000 37036.7 40.00 21.17 0.00800000 60796.0 0.02723083 60.00 32.22 27.78 0.000 3112.97 8.70 0.00699286 8.70 0.00000000 0.0000 21.00 0.00778658 21.00 0.00778658 50.2955 1572.81 0.00 3129.94 3129.94 0.35140350 16.60 13.15 0.00800000 36934.7 25.33 16.43 0.00800000 45841.7
RETAIL_2_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT RETAIL_2_FLR_1 VAV BOX RETAIL_2_FLR_1 N/A N/A N/A Yes Yes Yes No 1773.525 1773.525 0.241029 0.00001552 37.759 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.43912859 54.44 82.22 27.78 284447.51 0.6235 0.636046 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 23:40:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 23:40:00 Sensible 1773.53 1773.53 1.0000 0.28989545 0.241029 16.70 13.18 0.00800000 37036.7 40.00 21.17 0.00800000 60796.0 0.01551399 60.00 32.22 27.78 0.000 1773.53 8.70 0.00699286 8.70 0.00000000 0.0000 21.00 0.00775321 21.00 0.00775321 50.0823 502.99 0.00 1783.42 1783.42 0.28989545 16.60 13.15 0.00800000 36934.7 22.63 15.46 0.00800000 43086.7
MECH_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT MECH_FLR_1 VAV BOX MECH_FLR_1 N/A N/A N/A Yes Yes Yes No 2296.520 2296.520 0.260148 0.00002009 49.630 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.43912859 54.44 82.22 27.78 284447.51 0.8074 0.823610 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 23:40:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 23:40:00 Sensible 2296.52 2296.52 1.0000 0.31289003 0.260148 16.70 13.18 0.00800000 37036.7 40.00 21.17 0.00800000 60796.0 0.02008891 60.00 32.22 27.78 0.000 2296.52 8.70 0.00699286 8.70 0.00000000 0.0000 21.00 0.00770362 21.00 0.00770362 49.7659 925.33 0.00 2309.28 2309.28 0.31289003 16.60 13.15 0.00800000 36934.7 23.84 15.90 0.00800000 44315.2
STORAGE_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT STORAGE_FLR_1 VAV BOX STORAGE_FLR_1 N/A N/A N/A Yes Yes Yes No 1228.034 1228.034 0.129877 0.00001074 26.712 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.43912859 54.44 82.22 27.78 284447.51 0.4317 0.440415 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 23:40:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 23:40:00 Sensible 1228.03 1228.03 1.0000 0.15620762 0.129877 16.70 13.18 0.00800000 37036.7 40.00 21.17 0.00800000 60796.0 0.01074228 60.00 32.22 27.78 0.000 1228.03 8.70 0.00699286 8.70 0.00000000 0.0000 21.00 0.00770734 21.00 0.00770734 49.7896 543.48 0.00 1234.84 1234.84 0.15620762 16.60 13.15 0.00800000 36934.7 24.35 16.08 0.00800000 44839.9
LAUNDRY_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown LAUNDRY_FLR_1 N/A N/A N/A Yes Yes Yes No 18443.649 18443.649 3.250336 0.00016135 386.131 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.43912859 54.44 82.22 27.78 284447.51 6.4840 6.614519 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 23:40:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 23:40:00 Sensible 18443.65 18443.65 1.0000 3.90930530 3.250336 16.70 13.18 0.00800000 37036.7 40.00 21.17 0.00800000 60796.0 0.16133663 60.00 32.22 27.78 0.000 18443.65 8.70 0.00699286 8.70 0.00000000 0.0000 21.00 0.00771145 21.00 0.00771145 49.8162 1311.94 0.00 18547.16 18547.16 3.90930530 16.60 13.15 0.00800000 36934.7 21.25 14.95 0.00800000 41679.1
CAFE_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CAFE_FLR_1 VAV BOX CAFE_FLR_1 N/A N/A N/A Yes Yes Yes No 10789.676 10789.676 1.302981 0.00009439 231.875 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.43912859 54.44 82.22 27.78 284447.51 3.7932 3.869544 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 23:40:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 23:40:00 Sensible 10789.68 10789.68 1.0000 1.56714602 1.302981 16.70 13.18 0.00800000 37036.7 40.00 21.17 0.00800000 60796.0 0.09438316 60.00 32.22 27.78 0.000 10789.68 8.70 0.00699286 8.70 0.00000000 0.0000 21.00 0.00780610 21.00 0.00780610 50.4199 3920.76 0.00 10849.71 10849.71 1.56714602 16.60 13.15 0.00800000 36934.7 23.39 15.73 0.00800000 43858.0
LOBBY_FLR_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown LOBBY_FLR_1 N/A N/A N/A Yes Yes Yes No 32731.436 32731.436 4.535523 0.00028635 695.871 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.43912859 54.44 82.22 27.78 284447.51 11.5070 11.738605 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 23:40:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 23:40:00 Sensible 32731.44 32731.44 1.0000 5.45505043 4.535523 16.70 13.18 0.00800000 37036.7 40.00 21.17 0.00800000 60796.0 0.28631967 60.00 32.22 27.78 0.000 32731.44 8.70 0.00699286 8.70 0.00000000 0.0000 21.00 0.00776594 21.00 0.00776594 50.1635 8822.88 0.00 32914.17 32914.17 5.45505043 16.60 13.15 0.00800000 36934.7 22.52 15.42 0.00800000 42968.4
ROOM_1_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_3 FAN COIL ROOM_1_FLR_3 N/A N/A N/A Yes Yes Yes No 13663.360 -999.000 1.048541 0.00048801 -999.000 -999.0000 1.00000 1.00000 1021.3334 1004.8586 1.2027 ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 1.048541 1.26112051   4197.9300 999.8980 53.44443855 13.37 6.70 6.67 1496454.60 0.9130 0.913032 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00 unknown unknown unknown 7/21 17:00:00 Sensible 13663.36 12592.17 1.0000 1.26112051 1.048541 22.49 16.16 0.00887242 45156.5 12.80 12.09 0.00850000 34322.2 0.48796466 6.70 13.37 6.67 0.000 13663.36 32.26 0.01716543 25.09 0.00000000 0.0000 21.11 0.00887242 21.11 0.00887242 56.8280 10694.98 0.00 13687.30 12460.69 1.26112051 22.49 16.17 0.00887242 45156.5 12.81 12.09 0.00848718 34303.2
ROOM_1_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_3 FAN COIL ROOM_1_FLR_3 N/A N/A N/A Yes Yes Yes No 3659.956 3659.956 0.157984 0.00003202 104.574 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 1.048541 1.26112051   4197.9300 999.8980 2.43912859 54.44 82.22 27.78 284447.51 1.2867 1.312585 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 23:40:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 23:40:00 Sensible 3659.96 3659.96 1.0000 0.19001373 0.157984 21.11 14.69 0.00778795 40995.8 40.00 21.17 0.00800000 60796.0 0.03201562 60.00 32.22 27.78 0.000 3659.96 8.70 0.00699286 8.70 0.00000000 0.0000 21.11 0.00778795 21.11 0.00778795 49.9624 3659.98 0.00 3945.55 3945.55 0.19001373 16.60 12.94 0.00778795 36397.9 36.97 20.11 0.00778795 57162.4
ROOM_2_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_3 FAN COIL ROOM_2_FLR_3 N/A N/A N/A Yes Yes Yes No 13785.907 -999.000 1.058870 0.00049239 -999.000 -999.0000 1.00000 1.00000 1021.3265 1004.8586 1.2027 ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 1.058870 1.27354379   4197.9300 999.8980 53.44443855 13.37 6.70 6.67 1496454.60 0.9212 0.921221 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:10:00 unknown unknown unknown 7/21 17:10:00 Sensible 13785.91 12715.09 1.0000 1.27354379 1.058870 22.49 16.16 0.00886870 45147.0 12.80 12.09 0.00850000 34322.2 0.49234123 6.70 13.37 6.67 0.000 13785.91 32.15 0.01716522 25.06 0.00000000 0.0000 21.11 0.00886870 21.11 0.00886870 56.8045 10800.34 0.00 13810.07 12581.76 1.27354379 22.49 16.17 0.00886870 45147.0 12.81 12.09 0.00848668 34303.2
ROOM_2_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_3 FAN COIL ROOM_2_FLR_3 N/A N/A N/A Yes Yes Yes No 3660.184 3660.184 0.157994 0.00003202 104.581 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 1.058870 1.27354379   4197.9300 999.8980 2.43912859 54.44 82.22 27.78 284447.51 1.2868 1.312666 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 23:40:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 23:40:00 Sensible 3660.18 3660.18 1.0000 0.19002560 0.157994 21.11 14.69 0.00778797 40995.9 40.00 21.17 0.00800000 60796.0 0.03201762 60.00 32.22 27.78 0.000 3660.18 8.70 0.00699286 8.70 0.00000000 0.0000 21.11 0.00778797 21.11 0.00778797 49.9626 3660.21 0.00 3945.80 3945.80 0.19002560 16.60 12.94 0.00778797 36397.9 36.97 20.11 0.00778797 57162.5
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT19_FLR_3 FAN COIL ROOM_3_MULT19_FLR_3 N/A N/A N/A Yes Yes Yes No 75998.167 -999.000 5.953979 0.00271443 -999.000 -999.0000 1.00000 1.00000 1021.1703 1004.8586 1.2027 ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 5.953979 7.16108280   4197.9300 999.8980 53.44443855 13.37 6.70 6.67 1496454.60 5.0785 5.078453 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:50:00 unknown unknown unknown 7/21 14:50:00 Sensible 75998.17 71358.40 1.0000 7.16108280 5.953979 22.49 16.08 0.00878469 44934.9 12.80 12.09 0.00850000 34322.2 2.71415086 6.70 13.37 6.67 0.000 75998.17 33.20 0.01716721 25.32 0.00000000 0.0000 21.11 0.00878469 21.11 0.00878469 56.2698 60738.63 0.00 76133.27 70537.47 7.16108280 22.49 16.10 0.00878469 44934.9 12.84 12.09 0.00847520 34303.3
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT19_FLR_3 FAN COIL ROOM_3_MULT19_FLR_3 N/A N/A N/A Yes Yes Yes No 21298.526 21298.526 0.919369 0.00018633 608.547 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 5.953979 7.16108280   4197.9300 999.8980 2.43912859 54.44 82.22 27.78 284447.51 7.4877 7.638375 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 23:40:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 23:40:00 Sensible 21298.53 21298.53 1.0000 1.10576053 0.919369 21.11 14.70 0.00780313 41034.5 40.00 21.17 0.00800000 60796.0 0.18630979 60.00 32.22 27.78 0.000 21298.53 8.70 0.00699286 8.70 0.00000000 0.0000 21.11 0.00780313 21.11 0.00780313 50.0583 21298.60 0.00 22960.55 22960.55 1.10576053 16.60 12.96 0.00780313 36436.3 36.97 20.12 0.00780313 57200.8
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_4_MULT19_FLR_3 FAN COIL ROOM_4_MULT19_FLR_3 N/A N/A N/A Yes Yes Yes No 92061.169 -999.000 6.949400 0.00328815 -999.000 -999.0000 1.00000 1.00000 1021.4647 1004.8586 1.2027 ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 6.949400 8.35831450   4197.9300 999.8980 53.44443855 13.37 6.70 6.67 1496454.60 6.1520 6.151837 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:40:00 unknown unknown unknown 7/21 17:40:00 Sensible 92061.17 83600.84 1.0000 8.35831450 6.949400 22.49 16.22 0.00894306 45336.5 12.80 12.09 0.00850000 34322.2 3.28781481 6.70 13.37 6.67 0.000 92061.17 31.82 0.01716457 24.97 0.00000000 0.0000 21.11 0.00894306 21.11 0.00894306 57.2720 70888.06 0.00 92220.62 82796.81 8.35831450 22.49 16.23 0.00894306 45336.5 12.79 12.09 0.00849648 34303.1
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_4_MULT19_FLR_3 FAN COIL ROOM_4_MULT19_FLR_3 N/A N/A N/A Yes Yes Yes No 21316.133 21316.133 0.920129 0.00018648 609.050 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 6.949400 8.35831450   4197.9300 999.8980 2.43912859 54.44 82.22 27.78 284447.51 7.4939 7.644690 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 23:40:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 23:40:00 Sensible 21316.13 21316.13 1.0000 1.10667467 0.920129 21.11 14.70 0.00780322 41034.7 40.00 21.17 0.00800000 60796.0 0.18646381 60.00 32.22 27.78 0.000 21316.13 8.70 0.00699286 8.70 0.00000000 0.0000 21.11 0.00780322 21.11 0.00780322 50.0589 21316.21 0.00 22979.53 22979.53 1.10667467 16.60 12.96 0.00780322 36436.5 36.97 20.12 0.00780322 57201.0
ROOM_5_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_5_FLR_3 FAN COIL ROOM_5_FLR_3 N/A N/A N/A Yes Yes Yes No 12405.479 -999.000 0.942610 0.00044309 -999.000 -999.0000 1.00000 1.00000 1021.4125 1004.8586 1.2027 ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.942610 1.13371341   4197.9300 999.8980 53.44443855 13.37 6.70 6.67 1496454.60 0.8290 0.828976 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:00:00 unknown unknown unknown 7/21 10:00:00 Sensible 12405.48 11331.41 1.0000 1.13371341 0.942610 22.49 16.20 0.00891497 45264.5 12.80 12.09 0.00850000 34322.2 0.44304149 6.70 13.37 6.67 0.000 12405.48 30.65 0.01716236 24.67 0.00000000 0.0000 21.11 0.00891497 21.11 0.00891497 57.0968 9614.47 0.00 12427.06 11218.75 1.13371341 22.49 16.21 0.00891497 45264.5 12.80 12.09 0.00849282 34303.2
ROOM_5_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_5_FLR_3 FAN COIL ROOM_5_FLR_3 N/A N/A N/A Yes Yes Yes No 3658.994 3658.994 0.157943 0.00003201 104.547 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.942610 1.13371341   4197.9300 999.8980 2.43912859 54.44 82.22 27.78 284447.51 1.2864 1.312240 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 23:40:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 23:40:00 Sensible 3658.99 3658.99 1.0000 0.18996380 0.157943 21.11 14.69 0.00778790 40995.7 40.00 21.17 0.00800000 60796.0 0.03200721 60.00 32.22 27.78 0.000 3658.99 8.70 0.00699286 8.70 0.00000000 0.0000 21.11 0.00778790 21.11 0.00778790 49.9622 3659.02 0.00 3944.52 3944.52 0.18996380 16.60 12.94 0.00778790 36397.7 36.97 20.11 0.00778790 57162.3
ROOM_6_FLR_3 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_6_FLR_3 FAN COIL ROOM_6_FLR_3 N/A N/A N/A Yes Yes Yes No 12501.428 -999.000 0.950587 0.00044651 -999.000 -999.0000 1.00000 1.00000 1021.4067 1004.8586 1.2027 ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.950587 1.14330795   4197.9300 999.8980 53.44443855 13.37 6.70 6.67 1496454.60 0.8354 0.835387 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:00:00 unknown unknown unknown 7/21 10:00:00 Sensible 12501.43 11426.47 1.0000 1.14330795 0.950587 22.49 16.19 0.00891185 45256.6 12.80 12.09 0.00850000 34322.2 0.44646814 6.70 13.37 6.67 0.000 12501.43 30.65 0.01716236 24.67 0.00000000 0.0000 21.11 0.00891185 21.11 0.00891185 57.0771 9695.84 0.00 12523.19 11312.46 1.14330795 22.49 16.21 0.00891185 45256.6 12.80 12.09 0.00849241 34303.2
ROOM_6_FLR_3 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_6_FLR_3 FAN COIL ROOM_6_FLR_3 N/A N/A N/A Yes Yes Yes No 3659.223 3659.223 0.157953 0.00003201 104.553 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.950587 1.14330795   4197.9300 999.8980 2.43912859 54.44 82.22 27.78 284447.51 1.2864 1.312322 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 23:40:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 23:40:00 Sensible 3659.22 3659.22 1.0000 0.18997566 0.157953 21.11 14.69 0.00778793 40995.7 40.00 21.17 0.00800000 60796.0 0.03200921 60.00 32.22 27.78 0.000 3659.22 8.70 0.00699286 8.70 0.00000000 0.0000 21.11 0.00778793 21.11 0.00778793 49.9623 3659.25 0.00 3944.76 3944.76 0.18997566 16.60 12.94 0.00778793 36397.8 36.97 20.11 0.00778793 57162.4
CORRIDOR_FLR_3 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORRIDOR_FLR_3 VAV BOX CORRIDOR_FLR_3 N/A N/A N/A Yes Yes Yes No 11535.774 11535.774 1.095430 0.00010092 253.723 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.43912859 54.44 82.22 27.78 284447.51 4.0555 4.137121 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 11535.77 11535.77 1.0000 1.31751622 1.095430 16.70 13.18 0.00800000 37036.7 40.00 21.17 0.00800000 60796.0 0.10090969 60.00 32.22 27.78 0.000 11535.77 8.70 0.00699286 8.70 0.00000000 0.0000 21.00 0.00782775 21.00 0.00782775 50.5578 5760.67 0.00 11598.70 11598.70 1.31751622 16.60 13.15 0.00800000 36934.7 25.23 16.40 0.00800000 45738.2
ROOM_1_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_6 FAN COIL ROOM_1_FLR_6 N/A N/A N/A Yes Yes Yes No 3632.372 -999.000 0.280254 0.00012974 -999.000 -999.0000 1.00000 1.00000 1021.2909 1004.8586 1.2027 ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.280254 0.33707271   4197.9300 999.8980 53.44443855 13.37 6.70 6.67 1496454.60 0.2427 0.242727 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00 unknown unknown unknown 7/21 17:00:00 Sensible 3632.37 3363.80 1.0000 0.33707271 0.280254 22.49 16.14 0.00884955 45098.4 12.80 12.09 0.00850000 34322.2 0.12972425 6.70 13.37 6.67 0.000 3632.37 32.26 0.01716543 25.09 0.00000000 0.0000 21.11 0.00884955 21.11 0.00884955 56.6835 2858.57 0.00 3638.76 3327.75 0.33707271 22.49 16.15 0.00884955 45098.4 12.82 12.09 0.00848411 34303.2
ROOM_1_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_1_FLR_6 FAN COIL ROOM_1_FLR_6 N/A N/A N/A Yes Yes Yes No 1124.655 1124.655 0.048546 0.00000984 32.134 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.280254 0.33707271   4197.9300 999.8980 2.43912859 54.44 82.22 27.78 284447.51 0.3954 0.403339 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 23:40:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 23:40:00 Sensible 1124.65 1124.65 1.0000 0.05838863 0.048546 21.11 14.72 0.00782040 41078.2 40.00 21.17 0.00800000 60796.0 0.00983797 60.00 32.22 27.78 0.000 1124.65 8.70 0.00699286 8.70 0.00000000 0.0000 21.11 0.00782040 21.11 0.00782040 50.1681 1124.66 0.00 1212.41 1212.41 0.05838863 16.60 12.98 0.00782040 36480.0 36.97 20.13 0.00782040 57244.6
ROOM_2_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_6 FAN COIL ROOM_2_FLR_6 N/A N/A N/A Yes Yes Yes No 3661.774 -999.000 0.282749 0.00013079 -999.000 -999.0000 1.00000 1.00000 1021.2846 1004.8586 1.2027 ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.282749 0.34007358   4197.9300 999.8980 53.44443855 13.37 6.70 6.67 1496454.60 0.2447 0.244692 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00 unknown unknown unknown 7/21 17:00:00 Sensible 3661.77 3393.46 1.0000 0.34007358 0.282749 22.49 16.14 0.00884615 45089.8 12.80 12.09 0.00850000 34322.2 0.13077431 6.70 13.37 6.67 0.000 3661.77 32.26 0.01716543 25.09 0.00000000 0.0000 21.11 0.00884615 21.11 0.00884615 56.6621 2884.01 0.00 3668.22 3356.97 0.34007358 22.49 16.15 0.00884615 45089.8 12.82 12.09 0.00848365 34303.2
ROOM_2_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_2_FLR_6 FAN COIL ROOM_2_FLR_6 N/A N/A N/A Yes Yes Yes No 1124.882 1124.882 0.048556 0.00000984 32.140 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 0.282749 0.34007358   4197.9300 999.8980 2.43912859 54.44 82.22 27.78 284447.51 0.3955 0.403421 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 23:40:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 23:40:00 Sensible 1124.88 1124.88 1.0000 0.05840041 0.048556 21.11 14.72 0.00782044 41078.3 40.00 21.17 0.00800000 60796.0 0.00983995 60.00 32.22 27.78 0.000 1124.88 8.70 0.00699286 8.70 0.00000000 0.0000 21.11 0.00782044 21.11 0.00782044 50.1683 1124.89 0.00 1212.66 1212.66 0.05840041 16.60 12.98 0.00782044 36480.1 36.97 20.13 0.00782044 57244.7
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL COIL:COOLING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT9_FLR_6 FAN COIL ROOM_3_MULT9_FLR_6 N/A N/A N/A Yes Yes Yes No 15472.292 -999.000 1.165445 0.00055262 -999.000 -999.0000 1.00000 1.00000 1021.4824 1004.8586 1.2027 ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 1.165445 1.40172622   4197.9300 999.8980 53.44443855 13.37 6.70 6.67 1496454.60 1.0339 1.033911 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:40:00 unknown unknown unknown 7/21 14:40:00 Sensible 15472.29 14022.61 1.0000 1.40172622 1.165445 22.49 16.23 0.00895259 45360.2 12.80 12.09 0.00850000 34322.2 0.55256771 6.70 13.37 6.67 0.000 15472.29 33.20 0.01716721 25.32 0.00000000 0.0000 21.11 0.00895259 21.11 0.00895259 57.3340 11887.52 0.00 15499.05 13889.27 1.40172622 22.49 16.24 0.00895259 45360.2 12.79 12.09 0.00849772 34303.1
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:FOURPIPEFANCOIL ROOM_3_MULT9_FLR_6 FAN COIL ROOM_3_MULT9_FLR_6 N/A N/A N/A Yes Yes Yes No 5435.884 5435.884 0.234644 0.00004756 155.313 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN Fan:OnOff 1.165445 1.40172622   4197.9300 999.8980 2.43912859 54.44 82.22 27.78 284447.51 1.9110 1.949493 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 23:40:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 23:40:00 Sensible 5435.88 5435.88 1.0000 0.28221499 0.234644 21.11 14.72 0.00782744 41096.2 40.00 21.17 0.00800000 60796.0 0.04755063 60.00 32.22 27.78 0.000 5435.88 8.70 0.00699286 8.70 0.00000000 0.0000 21.11 0.00782744 21.11 0.00782744 50.2126 5435.92 0.00 5860.06 5860.06 0.28221499 16.60 12.98 0.00782744 36497.9 36.97 20.14 0.00782744 57262.4
BANQUET_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown BANQUET_FLR_6 N/A N/A N/A Yes Yes Yes No 15438.992 15438.992 2.225678 0.00013507 327.312 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.43912859 54.44 82.22 27.78 284447.51 5.4277 5.536947 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 23:40:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 23:40:00 Sensible 15438.99 15438.99 1.0000 2.67690912 2.225678 16.70 13.18 0.00800000 37036.7 40.00 21.17 0.00800000 60796.0 0.13505326 60.00 32.22 27.78 0.000 15438.99 8.70 0.00699286 8.70 0.00000000 0.0000 21.00 0.00785972 21.00 0.00785972 50.7617 3704.58 0.00 15525.26 15525.26 2.67690912 16.60 13.15 0.00800000 36934.7 22.29 15.33 0.00800000 42734.4
DINING_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown DINING_FLR_6 N/A N/A N/A Yes Yes Yes No 15947.956 15947.956 2.335481 0.00013952 337.735 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.43912859 54.44 82.22 27.78 284447.51 5.6066 5.719479 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 04:20:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 04:20:00 Sensible 15947.96 15947.96 1.0000 2.80897417 2.335481 16.70 13.18 0.00800000 37036.7 40.00 21.17 0.00800000 60796.0 0.13950544 60.00 32.22 27.78 0.000 15947.96 8.70 0.00699286 8.70 0.00000000 0.0000 21.00 0.00785734 21.00 0.00785734 50.7466 3634.68 0.00 16037.10 16037.10 2.80897417 16.60 13.15 0.00800000 36934.7 22.20 15.30 0.00800000 42644.0
KITCHEN_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Unknown Unknown Unknown KITCHEN_FLR_6 N/A N/A N/A Yes Yes Yes No 11816.389 11816.389 2.240617 0.00010337 246.410 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.43912859 54.44 82.22 27.78 284447.51 4.1542 4.237759   1/21 00:10:00 unknown unknown   1/21 00:10:00 Sensible 11816.39 11816.39 1.0000 2.69487718 2.240617 16.70 13.18 0.00800000 37036.7 40.00 21.17 0.00800000 60796.0 0.10336438 60.00 32.22 27.78 0.000 11816.39 8.70 0.00699286 8.70 0.00000000 0.0000 21.00 0.00800000 21.00 0.00800000 51.6560 0.00 0.00 11882.80 11882.80 2.69487718 16.60 13.15 0.00800000 36934.7 20.92 14.82 0.00800000 41344.1
CORRIDOR_FLR_6 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORRIDOR_FLR_6 VAV BOX CORRIDOR_FLR_6 N/A N/A N/A Yes Yes Yes No 7322.429 7322.429 0.659978 0.00006406 162.012 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 unknown unknown -999.0 -999.0   4197.9300 999.8980 2.43912859 54.44 82.22 27.78 284447.51 2.5743 2.626072 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 04:30:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 04:30:00 Sensible 7322.43 7322.43 1.0000 0.79378166 0.659978 16.70 13.18 0.00800000 37036.7 40.00 21.17 0.00800000 60796.0 0.06405327 60.00 32.22 27.78 0.000 7322.43 8.70 0.00699286 8.70 0.00000000 0.0000 21.00 0.00787883 21.00 0.00787883 50.8838 3842.74 0.00 7362.27 7362.27 0.79378166 16.60 13.15 0.00800000 36934.7 25.70 16.56 0.00800000 46209.7
VAV WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC VAV WITH REHEAT BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; Coincident CoolingDesignCapacity N/A Yes Yes Yes No 1144947.372 -999.000 21.217549 0.04089487 -999.000 -999.0000 1.00000 1.00000 1036.7530 1004.8586 1.2027 VAV WITH REHEAT FAN Fan:VariableVolume 21.217549 25.51917288   4197.9300 999.8980 53.44443855 13.37 6.70 6.67 1496454.60 76.5107 76.510665 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:50:00 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:50:00 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:50:00 Sensible 1144947.37 570594.23 1.0000 25.51917288 21.217549 33.20 25.32 0.01716721 77354.4 11.00 11.00 0.00850000 32488.2 40.89069558 6.70 13.37 6.67 47540.861 1097406.51 33.20 0.01716721 25.32 21.21247000 99.9761 23.99 0.00979524 23.99 0.00983433 52.7915 291395.06 0.00 1146407.07 577418.59 25.51917288 33.20 25.34 0.01716721 77354.4 11.38 11.33 0.00832671 32431.0
VAV WITH REHEAT HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC VAV WITH REHEAT BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 61543.584 61543.584 6.365265 0.00053841 1142.024 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 VAV WITH REHEAT FAN Fan:VariableVolume 21.217549 25.51917288   4197.9300 999.8980 2.43912859 54.44 82.22 27.78 284447.51 21.6362 22.071620 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 04:30:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 04:30:00 Sensible 61543.58 61543.58 1.0000 7.65575186 6.365265 8.70 8.70 0.00699286 26343.9 16.70 13.18 0.00800000 37036.7 0.53835520 60.00 32.22 27.78 0.000 61543.58 8.70 0.00699286 8.70 21.21247000 333.2535 17.40 0.00763756 22.68 0.00711736 41.5360 34496.53 0.00 66715.09 66715.09 7.65575186 2.80 2.80 0.00699286 20338.7 11.36 9.92 0.00699286 29053.0
FLR_3_DOAS COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC FLR_3_DOAS ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; Coincident CoolingDesignCapacity N/A Yes Yes Yes No 108329.821 -999.000 2.051317 0.00386929 -999.000 -999.0000 1.00000 1.00000 1036.7530 1004.8586 1.2027 FLR_3_DOAS FAN Fan:ConstantVolume 2.051245 2.46711237   4197.9300 999.8980 53.44443855 13.37 6.70 6.67 1496454.60 7.2391 7.239098 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 15:30:00 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 16:40:00 Sensible 108329.82 53987.08 1.0000 2.46719911 2.051317 33.20 25.32 0.01716721 77354.4 11.94 11.73 0.00850000 33446.3 3.86889549 6.70 13.37 6.67 2195.006 106134.81 33.20 0.01716721 25.32 2.05124512 99.9965 21.11 0.00889146 21.11 0.00887395 56.8347 184267.17 0.00 108457.34 54776.98 2.46719911 33.20 25.34 0.01716721 77354.4 11.78 11.72 0.00854298 33394.7
FLR_3_DOAS HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC FLR_3_DOAS ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 5950.047 5950.047 0.615395 0.00005205 110.411 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.2027 FLR_3_DOAS FAN Fan:ConstantVolume 2.051245 2.46711237   4197.9300 999.8980 2.43912859 54.44 82.22 27.78 284447.51 2.0918 2.133889 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 23:40:00 unknown unknown MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 23:40:00 Sensible 5950.05 5950.05 1.0000 0.74015973 0.615395 8.70 8.70 0.00699286 26343.9 16.70 13.18 0.00800000 37036.7 0.05204830 60.00 32.22 27.78 0.000 5950.05 8.70 0.00699286 8.70 2.05124512 333.3216 21.11 0.00780237 21.11 0.00780327 50.0592 64938.74 0.00 6450.03 6450.03 0.74015973 2.80 2.80 0.00699286 20338.7 11.36 9.92 0.00699286 29053.0



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2023-10-16 08:58:20

Economizer

High Limit Shutoff Control Minimum Outdoor Air [m3/s] Maximum Outdoor Air [m3/s] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [C] Outdoor Air Enthalpy Limit [C]
FLR_3_DOAS_OA_CONTROLLER DifferentialDryBulb 2.05 2.05 -      


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [m3/s-person] Outdoor Air Per Area [m3/s-m2] Outdoor Air Per Zone [m3/s] Outdoor Air ACH [ach] Outdoor Air Method Outdoor Air Schedule Name Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule Name
BASEMENT VAV WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
RETAIL_1_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.001181 0.000000 0.000000 Flow/Area   1.00 1.00  
RETAIL_2_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.001181 0.000000 0.000000 Flow/Area   1.00 1.00  
MECH_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.000000 0.000000 0.000000 Flow/Area   1.00 1.00  
STORAGE_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.000610 0.000000 0.000000 Flow/Area   1.00 1.00  
LAUNDRY_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.000000 0.000000 0.000000 Flow/Area   1.00 1.00  
CAFE_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.003581 0.000000 0.000000 Flow/Area   1.00 1.00  
LOBBY_FLR_1 VAV WITH REHEAT_DCV 0.000000 0.001448 0.000000 0.000000 Flow/Area   1.00 1.00  
CORRIDOR_FLR_3 VAV WITH REHEAT_DCV 0.000000 0.000305 0.000000 0.000000 Flow/Area   1.00 1.00  
BANQUET_FLR_6 VAV WITH REHEAT_DCV 0.000000 0.003581 0.000000 0.000000 Flow/Area   1.00 1.00  
DINING_FLR_6 VAV WITH REHEAT_DCV 0.000000 0.003581 0.000000 0.000000 Flow/Area   1.00 1.00  
KITCHEN_FLR_6 VAV WITH REHEAT_DCV 0.000000 0.003556 0.000000 0.000000 Flow/Area   1.00 1.00  
CORRIDOR_FLR_6 VAV WITH REHEAT_DCV 0.000000 0.000305 0.000000 0.000000 Flow/Area   1.00 1.00  


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
BASEMENT 0.00 8760.00 0.00
RETAIL_1_FLR_1 210.83 8329.17 5.17
RETAIL_2_FLR_1 0.00 8760.00 0.00
MECH_FLR_1 0.00 8760.00 0.00
STORAGE_FLR_1 1.50 8760.00 1.50
LAUNDRY_FLR_1 5861.83 1903.50 1257.00
CAFE_FLR_1 202.33 8011.50 0.00
LOBBY_FLR_1 0.00 8760.00 0.00
ROOM_1_FLR_3 269.17 7379.83 24.67
ROOM_2_FLR_3 205.00 7604.33 45.00
ROOM_3_MULT19_FLR_3 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 14.50 8760.00 14.50
ROOM_5_FLR_3 64.33 7174.00 21.33
ROOM_6_FLR_3 54.67 7417.83 40.17
CORRIDOR_FLR_3 0.00 8760.00 0.00
ROOM_1_FLR_6 782.00 7149.50 61.67
ROOM_2_FLR_6 636.17 7337.17 85.00
ROOM_3_MULT9_FLR_6 261.67 7217.33 36.83
BANQUET_FLR_6 580.33 7084.83 0.00
DINING_FLR_6 1060.17 6311.83 0.00
KITCHEN_FLR_6 7587.00 6379.33 6036.33
CORRIDOR_FLR_6 2.83 8760.00 2.83
Facility 7707.83 8760.00 6066.83
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
BASEMENT 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 0.00 0.00 0.00 0.00
MECH_FLR_1 0.00 0.00 0.00 0.00
STORAGE_FLR_1 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 0.00 0.00 0.00 0.00
CAFE_FLR_1 0.00 0.00 0.00 0.00
LOBBY_FLR_1 0.00 0.00 0.00 0.00
ROOM_1_FLR_3 0.00 0.50 0.00 0.50
ROOM_2_FLR_3 0.00 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 0.00 21.33 0.00 21.33
ROOM_5_FLR_3 0.00 0.00 0.00 0.00
ROOM_6_FLR_3 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 0.00 2.00 0.00 2.00
ROOM_2_FLR_6 0.00 0.50 0.00 0.50
ROOM_3_MULT9_FLR_6 0.00 30.00 0.00 30.00
BANQUET_FLR_6 0.00 0.00 0.00 0.00
DINING_FLR_6 0.00 0.00 0.00 0.00
KITCHEN_FLR_6 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6 0.00 0.00 0.00 0.00
Facility 0.00 45.33 0.00 45.33
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2023-10-16 08:58:20

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
BASEMENT 61.80 106.50 4826.41 2.000 0.000 0.000 0.000
RETAIL_1_FLR_1 6.28 10.83 265.76 4.011 0.235 0.000 0.000
RETAIL_2_FLR_1 7.28 12.54 307.76 2.856 0.078 0.000 0.000
MECH_FLR_1 1.54 2.65 650.80 1.457 0.087 0.000 0.000
STORAGE_FLR_1 1.18 2.04 375.47 1.261 0.087 0.000 0.000
LAUNDRY_FLR_1 4.87 8.40 309.22 38.328 0.251 0.000 0.000
CAFE_FLR_1 82.58 142.30 748.35 6.362 0.184 0.000 0.000
LOBBY_FLR_1 245.14 422.44 5183.56 3.195 0.076 0.000 0.000
ROOM_1_FLR_3 0.95 1.50 118.94 0.474 0.304 0.000 0.065
ROOM_2_FLR_3 0.95 1.50 118.93 0.474 0.304 0.000 0.066
ROOM_3_MULT19_FLR_3   1.50 74.75        
ROOM_4_MULT19_FLR_3 0.95 1.50 74.77 0.538 0.135 0.000 0.105
ROOM_5_FLR_3 0.95 1.50 118.94 0.474 0.304 0.000 0.065
ROOM_6_FLR_3 0.95 1.50 118.93 0.474 0.304 0.000 0.066
CORRIDOR_FLR_3 12.16 20.96 1186.91 0.844 0.037 0.000 0.000
ROOM_1_FLR_6 0.95 1.50 118.94 0.474 0.305 0.000 0.078
ROOM_2_FLR_6 0.95 1.50 118.93 0.474 0.305 0.000 0.080
ROOM_3_MULT9_FLR_6 0.95 1.50 74.77 0.538 0.248 0.000 0.125
BANQUET_FLR_6 145.01 249.90 1010.89 8.051 0.088 0.000 0.000
DINING_FLR_6 145.01 249.90 1010.89 8.450 0.088 0.000 0.000
KITCHEN_FLR_6 12.90 22.24 314.87 26.187 0.253 0.000 0.000
CORRIDOR_FLR_6 12.87 22.18 1256.16 1.917 0.062 0.000 0.000
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
BASEMENT 61.80 106.50 4826.41 1.955 0.000 0.000 0.000
RETAIL_1_FLR_1 6.28 10.83 265.76 3.914 0.005 0.000 0.000
RETAIL_2_FLR_1 7.28 12.54 307.76 2.789 0.002 0.000 0.000
MECH_FLR_1 1.54 2.65 650.80 1.423 0.002 0.000 0.000
STORAGE_FLR_1 1.18 2.04 375.47 1.232 0.002 0.000 0.000
LAUNDRY_FLR_1 4.87 8.40 309.22 37.426 0.005 0.000 0.000
CAFE_FLR_1 82.58 142.30 748.35 6.201 0.004 0.000 0.000
LOBBY_FLR_1 245.14 422.44 5183.56 3.116 0.002 0.000 0.000
ROOM_1_FLR_3 0.95 1.50 118.94 0.462 0.006 0.000 0.000
ROOM_2_FLR_3 0.95 1.50 118.93 0.461 0.006 0.000 0.000
ROOM_3_MULT19_FLR_3   1.50 74.75        
ROOM_4_MULT19_FLR_3 0.95 1.50 74.77 0.525 0.003 0.000 0.000
ROOM_5_FLR_3 0.95 1.50 118.94 0.463 0.006 0.000 0.000
ROOM_6_FLR_3 0.95 1.50 118.93 0.462 0.006 0.000 0.000
CORRIDOR_FLR_3 12.16 20.96 1186.91 0.822 0.001 0.000 0.000
ROOM_1_FLR_6 0.95 1.50 118.94 0.461 0.006 0.000 0.000
ROOM_2_FLR_6 0.95 1.50 118.93 0.461 0.006 0.000 0.000
ROOM_3_MULT9_FLR_6 0.95 1.50 74.77 0.525 0.005 0.000 0.000
BANQUET_FLR_6 145.01 249.90 1010.89 7.842 0.002 0.000 0.000
DINING_FLR_6 145.01 249.90 1010.89 8.230 0.002 0.000 0.000
KITCHEN_FLR_6 12.90 22.24 314.87 25.455 0.005 0.000 0.000
CORRIDOR_FLR_6 12.87 22.18 1256.16 1.871 0.001 0.000 0.000
Values shown for a single zone without multipliers


Table of Contents

Report: Outdoor Air Details

For: Entire Facility

Timestamp: 2023-10-16 08:58:20

Mechanical Ventilation Parameters by Zone

AirLoop Name Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Zone Area [m2] Design Zone Outdoor Airflow - Voz [m3/s] Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s]
BASEMENT VAV WITH REHEAT 61.80 106.50 4826.41 1978.83 0.0000 0.854
RETAIL_1_FLR_1 VAV WITH REHEAT 6.28 10.83 265.76 67.07 0.0000 0.079
RETAIL_2_FLR_1 VAV WITH REHEAT 7.28 12.54 307.76 77.67 0.0000 0.092
MECH_FLR_1 VAV WITH REHEAT 1.54 2.65 650.80 164.24 0.0000 0.000
STORAGE_FLR_1 VAV WITH REHEAT 1.18 2.04 375.47 94.76 0.0000 0.058
LAUNDRY_FLR_1 VAV WITH REHEAT 4.87 8.40 309.22 78.04 0.0000 0.000
CAFE_FLR_1 VAV WITH REHEAT 82.58 142.30 748.35 188.86 0.0000 0.676
LOBBY_FLR_1 VAV WITH REHEAT 245.14 422.44 5183.56 1308.19 0.0000 1.894
ROOM_1_FLR_3 FLR_3_DOAS 0.95 1.50 118.94 39.02 0.0000 0.062
ROOM_2_FLR_3 FLR_3_DOAS 0.95 1.50 118.93 39.02 0.0000 0.062
ROOM_3_MULT19_FLR_3 FLR_3_DOAS   1.50 74.75 24.52 0.0000 0.837
ROOM_4_MULT19_FLR_3 FLR_3_DOAS 0.95 1.50 74.77 24.53 0.0000 0.837
ROOM_5_FLR_3 FLR_3_DOAS 0.95 1.50 118.94 39.02 0.0000 0.062
ROOM_6_FLR_3 FLR_3_DOAS 0.95 1.50 118.93 39.02 0.0000 0.062
CORRIDOR_FLR_3 VAV WITH REHEAT 12.16 20.96 1186.91 389.40 0.0000 0.475
ROOM_1_FLR_6 FLR_3_DOAS 0.95 1.50 118.94 39.02 0.0000 0.015
ROOM_2_FLR_6 FLR_3_DOAS 0.95 1.50 118.93 39.02 0.0000 0.015
ROOM_3_MULT9_FLR_6 FLR_3_DOAS 0.95 1.50 74.77 24.53 0.0000 0.099
BANQUET_FLR_6 VAV WITH REHEAT 145.01 249.90 1010.89 331.66 0.0000 1.188
DINING_FLR_6 VAV WITH REHEAT 145.01 249.90 1010.89 331.66 0.0000 1.188
KITCHEN_FLR_6 VAV WITH REHEAT 12.90 22.24 314.87 103.30 0.0000 0.367
CORRIDOR_FLR_6 VAV WITH REHEAT 12.87 22.18 1256.16 412.12 0.0000 0.126
Total Facility   873.39 1604.23 35184.81 11345.29 0.0000 137.584


Total Outdoor Air by Zone

Mechanical Ventilation [m3] Natural Ventilation [m3] Total Ventilation [m3] Infiltration [m3] Total Ventilation and Infiltration [m3] Dynamic Target Ventilation - Voz-dyn [m3] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr] Time Above Zero When Unoccupied [hr]
BASEMENT 83480417.75 0.00 83480417.75 0.00 83480417.75 26946214.98 0.00 0.00 8760.00 0.00
RETAIL_1_FLR_1 9209833.68 0.00 9209833.68 538771.47 9748605.14 2498216.28 0.00 0.00 8760.00 0.00
RETAIL_2_FLR_1 7597786.71 0.00 7597786.71 207966.47 7805753.18 2892943.94 0.00 0.00 8760.00 0.00
MECH_FLR_1 8200445.09 0.00 8200445.09 491509.18 8691954.27 0.00 0.00 0.00 8760.00 0.00
STORAGE_FLR_1 4094000.82 0.00 4094000.82 283573.72 4377574.54 1821682.01 0.00 0.00 8760.00 0.00
LAUNDRY_FLR_1 0.10E+09 0.00 0.10E+09 671130.68 0.10E+09 0.00 0.00 0.00 8760.00 0.00
CAFE_FLR_1 41072880.89 0.00 41072880.89 1190984.83 42263865.72 21330615.53 0.00 0.00 8760.00 0.00
LOBBY_FLR_1 0.14E+09 0.00 0.14E+09 3402915.69 0.15E+09 59728886.00 0.00 0.00 8760.00 0.00
ROOM_1_FLR_3 1946875.62 66602.95 2013478.56 312717.28 2326195.85 1946875.62 0.00 7650.83 1109.17 0.00
ROOM_2_FLR_3 1946647.51 67779.04 2014426.55 312693.42 2327119.97 1946647.51 0.00 7650.83 1109.17 0.00
ROOM_3_MULT19_FLR_3 26397887.27 68920.90 26466808.17 87251.63 26554059.80 26397887.27 0.00 7743.33 1016.67 8760.00
ROOM_4_MULT19_FLR_3 26405105.73 67797.07 26472902.80 87275.49 26560178.29 26405105.73 0.00 7729.64 1030.36 0.00
ROOM_5_FLR_3 1946875.62 66705.09 2013580.71 312717.28 2326297.99 1946875.62 0.00 7650.83 1109.17 0.00
ROOM_6_FLR_3 1946647.51 67871.31 2014518.82 312693.42 2327212.24 1946647.51 0.00 7650.83 1109.17 0.00
CORRIDOR_FLR_3 34530404.86 0.00 34530404.86 378138.11 34908542.97 14972100.18 0.00 0.00 8760.00 0.00
ROOM_1_FLR_6 486718.90 80772.42 567491.32 312779.78 880271.10 486718.90 0.00 7637.17 1122.83 0.00
ROOM_2_FLR_6 486661.88 82366.77 569028.65 312755.92 881784.57 486661.88 0.00 7637.17 1122.83 0.00
ROOM_3_MULT9_FLR_6 3126920.42 80935.06 3207855.48 160029.08 3367884.56 3126920.42 0.00 7637.53 1122.47 0.00
BANQUET_FLR_6 70158343.84 0.00 70158343.84 763729.62 70922073.46 37458366.31 0.00 0.00 8760.00 0.00
DINING_FLR_6 73619598.85 0.00 73619598.85 763729.62 74383328.47 37458366.31 0.00 0.00 8760.00 0.00
KITCHEN_FLR_6 70751859.78 0.00 70751859.78 683715.08 71435574.86 11584760.86 0.00 0.00 8760.00 0.00
CORRIDOR_FLR_6 20803996.07 0.00 20803996.07 669182.16 21473178.24 3961413.96 0.00 0.00 8760.00 0.00
Total Facility 0.48E+10 12357954.02 0.49E+10 31512904.89 0.49E+10 0.43E+10 0.00 7801.26 8760.00 8760.00


Average Outdoor Air During Occupancy by Zone - Flow Rates

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Infiltration [m3/s] Total Ventilation and Infiltration [m3/s] Dynamic Target Ventilation - Voz-dyn [m3/s] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr]
BASEMENT 2.6471 0.0000 2.6471 0.0000 2.6471 0.8545 0.00 0.00 8760.00
RETAIL_1_FLR_1 0.2920 0.0000 0.2920 0.0171 0.3091 0.0792 0.00 0.00 8760.00
RETAIL_2_FLR_1 0.2409 0.0000 0.2409 0.0066 0.2475 0.0917 0.00 0.00 8760.00
MECH_FLR_1 0.2600 0.0000 0.2600 0.0156 0.2756 0.0000 0.00 0.00 8760.00
STORAGE_FLR_1 0.1298 0.0000 0.1298 0.0090 0.1388 0.0578 0.00 0.00 8760.00
LAUNDRY_FLR_1 3.2492 0.0000 3.2492 0.0213 3.2705 0.0000 0.00 0.00 8760.00
CAFE_FLR_1 1.3024 0.0000 1.3024 0.0378 1.3402 0.6764 0.00 0.00 8760.00
LOBBY_FLR_1 4.5335 0.0000 4.5335 0.1079 4.6415 1.8940 0.00 0.00 8760.00
ROOM_1_FLR_3 0.0617 0.0021 0.0638 0.0099 0.0738 0.0617 0.00 7650.83 1109.17
ROOM_2_FLR_3 0.0617 0.0021 0.0639 0.0099 0.0738 0.0617 0.00 7650.83 1109.17
ROOM_4_MULT19_FLR_3 0.8373 0.0021 0.8395 0.0028 0.8422 0.8373 0.00 7729.64 1030.36
ROOM_5_FLR_3 0.0617 0.0021 0.0639 0.0099 0.0738 0.0617 0.00 7650.83 1109.17
ROOM_6_FLR_3 0.0617 0.0022 0.0639 0.0099 0.0738 0.0617 0.00 7650.83 1109.17
CORRIDOR_FLR_3 1.0950 0.0000 1.0950 0.0120 1.1069 0.4748 0.00 0.00 8760.00
ROOM_1_FLR_6 0.0154 0.0026 0.0180 0.0099 0.0279 0.0154 0.00 7637.17 1122.83
ROOM_2_FLR_6 0.0154 0.0026 0.0180 0.0099 0.0280 0.0154 0.00 7637.17 1122.83
ROOM_3_MULT9_FLR_6 0.0992 0.0026 0.1017 0.0051 0.1068 0.0992 0.00 7637.53 1122.47
BANQUET_FLR_6 2.2247 0.0000 2.2247 0.0242 2.2489 1.1878 0.00 0.00 8760.00
DINING_FLR_6 2.3345 0.0000 2.3345 0.0242 2.3587 1.1878 0.00 0.00 8760.00
KITCHEN_FLR_6 2.2435 0.0000 2.2435 0.0217 2.2652 0.3674 0.00 0.00 8760.00
CORRIDOR_FLR_6 0.6597 0.0000 0.6597 0.0212 0.6809 0.1256 0.00 0.00 8760.00
Total Facility 90.0431 0.2258 90.2689 0.7890 91.0579 73.9670 0.00 7801.26 8760.00


Total Outdoor Air by AirLoop

Mechanical Ventilation [m3] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr] Time Above Zero When Unoccupied [hr]
VAV WITH REHEAT 0.97E+09 0.00 0.97E+09 0.22E+09 0.00 0.00 8760.00 0.00
FLR_3_DOAS 93579813.88 649750.60 94229564.48 64690340.46 0.00 0.00 8760.00 0.00


Average Outdoor Air During Occupancy by AirLoop

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr]
VAV WITH REHEAT 30.6856 0.0000 30.6856 6.9969 0.00 0.00 8760.00
FLR_3_DOAS 2.9674 0.0206 2.9880 2.0513 0.00 0.00 8760.00


Outdoor Air Controller Limiting Factors by AirLoop

No Limiting Factor [hr] Limits and Scheduled Limits [hr] Economizer [hr] Exhaust Flow [hr] Mixed Air Flow [hr] High Humidity [hr] Demand Controlled Ventilation [hr] Night Ventilation [hr] Demand Limiting [hr] Energy Management System [hr]
VAV WITH REHEAT 0.00 8760.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
FLR_3_DOAS 0.00 7869.88 890.12 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Average Outdoor Air for Limiting Factors During Occupancy

No Limiting Factor [m3/s] Limits and Scheduled Limits [m3/s] Economizer [m3/s] Exhaust Flow [m3/s] Mixed Air Flow [m3/s] High Humidity [m3/s] Demand Controlled Ventilation [m3/s] Night Ventilation [m3/s] Demand Limiting [m3/s] Energy Management System [m3/s]
VAV WITH REHEAT 0.0000 30.6856 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
FLR_3_DOAS 0.0000 2.9677 2.9678 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000



Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2023-10-16 08:58:20

Surfaces by Class

Total Outdoors
Wall 119 44
Floor 25 0
Roof 33 11
Internal Mass 22 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 30 30
Door 6 6
Glass Door 0 0
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 2
Conditioned Zones 22
Unconditioned Zones 0
Supply Plenums 0
Return Plenums 0


Input Fields

Count
IDF Objects 1306
Defaulted Fields 1181
Fields with Defaults 3945
Autosized Fields 350
Autosizable Fields 402
Autocalculated Fields 280
Autocalculatable Fields 539



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2023-10-16 08:58:20

Annual and Peak Values - Electricity

Electricity Annual Value [GJ] Electricity Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Electricity Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
Electricity:Facility 12134.96 134519.84 25-JAN-03:50 626175.88 27-JUL-18:10
Electricity:Building 2943.68 36656.90 02-JAN-02:10 182730.36 02-JAN-20:10
Electricity:Zone:BASEMENT 315.54 3631.19 02-JAN-02:10 23630.80 02-JAN-20:10
Electricity:SpaceType:GENERAL 2925.41 36182.64 02-JAN-02:10 182063.43 02-JAN-20:10
InteriorLights:Electricity 1174.11 10291.59 02-JAN-02:10 93091.76 02-JAN-20:10
InteriorLights:Electricity:Zone:BASEMENT 165.29 1501.97 02-JAN-02:10 13517.00 02-JAN-20:10
InteriorLights:Electricity:SpaceType:GENERAL 1174.11 10291.59 02-JAN-02:10 93091.76 02-JAN-20:10
LightsWired:InteriorLights:Electricity 1174.11 10291.59 02-JAN-02:10 93091.76 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:BASEMENT 165.29 1501.97 02-JAN-02:10 13517.00 02-JAN-20:10
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL 1174.11 10291.59 02-JAN-02:10 93091.76 02-JAN-20:10
Electricity:Zone:RETAIL_1_FLR_1 18.59 220.70 02-JAN-02:10 1372.90 02-JAN-20:10
InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 8.40 76.37 02-JAN-02:10 687.30 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 8.40 76.37 02-JAN-02:10 687.30 02-JAN-20:10
Electricity:Zone:RETAIL_2_FLR_1 21.53 255.58 02-JAN-02:10 1589.82 02-JAN-20:10
InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 9.73 88.43 02-JAN-02:10 795.89 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 9.73 88.43 02-JAN-02:10 795.89 02-JAN-20:10
Electricity:Zone:MECH_FLR_1 30.66 342.02 02-JAN-02:10 2327.13 02-JAN-20:10
InteriorLights:Electricity:Zone:MECH_FLR_1 18.19 165.30 02-JAN-02:10 1487.69 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:MECH_FLR_1 18.19 165.30 02-JAN-02:10 1487.69 02-JAN-20:10
Electricity:Zone:STORAGE_FLR_1 6.94 81.32 02-JAN-02:10 515.26 02-JAN-20:10
InteriorLights:Electricity:Zone:STORAGE_FLR_1 3.34 30.34 02-JAN-02:10 273.10 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:STORAGE_FLR_1 3.34 30.34 02-JAN-02:10 273.10 02-JAN-20:10
Electricity:Zone:LAUNDRY_FLR_1 72.06 1000.18 02-JAN-02:10 4910.17 02-JAN-20:10
InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 4.13 37.49 02-JAN-02:10 337.37 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 4.13 37.49 02-JAN-02:10 337.37 02-JAN-20:10
Electricity:Zone:CAFE_FLR_1 40.96 445.13 02-JAN-02:10 3142.50 02-JAN-20:10
InteriorLights:Electricity:Zone:CAFE_FLR_1 26.62 241.91 02-JAN-02:10 2177.23 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:CAFE_FLR_1 26.62 241.91 02-JAN-02:10 2177.23 02-JAN-20:10
Electricity:Zone:LOBBY_FLR_1 293.89 3428.00 02-JAN-02:10 21878.53 02-JAN-20:10
InteriorLights:Electricity:Zone:LOBBY_FLR_1 144.90 1316.59 02-JAN-02:10 11849.32 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:LOBBY_FLR_1 144.90 1316.59 02-JAN-02:10 11849.32 02-JAN-20:10
Electricity:Zone:ROOM_1_FLR_3 32.70 383.52 01-JAN-02:10 2308.42 01-JAN-21:10
InteriorLights:Electricity:Zone:ROOM_1_FLR_3 20.41 172.80 01-JAN-02:10 1570.91 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_3 20.41 172.80 01-JAN-02:10 1570.91 01-JAN-19:10
Electricity:Zone:ROOM_2_FLR_3 32.70 383.47 01-JAN-02:10 2308.15 01-JAN-21:10
InteriorLights:Electricity:Zone:ROOM_2_FLR_3 20.41 172.78 01-JAN-02:10 1570.72 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_3 20.41 172.78 01-JAN-02:10 1570.72 01-JAN-19:10
Electricity:Zone:ROOM_3_MULT19_FLR_3 472.46 5984.83 01-JAN-02:10 32482.97 01-JAN-21:10
InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 243.71 2063.36 01-JAN-02:10 18757.86 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 243.71 2063.36 01-JAN-02:10 18757.86 01-JAN-19:10
Electricity:Zone:ROOM_4_MULT19_FLR_3 472.59 5986.46 01-JAN-02:10 32491.86 01-JAN-21:10
InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 243.77 2063.93 01-JAN-02:10 18762.99 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 243.77 2063.93 01-JAN-02:10 18762.99 01-JAN-19:10
Electricity:Zone:ROOM_5_FLR_3 32.70 383.52 01-JAN-02:10 2308.42 01-JAN-21:10
InteriorLights:Electricity:Zone:ROOM_5_FLR_3 20.41 172.80 01-JAN-02:10 1570.91 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_5_FLR_3 20.41 172.80 01-JAN-02:10 1570.91 01-JAN-19:10
Electricity:Zone:ROOM_6_FLR_3 32.70 383.47 01-JAN-02:10 2308.15 01-JAN-21:10
InteriorLights:Electricity:Zone:ROOM_6_FLR_3 20.41 172.78 01-JAN-02:10 1570.72 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_6_FLR_3 20.41 172.78 01-JAN-02:10 1570.72 01-JAN-19:10
Electricity:Zone:CORRIDOR_FLR_3 62.74 570.05 02-JAN-02:10 5130.41 02-JAN-20:10
InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 62.74 570.05 02-JAN-02:10 5130.41 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 62.74 570.05 02-JAN-02:10 5130.41 02-JAN-20:10
Electricity:Zone:ROOM_1_FLR_6 8.18 95.88 01-JAN-02:10 577.11 01-JAN-21:10
InteriorLights:Electricity:Zone:ROOM_1_FLR_6 5.10 43.20 01-JAN-02:10 392.73 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_6 5.10 43.20 01-JAN-02:10 392.73 01-JAN-19:10
Electricity:Zone:ROOM_2_FLR_6 8.17 95.87 01-JAN-02:10 577.04 01-JAN-21:10
InteriorLights:Electricity:Zone:ROOM_2_FLR_6 5.10 43.19 01-JAN-02:10 392.68 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_6 5.10 43.19 01-JAN-02:10 392.68 01-JAN-19:10
Electricity:Zone:ROOM_3_MULT9_FLR_6 55.96 708.92 01-JAN-02:10 3847.72 01-JAN-21:10
InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 28.87 244.41 01-JAN-02:10 2221.93 01-JAN-19:10
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 28.87 244.41 01-JAN-02:10 2221.93 01-JAN-19:10
Electricity:Zone:BANQUET_FLR_6 222.61 2674.12 02-JAN-02:10 10571.30 02-JAN-20:10
InteriorLights:Electricity:Zone:BANQUET_FLR_6 46.75 424.82 02-JAN-02:10 3823.39 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:BANQUET_FLR_6 46.75 424.82 02-JAN-02:10 3823.39 02-JAN-20:10
Electricity:Zone:DINING_FLR_6 222.61 2674.12 02-JAN-02:10 10571.30 02-JAN-20:10
InteriorLights:Electricity:Zone:DINING_FLR_6 46.75 424.82 02-JAN-02:10 3823.39 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:DINING_FLR_6 46.75 424.82 02-JAN-02:10 3823.39 02-JAN-20:10
Electricity:Zone:KITCHEN_FLR_6 470.78 6777.71 02-JAN-02:10 19298.76 01-JAN-11:10
InteriorLights:Electricity:Zone:KITCHEN_FLR_6 12.48 113.42 02-JAN-02:10 1020.78 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:KITCHEN_FLR_6 12.48 113.42 02-JAN-02:10 1020.78 02-JAN-20:10
Electricity:Zone:CORRIDOR_FLR_6 16.60 150.83 02-JAN-02:10 1357.44 02-JAN-20:10
InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 16.60 150.83 02-JAN-02:10 1357.44 02-JAN-20:10
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 16.60 150.83 02-JAN-02:10 1357.44 02-JAN-20:10
InteriorEquipment:Electricity 1751.30 25891.05 02-JAN-02:10 89674.66 02-JAN-07:10
InteriorEquipment:Electricity:Zone:BASEMENT 150.26 2129.22 02-JAN-02:10 10113.80 02-JAN-20:10
InteriorEquipment:Electricity:SpaceType:GENERAL 1751.30 25891.05 02-JAN-02:10 89674.66 02-JAN-07:10
MiscPlug:InteriorEquipment:Electricity 959.56 15202.41 02-JAN-02:10 59492.27 02-JAN-07:10
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT 150.26 2129.22 02-JAN-02:10 10113.80 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL 959.56 15202.41 02-JAN-02:10 59492.27 02-JAN-07:10
InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 10.19 144.34 02-JAN-02:10 685.60 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 10.19 144.34 02-JAN-02:10 685.60 02-JAN-20:10
InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 11.79 167.14 02-JAN-02:10 793.93 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 11.79 167.14 02-JAN-02:10 793.93 02-JAN-20:10
InteriorEquipment:Electricity:Zone:MECH_FLR_1 12.47 176.73 02-JAN-02:10 839.45 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:MECH_FLR_1 12.47 176.73 02-JAN-02:10 839.45 02-JAN-20:10
InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 3.60 50.98 02-JAN-02:10 242.16 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 3.60 50.98 02-JAN-02:10 242.16 02-JAN-20:10
InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 67.94 962.69 02-JAN-02:10 4572.80 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 67.94 962.69 02-JAN-02:10 4572.80 02-JAN-20:10
InteriorEquipment:Electricity:Zone:CAFE_FLR_1 14.34 203.22 02-JAN-02:10 965.27 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:CAFE_FLR_1 14.34 203.22 02-JAN-02:10 965.27 02-JAN-20:10
InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 149.00 2111.41 02-JAN-02:10 10029.21 02-JAN-20:10
MiscPlug:InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 149.00 2111.41 02-JAN-02:10 10029.21 02-JAN-20:10
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 12.29 210.72 01-JAN-00:10 948.23 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 12.29 210.72 01-JAN-00:10 948.23 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 12.29 210.69 01-JAN-00:10 948.12 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 12.29 210.69 01-JAN-00:10 948.12 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 228.75 3921.46 01-JAN-00:10 17646.57 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 228.75 3921.46 01-JAN-00:10 17646.57 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 228.82 3922.53 01-JAN-00:10 17651.40 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 228.82 3922.53 01-JAN-00:10 17651.40 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 12.29 210.72 01-JAN-00:10 948.23 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 12.29 210.72 01-JAN-00:10 948.23 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 12.29 210.69 01-JAN-00:10 948.12 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 12.29 210.69 01-JAN-00:10 948.12 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 3.07 52.68 01-JAN-00:10 237.06 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 3.07 52.68 01-JAN-00:10 237.06 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 3.07 52.67 01-JAN-00:10 237.03 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 3.07 52.67 01-JAN-00:10 237.03 01-JAN-08:10
InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 27.10 464.51 01-JAN-00:10 2090.30 01-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 27.10 464.51 01-JAN-00:10 2090.30 01-JAN-08:10
InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 175.86 2249.30 01-JAN-00:10 6747.90 01-JAN-07:10
Cooking:InteriorEquipment:Electricity 762.04 9746.88 01-JAN-00:10 29240.64 01-JAN-07:10
Cooking:InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 175.86 2249.30 01-JAN-00:10 6747.90 01-JAN-07:10
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL 762.04 9746.88 01-JAN-00:10 29240.64 01-JAN-07:10
InteriorEquipment:Electricity:Zone:DINING_FLR_6 175.86 2249.30 01-JAN-00:10 6747.90 01-JAN-07:10
Cooking:InteriorEquipment:Electricity:Zone:DINING_FLR_6 175.86 2249.30 01-JAN-00:10 6747.90 01-JAN-07:10
InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 440.03 6190.03 01-JAN-00:10 16686.59 01-JAN-07:10
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 410.33 5248.28 01-JAN-00:10 15744.84 01-JAN-07:10
ReachInFreezer:InteriorEquipment:Electricity 16.27 515.92 01-JAN-00:10 515.92 01-JAN-00:10
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 16.27 515.92 01-JAN-00:10 515.92 01-JAN-00:10
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL 16.27 515.92 01-JAN-00:10 515.92 01-JAN-00:10
ReachInRefrigerator:InteriorEquipment:Electricity 13.43 425.83 01-JAN-00:10 425.83 01-JAN-00:10
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 13.43 425.83 01-JAN-00:10 425.83 01-JAN-00:10
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL 13.43 425.83 01-JAN-00:10 425.83 01-JAN-00:10
Refrigeration:Electricity 75.79 1278.51 03-FEB-23:30 3644.83 25-AUG-06:40
Refrigeration:Electricity:Zone:KITCHEN_FLR_6 18.27 261.51 02-JAN-11:30 2271.91 01-JAN-11:10
General:Refrigeration:Electricity 18.27 261.51 02-JAN-11:30 2271.91 01-JAN-11:10
General:Refrigeration:Electricity:Zone:KITCHEN_FLR_6 18.27 261.51 02-JAN-11:30 2271.91 01-JAN-11:10
Electricity:Plant 5901.99 2768.99 25-JAN-03:50 341058.72 27-JUL-18:10
LowTempRefrigeration:Refrigeration:Electricity 22.65 0.00 01-JAN-11:10 1889.43 07-NOV-08:20
MedTempRefrigeration:Refrigeration:Electricity 34.87 946.12 27-JAN-02:10 1202.21 18-FEB-14:10
Fans:Electricity 1826.65 50417.84 28-JAN-06:10 74877.68 30-SEP-15:20
Fans:Electricity:Zone:ROOM_1_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_2_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_5_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_5_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_6_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_6_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_1_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_2_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Electricity:HVAC 2379.90 66550.92 28-JAN-06:10 92696.42 29-JUL-18:20
ExteriorEquipment:Electricity 679.68 10574.27 02-JAN-02:20 40537.60 02-JAN-07:20
Transformer:ExteriorEquipment:Electricity 32.92 556.27 02-JAN-02:20 1912.91 02-JAN-21:10
ElectricityPurchased:Facility 12134.96 134519.84 25-JAN-03:50 626175.88 27-JUL-18:10
ElectricityPurchased:Plant 12134.96 134519.84 25-JAN-03:50 626175.88 27-JUL-18:10
Cogeneration:ElectricityPurchased 12134.96 134519.84 25-JAN-03:50 626175.88 27-JUL-18:10
General:Cogeneration:ElectricityPurchased 12134.96 134519.84 25-JAN-03:50 626175.88 27-JUL-18:10
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricityNet:Facility 12134.96 134519.84 25-JAN-03:50 626175.88 27-JUL-18:10
ElectricityNet:Plant 12134.96 134519.84 25-JAN-03:50 626175.88 27-JUL-18:10
Cogeneration:ElectricityNet 12134.96 134519.84 25-JAN-03:50 626175.88 27-JUL-18:10
General:Cogeneration:ElectricityNet 12134.96 134519.84 25-JAN-03:50 626175.88 27-JUL-18:10
General:Fans:Electricity 1826.65 50417.84 28-JAN-06:10 74877.68 30-SEP-15:20
ExteriorLights:Electricity 262.62 0.00 01-JAN-07:20 16690.39 01-JAN-00:10
General:ExteriorLights:Electricity 262.62 0.00 01-JAN-07:20 16690.39 01-JAN-00:10
ElevatorLift:ExteriorEquipment:Electricity 616.11 9046.01 01-JAN-00:10 37691.69 01-JAN-07:10
ElevatorLightsFan:ExteriorEquipment:Electricity 30.65 972.00 01-JAN-00:10 972.00 01-JAN-00:10
HeatRecovery:Electricity 520.33 15269.97 01-JAN-00:10 16791.79 01-JAN-09:20
General:HeatRecovery:Electricity 520.33 15269.97 01-JAN-00:10 16791.79 01-JAN-09:20
WaterSystems:Electricity 90.77 1086.98 23-AUG-00:10 4739.42 18-JAN-07:10
Water Heater:WaterSystems:Electricity 90.77 1086.98 23-AUG-00:10 4739.42 18-JAN-07:10
Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Boiler Parasitic:Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:Electricity 5293.72 0.00 25-JAN-03:50 317380.64 27-JUL-18:10
General:Cooling:Electricity 5293.72 0.00 25-JAN-03:50 317380.64 27-JUL-18:10
Pumps:Electricity 459.98 160.64 03-FEB-08:20 16829.26 29-JUL-10:40
General:Pumps:Electricity 459.98 160.64 03-FEB-08:20 16829.26 29-JUL-10:40
WIRED_LTG_ELECTRICITY 41.33 0.00 01-JAN-00:10 3276.83 02-JAN-20:20


Annual and Peak Values - Natural Gas

Natural Gas Annual Value [GJ] Natural Gas Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Natural Gas Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
NaturalGas:Facility 4881.68 41554.20 25-OCT-23:10 352716.65 17-DEC-18:00
NaturalGas:Building 1788.84 13361.90 02-JAN-02:10 104248.32 02-JAN-18:10
NaturalGas:Zone:LAUNDRY_FLR_1 590.20 8363.49 02-JAN-02:10 39726.58 02-JAN-20:10
NaturalGas:SpaceType:GENERAL 1788.84 13361.90 02-JAN-02:10 104248.32 02-JAN-18:10
InteriorEquipment:NaturalGas 1788.84 13361.90 02-JAN-02:10 104248.32 02-JAN-18:10
InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 590.20 8363.49 02-JAN-02:10 39726.58 02-JAN-20:10
InteriorEquipment:NaturalGas:SpaceType:GENERAL 1788.84 13361.90 02-JAN-02:10 104248.32 02-JAN-18:10
Laundry:InteriorEquipment:NaturalGas 590.20 8363.49 02-JAN-02:10 39726.58 02-JAN-20:10
Laundry:InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 590.20 8363.49 02-JAN-02:10 39726.58 02-JAN-20:10
Laundry:InteriorEquipment:NaturalGas:SpaceType:GENERAL 590.20 8363.49 02-JAN-02:10 39726.58 02-JAN-20:10
NaturalGas:Zone:KITCHEN_FLR_6 1198.64 4998.41 01-JAN-00:10 74976.11 01-JAN-16:10
InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 1198.64 4998.41 01-JAN-00:10 74976.11 01-JAN-16:10
Cooking:InteriorEquipment:NaturalGas 1198.64 4998.41 01-JAN-00:10 74976.11 01-JAN-16:10
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 1198.64 4998.41 01-JAN-00:10 74976.11 01-JAN-16:10
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL 1198.64 4998.41 01-JAN-00:10 74976.11 01-JAN-16:10
NaturalGas:Plant 3092.84 18467.44 18-MAY-07:10 265195.31 17-DEC-18:00
WaterSystems:NaturalGas 2623.98 18467.44 01-JAN-00:10 222392.17 17-JAN-21:20
Water Heater:WaterSystems:NaturalGas 2623.98 18467.44 01-JAN-00:10 222392.17 17-JAN-21:20
Heating:NaturalGas 468.86 0.00 02-JAN-21:50 98398.35 20-MAR-10:40
Boiler:Heating:NaturalGas 468.86 0.00 02-JAN-21:50 98398.35 20-MAR-10:40


Annual and Peak Values - Cooling

Cooling Annual Value [GJ] Cooling Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Cooling Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
PlantLoopCoolingDemand:Facility 16383.96 0.00 25-JAN-03:50 955350.72 27-JUL-18:10
PlantLoopCoolingDemand:HVAC 16383.96 0.00 25-JAN-03:50 955350.72 27-JUL-18:10
CoolingCoils:PlantLoopCoolingDemand 16383.96 0.00 25-JAN-03:50 955350.72 27-JUL-18:10


Annual and Peak Values - Water

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
Water:Facility 9857.19 0.00 02-JAN-01:10 0.00 02-JAN-21:10
Water:Plant 9857.19 0.00 02-JAN-01:10 0.00 02-JAN-21:10
WaterSystems:Water 9857.19 0.00 02-JAN-01:10 0.00 02-JAN-21:10
Water Heater:WaterSystems:Water 5742.51 0.00 02-JAN-01:10 0.00 02-JAN-19:20
MainsWater:Facility 9857.19 0.00 02-JAN-01:10 0.00 02-JAN-21:10
MainsWater:Plant 9857.19 0.00 02-JAN-01:10 0.00 02-JAN-21:10
WaterSystems:MainsWater 9857.19 0.00 02-JAN-01:10 0.00 02-JAN-21:10
Water Heater:WaterSystems:MainsWater 5742.51 0.00 02-JAN-01:10 0.00 02-JAN-19:20
WaterUse:WaterSystems:Water 4114.69 0.00 02-JAN-01:10 0.00 02-JAN-07:10
WaterUse:WaterSystems:MainsWater 4114.69 0.00 02-JAN-01:10 0.00 02-JAN-07:10


Annual and Peak Values - Other by Weight/Mass

Annual Value [kg] Minimum Value [kg/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [kg/s] Timestamp of Maximum {TIMESTAMP}
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10


Annual and Peak Values - Other Volumetric

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [L] Minimum Value [L] Timestamp of Minimum {TIMESTAMP} Maximum Value [L] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other

Annual Value [GJ] Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
EnergyTransfer:Facility 72009.40 249775.78 31-JAN-08:30 4196475.15 27-JUL-18:10
EnergyTransfer:Building 7554.41 125864.02 16-MAR-08:20 397045.80 29-JUL-18:10
EnergyTransfer:Zone:KITCHEN_FLR_6 788.12 12603.26 04-FEB-04:00 35983.06 23-JUL-10:50
Refrigeration:EnergyTransfer 194.83 3929.75 03-FEB-23:30 10388.25 25-AUG-06:40
Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 97.41 1964.88 03-FEB-23:30 5194.13 25-AUG-06:40
General:Refrigeration:EnergyTransfer 97.41 1964.88 03-FEB-23:30 5194.13 25-AUG-06:40
General:Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 97.41 1964.88 03-FEB-23:30 5194.13 25-AUG-06:40
EnergyTransfer:Plant 39785.94 36215.22 25-JAN-03:50 2278271.55 27-JUL-18:10
LowTempRefrigeration:Refrigeration:EnergyTransfer 25.91 0.00 01-JAN-11:10 2686.44 01-JAN-11:40
MedTempRefrigeration:Refrigeration:EnergyTransfer 71.50 1788.35 27-JAN-02:10 2556.62 18-FEB-14:10
EnergyTransfer:Zone:BASEMENT 571.45 10899.84 13-MAR-11:00 25224.75 02-AUG-18:10
Heating:EnergyTransfer 1.25 0.00 01-JAN-00:10 10145.63 04-FEB-09:10
Heating:EnergyTransfer:Zone:BASEMENT 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer 1.25 0.00 01-JAN-00:10 10145.63 04-FEB-09:10
General:Heating:EnergyTransfer:Zone:BASEMENT 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer 7455.74 121059.34 04-FEB-07:10 393265.51 29-JUL-18:10
Cooling:EnergyTransfer:Zone:BASEMENT 571.45 10899.84 13-MAR-11:00 25224.75 02-AUG-18:10
General:Cooling:EnergyTransfer 7455.74 121059.34 04-FEB-07:10 393265.51 29-JUL-18:10
General:Cooling:EnergyTransfer:Zone:BASEMENT 571.45 10899.84 13-MAR-11:00 25224.75 02-AUG-18:10
EnergyTransfer:Zone:RETAIL_1_FLR_1 65.05 5.09 04-FEB-04:50 3492.96 08-NOV-11:40
Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 0.00 0.00 01-JAN-00:10 150.57 04-FEB-07:20
General:Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 0.00 0.00 01-JAN-00:10 150.57 04-FEB-07:20
Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 65.05 0.00 04-FEB-04:50 3492.96 08-NOV-11:40
General:Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 65.05 0.00 04-FEB-04:50 3492.96 08-NOV-11:40
EnergyTransfer:Zone:RETAIL_2_FLR_1 52.02 767.92 20-MAR-09:50 2374.99 29-JUL-18:10
Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 52.02 767.92 20-MAR-09:50 2374.99 29-JUL-18:10
General:Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 52.02 767.92 20-MAR-09:50 2374.99 29-JUL-18:10
EnergyTransfer:Zone:MECH_FLR_1 52.39 265.83 04-FEB-06:00 2584.90 29-JUL-18:10
Heating:EnergyTransfer:Zone:MECH_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:MECH_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:MECH_FLR_1 52.39 265.83 04-FEB-06:00 2584.90 29-JUL-18:10
General:Cooling:EnergyTransfer:Zone:MECH_FLR_1 52.39 265.83 04-FEB-06:00 2584.90 29-JUL-18:10
EnergyTransfer:Zone:STORAGE_FLR_1 24.86 47.99 04-FEB-07:30 1271.40 29-JUL-18:10
Heating:EnergyTransfer:Zone:STORAGE_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:STORAGE_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 24.86 47.99 04-FEB-07:30 1271.40 29-JUL-18:10
General:Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 24.86 47.99 04-FEB-07:30 1271.40 29-JUL-18:10
EnergyTransfer:Zone:LAUNDRY_FLR_1 629.71 9321.26 04-FEB-06:00 37904.85 27-JUL-20:00
Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 629.71 9321.26 04-FEB-06:00 37904.85 27-JUL-20:00
General:Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 629.71 9321.26 04-FEB-06:00 37904.85 27-JUL-20:00
EnergyTransfer:Zone:CAFE_FLR_1 317.92 3212.23 16-MAR-08:10 14249.61 09-DEC-11:40
Heating:EnergyTransfer:Zone:CAFE_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:CAFE_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:CAFE_FLR_1 317.92 3212.23 16-MAR-08:10 14249.61 09-DEC-11:40
General:Cooling:EnergyTransfer:Zone:CAFE_FLR_1 317.92 3212.23 16-MAR-08:10 14249.61 09-DEC-11:40
EnergyTransfer:Zone:LOBBY_FLR_1 1063.20 16916.29 16-MAR-09:10 45087.94 29-JUL-18:10
Heating:EnergyTransfer:Zone:LOBBY_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:LOBBY_FLR_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 1063.20 16916.29 16-MAR-09:10 45087.94 29-JUL-18:10
General:Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 1063.20 16916.29 16-MAR-09:10 45087.94 29-JUL-18:10
EnergyTransfer:Zone:ROOM_1_FLR_3 107.46 0.05 20-MAR-03:30 11364.77 30-SEP-15:10
Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 0.13 0.00 01-JAN-00:10 1569.32 04-FEB-07:00
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 0.13 0.00 01-JAN-00:10 1569.32 04-FEB-07:00
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 107.34 0.00 25-JAN-02:30 11364.77 30-SEP-15:10
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 107.34 0.00 25-JAN-02:30 11364.77 30-SEP-15:10
EnergyTransfer:Zone:ROOM_2_FLR_3 98.77 0.24 20-DEC-03:50 11055.82 28-JUL-15:10
Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 0.25 0.00 01-JAN-00:10 1981.91 16-MAR-08:10
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 0.25 0.00 01-JAN-00:10 1981.91 16-MAR-08:10
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 98.52 0.00 09-JAN-04:40 11055.82 28-JUL-15:10
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 98.52 0.00 09-JAN-04:40 11055.82 28-JUL-15:10
EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 823.41 6428.04 04-FEB-06:00 57423.74 03-DEC-14:00
Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 823.41 6428.04 04-FEB-06:00 57423.74 03-DEC-14:00
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 823.41 6428.04 04-FEB-06:00 57423.74 03-DEC-14:00
EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 911.65 1271.08 04-FEB-06:00 79130.96 29-JUL-18:20
Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 0.27 0.00 01-JAN-00:10 5705.94 04-FEB-09:10
General:Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 0.27 0.00 01-JAN-00:10 5705.94 04-FEB-09:10
Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 911.38 0.00 03-FEB-16:20 79130.96 29-JUL-18:20
General:Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 911.38 0.00 03-FEB-16:20 79130.96 29-JUL-18:20
EnergyTransfer:Zone:ROOM_5_FLR_3 108.45 0.16 23-JAN-02:10 9655.19 29-JUL-15:10
Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 0.11 0.00 01-JAN-00:10 1641.15 04-FEB-07:00
General:Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 0.11 0.00 01-JAN-00:10 1641.15 04-FEB-07:00
Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 108.33 0.00 23-JAN-02:10 9655.19 29-JUL-15:10
General:Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 108.33 0.00 23-JAN-02:10 9655.19 29-JUL-15:10
EnergyTransfer:Zone:ROOM_6_FLR_3 99.62 0.56 20-MAR-05:30 9710.76 23-JUL-08:10
Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 0.24 0.00 01-JAN-00:10 1888.81 04-FEB-06:00
General:Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 0.24 0.00 01-JAN-00:10 1888.81 04-FEB-06:00
Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 99.38 0.00 09-JAN-04:10 9710.76 23-JUL-08:10
General:Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 99.38 0.00 09-JAN-04:10 9710.76 23-JUL-08:10
EnergyTransfer:Zone:CORRIDOR_FLR_3 283.36 2335.37 04-FEB-07:10 12570.33 30-JUL-10:40
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 283.36 2335.37 04-FEB-07:10 12570.33 30-JUL-10:40
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 283.36 2335.37 04-FEB-07:10 12570.33 30-JUL-10:40
EnergyTransfer:Zone:ROOM_1_FLR_6 29.31 0.05 27-NOV-02:30 3127.43 29-JUL-15:10
Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 0.08 0.00 01-JAN-00:10 603.45 16-MAR-08:10
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 0.08 0.00 01-JAN-00:10 603.45 16-MAR-08:10
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 29.23 0.00 08-JAN-06:10 3127.43 29-JUL-15:10
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 29.23 0.00 08-JAN-06:10 3127.43 29-JUL-15:10
EnergyTransfer:Zone:ROOM_2_FLR_6 27.03 0.11 14-DEC-03:20 3151.49 28-JUL-15:10
Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 0.14 0.00 01-JAN-00:10 714.87 16-MAR-08:10
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 0.14 0.00 01-JAN-00:10 714.87 16-MAR-08:10
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 26.90 0.00 08-JAN-06:10 3151.49 28-JUL-15:10
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 26.90 0.00 08-JAN-06:10 3151.49 28-JUL-15:10
EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 172.26 4.25 05-FEB-06:40 14358.73 26-JAN-16:10
Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 0.04 0.00 01-JAN-00:10 1558.19 04-FEB-07:00
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 0.04 0.00 01-JAN-00:10 1558.19 04-FEB-07:00
Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 172.23 0.00 04-FEB-02:10 14358.73 26-JAN-16:10
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 172.23 0.00 04-FEB-02:10 14358.73 26-JAN-16:10
EnergyTransfer:Zone:BANQUET_FLR_6 571.44 10647.69 16-MAR-08:20 23491.95 27-JUL-18:10
Heating:EnergyTransfer:Zone:BANQUET_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:BANQUET_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 571.44 10647.69 16-MAR-08:20 23491.95 27-JUL-18:10
General:Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 571.44 10647.69 16-MAR-08:20 23491.95 27-JUL-18:10
EnergyTransfer:Zone:DINING_FLR_6 608.21 11941.92 16-MAR-08:20 24830.75 27-JUL-18:10
Heating:EnergyTransfer:Zone:DINING_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:DINING_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:DINING_FLR_6 608.21 11941.92 16-MAR-08:20 24830.75 27-JUL-18:10
General:Cooling:EnergyTransfer:Zone:DINING_FLR_6 608.21 11941.92 16-MAR-08:20 24830.75 27-JUL-18:10
Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 690.70 10412.94 04-FEB-04:00 30917.08 23-JUL-10:50
General:Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 690.70 10412.94 04-FEB-04:00 30917.08 23-JUL-10:50
EnergyTransfer:Zone:CORRIDOR_FLR_6 148.71 39.86 04-FEB-08:00 7375.06 29-JUL-17:20
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 0.00 0.00 01-JAN-00:10 305.94 04-FEB-07:10
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 0.00 0.00 01-JAN-00:10 305.94 04-FEB-07:10
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 148.71 0.00 04-FEB-06:10 7375.06 29-JUL-17:20
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 148.71 0.00 04-FEB-06:10 7375.06 29-JUL-17:20
PlantLoopHeatingDemand:Facility 837.71 9044.68 30-JUL-00:10 85007.64 20-MAR-10:40
PlantLoopHeatingDemand:Plant 535.81 6417.92 19-JUL-00:50 39050.24 25-JAN-07:10
WaterSystems:PlantLoopHeatingDemand 535.81 6417.92 19-JUL-00:50 39050.24 25-JAN-07:10
General:WaterSystems:PlantLoopHeatingDemand 535.81 6417.92 19-JUL-00:50 39050.24 25-JAN-07:10
EnergyTransfer:HVAC 24669.05 21335.58 13-NOV-08:20 1524124.30 27-JUL-18:10
HeatingCoils:EnergyTransfer 301.90 0.00 02-JAN-21:50 70028.25 20-MAR-10:40
PlantLoopHeatingDemand:HVAC 301.90 0.00 02-JAN-21:50 70028.25 20-MAR-10:40
HeatingCoils:PlantLoopHeatingDemand 301.90 0.00 02-JAN-21:50 70028.25 20-MAR-10:40
CoolingCoils:EnergyTransfer 16383.96 0.00 25-JAN-03:50 955350.72 27-JUL-18:10
HeatRecoveryForHeating:EnergyTransfer 80.71 0.00 01-JAN-00:10 287887.68 04-FEB-07:00
HeatRecoveryForCooling:EnergyTransfer 7902.48 0.00 01-JAN-00:10 598067.25 14-JUL-11:00
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
WaterSystems:EnergyTransfer 535.81 6417.92 19-JUL-00:50 39050.24 25-JAN-07:10
WaterUse:WaterSystems:EnergyTransfer 535.81 6417.92 19-JUL-00:50 39050.24 25-JAN-07:10
Boilers:EnergyTransfer 299.40 0.00 02-JAN-21:50 76117.71 20-MAR-10:40
Chillers:EnergyTransfer 16779.80 0.00 25-JAN-03:50 967946.11 27-JUL-18:10
HeatRejection:EnergyTransfer 22073.52 0.00 25-JAN-03:50 1285326.75 27-JUL-18:10
General:HeatRejection:EnergyTransfer 22073.52 0.00 25-JAN-03:50 1285326.75 27-JUL-18:10



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2023-10-16 08:58:20

Annual Building Sensible Heat Gain Components

HVAC Zone Eq & Other Sensible Air Heating [GJ] HVAC Zone Eq & Other Sensible Air Cooling [GJ] HVAC Terminal Unit Sensible Air Heating [GJ] HVAC Terminal Unit Sensible Air Cooling [GJ] HVAC Input Heated Surface Heating [GJ] HVAC Input Cooled Surface Cooling [GJ] People Sensible Heat Addition [GJ] Lights Sensible Heat Addition [GJ] Equipment Sensible Heat Addition [GJ] Window Heat Addition [GJ] Interzone Air Transfer Heat Addition [GJ] Infiltration Heat Addition [GJ] Opaque Surface Conduction and Other Heat Addition [GJ] Equipment Sensible Heat Removal [GJ] Window Heat Removal [GJ] Interzone Air Transfer Heat Removal [GJ] Infiltration Heat Removal [GJ] Opaque Surface Conduction and Other Heat Removal [GJ]
BASEMENT 0.000 0.000 0.000 -571.454 0.000 0.000 157.215 165.288 150.255 0.000 0.000 0.000 98.696 0.000 0.000 0.000 0.000 0.000
RETAIL_1_FLR_1 0.000 0.000 0.001 -65.052 0.000 0.000 15.931 8.404 10.186 22.828 0.000 2.563 7.367 0.000 -1.715 0.000 -0.512 -0.000
RETAIL_2_FLR_1 0.000 0.000 0.000 -52.023 0.000 0.000 18.430 9.732 11.795 0.000 0.000 1.025 11.239 0.000 0.000 0.000 -0.198 0.000
MECH_FLR_1 0.000 0.000 0.000 -52.393 0.000 0.000 3.930 18.192 12.471 0.000 0.000 2.475 15.781 0.000 0.000 0.000 -0.455 0.000
STORAGE_FLR_1 0.000 0.000 0.000 -24.858 0.000 0.000 3.033 3.340 3.598 0.000 0.000 1.445 13.705 0.000 0.000 0.000 -0.262 0.000
LAUNDRY_FLR_1 0.000 0.000 0.000 -629.718 0.000 0.000 12.230 4.125 658.131 0.000 0.000 3.248 0.000 0.000 0.000 0.000 -0.699 -47.316
CAFE_FLR_1 0.000 0.000 0.000 -317.921 0.000 0.000 204.285 26.624 14.341 63.623 0.000 5.406 10.323 0.000 -5.451 0.000 -1.230 -0.001
LOBBY_FLR_1 0.000 0.000 0.000 -1063.210 0.000 0.000 610.445 144.896 148.998 85.915 0.000 16.013 67.170 0.000 -6.758 0.000 -3.469 -0.000
ROOM_1_FLR_3 0.309 -86.906 0.000 -20.609 0.000 0.000 9.635 20.410 12.292 48.982 0.000 5.783 15.721 0.000 -4.002 0.000 -1.613 -0.000
ROOM_2_FLR_3 0.568 -78.312 0.000 -20.521 0.000 0.000 9.644 20.407 12.291 41.028 0.000 5.804 14.652 0.000 -3.984 0.000 -1.577 -0.001
ROOM_3_MULT19_FLR_3 0.000 -491.402 0.000 -332.002 0.000 0.000 0.000 243.708 228.754 256.723 0.000 20.037 131.992 0.000 -32.360 0.000 -25.449 0.000
ROOM_4_MULT19_FLR_3 0.744 -636.032 0.000 -275.781 0.000 0.000 183.606 243.774 228.817 154.791 0.000 35.574 97.772 0.000 -20.530 0.000 -12.735 -0.005
ROOM_5_FLR_3 0.295 -87.847 0.000 -20.662 0.000 0.000 9.629 20.410 12.292 50.138 0.000 5.762 15.464 0.000 -3.838 0.000 -1.643 -0.001
ROOM_6_FLR_3 0.541 -79.090 0.000 -20.585 0.000 0.000 9.638 20.407 12.291 42.074 0.000 5.772 14.284 0.000 -3.726 0.000 -1.605 -0.001
CORRIDOR_FLR_3 0.000 0.000 0.000 -283.364 0.000 0.000 119.497 62.736 0.000 49.668 0.000 6.301 51.396 0.000 -4.689 0.000 -1.544 0.000
ROOM_1_FLR_6 0.152 -24.151 0.000 -5.154 0.000 0.000 2.409 5.102 3.073 12.070 0.000 1.441 6.473 0.000 -0.994 0.000 -0.421 -0.000
ROOM_2_FLR_6 0.261 -21.883 0.000 -5.134 0.000 0.000 2.411 5.102 3.073 10.103 0.000 1.445 6.023 0.000 -0.987 0.000 -0.413 -0.000
ROOM_3_MULT9_FLR_6 0.121 -139.117 0.000 -33.190 0.000 0.000 21.664 28.868 27.097 58.721 0.000 7.015 35.780 0.000 -4.538 0.000 -2.421 -0.001
BANQUET_FLR_6 0.000 0.000 0.000 -571.449 0.000 0.000 351.989 46.753 175.857 17.237 0.000 3.238 0.000 0.000 -2.963 0.000 -0.885 -19.776
DINING_FLR_6 0.000 0.000 0.000 -608.211 0.000 0.000 350.766 46.753 175.857 16.779 0.000 3.189 18.957 0.000 -3.192 0.000 -0.899 -0.002
KITCHEN_FLR_6 0.000 0.000 0.000 -690.697 0.000 0.000 30.124 12.482 556.656 23.357 0.000 2.039 69.903 0.000 -2.850 0.000 -1.015 0.000
CORRIDOR_FLR_6 0.000 0.000 0.001 -148.708 0.000 0.000 32.541 16.599 0.000 23.395 0.000 3.102 75.657 0.000 -1.952 0.000 -0.635 0.000
Total Facility 2.991 -1644.742 0.002 -5812.699 0.000 0.000 2159.049 1174.112 2458.123 977.432 0.000 138.678 778.354 0.000 -104.529 0.000 -59.680 -67.105


