Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:58
Tabular Output Report in Format: HTML
Building: HotelLarge
Environment: RUNPERIOD 1 ** Dubai Intl AP - ARE IWEC2 WMO#=411940
Simulation Timestamp: 2023-10-16 08:58:09
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:58:09
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 18380.30 | 1620.08 | 1620.08 |
Net Site Energy | 18380.30 | 1620.08 | 1620.08 |
Total Source Energy | 48123.72 | 4241.74 | 4241.74 |
Net Source Energy | 48123.72 | 4241.74 | 4241.74 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 11345.29 |
Net Conditioned Building Area | 11345.29 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 580.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 6426.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1174.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 262.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1751.30 | 1788.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 679.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2043.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 464.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 569.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 90.77 | 2473.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Refrigeration | 75.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 13537.92 | 4842.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 580.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 6426.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 1174.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 262.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 959.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 762.04 | 1198.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 16.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 13.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 590.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 32.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 616.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 30.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 2043.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 464.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 569.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 90.77 | 2473.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5742.51 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4114.69 | |
Refrigeration | General | 18.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 22.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 34.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 580.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 6426.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 1174.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 262.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 1751.30 | 1788.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 679.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 2043.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 464.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 569.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 90.77 | 2473.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Refrigeration | Unassigned | 75.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 126.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 795.48 | 269.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Other | 271.14 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 1193.26 | 426.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 126.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 795.48 | 269.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Other | 271.14 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 1193.26 | 426.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 13537.916 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 13537.916 | 100.00 |
Total On-Site and Utility Electric Sources | 13537.916 | 100.00 |
Total Electricity End Uses | 13537.916 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | 0.00 |
Air to Air Heat Recovery for Cooling | 10182.72 | 99.70 |
Air to Air Heat Recovery for Heating | 30.16 | 0.30 |
High-Temperature Geothermal* | 0.00 | 0.00 |
Solar Water Thermal | 0.00 | 0.00 |
Solar Air Thermal | 0.00 | 0.00 |
Total On-Site Thermal Sources | 10212.89 | 100.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 9857.19 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 9857.19 | 100.00 |
Total Water End Uses | 9857.19 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 13.33 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 5985.33 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2012
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 0B
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY ARE_DUBAI_DUBAIINTL
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneHeatingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneElectricSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |PeakSpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ComfortReportSimple55Monthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |OccupantComfortDataSummaryMonthly
| BASEMENT PEOPLE | RETAIL_1_FLR_1 PEOPLE | RETAIL_2_FLR_1 PEOPLE | LAUNDRY_FLR_1 PEOPLE | CAFE_FLR_1 PEOPLE | LOBBY_FLR_1 PEOPLE | ROOM_1_FLR_3 PEOPLE | ROOM_2_FLR_3 PEOPLE | ROOM_3_MULT19_FLR_3 PEOPLE | ROOM_4_MULT19_FLR_3 PEOPLE | ROOM_5_FLR_3 PEOPLE | ROOM_6_FLR_3 PEOPLE | ROOM_1_FLR_6 PEOPLE | ROOM_2_FLR_6 PEOPLE | ROOM_3_MULT9_FLR_6 PEOPLE | BANQUET_FLR_6 PEOPLE | DINING_FLR_6 PEOPLE | KITCHEN_FLR_6 PEOPLE | STORAGE_FLR_1 PEOPLE | CORRIDOR_FLR_3 PEOPLE | CORRIDOR_FLR_6 PEOPLE | MECH_FLR_1 PEOPLE |ChillerReportMonthly
| COOLSYS1 CHILLER1 |BoilerReportMonthly
| HEATSYS1 BOILER |DXReportMonthly
| VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |WindowReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowEnergyReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWH BOOSTER E WATER HEATER | SWH LAUNDRY G WATER HEATER | SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| VAV WITH REHEAT HEATING COIL | BASEMENT VAV BOX REHEAT COIL | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | MECH_FLR_1 VAV BOX REHEAT COIL | STORAGE_FLR_1 VAV BOX REHEAT COIL | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | CAFE_FLR_1 VAV BOX REHEAT COIL | LOBBY_FLR_1 VAV BOX REHEAT COIL | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | BANQUET_FLR_6 VAV BOX REHEAT COIL | DINING_FLR_6 VAV BOX REHEAT COIL | KITCHEN_FLR_6 VAV BOX REHEAT COIL | FLR_3_DOAS HEATING COIL | ROOM_1_FLR_3 FAN COIL HEATING COIL | ROOM_2_FLR_3 FAN COIL HEATING COIL | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_5_FLR_3 FAN COIL HEATING COIL | ROOM_6_FLR_3 FAN COIL HEATING COIL | ROOM_1_FLR_6 FAN COIL HEATING COIL | ROOM_2_FLR_6 FAN COIL HEATING COIL | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1 | SWHSYS1 |FanReportMonthly
| FLR_3_DOAS FAN | VAV WITH REHEAT FAN | LAUNDRY_FLR_1 EXHAUST FAN | LOBBY_FLR_1 EXHAUST FAN | BANQUET_FLR_6 EXHAUST FAN | DINING_FLR_6 EXHAUST FAN | KITCHEN_FLR_6 EXHAUST FAN | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 PUMP | SWHSYS1 PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1 | SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV WITH REHEAT | FLR_3_DOAS |AirLoopSystemComponentLoadsMonthly
| VAV WITH REHEAT | FLR_3_DOAS |AirLoopSystemComponentEnergyUseMonthly
| VAV WITH REHEAT | FLR_3_DOAS |MechanicalVentilationLoadsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:58:09
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:58 |
RunPeriod | RUNPERIOD 1 |
Weather File | Dubai Intl AP - ARE IWEC2 WMO#=411940 |
Latitude [deg] | 25.25 |
Longitude [deg] | 55.33 |
Elevation [m] | 5.00 |
Time Zone | 4.00 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1213.79 | 432.95 | 85.85 | 609.15 | 85.85 |
Gross Window-Wall Ratio [%] | 26.62 | 23.11 | 21.12 | 32.52 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.15 | 26.05 | 24.48 | 36.65 | 24.48 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1213.79 | 432.95 | 85.85 | 609.15 | 85.85 |
Gross Window-Wall Ratio [%] | 26.62 | 23.11 | 21.12 | 32.52 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.15 | 26.05 | 24.48 | 36.65 | 24.48 |
Total | |
Gross Roof Area [m2] | 1978.84 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 1978.83 | Yes | Yes | 4826.41 | 1.00 | 0.00 | 533.77 | 0.00 | 0.00 | 8.7495 | 18.58 | 5.3800 |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 265.76 | 1.00 | 68.84 | 0.00 | 23.26 | 23.26 | 13.0124 | 6.19 | 10.7600 |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 307.76 | 1.00 | 26.57 | 0.00 | 0.00 | 0.00 | 13.0124 | 6.19 | 10.7600 |
MECH_FLR_1 | 164.24 | Yes | Yes | 650.80 | 1.00 | 62.80 | 0.00 | 0.00 | 0.00 | 10.0642 | 61.93 | 5.3800 |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 375.47 | 1.00 | 36.23 | 0.00 | 0.00 | 0.00 | 7.3195 | 46.45 | 2.6900 |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 309.22 | 1.00 | 85.75 | 0.00 | 0.00 | 0.00 | 5.4896 | 9.29 | 597.5300 |
CAFE_FLR_1 | 188.86 | Yes | Yes | 748.35 | 1.00 | 152.17 | 0.00 | 65.50 | 65.50 | 12.8090 | 1.33 | 5.3800 |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 5183.56 | 1.00 | 434.79 | 0.00 | 85.08 | 85.08 | 10.0642 | 3.10 | 8.0700 |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 10.0642 | 26.01 | 6.7500 |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 10.0642 | 26.01 | 6.7500 |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 74.75 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 10.0642 | 16.35 | 10.5200 |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 74.77 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 10.0642 | 16.35 | 10.5200 |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 10.0642 | 26.01 | 6.7500 |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 10.0642 | 26.01 | 6.7500 |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 1186.91 | 4.00 | 48.31 | 0.00 | 15.94 | 15.94 | 3.6597 | 18.58 | 0.0000 |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 118.94 | 1.00 | 39.95 | 0.00 | 13.18 | 13.18 | 10.0642 | 26.01 | 6.7500 |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 118.93 | 1.00 | 39.95 | 0.00 | 13.18 | 13.18 | 10.0642 | 26.01 | 6.7500 |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 74.77 | 9.00 | 20.44 | 0.00 | 6.74 | 6.74 | 10.0642 | 16.35 | 10.5200 |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.19 | 32.19 | 12.8090 | 1.33 | 67.8200 |
DINING_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.19 | 32.19 | 12.8090 | 1.33 | 67.8200 |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 314.87 | 1.00 | 87.33 | 0.00 | 26.37 | 26.37 | 10.9792 | 4.65 | 2936.4163 |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1256.16 | 1.00 | 85.47 | 0.00 | 28.20 | 28.20 | 3.6597 | 18.58 | 0.0000 |
Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1213.79 | 1213.79 | 8.9207 | 7.07 | 41.0885 | |||
Conditioned Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1213.79 | 1213.79 | 8.9207 | 7.07 | 41.0885 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 1978.83 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 8.7495 | 18.58 | 5.3800 | |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 1.00 | RETAIL_1_FLR_1 | GENERAL | RETAIL_1_FLR_1 | 13.0124 | 6.19 | 10.7600 | |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 1.00 | RETAIL_2_FLR_1 | GENERAL | RETAIL_2_FLR_1 | 13.0124 | 6.19 | 10.7600 | |
MECH_FLR_1 | 164.24 | Yes | Yes | 1.00 | MECH_FLR_1 | GENERAL | MECH_FLR_1 | 10.0642 | 61.93 | 5.3800 | |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 1.00 | STORAGE_FLR_1 | GENERAL | STORAGE_FLR_1 | 7.3195 | 46.45 | 2.6900 | |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 1.00 | LAUNDRY_FLR_1 | GENERAL | LAUNDRY_FLR_1 | 5.4896 | 9.29 | 597.5300 | |
CAFE_FLR_1 | 188.86 | Yes | Yes | 1.00 | CAFE_FLR_1 | GENERAL | CAFE_FLR_1 | 12.8090 | 1.33 | 5.3800 | |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 1.00 | LOBBY_FLR_1 | GENERAL | LOBBY_FLR_1 | 10.0642 | 3.10 | 8.0700 | |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_1_FLR_3 | GENERAL | ROOM_1_FLR_3 | 10.0642 | 26.01 | 6.7500 | |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_2_FLR_3 | GENERAL | ROOM_2_FLR_3 | 10.0642 | 26.01 | 6.7500 | |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 76.00 | ROOM_3_MULT19_FLR_3 | GENERAL | ROOM_3_MULT19_FLR_3 | 10.0642 | 16.35 | 10.5200 | |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 76.00 | ROOM_4_MULT19_FLR_3 | GENERAL | ROOM_4_MULT19_FLR_3 | 10.0642 | 16.35 | 10.5200 | |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_5_FLR_3 | GENERAL | ROOM_5_FLR_3 | 10.0642 | 26.01 | 6.7500 | |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_6_FLR_3 | GENERAL | ROOM_6_FLR_3 | 10.0642 | 26.01 | 6.7500 | |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 4.00 | CORRIDOR_FLR_3 | GENERAL | CORRIDOR_FLR_3 | 3.6597 | 18.58 | 0.0000 | |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 1.00 | ROOM_1_FLR_6 | GENERAL | ROOM_1_FLR_6 | 10.0642 | 26.01 | 6.7500 | |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 1.00 | ROOM_2_FLR_6 | GENERAL | ROOM_2_FLR_6 | 10.0642 | 26.01 | 6.7500 | |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 9.00 | ROOM_3_MULT9_FLR_6 | GENERAL | ROOM_3_MULT9_FLR_6 | 10.0642 | 16.35 | 10.5200 | |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1.00 | BANQUET_FLR_6 | GENERAL | BANQUET_FLR_6 | 12.8090 | 1.33 | 67.8200 | |
DINING_FLR_6 | 331.66 | Yes | Yes | 1.00 | DINING_FLR_6 | GENERAL | DINING_FLR_6 | 12.8090 | 1.33 | 67.8200 | |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 1.00 | KITCHEN_FLR_6 | GENERAL | KITCHEN_FLR_6 | 10.9792 | 4.65 | 2936.4163 | |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1.00 | CORRIDOR_FLR_6 | GENERAL | CORRIDOR_FLR_6 | 3.6597 | 18.58 | 0.0000 | |
Total | 11345.29 | 8.9207 | 3.54 | 41.0885 | |||||||
Conditioned Total | 11345.29 | 8.9207 | 3.54 | 41.0885 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 11345.29 | 11345.29 | 0.00 | 0.00 | 4.6908 | 8.82 | 37.2165 |
Total | 11345.29 | 11345.29 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:58:09
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 10-AUG-18:10 | 20-FEB-18:40 | - | - | - | - | - | - | - | - | - | - | 02-JAN-21:10 |
Heating | 0.00 | 43165.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 518776.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 82800.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 79617.06 | 100066.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 32686.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 84299.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 18315.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 18408.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 4738.47 | 213109.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 2933.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 842574.52 | 356341.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 43165.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 518776.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 82800.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 49434.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 29240.64 | 74976.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 515.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 425.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 25090.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 1560.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 30153.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 972.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 84299.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 18315.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 18408.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 4738.47 | 213109.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 642.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 1186.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 1104.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:58:09
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 629.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 20352.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 3718.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 831.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 5546.36 | 1939.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 2152.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 6470.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 1470.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 1803.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 287.48 | 2680.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 239.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 42874.58 | 5249.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 55.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1793.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 327.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 73.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 488.87 | 170.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 189.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 570.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 129.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 158.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 25.34 | 236.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 21.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 3779.07 | 462.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 55.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1793.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 327.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 73.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 488.87 | 170.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 189.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 570.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 129.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 158.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 25.34 | 236.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 21.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 3779.07 | 462.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:58:09
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
BASEMENT VAV BOX COMPONENT | 2.90 | 0.519983 | 0.996000 | 2.89 | 1.00 | 0.500000 | 0.000733 | 0.000133 | 2.89 | 16.70 | 0.008000 |
RETAIL_1_FLR_1 VAV BOX COMPONENT | 0.402173 | 0.127080 | 0.996000 | 0.400565 | 0.996000 | 0.500000 | 0.002998 | 0.000028 | 0.400565 | 16.70 | 0.008000 |
RETAIL_2_FLR_1 VAV BOX COMPONENT | 0.264993 | 0.223340 | 0.996000 | 0.263933 | 0.996000 | 0.500000 | 0.001706 | 0.000015 | 0.263933 | 16.70 | 0.008000 |
MECH_FLR_1 VAV BOX COMPONENT | 0.305298 | 0.409939 | 0.996000 | 0.304077 | 1.00 | 0.500000 | 0.000929 | 0.000019 | 0.304077 | 16.70 | 0.008000 |
STORAGE_FLR_1 VAV BOX COMPONENT | 0.155673 | 0.463836 | 0.996000 | 0.155050 | 1.00 | 0.500000 | 0.000821 | 0.000010 | 0.155050 | 16.70 | 0.008000 |
LAUNDRY_FLR_1 VAV BOX COMPONENT | 3.32 | 0.071087 | 0.996000 | 3.31 | 0.996000 | 0.500000 | 0.021268 | 0.000161 | 3.31 | 16.70 | 0.008000 |
CAFE_FLR_1 VAV BOX COMPONENT | 1.60 | 0.090174 | 0.996000 | 1.59 | 0.996000 | 0.500000 | 0.004225 | 0.000098 | 1.59 | 16.70 | 0.008000 |
LOBBY_FLR_1 VAV BOX COMPONENT | 5.11 | 0.195058 | 0.996000 | 5.09 | 0.996000 | 0.500000 | 0.001953 | 0.000287 | 5.09 | 16.70 | 0.008000 |
CORRIDOR_FLR_3 VAV BOX COMPONENT | 1.40 | 0.845511 | 0.996000 | 1.40 | 1.00 | 0.500000 | 0.000451 | 0.000101 | 1.40 | 16.70 | 0.008000 |
BANQUET_FLR_6 VAV BOX COMPONENT | 2.40 | 0.105461 | 0.996000 | 2.39 | 0.996000 | 0.500000 | 0.003613 | 0.000135 | 2.39 | 16.70 | 0.008000 |
DINING_FLR_6 VAV BOX COMPONENT | 2.51 | 0.100797 | 0.996000 | 2.50 | 0.996000 | 0.500000 | 0.003780 | 0.000139 | 2.50 | 16.70 | 0.008000 |
KITCHEN_FLR_6 VAV BOX COMPONENT | 2.36 | 0.799178 | 0.996000 | 2.35 | 0.996000 | 0.500000 | 0.011433 | 0.000109 | 2.35 | 16.70 | 0.008000 |
CORRIDOR_FLR_6 VAV BOX COMPONENT | 0.843569 | 0.372274 | 0.996000 | 0.840195 | 0.996000 | 0.500000 | 0.001023 | 0.000064 | 0.840195 | 16.70 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
BASEMENT VAV BOX REHEAT COIL | 15242.62 | 0.000133 | 317.86 |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 3231.93 | 0.000028 | 69.30 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 1730.88 | 0.000015 | 36.55 |
MECH_FLR_1 VAV BOX REHEAT COIL | 2204.96 | 0.000019 | 46.89 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | 1171.70 | 0.000010 | 24.99 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 18371.26 | 0.000161 | 384.15 |
CAFE_FLR_1 VAV BOX REHEAT COIL | 11194.77 | 0.000098 | 237.57 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | 32825.24 | 0.000287 | 692.49 |
ROOM_1_FLR_3 FAN COIL HEATING COIL | 2586.65 | 0.000023 | 73.88 |
ROOM_2_FLR_3 FAN COIL HEATING COIL | 2584.69 | 0.000023 | 73.83 |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | 19405.55 | 0.000170 | 554.30 |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | 19410.86 | 0.000170 | 554.45 |
ROOM_5_FLR_3 FAN COIL HEATING COIL | 2590.21 | 0.000023 | 73.99 |
ROOM_6_FLR_3 FAN COIL HEATING COIL | 2588.25 | 0.000023 | 73.93 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 11495.13 | 0.000101 | 246.87 |
ROOM_1_FLR_6 FAN COIL HEATING COIL | 815.09 | 0.000007 | 23.28 |
ROOM_2_FLR_6 FAN COIL HEATING COIL | 814.77 | 0.000007 | 23.27 |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | 3967.86 | 0.000035 | 113.34 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | 15392.13 | 0.000135 | 324.72 |
DINING_FLR_6 VAV BOX REHEAT COIL | 15871.77 | 0.000139 | 334.52 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | 12416.40 | 0.000109 | 258.92 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 7354.89 | 0.000064 | 158.82 |
VAV WITH REHEAT HEATING COIL | 34066.70 | 0.000298 | 652.40 |
FLR_3_DOAS HEATING COIL | 2977.14 | 0.000026 | 57.01 |
User-Specified Maximum Flow Rate [m3/s] | |
LOBBY_FLR_1 EXHAUST FAN | 0.000000 |
BANQUET_FLR_6 EXHAUST FAN | 0.000000 |
DINING_FLR_6 EXHAUST FAN | 0.000000 |
Design Size Maximum Air Flow Rate [m3/s] | |
ROOM_1_FLR_3 DIRECT AIR | 0.061735 |
ROOM_2_FLR_3 DIRECT AIR | 0.061728 |
ROOM_3_MULT19_FLR_3 DIRECT AIR | 0.837072 |
ROOM_4_MULT19_FLR_3 DIRECT AIR | 0.837300 |
ROOM_5_FLR_3 DIRECT AIR | 0.061735 |
ROOM_6_FLR_3 DIRECT AIR | 0.061728 |
ROOM_1_FLR_6 DIRECT AIR | 0.015434 |
ROOM_2_FLR_6 DIRECT AIR | 0.015432 |
ROOM_3_MULT9_FLR_6 DIRECT AIR | 0.099154 |
Design Size Maximum Supply Air Flow Rate [m3/s] | Design Size Maximum Hot Water Flow [m3/s] | Design Size Maximum Cold Water Flow [m3/s] | |
ROOM_1_FLR_3 FAN COIL | 1.26 | 0.000023 | 0.000551 |
ROOM_2_FLR_3 FAN COIL | 1.23 | 0.000023 | 0.000541 |
ROOM_3_MULT19_FLR_3 FAN COIL | 7.98 | 0.000170 | 0.003442 |
ROOM_4_MULT19_FLR_3 FAN COIL | 8.31 | 0.000170 | 0.003729 |
ROOM_5_FLR_3 FAN COIL | 1.13 | 0.000023 | 0.000499 |
ROOM_6_FLR_3 FAN COIL | 1.11 | 0.000023 | 0.000490 |
ROOM_1_FLR_6 FAN COIL | 0.342804 | 0.000007 | 0.000150 |
ROOM_2_FLR_6 FAN COIL | 0.337175 | 0.000007 | 0.000148 |
ROOM_3_MULT9_FLR_6 FAN COIL | 1.64 | 0.000035 | 0.000726 |
Design Size Maximum Flow Rate [m3/s] | |
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | 1.26 |
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | 1.23 |
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | 7.98 |
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | 8.31 |
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | 1.13 |
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | 1.11 |
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | 0.342804 |
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | 0.337175 |
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | 1.64 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Temperature [C] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | Design Size Design Coil Load [W] | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | 22.49 | 6.70 | 0.008623 | 12.80 | 0.008500 | 0.000551 | 1.26 | |
