Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:57
Tabular Output Report in Format: HTML
Building: HotelLarge
Environment: RUNPERIOD 1 ** Albuquerque Intl Sunport NM USA TMY3 WMO#=723650
Simulation Timestamp: 2023-10-16 08:57:58
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:57:58
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 14818.23 | 1306.11 | 1306.11 |
Net Site Energy | 14818.23 | 1306.11 | 1306.11 |
Total Source Energy | 33805.55 | 2979.70 | 2979.70 |
Net Source Energy | 33805.55 | 2979.70 | 2979.70 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 11345.29 |
Net Conditioned Building Area | 11345.29 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 1384.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1656.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1174.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 262.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1751.30 | 1788.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 679.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2171.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 222.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 435.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 90.78 | 3126.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Refrigeration | 73.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 8517.80 | 6300.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 1384.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 1656.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 1174.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 262.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 959.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 762.04 | 1198.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 16.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 13.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 590.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 32.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 616.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 30.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 2171.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 222.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 435.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 90.78 | 3126.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5742.51 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4114.69 | |
Refrigeration | General | 18.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 22.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 33.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 1384.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 1656.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 1174.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 262.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 1751.30 | 1788.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 679.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 2171.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 222.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 435.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 90.78 | 3126.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Refrigeration | Unassigned | 73.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 126.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 364.99 | 397.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Other | 259.18 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 750.78 | 555.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 126.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 364.99 | 397.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Other | 259.18 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 750.78 | 555.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 8517.803 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 8517.803 | 100.00 |
Total On-Site and Utility Electric Sources | 8517.803 | 100.00 |
Total Electricity End Uses | 8517.803 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | 0.00 |
Air to Air Heat Recovery for Cooling | 571.26 | 13.03 |
Air to Air Heat Recovery for Heating | 3812.78 | 86.97 |
High-Temperature Geothermal* | 0.00 | 0.00 |
Solar Water Thermal | 0.00 | 0.00 |
Solar Air Thermal | 0.00 | 0.00 |
Total On-Site Thermal Sources | 4384.04 | 100.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 9857.19 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 9857.19 | 100.00 |
Total Water End Uses | 9857.19 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.17 |
Time Setpoint Not Met During Occupied Cooling | 14.67 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 7364.00 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2012
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4B
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NM_ALBUQUERQUE
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneHeatingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneElectricSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |PeakSpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ComfortReportSimple55Monthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |OccupantComfortDataSummaryMonthly
| BASEMENT PEOPLE | RETAIL_1_FLR_1 PEOPLE | RETAIL_2_FLR_1 PEOPLE | LAUNDRY_FLR_1 PEOPLE | CAFE_FLR_1 PEOPLE | LOBBY_FLR_1 PEOPLE | ROOM_1_FLR_3 PEOPLE | ROOM_2_FLR_3 PEOPLE | ROOM_3_MULT19_FLR_3 PEOPLE | ROOM_4_MULT19_FLR_3 PEOPLE | ROOM_5_FLR_3 PEOPLE | ROOM_6_FLR_3 PEOPLE | ROOM_1_FLR_6 PEOPLE | ROOM_2_FLR_6 PEOPLE | ROOM_3_MULT9_FLR_6 PEOPLE | BANQUET_FLR_6 PEOPLE | DINING_FLR_6 PEOPLE | KITCHEN_FLR_6 PEOPLE | STORAGE_FLR_1 PEOPLE | CORRIDOR_FLR_3 PEOPLE | CORRIDOR_FLR_6 PEOPLE | MECH_FLR_1 PEOPLE |ChillerReportMonthly
| COOLSYS1 CHILLER1 |BoilerReportMonthly
| HEATSYS1 BOILER |DXReportMonthly
| VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |WindowReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowEnergyReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWH BOOSTER E WATER HEATER | SWH LAUNDRY G WATER HEATER | SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| VAV WITH REHEAT HEATING COIL | BASEMENT VAV BOX REHEAT COIL | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | MECH_FLR_1 VAV BOX REHEAT COIL | STORAGE_FLR_1 VAV BOX REHEAT COIL | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | CAFE_FLR_1 VAV BOX REHEAT COIL | LOBBY_FLR_1 VAV BOX REHEAT COIL | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | BANQUET_FLR_6 VAV BOX REHEAT COIL | DINING_FLR_6 VAV BOX REHEAT COIL | KITCHEN_FLR_6 VAV BOX REHEAT COIL | FLR_3_DOAS HEATING COIL | ROOM_1_FLR_3 FAN COIL HEATING COIL | ROOM_2_FLR_3 FAN COIL HEATING COIL | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_5_FLR_3 FAN COIL HEATING COIL | ROOM_6_FLR_3 FAN COIL HEATING COIL | ROOM_1_FLR_6 FAN COIL HEATING COIL | ROOM_2_FLR_6 FAN COIL HEATING COIL | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1 | SWHSYS1 |FanReportMonthly
| FLR_3_DOAS FAN | VAV WITH REHEAT FAN | LAUNDRY_FLR_1 EXHAUST FAN | LOBBY_FLR_1 EXHAUST FAN | BANQUET_FLR_6 EXHAUST FAN | DINING_FLR_6 EXHAUST FAN | KITCHEN_FLR_6 EXHAUST FAN | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 PUMP | SWHSYS1 PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1 | SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV WITH REHEAT | FLR_3_DOAS |AirLoopSystemComponentLoadsMonthly
| VAV WITH REHEAT | FLR_3_DOAS |AirLoopSystemComponentEnergyUseMonthly
| VAV WITH REHEAT | FLR_3_DOAS |MechanicalVentilationLoadsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:57:58
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:57 |
RunPeriod | RUNPERIOD 1 |
Weather File | Albuquerque Intl Sunport NM USA TMY3 WMO#=723650 |
Latitude [deg] | 35.04 |
Longitude [deg] | -106.6 |
Elevation [m] | 1619.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1213.79 | 432.95 | 85.85 | 609.15 | 85.85 |
Gross Window-Wall Ratio [%] | 26.62 | 23.11 | 21.12 | 32.52 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.15 | 26.05 | 24.48 | 36.65 | 24.48 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1213.79 | 432.95 | 85.85 | 609.15 | 85.85 |
Gross Window-Wall Ratio [%] | 26.62 | 23.11 | 21.12 | 32.52 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.15 | 26.05 | 24.48 | 36.65 | 24.48 |
Total | |
Gross Roof Area [m2] | 1978.84 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 1978.83 | Yes | Yes | 4826.41 | 1.00 | 0.00 | 533.77 | 0.00 | 0.00 | 8.7495 | 18.58 | 5.3800 |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 265.76 | 1.00 | 68.84 | 0.00 | 23.26 | 23.26 | 13.0124 | 6.19 | 10.7600 |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 307.76 | 1.00 | 26.57 | 0.00 | 0.00 | 0.00 | 13.0124 | 6.19 | 10.7600 |
MECH_FLR_1 | 164.24 | Yes | Yes | 650.80 | 1.00 | 62.80 | 0.00 | 0.00 | 0.00 | 10.0642 | 61.93 | 5.3800 |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 375.47 | 1.00 | 36.23 | 0.00 | 0.00 | 0.00 | 7.3195 | 46.45 | 2.6900 |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 309.22 | 1.00 | 85.75 | 0.00 | 0.00 | 0.00 | 5.4896 | 9.29 | 597.5300 |
CAFE_FLR_1 | 188.86 | Yes | Yes | 748.35 | 1.00 | 152.17 | 0.00 | 65.50 | 65.50 | 12.8090 | 1.33 | 5.3800 |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 5183.56 | 1.00 | 434.79 | 0.00 | 85.08 | 85.08 | 10.0642 | 3.10 | 8.0700 |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 10.0642 | 26.01 | 6.7500 |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 10.0642 | 26.01 | 6.7500 |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 74.75 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 10.0642 | 16.35 | 10.5200 |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 74.77 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 10.0642 | 16.35 | 10.5200 |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 10.0642 | 26.01 | 6.7500 |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 10.0642 | 26.01 | 6.7500 |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 1186.91 | 4.00 | 48.31 | 0.00 | 15.94 | 15.94 | 3.6597 | 18.58 | 0.0000 |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 118.94 | 1.00 | 39.95 | 0.00 | 13.18 | 13.18 | 10.0642 | 26.01 | 6.7500 |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 118.93 | 1.00 | 39.95 | 0.00 | 13.18 | 13.18 | 10.0642 | 26.01 | 6.7500 |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 74.77 | 9.00 | 20.44 | 0.00 | 6.74 | 6.74 | 10.0642 | 16.35 | 10.5200 |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.19 | 32.19 | 12.8090 | 1.33 | 67.8200 |
DINING_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.19 | 32.19 | 12.8090 | 1.33 | 67.8200 |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 314.87 | 1.00 | 87.33 | 0.00 | 26.37 | 26.37 | 10.9792 | 4.65 | 2936.4163 |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1256.16 | 1.00 | 85.47 | 0.00 | 28.20 | 28.20 | 3.6597 | 18.58 | 0.0000 |
Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1213.79 | 1213.79 | 8.9207 | 7.07 | 41.0885 | |||
Conditioned Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1213.79 | 1213.79 | 8.9207 | 7.07 | 41.0885 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 1978.83 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 8.7495 | 18.58 | 5.3800 | |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 1.00 | RETAIL_1_FLR_1 | GENERAL | RETAIL_1_FLR_1 | 13.0124 | 6.19 | 10.7600 | |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 1.00 | RETAIL_2_FLR_1 | GENERAL | RETAIL_2_FLR_1 | 13.0124 | 6.19 | 10.7600 | |
MECH_FLR_1 | 164.24 | Yes | Yes | 1.00 | MECH_FLR_1 | GENERAL | MECH_FLR_1 | 10.0642 | 61.93 | 5.3800 | |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 1.00 | STORAGE_FLR_1 | GENERAL | STORAGE_FLR_1 | 7.3195 | 46.45 | 2.6900 | |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 1.00 | LAUNDRY_FLR_1 | GENERAL | LAUNDRY_FLR_1 | 5.4896 | 9.29 | 597.5300 | |
CAFE_FLR_1 | 188.86 | Yes | Yes | 1.00 | CAFE_FLR_1 | GENERAL | CAFE_FLR_1 | 12.8090 | 1.33 | 5.3800 | |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 1.00 | LOBBY_FLR_1 | GENERAL | LOBBY_FLR_1 | 10.0642 | 3.10 | 8.0700 | |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_1_FLR_3 | GENERAL | ROOM_1_FLR_3 | 10.0642 | 26.01 | 6.7500 | |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_2_FLR_3 | GENERAL | ROOM_2_FLR_3 | 10.0642 | 26.01 | 6.7500 | |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 76.00 | ROOM_3_MULT19_FLR_3 | GENERAL | ROOM_3_MULT19_FLR_3 | 10.0642 | 16.35 | 10.5200 | |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 76.00 | ROOM_4_MULT19_FLR_3 | GENERAL | ROOM_4_MULT19_FLR_3 | 10.0642 | 16.35 | 10.5200 | |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_5_FLR_3 | GENERAL | ROOM_5_FLR_3 | 10.0642 | 26.01 | 6.7500 | |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_6_FLR_3 | GENERAL | ROOM_6_FLR_3 | 10.0642 | 26.01 | 6.7500 | |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 4.00 | CORRIDOR_FLR_3 | GENERAL | CORRIDOR_FLR_3 | 3.6597 | 18.58 | 0.0000 | |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 1.00 | ROOM_1_FLR_6 | GENERAL | ROOM_1_FLR_6 | 10.0642 | 26.01 | 6.7500 | |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 1.00 | ROOM_2_FLR_6 | GENERAL | ROOM_2_FLR_6 | 10.0642 | 26.01 | 6.7500 | |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 9.00 | ROOM_3_MULT9_FLR_6 | GENERAL | ROOM_3_MULT9_FLR_6 | 10.0642 | 16.35 | 10.5200 | |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1.00 | BANQUET_FLR_6 | GENERAL | BANQUET_FLR_6 | 12.8090 | 1.33 | 67.8200 | |
DINING_FLR_6 | 331.66 | Yes | Yes | 1.00 | DINING_FLR_6 | GENERAL | DINING_FLR_6 | 12.8090 | 1.33 | 67.8200 | |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 1.00 | KITCHEN_FLR_6 | GENERAL | KITCHEN_FLR_6 | 10.9792 | 4.65 | 2936.4163 | |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1.00 | CORRIDOR_FLR_6 | GENERAL | CORRIDOR_FLR_6 | 3.6597 | 18.58 | 0.0000 | |
Total | 11345.29 | 8.9207 | 3.54 | 41.0885 | |||||||
Conditioned Total | 11345.29 | 8.9207 | 3.54 | 41.0885 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 11345.29 | 11345.29 | 0.00 | 0.00 | 4.6908 | 8.82 | 37.2165 |
Total | 11345.29 | 11345.29 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:57:58
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 20-JUL-18:10 | 16-JAN-17:00 | - | - | - | - | - | - | - | - | - | - | 02-JAN-21:10 |
Heating | 0.00 | 142208.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 235101.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 82800.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 79617.06 | 87521.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 32686.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 85055.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 10668.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 19111.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 4672.49 | 266372.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 2881.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 552594.89 | 496102.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 142208.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 235101.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 82800.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 49434.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 29240.64 | 74976.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 515.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 425.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 12545.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 1560.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 30153.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 972.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 85055.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 10668.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 19111.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 4672.49 | 266372.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 642.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 1179.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 1058.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:57:58
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 1501.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 5246.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 3718.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 830.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 5546.36 | 1939.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 2152.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 6876.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 704.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 1379.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 287.49 | 3389.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 233.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 26975.88 | 6829.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 132.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 462.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 327.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 73.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 488.87 | 170.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 189.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 606.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 62.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 121.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 25.34 | 298.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 20.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2377.72 | 601.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 132.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 462.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 327.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 73.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 488.87 | 170.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 189.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 606.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 62.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 121.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 25.34 | 298.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 20.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2377.72 | 601.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:57:58
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
BASEMENT VAV BOX COMPONENT | 3.05 | 0.494588 | 0.995000 | 3.03 | 1.00 | 0.500000 | 0.000770 | 0.000115 | 3.03 | 16.70 | 0.008000 |
RETAIL_1_FLR_1 VAV BOX COMPONENT | 0.441141 | 0.115855 | 0.995000 | 0.438935 | 0.995000 | 0.500000 | 0.003289 | 0.000040 | 0.438935 | 16.70 | 0.008000 |
RETAIL_2_FLR_1 VAV BOX COMPONENT | 0.292430 | 0.202386 | 0.995000 | 0.290968 | 0.995000 | 0.500000 | 0.001883 | 0.000019 | 0.290968 | 16.70 | 0.008000 |
MECH_FLR_1 VAV BOX COMPONENT | 0.296231 | 0.422486 | 0.995000 | 0.294750 | 1.00 | 0.500000 | 0.000902 | 0.000026 | 0.294750 | 16.70 | 0.008000 |
STORAGE_FLR_1 VAV BOX COMPONENT | 0.147617 | 0.489150 | 0.995000 | 0.146878 | 1.00 | 0.500000 | 0.000779 | 0.000015 | 0.146878 | 16.70 | 0.008000 |
LAUNDRY_FLR_1 VAV BOX COMPONENT | 3.97 | 0.059461 | 0.995000 | 3.95 | 0.995000 | 0.500000 | 0.025427 | 0.000170 | 3.95 | 16.70 | 0.008000 |
CAFE_FLR_1 VAV BOX COMPONENT | 1.86 | 0.077491 | 0.995000 | 1.85 | 0.995000 | 0.500000 | 0.004917 | 0.000130 | 1.85 | 16.70 | 0.008000 |
LOBBY_FLR_1 VAV BOX COMPONENT | 5.81 | 0.171581 | 0.995000 | 5.78 | 0.995000 | 0.500000 | 0.002221 | 0.000360 | 5.78 | 16.70 | 0.008000 |
CORRIDOR_FLR_3 VAV BOX COMPONENT | 1.45 | 0.820884 | 0.995000 | 1.44 | 1.00 | 0.500000 | 0.000464 | 0.000138 | 1.44 | 16.70 | 0.008000 |
BANQUET_FLR_6 VAV BOX COMPONENT | 2.78 | 0.091056 | 0.995000 | 2.76 | 0.995000 | 0.500000 | 0.004184 | 0.000161 | 2.76 | 16.70 | 0.008000 |
DINING_FLR_6 VAV BOX COMPONENT | 2.91 | 0.086797 | 0.995000 | 2.90 | 0.995000 | 0.500000 | 0.004390 | 0.000167 | 2.90 | 16.70 | 0.008000 |
KITCHEN_FLR_6 VAV BOX COMPONENT | 2.81 | 0.671783 | 0.995000 | 2.80 | 0.995000 | 0.500000 | 0.013601 | 0.000121 | 2.80 | 16.70 | 0.008000 |
CORRIDOR_FLR_6 VAV BOX COMPONENT | 0.908481 | 0.345675 | 0.995000 | 0.903938 | 0.995000 | 0.500000 | 0.001102 | 0.000093 | 0.903938 | 16.70 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
BASEMENT VAV BOX REHEAT COIL | 13173.56 | 0.000115 | 274.71 |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 4625.54 | 0.000040 | 104.22 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 2185.75 | 0.000019 | 47.38 |
MECH_FLR_1 VAV BOX REHEAT COIL | 2965.29 | 0.000026 | 66.40 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | 1657.71 | 0.000015 | 37.72 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 19387.04 | 0.000170 | 407.04 |
CAFE_FLR_1 VAV BOX REHEAT COIL | 14859.37 | 0.000130 | 324.25 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | 41161.84 | 0.000360 | 887.91 |
ROOM_1_FLR_3 FAN COIL HEATING COIL | 5974.04 | 0.000052 | 170.71 |
ROOM_2_FLR_3 FAN COIL HEATING COIL | 5973.71 | 0.000052 | 170.70 |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | 34371.24 | 0.000301 | 982.17 |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | 34381.88 | 0.000301 | 982.48 |
ROOM_5_FLR_3 FAN COIL HEATING COIL | 5974.04 | 0.000052 | 170.71 |
ROOM_6_FLR_3 FAN COIL HEATING COIL | 5973.71 | 0.000052 | 170.70 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 15782.72 | 0.000138 | 357.64 |
ROOM_1_FLR_6 FAN COIL HEATING COIL | 1874.25 | 0.000016 | 53.56 |
ROOM_2_FLR_6 FAN COIL HEATING COIL | 1875.26 | 0.000016 | 53.58 |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | 9023.85 | 0.000079 | 257.85 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | 18360.24 | 0.000161 | 393.74 |
DINING_FLR_6 VAV BOX REHEAT COIL | 19076.22 | 0.000167 | 408.77 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | 13792.57 | 0.000121 | 289.66 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 10668.74 | 0.000093 | 244.45 |
VAV WITH REHEAT HEATING COIL | 195220.44 | 0.001708 | 3266.92 |
FLR_3_DOAS HEATING COIL | 15066.37 | 0.000132 | 252.13 |
User-Specified Maximum Flow Rate [m3/s] | |
LOBBY_FLR_1 EXHAUST FAN | 0.000000 |
BANQUET_FLR_6 EXHAUST FAN | 0.000000 |
DINING_FLR_6 EXHAUST FAN | 0.000000 |
Design Size Maximum Air Flow Rate [m3/s] | |
ROOM_1_FLR_3 DIRECT AIR | 0.061735 |
ROOM_2_FLR_3 DIRECT AIR | 0.061728 |
ROOM_3_MULT19_FLR_3 DIRECT AIR | 0.837072 |
ROOM_4_MULT19_FLR_3 DIRECT AIR | 0.837300 |
ROOM_5_FLR_3 DIRECT AIR | 0.061735 |
ROOM_6_FLR_3 DIRECT AIR | 0.061728 |
ROOM_1_FLR_6 DIRECT AIR | 0.015434 |
ROOM_2_FLR_6 DIRECT AIR | 0.015432 |
ROOM_3_MULT9_FLR_6 DIRECT AIR | 0.099154 |
Design Size Maximum Supply Air Flow Rate [m3/s] | Design Size Maximum Hot Water Flow [m3/s] | Design Size Maximum Cold Water Flow [m3/s] | |
ROOM_1_FLR_3 FAN COIL | 1.53 | 0.000052 | 0.000553 |
ROOM_2_FLR_3 FAN COIL | 1.51 | 0.000052 | 0.000547 |
ROOM_3_MULT19_FLR_3 FAN COIL | 8.39 | 0.000301 | 0.003024 |
ROOM_4_MULT19_FLR_3 FAN COIL | 8.29 | 0.000301 | 0.003112 |
ROOM_5_FLR_3 FAN COIL | 1.35 | 0.000052 | 0.000488 |
ROOM_6_FLR_3 FAN COIL | 1.34 | 0.000052 | 0.000484 |
ROOM_1_FLR_6 FAN COIL | 0.412273 | 0.000016 | 0.000149 |
ROOM_2_FLR_6 FAN COIL | 0.406916 | 0.000016 | 0.000147 |
ROOM_3_MULT9_FLR_6 FAN COIL | 1.70 | 0.000079 | 0.000625 |
Design Size Maximum Flow Rate [m3/s] | |
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | 1.53 |
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | 1.51 |
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | 8.39 |
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | 8.29 |
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | 1.35 |
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | 1.34 |
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | 0.412273 |
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | 0.406916 |
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | 1.70 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Temperature [C] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | Design Size Design Coil Load [W] | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | 22.79 | 6.70 | 0.008519 | 12.80 | 0.008500 | 0.000553 | 1.53 | |
ROOM_2_FLR_3 FAN COIL COOLING COIL | 22.79 | 6.70 | 0.008519 | 12.80 | 0.008500 | 0.000547 | 1.51 | |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | 22.79 | 6.70 | 0.008463 | 12.80 | 0.008463 | 0.003024 | 8.39 | |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | 22.78 | 6.70 | 0.008666 | 12.80 | 0.008500 | 0.003112 | 8.29 | |
ROOM_5_FLR_3 FAN COIL COOLING COIL | 22.79 | 6.70 | 0.008521 | 12.80 | 0.008500 | 0.000488 | 1.35 | |
ROOM_6_FLR_3 FAN COIL COOLING COIL | 22.79 | 6.70 | 0.008521 | 12.80 | 0.008500 | 0.000484 | 1.34 | |
ROOM_1_FLR_6 FAN COIL COOLING COIL | 22.79 | 6.70 | 0.008518 | 12.80 | 0.008500 | 0.000149 | 0.412273 | |
ROOM_2_FLR_6 FAN COIL COOLING COIL | 22.79 | 6.70 | 0.008518 | 12.80 | 0.008500 | 0.000147 | 0.406916 | |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | 22.79 | 6.70 | 0.008577 | 12.80 | 0.008500 | 0.000625 | 1.70 | |
VAV WITH REHEAT COOLING COIL | 35.10 | 6.70 | 0.005699 | 10.57 | 0.005699 | 0.023419 | 26.58 | 655657.86 |
FLR_3_DOAS COOLING COIL | 35.10 | 6.70 | 0.005699 | 11.74 | 0.005699 | 0.001722 | 2.05 | 48199.93 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV WITH REHEAT | 26.58 | 26.58 | 26.71 | 26.58 | 26.58 | 26.58 | 0.300000 | 1.00 | 26.58 |
FLR_3_DOAS | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 0.300000 | 1.00 | 2.05 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV WITH REHEAT_OA_CONTROLLER | 26.58 | 26.57 |
FLR_3_DOAS_OA_CONTROLLER | 2.05 | 2.05 |
Design Size Nominal Supply Air Flow Rate [m3/s] | |
VAV WITH REHEAT OA HEAT RECOVERY | 26.57 |
Design Size Maximum Flow Rate [m3/s] | |
VAV WITH REHEAT FAN | 26.58 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV WITH REHEAT_COOLC_CONTROLLER | 0.023419 | 0.000020 |
VAV WITH REHEAT_HEATC_CONTROLLER | 0.001708 | |
FLR_3_DOAS_COOLC_CONTROLLER | 0.001722 | 0.000277 |
FLR_3_DOAS_HEATC_CONTROLLER | 0.000132 |
User-Specified Maximum Flow Rate [m3/s] | |
FLR_3_DOAS FAN | 2.05 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.034271 | 7062.08 | |
HEATSYS1 PUMP | 0.004317 | 1299.95 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
HEATSYS1 | 0.004317 | 0.517983 |
COOLSYS1 | 0.034271 | 4.11 |
SWHSYS1 | 0.000375 | 0.045004 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 493405.38 | 493405.38 | 0.004317 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 PUMP | 0.034271 | 4889.31 |
SWHSYS1 PUMP | 0.000375 | 47.91 |
Design Size Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Fluid Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.034271 | 959509.69 | 960212.92 | 109.46 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000375 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:57:58
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesPossible Shadow Receivers | |
RETAIL_1_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
CAFE_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
LOBBY_FLR_1_CEILING_2 | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
Possible Shadow Receivers | |
RETAIL_1_FLR_1_WALL_SOUTH | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | |
RETAIL_2_FLR_1_WALL_WEST | RETAIL_2_FLR_1_WALL_WEST_DOOR | |
STORAGE_FLR_1_WALL_NORTH | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | |
LAUNDRY_FLR_1_WALL_EAST | LAUNDRY_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_EAST | CAFE_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_SOUTH | CAFE_FLR_1_WALL_SOUTH_WINDOW | |
LOBBY_FLR_1_WALL_1_NORTH | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | |
LOBBY_FLR_1_WALL_1_SOUTH | LOBBY_FLR_1_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_SOUTH | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_WEST | ROOM_1_FLR_3_WALL_WEST_WINDOW | |
ROOM_2_FLR_3_WALL_NORTH | ROOM_2_FLR_3_WALL_NORTH_WINDOW | |
ROOM_2_FLR_3_WALL_WEST | ROOM_2_FLR_3_WALL_WEST_WINDOW | |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_4_MULT19_FLR_3_WALL_NORTH | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | |
ROOM_5_FLR_3_WALL_EAST | ROOM_5_FLR_3_WALL_EAST_WINDOW | |
ROOM_5_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_6_FLR_3_WALL_NORTH | ROOM_6_FLR_3_WALL_NORTH_WINDOW | |
ROOM_6_FLR_3_WALL_EAST | ROOM_6_FLR_3_WALL_EAST_WINDOW | |
CORRIDOR_FLR_3_WALL_1_NORTH | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_NORTH | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_SOUTH | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_WEST | ROOM_1_FLR_6_WALL_WEST_WINDOW | |
ROOM_2_FLR_6_WALL_NORTH | ROOM_2_FLR_6_WALL_NORTH_WINDOW | |
ROOM_2_FLR_6_WALL_WEST | ROOM_2_FLR_6_WALL_WEST_WINDOW | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | |
BANQUET_FLR_6_WALL_NORTH | BANQUET_FLR_6_WALL_NORTH_WINDOW | |
DINING_FLR_6_WALL_NORTH | DINING_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_NORTH | KITCHEN_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_EAST | KITCHEN_FLR_6_WALL_EAST_WINDOW | |
KITCHEN_FLR_6_WALL_1_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_6_WALL_1_NORTH | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_NORTH | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:57:58
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:57:58
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.70 | 7.00 | 2.10 | 2.60 | 4.30 | 8.80 | 13.90 | 17.80 | 23.20 | 25.60 | 24.10 | 20.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Albuquerque Intl Sunport NM USA TMY3 WMO#=723650 | 35.04 | -106.62 | -7.00 | 1619.00 | 83328 | 0.9904 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 13.63 | 23.50 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | HotelLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | DOE-2 |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 22 | 235 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 41.45 | 11.51 | -1.22 | 1 | 1 | 1 | 0.00 | 86.56 | 0.00 | 22.86 | -2.44 | 0.00 | 2.44 | 4826.41 | TARP | DOE-2 | 1978.83 | 0.00 | 0.00 | 0.00 | 13 | 0 | 0 | Yes |
2 | RETAIL_1_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 2.90 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 265.76 | TARP | DOE-2 | 67.07 | 68.84 | 45.58 | 23.26 | 6 | 1 | 0 | Yes |
3 | RETAIL_2_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 9.14 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 5.79 | 12.50 | 0.00 | 3.96 | 3.96 | 307.76 | TARP | DOE-2 | 77.67 | 26.57 | 24.62 | 0.00 | 6 | 1 | 0 | Yes |
4 | MECH_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 61.87 | 17.68 | 1.98 | 1 | 1 | 1 | 53.95 | 69.80 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 650.80 | TARP | DOE-2 | 164.24 | 62.80 | 62.80 | 0.00 | 6 | 0 | 0 | Yes |
5 | STORAGE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 74.37 | 17.68 | 1.98 | 1 | 1 | 1 | 69.80 | 78.94 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 375.47 | TARP | DOE-2 | 94.76 | 36.23 | 28.80 | 0.00 | 6 | 1 | 0 | Yes |
6 | LAUNDRY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 14.33 | 1.98 | 1 | 1 | 1 | 81.99 | 86.56 | 5.79 | 22.86 | 0.00 | 3.96 | 3.96 | 309.22 | TARP | DOE-2 | 78.04 | 85.75 | 83.80 | 0.00 | 6 | 1 | 0 | Yes |
7 | CAFE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 70.26 | 2.90 | 1.98 | 1 | 1 | 1 | 53.95 | 86.56 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 748.35 | TARP | DOE-2 | 188.86 | 152.17 | 84.72 | 65.50 | 7 | 2 | 0 | Yes |
8 | LOBBY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 38.29 | 12.45 | 1.98 | 1 | 1 | 1 | 0.00 | 81.99 | 0.00 | 22.86 | 0.00 | 3.96 | 3.96 | 5183.56 | TARP | DOE-2 | 1308.19 | 434.79 | 345.80 | 85.08 | 18 | 3 | 0 | Yes |
9 | ROOM_1_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
10 | ROOM_2_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
11 | ROOM_3_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 8.53 | 9.14 | 8.53 | 1 | 76 | 1 | 6.71 | 10.36 | 5.79 | 12.50 | 7.01 | 10.06 | 3.05 | 74.75 | TARP | DOE-2 | 24.52 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
12 | ROOM_4_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 12.19 | 19.51 | 8.53 | 1 | 76 | 1 | 10.36 | 14.02 | 16.15 | 22.86 | 7.01 | 10.06 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
13 | ROOM_5_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 10.06 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
14 | ROOM_6_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 18.59 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
15 | CORRIDOR_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 43.28 | 14.33 | 8.53 | 1 | 4 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 7.01 | 10.06 | 3.05 | 1186.91 | TARP | DOE-2 | 389.40 | 48.31 | 32.37 | 15.94 | 20 | 4 | 0 | Yes |
16 | ROOM_1_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 16.15 | 19.20 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
17 | ROOM_2_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 16.15 | 19.20 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
18 | ROOM_3_MULT9_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 7.93 | 7.62 | 17.68 | 1 | 9 | 1 | 4.57 | 11.28 | 5.79 | 9.45 | 16.15 | 19.20 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 20.44 | 13.70 | 6.74 | 6 | 1 | 0 | Yes |
19 | BANQUET_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 26.37 | 17.68 | 17.68 | 1 | 1 | 1 | 10.36 | 42.37 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.36 | 32.19 | 6 | 1 | 0 | Yes |
20 | DINING_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 63.55 | 17.68 | 17.68 | 1 | 1 | 1 | 47.55 | 79.55 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.36 | 32.19 | 6 | 1 | 0 | Yes |
21 | KITCHEN_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 82.99 | 14.11 | 17.68 | 1 | 1 | 1 | 79.55 | 86.56 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 314.87 | TARP | DOE-2 | 103.30 | 87.33 | 60.96 | 26.37 | 8 | 3 | 0 | Yes |
22 | CORRIDOR_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 41.51 | 13.35 | 17.68 | 1 | 1 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 1256.16 | TARP | DOE-2 | 412.12 | 85.47 | 57.27 | 28.20 | 15 | 3 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 1978.83 | 106.5 | 18.581 | 5.382E-002 | 8.749 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 14.129 | No |
2 | RETAIL_1_FLR_1 | 67.07 | 10.8 | 6.194 | 0.161 | 13.012 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 23.772 | No |
3 | RETAIL_2_FLR_1 | 77.67 | 12.5 | 6.194 | 0.161 | 13.012 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 23.772 | No |
4 | MECH_FLR_1 | 164.24 | 2.7 | 61.932 | 1.615E-002 | 10.064 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 15.444 | No |
5 | STORAGE_FLR_1 | 94.76 | 2.0 | 46.451 | 2.153E-002 | 7.319 | 2.690 | 0.000 | 0.000 | 0.000 | 0.000 | 10.009 | No |
6 | LAUNDRY_FLR_1 | 78.04 | 8.4 | 9.290 | 0.108 | 5.490 | 61.680 | 535.850 | 0.000 | 0.000 | 0.000 | 603.020 | No |
7 | CAFE_FLR_1 | 188.86 | 142.3 | 1.327 | 0.753 | 12.809 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 18.189 | No |
8 | LOBBY_FLR_1 | 1308.19 | 422.4 | 3.097 | 0.323 | 10.064 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.134 | No |
9 | ROOM_1_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 10.064 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 16.814 | No |
10 | ROOM_2_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 10.064 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 16.814 | No |
11 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 16.349 | 6.116E-002 | 10.064 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 20.584 | No |
12 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 10.064 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 20.584 | No |
13 | ROOM_5_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 10.064 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 16.814 | No |
14 | ROOM_6_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 10.064 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 16.814 | No |
15 | CORRIDOR_FLR_3 | 389.40 | 21.0 | 18.581 | 5.382E-002 | 3.660 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 3.660 | No |
16 | ROOM_1_FLR_6 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 10.064 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 16.814 | No |
17 | ROOM_2_FLR_6 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 10.064 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 16.814 | No |
18 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 10.064 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 20.584 | No |
19 | BANQUET_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 12.809 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 80.629 | No |
20 | DINING_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 12.809 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 80.629 | No |
21 | KITCHEN_FLR_6 | 103.30 | 22.2 | 4.645 | 0.215 | 10.979 | 517.156 | 2419.260 | 0.000 | 0.000 | 0.000 | 2947.395 | No |
22 | CORRIDOR_FLR_6 | 412.12 | 22.2 | 18.581 | 5.382E-002 | 3.660 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 3.660 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | BASEMENT PEOPLE | BLDG_OCC_SCH | BASEMENT | 1978.83 | 106.5 | 106.5 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 106 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | RETAIL_1_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 10.8 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | RETAIL_2_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 12.5 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 13 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | LAUNDRY_FLR_1 PEOPLE | BLDG_OCC_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 8.4 | 0.108 | 9.290 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 8 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | CAFE_FLR_1 PEOPLE | BLDG_OCC_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 142.3 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 142 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | LOBBY_FLR_1 PEOPLE | BLDG_OCC_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 422.4 | 0.323 | 3.097 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 422 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | ROOM_1_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | ROOM_2_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | ROOM_3_MULT19_FLR_3 PEOPLE | ALWAYS_OFF | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 1.5 | 6.116E-002 | 16.349 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 0 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | ROOM_4_MULT19_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | ROOM_5_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | ROOM_6_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | ROOM_1_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | ROOM_2_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | ROOM_3_MULT9_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | BANQUET_FLR_6 PEOPLE | BLDG_OCC_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | DINING_FLR_6 PEOPLE | BLDG_OCC_SCH | DINING_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | KITCHEN_FLR_6 PEOPLE | BLDG_OCC_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 22.2 | 0.215 | 4.645 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | STORAGE_FLR_1 PEOPLE | BLDG_OCC_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 2.0 | 2.153E-002 | 46.451 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | CORRIDOR_FLR_3 PEOPLE | BLDG_OCC_SCH | CORRIDOR_FLR_3 | 389.40 | 21.0 | 21.0 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 21 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
21 | CORRIDOR_FLR_6 PEOPLE | BLDG_OCC_SCH | CORRIDOR_FLR_6 | 412.12 | 22.2 | 22.2 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
22 | MECH_FLR_1 PEOPLE | BLDG_OCC_SCH | MECH_FLR_1 | 164.24 | 2.7 | 2.7 | 1.615E-002 | 61.932 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 3 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_BASEMENT | BASEMENT | 1978.83 | 106.5 | 17313.725 | 8.749 | 162.572 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 17313.725 |
2 | RETAIL_1_FLR_1_LIGHTS | LTG_SCH_RETAIL | RETAIL_1_FLR_1 | 67.07 | 10.8 | 872.757 | 13.012 | 80.594 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 872.757 |
3 | RETAIL_2_FLR_1_LIGHTS | LTG_SCH_RETAIL | RETAIL_2_FLR_1 | 77.67 | 12.5 | 1010.656 | 13.012 | 80.595 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1010.656 |
4 | MECH_FLR_1_LIGHTS | LTG_SCH_MECHANIC | MECH_FLR_1 | 164.24 | 2.7 | 1652.984 | 10.064 | 623.297 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1652.984 |
5 | STORAGE_FLR_1_LIGHTS | LTG_SCH_STORAGE | STORAGE_FLR_1 | 94.76 | 2.0 | 693.586 | 7.319 | 339.993 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 693.586 |
6 | LAUNDRY_FLR_1_LIGHTS | LTG_SCH_LAUNDRY | LAUNDRY_FLR_1 | 78.04 | 8.4 | 428.405 | 5.490 | 51.001 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 428.405 |
7 | CAFE_FLR_1_LIGHTS | LTG_SCH_DINING | CAFE_FLR_1 | 188.86 | 142.3 | 2419.140 | 12.809 | 17.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2419.140 |
8 | LOBBY_FLR_1_LIGHTS | LTG_SCH_LOBBY | LOBBY_FLR_1 | 1308.19 | 422.4 | 13165.908 | 10.064 | 31.167 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 13165.908 |
9 | ROOM_1_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_1_FLR_3 | 39.02 | 1.5 | 392.727 | 10.064 | 261.818 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 392.727 |
10 | ROOM_2_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_2_FLR_3 | 39.02 | 1.5 | 392.681 | 10.064 | 261.787 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 392.681 |
11 | ROOM_3_MULT19_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 246.814 | 10.064 | 164.543 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 246.814 |
12 | ROOM_4_MULT19_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 246.881 | 10.064 | 164.588 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 246.881 |
13 | ROOM_5_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_5_FLR_3 | 39.02 | 1.5 | 392.727 | 10.064 | 261.818 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 392.727 |
14 | ROOM_6_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_6_FLR_3 | 39.02 | 1.5 | 392.681 | 10.064 | 261.787 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 392.681 |
15 | CORRIDOR_FLR_3_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_FLR_3 | 389.40 | 21.0 | 1425.114 | 3.660 | 68.002 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1425.114 |
16 | ROOM_1_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_1_FLR_6 | 39.02 | 1.5 | 392.727 | 10.064 | 261.818 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 392.727 |
17 | ROOM_2_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_2_FLR_6 | 39.02 | 1.5 | 392.681 | 10.064 | 261.787 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 392.681 |
18 | ROOM_3_MULT9_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 246.881 | 10.064 | 164.588 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 246.881 |
19 | BANQUET_FLR_6_LIGHTS | LTG_SCH_DINING | BANQUET_FLR_6 | 331.66 | 249.9 | 4248.214 | 12.809 | 17.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 4248.214 |
20 | DINING_FLR_6_LIGHTS | LTG_SCH_DINING | DINING_FLR_6 | 331.66 | 249.9 | 4248.214 | 12.809 | 17.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 4248.214 |
21 | KITCHEN_FLR_6_LIGHTS | LTG_SCH_KITCHEN | KITCHEN_FLR_6 | 103.30 | 22.2 | 1134.198 | 10.979 | 51.003 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1134.198 |
22 | CORRIDOR_FLR_6_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_FLR_6 | 412.12 | 22.2 | 1508.264 | 3.660 | 68.001 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1508.264 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | BASEMENT_EQUIP_SCH | BASEMENT | 1978.83 | 106.5 | 10646.106 | 5.380 | 99.964 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10646.106 |
2 | RETAIL_1_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 721.688 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 721.688 |
3 | RETAIL_2_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 835.717 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 835.717 |
4 | MECH_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | MECH_FLR_1 | 164.24 | 2.7 | 883.628 | 5.380 | 333.193 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 883.628 |
5 | STORAGE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 254.902 | 2.690 | 124.952 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 254.902 |
6 | LAUNDRY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 4813.474 | 61.680 | 573.033 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 4813.474 |
7 | CAFE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 1016.077 | 5.380 | 7.140 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1016.077 |
8 | LOBBY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 10557.062 | 8.070 | 24.991 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10557.062 |
9 | ROOM_1_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_1_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
10 | ROOM_2_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_2_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
11 | ROOM_3_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 257.991 | 10.520 | 171.994 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 257.991 |
12 | ROOM_4_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
13 | ROOM_5_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_5_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
14 | ROOM_6_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_6_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
15 | ROOM_1_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_1_FLR_6 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
16 | ROOM_2_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_2_FLR_6 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
17 | ROOM_3_MULT9_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
18 | BANQUET_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
19 | DINING_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | DINING_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
20 | KITCHEN_FLR_6_MISCELEC_EQUIP | KITCHEN_ELEC_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 52482.799 | 508.040 | 2360.050 | 0.200 | 0.500 | 0.100 | 0.200 | Cooking | 0.000 | 15744.840 |
21 | KITCHEN_FLR_6_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 515.917 | 4.994 | 23.200 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 515.917 | 515.917 |
22 | KITCHEN_FLR_6_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 425.833 | 4.122 | 19.149 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 425.833 | 425.833 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LAUNDRY_FLR_1_MISCGAS_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 41817.449 | 535.850 | 4978.268 | 0.000 | 0.500 | 0.000 | 0.500 | Laundry | 0.000 | 41817.449 |
2 | KITCHEN_FLR_6_MISCGAS_EQUIP | KITCHEN_GAS_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 249920.353 | 2419.260 | 11238.437 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 74976.106 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.464 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | OVERHEAD DOOR_CON | 2 | 1 | 1 | 0.167 | 1.198 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
3 | INTERIORFURNISHINGS | 3 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 8 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 18 | 3 | 3 | 0.167 | 0.2284 | 0.900 | 0.900 | 0.770 | 0.700 | Rough |
6 | RES_ROOF | 19 | 3 | 3 | 0.167 | 0.2284 | 0.900 | 0.900 | 0.770 | 0.700 | Rough |
7 | NONRES_EXT_WALL_GRD | 21 | 3 | 9 | 0.167 | 0.9242 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | NONRES_EXT_WALL_MID | 22 | 3 | 9 | 0.167 | 1.217 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | NONRES_EXT_WALL_TOP | 23 | 3 | 9 | 0.167 | 1.286 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | RES_EXT_WALL_MID | 25 | 3 | 9 | 0.167 | 1.107 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | RES_EXT_WALL_TOP | 26 | 3 | 9 | 0.167 | 1.174 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | NONRES_FLOOR | 30 | 3 | 7 | 0.167 | 0.1963 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
13 | NONRES_FLOOR_CEILING | 33 | 3 | 7 | 0.167 | 0.1963 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
14 | BASEMENT_FLOOR | 36 | 2 | 7 | 0.333 | 2.705 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
15 | BASEMENT_WALL_NORTH_CFACTOR | 39 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | BASEMENT_WALL_EAST_CFACTOR | 40 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | BASEMENT_WALL_SOUTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
18 | BASEMENT_WALL_WEST_CFACTOR | 42 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2887 |
2 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8346 |
3 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
10 | RES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
11 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
12 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
13 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9147 |
14 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.6546 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.6103 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | RES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7359 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
25 | RES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.6841 |
26 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
27 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.833 |
28 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
29 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
30 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
31 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
32 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.833 |
33 | M10 200MM CONCRETE BLOCK BASEMENT WALL | 0.2032 | 1.326 | 1842.000 | 912.000 | 0.1532 |
34 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
35 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
36 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
37 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
38 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
39 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
40 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
41 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
42 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.4637404 | 3.4637404 | 3.4637404 | |
3 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
4 | 0 | 1.1981135 | 1.1981135 | 1.1981135 | |
5 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
6 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
7 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
8 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
9 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
10 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
11 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
12 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
13 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
14 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
15 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
16 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
17 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
18 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
19 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
20 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
21 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
22 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
23 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
24 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
25 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
26 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
27 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
28 | 9 | -0.28612306E-14 | 0.35438919E-16 | -0.14997333E-09 | 0.48037931E-16 |
29 | 8 | 0.21910456E-07 | 0.12451452E-12 | 0.37817107E-03 | -0.24912943E-09 |
30 | 7 | -0.12252860E-01 | 0.64616398E-08 | -0.23102096E-01 | 0.13931948E-03 |
31 | 6 | 0.40565756 | 0.22511349E-05 | 0.47235308 | -0.47513834E-02 |
32 | 5 | -5.1935619 | 0.84157732E-04 | -4.4432762 | 0.63221026E-01 |
33 | 4 | 33.016121 | 0.68920660E-03 | 21.448225 | -0.42229901 |
34 | 3 | -111.25447 | 0.15035857E-02 | -55.639617 | 1.5156026 |
35 | 2 | 197.15924 | 0.84653085E-03 | 77.889127 | -2.9011628 |
36 | 1 | -171.17492 | 0.90445513E-04 | -55.258822 | 2.7457697 |
37 | 0 | 57.057407 | 0.51539406E-06 | 15.557951 | |
38 | 9 | 0.12430042E-14 | 0.43603463E-16 | -0.13615479E-09 | -0.52742981E-17 |
39 | 8 | 0.19963588E-07 | 0.16114398E-12 | 0.35741204E-03 | -0.22699287E-09 |
40 | 7 | -0.11632381E-01 | 0.85488282E-08 | -0.22208377E-01 | 0.13226440E-03 |
41 | 6 | 0.38879653 | 0.30047059E-05 | 0.45796739 | -0.45526330E-02 |
42 | 5 | -5.0290001 | 0.11318598E-03 | -4.3326723 | 0.61180550E-01 |
43 | 4 | 32.288109 | 0.93328928E-03 | 21.015642 | -0.41263319 |
44 | 3 | -109.70522 | 0.20484795E-02 | -54.784283 | 1.4932205 |
45 | 2 | 195.62339 | 0.11595496E-02 | 77.105128 | -2.8767741 |
46 | 1 | -170.60747 | 0.12450863E-03 | -55.031726 | 2.7358244 |
47 | 0 | 57.057407 | 0.71328115E-06 | 15.596176 | |
48 | 9 | 0.10418955E-14 | 0.45554749E-16 | -0.13285794E-09 | -0.34221686E-17 |
49 | 8 | 0.19498290E-07 | 0.16949498E-12 | 0.35235048E-03 | -0.22170227E-09 |
50 | 7 | -0.11480752E-01 | 0.90423087E-08 | -0.21989859E-01 | 0.13054032E-03 |
51 | 6 | 0.38467563 | 0.31853038E-05 | 0.45444290 | -0.45040579E-02 |
52 | 5 | -4.9887746 | 0.12022067E-03 | -4.3055366 | 0.60681782E-01 |
53 | 4 | 32.110117 | 0.99300969E-03 | 20.909427 | -0.41027004 |
54 | 3 | -109.32633 | 0.21828955E-02 | -54.574228 | 1.4877470 |
55 | 2 | 195.24766 | 0.12373115E-02 | 76.912747 | -2.8708078 |
56 | 1 | -170.46860 | 0.13302463E-03 | -54.976289 | 2.7333905 |
57 | 0 | 57.057407 | 0.76310210E-06 | 15.605744 | |
58 | 9 | -0.19728226E-15 | 0.38070760E-16 | -0.14134637E-09 | 0.10329039E-17 |
59 | 8 | 0.20696804E-07 | 0.14765672E-12 | 0.36530744E-03 | -0.23532978E-09 |
60 | 7 | -0.11868633E-01 | 0.77667999E-08 | -0.22548754E-01 | 0.13495068E-03 |
61 | 6 | 0.39521686 | 0.27204939E-05 | 0.46345169 | -0.46283129E-02 |
62 | 5 | -5.0916664 | 0.10217830E-03 | -4.3748670 | 0.61957574E-01 |
63 | 4 | 32.565369 | 0.84029717E-03 | 21.180735 | -0.41631434 |
64 | 3 | -110.29532 | 0.18400486E-02 | -55.110745 | 1.5017457 |
65 | 2 | 196.20849 | 0.10394005E-02 | 77.404245 | -2.8860650 |
66 | 1 | -170.82368 | 0.11139293E-03 | -55.118150 | 2.7396138 |
67 | 0 | 57.057407 | 0.63685742E-06 | 15.581450 | |
68 | 9 | 0.13059652E-14 | 0.41030072E-16 | -0.13816519E-09 | -0.47111965E-17 |
69 | 8 | 0.20247126E-07 | 0.15597406E-12 | 0.36047671E-03 | -0.23021680E-09 |
70 | 7 | -0.11724123E-01 | 0.82470298E-08 | -0.22340566E-01 | 0.13330755E-03 |
71 | 6 | 0.39128975 | 0.28947446E-05 | 0.46009809 | -0.45820219E-02 |
72 | 5 | -5.0533361 | 0.10891817E-03 | -4.3490697 | 0.61482301E-01 |
73 | 4 | 32.395785 | 0.89717001E-03 | 21.079809 | -0.41406279 |
74 | 3 | -109.93440 | 0.19673976E-02 | -54.911173 | 1.4965315 |
75 | 2 | 195.85064 | 0.11127485E-02 | 77.221372 | -2.8803827 |
76 | 1 | -170.69145 | 0.11939355E-03 | -55.065279 | 2.7372963 |
77 | 0 | 57.057407 | 0.68346468E-06 | 15.590432 | |
78 | 7 | -0.15963512E-14 | -0.15187529E-16 | -0.22427203E-13 | 0.56155309E-15 |
79 | 6 | 0.17983713E-10 | 0.23594901E-11 | 0.52322926E-09 | -0.18637893E-10 |
80 | 5 | -0.60139213E-07 | 0.11510628E-07 | -0.21924491E-05 | 0.17161312E-06 |
81 | 4 | 0.62746279E-04 | 0.43399923E-05 | 0.17681060E-02 | -0.28244642E-03 |
82 | 3 | -0.90508353E-02 | 0.15320797E-03 | -0.21560640 | 0.43341486E-01 |
83 | 2 | 0.12836503 | 0.66328859E-03 | 2.9007871 | -0.61911613 |
84 | 1 | -0.32478029 | 0.41934727E-03 | -7.1379041 | 1.5697129 |
85 | 0 | 0.20664896 | 0.54311639E-05 | 4.4522013 | |
86 | 7 | -0.22427203E-13 | -0.15187529E-16 | -0.15963512E-14 | 0.56155309E-15 |
87 | 6 | 0.52322926E-09 | 0.23594901E-11 | 0.17983713E-10 | -0.18637893E-10 |
88 | 5 | -0.21924491E-05 | 0.11510628E-07 | -0.60139213E-07 | 0.17161312E-06 |
89 | 4 | 0.17681060E-02 | 0.43399923E-05 | 0.62746279E-04 | -0.28244642E-03 |
90 | 3 | -0.21560640 | 0.15320797E-03 | -0.90508353E-02 | 0.43341486E-01 |
91 | 2 | 2.9007871 | 0.66328859E-03 | 0.12836503 | -0.61911613 |
92 | 1 | -7.1379041 | 0.41934727E-03 | -0.32478029 | 1.5697129 |
93 | 0 | 4.4522013 | 0.54311639E-05 | 0.20664896 | |
94 | 7 | -0.52459208E-15 | -0.63961428E-15 | -0.12292524E-09 | -0.35846135E-17 |
95 | 6 | 0.39860198E-02 | 0.96339020E-07 | 0.40499006E-03 | -0.70890431E-04 |
96 | 5 | -0.20832379 | 0.49172556E-04 | -0.20585669E-01 | 0.38489246E-02 |
97 | 4 | 3.5198270 | 0.18993977E-02 | 0.34924834 | -0.69168259E-01 |
98 | 3 | -23.366787 | 0.13311857E-01 | -2.4329538 | 0.50524779 |
99 | 2 | 64.890127 | 0.19943872E-01 | 7.3672511 | -1.5911358 |
100 | 1 | -76.040094 | 0.56792084E-02 | -9.5568013 | 2.1361271 |
101 | 0 | 31.242244 | 0.96490710E-04 | 4.3344156 | |
102 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
103 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
104 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
105 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
106 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
107 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
108 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
109 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
110 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
111 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
112 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
113 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
114 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
115 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
116 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
117 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
118 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
119 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
120 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
121 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
122 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
123 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
124 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
125 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
126 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
127 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
128 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
129 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
130 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
131 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
132 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
133 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.3856_SHGC_0.4 | 37 | 1 | VerySmooth | 2.191 | 2.191 | 1.000 | 0.401 | ||
2 | RESWINDOW_U_0.3856_SHGC_0.4 | 38 | 1 | VerySmooth | 2.191 | 2.191 | 1.000 | 0.401 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER | SpectralAverage | 3.40174E-002 | 0.31435 | 0.47878 | 0.47878 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11969 | 1.00000 | No | |
2 | RESIDENTIAL WINDOW GLAZING LAYER | SpectralAverage | 3.40174E-002 | 0.31435 | 0.47878 | 0.47878 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11969 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 7 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 1.500 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 3.000 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWH BOOSTER E WATER HEATER | 2.2712E-002 | 8000.0 | 1.240 | 1.1473 |
2 | WaterHeater:Mixed | SWH LAUNDRY G WATER HEATER | 1.1356 | 163316.0 | 0.576 | 0.5074 |
3 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 2.2712 | 175842.6 | 0.260 | 2.5713E-002 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
6 | BASEMENT_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
7 | BASEMENT_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
8 | BASEMENT_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
9 | BASEMENT_CEILING_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
10 | BASEMENT_CEILING_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
11 | BASEMENT_CEILING_6 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
12 | BASEMENT_CEILING_7 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
13 | BASEMENT_CEILING_8 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
14 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
15 | RETAIL_1_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 4 | No | No |
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 1 | No | No |
17 | RETAIL_1_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 3 | No | No |
18 | RETAIL_1_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
19 | RETAIL_1_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
20 | RETAIL_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
21 | RETAIL_1_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
23 | RETAIL_2_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
25 | RETAIL_2_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
26 | RETAIL_2_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
27 | RETAIL_2_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
28 | RETAIL_2_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
29 | RETAIL_2_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
31 | MECH_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
32 | MECH_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
33 | MECH_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
34 | MECH_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
35 | MECH_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
36 | MECH_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
37 | MECH_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
38 | STORAGE_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
40 | STORAGE_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
41 | STORAGE_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
42 | STORAGE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
43 | STORAGE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
44 | STORAGE_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
45 | STORAGE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
46 | LAUNDRY_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
47 | LAUNDRY_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
49 | LAUNDRY_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
50 | LAUNDRY_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
51 | LAUNDRY_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
52 | LAUNDRY_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
54 | CAFE_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 3 | No | No |
55 | CAFE_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
56 | CAFE_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 4 | No | No |
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 1 | No | No |
58 | CAFE_FLR_1_WALL_1_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
59 | CAFE_FLR_1_WALL_2_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
60 | CAFE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
61 | CAFE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
62 | CAFE_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
63 | CAFE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
64 | LOBBY_FLR_1_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
67 | LOBBY_FLR_1_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
68 | LOBBY_FLR_1_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 1 | No | No |
70 | LOBBY_FLR_1_WALL_1_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
71 | LOBBY_FLR_1_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
72 | LOBBY_FLR_1_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
73 | LOBBY_FLR_1_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
74 | LOBBY_FLR_1_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
75 | LOBBY_FLR_1_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
76 | LOBBY_FLR_1_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
77 | LOBBY_FLR_1_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
78 | LOBBY_FLR_1_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
79 | LOBBY_FLR_1_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
80 | LOBBY_FLR_1_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
81 | LOBBY_FLR_1_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
82 | LOBBY_FLR_1_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
83 | LOBBY_FLR_1_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
84 | LOBBY_FLR_1_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
85 | LOBBY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
86 | ROOM_1_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
88 | ROOM_1_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
90 | ROOM_1_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
91 | ROOM_1_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
92 | ROOM_1_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
93 | ROOM_1_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
94 | ROOM_1_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
95 | ROOM_2_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
97 | ROOM_2_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
99 | ROOM_2_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
100 | ROOM_2_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
101 | ROOM_2_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
102 | ROOM_2_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
103 | ROOM_2_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
109 | ROOM_3_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
110 | ROOM_3_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
117 | ROOM_4_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
118 | ROOM_4_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
120 | ROOM_5_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
122 | ROOM_5_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
124 | ROOM_5_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
125 | ROOM_5_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
126 | ROOM_5_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
127 | ROOM_5_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
128 | ROOM_5_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
129 | ROOM_6_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
131 | ROOM_6_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
133 | ROOM_6_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
134 | ROOM_6_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
135 | ROOM_6_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
136 | ROOM_6_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
137 | ROOM_6_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
138 | CORRIDOR_FLR_3_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
147 | CORRIDOR_FLR_3_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
148 | CORRIDOR_FLR_3_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
149 | CORRIDOR_FLR_3_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
150 | CORRIDOR_FLR_3_WALL_4_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
152 | CORRIDOR_FLR_3_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
153 | CORRIDOR_FLR_3_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
154 | CORRIDOR_FLR_3_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
155 | CORRIDOR_FLR_3_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
156 | CORRIDOR_FLR_3_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
157 | CORRIDOR_FLR_3_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
158 | CORRIDOR_FLR_3_FLOOR_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
159 | CORRIDOR_FLR_3_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
160 | CORRIDOR_FLR_3_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
161 | CORRIDOR_FLR_3_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
163 | ROOM_1_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
165 | ROOM_1_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
167 | ROOM_1_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
168 | ROOM_1_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
169 | ROOM_1_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
170 | ROOM_1_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
171 | ROOM_1_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
172 | ROOM_2_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
174 | ROOM_2_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
176 | ROOM_2_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
177 | ROOM_2_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
178 | ROOM_2_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
179 | ROOM_2_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
180 | ROOM_2_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 3 | No | No |
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 2 | No | No |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
186 | ROOM_3_MULT9_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
187 | ROOM_3_MULT9_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
189 | BANQUET_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
191 | BANQUET_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
192 | BANQUET_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
193 | BANQUET_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
194 | BANQUET_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
195 | BANQUET_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
196 | BANQUET_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
197 | DINING_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
198 | DINING_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
199 | DINING_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
200 | DINING_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
201 | DINING_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
202 | DINING_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
203 | DINING_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
204 | DINING_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
205 | KITCHEN_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
207 | KITCHEN_FLR_6_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
212 | KITCHEN_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
213 | KITCHEN_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
214 | KITCHEN_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
215 | KITCHEN_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
216 | KITCHEN_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
217 | CORRIDOR_FLR_6_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
224 | CORRIDOR_FLR_6_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
226 | CORRIDOR_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
227 | CORRIDOR_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
228 | CORRIDOR_FLR_6_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
229 | CORRIDOR_FLR_6_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
230 | CORRIDOR_FLR_6_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
231 | CORRIDOR_FLR_6_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
232 | CORRIDOR_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
233 | CORRIDOR_FLR_6_CEILING_1 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
234 | CORRIDOR_FLR_6_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | RETAIL_1_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 3.921E-002 | 5.846E-004 | 2.885E-004 | 0.531 | 1.000 | 0.000 | 0.000 | 0.000 |
2 | RETAIL_2_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 1.513E-002 | 1.949E-004 | 5.306E-004 | 0.177 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | MECH_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | MECH_FLR_1 | 164.24 | 2.7 | 3.577E-002 | 2.178E-004 | 5.696E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
4 | STORAGE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 2.064E-002 | 2.178E-004 | 4.726E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | LAUNDRY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 4.884E-002 | 6.258E-004 | 5.569E-004 | 0.569 | 1.000 | 0.000 | 0.000 | 0.000 |
6 | CAFE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 8.667E-002 | 4.589E-004 | 2.527E-004 | 0.417 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | LOBBY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 0.248 | 1.893E-004 | 3.620E-004 | 0.172 | 1.000 | 0.000 | 0.000 | 0.000 |
8 | ROOM_1_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | ROOM_2_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
10 | ROOM_3_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 6.349E-003 | 2.589E-004 | 5.696E-004 | 0.306 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | ROOM_4_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 6.350E-003 | 2.589E-004 | 5.696E-004 | 0.306 | 1.000 | 0.000 | 0.000 | 0.000 |
12 | ROOM_5_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | ROOM_6_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
14 | CORRIDOR_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_3 | 389.40 | 21.0 | 2.751E-002 | 7.066E-005 | 5.696E-004 | 8.345E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | ROOM_1_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 2.881E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
16 | ROOM_2_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 2.881E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | ROOM_3_MULT9_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 1.164E-002 | 4.746E-004 | 2.589E-004 | 0.561 | 1.000 | 0.000 | 0.000 | 0.000 |
18 | BANQUET_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 5.556E-002 | 1.675E-004 | 1.295E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | DINING_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | DINING_FLR_6 | 331.66 | 249.9 | 5.556E-002 | 1.675E-004 | 1.295E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
20 | KITCHEN_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 4.974E-002 | 4.815E-004 | 2.609E-004 | 0.569 | 1.000 | 0.000 | 0.000 | 0.000 |
21 | CORRIDOR_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_6 | 412.12 | 22.2 | 4.868E-002 | 1.181E-004 | 9.784E-005 | 0.140 | 1.000 | 0.000 | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | ROOM_1_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
2 | ROOM_2_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
3 | ROOM_3_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
4 | ROOM_4_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
5 | ROOM_5_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_5_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
6 | ROOM_6_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_6_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
7 | ROOM_1_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
8 | ROOM_2_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
9 | ROOM_3_MULT9_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | RETAIL_1_FLR_1 | Mixing/Well-Stirred |
3 | RETAIL_2_FLR_1 | Mixing/Well-Stirred |
4 | MECH_FLR_1 | Mixing/Well-Stirred |
5 | STORAGE_FLR_1 | Mixing/Well-Stirred |
6 | LAUNDRY_FLR_1 | Mixing/Well-Stirred |
7 | CAFE_FLR_1 | Mixing/Well-Stirred |
8 | LOBBY_FLR_1 | Mixing/Well-Stirred |
9 | ROOM_1_FLR_3 | Mixing/Well-Stirred |
10 | ROOM_2_FLR_3 | Mixing/Well-Stirred |
11 | ROOM_3_MULT19_FLR_3 | Mixing/Well-Stirred |
12 | ROOM_4_MULT19_FLR_3 | Mixing/Well-Stirred |
13 | ROOM_5_FLR_3 | Mixing/Well-Stirred |
14 | ROOM_6_FLR_3 | Mixing/Well-Stirred |
15 | CORRIDOR_FLR_3 | Mixing/Well-Stirred |
16 | ROOM_1_FLR_6 | Mixing/Well-Stirred |
17 | ROOM_2_FLR_6 | Mixing/Well-Stirred |
18 | ROOM_3_MULT9_FLR_6 | Mixing/Well-Stirred |
19 | BANQUET_FLR_6 | Mixing/Well-Stirred |
20 | DINING_FLR_6 | Mixing/Well-Stirred |
21 | KITCHEN_FLR_6 | Mixing/Well-Stirred |
22 | CORRIDOR_FLR_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 34511.35070 | 34511.35070 | 3.04874 | 3.04874 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 20:00:00 | 28.35000 | 5.68899E-003 | 1978.83018 | 106.49900 | 0.85446 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 0.85446 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -7.90000 | 2.34317E-003 | 1978.83018 | 106.49900 | 0.85446 | 0.00000 |
3 | RETAIL_1_FLR_1 | Cooling | 4993.33648 | 4993.33648 | 0.44114 | 0.44114 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 34.76250 | 5.69886E-003 | 67.07136 | 10.82900 | 7.92179E-002 | 0.00000 |
4 | RETAIL_1_FLR_1 | Heating | 2720.99039 | 2720.99039 | 0.14179 | 0.14179 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -7.90000 | 2.34317E-003 | 67.07136 | 10.82900 | 7.92179E-002 | 0.00000 |
5 | RETAIL_2_FLR_1 | Cooling | 3309.91426 | 3309.91426 | 0.29243 | 0.29243 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 33.21000 | 5.69645E-003 | 77.66889 | 12.54000 | 9.17347E-002 | 0.00000 |
6 | RETAIL_2_FLR_1 | Heating | 923.24824 | 923.24824 | 4.81133E-002 | 9.17347E-002 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -7.90000 | 2.34317E-003 | 77.66889 | 12.54000 | 9.17347E-002 | 0.00000 |
7 | MECH_FLR_1 | Cooling | 3353.73600 | 3353.73600 | 0.29623 | 0.29623 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:20:00 | 31.18500 | 5.69333E-003 | 164.24319 | 2.65200 | 0.00000 | 0.00000 |
8 | MECH_FLR_1 | Heating | 1686.66534 | 1686.66534 | 8.78971E-002 | 8.78971E-002 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -7.90000 | 2.34317E-003 | 164.24319 | 2.65200 | 0.00000 | 0.00000 |
9 | STORAGE_FLR_1 | Cooling | 1671.20430 | 1671.20430 | 0.14762 | 0.14762 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:40:00 | 32.31000 | 5.69506E-003 | 94.75927 | 2.04000 | 5.77652E-002 | 0.00000 |
10 | STORAGE_FLR_1 | Heating | 1020.52602 | 1020.52602 | 5.31826E-002 | 5.77652E-002 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -7.90000 | 2.34317E-003 | 94.75927 | 2.04000 | 5.77652E-002 | 0.00000 |
11 | LAUNDRY_FLR_1 | Cooling | 44925.69652 | 44925.69652 | 3.96857 | 3.96857 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 34.96500 | 5.69918E-003 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
12 | LAUNDRY_FLR_1 | Heating | 2259.10585 | 2259.10585 | 0.11772 | 0.11772 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -7.90000 | 2.34317E-003 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
13 | CAFE_FLR_1 | Cooling | 21002.36710 | 21002.36710 | 1.85715 | 1.85715 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 34.76250 | 5.69886E-003 | 188.86188 | 142.30000 | 0.67639 | 0.00000 |
14 | CAFE_FLR_1 | Heating | 6840.58051 | 6840.58051 | 0.35648 | 0.67639 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -7.90000 | 2.34317E-003 | 188.86188 | 142.30000 | 0.67639 | 0.00000 |
15 | LOBBY_FLR_1 | Cooling | 65738.03737 | 65738.03737 | 5.80973 | 5.80973 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 34.87500 | 5.69904E-003 | 1308.18612 | 422.43500 | 1.89399 | 0.00000 |
16 | LOBBY_FLR_1 | Heating | 16078.57348 | 16078.57348 | 0.83790 | 1.89399 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -7.90000 | 2.34317E-003 | 1308.18612 | 422.43500 | 1.89399 | 0.00000 |
17 | ROOM_1_FLR_3 | Cooling | 12830.78883 | 12830.78883 | 1.52728 | 1.52728 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 33.39000 | 5.69673E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
18 | ROOM_1_FLR_3 | Heating | 5974.18609 | 5974.18609 | 0.31315 | 0.31315 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -7.90000 | 2.34317E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
19 | ROOM_2_FLR_3 | Cooling | 12688.03625 | 12688.03625 | 1.51029 | 1.51029 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 33.21000 | 5.69645E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
20 | ROOM_2_FLR_3 | Heating | 5973.85755 | 5973.85755 | 0.31313 | 0.31313 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -7.90000 | 2.34317E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
21 | ROOM_3_MULT19_FLR_3 | Cooling | 70473.90912 | 70473.90912 | 8.38843 | 8.38843 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 34.87500 | 5.69904E-003 | 24.52384 | 1.50000 | 0.83707 | 0.00000 |
22 | ROOM_3_MULT19_FLR_3 | Heating | 34371.65856 | 34371.65856 | 1.80172 | 1.80172 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -7.90000 | 2.34317E-003 | 24.52384 | 1.50000 | 0.83707 | 0.00000 |
23 | ROOM_4_MULT19_FLR_3 | Cooling | 69642.17803 | 69642.17803 | 8.29012 | 8.29012 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 34.96500 | 5.69918E-003 | 24.53055 | 1.50000 | 0.83730 | 0.00000 |
24 | ROOM_4_MULT19_FLR_3 | Heating | 34382.30086 | 34382.30086 | 1.80228 | 1.80228 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -7.90000 | 2.34317E-003 | 24.53055 | 1.50000 | 0.83730 | 0.00000 |
25 | ROOM_5_FLR_3 | Cooling | 11321.27722 | 11321.27722 | 1.34760 | 1.34760 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 | 29.58750 | 5.69088E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
26 | ROOM_5_FLR_3 | Heating | 5974.18609 | 5974.18609 | 0.31315 | 0.31315 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -7.90000 | 2.34317E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
27 | ROOM_6_FLR_3 | Cooling | 11222.08217 | 11222.08217 | 1.33579 | 1.33579 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 28.82250 | 5.68971E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
28 | ROOM_6_FLR_3 | Heating | 5973.85755 | 5973.85755 | 0.31313 | 0.31313 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -7.90000 | 2.34317E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
29 | CORRIDOR_FLR_3 | Cooling | 16367.76564 | 16367.76564 | 1.44589 | 1.44589 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 35.10000 | 5.69938E-003 | 389.40468 | 20.95700 | 0.47476 | 0.00000 |
30 | CORRIDOR_FLR_3 | Heating | 9538.88231 | 9538.88231 | 0.49711 | 0.49711 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -7.90000 | 2.34317E-003 | 389.40468 | 20.95700 | 0.47476 | 0.00000 |
31 | ROOM_1_FLR_6 | Cooling | 3463.53078 | 3463.53078 | 0.41227 | 0.41227 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 33.39000 | 5.69673E-003 | 39.02202 | 1.50000 | 1.54338E-002 | 0.00000 |
32 | ROOM_1_FLR_6 | Heating | 1874.29194 | 1874.29194 | 9.82454E-002 | 9.82454E-002 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -7.90000 | 2.34317E-003 | 39.02202 | 1.50000 | 1.54338E-002 | 0.00000 |
33 | ROOM_2_FLR_6 | Cooling | 3418.52251 | 3418.52251 | 0.40692 | 0.40692 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 33.21000 | 5.69645E-003 | 39.01745 | 1.50000 | 1.54319E-002 | 0.00000 |
34 | ROOM_2_FLR_6 | Heating | 1875.30139 | 1875.30139 | 9.82983E-002 | 9.82983E-002 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -7.90000 | 2.34317E-003 | 39.01745 | 1.50000 | 1.54319E-002 | 0.00000 |
35 | ROOM_3_MULT9_FLR_6 | Cooling | 14292.89601 | 14292.89601 | 1.70138 | 1.70138 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 34.98750 | 5.69921E-003 | 24.53055 | 1.50000 | 9.91540E-002 | 0.00000 |
36 | ROOM_3_MULT9_FLR_6 | Heating | 9024.02031 | 9024.02031 | 0.47302 | 0.47302 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -7.90000 | 2.34317E-003 | 24.53055 | 1.50000 | 9.91540E-002 | 0.00000 |
37 | BANQUET_FLR_6 | Cooling | 31377.51464 | 31377.51464 | 2.77548 | 2.77548 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 35.10000 | 5.69938E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
38 | BANQUET_FLR_6 | Heating | 6373.40660 | 6373.40660 | 0.33214 | 1.18780 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -7.90000 | 2.34317E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
39 | DINING_FLR_6 | Cooling | 32917.62744 | 32917.62744 | 2.91166 | 2.91166 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 35.10000 | 5.69938E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
40 | DINING_FLR_6 | Heating | 6502.07699 | 6502.07699 | 0.33884 | 1.18780 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 19:20:00 | -7.90000 | 2.34317E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
41 | KITCHEN_FLR_6 | Cooling | 31723.09595 | 31723.09595 | 2.81012 | 2.81012 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 33.88500 | 5.69749E-003 | 103.30446 | 22.23800 | 0.36735 | 0.00000 |
42 | KITCHEN_FLR_6 | Heating | 1698.11266 | 1698.11266 | 8.84797E-002 | 0.36735 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | -7.90000 | 2.34317E-003 | 103.30446 | 22.23800 | 0.36735 | 0.00000 |
43 | CORRIDOR_FLR_6 | Cooling | 10284.37029 | 10284.37029 | 0.90848 | 0.90848 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 35.10000 | 5.69938E-003 | 412.12471 | 22.18000 | 0.12562 | 0.00000 |
44 | CORRIDOR_FLR_6 | Heating | 6744.84501 | 6744.84501 | 0.35150 | 0.35150 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:50:00 | -7.90000 | 2.34317E-003 | 412.12471 | 22.18000 | 0.12562 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV WITH REHEAT | Cooling | Sensible | 589618.07 | 26.56724 | 26.56724 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | VAV WITH REHEAT | Heating | Sensible | 183943.35 | 7.51328 | 7.51328 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 |
3 | FLR_3_DOAS | Cooling | Sensible | 45524.16 | 23.55561 | 2.05125 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | FLR_3_DOAS | Heating | Sensible | 50219.47 | 5.52613 | 2.05125 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 3.04874 |
2 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.49459 |
3 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.99500 |
4 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 3.03349 |
5 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
6 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 7.70338E-004 |
8 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.15248E-004 |
9 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 3.03349 |
10 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
11 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
12 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 13173.56032 |
13 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.15248E-004 |
14 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 274.71189 |
15 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.44114 |
16 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11586 |
17 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.99500 |
18 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.43894 |
19 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.99500 |
20 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
21 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.28859E-003 |
22 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.04663E-005 |
23 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.43894 |
24 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
25 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
26 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 4625.54310 |
27 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.04663E-005 |
28 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 104.22149 |
29 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.29243 |
30 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.20239 |
31 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.99500 |
32 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.29097 |
33 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.99500 |
34 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
35 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.88254E-003 |
36 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.91219E-005 |
37 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.29097 |
38 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
40 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 2185.74579 |
41 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.91219E-005 |
42 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 47.37985 |
43 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.29623 |
44 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.42249 |
45 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.99500 |
46 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.29475 |
47 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
48 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
49 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 9.01805E-004 |
50 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.59416E-005 |
51 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.29475 |
52 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
53 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
54 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 2965.28767 |
55 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.59416E-005 |
56 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 66.39696 |
57 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.14762 |
58 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.48915 |
59 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.99500 |
60 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.14688 |
61 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
62 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 7.78903E-004 |
64 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.45024E-005 |
65 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.14688 |
66 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
67 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
68 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1657.71179 |
69 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.45024E-005 |
70 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 37.72210 |
71 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 3.96857 |
72 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 5.94606E-002 |
73 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.99500 |
74 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 3.94873 |
75 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.99500 |
76 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
77 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.54267E-002 |
78 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.69606E-004 |
79 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 3.94873 |
80 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
81 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
82 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 19387.04293 |
83 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.69606E-004 |
84 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 407.03874 |
85 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.85715 |
86 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 7.74911E-002 |
87 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.99500 |
88 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.84787 |
89 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.99500 |
90 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
91 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.91669E-003 |
92 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.29996E-004 |
93 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.84787 |
94 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
96 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 14859.36990 |
97 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.29996E-004 |
98 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 324.25404 |
99 | Fan:ZoneExhaust | LOBBY_FLR_1 EXHAUST FAN | User-Specified Maximum Flow Rate [m3/s] | 0.00000 |
100 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.80973 |
101 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.17158 |
102 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.99500 |
103 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 5.78068 |
104 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.99500 |
105 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
106 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.22053E-003 |
107 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.60102E-004 |
108 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 5.78068 |
109 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
110 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
111 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 41161.84428 |
112 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.60102E-004 |
113 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 887.90602 |
114 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_1_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17350E-002 |
115 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.52728 |
116 | Fan:OnOff | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.52728 |
117 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 5.22635E-005 |
118 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 5.53265E-004 |
119 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 22.78576 |
120 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
121 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.51914E-003 |
122 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
123 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
124 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 5.53265E-004 |
125 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.52728 |
126 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 5974.03757 |
127 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.22635E-005 |
128 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 170.71306 |
129 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_2_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17278E-002 |
130 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.51029 |
131 | Fan:OnOff | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.51029 |
132 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 5.22606E-005 |
133 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 5.47134E-004 |
134 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 22.78576 |
135 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
136 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.51933E-003 |
137 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
138 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
139 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 5.47134E-004 |
140 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.51029 |
141 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 5973.70904 |
142 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.22606E-005 |
143 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 170.70367 |
144 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_3_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.83707 |
145 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 8.38843 |
146 | Fan:OnOff | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 8.38843 |
147 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 3.00695E-004 |
148 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.02422E-003 |
149 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 22.78619 |
150 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
151 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.46252E-003 |
152 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
153 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.46252E-003 |
154 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.02422E-003 |
155 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 8.38843 |
156 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 34371.24075 |
157 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.00695E-004 |
158 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 982.17243 |
159 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_4_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.83730 |
160 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 8.29012 |
161 | Fan:OnOff | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 8.29012 |
162 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 3.00788E-004 |
163 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.11230E-003 |
164 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 22.78489 |
165 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
166 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.66587E-003 |
167 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
168 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
169 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.11230E-003 |
170 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 8.29012 |
171 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 34381.88290 |
172 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.00788E-004 |
173 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 982.47653 |
174 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_5_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17350E-002 |
175 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.34760 |
176 | Fan:OnOff | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.34760 |
177 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 5.22635E-005 |
178 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 4.88388E-004 |
179 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 22.78576 |
180 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
181 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.52090E-003 |
182 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
183 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
184 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.88388E-004 |
185 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.34760 |
186 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 5974.03757 |
187 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.22635E-005 |
188 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 170.71306 |
189 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_6_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17278E-002 |
190 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.33579 |
191 | Fan:OnOff | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.33579 |
192 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 5.22606E-005 |
193 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 4.84112E-004 |
194 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 22.78576 |
195 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
196 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.52093E-003 |
197 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
198 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
199 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.84112E-004 |
200 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.33579 |
201 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 5973.70904 |
202 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.22606E-005 |
203 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 170.70367 |
204 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.44589 |
205 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.82088 |
206 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.99500 |
207 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.43866 |
208 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
209 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
210 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.64134E-004 |
211 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.38074E-004 |
212 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.43866 |
213 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
214 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
215 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 15782.72293 |
216 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.38074E-004 |
217 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 357.64352 |
218 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_1_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.54338E-002 |
219 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.41227 |
220 | Fan:OnOff | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.41227 |
221 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.63967E-005 |
222 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 1.49297E-004 |
223 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 22.78577 |
224 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
225 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.51777E-003 |
226 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
227 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
228 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.49297E-004 |
229 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.41227 |
230 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 1874.24734 |
231 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.63967E-005 |
232 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 53.55564 |
233 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_2_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.54319E-002 |
234 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.40692 |
235 | Fan:OnOff | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.40692 |
236 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.64056E-005 |
237 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 1.47364E-004 |
238 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 22.78577 |
239 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
240 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.51797E-003 |
241 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
242 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
243 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.47364E-004 |
244 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.40692 |
245 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 1875.25677 |
246 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.64056E-005 |
247 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 53.58448 |
248 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_3_MULT9_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 9.91540E-002 |
249 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.70138 |
250 | Fan:OnOff | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.70138 |
251 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 7.89446E-005 |
252 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 6.25209E-004 |
253 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 22.78530 |
254 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
255 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.57732E-003 |
256 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
257 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
258 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 6.25209E-004 |
259 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.70138 |
260 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 9023.84817 |
261 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.89446E-005 |
262 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 257.84998 |
263 | Fan:ZoneExhaust | BANQUET_FLR_6 EXHAUST FAN | User-Specified Maximum Flow Rate [m3/s] | 0.00000 |
264 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.77548 |
265 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.10556E-002 |
266 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.99500 |
267 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.76160 |
268 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.99500 |
269 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
270 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.18426E-003 |
271 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.60623E-004 |
272 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.76160 |
273 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
274 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