Peak Cooling Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
BASEMENT 02-AUG-18:10 0.00 0.00 0.00 -25278.66 0.00 0.00 6161.76 12015.03 9581.50 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -2479.63
RETAIL_1_FLR_1 08-NOV-11:35 0.00 0.00 0.00 -3527.00 0.00 0.00 156.11 190.92 252.59 4236.05 0.00 86.54 0.00 0.00 -0.00 0.00 0.00 -1395.21
RETAIL_2_FLR_1 27-JUL-18:10 0.00 0.00 0.00 -2384.23 0.00 0.00 725.49 707.46 752.15 0.00 0.00 84.26 114.88 0.00 -0.00 0.00 0.00 0.00
MECH_FLR_1 29-JUL-10:35 0.00 0.00 0.00 -2616.96 0.00 0.00 65.43 413.25 309.27 0.00 0.00 207.63 1621.38 0.00 -0.00 0.00 0.00 0.00
STORAGE_FLR_1 29-JUL-10:35 0.00 0.00 0.00 -1314.02 0.00 0.00 50.26 75.86 89.22 0.00 0.00 119.30 979.38 0.00 -0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 27-JUL-20:00 0.00 0.00 0.00 -37905.67 0.00 0.00 425.99 337.37 44299.38 0.00 0.00 141.80 0.00 0.00 -0.00 0.00 0.00 -7298.86
CAFE_FLR_1 09-DEC-11:35 0.00 0.00 0.00 -14449.99 0.00 0.00 3225.94 604.78 355.63 12040.61 0.00 220.33 0.00 0.00 -0.00 0.00 0.00 -1997.31
LOBBY_FLR_1 27-JUL-18:10 0.00 0.00 0.00 -45395.66 0.00 0.00 24439.44 10532.73 9501.36 2618.31 0.00 1366.82 0.00 0.00 -0.00 0.00 0.00 -3062.99
ROOM_1_FLR_3 24-FEB-16:02 0.00 -12467.77 0.00 -737.56 0.00 0.00 235.29 439.85 273.93 7404.87 0.00 115.58 4735.80 0.00 -0.00 0.00 0.00 0.00
ROOM_2_FLR_3 24-FEB-16:02 0.00 -12414.75 0.00 -727.56 0.00 0.00 235.28 439.80 273.90 6207.68 0.00 122.00 5863.64 0.00 -0.00 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 03-DEC-14:00 0.00 -46601.78 0.00 -10820.86 0.00 0.00 0.00 6190.09 5686.12 51654.33 0.00 265.78 0.00 0.00 -0.00 0.00 0.00 -6373.68
ROOM_4_MULT19_FLR_3 17-APR-18:02 0.00 -80785.85 0.00 -10293.86 0.00 0.00 6374.59 16699.06 9610.21 6626.57 0.00 1826.33 49942.95 0.00 -0.00 0.00 0.00 0.00
ROOM_5_FLR_3 24-FEB-19:01 0.00 -11172.82 0.00 -731.73 0.00 0.00 335.51 1398.11 516.26 0.00 0.00 0.00 10295.76 0.00 -532.80 0.00 -108.29 0.00
ROOM_6_FLR_3 29-JUL-15:02 0.00 -11152.73 0.00 -753.26 0.00 0.00 130.71 518.34 305.51 3299.52 0.00 581.84 7070.07 0.00 -0.00 0.00 0.00 0.00
CORRIDOR_FLR_3 30-JUL-10:35 0.00 0.00 0.00 -12609.33 0.00 0.00 1944.70 1710.14 0.00 4288.70 0.00 554.58 4111.22 0.00 -0.00 0.00 0.00 0.00
ROOM_1_FLR_6 24-FEB-16:02 0.00 -3321.42 0.00 -184.32 0.00 0.00 58.82 109.96 68.48 1823.41 0.00 28.22 1416.85 0.00 -0.00 0.00 0.00 0.00
ROOM_2_FLR_6 28-JUL-15:02 0.00 -3319.62 0.00 -189.63 0.00 0.00 58.82 109.95 68.48 1814.39 0.00 142.64 1314.98 0.00 -0.00 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 26-JAN-16:02 0.00 -14372.83 0.00 -1187.91 0.00 0.00 529.40 622.14 603.86 6543.61 0.00 0.00 7709.09 0.00 -0.00 0.00 -447.36 0.00
BANQUET_FLR_6 27-JUL-18:10 0.00 0.00 0.00 -23847.16 0.00 0.00 14156.44 3398.57 6747.90 1275.71 0.00 287.11 0.00 0.00 -0.00 0.00 0.00 -2018.57
DINING_FLR_6 27-JUL-18:10 0.00 0.00 0.00 -25183.04 0.00 0.00 14103.74 3398.57 6747.90 1253.13 0.00 285.48 0.00 0.00 -0.00 0.00 0.00 -605.79
KITCHEN_FLR_6 23-JUL-10:50 0.00 0.00 0.00 -30910.63 0.00 0.00 464.20 340.26 24459.16 2823.75 0.00 226.74 2596.52 0.00 -0.00 0.00 0.00 0.00
CORRIDOR_FLR_6 29-JUL-10:35 0.00 0.00 0.00 -7401.64 0.00 0.00 521.48 377.07 0.00 1864.19 0.00 255.96 4382.94 0.00 -0.00 0.00 0.00 0.00
Total Facility 29-JUL-18:02 0.00 -175800.27 0.00 -246050.52 0.00 0.00 71741.18 82807.27 115371.52 38083.19 0.00 12642.63 101205.00 0.00 0.00 0.00 0.00 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
BASEMENT - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 04-FEB-07:20 0.00 0.00 150.57 0.00 0.00 0.00 449.85 229.10 288.68 0.00 0.00 0.00 0.00 0.00 -560.24 0.00 -349.24 -208.72
RETAIL_2_FLR_1 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
MECH_FLR_1 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
STORAGE_FLR_1 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CAFE_FLR_1 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
LOBBY_FLR_1 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_3 16-MAR-08:62 4514.27 406.08 0.00 -406.08 0.00 0.00 102.04 691.20 453.05 0.00 0.00 0.00 0.00 0.00 -507.37 0.00 -637.74 -4615.45
ROOM_2_FLR_3 26-JAN-09:02 4594.80 410.35 0.00 -410.35 0.00 0.00 101.55 691.12 452.99 0.00 0.00 0.00 0.00 0.00 -259.48 0.00 -369.79 -5211.18
ROOM_3_MULT19_FLR_3 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 03-FEB-16:03 28544.92 6171.12 0.00 -6171.12 0.00 0.00 4886.62 5253.64 5099.29 0.00 0.00 0.00 0.00 0.00 -176.02 0.00 -14735.63 -28872.82
ROOM_5_FLR_3 16-MAR-15:04 3580.86 531.96 0.00 -531.96 0.00 0.00 236.33 439.85 273.93 1802.72 0.00 0.00 0.00 0.00 -0.00 0.00 -399.31 -5934.40
ROOM_6_FLR_3 24-JAN-16:03 3628.71 467.00 0.00 -467.00 0.00 0.00 257.34 439.80 273.90 0.00 0.00 0.00 0.00 0.00 -243.06 0.00 -766.09 -3590.59
CORRIDOR_FLR_3 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 16-MAR-08:62 1340.75 92.59 0.00 -92.59 0.00 0.00 26.15 172.80 113.26 0.00 0.00 0.00 0.00 0.00 -115.35 0.00 -154.05 -1383.56
ROOM_2_FLR_6 16-MAR-08:62 1360.17 86.68 0.00 -86.68 0.00 0.00 26.51 172.78 113.25 0.00 0.00 0.00 0.00 0.00 -224.93 0.00 -149.96 -1297.82
ROOM_3_MULT9_FLR_6 16-MAR-08:62 4676.69 676.12 0.00 -676.12 0.00 0.00 226.29 977.65 998.70 393.23 0.00 0.00 0.00 0.00 -0.00 0.00 -749.76 -6522.80
BANQUET_FLR_6 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
DINING_FLR_6 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
KITCHEN_FLR_6 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6 04-FEB-07:10 0.00 0.00 305.94 0.00 0.00 0.00 916.54 452.48 0.00 0.00 0.00 0.00 0.00 0.00 -1008.19 0.00 -448.20 -218.56
Total Facility 19-MAR-15:05 -92657.54 137481.26 0.00 -137481.26 0.00 0.00 36545.80 25732.27 75340.19 29931.38 0.00 0.00 0.00 0.00 0.00 0.00 -34803.90 -40088.20



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2023-10-16 08:58:20

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow - Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
VAV WITH REHEAT 21.3242 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 21.2175 0.0000 1.0000 Not calculated 0.0000 0.0000    
FLR_3_DOAS 2.0513 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 2.0513 0.0000 1.0000 Not calculated 0.0000 0.0000    


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
VAV WITH REHEAT 21.2175 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 21.2175 0.0000 1.0000 Not calculated 0.0000 0.0000    
FLR_3_DOAS 2.0513 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 2.0513 0.0000 1.0000 Not calculated 0.0000 0.0000    


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [m3/s-person] Zone Population - Pz Area Outdoor Air Rate - Ra [m3/s-m2] Zone Floor Area - Az [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [m3/s]
BASEMENT VAV WITH REHEAT 0.000000 106.4990 0.000432 1978.83 0.0000 1.0000 0.0000 1.000 0.0000
RETAIL_1_FLR_1 VAV WITH REHEAT 0.000000 10.8290 0.001181 67.07 0.0000 1.0000 0.0000 1.000 0.0000
RETAIL_2_FLR_1 VAV WITH REHEAT 0.000000 12.5400 0.001181 77.67 0.0000 1.0000 0.0000 1.000 0.0000
MECH_FLR_1 VAV WITH REHEAT 0.000000 2.6520 0.000000 164.24 0.0000 1.0000 0.0000 1.000 0.0000
STORAGE_FLR_1 VAV WITH REHEAT 0.000000 2.0400 0.000610 94.76 0.0000 1.0000 0.0000 1.000 0.0000
LAUNDRY_FLR_1 VAV WITH REHEAT 0.000000 8.4000 0.000000 78.04 0.0000 1.0000 0.0000 1.000 0.0000
CAFE_FLR_1 VAV WITH REHEAT 0.000000 142.3000 0.003581 188.86 0.0000 1.0000 0.0000 1.000 0.0000
LOBBY_FLR_1 VAV WITH REHEAT 0.000000 422.4350 0.001448 1308.19 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_1_FLR_3 FLR_3_DOAS 0.000000 6.0000 0.000396 156.09 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_2_FLR_3 FLR_3_DOAS 0.000000 6.0000 0.000396 156.07 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_3_MULT19_FLR_3 FLR_3_DOAS 0.000000 114.0000 0.000449 1863.81 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_4_MULT19_FLR_3 FLR_3_DOAS 0.000000 114.0000 0.000449 1864.32 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_5_FLR_3 FLR_3_DOAS 0.000000 6.0000 0.000396 156.09 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_6_FLR_3 FLR_3_DOAS 0.000000 6.0000 0.000396 156.07 0.0000 1.0000 0.0000 1.000 0.0000
CORRIDOR_FLR_3 VAV WITH REHEAT 0.000000 83.8280 0.000305 1557.62 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_1_FLR_6 FLR_3_DOAS 0.000000 1.5000 0.000396 39.02 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_2_FLR_6 FLR_3_DOAS 0.000000 1.5000 0.000396 39.02 0.0000 1.0000 0.0000 1.000 0.0000
ROOM_3_MULT9_FLR_6 FLR_3_DOAS 0.000000 13.5000 0.000449 220.77 0.0000 1.0000 0.0000 1.000 0.0000
BANQUET_FLR_6 VAV WITH REHEAT 0.000000 249.8960 0.003581 331.66 0.0000 1.0000 0.0000 1.000 0.0000
DINING_FLR_6 VAV WITH REHEAT 0.000000 249.8960 0.003581 331.66 0.0000 1.0000 0.0000 1.000 0.0000
KITCHEN_FLR_6 VAV WITH REHEAT 0.000000 22.2380 0.003556 103.30 0.0000 1.0000 0.0000 1.000 0.0000
CORRIDOR_FLR_6 VAV WITH REHEAT 0.000000 22.1800 0.000305 412.12 0.0000 1.0000 0.0000 1.000 0.0000


System Ventilation Parameters

People Outdoor Air Rate - Rp [m3/s-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [m3/s-m2] Sum of Zone Floor Area - Az-sum [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Outdoor Airflow - Voz-htg [m3/s]
VAV WITH REHEAT   0.00 0.001045 6694.0231 0.0000 0.0000 0.0000
FLR_3_DOAS   0.00 0.000441 4651.2638 0.0000 0.0000 0.0000


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
BASEMENT VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.6616 2.6616 2.6483 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
RETAIL_1_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.2936 0.2936 0.2922 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
RETAIL_2_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.2422 0.2422 0.2410 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
MECH_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.2615 0.2615 0.2601 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
STORAGE_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1305 0.1305 0.1299 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LAUNDRY_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 3.2667 3.2667 3.2503 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CAFE_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.3095 1.3095 1.3030 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LOBBY_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 4.5583 4.5583 4.5355 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_1_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_2_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_3_MULT19_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.8371 0.8371 0.8371 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_4_MULT19_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.8373 0.8373 0.8373 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_5_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_6_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORRIDOR_FLR_3 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.1009 1.1009 1.0954 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_1_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0154 0.0154 0.0154 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_2_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0154 0.0154 0.0154 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_3_MULT9_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0992 0.0992 0.0992 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
BANQUET_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.2369 2.2369 2.2257 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DINING_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.3472 2.3472 2.3355 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
KITCHEN_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.2519 2.2519 2.2406 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORRIDOR_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.6633 0.6633 0.6600 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Zone Ventilation Efficiency - Evz-min
VAV WITH REHEAT 21.3242 21.2175 21.3242 21.2175 0.0000 1.0000
FLR_3_DOAS 2.0513 2.0513 2.0513 2.0513 0.0000 1.0000


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Heating - Voz-htg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
BASEMENT VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.6483 2.6483 2.6483 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
RETAIL_1_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.2922 0.2922 0.2922 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
RETAIL_2_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.2410 0.2410 0.2410 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
MECH_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.2601 0.2601 0.2601 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
STORAGE_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.1299 0.1299 0.1299 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LAUNDRY_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 3.2503 3.2503 3.2503 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CAFE_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.3030 1.3030 1.3030 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LOBBY_FLR_1 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 4.5355 4.5355 4.5355 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_1_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_2_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_3_MULT19_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.8371 0.8371 0.8371 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_4_MULT19_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.8373 0.8373 0.8373 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_5_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_6_FLR_3 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0617 0.0617 0.0617 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORRIDOR_FLR_3 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.0954 1.0954 1.0954 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_1_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0154 0.0154 0.0154 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_2_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0154 0.0154 0.0154 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
ROOM_3_MULT9_FLR_6 FLR_3_DOAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.0992 0.0992 0.0992 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
BANQUET_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.2257 2.2257 2.2257 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DINING_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.3355 2.3355 2.3355 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
KITCHEN_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.2406 2.2406 2.2406 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORRIDOR_FLR_6 VAV WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.6600 0.6600 0.6600 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Zone Ventilation Efficiency - Evz-min
VAV WITH REHEAT 21.2175 21.2175 21.2175 21.2175 0.0000 1.0000
FLR_3_DOAS 2.0513 2.0513 2.0513 2.0513 0.0000 1.0000



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2023-10-16 08:58:20

Sec1.1A-General Information

Data
Weather File RUNPERIOD 1 ** Miami Intl Ap FL USA TMY3 WMO#=722020
Total gross floor area [m2] 11345.29
Principal Heating Source Natural Gas


EAp2-1. Space Usage Type

Space Area [m2] Regularly Occupied Area [m2] Unconditioned Area [m2] Typical Hours/Week in Operation [hr/wk]
BASEMENT 1978.83 1978.83 0.00 168.00
RETAIL_1_FLR_1 67.07 67.07 0.00 168.00
RETAIL_2_FLR_1 77.67 77.67 0.00 168.00
MECH_FLR_1 164.24 164.24 0.00 168.00
STORAGE_FLR_1 94.76 94.76 0.00 168.00
LAUNDRY_FLR_1 78.04 78.04 0.00 168.00
CAFE_FLR_1 188.86 188.86 0.00 168.00
LOBBY_FLR_1 1308.19 1308.19 0.00 168.00
ROOM_1_FLR_3 39.02 39.02 0.00 168.00
ROOM_2_FLR_3 39.02 39.02 0.00 168.00
ROOM_3_MULT19_FLR_3 24.52 24.52 0.00 0.00
ROOM_4_MULT19_FLR_3 24.53 24.53 0.00 168.00
ROOM_5_FLR_3 39.02 39.02 0.00 168.00
ROOM_6_FLR_3 39.02 39.02 0.00 168.00
CORRIDOR_FLR_3 389.40 389.40 0.00 168.00
ROOM_1_FLR_6 39.02 39.02 0.00 168.00
ROOM_2_FLR_6 39.02 39.02 0.00 168.00
ROOM_3_MULT9_FLR_6 24.53 24.53 0.00 168.00
BANQUET_FLR_6 331.66 331.66 0.00 168.00
DINING_FLR_6 331.66 331.66 0.00 168.00
KITCHEN_FLR_6 103.30 103.30 0.00 168.00
CORRIDOR_FLR_6 412.12 412.12 0.00 168.00
Totals 11345.29 11345.29 0.00  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 0.00
Number of hours cooling loads not met 45.33
Number of hours not met 45.33


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electricity Energy Use [GJ] Electricity Demand [W] Natural Gas Energy Use [GJ] Natural Gas Demand [W] Gasoline Use [GJ] Gasoline Demand [W] Diesel Use [GJ] Diesel Demand [W] Coal Use [GJ] Coal Demand [W] Fuel Oil No 1 Use [GJ] Fuel Oil No 1 Demand [W] Fuel Oil No 2 Use [GJ] Fuel Oil No 2 Demand [W] Propane Use [GJ] Propane Demand [W] Other Fuel 1 Use [GJ] Other Fuel 1 Demand [W] Other Fuel 2 Use [GJ] Other Fuel 2 Demand [W] District Cooling Use [GJ] District Cooling Demand [W] District Heating Use [GJ] District Heating Demand [W]
Heating -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heating -- Boiler 0.00 0.00 468.86 98398.35 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heating -- Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling -- General 5293.72 317380.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting -- LightsWired 1174.11 93091.76 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting -- General 262.62 16690.39 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- MiscPlug 959.56 59492.27 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- Cooking 762.04 29240.64 1198.64 74976.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- ReachInFreezer 16.27 515.92 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- ReachInRefrigerator 13.43 425.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- Laundry 0.00 0.00 590.20 39726.58 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- Transformer 32.92 1912.91 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- ElevatorLift 616.11 37691.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- ElevatorLightsFan 30.65 972.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- General 1826.65 74877.68 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps -- General 459.98 16829.26 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery -- General 520.33 16791.79 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- Water Heater 90.77 4739.42 2623.98 222392.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- General 18.27 2271.91 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- LowTempRefrigeration 22.65 1889.43 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- MedTempRefrigeration 34.87 1202.21 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


EAp2-6. Energy Use Summary

Process Subtotal [GJ] Total Energy Use [GJ]
Electricity 1827.09 12134.96
Natural Gas 1788.84 4881.68
Additional 0.00 0.00
Total 3615.93 17016.64


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [GJ]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [MJ/m2]
Interior Lighting (All) 103.49
Space Heating 0.00
Space Cooling 466.60
Fans (All) 161.00
Service Water Heating 8.00
Receptacle Equipment 154.36
Miscellaneous (All) 1069.60
Subtotal 1069.60


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [MJ/m2]
Space Heating 41.33
Service Water Heating 231.28
Miscellaneous (All) 430.28
Subtotal 430.28


EAp2-17c. Energy Use Intensity - Additional

Additional [MJ/m2]
Subtotal 0.00
Miscellaneous 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting (All) 6.90
Space Heating 2.76
Space Cooling 31.11
Fans (All) 10.73
Service Water Heating 15.95
Receptacle Equipment 20.80
Miscellaneous 11.74


Schedules-Equivalent Full Load Hours (Schedule Type=Fraction)

Equivalent Full Load Hours of Operation Per Year [hr] Hours > 1% [hr]
LTG_SCH_KITCHEN 3061. 8760.
LTG_SCH_DINING 3061. 8760.
LTG_SCH_BASEMENT 2655. 8760.
LTG_SCH_LOBBY 3061. 8760.
LTG_SCH_STORAGE 1339. 8760.
LTG_SCH_MECHANIC 3061. 8760.
LTG_SCH_LAUNDRY 2678. 8760.
LTG_SCH_GUESTROOM 3599. 8760.
LTG_SCH_CORRIDOR 3061. 8760.
LTG_SCH_RETAIL 2678. 8760.
WALKIN_OCC_LGHT_SCH_1 3061. 8760.
EXTERIOR_LTG_SCH 4380. 4380.
BASEMENT_EQUIP_SCH 3924. 8760.
BLDG_EQUIP_SCH 3924. 8760.
GUESTROOM_EQP_SCH_BASE 3239. 8760.
GUESTROOM_EQP_SCH_ADVA 2762. 8760.
LOBBY_EQP_SCH 3292. 8760.
OFFICE_EQP_SCH 4941. 8760.
EMPLOYEELOUNGE_EQP_SCH 4044. 8760.
LAUNDRYROOM_EQP_ELEC_SCH 2920. 2920.
LAUNDRYROOM_EQP_GAS_SCH 2920. 2920.
MEETINGROOM_EQP_SCH 1336. 4745.
EXERCISEROOM_EQP_SCH 3832. 5840.
KITCHEN_ELEC_EQUIP_SCH 2172. 8760.
KITCHEN_GAS_EQUIP_SCH 1332. 8760.
KITCHEN_EXHAUST_SCH 6205. 6205.
BLDG_ELEVATORS 2270. 8760.
ELEV_LIGHT_FAN_SCH_24_7 8760. 8760.
ELEV_LIGHT_FAN_SCH_ADD_DF 2154. 8760.
BLDG_OCC_SCH 5026. 8760.
GUESTROOM_OCC_SCH 5515. 8760.
LOBBY_OCC_SCH 2304. 8760.
OFFICE_OCC_SCH 3954. 8760.
EMPLOYEELOUNGE_OCC_SCH 948. 5475.
MEETINGROOM_OCC_SCH 1168. 4745.
LAUNDRYROOM_OCC_SCH 427. 2920.
EXERCISEROOM_OCC_SCH 5292. 5840.
INFIL_SCH 8760. 8760.
INFIL_HALF_ON_SCH 4380. 8760.
INFIL_QUARTER_ON_SCH 2190. 8760.
LAUNDRY_SWH_SCH 2555. 2555.
BLDG_SWH_SCH 3301. 8760.
GUESTROOM_SWH_SCH 2899. 8760.
LAUNDRYROOM_SWH_SCH 2920. 2920.
EXTERIOR_LGT_ALWAYS_ON 8760. 8760.
ALWAYS_ON 8760. 8760.
ALWAYS_OFF 0. 0.
FAN_SCH 8760. 8760.
REHEATCOILAVAILSCHED 8760. 8760.
COOLINGCOILAVAILSCHED 8760. 8760.
OCC_GUESTROOM_VENT_CTRL_30MIN 6570. 6570.
OCC_GUESTROOM_VENT_CTRL_20MIN 6327. 6327.
VAC_GUESTROOM_VENTILATION_SCHEDULE 365. 365.
MINOA_MOTORIZEDDAMPER_SCHED 8760. 8760.
MINOA_SCHED 8760. 8760.
WORK_EFF_SCH 0. 0.
ROOM_1_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_1_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_2_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_2_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_5_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_5_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_6_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_6_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_1_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_1_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_2_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_2_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
KITCHEN_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
KITCHEN_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
KITCHEN_FLR_6_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED 2774. 8760.
FLR_3_DOAS_OAMINOAFRACSCHEDULE 8760. 8760.
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE 0. 0.
LAUNDRY_FLR_1 EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE 0. 0.
SLIDING_DOORS_VENTILATION_AVAILABILITY_SCH 3285. 3285.


Schedules-SetPoints (Schedule Type=Temperature)

First Object Used Month Assumed 11am First Wednesday [C] Days with Same 11am Value 11pm First Wednesday [C] Days with Same 11pm Value
VACGUESTROOM_HTGSP_SCH VACGUESTROOM THERMOSTAT DUAL SP CONTROL January 18.89 365 18.89 365
VACGUESTROOM_CLGSP_SCH VACGUESTROOM THERMOSTAT DUAL SP CONTROL July 23.33 365 23.33 365
OBCRESET_S_OCCGUESTROOM_HTGSP_SCH_30MIN S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL January 21.11 365 21.11 365
OBCRESET_S_OCCGUESTROOM_CLGSP_SCH_30MIN S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL July 23.33 365 21.11 365
OBCRESET_N_OCCGUESTROOM_HTGSP_SCH_30MIN N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL January 21.11 365 21.11 365
OBCRESET_N_OCCGUESTROOM_CLGSP_SCH_30MIN N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL July 23.33 365 21.11 365
HTGSETP_SCH BASEMENT DUAL SP CONTROL January 21.00 365 21.00 365
CLGSETP_SCH BASEMENT DUAL SP CONTROL July 24.00 365 24.00 365



Table of Contents

Report: Annual Thermal Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 08:58:20

Heat Index Hours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
BASEMENT 8760.00 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 8760.00 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 8760.00 0.00 0.00 0.00 0.00
MECH_FLR_1 8760.00 0.00 0.00 0.00 0.00
STORAGE_FLR_1 8760.00 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 8760.00 0.00 0.00 0.00 0.00
CAFE_FLR_1 8760.00 0.00 0.00 0.00 0.00
LOBBY_FLR_1 8760.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_5_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_6_FLR_3 8760.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 8760.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_6 8760.00 0.00 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 8760.00 0.00 0.00 0.00 0.00
BANQUET_FLR_6 8760.00 0.00 0.00 0.00 0.00
DINING_FLR_6 8760.00 0.00 0.00 0.00 0.00
KITCHEN_FLR_6 8760.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6 8760.00 0.00 0.00 0.00 0.00
Min 8760.00 0.00 0.00 0.00 0.00
Max 8760.00 0.00 0.00 0.00 0.00
Average 8760.00 0.00 0.00 0.00 0.00
Sum 192720.00 0.00 0.00 0.00 0.00


Heat Index OccupantHours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
BASEMENT 529331.00 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 50179.00 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 59156.00 0.00 0.00 0.00 0.00
MECH_FLR_1 8977.00 0.00 0.00 0.00 0.00
STORAGE_FLR_1 5588.00 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 37203.00 0.00 0.00 0.00 0.00
CAFE_FLR_1 710417.00 0.00 0.00 0.00 0.00
LOBBY_FLR_1 2115429.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 0.00 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_5_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_6_FLR_3 4154.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3 100358.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 4154.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_6 4154.00 0.00 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 4154.00 0.00 0.00 0.00 0.00
BANQUET_FLR_6 1245715.00 0.00 0.00 0.00 0.00
DINING_FLR_6 1245715.00 0.00 0.00 0.00 0.00
KITCHEN_FLR_6 108269.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6 105946.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 2115429.00 0.00 0.00 0.00 0.00
Average 288887.05 0.00 0.00 0.00 0.00
Sum 6355515.00 0.00 0.00 0.00 0.00


Humidex Hours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
BASEMENT 8760.00 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 8760.00 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 8760.00 0.00 0.00 0.00 0.00
MECH_FLR_1 8760.00 0.00 0.00 0.00 0.00
STORAGE_FLR_1 8760.00 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 8760.00 0.00 0.00 0.00 0.00
CAFE_FLR_1 8760.00 0.00 0.00 0.00 0.00
LOBBY_FLR_1 8760.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_3 8755.50 4.50 0.00 0.00 0.00
ROOM_2_FLR_3 8755.33 4.67 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 8740.83 19.17 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 8757.67 2.33 0.00 0.00 0.00
ROOM_5_FLR_3 8755.83 4.17 0.00 0.00 0.00
ROOM_6_FLR_3 8754.00 6.00 0.00 0.00 0.00
CORRIDOR_FLR_3 8760.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 8751.17 8.83 0.00 0.00 0.00
ROOM_2_FLR_6 8752.33 7.67 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 8751.50 8.50 0.00 0.00 0.00
BANQUET_FLR_6 8760.00 0.00 0.00 0.00 0.00
DINING_FLR_6 8760.00 0.00 0.00 0.00 0.00
KITCHEN_FLR_6 8760.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6 8760.00 0.00 0.00 0.00 0.00
Min 8740.83 0.00 0.00 0.00 0.00
Max 8760.00 19.17 0.00 0.00 0.00
Average 8757.01 2.99 0.00 0.00 0.00
Sum 192654.17 65.83 0.00 0.00 0.00


Humidex OccupantHours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
BASEMENT 529331.00 0.00 0.00 0.00 0.00
RETAIL_1_FLR_1 50179.00 0.00 0.00 0.00 0.00
RETAIL_2_FLR_1 59156.00 0.00 0.00 0.00 0.00
MECH_FLR_1 8977.00 0.00 0.00 0.00 0.00
STORAGE_FLR_1 5588.00 0.00 0.00 0.00 0.00
LAUNDRY_FLR_1 37203.00 0.00 0.00 0.00 0.00
CAFE_FLR_1 710417.00 0.00 0.00 0.00 0.00
LOBBY_FLR_1 2115429.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_3_MULT19_FLR_3 0.00 0.00 0.00 0.00 0.00
ROOM_4_MULT19_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_5_FLR_3 4154.00 0.00 0.00 0.00 0.00
ROOM_6_FLR_3 4154.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_3 100358.00 0.00 0.00 0.00 0.00
ROOM_1_FLR_6 4154.00 0.00 0.00 0.00 0.00
ROOM_2_FLR_6 4154.00 0.00 0.00 0.00 0.00
ROOM_3_MULT9_FLR_6 4154.00 0.00 0.00 0.00 0.00
BANQUET_FLR_6 1245715.00 0.00 0.00 0.00 0.00
DINING_FLR_6 1245715.00 0.00 0.00 0.00 0.00
KITCHEN_FLR_6 108269.00 0.00 0.00 0.00 0.00
CORRIDOR_FLR_6 105946.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 2115429.00 0.00 0.00 0.00 0.00
Average 288887.05 0.00 0.00 0.00 0.00
Sum 6355515.00 0.00 0.00 0.00 0.00


Heating SET Hours

SET ≤ 12.2°C Hours (°C) SET ≤ 12.2°C OccupantHours (°C) Longest SET ≤ 12.2°C Duration [hr] Start Time of the Longest SET ≤ 12.2°C Duration
None        


Cooling SET Hours

SET > 30°C Hours (°C) SET > 30°C OccupantHours (°C) Longest SET > 30°C Duration [hr] Start Time of the Longest SET > 30°C Duration
None        



Table of Contents

Report: Annual CO2 Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 08:58:20

CO2 Level Hours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      


CO2 Level OccupantHours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      



Table of Contents

Report: Annual Visual Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 08:58:20

Illuminance Level Hours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
None        


Illuminance Level OccupantHours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
None        



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR

For: Environment

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.420
February 20.868
March 21.567
April 24.112
May 26.413
June 27.683
July 28.127
August 27.974
September 27.493
October 26.347
November 23.587
December 20.295
   
Annual Sum or Average 24.507
Minimum of Months 19.420
Maximum of Months 28.127



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC

For: Environment

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.420
February 20.868
March 21.567
April 24.112
May 26.413
June 27.683
July 28.127
August 27.974
September 27.493
October 26.347
November 23.587
December 20.295
   
Annual Sum or Average 24.507
Minimum of Months 19.420
Maximum of Months 28.127



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2012

For: Environment

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.420
February 20.868
March 21.567
April 24.112
May 26.413
June 27.683
July 28.127
August 27.974
September 27.493
October 26.347
November 23.587
December 20.295
   
Annual Sum or Average 24.507
Minimum of Months 19.420
Maximum of Months 28.127



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

For: Environment

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.420
February 20.868
March 21.567
April 24.112
May 26.413
June 27.683
July 28.127
August 27.974
September 27.493
October 26.347
November 23.587
December 20.295
   
Annual Sum or Average 24.507
Minimum of Months 19.420
Maximum of Months 28.127



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE

For: Environment

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.420
February 20.868
March 21.567
April 24.112
May 26.413
June 27.683
July 28.127
August 27.974
September 27.493
October 26.347
November 23.587
December 20.295
   
Annual Sum or Average 24.507
Minimum of Months 19.420
Maximum of Months 28.127



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

For: Environment

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.420
February 20.868
March 21.567
April 24.112
May 26.413
June 27.683
July 28.127
August 27.974
September 27.493
October 26.347
November 23.587
December 20.295
   
Annual Sum or Average 24.507
Minimum of Months 19.420
Maximum of Months 28.127



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

For: Environment

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.420
February 20.868
March 21.567
April 24.112
May 26.413
June 27.683
July 28.127
August 27.974
September 27.493
October 26.347
November 23.587
December 20.295
   
Annual Sum or Average 24.507
Minimum of Months 19.420
Maximum of Months 28.127



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 1A

For: Environment

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.420
February 20.868
March 21.567
April 24.112
May 26.413
June 27.683
July 28.127
August 27.974
September 27.493
October 26.347
November 23.587
December 20.295
   
Annual Sum or Average 24.507
Minimum of Months 19.420
Maximum of Months 28.127



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_FL_MIAMI

For: Environment

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.420
February 20.868
March 21.567
April 24.112
May 26.413
June 27.683
July 28.127
August 27.974
September 27.493
October 26.347
November 23.587
December 20.295
   
Annual Sum or Average 24.507
Minimum of Months 19.420
Maximum of Months 28.127



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.498403E+11 23633.95 02-JAN-19:10 23.12 19.93 0.629840E+10 3908.60 25-JAN-22:10 12.70 7.25
February 0.428330E+11 23184.38 16-FEB-19:10 23.30 19.57 0.562558E+10 3865.58 03-FEB-22:10 23.30 19.57
March 0.441770E+11 22983.63 29-MAR-18:20 24.80 20.45 0.618361E+10 3800.09 01-MAR-22:10 24.80 20.45
April 0.418398E+11 23124.45 17-APR-19:10 26.83 19.37 0.594681E+10 3759.50 18-APR-22:10 17.62 12.99
May 0.448601E+11 23528.64 31-MAY-18:50 28.30 23.96 0.616105E+10 3782.77 26-MAY-22:10 28.30 23.96
June 0.444324E+11 23968.66 28-JUN-18:40 29.60 24.32 0.598174E+10 3794.14 30-JUN-22:10 27.45 24.25
July 0.483791E+11 24888.51 27-JUL-18:20 31.47 25.80 0.620443E+10 3842.11 14-JUL-22:10 31.47 25.80
August 0.507111E+11 25278.77 02-AUG-18:10 29.90 24.73 0.630418E+10 3887.58 25-AUG-22:10 27.12 24.38
September 0.504234E+11 25208.46 18-SEP-18:10 30.40 25.93 0.611735E+10 3913.45 22-SEP-22:10 28.30 25.74
October 0.523900E+11 24955.82 05-OCT-18:10 28.80 23.33 0.634038E+10 3927.67 26-OCT-22:10 24.32 22.01
November 0.503752E+11 24478.59 02-NOV-18:10 27.12 22.55 0.614105E+10 3925.62 10-NOV-23:10 22.52 20.48
December 0.511901E+11 23944.13 07-DEC-19:10 24.40 22.49 0.634187E+10 3947.76 15-DEC-22:10 13.72 11.89
                     
Annual Sum or Average 0.571451E+12         0.736465E+11        
Minimum of Months 0.418398E+11 22983.63   23.12 19.37 0.562558E+10 3759.50   12.70 7.25
Maximum of Months 0.523900E+11 25278.77   31.47 25.93 0.634187E+10 3947.76   31.47 25.80



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.465022E+10 3333.07 02-JAN-11:35 26.83 20.59 0.631628E+09 403.38 13-JAN-22:19 24.23 21.06
February 0.442074E+10 3216.88 11-FEB-11:35 27.60 23.74 0.571351E+09 390.08 09-FEB-22:30 27.60 23.74
March 0.491198E+10 3150.94 04-MAR-11:35 27.03 22.82 0.632089E+09 396.24 27-MAR-21:40 24.60 21.74
April 0.513727E+10 2974.02 15-APR-10:35 29.27 22.89 0.611457E+09 404.49 14-APR-21:40 29.27 22.89
May 0.563935E+10 2886.25 22-MAY-18:10 30.40 23.74 0.634265E+09 404.85 22-MAY-21:49 27.30 22.27
June 0.571467E+10 2975.80 11-JUN-10:35 30.93 23.60 0.621781E+09 412.31 09-JUN-21:00 30.93 23.60
July 0.612211E+10 3123.47 29-JUL-17:13 34.03 24.14 0.645286E+09 417.83 28-JUL-22:10 34.03 24.14
August 0.599419E+10 3099.79 19-AUG-10:35 31.50 24.70 0.649100E+09 414.51 18-AUG-22:10 31.50 24.70
September 0.603334E+10 3317.76 24-SEP-10:35 30.53 25.04 0.635530E+09 424.59 18-SEP-22:10 30.53 25.04
October 0.617471E+10 3354.34 07-OCT-10:35 31.13 24.14 0.654702E+09 423.35 25-OCT-21:40 26.30 21.54
November 0.539105E+10 3526.28 08-NOV-11:35 27.43 21.48 0.621765E+09 415.70 07-NOV-22:40 27.43 21.48
December 0.486233E+10 3453.80 09-DEC-11:35 27.20 22.50 0.634856E+09 406.20 08-DEC-22:30 27.20 22.50
                     
Annual Sum or Average 0.650520E+11         0.754381E+10        
Minimum of Months 0.442074E+10 2886.25   26.83 20.59 0.571351E+09 390.08   24.23 21.06
Maximum of Months 0.617471E+10 3526.28   34.03 25.04 0.654702E+09 424.59   34.03 25.04



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.391328E+10 2132.50 02-JAN-19:10 23.12 19.93 0.727771E+09 467.90 13-JAN-23:10 23.90 21.21
February 0.366768E+10 2137.29 11-FEB-19:10 23.40 21.47 0.660678E+09 465.09 17-FEB-23:10 23.90 20.81
March 0.414978E+10 2212.58 13-MAR-18:10 27.93 22.26 0.738354E+09 473.89 28-MAR-22:10 23.80 20.10
April 0.425556E+10 2292.13 17-APR-18:10 30.03 18.67 0.718394E+09 480.02 14-APR-22:10 30.03 18.67
May 0.454681E+10 2308.51 22-MAY-18:10 30.40 23.74 0.747904E+09 480.90 19-MAY-22:10 30.40 23.74
June 0.450905E+10 2348.05 29-JUN-18:10 30.00 24.76 0.729377E+09 485.74 09-JUN-22:10 30.00 24.76
July 0.478124E+10 2384.21 27-JUL-18:10 31.83 25.86 0.753543E+09 486.98 28-JUL-22:10 28.80 24.46
August 0.468423E+10 2342.66 17-AUG-18:10 29.82 24.66 0.754922E+09 484.23 17-AUG-22:10 27.88 24.83
September 0.460184E+10 2335.10 18-SEP-18:10 30.40 25.93 0.729311E+09 485.87 01-SEP-22:10 30.40 25.93
October 0.464700E+10 2279.37 05-OCT-18:10 28.80 23.33 0.748292E+09 483.72 06-OCT-22:10 26.70 23.84
November 0.421658E+10 2215.54 08-NOV-19:10 26.10 22.26 0.714246E+09 476.59 07-NOV-23:10 26.10 22.26
December 0.404951E+10 2147.11 09-DEC-19:10 25.00 22.31 0.730839E+09 473.10 08-DEC-23:10 25.00 22.31
                     
Annual Sum or Average 0.520225E+11         0.875363E+10        
Minimum of Months 0.366768E+10 2132.50   23.12 18.67 0.660678E+09 465.09   23.80 18.67
Maximum of Months 0.478124E+10 2384.21   31.83 25.93 0.754922E+09 486.98   30.40 25.93



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.331704E+10 2168.46 02-JAN-19:50 22.38 19.69 0.152011E+09 93.47 06-JAN-22:10 24.32 22.14
February 0.326363E+10 2188.34 16-FEB-19:15 23.30 19.57 0.137696E+09 94.12 17-FEB-22:10 23.90 20.81
March 0.381026E+10 2289.15 27-MAR-18:20 25.60 21.37 0.153267E+09 94.44 28-MAR-21:10 24.32 20.85
April 0.422360E+10 2444.62 17-APR-18:10 30.03 18.67 0.148487E+09 96.10 14-APR-22:10 30.03 18.67
May 0.489178E+10 2487.61 22-MAY-18:10 30.40 23.74 0.155198E+09 97.45 31-MAY-22:10 26.98 24.25
June 0.504815E+10 2586.85 11-JUN-10:35 30.93 23.60 0.152498E+09 99.15 29-JUN-22:10 28.90 24.77
July 0.532645E+10 2616.72 29-JUL-10:35 32.07 25.98 0.157501E+09 99.51 28-JUL-22:10 32.07 25.98
August 0.507500E+10 2567.04 20-AUG-10:35 31.13 25.97 0.156758E+09 98.73 18-AUG-22:10 31.13 25.97
September 0.495291E+10 2494.10 18-SEP-18:10 30.40 25.93 0.151244E+09 98.62 22-SEP-22:10 28.30 25.74
October 0.478395E+10 2418.43 05-OCT-18:10 28.80 23.33 0.154275E+09 96.86 03-OCT-22:10 28.80 23.33
November 0.411157E+10 2328.93 22-NOV-19:03 26.70 23.84 0.148110E+09 95.70 03-NOV-22:10 26.70 23.84
December 0.358878E+10 2239.14 07-DEC-19:20 24.40 22.49 0.152243E+09 94.46 08-DEC-22:10 23.98 22.48
                     
Annual Sum or Average 0.523931E+11         0.181929E+10        
Minimum of Months 0.326363E+10 2168.46   22.38 18.67 0.137696E+09 93.47   23.90 18.67
Maximum of Months 0.532645E+10 2616.72   32.07 25.98 0.157501E+09 99.51   32.07 25.98



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.143313E+10 983.57 13-JAN-21:00 24.40 20.99 0.116715E+09 69.76 13-JAN-23:10 23.90 21.21
February 0.145571E+10 991.37 17-FEB-20:20 23.90 20.81 0.105543E+09 70.20 17-FEB-23:10 23.90 20.81
March 0.172626E+10 1037.18 30-MAR-20:00 23.90 19.84 0.117365E+09 70.41 28-MAR-22:10 23.90 19.84
April 0.199076E+10 1112.03 17-APR-19:10 26.83 19.37 0.113442E+09 71.64 14-APR-22:10 26.83 19.37
May 0.237734E+10 1189.99 31-MAY-18:15 28.30 23.96 0.118247E+09 72.60 31-MAY-22:10 26.98 24.25
June 0.248039E+10 1293.28 11-JUN-10:35 30.93 23.60 0.116092E+09 73.90 29-JUN-22:10 28.90 24.77
July 0.262775E+10 1313.92 29-JUL-10:35 32.07 25.98 0.119843E+09 74.18 28-JUL-22:10 32.07 25.98
August 0.248858E+10 1294.34 19-AUG-10:35 31.50 24.70 0.119479E+09 73.66 18-AUG-22:10 31.50 24.70
September 0.243129E+10 1282.11 24-SEP-10:35 30.53 25.04 0.115218E+09 73.68 22-SEP-22:10 30.53 25.04
October 0.232443E+10 1134.02 05-OCT-19:10 28.22 23.14 0.117661E+09 72.36 03-OCT-22:10 28.22 23.14
November 0.192942E+10 1079.02 22-NOV-21:00 26.70 23.84 0.113226E+09 71.57 03-NOV-22:10 26.70 23.84
December 0.159335E+10 1022.97 07-DEC-21:00 23.90 22.40 0.116766E+09 70.57 08-DEC-23:10 24.50 22.98
                     
Annual Sum or Average 0.248584E+11         0.138960E+10        
Minimum of Months 0.143313E+10 983.57   23.90 19.37 0.105543E+09 69.76   23.90 19.37
Maximum of Months 0.262775E+10 1313.92   32.07 25.98 0.119843E+09 74.18   32.07 25.98



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.517195E+11 36756.05 02-JAN-21:00 22.20 19.62 0.508177E+09 382.20 10-JAN-22:10 17.62 14.98
February 0.471285E+11 36726.14 16-FEB-21:00 23.90 20.12 0.459214E+09 381.91 24-FEB-22:10 16.02 11.81
March 0.527021E+11 37145.35 27-MAR-20:00 24.40 20.99 0.510719E+09 381.90 14-MAR-21:10 24.40 20.99
April 0.517242E+11 37390.22 17-APR-20:00 25.00 18.53 0.491238E+09 381.86 18-APR-21:10 18.72 13.36
May 0.541911E+11 37723.94 31-MAY-20:00 27.80 24.12 0.507938E+09 381.80 26-MAY-21:10 27.80 24.12
June 0.530264E+11 37825.24 08-JUN-20:00 28.90 24.83 0.492281E+09 381.57 13-JUN-21:10 26.10 22.31
July 0.548645E+11 37904.85 27-JUL-20:00 28.90 25.60 0.505199E+09 381.73 14-JUL-21:10 28.90 25.60
August 0.544807E+11 37806.30 31-AUG-20:00 27.80 24.58 0.508984E+09 381.58 11-AUG-21:10 27.80 24.58
September 0.527797E+11 37764.94 21-SEP-20:00 28.90 24.82 0.490316E+09 381.77 05-SEP-21:10 28.90 24.82
October 0.539069E+11 37529.17 05-OCT-20:00 27.80 23.03 0.506842E+09 381.82 17-OCT-21:10 24.40 18.14
November 0.513508E+11 37207.32 02-NOV-20:00 26.70 22.81 0.490921E+09 381.88 14-NOV-22:10 18.30 14.23
December 0.518350E+11 36829.09 06-DEC-21:00 24.40 22.09 0.507545E+09 381.89 19-DEC-22:10 16.02 12.32
                     
Annual Sum or Average 0.629709E+12         0.597937E+10        
Minimum of Months 0.471285E+11 36726.14   22.20 18.53 0.459214E+09 381.57   16.02 11.81
Maximum of Months 0.548645E+11 37904.85   28.90 25.60 0.510719E+09 382.20   28.90 25.60



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.254724E+11 13713.20 15-JAN-11:35 24.43 17.04 0.864090E+10 5766.85 13-JAN-22:40 24.43 17.04
February 0.233515E+11 13613.36 11-FEB-11:35 27.60 23.74 0.784585E+10 5647.35 17-FEB-22:40 23.90 20.81
March 0.255453E+11 13396.57 04-MAR-11:35 27.03 22.82 0.873123E+10 5671.22 13-MAR-22:10 24.90 22.35
April 0.253636E+11 12786.19 17-APR-18:10 30.03 18.67 0.846560E+10 5710.17 14-APR-21:40 30.03 18.67
May 0.267903E+11 12842.85 22-MAY-18:10 30.40 23.74 0.883624E+10 5745.17 22-MAY-22:10 26.93 22.26
June 0.266047E+11 12992.97 29-JUN-18:10 30.00 24.76 0.866699E+10 5791.92 02-JUN-22:10 30.00 24.76
July 0.280782E+11 13326.03 27-JUL-18:10 31.83 25.86 0.891706E+10 5829.10 28-JUL-22:10 28.80 24.46
August 0.278690E+11 13004.92 02-AUG-18:10 29.90 24.73 0.899410E+10 5818.89 18-AUG-22:10 28.90 24.83
September 0.277996E+11 13867.31 24-SEP-10:35 30.53 25.04 0.874919E+10 5918.51 08-SEP-22:10 30.53 25.04
October 0.287012E+11 13955.98 07-OCT-10:35 31.13 24.14 0.904552E+10 5907.78 25-OCT-21:40 26.30 21.54
November 0.265069E+11 14288.84 08-NOV-11:35 27.43 21.48 0.859068E+10 5848.95 07-NOV-22:40 27.43 21.48
December 0.258352E+11 14446.24 09-DEC-11:35 27.20 22.50 0.869975E+10 5775.20 08-DEC-22:40 27.20 22.50
                     
Annual Sum or Average 0.317918E+12         0.104183E+12        
Minimum of Months 0.233515E+11 12786.19   24.43 17.04 0.784585E+10 5647.35   23.90 17.04
Maximum of Months 0.287012E+11 14446.24   31.83 25.86 0.904552E+10 5918.51   30.53 25.04



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.842362E+11 41098.71 02-JAN-19:10 23.12 19.93 0.253423E+11 16551.05 13-JAN-23:10 23.90 21.21
February 0.774386E+11 40953.48 11-FEB-19:10 23.40 21.47 0.230240E+11 16495.09 17-FEB-23:10 23.90 20.81
March 0.857883E+11 42336.72 13-MAR-18:10 27.93 22.26 0.257116E+11 16526.60 28-MAR-22:10 23.80 20.10
April 0.857087E+11 43779.35 17-APR-18:10 30.03 18.67 0.249775E+11 16696.58 14-APR-22:10 30.03 18.67
May 0.911861E+11 44232.74 22-MAY-18:10 30.40 23.74 0.260725E+11 16752.13 22-MAY-22:10 26.93 22.26
June 0.905825E+11 44792.13 29-JUN-18:10 30.00 24.76 0.254872E+11 16923.98 09-JUN-22:10 30.00 24.76
July 0.949746E+11 45394.92 27-JUL-18:10 31.83 25.86 0.262289E+11 16981.91 28-JUL-22:10 28.80 24.46
August 0.937925E+11 44668.12 02-AUG-18:10 29.90 24.73 0.263358E+11 16942.32 18-AUG-22:10 28.90 24.83
September 0.922545E+11 44809.15 24-SEP-10:35 30.53 25.04 0.254500E+11 17026.34 22-SEP-22:10 30.53 25.04
October 0.941099E+11 43584.88 05-OCT-18:10 28.80 23.33 0.261582E+11 16874.52 06-OCT-22:10 26.70 23.84
November 0.873549E+11 42600.44 19-NOV-11:35 26.70 21.43 0.250032E+11 16796.98 03-NOV-22:10 26.70 21.43
December 0.857761E+11 43417.94 09-DEC-11:35 27.20 22.50 0.254903E+11 16675.54 08-DEC-23:10 27.20 22.50
                     
Annual Sum or Average 0.106320E+13         0.305282E+12        
Minimum of Months 0.774386E+11 40953.48   23.12 18.67 0.230240E+11 16495.09   23.80 18.67
Maximum of Months 0.949746E+11 45394.92   31.83 25.86 0.263358E+11 17026.34   30.53 25.04



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.136024E+10 3278.88 26-JAN-16:02 20.50 11.94 98228917.33 56.70 13-JAN-22:40 20.50 11.94
February 0.149846E+10 3301.31 24-FEB-16:02 25.00 13.11 88931188.05 56.70 22-FEB-22:10 25.00 13.11
March 0.186010E+10 3235.14 15-MAR-15:01 17.30 8.90 98652830.24 56.70 31-MAR-22:10 23.05 18.37
April 0.225081E+10 3217.13 15-APR-15:02 31.20 22.93 95696040.22 56.70 15-APR-23:40 22.97 20.90
May 0.257865E+10 3220.81 16-MAY-15:02 30.40 21.78 99067533.97 56.70 19-MAY-00:10 25.50 22.72
June 0.262556E+10 3182.98 10-JUN-15:02 31.70 24.22 95937857.78 56.70 17-JUN-00:00 27.20 22.19
July 0.292568E+10 3229.87 28-JUL-15:02 35.00 25.20 99075368.67 56.70 01-JUL-23:00 35.00 25.20
August 0.280078E+10 3224.39 31-AUG-15:02 32.12 24.95 99137611.61 56.70 23-AUG-22:40 32.12 24.95
September 0.273142E+10 3230.81 17-SEP-15:02 31.10 24.65 95862788.06 56.70 01-SEP-01:39 31.10 24.65
October 0.264444E+10 3202.25 06-OCT-15:02 29.32 23.78 99044141.91 56.70 19-OCT-22:40 23.50 19.52
November 0.200445E+10 3172.94 17-NOV-16:02 29.13 21.96 95621202.72 56.70 30-NOV-22:40 25.03 22.28
December 0.155374E+10 3202.74 06-DEC-16:02 26.02 22.41 98266053.14 56.70 05-DEC-22:10 26.02 22.41
                     
Annual Sum or Average 0.268343E+11         0.116352E+10        
Minimum of Months 0.136024E+10 3172.94   17.30 8.90 88931188.05 56.70   20.50 11.94
Maximum of Months 0.292568E+10 3301.31   35.00 25.20 99137611.61 56.70   35.00 25.20



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.975476E+09 3237.51 26-JAN-16:02 20.50 11.94 97502772.93 56.69 27-JAN-22:10 19.40 15.40
February 0.120189E+10 3285.56 24-FEB-16:02 25.00 13.11 88534484.15 56.69 16-FEB-22:10 25.00 13.11
March 0.163135E+10 3216.86 15-MAR-15:01 17.30 8.90 98389943.61 56.70 30-MAR-22:10 23.80 20.03
April 0.212975E+10 3252.36 15-APR-18:02 29.82 21.94 95658846.73 56.70 04-APR-21:49 29.82 21.94
May 0.257697E+10 3248.03 20-MAY-15:02 30.00 21.38 99075954.30 56.70 17-MAY-00:40 30.00 21.38
June 0.266574E+10 3212.71 10-JUN-15:02 31.70 24.22 95956051.13 56.70 09-JUN-21:10 31.70 24.22
July 0.295135E+10 3262.61 28-JUL-15:02 35.00 25.20 99086333.07 56.70 23-JUL-00:20 35.00 25.20
August 0.274851E+10 3205.15 19-AUG-15:02 31.70 24.44 99135096.44 56.70 18-AUG-21:49 31.70 24.44
September 0.256490E+10 3195.62 30-SEP-15:02 31.10 24.59 95838733.35 56.70 17-SEP-00:10 31.10 24.59
October 0.232988E+10 3202.84 18-OCT-15:02 27.20 19.36 98969402.37 56.70 19-OCT-21:00 23.90 19.41
November 0.166439E+10 3163.54 06-NOV-16:02 27.80 20.07 95355950.37 56.70 07-NOV-22:40 24.40 22.09
December 0.118906E+10 3135.74 04-DEC-16:02 25.50 18.37 97701972.48 56.69 06-DEC-22:10 23.90 22.40
                     
Annual Sum or Average 0.246293E+11         0.116121E+10        
Minimum of Months 0.975476E+09 3135.74   17.30 8.90 88534484.15 56.69   19.40 13.11
Maximum of Months 0.295135E+10 3285.56   35.00 25.20 99135096.44 56.70   35.00 25.20



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.816848E+09 746.42 02-JAN-14:30 28.90 24.11 0.00 0.00 01-JAN-00:10 28.90 24.11
February 0.745103E+09 683.69 11-FEB-14:30 28.85 24.07 0.00 0.00 01-FEB-00:10 28.85 24.07
March 0.778612E+09 569.07 02-MAR-14:30 25.00 17.17 0.00 0.00 01-MAR-00:10 25.00 17.17
April 0.803100E+09 523.51 15-APR-19:10 28.53 21.74 0.00 0.00 01-APR-00:10 28.53 21.74
May 0.876933E+09 507.78 22-MAY-20:20 28.13 22.80 0.00 0.00 01-MAY-00:10 28.13 22.80
June 0.902508E+09 532.63 03-JUN-21:00 29.40 24.47 0.00 0.00 01-JUN-00:10 29.40 24.47
July 0.978363E+09 567.35 29-JUL-19:10 31.55 24.08 0.00 0.00 01-JUL-00:10 31.55 24.08
August 0.975711E+09 551.14 20-AUG-20:03 28.80 24.73 0.00 0.00 01-AUG-00:10 28.80 24.73
September 0.104153E+10 654.23 30-SEP-13:30 30.85 24.73 0.00 0.00 01-SEP-00:10 30.85 24.73
October 0.110823E+10 714.26 25-OCT-12:40 30.00 22.13 0.00 0.00 01-OCT-00:10 30.00 22.13
November 0.960684E+09 747.21 07-NOV-13:40 28.13 20.93 0.00 0.00 01-NOV-00:10 28.13 20.93
December 0.846727E+09 755.58 03-DEC-14:00 24.40 18.35 0.00 0.00 01-DEC-00:10 24.40 18.35
                     
Annual Sum or Average 0.108344E+11         0.00        
Minimum of Months 0.745103E+09 507.78   24.40 17.17 0.00 0.00   24.40 17.17
Maximum of Months 0.110823E+10 755.58   31.55 24.73 0.00 0.00   31.55 24.73



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.679352E+09 1129.77 16-JAN-16:02 21.60 14.75 97119184.51 56.69 18-JAN-22:40 21.87 16.72
February 0.705468E+09 1188.46 24-FEB-19:01 21.52 12.20 88050769.13 56.69 22-FEB-23:10 21.52 12.20
March 0.852104E+09 1185.13 14-MAR-18:02 24.13 14.61 97785942.90 56.69 27-MAR-21:10 24.90 21.81
April 0.984449E+09 1198.42 17-APR-18:02 30.03 18.67 95112382.92 56.69 20-APR-22:00 22.20 16.64
May 0.117084E+10 1183.38 20-MAY-18:02 28.03 21.49 98749260.58 56.70 19-MAY-22:10 28.03 21.49
June 0.122418E+10 1180.01 14-JUN-18:02 29.32 23.40 95703939.07 56.69 13-JUN-21:40 29.32 23.40
July 0.129227E+10 1188.42 29-JUL-18:02 33.12 24.14 98854370.55 56.69 05-JUL-21:40 33.12 24.14
August 0.121591E+10 1172.18 19-AUG-18:02 29.40 24.22 98815181.16 56.69 11-AUG-21:49 29.40 24.22
September 0.115722E+10 1166.52 01-SEP-18:02 29.90 23.26 95526859.49 56.70 12-SEP-21:49 26.20 23.25
October 0.108144E+10 1184.47 17-OCT-18:02 25.50 18.09 98520041.31 56.70 17-OCT-21:10 24.40 18.14
November 0.891157E+09 1177.48 20-NOV-19:02 26.02 20.73 94838313.67 56.69 20-NOV-22:10 25.60 21.07
December 0.737431E+09 1154.06 09-DEC-19:02 25.00 22.31 97287878.90 56.69 18-DEC-22:49 19.40 17.94
                     
Annual Sum or Average 0.119918E+11         0.115636E+10        
Minimum of Months 0.679352E+09 1129.77   21.52 12.20 88050769.13 56.69   19.40 12.20
Maximum of Months 0.129227E+10 1198.42   33.12 24.22 98854370.55 56.70   33.12 24.22



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.140724E+10 2952.88 26-JAN-16:02 20.50 11.94 98465061.11 56.69 02-JAN-22:40 20.50 11.94
February 0.149567E+10 2976.13 24-FEB-19:01 21.52 12.20 89133763.56 56.69 22-FEB-22:10 21.52 12.20
March 0.182545E+10 2936.42 20-MAR-15:01 19.40 10.17 98906276.48 56.69 27-MAR-22:40 24.07 21.37
April 0.222761E+10 2890.40 16-APR-15:02 31.52 21.13 95857274.53 56.70 15-APR-23:49 31.52 21.13
May 0.258183E+10 2859.58 20-MAY-15:02 30.00 21.38 99150660.22 56.69 20-MAY-00:40 30.00 21.38
June 0.275882E+10 2860.88 01-JUN-15:02 30.00 23.17 96010037.56 56.70 02-JUN-21:10 28.90 24.83
July 0.300733E+10 2948.35 29-JUL-15:02 35.10 24.20 99126592.62 56.70 25-JUL-21:10 35.10 24.20
August 0.280337E+10 2869.07 31-AUG-15:02 32.12 24.95 99182171.72 56.70 18-AUG-21:10 32.12 24.95
September 0.282276E+10 2876.42 30-SEP-15:02 31.10 24.59 95928167.56 56.70 01-SEP-21:10 31.10 24.59
October 0.267655E+10 2946.57 25-OCT-15:02 29.22 22.14 99117624.99 56.70 20-OCT-23:40 29.22 22.14
November 0.201399E+10 2861.98 14-NOV-16:02 23.30 15.73 95742746.85 56.70 01-NOV-21:49 23.30 15.73
December 0.146264E+10 2868.86 04-DEC-16:02 25.50 18.37 98315494.73 56.69 01-DEC-22:10 25.50 18.37
                     
Annual Sum or Average 0.270833E+11         0.116494E+10        
Minimum of Months 0.140724E+10 2859.58   19.40 10.17 89133763.56 56.69   20.50 11.94
Maximum of Months 0.300733E+10 2976.13   35.10 24.95 99182171.72 56.70   35.10 24.95



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.102017E+10 2758.50 15-JAN-16:02 24.72 16.69 97766699.65 56.69 13-JAN-22:10 24.72 16.69
February 0.118876E+10 2974.11 22-FEB-16:02 27.43 14.84 88825499.61 56.69 21-FEB-23:10 27.43 14.84
March 0.158922E+10 2852.41 01-MAR-16:02 24.90 15.69 98692122.20 56.70 28-MAR-21:49 23.98 20.27
April 0.210387E+10 2953.08 16-APR-15:02 31.52 21.13 95842174.65 56.70 04-APR-21:00 31.52 21.13
May 0.258000E+10 2878.67 20-MAY-08:62 27.88 22.09 99152652.54 56.70 02-MAY-22:00 27.88 22.09
June 0.279909E+10 2882.64 01-JUN-15:02 30.00 23.17 96012305.37 56.70 02-JUN-21:10 28.90 24.83
July 0.303301E+10 2976.32 29-JUL-15:02 35.10 24.20 99128216.98 56.70 25-JUL-21:10 35.10 24.20
August 0.275055E+10 2854.74 19-AUG-15:02 31.70 24.44 99180801.53 56.70 02-AUG-21:10 31.70 24.44
September 0.265398E+10 2841.01 13-SEP-15:02 31.32 24.14 95921394.42 56.70 08-SEP-21:10 31.32 24.14
October 0.235607E+10 2814.80 17-OCT-18:02 25.50 18.09 99087161.63 56.69 13-OCT-21:40 25.50 18.09
November 0.166821E+10 2817.81 14-NOV-16:02 23.30 15.73 95537683.37 56.70 20-NOV-23:10 25.60 21.12
December 0.110126E+10 2768.21 03-DEC-19:02 21.60 15.54 97668404.41 56.69 06-DEC-22:10 23.90 22.40
                     
Annual Sum or Average 0.248442E+11         0.116282E+10        
Minimum of Months 0.102017E+10 2758.50   21.60 14.84 88825499.61 56.69   23.90 14.84
Maximum of Months 0.303301E+10 2976.32   35.10 24.44 99180801.53 56.70   35.10 24.83



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.532378E+10 2793.51 01-JAN-11:35 26.30 21.34 0.124836E+10 792.64 03-JAN-22:40 21.87 20.31
February 0.490945E+10 2758.98 11-FEB-11:35 27.60 23.74 0.113924E+10 782.84 17-FEB-23:10 23.90 20.81
March 0.555903E+10 2767.13 04-MAR-11:35 27.03 22.82 0.127734E+10 793.08 30-MAR-22:10 23.80 20.03
April 0.578309E+10 2970.30 15-APR-10:35 29.27 22.89 0.126827E+10 811.40 14-APR-21:49 29.27 22.89
May 0.620770E+10 2987.72 20-MAY-10:35 29.23 21.81 0.133682E+10 818.73 22-MAY-22:10 26.93 22.26
June 0.623179E+10 3094.30 11-JUN-10:35 30.93 23.60 0.132234E+10 832.14 29-JUN-22:10 28.90 24.77
July 0.656798E+10 3152.16 30-JUL-10:35 31.83 24.36 0.137186E+10 836.84 28-JUL-22:10 31.83 24.36
August 0.644841E+10 3117.20 19-AUG-10:35 31.50 24.70 0.137082E+10 837.08 21-AUG-21:00 27.80 24.87
September 0.629199E+10 3151.62 24-SEP-10:35 30.53 25.04 0.132815E+10 843.02 22-SEP-22:10 30.53 25.04
October 0.636304E+10 3084.88 07-OCT-10:35 31.13 24.14 0.136050E+10 828.81 25-OCT-21:49 26.20 21.68
November 0.574420E+10 2887.13 08-NOV-11:35 27.43 21.48 0.126884E+10 815.29 10-NOV-22:49 22.88 20.65
December 0.541054E+10 2905.50 09-DEC-11:35 27.20 22.50 0.126232E+10 803.41 08-DEC-23:10 27.20 22.50
                     
Annual Sum or Average 0.708410E+11         0.155549E+11        
Minimum of Months 0.490945E+10 2758.98   26.30 21.34 0.113924E+10 782.84   21.87 20.03
Maximum of Months 0.656798E+10 3152.16   31.83 25.04 0.137186E+10 843.02   31.83 25.04



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.139721E+10 3486.54 26-JAN-16:02 20.50 11.94 98226706.66 56.70 13-JAN-22:30 20.50 11.94
February 0.158839E+10 3505.72 24-FEB-16:02 25.00 13.11 88928937.56 56.70 27-FEB-22:10 21.52 15.05
March 0.200279E+10 3427.73 15-MAR-15:01 17.30 8.90 98665977.45 56.70 31-MAR-21:49 23.13 18.35
April 0.247653E+10 3435.09 14-APR-15:02 30.40 24.46 95712002.00 56.70 03-APR-22:10 30.40 24.46
May 0.286444E+10 3426.50 31-MAY-15:02 30.82 24.59 99093954.33 56.70 21-MAY-00:30 30.82 24.59
June 0.292480E+10 3439.96 28-JUN-15:02 30.50 24.49 95959478.16 56.70 09-JUN-21:10 30.50 24.49
July 0.326586E+10 3442.05 20-JUL-15:02 31.10 24.66 99089524.65 56.70 28-JUL-21:10 29.32 24.20
August 0.309763E+10 3440.26 21-AUG-15:02 30.37 25.25 99153104.85 56.70 31-AUG-00:10 26.60 23.34
September 0.300094E+10 3422.14 04-SEP-15:02 30.50 24.31 95869212.91 56.70 08-SEP-21:10 29.90 24.64
October 0.285796E+10 3431.19 22-OCT-15:02 29.22 23.41 99043030.81 56.70 18-OCT-22:00 29.22 23.41
November 0.213415E+10 3433.91 07-NOV-16:02 28.22 22.20 95615559.24 56.70 10-NOV-22:49 22.88 20.65
December 0.161978E+10 3392.27 05-DEC-16:02 25.40 20.99 98245598.06 56.70 06-DEC-22:00 23.90 22.40
                     
Annual Sum or Average 0.292305E+11         0.116360E+10        
Minimum of Months 0.139721E+10 3392.27   17.30 8.90 88928937.56 56.70   20.50 11.94
Maximum of Months 0.326586E+10 3505.72   31.10 25.25 99153104.85 56.70   30.82 24.64



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.988357E+09 3430.65 26-JAN-16:02 20.50 11.94 97552894.03 56.69 18-JAN-22:10 20.50 11.94
February 0.127181E+10 3482.10 24-FEB-16:02 25.00 13.11 88580703.12 56.69 16-FEB-22:10 25.00 13.11
March 0.176023E+10 3408.01 31-MAR-15:02 25.78 18.38 98441157.90 56.70 30-MAR-21:00 25.78 18.38
April 0.235002E+10 3428.31 11-APR-15:02 28.80 22.61 95686579.17 56.70 04-APR-21:40 28.80 22.61
May 0.286340E+10 3451.97 19-MAY-18:02 28.12 22.04 99102232.11 56.70 21-MAY-00:30 25.60 22.31
June 0.296688E+10 3463.17 28-JUN-15:02 30.50 24.49 95974488.84 56.70 09-JUN-21:10 30.50 24.49
July 0.329301E+10 3509.15 28-JUL-15:02 35.00 25.20 99098634.91 56.70 28-JUL-21:10 29.32 24.20
August 0.304334E+10 3463.48 23-AUG-15:02 31.52 25.44 99152828.50 56.70 17-AUG-00:49 31.52 25.44
September 0.282680E+10 3457.13 20-SEP-15:02 31.78 24.57 95852259.17 56.70 29-SEP-23:49 28.30 23.88
October 0.252702E+10 3416.25 25-OCT-15:02 29.22 22.14 98979906.38 56.70 17-OCT-21:00 29.22 22.14
November 0.177395E+10 3392.73 07-NOV-16:02 28.22 22.20 95379558.10 56.70 22-NOV-22:30 26.40 23.42
December 0.123092E+10 3386.49 03-DEC-16:02 24.32 17.20 97704520.61 56.69 11-DEC-22:40 17.97 14.16
                     
Annual Sum or Average 0.268957E+11         0.116151E+10        
Minimum of Months 0.988357E+09 3386.49   20.50 11.94 88580703.12 56.69   17.97 11.94
Maximum of Months 0.329301E+10 3509.15   35.00 25.44 99152828.50 56.70   31.52 25.44



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.135202E+10 1728.98 26-JAN-16:02 20.50 11.94 98698776.72 56.69 03-JAN-01:19 20.50 11.94
February 0.126905E+10 1723.92 24-FEB-16:02 25.00 13.11 89218134.61 56.69 28-FEB-23:40 17.83 13.57
March 0.134918E+10 1682.95 20-MAR-15:01 19.40 10.17 98797919.30 56.70 28-MAR-21:10 24.32 20.85
April 0.143400E+10 1663.72 05-APR-15:02 26.70 20.52 95694428.74 56.70 11-APR-21:10 25.00 22.01
May 0.158772E+10 1641.30 01-MAY-15:02 29.90 20.98 99056557.51 56.70 04-MAY-21:10 25.60 21.81
June 0.165597E+10 1637.15 01-JUN-15:02 30.00 23.17 95926015.35 56.70 14-JUN-21:40 28.30 23.17
July 0.180624E+10 1678.76 28-JUL-15:02 35.00 25.20 99059943.88 56.70 07-JUL-21:40 35.00 25.20
August 0.177673E+10 1669.98 31-AUG-15:02 32.12 24.95 99127961.80 56.70 30-AUG-21:00 32.12 24.95
September 0.187821E+10 1676.67 16-SEP-15:02 30.60 24.39 95897316.14 56.70 26-SEP-22:10 26.73 22.71
October 0.195292E+10 1679.17 25-OCT-15:02 29.22 22.14 99139457.05 56.70 17-OCT-21:49 29.22 22.14
November 0.165249E+10 1668.47 07-NOV-16:02 28.22 22.20 95828440.14 56.70 20-NOV-22:49 25.60 21.07
December 0.142198E+10 1694.08 03-DEC-16:02 24.32 17.20 98665182.30 56.70 08-DEC-22:40 24.23 22.72
                     
Annual Sum or Average 0.191365E+11         0.116511E+10        
Minimum of Months 0.126905E+10 1637.15   19.40 10.17 89218134.61 56.69   17.83 11.94
Maximum of Months 0.195292E+10 1728.98   35.00 25.20 99139457.05 56.70   35.00 25.20



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.445881E+11 20835.59 13-JAN-23:40 23.90 21.21 0.156225E+11 10438.06 13-JAN-23:10 23.90 21.21
February 0.412756E+11 20990.78 17-FEB-23:40 23.90 20.81 0.142325E+11 10488.30 17-FEB-23:10 23.90 20.81
March 0.465429E+11 21830.87 13-MAR-18:10 27.93 22.26 0.159537E+11 10515.07 28-MAR-22:10 23.80 20.10
April 0.469454E+11 22828.63 17-APR-18:10 30.03 18.67 0.155567E+11 10651.27 14-APR-22:10 30.03 18.67
May 0.501634E+11 23192.50 22-MAY-18:10 30.40 23.74 0.163218E+11 10767.14 22-MAY-22:10 26.93 22.26
June 0.496950E+11 23582.88 29-JUN-18:10 30.00 24.76 0.159858E+11 10872.90 09-JUN-22:10 30.00 24.76
July 0.518611E+11 23846.50 27-JUL-18:10 31.83 25.86 0.164375E+11 10880.68 28-JUL-22:10 28.80 24.46
August 0.509300E+11 23459.25 02-AUG-18:10 29.90 24.73 0.164718E+11 10835.71 02-AUG-22:10 28.90 24.51
September 0.491111E+11 23011.37 18-SEP-18:10 30.40 25.93 0.158264E+11 10850.06 22-SEP-22:10 28.30 25.74
October 0.493043E+11 22387.99 05-OCT-18:10 28.80 23.33 0.161722E+11 10710.46 03-OCT-22:10 28.80 23.33
November 0.457669E+11 21672.56 03-NOV-22:40 26.70 23.98 0.154295E+11 10634.65 03-NOV-22:10 26.70 23.98
December 0.452606E+11 21132.83 08-DEC-23:40 24.80 23.27 0.157089E+11 10493.89 08-DEC-23:10 24.80 23.27
                     
Annual Sum or Average 0.571444E+12         0.189719E+12        
Minimum of Months 0.412756E+11 20835.59   23.90 18.67 0.142325E+11 10438.06   23.80 18.67
Maximum of Months 0.518611E+11 23846.50   31.83 25.93 0.164718E+11 10880.68   30.03 25.74



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.476985E+11 22093.35 02-JAN-19:10 23.12 19.93 0.157267E+11 10529.79 06-JAN-23:10 23.98 22.41
February 0.441135E+11 22280.19 17-FEB-23:40 23.90 20.81 0.143345E+11 10584.75 17-FEB-23:10 23.90 20.81
March 0.497353E+11 23173.76 13-MAR-18:10 27.93 22.26 0.160738E+11 10606.58 28-MAR-22:10 23.80 20.10
April 0.500419E+11 24172.36 17-APR-18:10 30.03 18.67 0.156737E+11 10730.08 14-APR-22:10 30.03 18.67
May 0.533452E+11 24559.52 22-MAY-18:10 30.40 23.74 0.164367E+11 10844.21 22-MAY-22:10 26.93 22.26
June 0.527206E+11 24919.77 29-JUN-18:10 30.00 24.76 0.160810E+11 10938.21 09-JUN-22:10 30.00 24.76
July 0.549346E+11 25182.38 27-JUL-18:10 31.83 25.86 0.165228E+11 10937.87 28-JUL-22:10 28.80 24.46
August 0.540247E+11 24786.72 02-AUG-18:10 29.90 24.73 0.165649E+11 10897.41 02-AUG-22:10 28.90 24.51
September 0.520727E+11 24310.40 18-SEP-18:10 30.40 25.93 0.159104E+11 10906.02 22-SEP-22:10 28.30 25.74
October 0.523738E+11 23691.48 05-OCT-18:10 28.80 23.33 0.162672E+11 10784.88 03-OCT-22:10 28.80 23.33
November 0.487812E+11 22944.93 02-NOV-18:10 27.12 22.55 0.155339E+11 10714.73 03-NOV-22:10 26.70 24.19
December 0.483640E+11 22401.89 07-DEC-19:10 24.40 22.49 0.158162E+11 10578.92 08-DEC-23:10 24.50 22.98
                     
Annual Sum or Average 0.608206E+12         0.190942E+12        
Minimum of Months 0.441135E+11 22093.35   23.12 18.67 0.143345E+11 10529.79   23.80 18.67
Maximum of Months 0.549346E+11 25182.38   31.83 25.93 0.165649E+11 10938.21   30.03 25.74



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.558516E+11 29016.77 01-JAN-11:50 26.20 21.28 0.186658E+11 11319.66 28-JAN-18:19 22.93 20.00
February 0.510776E+11 29205.74 11-FEB-11:50 27.70 23.78 0.168644E+11 11319.72 25-FEB-18:19 22.43 15.34
March 0.572412E+11 29387.15 27-MAR-10:40 26.13 21.70 0.186809E+11 11319.72 25-MAR-17:19 26.13 21.70
April 0.568504E+11 30274.81 15-APR-10:50 29.63 22.91 0.180819E+11 11319.74 08-APR-17:19 29.63 22.91
May 0.597788E+11 30301.64 31-MAY-10:50 32.52 24.26 0.186937E+11 11319.74 20-MAY-17:19 32.52 24.26
June 0.586647E+11 30637.70 11-JUN-10:50 31.02 23.55 0.180996E+11 11319.73 10-JUN-17:19 31.02 23.55
July 0.610127E+11 30917.08 23-JUL-10:50 32.75 24.78 0.186970E+11 11319.73 15-JUL-17:19 32.75 24.78
August 0.603000E+11 30600.54 19-AUG-10:40 31.50 24.70 0.187006E+11 11319.73 26-AUG-17:19 30.40 25.15
September 0.584738E+11 30510.58 24-SEP-10:50 30.82 25.18 0.180941E+11 11319.73 16-SEP-17:19 30.82 25.18
October 0.594337E+11 30387.61 07-OCT-10:40 31.13 24.14 0.186895E+11 11319.72 21-OCT-17:19 26.67 19.93
November 0.558986E+11 29251.67 03-NOV-10:50 28.22 23.99 0.180759E+11 11319.66 25-NOV-18:19 25.03 22.08
December 0.561179E+11 29223.04 09-DEC-11:40 27.20 22.50 0.186677E+11 11319.70 02-DEC-18:19 27.20 22.50
                     
Annual Sum or Average 0.690701E+12         0.220011E+12        
Minimum of Months 0.510776E+11 29016.77   26.13 21.28 0.168644E+11 11319.66   22.43 15.34
Maximum of Months 0.610127E+11 30917.08   32.75 25.18 0.187006E+11 11319.74   32.75 25.18



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.957094E+10 6348.01 01-JAN-11:35 26.30 21.34 0.127346E+10 779.59 13-JAN-23:10 23.90 21.21
February 0.947090E+10 6464.67 11-FEB-11:35 27.60 23.74 0.115325E+10 777.07 17-FEB-23:10 23.90 20.81
March 0.110328E+11 6377.72 04-MAR-11:35 27.03 22.82 0.128561E+10 787.03 27-MAR-22:10 24.32 21.61
April 0.122668E+11 6781.01 15-APR-10:35 29.27 22.89 0.125565E+10 811.83 14-APR-21:49 29.27 22.89
May 0.137000E+11 6931.67 31-MAY-10:35 32.23 24.19 0.132940E+10 823.55 22-MAY-22:10 32.23 24.19
June 0.139394E+11 7227.45 11-JUN-10:35 30.93 23.60 0.132181E+10 844.83 09-JUN-22:10 30.93 23.60
July 0.147896E+11 7400.77 29-JUL-10:35 32.07 25.98 0.137450E+10 853.30 28-JUL-22:10 32.07 25.98
August 0.143072E+11 7241.91 19-AUG-10:35 31.50 24.70 0.136360E+10 842.98 02-AUG-22:10 31.50 24.70
September 0.139438E+11 7287.70 24-SEP-10:35 30.53 25.04 0.131824E+10 852.13 22-SEP-22:10 30.53 25.04
October 0.137774E+11 7118.15 07-OCT-10:35 31.13 24.14 0.133164E+10 826.29 06-OCT-22:10 31.13 24.14
November 0.117460E+11 6685.07 08-NOV-11:35 27.43 21.48 0.125390E+10 808.80 03-NOV-22:10 27.43 21.48
December 0.101631E+11 6651.05 09-DEC-11:35 27.20 22.50 0.127851E+10 790.19 08-DEC-23:10 27.20 22.50
                     
Annual Sum or Average 0.148708E+12         0.155396E+11        
Minimum of Months 0.947090E+10 6348.01   26.30 21.34 0.115325E+10 777.07   23.90 20.81
Maximum of Months 0.147896E+11 7400.77   32.23 25.98 0.137450E+10 853.30   32.23 25.98



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:03 20.40
February 0.00 0.00 01-FEB-00:03 16.65
March 0.00 0.00 01-MAR-00:03 17.32
April 0.00 0.00 01-APR-00:10 22.57
May 0.00 0.00 01-MAY-00:10 22.05
June 0.00 0.00 01-JUN-00:10 26.68
July 0.00 0.00 01-JUL-00:10 26.83
August 0.00 0.00 01-AUG-00:10 28.60
September 0.00 0.00 01-SEP-00:10 27.05
October 0.00 0.00 01-OCT-00:10 27.93
November 0.00 0.00 01-NOV-00:10 22.40
December 0.00 0.00 01-DEC-00:03 24.10
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   16.65
Maximum of Months 0.00 0.00   28.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:03 20.40
February 995617.70 150.57 04-FEB-07:20 5.57
March 0.00 0.00 01-MAR-00:03 17.32
April 0.00 0.00 01-APR-00:10 22.57
May 0.00 0.00 01-MAY-00:10 22.05
June 0.00 0.00 01-JUN-00:10 26.68
July 0.00 0.00 01-JUL-00:10 26.83
August 0.00 0.00 01-AUG-00:10 28.60
September 0.00 0.00 01-SEP-00:10 27.05
October 0.00 0.00 01-OCT-00:10 27.93
November 0.00 0.00 01-NOV-00:10 22.40
December 0.00 0.00 01-DEC-00:03 24.10
         
Annual Sum or Average 995617.70      
Minimum of Months 0.00 0.00   5.57
Maximum of Months 995617.70 150.57   28.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:03 20.40
February 0.00 0.00 01-FEB-00:03 16.65
March 0.00 0.00 01-MAR-00:03 17.32
April 0.00 0.00 01-APR-00:10 22.57
May 0.00 0.00 01-MAY-00:10 22.05
June 0.00 0.00 01-JUN-00:10 26.68
July 0.00 0.00 01-JUL-00:10 26.83
August 0.00 0.00 01-AUG-00:10 28.60
September 0.00 0.00 01-SEP-00:10 27.05
October 0.00 0.00 01-OCT-00:10 27.93
November 0.00 0.00 01-NOV-00:10 22.40
December 0.00 0.00 01-DEC-00:03 24.10
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   16.65
Maximum of Months 0.00 0.00   28.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:03 20.40
February 0.00 0.00 01-FEB-00:03 16.65
March 0.00 0.00 01-MAR-00:03 17.32
April 0.00 0.00 01-APR-00:10 22.57
May 0.00 0.00 01-MAY-00:10 22.05
June 0.00 0.00 01-JUN-00:10 26.68
July 0.00 0.00 01-JUL-00:10 26.83
August 0.00 0.00 01-AUG-00:10 28.60
September 0.00 0.00 01-SEP-00:10 27.05
October 0.00 0.00 01-OCT-00:10 27.93
November 0.00 0.00 01-NOV-00:10 22.40
December 0.00 0.00 01-DEC-00:03 24.10
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   16.65
Maximum of Months 0.00 0.00   28.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:03 20.40
February 0.00 0.00 01-FEB-00:03 16.65
March 0.00 0.00 01-MAR-00:03 17.32
April 0.00 0.00 01-APR-00:10 22.57
May 0.00 0.00 01-MAY-00:10 22.05
June 0.00 0.00 01-JUN-00:10 26.68
July 0.00 0.00 01-JUL-00:10 26.83
August 0.00 0.00 01-AUG-00:10 28.60
September 0.00 0.00 01-SEP-00:10 27.05
October 0.00 0.00 01-OCT-00:10 27.93
November 0.00 0.00 01-NOV-00:10 22.40
December 0.00 0.00 01-DEC-00:03 24.10
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   16.65
Maximum of Months 0.00 0.00   28.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:03 20.40
February 0.00 0.00 01-FEB-00:03 16.65
March 0.00 0.00 01-MAR-00:03 17.32
April 0.00 0.00 01-APR-00:10 22.57
May 0.00 0.00 01-MAY-00:10 22.05
June 0.00 0.00 01-JUN-00:10 26.68
July 0.00 0.00 01-JUL-00:10 26.83
August 0.00 0.00 01-AUG-00:10 28.60
September 0.00 0.00 01-SEP-00:10 27.05
October 0.00 0.00 01-OCT-00:10 27.93
November 0.00 0.00 01-NOV-00:10 22.40
December 0.00 0.00 01-DEC-00:03 24.10
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   16.65
Maximum of Months 0.00 0.00   28.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:03 20.40
February 0.00 0.00 01-FEB-00:03 16.65
March 0.00 0.00 01-MAR-00:03 17.32
April 0.00 0.00 01-APR-00:10 22.57
May 0.00 0.00 01-MAY-00:10 22.05
June 0.00 0.00 01-JUN-00:10 26.68
July 0.00 0.00 01-JUL-00:10 26.83
August 0.00 0.00 01-AUG-00:10 28.60
September 0.00 0.00 01-SEP-00:10 27.05
October 0.00 0.00 01-OCT-00:10 27.93
November 0.00 0.00 01-NOV-00:10 22.40
December 0.00 0.00 01-DEC-00:03 24.10
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   16.65
Maximum of Months 0.00 0.00   28.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:03 20.40
February 0.00 0.00 01-FEB-00:03 16.65
March 0.00 0.00 01-MAR-00:03 17.32
April 0.00 0.00 01-APR-00:10 22.57
May 0.00 0.00 01-MAY-00:10 22.05
June 0.00 0.00 01-JUN-00:10 26.68
July 0.00 0.00 01-JUL-00:10 26.83
August 0.00 0.00 01-AUG-00:10 28.60
September 0.00 0.00 01-SEP-00:10 27.05
October 0.00 0.00 01-OCT-00:10 27.93
November 0.00 0.00 01-NOV-00:10 22.40
December 0.00 0.00 01-DEC-00:03 24.10
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   16.65
Maximum of Months 0.00 0.00   28.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 4411923.23 652.00 25-JAN-16:04 17.80
February 11063819.00 779.10 03-FEB-16:04 16.42
March 3997512.48 1128.57 16-MAR-08:62 8.68
April 1057837.24 660.17 29-APR-08:05 23.40
May 717104.18 811.78 08-MAY-08:04 25.18
June 387506.85 539.14 19-JUN-08:05 26.60
July 90517.87 355.30 03-JUL-08:05 26.88
August 463433.88 553.57 29-AUG-08:05 27.38
September 472122.68 495.67 28-SEP-08:05 24.78
October 703774.09 791.63 18-OCT-08:04 26.20
November 1555439.78 652.30 27-NOV-09:03 15.65
December 6573811.35 816.54 20-DEC-19:03 12.62
         
Annual Sum or Average 31494802.63      
Minimum of Months 90517.87 355.30   8.68
Maximum of Months 11063819.00 1128.57   27.38



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 11690197.69 1148.70 26-JAN-09:02 13.77
February 17409211.97 1116.73 04-FEB-09:02 10.47
March 7709468.90 1146.37 16-MAR-08:62 8.68
April 1112588.43 651.91 29-APR-08:05 23.40
May 723866.88 832.15 08-MAY-08:04 25.18
June 314203.60 509.22 19-JUN-08:05 26.60
July 40948.27 294.91 03-JUL-08:05 26.88
August 523430.93 547.74 29-AUG-08:05 27.38
September 619316.64 517.52 07-SEP-08:05 25.18
October 1209767.66 802.73 18-OCT-08:04 26.20
November 3265498.31 800.18 12-NOV-16:03 20.00
December 17476158.19 1128.51 27-DEC-09:02 11.47
         
Annual Sum or Average 62094657.47      
Minimum of Months 40948.27 294.91   8.68
Maximum of Months 17476158.19 1148.70   27.38



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:03 20.40
February 0.00 0.00 01-FEB-00:03 16.65
March 0.00 0.00 01-MAR-00:03 17.32
April 0.00 0.00 01-APR-00:10 22.57
May 0.00 0.00 01-MAY-00:10 22.05
June 0.00 0.00 01-JUN-00:10 26.68
July 0.00 0.00 01-JUL-00:10 26.83
August 0.00 0.00 01-AUG-00:10 28.60
September 0.00 0.00 01-SEP-00:10 27.05
October 0.00 0.00 01-OCT-00:10 27.93
November 0.00 0.00 01-NOV-00:10 22.40
December 0.00 0.00 01-DEC-00:03 24.10
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   16.65
Maximum of Months 0.00 0.00   28.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 682165.41 370.46 24-JAN-16:03 16.70
February 457410.56 375.60 03-FEB-16:03 16.42
March 558306.17 366.60 19-MAR-15:05 16.78
April 284336.21 339.73 20-APR-08:05 23.48
May 99577.86 195.45 11-MAY-08:06 24.60
June 159613.29 135.39 09-JUN-08:07 28.98
July 134652.50 100.18 12-JUL-08:07 28.22
August 89379.18 142.53 12-AUG-18:07 26.60
September 7545.36 35.73 11-SEP-08:07 27.48
October 172588.04 127.69 10-OCT-18:07 27.12
November 365432.03 331.06 15-NOV-09:05 23.98
December 585860.61 354.55 26-DEC-16:04 18.12
         
Annual Sum or Average 3596867.21      
Minimum of Months 7545.36 35.73   16.42
Maximum of Months 682165.41 375.60   28.98



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 5124433.07 705.61 25-JAN-16:04 17.80
February 10587875.73 519.25 19-FEB-09:05 21.20
March 3602659.10 895.21 16-MAR-15:04 18.48
April 173657.58 630.91 30-APR-08:05 23.12
May 85525.78 506.54 25-MAY-08:05 25.40
June 23766.86 237.67 15-JUN-08:05 23.68
July 0.00 0.00 01-JUL-00:10 26.83
August 53806.14 538.06 28-AUG-08:05 23.72
September 0.00 0.00 01-SEP-00:10 27.05
October 27224.11 264.21 31-OCT-08:05 24.50
November 1044560.03 390.43 27-NOV-19:05 22.20
December 7936852.79 643.88 20-DEC-19:03 12.62
         
Annual Sum or Average 28660361.19      
Minimum of Months 0.00 0.00   12.62
Maximum of Months 10587875.73 895.21   27.05



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 13804500.24 907.21 24-JAN-16:03 16.70
February 16278835.32 677.94 03-FEB-16:03 16.42
March 6232025.80 690.96 16-MAR-18:03 18.22
April 194523.46 622.87 30-APR-08:05 23.12
May 104047.81 573.58 25-MAY-08:05 25.40
June 24824.30 248.24 15-JUN-08:05 23.68
July 0.00 0.00 01-JUL-00:10 26.83
August 58226.77 524.66 28-AUG-08:05 23.72
September 0.00 0.00 01-SEP-00:10 27.05
October 85377.22 489.97 18-OCT-08:04 26.20
November 2764793.71 653.83 29-NOV-09:05 25.68
December 20116713.29 778.27 27-DEC-16:03 20.00
         
Annual Sum or Average 59663867.92      
Minimum of Months 0.00 0.00   16.42
Maximum of Months 20116713.29 907.21   27.05



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:03 20.40
February 0.00 0.00 01-FEB-00:03 16.65
March 0.00 0.00 01-MAR-00:03 17.32
April 0.00 0.00 01-APR-00:10 22.57
May 0.00 0.00 01-MAY-00:10 22.05
June 0.00 0.00 01-JUN-00:10 26.68
July 0.00 0.00 01-JUL-00:10 26.83
August 0.00 0.00 01-AUG-00:10 28.60
September 0.00 0.00 01-SEP-00:10 27.05
October 0.00 0.00 01-OCT-00:10 27.93
November 0.00 0.00 01-NOV-00:10 22.40
December 0.00 0.00 01-DEC-00:03 24.10
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   16.65
Maximum of Months 0.00 0.00   28.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 14203971.55 846.01 25-JAN-09:02 11.57
February 21143651.78 1288.85 04-FEB-09:02 10.47
March 11364832.94 1340.75 16-MAR-08:62 8.68
April 1000559.66 686.13 09-APR-08:04 23.90
May 635770.22 814.00 08-MAY-08:04 25.18
June 332313.64 425.09 22-JUN-08:05 24.90
July 78010.70 317.11 03-JUL-08:05 26.88
August 456116.31 553.33 12-AUG-08:05 22.70
September 480426.12 448.32 26-SEP-08:05 24.78
October 735169.14 799.81 18-OCT-08:04 26.20
November 4848462.18 596.82 29-NOV-09:05 25.68
December 20335815.31 1080.68 15-DEC-09:02 10.97
         
Annual Sum or Average 75615099.54      
Minimum of Months 78010.70 317.11   8.68
Maximum of Months 21143651.78 1340.75   26.88



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 35388587.17 1360.11 26-JAN-09:02 13.77
February 32120897.26 1340.14 05-FEB-09:02 15.37
March 17760108.78 1360.18 16-MAR-08:62 8.68
April 1075795.20 876.24 09-APR-08:04 23.90
May 587539.77 816.81 08-MAY-08:04 25.18
June 241582.03 387.40 19-JUN-08:05 26.60
July 41030.11 279.50 03-JUL-08:05 26.88
August 472175.50 567.39 12-AUG-08:05 22.70
September 558511.70 442.96 12-SEP-08:05 26.28
October 1118109.78 755.97 18-OCT-08:04 26.20
November 8527790.81 1319.92 13-NOV-09:02 16.65
December 40814680.29 1344.12 21-DEC-09:02 15.65
         
Annual Sum or Average 0.138707E+09      
Minimum of Months 41030.11 279.50   8.68
Maximum of Months 40814680.29 1360.18   26.88



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 165792.99 297.50 09-JAN-09:05 15.28
February 2268319.25 210.82 04-FEB-09:05 10.47
March 835034.50 519.64 16-MAR-08:62 8.68
April 371394.21 384.10 21-APR-08:05 24.60
May 72634.84 340.86 01-MAY-08:05 24.78
June 0.00 0.00 01-JUN-00:10 26.68
July 0.00 0.00 01-JUL-00:10 26.83
August 38061.76 329.51 28-AUG-08:05 23.72
September 1124.44 11.22 15-SEP-08:05 25.37
October 0.00 0.00 01-OCT-00:10 27.93
November 96101.75 323.73 12-NOV-16:05 20.00
December 174984.51 266.03 16-DEC-09:05 14.45
         
Annual Sum or Average 4023448.24      
Minimum of Months 0.00 0.00   8.68
Maximum of Months 2268319.25 519.64   27.93