ROOM_2_FLR_3 FAN COIL COOLING COIL | 22.49 | 6.70 | 0.008625 | 12.80 | 0.008500 | 0.000541 | 1.23 | |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | 22.49 | 6.70 | 0.008555 | 12.80 | 0.008500 | 0.003442 | 7.98 | |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | 22.49 | 6.70 | 0.008719 | 12.80 | 0.008500 | 0.003729 | 8.31 | |
ROOM_5_FLR_3 FAN COIL COOLING COIL | 22.49 | 6.70 | 0.008637 | 12.80 | 0.008500 | 0.000499 | 1.13 | |
ROOM_6_FLR_3 FAN COIL COOLING COIL | 22.49 | 6.70 | 0.008639 | 12.80 | 0.008500 | 0.000490 | 1.11 | |
ROOM_1_FLR_6 FAN COIL COOLING COIL | 22.49 | 6.70 | 0.008613 | 12.80 | 0.008500 | 0.000150 | 0.342804 | |
ROOM_2_FLR_6 FAN COIL COOLING COIL | 22.49 | 6.70 | 0.008615 | 12.80 | 0.008500 | 0.000148 | 0.337175 | |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | 22.49 | 6.70 | 0.008657 | 12.80 | 0.008500 | 0.000726 | 1.64 | |
VAV WITH REHEAT COOLING COIL | 42.80 | 6.70 | 0.010782 | 10.98 | 0.008500 | 0.038710 | 23.47 | 1083772.56 |
FLR_3_DOAS COOLING COIL | 42.80 | 6.70 | 0.010782 | 11.93 | 0.008500 | 0.003297 | 2.05 | 92321.21 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV WITH REHEAT | 23.47 | 23.47 | 23.57 | 23.47 | 23.47 | 23.47 | 0.300000 | 1.00 | 23.47 |
FLR_3_DOAS | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 0.300000 | 1.00 | 2.05 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV WITH REHEAT_OA_CONTROLLER | 23.47 | 23.47 |
FLR_3_DOAS_OA_CONTROLLER | 2.05 | 2.05 |
Design Size Nominal Supply Air Flow Rate [m3/s] | |
VAV WITH REHEAT OA HEAT RECOVERY | 23.47 |
FLR_3_DOAS OA HEAT RECOVERY | 2.05 |
Design Size Maximum Flow Rate [m3/s] | |
VAV WITH REHEAT FAN | 23.47 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV WITH REHEAT_COOLC_CONTROLLER | 0.038710 | 0.000012 |
VAV WITH REHEAT_HEATC_CONTROLLER | 0.000298 | |
FLR_3_DOAS_COOLC_CONTROLLER | 0.003297 | 0.000144 |
FLR_3_DOAS_HEATC_CONTROLLER | 0.000026 |
User-Specified Maximum Flow Rate [m3/s] | |
FLR_3_DOAS FAN | 2.05 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.052282 | 10773.42 | |
HEATSYS1 PUMP | 0.002102 | 633.14 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
HEATSYS1 | 0.002102 | 0.252282 |
COOLSYS1 | 0.052282 | 6.27 |
SWHSYS1 | 0.000375 | 0.045004 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 240311.47 | 240311.47 | 0.002102 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 PUMP | 0.052282 | 7458.80 |
SWHSYS1 PUMP | 0.000375 | 47.91 |
Design Size Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Fluid Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.052282 | 1463761.66 | 1464401.58 | 166.94 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000375 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:58:09
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesPossible Shadow Receivers | |
RETAIL_1_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
CAFE_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
LOBBY_FLR_1_CEILING_2 | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
Possible Shadow Receivers | |
RETAIL_1_FLR_1_WALL_SOUTH | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | |
RETAIL_2_FLR_1_WALL_WEST | RETAIL_2_FLR_1_WALL_WEST_DOOR | |
STORAGE_FLR_1_WALL_NORTH | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | |
LAUNDRY_FLR_1_WALL_EAST | LAUNDRY_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_EAST | CAFE_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_SOUTH | CAFE_FLR_1_WALL_SOUTH_WINDOW | |
LOBBY_FLR_1_WALL_1_NORTH | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | |
LOBBY_FLR_1_WALL_1_SOUTH | LOBBY_FLR_1_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_SOUTH | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_WEST | ROOM_1_FLR_3_WALL_WEST_WINDOW | |
ROOM_2_FLR_3_WALL_NORTH | ROOM_2_FLR_3_WALL_NORTH_WINDOW | |
ROOM_2_FLR_3_WALL_WEST | ROOM_2_FLR_3_WALL_WEST_WINDOW | |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_4_MULT19_FLR_3_WALL_NORTH | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | |
ROOM_5_FLR_3_WALL_EAST | ROOM_5_FLR_3_WALL_EAST_WINDOW | |
ROOM_5_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_6_FLR_3_WALL_NORTH | ROOM_6_FLR_3_WALL_NORTH_WINDOW | |
ROOM_6_FLR_3_WALL_EAST | ROOM_6_FLR_3_WALL_EAST_WINDOW | |
CORRIDOR_FLR_3_WALL_1_NORTH | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_NORTH | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_SOUTH | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_WEST | ROOM_1_FLR_6_WALL_WEST_WINDOW | |
ROOM_2_FLR_6_WALL_NORTH | ROOM_2_FLR_6_WALL_NORTH_WINDOW | |
ROOM_2_FLR_6_WALL_WEST | ROOM_2_FLR_6_WALL_WEST_WINDOW | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | |
BANQUET_FLR_6_WALL_NORTH | BANQUET_FLR_6_WALL_NORTH_WINDOW | |
DINING_FLR_6_WALL_NORTH | DINING_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_NORTH | KITCHEN_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_EAST | KITCHEN_FLR_6_WALL_EAST_WINDOW | |
KITCHEN_FLR_6_WALL_1_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_6_WALL_1_NORTH | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_NORTH | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:58:09
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:58:09
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 29.50 | 25.50 | 21.10 | 19.20 | 20.80 | 23.10 | 26.50 | 31.40 | 33.00 | 35.10 | 35.30 | 32.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Dubai Intl AP - ARE IWEC2 WMO#=411940 | 25.25 | 55.33 | 4.00 | 5.00 | 101265 | 1.2036 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 27.75 | 16.10 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | HotelLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | DOE-2 |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 22 | 235 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 41.45 | 11.51 | -1.22 | 1 | 1 | 1 | 0.00 | 86.56 | 0.00 | 22.86 | -2.44 | 0.00 | 2.44 | 4826.41 | TARP | DOE-2 | 1978.83 | 0.00 | 0.00 | 0.00 | 13 | 0 | 0 | Yes |
2 | RETAIL_1_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 2.90 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 265.76 | TARP | DOE-2 | 67.07 | 68.84 | 45.58 | 23.26 | 6 | 1 | 0 | Yes |
3 | RETAIL_2_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 9.14 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 5.79 | 12.50 | 0.00 | 3.96 | 3.96 | 307.76 | TARP | DOE-2 | 77.67 | 26.57 | 24.62 | 0.00 | 6 | 1 | 0 | Yes |
4 | MECH_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 61.87 | 17.68 | 1.98 | 1 | 1 | 1 | 53.95 | 69.80 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 650.80 | TARP | DOE-2 | 164.24 | 62.80 | 62.80 | 0.00 | 6 | 0 | 0 | Yes |
5 | STORAGE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 74.37 | 17.68 | 1.98 | 1 | 1 | 1 | 69.80 | 78.94 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 375.47 | TARP | DOE-2 | 94.76 | 36.23 | 28.80 | 0.00 | 6 | 1 | 0 | Yes |
6 | LAUNDRY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 14.33 | 1.98 | 1 | 1 | 1 | 81.99 | 86.56 | 5.79 | 22.86 | 0.00 | 3.96 | 3.96 | 309.22 | TARP | DOE-2 | 78.04 | 85.75 | 83.80 | 0.00 | 6 | 1 | 0 | Yes |
7 | CAFE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 70.26 | 2.90 | 1.98 | 1 | 1 | 1 | 53.95 | 86.56 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 748.35 | TARP | DOE-2 | 188.86 | 152.17 | 84.72 | 65.50 | 7 | 2 | 0 | Yes |
8 | LOBBY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 38.29 | 12.45 | 1.98 | 1 | 1 | 1 | 0.00 | 81.99 | 0.00 | 22.86 | 0.00 | 3.96 | 3.96 | 5183.56 | TARP | DOE-2 | 1308.19 | 434.79 | 345.80 | 85.08 | 18 | 3 | 0 | Yes |
9 | ROOM_1_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
10 | ROOM_2_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
11 | ROOM_3_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 8.53 | 9.14 | 8.53 | 1 | 76 | 1 | 6.71 | 10.36 | 5.79 | 12.50 | 7.01 | 10.06 | 3.05 | 74.75 | TARP | DOE-2 | 24.52 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
12 | ROOM_4_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 12.19 | 19.51 | 8.53 | 1 | 76 | 1 | 10.36 | 14.02 | 16.15 | 22.86 | 7.01 | 10.06 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
13 | ROOM_5_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 10.06 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
14 | ROOM_6_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 18.59 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
15 | CORRIDOR_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 43.28 | 14.33 | 8.53 | 1 | 4 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 7.01 | 10.06 | 3.05 | 1186.91 | TARP | DOE-2 | 389.40 | 48.31 | 32.37 | 15.94 | 20 | 4 | 0 | Yes |
16 | ROOM_1_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 16.15 | 19.20 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
17 | ROOM_2_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 16.15 | 19.20 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
18 | ROOM_3_MULT9_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 7.93 | 7.62 | 17.68 | 1 | 9 | 1 | 4.57 | 11.28 | 5.79 | 9.45 | 16.15 | 19.20 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 20.44 | 13.70 | 6.74 | 6 | 1 | 0 | Yes |
19 | BANQUET_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 26.37 | 17.68 | 17.68 | 1 | 1 | 1 | 10.36 | 42.37 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.36 | 32.19 | 6 | 1 | 0 | Yes |
20 | DINING_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 63.55 | 17.68 | 17.68 | 1 | 1 | 1 | 47.55 | 79.55 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.36 | 32.19 | 6 | 1 | 0 | Yes |
21 | KITCHEN_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 82.99 | 14.11 | 17.68 | 1 | 1 | 1 | 79.55 | 86.56 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 314.87 | TARP | DOE-2 | 103.30 | 87.33 | 60.96 | 26.37 | 8 | 3 | 0 | Yes |
22 | CORRIDOR_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 41.51 | 13.35 | 17.68 | 1 | 1 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 1256.16 | TARP | DOE-2 | 412.12 | 85.47 | 57.27 | 28.20 | 15 | 3 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 1978.83 | 106.5 | 18.581 | 5.382E-002 | 8.749 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 14.129 | No |
2 | RETAIL_1_FLR_1 | 67.07 | 10.8 | 6.194 | 0.161 | 13.012 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 23.772 | No |
3 | RETAIL_2_FLR_1 | 77.67 | 12.5 | 6.194 | 0.161 | 13.012 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 23.772 | No |
4 | MECH_FLR_1 | 164.24 | 2.7 | 61.932 | 1.615E-002 | 10.064 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 15.444 | No |
5 | STORAGE_FLR_1 | 94.76 | 2.0 | 46.451 | 2.153E-002 | 7.319 | 2.690 | 0.000 | 0.000 | 0.000 | 0.000 | 10.009 | No |
6 | LAUNDRY_FLR_1 | 78.04 | 8.4 | 9.290 | 0.108 | 5.490 | 61.680 | 535.850 | 0.000 | 0.000 | 0.000 | 603.020 | No |
7 | CAFE_FLR_1 | 188.86 | 142.3 | 1.327 | 0.753 | 12.809 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 18.189 | No |
8 | LOBBY_FLR_1 | 1308.19 | 422.4 | 3.097 | 0.323 | 10.064 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.134 | No |
9 | ROOM_1_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 10.064 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 16.814 | No |
10 | ROOM_2_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 10.064 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 16.814 | No |
11 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 16.349 | 6.116E-002 | 10.064 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 20.584 | No |
12 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 10.064 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 20.584 | No |
13 | ROOM_5_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 10.064 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 16.814 | No |
14 | ROOM_6_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 10.064 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 16.814 | No |
15 | CORRIDOR_FLR_3 | 389.40 | 21.0 | 18.581 | 5.382E-002 | 3.660 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 3.660 | No |
16 | ROOM_1_FLR_6 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 10.064 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 16.814 | No |
17 | ROOM_2_FLR_6 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 10.064 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 16.814 | No |
18 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 10.064 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 20.584 | No |
19 | BANQUET_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 12.809 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 80.629 | No |
20 | DINING_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 12.809 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 80.629 | No |
21 | KITCHEN_FLR_6 | 103.30 | 22.2 | 4.645 | 0.215 | 10.979 | 517.156 | 2419.260 | 0.000 | 0.000 | 0.000 | 2947.395 | No |
22 | CORRIDOR_FLR_6 | 412.12 | 22.2 | 18.581 | 5.382E-002 | 3.660 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 3.660 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | BASEMENT PEOPLE | BLDG_OCC_SCH | BASEMENT | 1978.83 | 106.5 | 106.5 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 106 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | RETAIL_1_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 10.8 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | RETAIL_2_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 12.5 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 13 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | LAUNDRY_FLR_1 PEOPLE | BLDG_OCC_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 8.4 | 0.108 | 9.290 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 8 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | CAFE_FLR_1 PEOPLE | BLDG_OCC_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 142.3 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 142 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | LOBBY_FLR_1 PEOPLE | BLDG_OCC_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 422.4 | 0.323 | 3.097 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 422 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | ROOM_1_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | ROOM_2_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | ROOM_3_MULT19_FLR_3 PEOPLE | ALWAYS_OFF | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 1.5 | 6.116E-002 | 16.349 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 0 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | ROOM_4_MULT19_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | ROOM_5_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | ROOM_6_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | ROOM_1_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | ROOM_2_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | ROOM_3_MULT9_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | BANQUET_FLR_6 PEOPLE | BLDG_OCC_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | DINING_FLR_6 PEOPLE | BLDG_OCC_SCH | DINING_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | KITCHEN_FLR_6 PEOPLE | BLDG_OCC_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 22.2 | 0.215 | 4.645 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | STORAGE_FLR_1 PEOPLE | BLDG_OCC_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 2.0 | 2.153E-002 | 46.451 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | CORRIDOR_FLR_3 PEOPLE | BLDG_OCC_SCH | CORRIDOR_FLR_3 | 389.40 | 21.0 | 21.0 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 21 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
21 | CORRIDOR_FLR_6 PEOPLE | BLDG_OCC_SCH | CORRIDOR_FLR_6 | 412.12 | 22.2 | 22.2 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
22 | MECH_FLR_1 PEOPLE | BLDG_OCC_SCH | MECH_FLR_1 | 164.24 | 2.7 | 2.7 | 1.615E-002 | 61.932 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 3 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_BASEMENT | BASEMENT | 1978.83 | 106.5 | 17313.725 | 8.749 | 162.572 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 17313.725 |
2 | RETAIL_1_FLR_1_LIGHTS | LTG_SCH_RETAIL | RETAIL_1_FLR_1 | 67.07 | 10.8 | 872.757 | 13.012 | 80.594 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 872.757 |
3 | RETAIL_2_FLR_1_LIGHTS | LTG_SCH_RETAIL | RETAIL_2_FLR_1 | 77.67 | 12.5 | 1010.656 | 13.012 | 80.595 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1010.656 |
4 | MECH_FLR_1_LIGHTS | LTG_SCH_MECHANIC | MECH_FLR_1 | 164.24 | 2.7 | 1652.984 | 10.064 | 623.297 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1652.984 |
5 | STORAGE_FLR_1_LIGHTS | LTG_SCH_STORAGE | STORAGE_FLR_1 | 94.76 | 2.0 | 693.586 | 7.319 | 339.993 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 693.586 |
6 | LAUNDRY_FLR_1_LIGHTS | LTG_SCH_LAUNDRY | LAUNDRY_FLR_1 | 78.04 | 8.4 | 428.405 | 5.490 | 51.001 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 428.405 |
7 | CAFE_FLR_1_LIGHTS | LTG_SCH_DINING | CAFE_FLR_1 | 188.86 | 142.3 | 2419.140 | 12.809 | 17.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2419.140 |
8 | LOBBY_FLR_1_LIGHTS | LTG_SCH_LOBBY | LOBBY_FLR_1 | 1308.19 | 422.4 | 13165.908 | 10.064 | 31.167 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 13165.908 |
9 | ROOM_1_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_1_FLR_3 | 39.02 | 1.5 | 392.727 | 10.064 | 261.818 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 392.727 |
10 | ROOM_2_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_2_FLR_3 | 39.02 | 1.5 | 392.681 | 10.064 | 261.787 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 392.681 |
11 | ROOM_3_MULT19_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 246.814 | 10.064 | 164.543 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 246.814 |
12 | ROOM_4_MULT19_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 246.881 | 10.064 | 164.588 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 246.881 |
13 | ROOM_5_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_5_FLR_3 | 39.02 | 1.5 | 392.727 | 10.064 | 261.818 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 392.727 |
14 | ROOM_6_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_6_FLR_3 | 39.02 | 1.5 | 392.681 | 10.064 | 261.787 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 392.681 |
15 | CORRIDOR_FLR_3_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_FLR_3 | 389.40 | 21.0 | 1425.114 | 3.660 | 68.002 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1425.114 |
16 | ROOM_1_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_1_FLR_6 | 39.02 | 1.5 | 392.727 | 10.064 | 261.818 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 392.727 |
17 | ROOM_2_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_2_FLR_6 | 39.02 | 1.5 | 392.681 | 10.064 | 261.787 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 392.681 |
18 | ROOM_3_MULT9_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 246.881 | 10.064 | 164.588 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 246.881 |
19 | BANQUET_FLR_6_LIGHTS | LTG_SCH_DINING | BANQUET_FLR_6 | 331.66 | 249.9 | 4248.214 | 12.809 | 17.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 4248.214 |
20 | DINING_FLR_6_LIGHTS | LTG_SCH_DINING | DINING_FLR_6 | 331.66 | 249.9 | 4248.214 | 12.809 | 17.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 4248.214 |
21 | KITCHEN_FLR_6_LIGHTS | LTG_SCH_KITCHEN | KITCHEN_FLR_6 | 103.30 | 22.2 | 1134.198 | 10.979 | 51.003 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1134.198 |
22 | CORRIDOR_FLR_6_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_FLR_6 | 412.12 | 22.2 | 1508.264 | 3.660 | 68.001 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1508.264 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | BASEMENT_EQUIP_SCH | BASEMENT | 1978.83 | 106.5 | 10646.106 | 5.380 | 99.964 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10646.106 |
2 | RETAIL_1_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 721.688 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 721.688 |
3 | RETAIL_2_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 835.717 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 835.717 |
4 | MECH_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | MECH_FLR_1 | 164.24 | 2.7 | 883.628 | 5.380 | 333.193 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 883.628 |
5 | STORAGE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 254.902 | 2.690 | 124.952 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 254.902 |
6 | LAUNDRY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 4813.474 | 61.680 | 573.033 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 4813.474 |
7 | CAFE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 1016.077 | 5.380 | 7.140 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1016.077 |
8 | LOBBY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 10557.062 | 8.070 | 24.991 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10557.062 |
9 | ROOM_1_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_1_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
10 | ROOM_2_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_2_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
11 | ROOM_3_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 257.991 | 10.520 | 171.994 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 257.991 |
12 | ROOM_4_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
13 | ROOM_5_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_5_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
14 | ROOM_6_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_6_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
15 | ROOM_1_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_1_FLR_6 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
16 | ROOM_2_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_2_FLR_6 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
17 | ROOM_3_MULT9_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
18 | BANQUET_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
19 | DINING_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | DINING_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
20 | KITCHEN_FLR_6_MISCELEC_EQUIP | KITCHEN_ELEC_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 52482.799 | 508.040 | 2360.050 | 0.200 | 0.500 | 0.100 | 0.200 | Cooking | 0.000 | 15744.840 |
21 | KITCHEN_FLR_6_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 515.917 | 4.994 | 23.200 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 515.917 | 515.917 |
22 | KITCHEN_FLR_6_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 425.833 | 4.122 | 19.149 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 425.833 | 425.833 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LAUNDRY_FLR_1_MISCGAS_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 41817.449 | 535.850 | 4978.268 | 0.000 | 0.500 | 0.000 | 0.500 | Laundry | 0.000 | 41817.449 |
2 | KITCHEN_FLR_6_MISCGAS_EQUIP | KITCHEN_GAS_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 249920.353 | 2419.260 | 11238.437 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 74976.106 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.464 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | OVERHEAD DOOR_CON | 2 | 1 | 1 | 0.167 | 1.198 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
3 | INTERIORFURNISHINGS | 3 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 8 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 18 | 3 | 3 | 0.167 | 0.2832 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
6 | RES_ROOF | 19 | 3 | 3 | 0.167 | 0.2832 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
7 | NONRES_EXT_WALL_GRD | 21 | 3 | 9 | 0.167 | 1.214 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | NONRES_EXT_WALL_MID | 22 | 3 | 9 | 0.167 | 1.530 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | NONRES_EXT_WALL_TOP | 23 | 3 | 9 | 0.167 | 1.605 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | RES_EXT_WALL_MID | 25 | 3 | 9 | 0.167 | 1.530 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | RES_EXT_WALL_TOP | 26 | 3 | 9 | 0.167 | 1.605 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | NONRES_FLOOR | 30 | 3 | 7 | 0.167 | 0.4124 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