275 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 18360.24187 |
276 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.60623E-004 |
277 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 393.73847 |
278 | Fan:ZoneExhaust | DINING_FLR_6 EXHAUST FAN | User-Specified Maximum Flow Rate [m3/s] | 0.00000 |
279 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.91166 |
280 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 8.67969E-002 |
281 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.99500 |
282 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.89710 |
283 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.99500 |
284 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
285 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.38956E-003 |
286 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.66887E-004 |
287 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.89710 |
288 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
289 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
290 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 19076.21503 |
291 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.66887E-004 |
292 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 408.77043 |
293 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.81012 |
294 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.67178 |
295 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.99500 |
296 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.79607 |
297 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.99500 |
298 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
299 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.36011E-002 |
300 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.20663E-004 |
301 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.79607 |
302 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
303 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
304 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 13792.57056 |
305 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.20663E-004 |
306 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 289.66125 |
307 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.90848 |
308 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.34567 |
309 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.99500 |
310 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.90394 |
311 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.99500 |
312 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
313 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.10219E-003 |
314 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.33348E-005 |
315 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.90394 |
316 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
317 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
318 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 10668.73972 |
319 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.33348E-005 |
320 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 244.45165 |
321 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 26.57966 |
322 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 26.57966 |
323 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 26.71323 |
324 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 26.57966 |
325 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 26.57966 |
326 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 26.57966 |
327 | AirLoopHVAC | VAV WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
328 | AirLoopHVAC | VAV WITH REHEAT | Calculated Heating Air Flow Ratio [] | 1.00000 |
329 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.05132 |
330 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.05132 |
331 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.05132 |
332 | AirLoopHVAC | FLR_3_DOAS | Adjusted Heating Design Air Flow Rate [m3/s] | 2.05132 |
333 | AirLoopHVAC | FLR_3_DOAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.05132 |
334 | AirLoopHVAC | FLR_3_DOAS | Adjusted Main Design Air Flow Rate [m3/s] | 2.05132 |
335 | AirLoopHVAC | FLR_3_DOAS | User Heating Air Flow Ratio [] | 0.30000 |
336 | AirLoopHVAC | FLR_3_DOAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
337 | AirLoopHVAC | VAV WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 26.57966 |
338 | AirLoopHVAC | FLR_3_DOAS | Design Supply Air Flow Rate [m3/s] | 2.05132 |
339 | Controller:OutdoorAir | VAV WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 26.57966 |
340 | Controller:OutdoorAir | VAV WITH REHEAT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 26.56724 |
341 | HeatExchanger:AirToAir:SensibleAndLatent | VAV WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 26.56724 |
342 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 35.10000 |
343 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
344 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.57205 |
345 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 5.69938E-003 |
346 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 5.69938E-003 |
347 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 655657.86315 |
348 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.34186E-002 |
349 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 26.57966 |
350 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 195220.43872 |
351 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.70787E-003 |
352 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 3266.91982 |
353 | Fan:VariableVolume | VAV WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 26.57966 |
354 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.34186E-002 |
355 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 2.03339E-005 |
356 | Controller:WaterCoil | VAV WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.70787E-003 |
357 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.05132 |
358 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.05125 |
359 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 35.10000 |
360 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
361 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.73601 |
362 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 5.69938E-003 |
363 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 5.69938E-003 |
364 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Coil Load [W] | 48199.92810 |
365 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.72159E-003 |
366 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 2.05132 |
367 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size Rated Capacity [W] | 15066.37152 |
368 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.31807E-004 |
369 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 252.12846 |
370 | Fan:ConstantVolume | FLR_3_DOAS FAN | User-Specified Maximum Flow Rate [m3/s] | 2.05125 |
371 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.72159E-003 |
372 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 2.76599E-004 |
373 | Controller:WaterCoil | FLR_3_DOAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.31807E-004 |
374 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 3.42715E-002 |
375 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 7062.07829 |
376 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 4.31653E-003 |
377 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 0.51798 |
378 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 4.31653E-003 |
379 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 1299.94791 |
380 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
381 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 493405.37531 |
382 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 493405.38000 |
383 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 4.31653E-003 |
384 | PlantLoop | COOLSYS1 | Maximum Loop Flow Rate [m3/s] | 3.42715E-002 |
385 | PlantLoop | COOLSYS1 | Plant Loop Volume [m3] | 4.11258 |
386 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Flow Rate [m3/s] | 3.42715E-002 |
387 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Power Consumption [W] | 4889.31499 |
388 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 3.42715E-002 |
389 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 959509.68974 |
390 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 960212.92000 |
391 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 109.46427 |
392 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 3.75036E-004 |
393 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 4.50044E-002 |
394 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 3.75036E-004 |
395 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 47.90688 |
396 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 3.75036E-004 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | 13242.76 |
2 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 4648.42 |
3 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 2196.97 |
4 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | 2980.01 |
5 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | 1665.86 |
6 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 19488.47 |
7 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | 14935.44 |
8 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | 41373.85 |
9 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | 6437.20 |
10 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | 6436.84 |
11 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | 37035.80 |
12 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | 37047.27 |
13 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | 6437.20 |
14 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | 6436.84 |
15 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 15860.49 |
16 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | 2019.50 |
17 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | 2020.59 |
18 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | 9723.16 |
19 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | 18455.11 |
20 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | 19174.83 |
21 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | 13864.71 |
22 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 10720.95 |
23 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | 142657.95 |
24 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | 11009.80 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | 27547.97 | 19494.34 | 8053.63 | 0.71 | 5181.81 | 52.56 |
2 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | 27242.26 | 19277.71 | 7964.55 | 0.71 | 5124.10 | 51.97 |
3 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | 151392.99 | 107180.08 | 44212.91 | 0.71 | 29198.08 | 296.14 |
4 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | 152883.47 | 106923.82 | 45959.65 | 0.70 | 27921.30 | 283.19 |
5 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | 24313.61 | 17203.03 | 7110.58 | 0.71 | 4571.64 | 46.37 |
6 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | 24100.67 | 17052.33 | 7048.34 | 0.71 | 4531.57 | 45.96 |
7 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | 7434.69 | 5261.76 | 2172.92 | 0.71 | 1398.90 | 14.19 |
8 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | 7338.31 | 5193.47 | 2144.85 | 0.71 | 1380.71 | 14.00 |
9 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | 30961.43 | 21806.19 | 9155.24 | 0.70 | 5751.38 | 58.33 |
10 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | 661053.24 | 400061.31 | 260991.93 | 0.61 | 70371.93 | 713.75 |
11 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | 47472.21 | 29284.36 | 18187.85 | 0.62 | 4618.55 | 46.84 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | 3.72 | 12.68 |
Zone Name | # Surfaces | |
1 | BASEMENT | 14 |
2 | RETAIL_1_FLR_1 | 8 |
3 | RETAIL_2_FLR_1 | 8 |
4 | MECH_FLR_1 | 7 |
5 | STORAGE_FLR_1 | 8 |
6 | LAUNDRY_FLR_1 | 8 |
7 | CAFE_FLR_1 | 10 |
8 | LOBBY_FLR_1 | 22 |
9 | ROOM_1_FLR_3 | 9 |
10 | ROOM_2_FLR_3 | 9 |
11 | ROOM_3_MULT19_FLR_3 | 8 |
12 | ROOM_4_MULT19_FLR_3 | 8 |
13 | ROOM_5_FLR_3 | 9 |
14 | ROOM_6_FLR_3 | 9 |
15 | CORRIDOR_FLR_3 | 25 |
16 | ROOM_1_FLR_6 | 9 |
17 | ROOM_2_FLR_6 | 9 |
18 | ROOM_3_MULT9_FLR_6 | 8 |
19 | BANQUET_FLR_6 | 8 |
20 | DINING_FLR_6 | 8 |
21 | KITCHEN_FLR_6 | 12 |
22 | CORRIDOR_FLR_6 | 19 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.419 | 0.394 | 211.13 | 211.13 | 211.13 | 0.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.419 | 0.394 | 55.76 | 55.76 | 55.76 | 90.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.419 | 0.394 | 211.13 | 211.13 | 211.13 | 180.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_WEST_CFACTOR | 0.419 | 0.394 | 55.76 | 55.76 | 55.76 | 270.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | BASEMENT_FLOOR | 2.705 | 1.632 | 1978.83 | 1978.83 | 1978.83 | 0.00 | 180.00 | 86.56 | 22.86 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | BASEMENT_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | RETAIL_1_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | BASEMENT_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | BASEMENT_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | BASEMENT_CEILING_4 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_CEILING_5 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
11 | BASEMENT_CEILING_6 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | CAFE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
12 | BASEMENT_CEILING_7 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 0.00 | 32.99 | 32.99 | 0.00 | LOBBY_FLR_1_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
13 | BASEMENT_CEILING_8 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 219.63 | 219.63 | 219.63 | 90.00 | 0.00 | 14.82 | 14.82 | 0.00 | LOBBY_FLR_1_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
14 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 3957.66 | 3957.66 | 3957.66 | 0.00 | 90.00 | 3957.66 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
15 | RETAIL_1_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.924 | 0.812 | 22.63 | 45.89 | 22.63 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | Window | RETAIL_1_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 23.26 | 23.26 | 23.26 | 180.00 | 90.00 | 10.92 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
17 | RETAIL_1_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.924 | 0.812 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
18 | RETAIL_1_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | RETAIL_1_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | RETAIL_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 67.07 | 67.07 | 67.07 | 0.00 | 180.00 | 11.58 | 5.79 | 0.00 | BASEMENT_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | RETAIL_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 7.62E-002 | 0.92 | 4 | ||
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 134.14 | 134.14 | 134.14 | 0.00 | 90.00 | 134.14 | 1.00 | 0.00 | RETAIL_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
23 | RETAIL_2_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.924 | 0.812 | 24.62 | 26.57 | 24.62 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | Door | RETAIL_2_FLR_1_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
25 | RETAIL_2_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
26 | RETAIL_2_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | RETAIL_2_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 90.00 | 90.00 | 6.71 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | RETAIL_2_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 77.67 | 77.67 | 77.67 | 0.00 | 180.00 | 11.58 | 6.71 | 0.00 | BASEMENT_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
29 | RETAIL_2_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 155.34 | 155.34 | 155.34 | 0.00 | 90.00 | 155.34 | 1.00 | 0.00 | RETAIL_2_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
31 | MECH_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.924 | 0.812 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | MECH_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | MECH_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 180.00 | 90.00 | 15.85 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | MECH_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | MECH_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 164.24 | 164.24 | 164.24 | 0.00 | 180.00 | 15.85 | 10.36 | 0.00 | BASEMENT_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | MECH_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | MECH_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 328.49 | 328.49 | 328.49 | 0.00 | 90.00 | 328.49 | 1.00 | 0.00 | MECH_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | STORAGE_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.924 | 0.812 | 28.80 | 36.23 | 28.80 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | Door | STORAGE_FLR_1_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.198 | 1.198 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | STORAGE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
41 | STORAGE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 180.00 | 90.00 | 9.14 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
42 | STORAGE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | STORAGE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 94.76 | 94.76 | 94.76 | 0.00 | 180.00 | 9.14 | 10.36 | 0.00 | BASEMENT_CEILING_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
44 | STORAGE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | STORAGE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 189.52 | 189.52 | 189.52 | 0.00 | 90.00 | 189.52 | 1.00 | 0.00 | STORAGE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
46 | LAUNDRY_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.924 | 0.812 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | LAUNDRY_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.924 | 0.812 | 65.68 | 67.63 | 65.68 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | Door | LAUNDRY_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
49 | LAUNDRY_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 180.00 | 90.00 | 4.57 | 3.96 | 0.00 | CAFE_FLR_1_WALL_2_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | LAUNDRY_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 270.00 | 90.00 | 17.07 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
51 | LAUNDRY_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 78.04 | 78.04 | 78.04 | 0.00 | 180.00 | 4.57 | 17.07 | 0.00 | BASEMENT_CEILING_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
52 | LAUNDRY_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 156.08 | 156.08 | 156.08 | 0.00 | 90.00 | 156.08 | 1.00 | 0.00 | LAUNDRY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
54 | CAFE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.924 | 0.812 | 21.00 | 22.95 | 21.00 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CAFE_FLR_1_WALL_EAST_DOOR | Door | CAFE_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | CAFE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.924 | 0.812 | 63.73 | 129.23 | 63.73 | 180.00 | 90.00 | 32.61 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | Window | CAFE_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 65.50 | 65.50 | 65.50 | 180.00 | 90.00 | 30.75 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
58 | CAFE_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 0.00 | 90.00 | 28.04 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | CAFE_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | CAFE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | CAFE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 188.86 | 188.86 | 188.86 | 0.00 | 180.00 | 32.61 | 5.79 | 0.00 | BASEMENT_CEILING_6 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
62 | CAFE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 3.86E-002 | 0.96 | 4 | ||
63 | CAFE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 377.72 | 377.72 | 377.72 | 0.00 | 90.00 | 377.72 | 1.00 | 0.00 | CAFE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
64 | LOBBY_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.924 | 0.812 | 209.87 | 213.77 | 209.87 | 0.00 | 90.00 | 53.95 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
67 | LOBBY_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.924 | 0.812 | 12.08 | 12.08 | 12.08 | 0.00 | 90.00 | 3.05 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
68 | LOBBY_FLR_1_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.924 | 0.812 | 82.79 | 167.88 | 82.79 | 180.00 | 90.00 | 42.37 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | Window | LOBBY_FLR_1_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 85.08 | 85.08 | 85.08 | 180.00 | 90.00 | 39.95 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LOBBY_FLR_1_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.924 | 0.812 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | LOBBY_FLR_1_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | LOBBY_FLR_1_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 180.00 | 90.00 | 28.04 | 3.96 | 0.00 | CAFE_FLR_1_WALL_1_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | LOBBY_FLR_1_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | LOBBY_FLR_1_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | LOBBY_FLR_1_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | LOBBY_FLR_1_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | MECH_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | LOBBY_FLR_1_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
78 | LOBBY_FLR_1_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | LOBBY_FLR_1_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | CAFE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | LOBBY_FLR_1_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | LOBBY_FLR_1_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 180.00 | 32.99 | 32.99 | 0.00 | BASEMENT_CEILING_7 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
82 | LOBBY_FLR_1_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 219.63 | 219.63 | 219.63 | 90.00 | 180.00 | 14.82 | 14.82 | 0.00 | BASEMENT_CEILING_8 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
83 | LOBBY_FLR_1_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 1062.83 | 1062.83 | 1062.83 | 270.00 | 0.00 | 32.60 | 32.60 | 0.00 | LOBBY_FLR_1_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 10 | ||
84 | LOBBY_FLR_1_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 245.35 | 245.35 | 245.35 | 180.00 | 0.00 | 42.37 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.22E-003 | 1.00 | 4 | ||
85 | LOBBY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 2616.37 | 2616.37 | 2616.37 | 0.00 | 90.00 | 2616.37 | 1.00 | 0.00 | LOBBY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | ROOM_1_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.107 | 0.950 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | ROOM_1_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.107 | 0.950 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | Window | ROOM_1_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | ROOM_1_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | ROOM_1_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | ROOM_1_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
93 | ROOM_1_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
94 | ROOM_1_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
95 | ROOM_2_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.107 | 0.950 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
97 | ROOM_2_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.107 | 0.950 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | Window | ROOM_2_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | ROOM_2_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | ROOM_2_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | ROOM_2_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | ROOM_2_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | ROOM_2_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.107 | 0.950 | 7.47 | 11.15 | 7.47 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 3.68 | 3.68 | 3.68 | 180.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | ROOM_3_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 24.52 | 24.52 | 24.52 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
110 | ROOM_3_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 24.52 | 24.52 | 24.52 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.05 | 49.05 | 49.05 | 0.00 | 90.00 | 49.05 | 1.00 | 0.00 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.107 | 0.950 | 7.47 | 11.15 | 7.47 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_4_MULT19_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 3.68 | 3.68 | 3.68 | 0.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
117 | ROOM_4_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
118 | ROOM_4_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
120 | ROOM_5_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.107 | 0.950 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | Window | ROOM_5_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
122 | ROOM_5_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.107 | 0.950 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_5_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
124 | ROOM_5_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
125 | ROOM_5_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
126 | ROOM_5_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
127 | ROOM_5_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
128 | ROOM_5_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_5_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
129 | ROOM_6_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.107 | 0.950 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_6_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
131 | ROOM_6_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.107 | 0.950 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | Window | ROOM_6_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
133 | ROOM_6_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
134 | ROOM_6_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
135 | ROOM_6_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
136 | ROOM_6_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
137 | ROOM_6_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_6_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
138 | CORRIDOR_FLR_3_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.217 | 1.029 | 11.83 | 17.65 | 11.83 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 5.82 | 5.82 | 5.82 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.217 | 1.029 | 4.35 | 6.50 | 4.35 | 0.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 2.15 | 2.15 | 2.15 | 0.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.217 | 1.029 | 4.36 | 6.50 | 4.36 | 180.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 2.15 | 2.15 | 2.15 | 180.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.217 | 1.029 | 11.83 | 17.65 | 11.83 | 180.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 5.82 | 5.82 | 5.82 | 180.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 0.00 | 90.00 | 69.50 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | CORRIDOR_FLR_3_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | CORRIDOR_FLR_3_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORRIDOR_FLR_3_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | CORRIDOR_FLR_3_WALL_4_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 180.00 | 90.00 | 69.49 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
152 | CORRIDOR_FLR_3_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | CORRIDOR_FLR_3_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | CORRIDOR_FLR_3_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | CORRIDOR_FLR_3_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | CORRIDOR_FLR_3_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 74.32 | 74.32 | 74.32 | 180.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
157 | CORRIDOR_FLR_3_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 240.77 | 240.77 | 240.77 | 270.00 | 180.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | CORRIDOR_FLR_3_FLOOR_3 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 74.32 | 74.32 | 74.32 | 90.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
159 | CORRIDOR_FLR_3_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
160 | CORRIDOR_FLR_3_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 240.77 | 240.77 | 240.77 | 90.00 | 0.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
161 | CORRIDOR_FLR_3_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 778.81 | 778.81 | 778.81 | 0.00 | 90.00 | 778.81 | 1.00 | 0.00 | CORRIDOR_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
163 | ROOM_1_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.174 | 0.999 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
165 | ROOM_1_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.174 | 0.999 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | Window | ROOM_1_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
167 | ROOM_1_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
168 | ROOM_1_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
169 | ROOM_1_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | ROOM_1_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.228 | 0.219 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
171 | ROOM_1_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
172 | ROOM_2_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.174 | 0.999 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
174 | ROOM_2_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.174 | 0.999 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | Window | ROOM_2_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
176 | ROOM_2_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
177 | ROOM_2_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
178 | ROOM_2_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | ROOM_2_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.228 | 0.219 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
180 | ROOM_2_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.174 | 0.999 | 13.70 | 20.44 | 13.70 | 180.00 | 90.00 | 6.71 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 6.74 | 6.74 | 6.74 | 180.00 | 90.00 | 5.53 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 0.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 90.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | ROOM_3_MULT9_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 6.71 | 3.66 | 0.00 | ROOM_3_MULT9_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
187 | ROOM_3_MULT9_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.228 | 0.219 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 6.71 | 3.66 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
189 | BANQUET_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.286 | 1.078 | 65.36 | 97.55 | 65.36 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | Window | BANQUET_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 32.19 | 32.19 | 32.19 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
191 | BANQUET_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
192 | BANQUET_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
193 | BANQUET_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
194 | BANQUET_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | BANQUET_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
195 | BANQUET_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
196 | BANQUET_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | BANQUET_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
197 | DINING_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.286 | 1.078 | 65.36 | 97.55 | 65.36 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DINING_FLR_6_WALL_NORTH_WINDOW | Window | DINING_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 32.19 | 32.19 | 32.19 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
199 | DINING_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
200 | DINING_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | DINING_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DINING_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DINING_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | DINING_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
203 | DINING_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
204 | DINING_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | DINING_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
205 | KITCHEN_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.286 | 1.078 | 16.77 | 21.37 | 16.77 | 0.00 | 90.00 | 7.01 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | Window | KITCHEN_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
207 | KITCHEN_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.286 | 1.078 | 34.86 | 52.03 | 34.86 | 90.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | Window | KITCHEN_FLR_6_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 17.17 | 17.17 | 17.17 | 90.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.286 | 1.078 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | Window | KITCHEN_FLR_6_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 7.43 | 7.43 | 7.43 | 180.00 | 90.00 | 2.44 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
212 | KITCHEN_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | KITCHEN_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | KITCHEN_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 103.30 | 103.30 | 103.30 | 180.00 | 180.00 | 10.16 | 10.16 | 0.00 | KITCHEN_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
215 | KITCHEN_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 103.30 | 103.30 | 103.30 | 270.00 | 0.00 | 10.16 | 10.16 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
216 | KITCHEN_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 206.61 | 206.61 | 206.61 | 0.00 | 90.00 | 206.61 | 1.00 | 0.00 | KITCHEN_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
217 | CORRIDOR_FLR_6_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.286 | 1.078 | 11.83 | 17.65 | 11.83 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 5.82 | 5.82 | 5.82 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.286 | 1.078 | 10.58 | 15.79 | 10.58 | 0.00 | 90.00 | 5.18 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 5.21 | 5.21 | 5.21 | 0.00 | 90.00 | 4.27 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.286 | 1.078 | 34.86 | 52.03 | 34.86 | 180.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 17.17 | 17.17 | 17.17 | 180.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
224 | CORRIDOR_FLR_6_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 104.98 | 104.98 | 104.98 | 0.00 | 90.00 | 34.44 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 183.95 | 183.95 | 183.95 | 180.00 | 90.00 | 60.35 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
226 | CORRIDOR_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
227 | CORRIDOR_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 40.88 | 40.88 | 40.88 | 270.00 | 90.00 | 13.41 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
228 | CORRIDOR_FLR_6_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
229 | CORRIDOR_FLR_6_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
230 | CORRIDOR_FLR_6_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
231 | CORRIDOR_FLR_6_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
232 | CORRIDOR_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 412.12 | 412.12 | 412.12 | 180.00 | 180.00 | 20.30 | 20.30 | 0.00 | CORRIDOR_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 12 | ||
233 | CORRIDOR_FLR_6_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 244.71 | 244.71 | 244.71 | 90.00 | 0.00 | 15.64 | 15.64 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 8 | ||
234 | CORRIDOR_FLR_6_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 167.42 | 167.42 | 167.42 | 270.00 | 0.00 | 12.94 | 12.94 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 824.25 | 824.25 | 824.25 | 0.00 | 90.00 | 824.25 | 1.00 | 0.00 | CORRIDOR_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 6.7220031419E-003 | 1.4312873785E-002 | Pass | Pass | 1.0856858899E-002 | 2.9549232904E-002 | Pass | Pass |
2 | RETAIL_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 4.6322650250E-002 | 7.8627275775E-002 | Pass | Pass | 5.3739241960E-002 | 6.0873570394E-002 | Pass | Pass |
3 | RETAIL_2_FLR_1 | RunPeriod: RUNPERIOD 1 | 3.7347113783E-003 | 8.2672528242E-003 | Pass | Pass | 1.7933603703E-002 | 2.8968987747E-002 | Pass | Pass |
4 | MECH_FLR_1 | RunPeriod: RUNPERIOD 1 | 9.3989280747E-004 | 7.4437605727E-004 | Pass | Pass | 4.5429945871E-002 | 6.5950646539E-002 | Pass | Pass |
5 | STORAGE_FLR_1 | RunPeriod: RUNPERIOD 1 | 8.7450499862E-004 | 6.0768852951E-004 | Pass | Pass | 0.1981812078 | 0.5214450598 | Pass | Pass |
6 | LAUNDRY_FLR_1 | RunPeriod: RUNPERIOD 1 | 4.5288531737E-002 | 0.1397255862 | Pass | Pass | 1.9207815614E-002 | 5.4778285966E-002 | Pass | Pass |
7 | CAFE_FLR_1 | RunPeriod: RUNPERIOD 1 | 5.1140246066E-002 | 7.4887272041E-002 | Pass | Pass | 2.0423357474E-002 | 2.7147106539E-002 | Pass | Pass |
8 | LOBBY_FLR_1 | RunPeriod: RUNPERIOD 1 | 1.9528961374E-002 | 3.3489117163E-002 | Pass | Pass | 1.7935337377E-002 | 2.7579012903E-002 | Pass | Pass |
9 | ROOM_1_FLR_3 | RunPeriod: RUNPERIOD 1 | 5.6464322528E-002 | 0.2222070489 | Pass | Pass | 0.2236488735 | 0.6197998963 | Pass | Pass |
10 | ROOM_2_FLR_3 | RunPeriod: RUNPERIOD 1 | 6.9359359092E-002 | 0.2344600349 | Pass | Pass | 0.2042489263 | 0.5351278499 | Pass | Pass |
11 | ROOM_3_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 2.0853170600E-002 | 4.5073939162E-002 | Pass | Pass | 3.0374426131E-002 | 4.7964365126E-002 | Pass | Pass |
12 | ROOM_4_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 1.1273847100E-002 | 3.7395560524E-002 | Pass | Pass | 0.6309184145 | 3.7296100576 | Pass | Pass |
13 | ROOM_5_FLR_3 | RunPeriod: RUNPERIOD 1 | 7.3482770139E-002 | 0.2978180611 | Pass | Pass | 0.6384003358 | 5.3721119096 | Pass | Pass |
14 | ROOM_6_FLR_3 | RunPeriod: RUNPERIOD 1 | 3.4766569251E-002 | 0.1332559959 | Pass | Pass | 0.9176243035 | 6.0909931512 | Pass | Pass |
15 | CORRIDOR_FLR_3 | RunPeriod: RUNPERIOD 1 | 6.3285242013E-003 | 1.1830685456E-002 | Pass | Pass | 2.4474865355E-002 | 3.3554887553E-002 | Pass | Pass |
16 | ROOM_1_FLR_6 | RunPeriod: RUNPERIOD 1 | 5.9808728861E-002 | 0.2249028752 | Pass | Pass | 0.2026249586 | 0.5591795033 | Pass | Pass |
17 | ROOM_2_FLR_6 | RunPeriod: RUNPERIOD 1 | 8.4877421539E-002 | 0.2754206519 | Pass | Pass | 0.2105850104 | 0.5227638357 | Pass | Pass |
18 | ROOM_3_MULT9_FLR_6 | RunPeriod: RUNPERIOD 1 | 9.2700578402E-002 | 0.3543834224 | Pass | Pass | 0.2815378897 | 1.0860603516 | Pass | Pass |
19 | BANQUET_FLR_6 | RunPeriod: RUNPERIOD 1 | 2.1323395079E-002 | 6.4867889130E-002 | Pass | Pass | 1.2946726869E-002 | 3.4839326784E-002 | Pass | Pass |
20 | DINING_FLR_6 | RunPeriod: RUNPERIOD 1 | 2.4217265455E-002 | 6.5527713153E-002 | Pass | Pass | 1.2126393637E-002 | 3.0763809109E-002 | Pass | Pass |
21 | KITCHEN_FLR_6 | RunPeriod: RUNPERIOD 1 | 6.5781590908E-002 | 0.1154399786 | Pass | Pass | 1.8772039949E-002 | 3.3065138013E-002 | Pass | Pass |
22 | CORRIDOR_FLR_6 | RunPeriod: RUNPERIOD 1 | 2.9983604633E-003 | 5.2661871415E-003 | Pass | Pass | 0.1423064306 | 0.3735636040 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:57:58
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 5139.27 | 75.21 | 619.60 | 8280.18 | 7514.15 | 21628.41 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:57:58
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | -7.90 | 0.00 | -7.90 | Wetbulb [C] | 3.20 | 0.00 |
ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 35.10 | 13.50 | 15.70 | Wetbulb [C] | 4.40 | 220.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 9.00 | 6 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 0.00 | 0 | |||
Sep | 0.00 | 0 | |||
Oct | 5.00 | 4 | |||
Nov | 9.00 | 7 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:57:58
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.399 | 0.419 | 211.13 | 211.13 | 0.00 | 90.00 | N |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.399 | 0.419 | 55.76 | 55.76 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.399 | 0.419 | 211.13 | 211.13 | 180.00 | 90.00 | S |
BASEMENT_WALL_WEST | BASEMENT_WALL_WEST_CFACTOR | 1.00 | 0.399 | 0.419 | 55.76 | 55.76 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.812 | 0.924 | 45.89 | 22.63 | 180.00 | 90.00 | S |
RETAIL_1_FLR_1_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.812 | 0.924 | 22.95 | 22.95 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_CEILING | NONRES_ROOF | 0.23 | 0.221 | 0.228 | 67.07 | 67.07 | 180.00 | 0.00 | |
RETAIL_2_FLR_1_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.812 | 0.924 | 26.57 | 24.62 | 270.00 | 90.00 | W |
MECH_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.812 | 0.924 | 62.80 | 62.80 | 0.00 | 90.00 | N |
STORAGE_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.812 | 0.924 | 36.23 | 28.80 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.812 | 0.924 | 18.12 | 18.12 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.812 | 0.924 | 67.63 | 65.68 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.812 | 0.924 | 22.95 | 21.00 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.812 | 0.924 | 129.23 | 63.73 | 180.00 | 90.00 | S |
CAFE_FLR_1_CEILING | NONRES_ROOF | 0.23 | 0.221 | 0.228 | 188.86 | 188.86 | 180.00 | 0.00 | |
LOBBY_FLR_1_WALL_1_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.812 | 0.924 | 213.77 | 209.87 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_2_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.812 | 0.924 | 12.08 | 12.08 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.812 | 0.924 | 167.88 | 82.79 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_1_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.812 | 0.924 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_CEILING_2 | NONRES_ROOF | 0.23 | 0.221 | 0.228 | 245.35 | 245.35 | 180.00 | 0.00 | |
ROOM_1_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.950 | 1.107 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_1_FLR_3_WALL_WEST | RES_EXT_WALL_MID | 0.30 | 0.950 | 1.107 | 104.06 | 69.72 | 270.00 | 90.00 | W |
ROOM_2_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.950 | 1.107 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_2_FLR_3_WALL_WEST | RES_EXT_WALL_MID | 0.30 | 0.950 | 1.107 | 104.05 | 69.71 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.950 | 1.107 | 847.14 | 567.58 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.950 | 1.107 | 847.37 | 567.71 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_EAST | RES_EXT_WALL_MID | 0.30 | 0.950 | 1.107 | 104.06 | 69.72 | 90.00 | 90.00 | E |
ROOM_5_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.950 | 1.107 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.950 | 1.107 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_6_FLR_3_WALL_EAST | RES_EXT_WALL_MID | 0.30 | 0.950 | 1.107 | 104.05 | 69.71 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_1_NORTH | NONRES_EXT_WALL_MID | 0.30 | 1.029 | 1.217 | 70.60 | 47.31 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_2_NORTH | NONRES_EXT_WALL_MID | 0.30 | 1.029 | 1.217 | 26.01 | 17.42 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 1.029 | 1.217 | 26.02 | 17.43 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_2_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 1.029 | 1.217 | 70.60 | 47.31 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_SOUTH | RES_EXT_WALL_TOP | 0.30 | 0.999 | 1.174 | 13.94 | 9.34 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_WEST | RES_EXT_WALL_TOP | 0.30 | 0.999 | 1.174 | 26.01 | 17.43 | 270.00 | 90.00 | W |
ROOM_1_FLR_6_CEILING | RES_ROOF | 0.23 | 0.221 | 0.228 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_2_FLR_6_WALL_NORTH | RES_EXT_WALL_TOP | 0.30 | 0.999 | 1.174 | 13.94 | 9.34 | 0.00 | 90.00 | N |
ROOM_2_FLR_6_WALL_WEST | RES_EXT_WALL_TOP | 0.30 | 0.999 | 1.174 | 26.01 | 17.43 | 270.00 | 90.00 | W |
ROOM_2_FLR_6_CEILING | RES_ROOF | 0.23 | 0.221 | 0.228 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | RES_EXT_WALL_TOP | 0.30 | 0.999 | 1.174 | 183.96 | 123.26 | 180.00 | 90.00 | S |
ROOM_3_MULT9_FLR_6_CEILING | RES_ROOF | 0.23 | 0.221 | 0.228 | 220.77 | 220.77 | 180.00 | 0.00 | |
BANQUET_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.078 | 1.286 | 97.55 | 65.36 | 0.00 | 90.00 | N |
BANQUET_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.221 | 0.228 | 331.66 | 331.66 | 180.00 | 0.00 | |
DINING_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.078 | 1.286 | 97.55 | 65.36 | 0.00 | 90.00 | N |
DINING_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.221 | 0.228 | 331.66 | 331.66 | 180.00 | 0.00 | |
KITCHEN_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.078 | 1.286 | 21.37 | 16.77 | 0.00 | 90.00 | N |
KITCHEN_FLR_6_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.078 | 1.286 | 52.03 | 34.86 | 90.00 | 90.00 | E |
KITCHEN_FLR_6_WALL_1_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.078 | 1.286 | 13.94 | 9.34 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.221 | 0.228 | 103.30 | 103.30 | 270.00 | 0.00 | |
CORRIDOR_FLR_6_WALL_1_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.078 | 1.286 | 17.65 | 11.83 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.078 | 1.286 | 15.79 | 10.58 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.078 | 1.286 | 52.03 | 34.86 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_CEILING_1 | NONRES_ROOF | 0.23 | 0.221 | 0.228 | 244.71 | 244.71 | 90.00 | 0.00 | |
CORRIDOR_FLR_6_CEILING_2 | NONRES_ROOF | 0.23 | 0.221 | 0.228 | 167.42 | 167.42 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_FLOOR | BASEMENT_FLOOR | 0.30 | 1.441 | 2.705 | 1978.83 | 1978.83 | 0.00 | 180.00 | |
BASEMENT_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.186 | 0.196 | 67.07 | 67.07 | 180.00 | 0.00 | |
BASEMENT_CEILING_2 | NONRES_FLOOR_CEILING | 0.30 | 0.186 | 0.196 | 77.67 | 77.67 | 180.00 | 0.00 | |
BASEMENT_CEILING_3 | NONRES_FLOOR_CEILING | 0.30 | 0.186 | 0.196 | 164.24 | 164.24 | 180.00 | 0.00 | |
BASEMENT_CEILING_4 | NONRES_FLOOR_CEILING | 0.30 | 0.186 | 0.196 | 94.76 | 94.76 | 180.00 | 0.00 | |
BASEMENT_CEILING_5 | NONRES_FLOOR_CEILING | 0.30 | 0.186 | 0.196 | 78.04 | 78.04 | 180.00 | 0.00 | |
BASEMENT_CEILING_6 | NONRES_FLOOR_CEILING | 0.30 | 0.186 | 0.196 | 188.86 | 188.86 | 180.00 | 0.00 | |
BASEMENT_CEILING_7 | NONRES_FLOOR_CEILING | 0.30 | 0.186 | 0.196 | 1088.56 | 1088.56 | 180.00 | 0.00 | |
BASEMENT_CEILING_8 | NONRES_FLOOR_CEILING | 0.30 | 0.186 | 0.196 | 219.63 | 219.63 | 90.00 | 0.00 | |
RETAIL_1_FLR_1_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 0.00 | 90.00 | N |
RETAIL_1_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 90.00 | 90.00 | E |
RETAIL_1_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.186 | 0.196 | 67.07 | 67.07 | 0.00 | 180.00 | |
RETAIL_2_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 180.00 | 90.00 | S |
RETAIL_2_FLR_1_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 0.00 | 90.00 | N |
RETAIL_2_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.57 | 26.57 | 90.00 | 90.00 | E |
RETAIL_2_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.186 | 0.196 | 77.67 | 77.67 | 0.00 | 180.00 | |
RETAIL_2_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 77.67 | 77.67 | 180.00 | 0.00 | |
MECH_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
MECH_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 62.80 | 62.80 | 180.00 | 90.00 | S |
MECH_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
MECH_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.186 | 0.196 | 164.24 | 164.24 | 0.00 | 180.00 | |
MECH_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 164.24 | 164.24 | 180.00 | 0.00 | |
STORAGE_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
STORAGE_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 36.23 | 36.23 | 180.00 | 90.00 | S |
STORAGE_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
STORAGE_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.186 | 0.196 | 94.76 | 94.76 | 0.00 | 180.00 | |
STORAGE_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 94.76 | 94.76 | 180.00 | 0.00 | |
LAUNDRY_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 18.12 | 18.12 | 180.00 | 90.00 | S |
LAUNDRY_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 67.63 | 67.63 | 270.00 | 90.00 | W |
LAUNDRY_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.186 | 0.196 | 78.04 | 78.04 | 0.00 | 180.00 | |
LAUNDRY_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 78.04 | 78.04 | 180.00 | 0.00 | |
CAFE_FLR_1_WALL_1_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.11 | 111.11 | 0.00 | 90.00 | N |
CAFE_FLR_1_WALL_2_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 18.12 | 18.12 | 0.00 | 90.00 | N |
CAFE_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 270.00 | 90.00 | W |
CAFE_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.186 | 0.196 | 188.86 | 188.86 | 0.00 | 180.00 | |
LOBBY_FLR_1_WALL_2_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_3_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.11 | 111.11 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.57 | 26.57 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_4_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 62.80 | 62.80 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_4_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 36.23 | 36.23 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
LOBBY_FLR_1_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 90.00 | 90.00 | E |
LOBBY_FLR_1_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 67.63 | 67.63 | 90.00 | 90.00 | E |
LOBBY_FLR_1_FLOOR_1 | NONRES_FLOOR | 0.30 | 0.186 | 0.196 | 1088.56 | 1088.56 | 180.00 | 180.00 | |
LOBBY_FLR_1_FLOOR_2 | NONRES_FLOOR | 0.30 | 0.186 | 0.196 | 219.63 | 219.63 | 90.00 | 180.00 | |
LOBBY_FLR_1_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 1062.83 | 1062.83 | 270.00 | 0.00 | |
ROOM_1_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 0.00 | 90.00 | N |
ROOM_1_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 90.00 | 90.00 | E |
ROOM_1_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 156.09 | 156.09 | 0.00 | 180.00 | |
ROOM_1_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 156.09 | 156.09 | 180.00 | 0.00 | |
ROOM_2_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 90.00 | 90.00 | E |
ROOM_2_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 180.00 | 90.00 | S |
ROOM_2_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 156.07 | 156.07 | 0.00 | 180.00 | |
ROOM_2_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 156.07 | 156.07 | 180.00 | 0.00 | |
ROOM_3_MULT19_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.14 | 847.14 | 0.00 | 90.00 | N |
ROOM_3_MULT19_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 90.00 | 90.00 | E |
ROOM_3_MULT19_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 1863.81 | 1863.81 | 0.00 | 180.00 | |
ROOM_3_MULT19_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 1863.81 | 1863.81 | 180.00 | 0.00 | |
ROOM_4_MULT19_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 90.00 | 90.00 | E |
ROOM_4_MULT19_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.37 | 847.37 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 270.00 | 90.00 | W |
ROOM_4_MULT19_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 1864.32 | 1864.32 | 0.00 | 180.00 | |
ROOM_4_MULT19_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 1864.32 | 1864.32 | 180.00 | 0.00 | |
ROOM_5_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 270.00 | 90.00 | W |
ROOM_5_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 156.09 | 156.09 | 0.00 | 180.00 | |
ROOM_5_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 156.09 | 156.09 | 180.00 | 0.00 | |
ROOM_6_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 270.00 | 90.00 | W |
ROOM_6_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 156.07 | 156.07 | 0.00 | 180.00 | |
ROOM_6_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 156.07 | 156.07 | 180.00 | 0.00 | |
CORRIDOR_FLR_3_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.28 | 847.28 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_4_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_3_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.27 | 847.27 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_4_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_FLOOR_1 | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 297.29 | 297.29 | 180.00 | 180.00 | |
CORRIDOR_FLR_3_FLOOR_2 | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 963.06 | 963.06 | 270.00 | 180.00 | |
CORRIDOR_FLR_3_FLOOR_3 | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 297.26 | 297.26 | 90.00 | 180.00 | |
CORRIDOR_FLR_3_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 297.29 | 297.29 | 90.00 | 0.00 | |
CORRIDOR_FLR_3_CEILING_2 | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 963.06 | 963.06 | 90.00 | 0.00 | |
CORRIDOR_FLR_3_CEILING_3 | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 297.26 | 297.26 | 90.00 | 0.00 | |
ROOM_1_FLR_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 13.94 | 13.94 | 0.00 | 90.00 | N |
ROOM_1_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.01 | 26.01 | 90.00 | 90.00 | E |
ROOM_1_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 39.02 | 39.02 | 0.00 | 180.00 | |
ROOM_2_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.01 | 26.01 | 90.00 | 90.00 | E |
ROOM_2_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 13.94 | 13.94 | 180.00 | 90.00 | S |
ROOM_2_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 39.02 | 39.02 | 0.00 | 180.00 | |
ROOM_3_MULT9_FLR_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 183.96 | 183.96 | 0.00 | 90.00 | N |
ROOM_3_MULT9_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 100.35 | 100.35 | 90.00 | 90.00 | E |
ROOM_3_MULT9_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 100.35 | 100.35 | 270.00 | 90.00 | W |
ROOM_3_MULT9_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 220.77 | 220.77 | 0.00 | 180.00 | |
BANQUET_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
BANQUET_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 180.00 | 90.00 | S |
BANQUET_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
BANQUET_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 331.66 | 331.66 | 0.00 | 180.00 | |
DINING_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
DINING_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 180.00 | 90.00 | S |
DINING_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
DINING_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 331.66 | 331.66 | 0.00 | 180.00 | |
KITCHEN_FLR_6_WALL_2_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 7.43 | 7.43 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 20.44 | 20.44 | 270.00 | 90.00 | W |
KITCHEN_FLR_6_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
KITCHEN_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 103.30 | 103.30 | 180.00 | 180.00 | |
CORRIDOR_FLR_6_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_4_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 104.98 | 104.98 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_1_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 183.95 | 183.95 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 11.15 | 11.15 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 40.88 | 40.88 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 20.44 | 20.44 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 412.12 | 412.12 | 180.00 | 180.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3957.66 | 0.00 | 90.00 | N | ||
RETAIL_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 134.14 | 0.00 | 90.00 | N | ||
RETAIL_2_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 155.34 | 0.00 | 90.00 | N | ||
MECH_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 328.49 | 0.00 | 90.00 | N | ||
STORAGE_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 189.52 | 0.00 | 90.00 | N | ||
LAUNDRY_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 156.08 | 0.00 | 90.00 | N | ||
CAFE_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 377.72 | 0.00 | 90.00 | N | ||
LOBBY_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 2616.37 | 0.00 | 90.00 | N | ||
ROOM_1_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.18 | 0.00 | 90.00 | N | ||
ROOM_2_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.14 | 0.00 | 90.00 | N | ||
ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3727.63 | 0.00 | 90.00 | N | ||
ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3728.64 | 0.00 | 90.00 | N | ||
ROOM_5_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.18 | 0.00 | 90.00 | N | ||
ROOM_6_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.14 | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3115.24 | 0.00 | 90.00 | N | ||
ROOM_1_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 78.04 | 0.00 | 90.00 | N | ||
ROOM_2_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 78.03 | 0.00 | 90.00 | N | ||
ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 441.55 | 0.00 | 90.00 | N | ||
BANQUET_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 663.31 | 0.00 | 90.00 | N | ||
DINING_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 663.31 | 0.00 | 90.00 | N | ||
KITCHEN_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 206.61 | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 824.25 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.3856_SHGC_0.4 | 23.26 | 0.00 | 0.00 | 23.26 | 23.26 | 2.191 | 0.401 | 0.402 | No | RETAIL_1_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
CAFE_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.3856_SHGC_0.4 | 65.50 | 0.00 | 0.00 | 65.50 | 65.50 | 2.191 | 0.401 | 0.402 | No | CAFE_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
LOBBY_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.3856_SHGC_0.4 | 85.08 | 0.00 | 0.00 | 85.08 | 85.08 | 2.191 | 0.401 | 0.402 | No | LOBBY_FLR_1_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.3856_SHGC_0.4 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.191 | 0.401 | 0.402 | No | ROOM_1_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.3856_SHGC_0.4 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.191 | 0.401 | 0.402 | No | ROOM_1_FLR_3_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_2_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.3856_SHGC_0.4 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.191 | 0.401 | 0.402 | No | ROOM_2_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_2_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.3856_SHGC_0.4 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.191 | 0.401 | 0.402 | No | ROOM_2_FLR_3_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.3856_SHGC_0.4 | 3.68 | 0.00 | 0.00 | 3.68 | 279.56 | 2.191 | 0.401 | 0.402 | No | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.3856_SHGC_0.4 | 3.68 | 0.00 | 0.00 | 3.68 | 279.65 | 2.191 | 0.401 | 0.402 | No | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_5_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.3856_SHGC_0.4 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.191 | 0.401 | 0.402 | No | ROOM_5_FLR_3_WALL_EAST | 90.00 | 90.00 | E | |||||||
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.3856_SHGC_0.4 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.191 | 0.401 | 0.402 | No | ROOM_5_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_6_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.3856_SHGC_0.4 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.191 | 0.401 | 0.402 | No | ROOM_6_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_6_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.3856_SHGC_0.4 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.191 | 0.401 | 0.402 | No | ROOM_6_FLR_3_WALL_EAST | 90.00 | 90.00 | E | |||||||
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.3856_SHGC_0.4 | 5.82 | 0.00 | 0.00 | 5.82 | 23.30 | 2.191 | 0.401 | 0.402 | No | CORRIDOR_FLR_3_WALL_1_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.3856_SHGC_0.4 | 2.15 | 0.00 | 0.00 | 2.15 | 8.59 | 2.191 | 0.401 | 0.402 | No | CORRIDOR_FLR_3_WALL_2_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.3856_SHGC_0.4 | 2.15 | 0.00 | 0.00 | 2.15 | 8.58 | 2.191 | 0.401 | 0.402 | No | CORRIDOR_FLR_3_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.3856_SHGC_0.4 | 5.82 | 0.00 | 0.00 | 5.82 | 23.30 | 2.191 | 0.401 | 0.402 | No | CORRIDOR_FLR_3_WALL_2_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.3856_SHGC_0.4 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.191 | 0.401 | 0.402 | No | ROOM_1_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.3856_SHGC_0.4 | 8.58 | 0.00 | 0.00 | 8.58 | 8.58 | 2.191 | 0.401 | 0.402 | No | ROOM_1_FLR_6_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_2_FLR_6_WALL_NORTH_WINDOW | RESWINDOW_U_0.3856_SHGC_0.4 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.191 | 0.401 | 0.402 | No | ROOM_2_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_2_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.3856_SHGC_0.4 | 8.58 | 0.00 | 0.00 | 8.58 | 8.58 | 2.191 | 0.401 | 0.402 | No | ROOM_2_FLR_6_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.3856_SHGC_0.4 | 6.74 | 0.00 | 0.00 | 6.74 | 60.70 | 2.191 | 0.401 | 0.402 | No | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
BANQUET_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.3856_SHGC_0.4 | 32.19 | 0.00 | 0.00 | 32.19 | 32.19 | 2.191 | 0.401 | 0.402 | No | BANQUET_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
DINING_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.3856_SHGC_0.4 | 32.19 | 0.00 | 0.00 | 32.19 | 32.19 | 2.191 | 0.401 | 0.402 | No | DINING_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
KITCHEN_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.3856_SHGC_0.4 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.191 | 0.401 | 0.402 | No | KITCHEN_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
KITCHEN_FLR_6_WALL_EAST_WINDOW | NONRESWINDOW_U_0.3856_SHGC_0.4 | 17.17 | 0.00 | 0.00 | 17.17 | 17.17 | 2.191 | 0.401 | 0.402 | No | KITCHEN_FLR_6_WALL_EAST | 90.00 | 90.00 | E | |||||||
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.3856_SHGC_0.4 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.191 | 0.401 | 0.402 | No | KITCHEN_FLR_6_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.3856_SHGC_0.4 | 5.82 | 0.00 | 0.00 | 5.82 | 5.82 | 2.191 | 0.401 | 0.402 | No | CORRIDOR_FLR_6_WALL_1_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.3856_SHGC_0.4 | 5.21 | 0.00 | 0.00 | 5.21 | 5.21 | 2.191 | 0.401 | 0.402 | No | CORRIDOR_FLR_6_WALL_2_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.3856_SHGC_0.4 | 17.17 | 0.00 | 0.00 | 17.17 | 17.17 | 2.191 | 0.401 | 0.402 | No | CORRIDOR_FLR_6_WALL_2_SOUTH | 180.00 | 90.00 | S | |||||||
Total or Average | 1213.79 | 2.191 | 0.401 | 0.402 | |||||||||||||||||
North Total or Average | 432.95 | 2.191 | 0.401 | 0.402 | |||||||||||||||||
Non-North Total or Average | 780.84 | 2.191 | 0.401 | 0.402 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
RETAIL_2_FLR_1_WALL_WEST_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | RETAIL_2_FLR_1_WALL_WEST |
STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | OVERHEAD DOOR_CON | 1.016 | 1.198 | 7.43 | STORAGE_FLR_1_WALL_NORTH |
LAUNDRY_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | LAUNDRY_FLR_1_WALL_EAST |
CAFE_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | CAFE_FLR_1_WALL_EAST |
LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:57:58
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CAFE_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LOBBY_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
BANQUET_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:57:58
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 8.7495 | 1978.83 | 17313.73 | LightsWired | LTG_SCH_BASEMENT | 50.91 | 168.00 | 50.86 | 0.0000 | Y | 165.29 |
RETAIL_1_FLR_1_LIGHTS | RETAIL_1_FLR_1 | RETAIL_1_FLR_1 | GENERAL | 13.0124 | 67.07 | 872.76 | LightsWired | LTG_SCH_RETAIL | 51.36 | 168.00 | 51.30 | 0.0000 | Y | 8.40 |
RETAIL_2_FLR_1_LIGHTS | RETAIL_2_FLR_1 | RETAIL_2_FLR_1 | GENERAL | 13.0124 | 77.67 | 1010.66 | LightsWired | LTG_SCH_RETAIL | 51.36 | 168.00 | 51.30 | 0.0000 | Y | 9.73 |
MECH_FLR_1_LIGHTS | MECH_FLR_1 | MECH_FLR_1 | GENERAL | 10.0642 | 164.24 | 1652.98 | LightsWired | LTG_SCH_MECHANIC | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 18.19 |
STORAGE_FLR_1_LIGHTS | STORAGE_FLR_1 | STORAGE_FLR_1 | GENERAL | 7.3195 | 94.76 | 693.59 | LightsWired | LTG_SCH_STORAGE | 25.68 | 168.00 | 25.65 | 0.0000 | Y | 3.34 |
LAUNDRY_FLR_1_LIGHTS | LAUNDRY_FLR_1 | LAUNDRY_FLR_1 | GENERAL | 5.4896 | 78.04 | 428.40 | LightsWired | LTG_SCH_LAUNDRY | 51.36 | 168.00 | 51.30 | 0.0000 | Y | 4.13 |
CAFE_FLR_1_LIGHTS | CAFE_FLR_1 | CAFE_FLR_1 | GENERAL | 12.8090 | 188.86 | 2419.14 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 26.62 |
LOBBY_FLR_1_LIGHTS | LOBBY_FLR_1 | LOBBY_FLR_1 | GENERAL | 10.0642 | 1308.19 | 13165.91 | LightsWired | LTG_SCH_LOBBY | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 144.89 |
ROOM_1_FLR_3_LIGHTS | ROOM_1_FLR_3 | ROOM_1_FLR_3 | GENERAL | 10.0642 | 156.09 | 1570.91 | LightsWired | LTG_SCH_GUESTROOM | 69.03 | 168.00 | 69.21 | 0.0000 | Y | 20.41 |
ROOM_2_FLR_3_LIGHTS | ROOM_2_FLR_3 | ROOM_2_FLR_3 | GENERAL | 10.0642 | 156.07 | 1570.72 | LightsWired | LTG_SCH_GUESTROOM | 69.03 | 168.00 | 69.21 | 0.0000 | Y | 20.41 |
ROOM_3_MULT19_FLR_3_LIGHTS | ROOM_3_MULT19_FLR_3 | ROOM_3_MULT19_FLR_3 | GENERAL | 10.0642 | 1863.81 | 18757.86 | LightsWired | LTG_SCH_GUESTROOM | 69.03 | 168.00 | 69.21 | 0.0000 | Y | 243.70 |
ROOM_4_MULT19_FLR_3_LIGHTS | ROOM_4_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | GENERAL | 10.0642 | 1864.32 | 18762.99 | LightsWired | LTG_SCH_GUESTROOM | 69.03 | 168.00 | 69.21 | 0.0000 | Y | 243.77 |
ROOM_5_FLR_3_LIGHTS | ROOM_5_FLR_3 | ROOM_5_FLR_3 | GENERAL | 10.0642 | 156.09 | 1570.91 | LightsWired | LTG_SCH_GUESTROOM | 69.03 | 168.00 | 69.21 | 0.0000 | Y | 20.41 |
ROOM_6_FLR_3_LIGHTS | ROOM_6_FLR_3 | ROOM_6_FLR_3 | GENERAL | 10.0642 | 156.07 | 1570.72 | LightsWired | LTG_SCH_GUESTROOM | 69.03 | 168.00 | 69.21 | 0.0000 | Y | 20.41 |
CORRIDOR_FLR_3_LIGHTS | CORRIDOR_FLR_3 | CORRIDOR_FLR_3 | GENERAL | 3.6597 | 1557.62 | 5700.46 | LightsWired | LTG_SCH_CORRIDOR | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 62.73 |
ROOM_1_FLR_6_LIGHTS | ROOM_1_FLR_6 | ROOM_1_FLR_6 | GENERAL | 10.0642 | 39.02 | 392.73 | LightsWired | LTG_SCH_GUESTROOM | 69.03 | 168.00 | 69.21 | 0.0000 | Y | 5.10 |
ROOM_2_FLR_6_LIGHTS | ROOM_2_FLR_6 | ROOM_2_FLR_6 | GENERAL | 10.0642 | 39.02 | 392.68 | LightsWired | LTG_SCH_GUESTROOM | 69.03 | 168.00 | 69.21 | 0.0000 | Y | 5.10 |
ROOM_3_MULT9_FLR_6_LIGHTS | ROOM_3_MULT9_FLR_6 | ROOM_3_MULT9_FLR_6 | GENERAL | 10.0642 | 220.77 | 2221.93 | LightsWired | LTG_SCH_GUESTROOM | 69.03 | 168.00 | 69.21 | 0.0000 | Y | 28.87 |
BANQUET_FLR_6_LIGHTS | BANQUET_FLR_6 | BANQUET_FLR_6 | GENERAL | 12.8090 | 331.66 | 4248.21 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 46.75 |
DINING_FLR_6_LIGHTS | DINING_FLR_6 | DINING_FLR_6 | GENERAL | 12.8090 | 331.66 | 4248.21 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 46.75 |
KITCHEN_FLR_6_LIGHTS | KITCHEN_FLR_6 | KITCHEN_FLR_6 | GENERAL | 10.9792 | 103.30 | 1134.20 | LightsWired | LTG_SCH_KITCHEN | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 12.48 |
CORRIDOR_FLR_6_LIGHTS | CORRIDOR_FLR_6 | CORRIDOR_FLR_6 | GENERAL | 3.6597 | 412.12 | 1508.26 | LightsWired | LTG_SCH_CORRIDOR | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 16.60 |
Interior Lighting Total | 8.9207 | 11345.29 | 101207.97 | 559.10 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR FACADE LIGHTING | 16690.39 | AstronomicalClock | - | 83.71 | 83.71 | 262.25 | |
Exterior Lighting Total | 16690.39 | 262.25 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:57:58
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
HEATSYS1 BOILER | Boiler:HotWater | 493405.38 | 0.80 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:EIR | 960212.92 | 2.80 | 960381.70 | 2.80 | 3.72 | 12.68 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 15490.23 | 27547.97 | 19494.34 | 8053.63 | 0.71 | - | 5181.81 | 52.56 |
ROOM_2_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 15318.59 | 27242.26 | 19277.71 | 7964.55 | 0.71 | - | 5124.10 | 51.97 |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 84671.76 | 151392.99 | 107180.08 | 44212.91 | 0.71 | - | 29198.08 | 296.14 |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 87137.83 | 152883.47 | 106923.82 | 45959.65 | 0.70 | - | 27921.30 | 283.19 |
ROOM_5_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 13673.80 | 24313.61 | 17203.03 | 7110.58 | 0.71 | - | 4571.64 | 46.37 |
ROOM_6_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 13554.09 | 24100.67 | 17052.33 | 7048.34 | 0.71 | - | 4531.57 | 45.96 |
ROOM_1_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 4179.99 | 7434.69 | 5261.76 | 2172.92 | 0.71 | - | 1398.90 | 14.19 |
ROOM_2_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 4125.88 | 7338.31 | 5193.47 | 2144.85 | 0.71 | - | 1380.71 | 14.00 |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 17504.50 | 30961.43 | 21806.19 | 9155.24 | 0.70 | - | 5751.38 | 58.33 |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | 655657.86 | 661053.24 | 400061.31 | 260991.93 | 0.61 | - | 70371.93 | 713.75 |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | 48199.93 | 47472.21 | 29284.36 | 18187.85 | 0.62 | - | 4618.55 | 46.84 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
BASEMENT VAV BOX REHEAT COIL | Coil:Heating:Water | 13173.56 | 13242.76 | - |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 4625.54 | 4648.42 | - |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 2185.75 | 2196.97 | - |
MECH_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 2965.29 | 2980.01 | - |
STORAGE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1657.71 | 1665.86 | - |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 19387.04 | 19488.47 | - |
CAFE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 14859.37 | 14935.44 | - |
LOBBY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 41161.84 | 41373.85 | - |
ROOM_1_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 5974.04 | 6437.20 | - |
ROOM_2_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 5973.71 | 6436.84 | - |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 34371.24 | 37035.80 | - |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 34381.88 | 37047.27 | - |
ROOM_5_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 5974.04 | 6437.20 | - |
ROOM_6_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 5973.71 | 6436.84 | - |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 15782.72 | 15860.49 | - |
ROOM_1_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 1874.25 | 2019.50 | - |
ROOM_2_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 1875.26 | 2020.59 | - |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 9023.85 | 9723.16 | - |
BANQUET_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 18360.24 | 18455.11 | - |
DINING_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 19076.22 | 19174.83 | - |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 13792.57 | 13864.71 | - |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 10668.74 | 10720.95 | - |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | 195220.44 | 142657.95 | - |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | 15066.37 | 11009.80 | - |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
LAUNDRY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 0.16 | 125.00 | 0.24 | 184.35 | 781.25 | 1.00 | 1.15 | General | ||
LOBBY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | General | |||
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.16 | 270.90 | 1.53 | 2585.88 | 1693.12 | 1.00 | 0.46 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 |
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.16 | 270.90 | 1.51 | 2557.11 | 1693.12 | 1.00 | 0.46 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 |
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.16 | 270.90 | 8.39 | 14202.67 | 1693.12 | 1.00 | 0.39 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 |
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.16 | 270.90 | 8.29 | 14036.20 | 1693.12 | 1.00 | 0.39 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 |
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.16 | 270.90 | 1.35 | 2281.66 | 1693.12 | 1.00 | 0.47 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 |
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.16 | 270.90 | 1.34 | 2261.66 | 1693.12 | 1.00 | 0.47 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 |
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.16 | 270.90 | 0.41 | 698.03 | 1693.12 | 1.00 | 0.63 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 |
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.16 | 270.90 | 0.41 | 688.96 | 1693.12 | 1.00 | 0.63 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 |
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.16 | 270.90 | 1.70 | 2880.65 | 1693.12 | 1.00 | 0.45 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 |
BANQUET_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | General | |||
DINING_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | General | |||
KITCHEN_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 0.16 | 125.00 | 1.89 | 1474.84 | 781.25 | 1.00 | 0.62 | General | ||
VAV WITH REHEAT FAN | Fan:VariableVolume | 0.62 | 1389.42 | 26.58 | 59555.42 | 2240.64 | 1.00 | 1.11 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 |
FLR_3_DOAS FAN | Fan:ConstantVolume | 0.58 | 622.50 | 2.05 | 2194.93 | 1070.05 | 1.00 | 1.30 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 133527.72 | 0.034271 | 7062.08 | 206062.94 | 0.90 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.004317 | 1299.95 | 301156.09 | 0.90 | General |
COOLSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 92445.74 | 0.034271 | 4889.31 | 142664.32 | 0.90 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000375 | 47.91 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWH BOOSTER E WATER HEATER | WaterHeater:Mixed | 0.02 | 8000.00 | 1.00 | 1.24 | 1.15 |
SWH LAUNDRY G WATER HEATER | WaterHeater:Mixed | 1.14 | 163316.00 | 0.80 | 0.58 | 0.51 |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 2.27 | 175842.60 | 0.80 | 0.26 | 0.03 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:57:58
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 34511.35 | 34511.35 | 17.44 | 3.049 | 3.049 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 20:00:00 | 24.00 | 24.00 | 0.00920 | 28.35 | 0.00569 | 0.854 | 0.00 |
RETAIL_1_FLR_1 | 4993.34 | 4993.34 | 74.45 | 0.441 | 0.441 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 24.00 | 24.00 | 0.00892 | 34.76 | 0.00570 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 3309.91 | 3309.91 | 42.62 | 0.292 | 0.292 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 24.00 | 24.00 | 0.00931 | 33.21 | 0.00570 | 0.092 | 0.00 |
MECH_FLR_1 | 3353.74 | 3353.74 | 20.42 | 0.296 | 0.296 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:20:00 | 24.00 | 24.00 | 0.00860 | 31.19 | 0.00569 | 0.000 | 0.00 |
STORAGE_FLR_1 | 1671.20 | 1671.20 | 17.64 | 0.148 | 0.148 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:40:00 | 24.00 | 24.00 | 0.00868 | 32.31 | 0.00570 | 0.058 | 0.00 |
LAUNDRY_FLR_1 | 44925.70 | 44925.70 | 575.68 | 3.969 | 3.969 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 24.00 | 24.00 | 0.00853 | 34.97 | 0.00570 | 0.000 | 0.00 |
CAFE_FLR_1 | 21002.37 | 21002.37 | 111.20 | 1.857 | 1.857 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 24.00 | 23.99 | 0.00998 | 34.76 | 0.00570 | 0.676 | 0.00 |
LOBBY_FLR_1 | 65738.04 | 65738.04 | 50.25 | 5.810 | 5.810 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 24.00 | 23.99 | 0.00991 | 34.88 | 0.00570 | 1.894 | 0.00 |
ROOM_1_FLR_3 | 12830.79 | 12830.79 | 328.81 | 1.527 | 1.527 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 21.11 | 21.11 | 0.00852 | 33.39 | 0.00570 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 12688.04 | 12688.04 | 325.19 | 1.510 | 1.510 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 21.11 | 21.11 | 0.00852 | 33.21 | 0.00570 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 70473.91 | 70473.91 | 2873.69 | 8.388 | 8.388 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 21.11 | 21.11 | 0.00846 | 34.88 | 0.00570 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 69642.18 | 69642.18 | 2839.00 | 8.290 | 8.290 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 21.11 | 21.11 | 0.00867 | 34.97 | 0.00570 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 11321.28 | 11321.28 | 290.13 | 1.348 | 1.348 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 | 21.11 | 21.11 | 0.00852 | 29.59 | 0.00569 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 11222.08 | 11222.08 | 287.62 | 1.336 | 1.336 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 21.11 | 21.11 | 0.00852 | 28.82 | 0.00569 | 0.062 | 0.00 |
CORRIDOR_FLR_3 | 16367.77 | 16367.77 | 42.03 | 1.446 | 1.446 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 24.00 | 24.00 | 0.00960 | 35.10 | 0.00570 | 0.475 | 0.00 |
ROOM_1_FLR_6 | 3463.53 | 3463.53 | 88.76 | 0.412 | 0.412 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 21.11 | 21.11 | 0.00852 | 33.39 | 0.00570 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 3418.52 | 3418.52 | 87.62 | 0.407 | 0.407 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 21.11 | 21.11 | 0.00852 | 33.21 | 0.00570 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 14292.90 | 14292.90 | 582.66 | 1.701 | 1.701 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 21.11 | 21.11 | 0.00858 | 34.99 | 0.00570 | 0.099 | 0.00 |
BANQUET_FLR_6 | 31377.51 | 31377.51 | 94.61 | 2.775 | 2.775 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 24.00 | 23.98 | 0.01028 | 35.10 | 0.00570 | 1.188 | 0.00 |
DINING_FLR_6 | 32917.63 | 32917.63 | 99.25 | 2.912 | 2.912 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 24.00 | 23.98 | 0.01019 | 35.10 | 0.00570 | 1.188 | 0.00 |
KITCHEN_FLR_6 | 31723.10 | 31723.10 | 307.08 | 2.810 | 2.810 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 24.00 | 23.97 | 0.01002 | 33.89 | 0.00570 | 0.367 | 0.00 |
CORRIDOR_FLR_6 | 10284.37 | 10284.37 | 24.95 | 0.908 | 0.908 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 24.00 | 24.00 | 0.00895 | 35.10 | 0.00570 | 0.126 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 0.854 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 22.87 | 0.00234 | -7.90 | 0.00234 | 0.854 | 0.00 |
RETAIL_1_FLR_1 | 2720.99 | 2720.99 | 40.57 | 0.142 | 0.142 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00760 | -7.90 | 0.00234 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 923.25 | 923.25 | 11.89 | 0.048 | 0.092 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00755 | -7.90 | 0.00234 | 0.092 | 0.00 |
MECH_FLR_1 | 1686.67 | 1686.67 | 10.27 | 0.088 | 0.088 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00743 | -7.90 | 0.00234 | 0.000 | 0.00 |
STORAGE_FLR_1 | 1020.53 | 1020.53 | 10.77 | 0.053 | 0.058 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00745 | -7.90 | 0.00234 | 0.058 | 0.00 |
LAUNDRY_FLR_1 | 2259.11 | 2259.11 | 28.95 | 0.118 | 0.118 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00742 | -7.90 | 0.00234 | 0.000 | 0.00 |
CAFE_FLR_1 | 6840.58 | 6840.58 | 36.22 | 0.356 | 0.676 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00765 | -7.90 | 0.00234 | 0.676 | 0.00 |
LOBBY_FLR_1 | 16078.57 | 16078.57 | 12.29 | 0.838 | 1.894 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00757 | -7.90 | 0.00234 | 1.894 | 0.00 |
ROOM_1_FLR_3 | 5974.19 | 5974.19 | 153.10 | 0.313 | 0.313 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00758 | -7.90 | 0.00234 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 5973.86 | 5973.86 | 153.11 | 0.313 | 0.313 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00758 | -7.90 | 0.00234 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 34371.66 | 34371.66 | 1401.56 | 1.802 | 1.802 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00761 | -7.90 | 0.00234 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 34382.30 | 34382.30 | 1401.61 | 1.802 | 1.802 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00761 | -7.90 | 0.00234 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 5974.19 | 5974.19 | 153.10 | 0.313 | 0.313 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00758 | -7.90 | 0.00234 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 5973.86 | 5973.86 | 153.11 | 0.313 | 0.313 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00758 | -7.90 | 0.00234 | 0.062 | 0.00 |
CORRIDOR_FLR_3 | 9538.88 | 9538.88 | 24.50 | 0.497 | 0.497 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00767 | -7.90 | 0.00234 | 0.475 | 0.00 |
ROOM_1_FLR_6 | 1874.29 | 1874.29 | 48.03 | 0.098 | 0.098 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00766 | -7.90 | 0.00234 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 1875.30 | 1875.30 | 48.06 | 0.098 | 0.098 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00766 | -7.90 | 0.00234 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 9024.02 | 9024.02 | 367.87 | 0.473 | 0.473 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00767 | -7.90 | 0.00234 | 0.099 | 0.00 |
BANQUET_FLR_6 | 6373.41 | 6373.41 | 19.22 | 0.332 | 1.188 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00775 | -7.90 | 0.00234 | 1.188 | 0.00 |
DINING_FLR_6 | 6502.08 | 6502.08 | 19.60 | 0.339 | 1.188 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 19:20:00 | 21.00 | 21.00 | 0.00776 | -7.90 | 0.00234 | 1.188 | 0.00 |
KITCHEN_FLR_6 | 1698.11 | 1698.11 | 16.44 | 0.088 | 0.367 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | 21.00 | 21.00 | 0.00630 | -7.90 | 0.00234 | 0.367 | 0.00 |
CORRIDOR_FLR_6 | 6744.85 | 6744.85 | 16.37 | 0.351 | 0.351 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:50:00 | 21.00 | 21.00 | 0.00779 | -7.90 | 0.00234 | 0.126 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV WITH REHEAT | 26.57 | 26.57 | 7.51 | 7.51 | 26.5797 | 26.5797 | 26.5797 | 1.0000 | 0.3000 |
FLR_3_DOAS | 23.56 | 2.05 | 5.53 | 2.05 | 2.0513 | 2.0513 | 2.0513 | 1.0000 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
BASEMENT VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | 13173.560 | 13173.560 | 3.033492 | 0.00011525 | 274.712 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 13173.56 | 13173.56 | 3.033492 | 16.70 | 11.36 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00800000 | 42.5367 | 0.00 | 0.00 | 13247.60 | 13247.60 |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | 4625.543 | 4625.543 | 0.438935 | 0.00004047 | 104.221 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 4625.54 | 4625.54 | 0.438935 | 16.70 | 11.36 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00759991 | 40.4364 | 2720.99 | 0.00 | 4650.53 | 4650.53 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | 2185.746 | 2185.746 | 0.290968 | 0.00001912 | 47.380 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 2185.75 | 2185.75 | 0.290968 | 16.70 | 11.36 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00754918 | 40.1689 | 923.25 | 0.00 | 2197.88 | 2197.88 |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | 2965.288 | 2965.288 | 0.294750 | 0.00002594 | 66.397 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 2965.29 | 2965.29 | 0.294750 | 16.70 | 11.36 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00743009 | 39.5427 | 1686.67 | 0.00 | 2981.35 | 2981.35 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | 1657.712 | 1657.712 | 0.146878 | 0.00001450 | 37.722 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 1657.71 | 1657.71 | 0.146878 | 16.70 | 11.36 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00745402 | 39.6686 | 1020.53 | 0.00 | 1666.64 | 1666.64 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 19387.043 | 19387.043 | 3.948728 | 0.00016961 | 407.039 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 19387.04 | 19387.04 | 3.948728 | 16.70 | 11.36 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00742022 | 39.4916 | 2259.11 | 0.00 | 19495.74 | 19495.74 |
CAFE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | 14859.370 | 14859.370 | 1.847866 | 0.00013000 | 324.254 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 14859.37 | 14859.37 | 1.847866 | 16.70 | 11.36 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00764518 | 40.6740 | 6840.58 | 0.00 | 14941.68 | 14941.68 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 41161.844 | 41161.844 | 5.780678 | 0.00036010 | 887.906 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 41161.84 | 41161.84 | 5.780678 | 16.70 | 11.36 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00757438 | 40.3014 | 16078.57 | 0.00 | 41390.60 | 41390.60 |
ROOM_1_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 15490.230 | -999.000 | 1.527282 | 0.00055326 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | unknown | 7/21 16:50:00 | 15490.23 | 15438.03 | 1.527282 | 22.79 | 13.99 | 0.00851914 | 12.80 | 10.33 | 0.00850000 | 33.39 | 0.00569673 | 15.22 | 0.0000 | 21.11 | 0.00851914 | 44.9525 | 12830.79 | 0.00 | 18937.82 | 17799.86 |
ROOM_1_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 5974.038 | 5974.038 | 0.313150 | 0.00005226 | 170.713 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 5974.04 | 5974.04 | 0.313150 | 21.11 | 12.61 | 0.00758092 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.11 | 0.00758092 | 40.0626 | 5974.19 | 0.00 | 6440.16 | 6440.16 |
ROOM_2_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 15318.594 | -999.000 | 1.510290 | 0.00054713 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | unknown | 7/21 17:00:00 | 15318.59 | 15266.47 | 1.510290 | 22.79 | 13.99 | 0.00851933 | 12.80 | 10.33 | 0.00850000 | 33.21 | 0.00569645 | 15.16 | 0.0000 | 21.11 | 0.00851933 | 44.9535 | 12688.04 | 0.00 | 18727.89 | 17601.85 |
ROOM_2_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 5973.709 | 5973.709 | 0.313133 | 0.00005226 | 170.704 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 5973.71 | 5973.71 | 0.313133 | 21.11 | 12.61 | 0.00758093 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.11 | 0.00758093 | 40.0627 | 5973.86 | 0.00 | 6439.81 | 6439.81 |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 84671.757 | -999.000 | 8.388434 | 0.00302422 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | unknown | 7/21 13:40:00 | 84671.76 | 84671.76 | 8.388434 | 22.79 | 13.94 | 0.00846252 | 12.80 | 10.30 | 0.00846252 | 34.88 | 0.00569904 | 15.70 | 0.0000 | 21.11 | 0.00846252 | 44.6570 | 70473.91 | 0.00 | 103651.90 | 98176.90 |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 34371.241 | 34371.241 | 1.801722 | 0.00030069 | 982.172 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 34371.24 | 34371.24 | 1.801722 | 21.11 | 12.63 | 0.00761158 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.11 | 0.00761158 | 40.2219 | 34371.66 | 0.00 | 37053.26 | 37053.26 |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 87137.830 | -999.000 | 8.290116 | 0.00311230 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | unknown | 7/21 15:10:00 | 87137.83 | 84657.34 | 8.290116 | 22.78 | 14.11 | 0.00866587 | 12.80 | 10.33 | 0.00850000 | 34.97 | 0.00569918 | 15.73 | 0.0000 | 21.11 | 0.00866587 | 45.7173 | 69642.18 | 0.00 | 106137.90 | 96751.72 |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 34381.883 | 34381.883 | 1.802280 | 0.00030079 | 982.477 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 34381.88 | 34381.88 | 1.802280 | 21.11 | 12.63 | 0.00761160 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.11 | 0.00761160 | 40.2220 | 34382.30 | 0.00 | 37064.73 | 37064.73 |
ROOM_5_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 13673.805 | -999.000 | 1.347600 | 0.00048839 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 | unknown | 7/21 09:50:00 | 13673.80 | 13623.50 | 1.347600 | 22.79 | 13.99 | 0.00852090 | 12.80 | 10.33 | 0.00850000 | 29.59 | 0.00569088 | 13.95 | 0.0000 | 21.11 | 0.00852090 | 44.9617 | 11321.28 | 0.00 | 16716.32 | 15705.98 |
ROOM_5_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 5974.038 | 5974.038 | 0.313150 | 0.00005226 | 170.713 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 5974.04 | 5974.04 | 0.313150 | 21.11 | 12.61 | 0.00758092 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.11 | 0.00758092 | 40.0626 | 5974.19 | 0.00 | 6440.16 | 6440.16 |
ROOM_6_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 13554.087 | -999.000 | 1.335793 | 0.00048411 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | unknown | 7/21 09:30:00 | 13554.09 | 13504.16 | 1.335793 | 22.79 | 13.99 | 0.00852093 | 12.80 | 10.33 | 0.00850000 | 28.82 | 0.00568971 | 13.69 | 0.0000 | 21.11 | 0.00852093 | 44.9618 | 11222.08 | 0.00 | 16569.95 | 15568.37 |
ROOM_6_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 5973.709 | 5973.709 | 0.313133 | 0.00005226 | 170.704 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 5973.71 | 5973.71 | 0.313133 | 21.11 | 12.61 | 0.00758093 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.11 | 0.00758093 | 40.0627 | 5973.86 | 0.00 | 6439.81 | 6439.81 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | 15782.723 | 15782.723 | 1.438658 | 0.00013807 | 357.644 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 15782.72 | 15782.72 | 1.438658 | 16.70 | 11.36 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00767494 | 40.8296 | 9538.88 | 0.00 | 15867.82 | 15867.82 |
ROOM_1_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 4179.987 | -999.000 | 0.412273 | 0.00014930 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | unknown | 7/21 16:50:00 | 4179.99 | 4166.91 | 0.412273 | 22.79 | 13.99 | 0.00851777 | 12.80 | 10.33 | 0.00850000 | 33.39 | 0.00569673 | 15.22 | 0.0000 | 21.11 | 0.00851777 | 44.9453 | 3463.53 | 0.00 | 5110.50 | 4804.82 |
ROOM_1_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 1874.247 | 1874.247 | 0.098245 | 0.00001640 | 53.556 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 1874.25 | 1874.25 | 0.098245 | 21.11 | 12.68 | 0.00766089 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.11 | 0.00766089 | 40.4801 | 1874.29 | 0.00 | 2020.49 | 2020.49 |
ROOM_2_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 4125.881 | -999.000 | 0.406916 | 0.00014736 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | unknown | 7/21 17:00:00 | 4125.88 | 4112.82 | 0.406916 | 22.79 | 13.99 | 0.00851797 | 12.80 | 10.33 | 0.00850000 | 33.21 | 0.00569645 | 15.16 | 0.0000 | 21.11 | 0.00851797 | 44.9464 | 3418.52 | 0.00 | 5044.32 | 4742.39 |
ROOM_2_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 1875.257 | 1875.257 | 0.098298 | 0.00001641 | 53.584 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 1875.26 | 1875.26 | 0.098298 | 21.11 | 12.68 | 0.00766108 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.11 | 0.00766108 | 40.4811 | 1875.30 | 0.00 | 2021.57 | 2021.57 |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 17504.501 | -999.000 | 1.701378 | 0.00062521 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | unknown | 7/21 13:50:00 | 17504.50 | 17268.65 | 1.701378 | 22.79 | 14.04 | 0.00857732 | 12.80 | 10.33 | 0.00850000 | 34.99 | 0.00569921 | 15.74 | 0.0000 | 21.11 | 0.00857732 | 45.2561 | 14292.90 | 0.00 | 21366.92 | 19838.47 |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 9023.848 | 9023.848 | 0.473020 | 0.00007894 | 257.850 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 9023.85 | 9023.85 | 0.473020 | 21.11 | 12.69 | 0.00767482 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.11 | 0.00767482 | 40.5525 | 9024.02 | 0.00 | 9727.95 | 9727.95 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 18360.242 | 18360.242 | 2.761603 | 0.00016062 | 393.738 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 18360.24 | 18360.24 | 2.761603 | 16.70 | 11.36 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00775091 | 41.2291 | 6373.41 | 0.00 | 18462.46 | 18462.46 |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 19076.215 | 19076.215 | 2.897101 | 0.00016689 | 408.770 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 19:20:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 19:20:00 | 19076.22 | 19076.22 | 2.897101 | 16.70 | 11.36 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00775563 | 41.2547 | 6502.08 | 0.00 | 19182.44 | 19182.44 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 13792.571 | 13792.571 | 2.796066 | 0.00012066 | 289.661 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | 13792.57 | 13792.57 | 2.796066 | 16.70 | 11.36 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00630261 | 33.6098 | 1698.11 | 0.00 | 13869.89 | 13869.89 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | 10668.740 | 10668.740 | 0.903938 | 0.00009333 | 244.452 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:50:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:50:00 | 10668.74 | 10668.74 | 0.903938 | 16.70 | 11.36 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00779218 | 41.4459 | 6744.85 | 0.00 | 10726.03 | 10726.03 |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV WITH REHEAT | 655657.863 | -999.000 | 26.579661 | 0.02341858 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 655657.86 | 655657.86 | 26.579661 | 35.10 | 15.77 | 0.00569938 | 10.57 | 6.56 | 0.00569938 | 35.10 | 0.00569938 | 15.77 | 99.9533 | 23.99 | 0.00961449 | 42.5143 | 300527.60 | 0.00 | 656275.91 | 656275.91 |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV WITH REHEAT | 195220.439 | 195220.439 | 7.973898 | 0.00170787 | 3266.920 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 195220.44 | 195220.44 | 7.973898 | -7.90 | -7.90 | 0.00234317 | 16.70 | 11.36 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 333.1776 | 21.57 | 0.00603739 | 31.0949 | 61818.88 | 0.00 | 172431.12 | 172431.12 |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | FLR_3_DOAS | 48199.928 | -999.000 | 2.051317 | 0.00172159 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 48199.93 | 48199.93 | 2.051317 | 35.10 | 15.77 | 0.00569938 | 11.74 | 7.07 | 0.00569938 | 35.10 | 0.00569938 | 15.77 | 99.9965 | 21.11 | 0.00856398 | 45.1861 | 197890.13 | 0.00 | 48236.96 | 48236.96 |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | FLR_3_DOAS | 15066.372 | 15066.372 | 0.615395 | 0.00013181 | 252.128 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 15066.37 | 15066.37 | 0.615395 | -7.90 | -7.90 | 0.00234317 | 16.70 | 11.36 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 333.3216 | 21.11 | 0.00761203 | 40.2243 | 105423.66 | 0.00 | 13307.58 | 13307.58 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:57:58
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
BASEMENT VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | BASEMENT | N/A | N/A | N/A | Yes | Yes | Yes | No | 13173.560 | 13173.560 | 3.033492 | 0.00011525 | 274.712 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.31608514 | 54.44 | 82.22 | 27.78 | 503335.35 | 2.6173 | 2.669926 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 13173.56 | 13173.56 | 1.0000 | 3.00439720 | 3.033492 | 16.70 | 11.36 | 0.00800000 | 37036.7 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.11523630 | 60.00 | 32.22 | 27.78 | 0.000 | 13173.56 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 42.5367 | 0.00 | 0.00 | 13247.60 | 13247.60 | 3.00439720 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 20.92 | 14.82 | 0.00800000 | 41344.1 | |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | RETAIL_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 4625.543 | 4625.543 | 0.438935 | 0.00004047 | 104.221 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.31608514 | 54.44 | 82.22 | 27.78 | 503335.35 | 0.9190 | 0.937473 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 4625.54 | 4625.54 | 1.0000 | 0.43472525 | 0.438935 | 16.70 | 11.36 | 0.00800000 | 37036.7 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.04046214 | 60.00 | 32.22 | 27.78 | 0.000 | 4625.54 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 21.00 | 0.00759991 | 21.00 | 0.00759991 | 40.4364 | 2720.99 | 0.00 | 4650.53 | 4650.53 | 0.43472525 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 27.09 | 17.05 | 0.00800000 | 47632.4 | |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | RETAIL_2_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2185.746 | 2185.746 | 0.290968 | 0.00001912 | 47.380 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.31608514 | 54.44 | 82.22 | 27.78 | 503335.35 | 0.4343 | 0.442992 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 2185.75 | 2185.75 | 1.0000 | 0.28817721 | 0.290968 | 16.70 | 11.36 | 0.00800000 | 37036.7 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.01911991 | 60.00 | 32.22 | 27.78 | 0.000 | 2185.75 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 21.00 | 0.00754918 | 21.00 | 0.00754918 | 40.1689 | 923.25 | 0.00 | 2197.88 | 2197.88 | 0.28817721 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 24.08 | 15.98 | 0.00800000 | 44561.6 | |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | MECH_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2965.288 | 2965.288 | 0.294750 | 0.00002594 | 66.397 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.31608514 | 54.44 | 82.22 | 27.78 | 503335.35 | 0.5891 | 0.600984 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 2965.29 | 2965.29 | 1.0000 | 0.29192266 | 0.294750 | 16.70 | 11.36 | 0.00800000 | 37036.7 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.02593898 | 60.00 | 32.22 | 27.78 | 0.000 | 2965.29 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 21.00 | 0.00743009 | 21.00 | 0.00743009 | 39.5427 | 1686.67 | 0.00 | 2981.35 | 2981.35 | 0.29192266 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 26.62 | 16.88 | 0.00800000 | 47147.5 | |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | STORAGE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1657.712 | 1657.712 | 0.146878 | 0.00001450 | 37.722 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.31608514 | 54.44 | 82.22 | 27.78 | 503335.35 | 0.3293 | 0.335974 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 1657.71 | 1657.71 | 1.0000 | 0.14546969 | 0.146878 | 16.70 | 11.36 | 0.00800000 | 37036.7 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.01450091 | 60.00 | 32.22 | 27.78 | 0.000 | 1657.71 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 21.00 | 0.00745402 | 21.00 | 0.00745402 | 39.6686 | 1020.53 | 0.00 | 1666.64 | 1666.64 | 0.14546969 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 27.84 | 17.30 | 0.00800000 | 48391.7 | |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LAUNDRY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 19387.043 | 19387.043 | 3.948728 | 0.00016961 | 407.039 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.31608514 | 54.44 | 82.22 | 27.78 | 503335.35 | 3.8517 | 3.929232 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 19387.04 | 19387.04 | 1.0000 | 3.91085547 | 3.948728 | 16.70 | 11.36 | 0.00800000 | 37036.7 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.16958901 | 60.00 | 32.22 | 27.78 | 0.000 | 19387.04 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 21.00 | 0.00742022 | 21.00 | 0.00742022 | 39.4916 | 2259.11 | 0.00 | 19495.74 | 19495.74 | 3.91085547 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 21.49 | 15.03 | 0.00800000 | 41919.8 | |
CAFE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | CAFE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 14859.370 | 14859.370 | 1.847866 | 0.00013000 | 324.254 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.31608514 | 54.44 | 82.22 | 27.78 | 503335.35 | 2.9522 | 3.011595 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 14859.37 | 14859.37 | 1.0000 | 1.83014263 | 1.847866 | 16.70 | 11.36 | 0.00800000 | 37036.7 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.12998299 | 60.00 | 32.22 | 27.78 | 0.000 | 14859.37 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 21.00 | 0.00764518 | 21.00 | 0.00764518 | 40.6740 | 6840.58 | 0.00 | 14941.68 | 14941.68 | 1.83014263 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 24.61 | 16.17 | 0.00800000 | 45099.0 | |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LOBBY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 41161.844 | 41161.844 | 5.780678 | 0.00036010 | 887.906 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.31608514 | 54.44 | 82.22 | 27.78 | 503335.35 | 8.1778 | 8.342399 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 41161.84 | 41161.84 | 1.0000 | 5.72523493 | 5.780678 | 16.70 | 11.36 | 0.00800000 | 37036.7 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.36006504 | 60.00 | 32.22 | 27.78 | 0.000 | 41161.84 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 21.00 | 0.00757438 | 21.00 | 0.00757438 | 40.3014 | 16078.57 | 0.00 | 41390.60 | 41390.60 | 5.72523493 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 23.69 | 15.84 | 0.00800000 | 44164.2 | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 15490.230 | -999.000 | 1.527282 | 0.00055326 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6767 | 1004.8586 | 0.9904 | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.527282 | 1.51263386 | 4197.9300 | 999.8980 | 34.26796688 | 13.37 | 6.70 | 6.67 | 959509.69 | 1.6144 | 1.614360 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | unknown | unknown | unknown | 7/21 16:50:00 | Sensible | 15490.23 | 15438.03 | 1.0000 | 1.51263386 | 1.527282 | 22.79 | 13.99 | 0.00851914 | 44562.8 | 12.80 | 10.33 | 0.00850000 | 34322.2 | 0.55320836 | 6.70 | 13.37 | 6.67 | 0.000 | 15490.23 | 33.39 | 0.00569673 | 15.22 | 0.00000000 | 0.0000 | 21.11 | 0.00851914 | 21.11 | 0.00851914 | 44.9525 | 12830.79 | 0.00 | 18937.82 | 17799.86 | 1.51263386 | 22.79 | 15.97 | 0.00851914 | 44562.8 | 11.26 | 11.17 | 0.00822083 | 32043.0 | |
ROOM_1_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5974.038 | 5974.038 | 0.313150 | 0.00005226 | 170.713 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.527282 | 1.51263386 | 4197.9300 | 999.8980 | 4.31608514 | 54.44 | 82.22 | 27.78 | 503335.35 | 1.1869 | 1.210777 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 5974.04 | 5974.04 | 1.0000 | 0.31014697 | 0.313150 | 21.11 | 12.61 | 0.00758092 | 40469.5 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.05225816 | 60.00 | 32.22 | 27.78 | 0.000 | 5974.04 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 21.11 | 0.00758092 | 21.11 | 0.00758092 | 40.0626 | 5974.19 | 0.00 | 6440.16 | 6440.16 | 0.31014697 | 16.60 | 12.74 | 0.00758092 | 35873.7 | 36.98 | 19.96 | 0.00758092 | 56638.6 | |
ROOM_2_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 15318.594 | -999.000 | 1.510290 | 0.00054713 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6770 | 1004.8586 | 0.9904 | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.510290 | 1.49580463 | 4197.9300 | 999.8980 | 34.26796688 | 13.37 | 6.70 | 6.67 | 959509.69 | 1.5965 | 1.596472 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | unknown | unknown | unknown | 7/21 17:00:00 | Sensible | 15318.59 | 15266.47 | 1.0000 | 1.49580463 | 1.510290 | 22.79 | 13.99 | 0.00851933 | 44563.2 | 12.80 | 10.33 | 0.00850000 | 34322.2 | 0.54707865 | 6.70 | 13.37 | 6.67 | 0.000 | 15318.59 | 33.21 | 0.00569645 | 15.16 | 0.00000000 | 0.0000 | 21.11 | 0.00851933 | 21.11 | 0.00851933 | 44.9535 | 12688.04 | 0.00 | 18727.89 | 17601.85 | 1.49580463 | 22.79 | 15.97 | 0.00851933 | 44563.2 | 11.26 | 11.17 | 0.00822082 | 32043.0 | |