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:03 20.40
February 0.00 0.00 01-FEB-00:03 16.65
March 0.00 0.00 01-MAR-00:03 17.32
April 0.00 0.00 01-APR-00:10 22.57
May 0.00 0.00 01-MAY-00:10 22.05
June 0.00 0.00 01-JUN-00:10 26.68
July 0.00 0.00 01-JUL-00:10 26.83
August 0.00 0.00 01-AUG-00:10 28.60
September 0.00 0.00 01-SEP-00:10 27.05
October 0.00 0.00 01-OCT-00:10 27.93
November 0.00 0.00 01-NOV-00:10 22.40
December 0.00 0.00 01-DEC-00:03 24.10
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   16.65
Maximum of Months 0.00 0.00   28.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:03 20.40
February 0.00 0.00 01-FEB-00:03 16.65
March 0.00 0.00 01-MAR-00:03 17.32
April 0.00 0.00 01-APR-00:10 22.57
May 0.00 0.00 01-MAY-00:10 22.05
June 0.00 0.00 01-JUN-00:10 26.68
July 0.00 0.00 01-JUL-00:10 26.83
August 0.00 0.00 01-AUG-00:10 28.60
September 0.00 0.00 01-SEP-00:10 27.05
October 0.00 0.00 01-OCT-00:10 27.93
November 0.00 0.00 01-NOV-00:10 22.40
December 0.00 0.00 01-DEC-00:03 24.10
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   16.65
Maximum of Months 0.00 0.00   28.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:03 20.40
February 0.00 0.00 01-FEB-00:03 16.65
March 0.00 0.00 01-MAR-00:03 17.32
April 0.00 0.00 01-APR-00:10 22.57
May 0.00 0.00 01-MAY-00:10 22.05
June 0.00 0.00 01-JUN-00:10 26.68
July 0.00 0.00 01-JUL-00:10 26.83
August 0.00 0.00 01-AUG-00:10 28.60
September 0.00 0.00 01-SEP-00:10 27.05
October 0.00 0.00 01-OCT-00:10 27.93
November 0.00 0.00 01-NOV-00:10 22.40
December 0.00 0.00 01-DEC-00:03 24.10
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   16.65
Maximum of Months 0.00 0.00   28.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:03 20.40
February 940919.02 305.94 04-FEB-07:10 5.28
March 0.00 0.00 01-MAR-00:03 17.32
April 0.00 0.00 01-APR-00:10 22.57
May 0.00 0.00 01-MAY-00:10 22.05
June 0.00 0.00 01-JUN-00:10 26.68
July 0.00 0.00 01-JUL-00:10 26.83
August 0.00 0.00 01-AUG-00:10 28.60
September 0.00 0.00 01-SEP-00:10 27.05
October 0.00 0.00 01-OCT-00:10 27.93
November 0.00 0.00 01-NOV-00:10 22.40
December 0.00 0.00 01-DEC-00:03 24.10
         
Annual Sum or Average 940919.02      
Minimum of Months 0.00 0.00   5.28
Maximum of Months 940919.02 305.94   28.60



Table of Contents

Report: ZoneElectricSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.140333E+11 13517.00 02-JAN-20:10 0.127587E+11 10113.80 02-JAN-20:10
February 0.126708E+11 13517.00 01-FEB-20:10 0.115208E+11 10113.80 01-FEB-20:10
March 0.140766E+11 13517.00 01-MAR-20:10 0.127855E+11 10113.80 01-MAR-20:10
April 0.135575E+11 13517.00 03-APR-19:10 0.123314E+11 10113.80 03-APR-19:10
May 0.140576E+11 13517.00 01-MAY-19:10 0.127741E+11 10113.80 01-MAY-19:10
June 0.136197E+11 13517.00 01-JUN-19:10 0.123716E+11 10113.80 01-JUN-19:10
July 0.139955E+11 13517.00 03-JUL-19:10 0.127338E+11 10113.80 03-JUL-19:10
August 0.140820E+11 13517.00 01-AUG-19:10 0.127894E+11 10113.80 01-AUG-19:10
September 0.135629E+11 13517.00 01-SEP-19:10 0.123352E+11 10113.80 01-SEP-19:10
October 0.140279E+11 13517.00 02-OCT-19:10 0.127549E+11 10113.80 02-OCT-19:10
November 0.136089E+11 13517.00 01-NOV-19:10 0.123659E+11 10113.80 01-NOV-19:10
December 0.139955E+11 13517.00 01-DEC-20:10 0.127338E+11 10113.80 01-DEC-20:10
             
Annual Sum or Average 0.165288E+12     0.150255E+12    
Minimum of Months 0.126708E+11 13517.00   0.115208E+11 10113.80  
Maximum of Months 0.140820E+11 13517.00   0.127894E+11 10113.80  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.713551E+09 687.30 02-JAN-20:10 0.864900E+09 685.60 02-JAN-20:10
February 0.644271E+09 687.30 01-FEB-20:10 0.780982E+09 685.60 01-FEB-20:10
March 0.715750E+09 687.30 01-MAR-20:10 0.866718E+09 685.60 01-MAR-20:10
April 0.689358E+09 687.30 03-APR-19:10 0.835931E+09 685.60 03-APR-19:10
May 0.714788E+09 687.30 01-MAY-19:10 0.865939E+09 685.60 01-MAY-19:10
June 0.692519E+09 687.30 01-JUN-19:10 0.838659E+09 685.60 01-JUN-19:10
July 0.711626E+09 687.30 03-JUL-19:10 0.863211E+09 685.60 03-JUL-19:10
August 0.716025E+09 687.30 01-AUG-19:10 0.866978E+09 685.60 01-AUG-19:10
September 0.689633E+09 687.30 01-SEP-19:10 0.836191E+09 685.60 01-SEP-19:10
October 0.713276E+09 687.30 02-OCT-19:10 0.864640E+09 685.60 02-OCT-19:10
November 0.691970E+09 687.30 01-NOV-19:10 0.838269E+09 685.60 01-NOV-19:10
December 0.711626E+09 687.30 01-DEC-20:10 0.863211E+09 685.60 01-DEC-20:10
             
Annual Sum or Average 0.840439E+10     0.101856E+11    
Minimum of Months 0.644271E+09 687.30   0.780982E+09 685.60  
Maximum of Months 0.716025E+09 687.30   0.866978E+09 685.60  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.826294E+09 795.89 02-JAN-20:10 0.100156E+10 793.93 02-JAN-20:10
February 0.746069E+09 795.89 01-FEB-20:10 0.904380E+09 793.93 01-FEB-20:10
March 0.828841E+09 795.89 01-MAR-20:10 0.100366E+10 793.93 01-MAR-20:10
April 0.798279E+09 795.89 03-APR-19:10 0.968011E+09 793.93 03-APR-19:10
May 0.827727E+09 795.89 01-MAY-19:10 0.100276E+10 793.93 01-MAY-19:10
June 0.801940E+09 795.89 01-JUN-19:10 0.971170E+09 793.93 01-JUN-19:10
July 0.824066E+09 795.89 03-JUL-19:10 0.999601E+09 793.93 03-JUL-19:10
August 0.829160E+09 795.89 01-AUG-19:10 0.100396E+10 793.93 01-AUG-19:10
September 0.798597E+09 795.89 01-SEP-19:10 0.968312E+09 793.93 01-SEP-19:10
October 0.825976E+09 795.89 02-OCT-19:10 0.100126E+10 793.93 02-OCT-19:10
November 0.801303E+09 795.89 01-NOV-19:10 0.970719E+09 793.93 01-NOV-19:10
December 0.824066E+09 795.89 01-DEC-20:10 0.999601E+09 793.93 01-DEC-20:10
             
Annual Sum or Average 0.973232E+10     0.117950E+11    
Minimum of Months 0.746069E+09 795.89   0.904380E+09 793.93  
Maximum of Months 0.829160E+09 795.89   0.100396E+10 793.93  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.154452E+10 1487.69 02-JAN-20:10 0.105898E+10 839.45 02-JAN-20:10
February 0.139456E+10 1487.69 01-FEB-20:10 0.956227E+09 839.45 01-FEB-20:10
March 0.154928E+10 1487.69 01-MAR-20:10 0.106120E+10 839.45 01-MAR-20:10
April 0.149215E+10 1487.69 03-APR-19:10 0.102351E+10 839.45 03-APR-19:10
May 0.154719E+10 1487.69 01-MAY-19:10 0.106025E+10 839.45 01-MAY-19:10
June 0.149899E+10 1487.69 01-JUN-19:10 0.102685E+10 839.45 01-JUN-19:10
July 0.154035E+10 1487.69 03-JUL-19:10 0.105691E+10 839.45 03-JUL-19:10
August 0.154987E+10 1487.69 01-AUG-19:10 0.106152E+10 839.45 01-AUG-19:10
September 0.149274E+10 1487.69 01-SEP-19:10 0.102382E+10 839.45 01-SEP-19:10
October 0.154392E+10 1487.69 02-OCT-19:10 0.105866E+10 839.45 02-OCT-19:10
November 0.149780E+10 1487.69 01-NOV-19:10 0.102637E+10 839.45 01-NOV-19:10
December 0.154035E+10 1487.69 01-DEC-20:10 0.105691E+10 839.45 01-DEC-20:10
             
Annual Sum or Average 0.181917E+11     0.124712E+11    
Minimum of Months 0.139456E+10 1487.69   0.956227E+09 839.45  
Maximum of Months 0.154987E+10 1487.69   0.106152E+10 839.45  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.283535E+09 273.10 02-JAN-20:10 0.305485E+09 242.16 02-JAN-20:10
February 0.256006E+09 273.10 01-FEB-20:10 0.275845E+09 242.16 01-FEB-20:10
March 0.284409E+09 273.10 01-MAR-20:10 0.306128E+09 242.16 01-MAR-20:10
April 0.273921E+09 273.10 03-APR-19:10 0.295253E+09 242.16 03-APR-19:10
May 0.284026E+09 273.10 01-MAY-19:10 0.305852E+09 242.16 01-MAY-19:10
June 0.275178E+09 273.10 01-JUN-19:10 0.296217E+09 242.16 01-JUN-19:10
July 0.282770E+09 273.10 03-JUL-19:10 0.304889E+09 242.16 03-JUL-19:10
August 0.284518E+09 273.10 01-AUG-19:10 0.306219E+09 242.16 01-AUG-19:10
September 0.274031E+09 273.10 01-SEP-19:10 0.295345E+09 242.16 01-SEP-19:10
October 0.283425E+09 273.10 02-OCT-19:10 0.305393E+09 242.16 02-OCT-19:10
November 0.274959E+09 273.10 01-NOV-19:10 0.296079E+09 242.16 01-NOV-19:10
December 0.282770E+09 273.10 01-DEC-20:10 0.304889E+09 242.16 01-DEC-20:10
             
Annual Sum or Average 0.333955E+10     0.359760E+10    
Minimum of Months 0.256006E+09 273.10   0.275845E+09 242.16  
Maximum of Months 0.284518E+09 273.10   0.306219E+09 242.16  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.350256E+09 337.37 02-JAN-20:10 0.576866E+10 4572.80 02-JAN-20:10
February 0.316249E+09 337.37 01-FEB-20:10 0.520895E+10 4572.80 01-FEB-20:10
March 0.351336E+09 337.37 01-MAR-20:10 0.578079E+10 4572.80 01-MAR-20:10
April 0.338381E+09 337.37 03-APR-19:10 0.557545E+10 4572.80 03-APR-19:10
May 0.350863E+09 337.37 01-MAY-19:10 0.577559E+10 4572.80 01-MAY-19:10
June 0.339933E+09 337.37 01-JUN-19:10 0.559364E+10 4572.80 01-JUN-19:10
July 0.349311E+09 337.37 03-JUL-19:10 0.575740E+10 4572.80 03-JUL-19:10
August 0.351471E+09 337.37 01-AUG-19:10 0.578252E+10 4572.80 01-AUG-19:10
September 0.338516E+09 337.37 01-SEP-19:10 0.557718E+10 4572.80 01-SEP-19:10
October 0.350121E+09 337.37 02-OCT-19:10 0.576693E+10 4572.80 02-OCT-19:10
November 0.339663E+09 337.37 01-NOV-19:10 0.559104E+10 4572.80 01-NOV-19:10
December 0.349311E+09 337.37 01-DEC-20:10 0.575740E+10 4572.80 01-DEC-20:10
             
Annual Sum or Average 0.412541E+10     0.679355E+11    
Minimum of Months 0.316249E+09 337.37   0.520895E+10 4572.80  
Maximum of Months 0.351471E+09 337.37   0.578252E+10 4572.80  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.226040E+10 2177.23 02-JAN-20:10 0.121771E+10 965.27 02-JAN-20:10
February 0.204093E+10 2177.23 01-FEB-20:10 0.109956E+10 965.27 01-FEB-20:10
March 0.226736E+10 2177.23 01-MAR-20:10 0.122027E+10 965.27 01-MAR-20:10
April 0.218376E+10 2177.23 03-APR-19:10 0.117692E+10 965.27 03-APR-19:10
May 0.226431E+10 2177.23 01-MAY-19:10 0.121917E+10 965.27 01-MAY-19:10
June 0.219377E+10 2177.23 01-JUN-19:10 0.118076E+10 965.27 01-JUN-19:10
July 0.225430E+10 2177.23 03-JUL-19:10 0.121533E+10 965.27 03-JUL-19:10
August 0.226823E+10 2177.23 01-AUG-19:10 0.122063E+10 965.27 01-AUG-19:10
September 0.218463E+10 2177.23 01-SEP-19:10 0.117729E+10 965.27 01-SEP-19:10
October 0.225952E+10 2177.23 02-OCT-19:10 0.121734E+10 965.27 02-OCT-19:10
November 0.219203E+10 2177.23 01-NOV-19:10 0.118021E+10 965.27 01-NOV-19:10
December 0.225430E+10 2177.23 01-DEC-20:10 0.121533E+10 965.27 01-DEC-20:10
             
Annual Sum or Average 0.266236E+11     0.143405E+11    
Minimum of Months 0.204093E+10 2177.23   0.109956E+10 965.27  
Maximum of Months 0.226823E+10 2177.23   0.122063E+10 965.27  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.123020E+11 11849.32 02-JAN-20:10 0.126520E+11 10029.21 02-JAN-20:10
February 0.111075E+11 11849.32 01-FEB-20:10 0.114244E+11 10029.21 01-FEB-20:10
March 0.123399E+11 11849.32 01-MAR-20:10 0.126786E+11 10029.21 01-MAR-20:10
April 0.118849E+11 11849.32 03-APR-19:10 0.122282E+11 10029.21 03-APR-19:10
May 0.123233E+11 11849.32 01-MAY-19:10 0.126672E+11 10029.21 01-MAY-19:10
June 0.119394E+11 11849.32 01-JUN-19:10 0.122682E+11 10029.21 01-JUN-19:10
July 0.122688E+11 11849.32 03-JUL-19:10 0.126273E+11 10029.21 03-JUL-19:10
August 0.123446E+11 11849.32 01-AUG-19:10 0.126824E+11 10029.21 01-AUG-19:10
September 0.118896E+11 11849.32 01-SEP-19:10 0.122320E+11 10029.21 01-SEP-19:10
October 0.122972E+11 11849.32 02-OCT-19:10 0.126482E+11 10029.21 02-OCT-19:10
November 0.119299E+11 11849.32 01-NOV-19:10 0.122624E+11 10029.21 01-NOV-19:10
December 0.122688E+11 11849.32 01-DEC-20:10 0.126273E+11 10029.21 01-DEC-20:10
             
Annual Sum or Average 0.144896E+12     0.148998E+12    
Minimum of Months 0.111075E+11 11849.32   0.114244E+11 10029.21  
Maximum of Months 0.123446E+11 11849.32   0.126824E+11 10029.21  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.434056E+09 392.73 01-JAN-19:10 0.261068E+09 237.06 01-JAN-08:09
February 0.391995E+09 392.73 01-FEB-20:10 0.235798E+09 237.06 01-FEB-07:10
March 0.430607E+09 392.73 01-MAR-20:10 0.260708E+09 237.06 01-MAR-07:10
April 0.420554E+09 392.73 01-APR-18:10 0.252705E+09 237.06 01-APR-07:10
May 0.432331E+09 392.73 01-MAY-19:10 0.260888E+09 237.06 01-MAY-06:10
June 0.417218E+09 392.73 01-JUN-19:10 0.252344E+09 237.06 01-JUN-06:10
July 0.435725E+09 392.73 01-JUL-18:10 0.261248E+09 237.06 01-JUL-07:10
August 0.430607E+09 392.73 01-AUG-19:10 0.260708E+09 237.06 01-AUG-06:10
September 0.420667E+09 392.73 01-SEP-19:10 0.252705E+09 237.06 01-SEP-06:10
October 0.434000E+09 392.73 01-OCT-18:10 0.261068E+09 237.06 01-OCT-07:10
November 0.418886E+09 392.73 01-NOV-19:10 0.252524E+09 237.06 01-NOV-06:10
December 0.435781E+09 392.73 01-DEC-20:10 0.261248E+09 237.06 01-DEC-07:10
             
Annual Sum or Average 0.510243E+10     0.307301E+10    
Minimum of Months 0.391995E+09 392.73   0.235798E+09 237.06  
Maximum of Months 0.435781E+09 392.73   0.261248E+09 237.06  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.434005E+09 392.68 01-JAN-19:10 0.261038E+09 237.03 01-JAN-08:09
February 0.391949E+09 392.68 01-FEB-20:10 0.235770E+09 237.03 01-FEB-07:10
March 0.430556E+09 392.68 01-MAR-20:10 0.260677E+09 237.03 01-MAR-07:10
April 0.420505E+09 392.68 01-APR-18:10 0.252675E+09 237.03 01-APR-07:10
May 0.432281E+09 392.68 01-MAY-19:10 0.260857E+09 237.03 01-MAY-06:10
June 0.417169E+09 392.68 01-JUN-19:10 0.252315E+09 237.03 01-JUN-06:10
July 0.435674E+09 392.68 01-JUL-18:10 0.261218E+09 237.03 01-JUL-07:10
August 0.430556E+09 392.68 01-AUG-19:10 0.260677E+09 237.03 01-AUG-06:10
September 0.420618E+09 392.68 01-SEP-19:10 0.252675E+09 237.03 01-SEP-06:10
October 0.433949E+09 392.68 01-OCT-18:10 0.261038E+09 237.03 01-OCT-07:10
November 0.418837E+09 392.68 01-NOV-19:10 0.252495E+09 237.03 01-NOV-06:10
December 0.435730E+09 392.68 01-DEC-20:10 0.261218E+09 237.03 01-DEC-07:10
             
Annual Sum or Average 0.510183E+10     0.307265E+10    
Minimum of Months 0.391949E+09 392.68   0.235770E+09 237.03  
Maximum of Months 0.435730E+09 392.68   0.261218E+09 237.03  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.272788E+09 246.81 01-JAN-19:10 0.255708E+09 232.19 01-JAN-08:09
February 0.246354E+09 246.81 01-FEB-20:10 0.230956E+09 232.19 01-FEB-07:10
March 0.270620E+09 246.81 01-MAR-20:10 0.255355E+09 232.19 01-MAR-07:10
April 0.264302E+09 246.81 01-APR-18:10 0.247516E+09 232.19 01-APR-07:10
May 0.271704E+09 246.81 01-MAY-19:10 0.255532E+09 232.19 01-MAY-06:10
June 0.262205E+09 246.81 01-JUN-19:10 0.247163E+09 232.19 01-JUN-06:10
July 0.273836E+09 246.81 01-JUL-18:10 0.255885E+09 232.19 01-JUL-07:10
August 0.270620E+09 246.81 01-AUG-19:10 0.255355E+09 232.19 01-AUG-06:10
September 0.264373E+09 246.81 01-SEP-19:10 0.247516E+09 232.19 01-SEP-06:10
October 0.272752E+09 246.81 01-OCT-18:10 0.255708E+09 232.19 01-OCT-07:10
November 0.263254E+09 246.81 01-NOV-19:10 0.247340E+09 232.19 01-NOV-06:10
December 0.273872E+09 246.81 01-DEC-20:10 0.255885E+09 232.19 01-DEC-07:10
             
Annual Sum or Average 0.320668E+10     0.300992E+10    
Minimum of Months 0.246354E+09 246.81   0.230956E+09 232.19  
Maximum of Months 0.273872E+09 246.81   0.255885E+09 232.19  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.272862E+09 246.88 01-JAN-19:10 0.255778E+09 232.26 01-JAN-08:09
February 0.246421E+09 246.88 01-FEB-20:10 0.231020E+09 232.26 01-FEB-07:10
March 0.270694E+09 246.88 01-MAR-20:10 0.255425E+09 232.26 01-MAR-07:10
April 0.264375E+09 246.88 01-APR-18:10 0.247584E+09 232.26 01-APR-07:10
May 0.271778E+09 246.88 01-MAY-19:10 0.255602E+09 232.26 01-MAY-06:10
June 0.262277E+09 246.88 01-JUN-19:10 0.247231E+09 232.26 01-JUN-06:10
July 0.273911E+09 246.88 01-JUL-18:10 0.255955E+09 232.26 01-JUL-07:10
August 0.270694E+09 246.88 01-AUG-19:10 0.255425E+09 232.26 01-AUG-06:10
September 0.264446E+09 246.88 01-SEP-19:10 0.247584E+09 232.26 01-SEP-06:10
October 0.272827E+09 246.88 01-OCT-18:10 0.255778E+09 232.26 01-OCT-07:10
November 0.263326E+09 246.88 01-NOV-19:10 0.247408E+09 232.26 01-NOV-06:10
December 0.273947E+09 246.88 01-DEC-20:10 0.255955E+09 232.26 01-DEC-07:10
             
Annual Sum or Average 0.320756E+10     0.301074E+10    
Minimum of Months 0.246421E+09 246.88   0.231020E+09 232.26  
Maximum of Months 0.273947E+09 246.88   0.255955E+09 232.26  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.434056E+09 392.73 01-JAN-19:10 0.261068E+09 237.06 01-JAN-08:09
February 0.391995E+09 392.73 01-FEB-20:10 0.235798E+09 237.06 01-FEB-07:10
March 0.430607E+09 392.73 01-MAR-20:10 0.260708E+09 237.06 01-MAR-07:10
April 0.420554E+09 392.73 01-APR-18:10 0.252705E+09 237.06 01-APR-07:10
May 0.432331E+09 392.73 01-MAY-19:10 0.260888E+09 237.06 01-MAY-06:10
June 0.417218E+09 392.73 01-JUN-19:10 0.252344E+09 237.06 01-JUN-06:10
July 0.435725E+09 392.73 01-JUL-18:10 0.261248E+09 237.06 01-JUL-07:10
August 0.430607E+09 392.73 01-AUG-19:10 0.260708E+09 237.06 01-AUG-06:10
September 0.420667E+09 392.73 01-SEP-19:10 0.252705E+09 237.06 01-SEP-06:10
October 0.434000E+09 392.73 01-OCT-18:10 0.261068E+09 237.06 01-OCT-07:10
November 0.418886E+09 392.73 01-NOV-19:10 0.252524E+09 237.06 01-NOV-06:10
December 0.435781E+09 392.73 01-DEC-20:10 0.261248E+09 237.06 01-DEC-07:10
             
Annual Sum or Average 0.510243E+10     0.307301E+10    
Minimum of Months 0.391995E+09 392.73   0.235798E+09 237.06  
Maximum of Months 0.435781E+09 392.73   0.261248E+09 237.06  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.434005E+09 392.68 01-JAN-19:10 0.261038E+09 237.03 01-JAN-08:09
February 0.391949E+09 392.68 01-FEB-20:10 0.235770E+09 237.03 01-FEB-07:10
March 0.430556E+09 392.68 01-MAR-20:10 0.260677E+09 237.03 01-MAR-07:10
April 0.420505E+09 392.68 01-APR-18:10 0.252675E+09 237.03 01-APR-07:10
May 0.432281E+09 392.68 01-MAY-19:10 0.260857E+09 237.03 01-MAY-06:10
June 0.417169E+09 392.68 01-JUN-19:10 0.252315E+09 237.03 01-JUN-06:10
July 0.435674E+09 392.68 01-JUL-18:10 0.261218E+09 237.03 01-JUL-07:10
August 0.430556E+09 392.68 01-AUG-19:10 0.260677E+09 237.03 01-AUG-06:10
September 0.420618E+09 392.68 01-SEP-19:10 0.252675E+09 237.03 01-SEP-06:10
October 0.433949E+09 392.68 01-OCT-18:10 0.261038E+09 237.03 01-OCT-07:10
November 0.418837E+09 392.68 01-NOV-19:10 0.252495E+09 237.03 01-NOV-06:10
December 0.435730E+09 392.68 01-DEC-20:10 0.261218E+09 237.03 01-DEC-07:10
             
Annual Sum or Average 0.510183E+10     0.307265E+10    
Minimum of Months 0.391949E+09 392.68   0.235770E+09 237.03  
Maximum of Months 0.435730E+09 392.68   0.261218E+09 237.03  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY []
January 0.133160E+10 1282.60 02-JAN-20:10 0.00 0.00
February 0.120231E+10 1282.60 01-FEB-20:10 0.00 0.00
March 0.133570E+10 1282.60 01-MAR-20:10 0.00 0.00
April 0.128645E+10 1282.60 03-APR-19:10 0.00 0.00
May 0.133391E+10 1282.60 01-MAY-19:10 0.00 0.00
June 0.129235E+10 1282.60 01-JUN-19:10 0.00 0.00
July 0.132801E+10 1282.60 03-JUL-19:10 0.00 0.00
August 0.133622E+10 1282.60 01-AUG-19:10 0.00 0.00
September 0.128696E+10 1282.60 01-SEP-19:10 0.00 0.00
October 0.133109E+10 1282.60 02-OCT-19:10 0.00 0.00
November 0.129132E+10 1282.60 01-NOV-19:10 0.00 0.00
December 0.132801E+10 1282.60 01-DEC-20:10 0.00 0.00
           
Annual Sum or Average 0.156839E+11     0.00 0.00
Minimum of Months 0.120231E+10 1282.60   0.00 0.00
Maximum of Months 0.133622E+10 1282.60   0.00 0.00



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.434056E+09 392.73 01-JAN-19:10 0.261068E+09 237.06 01-JAN-08:09
February 0.391995E+09 392.73 01-FEB-20:10 0.235798E+09 237.06 01-FEB-07:10
March 0.430607E+09 392.73 01-MAR-20:10 0.260708E+09 237.06 01-MAR-07:10
April 0.420554E+09 392.73 01-APR-18:10 0.252705E+09 237.06 01-APR-07:10
May 0.432331E+09 392.73 01-MAY-19:10 0.260888E+09 237.06 01-MAY-06:10
June 0.417218E+09 392.73 01-JUN-19:10 0.252344E+09 237.06 01-JUN-06:10
July 0.435725E+09 392.73 01-JUL-18:10 0.261248E+09 237.06 01-JUL-07:10
August 0.430607E+09 392.73 01-AUG-19:10 0.260708E+09 237.06 01-AUG-06:10
September 0.420667E+09 392.73 01-SEP-19:10 0.252705E+09 237.06 01-SEP-06:10
October 0.434000E+09 392.73 01-OCT-18:10 0.261068E+09 237.06 01-OCT-07:10
November 0.418886E+09 392.73 01-NOV-19:10 0.252524E+09 237.06 01-NOV-06:10
December 0.435781E+09 392.73 01-DEC-20:10 0.261248E+09 237.06 01-DEC-07:10
             
Annual Sum or Average 0.510243E+10     0.307301E+10    
Minimum of Months 0.391995E+09 392.73   0.235798E+09 237.06  
Maximum of Months 0.435781E+09 392.73   0.261248E+09 237.06  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.434005E+09 392.68 01-JAN-19:10 0.261038E+09 237.03 01-JAN-08:09
February 0.391949E+09 392.68 01-FEB-20:10 0.235770E+09 237.03 01-FEB-07:10
March 0.430556E+09 392.68 01-MAR-20:10 0.260677E+09 237.03 01-MAR-07:10
April 0.420505E+09 392.68 01-APR-18:10 0.252675E+09 237.03 01-APR-07:10
May 0.432281E+09 392.68 01-MAY-19:10 0.260857E+09 237.03 01-MAY-06:10
June 0.417169E+09 392.68 01-JUN-19:10 0.252315E+09 237.03 01-JUN-06:10
July 0.435674E+09 392.68 01-JUL-18:10 0.261218E+09 237.03 01-JUL-07:10
August 0.430556E+09 392.68 01-AUG-19:10 0.260677E+09 237.03 01-AUG-06:10
September 0.420618E+09 392.68 01-SEP-19:10 0.252675E+09 237.03 01-SEP-06:10
October 0.433949E+09 392.68 01-OCT-18:10 0.261038E+09 237.03 01-OCT-07:10
November 0.418837E+09 392.68 01-NOV-19:10 0.252495E+09 237.03 01-NOV-06:10
December 0.435730E+09 392.68 01-DEC-20:10 0.261218E+09 237.03 01-DEC-07:10
             
Annual Sum or Average 0.510183E+10     0.307265E+10    
Minimum of Months 0.391949E+09 392.68   0.235770E+09 237.03  
Maximum of Months 0.435730E+09 392.68   0.261218E+09 237.03  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.272862E+09 246.88 01-JAN-19:10 0.255778E+09 232.26 01-JAN-08:09
February 0.246421E+09 246.88 01-FEB-20:10 0.231020E+09 232.26 01-FEB-07:10
March 0.270694E+09 246.88 01-MAR-20:10 0.255425E+09 232.26 01-MAR-07:10
April 0.264375E+09 246.88 01-APR-18:10 0.247584E+09 232.26 01-APR-07:10
May 0.271778E+09 246.88 01-MAY-19:10 0.255602E+09 232.26 01-MAY-06:10
June 0.262277E+09 246.88 01-JUN-19:10 0.247231E+09 232.26 01-JUN-06:10
July 0.273911E+09 246.88 01-JUL-18:10 0.255955E+09 232.26 01-JUL-07:10
August 0.270694E+09 246.88 01-AUG-19:10 0.255425E+09 232.26 01-AUG-06:10
September 0.264446E+09 246.88 01-SEP-19:10 0.247584E+09 232.26 01-SEP-06:10
October 0.272827E+09 246.88 01-OCT-18:10 0.255778E+09 232.26 01-OCT-07:10
November 0.263326E+09 246.88 01-NOV-19:10 0.247408E+09 232.26 01-NOV-06:10
December 0.273947E+09 246.88 01-DEC-20:10 0.255955E+09 232.26 01-DEC-07:10
             
Annual Sum or Average 0.320756E+10     0.301074E+10    
Minimum of Months 0.246421E+09 246.88   0.231020E+09 232.26  
Maximum of Months 0.273947E+09 246.88   0.255955E+09 232.26  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.396945E+10 3823.39 02-JAN-20:10 0.149358E+11 6747.90 01-JAN-07:10
February 0.358405E+10 3823.39 01-FEB-20:10 0.134904E+11 6747.90 01-FEB-07:10
March 0.398168E+10 3823.39 01-MAR-20:10 0.149358E+11 6747.90 01-MAR-07:10
April 0.383486E+10 3823.39 03-APR-19:10 0.144540E+11 6747.90 01-APR-06:10
May 0.397633E+10 3823.39 01-MAY-19:10 0.149358E+11 6747.90 01-MAY-06:10
June 0.385245E+10 3823.39 01-JUN-19:10 0.144540E+11 6747.90 01-JUN-06:10
July 0.395874E+10 3823.39 03-JUL-19:10 0.149358E+11 6747.90 01-JUL-06:10
August 0.398321E+10 3823.39 01-AUG-19:10 0.149358E+11 6747.90 01-AUG-06:10
September 0.383639E+10 3823.39 01-SEP-19:10 0.144540E+11 6747.90 01-SEP-06:10
October 0.396792E+10 3823.39 02-OCT-19:10 0.149358E+11 6747.90 01-OCT-06:10
November 0.384939E+10 3823.39 01-NOV-19:10 0.144540E+11 6747.90 01-NOV-06:10
December 0.395874E+10 3823.39 01-DEC-20:10 0.149358E+11 6747.90 01-DEC-07:10
             
Annual Sum or Average 0.467532E+11     0.175857E+12    
Minimum of Months 0.358405E+10 3823.39   0.134904E+11 6747.90  
Maximum of Months 0.398321E+10 3823.39   0.149358E+11 6747.90  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.396945E+10 3823.39 02-JAN-20:10 0.149358E+11 6747.90 01-JAN-07:10
February 0.358405E+10 3823.39 01-FEB-20:10 0.134904E+11 6747.90 01-FEB-07:10
March 0.398168E+10 3823.39 01-MAR-20:10 0.149358E+11 6747.90 01-MAR-07:10
April 0.383486E+10 3823.39 03-APR-19:10 0.144540E+11 6747.90 01-APR-06:10
May 0.397633E+10 3823.39 01-MAY-19:10 0.149358E+11 6747.90 01-MAY-06:10
June 0.385245E+10 3823.39 01-JUN-19:10 0.144540E+11 6747.90 01-JUN-06:10
July 0.395874E+10 3823.39 03-JUL-19:10 0.149358E+11 6747.90 01-JUL-06:10
August 0.398321E+10 3823.39 01-AUG-19:10 0.149358E+11 6747.90 01-AUG-06:10
September 0.383639E+10 3823.39 01-SEP-19:10 0.144540E+11 6747.90 01-SEP-06:10
October 0.396792E+10 3823.39 02-OCT-19:10 0.149358E+11 6747.90 01-OCT-06:10
November 0.384939E+10 3823.39 01-NOV-19:10 0.144540E+11 6747.90 01-NOV-06:10
December 0.395874E+10 3823.39 01-DEC-20:10 0.149358E+11 6747.90 01-DEC-07:10
             
Annual Sum or Average 0.467532E+11     0.175857E+12    
Minimum of Months 0.358405E+10 3823.39   0.134904E+11 6747.90  
Maximum of Months 0.398321E+10 3823.39   0.149358E+11 6747.90  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.105977E+10 1020.78 02-JAN-20:10 0.373720E+11 16686.59 01-JAN-07:10
February 0.956878E+09 1020.78 01-FEB-20:10 0.337554E+11 16686.59 01-FEB-07:10
March 0.106304E+10 1020.78 01-MAR-20:10 0.373720E+11 16686.59 01-MAR-07:10
April 0.102384E+10 1020.78 03-APR-19:10 0.361665E+11 16686.59 01-APR-06:10
May 0.106161E+10 1020.78 01-MAY-19:10 0.373720E+11 16686.59 01-MAY-06:10
June 0.102854E+10 1020.78 01-JUN-19:10 0.361665E+11 16686.59 01-JUN-06:10
July 0.105691E+10 1020.78 03-JUL-19:10 0.373720E+11 16686.59 01-JUL-06:10
August 0.106345E+10 1020.78 01-AUG-19:10 0.373720E+11 16686.59 01-AUG-06:10
September 0.102425E+10 1020.78 01-SEP-19:10 0.361665E+11 16686.59 01-SEP-06:10
October 0.105936E+10 1020.78 02-OCT-19:10 0.373720E+11 16686.59 01-OCT-06:10
November 0.102772E+10 1020.78 01-NOV-19:10 0.361665E+11 16686.59 01-NOV-06:10
December 0.105691E+10 1020.78 01-DEC-20:10 0.373720E+11 16686.59 01-DEC-07:10
             
Annual Sum or Average 0.124823E+11     0.440025E+12    
Minimum of Months 0.956878E+09 1020.78   0.337554E+11 16686.59  
Maximum of Months 0.106345E+10 1020.78   0.373720E+11 16686.59  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY []
January 0.140929E+10 1357.44 02-JAN-20:10 0.00 0.00
February 0.127246E+10 1357.44 01-FEB-20:10 0.00 0.00
March 0.141364E+10 1357.44 01-MAR-20:10 0.00 0.00
April 0.136151E+10 1357.44 03-APR-19:10 0.00 0.00
May 0.141173E+10 1357.44 01-MAY-19:10 0.00 0.00
June 0.136775E+10 1357.44 01-JUN-19:10 0.00 0.00
July 0.140549E+10 1357.44 03-JUL-19:10 0.00 0.00
August 0.141418E+10 1357.44 01-AUG-19:10 0.00 0.00
September 0.136205E+10 1357.44 01-SEP-19:10 0.00 0.00
October 0.140875E+10 1357.44 02-OCT-19:10 0.00 0.00
November 0.136667E+10 1357.44 01-NOV-19:10 0.00 0.00
December 0.140549E+10 1357.44 01-DEC-20:10 0.00 0.00
           
Annual Sum or Average 0.165990E+11     0.00 0.00
Minimum of Months 0.127246E+10 1357.44   0.00 0.00
Maximum of Months 0.141418E+10 1357.44   0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.195762E+11 0.140333E+11 0.127587E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.176991E+11 0.126708E+11 0.115208E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.196682E+11 0.140766E+11 0.127855E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.189781E+11 0.135575E+11 0.123314E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.196176E+11 0.140576E+11 0.127741E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.190195E+11 0.136197E+11 0.123716E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.195762E+11 0.139955E+11 0.127338E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.196590E+11 0.140820E+11 0.127894E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.189689E+11 0.135629E+11 0.123352E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.195854E+11 0.140279E+11 0.127549E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.189367E+11 0.136089E+11 0.123659E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.195762E+11 0.139955E+11 0.127338E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.230861E+12 0.165288E+12 0.150255E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.176991E+11 0.126708E+11 0.115208E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.196682E+11 0.140820E+11 0.127894E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.199054E+10 0.713551E+09 0.864900E+09 0.00 0.00 0.00 0.00 44645897.07 0.157740E+09
February 0.179968E+10 0.644271E+09 0.780982E+09 0.00 0.00 0.00 0.00 69639015.44 96006745.50
March 0.199990E+10 0.715750E+09 0.866718E+09 0.00 0.00 0.00 0.00 0.100495E+09 83073488.68
April 0.192973E+10 0.689358E+09 0.835931E+09 0.00 0.00 0.00 0.00 0.168425E+09 9790363.41
May 0.199475E+10 0.714788E+09 0.865939E+09 0.00 0.00 0.00 0.00 0.292636E+09 96878.85
June 0.193394E+10 0.692519E+09 0.838659E+09 0.00 0.00 0.00 0.00 0.347329E+09 0.00
July 0.199054E+10 0.711626E+09 0.863211E+09 0.00 0.00 0.00 0.00 0.377031E+09 0.00
August 0.199896E+10 0.716025E+09 0.866978E+09 0.00 0.00 0.00 0.00 0.367784E+09 0.00
September 0.192879E+10 0.689633E+09 0.836191E+09 0.00 0.00 0.00 0.00 0.319441E+09 0.00
October 0.199148E+10 0.713276E+09 0.864640E+09 0.00 0.00 0.00 0.00 0.264042E+09 1675.56
November 0.192552E+10 0.691970E+09 0.838269E+09 0.00 0.00 0.00 0.00 0.150431E+09 37545309.04
December 0.199054E+10 0.711626E+09 0.863211E+09 0.00 0.00 0.00 0.00 61220743.61 0.127447E+09
                   
Annual Sum or Average 0.234744E+11 0.840439E+10 0.101856E+11 0.00 0.00 0.00 0.00 0.256312E+10 0.511702E+09
Minimum of Months 0.179968E+10 0.644271E+09 0.780982E+09 0.00 0.00 0.00 0.00 44645897.07 0.00
Maximum of Months 0.199990E+10 0.716025E+09 0.866978E+09 0.00 0.00 0.00 0.00 0.377031E+09 0.157740E+09



Table of Contents

Report: SpaceGainsMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.230505E+10 0.826294E+09 0.100156E+10 0.00 0.00 0.00 0.00 21094679.63 59769494.63
February 0.208403E+10 0.746069E+09 0.904380E+09 0.00 0.00 0.00 0.00 31243028.15 37694480.00
March 0.231589E+10 0.828841E+09 0.100366E+10 0.00 0.00 0.00 0.00 40409446.33 32691382.93
April 0.223463E+10 0.798279E+09 0.968011E+09 0.00 0.00 0.00 0.00 65071506.84 4107781.10
May 0.230993E+10 0.827727E+09 0.100276E+10 0.00 0.00 0.00 0.00 0.111584E+09 44253.73
June 0.223950E+10 0.801940E+09 0.971170E+09 0.00 0.00 0.00 0.00 0.133523E+09 0.00
July 0.230505E+10 0.824066E+09 0.999601E+09 0.00 0.00 0.00 0.00 0.146534E+09 0.00
August 0.231480E+10 0.829160E+09 0.100396E+10 0.00 0.00 0.00 0.00 0.143864E+09 0.00
September 0.223354E+10 0.798597E+09 0.968312E+09 0.00 0.00 0.00 0.00 0.128768E+09 0.00
October 0.230614E+10 0.825976E+09 0.100126E+10 0.00 0.00 0.00 0.00 0.109546E+09 27.43
November 0.222975E+10 0.801303E+09 0.970719E+09 0.00 0.00 0.00 0.00 64469528.73 14556003.92
December 0.230505E+10 0.824066E+09 0.999601E+09 0.00 0.00 0.00 0.00 28680700.03 48693995.83
                   
Annual Sum or Average 0.271834E+11 0.973232E+10 0.117950E+11 0.00 0.00 0.00 0.00 0.102479E+10 0.197557E+09
Minimum of Months 0.208403E+10 0.746069E+09 0.904380E+09 0.00 0.00 0.00 0.00 21094679.63 0.00
Maximum of Months 0.231589E+10 0.829160E+09 0.100396E+10 0.00 0.00 0.00 0.00 0.146534E+09 59769494.63



Table of Contents

Report: SpaceGainsMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.487480E+09 0.154452E+10 0.105898E+10 0.00 0.00 0.00 0.00 51235721.69 0.138484E+09
February 0.440737E+09 0.139456E+10 0.956227E+09 0.00 0.00 0.00 0.00 75786952.87 86613581.84
March 0.489771E+09 0.154928E+10 0.106120E+10 0.00 0.00 0.00 0.00 99805659.76 75336077.34
April 0.472586E+09 0.149215E+10 0.102351E+10 0.00 0.00 0.00 0.00 0.160517E+09 9005226.42
May 0.488511E+09 0.154719E+10 0.106025E+10 0.00 0.00 0.00 0.00 0.269741E+09 87968.19
June 0.473617E+09 0.149899E+10 0.102685E+10 0.00 0.00 0.00 0.00 0.318281E+09 0.00
July 0.487480E+09 0.154035E+10 0.105691E+10 0.00 0.00 0.00 0.00 0.349122E+09 0.00
August 0.489542E+09 0.154987E+10 0.106152E+10 0.00 0.00 0.00 0.00 0.345427E+09 0.00
September 0.472357E+09 0.149274E+10 0.102382E+10 0.00 0.00 0.00 0.00 0.310232E+09 0.00
October 0.487709E+09 0.154392E+10 0.105866E+10 0.00 0.00 0.00 0.00 0.267411E+09 0.00
November 0.471555E+09 0.149780E+10 0.102637E+10 0.00 0.00 0.00 0.00 0.157575E+09 33258658.19
December 0.487480E+09 0.154035E+10 0.105691E+10 0.00 0.00 0.00 0.00 70211218.76 0.112357E+09
                   
Annual Sum or Average 0.574883E+10 0.181917E+11 0.124712E+11 0.00 0.00 0.00 0.00 0.247535E+10 0.455142E+09
Minimum of Months 0.440737E+09 0.139456E+10 0.956227E+09 0.00 0.00 0.00 0.00 51235721.69 0.00
Maximum of Months 0.489771E+09 0.154987E+10 0.106152E+10 0.00 0.00 0.00 0.00 0.349122E+09 0.138484E+09



Table of Contents

Report: SpaceGainsMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.374985E+09 0.283535E+09 0.305485E+09 0.00 0.00 0.00 0.00 29826639.80 79800516.74
February 0.339028E+09 0.256006E+09 0.275845E+09 0.00 0.00 0.00 0.00 44142205.00 49749377.64
March 0.376747E+09 0.284409E+09 0.306128E+09 0.00 0.00 0.00 0.00 58360868.55 43345180.98
April 0.363528E+09 0.273921E+09 0.295253E+09 0.00 0.00 0.00 0.00 93906400.59 5148519.48
May 0.375778E+09 0.284026E+09 0.305852E+09 0.00 0.00 0.00 0.00 0.157692E+09 50779.28
June 0.364321E+09 0.275178E+09 0.296217E+09 0.00 0.00 0.00 0.00 0.185881E+09 0.00
July 0.374985E+09 0.282770E+09 0.304889E+09 0.00 0.00 0.00 0.00 0.203821E+09 0.00
August 0.376571E+09 0.284518E+09 0.306219E+09 0.00 0.00 0.00 0.00 0.201343E+09 0.00
September 0.363352E+09 0.274031E+09 0.295345E+09 0.00 0.00 0.00 0.00 0.181094E+09 0.00
October 0.375161E+09 0.283425E+09 0.305393E+09 0.00 0.00 0.00 0.00 0.156133E+09 0.00
November 0.362735E+09 0.274959E+09 0.296079E+09 0.00 0.00 0.00 0.00 92047085.72 19102422.70
December 0.374985E+09 0.282770E+09 0.304889E+09 0.00 0.00 0.00 0.00 40950644.75 64671470.87
                   
Annual Sum or Average 0.442217E+10 0.333955E+10 0.359760E+10 0.00 0.00 0.00 0.00 0.144520E+10 0.261868E+09
Minimum of Months 0.339028E+09 0.256006E+09 0.275845E+09 0.00 0.00 0.00 0.00 29826639.80 0.00
Maximum of Months 0.376747E+09 0.284518E+09 0.306219E+09 0.00 0.00 0.00 0.00 0.203821E+09 79800516.74



Table of Contents

Report: SpaceGainsMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.154405E+10 0.350256E+09 0.576866E+10 0.501157E+11 0.00 0.00 0.00 64391866.68 0.210506E+09
February 0.139600E+10 0.316249E+09 0.520895E+10 0.452532E+11 0.00 0.00 0.00 95866387.03 0.133870E+09
March 0.155131E+10 0.351336E+09 0.578079E+10 0.502211E+11 0.00 0.00 0.00 0.123199E+09 0.114948E+09
April 0.149688E+10 0.338381E+09 0.557545E+10 0.484372E+11 0.00 0.00 0.00 0.202297E+09 16103501.72
May 0.154732E+10 0.350863E+09 0.577559E+10 0.501759E+11 0.00 0.00 0.00 0.352728E+09 145365.12
June 0.150015E+10 0.339933E+09 0.559364E+10 0.485952E+11 0.00 0.00 0.00 0.426756E+09 0.00
July 0.154405E+10 0.349311E+09 0.575740E+10 0.500179E+11 0.00 0.00 0.00 0.472375E+09 221176.60
August 0.155059E+10 0.351471E+09 0.578252E+10 0.502361E+11 0.00 0.00 0.00 0.460499E+09 0.00
September 0.149615E+10 0.338516E+09 0.557718E+10 0.484522E+11 0.00 0.00 0.00 0.413441E+09 13282.21
October 0.154478E+10 0.350121E+09 0.576693E+10 0.501006E+11 0.00 0.00 0.00 0.347577E+09 11100.17
November 0.149361E+10 0.339663E+09 0.559104E+10 0.485726E+11 0.00 0.00 0.00 0.199702E+09 51553522.30
December 0.154405E+10 0.349311E+09 0.575740E+10 0.500179E+11 0.00 0.00 0.00 88855387.80 0.172119E+09
                   
Annual Sum or Average 0.182090E+11 0.412541E+10 0.679355E+11 0.590196E+12 0.00 0.00 0.00 0.324769E+10 0.699491E+09
Minimum of Months 0.139600E+10 0.316249E+09 0.520895E+10 0.452532E+11 0.00 0.00 0.00 64391866.68 0.00
Maximum of Months 0.155131E+10 0.351471E+09 0.578252E+10 0.502361E+11 0.00 0.00 0.00 0.472375E+09 0.210506E+09



Table of Contents

Report: SpaceGainsMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.261570E+11 0.226040E+10 0.121771E+10 0.00 0.00 0.00 0.00 96960621.59 0.370772E+09
February 0.236489E+11 0.204093E+10 0.109956E+10 0.00 0.00 0.00 0.00 0.150561E+09 0.232581E+09
March 0.262800E+11 0.226736E+10 0.122027E+10 0.00 0.00 0.00 0.00 0.202602E+09 0.197977E+09
April 0.253579E+11 0.218376E+10 0.117692E+10 0.00 0.00 0.00 0.00 0.345753E+09 28953507.97
May 0.262123E+11 0.226431E+10 0.121917E+10 0.00 0.00 0.00 0.00 0.606351E+09 794560.24
June 0.254132E+11 0.219377E+10 0.118076E+10 0.00 0.00 0.00 0.00 0.728152E+09 0.00
July 0.261570E+11 0.225430E+10 0.121533E+10 0.00 0.00 0.00 0.00 0.803271E+09 0.00
August 0.262677E+11 0.226823E+10 0.122063E+10 0.00 0.00 0.00 0.00 0.781162E+09 0.00
September 0.253456E+11 0.218463E+10 0.117729E+10 0.00 0.00 0.00 0.00 0.683898E+09 0.00
October 0.261693E+11 0.225952E+10 0.121734E+10 0.00 0.00 0.00 0.00 0.558331E+09 824212.61
November 0.253025E+11 0.219203E+10 0.118021E+10 0.00 0.00 0.00 0.00 0.317929E+09 96189335.82
December 0.261570E+11 0.225430E+10 0.121533E+10 0.00 0.00 0.00 0.00 0.130807E+09 0.301805E+09
                   
Annual Sum or Average 0.308468E+12 0.266236E+11 0.143405E+11 0.00 0.00 0.00 0.00 0.540578E+10 0.122990E+10
Minimum of Months 0.236489E+11 0.204093E+10 0.109956E+10 0.00 0.00 0.00 0.00 96960621.59 0.00
Maximum of Months 0.262800E+11 0.226823E+10 0.122063E+10 0.00 0.00 0.00 0.00 0.803271E+09 0.370772E+09



Table of Contents

Report: SpaceGainsMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.776503E+11 0.123020E+11 0.126520E+11 0.00 0.00 0.00 0.00 0.324437E+09 0.103667E+10
February 0.702046E+11 0.111075E+11 0.114244E+11 0.00 0.00 0.00 0.00 0.481525E+09 0.660496E+09
March 0.780153E+11 0.123399E+11 0.126786E+11 0.00 0.00 0.00 0.00 0.613042E+09 0.565590E+09
April 0.752779E+11 0.118849E+11 0.122282E+11 0.00 0.00 0.00 0.00 0.100781E+10 83032375.09
May 0.778146E+11 0.123233E+11 0.126672E+11 0.00 0.00 0.00 0.00 0.174552E+10 2421896.17
June 0.754422E+11 0.119394E+11 0.122682E+11 0.00 0.00 0.00 0.00 0.209988E+10 0.00
July 0.776503E+11 0.122688E+11 0.126273E+11 0.00 0.00 0.00 0.00 0.231865E+10 0.00
August 0.779788E+11 0.123446E+11 0.126824E+11 0.00 0.00 0.00 0.00 0.227020E+10 0.00
September 0.752414E+11 0.118896E+11 0.122320E+11 0.00 0.00 0.00 0.00 0.202335E+10 0.00
October 0.776868E+11 0.122972E+11 0.126482E+11 0.00 0.00 0.00 0.00 0.170077E+10 1337494.08
November 0.751137E+11 0.119299E+11 0.122624E+11 0.00 0.00 0.00 0.00 0.992923E+09 0.269937E+09
December 0.776503E+11 0.122688E+11 0.126273E+11 0.00 0.00 0.00 0.00 0.435226E+09 0.849278E+09
                   
Annual Sum or Average 0.915726E+12 0.144896E+12 0.148998E+12 0.00 0.00 0.00 0.00 0.160133E+11 0.346876E+10
Minimum of Months 0.702046E+11 0.111075E+11 0.114244E+11 0.00 0.00 0.00 0.00 0.324437E+09 0.00
Maximum of Months 0.780153E+11 0.123446E+11 0.126824E+11 0.00 0.00 0.00 0.00 0.231865E+10 0.103667E+10



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.434056E+09 0.261068E+09 0.00 0.00 0.00 0.00 21471652.27 98310176.11
February 0.273974E+09 0.391995E+09 0.235798E+09 0.00 0.00 0.00 0.00 32908225.61 59567488.82
March 0.303685E+09 0.430607E+09 0.260708E+09 0.00 0.00 0.00 0.00 46684966.27 52727500.53
April 0.293479E+09 0.420554E+09 0.252705E+09 0.00 0.00 0.00 0.00 81365315.93 6798667.60
May 0.303504E+09 0.432331E+09 0.260888E+09 0.00 0.00 0.00 0.00 0.151545E+09 294438.93
June 0.293842E+09 0.417218E+09 0.252344E+09 0.00 0.00 0.00 0.00 0.186005E+09 17572.21
July 0.303141E+09 0.435725E+09 0.261248E+09 0.00 0.00 0.00 0.00 0.205970E+09 36552.25
August 0.303685E+09 0.430607E+09 0.260708E+09 0.00 0.00 0.00 0.00 0.201495E+09 117337.12
September 0.293479E+09 0.420667E+09 0.252705E+09 0.00 0.00 0.00 0.00 0.179513E+09 0.00
October 0.303322E+09 0.434000E+09 0.261068E+09 0.00 0.00 0.00 0.00 0.148811E+09 89292.77
November 0.293661E+09 0.418886E+09 0.252524E+09 0.00 0.00 0.00 0.00 81946321.32 24197022.74
December 0.303141E+09 0.435781E+09 0.261248E+09 0.00 0.00 0.00 0.00 31927351.95 79925538.02
                   
Annual Sum or Average 0.357224E+10 0.510243E+10 0.307301E+10 0.00 0.00 0.00 0.00 0.136964E+10 0.322082E+09
Minimum of Months 0.273974E+09 0.391995E+09 0.235798E+09 0.00 0.00 0.00 0.00 21471652.27 0.00
Maximum of Months 0.303685E+09 0.435781E+09 0.261248E+09 0.00 0.00 0.00 0.00 0.205970E+09 98310176.11



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.434005E+09 0.261038E+09 0.00 0.00 0.00 0.00 22648199.99 94762724.16
February 0.273974E+09 0.391949E+09 0.235770E+09 0.00 0.00 0.00 0.00 34083509.87 58290909.85
March 0.303685E+09 0.430556E+09 0.260677E+09 0.00 0.00 0.00 0.00 47288873.43 51456699.14
April 0.293479E+09 0.420505E+09 0.252675E+09 0.00 0.00 0.00 0.00 81564436.75 6745032.86
May 0.303504E+09 0.432281E+09 0.260857E+09 0.00 0.00 0.00 0.00 0.151507E+09 295133.15
June 0.293842E+09 0.417169E+09 0.252315E+09 0.00 0.00 0.00 0.00 0.185915E+09 17574.28
July 0.303141E+09 0.435674E+09 0.261218E+09 0.00 0.00 0.00 0.00 0.205909E+09 36904.87
August 0.303685E+09 0.430556E+09 0.260677E+09 0.00 0.00 0.00 0.00 0.201512E+09 113751.78
September 0.293479E+09 0.420618E+09 0.252675E+09 0.00 0.00 0.00 0.00 0.179671E+09 0.00
October 0.303322E+09 0.433949E+09 0.261038E+09 0.00 0.00 0.00 0.00 0.149240E+09 80076.30
November 0.293661E+09 0.418837E+09 0.252495E+09 0.00 0.00 0.00 0.00 82876903.68 23628671.06
December 0.303141E+09 0.435730E+09 0.261218E+09 0.00 0.00 0.00 0.00 32813034.22 77132126.49
                   
Annual Sum or Average 0.357224E+10 0.510183E+10 0.307265E+10 0.00 0.00 0.00 0.00 0.137503E+10 0.312560E+09
Minimum of Months 0.273974E+09 0.391949E+09 0.235770E+09 0.00 0.00 0.00 0.00 22648199.99 0.00
Maximum of Months 0.303685E+09 0.435730E+09 0.261218E+09 0.00 0.00 0.00 0.00 0.205909E+09 94762724.16



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.272788E+09 0.255708E+09 0.00 0.00 0.00 0.00 2961711.86 40156187.93
February 0.00 0.246354E+09 0.230956E+09 0.00 0.00 0.00 0.00 4502982.25 25850631.05
March 0.00 0.270620E+09 0.255355E+09 0.00 0.00 0.00 0.00 5470177.50 22547440.48
April 0.00 0.264302E+09 0.247516E+09 0.00 0.00 0.00 0.00 12667654.52 6328049.87
May 0.00 0.271704E+09 0.255532E+09 0.00 0.00 0.00 0.00 28316427.91 799395.15
June 0.00 0.262205E+09 0.247163E+09 0.00 0.00 0.00 0.00 37784382.01 7264.87
July 0.00 0.273836E+09 0.255885E+09 0.00 0.00 0.00 0.00 43045147.21 113849.83
August 0.00 0.270620E+09 0.255355E+09 0.00 0.00 0.00 0.00 41728816.36 118763.31
September 0.00 0.264373E+09 0.247516E+09 0.00 0.00 0.00 0.00 36051781.47 51364.94
October 0.00 0.272752E+09 0.255708E+09 0.00 0.00 0.00 0.00 27569033.17 696806.28
November 0.00 0.263254E+09 0.247340E+09 0.00 0.00 0.00 0.00 14080198.92 12522152.50
December 0.00 0.273872E+09 0.255885E+09 0.00 0.00 0.00 0.00 4383774.47 33429656.05
                   
Annual Sum or Average 0.00 0.320668E+10 0.300992E+10 0.00 0.00 0.00 0.00 0.258562E+09 0.142622E+09
Minimum of Months 0.00 0.246354E+09 0.230956E+09 0.00 0.00 0.00 0.00 2961711.86 7264.87
Maximum of Months 0.00 0.273872E+09 0.255885E+09 0.00 0.00 0.00 0.00 43045147.21 40156187.93



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.272862E+09 0.255778E+09 0.00 0.00 0.00 0.00 6959432.70 26337319.10
February 0.273974E+09 0.246421E+09 0.231020E+09 0.00 0.00 0.00 0.00 10402598.47 16279071.46
March 0.303685E+09 0.270694E+09 0.255425E+09 0.00 0.00 0.00 0.00 14043190.43 14255936.39
April 0.293479E+09 0.264375E+09 0.247584E+09 0.00 0.00 0.00 0.00 23630031.21 1822995.09
May 0.303504E+09 0.271778E+09 0.255602E+09 0.00 0.00 0.00 0.00 42765779.22 63687.16
June 0.293842E+09 0.262277E+09 0.247231E+09 0.00 0.00 0.00 0.00 52246379.44 4692.71
July 0.303141E+09 0.273911E+09 0.255955E+09 0.00 0.00 0.00 0.00 57783576.22 7377.84
August 0.303685E+09 0.270694E+09 0.255425E+09 0.00 0.00 0.00 0.00 56696257.87 13355.94
September 0.293479E+09 0.264446E+09 0.247584E+09 0.00 0.00 0.00 0.00 50597640.06 0.00
October 0.303322E+09 0.272827E+09 0.255778E+09 0.00 0.00 0.00 0.00 42354710.48 17665.71
November 0.293661E+09 0.263326E+09 0.247408E+09 0.00 0.00 0.00 0.00 23982400.37 6530020.88
December 0.303141E+09 0.273947E+09 0.255955E+09 0.00 0.00 0.00 0.00 9803992.48 21412505.92
                   
Annual Sum or Average 0.357224E+10 0.320756E+10 0.301074E+10 0.00 0.00 0.00 0.00 0.391266E+09 86744628.19
Minimum of Months 0.273974E+09 0.246421E+09 0.231020E+09 0.00 0.00 0.00 0.00 6959432.70 0.00
Maximum of Months 0.303685E+09 0.273947E+09 0.255955E+09 0.00 0.00 0.00 0.00 57783576.22 26337319.10



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.434056E+09 0.261068E+09 0.00 0.00 0.00 0.00 21267325.92 99534580.70
February 0.273974E+09 0.391995E+09 0.235798E+09 0.00 0.00 0.00 0.00 32680498.69 60458981.08
March 0.303685E+09 0.430607E+09 0.260708E+09 0.00 0.00 0.00 0.00 46360884.16 54294937.66
April 0.293479E+09 0.420554E+09 0.252705E+09 0.00 0.00 0.00 0.00 80837961.58 7133933.34
May 0.303504E+09 0.432331E+09 0.260888E+09 0.00 0.00 0.00 0.00 0.151073E+09 305529.61
June 0.293842E+09 0.417218E+09 0.252344E+09 0.00 0.00 0.00 0.00 0.185524E+09 17584.66
July 0.303141E+09 0.435725E+09 0.261248E+09 0.00 0.00 0.00 0.00 0.205593E+09 38325.78
August 0.303685E+09 0.430607E+09 0.260708E+09 0.00 0.00 0.00 0.00 0.201185E+09 122003.72
September 0.293479E+09 0.420667E+09 0.252705E+09 0.00 0.00 0.00 0.00 0.179101E+09 0.00
October 0.303322E+09 0.434000E+09 0.261068E+09 0.00 0.00 0.00 0.00 0.148426E+09 115716.81
November 0.293661E+09 0.418886E+09 0.252524E+09 0.00 0.00 0.00 0.00 81682828.43 24614946.35
December 0.303141E+09 0.435781E+09 0.261248E+09 0.00 0.00 0.00 0.00 31811710.23 80253934.44
                   
Annual Sum or Average 0.357224E+10 0.510243E+10 0.307301E+10 0.00 0.00 0.00 0.00 0.136554E+10 0.326890E+09
Minimum of Months 0.273974E+09 0.391995E+09 0.235798E+09 0.00 0.00 0.00 0.00 21267325.92 0.00
Maximum of Months 0.303685E+09 0.435781E+09 0.261248E+09 0.00 0.00 0.00 0.00 0.205593E+09 99534580.70



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.434005E+09 0.261038E+09 0.00 0.00 0.00 0.00 21906020.56 95796392.60
February 0.273974E+09 0.391949E+09 0.235770E+09 0.00 0.00 0.00 0.00 33117960.34 59168845.47
March 0.303685E+09 0.430556E+09 0.260677E+09 0.00 0.00 0.00 0.00 46536822.22 53170467.48
April 0.293479E+09 0.420505E+09 0.252675E+09 0.00 0.00 0.00 0.00 80902040.46 7107517.33
May 0.303504E+09 0.432281E+09 0.260857E+09 0.00 0.00 0.00 0.00 0.151050E+09 306596.72
June 0.293842E+09 0.417169E+09 0.252315E+09 0.00 0.00 0.00 0.00 0.185480E+09 17583.90
July 0.303141E+09 0.435674E+09 0.261218E+09 0.00 0.00 0.00 0.00 0.205557E+09 38679.08
August 0.303685E+09 0.430556E+09 0.260677E+09 0.00 0.00 0.00 0.00 0.201191E+09 118498.97
September 0.293479E+09 0.420618E+09 0.252675E+09 0.00 0.00 0.00 0.00 0.179173E+09 0.00
October 0.303322E+09 0.433949E+09 0.261038E+09 0.00 0.00 0.00 0.00 0.148646E+09 108038.63
November 0.293661E+09 0.418837E+09 0.252495E+09 0.00 0.00 0.00 0.00 82328518.10 24101502.95
December 0.303141E+09 0.435730E+09 0.261218E+09 0.00 0.00 0.00 0.00 32610539.85 76890016.33
                   
Annual Sum or Average 0.357224E+10 0.510183E+10 0.307265E+10 0.00 0.00 0.00 0.00 0.136850E+10 0.316824E+09
Minimum of Months 0.273974E+09 0.391949E+09 0.235770E+09 0.00 0.00 0.00 0.00 21906020.56 0.00
Maximum of Months 0.303685E+09 0.435730E+09 0.261218E+09 0.00 0.00 0.00 0.00 0.205557E+09 95796392.60



Table of Contents

Report: SpaceGainsMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.385223E+10 0.133160E+10 0.00 0.00 0.00 0.00 0.00 31798537.74 0.114267E+09
February 0.348285E+10 0.120231E+10 0.00 0.00 0.00 0.00 0.00 47933247.15 72753097.73
March 0.387034E+10 0.133570E+10 0.00 0.00 0.00 0.00 0.00 60394202.69 62132797.68
April 0.373454E+10 0.128645E+10 0.00 0.00 0.00 0.00 0.00 98025620.20 10518975.56
May 0.386038E+10 0.133391E+10 0.00 0.00 0.00 0.00 0.00 0.173841E+09 399019.61
June 0.374269E+10 0.129235E+10 0.00 0.00 0.00 0.00 0.00 0.208698E+09 0.00
July 0.385223E+10 0.132801E+10 0.00 0.00 0.00 0.00 0.00 0.229149E+09 0.00
August 0.386853E+10 0.133622E+10 0.00 0.00 0.00 0.00 0.00 0.225564E+09 0.00
September 0.373273E+10 0.128696E+10 0.00 0.00 0.00 0.00 0.00 0.197954E+09 0.00
October 0.385404E+10 0.133109E+10 0.00 0.00 0.00 0.00 0.00 0.162998E+09 379869.33
November 0.372639E+10 0.129132E+10 0.00 0.00 0.00 0.00 0.00 96867587.78 32024074.34
December 0.385223E+10 0.132801E+10 0.00 0.00 0.00 0.00 0.00 42023593.01 93577480.21
                   
Annual Sum or Average 0.454292E+11 0.156839E+11 0.00 0.00 0.00 0.00 0.00 0.157525E+10 0.386053E+09
Minimum of Months 0.348285E+10 0.120231E+10 0.00 0.00 0.00 0.00 0.00 31798537.74 0.00
Maximum of Months 0.387034E+10 0.133622E+10 0.00 0.00 0.00 0.00 0.00 0.229149E+09 0.114267E+09



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.434056E+09 0.261068E+09 0.00 0.00 0.00 0.00 20734531.83 99621842.58
February 0.273974E+09 0.391995E+09 0.235798E+09 0.00 0.00 0.00 0.00 31876009.19 60361118.46
March 0.303685E+09 0.430607E+09 0.260708E+09 0.00 0.00 0.00 0.00 45311386.78 53472815.37
April 0.293479E+09 0.420554E+09 0.252705E+09 0.00 0.00 0.00 0.00 79555515.00 7029669.84
May 0.303504E+09 0.432331E+09 0.260888E+09 0.00 0.00 0.00 0.00 0.149474E+09 338711.29
June 0.293842E+09 0.417218E+09 0.252344E+09 0.00 0.00 0.00 0.00 0.183992E+09 21119.09
July 0.303141E+09 0.435725E+09 0.261248E+09 0.00 0.00 0.00 0.00 0.203918E+09 44718.08
August 0.303685E+09 0.430607E+09 0.260708E+09 0.00 0.00 0.00 0.00 0.199457E+09 141416.74
September 0.293479E+09 0.420667E+09 0.252705E+09 0.00 0.00 0.00 0.00 0.177564E+09 0.00
October 0.303322E+09 0.434000E+09 0.261068E+09 0.00 0.00 0.00 0.00 0.146838E+09 96511.33
November 0.293661E+09 0.418886E+09 0.252524E+09 0.00 0.00 0.00 0.00 80446900.64 24605979.55
December 0.303141E+09 0.435781E+09 0.261248E+09 0.00 0.00 0.00 0.00 31039862.62 80953842.49
                   
Annual Sum or Average 0.357224E+10 0.510243E+10 0.307301E+10 0.00 0.00 0.00 0.00 0.135021E+10 0.326688E+09
Minimum of Months 0.273974E+09 0.391995E+09 0.235798E+09 0.00 0.00 0.00 0.00 20734531.83 0.00
Maximum of Months 0.303685E+09 0.435781E+09 0.261248E+09 0.00 0.00 0.00 0.00 0.203918E+09 99621842.58



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.434005E+09 0.261038E+09 0.00 0.00 0.00 0.00 21602221.59 96160904.09
February 0.273974E+09 0.391949E+09 0.235770E+09 0.00 0.00 0.00 0.00 32685019.09 59034792.60
March 0.303685E+09 0.430556E+09 0.260677E+09 0.00 0.00 0.00 0.00 45664279.41 52183827.52
April 0.293479E+09 0.420505E+09 0.252675E+09 0.00 0.00 0.00 0.00 79683259.80 6986478.87
May 0.303504E+09 0.432281E+09 0.260857E+09 0.00 0.00 0.00 0.00 0.149437E+09 339242.60
June 0.293842E+09 0.417169E+09 0.252315E+09 0.00 0.00 0.00 0.00 0.183913E+09 21117.56
July 0.303141E+09 0.435674E+09 0.261218E+09 0.00 0.00 0.00 0.00 0.203864E+09 45067.94
August 0.303685E+09 0.430556E+09 0.260677E+09 0.00 0.00 0.00 0.00 0.199466E+09 138900.55
September 0.293479E+09 0.420618E+09 0.252675E+09 0.00 0.00 0.00 0.00 0.177695E+09 0.00
October 0.303322E+09 0.433949E+09 0.261038E+09 0.00 0.00 0.00 0.00 0.147224E+09 87861.58
November 0.293661E+09 0.418837E+09 0.252495E+09 0.00 0.00 0.00 0.00 81244277.74 24054754.82
December 0.303141E+09 0.435730E+09 0.261218E+09 0.00 0.00 0.00 0.00 31670850.86 78060266.84
                   
Annual Sum or Average 0.357224E+10 0.510183E+10 0.307265E+10 0.00 0.00 0.00 0.00 0.135415E+10 0.317113E+09
Minimum of Months 0.273974E+09 0.391949E+09 0.235770E+09 0.00 0.00 0.00 0.00 21602221.59 0.00
Maximum of Months 0.303685E+09 0.435730E+09 0.261218E+09 0.00 0.00 0.00 0.00 0.203864E+09 96160904.09



Table of Contents

Report: SpaceGainsMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.303322E+09 0.272862E+09 0.255778E+09 0.00 0.00 0.00 0.00 10413852.17 52096074.53
February 0.273974E+09 0.246421E+09 0.231020E+09 0.00 0.00 0.00 0.00 16096565.39 31517910.88
March 0.303685E+09 0.270694E+09 0.255425E+09 0.00 0.00 0.00 0.00 23097174.88 27860300.78
April 0.293479E+09 0.264375E+09 0.247584E+09 0.00 0.00 0.00 0.00 40753064.27 3589432.63
May 0.303504E+09 0.271778E+09 0.255602E+09 0.00 0.00 0.00 0.00 76586770.54 168352.71
June 0.293842E+09 0.262277E+09 0.247231E+09 0.00 0.00 0.00 0.00 94218845.07 10796.50
July 0.303141E+09 0.273911E+09 0.255955E+09 0.00 0.00 0.00 0.00 0.104405E+09 21055.24
August 0.303685E+09 0.270694E+09 0.255425E+09 0.00 0.00 0.00 0.00 0.102105E+09 65583.60
September 0.293479E+09 0.264446E+09 0.247584E+09 0.00 0.00 0.00 0.00 90734279.50 0.00
October 0.303322E+09 0.272827E+09 0.255778E+09 0.00 0.00 0.00 0.00 74850081.89 58774.92
November 0.293661E+09 0.263326E+09 0.247408E+09 0.00 0.00 0.00 0.00 40891678.05 12946861.79
December 0.303141E+09 0.273947E+09 0.255955E+09 0.00 0.00 0.00 0.00 15685850.43 42472412.11
                   
Annual Sum or Average 0.357224E+10 0.320756E+10 0.301074E+10 0.00 0.00 0.00 0.00 0.689838E+09 0.170808E+09
Minimum of Months 0.273974E+09 0.246421E+09 0.231020E+09 0.00 0.00 0.00 0.00 10413852.17 0.00
Maximum of Months 0.303685E+09 0.273947E+09 0.255955E+09 0.00 0.00 0.00 0.00 0.104405E+09 52096074.53



Table of Contents

Report: SpaceGainsMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.459349E+11 0.396945E+10 0.149358E+11 0.00 0.00 0.00 0.00 65754793.47 0.257790E+09
February 0.415303E+11 0.358405E+10 0.134904E+11 0.00 0.00 0.00 0.00 96277981.41 0.167539E+09
March 0.461508E+11 0.398168E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.117032E+09 0.143469E+09
April 0.445315E+11 0.383486E+10 0.144540E+11 0.00 0.00 0.00 0.00 0.196082E+09 27888103.91
May 0.460320E+11 0.397633E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.348027E+09 1964380.45
June 0.446286E+11 0.385245E+10 0.144540E+11 0.00 0.00 0.00 0.00 0.425497E+09 2581.76
July 0.459349E+11 0.395874E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.472953E+09 102855.47
August 0.461292E+11 0.398321E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.464605E+09 0.00
September 0.445099E+11 0.383639E+10 0.144540E+11 0.00 0.00 0.00 0.00 0.414703E+09 13430.70
October 0.459565E+11 0.396792E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.347475E+09 1406749.73
November 0.444343E+11 0.384939E+10 0.144540E+11 0.00 0.00 0.00 0.00 0.202776E+09 72719719.00
December 0.459349E+11 0.395874E+10 0.149358E+11 0.00 0.00 0.00 0.00 86984832.19 0.212052E+09
                   
Annual Sum or Average 0.541708E+12 0.467532E+11 0.175857E+12 0.00 0.00 0.00 0.00 0.323817E+10 0.884948E+09
Minimum of Months 0.415303E+11 0.358405E+10 0.134904E+11 0.00 0.00 0.00 0.00 65754793.47 0.00
Maximum of Months 0.461508E+11 0.398321E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.472953E+09 0.257790E+09



Table of Contents

Report: SpaceGainsMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.459349E+11 0.396945E+10 0.149358E+11 0.00 0.00 0.00 0.00 64314342.17 0.261115E+09
February 0.415303E+11 0.358405E+10 0.134904E+11 0.00 0.00 0.00 0.00 93939588.33 0.170051E+09
March 0.461508E+11 0.398168E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.113313E+09 0.145620E+09
April 0.445315E+11 0.383486E+10 0.144540E+11 0.00 0.00 0.00 0.00 0.191205E+09 29063412.25
May 0.460320E+11 0.397633E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.341968E+09 2090603.81
June 0.446286E+11 0.385245E+10 0.144540E+11 0.00 0.00 0.00 0.00 0.420193E+09 5386.13
July 0.459349E+11 0.395874E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.468131E+09 125489.63
August 0.461292E+11 0.398321E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.459461E+09 0.00
September 0.445099E+11 0.383639E+10 0.144540E+11 0.00 0.00 0.00 0.00 0.410088E+09 23183.88
October 0.459565E+11 0.396792E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.342518E+09 1498875.59
November 0.444343E+11 0.384939E+10 0.144540E+11 0.00 0.00 0.00 0.00 0.199002E+09 74166211.15
December 0.459349E+11 0.395874E+10 0.149358E+11 0.00 0.00 0.00 0.00 84711581.55 0.214874E+09
                   
Annual Sum or Average 0.541708E+12 0.467532E+11 0.175857E+12 0.00 0.00 0.00 0.00 0.318885E+10 0.898632E+09
Minimum of Months 0.415303E+11 0.358405E+10 0.134904E+11 0.00 0.00 0.00 0.00 64314342.17 0.00
Maximum of Months 0.461508E+11 0.398321E+10 0.149358E+11 0.00 0.00 0.00 0.00 0.468131E+09 0.261115E+09



Table of Contents

Report: SpaceGainsMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.408770E+10 0.105977E+10 0.338870E+11 0.305408E+11 0.00 0.00 0.00 19034666.72 0.293937E+09
February 0.369574E+10 0.956878E+09 0.306077E+11 0.275852E+11 0.00 0.00 0.00 31267938.27 0.185774E+09
March 0.410691E+10 0.106304E+10 0.338870E+11 0.305408E+11 0.00 0.00 0.00 43010759.13 0.164492E+09
April 0.396281E+10 0.102384E+10 0.327939E+11 0.295556E+11 0.00 0.00 0.00 95602531.74 35646985.55
May 0.409635E+10 0.106161E+10 0.338870E+11 0.305408E+11 0.00 0.00 0.00 0.225654E+09 2839142.42
June 0.397146E+10 0.102854E+10 0.327939E+11 0.295556E+11 0.00 0.00 0.00 0.300680E+09 356600.34
July 0.408770E+10 0.105691E+10 0.338870E+11 0.305408E+11 0.00 0.00 0.00 0.342615E+09 1238742.69
August 0.410499E+10 0.106345E+10 0.338870E+11 0.305408E+11 0.00 0.00 0.00 0.333234E+09 1407046.34
September 0.396089E+10 0.102425E+10 0.327939E+11 0.295556E+11 0.00 0.00 0.00 0.288006E+09 608892.61
October 0.408962E+10 0.105936E+10 0.338870E+11 0.305408E+11 0.00 0.00 0.00 0.221010E+09 2191767.56
November 0.395417E+10 0.102772E+10 0.327939E+11 0.295556E+11 0.00 0.00 0.00 0.106717E+09 82961479.94
December 0.408770E+10 0.105691E+10 0.338870E+11 0.305408E+11 0.00 0.00 0.00 32356974.68 0.243988E+09
                   
Annual Sum or Average 0.482060E+11 0.124823E+11 0.398993E+12 0.359593E+12 0.00 0.00 0.00 0.203919E+10 0.101544E+10
Minimum of Months 0.369574E+10 0.956878E+09 0.306077E+11 0.275852E+11 0.00 0.00 0.00 19034666.72 356600.34
Maximum of Months 0.410691E+10 0.106345E+10 0.338870E+11 0.305408E+11 0.00 0.00 0.00 0.342615E+09 0.293937E+09



Table of Contents

Report: SpaceGainsMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.407704E+10 0.140929E+10 0.00 0.00 0.00 0.00 0.00 64483603.01 0.193202E+09
February 0.368610E+10 0.127246E+10 0.00 0.00 0.00 0.00 0.00 96281430.14 0.120437E+09
March 0.409620E+10 0.141364E+10 0.00 0.00 0.00 0.00 0.00 0.127046E+09 0.104513E+09
April 0.395248E+10 0.136151E+10 0.00 0.00 0.00 0.00 0.00 0.202775E+09 12896772.28
May 0.408566E+10 0.141173E+10 0.00 0.00 0.00 0.00 0.00 0.341184E+09 164615.37
June 0.396110E+10 0.136775E+10 0.00 0.00 0.00 0.00 0.00 0.399611E+09 0.00
July 0.407704E+10 0.140549E+10 0.00 0.00 0.00 0.00 0.00 0.434380E+09 0.00
August 0.409429E+10 0.141418E+10 0.00 0.00 0.00 0.00 0.00 0.433600E+09 0.00
September 0.395056E+10 0.136205E+10 0.00 0.00 0.00 0.00 0.00 0.384923E+09 0.00
October 0.407896E+10 0.140875E+10 0.00 0.00 0.00 0.00 0.00 0.332499E+09 573.58
November 0.394385E+10 0.136667E+10 0.00 0.00 0.00 0.00 0.00 0.198252E+09 46797546.48
December 0.407704E+10 0.140549E+10 0.00 0.00 0.00 0.00 0.00 87258858.83 0.156839E+09
                   
Annual Sum or Average 0.480803E+11 0.165990E+11 0.00 0.00 0.00 0.00 0.00 0.310229E+10 0.634850E+09
Minimum of Months 0.368610E+10 0.127246E+10 0.00 0.00 0.00 0.00 0.00 64483603.01 0.00
Maximum of Months 0.409620E+10 0.141418E+10 0.00 0.00 0.00 0.00 0.00 0.434380E+09 0.193202E+09



Table of Contents

Report: PeakSpaceGainsMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 11501.89 02-JAN-00:10 13517.00 02-JAN-20:10 10113.80 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 0.00
February 11501.89 01-FEB-00:10 13517.00 01-FEB-20:10 10113.80 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 0.00
March 11501.89 01-MAR-00:10 13517.00 01-MAR-20:10 10113.80 01-MAR-20:10 0.00 0.00 0.00 0.00 0.00 0.00
April 11501.89 01-APR-00:10 13517.00 03-APR-19:10 10113.80 03-APR-19:10 0.00 0.00 0.00 0.00 0.00 0.00
May 11501.89 01-MAY-00:10 13517.00 01-MAY-19:10 10113.80 01-MAY-19:10 0.00 0.00 0.00 0.00 0.00 0.00
June 11501.89 01-JUN-00:10 13517.00 01-JUN-19:10 10113.80 01-JUN-19:10 0.00 0.00 0.00 0.00 0.00 0.00
July 11501.89 01-JUL-00:10 13517.00 03-JUL-19:10 10113.80 03-JUL-19:10 0.00 0.00 0.00 0.00 0.00 0.00
August 11501.89 01-AUG-00:10 13517.00 01-AUG-19:10 10113.80 01-AUG-19:10 0.00 0.00 0.00 0.00 0.00 0.00
September 11501.89 01-SEP-00:10 13517.00 01-SEP-19:10 10113.80 01-SEP-19:10 0.00 0.00 0.00 0.00 0.00 0.00
October 11501.89 01-OCT-23:10 13517.00 02-OCT-19:10 10113.80 02-OCT-19:10 0.00 0.00 0.00 0.00 0.00 0.00
November 11501.89 01-NOV-00:10 13517.00 01-NOV-19:10 10113.80 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 0.00
December 11501.89 01-DEC-00:10 13517.00 01-DEC-20:10 10113.80 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 11501.89   13517.00   10113.80   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 11501.89   13517.00   10113.80   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1169.53 02-JAN-00:10 687.30 02-JAN-20:10 685.60 02-JAN-20:10 0.00 0.00 0.00 0.00 136.77 07-JAN-15:00 260.25 25-JAN-06:50
February 1169.53 01-FEB-00:10 687.30 01-FEB-20:10 685.60 01-FEB-20:10 0.00 0.00 0.00 0.00 143.45 02-FEB-14:00 363.76 04-FEB-07:00
March 1169.53 01-MAR-00:10 687.30 01-MAR-20:10 685.60 01-MAR-20:10 0.00 0.00 0.00 0.00 156.19 13-MAR-16:00 323.10 16-MAR-07:00
April 1169.53 01-APR-00:10 687.30 03-APR-19:10 685.60 03-APR-19:10 0.00 0.00 0.00 0.00 210.51 17-APR-15:00 144.62 02-APR-05:40
May 1169.53 01-MAY-00:10 687.30 01-MAY-19:10 685.60 01-MAY-19:10 0.00 0.00 0.00 0.00 258.29 22-MAY-13:00 8.76 01-MAY-06:00
June 1169.53 01-JUN-00:10 687.30 01-JUN-19:10 685.60 01-JUN-19:10 0.00 0.00 0.00 0.00 220.80 11-JUN-13:00 0.00 01-JUN-00:10
July 1169.53 01-JUL-00:10 687.30 03-JUL-19:10 685.60 03-JUL-19:10 0.00 0.00 0.00 0.00 277.81 29-JUL-16:00 0.00 01-JUL-00:10
August 1169.53 01-AUG-00:10 687.30 01-AUG-19:10 685.60 01-AUG-19:10 0.00 0.00 0.00 0.00 240.11 08-AUG-11:00 0.00 01-AUG-00:10
September 1169.53 01-SEP-00:10 687.30 01-SEP-19:10 685.60 01-SEP-19:10 0.00 0.00 0.00 0.00 209.65 08-SEP-16:00 0.00 01-SEP-00:10
October 1169.53 01-OCT-23:10 687.30 02-OCT-19:10 685.60 02-OCT-19:10 0.00 0.00 0.00 0.00 206.00 09-OCT-11:00 2.79 26-OCT-14:00
November 1169.53 01-NOV-00:10 687.30 01-NOV-19:10 685.60 01-NOV-19:10 0.00 0.00 0.00 0.00 142.86 04-NOV-10:50 245.24 27-NOV-06:40
December 1169.53 01-DEC-00:10 687.30 01-DEC-20:10 685.60 01-DEC-20:10 0.00 0.00 0.00 0.00 125.11 24-DEC-14:00 297.92 15-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1169.53   687.30   685.60   0.00 0.00 0.00 0.00 125.11   0.00  
Maximum of Months 1169.53   687.30   685.60   0.00 0.00 0.00 0.00 277.81   363.76  



Table of Contents

Report: PeakSpaceGainsMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1354.32 02-JAN-00:10 795.89 02-JAN-20:10 793.93 02-JAN-20:10 0.00 0.00 0.00 0.00 63.79 02-JAN-14:00 100.47 25-JAN-07:00
February 1354.32 01-FEB-00:10 795.89 01-FEB-20:10 793.93 01-FEB-20:10 0.00 0.00 0.00 0.00 67.75 11-FEB-14:00 141.00 04-FEB-07:00
March 1354.32 01-MAR-00:10 795.89 01-MAR-20:10 793.93 01-MAR-20:10 0.00 0.00 0.00 0.00 67.11 13-MAR-16:00 124.69 16-MAR-07:00
April 1354.32 01-APR-00:10 795.89 03-APR-19:10 793.93 03-APR-19:10 0.00 0.00 0.00 0.00 88.68 17-APR-15:00 55.82 02-APR-06:00
May 1354.32 01-MAY-00:10 795.89 01-MAY-19:10 793.93 01-MAY-19:10 0.00 0.00 0.00 0.00 105.55 22-MAY-13:00 4.31 07-MAY-06:00
June 1354.32 01-JUN-00:10 795.89 01-JUN-19:10 793.93 01-JUN-19:10 0.00 0.00 0.00 0.00 89.32 11-JUN-13:00 0.00 01-JUN-00:10
July 1354.32 01-JUL-00:10 795.89 03-JUL-19:10 793.93 03-JUL-19:10 0.00 0.00 0.00 0.00 114.37 29-JUL-16:00 0.00 01-JUL-00:10
August 1354.32 01-AUG-00:10 795.89 01-AUG-19:10 793.93 01-AUG-19:10 0.00 0.00 0.00 0.00 102.25 23-AUG-13:00 0.00 01-AUG-00:10
September 1354.32 01-SEP-00:10 795.89 01-SEP-19:10 793.93 01-SEP-19:10 0.00 0.00 0.00 0.00 89.09 13-SEP-13:00 0.00 01-SEP-00:10
October 1354.32 01-OCT-23:10 795.89 02-OCT-19:10 793.93 02-OCT-19:10 0.00 0.00 0.00 0.00 89.07 09-OCT-11:00 0.05 28-OCT-03:00
November 1354.32 01-NOV-00:10 795.89 01-NOV-19:10 793.93 01-NOV-19:10 0.00 0.00 0.00 0.00 71.97 17-NOV-15:00 94.68 27-NOV-07:00
December 1354.32 01-DEC-00:10 795.89 01-DEC-20:10 793.93 01-DEC-20:10 0.00 0.00 0.00 0.00 63.27 10-DEC-14:10 115.02 15-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1354.32   795.89   793.93   0.00 0.00 0.00 0.00 63.27   0.00  
Maximum of Months 1354.32   795.89   793.93   0.00 0.00 0.00 0.00 114.37   141.00  



Table of Contents

Report: PeakSpaceGainsMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 286.42 02-JAN-00:10 1487.69 02-JAN-20:10 839.45 02-JAN-20:10 0.00 0.00 0.00 0.00 150.79 02-JAN-14:00 237.40 25-JAN-06:50
February 286.42 01-FEB-00:10 1487.69 01-FEB-20:10 839.45 01-FEB-20:10 0.00 0.00 0.00 0.00 160.16 11-FEB-14:00 333.24 04-FEB-07:00
March 286.42 01-MAR-00:10 1487.69 01-MAR-20:10 839.45 01-MAR-20:10 0.00 0.00 0.00 0.00 158.65 13-MAR-16:00 294.69 16-MAR-07:00
April 286.42 01-APR-00:10 1487.69 03-APR-19:10 839.45 03-APR-19:10 0.00 0.00 0.00 0.00 209.61 17-APR-15:00 131.91 02-APR-05:50
May 286.42 01-MAY-00:10 1487.69 01-MAY-19:10 839.45 01-MAY-19:10 0.00 0.00 0.00 0.00 249.45 22-MAY-13:00 7.91 01-MAY-05:30
June 286.42 01-JUN-00:10 1487.69 01-JUN-19:10 839.45 01-JUN-19:10 0.00 0.00 0.00 0.00 210.72 11-JUN-13:00 0.00 01-JUN-00:10
July 286.42 01-JUL-00:10 1487.69 03-JUL-19:10 839.45 03-JUL-19:10 0.00 0.00 0.00 0.00 270.28 29-JUL-16:00 0.00 01-JUL-00:10
August 286.42 01-AUG-00:10 1487.69 01-AUG-19:10 839.45 01-AUG-19:10 0.00 0.00 0.00 0.00 240.72 23-AUG-13:00 0.00 01-AUG-00:10
September 286.42 01-SEP-00:10 1487.69 01-SEP-19:10 839.45 01-SEP-19:10 0.00 0.00 0.00 0.00 210.54 13-SEP-13:00 0.00 01-SEP-00:10
October 286.42 01-OCT-23:10 1487.69 02-OCT-19:10 839.45 02-OCT-19:10 0.00 0.00 0.00 0.00 210.50 09-OCT-11:00 0.00 01-OCT-00:10
November 286.42 01-NOV-00:10 1487.69 01-NOV-19:10 839.45 01-NOV-19:10 0.00 0.00 0.00 0.00 170.31 17-NOV-15:00 223.75 27-NOV-07:00
December 286.42 01-DEC-00:10 1487.69 01-DEC-20:10 839.45 01-DEC-20:10 0.00 0.00 0.00 0.00 149.50 10-DEC-14:10 271.75 15-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 286.42   1487.69   839.45   0.00 0.00 0.00 0.00 149.50   0.00  
Maximum of Months 286.42   1487.69   839.45   0.00 0.00 0.00 0.00 270.28   333.24  



Table of Contents

Report: PeakSpaceGainsMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 220.32 02-JAN-00:10 273.10 02-JAN-20:10 242.16 02-JAN-20:10 0.00 0.00 0.00 0.00 87.00 02-JAN-14:00 136.97 25-JAN-07:00
February 220.32 01-FEB-00:10 273.10 01-FEB-20:10 242.16 01-FEB-20:10 0.00 0.00 0.00 0.00 92.40 11-FEB-14:00 192.25 04-FEB-07:00
March 220.32 01-MAR-00:10 273.10 01-MAR-20:10 242.16 01-MAR-20:10 0.00 0.00 0.00 0.00 91.54 13-MAR-16:00 169.99 16-MAR-07:00
April 220.32 01-APR-00:10 273.10 03-APR-19:10 242.16 03-APR-19:10 0.00 0.00 0.00 0.00 120.92 17-APR-15:00 76.10 02-APR-05:40
May 220.32 01-MAY-00:10 273.10 01-MAY-19:10 242.16 01-MAY-19:10 0.00 0.00 0.00 0.00 143.92 22-MAY-13:00 4.57 01-MAY-05:30
June 220.32 01-JUN-00:10 273.10 01-JUN-19:10 242.16 01-JUN-19:10 0.00 0.00 0.00 0.00 121.28 11-JUN-13:00 0.00 01-JUN-00:10
July 220.32 01-JUL-00:10 273.10 03-JUL-19:10 242.16 03-JUL-19:10 0.00 0.00 0.00 0.00 155.34 29-JUL-16:00 0.00 01-JUL-00:10
August 220.32 01-AUG-00:10 273.10 01-AUG-19:10 242.16 01-AUG-19:10 0.00 0.00 0.00 0.00 138.61 23-AUG-13:00 0.00 01-AUG-00:10
September 220.32 01-SEP-00:10 273.10 01-SEP-19:10 242.16 01-SEP-19:10 0.00 0.00 0.00 0.00 121.47 13-SEP-13:00 0.00 01-SEP-00:10
October 220.32 01-OCT-23:10 273.10 02-OCT-19:10 242.16 02-OCT-19:10 0.00 0.00 0.00 0.00 121.43 09-OCT-11:00 0.00 01-OCT-00:10
November 220.32 01-NOV-00:10 273.10 01-NOV-19:10 242.16 01-NOV-19:10 0.00 0.00 0.00 0.00 98.25 17-NOV-15:00 129.09 27-NOV-07:00
December 220.32 01-DEC-00:10 273.10 01-DEC-20:10 242.16 01-DEC-20:10 0.00 0.00 0.00 0.00 86.25 10-DEC-14:00 156.81 15-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 220.32   273.10   242.16   0.00 0.00 0.00 0.00 86.25   0.00  
Maximum of Months 220.32   273.10   242.16   0.00 0.00 0.00 0.00 155.34   192.25  



Table of Contents

Report: PeakSpaceGainsMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 907.20 02-JAN-00:10 337.37 02-JAN-20:10 4572.80 02-JAN-20:10 39726.58 02-JAN-20:10 0.00 0.00 0.00 206.09 02-JAN-14:00 341.03 24-JAN-22:00
February 907.20 01-FEB-00:10 337.37 01-FEB-20:10 4572.80 01-FEB-20:10 39726.58 01-FEB-20:10 0.00 0.00 0.00 218.84 11-FEB-14:00 454.94 04-FEB-07:00
March 907.20 01-MAR-00:10 337.37 01-MAR-20:10 4572.80 01-MAR-20:10 39726.58 01-MAR-20:10 0.00 0.00 0.00 216.74 13-MAR-16:00 415.36 16-MAR-07:00
April 907.20 01-APR-00:10 337.37 03-APR-19:10 4572.80 03-APR-19:10 39726.58 03-APR-19:10 0.00 0.00 0.00 286.06 17-APR-15:00 180.19 02-APR-06:00
May 907.20 01-MAY-00:10 337.37 01-MAY-19:10 4572.80 01-MAY-19:10 39726.58 01-MAY-19:10 0.00 0.00 0.00 340.49 22-MAY-13:00 17.78 01-MAY-06:10
June 907.20 01-JUN-00:10 337.37 01-JUN-19:10 4572.80 01-JUN-19:10 39726.58 01-JUN-19:10 0.00 0.00 0.00 288.31 11-JUN-13:00 0.00 01-JUN-00:10
July 907.20 01-JUL-00:10 337.37 03-JUL-19:10 4572.80 03-JUL-19:10 39726.58 03-JUL-19:10 0.00 0.00 0.00 369.00 29-JUL-16:00 31.29 14-JUL-20:00
August 907.20 01-AUG-00:10 337.37 01-AUG-19:10 4572.80 01-AUG-19:10 39726.58 01-AUG-19:10 0.00 0.00 0.00 330.01 23-AUG-13:00 0.00 01-AUG-00:10
September 907.20 01-SEP-00:10 337.37 01-SEP-19:10 4572.80 01-SEP-19:10 39726.58 01-SEP-19:10 0.00 0.00 0.00 287.76 13-SEP-13:10 2.90 05-SEP-21:00
October 907.20 01-OCT-23:10 337.37 02-OCT-19:10 4572.80 02-OCT-19:10 39726.58 02-OCT-19:10 0.00 0.00 0.00 288.94 09-OCT-11:00 2.93 27-OCT-21:00
November 907.20 01-NOV-00:10 337.37 01-NOV-19:10 4572.80 01-NOV-19:10 39726.58 01-NOV-19:10 0.00 0.00 0.00 232.47 17-NOV-15:00 305.64 27-NOV-06:00
December 907.20 01-DEC-00:10 337.37 01-DEC-20:10 4572.80 01-DEC-20:10 39726.58 01-DEC-20:10 0.00 0.00 0.00 204.12 10-DEC-14:20 377.14 15-DEC-07:10
                               