13 | NONRES_FLOOR_CEILING | 33 | 3 | 7 | 0.167 | 0.4124 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
14 | BASEMENT_FLOOR | 36 | 2 | 7 | 0.333 | 2.705 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
15 | BASEMENT_WALL_NORTH_CFACTOR | 39 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | BASEMENT_WALL_EAST_CFACTOR | 40 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | BASEMENT_WALL_SOUTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
18 | BASEMENT_WALL_WEST_CFACTOR | 42 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2887 |
2 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8346 |
3 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 3.472 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
10 | RES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 3.472 |
11 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
12 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
13 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.6561 |
14 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4862 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4557 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | RES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4862 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
25 | RES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4557 |
26 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
27 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.165 |
28 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
29 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
30 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
31 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
32 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.165 |
33 | M10 200MM CONCRETE BLOCK BASEMENT WALL | 0.2032 | 1.326 | 1842.000 | 912.000 | 0.1532 |
34 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
35 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
36 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
37 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
38 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
39 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
40 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
41 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
42 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.4637404 | 3.4637404 | 3.4637404 | |
3 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
4 | 0 | 1.1981135 | 1.1981135 | 1.1981135 | |
5 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
6 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
7 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
8 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
9 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
10 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
11 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
12 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
13 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
14 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
15 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
16 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
17 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
18 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
19 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
20 | 3 | -0.61927053E-06 | 0.12767249E-08 | -0.37968499E-05 | 0.16832131E-17 |
21 | 2 | 0.77611055 | 0.17315568E-02 | 1.0534842 | -0.72792597E-06 |
22 | 1 | -21.915918 | 0.11588205 | -6.3286394 | 0.20197014 |
23 | 0 | 21.365777 | 0.10835518 | 5.5011278 | |
24 | 3 | -0.61927053E-06 | 0.12767249E-08 | -0.37968499E-05 | 0.16832131E-17 |
25 | 2 | 0.77611055 | 0.17315568E-02 | 1.0534842 | -0.72792597E-06 |
26 | 1 | -21.915918 | 0.11588205 | -6.3286394 | 0.20197014 |
27 | 0 | 21.365777 | 0.10835518 | 5.5011278 | |
28 | 9 | 0.16334608E-14 | 0.44521285E-16 | -0.13626018E-09 | -0.55408550E-17 |
29 | 8 | 0.19978482E-07 | 0.16087698E-12 | 0.35757339E-03 | -0.22716220E-09 |
30 | 7 | -0.11637212E-01 | 0.85329953E-08 | -0.22215339E-01 | 0.13231934E-03 |
31 | 6 | 0.38892783 | 0.29989280E-05 | 0.45807963 | -0.45541807E-02 |
32 | 5 | -5.0302817 | 0.11296145E-03 | -4.3335362 | 0.61196441E-01 |
33 | 4 | 32.293780 | 0.93138689E-03 | 21.019023 | -0.41270848 |
34 | 3 | -109.71729 | 0.20442050E-02 | -54.790969 | 1.4933949 |
35 | 2 | 195.63536 | 0.11570803E-02 | 77.111252 | -2.8769641 |
36 | 1 | -170.61189 | 0.12423857E-03 | -55.033492 | 2.7359019 |
37 | 0 | 57.057407 | 0.71170334E-06 | 15.595873 | |
38 | 9 | 0.10594392E-14 | 0.47202510E-16 | -0.12114953E-09 | -0.13223917E-17 |
39 | 8 | 0.17843092E-07 | 0.19779160E-12 | 0.33399960E-03 | -0.20288210E-09 |
40 | 7 | -0.10929829E-01 | 0.10778020E-07 | -0.21195485E-01 | 0.12427612E-03 |
41 | 6 | 0.36970129 | 0.38290923E-05 | 0.44160549 | -0.43275484E-02 |
42 | 5 | -4.8425837 | 0.14557296E-03 | -4.2065674 | 0.58869135E-01 |
43 | 4 | 31.463113 | 0.12102446E-02 | 20.521745 | -0.40168017 |
44 | 3 | -107.94871 | 0.26756904E-02 | -53.807411 | 1.4678460 |
45 | 2 | 193.88106 | 0.15243179E-02 | 76.211002 | -2.8491083 |
46 | 1 | -169.96333 | 0.16464538E-03 | -54.775095 | 2.7245352 |
47 | 0 | 57.057407 | 0.94931294E-06 | 15.641308 | |
48 | 9 | 0.90003388E-15 | 0.50867187E-16 | -0.11754631E-09 | -0.30069304E-17 |
49 | 8 | 0.17333232E-07 | 0.20603527E-12 | 0.32823068E-03 | -0.19708482E-09 |
50 | 7 | -0.10756240E-01 | 0.11305735E-07 | -0.20945040E-01 | 0.12230235E-03 |
51 | 6 | 0.36498247 | 0.40277709E-05 | 0.43754979 | -0.42719257E-02 |
52 | 5 | -4.7965079 | 0.15349109E-03 | -4.1752560 | 0.58297839E-01 |
53 | 4 | 31.259149 | 0.12787761E-02 | 20.398993 | -0.39897233 |
54 | 3 | -107.51430 | 0.28324589E-02 | -53.564574 | 1.4615707 |
55 | 2 | 193.44998 | 0.16162686E-02 | 75.988960 | -2.8422636 |
56 | 1 | -169.80390 | 0.17483991E-03 | -54.711782 | 2.7217408 |
57 | 0 | 57.057407 | 0.10098010E-05 | 15.652787 | |
58 | 9 | 0.10594392E-14 | 0.47202510E-16 | -0.12114953E-09 | -0.13223917E-17 |
59 | 8 | 0.17843092E-07 | 0.19779160E-12 | 0.33399960E-03 | -0.20288210E-09 |
60 | 7 | -0.10929829E-01 | 0.10778020E-07 | -0.21195485E-01 | 0.12427612E-03 |
61 | 6 | 0.36970129 | 0.38290923E-05 | 0.44160549 | -0.43275484E-02 |
62 | 5 | -4.8425837 | 0.14557296E-03 | -4.2065674 | 0.58869135E-01 |
63 | 4 | 31.463113 | 0.12102446E-02 | 20.521745 | -0.40168017 |
64 | 3 | -107.94871 | 0.26756904E-02 | -53.807411 | 1.4678460 |
65 | 2 | 193.88106 | 0.15243179E-02 | 76.211002 | -2.8491083 |
66 | 1 | -169.96333 | 0.16464538E-03 | -54.775095 | 2.7245352 |
67 | 0 | 57.057407 | 0.94931294E-06 | 15.641308 | |
68 | 9 | 0.90003388E-15 | 0.50867187E-16 | -0.11754631E-09 | -0.30069304E-17 |
69 | 8 | 0.17333232E-07 | 0.20603527E-12 | 0.32823068E-03 | -0.19708482E-09 |
70 | 7 | -0.10756240E-01 | 0.11305735E-07 | -0.20945040E-01 | 0.12230235E-03 |
71 | 6 | 0.36498247 | 0.40277709E-05 | 0.43754979 | -0.42719257E-02 |
72 | 5 | -4.7965079 | 0.15349109E-03 | -4.1752560 | 0.58297839E-01 |
73 | 4 | 31.259149 | 0.12787761E-02 | 20.398993 | -0.39897233 |
74 | 3 | -107.51430 | 0.28324589E-02 | -53.564574 | 1.4615707 |
75 | 2 | 193.44998 | 0.16162686E-02 | 75.988960 | -2.8422636 |
76 | 1 | -169.80390 | 0.17483991E-03 | -54.711782 | 2.7217408 |
77 | 0 | 57.057407 | 0.10098010E-05 | 15.652787 | |
78 | 7 | -0.10696287E-14 | 0.39031946E-16 | -0.22096194E-13 | 0.53014468E-15 |
79 | 6 | 0.18597363E-10 | 0.52355087E-11 | 0.51921923E-09 | -0.18483703E-10 |
80 | 5 | -0.10208356E-06 | 0.25520809E-07 | -0.21786771E-05 | 0.17041956E-06 |
81 | 4 | 0.13587196E-03 | 0.96408156E-05 | 0.17589348E-02 | -0.28090751E-03 |
82 | 3 | -0.20124247E-01 | 0.34048350E-03 | -0.21477792 | 0.43172268E-01 |
83 | 2 | 0.28586126 | 0.14813331E-02 | 2.8938873 | -0.61762740 |
84 | 1 | -0.72340799 | 0.92453067E-03 | -7.1302655 | 1.5680075 |
85 | 0 | 0.46030979 | 0.18706506E-04 | 4.4521723 | |
86 | 7 | -0.22096194E-13 | 0.39031946E-16 | -0.10696287E-14 | 0.53014468E-15 |
87 | 6 | 0.51921923E-09 | 0.52355087E-11 | 0.18597363E-10 | -0.18483703E-10 |
88 | 5 | -0.21786771E-05 | 0.25520809E-07 | -0.10208356E-06 | 0.17041956E-06 |
89 | 4 | 0.17589348E-02 | 0.96408156E-05 | 0.13587196E-03 | -0.28090751E-03 |
90 | 3 | -0.21477792 | 0.34048350E-03 | -0.20124247E-01 | 0.43172268E-01 |
91 | 2 | 2.8938873 | 0.14813331E-02 | 0.28586126 | -0.61762740 |
92 | 1 | -7.1302655 | 0.92453067E-03 | -0.72340799 | 1.5680075 |
93 | 0 | 4.4521723 | 0.18706506E-04 | 0.46030979 | |
94 | 7 | -0.52459208E-15 | -0.63961428E-15 | -0.12292524E-09 | -0.35846135E-17 |
95 | 6 | 0.39860198E-02 | 0.96339020E-07 | 0.40499006E-03 | -0.70890431E-04 |
96 | 5 | -0.20832379 | 0.49172556E-04 | -0.20585669E-01 | 0.38489246E-02 |
97 | 4 | 3.5198270 | 0.18993977E-02 | 0.34924834 | -0.69168259E-01 |
98 | 3 | -23.366787 | 0.13311857E-01 | -2.4329538 | 0.50524779 |
99 | 2 | 64.890127 | 0.19943872E-01 | 7.3672511 | -1.5911358 |
100 | 1 | -76.040094 | 0.56792084E-02 | -9.5568013 | 2.1361271 |
101 | 0 | 31.242244 | 0.96490710E-04 | 4.3344156 | |
102 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
103 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
104 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
105 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
106 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
107 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
108 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
109 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
110 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
111 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
112 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
113 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
114 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
115 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
116 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
117 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
118 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
119 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
120 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
121 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
122 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
123 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
124 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
125 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
126 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
127 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
128 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
129 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
130 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
131 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
132 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
133 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.5119_SHGC_0.25 | 37 | 1 | VerySmooth | 2.910 | 2.910 | 1.000 | 0.251 | ||
2 | RESWINDOW_U_0.5119_SHGC_0.25 | 38 | 1 | VerySmooth | 2.910 | 2.910 | 1.000 | 0.251 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER | SpectralAverage | 1.79780E-002 | 0.16139 | 0.60964 | 0.60964 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.10364 | 1.00000 | No | |
2 | RESIDENTIAL WINDOW GLAZING LAYER | SpectralAverage | 1.79780E-002 | 0.16139 | 0.60964 | 0.60964 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.10364 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 7 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 1.500 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 3.000 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWH BOOSTER E WATER HEATER | 2.2712E-002 | 8000.0 | 1.240 | 1.1473 |
2 | WaterHeater:Mixed | SWH LAUNDRY G WATER HEATER | 1.1356 | 163316.0 | 0.576 | 0.5074 |
3 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 2.2712 | 175842.6 | 0.260 | 2.5713E-002 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
6 | BASEMENT_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
7 | BASEMENT_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
8 | BASEMENT_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
9 | BASEMENT_CEILING_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
10 | BASEMENT_CEILING_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
11 | BASEMENT_CEILING_6 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
12 | BASEMENT_CEILING_7 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
13 | BASEMENT_CEILING_8 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
14 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
15 | RETAIL_1_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 4 | No | No |
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 1 | No | No |
17 | RETAIL_1_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 3 | No | No |
18 | RETAIL_1_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
19 | RETAIL_1_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
20 | RETAIL_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
21 | RETAIL_1_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
23 | RETAIL_2_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
25 | RETAIL_2_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
26 | RETAIL_2_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
27 | RETAIL_2_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
28 | RETAIL_2_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
29 | RETAIL_2_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
31 | MECH_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
32 | MECH_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
33 | MECH_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
34 | MECH_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
35 | MECH_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
36 | MECH_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
37 | MECH_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
38 | STORAGE_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
40 | STORAGE_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
41 | STORAGE_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
42 | STORAGE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
43 | STORAGE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
44 | STORAGE_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
45 | STORAGE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
46 | LAUNDRY_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
47 | LAUNDRY_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
49 | LAUNDRY_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
50 | LAUNDRY_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
51 | LAUNDRY_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
52 | LAUNDRY_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
54 | CAFE_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 3 | No | No |
55 | CAFE_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
56 | CAFE_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 4 | No | No |
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 1 | No | No |
58 | CAFE_FLR_1_WALL_1_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
59 | CAFE_FLR_1_WALL_2_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
60 | CAFE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
61 | CAFE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
62 | CAFE_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
63 | CAFE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
64 | LOBBY_FLR_1_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
67 | LOBBY_FLR_1_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
68 | LOBBY_FLR_1_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 1 | No | No |
70 | LOBBY_FLR_1_WALL_1_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
71 | LOBBY_FLR_1_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
72 | LOBBY_FLR_1_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
73 | LOBBY_FLR_1_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
74 | LOBBY_FLR_1_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
75 | LOBBY_FLR_1_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
76 | LOBBY_FLR_1_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
77 | LOBBY_FLR_1_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
78 | LOBBY_FLR_1_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
79 | LOBBY_FLR_1_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
80 | LOBBY_FLR_1_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
81 | LOBBY_FLR_1_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
82 | LOBBY_FLR_1_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
83 | LOBBY_FLR_1_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
84 | LOBBY_FLR_1_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
85 | LOBBY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
86 | ROOM_1_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
88 | ROOM_1_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
90 | ROOM_1_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
91 | ROOM_1_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
92 | ROOM_1_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
93 | ROOM_1_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
94 | ROOM_1_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
95 | ROOM_2_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
97 | ROOM_2_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
99 | ROOM_2_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
100 | ROOM_2_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
101 | ROOM_2_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
102 | ROOM_2_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
103 | ROOM_2_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
109 | ROOM_3_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
110 | ROOM_3_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
117 | ROOM_4_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
118 | ROOM_4_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
120 | ROOM_5_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
122 | ROOM_5_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
124 | ROOM_5_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
125 | ROOM_5_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
126 | ROOM_5_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
127 | ROOM_5_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
128 | ROOM_5_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
129 | ROOM_6_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
131 | ROOM_6_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
133 | ROOM_6_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
134 | ROOM_6_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
135 | ROOM_6_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
136 | ROOM_6_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
137 | ROOM_6_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
138 | CORRIDOR_FLR_3_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
147 | CORRIDOR_FLR_3_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
148 | CORRIDOR_FLR_3_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
149 | CORRIDOR_FLR_3_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
150 | CORRIDOR_FLR_3_WALL_4_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
152 | CORRIDOR_FLR_3_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
153 | CORRIDOR_FLR_3_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
154 | CORRIDOR_FLR_3_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
155 | CORRIDOR_FLR_3_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
156 | CORRIDOR_FLR_3_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
157 | CORRIDOR_FLR_3_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
158 | CORRIDOR_FLR_3_FLOOR_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
159 | CORRIDOR_FLR_3_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
160 | CORRIDOR_FLR_3_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
161 | CORRIDOR_FLR_3_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
163 | ROOM_1_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
165 | ROOM_1_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
167 | ROOM_1_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
168 | ROOM_1_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
169 | ROOM_1_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
170 | ROOM_1_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
171 | ROOM_1_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
172 | ROOM_2_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
174 | ROOM_2_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
176 | ROOM_2_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
177 | ROOM_2_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
178 | ROOM_2_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
179 | ROOM_2_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
180 | ROOM_2_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 3 | No | No |
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 2 | No | No |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
186 | ROOM_3_MULT9_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
187 | ROOM_3_MULT9_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
189 | BANQUET_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
191 | BANQUET_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
192 | BANQUET_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
193 | BANQUET_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
194 | BANQUET_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
195 | BANQUET_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
196 | BANQUET_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
197 | DINING_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
198 | DINING_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
199 | DINING_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
200 | DINING_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
201 | DINING_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
202 | DINING_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
203 | DINING_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
204 | DINING_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
205 | KITCHEN_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
207 | KITCHEN_FLR_6_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
212 | KITCHEN_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
213 | KITCHEN_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
214 | KITCHEN_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
215 | KITCHEN_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
216 | KITCHEN_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
217 | CORRIDOR_FLR_6_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
224 | CORRIDOR_FLR_6_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
226 | CORRIDOR_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
227 | CORRIDOR_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
228 | CORRIDOR_FLR_6_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
229 | CORRIDOR_FLR_6_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
230 | CORRIDOR_FLR_6_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
231 | CORRIDOR_FLR_6_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
232 | CORRIDOR_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
233 | CORRIDOR_FLR_6_CEILING_1 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
234 | CORRIDOR_FLR_6_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | RETAIL_1_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 7.058E-002 | 1.052E-003 | 5.193E-004 | 0.956 | 1.000 | 0.000 | 0.000 | 0.000 |
2 | RETAIL_2_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 2.724E-002 | 3.507E-004 | 9.551E-004 | 0.319 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | MECH_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | MECH_FLR_1 | 164.24 | 2.7 | 6.438E-002 | 3.920E-004 | 1.025E-003 | 0.356 | 1.000 | 0.000 | 0.000 | 0.000 |