ROOM_2_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5973.709 | 5973.709 | 0.313133 | 0.00005226 | 170.704 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.510290 | 1.49580463 | 4197.9300 | 999.8980 | 4.31608514 | 54.44 | 82.22 | 27.78 | 503335.35 | 1.1868 | 1.210710 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 5973.71 | 5973.71 | 1.0000 | 0.31012991 | 0.313133 | 21.11 | 12.61 | 0.00758093 | 40469.5 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.05225528 | 60.00 | 32.22 | 27.78 | 0.000 | 5973.71 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 21.11 | 0.00758093 | 21.11 | 0.00758093 | 40.0627 | 5973.86 | 0.00 | 6439.81 | 6439.81 | 0.31012991 | 16.60 | 12.74 | 0.00758093 | 35873.7 | 36.98 | 19.96 | 0.00758093 | 56638.6 | |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 84671.757 | -999.000 | 8.388434 | 0.00302422 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.5714 | 1004.8586 | 0.9904 | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 8.388434 | 8.30797974 | 4197.9300 | 999.8980 | 34.26796688 | 13.37 | 6.70 | 6.67 | 959509.69 | 8.8245 | 8.824317 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | unknown | unknown | unknown | 7/21 13:40:00 | Sensible | 84671.76 | 84671.76 | 1.0000 | 8.30797974 | 8.388434 | 22.79 | 13.94 | 0.00846252 | 44419.2 | 12.80 | 10.30 | 0.00846252 | 34227.6 | 3.02391401 | 6.70 | 13.37 | 6.67 | 0.000 | 84671.76 | 34.88 | 0.00569904 | 15.70 | 0.00000000 | 0.0000 | 21.11 | 0.00846252 | 21.11 | 0.00846252 | 44.6570 | 70473.91 | 0.00 | 103651.90 | 98176.90 | 8.30797974 | 22.79 | 15.92 | 0.00846252 | 44419.2 | 11.21 | 11.13 | 0.00820119 | 31943.0 | |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 34371.241 | 34371.241 | 1.801722 | 0.00030069 | 982.172 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 8.388434 | 8.30797974 | 4197.9300 | 999.8980 | 4.31608514 | 54.44 | 82.22 | 27.78 | 503335.35 | 6.8287 | 6.966126 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 34371.24 | 34371.24 | 1.0000 | 1.78444187 | 1.801722 | 21.11 | 12.63 | 0.00761158 | 40547.7 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.30066393 | 60.00 | 32.22 | 27.78 | 0.000 | 34371.24 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 21.11 | 0.00761158 | 21.11 | 0.00761158 | 40.2219 | 34371.66 | 0.00 | 37053.26 | 37053.26 | 1.78444187 | 16.60 | 12.77 | 0.00761158 | 35951.3 | 36.98 | 19.98 | 0.00761158 | 56716.0 | |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 87137.830 | -999.000 | 8.290116 | 0.00311230 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9494 | 1004.8586 | 0.9904 | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 8.290116 | 8.21060470 | 4197.9300 | 999.8980 | 34.26796688 | 13.37 | 6.70 | 6.67 | 959509.69 | 9.0815 | 9.081326 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | unknown | unknown | unknown | 7/21 15:10:00 | Sensible | 87137.83 | 84657.34 | 1.0000 | 8.21060470 | 8.290116 | 22.78 | 14.11 | 0.00866587 | 44935.0 | 12.80 | 10.33 | 0.00850000 | 34322.2 | 3.11198579 | 6.70 | 13.37 | 6.67 | 0.000 | 87137.83 | 34.97 | 0.00569918 | 15.73 | 0.00000000 | 0.0000 | 21.11 | 0.00866587 | 21.11 | 0.00866587 | 45.7173 | 69642.18 | 0.00 | 106137.90 | 96751.72 | 8.21060470 | 22.78 | 16.10 | 0.00866587 | 44935.0 | 11.24 | 11.15 | 0.00821256 | 32008.1 | |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 34381.883 | 34381.883 | 1.802280 | 0.00030079 | 982.477 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 8.290116 | 8.21060470 | 4197.9300 | 999.8980 | 4.31608514 | 54.44 | 82.22 | 27.78 | 503335.35 | 6.8308 | 6.968283 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 34381.88 | 34381.88 | 1.0000 | 1.78499437 | 1.802280 | 21.11 | 12.63 | 0.00761160 | 40547.7 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.30075703 | 60.00 | 32.22 | 27.78 | 0.000 | 34381.88 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 21.11 | 0.00761160 | 21.11 | 0.00761160 | 40.2220 | 34382.30 | 0.00 | 37064.73 | 37064.73 | 1.78499437 | 16.60 | 12.77 | 0.00761160 | 35951.4 | 36.98 | 19.98 | 0.00761160 | 56716.0 | |
ROOM_5_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 13673.805 | -999.000 | 1.347600 | 0.00048839 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6799 | 1004.8586 | 0.9904 | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.347600 | 1.33467520 | 4197.9300 | 999.8980 | 34.26796688 | 13.37 | 6.70 | 6.67 | 959509.69 | 1.4251 | 1.425056 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 | unknown | unknown | unknown | 7/21 09:50:00 | Sensible | 13673.80 | 13623.50 | 1.0000 | 1.33467520 | 1.347600 | 22.79 | 13.99 | 0.00852090 | 44567.2 | 12.80 | 10.33 | 0.00850000 | 34322.2 | 0.48833769 | 6.70 | 13.37 | 6.67 | 0.000 | 13673.80 | 29.59 | 0.00569088 | 13.95 | 0.00000000 | 0.0000 | 21.11 | 0.00852090 | 21.11 | 0.00852090 | 44.9617 | 11321.28 | 0.00 | 16716.32 | 15705.98 | 1.33467520 | 22.79 | 15.97 | 0.00852090 | 44567.2 | 11.26 | 11.17 | 0.00822073 | 32042.6 | |
ROOM_5_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5974.038 | 5974.038 | 0.313150 | 0.00005226 | 170.713 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.347600 | 1.33467520 | 4197.9300 | 999.8980 | 4.31608514 | 54.44 | 82.22 | 27.78 | 503335.35 | 1.1869 | 1.210777 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 5974.04 | 5974.04 | 1.0000 | 0.31014697 | 0.313150 | 21.11 | 12.61 | 0.00758092 | 40469.5 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.05225816 | 60.00 | 32.22 | 27.78 | 0.000 | 5974.04 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 21.11 | 0.00758092 | 21.11 | 0.00758092 | 40.0626 | 5974.19 | 0.00 | 6440.16 | 6440.16 | 0.31014697 | 16.60 | 12.74 | 0.00758092 | 35873.7 | 36.98 | 19.96 | 0.00758092 | 56638.6 | |
ROOM_6_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 13554.087 | -999.000 | 1.335793 | 0.00048411 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6800 | 1004.8586 | 0.9904 | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.335793 | 1.32298095 | 4197.9300 | 999.8980 | 34.26796688 | 13.37 | 6.70 | 6.67 | 959509.69 | 1.4126 | 1.412579 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | unknown | unknown | unknown | 7/21 09:30:00 | Sensible | 13554.09 | 13504.16 | 1.0000 | 1.32298095 | 1.335793 | 22.79 | 13.99 | 0.00852093 | 44567.3 | 12.80 | 10.33 | 0.00850000 | 34322.2 | 0.48406215 | 6.70 | 13.37 | 6.67 | 0.000 | 13554.09 | 28.82 | 0.00568971 | 13.69 | 0.00000000 | 0.0000 | 21.11 | 0.00852093 | 21.11 | 0.00852093 | 44.9618 | 11222.08 | 0.00 | 16569.95 | 15568.37 | 1.32298095 | 22.79 | 15.97 | 0.00852093 | 44567.3 | 11.26 | 11.17 | 0.00822073 | 32042.6 | |
ROOM_6_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5973.709 | 5973.709 | 0.313133 | 0.00005226 | 170.704 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.335793 | 1.32298095 | 4197.9300 | 999.8980 | 4.31608514 | 54.44 | 82.22 | 27.78 | 503335.35 | 1.1868 | 1.210710 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 5973.71 | 5973.71 | 1.0000 | 0.31012991 | 0.313133 | 21.11 | 12.61 | 0.00758093 | 40469.5 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.05225528 | 60.00 | 32.22 | 27.78 | 0.000 | 5973.71 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 21.11 | 0.00758093 | 21.11 | 0.00758093 | 40.0627 | 5973.86 | 0.00 | 6439.81 | 6439.81 | 0.31012991 | 16.60 | 12.74 | 0.00758093 | 35873.7 | 36.98 | 19.96 | 0.00758093 | 56638.6 | |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | CORRIDOR_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 15782.723 | 15782.723 | 1.438658 | 0.00013807 | 357.644 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.31608514 | 54.44 | 82.22 | 27.78 | 503335.35 | 3.1356 | 3.198733 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 15782.72 | 15782.72 | 1.0000 | 1.42485923 | 1.438658 | 16.70 | 11.36 | 0.00800000 | 37036.7 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.13806006 | 60.00 | 32.22 | 27.78 | 0.000 | 15782.72 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 21.00 | 0.00767494 | 21.00 | 0.00767494 | 40.8296 | 9538.88 | 0.00 | 15867.82 | 15867.82 | 1.42485923 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 27.52 | 17.20 | 0.00800000 | 48071.1 | |
ROOM_1_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 4179.987 | -999.000 | 0.412273 | 0.00014930 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6741 | 1004.8586 | 0.9904 | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.412273 | 0.40831883 | 4197.9300 | 999.8980 | 34.26796688 | 13.37 | 6.70 | 6.67 | 959509.69 | 0.4356 | 0.435630 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | unknown | unknown | unknown | 7/21 16:50:00 | Sensible | 4179.99 | 4166.91 | 1.0000 | 0.40831883 | 0.412273 | 22.79 | 13.99 | 0.00851777 | 44559.3 | 12.80 | 10.33 | 0.00850000 | 34322.2 | 0.14928145 | 6.70 | 13.37 | 6.67 | 0.000 | 4179.99 | 33.39 | 0.00569673 | 15.22 | 0.00000000 | 0.0000 | 21.11 | 0.00851777 | 21.11 | 0.00851777 | 44.9453 | 3463.53 | 0.00 | 5110.50 | 4804.82 | 0.40831883 | 22.79 | 15.97 | 0.00851777 | 44559.3 | 11.26 | 11.17 | 0.00822091 | 32043.3 | |
ROOM_1_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1874.247 | 1874.247 | 0.098245 | 0.00001640 | 53.556 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.412273 | 0.40831883 | 4197.9300 | 999.8980 | 4.31608514 | 54.44 | 82.22 | 27.78 | 503335.35 | 0.3724 | 0.379860 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 1874.25 | 1874.25 | 1.0000 | 0.09730307 | 0.098245 | 21.11 | 12.68 | 0.00766089 | 40672.6 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.01639506 | 60.00 | 32.22 | 27.78 | 0.000 | 1874.25 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 21.11 | 0.00766089 | 21.11 | 0.00766089 | 40.4801 | 1874.29 | 0.00 | 2020.49 | 2020.49 | 0.09730307 | 16.60 | 12.82 | 0.00766089 | 36076.2 | 36.98 | 20.02 | 0.00766089 | 56841.0 | |
ROOM_2_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 4125.881 | -999.000 | 0.406916 | 0.00014736 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6745 | 1004.8586 | 0.9904 | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.406916 | 0.40301277 | 4197.9300 | 999.8980 | 34.26796688 | 13.37 | 6.70 | 6.67 | 959509.69 | 0.4300 | 0.429991 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | unknown | unknown | unknown | 7/21 17:00:00 | Sensible | 4125.88 | 4112.82 | 1.0000 | 0.40301277 | 0.406916 | 22.79 | 13.99 | 0.00851797 | 44559.8 | 12.80 | 10.33 | 0.00850000 | 34322.2 | 0.14734911 | 6.70 | 13.37 | 6.67 | 0.000 | 4125.88 | 33.21 | 0.00569645 | 15.16 | 0.00000000 | 0.0000 | 21.11 | 0.00851797 | 21.11 | 0.00851797 | 44.9464 | 3418.52 | 0.00 | 5044.32 | 4742.39 | 0.40301277 | 22.79 | 15.97 | 0.00851797 | 44559.8 | 11.26 | 11.17 | 0.00822090 | 32043.3 | |
ROOM_2_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1875.257 | 1875.257 | 0.098298 | 0.00001641 | 53.584 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.406916 | 0.40301277 | 4197.9300 | 999.8980 | 4.31608514 | 54.44 | 82.22 | 27.78 | 503335.35 | 0.3726 | 0.380064 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 1875.26 | 1875.26 | 1.0000 | 0.09735548 | 0.098298 | 21.11 | 12.68 | 0.00766108 | 40673.1 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.01640389 | 60.00 | 32.22 | 27.78 | 0.000 | 1875.26 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 21.11 | 0.00766108 | 21.11 | 0.00766108 | 40.4811 | 1875.30 | 0.00 | 2021.57 | 2021.57 | 0.09735548 | 16.60 | 12.82 | 0.00766108 | 36076.7 | 36.98 | 20.02 | 0.00766108 | 56841.5 | |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 17504.501 | -999.000 | 1.701378 | 0.00062521 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7848 | 1004.8586 | 0.9904 | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.701378 | 1.68506000 | 4197.9300 | 999.8980 | 34.26796688 | 13.37 | 6.70 | 6.67 | 959509.69 | 1.8243 | 1.824283 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | unknown | unknown | unknown | 7/21 13:50:00 | Sensible | 17504.50 | 17268.65 | 1.0000 | 1.68506000 | 1.701378 | 22.79 | 14.04 | 0.00857732 | 44710.3 | 12.80 | 10.33 | 0.00850000 | 34322.2 | 0.62514477 | 6.70 | 13.37 | 6.67 | 0.000 | 17504.50 | 34.99 | 0.00569921 | 15.74 | 0.00000000 | 0.0000 | 21.11 | 0.00857732 | 21.11 | 0.00857732 | 45.2561 | 14292.90 | 0.00 | 21366.92 | 19838.47 | 1.68506000 | 22.79 | 16.02 | 0.00857732 | 44710.3 | 11.25 | 11.16 | 0.00821764 | 32030.0 | |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9023.848 | 9023.848 | 0.473020 | 0.00007894 | 257.850 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.701378 | 1.68506000 | 4197.9300 | 999.8980 | 4.31608514 | 54.44 | 82.22 | 27.78 | 503335.35 | 1.7928 | 1.828891 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 9023.85 | 9023.85 | 1.0000 | 0.46848326 | 0.473020 | 21.11 | 12.69 | 0.00767482 | 40708.1 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.07893651 | 60.00 | 32.22 | 27.78 | 0.000 | 9023.85 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 21.11 | 0.00767482 | 21.11 | 0.00767482 | 40.5525 | 9024.02 | 0.00 | 9727.95 | 9727.95 | 0.46848326 | 16.60 | 12.83 | 0.00767482 | 36111.4 | 36.98 | 20.03 | 0.00767482 | 56876.2 | |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | BANQUET_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 18360.242 | 18360.242 | 2.761603 | 0.00016062 | 393.738 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.31608514 | 54.44 | 82.22 | 27.78 | 503335.35 | 3.6477 | 3.721127 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 18360.24 | 18360.24 | 1.0000 | 2.73511646 | 2.761603 | 16.70 | 11.36 | 0.00800000 | 37036.7 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.16060702 | 60.00 | 32.22 | 27.78 | 0.000 | 18360.24 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 21.00 | 0.00775091 | 21.00 | 0.00775091 | 41.2291 | 6373.41 | 0.00 | 18462.46 | 18462.46 | 2.73511646 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 23.22 | 15.67 | 0.00800000 | 43684.9 | |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | DINING_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 19076.215 | 19076.215 | 2.897101 | 0.00016689 | 408.770 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.31608514 | 54.44 | 82.22 | 27.78 | 503335.35 | 3.7900 | 3.866236 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 19:20:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 19:20:00 | Sensible | 19076.22 | 19076.22 | 1.0000 | 2.86931439 | 2.897101 | 16.70 | 11.36 | 0.00800000 | 37036.7 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.16687003 | 60.00 | 32.22 | 27.78 | 0.000 | 19076.22 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 21.00 | 0.00775563 | 21.00 | 0.00775563 | 41.2547 | 6502.08 | 0.00 | 19182.44 | 19182.44 | 2.86931439 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 23.16 | 15.65 | 0.00800000 | 43620.1 | |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | KITCHEN_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 13792.571 | 13792.571 | 2.796066 | 0.00012066 | 289.661 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.31608514 | 54.44 | 82.22 | 27.78 | 503335.35 | 2.7402 | 2.795383 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | Sensible | 13792.57 | 13792.57 | 1.0000 | 2.76924905 | 2.796066 | 16.70 | 11.36 | 0.00800000 | 37036.7 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.12065112 | 60.00 | 32.22 | 27.78 | 0.000 | 13792.57 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 20.42 | 0.00630261 | 21.00 | 0.00630261 | 33.6098 | 1698.11 | 0.00 | 13869.89 | 13869.89 | 2.76924905 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 21.51 | 15.04 | 0.00800000 | 41943.3 | |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | CORRIDOR_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10668.740 | 10668.740 | 0.903938 | 0.00009333 | 244.452 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.31608514 | 54.44 | 82.22 | 27.78 | 503335.35 | 2.1196 | 2.162267 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:50:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:50:00 | Sensible | 10668.74 | 10668.74 | 1.0000 | 0.89526872 | 0.903938 | 16.70 | 11.36 | 0.00800000 | 37036.7 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.09332527 | 60.00 | 32.22 | 27.78 | 0.000 | 10668.74 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 21.00 | 0.00779218 | 21.00 | 0.00779218 | 41.4459 | 6744.85 | 0.00 | 10726.03 | 10726.03 | 0.89526872 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 28.35 | 17.48 | 0.00800000 | 48915.5 | |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 655657.863 | -999.000 | 26.579661 | 0.02341858 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1015.4349 | 1004.8586 | 0.9904 | VAV WITH REHEAT FAN | Fan:VariableVolume | 26.579661 | 26.32473290 | 4197.9300 | 999.8980 | 34.26796688 | 13.37 | 6.70 | 6.67 | 959509.69 | 68.3326 | 68.332594 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | Sensible | 655657.86 | 655657.86 | 1.0000 | 26.32473290 | 26.579661 | 35.10 | 15.77 | 0.00569938 | 49895.6 | 10.57 | 6.56 | 0.00569938 | 24989.0 | 23.41619077 | 6.70 | 13.37 | 6.67 | 59555.415 | 596102.45 | 35.10 | 0.00569938 | 15.77 | 26.56724000 | 99.9533 | 23.99 | 0.00961554 | 23.99 | 0.00961449 | 42.5143 | 300527.60 | 0.00 | 656275.91 | 656275.91 | 26.32473290 | 35.10 | 17.86 | 0.00569938 | 49895.6 | 10.55 | 8.10 | 0.00569938 | 24965.6 | |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 195220.439 | 195220.439 | 7.973898 | 0.00170787 | 3266.920 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | VAV WITH REHEAT FAN | Fan:VariableVolume | 26.579661 | 26.32473290 | 4197.9300 | 999.8980 | 4.31608514 | 54.44 | 82.22 | 27.78 | 503335.35 | 38.7854 | 39.565933 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 195220.44 | 195220.44 | 1.0000 | 7.89741987 | 7.973898 | -7.90 | -7.90 | 0.00234317 | -2112.5 | 16.70 | 11.36 | 0.00800000 | 37036.7 | 1.70769934 | 60.00 | 32.22 | 27.78 | 0.000 | 195220.44 | -7.90 | 0.00234317 | -7.90 | 26.56724000 | 333.1776 | 18.58 | 0.00699018 | 21.57 | 0.00603739 | 31.0949 | 61818.88 | 0.00 | 172431.12 | 172431.12 | 7.89741987 | 2.80 | -0.65 | 0.00234317 | 8685.9 | 24.43 | 10.64 | 0.00234317 | 30519.7 | |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 48199.928 | -999.000 | 2.051317 | 0.00172159 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1015.4349 | 1004.8586 | 0.9904 | FLR_3_DOAS FAN | Fan:ConstantVolume | 2.051245 | 2.03157141 | 4197.9300 | 999.8980 | 34.26796688 | 13.37 | 6.70 | 6.67 | 959509.69 | 5.0234 | 5.023391 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | Sensible | 48199.93 | 48199.93 | 1.0000 | 2.03164284 | 2.051317 | 35.10 | 15.77 | 0.00569938 | 49895.6 | 11.74 | 7.07 | 0.00569938 | 26171.0 | 1.72141413 | 6.70 | 13.37 | 6.67 | 2195.006 | 46004.92 | 35.10 | 0.00569938 | 15.77 | 2.05124512 | 99.9965 | 21.11 | 0.00855621 | 21.11 | 0.00856398 | 45.1861 | 197890.13 | 0.00 | 48236.96 | 48236.96 | 2.03164284 | 35.10 | 17.86 | 0.00569938 | 49895.6 | 11.72 | 8.65 | 0.00569938 | 26152.7 | |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 15066.372 | 15066.372 | 0.615395 | 0.00013181 | 252.128 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | FLR_3_DOAS FAN | Fan:ConstantVolume | 2.051245 | 2.03157141 | 4197.9300 | 999.8980 | 4.31608514 | 54.44 | 82.22 | 27.78 | 503335.35 | 2.9933 | 3.053548 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 15066.37 | 15066.37 | 1.0000 | 0.60949285 | 0.615395 | -7.90 | -7.90 | 0.00234317 | -2112.5 | 16.70 | 11.36 | 0.00800000 | 37036.7 | 0.13179374 | 60.00 | 32.22 | 27.78 | 0.000 | 15066.37 | -7.90 | 0.00234317 | -7.90 | 2.05124512 | 333.3216 | 21.11 | 0.00761181 | 21.11 | 0.00761203 | 40.2243 | 105423.66 | 0.00 | 13307.58 | 13307.58 | 0.60949285 | 2.80 | -0.65 | 0.00234317 | 8685.9 | 24.43 | 10.64 | 0.00234317 | 30519.7 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:57:58
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
VAV WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 26.57 | 26.58 | - | |||
FLR_3_DOAS_OA_CONTROLLER | DifferentialDryBulb | 2.05 | 2.05 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
BASEMENT | VAV WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
RETAIL_1_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
RETAIL_2_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
MECH_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
STORAGE_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000610 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
LAUNDRY_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CAFE_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
LOBBY_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001448 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORRIDOR_FLR_3 | VAV WITH REHEAT_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
BANQUET_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
DINING_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
KITCHEN_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003556 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORRIDOR_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 350.17 | 8760.00 | 350.17 |
RETAIL_1_FLR_1 | 1431.50 | 8139.83 | 1168.00 |
RETAIL_2_FLR_1 | 116.83 | 8760.00 | 116.83 |
MECH_FLR_1 | 1717.33 | 8760.00 | 1717.33 |
STORAGE_FLR_1 | 2732.00 | 8760.00 | 2732.00 |
LAUNDRY_FLR_1 | 3146.50 | 4892.83 | 1049.50 |
CAFE_FLR_1 | 662.33 | 8073.00 | 368.00 |
LOBBY_FLR_1 | 276.33 | 8760.00 | 276.33 |
ROOM_1_FLR_3 | 1384.17 | 8051.67 | 1146.50 |
ROOM_2_FLR_3 | 2360.17 | 8262.00 | 2206.33 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 1424.83 | 8759.00 | 1424.83 |
ROOM_5_FLR_3 | 1437.33 | 7935.33 | 1141.33 |
ROOM_6_FLR_3 | 2244.00 | 8059.17 | 2129.17 |
CORRIDOR_FLR_3 | 993.83 | 8760.00 | 993.83 |
ROOM_1_FLR_6 | 2181.33 | 7805.17 | 1728.33 |
ROOM_2_FLR_6 | 2992.83 | 8027.67 | 2671.83 |
ROOM_3_MULT9_FLR_6 | 1015.33 | 7593.17 | 646.00 |
BANQUET_FLR_6 | 431.33 | 8532.00 | 366.83 |
DINING_FLR_6 | 499.67 | 8318.33 | 352.50 |
KITCHEN_FLR_6 | 6678.00 | 6912.33 | 5264.83 |
CORRIDOR_FLR_6 | 1715.50 | 8760.00 | 1715.50 |
Facility | 7915.67 | 8760.00 | 7364.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 1.17 | 0.00 | 1.17 |
ROOM_2_FLR_3 | 0.00 | 1.00 | 0.00 | 1.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.17 | 0.83 | 0.17 | 0.83 |
ROOM_5_FLR_3 | 0.00 | 0.17 | 0.00 | 0.17 |
ROOM_6_FLR_3 | 0.00 | 0.67 | 0.00 | 0.67 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 8.50 | 0.00 | 8.50 |
ROOM_2_FLR_6 | 0.00 | 3.67 | 0.00 | 3.67 |
ROOM_3_MULT9_FLR_6 | 0.00 | 7.67 | 0.00 | 7.67 |
BANQUET_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.50 | 0.00 | 0.50 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 0.17 | 14.67 | 0.17 | 14.67 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:57:58
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.79 | 106.50 | 4826.41 | 2.274 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.28 | 10.83 | 265.76 | 5.977 | 0.136 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.28 | 12.54 | 307.76 | 3.420 | 0.045 | 0.000 | 0.000 |
MECH_FLR_1 | 1.54 | 2.65 | 650.80 | 1.637 | 0.051 | 0.000 | 0.000 |
STORAGE_FLR_1 | 1.18 | 2.04 | 375.47 | 1.414 | 0.051 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.87 | 8.40 | 309.22 | 46.234 | 0.146 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.56 | 142.30 | 748.35 | 8.943 | 0.107 | 0.000 | 0.000 |
LOBBY_FLR_1 | 245.09 | 422.44 | 5183.56 | 4.038 | 0.044 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.471 | 0.177 | 0.000 | 0.058 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.470 | 0.177 | 0.000 | 0.056 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.534 | 0.079 | 0.000 | 0.088 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.471 | 0.177 | 0.000 | 0.058 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.471 | 0.177 | 0.000 | 0.056 |
CORRIDOR_FLR_3 | 12.16 | 20.96 | 1186.91 | 1.097 | 0.021 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.471 | 0.177 | 0.000 | 0.069 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.470 | 0.177 | 0.000 | 0.067 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.535 | 0.144 | 0.000 | 0.110 |
BANQUET_FLR_6 | 144.99 | 249.90 | 1010.89 | 9.905 | 0.051 | 0.000 | 0.000 |
DINING_FLR_6 | 144.99 | 249.90 | 1010.89 | 10.392 | 0.051 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.90 | 22.24 | 314.87 | 32.405 | 0.147 | 0.000 | 0.000 |
CORRIDOR_FLR_6 | 12.87 | 22.18 | 1256.16 | 2.603 | 0.036 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.79 | 106.50 | 4826.41 | 2.218 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.28 | 10.83 | 265.76 | 5.834 | 0.003 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.28 | 12.54 | 307.76 | 3.336 | 0.001 | 0.000 | 0.000 |
MECH_FLR_1 | 1.54 | 2.65 | 650.80 | 1.598 | 0.001 | 0.000 | 0.000 |
STORAGE_FLR_1 | 1.18 | 2.04 | 375.47 | 1.380 | 0.001 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.87 | 8.40 | 309.22 | 45.060 | 0.003 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.56 | 142.30 | 748.35 | 8.724 | 0.002 | 0.000 | 0.000 |
LOBBY_FLR_1 | 245.09 | 422.44 | 5183.56 | 3.937 | 0.001 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.459 | 0.003 | 0.000 | 0.000 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.456 | 0.003 | 0.000 | 0.000 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.519 | 0.002 | 0.000 | 0.000 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.459 | 0.003 | 0.000 | 0.000 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.457 | 0.003 | 0.000 | 0.000 |
CORRIDOR_FLR_3 | 12.16 | 20.96 | 1186.91 | 1.069 | 0.000 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.458 | 0.003 | 0.000 | 0.000 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.456 | 0.003 | 0.000 | 0.000 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.521 | 0.003 | 0.000 | 0.000 |
BANQUET_FLR_6 | 144.99 | 249.90 | 1010.89 | 9.641 | 0.001 | 0.000 | 0.000 |
DINING_FLR_6 | 144.99 | 249.90 | 1010.89 | 10.114 | 0.001 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.90 | 22.24 | 314.87 | 31.496 | 0.003 | 0.000 | 0.000 |
CORRIDOR_FLR_6 | 12.87 | 22.18 | 1256.16 | 2.539 | 0.001 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:57:58
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | VAV WITH REHEAT | 61.79 | 106.50 | 4826.41 | 1978.83 | 0.0000 | 0.854 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | 6.28 | 10.83 | 265.76 | 67.07 | 0.0000 | 0.079 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | 7.28 | 12.54 | 307.76 | 77.67 | 0.0000 | 0.092 |
MECH_FLR_1 | VAV WITH REHEAT | 1.54 | 2.65 | 650.80 | 164.24 | 0.0000 | 0.000 |
STORAGE_FLR_1 | VAV WITH REHEAT | 1.18 | 2.04 | 375.47 | 94.76 | 0.0000 | 0.058 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | 4.87 | 8.40 | 309.22 | 78.04 | 0.0000 | 0.000 |
CAFE_FLR_1 | VAV WITH REHEAT | 82.56 | 142.30 | 748.35 | 188.86 | 0.0000 | 0.676 |
LOBBY_FLR_1 | VAV WITH REHEAT | 245.09 | 422.44 | 5183.56 | 1308.19 | 0.0000 | 1.894 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.062 |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.062 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 1.50 | 74.75 | 24.52 | 0.0000 | 0.837 | |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 74.77 | 24.53 | 0.0000 | 0.837 |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.062 |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.062 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | 12.16 | 20.96 | 1186.91 | 389.40 | 0.0000 | 0.475 |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.015 |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.015 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 74.77 | 24.53 | 0.0000 | 0.099 |
BANQUET_FLR_6 | VAV WITH REHEAT | 144.99 | 249.90 | 1010.89 | 331.66 | 0.0000 | 1.188 |
DINING_FLR_6 | VAV WITH REHEAT | 144.99 | 249.90 | 1010.89 | 331.66 | 0.0000 | 1.188 |
KITCHEN_FLR_6 | VAV WITH REHEAT | 12.90 | 22.24 | 314.87 | 103.30 | 0.0000 | 0.367 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | 12.87 | 22.18 | 1256.16 | 412.12 | 0.0000 | 0.126 |
Total Facility | 873.25 | 1604.23 | 35184.81 | 11345.29 | 0.0000 | 137.584 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 95616087.71 | 0.00 | 95616087.71 | 0.00 | 95616087.71 | 26946214.98 | 0.00 | 0.00 | 8760.00 | 0.00 |
RETAIL_1_FLR_1 | 13835618.20 | 0.00 | 13835618.20 | 315975.89 | 14151594.09 | 2498216.28 | 0.00 | 0.00 | 8760.00 | 0.00 |
RETAIL_2_FLR_1 | 9171349.75 | 0.00 | 9171349.75 | 121967.09 | 9293316.84 | 2892943.94 | 0.00 | 0.00 | 8760.00 | 0.00 |
MECH_FLR_1 | 9290550.03 | 0.00 | 9290550.03 | 288257.75 | 9578807.78 | 0.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
STORAGE_FLR_1 | 4629628.53 | 0.00 | 4629628.53 | 166308.84 | 4795937.38 | 1821682.01 | 0.00 | 0.00 | 8760.00 | 0.00 |
LAUNDRY_FLR_1 | 0.12E+09 | 0.00 | 0.12E+09 | 393601.23 | 0.12E+09 | 0.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
CAFE_FLR_1 | 58244987.70 | 0.00 | 58244987.70 | 698482.59 | 58943470.29 | 21330615.53 | 0.00 | 0.00 | 8760.00 | 0.00 |
LOBBY_FLR_1 | 0.18E+09 | 0.00 | 0.18E+09 | 1995724.30 | 0.18E+09 | 59728886.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
ROOM_1_FLR_3 | 1946875.62 | 59663.27 | 2006538.89 | 183401.85 | 2189940.74 | 1946875.62 | 0.00 | 7918.33 | 841.67 | 0.00 |
ROOM_2_FLR_3 | 1946647.51 | 57698.37 | 2004345.88 | 183387.86 | 2187733.74 | 1946647.51 | 0.00 | 7918.33 | 841.67 | 0.00 |
ROOM_3_MULT19_FLR_3 | 26397887.27 | 64470.25 | 26462357.52 | 51171.17 | 26513528.69 | 26397887.27 | 0.00 | 7937.50 | 822.50 | 8760.00 |
ROOM_4_MULT19_FLR_3 | 26405105.73 | 57461.52 | 26462567.24 | 51185.17 | 26513752.41 | 26405105.73 | 0.00 | 7966.95 | 793.05 | 0.00 |
ROOM_5_FLR_3 | 1946875.62 | 59925.38 | 2006801.00 | 183401.85 | 2190202.85 | 1946875.62 | 0.00 | 7918.33 | 841.67 | 0.00 |
ROOM_6_FLR_3 | 1946647.51 | 57921.50 | 2004569.02 | 183387.86 | 2187956.87 | 1946647.51 | 0.00 | 7918.33 | 841.67 | 0.00 |
CORRIDOR_FLR_3 | 45346688.93 | 0.00 | 45346688.93 | 221769.73 | 45568458.67 | 14972100.18 | 0.00 | 0.00 | 8760.00 | 0.00 |
ROOM_1_FLR_6 | 486718.90 | 71697.49 | 558416.39 | 183439.96 | 741856.36 | 486718.90 | 0.00 | 7917.17 | 842.83 | 0.00 |
ROOM_2_FLR_6 | 486661.88 | 69160.37 | 555822.25 | 183425.97 | 739248.22 | 486661.88 | 0.00 | 7917.17 | 842.83 | 0.00 |
ROOM_3_MULT9_FLR_6 | 3126920.42 | 71679.98 | 3198600.40 | 93854.31 | 3292454.70 | 3126920.42 | 0.00 | 7917.17 | 842.83 | 0.00 |
BANQUET_FLR_6 | 87046125.18 | 0.00 | 87046125.18 | 447914.29 | 87494039.47 | 37458366.31 | 0.00 | 0.00 | 8760.00 | 0.00 |
DINING_FLR_6 | 91317025.44 | 0.00 | 91317025.44 | 447914.29 | 91764939.73 | 37458366.31 | 0.00 | 0.00 | 8760.00 | 0.00 |
KITCHEN_FLR_6 | 88241208.67 | 0.00 | 88241208.67 | 400987.13 | 88642195.81 | 11584760.86 | 0.00 | 0.00 | 8760.00 | 0.00 |
CORRIDOR_FLR_6 | 28492268.78 | 0.00 | 28492268.78 | 392463.83 | 28884732.61 | 3961413.96 | 0.00 | 0.00 | 8760.00 | 0.00 |
Total Facility | 0.50E+10 | 10993625.76 | 0.51E+10 | 18481630.20 | 0.51E+10 | 0.43E+10 | 0.00 | 7974.84 | 8760.00 | 8760.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 3.0320 | 0.0000 | 3.0320 | 0.0000 | 3.0320 | 0.8545 | 0.00 | 0.00 | 8760.00 |
RETAIL_1_FLR_1 | 0.4387 | 0.0000 | 0.4387 | 0.0100 | 0.4487 | 0.0792 | 0.00 | 0.00 | 8760.00 |
RETAIL_2_FLR_1 | 0.2908 | 0.0000 | 0.2908 | 0.0039 | 0.2947 | 0.0917 | 0.00 | 0.00 | 8760.00 |
MECH_FLR_1 | 0.2946 | 0.0000 | 0.2946 | 0.0091 | 0.3037 | 0.0000 | 0.00 | 0.00 | 8760.00 |
STORAGE_FLR_1 | 0.1468 | 0.0000 | 0.1468 | 0.0053 | 0.1521 | 0.0578 | 0.00 | 0.00 | 8760.00 |
LAUNDRY_FLR_1 | 3.9477 | 0.0000 | 3.9477 | 0.0125 | 3.9601 | 0.0000 | 0.00 | 0.00 | 8760.00 |
CAFE_FLR_1 | 1.8469 | 0.0000 | 1.8469 | 0.0221 | 1.8691 | 0.6764 | 0.00 | 0.00 | 8760.00 |
LOBBY_FLR_1 | 5.7778 | 0.0000 | 5.7778 | 0.0633 | 5.8411 | 1.8940 | 0.00 | 0.00 | 8760.00 |
ROOM_1_FLR_3 | 0.0617 | 0.0019 | 0.0636 | 0.0058 | 0.0694 | 0.0617 | 0.00 | 7918.33 | 841.67 |
ROOM_2_FLR_3 | 0.0617 | 0.0018 | 0.0636 | 0.0058 | 0.0694 | 0.0617 | 0.00 | 7918.33 | 841.67 |
ROOM_4_MULT19_FLR_3 | 0.8373 | 0.0018 | 0.8391 | 0.0016 | 0.8407 | 0.8373 | 0.00 | 7966.95 | 793.05 |
ROOM_5_FLR_3 | 0.0617 | 0.0019 | 0.0636 | 0.0058 | 0.0695 | 0.0617 | 0.00 | 7918.33 | 841.67 |
ROOM_6_FLR_3 | 0.0617 | 0.0018 | 0.0636 | 0.0058 | 0.0694 | 0.0617 | 0.00 | 7918.33 | 841.67 |
CORRIDOR_FLR_3 | 1.4379 | 0.0000 | 1.4379 | 0.0070 | 1.4450 | 0.4748 | 0.00 | 0.00 | 8760.00 |
ROOM_1_FLR_6 | 0.0154 | 0.0023 | 0.0177 | 0.0058 | 0.0235 | 0.0154 | 0.00 | 7917.17 | 842.83 |
ROOM_2_FLR_6 | 0.0154 | 0.0022 | 0.0176 | 0.0058 | 0.0234 | 0.0154 | 0.00 | 7917.17 | 842.83 |
ROOM_3_MULT9_FLR_6 | 0.0992 | 0.0023 | 0.1014 | 0.0030 | 0.1044 | 0.0992 | 0.00 | 7917.17 | 842.83 |
BANQUET_FLR_6 | 2.7602 | 0.0000 | 2.7602 | 0.0142 | 2.7744 | 1.1878 | 0.00 | 0.00 | 8760.00 |
DINING_FLR_6 | 2.8956 | 0.0000 | 2.8956 | 0.0142 | 2.9098 | 1.1878 | 0.00 | 0.00 | 8760.00 |
KITCHEN_FLR_6 | 2.7981 | 0.0000 | 2.7981 | 0.0127 | 2.8108 | 0.3674 | 0.00 | 0.00 | 8760.00 |
CORRIDOR_FLR_6 | 0.9035 | 0.0000 | 0.9035 | 0.0124 | 0.9159 | 0.1256 | 0.00 | 0.00 | 8760.00 |
Total Facility | 96.4303 | 0.1932 | 96.6235 | 0.4627 | 97.0862 | 73.9670 | 0.00 | 7974.84 | 8760.00 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV WITH REHEAT | 0.82E+09 | 0.00 | 0.82E+09 | 0.22E+09 | 0.00 | 0.00 | 8760.00 | 0.00 |
FLR_3_DOAS | 63455387.45 | 569678.14 | 64025065.58 | 64690340.46 | 7915.75 | 15.60 | 828.65 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV WITH REHEAT | 26.0634 | 0.0000 | 26.0634 | 6.9969 | 0.00 | 0.00 | 8760.00 |
FLR_3_DOAS | 2.0122 | 0.0181 | 2.0302 | 2.0513 | 7915.75 | 15.60 | 828.65 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV WITH REHEAT | 0.00 | 8138.00 | 618.33 | 0.00 | 3.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FLR_3_DOAS | 0.00 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV WITH REHEAT | 0.0000 | 26.0628 | 26.0860 | 0.0000 | 31.8452 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
FLR_3_DOAS | 0.0000 | 2.0122 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:57:58
Surfaces by ClassTotal | Outdoors | |
Wall | 119 | 44 |
Floor | 25 | 0 |
Roof | 33 | 11 |
Internal Mass | 22 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 30 | 30 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 22 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 1304 |
Defaulted Fields | 1181 |
Fields with Defaults | 3925 |
Autosized Fields | 349 |
Autosizable Fields | 401 |
Autocalculated Fields | 280 |
Autocalculatable Fields | 539 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:57:58
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 8517.80 | 145226.72 | 11-APR-01:50 | 552594.89 | 20-JUL-18:10 |
Electricity:Building | 2943.68 | 36656.90 | 02-JAN-02:10 | 182730.36 | 02-JAN-20:10 |
Electricity:Zone:BASEMENT | 315.54 | 3631.19 | 02-JAN-02:10 | 23630.80 | 02-JAN-20:10 |
Electricity:SpaceType:GENERAL | 2925.41 | 36182.64 | 02-JAN-02:10 | 182063.43 | 02-JAN-20:10 |
InteriorLights:Electricity | 1174.11 | 10291.59 | 02-JAN-02:10 | 93091.76 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BASEMENT | 165.29 | 1501.97 | 02-JAN-02:10 | 13517.00 | 02-JAN-20:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 1174.11 | 10291.59 | 02-JAN-02:10 | 93091.76 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity | 1174.11 | 10291.59 | 02-JAN-02:10 | 93091.76 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 165.29 | 1501.97 | 02-JAN-02:10 | 13517.00 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 1174.11 | 10291.59 | 02-JAN-02:10 | 93091.76 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_1_FLR_1 | 18.59 | 220.70 | 02-JAN-02:10 | 1372.90 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 8.40 | 76.37 | 02-JAN-02:10 | 687.30 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 8.40 | 76.37 | 02-JAN-02:10 | 687.30 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_2_FLR_1 | 21.53 | 255.58 | 02-JAN-02:10 | 1589.82 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 9.73 | 88.43 | 02-JAN-02:10 | 795.89 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 9.73 | 88.43 | 02-JAN-02:10 | 795.89 | 02-JAN-20:10 |
Electricity:Zone:MECH_FLR_1 | 30.66 | 342.02 | 02-JAN-02:10 | 2327.13 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:MECH_FLR_1 | 18.19 | 165.30 | 02-JAN-02:10 | 1487.69 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:MECH_FLR_1 | 18.19 | 165.30 | 02-JAN-02:10 | 1487.69 | 02-JAN-20:10 |
Electricity:Zone:STORAGE_FLR_1 | 6.94 | 81.32 | 02-JAN-02:10 | 515.26 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 3.34 | 30.34 | 02-JAN-02:10 | 273.10 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 3.34 | 30.34 | 02-JAN-02:10 | 273.10 | 02-JAN-20:10 |
Electricity:Zone:LAUNDRY_FLR_1 | 72.06 | 1000.18 | 02-JAN-02:10 | 4910.17 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 4.13 | 37.49 | 02-JAN-02:10 | 337.37 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 4.13 | 37.49 | 02-JAN-02:10 | 337.37 | 02-JAN-20:10 |
Electricity:Zone:CAFE_FLR_1 | 40.96 | 445.13 | 02-JAN-02:10 | 3142.50 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CAFE_FLR_1 | 26.62 | 241.91 | 02-JAN-02:10 | 2177.23 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CAFE_FLR_1 | 26.62 | 241.91 | 02-JAN-02:10 | 2177.23 | 02-JAN-20:10 |
Electricity:Zone:LOBBY_FLR_1 | 293.89 | 3428.00 | 02-JAN-02:10 | 21878.53 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 144.90 | 1316.59 | 02-JAN-02:10 | 11849.32 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 144.90 | 1316.59 | 02-JAN-02:10 | 11849.32 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_3 | 32.70 | 383.52 | 01-JAN-02:10 | 2308.42 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 20.41 | 172.80 | 01-JAN-02:10 | 1570.91 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 20.41 | 172.80 | 01-JAN-02:10 | 1570.91 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_3 | 32.70 | 383.47 | 01-JAN-02:10 | 2308.15 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 20.41 | 172.78 | 01-JAN-02:10 | 1570.72 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 20.41 | 172.78 | 01-JAN-02:10 | 1570.72 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT19_FLR_3 | 472.46 | 5984.83 | 01-JAN-02:10 | 32482.97 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 243.71 | 2063.36 | 01-JAN-02:10 | 18757.86 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 243.71 | 2063.36 | 01-JAN-02:10 | 18757.86 | 01-JAN-19:10 |
Electricity:Zone:ROOM_4_MULT19_FLR_3 | 472.59 | 5986.46 | 01-JAN-02:10 | 32491.86 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 243.77 | 2063.93 | 01-JAN-02:10 | 18762.99 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 243.77 | 2063.93 | 01-JAN-02:10 | 18762.99 | 01-JAN-19:10 |
Electricity:Zone:ROOM_5_FLR_3 | 32.70 | 383.52 | 01-JAN-02:10 | 2308.42 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 20.41 | 172.80 | 01-JAN-02:10 | 1570.91 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 20.41 | 172.80 | 01-JAN-02:10 | 1570.91 | 01-JAN-19:10 |
Electricity:Zone:ROOM_6_FLR_3 | 32.70 | 383.47 | 01-JAN-02:10 | 2308.15 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 20.41 | 172.78 | 01-JAN-02:10 | 1570.72 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 20.41 | 172.78 | 01-JAN-02:10 | 1570.72 | 01-JAN-19:10 |
Electricity:Zone:CORRIDOR_FLR_3 | 62.74 | 570.05 | 02-JAN-02:10 | 5130.41 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 62.74 | 570.05 | 02-JAN-02:10 | 5130.41 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 62.74 | 570.05 | 02-JAN-02:10 | 5130.41 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_6 | 8.18 | 95.88 | 01-JAN-02:10 | 577.11 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 5.10 | 43.20 | 01-JAN-02:10 | 392.73 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 5.10 | 43.20 | 01-JAN-02:10 | 392.73 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_6 | 8.17 | 95.87 | 01-JAN-02:10 | 577.04 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 5.10 | 43.19 | 01-JAN-02:10 | 392.68 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 5.10 | 43.19 | 01-JAN-02:10 | 392.68 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT9_FLR_6 | 55.96 | 708.92 | 01-JAN-02:10 | 3847.72 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 28.87 | 244.41 | 01-JAN-02:10 | 2221.93 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 28.87 | 244.41 | 01-JAN-02:10 | 2221.93 | 01-JAN-19:10 |
Electricity:Zone:BANQUET_FLR_6 | 222.61 | 2674.12 | 02-JAN-02:10 | 10571.30 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 46.75 | 424.82 | 02-JAN-02:10 | 3823.39 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 46.75 | 424.82 | 02-JAN-02:10 | 3823.39 | 02-JAN-20:10 |
Electricity:Zone:DINING_FLR_6 | 222.61 | 2674.12 | 02-JAN-02:10 | 10571.30 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:DINING_FLR_6 | 46.75 | 424.82 | 02-JAN-02:10 | 3823.39 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:DINING_FLR_6 | 46.75 | 424.82 | 02-JAN-02:10 | 3823.39 | 02-JAN-20:10 |
Electricity:Zone:KITCHEN_FLR_6 | 470.78 | 6777.71 | 02-JAN-02:10 | 19298.76 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 12.48 | 113.42 | 02-JAN-02:10 | 1020.78 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 12.48 | 113.42 | 02-JAN-02:10 | 1020.78 | 02-JAN-20:10 |
Electricity:Zone:CORRIDOR_FLR_6 | 16.60 | 150.83 | 02-JAN-02:10 | 1357.44 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 16.60 | 150.83 | 02-JAN-02:10 | 1357.44 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 16.60 | 150.83 | 02-JAN-02:10 | 1357.44 | 02-JAN-20:10 |
InteriorEquipment:Electricity | 1751.30 | 25891.05 | 02-JAN-02:10 | 89674.66 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 150.26 | 2129.22 | 02-JAN-02:10 | 10113.80 | 02-JAN-20:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 1751.30 | 25891.05 | 02-JAN-02:10 | 89674.66 | 02-JAN-07:10 |
MiscPlug:InteriorEquipment:Electricity | 959.56 | 15202.41 | 02-JAN-02:10 | 59492.27 | 02-JAN-07:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 150.26 | 2129.22 | 02-JAN-02:10 | 10113.80 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 959.56 | 15202.41 | 02-JAN-02:10 | 59492.27 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.79 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.79 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 12.29 | 210.72 | 01-JAN-00:10 | 948.23 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 12.29 | 210.72 | 01-JAN-00:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 12.29 | 210.69 | 01-JAN-00:10 | 948.12 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 12.29 | 210.69 | 01-JAN-00:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 228.75 | 3921.46 | 01-JAN-00:10 | 17646.57 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 228.75 | 3921.46 | 01-JAN-00:10 | 17646.57 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 228.82 | 3922.53 | 01-JAN-00:10 | 17651.40 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 228.82 | 3922.53 | 01-JAN-00:10 | 17651.40 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 12.29 | 210.72 | 01-JAN-00:10 | 948.23 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 12.29 | 210.72 | 01-JAN-00:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 12.29 | 210.69 | 01-JAN-00:10 | 948.12 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 12.29 | 210.69 | 01-JAN-00:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 3.07 | 52.68 | 01-JAN-00:10 | 237.06 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 3.07 | 52.68 | 01-JAN-00:10 | 237.06 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 3.07 | 52.67 | 01-JAN-00:10 | 237.03 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 3.07 | 52.67 | 01-JAN-00:10 | 237.03 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 27.10 | 464.51 | 01-JAN-00:10 | 2090.30 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 27.10 | 464.51 | 01-JAN-00:10 | 2090.30 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 440.03 | 6190.03 | 01-JAN-00:10 | 16686.59 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 410.33 | 5248.28 | 01-JAN-00:10 | 15744.84 | 01-JAN-07:10 |
ReachInFreezer:InteriorEquipment:Electricity | 16.27 | 515.92 | 01-JAN-00:10 | 515.92 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 16.27 | 515.92 | 01-JAN-00:10 | 515.92 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 16.27 | 515.92 | 01-JAN-00:10 | 515.92 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 13.43 | 425.83 | 01-JAN-00:10 | 425.83 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 13.43 | 425.83 | 01-JAN-00:10 | 425.83 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 13.43 | 425.83 | 01-JAN-00:10 | 425.83 | 01-JAN-00:10 |
Refrigeration:Electricity | 73.88 | 1234.09 | 05-FEB-23:30 | 3636.50 | 11-AUG-07:00 |
Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 18.27 | 261.51 | 02-JAN-11:30 | 2271.91 | 01-JAN-11:10 |
General:Refrigeration:Electricity | 18.27 | 261.51 | 02-JAN-11:30 | 2271.91 | 01-JAN-11:10 |
General:Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 18.27 | 261.51 | 02-JAN-11:30 | 2271.91 | 01-JAN-11:10 |
Electricity:Plant | 2025.42 | 2889.91 | 10-MAR-01:10 | 265031.70 | 28-JUN-15:20 |
LowTempRefrigeration:Refrigeration:Electricity | 22.38 | 0.00 | 01-JAN-11:10 | 1920.86 | 28-JUN-10:50 |
MedTempRefrigeration:Refrigeration:Electricity | 33.23 | 935.74 | 02-MAR-03:30 | 1195.09 | 01-JUL-13:40 |
Fans:Electricity | 2171.14 | 62792.48 | 13-MAR-00:20 | 93468.95 | 22-JUL-15:20 |
Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Electricity:HVAC | 2639.69 | 64284.50 | 28-MAR-10:10 | 113505.86 | 22-JUL-15:20 |
ExteriorEquipment:Electricity | 679.68 | 10574.27 | 02-JAN-02:20 | 40537.60 | 02-JAN-07:20 |
Transformer:ExteriorEquipment:Electricity | 32.92 | 556.27 | 02-JAN-02:20 | 1912.91 | 02-JAN-21:10 |
ElectricityPurchased:Facility | 8517.80 | 145226.72 | 11-APR-01:50 | 552594.89 | 20-JUL-18:10 |
ElectricityPurchased:Plant | 8517.80 | 145226.72 | 11-APR-01:50 | 552594.89 | 20-JUL-18:10 |
Cogeneration:ElectricityPurchased | 8517.80 | 145226.72 | 11-APR-01:50 | 552594.89 | 20-JUL-18:10 |
General:Cogeneration:ElectricityPurchased | 8517.80 | 145226.72 | 11-APR-01:50 | 552594.89 | 20-JUL-18:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 8517.80 | 145226.72 | 11-APR-01:50 | 552594.89 | 20-JUL-18:10 |
ElectricityNet:Plant | 8517.80 | 145226.72 | 11-APR-01:50 | 552594.89 | 20-JUL-18:10 |
Cogeneration:ElectricityNet | 8517.80 | 145226.72 | 11-APR-01:50 | 552594.89 | 20-JUL-18:10 |
General:Cogeneration:ElectricityNet | 8517.80 | 145226.72 | 11-APR-01:50 | 552594.89 | 20-JUL-18:10 |
General:Fans:Electricity | 2171.14 | 62792.48 | 13-MAR-00:20 | 93468.95 | 22-JUL-15:20 |
ExteriorLights:Electricity | 262.25 | 0.00 | 01-JAN-07:20 | 16690.39 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 262.25 | 0.00 | 01-JAN-07:20 | 16690.39 | 01-JAN-00:10 |
ElevatorLift:ExteriorEquipment:Electricity | 616.11 | 9046.01 | 01-JAN-00:10 | 37691.69 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 30.65 | 972.00 | 01-JAN-00:10 | 972.00 | 01-JAN-00:10 |
HeatRecovery:Electricity | 435.63 | 0.00 | 01-JAN-13:00 | 19111.97 | 01-JAN-11:20 |
General:HeatRecovery:Electricity | 435.63 | 0.00 | 01-JAN-13:00 | 19111.97 | 01-JAN-11:20 |
WaterSystems:Electricity | 90.78 | 1087.03 | 15-JUN-00:20 | 4739.92 | 28-DEC-07:20 |
Water Heater:WaterSystems:Electricity | 90.78 | 1087.03 | 15-JUN-00:20 | 4739.92 | 28-DEC-07:20 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 1656.65 | 0.00 | 01-JAN-01:50 | 250573.12 | 28-JUN-15:20 |
General:Cooling:Electricity | 1656.65 | 0.00 | 01-JAN-01:50 | 250573.12 | 28-JUN-15:20 |
Pumps:Electricity | 222.39 | 269.29 | 21-JAN-18:20 | 12220.85 | 23-JUL-15:30 |
General:Pumps:Electricity | 222.39 | 269.29 | 21-JAN-18:20 | 12220.85 | 23-JUL-15:30 |
WIRED_LTG_ELECTRICITY | 41.33 | 0.00 | 01-JAN-00:10 | 3276.83 | 02-JAN-20:20 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 6300.43 | 42179.81 | 21-AUG-23:10 | 496102.76 | 16-JAN-18:00 |
NaturalGas:Building | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
NaturalGas:SpaceType:GENERAL | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:NaturalGas | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
InteriorEquipment:NaturalGas:SpaceType:GENERAL | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
Laundry:InteriorEquipment:NaturalGas | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
NaturalGas:Plant | 4511.59 | 20468.97 | 22-JUL-23:20 | 424036.12 | 18-JAN-23:50 |
WaterSystems:NaturalGas | 3126.84 | 18467.44 | 06-JAN-00:10 | 287399.46 | 08-FEB-21:40 |
Water Heater:WaterSystems:NaturalGas | 3126.84 | 18467.44 | 06-JAN-00:10 | 287399.46 | 08-FEB-21:40 |
Heating:NaturalGas | 1384.76 | 0.00 | 13-APR-21:10 | 236891.60 | 21-JAN-07:10 |
Boiler:Heating:NaturalGas | 1384.76 | 0.00 | 13-APR-21:10 | 236891.60 | 21-JAN-07:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 5035.22 | 0.00 | 01-JAN-01:50 | 760786.00 | 31-JUL-18:10 |
PlantLoopCoolingDemand:HVAC | 5035.22 | 0.00 | 01-JAN-01:50 | 760786.00 | 31-JUL-18:10 |
CoolingCoils:PlantLoopCoolingDemand | 5035.22 | 0.00 | 01-JAN-01:50 | 760786.00 | 31-JUL-18:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-21:10 |
Water:Plant | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-21:10 |
WaterSystems:Water | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-21:10 |
Water Heater:WaterSystems:Water | 5742.51 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-19:20 |
MainsWater:Facility | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-21:10 |
MainsWater:Plant | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-21:10 |
WaterSystems:MainsWater | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-21:10 |
Water Heater:WaterSystems:MainsWater | 5742.51 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-19:20 |
WaterUse:WaterSystems:Water | 4114.69 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-07:10 |
WaterUse:WaterSystems:MainsWater | 4114.69 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-07:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 30674.14 | 263705.73 | 10-NOV-15:00 | 2869272.94 | 31-JUL-18:10 |
EnergyTransfer:Building | 6461.67 | 94953.99 | 25-DEC-14:30 | 410299.36 | 20-JUL-18:10 |
EnergyTransfer:Zone:KITCHEN_FLR_6 | 755.58 | 11243.79 | 15-DEC-04:00 | 37000.62 | 23-JUL-10:40 |
Refrigeration:EnergyTransfer | 184.44 | 3663.26 | 05-FEB-23:30 | 10343.49 | 11-AUG-06:50 |
Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 92.22 | 1831.63 | 05-FEB-23:30 | 5171.74 | 11-AUG-06:50 |
General:Refrigeration:EnergyTransfer | 92.22 | 1831.63 | 05-FEB-23:30 | 5171.74 | 11-AUG-06:50 |
General:Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 92.22 | 1831.63 | 05-FEB-23:30 | 5171.74 | 11-AUG-06:50 |
EnergyTransfer:Plant | 13851.83 | 51821.76 | 04-JAN-23:10 | 1763467.41 | 31-JUL-18:10 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 25.65 | 0.00 | 01-JAN-11:10 | 2686.44 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 66.57 | 1757.21 | 02-MAR-03:30 | 2535.27 | 01-JUL-13:40 |
EnergyTransfer:Zone:BASEMENT | 472.05 | 7504.92 | 20-MAR-11:00 | 22525.90 | 17-AUG-18:30 |
Heating:EnergyTransfer | 57.34 | 0.00 | 01-JAN-08:50 | 53425.98 | 21-DEC-16:10 |
Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer | 57.34 | 0.00 | 01-JAN-08:50 | 53425.98 | 21-DEC-16:10 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer | 6312.11 | 80828.72 | 19-JAN-10:20 | 406643.45 | 20-JUL-18:10 |
Cooling:EnergyTransfer:Zone:BASEMENT | 472.05 | 7504.92 | 20-MAR-11:00 | 22525.90 | 17-AUG-18:30 |
General:Cooling:EnergyTransfer | 6312.11 | 80828.72 | 19-JAN-10:20 | 406643.45 | 20-JUL-18:10 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 472.05 | 7504.92 | 20-MAR-11:00 | 22525.90 | 17-AUG-18:30 |
EnergyTransfer:Zone:RETAIL_1_FLR_1 | 55.12 | 0.04 | 05-JAN-04:10 | 4214.01 | 14-FEB-13:30 |
Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 0.36 | 0.00 | 01-JAN-00:10 | 750.11 | 09-DEC-07:30 |
General:Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 0.36 | 0.00 | 01-JAN-00:10 | 750.11 | 09-DEC-07:30 |
Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 54.76 | 0.00 | 02-JAN-07:10 | 4214.01 | 14-FEB-13:30 |
General:Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 54.76 | 0.00 | 02-JAN-07:10 | 4214.01 | 14-FEB-13:30 |
EnergyTransfer:Zone:RETAIL_2_FLR_1 | 43.20 | 313.87 | 19-JAN-11:40 | 2324.64 | 20-JUL-18:10 |
Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 43.20 | 313.87 | 19-JAN-11:40 | 2324.64 | 20-JUL-18:10 |
General:Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 43.20 | 313.87 | 19-JAN-11:40 | 2324.64 | 20-JUL-18:10 |
EnergyTransfer:Zone:MECH_FLR_1 | 30.74 | 0.01 | 12-JAN-04:30 | 2328.33 | 20-JUL-18:10 |
Heating:EnergyTransfer:Zone:MECH_FLR_1 | 0.08 | 0.00 | 01-JAN-00:10 | 277.19 | 15-DEC-05:00 |
General:Heating:EnergyTransfer:Zone:MECH_FLR_1 | 0.08 | 0.00 | 01-JAN-00:10 | 277.19 | 15-DEC-05:00 |
Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 30.66 | 0.00 | 07-JAN-03:10 | 2328.33 | 20-JUL-18:10 |
General:Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 30.66 | 0.00 | 07-JAN-03:10 | 2328.33 | 20-JUL-18:10 |
EnergyTransfer:Zone:STORAGE_FLR_1 | 12.68 | 0.02 | 03-JAN-09:00 | 1146.51 | 20-JUL-18:10 |
Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 0.41 | 0.00 | 01-JAN-00:10 | 282.66 | 15-DEC-05:00 |
General:Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 0.41 | 0.00 | 01-JAN-00:10 | 282.66 | 15-DEC-05:00 |
Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 12.27 | 0.00 | 01-JAN-03:00 | 1146.51 | 20-JUL-18:10 |
General:Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 12.27 | 0.00 | 01-JAN-03:00 | 1146.51 | 20-JUL-18:10 |
EnergyTransfer:Zone:LAUNDRY_FLR_1 | 605.88 | 8690.06 | 06-FEB-05:00 | 38014.37 | 28-JUN-20:00 |
Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 605.88 | 8690.06 | 06-FEB-05:00 | 38014.37 | 28-JUN-20:00 |
General:Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 605.88 | 8690.06 | 06-FEB-05:00 | 38014.37 | 28-JUN-20:00 |
EnergyTransfer:Zone:CAFE_FLR_1 | 310.31 | 1020.73 | 08-DEC-10:10 | 16485.48 | 19-NOV-11:40 |
Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 310.31 | 1020.73 | 08-DEC-10:10 | 16485.48 | 19-NOV-11:40 |
General:Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 310.31 | 1020.73 | 08-DEC-10:10 | 16485.48 | 19-NOV-11:40 |
EnergyTransfer:Zone:LOBBY_FLR_1 | 977.20 | 9120.35 | 19-JAN-11:30 | 46044.23 | 20-JUL-18:10 |
Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 977.20 | 9120.35 | 19-JAN-11:30 | 46044.23 | 20-JUL-18:10 |
General:Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 977.20 | 9120.35 | 19-JAN-11:30 | 46044.23 | 20-JUL-18:10 |
EnergyTransfer:Zone:ROOM_1_FLR_3 | 79.95 | 0.04 | 10-JAN-19:30 | 13831.43 | 21-JUL-18:10 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 5.94 | 0.00 | 01-JAN-08:10 | 4172.34 | 17-JAN-09:10 |
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 5.94 | 0.00 | 01-JAN-08:10 | 4172.34 | 17-JAN-09:10 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 74.01 | 0.00 | 01-JAN-00:10 | 13831.43 | 21-JUL-18:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 74.01 | 0.00 | 01-JAN-00:10 | 13831.43 | 21-JUL-18:10 |
EnergyTransfer:Zone:ROOM_2_FLR_3 | 70.18 | 0.01 | 21-FEB-20:30 | 14043.38 | 21-JUL-18:10 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 10.56 | 0.00 | 01-JAN-08:10 | 4613.53 | 15-DEC-09:10 |
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 10.56 | 0.00 | 01-JAN-08:10 | 4613.53 | 15-DEC-09:10 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 59.62 | 0.00 | 01-JAN-00:10 | 14043.38 | 21-JUL-18:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 59.62 | 0.00 | 01-JAN-00:10 | 14043.38 | 21-JUL-18:10 |
EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 729.17 | 206.32 | 19-JAN-01:20 | 71057.50 | 19-OCT-12:30 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 0.04 | 0.00 | 01-JAN-00:10 | 3647.55 | 19-JAN-05:00 |
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 0.04 | 0.00 | 01-JAN-00:10 | 3647.55 | 19-JAN-05:00 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 729.12 | 0.00 | 19-JAN-01:20 | 71057.50 | 19-OCT-12:30 |
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 729.12 | 0.00 | 19-JAN-01:20 | 71057.50 | 19-OCT-12:30 |
EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 550.61 | 1.54 | 18-DEC-02:00 | 81338.82 | 26-JUN-18:20 |
Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 10.00 | 0.00 | 01-JAN-00:10 | 29367.81 | 21-DEC-16:10 |
General:Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 10.00 | 0.00 | 01-JAN-00:10 | 29367.81 | 21-DEC-16:10 |
Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 540.62 | 0.00 | 01-JAN-04:10 | 81338.82 | 26-JUN-18:20 |
General:Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 540.62 | 0.00 | 01-JAN-04:10 | 81338.82 | 26-JUN-18:20 |
EnergyTransfer:Zone:ROOM_5_FLR_3 | 84.76 | 0.02 | 04-MAR-22:50 | 12156.74 | 17-JUN-08:10 |
Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 6.23 | 0.00 | 01-JAN-07:40 | 4158.50 | 20-JAN-09:10 |
General:Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 6.23 | 0.00 | 01-JAN-07:40 | 4158.50 | 20-JAN-09:10 |
Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 78.53 | 0.00 | 01-JAN-00:10 | 12156.74 | 17-JUN-08:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 78.53 | 0.00 | 01-JAN-00:10 | 12156.74 | 17-JUN-08:10 |
EnergyTransfer:Zone:ROOM_6_FLR_3 | 74.38 | 0.02 | 18-JAN-13:40 | 12325.67 | 17-JUN-08:10 |
Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 10.61 | 0.00 | 01-JAN-08:10 | 4300.42 | 20-JAN-09:10 |
General:Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 10.61 | 0.00 | 01-JAN-08:10 | 4300.42 | 20-JAN-09:10 |
Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 63.77 | 0.00 | 01-JAN-00:10 | 12325.67 | 17-JUN-08:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 63.77 | 0.00 | 01-JAN-00:10 | 12325.67 | 17-JUN-08:10 |
EnergyTransfer:Zone:CORRIDOR_FLR_3 | 235.64 | 0.86 | 21-DEC-15:20 | 13249.17 | 23-JUL-10:40 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 0.08 | 0.00 | 01-JAN-00:10 | 1414.28 | 19-JAN-09:10 |
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 0.08 | 0.00 | 01-JAN-00:10 | 1414.28 | 19-JAN-09:10 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 235.56 | 0.00 | 17-JAN-07:10 | 13249.17 | 23-JUL-10:40 |
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 235.56 | 0.00 | 17-JAN-07:10 | 13249.17 | 23-JUL-10:40 |
EnergyTransfer:Zone:ROOM_1_FLR_6 | 23.24 | 0.01 | 27-MAR-23:30 | 3969.13 | 21-JUL-18:10 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 2.76 | 0.00 | 01-JAN-08:10 | 1231.96 | 21-DEC-16:20 |
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 2.76 | 0.00 | 01-JAN-08:10 | 1231.96 | 21-DEC-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 20.47 | 0.00 | 01-JAN-00:10 | 3969.13 | 21-JUL-18:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 20.47 | 0.00 | 01-JAN-00:10 | 3969.13 | 21-JUL-18:10 |
EnergyTransfer:Zone:ROOM_2_FLR_6 | 21.12 | 0.08 | 07-MAY-02:50 | 4026.13 | 21-JUL-18:10 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 4.40 | 0.00 | 01-JAN-08:10 | 1461.26 | 21-DEC-16:20 |
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 4.40 | 0.00 | 01-JAN-08:10 | 1461.26 | 21-DEC-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 16.72 | 0.00 | 01-JAN-00:10 | 4026.13 | 21-JUL-18:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 16.72 | 0.00 | 01-JAN-00:10 | 4026.13 | 21-JUL-18:10 |
EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 141.72 | 0.13 | 20-APR-02:40 | 19921.44 | 31-OCT-15:10 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 4.06 | 0.00 | 01-JAN-00:10 | 5200.23 | 19-JAN-09:10 |
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 4.06 | 0.00 | 01-JAN-00:10 | 5200.23 | 19-JAN-09:10 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 137.66 | 0.00 | 01-JAN-04:00 | 19921.44 | 31-OCT-15:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 137.66 | 0.00 | 01-JAN-04:00 | 19921.44 | 31-OCT-15:10 |
EnergyTransfer:Zone:BANQUET_FLR_6 | 521.93 | 8073.96 | 15-DEC-09:10 | 23980.66 | 20-JUL-18:10 |
Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 521.93 | 8073.96 | 15-DEC-09:10 | 23980.66 | 20-JUL-18:10 |
General:Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 521.93 | 8073.96 | 15-DEC-09:10 | 23980.66 | 20-JUL-18:10 |
EnergyTransfer:Zone:DINING_FLR_6 | 558.77 | 9285.62 | 15-DEC-09:10 | 25379.84 | 20-JUL-18:10 |
Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 558.77 | 9285.62 | 15-DEC-09:10 | 25379.84 | 20-JUL-18:10 |
General:Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 558.77 | 9285.62 | 15-DEC-09:10 | 25379.84 | 20-JUL-18:10 |
Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 663.36 | 9099.41 | 15-DEC-04:00 | 31953.96 | 23-JUL-10:40 |
General:Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 663.36 | 9099.41 | 15-DEC-04:00 | 31953.96 | 23-JUL-10:40 |
EnergyTransfer:Zone:CORRIDOR_FLR_6 | 107.44 | 0.01 | 16-DEC-01:10 | 7987.43 | 22-JUL-10:40 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 1.80 | 0.00 | 01-JAN-00:10 | 2194.33 | 15-DEC-07:30 |
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 1.80 | 0.00 | 01-JAN-00:10 | 2194.33 | 15-DEC-07:30 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 105.63 | 0.00 | 01-JAN-03:40 | 7987.43 | 22-JUL-10:40 |
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 105.63 | 0.00 | 01-JAN-03:40 | 7987.43 | 22-JUL-10:40 |
PlantLoopHeatingDemand:Facility | 1664.02 | 11734.19 | 23-JUL-00:20 | 228790.49 | 21-JAN-07:10 |
PlantLoopHeatingDemand:Plant | 722.64 | 8271.43 | 08-AUG-02:30 | 54957.07 | 07-FEB-07:40 |
WaterSystems:PlantLoopHeatingDemand | 722.64 | 8271.43 | 08-AUG-02:30 | 54957.07 | 07-FEB-07:40 |
General:WaterSystems:PlantLoopHeatingDemand | 722.64 | 8271.43 | 08-AUG-02:30 | 54957.07 | 07-FEB-07:40 |
EnergyTransfer:HVAC | 10360.64 | 30008.81 | 04-OCT-07:10 | 922152.69 | 28-JUN-15:20 |
HeatingCoils:EnergyTransfer | 941.38 | 0.00 | 13-APR-21:10 | 186480.07 | 21-JAN-07:10 |
PlantLoopHeatingDemand:HVAC | 941.38 | 0.00 | 13-APR-21:10 | 186480.07 | 21-JAN-07:10 |
HeatingCoils:PlantLoopHeatingDemand | 941.38 | 0.00 | 13-APR-21:10 | 186480.07 | 21-JAN-07:10 |
CoolingCoils:EnergyTransfer | 5035.22 | 0.00 | 01-JAN-01:50 | 760786.00 | 31-JUL-18:10 |
HeatRecoveryForHeating:EnergyTransfer | 3812.78 | 0.00 | 01-JAN-13:00 | 631851.58 | 15-DEC-05:00 |
HeatRecoveryForCooling:EnergyTransfer | 571.26 | 0.00 | 01-JAN-00:10 | 311337.34 | 28-JUN-17:50 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:EnergyTransfer | 722.64 | 8271.43 | 08-AUG-02:30 | 54957.07 | 07-FEB-07:40 |
WaterUse:WaterSystems:EnergyTransfer | 722.64 | 8271.43 | 08-AUG-02:30 | 54957.07 | 07-FEB-07:40 |
Boilers:EnergyTransfer | 933.59 | 0.00 | 13-APR-21:10 | 183808.96 | 21-JAN-07:10 |
Chillers:EnergyTransfer | 5223.37 | 0.00 | 01-JAN-01:50 | 770986.60 | 31-JUL-18:10 |
HeatRejection:EnergyTransfer | 6880.02 | 0.00 | 01-JAN-01:50 | 959638.23 | 31-JUL-18:10 |
General:HeatRejection:EnergyTransfer | 6880.02 | 0.00 | 01-JAN-01:50 | 959638.23 | 31-JUL-18:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:57:58
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 0.000 | -472.050 | 0.000 | 0.000 | 158.008 | 165.288 | 150.255 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -1.502 |
RETAIL_1_FLR_1 | 0.000 | 0.000 | 0.358 | -54.759 | 0.000 | 0.000 | 16.064 | 8.404 | 10.186 | 38.718 | 0.000 | 0.389 | 0.001 | 0.000 | -9.219 | 0.000 | -2.905 | -7.235 |
RETAIL_2_FLR_1 | 0.000 | 0.000 | 0.000 | -43.203 | 0.000 | 0.000 | 18.591 | 9.732 | 11.795 | 0.000 | 0.000 | 0.155 | 4.036 | 0.000 | 0.000 | 0.000 | -1.106 | -0.000 |
MECH_FLR_1 | 0.000 | 0.000 | 0.078 | -30.663 | 0.000 | 0.000 | 3.951 | 18.192 | 12.471 | 0.000 | 0.000 | 0.372 | 0.001 | 0.000 | 0.000 | 0.000 | -2.601 | -1.800 |
STORAGE_FLR_1 | 0.000 | 0.000 | 0.410 | -12.269 | 0.000 | 0.000 | 3.044 | 3.340 | 3.598 | 0.000 | 0.000 | 0.217 | 3.160 | 0.000 | 0.000 | 0.000 | -1.499 | -0.000 |
LAUNDRY_FLR_1 | 0.000 | 0.000 | 0.000 | -605.880 | 0.000 | 0.000 | 12.199 | 4.125 | 658.131 | 0.000 | 0.000 | 0.484 | 0.000 | 0.000 | 0.000 | 0.000 | -3.675 | -65.384 |
CAFE_FLR_1 | 0.000 | 0.000 | 0.000 | -310.306 | 0.000 | 0.000 | 209.866 | 26.624 | 14.341 | 108.764 | 0.000 | 0.864 | 0.000 | 0.000 | -26.034 | 0.000 | -6.441 | -17.676 |
LOBBY_FLR_1 | 0.000 | 0.000 | 0.000 | -977.206 | 0.000 | 0.000 | 621.484 | 144.896 | 148.998 | 144.617 | 0.000 | 2.514 | 0.003 | 0.000 | -34.312 | 0.000 | -18.286 | -32.706 |
ROOM_1_FLR_3 | 10.422 | -61.773 | 0.000 | -16.720 | 0.000 | 0.000 | 9.673 | 20.410 | 12.292 | 73.779 | 0.000 | 0.858 | 0.001 | 0.000 | -21.740 | 0.000 | -7.391 | -19.810 |
ROOM_2_FLR_3 | 16.182 | -48.861 | 0.000 | -16.378 | 0.000 | 0.000 | 9.713 | 20.407 | 12.291 | 51.993 | 0.000 | 0.856 | 0.000 | 0.000 | -22.179 | 0.000 | -7.247 | -16.777 |
ROOM_3_MULT19_FLR_3 | 0.767 | -464.342 | 0.000 | -265.499 | 0.000 | 0.000 | 0.000 | 243.708 | 228.754 | 456.350 | 0.000 | 3.240 | 0.006 | 0.000 | -130.795 | 0.000 | -59.880 | -12.302 |
ROOM_4_MULT19_FLR_3 | 55.396 | -364.646 | 0.000 | -221.363 | 0.000 | 0.000 | 184.648 | 243.774 | 228.817 | 122.926 | 0.000 | 5.699 | 0.000 | 0.000 | -121.241 | 0.000 | -44.973 | -89.037 |
ROOM_5_FLR_3 | 10.631 | -66.103 | 0.000 | -16.826 | 0.000 | 0.000 | 9.658 | 20.410 | 12.292 | 77.496 | 0.000 | 0.856 | 0.000 | 0.000 | -21.118 | 0.000 | -7.446 | -19.849 |
ROOM_6_FLR_3 | 15.949 | -52.616 | 0.000 | -16.489 | 0.000 | 0.000 | 9.700 | 20.407 | 12.291 | 55.218 | 0.000 | 0.853 | 0.000 | 0.000 | -21.081 | 0.000 | -7.300 | -16.932 |
CORRIDOR_FLR_3 | 0.000 | 0.000 | 0.077 | -235.559 | 0.000 | 0.000 | 123.065 | 62.736 | 0.000 | 67.355 | 0.000 | 1.001 | 15.655 | 0.000 | -26.186 | 0.000 | -8.144 | -0.001 |
ROOM_1_FLR_6 | 4.039 | -17.577 | 0.000 | -4.171 | 0.000 | 0.000 | 2.420 | 5.102 | 3.073 | 18.297 | 0.000 | 0.215 | 0.000 | 0.000 | -5.413 | 0.000 | -1.877 | -4.109 |
ROOM_2_FLR_6 | 5.915 | -14.147 | 0.000 | -4.087 | 0.000 | 0.000 | 2.429 | 5.102 | 3.073 | 12.879 | 0.000 | 0.214 | 0.000 | 0.000 | -5.511 | 0.000 | -1.840 | -4.027 |
ROOM_3_MULT9_FLR_6 | 9.298 | -115.767 | 0.000 | -27.120 | 0.000 | 0.000 | 21.714 | 28.868 | 27.097 | 99.530 | 0.000 | 1.096 | 0.003 | 0.000 | -25.171 | 0.000 | -9.397 | -10.149 |
BANQUET_FLR_6 | 0.000 | 0.000 | 0.000 | -521.936 | 0.000 | 0.000 | 359.484 | 46.753 | 175.857 | 14.218 | 0.000 | 0.521 | 0.000 | 0.000 | -14.319 | 0.000 | -4.251 | -56.327 |
DINING_FLR_6 | 0.000 | 0.000 | 0.000 | -558.775 | 0.000 | 0.000 | 358.324 | 46.753 | 175.857 | 13.995 | 0.000 | 0.513 | 0.000 | 0.000 | -14.641 | 0.000 | -4.268 | -17.758 |
KITCHEN_FLR_6 | 0.000 | 0.000 | 0.000 | -663.350 | 0.000 | 0.000 | 30.474 | 12.482 | 556.656 | 36.195 | 0.000 | 0.289 | 41.901 | 0.000 | -10.455 | 0.000 | -4.192 | -0.000 |
CORRIDOR_FLR_6 | 0.000 | 0.000 | 1.805 | -105.634 | 0.000 | 0.000 | 32.980 | 16.599 | 0.000 | 33.353 | 0.000 | 0.469 | 35.505 | 0.000 | -11.505 | 0.000 | -3.572 | -0.000 |
Total Facility | 128.599 | -1205.831 | 2.727 | -5180.240 | 0.000 | 0.000 | 2197.489 | 1174.112 | 2458.123 | 1425.683 | 0.000 | 21.676 | 100.272 | 0.000 | -520.920 | 0.000 | -208.292 | -393.383 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 13-SEP-18:10 | 0.00 | 0.00 | 0.00 | -22607.00 | 0.00 | 0.00 | 6161.60 | 12015.03 | 9581.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -5151.12 |
RETAIL_1_FLR_1 | 14-FEB-13:30 | 0.00 | 0.00 | 0.00 | -4213.77 | 0.00 | 0.00 | 150.60 | 190.92 | 252.59 | 7344.02 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -39.10 | -3685.25 |
RETAIL_2_FLR_1 | 20-JUL-18:10 | 0.00 | 0.00 | 0.00 | -2346.38 | 0.00 | 0.00 | 725.62 | 707.46 | 752.15 | 0.00 | 0.00 | 52.33 | 108.82 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 20-JUL-18:10 | 0.00 | 0.00 | 0.00 | -2339.08 | 0.00 | 0.00 | 153.46 | 1322.39 | 795.27 | 0.00 | 0.00 | 124.73 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -56.75 |
STORAGE_FLR_1 | 20-JUL-18:02 | 0.00 | 0.00 | 0.00 | -1150.12 | 0.00 | 0.00 | 118.03 | 242.76 | 229.41 | 0.00 | 0.00 | 72.43 | 487.49 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 28-JUN-20:00 | 0.00 | 0.00 | 0.00 | -38016.69 | 0.00 | 0.00 | 421.94 | 337.37 | 44299.38 | 0.00 | 0.00 | 76.23 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -7118.22 |
CAFE_FLR_1 | 19-NOV-11:35 | 0.00 | 0.00 | 0.00 | -16696.99 | 0.00 | 0.00 | 3065.41 | 725.74 | 406.43 | 21696.55 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -328.13 | -8869.02 |
LOBBY_FLR_1 | 20-JUL-18:10 | 0.00 | 0.00 | 0.00 | -46406.98 | 0.00 | 0.00 | 24443.00 | 10532.73 | 9501.36 | 2723.22 | 0.00 | 858.65 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1651.97 |
ROOM_1_FLR_3 | 27-SEP-15:01 | 0.00 | -18571.35 | 0.00 | -597.87 | 0.00 | 0.00 | 235.29 | 439.85 | 273.93 | 13574.32 | 0.00 | 152.08 | 4493.74 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 11-JUN-18:01 | 0.00 | -18292.61 | 0.00 | -595.02 | 0.00 | 0.00 | 283.23 | 1570.72 | 516.20 | 10793.28 | 0.00 | 110.17 | 5614.01 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 19-OCT-12:30 | 0.00 | -62401.86 | 0.00 | -8652.86 | 0.00 | 0.00 | 0.00 | 5252.20 | 5097.90 | 85915.57 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -341.82 | -24869.12 |
ROOM_4_MULT19_FLR_3 | 20-AUG-18:01 | 0.00 | -103800.71 | 0.00 | -8327.91 | 0.00 | 0.00 | 5381.40 | 18762.99 | 9610.21 | 11114.14 | 0.00 | 1269.19 | 65990.69 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 17-JUN-08:61 | 0.00 | -16476.80 | 0.00 | -602.40 | 0.00 | 0.00 | 130.72 | 879.71 | 653.23 | 11911.37 | 0.00 | 52.54 | 3451.64 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 17-JUN-08:61 | 0.00 | -16364.99 | 0.00 | -603.84 | 0.00 | 0.00 | 130.72 | 879.61 | 653.15 | 11973.10 | 0.00 | 52.00 | 3280.25 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 23-JUL-10:35 | 0.00 | 0.00 | 0.00 | -13293.27 | 0.00 | 0.00 | 1977.09 | 1710.14 | 0.00 | 5373.18 | 0.00 | 262.37 | 3970.49 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 05-OCT-15:01 | 0.00 | -5017.36 | 0.00 | -149.73 | 0.00 | 0.00 | 58.82 | 109.96 | 68.48 | 3270.27 | 0.00 | 23.19 | 1636.35 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 11-JUN-18:01 | 0.00 | -4942.09 | 0.00 | -149.29 | 0.00 | 0.00 | 70.81 | 392.68 | 129.05 | 2678.26 | 0.00 | 27.03 | 1793.56 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 05-OCT-15:01 | 0.00 | -21301.34 | 0.00 | -992.60 | 0.00 | 0.00 | 529.39 | 622.14 | 603.86 | 9754.72 | 0.00 | 99.02 | 10684.80 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 20-JUL-18:10 | 0.00 | 0.00 | 0.00 | -24323.64 | 0.00 | 0.00 | 14121.55 | 3398.57 | 6747.90 | 2618.32 | 0.00 | 181.15 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2743.85 |
DINING_FLR_6 | 20-JUL-18:10 | 0.00 | 0.00 | 0.00 | -25717.86 | 0.00 | 0.00 | 14057.64 | 3398.57 | 6747.90 | 2600.58 | 0.00 | 180.23 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1267.07 |
KITCHEN_FLR_6 | 23-JUL-10:40 | 0.00 | 0.00 | 0.00 | -31959.46 | 0.00 | 0.00 | 464.19 | 340.26 | 24459.16 | 3925.73 | 0.00 | 92.79 | 2677.34 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 22-JUL-10:35 | 0.00 | 0.00 | 0.00 | -8027.78 | 0.00 | 0.00 | 531.09 | 377.07 | 0.00 | 2421.49 | 0.00 | 136.04 | 4562.10 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 20-JUL-18:02 | 0.00 | -232756.67 | 0.00 | -242308.20 | 0.00 | 0.00 | 84691.00 | 82800.17 | 122526.13 | 77148.74 | 0.00 | 7322.91 | 100575.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 09-DEC-07:30 | 0.00 | 0.00 | 750.01 | 0.00 | 0.00 | 0.00 | 452.43 | 229.10 | 288.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -985.94 | 0.00 | -251.33 | -482.95 |
RETAIL_2_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 15-DEC-05:00 | 0.00 | 0.00 | 277.19 | 0.00 | 0.00 | 0.00 | 197.27 | 165.30 | 176.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -305.37 | -511.11 |
STORAGE_FLR_1 | 15-DEC-05:00 | 0.00 | 0.00 | 282.66 | 0.00 | 0.00 | 0.00 | 151.75 | 30.34 | 50.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -176.19 | -339.55 |
LAUNDRY_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 23-MAR-08:61 | 7055.56 | 374.04 | 0.00 | -374.04 | 0.00 | 0.00 | 102.72 | 691.20 | 453.05 | 973.75 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -331.85 | -8944.43 |
ROOM_2_FLR_3 | 12-JAN-16:01 | 7173.41 | 353.26 | 0.00 | -353.26 | 0.00 | 0.00 | 287.19 | 439.80 | 273.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -345.98 | 0.00 | -328.40 | -7499.93 |
ROOM_3_MULT19_FLR_3 | 19-JAN-05:00 | 3647.70 | 10639.41 | 0.00 | -10639.41 | 0.00 | 0.00 | 0.00 | 2063.36 | 3921.46 | 0.00 | 0.00 | 0.00 | 4676.08 | 0.00 | -11453.68 | 0.00 | -2854.93 | 0.00 |
ROOM_4_MULT19_FLR_3 | 23-MAR-15:03 | 42837.16 | 4782.80 | 0.00 | -4782.80 | 0.00 | 0.00 | 4819.97 | 5253.64 | 5099.29 | 7007.88 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -13523.93 | -51494.01 |
ROOM_5_FLR_3 | 08-DEC-16:01 | 6807.57 | 578.16 | 0.00 | -578.16 | 0.00 | 0.00 | 293.98 | 439.85 | 273.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -645.05 | 0.00 | -431.66 | -6738.63 |
ROOM_6_FLR_3 | 20-JAN-16:01 | 7035.83 | 326.54 | 0.00 | -326.54 | 0.00 | 0.00 | 293.99 | 439.80 | 273.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -506.81 | 0.00 | -315.68 | -7221.04 |
CORRIDOR_FLR_3 | 19-JAN-09:02 | 0.00 | 0.00 | 1495.97 | 0.00 | 0.00 | 0.00 | 1385.85 | 2280.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -458.90 | 0.00 | -693.11 | -4010.00 |
ROOM_1_FLR_6 | 25-OCT-18:01 | 2108.34 | 125.05 | 0.00 | -125.05 | 0.00 | 0.00 | 104.80 | 349.53 | 129.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -413.67 | 0.00 | -99.25 | -2178.81 |
ROOM_2_FLR_6 | 12-JAN-16:01 | 2140.48 | 81.38 | 0.00 | -81.38 | 0.00 | 0.00 | 73.47 | 109.95 | 68.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -76.38 | 0.00 | -79.78 | -2236.22 |
ROOM_3_MULT9_FLR_6 | 17-JAN-16:02 | 9315.86 | 979.24 | 0.00 | -979.24 | 0.00 | 0.00 | 659.21 | 622.14 | 603.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -618.11 | 0.00 | -522.96 | -10060.00 |
BANQUET_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 15-DEC-07:30 | 0.00 | 0.00 | 2194.00 | 0.00 | 0.00 | 0.00 | 736.91 | 754.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1538.19 | 0.00 | -388.59 | -1758.26 |
Total Facility | 08-DEC-16:01 | -34026.07 | 123837.54 | 241.59 | -123837.54 | 0.00 | 0.00 | 62486.95 | 25962.78 | 77528.99 | 6184.84 | 0.00 | 0.00 | 0.00 | 0.00 | -12386.59 | 0.00 | -11545.44 | -114447.06 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:57:58
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV WITH REHEAT | 26.7132 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 26.5797 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
FLR_3_DOAS | 2.0513 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.0513 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV WITH REHEAT | 26.5797 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 26.5797 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
FLR_3_DOAS | 2.0513 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.0513 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | VAV WITH REHEAT | 0.000000 | 106.4990 | 0.000432 | 1978.83 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | 0.000000 | 10.8290 | 0.001181 | 67.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | 0.000000 | 12.5400 | 0.001181 | 77.67 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
MECH_FLR_1 | VAV WITH REHEAT | 0.000000 | 2.6520 | 0.000000 | 164.24 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | 0.000000 | 2.0400 | 0.000610 | 94.76 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | 0.000000 | 8.4000 | 0.000000 | 78.04 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | 0.000000 | 142.3000 | 0.003581 | 188.86 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | 0.000000 | 422.4350 | 0.001448 | 1308.19 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1863.81 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1864.32 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | 0.000000 | 83.8280 | 0.000305 | 1557.62 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000396 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000396 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.000000 | 13.5000 | 0.000449 | 220.77 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003581 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DINING_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003581 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | 0.000000 | 22.2380 | 0.003556 | 103.30 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | 0.000000 | 22.1800 | 0.000305 | 412.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV WITH REHEAT | 0.00 | 0.001045 | 6694.0231 | 0.0000 | 0.0000 | 0.0000 | |
FLR_3_DOAS | 0.00 | 0.000441 | 4651.2638 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.0487 | 3.0487 | 3.0335 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4411 | 0.4411 | 0.4389 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2924 | 0.2924 | 0.2910 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2962 | 0.2962 | 0.2947 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1476 | 0.1476 | 0.1469 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.9686 | 3.9686 | 3.9487 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.8572 | 1.8572 | 1.8479 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.8097 | 5.8097 | 5.7807 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8371 | 0.8371 | 0.8371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8373 | 0.8373 | 0.8373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4459 | 1.4459 | 1.4387 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0992 | 0.0992 | 0.0992 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.7755 | 2.7755 | 2.7616 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.9117 | 2.9117 | 2.8971 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.8101 | 2.8101 | 2.7961 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9085 | 0.9085 | 0.9039 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV WITH REHEAT | 26.7132 | 26.5797 | 26.7132 | 26.5797 | 0.0000 | 1.0000 |
FLR_3_DOAS | 2.0513 | 2.0513 | 2.0513 | 2.0513 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.0335 | 3.0335 | 3.0335 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4389 | 0.4389 | 0.4389 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2910 | 0.2910 | 0.2910 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2947 | 0.2947 | 0.2947 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1469 | 0.1469 | 0.1469 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.9487 | 3.9487 | 3.9487 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.8479 | 1.8479 | 1.8479 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.7807 | 5.7807 | 5.7807 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8371 | 0.8371 | 0.8371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8373 | 0.8373 | 0.8373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4387 | 1.4387 | 1.4387 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0992 | 0.0992 | 0.0992 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.7616 | 2.7616 | 2.7616 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.8971 | 2.8971 | 2.8971 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.7961 | 2.7961 | 2.7961 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9039 | 0.9039 | 0.9039 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV WITH REHEAT | 26.5797 | 26.5797 | 26.5797 | 26.5797 | 0.0000 | 1.0000 |
FLR_3_DOAS | 2.0513 | 2.0513 | 2.0513 | 2.0513 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:57:58
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Albuquerque Intl Sunport NM USA TMY3 WMO#=723650 |
Total gross floor area [m2] | 11345.29 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 1978.83 | 1978.83 | 0.00 | 168.00 |
RETAIL_1_FLR_1 | 67.07 | 67.07 | 0.00 | 168.00 |
RETAIL_2_FLR_1 | 77.67 | 77.67 | 0.00 | 168.00 |
MECH_FLR_1 | 164.24 | 164.24 | 0.00 | 168.00 |
STORAGE_FLR_1 | 94.76 | 94.76 | 0.00 | 168.00 |
LAUNDRY_FLR_1 | 78.04 | 78.04 | 0.00 | 168.00 |
CAFE_FLR_1 | 188.86 | 188.86 | 0.00 | 168.00 |
LOBBY_FLR_1 | 1308.19 | 1308.19 | 0.00 | 168.00 |
ROOM_1_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT19_FLR_3 | 24.52 | 24.52 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 24.53 | 24.53 | 0.00 | 168.00 |
ROOM_5_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_6_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
CORRIDOR_FLR_3 | 389.40 | 389.40 | 0.00 | 168.00 |
ROOM_1_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT9_FLR_6 | 24.53 | 24.53 | 0.00 | 168.00 |
BANQUET_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
DINING_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
KITCHEN_FLR_6 | 103.30 | 103.30 | 0.00 | 168.00 |
CORRIDOR_FLR_6 | 412.12 | 412.12 | 0.00 | 168.00 |
Totals | 11345.29 | 11345.29 | 0.00 |
Data | |
Number of hours heating loads not met | 0.17 |
Number of hours cooling loads not met | 14.67 |
Number of hours not met | 14.83 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 1384.76 | 236891.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 1656.65 | 250573.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 1174.11 | 93091.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 262.25 | 16690.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 959.56 | 59492.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 762.04 | 29240.64 | 1198.64 | 74976.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 16.27 | 515.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 13.43 | 425.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Laundry | 0.00 | 0.00 | 590.20 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 32.92 | 1912.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 616.11 | 37691.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 30.65 | 972.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 2171.14 | 93468.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 222.39 | 12220.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- General | 435.63 | 19111.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 90.78 | 4739.92 | 3126.84 | 287399.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 18.27 | 2271.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 22.38 | 1920.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 33.23 | 1195.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 1825.18 | 8517.80 |
Natural Gas | 1788.84 | 6300.43 |
Additional | 0.00 | 0.00 |
Total | 3614.01 | 14818.23 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 103.49 |
Space Heating | 0.00 |
Space Cooling | 146.02 |
Fans (All) | 191.37 |
Service Water Heating | 8.00 |
Receptacle Equipment | 154.36 |
Miscellaneous (All) | 750.78 |
Subtotal | 750.78 |
Natural Gas [MJ/m2] | |
Space Heating | 122.06 |
Service Water Heating | 275.61 |
Miscellaneous (All) | 555.33 |
Subtotal | 555.33 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 7.92 |
Space Heating | 9.34 |
Space Cooling | 11.18 |
Fans (All) | 14.65 |
Service Water Heating | 21.71 |
Receptacle Equipment | 23.89 |
Miscellaneous | 11.30 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_KITCHEN | 3061. | 8760. |
LTG_SCH_DINING | 3061. | 8760. |
LTG_SCH_BASEMENT | 2655. | 8760. |
LTG_SCH_LOBBY | 3061. | 8760. |
LTG_SCH_STORAGE | 1339. | 8760. |
LTG_SCH_MECHANIC | 3061. | 8760. |
LTG_SCH_LAUNDRY | 2678. | 8760. |
LTG_SCH_GUESTROOM | 3599. | 8760. |
LTG_SCH_CORRIDOR | 3061. | 8760. |
LTG_SCH_RETAIL | 2678. | 8760. |
WALKIN_OCC_LGHT_SCH_1 | 3061. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
BASEMENT_EQUIP_SCH | 3924. | 8760. |
BLDG_EQUIP_SCH | 3924. | 8760. |
GUESTROOM_EQP_SCH_BASE | 3239. | 8760. |
GUESTROOM_EQP_SCH_ADVA | 2762. | 8760. |
LOBBY_EQP_SCH | 3292. | 8760. |
OFFICE_EQP_SCH | 4941. | 8760. |
EMPLOYEELOUNGE_EQP_SCH | 4044. | 8760. |
LAUNDRYROOM_EQP_ELEC_SCH | 2920. | 2920. |
LAUNDRYROOM_EQP_GAS_SCH | 2920. | 2920. |
MEETINGROOM_EQP_SCH | 1336. | 4745. |
EXERCISEROOM_EQP_SCH | 3832. | 5840. |
KITCHEN_ELEC_EQUIP_SCH | 2172. | 8760. |
KITCHEN_GAS_EQUIP_SCH | 1332. | 8760. |
KITCHEN_EXHAUST_SCH | 6205. | 6205. |
BLDG_ELEVATORS | 2270. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_OCC_SCH | 5026. | 8760. |
GUESTROOM_OCC_SCH | 5515. | 8760. |
LOBBY_OCC_SCH | 2304. | 8760. |
OFFICE_OCC_SCH | 3954. | 8760. |
EMPLOYEELOUNGE_OCC_SCH | 948. | 5475. |
MEETINGROOM_OCC_SCH | 1168. | 4745. |
LAUNDRYROOM_OCC_SCH | 427. | 2920. |
EXERCISEROOM_OCC_SCH | 5292. | 5840. |
INFIL_SCH | 8760. | 8760. |
INFIL_HALF_ON_SCH | 4380. | 8760. |
INFIL_QUARTER_ON_SCH | 2190. | 8760. |
LAUNDRY_SWH_SCH | 2555. | 2555. |
BLDG_SWH_SCH | 3301. | 8760. |
GUESTROOM_SWH_SCH | 2899. | 8760. |
LAUNDRYROOM_SWH_SCH | 2920. | 2920. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
ALWAYS_ON | 8760. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
OCC_GUESTROOM_VENT_CTRL_30MIN | 6570. | 6570. |
OCC_GUESTROOM_VENT_CTRL_20MIN | 6327. | 6327. |
VAC_GUESTROOM_VENTILATION_SCHEDULE | 365. | 365. |
MINOA_MOTORIZEDDAMPER_SCHED | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
ROOM_1_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
FLR_3_DOAS_OAMINOAFRACSCHEDULE | 8760. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 0. | 0. |
LAUNDRY_FLR_1 EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 0. | 0. |
SLIDING_DOORS_VENTILATION_AVAILABILITY_SCH | 3285. | 3285. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
VACGUESTROOM_HTGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 18.89 | 365 | 18.89 | 365 |
VACGUESTROOM_CLGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 23.33 | 365 |
OBCRESET_S_OCCGUESTROOM_HTGSP_SCH_30MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_S_OCCGUESTROOM_CLGSP_SCH_30MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_HTGSP_SCH_30MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_CLGSP_SCH_30MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
HTGSETP_SCH | BASEMENT DUAL SP CONTROL | January | 21.00 | 365 | 21.00 | 365 |
CLGSETP_SCH | BASEMENT DUAL SP CONTROL | July | 24.00 | 365 | 24.00 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:57:58
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Average | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Sum | 192720.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 529331.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 50179.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 59156.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8977.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 5588.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 37203.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 710417.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 2115429.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 100358.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 108269.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 105946.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 2115429.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Average | 288887.05 | 0.00 | 0.00 | 0.00 | 0.00 |
Sum | 6355515.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Average | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Sum | 192720.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 529331.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 50179.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 59156.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8977.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 5588.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 37203.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 710417.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 2115429.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 100358.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 108269.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 105946.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 2115429.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Average | 288887.05 | 0.00 | 0.00 | 0.00 | 0.00 |
Sum | 6355515.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:57:58
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:57:58
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2012
For: Environment
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
For: Environment
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4B
For: Environment
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NM_ALBUQUERQUE
For: Environment
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.397889E+11 | 19490.73 | 03-JAN-21:00 | 3.90 | 0.12 | 0.616832E+10 | 3817.86 | 20-JAN-22:10 | 0.10 | -2.0 |
February | 0.330105E+11 | 19444.15 | 13-FEB-19:01 | 13.03 | 4.08 | 0.554808E+10 | 3782.08 | 01-FEB-22:10 | 13.03 | 4.08 |
March | 0.340334E+11 | 19330.12 | 08-MAR-20:10 | 15.73 | 6.05 | 0.614445E+10 | 3710.85 | 01-MAR-22:10 | 15.73 | 6.05 |
April | 0.330969E+11 | 19901.89 | 13-APR-19:10 | 21.32 | 8.04 | 0.591940E+10 | 3711.46 | 04-APR-21:10 | 21.32 | 8.04 |
May | 0.350997E+11 | 20362.74 | 18-MAY-19:10 | 25.13 | 11.79 | 0.612007E+10 | 3711.84 | 03-MAY-21:10 | 25.13 | 11.79 |
June | 0.365086E+11 | 21525.53 | 28-JUN-19:20 | 31.47 | 16.90 | 0.594066E+10 | 3734.32 | 08-JUN-21:10 | 31.47 | 16.90 |
July | 0.403862E+11 | 22255.88 | 20-JUL-19:10 | 33.35 | 14.34 | 0.613063E+10 | 3766.26 | 28-JUL-22:10 | 23.72 | 15.47 |
August | 0.426682E+11 | 22544.74 | 17-AUG-18:20 | 31.67 | 16.23 | 0.619004E+10 | 3801.73 | 18-AUG-22:10 | 23.98 | 12.16 |
September | 0.438065E+11 | 22607.13 | 13-SEP-18:10 | 26.93 | 13.80 | 0.604510E+10 | 3864.18 | 27-SEP-22:10 | 18.98 | 9.47 |
October | 0.462849E+11 | 22061.86 | 05-OCT-18:10 | 23.67 | 10.39 | 0.630309E+10 | 3925.87 | 25-OCT-21:10 | 3.12 | -0.4 |
November | 0.439412E+11 | 20542.68 | 01-NOV-20:00 | 7.80 | 4.71 | 0.609442E+10 | 3904.48 | 16-NOV-22:10 | 3.95 | -0.9 |
December | 0.434229E+11 | 20147.81 | 01-DEC-21:00 | 9.40 | 2.54 | 0.624881E+10 | 3887.53 | 14-DEC-22:10 | -2.8 | -7.5 |
Annual Sum or Average | 0.472048E+12 | 0.728531E+11 | ||||||||
Minimum of Months | 0.330105E+11 | 19330.12 | 3.90 | 0.12 | 0.554808E+10 | 3710.85 | -2.8 | -7.5 | ||
Maximum of Months | 0.462849E+11 | 22607.13 | 33.35 | 16.90 | 0.630309E+10 | 3925.87 | 31.47 | 16.90 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.316450E+10 | 4109.20 | 01-JAN-11:35 | 9.83 | 3.02 | 0.630743E+09 | 364.28 | 20-JAN-02:09 | -8.1 | -8.1 |
February | 0.318167E+10 | 4214.01 | 14-FEB-13:30 | 20.00 | 6.81 | 0.570091E+09 | 364.28 | 06-FEB-03:49 | 20.00 | 6.81 |
March | 0.361343E+10 | 3899.78 | 08-MAR-11:35 | 17.07 | 7.88 | 0.629480E+09 | 364.27 | 06-MAR-04:00 | 17.07 | 7.88 |
April | 0.412709E+10 | 3471.06 | 13-APR-10:35 | 20.77 | 7.23 | 0.603884E+09 | 365.61 | 13-APR-21:19 | 20.17 | 7.26 |
May | 0.434072E+10 | 2985.25 | 13-MAY-12:00 | 26.10 | 11.30 | 0.621741E+09 | 364.93 | 19-MAY-21:19 | 22.93 | 8.09 |
June | 0.515821E+10 | 3361.02 | 29-JUN-15:15 | 37.07 | 16.08 | 0.603634E+09 | 382.85 | 27-JUN-21:40 | 37.07 | 16.08 |
July | 0.610558E+10 | 3423.68 | 23-JUL-10:35 | 31.83 | 17.15 | 0.623590E+09 | 390.01 | 21-JUL-21:40 | 31.83 | 17.15 |
August | 0.637001E+10 | 3794.02 | 20-AUG-10:40 | 30.17 | 17.03 | 0.630847E+09 | 387.58 | 21-AUG-21:40 | 25.97 | 14.84 |
September | 0.599396E+10 | 4060.63 | 28-SEP-10:35 | 25.93 | 14.34 | 0.614821E+09 | 382.44 | 28-SEP-21:30 | 20.25 | 11.80 |
October | 0.538138E+10 | 4120.57 | 31-OCT-13:10 | 20.47 | 8.43 | 0.637644E+09 | 382.19 | 06-OCT-21:30 | 20.47 | 8.43 |
November | 0.402413E+10 | 4176.78 | 07-NOV-11:35 | 11.13 | 3.62 | 0.612557E+09 | 364.28 | 10-NOV-05:10 | 5.00 | 2.38 |
December | 0.329840E+10 | 4100.31 | 31-DEC-13:00 | 8.30 | 1.00 | 0.631595E+09 | 364.29 | 05-DEC-04:40 | 8.30 | 1.00 |
Annual Sum or Average | 0.547591E+11 | 0.741063E+10 | ||||||||
Minimum of Months | 0.316450E+10 | 2985.25 | 8.30 | 1.00 | 0.570091E+09 | 364.27 | -8.1 | -8.1 | ||
Maximum of Months | 0.637001E+10 | 4214.01 | 37.07 | 17.15 | 0.637644E+09 | 390.01 | 37.07 | 17.15 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.283537E+10 | 1797.87 | 03-JAN-21:00 | 3.90 | 0.12 | 0.718700E+09 | 437.25 | 09-JAN-22:19 | 6.50 | 0.58 |
February | 0.271261E+10 | 1900.48 | 14-FEB-21:00 | 10.00 | 3.10 | 0.650733E+09 | 449.90 | 14-FEB-22:19 | 10.60 | 3.54 |
March | 0.325627E+10 | 1953.35 | 08-MAR-19:10 | 17.02 | 6.70 | 0.725018E+09 | 450.82 | 08-MAR-22:19 | 10.53 | 4.18 |
April | 0.352397E+10 | 2113.21 | 13-APR-18:10 | 24.45 | 9.49 | 0.703912E+09 | 463.26 | 13-APR-21:40 | 19.23 | 6.82 |
May | 0.382875E+10 | 2166.48 | 15-MAY-18:10 | 27.85 | 10.46 | 0.730303E+09 | 467.74 | 19-MAY-22:10 | 21.93 | 7.53 |
June | 0.412268E+10 | 2322.44 | 28-JUN-18:10 | 34.03 | 16.72 | 0.717741E+09 | 480.11 | 27-JUN-22:10 | 34.03 | 16.72 |
July | 0.446823E+10 | 2346.30 | 20-JUL-18:10 | 35.73 | 14.77 | 0.742149E+09 | 486.00 | 21-JUL-22:10 | 27.85 | 14.51 |
August | 0.448065E+10 | 2302.66 | 17-AUG-18:10 | 31.93 | 16.45 | 0.745863E+09 | 481.49 | 18-AUG-22:10 | 23.98 | 12.16 |
September | 0.416349E+10 | 2195.51 | 13-SEP-18:10 | 26.93 | 13.80 | 0.713246E+09 | 471.10 | 21-SEP-22:10 | 18.80 | 9.62 |
October | 0.382972E+10 | 2123.71 | 05-OCT-18:10 | 23.67 | 10.39 | 0.728908E+09 | 469.83 | 06-OCT-21:40 | 19.60 | 11.17 |
November | 0.316007E+10 | 1893.27 | 02-NOV-18:10 | 15.00 | 8.23 | 0.697514E+09 | 451.02 | 02-NOV-21:19 | 11.87 | 5.90 |
December | 0.282098E+10 | 1775.18 | 29-DEC-21:00 | 1.70 | -2.0 | 0.718476E+09 | 435.22 | 29-DEC-22:19 | 2.03 | -1.4 |
Annual Sum or Average | 0.432028E+11 | 0.859256E+10 | ||||||||
Minimum of Months | 0.271261E+10 | 1775.18 | 1.70 | -2.0 | 0.650733E+09 | 435.22 | 2.03 | -1.4 | ||
Maximum of Months | 0.448065E+10 | 2346.30 | 35.73 | 16.72 | 0.745863E+09 | 486.00 | 34.03 | 16.72 |
Report: ZoneCoolingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.899329E+09 | 1357.04 | 05-JAN-21:00 | 5.00 | -0.9 | 0.151697E+09 | 89.15 | 11-JAN-01:49 | 4.18 | -1.0 |
February | 0.103885E+10 | 1617.08 | 15-FEB-21:00 | 7.80 | 3.08 | 0.137152E+09 | 89.15 | 06-FEB-03:00 | 7.80 | 3.08 |
March | 0.181150E+10 | 1724.44 | 08-MAR-21:00 | 13.90 | 5.15 | 0.152410E+09 | 89.15 | 21-MAR-02:09 | 10.92 | 5.40 |
April | 0.251604E+10 | 1980.11 | 27-APR-19:10 | 21.60 | 9.13 | 0.147270E+09 | 92.42 | 28-APR-21:19 | 19.80 | 7.02 |
May | 0.320157E+10 | 2101.45 | 31-MAY-18:20 | 26.83 | 10.16 | 0.152662E+09 | 94.41 | 19-MAY-22:10 | 26.83 | 10.16 |
June | 0.396620E+10 | 2329.80 | 28-JUN-18:10 | 34.03 | 16.72 | 0.149569E+09 | 97.77 | 28-JUN-22:10 | 27.20 | 14.98 |
July | 0.446154E+10 | 2339.05 | 20-JUL-18:10 | 35.73 | 14.77 | 0.154537E+09 | 98.46 | 21-JUL-22:10 | 27.85 | 14.51 |
August | 0.425582E+10 | 2288.59 | 17-AUG-18:10 | 31.93 | 16.45 | 0.154574E+09 | 96.96 | 18-AUG-22:10 | 23.98 | 12.16 |
September | 0.354937E+10 | 2117.92 | 13-SEP-18:20 | 26.67 | 13.74 | 0.147955E+09 | 94.37 | 01-SEP-21:19 | 26.67 | 13.74 |
October | 0.262175E+10 | 2015.38 | 02-OCT-18:30 | 20.60 | 15.47 | 0.152041E+09 | 92.88 | 03-OCT-21:10 | 18.62 | 10.85 |
November | 0.152687E+10 | 1685.61 | 02-NOV-20:00 | 12.80 | 4.41 | 0.146742E+09 | 89.15 | 27-NOV-04:49 | -3.9 | -6.4 |
December | 0.813752E+09 | 1426.16 | 01-DEC-21:00 | 9.40 | 2.54 | 0.151698E+09 | 89.15 | 14-DEC-03:39 | -0.5 | -5.2 |
Annual Sum or Average | 0.306626E+11 | 0.179831E+10 | ||||||||
Minimum of Months | 0.813752E+09 | 1357.04 | 5.00 | -0.9 | 0.137152E+09 | 89.15 | -3.9 | -6.4 | ||
Maximum of Months | 0.446154E+10 | 2339.05 | 35.73 | 16.72 | 0.154574E+09 | 98.46 | 27.85 | 14.98 |
Report: ZoneCoolingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.118757E+09 | 338.06 | 05-JAN-21:50 | 4.08 | -1.2 | 0.116691E+09 | 68.58 | 11-JAN-00:49 | 5.32 | 0.22 |
February | 0.204480E+09 | 510.17 | 14-FEB-22:00 | 10.60 | 3.54 | 0.105502E+09 | 68.58 | 02-FEB-01:10 | 10.60 | 3.54 |
March | 0.522847E+09 | 575.41 | 16-MAR-21:00 | 15.00 | 4.43 | 0.117239E+09 | 68.58 | 21-MAR-01:49 | 11.02 | 5.48 |
April | 0.961658E+09 | 850.19 | 28-APR-21:00 | 20.00 | 7.20 | 0.113126E+09 | 68.75 | 28-APR-21:40 | 19.60 | 6.84 |
May | 0.135646E+10 | 949.49 | 19-MAY-19:20 | 26.67 | 10.05 | 0.116973E+09 | 70.16 | 19-MAY-22:10 | 21.93 | 7.53 |
June | 0.184735E+10 | 1137.76 | 28-JUN-18:03 | 34.03 | 16.72 | 0.114090E+09 | 72.73 | 28-JUN-22:10 | 27.20 | 14.98 |
July | 0.213833E+10 | 1150.11 | 20-JUL-18:02 | 35.73 | 14.77 | 0.117674E+09 | 73.30 | 21-JUL-22:10 | 27.85 | 14.51 |
August | 0.201478E+10 | 1062.11 | 17-AUG-18:50 | 30.87 | 15.58 | 0.117814E+09 | 72.09 | 18-AUG-22:10 | 23.98 | 12.16 |
September | 0.160086E+10 | 960.20 | 13-SEP-20:00 | 23.90 | 12.88 | 0.113143E+09 | 70.05 | 01-SEP-22:10 | 23.90 | 12.88 |
October | 0.102124E+10 | 876.93 | 06-OCT-21:00 | 20.00 | 11.25 | 0.116751E+09 | 69.00 | 02-OCT-22:10 | 20.00 | 11.25 |
November | 0.389471E+09 | 572.74 | 02-NOV-21:00 | 12.80 | 4.93 | 0.112879E+09 | 68.58 | 18-NOV-00:00 | 7.20 | 0.41 |
December | 92731496.53 | 398.71 | 01-DEC-22:00 | 9.40 | 2.31 | 0.116692E+09 | 68.58 | 14-DEC-04:00 | -2.8 | -7.2 |
Annual Sum or Average | 0.122690E+11 | 0.137858E+10 | ||||||||
Minimum of Months | 92731496.53 | 338.06 | 4.08 | -1.2 | 0.105502E+09 | 68.58 | -2.8 | -7.2 | ||
Maximum of Months | 0.213833E+10 | 1150.11 | 35.73 | 16.72 | 0.117814E+09 | 73.30 | 27.85 | 14.98 |
Report: ZoneCoolingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.486977E+11 | 35623.46 | 03-JAN-21:00 | 3.90 | 0.12 | 0.510841E+09 | 381.93 | 24-JAN-22:10 | 0.73 | -3.6 |
February | 0.443846E+11 | 36179.52 | 14-FEB-21:00 | 10.00 | 3.10 | 0.461882E+09 | 381.93 | 10-FEB-22:10 | 10.00 | 3.10 |
March | 0.503749E+11 | 36299.27 | 08-MAR-21:00 | 13.90 | 5.15 | 0.513686E+09 | 387.84 | 13-MAR-21:10 | 11.88 | 3.50 |
April | 0.499734E+11 | 37031.62 | 28-APR-20:00 | 22.20 | 8.52 | 0.493964E+09 | 389.10 | 04-APR-21:10 | 22.20 | 8.52 |
May | 0.524652E+11 | 37212.18 | 19-MAY-20:00 | 25.60 | 9.31 | 0.510333E+09 | 387.79 | 03-MAY-21:10 | 25.60 | 9.31 |
June | 0.521263E+11 | 38014.37 | 28-JUN-20:00 | 30.00 | 16.25 | 0.493965E+09 | 381.92 | 09-JUN-21:10 | 30.00 | 16.25 |
July | 0.542195E+11 | 37914.53 | 20-JUL-20:00 | 30.60 | 14.01 | 0.506764E+09 | 381.86 | 28-JUL-21:10 | 24.82 | 14.46 |
August | 0.541352E+11 | 37799.92 | 17-AUG-20:00 | 28.30 | 14.86 | 0.510485E+09 | 381.97 | 04-AUG-21:10 | 28.30 | 14.86 |
September | 0.513163E+11 | 37300.49 | 13-SEP-20:00 | 23.90 | 12.88 | 0.492839E+09 | 381.95 | 08-SEP-21:10 | 23.90 | 12.88 |
October | 0.514369E+11 | 36952.32 | 06-OCT-20:00 | 19.40 | 11.28 | 0.510312E+09 | 389.06 | 16-OCT-21:10 | 12.38 | 5.43 |
November | 0.482316E+11 | 35995.65 | 01-NOV-20:00 | 7.80 | 4.71 | 0.494395E+09 | 384.49 | 02-NOV-21:10 | 12.33 | 5.44 |
December | 0.485152E+11 | 35665.68 | 01-DEC-21:00 | 9.40 | 2.54 | 0.510553E+09 | 381.92 | 29-DEC-22:10 | 2.12 | -1.4 |
Annual Sum or Average | 0.605877E+12 | 0.601002E+10 | ||||||||
Minimum of Months | 0.443846E+11 | 35623.46 | 3.90 | 0.12 | 0.461882E+09 | 381.86 | 0.73 | -3.6 | ||
Maximum of Months | 0.542195E+11 | 38014.37 | 30.60 | 16.25 | 0.513686E+09 | 389.10 | 30.00 | 16.25 |
Report: ZoneCoolingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.229390E+11 | 16583.28 | 01-JAN-11:35 | 9.83 | 3.02 | 0.828460E+10 | 5084.85 | 09-JAN-22:19 | 6.50 | 0.58 |
February | 0.216584E+11 | 16231.58 | 14-FEB-11:35 | 16.47 | 5.70 | 0.749750E+10 | 5265.31 | 14-FEB-22:19 | 10.60 | 3.54 |
March | 0.240260E+11 | 15418.24 | 11-MAR-11:35 | 12.57 | 3.35 | 0.829052E+10 | 5198.35 | 08-MAR-22:19 | 12.57 | 3.35 |
April | 0.245157E+11 | 14151.64 | 01-APR-10:35 | 17.97 | 5.88 | 0.799891E+10 | 5312.18 | 13-APR-21:30 | 19.70 | 7.05 |
May | 0.251285E+11 | 12978.46 | 19-MAY-18:10 | 29.03 | 11.19 | 0.826246E+10 | 5299.34 | 19-MAY-21:30 | 22.75 | 7.99 |
June | 0.264174E+11 | 14240.59 | 28-JUN-18:10 | 34.03 | 16.72 | 0.811880E+10 | 5461.44 | 27-JUN-21:40 | 34.03 | 16.72 |
July | 0.292742E+11 | 14517.50 | 20-JUL-18:03 | 35.73 | 14.77 | 0.844657E+10 | 5511.27 | 21-JUL-21:40 | 28.87 | 14.66 |
August | 0.302074E+11 | 14395.01 | 17-AUG-18:10 | 31.93 | 16.45 | 0.855108E+10 | 5499.84 | 21-AUG-21:40 | 25.97 | 14.84 |
September | 0.292010E+11 | 15736.74 | 03-SEP-10:35 | 28.53 | 16.32 | 0.827186E+10 | 5479.53 | 28-SEP-21:30 | 20.25 | 11.80 |
October | 0.284947E+11 | 16378.53 | 01-OCT-10:35 | 22.97 | 13.29 | 0.851399E+10 | 5484.48 | 06-OCT-21:30 | 19.70 | 11.19 |
November | 0.249732E+11 | 16696.94 | 19-NOV-11:35 | 8.87 | 1.47 | 0.807377E+10 | 5213.10 | 02-NOV-21:19 | 8.87 | 1.47 |
December | 0.234702E+11 | 16272.28 | 31-DEC-11:35 | 5.17 | -0.9 | 0.829265E+10 | 5009.97 | 29-DEC-22:19 | 5.17 | -0.9 |
Annual Sum or Average | 0.310306E+12 | 0.986027E+11 | ||||||||
Minimum of Months | 0.216584E+11 | 12978.46 | 5.17 | -0.9 | 0.749750E+10 | 5009.97 | 5.17 | -0.9 | ||
Maximum of Months | 0.302074E+11 | 16696.94 | 35.73 | 16.72 | 0.855108E+10 | 5511.27 | 34.03 | 16.72 |
Report: ZoneCoolingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.723883E+11 | 39754.13 | 01-JAN-11:35 | 9.83 | 3.02 | 0.243857E+11 | 15357.93 | 09-JAN-22:40 | 6.30 | 0.49 |
February | 0.675067E+11 | 38428.61 | 14-FEB-21:00 | 10.00 | 3.10 | 0.221078E+11 | 15730.82 | 14-FEB-22:40 | 10.60 | 3.54 |
March | 0.770483E+11 | 39443.05 | 09-MAR-19:04 | 11.83 | 2.95 | 0.247025E+11 | 15695.30 | 08-MAR-22:40 | 11.83 | 2.95 |
April | 0.785855E+11 | 42206.93 | 13-APR-18:10 | 24.45 | 9.49 | 0.240938E+11 | 16084.01 | 13-APR-21:40 | 19.23 | 6.82 |
May | 0.828943E+11 | 43033.91 | 15-MAY-18:10 | 27.85 | 10.46 | 0.250816E+11 | 16217.47 | 19-MAY-21:40 | 22.57 | 7.89 |
June | 0.863515E+11 | 46124.93 | 28-JUN-18:10 | 34.03 | 16.72 | 0.246911E+11 | 16552.18 | 27-JUN-21:49 | 34.03 | 16.72 |
July | 0.932801E+11 | 46404.79 | 20-JUL-18:10 | 35.73 | 14.77 | 0.255830E+11 | 16667.01 | 21-JUL-21:49 | 28.58 | 14.64 |
August | 0.940861E+11 | 45746.42 | 17-AUG-18:10 | 31.93 | 16.45 | 0.257315E+11 | 16569.09 | 18-AUG-21:49 | 24.27 | 12.29 |
September | 0.892518E+11 | 43893.34 | 13-SEP-18:10 | 26.93 | 13.80 | 0.246210E+11 | 16351.32 | 29-SEP-21:40 | 20.20 | 11.97 |
October | 0.863993E+11 | 42458.01 | 05-OCT-18:10 | 23.67 | 10.39 | 0.250619E+11 | 16314.14 | 06-OCT-21:40 | 19.60 | 11.17 |
November | 0.765035E+11 | 41074.22 | 23-NOV-11:35 | 11.10 | 3.58 | 0.238051E+11 | 15758.74 | 02-NOV-21:40 | 11.10 | 3.58 |
December | 0.729059E+11 | 38885.18 | 31-DEC-11:35 | 5.17 | -0.9 | 0.243769E+11 | 15268.65 | 29-DEC-22:40 | 5.17 | -0.9 |
Annual Sum or Average | 0.977201E+12 | 0.294242E+12 | ||||||||
Minimum of Months | 0.675067E+11 | 38428.61 | 5.17 | -0.9 | 0.221078E+11 | 15268.65 | 5.17 | -0.9 | ||
Maximum of Months | 0.940861E+11 | 46404.79 | 35.73 | 16.72 | 0.257315E+11 | 16667.01 | 34.03 | 16.72 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.459192E+09 | 4612.90 | 09-JAN-16:01 | 14.45 | 4.55 | 96333764.96 | 56.69 | 09-JAN-22:19 | 6.50 | 0.58 |
February | 0.596146E+09 | 4706.95 | 13-FEB-16:01 | 21.52 | 7.11 | 87591538.99 | 56.69 | 14-FEB-23:19 | 10.40 | 3.51 |
March | 0.871657E+09 | 4724.23 | 07-MAR-16:01 | 21.52 | 8.96 | 97733037.11 | 56.69 | 30-MAR-22:10 | 9.50 | 4.17 |
April | 0.147435E+10 | 4742.42 | 13-APR-15:01 | 25.10 | 9.79 | 95236103.16 | 56.69 | 20-APR-21:40 | 13.90 | 5.51 |
May | 0.178153E+10 | 4734.24 | 19-MAY-15:01 | 30.00 | 12.76 | 98560583.97 | 56.69 | 17-MAY-23:00 | 30.00 | 12.76 |
June | 0.246828E+10 | 4753.89 | 11-JUN-18:01 | 27.33 | 12.53 | 95748532.67 | 56.70 | 29-JUN-02:30 | 23.60 | 14.82 |
July | 0.285097E+10 | 4750.66 | 21-JUL-18:02 | 35.82 | 14.43 | 99031317.37 | 56.70 | 03-JUL-23:40 | 35.82 | 14.43 |
August | 0.283709E+10 | 4767.42 | 20-AUG-18:01 | 33.67 | 15.16 | 99091035.36 | 56.70 | 25-AUG-21:00 | 16.10 | 15.01 |
September | 0.233951E+10 | 4792.30 | 27-SEP-15:01 | 29.32 | 12.99 | 95651393.62 | 56.70 | 06-SEP-22:10 | 29.32 | 12.99 |
October | 0.166439E+10 | 4789.80 | 05-OCT-15:01 | 26.70 | 12.29 | 98295292.26 | 56.70 | 10-OCT-21:49 | 20.00 | 14.12 |
November | 0.740688E+09 | 4669.33 | 02-NOV-15:01 | 17.12 | 9.39 | 94357331.91 | 56.69 | 01-NOV-01:30 | 17.12 | 9.39 |
December | 0.419020E+09 | 4598.13 | 30-DEC-16:01 | 10.82 | 2.31 | 96252703.32 | 56.69 | 01-DEC-22:19 | 10.82 | 2.31 |
Annual Sum or Average | 0.185028E+11 | 0.115388E+10 | ||||||||
Minimum of Months | 0.419020E+09 | 4598.13 | 10.82 | 2.31 | 87591538.99 | 56.69 | 6.50 | 0.58 | ||
Maximum of Months | 0.285097E+10 | 4792.30 | 35.82 | 15.16 | 99091035.36 | 56.70 | 35.82 | 15.01 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.142537E+09 | 4453.10 | 01-JAN-16:01 | 14.95 | 5.48 | 94398178.09 | 56.69 | 31-JAN-00:10 | 2.62 | 0.23 |
February | 0.250310E+09 | 4561.22 | 13-FEB-16:01 | 21.52 | 7.11 | 86036002.70 | 56.69 | 14-FEB-22:19 | 10.60 | 3.54 |