Annual Sum or Average                 0.00 0.00 0.00        
Minimum of Months 907.20   337.37   4572.80   39726.58   0.00 0.00 0.00 204.12   0.00  
Maximum of Months 907.20   337.37   4572.80   39726.58   0.00 0.00 0.00 369.00   454.94  



Table of Contents

Report: PeakSpaceGainsMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 15368.40 02-JAN-00:10 2177.23 02-JAN-20:10 965.27 02-JAN-20:10 0.00 0.00 0.00 0.00 316.40 07-JAN-13:00 580.39 25-JAN-05:20
February 15368.40 01-FEB-00:10 2177.23 01-FEB-20:10 965.27 01-FEB-20:10 0.00 0.00 0.00 0.00 337.02 02-FEB-14:00 807.73 04-FEB-07:00
March 15368.40 01-MAR-00:10 2177.23 01-MAR-20:10 965.27 01-MAR-20:10 0.00 0.00 0.00 0.00 354.04 13-MAR-16:00 714.29 16-MAR-07:00
April 15368.40 01-APR-00:10 2177.23 03-APR-19:10 965.27 03-APR-19:10 0.00 0.00 0.00 0.00 489.34 17-APR-15:00 319.92 02-APR-05:40
May 15368.40 01-MAY-00:10 2177.23 01-MAY-19:10 965.27 01-MAY-19:10 0.00 0.00 0.00 0.00 601.15 22-MAY-13:00 51.64 01-MAY-05:00
June 15368.40 01-JUN-00:10 2177.23 01-JUN-19:10 965.27 01-JUN-19:10 0.00 0.00 0.00 0.00 511.38 11-JUN-13:00 0.00 01-JUN-00:10
July 15368.40 01-JUL-00:10 2177.23 03-JUL-19:10 965.27 03-JUL-19:10 0.00 0.00 0.00 0.00 652.34 29-JUL-16:00 0.00 01-JUL-00:10
August 15368.40 01-AUG-00:10 2177.23 01-AUG-19:10 965.27 01-AUG-19:10 0.00 0.00 0.00 0.00 565.04 23-AUG-13:00 0.00 01-AUG-00:10
September 15368.40 01-SEP-00:10 2177.23 01-SEP-19:10 965.27 01-SEP-19:10 0.00 0.00 0.00 0.00 489.44 13-SEP-13:00 0.00 01-SEP-00:10
October 15368.40 01-OCT-23:10 2177.23 02-OCT-19:10 965.27 02-OCT-19:10 0.00 0.00 0.00 0.00 482.69 09-OCT-11:00 38.41 28-OCT-03:00
November 15368.40 01-NOV-00:10 2177.23 01-NOV-19:10 965.27 01-NOV-19:10 0.00 0.00 0.00 0.00 349.71 17-NOV-15:00 555.38 27-NOV-03:00
December 15368.40 01-DEC-00:10 2177.23 01-DEC-20:10 965.27 01-DEC-20:10 0.00 0.00 0.00 0.00 295.57 10-DEC-14:00 662.51 15-DEC-05:20
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 15368.40   2177.23   965.27   0.00 0.00 0.00 0.00 295.57   0.00  
Maximum of Months 15368.40   2177.23   965.27   0.00 0.00 0.00 0.00 652.34   807.73  



Table of Contents

Report: PeakSpaceGainsMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 45622.98 02-JAN-00:10 11849.32 02-JAN-20:10 10029.21 02-JAN-20:10 0.00 0.00 0.00 0.00 1039.37 02-JAN-14:00 1681.06 25-JAN-05:40
February 45622.98 01-FEB-00:10 11849.32 01-FEB-20:10 10029.21 01-FEB-20:10 0.00 0.00 0.00 0.00 1078.91 11-FEB-14:00 2307.35 04-FEB-07:00
March 45622.98 01-MAR-00:10 11849.32 01-MAR-20:10 10029.21 01-MAR-20:10 0.00 0.00 0.00 0.00 1098.60 13-MAR-16:00 2064.48 16-MAR-05:00
April 45622.98 01-APR-00:10 11849.32 03-APR-19:10 10029.21 03-APR-19:10 0.00 0.00 0.00 0.00 1451.34 17-APR-15:00 948.60 02-APR-05:30
May 45622.98 01-MAY-00:10 11849.32 01-MAY-19:10 10029.21 01-MAY-19:10 0.00 0.00 0.00 0.00 1726.82 22-MAY-13:00 144.22 01-MAY-05:00
June 45622.98 01-JUN-00:10 11849.32 01-JUN-19:10 10029.21 01-JUN-19:10 0.00 0.00 0.00 0.00 1461.34 11-JUN-13:00 0.00 01-JUN-00:10
July 45622.98 01-JUL-00:10 11849.32 03-JUL-19:10 10029.21 03-JUL-19:10 0.00 0.00 0.00 0.00 1871.25 29-JUL-16:00 0.00 01-JUL-00:10
August 45622.98 01-AUG-00:10 11849.32 01-AUG-19:10 10029.21 01-AUG-19:10 0.00 0.00 0.00 0.00 1673.33 23-AUG-13:00 0.00 01-AUG-00:10
September 45622.98 01-SEP-00:10 11849.32 01-SEP-19:10 10029.21 01-SEP-19:10 0.00 0.00 0.00 0.00 1457.83 13-SEP-13:00 0.00 01-SEP-00:10
October 45622.98 01-OCT-23:10 11849.32 02-OCT-19:10 10029.21 02-OCT-19:10 0.00 0.00 0.00 0.00 1457.33 09-OCT-11:00 94.05 28-OCT-03:00
November 45622.98 01-NOV-00:10 11849.32 01-NOV-19:10 10029.21 01-NOV-19:10 0.00 0.00 0.00 0.00 1157.45 17-NOV-15:00 1596.05 27-NOV-03:00
December 45622.98 01-DEC-00:10 11849.32 01-DEC-20:10 10029.21 01-DEC-20:10 0.00 0.00 0.00 0.00 1020.24 10-DEC-14:00 1920.57 15-DEC-05:40
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 45622.98   11849.32   10029.21   0.00 0.00 0.00 0.00 1020.24   0.00  
Maximum of Months 45622.98   11849.32   10029.21   0.00 0.00 0.00 0.00 1871.25   2307.35  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 392.73 01-JAN-19:10 237.06 01-JAN-08:09 0.00 0.00 0.00 0.00 67.90 01-JAN-11:00 153.04 25-JAN-07:00
February 180.00 01-FEB-00:10 392.73 01-FEB-20:10 237.06 01-FEB-07:10 0.00 0.00 0.00 0.00 79.87 11-FEB-16:10 214.05 04-FEB-07:00
March 180.00 01-MAR-00:10 392.73 01-MAR-20:10 237.06 01-MAR-07:10 0.00 0.00 0.00 0.00 99.10 13-MAR-16:00 189.48 16-MAR-07:00
April 180.00 01-APR-00:10 392.73 01-APR-18:10 237.06 01-APR-07:10 0.00 0.00 0.00 0.00 130.55 17-APR-15:10 85.88 02-APR-06:00
May 180.00 01-MAY-00:10 392.73 01-MAY-19:10 237.06 01-MAY-06:10 0.00 0.00 0.00 0.00 144.03 29-MAY-16:00 20.79 10-MAY-15:00
June 180.00 01-JUN-00:10 392.73 01-JUN-19:10 237.06 01-JUN-06:10 0.00 0.00 0.00 0.00 126.59 10-JUN-16:00 7.14 05-JUN-15:00
July 180.00 01-JUL-00:10 392.73 01-JUL-18:10 237.06 01-JUL-07:10 0.00 0.00 0.00 0.00 170.16 29-JUL-16:00 7.16 14-JUL-17:40
August 180.00 01-AUG-00:10 392.73 01-AUG-19:10 237.06 01-AUG-06:10 0.00 0.00 0.00 0.00 132.09 21-AUG-16:00 12.35 28-AUG-13:00
September 180.00 01-SEP-00:10 392.73 01-SEP-19:10 237.06 01-SEP-06:10 0.00 0.00 0.00 0.00 132.05 20-SEP-16:00 0.00 01-SEP-00:10
October 180.00 01-OCT-00:10 392.73 01-OCT-18:10 237.06 01-OCT-07:10 0.00 0.00 0.00 0.00 125.82 14-OCT-16:00 20.77 26-OCT-14:00
November 180.00 01-NOV-00:10 392.73 01-NOV-19:10 237.06 01-NOV-06:10 0.00 0.00 0.00 0.00 96.36 17-NOV-16:10 144.33 27-NOV-07:00
December 180.00 01-DEC-00:10 392.73 01-DEC-20:10 237.06 01-DEC-07:10 0.00 0.00 0.00 0.00 84.04 10-DEC-16:10 174.93 15-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   392.73   237.06   0.00 0.00 0.00 0.00 67.90   0.00  
Maximum of Months 180.00   392.73   237.06   0.00 0.00 0.00 0.00 170.16   214.05  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 392.68 01-JAN-19:10 237.03 01-JAN-08:09 0.00 0.00 0.00 0.00 67.90 01-JAN-11:00 153.03 25-JAN-07:00
February 180.00 01-FEB-00:10 392.68 01-FEB-20:10 237.03 01-FEB-07:10 0.00 0.00 0.00 0.00 79.86 11-FEB-16:10 214.03 04-FEB-07:00
March 180.00 01-MAR-00:10 392.68 01-MAR-20:10 237.03 01-MAR-07:10 0.00 0.00 0.00 0.00 99.09 13-MAR-16:00 189.47 16-MAR-07:00
April 180.00 01-APR-00:10 392.68 01-APR-18:10 237.03 01-APR-07:10 0.00 0.00 0.00 0.00 130.54 17-APR-15:08 85.87 02-APR-05:40
May 180.00 01-MAY-00:10 392.68 01-MAY-19:10 237.03 01-MAY-06:10 0.00 0.00 0.00 0.00 144.02 29-MAY-16:00 20.78 10-MAY-15:00
June 180.00 01-JUN-00:10 392.68 01-JUN-19:10 237.03 01-JUN-06:10 0.00 0.00 0.00 0.00 126.58 10-JUN-16:00 7.14 05-JUN-15:00
July 180.00 01-JUL-00:10 392.68 01-JUL-18:10 237.03 01-JUL-07:10 0.00 0.00 0.00 0.00 170.15 29-JUL-16:00 7.16 14-JUL-17:40
August 180.00 01-AUG-00:10 392.68 01-AUG-19:10 237.03 01-AUG-06:10 0.00 0.00 0.00 0.00 132.07 21-AUG-16:00 12.05 28-AUG-13:00
September 180.00 01-SEP-00:10 392.68 01-SEP-19:10 237.03 01-SEP-06:10 0.00 0.00 0.00 0.00 132.03 20-SEP-16:00 0.00 01-SEP-00:10
October 180.00 01-OCT-00:10 392.68 01-OCT-18:10 237.03 01-OCT-07:10 0.00 0.00 0.00 0.00 125.81 14-OCT-16:00 20.76 26-OCT-14:00
November 180.00 01-NOV-00:10 392.68 01-NOV-19:10 237.03 01-NOV-06:10 0.00 0.00 0.00 0.00 96.35 17-NOV-16:10 144.32 27-NOV-07:00
December 180.00 01-DEC-00:10 392.68 01-DEC-20:10 237.03 01-DEC-07:10 0.00 0.00 0.00 0.00 84.03 10-DEC-16:08 174.91 15-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   392.68   237.03   0.00 0.00 0.00 0.00 67.90   0.00  
Maximum of Months 180.00   392.68   237.03   0.00 0.00 0.00 0.00 170.15   214.03  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 01-JAN-00:10 246.81 01-JAN-19:10 232.19 01-JAN-08:09 0.00 0.00 0.00 0.00 18.71 02-JAN-14:00 50.00 25-JAN-07:20
February 0.00 01-FEB-00:10 246.81 01-FEB-20:10 232.19 01-FEB-07:10 0.00 0.00 0.00 0.00 20.39 11-FEB-14:00 62.52 04-FEB-07:00
March 0.00 01-MAR-00:10 246.81 01-MAR-20:10 232.19 01-MAR-07:10 0.00 0.00 0.00 0.00 20.20 13-MAR-16:00 59.88 16-MAR-07:00
April 0.00 01-APR-00:10 246.81 01-APR-18:10 232.19 01-APR-07:10 0.00 0.00 0.00 0.00 29.31 17-APR-15:00 31.84 02-APR-06:00
May 0.00 01-MAY-00:10 246.81 01-MAY-19:10 232.19 01-MAY-06:10 0.00 0.00 0.00 0.00 36.43 22-MAY-13:00 9.66 01-MAY-06:00
June 0.00 01-JUN-00:10 246.81 01-JUN-19:10 232.19 01-JUN-06:10 0.00 0.00 0.00 0.00 29.53 11-JUN-13:00 1.99 05-JUN-15:00
July 0.00 01-JUL-00:10 246.81 01-JUL-18:10 232.19 01-JUL-07:10 0.00 0.00 0.00 0.00 40.17 29-JUL-16:00 2.00 14-JUL-22:03
August 0.00 01-AUG-00:10 246.81 01-AUG-19:10 232.19 01-AUG-06:10 0.00 0.00 0.00 0.00 35.00 23-AUG-13:00 4.09 28-AUG-12:00
September 0.00 01-SEP-00:10 246.81 01-SEP-19:10 232.19 01-SEP-06:10 0.00 0.00 0.00 0.00 29.44 13-SEP-13:00 4.06 05-SEP-06:00
October 0.00 01-OCT-00:10 246.81 01-OCT-18:10 232.19 01-OCT-07:10 0.00 0.00 0.00 0.00 29.44 09-OCT-11:00 7.87 28-OCT-03:00
November 0.00 01-NOV-00:10 246.81 01-NOV-19:10 232.19 01-NOV-06:10 0.00 0.00 0.00 0.00 22.25 17-NOV-15:00 48.23 27-NOV-07:00
December 0.00 01-DEC-00:10 246.81 01-DEC-20:10 232.19 01-DEC-07:10 0.00 0.00 0.00 0.00 18.55 10-DEC-14:00 56.16 15-DEC-07:20
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 0.00   246.81   232.19   0.00 0.00 0.00 0.00 18.55   1.99  
Maximum of Months 0.00   246.81   232.19   0.00 0.00 0.00 0.00 40.17   62.52  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 246.88 01-JAN-19:10 232.26 01-JAN-08:09 0.00 0.00 0.00 0.00 20.95 02-JAN-14:00 42.71 25-JAN-07:00
February 180.00 01-FEB-00:10 246.88 01-FEB-20:10 232.26 01-FEB-07:10 0.00 0.00 0.00 0.00 22.29 11-FEB-16:10 59.74 04-FEB-07:00
March 180.00 01-MAR-00:10 246.88 01-MAR-20:10 232.26 01-MAR-07:10 0.00 0.00 0.00 0.00 27.66 13-MAR-16:00 52.88 16-MAR-07:00
April 180.00 01-APR-00:10 246.88 01-APR-18:10 232.26 01-APR-07:10 0.00 0.00 0.00 0.00 36.43 17-APR-15:10 23.97 02-APR-06:00
May 180.00 01-MAY-00:10 246.88 01-MAY-19:10 232.26 01-MAY-06:10 0.00 0.00 0.00 0.00 40.20 29-MAY-16:00 5.80 10-MAY-15:00
June 180.00 01-JUN-00:10 246.88 01-JUN-19:10 232.26 01-JUN-06:10 0.00 0.00 0.00 0.00 35.33 10-JUN-16:00 1.99 05-JUN-15:00
July 180.00 01-JUL-00:10 246.88 01-JUL-18:10 232.26 01-JUL-07:10 0.00 0.00 0.00 0.00 47.49 29-JUL-16:00 1.99 14-JUL-18:00
August 180.00 01-AUG-00:10 246.88 01-AUG-19:10 232.26 01-AUG-06:10 0.00 0.00 0.00 0.00 36.87 21-AUG-16:00 1.99 05-AUG-18:00
September 180.00 01-SEP-00:10 246.88 01-SEP-19:10 232.26 01-SEP-06:10 0.00 0.00 0.00 0.00 36.85 20-SEP-16:00 0.00 01-SEP-00:10
October 180.00 01-OCT-00:10 246.88 01-OCT-18:10 232.26 01-OCT-07:10 0.00 0.00 0.00 0.00 35.12 14-OCT-16:00 4.31 26-OCT-14:00
November 180.00 01-NOV-00:10 246.88 01-NOV-19:10 232.26 01-NOV-06:10 0.00 0.00 0.00 0.00 26.89 17-NOV-16:08 40.28 27-NOV-07:00
December 180.00 01-DEC-00:10 246.88 01-DEC-20:10 232.26 01-DEC-07:10 0.00 0.00 0.00 0.00 23.46 10-DEC-16:10 48.82 15-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   246.88   232.26   0.00 0.00 0.00 0.00 20.95   0.00  
Maximum of Months 180.00   246.88   232.26   0.00 0.00 0.00 0.00 47.49   59.74  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 392.73 01-JAN-19:10 237.06 01-JAN-08:09 0.00 0.00 0.00 0.00 67.89 01-JAN-11:00 153.21 25-JAN-09:00
February 180.00 01-FEB-00:10 392.73 01-FEB-20:10 237.06 01-FEB-07:10 0.00 0.00 0.00 0.00 79.87 11-FEB-16:08 214.05 04-FEB-07:00
March 180.00 01-MAR-00:10 392.73 01-MAR-20:10 237.06 01-MAR-07:10 0.00 0.00 0.00 0.00 99.09 13-MAR-16:00 189.49 16-MAR-07:00
April 180.00 01-APR-00:10 392.73 01-APR-18:10 237.06 01-APR-07:10 0.00 0.00 0.00 0.00 130.55 17-APR-15:10 85.87 02-APR-06:00
May 180.00 01-MAY-00:10 392.73 01-MAY-19:10 237.06 01-MAY-06:10 0.00 0.00 0.00 0.00 144.03 29-MAY-16:00 20.79 10-MAY-15:00
June 180.00 01-JUN-00:10 392.73 01-JUN-19:10 237.06 01-JUN-06:10 0.00 0.00 0.00 0.00 126.59 10-JUN-15:50 7.14 05-JUN-15:00
July 180.00 01-JUL-00:10 392.73 01-JUL-18:10 237.06 01-JUL-07:10 0.00 0.00 0.00 0.00 170.17 29-JUL-16:00 7.16 14-JUL-17:40
August 180.00 01-AUG-00:10 392.73 01-AUG-19:10 237.06 01-AUG-06:10 0.00 0.00 0.00 0.00 132.09 21-AUG-16:00 12.69 28-AUG-13:00
September 180.00 01-SEP-00:10 392.73 01-SEP-19:10 237.06 01-SEP-06:10 0.00 0.00 0.00 0.00 132.04 20-SEP-16:00 0.00 01-SEP-00:10
October 180.00 01-OCT-00:10 392.73 01-OCT-18:10 237.06 01-OCT-07:10 0.00 0.00 0.00 0.00 125.82 14-OCT-16:00 20.77 26-OCT-14:00
November 180.00 01-NOV-00:10 392.73 01-NOV-19:10 237.06 01-NOV-06:10 0.00 0.00 0.00 0.00 96.36 17-NOV-16:08 144.33 27-NOV-07:00
December 180.00 01-DEC-00:10 392.73 01-DEC-20:10 237.06 01-DEC-07:10 0.00 0.00 0.00 0.00 84.04 10-DEC-16:08 174.93 15-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   392.73   237.06   0.00 0.00 0.00 0.00 67.89   0.00  
Maximum of Months 180.00   392.73   237.06   0.00 0.00 0.00 0.00 170.17   214.05  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 392.68 01-JAN-19:10 237.03 01-JAN-08:09 0.00 0.00 0.00 0.00 67.90 01-JAN-11:00 153.03 25-JAN-07:00
February 180.00 01-FEB-00:10 392.68 01-FEB-20:10 237.03 01-FEB-07:10 0.00 0.00 0.00 0.00 79.87 11-FEB-16:10 214.04 04-FEB-07:00
March 180.00 01-MAR-00:10 392.68 01-MAR-20:10 237.03 01-MAR-07:10 0.00 0.00 0.00 0.00 99.09 13-MAR-16:00 189.47 16-MAR-07:00
April 180.00 01-APR-00:10 392.68 01-APR-18:10 237.03 01-APR-07:10 0.00 0.00 0.00 0.00 130.54 17-APR-15:10 85.87 02-APR-06:00
May 180.00 01-MAY-00:10 392.68 01-MAY-19:10 237.03 01-MAY-06:10 0.00 0.00 0.00 0.00 144.02 29-MAY-16:00 20.79 10-MAY-15:00
June 180.00 01-JUN-00:10 392.68 01-JUN-19:10 237.03 01-JUN-06:10 0.00 0.00 0.00 0.00 126.58 10-JUN-15:50 7.14 05-JUN-15:00
July 180.00 01-JUL-00:10 392.68 01-JUL-18:10 237.03 01-JUL-07:10 0.00 0.00 0.00 0.00 170.15 29-JUL-16:00 7.16 14-JUL-17:40
August 180.00 01-AUG-00:10 392.68 01-AUG-19:10 237.03 01-AUG-06:10 0.00 0.00 0.00 0.00 132.08 21-AUG-16:00 12.39 28-AUG-13:00
September 180.00 01-SEP-00:10 392.68 01-SEP-19:10 237.03 01-SEP-06:10 0.00 0.00 0.00 0.00 132.03 20-SEP-16:00 0.00 01-SEP-00:10
October 180.00 01-OCT-00:10 392.68 01-OCT-18:10 237.03 01-OCT-07:10 0.00 0.00 0.00 0.00 125.80 14-OCT-16:00 20.76 26-OCT-14:00
November 180.00 01-NOV-00:10 392.68 01-NOV-19:10 237.03 01-NOV-06:10 0.00 0.00 0.00 0.00 96.35 17-NOV-16:10 144.32 27-NOV-07:00
December 180.00 01-DEC-00:10 392.68 01-DEC-20:10 237.03 01-DEC-07:10 0.00 0.00 0.00 0.00 84.04 10-DEC-16:10 174.91 15-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   392.68   237.03   0.00 0.00 0.00 0.00 67.90   0.00  
Maximum of Months 180.00   392.68   237.03   0.00 0.00 0.00 0.00 170.15   214.04  



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2263.36 02-JAN-00:10 1282.60 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 101.53 02-JAN-14:00 183.32 25-JAN-07:00
February 2263.36 01-FEB-00:10 1282.60 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 110.38 11-FEB-14:00 257.08 04-FEB-07:00
March 2263.36 01-MAR-00:10 1282.60 01-MAR-20:10 0.00 0.00 0.00 0.00 0.00 111.74 13-MAR-16:00 227.39 16-MAR-07:00
April 2263.36 01-APR-00:10 1282.60 03-APR-19:10 0.00 0.00 0.00 0.00 0.00 145.70 17-APR-15:00 110.99 02-APR-05:05
May 2263.36 01-MAY-00:10 1282.60 01-MAY-19:10 0.00 0.00 0.00 0.00 0.00 176.60 22-MAY-13:00 19.01 07-MAY-06:00
June 2263.36 01-JUN-00:10 1282.60 01-JUN-19:10 0.00 0.00 0.00 0.00 0.00 145.29 11-JUN-13:00 0.00 01-JUN-00:10
July 2263.36 01-JUL-00:10 1282.60 03-JUL-19:10 0.00 0.00 0.00 0.00 0.00 188.63 29-JUL-16:00 0.00 01-JUL-00:10
August 2263.36 01-AUG-00:10 1282.60 01-AUG-19:10 0.00 0.00 0.00 0.00 0.00 166.38 23-AUG-13:00 0.00 01-AUG-00:10
September 2263.36 01-SEP-00:10 1282.60 01-SEP-19:10 0.00 0.00 0.00 0.00 0.00 144.96 08-SEP-16:00 0.00 01-SEP-00:10
October 2263.36 01-OCT-23:10 1282.60 02-OCT-19:10 0.00 0.00 0.00 0.00 0.00 145.25 09-OCT-11:00 14.12 28-OCT-03:00
November 2263.36 01-NOV-00:10 1282.60 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 116.86 17-NOV-15:00 179.16 27-NOV-03:00
December 2263.36 01-DEC-00:10 1282.60 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 97.71 10-DEC-14:00 211.34 15-DEC-05:00
                           
Annual Sum or Average         0.00 0.00 0.00 0.00 0.00        
Minimum of Months 2263.36   1282.60   0.00 0.00 0.00 0.00 0.00 97.71   0.00  
Maximum of Months 2263.36   1282.60   0.00 0.00 0.00 0.00 0.00 188.63   257.08  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 392.73 01-JAN-19:10 237.06 01-JAN-08:09 0.00 0.00 0.00 0.00 67.19 01-JAN-11:00 153.85 25-JAN-07:00
February 180.00 01-FEB-00:10 392.73 01-FEB-20:10 237.06 01-FEB-07:10 0.00 0.00 0.00 0.00 79.16 11-FEB-16:10 214.88 04-FEB-07:00
March 180.00 01-MAR-00:10 392.73 01-MAR-20:10 237.06 01-MAR-07:10 0.00 0.00 0.00 0.00 98.40 13-MAR-16:00 190.30 16-MAR-07:00
April 180.00 01-APR-00:10 392.73 01-APR-18:10 237.06 01-APR-07:10 0.00 0.00 0.00 0.00 129.87 17-APR-15:10 86.65 02-APR-06:00
May 180.00 01-MAY-00:10 392.73 01-MAY-19:10 237.06 01-MAY-06:10 0.00 0.00 0.00 0.00 143.36 29-MAY-16:00 21.53 10-MAY-15:00
June 180.00 01-JUN-00:10 392.73 01-JUN-19:10 237.06 01-JUN-06:10 0.00 0.00 0.00 0.00 125.90 10-JUN-16:00 7.88 05-JUN-15:00
July 180.00 01-JUL-00:10 392.73 01-JUL-18:10 237.06 01-JUL-07:10 0.00 0.00 0.00 0.00 169.49 29-JUL-16:00 7.90 14-JUL-17:40
August 180.00 01-AUG-00:10 392.73 01-AUG-19:10 237.06 01-AUG-06:10 0.00 0.00 0.00 0.00 131.40 21-AUG-16:00 14.62 28-AUG-13:00
September 180.00 01-SEP-00:10 392.73 01-SEP-19:10 237.06 01-SEP-06:10 0.00 0.00 0.00 0.00 131.36 20-SEP-16:00 0.00 01-SEP-00:10
October 180.00 01-OCT-00:10 392.73 01-OCT-18:10 237.06 01-OCT-07:10 0.00 0.00 0.00 0.00 125.14 14-OCT-16:00 21.51 26-OCT-14:00
November 180.00 01-NOV-00:10 392.73 01-NOV-19:10 237.06 01-NOV-06:10 0.00 0.00 0.00 0.00 95.66 17-NOV-16:10 145.12 27-NOV-07:00
December 180.00 01-DEC-00:10 392.73 01-DEC-20:10 237.06 01-DEC-07:10 0.00 0.00 0.00 0.00 83.34 10-DEC-16:10 175.74 15-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   392.73   237.06   0.00 0.00 0.00 0.00 67.19   0.00  
Maximum of Months 180.00   392.73   237.06   0.00 0.00 0.00 0.00 169.49   214.88  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 392.68 01-JAN-19:10 237.03 01-JAN-08:09 0.00 0.00 0.00 0.00 67.18 01-JAN-11:00 153.83 25-JAN-07:00
February 180.00 01-FEB-00:10 392.68 01-FEB-20:10 237.03 01-FEB-07:10 0.00 0.00 0.00 0.00 79.15 11-FEB-16:10 214.87 04-FEB-07:00
March 180.00 01-MAR-00:10 392.68 01-MAR-20:10 237.03 01-MAR-07:10 0.00 0.00 0.00 0.00 98.39 13-MAR-16:00 190.28 16-MAR-07:00
April 180.00 01-APR-00:10 392.68 01-APR-18:10 237.03 01-APR-07:10 0.00 0.00 0.00 0.00 129.86 17-APR-15:10 86.64 02-APR-06:00
May 180.00 01-MAY-00:10 392.68 01-MAY-19:10 237.03 01-MAY-06:10 0.00 0.00 0.00 0.00 143.35 29-MAY-16:00 21.53 10-MAY-15:00
June 180.00 01-JUN-00:10 392.68 01-JUN-19:10 237.03 01-JUN-06:10 0.00 0.00 0.00 0.00 125.89 10-JUN-16:00 7.88 05-JUN-15:00
July 180.00 01-JUL-00:10 392.68 01-JUL-18:10 237.03 01-JUL-07:10 0.00 0.00 0.00 0.00 169.48 29-JUL-16:00 7.90 14-JUL-17:40
August 180.00 01-AUG-00:10 392.68 01-AUG-19:10 237.03 01-AUG-06:10 0.00 0.00 0.00 0.00 131.39 21-AUG-16:00 14.30 28-AUG-13:00
September 180.00 01-SEP-00:10 392.68 01-SEP-19:10 237.03 01-SEP-06:10 0.00 0.00 0.00 0.00 131.35 20-SEP-16:00 0.00 01-SEP-00:10
October 180.00 01-OCT-00:10 392.68 01-OCT-18:10 237.03 01-OCT-07:10 0.00 0.00 0.00 0.00 125.12 14-OCT-16:00 21.50 26-OCT-14:00
November 180.00 01-NOV-00:10 392.68 01-NOV-19:10 237.03 01-NOV-06:10 0.00 0.00 0.00 0.00 95.65 17-NOV-16:08 145.11 27-NOV-07:00
December 180.00 01-DEC-00:10 392.68 01-DEC-20:10 237.03 01-DEC-07:10 0.00 0.00 0.00 0.00 83.33 10-DEC-16:08 175.73 15-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   392.68   237.03   0.00 0.00 0.00 0.00 67.18   0.00  
Maximum of Months 180.00   392.68   237.03   0.00 0.00 0.00 0.00 169.48   214.87  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 180.00 01-JAN-00:10 246.88 01-JAN-19:10 232.26 01-JAN-08:09 0.00 0.00 0.00 0.00 34.38 01-JAN-11:00 78.72 25-JAN-07:00
February 180.00 01-FEB-00:10 246.88 01-FEB-20:10 232.26 01-FEB-07:10 0.00 0.00 0.00 0.00 37.80 11-FEB-16:50 109.94 04-FEB-07:00
March 180.00 01-MAR-00:10 246.88 01-MAR-20:10 232.26 01-MAR-07:10 0.00 0.00 0.00 0.00 50.35 13-MAR-16:00 97.37 16-MAR-07:00
April 180.00 01-APR-00:10 246.88 01-APR-18:10 232.26 01-APR-07:10 0.00 0.00 0.00 0.00 66.44 17-APR-15:10 44.33 02-APR-06:00
May 180.00 01-MAY-00:10 246.88 01-MAY-19:10 232.26 01-MAY-06:10 0.00 0.00 0.00 0.00 73.35 29-MAY-16:00 11.02 10-MAY-15:00
June 180.00 01-JUN-00:10 246.88 01-JUN-19:10 232.26 01-JUN-06:10 0.00 0.00 0.00 0.00 64.42 10-JUN-16:00 4.03 05-JUN-15:00
July 180.00 01-JUL-00:10 246.88 01-JUL-18:10 232.26 01-JUL-07:10 0.00 0.00 0.00 0.00 86.71 29-JUL-16:00 4.04 14-JUL-17:40
August 180.00 01-AUG-00:10 246.88 01-AUG-19:10 232.26 01-AUG-06:10 0.00 0.00 0.00 0.00 67.23 21-AUG-16:00 6.56 28-AUG-13:00
September 180.00 01-SEP-00:10 246.88 01-SEP-19:10 232.26 01-SEP-06:10 0.00 0.00 0.00 0.00 67.19 20-SEP-16:00 0.00 01-SEP-00:10
October 180.00 01-OCT-00:10 246.88 01-OCT-18:10 232.26 01-OCT-07:10 0.00 0.00 0.00 0.00 63.99 14-OCT-16:00 11.01 26-OCT-14:00
November 180.00 01-NOV-00:10 246.88 01-NOV-19:10 232.26 01-NOV-06:10 0.00 0.00 0.00 0.00 47.73 17-NOV-16:10 74.25 27-NOV-07:00
December 180.00 01-DEC-00:10 246.88 01-DEC-20:10 232.26 01-DEC-07:10 0.00 0.00 0.00 0.00 40.79 10-DEC-16:10 89.92 15-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 180.00   246.88   232.26   0.00 0.00 0.00 0.00 34.38   0.00  
Maximum of Months 180.00   246.88   232.26   0.00 0.00 0.00 0.00 86.71   109.94  



Table of Contents

Report: PeakSpaceGainsMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 26988.77 02-JAN-00:10 3823.39 02-JAN-20:10 6747.90 01-JAN-07:10 0.00 0.00 0.00 0.00 231.23 02-JAN-14:00 394.74 25-JAN-05:30
February 26988.77 01-FEB-00:10 3823.39 01-FEB-20:10 6747.90 01-FEB-07:10 0.00 0.00 0.00 0.00 238.03 11-FEB-14:00 535.61 04-FEB-07:00
March 26988.77 01-MAR-00:10 3823.39 01-MAR-20:10 6747.90 01-MAR-07:10 0.00 0.00 0.00 0.00 232.47 13-MAR-16:00 483.07 16-MAR-05:00
April 26988.77 01-APR-00:10 3823.39 03-APR-19:10 6747.90 01-APR-06:10 0.00 0.00 0.00 0.00 311.18 17-APR-15:00 235.20 02-APR-06:00
May 26988.77 01-MAY-00:10 3823.39 01-MAY-19:10 6747.90 01-MAY-06:10 0.00 0.00 0.00 0.00 380.36 22-MAY-13:00 52.84 01-MAY-05:00
June 26988.77 01-JUN-00:10 3823.39 01-JUN-19:10 6747.90 01-JUN-06:10 0.00 0.00 0.00 0.00 318.06 11-JUN-13:00 4.11 05-JUN-22:00
July 26988.77 01-JUL-00:10 3823.39 03-JUL-19:10 6747.90 01-JUL-06:10 0.00 0.00 0.00 0.00 411.87 29-JUL-16:00 18.08 14-JUL-22:00
August 26988.77 01-AUG-00:10 3823.39 01-AUG-19:10 6747.90 01-AUG-06:10 0.00 0.00 0.00 0.00 367.47 23-AUG-13:00 0.00 01-AUG-00:10
September 26988.77 01-SEP-00:10 3823.39 01-SEP-19:10 6747.90 01-SEP-06:10 0.00 0.00 0.00 0.00 321.83 13-SEP-13:00 7.12 05-SEP-06:00
October 26988.77 01-OCT-23:10 3823.39 02-OCT-19:10 6747.90 01-OCT-06:10 0.00 0.00 0.00 0.00 322.58 09-OCT-11:00 40.85 28-OCT-03:00
November 26988.77 01-NOV-00:10 3823.39 01-NOV-19:10 6747.90 01-NOV-06:10 0.00 0.00 0.00 0.00 256.54 17-NOV-15:00 376.21 27-NOV-03:00
December 26988.77 01-DEC-00:10 3823.39 01-DEC-20:10 6747.90 01-DEC-07:10 0.00 0.00 0.00 0.00 229.18 10-DEC-14:00 448.49 15-DEC-05:30
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 26988.77   3823.39   6747.90   0.00 0.00 0.00 0.00 229.18   0.00  
Maximum of Months 26988.77   3823.39   6747.90   0.00 0.00 0.00 0.00 411.87   535.61  



Table of Contents

Report: PeakSpaceGainsMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 26988.77 02-JAN-00:10 3823.39 02-JAN-20:10 6747.90 01-JAN-07:10 0.00 0.00 0.00 0.00 231.06 02-JAN-14:00 395.42 25-JAN-05:30
February 26988.77 01-FEB-00:10 3823.39 01-FEB-20:10 6747.90 01-FEB-07:10 0.00 0.00 0.00 0.00 234.84 11-FEB-14:00 537.23 04-FEB-07:00
March 26988.77 01-MAR-00:10 3823.39 01-MAR-20:10 6747.90 01-MAR-07:10 0.00 0.00 0.00 0.00 229.63 13-MAR-16:00 483.92 16-MAR-05:00
April 26988.77 01-APR-00:10 3823.39 03-APR-19:10 6747.90 01-APR-06:10 0.00 0.00 0.00 0.00 308.57 17-APR-15:00 236.47 02-APR-06:00
May 26988.77 01-MAY-00:10 3823.39 01-MAY-19:10 6747.90 01-MAY-06:10 0.00 0.00 0.00 0.00 377.39 22-MAY-13:00 53.82 01-MAY-05:00
June 26988.77 01-JUN-00:10 3823.39 01-JUN-19:10 6747.90 01-JUN-06:10 0.00 0.00 0.00 0.00 315.30 11-JUN-13:00 6.51 05-JUN-22:00
July 26988.77 01-JUL-00:10 3823.39 03-JUL-19:10 6747.90 01-JUL-06:10 0.00 0.00 0.00 0.00 410.02 29-JUL-16:00 20.46 14-JUL-22:00
August 26988.77 01-AUG-00:10 3823.39 01-AUG-19:10 6747.90 01-AUG-06:10 0.00 0.00 0.00 0.00 365.20 23-AUG-13:00 0.00 01-AUG-00:10
September 26988.77 01-SEP-00:10 3823.39 01-SEP-19:10 6747.90 01-SEP-06:10 0.00 0.00 0.00 0.00 319.30 13-SEP-13:00 8.94 04-SEP-22:00
October 26988.77 01-OCT-23:10 3823.39 02-OCT-19:10 6747.90 01-OCT-06:10 0.00 0.00 0.00 0.00 320.77 09-OCT-11:00 41.88 28-OCT-03:00
November 26988.77 01-NOV-00:10 3823.39 01-NOV-19:10 6747.90 01-NOV-06:10 0.00 0.00 0.00 0.00 253.80 17-NOV-15:00 377.24 27-NOV-03:00
December 26988.77 01-DEC-00:10 3823.39 01-DEC-20:10 6747.90 01-DEC-07:10 0.00 0.00 0.00 0.00 226.95 10-DEC-14:00 449.17 15-DEC-05:30
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 26988.77   3823.39   6747.90   0.00 0.00 0.00 0.00 226.95   0.00  
Maximum of Months 26988.77   3823.39   6747.90   0.00 0.00 0.00 0.00 410.02   537.23  



Table of Contents

Report: PeakSpaceGainsMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2401.70 02-JAN-00:10 1020.78 02-JAN-20:10 15112.11 01-JAN-07:10 22492.83 01-JAN-16:10 0.00 0.00 0.00 129.46 02-JAN-15:00 366.99 25-JAN-08:10
February 2401.70 01-FEB-00:10 1020.78 01-FEB-20:10 15112.11 01-FEB-07:10 22492.83 01-FEB-16:10 0.00 0.00 0.00 140.69 11-FEB-14:00 483.61 04-FEB-07:00
March 2401.70 01-MAR-00:10 1020.78 01-MAR-20:10 15112.11 01-MAR-07:10 22492.83 01-MAR-16:10 0.00 0.00 0.00 139.49 13-MAR-16:00 458.26 16-MAR-07:00
April 2401.70 01-APR-00:10 1020.78 03-APR-19:10 15112.11 01-APR-06:10 22492.83 01-APR-15:09 0.00 0.00 0.00 210.97 17-APR-15:00 221.37 02-APR-06:00
May 2401.70 01-MAY-00:10 1020.78 01-MAY-19:10 15112.11 01-MAY-06:10 22492.83 01-MAY-15:09 0.00 0.00 0.00 266.85 22-MAY-13:00 64.93 10-MAY-15:00
June 2401.70 01-JUN-00:10 1020.78 01-JUN-19:10 15112.11 01-JUN-06:10 22492.83 01-JUN-15:09 0.00 0.00 0.00 212.51 11-JUN-13:00 34.94 05-JUN-15:00
July 2401.70 01-JUL-00:10 1020.78 03-JUL-19:10 15112.11 01-JUL-06:10 22492.83 01-JUL-15:09 0.00 0.00 0.00 296.42 29-JUL-16:00 35.30 14-JUL-20:00
August 2401.70 01-AUG-00:10 1020.78 01-AUG-19:10 15112.11 01-AUG-06:10 22492.83 01-AUG-15:09 0.00 0.00 0.00 255.54 23-AUG-13:00 51.53 28-AUG-12:00
September 2401.70 01-SEP-00:10 1020.78 01-SEP-19:10 15112.11 01-SEP-06:10 22492.83 01-SEP-15:09 0.00 0.00 0.00 211.96 20-SEP-16:00 36.80 05-SEP-06:10
October 2401.70 01-OCT-23:10 1020.78 02-OCT-19:10 15112.11 01-OCT-06:10 22492.83 01-OCT-15:09 0.00 0.00 0.00 211.92 09-OCT-11:00 55.97 26-OCT-14:00
November 2401.70 01-NOV-00:10 1020.78 01-NOV-19:10 15112.11 01-NOV-06:10 22492.83 01-NOV-15:09 0.00 0.00 0.00 156.24 17-NOV-15:00 343.67 27-NOV-07:00
December 2401.70 01-DEC-00:10 1020.78 01-DEC-20:10 15112.11 01-DEC-07:10 22492.83 01-DEC-16:10 0.00 0.00 0.00 130.11 10-DEC-15:00 437.65 15-DEC-07:30
                               
Annual Sum or Average                 0.00 0.00 0.00        
Minimum of Months 2401.70   1020.78   15112.11   22492.83   0.00 0.00 0.00 129.46   34.94  
Maximum of Months 2401.70   1020.78   15112.11   22492.83   0.00 0.00 0.00 296.42   483.61  



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2395.44 02-JAN-00:10 1357.44 02-JAN-20:10 0.00 0.00 0.00 0.00 0.00 184.25 02-JAN-14:00 326.09 25-JAN-07:00
February 2395.44 01-FEB-00:10 1357.44 01-FEB-20:10 0.00 0.00 0.00 0.00 0.00 195.05 11-FEB-14:00 456.69 04-FEB-07:00
March 2395.44 01-MAR-00:10 1357.44 01-MAR-20:10 0.00 0.00 0.00 0.00 0.00 204.31 13-MAR-16:00 404.05 16-MAR-07:00
April 2395.44 01-APR-00:10 1357.44 03-APR-19:10 0.00 0.00 0.00 0.00 0.00 261.28 17-APR-15:00 182.38 02-APR-06:00
May 2395.44 01-MAY-00:10 1357.44 01-MAY-19:10 0.00 0.00 0.00 0.00 0.00 316.25 22-MAY-13:00 13.51 01-MAY-05:40
June 2395.44 01-JUN-00:10 1357.44 01-JUN-19:10 0.00 0.00 0.00 0.00 0.00 257.61 11-JUN-13:00 0.00 01-JUN-00:10
July 2395.44 01-JUL-00:10 1357.44 03-JUL-19:10 0.00 0.00 0.00 0.00 0.00 331.70 29-JUL-16:00 0.00 01-JUL-00:10
August 2395.44 01-AUG-00:10 1357.44 01-AUG-19:10 0.00 0.00 0.00 0.00 0.00 297.02 23-AUG-13:00 0.00 01-AUG-00:10
September 2395.44 01-SEP-00:10 1357.44 01-SEP-19:10 0.00 0.00 0.00 0.00 0.00 260.87 13-SEP-13:00 0.00 01-SEP-00:10
October 2395.44 01-OCT-23:10 1357.44 02-OCT-19:10 0.00 0.00 0.00 0.00 0.00 267.34 09-OCT-11:00 0.15 28-OCT-03:20
November 2395.44 01-NOV-00:10 1357.44 01-NOV-19:10 0.00 0.00 0.00 0.00 0.00 206.61 17-NOV-15:00 307.44 27-NOV-07:00
December 2395.44 01-DEC-00:10 1357.44 01-DEC-20:10 0.00 0.00 0.00 0.00 0.00 181.64 10-DEC-14:00 372.95 15-DEC-07:00
                           
Annual Sum or Average         0.00 0.00 0.00 0.00 0.00        
Minimum of Months 2395.44   1357.44   0.00 0.00 0.00 0.00 0.00 181.64   0.00  
Maximum of Months 2395.44   1357.44   0.00 0.00 0.00 0.00 0.00 331.70   456.69  



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 23633.95 02-JAN-19:10 53675.50 72090.20 57488.97 0.00 0.00 0.00 0.00 0.00 0.00
February 23184.38 16-FEB-19:10 53675.50 72090.20 57488.97 0.00 0.00 0.00 0.00 0.00 0.00
March 22983.63 29-MAR-18:20 17891.83 24030.07 19162.99 0.00 0.00 0.00 0.00 0.00 0.00
April 23124.45 17-APR-19:10 17891.83 27034.00 20227.60 0.00 0.00 0.00 0.00 0.00 0.00
May 23528.64 31-MAY-18:50 8945.92 12015.03 9581.50 0.00 0.00 0.00 0.00 0.00 0.00
June 23968.66 28-JUN-18:40 8945.92 12015.03 9581.50 0.00 0.00 0.00 0.00 0.00 0.00
July 24888.51 27-JUL-18:20 17891.83 24030.07 19162.99 0.00 0.00 0.00 0.00 0.00 0.00
August 25278.77 02-AUG-18:10 53675.50 72090.20 57488.97 0.00 0.00 0.00 0.00 0.00 0.00
September 25208.46 18-SEP-18:10 53675.50 72090.20 57488.97 0.00 0.00 0.00 0.00 0.00 0.00
October 24955.82 05-OCT-18:10 53675.50 72090.20 57488.97 0.00 0.00 0.00 0.00 0.00 0.00
November 24478.59 02-NOV-18:10 53675.50 72090.20 57488.97 0.00 0.00 0.00 0.00 0.00 0.00
December 23944.13 07-DEC-19:10 53675.50 72090.20 57488.97 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 22983.63   8945.92 12015.03 9581.50 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 25278.77   53675.50 72090.20 57488.97 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 3333.07 02-JAN-11:35 519.79 381.83 505.18 0.00 0.00 0.00 0.00 82.83 0.00
February 3216.88 11-FEB-11:35 779.69 381.83 505.18 0.00 0.00 0.00 0.00 109.65 0.00
March 3150.94 04-MAR-11:35 779.69 381.83 505.18 0.00 0.00 0.00 0.00 101.35 0.00
April 2974.02 15-APR-10:35 779.69 381.83 505.18 0.00 0.00 0.00 0.00 164.97 0.00
May 2886.25 22-MAY-18:10 5457.82 3665.58 3897.11 0.00 0.00 0.00 0.00 187.21 0.00
June 2975.80 11-JUN-10:35 779.69 458.20 577.35 0.00 0.00 0.00 0.00 201.98 0.00
July 3123.47 29-JUL-17:13 2339.06 1374.59 1515.54 0.00 0.00 0.00 0.00 249.03 0.00
August 3099.79 19-AUG-10:35 779.69 381.83 505.18 0.00 0.00 0.00 0.00 205.88 0.00
September 3317.76 24-SEP-10:35 779.69 458.20 577.35 0.00 0.00 0.00 0.00 172.73 0.00
October 3354.34 07-OCT-10:35 779.69 381.83 505.18 0.00 0.00 0.00 0.00 181.99 0.00
November 3526.28 08-NOV-11:35 519.79 381.83 505.18 0.00 0.00 0.00 0.00 86.54 0.00
December 3453.80 09-DEC-11:35 779.69 381.83 505.18 0.00 0.00 0.00 0.00 87.12 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2886.25   519.79 381.83 505.18 0.00 0.00 0.00 0.00 82.83 0.00
Maximum of Months 3526.28   5457.82 3665.58 3897.11 0.00 0.00 0.00 0.00 249.03 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2132.50 02-JAN-19:10 6320.16 4244.75 4512.87 0.00 0.00 0.00 0.00 16.91 0.00
February 2137.29 11-FEB-19:10 5417.28 3714.16 4011.44 0.00 0.00 0.00 0.00 19.36 0.00
March 2212.58 13-MAR-18:10 6320.16 4244.75 4512.87 0.00 0.00 0.00 0.00 54.99 0.00
April 2292.13 17-APR-18:10 6320.16 4244.75 4512.87 0.00 0.00 0.00 0.00 71.21 0.00
May 2308.51 22-MAY-18:10 6320.16 4244.75 4512.87 0.00 0.00 0.00 0.00 74.21 0.00
June 2348.05 29-JUN-18:10 6320.16 4244.75 4512.87 0.00 0.00 0.00 0.00 70.59 0.00
July 2384.21 27-JUL-18:10 6320.16 4244.75 4512.87 0.00 0.00 0.00 0.00 84.26 0.00
August 2342.66 17-AUG-18:10 6320.16 4244.75 4512.87 0.00 0.00 0.00 0.00 68.94 0.00
September 2335.10 18-SEP-18:10 6320.16 4244.75 4512.87 0.00 0.00 0.00 0.00 73.55 0.00
October 2279.37 05-OCT-18:10 6320.16 4244.75 4512.87 0.00 0.00 0.00 0.00 61.05 0.00
November 2215.54 08-NOV-19:10 6320.16 4244.75 4512.87 0.00 0.00 0.00 0.00 39.95 0.00
December 2147.11 09-DEC-19:10 5417.28 3714.16 4011.44 0.00 0.00 0.00 0.00 31.99 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2132.50   5417.28 3714.16 4011.44 0.00 0.00 0.00 0.00 16.91 0.00
Maximum of Months 2384.21   6320.16 4244.75 4512.87 0.00 0.00 0.00 0.00 84.26 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2168.46 02-JAN-19:50 222.77 1322.39 795.27 0.00 0.00 0.00 0.00 26.90 0.00
February 2188.34 16-FEB-19:15 445.54 2644.77 1590.53 0.00 0.00 0.00 0.00 44.72 0.00
March 2289.15 27-MAR-18:20 445.54 2644.77 1590.53 0.00 0.00 0.00 0.00 88.66 0.00
April 2444.62 17-APR-18:10 1336.61 7934.32 4771.59 0.00 0.00 0.00 0.00 169.97 0.00
May 2487.61 22-MAY-18:10 1336.61 7934.32 4771.59 0.00 0.00 0.00 0.00 175.62 0.00
June 2586.85 11-JUN-10:35 190.94 991.79 706.90 0.00 0.00 0.00 0.00 188.02 0.00
July 2616.72 29-JUL-10:35 190.94 826.49 618.54 0.00 0.00 0.00 0.00 207.63 0.00
August 2567.04 20-AUG-10:35 190.94 991.79 706.90 0.00 0.00 0.00 0.00 190.44 0.00
September 2494.10 18-SEP-18:10 1336.61 7934.32 4771.59 0.00 0.00 0.00 0.00 175.40 0.00
October 2418.43 05-OCT-18:10 1336.61 7934.32 4771.59 0.00 0.00 0.00 0.00 146.75 0.00
November 2328.93 22-NOV-19:03 1336.61 7934.32 4771.59 0.00 0.00 0.00 0.00 109.44 0.00
December 2239.14 07-DEC-19:20 445.54 2644.77 1590.53 0.00 0.00 0.00 0.00 65.58 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2168.46   190.94 826.49 618.54 0.00 0.00 0.00 0.00 26.90 0.00
Maximum of Months 2616.72   1336.61 7934.32 4771.59 0.00 0.00 0.00 0.00 207.63 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 983.57 13-JAN-21:00 171.36 273.10 242.16 0.00 0.00 0.00 0.00 37.67 0.00
February 991.37 17-FEB-20:20 171.36 273.10 242.16 0.00 0.00 0.00 0.00 32.44 0.00
March 1037.18 30-MAR-20:00 171.36 273.10 242.16 0.00 0.00 0.00 0.00 32.43 0.00
April 1112.03 17-APR-19:10 342.72 546.20 484.31 0.00 0.00 0.00 0.00 64.19 0.00
May 1189.99 31-MAY-18:15 342.72 485.51 458.82 0.00 0.00 0.00 0.00 80.31 0.00
June 1293.28 11-JUN-10:35 146.88 182.07 203.92 0.00 0.00 0.00 0.00 108.37 0.00
July 1313.92 29-JUL-10:35 146.88 151.73 178.43 0.00 0.00 0.00 0.00 119.30 0.00
August 1294.34 19-AUG-10:35 146.88 151.73 178.43 0.00 0.00 0.00 0.00 114.12 0.00
September 1282.11 24-SEP-10:35 146.88 182.07 203.92 0.00 0.00 0.00 0.00 104.16 0.00
October 1134.02 05-OCT-19:10 171.36 273.10 242.16 0.00 0.00 0.00 0.00 78.88 0.00
November 1079.02 22-NOV-21:00 171.36 273.10 242.16 0.00 0.00 0.00 0.00 62.77 0.00
December 1022.97 07-DEC-21:00 171.36 273.10 242.16 0.00 0.00 0.00 0.00 32.42 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 983.57   146.88 151.73 178.43 0.00 0.00 0.00 0.00 32.42 0.00
Maximum of Months 1313.92   342.72 546.20 484.31 0.00 0.00 0.00 0.00 119.30 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 36756.05 02-JAN-21:00 705.60 337.37 4572.80 39726.58 0.00 0.00 0.00 0.00 39.51
February 36726.14 16-FEB-21:00 705.60 337.37 4572.80 39726.58 0.00 0.00 0.00 5.29 0.00
March 37145.35 27-MAR-20:00 705.60 337.37 4572.80 39726.58 0.00 0.00 0.00 21.18 0.00
April 37390.22 17-APR-20:00 705.60 337.37 4572.80 39726.58 0.00 0.00 0.00 38.34 0.00
May 37723.94 31-MAY-20:00 705.60 337.37 4572.80 39726.58 0.00 0.00 0.00 112.68 0.00
June 37825.24 08-JUN-20:00 705.60 337.37 4572.80 39726.58 0.00 0.00 0.00 141.57 0.00
July 37904.85 27-JUL-20:00 705.60 337.37 4572.80 39726.58 0.00 0.00 0.00 141.80 0.00
August 37806.30 31-AUG-20:00 705.60 337.37 4572.80 39726.58 0.00 0.00 0.00 113.07 0.00
September 37764.94 21-SEP-20:00 705.60 337.37 4572.80 39726.58 0.00 0.00 0.00 141.07 0.00
October 37529.17 05-OCT-20:00 705.60 337.37 4572.80 39726.58 0.00 0.00 0.00 111.65 0.00
November 37207.32 02-NOV-20:00 705.60 337.37 4572.80 39726.58 0.00 0.00 0.00 81.46 0.00
December 36829.09 06-DEC-21:00 705.60 337.37 4572.80 39726.58 0.00 0.00 0.00 19.78 0.00
                       
Annual Sum or Average             0.00 0.00 0.00    
Minimum of Months 36726.14   705.60 337.37 4572.80 39726.58 0.00 0.00 0.00 0.00 0.00
Maximum of Months 37904.85   705.60 337.37 4572.80 39726.58 0.00 0.00 0.00 141.80 39.51



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 13713.20 15-JAN-11:35 10245.60 1451.48 812.86 0.00 0.00 0.00 0.00 101.22 0.00
February 13613.36 11-FEB-11:35 10245.60 1209.57 711.25 0.00 0.00 0.00 0.00 263.69 0.00
March 13396.57 04-MAR-11:35 10245.60 1209.57 711.25 0.00 0.00 0.00 0.00 243.12 0.00
April 12786.19 17-APR-18:10 71719.20 11611.87 5486.82 0.00 0.00 0.00 0.00 396.77 0.00
May 12842.85 22-MAY-18:10 71719.20 11611.87 5486.82 0.00 0.00 0.00 0.00 414.89 0.00
June 12992.97 29-JUN-18:10 71719.20 11611.87 5486.82 0.00 0.00 0.00 0.00 395.94 0.00
July 13326.03 27-JUL-18:10 71719.20 11611.87 5486.82 0.00 0.00 0.00 0.00 470.43 0.00
August 13004.92 02-AUG-18:10 71719.20 11611.87 5486.82 0.00 0.00 0.00 0.00 391.23 0.00
September 13867.31 24-SEP-10:35 10245.60 1451.48 812.86 0.00 0.00 0.00 0.00 408.48 0.00
October 13955.98 07-OCT-10:35 10245.60 1209.57 711.25 0.00 0.00 0.00 0.00 430.99 0.00
November 14288.84 08-NOV-11:35 6830.40 1209.57 711.25 0.00 0.00 0.00 0.00 232.82 0.00
December 14446.24 09-DEC-11:35 10245.60 1209.57 711.25 0.00 0.00 0.00 0.00 220.33 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 12786.19   6830.40 1209.57 711.25 0.00 0.00 0.00 0.00 101.22 0.00
Maximum of Months 14446.24   71719.20 11611.87 5486.82 0.00 0.00 0.00 0.00 470.43 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 41098.71 02-JAN-19:10 212907.24 63196.36 57008.13 0.00 0.00 0.00 0.00 253.65 0.00
February 40953.48 11-FEB-19:10 182491.92 55296.81 50673.90 0.00 0.00 0.00 0.00 299.49 0.00
March 42336.72 13-MAR-18:10 212907.24 63196.36 57008.13 0.00 0.00 0.00 0.00 883.67 0.00
April 43779.35 17-APR-18:10 212907.24 63196.36 57008.13 0.00 0.00 0.00 0.00 1150.46 0.00
May 44232.74 22-MAY-18:10 212907.24 63196.36 57008.13 0.00 0.00 0.00 0.00 1196.16 0.00
June 44792.13 29-JUN-18:10 212907.24 63196.36 57008.13 0.00 0.00 0.00 0.00 1141.21 0.00
July 45394.92 27-JUL-18:10 212907.24 63196.36 57008.13 0.00 0.00 0.00 0.00 1366.82 0.00
August 44668.12 02-AUG-18:10 212907.24 63196.36 57008.13 0.00 0.00 0.00 0.00 1131.64 0.00
September 44809.15 24-SEP-10:35 30415.32 7899.54 8445.65 0.00 0.00 0.00 0.00 1248.71 0.00
October 43584.88 05-OCT-18:10 212907.24 63196.36 57008.13 0.00 0.00 0.00 0.00 983.06 0.00
November 42600.44 19-NOV-11:35 30415.32 7899.54 8445.65 0.00 0.00 0.00 0.00 734.34 0.00
December 43417.94 09-DEC-11:35 30415.32 6582.95 7389.94 0.00 0.00 0.00 0.00 792.81 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 40953.48   30415.32 6582.95 7389.94 0.00 0.00 0.00 0.00 253.65 0.00
Maximum of Months 45394.92   212907.24 63196.36 57008.13 0.00 0.00 0.00 0.00 1366.82 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 3278.88 26-JAN-16:02 583.20 659.78 410.90 0.00 0.00 0.00 0.00 0.00 26.01
February 3301.31 24-FEB-16:02 583.20 659.78 410.90 0.00 0.00 0.00 0.00 28.90 0.00
March 3235.14 15-MAR-15:01 680.40 769.75 479.39 0.00 0.00 0.00 0.00 0.00 65.95
April 3217.13 15-APR-15:02 324.00 777.60 458.31 0.00 0.00 0.00 0.00 100.68 0.00
May 3220.81 16-MAY-15:02 583.20 659.78 410.90 0.00 0.00 0.00 0.00 92.46 0.00
June 3182.98 10-JUN-15:02 324.00 777.60 458.31 0.00 0.00 0.00 0.00 107.16 0.00
July 3229.87 28-JUL-15:02 583.20 659.78 410.90 0.00 0.00 0.00 0.00 143.76 0.00
August 3224.39 31-AUG-15:02 583.20 659.78 410.90 0.00 0.00 0.00 0.00 111.92 0.00
September 3230.81 17-SEP-15:02 324.00 777.60 458.31 0.00 0.00 0.00 0.00 99.46 0.00
October 3202.25 06-OCT-15:02 583.20 659.78 410.90 0.00 0.00 0.00 0.00 78.51 0.00
November 3172.94 17-NOV-16:02 583.20 659.78 410.90 0.00 0.00 0.00 0.00 78.14 0.00
December 3202.74 06-DEC-16:02 583.20 659.78 410.90 0.00 0.00 0.00 0.00 40.15 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 3172.94   324.00 659.78 410.90 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3301.31   680.40 777.60 479.39 0.00 0.00 0.00 0.00 143.76 65.95



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 3237.51 26-JAN-16:02 583.20 659.70 410.85 0.00 0.00 0.00 0.00 0.00 23.44
February 3285.56 24-FEB-16:02 583.20 659.70 410.85 0.00 0.00 0.00 0.00 30.50 0.00
March 3216.86 15-MAR-15:01 680.40 769.66 479.33 0.00 0.00 0.00 0.00 0.00 64.10
April 3252.36 15-APR-18:02 702.00 2356.09 774.30 0.00 0.00 0.00 0.00 85.53 0.00
May 3248.03 20-MAY-15:02 324.00 777.51 458.26 0.00 0.00 0.00 0.00 87.68 0.00
June 3212.71 10-JUN-15:02 324.00 777.51 458.26 0.00 0.00 0.00 0.00 107.20 0.00
July 3262.61 28-JUL-15:02 583.20 659.70 410.85 0.00 0.00 0.00 0.00 143.90 0.00
August 3205.15 19-AUG-15:02 324.00 777.51 458.26 0.00 0.00 0.00 0.00 107.06 0.00
September 3195.62 30-SEP-15:02 324.00 777.51 458.26 0.00 0.00 0.00 0.00 99.96 0.00
October 3202.84 18-OCT-15:02 583.20 659.70 410.85 0.00 0.00 0.00 0.00 55.19 0.00
November 3163.54 06-NOV-16:02 583.20 659.70 410.85 0.00 0.00 0.00 0.00 62.61 0.00
December 3135.74 04-DEC-16:02 583.20 659.70 410.85 0.00 0.00 0.00 0.00 35.86 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 3135.74   324.00 659.70 410.85 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3285.56   702.00 2356.09 774.30 0.00 0.00 0.00 0.00 143.90 64.10



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 746.42 02-JAN-14:30 0.00 69.11 67.08 0.00 0.00 0.00 0.00 18.71 0.00
February 683.69 11-FEB-14:30 0.00 81.45 74.82 0.00 0.00 0.00 0.00 18.56 0.00
March 569.07 02-MAR-14:30 0.00 69.11 67.08 0.00 0.00 0.00 0.00 5.57 0.00
April 523.51 15-APR-19:10 0.00 246.81 170.27 0.00 0.00 0.00 0.00 17.35 0.00
May 507.78 22-MAY-20:20 0.00 219.66 180.59 0.00 0.00 0.00 0.00 16.07 0.00
June 532.63 03-JUN-21:00 0.00 246.81 180.59 0.00 0.00 0.00 0.00 20.33 0.00
July 567.35 29-JUL-19:10 0.00 246.81 170.27 0.00 0.00 0.00 0.00 27.26 0.00
August 551.14 20-AUG-20:03 0.00 740.44 541.78 0.00 0.00 0.00 0.00 18.33 0.00
September 654.23 30-SEP-13:30 0.00 81.45 74.82 0.00 0.00 0.00 0.00 25.05 0.00
October 714.26 25-OCT-12:40 0.00 69.11 67.08 0.00 0.00 0.00 0.00 22.21 0.00
November 747.21 07-NOV-13:40 0.00 69.11 67.08 0.00 0.00 0.00 0.00 16.03 0.00
December 755.58 03-DEC-14:00 0.00 81.45 74.82 0.00 0.00 0.00 0.00 3.50 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 507.78   0.00 69.11 67.08 0.00 0.00 0.00 0.00 3.50 0.00
Maximum of Months 755.58   0.00 740.44 541.78 0.00 0.00 0.00 0.00 27.26 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1129.77 16-JAN-16:02 324.00 488.83 449.03 0.00 0.00 0.00 0.00 0.00 0.73
February 1188.46 24-FEB-19:01 970.20 1538.07 885.15 0.00 0.00 0.00 0.00 0.00 2.02
March 1185.13 14-MAR-18:02 831.60 1318.35 758.70 0.00 0.00 0.00 0.00 4.58 0.00
April 1198.42 17-APR-18:02 831.60 1318.35 758.70 0.00 0.00 0.00 0.00 24.03 0.00
May 1183.38 20-MAY-18:02 702.00 1481.29 758.70 0.00 0.00 0.00 0.00 17.43 0.00
June 1180.01 14-JUN-18:02 831.60 1318.35 758.70 0.00 0.00 0.00 0.00 21.62 0.00
July 1188.42 29-JUL-18:02 702.00 1481.29 758.70 0.00 0.00 0.00 0.00 33.82 0.00
August 1172.18 19-AUG-18:02 702.00 1481.29 758.70 0.00 0.00 0.00 0.00 21.92 0.00
September 1166.52 01-SEP-18:02 831.60 1318.35 758.70 0.00 0.00 0.00 0.00 23.60 0.00
October 1184.47 17-OCT-18:02 831.60 1318.35 758.70 0.00 0.00 0.00 0.00 9.22 0.00
November 1177.48 20-NOV-19:02 831.60 1318.35 758.70 0.00 0.00 0.00 0.00 11.05 0.00
December 1154.06 09-DEC-19:02 702.00 1481.29 758.70 0.00 0.00 0.00 0.00 7.54 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1129.77   324.00 488.83 449.03 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 1198.42   970.20 1538.07 885.15 0.00 0.00 0.00 0.00 33.82 2.02



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2952.88 26-JAN-16:02 583.20 659.78 410.90 0.00 0.00 0.00 0.00 0.00 24.87
February 2976.13 24-FEB-19:01 970.20 2446.69 903.46 0.00 0.00 0.00 0.00 0.00 12.82
March 2936.42 20-MAR-15:01 680.40 769.75 479.39 0.00 0.00 0.00 0.00 0.00 38.32
April 2890.40 16-APR-15:02 324.00 777.60 458.31 0.00 0.00 0.00 0.00 104.70 0.00
May 2859.58 20-MAY-15:02 324.00 777.60 458.31 0.00 0.00 0.00 0.00 87.82 0.00
June 2860.88 01-JUN-15:02 583.20 659.78 410.90 0.00 0.00 0.00 0.00 87.11 0.00
July 2948.35 29-JUL-15:02 324.00 777.60 458.31 0.00 0.00 0.00 0.00 145.32 0.00
August 2869.07 31-AUG-15:02 583.20 659.78 410.90 0.00 0.00 0.00 0.00 112.13 0.00
September 2876.42 30-SEP-15:02 324.00 777.60 458.31 0.00 0.00 0.00 0.00 99.66 0.00
October 2946.57 25-OCT-15:02 583.20 659.78 410.90 0.00 0.00 0.00 0.00 77.83 0.00
November 2861.98 14-NOV-16:02 583.20 659.78 410.90 0.00 0.00 0.00 0.00 9.29 0.00
December 2868.86 04-DEC-16:02 583.20 659.78 410.90 0.00 0.00 0.00 0.00 34.97 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2859.58   324.00 659.78 410.90 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 2976.13   970.20 2446.69 903.46 0.00 0.00 0.00 0.00 145.32 38.32



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2758.50 15-JAN-16:02 324.00 777.51 458.26 0.00 0.00 0.00 0.00 27.24 0.00
February 2974.11 22-FEB-16:02 583.20 659.70 410.85 0.00 0.00 0.00 0.00 59.94 0.00
March 2852.41 01-MAR-16:02 583.20 659.70 410.85 0.00 0.00 0.00 0.00 29.51 0.00
April 2953.08 16-APR-15:02 324.00 777.51 458.26 0.00 0.00 0.00 0.00 105.33 0.00
May 2878.67 20-MAY-08:62 324.00 1319.41 979.73 0.00 0.00 0.00 0.00 61.68 0.00
June 2882.64 01-JUN-15:02 583.20 659.70 410.85 0.00 0.00 0.00 0.00 87.15 0.00
July 2976.32 29-JUL-15:02 324.00 777.51 458.26 0.00 0.00 0.00 0.00 145.46 0.00
August 2854.74 19-AUG-15:02 324.00 777.51 458.26 0.00 0.00 0.00 0.00 107.18 0.00
September 2841.01 13-SEP-15:02 583.20 659.70 410.85 0.00 0.00 0.00 0.00 102.85 0.00
October 2814.80 17-OCT-18:02 831.60 2096.92 774.30 0.00 0.00 0.00 0.00 35.89 0.00
November 2817.81 14-NOV-16:02 583.20 659.70 410.85 0.00 0.00 0.00 0.00 12.46 0.00
December 2768.21 03-DEC-19:02 702.00 2356.09 774.30 0.00 0.00 0.00 0.00 0.00 7.85
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2758.50   324.00 659.70 410.85 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 2976.32   831.60 2356.09 979.73 0.00 0.00 0.00 0.00 145.46 7.85



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2793.51 01-JAN-11:35 1508.90 855.07 0.00 0.00 0.00 0.00 0.00 65.72 0.00
February 2758.98 11-FEB-11:35 1508.90 712.56 0.00 0.00 0.00 0.00 0.00 87.66 0.00
March 2767.13 04-MAR-11:35 1508.90 712.56 0.00 0.00 0.00 0.00 0.00 78.78 0.00
April 2970.30 15-APR-10:35 1508.90 712.56 0.00 0.00 0.00 0.00 0.00 107.35 0.00
May 2987.72 20-MAY-10:35 1508.90 712.56 0.00 0.00 0.00 0.00 0.00 105.68 0.00
June 3094.30 11-JUN-10:35 1508.90 855.07 0.00 0.00 0.00 0.00 0.00 128.08 0.00
July 3152.16 30-JUL-10:35 1508.90 855.07 0.00 0.00 0.00 0.00 0.00 138.64 0.00
August 3117.20 19-AUG-10:35 1508.90 712.56 0.00 0.00 0.00 0.00 0.00 134.86 0.00
September 3151.62 24-SEP-10:35 1508.90 855.07 0.00 0.00 0.00 0.00 0.00 118.94 0.00
October 3084.88 07-OCT-10:35 1508.90 712.56 0.00 0.00 0.00 0.00 0.00 129.80 0.00
November 2887.13 08-NOV-11:35 1005.94 712.56 0.00 0.00 0.00 0.00 0.00 78.46 0.00
December 2905.50 09-DEC-11:35 1508.90 712.56 0.00 0.00 0.00 0.00 0.00 75.13 0.00
                       
Annual Sum or Average         0.00 0.00 0.00 0.00 0.00    
Minimum of Months 2758.98   1005.94 712.56 0.00 0.00 0.00 0.00 0.00 65.72 0.00
Maximum of Months 3152.16   1508.90 855.07 0.00 0.00 0.00 0.00 0.00 138.64 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 3486.54 26-JAN-16:02 583.20 659.78 410.90 0.00 0.00 0.00 0.00 0.00 26.86
February 3505.72 24-FEB-16:02 583.20 659.78 410.90 0.00 0.00 0.00 0.00 28.22 0.00
March 3427.73 15-MAR-15:01 680.40 769.75 479.39 0.00 0.00 0.00 0.00 0.00 66.33
April 3435.09 14-APR-15:02 583.20 659.78 410.90 0.00 0.00 0.00 0.00 91.15 0.00
May 3426.50 31-MAY-15:02 583.20 659.78 410.90 0.00 0.00 0.00 0.00 96.59 0.00
June 3439.96 28-JUN-15:02 583.20 659.78 410.90 0.00 0.00 0.00 0.00 92.46 0.00
July 3442.05 20-JUL-15:02 583.20 659.78 410.90 0.00 0.00 0.00 0.00 99.54 0.00
August 3440.26 21-AUG-15:02 583.20 659.78 410.90 0.00 0.00 0.00 0.00 90.59 0.00
September 3422.14 04-SEP-15:02 324.00 777.60 458.31 0.00 0.00 0.00 0.00 93.04 0.00
October 3431.19 22-OCT-15:02 324.00 777.60 458.31 0.00 0.00 0.00 0.00 77.65 0.00
November 3433.91 07-NOV-16:02 583.20 659.78 410.90 0.00 0.00 0.00 0.00 64.55 0.00
December 3392.27 05-DEC-16:02 583.20 659.78 410.90 0.00 0.00 0.00 0.00 32.70 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 3392.27   324.00 659.78 410.90 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3505.72   680.40 777.60 479.39 0.00 0.00 0.00 0.00 99.54 66.33



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 3430.65 26-JAN-16:02 583.20 659.70 410.85 0.00 0.00 0.00 0.00 0.00 23.98
February 3482.10 24-FEB-16:02 583.20 659.70 410.85 0.00 0.00 0.00 0.00 29.95 0.00
March 3408.01 31-MAR-15:02 583.20 659.70 410.85 0.00 0.00 0.00 0.00 37.87 0.00
April 3428.31 11-APR-15:02 583.20 659.70 410.85 0.00 0.00 0.00 0.00 72.94 0.00
May 3451.97 19-MAY-18:02 831.60 2096.92 774.30 0.00 0.00 0.00 0.00 64.76 0.00
June 3463.17 28-JUN-15:02 583.20 659.70 410.85 0.00 0.00 0.00 0.00 92.48 0.00
July 3509.15 28-JUL-15:02 583.20 659.70 410.85 0.00 0.00 0.00 0.00 142.64 0.00
August 3463.48 23-AUG-15:02 583.20 659.70 410.85 0.00 0.00 0.00 0.00 104.23 0.00
September 3457.13 20-SEP-15:02 583.20 659.70 410.85 0.00 0.00 0.00 0.00 107.66 0.00
October 3416.25 25-OCT-15:02 583.20 659.70 410.85 0.00 0.00 0.00 0.00 77.73 0.00
November 3392.73 07-NOV-16:02 583.20 659.70 410.85 0.00 0.00 0.00 0.00 66.24 0.00
December 3386.49 03-DEC-16:02 324.00 777.51 458.26 0.00 0.00 0.00 0.00 20.69 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 3386.49   324.00 659.70 410.85 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3509.15   831.60 2096.92 774.30 0.00 0.00 0.00 0.00 142.64 23.98



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1728.98 26-JAN-16:02 583.20 414.76 402.58 0.00 0.00 0.00 0.00 0.00 15.70
February 1723.92 24-FEB-16:02 583.20 414.76 402.58 0.00 0.00 0.00 0.00 13.08 0.00
March 1682.95 20-MAR-15:01 680.40 483.89 469.67 0.00 0.00 0.00 0.00 0.00 21.46
April 1663.72 05-APR-15:02 583.20 414.76 402.58 0.00 0.00 0.00 0.00 23.72 0.00
May 1641.30 01-MAY-15:02 583.20 414.76 402.58 0.00 0.00 0.00 0.00 43.41 0.00
June 1637.15 01-JUN-15:02 583.20 414.76 402.58 0.00 0.00 0.00 0.00 43.63 0.00
July 1678.76 28-JUL-15:02 583.20 414.76 402.58 0.00 0.00 0.00 0.00 72.72 0.00
August 1669.98 31-AUG-15:02 583.20 414.76 402.58 0.00 0.00 0.00 0.00 56.12 0.00
September 1676.67 16-SEP-15:02 324.00 488.83 449.03 0.00 0.00 0.00 0.00 46.89 0.00
October 1679.17 25-OCT-15:02 583.20 414.76 402.58 0.00 0.00 0.00 0.00 37.52 0.00
November 1668.47 07-NOV-16:02 583.20 414.76 402.58 0.00 0.00 0.00 0.00 31.64 0.00
December 1694.08 03-DEC-16:02 324.00 488.83 449.03 0.00 0.00 0.00 0.00 7.91 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1637.15   324.00 414.76 402.58 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 1728.98   680.40 488.83 469.67 0.00 0.00 0.00 0.00 72.72 21.46



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 20835.59 13-JAN-23:40 53977.54 2548.93 13495.81 0.00 0.00 0.00 0.00 22.84 0.00
February 20990.78 17-FEB-23:40 53977.54 2548.93 13495.81 0.00 0.00 0.00 0.00 21.60 0.00
March 21830.87 13-MAR-18:10 125947.58 20391.43 40487.42 0.00 0.00 0.00 0.00 183.98 0.00
April 22828.63 17-APR-18:10 125947.58 20391.43 40487.42 0.00 0.00 0.00 0.00 240.89 0.00
May 23192.50 22-MAY-18:10 125947.58 20391.43 40487.42 0.00 0.00 0.00 0.00 249.59 0.00
June 23582.88 29-JUN-18:10 125947.58 20391.43 40487.42 0.00 0.00 0.00 0.00 235.92 0.00
July 23846.50 27-JUL-18:10 125947.58 20391.43 40487.42 0.00 0.00 0.00 0.00 287.11 0.00
August 23459.25 02-AUG-18:10 125947.58 20391.43 40487.42 0.00 0.00 0.00 0.00 234.42 0.00
September 23011.37 18-SEP-18:10 125947.58 20391.43 40487.42 0.00 0.00 0.00 0.00 251.64 0.00
October 22387.99 05-OCT-18:10 125947.58 20391.43 40487.42 0.00 0.00 0.00 0.00 206.92 0.00
November 21672.56 03-NOV-22:40 53977.54 2548.93 13495.81 0.00 0.00 0.00 0.00 102.66 0.00
December 21132.83 08-DEC-23:40 53977.54 2548.93 13495.81 0.00 0.00 0.00 0.00 49.02 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 20835.59   53977.54 2548.93 13495.81 0.00 0.00 0.00 0.00 21.60 0.00
Maximum of Months 23846.50   125947.58 20391.43 40487.42 0.00 0.00 0.00 0.00 287.11 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 22093.35 02-JAN-19:10 125947.58 20391.43 40487.42 0.00 0.00 0.00 0.00 44.08 0.00
February 22280.19 17-FEB-23:40 53977.54 2548.93 13495.81 0.00 0.00 0.00 0.00 18.91 0.00
March 23173.76 13-MAR-18:10 125947.58 20391.43 40487.42 0.00 0.00 0.00 0.00 181.24 0.00
April 24172.36 17-APR-18:10 125947.58 20391.43 40487.42 0.00 0.00 0.00 0.00 238.66 0.00
May 24559.52 22-MAY-18:10 125947.58 20391.43 40487.42 0.00 0.00 0.00 0.00 247.30 0.00
June 24919.77 29-JUN-18:10 125947.58 20391.43 40487.42 0.00 0.00 0.00 0.00 234.13 0.00
July 25182.38 27-JUL-18:10 125947.58 20391.43 40487.42 0.00 0.00 0.00 0.00 285.48 0.00
August 24786.72 02-AUG-18:10 125947.58 20391.43 40487.42 0.00 0.00 0.00 0.00 232.66 0.00
September 24310.40 18-SEP-18:10 125947.58 20391.43 40487.42 0.00 0.00 0.00 0.00 249.94 0.00
October 23691.48 05-OCT-18:10 125947.58 20391.43 40487.42 0.00 0.00 0.00 0.00 204.87 0.00
November 22944.93 02-NOV-18:10 125947.58 20391.43 40487.42 0.00 0.00 0.00 0.00 158.57 0.00
December 22401.89 07-DEC-19:10 125947.58 20391.43 40487.42 0.00 0.00 0.00 0.00 79.16 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 22093.35   53977.54 2548.93 13495.81 0.00 0.00 0.00 0.00 18.91 0.00
Maximum of Months 25182.38   125947.58 20391.43 40487.42 0.00 0.00 0.00 0.00 285.48 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 29016.77 01-JAN-11:50 800.57 340.26 15112.11 18744.03 0.00 0.00 0.00 56.43 0.00
February 29205.74 11-FEB-11:50 800.57 283.55 15112.11 18744.03 0.00 0.00 0.00 96.41 0.00
March 29387.15 27-MAR-10:40 1067.42 567.10 30224.21 37488.05 0.00 0.00 0.00 54.68 0.00
April 30274.81 15-APR-10:50 800.57 283.55 15112.11 18744.03 0.00 0.00 0.00 146.08 0.00
May 30301.64 31-MAY-10:50 533.71 283.55 15112.11 18744.03 0.00 0.00 0.00 220.71 0.00
June 30637.70 11-JUN-10:50 800.57 340.26 15112.11 18744.03 0.00 0.00 0.00 182.43 0.00
July 30917.08 23-JUL-10:50 800.57 340.26 15112.11 18744.03 0.00 0.00 0.00 226.74 0.00
August 30600.54 19-AUG-10:40 1601.14 567.10 30224.21 37488.05 0.00 0.00 0.00 194.74 0.00
September 30510.58 24-SEP-10:50 800.57 340.26 15112.11 18744.03 0.00 0.00 0.00 177.25 0.00
October 30387.61 07-OCT-10:40 1601.14 567.10 30224.21 37488.05 0.00 0.00 0.00 185.11 0.00
November 29251.67 03-NOV-10:50 533.71 283.55 15112.11 18744.03 0.00 0.00 0.00 109.17 0.00
December 29223.04 09-DEC-11:40 1601.14 567.10 30224.21 37488.05 0.00 0.00 0.00 82.73 0.00
                       
Annual Sum or Average             0.00 0.00 0.00    
Minimum of Months 29016.77   533.71 283.55 15112.11 18744.03 0.00 0.00 0.00 54.68 0.00
Maximum of Months 30917.08   1601.14 567.10 30224.21 37488.05 0.00 0.00 0.00 226.74 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 6348.01 01-JAN-11:35 1596.96 904.96 0.00 0.00 0.00 0.00 0.00 126.97 0.00
February 6464.67 11-FEB-11:35 1596.96 754.13 0.00 0.00 0.00 0.00 0.00 159.35 0.00
March 6377.72 04-MAR-11:35 1596.96 754.13 0.00 0.00 0.00 0.00 0.00 147.06 0.00
April 6781.01 15-APR-10:35 1596.96 754.13 0.00 0.00 0.00 0.00 0.00 200.26 0.00
May 6931.67 31-MAY-10:35 1064.64 754.13 0.00 0.00 0.00 0.00 0.00 270.46 0.00
June 7227.45 11-JUN-10:35 1596.96 904.96 0.00 0.00 0.00 0.00 0.00 232.17 0.00
July 7400.77 29-JUL-10:35 1596.96 754.13 0.00 0.00 0.00 0.00 0.00 255.96 0.00
August 7241.91 19-AUG-10:35 1596.96 754.13 0.00 0.00 0.00 0.00 0.00 245.47 0.00
September 7287.70 24-SEP-10:35 1596.96 904.96 0.00 0.00 0.00 0.00 0.00 218.46 0.00
October 7118.15 07-OCT-10:35 1596.96 754.13 0.00 0.00 0.00 0.00 0.00 237.97 0.00
November 6685.07 08-NOV-11:35 1064.64 754.13 0.00 0.00 0.00 0.00 0.00 145.87 0.00
December 6651.05 09-DEC-11:35 1596.96 754.13 0.00 0.00 0.00 0.00 0.00 142.51 0.00
                       
Annual Sum or Average         0.00 0.00 0.00 0.00 0.00    
Minimum of Months 6348.01   1064.64 754.13 0.00 0.00 0.00 0.00 0.00 126.97 0.00
Maximum of Months 7400.77   1596.96 904.96 0.00 0.00 0.00 0.00 0.00 270.46 0.00



Table of Contents

Report: EnergyConsumptionElectricityNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ELECTRICITY:FACILITY [J] ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} NATURALGAS:FACILITY [J] NATURALGAS:FACILITY {Maximum} [W] NATURALGAS:FACILITY {TIMESTAMP}
January 0.832936E+12 520208.21 06-JAN-20:10 0.434275E+12 349697.67 29-JAN-17:19
February 0.793916E+12 532932.23 10-FEB-20:10 0.390107E+12 350826.07 05-FEB-17:00
March 0.903291E+12 545308.86 13-MAR-19:10 0.431769E+12 351042.42 19-MAR-16:49
April 0.954514E+12 557253.57 14-APR-19:10 0.408861E+12 345899.58 30-APR-16:40
May 0.108626E+13 593357.95 29-MAY-19:10 0.411388E+12 343046.55 07-MAY-16:30
June 0.112218E+13 612478.45 29-JUN-19:19 0.391168E+12 340464.49 04-JUN-16:00
July 0.117986E+13 626175.88 27-JUL-18:10 0.399031E+12 336739.54 04-JUL-16:49
August 0.117515E+13 608499.58 02-AUG-19:10 0.397754E+12 336671.93 27-AUG-16:00
September 0.112298E+13 621202.38 18-SEP-18:19 0.385466E+12 334497.49 03-SEP-16:00
October 0.110423E+13 595599.98 03-OCT-19:10 0.403290E+12 333494.19 01-OCT-16:19
November 0.974049E+12 572376.26 29-NOV-20:10 0.400243E+12 344317.59 12-NOV-18:30
December 0.885601E+12 535563.67 10-DEC-20:10 0.428326E+12 352716.65 17-DEC-17:00
             
Annual Sum or Average 0.121350E+14     0.488168E+13    
Minimum of Months 0.793916E+12 520208.21   0.385466E+12 333494.19  
Maximum of Months 0.117986E+13 626175.88   0.434275E+12 352716.65  



Table of Contents

Report: EndUseEnergyConsumptionElectricityMonthly

For: Meter

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY [J] EXTERIORLIGHTS:ELECTRICITY [J] INTERIOREQUIPMENT:ELECTRICITY [J] EXTERIOREQUIPMENT:ELECTRICITY [J] FANS:ELECTRICITY [J] PUMPS:ELECTRICITY [J] HEATING:ELECTRICITY [J] COOLING:ELECTRICITY [J] HEATREJECTION:ELECTRICITY [] HUMIDIFIER:ELECTRICITY [] HEATRECOVERY:ELECTRICITY [J] WATERSYSTEMS:ELECTRICITY [J] COGENERATION:ELECTRICITY []
January 0.997859E+11 0.250556E+11 0.148746E+12 0.577258E+11 0.148835E+12 0.338502E+11 0.00 0.262151E+12 0.00 0.00 0.426736E+11 0.770703E+10 0.00
February 0.901073E+11 0.216207E+11 0.134341E+12 0.521396E+11 0.135806E+12 0.319215E+11 0.00 0.276178E+12 0.00 0.00 0.390476E+11 0.696416E+10 0.00
March 0.995228E+11 0.225721E+11 0.148757E+12 0.577286E+11 0.150947E+12 0.360341E+11 0.00 0.329865E+12 0.00 0.00 0.437375E+11 0.770550E+10 0.00
April 0.965474E+11 0.205092E+11 0.143913E+12 0.558635E+11 0.149020E+12 0.376191E+11 0.00 0.394556E+12 0.00 0.00 0.427907E+11 0.746740E+10 0.00
May 0.996636E+11 0.199884E+11 0.148757E+12 0.577273E+11 0.156958E+12 0.409283E+11 0.00 0.503221E+12 0.00 0.00 0.448538E+11 0.770645E+10 0.00
June 0.963626E+11 0.187967E+11 0.143963E+12 0.558662E+11 0.154107E+12 0.406096E+11 0.00 0.555244E+12 0.00 0.00 0.435178E+11 0.745896E+10 0.00
July 0.998551E+11 0.195979E+11 0.148708E+12 0.577246E+11 0.160427E+12 0.421419E+11 0.00 0.592290E+12 0.00 0.00 0.449650E+11 0.771466E+10 0.00
August 0.995413E+11 0.206594E+11 0.148768E+12 0.577287E+11 0.158919E+12 0.420653E+11 0.00 0.588352E+12 0.00 0.00 0.449515E+11 0.770657E+10 0.00
September 0.965794E+11 0.212802E+11 0.143924E+12 0.558636E+11 0.154580E+12 0.405829E+11 0.00 0.552925E+12 0.00 0.00 0.435243E+11 0.746839E+10 0.00
October 0.997606E+11 0.233732E+11 0.148735E+12 0.577257E+11 0.158162E+12 0.411089E+11 0.00 0.516331E+12 0.00 0.00 0.448770E+11 0.770534E+10 0.00
November 0.965244E+11 0.238539E+11 0.143978E+12 0.558644E+11 0.149028E+12 0.376705E+11 0.00 0.411026E+12 0.00 0.00 0.424295E+11 0.745108E+10 0.00
December 0.998619E+11 0.253160E+11 0.148708E+12 0.577246E+11 0.149859E+12 0.354465E+11 0.00 0.311584E+12 0.00 0.00 0.429661E+11 0.771518E+10 0.00
                           
Annual Sum or Average 0.117411E+13 0.262623E+12 0.175130E+13 0.679683E+12 0.182665E+13 0.459979E+12 0.00 0.529372E+13 0.00 0.00 0.520334E+12 0.907707E+11 0.00
Minimum of Months 0.901073E+11 0.187967E+11 0.134341E+12 0.521396E+11 0.135806E+12 0.319215E+11 0.00 0.262151E+12 0.00 0.00 0.390476E+11 0.696416E+10 0.00
Maximum of Months 0.998619E+11 0.253160E+11 0.148768E+12 0.577287E+11 0.160427E+12 0.421419E+11 0.00 0.592290E+12 0.00 0.00 0.449650E+11 0.771518E+10 0.00



Table of Contents

Report: EndUseEnergyConsumptionNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS [J] EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS [J] COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS [J] COGENERATION:NATURALGAS [] HUMIDIFIER:NATURALGAS []
January 0.151918E+12 0.00 0.473691E+11 0.00 0.234987E+12 0.00 0.00
February 0.137204E+12 0.00 0.418072E+11 0.00 0.211096E+12 0.00 0.00
March 0.152024E+12 0.00 0.500743E+11 0.00 0.229671E+12 0.00 0.00
April 0.146956E+12 0.00 0.454739E+11 0.00 0.216431E+12 0.00 0.00
May 0.151978E+12 0.00 0.419328E+11 0.00 0.217476E+12 0.00 0.00
June 0.147114E+12 0.00 0.381742E+11 0.00 0.205880E+12 0.00 0.00
July 0.151820E+12 0.00 0.365293E+11 0.00 0.210681E+12 0.00 0.00
August 0.152039E+12 0.00 0.336675E+11 0.00 0.212047E+12 0.00 0.00
September 0.146971E+12 0.00 0.292034E+11 0.00 0.209292E+12 0.00 0.00
October 0.151903E+12 0.00 0.291241E+11 0.00 0.222262E+12 0.00 0.00
November 0.147091E+12 0.00 0.321039E+11 0.00 0.221048E+12 0.00 0.00
December 0.151820E+12 0.00 0.434017E+11 0.00 0.233103E+12 0.00 0.00
               
Annual Sum or Average 0.178884E+13 0.00 0.468861E+12 0.00 0.262398E+13 0.00 0.00
Minimum of Months 0.137204E+12 0.00 0.291241E+11 0.00 0.205880E+12 0.00 0.00
Maximum of Months 0.152039E+12 0.00 0.500743E+11 0.00 0.234987E+12 0.00 0.00