4 | STORAGE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 3.715E-002 | 3.920E-004 | 8.507E-004 | 0.356 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | LAUNDRY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 8.791E-002 | 1.127E-003 | 1.002E-003 | 1.023 | 1.000 | 0.000 | 0.000 | 0.000 |
6 | CAFE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 0.156 | 8.261E-004 | 4.549E-004 | 0.751 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | LOBBY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 0.446 | 3.407E-004 | 6.517E-004 | 0.310 | 1.000 | 0.000 | 0.000 | 0.000 |
8 | ROOM_1_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 4.096E-002 | 1.050E-003 | 1.025E-003 | 1.240 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | ROOM_2_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 4.095E-002 | 1.050E-003 | 1.025E-003 | 1.240 | 1.000 | 0.000 | 0.000 | 0.000 |
10 | ROOM_3_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 1.143E-002 | 4.660E-004 | 1.025E-003 | 0.550 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | ROOM_4_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 1.143E-002 | 4.660E-004 | 1.025E-003 | 0.550 | 1.000 | 0.000 | 0.000 | 0.000 |
12 | ROOM_5_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 4.096E-002 | 1.050E-003 | 1.025E-003 | 1.240 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | ROOM_6_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 4.095E-002 | 1.050E-003 | 1.025E-003 | 1.240 | 1.000 | 0.000 | 0.000 | 0.000 |
14 | CORRIDOR_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_3 | 389.40 | 21.0 | 4.953E-002 | 1.272E-004 | 1.025E-003 | 0.150 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | ROOM_1_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 4.096E-002 | 1.050E-003 | 5.186E-004 | 1.240 | 1.000 | 0.000 | 0.000 | 0.000 |
16 | ROOM_2_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 4.095E-002 | 1.050E-003 | 5.186E-004 | 1.240 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | ROOM_3_MULT9_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 2.096E-002 | 8.543E-004 | 4.660E-004 | 1.009 | 1.000 | 0.000 | 0.000 | 0.000 |
18 | BANQUET_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 0.100 | 3.015E-004 | 2.330E-004 | 0.356 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | DINING_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | DINING_FLR_6 | 331.66 | 249.9 | 0.100 | 3.015E-004 | 2.330E-004 | 0.356 | 1.000 | 0.000 | 0.000 | 0.000 |
20 | KITCHEN_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 8.953E-002 | 8.667E-004 | 4.697E-004 | 1.024 | 1.000 | 0.000 | 0.000 | 0.000 |
21 | CORRIDOR_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_6 | 412.12 | 22.2 | 8.763E-002 | 2.126E-004 | 1.761E-004 | 0.251 | 1.000 | 0.000 | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | ROOM_1_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
2 | ROOM_2_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
3 | ROOM_3_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
4 | ROOM_4_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
5 | ROOM_5_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_5_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
6 | ROOM_6_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_6_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
7 | ROOM_1_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
8 | ROOM_2_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
9 | ROOM_3_MULT9_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | RETAIL_1_FLR_1 | Mixing/Well-Stirred |
3 | RETAIL_2_FLR_1 | Mixing/Well-Stirred |
4 | MECH_FLR_1 | Mixing/Well-Stirred |
5 | STORAGE_FLR_1 | Mixing/Well-Stirred |
6 | LAUNDRY_FLR_1 | Mixing/Well-Stirred |
7 | CAFE_FLR_1 | Mixing/Well-Stirred |
8 | LOBBY_FLR_1 | Mixing/Well-Stirred |
9 | ROOM_1_FLR_3 | Mixing/Well-Stirred |
10 | ROOM_2_FLR_3 | Mixing/Well-Stirred |
11 | ROOM_3_MULT19_FLR_3 | Mixing/Well-Stirred |
12 | ROOM_4_MULT19_FLR_3 | Mixing/Well-Stirred |
13 | ROOM_5_FLR_3 | Mixing/Well-Stirred |
14 | ROOM_6_FLR_3 | Mixing/Well-Stirred |
15 | CORRIDOR_FLR_3 | Mixing/Well-Stirred |
16 | ROOM_1_FLR_6 | Mixing/Well-Stirred |
17 | ROOM_2_FLR_6 | Mixing/Well-Stirred |
18 | ROOM_3_MULT9_FLR_6 | Mixing/Well-Stirred |
19 | BANQUET_FLR_6 | Mixing/Well-Stirred |
20 | DINING_FLR_6 | Mixing/Well-Stirred |
21 | KITCHEN_FLR_6 | Mixing/Well-Stirred |
22 | CORRIDOR_FLR_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 39892.39039 | 39892.39039 | 2.89984 | 2.89984 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 20:20:00 | 37.65900 | 1.07730E-002 | 1978.83018 | 106.49900 | 0.85446 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 0.85446 | 00:10:00 | 12.70000 | 9.15345E-003 | 1978.83018 | 106.49900 | 0.85446 | 0.00000 | |
3 | RETAIL_1_FLR_1 | Cooling | 5531.90243 | 5531.90243 | 0.40217 | 0.40217 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 42.80000 | 1.07818E-002 | 67.07136 | 10.82900 | 7.92179E-002 | 0.00000 |
4 | RETAIL_1_FLR_1 | Heating | 1116.62595 | 1116.62595 | 4.78856E-002 | 7.92179E-002 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | 12.70000 | 9.15345E-003 | 67.07136 | 10.82900 | 7.92179E-002 | 0.00000 |
5 | RETAIL_2_FLR_1 | Cooling | 3645.00364 | 3645.00364 | 0.26499 | 0.26499 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:50:00 | 41.57133 | 1.07797E-002 | 77.66889 | 12.54000 | 9.17347E-002 | 0.00000 |
6 | RETAIL_2_FLR_1 | Heating | 337.01095 | 337.01095 | 1.44523E-002 | 9.17347E-002 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | 12.70000 | 9.15345E-003 | 77.66889 | 12.54000 | 9.17347E-002 | 0.00000 |
7 | MECH_FLR_1 | Cooling | 4200.25951 | 4200.25951 | 0.30530 | 0.30530 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | 40.47200 | 1.07778E-002 | 164.24319 | 2.65200 | 0.00000 | 0.00000 |
8 | MECH_FLR_1 | Heating | 598.86583 | 598.86583 | 2.56816E-002 | 2.56816E-002 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | 12.70000 | 9.15345E-003 | 164.24319 | 2.65200 | 0.00000 | 0.00000 |
9 | STORAGE_FLR_1 | Cooling | 2141.71421 | 2141.71421 | 0.15567 | 0.15567 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:00:00 | 42.21800 | 1.07808E-002 | 94.75927 | 2.04000 | 5.77652E-002 | 0.00000 |
10 | STORAGE_FLR_1 | Heating | 352.75187 | 352.75187 | 1.51273E-002 | 5.77652E-002 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | 12.70000 | 9.15345E-003 | 94.75927 | 2.04000 | 5.77652E-002 | 0.00000 |
11 | LAUNDRY_FLR_1 | Cooling | 45664.20962 | 45664.20962 | 3.31950 | 3.31950 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:10:00 | 42.08867 | 1.07806E-002 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
12 | LAUNDRY_FLR_1 | Heating | 908.48914 | 908.48914 | 3.89598E-002 | 3.89598E-002 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | 12.70000 | 9.15345E-003 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
13 | CAFE_FLR_1 | Cooling | 21934.84648 | 21934.84648 | 1.59594 | 1.59594 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 42.80000 | 1.07818E-002 | 188.86188 | 142.30000 | 0.67639 | 0.00000 |
14 | CAFE_FLR_1 | Heating | 2801.16552 | 2801.16552 | 0.12013 | 0.67639 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | 12.70000 | 9.15345E-003 | 188.86188 | 142.30000 | 0.67639 | 0.00000 |
15 | LOBBY_FLR_1 | Cooling | 70276.10956 | 70276.10956 | 5.11047 | 5.11047 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:20:00 | 42.80000 | 1.07818E-002 | 1308.18612 | 422.43500 | 1.89399 | 0.00000 |
16 | LOBBY_FLR_1 | Heating | 5944.88523 | 5944.88523 | 0.25494 | 1.89399 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | 12.70000 | 9.15345E-003 | 1308.18612 | 422.43500 | 1.89399 | 0.00000 |
17 | ROOM_1_FLR_3 | Cooling | 12816.85266 | 12816.85266 | 1.25549 | 1.25549 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:10:00 | 42.08867 | 1.07806E-002 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
18 | ROOM_1_FLR_3 | Heating | 2586.63493 | 2586.63493 | 0.11158 | 0.11158 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | 12.70000 | 9.15345E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
19 | ROOM_2_FLR_3 | Cooling | 12597.97615 | 12597.97615 | 1.23405 | 1.23405 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:10:00 | 42.08867 | 1.07806E-002 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
20 | ROOM_2_FLR_3 | Heating | 2584.67656 | 2584.67656 | 0.11149 | 0.11149 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | 12.70000 | 9.15345E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
21 | ROOM_3_MULT19_FLR_3 | Cooling | 81507.71807 | 81507.71807 | 7.98366 | 7.98366 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:20:00 | 42.80000 | 1.07818E-002 | 24.52384 | 1.50000 | 0.83707 | 0.00000 |
22 | ROOM_3_MULT19_FLR_3 | Heating | 15172.27352 | 15172.27352 | 0.65447 | 0.83707 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | 12.70000 | 9.15345E-003 | 24.52384 | 1.50000 | 0.83707 | 0.00000 |
23 | ROOM_4_MULT19_FLR_3 | Cooling | 84784.51872 | 84784.51872 | 8.30523 | 8.30523 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 | 42.60600 | 1.07815E-002 | 24.53055 | 1.50000 | 0.83730 | 0.00000 |
24 | ROOM_4_MULT19_FLR_3 | Heating | 15149.15850 | 15149.15850 | 0.65347 | 0.83730 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | 12.70000 | 9.15345E-003 | 24.53055 | 1.50000 | 0.83730 | 0.00000 |
25 | ROOM_5_FLR_3 | Cooling | 11570.74219 | 11570.74219 | 1.13343 | 1.13343 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 10:50:00 | 40.32650 | 1.07776E-002 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
26 | ROOM_5_FLR_3 | Heating | 2590.19470 | 2590.19470 | 0.11173 | 0.11173 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | 12.70000 | 9.15345E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
27 | ROOM_6_FLR_3 | Cooling | 11362.98921 | 11362.98921 | 1.11308 | 1.11308 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 10:30:00 | 39.84150 | 1.07767E-002 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
28 | ROOM_6_FLR_3 | Heating | 2588.23377 | 2588.23377 | 0.11165 | 0.11165 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | 12.70000 | 9.15345E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
29 | CORRIDOR_FLR_3 | Cooling | 19311.63216 | 19311.63216 | 1.40377 | 1.40377 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 42.70300 | 1.07816E-002 | 389.40468 | 20.95700 | 0.47476 | 0.00000 |
30 | CORRIDOR_FLR_3 | Heating | 4112.82216 | 4112.82216 | 0.17637 | 0.47476 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 12.70000 | 9.15345E-003 | 389.40468 | 20.95700 | 0.47476 | 0.00000 |
31 | ROOM_1_FLR_6 | Cooling | 3499.56087 | 3499.56087 | 0.34280 | 0.34280 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:00:00 | 42.21800 | 1.07808E-002 | 39.02202 | 1.50000 | 1.54338E-002 | 0.00000 |
32 | ROOM_1_FLR_6 | Heating | 815.08335 | 815.08335 | 3.51597E-002 | 3.51597E-002 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | 12.70000 | 9.15345E-003 | 39.02202 | 1.50000 | 1.54338E-002 | 0.00000 |
33 | ROOM_2_FLR_6 | Cooling | 3442.09483 | 3442.09483 | 0.33718 | 0.33718 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:10:00 | 42.08867 | 1.07806E-002 | 39.01745 | 1.50000 | 1.54319E-002 | 0.00000 |
34 | ROOM_2_FLR_6 | Heating | 814.76375 | 814.76375 | 3.51459E-002 | 3.51459E-002 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | 12.70000 | 9.15345E-003 | 39.01745 | 1.50000 | 1.54319E-002 | 0.00000 |
35 | ROOM_3_MULT9_FLR_6 | Cooling | 16746.24312 | 16746.24312 | 1.64043 | 1.64043 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:20:00 | 42.80000 | 1.07818E-002 | 24.53055 | 1.50000 | 9.91540E-002 | 0.00000 |
36 | ROOM_3_MULT9_FLR_6 | Heating | 3967.83659 | 3967.83659 | 0.17116 | 0.17116 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | 12.70000 | 9.15345E-003 | 24.53055 | 1.50000 | 9.91540E-002 | 0.00000 |
37 | BANQUET_FLR_6 | Cooling | 32927.26252 | 32927.26252 | 2.39637 | 2.39637 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 42.80000 | 1.07818E-002 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
38 | BANQUET_FLR_6 | Heating | 2791.01653 | 2791.01653 | 0.11969 | 1.18780 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | 12.70000 | 9.15345E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
39 | DINING_FLR_6 | Cooling | 34451.11436 | 34451.11436 | 2.50724 | 2.50724 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 42.80000 | 1.07818E-002 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
40 | DINING_FLR_6 | Heating | 2687.30252 | 2687.30252 | 0.11524 | 1.18780 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 12.70000 | 9.15345E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
41 | KITCHEN_FLR_6 | Cooling | 32412.31258 | 32412.31258 | 2.36217 | 2.36217 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 12:30:00 | 41.92700 | 1.07803E-002 | 103.30446 | 22.23800 | 0.36735 | 0.00000 |
42 | KITCHEN_FLR_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.36735 | 00:10:00 | 12.70000 | 9.15345E-003 | 103.30446 | 22.23800 | 0.36735 | 0.00000 | |
43 | CORRIDOR_FLR_6 | Cooling | 11605.01373 | 11605.01373 | 0.84357 | 0.84357 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 42.80000 | 1.07818E-002 | 412.12471 | 22.18000 | 0.12562 | 0.00000 |
44 | CORRIDOR_FLR_6 | Heating | 2919.25376 | 2919.25376 | 0.12519 | 0.12562 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 12.70000 | 9.15345E-003 | 412.12471 | 22.18000 | 0.12562 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV WITH REHEAT | Cooling | Sensible | 851391.96 | 23.46513 | 23.46513 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
2 | VAV WITH REHEAT | Heating | Sensible | 34162.02 | 7.06152 | 7.06152 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 |
3 | FLR_3_DOAS | Cooling | Sensible | 74425.91 | 23.06752 | 2.05125 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
4 | FLR_3_DOAS | Heating | Sensible | 9923.45 | 2.36228 | 2.05125 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.89984 |
2 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.51998 |
3 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.99600 |
4 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.88824 |
5 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
6 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 7.32716E-004 |
8 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.33349E-004 |
9 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.88824 |
10 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
11 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
12 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 15242.61810 |
13 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.33349E-004 |
14 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 317.85852 |
15 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.40217 |
16 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12708 |
17 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.99600 |
18 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.40056 |
19 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.99600 |
20 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
21 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.99810E-003 |
22 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.82743E-005 |
23 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.40056 |
24 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
25 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
26 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 3231.92501 |
27 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.82743E-005 |
28 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 69.30139 |
29 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.26499 |
30 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.22334 |
31 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.99600 |
32 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.26393 |
33 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.99600 |
34 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
35 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.70592E-003 |
36 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.51425E-005 |
37 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.26393 |
38 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
40 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1730.88384 |
41 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.51425E-005 |
42 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 36.55482 |
43 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.30530 |
44 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.40994 |
45 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.99600 |
46 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.30408 |
47 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
48 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
49 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 9.29408E-004 |
50 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.92900E-005 |
51 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.30408 |
52 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
53 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
54 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 2204.96362 |
55 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.92900E-005 |
56 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 46.89148 |
57 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.15567 |
58 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.46384 |
59 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.99600 |
60 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.15505 |
61 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
62 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 8.21411E-004 |
64 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.02505E-005 |
65 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.15505 |
66 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
67 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
68 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1171.69950 |
69 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.02505E-005 |
70 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 24.99461 |
71 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 3.31950 |
72 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 7.10872E-002 |
73 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.99600 |
74 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 3.30622 |
75 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.99600 |
76 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
77 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.12681E-002 |
78 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.60720E-004 |
79 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 3.30622 |
80 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
81 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
82 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 18371.25901 |
83 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.60720E-004 |
84 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 384.15378 |
85 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.59594 |
86 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.01743E-002 |
87 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.99600 |
88 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.58956 |
89 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.99600 |
90 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
91 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.22515E-003 |
92 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.79368E-005 |
93 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.58956 |
94 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
96 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 11194.77345 |
97 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.79368E-005 |
98 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 237.57323 |
99 | Fan:ZoneExhaust | LOBBY_FLR_1 EXHAUST FAN | User-Specified Maximum Flow Rate [m3/s] | 0.00000 |
100 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.11047 |
101 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.19506 |
102 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.99600 |
103 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 5.09003 |
104 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.99600 |
105 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
106 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.95327E-003 |
107 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.87170E-004 |
108 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 5.09003 |
109 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
110 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
111 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 32825.24167 |
112 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.87170E-004 |
113 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 692.48827 |
114 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_1_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17350E-002 |
115 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.25549 |
116 | Fan:OnOff | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.25549 |
117 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 2.26292E-005 |
118 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 5.50567E-004 |
119 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 22.48821 |
120 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
121 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.62300E-003 |
122 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
123 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
124 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 5.50567E-004 |
125 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.25549 |
126 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 2586.65231 |
127 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.26292E-005 |
128 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 73.88468 |
129 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_2_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17278E-002 |
130 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.23405 |
131 | Fan:OnOff | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.23405 |
132 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 2.26120E-005 |
133 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 5.41426E-004 |
134 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 22.48820 |
135 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
136 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.62494E-003 |
137 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
138 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
139 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 5.41426E-004 |
140 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.23405 |
141 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 2584.69393 |
142 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.26120E-005 |
143 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 73.82873 |
144 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_3_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.83707 |
145 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 7.98366 |
146 | Fan:OnOff | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 7.98366 |
147 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.69768E-004 |
148 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.44215E-003 |
149 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 22.48894 |
150 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
151 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.55521E-003 |
152 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
153 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
154 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.44215E-003 |
155 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 7.98366 |
156 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 19405.55127 |
157 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.69768E-004 |