March | 0.510821E+09 | 4599.55 | 07-MAR-16:01 | 21.52 | 8.96 | 96733306.80 | 56.69 | 30-MAR-21:10 | 10.40 | 4.53 |
April | 0.119566E+10 | 4651.14 | 13-APR-15:01 | 25.10 | 9.79 | 94830707.95 | 56.69 | 17-APR-21:49 | 14.37 | 3.99 |
May | 0.167063E+10 | 4690.93 | 20-MAY-18:01 | 26.23 | 10.63 | 98446380.91 | 56.69 | 21-MAY-01:10 | 18.03 | 11.06 |
June | 0.246988E+10 | 4721.90 | 11-JUN-18:01 | 27.33 | 12.53 | 95761560.77 | 56.70 | 29-JUN-02:30 | 23.60 | 14.82 |
July | 0.277780E+10 | 4713.62 | 21-JUL-18:02 | 35.82 | 14.43 | 99040633.25 | 56.70 | 03-JUL-23:40 | 35.82 | 14.43 |
August | 0.259563E+10 | 4069.16 | 10-AUG-08:61 | 21.88 | 15.28 | 99054679.20 | 56.70 | 21-AUG-01:00 | 23.90 | 16.21 |
September | 0.187273E+10 | 4674.59 | 27-SEP-15:01 | 29.32 | 12.99 | 95484666.24 | 56.70 | 01-SEP-22:10 | 29.32 | 12.99 |
October | 0.104863E+10 | 4666.59 | 05-OCT-15:01 | 26.70 | 12.29 | 97416008.23 | 56.69 | 03-OCT-01:10 | 26.70 | 12.29 |
November | 0.253736E+09 | 4529.88 | 02-NOV-15:01 | 17.12 | 9.39 | 92737377.57 | 56.69 | 02-NOV-21:00 | 10.00 | 7.26 |
December | 0.116865E+09 | 4436.89 | 29-DEC-16:01 | 11.42 | 3.74 | 94018948.40 | 56.69 | 01-DEC-22:19 | 11.42 | 3.74 |
Annual Sum or Average | 0.149052E+11 | 0.114396E+10 | ||||||||
Minimum of Months | 0.116865E+09 | 4069.16 | 11.42 | 3.74 | 86036002.70 | 56.69 | 2.62 | 0.23 | ||
Maximum of Months | 0.277780E+10 | 4721.90 | 35.82 | 15.28 | 99054679.20 | 56.70 | 35.82 | 16.21 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.704494E+09 | 902.82 | 01-JAN-14:00 | 15.60 | 5.65 | 0.00 | 0.00 | 01-JAN-00:10 | 15.60 | 5.65 |
February | 0.652566E+09 | 922.93 | 14-FEB-13:00 | 19.40 | 6.65 | 0.00 | 0.00 | 01-FEB-00:10 | 19.40 | 6.65 |
March | 0.644472E+09 | 805.38 | 08-MAR-13:30 | 21.40 | 9.29 | 0.00 | 0.00 | 01-MAR-00:10 | 21.40 | 9.29 |
April | 0.647915E+09 | 633.27 | 13-APR-13:20 | 24.07 | 9.13 | 0.00 | 0.00 | 01-APR-00:10 | 24.07 | 9.13 |
May | 0.636643E+09 | 494.74 | 13-MAY-13:10 | 28.40 | 11.85 | 0.00 | 0.00 | 01-MAY-00:10 | 28.40 | 11.85 |
June | 0.758267E+09 | 523.78 | 28-JUN-19:10 | 31.83 | 17.06 | 0.00 | 0.00 | 01-JUN-00:10 | 31.83 | 17.06 |
July | 0.943721E+09 | 577.42 | 23-JUL-13:30 | 36.15 | 17.47 | 0.00 | 0.00 | 01-JUL-00:10 | 36.15 | 17.47 |
August | 0.100901E+10 | 704.25 | 22-AUG-13:30 | 31.40 | 16.68 | 0.00 | 0.00 | 01-AUG-00:10 | 31.40 | 16.68 |
September | 0.101615E+10 | 875.72 | 28-SEP-13:20 | 29.27 | 15.43 | 0.00 | 0.00 | 01-SEP-00:10 | 29.27 | 15.43 |
October | 0.998478E+09 | 934.97 | 19-OCT-12:30 | 20.55 | 8.60 | 0.00 | 0.00 | 01-OCT-00:10 | 20.55 | 8.60 |
November | 0.835872E+09 | 916.55 | 20-NOV-12:10 | 12.88 | 3.87 | 0.00 | 0.00 | 01-NOV-00:10 | 12.88 | 3.87 |
December | 0.746143E+09 | 913.67 | 31-DEC-13:40 | 9.43 | 1.41 | 0.00 | 0.00 | 01-DEC-00:10 | 9.43 | 1.41 |
Annual Sum or Average | 0.959373E+10 | 0.00 | ||||||||
Minimum of Months | 0.636643E+09 | 494.74 | 9.43 | 1.41 | 0.00 | 0.00 | 9.43 | 1.41 | ||
Maximum of Months | 0.101615E+10 | 934.97 | 36.15 | 17.47 | 0.00 | 0.00 | 36.15 | 17.47 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.147381E+09 | 936.59 | 05-JAN-19:01 | 7.52 | 1.62 | 94919270.94 | 56.69 | 31-JAN-00:10 | 2.62 | 0.23 |
February | 0.192929E+09 | 1318.69 | 15-FEB-19:01 | 9.50 | 2.34 | 86203409.37 | 56.69 | 15-FEB-22:30 | 6.40 | 2.29 |
March | 0.382655E+09 | 1368.07 | 27-MAR-15:01 | 18.40 | 7.10 | 96613379.58 | 56.69 | 28-MAR-21:10 | 7.62 | 6.20 |
April | 0.600788E+09 | 1460.21 | 29-APR-18:01 | 23.53 | 8.85 | 94338658.26 | 56.69 | 07-APR-21:30 | 23.53 | 8.85 |
May | 0.799040E+09 | 1469.24 | 31-MAY-18:01 | 27.02 | 10.18 | 98075032.40 | 56.69 | 31-MAY-21:10 | 21.53 | 8.50 |
June | 0.103206E+10 | 1472.91 | 11-JUN-18:01 | 27.33 | 12.53 | 95548294.76 | 56.70 | 23-JUN-21:40 | 26.30 | 15.96 |
July | 0.114932E+10 | 1473.10 | 03-JUL-15:01 | 34.08 | 14.69 | 98839726.87 | 56.70 | 21-JUL-22:10 | 27.85 | 14.51 |
August | 0.105311E+10 | 1475.37 | 20-AUG-18:01 | 33.67 | 15.16 | 98757467.67 | 56.70 | 09-AUG-21:10 | 33.67 | 15.16 |
September | 0.815021E+09 | 1467.87 | 30-SEP-15:01 | 27.30 | 13.20 | 95012423.28 | 56.69 | 11-SEP-21:10 | 27.30 | 13.20 |
October | 0.538095E+09 | 1462.45 | 01-OCT-15:01 | 28.40 | 12.95 | 96981867.27 | 56.69 | 03-OCT-00:30 | 17.75 | 13.38 |
November | 0.268836E+09 | 1341.97 | 02-NOV-18:01 | 15.00 | 8.23 | 92831011.36 | 56.69 | 09-NOV-22:10 | 8.43 | 6.92 |
December | 0.134127E+09 | 1018.03 | 01-DEC-19:02 | 11.52 | 3.77 | 94530237.48 | 56.69 | 01-DEC-22:19 | 8.50 | 2.01 |
Annual Sum or Average | 0.711336E+10 | 0.114265E+10 | ||||||||
Minimum of Months | 0.134127E+09 | 936.59 | 7.52 | 1.62 | 86203409.37 | 56.69 | 2.62 | 0.23 | ||
Maximum of Months | 0.114932E+10 | 1475.37 | 34.08 | 15.16 | 98839726.87 | 56.70 | 33.67 | 15.96 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.449483E+09 | 4158.94 | 26-JAN-09:01 | -0.6 | -5.0 | 96658323.16 | 56.69 | 09-JAN-22:19 | -0.6 | -5.0 |
February | 0.543094E+09 | 4172.18 | 09-FEB-09:01 | 1.47 | -1.3 | 87861802.77 | 56.69 | 14-FEB-23:19 | 10.40 | 3.51 |
March | 0.945669E+09 | 4174.02 | 04-MAR-09:01 | 2.15 | -2.2 | 98221149.10 | 56.69 | 30-MAR-21:40 | 9.80 | 4.32 |
April | 0.166919E+10 | 4199.09 | 29-APR-08:61 | 15.37 | 5.61 | 95765744.99 | 56.69 | 17-APR-22:10 | 15.37 | 5.61 |
May | 0.197203E+10 | 4171.96 | 14-MAY-08:62 | 19.27 | 8.83 | 99034901.20 | 56.69 | 21-MAY-00:00 | 18.30 | 10.90 |
June | 0.267620E+10 | 4269.82 | 17-JUN-08:61 | 24.87 | 12.27 | 95955477.69 | 56.70 | 24-JUN-01:39 | 23.67 | 15.60 |
July | 0.311557E+10 | 4187.40 | 03-JUL-15:01 | 34.08 | 14.69 | 99127070.07 | 56.70 | 26-JUL-00:20 | 21.10 | 16.73 |
August | 0.302843E+10 | 4186.69 | 20-AUG-18:01 | 33.67 | 15.16 | 99229627.50 | 56.70 | 08-AUG-23:00 | 33.67 | 15.16 |
September | 0.240113E+10 | 4192.42 | 27-SEP-15:01 | 29.32 | 12.99 | 95872405.30 | 56.70 | 01-SEP-00:10 | 29.32 | 12.99 |
October | 0.167909E+10 | 4198.34 | 01-OCT-15:01 | 28.40 | 12.95 | 98618446.89 | 56.70 | 10-OCT-22:10 | 19.72 | 14.02 |
November | 0.743611E+09 | 4188.47 | 19-NOV-09:01 | 2.57 | -1.8 | 94724346.26 | 56.69 | 01-NOV-01:30 | 2.57 | -1.8 |
December | 0.409459E+09 | 4189.57 | 31-DEC-09:01 | -0.3 | -4.0 | 96588395.70 | 56.69 | 01-DEC-22:19 | -0.3 | -4.0 |
Annual Sum or Average | 0.196329E+11 | 0.115766E+10 | ||||||||
Minimum of Months | 0.409459E+09 | 4158.94 | -0.6 | -5.0 | 87861802.77 | 56.69 | -0.6 | -5.0 | ||
Maximum of Months | 0.311557E+10 | 4269.82 | 34.08 | 15.16 | 99229627.50 | 56.70 | 33.67 | 16.73 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.140375E+09 | 3543.37 | 01-JAN-09:01 | 2.67 | -1.3 | 94359149.72 | 56.69 | 31-JAN-00:10 | 2.62 | 0.23 |
February | 0.208597E+09 | 4056.29 | 14-FEB-09:01 | 7.25 | 1.90 | 86013639.65 | 56.69 | 14-FEB-22:19 | 10.60 | 3.54 |
March | 0.545126E+09 | 4098.01 | 04-MAR-09:01 | 2.15 | -2.2 | 97480633.18 | 56.69 | 08-MAR-22:19 | 10.53 | 4.18 |
April | 0.136388E+10 | 4160.77 | 29-APR-08:61 | 15.37 | 5.61 | 95643031.10 | 56.69 | 17-APR-21:30 | 15.37 | 5.61 |
May | 0.185207E+10 | 4139.40 | 14-MAY-08:62 | 19.27 | 8.83 | 99006353.93 | 56.69 | 21-MAY-00:40 | 19.07 | 9.98 |
June | 0.267439E+10 | 4242.23 | 17-JUN-08:61 | 24.87 | 12.27 | 95953010.48 | 56.70 | 24-JUN-01:39 | 23.67 | 15.60 |
July | 0.303962E+10 | 4151.00 | 03-JUL-15:01 | 34.08 | 14.69 | 99126694.06 | 56.70 | 03-JUL-23:40 | 24.80 | 15.35 |
August | 0.278139E+10 | 4146.26 | 20-AUG-18:01 | 33.67 | 15.16 | 99225867.29 | 56.70 | 25-AUG-22:10 | 16.20 | 15.16 |
September | 0.191811E+10 | 4118.06 | 21-SEP-08:62 | 18.77 | 10.46 | 95837970.28 | 56.70 | 11-SEP-21:10 | 18.77 | 10.46 |
October | 0.102567E+10 | 4107.39 | 01-OCT-15:01 | 28.40 | 12.95 | 98044302.33 | 56.69 | 02-OCT-21:10 | 18.30 | 14.29 |
November | 0.265162E+09 | 4078.09 | 19-NOV-09:01 | 2.57 | -1.8 | 92809458.65 | 56.69 | 01-NOV-00:40 | 2.57 | -1.8 |
December | 0.127815E+09 | 3657.38 | 30-DEC-09:01 | 1.15 | -2.7 | 93804531.60 | 56.69 | 01-DEC-22:19 | 1.15 | -2.7 |
Annual Sum or Average | 0.159422E+11 | 0.114730E+10 | ||||||||
Minimum of Months | 0.127815E+09 | 3543.37 | 1.15 | -2.7 | 86013639.65 | 56.69 | 1.15 | -2.7 | ||
Maximum of Months | 0.303962E+10 | 4242.23 | 34.08 | 15.16 | 99225867.29 | 56.70 | 24.80 | 15.60 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.296082E+10 | 2455.35 | 01-JAN-11:35 | 9.83 | 3.02 | 0.119945E+10 | 704.87 | 09-JAN-22:19 | 6.50 | 0.58 |
February | 0.308642E+10 | 2578.72 | 14-FEB-11:35 | 16.47 | 5.70 | 0.108591E+10 | 728.73 | 14-FEB-22:40 | 10.60 | 3.54 |
March | 0.419462E+10 | 2573.76 | 08-MAR-11:35 | 17.07 | 7.88 | 0.120833E+10 | 729.36 | 08-MAR-22:30 | 9.70 | 3.76 |
April | 0.503905E+10 | 2867.12 | 29-APR-10:35 | 20.20 | 8.15 | 0.117990E+10 | 754.21 | 13-APR-21:40 | 20.20 | 8.15 |
May | 0.559623E+10 | 2934.16 | 20-MAY-10:35 | 22.40 | 8.51 | 0.123374E+10 | 768.56 | 19-MAY-21:40 | 22.40 | 8.51 |
June | 0.614203E+10 | 3258.92 | 29-JUN-10:35 | 32.60 | 16.86 | 0.124757E+10 | 813.67 | 29-JUN-21:40 | 24.47 | 13.56 |
July | 0.673046E+10 | 3323.32 | 23-JUL-10:35 | 31.83 | 17.15 | 0.132203E+10 | 819.09 | 21-JUL-21:49 | 31.83 | 17.15 |
August | 0.670082E+10 | 3307.56 | 20-AUG-10:40 | 30.17 | 17.03 | 0.132857E+10 | 817.93 | 21-AUG-21:40 | 25.97 | 14.84 |
September | 0.611462E+10 | 3202.01 | 03-SEP-10:35 | 28.53 | 16.32 | 0.124889E+10 | 789.78 | 29-SEP-21:40 | 20.20 | 11.97 |
October | 0.542620E+10 | 3082.80 | 01-OCT-10:35 | 22.97 | 13.29 | 0.124624E+10 | 790.44 | 06-OCT-21:40 | 19.60 | 11.17 |
November | 0.399984E+10 | 2666.40 | 01-NOV-10:35 | 13.13 | 7.69 | 0.116314E+10 | 728.42 | 01-NOV-21:40 | 8.13 | 4.88 |
December | 0.289847E+10 | 2414.63 | 30-DEC-11:35 | 7.77 | 1.25 | 0.119910E+10 | 704.51 | 04-DEC-02:39 | 7.77 | 1.25 |
Annual Sum or Average | 0.588896E+11 | 0.146628E+11 | ||||||||
Minimum of Months | 0.289847E+10 | 2414.63 | 7.77 | 1.25 | 0.108591E+10 | 704.51 | 6.50 | 0.58 | ||
Maximum of Months | 0.673046E+10 | 3323.32 | 32.60 | 17.15 | 0.132857E+10 | 819.09 | 31.83 | 17.15 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.436298E+09 | 4953.10 | 09-JAN-16:01 | 14.45 | 4.55 | 95965541.57 | 56.69 | 09-JAN-22:19 | 6.50 | 0.58 |
February | 0.602674E+09 | 5065.71 | 13-FEB-16:01 | 21.52 | 7.11 | 87363495.80 | 56.69 | 14-FEB-22:00 | 10.60 | 3.54 |
March | 0.911970E+09 | 5079.89 | 07-MAR-16:01 | 21.52 | 8.96 | 97584010.97 | 56.69 | 30-MAR-21:49 | 9.60 | 4.25 |
April | 0.163588E+10 | 5114.68 | 13-APR-15:01 | 25.10 | 9.79 | 95209246.67 | 56.69 | 17-APR-22:10 | 13.62 | 3.75 |
May | 0.203122E+10 | 5107.66 | 20-MAY-15:01 | 26.78 | 10.96 | 98594729.70 | 56.69 | 21-MAY-01:10 | 18.03 | 11.06 |
June | 0.285088E+10 | 5135.49 | 21-JUN-15:01 | 34.08 | 14.64 | 95802004.41 | 56.70 | 29-JUN-02:20 | 23.87 | 14.88 |
July | 0.328955E+10 | 5135.56 | 21-JUL-18:02 | 35.82 | 14.43 | 99056066.19 | 56.70 | 28-JUL-23:49 | 22.30 | 16.88 |
August | 0.323752E+10 | 4359.53 | 18-AUG-08:61 | 24.55 | 15.85 | 99126224.34 | 56.70 | 24-AUG-21:49 | 18.90 | 15.21 |
September | 0.260032E+10 | 5163.13 | 27-SEP-15:01 | 29.32 | 12.99 | 95631039.98 | 56.70 | 11-SEP-21:10 | 29.32 | 12.99 |
October | 0.177228E+10 | 5167.10 | 05-OCT-15:01 | 26.70 | 12.29 | 98186811.54 | 56.70 | 02-OCT-21:10 | 26.70 | 12.29 |
November | 0.721979E+09 | 5017.34 | 02-NOV-15:01 | 17.12 | 9.39 | 94126842.23 | 56.69 | 02-NOV-21:49 | 10.47 | 6.98 |
December | 0.381672E+09 | 4942.22 | 31-DEC-16:01 | 9.82 | 1.41 | 95850859.12 | 56.69 | 01-DEC-22:19 | 9.82 | 1.41 |
Annual Sum or Average | 0.204722E+11 | 0.115250E+10 | ||||||||
Minimum of Months | 0.381672E+09 | 4359.53 | 9.82 | 1.41 | 87363495.80 | 56.69 | 6.50 | 0.58 | ||
Maximum of Months | 0.328955E+10 | 5167.10 | 35.82 | 15.85 | 99126224.34 | 56.70 | 29.32 | 16.88 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.126928E+09 | 4749.45 | 01-JAN-16:01 | 14.95 | 5.48 | 94005447.92 | 56.69 | 09-JAN-22:19 | 6.50 | 0.58 |
February | 0.243016E+09 | 4885.70 | 13-FEB-16:01 | 21.52 | 7.11 | 85793620.19 | 56.69 | 14-FEB-22:10 | 10.60 | 3.54 |
March | 0.532235E+09 | 4927.64 | 07-MAR-16:01 | 21.52 | 8.96 | 96631441.70 | 56.69 | 30-MAR-21:10 | 10.40 | 4.53 |
April | 0.133128E+10 | 5006.16 | 13-APR-15:01 | 25.10 | 9.79 | 94907916.33 | 56.69 | 17-APR-21:10 | 16.23 | 4.42 |
May | 0.190869E+10 | 5054.82 | 20-MAY-18:01 | 26.23 | 10.63 | 98525652.60 | 56.69 | 21-MAY-00:00 | 18.30 | 10.90 |
June | 0.284960E+10 | 5091.37 | 11-JUN-18:01 | 27.33 | 12.53 | 95822893.79 | 56.70 | 24-JUN-01:00 | 23.30 | 15.36 |
July | 0.321114E+10 | 5088.08 | 21-JUL-18:02 | 35.82 | 14.43 | 99067996.81 | 56.70 | 03-JUL-23:40 | 35.82 | 14.43 |
August | 0.298004E+10 | 4311.47 | 24-AUG-18:01 | 21.52 | 15.15 | 99088868.87 | 56.70 | 21-AUG-01:00 | 21.52 | 15.15 |
September | 0.209838E+10 | 5022.84 | 27-SEP-15:01 | 29.32 | 12.99 | 95511532.83 | 56.70 | 01-SEP-22:10 | 29.32 | 12.99 |
October | 0.110919E+10 | 5019.16 | 05-OCT-15:01 | 26.70 | 12.29 | 97407744.04 | 56.69 | 03-OCT-00:30 | 26.70 | 12.29 |
November | 0.235082E+09 | 4845.90 | 02-NOV-15:01 | 17.12 | 9.39 | 92439570.08 | 56.69 | 02-NOV-21:00 | 10.00 | 7.26 |
December | 95277614.01 | 4731.23 | 30-DEC-16:01 | 10.82 | 2.31 | 93597849.43 | 56.69 | 02-DEC-00:10 | 10.82 | 2.31 |
Annual Sum or Average | 0.167209E+11 | 0.114280E+10 | ||||||||
Minimum of Months | 95277614.01 | 4311.47 | 10.82 | 2.31 | 85793620.19 | 56.69 | 6.50 | 0.58 | ||
Maximum of Months | 0.321114E+10 | 5091.37 | 35.82 | 15.15 | 99088868.87 | 56.70 | 35.82 | 15.36 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.903129E+09 | 2418.15 | 03-JAN-16:01 | 14.53 | 5.76 | 97678785.82 | 56.69 | 09-JAN-22:00 | 6.10 | 0.40 |
February | 0.881714E+09 | 2450.38 | 13-FEB-16:01 | 21.52 | 7.11 | 88535804.81 | 56.69 | 15-FEB-00:40 | 9.60 | 3.36 |
March | 0.901208E+09 | 2432.75 | 12-MAR-15:01 | 19.90 | 6.21 | 98260501.53 | 56.69 | 30-MAR-21:00 | 9.40 | 4.18 |
April | 0.102719E+10 | 2427.98 | 01-APR-15:01 | 24.40 | 8.92 | 95358545.81 | 56.69 | 17-APR-22:40 | 12.77 | 3.40 |
May | 0.107404E+10 | 2402.21 | 19-MAY-15:01 | 30.00 | 12.76 | 98597125.25 | 56.69 | 26-MAY-21:10 | 17.62 | 10.50 |
June | 0.137960E+10 | 2408.27 | 21-JUN-15:01 | 34.08 | 14.64 | 95750177.84 | 56.69 | 29-JUN-04:40 | 24.40 | 15.72 |
July | 0.174358E+10 | 2402.28 | 21-JUL-15:02 | 37.70 | 15.25 | 99026900.17 | 56.70 | 12-JUL-21:10 | 37.70 | 15.25 |
August | 0.184920E+10 | 2141.69 | 24-AUG-18:01 | 21.52 | 15.15 | 99076470.99 | 56.70 | 14-AUG-21:10 | 21.52 | 15.15 |
September | 0.177700E+10 | 2467.84 | 27-SEP-15:01 | 29.32 | 12.99 | 95708949.99 | 56.70 | 06-SEP-23:00 | 29.32 | 12.99 |
October | 0.161219E+10 | 2477.10 | 05-OCT-15:01 | 26.70 | 12.29 | 98667855.51 | 56.69 | 03-OCT-00:40 | 26.70 | 12.29 |
November | 0.116720E+10 | 2423.41 | 01-NOV-15:01 | 12.43 | 7.32 | 95296365.29 | 56.69 | 01-NOV-00:49 | 12.43 | 7.32 |
December | 0.978957E+09 | 2417.45 | 31-DEC-16:01 | 9.82 | 1.41 | 97637085.91 | 56.69 | 01-DEC-23:19 | 9.82 | 1.41 |
Annual Sum or Average | 0.152950E+11 | 0.115959E+10 | ||||||||
Minimum of Months | 0.881714E+09 | 2141.69 | 9.82 | 1.41 | 88535804.81 | 56.69 | 6.10 | 0.40 | ||
Maximum of Months | 0.184920E+10 | 2477.10 | 37.70 | 15.25 | 99076470.99 | 56.70 | 37.70 | 15.72 |
Report: ZoneCoolingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.378051E+11 | 18618.62 | 09-JAN-23:00 | 6.10 | 0.40 | 0.148349E+11 | 9645.72 | 09-JAN-23:10 | 5.82 | 0.25 |
February | 0.353355E+11 | 19291.18 | 14-FEB-23:00 | 10.60 | 3.54 | 0.134959E+11 | 9878.05 | 14-FEB-23:10 | 10.50 | 3.53 |
March | 0.417168E+11 | 19580.88 | 13-MAR-18:10 | 17.62 | 6.15 | 0.152563E+11 | 9981.20 | 16-MAR-21:19 | 13.33 | 3.70 |
April | 0.434216E+11 | 21443.53 | 13-APR-18:10 | 24.45 | 9.49 | 0.149946E+11 | 10315.71 | 28-APR-22:10 | 19.40 | 6.69 |
May | 0.469639E+11 | 22426.89 | 31-MAY-18:10 | 27.02 | 10.18 | 0.157428E+11 | 10474.45 | 19-MAY-21:30 | 27.02 | 10.18 |
June | 0.485902E+11 | 24117.45 | 28-JUN-18:10 | 34.03 | 16.72 | 0.155983E+11 | 10757.68 | 27-JUN-21:40 | 34.03 | 16.72 |
July | 0.513669E+11 | 24322.09 | 20-JUL-18:10 | 35.73 | 14.77 | 0.161319E+11 | 10800.42 | 21-JUL-22:10 | 27.85 | 14.51 |
August | 0.505336E+11 | 23674.14 | 04-AUG-17:04 | 33.35 | 15.89 | 0.161383E+11 | 10631.46 | 17-AUG-22:10 | 26.93 | 14.57 |
September | 0.463267E+11 | 22038.33 | 13-SEP-18:10 | 26.93 | 13.80 | 0.152732E+11 | 10395.29 | 01-SEP-22:10 | 26.93 | 13.80 |
October | 0.437864E+11 | 20998.91 | 05-OCT-18:10 | 23.67 | 10.39 | 0.153902E+11 | 10257.64 | 06-OCT-22:10 | 19.22 | 11.09 |
November | 0.387323E+11 | 19479.88 | 08-NOV-23:00 | 12.20 | 6.07 | 0.145552E+11 | 9925.43 | 08-NOV-23:10 | 12.30 | 6.15 |
December | 0.373545E+11 | 18934.83 | 01-DEC-22:10 | 8.95 | 2.17 | 0.148125E+11 | 9758.16 | 01-DEC-22:19 | 8.50 | 2.01 |
Annual Sum or Average | 0.521933E+12 | 0.182224E+12 | ||||||||
Minimum of Months | 0.353355E+11 | 18618.62 | 6.10 | 0.40 | 0.134959E+11 | 9645.72 | 5.82 | 0.25 | ||
Maximum of Months | 0.513669E+11 | 24322.09 | 35.73 | 16.72 | 0.161383E+11 | 10800.42 | 34.03 | 16.72 |
Report: ZoneCoolingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.407318E+11 | 19766.69 | 05-JAN-23:00 | 2.80 | -1.4 | 0.149029E+11 | 9724.35 | 05-JAN-22:19 | 2.80 | -1.4 |
February | 0.380099E+11 | 20464.01 | 14-FEB-23:00 | 10.60 | 3.54 | 0.135618E+11 | 9955.69 | 14-FEB-23:10 | 10.50 | 3.53 |
March | 0.448165E+11 | 20794.57 | 13-MAR-18:10 | 17.62 | 6.15 | 0.153480E+11 | 10073.96 | 16-MAR-21:19 | 13.33 | 3.70 |
April | 0.465432E+11 | 22766.09 | 13-APR-18:10 | 24.45 | 9.49 | 0.151057E+11 | 10415.98 | 28-APR-22:10 | 19.40 | 6.69 |
May | 0.502564E+11 | 23830.72 | 31-MAY-18:10 | 27.02 | 10.18 | 0.158720E+11 | 10576.15 | 19-MAY-21:30 | 27.02 | 10.18 |
June | 0.518217E+11 | 25496.77 | 28-JUN-18:10 | 34.03 | 16.72 | 0.157239E+11 | 10836.67 | 27-JUN-21:40 | 34.03 | 16.72 |
July | 0.546532E+11 | 25716.27 | 20-JUL-18:10 | 35.73 | 14.77 | 0.162499E+11 | 10875.23 | 21-JUL-22:10 | 27.85 | 14.51 |
August | 0.537886E+11 | 25101.57 | 04-AUG-17:04 | 33.35 | 15.89 | 0.162499E+11 | 10708.82 | 17-AUG-22:10 | 26.93 | 14.57 |
September | 0.494125E+11 | 23341.88 | 13-SEP-18:10 | 26.93 | 13.80 | 0.153789E+11 | 10483.70 | 01-SEP-22:10 | 26.93 | 13.80 |
October | 0.468680E+11 | 22255.71 | 02-OCT-18:10 | 20.60 | 15.66 | 0.154826E+11 | 10339.09 | 06-OCT-22:10 | 19.22 | 11.09 |
November | 0.416179E+11 | 20698.93 | 08-NOV-23:00 | 12.20 | 6.07 | 0.146299E+11 | 10015.64 | 08-NOV-23:10 | 12.30 | 6.15 |
December | 0.402530E+11 | 20125.17 | 01-DEC-22:10 | 8.95 | 2.17 | 0.148782E+11 | 9847.12 | 01-DEC-22:19 | 8.50 | 2.01 |
Annual Sum or Average | 0.558773E+12 | 0.183384E+12 | ||||||||
Minimum of Months | 0.380099E+11 | 19766.69 | 2.80 | -1.4 | 0.135618E+11 | 9724.35 | 2.80 | -1.4 | ||
Maximum of Months | 0.546532E+11 | 25716.27 | 35.73 | 16.72 | 0.162499E+11 | 10875.23 | 34.03 | 16.72 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.511382E+11 | 27249.75 | 01-JAN-11:40 | 9.83 | 3.02 | 0.186193E+11 | 11319.59 | 14-JAN-18:19 | 3.30 | -2.2 |
February | 0.470598E+11 | 28249.12 | 14-FEB-11:40 | 16.47 | 5.70 | 0.168259E+11 | 11319.64 | 18-FEB-18:19 | 9.63 | 3.33 |
March | 0.541412E+11 | 29207.14 | 26-MAR-10:40 | 14.80 | 5.60 | 0.186487E+11 | 11330.35 | 11-MAR-18:49 | 14.80 | 5.60 |
April | 0.550355E+11 | 30474.60 | 29-APR-10:40 | 20.20 | 8.15 | 0.180615E+11 | 11319.72 | 08-APR-17:19 | 20.20 | 8.15 |
May | 0.582325E+11 | 30626.85 | 20-MAY-10:40 | 22.40 | 8.51 | 0.186713E+11 | 11319.72 | 06-MAY-17:19 | 22.40 | 8.51 |
June | 0.588150E+11 | 31557.29 | 29-JUN-10:40 | 32.60 | 16.86 | 0.180840E+11 | 11324.35 | 24-JUN-17:10 | 32.60 | 16.86 |
July | 0.618194E+11 | 31963.69 | 23-JUL-10:40 | 31.83 | 17.15 | 0.186848E+11 | 11359.80 | 22-JUL-17:40 | 31.83 | 17.15 |
August | 0.613621E+11 | 31869.04 | 20-AUG-10:40 | 30.17 | 17.03 | 0.186879E+11 | 11319.72 | 19-AUG-17:19 | 30.17 | 17.03 |
September | 0.574199E+11 | 31550.29 | 03-SEP-10:40 | 28.53 | 16.32 | 0.180712E+11 | 11320.33 | 02-SEP-17:00 | 28.53 | 16.32 |
October | 0.561644E+11 | 30533.36 | 01-OCT-10:50 | 23.43 | 13.48 | 0.186554E+11 | 11319.72 | 21-OCT-17:19 | 17.77 | 7.17 |
November | 0.512510E+11 | 28653.16 | 01-NOV-10:35 | 13.13 | 7.69 | 0.180337E+11 | 11319.64 | 18-NOV-18:19 | 10.20 | 1.74 |
December | 0.509227E+11 | 27120.00 | 30-DEC-11:40 | 7.77 | 1.25 | 0.186179E+11 | 11319.59 | 30-DEC-18:19 | 4.40 | -1.8 |
Annual Sum or Average | 0.663362E+12 | 0.219662E+12 | ||||||||
Minimum of Months | 0.470598E+11 | 27120.00 | 7.77 | 1.25 | 0.168259E+11 | 11319.59 | 3.30 | -2.2 | ||
Maximum of Months | 0.618194E+11 | 31963.69 | 32.60 | 17.15 | 0.186879E+11 | 11359.80 | 32.60 | 17.15 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.322838E+10 | 5469.59 | 23-JAN-13:40 | 13.87 | 4.00 | 0.126885E+10 | 745.76 | 04-JAN-03:30 | 13.87 | 4.00 |
February | 0.385893E+10 | 6420.71 | 14-FEB-11:35 | 16.47 | 5.70 | 0.114785E+10 | 745.76 | 08-FEB-02:09 | 16.47 | 5.70 |
March | 0.597086E+10 | 6431.29 | 08-MAR-11:35 | 17.07 | 7.88 | 0.127588E+10 | 745.76 | 23-MAR-03:09 | -0.3 | -2.1 |
April | 0.868323E+10 | 7104.41 | 28-APR-10:35 | 21.13 | 8.61 | 0.123248E+10 | 753.35 | 13-APR-21:40 | 21.13 | 8.61 |
May | 0.106658E+11 | 7210.97 | 20-MAY-10:35 | 22.40 | 8.51 | 0.127620E+10 | 766.20 | 19-MAY-21:30 | 22.40 | 8.51 |
June | 0.131996E+11 | 7964.43 | 29-JUN-10:35 | 32.60 | 16.86 | 0.126018E+10 | 821.07 | 28-JUN-21:40 | 32.60 | 16.86 |
July | 0.152014E+11 | 8027.78 | 22-JUL-10:35 | 33.33 | 17.03 | 0.130976E+10 | 827.57 | 21-JUL-21:40 | 33.33 | 17.03 |
August | 0.148213E+11 | 7889.01 | 04-AUG-17:04 | 33.35 | 15.89 | 0.131212E+10 | 809.52 | 21-AUG-21:40 | 25.97 | 14.84 |
September | 0.124719E+11 | 7767.16 | 03-SEP-10:35 | 28.53 | 16.32 | 0.124464E+10 | 774.97 | 13-SEP-21:40 | 21.30 | 12.37 |
October | 0.927190E+10 | 7306.99 | 01-OCT-10:35 | 22.97 | 13.29 | 0.127577E+10 | 759.37 | 06-OCT-21:40 | 19.60 | 11.17 |
November | 0.521022E+10 | 6311.79 | 23-NOV-11:35 | 11.10 | 3.58 | 0.122792E+10 | 745.76 | 06-NOV-03:20 | 11.10 | 3.58 |
December | 0.305094E+10 | 5431.49 | 31-DEC-13:50 | 9.72 | 1.51 | 0.126882E+10 | 745.83 | 27-DEC-01:00 | 9.72 | 1.51 |
Annual Sum or Average | 0.105634E+12 | 0.151005E+11 | ||||||||
Minimum of Months | 0.305094E+10 | 5431.49 | 9.72 | 1.51 | 0.114785E+10 | 745.76 | -0.3 | -2.1 | ||
Maximum of Months | 0.152014E+11 | 8027.78 | 33.35 | 17.03 | 0.131212E+10 | 827.57 | 33.33 | 17.03 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 2.30 |
February | 0.00 | 0.00 | 01-FEB-00:05 | -3.2 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 2.47 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 12.83 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 5.13 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -3.2 | |
Maximum of Months | 0.00 | 0.00 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.132308E+09 | 695.99 | 21-JAN-07:10 | -7.8 |
February | 63482936.11 | 652.53 | 04-FEB-07:10 | -6.6 |
March | 10765881.88 | 444.27 | 04-MAR-06:10 | -1.7 |
April | 54806.69 | 54.00 | 08-APR-06:10 | 1.78 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 |
October | 16461085.92 | 581.61 | 26-OCT-06:10 | -1.4 |
November | 12242311.28 | 261.97 | 12-NOV-06:00 | 0.60 |
December | 0.122233E+09 | 750.11 | 09-DEC-07:30 | -2.8 |
Annual Sum or Average | 0.357548E+09 | |||
Minimum of Months | 0.00 | 0.00 | -7.8 | |
Maximum of Months | 0.132308E+09 | 750.11 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 2.30 |
February | 0.00 | 0.00 | 01-FEB-00:05 | -3.2 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 2.47 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 12.83 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 5.13 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -3.2 | |
Maximum of Months | 0.00 | 0.00 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 31626699.43 | 256.95 | 20-JAN-04:40 | -4.6 |
February | 16180863.07 | 274.32 | 06-FEB-04:50 | -4.4 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 2.47 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 |
October | 1343.62 | 2.24 | 26-OCT-04:00 | -2.8 |
November | 975001.55 | 107.40 | 27-NOV-05:00 | -3.9 |
December | 28994918.06 | 277.19 | 15-DEC-05:00 | -9.4 |
Annual Sum or Average | 77778825.73 | |||
Minimum of Months | 0.00 | 0.00 | -9.4 | |
Maximum of Months | 31626699.43 | 277.19 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.141815E+09 | 281.27 | 21-JAN-07:10 | -7.8 |
February | 83508308.56 | 273.98 | 06-FEB-05:00 | -4.4 |
March | 5128258.62 | 122.28 | 05-MAR-06:00 | -2.8 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 |
October | 4729723.95 | 115.99 | 26-OCT-04:00 | -2.8 |
November | 13003529.88 | 163.09 | 27-NOV-05:00 | -3.9 |
December | 0.162026E+09 | 282.66 | 15-DEC-05:00 | -9.4 |
Annual Sum or Average | 0.410210E+09 | |||
Minimum of Months | 0.00 | 0.00 | -9.4 | |
Maximum of Months | 0.162026E+09 | 282.66 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 2.30 |
February | 0.00 | 0.00 | 01-FEB-00:05 | -3.2 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 2.47 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 12.83 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 5.13 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -3.2 | |
Maximum of Months | 0.00 | 0.00 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 2.30 |
February | 0.00 | 0.00 | 01-FEB-00:05 | -3.2 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 2.47 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 12.83 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 5.13 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -3.2 | |
Maximum of Months | 0.00 | 0.00 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 2.30 |
February | 0.00 | 0.00 | 01-FEB-00:05 | -3.2 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 2.47 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 12.83 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 5.13 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -3.2 | |
Maximum of Months | 0.00 | 0.00 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.436848E+09 | 1763.85 | 12-JAN-16:01 | 6.52 |
February | 0.280022E+09 | 1737.36 | 16-FEB-19:01 | 1.70 |
March | 0.108311E+09 | 1763.90 | 23-MAR-08:61 | 7.07 |
April | 15965724.76 | 1567.65 | 29-APR-08:03 | 15.37 |
May | 7198840.90 | 1263.22 | 04-MAY-15:03 | 12.20 |
June | 1452879.44 | 1077.60 | 03-JUN-08:03 | 19.08 |
July | 91091.79 | 240.10 | 08-JUL-08:04 | 21.38 |
August | 683063.92 | 806.34 | 31-AUG-08:03 | 20.87 |
September | 1350741.18 | 1016.36 | 09-SEP-08:03 | 15.18 |
October | 53510982.81 | 1753.94 | 25-OCT-18:01 | 3.30 |
November | 0.140796E+09 | 1730.72 | 10-NOV-19:02 | 6.10 |
December | 0.438572E+09 | 1744.54 | 07-DEC-16:02 | 8.03 |
Annual Sum or Average | 0.148480E+10 | |||
Minimum of Months | 91091.79 | 240.10 | 1.70 | |
Maximum of Months | 0.438572E+09 | 1763.90 | 21.38 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.739360E+09 | 1793.35 | 12-JAN-16:01 | 6.52 |
February | 0.481554E+09 | 1777.78 | 08-FEB-09:01 | 4.18 |
March | 0.184519E+09 | 1779.21 | 23-MAR-08:61 | 7.07 |
April | 25401515.86 | 1528.72 | 29-APR-08:03 | 15.37 |
May | 8014521.85 | 1173.27 | 03-MAY-15:03 | 18.62 |
June | 1476031.34 | 1122.15 | 03-JUN-08:03 | 19.08 |
July | 89946.64 | 213.20 | 08-JUL-08:04 | 21.38 |
August | 784696.20 | 953.00 | 31-AUG-08:03 | 20.87 |
September | 1796965.17 | 1169.44 | 24-SEP-08:03 | 15.28 |
October | 88656115.59 | 1772.43 | 26-OCT-08:61 | 1.97 |
November | 0.297862E+09 | 1760.44 | 24-NOV-09:01 | 6.47 |
December | 0.811285E+09 | 1784.31 | 07-DEC-16:02 | 8.03 |
Annual Sum or Average | 0.264080E+10 | |||
Minimum of Months | 89946.64 | 213.20 | 1.97 | |
Maximum of Months | 0.811285E+09 | 1793.35 | 21.38 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 565549.78 | 47.99 | 19-JAN-05:00 | -2.8 |
February | 0.00 | 0.00 | 01-FEB-00:05 | -3.2 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 2.47 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 12.83 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 5.13 |
Annual Sum or Average | 565549.78 | |||
Minimum of Months | 0.00 | 0.00 | -3.2 | |
Maximum of Months | 565549.78 | 47.99 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 37211542.12 | 524.98 | 20-JAN-16:01 | 6.32 |
February | 23108761.90 | 558.46 | 19-FEB-16:03 | 15.82 |
March | 2164812.61 | 563.67 | 23-MAR-15:03 | 15.68 |
April | 1290550.13 | 504.97 | 10-APR-08:03 | 10.37 |
May | 787720.87 | 429.11 | 05-MAY-08:03 | 8.07 |
June | 349340.97 | 379.78 | 21-JUN-08:04 | 23.35 |
July | 87081.48 | 392.45 | 28-JUL-08:04 | 22.57 |
August | 283597.70 | 432.81 | 16-AUG-08:04 | 23.07 |
September | 434587.60 | 379.28 | 27-SEP-15:04 | 29.32 |
October | 1526365.37 | 539.06 | 17-OCT-08:03 | 10.47 |
November | 4402612.43 | 549.46 | 08-NOV-16:03 | 16.02 |
December | 59920151.39 | 531.18 | 23-DEC-16:01 | 7.02 |
Annual Sum or Average | 0.131567E+09 | |||
Minimum of Months | 87081.48 | 379.28 | 6.32 | |
Maximum of Months | 59920151.39 | 563.67 | 29.32 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.462244E+09 | 1685.26 | 12-JAN-16:01 | 6.52 |
February | 0.301827E+09 | 1676.50 | 16-FEB-19:01 | 1.70 |
March | 0.108499E+09 | 1653.71 | 22-MAR-08:62 | 4.87 |
April | 15916011.52 | 1242.65 | 07-APR-18:03 | 10.92 |
May | 4147582.81 | 1242.46 | 03-MAY-15:03 | 18.62 |
June | 330192.68 | 894.78 | 08-JUN-18:03 | 11.60 |
July | 27161.09 | 146.12 | 17-JUL-08:04 | 20.87 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 |
September | 268895.88 | 690.67 | 23-SEP-08:04 | 17.38 |
October | 53958205.55 | 1686.54 | 25-OCT-18:01 | 3.30 |
November | 0.151761E+09 | 1664.17 | 10-NOV-19:02 | 6.10 |
December | 0.459066E+09 | 1701.89 | 08-DEC-16:01 | 1.70 |
Annual Sum or Average | 0.155805E+10 | |||
Minimum of Months | 0.00 | 0.00 | 1.70 | |
Maximum of Months | 0.462244E+09 | 1701.89 | 20.95 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.753909E+09 | 1758.95 | 20-JAN-16:01 | 6.32 |
February | 0.497904E+09 | 1708.99 | 05-FEB-16:01 | 3.48 |
March | 0.169665E+09 | 1654.15 | 22-MAR-08:62 | 4.87 |
April | 25907608.59 | 1321.50 | 08-APR-18:03 | 14.82 |
May | 5232649.39 | 1289.94 | 03-MAY-15:03 | 18.62 |
June | 369116.77 | 884.45 | 08-JUN-18:03 | 11.60 |
July | 27410.80 | 167.48 | 17-JUL-08:04 | 20.87 |
August | 3652.23 | 42.61 | 29-AUG-18:04 | 21.83 |
September | 463646.47 | 684.75 | 23-SEP-08:04 | 17.38 |
October | 84675254.75 | 1691.05 | 25-OCT-18:01 | 3.30 |
November | 0.297014E+09 | 1716.58 | 27-NOV-16:01 | 6.52 |
December | 0.817787E+09 | 1743.35 | 23-DEC-16:01 | 7.02 |
Annual Sum or Average | 0.265296E+10 | |||
Minimum of Months | 3652.23 | 42.61 | 3.30 | |
Maximum of Months | 0.817787E+09 | 1758.95 | 21.83 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 15008693.06 | 373.99 | 19-JAN-09:02 | -2.1 |
February | 366625.78 | 159.38 | 06-FEB-07:10 | -5.4 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 2.47 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 12.83 |
December | 3928912.96 | 238.31 | 08-DEC-09:10 | -0.5 |
Annual Sum or Average | 19304231.80 | |||
Minimum of Months | 0.00 | 0.00 | -5.4 | |
Maximum of Months | 15008693.06 | 373.99 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.763312E+09 | 2100.59 | 12-JAN-16:01 | 6.52 |
February | 0.510401E+09 | 2095.17 | 16-FEB-19:01 | 1.70 |
March | 0.241773E+09 | 2106.40 | 23-MAR-08:61 | 7.07 |
April | 48937076.11 | 1592.21 | 30-APR-08:03 | 15.10 |
May | 17769395.58 | 1438.84 | 05-MAY-08:62 | 8.07 |
June | 2698806.04 | 1145.17 | 20-JUN-08:03 | 21.05 |
July | 11787.45 | 65.88 | 09-JUL-08:04 | 22.48 |
August | 699855.79 | 897.14 | 31-AUG-08:03 | 20.87 |
September | 1660679.97 | 1212.68 | 24-SEP-08:03 | 15.28 |
October | 0.109214E+09 | 2108.33 | 25-OCT-18:01 | 3.30 |
November | 0.295092E+09 | 2066.90 | 10-NOV-19:02 | 6.10 |
December | 0.771237E+09 | 2100.71 | 07-DEC-19:01 | 3.22 |
Annual Sum or Average | 0.276281E+10 | |||
Minimum of Months | 11787.45 | 65.88 | 1.70 | |
Maximum of Months | 0.771237E+09 | 2108.33 | 22.48 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.117774E+10 | 2140.48 | 12-JAN-16:01 | 6.52 |
February | 0.783457E+09 | 2121.63 | 08-FEB-09:01 | 4.18 |
March | 0.356775E+09 | 2123.16 | 23-MAR-08:61 | 7.07 |
April | 66643551.77 | 2002.87 | 06-APR-08:62 | 4.08 |
May | 19634300.16 | 1509.46 | 05-MAY-08:62 | 8.07 |
June | 2546485.51 | 1161.61 | 03-JUN-08:03 | 19.08 |
July | 4933.18 | 31.51 | 01-JUL-08:04 | 18.07 |
August | 729807.48 | 909.00 | 31-AUG-08:03 | 20.87 |
September | 2001216.61 | 1120.84 | 24-SEP-08:03 | 15.28 |
October | 0.170778E+09 | 2115.60 | 26-OCT-08:61 | 1.97 |
November | 0.542137E+09 | 2106.05 | 05-NOV-08:61 | 4.60 |
December | 0.127930E+10 | 2125.78 | 07-DEC-16:02 | 8.03 |
Annual Sum or Average | 0.440174E+10 | |||
Minimum of Months | 4933.18 | 31.51 | 1.97 | |
Maximum of Months | 0.127930E+10 | 2140.48 | 20.87 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.137128E+09 | 1035.09 | 17-JAN-16:02 | 1.32 |
February | 87476038.92 | 1029.23 | 16-FEB-19:01 | 1.70 |
March | 34583621.66 | 1034.32 | 22-MAR-08:62 | 4.87 |
April | 7385497.08 | 655.33 | 12-APR-08:03 | 13.07 |
May | 3281255.61 | 800.06 | 03-MAY-15:03 | 18.62 |
June | 535444.70 | 448.50 | 07-JUN-08:04 | 24.60 |
July | 512199.87 | 335.22 | 09-JUL-08:04 | 22.48 |
August | 435500.39 | 346.72 | 02-AUG-08:04 | 24.78 |
September | 171480.55 | 429.90 | 08-SEP-08:04 | 15.10 |
October | 19755300.94 | 1034.07 | 25-OCT-18:01 | 3.30 |
November | 31019768.25 | 877.71 | 10-NOV-19:02 | 6.10 |
December | 0.129307E+09 | 1025.98 | 08-DEC-16:01 | 1.70 |
Annual Sum or Average | 0.451591E+09 | |||
Minimum of Months | 171480.55 | 335.22 | 1.32 | |
Maximum of Months | 0.137128E+09 | 1035.09 | 24.78 |
Report: ZoneHeatingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 2.30 |
February | 0.00 | 0.00 | 01-FEB-00:05 | -3.2 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 2.47 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 12.83 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 5.13 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -3.2 | |
Maximum of Months | 0.00 | 0.00 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 2.30 |
February | 0.00 | 0.00 | 01-FEB-00:05 | -3.2 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 2.47 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 12.83 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 5.13 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -3.2 | |
Maximum of Months | 0.00 | 0.00 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 2.30 |
February | 0.00 | 0.00 | 01-FEB-00:05 | -3.2 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 2.47 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 12.83 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 5.13 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -3.2 | |
Maximum of Months | 0.00 | 0.00 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.650932E+09 | 2125.29 | 21-JAN-07:10 | -7.8 |
February | 0.337056E+09 | 2085.68 | 06-FEB-07:10 | -5.4 |
March | 46625223.15 | 979.88 | 05-MAR-06:30 | -3.3 |
April | 145235.25 | 120.59 | 08-APR-06:10 | 1.78 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 |
October | 41986312.90 | 1509.89 | 26-OCT-06:20 | -1.7 |
November | 79753919.64 | 1371.70 | 27-NOV-07:10 | -4.2 |
December | 0.648298E+09 | 2194.33 | 15-DEC-07:30 | -7.8 |
Annual Sum or Average | 0.180480E+10 | |||
Minimum of Months | 0.00 | 0.00 | -7.8 | |
Maximum of Months | 0.650932E+09 | 2194.33 | 21.95 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.140333E+11 | 13517.00 | 02-JAN-20:10 | 0.127587E+11 | 10113.80 | 02-JAN-20:10 |
February | 0.126708E+11 | 13517.00 | 01-FEB-20:10 | 0.115208E+11 | 10113.80 | 01-FEB-20:10 |
March | 0.140766E+11 | 13517.00 | 01-MAR-20:10 | 0.127855E+11 | 10113.80 | 01-MAR-20:10 |
April | 0.135575E+11 | 13517.00 | 03-APR-19:10 | 0.123314E+11 | 10113.80 | 03-APR-19:10 |
May | 0.140576E+11 | 13517.00 | 01-MAY-19:10 | 0.127741E+11 | 10113.80 | 01-MAY-19:10 |
June | 0.136197E+11 | 13517.00 | 01-JUN-19:10 | 0.123716E+11 | 10113.80 | 01-JUN-19:10 |
July | 0.139955E+11 | 13517.00 | 03-JUL-19:10 | 0.127338E+11 | 10113.80 | 03-JUL-19:10 |
August | 0.140820E+11 | 13517.00 | 01-AUG-19:10 | 0.127894E+11 | 10113.80 | 01-AUG-19:10 |
September | 0.135629E+11 | 13517.00 | 01-SEP-19:10 | 0.123352E+11 | 10113.80 | 01-SEP-19:10 |
October | 0.140279E+11 | 13517.00 | 02-OCT-19:10 | 0.127549E+11 | 10113.80 | 02-OCT-19:10 |
November | 0.136089E+11 | 13517.00 | 01-NOV-19:10 | 0.123659E+11 | 10113.80 | 01-NOV-19:10 |
December | 0.139955E+11 | 13517.00 | 01-DEC-20:10 | 0.127338E+11 | 10113.80 | 01-DEC-20:10 |
Annual Sum or Average | 0.165288E+12 | 0.150255E+12 | ||||
Minimum of Months | 0.126708E+11 | 13517.00 | 0.115208E+11 | 10113.80 | ||
Maximum of Months | 0.140820E+11 | 13517.00 | 0.127894E+11 | 10113.80 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.713551E+09 | 687.30 | 02-JAN-20:10 | 0.864900E+09 | 685.60 | 02-JAN-20:10 |
February | 0.644271E+09 | 687.30 | 01-FEB-20:10 | 0.780982E+09 | 685.60 | 01-FEB-20:10 |
March | 0.715750E+09 | 687.30 | 01-MAR-20:10 | 0.866718E+09 | 685.60 | 01-MAR-20:10 |
April | 0.689358E+09 | 687.30 | 03-APR-19:10 | 0.835931E+09 | 685.60 | 03-APR-19:10 |
May | 0.714788E+09 | 687.30 | 01-MAY-19:10 | 0.865939E+09 | 685.60 | 01-MAY-19:10 |
June | 0.692519E+09 | 687.30 | 01-JUN-19:10 | 0.838659E+09 | 685.60 | 01-JUN-19:10 |
July | 0.711626E+09 | 687.30 | 03-JUL-19:10 | 0.863211E+09 | 685.60 | 03-JUL-19:10 |
August | 0.716025E+09 | 687.30 | 01-AUG-19:10 | 0.866978E+09 | 685.60 | 01-AUG-19:10 |
September | 0.689633E+09 | 687.30 | 01-SEP-19:10 | 0.836191E+09 | 685.60 | 01-SEP-19:10 |
October | 0.713276E+09 | 687.30 | 02-OCT-19:10 | 0.864640E+09 | 685.60 | 02-OCT-19:10 |
November | 0.691970E+09 | 687.30 | 01-NOV-19:10 | 0.838269E+09 | 685.60 | 01-NOV-19:10 |
December | 0.711626E+09 | 687.30 | 01-DEC-20:10 | 0.863211E+09 | 685.60 | 01-DEC-20:10 |
Annual Sum or Average | 0.840439E+10 | 0.101856E+11 | ||||
Minimum of Months | 0.644271E+09 | 687.30 | 0.780982E+09 | 685.60 | ||
Maximum of Months | 0.716025E+09 | 687.30 | 0.866978E+09 | 685.60 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.826294E+09 | 795.89 | 02-JAN-20:10 | 0.100156E+10 | 793.93 | 02-JAN-20:10 |
February | 0.746069E+09 | 795.89 | 01-FEB-20:10 | 0.904380E+09 | 793.93 | 01-FEB-20:10 |
March | 0.828841E+09 | 795.89 | 01-MAR-20:10 | 0.100366E+10 | 793.93 | 01-MAR-20:10 |
April | 0.798279E+09 | 795.89 | 03-APR-19:10 | 0.968011E+09 | 793.93 | 03-APR-19:10 |
May | 0.827727E+09 | 795.89 | 01-MAY-19:10 | 0.100276E+10 | 793.93 | 01-MAY-19:10 |
June | 0.801940E+09 | 795.89 | 01-JUN-19:10 | 0.971170E+09 | 793.93 | 01-JUN-19:10 |
July | 0.824066E+09 | 795.89 | 03-JUL-19:10 | 0.999601E+09 | 793.93 | 03-JUL-19:10 |
August | 0.829160E+09 | 795.89 | 01-AUG-19:10 | 0.100396E+10 | 793.93 | 01-AUG-19:10 |
September | 0.798597E+09 | 795.89 | 01-SEP-19:10 | 0.968312E+09 | 793.93 | 01-SEP-19:10 |
October | 0.825976E+09 | 795.89 | 02-OCT-19:10 | 0.100126E+10 | 793.93 | 02-OCT-19:10 |
November | 0.801303E+09 | 795.89 | 01-NOV-19:10 | 0.970719E+09 | 793.93 | 01-NOV-19:10 |
December | 0.824066E+09 | 795.89 | 01-DEC-20:10 | 0.999601E+09 | 793.93 | 01-DEC-20:10 |
Annual Sum or Average | 0.973232E+10 | 0.117950E+11 | ||||
Minimum of Months | 0.746069E+09 | 795.89 | 0.904380E+09 | 793.93 | ||
Maximum of Months | 0.829160E+09 | 795.89 | 0.100396E+10 | 793.93 |
Report: ZoneElectricSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.154452E+10 | 1487.69 | 02-JAN-20:10 | 0.105898E+10 | 839.45 | 02-JAN-20:10 |
February | 0.139456E+10 | 1487.69 | 01-FEB-20:10 | 0.956227E+09 | 839.45 | 01-FEB-20:10 |
March | 0.154928E+10 | 1487.69 | 01-MAR-20:10 | 0.106120E+10 | 839.45 | 01-MAR-20:10 |
April | 0.149215E+10 | 1487.69 | 03-APR-19:10 | 0.102351E+10 | 839.45 | 03-APR-19:10 |
May | 0.154719E+10 | 1487.69 | 01-MAY-19:10 | 0.106025E+10 | 839.45 | 01-MAY-19:10 |
June | 0.149899E+10 | 1487.69 | 01-JUN-19:10 | 0.102685E+10 | 839.45 | 01-JUN-19:10 |
July | 0.154035E+10 | 1487.69 | 03-JUL-19:10 | 0.105691E+10 | 839.45 | 03-JUL-19:10 |
August | 0.154987E+10 | 1487.69 | 01-AUG-19:10 | 0.106152E+10 | 839.45 | 01-AUG-19:10 |
September | 0.149274E+10 | 1487.69 | 01-SEP-19:10 | 0.102382E+10 | 839.45 | 01-SEP-19:10 |
October | 0.154392E+10 | 1487.69 | 02-OCT-19:10 | 0.105866E+10 | 839.45 | 02-OCT-19:10 |
November | 0.149780E+10 | 1487.69 | 01-NOV-19:10 | 0.102637E+10 | 839.45 | 01-NOV-19:10 |
December | 0.154035E+10 | 1487.69 | 01-DEC-20:10 | 0.105691E+10 | 839.45 | 01-DEC-20:10 |
Annual Sum or Average | 0.181917E+11 | 0.124712E+11 | ||||
Minimum of Months | 0.139456E+10 | 1487.69 | 0.956227E+09 | 839.45 | ||
Maximum of Months | 0.154987E+10 | 1487.69 | 0.106152E+10 | 839.45 |
Report: ZoneElectricSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.283535E+09 | 273.10 | 02-JAN-20:10 | 0.305485E+09 | 242.16 | 02-JAN-20:10 |
February | 0.256006E+09 | 273.10 | 01-FEB-20:10 | 0.275845E+09 | 242.16 | 01-FEB-20:10 |
March | 0.284409E+09 | 273.10 | 01-MAR-20:10 | 0.306128E+09 | 242.16 | 01-MAR-20:10 |
April | 0.273921E+09 | 273.10 | 03-APR-19:10 | 0.295253E+09 | 242.16 | 03-APR-19:10 |
May | 0.284026E+09 | 273.10 | 01-MAY-19:10 | 0.305852E+09 | 242.16 | 01-MAY-19:10 |
June | 0.275178E+09 | 273.10 | 01-JUN-19:10 | 0.296217E+09 | 242.16 | 01-JUN-19:10 |
July | 0.282770E+09 | 273.10 | 03-JUL-19:10 | 0.304889E+09 | 242.16 | 03-JUL-19:10 |
August | 0.284518E+09 | 273.10 | 01-AUG-19:10 | 0.306219E+09 | 242.16 | 01-AUG-19:10 |
September | 0.274031E+09 | 273.10 | 01-SEP-19:10 | 0.295345E+09 | 242.16 | 01-SEP-19:10 |
October | 0.283425E+09 | 273.10 | 02-OCT-19:10 | 0.305393E+09 | 242.16 | 02-OCT-19:10 |
November | 0.274959E+09 | 273.10 | 01-NOV-19:10 | 0.296079E+09 | 242.16 | 01-NOV-19:10 |
December | 0.282770E+09 | 273.10 | 01-DEC-20:10 | 0.304889E+09 | 242.16 | 01-DEC-20:10 |
Annual Sum or Average | 0.333955E+10 | 0.359760E+10 | ||||
Minimum of Months | 0.256006E+09 | 273.10 | 0.275845E+09 | 242.16 | ||
Maximum of Months | 0.284518E+09 | 273.10 | 0.306219E+09 | 242.16 |
Report: ZoneElectricSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.350256E+09 | 337.37 | 02-JAN-20:10 | 0.576866E+10 | 4572.80 | 02-JAN-20:10 |
February | 0.316249E+09 | 337.37 | 01-FEB-20:10 | 0.520895E+10 | 4572.80 | 01-FEB-20:10 |
March | 0.351336E+09 | 337.37 | 01-MAR-20:10 | 0.578079E+10 | 4572.80 | 01-MAR-20:10 |
April | 0.338381E+09 | 337.37 | 03-APR-19:10 | 0.557545E+10 | 4572.80 | 03-APR-19:10 |
May | 0.350863E+09 | 337.37 | 01-MAY-19:10 | 0.577559E+10 | 4572.80 | 01-MAY-19:10 |
June | 0.339933E+09 | 337.37 | 01-JUN-19:10 | 0.559364E+10 | 4572.80 | 01-JUN-19:10 |
July | 0.349311E+09 | 337.37 | 03-JUL-19:10 | 0.575740E+10 | 4572.80 | 03-JUL-19:10 |
August | 0.351471E+09 | 337.37 | 01-AUG-19:10 | 0.578252E+10 | 4572.80 | 01-AUG-19:10 |
September | 0.338516E+09 | 337.37 | 01-SEP-19:10 | 0.557718E+10 | 4572.80 | 01-SEP-19:10 |
October | 0.350121E+09 | 337.37 | 02-OCT-19:10 | 0.576693E+10 | 4572.80 | 02-OCT-19:10 |
November | 0.339663E+09 | 337.37 | 01-NOV-19:10 | 0.559104E+10 | 4572.80 | 01-NOV-19:10 |
December | 0.349311E+09 | 337.37 | 01-DEC-20:10 | 0.575740E+10 | 4572.80 | 01-DEC-20:10 |
Annual Sum or Average | 0.412541E+10 | 0.679355E+11 | ||||
Minimum of Months | 0.316249E+09 | 337.37 | 0.520895E+10 | 4572.80 | ||
Maximum of Months | 0.351471E+09 | 337.37 | 0.578252E+10 | 4572.80 |
Report: ZoneElectricSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.226040E+10 | 2177.23 | 02-JAN-20:10 | 0.121771E+10 | 965.27 | 02-JAN-20:10 |
February | 0.204093E+10 | 2177.23 | 01-FEB-20:10 | 0.109956E+10 | 965.27 | 01-FEB-20:10 |
March | 0.226736E+10 | 2177.23 | 01-MAR-20:10 | 0.122027E+10 | 965.27 | 01-MAR-20:10 |
April | 0.218376E+10 | 2177.23 | 03-APR-19:10 | 0.117692E+10 | 965.27 | 03-APR-19:10 |
May | 0.226431E+10 | 2177.23 | 01-MAY-19:10 | 0.121917E+10 | 965.27 | 01-MAY-19:10 |
June | 0.219377E+10 | 2177.23 | 01-JUN-19:10 | 0.118076E+10 | 965.27 | 01-JUN-19:10 |
July | 0.225430E+10 | 2177.23 | 03-JUL-19:10 | 0.121533E+10 | 965.27 | 03-JUL-19:10 |
August | 0.226823E+10 | 2177.23 | 01-AUG-19:10 | 0.122063E+10 | 965.27 | 01-AUG-19:10 |
September | 0.218463E+10 | 2177.23 | 01-SEP-19:10 | 0.117729E+10 | 965.27 | 01-SEP-19:10 |
October | 0.225952E+10 | 2177.23 | 02-OCT-19:10 | 0.121734E+10 | 965.27 | 02-OCT-19:10 |
November | 0.219203E+10 | 2177.23 | 01-NOV-19:10 | 0.118021E+10 | 965.27 | 01-NOV-19:10 |
December | 0.225430E+10 | 2177.23 | 01-DEC-20:10 | 0.121533E+10 | 965.27 | 01-DEC-20:10 |
Annual Sum or Average | 0.266236E+11 | 0.143405E+11 | ||||
Minimum of Months | 0.204093E+10 | 2177.23 | 0.109956E+10 | 965.27 | ||
Maximum of Months | 0.226823E+10 | 2177.23 | 0.122063E+10 | 965.27 |
Report: ZoneElectricSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.123020E+11 | 11849.32 | 02-JAN-20:10 | 0.126520E+11 | 10029.21 | 02-JAN-20:10 |
February | 0.111075E+11 | 11849.32 | 01-FEB-20:10 | 0.114244E+11 | 10029.21 | 01-FEB-20:10 |
March | 0.123399E+11 | 11849.32 | 01-MAR-20:10 | 0.126786E+11 | 10029.21 | 01-MAR-20:10 |
April | 0.118849E+11 | 11849.32 | 03-APR-19:10 | 0.122282E+11 | 10029.21 | 03-APR-19:10 |
May | 0.123233E+11 | 11849.32 | 01-MAY-19:10 | 0.126672E+11 | 10029.21 | 01-MAY-19:10 |
June | 0.119394E+11 | 11849.32 | 01-JUN-19:10 | 0.122682E+11 | 10029.21 | 01-JUN-19:10 |
July | 0.122688E+11 | 11849.32 | 03-JUL-19:10 | 0.126273E+11 | 10029.21 | 03-JUL-19:10 |
August | 0.123446E+11 | 11849.32 | 01-AUG-19:10 | 0.126824E+11 | 10029.21 | 01-AUG-19:10 |
September | 0.118896E+11 | 11849.32 | 01-SEP-19:10 | 0.122320E+11 | 10029.21 | 01-SEP-19:10 |
October | 0.122972E+11 | 11849.32 | 02-OCT-19:10 | 0.126482E+11 | 10029.21 | 02-OCT-19:10 |
November | 0.119299E+11 | 11849.32 | 01-NOV-19:10 | 0.122624E+11 | 10029.21 | 01-NOV-19:10 |
December | 0.122688E+11 | 11849.32 | 01-DEC-20:10 | 0.126273E+11 | 10029.21 | 01-DEC-20:10 |
Annual Sum or Average | 0.144896E+12 | 0.148998E+12 | ||||
Minimum of Months | 0.111075E+11 | 11849.32 | 0.114244E+11 | 10029.21 | ||
Maximum of Months | 0.123446E+11 | 11849.32 | 0.126824E+11 | 10029.21 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.434056E+09 | 392.73 | 01-JAN-19:10 | 0.261068E+09 | 237.06 | 01-JAN-08:09 |
February | 0.391995E+09 | 392.73 | 01-FEB-20:10 | 0.235798E+09 | 237.06 | 01-FEB-07:10 |
March | 0.430607E+09 | 392.73 | 01-MAR-20:10 | 0.260708E+09 | 237.06 | 01-MAR-07:10 |
April | 0.420554E+09 | 392.73 | 01-APR-18:10 | 0.252705E+09 | 237.06 | 01-APR-07:10 |
May | 0.432331E+09 | 392.73 | 01-MAY-19:10 | 0.260888E+09 | 237.06 | 01-MAY-06:10 |
June | 0.417218E+09 | 392.73 | 01-JUN-19:10 | 0.252344E+09 | 237.06 | 01-JUN-06:10 |
July | 0.435725E+09 | 392.73 | 01-JUL-18:10 | 0.261248E+09 | 237.06 | 01-JUL-07:10 |
August | 0.430607E+09 | 392.73 | 01-AUG-19:10 | 0.260708E+09 | 237.06 | 01-AUG-06:10 |
September | 0.420667E+09 | 392.73 | 01-SEP-19:10 | 0.252705E+09 | 237.06 | 01-SEP-06:10 |
October | 0.434000E+09 | 392.73 | 01-OCT-18:10 | 0.261068E+09 | 237.06 | 01-OCT-07:10 |
November | 0.418886E+09 | 392.73 | 01-NOV-19:10 | 0.252524E+09 | 237.06 | 01-NOV-06:10 |
December | 0.435781E+09 | 392.73 | 01-DEC-20:10 | 0.261248E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.510243E+10 | 0.307301E+10 | ||||
Minimum of Months | 0.391995E+09 | 392.73 | 0.235798E+09 | 237.06 | ||
Maximum of Months | 0.435781E+09 | 392.73 | 0.261248E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.434005E+09 | 392.68 | 01-JAN-19:10 | 0.261038E+09 | 237.03 | 01-JAN-08:09 |
February | 0.391949E+09 | 392.68 | 01-FEB-20:10 | 0.235770E+09 | 237.03 | 01-FEB-07:10 |
March | 0.430556E+09 | 392.68 | 01-MAR-20:10 | 0.260677E+09 | 237.03 | 01-MAR-07:10 |
April | 0.420505E+09 | 392.68 | 01-APR-18:10 | 0.252675E+09 | 237.03 | 01-APR-07:10 |
May | 0.432281E+09 | 392.68 | 01-MAY-19:10 | 0.260857E+09 | 237.03 | 01-MAY-06:10 |
June | 0.417169E+09 | 392.68 | 01-JUN-19:10 | 0.252315E+09 | 237.03 | 01-JUN-06:10 |
July | 0.435674E+09 | 392.68 | 01-JUL-18:10 | 0.261218E+09 | 237.03 | 01-JUL-07:10 |
August | 0.430556E+09 | 392.68 | 01-AUG-19:10 | 0.260677E+09 | 237.03 | 01-AUG-06:10 |
September | 0.420618E+09 | 392.68 | 01-SEP-19:10 | 0.252675E+09 | 237.03 | 01-SEP-06:10 |
October | 0.433949E+09 | 392.68 | 01-OCT-18:10 | 0.261038E+09 | 237.03 | 01-OCT-07:10 |
November | 0.418837E+09 | 392.68 | 01-NOV-19:10 | 0.252495E+09 | 237.03 | 01-NOV-06:10 |
December | 0.435730E+09 | 392.68 | 01-DEC-20:10 | 0.261218E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.510183E+10 | 0.307265E+10 | ||||
Minimum of Months | 0.391949E+09 | 392.68 | 0.235770E+09 | 237.03 | ||
Maximum of Months | 0.435730E+09 | 392.68 | 0.261218E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.272788E+09 | 246.81 | 01-JAN-19:10 | 0.255708E+09 | 232.19 | 01-JAN-08:09 |
February | 0.246354E+09 | 246.81 | 01-FEB-20:10 | 0.230956E+09 | 232.19 | 01-FEB-07:10 |
March | 0.270620E+09 | 246.81 | 01-MAR-20:10 | 0.255355E+09 | 232.19 | 01-MAR-07:10 |
April | 0.264302E+09 | 246.81 | 01-APR-18:10 | 0.247516E+09 | 232.19 | 01-APR-07:10 |
May | 0.271704E+09 | 246.81 | 01-MAY-19:10 | 0.255532E+09 | 232.19 | 01-MAY-06:10 |
June | 0.262205E+09 | 246.81 | 01-JUN-19:10 | 0.247163E+09 | 232.19 | 01-JUN-06:10 |
July | 0.273836E+09 | 246.81 | 01-JUL-18:10 | 0.255885E+09 | 232.19 | 01-JUL-07:10 |
August | 0.270620E+09 | 246.81 | 01-AUG-19:10 | 0.255355E+09 | 232.19 | 01-AUG-06:10 |
September | 0.264373E+09 | 246.81 | 01-SEP-19:10 | 0.247516E+09 | 232.19 | 01-SEP-06:10 |
October | 0.272752E+09 | 246.81 | 01-OCT-18:10 | 0.255708E+09 | 232.19 | 01-OCT-07:10 |
November | 0.263254E+09 | 246.81 | 01-NOV-19:10 | 0.247340E+09 | 232.19 | 01-NOV-06:10 |
December | 0.273872E+09 | 246.81 | 01-DEC-20:10 | 0.255885E+09 | 232.19 | 01-DEC-07:10 |
Annual Sum or Average | 0.320668E+10 | 0.300992E+10 | ||||
Minimum of Months | 0.246354E+09 | 246.81 | 0.230956E+09 | 232.19 | ||
Maximum of Months | 0.273872E+09 | 246.81 | 0.255885E+09 | 232.19 |
Report: ZoneElectricSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.272862E+09 | 246.88 | 01-JAN-19:10 | 0.255778E+09 | 232.26 | 01-JAN-08:09 |
February | 0.246421E+09 | 246.88 | 01-FEB-20:10 | 0.231020E+09 | 232.26 | 01-FEB-07:10 |
March | 0.270694E+09 | 246.88 | 01-MAR-20:10 | 0.255425E+09 | 232.26 | 01-MAR-07:10 |
April | 0.264375E+09 | 246.88 | 01-APR-18:10 | 0.247584E+09 | 232.26 | 01-APR-07:10 |
May | 0.271778E+09 | 246.88 | 01-MAY-19:10 | 0.255602E+09 | 232.26 | 01-MAY-06:10 |
June | 0.262277E+09 | 246.88 | 01-JUN-19:10 | 0.247231E+09 | 232.26 | 01-JUN-06:10 |
July | 0.273911E+09 | 246.88 | 01-JUL-18:10 | 0.255955E+09 | 232.26 | 01-JUL-07:10 |
August | 0.270694E+09 | 246.88 | 01-AUG-19:10 | 0.255425E+09 | 232.26 | 01-AUG-06:10 |
September | 0.264446E+09 | 246.88 | 01-SEP-19:10 | 0.247584E+09 | 232.26 | 01-SEP-06:10 |
October | 0.272827E+09 | 246.88 | 01-OCT-18:10 | 0.255778E+09 | 232.26 | 01-OCT-07:10 |
November | 0.263326E+09 | 246.88 | 01-NOV-19:10 | 0.247408E+09 | 232.26 | 01-NOV-06:10 |
December | 0.273947E+09 | 246.88 | 01-DEC-20:10 | 0.255955E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.320756E+10 | 0.301074E+10 | ||||
Minimum of Months | 0.246421E+09 | 246.88 | 0.231020E+09 | 232.26 | ||
Maximum of Months | 0.273947E+09 | 246.88 | 0.255955E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.434056E+09 | 392.73 | 01-JAN-19:10 | 0.261068E+09 | 237.06 | 01-JAN-08:09 |
February | 0.391995E+09 | 392.73 | 01-FEB-20:10 | 0.235798E+09 | 237.06 | 01-FEB-07:10 |
March | 0.430607E+09 | 392.73 | 01-MAR-20:10 | 0.260708E+09 | 237.06 | 01-MAR-07:10 |
April | 0.420554E+09 | 392.73 | 01-APR-18:10 | 0.252705E+09 | 237.06 | 01-APR-07:10 |
May | 0.432331E+09 | 392.73 | 01-MAY-19:10 | 0.260888E+09 | 237.06 | 01-MAY-06:10 |
June | 0.417218E+09 | 392.73 | 01-JUN-19:10 | 0.252344E+09 | 237.06 | 01-JUN-06:10 |
July | 0.435725E+09 | 392.73 | 01-JUL-18:10 | 0.261248E+09 | 237.06 | 01-JUL-07:10 |
August | 0.430607E+09 | 392.73 | 01-AUG-19:10 | 0.260708E+09 | 237.06 | 01-AUG-06:10 |
September | 0.420667E+09 | 392.73 | 01-SEP-19:10 | 0.252705E+09 | 237.06 | 01-SEP-06:10 |
October | 0.434000E+09 | 392.73 | 01-OCT-18:10 | 0.261068E+09 | 237.06 | 01-OCT-07:10 |
November | 0.418886E+09 | 392.73 | 01-NOV-19:10 | 0.252524E+09 | 237.06 | 01-NOV-06:10 |
December | 0.435781E+09 | 392.73 | 01-DEC-20:10 | 0.261248E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.510243E+10 | 0.307301E+10 | ||||
Minimum of Months | 0.391995E+09 | 392.73 | 0.235798E+09 | 237.06 | ||
Maximum of Months | 0.435781E+09 | 392.73 | 0.261248E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.434005E+09 | 392.68 | 01-JAN-19:10 | 0.261038E+09 | 237.03 | 01-JAN-08:09 |
February | 0.391949E+09 | 392.68 | 01-FEB-20:10 | 0.235770E+09 | 237.03 | 01-FEB-07:10 |
March | 0.430556E+09 | 392.68 | 01-MAR-20:10 | 0.260677E+09 | 237.03 | 01-MAR-07:10 |
April | 0.420505E+09 | 392.68 | 01-APR-18:10 | 0.252675E+09 | 237.03 | 01-APR-07:10 |
May | 0.432281E+09 | 392.68 | 01-MAY-19:10 | 0.260857E+09 | 237.03 | 01-MAY-06:10 |
June | 0.417169E+09 | 392.68 | 01-JUN-19:10 | 0.252315E+09 | 237.03 | 01-JUN-06:10 |
July | 0.435674E+09 | 392.68 | 01-JUL-18:10 | 0.261218E+09 | 237.03 | 01-JUL-07:10 |
August | 0.430556E+09 | 392.68 | 01-AUG-19:10 | 0.260677E+09 | 237.03 | 01-AUG-06:10 |
September | 0.420618E+09 | 392.68 | 01-SEP-19:10 | 0.252675E+09 | 237.03 | 01-SEP-06:10 |
October | 0.433949E+09 | 392.68 | 01-OCT-18:10 | 0.261038E+09 | 237.03 | 01-OCT-07:10 |
November | 0.418837E+09 | 392.68 | 01-NOV-19:10 | 0.252495E+09 | 237.03 | 01-NOV-06:10 |
December | 0.435730E+09 | 392.68 | 01-DEC-20:10 | 0.261218E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.510183E+10 | 0.307265E+10 | ||||
Minimum of Months | 0.391949E+09 | 392.68 | 0.235770E+09 | 237.03 | ||
Maximum of Months | 0.435730E+09 | 392.68 | 0.261218E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.133160E+10 | 1282.60 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.120231E+10 | 1282.60 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.133570E+10 | 1282.60 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.128645E+10 | 1282.60 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.133391E+10 | 1282.60 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.129235E+10 | 1282.60 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.132801E+10 | 1282.60 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.133622E+10 | 1282.60 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.128696E+10 | 1282.60 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.133109E+10 | 1282.60 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.129132E+10 | 1282.60 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.132801E+10 | 1282.60 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.156839E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.120231E+10 | 1282.60 | 0.00 | 0.00 | |
Maximum of Months | 0.133622E+10 | 1282.60 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.434056E+09 | 392.73 | 01-JAN-19:10 | 0.261068E+09 | 237.06 | 01-JAN-08:09 |
February | 0.391995E+09 | 392.73 | 01-FEB-20:10 | 0.235798E+09 | 237.06 | 01-FEB-07:10 |
March | 0.430607E+09 | 392.73 | 01-MAR-20:10 | 0.260708E+09 | 237.06 | 01-MAR-07:10 |
April | 0.420554E+09 | 392.73 | 01-APR-18:10 | 0.252705E+09 | 237.06 | 01-APR-07:10 |
May | 0.432331E+09 | 392.73 | 01-MAY-19:10 | 0.260888E+09 | 237.06 | 01-MAY-06:10 |
June | 0.417218E+09 | 392.73 | 01-JUN-19:10 | 0.252344E+09 | 237.06 | 01-JUN-06:10 |
July | 0.435725E+09 | 392.73 | 01-JUL-18:10 | 0.261248E+09 | 237.06 | 01-JUL-07:10 |
August | 0.430607E+09 | 392.73 | 01-AUG-19:10 | 0.260708E+09 | 237.06 | 01-AUG-06:10 |
September | 0.420667E+09 | 392.73 | 01-SEP-19:10 | 0.252705E+09 | 237.06 | 01-SEP-06:10 |
October | 0.434000E+09 | 392.73 | 01-OCT-18:10 | 0.261068E+09 | 237.06 | 01-OCT-07:10 |
November | 0.418886E+09 | 392.73 | 01-NOV-19:10 | 0.252524E+09 | 237.06 | 01-NOV-06:10 |
December | 0.435781E+09 | 392.73 | 01-DEC-20:10 | 0.261248E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.510243E+10 | 0.307301E+10 | ||||
Minimum of Months | 0.391995E+09 | 392.73 | 0.235798E+09 | 237.06 | ||
Maximum of Months | 0.435781E+09 | 392.73 | 0.261248E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.434005E+09 | 392.68 | 01-JAN-19:10 | 0.261038E+09 | 237.03 | 01-JAN-08:09 |
February | 0.391949E+09 | 392.68 | 01-FEB-20:10 | 0.235770E+09 | 237.03 | 01-FEB-07:10 |
March | 0.430556E+09 | 392.68 | 01-MAR-20:10 | 0.260677E+09 | 237.03 | 01-MAR-07:10 |
April | 0.420505E+09 | 392.68 | 01-APR-18:10 | 0.252675E+09 | 237.03 | 01-APR-07:10 |
May | 0.432281E+09 | 392.68 | 01-MAY-19:10 | 0.260857E+09 | 237.03 | 01-MAY-06:10 |
June | 0.417169E+09 | 392.68 | 01-JUN-19:10 | 0.252315E+09 | 237.03 | 01-JUN-06:10 |
July | 0.435674E+09 | 392.68 | 01-JUL-18:10 | 0.261218E+09 | 237.03 | 01-JUL-07:10 |
August | 0.430556E+09 | 392.68 | 01-AUG-19:10 | 0.260677E+09 | 237.03 | 01-AUG-06:10 |
September | 0.420618E+09 | 392.68 | 01-SEP-19:10 | 0.252675E+09 | 237.03 | 01-SEP-06:10 |
October | 0.433949E+09 | 392.68 | 01-OCT-18:10 | 0.261038E+09 | 237.03 | 01-OCT-07:10 |
November | 0.418837E+09 | 392.68 | 01-NOV-19:10 | 0.252495E+09 | 237.03 | 01-NOV-06:10 |
December | 0.435730E+09 | 392.68 | 01-DEC-20:10 | 0.261218E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.510183E+10 | 0.307265E+10 | ||||
Minimum of Months | 0.391949E+09 | 392.68 | 0.235770E+09 | 237.03 | ||
Maximum of Months | 0.435730E+09 | 392.68 | 0.261218E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.272862E+09 | 246.88 | 01-JAN-19:10 | 0.255778E+09 | 232.26 | 01-JAN-08:09 |
February | 0.246421E+09 | 246.88 | 01-FEB-20:10 | 0.231020E+09 | 232.26 | 01-FEB-07:10 |
March | 0.270694E+09 | 246.88 | 01-MAR-20:10 | 0.255425E+09 | 232.26 | 01-MAR-07:10 |
April | 0.264375E+09 | 246.88 | 01-APR-18:10 | 0.247584E+09 | 232.26 | 01-APR-07:10 |
May | 0.271778E+09 | 246.88 | 01-MAY-19:10 | 0.255602E+09 | 232.26 | 01-MAY-06:10 |
June | 0.262277E+09 | 246.88 | 01-JUN-19:10 | 0.247231E+09 | 232.26 | 01-JUN-06:10 |
July | 0.273911E+09 | 246.88 | 01-JUL-18:10 | 0.255955E+09 | 232.26 | 01-JUL-07:10 |
August | 0.270694E+09 | 246.88 | 01-AUG-19:10 | 0.255425E+09 | 232.26 | 01-AUG-06:10 |
September | 0.264446E+09 | 246.88 | 01-SEP-19:10 | 0.247584E+09 | 232.26 | 01-SEP-06:10 |
October | 0.272827E+09 | 246.88 | 01-OCT-18:10 | 0.255778E+09 | 232.26 | 01-OCT-07:10 |
November | 0.263326E+09 | 246.88 | 01-NOV-19:10 | 0.247408E+09 | 232.26 | 01-NOV-06:10 |
December | 0.273947E+09 | 246.88 | 01-DEC-20:10 | 0.255955E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.320756E+10 | 0.301074E+10 | ||||
Minimum of Months | 0.246421E+09 | 246.88 | 0.231020E+09 | 232.26 | ||
Maximum of Months | 0.273947E+09 | 246.88 | 0.255955E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.396945E+10 | 3823.39 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.358405E+10 | 3823.39 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.398168E+10 | 3823.39 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.383486E+10 | 3823.39 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.397633E+10 | 3823.39 | 01-MAY-19:10 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.385245E+10 | 3823.39 | 01-JUN-19:10 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.395874E+10 | 3823.39 | 03-JUL-19:10 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.398321E+10 | 3823.39 | 01-AUG-19:10 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.383639E+10 | 3823.39 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.396792E+10 | 3823.39 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.384939E+10 | 3823.39 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.395874E+10 | 3823.39 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.467532E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.358405E+10 | 3823.39 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.398321E+10 | 3823.39 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.396945E+10 | 3823.39 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.358405E+10 | 3823.39 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.398168E+10 | 3823.39 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.383486E+10 | 3823.39 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.397633E+10 | 3823.39 | 01-MAY-19:10 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.385245E+10 | 3823.39 | 01-JUN-19:10 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.395874E+10 | 3823.39 | 03-JUL-19:10 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.398321E+10 | 3823.39 | 01-AUG-19:10 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.383639E+10 | 3823.39 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.396792E+10 | 3823.39 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.384939E+10 | 3823.39 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.395874E+10 | 3823.39 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.467532E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.358405E+10 | 3823.39 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.398321E+10 | 3823.39 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.105977E+10 | 1020.78 | 02-JAN-20:10 | 0.373720E+11 | 16686.59 | 01-JAN-07:10 |
February | 0.956878E+09 | 1020.78 | 01-FEB-20:10 | 0.337554E+11 | 16686.59 | 01-FEB-07:10 |
March | 0.106304E+10 | 1020.78 | 01-MAR-20:10 | 0.373720E+11 | 16686.59 | 01-MAR-07:10 |
April | 0.102384E+10 | 1020.78 | 03-APR-19:10 | 0.361665E+11 | 16686.59 | 01-APR-06:10 |
May | 0.106161E+10 | 1020.78 | 01-MAY-19:10 | 0.373720E+11 | 16686.59 | 01-MAY-06:10 |
June | 0.102854E+10 | 1020.78 | 01-JUN-19:10 | 0.361665E+11 | 16686.59 | 01-JUN-06:10 |
July | 0.105691E+10 | 1020.78 | 03-JUL-19:10 | 0.373720E+11 | 16686.59 | 01-JUL-06:10 |
August | 0.106345E+10 | 1020.78 | 01-AUG-19:10 | 0.373720E+11 | 16686.59 | 01-AUG-06:10 |
September | 0.102425E+10 | 1020.78 | 01-SEP-19:10 | 0.361665E+11 | 16686.59 | 01-SEP-06:10 |
October | 0.105936E+10 | 1020.78 | 02-OCT-19:10 | 0.373720E+11 | 16686.59 | 01-OCT-06:10 |
November | 0.102772E+10 | 1020.78 | 01-NOV-19:10 | 0.361665E+11 | 16686.59 | 01-NOV-06:10 |
December | 0.105691E+10 | 1020.78 | 01-DEC-20:10 | 0.373720E+11 | 16686.59 | 01-DEC-07:10 |
Annual Sum or Average | 0.124823E+11 | 0.440025E+12 | ||||
Minimum of Months | 0.956878E+09 | 1020.78 | 0.337554E+11 | 16686.59 | ||
Maximum of Months | 0.106345E+10 | 1020.78 | 0.373720E+11 | 16686.59 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.140929E+10 | 1357.44 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.127246E+10 | 1357.44 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.141364E+10 | 1357.44 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.136151E+10 | 1357.44 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.141173E+10 | 1357.44 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.136775E+10 | 1357.44 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.140549E+10 | 1357.44 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.141418E+10 | 1357.44 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.136205E+10 | 1357.44 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.140875E+10 | 1357.44 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.136667E+10 | 1357.44 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.140549E+10 | 1357.44 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.165990E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.127246E+10 | 1357.44 | 0.00 | 0.00 | |
Maximum of Months | 0.141418E+10 | 1357.44 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.195762E+11 | 0.140333E+11 | 0.127587E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.176991E+11 | 0.126708E+11 | 0.115208E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.196682E+11 | 0.140766E+11 | 0.127855E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.189781E+11 | 0.135575E+11 | 0.123314E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.196176E+11 | 0.140576E+11 | 0.127741E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.190195E+11 | 0.136197E+11 | 0.123716E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.195762E+11 | 0.139955E+11 | 0.127338E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.196590E+11 | 0.140820E+11 | 0.127894E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.189689E+11 | 0.135629E+11 | 0.123352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.195854E+11 | 0.140279E+11 | 0.127549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.189367E+11 | 0.136089E+11 | 0.123659E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.195762E+11 | 0.139955E+11 | 0.127338E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.230861E+12 | 0.165288E+12 | 0.150255E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.176991E+11 | 0.126708E+11 | 0.115208E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.196682E+11 | 0.140820E+11 | 0.127894E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.199054E+10 | 0.713551E+09 | 0.864900E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.528784E+09 |
February | 0.179968E+10 | 0.644271E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.431244E+09 |
March | 0.199990E+10 | 0.715750E+09 | 0.866718E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19064.88 | 0.343334E+09 |
April | 0.192973E+10 | 0.689358E+09 | 0.835931E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6726502.41 | 0.196700E+09 |
May | 0.199475E+10 | 0.714788E+09 | 0.865939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 28930553.39 | 0.116703E+09 |
June | 0.193394E+10 | 0.692519E+09 | 0.838659E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 96712888.40 | 45933851.92 |
July | 0.199054E+10 | 0.711626E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124316E+09 | 9587687.02 |
August | 0.199896E+10 | 0.716025E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 91311888.95 | 19228741.75 |
September | 0.192879E+10 | 0.689633E+09 | 0.836191E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 34890388.03 | 60470090.85 |
October | 0.199148E+10 | 0.713276E+09 | 0.864640E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6592921.32 | 0.220189E+09 |
November | 0.192552E+10 | 0.691970E+09 | 0.838269E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.389068E+09 |
December | 0.199054E+10 | 0.711626E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.543792E+09 |
Annual Sum or Average | 0.234744E+11 | 0.840439E+10 | 0.101856E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.389500E+09 | 0.290503E+10 |
Minimum of Months | 0.179968E+10 | 0.644271E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9587687.02 |
Maximum of Months | 0.199990E+10 | 0.716025E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124316E+09 | 0.543792E+09 |
Report: SpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.230505E+10 | 0.826294E+09 | 0.100156E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.200500E+09 |
February | 0.208403E+10 | 0.746069E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 33088.67 | 0.163476E+09 |
March | 0.231589E+10 | 0.828841E+09 | 0.100366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 82990.49 | 0.130741E+09 |
April | 0.223463E+10 | 0.798279E+09 | 0.968011E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3089183.15 | 76113114.14 |
May | 0.230993E+10 | 0.827727E+09 | 0.100276E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11184597.49 | 45768785.44 |
June | 0.223950E+10 | 0.801940E+09 | 0.971170E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 36584117.25 | 18401316.79 |
July | 0.230505E+10 | 0.824066E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 47301718.35 | 4201767.79 |
August | 0.231480E+10 | 0.829160E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36018283.61 | 8223283.69 |
September | 0.223354E+10 | 0.798597E+09 | 0.968312E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16875864.34 | 24406084.77 |
October | 0.230614E+10 | 0.825976E+09 | 0.100126E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4206545.63 | 82626398.22 |
November | 0.222975E+10 | 0.801303E+09 | 0.970719E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146059E+09 |
December | 0.230505E+10 | 0.824066E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205850E+09 |
Annual Sum or Average | 0.271834E+11 | 0.973232E+10 | 0.117950E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155376E+09 | 0.110637E+10 |
Minimum of Months | 0.208403E+10 | 0.746069E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4201767.79 |
Maximum of Months | 0.231589E+10 | 0.829160E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47301718.35 | 0.205850E+09 |
Report: SpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.487480E+09 | 0.154452E+10 | 0.105898E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.473538E+09 |
February | 0.440737E+09 | 0.139456E+10 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 78288.61 | 0.385855E+09 |
March | 0.489771E+09 | 0.154928E+10 | 0.106120E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 196250.48 | 0.308016E+09 |
April | 0.472586E+09 | 0.149215E+10 | 0.102351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7383380.88 | 0.178342E+09 |
May | 0.488511E+09 | 0.154719E+10 | 0.106025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26796795.15 | 0.106757E+09 |
June | 0.473617E+09 | 0.149899E+10 | 0.102685E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 87428854.13 | 42312677.23 |
July | 0.487480E+09 | 0.154035E+10 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113273E+09 | 9111934.12 |
August | 0.489542E+09 | 0.154987E+10 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 86776910.86 | 18019055.77 |
September | 0.472357E+09 | 0.149274E+10 | 0.102382E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40335512.32 | 55254681.84 |
October | 0.487709E+09 | 0.154392E+10 | 0.105866E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10009012.82 | 0.193187E+09 |
November | 0.471555E+09 | 0.149780E+10 | 0.102637E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.344369E+09 |
December | 0.487480E+09 | 0.154035E+10 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.486235E+09 |
Annual Sum or Average | 0.574883E+10 | 0.181917E+11 | 0.124712E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.372278E+09 | 0.260100E+10 |
Minimum of Months | 0.440737E+09 | 0.139456E+10 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9111934.12 |
Maximum of Months | 0.489771E+09 | 0.154987E+10 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113273E+09 | 0.486235E+09 |
Report: SpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.374985E+09 | 0.283535E+09 | 0.305485E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.273206E+09 |
February | 0.339028E+09 | 0.256006E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 45185.42 | 0.222618E+09 |
March | 0.376747E+09 | 0.284409E+09 | 0.306128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 113242.36 | 0.177709E+09 |
April | 0.363528E+09 | 0.273921E+09 | 0.295253E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4271588.87 | 0.102784E+09 |
May | 0.375778E+09 | 0.284026E+09 | 0.305852E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15614919.61 | 61392332.55 |
June | 0.364321E+09 | 0.275178E+09 | 0.296217E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 51005624.43 | 24224309.35 |
July | 0.374985E+09 | 0.282770E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 66152237.87 | 5094194.63 |
August | 0.376571E+09 | 0.284518E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 50689066.16 | 10159405.78 |
September | 0.363352E+09 | 0.274031E+09 | 0.295345E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 23401678.97 | 31485611.60 |
October | 0.375161E+09 | 0.283425E+09 | 0.305393E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5780846.41 | 0.111308E+09 |
November | 0.362735E+09 | 0.274959E+09 | 0.296079E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.198683E+09 |
December | 0.374985E+09 | 0.282770E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.280532E+09 |
Annual Sum or Average | 0.442217E+10 | 0.333955E+10 | 0.359760E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.217074E+09 | 0.149920E+10 |
Minimum of Months | 0.339028E+09 | 0.256006E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5094194.63 |
Maximum of Months | 0.376747E+09 | 0.284518E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 66152237.87 | 0.280532E+09 |
Report: SpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.154405E+10 | 0.350256E+09 | 0.576866E+10 | 0.501157E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.661673E+09 |
February | 0.139600E+10 | 0.316249E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 106587.04 | 0.540357E+09 |
March | 0.155131E+10 | 0.351336E+09 | 0.578079E+10 | 0.502211E+11 | 0.00 | 0.00 | 0.00 | 270021.70 | 0.435324E+09 |
April | 0.149688E+10 | 0.338381E+09 | 0.557545E+10 | 0.484372E+11 | 0.00 | 0.00 | 0.00 | 9349451.96 | 0.255574E+09 |
May | 0.154732E+10 | 0.350863E+09 | 0.577559E+10 | 0.501759E+11 | 0.00 | 0.00 | 0.00 | 33385311.53 | 0.154779E+09 |
June | 0.150015E+10 | 0.339933E+09 | 0.559364E+10 | 0.485952E+11 | 0.00 | 0.00 | 0.00 | 0.113795E+09 | 61235474.69 |
July | 0.154405E+10 | 0.349311E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 0.148559E+09 | 14022989.03 |
August | 0.155059E+10 | 0.351471E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 0.112491E+09 | 27874654.21 |
September | 0.149615E+10 | 0.338516E+09 | 0.557718E+10 | 0.484522E+11 | 0.00 | 0.00 | 0.00 | 52473454.14 | 83952435.90 |
October | 0.154478E+10 | 0.350121E+09 | 0.576693E+10 | 0.501006E+11 | 0.00 | 0.00 | 0.00 | 13320026.12 | 0.276972E+09 |
November | 0.149361E+10 | 0.339663E+09 | 0.559104E+10 | 0.485726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.484591E+09 |
December | 0.154405E+10 | 0.349311E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.678888E+09 |
Annual Sum or Average | 0.182090E+11 | 0.412541E+10 | 0.679355E+11 | 0.590196E+12 | 0.00 | 0.00 | 0.00 | 0.483749E+09 | 0.367524E+10 |
Minimum of Months | 0.139600E+10 | 0.316249E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 14022989.03 |
Maximum of Months | 0.155131E+10 | 0.351471E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 0.148559E+09 | 0.678888E+09 |
Report: SpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.261570E+11 | 0.226040E+10 | 0.121771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116608E+10 |
February | 0.236489E+11 | 0.204093E+10 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.951117E+09 |
March | 0.262800E+11 | 0.226736E+10 | 0.122027E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 71657.77 | 0.757715E+09 |
April | 0.253579E+11 | 0.218376E+10 | 0.117692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16008696.30 | 0.436768E+09 |
May | 0.262123E+11 | 0.226431E+10 | 0.121917E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 64464996.05 | 0.261386E+09 |
June | 0.254132E+11 | 0.219377E+10 | 0.118076E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.210550E+09 | 0.104959E+09 |
July | 0.261570E+11 | 0.225430E+10 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.270551E+09 | 24973831.07 |
August | 0.262677E+11 | 0.226823E+10 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.201146E+09 | 48555386.46 |
September | 0.253456E+11 | 0.218463E+10 | 0.117729E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 83999974.79 | 0.143217E+09 |
October | 0.261693E+11 | 0.225952E+10 | 0.121734E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17097155.83 | 0.490110E+09 |
November | 0.253025E+11 | 0.219203E+10 | 0.118021E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.857626E+09 |
December | 0.261570E+11 | 0.225430E+10 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119896E+10 |
Annual Sum or Average | 0.308468E+12 | 0.266236E+11 | 0.143405E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.863889E+09 | 0.644147E+10 |
Minimum of Months | 0.236489E+11 | 0.204093E+10 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24973831.07 |
Maximum of Months | 0.262800E+11 | 0.226823E+10 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.270551E+09 | 0.119896E+10 |
Report: SpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.776503E+11 | 0.123020E+11 | 0.126520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.328933E+10 |
February | 0.702046E+11 | 0.111075E+11 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 401120.81 | 0.268370E+10 |
March | 0.780153E+11 | 0.123399E+11 | 0.126786E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1319767.67 | 0.215148E+10 |
April | 0.752779E+11 | 0.118849E+11 | 0.122282E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 50355174.51 | 0.126132E+10 |
May | 0.778146E+11 | 0.123233E+11 | 0.126672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181928E+09 | 0.768016E+09 |
June | 0.754422E+11 | 0.119394E+11 | 0.122682E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.593613E+09 | 0.317473E+09 |
July | 0.776503E+11 | 0.122688E+11 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.764330E+09 | 83637147.52 |
August | 0.779788E+11 | 0.123446E+11 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.581949E+09 | 0.152605E+09 |
September | 0.752414E+11 | 0.118896E+11 | 0.122320E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.273395E+09 | 0.423029E+09 |
October | 0.776868E+11 | 0.122972E+11 | 0.126482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 67036215.39 | 0.137380E+10 |
November | 0.751137E+11 | 0.119299E+11 | 0.122624E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.240462E+10 |
December | 0.776503E+11 | 0.122688E+11 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.337683E+10 |
Annual Sum or Average | 0.915726E+12 | 0.144896E+12 | 0.148998E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.251433E+10 | 0.182858E+11 |
Minimum of Months | 0.702046E+11 | 0.111075E+11 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83637147.52 |
Maximum of Months | 0.780153E+11 | 0.123446E+11 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.764330E+09 | 0.337683E+10 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.434056E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.306842E+09 |
February | 0.273974E+09 | 0.391995E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9276.95 | 0.251992E+09 |
March | 0.303685E+09 | 0.430607E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 30835.15 | 0.204415E+09 |
April | 0.293479E+09 | 0.420554E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2599491.68 | 0.121289E+09 |
May | 0.303504E+09 | 0.432331E+09 | 0.260888E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11843703.29 | 72780746.51 |
June | 0.293842E+09 | 0.417218E+09 | 0.252344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 48309064.07 | 28985427.00 |
July | 0.303141E+09 | 0.435725E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 63216376.37 | 6627159.88 |
August | 0.303685E+09 | 0.430607E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 46491118.11 | 12838641.28 |
September | 0.293479E+09 | 0.420667E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18371981.43 | 38200655.96 |
October | 0.303322E+09 | 0.434000E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3776024.10 | 0.130230E+09 |
November | 0.293661E+09 | 0.418886E+09 | 0.252524E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.227494E+09 |
December | 0.303141E+09 | 0.435781E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.314999E+09 |
Annual Sum or Average | 0.357224E+10 | 0.510243E+10 | 0.307301E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.194648E+09 | 0.171669E+10 |
Minimum of Months | 0.273974E+09 | 0.391995E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6627159.88 |
Maximum of Months | 0.303685E+09 | 0.435781E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 63216376.37 | 0.314999E+09 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.434005E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.300465E+09 |
February | 0.273974E+09 | 0.391949E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9457.25 | 0.246857E+09 |
March | 0.303685E+09 | 0.430556E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 31008.21 | 0.201129E+09 |
April | 0.293479E+09 | 0.420505E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2603226.32 | 0.119879E+09 |
May | 0.303504E+09 | 0.432281E+09 | 0.260857E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11869999.88 | 72379064.25 |
June | 0.293842E+09 | 0.417169E+09 | 0.252315E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 48301870.48 | 28970757.43 |
July | 0.303141E+09 | 0.435674E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 63226262.30 | 6640780.80 |
August | 0.303685E+09 | 0.430556E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 46574163.31 | 12802046.29 |
September | 0.293479E+09 | 0.420618E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18532931.08 | 37859966.33 |
October | 0.303322E+09 | 0.433949E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3835538.26 | 0.127488E+09 |
November | 0.293661E+09 | 0.418837E+09 | 0.252495E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222440E+09 |
December | 0.303141E+09 | 0.435730E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.307463E+09 |
Annual Sum or Average | 0.357224E+10 | 0.510183E+10 | 0.307265E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.194984E+09 | 0.168437E+10 |
Minimum of Months | 0.273974E+09 | 0.391949E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6640780.80 |
Maximum of Months | 0.303685E+09 | 0.435730E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 63226262.30 | 0.307463E+09 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.272788E+09 | 0.255708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90242934.56 |
February | 0.00 | 0.246354E+09 | 0.230956E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75367129.70 |
March | 0.00 | 0.270620E+09 | 0.255355E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63645052.60 |
April | 0.00 | 0.264302E+09 | 0.247516E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 320289.23 | 40125635.55 |
May | 0.00 | 0.271704E+09 | 0.255532E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2188655.65 | 26185817.30 |
June | 0.00 | 0.262205E+09 | 0.247163E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10733043.38 | 11988740.97 |
July | 0.00 | 0.273836E+09 | 0.255885E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13876753.51 | 4832682.54 |
August | 0.00 | 0.270620E+09 | 0.255355E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9895293.66 | 7306205.78 |
September | 0.00 | 0.264373E+09 | 0.247516E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3825297.24 | 16110693.19 |
October | 0.00 | 0.272752E+09 | 0.255708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 713664.98 | 42886688.68 |
November | 0.00 | 0.263254E+09 | 0.247340E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70137997.97 |
December | 0.00 | 0.273872E+09 | 0.255885E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93407184.69 |
Annual Sum or Average | 0.00 | 0.320668E+10 | 0.300992E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41552997.65 | 0.542237E+09 |
Minimum of Months | 0.00 | 0.246354E+09 | 0.230956E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4832682.54 |
Maximum of Months | 0.00 | 0.273872E+09 | 0.255885E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13876753.51 | 93407184.69 |
Report: SpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.272862E+09 | 0.255778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84241694.49 |
February | 0.273974E+09 | 0.246421E+09 | 0.231020E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5401.97 | 69011072.66 |
March | 0.303685E+09 | 0.270694E+09 | 0.255425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16180.86 | 56095011.56 |
April | 0.293479E+09 | 0.264375E+09 | 0.247584E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 807419.04 | 33180115.34 |
May | 0.303504E+09 | 0.271778E+09 | 0.255602E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3474314.02 | 20060869.73 |
June | 0.293842E+09 | 0.262277E+09 | 0.247231E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13611378.32 | 8035180.00 |
July | 0.303141E+09 | 0.273911E+09 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17777813.93 | 1835252.66 |
August | 0.303685E+09 | 0.270694E+09 | 0.255425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13185575.69 | 3518390.67 |
September | 0.293479E+09 | 0.264446E+09 | 0.247584E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5471069.38 | 10481264.89 |
October | 0.303322E+09 | 0.272827E+09 | 0.255778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1225571.08 | 35440838.58 |
November | 0.293661E+09 | 0.263326E+09 | 0.247408E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62042617.12 |
December | 0.303141E+09 | 0.273947E+09 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86170348.80 |
Annual Sum or Average | 0.357224E+10 | 0.320756E+10 | 0.301074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 55574724.28 | 0.470113E+09 |
Minimum of Months | 0.273974E+09 | 0.246421E+09 | 0.231020E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1835252.66 |
Maximum of Months | 0.303685E+09 | 0.273947E+09 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17777813.93 | 86170348.80 |
Report: SpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.434056E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.307652E+09 |
February | 0.273974E+09 | 0.391995E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9390.25 | 0.252821E+09 |
March | 0.303685E+09 | 0.430607E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 30967.21 | 0.205903E+09 |
April | 0.293479E+09 | 0.420554E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2620009.82 | 0.122729E+09 |
May | 0.303504E+09 | 0.432331E+09 | 0.260888E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11826591.79 | 74038246.84 |
June | 0.293842E+09 | 0.417218E+09 | 0.252344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 48164832.21 | 29446399.71 |
July | 0.303141E+09 | 0.435725E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 63061442.31 | 6784632.15 |
August | 0.303685E+09 | 0.430607E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 46439801.50 | 13157060.80 |
September | 0.293479E+09 | 0.420667E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18378486.11 | 38703380.85 |
October | 0.303322E+09 | 0.434000E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3793572.90 | 0.131109E+09 |
November | 0.293661E+09 | 0.418886E+09 | 0.252524E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.228420E+09 |
December | 0.303141E+09 | 0.435781E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.315916E+09 |
Annual Sum or Average | 0.357224E+10 | 0.510243E+10 | 0.307301E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.194325E+09 | 0.172668E+10 |
Minimum of Months | 0.273974E+09 | 0.391995E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6784632.15 |
Maximum of Months | 0.303685E+09 | 0.435781E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 63061442.31 | 0.315916E+09 |
Report: SpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.434005E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.300417E+09 |
February | 0.273974E+09 | 0.391949E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9987.49 | 0.247011E+09 |
March | 0.303685E+09 | 0.430556E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 31145.40 | 0.203802E+09 |
April | 0.293479E+09 | 0.420505E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2635136.99 | 0.122432E+09 |
May | 0.303504E+09 | 0.432281E+09 | 0.260857E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11832628.22 | 73964483.62 |
June | 0.293842E+09 | 0.417169E+09 | 0.252315E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 48155234.14 | 29437501.09 |
July | 0.303141E+09 | 0.435674E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 63058750.71 | 6784089.07 |
August | 0.303685E+09 | 0.430556E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 46455488.02 | 13147097.68 |
September | 0.293479E+09 | 0.420618E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18436356.61 | 38639468.90 |
October | 0.303322E+09 | 0.433949E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3826103.28 | 0.129581E+09 |
November | 0.293661E+09 | 0.418837E+09 | 0.252495E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222532E+09 |
December | 0.303141E+09 | 0.435730E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.306768E+09 |
Annual Sum or Average | 0.357224E+10 | 0.510183E+10 | 0.307265E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.194441E+09 | 0.169451E+10 |
Minimum of Months | 0.273974E+09 | 0.391949E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6784089.07 |
Maximum of Months | 0.303685E+09 | 0.435730E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 63058750.71 | 0.306768E+09 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.385223E+10 | 0.133160E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.365324E+09 |
February | 0.348285E+10 | 0.120231E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20964.08 | 0.297939E+09 |
March | 0.387034E+10 | 0.133570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99215.10 | 0.238352E+09 |
April | 0.373454E+10 | 0.128645E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4899224.85 | 0.139256E+09 |
May | 0.386038E+10 | 0.133391E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18951644.01 | 84691028.18 |
June | 0.374269E+10 | 0.129235E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60979227.74 | 35830292.92 |
July | 0.385223E+10 | 0.132801E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76631270.86 | 11031927.55 |
August | 0.386853E+10 | 0.133622E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56810238.74 | 19208200.89 |
September | 0.373273E+10 | 0.128696E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25849366.09 | 49066306.92 |
October | 0.385404E+10 | 0.133109E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5888860.76 | 0.153882E+09 |
November | 0.372639E+10 | 0.129132E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.266404E+09 |
December | 0.385223E+10 | 0.132801E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.375008E+09 |
Annual Sum or Average | 0.454292E+11 | 0.156839E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.250130E+09 | 0.203599E+10 |
Minimum of Months | 0.348285E+10 | 0.120231E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11031927.55 |
Maximum of Months | 0.387034E+10 | 0.133622E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76631270.86 | 0.375008E+09 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.434056E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.306834E+09 |
February | 0.273974E+09 | 0.391995E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7917.97 | 0.252224E+09 |
March | 0.303685E+09 | 0.430607E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 28695.18 | 0.204996E+09 |
April | 0.293479E+09 | 0.420554E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2513666.17 | 0.122124E+09 |
May | 0.303504E+09 | 0.432331E+09 | 0.260888E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11570520.06 | 73586088.37 |
June | 0.293842E+09 | 0.417218E+09 | 0.252344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 47746491.35 | 29471214.47 |
July | 0.303141E+09 | 0.435725E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 62474613.29 | 6878685.99 |
August | 0.303685E+09 | 0.430607E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 45825781.60 | 13181242.08 |
September | 0.293479E+09 | 0.420667E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18020825.54 | 38731864.45 |
October | 0.303322E+09 | 0.434000E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3678533.77 | 0.130814E+09 |
November | 0.293661E+09 | 0.418886E+09 | 0.252524E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.227891E+09 |
December | 0.303141E+09 | 0.435781E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.314908E+09 |
Annual Sum or Average | 0.357224E+10 | 0.510243E+10 | 0.307301E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.191867E+09 | 0.172164E+10 |
Minimum of Months | 0.273974E+09 | 0.391995E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6878685.99 |
Maximum of Months | 0.303685E+09 | 0.435781E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 62474613.29 | 0.314908E+09 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.434005E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.300251E+09 |
February | 0.273974E+09 | 0.391949E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8104.54 | 0.247003E+09 |
March | 0.303685E+09 | 0.430556E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 28876.14 | 0.201851E+09 |
April | 0.293479E+09 | 0.420505E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2515994.78 | 0.121097E+09 |
May | 0.303504E+09 | 0.432281E+09 | 0.260857E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11580424.54 | 73337181.76 |
June | 0.293842E+09 | 0.417169E+09 | 0.252315E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 47725231.51 | 29472008.56 |
July | 0.303141E+09 | 0.435674E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 62473755.52 | 6891886.06 |
August | 0.303685E+09 | 0.430556E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 45903013.39 | 13151914.54 |
September | 0.293479E+09 | 0.420618E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18120420.86 | 38483118.05 |
October | 0.303322E+09 | 0.433949E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3703677.76 | 0.128350E+09 |
November | 0.293661E+09 | 0.418837E+09 | 0.252495E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222576E+09 |
December | 0.303141E+09 | 0.435730E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.307154E+09 |
Annual Sum or Average | 0.357224E+10 | 0.510183E+10 | 0.307265E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192059E+09 | 0.168962E+10 |
Minimum of Months | 0.273974E+09 | 0.391949E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6891886.06 |
Maximum of Months | 0.303685E+09 | 0.435730E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 62473755.52 | 0.307154E+09 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.272862E+09 | 0.255778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159353E+09 |
February | 0.273974E+09 | 0.246421E+09 | 0.231020E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3763.47 | 0.130703E+09 |
March | 0.303685E+09 | 0.270694E+09 | 0.255425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14475.74 | 0.105891E+09 |
April | 0.293479E+09 | 0.264375E+09 | 0.247584E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1291858.52 | 62738809.15 |
May | 0.303504E+09 | 0.271778E+09 | 0.255602E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5935932.74 | 37700053.07 |
June | 0.293842E+09 | 0.262277E+09 | 0.247231E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 24480929.83 | 15062911.21 |
July | 0.303141E+09 | 0.273911E+09 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 32002987.85 | 3512054.54 |
August | 0.303685E+09 | 0.270694E+09 | 0.255425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 23476434.62 | 6730900.48 |
September | 0.293479E+09 | 0.264446E+09 | 0.247584E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9193184.66 | 19895385.14 |
October | 0.303322E+09 | 0.272827E+09 | 0.255778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1858917.23 | 67568869.78 |
November | 0.293661E+09 | 0.263326E+09 | 0.247408E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118007E+09 |
December | 0.303141E+09 | 0.273947E+09 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163576E+09 |
Annual Sum or Average | 0.357224E+10 | 0.320756E+10 | 0.301074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 98258484.64 | 0.890740E+09 |
Minimum of Months | 0.273974E+09 | 0.246421E+09 | 0.231020E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3512054.54 |
Maximum of Months | 0.303685E+09 | 0.273947E+09 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 32002987.85 | 0.163576E+09 |
Report: SpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.396945E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.749262E+09 |
February | 0.415303E+11 | 0.358405E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 88112.31 | 0.613069E+09 |
March | 0.461508E+11 | 0.398168E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 252964.76 | 0.497682E+09 |
April | 0.445315E+11 | 0.383486E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 9874515.53 | 0.298393E+09 |
May | 0.460320E+11 | 0.397633E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 36996957.52 | 0.188605E+09 |
June | 0.446286E+11 | 0.385245E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122927E+09 | 82955432.03 |
July | 0.459349E+11 | 0.395874E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157761E+09 | 27611017.45 |
August | 0.461292E+11 | 0.398321E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120212E+09 | 44514963.24 |
September | 0.445099E+11 | 0.383639E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 57998775.32 | 0.107973E+09 |
October | 0.459565E+11 | 0.396792E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 14503709.20 | 0.321109E+09 |
November | 0.444343E+11 | 0.384939E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.551415E+09 |
December | 0.459349E+11 | 0.395874E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.768578E+09 |
Annual Sum or Average | 0.541708E+12 | 0.467532E+11 | 0.175857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.520615E+09 | 0.425117E+10 |
Minimum of Months | 0.415303E+11 | 0.358405E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27611017.45 |
Maximum of Months | 0.461508E+11 | 0.398321E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157761E+09 | 0.768578E+09 |
Report: SpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.396945E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.750527E+09 |
February | 0.415303E+11 | 0.358405E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 85304.46 | 0.614301E+09 |
March | 0.461508E+11 | 0.398168E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 241964.32 | 0.499440E+09 |
April | 0.445315E+11 | 0.383486E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 9486138.98 | 0.300335E+09 |
May | 0.460320E+11 | 0.397633E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 36076188.37 | 0.190542E+09 |
June | 0.446286E+11 | 0.385245E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121188E+09 | 84130968.72 |
July | 0.459349E+11 | 0.395874E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155684E+09 | 28363854.50 |
August | 0.461292E+11 | 0.398321E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118567E+09 | 45478957.03 |
September | 0.445099E+11 | 0.383639E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 57172274.13 | 0.109504E+09 |
October | 0.459565E+11 | 0.396792E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 14280580.26 | 0.322767E+09 |
November | 0.444343E+11 | 0.384939E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.552846E+09 |
December | 0.459349E+11 | 0.395874E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.769784E+09 |
Annual Sum or Average | 0.541708E+12 | 0.467532E+11 | 0.175857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.512781E+09 | 0.426802E+10 |
Minimum of Months | 0.415303E+11 | 0.358405E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28363854.50 |
Maximum of Months | 0.461508E+11 | 0.398321E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155684E+09 | 0.769784E+09 |
Report: SpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.408770E+10 | 0.105977E+10 | 0.338870E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.721501E+09 |
February | 0.369574E+10 | 0.956878E+09 | 0.306077E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.595102E+09 |
March | 0.410691E+10 | 0.106304E+10 | 0.338870E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.495992E+09 |
April | 0.396281E+10 | 0.102384E+10 | 0.327939E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 1143871.12 | 0.307915E+09 |
May | 0.409635E+10 | 0.106161E+10 | 0.338870E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 12706448.70 | 0.195201E+09 |
June | 0.397146E+10 | 0.102854E+10 | 0.327939E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 76638013.55 | 82086167.60 |
July | 0.408770E+10 | 0.105691E+10 | 0.338870E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.100784E+09 | 25456084.33 |
August | 0.410499E+10 | 0.106345E+10 | 0.338870E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 69870226.11 | 44805464.29 |
September | 0.396089E+10 | 0.102425E+10 | 0.327939E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 23771806.34 | 0.113345E+09 |
October | 0.408962E+10 | 0.105936E+10 | 0.338870E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 3976011.59 | 0.328140E+09 |
November | 0.395417E+10 | 0.102772E+10 | 0.327939E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.543650E+09 |
December | 0.408770E+10 | 0.105691E+10 | 0.338870E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.738967E+09 |
Annual Sum or Average | 0.482060E+11 | 0.124823E+11 | 0.398993E+12 | 0.359593E+12 | 0.00 | 0.00 | 0.00 | 0.288890E+09 | 0.419216E+10 |
Minimum of Months | 0.369574E+10 | 0.956878E+09 | 0.306077E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 25456084.33 |
Maximum of Months | 0.410691E+10 | 0.106345E+10 | 0.338870E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.100784E+09 | 0.738967E+09 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.407704E+10 | 0.140929E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.648337E+09 |
February | 0.368610E+10 | 0.127246E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32044.69 | 0.528838E+09 |
March | 0.409620E+10 | 0.141364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 164058.80 | 0.423316E+09 |
April | 0.395248E+10 | 0.136151E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8728798.14 | 0.245626E+09 |
May | 0.408566E+10 | 0.141173E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34030340.07 | 0.147297E+09 |
June | 0.396110E+10 | 0.136775E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112643E+09 | 58574350.07 |
July | 0.407704E+10 | 0.140549E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144785E+09 | 12996317.10 |
August | 0.409429E+10 | 0.141418E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108602E+09 | 25404011.03 |
September | 0.395056E+10 | 0.136205E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48847621.90 | 76536770.00 |
October | 0.407896E+10 | 0.140875E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11597085.59 | 0.266783E+09 |
November | 0.394385E+10 | 0.136667E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.472612E+09 |
December | 0.407704E+10 | 0.140549E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.665605E+09 |
Annual Sum or Average | 0.480803E+11 | 0.165990E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.469430E+09 | 0.357192E+10 |
Minimum of Months | 0.368610E+10 | 0.127246E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12996317.10 |
Maximum of Months | 0.409620E+10 | 0.141418E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144785E+09 | 0.665605E+09 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 11501.89 | 02-JAN-00:10 | 13517.00 | 02-JAN-20:10 | 10113.80 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 11501.89 | 01-FEB-00:10 | 13517.00 | 01-FEB-20:10 | 10113.80 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 11501.89 | 01-MAR-00:10 | 13517.00 | 01-MAR-20:10 | 10113.80 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 11501.89 | 01-APR-00:10 | 13517.00 | 03-APR-19:10 | 10113.80 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 11501.89 | 01-MAY-00:10 | 13517.00 | 01-MAY-19:10 | 10113.80 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 11501.89 | 01-JUN-00:10 | 13517.00 | 01-JUN-19:10 | 10113.80 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 11501.89 | 01-JUL-00:10 | 13517.00 | 03-JUL-19:10 | 10113.80 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 11501.89 | 01-AUG-00:10 | 13517.00 | 01-AUG-19:10 | 10113.80 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 11501.89 | 01-SEP-00:10 | 13517.00 | 01-SEP-19:10 | 10113.80 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 11501.89 | 01-OCT-23:10 | 13517.00 | 02-OCT-19:10 | 10113.80 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 11501.89 | 01-NOV-00:10 | 13517.00 | 01-NOV-19:10 | 10113.80 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 11501.89 | 01-DEC-00:10 | 13517.00 | 01-DEC-20:10 | 10113.80 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 11501.89 | 13517.00 | 10113.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 11501.89 | 13517.00 | 10113.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1169.53 | 02-JAN-00:10 | 687.30 | 02-JAN-20:10 | 685.60 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 320.31 | 21-JAN-07:00 |
February | 1169.53 | 01-FEB-00:10 | 687.30 | 01-FEB-20:10 | 685.60 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 299.58 | 04-FEB-06:50 |