Table of Contents

Report: PeakEnergyEndUseElectricityPart1Monthly

For: Meter

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY {Maximum} [W] INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} FANS:ELECTRICITY {Maximum} [W] FANS:ELECTRICITY {TIMESTAMP} PUMPS:ELECTRICITY {Maximum} [W] PUMPS:ELECTRICITY {TIMESTAMP} HEATING:ELECTRICITY {Maximum} [W] HEATING:ELECTRICITY {TIMESTAMP}
January 93091.76 02-JAN-20:10 16690.39 01-JAN-00:10 89674.66 02-JAN-07:10 40537.60 02-JAN-07:19 69289.24 02-JAN-16:19 16022.02 04-JAN-17:00 0.00 01-JAN-00:10
February 93091.76 01-FEB-20:10 16690.39 01-FEB-00:10 89674.66 01-FEB-07:10 40537.60 01-FEB-07:19 72202.04 11-FEB-16:19 16261.20 11-FEB-11:50 0.00 01-FEB-00:10
March 93091.76 01-MAR-20:10 16690.39 01-MAR-00:10 89674.66 01-MAR-07:10 40537.60 01-MAR-07:19 69031.21 25-MAR-15:09 16262.39 14-MAR-10:39 0.00 01-MAR-00:10
April 93091.76 03-APR-19:10 16690.39 01-APR-00:10 89674.66 03-APR-06:10 40537.60 03-APR-06:19 72116.33 14-APR-15:20 16418.43 01-APR-16:40 0.00 01-APR-00:10
May 93091.76 01-MAY-19:10 16690.39 01-MAY-00:10 89674.66 01-MAY-06:10 40537.60 01-MAY-06:19 72296.83 29-MAY-18:19 16564.63 28-MAY-10:39 0.00 01-MAY-00:10
June 93091.76 01-JUN-19:10 16690.39 01-JUN-00:10 89674.66 01-JUN-06:10 40537.60 01-JUN-06:19 73398.88 29-JUN-15:20 16655.62 26-JUN-10:39 0.00 01-JUN-00:10
July 93091.76 03-JUL-19:10 16690.39 01-JUL-00:10 89674.66 03-JUL-06:10 40537.60 03-JUL-06:19 74737.69 29-JUL-15:20 16829.26 29-JUL-10:39 0.00 01-JUL-00:10
August 93091.76 01-AUG-19:10 16690.39 01-AUG-00:10 89674.66 01-AUG-06:10 40537.60 01-AUG-06:19 73943.94 20-AUG-15:20 16738.30 20-AUG-10:50 0.00 01-AUG-00:10
September 93091.76 01-SEP-19:10 16690.39 01-SEP-00:10 89674.66 01-SEP-06:10 40537.60 01-SEP-06:19 74877.68 30-SEP-15:20 16647.68 24-SEP-10:50 0.00 01-SEP-00:10
October 93091.76 02-OCT-19:10 16690.39 01-OCT-00:10 89674.66 02-OCT-06:10 40537.60 02-OCT-06:19 73901.92 07-OCT-15:20 16582.26 03-OCT-10:50 0.00 01-OCT-00:10
November 93091.76 01-NOV-19:10 16690.39 01-NOV-00:10 89674.66 01-NOV-06:10 40537.60 01-NOV-06:19 71249.42 02-NOV-15:09 16407.35 03-NOV-10:39 0.00 01-NOV-00:10
December 93091.76 01-DEC-20:10 16690.39 01-DEC-00:10 89674.66 01-DEC-07:10 40537.60 01-DEC-07:19 71117.33 08-DEC-16:10 16181.78 24-DEC-11:50 0.00 01-DEC-00:10
                             
Annual Sum or Average                            
Minimum of Months 93091.76   16690.39   89674.66   40537.60   69031.21   16022.02   0.00  
Maximum of Months 93091.76   16690.39   89674.66   40537.60   74877.68   16829.26   0.00  



Table of Contents

Report: PeakEnergyEndUseElectricityPart2Monthly

For: Meter

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

COOLING:ELECTRICITY {Maximum} [W] COOLING:ELECTRICITY {TIMESTAMP} HEATREJECTION:ELECTRICITY [] HUMIDIFIER:ELECTRICITY [] HEATRECOVERY:ELECTRICITY {Maximum} [W] HEATRECOVERY:ELECTRICITY {TIMESTAMP} WATERSYSTEMS:ELECTRICITY {Maximum} [W] WATERSYSTEMS:ELECTRICITY {TIMESTAMP} COGENERATION:ELECTRICITY []
January 220518.53 02-JAN-13:00 0.00 0.00 16791.79 01-JAN-09:20 4739.42 18-JAN-07:10 0.00
February 241994.72 11-FEB-16:19 0.00 0.00 16791.79 01-FEB-09:20 4739.31 15-FEB-07:10 0.00
March 233815.87 13-MAR-15:20 0.00 0.00 16791.79 01-MAR-02:49 4738.65 02-MAR-19:10 0.00
April 266696.36 14-APR-15:20 0.00 0.00 16791.79 01-APR-00:10 4738.77 04-APR-06:10 0.00
May 281604.93 29-MAY-18:10 0.00 0.00 16791.79 01-MAY-00:10 4738.73 30-MAY-18:10 0.00
June 293742.52 08-JUN-18:10 0.00 0.00 16791.79 01-JUN-00:10 4738.60 15-JUN-18:10 0.00
July 317380.64 27-JUL-18:10 0.00 0.00 16791.79 01-JUL-00:10 4738.75 27-JUL-18:10 0.00
August 307724.77 21-AUG-15:00 0.00 0.00 16791.79 01-AUG-00:10 4738.76 24-AUG-18:10 0.00
September 305064.73 18-SEP-18:10 0.00 0.00 16791.79 01-SEP-00:10 4738.62 21-SEP-18:10 0.00
October 287699.51 03-OCT-15:20 0.00 0.00 16791.79 01-OCT-00:10 4738.65 31-OCT-06:10 0.00
November 251934.19 03-NOV-15:20 0.00 0.00 16791.79 01-NOV-00:10 4738.74 08-NOV-07:10 0.00
December 223892.20 08-DEC-16:10 0.00 0.00 16791.79 01-DEC-00:10 4738.77 26-DEC-19:10 0.00
                   
Annual Sum or Average     0.00 0.00         0.00
Minimum of Months 220518.53   0.00 0.00 16791.79   4738.60   0.00
Maximum of Months 317380.64   0.00 0.00 16791.79   4739.42   0.00



Table of Contents

Report: ElectricComponentsOfPeakDemandMonthly

For: Meter

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] FANS:ELECTRICITY {AT MAX/MIN} [W] PUMPS:ELECTRICITY {AT MAX/MIN} [W] HEATING:ELECTRICITY {AT MAX/MIN} [W] COOLING:ELECTRICITY {AT MAX/MIN} [W] HEATREJECTION:ELECTRICITY []
January 520208.21 06-JAN-20:10 93091.76 88971.67 16690.39 33012.66 62087.48 15583.73 0.00 187916.26 0.00
February 532932.23 10-FEB-20:10 93091.76 88971.67 16690.39 33012.66 64196.09 15739.06 0.00 198018.28 0.00
March 545308.86 13-MAR-19:10 93091.76 88971.67 16690.39 33012.66 64357.37 15962.20 0.00 209749.18 0.00
April 557253.57 14-APR-19:10 93091.76 88971.67 16690.39 33012.66 66055.66 15959.86 0.00 220401.56 0.00
May 593357.95 29-MAY-19:10 87949.43 87485.24 16690.39 32961.22 68778.63 16217.71 0.00 260446.72 0.00
June 612478.45 29-JUN-19:19 93091.76 88971.67 16690.39 33025.38 69187.21 16301.06 0.00 271735.62 0.00
July 626175.88 27-JUL-18:10 82800.17 79617.06 0.00 32686.23 72579.08 16647.58 0.00 317380.64 0.00
August 608499.58 02-AUG-19:10 93091.76 88971.67 16690.39 33012.66 69025.97 16315.14 0.00 268065.48 0.00
September 621202.38 18-SEP-18:19 82800.17 79617.06 16690.39 32707.97 71494.32 16509.21 0.00 297360.01 0.00
October 595599.98 03-OCT-19:10 93091.76 88971.67 16690.39 33012.66 66618.68 16228.22 0.00 257806.00 0.00
November 572376.26 29-NOV-20:10 93091.76 88971.67 16690.39 33012.66 63327.66 16184.13 0.00 237772.36 0.00
December 535563.67 10-DEC-20:10 87949.43 87485.24 16690.39 32961.22 64364.09 15967.23 0.00 207345.66 0.00
                       
Annual Sum or Average                     0.00
Minimum of Months 520208.21   82800.17 79617.06 0.00 32686.23 62087.48 15583.73 0.00 187916.26 0.00
Maximum of Months 626175.88   93091.76 88971.67 16690.39 33025.38 72579.08 16647.58 0.00 317380.64 0.00



Table of Contents

Report: PeakEnergyEndUseNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS {Maximum} [W] INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS {Maximum} [W] HEATING:NATURALGAS {TIMESTAMP} COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS {Maximum} [W] WATERSYSTEMS:NATURALGAS {TIMESTAMP} COGENERATION:NATURALGAS []
January 104248.32 02-JAN-18:10 0.00 79171.49 18-JAN-11:39 0.00 222392.17 17-JAN-21:19 0.00
February 104248.32 01-FEB-18:10 0.00 87145.53 06-FEB-11:39 0.00 221607.00 01-FEB-21:40 0.00
March 104248.32 01-MAR-18:10 0.00 98398.35 20-MAR-10:39 0.00 217147.95 01-MAR-21:19 0.00
April 104248.32 01-APR-17:10 0.00 83307.82 19-APR-10:39 0.00 215262.11 03-APR-20:00 0.00
May 104248.32 01-MAY-17:10 0.00 78129.61 01-MAY-10:39 0.00 213367.98 01-MAY-20:30 0.00
June 104248.32 01-JUN-17:10 0.00 76181.39 13-JUN-10:39 0.00 211412.46 01-JUN-20:30 0.00
July 104248.32 01-JUL-17:10 0.00 73138.83 07-JUL-10:39 0.00 210091.75 05-JUL-20:49 0.00
August 104248.32 01-AUG-17:10 0.00 71362.39 29-AUG-10:39 0.00 211070.36 31-AUG-20:00 0.00
September 104248.32 01-SEP-17:10 0.00 70238.02 05-SEP-10:39 0.00 212809.14 29-SEP-20:49 0.00
October 104248.32 02-OCT-17:10 0.00 64827.60 02-OCT-10:39 0.00 215047.34 31-OCT-20:00 0.00
November 104248.32 01-NOV-17:10 0.00 71946.31 27-NOV-11:39 0.00 216839.17 30-NOV-21:40 0.00
December 104248.32 01-DEC-18:10 0.00 80582.32 21-DEC-11:39 0.00 220138.69 31-DEC-22:40 0.00
                   
Annual Sum or Average     0.00     0.00     0.00
Minimum of Months 104248.32   0.00 64827.60   0.00 210091.75   0.00
Maximum of Months 104248.32   0.00 98398.35   0.00 222392.17   0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.50 21.86 0.50 21.86
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.50 21.86 0.50 21.86
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.50 21.86 0.50 21.86



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 1.67 21.68 1.67 21.68
June 0.00 0.00 0.00 0.00 5.67 21.69 5.67 21.69
July 0.00 0.00 0.00 0.00 8.17 21.70 8.17 21.70
August 0.00 0.00 0.00 0.00 3.83 21.69 3.83 21.69
September 0.00 0.00 0.00 0.00 2.00 21.68 2.00 21.68
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   21.33 21.69 21.33 21.69
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 8.17 21.70 8.17 21.70



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.67 21.94 0.67 21.94
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.17 21.70 0.17 21.70
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.33 21.76 0.33 21.76
August 0.00 0.00 0.00 0.00 0.17 21.68 0.17 21.68
September 0.00 0.00 0.00 0.00 0.50 21.73 0.50 21.73
October 0.00 0.00 0.00 0.00 0.17 21.70 0.17 21.70
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   2.00 21.79 2.00 21.79
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.67 21.94 0.67 21.94



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.17 21.72 0.17 21.72
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.33 21.71 0.33 21.71
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.50 21.72 0.50 21.72
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.33 21.72 0.33 21.72



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 2.50 21.82 2.50 21.82
February 0.00 0.00 0.00 0.00 3.00 21.95 3.00 21.95
March 0.00 0.00 0.00 0.00 1.00 21.71 1.00 21.71
April 0.00 0.00 0.00 0.00 1.00 21.70 1.00 21.70
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.33 21.67 0.33 21.67
July 0.00 0.00 0.00 0.00 1.67 21.71 1.67 21.71
August 0.00 0.00 0.00 0.00 2.17 21.73 2.17 21.73
September 0.00 0.00 0.00 0.00 4.50 21.84 4.50 21.84
October 0.00 0.00 0.00 0.00 7.17 21.91 7.17 21.91
November 0.00 0.00 0.00 0.00 3.50 21.85 3.50 21.85
December 0.00 0.00 0.00 0.00 3.17 21.87 3.17 21.87
                 
Annual Sum or Average 0.00   0.00   30.00 21.84 30.00 21.84
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 7.17 21.95 7.17 21.95



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: BASEMENT

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.24 0.00 21.24 0.00 21.24
February 672.00 21.14 0.00 21.14 0.00 21.14
March 744.00 21.07 0.00 21.07 0.00 21.07
April 720.00 21.04 0.00 21.04 0.00 21.04
May 744.00 21.06 0.00 21.06 0.00 21.06
June 720.00 21.07 0.00 21.07 0.00 21.07
July 744.00 21.12 0.00 21.12 0.00 21.12
August 744.00 21.21 0.00 21.21 0.00 21.21
September 720.00 21.25 0.00 21.25 0.00 21.25
October 744.00 21.28 0.00 21.28 0.00 21.28
November 720.00 21.30 0.00 21.30 0.00 21.30
December 744.00 21.29 0.00 21.29 0.00 21.29
             
Annual Sum or Average 8760.00 21.17 0.00 21.17 0.00 21.17
Minimum of Months 672.00 21.04 0.00 21.04 0.00 21.04
Maximum of Months 744.00 21.30 0.00 21.30 0.00 21.30



Table of Contents

Report: ComfortReportSimple55Monthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 687.83 21.19 26.83 21.26 0.00 21.26
February 627.00 21.20 17.00 21.23 5.17 21.23
March 738.17 21.19 0.00 21.19 0.00 21.19
April 719.00 21.20 0.00 21.20 0.00 21.20
May 744.00 21.20 0.00 21.20 0.00 21.20
June 720.00 21.28 0.00 21.28 0.00 21.28
July 744.00 21.38 0.00 21.38 0.00 21.38
August 737.33 21.39 0.00 21.39 0.00 21.39
September 662.50 21.50 20.50 21.54 0.00 21.54
October 637.50 21.44 57.33 21.57 0.00 21.57
November 637.67 21.31 48.50 21.44 0.00 21.44
December 674.17 21.21 40.67 21.33 0.00 21.33
             
Annual Sum or Average 8329.17 21.29 210.83 21.33 5.17 21.33
Minimum of Months 627.00 21.19 0.00 21.19 0.00 21.19
Maximum of Months 744.00 21.50 57.33 21.57 5.17 21.57



Table of Contents

Report: ComfortReportSimple55Monthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.09 0.00 21.09 0.00 21.09
February 672.00 21.12 0.00 21.12 0.00 21.12
March 744.00 21.16 0.00 21.16 0.00 21.16
April 720.00 21.21 0.00 21.21 0.00 21.21
May 744.00 21.26 0.00 21.26 0.00 21.26
June 720.00 21.30 0.00 21.30 0.00 21.30
July 744.00 21.33 0.00 21.33 0.00 21.33
August 744.00 21.31 0.00 21.31 0.00 21.31
September 720.00 21.32 0.00 21.32 0.00 21.32
October 744.00 21.28 0.00 21.28 0.00 21.28
November 720.00 21.19 0.00 21.19 0.00 21.19
December 744.00 21.12 0.00 21.12 0.00 21.12
             
Annual Sum or Average 8760.00 21.23 0.00 21.23 0.00 21.23
Minimum of Months 672.00 21.09 0.00 21.09 0.00 21.09
Maximum of Months 744.00 21.33 0.00 21.33 0.00 21.33



Table of Contents

Report: ComfortReportSimple55Monthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.01 0.00 21.01 0.00 21.01
February 672.00 21.03 0.00 21.03 0.00 21.03
March 744.00 21.04 0.00 21.04 0.00 21.04
April 720.00 21.06 0.00 21.06 0.00 21.06
May 744.00 21.14 0.00 21.14 0.00 21.14
June 720.00 21.25 0.00 21.25 0.00 21.25
July 744.00 21.28 0.00 21.28 0.00 21.28
August 744.00 21.21 0.00 21.21 0.00 21.21
September 720.00 21.21 0.00 21.21 0.00 21.21
October 744.00 21.11 0.00 21.11 0.00 21.11
November 720.00 21.06 0.00 21.06 0.00 21.06
December 744.00 21.02 0.00 21.02 0.00 21.02
             
Annual Sum or Average 8760.00 21.12 0.00 21.12 0.00 21.12
Minimum of Months 672.00 21.01 0.00 21.01 0.00 21.01
Maximum of Months 744.00 21.28 0.00 21.28 0.00 21.28



Table of Contents

Report: ComfortReportSimple55Monthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.00 0.00 21.00 0.00 21.00
February 672.00 21.00 0.00 21.00 0.00 21.00
March 744.00 21.01 1.50 21.01 1.50 21.01
April 720.00 21.02 0.00 21.02 0.00 21.02
May 744.00 21.07 0.00 21.07 0.00 21.07
June 720.00 21.17 0.00 21.17 0.00 21.17
July 744.00 21.20 0.00 21.20 0.00 21.20
August 744.00 21.14 0.00 21.14 0.00 21.14
September 720.00 21.13 0.00 21.13 0.00 21.13
October 744.00 21.05 0.00 21.05 0.00 21.05
November 720.00 21.02 0.00 21.02 0.00 21.02
December 744.00 21.00 0.00 21.00 0.00 21.00
             
Annual Sum or Average 8760.00 21.07 1.50 21.07 1.50 21.07
Minimum of Months 672.00 21.00 0.00 21.00 0.00 21.00
Maximum of Months 744.00 21.20 1.50 21.20 1.50 21.20



Table of Contents

Report: ComfortReportSimple55Monthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 250.50 21.97 355.17 21.88 104.33 22.09
February 216.17 22.01 349.17 21.84 93.83 22.05
March 212.67 22.18 419.17 21.86 108.83 22.07
April 142.83 22.61 489.67 21.79 104.00 21.99
May 127.00 22.87 555.50 21.75 107.67 21.95
June 110.67 23.07 572.33 21.72 105.67 21.92
July 110.17 23.01 602.33 21.68 106.50 21.86
August 122.17 22.95 553.83 21.76 109.67 21.96
September 109.17 23.04 567.33 21.71 103.50 21.90
October 132.00 22.77 545.83 21.75 106.33 21.95
November 164.17 22.40 455.33 21.81 101.33 22.02
December 206.00 22.17 396.17 21.87 105.33 22.08
             
Annual Sum or Average 1903.50 22.47 5861.83 21.78 1257.00 21.98
Minimum of Months 109.17 21.97 349.17 21.68 93.83 21.86
Maximum of Months 250.50 23.07 602.33 21.88 109.67 22.09



Table of Contents

Report: ComfortReportSimple55Monthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 674.83 21.42 25.67 21.46 0.00 21.46
February 630.67 21.47 10.67 21.48 0.00 21.48
March 737.00 21.46 0.00 21.46 0.00 21.46
April 715.17 21.47 0.00 21.47 0.00 21.47
May 732.00 21.51 0.00 21.51 0.00 21.51
June 677.67 21.54 1.33 21.54 0.00 21.54
July 704.33 21.56 2.17 21.57 0.00 21.57
August 689.33 21.58 4.17 21.58 0.00 21.58
September 590.67 21.61 23.33 21.66 0.00 21.66
October 595.50 21.72 46.00 21.77 0.00 21.77
November 602.67 21.59 48.67 21.66 0.00 21.66
December 661.67 21.47 40.33 21.53 0.00 21.53
             
Annual Sum or Average 8011.50 21.53 202.33 21.55 0.00 21.55
Minimum of Months 590.67 21.42 0.00 21.46 0.00 21.46
Maximum of Months 737.00 21.72 48.67 21.77 0.00 21.77



Table of Contents

Report: ComfortReportSimple55Monthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.31 0.00 21.31 0.00 21.31
February 672.00 21.34 0.00 21.34 0.00 21.34
March 744.00 21.37 0.00 21.37 0.00 21.37
April 720.00 21.42 0.00 21.42 0.00 21.42
May 744.00 21.49 0.00 21.49 0.00 21.49
June 720.00 21.55 0.00 21.55 0.00 21.55
July 744.00 21.55 0.00 21.55 0.00 21.55
August 744.00 21.55 0.00 21.55 0.00 21.55
September 720.00 21.57 0.00 21.57 0.00 21.57
October 744.00 21.54 0.00 21.54 0.00 21.54
November 720.00 21.46 0.00 21.46 0.00 21.46
December 744.00 21.36 0.00 21.36 0.00 21.36
             
Annual Sum or Average 8760.00 21.46 0.00 21.46 0.00 21.46
Minimum of Months 672.00 21.31 0.00 21.31 0.00 21.31
Maximum of Months 744.00 21.57 0.00 21.57 0.00 21.57



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 692.67 21.49 3.33 21.49 2.00 21.50
February 613.67 21.48 10.17 21.50 5.67 21.50
March 662.67 21.44 6.83 21.45 4.50 21.46
April 617.00 21.44 10.83 21.47 0.17 21.47
May 604.83 21.36 17.17 21.41 0.67 21.41
June 573.33 21.32 23.67 21.40 0.00 21.40
July 580.17 21.29 39.50 21.42 0.00 21.42
August 593.33 21.33 47.17 21.47 5.83 21.49
September 564.67 21.30 38.00 21.42 0.00 21.42
October 593.00 21.32 36.33 21.44 1.50 21.44
November 613.00 21.40 19.83 21.46 1.50 21.47
December 671.50 21.43 16.33 21.48 2.83 21.48
             
Annual Sum or Average 7379.83 21.39 269.17 21.45 24.67 21.46
Minimum of Months 564.67 21.29 3.33 21.40 0.00 21.40
Maximum of Months 692.67 21.49 47.17 21.50 5.83 21.50



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 728.50 21.43 3.67 21.43 3.67 21.44
February 644.33 21.49 9.17 21.49 8.17 21.49
March 686.17 21.44 6.67 21.45 6.33 21.45
April 635.00 21.48 6.50 21.50 0.17 21.50
May 606.33 21.36 17.67 21.42 1.00 21.42
June 570.83 21.32 26.17 21.41 0.00 21.41
July 578.17 21.28 40.33 21.42 0.00 21.42
August 596.50 21.34 40.17 21.46 6.33 21.48
September 574.50 21.32 21.67 21.40 0.00 21.40
October 623.67 21.41 15.83 21.45 4.00 21.46
November 652.83 21.47 7.17 21.49 5.33 21.50
December 707.50 21.42 10.00 21.44 10.00 21.46
             
Annual Sum or Average 7604.33 21.40 205.00 21.45 45.00 21.45
Minimum of Months 570.83 21.28 3.67 21.40 0.00 21.40
Maximum of Months 728.50 21.49 40.33 21.50 10.00 21.50



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.39 2.17 21.39 2.17 21.40
February 672.00 21.46 1.83 21.46 1.83 21.46
March 744.00 21.49 5.00 21.49 5.00 21.50
April 720.00 21.60 0.17 21.60 0.17 21.60
May 744.00 21.67 1.50 21.67 1.50 21.68
June 720.00 21.69 0.00 21.69 0.00 21.69
July 744.00 21.71 0.17 21.71 0.17 21.71
August 744.00 21.68 0.67 21.68 0.67 21.68
September 720.00 21.68 0.00 21.68 0.00 21.68
October 744.00 21.64 0.50 21.64 0.50 21.64
November 720.00 21.54 0.67 21.54 0.67 21.54
December 744.00 21.43 1.83 21.43 1.83 21.43
             
Annual Sum or Average 8760.00 21.58 14.50 21.58 14.50 21.58
Minimum of Months 672.00 21.39 0.00 21.39 0.00 21.40
Maximum of Months 744.00 21.71 5.00 21.71 5.00 21.71



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 691.67 21.53 1.83 21.53 1.50 21.53
February 604.67 21.50 4.17 21.50 4.17 21.50
March 649.17 21.46 3.33 21.47 3.00 21.48
April 587.00 21.37 0.67 21.38 0.00 21.38
May 573.83 21.27 0.83 21.27 0.67 21.28
June 543.00 21.23 3.67 21.25 0.00 21.25
July 554.33 21.21 4.83 21.23 0.00 21.23
August 572.83 21.27 13.33 21.31 5.83 21.33
September 544.00 21.24 17.83 21.30 0.00 21.30
October 572.83 21.27 6.50 21.29 0.83 21.29
November 605.83 21.41 3.17 21.42 1.33 21.42
December 674.83 21.46 4.17 21.47 4.00 21.48
             
Annual Sum or Average 7174.00 21.36 64.33 21.38 21.33 21.38
Minimum of Months 543.00 21.21 0.67 21.23 0.00 21.23
Maximum of Months 691.67 21.53 17.83 21.53 5.83 21.53



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 732.83 21.50 5.17 21.50 5.17 21.50
February 656.33 21.58 6.50 21.58 6.50 21.58
March 679.00 21.50 2.83 21.51 2.83 21.51
April 595.83 21.40 0.50 21.40 0.00 21.40
May 574.00 21.27 1.50 21.28 1.00 21.28
June 540.33 21.22 5.00 21.24 0.00 21.24
July 553.33 21.21 5.17 21.23 0.00 21.23
August 573.83 21.27 8.83 21.30 5.83 21.32
September 548.67 21.25 0.17 21.25 0.00 21.25
October 592.83 21.33 1.17 21.33 1.17 21.34
November 647.83 21.49 5.83 21.51 5.67 21.52
December 723.00 21.46 12.00 21.48 12.00 21.51
             
Annual Sum or Average 7417.83 21.38 54.67 21.40 40.17 21.40
Minimum of Months 540.33 21.21 0.17 21.23 0.00 21.23
Maximum of Months 732.83 21.58 12.00 21.58 12.00 21.58



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.35 0.00 21.35 0.00 21.35
February 672.00 21.44 0.00 21.44 0.00 21.44
March 744.00 21.51 0.00 21.51 0.00 21.51
April 720.00 21.77 0.00 21.77 0.00 21.77
May 744.00 21.96 0.00 21.96 0.00 21.96
June 720.00 22.15 0.00 22.15 0.00 22.15
July 744.00 22.24 0.00 22.24 0.00 22.24
August 744.00 22.18 0.00 22.18 0.00 22.18
September 720.00 22.23 0.00 22.23 0.00 22.23
October 744.00 22.16 0.00 22.16 0.00 22.16
November 720.00 21.82 0.00 21.82 0.00 21.82
December 744.00 21.46 0.00 21.46 0.00 21.46
             
Annual Sum or Average 8760.00 21.86 0.00 21.86 0.00 21.86
Minimum of Months 672.00 21.35 0.00 21.35 0.00 21.35
Maximum of Months 744.00 22.24 0.00 22.24 0.00 22.24



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 672.17 21.43 17.50 21.46 8.83 21.46
February 588.67 21.41 27.33 21.46 12.00 21.47
March 641.67 21.38 34.50 21.46 10.67 21.48
April 583.83 21.34 43.17 21.48 1.50 21.48
May 583.83 21.30 63.50 21.50 1.67 21.50
June 555.00 21.27 81.00 21.53 0.17 21.53
July 561.17 21.24 119.00 21.60 0.00 21.60
August 578.17 21.29 111.17 21.61 7.00 21.63
September 551.83 21.26 101.50 21.58 1.83 21.58
October 579.67 21.29 83.67 21.54 3.00 21.55
November 596.33 21.35 56.00 21.52 3.83 21.52
December 657.17 21.39 43.67 21.49 11.17 21.49
             
Annual Sum or Average 7149.50 21.33 782.00 21.52 61.67 21.53
Minimum of Months 551.83 21.24 17.50 21.46 0.00 21.46
Maximum of Months 672.17 21.43 119.00 21.61 12.00 21.63



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 711.50 21.40 15.17 21.40 14.67 21.40
February 620.17 21.43 21.17 21.44 16.00 21.44
March 662.67 21.39 22.83 21.42 14.33 21.42
April 593.33 21.36 27.17 21.45 2.00 21.45
May 582.67 21.29 60.33 21.48 1.17 21.49
June 552.17 21.26 83.50 21.53 0.00 21.53
July 559.67 21.23 120.67 21.60 0.00 21.60
August 580.17 21.29 102.33 21.59 7.00 21.61
September 558.67 21.27 78.50 21.53 2.33 21.53
October 596.50 21.32 50.67 21.48 3.67 21.48
November 628.83 21.41 26.83 21.47 6.67 21.48
December 690.83 21.37 27.00 21.41 17.17 21.41
             
Annual Sum or Average 7337.17 21.34 636.17 21.48 85.00 21.49
Minimum of Months 552.17 21.23 15.17 21.40 0.00 21.40
Maximum of Months 711.50 21.43 120.67 21.60 17.17 21.61



Table of Contents

Report: ComfortReportSimple55Monthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 630.00 21.39 31.50 21.48 4.50 21.49
February 571.17 21.41 16.67 21.46 6.17 21.47
March 646.33 21.44 11.00 21.45 11.00 21.46
April 620.50 21.45 1.67 21.45 1.67 21.46
May 617.67 21.40 1.83 21.40 1.83 21.40
June 584.67 21.36 0.00 21.36 0.00 21.36
July 591.00 21.33 0.33 21.33 0.33 21.33
August 601.67 21.36 3.17 21.36 2.67 21.37
September 566.17 21.32 36.83 21.44 0.00 21.44
October 582.67 21.32 72.67 21.54 2.50 21.55
November 580.33 21.35 46.00 21.49 1.17 21.49
December 625.17 21.38 40.00 21.49 5.00 21.50
             
Annual Sum or Average 7217.33 21.38 261.67 21.44 36.83 21.45
Minimum of Months 566.17 21.32 0.00 21.33 0.00 21.33
Maximum of Months 646.33 21.45 72.67 21.54 11.00 21.55



Table of Contents

Report: ComfortReportSimple55Monthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 717.50 21.55 4.67 21.56 0.00 21.56
February 641.67 21.60 9.67 21.62 0.00 21.62
March 693.67 21.64 23.50 21.69 0.00 21.69
April 631.33 21.67 35.33 21.75 0.00 21.75
May 537.00 21.63 61.17 21.79 0.00 21.79
June 449.67 21.58 97.33 21.85 0.00 21.85
July 470.00 21.62 94.83 21.87 0.00 21.87
August 486.00 21.59 87.50 21.82 0.00 21.82
September 501.17 21.61 77.17 21.81 0.00 21.81
October 601.33 21.66 50.17 21.77 0.00 21.77
November 642.83 21.63 31.50 21.70 0.00 21.70
December 712.67 21.60 7.50 21.61 0.00 21.61
             
Annual Sum or Average 7084.83 21.62 580.33 21.73 0.00 21.73
Minimum of Months 449.67 21.55 4.67 21.56 0.00 21.56
Maximum of Months 717.50 21.67 97.33 21.87 0.00 21.87



Table of Contents

Report: ComfortReportSimple55Monthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 690.33 21.57 20.00 21.61 0.00 21.61
February 600.50 21.60 23.50 21.65 0.00 21.65
March 634.83 21.63 38.83 21.71 0.00 21.71
April 554.83 21.64 61.33 21.79 0.00 21.79
May 449.50 21.57 113.67 21.87 0.00 21.87
June 381.67 21.54 178.00 22.00 0.00 22.00
July 399.17 21.58 165.33 21.99 0.00 21.99
August 417.00 21.54 156.67 21.94 0.00 21.94
September 423.17 21.55 138.67 21.90 0.00 21.90
October 511.00 21.58 86.00 21.79 0.00 21.79
November 580.83 21.61 56.00 21.74 0.00 21.74
December 669.00 21.60 22.17 21.64 0.00 21.64
             
Annual Sum or Average 6311.83 21.59 1060.17 21.79 0.00 21.79
Minimum of Months 381.67 21.54 20.00 21.61 0.00 21.61
Maximum of Months 690.33 21.64 178.00 22.00 0.00 22.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 579.67 23.37 588.50 23.45 486.50 23.56
February 514.67 23.46 534.17 23.51 445.00 23.61
March 556.33 23.57 608.33 23.55 501.67 23.64
April 517.17 23.78 608.00 23.63 499.33 23.71
May 526.17 23.89 663.33 23.64 525.00 23.72
June 510.83 23.91 676.83 23.59 510.83 23.69
July 527.67 23.92 695.50 23.60 527.67 23.69
August 526.33 23.90 688.67 23.60 526.33 23.69
September 507.50 23.91 668.00 23.60 507.50 23.70
October 521.50 23.89 656.33 23.64 520.83 23.72
November 525.83 23.68 601.83 23.59 493.00 23.67
December 565.67 23.44 597.50 23.48 492.67 23.57
             
Annual Sum or Average 6379.33 23.72 7587.00 23.57 6036.33 23.66
Minimum of Months 507.50 23.37 534.17 23.45 445.00 23.56
Maximum of Months 579.67 23.92 695.50 23.64 527.67 23.72



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 744.00 21.05 0.00 21.05 0.00 21.05
February 672.00 21.07 2.83 21.07 2.83 21.07
March 744.00 21.09 0.00 21.09 0.00 21.09
April 720.00 21.20 0.00 21.20 0.00 21.20
May 744.00 21.42 0.00 21.42 0.00 21.42
June 720.00 21.65 0.00 21.65 0.00 21.65
July 744.00 21.77 0.00 21.77 0.00 21.77
August 744.00 21.63 0.00 21.63 0.00 21.63
September 720.00 21.66 0.00 21.66 0.00 21.66
October 744.00 21.46 0.00 21.46 0.00 21.46
November 720.00 21.22 0.00 21.22 0.00 21.22
December 744.00 21.09 0.00 21.09 0.00 21.09
             
Annual Sum or Average 8760.00 21.36 2.83 21.36 2.83 21.36
Minimum of Months 672.00 21.05 0.00 21.05 0.00 21.05
Maximum of Months 744.00 21.77 2.83 21.77 2.83 21.77



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: BASEMENT PEOPLE

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.23662 56.08013 -0.2046 5.99944
February 672.00000 21.14439 56.66249 -0.2307 6.22115
March 744.00000 21.06665 58.01592 -0.2510 6.40602
April 720.00000 21.04339 62.05332 -0.2375 6.23721
May 744.00000 21.05863 62.73442 -1.4053 45.80930
June 720.00000 21.06851 62.56940 -1.3988 45.46501
July 744.00000 21.12367 62.16269 -1.3729 44.09891
August 744.00000 21.21011 62.15343 -1.3353 42.14130
September 720.00000 21.25415 61.80037 -1.3156 41.16553
October 744.00000 21.28421 61.91112 -0.1521 5.54584
November 720.00000 21.30006 60.27193 -0.1587 5.61057
December 744.00000 21.29335 58.75123 -0.1715 5.70421
           
Annual Sum or Average 8760.00000 21.17396 60.44788 -0.6889 21.79561
Minimum of Months 672.00000 21.04339 56.08013 -1.4053 5.54584
Maximum of Months 744.00000 21.30006 62.73442 -0.1521 45.80930



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: RETAIL_1_FLR_1 PEOPLE

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.31949 56.17497 -0.1041 6.14509
February 672.00000 21.30965 56.59487 -0.0952 5.97360
March 744.00000 21.20234 58.21890 -0.1113 5.77096
April 720.00000 21.20109 62.39231 -0.0753 5.42310
May 744.00000 21.19862 64.03737 -1.1718 34.06509
June 720.00000 21.27787 64.28540 -1.1302 32.09681
July 744.00000 21.38208 63.75069 -1.0855 30.11044
August 744.00000 21.40210 64.05079 -1.0845 30.19592
September 720.00000 21.58880 63.01965 -1.0089 27.31003
October 744.00000 21.63372 62.63529 0.06825 5.73960
November 720.00000 21.49058 60.93537 0.00085 5.91610
December 744.00000 21.37621 59.16979 -0.0640 6.07304
           
Annual Sum or Average 8760.00000 21.36540 61.29537 -0.4910 16.30342
Minimum of Months 672.00000 21.19862 56.17497 -1.1718 5.42310
Maximum of Months 744.00000 21.63372 64.28540 0.06825 34.06509



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: RETAIL_2_FLR_1 PEOPLE

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.09232 57.29245 -0.2045 6.03486
February 672.00000 21.11912 57.53295 -0.1917 5.94909
March 744.00000 21.15554 58.61964 -0.1732 5.83082
April 720.00000 21.21128 62.47245 -0.1303 5.51500
May 744.00000 21.26026 63.45759 -1.2452 37.64373
June 720.00000 21.30244 63.49917 -1.2253 36.67366
July 744.00000 21.33292 63.20611 -1.2100 35.92697
August 744.00000 21.31206 63.62523 -1.2203 36.43843
September 720.00000 21.32422 63.30389 -1.2114 36.03271
October 744.00000 21.27806 63.46611 -0.0976 5.31548
November 720.00000 21.18795 61.88681 -0.1389 5.55812
December 744.00000 21.12199 60.24652 -0.1751 5.77386
           
Annual Sum or Average 8760.00000 21.22537 61.57018 -0.6045 18.63520
Minimum of Months 672.00000 21.09232 57.29245 -1.2452 5.31548
Maximum of Months 744.00000 21.33292 63.62523 -0.0976 37.64373



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: LAUNDRY_FLR_1 PEOPLE

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.38791 54.01956 0.44710 11.54982
February 672.00000 21.38394 54.32146 0.45650 11.73535
March 744.00000 21.38818 55.42679 0.47364 12.08432
April 720.00000 21.36491 59.40379 0.50558 12.53121
May 744.00000 21.36559 60.24392 -0.3390 11.81422
June 720.00000 21.36410 60.19690 -0.3233 11.54078
July 744.00000 21.34394 60.07011 -0.3262 11.34186
August 744.00000 21.36607 60.30427 -0.3335 11.71626
September 720.00000 21.35625 60.13098 -0.3304 11.54157
October 744.00000 21.36346 60.27010 0.51830 12.71169
November 720.00000 21.37612 58.56262 0.49490 12.36212
December 744.00000 21.38065 56.94081 0.46490 11.75187
           
Annual Sum or Average 8760.00000 21.37003 58.34348 0.14041 11.89022
Minimum of Months 672.00000 21.34394 54.01956 -0.3390 11.34186
Maximum of Months 744.00000 21.38818 60.30427 0.51830 12.71169



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CAFE_FLR_1 PEOPLE

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.50439 58.48281 0.02118 5.66074
February 672.00000 21.51364 58.80932 0.03059 5.55696
March 744.00000 21.46819 60.12692 0.02288 5.45996
April 720.00000 21.47668 64.09616 0.05562 5.32628
May 744.00000 21.52588 65.10302 -0.9831 25.78419
June 720.00000 21.60551 65.05142 -0.9419 24.22291
July 744.00000 21.62128 64.80194 -0.9260 23.50019
August 744.00000 21.65579 65.03807 -0.9176 23.27632
September 720.00000 21.77041 64.35066 -0.8604 21.20907
October 744.00000 21.84051 64.08033 0.18514 6.02758
November 720.00000 21.71632 62.60857 0.12691 5.92012
December 744.00000 21.56740 61.27500 0.05918 5.72249
           
Annual Sum or Average 8760.00000 21.60585 62.83840 -0.3464 13.18992
Minimum of Months 672.00000 21.46819 58.48281 -0.9831 5.32628
Maximum of Months 744.00000 21.84051 65.10302 0.18514 25.78419



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: LOBBY_FLR_1 PEOPLE

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.30949 58.36863 -0.1120 5.52266
February 672.00000 21.34190 58.59542 -0.0992 5.48539
March 744.00000 21.37238 59.68735 -0.0855 5.46010
April 720.00000 21.41946 63.51115 -0.0461 5.28452
May 744.00000 21.48958 64.35680 -1.1210 31.83994
June 720.00000 21.54893 64.30933 -1.0923 30.59254
July 744.00000 21.55460 64.09602 -1.0861 30.29239
August 744.00000 21.54751 64.46599 -1.0917 30.55787
September 720.00000 21.56709 64.12512 -1.0782 29.96538
October 744.00000 21.53903 64.23884 0.00426 5.21332
November 720.00000 21.45663 62.68486 -0.0347 5.29114
December 744.00000 21.35943 61.20851 -0.0788 5.35828
           
Annual Sum or Average 8760.00000 21.45937 62.48951 -0.4959 15.97035
Minimum of Months 672.00000 21.30949 58.36863 -1.1210 5.21332
Maximum of Months 744.00000 21.56709 64.46599 0.00426 31.83994



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_1_FLR_3 PEOPLE

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.61273 55.91600 -0.0982 6.05593
February 672.00000 21.64520 55.42531 -0.0746 6.06428
March 744.00000 21.64704 55.52574 -0.0586 6.02310
April 720.00000 21.70890 57.06389 -0.0061 5.90409
May 744.00000 21.72643 58.14501 -1.0547 29.97466
June 720.00000 21.73188 58.81234 -1.0376 29.22277
July 744.00000 21.73893 58.19579 -1.0195 28.50823
August 744.00000 21.73212 58.87448 -1.0299 28.94170
September 720.00000 21.73408 58.35692 -1.0271 28.88363
October 744.00000 21.73066 57.90605 0.02623 5.90760
November 720.00000 21.69103 57.53943 -0.0220 5.95562
December 744.00000 21.61991 58.14869 -0.0704 5.98643
           
Annual Sum or Average 8760.00000 21.69338 57.50452 -0.4585 15.67701
Minimum of Months 672.00000 21.61273 55.42531 -1.0547 5.90409
Maximum of Months 744.00000 21.73893 58.87448 0.02623 29.97466



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_2_FLR_3 PEOPLE

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.47167 57.83823 -0.1552 6.18920
February 672.00000 21.56387 56.81809 -0.1137 6.11548
March 744.00000 21.59111 56.40022 -0.0853 6.07280
April 720.00000 21.70080 57.51222 -0.0146 5.86837
May 744.00000 21.72725 58.14487 -1.0546 29.95988
June 720.00000 21.73428 58.67794 -1.0333 29.04845
July 744.00000 21.74034 58.13494 -1.0168 28.39399
August 744.00000 21.73101 59.08900 -1.0340 29.09037
September 720.00000 21.72864 58.97575 -1.0422 29.44944
October 744.00000 21.71686 59.16099 0.00800 5.83267
November 720.00000 21.64413 59.27953 -0.0504 5.89732
December 744.00000 21.51024 60.08543 -0.1172 6.05055
           
Annual Sum or Average 8760.00000 21.65525 58.35269 -0.4781 15.72168
Minimum of Months 672.00000 21.47167 56.40022 -1.0546 5.83267
Maximum of Months 744.00000 21.74034 60.08543 0.00800 29.95988



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_3_MULT19_FLR_3 PEOPLE

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 0.00000 0.00000 0.00000 0.00000 0.00000
February 0.00000 0.00000 0.00000 0.00000 0.00000
March 0.00000 0.00000 0.00000 0.00000 0.00000
April 0.00000 0.00000 0.00000 0.00000 0.00000
May 0.00000 0.00000 0.00000 0.00000 0.00000
June 0.00000 0.00000 0.00000 0.00000 0.00000
July 0.00000 0.00000 0.00000 0.00000 0.00000
August 0.00000 0.00000 0.00000 0.00000 0.00000
September 0.00000 0.00000 0.00000 0.00000 0.00000
October 0.00000 0.00000 0.00000 0.00000 0.00000
November 0.00000 0.00000 0.00000 0.00000 0.00000
December 0.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 0.00000        
Minimum of Months 0.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 0.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_4_MULT19_FLR_3 PEOPLE

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.38959 55.13764 -0.2021 6.16302
February 672.00000 21.45713 55.01451 -0.1760 6.03230
March 744.00000 21.48749 55.21839 -0.1595 5.99808
April 720.00000 21.59660 56.77122 -0.1078 5.75523
May 744.00000 21.67253 56.83643 -1.1806 35.22791
June 720.00000 21.69379 57.16413 -1.1570 34.20176
July 744.00000 21.70549 57.10781 -1.1497 33.90415
August 744.00000 21.67919 57.49784 -1.1686 34.71036
September 720.00000 21.67735 57.37631 -1.1714 34.85782
October 744.00000 21.63909 57.52291 -0.0847 5.69264
November 720.00000 21.54045 57.05159 -0.1282 5.76985
December 744.00000 21.42699 57.51718 -0.1723 5.95567
           
Annual Sum or Average 8760.00000 21.58098 56.69394 -0.5740 17.92781
Minimum of Months 672.00000 21.38959 55.01451 -1.1806 5.69264
Maximum of Months 744.00000 21.70549 57.52291 -0.0847 35.22791



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_5_FLR_3 PEOPLE

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.65508 55.33249 -0.0868 6.05851
February 672.00000 21.68205 55.15967 -0.0658 6.05136
March 744.00000 21.70292 55.27277 -0.0471 5.99990
April 720.00000 21.73578 56.78580 -0.0010 5.95686
May 744.00000 21.74119 57.99708 -1.0484 29.76934
June 720.00000 21.74708 58.34743 -1.0205 28.57489
July 744.00000 21.75057 57.87995 -1.0084 28.11633
August 744.00000 21.74177 58.78557 -1.0258 28.82745
September 720.00000 21.74713 57.93268 -1.0150 28.43061
October 744.00000 21.74323 57.80989 0.03154 5.94007
November 720.00000 21.71213 57.55275 -0.0154 5.95136
December 744.00000 21.63304 58.34259 -0.0728 5.96319
           
Annual Sum or Average 8760.00000 21.71606 57.27962 -0.4504 15.52813
Minimum of Months 672.00000 21.63304 55.15967 -1.0484 5.94007
Maximum of Months 744.00000 21.75057 58.78557 0.03154 29.76934



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_6_FLR_3 PEOPLE

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.52458 57.05243 -0.1419 6.12451
February 672.00000 21.62506 56.24290 -0.1014 6.07347
March 744.00000 21.66422 55.96527 -0.0712 6.00071
April 720.00000 21.73276 57.16436 -0.0087 5.93186
May 744.00000 21.74156 58.02322 -1.0483 29.75697
June 720.00000 21.74803 58.24396 -1.0168 28.42384
July 744.00000 21.75120 57.83573 -1.0060 28.01502
August 744.00000 21.74102 59.02907 -1.0297 28.96306
September 720.00000 21.74441 58.62298 -1.0285 28.92810
October 744.00000 21.73591 58.86495 0.01398 5.86941
November 720.00000 21.67586 58.89677 -0.0435 5.88108
December 744.00000 21.50896 60.26748 -0.1232 6.02408
           
Annual Sum or Average 8760.00000 21.68281 58.02966 -0.4695 15.55718
Minimum of Months 672.00000 21.50896 55.96527 -1.0483 5.86941
Maximum of Months 744.00000 21.75120 60.26748 0.01398 29.75697



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_1_FLR_6 PEOPLE

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.61415 56.53730 -0.0943 6.19895
February 672.00000 21.64629 55.86259 -0.0662 6.20778
March 744.00000 21.65130 55.78520 -0.0466 6.14935
April 720.00000 21.71385 57.05818 0.01276 6.02638
May 744.00000 21.73261 57.75114 -1.0236 28.85356
June 720.00000 21.73750 58.22691 -1.0052 28.05247
July 744.00000 21.74401 57.68449 -0.9845 27.30820
August 744.00000 21.73720 58.41103 -0.9990 27.85568
September 720.00000 21.73765 58.00754 -0.9982 27.88746
October 744.00000 21.73284 57.80163 0.04199 6.02098
November 720.00000 21.69174 57.73131 -0.0114 6.06072
December 744.00000 21.61761 58.68376 -0.0657 6.11397
           
Annual Sum or Average 8760.00000 21.69655 57.47168 -0.4390 15.28260
Minimum of Months 672.00000 21.61415 55.78520 -1.0236 6.02098
Maximum of Months 744.00000 21.74401 58.68376 0.04199 28.85356



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_2_FLR_6 PEOPLE

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.48512 58.45714 -0.1514 6.33670
February 672.00000 21.57566 57.22556 -0.1045 6.26184
March 744.00000 21.60243 56.60420 -0.0729 6.19498
April 720.00000 21.70832 57.49396 0.00479 5.98292
May 744.00000 21.73339 57.75382 -1.0233 28.83092
June 720.00000 21.73955 58.10414 -1.0010 27.88402
July 744.00000 21.74521 57.62426 -0.9817 27.19595
August 744.00000 21.73637 58.55540 -1.0035 28.00188
September 720.00000 21.73307 58.57074 -1.0133 28.42087
October 744.00000 21.72038 58.99350 0.02343 5.91981
November 720.00000 21.64958 59.44178 -0.0398 5.98674
December 744.00000 21.51274 60.60933 -0.1138 6.19222
           
Annual Sum or Average 8760.00000 21.66202 58.29359 -0.4587 15.32168
Minimum of Months 672.00000 21.48512 56.60420 -1.0233 5.91981
Maximum of Months 744.00000 21.74521 60.60933 0.02343 28.83092



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: ROOM_3_MULT9_FLR_6 PEOPLE

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.69086 53.97492 -0.0543 6.18332
February 672.00000 21.70080 54.26119 -0.0472 6.14549
March 744.00000 21.68517 54.88606 -0.0540 6.06941
April 720.00000 21.71036 56.73387 -0.0264 5.94768
May 744.00000 21.72568 57.66104 -1.0910 31.55936
June 720.00000 21.73243 58.02493 -1.0695 30.60648
July 744.00000 21.73950 57.67661 -1.0558 30.09904
August 744.00000 21.73347 57.95463 -1.0612 30.32204
September 720.00000 21.74475 57.23089 -1.0359 29.41300
October 744.00000 21.75006 56.67716 0.03173 6.05826
November 720.00000 21.72971 55.95298 0.00013 6.10035
December 744.00000 21.69012 56.25164 -0.0344 6.12472
           
Annual Sum or Average 8760.00000 21.71945 56.45243 -0.4607 16.28219
Minimum of Months 672.00000 21.68517 53.97492 -1.0910 5.94768
Maximum of Months 744.00000 21.75006 58.02493 0.03173 31.55936



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: BANQUET_FLR_6 PEOPLE

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.59967 58.27208 0.01808 5.50691
February 672.00000 21.66052 58.40178 0.04584 5.57374
March 744.00000 21.72549 59.32091 0.07660 5.68226
April 720.00000 21.82098 62.84638 0.14122 5.83098
May 744.00000 21.95212 63.27849 -0.8237 20.06594
June 720.00000 22.04073 62.99530 -0.7777 18.55881
July 744.00000 22.04941 62.75697 -0.7686 18.15639
August 744.00000 22.00932 63.22297 -0.7943 19.11327
September 720.00000 21.97656 63.09250 -0.8070 19.55588
October 744.00000 21.87955 63.53462 0.16919 6.01274
November 720.00000 21.76607 62.26002 0.11241 5.75267
December 744.00000 21.64963 60.99384 0.05415 5.52083
           
Annual Sum or Average 8760.00000 21.84506 61.76398 -0.2816 11.31184
Minimum of Months 672.00000 21.59967 58.27208 -0.8237 5.50691
Maximum of Months 744.00000 22.04941 63.53462 0.16919 20.06594



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: DINING_FLR_6 PEOPLE

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.65794 57.84932 0.06208 5.60455
February 672.00000 21.72638 57.95408 0.09160 5.72527
March 744.00000 21.79779 58.84371 0.12414 5.89529
April 720.00000 21.89861 62.33643 0.18951 6.16035
May 744.00000 22.02968 62.75762 -0.7555 17.76812
June 720.00000 22.10968 62.49667 -0.7138 16.50830
July 744.00000 22.11044 62.28607 -0.7082 16.24444
August 744.00000 22.07403 62.73677 -0.7320 17.07395
September 720.00000 22.03672 62.62500 -0.7468 17.55269
October 744.00000 21.94297 63.06046 0.21242 6.34971
November 720.00000 21.83301 61.78540 0.15760 6.01444
December 744.00000 21.71211 60.54500 0.09887 5.68336
           
Annual Sum or Average 8760.00000 21.91165 61.28895 -0.2287 10.57694
Minimum of Months 672.00000 21.65794 57.84932 -0.7555 5.60455
Maximum of Months 744.00000 22.11044 63.06046 0.21242 17.76812



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: KITCHEN_FLR_6 PEOPLE

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 23.01453 54.98266 1.00124 30.93443
February 672.00000 23.04686 55.13519 1.02369 31.91587
March 744.00000 23.07560 56.05688 1.05028 32.88263
April 720.00000 23.12692 59.39143 1.11145 35.36061
May 744.00000 23.17729 60.01357 0.53088 20.82046
June 720.00000 23.21446 59.87814 0.56559 21.29723
July 744.00000 23.20948 59.74576 0.57573 21.81918
August 744.00000 23.19642 60.04850 0.55024 20.99308
September 720.00000 23.20131 59.83299 0.55600 21.18945
October 744.00000 23.16281 60.07185 1.13727 36.22159
November 720.00000 23.10006 58.74571 1.08249 34.09560
December 744.00000 23.02076 57.54449 1.02315 31.65195
           
Annual Sum or Average 8760.00000 23.12920 58.47016 0.84948 28.23823
Minimum of Months 672.00000 23.01453 54.98266 0.53088 20.82046
Maximum of Months 744.00000 23.21446 60.07185 1.13727 36.22159



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: STORAGE_FLR_1 PEOPLE

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.00139 56.41813 -0.2958 6.93997
February 672.00000 21.00256 56.78073 -0.2873 6.83974
March 744.00000 21.00675 58.14788 -0.2744 6.68809
April 720.00000 21.01747 62.36348 -0.2378 6.23635
May 744.00000 21.07388 63.94728 -1.3789 44.40746
June 720.00000 21.16948 64.23956 -1.3362 42.17645
July 744.00000 21.19794 63.98737 -1.3250 41.59483
August 744.00000 21.13745 64.60696 -1.3495 42.87285
September 720.00000 21.13200 64.24019 -1.3497 42.91438
October 744.00000 21.05051 64.22991 -0.2088 5.92073
November 720.00000 21.01936 62.00672 -0.2399 6.25810
December 744.00000 21.00416 59.71944 -0.2702 6.59509
           
Annual Sum or Average 8760.00000 21.06810 61.74829 -0.7154 21.71140
Minimum of Months 672.00000 21.00139 56.41813 -1.3789 5.92073
Maximum of Months 744.00000 21.19794 64.60696 -0.2088 44.40746



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORRIDOR_FLR_3 PEOPLE

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.35163 57.55519 -0.2146 6.23400
February 672.00000 21.43735 57.64693 -0.1923 5.98928
March 744.00000 21.50674 58.64867 -0.1676 5.85363
April 720.00000 21.77403 61.84493 -0.0797 5.23039
May 744.00000 21.96137 62.54826 -1.1339 32.14790
June 720.00000 22.15377 62.25308 -1.0662 29.03186
July 744.00000 22.23842 61.80179 -1.0378 27.77743
August 744.00000 22.18474 62.32991 -1.0550 28.56405
September 720.00000 22.23230 61.85793 -1.0389 27.88425
October 744.00000 22.16312 61.96041 0.02390 5.03455
November 720.00000 21.81767 61.13161 -0.0715 5.28573
December 744.00000 21.45758 60.35761 -0.1712 5.88324
           
Annual Sum or Average 8760.00000 21.85849 60.84383 -0.5192 15.47125
Minimum of Months 672.00000 21.35163 57.55519 -1.1339 5.03455
Maximum of Months 744.00000 22.23842 62.54826 0.02390 32.14790



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORRIDOR_FLR_6 PEOPLE

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.05067 56.66208 -0.2575 6.56171
February 672.00000 21.07093 56.93332 -0.2422 6.40419
March 744.00000 21.08662 58.09452 -0.2260 6.25307
April 720.00000 21.20347 61.77794 -0.1622 5.69028
May 744.00000 21.41590 62.23986 -1.2282 36.74058
June 720.00000 21.64678 61.64668 -1.1437 32.64976
July 744.00000 21.76655 61.05498 -1.1013 30.69332
August 744.00000 21.63271 61.86872 -1.1491 32.95101
September 720.00000 21.66094 61.48783 -1.1387 32.52017
October 744.00000 21.46464 62.15269 -0.0846 5.23609
November 720.00000 21.22168 61.07004 -0.1658 5.75052
December 744.00000 21.09378 59.59471 -0.2241 6.21574
           
Annual Sum or Average 8760.00000 21.36112 60.39809 -0.5959 17.37489
Minimum of Months 672.00000 21.05067 56.66208 -1.2282 5.23609
Maximum of Months 744.00000 21.76655 62.23986 -0.0846 36.74058



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: MECH_FLR_1 PEOPLE

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 744.00000 21.01345 56.05500 -0.2759 6.71332
February 672.00000 21.02598 56.36974 -0.2651 6.59933
March 744.00000 21.03660 57.67581 -0.2508 6.44909
April 720.00000 21.06381 61.79360 -0.2107 6.00382
May 744.00000 21.14341 63.15427 -1.3348 42.12677
June 720.00000 21.24805 63.31102 -1.2895 39.80675
July 744.00000 21.27879 63.04478 -1.2775 39.19996
August 744.00000 21.20675 63.69408 -1.3064 40.67280
September 720.00000 21.20557 63.33765 -1.3050 40.62894
October 744.00000 21.11294 63.43834 -0.1796 5.70803
November 720.00000 21.06161 61.38142 -0.2143 6.03791
December 744.00000 21.02390 59.27539 -0.2487 6.37508
           
Annual Sum or Average 8760.00000 21.11888 61.06721 -0.6825 20.61288
Minimum of Months 672.00000 21.01345 56.05500 -1.3348 5.70803
Maximum of Months 744.00000 21.27879 63.69408 -0.1796 42.12677



Table of Contents

Report: ChillerReportMonthly

For: COOLSYS1 CHILLER1

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

CHILLER ELECTRICITY ENERGY [J] CHILLER ELECTRICITY RATE {Maximum} [W] CHILLER ELECTRICITY RATE {TIMESTAMP} CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] CHILLER EVAPORATOR COOLING ENERGY [J] CHILLER EVAPORATOR COOLING RATE [] CHILLER CONDENSER HEAT TRANSFER ENERGY [J] CHILLER COP [W/W] CHILLER COP {Maximum} [W/W] CHILLER COP {TIMESTAMP} CHILLER PART LOAD RATIO [] CHILLER PART LOAD RATIO []
January 0.262151E+12 220518.53 02-JAN-14:00 741.17 0.810376E+12 0.00 0.107253E+13 2.98 3.93 07-JAN-19:02 0.00 0.00
February 0.276178E+12 254325.80 11-FEB-16:03 665.33 0.849247E+12 0.00 0.112543E+13 2.97 3.93 12-FEB-19:03 0.00 0.00
March 0.329865E+12 246838.95 13-MAR-15:03 738.67 0.102837E+13 0.00 0.135823E+13 3.02 3.94 19-MAR-08:62 0.00 0.00
April 0.394556E+12 273933.84 14-APR-15:03 720.00 0.122483E+13 0.00 0.161939E+13 3.08 3.82 25-APR-16:00 0.00 0.00
May 0.503221E+12 290642.90 29-MAY-18:03 744.00 0.159973E+13 0.00 0.210295E+13 3.18 3.74 24-MAY-18:03 0.00 0.00
June 0.555244E+12 302651.01 08-JUN-18:03 720.00 0.177436E+13 0.00 0.232960E+13 3.20 3.69 18-JUN-18:03 0.00 0.00
July 0.592290E+12 325242.66 27-JUL-18:03 744.00 0.187576E+13 0.00 0.246805E+13 3.18 3.77 02-JUL-18:03 0.00 0.00
August 0.588352E+12 307724.77 21-AUG-16:00 744.00 0.187315E+13 0.00 0.246150E+13 3.19 3.74 12-AUG-08:03 0.00 0.00
September 0.552925E+12 315842.55 18-SEP-18:03 720.00 0.176978E+13 0.00 0.232270E+13 3.21 3.70 27-SEP-18:03 0.00 0.00
October 0.516331E+12 294975.88 03-OCT-15:03 744.00 0.165827E+13 0.00 0.217461E+13 3.21 3.79 31-OCT-05:50 0.00 0.00
November 0.411026E+12 267465.13 04-NOV-18:03 720.00 0.132807E+13 0.00 0.173910E+13 3.18 3.92 25-NOV-09:02 0.00 0.00
December 0.311584E+12 238903.49 24-DEC-16:03 742.33 0.987861E+12 0.00 0.129944E+13 3.06 3.96 30-DEC-19:02 0.00 0.00
                         
Annual Sum or Average 0.529372E+13     8743.50 0.167798E+14 0.00 0.220735E+14 3.12     0.00 0.00
Minimum of Months 0.262151E+12 220518.53   665.33 0.810376E+12 0.00 0.107253E+13 2.97 3.69   0.00 0.00
Maximum of Months 0.592290E+12 325242.66   744.00 0.187576E+13 0.00 0.246805E+13 3.21 3.96   0.00 0.00



Table of Contents

Report: BoilerReportMonthly

For: HEATSYS1 BOILER

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

BOILER HEATING ENERGY [J] BOILER GAS CONSUMPTION [] BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] BOILER HEATING RATE {Maximum} [W] BOILER HEATING RATE {TIMESTAMP} BOILER GAS CONSUMPTION RATE [] BOILER INLET TEMPERATURE [C] BOILER OUTLET TEMPERATURE [C] BOILER MASS FLOW RATE [kg/s] BOILER ANCILLARY ELECTRICITY RATE [W] BOILER PART LOAD RATIO [] BOILER PART LOAD RATIO {Maximum} [] BOILER PART LOAD RATIO {TIMESTAMP}
January 0.300872E+11 0.00 734.56 60722.14 18-JAN-11:40 0.00 30.42 59.61 0.10 0.00 0.04 0.22 18-JAN-11:40
February 0.267775E+11 0.00 653.67 67096.09 06-FEB-11:40 0.00 30.37 59.11 0.10 0.00 0.04 0.24 06-FEB-11:40
March 0.326279E+11 0.00 706.61 76117.71 20-MAR-10:40 0.00 30.95 58.42 0.11 0.00 0.04 0.27 20-MAR-10:40
April 0.295541E+11 0.00 660.33 67094.71 18-APR-10:35 0.00 31.27 57.42 0.10 0.00 0.04 0.24 18-APR-10:35
May 0.271795E+11 0.00 641.69 62175.45 01-MAY-10:35 0.00 31.67 55.71 0.09 0.00 0.04 0.22 01-MAY-10:35
June 0.246494E+11 0.00 591.99 60608.83 13-JUN-10:35 0.00 32.05 54.59 0.09 0.00 0.03 0.22 13-JUN-10:35
July 0.234215E+11 0.00 577.69 57541.44 07-JUL-10:35 0.00 31.96 53.26 0.08 0.00 0.03 0.21 07-JUL-10:35
August 0.212880E+11 0.00 593.17 56734.21 29-AUG-10:35 0.00 31.69 53.88 0.07 0.00 0.03 0.20 29-AUG-10:35
September 0.182328E+11 0.00 568.60 53503.53 05-SEP-10:40 0.00 32.18 53.89 0.06 0.00 0.03 0.19 05-SEP-10:40
October 0.180498E+11 0.00 632.57 48951.54 02-OCT-10:40 0.00 32.39 55.75 0.06 0.00 0.02 0.18 02-OCT-10:40
November 0.200005E+11 0.00 660.79 54928.78 27-NOV-11:40 0.00 31.39 57.61 0.07 0.00 0.03 0.20 27-NOV-11:40
December 0.275284E+11 0.00 722.25 61852.08 21-DEC-11:40 0.00 30.85 59.13 0.09 0.00 0.04 0.22 21-DEC-11:40
                           
Annual Sum or Average 0.299397E+12 0.00 7743.92     0.00 31.44 56.52 0.08 0.00 0.03    
Minimum of Months 0.180498E+11 0.00 568.60 48951.54   0.00 30.37 53.26 0.06 0.00 0.02 0.18  
Maximum of Months 0.326279E+11 0.00 734.56 76117.71   0.00 32.39 59.61 0.11 0.00 0.04 0.27  



Table of Contents

Report: DXReportMonthly

For: VAV WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.588169E+12 0.00 670.25 0.382147E+12 0.00 0.00 0.00 0.00 578284.50 04-JAN-18:00 298749.05 07-JAN-11:35 0.00 0.00 0.00
February 0.619413E+12 0.00 618.43 0.419633E+12 0.00 0.00 0.00 0.00 608170.58 11-FEB-11:35 310069.82 11-FEB-11:35 0.00 0.00 0.00
March 0.757114E+12 0.00 690.17 0.501126E+12 0.00 0.00 0.00 0.00 596268.05 14-MAR-10:35 310026.83 13-MAR-18:10 0.00 0.00 0.00
April 0.911343E+12 0.00 720.00 0.600445E+12 0.00 0.00 0.00 0.00 603046.69 01-APR-17:12 338815.42 15-APR-17:12 0.00 0.00 0.00
May 0.121938E+13 0.00 744.00 0.692135E+12 0.00 0.00 0.00 0.00 695941.36 28-MAY-10:35 357834.93 31-MAY-10:50 0.00 0.00 0.00
June 0.136731E+13 0.00 720.00 0.705696E+12 0.00 0.00 0.00 0.00 702211.90 10-JUN-10:35 351671.61 11-JUN-10:35 0.00 0.00 0.00
July 0.144135E+13 0.00 744.00 0.745435E+12 0.00 0.00 0.00 0.00 735216.74 29-JUL-10:35 375034.43 29-JUL-17:13 0.00 0.00 0.00
August 0.144829E+13 0.00 744.00 0.735571E+12 0.00 0.00 0.00 0.00 729874.45 20-AUG-10:35 358432.36 08-AUG-10:35 0.00 0.00 0.00
September 0.135531E+13 0.00 720.00 0.702928E+12 0.00 0.00 0.00 0.00 701187.95 06-SEP-10:35 352052.96 09-SEP-10:35 0.00 0.00 0.00
October 0.125873E+13 0.00 744.00 0.692163E+12 0.00 0.00 0.00 0.00 719322.49 04-OCT-10:35 352541.95 09-OCT-10:50 0.00 0.00 0.00
November 0.100361E+13 0.00 704.17 0.565162E+12 0.00 0.00 0.00 0.00 655600.26 05-NOV-10:35 312593.18 03-NOV-10:35 0.00 0.00 0.00
December 0.733564E+12 0.00 670.00 0.437330E+12 0.00 0.00 0.00 0.00 638135.34 24-DEC-21:40 309229.50 10-DEC-11:35 0.00 0.00 0.00
                               
Annual Sum or Average 0.127036E+14 0.00 8489.02 0.717977E+13 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.588169E+12 0.00 618.43 0.382147E+12 0.00 0.00 0.00 0.00 578284.50   298749.05   0.00 0.00 0.00
Maximum of Months 0.144829E+13 0.00 744.00 0.745435E+12 0.00 0.00 0.00 0.00 735216.74   375034.43   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: FLR_3_DOAS COOLING COIL

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.678594E+11 0.00 629.83 0.426226E+11 0.00 0.00 0.00 0.00 69237.45 07-JAN-03:30 32142.12 02-JAN-15:00 0.00 0.00 0.00
February 0.730381E+11 0.00 607.50 0.481752E+11 0.00 0.00 0.00 0.00 68133.31 11-FEB-19:00 32836.20 11-FEB-14:00 0.00 0.00 0.00
March 0.884958E+11 0.00 672.00 0.577357E+11 0.00 0.00 0.00 0.00 71113.56 19-MAR-07:30 32552.45 13-MAR-15:02 0.00 0.00 0.00
April 0.104580E+12 0.00 718.83 0.690403E+11 0.00 0.00 0.00 0.00 71819.61 26-APR-14:30 34346.54 17-APR-15:00 0.00 0.00 0.00
May 0.131409E+12 0.00 744.00 0.777571E+11 0.00 0.00 0.00 0.00 80981.70 28-MAY-18:00 35994.17 22-MAY-13:00 0.00 0.00 0.00
June 0.141915E+12 0.00 720.00 0.777573E+11 0.00 0.00 0.00 0.00 66955.40 28-JUN-12:00 34670.66 11-JUN-13:00 0.00 0.00 0.00
July 0.147828E+12 0.00 744.00 0.811791E+11 0.00 0.00 0.00 0.00 78320.79 02-JUL-17:10 36585.74 28-JUL-15:00 0.00 0.00 0.00
August 0.150052E+12 0.00 744.00 0.808641E+11 0.00 0.00 0.00 0.00 78921.70 28-AUG-14:10 35898.95 23-AUG-13:00 0.00 0.00 0.00
September 0.140049E+12 0.00 720.00 0.773878E+11 0.00 0.00 0.00 0.00 64377.90 06-SEP-11:00 34832.89 20-SEP-14:00 0.00 0.00 0.00
October 0.134316E+12 0.00 744.00 0.776926E+11 0.00 0.00 0.00 0.00 75497.39 01-OCT-07:10 34746.76 14-OCT-13:00 0.00 0.00 0.00
November 0.111940E+12 0.00 692.67 0.645080E+11 0.00 0.00 0.00 0.00 78941.50 08-NOV-09:00 33000.87 17-NOV-15:00 0.00 0.00 0.00
December 0.842073E+11 0.00 655.33 0.497458E+11 0.00 0.00 0.00 0.00 82125.11 24-DEC-08:17 32506.84 10-DEC-15:00 0.00 0.00 0.00
                               
Annual Sum or Average 0.137569E+13 0.00 8392.17 0.804466E+12 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.678594E+11 0.00 607.50 0.426226E+11 0.00 0.00 0.00 0.00 64377.90   32142.12   0.00 0.00 0.00
Maximum of Months 0.150052E+12 0.00 744.00 0.811791E+11 0.00 0.00 0.00 0.00 82125.11   36585.74   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_1_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.549733E+10 0.00 582.25 0.269398E+10 0.00 0.00 0.00 0.00 20555.66 07-JAN-09:01 15196.03 26-JAN-16:02 0.00 0.00 0.00
February 0.632953E+10 0.00 560.05 0.334204E+10 0.00 0.00 0.00 0.00 19741.34 02-FEB-09:02 15195.07 24-FEB-19:01 0.00 0.00 0.00
March 0.817434E+10 0.00 624.85 0.447441E+10 0.00 0.00 0.00 0.00 20369.81 19-MAR-08:62 15186.97 15-MAR-18:02 0.00 0.00 0.00
April 0.101237E+11 0.00 662.38 0.577476E+10 0.00 0.00 0.00 0.00 18893.56 16-APR-08:62 14733.62 15-APR-18:02 0.00 0.00 0.00
May 0.122213E+11 0.00 698.08 0.702649E+10 0.00 0.00 0.00 0.00 19719.93 24-MAY-18:02 14731.00 16-MAY-15:02 0.00 0.00 0.00
June 0.128607E+11 0.00 681.51 0.739887E+10 0.00 0.00 0.00 0.00 18550.38 13-JUN-08:61 14532.73 10-JUN-15:02 0.00 0.00 0.00
July 0.143713E+11 0.00 711.35 0.855364E+10 0.00 0.00 0.00 0.00 18163.38 24-JUL-08:62 14665.83 28-JUL-15:02 0.00 0.00 0.00
August 0.137867E+11 0.00 700.13 0.805387E+10 0.00 0.00 0.00 0.00 20220.47 12-AUG-08:62 14661.94 31-AUG-15:02 0.00 0.00 0.00
September 0.133697E+11 0.00 682.32 0.779853E+10 0.00 0.00 0.00 0.00 18652.03 16-SEP-08:62 14675.16 17-SEP-15:02 0.00 0.00 0.00
October 0.126403E+11 0.00 700.45 0.729565E+10 0.00 0.00 0.00 0.00 19352.86 01-OCT-08:62 14629.05 14-OCT-15:02 0.00 0.00 0.00
November 0.921094E+10 0.00 638.93 0.492251E+10 0.00 0.00 0.00 0.00 19340.16 24-NOV-09:02 14642.01 17-NOV-16:02 0.00 0.00 0.00
December 0.668336E+10 0.00 599.64 0.335713E+10 0.00 0.00 0.00 0.00 20412.67 23-DEC-09:02 15181.47 20-DEC-16:02 0.00 0.00 0.00
                               
Annual Sum or Average 0.125269E+12 0.00 7841.94 0.706919E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.549733E+10 0.00 560.05 0.269398E+10 0.00 0.00 0.00 0.00 18163.38   14532.73   0.00 0.00 0.00
Maximum of Months 0.143713E+11 0.00 711.35 0.855364E+10 0.00 0.00 0.00 0.00 20555.66   15196.03   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_2_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.360931E+10 0.00 480.47 0.149835E+10 0.00 0.00 0.00 0.00 20730.55 07-JAN-09:01 15339.17 26-JAN-16:02 0.00 0.00 0.00
February 0.486216E+10 0.00 501.27 0.230758E+10 0.00 0.00 0.00 0.00 19471.05 18-FEB-09:01 15334.65 24-FEB-16:02 0.00 0.00 0.00
March 0.703085E+10 0.00 583.94 0.363766E+10 0.00 0.00 0.00 0.00 20542.18 19-MAR-08:62 15300.56 15-MAR-15:01 0.00 0.00 0.00
April 0.952975E+10 0.00 651.75 0.531652E+10 0.00 0.00 0.00 0.00 19112.25 16-APR-08:62 14943.04 15-APR-18:02 0.00 0.00 0.00
May 0.122123E+11 0.00 698.10 0.701907E+10 0.00 0.00 0.00 0.00 20268.48 24-MAY-18:02 14887.34 20-MAY-15:02 0.00 0.00 0.00
June 0.130636E+11 0.00 683.47 0.754903E+10 0.00 0.00 0.00 0.00 18647.63 13-JUN-08:61 14682.60 10-JUN-15:02 0.00 0.00 0.00
July 0.144997E+11 0.00 712.44 0.863567E+10 0.00 0.00 0.00 0.00 18473.74 02-JUL-18:02 14839.95 28-JUL-15:02 0.00 0.00 0.00
August 0.135233E+11 0.00 699.28 0.779757E+10 0.00 0.00 0.00 0.00 20299.54 12-AUG-08:62 14646.63 19-AUG-15:02 0.00 0.00 0.00
September 0.125306E+11 0.00 678.35 0.708070E+10 0.00 0.00 0.00 0.00 18869.74 16-SEP-08:62 14643.59 08-SEP-15:02 0.00 0.00 0.00
October 0.110591E+11 0.00 690.49 0.598321E+10 0.00 0.00 0.00 0.00 19526.75 01-OCT-08:62 14793.07 18-OCT-15:02 0.00 0.00 0.00
November 0.747555E+10 0.00 606.47 0.360117E+10 0.00 0.00 0.00 0.00 19491.81 24-NOV-09:02 14825.79 14-NOV-16:02 0.00 0.00 0.00
December 0.484260E+10 0.00 519.36 0.213318E+10 0.00 0.00 0.00 0.00 20291.47 23-DEC-09:02 14825.36 20-DEC-16:02 0.00 0.00 0.00
                               
Annual Sum or Average 0.114239E+12 0.00 7505.39 0.625597E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.360931E+10 0.00 480.47 0.149835E+10 0.00 0.00 0.00 0.00 18473.74   14643.59   0.00 0.00 0.00
Maximum of Months 0.144997E+11 0.00 712.44 0.863567E+10 0.00 0.00 0.00 0.00 20730.55   15339.17   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.455826E+11 0.00 631.01 0.283158E+11 0.00 0.00 0.00 0.00 56760.76 02-JAN-14:30 44761.69 02-JAN-14:30 0.00 0.00 0.00
February 0.414757E+11 0.00 580.44 0.251492E+11 0.00 0.00 0.00 0.00 50980.70 11-FEB-14:20 43095.66 22-FEB-14:50 0.00 0.00 0.00
March 0.422313E+11 0.00 656.50 0.226321E+11 0.00 0.00 0.00 0.00 45455.82 04-MAR-20:20 35249.05 02-MAR-14:30 0.00 0.00 0.00
April 0.436538E+11 0.00 687.47 0.221405E+11 0.00 0.00 0.00 0.00 39866.44 07-APR-21:00 28952.64 15-APR-19:10 0.00 0.00 0.00
May 0.501381E+11 0.00 739.17 0.247021E+11 0.00 0.00 0.00 0.00 42893.49 25-MAY-20:50 26833.81 22-MAY-20:20 0.00 0.00 0.00
June 0.547656E+11 0.00 720.00 0.278189E+11 0.00 0.00 0.00 0.00 47398.96 18-JUN-20:20 30321.22 03-JUN-21:00 0.00 0.00 0.00
July 0.612697E+11 0.00 744.00 0.332071E+11 0.00 0.00 0.00 0.00 42047.07 29-JUL-19:10 35459.18 29-JUL-19:10 0.00 0.00 0.00
August 0.610536E+11 0.00 744.00 0.333345E+11 0.00 0.00 0.00 0.00 41340.99 20-AUG-20:03 33042.52 20-AUG-20:03 0.00 0.00 0.00
September 0.681249E+11 0.00 720.00 0.411311E+11 0.00 0.00 0.00 0.00 48350.88 30-SEP-13:30 35708.57 23-SEP-12:10 0.00 0.00 0.00
October 0.720983E+11 0.00 742.83 0.447246E+11 0.00 0.00 0.00 0.00 52569.55 25-OCT-12:30 40364.81 25-OCT-12:40 0.00 0.00 0.00
November 0.595191E+11 0.00 675.14 0.363804E+11 0.00 0.00 0.00 0.00 55189.48 07-NOV-13:30 44615.28 07-NOV-13:40 0.00 0.00 0.00
December 0.486168E+11 0.00 627.68 0.294926E+11 0.00 0.00 0.00 0.00 56667.85 09-DEC-12:30 45453.35 03-DEC-14:00 0.00 0.00 0.00
                               
Annual Sum or Average 0.648529E+12 0.00 8268.25 0.369029E+12 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.414757E+11 0.00 580.44 0.221405E+11 0.00 0.00 0.00 0.00 39866.44   26833.81   0.00 0.00 0.00
Maximum of Months 0.720983E+11 0.00 744.00 0.447246E+11 0.00 0.00 0.00 0.00 56760.76   45453.35   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.449269E+11 0.00 521.43 0.235372E+11 0.00 0.00 0.00 0.00 138891.19 07-JAN-09:01 93859.06 24-JAN-19:01 0.00 0.00 0.00
February 0.495889E+11 0.00 469.73 0.280714E+11 0.00 0.00 0.00 0.00 129388.70 18-FEB-19:02 97058.33 24-FEB-19:01 0.00 0.00 0.00
March 0.615357E+11 0.00 529.44 0.359941E+11 0.00 0.00 0.00 0.00 137864.32 19-MAR-08:62 96637.96 14-MAR-18:02 0.00 0.00 0.00
April 0.736779E+11 0.00 538.09 0.456159E+11 0.00 0.00 0.00 0.00 125820.00 29-APR-18:02 97018.26 17-APR-18:02 0.00 0.00 0.00
May 0.914833E+11 0.00 616.31 0.602573E+11 0.00 0.00 0.00 0.00 138635.74 24-MAY-18:02 95612.31 20-MAY-08:62 0.00 0.00 0.00
June 0.978750E+11 0.00 624.67 0.662440E+11 0.00 0.00 0.00 0.00 117525.29 23-JUN-15:02 95497.15 17-JUN-08:62 0.00 0.00 0.00
July 0.103723E+12 0.00 662.78 0.704427E+11 0.00 0.00 0.00 0.00 126891.49 02-JUL-18:02 95575.59 29-JUL-18:02 0.00 0.00 0.00
August 0.969086E+11 0.00 633.36 0.644793E+11 0.00 0.00 0.00 0.00 135273.80 12-AUG-08:62 94561.89 19-AUG-18:02 0.00 0.00 0.00
September 0.919014E+11 0.00 611.47 0.608522E+11 0.00 0.00 0.00 0.00 117910.02 16-SEP-08:62 94297.91 01-SEP-18:02 0.00 0.00 0.00
October 0.832404E+11 0.00 581.76 0.524719E+11 0.00 0.00 0.00 0.00 128888.42 01-OCT-08:62 96481.19 17-OCT-18:02 0.00 0.00 0.00
November 0.655798E+11 0.00 516.91 0.386498E+11 0.00 0.00 0.00 0.00 128391.06 24-NOV-09:02 97905.99 12-NOV-09:02 0.00 0.00 0.00
December 0.511800E+11 0.00 525.23 0.272134E+11 0.00 0.00 0.00 0.00 133545.72 23-DEC-09:02 94147.29 09-DEC-19:02 0.00 0.00 0.00
                               
Annual Sum or Average 0.911621E+12 0.00 6831.19 0.573829E+12 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.449269E+11 0.00 469.73 0.235372E+11 0.00 0.00 0.00 0.00 117525.29   93859.06   0.00 0.00 0.00
Maximum of Months 0.103723E+12 0.00 662.78 0.704427E+11 0.00 0.00 0.00 0.00 138891.19   97905.99   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_5_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.579143E+10 0.00 596.14 0.303351E+10 0.00 0.00 0.00 0.00 18372.60 07-JAN-09:01 13721.08 26-JAN-16:02 0.00 0.00 0.00
February 0.634637E+10 0.00 575.20 0.342013E+10 0.00 0.00 0.00 0.00 17500.21 18-FEB-09:01 13720.45 24-FEB-19:01 0.00 0.00 0.00
March 0.803494E+10 0.00 648.02 0.441324E+10 0.00 0.00 0.00 0.00 18429.89 19-MAR-08:62 13709.61 15-MAR-15:01 0.00 0.00 0.00
April 0.100700E+11 0.00 684.62 0.571153E+10 0.00 0.00 0.00 0.00 16793.66 29-APR-08:62 13221.16 19-APR-08:62 0.00 0.00 0.00
May 0.122725E+11 0.00 711.56 0.709469E+10 0.00 0.00 0.00 0.00 17831.74 24-MAY-18:02 13056.21 20-MAY-15:02 0.00 0.00 0.00
June 0.135563E+11 0.00 696.88 0.805376E+10 0.00 0.00 0.00 0.00 16021.98 21-JUN-18:02 12993.37 01-JUN-15:02 0.00 0.00 0.00
July 0.148119E+11 0.00 723.68 0.905932E+10 0.00 0.00 0.00 0.00 16503.21 02-JUL-18:02 13310.62 29-JUL-15:02 0.00 0.00 0.00
August 0.138300E+11 0.00 710.00 0.820418E+10 0.00 0.00 0.00 0.00 18285.23 12-AUG-08:62 13007.48 31-AUG-15:02 0.00 0.00 0.00
September 0.138651E+11 0.00 696.03 0.840389E+10 0.00 0.00 0.00 0.00 16638.77 05-SEP-08:62 13045.20 08-SEP-15:02 0.00 0.00 0.00
October 0.128383E+11 0.00 714.50 0.754117E+10 0.00 0.00 0.00 0.00 17513.28 01-OCT-08:62 13355.80 25-OCT-15:02 0.00 0.00 0.00
November 0.927716E+10 0.00 652.84 0.505158E+10 0.00 0.00 0.00 0.00 17481.22 24-NOV-09:02 13268.13 14-NOV-16:02 0.00 0.00 0.00
December 0.625108E+10 0.00 598.51 0.315066E+10 0.00 0.00 0.00 0.00 18444.89 23-DEC-09:02 13344.29 20-DEC-16:02 0.00 0.00 0.00
                               
Annual Sum or Average 0.126945E+12 0.00 8007.98 0.731377E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.579143E+10 0.00 575.20 0.303351E+10 0.00 0.00 0.00 0.00 16021.98   12993.37   0.00 0.00 0.00
Maximum of Months 0.148119E+11 0.00 723.68 0.905932E+10 0.00 0.00 0.00 0.00 18444.89   13721.08   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_6_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.389451E+10 0.00 489.05 0.173267E+10 0.00 0.00 0.00 0.00 18642.24 07-JAN-09:01 12961.58 15-JAN-16:02 0.00 0.00 0.00
February 0.484168E+10 0.00 519.57 0.239041E+10 0.00 0.00 0.00 0.00 17557.14 18-FEB-09:01 13836.07 22-FEB-16:02 0.00 0.00 0.00
March 0.685468E+10 0.00 606.65 0.359389E+10 0.00 0.00 0.00 0.00 18563.07 19-MAR-08:62 13375.00 17-MAR-08:62 0.00 0.00 0.00
April 0.946399E+10 0.00 680.89 0.527368E+10 0.00 0.00 0.00 0.00 17000.77 29-APR-18:02 13471.85 16-APR-15:02 0.00 0.00 0.00
May 0.122603E+11 0.00 712.46 0.707278E+10 0.00 0.00 0.00 0.00 18307.32 24-MAY-18:02 13148.47 20-MAY-15:02 0.00 0.00 0.00
June 0.137561E+11 0.00 698.47 0.821296E+10 0.00 0.00 0.00 0.00 16125.98 21-JUN-18:02 13104.78 01-JUN-15:02 0.00 0.00 0.00
July 0.149366E+11 0.00 724.11 0.914412E+10 0.00 0.00 0.00 0.00 16773.25 02-JUL-18:02 13458.02 29-JUL-15:02 0.00 0.00 0.00
August 0.135635E+11 0.00 709.25 0.790627E+10 0.00 0.00 0.00 0.00 18332.99 12-AUG-08:62 12993.49 19-AUG-15:02 0.00 0.00 0.00
September 0.130218E+11 0.00 692.80 0.753970E+10 0.00 0.00 0.00 0.00 16839.37 05-SEP-08:62 12975.74 13-SEP-15:02 0.00 0.00 0.00
October 0.112438E+11 0.00 706.21 0.619810E+10 0.00 0.00 0.00 0.00 17634.97 01-OCT-08:62 13082.81 17-OCT-18:02 0.00 0.00 0.00
November 0.753874E+10 0.00 614.17 0.385848E+10 0.00 0.00 0.00 0.00 17597.36 24-NOV-09:02 13215.53 14-NOV-16:02 0.00 0.00 0.00
December 0.441693E+10 0.00 503.24 0.196275E+10 0.00 0.00 0.00 0.00 18308.78 23-DEC-09:02 13014.50 03-DEC-19:02 0.00 0.00 0.00
                               
Annual Sum or Average 0.115793E+12 0.00 7656.88 0.648858E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.389451E+10 0.00 489.05 0.173267E+10 0.00 0.00 0.00 0.00 16125.98   12961.58   0.00 0.00 0.00
Maximum of Months 0.149366E+11 0.00 724.11 0.914412E+10 0.00 0.00 0.00 0.00 18642.24   13836.07   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_1_FLR_6 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.144156E+10 0.00 556.97 0.717942E+09 0.00 0.00 0.00 0.00 5663.35 07-JAN-09:01 4051.79 26-JAN-16:02 0.00 0.00 0.00
February 0.171243E+10 0.00 553.32 0.919900E+09 0.00 0.00 0.00 0.00 5429.47 02-FEB-09:02 4051.52 24-FEB-19:01 0.00 0.00 0.00
March 0.224357E+10 0.00 616.58 0.124199E+10 0.00 0.00 0.00 0.00 5599.15 19-MAR-08:62 4050.10 20-MAR-15:01 0.00 0.00 0.00
April 0.282257E+10 0.00 668.40 0.164174E+10 0.00 0.00 0.00 0.00 5186.85 16-APR-08:62 3931.78 14-APR-15:02 0.00 0.00 0.00
May 0.342546E+10 0.00 703.88 0.201743E+10 0.00 0.00 0.00 0.00 5334.89 24-MAY-18:02 3933.63 31-MAY-15:02 0.00 0.00 0.00
June 0.360329E+10 0.00 686.68 0.212289E+10 0.00 0.00 0.00 0.00 5046.45 13-JUN-08:61 3934.69 28-JUN-15:02 0.00 0.00 0.00
July 0.402515E+10 0.00 716.26 0.246315E+10 0.00 0.00 0.00 0.00 4915.73 24-JUL-08:62 3935.10 20-JUL-15:02 0.00 0.00 0.00
August 0.382786E+10 0.00 706.60 0.229348E+10 0.00 0.00 0.00 0.00 5581.22 12-AUG-08:62 3930.78 21-AUG-15:02 0.00 0.00 0.00
September 0.368803E+10 0.00 686.57 0.220648E+10 0.00 0.00 0.00 0.00 5143.77 16-SEP-08:62 3945.59 04-SEP-15:02 0.00 0.00 0.00
October 0.343720E+10 0.00 703.21 0.202046E+10 0.00 0.00 0.00 0.00 5322.42 01-OCT-08:62 3946.02 22-OCT-15:02 0.00 0.00 0.00
November 0.247786E+10 0.00 637.94 0.134372E+10 0.00 0.00 0.00 0.00 5327.78 24-NOV-09:02 3916.05 20-NOV-16:02 0.00 0.00 0.00
December 0.177414E+10 0.00 578.18 0.910788E+09 0.00 0.00 0.00 0.00 5645.65 23-DEC-09:02 4047.97 20-DEC-16:02 0.00 0.00 0.00
                               
Annual Sum or Average 0.344791E+11 0.00 7814.58 0.199000E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.144156E+10 0.00 553.32 0.717942E+09 0.00 0.00 0.00 0.00 4915.73   3916.05   0.00 0.00 0.00
Maximum of Months 0.402515E+10 0.00 716.26 0.246315E+10 0.00 0.00 0.00 0.00 5663.35   4051.79   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_2_FLR_6 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.945329E+09 0.00 454.10 0.402077E+09 0.00 0.00 0.00 0.00 5714.15 07-JAN-09:01 4086.30 26-JAN-16:02 0.00 0.00 0.00
February 0.132540E+10 0.00 495.67 0.640397E+09 0.00 0.00 0.00 0.00 5339.79 18-FEB-09:01 4085.07 24-FEB-16:02 0.00 0.00 0.00
March 0.194328E+10 0.00 579.87 0.101694E+10 0.00 0.00 0.00 0.00 5641.16 19-MAR-08:62 4083.95 15-MAR-18:02 0.00 0.00 0.00
April 0.266844E+10 0.00 664.73 0.151290E+10 0.00 0.00 0.00 0.00 5243.10 16-APR-08:62 3960.39 02-APR-18:02 0.00 0.00 0.00
May 0.342405E+10 0.00 704.77 0.201205E+10 0.00 0.00 0.00 0.00 5486.29 24-MAY-18:02 3970.16 19-MAY-18:02 0.00 0.00 0.00
June 0.365590E+10 0.00 688.70 0.216267E+10 0.00 0.00 0.00 0.00 5059.37 13-JUN-08:61 3964.88 28-JUN-15:02 0.00 0.00 0.00
July 0.405891E+10 0.00 717.75 0.248440E+10 0.00 0.00 0.00 0.00 4948.22 15-JUL-08:62 3981.49 28-JUL-15:02 0.00 0.00 0.00
August 0.376171E+10 0.00 705.14 0.222505E+10 0.00 0.00 0.00 0.00 5600.35 12-AUG-08:62 3975.00 06-AUG-15:02 0.00 0.00 0.00
September 0.347283E+10 0.00 682.14 0.199981E+10 0.00 0.00 0.00 0.00 5201.33 16-SEP-08:62 3973.57 20-SEP-15:02 0.00 0.00 0.00
October 0.302530E+10 0.00 694.87 0.165297E+10 0.00 0.00 0.00 0.00 5363.71 01-OCT-08:62 3949.43 14-OCT-15:02 0.00 0.00 0.00
November 0.202302E+10 0.00 608.71 0.984997E+09 0.00 0.00 0.00 0.00 5365.09 24-NOV-09:02 3964.35 14-NOV-16:02 0.00 0.00 0.00
December 0.129114E+10 0.00 498.49 0.579014E+09 0.00 0.00 0.00 0.00 5598.75 23-DEC-09:02 3961.20 03-DEC-16:02 0.00 0.00 0.00
                               
Annual Sum or Average 0.315953E+11 0.00 7494.95 0.176733E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.945329E+09 0.00 454.10 0.402077E+09 0.00 0.00 0.00 0.00 4948.22   3949.43   0.00 0.00 0.00
Maximum of Months 0.405891E+10 0.00 717.75 0.248440E+10 0.00 0.00 0.00 0.00 5714.15   4086.30   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.129891E+11 0.00 662.08 0.838847E+10 0.00 0.00 0.00 0.00 23619.09 07-JAN-09:01 17032.58 26-JAN-16:02 0.00 0.00 0.00
February 0.124059E+11 0.00 598.68 0.792331E+10 0.00 0.00 0.00 0.00 22992.84 02-FEB-09:02 17029.95 24-FEB-19:01 0.00 0.00 0.00
March 0.133315E+11 0.00 654.76 0.818121E+10 0.00 0.00 0.00 0.00 23720.52 19-MAR-08:62 17025.57 20-MAR-15:01 0.00 0.00 0.00
April 0.142435E+11 0.00 661.02 0.867965E+10 0.00 0.00 0.00 0.00 21764.66 16-APR-08:62 16491.66 05-APR-15:02 0.00 0.00 0.00
May 0.163781E+11 0.00 693.64 0.998314E+10 0.00 0.00 0.00 0.00 23176.37 24-MAY-18:02 16355.02 01-MAY-15:02 0.00 0.00 0.00
June 0.175109E+11 0.00 678.07 0.109835E+11 0.00 0.00 0.00 0.00 20430.00 13-JUN-08:61 16226.52 01-JUN-15:02 0.00 0.00 0.00
July 0.191637E+11 0.00 707.29 0.122875E+11 0.00 0.00 0.00 0.00 21396.89 02-JUL-18:02 16550.55 28-JUL-15:02 0.00 0.00 0.00
August 0.188724E+11 0.00 696.38 0.121001E+11 0.00 0.00 0.00 0.00 23868.60 12-AUG-08:62 16419.01 31-AUG-15:02 0.00 0.00 0.00
September 0.199313E+11 0.00 684.67 0.132801E+11 0.00 0.00 0.00 0.00 20813.32 28-SEP-08:62 16534.91 29-SEP-15:02 0.00 0.00 0.00
October 0.204146E+11 0.00 709.93 0.138096E+11 0.00 0.00 0.00 0.00 22524.73 01-OCT-08:62 16449.09 28-OCT-15:02 0.00 0.00 0.00
November 0.168684E+11 0.00 668.46 0.110169E+11 0.00 0.00 0.00 0.00 22609.12 24-NOV-09:02 16474.38 25-NOV-16:02 0.00 0.00 0.00
December 0.141203E+11 0.00 657.81 0.890404E+10 0.00 0.00 0.00 0.00 23768.39 23-DEC-09:02 17016.97 20-DEC-16:02 0.00 0.00 0.00
                               