158 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 554.30308 |
159 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_4_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.83730 |
160 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 8.30523 |
161 | Fan:OnOff | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 8.30523 |
162 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.69815E-004 |
163 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.72892E-003 |
164 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 22.48793 |
165 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
166 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.71878E-003 |
167 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
168 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
169 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.72892E-003 |
170 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 8.30523 |
171 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 19410.85773 |
172 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.69815E-004 |
173 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 554.45453 |
174 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_5_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17350E-002 |
175 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.13343 |
176 | Fan:OnOff | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.13343 |
177 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 2.26603E-005 |
178 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 4.98714E-004 |
179 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 22.48816 |
180 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
181 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.63653E-003 |
182 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
183 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
184 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.98714E-004 |
185 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.13343 |
186 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 2590.21210 |
187 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.26603E-005 |
188 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 73.98637 |
189 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_6_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17278E-002 |
190 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.11308 |
191 | Fan:OnOff | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.11308 |
192 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 2.26432E-005 |
193 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 4.90044E-004 |
194 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 22.48816 |
195 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
196 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.63887E-003 |
197 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
198 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
199 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.90044E-004 |
200 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.11308 |
201 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 2588.25116 |
202 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.26432E-005 |
203 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 73.93036 |
204 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.40377 |
205 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.84551 |
206 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.99600 |
207 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.39816 |
208 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
209 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
210 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.50615E-004 |
211 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.00564E-004 |
212 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.39816 |
213 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
214 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
215 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 11495.12837 |
216 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.00564E-004 |
217 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 246.87178 |
218 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_1_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.54338E-002 |
219 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.34280 |
220 | Fan:OnOff | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.34280 |
221 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 7.13075E-006 |
222 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 1.49952E-004 |
223 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 22.48824 |
224 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
225 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.61294E-003 |
226 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
227 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
228 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.49952E-004 |
229 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.34280 |
230 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 815.08883 |
231 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.13075E-006 |
232 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 23.28274 |
233 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_2_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.54319E-002 |
234 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.33718 |
235 | Fan:OnOff | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.33718 |
236 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 7.12796E-006 |
237 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 1.47555E-004 |
238 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 22.48824 |
239 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
240 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.61471E-003 |
241 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
242 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
243 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.47555E-004 |
244 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.33718 |
245 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 814.76923 |
246 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.12796E-006 |
247 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 23.27361 |
248 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_3_MULT9_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 9.91540E-002 |
249 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.64043 |
250 | Fan:OnOff | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.64043 |
251 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 3.47126E-005 |
252 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 7.25509E-004 |
253 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 22.48800 |
254 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
255 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.65732E-003 |
256 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
257 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
258 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 7.25509E-004 |
259 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.64043 |
260 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 3967.85819 |
261 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.47126E-005 |
262 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 113.34120 |
263 | Fan:ZoneExhaust | BANQUET_FLR_6 EXHAUST FAN | User-Specified Maximum Flow Rate [m3/s] | 0.00000 |
264 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.39637 |
265 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10546 |
266 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.99600 |
267 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.38678 |
268 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.99600 |
269 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
270 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.61271E-003 |
271 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.34657E-004 |
272 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.38678 |
273 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
274 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
275 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 15392.13186 |
276 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.34657E-004 |
277 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 324.71561 |
278 | Fan:ZoneExhaust | DINING_FLR_6 EXHAUST FAN | User-Specified Maximum Flow Rate [m3/s] | 0.00000 |
279 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.50724 |
280 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10080 |
281 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.99600 |
282 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.49721 |
283 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.99600 |
284 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
285 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.77986E-003 |
286 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.38853E-004 |
287 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.49721 |
288 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
289 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
290 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 15871.77141 |
291 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.38853E-004 |
292 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 334.52407 |
293 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.36217 |
294 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.79918 |
295 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.99600 |
296 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.35272 |
297 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.99600 |
298 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
299 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.14330E-002 |
300 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.08624E-004 |
301 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.35272 |
302 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
303 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
304 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 12416.40340 |
305 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.08624E-004 |
306 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 258.92269 |
307 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.84357 |
308 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.37227 |
309 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.99600 |
310 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.84020 |
311 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.99600 |
312 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
313 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.02344E-003 |
314 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.43438E-005 |
315 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.84020 |
316 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
317 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
318 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 7354.89248 |
319 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.43438E-005 |
320 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 158.81653 |
321 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 23.47273 |
322 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 23.47273 |
323 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 23.56700 |
324 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 23.47273 |
325 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 23.47273 |
326 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 23.47273 |
327 | AirLoopHVAC | VAV WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
328 | AirLoopHVAC | VAV WITH REHEAT | Calculated Heating Air Flow Ratio [] | 1.00000 |
329 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.05132 |
330 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.05132 |
331 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.05132 |
332 | AirLoopHVAC | FLR_3_DOAS | Adjusted Heating Design Air Flow Rate [m3/s] | 2.05132 |
333 | AirLoopHVAC | FLR_3_DOAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.05132 |
334 | AirLoopHVAC | FLR_3_DOAS | Adjusted Main Design Air Flow Rate [m3/s] | 2.05132 |
335 | AirLoopHVAC | FLR_3_DOAS | User Heating Air Flow Ratio [] | 0.30000 |
336 | AirLoopHVAC | FLR_3_DOAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
337 | AirLoopHVAC | VAV WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 23.47273 |
338 | AirLoopHVAC | FLR_3_DOAS | Design Supply Air Flow Rate [m3/s] | 2.05132 |
339 | Controller:OutdoorAir | VAV WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 23.47273 |
340 | Controller:OutdoorAir | VAV WITH REHEAT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 23.46513 |
341 | HeatExchanger:AirToAir:SensibleAndLatent | VAV WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 23.46513 |
342 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 42.80000 |
343 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
344 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.98358 |
345 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.07818E-002 |
346 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
347 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 1083772.56116 |
348 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.87098E-002 |
349 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 23.47273 |
350 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 34066.70480 |
351 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.98030E-004 |
352 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 652.39799 |
353 | Fan:VariableVolume | VAV WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 23.47273 |
354 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 3.87098E-002 |
355 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.23015E-005 |
356 | Controller:WaterCoil | VAV WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.98030E-004 |
357 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.05132 |
358 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.05125 |
359 | HeatExchanger:AirToAir:SensibleAndLatent | FLR_3_DOAS OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.05125 |
360 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 42.80000 |
361 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
362 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.93254 |
363 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.07818E-002 |
364 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
365 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Coil Load [W] | 92321.21181 |
366 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.29750E-003 |
367 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 2.05132 |
368 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size Rated Capacity [W] | 2977.14093 |
369 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.60453E-005 |
370 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 57.01405 |
371 | Fan:ConstantVolume | FLR_3_DOAS FAN | User-Specified Maximum Flow Rate [m3/s] | 2.05125 |
372 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 3.29750E-003 |
373 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.44410E-004 |
374 | Controller:WaterCoil | FLR_3_DOAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.60453E-005 |
375 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 5.22822E-002 |
376 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 10773.41849 |
377 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 2.10235E-003 |
378 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 0.25228 |
379 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 2.10235E-003 |
380 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 633.13537 |
381 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
382 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 240311.47221 |
383 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 240311.47000 |
384 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 2.10235E-003 |
385 | PlantLoop | COOLSYS1 | Maximum Loop Flow Rate [m3/s] | 5.22822E-002 |
386 | PlantLoop | COOLSYS1 | Plant Loop Volume [m3] | 6.27386 |
387 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Flow Rate [m3/s] | 5.22822E-002 |
388 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Power Consumption [W] | 7458.80099 |
389 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 5.22822E-002 |
390 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 1463761.65824 |
391 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 1464401.58000 |
392 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 166.94178 |
393 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 3.75036E-004 |
394 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 4.50044E-002 |
395 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 3.75036E-004 |
396 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 47.90688 |
397 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 3.75036E-004 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | 15321.34 |
2 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 3248.18 |
3 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 1739.72 |
4 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | 2216.14 |
5 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | 1177.62 |
6 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 18465.89 |
7 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | 11251.63 |
8 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | 32992.91 |
9 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | 2785.30 |
10 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | 2783.19 |
11 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | 20895.95 |
12 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | 20901.66 |
13 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | 2789.13 |
14 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | 2787.02 |
15 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 11552.87 |
16 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | 877.70 |
17 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | 877.36 |
18 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | 4272.66 |
19 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | 15470.75 |
20 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | 15952.91 |
21 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | 12480.53 |
22 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 7391.66 |
23 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | 32263.52 |
24 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | 2819.56 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | 21957.96 | 17388.36 | 4569.59 | 0.79 | 2422.43 | 24.57 |
2 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | 21589.60 | 17094.74 | 4494.86 | 0.79 | 2381.74 | 24.16 |
3 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | 138128.95 | 109818.68 | 28310.27 | 0.80 | 15250.15 | 154.68 |
4 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | 147433.11 | 116116.64 | 31316.46 | 0.79 | 16249.85 | 164.81 |
5 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | 19865.47 | 15719.03 | 4146.44 | 0.79 | 2191.27 | 22.23 |
6 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | 19515.97 | 15440.40 | 4075.57 | 0.79 | 2152.67 | 21.83 |
7 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | 5985.93 | 4742.99 | 1242.94 | 0.79 | 660.45 | 6.70 |
8 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | 5889.29 | 4665.94 | 1223.35 | 0.79 | 649.77 | 6.59 |
9 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | 28845.15 | 22797.24 | 6047.91 | 0.79 | 3181.11 | 32.26 |
10 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | 739424.02 | 480727.82 | 258696.20 | 0.65 | 84057.47 | 852.56 |
11 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | 62973.74 | 41190.39 | 21783.35 | 0.65 | 6855.01 | 69.53 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | 3.72 | 12.68 |
Zone Name | # Surfaces | |
1 | BASEMENT | 14 |
2 | RETAIL_1_FLR_1 | 8 |
3 | RETAIL_2_FLR_1 | 8 |
4 | MECH_FLR_1 | 7 |
5 | STORAGE_FLR_1 | 8 |
6 | LAUNDRY_FLR_1 | 8 |
7 | CAFE_FLR_1 | 10 |
8 | LOBBY_FLR_1 | 22 |
9 | ROOM_1_FLR_3 | 9 |
10 | ROOM_2_FLR_3 | 9 |
11 | ROOM_3_MULT19_FLR_3 | 8 |
12 | ROOM_4_MULT19_FLR_3 | 8 |
13 | ROOM_5_FLR_3 | 9 |
14 | ROOM_6_FLR_3 | 9 |
15 | CORRIDOR_FLR_3 | 25 |
16 | ROOM_1_FLR_6 | 9 |
17 | ROOM_2_FLR_6 | 9 |
18 | ROOM_3_MULT9_FLR_6 | 8 |
19 | BANQUET_FLR_6 | 8 |
20 | DINING_FLR_6 | 8 |
21 | KITCHEN_FLR_6 | 12 |
22 | CORRIDOR_FLR_6 | 19 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.940 | 0.824 | 211.13 | 211.13 | 211.13 | 0.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.940 | 0.824 | 55.76 | 55.76 | 55.76 | 90.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.940 | 0.824 | 211.13 | 211.13 | 211.13 | 180.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_WEST_CFACTOR | 0.940 | 0.824 | 55.76 | 55.76 | 55.76 | 270.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | BASEMENT_FLOOR | 2.705 | 1.632 | 1978.83 | 1978.83 | 1978.83 | 0.00 | 180.00 | 86.56 | 22.86 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | BASEMENT_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.412 | 0.383 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | RETAIL_1_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | BASEMENT_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.412 | 0.383 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | BASEMENT_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.412 | 0.383 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | BASEMENT_CEILING_4 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.412 | 0.383 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_CEILING_5 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.412 | 0.383 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
11 | BASEMENT_CEILING_6 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.412 | 0.383 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | CAFE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
12 | BASEMENT_CEILING_7 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.412 | 0.383 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 0.00 | 32.99 | 32.99 | 0.00 | LOBBY_FLR_1_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
13 | BASEMENT_CEILING_8 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.412 | 0.383 | 219.63 | 219.63 | 219.63 | 90.00 | 0.00 | 14.82 | 14.82 | 0.00 | LOBBY_FLR_1_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
14 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 3957.66 | 3957.66 | 3957.66 | 0.00 | 90.00 | 3957.66 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
15 | RETAIL_1_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.214 | 1.028 | 22.63 | 45.89 | 22.63 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | Window | RETAIL_1_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5119_SHGC_0.25 | N/A | 2.910 | No | 23.26 | 23.26 | 23.26 | 180.00 | 90.00 | 10.92 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
17 | RETAIL_1_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.214 | 1.028 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
18 | RETAIL_1_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | RETAIL_1_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | RETAIL_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.412 | 0.375 | 67.07 | 67.07 | 67.07 | 0.00 | 180.00 | 11.58 | 5.79 | 0.00 | BASEMENT_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | RETAIL_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 7.62E-002 | 0.92 | 4 | ||
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 134.14 | 134.14 | 134.14 | 0.00 | 90.00 | 134.14 | 1.00 | 0.00 | RETAIL_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
23 | RETAIL_2_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.214 | 1.028 | 24.62 | 26.57 | 24.62 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | Door | RETAIL_2_FLR_1_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