March | 1169.53 | 01-MAR-00:10 | 687.30 | 01-MAR-20:10 | 685.60 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.22 | 08-MAR-17:00 | 268.33 | 05-MAR-07:00 |
April | 1169.53 | 01-APR-00:10 | 687.30 | 03-APR-19:10 | 685.60 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.79 | 13-APR-17:00 | 203.83 | 08-APR-06:00 |
May | 1169.53 | 01-MAY-00:10 | 687.30 | 01-MAY-19:10 | 685.60 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 86.11 | 22-MAY-13:00 | 172.12 | 07-MAY-05:00 |
June | 1169.53 | 01-JUN-00:10 | 687.30 | 01-JUN-19:10 | 685.60 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 163.71 | 28-JUN-16:00 | 135.91 | 09-JUN-05:00 |
July | 1169.53 | 01-JUL-00:10 | 687.30 | 03-JUL-19:10 | 685.60 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 155.45 | 21-JUL-17:00 | 49.01 | 08-JUL-03:20 |
August | 1169.53 | 01-AUG-00:10 | 687.30 | 01-AUG-19:10 | 685.60 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 127.96 | 01-AUG-16:00 | 82.80 | 31-AUG-06:00 |
September | 1169.53 | 01-SEP-00:10 | 687.30 | 01-SEP-19:10 | 685.60 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 94.52 | 02-SEP-17:00 | 106.44 | 09-SEP-06:00 |
October | 1169.53 | 01-OCT-23:10 | 687.30 | 02-OCT-19:10 | 685.60 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 63.42 | 01-OCT-16:00 | 254.59 | 26-OCT-07:00 |
November | 1169.53 | 01-NOV-00:10 | 687.30 | 01-NOV-19:10 | 685.60 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 272.99 | 27-NOV-06:00 |
December | 1169.53 | 01-DEC-00:10 | 687.30 | 01-DEC-20:10 | 685.60 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 334.77 | 15-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1169.53 | 687.30 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.01 | |||||
Maximum of Months | 1169.53 | 687.30 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 163.71 | 334.77 |
Report: PeakSpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1354.32 | 02-JAN-00:10 | 795.89 | 02-JAN-20:10 | 793.93 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 123.76 | 21-JAN-07:00 |
February | 1354.32 | 01-FEB-00:10 | 795.89 | 01-FEB-20:10 | 793.93 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.48 | 14-FEB-16:00 | 115.62 | 04-FEB-07:00 |
March | 1354.32 | 01-MAR-00:10 | 795.89 | 01-MAR-20:10 | 793.93 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.68 | 08-MAR-14:00 | 103.58 | 05-MAR-07:00 |
April | 1354.32 | 01-APR-00:10 | 795.89 | 03-APR-19:10 | 793.93 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.85 | 13-APR-17:00 | 78.67 | 08-APR-06:00 |
May | 1354.32 | 01-MAY-00:10 | 795.89 | 01-MAY-19:10 | 793.93 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.23 | 22-MAY-13:00 | 66.46 | 07-MAY-05:00 |
June | 1354.32 | 01-JUN-00:10 | 795.89 | 01-JUN-19:10 | 793.93 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 63.85 | 28-JUN-16:00 | 52.43 | 09-JUN-05:00 |
July | 1354.32 | 01-JUL-00:10 | 795.89 | 03-JUL-19:10 | 793.93 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.66 | 22-JUL-15:00 | 19.00 | 08-JUL-03:00 |
August | 1354.32 | 01-AUG-00:10 | 795.89 | 01-AUG-19:10 | 793.93 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 50.67 | 20-AUG-15:00 | 32.40 | 31-AUG-06:00 |
September | 1354.32 | 01-SEP-00:10 | 795.89 | 01-SEP-19:10 | 793.93 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.84 | 03-SEP-14:00 | 41.17 | 20-SEP-06:00 |
October | 1354.32 | 01-OCT-23:10 | 795.89 | 02-OCT-19:10 | 793.93 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.13 | 01-OCT-16:00 | 98.28 | 26-OCT-07:00 |
November | 1354.32 | 01-NOV-00:10 | 795.89 | 01-NOV-19:10 | 793.93 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 105.37 | 27-NOV-07:00 |
December | 1354.32 | 01-DEC-00:10 | 795.89 | 01-DEC-20:10 | 793.93 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 129.22 | 15-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1354.32 | 795.89 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.00 | |||||
Maximum of Months | 1354.32 | 795.89 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 63.85 | 129.22 |
Report: PeakSpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 286.42 | 02-JAN-00:10 | 1487.69 | 02-JAN-20:10 | 839.45 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 292.54 | 21-JAN-07:00 |
February | 286.42 | 01-FEB-00:10 | 1487.69 | 01-FEB-20:10 | 839.45 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.57 | 14-FEB-16:00 | 273.25 | 04-FEB-07:00 |
March | 286.42 | 01-MAR-00:10 | 1487.69 | 01-MAR-20:10 | 839.45 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.81 | 08-MAR-14:00 | 244.84 | 05-MAR-07:00 |
April | 286.42 | 01-APR-00:10 | 1487.69 | 03-APR-19:10 | 839.45 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.55 | 13-APR-17:00 | 185.94 | 08-APR-06:00 |
May | 286.42 | 01-MAY-00:10 | 1487.69 | 01-MAY-19:10 | 839.45 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 78.55 | 22-MAY-13:00 | 157.02 | 07-MAY-05:00 |
June | 286.42 | 01-JUN-00:10 | 1487.69 | 01-JUN-19:10 | 839.45 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 150.90 | 28-JUN-16:00 | 123.93 | 09-JUN-05:00 |
July | 286.42 | 01-JUL-00:10 | 1487.69 | 03-JUL-19:10 | 839.45 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 145.72 | 22-JUL-15:00 | 44.67 | 08-JUL-03:00 |
August | 286.42 | 01-AUG-00:10 | 1487.69 | 01-AUG-19:10 | 839.45 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 119.74 | 20-AUG-15:00 | 75.52 | 31-AUG-06:00 |
September | 286.42 | 01-SEP-00:10 | 1487.69 | 01-SEP-19:10 | 839.45 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 101.22 | 03-SEP-14:00 | 97.08 | 09-SEP-06:00 |
October | 286.42 | 01-OCT-23:10 | 1487.69 | 02-OCT-19:10 | 839.45 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 68.83 | 01-OCT-16:00 | 232.26 | 26-OCT-07:00 |
November | 286.42 | 01-NOV-00:10 | 1487.69 | 01-NOV-19:10 | 839.45 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 249.01 | 27-NOV-07:00 |
December | 286.42 | 01-DEC-00:10 | 1487.69 | 01-DEC-20:10 | 839.45 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 305.37 | 15-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 286.42 | 1487.69 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.67 | |||||
Maximum of Months | 286.42 | 1487.69 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 150.90 | 305.37 |
Report: PeakSpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 220.32 | 02-JAN-00:10 | 273.10 | 02-JAN-20:10 | 242.16 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 168.77 | 21-JAN-07:00 |
February | 220.32 | 01-FEB-00:10 | 273.10 | 01-FEB-20:10 | 242.16 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.10 | 14-FEB-16:00 | 157.65 | 04-FEB-06:00 |
March | 220.32 | 01-MAR-00:10 | 273.10 | 01-MAR-20:10 | 242.16 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.12 | 08-MAR-14:00 | 141.26 | 05-MAR-07:00 |
April | 220.32 | 01-APR-00:10 | 273.10 | 03-APR-19:10 | 242.16 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.71 | 13-APR-17:00 | 107.28 | 08-APR-06:00 |
May | 220.32 | 01-MAY-00:10 | 273.10 | 01-MAY-19:10 | 242.16 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 45.32 | 22-MAY-13:00 | 90.60 | 07-MAY-05:00 |
June | 220.32 | 01-JUN-00:10 | 273.10 | 01-JUN-19:10 | 242.16 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 87.06 | 28-JUN-16:00 | 71.50 | 09-JUN-05:00 |
July | 220.32 | 01-JUL-00:10 | 273.10 | 03-JUL-19:10 | 242.16 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 84.06 | 22-JUL-15:00 | 25.77 | 08-JUL-03:40 |
August | 220.32 | 01-AUG-00:10 | 273.10 | 01-AUG-19:10 | 242.16 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 69.09 | 20-AUG-15:00 | 43.57 | 31-AUG-06:00 |
September | 220.32 | 01-SEP-00:10 | 273.10 | 01-SEP-19:10 | 242.16 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 58.41 | 03-SEP-14:00 | 56.02 | 09-SEP-06:00 |
October | 220.32 | 01-OCT-23:10 | 273.10 | 02-OCT-19:10 | 242.16 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.72 | 01-OCT-16:00 | 134.00 | 26-OCT-07:00 |
November | 220.32 | 01-NOV-00:10 | 273.10 | 01-NOV-19:10 | 242.16 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 143.66 | 27-NOV-06:40 |
December | 220.32 | 01-DEC-00:10 | 273.10 | 01-DEC-20:10 | 242.16 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 176.19 | 15-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 220.32 | 273.10 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.77 | |||||
Maximum of Months | 220.32 | 273.10 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 87.06 | 176.19 |
Report: PeakSpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 907.20 | 02-JAN-00:10 | 337.37 | 02-JAN-20:10 | 4572.80 | 02-JAN-20:10 | 39726.58 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 399.29 | 21-JAN-07:00 |
February | 907.20 | 01-FEB-00:10 | 337.37 | 01-FEB-20:10 | 4572.80 | 01-FEB-20:10 | 39726.58 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 14.46 | 14-FEB-16:00 | 373.14 | 04-FEB-06:50 |
March | 907.20 | 01-MAR-00:10 | 337.37 | 01-MAR-20:10 | 4572.80 | 01-MAR-20:10 | 39726.58 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 21.76 | 08-MAR-16:00 | 334.17 | 05-MAR-07:00 |
April | 907.20 | 01-APR-00:10 | 337.37 | 03-APR-19:10 | 4572.80 | 03-APR-19:10 | 39726.58 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 60.83 | 13-APR-17:00 | 253.68 | 08-APR-06:00 |
May | 907.20 | 01-MAY-00:10 | 337.37 | 01-MAY-19:10 | 4572.80 | 01-MAY-19:10 | 39726.58 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 107.03 | 22-MAY-13:00 | 214.44 | 07-MAY-05:00 |
June | 907.20 | 01-JUN-00:10 | 337.37 | 01-JUN-19:10 | 4572.80 | 01-JUN-19:10 | 39726.58 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 205.91 | 28-JUN-16:00 | 169.22 | 09-JUN-04:50 |
July | 907.20 | 01-JUL-00:10 | 337.37 | 03-JUL-19:10 | 4572.80 | 03-JUL-19:10 | 39726.58 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 199.00 | 22-JUL-15:00 | 70.68 | 07-JUL-21:00 |
August | 907.20 | 01-AUG-00:10 | 337.37 | 01-AUG-19:10 | 4572.80 | 01-AUG-19:10 | 39726.58 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 163.45 | 20-AUG-15:20 | 103.17 | 31-AUG-06:00 |
September | 907.20 | 01-SEP-00:10 | 337.37 | 01-SEP-19:10 | 4572.80 | 01-SEP-19:10 | 39726.58 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 138.10 | 03-SEP-14:00 | 132.60 | 09-SEP-06:00 |
October | 907.20 | 01-OCT-23:10 | 337.37 | 02-OCT-19:10 | 4572.80 | 02-OCT-19:10 | 39726.58 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 94.10 | 01-OCT-16:00 | 322.72 | 27-OCT-07:00 |
November | 907.20 | 01-NOV-00:10 | 337.37 | 01-NOV-19:10 | 4572.80 | 01-NOV-19:10 | 39726.58 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 340.25 | 27-NOV-06:00 |
December | 907.20 | 01-DEC-00:10 | 337.37 | 01-DEC-20:10 | 4572.80 | 01-DEC-20:10 | 39726.58 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 417.07 | 15-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 907.20 | 337.37 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 70.68 | ||||||
Maximum of Months | 907.20 | 337.37 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 205.91 | 417.07 |
Report: PeakSpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 15368.40 | 02-JAN-00:10 | 2177.23 | 02-JAN-20:10 | 965.27 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 708.91 | 21-JAN-07:00 |
February | 15368.40 | 01-FEB-00:10 | 2177.23 | 01-FEB-20:10 | 965.27 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 662.38 | 04-FEB-06:40 |
March | 15368.40 | 01-MAR-00:10 | 2177.23 | 01-MAR-20:10 | 965.27 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.00 | 08-MAR-16:00 | 593.35 | 05-MAR-07:00 |
April | 15368.40 | 01-APR-00:10 | 2177.23 | 03-APR-19:10 | 965.27 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 107.90 | 13-APR-17:00 | 450.66 | 08-APR-06:00 |
May | 15368.40 | 01-MAY-00:10 | 2177.23 | 01-MAY-19:10 | 965.27 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 190.22 | 22-MAY-13:00 | 380.59 | 07-MAY-05:00 |
June | 15368.40 | 01-JUN-00:10 | 2177.23 | 01-JUN-19:10 | 965.27 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 365.58 | 28-JUN-16:00 | 300.34 | 09-JUN-04:50 |
July | 15368.40 | 01-JUL-00:10 | 2177.23 | 03-JUL-19:10 | 965.27 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 348.08 | 22-JUL-15:00 | 113.05 | 08-JUL-03:00 |
August | 15368.40 | 01-AUG-00:10 | 2177.23 | 01-AUG-19:10 | 965.27 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 288.68 | 20-AUG-16:00 | 183.17 | 31-AUG-06:00 |
September | 15368.40 | 01-SEP-00:10 | 2177.23 | 01-SEP-19:10 | 965.27 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 215.58 | 03-SEP-14:00 | 235.40 | 09-SEP-06:00 |
October | 15368.40 | 01-OCT-23:10 | 2177.23 | 02-OCT-19:10 | 965.27 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 154.75 | 01-OCT-16:00 | 562.88 | 26-OCT-07:00 |
November | 15368.40 | 01-NOV-00:10 | 2177.23 | 01-NOV-19:10 | 965.27 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 603.64 | 27-NOV-06:50 |
December | 15368.40 | 01-DEC-00:10 | 2177.23 | 01-DEC-20:10 | 965.27 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 740.01 | 15-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 15368.40 | 2177.23 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 113.05 | |||||
Maximum of Months | 15368.40 | 2177.23 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 365.58 | 740.01 |
Report: PeakSpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 45622.98 | 02-JAN-00:10 | 11849.32 | 02-JAN-20:10 | 10029.21 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2025.45 | 21-JAN-07:00 |
February | 45622.98 | 01-FEB-00:10 | 11849.32 | 01-FEB-20:10 | 10029.21 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 62.68 | 14-FEB-16:00 | 1891.88 | 04-FEB-06:20 |
March | 45622.98 | 01-MAR-00:10 | 11849.32 | 01-MAR-20:10 | 10029.21 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 109.21 | 08-MAR-16:00 | 1695.34 | 05-MAR-07:00 |
April | 45622.98 | 01-APR-00:10 | 11849.32 | 03-APR-19:10 | 10029.21 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 308.37 | 13-APR-17:00 | 1287.46 | 08-APR-06:00 |
May | 45622.98 | 01-MAY-00:10 | 11849.32 | 01-MAY-19:10 | 10029.21 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 543.77 | 22-MAY-13:00 | 1087.44 | 07-MAY-05:00 |
June | 45622.98 | 01-JUN-00:10 | 11849.32 | 01-JUN-19:10 | 10029.21 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1044.77 | 28-JUN-16:00 | 870.89 | 09-JUN-05:00 |
July | 45622.98 | 01-JUL-00:10 | 11849.32 | 03-JUL-19:10 | 10029.21 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1008.85 | 22-JUL-15:00 | 344.77 | 08-JUL-03:00 |
August | 45622.98 | 01-AUG-00:10 | 11849.32 | 01-AUG-19:10 | 10029.21 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 829.04 | 20-AUG-15:00 | 547.37 | 31-AUG-06:00 |
September | 45622.98 | 01-SEP-00:10 | 11849.32 | 01-SEP-19:10 | 10029.21 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 696.73 | 03-SEP-14:00 | 694.09 | 25-SEP-05:00 |
October | 45622.98 | 01-OCT-23:10 | 11849.32 | 02-OCT-19:10 | 10029.21 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 476.44 | 01-OCT-16:00 | 1608.22 | 26-OCT-07:00 |
November | 45622.98 | 01-NOV-00:10 | 11849.32 | 01-NOV-19:10 | 10029.21 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1724.21 | 27-NOV-06:30 |
December | 45622.98 | 01-DEC-00:10 | 11849.32 | 01-DEC-20:10 | 10029.21 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 2114.66 | 15-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 45622.98 | 11849.32 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 344.77 | |||||
Maximum of Months | 45622.98 | 11849.32 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 1044.77 | 2114.66 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 392.73 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 187.07 | 21-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 392.73 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.84 | 14-FEB-16:10 | 174.80 | 04-FEB-06:00 |
March | 180.00 | 01-MAR-00:10 | 392.73 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.63 | 08-MAR-16:07 | 156.72 | 05-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 392.73 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.49 | 13-APR-17:00 | 119.24 | 08-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 392.73 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.74 | 19-MAY-15:09 | 100.83 | 07-MAY-05:00 |
June | 180.00 | 01-JUN-00:10 | 392.73 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 95.19 | 28-JUN-16:00 | 79.75 | 09-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 392.73 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 89.42 | 21-JUL-17:00 | 32.18 | 01-JUL-08:00 |
August | 180.00 | 01-AUG-00:10 | 392.73 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.27 | 01-AUG-15:10 | 48.95 | 31-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 392.73 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 57.10 | 02-SEP-15:10 | 62.68 | 09-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 392.73 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.95 | 01-OCT-16:00 | 148.72 | 26-OCT-07:00 |
November | 180.00 | 01-NOV-00:10 | 392.73 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 159.37 | 27-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 392.73 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 195.27 | 15-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 392.73 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.18 | |||||
Maximum of Months | 180.00 | 392.73 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 95.19 | 195.27 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 392.68 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 187.05 | 21-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 392.68 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.84 | 14-FEB-16:10 | 174.78 | 04-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 392.68 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.63 | 08-MAR-16:09 | 156.71 | 05-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 392.68 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.49 | 13-APR-17:00 | 119.23 | 08-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 392.68 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.74 | 19-MAY-15:07 | 100.82 | 07-MAY-05:00 |
June | 180.00 | 01-JUN-00:10 | 392.68 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 95.19 | 28-JUN-16:00 | 79.75 | 09-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 392.68 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 89.81 | 22-JUL-15:10 | 32.18 | 01-JUL-08:00 |
August | 180.00 | 01-AUG-00:10 | 392.68 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.31 | 20-AUG-15:10 | 48.94 | 31-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 392.68 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 57.10 | 02-SEP-15:10 | 62.68 | 09-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 392.68 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.95 | 01-OCT-16:00 | 148.71 | 26-OCT-07:00 |
November | 180.00 | 01-NOV-00:10 | 392.68 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 159.36 | 27-NOV-06:50 |
December | 180.00 | 01-DEC-00:10 | 392.68 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 195.25 | 15-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 392.68 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.18 | |||||
Maximum of Months | 180.00 | 392.68 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 95.19 | 195.25 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 01-JAN-00:10 | 246.81 | 01-JAN-19:10 | 232.19 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 50.67 | 26-JAN-04:00 |
February | 0.00 | 01-FEB-00:10 | 246.81 | 01-FEB-20:10 | 232.19 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 48.17 | 05-FEB-08:10 |
March | 0.00 | 01-MAR-00:10 | 246.81 | 01-MAR-20:10 | 232.19 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 43.59 | 05-MAR-07:00 |
April | 0.00 | 01-APR-00:10 | 246.81 | 01-APR-18:10 | 232.19 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.22 | 13-APR-17:00 | 34.66 | 06-APR-06:10 |
May | 0.00 | 01-MAY-00:10 | 246.81 | 01-MAY-19:10 | 232.19 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.26 | 22-MAY-13:00 | 30.07 | 07-MAY-05:00 |
June | 0.00 | 01-JUN-00:10 | 246.81 | 01-JUN-19:10 | 232.19 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.23 | 28-JUN-16:00 | 24.84 | 09-JUN-05:10 |
July | 0.00 | 01-JUL-00:10 | 246.81 | 01-JUL-18:10 | 232.19 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.32 | 22-JUL-15:00 | 11.77 | 08-JUL-03:30 |
August | 0.00 | 01-AUG-00:10 | 246.81 | 01-AUG-19:10 | 232.19 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.65 | 20-AUG-15:00 | 17.29 | 31-AUG-06:00 |
September | 0.00 | 01-SEP-00:10 | 246.81 | 01-SEP-19:10 | 232.19 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.35 | 03-SEP-14:00 | 21.07 | 25-SEP-05:00 |
October | 0.00 | 01-OCT-00:10 | 246.81 | 01-OCT-18:10 | 232.19 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.55 | 01-OCT-16:00 | 43.35 | 27-OCT-07:00 |
November | 0.00 | 01-NOV-00:10 | 246.81 | 01-NOV-19:10 | 232.19 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 45.55 | 28-NOV-08:00 |
December | 0.00 | 01-DEC-00:10 | 246.81 | 01-DEC-20:10 | 232.19 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 53.18 | 15-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 0.00 | 246.81 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.77 | |||||
Maximum of Months | 0.00 | 246.81 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 23.23 | 53.18 |
Report: PeakSpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 246.88 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 52.21 | 21-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 246.88 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.35 | 14-FEB-16:05 | 48.78 | 04-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 246.88 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.41 | 08-MAR-16:06 | 43.74 | 05-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 246.88 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 13-APR-17:00 | 33.28 | 08-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 246.88 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.60 | 19-MAY-15:20 | 28.14 | 07-MAY-05:00 |
June | 180.00 | 01-JUN-00:10 | 246.88 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.57 | 28-JUN-16:00 | 22.26 | 09-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 246.88 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.27 | 22-JUL-15:10 | 8.62 | 01-JUL-08:00 |
August | 180.00 | 01-AUG-00:10 | 246.88 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.03 | 20-AUG-15:10 | 13.66 | 31-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 246.88 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.94 | 02-SEP-15:10 | 17.49 | 09-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 246.88 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.99 | 01-OCT-16:00 | 41.51 | 26-OCT-07:00 |
November | 180.00 | 01-NOV-00:10 | 246.88 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 44.48 | 27-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 246.88 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 54.50 | 15-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 246.88 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.62 | |||||
Maximum of Months | 180.00 | 246.88 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 26.57 | 54.50 |
Report: PeakSpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 392.73 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 187.07 | 21-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 392.73 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.84 | 14-FEB-16:10 | 174.80 | 04-FEB-06:00 |
March | 180.00 | 01-MAR-00:10 | 392.73 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.63 | 08-MAR-16:09 | 156.72 | 05-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 392.73 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.50 | 13-APR-17:00 | 123.48 | 08-APR-07:20 |
May | 180.00 | 01-MAY-00:10 | 392.73 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.75 | 19-MAY-15:20 | 100.83 | 07-MAY-05:00 |
June | 180.00 | 01-JUN-00:10 | 392.73 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 95.19 | 28-JUN-16:00 | 79.75 | 09-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 392.73 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 90.54 | 22-JUL-15:10 | 32.19 | 01-JUL-08:00 |
August | 180.00 | 01-AUG-00:10 | 392.73 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.34 | 20-AUG-15:10 | 48.95 | 31-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 392.73 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 57.10 | 02-SEP-15:07 | 62.68 | 09-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 392.73 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.95 | 01-OCT-16:00 | 148.72 | 26-OCT-07:00 |
November | 180.00 | 01-NOV-00:10 | 392.73 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 159.37 | 27-NOV-06:50 |
December | 180.00 | 01-DEC-00:10 | 392.73 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 195.27 | 15-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 392.73 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.19 | |||||
Maximum of Months | 180.00 | 392.73 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 95.19 | 195.27 |
Report: PeakSpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 392.68 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 187.06 | 21-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 392.68 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.84 | 14-FEB-16:07 | 174.78 | 04-FEB-06:00 |
March | 180.00 | 01-MAR-00:10 | 392.68 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.63 | 08-MAR-16:06 | 156.71 | 05-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 392.68 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.50 | 13-APR-17:00 | 122.48 | 08-APR-07:20 |
May | 180.00 | 01-MAY-00:10 | 392.68 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.74 | 19-MAY-15:20 | 100.82 | 07-MAY-05:00 |
June | 180.00 | 01-JUN-00:10 | 392.68 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 95.18 | 28-JUN-16:00 | 79.75 | 09-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 392.68 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 90.54 | 22-JUL-15:10 | 32.18 | 01-JUL-08:00 |
August | 180.00 | 01-AUG-00:10 | 392.68 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.34 | 20-AUG-15:10 | 48.94 | 31-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 392.68 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 57.10 | 02-SEP-15:10 | 62.68 | 09-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 392.68 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.95 | 01-OCT-16:00 | 148.71 | 26-OCT-07:00 |
November | 180.00 | 01-NOV-00:10 | 392.68 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 159.36 | 27-NOV-06:50 |
December | 180.00 | 01-DEC-00:10 | 392.68 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 195.25 | 15-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 392.68 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.18 | |||||
Maximum of Months | 180.00 | 392.68 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 95.18 | 195.25 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2263.36 | 02-JAN-00:10 | 1282.60 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 225.37 | 21-JAN-07:00 |
February | 2263.36 | 01-FEB-00:10 | 1282.60 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.80 | 14-FEB-16:00 | 210.54 | 04-FEB-07:00 |
March | 2263.36 | 01-MAR-00:10 | 1282.60 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.82 | 08-MAR-14:00 | 188.68 | 05-MAR-07:00 |
April | 2263.36 | 01-APR-00:10 | 1282.60 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.57 | 13-APR-17:00 | 143.38 | 08-APR-06:00 |
May | 2263.36 | 01-MAY-00:10 | 1282.60 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.95 | 22-MAY-13:00 | 121.13 | 07-MAY-05:00 |
June | 2263.36 | 01-JUN-00:10 | 1282.60 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.07 | 28-JUN-16:00 | 95.64 | 09-JUN-05:00 |
July | 2263.36 | 01-JUL-00:10 | 1282.60 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.14 | 22-JUL-15:00 | 40.11 | 08-JUL-03:00 |
August | 2263.36 | 01-AUG-00:10 | 1282.60 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.58 | 01-AUG-16:00 | 61.81 | 31-AUG-06:00 |
September | 2263.36 | 01-SEP-00:10 | 1282.60 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.53 | 03-SEP-14:00 | 77.85 | 20-SEP-06:00 |
October | 2263.36 | 01-OCT-23:10 | 1282.60 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.45 | 01-OCT-16:00 | 179.01 | 26-OCT-07:00 |
November | 2263.36 | 01-NOV-00:10 | 1282.60 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 191.89 | 27-NOV-06:10 |
December | 2263.36 | 01-DEC-00:10 | 1282.60 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 235.29 | 15-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 2263.36 | 1282.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.11 | ||||
Maximum of Months | 2263.36 | 1282.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.07 | 235.29 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 392.73 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 187.49 | 21-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 392.73 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 14-FEB-16:10 | 175.21 | 04-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 392.73 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.30 | 08-MAR-16:07 | 157.13 | 05-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 392.73 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.17 | 13-APR-17:00 | 119.63 | 08-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 392.73 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.43 | 19-MAY-15:30 | 101.21 | 07-MAY-05:00 |
June | 180.00 | 01-JUN-00:10 | 392.73 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 94.88 | 28-JUN-16:00 | 80.12 | 09-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 392.73 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 89.12 | 21-JUL-17:00 | 32.52 | 01-JUL-08:00 |
August | 180.00 | 01-AUG-00:10 | 392.73 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 74.30 | 01-AUG-16:00 | 49.30 | 31-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 392.73 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.11 | 02-SEP-15:10 | 63.05 | 09-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 392.73 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.63 | 01-OCT-16:00 | 149.12 | 26-OCT-07:00 |
November | 180.00 | 01-NOV-00:10 | 392.73 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 159.77 | 27-NOV-06:50 |
December | 180.00 | 01-DEC-00:10 | 392.73 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 195.69 | 15-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 392.73 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.52 | |||||
Maximum of Months | 180.00 | 392.73 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 94.88 | 195.69 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 392.68 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 187.48 | 21-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 392.68 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 14-FEB-16:10 | 175.20 | 04-FEB-06:00 |
March | 180.00 | 01-MAR-00:10 | 392.68 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.30 | 08-MAR-16:09 | 157.11 | 05-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 392.68 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.16 | 13-APR-17:00 | 119.61 | 08-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 392.68 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.42 | 19-MAY-15:30 | 101.20 | 07-MAY-05:00 |
June | 180.00 | 01-JUN-00:10 | 392.68 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 94.87 | 28-JUN-16:00 | 80.12 | 09-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 392.68 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 89.10 | 21-JUL-17:00 | 32.53 | 01-JUL-08:00 |
August | 180.00 | 01-AUG-00:10 | 392.68 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 74.87 | 01-AUG-15:10 | 49.30 | 31-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 392.68 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.79 | 02-SEP-15:10 | 63.04 | 09-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 392.68 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.62 | 01-OCT-16:00 | 149.11 | 26-OCT-07:00 |
November | 180.00 | 01-NOV-00:10 | 392.68 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 159.76 | 27-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 392.68 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 195.68 | 15-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 392.68 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.53 | |||||
Maximum of Months | 180.00 | 392.68 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 94.87 | 195.68 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 246.88 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 95.93 | 21-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 246.88 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.30 | 14-FEB-16:10 | 89.64 | 04-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 246.88 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.25 | 08-MAR-16:10 | 80.39 | 05-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 246.88 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.90 | 13-APR-17:00 | 61.20 | 08-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 246.88 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.78 | 19-MAY-15:07 | 51.78 | 07-MAY-05:00 |
June | 180.00 | 01-JUN-00:10 | 246.88 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.55 | 28-JUN-16:00 | 40.99 | 09-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 246.88 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.14 | 22-JUL-15:10 | 16.16 | 01-JUL-08:00 |
August | 180.00 | 01-AUG-00:10 | 246.88 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.35 | 01-AUG-15:10 | 25.23 | 31-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 246.88 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.46 | 02-SEP-15:10 | 32.26 | 09-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 246.88 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.59 | 01-OCT-16:00 | 76.29 | 26-OCT-07:00 |
November | 180.00 | 01-NOV-00:10 | 246.88 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 81.75 | 27-NOV-06:50 |
December | 180.00 | 01-DEC-00:10 | 246.88 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 100.12 | 15-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 246.88 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.16 | |||||
Maximum of Months | 180.00 | 246.88 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 48.55 | 100.12 |
Report: PeakSpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 3823.39 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 456.27 | 21-JAN-07:00 |
February | 26988.77 | 01-FEB-00:10 | 3823.39 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.00 | 14-FEB-16:00 | 428.54 | 04-FEB-06:00 |
March | 26988.77 | 01-MAR-00:10 | 3823.39 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.15 | 08-MAR-14:00 | 383.27 | 05-MAR-07:00 |
April | 26988.77 | 01-APR-00:10 | 3823.39 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 64.79 | 13-APR-17:00 | 297.10 | 08-APR-06:00 |
May | 26988.77 | 01-MAY-00:10 | 3823.39 | 01-MAY-19:10 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 120.65 | 22-MAY-13:00 | 245.77 | 07-MAY-05:00 |
June | 26988.77 | 01-JUN-00:10 | 3823.39 | 01-JUN-19:10 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 223.72 | 28-JUN-16:00 | 206.99 | 09-JUN-05:00 |
July | 26988.77 | 01-JUL-00:10 | 3823.39 | 03-JUL-19:10 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 217.66 | 22-JUL-15:00 | 88.11 | 08-JUL-03:00 |
August | 26988.77 | 01-AUG-00:10 | 3823.39 | 01-AUG-19:10 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 184.33 | 20-AUG-16:00 | 133.83 | 31-AUG-06:00 |
September | 26988.77 | 01-SEP-00:10 | 3823.39 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 151.91 | 03-SEP-14:00 | 165.22 | 25-SEP-05:00 |
October | 26988.77 | 01-OCT-23:10 | 3823.39 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 105.54 | 01-OCT-16:00 | 367.26 | 26-OCT-05:00 |
November | 26988.77 | 01-NOV-00:10 | 3823.39 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 391.75 | 27-NOV-06:00 |
December | 26988.77 | 01-DEC-00:10 | 3823.39 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 477.24 | 15-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26988.77 | 3823.39 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.11 | |||||
Maximum of Months | 26988.77 | 3823.39 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 223.72 | 477.24 |
Report: PeakSpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 3823.39 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 456.38 | 21-JAN-07:00 |
February | 26988.77 | 01-FEB-00:10 | 3823.39 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.97 | 14-FEB-16:00 | 428.82 | 04-FEB-06:00 |
March | 26988.77 | 01-MAR-00:10 | 3823.39 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.18 | 08-MAR-14:00 | 383.89 | 05-MAR-07:00 |
April | 26988.77 | 01-APR-00:10 | 3823.39 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 63.38 | 13-APR-17:00 | 297.86 | 08-APR-06:00 |
May | 26988.77 | 01-MAY-00:10 | 3823.39 | 01-MAY-19:10 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 120.69 | 22-MAY-13:00 | 246.34 | 07-MAY-05:00 |
June | 26988.77 | 01-JUN-00:10 | 3823.39 | 01-JUN-19:10 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 222.79 | 28-JUN-16:00 | 207.48 | 09-JUN-05:00 |
July | 26988.77 | 01-JUL-00:10 | 3823.39 | 03-JUL-19:10 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 216.60 | 22-JUL-15:00 | 88.60 | 08-JUL-03:00 |
August | 26988.77 | 01-AUG-00:10 | 3823.39 | 01-AUG-19:10 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 183.25 | 20-AUG-16:00 | 134.66 | 31-AUG-06:00 |
September | 26988.77 | 01-SEP-00:10 | 3823.39 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 150.71 | 03-SEP-14:00 | 165.60 | 25-SEP-05:00 |
October | 26988.77 | 01-OCT-23:10 | 3823.39 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 105.53 | 01-OCT-16:00 | 367.69 | 26-OCT-05:00 |
November | 26988.77 | 01-NOV-00:10 | 3823.39 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 391.98 | 27-NOV-06:00 |
December | 26988.77 | 01-DEC-00:10 | 3823.39 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 477.48 | 15-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26988.77 | 3823.39 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.60 | |||||
Maximum of Months | 26988.77 | 3823.39 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 222.79 | 477.48 |
Report: PeakSpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2401.70 | 02-JAN-00:10 | 1020.78 | 02-JAN-20:10 | 15112.11 | 01-JAN-07:10 | 22492.83 | 01-JAN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 411.23 | 21-JAN-07:00 |
February | 2401.70 | 01-FEB-00:10 | 1020.78 | 01-FEB-20:10 | 15112.11 | 01-FEB-07:10 | 22492.83 | 01-FEB-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 394.69 | 05-FEB-08:00 |
March | 2401.70 | 01-MAR-00:10 | 1020.78 | 01-MAR-20:10 | 15112.11 | 01-MAR-07:10 | 22492.83 | 01-MAR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 353.36 | 05-MAR-07:00 |
April | 2401.70 | 01-APR-00:10 | 1020.78 | 03-APR-19:10 | 15112.11 | 01-APR-06:10 | 22492.83 | 01-APR-15:09 | 0.00 | 0.00 | 0.00 | 24.42 | 13-APR-17:00 | 276.39 | 08-APR-07:00 |
May | 2401.70 | 01-MAY-00:10 | 1020.78 | 01-MAY-19:10 | 15112.11 | 01-MAY-06:10 | 22492.83 | 01-MAY-15:09 | 0.00 | 0.00 | 0.00 | 74.24 | 22-MAY-13:20 | 226.47 | 05-MAY-06:30 |
June | 2401.70 | 01-JUN-00:10 | 1020.78 | 01-JUN-19:10 | 15112.11 | 01-JUN-06:10 | 22492.83 | 01-JUN-15:09 | 0.00 | 0.00 | 0.00 | 173.70 | 28-JUN-16:00 | 190.13 | 09-JUN-05:20 |
July | 2401.70 | 01-JUL-00:10 | 1020.78 | 03-JUL-19:10 | 15112.11 | 01-JUL-06:10 | 22492.83 | 01-JUL-15:09 | 0.00 | 0.00 | 0.00 | 166.47 | 22-JUL-15:00 | 76.22 | 07-JUL-22:40 |
August | 2401.70 | 01-AUG-00:10 | 1020.78 | 01-AUG-19:10 | 15112.11 | 01-AUG-06:10 | 22492.83 | 01-AUG-15:09 | 0.00 | 0.00 | 0.00 | 129.76 | 20-AUG-15:00 | 124.64 | 31-AUG-06:00 |
September | 2401.70 | 01-SEP-00:10 | 1020.78 | 01-SEP-19:10 | 15112.11 | 01-SEP-06:10 | 22492.83 | 01-SEP-15:09 | 0.00 | 0.00 | 0.00 | 103.86 | 03-SEP-14:00 | 151.83 | 20-SEP-06:00 |
October | 2401.70 | 01-OCT-23:10 | 1020.78 | 02-OCT-19:10 | 15112.11 | 01-OCT-06:10 | 22492.83 | 01-OCT-15:09 | 0.00 | 0.00 | 0.00 | 58.29 | 01-OCT-16:00 | 357.63 | 27-OCT-07:00 |
November | 2401.70 | 01-NOV-00:10 | 1020.78 | 01-NOV-19:10 | 15112.11 | 01-NOV-06:10 | 22492.83 | 01-NOV-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 364.83 | 28-NOV-08:00 |
December | 2401.70 | 01-DEC-00:10 | 1020.78 | 01-DEC-20:10 | 15112.11 | 01-DEC-07:10 | 22492.83 | 01-DEC-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 430.74 | 15-DEC-08:40 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 2401.70 | 1020.78 | 15112.11 | 22492.83 | 0.00 | 0.00 | 0.00 | 0.00 | 76.22 | ||||||
Maximum of Months | 2401.70 | 1020.78 | 15112.11 | 22492.83 | 0.00 | 0.00 | 0.00 | 173.70 | 430.74 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2395.44 | 02-JAN-00:10 | 1357.44 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 399.60 | 21-JAN-07:00 |
February | 2395.44 | 01-FEB-00:10 | 1357.44 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.14 | 14-FEB-16:00 | 373.43 | 04-FEB-06:00 |
March | 2395.44 | 01-MAR-00:10 | 1357.44 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.94 | 08-MAR-16:00 | 334.67 | 05-MAR-07:00 |
April | 2395.44 | 01-APR-00:10 | 1357.44 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.03 | 13-APR-17:00 | 254.49 | 08-APR-06:00 |
May | 2395.44 | 01-MAY-00:10 | 1357.44 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.71 | 22-MAY-13:00 | 215.15 | 07-MAY-05:00 |
June | 2395.44 | 01-JUN-00:10 | 1357.44 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 191.53 | 28-JUN-16:00 | 170.03 | 09-JUN-05:00 |
July | 2395.44 | 01-JUL-00:10 | 1357.44 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 182.85 | 22-JUL-15:00 | 62.09 | 08-JUL-03:20 |
August | 2395.44 | 01-AUG-00:10 | 1357.44 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 152.05 | 01-AUG-16:00 | 104.10 | 31-AUG-06:00 |
September | 2395.44 | 01-SEP-00:10 | 1357.44 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 122.22 | 03-SEP-14:00 | 133.50 | 09-SEP-06:00 |
October | 2395.44 | 01-OCT-23:10 | 1357.44 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.74 | 01-OCT-16:00 | 317.57 | 26-OCT-07:00 |
November | 2395.44 | 01-NOV-00:10 | 1357.44 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 340.40 | 27-NOV-06:50 |
December | 2395.44 | 01-DEC-00:10 | 1357.44 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 417.19 | 15-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 2395.44 | 1357.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.09 | ||||
Maximum of Months | 2395.44 | 1357.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 191.53 | 417.19 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 19490.73 | 03-JAN-21:00 | 8945.92 | 13517.00 | 10113.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 19444.15 | 13-FEB-19:01 | 62621.41 | 84105.23 | 67070.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 19330.12 | 08-MAR-20:10 | 8945.92 | 13517.00 | 10113.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 19901.89 | 13-APR-19:10 | 17891.83 | 27034.00 | 20227.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 20362.74 | 18-MAY-19:10 | 17891.83 | 27034.00 | 20227.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 21525.53 | 28-JUN-19:20 | 8945.92 | 13517.00 | 10113.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 22255.88 | 20-JUL-19:10 | 17891.83 | 27034.00 | 20227.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 22544.74 | 17-AUG-18:20 | 17891.83 | 24030.07 | 19162.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 22607.13 | 13-SEP-18:10 | 53675.50 | 72090.20 | 57488.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 22061.86 | 05-OCT-18:10 | 62621.41 | 84105.23 | 67070.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 20542.68 | 01-NOV-20:00 | 8945.92 | 13517.00 | 10113.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 20147.81 | 01-DEC-21:00 | 8945.92 | 13517.00 | 10113.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 19330.12 | 8945.92 | 13517.00 | 10113.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22607.13 | 62621.41 | 84105.23 | 67070.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4109.20 | 01-JAN-11:35 | 779.69 | 458.20 | 577.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 141.84 |
February | 4214.01 | 14-FEB-13:30 | 259.90 | 190.92 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.10 |
March | 3899.78 | 08-MAR-11:35 | 519.79 | 381.83 | 505.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.54 |
April | 3471.06 | 13-APR-10:35 | 519.79 | 381.83 | 505.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.43 |
May | 2985.25 | 13-MAY-12:00 | 389.84 | 190.92 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 45.97 | 0.00 |
June | 3361.02 | 29-JUN-15:15 | 1299.48 | 381.83 | 505.18 | 0.00 | 0.00 | 0.00 | 0.00 | 143.57 | 0.00 |
July | 3423.68 | 23-JUL-10:35 | 779.69 | 458.20 | 577.35 | 0.00 | 0.00 | 0.00 | 0.00 | 102.42 | 0.00 |
August | 3794.02 | 20-AUG-10:40 | 389.84 | 229.10 | 288.68 | 0.00 | 0.00 | 0.00 | 0.00 | 84.41 | 0.00 |
September | 4060.63 | 28-SEP-10:35 | 519.79 | 381.83 | 505.18 | 0.00 | 0.00 | 0.00 | 0.00 | 33.18 | 0.00 |
October | 4120.57 | 31-OCT-13:10 | 259.90 | 190.92 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.58 |
November | 4176.78 | 07-NOV-11:35 | 519.79 | 381.83 | 505.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 128.40 |
December | 4100.31 | 31-DEC-13:00 | 389.84 | 229.10 | 288.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 160.92 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2985.25 | 259.90 | 190.92 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4214.01 | 1299.48 | 458.20 | 577.35 | 0.00 | 0.00 | 0.00 | 0.00 | 143.57 | 160.92 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1797.87 | 03-JAN-21:00 | 1053.36 | 795.89 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.82 |
February | 1900.48 | 14-FEB-21:00 | 1053.36 | 795.89 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.57 |
March | 1953.35 | 08-MAR-19:10 | 7373.52 | 4952.21 | 5265.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.22 |
April | 2113.21 | 13-APR-18:10 | 7373.52 | 4952.21 | 5265.02 | 0.00 | 0.00 | 0.00 | 0.00 | 12.55 | 0.00 |
May | 2166.48 | 15-MAY-18:10 | 7373.52 | 4952.21 | 5265.02 | 0.00 | 0.00 | 0.00 | 0.00 | 24.93 | 0.00 |
June | 2322.44 | 28-JUN-18:10 | 6320.16 | 4244.75 | 4512.87 | 0.00 | 0.00 | 0.00 | 0.00 | 46.60 | 0.00 |
July | 2346.30 | 20-JUL-18:10 | 6320.16 | 4244.75 | 4512.87 | 0.00 | 0.00 | 0.00 | 0.00 | 52.33 | 0.00 |
August | 2302.66 | 17-AUG-18:10 | 6320.16 | 4244.75 | 4512.87 | 0.00 | 0.00 | 0.00 | 0.00 | 39.23 | 0.00 |
September | 2195.51 | 13-SEP-18:10 | 6320.16 | 4244.75 | 4512.87 | 0.00 | 0.00 | 0.00 | 0.00 | 21.30 | 0.00 |
October | 2123.71 | 05-OCT-18:10 | 7373.52 | 4952.21 | 5265.02 | 0.00 | 0.00 | 0.00 | 0.00 | 9.13 | 0.00 |
November | 1893.27 | 02-NOV-18:10 | 7373.52 | 4952.21 | 5265.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.43 |
December | 1775.18 | 29-DEC-21:00 | 1053.36 | 795.89 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.44 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1775.18 | 1053.36 | 795.89 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2346.30 | 7373.52 | 4952.21 | 5265.02 | 0.00 | 0.00 | 0.00 | 0.00 | 52.33 | 78.44 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1357.04 | 05-JAN-21:00 | 222.77 | 1487.69 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 151.03 |
February | 1617.08 | 15-FEB-21:00 | 222.77 | 1487.69 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 123.11 |
March | 1724.44 | 08-MAR-21:00 | 222.77 | 1487.69 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.50 |
April | 1980.11 | 27-APR-19:10 | 445.54 | 2975.37 | 1678.89 | 0.00 | 0.00 | 0.00 | 0.00 | 4.93 | 0.00 |
May | 2101.45 | 31-MAY-18:20 | 445.54 | 2644.77 | 1590.53 | 0.00 | 0.00 | 0.00 | 0.00 | 51.06 | 0.00 |
June | 2329.80 | 28-JUN-18:10 | 1336.61 | 7934.32 | 4771.59 | 0.00 | 0.00 | 0.00 | 0.00 | 110.67 | 0.00 |
July | 2339.05 | 20-JUL-18:10 | 1336.61 | 7934.32 | 4771.59 | 0.00 | 0.00 | 0.00 | 0.00 | 124.73 | 0.00 |
August | 2288.59 | 17-AUG-18:10 | 1336.61 | 7934.32 | 4771.59 | 0.00 | 0.00 | 0.00 | 0.00 | 93.98 | 0.00 |
September | 2117.92 | 13-SEP-18:20 | 445.54 | 2644.77 | 1590.53 | 0.00 | 0.00 | 0.00 | 0.00 | 49.52 | 0.00 |
October | 2015.38 | 02-OCT-18:30 | 222.77 | 1322.39 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.62 |
November | 1685.61 | 02-NOV-20:00 | 222.77 | 1487.69 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.33 |
December | 1426.16 | 01-DEC-21:00 | 222.77 | 1487.69 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.30 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1357.04 | 222.77 | 1322.39 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2339.05 | 1336.61 | 7934.32 | 4771.59 | 0.00 | 0.00 | 0.00 | 0.00 | 124.73 | 151.03 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 338.06 | 05-JAN-21:50 | 195.84 | 242.76 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.53 |
February | 510.17 | 14-FEB-22:00 | 195.84 | 242.76 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.28 |
March | 575.41 | 16-MAR-21:00 | 195.84 | 242.76 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.33 |
April | 850.19 | 28-APR-21:00 | 195.84 | 242.76 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 |
May | 949.49 | 19-MAY-19:20 | 171.36 | 273.10 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 28.54 | 0.00 |
June | 1137.76 | 28-JUN-18:03 | 1028.16 | 1456.53 | 1376.47 | 0.00 | 0.00 | 0.00 | 0.00 | 64.48 | 0.00 |
July | 1150.11 | 20-JUL-18:02 | 1028.16 | 1456.53 | 1376.47 | 0.00 | 0.00 | 0.00 | 0.00 | 72.43 | 0.00 |
August | 1062.11 | 17-AUG-18:50 | 171.36 | 242.76 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 49.31 | 0.00 |
September | 960.20 | 13-SEP-20:00 | 171.36 | 273.10 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 14.81 | 0.00 |
October | 876.93 | 06-OCT-21:00 | 195.84 | 242.76 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.16 |
November | 572.74 | 02-NOV-21:00 | 195.84 | 242.76 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.46 |
December | 398.71 | 01-DEC-22:00 | 195.84 | 242.76 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.91 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 338.06 | 171.36 | 242.76 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1150.11 | 1028.16 | 1456.53 | 1376.47 | 0.00 | 0.00 | 0.00 | 0.00 | 72.43 | 92.53 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 35623.46 | 03-JAN-21:00 | 705.60 | 337.37 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 261.76 |
February | 36179.52 | 14-FEB-21:00 | 705.60 | 337.37 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 176.47 |
March | 36299.27 | 08-MAR-21:00 | 705.60 | 337.37 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 124.86 |
April | 37031.62 | 28-APR-20:00 | 705.60 | 337.37 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 21.57 |
May | 37212.18 | 19-MAY-20:00 | 705.60 | 337.37 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 19.48 | 0.00 |
June | 38014.37 | 28-JUN-20:00 | 705.60 | 337.37 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 76.23 | 0.00 |
July | 37914.53 | 20-JUL-20:00 | 705.60 | 337.37 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 82.91 | 0.00 |
August | 37799.92 | 17-AUG-20:00 | 705.60 | 337.37 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 55.71 | 0.00 |
September | 37300.49 | 13-SEP-20:00 | 705.60 | 337.37 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 1.43 | 0.00 |
October | 36952.32 | 06-OCT-20:00 | 705.60 | 337.37 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 55.95 |
November | 35995.65 | 01-NOV-20:00 | 705.60 | 337.37 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 206.86 |
December | 35665.68 | 01-DEC-21:00 | 705.60 | 337.37 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 184.46 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 35623.46 | 705.60 | 337.37 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 38014.37 | 705.60 | 337.37 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 82.91 | 261.76 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 16583.28 | 01-JAN-11:35 | 10245.60 | 1451.48 | 812.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 304.65 |
February | 16231.58 | 14-FEB-11:35 | 6830.40 | 1209.57 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 137.43 |
March | 15418.24 | 11-MAR-11:35 | 10245.60 | 1209.57 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 218.72 |
April | 14151.64 | 01-APR-10:35 | 10245.60 | 1209.57 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.81 |
May | 12978.46 | 19-MAY-18:10 | 83672.40 | 13547.18 | 6401.28 | 0.00 | 0.00 | 0.00 | 0.00 | 167.28 | 0.00 |
June | 14240.59 | 28-JUN-18:10 | 71719.20 | 11611.87 | 5486.82 | 0.00 | 0.00 | 0.00 | 0.00 | 270.78 | 0.00 |
July | 14517.50 | 20-JUL-18:03 | 71719.20 | 11611.87 | 5486.82 | 0.00 | 0.00 | 0.00 | 0.00 | 304.16 | 0.00 |
August | 14395.01 | 17-AUG-18:10 | 71719.20 | 11611.87 | 5486.82 | 0.00 | 0.00 | 0.00 | 0.00 | 227.30 | 0.00 |
September | 15736.74 | 03-SEP-10:35 | 10245.60 | 1451.48 | 812.86 | 0.00 | 0.00 | 0.00 | 0.00 | 152.40 | 0.00 |
October | 16378.53 | 01-OCT-10:35 | 10245.60 | 1451.48 | 812.86 | 0.00 | 0.00 | 0.00 | 0.00 | 20.25 | 0.00 |
November | 16696.94 | 19-NOV-11:35 | 10245.60 | 1451.48 | 812.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 328.13 |
December | 16272.28 | 31-DEC-11:35 | 10245.60 | 1451.48 | 812.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 413.08 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 12978.46 | 6830.40 | 1209.57 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16696.94 | 83672.40 | 13547.18 | 6401.28 | 0.00 | 0.00 | 0.00 | 0.00 | 304.16 | 413.08 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 39754.13 | 01-JAN-11:35 | 30415.32 | 7899.54 | 8445.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 734.59 |
February | 38428.61 | 14-FEB-21:00 | 35484.54 | 11849.32 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 736.45 |
March | 39443.05 | 09-MAR-19:04 | 248391.78 | 73729.08 | 66509.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 585.83 |
April | 42206.93 | 13-APR-18:10 | 248391.78 | 73729.08 | 66509.49 | 0.00 | 0.00 | 0.00 | 0.00 | 203.26 | 0.00 |
May | 43033.91 | 15-MAY-18:10 | 248391.78 | 73729.08 | 66509.49 | 0.00 | 0.00 | 0.00 | 0.00 | 408.16 | 0.00 |
June | 46124.93 | 28-JUN-18:10 | 212907.24 | 63196.36 | 57008.13 | 0.00 | 0.00 | 0.00 | 0.00 | 763.09 | 0.00 |
July | 46404.79 | 20-JUL-18:10 | 212907.24 | 63196.36 | 57008.13 | 0.00 | 0.00 | 0.00 | 0.00 | 858.65 | 0.00 |
August | 45746.42 | 17-AUG-18:10 | 212907.24 | 63196.36 | 57008.13 | 0.00 | 0.00 | 0.00 | 0.00 | 642.16 | 0.00 |
September | 43893.34 | 13-SEP-18:10 | 212907.24 | 63196.36 | 57008.13 | 0.00 | 0.00 | 0.00 | 0.00 | 345.84 | 0.00 |
October | 42458.01 | 05-OCT-18:10 | 248391.78 | 73729.08 | 66509.49 | 0.00 | 0.00 | 0.00 | 0.00 | 146.79 | 0.00 |
November | 41074.22 | 23-NOV-11:35 | 30415.32 | 7899.54 | 8445.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 648.96 |
December | 38885.18 | 31-DEC-11:35 | 30415.32 | 7899.54 | 8445.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1044.14 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 38428.61 | 30415.32 | 7899.54 | 8445.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 46404.79 | 248391.78 | 73729.08 | 66509.49 | 0.00 | 0.00 | 0.00 | 0.00 | 858.65 | 1044.14 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4612.90 | 09-JAN-16:01 | 680.40 | 769.75 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.89 |
February | 4706.95 | 13-FEB-16:01 | 680.40 | 769.75 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.36 |
March | 4724.23 | 07-MAR-16:01 | 680.40 | 769.75 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.52 |
April | 4742.42 | 13-APR-15:01 | 680.40 | 769.75 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 15.34 | 0.00 |
May | 4734.24 | 19-MAY-15:01 | 680.40 | 769.75 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 42.29 | 0.00 |
June | 4753.89 | 11-JUN-18:01 | 819.00 | 2749.09 | 903.46 | 0.00 | 0.00 | 0.00 | 0.00 | 27.82 | 0.00 |
July | 4750.66 | 21-JUL-18:02 | 831.60 | 2097.16 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 72.72 | 0.00 |
August | 4767.42 | 20-AUG-18:01 | 819.00 | 2749.09 | 903.46 | 0.00 | 0.00 | 0.00 | 0.00 | 61.57 | 0.00 |
September | 4792.30 | 27-SEP-15:01 | 680.40 | 769.75 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 38.02 | 0.00 |
October | 4789.80 | 05-OCT-15:01 | 680.40 | 769.75 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 23.61 | 0.00 |
November | 4669.33 | 02-NOV-15:01 | 680.40 | 769.75 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.45 |
December | 4598.13 | 30-DEC-16:01 | 378.00 | 907.20 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.75 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4598.13 | 378.00 | 769.75 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4792.30 | 831.60 | 2749.09 | 903.46 | 0.00 | 0.00 | 0.00 | 0.00 | 72.72 | 66.75 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4453.10 | 01-JAN-16:01 | 378.00 | 907.09 | 534.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.40 |
February | 4561.22 | 13-FEB-16:01 | 680.40 | 769.66 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.99 |
March | 4599.55 | 07-MAR-16:01 | 680.40 | 769.66 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.46 |
April | 4651.14 | 13-APR-15:01 | 680.40 | 769.66 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 15.91 | 0.00 |
May | 4690.93 | 20-MAY-18:01 | 819.00 | 2748.77 | 903.35 | 0.00 | 0.00 | 0.00 | 0.00 | 21.66 | 0.00 |
June | 4721.90 | 11-JUN-18:01 | 819.00 | 2748.77 | 903.35 | 0.00 | 0.00 | 0.00 | 0.00 | 27.54 | 0.00 |
July | 4713.62 | 21-JUL-18:02 | 831.60 | 2096.92 | 774.30 | 0.00 | 0.00 | 0.00 | 0.00 | 72.52 | 0.00 |
August | 4069.16 | 10-AUG-08:61 | 252.00 | 1209.46 | 792.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.78 |
September | 4674.59 | 27-SEP-15:01 | 680.40 | 769.66 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 38.94 | 0.00 |
October | 4666.59 | 05-OCT-15:01 | 680.40 | 769.66 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 24.61 | 0.00 |
November | 4529.88 | 02-NOV-15:01 | 680.40 | 769.66 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.16 |
December | 4436.89 | 29-DEC-16:01 | 680.40 | 769.66 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.14 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4069.16 | 252.00 | 769.66 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4721.90 | 831.60 | 2748.77 | 903.35 | 0.00 | 0.00 | 0.00 | 0.00 | 72.52 | 61.14 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 902.82 | 01-JAN-14:00 | 0.00 | 81.45 | 74.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.65 |
February | 922.93 | 14-FEB-13:00 | 0.00 | 69.11 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.31 |
March | 805.38 | 08-MAR-13:30 | 0.00 | 69.11 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.11 |
April | 633.27 | 13-APR-13:20 | 0.00 | 69.11 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 1.08 | 0.00 |
May | 494.74 | 13-MAY-13:10 | 0.00 | 81.45 | 74.82 | 0.00 | 0.00 | 0.00 | 0.00 | 7.76 | 0.00 |
June | 523.78 | 28-JUN-19:10 | 0.00 | 246.81 | 170.27 | 0.00 | 0.00 | 0.00 | 0.00 | 12.97 | 0.00 |
July | 577.42 | 23-JUL-13:30 | 0.00 | 81.45 | 74.82 | 0.00 | 0.00 | 0.00 | 0.00 | 19.28 | 0.00 |
August | 704.25 | 22-AUG-13:30 | 0.00 | 69.11 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 12.33 | 0.00 |
September | 875.72 | 28-SEP-13:20 | 0.00 | 69.11 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 9.12 | 0.00 |
October | 934.97 | 19-OCT-12:30 | 0.00 | 69.11 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 |
November | 916.55 | 20-NOV-12:10 | 0.00 | 69.11 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.36 |
December | 913.67 | 31-DEC-13:40 | 0.00 | 81.45 | 74.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 494.74 | 0.00 | 69.11 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 934.97 | 0.00 | 246.81 | 170.27 | 0.00 | 0.00 | 0.00 | 0.00 | 19.28 | 23.03 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 936.59 | 05-JAN-19:01 | 970.20 | 1538.07 | 885.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.67 |
February | 1318.69 | 15-FEB-19:01 | 970.20 | 1538.07 | 885.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.79 |
March | 1368.07 | 27-MAR-15:01 | 680.40 | 483.89 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.51 |
April | 1460.21 | 29-APR-18:01 | 819.00 | 1728.17 | 885.15 | 0.00 | 0.00 | 0.00 | 0.00 | 1.42 | 0.00 |
May | 1469.24 | 31-MAY-18:01 | 970.20 | 1538.07 | 885.15 | 0.00 | 0.00 | 0.00 | 0.00 | 6.72 | 0.00 |
June | 1472.91 | 11-JUN-18:01 | 819.00 | 1728.17 | 885.15 | 0.00 | 0.00 | 0.00 | 0.00 | 7.24 | 0.00 |
July | 1473.10 | 03-JUL-15:01 | 680.40 | 483.89 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 17.33 | 0.00 |
August | 1475.37 | 20-AUG-18:01 | 819.00 | 1728.17 | 885.15 | 0.00 | 0.00 | 0.00 | 0.00 | 16.70 | 0.00 |
September | 1467.87 | 30-SEP-15:01 | 378.00 | 570.30 | 523.86 | 0.00 | 0.00 | 0.00 | 0.00 | 7.22 | 0.00 |
October | 1462.45 | 01-OCT-15:01 | 378.00 | 570.30 | 523.86 | 0.00 | 0.00 | 0.00 | 0.00 | 8.98 | 0.00 |
November | 1341.97 | 02-NOV-18:01 | 970.20 | 1538.07 | 885.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.85 |
December | 1018.03 | 01-DEC-19:02 | 693.00 | 1098.62 | 632.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.83 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 936.59 | 378.00 | 483.89 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1475.37 | 970.20 | 1728.17 | 885.15 | 0.00 | 0.00 | 0.00 | 0.00 | 17.33 | 22.67 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4158.94 | 26-JAN-09:01 | 252.00 | 1209.60 | 792.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 138.26 |
February | 4172.18 | 09-FEB-09:01 | 252.00 | 1209.60 | 792.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.98 |
March | 4174.02 | 04-MAR-09:01 | 378.00 | 1539.49 | 1143.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 121.83 |
April | 4199.09 | 29-APR-08:61 | 378.00 | 1539.49 | 1143.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.06 |
May | 4171.96 | 14-MAY-08:62 | 324.00 | 1319.56 | 979.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.30 |
June | 4269.82 | 17-JUN-08:61 | 378.00 | 1539.49 | 1143.15 | 0.00 | 0.00 | 0.00 | 0.00 | 13.13 | 0.00 |
July | 4187.40 | 03-JUL-15:01 | 680.40 | 769.75 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 64.29 | 0.00 |
August | 4186.69 | 20-AUG-18:01 | 819.00 | 2749.09 | 903.46 | 0.00 | 0.00 | 0.00 | 0.00 | 62.14 | 0.00 |
September | 4192.42 | 27-SEP-15:01 | 680.40 | 769.75 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 38.87 | 0.00 |
October | 4198.34 | 01-OCT-15:01 | 378.00 | 907.20 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 33.78 | 0.00 |
November | 4188.47 | 19-NOV-09:01 | 378.00 | 1539.49 | 1143.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 120.35 |
December | 4189.57 | 31-DEC-09:01 | 378.00 | 1539.49 | 1143.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 137.63 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4158.94 | 252.00 | 769.75 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4269.82 | 819.00 | 2749.09 | 1143.15 | 0.00 | 0.00 | 0.00 | 0.00 | 64.29 | 138.26 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3543.37 | 01-JAN-09:01 | 378.00 | 1539.31 | 1143.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 113.91 |
February | 4056.29 | 14-FEB-09:01 | 252.00 | 1209.46 | 792.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.61 |
March | 4098.01 | 04-MAR-09:01 | 378.00 | 1539.31 | 1143.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 121.11 |
April | 4160.77 | 29-APR-08:61 | 378.00 | 1539.31 | 1143.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.02 |
May | 4139.40 | 14-MAY-08:62 | 324.00 | 1319.41 | 979.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.35 |
June | 4242.23 | 17-JUN-08:61 | 378.00 | 1539.31 | 1143.02 | 0.00 | 0.00 | 0.00 | 0.00 | 13.00 | 0.00 |
July | 4151.00 | 03-JUL-15:01 | 680.40 | 769.66 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 64.30 | 0.00 |
August | 4146.26 | 20-AUG-18:01 | 819.00 | 2748.77 | 903.35 | 0.00 | 0.00 | 0.00 | 0.00 | 62.22 | 0.00 |
September | 4118.06 | 21-SEP-08:62 | 216.00 | 1036.68 | 679.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.98 |
October | 4107.39 | 01-OCT-15:01 | 378.00 | 907.09 | 534.64 | 0.00 | 0.00 | 0.00 | 0.00 | 34.65 | 0.00 |
November | 4078.09 | 19-NOV-09:01 | 378.00 | 1539.31 | 1143.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 119.02 |
December | 3657.38 | 30-DEC-09:01 | 378.00 | 1539.31 | 1143.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 122.90 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3543.37 | 216.00 | 769.66 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4242.23 | 819.00 | 2748.77 | 1143.02 | 0.00 | 0.00 | 0.00 | 0.00 | 64.30 | 122.90 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2455.35 | 01-JAN-11:35 | 1508.90 | 855.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.57 |
February | 2578.72 | 14-FEB-11:35 | 1005.94 | 712.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.68 |
March | 2573.76 | 08-MAR-11:35 | 1005.94 | 712.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.02 |
April | 2867.12 | 29-APR-10:35 | 1508.90 | 712.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.72 |
May | 2934.16 | 20-MAY-10:35 | 1508.90 | 712.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.43 | 0.00 |
June | 3258.92 | 29-JUN-10:35 | 1005.94 | 712.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.30 | 0.00 |
July | 3323.32 | 23-JUL-10:35 | 1508.90 | 855.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.59 | 0.00 |
August | 3307.56 | 20-AUG-10:40 | 754.45 | 427.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.30 | 0.00 |
September | 3202.01 | 03-SEP-10:35 | 1508.90 | 855.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.52 | 0.00 |
October | 3082.80 | 01-OCT-10:35 | 1508.90 | 855.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.10 | 0.00 |
November | 2666.40 | 01-NOV-10:35 | 1005.94 | 712.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.75 |
December | 2414.63 | 30-DEC-11:35 | 1508.90 | 712.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.01 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 2414.63 | 754.45 | 427.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3323.32 | 1508.90 | 855.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.30 | 96.01 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4953.10 | 09-JAN-16:01 | 680.40 | 769.75 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.98 |
February | 5065.71 | 13-FEB-16:01 | 680.40 | 769.75 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.63 |
March | 5079.89 | 07-MAR-16:01 | 680.40 | 769.75 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.74 |
April | 5114.68 | 13-APR-15:01 | 680.40 | 769.75 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 14.93 | 0.00 |
May | 5107.66 | 20-MAY-15:01 | 378.00 | 907.20 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 24.38 | 0.00 |
June | 5135.49 | 21-JUN-15:01 | 680.40 | 769.75 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 63.40 | 0.00 |
July | 5135.56 | 21-JUL-18:02 | 831.60 | 2097.16 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 72.19 | 0.00 |
August | 4359.53 | 18-AUG-08:61 | 252.00 | 1209.60 | 792.83 | 0.00 | 0.00 | 0.00 | 0.00 | 14.04 | 0.00 |
September | 5163.13 | 27-SEP-15:01 | 680.40 | 769.75 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 37.69 | 0.00 |
October | 5167.10 | 05-OCT-15:01 | 680.40 | 769.75 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 23.19 | 0.00 |
November | 5017.34 | 02-NOV-15:01 | 680.40 | 769.75 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.60 |
December | 4942.22 | 31-DEC-16:01 | 378.00 | 907.20 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.75 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4359.53 | 252.00 | 769.75 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5167.10 | 831.60 | 2097.16 | 792.83 | 0.00 | 0.00 | 0.00 | 0.00 | 72.19 | 72.75 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4749.45 | 01-JAN-16:01 | 378.00 | 907.09 | 534.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.18 |
February | 4885.70 | 13-FEB-16:01 | 680.40 | 769.66 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.08 |
March | 4927.64 | 07-MAR-16:01 | 680.40 | 769.66 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.56 |
April | 5006.16 | 13-APR-15:01 | 680.40 | 769.66 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 15.51 | 0.00 |
May | 5054.82 | 20-MAY-18:01 | 819.00 | 2748.77 | 903.35 | 0.00 | 0.00 | 0.00 | 0.00 | 21.18 | 0.00 |
June | 5091.37 | 11-JUN-18:01 | 819.00 | 2748.77 | 903.35 | 0.00 | 0.00 | 0.00 | 0.00 | 27.03 | 0.00 |
July | 5088.08 | 21-JUL-18:02 | 831.60 | 2096.92 | 774.30 | 0.00 | 0.00 | 0.00 | 0.00 | 71.96 | 0.00 |
August | 4311.47 | 24-AUG-18:01 | 970.20 | 2446.40 | 903.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.97 |
September | 5022.84 | 27-SEP-15:01 | 680.40 | 769.66 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 38.66 | 0.00 |
October | 5019.16 | 05-OCT-15:01 | 680.40 | 769.66 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 24.27 | 0.00 |
November | 4845.90 | 02-NOV-15:01 | 680.40 | 769.66 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.14 |
December | 4731.23 | 30-DEC-16:01 | 378.00 | 907.09 | 534.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.85 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4311.47 | 378.00 | 769.66 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5091.37 | 970.20 | 2748.77 | 903.35 | 0.00 | 0.00 | 0.00 | 0.00 | 71.96 | 64.85 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2418.15 | 03-JAN-16:01 | 680.40 | 483.89 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.47 |
February | 2450.38 | 13-FEB-16:01 | 680.40 | 483.89 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.55 |
March | 2432.75 | 12-MAR-15:01 | 378.00 | 570.30 | 523.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.10 |
April | 2427.98 | 01-APR-15:01 | 378.00 | 570.30 | 523.86 | 0.00 | 0.00 | 0.00 | 0.00 | 5.10 | 0.00 |
May | 2402.21 | 19-MAY-15:01 | 680.40 | 483.89 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 21.23 | 0.00 |
June | 2408.27 | 21-JUN-15:01 | 680.40 | 483.89 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 32.34 | 0.00 |
July | 2402.28 | 21-JUL-15:02 | 583.20 | 414.76 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 41.89 | 0.00 |
August | 2141.69 | 24-AUG-18:01 | 970.20 | 1538.07 | 885.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.81 |
September | 2467.84 | 27-SEP-15:01 | 680.40 | 483.89 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 18.53 | 0.00 |
October | 2477.10 | 05-OCT-15:01 | 680.40 | 483.89 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 11.00 | 0.00 |
November | 2423.41 | 01-NOV-15:01 | 680.40 | 483.89 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.84 |
December | 2417.45 | 31-DEC-16:01 | 378.00 | 570.30 | 523.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.98 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2141.69 | 378.00 | 414.76 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2477.10 | 970.20 | 1538.07 | 885.15 | 0.00 | 0.00 | 0.00 | 0.00 | 41.89 | 38.98 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 18618.62 | 09-JAN-23:00 | 26988.77 | 2548.93 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 240.50 |
February | 19291.18 | 14-FEB-23:00 | 26988.77 | 2548.93 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 172.63 |
March | 19580.88 | 13-MAR-18:10 | 146938.85 | 23790.00 | 47235.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.22 |
April | 21443.53 | 13-APR-18:10 | 146938.85 | 23790.00 | 47235.32 | 0.00 | 0.00 | 0.00 | 0.00 | 37.91 | 0.00 |
May | 22426.89 | 31-MAY-18:10 | 146938.85 | 23790.00 | 47235.32 | 0.00 | 0.00 | 0.00 | 0.00 | 69.49 | 0.00 |
June | 24117.45 | 28-JUN-18:10 | 125947.58 | 20391.43 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 160.11 | 0.00 |
July | 24322.09 | 20-JUL-18:10 | 125947.58 | 20391.43 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 181.15 | 0.00 |
August | 23674.14 | 04-AUG-17:04 | 119950.08 | 20391.43 | 53983.22 | 0.00 | 0.00 | 0.00 | 0.00 | 156.21 | 0.00 |
September | 22038.33 | 13-SEP-18:10 | 125947.58 | 20391.43 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 71.06 | 0.00 |
October | 20998.91 | 05-OCT-18:10 | 146938.85 | 23790.00 | 47235.32 | 0.00 | 0.00 | 0.00 | 0.00 | 28.06 | 0.00 |
November | 19479.88 | 08-NOV-23:00 | 26988.77 | 2548.93 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 149.64 |
December | 18934.83 | 01-DEC-22:10 | 80966.30 | 7646.79 | 20243.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 195.62 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 18618.62 | 26988.77 | 2548.93 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 24322.09 | 146938.85 | 23790.00 | 53983.22 | 0.00 | 0.00 | 0.00 | 0.00 | 181.15 | 240.50 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 19766.69 | 05-JAN-23:00 | 26988.77 | 2548.93 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 292.01 |
February | 20464.01 | 14-FEB-23:00 | 26988.77 | 2548.93 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 173.76 |
March | 20794.57 | 13-MAR-18:10 | 146938.85 | 23790.00 | 47235.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.46 |
April | 22766.09 | 13-APR-18:10 | 146938.85 | 23790.00 | 47235.32 | 0.00 | 0.00 | 0.00 | 0.00 | 36.63 | 0.00 |
May | 23830.72 | 31-MAY-18:10 | 146938.85 | 23790.00 | 47235.32 | 0.00 | 0.00 | 0.00 | 0.00 | 68.06 | 0.00 |
June | 25496.77 | 28-JUN-18:10 | 125947.58 | 20391.43 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 159.21 | 0.00 |
July | 25716.27 | 20-JUL-18:10 | 125947.58 | 20391.43 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 180.23 | 0.00 |
August | 25101.57 | 04-AUG-17:04 | 119950.08 | 20391.43 | 53983.22 | 0.00 | 0.00 | 0.00 | 0.00 | 154.99 | 0.00 |
September | 23341.88 | 13-SEP-18:10 | 125947.58 | 20391.43 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 70.02 | 0.00 |
October | 22255.71 | 02-OCT-18:10 | 146938.85 | 23790.00 | 47235.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.19 |
November | 20698.93 | 08-NOV-23:00 | 26988.77 | 2548.93 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 150.93 |
December | 20125.17 | 01-DEC-22:10 | 80966.30 | 7646.79 | 20243.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 196.92 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 19766.69 | 26988.77 | 2548.93 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 25716.27 | 146938.85 | 23790.00 | 53983.22 | 0.00 | 0.00 | 0.00 | 0.00 | 180.23 | 292.01 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 27249.75 | 01-JAN-11:40 | 1601.14 | 680.52 | 30224.21 | 37488.05 | 0.00 | 0.00 | 0.00 | 0.00 | 185.32 |
February | 28249.12 | 14-FEB-11:40 | 1067.42 | 567.10 | 30224.21 | 37488.05 | 0.00 | 0.00 | 0.00 | 0.00 | 96.01 |
March | 29207.14 | 26-MAR-10:40 | 1601.14 | 680.52 | 30224.21 | 37488.05 | 0.00 | 0.00 | 0.00 | 0.00 | 117.63 |
April | 30474.60 | 29-APR-10:40 | 1601.14 | 567.10 | 30224.21 | 37488.05 | 0.00 | 0.00 | 0.00 | 0.00 | 48.44 |
May | 30626.85 | 20-MAY-10:40 | 1601.14 | 567.10 | 30224.21 | 37488.05 | 0.00 | 0.00 | 0.00 | 0.00 | 20.94 |
June | 31557.29 | 29-JUN-10:40 | 1067.42 | 567.10 | 30224.21 | 37488.05 | 0.00 | 0.00 | 0.00 | 102.34 | 0.00 |
July | 31963.69 | 23-JUL-10:40 | 1601.14 | 680.52 | 30224.21 | 37488.05 | 0.00 | 0.00 | 0.00 | 92.79 | 0.00 |
August | 31869.04 | 20-AUG-10:40 | 800.57 | 340.26 | 15112.11 | 18744.03 | 0.00 | 0.00 | 0.00 | 73.79 | 0.00 |
September | 31550.29 | 03-SEP-10:40 | 1601.14 | 680.52 | 30224.21 | 37488.05 | 0.00 | 0.00 | 0.00 | 53.86 | 0.00 |
October | 30533.36 | 01-OCT-10:50 | 800.57 | 340.26 | 15112.11 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 8.20 |
November | 28653.16 | 01-NOV-10:35 | 1067.42 | 567.10 | 30224.21 | 37488.05 | 0.00 | 0.00 | 0.00 | 0.00 | 140.55 |
December | 27120.00 | 30-DEC-11:40 | 1601.14 | 567.10 | 30224.21 | 37488.05 | 0.00 | 0.00 | 0.00 | 0.00 | 212.37 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 27120.00 | 800.57 | 340.26 | 15112.11 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 31963.69 | 1601.14 | 680.52 | 30224.21 | 37488.05 | 0.00 | 0.00 | 0.00 | 102.34 | 212.37 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5469.59 | 23-JAN-13:40 | 532.32 | 377.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.13 |
February | 6420.71 | 14-FEB-11:35 | 1064.64 | 754.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.79 |
March | 6431.29 | 08-MAR-11:35 | 1064.64 | 754.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.83 |
April | 7104.41 | 28-APR-10:35 | 1064.64 | 754.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.12 |
May | 7210.97 | 20-MAY-10:35 | 1596.96 | 754.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.60 | 0.00 |
June | 7964.43 | 29-JUN-10:35 | 1064.64 | 754.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 128.28 | 0.00 |
July | 8027.78 | 22-JUL-10:35 | 1596.96 | 754.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.04 | 0.00 |
August | 7889.01 | 04-AUG-17:04 | 10646.40 | 7239.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 135.02 | 0.00 |
September | 7767.16 | 03-SEP-10:35 | 1596.96 | 904.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.46 | 0.00 |
October | 7306.99 | 01-OCT-10:35 | 1596.96 | 904.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.46 | 0.00 |
November | 6311.79 | 23-NOV-11:35 | 1596.96 | 904.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 127.39 |
December | 5431.49 | 31-DEC-13:50 | 532.32 | 301.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 144.09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 5431.49 | 532.32 | 301.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8027.78 | 10646.40 | 7239.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.04 | 144.09 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.604643E+12 | 348321.66 | 09-JAN-20:49 | 0.651261E+12 | 496102.76 | 16-JAN-17:00 |
February | 0.551186E+12 | 360894.56 | 14-FEB-20:10 | 0.568188E+12 | 466191.70 | 16-FEB-17:00 |
March | 0.623078E+12 | 378372.63 | 13-MAR-19:10 | 0.582828E+12 | 438805.86 | 02-MAR-18:00 |
April | 0.659190E+12 | 459312.67 | 28-APR-19:10 | 0.517735E+12 | 418938.53 | 23-APR-16:49 |
May | 0.736097E+12 | 483621.76 | 19-MAY-19:10 | 0.505507E+12 | 398416.05 | 04-MAY-16:00 |
June | 0.827367E+12 | 531871.03 | 26-JUN-18:10 | 0.458686E+12 | 389065.78 | 08-JUN-17:40 |
July | 0.937339E+12 | 552594.89 | 20-JUL-18:10 | 0.453043E+12 | 375953.25 | 08-JUL-16:49 |
August | 0.898942E+12 | 523584.82 | 20-AUG-18:10 | 0.446098E+12 | 376980.54 | 27-AUG-16:00 |
September | 0.777331E+12 | 482897.05 | 13-SEP-19:10 | 0.434221E+12 | 372341.21 | 08-SEP-16:49 |
October | 0.694886E+12 | 454712.70 | 05-OCT-18:10 | 0.494772E+12 | 423799.00 | 25-OCT-16:00 |
November | 0.600490E+12 | 364057.08 | 02-NOV-19:10 | 0.544238E+12 | 421738.33 | 26-NOV-17:49 |
December | 0.607254E+12 | 346085.38 | 01-DEC-20:49 | 0.643854E+12 | 481293.73 | 21-DEC-17:10 |
Annual Sum or Average | 0.851780E+13 | 0.630043E+13 | ||||
Minimum of Months | 0.551186E+12 | 346085.38 | 0.434221E+12 | 372341.21 | ||
Maximum of Months | 0.937339E+12 | 552594.89 | 0.651261E+12 | 496102.76 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [J] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.997859E+11 | 0.261372E+11 | 0.148746E+12 | 0.577258E+11 | 0.181001E+12 | 0.962754E+10 | 0.00 | 0.186382E+11 | 0.00 | 0.00 | 0.490795E+11 | 0.770782E+10 | 0.00 |
February | 0.901073E+11 | 0.222616E+11 | 0.134341E+12 | 0.521396E+11 | 0.162711E+12 | 0.102817E+11 | 0.00 | 0.238926E+11 | 0.00 | 0.00 | 0.428799E+11 | 0.696502E+10 | 0.00 |
March | 0.995228E+11 | 0.227023E+11 | 0.148757E+12 | 0.577286E+11 | 0.178467E+12 | 0.149432E+11 | 0.00 | 0.481020E+11 | 0.00 | 0.00 | 0.389234E+11 | 0.770630E+10 | 0.00 |
April | 0.965474E+11 | 0.199784E+11 | 0.143913E+12 | 0.558635E+11 | 0.175289E+12 | 0.191783E+11 | 0.00 | 0.104565E+12 | 0.00 | 0.00 | 0.303610E+11 | 0.746747E+10 | 0.00 |
May | 0.996636E+11 | 0.189469E+11 | 0.148757E+12 | 0.577273E+11 | 0.183108E+12 | 0.222879E+11 | 0.00 | 0.164240E+12 | 0.00 | 0.00 | 0.273779E+11 | 0.770689E+10 | 0.00 |
June | 0.963626E+11 | 0.174348E+11 | 0.143963E+12 | 0.558662E+11 | 0.183102E+12 | 0.245397E+11 | 0.00 | 0.261335E+12 | 0.00 | 0.00 | 0.311711E+11 | 0.745925E+10 | 0.00 |
July | 0.998551E+11 | 0.184863E+11 | 0.148708E+12 | 0.577246E+11 | 0.192293E+12 | 0.273646E+11 | 0.00 | 0.341999E+12 | 0.00 | 0.00 | 0.368125E+11 | 0.771477E+10 | 0.00 |
August | 0.995413E+11 | 0.198783E+11 | 0.148768E+12 | 0.577287E+11 | 0.191899E+12 | 0.269171E+11 | 0.00 | 0.307550E+12 | 0.00 | 0.00 | 0.325506E+11 | 0.770670E+10 | 0.00 |
September | 0.965794E+11 | 0.211300E+11 | 0.143924E+12 | 0.558636E+11 | 0.182931E+12 | 0.241315E+11 | 0.00 | 0.217877E+12 | 0.00 | 0.00 | 0.212678E+11 | 0.746874E+10 | 0.00 |
October | 0.997606E+11 | 0.238539E+11 | 0.148735E+12 | 0.577257E+11 | 0.184371E+12 | 0.196109E+11 | 0.00 | 0.117281E+12 | 0.00 | 0.00 | 0.295717E+11 | 0.770595E+10 | 0.00 |
November | 0.965244E+11 | 0.248253E+11 | 0.143978E+12 | 0.558644E+11 | 0.174494E+12 | 0.135307E+11 | 0.00 | 0.333633E+11 | 0.00 | 0.00 | 0.444468E+11 | 0.745195E+10 | 0.00 |
December | 0.998619E+11 | 0.266178E+11 | 0.148708E+12 | 0.577246E+11 | 0.181474E+12 | 0.997291E+10 | 0.00 | 0.178013E+11 | 0.00 | 0.00 | 0.511895E+11 | 0.771606E+10 | 0.00 |
Annual Sum or Average | 0.117411E+13 | 0.262253E+12 | 0.175130E+13 | 0.679683E+12 | 0.217114E+13 | 0.222386E+12 | 0.00 | 0.165665E+13 | 0.00 | 0.00 | 0.435632E+12 | 0.907769E+11 | 0.00 |
Minimum of Months | 0.901073E+11 | 0.174348E+11 | 0.134341E+12 | 0.521396E+11 | 0.162711E+12 | 0.962754E+10 | 0.00 | 0.178013E+11 | 0.00 | 0.00 | 0.212678E+11 | 0.696502E+10 | 0.00 |
Maximum of Months | 0.998619E+11 | 0.266178E+11 | 0.148768E+12 | 0.577287E+11 | 0.192293E+12 | 0.273646E+11 | 0.00 | 0.341999E+12 | 0.00 | 0.00 | 0.511895E+11 | 0.771606E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.151918E+12 | 0.00 | 0.211408E+12 | 0.00 | 0.287934E+12 | 0.00 | 0.00 |
February | 0.137204E+12 | 0.00 | 0.169578E+12 | 0.00 | 0.261405E+12 | 0.00 | 0.00 |
March | 0.152024E+12 | 0.00 | 0.145993E+12 | 0.00 | 0.284812E+12 | 0.00 | 0.00 |
April | 0.146956E+12 | 0.00 | 0.104719E+12 | 0.00 | 0.266060E+12 | 0.00 | 0.00 |
May | 0.151978E+12 | 0.00 | 0.909480E+11 | 0.00 | 0.262580E+12 | 0.00 | 0.00 |
June | 0.147114E+12 | 0.00 | 0.685869E+11 | 0.00 | 0.242985E+12 | 0.00 | 0.00 |
July | 0.151820E+12 | 0.00 | 0.578038E+11 | 0.00 | 0.243419E+12 | 0.00 | 0.00 |
August | 0.152039E+12 | 0.00 | 0.522221E+11 | 0.00 | 0.241837E+12 | 0.00 | 0.00 |
September | 0.146971E+12 | 0.00 | 0.485909E+11 | 0.00 | 0.238659E+12 | 0.00 | 0.00 |
October | 0.151903E+12 | 0.00 | 0.863158E+11 | 0.00 | 0.256553E+12 | 0.00 | 0.00 |
November | 0.147091E+12 | 0.00 | 0.136937E+12 | 0.00 | 0.260210E+12 | 0.00 | 0.00 |
December | 0.151820E+12 | 0.00 | 0.211652E+12 | 0.00 | 0.280381E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.178884E+13 | 0.00 | 0.138476E+13 | 0.00 | 0.312684E+13 | 0.00 | 0.00 |
Minimum of Months | 0.137204E+12 | 0.00 | 0.485909E+11 | 0.00 | 0.238659E+12 | 0.00 | 0.00 |
Maximum of Months | 0.152039E+12 | 0.00 | 0.211652E+12 | 0.00 | 0.287934E+12 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 93091.76 | 02-JAN-20:10 | 16690.39 | 01-JAN-00:10 | 89674.66 | 02-JAN-07:10 | 40537.60 | 02-JAN-07:19 | 80056.37 | 20-JAN-09:09 | 8312.09 | 23-JAN-16:10 | 0.00 | 01-JAN-00:10 |
February | 93091.76 | 01-FEB-20:10 | 16690.39 | 01-FEB-00:10 | 89674.66 | 01-FEB-07:10 | 40537.60 | 01-FEB-07:19 | 79931.38 | 14-FEB-16:10 | 10021.49 | 14-FEB-16:30 | 0.00 | 01-FEB-00:10 |
March | 93091.76 | 01-MAR-20:10 | 16690.39 | 01-MAR-00:10 | 89674.66 | 01-MAR-07:10 | 40537.60 | 01-MAR-07:19 | 79246.33 | 12-MAR-15:09 | 10062.96 | 08-MAR-16:30 | 0.00 | 01-MAR-00:10 |
April | 93091.76 | 03-APR-19:10 | 16690.39 | 01-APR-00:10 | 89674.66 | 03-APR-06:10 | 40537.60 | 03-APR-06:19 | 82117.85 | 13-APR-15:09 | 10471.01 | 29-APR-15:50 | 0.00 | 01-APR-00:10 |
May | 93091.76 | 01-MAY-19:10 | 16690.39 | 01-MAY-00:10 | 89674.66 | 01-MAY-06:10 | 40537.60 | 01-MAY-06:19 | 81721.80 | 27-MAY-15:09 | 11325.82 | 27-MAY-10:50 | 0.00 | 01-MAY-00:10 |
June | 93091.76 | 01-JUN-19:10 | 16690.39 | 01-JUN-00:10 | 89674.66 | 01-JUN-06:10 | 40537.60 | 01-JUN-06:19 | 89225.66 | 26-JUN-18:19 | 11826.89 | 29-JUN-18:19 | 0.00 | 01-JUN-00:10 |
July | 93091.76 | 03-JUL-19:10 | 16690.39 | 01-JUL-00:10 | 89674.66 | 03-JUL-06:10 | 40537.60 | 03-JUL-06:19 | 93468.95 | 22-JUL-15:20 | 12220.85 | 23-JUL-15:30 | 0.00 | 01-JUL-00:10 |
August | 93091.76 | 01-AUG-19:10 | 16690.39 | 01-AUG-00:10 | 89674.66 | 01-AUG-06:10 | 40537.60 | 01-AUG-06:19 | 93130.21 | 07-AUG-15:20 | 11899.07 | 09-AUG-15:50 | 0.00 | 01-AUG-00:10 |
September | 93091.76 | 01-SEP-19:10 | 16690.39 | 01-SEP-00:10 | 89674.66 | 01-SEP-06:10 | 40537.60 | 01-SEP-06:19 | 90904.33 | 13-SEP-15:20 | 11760.02 | 02-SEP-18:10 | 0.00 | 01-SEP-00:10 |
October | 93091.76 | 02-OCT-19:10 | 16690.39 | 01-OCT-00:10 | 89674.66 | 02-OCT-06:10 | 40537.60 | 02-OCT-06:19 | 86738.29 | 03-OCT-15:09 | 11205.89 | 01-OCT-10:50 | 0.00 | 01-OCT-00:10 |
November | 93091.76 | 01-NOV-19:10 | 16690.39 | 01-NOV-00:10 | 89674.66 | 01-NOV-06:10 | 40537.60 | 01-NOV-06:19 | 80519.22 | 01-NOV-15:09 | 8890.89 | 02-NOV-15:09 | 0.00 | 01-NOV-00:10 |
December | 93091.76 | 01-DEC-20:10 | 16690.39 | 01-DEC-00:10 | 89674.66 | 01-DEC-07:10 | 40537.60 | 01-DEC-07:19 | 82779.26 | 21-DEC-16:10 | 7873.92 | 31-DEC-16:30 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 93091.76 | 16690.39 | 89674.66 | 40537.60 | 79246.33 | 7873.92 | 0.00 | |||||||
Maximum of Months | 93091.76 | 16690.39 | 89674.66 | 40537.60 | 93468.95 | 12220.85 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY {Maximum} [W] | HEATRECOVERY:ELECTRICITY {TIMESTAMP} | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 60625.02 | 01-JAN-14:00 | 0.00 | 0.00 | 19111.97 | 01-JAN-11:20 | 4738.99 | 02-JAN-07:10 | 0.00 |
February | 110486.37 | 14-FEB-16:10 | 0.00 | 0.00 | 19111.97 | 01-FEB-18:19 | 4739.42 | 22-FEB-07:10 | 0.00 |
March | 111211.34 | 08-MAR-16:10 | 0.00 | 0.00 | 19111.97 | 01-MAR-00:10 | 4739.19 | 31-MAR-06:10 | 0.00 |
April | 132059.26 | 13-APR-15:09 | 0.00 | 0.00 | 19111.97 | 01-APR-07:19 | 4738.27 | 18-APR-06:10 | 0.00 |
May | 162505.49 | 19-MAY-15:09 | 0.00 | 0.00 | 19111.97 | 01-MAY-10:20 | 4738.53 | 22-MAY-06:30 | 0.00 |
June | 250573.12 | 28-JUN-15:20 | 0.00 | 0.00 | 19111.97 | 01-JUN-21:10 | 4738.64 | 14-JUN-06:19 | 0.00 |
July | 248692.01 | 22-JUL-15:09 | 0.00 | 0.00 | 19111.97 | 01-JUL-10:20 | 4738.79 | 18-JUL-06:10 | 0.00 |
August | 219997.17 | 20-AUG-15:20 | 0.00 | 0.00 | 19111.97 | 01-AUG-07:19 | 4738.66 | 30-AUG-06:19 | 0.00 |
September | 182566.46 | 02-SEP-15:20 | 0.00 | 0.00 | 19111.97 | 02-SEP-15:20 | 4739.14 | 20-SEP-06:19 | 0.00 |
October | 157663.20 | 01-OCT-15:09 | 0.00 | 0.00 | 19111.97 | 01-OCT-10:20 | 4739.28 | 04-OCT-06:19 | 0.00 |
November | 73241.87 | 02-NOV-15:09 | 0.00 | 0.00 | 19111.97 | 01-NOV-17:19 | 4739.23 | 14-NOV-07:10 | 0.00 |
December | 37119.58 | 31-DEC-16:10 | 0.00 | 0.00 | 19111.97 | 01-DEC-00:10 | 4739.92 | 28-DEC-07:19 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 37119.58 | 0.00 | 0.00 | 19111.97 | 4738.27 | 0.00 | |||
Maximum of Months | 250573.12 | 0.00 | 0.00 | 19111.97 | 4739.92 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 348321.66 | 09-JAN-20:49 | 93091.76 | 88971.67 | 16690.39 | 33025.38 | 68269.61 | 6890.68 | 0.00 | 15529.31 | 0.00 |
February | 360894.56 | 14-FEB-20:10 | 93091.76 | 88971.67 | 16690.39 | 33012.66 | 70842.92 | 7651.79 | 0.00 | 25204.82 | 0.00 |
March | 378372.63 | 13-MAR-19:10 | 93091.76 | 88971.67 | 16690.39 | 33012.66 | 69251.71 | 8539.21 | 0.00 | 62210.13 | 0.00 |
April | 459312.67 | 28-APR-19:10 | 93091.76 | 88971.67 | 16690.39 | 33012.66 | 75433.36 | 9997.36 | 0.00 | 116806.19 | 0.00 |
May | 483621.76 | 19-MAY-19:10 | 93091.76 | 88971.67 | 16690.39 | 33012.66 | 77063.62 | 10204.54 | 0.00 | 139110.35 | 0.00 |
June | 531871.03 | 26-JUN-18:10 | 82800.17 | 79617.06 | 0.00 | 32686.23 | 87873.58 | 10646.25 | 0.00 | 211611.51 | 0.00 |
July | 552594.89 | 20-JUL-18:10 | 82800.17 | 79617.06 | 0.00 | 32686.23 | 85055.87 | 10668.14 | 0.00 | 235101.95 | 0.00 |
August | 523584.82 | 20-AUG-18:10 | 82807.27 | 76644.19 | 0.00 | 32602.97 | 85904.49 | 10577.24 | 0.00 | 209326.95 | 0.00 |
September | 482897.05 | 13-SEP-19:10 | 93091.76 | 88971.67 | 16690.39 | 33012.66 | 78087.96 | 11146.87 | 0.00 | 136258.10 | 0.00 |
October | 454712.70 | 05-OCT-18:10 | 82800.17 | 79617.06 | 16690.39 | 32686.23 | 78980.83 | 10223.12 | 0.00 | 127125.87 | 0.00 |
November | 364057.08 | 02-NOV-19:10 | 93091.76 | 88971.67 | 16690.39 | 33012.66 | 71021.56 | 8343.51 | 0.00 | 46312.10 | 0.00 |
December | 346085.38 | 01-DEC-20:49 | 93091.76 | 88971.67 | 16690.39 | 33025.38 | 67841.51 | 6768.03 | 0.00 | 14268.10 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 346085.38 | 82800.17 | 76644.19 | 0.00 | 32602.97 | 67841.51 | 6768.03 | 0.00 | 14268.10 | 0.00 | |
Maximum of Months | 552594.89 | 93091.76 | 88971.67 | 16690.39 | 33025.38 | 87873.58 | 11146.87 | 0.00 | 235101.95 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 104248.32 | 02-JAN-18:10 | 0.00 | 236891.60 | 21-JAN-07:10 | 0.00 | 287241.44 | 30-JAN-21:40 | 0.00 |
February | 104248.32 | 01-FEB-18:10 | 0.00 | 211222.87 | 04-FEB-07:10 | 0.00 | 287399.46 | 08-FEB-21:40 | 0.00 |
March | 104248.32 | 01-MAR-18:10 | 0.00 | 120185.25 | 05-MAR-05:00 | 0.00 | 283622.33 | 02-MAR-21:00 | 0.00 |
April | 104248.32 | 01-APR-17:10 | 0.00 | 114312.22 | 06-APR-10:39 | 0.00 | 270444.35 | 02-APR-21:10 | 0.00 |
May | 104248.32 | 01-MAY-17:10 | 0.00 | 118533.33 | 05-MAY-10:39 | 0.00 | 249621.37 | 01-MAY-20:40 | 0.00 |
June | 104248.32 | 01-JUN-17:10 | 0.00 | 106269.82 | 09-JUN-10:39 | 0.00 | 247381.73 | 01-JUN-20:00 | 0.00 |
July | 104248.32 | 01-JUL-17:10 | 0.00 | 85892.18 | 03-JUL-10:39 | 0.00 | 244485.98 | 02-JUL-21:19 | 0.00 |
August | 104248.32 | 01-AUG-17:10 | 0.00 | 88964.38 | 29-AUG-10:39 | 0.00 | 240437.81 | 31-AUG-17:49 | 0.00 |
September | 104248.32 | 01-SEP-17:10 | 0.00 | 89940.89 | 08-SEP-10:39 | 0.00 | 246297.17 | 28-SEP-20:00 | 0.00 |
October | 104248.32 | 02-OCT-17:10 | 0.00 | 143295.64 | 25-OCT-08:09 | 0.00 | 248509.88 | 31-OCT-20:49 | 0.00 |
November | 104248.32 | 01-NOV-17:10 | 0.00 | 141275.43 | 27-NOV-07:10 | 0.00 | 252381.66 | 29-NOV-21:19 | 0.00 |
December | 104248.32 | 01-DEC-18:10 | 0.00 | 223065.44 | 15-DEC-07:10 | 0.00 | 282465.88 | 27-DEC-21:40 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 104248.32 | 0.00 | 85892.18 | 0.00 | 240437.81 | 0.00 | |||
Maximum of Months | 104248.32 | 0.00 | 236891.60 | 0.00 | 287399.46 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.78 | 0.17 | 21.78 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.86 | 0.17 | 21.86 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.82 | 0.67 | 21.82 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.78 | 0.17 | 21.78 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 1.17 | 21.81 | 1.17 | 21.81 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.86 | 0.67 | 21.86 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.89 | 0.17 | 21.89 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.74 | 0.33 | 21.74 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.68 | 0.50 | 21.68 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 1.00 | 21.74 | 1.00 | 21.74 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.89 | 0.50 | 21.89 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.76 | 0.17 | 21.76 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.73 | 0.33 | 21.73 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.70 | 0.33 | 21.70 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.17 | 20.49 | 0.17 | 20.49 | 0.00 | 20.49 | 0.00 | 20.49 |
Annual Sum or Average | 0.17 | 20.49 | 0.17 | 20.49 | 0.83 | 21.37 | 0.83 | 21.52 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 20.49 | 0.17 | 20.49 | 0.33 | 21.76 | 0.33 | 21.76 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.70 | 0.17 | 21.70 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.17 | 21.70 | 0.17 | 21.70 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.70 | 0.17 | 21.70 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.68 | 0.33 | 21.68 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.71 | 0.33 | 21.71 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.67 | 21.69 | 0.67 | 21.69 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.71 | 0.33 | 21.71 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.83 | 0.83 | 21.83 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 21.80 | 1.83 | 21.80 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 21.85 | 4.33 | 21.85 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 21.76 | 1.17 | 21.76 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.83 | 0.33 | 21.83 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 8.50 | 21.83 | 8.50 | 21.83 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 21.85 | 4.33 | 21.85 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.89 | 0.83 | 21.89 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 21.82 | 1.33 | 21.82 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 21.82 | 1.50 | 21.82 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 3.67 | 21.83 | 3.67 | 21.83 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 21.89 | 1.50 | 21.89 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.72 | 0.17 | 21.72 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 21.79 | 2.00 | 21.79 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 21.88 | 3.33 | 21.88 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 22.02 | 2.17 | 22.02 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 7.67 | 21.89 | 7.67 | 21.89 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 22.02 | 3.33 | 22.02 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.68 | 0.17 | 24.68 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.61 | 0.33 | 24.61 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.50 | 24.63 | 0.50 | 24.63 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.68 | 0.33 | 24.68 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.08 | 15.33 | 21.08 | 15.33 | 21.08 |
February | 672.00 | 21.05 | 29.00 | 21.05 | 29.00 | 21.04 |
March | 744.00 | 21.02 | 81.50 | 21.02 | 81.50 | 21.02 |
April | 720.00 | 21.01 | 133.50 | 21.00 | 133.50 | 20.99 |
May | 744.00 | 21.01 | 52.67 | 21.00 | 52.67 | 21.00 |
June | 720.00 | 21.01 | 3.67 | 21.01 | 3.67 | 21.01 |
July | 744.00 | 21.04 | 2.83 | 21.04 | 2.83 | 21.04 |
August | 744.00 | 21.08 | 10.00 | 21.08 | 10.00 | 21.08 |
September | 720.00 | 21.16 | 6.50 | 21.16 | 6.50 | 21.16 |
October | 744.00 | 21.24 | 0.00 | 21.24 | 0.00 | 21.24 |
November | 720.00 | 21.24 | 0.00 | 21.24 | 0.00 | 21.24 |
December | 744.00 | 21.18 | 15.17 | 21.17 | 15.17 | 21.17 |
Annual Sum or Average | 8760.00 | 21.09 | 350.17 | 21.09 | 350.17 | 21.08 |
Minimum of Months | 672.00 | 21.01 | 0.00 | 21.00 | 0.00 | 20.99 |
Maximum of Months | 744.00 | 21.24 | 133.50 | 21.24 | 133.50 | 21.24 |
Report: ComfortReportSimple55Monthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 669.00 | 21.12 | 304.50 | 21.16 | 278.83 | 21.12 |
February | 620.17 | 21.16 | 189.50 | 21.20 | 168.83 | 21.17 |
March | 713.17 | 21.14 | 127.33 | 21.12 | 125.17 | 21.11 |
April | 720.00 | 21.11 | 82.00 | 21.10 | 82.00 | 21.09 |
May | 744.00 | 21.03 | 27.67 | 21.03 | 27.67 | 21.03 |
June | 720.00 | 21.05 | 0.00 | 21.05 | 0.00 | 21.05 |
July | 744.00 | 21.11 | 0.00 | 21.11 | 0.00 | 21.11 |
August | 681.50 | 21.13 | 17.67 | 21.16 | 0.00 | 21.16 |
September | 601.17 | 21.11 | 82.83 | 21.36 | 0.00 | 21.36 |
October | 624.83 | 21.15 | 121.00 | 21.37 | 51.67 | 21.34 |
November | 632.50 | 21.16 | 151.33 | 21.23 | 122.33 | 21.20 |
December | 669.50 | 21.17 | 327.67 | 21.16 | 311.50 | 21.12 |
Annual Sum or Average | 8139.83 | 21.12 | 1431.50 | 21.17 | 1168.00 | 21.15 |
Minimum of Months | 601.17 | 21.03 | 0.00 | 21.03 | 0.00 | 21.03 |
Maximum of Months | 744.00 | 21.17 | 327.67 | 21.37 | 311.50 | 21.36 |
Report: ComfortReportSimple55Monthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.01 | 3.67 | 21.01 | 3.67 | 21.01 |
February | 672.00 | 21.02 | 5.67 | 21.02 | 5.67 | 21.02 |
March | 744.00 | 21.04 | 0.00 | 21.04 | 0.00 | 21.04 |
April | 720.00 | 21.08 | 0.00 | 21.08 | 0.00 | 21.08 |
May | 744.00 | 21.10 | 0.00 | 21.10 | 0.00 | 21.10 |
June | 720.00 | 21.19 | 0.00 | 21.19 | 0.00 | 21.19 |
July | 744.00 | 21.22 | 23.17 | 21.22 | 23.17 | 21.22 |
August | 744.00 | 21.22 | 37.17 | 21.22 | 37.17 | 21.23 |
September | 720.00 | 21.17 | 17.83 | 21.16 | 17.83 | 21.16 |
October | 744.00 | 21.10 | 0.00 | 21.10 | 0.00 | 21.10 |
November | 720.00 | 21.03 | 0.00 | 21.03 | 0.00 | 21.03 |
December | 744.00 | 21.01 | 29.33 | 21.01 | 29.33 | 21.01 |
Annual Sum or Average | 8760.00 | 21.10 | 116.83 | 21.10 | 116.83 | 21.10 |
Minimum of Months | 672.00 | 21.01 | 0.00 | 21.01 | 0.00 | 21.01 |
Maximum of Months | 744.00 | 21.22 | 37.17 | 21.22 | 37.17 | 21.23 |
Report: ComfortReportSimple55Monthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.00 | 400.33 | 21.00 | 400.33 | 21.00 |
February | 672.00 | 21.00 | 212.17 | 21.00 | 212.17 | 21.00 |
March | 744.00 | 21.00 | 144.67 | 21.00 | 144.67 | 21.00 |
April | 720.00 | 21.01 | 127.33 | 21.01 | 127.33 | 21.01 |
May | 744.00 | 21.03 | 44.67 | 21.03 | 44.67 | 21.02 |
June | 720.00 | 21.10 | 0.00 | 21.10 | 0.00 | 21.10 |
July | 744.00 | 21.12 | 0.00 | 21.12 | 0.00 | 21.12 |
August | 744.00 | 21.10 | 0.00 | 21.10 | 0.00 | 21.10 |
September | 720.00 | 21.04 | 0.00 | 21.04 | 0.00 | 21.04 |
October | 744.00 | 21.01 | 44.50 | 21.01 | 44.50 | 21.01 |
November | 720.00 | 21.00 | 231.50 | 21.00 | 231.50 | 21.00 |
December | 744.00 | 21.00 | 512.17 | 21.00 | 512.17 | 21.00 |
Annual Sum or Average | 8760.00 | 21.03 | 1717.33 | 21.03 | 1717.33 | 21.02 |
Minimum of Months | 672.00 | 21.00 | 0.00 | 21.00 | 0.00 | 21.00 |
Maximum of Months | 744.00 | 21.12 | 512.17 | 21.12 | 512.17 | 21.12 |
Report: ComfortReportSimple55Monthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.00 | 614.00 | 21.00 | 614.00 | 21.00 |
February | 672.00 | 21.00 | 375.50 | 21.00 | 375.50 | 21.00 |
March | 744.00 | 21.00 | 297.83 | 21.00 | 297.83 | 21.00 |
April | 720.00 | 21.00 | 229.17 | 21.00 | 229.17 | 21.00 |
May | 744.00 | 21.00 | 73.17 | 21.00 | 73.17 | 21.00 |
June | 720.00 | 21.04 | 0.00 | 21.04 | 0.00 | 21.04 |
July | 744.00 | 21.05 | 0.00 | 21.05 | 0.00 | 21.05 |
August | 744.00 | 21.03 | 0.00 | 21.03 | 0.00 | 21.03 |
September | 720.00 | 21.00 | 0.00 | 21.00 | 0.00 | 21.00 |
October | 744.00 | 21.00 | 126.83 | 21.00 | 126.83 | 21.00 |
November | 720.00 | 21.00 | 354.17 | 21.00 | 354.17 | 21.00 |
December | 744.00 | 21.00 | 661.33 | 21.00 | 661.33 | 21.00 |
Annual Sum or Average | 8760.00 | 21.01 | 2732.00 | 21.01 | 2732.00 | 21.01 |
Minimum of Months | 672.00 | 21.00 | 0.00 | 21.00 | 0.00 | 21.00 |
Maximum of Months | 744.00 | 21.05 | 661.33 | 21.05 | 661.33 | 21.05 |
Report: ComfortReportSimple55Monthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 592.33 | 21.32 | 143.17 | 21.67 | 68.00 | 21.85 |
February | 513.00 | 21.35 | 131.33 | 21.71 | 65.67 | 21.90 |
March | 555.00 | 21.40 | 150.50 | 21.75 | 82.67 | 21.96 |
April | 519.00 | 21.39 | 145.17 | 21.73 | 78.33 | 21.93 |
May | 424.33 | 21.55 | 231.50 | 21.80 | 94.50 | 22.01 |
June | 258.17 | 21.92 | 318.00 | 21.90 | 101.33 | 22.12 |
July | 128.50 | 22.89 | 593.67 | 21.71 | 111.67 | 21.91 |
August | 141.00 | 22.83 | 548.00 | 21.79 | 113.67 | 22.00 |
September | 193.00 | 22.28 | 387.17 | 21.92 | 105.50 | 22.14 |
October | 436.67 | 21.53 | 211.00 | 21.82 | 90.67 | 22.04 |
November | 537.50 | 21.38 | 147.50 | 21.73 | 74.67 | 21.93 |
December | 594.33 | 21.30 | 139.50 | 21.65 | 62.83 | 21.82 |
Annual Sum or Average | 4892.83 | 21.54 | 3146.50 | 21.76 | 1049.50 | 21.96 |
Minimum of Months | 128.50 | 21.30 | 131.33 | 21.65 | 62.83 | 21.82 |
Maximum of Months | 594.33 | 22.89 | 593.67 | 21.92 | 113.67 | 22.14 |
Report: ComfortReportSimple55Monthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 659.17 | 21.10 | 65.33 | 21.21 | 27.33 | 21.20 |
February | 607.67 | 21.14 | 39.50 | 21.21 | 14.67 | 21.21 |
March | 704.50 | 21.12 | 3.50 | 21.13 | 1.50 | 21.13 |
April | 719.00 | 21.12 | 0.00 | 21.12 | 0.00 | 21.12 |
May | 744.00 | 21.08 | 0.00 | 21.08 | 0.00 | 21.08 |
June | 720.00 | 21.16 | 9.33 | 21.17 | 9.33 | 21.17 |
July | 743.33 | 21.24 | 145.83 | 21.27 | 145.83 | 21.29 |
August | 687.50 | 21.31 | 108.83 | 21.34 | 98.00 | 21.36 |
September | 598.00 | 21.29 | 111.00 | 21.42 | 29.00 | 21.42 |
October | 614.17 | 21.27 | 74.67 | 21.44 | 1.67 | 21.43 |
November | 621.17 | 21.16 | 38.67 | 21.28 | 0.00 | 21.28 |
December | 654.50 | 21.13 | 65.67 | 21.19 | 40.67 | 21.18 |
Annual Sum or Average | 8073.00 | 21.17 | 662.33 | 21.24 | 368.00 | 21.24 |
Minimum of Months | 598.00 | 21.08 | 0.00 | 21.08 | 0.00 | 21.08 |
Maximum of Months | 744.00 | 21.31 | 145.83 | 21.44 | 145.83 | 21.43 |
Report: ComfortReportSimple55Monthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.06 | 0.00 | 21.06 | 0.00 | 21.06 |
February | 672.00 | 21.08 | 0.00 | 21.08 | 0.00 | 21.08 |
March | 744.00 | 21.11 | 0.00 | 21.11 | 0.00 | 21.11 |
April | 720.00 | 21.18 | 0.00 | 21.18 | 0.00 | 21.18 |
May | 744.00 | 21.22 | 0.00 | 21.22 | 0.00 | 21.22 |
June | 720.00 | 21.32 | 9.17 | 21.33 | 9.17 | 21.33 |
July | 744.00 | 21.37 | 141.17 | 21.41 | 141.17 | 21.44 |
August | 744.00 | 21.38 | 96.00 | 21.41 | 96.00 | 21.45 |
September | 720.00 | 21.33 | 28.33 | 21.34 | 28.33 | 21.34 |
October | 744.00 | 21.24 | 0.00 | 21.24 | 0.00 | 21.24 |
November | 720.00 | 21.12 | 0.00 | 21.12 | 0.00 | 21.12 |
December | 744.00 | 21.06 | 1.67 | 21.06 | 1.67 | 21.06 |
Annual Sum or Average | 8760.00 | 21.21 | 276.33 | 21.22 | 276.33 | 21.23 |
Minimum of Months | 672.00 | 21.06 | 0.00 | 21.06 | 0.00 | 21.06 |
Maximum of Months | 744.00 | 21.38 | 141.17 | 21.41 | 141.17 | 21.45 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 742.67 | 21.31 | 336.00 | 21.18 | 336.00 | 21.11 |
February | 662.33 | 21.39 | 183.17 | 21.28 | 183.17 | 21.22 |
March | 733.00 | 21.48 | 71.17 | 21.43 | 71.17 | 21.40 |
April | 705.17 | 21.60 | 18.67 | 21.58 | 18.67 | 21.57 |
May | 707.67 | 21.56 | 4.83 | 21.56 | 4.83 | 21.55 |
June | 629.17 | 21.47 | 15.00 | 21.51 | 0.00 | 21.51 |
July | 584.33 | 21.31 | 73.50 | 21.53 | 1.83 | 21.54 |
August | 577.17 | 21.28 | 80.83 | 21.53 | 1.33 | 21.53 |
September | 577.17 | 21.31 | 56.50 | 21.49 | 1.17 | 21.49 |
October | 679.67 | 21.45 | 60.00 | 21.46 | 43.83 | 21.42 |
November | 709.33 | 21.48 | 118.33 | 21.40 | 118.33 | 21.35 |
December | 744.00 | 21.31 | 366.17 | 21.17 | 366.17 | 21.10 |
Annual Sum or Average | 8051.67 | 21.42 | 1384.17 | 21.40 | 1146.50 | 21.35 |
Minimum of Months | 577.17 | 21.28 | 4.83 | 21.17 | 0.00 | 21.10 |
Maximum of Months | 744.00 | 21.60 | 366.17 | 21.58 | 366.17 | 21.57 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.91 | 614.83 | 20.85 | 614.83 | 20.83 |
February | 672.00 | 21.06 | 360.67 | 20.96 | 360.67 | 20.91 |
March | 744.00 | 21.30 | 151.50 | 21.23 | 151.50 | 21.19 |
April | 716.67 | 21.53 | 33.50 | 21.51 | 33.50 | 21.49 |
May | 720.50 | 21.56 | 6.83 | 21.56 | 6.83 | 21.55 |
June | 638.17 | 21.50 | 15.83 | 21.54 | 0.00 | 21.54 |
July | 594.33 | 21.34 | 62.33 | 21.53 | 1.67 | 21.53 |
August | 607.00 | 21.37 | 57.17 | 21.53 | 1.83 | 21.53 |
September | 635.83 | 21.45 | 23.33 | 21.51 | 3.17 | 21.51 |
October | 725.50 | 21.39 | 91.17 | 21.33 | 89.33 | 21.28 |
November | 720.00 | 21.18 | 300.83 | 21.09 | 300.83 | 21.04 |
December | 744.00 | 20.84 | 642.17 | 20.79 | 642.17 | 20.77 |
Annual Sum or Average | 8262.00 | 21.28 | 2360.17 | 21.21 | 2206.33 | 21.14 |
Minimum of Months | 594.33 | 20.84 | 6.83 | 20.79 | 0.00 | 20.77 |
Maximum of Months | 744.00 | 21.56 | 642.17 | 21.56 | 642.17 | 21.55 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.99 | 469.17 | 20.96 | 469.17 | 20.95 |