Annual Sum or Average 0.196230E+12 0.00 8072.79 0.125538E+12 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.124059E+11 0.00 598.68 0.792331E+10 0.00 0.00 0.00 0.00 20430.00   16226.52   0.00 0.00 0.00
Maximum of Months 0.204146E+11 0.00 709.93 0.138096E+11 0.00 0.00 0.00 0.00 23868.60   17032.58   0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 555.54 361.23 194.31 900.07 166.72 0.00 0.00 0.00
February 490.42 278.92 211.50 844.33 130.15 0.00 0.00 0.00
March 379.01 156.70 222.31 679.10 95.01 0.00 0.00 0.00
April 271.75 55.67 216.09 561.84 40.43 0.00 0.00 0.00
May 212.18 6.74 205.44 524.16 6.56 0.00 0.00 0.00
June 200.14 0.42 199.72 548.84 0.36 0.00 0.00 0.00
July 214.16 1.80 212.36 585.41 2.30 0.00 0.00 0.00
August 240.75 18.00 222.75 632.33 0.13 0.00 0.00 0.00
September 312.20 77.13 235.07 754.22 3.77 0.00 0.00 0.00
October 433.29 206.02 227.26 886.28 12.12 0.00 0.00 0.00
November 490.86 275.48 215.37 891.20 62.50 0.00 0.00 0.00
December 535.60 338.19 197.42 885.80 136.38 0.00 0.00 0.00
                 
Annual Sum or Average 360.73 147.45 213.28 723.87 54.39 0.00 0.00 0.00
Minimum of Months 200.14 0.42 194.31 524.16 0.13 0.00 0.00 0.00
Maximum of Months 555.54 361.23 235.07 900.07 166.72 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CAFE_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 1564.36 1017.20 547.16 2522.61 500.18 0.00 0.00 0.00
February 1380.98 785.42 595.57 2364.35 397.48 0.00 0.00 0.00
March 1067.25 441.25 626.01 1897.89 301.51 0.00 0.00 0.00
April 765.24 156.76 608.48 1568.11 142.90 0.00 0.00 0.00
May 597.48 18.97 578.52 1438.87 28.83 0.00 0.00 0.00
June 563.58 1.17 562.41 1502.50 3.88 0.00 0.00 0.00
July 603.05 5.06 597.99 1623.72 12.18 0.00 0.00 0.00
August 677.95 50.70 627.25 1743.64 2.58 0.00 0.00 0.00
September 879.14 217.19 661.95 2110.43 24.80 0.00 0.00 0.00
October 1220.12 580.15 639.96 2481.21 54.77 0.00 0.00 0.00
November 1382.22 775.75 606.47 2492.39 201.33 0.00 0.00 0.00
December 1508.22 952.31 555.91 2484.75 415.20 0.00 0.00 0.00
                 
Annual Sum or Average 1015.79 415.21 600.58 2017.47 172.85 0.00 0.00 0.00
Minimum of Months 563.58 1.17 547.16 1438.87 2.58 0.00 0.00 0.00
Maximum of Months 1564.36 1017.20 661.95 2522.61 500.18 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: LOBBY_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 2032.19 1321.40 710.79 3381.22 635.96 0.00 0.00 0.00
February 1793.98 1020.30 773.67 3173.01 499.94 0.00 0.00 0.00
March 1386.42 573.21 813.22 2549.42 377.97 0.00 0.00 0.00
April 994.09 203.64 790.45 2113.68 172.51 0.00 0.00 0.00
May 776.16 24.64 751.52 1949.82 32.99 0.00 0.00 0.00
June 732.13 1.52 730.60 2040.57 3.97 0.00 0.00 0.00
July 783.39 6.58 776.82 2202.27 13.52 0.00 0.00 0.00
August 880.69 65.86 814.83 2372.17 1.93 0.00 0.00 0.00
September 1142.06 282.14 859.91 2868.12 24.48 0.00 0.00 0.00
October 1585.00 753.65 831.35 3368.04 53.38 0.00 0.00 0.00
November 1795.58 1007.74 787.84 3367.13 246.15 0.00 0.00 0.00
December 1959.26 1237.10 722.16 3333.82 523.23 0.00 0.00 0.00
                 
Annual Sum or Average 1319.57 539.38 780.19 2724.35 214.30 0.00 0.00 0.00
Minimum of Months 732.13 1.52 710.79 1949.82 1.93 0.00 0.00 0.00
Maximum of Months 2032.19 1321.40 859.91 3381.22 635.96 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 109.84 71.42 38.42 176.69 33.73 0.00 0.00 0.00
February 96.96 55.15 41.82 164.45 26.26 0.00 0.00 0.00
March 74.94 30.98 43.95 130.10 19.13 0.00 0.00 0.00
April 53.73 11.01 42.72 106.85 8.16 0.00 0.00 0.00
May 41.95 1.33 40.62 100.95 1.29 0.00 0.00 0.00
June 39.57 0.08 39.49 106.98 0.09 0.00 0.00 0.00
July 42.34 0.36 41.99 114.71 0.45 0.00 0.00 0.00
August 47.60 3.56 44.04 124.05 0.03 0.00 0.00 0.00
September 61.73 15.25 46.48 150.02 0.68 0.00 0.00 0.00
October 85.67 40.73 44.93 176.10 1.95 0.00 0.00 0.00
November 97.05 54.47 42.58 175.81 12.17 0.00 0.00 0.00
December 105.90 66.86 39.03 173.69 27.41 0.00 0.00 0.00
                 
Annual Sum or Average 71.32 29.15 42.17 141.59 10.88 0.00 0.00 0.00
Minimum of Months 39.57 0.08 38.42 100.95 0.03 0.00 0.00 0.00
Maximum of Months 109.84 71.42 46.48 176.69 33.73 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_1_FLR_3_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 94.49 40.86 53.63 142.60 67.32 0.00 0.00 0.00
February 118.59 54.01 64.58 195.21 52.23 0.00 0.00 0.00
March 146.90 67.15 79.75 241.66 37.46 0.00 0.00 0.00
April 161.24 74.56 86.68 291.76 15.07 0.00 0.00 0.00
May 147.47 56.94 90.54 305.99 2.41 0.00 0.00 0.00
June 124.86 35.04 89.82 290.48 0.17 0.00 0.00 0.00
July 139.32 43.06 96.27 321.61 0.86 0.00 0.00 0.00
August 139.00 45.18 93.82 313.71 0.05 0.00 0.00 0.00
September 118.61 34.96 83.66 274.99 1.33 0.00 0.00 0.00
October 118.21 46.17 72.04 246.48 3.71 0.00 0.00 0.00
November 97.25 35.62 61.63 183.43 24.27 0.00 0.00 0.00
December 97.50 43.57 53.92 155.74 53.27 0.00 0.00 0.00
                 
Annual Sum or Average 125.34 48.08 77.26 247.25 21.38 0.00 0.00 0.00
Minimum of Months 94.49 34.96 53.63 142.60 0.05 0.00 0.00 0.00
Maximum of Months 161.24 74.56 96.27 321.61 67.32 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_2_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 23.33 0.00 23.33 31.12 35.24 0.00 0.00 0.00
February 27.61 0.00 27.61 44.21 27.21 0.00 0.00 0.00
March 32.94 0.00 32.94 51.88 19.79 0.00 0.00 0.00
April 37.01 0.21 36.79 71.00 7.85 0.00 0.00 0.00
May 42.02 1.72 40.30 100.44 1.25 0.00 0.00 0.00
June 45.04 3.24 41.80 118.66 0.10 0.00 0.00 0.00
July 45.63 2.27 43.35 121.60 0.47 0.00 0.00 0.00
August 40.41 0.42 39.98 108.56 0.03 0.00 0.00 0.00
September 35.78 0.01 35.77 98.73 0.69 0.00 0.00 0.00
October 29.96 0.00 29.96 74.86 1.84 0.00 0.00 0.00
November 26.05 0.00 26.05 54.05 12.49 0.00 0.00 0.00
December 23.07 0.00 23.07 34.58 27.82 0.00 0.00 0.00
                 
Annual Sum or Average 34.10 0.66 33.44 75.96 11.16 0.00 0.00 0.00
Minimum of Months 23.07 0.00 23.07 31.12 0.03 0.00 0.00 0.00
Maximum of Months 45.63 3.24 43.35 121.60 35.24 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_2_FLR_3_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 94.49 40.86 53.63 147.63 64.67 0.00 0.00 0.00
February 118.59 54.01 64.58 199.21 50.36 0.00 0.00 0.00
March 146.90 67.15 79.75 244.50 36.31 0.00 0.00 0.00
April 161.24 74.56 86.68 292.92 14.69 0.00 0.00 0.00
May 147.47 56.94 90.54 306.00 2.40 0.00 0.00 0.00
June 124.86 35.04 89.82 290.05 0.18 0.00 0.00 0.00
July 139.32 43.06 96.27 321.36 0.86 0.00 0.00 0.00
August 139.00 45.18 93.82 314.25 0.05 0.00 0.00 0.00
September 118.61 34.96 83.66 276.71 1.23 0.00 0.00 0.00
October 118.21 46.17 72.04 249.71 3.37 0.00 0.00 0.00
November 97.25 35.62 61.63 187.38 23.28 0.00 0.00 0.00
December 97.50 43.57 53.92 160.29 50.99 0.00 0.00 0.00
                 
Annual Sum or Average 125.34 48.08 77.26 249.44 20.57 0.00 0.00 0.00
Minimum of Months 94.49 34.96 53.63 147.63 0.05 0.00 0.00 0.00
Maximum of Months 161.24 74.56 96.27 321.36 64.67 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 87.85 57.13 30.73 136.24 36.51 0.00 0.00 0.00
February 77.56 44.11 33.45 126.53 29.50 0.00 0.00 0.00
March 59.94 24.78 35.16 99.58 23.00 0.00 0.00 0.00
April 42.98 8.80 34.17 81.72 12.60 0.00 0.00 0.00
May 33.55 1.07 32.49 73.72 3.24 0.00 0.00 0.00
June 31.65 0.07 31.59 77.37 0.83 0.00 0.00 0.00
July 33.87 0.28 33.58 84.83 1.60 0.00 0.00 0.00
August 38.07 2.85 35.23 90.93 0.79 0.00 0.00 0.00
September 49.37 12.20 37.18 113.15 3.02 0.00 0.00 0.00
October 68.52 32.58 35.94 134.09 5.12 0.00 0.00 0.00
November 77.63 43.57 34.06 134.10 15.45 0.00 0.00 0.00
December 84.70 53.48 31.22 134.28 31.18 0.00 0.00 0.00
                 
Annual Sum or Average 57.05 23.32 33.73 107.11 13.50 0.00 0.00 0.00
Minimum of Months 31.65 0.07 30.73 73.72 0.79 0.00 0.00 0.00
Maximum of Months 87.85 57.13 37.18 136.24 36.51 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 18.66 0.00 18.66 26.17 28.08 0.00 0.00 0.00
February 22.09 0.00 22.09 37.58 21.21 0.00 0.00 0.00
March 26.35 0.00 26.35 44.49 14.90 0.00 0.00 0.00
April 29.61 0.17 29.44 60.94 5.16 0.00 0.00 0.00
May 33.62 1.38 32.24 85.39 0.81 0.00 0.00 0.00
June 36.04 2.59 33.45 99.91 0.04 0.00 0.00 0.00
July 36.50 1.82 34.69 102.62 0.23 0.00 0.00 0.00
August 32.33 0.34 31.99 92.33 0.01 0.00 0.00 0.00
September 28.63 0.01 28.62 83.92 0.30 0.00 0.00 0.00
October 23.97 0.00 23.97 64.46 1.06 0.00 0.00 0.00
November 20.84 0.00 20.84 46.33 9.57 0.00 0.00 0.00
December 18.46 0.00 18.46 29.31 22.01 0.00 0.00 0.00
                 
Annual Sum or Average 27.29 0.53 26.76 64.58 8.57 0.00 0.00 0.00
Minimum of Months 18.46 0.00 18.46 26.17 0.01 0.00 0.00 0.00
Maximum of Months 36.50 2.59 34.69 102.62 28.08 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_5_FLR_3_WALL_EAST_WINDOW

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 104.88 50.26 54.62 156.90 64.07 0.00 0.00 0.00
February 121.65 56.52 65.13 195.83 48.12 0.00 0.00 0.00
March 148.18 70.06 78.12 237.71 33.29 0.00 0.00 0.00
April 161.02 71.88 89.14 291.42 14.04 0.00 0.00 0.00
May 152.34 60.91 91.43 315.03 2.21 0.00 0.00 0.00
June 149.72 57.46 92.26 333.55 0.19 0.00 0.00 0.00
July 154.05 55.59 98.46 348.00 0.81 0.00 0.00 0.00
August 140.80 47.14 93.66 318.17 0.05 0.00 0.00 0.00
September 135.65 48.98 86.67 305.32 1.26 0.00 0.00 0.00
October 124.71 53.52 71.19 258.77 3.51 0.00 0.00 0.00
November 101.55 40.44 61.11 188.94 22.41 0.00 0.00 0.00
December 82.13 29.10 53.03 128.41 51.48 0.00 0.00 0.00
                 
Annual Sum or Average 131.41 53.45 77.96 256.75 20.01 0.00 0.00 0.00
Minimum of Months 82.13 29.10 53.03 128.41 0.05 0.00 0.00 0.00
Maximum of Months 161.02 71.88 98.46 348.00 64.07 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 109.84 71.42 38.42 175.72 33.57 0.00 0.00 0.00
February 96.96 55.15 41.82 163.64 25.94 0.00 0.00 0.00
March 74.94 30.98 43.95 129.10 18.71 0.00 0.00 0.00
April 53.73 11.01 42.72 106.19 7.78 0.00 0.00 0.00
May 41.95 1.33 40.62 100.66 1.25 0.00 0.00 0.00
June 39.57 0.08 39.49 106.08 0.10 0.00 0.00 0.00
July 42.34 0.36 41.99 114.15 0.45 0.00 0.00 0.00
August 47.60 3.56 44.04 123.90 0.03 0.00 0.00 0.00
September 61.73 15.25 46.48 149.38 0.69 0.00 0.00 0.00
October 85.67 40.73 44.93 175.73 1.88 0.00 0.00 0.00
November 97.05 54.47 42.58 175.35 12.03 0.00 0.00 0.00
December 105.90 66.86 39.03 173.65 26.97 0.00 0.00 0.00
                 
Annual Sum or Average 71.32 29.15 42.17 141.02 10.72 0.00 0.00 0.00
Minimum of Months 39.57 0.08 38.42 100.66 0.03 0.00 0.00 0.00
Maximum of Months 109.84 71.42 46.48 175.73 33.57 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_6_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 23.33 0.00 23.33 30.10 35.15 0.00 0.00 0.00
February 27.61 0.00 27.61 43.28 27.01 0.00 0.00 0.00
March 32.94 0.00 32.94 50.93 19.57 0.00 0.00 0.00
April 37.01 0.21 36.79 70.29 7.48 0.00 0.00 0.00
May 42.02 1.72 40.30 100.14 1.20 0.00 0.00 0.00
June 45.04 3.24 41.80 117.77 0.11 0.00 0.00 0.00
July 45.63 2.27 43.35 121.04 0.46 0.00 0.00 0.00
August 40.41 0.42 39.98 108.40 0.03 0.00 0.00 0.00
September 35.78 0.01 35.77 98.04 0.70 0.00 0.00 0.00
October 29.96 0.00 29.96 74.38 1.78 0.00 0.00 0.00
November 26.05 0.00 26.05 53.51 12.37 0.00 0.00 0.00
December 23.07 0.00 23.07 34.46 27.27 0.00 0.00 0.00
                 
Annual Sum or Average 34.10 0.66 33.44 75.35 11.03 0.00 0.00 0.00
Minimum of Months 23.07 0.00 23.07 30.10 0.03 0.00 0.00 0.00
Maximum of Months 45.63 3.24 43.35 121.04 35.15 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_6_FLR_3_WALL_EAST_WINDOW

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 104.88 50.26 54.62 161.61 61.29 0.00 0.00 0.00
February 121.65 56.52 65.13 199.56 46.30 0.00 0.00 0.00
March 148.18 70.06 78.12 240.37 32.19 0.00 0.00 0.00
April 161.02 71.88 89.14 292.52 13.68 0.00 0.00 0.00
May 152.34 60.91 91.43 315.06 2.20 0.00 0.00 0.00
June 149.72 57.46 92.26 333.15 0.19 0.00 0.00 0.00
July 154.05 55.59 98.46 347.76 0.81 0.00 0.00 0.00
August 140.80 47.14 93.66 318.71 0.05 0.00 0.00 0.00
September 135.65 48.98 86.67 306.99 1.18 0.00 0.00 0.00
October 124.71 53.52 71.19 261.90 3.20 0.00 0.00 0.00
November 101.55 40.44 61.11 192.80 21.45 0.00 0.00 0.00
December 82.13 29.10 53.03 132.91 48.91 0.00 0.00 0.00
                 
Annual Sum or Average 131.41 53.45 77.96 258.85 19.18 0.00 0.00 0.00
Minimum of Months 82.13 29.10 53.03 132.91 0.05 0.00 0.00 0.00
Maximum of Months 161.02 71.88 98.46 347.76 61.29 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 29.54 0.00 29.54 42.65 44.84 0.00 0.00 0.00
February 34.97 0.00 34.97 61.44 33.95 0.00 0.00 0.00
March 41.71 0.00 41.71 72.74 24.28 0.00 0.00 0.00
April 46.86 0.27 46.60 98.45 9.60 0.00 0.00 0.00
May 53.22 2.18 51.04 135.43 1.58 0.00 0.00 0.00
June 57.04 4.10 52.94 156.32 0.22 0.00 0.00 0.00
July 57.78 2.88 54.91 159.97 0.76 0.00 0.00 0.00
August 51.17 0.54 50.63 143.18 0.08 0.00 0.00 0.00
September 45.31 0.01 45.30 129.71 1.35 0.00 0.00 0.00
October 37.94 0.00 37.94 99.07 3.08 0.00 0.00 0.00
November 32.99 0.00 32.99 72.96 16.65 0.00 0.00 0.00
December 29.22 0.00 29.22 47.46 35.50 0.00 0.00 0.00
                 
Annual Sum or Average 43.19 0.84 42.35 101.81 14.24 0.00 0.00 0.00
Minimum of Months 29.22 0.00 29.22 42.65 0.08 0.00 0.00 0.00
Maximum of Months 57.78 4.10 54.91 159.97 44.84 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 10.89 0.00 10.89 15.72 16.53 0.00 0.00 0.00
February 12.89 0.00 12.89 22.65 12.52 0.00 0.00 0.00
March 15.38 0.00 15.38 26.82 8.95 0.00 0.00 0.00
April 17.28 0.10 17.18 36.29 3.54 0.00 0.00 0.00
May 19.62 0.80 18.81 49.93 0.58 0.00 0.00 0.00
June 21.03 1.51 19.52 57.63 0.08 0.00 0.00 0.00
July 21.30 1.06 20.24 58.97 0.28 0.00 0.00 0.00
August 18.86 0.20 18.67 52.78 0.03 0.00 0.00 0.00
September 16.70 0.00 16.70 47.82 0.50 0.00 0.00 0.00
October 13.99 0.00 13.99 36.52 1.14 0.00 0.00 0.00
November 12.16 0.00 12.16 26.90 6.14 0.00 0.00 0.00
December 10.77 0.00 10.77 17.49 13.09 0.00 0.00 0.00
                 
Annual Sum or Average 15.92 0.31 15.61 37.53 5.25 0.00 0.00 0.00
Minimum of Months 10.77 0.00 10.77 15.72 0.03 0.00 0.00 0.00
Maximum of Months 21.30 1.51 20.24 58.97 16.53 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 51.25 33.32 17.93 85.04 15.26 0.00 0.00 0.00
February 45.24 25.73 19.51 79.71 11.65 0.00 0.00 0.00
March 34.96 14.46 20.51 63.97 8.40 0.00 0.00 0.00
April 25.07 5.14 19.93 53.24 3.59 0.00 0.00 0.00
May 19.57 0.62 18.95 50.19 0.60 0.00 0.00 0.00
June 18.46 0.04 18.43 52.06 0.07 0.00 0.00 0.00
July 19.76 0.17 19.59 55.68 0.27 0.00 0.00 0.00
August 22.21 1.66 20.55 60.11 0.03 0.00 0.00 0.00
September 28.80 7.12 21.69 72.06 0.47 0.00 0.00 0.00
October 39.97 19.01 20.97 84.42 1.11 0.00 0.00 0.00
November 45.28 25.41 19.87 84.62 5.74 0.00 0.00 0.00
December 49.41 31.20 18.21 83.66 12.41 0.00 0.00 0.00
                 
Annual Sum or Average 33.28 13.60 19.68 68.68 4.94 0.00 0.00 0.00
Minimum of Months 18.46 0.04 17.93 50.19 0.03 0.00 0.00 0.00
Maximum of Months 51.25 33.32 21.69 85.04 15.26 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 139.10 90.45 48.65 230.80 41.41 0.00 0.00 0.00
February 122.80 69.84 52.96 216.34 31.63 0.00 0.00 0.00
March 94.90 39.24 55.67 173.63 22.81 0.00 0.00 0.00
April 68.05 13.94 54.11 144.50 9.73 0.00 0.00 0.00
May 53.13 1.69 51.44 136.21 1.64 0.00 0.00 0.00
June 50.12 0.10 50.01 141.31 0.20 0.00 0.00 0.00
July 53.62 0.45 53.17 151.14 0.74 0.00 0.00 0.00
August 60.28 4.51 55.78 163.15 0.07 0.00 0.00 0.00
September 78.17 19.31 58.86 195.59 1.29 0.00 0.00 0.00
October 108.49 51.59 56.91 229.14 3.00 0.00 0.00 0.00
November 122.91 68.98 53.93 229.68 15.57 0.00 0.00 0.00
December 134.11 84.68 49.43 227.07 33.68 0.00 0.00 0.00
                 
Annual Sum or Average 90.33 36.92 53.40 186.40 13.41 0.00 0.00 0.00
Minimum of Months 50.12 0.10 48.65 136.21 0.07 0.00 0.00 0.00
Maximum of Months 139.10 90.45 58.86 230.80 41.41 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 109.84 71.42 38.42 174.61 33.54 0.00 0.00 0.00
February 96.96 55.15 41.82 162.11 26.18 0.00 0.00 0.00
March 74.94 30.98 43.95 127.74 19.03 0.00 0.00 0.00
April 53.73 11.01 42.72 104.71 8.12 0.00 0.00 0.00
May 41.95 1.33 40.62 99.32 1.24 0.00 0.00 0.00
June 39.57 0.08 39.49 105.44 0.08 0.00 0.00 0.00
July 42.34 0.36 41.99 113.04 0.43 0.00 0.00 0.00
August 47.60 3.56 44.04 122.41 0.04 0.00 0.00 0.00
September 61.73 15.25 46.48 148.11 0.64 0.00 0.00 0.00
October 85.67 40.73 44.93 174.13 1.86 0.00 0.00 0.00
November 97.05 54.47 42.58 173.70 11.98 0.00 0.00 0.00
December 105.90 66.86 39.03 171.50 27.30 0.00 0.00 0.00
                 
Annual Sum or Average 71.32 29.15 42.17 139.62 10.81 0.00 0.00 0.00
Minimum of Months 39.57 0.08 38.42 99.32 0.04 0.00 0.00 0.00
Maximum of Months 109.84 71.42 46.48 174.61 33.54 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_1_FLR_6_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 94.49 40.86 53.63 139.97 66.93 0.00 0.00 0.00
February 118.59 54.01 64.58 191.95 52.08 0.00 0.00 0.00
March 146.90 67.15 79.75 237.49 37.38 0.00 0.00 0.00
April 161.24 74.56 86.68 287.21 15.03 0.00 0.00 0.00
May 147.47 56.94 90.54 301.62 2.32 0.00 0.00 0.00
June 124.86 35.04 89.82 286.51 0.16 0.00 0.00 0.00
July 139.32 43.06 96.27 317.49 0.81 0.00 0.00 0.00
August 139.00 45.18 93.82 309.75 0.06 0.00 0.00 0.00
September 118.61 34.96 83.66 271.46 1.22 0.00 0.00 0.00
October 118.21 46.17 72.04 243.54 3.49 0.00 0.00 0.00
November 97.25 35.62 61.63 180.62 23.87 0.00 0.00 0.00
December 97.50 43.57 53.92 152.94 53.11 0.00 0.00 0.00
                 
Annual Sum or Average 125.34 48.08 77.26 243.66 21.24 0.00 0.00 0.00
Minimum of Months 94.49 34.96 53.63 139.97 0.06 0.00 0.00 0.00
Maximum of Months 161.24 74.56 96.27 317.49 66.93 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_2_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 23.33 0.00 23.33 30.32 34.97 0.00 0.00 0.00
February 27.61 0.00 27.61 43.13 27.08 0.00 0.00 0.00
March 32.94 0.00 32.94 50.45 19.70 0.00 0.00 0.00
April 37.01 0.21 36.79 69.28 7.80 0.00 0.00 0.00
May 42.02 1.72 40.30 98.67 1.21 0.00 0.00 0.00
June 45.04 3.24 41.80 116.89 0.09 0.00 0.00 0.00
July 45.63 2.27 43.35 119.85 0.44 0.00 0.00 0.00
August 40.41 0.42 39.98 107.01 0.04 0.00 0.00 0.00
September 35.78 0.01 35.77 97.39 0.63 0.00 0.00 0.00
October 29.96 0.00 29.96 73.91 1.71 0.00 0.00 0.00
November 26.05 0.00 26.05 53.11 12.25 0.00 0.00 0.00
December 23.07 0.00 23.07 33.71 27.65 0.00 0.00 0.00
                 
Annual Sum or Average 34.10 0.66 33.44 74.63 11.07 0.00 0.00 0.00
Minimum of Months 23.07 0.00 23.07 30.32 0.04 0.00 0.00 0.00
Maximum of Months 45.63 3.24 43.35 119.85 34.97 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_2_FLR_6_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 94.49 40.86 53.63 145.17 64.07 0.00 0.00 0.00
February 118.59 54.01 64.58 196.02 50.13 0.00 0.00 0.00
March 146.90 67.15 79.75 240.34 36.19 0.00 0.00 0.00
April 161.24 74.56 86.68 288.34 14.65 0.00 0.00 0.00
May 147.47 56.94 90.54 301.61 2.31 0.00 0.00 0.00
June 124.86 35.04 89.82 286.08 0.16 0.00 0.00 0.00
July 139.32 43.06 96.27 317.23 0.82 0.00 0.00 0.00
August 139.00 45.18 93.82 310.28 0.06 0.00 0.00 0.00
September 118.61 34.96 83.66 273.19 1.13 0.00 0.00 0.00
October 118.21 46.17 72.04 246.81 3.15 0.00 0.00 0.00
November 97.25 35.62 61.63 184.66 22.83 0.00 0.00 0.00
December 97.50 43.57 53.92 157.68 50.61 0.00 0.00 0.00
                 
Annual Sum or Average 125.34 48.08 77.26 245.89 20.38 0.00 0.00 0.00
Minimum of Months 94.49 34.96 53.63 145.17 0.06 0.00 0.00 0.00
Maximum of Months 161.24 74.56 96.27 317.23 64.07 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 161.09 104.75 56.34 252.99 51.08 0.00 0.00 0.00
February 142.21 80.88 61.33 236.24 39.09 0.00 0.00 0.00
March 109.90 45.44 64.46 187.95 27.33 0.00 0.00 0.00
April 78.80 16.14 62.66 157.19 10.48 0.00 0.00 0.00
May 61.53 1.95 59.57 151.70 1.57 0.00 0.00 0.00
June 58.04 0.12 57.92 160.49 0.08 0.00 0.00 0.00
July 62.10 0.52 61.58 172.11 0.47 0.00 0.00 0.00
August 69.81 5.22 64.59 185.22 0.02 0.00 0.00 0.00
September 90.53 22.37 68.17 220.72 0.72 0.00 0.00 0.00
October 125.64 59.74 65.90 256.81 2.53 0.00 0.00 0.00
November 142.33 79.88 62.45 253.77 17.97 0.00 0.00 0.00
December 155.31 98.06 57.25 249.21 41.64 0.00 0.00 0.00
                 
Annual Sum or Average 104.60 42.76 61.85 206.89 15.99 0.00 0.00 0.00
Minimum of Months 58.04 0.12 56.34 151.70 0.02 0.00 0.00 0.00
Maximum of Months 161.09 104.75 68.17 256.81 51.08 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: BANQUET_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 163.29 0.00 163.29 223.50 275.11 0.00 0.00 0.00
February 193.28 0.00 193.28 322.09 218.65 0.00 0.00 0.00
March 230.56 0.00 230.56 382.38 166.38 0.00 0.00 0.00
April 259.03 1.48 257.55 526.56 75.87 0.00 0.00 0.00
May 294.14 12.05 282.09 717.72 16.06 0.00 0.00 0.00
June 315.27 22.68 292.60 836.44 2.89 0.00 0.00 0.00
July 319.36 15.90 303.47 866.36 7.51 0.00 0.00 0.00
August 282.83 2.96 279.86 770.21 2.52 0.00 0.00 0.00
September 250.44 0.06 250.38 709.93 13.35 0.00 0.00 0.00
October 209.71 0.00 209.71 546.52 24.14 0.00 0.00 0.00
November 182.34 0.00 182.34 394.16 107.29 0.00 0.00 0.00
December 161.51 0.00 161.51 250.34 224.13 0.00 0.00 0.00
                 
Annual Sum or Average 238.71 4.62 234.09 546.57 93.96 0.00 0.00 0.00
Minimum of Months 161.51 0.00 161.51 223.50 2.52 0.00 0.00 0.00
Maximum of Months 319.36 22.68 303.47 866.36 275.11 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: DINING_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 163.29 0.00 163.29 215.76 289.12 0.00 0.00 0.00
February 193.28 0.00 193.28 312.40 232.08 0.00 0.00 0.00
March 230.56 0.00 230.56 370.95 178.70 0.00 0.00 0.00
April 259.03 1.48 257.55 513.06 85.84 0.00 0.00 0.00
May 294.14 12.05 282.09 698.87 19.96 0.00 0.00 0.00
June 315.27 22.68 292.60 816.59 4.02 0.00 0.00 0.00
July 319.36 15.90 303.47 848.63 9.29 0.00 0.00 0.00
August 282.83 2.96 279.86 750.60 3.72 0.00 0.00 0.00
September 250.44 0.06 250.38 693.60 16.87 0.00 0.00 0.00
October 209.71 0.00 209.71 530.25 28.81 0.00 0.00 0.00
November 182.34 0.00 182.34 380.14 115.43 0.00 0.00 0.00
December 161.51 0.00 161.51 241.60 237.36 0.00 0.00 0.00
                 
Annual Sum or Average 238.71 4.62 234.09 532.07 101.20 0.00 0.00 0.00
Minimum of Months 161.51 0.00 161.51 215.76 3.72 0.00 0.00 0.00
Maximum of Months 319.36 22.68 303.47 848.63 289.12 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: KITCHEN_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 23.33 0.00 23.33 31.26 44.78 0.00 0.00 0.00
February 27.61 0.00 27.61 43.51 37.55 0.00 0.00 0.00
March 32.94 0.00 32.94 51.98 29.41 0.00 0.00 0.00
April 37.01 0.21 36.79 73.49 14.96 0.00 0.00 0.00
May 42.02 1.72 40.30 101.26 4.48 0.00 0.00 0.00
June 45.04 3.24 41.80 119.30 1.08 0.00 0.00 0.00
July 45.63 2.27 43.35 126.00 2.00 0.00 0.00 0.00
August 40.41 0.42 39.98 108.35 1.23 0.00 0.00 0.00
September 35.78 0.01 35.77 101.29 2.98 0.00 0.00 0.00
October 29.96 0.00 29.96 75.95 5.50 0.00 0.00 0.00
November 26.05 0.00 26.05 54.45 18.75 0.00 0.00 0.00
December 23.07 0.00 23.07 35.45 36.79 0.00 0.00 0.00
                 
Annual Sum or Average 34.10 0.66 33.44 77.02 16.53 0.00 0.00 0.00
Minimum of Months 23.07 0.00 23.07 31.26 1.08 0.00 0.00 0.00
Maximum of Months 45.63 3.24 43.35 126.00 44.78 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: KITCHEN_FLR_6_WALL_EAST_WINDOW

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 209.74 100.51 109.23 328.42 158.60 0.00 0.00 0.00
February 243.28 113.02 130.26 398.58 132.41 0.00 0.00 0.00
March 296.35 140.11 156.24 482.37 102.03 0.00 0.00 0.00
April 322.01 143.75 178.26 593.51 56.69 0.00 0.00 0.00
May 304.66 121.80 182.86 626.36 17.13 0.00 0.00 0.00
June 299.42 114.92 184.51 667.07 4.12 0.00 0.00 0.00
July 308.07 111.17 196.90 710.13 7.54 0.00 0.00 0.00
August 281.59 94.28 187.31 631.77 4.79 0.00 0.00 0.00
September 271.28 97.96 173.32 622.86 11.27 0.00 0.00 0.00
October 249.41 107.04 142.37 526.95 20.82 0.00 0.00 0.00
November 203.09 80.88 122.21 388.01 66.70 0.00 0.00 0.00
December 164.25 58.20 106.06 268.65 132.99 0.00 0.00 0.00
                 
Annual Sum or Average 262.80 106.89 155.91 520.87 59.27 0.00 0.00 0.00
Minimum of Months 164.25 58.20 106.06 268.65 4.12 0.00 0.00 0.00
Maximum of Months 322.01 143.75 196.90 710.13 158.60 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 109.84 71.42 38.42 180.34 41.63 0.00 0.00 0.00
February 96.96 55.15 41.82 166.60 34.95 0.00 0.00 0.00
March 74.94 30.98 43.95 131.73 27.77 0.00 0.00 0.00
April 53.73 11.01 42.72 110.07 14.93 0.00 0.00 0.00
May 41.95 1.33 40.62 100.38 4.51 0.00 0.00 0.00
June 39.57 0.08 39.49 107.12 1.06 0.00 0.00 0.00
July 42.34 0.36 41.99 118.53 2.00 0.00 0.00 0.00
August 47.60 3.56 44.04 123.41 1.26 0.00 0.00 0.00
September 61.73 15.25 46.48 153.56 2.97 0.00 0.00 0.00
October 85.67 40.73 44.93 179.03 5.44 0.00 0.00 0.00
November 97.05 54.47 42.58 179.13 17.67 0.00 0.00 0.00
December 105.90 66.86 39.03 177.81 34.78 0.00 0.00 0.00
                 
Annual Sum or Average 71.32 29.15 42.17 143.86 15.66 0.00 0.00 0.00
Minimum of Months 39.57 0.08 38.42 100.38 1.06 0.00 0.00 0.00
Maximum of Months 109.84 71.42 46.48 180.34 41.63 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 29.54 0.00 29.54 41.69 44.04 0.00 0.00 0.00
February 34.97 0.00 34.97 60.72 32.98 0.00 0.00 0.00
March 41.71 0.00 41.71 72.29 23.22 0.00 0.00 0.00
April 46.86 0.27 46.60 99.01 8.04 0.00 0.00 0.00
May 53.22 2.18 51.04 136.69 1.27 0.00 0.00 0.00
June 57.04 4.10 52.94 156.99 0.10 0.00 0.00 0.00
July 57.78 2.88 54.91 159.89 0.54 0.00 0.00 0.00
August 51.17 0.54 50.63 144.77 0.02 0.00 0.00 0.00
September 45.31 0.01 45.30 130.92 0.68 0.00 0.00 0.00
October 37.94 0.00 37.94 102.09 1.97 0.00 0.00 0.00
November 32.99 0.00 32.99 74.42 14.97 0.00 0.00 0.00
December 29.22 0.00 29.22 46.81 34.74 0.00 0.00 0.00
                 
Annual Sum or Average 43.19 0.84 42.35 102.39 13.47 0.00 0.00 0.00
Minimum of Months 29.22 0.00 29.22 41.69 0.02 0.00 0.00 0.00
Maximum of Months 57.78 4.10 54.91 159.89 44.04 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 26.43 0.00 26.43 37.30 39.40 0.00 0.00 0.00
February 31.29 0.00 31.29 54.33 29.51 0.00 0.00 0.00
March 37.32 0.00 37.32 64.68 20.78 0.00 0.00 0.00
April 41.93 0.24 41.69 88.58 7.19 0.00 0.00 0.00
May 47.61 1.95 45.66 122.29 1.13 0.00 0.00 0.00
June 51.04 3.67 47.36 140.46 0.09 0.00 0.00 0.00
July 51.70 2.57 49.12 143.05 0.49 0.00 0.00 0.00
August 45.78 0.48 45.30 129.52 0.02 0.00 0.00 0.00
September 40.54 0.01 40.53 117.13 0.61 0.00 0.00 0.00
October 33.95 0.00 33.95 91.34 1.77 0.00 0.00 0.00
November 29.52 0.00 29.52 66.58 13.39 0.00 0.00 0.00
December 26.14 0.00 26.14 41.88 31.08 0.00 0.00 0.00
                 
Annual Sum or Average 38.64 0.75 37.89 91.61 12.05 0.00 0.00 0.00
Minimum of Months 26.14 0.00 26.14 37.30 0.02 0.00 0.00 0.00
Maximum of Months 51.70 3.67 49.12 143.05 39.40 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 410.06 266.64 143.43 673.16 119.75 0.00 0.00 0.00
February 362.00 205.88 156.12 631.04 90.61 0.00 0.00 0.00
March 279.76 115.66 164.10 507.18 64.31 0.00 0.00 0.00
April 200.59 41.09 159.50 425.64 24.28 0.00 0.00 0.00
May 156.62 4.97 151.65 405.48 3.86 0.00 0.00 0.00
June 147.73 0.31 147.43 419.00 0.29 0.00 0.00 0.00
July 158.08 1.33 156.75 445.31 1.60 0.00 0.00 0.00
August 177.71 13.29 164.42 485.09 0.07 0.00 0.00 0.00
September 230.45 56.93 173.52 577.94 1.96 0.00 0.00 0.00
October 319.83 152.07 167.75 680.75 5.83 0.00 0.00 0.00
November 362.32 203.35 158.97 677.52 41.47 0.00 0.00 0.00
December 395.35 249.63 145.72 663.11 97.08 0.00 0.00 0.00
                 
Annual Sum or Average 266.27 108.84 157.43 548.86 37.38 0.00 0.00 0.00
Minimum of Months 147.73 0.31 143.43 405.48 0.07 0.00 0.00 0.00
Maximum of Months 410.06 266.64 173.52 680.75 119.75 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyReportMonthly

For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.148795E+10 0.967519E+09 0.520433E+09 0.241075E+10 0.446551E+09
February 0.118642E+10 0.674762E+09 0.511657E+09 0.204261E+10 0.314857E+09
March 0.101513E+10 0.419697E+09 0.595431E+09 0.181890E+10 0.254480E+09
April 0.704385E+09 0.144292E+09 0.560093E+09 0.145629E+10 0.104798E+09
May 0.568300E+09 18039893.06 0.550260E+09 0.140390E+10 17567904.18
June 0.518766E+09 1079877.92 0.517686E+09 0.142259E+10 946029.98
July 0.573595E+09 4816469.25 0.568779E+09 0.156796E+10 6150496.22
August 0.644834E+09 48222350.38 0.596611E+09 0.169363E+10 352411.32
September 0.809229E+09 0.199919E+09 0.609311E+09 0.195495E+10 9773733.42
October 0.116052E+10 0.551817E+09 0.608706E+09 0.237380E+10 32465453.46
November 0.127230E+10 0.714056E+09 0.558244E+09 0.230998E+10 0.161993E+09
December 0.143456E+10 0.905795E+09 0.528761E+09 0.237253E+10 0.365284E+09
           
Annual Sum or Average 0.113760E+11 0.465001E+10 0.672597E+10 0.228279E+11 0.171522E+10
Minimum of Months 0.518766E+09 1079877.92 0.511657E+09 0.140390E+10 352411.32
Maximum of Months 0.148795E+10 0.967519E+09 0.609311E+09 0.241075E+10 0.446551E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CAFE_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.418997E+10 0.272447E+10 0.146550E+10 0.675656E+10 0.133968E+10
February 0.334088E+10 0.190008E+10 0.144079E+10 0.571985E+10 0.961590E+09
March 0.285853E+10 0.118184E+10 0.167669E+10 0.508332E+10 0.807559E+09
April 0.198350E+10 0.406316E+09 0.157718E+10 0.406453E+10 0.370384E+09
May 0.160030E+10 50799149.42 0.154950E+10 0.385386E+10 77208674.60
June 0.146081E+10 3040865.03 0.145777E+10 0.389448E+10 10063266.45
July 0.161521E+10 13562859.83 0.160164E+10 0.434896E+10 32617060.45
August 0.181581E+10 0.135791E+09 0.168002E+10 0.467016E+10 6911631.55
September 0.227874E+10 0.562957E+09 0.171578E+10 0.547023E+10 64293223.72
October 0.326796E+10 0.155388E+10 0.171408E+10 0.664567E+10 0.146700E+09
November 0.358271E+10 0.201074E+10 0.157198E+10 0.646028E+10 0.521859E+09
December 0.403962E+10 0.255066E+10 0.148896E+10 0.665514E+10 0.111208E+10
           
Annual Sum or Average 0.320340E+11 0.130941E+11 0.189399E+11 0.636230E+11 0.545095E+10
Minimum of Months 0.146081E+10 3040865.03 0.144079E+10 0.385386E+10 6911631.55
Maximum of Months 0.418997E+10 0.272447E+10 0.171578E+10 0.675656E+10 0.133968E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: LOBBY_FLR_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.544302E+10 0.353924E+10 0.190377E+10 0.905625E+10 0.170334E+10
February 0.433999E+10 0.246832E+10 0.187167E+10 0.767614E+10 0.120946E+10
March 0.371340E+10 0.153528E+10 0.217812E+10 0.682837E+10 0.101236E+10
April 0.257668E+10 0.527828E+09 0.204885E+10 0.547866E+10 0.447140E+09
May 0.207888E+10 65990986.10 0.201288E+10 0.522239E+10 88357129.81
June 0.189768E+10 3950256.73 0.189373E+10 0.528916E+10 10287770.09
July 0.209825E+10 17618926.79 0.208063E+10 0.589857E+10 36202971.73
August 0.235884E+10 0.176400E+09 0.218244E+10 0.635362E+10 5163901.75
September 0.296021E+10 0.731314E+09 0.222890E+10 0.743417E+10 63452857.53
October 0.424526E+10 0.201858E+10 0.222668E+10 0.902096E+10 0.142985E+09
November 0.465415E+10 0.261206E+10 0.204209E+10 0.872759E+10 0.638017E+09
December 0.524769E+10 0.331345E+10 0.193424E+10 0.892929E+10 0.140142E+10
           
Annual Sum or Average 0.416140E+11 0.170100E+11 0.246040E+11 0.859152E+11 0.675819E+10
Minimum of Months 0.189768E+10 3950256.73 0.187167E+10 0.522239E+10 5163901.75
Maximum of Months 0.544302E+10 0.353924E+10 0.222890E+10 0.905625E+10 0.170334E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.294194E+09 0.191295E+09 0.102899E+09 0.473240E+09 90331948.15
February 0.234576E+09 0.133412E+09 0.101164E+09 0.397844E+09 63531545.29
March 0.200709E+09 82981349.66 0.117728E+09 0.348447E+09 51235444.46
April 0.139270E+09 28528948.73 0.110741E+09 0.276958E+09 21152943.78
May 0.112364E+09 3566796.69 0.108797E+09 0.270377E+09 3458999.56
June 0.102570E+09 213510.41 0.102357E+09 0.277296E+09 233247.64
July 0.113411E+09 952298.69 0.112459E+09 0.307244E+09 1216116.21
August 0.127496E+09 9534386.88 0.117961E+09 0.332259E+09 88558.66
September 0.160000E+09 39527329.16 0.120472E+09 0.388847E+09 1759980.12
October 0.229456E+09 0.109104E+09 0.120353E+09 0.471669E+09 5220867.51
November 0.251556E+09 0.141181E+09 0.110375E+09 0.455696E+09 31548798.16
December 0.283637E+09 0.179091E+09 0.104546E+09 0.465205E+09 73416414.06
           
Annual Sum or Average 0.224924E+10 0.919388E+09 0.132985E+10 0.446508E+10 0.343195E+09
Minimum of Months 0.102570E+09 213510.41 0.101164E+09 0.270377E+09 88558.66
Maximum of Months 0.294194E+09 0.191295E+09 0.120472E+09 0.473240E+09 90331948.15



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_1_FLR_3_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.253088E+09 0.109438E+09 0.143650E+09 0.381933E+09 0.180310E+09
February 0.286903E+09 0.130669E+09 0.156234E+09 0.472253E+09 0.126362E+09
March 0.393465E+09 0.179864E+09 0.213602E+09 0.647263E+09 0.100336E+09
April 0.417943E+09 0.193256E+09 0.224687E+09 0.756246E+09 39054260.14
May 0.394988E+09 0.152497E+09 0.242491E+09 0.819569E+09 6444345.39
June 0.323637E+09 90811701.15 0.232825E+09 0.752924E+09 451753.14
July 0.373167E+09 0.115324E+09 0.257843E+09 0.861408E+09 2295073.37
August 0.372297E+09 0.121012E+09 0.251286E+09 0.840235E+09 145825.19
September 0.307449E+09 90604734.42 0.216844E+09 0.712762E+09 3441109.48
October 0.316622E+09 0.123668E+09 0.192954E+09 0.660173E+09 9935247.20
November 0.252061E+09 92323391.94 0.159737E+09 0.475454E+09 62918195.90
December 0.261142E+09 0.116710E+09 0.144432E+09 0.417135E+09 0.142687E+09
           
Annual Sum or Average 0.395276E+10 0.151618E+10 0.243658E+10 0.779735E+10 0.674381E+09
Minimum of Months 0.252061E+09 90604734.42 0.143650E+09 0.381933E+09 145825.19
Maximum of Months 0.417943E+09 0.193256E+09 0.257843E+09 0.861408E+09 0.180310E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_2_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 62480615.07 0.00 62480615.07 83353513.14 94395632.35
February 66798791.70 0.00 66798791.70 0.106943E+09 65821070.46
March 88222215.26 1556.86 88220658.39 0.138951E+09 52999676.95
April 95917903.38 547620.98 95370282.40 0.184026E+09 20336796.98
May 0.112552E+09 4610857.06 0.107941E+09 0.269030E+09 3335095.82
June 0.116746E+09 8396627.57 0.108349E+09 0.307562E+09 262878.22
July 0.122202E+09 6082373.67 0.116120E+09 0.325706E+09 1256702.79
August 0.108221E+09 1134477.74 0.107087E+09 0.290777E+09 93672.07
September 92738767.59 21425.30 92717342.29 0.255917E+09 1775790.52
October 80243081.80 0.00 80243081.80 0.200492E+09 4915136.08
November 67521071.96 0.00 67521071.96 0.140105E+09 32378272.10
December 61801109.67 0.00 61801109.67 92609106.78 74504895.29
           
Annual Sum or Average 0.107544E+10 20794939.18 0.105465E+10 0.239547E+10 0.352076E+09
Minimum of Months 61801109.67 0.00 61801109.67 83353513.14 93672.07
Maximum of Months 0.122202E+09 8396627.57 0.116120E+09 0.325706E+09 94395632.35



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_2_FLR_3_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.253088E+09 0.109438E+09 0.143650E+09 0.395418E+09 0.173210E+09
February 0.286903E+09 0.130669E+09 0.156234E+09 0.481927E+09 0.121833E+09
March 0.393465E+09 0.179864E+09 0.213602E+09 0.654868E+09 97253999.05
April 0.417943E+09 0.193256E+09 0.224687E+09 0.759258E+09 38069084.99
May 0.394988E+09 0.152497E+09 0.242491E+09 0.819582E+09 6416686.18
June 0.323637E+09 90811701.15 0.232825E+09 0.751798E+09 463963.68
July 0.373167E+09 0.115324E+09 0.257843E+09 0.860729E+09 2315432.50
August 0.372297E+09 0.121012E+09 0.251286E+09 0.841683E+09 138430.19
September 0.307449E+09 90604734.42 0.216844E+09 0.717244E+09 3199768.86
October 0.316622E+09 0.123668E+09 0.192954E+09 0.668822E+09 9018727.03
November 0.252061E+09 92323391.94 0.159737E+09 0.485700E+09 60331170.85
December 0.261142E+09 0.116710E+09 0.144432E+09 0.429329E+09 0.136564E+09
           
Annual Sum or Average 0.395276E+10 0.151618E+10 0.243658E+10 0.786636E+10 0.648814E+09
Minimum of Months 0.252061E+09 90604734.42 0.143650E+09 0.395418E+09 138430.19
Maximum of Months 0.417943E+09 0.193256E+09 0.257843E+09 0.860729E+09 0.173210E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.235309E+09 0.153006E+09 82302997.65 0.364894E+09 97781420.27
February 0.187624E+09 0.106708E+09 80915277.26 0.306094E+09 71368267.21
March 0.160536E+09 66371880.15 94163689.54 0.266707E+09 61608765.86
April 0.111394E+09 22818620.98 88575365.15 0.211829E+09 32649015.10
May 89873280.16 2852869.99 87020410.17 0.197460E+09 8688711.61
June 82039774.92 170774.37 81869000.56 0.200536E+09 2157193.81
July 90710703.00 761687.47 89949015.53 0.227211E+09 4296855.71
August 0.101976E+09 7625992.90 94350425.71 0.243551E+09 2124044.25
September 0.127974E+09 31615575.84 96358645.11 0.293281E+09 7825112.03
October 0.183529E+09 87265587.65 96262912.52 0.359144E+09 13718865.81
November 0.201205E+09 0.112922E+09 88282536.13 0.347580E+09 40049532.75
December 0.226865E+09 0.143244E+09 83620064.08 0.359650E+09 83522498.42
           
Annual Sum or Average 0.179903E+10 0.735364E+09 0.106367E+10 0.337794E+10 0.425790E+09
Minimum of Months 82039774.92 170774.37 80915277.26 0.197460E+09 2124044.25
Maximum of Months 0.235309E+09 0.153006E+09 96358645.11 0.364894E+09 97781420.27



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 49991117.79 0.00 49991117.79 70096559.15 75202368.82
February 53446117.01 0.00 53446117.01 90902765.60 51314685.63
March 70587127.69 1245.66 70585882.03 0.119161E+09 39921099.57
April 76744494.28 438154.86 76306339.42 0.157946E+09 13385655.68
May 90053455.50 3689174.61 86364280.90 0.228712E+09 2172375.97
June 93409270.91 6718192.47 86691078.44 0.258974E+09 101216.01
July 97774596.35 4866543.94 92908052.41 0.274848E+09 625017.25
August 86588371.69 907702.50 85680669.19 0.247303E+09 23584.37
September 74200848.51 17142.51 74183706.00 0.217517E+09 764947.25
October 64202974.78 0.00 64202974.78 0.172662E+09 2845975.84
November 54024017.81 0.00 54024017.81 0.120097E+09 24805621.58
December 49447441.40 0.00 49447441.40 78507998.05 58962788.38
           
Annual Sum or Average 0.860470E+09 16638156.53 0.843832E+09 0.203673E+10 0.270125E+09
Minimum of Months 49447441.40 0.00 49447441.40 70096559.15 23584.37
Maximum of Months 97774596.35 6718192.47 92908052.41 0.274848E+09 75202368.82



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_5_FLR_3_WALL_EAST_WINDOW

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.280909E+09 0.134618E+09 0.146291E+09 0.420244E+09 0.171597E+09
February 0.294295E+09 0.136722E+09 0.157574E+09 0.473759E+09 0.116412E+09
March 0.396895E+09 0.187649E+09 0.209246E+09 0.636690E+09 89169432.79
April 0.417353E+09 0.186314E+09 0.231039E+09 0.755363E+09 36403903.04
May 0.408027E+09 0.163129E+09 0.244897E+09 0.843787E+09 5913879.06
June 0.388079E+09 0.148941E+09 0.239138E+09 0.864554E+09 487278.71
July 0.412596E+09 0.148889E+09 0.263707E+09 0.932074E+09 2159813.83
August 0.377126E+09 0.126265E+09 0.250860E+09 0.852187E+09 133297.54
September 0.351604E+09 0.126961E+09 0.224643E+09 0.791399E+09 3275797.64
October 0.334034E+09 0.143355E+09 0.190679E+09 0.693098E+09 9408143.66
November 0.263220E+09 0.104823E+09 0.158397E+09 0.489726E+09 58079501.06
December 0.219983E+09 77942147.70 0.142041E+09 0.343926E+09 0.137882E+09
           
Annual Sum or Average 0.414412E+10 0.168561E+10 0.245851E+10 0.809681E+10 0.630921E+09
Minimum of Months 0.219983E+09 77942147.70 0.142041E+09 0.343926E+09 133297.54
Maximum of Months 0.417353E+09 0.187649E+09 0.263707E+09 0.932074E+09 0.171597E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.294194E+09 0.191295E+09 0.102899E+09 0.470645E+09 89905644.49
February 0.234576E+09 0.133412E+09 0.101164E+09 0.395876E+09 62749023.58
March 0.200709E+09 82981349.66 0.117728E+09 0.345788E+09 50106247.87
April 0.139270E+09 28528948.73 0.110741E+09 0.275254E+09 20171580.07
May 0.112364E+09 3566796.69 0.108797E+09 0.269599E+09 3339281.08
June 0.102570E+09 213510.41 0.102357E+09 0.274957E+09 266580.95
July 0.113411E+09 952298.69 0.112459E+09 0.305739E+09 1200703.83
August 0.127496E+09 9534386.88 0.117961E+09 0.331864E+09 70233.10
September 0.160000E+09 39527329.16 0.120472E+09 0.387201E+09 1790989.98
October 0.229456E+09 0.109104E+09 0.120353E+09 0.470673E+09 5047820.50
November 0.251556E+09 0.141181E+09 0.110375E+09 0.454503E+09 31174310.44
December 0.283637E+09 0.179091E+09 0.104546E+09 0.465092E+09 72229486.53
           
Annual Sum or Average 0.224924E+10 0.919388E+09 0.132985E+10 0.444719E+10 0.338052E+09
Minimum of Months 0.102570E+09 213510.41 0.101164E+09 0.269599E+09 70233.10
Maximum of Months 0.294194E+09 0.191295E+09 0.120472E+09 0.470673E+09 89905644.49



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_6_FLR_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 62480615.07 0.00 62480615.07 80607098.80 94134476.34
February 66798791.70 0.00 66798791.70 0.104708E+09 65337330.38
March 88222215.26 1556.86 88220658.39 0.136402E+09 52410266.70
April 95917903.38 547620.98 95370282.40 0.182187E+09 19396620.02
May 0.112552E+09 4610857.06 0.107941E+09 0.268227E+09 3213432.32
June 0.116746E+09 8396627.57 0.108349E+09 0.305249E+09 297890.60
July 0.122202E+09 6082373.67 0.116120E+09 0.324203E+09 1241601.87
August 0.108221E+09 1134477.74 0.107087E+09 0.290351E+09 74814.01
September 92738767.59 21425.30 92717342.29 0.254107E+09 1809417.12
October 80243081.80 0.00 80243081.80 0.199229E+09 4764910.06
November 67521071.96 0.00 67521071.96 0.138690E+09 32072638.26
December 61801109.67 0.00 61801109.67 92304065.71 73051565.52
           
Annual Sum or Average 0.107544E+10 20794939.18 0.105465E+10 0.237626E+10 0.347805E+09
Minimum of Months 61801109.67 0.00 61801109.67 80607098.80 74814.01
Maximum of Months 0.122202E+09 8396627.57 0.116120E+09 0.324203E+09 94134476.34



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_6_FLR_3_WALL_EAST_WINDOW

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.280909E+09 0.134618E+09 0.146291E+09 0.432863E+09 0.164157E+09
February 0.294295E+09 0.136722E+09 0.157574E+09 0.482772E+09 0.112007E+09
March 0.396895E+09 0.187649E+09 0.209246E+09 0.643814E+09 86206410.02
April 0.417353E+09 0.186314E+09 0.231039E+09 0.758218E+09 35453017.04
May 0.408027E+09 0.163129E+09 0.244897E+09 0.843845E+09 5890151.35
June 0.388079E+09 0.148941E+09 0.239138E+09 0.863529E+09 499276.96
July 0.412596E+09 0.148889E+09 0.263707E+09 0.931450E+09 2179037.58
August 0.377126E+09 0.126265E+09 0.250860E+09 0.853633E+09 126574.38
September 0.351604E+09 0.126961E+09 0.224643E+09 0.795720E+09 3046783.46
October 0.334034E+09 0.143355E+09 0.190679E+09 0.701463E+09 8561586.58
November 0.263220E+09 0.104823E+09 0.158397E+09 0.499736E+09 55597790.62
December 0.219983E+09 77942147.70 0.142041E+09 0.355994E+09 0.131001E+09
           
Annual Sum or Average 0.414412E+10 0.168561E+10 0.245851E+10 0.816304E+10 0.604726E+09
Minimum of Months 0.219983E+09 77942147.70 0.142041E+09 0.355994E+09 126574.38
Maximum of Months 0.417353E+09 0.187649E+09 0.263707E+09 0.931450E+09 0.164157E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 79127756.68 0.00 79127756.68 0.114236E+09 0.120113E+09
February 84596454.92 0.00 84596454.92 0.148636E+09 82135808.66
March 0.111728E+09 1971.67 0.111726E+09 0.194832E+09 65034177.94
April 0.121474E+09 693527.42 0.120780E+09 0.255189E+09 24872669.40
May 0.142540E+09 5839359.54 0.136701E+09 0.362744E+09 4243454.09
June 0.147852E+09 10633799.02 0.137218E+09 0.405180E+09 561955.84
July 0.154761E+09 7702942.47 0.147058E+09 0.428459E+09 2031783.69
August 0.137055E+09 1436744.47 0.135618E+09 0.383481E+09 206807.41
September 0.117448E+09 27133.79 0.117421E+09 0.336208E+09 3511661.13
October 0.101623E+09 0.00 0.101623E+09 0.265351E+09 8247096.82
November 85511177.30 0.00 85511177.30 0.189122E+09 43159581.47
December 78267205.96 0.00 78267205.96 0.127111E+09 95095569.61
           
Annual Sum or Average 0.136198E+10 26335478.38 0.133565E+10 0.321055E+10 0.449213E+09
Minimum of Months 78267205.96 0.00 78267205.96 0.114236E+09 206807.41
Maximum of Months 0.154761E+09 10633799.02 0.147058E+09 0.428459E+09 0.120113E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 29169767.54 0.00 29169767.54 42112190.11 44278503.40
February 31185756.15 0.00 31185756.15 54793321.74 30278660.05
March 41187518.84 726.84 41186792.00 71823038.55 23974290.84
April 44780336.12 255662.92 44524673.20 94073240.15 9169095.84
May 52546101.77 2152629.72 50393472.05 0.133722E+09 1564312.89
June 54504216.72 3920058.63 50584158.09 0.149366E+09 207160.19
July 57051379.78 2839623.55 54211756.23 0.157948E+09 748999.60
August 50524228.81 529643.50 49994585.30 0.141367E+09 76237.78
September 43296121.35 10002.64 43286118.71 0.123940E+09 1294543.70
October 37462371.96 0.00 37462371.96 97819367.83 3040488.84
November 31522960.69 0.00 31522960.69 69718213.95 15910408.83
December 28852532.91 0.00 28852532.91 46858204.40 35056164.55
           
Annual Sum or Average 0.502083E+09 9708347.80 0.492375E+09 0.118354E+10 0.165599E+09
Minimum of Months 28852532.91 0.00 28852532.91 42112190.11 76237.78
Maximum of Months 57051379.78 3920058.63 54211756.23 0.157948E+09 44278503.40



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.137270E+09 89257568.62 48012355.27 0.227758E+09 40865379.26
February 0.109452E+09 62249486.00 47202813.38 0.192829E+09 28193786.10
March 93650183.18 38718763.36 54931419.82 0.171335E+09 22511829.19
April 64982902.08 13311492.51 51671409.57 0.137991E+09 9296487.82
May 52428562.51 1664252.96 50764309.54 0.134417E+09 1619139.26
June 47858801.41 99623.10 47759178.32 0.134950E+09 194114.29
July 52917082.30 444338.73 52472743.56 0.149142E+09 734759.78
August 59489060.90 4448706.50 55040354.41 0.160998E+09 68371.56
September 74655163.70 18443292.50 56211871.19 0.186784E+09 1228912.51
October 0.107063E+09 50907336.51 56156024.54 0.226116E+09 2962841.48
November 0.117375E+09 65874561.67 51500584.55 0.219341E+09 14870094.92
December 0.132344E+09 83563227.84 48780680.41 0.224075E+09 33233200.75
           
Annual Sum or Average 0.104949E+10 0.428983E+09 0.620504E+09 0.216574E+10 0.155779E+09
Minimum of Months 47858801.41 99623.10 47202813.38 0.134417E+09 68371.56
Maximum of Months 0.137270E+09 89257568.62 56211871.19 0.227758E+09 40865379.26



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.372579E+09 0.242263E+09 0.130315E+09 0.618183E+09 0.110917E+09
February 0.297076E+09 0.168958E+09 0.128118E+09 0.523378E+09 76523702.38
March 0.254186E+09 0.105091E+09 0.149095E+09 0.465039E+09 61101709.10
April 0.176377E+09 36130113.49 0.140247E+09 0.374535E+09 25232569.50
May 0.142302E+09 4517122.96 0.137785E+09 0.364835E+09 4394675.14
June 0.129899E+09 270397.47 0.129628E+09 0.366283E+09 526865.90
July 0.143628E+09 1206026.21 0.142422E+09 0.404801E+09 1994288.33
August 0.161465E+09 12074699.40 0.149391E+09 0.436981E+09 185574.39
September 0.202629E+09 50058868.35 0.152571E+09 0.506970E+09 3335519.92
October 0.290592E+09 0.138173E+09 0.152419E+09 0.613724E+09 8041757.82
November 0.318580E+09 0.178797E+09 0.139783E+09 0.595337E+09 40360479.21
December 0.359208E+09 0.226808E+09 0.132401E+09 0.608184E+09 90201704.54
           
Annual Sum or Average 0.284852E+10 0.116435E+10 0.168417E+10 0.587825E+10 0.422816E+09
Minimum of Months 0.129899E+09 270397.47 0.128118E+09 0.364835E+09 185574.39
Maximum of Months 0.372579E+09 0.242263E+09 0.152571E+09 0.618183E+09 0.110917E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.294194E+09 0.191295E+09 0.102899E+09 0.467663E+09 89846749.14
February 0.234576E+09 0.133412E+09 0.101164E+09 0.392179E+09 63327843.94
March 0.200709E+09 82981349.66 0.117728E+09 0.342150E+09 50972816.35
April 0.139270E+09 28528948.73 0.110741E+09 0.271406E+09 21058087.15
May 0.112364E+09 3566796.69 0.108797E+09 0.266005E+09 3333997.90
June 0.102570E+09 213510.41 0.102357E+09 0.273311E+09 214550.75
July 0.113411E+09 952298.69 0.112459E+09 0.302772E+09 1159100.62
August 0.127496E+09 9534386.88 0.117961E+09 0.327865E+09 112104.45
September 0.160000E+09 39527329.16 0.120472E+09 0.383895E+09 1657652.23
October 0.229456E+09 0.109104E+09 0.120353E+09 0.466380E+09 4969377.62
November 0.251556E+09 0.141181E+09 0.110375E+09 0.450218E+09 31055822.78
December 0.283637E+09 0.179091E+09 0.104546E+09 0.459343E+09 73115363.13
           
Annual Sum or Average 0.224924E+10 0.919388E+09 0.132985E+10 0.440319E+10 0.340823E+09
Minimum of Months 0.102570E+09 213510.41 0.101164E+09 0.266005E+09 112104.45
Maximum of Months 0.294194E+09 0.191295E+09 0.120472E+09 0.467663E+09 89846749.14



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_1_FLR_6_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.253088E+09 0.109438E+09 0.143650E+09 0.374898E+09 0.179261E+09
February 0.286903E+09 0.130669E+09 0.156234E+09 0.464376E+09 0.125987E+09
March 0.393465E+09 0.179864E+09 0.213602E+09 0.636102E+09 0.100112E+09
April 0.417943E+09 0.193256E+09 0.224687E+09 0.744440E+09 38953862.22
May 0.394988E+09 0.152497E+09 0.242491E+09 0.807866E+09 6203636.65
June 0.323637E+09 90811701.15 0.232825E+09 0.742643E+09 403730.02
July 0.373167E+09 0.115324E+09 0.257843E+09 0.850369E+09 2162046.95
August 0.372297E+09 0.121012E+09 0.251286E+09 0.829637E+09 171958.09
September 0.307449E+09 90604734.42 0.216844E+09 0.703615E+09 3165429.18
October 0.316622E+09 0.123668E+09 0.192954E+09 0.652284E+09 9341823.79
November 0.252061E+09 92323391.94 0.159737E+09 0.468173E+09 61882950.56
December 0.261142E+09 0.116710E+09 0.144432E+09 0.409629E+09 0.142252E+09
           
Annual Sum or Average 0.395276E+10 0.151618E+10 0.243658E+10 0.768403E+10 0.669897E+09
Minimum of Months 0.252061E+09 90604734.42 0.143650E+09 0.374898E+09 171958.09
Maximum of Months 0.417943E+09 0.193256E+09 0.257843E+09 0.850369E+09 0.179261E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_2_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 62480615.07 0.00 62480615.07 81198848.78 93674146.48
February 66798791.70 0.00 66798791.70 0.104347E+09 65515194.11
March 88222215.26 1556.86 88220658.39 0.135136E+09 52775461.88
April 95917903.38 547620.98 95370282.40 0.179582E+09 20206553.55
May 0.112552E+09 4610857.06 0.107941E+09 0.264275E+09 3232495.95
June 0.116746E+09 8396627.57 0.108349E+09 0.302982E+09 238421.65
July 0.122202E+09 6082373.67 0.116120E+09 0.321000E+09 1190564.95
August 0.108221E+09 1134477.74 0.107087E+09 0.286627E+09 111134.51
September 92738767.59 21425.30 92717342.29 0.252443E+09 1630732.51
October 80243081.80 0.00 80243081.80 0.197955E+09 4582105.24
November 67521071.96 0.00 67521071.96 0.137669E+09 31747538.82
December 61801109.67 0.00 61801109.67 90300527.86 74044717.66
           
Annual Sum or Average 0.107544E+10 20794939.18 0.105465E+10 0.235352E+10 0.348949E+09
Minimum of Months 61801109.67 0.00 61801109.67 81198848.78 111134.51
Maximum of Months 0.122202E+09 8396627.57 0.116120E+09 0.321000E+09 93674146.48



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_2_FLR_6_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.253088E+09 0.109438E+09 0.143650E+09 0.388812E+09 0.171614E+09
February 0.286903E+09 0.130669E+09 0.156234E+09 0.474204E+09 0.121271E+09
March 0.393465E+09 0.179864E+09 0.213602E+09 0.643737E+09 96924184.15
April 0.417943E+09 0.193256E+09 0.224687E+09 0.747374E+09 37976462.59
May 0.394988E+09 0.152497E+09 0.242491E+09 0.807844E+09 6179184.79
June 0.323637E+09 90811701.15 0.232825E+09 0.741520E+09 415184.65
July 0.373167E+09 0.115324E+09 0.257843E+09 0.849679E+09 2183602.33
August 0.372297E+09 0.121012E+09 0.251286E+09 0.831051E+09 163503.78
September 0.307449E+09 90604734.42 0.216844E+09 0.708104E+09 2929320.01
October 0.316622E+09 0.123668E+09 0.192954E+09 0.661067E+09 8434240.86
November 0.252061E+09 92323391.94 0.159737E+09 0.478647E+09 59175041.66
December 0.261142E+09 0.116710E+09 0.144432E+09 0.422335E+09 0.135556E+09
           
Annual Sum or Average 0.395276E+10 0.151618E+10 0.243658E+10 0.775437E+10 0.642822E+09
Minimum of Months 0.252061E+09 90604734.42 0.143650E+09 0.388812E+09 163503.78
Maximum of Months 0.417943E+09 0.193256E+09 0.257843E+09 0.849679E+09 0.171614E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.431464E+09 0.280553E+09 0.150912E+09 0.677617E+09 0.136810E+09
February 0.344028E+09 0.195661E+09 0.148367E+09 0.571508E+09 94577921.33
March 0.294360E+09 0.121700E+09 0.172659E+09 0.503411E+09 73187636.59
April 0.204253E+09 41840441.24 0.162413E+09 0.407427E+09 27170169.58
May 0.164793E+09 5231049.65 0.159561E+09 0.406323E+09 4198012.81
June 0.150429E+09 313133.51 0.150116E+09 0.415983E+09 202273.58
July 0.166328E+09 1396637.42 0.164931E+09 0.460971E+09 1268640.48
August 0.186985E+09 13983093.38 0.173002E+09 0.496103E+09 60393.46
September 0.234655E+09 57970621.67 0.176684E+09 0.572119E+09 1862908.71
October 0.336520E+09 0.160011E+09 0.176509E+09 0.687831E+09 6766448.79
November 0.368931E+09 0.207056E+09 0.161876E+09 0.657776E+09 46576805.56
December 0.415981E+09 0.262654E+09 0.153327E+09 0.667492E+09 0.111524E+09
           
Annual Sum or Average 0.329873E+10 0.134837E+10 0.195036E+10 0.652456E+10 0.504205E+09
Minimum of Months 0.150429E+09 313133.51 0.148367E+09 0.406323E+09 60393.46
Maximum of Months 0.431464E+09 0.280553E+09 0.176684E+09 0.687831E+09 0.136810E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: BANQUET_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.437348E+09 0.00 0.437348E+09 0.598611E+09 0.736856E+09
February 0.467574E+09 0.00 0.467574E+09 0.779193E+09 0.528952E+09
March 0.617532E+09 10897.63 0.617521E+09 0.102416E+10 0.445633E+09
April 0.671400E+09 3833201.69 0.667567E+09 0.136484E+10 0.196658E+09
May 0.787833E+09 32274777.04 0.755559E+09 0.192233E+10 43008478.21
June 0.817192E+09 58774166.93 0.758418E+09 0.216805E+10 7482274.71
July 0.855382E+09 42575003.16 0.812807E+09 0.232045E+10 20120539.56
August 0.757519E+09 7941043.40 0.749578E+09 0.206294E+10 6743098.86
September 0.649147E+09 149971.41 0.648997E+09 0.184015E+10 34600113.66
October 0.561680E+09 0.00 0.561680E+09 0.146381E+10 64657980.60
November 0.472630E+09 0.00 0.472630E+09 0.102167E+10 0.278102E+09
December 0.432591E+09 0.00 0.432591E+09 0.670504E+09 0.600315E+09
           
Annual Sum or Average 0.752783E+10 0.145559E+09 0.738227E+10 0.172367E+11 0.296313E+10
Minimum of Months 0.432591E+09 0.00 0.432591E+09 0.598611E+09 6743098.86
Maximum of Months 0.855382E+09 58774166.93 0.812807E+09 0.232045E+10 0.736856E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: DINING_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.437348E+09 0.00 0.437348E+09 0.577903E+09 0.774388E+09
February 0.467574E+09 0.00 0.467574E+09 0.755748E+09 0.561450E+09
March 0.617532E+09 10897.63 0.617521E+09 0.993551E+09 0.478621E+09
April 0.671400E+09 3833201.69 0.667567E+09 0.132984E+10 0.222497E+09
May 0.787833E+09 32274777.04 0.755559E+09 0.187185E+10 53467106.42
June 0.817192E+09 58774166.93 0.758418E+09 0.211660E+10 10428410.16
July 0.855382E+09 42575003.16 0.812807E+09 0.227297E+10 24895277.58
August 0.757519E+09 7941043.40 0.749578E+09 0.201041E+10 9976421.44
September 0.649147E+09 149971.41 0.648997E+09 0.179782E+10 43715557.27
October 0.561680E+09 0.00 0.561680E+09 0.142021E+10 77175912.54
November 0.472630E+09 0.00 0.472630E+09 0.985321E+09 0.299191E+09
December 0.432591E+09 0.00 0.432591E+09 0.647096E+09 0.635738E+09
           
Annual Sum or Average 0.752783E+10 0.145559E+09 0.738227E+10 0.167793E+11 0.319154E+10
Minimum of Months 0.432591E+09 0.00 0.432591E+09 0.577903E+09 9976421.44
Maximum of Months 0.855382E+09 58774166.93 0.812807E+09 0.227297E+10 0.774388E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: KITCHEN_FLR_6_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 62480615.07 0.00 62480615.07 83734277.71 0.119950E+09
February 66798791.70 0.00 66798791.70 0.105254E+09 90848039.60
March 88222215.26 1556.86 88220658.39 0.139229E+09 78779164.76
April 95917903.38 547620.98 95370282.40 0.190479E+09 38772206.80
May 0.112552E+09 4610857.06 0.107941E+09 0.271216E+09 11992946.81
June 0.116746E+09 8396627.57 0.108349E+09 0.309213E+09 2809668.57
July 0.122202E+09 6082373.67 0.116120E+09 0.337487E+09 5349463.54
August 0.108221E+09 1134477.74 0.107087E+09 0.290211E+09 3301889.66
September 92738767.59 21425.30 92717342.29 0.262549E+09 7730764.71
October 80243081.80 0.00 80243081.80 0.203415E+09 14736914.35
November 67521071.96 0.00 67521071.96 0.141128E+09 48589819.13
December 61801109.67 0.00 61801109.67 94946716.17 98530075.19
           
Annual Sum or Average 0.107544E+10 20794939.18 0.105465E+10 0.242886E+10 0.521391E+09
Minimum of Months 61801109.67 0.00 61801109.67 83734277.71 2809668.57
Maximum of Months 0.122202E+09 8396627.57 0.116120E+09 0.337487E+09 0.119950E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: KITCHEN_FLR_6_WALL_EAST_WINDOW

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.561778E+09 0.269218E+09 0.292561E+09 0.879643E+09 0.424799E+09
February 0.588549E+09 0.273424E+09 0.315125E+09 0.964245E+09 0.320325E+09
March 0.793733E+09 0.375272E+09 0.418462E+09 0.129198E+10 0.273274E+09
April 0.834647E+09 0.372602E+09 0.462045E+09 0.153839E+10 0.146928E+09
May 0.815995E+09 0.326235E+09 0.489760E+09 0.167765E+10 45874105.12
June 0.776103E+09 0.297862E+09 0.478241E+09 0.172904E+10 10683107.81
July 0.825133E+09 0.297756E+09 0.527377E+09 0.190201E+10 20202761.70
August 0.754198E+09 0.252513E+09 0.501685E+09 0.169212E+10 12824142.80
September 0.703159E+09 0.253905E+09 0.449254E+09 0.161446E+10 29224799.44
October 0.668020E+09 0.286690E+09 0.381330E+09 0.141138E+10 55776317.22
November 0.526403E+09 0.209630E+09 0.316772E+09 0.100572E+10 0.172880E+09
December 0.439935E+09 0.155873E+09 0.284062E+09 0.719547E+09 0.356200E+09
           
Annual Sum or Average 0.828765E+10 0.337098E+10 0.491667E+10 0.164262E+11 0.186899E+10
Minimum of Months 0.439935E+09 0.155873E+09 0.284062E+09 0.719547E+09 10683107.81
Maximum of Months 0.834647E+09 0.375272E+09 0.527377E+09 0.190201E+10 0.424799E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.294194E+09 0.191295E+09 0.102899E+09 0.483018E+09 0.111508E+09
February 0.234576E+09 0.133412E+09 0.101164E+09 0.403030E+09 84539627.26
March 0.200709E+09 82981349.66 0.117728E+09 0.352826E+09 74369347.38
April 0.139270E+09 28528948.73 0.110741E+09 0.285297E+09 38708877.56
May 0.112364E+09 3566796.69 0.108797E+09 0.268860E+09 12081111.35
June 0.102570E+09 213510.41 0.102357E+09 0.277646E+09 2735309.54
July 0.113411E+09 952298.69 0.112459E+09 0.317470E+09 5364678.93
August 0.127496E+09 9534386.88 0.117961E+09 0.330546E+09 3374885.04
September 0.160000E+09 39527329.16 0.120472E+09 0.398024E+09 7709820.18
October 0.229456E+09 0.109104E+09 0.120353E+09 0.479523E+09 14583623.27
November 0.251556E+09 0.141181E+09 0.110375E+09 0.464303E+09 45804815.50
December 0.283637E+09 0.179091E+09 0.104546E+09 0.476251E+09 93144546.53
           
Annual Sum or Average 0.224924E+10 0.919388E+09 0.132985E+10 0.453680E+10 0.493925E+09
Minimum of Months 0.102570E+09 213510.41 0.101164E+09 0.268860E+09 2735309.54
Maximum of Months 0.294194E+09 0.191295E+09 0.120472E+09 0.483018E+09 0.111508E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 79127756.68 0.00 79127756.68 0.111673E+09 0.117954E+09
February 84596454.92 0.00 84596454.92 0.146895E+09 79796420.18
March 0.111728E+09 1971.67 0.111726E+09 0.193629E+09 62198641.12
April 0.121474E+09 693527.42 0.120780E+09 0.256633E+09 20839760.97
May 0.142540E+09 5839359.54 0.136701E+09 0.366103E+09 3395711.01
June 0.147852E+09 10633799.02 0.137218E+09 0.406910E+09 268446.77
July 0.154761E+09 7702942.47 0.147058E+09 0.428248E+09 1453579.20
August 0.137055E+09 1436744.47 0.135618E+09 0.387741E+09 66782.43
September 0.117448E+09 27133.79 0.117421E+09 0.339334E+09 1765396.74
October 0.101623E+09 0.00 0.101623E+09 0.273432E+09 5287198.26
November 85511177.30 0.00 85511177.30 0.192886E+09 38801243.24
December 78267205.96 0.00 78267205.96 0.125372E+09 93053408.61
           
Annual Sum or Average 0.136198E+10 26335478.38 0.133565E+10 0.322886E+10 0.424880E+09
Minimum of Months 78267205.96 0.00 78267205.96 0.111673E+09 66782.43
Maximum of Months 0.154761E+09 10633799.02 0.147058E+09 0.428248E+09 0.117954E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 70795903.72 0.00 70795903.72 99914646.26 0.105531E+09
February 75688768.75 0.00 75688768.75 0.131428E+09 71394159.48
March 99963347.83 1764.06 99961583.77 0.173241E+09 55649359.88
April 0.108683E+09 620501.61 0.108063E+09 0.229611E+09 18645413.10
May 0.127531E+09 5224497.11 0.122306E+09 0.327554E+09 3038155.51
June 0.132283E+09 9514100.27 0.122769E+09 0.364064E+09 240180.34
July 0.138465E+09 6891851.82 0.131574E+09 0.383155E+09 1300522.82
August 0.122624E+09 1285460.72 0.121338E+09 0.346913E+09 59750.49
September 0.105081E+09 24276.70 0.105057E+09 0.303603E+09 1579507.15
October 90922304.24 0.00 90922304.24 0.244640E+09 4730971.31
November 76507174.33 0.00 76507174.33 0.172576E+09 34715535.73
December 70025965.73 0.00 70025965.73 0.112172E+09 83255124.46
           
Annual Sum or Average 0.121857E+10 23562452.29 0.119501E+10 0.288887E+10 0.380140E+09
Minimum of Months 70025965.73 0.00 70025965.73 99914646.26 59750.49
Maximum of Months 0.138465E+09 9514100.27 0.131574E+09 0.383155E+09 0.105531E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.109832E+10 0.714162E+09 0.384153E+09 0.180299E+10 0.320746E+09
February 0.875743E+09 0.498067E+09 0.377676E+09 0.152661E+10 0.219212E+09
March 0.749308E+09 0.309794E+09 0.439514E+09 0.135843E+10 0.172241E+09
April 0.519937E+09 0.106507E+09 0.413430E+09 0.110326E+10 62921583.03
May 0.419488E+09 13315914.90 0.406172E+09 0.108604E+10 10337914.29
June 0.382925E+09 797097.99 0.382128E+09 0.108604E+10 749488.71
July 0.423397E+09 3555214.79 0.419842E+09 0.119272E+10 4289111.12
August 0.475980E+09 35594707.33 0.440385E+09 0.129928E+10 188499.47
September 0.597326E+09 0.147567E+09 0.449759E+09 0.149801E+10 5087839.93
October 0.856629E+09 0.407317E+09 0.449312E+09 0.182332E+10 15622817.92
November 0.939135E+09 0.527071E+09 0.412063E+09 0.175614E+10 0.107503E+09
December 0.105890E+10 0.668601E+09 0.390301E+09 0.177607E+10 0.260021E+09
           
Annual Sum or Average 0.839708E+10 0.343235E+10 0.496474E+10 0.173089E+11 0.117892E+10
Minimum of Months 0.382925E+09 797097.99 0.377676E+09 0.108604E+10 188499.47
Maximum of Months 0.109832E+10 0.714162E+09 0.449759E+09 0.182332E+10 0.320746E+09



Table of Contents

Report: WindowZoneSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 900.07 166.72 555.54 361.23 194.31 0.00 0.00
February 844.33 130.15 490.42 278.92 211.50 0.00 0.00
March 679.10 95.01 379.01 156.70 222.31 0.00 0.00
April 561.84 40.43 271.75 55.67 216.09 0.00 0.00
May 524.16 6.56 212.18 6.74 205.44 0.00 0.00
June 548.84 0.36 200.14 0.42 199.72 0.00 0.00
July 585.41 2.30 214.16 1.80 212.36 0.00 0.00
August 632.33 0.13 240.75 18.00 222.75 0.00 0.00
September 754.22 3.77 312.20 77.13 235.07 0.00 0.00
October 886.28 12.12 433.29 206.02 227.26 0.00 0.00
November 891.20 62.50 490.86 275.48 215.37 0.00 0.00
December 885.80 136.38 535.60 338.19 197.42 0.00 0.00
               
Annual Sum or Average 723.87 54.39 360.73 147.45 213.28 0.00 0.00
Minimum of Months 524.16 0.13 200.14 0.42 194.31 0.00 0.00
Maximum of Months 900.07 166.72 555.54 361.23 235.07 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 2522.61 500.18 1564.36 1017.20 547.16 0.00 0.00
February 2364.35 397.48 1380.98 785.42 595.57 0.00 0.00
March 1897.89 301.51 1067.25 441.25 626.01 0.00 0.00
April 1568.11 142.90 765.24 156.76 608.48 0.00 0.00
May 1438.87 28.83 597.48 18.97 578.52 0.00 0.00
June 1502.50 3.88 563.58 1.17 562.41 0.00 0.00
July 1623.72 12.18 603.05 5.06 597.99 0.00 0.00
August 1743.64 2.58 677.95 50.70 627.25 0.00 0.00
September 2110.43 24.80 879.14 217.19 661.95 0.00 0.00
October 2481.21 54.77 1220.12 580.15 639.96 0.00 0.00
November 2492.39 201.33 1382.22 775.75 606.47 0.00 0.00
December 2484.75 415.20 1508.22 952.31 555.91 0.00 0.00
               
Annual Sum or Average 2017.47 172.85 1015.79 415.21 600.58 0.00 0.00
Minimum of Months 1438.87 2.58 563.58 1.17 547.16 0.00 0.00
Maximum of Months 2522.61 500.18 1564.36 1017.20 661.95 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 3381.22 635.96 2032.19 1321.40 710.79 0.00 0.00
February 3173.01 499.94 1793.98 1020.30 773.67 0.00 0.00
March 2549.42 377.97 1386.42 573.21 813.22 0.00 0.00
April 2113.68 172.51 994.09 203.64 790.45 0.00 0.00
May 1949.82 32.99 776.16 24.64 751.52 0.00 0.00
June 2040.57 3.97 732.13 1.52 730.60 0.00 0.00
July 2202.27 13.52 783.39 6.58 776.82 0.00 0.00
August 2372.17 1.93 880.69 65.86 814.83 0.00 0.00
September 2868.12 24.48 1142.06 282.14 859.91 0.00 0.00
October 3368.04 53.38 1585.00 753.65 831.35 0.00 0.00
November 3367.13 246.15 1795.58 1007.74 787.84 0.00 0.00
December 3333.82 523.23 1959.26 1237.10 722.16 0.00 0.00
               
Annual Sum or Average 2724.35 214.30 1319.57 539.38 780.19 0.00 0.00
Minimum of Months 1949.82 1.93 732.13 1.52 710.79 0.00 0.00
Maximum of Months 3381.22 635.96 2032.19 1321.40 859.91 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 316.79 98.56 204.33 112.28 92.05 0.00 0.00
February 358.43 77.26 215.56 109.16 106.40 0.00 0.00
March 370.84 55.67 221.84 98.14 123.70 0.00 0.00
April 398.53 23.14 214.97 85.57 129.41 0.00 0.00
May 406.94 3.70 189.42 58.27 131.16 0.00 0.00
June 397.46 0.26 164.43 35.12 129.31 0.00 0.00
July 436.32 1.31 181.67 43.41 138.25 0.00 0.00
August 437.76 0.08 186.60 48.74 137.86 0.00 0.00
September 425.00 2.00 180.34 50.21 130.14 0.00 0.00
October 422.56 5.64 203.88 86.91 116.98 0.00 0.00
November 358.54 35.75 194.30 90.09 104.21 0.00 0.00
December 328.37 79.62 203.40 110.44 92.96 0.00 0.00
               
Annual Sum or Average 388.30 31.73 196.66 77.23 119.43 0.00 0.00
Minimum of Months 316.79 0.08 164.43 35.12 92.05 0.00 0.00
Maximum of Months 437.76 98.56 221.84 112.28 138.25 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 178.17 99.33 117.82 40.86 76.96 0.00 0.00
February 243.17 77.32 146.21 54.01 92.19 0.00 0.00
March 296.03 55.75 179.84 67.15 112.69 0.00 0.00
April 363.86 22.47 198.25 74.77 123.48 0.00 0.00
May 406.39 3.59 189.49 58.66 130.84 0.00 0.00
June 408.70 0.28 169.90 38.27 131.63 0.00 0.00
July 442.96 1.33 184.95 45.33 139.62 0.00 0.00
August 422.81 0.08 179.40 45.60 133.80 0.00 0.00
September 375.45 1.92 154.39 34.96 119.43 0.00 0.00
October 324.56 5.20 148.17 46.17 102.00 0.00 0.00
November 241.41 35.74 123.30 35.62 87.68 0.00 0.00
December 194.38 78.32 120.57 43.57 77.00 0.00 0.00
               
Annual Sum or Average 325.25 31.59 159.44 48.74 110.71 0.00 0.00
Minimum of Months 178.17 0.08 117.82 34.96 76.96 0.00 0.00
Maximum of Months 442.96 99.33 198.25 74.77 139.62 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 136.24 36.51 87.85 57.13 30.73 0.00 0.00
February 126.53 29.50 77.56 44.11 33.45 0.00 0.00
March 99.58 23.00 59.94 24.78 35.16 0.00 0.00
April 81.72 12.60 42.98 8.80 34.17 0.00 0.00
May 73.72 3.24 33.55 1.07 32.49 0.00 0.00
June 77.37 0.83 31.65 0.07 31.59 0.00 0.00
July 84.83 1.60 33.87 0.28 33.58 0.00 0.00
August 90.93 0.79 38.07 2.85 35.23 0.00 0.00
September 113.15 3.02 49.37 12.20 37.18 0.00 0.00
October 134.09 5.12 68.52 32.58 35.94 0.00 0.00
November 134.10 15.45 77.63 43.57 34.06 0.00 0.00
December 134.28 31.18 84.70 53.48 31.22 0.00 0.00
               
Annual Sum or Average 107.11 13.50 57.05 23.32 33.73 0.00 0.00
Minimum of Months 73.72 0.79 31.65 0.07 30.73 0.00 0.00
Maximum of Months 136.24 36.51 87.85 57.13 37.18 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 26.17 28.08 18.66 0.00 18.66 0.00 0.00
February 37.58 21.21 22.09 0.00 22.09 0.00 0.00
March 44.49 14.90 26.35 0.00 26.35 0.00 0.00
April 60.94 5.16 29.61 0.17 29.44 0.00 0.00
May 85.39 0.81 33.62 1.38 32.24 0.00 0.00
June 99.91 0.04 36.04 2.59 33.45 0.00 0.00
July 102.62 0.23 36.50 1.82 34.69 0.00 0.00
August 92.33 0.01 32.33 0.34 31.99 0.00 0.00
September 83.92 0.30 28.63 0.01 28.62 0.00 0.00
October 64.46 1.06 23.97 0.00 23.97 0.00 0.00
November 46.33 9.57 20.84 0.00 20.84 0.00 0.00
December 29.31 22.01 18.46 0.00 18.46 0.00 0.00
               
Annual Sum or Average 64.58 8.57 27.29 0.53 26.76 0.00 0.00
Minimum of Months 26.17 0.01 18.46 0.00 18.46 0.00 0.00
Maximum of Months 102.62 28.08 36.50 2.59 34.69 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 331.59 96.60 214.72 121.68 93.04 0.00 0.00
February 358.94 73.52 218.61 111.66 106.95 0.00 0.00
March 365.79 50.97 223.12 101.04 122.08 0.00 0.00
April 397.47 21.68 214.75 82.89 131.86 0.00 0.00
May 415.65 3.41 194.29 62.24 132.05 0.00 0.00
June 439.63 0.29 189.29 57.54 131.75 0.00 0.00
July 462.14 1.25 196.39 55.94 140.44 0.00 0.00
August 442.07 0.08 188.40 50.70 137.70 0.00 0.00
September 454.70 1.95 197.38 64.23 133.15 0.00 0.00
October 434.50 5.40 210.38 94.26 116.13 0.00 0.00
November 364.19 34.33 198.60 94.91 103.69 0.00 0.00
December 301.32 77.71 188.03 95.97 92.06 0.00 0.00
               
Annual Sum or Average 397.47 30.42 202.73 82.60 120.13 0.00 0.00
Minimum of Months 301.32 0.08 188.03 50.70 92.06 0.00 0.00
Maximum of Months 462.14 96.60 223.12 121.68 140.44 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 189.46 94.18 128.21 50.26 77.95 0.00 0.00
February 240.88 71.34 149.26 56.52 92.75 0.00 0.00
March 289.17 49.63 181.12 70.06 111.06 0.00 0.00
April 362.72 21.07 198.02 72.09 125.93 0.00 0.00
May 415.20 3.40 194.36 62.63 131.73 0.00 0.00
June 450.92 0.31 194.76 60.70 134.06 0.00 0.00
July 468.81 1.28 199.67 57.86 141.81 0.00 0.00
August 427.11 0.07 181.21 47.57 133.64 0.00 0.00
September 405.02 1.87 171.43 48.99 122.44 0.00 0.00
October 336.26 4.96 154.67 53.52 101.15 0.00 0.00
November 245.56 33.07 127.60 40.44 87.16 0.00 0.00
December 166.56 75.37 105.21 29.10 76.11 0.00 0.00
               
Annual Sum or Average 333.54 29.54 165.51 54.11 111.40 0.00 0.00
Minimum of Months 166.56 0.07 105.21 29.10 76.11 0.00 0.00
Maximum of Months 468.81 94.18 199.67 72.09 141.81 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 370.96 114.80 230.79 123.78 107.01 0.00 0.00
February 378.67 88.29 215.90 95.57 120.33 0.00 0.00
March 336.35 63.65 186.96 53.69 133.27 0.00 0.00
April 332.41 26.39 157.26 19.44 137.82 0.00 0.00
May 371.70 4.35 145.54 5.29 140.25 0.00 0.00
June 407.32 0.57 146.65 5.76 140.89 0.00 0.00
July 425.75 2.05 152.46 4.55 147.91 0.00 0.00
August 419.21 0.20 152.53 6.90 145.63 0.00 0.00
September 445.17 3.61 168.99 26.44 142.55 0.00 0.00
October 449.11 8.28 200.40 70.59 129.80 0.00 0.00
November 413.35 43.28 213.34 94.39 118.95 0.00 0.00
December 374.12 93.12 223.52 115.88 107.64 0.00 0.00
               