25 | RETAIL_2_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
26 | RETAIL_2_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | RETAIL_2_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 90.00 | 90.00 | 6.71 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | RETAIL_2_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.412 | 0.375 | 77.67 | 77.67 | 77.67 | 0.00 | 180.00 | 11.58 | 6.71 | 0.00 | BASEMENT_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
29 | RETAIL_2_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.412 | 0.383 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 155.34 | 155.34 | 155.34 | 0.00 | 90.00 | 155.34 | 1.00 | 0.00 | RETAIL_2_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
31 | MECH_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.214 | 1.028 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | MECH_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | MECH_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 180.00 | 90.00 | 15.85 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | MECH_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | MECH_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.412 | 0.375 | 164.24 | 164.24 | 164.24 | 0.00 | 180.00 | 15.85 | 10.36 | 0.00 | BASEMENT_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | MECH_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.412 | 0.383 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | MECH_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 328.49 | 328.49 | 328.49 | 0.00 | 90.00 | 328.49 | 1.00 | 0.00 | MECH_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | STORAGE_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.214 | 1.028 | 28.80 | 36.23 | 28.80 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | Door | STORAGE_FLR_1_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.198 | 1.198 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | STORAGE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
41 | STORAGE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 180.00 | 90.00 | 9.14 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
42 | STORAGE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | STORAGE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.412 | 0.375 | 94.76 | 94.76 | 94.76 | 0.00 | 180.00 | 9.14 | 10.36 | 0.00 | BASEMENT_CEILING_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
44 | STORAGE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.412 | 0.383 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | STORAGE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 189.52 | 189.52 | 189.52 | 0.00 | 90.00 | 189.52 | 1.00 | 0.00 | STORAGE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
46 | LAUNDRY_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.214 | 1.028 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | LAUNDRY_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.214 | 1.028 | 65.68 | 67.63 | 65.68 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | Door | LAUNDRY_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
49 | LAUNDRY_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 180.00 | 90.00 | 4.57 | 3.96 | 0.00 | CAFE_FLR_1_WALL_2_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | LAUNDRY_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 270.00 | 90.00 | 17.07 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
51 | LAUNDRY_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.412 | 0.375 | 78.04 | 78.04 | 78.04 | 0.00 | 180.00 | 4.57 | 17.07 | 0.00 | BASEMENT_CEILING_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
52 | LAUNDRY_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.412 | 0.383 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 156.08 | 156.08 | 156.08 | 0.00 | 90.00 | 156.08 | 1.00 | 0.00 | LAUNDRY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
54 | CAFE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.214 | 1.028 | 21.00 | 22.95 | 21.00 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CAFE_FLR_1_WALL_EAST_DOOR | Door | CAFE_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | CAFE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.214 | 1.028 | 63.73 | 129.23 | 63.73 | 180.00 | 90.00 | 32.61 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | Window | CAFE_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5119_SHGC_0.25 | N/A | 2.910 | No | 65.50 | 65.50 | 65.50 | 180.00 | 90.00 | 30.75 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
58 | CAFE_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 0.00 | 90.00 | 28.04 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | CAFE_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | CAFE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | CAFE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.412 | 0.375 | 188.86 | 188.86 | 188.86 | 0.00 | 180.00 | 32.61 | 5.79 | 0.00 | BASEMENT_CEILING_6 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
62 | CAFE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 3.86E-002 | 0.96 | 4 | ||
63 | CAFE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 377.72 | 377.72 | 377.72 | 0.00 | 90.00 | 377.72 | 1.00 | 0.00 | CAFE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
64 | LOBBY_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.214 | 1.028 | 209.87 | 213.77 | 209.87 | 0.00 | 90.00 | 53.95 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
67 | LOBBY_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.214 | 1.028 | 12.08 | 12.08 | 12.08 | 0.00 | 90.00 | 3.05 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
68 | LOBBY_FLR_1_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.214 | 1.028 | 82.79 | 167.88 | 82.79 | 180.00 | 90.00 | 42.37 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | Window | LOBBY_FLR_1_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5119_SHGC_0.25 | N/A | 2.910 | No | 85.08 | 85.08 | 85.08 | 180.00 | 90.00 | 39.95 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LOBBY_FLR_1_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.214 | 1.028 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | LOBBY_FLR_1_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | LOBBY_FLR_1_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 180.00 | 90.00 | 28.04 | 3.96 | 0.00 | CAFE_FLR_1_WALL_1_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | LOBBY_FLR_1_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | LOBBY_FLR_1_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | LOBBY_FLR_1_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | LOBBY_FLR_1_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | MECH_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | LOBBY_FLR_1_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
78 | LOBBY_FLR_1_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | LOBBY_FLR_1_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | CAFE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | LOBBY_FLR_1_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | LOBBY_FLR_1_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.412 | 0.375 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 180.00 | 32.99 | 32.99 | 0.00 | BASEMENT_CEILING_7 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
82 | LOBBY_FLR_1_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.412 | 0.375 | 219.63 | 219.63 | 219.63 | 90.00 | 180.00 | 14.82 | 14.82 | 0.00 | BASEMENT_CEILING_8 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
83 | LOBBY_FLR_1_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.412 | 0.383 | 1062.83 | 1062.83 | 1062.83 | 270.00 | 0.00 | 32.60 | 32.60 | 0.00 | LOBBY_FLR_1_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 10 | ||
84 | LOBBY_FLR_1_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 245.35 | 245.35 | 245.35 | 180.00 | 0.00 | 42.37 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.22E-003 | 1.00 | 4 | ||
85 | LOBBY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 2616.37 | 2616.37 | 2616.37 | 0.00 | 90.00 | 2616.37 | 1.00 | 0.00 | LOBBY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | ROOM_1_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.530 | 1.245 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.5119_SHGC_0.25 | N/A | 2.910 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | ROOM_1_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.530 | 1.245 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | Window | ROOM_1_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.5119_SHGC_0.25 | N/A | 2.910 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | ROOM_1_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | ROOM_1_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | ROOM_1_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.412 | 0.375 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
93 | ROOM_1_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.412 | 0.383 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
94 | ROOM_1_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
95 | ROOM_2_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.530 | 1.245 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.5119_SHGC_0.25 | N/A | 2.910 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
97 | ROOM_2_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.530 | 1.245 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | Window | ROOM_2_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.5119_SHGC_0.25 | N/A | 2.910 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | ROOM_2_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | ROOM_2_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | ROOM_2_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.412 | 0.375 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | ROOM_2_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.412 | 0.383 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | ROOM_2_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.530 | 1.245 | 7.47 | 11.15 | 7.47 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.5119_SHGC_0.25 | N/A | 2.910 | No | 3.68 | 3.68 | 3.68 | 180.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | ROOM_3_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.412 | 0.375 | 24.52 | 24.52 | 24.52 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
110 | ROOM_3_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.412 | 0.383 | 24.52 | 24.52 | 24.52 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.05 | 49.05 | 49.05 | 0.00 | 90.00 | 49.05 | 1.00 | 0.00 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.530 | 1.245 | 7.47 | 11.15 | 7.47 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_4_MULT19_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.5119_SHGC_0.25 | N/A | 2.910 | No | 3.68 | 3.68 | 3.68 | 0.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
117 | ROOM_4_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.412 | 0.375 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
118 | ROOM_4_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.412 | 0.383 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
120 | ROOM_5_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.530 | 1.245 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | Window | ROOM_5_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.5119_SHGC_0.25 | N/A | 2.910 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
122 | ROOM_5_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.530 | 1.245 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_5_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.5119_SHGC_0.25 | N/A | 2.910 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
124 | ROOM_5_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
125 | ROOM_5_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
126 | ROOM_5_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.412 | 0.375 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
127 | ROOM_5_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.412 | 0.383 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
128 | ROOM_5_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_5_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
129 | ROOM_6_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.530 | 1.245 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_6_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.5119_SHGC_0.25 | N/A | 2.910 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
131 | ROOM_6_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.530 | 1.245 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | Window | ROOM_6_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.5119_SHGC_0.25 | N/A | 2.910 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
133 | ROOM_6_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
134 | ROOM_6_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
135 | ROOM_6_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.412 | 0.375 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
136 | ROOM_6_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.412 | 0.383 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
137 | ROOM_6_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_6_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
138 | CORRIDOR_FLR_3_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.530 | 1.245 | 11.83 | 17.65 | 11.83 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5119_SHGC_0.25 | N/A | 2.910 | No | 5.82 | 5.82 | 5.82 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.530 | 1.245 | 4.35 | 6.50 | 4.35 | 0.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5119_SHGC_0.25 | N/A | 2.910 | No | 2.15 | 2.15 | 2.15 | 0.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.530 | 1.245 | 4.36 | 6.50 | 4.36 | 180.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5119_SHGC_0.25 | N/A | 2.910 | No | 2.15 | 2.15 | 2.15 | 180.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.530 | 1.245 | 11.83 | 17.65 | 11.83 | 180.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5119_SHGC_0.25 | N/A | 2.910 | No | 5.82 | 5.82 | 5.82 | 180.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 0.00 | 90.00 | 69.50 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | CORRIDOR_FLR_3_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | CORRIDOR_FLR_3_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORRIDOR_FLR_3_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | CORRIDOR_FLR_3_WALL_4_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 180.00 | 90.00 | 69.49 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
152 | CORRIDOR_FLR_3_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | CORRIDOR_FLR_3_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | CORRIDOR_FLR_3_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | CORRIDOR_FLR_3_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | CORRIDOR_FLR_3_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.412 | 0.375 | 74.32 | 74.32 | 74.32 | 180.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
157 | CORRIDOR_FLR_3_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.412 | 0.375 | 240.77 | 240.77 | 240.77 | 270.00 | 180.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | CORRIDOR_FLR_3_FLOOR_3 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.412 | 0.375 | 74.32 | 74.32 | 74.32 | 90.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
159 | CORRIDOR_FLR_3_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.412 | 0.383 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
160 | CORRIDOR_FLR_3_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.412 | 0.383 | 240.77 | 240.77 | 240.77 | 90.00 | 0.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
161 | CORRIDOR_FLR_3_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.412 | 0.383 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 778.81 | 778.81 | 778.81 | 0.00 | 90.00 | 778.81 | 1.00 | 0.00 | CORRIDOR_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
163 | ROOM_1_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.605 | 1.294 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.5119_SHGC_0.25 | N/A | 2.910 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
165 | ROOM_1_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.605 | 1.294 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | Window | ROOM_1_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.5119_SHGC_0.25 | N/A | 2.910 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
167 | ROOM_1_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
168 | ROOM_1_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
169 | ROOM_1_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.412 | 0.375 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | ROOM_1_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.283 | 0.269 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
171 | ROOM_1_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
172 | ROOM_2_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.605 | 1.294 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.5119_SHGC_0.25 | N/A | 2.910 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
174 | ROOM_2_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.605 | 1.294 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | Window | ROOM_2_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.5119_SHGC_0.25 | N/A | 2.910 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
176 | ROOM_2_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
177 | ROOM_2_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
178 | ROOM_2_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.412 | 0.375 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | ROOM_2_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.283 | 0.269 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
180 | ROOM_2_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.605 | 1.294 | 13.70 | 20.44 | 13.70 | 180.00 | 90.00 | 6.71 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.5119_SHGC_0.25 | N/A | 2.910 | No | 6.74 | 6.74 | 6.74 | 180.00 | 90.00 | 5.53 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 0.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 90.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | ROOM_3_MULT9_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.412 | 0.375 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 6.71 | 3.66 | 0.00 | ROOM_3_MULT9_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
187 | ROOM_3_MULT9_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.283 | 0.269 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 6.71 | 3.66 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
189 | BANQUET_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.605 | 1.294 | 65.36 | 97.55 | 65.36 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | Window | BANQUET_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5119_SHGC_0.25 | N/A | 2.910 | No | 32.19 | 32.19 | 32.19 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
191 | BANQUET_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
192 | BANQUET_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
193 | BANQUET_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
194 | BANQUET_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.412 | 0.375 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | BANQUET_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
195 | BANQUET_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
196 | BANQUET_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | BANQUET_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
197 | DINING_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.605 | 1.294 | 65.36 | 97.55 | 65.36 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DINING_FLR_6_WALL_NORTH_WINDOW | Window | DINING_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5119_SHGC_0.25 | N/A | 2.910 | No | 32.19 | 32.19 | 32.19 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
199 | DINING_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
200 | DINING_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | DINING_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DINING_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DINING_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.412 | 0.375 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | DINING_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
203 | DINING_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
204 | DINING_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | DINING_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
205 | KITCHEN_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.605 | 1.294 | 16.77 | 21.37 | 16.77 | 0.00 | 90.00 | 7.01 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | Window | KITCHEN_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5119_SHGC_0.25 | N/A | 2.910 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
207 | KITCHEN_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.605 | 1.294 | 34.86 | 52.03 | 34.86 | 90.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | Window | KITCHEN_FLR_6_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5119_SHGC_0.25 | N/A | 2.910 | No | 17.17 | 17.17 | 17.17 | 90.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.605 | 1.294 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | Window | KITCHEN_FLR_6_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5119_SHGC_0.25 | N/A | 2.910 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 7.43 | 7.43 | 7.43 | 180.00 | 90.00 | 2.44 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
212 | KITCHEN_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | KITCHEN_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | KITCHEN_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.412 | 0.375 | 103.30 | 103.30 | 103.30 | 180.00 | 180.00 | 10.16 | 10.16 | 0.00 | KITCHEN_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
215 | KITCHEN_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 103.30 | 103.30 | 103.30 | 270.00 | 0.00 | 10.16 | 10.16 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
216 | KITCHEN_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 206.61 | 206.61 | 206.61 | 0.00 | 90.00 | 206.61 | 1.00 | 0.00 | KITCHEN_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
217 | CORRIDOR_FLR_6_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.605 | 1.294 | 11.83 | 17.65 | 11.83 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5119_SHGC_0.25 | N/A | 2.910 | No | 5.82 | 5.82 | 5.82 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.605 | 1.294 | 10.58 | 15.79 | 10.58 | 0.00 | 90.00 | 5.18 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5119_SHGC_0.25 | N/A | 2.910 | No | 5.21 | 5.21 | 5.21 | 0.00 | 90.00 | 4.27 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.605 | 1.294 | 34.86 | 52.03 | 34.86 | 180.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5119_SHGC_0.25 | N/A | 2.910 | No | 17.17 | 17.17 | 17.17 | 180.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
224 | CORRIDOR_FLR_6_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 104.98 | 104.98 | 104.98 | 0.00 | 90.00 | 34.44 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 183.95 | 183.95 | 183.95 | 180.00 | 90.00 | 60.35 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
226 | CORRIDOR_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
227 | CORRIDOR_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 40.88 | 40.88 | 40.88 | 270.00 | 90.00 | 13.41 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
228 | CORRIDOR_FLR_6_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
229 | CORRIDOR_FLR_6_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
230 | CORRIDOR_FLR_6_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
231 | CORRIDOR_FLR_6_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
232 | CORRIDOR_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.412 | 0.375 | 412.12 | 412.12 | 412.12 | 180.00 | 180.00 | 20.30 | 20.30 | 0.00 | CORRIDOR_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 12 | ||