February | 672.00 | 21.08 | 215.33 | 21.04 | 215.33 | 21.01 |
March | 744.00 | 21.28 | 13.50 | 21.28 | 13.50 | 21.28 |
April | 720.00 | 21.45 | 1.50 | 21.45 | 1.50 | 21.45 |
May | 744.00 | 21.55 | 0.00 | 21.55 | 0.00 | 21.55 |
June | 720.00 | 21.66 | 0.00 | 21.66 | 0.00 | 21.66 |
July | 743.00 | 21.70 | 1.67 | 21.70 | 1.67 | 21.70 |
August | 744.00 | 21.66 | 0.33 | 21.66 | 0.33 | 21.66 |
September | 720.00 | 21.58 | 0.17 | 21.58 | 0.17 | 21.58 |
October | 744.00 | 21.36 | 17.50 | 21.35 | 17.50 | 21.34 |
November | 720.00 | 21.17 | 116.67 | 21.14 | 116.67 | 21.13 |
December | 744.00 | 20.92 | 589.00 | 20.89 | 589.00 | 20.88 |
Annual Sum or Average | 8759.00 | 21.37 | 1424.83 | 21.30 | 1424.83 | 21.25 |
Minimum of Months | 672.00 | 20.92 | 0.00 | 20.89 | 0.00 | 20.88 |
Maximum of Months | 744.00 | 21.70 | 589.00 | 21.70 | 589.00 | 21.70 |
Report: ComfortReportSimple55Monthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.36 | 318.17 | 21.23 | 318.17 | 21.16 |
February | 671.83 | 21.47 | 194.67 | 21.36 | 194.67 | 21.29 |
March | 743.17 | 21.60 | 67.33 | 21.55 | 67.33 | 21.52 |
April | 709.50 | 21.70 | 23.17 | 21.68 | 23.17 | 21.67 |
May | 691.33 | 21.61 | 6.83 | 21.61 | 4.50 | 21.61 |
June | 587.83 | 21.39 | 19.83 | 21.46 | 0.00 | 21.46 |
July | 542.17 | 21.18 | 103.67 | 21.53 | 1.00 | 21.53 |
August | 544.33 | 21.18 | 112.83 | 21.55 | 0.00 | 21.55 |
September | 557.50 | 21.28 | 49.17 | 21.44 | 0.17 | 21.44 |
October | 683.67 | 21.52 | 53.67 | 21.51 | 44.33 | 21.47 |
November | 716.00 | 21.55 | 127.50 | 21.47 | 127.50 | 21.41 |
December | 744.00 | 21.36 | 360.50 | 21.23 | 360.50 | 21.16 |
Annual Sum or Average | 7935.33 | 21.45 | 1437.33 | 21.45 | 1141.33 | 21.40 |
Minimum of Months | 542.17 | 21.18 | 6.83 | 21.23 | 0.00 | 21.16 |
Maximum of Months | 744.00 | 21.70 | 360.50 | 21.68 | 360.50 | 21.67 |
Report: ComfortReportSimple55Monthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.90 | 590.67 | 20.88 | 590.67 | 20.87 |
February | 672.00 | 21.07 | 366.83 | 21.00 | 366.83 | 20.97 |
March | 744.00 | 21.47 | 118.00 | 21.41 | 118.00 | 21.37 |
April | 714.50 | 21.69 | 35.00 | 21.67 | 35.00 | 21.64 |
May | 703.33 | 21.63 | 8.50 | 21.63 | 6.00 | 21.63 |
June | 601.00 | 21.44 | 18.17 | 21.49 | 0.00 | 21.49 |
July | 542.33 | 21.18 | 55.17 | 21.38 | 1.00 | 21.38 |
August | 550.33 | 21.20 | 36.17 | 21.33 | 0.00 | 21.33 |
September | 599.83 | 21.41 | 5.50 | 21.42 | 2.00 | 21.42 |
October | 723.83 | 21.52 | 73.00 | 21.47 | 72.67 | 21.42 |
November | 720.00 | 21.18 | 281.50 | 21.12 | 281.50 | 21.09 |
December | 744.00 | 20.80 | 655.50 | 20.78 | 655.50 | 20.77 |
Annual Sum or Average | 8059.17 | 21.29 | 2244.00 | 21.22 | 2129.17 | 21.16 |
Minimum of Months | 542.33 | 20.80 | 5.50 | 20.78 | 0.00 | 20.77 |
Maximum of Months | 744.00 | 21.69 | 655.50 | 21.67 | 655.50 | 21.64 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.01 | 180.33 | 21.01 | 180.33 | 21.01 |
February | 672.00 | 21.02 | 75.50 | 21.02 | 75.50 | 21.02 |
March | 744.00 | 21.03 | 18.50 | 21.03 | 18.50 | 21.03 |
April | 720.00 | 21.12 | 68.50 | 21.11 | 68.50 | 21.11 |
May | 744.00 | 21.21 | 41.00 | 21.20 | 41.00 | 21.19 |
June | 720.00 | 21.60 | 3.67 | 21.60 | 3.67 | 21.60 |
July | 744.00 | 21.88 | 100.00 | 21.87 | 100.00 | 21.87 |
August | 744.00 | 21.89 | 66.50 | 21.89 | 66.50 | 21.88 |
September | 720.00 | 21.66 | 22.50 | 21.66 | 22.50 | 21.65 |
October | 744.00 | 21.35 | 3.33 | 21.35 | 3.33 | 21.35 |
November | 720.00 | 21.04 | 55.50 | 21.03 | 55.50 | 21.03 |
December | 744.00 | 21.00 | 358.50 | 21.00 | 358.50 | 21.00 |
Annual Sum or Average | 8760.00 | 21.32 | 993.83 | 21.30 | 993.83 | 21.29 |
Minimum of Months | 672.00 | 21.00 | 3.33 | 21.00 | 3.33 | 21.00 |
Maximum of Months | 744.00 | 21.89 | 358.50 | 21.89 | 358.50 | 21.88 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 736.50 | 21.22 | 434.17 | 21.09 | 434.17 | 21.03 |
February | 653.00 | 21.31 | 284.50 | 21.19 | 284.50 | 21.12 |
March | 723.33 | 21.43 | 168.00 | 21.34 | 168.00 | 21.28 |
April | 683.17 | 21.54 | 59.00 | 21.50 | 59.00 | 21.47 |
May | 671.83 | 21.48 | 22.50 | 21.48 | 16.17 | 21.47 |
June | 584.00 | 21.36 | 47.00 | 21.51 | 0.00 | 21.51 |
July | 552.83 | 21.24 | 140.33 | 21.65 | 6.17 | 21.66 |
August | 546.33 | 21.23 | 144.83 | 21.65 | 6.00 | 21.65 |
September | 555.50 | 21.26 | 103.83 | 21.56 | 6.33 | 21.56 |
October | 660.17 | 21.38 | 103.00 | 21.40 | 74.83 | 21.35 |
November | 697.67 | 21.41 | 221.00 | 21.31 | 220.00 | 21.24 |
December | 740.83 | 21.23 | 453.17 | 21.09 | 453.17 | 21.03 |
Annual Sum or Average | 7805.17 | 21.34 | 2181.33 | 21.36 | 1728.33 | 21.29 |
Minimum of Months | 546.33 | 21.22 | 22.50 | 21.09 | 0.00 | 21.03 |
Maximum of Months | 740.83 | 21.54 | 453.17 | 21.65 | 453.17 | 21.66 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.83 | 658.17 | 20.78 | 658.17 | 20.76 |
February | 671.67 | 21.01 | 445.83 | 20.91 | 445.83 | 20.87 |
March | 743.50 | 21.28 | 252.00 | 21.19 | 252.00 | 21.14 |
April | 702.67 | 21.52 | 72.00 | 21.48 | 72.00 | 21.44 |
May | 686.50 | 21.50 | 21.83 | 21.50 | 17.33 | 21.49 |
June | 588.50 | 21.38 | 40.67 | 21.51 | 0.00 | 21.51 |
July | 555.83 | 21.25 | 121.00 | 21.61 | 5.33 | 21.61 |
August | 563.67 | 21.26 | 109.67 | 21.58 | 7.50 | 21.58 |
September | 597.17 | 21.35 | 57.67 | 21.50 | 7.33 | 21.50 |
October | 710.50 | 21.35 | 121.00 | 21.29 | 113.33 | 21.24 |
November | 719.67 | 21.12 | 414.50 | 21.03 | 414.50 | 20.99 |
December | 744.00 | 20.76 | 678.50 | 20.72 | 678.50 | 20.71 |
Annual Sum or Average | 8027.67 | 21.21 | 2992.83 | 21.17 | 2671.83 | 21.09 |
Minimum of Months | 555.83 | 20.76 | 21.83 | 20.72 | 0.00 | 20.71 |
Maximum of Months | 744.00 | 21.52 | 678.50 | 21.61 | 678.50 | 21.61 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 663.17 | 21.31 | 184.00 | 21.23 | 184.00 | 21.17 |
February | 597.00 | 21.37 | 101.33 | 21.31 | 101.33 | 21.27 |
March | 677.50 | 21.44 | 41.67 | 21.42 | 40.33 | 21.40 |
April | 690.00 | 21.59 | 20.83 | 21.58 | 20.83 | 21.56 |
May | 707.00 | 21.57 | 7.17 | 21.57 | 7.17 | 21.56 |
June | 637.50 | 21.50 | 2.50 | 21.50 | 0.00 | 21.50 |
July | 587.00 | 21.31 | 73.33 | 21.53 | 3.17 | 21.54 |
August | 576.83 | 21.27 | 113.67 | 21.61 | 2.17 | 21.61 |
September | 566.00 | 21.29 | 112.67 | 21.63 | 0.67 | 21.63 |
October | 618.00 | 21.34 | 97.17 | 21.50 | 33.00 | 21.48 |
November | 623.17 | 21.38 | 45.17 | 21.38 | 37.50 | 21.36 |
December | 650.00 | 21.28 | 215.83 | 21.20 | 215.83 | 21.16 |
Annual Sum or Average | 7593.17 | 21.39 | 1015.33 | 21.45 | 646.00 | 21.41 |
Minimum of Months | 566.00 | 21.27 | 2.50 | 21.20 | 0.00 | 21.16 |
Maximum of Months | 707.00 | 21.59 | 215.83 | 21.63 | 215.83 | 21.63 |
Report: ComfortReportSimple55Monthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.23 | 0.00 | 21.23 | 0.00 | 21.23 |
February | 672.00 | 21.28 | 0.00 | 21.28 | 0.00 | 21.28 |
March | 744.00 | 21.39 | 0.00 | 21.39 | 0.00 | 21.39 |
April | 720.00 | 21.53 | 0.00 | 21.53 | 0.00 | 21.53 |
May | 740.50 | 21.65 | 0.67 | 21.65 | 0.67 | 21.65 |
June | 662.50 | 21.73 | 31.83 | 21.78 | 15.67 | 21.80 |
July | 670.67 | 21.78 | 201.67 | 21.94 | 176.83 | 22.01 |
August | 676.17 | 21.73 | 150.83 | 21.87 | 130.67 | 21.94 |
September | 697.83 | 21.64 | 44.50 | 21.67 | 41.83 | 21.69 |
October | 740.33 | 21.48 | 1.83 | 21.48 | 1.17 | 21.48 |
November | 720.00 | 21.33 | 0.00 | 21.33 | 0.00 | 21.33 |
December | 744.00 | 21.22 | 0.00 | 21.22 | 0.00 | 21.22 |
Annual Sum or Average | 8532.00 | 21.49 | 431.33 | 21.54 | 366.83 | 21.57 |
Minimum of Months | 662.50 | 21.22 | 0.00 | 21.22 | 0.00 | 21.22 |
Maximum of Months | 744.00 | 21.78 | 201.67 | 21.94 | 176.83 | 22.01 |
Report: ComfortReportSimple55Monthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.27 | 0.00 | 21.27 | 0.00 | 21.27 |
February | 672.00 | 21.31 | 0.00 | 21.31 | 0.00 | 21.31 |
March | 744.00 | 21.44 | 0.00 | 21.44 | 0.00 | 21.44 |
April | 718.17 | 21.59 | 0.00 | 21.59 | 0.00 | 21.59 |
May | 721.83 | 21.69 | 0.67 | 21.69 | 0.67 | 21.69 |
June | 618.83 | 21.76 | 49.50 | 21.85 | 14.50 | 21.86 |
July | 607.67 | 21.80 | 224.67 | 22.01 | 172.67 | 22.09 |
August | 623.17 | 21.75 | 171.33 | 21.93 | 124.33 | 22.00 |
September | 671.00 | 21.66 | 48.83 | 21.71 | 39.17 | 21.73 |
October | 733.67 | 21.51 | 4.67 | 21.52 | 1.17 | 21.53 |
November | 720.00 | 21.37 | 0.00 | 21.37 | 0.00 | 21.37 |
December | 744.00 | 21.26 | 0.00 | 21.26 | 0.00 | 21.26 |
Annual Sum or Average | 8318.33 | 21.52 | 499.67 | 21.58 | 352.50 | 21.62 |
Minimum of Months | 607.67 | 21.26 | 0.00 | 21.26 | 0.00 | 21.26 |
Maximum of Months | 744.00 | 21.80 | 224.67 | 22.01 | 172.67 | 22.09 |
Report: ComfortReportSimple55Monthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 548.50 | 22.68 | 515.00 | 23.01 | 340.17 | 23.17 |
February | 520.17 | 22.78 | 470.67 | 23.10 | 337.67 | 23.26 |
March | 604.17 | 22.94 | 529.50 | 23.24 | 415.67 | 23.39 |
April | 614.67 | 23.09 | 522.17 | 23.39 | 442.50 | 23.53 |
May | 633.17 | 23.21 | 558.83 | 23.44 | 482.17 | 23.57 |
June | 590.33 | 23.46 | 576.50 | 23.56 | 499.67 | 23.66 |
July | 548.50 | 23.82 | 687.50 | 23.55 | 544.17 | 23.64 |
August | 551.00 | 23.78 | 666.33 | 23.56 | 537.83 | 23.65 |
September | 579.00 | 23.44 | 582.00 | 23.50 | 496.50 | 23.60 |
October | 605.00 | 23.12 | 548.17 | 23.35 | 449.00 | 23.49 |
November | 580.00 | 22.86 | 511.67 | 23.16 | 392.50 | 23.31 |
December | 537.83 | 22.64 | 509.67 | 22.99 | 327.00 | 23.15 |
Annual Sum or Average | 6912.33 | 23.16 | 6678.00 | 23.33 | 5264.83 | 23.47 |
Minimum of Months | 520.17 | 22.64 | 470.67 | 22.99 | 327.00 | 23.15 |
Maximum of Months | 633.17 | 23.82 | 687.50 | 23.56 | 544.17 | 23.66 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.00 | 427.50 | 21.00 | 427.50 | 21.00 |
February | 672.00 | 21.01 | 218.00 | 21.01 | 218.00 | 21.01 |
March | 744.00 | 21.02 | 137.17 | 21.02 | 137.17 | 21.01 |
April | 720.00 | 21.04 | 110.83 | 21.03 | 110.83 | 21.03 |
May | 744.00 | 21.06 | 40.00 | 21.06 | 40.00 | 21.05 |
June | 720.00 | 21.23 | 0.00 | 21.23 | 0.00 | 21.23 |
July | 744.00 | 21.34 | 0.00 | 21.34 | 0.00 | 21.34 |
August | 744.00 | 21.32 | 0.00 | 21.32 | 0.00 | 21.32 |
September | 720.00 | 21.18 | 0.00 | 21.18 | 0.00 | 21.18 |
October | 744.00 | 21.09 | 80.50 | 21.08 | 80.50 | 21.07 |
November | 720.00 | 21.01 | 199.50 | 21.01 | 199.50 | 21.01 |
December | 744.00 | 21.00 | 502.00 | 21.00 | 502.00 | 21.00 |
Annual Sum or Average | 8760.00 | 21.11 | 1715.50 | 21.09 | 1715.50 | 21.08 |
Minimum of Months | 672.00 | 21.00 | 0.00 | 21.00 | 0.00 | 21.00 |
Maximum of Months | 744.00 | 21.34 | 502.00 | 21.34 | 502.00 | 21.34 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT PEOPLE
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.08355 | 18.75637 | -0.4870 | 9.99944 |
February | 672.00000 | 21.04830 | 20.50243 | -0.4957 | 10.17241 |
March | 744.00000 | 21.02342 | 20.27998 | -0.5108 | 10.49218 |
April | 720.00000 | 21.00613 | 17.79226 | -0.5302 | 10.95119 |
May | 744.00000 | 21.00654 | 27.67019 | -1.6684 | 60.01989 |
June | 720.00000 | 21.01437 | 38.37949 | -1.5922 | 55.91128 |
July | 744.00000 | 21.03694 | 53.97172 | -1.4819 | 49.93207 |
August | 744.00000 | 21.07551 | 53.10282 | -1.4646 | 48.99889 |
September | 720.00000 | 21.16273 | 45.48831 | -1.4672 | 49.17408 |
October | 744.00000 | 21.23747 | 28.40587 | -0.3762 | 8.08950 |
November | 720.00000 | 21.23824 | 20.36261 | -0.4254 | 8.87196 |
December | 744.00000 | 21.17691 | 16.61587 | -0.4671 | 9.62377 |
Annual Sum or Average | 8760.00000 | 21.09273 | 30.18530 | -0.9163 | 27.79153 |
Minimum of Months | 672.00000 | 21.00613 | 16.61587 | -1.6684 | 8.08950 |
Maximum of Months | 744.00000 | 21.23824 | 53.97172 | -0.3762 | 60.01989 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_1_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.35709 | 17.97781 | -0.3967 | 10.38143 |
February | 672.00000 | 21.34214 | 19.70510 | -0.3700 | 9.67319 |
March | 744.00000 | 21.22134 | 19.58363 | -0.3917 | 9.30299 |
April | 720.00000 | 21.11038 | 17.17871 | -0.4014 | 8.93496 |
May | 744.00000 | 21.03282 | 27.12175 | -1.5093 | 51.47612 |
June | 720.00000 | 21.04526 | 37.82290 | -1.3856 | 44.91569 |
July | 744.00000 | 21.10501 | 53.32906 | -1.2296 | 37.02238 |
August | 744.00000 | 21.22657 | 52.18751 | -1.1795 | 35.09383 |
September | 720.00000 | 21.41278 | 44.39103 | -1.1720 | 36.12965 |
October | 744.00000 | 21.49716 | 27.51091 | -0.2051 | 8.10271 |
November | 720.00000 | 21.43729 | 19.71249 | -0.3178 | 9.17434 |
December | 744.00000 | 21.39016 | 15.92000 | -0.3953 | 10.43416 |
Annual Sum or Average | 8760.00000 | 21.26434 | 29.44506 | -0.7485 | 22.63482 |
Minimum of Months | 672.00000 | 21.03282 | 15.92000 | -1.5093 | 8.10271 |
Maximum of Months | 744.00000 | 21.49716 | 53.32906 | -0.2051 | 51.47612 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_2_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.01284 | 19.12435 | -0.4898 | 10.03429 |
February | 672.00000 | 21.02231 | 20.83908 | -0.4702 | 9.65254 |
March | 744.00000 | 21.03946 | 20.58636 | -0.4576 | 9.41559 |
April | 720.00000 | 21.07835 | 18.05691 | -0.4483 | 9.30187 |
May | 744.00000 | 21.10139 | 27.88112 | -1.5413 | 53.16228 |
June | 720.00000 | 21.18892 | 38.34587 | -1.4285 | 47.14108 |
July | 744.00000 | 21.21988 | 53.78325 | -1.3165 | 41.23599 |
August | 744.00000 | 21.22414 | 53.00653 | -1.3183 | 41.33069 |
September | 720.00000 | 21.16603 | 45.83265 | -1.3867 | 44.90029 |
October | 744.00000 | 21.10024 | 28.91712 | -0.3707 | 8.07475 |
November | 720.00000 | 21.03411 | 20.90807 | -0.4558 | 9.39159 |
December | 744.00000 | 21.01079 | 17.05527 | -0.5026 | 10.30773 |
Annual Sum or Average | 8760.00000 | 21.10032 | 30.43500 | -0.8511 | 24.58279 |
Minimum of Months | 672.00000 | 21.01079 | 17.05527 | -1.5413 | 8.07475 |
Maximum of Months | 744.00000 | 21.22414 | 53.78325 | -0.3707 | 53.16228 |
Report: OccupantComfortDataSummaryMonthly
For: LAUNDRY_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.43057 | 16.89870 | 0.17549 | 8.24691 |
February | 672.00000 | 21.43104 | 18.58606 | 0.19528 | 8.43375 |
March | 744.00000 | 21.43413 | 18.35075 | 0.21953 | 8.67221 |
April | 720.00000 | 21.40710 | 15.94120 | 0.22614 | 8.59430 |
May | 744.00000 | 21.39909 | 25.62877 | -0.5749 | 17.03934 |
June | 720.00000 | 21.38462 | 36.15081 | -0.4770 | 14.78474 |
July | 744.00000 | 21.36231 | 51.60083 | -0.3806 | 12.53822 |
August | 744.00000 | 21.38207 | 50.77519 | -0.3838 | 12.89241 |
September | 720.00000 | 21.39210 | 43.47962 | -0.4524 | 14.10410 |
October | 744.00000 | 21.41610 | 26.64729 | 0.28771 | 9.33814 |
November | 720.00000 | 21.43172 | 18.65849 | 0.20986 | 8.55692 |
December | 744.00000 | 21.42840 | 14.87242 | 0.16023 | 8.12564 |
Annual Sum or Average | 8760.00000 | 21.40813 | 28.20632 | -0.0677 | 10.95832 |
Minimum of Months | 672.00000 | 21.36231 | 14.87242 | -0.5749 | 8.12564 |
Maximum of Months | 744.00000 | 21.43413 | 51.60083 | 0.28771 | 17.03934 |
Report: OccupantComfortDataSummaryMonthly
For: CAFE_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.30944 | 20.42750 | -0.3017 | 8.61216 |
February | 672.00000 | 21.30136 | 22.14204 | -0.2759 | 8.04586 |
March | 744.00000 | 21.19896 | 21.99591 | -0.2983 | 7.70058 |
April | 720.00000 | 21.12409 | 19.55021 | -0.3082 | 7.39024 |
May | 744.00000 | 21.08192 | 29.43053 | -1.3796 | 44.57337 |
June | 720.00000 | 21.16281 | 39.93482 | -1.2445 | 37.68528 |
July | 744.00000 | 21.24169 | 55.23443 | -1.0844 | 30.00008 |
August | 744.00000 | 21.33979 | 54.19329 | -1.0385 | 28.21188 |
September | 720.00000 | 21.45574 | 46.68082 | -1.0453 | 29.47328 |
October | 744.00000 | 21.50929 | 29.86064 | -0.1098 | 6.86200 |
November | 720.00000 | 21.39522 | 22.14002 | -0.2255 | 7.67846 |
December | 744.00000 | 21.33888 | 18.36739 | -0.2997 | 8.66719 |
Annual Sum or Average | 8760.00000 | 21.28820 | 31.73686 | -0.6364 | 18.80972 |
Minimum of Months | 672.00000 | 21.08192 | 18.36739 | -1.3796 | 6.86200 |
Maximum of Months | 744.00000 | 21.50929 | 55.23443 | -0.1098 | 44.57337 |
Report: OccupantComfortDataSummaryMonthly
For: LOBBY_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.06134 | 20.44881 | -0.4288 | 8.89482 |
February | 672.00000 | 21.07853 | 22.14423 | -0.4075 | 8.52849 |
March | 744.00000 | 21.11002 | 21.87803 | -0.3952 | 8.32807 |
April | 720.00000 | 21.17630 | 19.34228 | -0.3833 | 8.19286 |
May | 744.00000 | 21.22115 | 29.07138 | -1.4493 | 48.23497 |
June | 720.00000 | 21.32087 | 39.42897 | -1.3304 | 42.04962 |
July | 744.00000 | 21.36757 | 54.67206 | -1.2081 | 35.85761 |
August | 744.00000 | 21.37678 | 53.90519 | -1.2061 | 35.74750 |
September | 720.00000 | 21.32835 | 46.79930 | -1.2697 | 38.87006 |
October | 744.00000 | 21.23931 | 30.05308 | -0.2889 | 7.00796 |
November | 720.00000 | 21.12112 | 22.17801 | -0.3842 | 8.17338 |
December | 744.00000 | 21.05913 | 18.38264 | -0.4396 | 9.09690 |
Annual Sum or Average | 8760.00000 | 21.20573 | 31.59792 | -0.7680 | 21.65912 |
Minimum of Months | 672.00000 | 21.05913 | 18.38264 | -1.4493 | 7.00796 |
Maximum of Months | 744.00000 | 21.37678 | 54.67206 | -0.2889 | 48.23497 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.30955 | 22.76649 | -0.4765 | 10.93353 |
February | 672.00000 | 21.41598 | 24.53921 | -0.4134 | 9.79950 |
March | 744.00000 | 21.50579 | 24.75635 | -0.3586 | 8.69615 |
April | 720.00000 | 21.63254 | 22.34355 | -0.2851 | 7.80340 |
May | 744.00000 | 21.64610 | 31.30073 | -1.3121 | 42.07504 |
June | 720.00000 | 21.70315 | 39.56115 | -1.1690 | 35.28625 |
July | 744.00000 | 21.73356 | 47.35992 | -1.0804 | 31.39113 |
August | 744.00000 | 21.72861 | 47.47607 | -1.0801 | 31.47288 |
September | 720.00000 | 21.70624 | 45.06222 | -1.1395 | 34.27974 |
October | 744.00000 | 21.61289 | 32.21227 | -0.2228 | 7.50115 |
November | 720.00000 | 21.50355 | 25.16584 | -0.3667 | 8.93878 |
December | 744.00000 | 21.30914 | 20.72380 | -0.4913 | 11.25178 |
Annual Sum or Average | 8760.00000 | 21.56774 | 31.98780 | -0.7015 | 20.01809 |
Minimum of Months | 672.00000 | 21.30914 | 20.72380 | -1.3121 | 7.50115 |
Maximum of Months | 744.00000 | 21.73356 | 47.47607 | -0.2228 | 42.07504 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.91076 | 23.20543 | -0.6294 | 13.83388 |
February | 672.00000 | 21.05987 | 24.94981 | -0.5530 | 12.12001 |
March | 744.00000 | 21.29655 | 25.00821 | -0.4466 | 9.76990 |
April | 720.00000 | 21.53920 | 22.45386 | -0.3312 | 8.17421 |
May | 744.00000 | 21.61860 | 31.32469 | -1.3334 | 43.02505 |
June | 720.00000 | 21.70254 | 39.54611 | -1.1689 | 35.22221 |
July | 744.00000 | 21.73348 | 47.49611 | -1.0868 | 31.58550 |
August | 744.00000 | 21.72050 | 48.00289 | -1.1039 | 32.32868 |
September | 720.00000 | 21.67245 | 45.84927 | -1.1969 | 36.55031 |
October | 744.00000 | 21.43425 | 32.68190 | -0.3166 | 8.22876 |
November | 720.00000 | 21.17733 | 25.54341 | -0.5062 | 10.93485 |
December | 744.00000 | 20.84306 | 21.17187 | -0.6655 | 14.83780 |
Annual Sum or Average | 8760.00000 | 21.39368 | 32.31780 | -0.7798 | 21.44577 |
Minimum of Months | 672.00000 | 20.84306 | 21.17187 | -1.3334 | 8.17421 |
Maximum of Months | 744.00000 | 21.73348 | 48.00289 | -0.3166 | 43.02505 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT19_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 0.00000 | ||||
Minimum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_4_MULT19_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.99135 | 21.13967 | -0.5806 | 12.13826 |
February | 672.00000 | 21.08297 | 22.95232 | -0.5355 | 11.12633 |
March | 744.00000 | 21.28217 | 23.06256 | -0.4565 | 9.44822 |
April | 720.00000 | 21.45102 | 20.70033 | -0.3999 | 8.64866 |
May | 744.00000 | 21.54690 | 29.30035 | -1.4386 | 47.90651 |
June | 720.00000 | 21.65793 | 37.93084 | -1.3074 | 41.30557 |
July | 744.00000 | 21.69777 | 47.84790 | -1.2223 | 37.25304 |
August | 744.00000 | 21.66312 | 48.11289 | -1.2470 | 38.36744 |
September | 720.00000 | 21.57819 | 44.27523 | -1.3312 | 42.44075 |
October | 744.00000 | 21.36196 | 30.87321 | -0.3718 | 8.28244 |
November | 720.00000 | 21.16538 | 23.59244 | -0.4992 | 10.31601 |
December | 744.00000 | 20.91960 | 19.07410 | -0.6163 | 13.11876 |
Annual Sum or Average | 8760.00000 | 21.36780 | 30.79277 | -0.8358 | 23.43787 |
Minimum of Months | 672.00000 | 20.91960 | 19.07410 | -1.4386 | 8.28244 |
Maximum of Months | 744.00000 | 21.69777 | 48.11289 | -0.3718 | 47.90651 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_5_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.35875 | 22.72029 | -0.4673 | 10.74961 |
February | 672.00000 | 21.47187 | 24.46902 | -0.4064 | 9.63525 |
March | 744.00000 | 21.59872 | 24.66043 | -0.3283 | 8.38734 |
April | 720.00000 | 21.72537 | 22.29557 | -0.2443 | 7.55579 |
May | 744.00000 | 21.72808 | 30.92771 | -1.2615 | 39.80379 |
June | 720.00000 | 21.74385 | 39.20828 | -1.1317 | 33.76446 |
July | 744.00000 | 21.75410 | 46.54251 | -1.0501 | 30.23447 |
August | 744.00000 | 21.75263 | 46.79950 | -1.0549 | 30.50335 |
September | 720.00000 | 21.73926 | 44.67479 | -1.1217 | 33.54546 |
October | 744.00000 | 21.66674 | 32.04772 | -0.2074 | 7.43158 |
November | 720.00000 | 21.56236 | 25.11951 | -0.3532 | 8.77436 |
December | 744.00000 | 21.36450 | 20.66412 | -0.4813 | 10.93746 |
Annual Sum or Average | 8760.00000 | 21.62265 | 31.72413 | -0.6775 | 19.33826 |
Minimum of Months | 672.00000 | 21.35875 | 20.66412 | -1.2615 | 7.43158 |
Maximum of Months | 744.00000 | 21.75410 | 46.79950 | -0.2074 | 39.80379 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_6_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.90471 | 23.16189 | -0.6316 | 13.68711 |
February | 672.00000 | 21.06790 | 24.87843 | -0.5565 | 11.96174 |
March | 744.00000 | 21.46523 | 24.78792 | -0.4007 | 9.05876 |
April | 720.00000 | 21.70526 | 22.31672 | -0.2754 | 7.73149 |
May | 744.00000 | 21.72321 | 30.93113 | -1.2765 | 40.42595 |
June | 720.00000 | 21.74382 | 39.23330 | -1.1319 | 33.72018 |
July | 744.00000 | 21.75395 | 46.69984 | -1.0565 | 30.42995 |
August | 744.00000 | 21.75076 | 47.22470 | -1.0768 | 31.27335 |
September | 720.00000 | 21.73111 | 45.31198 | -1.1712 | 35.44991 |
October | 744.00000 | 21.56754 | 32.29274 | -0.2854 | 7.90794 |
November | 720.00000 | 21.18094 | 25.49402 | -0.5033 | 10.71998 |
December | 744.00000 | 20.79749 | 21.13328 | -0.6754 | 14.91903 |
Annual Sum or Average | 8760.00000 | 21.45092 | 32.00124 | -0.7549 | 20.66395 |
Minimum of Months | 672.00000 | 20.79749 | 21.13328 | -1.2765 | 7.73149 |
Maximum of Months | 744.00000 | 21.75395 | 47.22470 | -0.2754 | 40.42595 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.24529 | 23.02722 | -0.5245 | 12.20429 |
February | 672.00000 | 21.36893 | 24.81256 | -0.4491 | 10.78968 |
March | 744.00000 | 21.48062 | 24.98088 | -0.3770 | 9.29059 |
April | 720.00000 | 21.63282 | 22.41497 | -0.2782 | 8.04787 |
May | 744.00000 | 21.65609 | 31.41958 | -1.2849 | 41.12032 |
June | 720.00000 | 21.71549 | 39.65336 | -1.1246 | 33.72207 |
July | 744.00000 | 21.74095 | 47.16032 | -1.0346 | 29.85490 |
August | 744.00000 | 21.73640 | 47.38692 | -1.0381 | 30.12150 |
September | 720.00000 | 21.70615 | 45.23987 | -1.1133 | 33.55048 |
October | 744.00000 | 21.59582 | 32.46456 | -0.2266 | 7.92931 |
November | 720.00000 | 21.46670 | 25.43351 | -0.3954 | 9.67952 |
December | 744.00000 | 21.23986 | 20.94448 | -0.5424 | 12.62970 |
Annual Sum or Average | 8760.00000 | 21.54934 | 32.12577 | -0.7008 | 19.97200 |
Minimum of Months | 672.00000 | 21.23986 | 20.94448 | -1.2849 | 7.92931 |
Maximum of Months | 744.00000 | 21.74095 | 47.38692 | -0.2266 | 41.12032 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.83293 | 23.48461 | -0.6851 | 15.46847 |
February | 672.00000 | 21.00665 | 25.23188 | -0.5950 | 13.33034 |
March | 744.00000 | 21.28066 | 25.22797 | -0.4665 | 10.38832 |
April | 720.00000 | 21.56532 | 22.49697 | -0.3205 | 8.34602 |
May | 744.00000 | 21.63966 | 31.42784 | -1.3035 | 41.90332 |
June | 720.00000 | 21.71690 | 39.63679 | -1.1240 | 33.62472 |
July | 744.00000 | 21.74157 | 47.27454 | -1.0409 | 30.01732 |
August | 744.00000 | 21.72911 | 47.85534 | -1.0622 | 30.91180 |
September | 720.00000 | 21.68276 | 46.00338 | -1.1689 | 35.63194 |
October | 744.00000 | 21.43744 | 32.91847 | -0.3202 | 8.63107 |
November | 720.00000 | 21.12356 | 25.83842 | -0.5451 | 11.95094 |
December | 744.00000 | 20.75956 | 21.40927 | -0.7252 | 16.64815 |
Annual Sum or Average | 8760.00000 | 21.37778 | 32.44739 | -0.7812 | 21.45994 |
Minimum of Months | 672.00000 | 20.75956 | 21.40927 | -1.3035 | 8.34602 |
Maximum of Months | 744.00000 | 21.74157 | 47.85534 | -0.3202 | 41.90332 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT9_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.53107 | 23.87374 | -0.3472 | 9.51340 |
February | 672.00000 | 21.59165 | 25.58671 | -0.3079 | 8.84767 |
March | 744.00000 | 21.60509 | 25.64533 | -0.3038 | 8.35904 |
April | 720.00000 | 21.66466 | 23.19917 | -0.2801 | 7.96431 |
May | 744.00000 | 21.66020 | 31.79115 | -1.3381 | 43.48370 |
June | 720.00000 | 21.70631 | 39.85114 | -1.2200 | 37.71647 |
July | 744.00000 | 21.73488 | 47.43321 | -1.1159 | 33.03009 |
August | 744.00000 | 21.73067 | 47.37108 | -1.1015 | 32.62171 |
September | 720.00000 | 21.72003 | 44.65614 | -1.1229 | 34.04698 |
October | 744.00000 | 21.67762 | 32.63395 | -0.1647 | 7.45744 |
November | 720.00000 | 21.64411 | 26.30004 | -0.2585 | 8.16893 |
December | 744.00000 | 21.53537 | 21.92484 | -0.3479 | 9.56522 |
Annual Sum or Average | 8760.00000 | 21.65025 | 32.56848 | -0.6613 | 20.13585 |
Minimum of Months | 672.00000 | 21.53107 | 21.92484 | -1.3381 | 7.45744 |
Maximum of Months | 744.00000 | 21.73488 | 47.43321 | -0.1647 | 43.48370 |
Report: OccupantComfortDataSummaryMonthly
For: BANQUET_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.23430 | 21.13019 | -0.3728 | 8.03202 |
February | 672.00000 | 21.27640 | 22.77485 | -0.3372 | 7.54747 |
March | 744.00000 | 21.38932 | 22.43451 | -0.2818 | 6.87582 |
April | 720.00000 | 21.52812 | 19.90408 | -0.2285 | 6.37746 |
May | 744.00000 | 21.65189 | 29.31950 | -1.1794 | 34.70954 |
June | 720.00000 | 21.83117 | 39.28051 | -1.0098 | 27.19081 |
July | 744.00000 | 21.87927 | 54.02675 | -0.8854 | 22.09285 |
August | 744.00000 | 21.83230 | 53.45133 | -0.9181 | 23.34729 |
September | 720.00000 | 21.67659 | 46.78746 | -1.0510 | 28.76507 |
October | 744.00000 | 21.48453 | 30.51176 | -0.1866 | 6.19759 |
November | 720.00000 | 21.32751 | 22.80112 | -0.3139 | 7.28817 |
December | 744.00000 | 21.22498 | 19.08760 | -0.3925 | 8.35969 |
Annual Sum or Average | 8760.00000 | 21.52941 | 31.86220 | -0.5980 | 15.61105 |
Minimum of Months | 672.00000 | 21.22498 | 19.08760 | -1.1794 | 6.19759 |
Maximum of Months | 744.00000 | 21.87927 | 54.02675 | -0.1866 | 34.70954 |
Report: OccupantComfortDataSummaryMonthly
For: DINING_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.26596 | 20.91133 | -0.3340 | 7.48268 |
February | 672.00000 | 21.31098 | 22.54995 | -0.2979 | 7.05203 |
March | 744.00000 | 21.43503 | 22.19917 | -0.2394 | 6.44252 |
April | 720.00000 | 21.59170 | 19.65906 | -0.1819 | 6.00289 |
May | 744.00000 | 21.72819 | 29.02031 | -1.1086 | 31.45722 |
June | 720.00000 | 21.91278 | 38.92501 | -0.9379 | 24.27560 |
July | 744.00000 | 21.95647 | 53.60835 | -0.8161 | 19.60628 |
August | 744.00000 | 21.90305 | 53.05455 | -0.8512 | 20.86025 |
September | 720.00000 | 21.74176 | 46.43270 | -0.9860 | 26.03347 |
October | 744.00000 | 21.53391 | 30.24555 | -0.1445 | 5.93185 |
November | 720.00000 | 21.36523 | 22.57072 | -0.2740 | 6.82579 |
December | 744.00000 | 21.25524 | 18.87335 | -0.3541 | 7.78577 |
Annual Sum or Average | 8760.00000 | 21.58484 | 31.57346 | -0.5453 | 14.18672 |
Minimum of Months | 672.00000 | 21.25524 | 18.87335 | -1.1086 | 5.93185 |
Maximum of Months | 744.00000 | 21.95647 | 53.60835 | -0.1445 | 31.45722 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.67614 | 21.26034 | 0.61496 | 18.33014 |
February | 672.00000 | 22.74768 | 22.70678 | 0.66153 | 19.78636 |
March | 744.00000 | 22.87136 | 22.34143 | 0.73149 | 21.97020 |
April | 720.00000 | 23.01470 | 19.90450 | 0.80735 | 24.84067 |
May | 744.00000 | 23.05697 | 28.48202 | 0.26469 | 18.56242 |
June | 720.00000 | 23.13817 | 37.73312 | 0.42054 | 20.53081 |
July | 744.00000 | 23.15095 | 51.31380 | 0.53821 | 22.48964 |
August | 744.00000 | 23.14050 | 50.62565 | 0.51612 | 22.14835 |
September | 720.00000 | 23.07754 | 44.25716 | 0.39894 | 20.26780 |
October | 744.00000 | 22.95399 | 29.58044 | 0.83815 | 25.65906 |
November | 720.00000 | 22.81013 | 22.72959 | 0.69550 | 20.62837 |
December | 744.00000 | 22.66422 | 19.40865 | 0.59627 | 17.77926 |
Annual Sum or Average | 8760.00000 | 22.94271 | 30.92576 | 0.58983 | 21.08811 |
Minimum of Months | 672.00000 | 22.66422 | 19.40865 | 0.26469 | 17.77926 |
Maximum of Months | 744.00000 | 23.15095 | 51.31380 | 0.83815 | 25.65906 |
Report: OccupantComfortDataSummaryMonthly
For: STORAGE_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.00017 | 17.74431 | -0.5826 | 12.12289 |
February | 672.00000 | 21.00017 | 19.47381 | -0.5654 | 11.71463 |
March | 744.00000 | 21.00014 | 19.25421 | -0.5496 | 11.34557 |
April | 720.00000 | 21.00016 | 16.77844 | -0.5452 | 11.28691 |
May | 744.00000 | 21.00200 | 26.65411 | -1.6692 | 60.06413 |
June | 720.00000 | 21.03994 | 37.26160 | -1.5652 | 54.44994 |
July | 744.00000 | 21.05317 | 52.97789 | -1.4576 | 48.61398 |
August | 744.00000 | 21.03341 | 52.25689 | -1.4745 | 49.52431 |
September | 720.00000 | 21.00410 | 44.88325 | -1.5445 | 53.34413 |
October | 744.00000 | 21.00041 | 27.74681 | -0.4794 | 9.94634 |
November | 720.00000 | 21.00017 | 19.56857 | -0.5529 | 11.43618 |
December | 744.00000 | 21.00018 | 15.67458 | -0.5967 | 12.48107 |
Annual Sum or Average | 8760.00000 | 21.01126 | 29.26464 | -0.9676 | 28.96047 |
Minimum of Months | 672.00000 | 21.00014 | 15.67458 | -1.6692 | 9.94634 |
Maximum of Months | 744.00000 | 21.05317 | 52.97789 | -0.4794 | 60.06413 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.00902 | 19.77787 | -0.5447 | 11.22245 |
February | 672.00000 | 21.02191 | 21.47818 | -0.5259 | 10.80463 |
March | 744.00000 | 21.03300 | 21.24061 | -0.5163 | 10.59234 |
April | 720.00000 | 21.12382 | 18.67726 | -0.5005 | 10.32269 |
May | 744.00000 | 21.21355 | 28.35634 | -1.5984 | 56.24098 |
June | 720.00000 | 21.59671 | 38.14257 | -1.4021 | 45.74750 |
July | 744.00000 | 21.88093 | 52.45387 | -1.2135 | 35.94368 |
August | 744.00000 | 21.89084 | 51.70739 | -1.2147 | 36.02484 |
September | 720.00000 | 21.65742 | 45.25378 | -1.3370 | 42.26299 |
October | 744.00000 | 21.34888 | 29.09319 | -0.3815 | 8.40008 |
November | 720.00000 | 21.03611 | 21.54710 | -0.5141 | 10.56493 |
December | 744.00000 | 21.00452 | 17.71042 | -0.5582 | 11.53911 |
Annual Sum or Average | 8760.00000 | 21.32010 | 30.52203 | -0.8608 | 24.21463 |
Minimum of Months | 672.00000 | 21.00452 | 17.71042 | -1.5984 | 8.40008 |
Maximum of Months | 744.00000 | 21.89084 | 52.45387 | -0.3815 | 56.24098 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.00159 | 18.29652 | -0.5631 | 11.69417 |
February | 672.00000 | 21.01283 | 20.01383 | -0.5362 | 11.08679 |
March | 744.00000 | 21.01812 | 19.77100 | -0.5154 | 10.61726 |
April | 720.00000 | 21.03632 | 17.25086 | -0.4963 | 10.28894 |
May | 744.00000 | 21.06046 | 27.08483 | -1.5923 | 55.91272 |
June | 720.00000 | 21.23387 | 37.43059 | -1.4356 | 47.54158 |
July | 744.00000 | 21.33819 | 52.64259 | -1.2909 | 39.95081 |
August | 744.00000 | 21.32063 | 51.91625 | -1.3058 | 40.75561 |
September | 720.00000 | 21.17743 | 44.94508 | -1.4189 | 46.68697 |
October | 744.00000 | 21.08505 | 28.10570 | -0.4190 | 8.97176 |
November | 720.00000 | 21.01110 | 20.09563 | -0.5219 | 10.76984 |
December | 744.00000 | 21.00099 | 16.22716 | -0.5769 | 12.03042 |
Annual Sum or Average | 8760.00000 | 21.10876 | 29.55457 | -0.8914 | 25.60812 |
Minimum of Months | 672.00000 | 21.00099 | 16.22716 | -1.5923 | 8.97176 |
Maximum of Months | 744.00000 | 21.33819 | 52.64259 | -0.4190 | 55.91272 |
Report: OccupantComfortDataSummaryMonthly
For: MECH_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.00010 | 17.54411 | -0.5614 | 11.61393 |
February | 672.00000 | 21.00011 | 19.27479 | -0.5450 | 11.24029 |
March | 744.00000 | 21.00011 | 19.05053 | -0.5300 | 10.90536 |
April | 720.00000 | 21.00924 | 16.55979 | -0.5245 | 10.82658 |
May | 744.00000 | 21.02768 | 26.41201 | -1.6345 | 58.19501 |
June | 720.00000 | 21.09665 | 36.94391 | -1.5224 | 52.14610 |
July | 744.00000 | 21.12355 | 52.55428 | -1.4119 | 46.18563 |
August | 744.00000 | 21.09604 | 51.86081 | -1.4310 | 47.20192 |
September | 720.00000 | 21.04301 | 44.57828 | -1.5071 | 51.32131 |
October | 744.00000 | 21.01168 | 27.51456 | -0.4586 | 9.54867 |
November | 720.00000 | 21.00010 | 19.36605 | -0.5336 | 10.99785 |
December | 744.00000 | 21.00013 | 15.47463 | -0.5751 | 11.95034 |
Annual Sum or Average | 8760.00000 | 21.03428 | 29.00239 | -0.9385 | 27.77290 |
Minimum of Months | 672.00000 | 21.00010 | 15.47463 | -1.6345 | 9.54867 |
Maximum of Months | 744.00000 | 21.12355 | 52.55428 | -0.4586 | 58.19501 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.186382E+11 | 67726.41 | 01-JAN-16:01 | 385.67 | 0.545104E+11 | 0.00 | 0.731487E+11 | 1.52 | 3.17 | 01-JAN-16:01 | 0.00 | 0.00 |
February | 0.238926E+11 | 127513.84 | 14-FEB-16:02 | 413.22 | 0.717155E+11 | 0.00 | 0.956080E+11 | 1.82 | 3.84 | 15-FEB-16:01 | 0.00 | 0.00 |
March | 0.481020E+11 | 131795.92 | 08-MAR-16:01 | 596.71 | 0.143297E+12 | 0.00 | 0.191399E+12 | 2.36 | 3.82 | 13-MAR-18:01 | 0.00 | 0.00 |
April | 0.104565E+12 | 151463.74 | 13-APR-15:03 | 699.12 | 0.327991E+12 | 0.00 | 0.432556E+12 | 2.93 | 3.88 | 10-APR-18:01 | 0.00 | 0.00 |
May | 0.164240E+12 | 183024.60 | 19-MAY-15:03 | 743.21 | 0.516549E+12 | 0.00 | 0.680788E+12 | 3.04 | 3.85 | 25-MAY-18:02 | 0.00 | 0.00 |
June | 0.261335E+12 | 273073.22 | 28-JUN-15:03 | 720.00 | 0.802091E+12 | 0.00 | 0.106343E+13 | 3.06 | 3.79 | 20-JUN-08:61 | 0.00 | 0.00 |
July | 0.341999E+12 | 266059.35 | 21-JUL-15:03 | 744.00 | 0.109604E+13 | 0.00 | 0.143804E+13 | 3.24 | 4.22 | 01-JUL-08:61 | 0.00 | 0.00 |
August | 0.307550E+12 | 229543.64 | 20-AUG-18:03 | 744.00 | 0.992139E+12 | 0.00 | 0.129969E+13 | 3.23 | 4.09 | 26-AUG-08:61 | 0.00 | 0.00 |
September | 0.217877E+12 | 199128.83 | 20-SEP-15:02 | 720.00 | 0.698522E+12 | 0.00 | 0.916399E+12 | 3.13 | 3.94 | 06-SEP-08:62 | 0.00 | 0.00 |
October | 0.117281E+12 | 178567.38 | 01-OCT-15:03 | 689.97 | 0.370659E+12 | 0.00 | 0.487940E+12 | 2.81 | 4.02 | 02-OCT-18:01 | 0.00 | 0.00 |
November | 0.333633E+11 | 93521.11 | 02-NOV-15:01 | 559.39 | 0.973936E+11 | 0.00 | 0.130757E+12 | 2.28 | 3.79 | 02-NOV-15:01 | 0.00 | 0.00 |
December | 0.178013E+11 | 49154.17 | 31-DEC-16:03 | 402.76 | 0.524682E+11 | 0.00 | 0.702695E+11 | 1.60 | 2.95 | 01-DEC-00:20 | 0.00 | 0.00 |
Annual Sum or Average | 0.165665E+13 | 7418.05 | 0.522337E+13 | 0.00 | 0.688002E+13 | 2.59 | 0.00 | 0.00 | ||||
Minimum of Months | 0.178013E+11 | 49154.17 | 385.67 | 0.524682E+11 | 0.00 | 0.702695E+11 | 1.52 | 2.95 | 0.00 | 0.00 | ||
Maximum of Months | 0.341999E+12 | 273073.22 | 744.00 | 0.109604E+13 | 0.00 | 0.143804E+13 | 3.24 | 4.22 | 0.00 | 0.00 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.151104E+12 | 0.00 | 744.00 | 183808.96 | 21-JAN-07:10 | 0.00 | 35.48 | 60.00 | 0.57 | 0.00 | 0.11 | 0.37 | 21-JAN-07:10 |
February | 0.119347E+12 | 0.00 | 672.00 | 172682.67 | 05-FEB-09:02 | 0.00 | 34.94 | 60.00 | 0.49 | 0.00 | 0.10 | 0.35 | 05-FEB-09:02 |
March | 0.986638E+11 | 0.00 | 744.00 | 109002.62 | 22-MAR-08:62 | 0.00 | 33.77 | 60.00 | 0.35 | 0.00 | 0.07 | 0.22 | 22-MAR-08:62 |
April | 0.679372E+11 | 0.00 | 719.67 | 94462.42 | 10-APR-08:03 | 0.00 | 31.90 | 59.99 | 0.24 | 0.00 | 0.05 | 0.19 | 10-APR-08:03 |
May | 0.577700E+11 | 0.00 | 743.67 | 89815.36 | 05-MAY-10:40 | 0.00 | 31.20 | 59.99 | 0.19 | 0.00 | 0.04 | 0.18 | 05-MAY-10:40 |
June | 0.427530E+11 | 0.00 | 696.17 | 79518.19 | 09-JUN-10:40 | 0.00 | 31.48 | 59.05 | 0.15 | 0.00 | 0.03 | 0.16 | 09-JUN-10:40 |
July | 0.357454E+11 | 0.00 | 697.61 | 64753.56 | 10-JUL-08:04 | 0.00 | 31.50 | 58.12 | 0.12 | 0.00 | 0.03 | 0.13 | 10-JUL-08:04 |
August | 0.321068E+11 | 0.00 | 684.89 | 67562.24 | 29-AUG-10:35 | 0.00 | 31.25 | 57.59 | 0.11 | 0.00 | 0.02 | 0.14 | 29-AUG-10:35 |
September | 0.296304E+11 | 0.00 | 691.22 | 66353.14 | 05-SEP-10:35 | 0.00 | 30.05 | 58.79 | 0.10 | 0.00 | 0.02 | 0.13 | 05-SEP-10:35 |
October | 0.557339E+11 | 0.00 | 738.42 | 143611.05 | 25-OCT-08:62 | 0.00 | 31.06 | 59.78 | 0.19 | 0.00 | 0.04 | 0.29 | 25-OCT-08:62 |
November | 0.915331E+11 | 0.00 | 720.00 | 119699.91 | 04-NOV-15:02 | 0.00 | 33.72 | 60.00 | 0.34 | 0.00 | 0.07 | 0.24 | 04-NOV-15:02 |
December | 0.151267E+12 | 0.00 | 744.00 | 172480.00 | 15-DEC-07:10 | 0.00 | 35.69 | 60.00 | 0.57 | 0.00 | 0.11 | 0.35 | 15-DEC-07:10 |
Annual Sum or Average | 0.933591E+12 | 0.00 | 8595.64 | 0.00 | 32.66 | 59.44 | 0.28 | 0.00 | 0.06 | ||||
Minimum of Months | 0.296304E+11 | 0.00 | 672.00 | 64753.56 | 0.00 | 30.05 | 57.59 | 0.10 | 0.00 | 0.02 | 0.13 | ||
Maximum of Months | 0.151267E+12 | 0.00 | 744.00 | 183808.96 | 0.00 | 35.69 | 60.00 | 0.57 | 0.00 | 0.11 | 0.37 |
Report: DXReportMonthly
For: VAV WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.399918E+10 | 0.00 | 59.51 | 0.399918E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 72847.89 | 05-JAN-14:10 | 72847.89 | 05-JAN-14:10 | 0.00 | 0.00 | 0.00 |
February | 0.149680E+11 | 0.00 | 77.95 | 0.149680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 231277.92 | 14-FEB-16:30 | 231277.92 | 14-FEB-16:30 | 0.00 | 0.00 | 0.00 |
March | 0.601961E+11 | 0.00 | 211.32 | 0.601961E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 238364.97 | 08-MAR-16:30 | 238364.97 | 08-MAR-16:30 | 0.00 | 0.00 | 0.00 |
April | 0.194567E+12 | 0.00 | 391.67 | 0.194567E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 289922.73 | 13-APR-17:13 | 289922.73 | 13-APR-17:13 | 0.00 | 0.00 | 0.00 |
May | 0.342353E+12 | 0.00 | 567.44 | 0.342195E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 330163.97 | 19-MAY-17:12 | 330163.97 | 19-MAY-17:12 | 0.00 | 0.00 | 0.00 |
June | 0.549914E+12 | 0.00 | 680.50 | 0.549446E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 407683.28 | 28-JUN-16:20 | 407683.28 | 28-JUN-16:20 | 0.00 | 0.00 | 0.00 |
July | 0.765277E+12 | 0.00 | 744.00 | 0.696813E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 540015.58 | 31-JUL-18:03 | 405435.68 | 21-JUL-17:13 | 0.00 | 0.00 | 0.00 |
August | 0.680082E+12 | 0.00 | 743.33 | 0.639037E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 465428.96 | 26-AUG-10:35 | 381917.14 | 04-AUG-17:04 | 0.00 | 0.00 | 0.00 |
September | 0.456565E+12 | 0.00 | 685.83 | 0.449369E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 434399.55 | 05-SEP-10:50 | 344963.33 | 03-SEP-10:35 | 0.00 | 0.00 | 0.00 |
October | 0.205680E+12 | 0.00 | 418.21 | 0.204897E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 340764.79 | 11-OCT-10:40 | 304535.55 | 01-OCT-16:00 | 0.00 | 0.00 | 0.00 |
November | 0.115932E+11 | 0.00 | 108.44 | 0.115932E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 161028.29 | 09-NOV-14:00 | 161028.29 | 09-NOV-14:00 | 0.00 | 0.00 | 0.00 |
December | 102015.20 | 0.00 | 30.33 | 102015.20 | 0.00 | 0.00 | 0.00 | 0.00 | 2.26 | 01-DEC-19:06 | 2.26 | 01-DEC-19:06 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.328520E+13 | 0.00 | 4718.54 | 0.316708E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 102015.20 | 0.00 | 30.33 | 102015.20 | 0.00 | 0.00 | 0.00 | 0.00 | 2.26 | 2.26 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.765277E+12 | 0.00 | 744.00 | 0.696813E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 540015.58 | 407683.28 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: FLR_3_DOAS COOLING COIL
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.119132E+09 | 0.00 | 16.67 | 0.119132E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4033.62 | 05-JAN-14:00 | 4033.62 | 05-JAN-14:00 | 0.00 | 0.00 | 0.00 |
February | 0.100794E+10 | 0.00 | 33.50 | 0.100794E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21463.19 | 14-FEB-16:00 | 21463.19 | 14-FEB-16:00 | 0.00 | 0.00 | 0.00 |
March | 0.394114E+10 | 0.00 | 136.67 | 0.394114E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22751.51 | 08-MAR-14:00 | 22751.51 | 08-MAR-14:00 | 0.00 | 0.00 | 0.00 |
April | 0.157164E+11 | 0.00 | 322.17 | 0.157164E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 29499.20 | 13-APR-17:00 | 29499.20 | 13-APR-17:00 | 0.00 | 0.00 | 0.00 |
May | 0.310275E+11 | 0.00 | 507.00 | 0.310263E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 37738.79 | 22-MAY-13:00 | 37738.79 | 22-MAY-13:00 | 0.00 | 0.00 | 0.00 |
June | 0.581003E+11 | 0.00 | 649.83 | 0.578737E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 54641.56 | 28-JUN-16:00 | 54641.56 | 28-JUN-16:00 | 0.00 | 0.00 | 0.00 |
July | 0.847239E+11 | 0.00 | 744.00 | 0.740760E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 53799.62 | 22-JUL-15:00 | 53799.62 | 22-JUL-15:00 | 0.00 | 0.00 | 0.00 |
August | 0.717942E+11 | 0.00 | 742.50 | 0.652323E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 48044.34 | 01-AUG-16:00 | 48044.34 | 01-AUG-16:00 | 0.00 | 0.00 | 0.00 |
September | 0.429417E+11 | 0.00 | 657.83 | 0.417535E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 41176.38 | 05-SEP-13:00 | 40064.81 | 02-SEP-16:20 | 0.00 | 0.00 | 0.00 |
October | 0.170638E+11 | 0.00 | 350.00 | 0.169269E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 35370.21 | 01-OCT-16:00 | 35370.21 | 01-OCT-16:00 | 0.00 | 0.00 | 0.00 |
November | 0.449857E+09 | 0.00 | 40.83 | 0.449857E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14180.63 | 09-NOV-14:00 | 14180.63 | 09-NOV-14:00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.326886E+12 | 0.00 | 4201.00 | 0.308123E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.847239E+11 | 0.00 | 744.00 | 0.740760E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 54641.56 | 54641.56 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.134641E+10 | 0.00 | 182.04 | 0.134641E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22534.52 | 20-JAN-16:01 | 22534.52 | 20-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.197603E+10 | 0.00 | 226.12 | 0.197603E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22533.56 | 17-FEB-16:01 | 22533.56 | 17-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.309331E+10 | 0.00 | 348.67 | 0.308900E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22547.21 | 20-MAR-15:01 | 22547.21 | 20-MAR-15:01 | 0.00 | 0.00 | 0.00 |
April | 0.556398E+10 | 0.00 | 550.39 | 0.553261E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22548.61 | 19-APR-18:01 | 22548.61 | 19-APR-18:01 | 0.00 | 0.00 | 0.00 |
May | 0.683807E+10 | 0.00 | 620.42 | 0.598752E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22573.36 | 26-MAY-15:01 | 22573.36 | 26-MAY-15:01 | 0.00 | 0.00 | 0.00 |
June | 0.998814E+10 | 0.00 | 660.74 | 0.770345E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22578.85 | 25-JUN-18:02 | 22578.85 | 25-JUN-18:02 | 0.00 | 0.00 | 0.00 |
July | 0.124646E+11 | 0.00 | 708.72 | 0.758421E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24606.55 | 01-JUL-08:61 | 22568.25 | 21-JUL-15:02 | 0.00 | 0.00 | 0.00 |
August | 0.123694E+11 | 0.00 | 706.36 | 0.740996E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24178.43 | 26-AUG-08:61 | 22579.28 | 20-AUG-18:01 | 0.00 | 0.00 | 0.00 |
September | 0.971822E+10 | 0.00 | 670.56 | 0.622197E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22577.59 | 25-SEP-18:01 | 22577.59 | 25-SEP-18:01 | 0.00 | 0.00 | 0.00 |
October | 0.650168E+10 | 0.00 | 562.21 | 0.534551E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22579.94 | 09-OCT-18:01 | 22579.94 | 09-OCT-18:01 | 0.00 | 0.00 | 0.00 |
November | 0.251865E+10 | 0.00 | 332.99 | 0.246902E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22574.18 | 02-NOV-15:01 | 22574.18 | 02-NOV-15:01 | 0.00 | 0.00 | 0.00 |
December | 0.110500E+10 | 0.00 | 183.33 | 0.110500E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22529.02 | 26-DEC-16:01 | 22529.02 | 26-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.734836E+11 | 0.00 | 5752.55 | 0.557707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.110500E+10 | 0.00 | 182.04 | 0.110500E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22529.02 | 22529.02 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.124646E+11 | 0.00 | 708.72 | 0.770345E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24606.55 | 22579.94 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.236786E+09 | 0.00 | 37.74 | 0.236786E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 22279.46 | 05-JAN-16:01 | 22279.46 | 05-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.652324E+09 | 0.00 | 92.15 | 0.652324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 22282.16 | 17-FEB-16:01 | 22282.16 | 17-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.162033E+10 | 0.00 | 225.65 | 0.161721E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22287.11 | 16-MAR-15:01 | 22287.11 | 16-MAR-15:01 | 0.00 | 0.00 | 0.00 |
April | 0.435538E+10 | 0.00 | 477.41 | 0.432706E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22298.28 | 19-APR-18:01 | 22298.28 | 19-APR-18:01 | 0.00 | 0.00 | 0.00 |
May | 0.634659E+10 | 0.00 | 596.14 | 0.553461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22328.62 | 27-MAY-18:01 | 22328.62 | 27-MAY-18:01 | 0.00 | 0.00 | 0.00 |
June | 0.999982E+10 | 0.00 | 657.16 | 0.774261E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22328.09 | 25-JUN-18:02 | 22328.09 | 25-JUN-18:02 | 0.00 | 0.00 | 0.00 |
July | 0.121238E+11 | 0.00 | 708.13 | 0.734793E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24245.63 | 01-JUL-08:61 | 22318.06 | 21-JUL-15:02 | 0.00 | 0.00 | 0.00 |
August | 0.112175E+11 | 0.00 | 699.87 | 0.647716E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23945.79 | 26-AUG-08:61 | 20340.75 | 10-AUG-08:61 | 0.00 | 0.00 | 0.00 |
September | 0.752828E+10 | 0.00 | 642.90 | 0.444663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22328.35 | 25-SEP-18:01 | 22328.35 | 25-SEP-18:01 | 0.00 | 0.00 | 0.00 |
October | 0.380258E+10 | 0.00 | 427.35 | 0.292403E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22323.58 | 11-OCT-18:01 | 22323.58 | 11-OCT-18:01 | 0.00 | 0.00 | 0.00 |
November | 0.610709E+09 | 0.00 | 133.84 | 0.601231E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 22322.80 | 02-NOV-15:01 | 22322.80 | 02-NOV-15:01 | 0.00 | 0.00 | 0.00 |
December | 0.133833E+09 | 0.00 | 25.65 | 0.133833E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 22266.02 | 29-DEC-16:01 | 22266.02 | 29-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.586280E+11 | 0.00 | 4724.01 | 0.420414E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.133833E+09 | 0.00 | 25.65 | 0.133833E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 22266.02 | 20340.75 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.121238E+11 | 0.00 | 708.13 | 0.774261E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24245.63 | 22328.62 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.306635E+11 | 0.00 | 316.28 | 0.306635E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 69442.09 | 01-JAN-13:50 | 69442.09 | 01-JAN-13:50 | 0.00 | 0.00 | 0.00 |
February | 0.298918E+11 | 0.00 | 334.04 | 0.298918E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 69377.62 | 14-FEB-13:00 | 69377.62 | 14-FEB-13:00 | 0.00 | 0.00 | 0.00 |
March | 0.314322E+11 | 0.00 | 441.78 | 0.314322E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 58775.28 | 08-MAR-13:30 | 58775.28 | 08-MAR-13:30 | 0.00 | 0.00 | 0.00 |
April | 0.337194E+11 | 0.00 | 552.97 | 0.337194E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 43493.53 | 13-APR-13:20 | 43493.53 | 13-APR-13:20 | 0.00 | 0.00 | 0.00 |
May | 0.315319E+11 | 0.00 | 607.61 | 0.287188E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 31905.39 | 13-MAY-13:10 | 31905.39 | 13-MAY-13:10 | 0.00 | 0.00 | 0.00 |
June | 0.412337E+11 | 0.00 | 665.89 | 0.334316E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 35933.54 | 28-JUN-18:15 | 35933.54 | 28-JUN-18:15 | 0.00 | 0.00 | 0.00 |
July | 0.588900E+11 | 0.00 | 737.42 | 0.331885E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 43247.56 | 23-JUL-13:40 | 39386.27 | 23-JUL-13:50 | 0.00 | 0.00 | 0.00 |
August | 0.644360E+11 | 0.00 | 736.75 | 0.405323E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 53275.05 | 20-AUG-13:50 | 48006.00 | 18-AUG-12:50 | 0.00 | 0.00 | 0.00 |
September | 0.652363E+11 | 0.00 | 707.00 | 0.491290E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 68330.53 | 28-SEP-13:20 | 63272.02 | 28-SEP-13:20 | 0.00 | 0.00 | 0.00 |
October | 0.626344E+11 | 0.00 | 623.16 | 0.582839E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 69835.86 | 19-OCT-12:30 | 69835.86 | 19-OCT-12:30 | 0.00 | 0.00 | 0.00 |
November | 0.477806E+11 | 0.00 | 467.51 | 0.477806E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 70614.50 | 20-NOV-12:10 | 70614.50 | 20-NOV-12:10 | 0.00 | 0.00 | 0.00 |
December | 0.328700E+11 | 0.00 | 340.95 | 0.328700E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 70381.29 | 31-DEC-13:40 | 70381.29 | 31-DEC-13:40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.530320E+12 | 0.00 | 6531.36 | 0.449642E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.298918E+11 | 0.00 | 316.28 | 0.287188E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 31905.39 | 31905.39 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.652363E+11 | 0.00 | 737.42 | 0.582839E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 70614.50 | 70614.50 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.134853E+10 | 0.00 | 79.15 | 0.134853E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 77786.84 | 05-JAN-19:01 | 77786.84 | 05-JAN-19:01 | 0.00 | 0.00 | 0.00 |
February | 0.476566E+10 | 0.00 | 159.57 | 0.476566E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 115234.52 | 15-FEB-19:01 | 115234.52 | 15-FEB-19:01 | 0.00 | 0.00 | 0.00 |
March | 0.166612E+11 | 0.00 | 383.67 | 0.164916E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 118080.37 | 27-MAR-15:01 | 118080.37 | 27-MAR-15:01 | 0.00 | 0.00 | 0.00 |
April | 0.347254E+11 | 0.00 | 493.27 | 0.344872E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 123169.20 | 14-APR-15:01 | 123169.20 | 14-APR-15:01 | 0.00 | 0.00 | 0.00 |
May | 0.515688E+11 | 0.00 | 551.10 | 0.456326E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 123447.91 | 29-MAY-15:01 | 123447.91 | 29-MAY-15:01 | 0.00 | 0.00 | 0.00 |
June | 0.719567E+11 | 0.00 | 601.48 | 0.597105E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 123456.33 | 15-JUN-15:02 | 123456.33 | 15-JUN-15:02 | 0.00 | 0.00 | 0.00 |
July | 0.879829E+11 | 0.00 | 656.58 | 0.594544E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 132441.68 | 01-JUL-08:61 | 123402.81 | 03-JUL-15:01 | 0.00 | 0.00 | 0.00 |
August | 0.789202E+11 | 0.00 | 623.11 | 0.512828E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 129765.19 | 26-AUG-08:61 | 123443.07 | 16-AUG-18:01 | 0.00 | 0.00 | 0.00 |
September | 0.561629E+11 | 0.00 | 539.37 | 0.383703E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 123385.70 | 30-SEP-15:01 | 123385.70 | 30-SEP-15:01 | 0.00 | 0.00 | 0.00 |
October | 0.303493E+11 | 0.00 | 470.06 | 0.249738E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 123396.25 | 01-OCT-15:01 | 123396.25 | 01-OCT-15:01 | 0.00 | 0.00 | 0.00 |
November | 0.904546E+10 | 0.00 | 278.43 | 0.869677E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 117410.59 | 09-NOV-19:03 | 117410.59 | 09-NOV-19:03 | 0.00 | 0.00 | 0.00 |
December | 0.106766E+10 | 0.00 | 64.58 | 0.106766E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 89005.32 | 01-DEC-19:02 | 89005.32 | 01-DEC-19:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.444555E+12 | 0.00 | 4900.36 | 0.346282E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.106766E+10 | 0.00 | 64.58 | 0.106766E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 77786.84 | 77786.84 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.879829E+11 | 0.00 | 656.58 | 0.597105E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 132441.68 | 123456.33 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_5_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.129058E+10 | 0.00 | 192.49 | 0.129058E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19889.27 | 03-JAN-09:01 | 19889.27 | 03-JAN-09:01 | 0.00 | 0.00 | 0.00 |
February | 0.171026E+10 | 0.00 | 229.17 | 0.171026E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19902.94 | 19-FEB-09:01 | 19902.94 | 19-FEB-09:01 | 0.00 | 0.00 | 0.00 |
March | 0.336828E+10 | 0.00 | 392.61 | 0.336416E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19921.81 | 29-MAR-08:61 | 19921.81 | 29-MAR-08:61 | 0.00 | 0.00 | 0.00 |
April | 0.640032E+10 | 0.00 | 600.79 | 0.636344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19921.99 | 22-APR-08:62 | 19921.99 | 22-APR-08:62 | 0.00 | 0.00 | 0.00 |
May | 0.771519E+10 | 0.00 | 673.28 | 0.665267E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19924.80 | 27-MAY-18:01 | 19924.80 | 27-MAY-18:01 | 0.00 | 0.00 | 0.00 |
June | 0.109570E+11 | 0.00 | 695.62 | 0.865332E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19923.37 | 25-JUN-18:02 | 19923.37 | 25-JUN-18:02 | 0.00 | 0.00 | 0.00 |
July | 0.137671E+11 | 0.00 | 731.86 | 0.888212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21458.71 | 01-JUL-08:61 | 19922.83 | 03-JUL-15:01 | 0.00 | 0.00 | 0.00 |
August | 0.133051E+11 | 0.00 | 729.85 | 0.838748E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19923.05 | 20-AUG-18:01 | 19923.05 | 20-AUG-18:01 | 0.00 | 0.00 | 0.00 |
September | 0.100242E+11 | 0.00 | 693.79 | 0.661327E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20357.12 | 06-SEP-08:62 | 19922.07 | 21-SEP-18:01 | 0.00 | 0.00 | 0.00 |
October | 0.656249E+10 | 0.00 | 585.59 | 0.540305E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19922.03 | 01-OCT-15:01 | 19922.03 | 01-OCT-15:01 | 0.00 | 0.00 | 0.00 |
November | 0.252337E+10 | 0.00 | 351.02 | 0.246576E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19920.03 | 02-NOV-15:01 | 19920.03 | 02-NOV-15:01 | 0.00 | 0.00 | 0.00 |
December | 0.103711E+10 | 0.00 | 162.93 | 0.103711E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19889.31 | 29-DEC-09:01 | 19889.31 | 29-DEC-09:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.786611E+11 | 0.00 | 6039.01 | 0.608232E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.103711E+10 | 0.00 | 162.93 | 0.103711E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19889.27 | 19889.27 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.137671E+11 | 0.00 | 731.86 | 0.888212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21458.71 | 19924.80 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_6_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.200567E+09 | 0.00 | 37.88 | 0.200567E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17116.95 | 01-JAN-09:01 | 17116.95 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 |
February | 0.426518E+09 | 0.00 | 80.56 | 0.426518E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19729.32 | 19-FEB-09:01 | 19729.32 | 19-FEB-09:01 | 0.00 | 0.00 | 0.00 |
March | 0.166932E+10 | 0.00 | 263.46 | 0.166627E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19747.05 | 29-MAR-08:61 | 19747.05 | 29-MAR-08:61 | 0.00 | 0.00 | 0.00 |
April | 0.505881E+10 | 0.00 | 552.33 | 0.502321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19747.45 | 22-APR-08:62 | 19747.45 | 22-APR-08:62 | 0.00 | 0.00 | 0.00 |
May | 0.718195E+10 | 0.00 | 662.22 | 0.615755E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19750.26 | 27-MAY-18:01 | 19750.26 | 27-MAY-18:01 | 0.00 | 0.00 | 0.00 |
June | 0.109567E+11 | 0.00 | 694.80 | 0.868480E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19748.52 | 25-JUN-18:02 | 19748.52 | 25-JUN-18:02 | 0.00 | 0.00 | 0.00 |
July | 0.134128E+11 | 0.00 | 731.38 | 0.858891E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21174.81 | 01-JUL-08:61 | 19748.37 | 03-JUL-15:01 | 0.00 | 0.00 | 0.00 |
August | 0.121387E+11 | 0.00 | 727.94 | 0.733246E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19750.04 | 20-AUG-18:01 | 19750.04 | 20-AUG-18:01 | 0.00 | 0.00 | 0.00 |
September | 0.777069E+10 | 0.00 | 685.23 | 0.468146E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20196.22 | 06-SEP-08:62 | 19747.50 | 21-SEP-18:01 | 0.00 | 0.00 | 0.00 |
October | 0.368095E+10 | 0.00 | 464.49 | 0.273694E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19749.25 | 01-OCT-15:01 | 19749.25 | 01-OCT-15:01 | 0.00 | 0.00 | 0.00 |
November | 0.604338E+09 | 0.00 | 131.21 | 0.578474E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19724.05 | 12-NOV-09:01 | 19724.05 | 12-NOV-09:01 | 0.00 | 0.00 | 0.00 |
December | 0.105666E+09 | 0.00 | 29.67 | 0.105666E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17652.94 | 30-DEC-09:01 | 17652.94 | 30-DEC-09:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.632071E+11 | 0.00 | 5061.18 | 0.461828E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.105666E+09 | 0.00 | 29.67 | 0.105666E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17116.95 | 17116.95 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.134128E+11 | 0.00 | 731.38 | 0.868480E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21174.81 | 19750.26 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.343709E+09 | 0.00 | 146.21 | 0.343709E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6082.39 | 20-JAN-16:01 | 6082.39 | 20-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.525916E+09 | 0.00 | 199.00 | 0.525916E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6082.28 | 17-FEB-16:01 | 6082.28 | 17-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.839811E+09 | 0.00 | 318.36 | 0.839694E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6086.00 | 20-MAR-15:01 | 6086.00 | 20-MAR-15:01 | 0.00 | 0.00 | 0.00 |
April | 0.158550E+10 | 0.00 | 530.56 | 0.157814E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6086.17 | 19-APR-18:01 | 6086.17 | 19-APR-18:01 | 0.00 | 0.00 | 0.00 |
May | 0.199825E+10 | 0.00 | 618.42 | 0.176452E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6092.86 | 26-MAY-15:01 | 6092.86 | 26-MAY-15:01 | 0.00 | 0.00 | 0.00 |
June | 0.293646E+10 | 0.00 | 669.16 | 0.231021E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6094.46 | 17-JUN-08:61 | 6094.46 | 17-JUN-08:61 | 0.00 | 0.00 | 0.00 |
July | 0.364319E+10 | 0.00 | 716.18 | 0.233453E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6772.17 | 01-JUL-08:61 | 6092.09 | 20-JUL-15:02 | 0.00 | 0.00 | 0.00 |
August | 0.357284E+10 | 0.00 | 711.95 | 0.226318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6665.17 | 26-AUG-08:61 | 5483.28 | 18-AUG-08:61 | 0.00 | 0.00 | 0.00 |
September | 0.273784E+10 | 0.00 | 669.49 | 0.183473E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6093.97 | 25-SEP-18:01 | 6093.97 | 25-SEP-18:01 | 0.00 | 0.00 | 0.00 |
October | 0.176352E+10 | 0.00 | 528.25 | 0.146911E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6094.68 | 09-OCT-18:01 | 6094.68 | 09-OCT-18:01 | 0.00 | 0.00 | 0.00 |
November | 0.634505E+09 | 0.00 | 290.39 | 0.623266E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6093.44 | 02-NOV-15:01 | 6093.44 | 02-NOV-15:01 | 0.00 | 0.00 | 0.00 |
December | 0.275016E+09 | 0.00 | 140.51 | 0.275016E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6081.06 | 26-DEC-16:01 | 6081.06 | 26-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.208566E+11 | 0.00 | 5538.48 | 0.161620E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.275016E+09 | 0.00 | 140.51 | 0.275016E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6081.06 | 5483.28 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.364319E+10 | 0.00 | 716.18 | 0.233453E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6772.17 | 6094.68 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 61469492.76 | 0.00 | 34.30 | 61469492.76 | 0.00 | 0.00 | 0.00 | 0.00 | 6002.35 | 05-JAN-16:01 | 6002.35 | 05-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.174969E+09 | 0.00 | 82.36 | 0.174969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6003.00 | 17-FEB-16:01 | 6003.00 | 17-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.444405E+09 | 0.00 | 198.65 | 0.444385E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6004.50 | 16-MAR-15:01 | 6004.50 | 16-MAR-15:01 | 0.00 | 0.00 | 0.00 |
April | 0.125324E+10 | 0.00 | 470.00 | 0.124666E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6007.29 | 19-APR-18:01 | 6007.29 | 19-APR-18:01 | 0.00 | 0.00 | 0.00 |
May | 0.186245E+10 | 0.00 | 604.48 | 0.163824E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6013.77 | 26-MAY-15:01 | 6013.77 | 26-MAY-15:01 | 0.00 | 0.00 | 0.00 |
June | 0.293673E+10 | 0.00 | 669.25 | 0.231535E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6015.56 | 17-JUN-08:61 | 6015.56 | 17-JUN-08:61 | 0.00 | 0.00 | 0.00 |
July | 0.355246E+10 | 0.00 | 715.34 | 0.225914E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6656.66 | 01-JUL-08:61 | 6012.60 | 21-JUL-15:02 | 0.00 | 0.00 | 0.00 |
August | 0.326707E+10 | 0.00 | 707.36 | 0.199192E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6595.76 | 26-AUG-08:61 | 5409.83 | 18-AUG-08:61 | 0.00 | 0.00 | 0.00 |
September | 0.214754E+10 | 0.00 | 654.16 | 0.132145E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6015.31 | 25-SEP-18:01 | 6015.31 | 25-SEP-18:01 | 0.00 | 0.00 | 0.00 |
October | 0.103792E+10 | 0.00 | 413.37 | 0.809853E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6015.82 | 09-OCT-18:01 | 6015.82 | 09-OCT-18:01 | 0.00 | 0.00 | 0.00 |
November | 0.150284E+09 | 0.00 | 102.59 | 0.148784E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6014.09 | 02-NOV-15:01 | 6014.09 | 02-NOV-15:01 | 0.00 | 0.00 | 0.00 |
December | 31405776.05 | 0.00 | 21.79 | 31405776.05 | 0.00 | 0.00 | 0.00 | 0.00 | 5996.82 | 02-DEC-16:01 | 5996.82 | 02-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.169199E+11 | 0.00 | 4673.62 | 0.124436E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 31405776.05 | 0.00 | 21.79 | 31405776.05 | 0.00 | 0.00 | 0.00 | 0.00 | 5996.82 | 5409.83 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.355246E+10 | 0.00 | 715.34 | 0.231535E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6656.66 | 6015.82 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.741363E+10 | 0.00 | 337.82 | 0.741363E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25180.54 | 20-JAN-16:01 | 25180.54 | 20-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.732802E+10 | 0.00 | 363.29 | 0.732802E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25194.64 | 19-FEB-09:01 | 25194.64 | 19-FEB-09:01 | 0.00 | 0.00 | 0.00 |
March | 0.745554E+10 | 0.00 | 462.27 | 0.743615E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25201.77 | 08-MAR-09:01 | 25201.77 | 08-MAR-09:01 | 0.00 | 0.00 | 0.00 |
April | 0.856386E+10 | 0.00 | 573.34 | 0.851199E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25185.94 | 21-APR-15:01 | 25185.94 | 21-APR-15:01 | 0.00 | 0.00 | 0.00 |
May | 0.893443E+10 | 0.00 | 631.15 | 0.768958E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25221.05 | 26-MAY-15:01 | 25221.05 | 26-MAY-15:01 | 0.00 | 0.00 | 0.00 |
June | 0.121294E+11 | 0.00 | 664.95 | 0.923353E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25222.27 | 22-JUN-15:02 | 25222.27 | 22-JUN-15:02 | 0.00 | 0.00 | 0.00 |
July | 0.170163E+11 | 0.00 | 708.92 | 0.108117E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 27753.34 | 01-JUL-08:61 | 25208.04 | 21-JUL-15:02 | 0.00 | 0.00 | 0.00 |
August | 0.180495E+11 | 0.00 | 707.95 | 0.119067E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 27171.81 | 26-AUG-08:61 | 22843.02 | 24-AUG-18:01 | 0.00 | 0.00 | 0.00 |
September | 0.168107E+11 | 0.00 | 677.99 | 0.122488E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 25223.58 | 21-SEP-15:02 | 25223.58 | 21-SEP-15:02 | 0.00 | 0.00 | 0.00 |
October | 0.146473E+11 | 0.00 | 633.04 | 0.129970E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 25220.05 | 05-OCT-15:01 | 25220.05 | 05-OCT-15:01 | 0.00 | 0.00 | 0.00 |
November | 0.100986E+11 | 0.00 | 485.37 | 0.993315E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25226.57 | 02-NOV-15:01 | 25226.57 | 02-NOV-15:01 | 0.00 | 0.00 | 0.00 |
December | 0.805730E+10 | 0.00 | 359.81 | 0.805730E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25173.62 | 26-DEC-16:01 | 25173.62 | 26-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.136505E+12 | 0.00 | 6605.91 | 0.113568E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.732802E+10 | 0.00 | 337.82 | 0.732802E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25173.62 | 22843.02 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.180495E+11 | 0.00 | 708.92 | 0.129970E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 27753.34 | 25226.57 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1365.45 | 1061.86 | 303.59 | 1554.97 | 559.79 | 0.00 | 0.00 | 0.00 |
February | 1345.94 | 985.04 | 360.90 | 1565.18 | 510.23 | 0.00 | 0.00 | 0.00 |
March | 1000.83 | 610.71 | 390.12 | 1201.58 | 396.17 | 0.00 | 0.00 | 0.00 |
April | 768.64 | 315.00 | 453.64 | 975.29 | 258.45 | 0.00 | 0.00 | 0.00 |
May | 517.30 | 117.03 | 400.27 | 686.76 | 171.38 | 0.00 | 0.00 | 0.00 |
June | 432.45 | 51.93 | 380.52 | 681.93 | 96.74 | 0.00 | 0.00 | 0.00 |
July | 478.69 | 75.11 | 403.58 | 812.24 | 44.15 | 0.00 | 0.00 | 0.00 |
August | 651.18 | 205.38 | 445.80 | 1026.79 | 58.74 | 0.00 | 0.00 | 0.00 |
September | 924.44 | 520.38 | 404.06 | 1317.51 | 137.04 | 0.00 | 0.00 | 0.00 |
October | 1245.45 | 916.13 | 329.32 | 1584.34 | 281.38 | 0.00 | 0.00 | 0.00 |
November | 1404.90 | 1081.24 | 323.66 | 1648.12 | 433.31 | 0.00 | 0.00 | 0.00 |
December | 1489.03 | 1229.18 | 259.85 | 1701.41 | 573.87 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 966.54 | 595.38 | 371.15 | 1227.73 | 292.34 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 432.45 | 51.93 | 259.85 | 681.93 | 44.15 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1489.03 | 1229.18 | 453.64 | 1701.41 | 573.87 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 3845.01 | 2990.13 | 854.88 | 4365.28 | 1577.65 | 0.00 | 0.00 | 0.00 |
February | 3790.08 | 2773.82 | 1016.26 | 4394.59 | 1437.64 | 0.00 | 0.00 | 0.00 |
March | 2818.28 | 1719.73 | 1098.54 | 3370.99 | 1115.15 | 0.00 | 0.00 | 0.00 |
April | 2164.44 | 887.02 | 1277.42 | 2735.91 | 726.13 | 0.00 | 0.00 | 0.00 |
May | 1456.68 | 329.54 | 1127.14 | 1923.56 | 481.29 | 0.00 | 0.00 | 0.00 |
June | 1217.75 | 146.22 | 1071.52 | 1912.41 | 273.84 | 0.00 | 0.00 | 0.00 |
July | 1347.97 | 211.51 | 1136.46 | 2282.99 | 129.71 | 0.00 | 0.00 | 0.00 |
August | 1833.69 | 578.34 | 1255.35 | 2890.15 | 172.77 | 0.00 | 0.00 | 0.00 |
September | 2603.16 | 1465.35 | 1137.81 | 3710.79 | 391.79 | 0.00 | 0.00 | 0.00 |
October | 3507.10 | 2579.76 | 927.34 | 4456.78 | 797.40 | 0.00 | 0.00 | 0.00 |
November | 3956.12 | 3044.70 | 911.42 | 4630.22 | 1221.39 | 0.00 | 0.00 | 0.00 |
December | 4193.02 | 3461.29 | 731.73 | 4778.52 | 1618.53 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2721.70 | 1676.56 | 1045.14 | 3448.89 | 825.52 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1217.75 | 146.22 | 731.73 | 1912.41 | 129.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4193.02 | 3461.29 | 1277.42 | 4778.52 | 1618.53 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 4994.88 | 3884.35 | 1110.53 | 5791.38 | 2075.35 | 0.00 | 0.00 | 0.00 |
February | 4923.53 | 3603.35 | 1320.18 | 5833.43 | 1890.47 | 0.00 | 0.00 | 0.00 |
March | 3661.10 | 2234.03 | 1427.07 | 4479.19 | 1474.41 | 0.00 | 0.00 | 0.00 |
April | 2811.73 | 1152.28 | 1659.44 | 3638.92 | 966.74 | 0.00 | 0.00 | 0.00 |
May | 1892.31 | 428.09 | 1464.22 | 2562.61 | 650.68 | 0.00 | 0.00 | 0.00 |
June | 1581.92 | 189.95 | 1391.97 | 2549.75 | 373.96 | 0.00 | 0.00 | 0.00 |
July | 1751.09 | 274.76 | 1476.33 | 3043.16 | 176.24 | 0.00 | 0.00 | 0.00 |
August | 2382.07 | 751.30 | 1630.78 | 3853.73 | 228.11 | 0.00 | 0.00 | 0.00 |
September | 3381.65 | 1903.57 | 1478.08 | 4944.43 | 506.65 | 0.00 | 0.00 | 0.00 |
October | 4555.93 | 3351.26 | 1204.67 | 5930.19 | 1035.41 | 0.00 | 0.00 | 0.00 |
November | 5139.22 | 3955.24 | 1183.98 | 6151.90 | 1599.86 | 0.00 | 0.00 | 0.00 |
December | 5446.97 | 4496.41 | 950.56 | 6337.13 | 2126.89 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3535.64 | 2177.95 | 1357.69 | 4585.77 | 1088.03 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1581.92 | 189.95 | 950.56 | 2549.75 | 176.24 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 5446.97 | 4496.41 | 1659.44 | 6337.13 | 2126.89 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 269.97 | 209.95 | 60.02 | 309.19 | 113.26 | 0.00 | 0.00 | 0.00 |
February | 266.12 | 194.76 | 71.36 | 310.05 | 103.86 | 0.00 | 0.00 | 0.00 |
March | 197.88 | 120.75 | 77.13 | 236.05 | 81.57 | 0.00 | 0.00 | 0.00 |
April | 151.97 | 62.28 | 89.69 | 189.18 | 53.69 | 0.00 | 0.00 | 0.00 |
May | 102.28 | 23.14 | 79.14 | 131.60 | 35.73 | 0.00 | 0.00 | 0.00 |
June | 85.50 | 10.27 | 75.24 | 131.35 | 20.25 | 0.00 | 0.00 | 0.00 |
July | 94.65 | 14.85 | 79.80 | 157.50 | 9.27 | 0.00 | 0.00 | 0.00 |
August | 128.75 | 40.61 | 88.14 | 200.42 | 12.15 | 0.00 | 0.00 | 0.00 |
September | 182.78 | 102.89 | 79.89 | 259.62 | 27.83 | 0.00 | 0.00 | 0.00 |
October | 246.25 | 181.13 | 65.11 | 314.43 | 56.97 | 0.00 | 0.00 | 0.00 |
November | 277.77 | 213.78 | 63.99 | 327.56 | 87.53 | 0.00 | 0.00 | 0.00 |
December | 294.41 | 243.03 | 51.38 | 339.02 | 115.49 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 191.10 | 117.72 | 73.38 | 241.77 | 59.57 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 85.50 | 10.27 | 51.38 | 131.35 | 9.27 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 294.41 | 243.03 | 89.69 | 339.02 | 115.49 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 195.30 | 111.38 | 83.92 | 181.91 | 230.80 | 0.00 | 0.00 | 0.00 |
February | 250.90 | 144.77 | 106.13 | 250.86 | 207.17 | 0.00 | 0.00 | 0.00 |
March | 279.96 | 148.71 | 131.25 | 300.81 | 157.00 | 0.00 | 0.00 | 0.00 |
April | 358.17 | 190.62 | 167.55 | 418.22 | 97.98 | 0.00 | 0.00 | 0.00 |
May | 340.60 | 175.98 | 164.62 | 425.94 | 65.64 | 0.00 | 0.00 | 0.00 |
June | 362.93 | 202.12 | 160.81 | 510.63 | 37.70 | 0.00 | 0.00 | 0.00 |
July | 327.68 | 160.12 | 167.56 | 485.21 | 17.25 | 0.00 | 0.00 | 0.00 |
August | 335.18 | 154.81 | 180.38 | 476.76 | 22.66 | 0.00 | 0.00 | 0.00 |
September | 304.12 | 160.57 | 143.55 | 405.63 | 52.36 | 0.00 | 0.00 | 0.00 |
October | 278.31 | 173.36 | 104.96 | 328.82 | 113.94 | 0.00 | 0.00 | 0.00 |
November | 217.48 | 127.93 | 89.54 | 215.51 | 176.00 | 0.00 | 0.00 | 0.00 |
December | 186.74 | 116.61 | 70.13 | 169.42 | 236.70 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 286.48 | 155.51 | 130.97 | 347.83 | 117.50 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 186.74 | 111.38 | 70.13 | 169.42 | 17.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 362.93 | 202.12 | 180.38 | 510.63 | 236.70 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 36.58 | 0.00 | 36.58 | 10.34 | 124.58 | 0.00 | 0.00 | 0.00 |
February | 45.72 | 0.00 | 45.72 | 19.27 | 111.64 | 0.00 | 0.00 | 0.00 |
March | 57.68 | 0.00 | 57.68 | 39.43 | 84.40 | 0.00 | 0.00 | 0.00 |
April | 73.57 | 0.99 | 72.59 | 64.50 | 51.25 | 0.00 | 0.00 | 0.00 |
May | 79.63 | 5.17 | 74.46 | 88.55 | 33.50 | 0.00 | 0.00 | 0.00 |
June | 90.67 | 15.08 | 75.59 | 134.32 | 18.91 | 0.00 | 0.00 | 0.00 |
July | 83.14 | 7.09 | 76.05 | 134.13 | 8.97 | 0.00 | 0.00 | 0.00 |
August | 77.16 | 1.89 | 75.27 | 113.85 | 11.55 | 0.00 | 0.00 | 0.00 |
September | 61.59 | 0.04 | 61.55 | 77.43 | 27.36 | 0.00 | 0.00 | 0.00 |
October | 45.92 | 0.00 | 45.92 | 37.28 | 60.44 | 0.00 | 0.00 | 0.00 |
November | 38.99 | 0.00 | 38.99 | 14.82 | 94.73 | 0.00 | 0.00 | 0.00 |
December | 31.14 | 0.00 | 31.14 | 4.05 | 128.28 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 60.20 | 2.53 | 57.68 | 61.72 | 62.73 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 31.14 | 0.00 | 31.14 | 4.05 | 8.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 90.67 | 15.08 | 76.05 | 134.32 | 128.28 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 195.30 | 111.38 | 83.92 | 189.85 | 225.63 | 0.00 | 0.00 | 0.00 |
February | 250.90 | 144.77 | 106.13 | 258.89 | 202.55 | 0.00 | 0.00 | 0.00 |
March | 279.96 | 148.71 | 131.25 | 306.59 | 154.35 | 0.00 | 0.00 | 0.00 |
April | 358.17 | 190.62 | 167.55 | 421.75 | 96.89 | 0.00 | 0.00 | 0.00 |
May | 340.60 | 175.98 | 164.62 | 427.18 | 65.29 | 0.00 | 0.00 | 0.00 |
June | 362.93 | 202.12 | 160.81 | 510.70 | 37.58 | 0.00 | 0.00 | 0.00 |
July | 327.68 | 160.12 | 167.56 | 485.75 | 17.10 | 0.00 | 0.00 | 0.00 |
August | 335.18 | 154.81 | 180.38 | 478.55 | 22.24 | 0.00 | 0.00 | 0.00 |
September | 304.12 | 160.57 | 143.55 | 409.25 | 51.05 | 0.00 | 0.00 | 0.00 |
October | 278.31 | 173.36 | 104.96 | 335.06 | 110.98 | 0.00 | 0.00 | 0.00 |
November | 217.48 | 127.93 | 89.54 | 223.13 | 171.31 | 0.00 | 0.00 | 0.00 |
December | 186.74 | 116.61 | 70.13 | 177.35 | 229.95 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 286.48 | 155.51 | 130.97 | 352.34 | 114.98 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 186.74 | 111.38 | 70.13 | 177.35 | 17.10 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 362.93 | 202.12 | 180.38 | 510.70 | 229.95 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 215.94 | 167.92 | 48.01 | 243.43 | 98.50 | 0.00 | 0.00 | 0.00 |
February | 212.85 | 155.78 | 57.07 | 244.33 | 91.53 | 0.00 | 0.00 | 0.00 |
March | 158.27 | 96.58 | 61.69 | 185.22 | 73.50 | 0.00 | 0.00 | 0.00 |
April | 121.56 | 49.81 | 71.74 | 148.78 | 49.77 | 0.00 | 0.00 | 0.00 |
May | 81.81 | 18.51 | 63.30 | 102.86 | 34.64 | 0.00 | 0.00 | 0.00 |
June | 68.39 | 8.21 | 60.18 | 103.10 | 20.79 | 0.00 | 0.00 | 0.00 |
July | 75.70 | 11.88 | 63.82 | 123.85 | 11.35 | 0.00 | 0.00 | 0.00 |
August | 102.98 | 32.48 | 70.50 | 158.28 | 14.18 | 0.00 | 0.00 | 0.00 |
September | 146.19 | 82.29 | 63.90 | 205.58 | 28.45 | 0.00 | 0.00 | 0.00 |
October | 196.96 | 144.88 | 52.08 | 248.28 | 53.19 | 0.00 | 0.00 | 0.00 |
November | 222.18 | 170.99 | 51.19 | 257.82 | 79.52 | 0.00 | 0.00 | 0.00 |
December | 235.48 | 194.39 | 41.09 | 267.04 | 101.75 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 152.85 | 94.16 | 58.70 | 190.40 | 54.57 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 68.39 | 8.21 | 41.09 | 102.86 | 11.35 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 235.48 | 194.39 | 71.74 | 267.04 | 101.75 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 29.27 | 0.00 | 29.27 | 7.73 | 102.52 | 0.00 | 0.00 | 0.00 |
February | 36.58 | 0.00 | 36.58 | 15.54 | 91.10 | 0.00 | 0.00 | 0.00 |
March | 46.15 | 0.00 | 46.15 | 32.50 | 68.28 | 0.00 | 0.00 | 0.00 |
April | 58.87 | 0.79 | 58.08 | 54.14 | 40.45 | 0.00 | 0.00 | 0.00 |
May | 63.72 | 4.14 | 59.58 | 73.76 | 26.22 | 0.00 | 0.00 | 0.00 |
June | 72.54 | 12.06 | 60.48 | 111.45 | 14.30 | 0.00 | 0.00 | 0.00 |
July | 66.52 | 5.67 | 60.85 | 111.56 | 6.26 | 0.00 | 0.00 | 0.00 |
August | 61.73 | 1.51 | 60.22 | 95.29 | 8.19 | 0.00 | 0.00 | 0.00 |
September | 49.28 | 0.04 | 49.25 | 65.17 | 20.68 | 0.00 | 0.00 | 0.00 |
October | 36.74 | 0.00 | 36.74 | 31.47 | 48.05 | 0.00 | 0.00 | 0.00 |
November | 31.20 | 0.00 | 31.20 | 11.79 | 77.38 | 0.00 | 0.00 | 0.00 |
December | 24.91 | 0.00 | 24.91 | 2.80 | 105.92 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 48.17 | 2.02 | 46.15 | 51.29 | 50.59 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 24.91 | 0.00 | 24.91 | 2.80 | 6.26 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 72.54 | 12.06 | 60.85 | 111.56 | 105.92 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 189.37 | 105.99 | 83.38 | 160.45 | 218.47 | 0.00 | 0.00 | 0.00 |
February | 229.33 | 123.28 | 106.05 | 213.34 | 196.90 | 0.00 | 0.00 | 0.00 |
March | 304.76 | 173.62 | 131.14 | 323.96 | 147.59 | 0.00 | 0.00 | 0.00 |
April | 413.42 | 235.26 | 178.16 | 488.84 | 92.71 | 0.00 | 0.00 | 0.00 |
May | 394.96 | 224.96 | 169.99 | 496.41 | 62.97 | 0.00 | 0.00 | 0.00 |
June | 425.94 | 262.36 | 163.58 | 592.17 | 34.86 | 0.00 | 0.00 | 0.00 |
July | 393.93 | 225.19 | 168.74 | 574.23 | 16.61 | 0.00 | 0.00 | 0.00 |
August | 389.89 | 214.90 | 174.99 | 548.26 | 21.45 | 0.00 | 0.00 | 0.00 |
September | 325.12 | 181.92 | 143.20 | 430.16 | 49.42 | 0.00 | 0.00 | 0.00 |
October | 283.26 | 179.87 | 103.38 | 327.45 | 106.17 | 0.00 | 0.00 | 0.00 |
November | 220.30 | 129.24 | 91.06 | 212.04 | 169.44 | 0.00 | 0.00 | 0.00 |
December | 179.45 | 109.46 | 69.99 | 153.37 | 229.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 312.79 | 180.74 | 132.05 | 377.47 | 111.79 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 179.45 | 105.99 | 69.99 | 153.37 | 16.61 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 425.94 | 262.36 | 178.16 | 592.17 | 229.86 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 269.97 | 209.95 | 60.02 | 308.42 | 112.76 | 0.00 | 0.00 | 0.00 |
February | 266.12 | 194.76 | 71.36 | 309.25 | 103.10 | 0.00 | 0.00 | 0.00 |
March | 197.88 | 120.75 | 77.13 | 234.32 | 81.19 | 0.00 | 0.00 | 0.00 |
April | 151.97 | 62.28 | 89.69 | 187.00 | 53.45 | 0.00 | 0.00 | 0.00 |
May | 102.28 | 23.14 | 79.14 | 129.44 | 35.53 | 0.00 | 0.00 | 0.00 |
June | 85.50 | 10.27 | 75.24 | 129.60 | 19.90 | 0.00 | 0.00 | 0.00 |
July | 94.65 | 14.85 | 79.80 | 156.03 | 9.18 | 0.00 | 0.00 | 0.00 |
August | 128.75 | 40.61 | 88.14 | 199.13 | 11.97 | 0.00 | 0.00 | 0.00 |
September | 182.78 | 102.89 | 79.89 | 258.67 | 27.48 | 0.00 | 0.00 | 0.00 |
October | 246.25 | 181.13 | 65.11 | 313.29 | 56.44 | 0.00 | 0.00 | 0.00 |
November | 277.77 | 213.78 | 63.99 | 326.57 | 87.02 | 0.00 | 0.00 | 0.00 |
December | 294.41 | 243.03 | 51.38 | 338.24 | 115.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 191.10 | 117.72 | 73.38 | 240.44 | 59.19 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 85.50 | 10.27 | 51.38 | 129.44 | 9.18 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 294.41 | 243.03 | 89.69 | 338.24 | 115.00 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 36.58 | 0.00 | 36.58 | 9.70 | 123.91 | 0.00 | 0.00 | 0.00 |
February | 45.72 | 0.00 | 45.72 | 18.69 | 110.84 | 0.00 | 0.00 | 0.00 |
March | 57.68 | 0.00 | 57.68 | 37.80 | 84.69 | 0.00 | 0.00 | 0.00 |
April | 73.57 | 0.99 | 72.59 | 61.79 | 51.12 | 0.00 | 0.00 | 0.00 |
May | 79.63 | 5.17 | 74.46 | 86.23 | 33.28 | 0.00 | 0.00 | 0.00 |
June | 90.67 | 15.08 | 75.59 | 132.57 | 18.67 | 0.00 | 0.00 | 0.00 |
July | 83.14 | 7.09 | 76.05 | 132.66 | 8.91 | 0.00 | 0.00 | 0.00 |
August | 77.16 | 1.89 | 75.27 | 112.41 | 11.35 | 0.00 | 0.00 | 0.00 |
September | 61.59 | 0.04 | 61.55 | 76.25 | 27.08 | 0.00 | 0.00 | 0.00 |
October | 45.92 | 0.00 | 45.92 | 35.93 | 60.22 | 0.00 | 0.00 | 0.00 |
November | 38.99 | 0.00 | 38.99 | 14.00 | 94.10 | 0.00 | 0.00 | 0.00 |
December | 31.14 | 0.00 | 31.14 | 3.56 | 127.71 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 60.20 | 2.53 | 57.68 | 60.35 | 62.42 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 31.14 | 0.00 | 31.14 | 3.56 | 8.91 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 90.67 | 15.08 | 76.05 | 132.66 | 127.71 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 189.37 | 105.99 | 83.38 | 167.85 | 212.01 | 0.00 | 0.00 | 0.00 |
February | 229.33 | 123.28 | 106.05 | 221.14 | 191.34 | 0.00 | 0.00 | 0.00 |
March | 304.76 | 173.62 | 131.14 | 328.93 | 145.03 | 0.00 | 0.00 | 0.00 |
April | 413.42 | 235.26 | 178.16 | 491.48 | 91.65 | 0.00 | 0.00 | 0.00 |
May | 394.96 | 224.96 | 169.99 | 497.42 | 62.64 | 0.00 | 0.00 | 0.00 |
June | 425.94 | 262.36 | 163.58 | 592.35 | 34.83 | 0.00 | 0.00 | 0.00 |
July | 393.93 | 225.19 | 168.74 | 574.82 | 16.49 | 0.00 | 0.00 | 0.00 |
August | 389.89 | 214.90 | 174.99 | 549.95 | 21.05 | 0.00 | 0.00 | 0.00 |
September | 325.12 | 181.92 | 143.20 | 433.45 | 48.16 | 0.00 | 0.00 | 0.00 |
October | 283.26 | 179.87 | 103.38 | 332.85 | 103.20 | 0.00 | 0.00 | 0.00 |
November | 220.30 | 129.24 | 91.06 | 219.08 | 163.47 | 0.00 | 0.00 | 0.00 |
December | 179.45 | 109.46 | 69.99 | 159.33 | 220.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 312.79 | 180.74 | 132.05 | 381.45 | 108.75 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 179.45 | 105.99 | 69.99 | 159.33 | 16.49 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 425.94 | 262.36 | 178.16 | 592.35 | 220.00 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 46.33 | 0.00 | 46.33 | 11.06 | 165.56 | 0.00 | 0.00 | 0.00 |
February | 57.90 | 0.00 | 57.90 | 23.74 | 146.45 | 0.00 | 0.00 | 0.00 |
March | 73.05 | 0.00 | 73.05 | 52.19 | 108.11 | 0.00 | 0.00 | 0.00 |
April | 93.17 | 1.25 | 91.93 | 88.46 | 63.68 | 0.00 | 0.00 | 0.00 |
May | 100.85 | 6.55 | 94.30 | 120.91 | 41.11 | 0.00 | 0.00 | 0.00 |
June | 114.82 | 19.10 | 95.73 | 179.77 | 22.94 | 0.00 | 0.00 | 0.00 |
July | 105.29 | 8.97 | 96.32 | 178.47 | 11.19 | 0.00 | 0.00 | 0.00 |
August | 97.72 | 2.39 | 95.32 | 151.90 | 14.63 | 0.00 | 0.00 | 0.00 |
September | 78.01 | 0.06 | 77.95 | 104.47 | 34.56 | 0.00 | 0.00 | 0.00 |
October | 58.15 | 0.00 | 58.15 | 49.72 | 77.70 | 0.00 | 0.00 | 0.00 |
November | 49.38 | 0.00 | 49.38 | 18.15 | 124.03 | 0.00 | 0.00 | 0.00 |
December | 39.43 | 0.00 | 39.43 | 3.62 | 172.56 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 76.24 | 3.20 | 73.04 | 82.17 | 81.57 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 39.43 | 0.00 | 39.43 | 3.62 | 11.19 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 114.82 | 19.10 | 96.32 | 179.77 | 172.56 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 17.08 | 0.00 | 17.08 | 4.08 | 61.03 | 0.00 | 0.00 | 0.00 |
February | 21.35 | 0.00 | 21.35 | 8.75 | 53.99 | 0.00 | 0.00 | 0.00 |
March | 26.93 | 0.00 | 26.93 | 19.24 | 39.85 | 0.00 | 0.00 | 0.00 |
April | 34.35 | 0.46 | 33.89 | 32.61 | 23.47 | 0.00 | 0.00 | 0.00 |
May | 37.18 | 2.42 | 34.76 | 44.57 | 15.15 | 0.00 | 0.00 | 0.00 |
June | 42.33 | 7.04 | 35.29 | 66.27 | 8.46 | 0.00 | 0.00 | 0.00 |
July | 38.81 | 3.31 | 35.51 | 65.79 | 4.12 | 0.00 | 0.00 | 0.00 |
August | 36.02 | 0.88 | 35.14 | 56.00 | 5.39 | 0.00 | 0.00 | 0.00 |
September | 28.76 | 0.02 | 28.74 | 38.51 | 12.74 | 0.00 | 0.00 | 0.00 |
October | 21.44 | 0.00 | 21.44 | 18.33 | 28.64 | 0.00 | 0.00 | 0.00 |
November | 18.20 | 0.00 | 18.20 | 6.69 | 45.72 | 0.00 | 0.00 | 0.00 |
December | 14.54 | 0.00 | 14.54 | 1.33 | 63.61 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 28.11 | 1.18 | 26.93 | 30.29 | 30.07 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 14.54 | 0.00 | 14.54 | 1.33 | 4.12 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 42.33 | 7.04 | 35.51 | 66.27 | 63.61 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 125.97 | 97.96 | 28.01 | 145.65 | 53.83 | 0.00 | 0.00 | 0.00 |
February | 124.17 | 90.87 | 33.29 | 146.62 | 48.99 | 0.00 | 0.00 | 0.00 |
March | 92.33 | 56.34 | 35.99 | 112.42 | 37.90 | 0.00 | 0.00 | 0.00 |
April | 70.91 | 29.06 | 41.85 | 91.53 | 24.27 | 0.00 | 0.00 | 0.00 |
May | 47.72 | 10.80 | 36.93 | 64.78 | 16.02 | 0.00 | 0.00 | 0.00 |
June | 39.90 | 4.79 | 35.11 | 64.76 | 9.07 | 0.00 | 0.00 | 0.00 |
July | 44.16 | 6.93 | 37.23 | 76.72 | 4.24 | 0.00 | 0.00 | 0.00 |
August | 60.07 | 18.95 | 41.13 | 96.75 | 5.59 | 0.00 | 0.00 | 0.00 |
September | 85.28 | 48.01 | 37.28 | 124.28 | 12.65 | 0.00 | 0.00 | 0.00 |
October | 114.90 | 84.52 | 30.38 | 149.39 | 26.32 | 0.00 | 0.00 | 0.00 |
November | 129.61 | 99.75 | 29.86 | 155.01 | 40.97 | 0.00 | 0.00 | 0.00 |
December | 137.37 | 113.40 | 23.97 | 159.67 | 55.03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 89.17 | 54.93 | 34.24 | 115.45 | 27.80 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 39.90 | 4.79 | 23.97 | 64.76 | 4.24 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 137.37 | 113.40 | 41.85 | 159.67 | 55.03 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 341.90 | 265.89 | 76.02 | 395.32 | 146.10 | 0.00 | 0.00 | 0.00 |
February | 337.02 | 246.65 | 90.37 | 397.94 | 132.98 | 0.00 | 0.00 | 0.00 |
March | 250.61 | 152.92 | 97.68 | 305.12 | 102.87 | 0.00 | 0.00 | 0.00 |
April | 192.47 | 78.87 | 113.59 | 248.42 | 65.88 | 0.00 | 0.00 | 0.00 |
May | 129.53 | 29.30 | 100.23 | 175.82 | 43.49 | 0.00 | 0.00 | 0.00 |
June | 108.29 | 13.00 | 95.28 | 175.76 | 24.63 | 0.00 | 0.00 | 0.00 |
July | 119.86 | 18.81 | 101.06 | 208.23 | 11.52 | 0.00 | 0.00 | 0.00 |
August | 163.06 | 51.43 | 111.63 | 262.59 | 15.19 | 0.00 | 0.00 | 0.00 |
September | 231.48 | 130.30 | 101.18 | 337.33 | 34.33 | 0.00 | 0.00 | 0.00 |
October | 311.86 | 229.40 | 82.46 | 405.46 | 71.45 | 0.00 | 0.00 | 0.00 |
November | 351.78 | 270.74 | 81.05 | 420.73 | 111.21 | 0.00 | 0.00 | 0.00 |
December | 372.85 | 307.78 | 65.07 | 433.38 | 149.35 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 242.02 | 149.08 | 92.94 | 313.35 | 75.46 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 108.29 | 13.00 | 65.07 | 175.76 | 11.52 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 372.85 | 307.78 | 113.59 | 433.38 | 149.35 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 269.97 | 209.95 | 60.02 | 308.15 | 112.64 | 0.00 | 0.00 | 0.00 |
February | 266.12 | 194.76 | 71.36 | 308.63 | 103.48 | 0.00 | 0.00 | 0.00 |
March | 197.88 | 120.75 | 77.13 | 234.42 | 81.41 | 0.00 | 0.00 | 0.00 |
April | 151.97 | 62.28 | 89.69 | 187.09 | 53.64 | 0.00 | 0.00 | 0.00 |
May | 102.28 | 23.14 | 79.14 | 129.63 | 35.74 | 0.00 | 0.00 | 0.00 |
June | 85.50 | 10.27 | 75.24 | 129.59 | 20.24 | 0.00 | 0.00 | 0.00 |
July | 94.65 | 14.85 | 79.80 | 155.56 | 9.26 | 0.00 | 0.00 | 0.00 |
August | 128.75 | 40.61 | 88.14 | 198.22 | 12.19 | 0.00 | 0.00 | 0.00 |
September | 182.78 | 102.89 | 79.89 | 257.43 | 27.86 | 0.00 | 0.00 | 0.00 |
October | 246.25 | 181.13 | 65.11 | 312.76 | 56.80 | 0.00 | 0.00 | 0.00 |
November | 277.77 | 213.78 | 63.99 | 326.30 | 87.01 | 0.00 | 0.00 | 0.00 |
December | 294.41 | 243.03 | 51.38 | 338.18 | 114.65 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 191.10 | 117.72 | 73.38 | 240.10 | 59.35 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 85.50 | 10.27 | 51.38 | 129.59 | 9.26 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 294.41 | 243.03 | 89.69 | 338.18 | 114.65 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 195.30 | 111.38 | 83.92 | 180.65 | 229.16 | 0.00 | 0.00 | 0.00 |
February | 250.90 | 144.77 | 106.13 | 248.71 | 206.29 | 0.00 | 0.00 | 0.00 |
March | 279.96 | 148.71 | 131.25 | 297.98 | 156.49 | 0.00 | 0.00 | 0.00 |
April | 358.17 | 190.62 | 167.55 | 413.82 | 97.71 | 0.00 | 0.00 | 0.00 |
May | 340.60 | 175.98 | 164.62 | 421.37 | 65.59 | 0.00 | 0.00 | 0.00 |
June | 362.93 | 202.12 | 160.81 | 506.23 | 37.76 | 0.00 | 0.00 | 0.00 |
July | 327.68 | 160.12 | 167.56 | 480.83 | 17.28 | 0.00 | 0.00 | 0.00 |
August | 335.18 | 154.81 | 180.38 | 472.43 | 22.76 | 0.00 | 0.00 | 0.00 |
September | 304.12 | 160.57 | 143.55 | 401.99 | 52.39 | 0.00 | 0.00 | 0.00 |
October | 278.31 | 173.36 | 104.96 | 326.15 | 113.38 | 0.00 | 0.00 | 0.00 |
November | 217.48 | 127.93 | 89.54 | 213.74 | 174.64 | 0.00 | 0.00 | 0.00 |
December | 186.74 | 116.61 | 70.13 | 168.29 | 234.53 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 286.48 | 155.51 | 130.97 | 344.70 | 116.89 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 186.74 | 111.38 | 70.13 | 168.29 | 17.28 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 362.93 | 202.12 | 180.38 | 506.23 | 234.53 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 36.58 | 0.00 | 36.58 | 10.53 | 123.65 | 0.00 | 0.00 | 0.00 |
February | 45.72 | 0.00 | 45.72 | 19.16 | 111.14 | 0.00 | 0.00 | 0.00 |
March | 57.68 | 0.00 | 57.68 | 38.90 | 84.13 | 0.00 | 0.00 | 0.00 |
April | 73.57 | 0.99 | 72.59 | 63.08 | 51.19 | 0.00 | 0.00 | 0.00 |
May | 79.63 | 5.17 | 74.46 | 86.81 | 33.50 | 0.00 | 0.00 | 0.00 |
June | 90.67 | 15.08 | 75.59 | 132.50 | 18.98 | 0.00 | 0.00 | 0.00 |
July | 83.14 | 7.09 | 76.05 | 132.38 | 8.97 | 0.00 | 0.00 | 0.00 |
August | 77.16 | 1.89 | 75.27 | 112.15 | 11.58 | 0.00 | 0.00 | 0.00 |
September | 61.59 | 0.04 | 61.55 | 76.14 | 27.36 | 0.00 | 0.00 | 0.00 |
October | 45.92 | 0.00 | 45.92 | 36.60 | 60.11 | 0.00 | 0.00 | 0.00 |
November | 38.99 | 0.00 | 38.99 | 14.79 | 93.93 | 0.00 | 0.00 | 0.00 |
December | 31.14 | 0.00 | 31.14 | 4.20 | 127.01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 60.20 | 2.53 | 57.68 | 60.82 | 62.39 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 31.14 | 0.00 | 31.14 | 4.20 | 8.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 90.67 | 15.08 | 76.05 | 132.50 | 127.01 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 195.30 | 111.38 | 83.92 | 189.33 | 223.79 | 0.00 | 0.00 | 0.00 |
February | 250.90 | 144.77 | 106.13 | 257.36 | 201.42 | 0.00 | 0.00 | 0.00 |
March | 279.96 | 148.71 | 131.25 | 304.03 | 153.68 | 0.00 | 0.00 | 0.00 |
April | 358.17 | 190.62 | 167.55 | 417.24 | 96.61 | 0.00 | 0.00 | 0.00 |
May | 340.60 | 175.98 | 164.62 | 422.53 | 65.25 | 0.00 | 0.00 | 0.00 |
June | 362.93 | 202.12 | 160.81 | 506.28 | 37.65 | 0.00 | 0.00 | 0.00 |
July | 327.68 | 160.12 | 167.56 | 481.36 | 17.13 | 0.00 | 0.00 | 0.00 |
August | 335.18 | 154.81 | 180.38 | 474.23 | 22.32 | 0.00 | 0.00 | 0.00 |
September | 304.12 | 160.57 | 143.55 | 405.57 | 51.04 | 0.00 | 0.00 | 0.00 |
October | 278.31 | 173.36 | 104.96 | 332.56 | 110.26 | 0.00 | 0.00 | 0.00 |
November | 217.48 | 127.93 | 89.54 | 222.10 | 169.50 | 0.00 | 0.00 | 0.00 |
December | 186.74 | 116.61 | 70.13 | 177.11 | 227.64 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 286.48 | 155.51 | 130.97 | 349.47 | 114.26 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 186.74 | 111.38 | 70.13 | 177.11 | 17.13 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 362.93 | 202.12 | 180.38 | 506.28 | 227.64 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 395.94 | 307.91 | 88.03 | 444.34 | 171.50 | 0.00 | 0.00 | 0.00 |
February | 390.28 | 285.63 | 104.65 | 446.41 | 156.68 | 0.00 | 0.00 | 0.00 |
March | 290.21 | 177.09 | 113.12 | 340.43 | 121.57 | 0.00 | 0.00 | 0.00 |
April | 222.88 | 91.34 | 131.54 | 274.77 | 77.85 | 0.00 | 0.00 | 0.00 |
May | 150.00 | 33.93 | 116.07 | 192.65 | 51.02 | 0.00 | 0.00 | 0.00 |
June | 125.40 | 15.06 | 110.34 | 195.09 | 28.11 | 0.00 | 0.00 | 0.00 |
July | 138.81 | 21.78 | 117.03 | 232.92 | 12.37 | 0.00 | 0.00 | 0.00 |
August | 188.83 | 59.55 | 129.27 | 294.26 | 16.68 | 0.00 | 0.00 | 0.00 |
September | 268.06 | 150.89 | 117.17 | 377.99 | 40.20 | 0.00 | 0.00 | 0.00 |
October | 361.15 | 265.65 | 95.49 | 455.62 | 84.85 | 0.00 | 0.00 | 0.00 |
November | 407.38 | 313.53 | 93.85 | 472.41 | 132.27 | 0.00 | 0.00 | 0.00 |
December | 431.78 | 356.43 | 75.35 | 487.83 | 175.25 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 280.27 | 172.64 | 107.62 | 350.68 | 88.69 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 125.40 | 15.06 | 75.35 | 192.65 | 12.37 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 431.78 | 356.43 | 131.54 | 487.83 | 175.25 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 256.06 | 0.00 | 256.06 | 60.38 | 906.74 | 0.00 | 0.00 | 0.00 |
February | 320.04 | 0.00 | 320.04 | 128.48 | 807.29 | 0.00 | 0.00 | 0.00 |
March | 403.77 | 0.01 | 403.75 | 281.14 | 605.02 | 0.00 | 0.00 | 0.00 |
April | 514.99 | 6.90 | 508.09 | 477.46 | 363.22 | 0.00 | 0.00 | 0.00 |
May | 557.42 | 36.22 | 521.20 | 652.46 | 241.85 | 0.00 | 0.00 | 0.00 |
June | 634.64 | 105.54 | 529.10 | 983.76 | 138.89 | 0.00 | 0.00 | 0.00 |
July | 581.96 | 49.60 | 532.35 | 985.83 | 69.99 | 0.00 | 0.00 | 0.00 |
August | 540.08 | 13.22 | 526.86 | 843.56 | 88.51 | 0.00 | 0.00 | 0.00 |
September | 431.15 | 0.31 | 430.84 | 581.33 | 195.10 | 0.00 | 0.00 | 0.00 |
October | 321.40 | 0.00 | 321.40 | 277.12 | 428.39 | 0.00 | 0.00 | 0.00 |
November | 272.95 | 0.00 | 272.95 | 98.35 | 682.08 | 0.00 | 0.00 | 0.00 |
December | 217.95 | 0.00 | 217.95 | 20.01 | 941.80 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 421.40 | 17.68 | 403.72 | 450.85 | 454.07 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 217.95 | 0.00 | 217.95 | 20.01 | 69.99 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 634.64 | 105.54 | 532.35 | 985.83 | 941.80 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 256.06 | 0.00 | 256.06 | 57.50 | 919.54 | 0.00 | 0.00 | 0.00 |
February | 320.04 | 0.00 | 320.04 | 124.69 | 819.55 | 0.00 | 0.00 | 0.00 |
March | 403.77 | 0.01 | 403.75 | 275.50 | 616.68 | 0.00 | 0.00 | 0.00 |
April | 514.99 | 6.90 | 508.09 | 469.00 | 373.14 | 0.00 | 0.00 | 0.00 |
May | 557.42 | 36.22 | 521.20 | 642.10 | 250.66 | 0.00 | 0.00 | 0.00 |
June | 634.64 | 105.54 | 529.10 | 971.91 | 145.96 | 0.00 | 0.00 | 0.00 |
July | 581.96 | 49.60 | 532.35 | 973.82 | 76.10 | 0.00 | 0.00 | 0.00 |
August | 540.08 | 13.22 | 526.86 | 832.52 | 95.19 | 0.00 | 0.00 | 0.00 |
September | 431.15 | 0.31 | 430.84 | 573.17 | 204.47 | 0.00 | 0.00 | 0.00 |
October | 321.40 | 0.00 | 321.40 | 271.63 | 439.67 | 0.00 | 0.00 | 0.00 |
November | 272.95 | 0.00 | 272.95 | 94.75 | 694.60 | 0.00 | 0.00 | 0.00 |
December | 217.95 | 0.00 | 217.95 | 18.55 | 955.67 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 421.40 | 17.68 | 403.72 | 443.77 | 464.25 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 217.95 | 0.00 | 217.95 | 18.55 | 76.10 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 634.64 | 105.54 | 532.35 | 973.82 | 955.67 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 36.58 | 0.00 | 36.58 | 13.23 | 120.85 | 0.00 | 0.00 | 0.00 |
February | 45.72 | 0.00 | 45.72 | 23.81 | 109.19 | 0.00 | 0.00 | 0.00 |
March | 57.68 | 0.00 | 57.68 | 47.52 | 83.35 | 0.00 | 0.00 | 0.00 |
April | 73.57 | 0.99 | 72.59 | 78.36 | 51.15 | 0.00 | 0.00 | 0.00 |
May | 79.63 | 5.17 | 74.46 | 105.84 | 34.79 | 0.00 | 0.00 | 0.00 |
June | 90.67 | 15.08 | 75.59 | 156.16 | 20.50 | 0.00 | 0.00 | 0.00 |
July | 83.14 | 7.09 | 76.05 | 157.14 | 10.46 | 0.00 | 0.00 | 0.00 |
August | 77.16 | 1.89 | 75.27 | 136.20 | 12.88 | 0.00 | 0.00 | 0.00 |
September | 61.59 | 0.04 | 61.55 | 96.02 | 26.52 | 0.00 | 0.00 | 0.00 |
October | 45.92 | 0.00 | 45.92 | 48.41 | 57.58 | 0.00 | 0.00 | 0.00 |
November | 38.99 | 0.00 | 38.99 | 19.21 | 90.40 | 0.00 | 0.00 | 0.00 |
December | 31.14 | 0.00 | 31.14 | 5.54 | 123.78 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 60.20 | 2.53 | 57.68 | 74.22 | 61.56 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 31.14 | 0.00 | 31.14 | 5.54 | 10.46 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 90.67 | 15.08 | 76.05 | 157.14 | 123.78 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 378.72 | 211.97 | 166.75 | 359.48 | 419.56 | 0.00 | 0.00 | 0.00 |
February | 458.63 | 246.53 | 212.09 | 471.97 | 381.62 | 0.00 | 0.00 | 0.00 |
March | 609.47 | 347.21 | 262.26 | 704.49 | 291.94 | 0.00 | 0.00 | 0.00 |
April | 826.77 | 470.48 | 356.29 | 1051.75 | 187.67 | 0.00 | 0.00 | 0.00 |
May | 789.86 | 449.90 | 339.96 | 1069.59 | 131.18 | 0.00 | 0.00 | 0.00 |
June | 851.82 | 524.69 | 327.13 | 1271.53 | 76.88 | 0.00 | 0.00 | 0.00 |
July | 787.80 | 450.35 | 337.45 | 1240.62 | 39.29 | 0.00 | 0.00 | 0.00 |
August | 779.72 | 429.77 | 349.95 | 1188.30 | 48.59 | 0.00 | 0.00 | 0.00 |
September | 650.19 | 363.81 | 286.38 | 944.06 | 98.09 | 0.00 | 0.00 | 0.00 |
October | 566.48 | 359.72 | 206.75 | 722.54 | 203.11 | 0.00 | 0.00 | 0.00 |
November | 440.57 | 258.46 | 182.12 | 468.95 | 319.44 | 0.00 | 0.00 | 0.00 |
December | 358.87 | 218.90 | 139.97 | 337.85 | 432.52 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 625.54 | 361.45 | 264.09 | 820.86 | 218.36 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 358.87 | 211.97 | 139.97 | 337.85 | 39.29 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 851.82 | 524.69 | 356.29 | 1271.53 | 432.52 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 269.97 | 209.95 | 60.02 | 322.46 | 109.74 | 0.00 | 0.00 | 0.00 |
February | 266.12 | 194.76 | 71.36 | 324.06 | 100.74 | 0.00 | 0.00 | 0.00 |
March | 197.88 | 120.75 | 77.13 | 249.53 | 79.77 | 0.00 | 0.00 | 0.00 |
April | 151.97 | 62.28 | 89.69 | 204.93 | 52.63 | 0.00 | 0.00 | 0.00 |
May | 102.28 | 23.14 | 79.14 | 148.92 | 36.17 | 0.00 | 0.00 | 0.00 |
June | 85.50 | 10.27 | 75.24 | 152.12 | 21.25 | 0.00 | 0.00 | 0.00 |
July | 94.65 | 14.85 | 79.80 | 180.32 | 10.48 | 0.00 | 0.00 | 0.00 |
August | 128.75 | 40.61 | 88.14 | 223.40 | 13.04 | 0.00 | 0.00 | 0.00 |
September | 182.78 | 102.89 | 79.89 | 280.49 | 26.51 | 0.00 | 0.00 | 0.00 |
October | 246.25 | 181.13 | 65.11 | 332.40 | 54.11 | 0.00 | 0.00 | 0.00 |
November | 277.77 | 213.78 | 63.99 | 342.55 | 83.62 | 0.00 | 0.00 | 0.00 |
December | 294.41 | 243.03 | 51.38 | 352.30 | 110.99 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 191.10 | 117.72 | 73.38 | 259.08 | 58.04 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 85.50 | 10.27 | 51.38 | 148.92 | 10.48 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 294.41 | 243.03 | 89.69 | 352.30 | 110.99 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 46.33 | 0.00 | 46.33 | 9.88 | 166.46 | 0.00 | 0.00 | 0.00 |
February | 57.90 | 0.00 | 57.90 | 21.98 | 147.46 | 0.00 | 0.00 | 0.00 |
March | 73.05 | 0.00 | 73.05 | 50.04 | 108.82 | 0.00 | 0.00 | 0.00 |
April | 93.17 | 1.25 | 91.93 | 85.90 | 63.70 | 0.00 | 0.00 | 0.00 |
May | 100.85 | 6.55 | 94.30 | 118.27 | 40.86 | 0.00 | 0.00 | 0.00 |
June | 114.82 | 19.10 | 95.73 | 178.20 | 22.32 | 0.00 | 0.00 | 0.00 |
July | 105.29 | 8.97 | 96.32 | 177.79 | 10.02 | 0.00 | 0.00 | 0.00 |
August | 97.72 | 2.39 | 95.32 | 151.26 | 13.25 | 0.00 | 0.00 | 0.00 |
September | 78.01 | 0.06 | 77.95 | 103.15 | 32.78 | 0.00 | 0.00 | 0.00 |
October | 58.15 | 0.00 | 58.15 | 48.15 | 76.77 | 0.00 | 0.00 | 0.00 |
November | 49.38 | 0.00 | 49.38 | 16.60 | 124.79 | 0.00 | 0.00 | 0.00 |
December | 39.43 | 0.00 | 39.43 | 2.97 | 173.84 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 76.24 | 3.20 | 73.04 | 80.66 | 81.44 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 39.43 | 0.00 | 39.43 | 2.97 | 10.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 114.82 | 19.10 | 96.32 | 178.20 | 173.84 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 41.45 | 0.00 | 41.45 | 8.84 | 148.90 | 0.00 | 0.00 | 0.00 |
February | 51.81 | 0.00 | 51.81 | 19.66 | 131.93 | 0.00 | 0.00 | 0.00 |
March | 65.36 | 0.00 | 65.36 | 44.77 | 97.36 | 0.00 | 0.00 | 0.00 |
April | 83.36 | 1.12 | 82.25 | 76.85 | 57.00 | 0.00 | 0.00 | 0.00 |
May | 90.23 | 5.86 | 84.37 | 105.82 | 36.56 | 0.00 | 0.00 | 0.00 |
June | 102.73 | 17.08 | 85.65 | 159.43 | 19.97 | 0.00 | 0.00 | 0.00 |
July | 94.20 | 8.03 | 86.17 | 159.07 | 8.96 | 0.00 | 0.00 | 0.00 |
August | 87.43 | 2.14 | 85.29 | 135.33 | 11.85 | 0.00 | 0.00 | 0.00 |
September | 69.79 | 0.05 | 69.74 | 92.29 | 29.33 | 0.00 | 0.00 | 0.00 |
October | 52.03 | 0.00 | 52.03 | 43.08 | 68.68 | 0.00 | 0.00 | 0.00 |
November | 44.18 | 0.00 | 44.18 | 14.85 | 111.64 | 0.00 | 0.00 | 0.00 |
December | 35.28 | 0.00 | 35.28 | 2.66 | 155.52 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 68.21 | 2.86 | 65.35 | 72.16 | 72.86 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 35.28 | 0.00 | 35.28 | 2.66 | 8.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 102.73 | 17.08 | 86.17 | 159.43 | 155.52 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1007.89 | 783.80 | 224.09 | 1156.15 | 431.96 | 0.00 | 0.00 | 0.00 |
February | 993.49 | 727.10 | 266.39 | 1162.78 | 393.75 | 0.00 | 0.00 | 0.00 |
March | 738.75 | 450.79 | 287.96 | 889.22 | 305.39 | 0.00 | 0.00 | 0.00 |
April | 567.37 | 232.51 | 334.85 | 722.03 | 194.60 | 0.00 | 0.00 | 0.00 |
May | 381.84 | 86.38 | 295.46 | 509.33 | 127.88 | 0.00 | 0.00 | 0.00 |
June | 319.21 | 38.33 | 280.88 | 513.35 | 70.62 | 0.00 | 0.00 | 0.00 |
July | 353.35 | 55.44 | 297.90 | 610.74 | 30.55 | 0.00 | 0.00 | 0.00 |
August | 480.67 | 151.60 | 329.07 | 770.01 | 40.67 | 0.00 | 0.00 | 0.00 |
September | 682.37 | 384.11 | 298.26 | 987.31 | 96.24 | 0.00 | 0.00 | 0.00 |
October | 919.32 | 676.23 | 243.09 | 1187.18 | 208.04 | 0.00 | 0.00 | 0.00 |
November | 1037.01 | 798.10 | 238.91 | 1231.00 | 328.92 | 0.00 | 0.00 | 0.00 |
December | 1099.11 | 907.30 | 191.81 | 1268.94 | 441.08 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 713.44 | 439.47 | 273.96 | 915.91 | 221.61 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 319.21 | 38.33 | 191.81 | 509.33 | 30.55 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1099.11 | 907.30 | 334.85 | 1268.94 | 441.08 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.365721E+10 | 0.284409E+10 | 0.813124E+09 | 0.416484E+10 | 0.149934E+10 |
February | 0.325610E+10 | 0.238302E+10 | 0.873079E+09 | 0.378648E+10 | 0.123434E+10 |
March | 0.268063E+10 | 0.163574E+10 | 0.104489E+10 | 0.321832E+10 | 0.106111E+10 |
April | 0.199231E+10 | 0.816477E+09 | 0.117584E+10 | 0.252796E+10 | 0.669891E+09 |
May | 0.138554E+10 | 0.313445E+09 | 0.107209E+10 | 0.183941E+10 | 0.459023E+09 |
June | 0.112091E+10 | 0.134596E+09 | 0.986310E+09 | 0.176755E+10 | 0.250754E+09 |
July | 0.128213E+10 | 0.201175E+09 | 0.108095E+10 | 0.217550E+10 | 0.118264E+09 |
August | 0.174413E+10 | 0.550093E+09 | 0.119404E+10 | 0.275015E+10 | 0.157320E+09 |
September | 0.239615E+10 | 0.134882E+10 | 0.104733E+10 | 0.341499E+10 | 0.355196E+09 |
October | 0.333581E+10 | 0.245376E+10 | 0.882050E+09 | 0.424349E+10 | 0.753662E+09 |
November | 0.364151E+10 | 0.280257E+10 | 0.838938E+09 | 0.427192E+10 | 0.112314E+10 |
December | 0.398823E+10 | 0.329223E+10 | 0.695993E+09 | 0.455707E+10 | 0.153706E+10 |
Annual Sum or Average | 0.304806E+11 | 0.187760E+11 | 0.117046E+11 | 0.387177E+11 | 0.921910E+10 |
Minimum of Months | 0.112091E+10 | 0.134596E+09 | 0.695993E+09 | 0.176755E+10 | 0.118264E+09 |
Maximum of Months | 0.398823E+10 | 0.329223E+10 | 0.119404E+10 | 0.455707E+10 | 0.153706E+10 |
Report: WindowEnergyReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.102985E+11 | 0.800876E+10 | 0.228970E+10 | 0.116920E+11 | 0.422557E+10 |
February | 0.916896E+10 | 0.671042E+10 | 0.245853E+10 | 0.106314E+11 | 0.347794E+10 |
March | 0.754847E+10 | 0.460613E+10 | 0.294234E+10 | 0.902886E+10 | 0.298681E+10 |
April | 0.561022E+10 | 0.229915E+10 | 0.331108E+10 | 0.709147E+10 | 0.188212E+10 |
May | 0.390158E+10 | 0.882641E+09 | 0.301894E+10 | 0.515205E+10 | 0.128908E+10 |
June | 0.315640E+10 | 0.379014E+09 | 0.277738E+10 | 0.495696E+10 | 0.709797E+09 |
July | 0.361039E+10 | 0.566496E+09 | 0.304390E+10 | 0.611477E+10 | 0.347404E+09 |
August | 0.491137E+10 | 0.154903E+10 | 0.336234E+10 | 0.774097E+10 | 0.462749E+09 |
September | 0.674739E+10 | 0.379819E+10 | 0.294920E+10 | 0.961837E+10 | 0.101552E+10 |
October | 0.939343E+10 | 0.690963E+10 | 0.248379E+10 | 0.119370E+11 | 0.213575E+10 |
November | 0.102543E+11 | 0.789186E+10 | 0.236239E+10 | 0.120015E+11 | 0.316585E+10 |
December | 0.112306E+11 | 0.927071E+10 | 0.195987E+10 | 0.127988E+11 | 0.433508E+10 |
Annual Sum or Average | 0.858315E+11 | 0.528720E+11 | 0.329595E+11 | 0.108764E+12 | 0.260337E+11 |
Minimum of Months | 0.315640E+10 | 0.379014E+09 | 0.195987E+10 | 0.495696E+10 | 0.347404E+09 |
Maximum of Months | 0.112306E+11 | 0.927071E+10 | 0.336234E+10 | 0.127988E+11 | 0.433508E+10 |
Report: WindowEnergyReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.133783E+11 | 0.104038E+11 | 0.297446E+10 | 0.155116E+11 | 0.555863E+10 |
February | 0.119110E+11 | 0.871722E+10 | 0.319378E+10 | 0.141122E+11 | 0.457343E+10 |
March | 0.980589E+10 | 0.598362E+10 | 0.382227E+10 | 0.119970E+11 | 0.394907E+10 |
April | 0.728800E+10 | 0.298672E+10 | 0.430128E+10 | 0.943208E+10 | 0.250579E+10 |
May | 0.506838E+10 | 0.114660E+10 | 0.392177E+10 | 0.686370E+10 | 0.174278E+10 |
June | 0.410034E+10 | 0.492361E+09 | 0.360798E+10 | 0.660896E+10 | 0.969302E+09 |
July | 0.469011E+10 | 0.735911E+09 | 0.395420E+10 | 0.815080E+10 | 0.472047E+09 |
August | 0.638014E+10 | 0.201227E+10 | 0.436787E+10 | 0.103218E+11 | 0.610978E+09 |
September | 0.876524E+10 | 0.493407E+10 | 0.383118E+10 | 0.128160E+11 | 0.131323E+10 |
October | 0.122026E+11 | 0.897601E+10 | 0.322659E+10 | 0.158834E+11 | 0.277325E+10 |
November | 0.133209E+11 | 0.102520E+11 | 0.306888E+10 | 0.159457E+11 | 0.414683E+10 |
December | 0.145892E+11 | 0.120432E+11 | 0.254598E+10 | 0.169734E+11 | 0.569666E+10 |
Annual Sum or Average | 0.111500E+12 | 0.686838E+11 | 0.428162E+11 | 0.144617E+12 | 0.343120E+11 |
Minimum of Months | 0.410034E+10 | 0.492361E+09 | 0.254598E+10 | 0.660896E+10 | 0.472047E+09 |
Maximum of Months | 0.145892E+11 | 0.120432E+11 | 0.436787E+10 | 0.169734E+11 | 0.569666E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.723095E+09 | 0.562325E+09 | 0.160770E+09 | 0.828129E+09 | 0.303350E+09 |
February | 0.643788E+09 | 0.471164E+09 | 0.172624E+09 | 0.750072E+09 | 0.251261E+09 |