Annual Sum or Average 393.74 37.17 182.71 51.67 131.05 0.00 0.00
Minimum of Months 332.41 0.20 145.54 4.55 107.01 0.00 0.00
Maximum of Months 449.11 114.80 230.79 123.78 147.91 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 312.15 98.04 204.33 112.28 92.05 0.00 0.00
February 352.88 77.07 215.56 109.16 106.40 0.00 0.00
March 364.29 55.47 221.84 98.14 123.70 0.00 0.00
April 391.81 23.04 214.97 85.57 129.41 0.00 0.00
May 400.94 3.56 189.42 58.27 131.16 0.00 0.00
June 391.96 0.24 164.43 35.12 129.31 0.00 0.00
July 430.53 1.24 181.67 43.41 138.25 0.00 0.00
August 432.16 0.10 186.60 48.74 137.86 0.00 0.00
September 419.56 1.86 180.34 50.21 130.14 0.00 0.00
October 417.64 5.33 203.88 86.91 116.98 0.00 0.00
November 353.65 35.19 194.30 90.09 104.21 0.00 0.00
December 323.41 79.38 203.40 110.44 92.96 0.00 0.00
               
Annual Sum or Average 382.75 31.52 196.66 77.23 119.43 0.00 0.00
Minimum of Months 312.15 0.10 164.43 35.12 92.05 0.00 0.00
Maximum of Months 432.16 98.04 221.84 112.28 138.25 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 174.86 98.43 117.82 40.86 76.96 0.00 0.00
February 238.89 76.95 146.21 54.01 92.19 0.00 0.00
March 290.41 55.51 179.84 67.15 112.69 0.00 0.00
April 357.55 22.38 198.25 74.77 123.48 0.00 0.00
May 400.24 3.47 189.49 58.66 130.84 0.00 0.00
June 402.97 0.25 169.90 38.27 131.63 0.00 0.00
July 437.08 1.26 184.95 45.33 139.62 0.00 0.00
August 417.29 0.10 179.40 45.60 133.80 0.00 0.00
September 370.58 1.76 154.39 34.96 119.43 0.00 0.00
October 320.72 4.86 148.17 46.17 102.00 0.00 0.00
November 237.74 35.04 123.30 35.62 87.68 0.00 0.00
December 190.88 77.74 120.57 43.57 77.00 0.00 0.00
               
Annual Sum or Average 320.36 31.29 159.44 48.74 110.71 0.00 0.00
Minimum of Months 174.86 0.10 117.82 34.96 76.96 0.00 0.00
Maximum of Months 437.08 98.43 198.25 74.77 139.62 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 252.99 51.08 161.09 104.75 56.34 0.00 0.00
February 236.24 39.09 142.21 80.88 61.33 0.00 0.00
March 187.95 27.33 109.90 45.44 64.46 0.00 0.00
April 157.19 10.48 78.80 16.14 62.66 0.00 0.00
May 151.70 1.57 61.53 1.95 59.57 0.00 0.00
June 160.49 0.08 58.04 0.12 57.92 0.00 0.00
July 172.11 0.47 62.10 0.52 61.58 0.00 0.00
August 185.22 0.02 69.81 5.22 64.59 0.00 0.00
September 220.72 0.72 90.53 22.37 68.17 0.00 0.00
October 256.81 2.53 125.64 59.74 65.90 0.00 0.00
November 253.77 17.97 142.33 79.88 62.45 0.00 0.00
December 249.21 41.64 155.31 98.06 57.25 0.00 0.00
               
Annual Sum or Average 206.89 15.99 104.60 42.76 61.85 0.00 0.00
Minimum of Months 151.70 0.02 58.04 0.12 56.34 0.00 0.00
Maximum of Months 256.81 51.08 161.09 104.75 68.17 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 223.50 275.11 163.29 0.00 163.29 0.00 0.00
February 322.09 218.65 193.28 0.00 193.28 0.00 0.00
March 382.38 166.38 230.56 0.00 230.56 0.00 0.00
April 526.56 75.87 259.03 1.48 257.55 0.00 0.00
May 717.72 16.06 294.14 12.05 282.09 0.00 0.00
June 836.44 2.89 315.27 22.68 292.60 0.00 0.00
July 866.36 7.51 319.36 15.90 303.47 0.00 0.00
August 770.21 2.52 282.83 2.96 279.86 0.00 0.00
September 709.93 13.35 250.44 0.06 250.38 0.00 0.00
October 546.52 24.14 209.71 0.00 209.71 0.00 0.00
November 394.16 107.29 182.34 0.00 182.34 0.00 0.00
December 250.34 224.13 161.51 0.00 161.51 0.00 0.00
               
Annual Sum or Average 546.57 93.96 238.71 4.62 234.09 0.00 0.00
Minimum of Months 223.50 2.52 161.51 0.00 161.51 0.00 0.00
Maximum of Months 866.36 275.11 319.36 22.68 303.47 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 215.76 289.12 163.29 0.00 163.29 0.00 0.00
February 312.40 232.08 193.28 0.00 193.28 0.00 0.00
March 370.95 178.70 230.56 0.00 230.56 0.00 0.00
April 513.06 85.84 259.03 1.48 257.55 0.00 0.00
May 698.87 19.96 294.14 12.05 282.09 0.00 0.00
June 816.59 4.02 315.27 22.68 292.60 0.00 0.00
July 848.63 9.29 319.36 15.90 303.47 0.00 0.00
August 750.60 3.72 282.83 2.96 279.86 0.00 0.00
September 693.60 16.87 250.44 0.06 250.38 0.00 0.00
October 530.25 28.81 209.71 0.00 209.71 0.00 0.00
November 380.14 115.43 182.34 0.00 182.34 0.00 0.00
December 241.60 237.36 161.51 0.00 161.51 0.00 0.00
               
Annual Sum or Average 532.07 101.20 238.71 4.62 234.09 0.00 0.00
Minimum of Months 215.76 3.72 161.51 0.00 161.51 0.00 0.00
Maximum of Months 848.63 289.12 319.36 22.68 303.47 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 536.12 241.12 342.91 171.94 170.98 0.00 0.00
February 605.95 202.18 367.86 168.17 199.69 0.00 0.00
March 662.80 155.92 404.22 171.09 233.13 0.00 0.00
April 776.86 86.37 412.74 154.97 257.78 0.00 0.00
May 827.96 26.08 388.63 124.86 263.78 0.00 0.00
June 893.48 6.26 384.04 118.24 265.80 0.00 0.00
July 954.66 11.54 396.04 113.80 282.24 0.00 0.00
August 863.53 7.28 369.59 98.26 271.33 0.00 0.00
September 877.71 17.23 368.79 113.22 255.57 0.00 0.00
October 781.91 31.76 365.04 147.77 217.27 0.00 0.00
November 620.70 102.23 326.19 135.34 190.84 0.00 0.00
December 479.71 202.35 293.22 125.06 168.16 0.00 0.00
               
Annual Sum or Average 740.65 90.36 368.22 136.71 231.52 0.00 0.00
Minimum of Months 479.71 6.26 293.22 98.26 168.16 0.00 0.00
Maximum of Months 954.66 241.12 412.74 171.94 282.24 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 747.26 198.30 466.04 266.64 199.40 0.00 0.00
February 743.85 150.87 428.25 205.88 222.37 0.00 0.00
March 642.92 107.07 358.80 115.67 243.13 0.00 0.00
April 613.12 39.40 289.39 41.60 247.79 0.00 0.00
May 664.38 6.18 257.45 9.10 248.35 0.00 0.00
June 716.44 0.48 255.81 8.08 247.73 0.00 0.00
July 748.25 2.62 267.56 6.78 260.78 0.00 0.00
August 759.38 0.12 274.66 14.31 260.36 0.00 0.00
September 825.98 3.25 316.30 56.95 259.35 0.00 0.00
October 874.15 9.55 391.72 152.07 239.64 0.00 0.00
November 817.41 68.73 424.83 203.35 221.48 0.00 0.00
December 749.46 160.56 450.71 249.63 201.09 0.00 0.00
               
Annual Sum or Average 741.85 61.91 348.10 110.42 237.68 0.00 0.00
Minimum of Months 613.12 0.12 255.81 6.78 199.40 0.00 0.00
Maximum of Months 874.15 198.30 466.04 266.64 260.78 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.241075E+10 0.446551E+09 0.148795E+10 0.967519E+09 0.520433E+09 0.00 0.00
February 0.204261E+10 0.314857E+09 0.118642E+10 0.674762E+09 0.511657E+09 0.00 0.00
March 0.181890E+10 0.254480E+09 0.101513E+10 0.419697E+09 0.595431E+09 0.00 0.00
April 0.145629E+10 0.104798E+09 0.704385E+09 0.144292E+09 0.560093E+09 0.00 0.00
May 0.140390E+10 17567904.18 0.568300E+09 18039893.06 0.550260E+09 0.00 0.00
June 0.142259E+10 946029.98 0.518766E+09 1079877.92 0.517686E+09 0.00 0.00
July 0.156796E+10 6150496.22 0.573595E+09 4816469.25 0.568779E+09 0.00 0.00
August 0.169363E+10 352411.32 0.644834E+09 48222350.38 0.596611E+09 0.00 0.00
September 0.195495E+10 9773733.42 0.809229E+09 0.199919E+09 0.609311E+09 0.00 0.00
October 0.237380E+10 32465453.46 0.116052E+10 0.551817E+09 0.608706E+09 0.00 0.00
November 0.230998E+10 0.161993E+09 0.127230E+10 0.714056E+09 0.558244E+09 0.00 0.00
December 0.237253E+10 0.365284E+09 0.143456E+10 0.905795E+09 0.528761E+09 0.00 0.00
               
Annual Sum or Average 0.228279E+11 0.171522E+10 0.113760E+11 0.465001E+10 0.672597E+10 0.00 0.00
Minimum of Months 0.140390E+10 352411.32 0.518766E+09 1079877.92 0.511657E+09 0.00 0.00
Maximum of Months 0.241075E+10 0.446551E+09 0.148795E+10 0.967519E+09 0.609311E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.675656E+10 0.133968E+10 0.418997E+10 0.272447E+10 0.146550E+10 0.00 0.00
February 0.571985E+10 0.961590E+09 0.334088E+10 0.190008E+10 0.144079E+10 0.00 0.00
March 0.508332E+10 0.807559E+09 0.285853E+10 0.118184E+10 0.167669E+10 0.00 0.00
April 0.406453E+10 0.370384E+09 0.198350E+10 0.406316E+09 0.157718E+10 0.00 0.00
May 0.385386E+10 77208674.60 0.160030E+10 50799149.42 0.154950E+10 0.00 0.00
June 0.389448E+10 10063266.45 0.146081E+10 3040865.03 0.145777E+10 0.00 0.00
July 0.434896E+10 32617060.45 0.161521E+10 13562859.83 0.160164E+10 0.00 0.00
August 0.467016E+10 6911631.55 0.181581E+10 0.135791E+09 0.168002E+10 0.00 0.00
September 0.547023E+10 64293223.72 0.227874E+10 0.562957E+09 0.171578E+10 0.00 0.00
October 0.664567E+10 0.146700E+09 0.326796E+10 0.155388E+10 0.171408E+10 0.00 0.00
November 0.646028E+10 0.521859E+09 0.358271E+10 0.201074E+10 0.157198E+10 0.00 0.00
December 0.665514E+10 0.111208E+10 0.403962E+10 0.255066E+10 0.148896E+10 0.00 0.00
               
Annual Sum or Average 0.636230E+11 0.545095E+10 0.320340E+11 0.130941E+11 0.189399E+11 0.00 0.00
Minimum of Months 0.385386E+10 6911631.55 0.146081E+10 3040865.03 0.144079E+10 0.00 0.00
Maximum of Months 0.675656E+10 0.133968E+10 0.418997E+10 0.272447E+10 0.171578E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.905625E+10 0.170334E+10 0.544302E+10 0.353924E+10 0.190377E+10 0.00 0.00
February 0.767614E+10 0.120946E+10 0.433999E+10 0.246832E+10 0.187167E+10 0.00 0.00
March 0.682837E+10 0.101236E+10 0.371340E+10 0.153528E+10 0.217812E+10 0.00 0.00
April 0.547866E+10 0.447140E+09 0.257668E+10 0.527828E+09 0.204885E+10 0.00 0.00
May 0.522239E+10 88357129.81 0.207888E+10 65990986.10 0.201288E+10 0.00 0.00
June 0.528916E+10 10287770.09 0.189768E+10 3950256.73 0.189373E+10 0.00 0.00
July 0.589857E+10 36202971.73 0.209825E+10 17618926.79 0.208063E+10 0.00 0.00
August 0.635362E+10 5163901.75 0.235884E+10 0.176400E+09 0.218244E+10 0.00 0.00
September 0.743417E+10 63452857.53 0.296021E+10 0.731314E+09 0.222890E+10 0.00 0.00
October 0.902096E+10 0.142985E+09 0.424526E+10 0.201858E+10 0.222668E+10 0.00 0.00
November 0.872759E+10 0.638017E+09 0.465415E+10 0.261206E+10 0.204209E+10 0.00 0.00
December 0.892929E+10 0.140142E+10 0.524769E+10 0.331345E+10 0.193424E+10 0.00 0.00
               
Annual Sum or Average 0.859152E+11 0.675819E+10 0.416140E+11 0.170100E+11 0.246040E+11 0.00 0.00
Minimum of Months 0.522239E+10 5163901.75 0.189768E+10 3950256.73 0.187167E+10 0.00 0.00
Maximum of Months 0.905625E+10 0.170334E+10 0.544302E+10 0.353924E+10 0.222890E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.848502E+09 0.263971E+09 0.547283E+09 0.300734E+09 0.246549E+09 0.00 0.00
February 0.867120E+09 0.186917E+09 0.521479E+09 0.264081E+09 0.257398E+09 0.00 0.00
March 0.993245E+09 0.149107E+09 0.594175E+09 0.262845E+09 0.331330E+09 0.00 0.00
April 0.103298E+10 59986320.56 0.557213E+09 0.221785E+09 0.335428E+09 0.00 0.00
May 0.108995E+10 9902586.75 0.507352E+09 0.156063E+09 0.351288E+09 0.00 0.00
June 0.103022E+10 684787.82 0.426207E+09 91025211.56 0.335181E+09 0.00 0.00
July 0.116865E+10 3509614.56 0.486578E+09 0.116277E+09 0.370301E+09 0.00 0.00
August 0.117249E+10 226695.67 0.499793E+09 0.130546E+09 0.369247E+09 0.00 0.00
September 0.110160E+10 5192144.23 0.467448E+09 0.130132E+09 0.337316E+09 0.00 0.00
October 0.113178E+10 15098585.97 0.546079E+09 0.232772E+09 0.313307E+09 0.00 0.00
November 0.929348E+09 92665190.55 0.503617E+09 0.233505E+09 0.270113E+09 0.00 0.00
December 0.879496E+09 0.213259E+09 0.544779E+09 0.295801E+09 0.248978E+09 0.00 0.00
               
Annual Sum or Average 0.122454E+11 0.100052E+10 0.620200E+10 0.243557E+10 0.376644E+10 0.00 0.00
Minimum of Months 0.848502E+09 226695.67 0.426207E+09 91025211.56 0.246549E+09 0.00 0.00
Maximum of Months 0.117249E+10 0.263971E+09 0.594175E+09 0.300734E+09 0.370301E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.477220E+09 0.266054E+09 0.315569E+09 0.109438E+09 0.206131E+09 0.00 0.00
February 0.588267E+09 0.187051E+09 0.353702E+09 0.130669E+09 0.223033E+09 0.00 0.00
March 0.792874E+09 0.149309E+09 0.481688E+09 0.179865E+09 0.301822E+09 0.00 0.00
April 0.943130E+09 58252319.37 0.513861E+09 0.193804E+09 0.320057E+09 0.00 0.00
May 0.108848E+10 9618470.52 0.507540E+09 0.157107E+09 0.350432E+09 0.00 0.00
June 0.105936E+10 726331.39 0.440383E+09 99208328.72 0.341174E+09 0.00 0.00
July 0.118642E+10 3559212.35 0.495369E+09 0.121407E+09 0.373962E+09 0.00 0.00
August 0.113245E+10 225241.64 0.480518E+09 0.122146E+09 0.358372E+09 0.00 0.00
September 0.973159E+09 4972818.59 0.400187E+09 90626159.72 0.309561E+09 0.00 0.00
October 0.869310E+09 13929514.34 0.396866E+09 0.123668E+09 0.273197E+09 0.00 0.00
November 0.625728E+09 92632688.66 0.319582E+09 92323391.94 0.227259E+09 0.00 0.00
December 0.520636E+09 0.209767E+09 0.322943E+09 0.116710E+09 0.206233E+09 0.00 0.00
               
Annual Sum or Average 0.102570E+11 0.996099E+09 0.502821E+10 0.153697E+10 0.349123E+10 0.00 0.00
Minimum of Months 0.477220E+09 225241.64 0.315569E+09 90626159.72 0.206131E+09 0.00 0.00
Maximum of Months 0.118642E+10 0.266054E+09 0.513861E+09 0.193804E+09 0.373962E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.364894E+09 97781420.27 0.235309E+09 0.153006E+09 82302997.65 0.00 0.00
February 0.306094E+09 71368267.21 0.187624E+09 0.106708E+09 80915277.26 0.00 0.00
March 0.266707E+09 61608765.86 0.160536E+09 66371880.15 94163689.54 0.00 0.00
April 0.211829E+09 32649015.10 0.111394E+09 22818620.98 88575365.15 0.00 0.00
May 0.197460E+09 8688711.61 89873280.16 2852869.99 87020410.17 0.00 0.00
June 0.200536E+09 2157193.81 82039774.92 170774.37 81869000.56 0.00 0.00
July 0.227211E+09 4296855.71 90710703.00 761687.47 89949015.53 0.00 0.00
August 0.243551E+09 2124044.25 0.101976E+09 7625992.90 94350425.71 0.00 0.00
September 0.293281E+09 7825112.03 0.127974E+09 31615575.84 96358645.11 0.00 0.00
October 0.359144E+09 13718865.81 0.183529E+09 87265587.65 96262912.52 0.00 0.00
November 0.347580E+09 40049532.75 0.201205E+09 0.112922E+09 88282536.13 0.00 0.00
December 0.359650E+09 83522498.42 0.226865E+09 0.143244E+09 83620064.08 0.00 0.00
               
Annual Sum or Average 0.337794E+10 0.425790E+09 0.179903E+10 0.735364E+09 0.106367E+10 0.00 0.00
Minimum of Months 0.197460E+09 2124044.25 82039774.92 170774.37 80915277.26 0.00 0.00
Maximum of Months 0.364894E+09 97781420.27 0.235309E+09 0.153006E+09 96358645.11 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 70096559.15 75202368.82 49991117.79 0.00 49991117.79 0.00 0.00
February 90902765.60 51314685.63 53446117.01 0.00 53446117.01 0.00 0.00
March 0.119161E+09 39921099.57 70587127.69 1245.66 70585882.03 0.00 0.00
April 0.157946E+09 13385655.68 76744494.28 438154.86 76306339.42 0.00 0.00
May 0.228712E+09 2172375.97 90053455.50 3689174.61 86364280.90 0.00 0.00
June 0.258974E+09 101216.01 93409270.91 6718192.47 86691078.44 0.00 0.00
July 0.274848E+09 625017.25 97774596.35 4866543.94 92908052.41 0.00 0.00
August 0.247303E+09 23584.37 86588371.69 907702.50 85680669.19 0.00 0.00
September 0.217517E+09 764947.25 74200848.51 17142.51 74183706.00 0.00 0.00
October 0.172662E+09 2845975.84 64202974.78 0.00 64202974.78 0.00 0.00
November 0.120097E+09 24805621.58 54024017.81 0.00 54024017.81 0.00 0.00
December 78507998.05 58962788.38 49447441.40 0.00 49447441.40 0.00 0.00
               
Annual Sum or Average 0.203673E+10 0.270125E+09 0.860470E+09 16638156.53 0.843832E+09 0.00 0.00
Minimum of Months 70096559.15 23584.37 49447441.40 0.00 49447441.40 0.00 0.00
Maximum of Months 0.274848E+09 75202368.82 97774596.35 6718192.47 92908052.41 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.888134E+09 0.258747E+09 0.575104E+09 0.325914E+09 0.249190E+09 0.00 0.00
February 0.868339E+09 0.177866E+09 0.528872E+09 0.270134E+09 0.258738E+09 0.00 0.00
March 0.979725E+09 0.136523E+09 0.597604E+09 0.270631E+09 0.326974E+09 0.00 0.00
April 0.103024E+10 56196544.51 0.556623E+09 0.214843E+09 0.341780E+09 0.00 0.00
May 0.111328E+10 9146237.42 0.520390E+09 0.166696E+09 0.353695E+09 0.00 0.00
June 0.113951E+10 753822.08 0.490649E+09 0.149155E+09 0.341494E+09 0.00 0.00
July 0.123781E+10 3354466.27 0.526007E+09 0.149841E+09 0.376166E+09 0.00 0.00
August 0.118405E+10 203170.76 0.504622E+09 0.135800E+09 0.368822E+09 0.00 0.00
September 0.117859E+10 5057945.84 0.511604E+09 0.166489E+09 0.345115E+09 0.00 0.00
October 0.116377E+10 14452189.23 0.563490E+09 0.252459E+09 0.311031E+09 0.00 0.00
November 0.943969E+09 88994167.64 0.514776E+09 0.246004E+09 0.268773E+09 0.00 0.00
December 0.807046E+09 0.208138E+09 0.503620E+09 0.257033E+09 0.246587E+09 0.00 0.00
               
Annual Sum or Average 0.125345E+11 0.959432E+09 0.639336E+10 0.260500E+10 0.378836E+10 0.00 0.00
Minimum of Months 0.807046E+09 203170.76 0.490649E+09 0.135800E+09 0.246587E+09 0.00 0.00
Maximum of Months 0.123781E+10 0.258747E+09 0.597604E+09 0.325914E+09 0.376166E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.507439E+09 0.252261E+09 0.343390E+09 0.134618E+09 0.208771E+09 0.00 0.00
February 0.582731E+09 0.172596E+09 0.361094E+09 0.136722E+09 0.224373E+09 0.00 0.00
March 0.774520E+09 0.132921E+09 0.485117E+09 0.187651E+09 0.297466E+09 0.00 0.00
April 0.940165E+09 54609628.43 0.513271E+09 0.186862E+09 0.326409E+09 0.00 0.00
May 0.111207E+10 9102704.25 0.520578E+09 0.167740E+09 0.352838E+09 0.00 0.00
June 0.116878E+10 796328.34 0.504825E+09 0.157338E+09 0.347487E+09 0.00 0.00
July 0.125565E+10 3418538.18 0.534798E+09 0.154971E+09 0.379827E+09 0.00 0.00
August 0.114398E+10 200081.60 0.485347E+09 0.127400E+09 0.357947E+09 0.00 0.00
September 0.104981E+10 4836873.69 0.444343E+09 0.126983E+09 0.317360E+09 0.00 0.00
October 0.900644E+09 13278465.12 0.414277E+09 0.143355E+09 0.270922E+09 0.00 0.00
November 0.636482E+09 85727018.62 0.330741E+09 0.104823E+09 0.225919E+09 0.00 0.00
December 0.446111E+09 0.201866E+09 0.281784E+09 77942147.70 0.203842E+09 0.00 0.00
               
Annual Sum or Average 0.105184E+11 0.931613E+09 0.521957E+10 0.170640E+10 0.351316E+10 0.00 0.00
Minimum of Months 0.446111E+09 200081.60 0.281784E+09 77942147.70 0.203842E+09 0.00 0.00
Maximum of Months 0.125565E+10 0.252261E+09 0.534798E+09 0.187651E+09 0.379827E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.993591E+09 0.307475E+09 0.618146E+09 0.331521E+09 0.286625E+09 0.00 0.00
February 0.916085E+09 0.213580E+09 0.522310E+09 0.231207E+09 0.291103E+09 0.00 0.00
March 0.900876E+09 0.170469E+09 0.500751E+09 0.143812E+09 0.356939E+09 0.00 0.00
April 0.861613E+09 68395269.02 0.407614E+09 50390796.35 0.357223E+09 0.00 0.00
May 0.995552E+09 11655632.24 0.389816E+09 14173365.17 0.375643E+09 0.00 0.00
June 0.105578E+10 1488699.83 0.380113E+09 14923878.21 0.365189E+09 0.00 0.00
July 0.114032E+10 5481659.92 0.408357E+09 12192930.96 0.396164E+09 0.00 0.00
August 0.112283E+10 535915.89 0.408534E+09 18489793.87 0.390044E+09 0.00 0.00
September 0.115389E+10 9362104.02 0.438028E+09 68539297.28 0.369489E+09 0.00 0.00
October 0.120291E+10 22188142.80 0.536740E+09 0.189080E+09 0.347660E+09 0.00 0.00
November 0.107139E+10 0.112174E+09 0.552989E+09 0.244672E+09 0.308318E+09 0.00 0.00
December 0.100205E+10 0.249412E+09 0.598672E+09 0.310371E+09 0.288301E+09 0.00 0.00
               
Annual Sum or Average 0.124169E+11 0.117222E+10 0.576207E+10 0.162937E+10 0.413270E+10 0.00 0.00
Minimum of Months 0.861613E+09 535915.89 0.380113E+09 12192930.96 0.286625E+09 0.00 0.00
Maximum of Months 0.120291E+10 0.307475E+09 0.618146E+09 0.331521E+09 0.396164E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.836055E+09 0.262601E+09 0.547283E+09 0.300734E+09 0.246549E+09 0.00 0.00
February 0.853687E+09 0.186447E+09 0.521479E+09 0.264081E+09 0.257398E+09 0.00 0.00
March 0.975727E+09 0.148559E+09 0.594175E+09 0.262845E+09 0.331330E+09 0.00 0.00
April 0.101556E+10 59729715.53 0.557213E+09 0.221785E+09 0.335428E+09 0.00 0.00
May 0.107387E+10 9537036.51 0.507352E+09 0.156063E+09 0.351288E+09 0.00 0.00
June 0.101595E+10 618096.58 0.426207E+09 91025211.56 0.335181E+09 0.00 0.00
July 0.115314E+10 3320283.14 0.486578E+09 0.116277E+09 0.370301E+09 0.00 0.00
August 0.115750E+10 278323.89 0.499793E+09 0.130546E+09 0.369247E+09 0.00 0.00
September 0.108750E+10 4816769.41 0.467448E+09 0.130132E+09 0.337316E+09 0.00 0.00
October 0.111862E+10 14265314.30 0.546079E+09 0.232772E+09 0.313307E+09 0.00 0.00
November 0.916662E+09 91209765.58 0.503617E+09 0.233505E+09 0.270113E+09 0.00 0.00
December 0.866220E+09 0.212615E+09 0.544779E+09 0.295801E+09 0.248978E+09 0.00 0.00
               
Annual Sum or Average 0.120705E+11 0.993997E+09 0.620200E+10 0.243557E+10 0.376644E+10 0.00 0.00
Minimum of Months 0.836055E+09 278323.89 0.426207E+09 91025211.56 0.246549E+09 0.00 0.00
Maximum of Months 0.115750E+10 0.262601E+09 0.594175E+09 0.300734E+09 0.370301E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.468351E+09 0.263629E+09 0.315569E+09 0.109438E+09 0.206131E+09 0.00 0.00
February 0.577921E+09 0.186157E+09 0.353702E+09 0.130669E+09 0.223033E+09 0.00 0.00
March 0.777844E+09 0.148670E+09 0.481688E+09 0.179865E+09 0.301822E+09 0.00 0.00
April 0.926776E+09 58003042.28 0.513861E+09 0.193804E+09 0.320057E+09 0.00 0.00
May 0.107199E+10 9283051.54 0.507540E+09 0.157107E+09 0.350432E+09 0.00 0.00
June 0.104450E+10 652814.36 0.440383E+09 99208328.72 0.341174E+09 0.00 0.00
July 0.117067E+10 3363282.57 0.495369E+09 0.121407E+09 0.373962E+09 0.00 0.00
August 0.111768E+10 273835.48 0.480518E+09 0.122146E+09 0.358372E+09 0.00 0.00
September 0.960545E+09 4557936.19 0.400187E+09 90626159.72 0.309561E+09 0.00 0.00
October 0.859013E+09 13007481.17 0.396866E+09 0.123668E+09 0.273197E+09 0.00 0.00
November 0.616229E+09 90835804.83 0.319582E+09 92323391.94 0.227259E+09 0.00 0.00
December 0.511249E+09 0.208214E+09 0.322943E+09 0.116710E+09 0.206233E+09 0.00 0.00
               
Annual Sum or Average 0.101028E+11 0.986647E+09 0.502821E+10 0.153697E+10 0.349123E+10 0.00 0.00
Minimum of Months 0.468351E+09 273835.48 0.315569E+09 90626159.72 0.206131E+09 0.00 0.00
Maximum of Months 0.117067E+10 0.263629E+09 0.513861E+09 0.193804E+09 0.373962E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.677617E+09 0.136810E+09 0.431464E+09 0.280553E+09 0.150912E+09 0.00 0.00
February 0.571508E+09 94577921.33 0.344028E+09 0.195661E+09 0.148367E+09 0.00 0.00
March 0.503411E+09 73187636.59 0.294360E+09 0.121700E+09 0.172659E+09 0.00 0.00
April 0.407427E+09 27170169.58 0.204253E+09 41840441.24 0.162413E+09 0.00 0.00
May 0.406323E+09 4198012.81 0.164793E+09 5231049.65 0.159561E+09 0.00 0.00
June 0.415983E+09 202273.58 0.150429E+09 313133.51 0.150116E+09 0.00 0.00
July 0.460971E+09 1268640.48 0.166328E+09 1396637.42 0.164931E+09 0.00 0.00
August 0.496103E+09 60393.46 0.186985E+09 13983093.38 0.173002E+09 0.00 0.00
September 0.572119E+09 1862908.71 0.234655E+09 57970621.67 0.176684E+09 0.00 0.00
October 0.687831E+09 6766448.79 0.336520E+09 0.160011E+09 0.176509E+09 0.00 0.00
November 0.657776E+09 46576805.56 0.368931E+09 0.207056E+09 0.161876E+09 0.00 0.00
December 0.667492E+09 0.111524E+09 0.415981E+09 0.262654E+09 0.153327E+09 0.00 0.00
               
Annual Sum or Average 0.652456E+10 0.504205E+09 0.329873E+10 0.134837E+10 0.195036E+10 0.00 0.00
Minimum of Months 0.406323E+09 60393.46 0.150429E+09 313133.51 0.148367E+09 0.00 0.00
Maximum of Months 0.687831E+09 0.136810E+09 0.431464E+09 0.280553E+09 0.176684E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.598611E+09 0.736856E+09 0.437348E+09 0.00 0.437348E+09 0.00 0.00
February 0.779193E+09 0.528952E+09 0.467574E+09 0.00 0.467574E+09 0.00 0.00
March 0.102416E+10 0.445633E+09 0.617532E+09 10897.63 0.617521E+09 0.00 0.00
April 0.136484E+10 0.196658E+09 0.671400E+09 3833201.69 0.667567E+09 0.00 0.00
May 0.192233E+10 43008478.21 0.787833E+09 32274777.04 0.755559E+09 0.00 0.00
June 0.216805E+10 7482274.71 0.817192E+09 58774166.93 0.758418E+09 0.00 0.00
July 0.232045E+10 20120539.56 0.855382E+09 42575003.16 0.812807E+09 0.00 0.00
August 0.206294E+10 6743098.86 0.757519E+09 7941043.40 0.749578E+09 0.00 0.00
September 0.184015E+10 34600113.66 0.649147E+09 149971.41 0.648997E+09 0.00 0.00
October 0.146381E+10 64657980.60 0.561680E+09 0.00 0.561680E+09 0.00 0.00
November 0.102167E+10 0.278102E+09 0.472630E+09 0.00 0.472630E+09 0.00 0.00
December 0.670504E+09 0.600315E+09 0.432591E+09 0.00 0.432591E+09 0.00 0.00
               
Annual Sum or Average 0.172367E+11 0.296313E+10 0.752783E+10 0.145559E+09 0.738227E+10 0.00 0.00
Minimum of Months 0.598611E+09 6743098.86 0.432591E+09 0.00 0.432591E+09 0.00 0.00
Maximum of Months 0.232045E+10 0.736856E+09 0.855382E+09 58774166.93 0.812807E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.577903E+09 0.774388E+09 0.437348E+09 0.00 0.437348E+09 0.00 0.00
February 0.755748E+09 0.561450E+09 0.467574E+09 0.00 0.467574E+09 0.00 0.00
March 0.993551E+09 0.478621E+09 0.617532E+09 10897.63 0.617521E+09 0.00 0.00
April 0.132984E+10 0.222497E+09 0.671400E+09 3833201.69 0.667567E+09 0.00 0.00
May 0.187185E+10 53467106.42 0.787833E+09 32274777.04 0.755559E+09 0.00 0.00
June 0.211660E+10 10428410.16 0.817192E+09 58774166.93 0.758418E+09 0.00 0.00
July 0.227297E+10 24895277.58 0.855382E+09 42575003.16 0.812807E+09 0.00 0.00
August 0.201041E+10 9976421.44 0.757519E+09 7941043.40 0.749578E+09 0.00 0.00
September 0.179782E+10 43715557.27 0.649147E+09 149971.41 0.648997E+09 0.00 0.00
October 0.142021E+10 77175912.54 0.561680E+09 0.00 0.561680E+09 0.00 0.00
November 0.985321E+09 0.299191E+09 0.472630E+09 0.00 0.472630E+09 0.00 0.00
December 0.647096E+09 0.635738E+09 0.432591E+09 0.00 0.432591E+09 0.00 0.00
               
Annual Sum or Average 0.167793E+11 0.319154E+10 0.752783E+10 0.145559E+09 0.738227E+10 0.00 0.00
Minimum of Months 0.577903E+09 9976421.44 0.432591E+09 0.00 0.432591E+09 0.00 0.00
Maximum of Months 0.227297E+10 0.774388E+09 0.855382E+09 58774166.93 0.812807E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.143596E+10 0.645817E+09 0.918453E+09 0.460513E+09 0.457941E+09 0.00 0.00
February 0.146592E+10 0.489103E+09 0.889924E+09 0.406836E+09 0.483088E+09 0.00 0.00
March 0.177523E+10 0.417621E+09 0.108266E+10 0.458255E+09 0.624410E+09 0.00 0.00
April 0.201362E+10 0.223870E+09 0.106984E+10 0.401679E+09 0.668156E+09 0.00 0.00
May 0.221762E+10 69844011.66 0.104091E+10 0.334413E+09 0.706498E+09 0.00 0.00
June 0.231589E+10 16225171.44 0.995419E+09 0.306472E+09 0.688947E+09 0.00 0.00
July 0.255696E+10 30914393.75 0.106075E+10 0.304791E+09 0.755955E+09 0.00 0.00
August 0.231287E+10 19488691.23 0.989915E+09 0.263182E+09 0.726733E+09 0.00 0.00
September 0.227503E+10 44663434.76 0.955897E+09 0.293453E+09 0.662444E+09 0.00 0.00
October 0.209428E+10 85060485.37 0.977720E+09 0.395794E+09 0.581926E+09 0.00 0.00
November 0.160884E+10 0.264971E+09 0.845480E+09 0.350811E+09 0.494669E+09 0.00 0.00
December 0.128484E+10 0.541974E+09 0.785373E+09 0.334964E+09 0.450409E+09 0.00 0.00
               
Annual Sum or Average 0.233571E+11 0.284955E+10 0.116123E+11 0.431116E+10 0.730118E+10 0.00 0.00
Minimum of Months 0.128484E+10 16225171.44 0.785373E+09 0.263182E+09 0.450409E+09 0.00 0.00
Maximum of Months 0.255696E+10 0.645817E+09 0.108266E+10 0.460513E+09 0.755955E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.200147E+10 0.531123E+09 0.124824E+10 0.714162E+09 0.534077E+09 0.00 0.00
February 0.179951E+10 0.364985E+09 0.103603E+10 0.498067E+09 0.537961E+09 0.00 0.00
March 0.172199E+10 0.286772E+09 0.960999E+09 0.309798E+09 0.651201E+09 0.00 0.00
April 0.158922E+10 0.102122E+09 0.750094E+09 0.107821E+09 0.642273E+09 0.00 0.00
May 0.177948E+10 16554625.41 0.689559E+09 24379771.54 0.665179E+09 0.00 0.00
June 0.185701E+10 1256803.30 0.663060E+09 20944997.28 0.642115E+09 0.00 0.00
July 0.200411E+10 7021417.13 0.716623E+09 18150009.08 0.698473E+09 0.00 0.00
August 0.203393E+10 314348.17 0.735659E+09 38316912.53 0.697342E+09 0.00 0.00
September 0.214094E+10 8422915.67 0.819855E+09 0.147619E+09 0.672236E+09 0.00 0.00
October 0.234132E+10 25570185.81 0.104917E+10 0.407317E+09 0.641857E+09 0.00 0.00
November 0.211873E+10 0.178148E+09 0.110115E+10 0.527071E+09 0.574082E+09 0.00 0.00
December 0.200734E+10 0.430057E+09 0.120719E+10 0.668601E+09 0.538594E+09 0.00 0.00
               
Annual Sum or Average 0.233950E+11 0.195235E+10 0.109776E+11 0.348225E+10 0.749539E+10 0.00 0.00
Minimum of Months 0.158922E+10 314348.17 0.663060E+09 18150009.08 0.534077E+09 0.00 0.00
Maximum of Months 0.234132E+10 0.531123E+09 0.124824E+10 0.714162E+09 0.698473E+09 0.00 0.00



Table of Contents

Report: AverageOutdoorConditionsMonthly

For: Environment

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] SITE OUTDOOR AIR WETBULB TEMPERATURE [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] SITE WIND SPEED [m/s] SITE SKY TEMPERATURE [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] SITE RAIN STATUS []
January 19.42 15.96 13.59 3.30 9.49 57.21 169.93 0.03
February 20.87 16.70 13.89 5.53 11.19 68.99 182.59 0.00
March 21.57 17.63 15.09 5.59 12.13 85.97 199.13 0.00
April 24.11 19.68 17.40 4.69 15.31 97.05 212.67 0.01
May 26.41 22.40 20.67 5.05 18.50 110.67 177.92 0.00
June 27.68 24.06 22.67 3.87 20.33 120.35 147.07 0.00
July 28.13 24.25 22.77 2.86 20.30 124.71 163.26 0.00
August 27.97 24.38 23.03 3.45 20.36 120.27 145.14 0.08
September 27.49 23.91 22.56 3.39 20.13 107.67 134.94 0.00
October 26.35 22.68 21.10 3.72 17.49 81.44 160.40 0.04
November 23.59 20.24 18.46 4.39 14.74 70.67 140.11 0.00
December 20.30 17.47 15.75 3.70 12.21 59.50 147.31 0.00
                 
Annual Sum or Average 24.51 20.80 18.94 4.12 16.04 92.16 164.97 0.01
Minimum of Months 19.42 15.96 13.59 2.86 9.49 57.21 134.94 0.00
Maximum of Months 28.13 24.38 23.03 5.59 20.36 124.71 212.67 0.08



Table of Contents

Report: OutdoorConditionsMaximumDryBulbMonthly

For: Environment

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 28.90 02-JAN-14:20 24.35 22.57 2.37 19.46 142.33 666.50
February 29.40 11-FEB-13:00 24.15 22.20 4.60 20.75 178.50 682.00
March 29.40 13-MAR-15:00 22.41 19.40 6.20 21.27 178.00 499.00
April 32.20 17-APR-14:00 19.76 12.80 5.20 21.27 367.00 219.50
May 34.40 22-MAY-12:00 23.24 18.30 5.70 25.99 382.50 457.50
June 32.20 11-JUN-12:00 23.83 20.60 3.60 23.15 181.50 762.50
July 35.60 29-JUL-15:00 24.39 20.00 3.60 25.66 281.50 374.50
August 33.90 23-AUG-12:00 25.44 22.20 5.70 24.50 261.50 640.00
September 32.20 08-SEP-14:00 23.42 20.00 2.10 21.61 221.50 576.00
October 32.20 09-OCT-10:00 23.83 20.60 3.10 25.16 286.50 457.50
November 30.00 17-NOV-14:00 22.20 18.90 4.10 19.35 178.50 412.50
December 28.90 10-DEC-14:20 22.91 20.40 7.87 19.82 162.67 585.17
                 
Annual Sum or Average                
Minimum of Months 28.90   19.76 12.80 2.10 19.35 142.33 219.50
Maximum of Months 35.60   25.44 22.57 7.87 25.99 382.50 762.50



Table of Contents

Report: OutdoorConditionsMinimumDryBulbMonthly

For: Environment

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 9.40 25-JAN-04:00 4.59 -1.7 3.10 -7.3 0.00 0.00
February 5.00 04-FEB-06:00 1.99 -2.8 5.70 -11.9 0.00 0.00
March 6.70 16-MAR-04:00 4.49 1.70 4.60 -9.2 0.00 0.00
April 14.40 02-APR-05:49 13.38 12.70 1.60 0.69 0.00 0.00
May 20.60 01-MAY-04:00 19.45 18.90 1.00 7.95 0.00 0.00
June 22.80 05-JUN-14:00 20.57 19.40 2.10 18.46 245.00 55.00
July 22.80 02-JUL-15:00 21.59 21.10 4.60 20.92 155.00 8.50
August 22.20 12-AUG-06:00 21.85 21.70 2.60 20.40 65.50 0.00
September 22.20 05-SEP-05:00 21.37 21.10 2.60 13.54 0.00 0.00
October 21.10 28-OCT-02:00 20.29 20.00 2.60 8.54 0.00 0.00
November 10.00 27-NOV-02:00 8.82 7.80 3.10 -4.6 0.00 0.00
December 7.80 15-DEC-05:40 5.61 3.13 6.37 -7.8 0.00 0.00
                 
Annual Sum or Average                
Minimum of Months 5.00   1.99 -2.8 1.00 -11.9 0.00 0.00
Maximum of Months 22.80   21.85 21.70 6.37 20.92 245.00 55.00



Table of Contents

Report: OutdoorConditionsMaximumWetBulbMonthly

For: Environment

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

SITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 24.83 02-JAN-13:00 28.90 23.30 1.50 19.87 151.00 613.50
February 24.15 11-FEB-13:00 29.40 22.20 4.60 20.75 178.50 682.00
March 23.83 14-MAR-09:00 26.70 22.80 11.30 19.52 243.50 478.00
April 24.58 01-APR-15:00 28.30 23.30 3.60 16.30 93.50 759.50
May 26.05 28-MAY-14:00 28.90 25.00 5.20 25.66 289.00 98.50
June 26.06 28-JUN-11:00 28.90 25.00 1.50 22.98 404.50 373.50
July 26.39 12-JUL-10:00 30.60 25.00 4.60 23.82 287.50 574.00
August 26.46 21-AUG-15:00 32.20 24.40 3.60 24.50 205.50 366.00
September 26.31 22-SEP-16:00 30.00 25.00 6.20 28.91 54.00 21.00
October 26.52 01-OCT-11:00 29.40 25.60 6.20 28.43 283.50 0.00
November 25.31 04-NOV-13:00 27.80 24.40 2.10 26.48 199.00 3.00
December 24.31 24-DEC-14:00 27.20 23.30 2.10 23.66 201.50 114.50
                 
Annual Sum or Average                
Minimum of Months 23.83   26.70 22.20 1.50 16.30 54.00 0.00
Maximum of Months 26.52   32.20 25.60 11.30 28.91 404.50 759.50



Table of Contents

Report: OutdoorConditionsMaximumDewPointMonthly

For: Environment

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

SITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 23.30 02-JAN-13:00 28.90 24.83 1.50 19.87 151.00 613.50
February 22.80 11-FEB-16:19 27.60 24.09 5.70 18.94 101.33 565.33
March 22.80 14-MAR-09:20 25.57 23.60 9.63 22.18 176.17 527.17
April 23.30 01-APR-14:00 27.80 24.57 5.70 15.76 108.00 831.00
May 25.00 28-MAY-12:00 27.80 25.74 6.70 22.98 249.50 244.50
June 25.00 06-JUN-18:00 27.20 25.59 3.60 23.99 17.50 0.00
July 25.00 12-JUL-03:00 27.20 25.59 1.50 19.70 0.00 0.00
August 25.60 21-AUG-11:00 28.90 26.35 2.60 23.15 567.00 173.50
September 25.00 22-SEP-00:00 27.80 25.31 3.60 20.92 0.00 0.00
October 25.60 01-OCT-11:00 29.40 26.52 6.20 28.43 283.50 0.00
November 24.40 05-NOV-01:19 26.10 24.93 2.03 16.37 0.00 0.00
December 23.90 24-DEC-08:00 23.90 23.90 2.60 17.75 168.50 167.00
                 
Annual Sum or Average                
Minimum of Months 22.80   23.90 23.60 1.50 15.76 0.00 0.00
Maximum of Months 25.60   29.40 26.52 9.63 28.43 567.00 831.00



Table of Contents

Report: OutdoorGroundConditionsMonthly

For: Environment

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

SITE GROUND TEMPERATURE [C] SITE SURFACE GROUND TEMPERATURE [C] SITE DEEP GROUND TEMPERATURE [C] SITE MAINS WATER TEMPERATURE [C] SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] SITE SNOW ON GROUND STATUS []
January 18.00 13.00 16.00 24.73 28.77 0.00
February 18.00 13.00 16.00 25.06 35.04 0.00
March 18.00 13.00 16.00 26.11 42.49 0.00
April 18.00 13.00 16.00 27.63 49.05 0.00
May 18.00 13.00 16.00 29.20 48.15 0.00
June 18.00 13.00 16.00 30.41 45.99 0.00
July 18.00 13.00 16.00 30.92 49.88 0.00
August 18.00 13.00 16.00 30.58 45.60 0.00
September 18.00 13.00 16.00 29.50 40.49 0.00
October 18.00 13.00 16.00 27.97 35.89 0.00
November 18.00 13.00 16.00 26.40 29.31 0.00
December 18.00 13.00 16.00 25.21 26.63 0.00
             
Annual Sum or Average 18.00 13.00 16.00 27.83 39.80 0.00
Minimum of Months 18.00 13.00 16.00 24.73 26.63 0.00
Maximum of Months 18.00 13.00 16.00 30.92 49.88 0.00



Table of Contents

Report: WaterHeaterReportMonthly

For: SWH BOOSTER E WATER HEATER

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] WATER HEATER BURNER HEATING ENERGY [] WATER HEATER GAS CONSUMPTION [] WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] WATER HEATER LOSS DEMAND ENERGY [] WATER HEATER HEAT LOSS ENERGY [J] WATER HEATER TANK TEMPERATURE [C] WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] WATER HEATER SOURCE ENERGY []
January 0.770695E+10 -0.754278E+10 0.00 0.00 744.00 0.00 -164172207.9 81.21 0.00 0.00
February 0.696417E+10 -0.681597E+10 0.00 0.00 672.00 0.00 -148202007.5 81.21 0.00 0.00
March 0.770546E+10 -0.754146E+10 0.00 0.00 744.00 0.00 -164000588.0 81.21 0.00 0.00
April 0.746716E+10 -0.730860E+10 0.00 0.00 720.00 0.00 -158568777.9 81.21 0.00 0.00
May 0.770651E+10 -0.754279E+10 0.00 0.00 744.00 0.00 -163713757.7 81.21 0.00 0.00
June 0.745886E+10 -0.730053E+10 0.00 0.00 720.00 0.00 -158328113.3 81.21 0.00 0.00
July 0.771447E+10 -0.755085E+10 0.00 0.00 744.00 0.00 -163620586.0 81.21 0.00 0.00
August 0.770646E+10 -0.754281E+10 0.00 0.00 744.00 0.00 -163656269.4 81.21 0.00 0.00
September 0.746830E+10 -0.730993E+10 0.00 0.00 720.00 0.00 -158364402.7 81.21 0.00 0.00
October 0.770519E+10 -0.754143E+10 0.00 0.00 744.00 0.00 -163753837.7 81.21 0.00 0.00
November 0.745108E+10 -0.729244E+10 0.00 0.00 720.00 0.00 -158644553.7 81.21 0.00 0.00
December 0.771501E+10 -0.755086E+10 0.00 0.00 744.00 0.00 -164155210.9 81.21 0.00 0.00
                     
Annual Sum or Average 0.907696E+11 -0.888404E+11 0.00 0.00 8760.00 0.00 -0.192918E+10 81.21 0.00 0.00
Minimum of Months 0.696417E+10 -0.755086E+10 0.00 0.00 672.00 0.00 -164172207.9 81.21 0.00 0.00
Maximum of Months 0.771501E+10 -0.681597E+10 0.00 0.00 744.00 0.00 -148202007.5 81.21 0.00 0.00



Table of Contents

Report: WaterHeaterReportMonthly

For: SWH LAUNDRY G WATER HEATER

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] WATER HEATER BURNER HEATING ENERGY [] WATER HEATER GAS CONSUMPTION [] WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] WATER HEATER LOSS DEMAND ENERGY [] WATER HEATER HEAT LOSS ENERGY [J] WATER HEATER TANK TEMPERATURE [C] WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] WATER HEATER SOURCE ENERGY []
January 0.974759E+11 -0.956666E+11 0.00 0.00 744.00 0.00 -0.180925E+10 81.26 0.00 0.00
February 0.875331E+11 -0.858966E+11 0.00 0.00 672.00 0.00 -0.163648E+10 81.25 0.00 0.00
March 0.951460E+11 -0.933318E+11 0.00 0.00 744.00 0.00 -0.181415E+10 81.25 0.00 0.00
April 0.895805E+11 -0.878242E+11 0.00 0.00 720.00 0.00 -0.175632E+10 81.25 0.00 0.00
May 0.898951E+11 -0.880808E+11 0.00 0.00 744.00 0.00 -0.181430E+10 81.25 0.00 0.00
June 0.850167E+11 -0.832614E+11 0.00 0.00 720.00 0.00 -0.175528E+10 81.24 0.00 0.00
July 0.869910E+11 -0.851793E+11 0.00 0.00 744.00 0.00 -0.181170E+10 81.23 0.00 0.00
August 0.875554E+11 -0.857456E+11 0.00 0.00 744.00 0.00 -0.180977E+10 81.25 0.00 0.00
September 0.864983E+11 -0.847484E+11 0.00 0.00 720.00 0.00 -0.174988E+10 81.24 0.00 0.00
October 0.919776E+11 -0.901701E+11 0.00 0.00 744.00 0.00 -0.180750E+10 81.25 0.00 0.00
November 0.915870E+11 -0.898383E+11 0.00 0.00 720.00 0.00 -0.174873E+10 81.25 0.00 0.00
December 0.966521E+11 -0.948449E+11 0.00 0.00 744.00 0.00 -0.180722E+10 81.25 0.00 0.00
                     
Annual Sum or Average 0.108591E+13 -0.106459E+13 0.00 0.00 8760.00 0.00 -0.213206E+11 81.25 0.00 0.00
Minimum of Months 0.850167E+11 -0.956666E+11 0.00 0.00 672.00 0.00 -0.181430E+10 81.23 0.00 0.00
Maximum of Months 0.974759E+11 -0.832614E+11 0.00 0.00 744.00 0.00 -0.163648E+10 81.26 0.00 0.00



Table of Contents

Report: WaterHeaterReportMonthly

For: SWHSYS1 WATER HEATER

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] WATER HEATER BURNER HEATING ENERGY [] WATER HEATER GAS CONSUMPTION [] WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] WATER HEATER LOSS DEMAND ENERGY [] WATER HEATER HEAT LOSS ENERGY [J] WATER HEATER TANK TEMPERATURE [C] WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] WATER HEATER SOURCE ENERGY []
January 0.516122E+11 -0.500351E+11 0.00 0.00 744.00 0.00 -0.157707E+10 58.98 0.00 0.00
February 0.461879E+11 -0.447600E+11 0.00 0.00 672.00 0.00 -0.142791E+10 58.98 0.00 0.00
March 0.496483E+11 -0.480641E+11 0.00 0.00 744.00 0.00 -0.158416E+10 58.98 0.00 0.00
April 0.458655E+11 -0.443315E+11 0.00 0.00 720.00 0.00 -0.153399E+10 58.98 0.00 0.00
May 0.450943E+11 -0.435099E+11 0.00 0.00 744.00 0.00 -0.158442E+10 58.98 0.00 0.00
June 0.419458E+11 -0.404129E+11 0.00 0.00 720.00 0.00 -0.153290E+10 58.97 0.00 0.00
July 0.425608E+11 -0.409791E+11 0.00 0.00 744.00 0.00 -0.158169E+10 58.97 0.00 0.00
August 0.430901E+11 -0.415120E+11 0.00 0.00 744.00 0.00 -0.157804E+10 58.97 0.00 0.00
September 0.432038E+11 -0.416784E+11 0.00 0.00 720.00 0.00 -0.152537E+10 58.98 0.00 0.00
October 0.468636E+11 -0.452886E+11 0.00 0.00 744.00 0.00 -0.157501E+10 58.98 0.00 0.00
November 0.475758E+11 -0.460522E+11 0.00 0.00 720.00 0.00 -0.152358E+10 58.98 0.00 0.00
December 0.508969E+11 -0.493222E+11 0.00 0.00 744.00 0.00 -0.157469E+10 58.98 0.00 0.00
                     
Annual Sum or Average 0.554545E+12 -0.535946E+12 0.00 0.00 8760.00 0.00 -0.185988E+11 58.98 0.00 0.00
Minimum of Months 0.419458E+11 -0.500351E+11 0.00 0.00 672.00 0.00 -0.158442E+10 58.97 0.00 0.00
Maximum of Months 0.516122E+11 -0.404129E+11 0.00 0.00 744.00 0.00 -0.142791E+10 58.98 0.00 0.00



Table of Contents

Report: DaylightingReportMonthly

For: Environment

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER [] DAYLIGHTING LIGHTING POWER MULTIPLIER [] DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME []
January 287.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 304.33 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 362.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 357.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 389.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 388.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 403.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 348.33 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 349.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 323.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 314.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 282.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average 4111.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 282.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 403.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: VAV WITH REHEAT HEATING COIL

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 252198.49 391.22 11-JAN-12:50 0.00 0.00 0.00 0.00 0.00
February 76023.04 126.71 28-FEB-11:50 0.00 0.00 0.00 0.00 0.00
March 3382.24 5.64 01-MAR-10:00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 675292.53 1125.49 15-NOV-09:30 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 1006896.29     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 675292.53 1125.49   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: BASEMENT VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.139949E+10 7650.21 02-JAN-11:35 0.00 0.00 0.00 0.00 0.00
February 0.309514E+10 9309.42 27-FEB-11:35 0.00 0.00 0.00 0.00 0.00
March 0.637394E+10 9508.75 27-MAR-10:35 0.00 0.00 0.00 0.00 0.00
April 0.787060E+10 9568.70 15-APR-10:50 0.00 0.00 0.00 0.00 0.00
May 0.723226E+10 9570.47 31-MAY-10:50 0.00 0.00 0.00 0.00 0.00
June 0.659619E+10 9592.81 11-JUN-10:50 0.00 0.00 0.00 0.00 0.00
July 0.533477E+10 9611.28 23-JUL-10:50 0.00 0.00 0.00 0.00 0.00
August 0.307017E+10 9080.26 01-AUG-10:50 0.00 0.00 0.00 0.00 0.00
September 0.209485E+10 8130.30 11-SEP-10:35 0.00 0.00 0.00 0.00 0.00
October 0.141170E+10 6815.43 03-OCT-10:50 0.00 0.00 0.00 0.00 0.00
November 0.756992E+09 6138.05 04-NOV-10:40 0.00 0.00 0.00 0.00 0.00
December 0.697012E+09 6274.71 10-DEC-11:40 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.459331E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.697012E+09 6138.05   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.787060E+10 9611.28   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: RETAIL_1_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.108222E+10 1640.87 26-JAN-07:05 0.00 0.00 0.00 0.00 0.00
February 0.790755E+09 2030.76 04-FEB-07:30 0.00 0.00 0.00 0.00 0.00
March 0.796413E+09 1894.98 16-MAR-06:05 0.00 0.00 0.00 0.00 0.00
April 0.495300E+09 1123.42 19-APR-06:10 0.00 0.00 0.00 0.00 0.00
May 0.245533E+09 940.31 27-MAY-10:40 0.00 0.00 0.00 0.00 0.00
June 0.114366E+09 844.97 22-JUN-10:35 0.00 0.00 0.00 0.00 0.00
July 57133174.25 617.66 17-JUL-10:40 0.00 0.00 0.00 0.00 0.00
August 0.128413E+09 1101.71 28-AUG-10:40 0.00 0.00 0.00 0.00 0.00
September 76482989.04 647.67 26-SEP-07:30 0.00 0.00 0.00 0.00 0.00
October 0.100522E+09 762.28 31-OCT-10:40 0.00 0.00 0.00 0.00 0.00
November 0.429425E+09 1526.34 13-NOV-06:10 0.00 0.00 0.00 0.00 0.00
December 0.942273E+09 1713.88 27-DEC-07:05 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.525883E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 57133174.25 617.66   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.108222E+10 2030.76   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: RETAIL_2_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.636489E+09 1118.12 31-JAN-11:40 0.00 0.00 0.00 0.00 0.00
February 0.495128E+09 1062.98 03-FEB-11:40 0.00 0.00 0.00 0.00 0.00
March 0.522829E+09 1195.49 21-MAR-10:50 0.00 0.00 0.00 0.00 0.00
April 0.399297E+09 1074.35 26-APR-10:35 0.00 0.00 0.00 0.00 0.00
May 0.356624E+09 1117.53 01-MAY-10:35 0.00 0.00 0.00 0.00 0.00
June 0.317648E+09 1001.72 13-JUN-10:40 0.00 0.00 0.00 0.00 0.00
July 0.276361E+09 926.20 03-JUL-10:40 0.00 0.00 0.00 0.00 0.00
August 0.294142E+09 1006.68 29-AUG-10:35 0.00 0.00 0.00 0.00 0.00
September 0.234253E+09 911.04 06-SEP-10:35 0.00 0.00 0.00 0.00 0.00
October 0.246813E+09 872.23 02-OCT-10:50 0.00 0.00 0.00 0.00 0.00
November 0.352501E+09 999.26 27-NOV-11:40 0.00 0.00 0.00 0.00 0.00
December 0.537868E+09 1051.23 21-DEC-11:50 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.466995E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.234253E+09 872.23   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.636489E+09 1195.49   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: MECH_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.152395E+10 1537.05 25-JAN-11:40 0.00 0.00 0.00 0.00 0.00
February 0.115542E+10 1534.72 04-FEB-11:40 0.00 0.00 0.00 0.00 0.00
March 0.112909E+10 1548.79 21-MAR-10:50 0.00 0.00 0.00 0.00 0.00
April 0.676269E+09 1171.34 19-APR-10:50 0.00 0.00 0.00 0.00 0.00
May 0.299234E+09 1087.62 01-MAY-10:35 0.00 0.00 0.00 0.00 0.00
June 0.115772E+09 746.64 19-JUN-10:50 0.00 0.00 0.00 0.00 0.00
July 85416577.90 700.09 03-JUL-10:50 0.00 0.00 0.00 0.00 0.00
August 0.207393E+09 1001.68 29-AUG-10:50 0.00 0.00 0.00 0.00 0.00
September 0.167646E+09 817.33 05-SEP-10:50 0.00 0.00 0.00 0.00 0.00
October 0.355266E+09 952.95 28-OCT-10:40 0.00 0.00 0.00 0.00 0.00
November 0.713603E+09 1298.29 13-NOV-11:40 0.00 0.00 0.00 0.00 0.00
December 0.127653E+10 1467.88 15-DEC-11:40 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.770559E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 85416577.90 700.09   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.152395E+10 1548.79   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: STORAGE_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.978621E+09 822.07 25-JAN-11:40 0.00 0.00 0.00 0.00 0.00
February 0.741525E+09 820.83 04-FEB-11:40 0.00 0.00 0.00 0.00 0.00
March 0.727035E+09 828.37 21-MAR-10:50 0.00 0.00 0.00 0.00 0.00
April 0.436461E+09 627.09 19-APR-10:50 0.00 0.00 0.00 0.00 0.00
May 0.184810E+09 547.87 01-MAY-10:40 0.00 0.00 0.00 0.00 0.00
June 65560852.41 391.88 19-JUN-10:40 0.00 0.00 0.00 0.00 0.00
July 39966259.11 344.89 03-JUL-10:40 0.00 0.00 0.00 0.00 0.00
August 0.119403E+09 484.81 29-AUG-10:50 0.00 0.00 0.00 0.00 0.00
September 95061787.30 441.46 05-SEP-10:50 0.00 0.00 0.00 0.00 0.00
October 0.214901E+09 470.18 28-OCT-10:40 0.00 0.00 0.00 0.00 0.00
November 0.462226E+09 686.61 13-NOV-11:40 0.00 0.00 0.00 0.00 0.00
December 0.827285E+09 809.58 15-DEC-11:40 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.489286E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 39966259.11 344.89   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.978621E+09 828.37   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: LAUNDRY_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.127679E+11 12499.27 02-JAN-11:50 0.00 0.00 0.00 0.00 0.00
February 0.115369E+11 12543.98 11-FEB-11:50 0.00 0.00 0.00 0.00 0.00
March 0.127636E+11 12558.78 27-MAR-10:35 0.00 0.00 0.00 0.00 0.00
April 0.125991E+11 12637.97 15-APR-10:50 0.00 0.00 0.00 0.00 0.00
May 0.130084E+11 12640.31 31-MAY-10:50 0.00 0.00 0.00 0.00 0.00
June 0.126424E+11 12669.82 11-JUN-10:50 0.00 0.00 0.00 0.00 0.00
July 0.133924E+11 12694.23 23-JUL-10:50 0.00 0.00 0.00 0.00 0.00
August 0.131703E+11 12665.44 19-AUG-10:35 0.00 0.00 0.00 0.00 0.00
September 0.127088E+11 12658.51 24-SEP-10:50 0.00 0.00 0.00 0.00 0.00
October 0.129492E+11 12647.34 07-OCT-10:50 0.00 0.00 0.00 0.00 0.00
November 0.121702E+11 12547.98 03-NOV-10:50 0.00 0.00 0.00 0.00 0.00
December 0.127628E+11 12544.36 09-DEC-11:35 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.152472E+12     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.115369E+11 12499.27   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.133924E+11 12694.23   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CAFE_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.912121E+09 4913.37 30-JAN-11:40 0.00 0.00 0.00 0.00 0.00
February 0.700052E+09 4549.48 06-FEB-11:40 0.00 0.00 0.00 0.00 0.00
March 0.107833E+10 5391.36 16-MAR-08:04 0.00 0.00 0.00 0.00 0.00
April 0.924914E+09 4681.70 28-APR-10:40 0.00 0.00 0.00 0.00 0.00
May 0.882107E+09 4459.03 25-MAY-10:40 0.00 0.00 0.00 0.00 0.00
June 0.772408E+09 4361.60 22-JUN-10:35 0.00 0.00 0.00 0.00 0.00
July 0.526490E+09 4021.93 17-JUL-10:50 0.00 0.00 0.00 0.00 0.00
August 0.545745E+09 5006.69 28-AUG-10:40 0.00 0.00 0.00 0.00 0.00
September 0.223691E+09 3829.32 05-SEP-10:40 0.00 0.00 0.00 0.00 0.00
October 0.195668E+09 4117.47 31-OCT-10:40 0.00 0.00 0.00 0.00 0.00
November 0.412005E+09 4913.48 24-NOV-11:40 0.00 0.00 0.00 0.00 0.00
December 0.897430E+09 4947.26 28-DEC-11:40 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.807096E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.195668E+09 3829.32   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.107833E+10 5391.36   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: LOBBY_FLR_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.467458E+10 16519.06 18-JAN-11:40 0.00 0.00 0.00 0.00 0.00
February 0.394724E+10 17153.25 06-FEB-11:40 0.00 0.00 0.00 0.00 0.00
March 0.542986E+10 18878.73 20-MAR-10:40 0.00 0.00 0.00 0.00 0.00
April 0.494683E+10 16695.31 26-APR-10:40 0.00 0.00 0.00 0.00 0.00
May 0.456742E+10 17488.49 01-MAY-10:35 0.00 0.00 0.00 0.00 0.00
June 0.386442E+10 16199.36 13-JUN-10:35 0.00 0.00 0.00 0.00 0.00
July 0.356592E+10 15396.97 07-JUL-10:50 0.00 0.00 0.00 0.00 0.00
August 0.346371E+10 15193.12 07-AUG-10:35 0.00 0.00 0.00 0.00 0.00
September 0.231685E+10 14711.08 05-SEP-10:50 0.00 0.00 0.00 0.00 0.00
October 0.193699E+10 13854.54 02-OCT-10:50 0.00 0.00 0.00 0.00 0.00
November 0.256256E+10 15301.26 27-NOV-11:40 0.00 0.00 0.00 0.00 0.00
December 0.414701E+10 17341.88 21-DEC-11:40 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.454234E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.193699E+10 13854.54   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.542986E+10 18878.73   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORRIDOR_FLR_3 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.327948E+09 3694.15 26-JAN-07:05 0.00 0.00 0.00 0.00 0.00
February 0.326168E+09 4865.48 04-FEB-07:10 0.00 0.00 0.00 0.00 0.00
March 0.277364E+09 4219.09 20-MAR-10:40 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 583038.44 561.55 13-NOV-07:20 0.00 0.00 0.00 0.00 0.00
December 0.427735E+09 3823.26 21-DEC-11:40 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.135980E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.427735E+09 4865.48   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORRIDOR_FLR_6 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.279335E+10 3960.72 25-JAN-07:05 0.00 0.00 0.00 0.00 0.00
February 0.183106E+10 4642.07 04-FEB-07:10 0.00 0.00 0.00 0.00 0.00
March 0.160896E+10 4256.56 16-MAR-06:30 0.00 0.00 0.00 0.00 0.00
April 0.460010E+09 2212.29 19-APR-06:10 0.00 0.00 0.00 0.00 0.00
May 62803787.38 1627.80 01-MAY-06:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 19915836.49 1283.83 28-AUG-10:50 0.00 0.00 0.00 0.00 0.00
September 4997211.05 507.46 26-SEP-07:40 0.00 0.00 0.00 0.00 0.00
October 26220340.42 919.73 31-OCT-10:50 0.00 0.00 0.00 0.00 0.00
November 0.833416E+09 3386.76 27-NOV-07:05 0.00 0.00 0.00 0.00 0.00
December 0.233358E+10 3836.51 15-DEC-07:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.997432E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.279335E+10 4642.07   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: BANQUET_FLR_6 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.118465E+10 6425.62 26-JAN-11:40 0.00 0.00 0.00 0.00 0.00
February 0.786014E+09 6078.65 03-FEB-11:40 0.00 0.00 0.00 0.00 0.00
March 0.825128E+09 7010.65 16-MAR-10:40 0.00 0.00 0.00 0.00 0.00
April 0.408882E+09 5761.81 03-APR-10:35 0.00 0.00 0.00 0.00 0.00
May 0.235240E+09 5289.17 02-MAY-10:35 0.00 0.00 0.00 0.00 0.00
June 0.158641E+09 4533.30 13-JUN-10:40 0.00 0.00 0.00 0.00 0.00
July 0.139517E+09 4316.61 18-JUL-10:50 0.00 0.00 0.00 0.00 0.00
August 0.198257E+09 4549.92 30-AUG-10:50 0.00 0.00 0.00 0.00 0.00
September 0.217267E+09 4927.45 26-SEP-10:50 0.00 0.00 0.00 0.00 0.00
October 0.339932E+09 5237.32 20-OCT-10:40 0.00 0.00 0.00 0.00 0.00
November 0.567506E+09 5770.42 13-NOV-11:40 0.00 0.00 0.00 0.00 0.00
December 0.100980E+10 6475.97 15-DEC-11:40 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.607084E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.139517E+09 4316.61   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.118465E+10 7010.65   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: DINING_FLR_6 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.777972E+09 6048.70 26-JAN-11:40 0.00 0.00 0.00 0.00 0.00
February 0.478021E+09 5568.97 03-FEB-11:40 0.00 0.00 0.00 0.00 0.00
March 0.522821E+09 6629.88 16-MAR-10:40 0.00 0.00 0.00 0.00 0.00
April 0.223821E+09 5179.05 03-APR-10:40 0.00 0.00 0.00 0.00 0.00
May 0.133502E+09 4679.37 02-MAY-10:40 0.00 0.00 0.00 0.00 0.00
June 0.102489E+09 4343.26 13-JUN-10:40 0.00 0.00 0.00 0.00 0.00
July 97250085.31 4132.67 25-JUL-10:40 0.00 0.00 0.00 0.00 0.00
August 0.120174E+09 4358.00 31-AUG-10:40 0.00 0.00 0.00 0.00 0.00
September 0.133837E+09 4551.44 26-SEP-10:50 0.00 0.00 0.00 0.00 0.00
October 0.204370E+09 4892.72 20-OCT-10:35 0.00 0.00 0.00 0.00 0.00
November 0.334640E+09 5403.64 13-NOV-11:40 0.00 0.00 0.00 0.00 0.00
December 0.667050E+09 6110.39 15-DEC-11:40 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.379595E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 97250085.31 4132.67   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.777972E+09 6629.88   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: KITCHEN_FLR_6 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.778503E+09 3868.65 25-JAN-04:00 0.00 0.00 0.00 0.00 0.00
February 0.616918E+09 4331.51 04-FEB-04:00 0.00 0.00 0.00 0.00 0.00
March 0.535062E+09 3868.78 16-MAR-03:00 0.00 0.00 0.00 0.00 0.00
April 0.300051E+09 2710.84 19-APR-03:00 0.00 0.00 0.00 0.00 0.00
May 0.169172E+09 2024.82 01-MAY-03:00 0.00 0.00 0.00 0.00 0.00
June 77510333.73 1355.81 19-JUN-03:00 0.00 0.00 0.00 0.00 0.00
July 78896804.24 1355.81 15-JUL-03:00 0.00 0.00 0.00 0.00 0.00
August 0.102763E+09 1622.29 29-AUG-03:00 0.00 0.00 0.00 0.00 0.00
September 0.101669E+09 1463.87 06-SEP-03:00 0.00 0.00 0.00 0.00 0.00
October 0.178733E+09 1674.16 28-OCT-03:00 0.00 0.00 0.00 0.00 0.00
November 0.412839E+09 3510.38 27-NOV-04:00 0.00 0.00 0.00 0.00 0.00
December 0.698823E+09 3869.07 21-DEC-04:00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.405094E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 77510333.73 1355.81   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.778503E+09 4331.51   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: FLR_3_DOAS HEATING COIL

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 16088.21 0.55 03-JAN-09:00 0.00 0.00 0.00 0.00 0.00
February 10164.89 0.54 24-FEB-18:35 0.00 0.00 0.00 0.00 0.00
March 10841.74 4.55 02-MAR-16:07 0.00 0.00 0.00 0.00 0.00
April 10483.25 0.54 30-APR-07:30 0.00 0.00 0.00 0.00 0.00
May 9159.30 0.55 11-MAY-20:50 0.00 0.00 0.00 0.00 0.00
June 6740.83 0.54 20-JUN-20:50 0.00 0.00 0.00 0.00 0.00
July 8790.63 0.54 29-JUL-04:00 0.00 0.00 0.00 0.00 0.00
August 5251.23 0.54 20-AUG-20:20 0.00 0.00 0.00 0.00 0.00
September 9623.38 0.54 04-SEP-07:03 0.00 0.00 0.00 0.00 0.00
October 7210.07 0.55 26-OCT-05:30 0.00 0.00 0.00 0.00 0.00
November 12189.19 0.54 01-NOV-16:30 0.00 0.00 0.00 0.00 0.00
December 15792.48 0.54 01-DEC-14:30 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 122335.18     0.00 0.00 0.00 0.00 0.00
Minimum of Months 5251.23 0.54   0.00 0.00 0.00 0.00 0.00
Maximum of Months 16088.21 4.55   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_1_FLR_3 FAN COIL HEATING COIL

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 44069758.06 2542.22 25-JAN-16:04 0.00 0.00 0.00 0.00 0.00
February 60367991.06 2944.00 03-FEB-16:04 0.00 0.00 0.00 0.00 0.00
March 34090633.07 3762.67 16-MAR-08:62 0.00 0.00 0.00 0.00 0.00
April 4882101.47 2677.80 29-APR-08:05 0.00 0.00 0.00 0.00 0.00
May 3407825.82 2785.93 08-MAY-08:04 0.00 0.00 0.00 0.00 0.00
June 1884180.83 2255.73 19-JUN-08:05 0.00 0.00 0.00 0.00 0.00
July 467990.42 1614.76 03-JUL-08:05 0.00 0.00 0.00 0.00 0.00
August 2130807.12 2310.31 29-AUG-08:05 0.00 0.00 0.00 0.00 0.00
September 2188591.24 2106.57 28-SEP-08:05 0.00 0.00 0.00 0.00 0.00
October 3250616.90 2712.57 18-OCT-08:04 0.00 0.00 0.00 0.00 0.00
November 14656381.22 2489.92 27-NOV-09:03 0.00 0.00 0.00 0.00 0.00
December 53915591.21 2736.92 28-DEC-16:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.225312E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 467990.42 1614.76   0.00 0.00 0.00 0.00 0.00
Maximum of Months 60367991.06 3762.67   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_2_FLR_3 FAN COIL HEATING COIL

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.105859E+09 3775.70 25-JAN-09:02 0.00 0.00 0.00 0.00 0.00
February 92736206.54 3788.51 04-FEB-09:02 0.00 0.00 0.00 0.00 0.00
March 55463987.68 3797.22 16-MAR-08:62 0.00 0.00 0.00 0.00 0.00
April 5133334.84 2646.09 29-APR-08:05 0.00 0.00 0.00 0.00 0.00
May 3395843.44 2842.75 08-MAY-08:04 0.00 0.00 0.00 0.00 0.00
June 1531000.80 2148.81 19-JUN-08:05 0.00 0.00 0.00 0.00 0.00
July 267373.18 1406.93 03-JUL-08:05 0.00 0.00 0.00 0.00 0.00
August 2367438.21 2287.59 29-AUG-08:05 0.00 0.00 0.00 0.00 0.00
September 2803186.54 2175.63 07-SEP-08:05 0.00 0.00 0.00 0.00 0.00
October 5437431.97 2762.97 18-OCT-08:04 0.00 0.00 0.00 0.00 0.00
November 25660037.86 2935.63 28-NOV-19:04 0.00 0.00 0.00 0.00 0.00
December 0.114953E+09 3768.38 15-DEC-09:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.415607E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 267373.18 1406.93   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.114953E+09 3797.22   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:03 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:03 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:03 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 82664286.91 21830.44 24-JAN-16:03 0.00 0.00 0.00 0.00 0.00
February 92300133.80 21770.85 03-FEB-16:03 0.00 0.00 0.00 0.00 0.00
March 69788894.48 21815.37 19-MAR-15:05 0.00 0.00 0.00 0.00 0.00
April 40058958.48 21821.55 20-APR-08:05 0.00 0.00 0.00 0.00 0.00
May 20751402.58 16532.94 11-MAY-08:06 0.00 0.00 0.00 0.00 0.00
June 26648236.23 15235.94 09-JUN-08:07 0.00 0.00 0.00 0.00 0.00
July 26111861.57 12941.00 12-JUL-08:07 0.00 0.00 0.00 0.00 0.00
August 20446252.15 15703.12 12-AUG-18:07 0.00 0.00 0.00 0.00 0.00
September 6909071.14 8799.75 11-SEP-08:07 0.00 0.00 0.00 0.00 0.00
October 33918527.13 14700.87 10-OCT-18:07 0.00 0.00 0.00 0.00 0.00
November 58904476.33 21626.33 15-NOV-09:05 0.00 0.00 0.00 0.00 0.00
December 73228066.31 21843.04 15-DEC-16:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.551730E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 6909071.14 8799.75   0.00 0.00 0.00 0.00 0.00
Maximum of Months 92300133.80 21843.04   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_5_FLR_3 FAN COIL HEATING COIL

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 51508306.23 2790.09 25-JAN-16:04 0.00 0.00 0.00 0.00 0.00
February 58373055.27 2232.83 19-FEB-09:05 0.00 0.00 0.00 0.00 0.00
March 30027359.90 3062.44 16-MAR-15:04 0.00 0.00 0.00 0.00 0.00
April 804085.23 2624.61 30-APR-08:05 0.00 0.00 0.00 0.00 0.00
May 421227.38 2177.54 25-MAY-08:05 0.00 0.00 0.00 0.00 0.00
June 123019.48 1230.19 15-JUN-08:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 274333.01 2298.83 28-AUG-08:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 173171.27 1333.45 31-OCT-08:05 0.00 0.00 0.00 0.00 0.00
November 13182313.09 1789.98 27-NOV-19:05 0.00 0.00 0.00 0.00 0.00
December 64317039.17 2501.47 20-DEC-19:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.219204E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 64317039.17 3062.44   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_6_FLR_3 FAN COIL HEATING COIL

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.116279E+09 3075.49 24-JAN-16:03 0.00 0.00 0.00 0.00 0.00
February 87068598.94 2658.54 03-FEB-16:03 0.00 0.00 0.00 0.00 0.00
March 47130942.14 2743.91 16-MAR-18:03 0.00 0.00 0.00 0.00 0.00
April 939065.85 2593.60 30-APR-08:05 0.00 0.00 0.00 0.00 0.00
May 483800.67 2414.11 25-MAY-08:05 0.00 0.00 0.00 0.00 0.00
June 126521.31 1265.21 15-JUN-08:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 333587.02 2249.83 28-AUG-08:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 382485.15 2098.55 18-OCT-08:04 0.00 0.00 0.00 0.00 0.00
November 22729377.54 2694.09 29-NOV-09:05 0.00 0.00 0.00 0.00 0.00
December 0.129726E+09 2766.44 28-DEC-16:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.405199E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.129726E+09 3075.49   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_1_FLR_6 FAN COIL HEATING COIL

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 27271321.69 841.47 25-JAN-09:02 0.00 0.00 0.00 0.00 0.00
February 26891065.91 1140.15 04-FEB-09:02 0.00 0.00 0.00 0.00 0.00
March 17527491.08 1151.12 16-MAR-08:62 0.00 0.00 0.00 0.00 0.00
April 1187614.39 693.84 09-APR-08:04 0.00 0.00 0.00 0.00 0.00
May 781938.44 809.32 08-MAY-08:04 0.00 0.00 0.00 0.00 0.00
June 430544.67 468.73 22-JUN-08:05 0.00 0.00 0.00 0.00 0.00
July 107381.23 375.84 03-JUL-08:05 0.00 0.00 0.00 0.00 0.00
August 535368.47 580.73 12-AUG-08:05 0.00 0.00 0.00 0.00 0.00
September 569814.53 492.98 26-SEP-08:05 0.00 0.00 0.00 0.00 0.00
October 887539.84 797.21 18-OCT-08:04 0.00 0.00 0.00 0.00 0.00
November 8133470.63 621.94 29-NOV-09:05 0.00 0.00 0.00 0.00 0.00
December 29719232.03 1009.11 15-DEC-09:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.114043E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 107381.23 375.84   0.00 0.00 0.00 0.00 0.00
Maximum of Months 29719232.03 1151.12   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_2_FLR_6 FAN COIL HEATING COIL

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 56690300.28 1153.02 25-JAN-09:02 0.00 0.00 0.00 0.00 0.00
February 40591574.99 1158.83 04-FEB-09:02 0.00 0.00 0.00 0.00 0.00
March 26376275.58 1161.83 16-MAR-08:62 0.00 0.00 0.00 0.00 0.00
April 1260652.42 862.51 09-APR-08:04 0.00 0.00 0.00 0.00 0.00
May 731251.76 810.64 08-MAY-08:04 0.00 0.00 0.00 0.00 0.00
June 332934.70 436.45 19-JUN-08:05 0.00 0.00 0.00 0.00 0.00
July 71212.36 343.17 03-JUL-08:05 0.00 0.00 0.00 0.00 0.00
August 557605.02 592.39 12-AUG-08:05 0.00 0.00 0.00 0.00 0.00
September 678325.21 484.44 12-SEP-08:05 0.00 0.00 0.00 0.00 0.00
October 1321306.74 759.76 18-OCT-08:04 0.00 0.00 0.00 0.00 0.00
November 12838823.68 1136.42 13-NOV-09:02 0.00 0.00 0.00 0.00 0.00
December 56555310.61 1151.71 15-DEC-09:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.198006E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 71212.36 343.17   0.00 0.00 0.00 0.00 0.00
Maximum of Months 56690300.28 1161.83   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 10357712.65 2813.43 09-JAN-09:05 0.00 0.00 0.00 0.00 0.00
February 37351687.82 2129.69 04-FEB-09:05 0.00 0.00 0.00 0.00 0.00
March 21803445.53 4462.58 16-MAR-08:62 0.00 0.00 0.00 0.00 0.00
April 4285076.56 3804.93 21-APR-08:05 0.00 0.00 0.00 0.00 0.00
May 1097598.96 3459.33 01-MAY-08:05 0.00 0.00 0.00 0.00 0.00
June 149866.92 718.75 13-JUN-08:06 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 544113.96 3335.72 28-AUG-08:05 0.00 0.00 0.00 0.00 0.00
September 157626.50 827.84 15-SEP-08:05 0.00 0.00 0.00 0.00 0.00
October 60305.13 703.56 02-OCT-08:06 0.00 0.00 0.00 0.00 0.00
November 4132993.45 3257.29 12-NOV-16:05 0.00 0.00 0.00 0.00 0.00
December 11001164.85 2756.09 28-DEC-16:05 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 90941592.32     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 37351687.82 4462.58   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: VAV WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.588169E+12 0.382147E+12 578284.50 04-JAN-18:00 201566.05 0.82
February 0.00 0.00 0.619413E+12 0.419633E+12 608170.58 11-FEB-11:35 310069.82 0.84
March 0.00 0.00 0.757114E+12 0.501126E+12 596268.05 14-MAR-10:35 292360.50 0.86
April 0.00 0.00 0.911343E+12 0.600445E+12 603046.69 01-APR-17:12 300779.69 1.00
May 0.00 0.00 0.121938E+13 0.692135E+12 695941.36 28-MAY-10:35 323584.77 1.00
June 0.00 0.00 0.136731E+13 0.705696E+12 702211.90 10-JUN-10:35 345048.33 1.00
July 0.00 0.00 0.144135E+13 0.745435E+12 735216.74 29-JUL-10:35 365963.13 1.00
August 0.00 0.00 0.144829E+13 0.735571E+12 729874.45 20-AUG-10:35 353888.61 1.00
September 0.00 0.00 0.135531E+13 0.702928E+12 701187.95 06-SEP-10:35 331498.84 1.00
October 0.00 0.00 0.125873E+13 0.692163E+12 719322.49 04-OCT-10:35 313962.95 1.00
November 0.00 0.00 0.100361E+13 0.565162E+12 655600.26 05-NOV-10:35 285984.77 0.95
December 0.00 0.00 0.733564E+12 0.437330E+12 638135.34 24-DEC-21:40 221086.16 0.88
                 
Annual Sum or Average 0.00 0.00 0.127036E+14 0.717977E+13       0.95
Minimum of Months 0.00 0.00 0.588169E+12 0.382147E+12 578284.50   201566.05 0.82
Maximum of Months 0.00 0.00 0.144829E+13 0.745435E+12 735216.74   365963.13 1.00



Table of Contents

Report: CoilReportMonthly

For: FLR_3_DOAS COOLING COIL

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.678594E+11 0.426226E+11 69237.45 07-JAN-03:30 25566.96 0.78
February 0.00 0.00 0.730381E+11 0.481752E+11 68133.31 11-FEB-19:00 28972.18 0.84
March 0.00 0.00 0.884958E+11 0.577357E+11 71113.56 19-MAR-07:30 26973.70 0.85
April 0.00 0.00 0.104580E+12 0.690403E+11 71819.61 26-APR-14:30 28370.87 1.00
May 0.00 0.00 0.131409E+12 0.777571E+11 80981.70 28-MAY-18:00 29080.91 1.00
June 0.00 0.00 0.141915E+12 0.777573E+11 66955.40 28-JUN-12:00 32703.90 1.00
July 0.00 0.00 0.147828E+12 0.811791E+11 78320.79 02-JUL-17:10 27791.28 1.00
August 0.00 0.00 0.150052E+12 0.808641E+11 78921.70 28-AUG-14:10 28260.66 1.00
September 0.00 0.00 0.140049E+12 0.773878E+11 64377.90 06-SEP-11:00 33420.12 1.00
October 0.00 0.00 0.134316E+12 0.776926E+11 75497.39 01-OCT-07:10 27515.07 1.00
November 0.00 0.00 0.111940E+12 0.645080E+11 78941.50 08-NOV-09:00 27796.02 0.95
December 0.00 0.00 0.842073E+11 0.497458E+11 82125.11 24-DEC-08:17 27737.47 0.87
                 
Annual Sum or Average 0.00 0.00 0.137569E+13 0.804466E+12       0.94
Minimum of Months 0.00 0.00 0.678594E+11 0.426226E+11 64377.90   25566.96 0.78
Maximum of Months 0.00 0.00 0.150052E+12 0.811791E+11 82125.11   33420.12 1.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_1_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.549733E+10 0.269398E+10 20555.66 07-JAN-09:01 11635.50 0.74
February 0.00 0.00 0.632953E+10 0.334204E+10 19741.34 02-FEB-09:02 11826.15 0.80
March 0.00 0.00 0.817434E+10 0.447441E+10 20369.81 19-MAR-08:62 10852.65 0.81
April 0.00 0.00 0.101237E+11 0.577476E+10 18893.56 16-APR-08:62 12519.47 0.92
May 0.00 0.00 0.122213E+11 0.702649E+10 19719.93 24-MAY-18:02 12068.51 0.94
June 0.00 0.00 0.128607E+11 0.739887E+10 18550.38 13-JUN-08:61 12638.09 0.95
July 0.00 0.00 0.143713E+11 0.855364E+10 18163.38 24-JUL-08:62 12932.31 0.96
August 0.00 0.00 0.137867E+11 0.805387E+10 20220.47 12-AUG-08:62 11669.69 0.94
September 0.00 0.00 0.133697E+11 0.779853E+10 18652.03 16-SEP-08:62 12646.74 0.95
October 0.00 0.00 0.126403E+11 0.729565E+10 19352.86 01-OCT-08:62 12268.67 0.94
November 0.00 0.00 0.921094E+10 0.492251E+10 19340.16 24-NOV-09:02 11431.30 0.88
December 0.00 0.00 0.668336E+10 0.335713E+10 20412.67 23-DEC-09:02 11321.18 0.80
                 
Annual Sum or Average 0.00 0.00 0.125269E+12 0.706919E+11       0.88
Minimum of Months 0.00 0.00 0.549733E+10 0.269398E+10 18163.38   10852.65 0.74
Maximum of Months 0.00 0.00 0.143713E+11 0.855364E+10 20555.66   12932.31 0.96



Table of Contents

Report: CoilReportMonthly

For: ROOM_2_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.360931E+10 0.149835E+10 20730.55 07-JAN-09:01 11595.94 0.62
February 0.00 0.00 0.486216E+10 0.230758E+10 19471.05 18-FEB-09:01 12478.48 0.73
March 0.00 0.00 0.703085E+10 0.363766E+10 20542.18 19-MAR-08:62 10906.80 0.76
April 0.00 0.00 0.952975E+10 0.531652E+10 19112.25 16-APR-08:62 12614.75 0.91
May 0.00 0.00 0.122123E+11 0.701907E+10 20268.48 24-MAY-18:02 11981.64 0.94
June 0.00 0.00 0.130636E+11 0.754903E+10 18647.63 13-JUN-08:61 12884.20 0.95
July 0.00 0.00 0.144997E+11 0.863567E+10 18473.74 02-JUL-18:02 12967.06 0.96
August 0.00 0.00 0.135233E+11 0.779757E+10 20299.54 12-AUG-08:62 11848.48 0.94
September 0.00 0.00 0.125306E+11 0.708070E+10 18869.74 16-SEP-08:62 12741.60 0.94
October 0.00 0.00 0.110591E+11 0.598321E+10 19526.75 01-OCT-08:62 12387.59 0.93
November 0.00 0.00 0.747555E+10 0.360117E+10 19491.81 24-NOV-09:02 11441.14 0.84
December 0.00 0.00 0.484260E+10 0.213318E+10 20291.47 23-DEC-09:02 11402.96 0.69
                 
Annual Sum or Average 0.00 0.00 0.114239E+12 0.625597E+11       0.85
Minimum of Months 0.00 0.00 0.360931E+10 0.149835E+10 18473.74   10906.80 0.62
Maximum of Months 0.00 0.00 0.144997E+11 0.863567E+10 20730.55   12967.06 0.96



Table of Contents

Report: CoilReportMonthly

For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.455826E+11 0.283158E+11 56760.76 02-JAN-14:30 44761.69 0.75
February 0.00 0.00 0.414757E+11 0.251492E+11 50980.70 11-FEB-14:20 36687.16 0.78
March 0.00 0.00 0.422313E+11 0.226321E+11 45455.82 04-MAR-20:20 23912.99 0.82
April 0.00 0.00 0.436538E+11 0.221405E+11 39866.44 07-APR-21:00 23090.45 0.95
May 0.00 0.00 0.501381E+11 0.247021E+11 42893.49 25-MAY-20:50 18106.54 0.99
June 0.00 0.00 0.547656E+11 0.278189E+11 47398.96 18-JUN-20:20 21587.74 1.00
July 0.00 0.00 0.612697E+11 0.332071E+11 42047.07 29-JUL-19:10 35459.18 1.00
August 0.00 0.00 0.610536E+11 0.333345E+11 41340.99 20-AUG-20:03 33042.52 1.00
September 0.00 0.00 0.681249E+11 0.411311E+11 48350.88 30-SEP-13:30 33294.14 1.00
October 0.00 0.00 0.720983E+11 0.447246E+11 52569.55 25-OCT-12:30 40335.11 1.00
November 0.00 0.00 0.595191E+11 0.363804E+11 55189.48 07-NOV-13:30 44603.36 0.92
December 0.00 0.00 0.486168E+11 0.294926E+11 56667.85 09-DEC-12:30 44721.57 0.81
                 
Annual Sum or Average 0.00 0.00 0.648529E+12 0.369029E+12       0.92
Minimum of Months 0.00 0.00 0.414757E+11 0.221405E+11 39866.44   18106.54 0.75
Maximum of Months 0.00 0.00 0.720983E+11 0.447246E+11 56760.76   44761.69 1.00



Table of Contents

Report: CoilReportMonthly

For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.449269E+11 0.235372E+11 138891.19 07-JAN-09:01 76922.13 0.65
February 0.00 0.00 0.495889E+11 0.280714E+11 129388.70 18-FEB-19:02 81120.76 0.66
March 0.00 0.00 0.615357E+11 0.359941E+11 137864.32 19-MAR-08:62 72547.03 0.67
April 0.00 0.00 0.736779E+11 0.456159E+11 125820.00 29-APR-18:02 82139.02 0.75
May 0.00 0.00 0.914833E+11 0.602573E+11 138635.74 24-MAY-18:02 76960.68 0.83
June 0.00 0.00 0.978750E+11 0.662440E+11 117525.29 23-JUN-15:02 88487.41 0.87
July 0.00 0.00 0.103723E+12 0.704427E+11 126891.49 02-JUL-18:02 83429.01 0.89
August 0.00 0.00 0.969086E+11 0.644793E+11 135273.80 12-AUG-08:62 78284.94 0.85
September 0.00 0.00 0.919014E+11 0.608522E+11 117910.02 16-SEP-08:62 88024.07 0.85
October 0.00 0.00 0.832404E+11 0.524719E+11 128888.42 01-OCT-08:62 82232.20 0.78
November 0.00 0.00 0.655798E+11 0.386498E+11 128391.06 24-NOV-09:02 75110.10 0.71
December 0.00 0.00 0.511800E+11 0.272134E+11 133545.72 23-DEC-09:02 77936.81 0.70
                 
Annual Sum or Average 0.00 0.00 0.911621E+12 0.573829E+12       0.77
Minimum of Months 0.00 0.00 0.449269E+11 0.235372E+11 117525.29   72547.03 0.65
Maximum of Months 0.00 0.00 0.103723E+12 0.704427E+11 138891.19   88487.41 0.89



Table of Contents

Report: CoilReportMonthly

For: ROOM_5_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.579143E+10 0.303351E+10 18372.60 07-JAN-09:01 10640.23 0.76
February 0.00 0.00 0.634637E+10 0.342013E+10 17500.21 18-FEB-09:01 11140.89 0.82
March 0.00 0.00 0.803494E+10 0.441324E+10 18429.89 19-MAR-08:62 9820.01 0.83
April 0.00 0.00 0.100700E+11 0.571153E+10 16793.66 29-APR-08:62 11511.07 0.95
May 0.00 0.00 0.122725E+11 0.709469E+10 17831.74 24-MAY-18:02 10902.33 0.96
June 0.00 0.00 0.135563E+11 0.805376E+10 16021.98 21-JUN-18:02 11895.94 0.97
July 0.00 0.00 0.148119E+11 0.905932E+10 16503.21 02-JUL-18:02 11624.09 0.97
August 0.00 0.00 0.138300E+11 0.820418E+10 18285.23 12-AUG-08:62 10552.77 0.95
September 0.00 0.00 0.138651E+11 0.840389E+10 16638.77 05-SEP-08:62 11530.79 0.97
October 0.00 0.00 0.128383E+11 0.754117E+10 17513.28 01-OCT-08:62 11074.38 0.96
November 0.00 0.00 0.927716E+10 0.505158E+10 17481.22 24-NOV-09:02 10315.80 0.90
December 0.00 0.00 0.625108E+10 0.315066E+10 18444.89 23-DEC-09:02 10226.73 0.80
                 