233 | CORRIDOR_FLR_6_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 244.71 | 244.71 | 244.71 | 90.00 | 0.00 | 15.64 | 15.64 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 8 | ||
234 | CORRIDOR_FLR_6_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 167.42 | 167.42 | 167.42 | 270.00 | 0.00 | 12.94 | 12.94 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 824.25 | 824.25 | 824.25 | 0.00 | 90.00 | 824.25 | 1.00 | 0.00 | CORRIDOR_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 1.1078575894E-002 | 1.8017855108E-002 | Pass | Pass | 5.9131166824E-003 | 1.6416601189E-002 | Pass | Pass |
2 | RETAIL_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 3.4660655077E-003 | 4.2871523101E-003 | Pass | Pass | 2.9797918898E-002 | 2.8370438354E-002 | Pass | Pass |
3 | RETAIL_2_FLR_1 | RunPeriod: RUNPERIOD 1 | 2.6350570417E-003 | 4.8428314225E-003 | Pass | Pass | 1.5109635839E-002 | 3.0538877152E-002 | Pass | Pass |
4 | MECH_FLR_1 | RunPeriod: RUNPERIOD 1 | 8.3505955449E-004 | 6.5132957218E-004 | Pass | Pass | 1.7822869450E-002 | 3.2267725063E-002 | Pass | Pass |
5 | STORAGE_FLR_1 | RunPeriod: RUNPERIOD 1 | 1.2430010900E-003 | 1.8501039770E-003 | Pass | Pass | 2.1223029857E-002 | 2.6325087736E-002 | Pass | Pass |
6 | LAUNDRY_FLR_1 | RunPeriod: RUNPERIOD 1 | 4.3588615983E-002 | 0.1350490964 | Pass | Pass | 1.8446907361E-002 | 5.3737491449E-002 | Pass | Pass |
7 | CAFE_FLR_1 | RunPeriod: RUNPERIOD 1 | 2.6365433262E-003 | 1.9193035652E-003 | Pass | Pass | 2.0828615009E-002 | 3.9114081536E-002 | Pass | Pass |
8 | LOBBY_FLR_1 | RunPeriod: RUNPERIOD 1 | 6.4600654308E-003 | 1.5776944231E-002 | Pass | Pass | 1.5362599619E-002 | 3.5985570595E-002 | Pass | Pass |
9 | ROOM_1_FLR_3 | RunPeriod: RUNPERIOD 1 | 5.5547546174E-002 | 0.2082695279 | Pass | Pass | 0.2172869655 | 0.9001627844 | Pass | Pass |
10 | ROOM_2_FLR_3 | RunPeriod: RUNPERIOD 1 | 4.4824723179E-002 | 0.1728274261 | Pass | Pass | 0.1717735766 | 0.3764906904 | Pass | Pass |
11 | ROOM_3_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 9.2973660458E-003 | 2.0325842950E-002 | Pass | Pass | 3.4537232864E-002 | 6.0348784111E-002 | Pass | Pass |
12 | ROOM_4_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 5.0434403921E-002 | 0.1738544202 | Pass | Pass | 8.9408719240E-002 | 0.2722827965 | Pass | Pass |
13 | ROOM_5_FLR_3 | RunPeriod: RUNPERIOD 1 | 5.0727153941E-002 | 0.1740450391 | Pass | Pass | 0.2190531342 | 0.7195989142 | Pass | Pass |
14 | ROOM_6_FLR_3 | RunPeriod: RUNPERIOD 1 | 3.1532843118E-002 | 0.1089679587 | Pass | Pass | 0.1568490311 | 0.3447142881 | Pass | Pass |
15 | CORRIDOR_FLR_3 | RunPeriod: RUNPERIOD 1 | 5.8587128028E-004 | 4.1421022561E-004 | Pass | Pass | 1.7083964507E-002 | 2.7473255315E-002 | Pass | Pass |
16 | ROOM_1_FLR_6 | RunPeriod: RUNPERIOD 1 | 5.1765626513E-002 | 0.2054132352 | Pass | Pass | 0.2529150203 | 0.8069281723 | Pass | Pass |
17 | ROOM_2_FLR_6 | RunPeriod: RUNPERIOD 1 | 4.5966143481E-002 | 0.1841209666 | Pass | Pass | 1.6877542523 | 18.7014743830 | Pass | Pass |
18 | ROOM_3_MULT9_FLR_6 | RunPeriod: RUNPERIOD 1 | 6.8175347057E-002 | 0.2432432861 | Pass | Pass | 0.1235245548 | 0.3741232148 | Pass | Pass |
19 | BANQUET_FLR_6 | RunPeriod: RUNPERIOD 1 | 2.7099773294E-002 | 6.5899912928E-002 | Pass | Pass | 1.0578712806E-002 | 2.9467468079E-002 | Pass | Pass |
20 | DINING_FLR_6 | RunPeriod: RUNPERIOD 1 | 2.9250803974E-002 | 6.6799654076E-002 | Pass | Pass | 1.0061001202E-002 | 2.5684233778E-002 | Pass | Pass |
21 | KITCHEN_FLR_6 | RunPeriod: RUNPERIOD 1 | 6.8343361409E-002 | 0.1206194322 | Pass | Pass | 1.6832133047E-002 | 3.0188939155E-002 | Pass | Pass |
22 | CORRIDOR_FLR_6 | RunPeriod: RUNPERIOD 1 | 1.2427593523E-003 | 1.0087341564E-003 | Pass | Pass | 2.6654270744E-002 | 2.1621134078E-002 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:58:09
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 2188.39 | -233.2 | -802.4 | -15028.0 | 25297.57 | 11422.29 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:58:09
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 12.70 | 0.00 | 12.70 | Wetbulb [C] | 2.00 | 170.00 |
DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 42.80 | 9.70 | 23.80 | Wetbulb [C] | 5.00 | 80.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 2.40 | 26 | |||
Feb | 9.60 | 38 | |||
Mar | 3.60 | 37 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 0.00 | 0 | |||
Jul | 1.20 | 13 | |||
Aug | 0.00 | 0 | |||
Sep | 0.00 | 0 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 18.00 | 37 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:58:09
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.845 | 0.940 | 211.13 | 211.13 | 0.00 | 90.00 | N |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.845 | 0.940 | 55.76 | 55.76 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.845 | 0.940 | 211.13 | 211.13 | 180.00 | 90.00 | S |
BASEMENT_WALL_WEST | BASEMENT_WALL_WEST_CFACTOR | 1.00 | 0.845 | 0.940 | 55.76 | 55.76 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 1.028 | 1.214 | 45.89 | 22.63 | 180.00 | 90.00 | S |
RETAIL_1_FLR_1_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 1.028 | 1.214 | 22.95 | 22.95 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_CEILING | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 67.07 | 67.07 | 180.00 | 0.00 | |
RETAIL_2_FLR_1_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 1.028 | 1.214 | 26.57 | 24.62 | 270.00 | 90.00 | W |
MECH_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 1.028 | 1.214 | 62.80 | 62.80 | 0.00 | 90.00 | N |
STORAGE_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 1.028 | 1.214 | 36.23 | 28.80 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 1.028 | 1.214 | 18.12 | 18.12 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 1.028 | 1.214 | 67.63 | 65.68 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 1.028 | 1.214 | 22.95 | 21.00 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 1.028 | 1.214 | 129.23 | 63.73 | 180.00 | 90.00 | S |
CAFE_FLR_1_CEILING | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 188.86 | 188.86 | 180.00 | 0.00 | |
LOBBY_FLR_1_WALL_1_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 1.028 | 1.214 | 213.77 | 209.87 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_2_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 1.028 | 1.214 | 12.08 | 12.08 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 1.028 | 1.214 | 167.88 | 82.79 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_1_WEST | NONRES_EXT_WALL_GRD | 0.30 | 1.028 | 1.214 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_CEILING_2 | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 245.35 | 245.35 | 180.00 | 0.00 | |
ROOM_1_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 1.245 | 1.530 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_1_FLR_3_WALL_WEST | RES_EXT_WALL_MID | 0.30 | 1.245 | 1.530 | 104.06 | 69.72 | 270.00 | 90.00 | W |
ROOM_2_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 1.245 | 1.530 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_2_FLR_3_WALL_WEST | RES_EXT_WALL_MID | 0.30 | 1.245 | 1.530 | 104.05 | 69.71 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 1.245 | 1.530 | 847.14 | 567.58 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 1.245 | 1.530 | 847.37 | 567.71 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_EAST | RES_EXT_WALL_MID | 0.30 | 1.245 | 1.530 | 104.06 | 69.72 | 90.00 | 90.00 | E |
ROOM_5_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 1.245 | 1.530 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 1.245 | 1.530 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_6_FLR_3_WALL_EAST | RES_EXT_WALL_MID | 0.30 | 1.245 | 1.530 | 104.05 | 69.71 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_1_NORTH | NONRES_EXT_WALL_MID | 0.30 | 1.245 | 1.530 | 70.60 | 47.31 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_2_NORTH | NONRES_EXT_WALL_MID | 0.30 | 1.245 | 1.530 | 26.01 | 17.42 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 1.245 | 1.530 | 26.02 | 17.43 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_2_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 1.245 | 1.530 | 70.60 | 47.31 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_SOUTH | RES_EXT_WALL_TOP | 0.30 | 1.294 | 1.605 | 13.94 | 9.34 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_WEST | RES_EXT_WALL_TOP | 0.30 | 1.294 | 1.605 | 26.01 | 17.43 | 270.00 | 90.00 | W |
ROOM_1_FLR_6_CEILING | RES_ROOF | 0.55 | 0.273 | 0.283 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_2_FLR_6_WALL_NORTH | RES_EXT_WALL_TOP | 0.30 | 1.294 | 1.605 | 13.94 | 9.34 | 0.00 | 90.00 | N |
ROOM_2_FLR_6_WALL_WEST | RES_EXT_WALL_TOP | 0.30 | 1.294 | 1.605 | 26.01 | 17.43 | 270.00 | 90.00 | W |
ROOM_2_FLR_6_CEILING | RES_ROOF | 0.55 | 0.273 | 0.283 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | RES_EXT_WALL_TOP | 0.30 | 1.294 | 1.605 | 183.96 | 123.26 | 180.00 | 90.00 | S |
ROOM_3_MULT9_FLR_6_CEILING | RES_ROOF | 0.55 | 0.273 | 0.283 | 220.77 | 220.77 | 180.00 | 0.00 | |
BANQUET_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.294 | 1.605 | 97.55 | 65.36 | 0.00 | 90.00 | N |
BANQUET_FLR_6_CEILING | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 331.66 | 331.66 | 180.00 | 0.00 | |
DINING_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.294 | 1.605 | 97.55 | 65.36 | 0.00 | 90.00 | N |
DINING_FLR_6_CEILING | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 331.66 | 331.66 | 180.00 | 0.00 | |
KITCHEN_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.294 | 1.605 | 21.37 | 16.77 | 0.00 | 90.00 | N |
KITCHEN_FLR_6_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.294 | 1.605 | 52.03 | 34.86 | 90.00 | 90.00 | E |
KITCHEN_FLR_6_WALL_1_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.294 | 1.605 | 13.94 | 9.34 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_CEILING | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 103.30 | 103.30 | 270.00 | 0.00 | |
CORRIDOR_FLR_6_WALL_1_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.294 | 1.605 | 17.65 | 11.83 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.294 | 1.605 | 15.79 | 10.58 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.294 | 1.605 | 52.03 | 34.86 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_CEILING_1 | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 244.71 | 244.71 | 90.00 | 0.00 | |
CORRIDOR_FLR_6_CEILING_2 | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 167.42 | 167.42 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_FLOOR | BASEMENT_FLOOR | 0.30 | 1.441 | 2.705 | 1978.83 | 1978.83 | 0.00 | 180.00 | |
BASEMENT_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.371 | 0.412 | 67.07 | 67.07 | 180.00 | 0.00 | |
BASEMENT_CEILING_2 | NONRES_FLOOR_CEILING | 0.30 | 0.371 | 0.412 | 77.67 | 77.67 | 180.00 | 0.00 | |
BASEMENT_CEILING_3 | NONRES_FLOOR_CEILING | 0.30 | 0.371 | 0.412 | 164.24 | 164.24 | 180.00 | 0.00 | |
BASEMENT_CEILING_4 | NONRES_FLOOR_CEILING | 0.30 | 0.371 | 0.412 | 94.76 | 94.76 | 180.00 | 0.00 | |
BASEMENT_CEILING_5 | NONRES_FLOOR_CEILING | 0.30 | 0.371 | 0.412 | 78.04 | 78.04 | 180.00 | 0.00 | |
BASEMENT_CEILING_6 | NONRES_FLOOR_CEILING | 0.30 | 0.371 | 0.412 | 188.86 | 188.86 | 180.00 | 0.00 | |
BASEMENT_CEILING_7 | NONRES_FLOOR_CEILING | 0.30 | 0.371 | 0.412 | 1088.56 | 1088.56 | 180.00 | 0.00 | |
BASEMENT_CEILING_8 | NONRES_FLOOR_CEILING | 0.30 | 0.371 | 0.412 | 219.63 | 219.63 | 90.00 | 0.00 | |
RETAIL_1_FLR_1_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 0.00 | 90.00 | N |
RETAIL_1_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 90.00 | 90.00 | E |
RETAIL_1_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.371 | 0.412 | 67.07 | 67.07 | 0.00 | 180.00 | |
RETAIL_2_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 180.00 | 90.00 | S |
RETAIL_2_FLR_1_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 0.00 | 90.00 | N |
RETAIL_2_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.57 | 26.57 | 90.00 | 90.00 | E |
RETAIL_2_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.371 | 0.412 | 77.67 | 77.67 | 0.00 | 180.00 | |
RETAIL_2_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.379 | 0.412 | 77.67 | 77.67 | 180.00 | 0.00 | |
MECH_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
MECH_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 62.80 | 62.80 | 180.00 | 90.00 | S |
MECH_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
MECH_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.371 | 0.412 | 164.24 | 164.24 | 0.00 | 180.00 | |
MECH_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.379 | 0.412 | 164.24 | 164.24 | 180.00 | 0.00 | |
STORAGE_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
STORAGE_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 36.23 | 36.23 | 180.00 | 90.00 | S |
STORAGE_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
STORAGE_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.371 | 0.412 | 94.76 | 94.76 | 0.00 | 180.00 | |
STORAGE_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.379 | 0.412 | 94.76 | 94.76 | 180.00 | 0.00 | |
LAUNDRY_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 18.12 | 18.12 | 180.00 | 90.00 | S |
LAUNDRY_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 67.63 | 67.63 | 270.00 | 90.00 | W |
LAUNDRY_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.371 | 0.412 | 78.04 | 78.04 | 0.00 | 180.00 | |
LAUNDRY_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.379 | 0.412 | 78.04 | 78.04 | 180.00 | 0.00 | |
CAFE_FLR_1_WALL_1_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.11 | 111.11 | 0.00 | 90.00 | N |
CAFE_FLR_1_WALL_2_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 18.12 | 18.12 | 0.00 | 90.00 | N |
CAFE_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 270.00 | 90.00 | W |
CAFE_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.371 | 0.412 | 188.86 | 188.86 | 0.00 | 180.00 | |
LOBBY_FLR_1_WALL_2_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_3_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.11 | 111.11 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.57 | 26.57 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_4_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 62.80 | 62.80 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_4_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 36.23 | 36.23 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
LOBBY_FLR_1_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 90.00 | 90.00 | E |
LOBBY_FLR_1_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 67.63 | 67.63 | 90.00 | 90.00 | E |
LOBBY_FLR_1_FLOOR_1 | NONRES_FLOOR | 0.30 | 0.371 | 0.412 | 1088.56 | 1088.56 | 180.00 | 180.00 | |
LOBBY_FLR_1_FLOOR_2 | NONRES_FLOOR | 0.30 | 0.371 | 0.412 | 219.63 | 219.63 | 90.00 | 180.00 | |
LOBBY_FLR_1_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.379 | 0.412 | 1062.83 | 1062.83 | 270.00 | 0.00 | |
ROOM_1_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 0.00 | 90.00 | N |
ROOM_1_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 90.00 | 90.00 | E |
ROOM_1_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.364 | 0.412 | 156.09 | 156.09 | 0.00 | 180.00 | |
ROOM_1_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.379 | 0.412 | 156.09 | 156.09 | 180.00 | 0.00 | |
ROOM_2_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 90.00 | 90.00 | E |
ROOM_2_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 180.00 | 90.00 | S |
ROOM_2_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.364 | 0.412 | 156.07 | 156.07 | 0.00 | 180.00 | |
ROOM_2_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.379 | 0.412 | 156.07 | 156.07 | 180.00 | 0.00 | |
ROOM_3_MULT19_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.14 | 847.14 | 0.00 | 90.00 | N |
ROOM_3_MULT19_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 90.00 | 90.00 | E |
ROOM_3_MULT19_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.364 | 0.412 | 1863.81 | 1863.81 | 0.00 | 180.00 | |
ROOM_3_MULT19_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.379 | 0.412 | 1863.81 | 1863.81 | 180.00 | 0.00 | |
ROOM_4_MULT19_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 90.00 | 90.00 | E |
ROOM_4_MULT19_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.37 | 847.37 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 270.00 | 90.00 | W |
ROOM_4_MULT19_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.364 | 0.412 | 1864.32 | 1864.32 | 0.00 | 180.00 | |
ROOM_4_MULT19_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.379 | 0.412 | 1864.32 | 1864.32 | 180.00 | 0.00 | |
ROOM_5_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 270.00 | 90.00 | W |
ROOM_5_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.364 | 0.412 | 156.09 | 156.09 | 0.00 | 180.00 | |
ROOM_5_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.379 | 0.412 | 156.09 | 156.09 | 180.00 | 0.00 | |
ROOM_6_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 270.00 | 90.00 | W |
ROOM_6_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.364 | 0.412 | 156.07 | 156.07 | 0.00 | 180.00 | |
ROOM_6_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.379 | 0.412 | 156.07 | 156.07 | 180.00 | 0.00 | |
CORRIDOR_FLR_3_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.28 | 847.28 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_4_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_3_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.27 | 847.27 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_4_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_FLOOR_1 | NONRES_FLOOR | 0.30 | 0.364 | 0.412 | 297.29 | 297.29 | 180.00 | 180.00 | |
CORRIDOR_FLR_3_FLOOR_2 | NONRES_FLOOR | 0.30 | 0.364 | 0.412 | 963.06 | 963.06 | 270.00 | 180.00 | |
CORRIDOR_FLR_3_FLOOR_3 | NONRES_FLOOR | 0.30 | 0.364 | 0.412 | 297.26 | 297.26 | 90.00 | 180.00 | |
CORRIDOR_FLR_3_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.379 | 0.412 | 297.29 | 297.29 | 90.00 | 0.00 | |
CORRIDOR_FLR_3_CEILING_2 | NONRES_FLOOR_CEILING | 0.30 | 0.379 | 0.412 | 963.06 | 963.06 | 90.00 | 0.00 | |
CORRIDOR_FLR_3_CEILING_3 | NONRES_FLOOR_CEILING | 0.30 | 0.379 | 0.412 | 297.26 | 297.26 | 90.00 | 0.00 | |
ROOM_1_FLR_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 13.94 | 13.94 | 0.00 | 90.00 | N |
ROOM_1_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.01 | 26.01 | 90.00 | 90.00 | E |
ROOM_1_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.364 | 0.412 | 39.02 | 39.02 | 0.00 | 180.00 | |
ROOM_2_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.01 | 26.01 | 90.00 | 90.00 | E |
ROOM_2_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 13.94 | 13.94 | 180.00 | 90.00 | S |
ROOM_2_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.364 | 0.412 | 39.02 | 39.02 | 0.00 | 180.00 | |
ROOM_3_MULT9_FLR_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 183.96 | 183.96 | 0.00 | 90.00 | N |
ROOM_3_MULT9_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 100.35 | 100.35 | 90.00 | 90.00 | E |
ROOM_3_MULT9_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 100.35 | 100.35 | 270.00 | 90.00 | W |
ROOM_3_MULT9_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.364 | 0.412 | 220.77 | 220.77 | 0.00 | 180.00 | |
BANQUET_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
BANQUET_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 180.00 | 90.00 | S |
BANQUET_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
BANQUET_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.364 | 0.412 | 331.66 | 331.66 | 0.00 | 180.00 | |
DINING_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
DINING_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 180.00 | 90.00 | S |
DINING_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
DINING_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.364 | 0.412 | 331.66 | 331.66 | 0.00 | 180.00 | |
KITCHEN_FLR_6_WALL_2_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 7.43 | 7.43 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 20.44 | 20.44 | 270.00 | 90.00 | W |
KITCHEN_FLR_6_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
KITCHEN_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.364 | 0.412 | 103.30 | 103.30 | 180.00 | 180.00 | |
CORRIDOR_FLR_6_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_4_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 104.98 | 104.98 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_1_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 183.95 | 183.95 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 11.15 | 11.15 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 40.88 | 40.88 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 20.44 | 20.44 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.364 | 0.412 | 412.12 | 412.12 | 180.00 | 180.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3957.66 | 0.00 | 90.00 | N | ||
RETAIL_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 134.14 | 0.00 | 90.00 | N | ||
RETAIL_2_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 155.34 | 0.00 | 90.00 | N | ||
MECH_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 328.49 | 0.00 | 90.00 | N | ||
STORAGE_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 189.52 | 0.00 | 90.00 | N | ||
LAUNDRY_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 156.08 | 0.00 | 90.00 | N | ||
CAFE_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 377.72 | 0.00 | 90.00 | N | ||
LOBBY_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 2616.37 | 0.00 | 90.00 | N | ||
ROOM_1_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.18 | 0.00 | 90.00 | N | ||
ROOM_2_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.14 | 0.00 | 90.00 | N | ||
ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3727.63 | 0.00 | 90.00 | N | ||
ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3728.64 | 0.00 | 90.00 | N | ||
ROOM_5_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.18 | 0.00 | 90.00 | N | ||
ROOM_6_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.14 | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3115.24 | 0.00 | 90.00 | N | ||
ROOM_1_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 78.04 | 0.00 | 90.00 | N | ||
ROOM_2_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 78.03 | 0.00 | 90.00 | N | ||
ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 441.55 | 0.00 | 90.00 | N | ||
BANQUET_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 663.31 | 0.00 | 90.00 | N | ||
DINING_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 663.31 | 0.00 | 90.00 | N | ||
KITCHEN_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 206.61 | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 824.25 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.5119_SHGC_0.25 | 23.26 | 0.00 | 0.00 | 23.26 | 23.26 | 2.910 | 0.251 | 0.251 | No | RETAIL_1_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
CAFE_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.5119_SHGC_0.25 | 65.50 | 0.00 | 0.00 | 65.50 | 65.50 | 2.910 | 0.251 | 0.251 | No | CAFE_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
LOBBY_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.5119_SHGC_0.25 | 85.08 | 0.00 | 0.00 | 85.08 | 85.08 | 2.910 | 0.251 | 0.251 | No | LOBBY_FLR_1_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.5119_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.910 | 0.251 | 0.251 | No | ROOM_1_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.5119_SHGC_0.25 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.910 | 0.251 | 0.251 | No | ROOM_1_FLR_3_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_2_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.5119_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.910 | 0.251 | 0.251 | No | ROOM_2_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_2_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.5119_SHGC_0.25 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.910 | 0.251 | 0.251 | No | ROOM_2_FLR_3_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.5119_SHGC_0.25 | 3.68 | 0.00 | 0.00 | 3.68 | 279.56 | 2.910 | 0.251 | 0.251 | No | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.5119_SHGC_0.25 | 3.68 | 0.00 | 0.00 | 3.68 | 279.65 | 2.910 | 0.251 | 0.251 | No | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_5_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.5119_SHGC_0.25 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.910 | 0.251 | 0.251 | No | ROOM_5_FLR_3_WALL_EAST | 90.00 | 90.00 | E | |||||||