March | 0.530008E+09 | 0.323413E+09 | 0.206595E+09 | 0.632242E+09 | 0.218485E+09 |
April | 0.393917E+09 | 0.161432E+09 | 0.232486E+09 | 0.490349E+09 | 0.139159E+09 |
May | 0.273947E+09 | 61973527.69 | 0.211974E+09 | 0.352478E+09 | 95699050.82 |
June | 0.221626E+09 | 26612006.93 | 0.195014E+09 | 0.340450E+09 | 52481397.44 |
July | 0.253502E+09 | 39775788.64 | 0.213726E+09 | 0.421842E+09 | 24816770.59 |
August | 0.344848E+09 | 0.108763E+09 | 0.236085E+09 | 0.536810E+09 | 32554604.93 |
September | 0.473762E+09 | 0.266685E+09 | 0.207077E+09 | 0.672940E+09 | 72143319.53 |
October | 0.659549E+09 | 0.485151E+09 | 0.174398E+09 | 0.842170E+09 | 0.152581E+09 |
November | 0.719990E+09 | 0.554116E+09 | 0.165874E+09 | 0.849029E+09 | 0.226881E+09 |
December | 0.788542E+09 | 0.650931E+09 | 0.137611E+09 | 0.908026E+09 | 0.309338E+09 |
Annual Sum or Average | 0.602657E+10 | 0.371234E+10 | 0.231423E+10 | 0.762454E+10 | 0.187875E+10 |
Minimum of Months | 0.221626E+09 | 26612006.93 | 0.137611E+09 | 0.340450E+09 | 24816770.59 |
Maximum of Months | 0.788542E+09 | 0.650931E+09 | 0.236085E+09 | 0.908026E+09 | 0.309338E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.523089E+09 | 0.298319E+09 | 0.224770E+09 | 0.487231E+09 | 0.618185E+09 |
February | 0.606983E+09 | 0.350236E+09 | 0.256747E+09 | 0.606887E+09 | 0.501176E+09 |
March | 0.749847E+09 | 0.398315E+09 | 0.351532E+09 | 0.805702E+09 | 0.420521E+09 |
April | 0.928389E+09 | 0.494100E+09 | 0.434289E+09 | 0.108403E+10 | 0.253962E+09 |
May | 0.912271E+09 | 0.471357E+09 | 0.440913E+09 | 0.114084E+10 | 0.175798E+09 |
June | 0.940717E+09 | 0.523906E+09 | 0.416811E+09 | 0.132355E+10 | 97723303.72 |
July | 0.877654E+09 | 0.428858E+09 | 0.448795E+09 | 0.129959E+10 | 46202141.98 |
August | 0.897753E+09 | 0.414634E+09 | 0.483120E+09 | 0.127696E+10 | 60703777.49 |
September | 0.788271E+09 | 0.416188E+09 | 0.372084E+09 | 0.105138E+10 | 0.135715E+09 |
October | 0.745436E+09 | 0.464315E+09 | 0.281121E+09 | 0.880707E+09 | 0.305164E+09 |
November | 0.563698E+09 | 0.331600E+09 | 0.232098E+09 | 0.558609E+09 | 0.456198E+09 |
December | 0.500176E+09 | 0.312337E+09 | 0.187839E+09 | 0.453769E+09 | 0.633988E+09 |
Annual Sum or Average | 0.903428E+10 | 0.490416E+10 | 0.413012E+10 | 0.109693E+11 | 0.370534E+10 |
Minimum of Months | 0.500176E+09 | 0.298319E+09 | 0.187839E+09 | 0.453769E+09 | 46202141.98 |
Maximum of Months | 0.940717E+09 | 0.523906E+09 | 0.483120E+09 | 0.132355E+10 | 0.633988E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 97981004.79 | 0.00 | 97981004.79 | 27682336.76 | 0.333684E+09 |
February | 0.110609E+09 | 0.00 | 0.110609E+09 | 46612931.17 | 0.270073E+09 |
March | 0.154499E+09 | 5370.55 | 0.154493E+09 | 0.105609E+09 | 0.226061E+09 |
April | 0.190699E+09 | 2554501.35 | 0.188145E+09 | 0.167185E+09 | 0.132830E+09 |
May | 0.213292E+09 | 13858268.08 | 0.199434E+09 | 0.237173E+09 | 89725520.97 |
June | 0.235007E+09 | 39082164.48 | 0.195925E+09 | 0.348156E+09 | 49021067.35 |
July | 0.222682E+09 | 18980349.87 | 0.203701E+09 | 0.359256E+09 | 24017527.39 |
August | 0.206659E+09 | 5057538.87 | 0.201601E+09 | 0.304936E+09 | 30931462.40 |
September | 0.159653E+09 | 113768.03 | 0.159539E+09 | 0.200706E+09 | 70914652.97 |
October | 0.122983E+09 | 0.00 | 0.122983E+09 | 99859370.46 | 0.161875E+09 |
November | 0.101073E+09 | 0.00 | 0.101073E+09 | 38418428.73 | 0.245552E+09 |
December | 83396664.10 | 0.00 | 83396664.10 | 10844420.75 | 0.343586E+09 |
Annual Sum or Average | 0.189853E+10 | 79651961.22 | 0.181888E+10 | 0.194644E+10 | 0.197827E+10 |
Minimum of Months | 83396664.10 | 0.00 | 83396664.10 | 10844420.75 | 24017527.39 |
Maximum of Months | 0.235007E+09 | 39082164.48 | 0.203701E+09 | 0.359256E+09 | 0.343586E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.523089E+09 | 0.298319E+09 | 0.224770E+09 | 0.508493E+09 | 0.604322E+09 |
February | 0.606983E+09 | 0.350236E+09 | 0.256747E+09 | 0.626306E+09 | 0.490013E+09 |
March | 0.749847E+09 | 0.398315E+09 | 0.351532E+09 | 0.821165E+09 | 0.413402E+09 |
April | 0.928389E+09 | 0.494100E+09 | 0.434289E+09 | 0.109318E+10 | 0.251139E+09 |
May | 0.912271E+09 | 0.471357E+09 | 0.440913E+09 | 0.114415E+10 | 0.174885E+09 |
June | 0.940717E+09 | 0.523906E+09 | 0.416811E+09 | 0.132374E+10 | 97408614.37 |
July | 0.877654E+09 | 0.428858E+09 | 0.448795E+09 | 0.130103E+10 | 45810132.65 |
August | 0.897753E+09 | 0.414634E+09 | 0.483120E+09 | 0.128174E+10 | 59564932.92 |
September | 0.788271E+09 | 0.416188E+09 | 0.372084E+09 | 0.106078E+10 | 0.132330E+09 |
October | 0.745436E+09 | 0.464315E+09 | 0.281121E+09 | 0.897432E+09 | 0.297250E+09 |
November | 0.563698E+09 | 0.331600E+09 | 0.232098E+09 | 0.578352E+09 | 0.444024E+09 |
December | 0.500176E+09 | 0.312337E+09 | 0.187839E+09 | 0.475024E+09 | 0.615895E+09 |
Annual Sum or Average | 0.903428E+10 | 0.490416E+10 | 0.413012E+10 | 0.111114E+11 | 0.362604E+10 |
Minimum of Months | 0.500176E+09 | 0.298319E+09 | 0.187839E+09 | 0.475024E+09 | 45810132.65 |
Maximum of Months | 0.940717E+09 | 0.523906E+09 | 0.483120E+09 | 0.132374E+10 | 0.615895E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.578361E+09 | 0.449770E+09 | 0.128590E+09 | 0.652004E+09 | 0.263811E+09 |
February | 0.514928E+09 | 0.376856E+09 | 0.138072E+09 | 0.591081E+09 | 0.221427E+09 |
March | 0.423922E+09 | 0.258679E+09 | 0.165243E+09 | 0.496101E+09 | 0.196865E+09 |
April | 0.315071E+09 | 0.129120E+09 | 0.185952E+09 | 0.385629E+09 | 0.129000E+09 |
May | 0.219114E+09 | 49568964.22 | 0.169545E+09 | 0.275499E+09 | 92779327.46 |
June | 0.177265E+09 | 21285372.45 | 0.155980E+09 | 0.267244E+09 | 53899772.58 |
July | 0.202761E+09 | 31814303.90 | 0.170947E+09 | 0.331707E+09 | 30400395.50 |
August | 0.275824E+09 | 86993003.94 | 0.188831E+09 | 0.423946E+09 | 37967998.04 |
September | 0.378934E+09 | 0.213306E+09 | 0.165628E+09 | 0.532874E+09 | 73748485.78 |
October | 0.527535E+09 | 0.388044E+09 | 0.139491E+09 | 0.664999E+09 | 0.142457E+09 |
November | 0.575878E+09 | 0.443205E+09 | 0.132673E+09 | 0.668281E+09 | 0.206106E+09 |
December | 0.630708E+09 | 0.520641E+09 | 0.110067E+09 | 0.715235E+09 | 0.272530E+09 |
Annual Sum or Average | 0.482030E+10 | 0.296928E+10 | 0.185102E+10 | 0.600460E+10 | 0.172099E+10 |
Minimum of Months | 0.177265E+09 | 21285372.45 | 0.110067E+09 | 0.267244E+09 | 30400395.50 |
Maximum of Months | 0.630708E+09 | 0.520641E+09 | 0.188831E+09 | 0.715235E+09 | 0.272530E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 78395194.18 | 0.00 | 78395194.18 | 20708573.02 | 0.274592E+09 |
February | 88498821.31 | 0.00 | 88498821.31 | 37604407.79 | 0.220394E+09 |
March | 0.123615E+09 | 4297.01 | 0.123611E+09 | 87037622.72 | 0.182891E+09 |
April | 0.152580E+09 | 2043871.97 | 0.150536E+09 | 0.140342E+09 | 0.104838E+09 |
May | 0.170657E+09 | 11088084.06 | 0.159568E+09 | 0.197546E+09 | 70227432.11 |
June | 0.188031E+09 | 31269876.03 | 0.156761E+09 | 0.288889E+09 | 37061616.18 |
July | 0.178169E+09 | 15186292.66 | 0.162983E+09 | 0.298800E+09 | 16763961.93 |
August | 0.165349E+09 | 4046567.42 | 0.161302E+09 | 0.255235E+09 | 21936080.64 |
September | 0.127739E+09 | 91026.49 | 0.127648E+09 | 0.168930E+09 | 53615458.61 |
October | 98399454.57 | 0.00 | 98399454.57 | 84299422.01 | 0.128708E+09 |
November | 80868758.46 | 0.00 | 80868758.46 | 30556325.80 | 0.200559E+09 |
December | 66726175.04 | 0.00 | 66726175.04 | 7500917.73 | 0.283695E+09 |
Annual Sum or Average | 0.151903E+10 | 63730015.63 | 0.145530E+10 | 0.161745E+10 | 0.159528E+10 |
Minimum of Months | 66726175.04 | 0.00 | 66726175.04 | 7500917.73 | 16763961.93 |
Maximum of Months | 0.188031E+09 | 31269876.03 | 0.162983E+09 | 0.298800E+09 | 0.283695E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.507216E+09 | 0.283893E+09 | 0.223323E+09 | 0.429762E+09 | 0.585151E+09 |
February | 0.554793E+09 | 0.298227E+09 | 0.256566E+09 | 0.516103E+09 | 0.476332E+09 |
March | 0.816260E+09 | 0.465022E+09 | 0.351239E+09 | 0.867687E+09 | 0.395310E+09 |
April | 0.107158E+10 | 0.609786E+09 | 0.461789E+09 | 0.126708E+10 | 0.240293E+09 |
May | 0.105785E+10 | 0.602543E+09 | 0.455309E+09 | 0.132958E+10 | 0.168652E+09 |
June | 0.110403E+10 | 0.680041E+09 | 0.423991E+09 | 0.153491E+10 | 90349272.38 |
July | 0.105510E+10 | 0.603154E+09 | 0.451944E+09 | 0.153802E+10 | 44474979.39 |
August | 0.104428E+10 | 0.575590E+09 | 0.468689E+09 | 0.146847E+10 | 57442874.39 |
September | 0.842711E+09 | 0.471538E+09 | 0.371174E+09 | 0.111498E+10 | 0.128097E+09 |
October | 0.758679E+09 | 0.481775E+09 | 0.276904E+09 | 0.877046E+09 | 0.284355E+09 |
November | 0.571024E+09 | 0.334984E+09 | 0.236040E+09 | 0.549598E+09 | 0.439199E+09 |
December | 0.480632E+09 | 0.293171E+09 | 0.187461E+09 | 0.410794E+09 | 0.615651E+09 |
Annual Sum or Average | 0.986415E+10 | 0.569972E+10 | 0.416443E+10 | 0.119040E+11 | 0.352531E+10 |
Minimum of Months | 0.480632E+09 | 0.283893E+09 | 0.187461E+09 | 0.410794E+09 | 44474979.39 |
Maximum of Months | 0.110403E+10 | 0.680041E+09 | 0.468689E+09 | 0.153802E+10 | 0.615651E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.723095E+09 | 0.562325E+09 | 0.160770E+09 | 0.826069E+09 | 0.302012E+09 |
February | 0.643788E+09 | 0.471164E+09 | 0.172624E+09 | 0.748138E+09 | 0.249427E+09 |
March | 0.530008E+09 | 0.323413E+09 | 0.206595E+09 | 0.627614E+09 | 0.217456E+09 |
April | 0.393917E+09 | 0.161432E+09 | 0.232486E+09 | 0.484699E+09 | 0.138540E+09 |
May | 0.273947E+09 | 61973527.69 | 0.211974E+09 | 0.346694E+09 | 95167523.79 |
June | 0.221626E+09 | 26612006.93 | 0.195014E+09 | 0.335931E+09 | 51569965.30 |
July | 0.253502E+09 | 39775788.64 | 0.213726E+09 | 0.417902E+09 | 24574395.61 |
August | 0.344848E+09 | 0.108763E+09 | 0.236085E+09 | 0.533353E+09 | 32058624.87 |
September | 0.473762E+09 | 0.266685E+09 | 0.207077E+09 | 0.670472E+09 | 71215754.25 |
October | 0.659549E+09 | 0.485151E+09 | 0.174398E+09 | 0.839124E+09 | 0.151167E+09 |
November | 0.719990E+09 | 0.554116E+09 | 0.165874E+09 | 0.846467E+09 | 0.225545E+09 |
December | 0.788542E+09 | 0.650931E+09 | 0.137611E+09 | 0.905943E+09 | 0.308004E+09 |
Annual Sum or Average | 0.602657E+10 | 0.371234E+10 | 0.231423E+10 | 0.758241E+10 | 0.186674E+10 |
Minimum of Months | 0.221626E+09 | 26612006.93 | 0.137611E+09 | 0.335931E+09 | 24574395.61 |
Maximum of Months | 0.788542E+09 | 0.650931E+09 | 0.236085E+09 | 0.905943E+09 | 0.308004E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 97981004.79 | 0.00 | 97981004.79 | 25974465.89 | 0.331873E+09 |
February | 0.110609E+09 | 0.00 | 0.110609E+09 | 45204807.70 | 0.268141E+09 |
March | 0.154499E+09 | 5370.55 | 0.154493E+09 | 0.101253E+09 | 0.226837E+09 |
April | 0.190699E+09 | 2554501.35 | 0.188145E+09 | 0.160172E+09 | 0.132498E+09 |
May | 0.213292E+09 | 13858268.08 | 0.199434E+09 | 0.230948E+09 | 89140209.20 |
June | 0.235007E+09 | 39082164.48 | 0.195925E+09 | 0.343611E+09 | 48380418.13 |
July | 0.222682E+09 | 18980349.87 | 0.203701E+09 | 0.355310E+09 | 23872753.33 |
August | 0.206659E+09 | 5057538.87 | 0.201601E+09 | 0.301069E+09 | 30411737.03 |
September | 0.159653E+09 | 113768.03 | 0.159539E+09 | 0.197645E+09 | 70193549.46 |
October | 0.122983E+09 | 0.00 | 0.122983E+09 | 96245038.28 | 0.161287E+09 |
November | 0.101073E+09 | 0.00 | 0.101073E+09 | 36275634.92 | 0.243906E+09 |
December | 83396664.10 | 0.00 | 83396664.10 | 9541810.16 | 0.342067E+09 |
Annual Sum or Average | 0.189853E+10 | 79651961.22 | 0.181888E+10 | 0.190325E+10 | 0.196861E+10 |
Minimum of Months | 83396664.10 | 0.00 | 83396664.10 | 9541810.16 | 23872753.33 |
Maximum of Months | 0.235007E+09 | 39082164.48 | 0.203701E+09 | 0.355310E+09 | 0.342067E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.507216E+09 | 0.283893E+09 | 0.223323E+09 | 0.449569E+09 | 0.567839E+09 |
February | 0.554793E+09 | 0.298227E+09 | 0.256566E+09 | 0.534983E+09 | 0.462879E+09 |
March | 0.816260E+09 | 0.465022E+09 | 0.351239E+09 | 0.880994E+09 | 0.388453E+09 |
April | 0.107158E+10 | 0.609786E+09 | 0.461789E+09 | 0.127393E+10 | 0.237564E+09 |
May | 0.105785E+10 | 0.602543E+09 | 0.455309E+09 | 0.133229E+10 | 0.167781E+09 |
June | 0.110403E+10 | 0.680041E+09 | 0.423991E+09 | 0.153538E+10 | 90285202.54 |
July | 0.105510E+10 | 0.603154E+09 | 0.451944E+09 | 0.153958E+10 | 44159170.54 |
August | 0.104428E+10 | 0.575590E+09 | 0.468689E+09 | 0.147300E+10 | 56377156.10 |
September | 0.842711E+09 | 0.471538E+09 | 0.371174E+09 | 0.112349E+10 | 0.124840E+09 |
October | 0.758679E+09 | 0.481775E+09 | 0.276904E+09 | 0.891509E+09 | 0.276407E+09 |
November | 0.571024E+09 | 0.334984E+09 | 0.236040E+09 | 0.567847E+09 | 0.423720E+09 |
December | 0.480632E+09 | 0.293171E+09 | 0.187461E+09 | 0.426742E+09 | 0.589238E+09 |
Annual Sum or Average | 0.986415E+10 | 0.569972E+10 | 0.416443E+10 | 0.120293E+11 | 0.342954E+10 |
Minimum of Months | 0.480632E+09 | 0.283893E+09 | 0.187461E+09 | 0.426742E+09 | 44159170.54 |
Maximum of Months | 0.110403E+10 | 0.680041E+09 | 0.468689E+09 | 0.153958E+10 | 0.589238E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.124087E+09 | 0.00 | 0.124087E+09 | 29616985.69 | 0.443428E+09 |
February | 0.140079E+09 | 0.00 | 0.140079E+09 | 57420860.42 | 0.354286E+09 |
March | 0.195663E+09 | 6801.46 | 0.195656E+09 | 0.139787E+09 | 0.289558E+09 |
April | 0.241509E+09 | 3235114.78 | 0.238274E+09 | 0.229285E+09 | 0.165051E+09 |
May | 0.270121E+09 | 17550622.12 | 0.252571E+09 | 0.323842E+09 | 0.110098E+09 |
June | 0.297622E+09 | 49495095.36 | 0.248127E+09 | 0.465956E+09 | 59458279.13 |
July | 0.282012E+09 | 24037415.51 | 0.257975E+09 | 0.478008E+09 | 29969514.36 |
August | 0.261720E+09 | 6405053.86 | 0.255315E+09 | 0.406847E+09 | 39173235.66 |
September | 0.202191E+09 | 144080.03 | 0.202047E+09 | 0.270781E+09 | 89570820.24 |
October | 0.155750E+09 | 0.00 | 0.155750E+09 | 0.133182E+09 | 0.208105E+09 |
November | 0.128002E+09 | 0.00 | 0.128002E+09 | 47035411.23 | 0.321483E+09 |
December | 0.105617E+09 | 0.00 | 0.105617E+09 | 9683028.08 | 0.462177E+09 |
Annual Sum or Average | 0.240437E+10 | 0.100874E+09 | 0.230350E+10 | 0.259144E+10 | 0.257236E+10 |
Minimum of Months | 0.105617E+09 | 0.00 | 0.105617E+09 | 9683028.08 | 29969514.36 |
Maximum of Months | 0.297622E+09 | 49495095.36 | 0.257975E+09 | 0.478008E+09 | 0.462177E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 45743517.88 | 0.00 | 45743517.88 | 10918047.27 | 0.163466E+09 |
February | 51638974.26 | 0.00 | 51638974.26 | 21167706.76 | 0.130604E+09 |
March | 72129348.61 | 2507.30 | 72126841.31 | 51531421.91 | 0.106743E+09 |
April | 89030149.10 | 1192597.26 | 87837551.84 | 84524063.42 | 60844649.54 |
May | 99577941.81 | 6469886.03 | 93108055.78 | 0.119382E+09 | 40586572.17 |
June | 0.109716E+09 | 18245941.58 | 91469732.72 | 0.171771E+09 | 21918783.66 |
July | 0.103961E+09 | 8861186.67 | 95100166.05 | 0.176213E+09 | 11048003.93 |
August | 96480877.97 | 2361168.07 | 94119709.91 | 0.149981E+09 | 14440876.70 |
September | 74535836.68 | 53113.86 | 74482722.82 | 99821050.58 | 33019513.18 |
October | 57415983.93 | 0.00 | 57415983.93 | 49096384.49 | 76716293.17 |
November | 47186840.17 | 0.00 | 47186840.17 | 17339200.16 | 0.118512E+09 |
December | 38934656.81 | 0.00 | 38934656.81 | 3569565.09 | 0.170378E+09 |
Annual Sum or Average | 0.886351E+09 | 37186400.77 | 0.849165E+09 | 0.955314E+09 | 0.948277E+09 |
Minimum of Months | 38934656.81 | 0.00 | 38934656.81 | 3569565.09 | 11048003.93 |
Maximum of Months | 0.109716E+09 | 18245941.58 | 95100166.05 | 0.176213E+09 | 0.170378E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.337393E+09 | 0.262378E+09 | 75014586.89 | 0.390105E+09 | 0.144177E+09 |
February | 0.300389E+09 | 0.219843E+09 | 80545831.06 | 0.354693E+09 | 0.118523E+09 |
March | 0.247300E+09 | 0.150903E+09 | 96396323.39 | 0.301100E+09 | 0.101509E+09 |
April | 0.183800E+09 | 75323316.63 | 0.108477E+09 | 0.237235E+09 | 62915064.14 |
May | 0.127823E+09 | 28916598.29 | 98906174.13 | 0.173497E+09 | 42914535.99 |
June | 0.103410E+09 | 12417055.19 | 90992515.30 | 0.167850E+09 | 23522293.19 |
July | 0.118283E+09 | 18559222.69 | 99723891.11 | 0.205482E+09 | 11366651.37 |
August | 0.160905E+09 | 50748321.82 | 0.110156E+09 | 0.259123E+09 | 14984919.31 |
September | 0.221055E+09 | 0.124434E+09 | 96621084.81 | 0.322141E+09 | 32783780.64 |
October | 0.307743E+09 | 0.226370E+09 | 81373553.20 | 0.400114E+09 | 70504463.78 |
November | 0.335945E+09 | 0.258549E+09 | 77396069.05 | 0.401787E+09 | 0.106205E+09 |
December | 0.367930E+09 | 0.303722E+09 | 64208705.21 | 0.427662E+09 | 0.147380E+09 |
Annual Sum or Average | 0.281198E+10 | 0.173216E+10 | 0.107981E+10 | 0.364079E+10 | 0.876784E+09 |
Minimum of Months | 0.103410E+09 | 12417055.19 | 64208705.21 | 0.167850E+09 | 11366651.37 |
Maximum of Months | 0.367930E+09 | 0.303722E+09 | 0.110156E+09 | 0.427662E+09 | 0.147380E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.915754E+09 | 0.712149E+09 | 0.203605E+09 | 0.105883E+10 | 0.391325E+09 |
February | 0.815317E+09 | 0.596699E+09 | 0.218618E+09 | 0.962708E+09 | 0.321695E+09 |
March | 0.671222E+09 | 0.409583E+09 | 0.261639E+09 | 0.817246E+09 | 0.275517E+09 |
April | 0.498871E+09 | 0.204443E+09 | 0.294428E+09 | 0.643905E+09 | 0.170764E+09 |
May | 0.346937E+09 | 78485562.51 | 0.268452E+09 | 0.470906E+09 | 0.116479E+09 |
June | 0.280675E+09 | 33702427.65 | 0.246972E+09 | 0.455580E+09 | 63844315.10 |
July | 0.321045E+09 | 50373526.60 | 0.270671E+09 | 0.557720E+09 | 30851416.83 |
August | 0.436728E+09 | 0.137741E+09 | 0.298987E+09 | 0.703314E+09 | 40672128.24 |
September | 0.599989E+09 | 0.337740E+09 | 0.262249E+09 | 0.874357E+09 | 88981886.44 |
October | 0.835278E+09 | 0.614413E+09 | 0.220864E+09 | 0.108599E+10 | 0.191364E+09 |
November | 0.911822E+09 | 0.701754E+09 | 0.210069E+09 | 0.109053E+10 | 0.288262E+09 |
December | 0.998639E+09 | 0.824363E+09 | 0.174276E+09 | 0.116076E+10 | 0.400018E+09 |
Annual Sum or Average | 0.763228E+10 | 0.470145E+10 | 0.293083E+10 | 0.988185E+10 | 0.237977E+10 |
Minimum of Months | 0.280675E+09 | 33702427.65 | 0.174276E+09 | 0.455580E+09 | 30851416.83 |
Maximum of Months | 0.998639E+09 | 0.824363E+09 | 0.298987E+09 | 0.116076E+10 | 0.400018E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.723095E+09 | 0.562325E+09 | 0.160770E+09 | 0.825339E+09 | 0.301694E+09 |
February | 0.643788E+09 | 0.471164E+09 | 0.172624E+09 | 0.746630E+09 | 0.250327E+09 |
March | 0.530008E+09 | 0.323413E+09 | 0.206595E+09 | 0.627883E+09 | 0.218050E+09 |
April | 0.393917E+09 | 0.161432E+09 | 0.232486E+09 | 0.484949E+09 | 0.139044E+09 |
May | 0.273947E+09 | 61973527.69 | 0.211974E+09 | 0.347191E+09 | 95722088.92 |
June | 0.221626E+09 | 26612006.93 | 0.195014E+09 | 0.335897E+09 | 52472336.47 |
July | 0.253502E+09 | 39775788.64 | 0.213726E+09 | 0.416648E+09 | 24814460.43 |
August | 0.344848E+09 | 0.108763E+09 | 0.236085E+09 | 0.530903E+09 | 32656035.57 |
September | 0.473762E+09 | 0.266685E+09 | 0.207077E+09 | 0.667253E+09 | 72203720.84 |
October | 0.659549E+09 | 0.485151E+09 | 0.174398E+09 | 0.837686E+09 | 0.152126E+09 |
November | 0.719990E+09 | 0.554116E+09 | 0.165874E+09 | 0.845782E+09 | 0.225538E+09 |
December | 0.788542E+09 | 0.650931E+09 | 0.137611E+09 | 0.905770E+09 | 0.307081E+09 |
Annual Sum or Average | 0.602657E+10 | 0.371234E+10 | 0.231423E+10 | 0.757193E+10 | 0.187173E+10 |
Minimum of Months | 0.221626E+09 | 26612006.93 | 0.137611E+09 | 0.335897E+09 | 24814460.43 |
Maximum of Months | 0.788542E+09 | 0.650931E+09 | 0.236085E+09 | 0.905770E+09 | 0.307081E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.523089E+09 | 0.298319E+09 | 0.224770E+09 | 0.483858E+09 | 0.613794E+09 |
February | 0.606983E+09 | 0.350236E+09 | 0.256747E+09 | 0.601667E+09 | 0.499052E+09 |
March | 0.749847E+09 | 0.398315E+09 | 0.351532E+09 | 0.798111E+09 | 0.419150E+09 |
April | 0.928389E+09 | 0.494100E+09 | 0.434289E+09 | 0.107262E+10 | 0.253277E+09 |
May | 0.912271E+09 | 0.471357E+09 | 0.440913E+09 | 0.112860E+10 | 0.175663E+09 |
June | 0.940717E+09 | 0.523906E+09 | 0.416811E+09 | 0.131215E+10 | 97877193.12 |
July | 0.877654E+09 | 0.428858E+09 | 0.448795E+09 | 0.128786E+10 | 46272983.00 |
August | 0.897753E+09 | 0.414634E+09 | 0.483120E+09 | 0.126537E+10 | 60948039.50 |
September | 0.788271E+09 | 0.416188E+09 | 0.372084E+09 | 0.104195E+10 | 0.135792E+09 |
October | 0.745436E+09 | 0.464315E+09 | 0.281121E+09 | 0.873573E+09 | 0.303687E+09 |
November | 0.563698E+09 | 0.331600E+09 | 0.232098E+09 | 0.554015E+09 | 0.452678E+09 |
December | 0.500176E+09 | 0.312337E+09 | 0.187839E+09 | 0.450753E+09 | 0.628161E+09 |
Annual Sum or Average | 0.903428E+10 | 0.490416E+10 | 0.413012E+10 | 0.108705E+11 | 0.368635E+10 |
Minimum of Months | 0.500176E+09 | 0.298319E+09 | 0.187839E+09 | 0.450753E+09 | 46272983.00 |
Maximum of Months | 0.940717E+09 | 0.523906E+09 | 0.483120E+09 | 0.131215E+10 | 0.628161E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 97981004.79 | 0.00 | 97981004.79 | 28210639.97 | 0.331187E+09 |
February | 0.110609E+09 | 0.00 | 0.110609E+09 | 46363047.12 | 0.268880E+09 |
March | 0.154499E+09 | 5370.55 | 0.154493E+09 | 0.104184E+09 | 0.225321E+09 |
April | 0.190699E+09 | 2554501.35 | 0.188145E+09 | 0.163511E+09 | 0.132680E+09 |
May | 0.213292E+09 | 13858268.08 | 0.199434E+09 | 0.232521E+09 | 89717521.33 |
June | 0.235007E+09 | 39082164.48 | 0.195925E+09 | 0.343427E+09 | 49200070.37 |
July | 0.222682E+09 | 18980349.87 | 0.203701E+09 | 0.354578E+09 | 24030824.88 |
August | 0.206659E+09 | 5057538.87 | 0.201601E+09 | 0.300370E+09 | 31021658.40 |
September | 0.159653E+09 | 113768.03 | 0.159539E+09 | 0.197345E+09 | 70925346.07 |
October | 0.122983E+09 | 0.00 | 0.122983E+09 | 98019864.97 | 0.160989E+09 |
November | 0.101073E+09 | 0.00 | 0.101073E+09 | 38340793.90 | 0.243465E+09 |
December | 83396664.10 | 0.00 | 83396664.10 | 11260406.43 | 0.340192E+09 |
Annual Sum or Average | 0.189853E+10 | 79651961.22 | 0.181888E+10 | 0.191813E+10 | 0.196761E+10 |
Minimum of Months | 83396664.10 | 0.00 | 83396664.10 | 11260406.43 | 24030824.88 |
Maximum of Months | 0.235007E+09 | 39082164.48 | 0.203701E+09 | 0.354578E+09 | 0.340192E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.523089E+09 | 0.298319E+09 | 0.224770E+09 | 0.507101E+09 | 0.599386E+09 |
February | 0.606983E+09 | 0.350236E+09 | 0.256747E+09 | 0.622614E+09 | 0.487280E+09 |
March | 0.749847E+09 | 0.398315E+09 | 0.351532E+09 | 0.814310E+09 | 0.411618E+09 |
April | 0.928389E+09 | 0.494100E+09 | 0.434289E+09 | 0.108148E+10 | 0.250404E+09 |
May | 0.912271E+09 | 0.471357E+09 | 0.440913E+09 | 0.113170E+10 | 0.174768E+09 |
June | 0.940717E+09 | 0.523906E+09 | 0.416811E+09 | 0.131229E+10 | 97579964.99 |
July | 0.877654E+09 | 0.428858E+09 | 0.448795E+09 | 0.128927E+10 | 45883889.22 |
August | 0.897753E+09 | 0.414634E+09 | 0.483120E+09 | 0.127017E+10 | 59780675.94 |
September | 0.788271E+09 | 0.416188E+09 | 0.372084E+09 | 0.105125E+10 | 0.132298E+09 |
October | 0.745436E+09 | 0.464315E+09 | 0.281121E+09 | 0.890740E+09 | 0.295314E+09 |
November | 0.563698E+09 | 0.331600E+09 | 0.232098E+09 | 0.575683E+09 | 0.439334E+09 |
December | 0.500176E+09 | 0.312337E+09 | 0.187839E+09 | 0.474372E+09 | 0.609705E+09 |
Annual Sum or Average | 0.903428E+10 | 0.490416E+10 | 0.413012E+10 | 0.110210E+11 | 0.360335E+10 |
Minimum of Months | 0.500176E+09 | 0.298319E+09 | 0.187839E+09 | 0.474372E+09 | 45883889.22 |
Maximum of Months | 0.940717E+09 | 0.523906E+09 | 0.483120E+09 | 0.131229E+10 | 0.609705E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.106049E+10 | 0.824703E+09 | 0.235784E+09 | 0.119012E+10 | 0.459350E+09 |
February | 0.944177E+09 | 0.691007E+09 | 0.253170E+09 | 0.107996E+10 | 0.379030E+09 |
March | 0.777308E+09 | 0.474317E+09 | 0.302991E+09 | 0.911808E+09 | 0.325604E+09 |
April | 0.577717E+09 | 0.236755E+09 | 0.340963E+09 | 0.712205E+09 | 0.201782E+09 |
May | 0.401770E+09 | 90890125.98 | 0.310880E+09 | 0.516000E+09 | 0.136642E+09 |
June | 0.325035E+09 | 39029062.12 | 0.286006E+09 | 0.505678E+09 | 72873556.29 |
July | 0.371785E+09 | 58335011.33 | 0.313450E+09 | 0.623844E+09 | 33140602.75 |
August | 0.505753E+09 | 0.159511E+09 | 0.346242E+09 | 0.788140E+09 | 44677079.81 |
September | 0.694817E+09 | 0.391119E+09 | 0.303698E+09 | 0.979752E+09 | 0.104192E+09 |
October | 0.967293E+09 | 0.711521E+09 | 0.255772E+09 | 0.122035E+10 | 0.227271E+09 |
November | 0.105593E+10 | 0.812665E+09 | 0.243270E+09 | 0.122448E+10 | 0.342846E+09 |
December | 0.115647E+10 | 0.954653E+09 | 0.201820E+09 | 0.130662E+10 | 0.469402E+09 |
Annual Sum or Average | 0.883855E+10 | 0.544450E+10 | 0.339405E+10 | 0.110589E+11 | 0.279681E+10 |
Minimum of Months | 0.325035E+09 | 39029062.12 | 0.201820E+09 | 0.505678E+09 | 33140602.75 |
Maximum of Months | 0.115647E+10 | 0.954653E+09 | 0.346242E+09 | 0.130662E+10 | 0.469402E+09 |
Report: WindowEnergyReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.685841E+09 | 0.00 | 0.685841E+09 | 0.161712E+09 | 0.242860E+10 |
February | 0.774233E+09 | 0.00 | 0.774233E+09 | 0.310825E+09 | 0.195301E+10 |
March | 0.108145E+10 | 37592.41 | 0.108141E+10 | 0.753005E+09 | 0.162048E+10 |
April | 0.133485E+10 | 17880832.21 | 0.131696E+10 | 0.123757E+10 | 0.941457E+09 |
May | 0.149299E+10 | 97004202.60 | 0.139599E+10 | 0.174755E+10 | 0.647774E+09 |
June | 0.164499E+10 | 0.273565E+09 | 0.137142E+10 | 0.254991E+10 | 0.360004E+09 |
July | 0.155871E+10 | 0.132857E+09 | 0.142585E+10 | 0.264045E+10 | 0.187462E+09 |
August | 0.144656E+10 | 35401431.26 | 0.141115E+10 | 0.225940E+10 | 0.237065E+09 |
September | 0.111753E+10 | 796346.02 | 0.111673E+10 | 0.150681E+10 | 0.505691E+09 |
October | 0.860849E+09 | 0.00 | 0.860849E+09 | 0.742236E+09 | 0.114740E+10 |
November | 0.707481E+09 | 0.00 | 0.707481E+09 | 0.254933E+09 | 0.176794E+10 |
December | 0.583755E+09 | 0.00 | 0.583755E+09 | 53597221.77 | 0.252252E+10 |
Annual Sum or Average | 0.132892E+11 | 0.557543E+09 | 0.127317E+11 | 0.142180E+11 | 0.143194E+11 |
Minimum of Months | 0.583755E+09 | 0.00 | 0.583755E+09 | 53597221.77 | 0.187462E+09 |
Maximum of Months | 0.164499E+10 | 0.273565E+09 | 0.142585E+10 | 0.264045E+10 | 0.252252E+10 |
Report: WindowEnergyReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.685841E+09 | 0.00 | 0.685841E+09 | 0.154015E+09 | 0.246291E+10 |
February | 0.774233E+09 | 0.00 | 0.774233E+09 | 0.301649E+09 | 0.198266E+10 |
March | 0.108145E+10 | 37592.41 | 0.108141E+10 | 0.737912E+09 | 0.165172E+10 |
April | 0.133485E+10 | 17880832.21 | 0.131696E+10 | 0.121565E+10 | 0.967180E+09 |
May | 0.149299E+10 | 97004202.60 | 0.139599E+10 | 0.171981E+10 | 0.671374E+09 |
June | 0.164499E+10 | 0.273565E+09 | 0.137142E+10 | 0.251920E+10 | 0.378339E+09 |
July | 0.155871E+10 | 0.132857E+09 | 0.142585E+10 | 0.260828E+10 | 0.203831E+09 |
August | 0.144656E+10 | 35401431.26 | 0.141115E+10 | 0.222983E+10 | 0.254946E+09 |
September | 0.111753E+10 | 796346.02 | 0.111673E+10 | 0.148565E+10 | 0.529974E+09 |
October | 0.860849E+09 | 0.00 | 0.860849E+09 | 0.727532E+09 | 0.117760E+10 |
November | 0.707481E+09 | 0.00 | 0.707481E+09 | 0.245580E+09 | 0.180040E+10 |
December | 0.583755E+09 | 0.00 | 0.583755E+09 | 49675758.57 | 0.255966E+10 |
Annual Sum or Average | 0.132892E+11 | 0.557543E+09 | 0.127317E+11 | 0.139948E+11 | 0.146406E+11 |
Minimum of Months | 0.583755E+09 | 0.00 | 0.583755E+09 | 49675758.57 | 0.203831E+09 |
Maximum of Months | 0.164499E+10 | 0.273565E+09 | 0.142585E+10 | 0.260828E+10 | 0.255966E+10 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 97981004.79 | 0.00 | 97981004.79 | 35421889.22 | 0.323673E+09 |
February | 0.110609E+09 | 0.00 | 0.110609E+09 | 57604750.33 | 0.264141E+09 |
March | 0.154499E+09 | 5370.55 | 0.154493E+09 | 0.127282E+09 | 0.223244E+09 |
April | 0.190699E+09 | 2554501.35 | 0.188145E+09 | 0.203112E+09 | 0.132588E+09 |
May | 0.213292E+09 | 13858268.08 | 0.199434E+09 | 0.283482E+09 | 93174360.71 |
June | 0.235007E+09 | 39082164.48 | 0.195925E+09 | 0.404778E+09 | 53143922.57 |
July | 0.222682E+09 | 18980349.87 | 0.203701E+09 | 0.420888E+09 | 28003746.64 |
August | 0.206659E+09 | 5057538.87 | 0.201601E+09 | 0.364785E+09 | 34500148.85 |
September | 0.159653E+09 | 113768.03 | 0.159539E+09 | 0.248885E+09 | 68742163.14 |
October | 0.122983E+09 | 0.00 | 0.122983E+09 | 0.129657E+09 | 0.154222E+09 |
November | 0.101073E+09 | 0.00 | 0.101073E+09 | 49805044.40 | 0.234320E+09 |
December | 83396664.10 | 0.00 | 83396664.10 | 14829835.95 | 0.331525E+09 |
Annual Sum or Average | 0.189853E+10 | 79651961.22 | 0.181888E+10 | 0.234053E+10 | 0.194128E+10 |
Minimum of Months | 83396664.10 | 0.00 | 83396664.10 | 14829835.95 | 28003746.64 |
Maximum of Months | 0.235007E+09 | 39082164.48 | 0.203701E+09 | 0.420888E+09 | 0.331525E+09 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.101436E+10 | 0.567746E+09 | 0.446614E+09 | 0.962822E+09 | 0.112376E+10 |
February | 0.110951E+10 | 0.596411E+09 | 0.513096E+09 | 0.114178E+10 | 0.923216E+09 |
March | 0.163240E+10 | 0.929977E+09 | 0.702427E+09 | 0.188689E+10 | 0.781926E+09 |
April | 0.214300E+10 | 0.121949E+10 | 0.923513E+09 | 0.272613E+10 | 0.486429E+09 |
May | 0.211555E+10 | 0.120500E+10 | 0.910554E+09 | 0.286478E+10 | 0.351359E+09 |
June | 0.220791E+10 | 0.135999E+10 | 0.847922E+09 | 0.329582E+10 | 0.199277E+09 |
July | 0.211005E+10 | 0.120622E+10 | 0.903823E+09 | 0.332289E+10 | 0.105239E+09 |
August | 0.208841E+10 | 0.115110E+10 | 0.937312E+09 | 0.318273E+10 | 0.130157E+09 |
September | 0.168530E+10 | 0.943008E+09 | 0.742295E+09 | 0.244701E+10 | 0.254238E+09 |
October | 0.151725E+10 | 0.963481E+09 | 0.553769E+09 | 0.193525E+10 | 0.544011E+09 |
November | 0.114197E+10 | 0.669921E+09 | 0.472046E+09 | 0.121552E+10 | 0.827980E+09 |
December | 0.961196E+09 | 0.586300E+09 | 0.374896E+09 | 0.904895E+09 | 0.115846E+10 |
Annual Sum or Average | 0.197269E+11 | 0.113986E+11 | 0.832827E+10 | 0.258865E+11 | 0.688605E+10 |
Minimum of Months | 0.961196E+09 | 0.567746E+09 | 0.374896E+09 | 0.904895E+09 | 0.105239E+09 |
Maximum of Months | 0.220791E+10 | 0.135999E+10 | 0.937312E+09 | 0.332289E+10 | 0.115846E+10 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.723095E+09 | 0.562325E+09 | 0.160770E+09 | 0.863673E+09 | 0.293938E+09 |
February | 0.643788E+09 | 0.471164E+09 | 0.172624E+09 | 0.783955E+09 | 0.243703E+09 |
March | 0.530008E+09 | 0.323413E+09 | 0.206595E+09 | 0.668333E+09 | 0.213653E+09 |
April | 0.393917E+09 | 0.161432E+09 | 0.232486E+09 | 0.531181E+09 | 0.136427E+09 |
May | 0.273947E+09 | 61973527.69 | 0.211974E+09 | 0.398863E+09 | 96872482.28 |
June | 0.221626E+09 | 26612006.93 | 0.195014E+09 | 0.394284E+09 | 55087280.85 |
July | 0.253502E+09 | 39775788.64 | 0.213726E+09 | 0.482960E+09 | 28080240.86 |
August | 0.344848E+09 | 0.108763E+09 | 0.236085E+09 | 0.598361E+09 | 34924744.46 |
September | 0.473762E+09 | 0.266685E+09 | 0.207077E+09 | 0.727043E+09 | 68725405.53 |
October | 0.659549E+09 | 0.485151E+09 | 0.174398E+09 | 0.890299E+09 | 0.144934E+09 |
November | 0.719990E+09 | 0.554116E+09 | 0.165874E+09 | 0.887901E+09 | 0.216742E+09 |
December | 0.788542E+09 | 0.650931E+09 | 0.137611E+09 | 0.943610E+09 | 0.297274E+09 |
Annual Sum or Average | 0.602657E+10 | 0.371234E+10 | 0.231423E+10 | 0.817046E+10 | 0.183036E+10 |
Minimum of Months | 0.221626E+09 | 26612006.93 | 0.137611E+09 | 0.394284E+09 | 28080240.86 |
Maximum of Months | 0.788542E+09 | 0.650931E+09 | 0.236085E+09 | 0.943610E+09 | 0.297274E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.124087E+09 | 0.00 | 0.124087E+09 | 26455911.04 | 0.445844E+09 |
February | 0.140079E+09 | 0.00 | 0.140079E+09 | 53170529.47 | 0.356735E+09 |
March | 0.195663E+09 | 6801.46 | 0.195656E+09 | 0.134016E+09 | 0.291471E+09 |
April | 0.241509E+09 | 3235114.78 | 0.238274E+09 | 0.222651E+09 | 0.165119E+09 |
May | 0.270121E+09 | 17550622.12 | 0.252571E+09 | 0.316780E+09 | 0.109436E+09 |
June | 0.297622E+09 | 49495095.36 | 0.248127E+09 | 0.461882E+09 | 57851096.18 |
July | 0.282012E+09 | 24037415.51 | 0.257975E+09 | 0.476199E+09 | 26828430.95 |
August | 0.261720E+09 | 6405053.86 | 0.255315E+09 | 0.405122E+09 | 35486901.69 |
September | 0.202191E+09 | 144080.03 | 0.202047E+09 | 0.267354E+09 | 84959797.11 |
October | 0.155750E+09 | 0.00 | 0.155750E+09 | 0.128972E+09 | 0.205615E+09 |
November | 0.128002E+09 | 0.00 | 0.128002E+09 | 43018699.34 | 0.323453E+09 |
December | 0.105617E+09 | 0.00 | 0.105617E+09 | 7952194.72 | 0.465618E+09 |
Annual Sum or Average | 0.240437E+10 | 0.100874E+09 | 0.230350E+10 | 0.254357E+10 | 0.256842E+10 |
Minimum of Months | 0.105617E+09 | 0.00 | 0.105617E+09 | 7952194.72 | 26828430.95 |
Maximum of Months | 0.297622E+09 | 49495095.36 | 0.257975E+09 | 0.476199E+09 | 0.465618E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.111021E+09 | 0.00 | 0.111021E+09 | 23670203.85 | 0.398824E+09 |
February | 0.125329E+09 | 0.00 | 0.125329E+09 | 47571874.17 | 0.319175E+09 |
March | 0.175060E+09 | 6085.29 | 0.175054E+09 | 0.119904E+09 | 0.260780E+09 |
April | 0.216079E+09 | 2894469.45 | 0.213184E+09 | 0.199207E+09 | 0.147732E+09 |
May | 0.241679E+09 | 15702608.11 | 0.225976E+09 | 0.283424E+09 | 97912425.22 |
June | 0.266283E+09 | 44283449.36 | 0.222000E+09 | 0.413248E+09 | 51759594.95 |
July | 0.252317E+09 | 21506366.74 | 0.230811E+09 | 0.426057E+09 | 24003498.82 |
August | 0.234162E+09 | 5730625.96 | 0.228431E+09 | 0.362464E+09 | 31750265.40 |
September | 0.180901E+09 | 128908.95 | 0.180772E+09 | 0.239203E+09 | 76013852.39 |
October | 0.139350E+09 | 0.00 | 0.139350E+09 | 0.115392E+09 | 0.183964E+09 |
November | 0.114524E+09 | 0.00 | 0.114524E+09 | 38488993.30 | 0.289375E+09 |
December | 94495583.87 | 0.00 | 94495583.87 | 7114858.74 | 0.416555E+09 |
Annual Sum or Average | 0.215120E+10 | 90252513.85 | 0.206095E+10 | 0.227575E+10 | 0.229785E+10 |
Minimum of Months | 94495583.87 | 0.00 | 94495583.87 | 7114858.74 | 24003498.82 |
Maximum of Months | 0.266283E+09 | 44283449.36 | 0.230811E+09 | 0.426057E+09 | 0.416555E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.269953E+10 | 0.209933E+10 | 0.600202E+09 | 0.309663E+10 | 0.115696E+10 |
February | 0.240345E+10 | 0.175899E+10 | 0.644458E+09 | 0.281300E+10 | 0.952554E+09 |
March | 0.197868E+10 | 0.120740E+10 | 0.771280E+09 | 0.238169E+10 | 0.817952E+09 |
April | 0.147061E+10 | 0.602672E+09 | 0.867938E+09 | 0.187151E+10 | 0.504396E+09 |
May | 0.102273E+10 | 0.231366E+09 | 0.791362E+09 | 0.136420E+10 | 0.342510E+09 |
June | 0.827394E+09 | 99350551.84 | 0.728044E+09 | 0.133061E+10 | 0.183054E+09 |
July | 0.946399E+09 | 0.148495E+09 | 0.797904E+09 | 0.163580E+10 | 81828283.12 |
August | 0.128742E+10 | 0.406044E+09 | 0.881376E+09 | 0.206239E+10 | 0.108937E+09 |
September | 0.176869E+10 | 0.995615E+09 | 0.773078E+09 | 0.255911E+10 | 0.249465E+09 |
October | 0.246229E+10 | 0.181121E+10 | 0.651081E+09 | 0.317973E+10 | 0.557207E+09 |
November | 0.268794E+10 | 0.206868E+10 | 0.619257E+09 | 0.319075E+10 | 0.852548E+09 |
December | 0.294386E+10 | 0.243012E+10 | 0.513743E+09 | 0.339874E+10 | 0.118139E+10 |
Annual Sum or Average | 0.224990E+11 | 0.138593E+11 | 0.863972E+10 | 0.288841E+11 | 0.698879E+10 |
Minimum of Months | 0.827394E+09 | 99350551.84 | 0.513743E+09 | 0.133061E+10 | 81828283.12 |
Maximum of Months | 0.294386E+10 | 0.243012E+10 | 0.881376E+09 | 0.339874E+10 | 0.118139E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1554.97 | 559.79 | 1365.45 | 1061.86 | 303.59 | 0.00 | 0.00 |
February | 1565.18 | 510.23 | 1345.94 | 985.04 | 360.90 | 0.00 | 0.00 |
March | 1201.58 | 396.17 | 1000.83 | 610.71 | 390.12 | 0.00 | 0.00 |
April | 975.29 | 258.45 | 768.64 | 315.00 | 453.64 | 0.00 | 0.00 |
May | 686.76 | 171.38 | 517.30 | 117.03 | 400.27 | 0.00 | 0.00 |
June | 681.93 | 96.74 | 432.45 | 51.93 | 380.52 | 0.00 | 0.00 |
July | 812.24 | 44.15 | 478.69 | 75.11 | 403.58 | 0.00 | 0.00 |
August | 1026.79 | 58.74 | 651.18 | 205.38 | 445.80 | 0.00 | 0.00 |
September | 1317.51 | 137.04 | 924.44 | 520.38 | 404.06 | 0.00 | 0.00 |
October | 1584.34 | 281.38 | 1245.45 | 916.13 | 329.32 | 0.00 | 0.00 |
November | 1648.12 | 433.31 | 1404.90 | 1081.24 | 323.66 | 0.00 | 0.00 |
December | 1701.41 | 573.87 | 1489.03 | 1229.18 | 259.85 | 0.00 | 0.00 |
Annual Sum or Average | 1227.73 | 292.34 | 966.54 | 595.38 | 371.15 | 0.00 | 0.00 |
Minimum of Months | 681.93 | 44.15 | 432.45 | 51.93 | 259.85 | 0.00 | 0.00 |
Maximum of Months | 1701.41 | 573.87 | 1489.03 | 1229.18 | 453.64 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 4365.28 | 1577.65 | 3845.01 | 2990.13 | 854.88 | 0.00 | 0.00 |
February | 4394.59 | 1437.64 | 3790.08 | 2773.82 | 1016.26 | 0.00 | 0.00 |
March | 3370.99 | 1115.15 | 2818.28 | 1719.73 | 1098.54 | 0.00 | 0.00 |
April | 2735.91 | 726.13 | 2164.44 | 887.02 | 1277.42 | 0.00 | 0.00 |
May | 1923.56 | 481.29 | 1456.68 | 329.54 | 1127.14 | 0.00 | 0.00 |
June | 1912.41 | 273.84 | 1217.75 | 146.22 | 1071.52 | 0.00 | 0.00 |
July | 2282.99 | 129.71 | 1347.97 | 211.51 | 1136.46 | 0.00 | 0.00 |
August | 2890.15 | 172.77 | 1833.69 | 578.34 | 1255.35 | 0.00 | 0.00 |
September | 3710.79 | 391.79 | 2603.16 | 1465.35 | 1137.81 | 0.00 | 0.00 |
October | 4456.78 | 797.40 | 3507.10 | 2579.76 | 927.34 | 0.00 | 0.00 |
November | 4630.22 | 1221.39 | 3956.12 | 3044.70 | 911.42 | 0.00 | 0.00 |
December | 4778.52 | 1618.53 | 4193.02 | 3461.29 | 731.73 | 0.00 | 0.00 |
Annual Sum or Average | 3448.89 | 825.52 | 2721.70 | 1676.56 | 1045.14 | 0.00 | 0.00 |
Minimum of Months | 1912.41 | 129.71 | 1217.75 | 146.22 | 731.73 | 0.00 | 0.00 |
Maximum of Months | 4778.52 | 1618.53 | 4193.02 | 3461.29 | 1277.42 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 5791.38 | 2075.35 | 4994.88 | 3884.35 | 1110.53 | 0.00 | 0.00 |
February | 5833.43 | 1890.47 | 4923.53 | 3603.35 | 1320.18 | 0.00 | 0.00 |
March | 4479.19 | 1474.41 | 3661.10 | 2234.03 | 1427.07 | 0.00 | 0.00 |
April | 3638.92 | 966.74 | 2811.73 | 1152.28 | 1659.44 | 0.00 | 0.00 |
May | 2562.61 | 650.68 | 1892.31 | 428.09 | 1464.22 | 0.00 | 0.00 |
June | 2549.75 | 373.96 | 1581.92 | 189.95 | 1391.97 | 0.00 | 0.00 |
July | 3043.16 | 176.24 | 1751.09 | 274.76 | 1476.33 | 0.00 | 0.00 |
August | 3853.73 | 228.11 | 2382.07 | 751.30 | 1630.78 | 0.00 | 0.00 |
September | 4944.43 | 506.65 | 3381.65 | 1903.57 | 1478.08 | 0.00 | 0.00 |
October | 5930.19 | 1035.41 | 4555.93 | 3351.26 | 1204.67 | 0.00 | 0.00 |
November | 6151.90 | 1599.86 | 5139.22 | 3955.24 | 1183.98 | 0.00 | 0.00 |
December | 6337.13 | 2126.89 | 5446.97 | 4496.41 | 950.56 | 0.00 | 0.00 |
Annual Sum or Average | 4585.77 | 1088.03 | 3535.64 | 2177.95 | 1357.69 | 0.00 | 0.00 |
Minimum of Months | 2549.75 | 176.24 | 1581.92 | 189.95 | 950.56 | 0.00 | 0.00 |
Maximum of Months | 6337.13 | 2126.89 | 5446.97 | 4496.41 | 1659.44 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 478.34 | 331.31 | 465.27 | 321.33 | 143.94 | 0.00 | 0.00 |
February | 552.87 | 302.98 | 517.02 | 339.53 | 177.48 | 0.00 | 0.00 |
March | 532.95 | 234.66 | 477.84 | 269.46 | 208.38 | 0.00 | 0.00 |
April | 605.92 | 150.18 | 510.15 | 252.91 | 257.24 | 0.00 | 0.00 |
May | 556.91 | 100.73 | 442.88 | 199.12 | 243.76 | 0.00 | 0.00 |
June | 641.95 | 57.92 | 448.43 | 212.39 | 236.04 | 0.00 | 0.00 |
July | 642.71 | 26.51 | 422.33 | 174.97 | 247.36 | 0.00 | 0.00 |
August | 677.18 | 34.81 | 463.93 | 195.41 | 268.52 | 0.00 | 0.00 |
September | 665.02 | 79.96 | 486.90 | 263.45 | 223.44 | 0.00 | 0.00 |
October | 638.90 | 166.56 | 524.56 | 354.49 | 170.07 | 0.00 | 0.00 |
November | 534.01 | 254.47 | 495.25 | 341.71 | 153.54 | 0.00 | 0.00 |
December | 492.13 | 335.89 | 481.15 | 359.64 | 121.51 | 0.00 | 0.00 |
Annual Sum or Average | 584.88 | 172.34 | 477.58 | 273.23 | 204.35 | 0.00 | 0.00 |
Minimum of Months | 478.34 | 26.51 | 422.33 | 174.97 | 121.51 | 0.00 | 0.00 |
Maximum of Months | 677.18 | 335.89 | 524.56 | 359.64 | 268.52 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 196.91 | 346.93 | 231.88 | 111.38 | 120.50 | 0.00 | 0.00 |
February | 275.01 | 311.04 | 296.62 | 144.77 | 151.85 | 0.00 | 0.00 |
March | 344.23 | 236.96 | 337.64 | 148.72 | 188.93 | 0.00 | 0.00 |
April | 484.96 | 146.84 | 431.75 | 191.61 | 240.14 | 0.00 | 0.00 |
May | 514.61 | 97.68 | 420.24 | 181.16 | 239.08 | 0.00 | 0.00 |
June | 643.01 | 54.48 | 453.60 | 217.20 | 236.39 | 0.00 | 0.00 |
July | 619.59 | 25.78 | 410.82 | 167.20 | 243.61 | 0.00 | 0.00 |
August | 592.01 | 33.40 | 412.34 | 156.69 | 255.65 | 0.00 | 0.00 |
September | 486.60 | 78.33 | 365.71 | 160.61 | 205.10 | 0.00 | 0.00 |
October | 371.31 | 170.38 | 324.23 | 173.36 | 150.88 | 0.00 | 0.00 |
November | 234.97 | 263.05 | 256.47 | 127.93 | 128.54 | 0.00 | 0.00 |
December | 176.05 | 352.88 | 217.88 | 116.61 | 101.27 | 0.00 | 0.00 |
Annual Sum or Average | 412.17 | 175.82 | 346.68 | 158.04 | 188.64 | 0.00 | 0.00 |
Minimum of Months | 176.05 | 25.78 | 217.88 | 111.38 | 101.27 | 0.00 | 0.00 |
Maximum of Months | 643.01 | 352.88 | 453.60 | 217.20 | 255.65 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 243.43 | 98.50 | 215.94 | 167.92 | 48.01 | 0.00 | 0.00 |
February | 244.33 | 91.53 | 212.85 | 155.78 | 57.07 | 0.00 | 0.00 |
March | 185.22 | 73.50 | 158.27 | 96.58 | 61.69 | 0.00 | 0.00 |
April | 148.78 | 49.77 | 121.56 | 49.81 | 71.74 | 0.00 | 0.00 |
May | 102.86 | 34.64 | 81.81 | 18.51 | 63.30 | 0.00 | 0.00 |
June | 103.10 | 20.79 | 68.39 | 8.21 | 60.18 | 0.00 | 0.00 |
July | 123.85 | 11.35 | 75.70 | 11.88 | 63.82 | 0.00 | 0.00 |
August | 158.28 | 14.18 | 102.98 | 32.48 | 70.50 | 0.00 | 0.00 |
September | 205.58 | 28.45 | 146.19 | 82.29 | 63.90 | 0.00 | 0.00 |
October | 248.28 | 53.19 | 196.96 | 144.88 | 52.08 | 0.00 | 0.00 |
November | 257.82 | 79.52 | 222.18 | 170.99 | 51.19 | 0.00 | 0.00 |
December | 267.04 | 101.75 | 235.48 | 194.39 | 41.09 | 0.00 | 0.00 |
Annual Sum or Average | 190.40 | 54.57 | 152.85 | 94.16 | 58.70 | 0.00 | 0.00 |
Minimum of Months | 102.86 | 11.35 | 68.39 | 8.21 | 41.09 | 0.00 | 0.00 |
Maximum of Months | 267.04 | 101.75 | 235.48 | 194.39 | 71.74 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 7.73 | 102.52 | 29.27 | 0.00 | 29.27 | 0.00 | 0.00 |
February | 15.54 | 91.10 | 36.58 | 0.00 | 36.58 | 0.00 | 0.00 |
March | 32.50 | 68.28 | 46.15 | 0.00 | 46.15 | 0.00 | 0.00 |
April | 54.14 | 40.45 | 58.87 | 0.79 | 58.08 | 0.00 | 0.00 |
May | 73.76 | 26.22 | 63.72 | 4.14 | 59.58 | 0.00 | 0.00 |
June | 111.45 | 14.30 | 72.54 | 12.06 | 60.48 | 0.00 | 0.00 |
July | 111.56 | 6.26 | 66.52 | 5.67 | 60.85 | 0.00 | 0.00 |
August | 95.29 | 8.19 | 61.73 | 1.51 | 60.22 | 0.00 | 0.00 |
September | 65.17 | 20.68 | 49.28 | 0.04 | 49.25 | 0.00 | 0.00 |
October | 31.47 | 48.05 | 36.74 | 0.00 | 36.74 | 0.00 | 0.00 |
November | 11.79 | 77.38 | 31.20 | 0.00 | 31.20 | 0.00 | 0.00 |
December | 2.80 | 105.92 | 24.91 | 0.00 | 24.91 | 0.00 | 0.00 |
Annual Sum or Average | 51.29 | 50.59 | 48.17 | 2.02 | 46.15 | 0.00 | 0.00 |
Minimum of Months | 2.80 | 6.26 | 24.91 | 0.00 | 24.91 | 0.00 | 0.00 |
Maximum of Months | 111.56 | 105.92 | 72.54 | 12.06 | 60.85 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 462.67 | 325.03 | 459.35 | 315.94 | 143.40 | 0.00 | 0.00 |
February | 517.97 | 295.38 | 495.45 | 318.04 | 177.41 | 0.00 | 0.00 |
March | 555.09 | 225.59 | 502.64 | 294.37 | 208.27 | 0.00 | 0.00 |
April | 671.90 | 142.22 | 565.39 | 297.54 | 267.85 | 0.00 | 0.00 |
May | 624.03 | 96.68 | 497.24 | 248.10 | 249.13 | 0.00 | 0.00 |
June | 720.55 | 53.53 | 511.44 | 272.63 | 238.81 | 0.00 | 0.00 |
July | 730.07 | 25.59 | 488.58 | 240.04 | 248.53 | 0.00 | 0.00 |
August | 746.94 | 32.96 | 518.64 | 255.51 | 263.13 | 0.00 | 0.00 |
September | 687.80 | 75.87 | 507.90 | 284.81 | 223.09 | 0.00 | 0.00 |
October | 639.08 | 160.94 | 529.51 | 361.01 | 168.50 | 0.00 | 0.00 |
November | 532.92 | 250.77 | 498.08 | 343.02 | 155.06 | 0.00 | 0.00 |
December | 478.81 | 332.05 | 473.86 | 352.49 | 121.37 | 0.00 | 0.00 |
Annual Sum or Average | 614.35 | 167.42 | 503.89 | 298.45 | 205.44 | 0.00 | 0.00 |
Minimum of Months | 462.67 | 25.59 | 459.35 | 240.04 | 121.37 | 0.00 | 0.00 |
Maximum of Months | 746.94 | 332.05 | 565.39 | 361.01 | 267.85 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 168.30 | 326.67 | 225.95 | 105.99 | 119.96 | 0.00 | 0.00 |
February | 232.39 | 294.74 | 275.05 | 123.28 | 151.78 | 0.00 | 0.00 |
March | 360.11 | 223.11 | 362.44 | 173.62 | 188.82 | 0.00 | 0.00 |
April | 550.71 | 140.21 | 486.99 | 236.24 | 250.75 | 0.00 | 0.00 |
May | 582.90 | 95.18 | 474.59 | 230.14 | 244.45 | 0.00 | 0.00 |
June | 724.87 | 53.45 | 516.60 | 277.44 | 239.17 | 0.00 | 0.00 |
July | 707.46 | 25.39 | 477.07 | 232.28 | 244.79 | 0.00 | 0.00 |
August | 662.32 | 32.36 | 467.05 | 216.79 | 250.26 | 0.00 | 0.00 |
September | 508.47 | 74.01 | 386.71 | 181.96 | 204.75 | 0.00 | 0.00 |
October | 363.91 | 158.55 | 329.17 | 179.87 | 149.30 | 0.00 | 0.00 |
November | 226.60 | 251.10 | 259.30 | 129.24 | 130.06 | 0.00 | 0.00 |
December | 153.33 | 338.15 | 210.58 | 109.46 | 101.13 | 0.00 | 0.00 |
Annual Sum or Average | 437.74 | 167.12 | 372.99 | 183.26 | 189.73 | 0.00 | 0.00 |
Minimum of Months | 153.33 | 25.39 | 210.58 | 105.99 | 101.13 | 0.00 | 0.00 |
Maximum of Months | 724.87 | 338.15 | 516.60 | 277.44 | 250.75 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 536.61 | 407.03 | 531.28 | 363.85 | 167.43 | 0.00 | 0.00 |
February | 565.05 | 370.41 | 540.44 | 337.53 | 202.91 | 0.00 | 0.00 |
March | 485.33 | 285.08 | 442.92 | 209.26 | 233.65 | 0.00 | 0.00 |
April | 460.35 | 176.64 | 390.90 | 109.64 | 281.26 | 0.00 | 0.00 |
May | 404.35 | 114.05 | 315.28 | 49.07 | 266.22 | 0.00 | 0.00 |
June | 484.37 | 62.92 | 305.33 | 43.93 | 261.40 | 0.00 | 0.00 |
July | 528.88 | 30.75 | 308.13 | 38.02 | 270.11 | 0.00 | 0.00 |
August | 566.78 | 40.35 | 356.87 | 73.65 | 283.22 | 0.00 | 0.00 |
September | 604.41 | 94.09 | 423.52 | 178.38 | 245.14 | 0.00 | 0.00 |
October | 617.46 | 198.67 | 506.34 | 313.91 | 192.43 | 0.00 | 0.00 |
November | 586.39 | 307.75 | 548.98 | 370.49 | 178.49 | 0.00 | 0.00 |
December | 570.44 | 412.98 | 564.19 | 421.18 | 143.01 | 0.00 | 0.00 |
Annual Sum or Average | 533.95 | 207.59 | 435.53 | 208.39 | 227.15 | 0.00 | 0.00 |
Minimum of Months | 404.35 | 30.75 | 305.33 | 38.02 | 143.01 | 0.00 | 0.00 |
Maximum of Months | 617.46 | 412.98 | 564.19 | 421.18 | 283.22 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 476.41 | 329.42 | 465.27 | 321.33 | 143.94 | 0.00 | 0.00 |
February | 549.48 | 301.91 | 517.02 | 339.53 | 177.48 | 0.00 | 0.00 |
March | 528.54 | 234.03 | 477.84 | 269.46 | 208.38 | 0.00 | 0.00 |
April | 599.35 | 149.80 | 510.15 | 252.91 | 257.24 | 0.00 | 0.00 |
May | 550.31 | 100.64 | 442.88 | 199.12 | 243.76 | 0.00 | 0.00 |
June | 635.79 | 57.97 | 448.43 | 212.39 | 236.04 | 0.00 | 0.00 |
July | 636.39 | 26.54 | 422.33 | 174.97 | 247.36 | 0.00 | 0.00 |
August | 670.64 | 34.94 | 463.93 | 195.41 | 268.52 | 0.00 | 0.00 |
September | 659.18 | 80.01 | 486.90 | 263.45 | 223.44 | 0.00 | 0.00 |
October | 634.71 | 165.98 | 524.56 | 354.49 | 170.07 | 0.00 | 0.00 |
November | 531.28 | 252.89 | 495.25 | 341.71 | 153.54 | 0.00 | 0.00 |
December | 490.65 | 333.36 | 481.15 | 359.64 | 121.51 | 0.00 | 0.00 |
Annual Sum or Average | 580.19 | 171.63 | 477.58 | 273.23 | 204.35 | 0.00 | 0.00 |
Minimum of Months | 476.41 | 26.54 | 422.33 | 174.97 | 121.51 | 0.00 | 0.00 |
Maximum of Months | 670.64 | 333.36 | 524.56 | 359.64 | 268.52 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 196.60 | 344.17 | 231.88 | 111.38 | 120.50 | 0.00 | 0.00 |
February | 273.33 | 309.36 | 296.62 | 144.77 | 151.85 | 0.00 | 0.00 |
March | 341.06 | 235.94 | 337.64 | 148.72 | 188.93 | 0.00 | 0.00 |
April | 478.96 | 146.44 | 431.75 | 191.61 | 240.14 | 0.00 | 0.00 |
May | 508.24 | 97.65 | 420.24 | 181.16 | 239.08 | 0.00 | 0.00 |
June | 636.81 | 54.66 | 453.60 | 217.20 | 236.39 | 0.00 | 0.00 |
July | 613.47 | 25.83 | 410.82 | 167.20 | 243.61 | 0.00 | 0.00 |
August | 586.00 | 33.53 | 412.34 | 156.69 | 255.65 | 0.00 | 0.00 |
September | 481.62 | 78.31 | 365.71 | 160.61 | 205.10 | 0.00 | 0.00 |
October | 368.06 | 169.27 | 324.23 | 173.36 | 150.88 | 0.00 | 0.00 |
November | 233.84 | 260.37 | 256.47 | 127.93 | 128.54 | 0.00 | 0.00 |
December | 176.09 | 349.43 | 217.88 | 116.61 | 101.27 | 0.00 | 0.00 |
Annual Sum or Average | 408.40 | 174.75 | 346.68 | 158.04 | 188.64 | 0.00 | 0.00 |
Minimum of Months | 176.09 | 25.83 | 217.88 | 111.38 | 101.27 | 0.00 | 0.00 |
Maximum of Months | 636.81 | 349.43 | 453.60 | 217.20 | 255.65 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 444.34 | 171.50 | 395.94 | 307.91 | 88.03 | 0.00 | 0.00 |
February | 446.41 | 156.68 | 390.28 | 285.63 | 104.65 | 0.00 | 0.00 |
March | 340.43 | 121.57 | 290.21 | 177.09 | 113.12 | 0.00 | 0.00 |
April | 274.77 | 77.85 | 222.88 | 91.34 | 131.54 | 0.00 | 0.00 |
May | 192.65 | 51.02 | 150.00 | 33.93 | 116.07 | 0.00 | 0.00 |
June | 195.09 | 28.11 | 125.40 | 15.06 | 110.34 | 0.00 | 0.00 |
July | 232.92 | 12.37 | 138.81 | 21.78 | 117.03 | 0.00 | 0.00 |
August | 294.26 | 16.68 | 188.83 | 59.55 | 129.27 | 0.00 | 0.00 |
September | 377.99 | 40.20 | 268.06 | 150.89 | 117.17 | 0.00 | 0.00 |
October | 455.62 | 84.85 | 361.15 | 265.65 | 95.49 | 0.00 | 0.00 |
November | 472.41 | 132.27 | 407.38 | 313.53 | 93.85 | 0.00 | 0.00 |
December | 487.83 | 175.25 | 431.78 | 356.43 | 75.35 | 0.00 | 0.00 |
Annual Sum or Average | 350.68 | 88.69 | 280.27 | 172.64 | 107.62 | 0.00 | 0.00 |
Minimum of Months | 192.65 | 12.37 | 125.40 | 15.06 | 75.35 | 0.00 | 0.00 |
Maximum of Months | 487.83 | 175.25 | 431.78 | 356.43 | 131.54 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 60.38 | 906.74 | 256.06 | 0.00 | 256.06 | 0.00 | 0.00 |
February | 128.48 | 807.29 | 320.04 | 0.00 | 320.04 | 0.00 | 0.00 |
March | 281.14 | 605.02 | 403.77 | 0.01 | 403.75 | 0.00 | 0.00 |
April | 477.46 | 363.22 | 514.99 | 6.90 | 508.09 | 0.00 | 0.00 |
May | 652.46 | 241.85 | 557.42 | 36.22 | 521.20 | 0.00 | 0.00 |
June | 983.76 | 138.89 | 634.64 | 105.54 | 529.10 | 0.00 | 0.00 |
July | 985.83 | 69.99 | 581.96 | 49.60 | 532.35 | 0.00 | 0.00 |
August | 843.56 | 88.51 | 540.08 | 13.22 | 526.86 | 0.00 | 0.00 |
September | 581.33 | 195.10 | 431.15 | 0.31 | 430.84 | 0.00 | 0.00 |
October | 277.12 | 428.39 | 321.40 | 0.00 | 321.40 | 0.00 | 0.00 |
November | 98.35 | 682.08 | 272.95 | 0.00 | 272.95 | 0.00 | 0.00 |
December | 20.01 | 941.80 | 217.95 | 0.00 | 217.95 | 0.00 | 0.00 |
Annual Sum or Average | 450.85 | 454.07 | 421.40 | 17.68 | 403.72 | 0.00 | 0.00 |
Minimum of Months | 20.01 | 69.99 | 217.95 | 0.00 | 217.95 | 0.00 | 0.00 |
Maximum of Months | 985.83 | 941.80 | 634.64 | 105.54 | 532.35 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 57.50 | 919.54 | 256.06 | 0.00 | 256.06 | 0.00 | 0.00 |
February | 124.69 | 819.55 | 320.04 | 0.00 | 320.04 | 0.00 | 0.00 |
March | 275.50 | 616.68 | 403.77 | 0.01 | 403.75 | 0.00 | 0.00 |
April | 469.00 | 373.14 | 514.99 | 6.90 | 508.09 | 0.00 | 0.00 |
May | 642.10 | 250.66 | 557.42 | 36.22 | 521.20 | 0.00 | 0.00 |
June | 971.91 | 145.96 | 634.64 | 105.54 | 529.10 | 0.00 | 0.00 |
July | 973.82 | 76.10 | 581.96 | 49.60 | 532.35 | 0.00 | 0.00 |
August | 832.52 | 95.19 | 540.08 | 13.22 | 526.86 | 0.00 | 0.00 |
September | 573.17 | 204.47 | 431.15 | 0.31 | 430.84 | 0.00 | 0.00 |
October | 271.63 | 439.67 | 321.40 | 0.00 | 321.40 | 0.00 | 0.00 |
November | 94.75 | 694.60 | 272.95 | 0.00 | 272.95 | 0.00 | 0.00 |
December | 18.55 | 955.67 | 217.95 | 0.00 | 217.95 | 0.00 | 0.00 |
Annual Sum or Average | 443.77 | 464.25 | 421.40 | 17.68 | 403.72 | 0.00 | 0.00 |
Minimum of Months | 18.55 | 76.10 | 217.95 | 0.00 | 217.95 | 0.00 | 0.00 |
Maximum of Months | 973.82 | 955.67 | 634.64 | 105.54 | 532.35 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 681.05 | 636.04 | 685.27 | 421.92 | 263.35 | 0.00 | 0.00 |
February | 809.63 | 581.34 | 770.46 | 441.29 | 329.17 | 0.00 | 0.00 |
March | 994.18 | 447.70 | 865.04 | 467.96 | 397.07 | 0.00 | 0.00 |
April | 1331.08 | 287.49 | 1052.32 | 533.75 | 518.57 | 0.00 | 0.00 |
May | 1322.53 | 200.32 | 971.77 | 478.21 | 493.56 | 0.00 | 0.00 |
June | 1578.98 | 117.80 | 1027.99 | 550.03 | 477.96 | 0.00 | 0.00 |
July | 1578.05 | 60.20 | 965.59 | 472.29 | 493.30 | 0.00 | 0.00 |
August | 1547.76 | 74.38 | 985.63 | 472.27 | 513.37 | 0.00 | 0.00 |
September | 1319.70 | 150.24 | 894.57 | 466.75 | 427.82 | 0.00 | 0.00 |
October | 1099.19 | 310.65 | 858.64 | 540.86 | 317.78 | 0.00 | 0.00 |
November | 820.58 | 483.32 | 757.34 | 472.24 | 285.11 | 0.00 | 0.00 |
December | 672.21 | 643.80 | 684.41 | 461.93 | 222.48 | 0.00 | 0.00 |
Annual Sum or Average | 1147.74 | 331.53 | 876.84 | 481.69 | 395.15 | 0.00 | 0.00 |
Minimum of Months | 672.21 | 60.20 | 684.41 | 421.92 | 222.48 | 0.00 | 0.00 |
Maximum of Months | 1578.98 | 643.80 | 1052.32 | 550.03 | 518.57 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1145.76 | 718.22 | 1095.67 | 783.80 | 311.87 | 0.00 | 0.00 |
February | 1186.27 | 654.98 | 1103.20 | 727.10 | 376.10 | 0.00 | 0.00 |
March | 978.50 | 506.05 | 877.17 | 450.80 | 426.37 | 0.00 | 0.00 |
April | 883.69 | 314.20 | 743.90 | 234.88 | 509.03 | 0.00 | 0.00 |
May | 730.23 | 202.10 | 572.93 | 98.80 | 474.13 | 0.00 | 0.00 |
June | 846.76 | 108.69 | 536.77 | 74.51 | 462.26 | 0.00 | 0.00 |
July | 947.05 | 48.98 | 552.84 | 72.45 | 480.40 | 0.00 | 0.00 |
August | 1055.85 | 65.04 | 665.81 | 156.13 | 509.68 | 0.00 | 0.00 |
September | 1182.47 | 158.08 | 830.16 | 384.22 | 445.95 | 0.00 | 0.00 |
October | 1270.29 | 345.37 | 1029.49 | 676.23 | 353.26 | 0.00 | 0.00 |
November | 1241.33 | 544.23 | 1130.58 | 798.10 | 332.48 | 0.00 | 0.00 |
December | 1233.30 | 729.18 | 1173.83 | 907.30 | 266.52 | 0.00 | 0.00 |
Annual Sum or Average | 1057.63 | 364.82 | 857.89 | 445.54 | 412.36 | 0.00 | 0.00 |
Minimum of Months | 730.23 | 48.98 | 536.77 | 72.45 | 266.52 | 0.00 | 0.00 |
Maximum of Months | 1270.29 | 729.18 | 1173.83 | 907.30 | 509.68 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.416484E+10 | 0.149934E+10 | 0.365721E+10 | 0.284409E+10 | 0.813124E+09 | 0.00 | 0.00 |
February | 0.378648E+10 | 0.123434E+10 | 0.325610E+10 | 0.238302E+10 | 0.873079E+09 | 0.00 | 0.00 |
March | 0.321832E+10 | 0.106111E+10 | 0.268063E+10 | 0.163574E+10 | 0.104489E+10 | 0.00 | 0.00 |
April | 0.252796E+10 | 0.669891E+09 | 0.199231E+10 | 0.816477E+09 | 0.117584E+10 | 0.00 | 0.00 |
May | 0.183941E+10 | 0.459023E+09 | 0.138554E+10 | 0.313445E+09 | 0.107209E+10 | 0.00 | 0.00 |
June | 0.176755E+10 | 0.250754E+09 | 0.112091E+10 | 0.134596E+09 | 0.986310E+09 | 0.00 | 0.00 |
July | 0.217550E+10 | 0.118264E+09 | 0.128213E+10 | 0.201175E+09 | 0.108095E+10 | 0.00 | 0.00 |
August | 0.275015E+10 | 0.157320E+09 | 0.174413E+10 | 0.550093E+09 | 0.119404E+10 | 0.00 | 0.00 |
September | 0.341499E+10 | 0.355196E+09 | 0.239615E+10 | 0.134882E+10 | 0.104733E+10 | 0.00 | 0.00 |
October | 0.424349E+10 | 0.753662E+09 | 0.333581E+10 | 0.245376E+10 | 0.882050E+09 | 0.00 | 0.00 |
November | 0.427192E+10 | 0.112314E+10 | 0.364151E+10 | 0.280257E+10 | 0.838938E+09 | 0.00 | 0.00 |
December | 0.455707E+10 | 0.153706E+10 | 0.398823E+10 | 0.329223E+10 | 0.695993E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.387177E+11 | 0.921910E+10 | 0.304806E+11 | 0.187760E+11 | 0.117046E+11 | 0.00 | 0.00 |
Minimum of Months | 0.176755E+10 | 0.118264E+09 | 0.112091E+10 | 0.134596E+09 | 0.695993E+09 | 0.00 | 0.00 |
Maximum of Months | 0.455707E+10 | 0.153706E+10 | 0.398823E+10 | 0.329223E+10 | 0.119404E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.116920E+11 | 0.422557E+10 | 0.102985E+11 | 0.800876E+10 | 0.228970E+10 | 0.00 | 0.00 |
February | 0.106314E+11 | 0.347794E+10 | 0.916896E+10 | 0.671042E+10 | 0.245853E+10 | 0.00 | 0.00 |
March | 0.902886E+10 | 0.298681E+10 | 0.754847E+10 | 0.460613E+10 | 0.294234E+10 | 0.00 | 0.00 |
April | 0.709147E+10 | 0.188212E+10 | 0.561022E+10 | 0.229915E+10 | 0.331108E+10 | 0.00 | 0.00 |
May | 0.515205E+10 | 0.128908E+10 | 0.390158E+10 | 0.882641E+09 | 0.301894E+10 | 0.00 | 0.00 |
June | 0.495696E+10 | 0.709797E+09 | 0.315640E+10 | 0.379014E+09 | 0.277738E+10 | 0.00 | 0.00 |
July | 0.611477E+10 | 0.347404E+09 | 0.361039E+10 | 0.566496E+09 | 0.304390E+10 | 0.00 | 0.00 |
August | 0.774097E+10 | 0.462749E+09 | 0.491137E+10 | 0.154903E+10 | 0.336234E+10 | 0.00 | 0.00 |
September | 0.961837E+10 | 0.101552E+10 | 0.674739E+10 | 0.379819E+10 | 0.294920E+10 | 0.00 | 0.00 |
October | 0.119370E+11 | 0.213575E+10 | 0.939343E+10 | 0.690963E+10 | 0.248379E+10 | 0.00 | 0.00 |
November | 0.120015E+11 | 0.316585E+10 | 0.102543E+11 | 0.789186E+10 | 0.236239E+10 | 0.00 | 0.00 |
December | 0.127988E+11 | 0.433508E+10 | 0.112306E+11 | 0.927071E+10 | 0.195987E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.108764E+12 | 0.260337E+11 | 0.858315E+11 | 0.528720E+11 | 0.329595E+11 | 0.00 | 0.00 |
Minimum of Months | 0.495696E+10 | 0.347404E+09 | 0.315640E+10 | 0.379014E+09 | 0.195987E+10 | 0.00 | 0.00 |
Maximum of Months | 0.127988E+11 | 0.433508E+10 | 0.112306E+11 | 0.927071E+10 | 0.336234E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.155116E+11 | 0.555863E+10 | 0.133783E+11 | 0.104038E+11 | 0.297446E+10 | 0.00 | 0.00 |
February | 0.141122E+11 | 0.457343E+10 | 0.119110E+11 | 0.871722E+10 | 0.319378E+10 | 0.00 | 0.00 |
March | 0.119970E+11 | 0.394907E+10 | 0.980589E+10 | 0.598362E+10 | 0.382227E+10 | 0.00 | 0.00 |
April | 0.943208E+10 | 0.250579E+10 | 0.728800E+10 | 0.298672E+10 | 0.430128E+10 | 0.00 | 0.00 |
May | 0.686370E+10 | 0.174278E+10 | 0.506838E+10 | 0.114660E+10 | 0.392177E+10 | 0.00 | 0.00 |
June | 0.660896E+10 | 0.969302E+09 | 0.410034E+10 | 0.492361E+09 | 0.360798E+10 | 0.00 | 0.00 |
July | 0.815080E+10 | 0.472047E+09 | 0.469011E+10 | 0.735911E+09 | 0.395420E+10 | 0.00 | 0.00 |
August | 0.103218E+11 | 0.610978E+09 | 0.638014E+10 | 0.201227E+10 | 0.436787E+10 | 0.00 | 0.00 |
September | 0.128160E+11 | 0.131323E+10 | 0.876524E+10 | 0.493407E+10 | 0.383118E+10 | 0.00 | 0.00 |
October | 0.158834E+11 | 0.277325E+10 | 0.122026E+11 | 0.897601E+10 | 0.322659E+10 | 0.00 | 0.00 |
November | 0.159457E+11 | 0.414683E+10 | 0.133209E+11 | 0.102520E+11 | 0.306888E+10 | 0.00 | 0.00 |
December | 0.169734E+11 | 0.569666E+10 | 0.145892E+11 | 0.120432E+11 | 0.254598E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.144617E+12 | 0.343120E+11 | 0.111500E+12 | 0.686838E+11 | 0.428162E+11 | 0.00 | 0.00 |
Minimum of Months | 0.660896E+10 | 0.472047E+09 | 0.410034E+10 | 0.492361E+09 | 0.254598E+10 | 0.00 | 0.00 |
Maximum of Months | 0.169734E+11 | 0.569666E+10 | 0.145892E+11 | 0.120432E+11 | 0.436787E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.128120E+10 | 0.887372E+09 | 0.124618E+10 | 0.860644E+09 | 0.385540E+09 | 0.00 | 0.00 |
February | 0.133750E+10 | 0.732976E+09 | 0.125077E+10 | 0.821399E+09 | 0.429371E+09 | 0.00 | 0.00 |
March | 0.142745E+10 | 0.628508E+09 | 0.127985E+10 | 0.721728E+09 | 0.558127E+09 | 0.00 | 0.00 |
April | 0.157053E+10 | 0.389277E+09 | 0.132231E+10 | 0.655531E+09 | 0.666775E+09 | 0.00 | 0.00 |
May | 0.149162E+10 | 0.269799E+09 | 0.118622E+10 | 0.533331E+09 | 0.652887E+09 | 0.00 | 0.00 |
June | 0.166393E+10 | 0.150135E+09 | 0.116234E+10 | 0.550518E+09 | 0.611824E+09 | 0.00 | 0.00 |
July | 0.172143E+10 | 71015337.77 | 0.113116E+10 | 0.468634E+09 | 0.662522E+09 | 0.00 | 0.00 |
August | 0.181375E+10 | 93233442.49 | 0.124260E+10 | 0.523397E+09 | 0.719205E+09 | 0.00 | 0.00 |
September | 0.172373E+10 | 0.207265E+09 | 0.126203E+10 | 0.682873E+09 | 0.579160E+09 | 0.00 | 0.00 |
October | 0.171124E+10 | 0.446109E+09 | 0.140499E+10 | 0.949466E+09 | 0.455520E+09 | 0.00 | 0.00 |
November | 0.138415E+10 | 0.659590E+09 | 0.128369E+10 | 0.885716E+09 | 0.397972E+09 | 0.00 | 0.00 |
December | 0.131811E+10 | 0.899645E+09 | 0.128872E+10 | 0.963268E+09 | 0.325450E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.184446E+11 | 0.543493E+10 | 0.150609E+11 | 0.861650E+10 | 0.644435E+10 | 0.00 | 0.00 |
Minimum of Months | 0.128120E+10 | 71015337.77 | 0.113116E+10 | 0.468634E+09 | 0.325450E+09 | 0.00 | 0.00 |
Maximum of Months | 0.181375E+10 | 0.899645E+09 | 0.140499E+10 | 0.963268E+09 | 0.719205E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.527394E+09 | 0.929226E+09 | 0.621070E+09 | 0.298319E+09 | 0.322751E+09 | 0.00 | 0.00 |
February | 0.665298E+09 | 0.752464E+09 | 0.717592E+09 | 0.350236E+09 | 0.367356E+09 | 0.00 | 0.00 |
March | 0.921977E+09 | 0.634666E+09 | 0.904345E+09 | 0.398320E+09 | 0.506025E+09 | 0.00 | 0.00 |
April | 0.125702E+10 | 0.380619E+09 | 0.111909E+10 | 0.496654E+09 | 0.622434E+09 | 0.00 | 0.00 |
May | 0.137834E+10 | 0.261631E+09 | 0.112556E+10 | 0.485216E+09 | 0.640348E+09 | 0.00 | 0.00 |
June | 0.166668E+10 | 0.141213E+09 | 0.117572E+10 | 0.562988E+09 | 0.612736E+09 | 0.00 | 0.00 |
July | 0.165951E+10 | 69055705.24 | 0.110034E+10 | 0.447839E+09 | 0.652497E+09 | 0.00 | 0.00 |
August | 0.158565E+10 | 89465608.78 | 0.110441E+10 | 0.419691E+09 | 0.684721E+09 | 0.00 | 0.00 |
September | 0.126127E+10 | 0.203026E+09 | 0.947924E+09 | 0.416301E+09 | 0.531623E+09 | 0.00 | 0.00 |
October | 0.994512E+09 | 0.456344E+09 | 0.868419E+09 | 0.464315E+09 | 0.404104E+09 | 0.00 | 0.00 |
November | 0.609033E+09 | 0.681837E+09 | 0.664771E+09 | 0.331600E+09 | 0.333171E+09 | 0.00 | 0.00 |
December | 0.471538E+09 | 0.945152E+09 | 0.583573E+09 | 0.312337E+09 | 0.271236E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.129982E+11 | 0.554470E+10 | 0.109328E+11 | 0.498382E+10 | 0.594900E+10 | 0.00 | 0.00 |
Minimum of Months | 0.471538E+09 | 69055705.24 | 0.583573E+09 | 0.298319E+09 | 0.271236E+09 | 0.00 | 0.00 |
Maximum of Months | 0.166668E+10 | 0.945152E+09 | 0.117572E+10 | 0.562988E+09 | 0.684721E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.652004E+09 | 0.263811E+09 | 0.578361E+09 | 0.449770E+09 | 0.128590E+09 | 0.00 | 0.00 |
February | 0.591081E+09 | 0.221427E+09 | 0.514928E+09 | 0.376856E+09 | 0.138072E+09 | 0.00 | 0.00 |
March | 0.496101E+09 | 0.196865E+09 | 0.423922E+09 | 0.258679E+09 | 0.165243E+09 | 0.00 | 0.00 |
April | 0.385629E+09 | 0.129000E+09 | 0.315071E+09 | 0.129120E+09 | 0.185952E+09 | 0.00 | 0.00 |
May | 0.275499E+09 | 92779327.46 | 0.219114E+09 | 49568964.22 | 0.169545E+09 | 0.00 | 0.00 |
June | 0.267244E+09 | 53899772.58 | 0.177265E+09 | 21285372.45 | 0.155980E+09 | 0.00 | 0.00 |
July | 0.331707E+09 | 30400395.50 | 0.202761E+09 | 31814303.90 | 0.170947E+09 | 0.00 | 0.00 |
August | 0.423946E+09 | 37967998.04 | 0.275824E+09 | 86993003.94 | 0.188831E+09 | 0.00 | 0.00 |
September | 0.532874E+09 | 73748485.78 | 0.378934E+09 | 0.213306E+09 | 0.165628E+09 | 0.00 | 0.00 |
October | 0.664999E+09 | 0.142457E+09 | 0.527535E+09 | 0.388044E+09 | 0.139491E+09 | 0.00 | 0.00 |
November | 0.668281E+09 | 0.206106E+09 | 0.575878E+09 | 0.443205E+09 | 0.132673E+09 | 0.00 | 0.00 |
December | 0.715235E+09 | 0.272530E+09 | 0.630708E+09 | 0.520641E+09 | 0.110067E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.600460E+10 | 0.172099E+10 | 0.482030E+10 | 0.296928E+10 | 0.185102E+10 | 0.00 | 0.00 |
Minimum of Months | 0.267244E+09 | 30400395.50 | 0.177265E+09 | 21285372.45 | 0.110067E+09 | 0.00 | 0.00 |
Maximum of Months | 0.715235E+09 | 0.272530E+09 | 0.630708E+09 | 0.520641E+09 | 0.188831E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 20708573.02 | 0.274592E+09 | 78395194.18 | 0.00 | 78395194.18 | 0.00 | 0.00 |
February | 37604407.79 | 0.220394E+09 | 88498821.31 | 0.00 | 88498821.31 | 0.00 | 0.00 |
March | 87037622.72 | 0.182891E+09 | 0.123615E+09 | 4297.01 | 0.123611E+09 | 0.00 | 0.00 |
April | 0.140342E+09 | 0.104838E+09 | 0.152580E+09 | 2043871.97 | 0.150536E+09 | 0.00 | 0.00 |
May | 0.197546E+09 | 70227432.11 | 0.170657E+09 | 11088084.06 | 0.159568E+09 | 0.00 | 0.00 |
June | 0.288889E+09 | 37061616.18 | 0.188031E+09 | 31269876.03 | 0.156761E+09 | 0.00 | 0.00 |
July | 0.298800E+09 | 16763961.93 | 0.178169E+09 | 15186292.66 | 0.162983E+09 | 0.00 | 0.00 |
August | 0.255235E+09 | 21936080.64 | 0.165349E+09 | 4046567.42 | 0.161302E+09 | 0.00 | 0.00 |
September | 0.168930E+09 | 53615458.61 | 0.127739E+09 | 91026.49 | 0.127648E+09 | 0.00 | 0.00 |
October | 84299422.01 | 0.128708E+09 | 98399454.57 | 0.00 | 98399454.57 | 0.00 | 0.00 |
November | 30556325.80 | 0.200559E+09 | 80868758.46 | 0.00 | 80868758.46 | 0.00 | 0.00 |
December | 7500917.73 | 0.283695E+09 | 66726175.04 | 0.00 | 66726175.04 | 0.00 | 0.00 |
Annual Sum or Average | 0.161745E+10 | 0.159528E+10 | 0.151903E+10 | 63730015.63 | 0.145530E+10 | 0.00 | 0.00 |
Minimum of Months | 7500917.73 | 16763961.93 | 66726175.04 | 0.00 | 66726175.04 | 0.00 | 0.00 |
Maximum of Months | 0.298800E+09 | 0.283695E+09 | 0.188031E+09 | 31269876.03 | 0.162983E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.123922E+10 | 0.870556E+09 | 0.123031E+10 | 0.846218E+09 | 0.384093E+09 | 0.00 | 0.00 |
February | 0.125308E+10 | 0.714595E+09 | 0.119858E+10 | 0.769391E+09 | 0.429191E+09 | 0.00 | 0.00 |
March | 0.148675E+10 | 0.604220E+09 | 0.134627E+10 | 0.788435E+09 | 0.557833E+09 | 0.00 | 0.00 |
April | 0.174157E+10 | 0.368633E+09 | 0.146549E+10 | 0.771218E+09 | 0.694275E+09 | 0.00 | 0.00 |
May | 0.167139E+10 | 0.258940E+09 | 0.133180E+10 | 0.664517E+09 | 0.667283E+09 | 0.00 | 0.00 |
June | 0.186767E+10 | 0.138743E+09 | 0.132566E+10 | 0.706653E+09 | 0.619005E+09 | 0.00 | 0.00 |
July | 0.195542E+10 | 68543659.82 | 0.130860E+10 | 0.642930E+09 | 0.665670E+09 | 0.00 | 0.00 |
August | 0.200061E+10 | 88290646.44 | 0.138913E+10 | 0.684353E+09 | 0.704775E+09 | 0.00 | 0.00 |
September | 0.178278E+10 | 0.196642E+09 | 0.131647E+10 | 0.738223E+09 | 0.578250E+09 | 0.00 | 0.00 |
October | 0.171171E+10 | 0.431067E+09 | 0.141823E+10 | 0.966926E+09 | 0.451303E+09 | 0.00 | 0.00 |
November | 0.138132E+10 | 0.649996E+09 | 0.129101E+10 | 0.889101E+09 | 0.401914E+09 | 0.00 | 0.00 |
December | 0.128246E+10 | 0.889375E+09 | 0.126917E+10 | 0.944102E+09 | 0.325072E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.193740E+11 | 0.527960E+10 | 0.158907E+11 | 0.941206E+10 | 0.647866E+10 | 0.00 | 0.00 |
Minimum of Months | 0.123922E+10 | 68543659.82 | 0.119858E+10 | 0.642930E+09 | 0.325072E+09 | 0.00 | 0.00 |
Maximum of Months | 0.200061E+10 | 0.889375E+09 | 0.146549E+10 | 0.966926E+09 | 0.704775E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.450786E+09 | 0.874954E+09 | 0.605197E+09 | 0.283893E+09 | 0.321304E+09 | 0.00 | 0.00 |
February | 0.562199E+09 | 0.713031E+09 | 0.665402E+09 | 0.298227E+09 | 0.367175E+09 | 0.00 | 0.00 |
March | 0.964529E+09 | 0.597573E+09 | 0.970759E+09 | 0.465027E+09 | 0.505732E+09 | 0.00 | 0.00 |
April | 0.142745E+10 | 0.363413E+09 | 0.126228E+10 | 0.612341E+09 | 0.649934E+09 | 0.00 | 0.00 |
May | 0.156123E+10 | 0.254920E+09 | 0.127114E+10 | 0.616401E+09 | 0.654743E+09 | 0.00 | 0.00 |
June | 0.187886E+10 | 0.138541E+09 | 0.133904E+10 | 0.719123E+09 | 0.619916E+09 | 0.00 | 0.00 |
July | 0.189486E+10 | 67993345.24 | 0.127778E+10 | 0.622134E+09 | 0.655645E+09 | 0.00 | 0.00 |
August | 0.177396E+10 | 86683675.47 | 0.125094E+10 | 0.580648E+09 | 0.670290E+09 | 0.00 | 0.00 |
September | 0.131795E+10 | 0.191845E+09 | 0.100236E+10 | 0.471651E+09 | 0.530713E+09 | 0.00 | 0.00 |
October | 0.974710E+09 | 0.424649E+09 | 0.881662E+09 | 0.481775E+09 | 0.399887E+09 | 0.00 | 0.00 |
November | 0.587349E+09 | 0.650853E+09 | 0.672096E+09 | 0.334984E+09 | 0.337112E+09 | 0.00 | 0.00 |
December | 0.410685E+09 | 0.905707E+09 | 0.564029E+09 | 0.293171E+09 | 0.270858E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.138046E+11 | 0.527016E+10 | 0.117627E+11 | 0.577938E+10 | 0.598331E+10 | 0.00 | 0.00 |
Minimum of Months | 0.410685E+09 | 67993345.24 | 0.564029E+09 | 0.283893E+09 | 0.270858E+09 | 0.00 | 0.00 |
Maximum of Months | 0.189486E+10 | 0.905707E+09 | 0.133904E+10 | 0.719123E+09 | 0.670290E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.143725E+10 | 0.109018E+10 | 0.142298E+10 | 0.974527E+09 | 0.448450E+09 | 0.00 | 0.00 |
February | 0.136697E+10 | 0.896091E+09 | 0.130742E+10 | 0.816542E+09 | 0.490882E+09 | 0.00 | 0.00 |
March | 0.129990E+10 | 0.763565E+09 | 0.118631E+10 | 0.560495E+09 | 0.625818E+09 | 0.00 | 0.00 |
April | 0.119323E+10 | 0.457853E+09 | 0.101321E+10 | 0.284194E+09 | 0.729017E+09 | 0.00 | 0.00 |
May | 0.108301E+10 | 0.305462E+09 | 0.844459E+09 | 0.131423E+09 | 0.713037E+09 | 0.00 | 0.00 |
June | 0.125550E+10 | 0.163082E+09 | 0.791422E+09 | 0.113861E+09 | 0.677561E+09 | 0.00 | 0.00 |
July | 0.141654E+10 | 82351861.76 | 0.825301E+09 | 0.101831E+09 | 0.723470E+09 | 0.00 | 0.00 |
August | 0.151806E+10 | 0.108068E+09 | 0.955834E+09 | 0.197256E+09 | 0.758578E+09 | 0.00 | 0.00 |
September | 0.156663E+10 | 0.243890E+09 | 0.109777E+10 | 0.462371E+09 | 0.635400E+09 | 0.00 | 0.00 |
October | 0.165382E+10 | 0.532122E+09 | 0.135619E+10 | 0.840783E+09 | 0.515404E+09 | 0.00 | 0.00 |
November | 0.151993E+10 | 0.797692E+09 | 0.142296E+10 | 0.960302E+09 | 0.462654E+09 | 0.00 | 0.00 |
December | 0.152786E+10 | 0.110613E+10 | 0.151112E+10 | 0.112808E+10 | 0.383036E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.168387E+11 | 0.654649E+10 | 0.137350E+11 | 0.657167E+10 | 0.716331E+10 | 0.00 | 0.00 |
Minimum of Months | 0.108301E+10 | 82351861.76 | 0.791422E+09 | 0.101831E+09 | 0.383036E+09 | 0.00 | 0.00 |
Maximum of Months | 0.165382E+10 | 0.110613E+10 | 0.151112E+10 | 0.112808E+10 | 0.758578E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.127602E+10 | 0.882310E+09 | 0.124618E+10 | 0.860644E+09 | 0.385540E+09 | 0.00 | 0.00 |
February | 0.132930E+10 | 0.730386E+09 | 0.125077E+10 | 0.821399E+09 | 0.429371E+09 | 0.00 | 0.00 |
March | 0.141563E+10 | 0.626839E+09 | 0.127985E+10 | 0.721728E+09 | 0.558127E+09 | 0.00 | 0.00 |
April | 0.155352E+10 | 0.388278E+09 | 0.132231E+10 | 0.655531E+09 | 0.666775E+09 | 0.00 | 0.00 |
May | 0.147396E+10 | 0.269556E+09 | 0.118622E+10 | 0.533331E+09 | 0.652887E+09 | 0.00 | 0.00 |
June | 0.164796E+10 | 0.150267E+09 | 0.116234E+10 | 0.550518E+09 | 0.611824E+09 | 0.00 | 0.00 |
July | 0.170450E+10 | 71076558.37 | 0.113116E+10 | 0.468634E+09 | 0.662522E+09 | 0.00 | 0.00 |
August | 0.179624E+10 | 93572456.17 | 0.124260E+10 | 0.523397E+09 | 0.719205E+09 | 0.00 | 0.00 |
September | 0.170859E+10 | 0.207385E+09 | 0.126203E+10 | 0.682873E+09 | 0.579160E+09 | 0.00 | 0.00 |
October | 0.170001E+10 | 0.444564E+09 | 0.140499E+10 | 0.949466E+09 | 0.455520E+09 | 0.00 | 0.00 |
November | 0.137707E+10 | 0.655491E+09 | 0.128369E+10 | 0.885716E+09 | 0.397972E+09 | 0.00 | 0.00 |
December | 0.131416E+10 | 0.892874E+09 | 0.128872E+10 | 0.963268E+09 | 0.325450E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.182970E+11 | 0.541260E+10 | 0.150609E+11 | 0.861650E+10 | 0.644435E+10 | 0.00 | 0.00 |
Minimum of Months | 0.127602E+10 | 71076558.37 | 0.113116E+10 | 0.468634E+09 | 0.325450E+09 | 0.00 | 0.00 |
Maximum of Months | 0.179624E+10 | 0.892874E+09 | 0.140499E+10 | 0.963268E+09 | 0.719205E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.526577E+09 | 0.921838E+09 | 0.621070E+09 | 0.298319E+09 | 0.322751E+09 | 0.00 | 0.00 |
February | 0.661229E+09 | 0.748411E+09 | 0.717592E+09 | 0.350236E+09 | 0.367356E+09 | 0.00 | 0.00 |
March | 0.913497E+09 | 0.631941E+09 | 0.904345E+09 | 0.398320E+09 | 0.506025E+09 | 0.00 | 0.00 |
April | 0.124147E+10 | 0.379567E+09 | 0.111909E+10 | 0.496654E+09 | 0.622434E+09 | 0.00 | 0.00 |
May | 0.136127E+10 | 0.261539E+09 | 0.112556E+10 | 0.485216E+09 | 0.640348E+09 | 0.00 | 0.00 |
June | 0.165061E+10 | 0.141677E+09 | 0.117572E+10 | 0.562988E+09 | 0.612736E+09 | 0.00 | 0.00 |
July | 0.164311E+10 | 69179072.89 | 0.110034E+10 | 0.447839E+09 | 0.652497E+09 | 0.00 | 0.00 |
August | 0.156953E+10 | 89795536.94 | 0.110441E+10 | 0.419691E+09 | 0.684721E+09 | 0.00 | 0.00 |
September | 0.124835E+10 | 0.202978E+09 | 0.947924E+09 | 0.416301E+09 | 0.531623E+09 | 0.00 | 0.00 |
October | 0.985820E+09 | 0.453362E+09 | 0.868419E+09 | 0.464315E+09 | 0.404104E+09 | 0.00 | 0.00 |
November | 0.606107E+09 | 0.674883E+09 | 0.664771E+09 | 0.331600E+09 | 0.333171E+09 | 0.00 | 0.00 |
December | 0.471636E+09 | 0.935901E+09 | 0.583573E+09 | 0.312337E+09 | 0.271236E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.128792E+11 | 0.551107E+10 | 0.109328E+11 | 0.498382E+10 | 0.594900E+10 | 0.00 | 0.00 |
Minimum of Months | 0.471636E+09 | 69179072.89 | 0.583573E+09 | 0.298319E+09 | 0.271236E+09 | 0.00 | 0.00 |
Maximum of Months | 0.165061E+10 | 0.935901E+09 | 0.117572E+10 | 0.562988E+09 | 0.684721E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.119012E+10 | 0.459350E+09 | 0.106049E+10 | 0.824703E+09 | 0.235784E+09 | 0.00 | 0.00 |
February | 0.107996E+10 | 0.379030E+09 | 0.944177E+09 | 0.691007E+09 | 0.253170E+09 | 0.00 | 0.00 |
March | 0.911808E+09 | 0.325604E+09 | 0.777308E+09 | 0.474317E+09 | 0.302991E+09 | 0.00 | 0.00 |
April | 0.712205E+09 | 0.201782E+09 | 0.577717E+09 | 0.236755E+09 | 0.340963E+09 | 0.00 | 0.00 |
May | 0.516000E+09 | 0.136642E+09 | 0.401770E+09 | 90890125.98 | 0.310880E+09 | 0.00 | 0.00 |
June | 0.505678E+09 | 72873556.29 | 0.325035E+09 | 39029062.12 | 0.286006E+09 | 0.00 | 0.00 |
July | 0.623844E+09 | 33140602.75 | 0.371785E+09 | 58335011.33 | 0.313450E+09 | 0.00 | 0.00 |
August | 0.788140E+09 | 44677079.81 | 0.505753E+09 | 0.159511E+09 | 0.346242E+09 | 0.00 | 0.00 |
September | 0.979752E+09 | 0.104192E+09 | 0.694817E+09 | 0.391119E+09 | 0.303698E+09 | 0.00 | 0.00 |
October | 0.122035E+10 | 0.227271E+09 | 0.967293E+09 | 0.711521E+09 | 0.255772E+09 | 0.00 | 0.00 |
November | 0.122448E+10 | 0.342846E+09 | 0.105593E+10 | 0.812665E+09 | 0.243270E+09 | 0.00 | 0.00 |
December | 0.130662E+10 | 0.469402E+09 | 0.115647E+10 | 0.954653E+09 | 0.201820E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.110589E+11 | 0.279681E+10 | 0.883855E+10 | 0.544450E+10 | 0.339405E+10 | 0.00 | 0.00 |
Minimum of Months | 0.505678E+09 | 33140602.75 | 0.325035E+09 | 39029062.12 | 0.201820E+09 | 0.00 | 0.00 |
Maximum of Months | 0.130662E+10 | 0.469402E+09 | 0.115647E+10 | 0.954653E+09 | 0.346242E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.161712E+09 | 0.242860E+10 | 0.685841E+09 | 0.00 | 0.685841E+09 | 0.00 | 0.00 |
February | 0.310825E+09 | 0.195301E+10 | 0.774233E+09 | 0.00 | 0.774233E+09 | 0.00 | 0.00 |
March | 0.753005E+09 | 0.162048E+10 | 0.108145E+10 | 37592.41 | 0.108141E+10 | 0.00 | 0.00 |
April | 0.123757E+10 | 0.941457E+09 | 0.133485E+10 | 17880832.21 | 0.131696E+10 | 0.00 | 0.00 |
May | 0.174755E+10 | 0.647774E+09 | 0.149299E+10 | 97004202.60 | 0.139599E+10 | 0.00 | 0.00 |
June | 0.254991E+10 | 0.360004E+09 | 0.164499E+10 | 0.273565E+09 | 0.137142E+10 | 0.00 | 0.00 |
July | 0.264045E+10 | 0.187462E+09 | 0.155871E+10 | 0.132857E+09 | 0.142585E+10 | 0.00 | 0.00 |
August | 0.225940E+10 | 0.237065E+09 | 0.144656E+10 | 35401431.26 | 0.141115E+10 | 0.00 | 0.00 |
September | 0.150681E+10 | 0.505691E+09 | 0.111753E+10 | 796346.02 | 0.111673E+10 | 0.00 | 0.00 |
October | 0.742236E+09 | 0.114740E+10 | 0.860849E+09 | 0.00 | 0.860849E+09 | 0.00 | 0.00 |
November | 0.254933E+09 | 0.176794E+10 | 0.707481E+09 | 0.00 | 0.707481E+09 | 0.00 | 0.00 |
December | 53597221.77 | 0.252252E+10 | 0.583755E+09 | 0.00 | 0.583755E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.142180E+11 | 0.143194E+11 | 0.132892E+11 | 0.557543E+09 | 0.127317E+11 | 0.00 | 0.00 |
Minimum of Months | 53597221.77 | 0.187462E+09 | 0.583755E+09 | 0.00 | 0.583755E+09 | 0.00 | 0.00 |
Maximum of Months | 0.264045E+10 | 0.252252E+10 | 0.164499E+10 | 0.273565E+09 | 0.142585E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.154015E+09 | 0.246291E+10 | 0.685841E+09 | 0.00 | 0.685841E+09 | 0.00 | 0.00 |
February | 0.301649E+09 | 0.198266E+10 | 0.774233E+09 | 0.00 | 0.774233E+09 | 0.00 | 0.00 |
March | 0.737912E+09 | 0.165172E+10 | 0.108145E+10 | 37592.41 | 0.108141E+10 | 0.00 | 0.00 |
April | 0.121565E+10 | 0.967180E+09 | 0.133485E+10 | 17880832.21 | 0.131696E+10 | 0.00 | 0.00 |
May | 0.171981E+10 | 0.671374E+09 | 0.149299E+10 | 97004202.60 | 0.139599E+10 | 0.00 | 0.00 |
June | 0.251920E+10 | 0.378339E+09 | 0.164499E+10 | 0.273565E+09 | 0.137142E+10 | 0.00 | 0.00 |
July | 0.260828E+10 | 0.203831E+09 | 0.155871E+10 | 0.132857E+09 | 0.142585E+10 | 0.00 | 0.00 |
August | 0.222983E+10 | 0.254946E+09 | 0.144656E+10 | 35401431.26 | 0.141115E+10 | 0.00 | 0.00 |
September | 0.148565E+10 | 0.529974E+09 | 0.111753E+10 | 796346.02 | 0.111673E+10 | 0.00 | 0.00 |
October | 0.727532E+09 | 0.117760E+10 | 0.860849E+09 | 0.00 | 0.860849E+09 | 0.00 | 0.00 |
November | 0.245580E+09 | 0.180040E+10 | 0.707481E+09 | 0.00 | 0.707481E+09 | 0.00 | 0.00 |
December | 49675758.57 | 0.255966E+10 | 0.583755E+09 | 0.00 | 0.583755E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.139948E+11 | 0.146406E+11 | 0.132892E+11 | 0.557543E+09 | 0.127317E+11 | 0.00 | 0.00 |
Minimum of Months | 49675758.57 | 0.203831E+09 | 0.583755E+09 | 0.00 | 0.583755E+09 | 0.00 | 0.00 |
Maximum of Months | 0.260828E+10 | 0.255966E+10 | 0.164499E+10 | 0.273565E+09 | 0.142585E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.182413E+10 | 0.170358E+10 | 0.183544E+10 | 0.113007E+10 | 0.705365E+09 | 0.00 | 0.00 |
February | 0.195865E+10 | 0.140637E+10 | 0.186390E+10 | 0.106758E+10 | 0.796329E+09 | 0.00 | 0.00 |
March | 0.266281E+10 | 0.119913E+10 | 0.231691E+10 | 0.125340E+10 | 0.106352E+10 | 0.00 | 0.00 |
April | 0.345016E+10 | 0.745179E+09 | 0.272762E+10 | 0.138347E+10 | 0.134414E+10 | 0.00 | 0.00 |
May | 0.354226E+10 | 0.536542E+09 | 0.260279E+10 | 0.128083E+10 | 0.132196E+10 | 0.00 | 0.00 |
June | 0.409271E+10 | 0.305337E+09 | 0.266454E+10 | 0.142568E+10 | 0.123886E+10 | 0.00 | 0.00 |
July | 0.422664E+10 | 0.161227E+09 | 0.258623E+10 | 0.126498E+10 | 0.132125E+10 | 0.00 | 0.00 |
August | 0.414552E+10 | 0.199217E+09 | 0.263992E+10 | 0.126492E+10 | 0.137500E+10 | 0.00 | 0.00 |
September | 0.342065E+10 | 0.389414E+09 | 0.231872E+10 | 0.120981E+10 | 0.110891E+10 | 0.00 | 0.00 |
October | 0.294407E+10 | 0.832033E+09 | 0.229978E+10 | 0.144863E+10 | 0.851151E+09 | 0.00 | 0.00 |
November | 0.212694E+10 | 0.125275E+10 | 0.196303E+10 | 0.122404E+10 | 0.738993E+09 | 0.00 | 0.00 |
December | 0.180044E+10 | 0.172437E+10 | 0.183313E+10 | 0.123723E+10 | 0.595904E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.361950E+11 | 0.104551E+11 | 0.276520E+11 | 0.151906E+11 | 0.124614E+11 | 0.00 | 0.00 |
Minimum of Months | 0.180044E+10 | 0.161227E+09 | 0.183313E+10 | 0.106758E+10 | 0.595904E+09 | 0.00 | 0.00 |
Maximum of Months | 0.422664E+10 | 0.172437E+10 | 0.272762E+10 | 0.144863E+10 | 0.137500E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.306880E+10 | 0.192367E+10 | 0.293464E+10 | 0.209933E+10 | 0.835310E+09 | 0.00 | 0.00 |
February | 0.286982E+10 | 0.158454E+10 | 0.266886E+10 | 0.175899E+10 | 0.909867E+09 | 0.00 | 0.00 |
March | 0.262081E+10 | 0.135540E+10 | 0.234940E+10 | 0.120741E+10 | 0.114199E+10 | 0.00 | 0.00 |
April | 0.229052E+10 | 0.814406E+09 | 0.192820E+10 | 0.608802E+09 | 0.131940E+10 | 0.00 | 0.00 |
May | 0.195585E+10 | 0.541303E+09 | 0.153453E+10 | 0.264619E+09 | 0.126991E+10 | 0.00 | 0.00 |
June | 0.219479E+10 | 0.281718E+09 | 0.139130E+10 | 0.193129E+09 | 0.119817E+10 | 0.00 | 0.00 |
July | 0.253658E+10 | 0.131182E+09 | 0.148073E+10 | 0.194039E+09 | 0.128669E+10 | 0.00 | 0.00 |
August | 0.282800E+10 | 0.174197E+09 | 0.178330E+10 | 0.418180E+09 | 0.136512E+10 | 0.00 | 0.00 |
September | 0.306497E+10 | 0.409743E+09 | 0.215178E+10 | 0.995888E+09 | 0.115590E+10 | 0.00 | 0.00 |
October | 0.340235E+10 | 0.925043E+09 | 0.275740E+10 | 0.181121E+10 | 0.946181E+09 | 0.00 | 0.00 |
November | 0.321752E+10 | 0.141064E+10 | 0.293046E+10 | 0.206868E+10 | 0.861782E+09 | 0.00 | 0.00 |
December | 0.330327E+10 | 0.195303E+10 | 0.314397E+10 | 0.243012E+10 | 0.713855E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.333533E+11 | 0.115049E+11 | 0.270546E+11 | 0.140504E+11 | 0.130042E+11 | 0.00 | 0.00 |
Minimum of Months | 0.195585E+10 | 0.131182E+09 | 0.139130E+10 | 0.193129E+09 | 0.713855E+09 | 0.00 | 0.00 |
Maximum of Months | 0.340235E+10 | 0.195303E+10 | 0.314397E+10 | 0.243012E+10 | 0.136512E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 2.60 | -1.3 | -7.5 | 3.29 | -12.5 | 38.91 | 220.14 | 0.00 |
February | 4.28 | 0.13 | -5.8 | 3.80 | -10.7 | 48.21 | 247.44 | 0.00 |
March | 8.76 | 2.64 | -5.5 | 4.72 | -6.0 | 66.36 | 249.43 | 0.00 |
April | 13.90 | 4.70 | -6.4 | 4.61 | -1.8 | 81.54 | 308.98 | 0.00 |
May | 17.82 | 8.42 | -1.1 | 4.68 | 3.61 | 77.67 | 310.50 | 0.00 |
June | 23.21 | 12.42 | 4.15 | 4.28 | 9.16 | 70.88 | 348.57 | 0.00 |
July | 25.63 | 16.13 | 10.74 | 4.00 | 14.07 | 80.74 | 308.61 | 0.00 |
August | 24.08 | 15.39 | 10.38 | 3.96 | 13.00 | 86.20 | 290.42 | 0.00 |
September | 20.49 | 12.87 | 7.70 | 3.48 | 8.22 | 67.00 | 274.65 | 0.00 |
October | 13.71 | 6.72 | -0.1 | 3.54 | -0.8 | 42.11 | 283.53 | 0.00 |
November | 6.96 | 1.72 | -4.9 | 3.43 | -7.6 | 39.44 | 239.51 | 0.01 |
December | 2.07 | -2.2 | -8.9 | 2.95 | -13.5 | 27.44 | 240.96 | 0.00 |
Annual Sum or Average | 13.68 | 6.50 | -0.6 | 3.90 | -0.3 | 60.60 | 276.96 | 0.00 |
Minimum of Months | 2.07 | -2.2 | -8.9 | 2.95 | -13.5 | 27.44 | 220.14 | 0.00 |
Maximum of Months | 25.63 | 16.13 | 10.74 | 4.72 | 14.07 | 86.20 | 348.57 | 0.01 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 16.10 | 01-JAN-14:00 | 5.83 | -6.7 | 5.20 | -2.3 | 27.00 | 880.00 |
February | 22.20 | 14-FEB-15:00 | 7.86 | -10.0 | 4.60 | 4.72 | 61.50 | 778.50 |
March | 22.80 | 08-MAR-13:00 | 9.68 | -2.8 | 3.60 | 4.92 | 122.50 | 851.50 |
April | 26.10 | 13-APR-16:00 | 10.32 | -4.4 | 5.20 | 7.55 | 95.00 | 507.00 |
May | 30.00 | 19-MAY-15:20 | 12.71 | -1.5 | 8.93 | 13.35 | 108.33 | 887.00 |
June | 38.90 | 28-JUN-15:00 | 14.16 | -8.9 | 3.10 | 20.75 | 70.00 | 888.00 |
July | 38.30 | 22-JUL-14:00 | 16.71 | 3.30 | 5.20 | 24.16 | 99.00 | 907.50 |
August | 35.00 | 01-AUG-14:00 | 16.30 | 4.40 | 2.60 | 19.52 | 113.00 | 840.50 |
September | 32.80 | 03-SEP-13:00 | 16.76 | 7.80 | 3.60 | 21.78 | 263.50 | 532.50 |
October | 28.90 | 01-OCT-15:00 | 13.26 | 1.70 | 4.10 | 15.94 | 85.00 | 435.00 |
November | 19.40 | 09-NOV-13:00 | 9.81 | 1.70 | 10.80 | 8.35 | 157.50 | 0.00 |
December | 13.30 | 24-DEC-14:00 | 4.02 | -8.3 | 8.20 | -2.5 | 40.50 | 792.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 13.30 | 4.02 | -10.0 | 2.60 | -2.5 | 27.00 | 0.00 | |
Maximum of Months | 38.90 | 16.76 | 7.80 | 10.80 | 24.16 | 263.50 | 907.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -8.3 | 20-JAN-01:00 | -8.3 | -8.3 | 2.10 | -25.6 | 0.00 | 0.00 |
February | -6.7 | 04-FEB-06:10 | -8.2 | -11.7 | 5.10 | -25.0 | 0.00 | 0.00 |
March | -3.9 | 05-MAR-06:00 | -5.7 | -9.4 | 1.50 | -21.6 | 17.00 | 434.50 |
April | 1.70 | 06-APR-05:00 | -2.4 | -8.3 | 2.60 | -12.9 | 28.00 | 215.00 |
May | 4.40 | 07-MAY-04:00 | -1.0 | -8.3 | 1.50 | -13.7 | 0.00 | 0.00 |
June | 7.80 | 09-JUN-04:40 | 5.54 | 3.30 | 4.83 | -7.8 | 0.00 | 0.00 |
July | 16.10 | 08-JUL-02:00 | 14.67 | 13.90 | 0.00 | 4.72 | 0.00 | 0.00 |
August | 12.80 | 31-AUG-05:00 | 10.77 | 9.40 | 3.10 | -1.7 | 24.50 | 228.50 |
September | 10.60 | 09-SEP-05:00 | 9.95 | 9.40 | 2.10 | -2.5 | 15.50 | 177.00 |
October | -2.8 | 26-OCT-04:10 | -4.1 | -6.1 | 2.42 | -17.7 | 0.00 | 0.00 |
November | -4.4 | 27-NOV-05:00 | -6.9 | -11.7 | 2.60 | -22.7 | 0.00 | 0.00 |
December | -9.4 | 15-DEC-04:00 | -12.1 | -21.7 | 0.00 | -29.7 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -9.4 | -12.1 | -21.7 | 0.00 | -29.7 | 0.00 | 0.00 | |
Maximum of Months | 16.10 | 14.67 | 13.90 | 5.10 | 4.72 | 28.00 | 434.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 6.84 | 05-JAN-13:00 | 16.10 | -2.8 | 3.10 | -0.1 | 62.00 | 873.00 |
February | 7.86 | 14-FEB-15:00 | 22.20 | -10.0 | 4.60 | 4.72 | 61.50 | 778.50 |
March | 9.68 | 08-MAR-13:00 | 22.80 | -2.8 | 3.60 | 4.92 | 122.50 | 851.50 |
April | 10.95 | 14-APR-15:00 | 24.40 | -0.6 | 8.20 | 17.21 | 237.00 | 154.00 |
May | 15.08 | 22-MAY-12:30 | 28.60 | 6.40 | 5.15 | 16.76 | 167.00 | 0.00 |
June | 18.19 | 24-JUN-13:00 | 31.70 | 11.70 | 2.60 | 19.17 | 130.00 | 891.50 |
July | 19.21 | 31-JUL-14:00 | 32.80 | 12.80 | 6.20 | 22.98 | 264.50 | 624.50 |
August | 19.18 | 26-AUG-12:00 | 27.80 | 15.60 | 3.60 | 17.03 | 289.00 | 426.50 |
September | 18.19 | 05-SEP-12:00 | 23.90 | 15.60 | 3.10 | 13.35 | 196.50 | 796.00 |
October | 16.16 | 11-OCT-10:00 | 23.90 | 12.20 | 13.40 | 13.73 | 219.50 | 450.00 |
November | 9.81 | 09-NOV-13:00 | 19.40 | 1.70 | 10.80 | 8.35 | 157.50 | 0.00 |
December | 4.92 | 01-DEC-15:00 | 12.80 | -3.9 | 2.10 | 1.58 | 50.00 | 276.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 4.92 | 12.80 | -10.0 | 2.10 | -0.1 | 50.00 | 0.00 | |
Maximum of Months | 19.21 | 32.80 | 15.60 | 13.40 | 22.98 | 289.00 | 891.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -0.6 | 28-JAN-17:00 | 6.10 | 3.01 | 4.60 | -5.0 | 0.00 | 0.00 |
February | 2.20 | 17-FEB-10:00 | 7.20 | 4.72 | 3.10 | -4.1 | 212.50 | 561.00 |
March | 5.60 | 28-MAR-17:10 | 8.80 | 7.05 | 4.60 | 3.37 | 35.00 | 0.67 |
April | 7.20 | 15-APR-06:00 | 13.30 | 9.79 | 7.20 | 6.35 | 116.00 | 422.00 |
May | 13.90 | 24-MAY-14:00 | 16.70 | 14.90 | 4.60 | 11.07 | 128.00 | 0.00 |
June | 13.30 | 30-JUN-13:00 | 26.70 | 17.72 | 6.70 | 20.75 | 170.00 | 126.50 |
July | 17.80 | 01-JUL-13:00 | 22.20 | 19.05 | 3.60 | 13.91 | 361.00 | 125.00 |
August | 17.20 | 26-AUG-09:00 | 21.70 | 18.59 | 2.60 | 11.65 | 243.50 | 681.50 |
September | 15.60 | 05-SEP-11:00 | 22.20 | 17.61 | 3.10 | 12.79 | 231.00 | 705.00 |
October | 13.90 | 02-OCT-16:00 | 20.60 | 16.04 | 6.20 | 13.54 | 38.50 | 65.00 |
November | 6.10 | 09-NOV-21:00 | 8.90 | 7.38 | 11.80 | 3.69 | 0.00 | 0.00 |
December | 1.10 | 25-DEC-08:00 | 2.20 | 1.65 | 2.10 | -4.1 | 54.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -0.6 | 2.20 | 1.65 | 2.10 | -5.0 | 0.00 | 0.00 | |
Maximum of Months | 17.80 | 26.70 | 19.05 | 11.80 | 20.75 | 361.00 | 705.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 11.28 | 25.87 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 10.91 | 34.17 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 12.10 | 41.92 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 14.59 | 56.24 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 17.73 | 59.47 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 20.66 | 62.98 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 22.59 | 61.22 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 23.01 | 57.83 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 21.78 | 48.11 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 19.25 | 37.89 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 16.11 | 28.37 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 13.20 | 24.17 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 16.97 | 44.90 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 10.91 | 24.17 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 23.01 | 62.98 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH BOOSTER E WATER HEATER
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.770790E+10 | -0.754277E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -165124420.0 | 81.21 | 0.00 | 0.00 |
February | 0.696493E+10 | -0.681596E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -148964071.5 | 81.21 | 0.00 | 0.00 |
March | 0.770606E+10 | -0.754148E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164577876.1 | 81.21 | 0.00 | 0.00 |
April | 0.746747E+10 | -0.730860E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -158876745.7 | 81.21 | 0.00 | 0.00 |
May | 0.770684E+10 | -0.754279E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164052752.0 | 81.21 | 0.00 | 0.00 |
June | 0.745907E+10 | -0.730053E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -158537276.4 | 81.21 | 0.00 | 0.00 |
July | 0.771465E+10 | -0.755086E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -163788044.9 | 81.21 | 0.00 | 0.00 |
August | 0.770662E+10 | -0.754280E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -163816748.2 | 81.21 | 0.00 | 0.00 |
September | 0.746864E+10 | -0.730994E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -158702462.7 | 81.21 | 0.00 | 0.00 |
October | 0.770578E+10 | -0.754144E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164342943.6 | 81.21 | 0.00 | 0.00 |
November | 0.745187E+10 | -0.729244E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -159434671.5 | 81.21 | 0.00 | 0.00 |
December | 0.771600E+10 | -0.755084E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -165156455.1 | 81.21 | 0.00 | 0.00 |
Annual Sum or Average | 0.907758E+11 | -0.888405E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.193537E+10 | 81.21 | 0.00 | 0.00 |
Minimum of Months | 0.696493E+10 | -0.755086E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -165156455.1 | 81.21 | 0.00 | 0.00 |
Maximum of Months | 0.771600E+10 | -0.681596E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -148964071.5 | 81.21 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH LAUNDRY G WATER HEATER
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.120332E+12 | -0.118518E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.181417E+10 | 81.27 | 0.00 | 0.00 |
February | 0.109256E+12 | -0.107616E+12 | 0.00 | 0.00 | 672.00 | 0.00 | -0.163967E+10 | 81.27 | 0.00 | 0.00 |
March | 0.118935E+12 | -0.117119E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.181598E+10 | 81.27 | 0.00 | 0.00 |
April | 0.110985E+12 | -0.109228E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.175770E+10 | 81.26 | 0.00 | 0.00 |
May | 0.109355E+12 | -0.107539E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.181619E+10 | 81.26 | 0.00 | 0.00 |
June | 0.101011E+12 | -0.992535E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.175732E+10 | 81.26 | 0.00 | 0.00 |
July | 0.101097E+12 | -0.992823E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.181511E+10 | 81.25 | 0.00 | 0.00 |
August | 0.100393E+12 | -0.985789E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.181401E+10 | 81.25 | 0.00 | 0.00 |
September | 0.991677E+11 | -0.974148E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.175291E+10 | 81.25 | 0.00 | 0.00 |
October | 0.106764E+12 | -0.104954E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.180916E+10 | 81.26 | 0.00 | 0.00 |
November | 0.108482E+12 | -0.106731E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.175079E+10 | 81.26 | 0.00 | 0.00 |
December | 0.117051E+12 | -0.115240E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.181116E+10 | 81.26 | 0.00 | 0.00 |
Annual Sum or Average | 0.130283E+13 | -0.128148E+13 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.213542E+11 | 81.26 | 0.00 | 0.00 |
Minimum of Months | 0.991677E+11 | -0.118518E+12 | 0.00 | 0.00 | 672.00 | 0.00 | -0.181619E+10 | 81.25 | 0.00 | 0.00 |
Maximum of Months | 0.120332E+12 | -0.974148E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.163967E+10 | 81.27 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.712900E+11 | -0.697064E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.158369E+10 | 58.98 | 0.00 | 0.00 |
February | 0.648885E+11 | -0.634567E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.143176E+10 | 58.98 | 0.00 | 0.00 |
March | 0.701573E+11 | -0.685711E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.158621E+10 | 58.98 | 0.00 | 0.00 |
April | 0.643276E+11 | -0.627919E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.153571E+10 | 58.98 | 0.00 | 0.00 |
May | 0.618917E+11 | -0.603048E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.158684E+10 | 58.98 | 0.00 | 0.00 |
June | 0.557615E+11 | -0.542262E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.153528E+10 | 58.98 | 0.00 | 0.00 |
July | 0.547370E+11 | -0.531515E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.158549E+10 | 58.98 | 0.00 | 0.00 |
August | 0.541833E+11 | -0.525995E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.158387E+10 | 58.98 | 0.00 | 0.00 |
September | 0.541440E+11 | -0.526148E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.152925E+10 | 58.98 | 0.00 | 0.00 |
October | 0.596209E+11 | -0.580437E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.157714E+10 | 58.98 | 0.00 | 0.00 |
November | 0.621446E+11 | -0.606183E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.152628E+10 | 58.98 | 0.00 | 0.00 |
December | 0.684741E+11 | -0.668943E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.157975E+10 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.741621E+12 | -0.722979E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.186413E+11 | 58.98 | 0.00 | 0.00 |
Minimum of Months | 0.541440E+11 | -0.697064E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.158684E+10 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.712900E+11 | -0.525995E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.143176E+10 | 58.98 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 301.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 282.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 351.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 381.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 378.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 412.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 395.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 408.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 359.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 329.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 284.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 265.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4149.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 265.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 412.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.674968E+10 | 67224.73 | 21-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.296643E+10 | 57297.50 | 05-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.271573E+09 | 24316.25 | 05-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.197992E+09 | 15602.78 | 17-APR-22:37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.119317E+09 | 15782.41 | 29-MAY-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 29856682.64 | 13018.82 | 08-JUN-18:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 397185.50 | 661.98 | 31-AUG-05:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 23294588.21 | 15248.21 | 26-SEP-06:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.282588E+09 | 18784.11 | 26-OCT-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.404912E+09 | 32777.88 | 27-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.590336E+10 | 69370.38 | 15-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.169494E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.674968E+10 | 69370.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BASEMENT VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.525753E+10 | 8797.21 | 30-JAN-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.766748E+10 | 8866.44 | 14-FEB-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.114380E+11 | 8925.44 | 12-MAR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.119357E+11 | 9000.79 | 29-APR-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.121654E+11 | 9010.95 | 20-MAY-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.108305E+11 | 9051.45 | 29-JUN-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.940202E+10 | 9067.77 | 23-JUL-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.710897E+10 | 9066.36 | 20-AUG-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.381724E+10 | 9048.64 | 03-SEP-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.186160E+10 | 8556.41 | 02-OCT-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.121957E+10 | 5949.40 | 06-NOV-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.228546E+10 | 6796.78 | 26-DEC-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.849894E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.121957E+10 | 5949.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.121654E+11 | 9067.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.380544E+10 | 3019.63 | 19-JAN-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.307845E+10 | 3018.70 | 04-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.320790E+10 | 2819.80 | 04-MAR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.250613E+10 | 2429.72 | 08-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.252787E+10 | 2415.21 | 05-MAY-07:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.172583E+10 | 2233.12 | 09-JUN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.117853E+10 | 1524.29 | 28-JUL-07:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.101106E+10 | 1566.26 | 04-AUG-07:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.118265E+10 | 1873.02 | 09-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.190701E+10 | 2956.49 | 26-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.274690E+10 | 2639.30 | 12-NOV-05:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.368555E+10 | 3019.17 | 09-DEC-03:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.285633E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.101106E+10 | 1524.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.380544E+10 | 3019.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_2_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.142995E+10 | 1323.07 | 19-JAN-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.117084E+10 | 1241.87 | 06-FEB-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.111816E+10 | 1283.60 | 23-MAR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.850584E+09 | 1353.35 | 24-APR-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.779692E+09 | 1301.26 | 05-MAY-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.551630E+09 | 1260.97 | 09-JUN-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.452772E+09 | 1079.18 | 08-JUL-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.412047E+09 | 1069.80 | 04-AUG-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.407462E+09 | 1090.17 | 09-SEP-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.681206E+09 | 1229.65 | 26-OCT-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.101713E+10 | 1171.36 | 10-NOV-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.143326E+10 | 1285.23 | 08-DEC-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.103047E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.407462E+09 | 1069.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.143326E+10 | 1353.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: MECH_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.344111E+10 | 1911.42 | 21-JAN-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.289360E+10 | 1977.78 | 06-FEB-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.258655E+10 | 1718.75 | 30-MAR-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.186038E+10 | 1731.30 | 08-APR-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.140611E+10 | 1591.88 | 06-MAY-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.695294E+09 | 1319.24 | 09-JUN-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.443759E+09 | 1015.48 | 08-JUL-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.595362E+09 | 1121.02 | 31-AUG-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.983678E+09 | 1291.60 | 09-SEP-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.187516E+10 | 1749.48 | 26-OCT-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.267754E+10 | 1797.48 | 27-NOV-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.351448E+10 | 1906.76 | 23-DEC-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.229730E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.443759E+09 | 1015.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.351448E+10 | 1977.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: STORAGE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.217018E+10 | 1088.89 | 20-JAN-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.183057E+10 | 1106.10 | 06-FEB-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.167392E+10 | 967.94 | 30-MAR-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.121576E+10 | 953.80 | 08-APR-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.929561E+09 | 886.04 | 06-MAY-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.453905E+09 | 740.15 | 09-JUN-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.278173E+09 | 537.77 | 08-JUL-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.377839E+09 | 596.51 | 30-AUG-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.643193E+09 | 695.04 | 09-SEP-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.121995E+10 | 989.49 | 26-OCT-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.171819E+10 | 1006.29 | 27-NOV-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.221164E+10 | 1074.63 | 15-DEC-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.147229E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.278173E+09 | 537.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.221164E+10 | 1106.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LAUNDRY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.136093E+11 | 12632.30 | 21-JAN-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.122287E+11 | 12631.44 | 06-FEB-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.131706E+11 | 13126.06 | 25-MAR-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.127488E+11 | 13248.79 | 29-APR-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.132226E+11 | 13263.73 | 20-MAY-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.133045E+11 | 13324.06 | 29-JUN-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.140561E+11 | 13348.17 | 23-JUL-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.139262E+11 | 13346.09 | 20-AUG-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.130304E+11 | 13320.01 | 03-SEP-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.131222E+11 | 13207.29 | 06-OCT-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.125326E+11 | 12489.64 | 01-NOV-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.136372E+11 | 12450.78 | 26-DEC-04:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.158589E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.122287E+11 | 12450.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.140561E+11 | 13348.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAFE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.563161E+10 | 8794.69 | 17-JAN-09:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.426597E+10 | 8265.10 | 16-FEB-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.455915E+10 | 7817.25 | 21-MAR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.349896E+10 | 6644.28 | 19-APR-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.405620E+10 | 7289.68 | 24-MAY-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.315760E+10 | 6646.05 | 05-JUN-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.210452E+10 | 5370.83 | 03-JUL-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.146235E+10 | 5033.88 | 04-AUG-07:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.124570E+10 | 6767.70 | 08-SEP-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.220346E+10 | 8537.77 | 25-OCT-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.330158E+10 | 7866.51 | 10-NOV-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.518539E+10 | 8957.78 | 08-DEC-09:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.406725E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.124570E+10 | 5033.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.563161E+10 | 8957.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LOBBY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.131495E+11 | 22326.06 | 19-JAN-11:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.104768E+11 | 20519.50 | 21-FEB-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.110019E+11 | 20864.20 | 03-MAR-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.983929E+10 | 21028.75 | 24-APR-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.105728E+11 | 21079.10 | 05-MAY-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.855728E+10 | 21048.28 | 09-JUN-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.685751E+10 | 19183.20 | 03-JUL-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.556590E+10 | 17799.04 | 04-AUG-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.406581E+10 | 18322.39 | 08-SEP-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.543480E+10 | 21341.54 | 25-OCT-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.783987E+10 | 20683.62 | 10-NOV-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.124094E+11 | 22407.77 | 08-DEC-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.105771E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.406581E+10 | 17799.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.131495E+11 | 22407.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.929149E+10 | 9285.64 | 19-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.685670E+10 | 8404.81 | 06-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.482857E+10 | 6642.83 | 03-MAR-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.164863E+10 | 5142.49 | 08-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.841682E+09 | 4958.97 | 05-MAY-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 82900127.10 | 3420.74 | 09-JUN-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 1500226.76 | 1305.04 | 08-SEP-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.157004E+10 | 7622.13 | 26-OCT-06:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.466463E+10 | 6773.98 | 27-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.943212E+10 | 8717.06 | 22-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.392183E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.943212E+10 | 9285.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.106407E+11 | 6966.23 | 21-JAN-06:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.851727E+10 | 6965.23 | 06-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.760887E+10 | 5866.89 | 05-MAR-06:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.480395E+10 | 5011.48 | 08-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.354726E+10 | 4615.72 | 05-MAY-07:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.142338E+10 | 3631.04 | 09-JUN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.371770E+09 | 2014.28 | 02-JUL-04:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.610486E+09 | 2517.46 | 30-AUG-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.175119E+10 | 3356.35 | 09-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.474202E+10 | 6399.79 | 26-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.778758E+10 | 6251.84 | 27-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.107846E+11 | 6966.38 | 09-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.625891E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.371770E+09 | 2014.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.107846E+11 | 6966.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BANQUET_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.435864E+10 | 7979.11 | 09-JAN-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.326189E+10 | 7978.36 | 07-FEB-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.243945E+10 | 7903.74 | 13-MAR-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.136475E+10 | 7036.02 | 04-APR-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.913714E+09 | 7101.94 | 05-MAY-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.459473E+09 | 6184.61 | 09-JUN-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.334621E+09 | 5090.52 | 11-JUL-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.512228E+09 | 5902.43 | 31-AUG-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.794643E+09 | 6561.53 | 19-SEP-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.192860E+10 | 7664.68 | 27-OCT-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.305966E+10 | 7713.01 | 28-NOV-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.464905E+10 | 7972.49 | 19-DEC-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.240767E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.334621E+09 | 5090.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.464905E+10 | 7979.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: DINING_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.374513E+10 | 7723.32 | 09-JAN-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.272267E+10 | 7624.09 | 07-FEB-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.185989E+10 | 7521.15 | 13-MAR-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.916592E+09 | 6533.00 | 04-APR-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.562782E+09 | 6615.52 | 05-MAY-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.249747E+09 | 5684.65 | 09-JUN-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.189391E+09 | 4574.02 | 11-JUL-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.315253E+09 | 5417.75 | 31-AUG-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.513234E+09 | 6164.45 | 19-SEP-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.147301E+10 | 7259.50 | 27-OCT-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.250682E+10 | 7424.83 | 28-NOV-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.404484E+10 | 7618.49 | 19-DEC-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.190993E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.189391E+09 | 4574.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.404484E+10 | 7723.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: KITCHEN_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.244164E+10 | 6011.06 | 20-JAN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.207083E+10 | 5948.48 | 01-FEB-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.179459E+10 | 5281.83 | 04-MAR-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.124167E+10 | 4524.48 | 08-APR-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.972894E+09 | 4105.51 | 05-MAY-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.573294E+09 | 3655.74 | 09-JUN-02:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.368896E+09 | 2425.30 | 02-JUL-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.433100E+09 | 2647.09 | 29-AUG-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.719161E+09 | 3271.11 | 09-SEP-02:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.131222E+10 | 5281.93 | 26-OCT-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.191625E+10 | 5625.35 | 27-NOV-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.246453E+10 | 6010.47 | 15-DEC-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.163091E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.368896E+09 | 2425.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.246453E+10 | 6011.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: FLR_3_DOAS HEATING COIL