Annual Sum or Average 0.00 0.00 0.126945E+12 0.731377E+11       0.90
Minimum of Months 0.00 0.00 0.579143E+10 0.303351E+10 16021.98   9820.01 0.76
Maximum of Months 0.00 0.00 0.148119E+11 0.905932E+10 18444.89   11895.94 0.97



Table of Contents

Report: CoilReportMonthly

For: ROOM_6_FLR_3 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.389451E+10 0.173267E+10 18642.24 07-JAN-09:01 10658.81 0.64
February 0.00 0.00 0.484168E+10 0.239041E+10 17557.14 18-FEB-09:01 11271.98 0.75
March 0.00 0.00 0.685468E+10 0.359389E+10 18563.07 19-MAR-08:62 9859.13 0.78
April 0.00 0.00 0.946399E+10 0.527368E+10 17000.77 29-APR-18:02 11513.40 0.95
May 0.00 0.00 0.122603E+11 0.707278E+10 18307.32 24-MAY-18:02 10809.55 0.96
June 0.00 0.00 0.137561E+11 0.821296E+10 16125.98 21-JUN-18:02 12005.82 0.97
July 0.00 0.00 0.149366E+11 0.914412E+10 16773.25 02-JUL-18:02 11645.96 0.97
August 0.00 0.00 0.135635E+11 0.790627E+10 18332.99 12-AUG-08:62 10700.31 0.95
September 0.00 0.00 0.130218E+11 0.753970E+10 16839.37 05-SEP-08:62 11587.60 0.96
October 0.00 0.00 0.112438E+11 0.619810E+10 17634.97 01-OCT-08:62 11174.38 0.95
November 0.00 0.00 0.753874E+10 0.385848E+10 17597.36 24-NOV-09:02 10312.99 0.85
December 0.00 0.00 0.441693E+10 0.196275E+10 18308.78 23-DEC-09:02 10288.68 0.68
                 
Annual Sum or Average 0.00 0.00 0.115793E+12 0.648858E+11       0.87
Minimum of Months 0.00 0.00 0.389451E+10 0.173267E+10 16125.98   9859.13 0.64
Maximum of Months 0.00 0.00 0.149366E+11 0.914412E+10 18642.24   12005.82 0.97



Table of Contents

Report: CoilReportMonthly

For: ROOM_1_FLR_6 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.144156E+10 0.717942E+09 5663.35 07-JAN-09:01 2996.28 0.71
February 0.00 0.00 0.171243E+10 0.919900E+09 5429.47 02-FEB-09:02 3083.37 0.80
March 0.00 0.00 0.224357E+10 0.124199E+10 5599.15 19-MAR-08:62 2791.59 0.80
April 0.00 0.00 0.282257E+10 0.164174E+10 5186.85 16-APR-08:62 3254.47 0.93
May 0.00 0.00 0.342546E+10 0.201743E+10 5334.89 24-MAY-18:02 3172.55 0.95
June 0.00 0.00 0.360329E+10 0.212289E+10 5046.45 13-JUN-08:61 3328.62 0.95
July 0.00 0.00 0.402515E+10 0.246315E+10 4915.73 24-JUL-08:62 3407.45 0.96
August 0.00 0.00 0.382786E+10 0.229348E+10 5581.22 12-AUG-08:62 2988.79 0.95
September 0.00 0.00 0.368803E+10 0.220648E+10 5143.77 16-SEP-08:62 3277.30 0.95
October 0.00 0.00 0.343720E+10 0.202046E+10 5322.42 01-OCT-08:62 3179.27 0.95
November 0.00 0.00 0.247786E+10 0.134372E+10 5327.78 24-NOV-09:02 2930.11 0.89
December 0.00 0.00 0.177414E+10 0.910788E+09 5645.65 23-DEC-09:02 2916.18 0.77
                 
Annual Sum or Average 0.00 0.00 0.344791E+11 0.199000E+11       0.88
Minimum of Months 0.00 0.00 0.144156E+10 0.717942E+09 4915.73   2791.59 0.71
Maximum of Months 0.00 0.00 0.402515E+10 0.246315E+10 5663.35   3407.45 0.96



Table of Contents

Report: CoilReportMonthly

For: ROOM_2_FLR_6 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.945329E+09 0.402077E+09 5714.15 07-JAN-09:01 2991.13 0.59
February 0.00 0.00 0.132540E+10 0.640397E+09 5339.79 18-FEB-09:01 3237.97 0.72
March 0.00 0.00 0.194328E+10 0.101694E+10 5641.16 19-MAR-08:62 2804.83 0.76
April 0.00 0.00 0.266844E+10 0.151290E+10 5243.10 16-APR-08:62 3275.25 0.92
May 0.00 0.00 0.342405E+10 0.201205E+10 5486.29 24-MAY-18:02 3140.34 0.95
June 0.00 0.00 0.365590E+10 0.216267E+10 5059.37 13-JUN-08:61 3380.71 0.96
July 0.00 0.00 0.405891E+10 0.248440E+10 4948.22 15-JUL-08:62 3450.12 0.96
August 0.00 0.00 0.376171E+10 0.222505E+10 5600.35 12-AUG-08:62 3033.45 0.95
September 0.00 0.00 0.347283E+10 0.199981E+10 5201.33 16-SEP-08:62 3296.98 0.95
October 0.00 0.00 0.302530E+10 0.165297E+10 5363.71 01-OCT-08:62 3208.21 0.93
November 0.00 0.00 0.202302E+10 0.984997E+09 5365.09 24-NOV-09:02 2931.20 0.85
December 0.00 0.00 0.129114E+10 0.579014E+09 5598.75 23-DEC-09:02 2941.53 0.67
                 
Annual Sum or Average 0.00 0.00 0.315953E+11 0.176733E+11       0.85
Minimum of Months 0.00 0.00 0.945329E+09 0.402077E+09 4948.22   2804.83 0.59
Maximum of Months 0.00 0.00 0.405891E+10 0.248440E+10 5714.15   3450.12 0.96



Table of Contents

Report: CoilReportMonthly

For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.129891E+11 0.838847E+10 23619.09 07-JAN-09:01 12783.41 0.83
February 0.00 0.00 0.124059E+11 0.792331E+10 22992.84 02-FEB-09:02 13134.77 0.85
March 0.00 0.00 0.133315E+11 0.818121E+10 23720.52 19-MAR-08:62 11917.37 0.83
April 0.00 0.00 0.142435E+11 0.867965E+10 21764.66 16-APR-08:62 13751.31 0.92
May 0.00 0.00 0.163781E+11 0.998314E+10 23176.37 24-MAY-18:02 12985.23 0.93
June 0.00 0.00 0.175109E+11 0.109835E+11 20430.00 13-JUN-08:61 14365.82 0.94
July 0.00 0.00 0.191637E+11 0.122875E+11 21396.89 02-JUL-18:02 13958.14 0.95
August 0.00 0.00 0.188724E+11 0.121001E+11 23868.60 12-AUG-08:62 12627.34 0.94
September 0.00 0.00 0.199313E+11 0.132801E+11 20813.32 28-SEP-08:62 14242.15 0.95
October 0.00 0.00 0.204146E+11 0.138096E+11 22524.73 01-OCT-08:62 13339.75 0.95
November 0.00 0.00 0.168684E+11 0.110169E+11 22609.12 24-NOV-09:02 12428.47 0.92
December 0.00 0.00 0.141203E+11 0.890404E+10 23768.39 23-DEC-09:02 12684.80 0.87
                 
Annual Sum or Average 0.00 0.00 0.196230E+12 0.125538E+12       0.91
Minimum of Months 0.00 0.00 0.124059E+11 0.792331E+10 20430.00   11917.37 0.83
Maximum of Months 0.00 0.00 0.204146E+11 0.138096E+11 23868.60   14365.82 0.95



Table of Contents

Report: PlantLoopDemandReportMonthly

For: HEATSYS1

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:03 11233.28 60722.14 18-JAN-11:40
February 0.00 0.00 01-FEB-00:03 11068.74 67096.09 06-FEB-11:40
March 0.00 0.00 01-MAR-00:03 12181.84 76117.71 20-MAR-10:40
April 0.00 0.00 01-APR-00:10 11402.04 67094.71 18-APR-10:35
May 0.00 0.00 01-MAY-00:10 10147.67 62175.45 01-MAY-10:35
June 0.00 0.00 01-JUN-00:10 9509.79 60608.83 13-JUN-10:35
July 0.00 0.00 01-JUL-00:10 8744.58 57541.44 07-JUL-10:35
August 0.00 0.00 01-AUG-00:10 7948.03 56734.21 29-AUG-10:35
September 0.00 0.00 01-SEP-00:10 7034.27 53503.53 05-SEP-10:40
October 0.00 0.00 01-OCT-00:10 6739.02 48951.54 02-OCT-10:40
November 0.00 0.00 01-NOV-00:10 7716.25 54928.78 27-NOV-11:40
December 0.00 0.00 01-DEC-00:03 10277.94 61852.08 21-DEC-11:40
             
Annual Sum or Average 0.00     9493.80    
Minimum of Months 0.00 0.00   6739.02 48951.54  
Maximum of Months 0.00 0.00   12181.84 76117.71  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: COOLSYS1

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 302559.88 856106.84 07-JAN-19:02 0.00 0.00 01-JAN-00:03
February 351044.64 852956.23 11-FEB-16:03 0.00 0.00 01-FEB-00:03
March 383948.18 862782.08 19-MAR-08:62 0.00 0.00 01-MAR-00:03
April 472543.71 866837.27 01-APR-15:03 0.00 0.00 01-APR-00:10
May 597269.56 910447.94 28-MAY-15:03 0.00 0.00 01-MAY-00:10
June 684550.66 974223.34 08-JUN-18:03 0.00 0.00 01-JUN-00:10
July 700328.25 994549.63 27-JUL-18:03 0.00 0.00 01-JUL-00:10
August 699352.89 950054.48 21-AUG-18:03 0.00 0.00 01-AUG-00:10
September 682785.30 1006036.25 18-SEP-18:03 0.00 0.00 01-SEP-00:10
October 619128.68 940360.79 29-OCT-18:03 0.00 0.00 01-OCT-00:10
November 512373.74 932511.46 04-NOV-18:03 0.00 0.00 01-NOV-00:10
December 368825.07 867595.97 23-DEC-19:03 0.00 0.00 01-DEC-00:03
             
Annual Sum or Average 532083.95     0.00    
Minimum of Months 302559.88 852956.23   0.00 0.00  
Maximum of Months 700328.25 1006036.25   0.00 0.00  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:03 20265.30 40653.20 20-JAN-07:20
February 0.00 0.00 01-FEB-00:03 20087.51 40517.08 03-FEB-07:15
March 0.00 0.00 01-MAR-00:03 19531.38 39744.28 01-MAR-07:10
April 0.00 0.00 01-APR-00:10 18691.42 38037.64 03-APR-06:10
May 0.00 0.00 01-MAY-00:10 17836.46 36368.87 01-MAY-06:10
June 0.00 0.00 01-JUN-00:10 17184.54 34652.15 01-JUN-07:00
July 0.00 0.00 01-JUL-00:10 16893.45 33643.94 03-JUL-06:50
August 0.00 0.00 01-AUG-00:10 17092.96 34405.19 31-AUG-06:30
September 0.00 0.00 01-SEP-00:10 17671.85 35922.08 29-SEP-06:20
October 0.00 0.00 01-OCT-00:10 18498.15 37791.94 31-OCT-06:20
November 0.00 0.00 01-NOV-00:10 19354.26 39393.91 30-NOV-08:00
December 0.00 0.00 01-DEC-00:03 19999.10 40446.38 29-DEC-07:15
             
Annual Sum or Average 0.00     18583.93    
Minimum of Months 0.00 0.00   16893.45 33643.94  
Maximum of Months 0.00 0.00   20265.30 40653.20  



Table of Contents

Report: FanReportMonthly

For: FLR_3_DOAS FAN

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.587890E+10 0.87 2194.93 01-JAN-00:03 0.87
February 0.530997E+10 0.87 2194.93 01-FEB-00:03 0.87
March 0.587890E+10 0.87 2194.93 01-MAR-00:03 0.87
April 0.568926E+10 0.87 2194.93 01-APR-00:10 0.87
May 0.587890E+10 0.87 2194.93 01-MAY-00:10 0.87
June 0.568926E+10 0.87 2194.93 01-JUN-00:10 0.87
July 0.587890E+10 0.87 2194.93 01-JUL-00:10 0.87
August 0.587890E+10 0.87 2194.93 01-AUG-00:10 0.87
September 0.568926E+10 0.87 2194.93 01-SEP-00:10 0.87
October 0.587890E+10 0.87 2194.93 01-OCT-00:10 0.87
November 0.568926E+10 0.87 2194.93 01-NOV-00:10 0.87
December 0.587890E+10 0.87 2194.93 01-DEC-00:03 0.87
           
Annual Sum or Average 0.692193E+11 0.87      
Minimum of Months 0.530997E+10 0.87 2194.93   0.87
Maximum of Months 0.587890E+10 0.87 2194.93   0.87



Table of Contents

Report: FanReportMonthly

For: VAV WITH REHEAT FAN

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.127282E+12 1.82 47521.84 01-JAN-00:03 1.82
February 0.114965E+12 1.82 47521.84 01-FEB-00:03 1.83
March 0.127283E+12 1.82 47521.84 01-MAR-00:03 1.83
April 0.123177E+12 1.82 47521.84 01-APR-00:10 1.82
May 0.127283E+12 1.82 47521.84 01-MAY-00:10 1.82
June 0.123177E+12 1.82 47521.84 01-JUN-00:10 1.82
July 0.127283E+12 1.82 47521.84 01-JUL-00:10 1.82
August 0.127283E+12 1.82 47521.84 01-AUG-00:10 1.82
September 0.123177E+12 1.82 47521.84 01-SEP-00:10 1.82
October 0.127283E+12 1.82 47521.84 01-OCT-00:10 1.82
November 0.123177E+12 1.82 47521.84 01-NOV-00:10 1.82
December 0.127283E+12 1.82 47521.84 01-DEC-00:03 1.82
           
Annual Sum or Average 0.149865E+13 1.82      
Minimum of Months 0.114965E+12 1.82 47521.84   1.82
Maximum of Months 0.127283E+12 1.82 47521.84   1.83



Table of Contents

Report: FanReportMonthly

For: LAUNDRY_FLR_1 EXHAUST FAN

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.493775E+09 0.64 184.35 01-JAN-00:03 0.63
February 0.445990E+09 0.64 184.35 01-FEB-00:03 0.64
March 0.493775E+09 0.64 184.35 01-MAR-00:03 0.64
April 0.477847E+09 0.64 184.35 01-APR-00:10 0.63
May 0.493775E+09 0.64 184.35 01-MAY-00:10 0.63
June 0.477847E+09 0.64 184.35 01-JUN-00:10 0.63
July 0.493775E+09 0.64 184.35 01-JUL-00:10 0.63
August 0.493775E+09 0.64 184.35 01-AUG-00:10 0.63
September 0.477847E+09 0.64 184.35 01-SEP-00:10 0.63
October 0.493775E+09 0.64 184.35 01-OCT-00:10 0.63
November 0.477847E+09 0.64 184.35 01-NOV-00:10 0.63
December 0.493775E+09 0.64 184.35 01-DEC-00:03 0.63
           
Annual Sum or Average 0.581380E+10 0.64      
Minimum of Months 0.445990E+09 0.64 184.35   0.63
Maximum of Months 0.493775E+09 0.64 184.35   0.64



Table of Contents

Report: FanReportMonthly

For: LOBBY_FLR_1 EXHAUST FAN

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.00 0.00 0.00 01-JAN-00:03 0.00
February 0.00 0.00 0.00 01-FEB-00:03 0.00
March 0.00 0.00 0.00 01-MAR-00:03 0.00
April 0.00 0.00 0.00 01-APR-00:10 0.00
May 0.00 0.00 0.00 01-MAY-00:10 0.00
June 0.00 0.00 0.00 01-JUN-00:10 0.00
July 0.00 0.00 0.00 01-JUL-00:10 0.00
August 0.00 0.00 0.00 01-AUG-00:10 0.00
September 0.00 0.00 0.00 01-SEP-00:10 0.00
October 0.00 0.00 0.00 01-OCT-00:10 0.00
November 0.00 0.00 0.00 01-NOV-00:10 0.00
December 0.00 0.00 0.00 01-DEC-00:03 0.00
           
Annual Sum or Average 0.00 0.00      
Minimum of Months 0.00 0.00 0.00   0.00
Maximum of Months 0.00 0.00 0.00   0.00



Table of Contents

Report: FanReportMonthly

For: BANQUET_FLR_6 EXHAUST FAN

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.00 0.00 0.00 01-JAN-00:03 0.00
February 0.00 0.00 0.00 01-FEB-00:03 0.00
March 0.00 0.00 0.00 01-MAR-00:03 0.00
April 0.00 0.00 0.00 01-APR-00:10 0.00
May 0.00 0.00 0.00 01-MAY-00:10 0.00
June 0.00 0.00 0.00 01-JUN-00:10 0.00
July 0.00 0.00 0.00 01-JUL-00:10 0.00
August 0.00 0.00 0.00 01-AUG-00:10 0.00
September 0.00 0.00 0.00 01-SEP-00:10 0.00
October 0.00 0.00 0.00 01-OCT-00:10 0.00
November 0.00 0.00 0.00 01-NOV-00:10 0.00
December 0.00 0.00 0.00 01-DEC-00:03 0.00
           
Annual Sum or Average 0.00 0.00      
Minimum of Months 0.00 0.00 0.00   0.00
Maximum of Months 0.00 0.00 0.00   0.00



Table of Contents

Report: FanReportMonthly

For: DINING_FLR_6 EXHAUST FAN

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.00 0.00 0.00 01-JAN-00:03 0.00
February 0.00 0.00 0.00 01-FEB-00:03 0.00
March 0.00 0.00 0.00 01-MAR-00:03 0.00
April 0.00 0.00 0.00 01-APR-00:10 0.00
May 0.00 0.00 0.00 01-MAY-00:10 0.00
June 0.00 0.00 0.00 01-JUN-00:10 0.00
July 0.00 0.00 0.00 01-JUL-00:10 0.00
August 0.00 0.00 0.00 01-AUG-00:10 0.00
September 0.00 0.00 0.00 01-SEP-00:10 0.00
October 0.00 0.00 0.00 01-OCT-00:10 0.00
November 0.00 0.00 0.00 01-NOV-00:10 0.00
December 0.00 0.00 0.00 01-DEC-00:03 0.00
           
Annual Sum or Average 0.00 0.00      
Minimum of Months 0.00 0.00 0.00   0.00
Maximum of Months 0.00 0.00 0.00   0.00



Table of Contents

Report: FanReportMonthly

For: KITCHEN_FLR_6 EXHAUST FAN

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.279806E+10 0.45 1474.84 01-JAN-07:10 0.63
February 0.252728E+10 0.45 1474.84 01-FEB-07:05 0.63
March 0.279806E+10 0.45 1474.84 01-MAR-07:05 0.64
April 0.270780E+10 0.45 1474.84 01-APR-06:10 0.63
May 0.279806E+10 0.45 1474.84 01-MAY-06:05 0.63
June 0.270780E+10 0.45 1474.84 01-JUN-06:05 0.63
July 0.279806E+10 0.45 1474.84 01-JUL-06:10 0.63
August 0.279806E+10 0.45 1474.84 01-AUG-06:05 0.63
September 0.270780E+10 0.45 1474.84 01-SEP-06:05 0.63
October 0.279806E+10 0.45 1474.84 01-OCT-06:10 0.63
November 0.270780E+10 0.45 1474.84 01-NOV-06:05 0.63
December 0.279806E+10 0.45 1474.84 01-DEC-07:05 0.63
           
Annual Sum or Average 0.329449E+11 0.45      
Minimum of Months 0.252728E+10 0.45 1474.84   0.63
Maximum of Months 0.279806E+10 0.45 1474.84   0.64



Table of Contents

Report: FanReportMonthly

For: ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.580494E+09 1.16 1775.31 01-JAN-09:02 1.37
February 0.660358E+09 1.21 1775.31 01-FEB-16:02 1.38
March 0.818118E+09 1.21 1775.31 01-MAR-16:02 1.38
April 0.100729E+10 1.27 1775.31 01-APR-08:62 1.37
May 0.117141E+10 1.29 1775.31 01-MAY-08:62 1.37
June 0.120306E+10 1.30 1775.31 01-JUN-08:62 1.37
July 0.135959E+10 1.32 1775.31 01-JUL-08:62 1.37
August 0.129349E+10 1.30 1775.31 01-AUG-08:62 1.37
September 0.126267E+10 1.31 1775.31 01-SEP-08:62 1.37
October 0.119498E+10 1.30 1775.31 01-OCT-08:62 1.37
November 0.867705E+09 1.25 1775.31 01-NOV-08:62 1.37
December 0.670480E+09 1.18 1775.31 01-DEC-09:02 1.38
           
Annual Sum or Average 0.120896E+11 1.26      
Minimum of Months 0.580494E+09 1.16 1775.31   1.37
Maximum of Months 0.135959E+10 1.32 1775.31   1.38



Table of Contents

Report: FanReportMonthly

For: ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.419314E+09 1.06 1792.80 01-JAN-09:02 1.37
February 0.523236E+09 1.12 1792.80 01-FEB-16:02 1.37
March 0.711471E+09 1.15 1792.80 01-MAR-16:02 1.38
April 0.940985E+09 1.25 1792.80 01-APR-08:62 1.37
May 0.116916E+10 1.29 1792.80 01-MAY-08:62 1.37
June 0.122499E+10 1.31 1792.80 01-JUN-08:62 1.37
July 0.137437E+10 1.32 1792.80 01-JUL-08:62 1.37
August 0.126589E+10 1.29 1792.80 01-AUG-08:62 1.37
September 0.117151E+10 1.30 1792.80 01-SEP-08:62 1.37
October 0.103121E+10 1.28 1792.80 01-OCT-08:62 1.37
November 0.709077E+09 1.20 1792.80 01-NOV-08:62 1.37
December 0.516618E+09 1.10 1792.80 01-DEC-09:02 1.38
           
Annual Sum or Average 0.110578E+11 1.22      
Minimum of Months 0.419314E+09 1.06 1792.80   1.37
Maximum of Months 0.137437E+10 1.32 1792.80   1.38



Table of Contents

Report: FanReportMonthly

For: ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.434911E+10 1.17 5764.46 02-JAN-14:30 1.38
February 0.384781E+10 1.19 5876.08 22-FEB-14:40 1.39
March 0.375204E+10 1.22 3282.17 02-MAR-14:30 1.38
April 0.390133E+10 1.32 3011.59 15-APR-19:10 1.38
May 0.439346E+10 1.37 2915.33 29-MAY-20:20 1.38
June 0.466900E+10 1.38 3081.01 03-JUN-21:00 1.38
July 0.514548E+10 1.38 3312.36 29-JUL-19:10 1.38
August 0.512364E+10 1.38 3207.23 20-AUG-20:03 1.38
September 0.577741E+10 1.38 5042.44 30-SEP-13:30 1.38
October 0.638503E+10 1.38 5487.06 25-OCT-12:40 1.38
November 0.533464E+10 1.29 5741.52 07-NOV-13:30 1.38
December 0.448917E+10 1.16 5773.90 03-DEC-14:00 1.38
           
Annual Sum or Average 0.571681E+11 1.30      
Minimum of Months 0.375204E+10 1.16 2915.33   1.38
Maximum of Months 0.638503E+10 1.38 5876.08   1.39



Table of Contents

Report: FanReportMonthly

For: ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.438456E+10 0.98 11766.20 01-JAN-09:02 1.37
February 0.477492E+10 0.98 11766.20 01-FEB-09:02 1.37
March 0.599605E+10 0.99 11766.20 01-MAR-16:02 1.38
April 0.725515E+10 1.03 11766.20 01-APR-08:62 1.37
May 0.916429E+10 1.14 11766.20 01-MAY-08:62 1.37
June 0.996510E+10 1.20 11766.20 01-JUN-08:62 1.38
July 0.105976E+11 1.23 11766.20 01-JUL-08:62 1.38
August 0.965302E+10 1.17 11766.20 01-AUG-08:62 1.38
September 0.909143E+10 1.17 11766.20 01-SEP-08:62 1.38
October 0.815083E+10 1.08 11766.20 01-OCT-08:62 1.37
November 0.633846E+10 0.99 11766.20 01-NOV-08:62 1.37
December 0.488734E+10 0.98 11766.20 01-DEC-09:02 1.38
           
Annual Sum or Average 0.902587E+11 1.08      
Minimum of Months 0.438456E+10 0.98 11766.20   1.37
Maximum of Months 0.105976E+11 1.23 11766.20   1.38



Table of Contents

Report: FanReportMonthly

For: ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.600899E+09 1.20 1595.96 01-JAN-09:02 1.37
February 0.649454E+09 1.23 1595.96 01-FEB-09:02 1.37
March 0.790821E+09 1.24 1595.96 01-MAR-09:02 1.38
April 0.989588E+09 1.31 1595.96 01-APR-08:62 1.37
May 0.117766E+10 1.32 1595.96 01-MAY-08:62 1.37
June 0.129288E+10 1.33 1595.96 01-JUN-08:62 1.38
July 0.141502E+10 1.34 1595.96 01-JUL-08:62 1.38
August 0.130146E+10 1.31 1595.96 01-AUG-08:62 1.37
September 0.131770E+10 1.33 1595.96 01-SEP-08:62 1.38
October 0.122543E+10 1.32 1595.96 01-OCT-08:62 1.37
November 0.888946E+09 1.27 1595.96 01-NOV-08:62 1.37
December 0.625736E+09 1.19 1595.96 01-DEC-09:02 1.38
           
Annual Sum or Average 0.122756E+11 1.28      
Minimum of Months 0.600899E+09 1.19 1595.96   1.37
Maximum of Months 0.141502E+10 1.34 1595.96   1.38



Table of Contents

Report: FanReportMonthly

For: ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.431785E+09 1.07 1609.46 01-JAN-09:02 1.37
February 0.499507E+09 1.16 1609.46 01-FEB-09:02 1.37
March 0.673553E+09 1.19 1609.46 01-MAR-09:02 1.38
April 0.920787E+09 1.30 1609.46 01-APR-08:62 1.37
May 0.117761E+10 1.32 1609.46 01-MAY-08:62 1.37
June 0.131545E+10 1.34 1609.46 01-JUN-08:62 1.38
July 0.143009E+10 1.34 1609.46 01-JUL-08:62 1.38
August 0.127750E+10 1.31 1609.46 01-AUG-08:62 1.37
September 0.123640E+10 1.32 1609.46 01-SEP-08:62 1.38
October 0.105363E+10 1.31 1609.46 01-OCT-08:62 1.37
November 0.701427E+09 1.21 1609.46 01-NOV-08:62 1.37
December 0.466381E+09 1.09 1609.46 01-DEC-09:02 1.38
           
Annual Sum or Average 0.111841E+11 1.25      
Minimum of Months 0.431785E+09 1.07 1609.46   1.37
Maximum of Months 0.143009E+10 1.34 1609.46   1.38



Table of Contents

Report: FanReportMonthly

For: ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.156889E+09 1.18 474.51 01-JAN-09:02 1.37
February 0.181642E+09 1.22 474.51 01-FEB-16:02 1.38
March 0.228092E+09 1.22 474.51 01-MAR-16:02 1.38
April 0.284312E+09 1.28 474.51 01-APR-08:62 1.37
May 0.332280E+09 1.30 474.51 01-MAY-08:62 1.37
June 0.341877E+09 1.31 474.51 01-JUN-08:62 1.37
July 0.387764E+09 1.33 474.51 01-JUL-08:62 1.37
August 0.364345E+09 1.31 474.51 01-AUG-08:62 1.37
September 0.352253E+09 1.31 474.51 01-SEP-08:62 1.37
October 0.327836E+09 1.30 474.51 01-OCT-08:62 1.37
November 0.236608E+09 1.26 474.51 01-NOV-08:62 1.37
December 0.181956E+09 1.19 474.51 01-DEC-09:02 1.37
           
Annual Sum or Average 0.337585E+10 1.27      
Minimum of Months 0.156889E+09 1.18 474.51   1.37
Maximum of Months 0.387764E+09 1.33 474.51   1.38



Table of Contents

Report: FanReportMonthly

For: ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.116878E+09 1.08 478.73 01-JAN-09:02 1.37
February 0.146364E+09 1.16 478.73 01-FEB-16:02 1.37
March 0.200603E+09 1.18 478.73 01-MAR-16:02 1.38
April 0.267110E+09 1.27 478.73 01-APR-08:62 1.37
May 0.332091E+09 1.31 478.73 01-MAY-08:62 1.37
June 0.347703E+09 1.32 478.73 01-JUN-08:62 1.37
July 0.391765E+09 1.33 478.73 01-JUL-08:62 1.37
August 0.356767E+09 1.31 478.73 01-AUG-08:62 1.37
September 0.329270E+09 1.31 478.73 01-SEP-08:62 1.37
October 0.284843E+09 1.29 478.73 01-OCT-08:62 1.37
November 0.194861E+09 1.21 478.73 01-NOV-15:02 1.38
December 0.143685E+09 1.13 478.73 01-DEC-09:02 1.37
           
Annual Sum or Average 0.311194E+10 1.24      
Minimum of Months 0.116878E+09 1.08 478.73   1.37
Maximum of Months 0.391765E+09 1.33 478.73   1.38



Table of Contents

Report: FanReportMonthly

For: ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.134147E+10 1.25 1973.24 01-JAN-09:02 1.37
February 0.127423E+10 1.26 1973.24 01-FEB-09:02 1.37
March 0.132264E+10 1.24 1973.24 01-MAR-09:02 1.38
April 0.140231E+10 1.27 1973.24 01-APR-08:62 1.37
May 0.158682E+10 1.28 1973.24 01-MAY-08:62 1.37
June 0.169497E+10 1.30 1973.24 01-JUN-08:62 1.37
July 0.187255E+10 1.31 1973.24 01-JUL-08:62 1.37
August 0.183004E+10 1.29 1973.24 01-AUG-08:62 1.37
September 0.198969E+10 1.31 1973.24 01-SEP-08:62 1.37
October 0.205514E+10 1.31 1973.24 01-OCT-08:62 1.37
November 0.170513E+10 1.29 1973.24 01-NOV-08:62 1.37
December 0.142404E+10 1.25 1973.24 01-DEC-09:02 1.38
           
Annual Sum or Average 0.194990E+11 1.28      
Minimum of Months 0.127423E+10 1.24 1973.24   1.37
Maximum of Months 0.205514E+10 1.31 1973.24   1.38



Table of Contents

Report: PumpReportMonthly

For: HEATSYS1 PUMP

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.232411E+09 0.209170E+09 377.30 18-JAN-11:40 339.57 339.57 32.92 0.54
February 0.206140E+09 0.185526E+09 407.64 06-FEB-11:40 366.88 366.88 33.51 0.61
March 0.251898E+09 0.226708E+09 461.85 20-MAR-10:40 415.67 415.67 35.93 0.76
April 0.232925E+09 0.209633E+09 406.62 18-APR-10:40 365.96 365.96 36.10 0.60
May 0.217296E+09 0.195566E+09 402.17 01-MAY-10:40 361.95 361.95 36.73 0.59
June 0.199514E+09 0.179562E+09 387.79 13-JUN-10:40 349.01 349.01 36.01 0.56
July 0.190099E+09 0.171089E+09 375.51 07-JUL-10:40 337.96 337.96 35.64 0.53
August 0.170711E+09 0.153640E+09 361.41 07-AUG-10:40 325.27 325.27 35.12 0.50
September 0.149493E+09 0.134544E+09 346.71 05-SEP-10:50 312.04 312.04 34.87 0.47
October 0.148596E+09 0.133736E+09 326.37 02-OCT-10:50 293.74 293.74 34.13 0.43
November 0.159800E+09 0.143820E+09 346.71 27-NOV-11:40 312.04 312.04 32.24 0.47
December 0.215446E+09 0.193901E+09 391.15 21-DEC-11:50 352.04 352.04 35.53 0.57
                 
Annual Sum or Average 0.237433E+10 0.213689E+10            
Minimum of Months 0.148596E+09 0.133736E+09 326.37   293.74 293.74 32.24 0.43
Maximum of Months 0.251898E+09 0.226708E+09 461.85   415.67 415.67 36.73 0.76



Table of Contents

Report: PumpReportMonthly

For: COOLSYS1 PUMP SECONDARY

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.131434E+11 0.118291E+11 8398.39 07-JAN-19:02 7558.55 7558.55 6.73 27.86
February 0.133352E+11 0.120016E+11 8391.53 11-FEB-17:50 7552.38 7552.38 6.73 27.77
March 0.153764E+11 0.138388E+11 8441.81 13-MAR-18:03 7597.63 7597.63 6.73 28.45
April 0.174970E+11 0.157473E+11 8556.85 13-APR-18:03 7701.16 7701.16 6.73 30.16
May 0.201588E+11 0.181429E+11 8710.14 29-MAY-18:03 7839.13 7839.13 6.73 32.68
June 0.205209E+11 0.184688E+11 8885.27 08-JUN-18:03 7996.74 7996.74 6.73 35.65
July 0.213997E+11 0.192597E+11 8990.03 27-JUL-18:03 8091.03 8091.03 6.73 37.30
August 0.213425E+11 0.192082E+11 8836.97 21-AUG-18:03 7953.28 7953.28 6.73 34.85
September 0.205442E+11 0.184898E+11 8945.32 18-SEP-18:03 8050.79 8050.79 6.73 36.62
October 0.204082E+11 0.183674E+11 8721.31 29-OCT-18:03 7849.18 7849.18 6.73 32.87
November 0.176215E+11 0.158593E+11 8696.20 04-NOV-18:03 7826.58 7826.58 6.73 32.44
December 0.147247E+11 0.132522E+11 8484.94 25-DEC-19:03 7636.44 7636.44 6.73 29.07
                 
Annual Sum or Average 0.216072E+12 0.194465E+12            
Minimum of Months 0.131434E+11 0.118291E+11 8391.53   7552.38 7552.38 6.73 27.77
Maximum of Months 0.213997E+11 0.192597E+11 8990.03   8091.03 8091.03 6.73 37.30



Table of Contents

Report: PumpReportMonthly

For: COOLSYS1 PUMP

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.203461E+11 0.183115E+11 7625.39 01-JAN-00:03 6862.85 6862.85 9.09 53.44
February 0.182643E+11 0.164379E+11 7625.39 01-FEB-00:03 6862.85 6862.85 7.18 53.44
March 0.202774E+11 0.182497E+11 7625.39 01-MAR-00:03 6862.85 6862.85 7.39 53.44
April 0.197650E+11 0.177885E+11 7625.39 01-APR-00:10 6862.85 6862.85 8.48 53.44
May 0.204239E+11 0.183815E+11 7625.39 01-MAY-00:10 6862.85 6862.85 8.69 53.44
June 0.197650E+11 0.177885E+11 7625.39 01-JUN-00:10 6862.85 6862.85 9.66 53.44
July 0.204239E+11 0.183815E+11 7625.39 01-JUL-00:10 6862.85 6862.85 9.54 53.44
August 0.204239E+11 0.183815E+11 7625.39 01-AUG-00:10 6862.85 6862.85 10.03 53.44
September 0.197650E+11 0.177885E+11 7625.39 01-SEP-00:10 6862.85 6862.85 9.59 53.44
October 0.204239E+11 0.183815E+11 7625.39 01-OCT-00:10 6862.85 6862.85 9.56 53.44
November 0.197650E+11 0.177885E+11 7625.39 01-NOV-00:10 6862.85 6862.85 8.93 53.44
December 0.203781E+11 0.183403E+11 7625.39 01-DEC-00:03 6862.85 6862.85 9.05 53.44
                 
Annual Sum or Average 0.240021E+12 0.216019E+12            
Minimum of Months 0.182643E+11 0.164379E+11 7625.39   6862.85 6862.85 7.18 53.44
Maximum of Months 0.204239E+11 0.183815E+11 7625.39   6862.85 6862.85 10.03 53.44



Table of Contents

Report: PumpReportMonthly

For: SWHSYS1 PUMP

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.128314E+09 38494137.67 47.91 01-JAN-00:03 14.37 14.37 51.18 0.37
February 0.115896E+09 34768898.54 47.91 01-FEB-00:03 14.37 14.37 51.64 0.37
March 0.128314E+09 38494137.67 47.91 01-MAR-00:03 14.37 14.37 51.36 0.37
April 0.124175E+09 37252391.29 47.91 01-APR-00:10 14.37 14.37 53.63 0.37
May 0.128314E+09 38494137.67 47.91 01-MAY-00:10 14.37 14.37 53.86 0.37
June 0.124175E+09 37252391.29 47.91 01-JUN-00:10 14.37 14.37 54.76 0.37
July 0.128314E+09 38494137.67 47.91 01-JUL-00:10 14.37 14.37 54.99 0.37
August 0.128314E+09 38494137.67 47.91 01-AUG-00:10 14.37 14.37 54.82 0.37
September 0.124175E+09 37252391.29 47.91 01-SEP-00:10 14.37 14.37 54.82 0.37
October 0.128314E+09 38494137.67 47.91 01-OCT-00:10 14.37 14.37 54.11 0.37
November 0.124175E+09 37252391.29 47.91 01-NOV-00:10 14.37 14.37 53.96 0.37
December 0.128314E+09 38494137.67 47.91 01-DEC-00:03 14.37 14.37 51.34 0.37
                 
Annual Sum or Average 0.151079E+10 0.453237E+09            
Minimum of Months 0.115896E+09 34768898.54 47.91   14.37 14.37 51.18 0.37
Maximum of Months 0.128314E+09 38494137.67 47.91   14.37 14.37 54.99 0.37



Table of Contents

Report: CondLoopDemandReportMonthly

For: HEATSYS1

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:03 25.08 60.00 11233.28 60722.14 18-JAN-11:40
February 0.00 0.00 01-FEB-00:03 26.64 60.00 11068.74 67096.09 06-FEB-11:40
March 0.00 0.00 01-MAR-00:03 26.53 60.00 12181.84 76117.71 20-MAR-10:40
April 0.00 0.00 01-APR-00:10 29.69 60.00 11402.04 67094.71 18-APR-10:35
May 0.00 0.00 01-MAY-00:10 29.82 60.00 10147.67 62175.45 01-MAY-10:35
June 0.00 0.00 01-JUN-00:10 29.43 60.00 9509.79 60608.83 13-JUN-10:35
July 0.00 0.00 01-JUL-00:10 29.37 60.00 8744.58 57541.44 07-JUL-10:35
August 0.00 0.00 01-AUG-00:10 29.37 60.00 7948.03 56734.21 29-AUG-10:35
September 0.00 0.00 01-SEP-00:10 29.44 60.00 7034.27 53503.53 05-SEP-10:40
October 0.00 0.00 01-OCT-00:10 30.07 60.00 6739.02 48951.54 02-OCT-10:40
November 0.00 0.00 01-NOV-00:10 30.21 60.00 7716.25 54928.78 27-NOV-11:40
December 0.00 0.00 01-DEC-00:03 28.69 60.00 10277.94 61852.08 21-DEC-11:40
                 
Annual Sum or Average 0.00         9493.80    
Minimum of Months 0.00 0.00   25.08 60.00 6739.02 48951.54  
Maximum of Months 0.00 0.00   30.21 60.00 12181.84 76117.71  



Table of Contents

Report: CondLoopDemandReportMonthly

For: COOLSYS1

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 302559.88 856106.84 07-JAN-19:02 10.52 6.70 0.00 0.00 01-JAN-00:03
February 351044.64 852956.23 11-FEB-16:03 10.51 6.70 0.00 0.00 01-FEB-00:03
March 383948.18 862782.08 19-MAR-08:62 10.55 6.70 0.00 0.00 01-MAR-00:03
April 472543.71 866837.27 01-APR-15:03 10.57 6.70 0.00 0.00 01-APR-00:10
May 597269.56 910447.94 28-MAY-15:03 10.77 6.70 0.00 0.00 01-MAY-00:10
June 684550.66 974223.34 08-JUN-18:03 11.05 6.70 0.00 0.00 01-JUN-00:10
July 700328.25 994549.63 27-JUL-18:03 11.14 6.70 0.00 0.00 01-JUL-00:10
August 699352.89 950054.48 21-AUG-18:03 10.94 6.70 0.00 0.00 01-AUG-00:10
September 682785.30 1006036.25 18-SEP-18:03 11.19 6.70 0.00 0.00 01-SEP-00:10
October 619128.68 940360.79 29-OCT-18:03 10.90 6.70 0.00 0.00 01-OCT-00:10
November 512373.74 932511.46 04-NOV-18:03 10.86 6.70 0.00 0.00 01-NOV-00:10
December 368825.07 867595.97 23-DEC-19:03 10.57 6.70 0.00 0.00 01-DEC-00:03
                 
Annual Sum or Average 532083.95         0.00    
Minimum of Months 302559.88 852956.23   10.51 6.70 0.00 0.00  
Maximum of Months 700328.25 1006036.25   11.19 6.70 0.00 0.00  



Table of Contents

Report: CondLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:03 51.18 59.85 20265.30 40653.20 20-JAN-07:20
February 0.00 0.00 01-FEB-00:03 51.64 59.67 20087.51 40517.08 03-FEB-07:15
March 0.00 0.00 01-MAR-00:03 51.36 58.40 19531.38 39744.28 01-MAR-07:10
April 0.00 0.00 01-APR-00:10 53.63 58.42 18691.42 38037.64 03-APR-06:10
May 0.00 0.00 01-MAY-00:10 53.86 58.48 17836.46 36368.87 01-MAY-06:10
June 0.00 0.00 01-JUN-00:10 54.76 59.31 17184.54 34652.15 01-JUN-07:00
July 0.00 0.00 01-JUL-00:10 54.99 59.58 16893.45 33643.94 03-JUL-06:50
August 0.00 0.00 01-AUG-00:10 54.82 59.11 17092.96 34405.19 31-AUG-06:30
September 0.00 0.00 01-SEP-00:10 54.82 59.57 17671.85 35922.08 29-SEP-06:20
October 0.00 0.00 01-OCT-00:10 54.11 59.67 18498.15 37791.94 31-OCT-06:20
November 0.00 0.00 01-NOV-00:10 53.96 58.77 19354.26 39393.91 30-NOV-08:00
December 0.00 0.00 01-DEC-00:03 51.34 58.31 19999.10 40446.38 29-DEC-07:15
                 
Annual Sum or Average 0.00         18583.93    
Minimum of Months 0.00 0.00   51.18 58.31 16893.45 33643.94  
Maximum of Months 0.00 0.00   54.99 59.85 20265.30 40653.20  



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: VAV WITH REHEAT

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.298380E+11 0.00 0.588169E+12 0.127282E+12 0.00 0.00
February 0.265004E+11 0.00 0.619413E+12 0.114965E+12 0.00 0.00
March 0.325904E+11 0.00 0.757114E+12 0.127283E+12 0.00 0.00
April 0.297415E+11 0.00 0.911343E+12 0.123177E+12 0.00 0.00
May 0.273772E+11 0.00 0.121938E+13 0.127283E+12 0.00 0.00
June 0.248274E+11 0.00 0.136731E+13 0.123177E+12 0.00 0.00
July 0.235941E+11 0.00 0.144135E+13 0.127283E+12 0.00 0.00
August 0.214403E+11 0.00 0.144829E+13 0.127283E+12 0.00 0.00
September 0.183754E+11 0.00 0.135531E+13 0.123177E+12 0.00 0.00
October 0.181604E+11 0.00 0.125873E+13 0.127283E+12 0.00 0.00
November 0.200092E+11 0.00 0.100361E+13 0.123177E+12 0.00 0.00
December 0.272252E+11 0.00 0.733564E+12 0.127283E+12 0.00 0.00
             
Annual Sum or Average 0.299680E+12 0.00 0.127036E+14 0.149865E+13 0.00 0.00
Minimum of Months 0.181604E+11 0.00 0.588169E+12 0.114965E+12 0.00 0.00
Maximum of Months 0.325904E+11 0.00 0.144829E+13 0.127283E+12 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: FLR_3_DOAS

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 16088.21 0.00 0.678594E+11 0.587890E+10 0.00 0.00
February 10164.89 0.00 0.730381E+11 0.530997E+10 0.00 0.00
March 10841.74 0.00 0.884958E+11 0.587890E+10 0.00 0.00
April 10483.25 0.00 0.104580E+12 0.568926E+10 0.00 0.00
May 9159.30 0.00 0.131409E+12 0.587890E+10 0.00 0.00
June 6740.83 0.00 0.141915E+12 0.568926E+10 0.00 0.00
July 8790.63 0.00 0.147828E+12 0.587890E+10 0.00 0.00
August 5251.23 0.00 0.150052E+12 0.587890E+10 0.00 0.00
September 9623.38 0.00 0.140049E+12 0.568926E+10 0.00 0.00
October 7210.07 0.00 0.134316E+12 0.587890E+10 0.00 0.00
November 12189.19 0.00 0.111940E+12 0.568926E+10 0.00 0.00
December 15792.48 0.00 0.842073E+11 0.587890E+10 0.00 0.00
             
Annual Sum or Average 122335.18 0.00 0.137569E+13 0.692193E+11 0.00 0.00
Minimum of Months 5251.23 0.00 0.678594E+11 0.530997E+10 0.00 0.00
Maximum of Months 16088.21 0.00 0.150052E+12 0.587890E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: VAV WITH REHEAT

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.127282E+12 0.588169E+12 0.298380E+11 0.125217E+11 0.138372E+12 0.00 0.00 0.00
February 0.114965E+12 0.619413E+12 0.265004E+11 0.171375E+11 0.171466E+12 0.00 0.00 0.00
March 0.127283E+12 0.757114E+12 0.325904E+11 0.132702E+11 0.285859E+12 0.00 0.00 0.00
April 0.123177E+12 0.911343E+12 0.297415E+11 0.258582E+10 0.377056E+12 0.00 0.00 0.00
May 0.127283E+12 0.121938E+13 0.273772E+11 0.00 0.736867E+12 0.00 0.00 0.00
June 0.123177E+12 0.136731E+13 0.248274E+11 0.00 0.953028E+12 0.00 0.00 0.00
July 0.127283E+12 0.144135E+13 0.235941E+11 0.00 0.101775E+13 0.00 0.00 0.00
August 0.127283E+12 0.144829E+13 0.214403E+11 0.00 0.103113E+13 0.00 0.00 0.00
September 0.123177E+12 0.135531E+13 0.183754E+11 0.00 0.931071E+12 0.00 0.00 0.00
October 0.127283E+12 0.125873E+13 0.181604E+11 0.00 0.777788E+12 0.00 0.00 0.00
November 0.123177E+12 0.100361E+13 0.200092E+11 0.494369E+10 0.470502E+12 0.00 0.00 0.00
December 0.127283E+12 0.733564E+12 0.272252E+11 0.207733E+11 0.238416E+12 0.00 0.00 0.00
                 
Annual Sum or Average 0.149865E+13 0.127036E+14 0.299680E+12 0.712322E+11 0.712930E+13 0.00 0.00 0.00
Minimum of Months 0.114965E+12 0.588169E+12 0.181604E+11 0.00 0.138372E+12 0.00 0.00 0.00
Maximum of Months 0.127283E+12 0.144829E+13 0.325904E+11 0.207733E+11 0.103113E+13 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: FLR_3_DOAS

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.587890E+10 0.678594E+11 16088.21 0.205720E+10 0.137647E+11 0.00 0.00 0.00
February 0.530997E+10 0.730381E+11 10164.89 0.220812E+10 0.170978E+11 0.00 0.00 0.00
March 0.587890E+10 0.884958E+11 10841.74 0.185009E+10 0.300033E+11 0.00 0.00 0.00
April 0.568926E+10 0.104580E+12 10483.25 56728160.02 0.411858E+11 0.00 0.00 0.00
May 0.587890E+10 0.131409E+12 9159.30 0.00 0.806956E+11 0.00 0.00 0.00
June 0.568926E+10 0.141915E+12 6740.83 0.00 0.103606E+12 0.00 0.00 0.00
July 0.587890E+10 0.147828E+12 8790.63 0.00 0.110840E+12 0.00 0.00 0.00
August 0.587890E+10 0.150052E+12 5251.23 0.00 0.111911E+12 0.00 0.00 0.00
September 0.568926E+10 0.140049E+12 9623.38 0.00 0.102357E+12 0.00 0.00 0.00
October 0.587890E+10 0.134316E+12 7210.07 0.00 0.860742E+11 0.00 0.00 0.00
November 0.568926E+10 0.111940E+12 12189.19 0.571323E+09 0.509871E+11 0.00 0.00 0.00
December 0.587890E+10 0.842073E+11 15792.48 0.273017E+10 0.246607E+11 0.00 0.00 0.00
                 
Annual Sum or Average 0.692193E+11 0.137569E+13 122335.18 0.947364E+10 0.773183E+12 0.00 0.00 0.00
Minimum of Months 0.530997E+10 0.678594E+11 5251.23 0.00 0.137647E+11 0.00 0.00 0.00
Maximum of Months 0.587890E+10 0.150052E+12 16088.21 0.273017E+10 0.111911E+12 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: VAV WITH REHEAT

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.127282E+12 0.298380E+11 0.588169E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.114965E+12 0.265004E+11 0.619413E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.127283E+12 0.325904E+11 0.757114E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.123177E+12 0.297415E+11 0.911343E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.127283E+12 0.273772E+11 0.121938E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.123177E+12 0.248274E+11 0.136731E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.127283E+12 0.235941E+11 0.144135E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.127283E+12 0.214403E+11 0.144829E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.123177E+12 0.183754E+11 0.135531E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.127283E+12 0.181604E+11 0.125873E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.123177E+12 0.200092E+11 0.100361E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.127283E+12 0.272252E+11 0.733564E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.149865E+13 0.299680E+12 0.127036E+14 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.114965E+12 0.181604E+11 0.588169E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.127283E+12 0.325904E+11 0.144829E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: FLR_3_DOAS

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.587890E+10 16088.21 0.678594E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.530997E+10 10164.89 0.730381E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.587890E+10 10841.74 0.884958E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.568926E+10 10483.25 0.104580E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.587890E+10 9159.30 0.131409E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.568926E+10 6740.83 0.141915E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.587890E+10 8790.63 0.147828E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.587890E+10 5251.23 0.150052E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.568926E+10 9623.38 0.140049E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.587890E+10 7210.07 0.134316E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.568926E+10 12189.19 0.111940E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.587890E+10 15792.48 0.842073E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.692193E+11 122335.18 0.137569E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.530997E+10 5251.23 0.678594E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.587890E+10 16088.21 0.150052E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.262209E+11 0.00 0.00 0.00 0.192311E+11 0.00 0.00 0.00 2.00
February 0.160115E+11 0.00 0.00 0.00 0.200933E+11 0.00 0.00 0.00 1.99
March 0.153995E+11 0.00 0.00 0.00 0.279969E+11 0.00 0.00 0.00 1.99
April 0.280847E+10 0.00 0.00 0.00 0.355758E+11 0.00 0.00 0.00 2.00
May 0.00 0.00 0.00 0.00 0.662112E+11 0.00 0.00 0.00 2.00
June 0.00 0.00 0.00 0.00 0.855684E+11 0.00 0.00 0.00 2.00
July 0.00 0.00 0.00 0.00 0.912862E+11 0.00 0.00 0.00 2.00
August 0.00 0.00 0.00 0.00 0.927575E+11 0.00 0.00 0.00 2.00
September 0.00 0.00 0.00 0.00 0.839501E+11 0.00 0.00 0.00 2.01
October 0.00 0.00 0.00 0.00 0.706361E+11 0.00 0.00 0.00 2.01
November 0.629428E+10 0.00 0.00 0.00 0.504191E+11 0.00 0.00 0.00 2.00
December 0.188427E+11 0.00 0.00 0.00 0.290404E+11 0.00 0.00 0.00 2.00
                   
Annual Sum or Average 0.855773E+11 0.00 0.00 0.00 0.672766E+12 0.00 0.00 0.00 2.00
Minimum of Months 0.00 0.00 0.00 0.00 0.192311E+11 0.00 0.00 0.00 1.99
Maximum of Months 0.262209E+11 0.00 0.00 0.00 0.927575E+11 0.00 0.00 0.00 2.01



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: RETAIL_1_FLR_1

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.285899E+10 0.193392E+09 0.00 64586.95 0.192825E+10 0.00 33719990.79 0.00 4.00
February 0.173264E+10 0.141721E+09 0.00 6193.21 0.207504E+10 33179049.25 613567.11 0.00 4.00
March 0.169892E+10 8418000.97 0.00 88.55 0.308029E+10 0.00 1933.93 0.00 4.00
April 0.309840E+09 0.00 0.00 0.00 0.392484E+10 0.00 0.00 0.00 4.00
May 0.00 0.00 0.00 0.00 0.730464E+10 0.00 0.00 0.00 4.02
June 0.00 0.00 0.00 0.00 0.944019E+10 0.00 0.00 0.00 4.01
July 0.00 0.00 0.00 0.00 0.100710E+11 0.00 0.00 0.00 4.01
August 0.00 37504798.67 0.00 0.00 0.101958E+11 0.00 0.00 0.00 4.02
September 0.00 0.729782E+09 0.00 0.00 0.853186E+10 0.00 0.00 0.00 4.03
October 0.00 0.982940E+09 0.00 0.00 0.680987E+10 0.00 0.00 0.00 4.03
November 0.686890E+09 0.589043E+09 0.00 21696.76 0.497335E+10 0.00 7493184.97 0.00 4.01
December 0.207237E+10 0.366377E+09 0.00 7863.38 0.283746E+10 0.00 6413321.28 0.00 4.00
                   
Annual Sum or Average 0.935965E+10 0.304918E+10 0.00 100428.85 0.711726E+11 33179049.25 48241998.10 0.00 4.01
Minimum of Months 0.00 0.00 0.00 0.00 0.192825E+10 0.00 0.00 0.00 4.00
Maximum of Months 0.285899E+10 0.982940E+09 0.00 64586.95 0.101958E+11 33179049.25 33719990.79 0.00 4.03



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: RETAIL_2_FLR_1

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.238643E+10 0.00 0.00 0.00 0.175028E+10 0.00 0.00 0.00 2.85
February 0.145725E+10 0.00 0.00 0.00 0.182875E+10 0.00 0.00 0.00 2.85
March 0.140155E+10 0.00 0.00 0.00 0.254807E+10 0.00 0.00 0.00 2.85
April 0.255607E+09 0.00 0.00 0.00 0.323785E+10 0.00 0.00 0.00 2.85
May 0.00 0.00 0.00 0.00 0.602607E+10 0.00 0.00 0.00 2.86
June 0.00 0.00 0.00 0.00 0.778782E+10 0.00 0.00 0.00 2.86
July 0.00 0.00 0.00 0.00 0.830822E+10 0.00 0.00 0.00 2.86
August 0.00 0.00 0.00 0.00 0.844212E+10 0.00 0.00 0.00 2.86
September 0.00 0.00 0.00 0.00 0.764053E+10 0.00 0.00 0.00 2.86
October 0.00 0.00 0.00 0.00 0.642879E+10 0.00 0.00 0.00 2.87
November 0.572860E+09 0.00 0.00 0.00 0.458878E+10 0.00 0.00 0.00 2.86
December 0.171493E+10 0.00 0.00 0.00 0.264305E+10 0.00 0.00 0.00 2.85
                   
Annual Sum or Average 0.778863E+10 0.00 0.00 0.00 0.612303E+11 0.00 0.00 0.00 2.86
Minimum of Months 0.00 0.00 0.00 0.00 0.175028E+10 0.00 0.00 0.00 2.85
Maximum of Months 0.238643E+10 0.00 0.00 0.00 0.844212E+10 0.00 0.00 0.00 2.87



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: MECH_FLR_1

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.257573E+10 0.00 0.00 0.00 0.188911E+10 0.00 0.00 0.00 1.45
February 0.157284E+10 0.00 0.00 0.00 0.197381E+10 0.00 0.00 0.00 1.45
March 0.151272E+10 0.00 0.00 0.00 0.275019E+10 0.00 0.00 0.00 1.45
April 0.275882E+09 0.00 0.00 0.00 0.349468E+10 0.00 0.00 0.00 1.46
May 0.00 0.00 0.00 0.00 0.650406E+10 0.00 0.00 0.00 1.46
June 0.00 0.00 0.00 0.00 0.840555E+10 0.00 0.00 0.00 1.46
July 0.00 0.00 0.00 0.00 0.896723E+10 0.00 0.00 0.00 1.46
August 0.00 0.00 0.00 0.00 0.911175E+10 0.00 0.00 0.00 1.46
September 0.00 0.00 0.00 0.00 0.824658E+10 0.00 0.00 0.00 1.46
October 0.00 0.00 0.00 0.00 0.693872E+10 0.00 0.00 0.00 1.46
November 0.618299E+09 0.00 0.00 0.00 0.495276E+10 0.00 0.00 0.00 1.46
December 0.185096E+10 0.00 0.00 0.00 0.285270E+10 0.00 0.00 0.00 1.45
                   
Annual Sum or Average 0.840642E+10 0.00 0.00 0.00 0.660871E+11 0.00 0.00 0.00 1.46
Minimum of Months 0.00 0.00 0.00 0.00 0.188911E+10 0.00 0.00 0.00 1.45
Maximum of Months 0.257573E+10 0.00 0.00 0.00 0.911175E+10 0.00 0.00 0.00 1.46



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: STORAGE_FLR_1

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.128591E+10 0.00 0.00 0.00 0.943122E+09 0.00 0.00 0.00 1.26
February 0.783371E+09 0.00 0.00 0.00 0.985407E+09 1854943.49 0.00 0.00 1.26
March 0.754511E+09 0.00 0.00 0.00 0.137301E+10 701805.99 0.00 0.00 1.26
April 0.137732E+09 0.00 0.00 0.00 0.174469E+10 0.00 0.00 0.00 1.26
May 0.00 0.00 0.00 0.00 0.324709E+10 0.00 0.00 0.00 1.26
June 0.00 0.00 0.00 0.00 0.419640E+10 0.00 0.00 0.00 1.26
July 0.00 0.00 0.00 0.00 0.447681E+10 0.00 0.00 0.00 1.26
August 0.00 0.00 0.00 0.00 0.454896E+10 0.00 0.00 0.00 1.26
September 0.00 0.00 0.00 0.00 0.411703E+10 0.00 0.00 0.00 1.26
October 0.00 0.00 0.00 0.00 0.346410E+10 0.00 0.00 0.00 1.27
November 0.308680E+09 0.00 0.00 0.00 0.247262E+10 0.00 0.00 0.00 1.26
December 0.924074E+09 0.00 0.00 0.00 0.142419E+10 0.00 0.00 0.00 1.26
                   
Annual Sum or Average 0.419428E+10 0.00 0.00 0.00 0.329934E+11 2556749.48 0.00 0.00 1.26
Minimum of Months 0.00 0.00 0.00 0.00 0.943122E+09 0.00 0.00 0.00 1.26
Maximum of Months 0.128591E+10 0.00 0.00 0.00 0.454896E+10 1854943.49 0.00 0.00 1.27



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: LAUNDRY_FLR_1

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.531943E+09 0.229122E+11 0.00 34496234.67 0.693328E+09 0.00 0.316242E+11 0.00 38.27
February 0.242170E+09 0.238829E+11 0.00 24000619.47 0.781358E+09 0.00 0.193891E+11 0.00 38.21
March 0.397700E+09 0.332103E+11 0.00 22587070.13 0.115366E+10 0.00 0.184848E+11 0.00 38.23
April 50055966.14 0.419534E+11 0.00 7780560.34 0.171305E+10 0.00 0.338968E+10 0.00 38.29
May 0.00 0.782894E+11 0.00 0.00 0.297843E+10 0.00 0.00 0.00 38.39
June 0.00 0.101408E+12 0.00 0.00 0.361633E+10 0.00 0.00 0.00 38.35
July 0.00 0.108073E+12 0.00 0.00 0.396749E+10 0.00 0.00 0.00 38.33
August 0.00 0.109945E+12 0.00 0.00 0.390285E+10 0.00 0.00 0.00 38.35
September 0.00 0.994904E+11 0.00 0.00 0.354771E+10 0.00 0.00 0.00 38.43
October 0.00 0.836920E+11 0.00 0.00 0.300757E+10 0.00 0.00 0.00 38.48
November 91118546.54 0.599700E+11 0.00 9324013.90 0.191677E+10 0.00 0.762532E+10 0.00 38.34
December 0.328712E+09 0.346859E+11 0.00 27382255.70 0.959643E+09 0.00 0.227787E+11 0.00 38.26
                   
Annual Sum or Average 0.164170E+10 0.797512E+12 0.00 0.125571E+09 0.282382E+11 0.00 0.103292E+12 0.00 38.33
Minimum of Months 0.00 0.229122E+11 0.00 0.00 0.693328E+09 0.00 0.00 0.00 38.21
Maximum of Months 0.531943E+09 0.109945E+12 0.00 34496234.67 0.396749E+10 0.00 0.316242E+11 0.00 38.48



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CAFE_FLR_1

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.114904E+11 0.329657E+10 0.00 599698.67 0.616526E+10 0.00 0.140983E+10 0.00 6.35
February 0.677927E+10 0.277328E+10 0.00 322279.87 0.711277E+10 0.00 0.109815E+10 0.00 6.34
March 0.668658E+10 0.358045E+10 0.00 254680.18 0.101942E+11 0.00 0.889810E+09 0.00 6.34
April 0.101273E+10 0.438912E+10 0.00 202150.93 0.131144E+11 0.00 0.368854E+09 0.00 6.35
May 0.00 0.883325E+10 0.00 0.00 0.237431E+11 0.00 0.00 0.00 6.37
June 0.00 0.144718E+11 0.00 0.00 0.276284E+11 0.00 0.00 0.00 6.37
July 0.00 0.149640E+11 0.00 0.00 0.299494E+11 0.00 0.00 0.00 6.36
August 0.00 0.163203E+11 0.00 0.00 0.293170E+11 0.00 0.00 0.00 6.37
September 0.00 0.182097E+11 0.00 0.00 0.230942E+11 0.00 0.00 0.00 6.38
October 0.00 0.170660E+11 0.00 0.00 0.176874E+11 0.00 0.00 0.00 6.39
November 0.274629E+10 0.109757E+11 0.00 196265.51 0.138308E+11 0.00 0.350340E+09 0.00 6.37
December 0.821371E+10 0.541367E+10 0.00 214159.06 0.887440E+10 0.00 0.105682E+10 0.00 6.35
                   
Annual Sum or Average 0.369290E+11 0.120294E+12 0.00 1789234.22 0.210711E+12 0.00 0.517381E+10 0.00 6.36
Minimum of Months 0.00 0.277328E+10 0.00 0.00 0.616526E+10 0.00 0.00 0.00 6.34
Maximum of Months 0.114904E+11 0.182097E+11 0.00 599698.67 0.299494E+11 0.00 0.140983E+10 0.00 6.39



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: LOBBY_FLR_1

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.449063E+11 0.00 0.00 0.00 0.329355E+11 0.00 0.00 0.00 3.19
February 0.274215E+11 0.00 0.00 0.00 0.344122E+11 0.00 0.00 0.00 3.18
March 0.263734E+11 0.00 0.00 0.00 0.479478E+11 0.00 0.00 0.00 3.18
April 0.480983E+10 0.00 0.00 0.00 0.609277E+11 0.00 0.00 0.00 3.19
May 0.00 0.00 0.00 0.00 0.113394E+12 0.00 0.00 0.00 3.20
June 0.00 0.143793E+10 0.00 0.00 0.145108E+12 0.00 0.00 0.00 3.20
July 0.00 0.164141E+10 0.00 0.00 0.154697E+12 0.00 0.00 0.00 3.20
August 0.00 0.142597E+10 0.00 0.00 0.157432E+12 0.00 0.00 0.00 3.20
September 0.00 0.137256E+10 0.00 0.00 0.142402E+12 0.00 0.00 0.00 3.20
October 0.00 0.498343E+09 0.00 0.00 0.120474E+12 0.00 0.00 0.00 3.21
November 0.107797E+11 99635772.01 0.00 0.00 0.862489E+11 0.00 0.00 0.00 3.20
December 0.322703E+11 0.00 0.00 0.00 0.497351E+11 0.00 0.00 0.00 3.19
                   
Annual Sum or Average 0.146561E+12 0.647585E+10 0.00 0.00 0.114571E+13 0.00 0.00 0.00 3.19
Minimum of Months 0.00 0.00 0.00 0.00 0.329355E+11 0.00 0.00 0.00 3.18
Maximum of Months 0.449063E+11 0.164141E+10 0.00 0.00 0.157432E+12 0.00 0.00 0.00 3.21



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_1_FLR_3

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 93353463.63 0.443637E+09 614172.50 4603700.06 49323191.75 36840680.62 0.468647E+09 31912.81 0.47
February 41722106.19 0.436115E+09 541942.71 3536759.92 47344842.38 41714500.34 0.263724E+09 27347.61 0.47
March 62417380.19 0.631924E+09 555679.90 2926948.85 48362077.00 28278490.28 0.249998E+09 28089.77 0.47
April 5147660.54 0.845818E+09 755973.86 1104929.80 48177917.23 64041.28 45787766.42 38867.49 0.47
May 0.00 0.144072E+10 1018693.77 0.00 77587496.11 0.00 0.00 28169.11 0.47
June 0.00 0.180463E+10 758247.92 0.00 84914890.79 0.00 0.00 14881.45 0.47
July 0.00 0.193145E+10 187673.09 0.00 81372268.78 0.00 0.00 3457.67 0.47
August 0.00 0.195571E+10 730797.27 0.00 98133955.58 0.00 0.00 17900.11 0.47
September 0.00 0.178827E+10 946044.61 0.00 80505669.81 0.00 0.00 18199.97 0.48
October 0.00 0.155181E+10 958490.70 0.00 75947138.31 0.00 0.00 27605.28 0.48
November 16277451.33 0.114524E+10 617415.99 1269520.70 78602238.95 11614536.13 0.114639E+09 20853.56 0.47
December 63592521.29 0.644071E+09 584577.21 3234800.99 53744361.07 51952263.04 0.301212E+09 28605.74 0.47
                   
Annual Sum or Average 0.282511E+09 0.146194E+11 8269709.53 16676660.32 0.824016E+09 0.170465E+09 0.144401E+10 285890.56 0.47
Minimum of Months 0.00 0.436115E+09 187673.09 0.00 47344842.38 0.00 0.00 3457.67 0.47
Maximum of Months 93353463.63 0.195571E+10 1018693.77 4603700.06 98133955.58 51952263.04 0.468647E+09 38867.49 0.48



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_2_FLR_3

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.117595E+09 0.413822E+09 859403.28 2701951.27 78821283.02 92854496.45 0.390223E+09 45427.06 0.47
February 49204918.15 0.421341E+09 718898.19 2476081.11 61872914.26 58325520.97 0.240650E+09 39275.91 0.47
March 67804098.61 0.621006E+09 699382.25 2294967.56 59046749.65 47368573.43 0.226113E+09 38600.80 0.47
April 5863116.08 0.840638E+09 861736.57 1028019.73 53145232.14 64033.78 45143123.66 40896.37 0.47
May 0.00 0.144174E+10 1016793.38 0.00 76392222.23 0.00 0.00 28465.19 0.47
June 0.00 0.180821E+10 558634.17 0.00 81316778.77 0.00 0.00 12088.63 0.47
July 0.00 0.193409E+10 126445.04 0.00 78553369.81 0.00 0.00 1535.65 0.47
August 0.00 0.195420E+10 804474.05 0.00 99332038.03 0.00 0.00 20266.02 0.47
September 0.00 0.177600E+10 1020508.03 0.00 92475309.54 0.00 0.00 24102.00 0.48
October 0.00 0.153106E+10 1684460.41 0.00 95758103.12 0.00 0.00 47791.02 0.48
November 18446462.06 0.111717E+10 1571010.47 895094.03 0.105548E+09 23282681.64 0.101159E+09 47694.47 0.47
December 83795140.25 0.619938E+09 976317.25 2011226.43 77388909.85 92389021.73 0.241747E+09 43826.60 0.47
                   
Annual Sum or Average 0.342708E+09 0.144792E+11 10898063.09 11407340.14 0.959651E+09 0.314284E+09 0.124503E+10 389969.71 0.47
Minimum of Months 0.00 0.413822E+09 126445.04 0.00 53145232.14 0.00 0.00 1535.65 0.47
Maximum of Months 0.117595E+09 0.195420E+10 1684460.41 2701951.27 0.105548E+09 92854496.45 0.390223E+09 47791.02 0.48



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_3_MULT19_FLR_3

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.145364E+10 0.665502E+10 0.00 52685356.21 37836460.69 0.00 0.667585E+10 0.00 0.54
February 0.102440E+10 0.654733E+10 0.00 33668867.06 15666599.67 0.00 0.369707E+10 0.00 0.54
March 0.129438E+10 0.923199E+10 0.00 21473026.62 0.00 0.00 0.334333E+10 0.00 0.54
April 0.134566E+09 0.121326E+11 0.00 6970828.72 0.00 0.00 0.564952E+09 0.00 0.54
May 0.00 0.206011E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.54
June 0.00 0.256310E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.54
July 0.00 0.272946E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.54
August 0.00 0.278584E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.54
September 0.00 0.253520E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.54
October 0.00 0.220843E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.54
November 0.481376E+09 0.165680E+11 0.00 12581689.16 34830060.97 0.00 0.145585E+10 0.00 0.54
December 0.116325E+10 0.940677E+10 0.00 36848462.89 63295161.36 0.00 0.449461E+10 0.00 0.54
                   
Annual Sum or Average 0.555162E+10 0.209363E+12 0.00 0.164228E+09 0.151628E+09 0.00 0.202317E+11 0.00 0.54
Minimum of Months 0.00 0.654733E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.54
Maximum of Months 0.145364E+10 0.278584E+11 0.00 52685356.21 63295161.36 0.00 0.667585E+10 0.00 0.54



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_4_MULT19_FLR_3

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.168740E+10 0.484241E+10 8659714.86 42679792.42 0.184344E+10 20295175.42 0.643404E+10 167691.14 0.54
February 0.702085E+09 0.477228E+10 5992556.35 33606389.57 0.178638E+10 12938292.45 0.400781E+10 134177.97 0.54
March 0.961860E+09 0.725598E+10 10132923.03 27644446.67 0.196819E+10 9068062.80 0.366189E+10 213671.26 0.54
April 0.101119E+09 0.100614E+11 9351238.85 10234265.66 0.206498E+10 205560.23 0.595124E+09 192629.88 0.54
May 0.00 0.184096E+11 12339612.03 0.00 0.218470E+10 0.00 0.00 75177.91 0.54
June 0.00 0.234322E+11 20676216.02 0.00 0.218503E+10 0.00 0.00 118659.80 0.54
July 0.00 0.251050E+11 22449205.49 0.00 0.217451E+10 0.00 0.00 99158.11 0.54
August 0.00 0.250030E+11 16337665.75 0.00 0.284664E+10 0.00 0.00 65725.71 0.54
September 0.00 0.227863E+11 4348982.80 0.00 0.256820E+10 0.00 0.00 5240.09 0.54
October 0.00 0.189307E+11 16093228.90 0.00 0.314345E+10 0.00 0.00 126093.52 0.54
November 0.300177E+09 0.133316E+11 18566933.68 14020206.71 0.325698E+10 3278960.47 0.163286E+10 209667.93 0.54
December 0.119974E+10 0.721888E+10 12018250.83 33945528.94 0.224162E+10 13668680.67 0.444891E+10 136437.39 0.54
                   
Annual Sum or Average 0.495238E+10 0.181149E+12 0.156967E+09 0.162131E+09 0.282641E+11 59454732.04 0.207806E+11 1544330.70 0.54
Minimum of Months 0.00 0.477228E+10 4348982.80 0.00 0.178638E+10 0.00 0.00 5240.09 0.54
Maximum of Months 0.168740E+10 0.251050E+11 22449205.49 42679792.42 0.325698E+10 20295175.42 0.643404E+10 213671.26 0.54



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_5_FLR_3

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 76451210.15 0.453372E+09 234539.09 4795091.44 39985289.92 48620222.75 0.473579E+09 14278.73 0.47
February 39543295.08 0.444138E+09 239495.03 3925316.51 39641201.44 40495773.25 0.266733E+09 10754.72 0.47
March 39960423.88 0.643649E+09 164310.47 3095605.83 37051285.20 24625579.47 0.275939E+09 6100.82 0.47
April 3186881.17 0.863769E+09 79642.96 1204980.19 30936425.96 24970.97 47687565.71 5337.23 0.47
May 0.00 0.146554E+10 176849.78 0.00 53635135.62 0.00 0.00 3235.82 0.47
June 0.00 0.183964E+10 44410.64 0.00 50636332.02 0.00 0.00 884.21 0.47
July 0.00 0.196085E+10 0.00 0.00 52159677.31 0.00 0.00 0.00 0.47
August 0.00 0.198435E+10 41782.02 0.00 70201881.22 0.00 0.00 2115.48 0.47
September 0.00 0.181846E+10 0.00 0.00 51281064.32 0.00 0.00 0.00 0.48
October 0.00 0.157767E+10 36273.32 0.00 51032650.89 0.00 0.00 1007.76 0.48
November 14990300.05 0.116176E+10 256089.52 1408105.09 62460705.50 14193112.58 0.113209E+09 7264.65 0.47
December 67275427.49 0.649763E+09 239645.10 3058926.83 48413934.96 62648874.09 0.287008E+09 11753.99 0.47
                   
Annual Sum or Average 0.241408E+09 0.148629E+11 1513037.93 17488025.89 0.587436E+09 0.190609E+09 0.146415E+10 62733.42 0.47
Minimum of Months 0.00 0.444138E+09 0.00 0.00 30936425.96 0.00 0.00 0.00 0.47
Maximum of Months 76451210.15 0.198435E+10 256089.52 4795091.44 70201881.22 62648874.09 0.473579E+09 14278.73 0.48



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_6_FLR_3

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.124390E+09 0.428440E+09 560687.51 2703896.67 64516132.65 0.106572E+09 0.369708E+09 31264.11 0.47
February 45097120.21 0.433915E+09 439449.08 2816066.37 49592347.91 53917052.46 0.248826E+09 25486.39 0.47
March 67053187.34 0.635645E+09 255491.35 2338055.16 44870355.47 38229679.26 0.235959E+09 19828.41 0.47
April 3331846.01 0.859977E+09 78578.46 1127826.92 34623618.25 24968.04 47613652.28 6391.78 0.47
May 0.00 0.146612E+10 176090.37 0.00 52880249.70 0.00 0.00 3974.14 0.47
June 0.00 0.184174E+10 44362.30 0.00 48314677.73 0.00 0.00 927.25 0.47
July 0.00 0.196218E+10 0.00 0.00 50588804.07 0.00 0.00 0.00 0.47
August 0.00 0.198255E+10 109530.71 0.00 71688187.66 0.00 0.00 2233.77 0.47
September 0.00 0.181091E+10 0.00 0.00 58607603.04 0.00 0.00 0.00 0.48
October 0.00 0.156235E+10 49531.04 0.00 66150693.51 0.00 0.00 3585.38 0.48
November 21628491.37 0.113165E+10 404925.28 999527.59 92267142.21 23510567.64 97644865.40 16134.66 0.47
December 88259715.49 0.616650E+09 656859.93 1769160.17 81010992.98 99578497.40 0.230335E+09 29224.62 0.47
                   
Annual Sum or Average 0.349760E+09 0.147321E+11 2775506.00 11754532.88 0.715111E+09 0.321833E+09 0.123009E+10 139050.50 0.47
Minimum of Months 0.00 0.428440E+09 0.00 0.00 34623618.25 0.00 0.00 0.00 0.47
Maximum of Months 0.124390E+09 0.198255E+10 656859.93 2816066.37 92267142.21 0.106572E+09 0.369708E+09 31264.11 0.48



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORRIDOR_FLR_3

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.108459E+11 0.00 0.00 0.00 0.795466E+10 0.00 0.00 0.00 0.84
February 0.662290E+10 0.00 0.00 0.00 0.831131E+10 0.00 0.00 0.00 0.84
March 0.636976E+10 0.00 0.00 0.00 0.115805E+11 0.00 0.00 0.00 0.84
April 0.116168E+10 0.00 0.00 0.00 0.147154E+11 0.00 0.00 0.00 0.84
May 0.00 0.00 0.00 0.00 0.273873E+11 0.00 0.00 0.00 0.85
June 0.00 0.00 0.00 0.00 0.353941E+11 0.00 0.00 0.00 0.85
July 0.00 0.00 0.00 0.00 0.377592E+11 0.00 0.00 0.00 0.85
August 0.00 0.00 0.00 0.00 0.383677E+11 0.00 0.00 0.00 0.85
September 0.00 0.00 0.00 0.00 0.347247E+11 0.00 0.00 0.00 0.85
October 0.00 0.00 0.00 0.00 0.292175E+11 0.00 0.00 0.00 0.85
November 0.260353E+10 0.00 0.00 0.00 0.208551E+11 0.00 0.00 0.00 0.84
December 0.779401E+10 0.00 0.00 0.00 0.120121E+11 0.00 0.00 0.00 0.84
                   
Annual Sum or Average 0.353977E+11 0.00 0.00 0.00 0.278279E+12 0.00 0.00 0.00 0.84
Minimum of Months 0.00 0.00 0.00 0.00 0.795466E+10 0.00 0.00 0.00 0.84
Maximum of Months 0.108459E+11 0.00 0.00 0.00 0.383677E+11 0.00 0.00 0.00 0.85



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_1_FLR_6

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 22678497.50 0.111776E+09 144049.45 1099340.96 11474560.57 25033921.31 0.102050E+09 6767.80 0.47
February 10617167.69 0.110210E+09 121257.38 847611.56 10669019.87 16327058.09 59882441.07 6625.14 0.47
March 15436919.65 0.159587E+09 125307.09 722945.59 10499150.50 13505959.45 56239275.32 5904.40 0.47
April 1219561.80 0.212655E+09 189927.11 280037.89 10843435.59 20509.94 11505989.87 8783.23 0.47
May 0.00 0.362672E+09 255409.12 0.00 16905167.04 0.00 0.00 6306.60 0.47
June 0.00 0.454509E+09 206551.97 0.00 17860949.84 0.00 0.00 3207.37 0.47
July 0.00 0.486998E+09 47034.97 0.00 16206639.08 0.00 0.00 747.72 0.47
August 0.00 0.493395E+09 201791.54 0.00 20046984.27 0.00 0.00 4417.64 0.47
September 0.00 0.449325E+09 236401.24 0.00 17868303.44 0.00 0.00 4659.91 0.48
October 0.00 0.389614E+09 283845.93 0.00 17280574.85 0.00 0.00 7241.04 0.48
November 4069362.83 0.288166E+09 154615.24 293167.47 17793758.68 7431971.28 24155573.49 5047.07 0.47
December 15647781.12 0.162109E+09 139971.13 746862.19 12351759.75 22602137.90 66001123.18 6380.83 0.47
                   
Annual Sum or Average 69669290.60 0.368102E+10 2106162.16 3989965.66 0.179800E+09 84921557.99 0.319834E+09 66088.74 0.47
Minimum of Months 0.00 0.110210E+09 47034.97 0.00 10499150.50 0.00 0.00 747.72 0.47
Maximum of Months 22678497.50 0.493395E+09 283845.93 1099340.96 20046984.27 25033921.31 0.102050E+09 8783.23 0.48



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_2_FLR_6

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 29234879.89 0.106621E+09 207427.61 620774.79 16548451.22 49273288.75 71714645.38 10481.12 0.47
February 12154859.46 0.106953E+09 167709.45 582297.43 13865024.13 23727343.15 51199506.06 7652.14 0.47
March 16921662.84 0.157478E+09 174905.10 559870.92 12536406.99 19803454.64 48610046.58 8512.67 0.47
April 1290792.11 0.211531E+09 208855.55 261123.90 11922021.51 20507.54 11452149.76 9208.15 0.47
May 0.00 0.363264E+09 242082.73 0.00 16281933.99 0.00 0.00 5826.04 0.47
June 0.00 0.455490E+09 156849.11 0.00 16874713.27 0.00 0.00 2306.66 0.47
July 0.00 0.487665E+09 31611.38 0.00 15496537.05 0.00 0.00 383.80 0.47
August 0.00 0.492787E+09 201605.53 0.00 20594574.54 0.00 0.00 4579.49 0.47
September 0.00 0.447018E+09 271687.31 0.00 20084258.92 0.00 0.00 5430.22 0.48
October 0.00 0.384567E+09 438838.28 0.00 22120608.11 0.00 0.00 11158.77 0.48
November 4479126.03 0.281569E+09 407608.39 201589.64 24097366.84 10288783.84 20976363.50 10215.65 0.47
December 20759570.74 0.157465E+09 241090.61 438730.26 16871809.96 36134563.74 47652737.61 8959.40 0.47
                   
Annual Sum or Average 84840891.07 0.365241E+10 2750271.04 2664386.93 0.207294E+09 0.139248E+09 0.251605E+09 84714.09 0.47
Minimum of Months 0.00 0.106621E+09 31611.38 0.00 11922021.51 0.00 0.00 383.80 0.47
Maximum of Months 29234879.89 0.492787E+09 438838.28 620774.79 24097366.84 49273288.75 71714645.38 11158.77 0.48



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: ROOM_3_MULT9_FLR_6

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.100993E+09 0.742764E+09 138318.22 11621035.14 49888765.70 776096.61 0.855816E+09 845.51 0.54
February 50891473.47 0.730212E+09 70039.16 7337148.71 47125436.75 28607873.34 0.476426E+09 2613.24 0.54
March 75596891.95 0.102632E+10 304888.87 5095196.61 66921248.06 15299578.43 0.455905E+09 12381.41 0.54
April 8145336.25 0.135555E+10 552845.96 1517588.99 81009488.73 63675.64 73959436.59 29876.44 0.54
May 0.00 0.230609E+10 445995.46 0.00 0.133730E+09 0.00 0.00 6295.20 0.54
June 0.00 0.289070E+10 0.00 0.00 0.145380E+09 0.00 0.00 0.00 0.54
July 0.00 0.309028E+10 0.00 0.00 0.142853E+09 0.00 0.00 0.00 0.54
August 0.00 0.313306E+10 235315.62 0.00 0.166629E+09 0.00 0.00 3248.67 0.54
September 0.00 0.288601E+10 105549.43 0.00 0.116910E+09 0.00 0.00 16.62 0.54
October 0.00 0.252167E+10 0.00 0.00 94288801.12 0.00 0.00 0.00 0.54
November 19227004.20 0.188088E+10 262794.16 2849279.40 85514757.83 266778.76 0.208618E+09 2157.22 0.54
December 65796972.32 0.107007E+10 125239.06 8194621.72 51569680.50 1539423.71 0.599027E+09 1351.02 0.54
                   
Annual Sum or Average 0.320651E+09 0.236336E+11 2240985.95 36614870.57 0.118182E+10 46553426.49 0.266975E+10 58785.33 0.54
Minimum of Months 0.00 0.730212E+09 0.00 0.00 47125436.75 0.00 0.00 0.00 0.54
Maximum of Months 0.100993E+09 0.313306E+10 552845.96 11621035.14 0.166629E+09 28607873.34 0.855816E+09 29876.44 0.54



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: BANQUET_FLR_6

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.840845E+10 0.739567E+10 0.00 6648984.41 0.876648E+10 0.00 0.136213E+11 0.00 8.03
February 0.452812E+10 0.795508E+10 0.00 5121134.09 0.893171E+10 0.00 0.892307E+10 0.00 8.02
March 0.440560E+10 0.124451E+11 0.00 5470191.82 0.110840E+11 0.00 0.853091E+10 0.00 8.03
April 0.398179E+09 0.161365E+11 0.00 2973974.54 0.137620E+11 0.00 0.195913E+10 0.00 8.04
May 0.00 0.333132E+11 0.00 0.00 0.223318E+11 0.00 0.00 0.00 8.07
June 0.00 0.471908E+11 0.00 0.00 0.247223E+11 0.00 0.00 0.00 8.06
July 0.00 0.511503E+11 0.00 0.00 0.255682E+11 0.00 0.00 0.00 8.06
August 0.00 0.491451E+11 0.00 0.00 0.288098E+11 0.00 0.00 0.00 8.06
September 0.00 0.438676E+11 0.00 0.00 0.266855E+11 0.00 0.00 0.00 8.08
October 0.00 0.339470E+11 0.00 0.00 0.254168E+11 0.00 0.00 0.00 8.08
November 0.154371E+10 0.236270E+11 0.00 1889976.17 0.187460E+11 0.00 0.374422E+10 0.00 8.05
December 0.596186E+10 0.125288E+11 0.00 5229650.02 0.118773E+11 0.00 0.986866E+10 0.00 8.03
                   
Annual Sum or Average 0.252459E+11 0.338702E+12 0.00 27333911.04 0.226702E+12 0.00 0.466473E+11 0.00 8.05
Minimum of Months 0.00 0.739567E+10 0.00 0.00 0.876648E+10 0.00 0.00 0.00 8.02
Maximum of Months 0.840845E+10 0.511503E+11 0.00 6648984.41 0.288098E+11 0.00 0.136213E+11 0.00 8.08



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: DINING_FLR_6

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.766501E+10 0.922853E+10 0.00 8514811.80 0.773098E+10 0.00 0.154501E+11 0.00 8.43
February 0.428317E+10 0.962338E+10 0.00 6501326.82 0.809652E+10 0.00 0.983050E+10 0.00 8.42
March 0.430943E+10 0.143788E+11 0.00 6937189.11 0.103111E+11 0.00 0.926411E+10 0.00 8.42
April 0.324542E+09 0.192059E+11 0.00 3629127.93 0.121676E+11 0.00 0.214856E+10 0.00 8.44
May 0.00 0.396186E+11 0.00 0.00 0.187717E+11 0.00 0.00 0.00 8.47
June 0.00 0.555073E+11 0.00 0.00 0.199537E+11 0.00 0.00 0.00 8.46
July 0.00 0.618455E+11 0.00 0.00 0.186579E+11 0.00 0.00 0.00 8.46
August 0.00 0.580811E+11 0.00 0.00 0.237198E+11 0.00 0.00 0.00 8.46
September 0.00 0.516159E+11 0.00 0.00 0.224178E+11 0.00 0.00 0.00 8.48
October 0.00 0.396138E+11 0.00 0.00 0.226787E+11 0.00 0.00 0.00 8.48
November 0.133752E+10 0.272883E+11 0.00 2440958.38 0.171752E+11 0.00 0.421083E+10 0.00 8.45
December 0.562004E+10 0.143991E+11 0.00 6647707.14 0.112110E+11 0.00 0.109903E+11 0.00 8.43
                   
Annual Sum or Average 0.235397E+11 0.400406E+12 0.00 34671121.18 0.192892E+12 0.00 0.518944E+11 0.00 8.45
Minimum of Months 0.00 0.922853E+10 0.00 0.00 0.773098E+10 0.00 0.00 0.00 8.42
Maximum of Months 0.766501E+10 0.618455E+11 0.00 8514811.80 0.237198E+11 0.00 0.154501E+11 0.00 8.48



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: KITCHEN_FLR_6

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.00 0.162985E+11 0.00 52377587.42 0.00 0.00 0.221459E+11 0.00 26.12
February 0.00 0.170307E+11 0.00 34419482.30 0.00 0.00 0.135183E+11 0.00 26.09
March 0.00 0.237318E+11 0.00 33705949.14 0.00 0.00 0.130017E+11 0.00 26.10
April 0.00 0.301635E+11 0.00 11229057.70 0.00 0.00 0.236592E+10 0.00 26.16
May 0.00 0.561405E+11 0.00 0.00 0.00 0.00 0.00 0.00 26.24
June 0.00 0.725608E+11 0.00 0.00 0.00 0.00 0.00 0.00 26.22
July 0.00 0.774149E+11 0.00 0.00 0.00 0.00 0.00 0.00 26.21
August 0.00 0.786497E+11 0.00 0.00 0.00 0.00 0.00 0.00 26.22
September 0.00 0.711863E+11 0.00 0.00 0.00 0.00 0.00 0.00 26.27
October 0.00 0.598852E+11 0.00 0.00 0.00 0.00 0.00 0.00 26.30
November 0.00 0.427384E+11 0.00 14320293.32 0.00 0.00 0.531395E+10 0.00 26.19
December 0.00 0.246131E+11 0.00 40118095.51 0.00 0.00 0.159120E+11 0.00 26.12
                   
Annual Sum or Average 0.00 0.570413E+12 0.00 0.186170E+09 0.00 0.00 0.722578E+11 0.00 26.19
Minimum of Months 0.00 0.162985E+11 0.00 0.00 0.00 0.00 0.00 0.00 26.09
Maximum of Months 0.00 0.786497E+11 0.00 52377587.42 0.00 0.00 0.221459E+11 0.00 26.30



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORRIDOR_FLR_6

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.653445E+10 0.00 0.00 0.00 0.479255E+10 0.00 0.00 0.00 1.91
February 0.394326E+10 0.00 0.00 0.00 0.500742E+10 46928175.91 0.00 0.00 1.91
March 0.383768E+10 0.00 0.00 0.00 0.697704E+10 0.00 0.00 0.00 1.91
April 0.699894E+09 0.00 0.00 0.00 0.886578E+10 0.00 0.00 0.00 1.91
May 0.00 0.00 0.00 0.00 0.165004E+11 0.00 0.00 0.00 1.92
June 0.00 0.00 0.00 0.00 0.213243E+11 0.00 0.00 0.00 1.92
July 0.00 0.00 0.00 0.00 0.227493E+11 0.00 0.00 0.00 1.92
August 0.00 0.00 0.00 0.00 0.231159E+11 0.00 0.00 0.00 1.92
September 0.00 0.00 0.00 0.00 0.209210E+11 0.00 0.00 0.00 1.92
October 0.00 0.00 0.00 0.00 0.176031E+11 0.00 0.00 0.00 1.92
November 0.156858E+10 0.00 0.00 0.00 0.125648E+11 0.00 0.00 0.00 1.92
December 0.469576E+10 0.00 0.00 0.00 0.723711E+10 0.00 0.00 0.00 1.91
                   
Annual Sum or Average 0.212796E+11 0.00 0.00 0.00 0.167659E+12 46928175.91 0.00 0.00 1.92
Minimum of Months 0.00 0.00 0.00 0.00 0.479255E+10 0.00 0.00 0.00 1.91
Maximum of Months 0.653445E+10 0.00 0.00 0.00 0.231159E+11 46928175.91 0.00 0.00 1.92



Table of Contents

Report: HeatEmissionsReportMonthly

For: Environment

Timestamp: 2023-10-16 08:58:20

Custom Monthly Report

SITE TOTAL SURFACE HEAT EMISSION TO AIR [J] SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J]
January 0.190027E+12 -962823871.6 0.112396E+11 -0.664023E+11 0.110524E+13
February 0.219909E+12 -0.364378E+10 0.349295E+09 -0.186146E+12 0.115474E+13
March 0.307887E+12 -0.723187E+10 -0.101514E+11 -0.379993E+12 0.139154E+13
April 0.331400E+12 -0.122351E+11 -0.311940E+11 -0.653130E+12 0.165102E+13
May 0.327342E+12 -0.232371E+11 -0.777552E+11 -0.129875E+13 0.213417E+13
June 0.287627E+12 -0.295778E+11 -0.104906E+12 -0.167921E+13 0.235905E+13
July 0.302040E+12 -0.315441E+11 -0.115012E+12 -0.179041E+13 0.249761E+13
August 0.330296E+12 -0.319336E+11 -0.115127E+12 -0.181796E+13 0.249034E+13
September 0.246508E+12 -0.289602E+11 -0.103874E+12 -0.164361E+13 0.234961E+13
October 0.234782E+12 -0.244355E+11 -0.826799E+11 -0.137970E+13 0.220211E+13
November 0.173461E+12 -0.149767E+11 -0.462504E+11 -0.837924E+12 0.176681E+13
December 0.187885E+12 -0.531800E+10 -0.567211E+10 -0.302655E+12 0.133090E+13
           
Annual Sum or Average 0.313916E+13 -0.214056E+12 -0.681034E+12 -0.120359E+14 0.224331E+14
Minimum of Months 0.173461E+12 -0.319336E+11 -0.115127E+12 -0.181796E+13 0.110524E+13
Maximum of Months 0.331400E+12 -962823871.6 0.112396E+11 -0.664023E+11 0.249761E+13