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.369318E+11 | 17579.12 | 20-JAN-02:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.309905E+11 | 17203.82 | 01-FEB-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.252133E+11 | 16543.52 | 05-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.127282E+11 | 15204.01 | 08-APR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.527082E+10 | 14547.03 | 07-MAY-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.946234E+09 | 13694.87 | 09-JUN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 37167.12 | 0.56 | 07-JUL-17:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 10903757.70 | 3407.71 | 31-AUG-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.629960E+09 | 7972.84 | 09-SEP-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.135745E+11 | 16283.35 | 26-OCT-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.293647E+11 | 16661.16 | 27-NOV-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.394390E+11 | 17831.62 | 15-DEC-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.195100E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 37167.12 | 0.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.394390E+11 | 17831.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.228014E+10 | 6059.94 | 19-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.153031E+10 | 6059.28 | 16-FEB-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.696359E+09 | 5906.19 | 22-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.131831E+09 | 4810.88 | 29-APR-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 47189524.27 | 4181.42 | 14-MAY-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 8496925.91 | 3871.18 | 03-JUN-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 665604.22 | 1122.82 | 08-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 2767356.19 | 2961.20 | 31-AUG-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 5129650.11 | 3577.76 | 09-SEP-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.299288E+09 | 6042.98 | 25-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.814381E+09 | 5909.19 | 10-NOV-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.224695E+10 | 6059.71 | 08-DEC-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.806350E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 665604.22 | 1122.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.228014E+10 | 6059.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.346212E+10 | 6048.71 | 13-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.232450E+10 | 6048.66 | 16-FEB-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.102513E+10 | 5961.07 | 04-MAR-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.184341E+09 | 4905.68 | 06-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 52614032.05 | 4214.87 | 03-MAY-15:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 8237401.60 | 4019.49 | 03-JUN-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 682768.00 | 1034.95 | 08-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 3207244.69 | 3497.66 | 31-AUG-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6812246.62 | 4105.57 | 24-SEP-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.462921E+09 | 6047.99 | 26-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.148129E+10 | 6047.71 | 28-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.370696E+10 | 6048.65 | 26-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.127188E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 682768.00 | 1034.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.370696E+10 | 6048.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.564930E+09 | 12414.24 | 19-JAN-02:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 22809793.97 | 3964.66 | 09-DEC-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.587740E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.564930E+09 | 12414.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.131361E+11 | 33891.41 | 18-JAN-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.855424E+10 | 33693.36 | 06-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.195561E+10 | 32519.37 | 23-MAR-15:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.190981E+09 | 29516.94 | 10-APR-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 70142553.40 | 28168.88 | 05-MAY-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 35153504.52 | 26501.74 | 21-JUN-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 9935507.68 | 27610.44 | 28-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 26233849.60 | 29602.93 | 03-AUG-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 45346550.87 | 26920.01 | 27-SEP-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.871403E+09 | 33144.71 | 26-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.334530E+10 | 33426.41 | 28-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.151335E+11 | 34389.56 | 21-DEC-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.433739E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 9935507.68 | 26501.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.151335E+11 | 34389.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.241227E+10 | 5931.88 | 19-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.162645E+10 | 5931.93 | 16-FEB-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.691977E+09 | 5785.21 | 22-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.131180E+09 | 3998.47 | 15-APR-18:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 35278864.21 | 3962.43 | 03-MAY-15:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 3117664.31 | 3225.04 | 08-JUN-18:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 174422.56 | 824.14 | 17-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 31020.30 | 218.49 | 29-AUG-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 1323796.15 | 2546.64 | 23-SEP-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.306764E+09 | 5908.51 | 25-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.870495E+09 | 5795.43 | 04-NOV-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.235466E+10 | 5931.67 | 08-DEC-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.843372E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 31020.30 | 218.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.241227E+10 | 5931.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.355847E+10 | 5922.23 | 19-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.240684E+10 | 5922.39 | 16-FEB-19:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.954552E+09 | 5790.51 | 22-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.178939E+09 | 4207.27 | 08-APR-18:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 40915773.81 | 4145.38 | 03-MAY-15:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 3373148.51 | 3195.12 | 08-JUN-18:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 186243.67 | 896.58 | 17-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 75763.94 | 490.34 | 29-AUG-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2261868.22 | 2537.18 | 23-SEP-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.452831E+09 | 5919.05 | 25-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.147914E+10 | 5854.89 | 27-NOV-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.374060E+10 | 5922.06 | 25-DEC-16:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.128182E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 75763.94 | 490.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.374060E+10 | 5922.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.874891E+09 | 1852.62 | 19-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.597353E+09 | 1852.86 | 22-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.299691E+09 | 1833.33 | 22-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 68039976.08 | 1441.23 | 06-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 23497102.48 | 1278.56 | 05-MAY-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 3446924.29 | 1034.95 | 20-JUN-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 47436.49 | 139.11 | 09-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 657692.90 | 828.18 | 31-AUG-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 1755572.92 | 1073.25 | 24-SEP-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.130681E+09 | 1852.54 | 25-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.350686E+09 | 1831.43 | 04-NOV-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.876690E+09 | 1852.53 | 04-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.322744E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 47436.49 | 139.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.876690E+09 | 1852.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.126219E+10 | 1848.99 | 13-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.857234E+09 | 1849.41 | 17-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.412266E+09 | 1848.59 | 04-MAR-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 87694720.72 | 1797.24 | 06-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 25611326.85 | 1349.08 | 05-MAY-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 3221220.59 | 1043.71 | 03-JUN-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 38651.10 | 101.34 | 09-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 689296.87 | 843.08 | 31-AUG-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2226295.73 | 998.61 | 24-SEP-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.195659E+09 | 1848.91 | 25-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.590880E+09 | 1848.79 | 16-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.134815E+10 | 1849.05 | 25-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.478586E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 38651.10 | 101.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.134815E+10 | 1849.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.213917E+10 | 8655.40 | 19-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.143951E+10 | 8595.32 | 16-FEB-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.692603E+09 | 8424.70 | 22-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.179979E+09 | 5432.79 | 12-APR-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 65070734.92 | 6053.13 | 03-MAY-15:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 7753129.52 | 4073.28 | 07-JUN-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5508081.46 | 3186.28 | 09-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 4649350.84 | 3274.63 | 02-AUG-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2081122.15 | 3688.72 | 08-SEP-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.289243E+09 | 8548.15 | 25-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.617086E+09 | 7263.19 | 04-NOV-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.200469E+10 | 8609.39 | 08-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.744734E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 2081122.15 | 3186.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.213917E+10 | 8655.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.399918E+10 | 0.399918E+10 | 72847.89 | 05-JAN-14:10 | 72847.89 | 0.00 |
February | 0.00 | 0.00 | 0.149680E+11 | 0.149680E+11 | 231277.92 | 14-FEB-16:30 | 231277.92 | 0.00 |
March | 0.00 | 0.00 | 0.601961E+11 | 0.601961E+11 | 238364.97 | 08-MAR-16:30 | 238364.97 | 0.00 |
April | 0.00 | 0.00 | 0.194567E+12 | 0.194567E+12 | 289922.73 | 13-APR-17:13 | 289922.73 | 0.00 |
May | 0.00 | 0.00 | 0.342353E+12 | 0.342195E+12 | 330163.97 | 19-MAY-17:12 | 330163.97 | 0.17 |
June | 0.00 | 0.00 | 0.549914E+12 | 0.549446E+12 | 407683.28 | 28-JUN-16:20 | 407683.28 | 0.42 |
July | 0.00 | 0.00 | 0.765277E+12 | 0.696813E+12 | 540015.58 | 31-JUL-18:03 | 260219.40 | 0.93 |
August | 0.00 | 0.00 | 0.680082E+12 | 0.639037E+12 | 465428.96 | 26-AUG-10:35 | 286251.78 | 0.94 |
September | 0.00 | 0.00 | 0.456565E+12 | 0.449369E+12 | 434399.55 | 05-SEP-10:50 | 254537.11 | 0.68 |
October | 0.00 | 0.00 | 0.205680E+12 | 0.204897E+12 | 340764.79 | 11-OCT-10:40 | 271545.46 | 0.16 |
November | 0.00 | 0.00 | 0.115932E+11 | 0.115932E+11 | 161028.29 | 09-NOV-14:00 | 161028.29 | 0.00 |
December | 0.00 | 0.00 | 102015.20 | 102015.20 | 2.26 | 01-DEC-19:06 | 2.26 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.328520E+13 | 0.316708E+13 | 0.28 | |||
Minimum of Months | 0.00 | 0.00 | 102015.20 | 102015.20 | 2.26 | 2.26 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.765277E+12 | 0.696813E+12 | 540015.58 | 407683.28 | 0.94 |
Report: CoilReportMonthly
For: FLR_3_DOAS COOLING COIL
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.119132E+09 | 0.119132E+09 | 4033.62 | 05-JAN-14:00 | 4033.62 | 0.00 |
February | 0.00 | 0.00 | 0.100794E+10 | 0.100794E+10 | 21463.19 | 14-FEB-16:00 | 21463.19 | 0.00 |
March | 0.00 | 0.00 | 0.394114E+10 | 0.394114E+10 | 22751.51 | 08-MAR-14:00 | 22751.51 | 0.00 |
April | 0.00 | 0.00 | 0.157164E+11 | 0.157164E+11 | 29499.20 | 13-APR-17:00 | 29499.20 | 0.00 |
May | 0.00 | 0.00 | 0.310275E+11 | 0.310263E+11 | 37738.79 | 22-MAY-13:00 | 37738.79 | 0.13 |
June | 0.00 | 0.00 | 0.581003E+11 | 0.578737E+11 | 54641.56 | 28-JUN-16:00 | 54641.56 | 0.33 |
July | 0.00 | 0.00 | 0.847239E+11 | 0.740760E+11 | 53799.62 | 22-JUL-15:00 | 53799.62 | 0.90 |
August | 0.00 | 0.00 | 0.717942E+11 | 0.652323E+11 | 48044.34 | 01-AUG-16:00 | 48044.34 | 0.88 |
September | 0.00 | 0.00 | 0.429417E+11 | 0.417535E+11 | 41176.38 | 05-SEP-13:00 | 24733.25 | 0.61 |
October | 0.00 | 0.00 | 0.170638E+11 | 0.169269E+11 | 35370.21 | 01-OCT-16:00 | 35370.21 | 0.14 |
November | 0.00 | 0.00 | 0.449857E+09 | 0.449857E+09 | 14180.63 | 09-NOV-14:00 | 14180.63 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.326886E+12 | 0.308123E+12 | 0.25 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.847239E+11 | 0.740760E+11 | 54641.56 | 54641.56 | 0.90 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.134641E+10 | 0.134641E+10 | 22534.52 | 20-JAN-16:01 | 22534.52 | 0.00 |
February | 0.00 | 0.00 | 0.197603E+10 | 0.197603E+10 | 22533.56 | 17-FEB-16:01 | 22533.56 | 0.00 |
March | 0.00 | 0.00 | 0.309331E+10 | 0.308900E+10 | 22547.21 | 20-MAR-15:01 | 22547.21 | 0.00 |
April | 0.00 | 0.00 | 0.556398E+10 | 0.553261E+10 | 22548.61 | 19-APR-18:01 | 22548.61 | 0.01 |
May | 0.00 | 0.00 | 0.683807E+10 | 0.598752E+10 | 22573.36 | 26-MAY-15:01 | 22573.36 | 0.25 |
June | 0.00 | 0.00 | 0.998814E+10 | 0.770345E+10 | 22578.85 | 25-JUN-18:02 | 22578.85 | 0.57 |
July | 0.00 | 0.00 | 0.124646E+11 | 0.758421E+10 | 24606.55 | 01-JUL-08:61 | 18224.42 | 0.91 |
August | 0.00 | 0.00 | 0.123694E+11 | 0.740996E+10 | 24178.43 | 26-AUG-08:61 | 18459.60 | 0.95 |
September | 0.00 | 0.00 | 0.971822E+10 | 0.622197E+10 | 22577.59 | 25-SEP-18:01 | 22577.59 | 0.79 |
October | 0.00 | 0.00 | 0.650168E+10 | 0.534551E+10 | 22579.94 | 09-OCT-18:01 | 22579.94 | 0.28 |
November | 0.00 | 0.00 | 0.251865E+10 | 0.246902E+10 | 22574.18 | 02-NOV-15:01 | 22574.18 | 0.03 |
December | 0.00 | 0.00 | 0.110500E+10 | 0.110500E+10 | 22529.02 | 26-DEC-16:01 | 22529.02 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.734836E+11 | 0.557707E+11 | 0.32 | |||
Minimum of Months | 0.00 | 0.00 | 0.110500E+10 | 0.110500E+10 | 22529.02 | 18224.42 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.124646E+11 | 0.770345E+10 | 24606.55 | 22579.94 | 0.95 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.236786E+09 | 0.236786E+09 | 22279.46 | 05-JAN-16:01 | 22279.46 | 0.00 |
February | 0.00 | 0.00 | 0.652324E+09 | 0.652324E+09 | 22282.16 | 17-FEB-16:01 | 22282.16 | 0.00 |
March | 0.00 | 0.00 | 0.162033E+10 | 0.161721E+10 | 22287.11 | 16-MAR-15:01 | 22287.11 | 0.00 |
April | 0.00 | 0.00 | 0.435538E+10 | 0.432706E+10 | 22298.28 | 19-APR-18:01 | 22298.28 | 0.01 |
May | 0.00 | 0.00 | 0.634659E+10 | 0.553461E+10 | 22328.62 | 27-MAY-18:01 | 22328.62 | 0.25 |
June | 0.00 | 0.00 | 0.999982E+10 | 0.774261E+10 | 22328.09 | 25-JUN-18:02 | 22328.09 | 0.56 |
July | 0.00 | 0.00 | 0.121238E+11 | 0.734793E+10 | 24245.63 | 01-JUL-08:61 | 18070.24 | 0.91 |
August | 0.00 | 0.00 | 0.112175E+11 | 0.647716E+10 | 23945.79 | 26-AUG-08:61 | 18231.81 | 0.94 |
September | 0.00 | 0.00 | 0.752828E+10 | 0.444663E+10 | 22328.35 | 25-SEP-18:01 | 22328.35 | 0.75 |
October | 0.00 | 0.00 | 0.380258E+10 | 0.292403E+10 | 22323.58 | 11-OCT-18:01 | 22323.58 | 0.25 |
November | 0.00 | 0.00 | 0.610709E+09 | 0.601231E+09 | 22322.80 | 02-NOV-15:01 | 22322.80 | 0.01 |
December | 0.00 | 0.00 | 0.133833E+09 | 0.133833E+09 | 22266.02 | 29-DEC-16:01 | 22266.02 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.586280E+11 | 0.420414E+11 | 0.31 | |||
Minimum of Months | 0.00 | 0.00 | 0.133833E+09 | 0.133833E+09 | 22266.02 | 18070.24 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.121238E+11 | 0.774261E+10 | 24245.63 | 22328.62 | 0.94 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.306635E+11 | 0.306635E+11 | 69442.09 | 01-JAN-13:50 | 69442.09 | 0.00 |
February | 0.00 | 0.00 | 0.298918E+11 | 0.298918E+11 | 69377.62 | 14-FEB-13:00 | 69377.62 | 0.00 |
March | 0.00 | 0.00 | 0.314322E+11 | 0.314322E+11 | 58775.28 | 08-MAR-13:30 | 58775.28 | 0.00 |
April | 0.00 | 0.00 | 0.337194E+11 | 0.337194E+11 | 43493.53 | 13-APR-13:20 | 43493.53 | 0.00 |
May | 0.00 | 0.00 | 0.315319E+11 | 0.287188E+11 | 31905.39 | 13-MAY-13:10 | 31905.39 | 0.15 |
June | 0.00 | 0.00 | 0.412337E+11 | 0.334316E+11 | 35933.54 | 28-JUN-18:15 | 35933.54 | 0.35 |
July | 0.00 | 0.00 | 0.588900E+11 | 0.331885E+11 | 43247.56 | 23-JUL-13:40 | 39274.09 | 0.90 |
August | 0.00 | 0.00 | 0.644360E+11 | 0.405323E+11 | 53275.05 | 20-AUG-13:50 | 38418.02 | 0.91 |
September | 0.00 | 0.00 | 0.652363E+11 | 0.491290E+11 | 68330.53 | 28-SEP-13:20 | 63272.02 | 0.68 |
October | 0.00 | 0.00 | 0.626344E+11 | 0.582839E+11 | 69835.86 | 19-OCT-12:30 | 69835.86 | 0.17 |
November | 0.00 | 0.00 | 0.477806E+11 | 0.477806E+11 | 70614.50 | 20-NOV-12:10 | 70614.50 | 0.00 |
December | 0.00 | 0.00 | 0.328700E+11 | 0.328700E+11 | 70381.29 | 31-DEC-13:40 | 70381.29 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.530320E+12 | 0.449642E+12 | 0.26 | |||
Minimum of Months | 0.00 | 0.00 | 0.298918E+11 | 0.287188E+11 | 31905.39 | 31905.39 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.652363E+11 | 0.582839E+11 | 70614.50 | 70614.50 | 0.91 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.134853E+10 | 0.134853E+10 | 77786.84 | 05-JAN-19:01 | 77786.84 | 0.00 |
February | 0.00 | 0.00 | 0.476566E+10 | 0.476566E+10 | 115234.52 | 15-FEB-19:01 | 115234.52 | 0.00 |
March | 0.00 | 0.00 | 0.166612E+11 | 0.164916E+11 | 118080.37 | 27-MAR-15:01 | 118080.37 | 0.01 |
April | 0.00 | 0.00 | 0.347254E+11 | 0.344872E+11 | 123169.20 | 14-APR-15:01 | 123169.20 | 0.01 |
May | 0.00 | 0.00 | 0.515688E+11 | 0.456326E+11 | 123447.91 | 29-MAY-15:01 | 123447.91 | 0.21 |
June | 0.00 | 0.00 | 0.719567E+11 | 0.597105E+11 | 123456.33 | 15-JUN-15:02 | 123456.33 | 0.48 |
July | 0.00 | 0.00 | 0.879829E+11 | 0.594544E+11 | 132441.68 | 01-JUL-08:61 | 99974.46 | 0.83 |
August | 0.00 | 0.00 | 0.789202E+11 | 0.512828E+11 | 129765.19 | 26-AUG-08:61 | 101901.52 | 0.83 |
September | 0.00 | 0.00 | 0.561629E+11 | 0.383703E+11 | 123385.70 | 30-SEP-15:01 | 123385.70 | 0.61 |
October | 0.00 | 0.00 | 0.303493E+11 | 0.249738E+11 | 123396.25 | 01-OCT-15:01 | 123396.25 | 0.21 |
November | 0.00 | 0.00 | 0.904546E+10 | 0.869677E+10 | 117410.59 | 09-NOV-19:03 | 117410.59 | 0.02 |
December | 0.00 | 0.00 | 0.106766E+10 | 0.106766E+10 | 89005.32 | 01-DEC-19:02 | 89005.32 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.444555E+12 | 0.346282E+12 | 0.27 | |||
Minimum of Months | 0.00 | 0.00 | 0.106766E+10 | 0.106766E+10 | 77786.84 | 77786.84 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.879829E+11 | 0.597105E+11 | 132441.68 | 123456.33 | 0.83 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.129058E+10 | 0.129058E+10 | 19889.27 | 03-JAN-09:01 | 19889.27 | 0.00 |
February | 0.00 | 0.00 | 0.171026E+10 | 0.171026E+10 | 19902.94 | 19-FEB-09:01 | 19902.94 | 0.00 |
March | 0.00 | 0.00 | 0.336828E+10 | 0.336416E+10 | 19921.81 | 29-MAR-08:61 | 19921.81 | 0.00 |
April | 0.00 | 0.00 | 0.640032E+10 | 0.636344E+10 | 19921.99 | 22-APR-08:62 | 19921.99 | 0.01 |
May | 0.00 | 0.00 | 0.771519E+10 | 0.665267E+10 | 19924.80 | 27-MAY-18:01 | 19924.80 | 0.28 |
June | 0.00 | 0.00 | 0.109570E+11 | 0.865332E+10 | 19923.37 | 25-JUN-18:02 | 19923.37 | 0.60 |
July | 0.00 | 0.00 | 0.137671E+11 | 0.888212E+10 | 21458.71 | 01-JUL-08:61 | 16223.65 | 0.94 |
August | 0.00 | 0.00 | 0.133051E+11 | 0.838748E+10 | 19923.05 | 20-AUG-18:01 | 19923.05 | 0.98 |
September | 0.00 | 0.00 | 0.100242E+11 | 0.661327E+10 | 20357.12 | 06-SEP-08:62 | 16806.66 | 0.82 |
October | 0.00 | 0.00 | 0.656249E+10 | 0.540305E+10 | 19922.03 | 01-OCT-15:01 | 19922.03 | 0.30 |
November | 0.00 | 0.00 | 0.252337E+10 | 0.246576E+10 | 19920.03 | 02-NOV-15:01 | 19920.03 | 0.03 |
December | 0.00 | 0.00 | 0.103711E+10 | 0.103711E+10 | 19889.31 | 29-DEC-09:01 | 19889.31 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.786611E+11 | 0.608232E+11 | 0.33 | |||
Minimum of Months | 0.00 | 0.00 | 0.103711E+10 | 0.103711E+10 | 19889.27 | 16223.65 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.137671E+11 | 0.888212E+10 | 21458.71 | 19924.80 | 0.98 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.200567E+09 | 0.200567E+09 | 17116.95 | 01-JAN-09:01 | 17116.95 | 0.00 |
February | 0.00 | 0.00 | 0.426518E+09 | 0.426518E+09 | 19729.32 | 19-FEB-09:01 | 19729.32 | 0.00 |
March | 0.00 | 0.00 | 0.166932E+10 | 0.166627E+10 | 19747.05 | 29-MAR-08:61 | 19747.05 | 0.00 |
April | 0.00 | 0.00 | 0.505881E+10 | 0.502321E+10 | 19747.45 | 22-APR-08:62 | 19747.45 | 0.01 |
May | 0.00 | 0.00 | 0.718195E+10 | 0.615755E+10 | 19750.26 | 27-MAY-18:01 | 19750.26 | 0.28 |
June | 0.00 | 0.00 | 0.109567E+11 | 0.868480E+10 | 19748.52 | 25-JUN-18:02 | 19748.52 | 0.60 |
July | 0.00 | 0.00 | 0.134128E+11 | 0.858891E+10 | 21174.81 | 01-JUL-08:61 | 16133.34 | 0.94 |
August | 0.00 | 0.00 | 0.121387E+11 | 0.733246E+10 | 19750.04 | 20-AUG-18:01 | 19750.04 | 0.98 |
September | 0.00 | 0.00 | 0.777069E+10 | 0.468146E+10 | 20196.22 | 06-SEP-08:62 | 16567.99 | 0.81 |
October | 0.00 | 0.00 | 0.368095E+10 | 0.273694E+10 | 19749.25 | 01-OCT-15:01 | 19749.25 | 0.28 |
November | 0.00 | 0.00 | 0.604338E+09 | 0.578474E+09 | 19724.05 | 12-NOV-09:01 | 19724.05 | 0.01 |
December | 0.00 | 0.00 | 0.105666E+09 | 0.105666E+09 | 17652.94 | 30-DEC-09:01 | 17652.94 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.632071E+11 | 0.461828E+11 | 0.33 | |||
Minimum of Months | 0.00 | 0.00 | 0.105666E+09 | 0.105666E+09 | 17116.95 | 16133.34 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.134128E+11 | 0.868480E+10 | 21174.81 | 19750.26 | 0.98 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.343709E+09 | 0.343709E+09 | 6082.39 | 20-JAN-16:01 | 6082.39 | 0.00 |
February | 0.00 | 0.00 | 0.525916E+09 | 0.525916E+09 | 6082.28 | 17-FEB-16:01 | 6082.28 | 0.00 |
March | 0.00 | 0.00 | 0.839811E+09 | 0.839694E+09 | 6086.00 | 20-MAR-15:01 | 6086.00 | 0.00 |
April | 0.00 | 0.00 | 0.158550E+10 | 0.157814E+10 | 6086.17 | 19-APR-18:01 | 6086.17 | 0.01 |
May | 0.00 | 0.00 | 0.199825E+10 | 0.176452E+10 | 6092.86 | 26-MAY-15:01 | 6092.86 | 0.26 |
June | 0.00 | 0.00 | 0.293646E+10 | 0.231021E+10 | 6094.46 | 17-JUN-08:61 | 6094.46 | 0.58 |
July | 0.00 | 0.00 | 0.364319E+10 | 0.233453E+10 | 6772.17 | 01-JUL-08:61 | 4846.26 | 0.92 |
August | 0.00 | 0.00 | 0.357284E+10 | 0.226318E+10 | 6665.17 | 26-AUG-08:61 | 4905.94 | 0.96 |
September | 0.00 | 0.00 | 0.273784E+10 | 0.183473E+10 | 6093.97 | 25-SEP-18:01 | 6093.97 | 0.79 |
October | 0.00 | 0.00 | 0.176352E+10 | 0.146911E+10 | 6094.68 | 09-OCT-18:01 | 6094.68 | 0.28 |
November | 0.00 | 0.00 | 0.634505E+09 | 0.623266E+09 | 6093.44 | 02-NOV-15:01 | 6093.44 | 0.02 |
December | 0.00 | 0.00 | 0.275016E+09 | 0.275016E+09 | 6081.06 | 26-DEC-16:01 | 6081.06 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.208566E+11 | 0.161620E+11 | 0.32 | |||
Minimum of Months | 0.00 | 0.00 | 0.275016E+09 | 0.275016E+09 | 6081.06 | 4846.26 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.364319E+10 | 0.233453E+10 | 6772.17 | 6094.68 | 0.96 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 61469492.76 | 61469492.76 | 6002.35 | 05-JAN-16:01 | 6002.35 | 0.00 |
February | 0.00 | 0.00 | 0.174969E+09 | 0.174969E+09 | 6003.00 | 17-FEB-16:01 | 6003.00 | 0.00 |
March | 0.00 | 0.00 | 0.444405E+09 | 0.444385E+09 | 6004.50 | 16-MAR-15:01 | 6004.50 | 0.00 |
April | 0.00 | 0.00 | 0.125324E+10 | 0.124666E+10 | 6007.29 | 19-APR-18:01 | 6007.29 | 0.01 |
May | 0.00 | 0.00 | 0.186245E+10 | 0.163824E+10 | 6013.77 | 26-MAY-15:01 | 6013.77 | 0.25 |
June | 0.00 | 0.00 | 0.293673E+10 | 0.231535E+10 | 6015.56 | 17-JUN-08:61 | 6015.56 | 0.58 |
July | 0.00 | 0.00 | 0.355246E+10 | 0.225914E+10 | 6656.66 | 01-JUL-08:61 | 4799.13 | 0.92 |
August | 0.00 | 0.00 | 0.326707E+10 | 0.199192E+10 | 6595.76 | 26-AUG-08:61 | 4832.41 | 0.95 |
September | 0.00 | 0.00 | 0.214754E+10 | 0.132145E+10 | 6015.31 | 25-SEP-18:01 | 6015.31 | 0.77 |
October | 0.00 | 0.00 | 0.103792E+10 | 0.809853E+09 | 6015.82 | 09-OCT-18:01 | 6015.82 | 0.26 |
November | 0.00 | 0.00 | 0.150284E+09 | 0.148784E+09 | 6014.09 | 02-NOV-15:01 | 6014.09 | 0.01 |
December | 0.00 | 0.00 | 31405776.05 | 31405776.05 | 5996.82 | 02-DEC-16:01 | 5996.82 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.169199E+11 | 0.124436E+11 | 0.31 | |||
Minimum of Months | 0.00 | 0.00 | 31405776.05 | 31405776.05 | 5996.82 | 4799.13 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.355246E+10 | 0.231535E+10 | 6656.66 | 6015.82 | 0.95 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.741363E+10 | 0.741363E+10 | 25180.54 | 20-JAN-16:01 | 25180.54 | 0.00 |
February | 0.00 | 0.00 | 0.732802E+10 | 0.732802E+10 | 25194.64 | 19-FEB-09:01 | 25194.64 | 0.00 |
March | 0.00 | 0.00 | 0.745554E+10 | 0.743615E+10 | 25201.77 | 08-MAR-09:01 | 25201.77 | 0.01 |
April | 0.00 | 0.00 | 0.856386E+10 | 0.851199E+10 | 25185.94 | 21-APR-15:01 | 25185.94 | 0.01 |
May | 0.00 | 0.00 | 0.893443E+10 | 0.768958E+10 | 25221.05 | 26-MAY-15:01 | 25221.05 | 0.27 |
June | 0.00 | 0.00 | 0.121294E+11 | 0.923353E+10 | 25222.27 | 22-JUN-15:02 | 25222.27 | 0.59 |
July | 0.00 | 0.00 | 0.170163E+11 | 0.108117E+11 | 27753.34 | 01-JUL-08:61 | 20018.44 | 0.91 |
August | 0.00 | 0.00 | 0.180495E+11 | 0.119067E+11 | 27171.81 | 26-AUG-08:61 | 20641.22 | 0.95 |
September | 0.00 | 0.00 | 0.168107E+11 | 0.122488E+11 | 25223.58 | 21-SEP-15:02 | 25223.58 | 0.81 |
October | 0.00 | 0.00 | 0.146473E+11 | 0.129970E+11 | 25220.05 | 05-OCT-15:01 | 25220.05 | 0.32 |
November | 0.00 | 0.00 | 0.100986E+11 | 0.993315E+10 | 25226.57 | 02-NOV-15:01 | 25226.57 | 0.05 |
December | 0.00 | 0.00 | 0.805730E+10 | 0.805730E+10 | 25173.62 | 26-DEC-16:01 | 25173.62 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.136505E+12 | 0.113568E+12 | 0.33 | |||
Minimum of Months | 0.00 | 0.00 | 0.732802E+10 | 0.732802E+10 | 25173.62 | 20018.44 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.180495E+11 | 0.129970E+11 | 27753.34 | 25226.57 | 0.95 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 56415.72 | 183808.96 | 21-JAN-07:10 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 49333.07 | 172682.67 | 05-FEB-09:02 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 36836.83 | 109002.62 | 22-MAR-08:62 |
April | 0.00 | 0.00 | 01-APR-00:10 | 26210.35 | 94462.42 | 10-APR-08:03 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 21568.85 | 89815.36 | 05-MAY-10:40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 16494.23 | 79518.19 | 09-JUN-10:40 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 13345.81 | 64753.56 | 10-JUL-08:04 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11987.30 | 67562.24 | 29-AUG-10:35 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 11431.50 | 66353.14 | 05-SEP-10:35 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 20808.64 | 143611.05 | 25-OCT-08:62 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 35313.68 | 119699.91 | 04-NOV-15:02 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 56476.65 | 172480.00 | 15-DEC-07:10 |
Annual Sum or Average | 0.00 | 29603.98 | ||||
Minimum of Months | 0.00 | 0.00 | 11431.50 | 64753.56 | ||
Maximum of Months | 0.00 | 0.00 | 56476.65 | 183808.96 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 20351.86 | 214780.07 | 01-JAN-16:01 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 29644.29 | 478135.78 | 14-FEB-16:02 | 0.00 | 0.00 | 01-FEB-00:05 |
March | 53500.84 | 489115.64 | 08-MAR-16:01 | 0.00 | 0.00 | 01-MAR-00:03 |
April | 126539.61 | 542827.75 | 13-APR-18:01 | 0.00 | 0.00 | 01-APR-00:10 |
May | 192857.14 | 589178.05 | 19-MAY-18:03 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 309448.63 | 695489.24 | 28-JUN-15:03 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 409213.30 | 840680.02 | 31-JUL-18:02 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 370422.09 | 669040.39 | 20-AUG-18:03 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 269491.42 | 631192.89 | 20-SEP-15:02 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 138388.20 | 599591.85 | 06-OCT-15:01 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 37574.69 | 354729.04 | 02-NOV-15:01 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 19589.38 | 144882.04 | 31-DEC-16:03 | 0.00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 165631.99 | 0.00 | ||||
Minimum of Months | 19589.38 | 144882.04 | 0.00 | 0.00 | ||
Maximum of Months | 409213.30 | 840680.02 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 27591.51 | 56404.32 | 30-JAN-07:15 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 27796.52 | 56461.11 | 08-FEB-07:15 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 27168.48 | 55896.74 | 01-MAR-08:00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 25795.66 | 53444.53 | 03-APR-06:40 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 24089.66 | 50315.12 | 01-MAY-07:00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22499.34 | 46642.07 | 01-JUN-07:00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21425.68 | 43669.40 | 03-JUL-06:15 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 21220.30 | 42890.56 | 31-AUG-06:15 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21878.89 | 44996.80 | 29-SEP-06:20 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 23247.32 | 48510.85 | 31-OCT-07:00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 24959.02 | 52061.11 | 30-NOV-07:50 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 26544.06 | 54869.58 | 29-DEC-07:20 |
Annual Sum or Average | 0.00 | 24499.14 | ||||
Minimum of Months | 0.00 | 0.00 | 21220.30 | 42890.56 | ||
Maximum of Months | 0.00 | 0.00 | 27796.52 | 56461.11 |
Report: FanReportMonthly
For: FLR_3_DOAS FAN
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.587890E+10 | 1.07 | 2194.93 | 01-JAN-00:05 | 1.07 |
February | 0.530997E+10 | 1.07 | 2194.93 | 01-FEB-00:05 | 1.07 |
March | 0.587890E+10 | 1.07 | 2194.93 | 01-MAR-00:03 | 1.07 |
April | 0.568926E+10 | 1.07 | 2194.93 | 01-APR-00:10 | 1.07 |
May | 0.587890E+10 | 1.07 | 2194.93 | 01-MAY-00:10 | 1.07 |
June | 0.568926E+10 | 1.06 | 2194.93 | 01-JUN-00:10 | 1.07 |
July | 0.587890E+10 | 1.06 | 2194.93 | 01-JUL-00:10 | 1.06 |
August | 0.587890E+10 | 1.06 | 2194.93 | 01-AUG-00:10 | 1.06 |
September | 0.568926E+10 | 1.06 | 2194.93 | 01-SEP-00:10 | 1.06 |
October | 0.587890E+10 | 1.07 | 2194.93 | 01-OCT-00:10 | 1.06 |
November | 0.568926E+10 | 1.07 | 2194.93 | 01-NOV-00:10 | 1.07 |
December | 0.587890E+10 | 1.07 | 2194.93 | 01-DEC-00:03 | 1.07 |
Annual Sum or Average | 0.692193E+11 | 1.07 | |||
Minimum of Months | 0.530997E+10 | 1.06 | 2194.93 | 1.06 | |
Maximum of Months | 0.587890E+10 | 1.07 | 2194.93 | 1.07 |
Report: FanReportMonthly
For: VAV WITH REHEAT FAN
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.159449E+12 | 2.24 | 59531.59 | 01-JAN-00:05 | 2.24 |
February | 0.144018E+12 | 2.24 | 59531.59 | 01-FEB-00:05 | 2.24 |
March | 0.159449E+12 | 2.24 | 59531.59 | 01-MAR-00:03 | 2.23 |
April | 0.154305E+12 | 2.24 | 59531.59 | 01-APR-00:10 | 2.23 |
May | 0.159449E+12 | 2.23 | 59531.59 | 01-MAY-00:10 | 2.24 |
June | 0.154306E+12 | 2.22 | 59531.59 | 01-JUN-00:10 | 2.23 |
July | 0.159449E+12 | 2.21 | 59531.59 | 01-JUL-00:10 | 2.21 |
August | 0.159449E+12 | 2.21 | 59531.59 | 01-AUG-00:10 | 2.20 |
September | 0.154306E+12 | 2.22 | 59531.59 | 01-SEP-00:10 | 2.21 |
October | 0.159449E+12 | 2.23 | 59531.59 | 01-OCT-00:10 | 2.22 |
November | 0.154305E+12 | 2.24 | 59531.59 | 01-NOV-00:10 | 2.24 |
December | 0.159449E+12 | 2.24 | 59531.59 | 01-DEC-00:03 | 2.23 |
Annual Sum or Average | 0.187738E+13 | 2.23 | |||
Minimum of Months | 0.144018E+12 | 2.21 | 59531.59 | 2.20 | |
Maximum of Months | 0.159449E+12 | 2.24 | 59531.59 | 2.24 |
Report: FanReportMonthly
For: LAUNDRY_FLR_1 EXHAUST FAN
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.493775E+09 | 0.78 | 184.35 | 01-JAN-00:05 | 0.78 |
February | 0.445990E+09 | 0.78 | 184.35 | 01-FEB-00:05 | 0.78 |
March | 0.493775E+09 | 0.78 | 184.35 | 01-MAR-00:03 | 0.78 |
April | 0.477847E+09 | 0.78 | 184.35 | 01-APR-00:10 | 0.78 |
May | 0.493775E+09 | 0.78 | 184.35 | 01-MAY-00:10 | 0.78 |
June | 0.477847E+09 | 0.78 | 184.35 | 01-JUN-00:10 | 0.78 |
July | 0.493775E+09 | 0.77 | 184.35 | 01-JUL-00:10 | 0.77 |
August | 0.493775E+09 | 0.77 | 184.35 | 01-AUG-00:10 | 0.77 |
September | 0.477847E+09 | 0.77 | 184.35 | 01-SEP-00:10 | 0.77 |
October | 0.493775E+09 | 0.78 | 184.35 | 01-OCT-00:10 | 0.78 |
November | 0.477847E+09 | 0.78 | 184.35 | 01-NOV-00:10 | 0.78 |
December | 0.493775E+09 | 0.78 | 184.35 | 01-DEC-00:03 | 0.78 |
Annual Sum or Average | 0.581380E+10 | 0.78 | |||
Minimum of Months | 0.445990E+09 | 0.77 | 184.35 | 0.77 | |
Maximum of Months | 0.493775E+09 | 0.78 | 184.35 | 0.78 |
Report: FanReportMonthly
For: LOBBY_FLR_1 EXHAUST FAN
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: BANQUET_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: DINING_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.279806E+10 | 0.55 | 1474.84 | 01-JAN-07:10 | 0.78 |
February | 0.252728E+10 | 0.55 | 1474.84 | 01-FEB-07:10 | 0.78 |
March | 0.279806E+10 | 0.55 | 1474.84 | 01-MAR-07:10 | 0.78 |
April | 0.270780E+10 | 0.55 | 1474.84 | 01-APR-06:10 | 0.78 |
May | 0.279806E+10 | 0.55 | 1474.84 | 01-MAY-06:05 | 0.78 |
June | 0.270780E+10 | 0.55 | 1474.84 | 01-JUN-06:05 | 0.77 |
July | 0.279806E+10 | 0.54 | 1474.84 | 01-JUL-06:10 | 0.77 |
August | 0.279806E+10 | 0.55 | 1474.84 | 01-AUG-06:05 | 0.77 |
September | 0.270780E+10 | 0.55 | 1474.84 | 01-SEP-06:05 | 0.77 |
October | 0.279806E+10 | 0.55 | 1474.84 | 01-OCT-06:10 | 0.77 |
November | 0.270780E+10 | 0.55 | 1474.84 | 01-NOV-06:05 | 0.77 |
December | 0.279806E+10 | 0.55 | 1474.84 | 01-DEC-07:05 | 0.78 |
Annual Sum or Average | 0.329449E+11 | 0.55 | |||
Minimum of Months | 0.252728E+10 | 0.54 | 1474.84 | 0.77 | |
Maximum of Months | 0.279806E+10 | 0.55 | 1474.84 | 0.78 |
Report: FanReportMonthly
For: ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.792233E+09 | 1.36 | 2585.88 | 01-JAN-16:01 | 1.69 |
February | 0.680007E+09 | 1.37 | 2585.88 | 01-FEB-09:01 | 1.69 |
March | 0.628988E+09 | 1.39 | 2585.88 | 03-MAR-09:02 | 1.68 |
April | 0.741604E+09 | 1.49 | 2585.88 | 01-APR-15:01 | 1.69 |
May | 0.851748E+09 | 1.48 | 2585.88 | 01-MAY-15:01 | 1.69 |
June | 0.118303E+10 | 1.55 | 2585.88 | 01-JUN-15:01 | 1.67 |
July | 0.136457E+10 | 1.59 | 2585.88 | 01-JUL-08:61 | 1.66 |
August | 0.139341E+10 | 1.59 | 2585.88 | 01-AUG-08:61 | 1.67 |
September | 0.112735E+10 | 1.56 | 2585.88 | 01-SEP-08:62 | 1.67 |
October | 0.882631E+09 | 1.50 | 2585.88 | 01-OCT-08:61 | 1.67 |
November | 0.587657E+09 | 1.41 | 2585.88 | 01-NOV-15:01 | 1.68 |
December | 0.757422E+09 | 1.36 | 2585.88 | 01-DEC-16:01 | 1.69 |
Annual Sum or Average | 0.109906E+11 | 1.47 | |||
Minimum of Months | 0.587657E+09 | 1.36 | 2585.88 | 1.66 | |
Maximum of Months | 0.139341E+10 | 1.59 | 2585.88 | 1.69 |
Report: FanReportMonthly
For: ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.920642E+09 | 1.26 | 2557.11 | 01-JAN-09:01 | 1.69 |
February | 0.705310E+09 | 1.25 | 2557.11 | 01-FEB-09:01 | 1.69 |
March | 0.544082E+09 | 1.27 | 2557.11 | 03-MAR-09:02 | 1.68 |
April | 0.619193E+09 | 1.38 | 2557.11 | 01-APR-15:01 | 1.69 |
May | 0.797407E+09 | 1.44 | 2557.11 | 01-MAY-15:01 | 1.69 |
June | 0.118447E+10 | 1.54 | 2557.11 | 01-JUN-15:01 | 1.67 |
July | 0.132901E+10 | 1.59 | 2557.11 | 01-JUL-08:61 | 1.66 |
August | 0.126721E+10 | 1.57 | 2557.11 | 01-AUG-08:61 | 1.67 |
September | 0.887083E+09 | 1.50 | 2557.11 | 01-SEP-08:62 | 1.67 |
October | 0.626479E+09 | 1.34 | 2557.11 | 01-OCT-08:61 | 1.67 |
November | 0.544092E+09 | 1.25 | 2557.11 | 01-NOV-15:01 | 1.68 |
December | 0.960687E+09 | 1.27 | 2557.11 | 02-DEC-09:02 | 1.69 |
Annual Sum or Average | 0.103857E+11 | 1.39 | |||
Minimum of Months | 0.544082E+09 | 1.25 | 2557.11 | 1.66 | |
Maximum of Months | 0.132901E+10 | 1.59 | 2557.11 | 1.69 |
Report: FanReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.343716E+10 | 0.79 | 7401.73 | 01-JAN-13:50 | 1.69 |
February | 0.314892E+10 | 0.84 | 7397.00 | 14-FEB-13:00 | 1.69 |
March | 0.333340E+10 | 1.00 | 6411.99 | 08-MAR-13:30 | 1.69 |
April | 0.360286E+10 | 1.30 | 4179.79 | 13-APR-13:20 | 1.69 |
May | 0.346276E+10 | 1.38 | 3144.95 | 13-MAY-13:10 | 1.69 |
June | 0.438380E+10 | 1.55 | 3584.94 | 29-JUN-13:40 | 1.68 |
July | 0.572199E+10 | 1.66 | 4273.33 | 23-JUL-14:00 | 1.68 |
August | 0.627828E+10 | 1.66 | 6759.66 | 20-AUG-13:50 | 1.68 |
September | 0.690151E+10 | 1.65 | 8679.82 | 28-SEP-13:20 | 1.68 |
October | 0.664901E+10 | 1.41 | 8737.28 | 01-OCT-13:30 | 1.68 |
November | 0.505940E+10 | 1.10 | 7512.74 | 20-NOV-12:10 | 1.69 |
December | 0.348976E+10 | 0.78 | 7493.67 | 31-DEC-13:40 | 1.69 |
Annual Sum or Average | 0.554688E+11 | 1.26 | |||
Minimum of Months | 0.314892E+10 | 0.78 | 3144.95 | 1.68 | |
Maximum of Months | 0.690151E+10 | 1.66 | 8737.28 | 1.69 |
Report: FanReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.374951E+10 | 1.20 | 14036.20 | 02-JAN-09:01 | 1.69 |
February | 0.300629E+10 | 1.20 | 14036.20 | 01-FEB-09:01 | 1.69 |
March | 0.280623E+10 | 1.20 | 14036.20 | 06-MAR-19:01 | 1.69 |
April | 0.419763E+10 | 1.20 | 14036.20 | 01-APR-08:62 | 1.69 |
May | 0.600880E+10 | 1.25 | 14036.20 | 01-MAY-08:62 | 1.68 |
June | 0.849837E+10 | 1.40 | 14036.20 | 01-JUN-08:62 | 1.68 |
July | 0.968115E+10 | 1.48 | 14036.20 | 01-JUL-08:61 | 1.66 |
August | 0.878441E+10 | 1.40 | 14036.20 | 01-AUG-08:61 | 1.67 |
September | 0.626835E+10 | 1.26 | 14036.20 | 01-SEP-08:62 | 1.67 |
October | 0.389182E+10 | 1.20 | 14036.20 | 01-OCT-08:61 | 1.68 |
November | 0.235800E+10 | 1.19 | 14036.20 | 01-NOV-15:01 | 1.68 |
December | 0.414585E+10 | 1.20 | 14036.20 | 03-DEC-16:02 | 1.69 |
Annual Sum or Average | 0.633964E+11 | 1.26 | |||
Minimum of Months | 0.235800E+10 | 1.19 | 14036.20 | 1.66 | |
Maximum of Months | 0.968115E+10 | 1.48 | 14036.20 | 1.69 |
Report: FanReportMonthly
For: ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.750139E+09 | 1.38 | 2281.66 | 01-JAN-09:01 | 1.69 |
February | 0.624246E+09 | 1.37 | 2281.66 | 01-FEB-19:01 | 1.68 |
March | 0.626576E+09 | 1.45 | 2281.66 | 02-MAR-09:01 | 1.69 |
April | 0.811300E+09 | 1.60 | 2281.66 | 01-APR-08:62 | 1.69 |
May | 0.934749E+09 | 1.59 | 2281.66 | 01-MAY-08:62 | 1.68 |
June | 0.128229E+10 | 1.63 | 2281.66 | 01-JUN-08:62 | 1.67 |
July | 0.149502E+10 | 1.65 | 2281.66 | 01-JUL-08:61 | 1.66 |
August | 0.145515E+10 | 1.64 | 2281.66 | 01-AUG-08:61 | 1.67 |
September | 0.114094E+10 | 1.61 | 2281.66 | 01-SEP-08:62 | 1.67 |
October | 0.872331E+09 | 1.55 | 2281.66 | 01-OCT-08:61 | 1.67 |
November | 0.576306E+09 | 1.45 | 2281.66 | 01-NOV-08:62 | 1.68 |
December | 0.706904E+09 | 1.31 | 2281.66 | 02-DEC-16:01 | 1.69 |
Annual Sum or Average | 0.112760E+11 | 1.52 | |||
Minimum of Months | 0.576306E+09 | 1.31 | 2281.66 | 1.66 | |
Maximum of Months | 0.149502E+10 | 1.65 | 2281.66 | 1.69 |
Report: FanReportMonthly
For: ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.853310E+09 | 1.25 | 2261.66 | 02-JAN-19:02 | 1.69 |
February | 0.630670E+09 | 1.21 | 2261.66 | 01-FEB-09:01 | 1.69 |
March | 0.493097E+09 | 1.26 | 2261.66 | 02-MAR-09:01 | 1.69 |
April | 0.680907E+09 | 1.53 | 2261.66 | 01-APR-08:62 | 1.69 |
May | 0.880541E+09 | 1.57 | 2261.66 | 01-MAY-08:62 | 1.68 |
June | 0.129192E+10 | 1.63 | 2261.66 | 01-JUN-08:62 | 1.67 |
July | 0.146260E+10 | 1.64 | 2261.66 | 01-JUL-08:61 | 1.66 |
August | 0.132973E+10 | 1.64 | 2261.66 | 01-AUG-08:61 | 1.67 |
September | 0.897144E+09 | 1.60 | 2261.66 | 01-SEP-08:62 | 1.67 |
October | 0.588751E+09 | 1.39 | 2261.66 | 01-OCT-08:61 | 1.67 |
November | 0.490377E+09 | 1.20 | 2261.66 | 01-NOV-08:62 | 1.68 |
December | 0.871968E+09 | 1.25 | 2261.66 | 02-DEC-19:02 | 1.69 |
Annual Sum or Average | 0.104710E+11 | 1.43 | |||
Minimum of Months | 0.490377E+09 | 1.20 | 2261.66 | 1.66 | |
Maximum of Months | 0.146260E+10 | 1.64 | 2261.66 | 1.69 |
Report: FanReportMonthly
For: ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.247965E+09 | 1.37 | 698.03 | 01-JAN-16:01 | 1.69 |
February | 0.209831E+09 | 1.39 | 698.03 | 01-FEB-09:01 | 1.69 |
March | 0.190354E+09 | 1.40 | 698.03 | 03-MAR-09:02 | 1.68 |
April | 0.216050E+09 | 1.51 | 698.03 | 01-APR-15:01 | 1.69 |
May | 0.248369E+09 | 1.51 | 698.03 | 01-MAY-15:01 | 1.69 |
June | 0.346744E+09 | 1.58 | 698.03 | 01-JUN-15:01 | 1.67 |
July | 0.405668E+09 | 1.61 | 698.03 | 01-JUL-08:61 | 1.66 |
August | 0.409433E+09 | 1.60 | 698.03 | 01-AUG-08:61 | 1.67 |
September | 0.320524E+09 | 1.57 | 698.03 | 01-SEP-08:62 | 1.67 |
October | 0.249070E+09 | 1.52 | 698.03 | 01-OCT-08:61 | 1.67 |
November | 0.176620E+09 | 1.41 | 698.03 | 01-NOV-15:01 | 1.68 |
December | 0.241320E+09 | 1.38 | 698.03 | 01-DEC-16:01 | 1.69 |
Annual Sum or Average | 0.326195E+10 | 1.49 | |||
Minimum of Months | 0.176620E+09 | 1.37 | 698.03 | 1.66 | |
Maximum of Months | 0.409433E+09 | 1.61 | 698.03 | 1.69 |
Report: FanReportMonthly
For: ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.287394E+09 | 1.30 | 688.96 | 01-JAN-09:01 | 1.69 |
February | 0.219973E+09 | 1.30 | 688.96 | 01-FEB-09:01 | 1.69 |
March | 0.169932E+09 | 1.28 | 688.96 | 03-MAR-09:02 | 1.68 |
April | 0.184058E+09 | 1.43 | 688.96 | 01-APR-15:01 | 1.69 |
May | 0.234267E+09 | 1.48 | 688.96 | 01-MAY-15:01 | 1.69 |
June | 0.347610E+09 | 1.58 | 688.96 | 01-JUN-15:01 | 1.67 |
July | 0.395998E+09 | 1.61 | 688.96 | 01-JUL-08:61 | 1.66 |
August | 0.375212E+09 | 1.59 | 688.96 | 01-AUG-08:61 | 1.67 |
September | 0.253737E+09 | 1.54 | 688.96 | 01-SEP-15:01 | 1.67 |
October | 0.185185E+09 | 1.39 | 688.96 | 01-OCT-08:61 | 1.67 |
November | 0.174539E+09 | 1.25 | 688.96 | 01-NOV-15:01 | 1.68 |
December | 0.303904E+09 | 1.33 | 688.96 | 01-DEC-09:02 | 1.68 |
Annual Sum or Average | 0.313181E+10 | 1.42 | |||
Minimum of Months | 0.169932E+09 | 1.25 | 688.96 | 1.66 | |
Maximum of Months | 0.395998E+09 | 1.61 | 688.96 | 1.69 |
Report: FanReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.134235E+10 | 1.47 | 2880.65 | 01-JAN-09:01 | 1.69 |
February | 0.118373E+10 | 1.51 | 2880.65 | 01-FEB-16:01 | 1.69 |
March | 0.105483E+10 | 1.49 | 2880.65 | 01-MAR-16:01 | 1.69 |
April | 0.105531E+10 | 1.53 | 2880.65 | 01-APR-15:01 | 1.69 |
May | 0.106998E+10 | 1.50 | 2880.65 | 01-MAY-08:62 | 1.68 |
June | 0.140280E+10 | 1.56 | 2880.65 | 01-JUN-15:01 | 1.67 |
July | 0.181743E+10 | 1.60 | 2880.65 | 01-JUL-08:61 | 1.66 |
August | 0.198638E+10 | 1.59 | 2880.65 | 01-AUG-08:61 | 1.67 |
September | 0.195399E+10 | 1.58 | 2880.65 | 01-SEP-08:62 | 1.67 |
October | 0.180648E+10 | 1.56 | 2880.65 | 01-OCT-08:61 | 1.67 |
November | 0.134700E+10 | 1.54 | 2880.65 | 01-NOV-08:62 | 1.68 |
December | 0.137585E+10 | 1.49 | 2880.65 | 01-DEC-16:01 | 1.69 |
Annual Sum or Average | 0.173961E+11 | 1.53 | |||
Minimum of Months | 0.105483E+10 | 1.47 | 2880.65 | 1.66 | |
Maximum of Months | 0.198638E+10 | 1.60 | 2880.65 | 1.69 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.117281E+10 | 0.105553E+10 | 930.60 | 21-JAN-07:10 | 837.54 | 837.54 | 35.69 | 1.81 |
February | 0.940426E+09 | 0.846383E+09 | 879.53 | 04-FEB-07:10 | 791.58 | 791.58 | 35.09 | 1.57 |
March | 0.792970E+09 | 0.713673E+09 | 679.67 | 04-MAR-06:00 | 611.71 | 611.71 | 38.79 | 0.97 |
April | 0.536760E+09 | 0.483084E+09 | 594.78 | 06-APR-10:35 | 535.30 | 535.30 | 33.60 | 0.80 |
May | 0.454116E+09 | 0.408705E+09 | 602.17 | 05-MAY-10:40 | 541.95 | 541.95 | 33.65 | 0.82 |
June | 0.345080E+09 | 0.310572E+09 | 552.46 | 09-JUN-10:40 | 497.22 | 497.22 | 33.72 | 0.72 |
July | 0.294395E+09 | 0.264955E+09 | 476.98 | 03-JUL-10:40 | 429.28 | 429.28 | 35.02 | 0.60 |
August | 0.260774E+09 | 0.234697E+09 | 461.06 | 04-AUG-10:35 | 414.95 | 414.95 | 33.09 | 0.57 |
September | 0.229417E+09 | 0.206475E+09 | 441.99 | 05-SEP-10:40 | 397.79 | 397.79 | 32.94 | 0.54 |
October | 0.439207E+09 | 0.395286E+09 | 802.42 | 25-OCT-08:62 | 722.17 | 722.17 | 33.44 | 1.29 |
November | 0.748149E+09 | 0.673334E+09 | 719.73 | 04-NOV-15:02 | 647.76 | 647.76 | 33.20 | 1.07 |
December | 0.118590E+10 | 0.106731E+10 | 898.69 | 15-DEC-07:10 | 808.82 | 808.82 | 34.98 | 1.65 |
Annual Sum or Average | 0.740001E+10 | 0.666001E+10 | ||||||
Minimum of Months | 0.229417E+09 | 0.206475E+09 | 441.99 | 397.79 | 397.79 | 32.94 | 0.54 | |
Maximum of Months | 0.118590E+10 | 0.106731E+10 | 930.60 | 837.54 | 837.54 | 38.79 | 1.81 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.153809E+10 | 0.138428E+10 | 3608.02 | 23-JAN-16:03 | 3247.22 | 3247.22 | 6.73 | 7.51 |
February | 0.195202E+10 | 0.175681E+10 | 4982.70 | 14-FEB-16:02 | 4484.43 | 4484.43 | 6.73 | 13.88 |
March | 0.351880E+10 | 0.316692E+10 | 5140.99 | 08-MAR-16:01 | 4626.89 | 4626.89 | 6.73 | 15.18 |
April | 0.621171E+10 | 0.559054E+10 | 5391.22 | 13-APR-18:01 | 4852.10 | 4852.10 | 6.73 | 17.95 |
May | 0.862378E+10 | 0.776140E+10 | 6186.57 | 21-MAY-18:03 | 5567.92 | 5567.92 | 6.73 | 28.54 |
June | 0.113974E+11 | 0.102576E+11 | 6940.77 | 29-JUN-18:03 | 6246.70 | 6246.70 | 6.73 | 32.85 |
July | 0.138464E+11 | 0.124617E+11 | 7049.04 | 22-JUL-18:03 | 6344.14 | 6344.14 | 6.73 | 33.31 |
August | 0.134325E+11 | 0.120892E+11 | 7009.74 | 02-AUG-18:02 | 6308.77 | 6308.77 | 6.73 | 33.15 |
September | 0.111048E+11 | 0.999432E+10 | 7014.54 | 02-SEP-18:03 | 6313.09 | 6313.09 | 6.73 | 33.17 |
October | 0.689890E+10 | 0.620901E+10 | 6184.27 | 01-OCT-18:03 | 5565.84 | 5565.84 | 6.73 | 28.52 |
November | 0.281222E+10 | 0.253100E+10 | 4559.15 | 02-NOV-15:01 | 4103.23 | 4103.23 | 6.73 | 11.28 |
December | 0.156957E+10 | 0.141262E+10 | 3453.04 | 02-DEC-16:01 | 3107.73 | 3107.73 | 6.73 | 7.04 |
Annual Sum or Average | 0.829061E+11 | 0.746155E+11 | ||||||
Minimum of Months | 0.153809E+10 | 0.138428E+10 | 3453.04 | 3107.73 | 3107.73 | 6.73 | 7.04 | |
Maximum of Months | 0.138464E+11 | 0.124617E+11 | 7049.04 | 6344.14 | 6344.14 | 6.73 | 33.31 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.678832E+10 | 0.610949E+10 | 4889.31 | 01-JAN-00:05 | 4400.38 | 4400.38 | 6.74 | 34.27 |
February | 0.727334E+10 | 0.654601E+10 | 4889.31 | 01-FEB-09:03 | 4400.38 | 4400.38 | 6.77 | 34.27 |
March | 0.105031E+11 | 0.945277E+10 | 4889.31 | 01-MAR-00:03 | 4400.38 | 4400.38 | 6.73 | 34.27 |
April | 0.123056E+11 | 0.110751E+11 | 4889.31 | 01-APR-00:10 | 4400.38 | 4400.38 | 6.77 | 34.27 |
May | 0.130817E+11 | 0.117735E+11 | 4889.31 | 01-MAY-00:10 | 4400.38 | 4400.38 | 7.19 | 34.27 |
June | 0.126731E+11 | 0.114058E+11 | 4889.31 | 01-JUN-00:10 | 4400.38 | 4400.38 | 8.09 | 34.27 |
July | 0.130955E+11 | 0.117860E+11 | 4889.31 | 01-JUL-00:10 | 4400.38 | 4400.38 | 8.92 | 34.27 |
August | 0.130955E+11 | 0.117860E+11 | 4889.31 | 01-AUG-00:10 | 4400.38 | 4400.38 | 9.53 | 34.27 |
September | 0.126731E+11 | 0.114058E+11 | 4889.31 | 01-SEP-00:10 | 4400.38 | 4400.38 | 8.88 | 34.27 |
October | 0.121444E+11 | 0.109300E+11 | 4889.31 | 01-OCT-00:10 | 4400.38 | 4400.38 | 7.90 | 34.27 |
November | 0.984620E+10 | 0.886158E+10 | 4889.31 | 01-NOV-00:10 | 4400.38 | 4400.38 | 6.94 | 34.27 |
December | 0.708912E+10 | 0.638020E+10 | 4889.31 | 01-DEC-00:03 | 4400.38 | 4400.38 | 6.73 | 34.27 |
Annual Sum or Average | 0.130569E+12 | 0.117512E+12 | ||||||
Minimum of Months | 0.678832E+10 | 0.610949E+10 | 4889.31 | 4400.38 | 4400.38 | 6.73 | 34.27 | |
Maximum of Months | 0.130955E+11 | 0.117860E+11 | 4889.31 | 4400.38 | 4400.38 | 9.53 | 34.27 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.128314E+09 | 38494137.67 | 47.91 | 01-JAN-00:05 | 14.37 | 14.37 | 48.41 | 0.37 |
February | 0.115896E+09 | 34768898.54 | 47.91 | 01-FEB-00:05 | 14.37 | 14.37 | 48.92 | 0.37 |
March | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAR-00:03 | 14.37 | 14.37 | 48.45 | 0.37 |
April | 0.124175E+09 | 37252391.29 | 47.91 | 01-APR-00:10 | 14.37 | 14.37 | 52.26 | 0.37 |
May | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAY-00:10 | 14.37 | 14.37 | 52.41 | 0.37 |
June | 0.124175E+09 | 37252391.29 | 47.91 | 01-JUN-00:10 | 14.37 | 14.37 | 52.55 | 0.37 |
July | 0.128314E+09 | 38494137.67 | 47.91 | 01-JUL-00:10 | 14.37 | 14.37 | 52.99 | 0.37 |
August | 0.128314E+09 | 38494137.67 | 47.91 | 01-AUG-00:10 | 14.37 | 14.37 | 53.72 | 0.37 |
September | 0.124175E+09 | 37252391.29 | 47.91 | 01-SEP-00:10 | 14.37 | 14.37 | 53.54 | 0.37 |
October | 0.128314E+09 | 38494137.67 | 47.91 | 01-OCT-00:10 | 14.37 | 14.37 | 52.33 | 0.37 |
November | 0.124175E+09 | 37252391.29 | 47.91 | 01-NOV-00:10 | 14.37 | 14.37 | 52.66 | 0.37 |
December | 0.128314E+09 | 38494137.67 | 47.91 | 01-DEC-00:03 | 14.37 | 14.37 | 48.96 | 0.37 |
Annual Sum or Average | 0.151079E+10 | 0.453237E+09 | ||||||
Minimum of Months | 0.115896E+09 | 34768898.54 | 47.91 | 14.37 | 14.37 | 48.41 | 0.37 | |
Maximum of Months | 0.128314E+09 | 38494137.67 | 47.91 | 14.37 | 14.37 | 53.72 | 0.37 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 38.60 | 60.00 | 56415.72 | 183808.96 | 21-JAN-07:10 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 37.19 | 60.00 | 49333.07 | 172682.67 | 05-FEB-09:02 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 38.12 | 60.00 | 36836.83 | 109002.62 | 22-MAR-08:62 |
April | 0.00 | 0.00 | 01-APR-00:10 | 34.45 | 60.00 | 26210.35 | 94462.42 | 10-APR-08:03 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 28.07 | 60.00 | 21568.85 | 89815.36 | 05-MAY-10:40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.22 | 60.00 | 16494.23 | 79518.19 | 09-JUN-10:40 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 29.39 | 60.00 | 13345.81 | 64753.56 | 10-JUL-08:04 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 28.57 | 60.00 | 11987.30 | 67562.24 | 29-AUG-10:35 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 29.01 | 60.00 | 11431.50 | 66353.14 | 05-SEP-10:35 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.57 | 60.00 | 20808.64 | 143611.05 | 25-OCT-08:62 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 27.46 | 60.00 | 35313.68 | 119699.91 | 04-NOV-15:02 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 36.62 | 60.00 | 56476.65 | 172480.00 | 15-DEC-07:10 |
Annual Sum or Average | 0.00 | 29603.98 | ||||||
Minimum of Months | 0.00 | 0.00 | 26.57 | 60.00 | 11431.50 | 64753.56 | ||
Maximum of Months | 0.00 | 0.00 | 38.60 | 60.00 | 56476.65 | 183808.96 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 20351.86 | 214780.07 | 01-JAN-16:01 | 8.19 | 6.70 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 29644.29 | 478135.78 | 14-FEB-16:02 | 10.03 | 6.70 | 0.00 | 0.00 | 01-FEB-00:05 |
March | 53500.84 | 489115.64 | 08-MAR-16:01 | 10.11 | 6.70 | 0.00 | 0.00 | 01-MAR-00:03 |
April | 126539.61 | 542827.75 | 13-APR-18:01 | 10.48 | 6.70 | 0.00 | 0.00 | 01-APR-00:10 |
May | 192857.14 | 589178.05 | 19-MAY-18:03 | 10.80 | 6.70 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 309448.63 | 695489.24 | 28-JUN-15:03 | 11.54 | 6.70 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 409213.30 | 840680.02 | 31-JUL-18:02 | 12.56 | 6.70 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 370422.09 | 669040.39 | 20-AUG-18:03 | 11.36 | 6.70 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 269491.42 | 631192.89 | 20-SEP-15:02 | 11.10 | 6.70 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 138388.20 | 599591.85 | 06-OCT-15:01 | 10.88 | 6.70 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 37574.69 | 354729.04 | 02-NOV-15:01 | 9.17 | 6.70 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 19589.38 | 144882.04 | 31-DEC-16:03 | 7.71 | 6.70 | 0.00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 165631.99 | 0.00 | ||||||
Minimum of Months | 19589.38 | 144882.04 | 7.71 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 409213.30 | 840680.02 | 12.56 | 6.70 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 48.41 | 59.70 | 27591.51 | 56404.32 | 30-JAN-07:15 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 48.92 | 58.84 | 27796.52 | 56461.11 | 08-FEB-07:15 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 48.45 | 58.37 | 27168.48 | 55896.74 | 01-MAR-08:00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 52.26 | 59.63 | 25795.66 | 53444.53 | 03-APR-06:40 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 52.41 | 59.00 | 24089.66 | 50315.12 | 01-MAY-07:00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 52.55 | 58.58 | 22499.34 | 46642.07 | 01-JUN-07:00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 52.99 | 58.56 | 21425.68 | 43669.40 | 03-JUL-06:15 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 53.72 | 59.44 | 21220.30 | 42890.56 | 31-AUG-06:15 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 53.54 | 59.21 | 21878.89 | 44996.80 | 29-SEP-06:20 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 52.33 | 59.03 | 23247.32 | 48510.85 | 31-OCT-07:00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 52.66 | 59.02 | 24959.02 | 52061.11 | 30-NOV-07:50 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 48.96 | 58.18 | 26544.06 | 54869.58 | 29-DEC-07:20 |
Annual Sum or Average | 0.00 | 24499.14 | ||||||
Minimum of Months | 0.00 | 0.00 | 48.41 | 58.18 | 21220.30 | 42890.56 | ||
Maximum of Months | 0.00 | 0.00 | 53.72 | 59.70 | 27796.52 | 56461.11 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.857219E+11 | 0.00 | 0.399918E+10 | 0.159449E+12 | 0.00 | 0.00 |
February | 0.700082E+11 | 0.00 | 0.149680E+11 | 0.144018E+12 | 0.00 | 0.00 |
March | 0.675591E+11 | 0.00 | 0.601961E+11 | 0.159449E+12 | 0.00 | 0.00 |
April | 0.546292E+11 | 0.00 | 0.194567E+12 | 0.154305E+12 | 0.00 | 0.00 |
May | 0.526179E+11 | 0.00 | 0.342353E+12 | 0.159449E+12 | 0.00 | 0.00 |
June | 0.420952E+11 | 0.00 | 0.549914E+12 | 0.154306E+12 | 0.00 | 0.00 |
July | 0.360381E+11 | 0.00 | 0.765277E+12 | 0.159449E+12 | 0.00 | 0.00 |
August | 0.323312E+11 | 0.00 | 0.680082E+12 | 0.159449E+12 | 0.00 | 0.00 |
September | 0.291792E+11 | 0.00 | 0.456565E+12 | 0.154306E+12 | 0.00 | 0.00 |
October | 0.396138E+11 | 0.00 | 0.205680E+12 | 0.159449E+12 | 0.00 | 0.00 |
November | 0.533932E+11 | 0.00 | 0.115932E+11 | 0.154305E+12 | 0.00 | 0.00 |
December | 0.816409E+11 | 0.00 | 102015.20 | 0.159449E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.644828E+12 | 0.00 | 0.328520E+13 | 0.187738E+13 | 0.00 | 0.00 |
Minimum of Months | 0.291792E+11 | 0.00 | 102015.20 | 0.144018E+12 | 0.00 | 0.00 |
Maximum of Months | 0.857219E+11 | 0.00 | 0.765277E+12 | 0.159449E+12 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.369318E+11 | 0.00 | 0.119132E+09 | 0.587890E+10 | 0.00 | 0.00 |
February | 0.309905E+11 | 0.00 | 0.100794E+10 | 0.530997E+10 | 0.00 | 0.00 |
March | 0.252133E+11 | 0.00 | 0.394114E+10 | 0.587890E+10 | 0.00 | 0.00 |
April | 0.127282E+11 | 0.00 | 0.157164E+11 | 0.568926E+10 | 0.00 | 0.00 |
May | 0.527082E+10 | 0.00 | 0.310275E+11 | 0.587890E+10 | 0.00 | 0.00 |
June | 0.946234E+09 | 0.00 | 0.581003E+11 | 0.568926E+10 | 0.00 | 0.00 |
July | 37167.12 | 0.00 | 0.847239E+11 | 0.587890E+10 | 0.00 | 0.00 |
August | 10903757.70 | 0.00 | 0.717942E+11 | 0.587890E+10 | 0.00 | 0.00 |
September | 0.629960E+09 | 0.00 | 0.429417E+11 | 0.568926E+10 | 0.00 | 0.00 |
October | 0.135745E+11 | 0.00 | 0.170638E+11 | 0.587890E+10 | 0.00 | 0.00 |
November | 0.293647E+11 | 0.00 | 0.449857E+09 | 0.568926E+10 | 0.00 | 0.00 |
December | 0.394390E+11 | 0.00 | 0.00 | 0.587890E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.195100E+12 | 0.00 | 0.326886E+12 | 0.692193E+11 | 0.00 | 0.00 |
Minimum of Months | 37167.12 | 0.00 | 0.00 | 0.530997E+10 | 0.00 | 0.00 |
Maximum of Months | 0.394390E+11 | 0.00 | 0.847239E+11 | 0.587890E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.159449E+12 | 0.399918E+10 | 0.857219E+11 | 0.850285E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.144018E+12 | 0.149680E+11 | 0.700082E+11 | 0.663188E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.159449E+12 | 0.601961E+11 | 0.675591E+11 | 0.428555E+12 | 6761415.74 | 0.00 | 0.00 | 0.00 |
April | 0.154305E+12 | 0.194567E+12 | 0.546292E+11 | 0.172254E+12 | 0.603036E+10 | 0.00 | 0.00 | 0.00 |
May | 0.159449E+12 | 0.342353E+12 | 0.526179E+11 | 0.593027E+11 | 0.311734E+11 | 0.00 | 0.00 | 0.00 |
June | 0.154306E+12 | 0.549914E+12 | 0.420952E+11 | 0.153606E+11 | 0.132002E+12 | 0.00 | 0.00 | 0.00 |
July | 0.159449E+12 | 0.765277E+12 | 0.360381E+11 | 0.100086E+11 | 0.198194E+12 | 0.00 | 0.00 | 0.00 |
August | 0.159449E+12 | 0.680082E+12 | 0.323312E+11 | 0.109303E+11 | 0.139747E+12 | 0.00 | 0.00 | 0.00 |
September | 0.154306E+12 | 0.456565E+12 | 0.291792E+11 | 0.697769E+10 | 0.538943E+11 | 0.00 | 0.00 | 0.00 |
October | 0.159449E+12 | 0.205680E+12 | 0.396138E+11 | 0.205293E+12 | 0.102112E+11 | 0.00 | 0.00 | 0.00 |
November | 0.154305E+12 | 0.115932E+11 | 0.533932E+11 | 0.504197E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.159449E+12 | 102015.20 | 0.816409E+11 | 0.886426E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.187738E+13 | 0.328520E+13 | 0.644828E+12 | 0.381278E+13 | 0.571259E+12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.144018E+12 | 102015.20 | 0.291792E+11 | 0.697769E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.159449E+12 | 0.765277E+12 | 0.857219E+11 | 0.886426E+12 | 0.198194E+12 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.587890E+10 | 0.119132E+09 | 0.369318E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.530997E+10 | 0.100794E+10 | 0.309905E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.587890E+10 | 0.394114E+10 | 0.252133E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.568926E+10 | 0.157164E+11 | 0.127282E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.587890E+10 | 0.310275E+11 | 0.527082E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.568926E+10 | 0.581003E+11 | 0.946234E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.587890E+10 | 0.847239E+11 | 37167.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.587890E+10 | 0.717942E+11 | 10903757.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.568926E+10 | 0.429417E+11 | 0.629960E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.587890E+10 | 0.170638E+11 | 0.135745E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.568926E+10 | 0.449857E+09 | 0.293647E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.587890E+10 | 0.00 | 0.394390E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.692193E+11 | 0.326886E+12 | 0.195100E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.530997E+10 | 0.00 | 37167.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.587890E+10 | 0.847239E+11 | 0.394390E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.159449E+12 | 0.857219E+11 | 0.399918E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.144018E+12 | 0.700082E+11 | 0.149680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.159449E+12 | 0.675591E+11 | 0.601961E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.154305E+12 | 0.546292E+11 | 0.194567E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.159449E+12 | 0.526179E+11 | 0.342353E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.154306E+12 | 0.420952E+11 | 0.549914E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.159449E+12 | 0.360381E+11 | 0.765277E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.159449E+12 | 0.323312E+11 | 0.680082E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.154306E+12 | 0.291792E+11 | 0.456565E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.159449E+12 | 0.396138E+11 | 0.205680E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.154305E+12 | 0.533932E+11 | 0.115932E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.159449E+12 | 0.816409E+11 | 102015.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.187738E+13 | 0.644828E+12 | 0.328520E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.144018E+12 | 0.291792E+11 | 102015.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.159449E+12 | 0.857219E+11 | 0.765277E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.587890E+10 | 0.369318E+11 | 0.119132E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.530997E+10 | 0.309905E+11 | 0.100794E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.587890E+10 | 0.252133E+11 | 0.394114E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.568926E+10 | 0.127282E+11 | 0.157164E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.587890E+10 | 0.527082E+10 | 0.310275E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.568926E+10 | 0.946234E+09 | 0.581003E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.587890E+10 | 37167.12 | 0.847239E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.587890E+10 | 10903757.70 | 0.717942E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.568926E+10 | 0.629960E+09 | 0.429417E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.587890E+10 | 0.135745E+11 | 0.170638E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.568926E+10 | 0.293647E+11 | 0.449857E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.587890E+10 | 0.394390E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.692193E+11 | 0.195100E+12 | 0.326886E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.530997E+10 | 37167.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.587890E+10 | 0.394390E+11 | 0.847239E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.750079E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.26 |
February | 0.664515E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.27 |
March | 0.692341E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 14145915.75 | 0.00 | 0.00 | 2.27 |
April | 0.532525E+11 | 0.00 | 89691.69 | 0.00 | 0.132803E+09 | 22091554.40 | 0.00 | 140.91 | 2.27 |
May | 0.408684E+11 | 0.00 | 5926796.79 | 0.00 | 0.985780E+09 | 1007897.08 | 0.00 | 112743.83 | 2.28 |
June | 0.213842E+11 | 0.00 | 17146645.02 | 0.00 | 0.530869E+10 | 0.00 | 0.00 | 95482.08 | 2.28 |
July | 0.604836E+10 | 0.00 | 0.00 | 0.00 | 0.107500E+11 | 0.00 | 0.00 | 0.00 | 2.29 |
August | 0.114971E+11 | 0.00 | 0.00 | 0.00 | 0.668568E+10 | 0.00 | 0.00 | 0.00 | 2.28 |
September | 0.279625E+11 | 0.00 | 0.00 | 0.00 | 0.200206E+10 | 0.00 | 0.00 | 0.00 | 2.28 |
October | 0.551206E+11 | 0.00 | 0.00 | 0.00 | 0.304126E+09 | 0.00 | 0.00 | 0.00 | 2.28 |
November | 0.719802E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.26 |
December | 0.753616E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.26 |
Annual Sum or Average | 0.574169E+12 | 0.00 | 23163133.50 | 0.00 | 0.261691E+11 | 37245367.23 | 0.00 | 208366.82 | 2.27 |
Minimum of Months | 0.604836E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.26 |
Maximum of Months | 0.753616E+11 | 0.00 | 17146645.02 | 0.00 | 0.107500E+11 | 22091554.40 | 0.00 | 112743.83 | 2.29 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.746145E+10 | 0.00 | 0.00 | 1320716.69 | 0.00 | 0.212198E+10 | 0.126915E+10 | 0.00 | 5.95 |
February | 0.721223E+10 | 0.00 | 0.00 | 968363.91 | 0.00 | 0.138454E+10 | 0.101772E+10 | 0.00 | 5.97 |
March | 0.908600E+10 | 0.00 | 0.00 | 525067.90 | 0.00 | 0.369890E+09 | 0.563547E+09 | 0.00 | 5.98 |
April | 0.769612E+10 | 4010592.62 | 0.00 | 19729.19 | 15218552.85 | 7246194.15 | 5248956.55 | 0.00 | 5.98 |
May | 0.591365E+10 | 0.00 | 0.00 | 0.00 | 0.143513E+09 | 0.00 | 0.00 | 0.00 | 5.98 |
June | 0.309421E+10 | 0.00 | 0.00 | 0.00 | 0.770643E+09 | 0.00 | 0.00 | 0.00 | 5.98 |
July | 0.875175E+09 | 18586772.93 | 0.00 | 0.00 | 0.153690E+10 | 0.00 | 0.00 | 0.00 | 6.01 |
August | 0.166359E+10 | 0.211442E+09 | 0.00 | 0.00 | 0.755951E+09 | 0.00 | 0.00 | 0.00 | 6.00 |
September | 0.403989E+10 | 0.173130E+09 | 0.00 | 84707.42 | 0.116569E+09 | 0.00 | 6103642.84 | 0.00 | 5.99 |
October | 0.704514E+10 | 31724600.96 | 0.00 | 1358427.68 | 12288433.77 | 0.267080E+09 | 0.662332E+09 | 0.00 | 5.99 |
November | 0.841520E+10 | 0.00 | 0.00 | 1582775.27 | 0.00 | 0.368693E+09 | 0.163028E+10 | 0.00 | 5.95 |
December | 0.728560E+10 | 0.00 | 0.00 | 1307850.93 | 0.00 | 0.207732E+10 | 0.154068E+10 | 0.00 | 5.96 |
Annual Sum or Average | 0.697882E+11 | 0.438894E+09 | 0.00 | 7167638.98 | 0.335108E+10 | 0.659675E+10 | 0.669506E+10 | 0.00 | 5.98 |
Minimum of Months | 0.875175E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.95 |
Maximum of Months | 0.908600E+10 | 0.211442E+09 | 0.00 | 1582775.27 | 0.153690E+10 | 0.212198E+10 | 0.163028E+10 | 0.00 | 6.01 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.719464E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.40 |
February | 0.637393E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.41 |
March | 0.664219E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.42 |
April | 0.511001E+10 | 0.00 | 0.00 | 0.00 | 12746905.24 | 0.00 | 0.00 | 0.00 | 3.42 |
May | 0.392013E+10 | 0.00 | 0.00 | 0.00 | 95133813.04 | 0.00 | 0.00 | 0.00 | 3.43 |
June | 0.205114E+10 | 0.00 | 0.00 | 0.00 | 0.510855E+09 | 0.00 | 0.00 | 0.00 | 3.43 |
July | 0.580149E+09 | 0.00 | 0.00 | 0.00 | 0.103112E+10 | 0.00 | 0.00 | 0.00 | 3.44 |
August | 0.110278E+10 | 0.00 | 0.00 | 0.00 | 0.641280E+09 | 0.00 | 0.00 | 0.00 | 3.44 |
September | 0.268213E+10 | 0.00 | 0.00 | 0.00 | 0.192034E+09 | 0.00 | 0.00 | 0.00 | 3.43 |
October | 0.528709E+10 | 0.00 | 0.00 | 0.00 | 29171337.30 | 0.00 | 0.00 | 0.00 | 3.42 |
November | 0.690423E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.40 |
December | 0.722857E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.41 |
Annual Sum or Average | 0.550770E+11 | 0.00 | 0.00 | 0.00 | 0.251234E+10 | 0.00 | 0.00 | 0.00 | 3.42 |
Minimum of Months | 0.580149E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.40 |
Maximum of Months | 0.722857E+10 | 0.00 | 0.00 | 0.00 | 0.103112E+10 | 0.00 | 0.00 | 0.00 | 3.44 |
Report: MechanicalVentilationLoadsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.646132E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.826828E+09 | 0.00 | 0.00 | 1.63 |
February | 0.594037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.516406E+09 | 0.00 | 0.00 | 1.63 |
March | 0.672852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.64 |
April | 0.517643E+10 | 0.00 | 0.00 | 0.00 | 12912577.11 | 0.00 | 0.00 | 0.00 | 1.64 |
May | 0.397108E+10 | 0.00 | 0.00 | 0.00 | 96370269.80 | 0.00 | 0.00 | 0.00 | 1.64 |
June | 0.207779E+10 | 0.00 | 0.00 | 0.00 | 0.517495E+09 | 0.00 | 0.00 | 0.00 | 1.64 |
July | 0.587689E+09 | 0.00 | 0.00 | 0.00 | 0.104452E+10 | 0.00 | 0.00 | 0.00 | 1.65 |
August | 0.111712E+10 | 0.00 | 0.00 | 0.00 | 0.649615E+09 | 0.00 | 0.00 | 0.00 | 1.65 |
September | 0.271698E+10 | 0.00 | 0.00 | 0.00 | 0.194530E+09 | 0.00 | 0.00 | 0.00 | 1.64 |
October | 0.535412E+10 | 0.00 | 0.00 | 0.00 | 29550477.97 | 1685701.43 | 0.00 | 0.00 | 1.64 |
November | 0.693487E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 59095812.54 | 0.00 | 0.00 | 1.63 |
December | 0.627927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104325E+10 | 0.00 | 0.00 | 1.63 |
Annual Sum or Average | 0.533455E+11 | 0.00 | 0.00 | 0.00 | 0.254500E+10 | 0.244727E+10 | 0.00 | 0.00 | 1.64 |
Minimum of Months | 0.587689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.63 |
Maximum of Months | 0.693487E+10 | 0.00 | 0.00 | 0.00 | 0.104452E+10 | 0.104325E+10 | 0.00 | 0.00 | 1.65 |
Report: MechanicalVentilationLoadsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.157279E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205901E+10 | 0.00 | 0.00 | 1.41 |
February | 0.187802E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133949E+10 | 0.00 | 0.00 | 1.41 |
March | 0.319869E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154239E+09 | 0.00 | 0.00 | 1.41 |
April | 0.257950E+10 | 0.00 | 0.00 | 0.00 | 6434542.11 | 0.00 | 0.00 | 0.00 | 1.41 |
May | 0.197885E+10 | 0.00 | 0.00 | 0.00 | 48022834.96 | 0.00 | 0.00 | 0.00 | 1.42 |
June | 0.103540E+10 | 0.00 | 0.00 | 0.00 | 0.257876E+09 | 0.00 | 0.00 | 0.00 | 1.42 |
July | 0.292855E+09 | 0.00 | 0.00 | 0.00 | 0.520503E+09 | 0.00 | 0.00 | 0.00 | 1.42 |
August | 0.556677E+09 | 0.00 | 0.00 | 0.00 | 0.323713E+09 | 0.00 | 0.00 | 0.00 | 1.42 |
September | 0.135392E+10 | 0.00 | 0.00 | 0.00 | 96937458.85 | 0.00 | 0.00 | 0.00 | 1.42 |
October | 0.252046E+10 | 0.00 | 0.00 | 0.00 | 14725472.18 | 0.148417E+09 | 0.00 | 0.00 | 1.41 |
November | 0.308640E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.398800E+09 | 0.00 | 0.00 | 1.41 |
December | 0.143762E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.221131E+10 | 0.00 | 0.00 | 1.41 |
Annual Sum or Average | 0.214912E+11 | 0.00 | 0.00 | 0.00 | 0.126821E+10 | 0.631127E+10 | 0.00 | 0.00 | 1.41 |
Minimum of Months | 0.292855E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.41 |
Maximum of Months | 0.319869E+10 | 0.00 | 0.00 | 0.00 | 0.520503E+09 | 0.221131E+10 | 0.00 | 0.00 | 1.42 |
Report: MechanicalVentilationLoadsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.201825E+10 | 0.00 | 0.00 | 67164725.34 | 0.00 | 0.00 | 0.955836E+11 | 0.00 | 46.02 |
February | 0.161740E+10 | 0.00 | 0.00 | 61207757.25 | 0.00 | 0.00 | 0.848508E+11 | 0.00 | 46.16 |
March | 0.126705E+10 | 0.00 | 0.00 | 70012292.95 | 0.00 | 0.00 | 0.888386E+11 | 0.00 | 46.27 |
April | 0.102196E+10 | 0.164496E+09 | 0.00 | 66462060.06 | 8492612.64 | 0.00 | 0.682782E+11 | 0.00 | 46.24 |
May | 0.679142E+09 | 0.124196E+10 | 0.00 | 61237087.73 | 49097041.30 | 0.00 | 0.524732E+11 | 0.00 | 46.29 |
June | 0.200295E+09 | 0.670954E+10 | 0.00 | 42254006.28 | 0.223979E+09 | 0.00 | 0.275986E+11 | 0.00 | 46.28 |
July | 8491138.99 | 0.135169E+11 | 0.00 | 25054525.44 | 0.476853E+09 | 0.00 | 0.784032E+10 | 0.00 | 46.47 |
August | 49423370.52 | 0.839806E+10 | 0.00 | 36767951.02 | 0.305215E+09 | 0.00 | 0.148814E+11 | 0.00 | 46.44 |
September | 0.165074E+09 | 0.251754E+10 | 0.00 | 55517683.40 | 88561664.68 | 0.00 | 0.361863E+11 | 0.00 | 46.32 |
October | 0.103816E+10 | 0.380723E+09 | 0.00 | 68199414.19 | 15161185.22 | 0.00 | 0.706661E+11 | 0.00 | 46.26 |
November | 0.157784E+10 | 0.00 | 0.00 | 67259053.27 | 0.00 | 0.00 | 0.920850E+11 | 0.00 | 46.00 |
December | 0.208728E+10 | 0.00 | 0.00 | 66749312.01 | 0.00 | 0.00 | 0.959744E+11 | 0.00 | 46.05 |
Annual Sum or Average | 0.117304E+11 | 0.329293E+11 | 0.00 | 0.687886E+09 | 0.116736E+10 | 0.00 | 0.735256E+12 | 0.00 | 46.23 |
Minimum of Months | 8491138.99 | 0.00 | 0.00 | 25054525.44 | 0.00 | 0.00 | 0.784032E+10 | 0.00 | 46.00 |
Maximum of Months | 0.208728E+10 | 0.135169E+11 | 0.00 | 70012292.95 | 0.476853E+09 | 0.00 | 0.959744E+11 | 0.00 | 46.47 |
Report: MechanicalVentilationLoadsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.382549E+11 | 0.00 | 0.00 | 5247851.98 | 0.00 | 0.00 | 0.743124E+10 | 0.00 | 8.90 |
February | 0.334491E+11 | 0.00 | 0.00 | 4164018.41 | 0.00 | 0.00 | 0.702600E+10 | 0.00 | 8.93 |
March | 0.374035E+11 | 0.00 | 0.00 | 2552421.27 | 0.00 | 0.00 | 0.477680E+10 | 0.00 | 8.95 |
April | 0.298729E+11 | 44229162.13 | 0.00 | 525905.27 | 36723299.52 | 0.00 | 0.257900E+10 | 0.00 | 8.94 |
May | 0.231005E+11 | 16771048.28 | 0.00 | 394372.77 | 0.587400E+09 | 0.00 | 0.179491E+10 | 0.00 | 8.95 |
June | 0.104945E+11 | 0.344093E+09 | 0.00 | 1180930.75 | 0.290022E+10 | 0.00 | 0.253059E+10 | 0.00 | 8.95 |
July | 0.134613E+10 | 0.103517E+10 | 0.00 | 1734662.28 | 0.551324E+10 | 0.00 | 0.233652E+10 | 0.00 | 8.99 |
August | 0.343350E+10 | 0.178477E+10 | 0.00 | 2281126.06 | 0.228784E+10 | 0.00 | 0.356773E+10 | 0.00 | 8.99 |
September | 0.101226E+11 | 0.852565E+09 | 0.00 | 2460917.28 | 0.366997E+09 | 0.00 | 0.690843E+10 | 0.00 | 8.97 |
October | 0.232237E+11 | 0.139095E+09 | 0.00 | 6375794.69 | 46165358.79 | 0.00 | 0.103469E+11 | 0.00 | 8.95 |
November | 0.337332E+11 | 0.00 | 0.00 | 6167770.99 | 0.00 | 0.00 | 0.101077E+11 | 0.00 | 8.90 |
December | 0.373114E+11 | 0.00 | 0.00 | 5584526.91 | 0.00 | 0.00 | 0.858993E+10 | 0.00 | 8.91 |
Annual Sum or Average | 0.281746E+12 | 0.421670E+10 | 0.00 | 38670298.66 | 0.117386E+11 | 0.00 | 0.679957E+11 | 0.00 | 8.94 |
Minimum of Months | 0.134613E+10 | 0.00 | 0.00 | 394372.77 | 0.00 | 0.00 | 0.179491E+10 | 0.00 | 8.90 |
Maximum of Months | 0.382549E+11 | 0.178477E+10 | 0.00 | 6375794.69 | 0.551324E+10 | 0.00 | 0.103469E+11 | 0.00 | 8.99 |
Report: MechanicalVentilationLoadsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.142936E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.02 |
February | 0.126631E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.03 |
March | 0.131961E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.04 |
April | 0.101521E+12 | 0.00 | 0.00 | 0.00 | 0.253244E+09 | 0.00 | 0.00 | 0.00 | 4.04 |
May | 0.778815E+11 | 0.00 | 0.00 | 0.00 | 0.189003E+10 | 0.00 | 0.00 | 0.00 | 4.04 |
June | 0.407176E+11 | 6398401.17 | 0.00 | 19490.51 | 0.101428E+11 | 0.00 | 32445324.19 | 0.00 | 4.04 |
July | 0.114938E+11 | 19149343.52 | 0.00 | 22490.87 | 0.204662E+11 | 0.00 | 31994897.77 | 0.00 | 4.06 |
August | 0.218095E+11 | 0.00 | 0.00 | 23369.63 | 0.127404E+11 | 0.00 | 99511881.22 | 0.00 | 4.06 |
September | 0.532860E+11 | 0.00 | 0.00 | 0.00 | 0.381516E+10 | 0.00 | 0.00 | 0.00 | 4.05 |
October | 0.105039E+12 | 0.00 | 0.00 | 0.00 | 0.579549E+09 | 0.00 | 0.00 | 0.00 | 4.04 |
November | 0.137167E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.01 |
December | 0.143610E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.02 |
Annual Sum or Average | 0.109405E+13 | 25547744.69 | 0.00 | 65351.02 | 0.498874E+11 | 0.00 | 0.163952E+09 | 0.00 | 4.04 |
Minimum of Months | 0.114938E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.01 |
Maximum of Months | 0.143610E+12 | 19149343.52 | 0.00 | 23369.63 | 0.204662E+11 | 0.00 | 99511881.22 | 0.00 | 4.06 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.600487E+09 | 0.00 | 0.00 | 4234861.72 | 0.00 | 0.200385E+10 | 0.895381E+09 | 0.00 | 0.47 |
February | 0.475287E+09 | 0.00 | 0.00 | 5630415.05 | 0.00 | 0.148050E+10 | 0.977145E+09 | 0.00 | 0.47 |
March | 0.378888E+09 | 0.00 | 0.00 | 8684852.89 | 0.00 | 0.914214E+09 | 0.123799E+10 | 0.00 | 0.47 |
April | 0.217481E+09 | 7443696.89 | 0.00 | 12189979.27 | 104589.02 | 0.206008E+09 | 0.122173E+10 | 0.00 | 0.47 |
May | 0.139445E+09 | 48019150.31 | 3100.83 | 10686264.58 | 2245383.76 | 70586686.36 | 0.858000E+09 | 1439.17 | 0.47 |
June | 38433899.97 | 0.370108E+09 | 52652.11 | 7341494.42 | 9850225.43 | 11835732.20 | 0.406221E+09 | 2982.12 | 0.47 |
July | 215417.14 | 0.882222E+09 | 164971.35 | 1645553.68 | 36519166.82 | 1539.11 | 34144094.84 | 3605.00 | 0.47 |
August | 8429738.92 | 0.591564E+09 | 77050.46 | 3708338.13 | 20199241.80 | 156117.64 | 0.102782E+09 | 2215.98 | 0.47 |
September | 41493876.43 | 0.149992E+09 | 0.00 | 10206066.73 | 5049866.19 | 724721.97 | 0.484030E+09 | 0.00 | 0.47 |
October | 0.214473E+09 | 18352002.46 | 0.00 | 13016640.81 | 831421.71 | 0.331847E+09 | 0.115530E+10 | 0.00 | 0.47 |
November | 0.398228E+09 | 0.00 | 0.00 | 7270339.71 | 0.00 | 0.990096E+09 | 0.136151E+10 | 0.00 | 0.47 |
December | 0.630639E+09 | 0.00 | 0.00 | 3814286.11 | 0.00 | 0.195695E+10 | 0.100674E+10 | 0.00 | 0.47 |
Annual Sum or Average | 0.314350E+10 | 0.206770E+10 | 297774.75 | 88429093.12 | 74799894.72 | 0.796677E+10 | 0.974097E+10 | 10242.26 | 0.47 |
Minimum of Months | 215417.14 | 0.00 | 0.00 | 1645553.68 | 0.00 | 1539.11 | 34144094.84 | 0.00 | 0.47 |
Maximum of Months | 0.630639E+09 | 0.882222E+09 | 164971.35 | 13016640.81 | 36519166.82 | 0.200385E+10 | 0.136151E+10 | 3605.00 | 0.47 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.734117E+09 | 0.00 | 0.00 | 1141053.85 | 0.00 | 0.258094E+10 | 0.187344E+09 | 0.00 | 0.47 |
February | 0.622659E+09 | 0.00 | 0.00 | 2295119.01 | 0.00 | 0.190073E+10 | 0.412536E+09 | 0.00 | 0.47 |
March | 0.480607E+09 | 0.00 | 0.00 | 5137791.67 | 0.00 | 0.127317E+10 | 0.780559E+09 | 0.00 | 0.47 |
April | 0.288507E+09 | 7426619.26 | 0.00 | 9889065.64 | 120782.25 | 0.299653E+09 | 0.105917E+10 | 0.00 | 0.47 |
May | 0.159134E+09 | 47829917.29 | 25816.09 | 9995222.39 | 2405204.95 | 76308002.27 | 0.833154E+09 | 2245.98 | 0.47 |
June | 39102970.09 | 0.370005E+09 | 10593.60 | 7468949.43 | 9951644.46 | 12457480.87 | 0.404748E+09 | 1904.80 | 0.47 |
July | 210613.09 | 0.879641E+09 | 157321.59 | 1658369.11 | 39000324.16 | 1538.93 | 34131864.94 | 3518.13 | 0.47 |
August | 8477840.95 | 0.584929E+09 | 88030.54 | 3547296.64 | 26750885.94 | 156099.35 | 0.102882E+09 | 3291.22 | 0.47 |
September | 46094316.10 | 0.145545E+09 | 0.00 | 8464997.37 | 9478539.44 | 807100.45 | 0.481026E+09 | 0.00 | 0.47 |
October | 0.322448E+09 | 16728060.89 | 0.00 | 7985994.14 | 2453115.66 | 0.516994E+09 | 0.867012E+09 | 0.00 | 0.47 |
November | 0.598043E+09 | 0.00 | 0.00 | 2472193.69 | 0.00 | 0.155737E+10 | 0.598892E+09 | 0.00 | 0.47 |
December | 0.801069E+09 | 0.00 | 0.00 | 834114.87 | 0.00 | 0.265416E+10 | 0.141662E+09 | 0.00 | 0.47 |
Annual Sum or Average | 0.410047E+10 | 0.205210E+10 | 281761.82 | 60890167.80 | 90160496.85 | 0.108727E+11 | 0.590311E+10 | 10960.11 | 0.47 |
Minimum of Months | 210613.09 | 0.00 | 0.00 | 834114.87 | 0.00 | 1538.93 | 34131864.94 | 0.00 | 0.47 |
Maximum of Months | 0.801069E+09 | 0.879641E+09 | 157321.59 | 9995222.39 | 39000324.16 | 0.265416E+10 | 0.105917E+10 | 3518.13 | 0.47 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.286042E+11 | 0.00 | 0.00 | 87555229.77 | 0.00 | 0.385059E+09 | 0.184336E+11 | 0.00 | 0.53 |
February | 0.215343E+11 | 0.00 | 0.00 | 85355448.55 | 0.00 | 0.00 | 0.182246E+11 | 0.00 | 0.53 |
March | 0.154383E+11 | 0.00 | 0.00 | 93535183.82 | 0.00 | 0.00 | 0.189053E+11 | 0.00 | 0.54 |
April | 0.617606E+10 | 0.102348E+09 | 0.00 | 98794986.74 | 0.00 | 0.00 | 0.161981E+11 | 0.00 | 0.54 |
May | 0.306363E+10 | 0.681604E+09 | 0.00 | 78591456.30 | 0.00 | 0.00 | 0.114842E+11 | 0.00 | 0.54 |
June | 0.730926E+09 | 0.515265E+10 | 0.00 | 48317032.20 | 0.00 | 0.00 | 0.550990E+10 | 0.00 | 0.54 |
July | 9789454.64 | 0.124589E+11 | 0.00 | 8889684.56 | 685889.69 | 0.00 | 0.469538E+09 | 0.00 | 0.54 |
August | 22335133.31 | 0.829563E+10 | 0.00 | 25934880.67 | 412750.96 | 0.00 | 0.151206E+10 | 0.00 | 0.54 |
September | 0.105269E+09 | 0.210223E+10 | 0.00 | 90602264.65 | 0.00 | 0.00 | 0.707798E+10 | 0.00 | 0.54 |
October | 0.548420E+10 | 0.260110E+09 | 0.00 | 0.153337E+09 | 0.00 | 0.00 | 0.176115E+11 | 0.00 | 0.54 |
November | 0.132204E+11 | 0.00 | 0.00 | 0.136861E+09 | 0.00 | 0.00 | 0.240265E+11 | 0.00 | 0.53 |
December | 0.271223E+11 | 0.00 | 0.00 | 95975102.16 | 0.00 | 0.00 | 0.215693E+11 | 0.00 | 0.53 |
Annual Sum or Average | 0.121512E+12 | 0.290535E+11 | 0.00 | 0.100375E+10 | 1098640.65 | 0.385059E+09 | 0.161023E+12 | 0.00 | 0.54 |
Minimum of Months | 9789454.64 | 0.00 | 0.00 | 8889684.56 | 0.00 | 0.00 | 0.469538E+09 | 0.00 | 0.53 |
Maximum of Months | 0.286042E+11 | 0.124589E+11 | 0.00 | 0.153337E+09 | 685889.69 | 0.385059E+09 | 0.240265E+11 | 0.00 | 0.54 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.106974E+11 | 0.00 | 0.00 | 14686899.77 | 0.00 | 0.158952E+11 | 0.209162E+11 | 0.00 | 0.53 |
February | 0.910103E+10 | 0.00 | 0.00 | 25033770.30 | 0.00 | 0.940442E+10 | 0.213247E+11 | 0.00 | 0.53 |
March | 0.741813E+10 | 0.00 | 0.00 | 60359722.32 | 0.00 | 0.500030E+09 | 0.264680E+11 | 0.00 | 0.53 |
April | 0.486592E+10 | 80975066.12 | 660068.20 | 94767991.87 | 20583094.82 | 45740353.69 | 0.174727E+11 | 157744.69 | 0.53 |
May | 0.268637E+10 | 0.574725E+09 | 954992.96 | 0.103847E+09 | 0.105989E+09 | 24627585.61 | 0.118156E+11 | 120786.61 | 0.54 |
June | 0.650441E+09 | 0.473088E+10 | 1340029.26 | 79710138.29 | 0.421704E+09 | 6253095.55 | 0.555446E+10 | 132172.13 | 0.54 |
July | 4992000.01 | 0.112973E+11 | 1905568.34 | 17440881.63 | 0.116374E+10 | 0.00 | 0.465918E+09 | 74261.53 | 0.54 |
August | 0.120598E+09 | 0.716238E+10 | 1867799.54 | 37857918.95 | 0.113385E+10 | 359663.46 | 0.140195E+10 | 211759.93 | 0.54 |
September | 0.683301E+09 | 0.144398E+10 | 2287302.62 | 92332226.47 | 0.656410E+09 | 6270992.05 | 0.649393E+10 | 121970.47 | 0.54 |
October | 0.501673E+10 | 0.148554E+09 | 698161.86 | 79940170.86 | 0.110860E+09 | 0.409893E+09 | 0.177488E+11 | 69112.75 | 0.53 |
November | 0.895688E+10 | 0.00 | 0.00 | 39279891.72 | 0.00 | 0.185712E+10 | 0.265407E+11 | 0.00 | 0.53 |
December | 0.119179E+11 | 0.00 | 0.00 | 11656730.70 | 0.00 | 0.197871E+11 | 0.170843E+11 | 0.00 | 0.53 |
Annual Sum or Average | 0.621196E+11 | 0.254388E+11 | 9713922.77 | 0.656914E+09 | 0.361313E+10 | 0.479370E+11 | 0.173287E+12 | 887808.10 | 0.53 |
Minimum of Months | 4992000.01 | 0.00 | 0.00 | 11656730.70 | 0.00 | 0.00 | 0.465918E+09 | 0.00 | 0.53 |
Maximum of Months | 0.119179E+11 | 0.112973E+11 | 2287302.62 | 0.103847E+09 | 0.116374E+10 | 0.197871E+11 | 0.265407E+11 | 211759.93 | 0.54 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.559315E+09 | 0.00 | 0.00 | 4358094.03 | 0.00 | 0.203176E+10 | 0.908524E+09 | 0.00 | 0.47 |
February | 0.474641E+09 | 0.00 | 0.00 | 5340778.06 | 0.00 | 0.149288E+10 | 0.965702E+09 | 0.00 | 0.47 |
March | 0.277039E+09 | 0.00 | 0.00 | 9739984.24 | 0.00 | 0.884455E+09 | 0.136854E+10 | 0.00 | 0.47 |
April | 72734934.97 | 7342743.12 | 0.00 | 15038643.04 | 205542.78 | 0.221453E+09 | 0.134818E+10 | 0.00 | 0.47 |
May | 41662303.57 | 48005156.28 | 2605.63 | 14717986.16 | 2259377.79 | 64965962.05 | 0.957371E+09 | 1934.37 | 0.47 |
June | 15655740.17 | 0.374044E+09 | 0.00 | 9911810.94 | 5970299.80 | 5929419.83 | 0.432335E+09 | 0.00 | 0.47 |
July | 43921.56 | 0.903724E+09 | 26308.63 | 1888237.68 | 15158025.18 | 1539.11 | 34072906.43 | 1089.64 | 0.47 |
August | 3040965.16 | 0.602159E+09 | 0.00 | 4841359.02 | 9683915.84 | 0.00 | 0.107194E+09 | 0.00 | 0.47 |
September | 17420785.01 | 0.151191E+09 | 9407.00 | 12774386.26 | 3840877.03 | 232454.19 | 0.506027E+09 | 666.40 | 0.47 |
October | 0.144706E+09 | 18473784.57 | 0.00 | 14613972.63 | 709639.60 | 0.321871E+09 | 0.123345E+10 | 0.00 | 0.47 |
November | 0.307310E+09 | 0.00 | 0.00 | 7877249.08 | 0.00 | 0.101160E+10 | 0.143031E+10 | 0.00 | 0.47 |
December | 0.680871E+09 | 0.00 | 0.00 | 3821371.28 | 0.00 | 0.197511E+10 | 0.938337E+09 | 0.00 | 0.47 |
Annual Sum or Average | 0.259444E+10 | 0.210494E+10 | 38321.26 | 0.104924E+09 | 37827678.01 | 0.801026E+10 | 0.102300E+11 | 3690.41 | 0.47 |
Minimum of Months | 43921.56 | 0.00 | 0.00 | 1888237.68 | 0.00 | 0.00 | 34072906.43 | 0.00 | 0.47 |
Maximum of Months | 0.680871E+09 | 0.903724E+09 | 26308.63 | 15038643.04 | 15158025.18 | 0.203176E+10 | 0.143031E+10 | 1934.37 | 0.47 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.716397E+09 | 0.00 | 0.00 | 809296.41 | 0.00 | 0.255722E+10 | 0.229121E+09 | 0.00 | 0.47 |
February | 0.659578E+09 | 0.00 | 0.00 | 1605212.59 | 0.00 | 0.187363E+10 | 0.403399E+09 | 0.00 | 0.47 |
March | 0.451461E+09 | 0.00 | 0.00 | 5415180.94 | 0.00 | 0.112593E+10 | 0.956668E+09 | 0.00 | 0.47 |
April | 0.131707E+09 | 7256840.54 | 0.00 | 12374115.79 | 290560.97 | 0.278562E+09 | 0.123457E+10 | 0.00 | 0.47 |
May | 53451807.17 | 47854030.60 | 2570.99 | 13924096.10 | 2404614.24 | 74083940.04 | 0.937131E+09 | 1968.48 | 0.47 |
June | 16162043.44 | 0.374359E+09 | 0.00 | 10053706.71 | 5610473.69 | 6649287.26 | 0.430912E+09 | 0.00 | 0.47 |
July | 42290.88 | 0.903422E+09 | 26308.80 | 1899640.88 | 15353145.66 | 1538.93 | 34058915.39 | 1086.25 | 0.47 |
August | 3415806.18 | 0.600182E+09 | 26262.81 | 4665886.22 | 11562922.32 | 0.00 | 0.106981E+09 | 160.67 | 0.47 |
September | 20402960.30 | 0.149306E+09 | 56230.83 | 10789286.37 | 5656155.13 | 269891.96 | 0.504930E+09 | 5425.40 | 0.47 |
October | 0.267370E+09 | 17829317.15 | 11857.06 | 8740552.82 | 1338297.21 | 0.490814E+09 | 0.947515E+09 | 1705.13 | 0.47 |
November | 0.636684E+09 | 0.00 | 0.00 | 2385608.73 | 0.00 | 0.146461E+10 | 0.653097E+09 | 0.00 | 0.47 |
December | 0.850098E+09 | 0.00 | 0.00 | 591282.29 | 0.00 | 0.250405E+10 | 0.242984E+09 | 0.00 | 0.47 |
Annual Sum or Average | 0.380677E+10 | 0.210021E+10 | 123230.50 | 73253865.85 | 42216169.22 | 0.103758E+11 | 0.668137E+10 | 10345.93 | 0.47 |
Minimum of Months | 42290.88 | 0.00 | 0.00 | 591282.29 | 0.00 | 0.00 | 34058915.39 | 0.00 | 0.47 |
Maximum of Months | 0.850098E+09 | 0.903422E+09 | 56230.83 | 13924096.10 | 15353145.66 | 0.255722E+10 | 0.123457E+10 | 5425.40 | 0.47 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.343218E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125123E+10 | 0.00 | 0.00 | 1.09 |
February | 0.314603E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 54838308.79 | 0.00 | 0.00 | 1.09 |
March | 0.328415E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.10 |
April | 0.252659E+11 | 0.00 | 0.00 | 0.00 | 63025613.73 | 0.00 | 0.00 | 0.00 | 1.10 |
May | 0.193826E+11 | 0.00 | 0.00 | 0.00 | 0.470378E+09 | 0.00 | 0.00 | 0.00 | 1.10 |
June | 0.101416E+11 | 0.00 | 0.00 | 0.00 | 0.252586E+10 | 0.00 | 0.00 | 0.00 | 1.10 |
July | 0.286848E+10 | 0.00 | 0.00 | 0.00 | 0.509827E+10 | 0.00 | 0.00 | 0.00 | 1.11 |
August | 0.545259E+10 | 0.00 | 0.00 | 0.00 | 0.317074E+10 | 0.00 | 0.00 | 0.00 | 1.10 |
September | 0.132615E+11 | 0.00 | 0.00 | 0.00 | 0.949491E+09 | 0.00 | 0.00 | 0.00 | 1.10 |
October | 0.261414E+11 | 0.00 | 0.00 | 0.00 | 0.144234E+09 | 0.00 | 0.00 | 0.00 | 1.10 |
November | 0.341372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.09 |
December | 0.352828E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.458035E+09 | 0.00 | 0.00 | 1.09 |
Annual Sum or Average | 0.270558E+12 | 0.00 | 0.00 | 0.00 | 0.124220E+11 | 0.176410E+10 | 0.00 | 0.00 | 1.10 |
Minimum of Months | 0.286848E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.09 |
Maximum of Months | 0.352828E+11 | 0.00 | 0.00 | 0.00 | 0.509827E+10 | 0.125123E+10 | 0.00 | 0.00 | 1.11 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.141642E+09 | 0.00 | 0.00 | 1024504.99 | 0.00 | 0.570740E+09 | 0.162582E+09 | 0.00 | 0.47 |
February | 0.116852E+09 | 0.00 | 0.00 | 1423645.11 | 0.00 | 0.429508E+09 | 0.186857E+09 | 0.00 | 0.47 |
March | 92399057.17 | 0.00 | 0.00 | 2280328.22 | 0.00 | 0.300320E+09 | 0.239945E+09 | 0.00 | 0.47 |
April | 50590974.41 | 1862530.59 | 0.00 | 3315344.14 | 24540.89 | 90370849.35 | 0.270075E+09 | 0.00 | 0.47 |
May | 32157996.93 | 12150875.79 | 979.10 | 2930167.74 | 415257.73 | 32458693.69 | 0.202133E+09 | 155.90 | 0.47 |
June | 8239014.39 | 93479561.43 | 4238.04 | 1940471.68 | 1519159.83 | 5097417.63 | 0.100681E+09 | 558.50 | 0.47 |
July | 53854.28 | 0.223283E+09 | 12478.07 | 404692.66 | 6432340.13 | 384.78 | 8542719.48 | 116.63 | 0.47 |
August | 2102019.77 | 0.149469E+09 | 5267.46 | 919238.58 | 3486097.79 | 38960.53 | 25708910.46 | 130.57 | 0.47 |
September | 10348676.55 | 37805663.57 | 0.00 | 2614974.84 | 954783.04 | 180508.31 | 0.120970E+09 | 0.00 | 0.47 |
October | 51676787.78 | 4615523.77 | 0.00 | 3394164.33 | 180332.27 | 0.117345E+09 | 0.256244E+09 | 0.00 | 0.47 |
November | 0.100552E+09 | 0.00 | 0.00 | 1752895.37 | 0.00 | 0.317829E+09 | 0.269141E+09 | 0.00 | 0.47 |
December | 0.150852E+09 | 0.00 | 0.00 | 894886.67 | 0.00 | 0.568930E+09 | 0.178859E+09 | 0.00 | 0.47 |
Annual Sum or Average | 0.757466E+09 | 0.522666E+09 | 22962.67 | 22895314.31 | 13012511.68 | 0.243282E+10 | 0.202174E+10 | 961.61 | 0.47 |
Minimum of Months | 53854.28 | 0.00 | 0.00 | 404692.66 | 0.00 | 384.78 | 8542719.48 | 0.00 | 0.47 |
Maximum of Months | 0.150852E+09 | 0.223283E+09 | 12478.07 | 3394164.33 | 6432340.13 | 0.570740E+09 | 0.270075E+09 | 558.50 | 0.47 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.155845E+09 | 0.00 | 0.00 | 277457.68 | 0.00 | 0.688861E+09 | 30902170.56 | 0.00 | 0.47 |
February | 0.142252E+09 | 0.00 | 0.00 | 568198.57 | 0.00 | 0.520751E+09 | 70982864.33 | 0.00 | 0.47 |
March | 0.118168E+09 | 0.00 | 0.00 | 1361267.48 | 0.00 | 0.363449E+09 | 0.151891E+09 | 0.00 | 0.47 |
April | 66334012.60 | 1862312.37 | 0.00 | 2711303.01 | 24538.01 | 0.108620E+09 | 0.236639E+09 | 0.00 | 0.47 |
May | 35843933.53 | 12141380.42 | 948.51 | 2747846.41 | 423280.79 | 34975368.30 | 0.196081E+09 | 186.35 | 0.47 |
June | 8534078.21 | 93478192.66 | 1708.00 | 1968038.65 | 1512353.83 | 4420662.92 | 0.101022E+09 | 132.26 | 0.47 |
July | 52653.27 | 0.222912E+09 | 9106.82 | 407321.40 | 6779750.09 | 384.73 | 8540237.11 | 25.03 | 0.47 |
August | 2111411.36 | 0.148251E+09 | 5109.75 | 878238.71 | 4686549.60 | 38955.96 | 25737152.59 | 287.65 | 0.47 |
September | 10952130.78 | 37170622.17 | 0.00 | 2167369.89 | 1585283.08 | 205746.12 | 0.120773E+09 | 0.00 | 0.47 |
October | 75726021.89 | 4341690.28 | 0.00 | 2075005.28 | 453603.86 | 0.175139E+09 | 0.175670E+09 | 0.00 | 0.47 |
November | 0.148423E+09 | 0.00 | 0.00 | 581215.50 | 0.00 | 0.444225E+09 | 95965541.15 | 0.00 | 0.47 |
December | 0.163354E+09 | 0.00 | 0.00 | 183164.14 | 0.00 | 0.711352E+09 | 24541072.80 | 0.00 | 0.47 |
Annual Sum or Average | 0.927597E+09 | 0.520157E+09 | 16873.09 | 15926426.71 | 15465359.28 | 0.305204E+10 | 0.123874E+10 | 631.29 | 0.47 |
Minimum of Months | 52653.27 | 0.00 | 0.00 | 183164.14 | 0.00 | 384.73 | 8540237.11 | 0.00 | 0.47 |
Maximum of Months | 0.163354E+09 | 0.222912E+09 | 9106.82 | 2747846.41 | 6779750.09 | 0.711352E+09 | 0.236639E+09 | 287.65 | 0.47 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.649255E+09 | 0.00 | 0.00 | 19427319.22 | 0.00 | 0.217338E+10 | 0.278572E+10 | 0.00 | 0.53 |
February | 0.455271E+09 | 0.00 | 0.00 | 18723753.76 | 0.00 | 0.155617E+10 | 0.268953E+10 | 0.00 | 0.53 |
March | 0.438044E+09 | 0.00 | 0.00 | 19322499.38 | 0.00 | 0.885571E+09 | 0.273625E+10 | 0.00 | 0.54 |
April | 0.256329E+09 | 11833029.60 | 0.00 | 18622763.06 | 290440.98 | 0.268046E+09 | 0.211901E+10 | 0.00 | 0.54 |
May | 0.197513E+09 | 76775188.78 | 5503.65 | 14904964.84 | 3955802.07 | 94857929.84 | 0.142528E+10 | 1788.14 | 0.54 |
June | 47141318.46 | 0.592117E+09 | 268279.52 | 9754235.55 | 17942168.20 | 691154.96 | 0.687384E+09 | 21548.16 | 0.54 |
July | 356972.57 | 0.142280E+10 | 988514.08 | 2207694.49 | 52042997.19 | 15093.09 | 55251252.01 | 50948.95 | 0.54 |
August | 13442955.53 | 0.956474E+09 | 429491.57 | 5322800.31 | 25756336.24 | 103194.29 | 0.165958E+09 | 34511.15 | 0.54 |
September | 61823932.09 | 0.243477E+09 | 0.00 | 17865972.62 | 5538605.32 | 561794.54 | 0.781360E+09 | 0.00 | 0.54 |
October | 0.240374E+09 | 30109575.32 | 0.00 | 29447308.15 | 701350.70 | 0.290649E+09 | 0.219345E+10 | 0.00 | 0.54 |
November | 0.342253E+09 | 0.00 | 0.00 | 26007676.53 | 0.00 | 0.751402E+09 | 0.330858E+10 | 0.00 | 0.53 |
December | 0.637442E+09 | 0.00 | 0.00 | 20893424.02 | 0.00 | 0.212645E+10 | 0.299427E+10 | 0.00 | 0.53 |
Annual Sum or Average | 0.333925E+10 | 0.333359E+10 | 1691788.82 | 0.202500E+09 | 0.106228E+09 | 0.814789E+10 | 0.219420E+11 | 108796.40 | 0.53 |
Minimum of Months | 356972.57 | 0.00 | 0.00 | 2207694.49 | 0.00 | 15093.09 | 55251252.01 | 0.00 | 0.53 |
Maximum of Months | 0.649255E+09 | 0.142280E+10 | 988514.08 | 29447308.15 | 52042997.19 | 0.217338E+10 | 0.330858E+10 | 50948.95 | 0.54 |
Report: MechanicalVentilationLoadsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.406578E+11 | 0.00 | 0.00 | 5332391.48 | 0.00 | 0.00 | 0.276219E+11 | 0.00 | 9.85 |
February | 0.340373E+11 | 0.00 | 0.00 | 5970157.32 | 0.00 | 0.00 | 0.264523E+11 | 0.00 | 9.88 |
March | 0.296970E+11 | 0.00 | 0.00 | 10269307.11 | 0.00 | 0.00 | 0.333343E+11 | 0.00 | 9.91 |
April | 0.174899E+11 | 40480876.93 | 0.00 | 14554552.61 | 80501174.72 | 0.00 | 0.309951E+11 | 0.00 | 9.91 |
May | 0.918852E+10 | 0.387436E+09 | 0.00 | 18613660.70 | 0.515488E+09 | 0.00 | 0.279992E+11 | 0.00 | 9.92 |
June | 0.272807E+10 | 0.304784E+10 | 0.00 | 20759545.41 | 0.180074E+10 | 0.00 | 0.167187E+11 | 0.00 | 9.93 |
July | 0.190772E+09 | 0.629867E+10 | 0.00 | 17975495.63 | 0.348782E+10 | 0.00 | 0.529750E+10 | 0.00 | 9.97 |
August | 0.806910E+09 | 0.327353E+10 | 0.00 | 20752869.53 | 0.281292E+10 | 0.00 | 0.963896E+10 | 0.00 | 9.96 |
September | 0.396132E+10 | 0.656660E+09 | 0.00 | 18813453.15 | 0.116595E+10 | 0.00 | 0.214762E+11 | 0.00 | 9.93 |
October | 0.201719E+11 | 63100902.53 | 0.00 | 13595600.53 | 0.213767E+09 | 0.00 | 0.299948E+11 | 0.00 | 9.91 |
November | 0.363145E+11 | 0.00 | 0.00 | 7926773.50 | 0.00 | 0.00 | 0.292063E+11 | 0.00 | 9.84 |
December | 0.411599E+11 | 0.00 | 0.00 | 5081663.09 | 0.00 | 0.00 | 0.274420E+11 | 0.00 | 9.85 |
Annual Sum or Average | 0.236404E+12 | 0.137677E+11 | 0.00 | 0.159645E+09 | 0.100772E+11 | 0.00 | 0.286177E+12 | 0.00 | 9.90 |
Minimum of Months | 0.190772E+09 | 0.00 | 0.00 | 5081663.09 | 0.00 | 0.00 | 0.529750E+10 | 0.00 | 9.84 |
Maximum of Months | 0.411599E+11 | 0.629867E+10 | 0.00 | 20759545.41 | 0.348782E+10 | 0.00 | 0.333343E+11 | 0.00 | 9.97 |
Report: MechanicalVentilationLoadsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.401650E+11 | 0.00 | 0.00 | 7129191.15 | 0.00 | 0.00 | 0.314632E+11 | 0.00 | 10.33 |
February | 0.327376E+11 | 0.00 | 0.00 | 7871565.00 | 0.00 | 0.00 | 0.307183E+11 | 0.00 | 10.36 |
March | 0.272328E+11 | 0.00 | 0.00 | 13403386.51 | 0.00 | 0.00 | 0.388885E+11 | 0.00 | 10.39 |
April | 0.160060E+11 | 67343486.53 | 0.00 | 18393946.73 | 59574524.63 | 0.00 | 0.348549E+11 | 0.00 | 10.39 |
May | 0.827832E+10 | 0.588233E+09 | 0.00 | 23135852.51 | 0.358992E+09 | 0.00 | 0.307304E+11 | 0.00 | 10.41 |
June | 0.223902E+10 | 0.432546E+10 | 0.00 | 24711100.68 | 0.761009E+09 | 0.00 | 0.181590E+11 | 0.00 | 10.42 |
July | 0.123635E+09 | 0.862308E+10 | 0.00 | 20678626.02 | 0.164358E+10 | 0.00 | 0.563210E+10 | 0.00 | 10.46 |
August | 0.713484E+09 | 0.478260E+10 | 0.00 | 24192269.79 | 0.160248E+10 | 0.00 | 0.102425E+11 | 0.00 | 10.45 |
September | 0.303961E+10 | 0.945704E+09 | 0.00 | 22727645.62 | 0.966337E+09 | 0.00 | 0.236430E+11 | 0.00 | 10.42 |
October | 0.185438E+11 | 0.128461E+09 | 0.00 | 16945353.22 | 0.161991E+09 | 0.00 | 0.340816E+11 | 0.00 | 10.40 |
November | 0.344415E+11 | 0.00 | 0.00 | 10216443.42 | 0.00 | 0.00 | 0.342921E+11 | 0.00 | 10.33 |
December | 0.410116E+11 | 0.00 | 0.00 | 6850844.43 | 0.00 | 0.00 | 0.309548E+11 | 0.00 | 10.34 |
Annual Sum or Average | 0.224532E+12 | 0.194609E+11 | 0.00 | 0.196256E+09 | 0.555396E+10 | 0.00 | 0.323660E+12 | 0.00 | 10.39 |
Minimum of Months | 0.123635E+09 | 0.00 | 0.00 | 6850844.43 | 0.00 | 0.00 | 0.563210E+10 | 0.00 | 10.33 |
Maximum of Months | 0.410116E+11 | 0.862308E+10 | 0.00 | 24711100.68 | 0.164358E+10 | 0.00 | 0.388885E+11 | 0.00 | 10.46 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.101301E+09 | 0.00 | 0.00 | 0.690610E+11 | 0.00 | 32.19 |
February | 0.00 | 0.00 | 0.00 | 93809188.63 | 0.00 | 0.00 | 0.611901E+11 | 0.00 | 32.31 |
March | 0.00 | 0.00 | 0.00 | 0.110809E+09 | 0.00 | 0.00 | 0.637674E+11 | 0.00 | 32.41 |
April | 0.00 | 0.122823E+09 | 0.00 | 0.113175E+09 | 0.00 | 0.00 | 0.490356E+11 | 0.00 | 32.43 |
May | 0.00 | 0.916961E+09 | 0.00 | 97365772.90 | 0.00 | 0.00 | 0.376024E+11 | 0.00 | 32.47 |
June | 0.00 | 0.492631E+10 | 0.00 | 64659033.05 | 0.00 | 0.00 | 0.196558E+11 | 0.00 | 32.49 |
July | 0.00 | 0.994159E+10 | 0.00 | 31638959.87 | 0.00 | 0.00 | 0.554418E+10 | 0.00 | 32.63 |
August | 0.00 | 0.618374E+10 | 0.00 | 50613877.21 | 0.00 | 0.00 | 0.105504E+11 | 0.00 | 32.60 |
September | 0.00 | 0.185175E+10 | 0.00 | 79770127.24 | 0.00 | 0.00 | 0.257075E+11 | 0.00 | 32.50 |
October | 0.00 | 0.281165E+09 | 0.00 | 0.111176E+09 | 0.00 | 0.00 | 0.507340E+11 | 0.00 | 32.42 |
November | 0.00 | 0.00 | 0.00 | 0.104949E+09 | 0.00 | 0.00 | 0.662817E+11 | 0.00 | 32.20 |
December | 0.00 | 0.00 | 0.00 | 0.100517E+09 | 0.00 | 0.00 | 0.693830E+11 | 0.00 | 32.21 |
Annual Sum or Average | 0.00 | 0.242243E+11 | 0.00 | 0.105978E+10 | 0.00 | 0.00 | 0.528513E+12 | 0.00 | 32.41 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 31638959.87 | 0.00 | 0.00 | 0.554418E+10 | 0.00 | 32.19 |
Maximum of Months | 0.00 | 0.994159E+10 | 0.00 | 0.113175E+09 | 0.00 | 0.00 | 0.693830E+11 | 0.00 | 32.63 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.143973E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.795400E+10 | 0.00 | 0.00 | 2.59 |
February | 0.147940E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.500764E+10 | 0.00 | 0.00 | 2.60 |
March | 0.192977E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133729E+10 | 0.00 | 0.00 | 2.60 |
April | 0.158551E+11 | 0.00 | 0.00 | 0.00 | 39600305.31 | 20012670.97 | 0.00 | 0.00 | 2.60 |
May | 0.121785E+11 | 0.00 | 0.00 | 0.00 | 0.295548E+09 | 0.00 | 0.00 | 0.00 | 2.61 |
June | 0.637218E+10 | 0.00 | 0.00 | 0.00 | 0.158705E+10 | 0.00 | 0.00 | 0.00 | 2.61 |
July | 0.180233E+10 | 0.00 | 0.00 | 0.00 | 0.320335E+10 | 0.00 | 0.00 | 0.00 | 2.62 |
August | 0.342598E+10 | 0.00 | 0.00 | 0.00 | 0.199224E+10 | 0.00 | 0.00 | 0.00 | 2.62 |
September | 0.833245E+10 | 0.00 | 0.00 | 0.00 | 0.596585E+09 | 0.00 | 0.00 | 0.00 | 2.61 |
October | 0.157496E+11 | 0.00 | 0.00 | 0.00 | 90625437.49 | 0.675589E+09 | 0.00 | 0.00 | 2.60 |
November | 0.195671E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188204E+10 | 0.00 | 0.00 | 2.59 |
December | 0.147948E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.766191E+10 | 0.00 | 0.00 | 2.59 |
Annual Sum or Average | 0.146567E+12 | 0.00 | 0.00 | 0.00 | 0.780500E+10 | 0.245385E+11 | 0.00 | 0.00 | 2.60 |
Minimum of Months | 0.180233E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.59 |
Maximum of Months | 0.195671E+11 | 0.00 | 0.00 | 0.00 | 0.320335E+10 | 0.795400E+10 | 0.00 | 0.00 | 2.62 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:57:58
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.255385E+12 | 0.138036E+11 | 0.100497E+12 | 0.154250E+13 | 0.148384E+12 |
February | 0.324304E+12 | 0.113783E+11 | 0.835191E+11 | 0.127718E+13 | 0.159199E+12 |
March | 0.446694E+12 | 0.960809E+10 | 0.721444E+11 | 0.106755E+13 | 0.253470E+12 |
April | 0.559772E+12 | 0.612853E+10 | 0.500816E+11 | 0.656513E+12 | 0.484104E+12 |
May | 0.604837E+12 | 0.385748E+10 | 0.354938E+11 | 0.396520E+12 | 0.729485E+12 |
June | 0.564458E+12 | 0.642084E+09 | 0.122757E+11 | 0.339609E+11 | 0.110498E+13 |
July | 0.566430E+12 | -0.217864E+10 | -0.203166E+10 | -0.237271E+12 | 0.147659E+13 |
August | 0.540008E+12 | -861415230.5 | 0.721861E+10 | -0.910110E+11 | 0.133638E+13 |
September | 0.430216E+12 | 0.190341E+10 | 0.230802E+11 | 0.189004E+12 | 0.951169E+12 |
October | 0.343121E+12 | 0.643315E+10 | 0.530109E+11 | 0.698387E+12 | 0.534192E+12 |
November | 0.272200E+12 | 0.103659E+11 | 0.800928E+11 | 0.116535E+13 | 0.190644E+12 |
December | 0.231842E+12 | 0.141303E+11 | 0.104214E+12 | 0.158130E+13 | 0.145539E+12 |
Annual Sum or Average | 0.513927E+13 | 0.752108E+11 | 0.619596E+12 | 0.827999E+13 | 0.751414E+13 |
Minimum of Months | 0.231842E+12 | -0.217864E+10 | -0.203166E+10 | -0.237271E+12 | 0.145539E+12 |
Maximum of Months | 0.604837E+12 | 0.141303E+11 | 0.104214E+12 | 0.158130E+13 | 0.147659E+13 |