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.5119_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.910 | 0.251 | 0.251 | No | ROOM_5_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_6_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.5119_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.910 | 0.251 | 0.251 | No | ROOM_6_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_6_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.5119_SHGC_0.25 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.910 | 0.251 | 0.251 | No | ROOM_6_FLR_3_WALL_EAST | 90.00 | 90.00 | E | |||||||
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.5119_SHGC_0.25 | 5.82 | 0.00 | 0.00 | 5.82 | 23.30 | 2.910 | 0.251 | 0.251 | No | CORRIDOR_FLR_3_WALL_1_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.5119_SHGC_0.25 | 2.15 | 0.00 | 0.00 | 2.15 | 8.59 | 2.910 | 0.251 | 0.251 | No | CORRIDOR_FLR_3_WALL_2_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.5119_SHGC_0.25 | 2.15 | 0.00 | 0.00 | 2.15 | 8.58 | 2.910 | 0.251 | 0.251 | No | CORRIDOR_FLR_3_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.5119_SHGC_0.25 | 5.82 | 0.00 | 0.00 | 5.82 | 23.30 | 2.910 | 0.251 | 0.251 | No | CORRIDOR_FLR_3_WALL_2_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.5119_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.910 | 0.251 | 0.251 | No | ROOM_1_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.5119_SHGC_0.25 | 8.58 | 0.00 | 0.00 | 8.58 | 8.58 | 2.910 | 0.251 | 0.251 | No | ROOM_1_FLR_6_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_2_FLR_6_WALL_NORTH_WINDOW | RESWINDOW_U_0.5119_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.910 | 0.251 | 0.251 | No | ROOM_2_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_2_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.5119_SHGC_0.25 | 8.58 | 0.00 | 0.00 | 8.58 | 8.58 | 2.910 | 0.251 | 0.251 | No | ROOM_2_FLR_6_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.5119_SHGC_0.25 | 6.74 | 0.00 | 0.00 | 6.74 | 60.70 | 2.910 | 0.251 | 0.251 | No | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
BANQUET_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.5119_SHGC_0.25 | 32.19 | 0.00 | 0.00 | 32.19 | 32.19 | 2.910 | 0.251 | 0.251 | No | BANQUET_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
DINING_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.5119_SHGC_0.25 | 32.19 | 0.00 | 0.00 | 32.19 | 32.19 | 2.910 | 0.251 | 0.251 | No | DINING_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
KITCHEN_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.5119_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.910 | 0.251 | 0.251 | No | KITCHEN_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
KITCHEN_FLR_6_WALL_EAST_WINDOW | NONRESWINDOW_U_0.5119_SHGC_0.25 | 17.17 | 0.00 | 0.00 | 17.17 | 17.17 | 2.910 | 0.251 | 0.251 | No | KITCHEN_FLR_6_WALL_EAST | 90.00 | 90.00 | E | |||||||
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.5119_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.910 | 0.251 | 0.251 | No | KITCHEN_FLR_6_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.5119_SHGC_0.25 | 5.82 | 0.00 | 0.00 | 5.82 | 5.82 | 2.910 | 0.251 | 0.251 | No | CORRIDOR_FLR_6_WALL_1_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.5119_SHGC_0.25 | 5.21 | 0.00 | 0.00 | 5.21 | 5.21 | 2.910 | 0.251 | 0.251 | No | CORRIDOR_FLR_6_WALL_2_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.5119_SHGC_0.25 | 17.17 | 0.00 | 0.00 | 17.17 | 17.17 | 2.910 | 0.251 | 0.251 | No | CORRIDOR_FLR_6_WALL_2_SOUTH | 180.00 | 90.00 | S | |||||||
Total or Average | 1213.79 | 2.910 | 0.251 | 0.251 | |||||||||||||||||
North Total or Average | 432.95 | 2.910 | 0.251 | 0.251 | |||||||||||||||||
Non-North Total or Average | 780.84 | 2.910 | 0.251 | 0.251 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
RETAIL_2_FLR_1_WALL_WEST_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | RETAIL_2_FLR_1_WALL_WEST |
STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | OVERHEAD DOOR_CON | 1.016 | 1.198 | 7.43 | STORAGE_FLR_1_WALL_NORTH |
LAUNDRY_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | LAUNDRY_FLR_1_WALL_EAST |
CAFE_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | CAFE_FLR_1_WALL_EAST |
LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:58:09
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
CAFE_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LOBBY_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
BANQUET_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:58:09
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 8.7495 | 1978.83 | 17313.73 | LightsWired | LTG_SCH_BASEMENT | 50.91 | 168.00 | 50.86 | 0.0000 | Y | 165.29 |
RETAIL_1_FLR_1_LIGHTS | RETAIL_1_FLR_1 | RETAIL_1_FLR_1 | GENERAL | 13.0124 | 67.07 | 872.76 | LightsWired | LTG_SCH_RETAIL | 51.36 | 168.00 | 51.30 | 0.0000 | Y | 8.40 |
RETAIL_2_FLR_1_LIGHTS | RETAIL_2_FLR_1 | RETAIL_2_FLR_1 | GENERAL | 13.0124 | 77.67 | 1010.66 | LightsWired | LTG_SCH_RETAIL | 51.36 | 168.00 | 51.30 | 0.0000 | Y | 9.73 |
MECH_FLR_1_LIGHTS | MECH_FLR_1 | MECH_FLR_1 | GENERAL | 10.0642 | 164.24 | 1652.98 | LightsWired | LTG_SCH_MECHANIC | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 18.19 |
STORAGE_FLR_1_LIGHTS | STORAGE_FLR_1 | STORAGE_FLR_1 | GENERAL | 7.3195 | 94.76 | 693.59 | LightsWired | LTG_SCH_STORAGE | 25.68 | 168.00 | 25.65 | 0.0000 | Y | 3.34 |
LAUNDRY_FLR_1_LIGHTS | LAUNDRY_FLR_1 | LAUNDRY_FLR_1 | GENERAL | 5.4896 | 78.04 | 428.40 | LightsWired | LTG_SCH_LAUNDRY | 51.36 | 168.00 | 51.30 | 0.0000 | Y | 4.13 |
CAFE_FLR_1_LIGHTS | CAFE_FLR_1 | CAFE_FLR_1 | GENERAL | 12.8090 | 188.86 | 2419.14 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 26.62 |
LOBBY_FLR_1_LIGHTS | LOBBY_FLR_1 | LOBBY_FLR_1 | GENERAL | 10.0642 | 1308.19 | 13165.91 | LightsWired | LTG_SCH_LOBBY | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 144.89 |
ROOM_1_FLR_3_LIGHTS | ROOM_1_FLR_3 | ROOM_1_FLR_3 | GENERAL | 10.0642 | 156.09 | 1570.91 | LightsWired | LTG_SCH_GUESTROOM | 69.03 | 168.00 | 69.21 | 0.0000 | Y | 20.41 |
ROOM_2_FLR_3_LIGHTS | ROOM_2_FLR_3 | ROOM_2_FLR_3 | GENERAL | 10.0642 | 156.07 | 1570.72 | LightsWired | LTG_SCH_GUESTROOM | 69.03 | 168.00 | 69.21 | 0.0000 | Y | 20.41 |
ROOM_3_MULT19_FLR_3_LIGHTS | ROOM_3_MULT19_FLR_3 | ROOM_3_MULT19_FLR_3 | GENERAL | 10.0642 | 1863.81 | 18757.86 | LightsWired | LTG_SCH_GUESTROOM | 69.03 | 168.00 | 69.21 | 0.0000 | Y | 243.70 |
ROOM_4_MULT19_FLR_3_LIGHTS | ROOM_4_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | GENERAL | 10.0642 | 1864.32 | 18762.99 | LightsWired | LTG_SCH_GUESTROOM | 69.03 | 168.00 | 69.21 | 0.0000 | Y | 243.77 |
ROOM_5_FLR_3_LIGHTS | ROOM_5_FLR_3 | ROOM_5_FLR_3 | GENERAL | 10.0642 | 156.09 | 1570.91 | LightsWired | LTG_SCH_GUESTROOM | 69.03 | 168.00 | 69.21 | 0.0000 | Y | 20.41 |
ROOM_6_FLR_3_LIGHTS | ROOM_6_FLR_3 | ROOM_6_FLR_3 | GENERAL | 10.0642 | 156.07 | 1570.72 | LightsWired | LTG_SCH_GUESTROOM | 69.03 | 168.00 | 69.21 | 0.0000 | Y | 20.41 |
CORRIDOR_FLR_3_LIGHTS | CORRIDOR_FLR_3 | CORRIDOR_FLR_3 | GENERAL | 3.6597 | 1557.62 | 5700.46 | LightsWired | LTG_SCH_CORRIDOR | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 62.73 |
ROOM_1_FLR_6_LIGHTS | ROOM_1_FLR_6 | ROOM_1_FLR_6 | GENERAL | 10.0642 | 39.02 | 392.73 | LightsWired | LTG_SCH_GUESTROOM | 69.03 | 168.00 | 69.21 | 0.0000 | Y | 5.10 |
ROOM_2_FLR_6_LIGHTS | ROOM_2_FLR_6 | ROOM_2_FLR_6 | GENERAL | 10.0642 | 39.02 | 392.68 | LightsWired | LTG_SCH_GUESTROOM | 69.03 | 168.00 | 69.21 | 0.0000 | Y | 5.10 |
ROOM_3_MULT9_FLR_6_LIGHTS | ROOM_3_MULT9_FLR_6 | ROOM_3_MULT9_FLR_6 | GENERAL | 10.0642 | 220.77 | 2221.93 | LightsWired | LTG_SCH_GUESTROOM | 69.03 | 168.00 | 69.21 | 0.0000 | Y | 28.87 |
BANQUET_FLR_6_LIGHTS | BANQUET_FLR_6 | BANQUET_FLR_6 | GENERAL | 12.8090 | 331.66 | 4248.21 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 46.75 |
DINING_FLR_6_LIGHTS | DINING_FLR_6 | DINING_FLR_6 | GENERAL | 12.8090 | 331.66 | 4248.21 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 46.75 |
KITCHEN_FLR_6_LIGHTS | KITCHEN_FLR_6 | KITCHEN_FLR_6 | GENERAL | 10.9792 | 103.30 | 1134.20 | LightsWired | LTG_SCH_KITCHEN | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 12.48 |
CORRIDOR_FLR_6_LIGHTS | CORRIDOR_FLR_6 | CORRIDOR_FLR_6 | GENERAL | 3.6597 | 412.12 | 1508.26 | LightsWired | LTG_SCH_CORRIDOR | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 16.60 |
Interior Lighting Total | 8.9207 | 11345.29 | 101207.97 | 559.10 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR FACADE LIGHTING | 16690.39 | AstronomicalClock | - | 83.85 | 83.85 | 262.70 | |
Exterior Lighting Total | 16690.39 | 262.70 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:58:09
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
HEATSYS1 BOILER | Boiler:HotWater | 240311.47 | 0.80 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:EIR | 1464401.58 | 2.80 | 1464658.98 | 2.80 | 3.72 | 12.68 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 15414.70 | 21957.96 | 17388.36 | 4569.59 | 0.79 | - | 2422.43 | 24.57 |
ROOM_2_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 15158.78 | 21589.60 | 17094.74 | 4494.86 | 0.79 | - | 2381.74 | 24.16 |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 96372.76 | 138128.95 | 109818.68 | 28310.27 | 0.80 | - | 15250.15 | 154.68 |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 104401.67 | 147433.11 | 116116.64 | 31316.46 | 0.79 | - | 16249.85 | 164.81 |
ROOM_5_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 13962.91 | 19865.47 | 15719.03 | 4146.44 | 0.79 | - | 2191.27 | 22.23 |
ROOM_6_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 13720.18 | 19515.97 | 15440.40 | 4075.57 | 0.79 | - | 2152.67 | 21.83 |
ROOM_1_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 4198.34 | 5985.93 | 4742.99 | 1242.94 | 0.79 | - | 660.45 | 6.70 |
ROOM_2_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 4131.23 | 5889.29 | 4665.94 | 1223.35 | 0.79 | - | 649.77 | 6.59 |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 20312.69 | 28845.15 | 22797.24 | 6047.91 | 0.79 | - | 3181.11 | 32.26 |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | 1083772.56 | 739424.02 | 480727.82 | 258696.20 | 0.65 | - | 84057.47 | 852.56 |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | 92321.21 | 62973.74 | 41190.39 | 21783.35 | 0.65 | - | 6855.01 | 69.53 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
BASEMENT VAV BOX REHEAT COIL | Coil:Heating:Water | 15242.62 | 15321.34 | - |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 3231.93 | 3248.18 | - |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1730.88 | 1739.72 | - |
MECH_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 2204.96 | 2216.14 | - |
STORAGE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1171.70 | 1177.62 | - |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 18371.26 | 18465.89 | - |
CAFE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 11194.77 | 11251.63 | - |
LOBBY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 32825.24 | 32992.91 | - |
ROOM_1_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 2586.65 | 2785.30 | - |
ROOM_2_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 2584.69 | 2783.19 | - |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 19405.55 | 20895.95 | - |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 19410.86 | 20901.66 | - |
ROOM_5_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 2590.21 | 2789.13 | - |
ROOM_6_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 2588.25 | 2787.02 | - |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 11495.13 | 11552.87 | - |
ROOM_1_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 815.09 | 877.70 | - |
ROOM_2_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 814.77 | 877.36 | - |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 3967.86 | 4272.66 | - |
BANQUET_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 15392.13 | 15470.75 | - |
DINING_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 15871.77 | 15952.91 | - |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 12416.40 | 12480.53 | - |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 7354.89 | 7391.66 | - |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | 34066.70 | 32263.52 | - |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | 2977.14 | 2819.56 | - |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
LAUNDRY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 0.16 | 125.00 | 0.24 | 184.35 | 781.25 | 1.00 | 1.15 | General | ||
LOBBY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | General | |||
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.16 | 270.90 | 1.26 | 2125.71 | 1693.12 | 1.00 | 0.48 | General | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:10:00 |
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.16 | 270.90 | 1.23 | 2089.41 | 1693.12 | 1.00 | 0.48 | General | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:10:00 |
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.16 | 270.90 | 7.98 | 13517.34 | 1693.12 | 1.00 | 0.39 | General | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:20:00 |
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.16 | 270.90 | 8.31 | 14061.79 | 1693.12 | 1.00 | 0.39 | General | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 |
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.16 | 270.90 | 1.13 | 1919.04 | 1693.12 | 1.00 | 0.49 | General | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 10:50:00 |
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.16 | 270.90 | 1.11 | 1884.58 | 1693.12 | 1.00 | 0.49 | General | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 10:30:00 |
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.16 | 270.90 | 0.34 | 580.41 | 1693.12 | 1.00 | 0.68 | General | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:00:00 |
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.16 | 270.90 | 0.34 | 570.88 | 1693.12 | 1.00 | 0.68 | General | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:10:00 |
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.16 | 270.90 | 1.64 | 2777.45 | 1693.12 | 1.00 | 0.46 | General | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:20:00 |
BANQUET_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | General | |||
DINING_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | General | |||
KITCHEN_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 0.16 | 125.00 | 1.89 | 1474.84 | 781.25 | 1.00 | 0.62 | General | ||
VAV WITH REHEAT FAN | Fan:VariableVolume | 0.62 | 1389.42 | 23.47 | 52593.90 | 2240.64 | 1.00 | 1.11 | General | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 |
FLR_3_DOAS FAN | Fan:ConstantVolume | 0.58 | 622.50 | 2.05 | 2194.93 | 1070.05 | 1.00 | 1.30 | General | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 133527.72 | 0.052282 | 10773.42 | 206062.94 | 0.90 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.002102 | 633.14 | 301156.09 | 0.90 | General |
COOLSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 92445.74 | 0.052282 | 7458.80 | 142664.32 | 0.90 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000375 | 47.91 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWH BOOSTER E WATER HEATER | WaterHeater:Mixed | 0.02 | 8000.00 | 1.00 | 1.24 | 1.15 |
SWH LAUNDRY G WATER HEATER | WaterHeater:Mixed | 1.14 | 163316.00 | 0.80 | 0.58 | 0.51 |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 2.27 | 175842.60 | 0.80 | 0.26 | 0.03 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:58:09
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 39892.39 | 39892.39 | 20.16 | 2.900 | 2.900 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 20:20:00 | 24.00 | 24.00 | 0.00910 | 37.66 | 0.01077 | 0.854 | 0.00 |
RETAIL_1_FLR_1 | 5531.90 | 5531.90 | 82.48 | 0.402 | 0.402 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 24.00 | 24.00 | 0.00901 | 42.80 | 0.01078 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 3645.00 | 3645.00 | 46.93 | 0.265 | 0.265 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:50:00 | 24.00 | 24.00 | 0.00931 | 41.57 | 0.01078 | 0.092 | 0.00 |
MECH_FLR_1 | 4200.26 | 4200.26 | 25.57 | 0.305 | 0.305 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | 24.00 | 24.00 | 0.00874 | 40.47 | 0.01078 | 0.000 | 0.00 |
STORAGE_FLR_1 | 2141.71 | 2141.71 | 22.60 | 0.156 | 0.156 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:00:00 | 24.00 | 24.00 | 0.00882 | 42.22 | 0.01078 | 0.058 | 0.00 |
LAUNDRY_FLR_1 | 45664.21 | 45664.21 | 585.14 | 3.319 | 3.319 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:10:00 | 24.00 | 24.00 | 0.00856 | 42.09 | 0.01078 | 0.000 | 0.00 |
CAFE_FLR_1 | 21934.85 | 21934.85 | 116.14 | 1.596 | 1.596 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 24.00 | 23.99 | 0.00998 | 42.80 | 0.01078 | 0.676 | 0.00 |
LOBBY_FLR_1 | 70276.11 | 70276.11 | 53.72 | 5.110 | 5.110 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:20:00 | 24.00 | 23.99 | 0.00988 | 42.80 | 0.01078 | 1.894 | 0.00 |
ROOM_1_FLR_3 | 12816.85 | 12816.85 | 328.45 | 1.255 | 1.255 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:10:00 | 21.11 | 21.11 | 0.00862 | 42.09 | 0.01078 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 12597.98 | 12597.98 | 322.88 | 1.234 | 1.234 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:10:00 | 21.11 | 21.11 | 0.00862 | 42.09 | 0.01078 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 81507.72 | 81507.72 | 3323.61 | 7.984 | 7.984 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:20:00 | 21.11 | 21.11 | 0.00856 | 42.80 | 0.01078 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 84784.52 | 84784.52 | 3456.28 | 8.305 | 8.305 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 | 21.11 | 21.11 | 0.00872 | 42.61 | 0.01078 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 11570.74 | 11570.74 | 296.52 | 1.133 | 1.133 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 10:50:00 | 21.11 | 21.11 | 0.00864 | 40.33 | 0.01078 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 11362.99 | 11362.99 | 291.23 | 1.113 | 1.113 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 10:30:00 | 21.11 | 21.11 | 0.00864 | 39.84 | 0.01078 | 0.062 | 0.00 |
CORRIDOR_FLR_3 | 19311.63 | 19311.63 | 49.59 | 1.404 | 1.404 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 24.00 | 24.00 | 0.00953 | 42.70 | 0.01078 | 0.475 | 0.00 |
ROOM_1_FLR_6 | 3499.56 | 3499.56 | 89.68 | 0.343 | 0.343 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:00:00 | 21.11 | 21.11 | 0.00861 | 42.22 | 0.01078 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 3442.09 | 3442.09 | 88.22 | 0.337 | 0.337 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:10:00 | 21.11 | 21.11 | 0.00861 | 42.09 | 0.01078 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 16746.24 | 16746.24 | 682.67 | 1.640 | 1.640 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:20:00 | 21.11 | 21.11 | 0.00866 | 42.80 | 0.01078 | 0.099 | 0.00 |
BANQUET_FLR_6 | 32927.26 | 32927.26 | 99.28 | 2.396 | 2.396 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 24.00 | 23.99 | 0.01022 | 42.80 | 0.01078 | 1.188 | 0.00 |
DINING_FLR_6 | 34451.11 | 34451.11 | 103.88 | 2.507 | 2.507 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 24.00 | 23.99 | 0.01015 | 42.80 | 0.01078 | 1.188 | 0.00 |
KITCHEN_FLR_6 | 32412.31 | 32412.31 | 313.76 | 2.362 | 2.362 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 12:30:00 | 24.00 | 23.97 | 0.01000 | 41.93 | 0.01078 | 0.367 | 0.00 |
CORRIDOR_FLR_6 | 11605.01 | 11605.01 | 28.16 | 0.844 | 0.844 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 24.00 | 24.00 | 0.00898 | 42.80 | 0.01078 | 0.126 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 0.854 | 00:10:00 | 21.00 | 24.00 | 0.00851 | 12.70 | 0.00915 | 0.854 | 0.00 | |
RETAIL_1_FLR_1 | 1116.63 | 1116.63 | 16.65 | 0.048 | 0.079 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | 21.00 | 21.00 | 0.00831 | 12.70 | 0.00915 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 337.01 | 337.01 | 4.34 | 0.014 | 0.092 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | 21.00 | 21.00 | 0.00837 | 12.70 | 0.00915 | 0.092 | 0.00 |
MECH_FLR_1 | 598.87 | 598.87 | 3.65 | 0.026 | 0.026 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | 21.00 | 21.00 | 0.00845 | 12.70 | 0.00915 | 0.000 | 0.00 |
STORAGE_FLR_1 | 352.75 | 352.75 | 3.72 | 0.015 | 0.058 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | 21.00 | 21.00 | 0.00844 | 12.70 | 0.00915 | 0.058 | 0.00 |
LAUNDRY_FLR_1 | 908.49 | 908.49 | 11.64 | 0.039 | 0.039 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | 21.00 | 21.00 | 0.00842 | 12.70 | 0.00915 | 0.000 | 0.00 |
CAFE_FLR_1 | 2801.17 | 2801.17 | 14.83 | 0.120 | 0.676 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | 21.00 | 21.00 | 0.00828 | 12.70 | 0.00915 | 0.676 | 0.00 |
LOBBY_FLR_1 | 5944.89 | 5944.89 | 4.54 | 0.255 | 1.894 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | 21.00 | 21.00 | 0.00835 | 12.70 | 0.00915 | 1.894 | 0.00 |
ROOM_1_FLR_3 | 2586.63 | 2586.63 | 66.29 | 0.112 | 0.112 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | 21.11 | 21.11 | 0.00831 | 12.70 | 0.00915 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 2584.68 | 2584.68 | 66.24 | 0.111 | 0.111 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | 21.11 | 21.11 | 0.00831 | 12.70 | 0.00915 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 15172.27 | 15172.27 | 618.67 | 0.654 | 0.837 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | 21.11 | 21.11 | 0.00829 | 12.70 | 0.00915 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 15149.16 | 15149.16 | 617.56 | 0.653 | 0.837 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | 21.11 | 21.11 | 0.00829 | 12.70 | 0.00915 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 2590.19 | 2590.19 | 66.38 | 0.112 | 0.112 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | 21.11 | 21.11 | 0.00831 | 12.70 | 0.00915 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 2588.23 | 2588.23 | 66.34 | 0.112 | 0.112 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | 21.11 | 21.11 | 0.00831 | 12.70 | 0.00915 | 0.062 | 0.00 |
CORRIDOR_FLR_3 | 4112.82 | 4112.82 | 10.56 | 0.176 | 0.475 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00826 | 12.70 | 0.00915 | 0.475 | 0.00 |
ROOM_1_FLR_6 | 815.08 | 815.08 | 20.89 | 0.035 | 0.035 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | 21.11 | 21.11 | 0.00826 | 12.70 | 0.00915 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 814.76 | 814.76 | 20.88 | 0.035 | 0.035 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | 21.11 | 21.11 | 0.00826 | 12.70 | 0.00915 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 3967.84 | 3967.84 | 161.75 | 0.171 | 0.171 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | 21.11 | 21.11 | 0.00825 | 12.70 | 0.00915 | 0.099 | 0.00 |
BANQUET_FLR_6 | 2791.02 | 2791.02 | 8.42 | 0.120 | 1.188 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | 21.00 | 21.00 | 0.00820 | 12.70 | 0.00915 | 1.188 | 0.00 |
DINING_FLR_6 | 2687.30 | 2687.30 | 8.10 | 0.115 | 1.188 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00821 | 12.70 | 0.00915 | 1.188 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.367 | 00:10:00 | 21.00 | 24.00 | 0.00803 | 12.70 | 0.00915 | 0.367 | 0.00 | |
CORRIDOR_FLR_6 | 2919.25 | 2919.25 | 7.08 | 0.125 | 0.126 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00817 | 12.70 | 0.00915 | 0.126 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV WITH REHEAT | 23.47 | 23.47 | 7.06 | 7.06 | 23.4727 | 23.4727 | 23.4727 | 1.0000 | 0.3000 |
FLR_3_DOAS | 23.07 | 2.05 | 2.36 | 2.05 | 2.0513 | 2.0513 | 2.0513 | 1.0000 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
BASEMENT VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | 15242.618 | 15242.618 | 2.888241 | 0.00013335 | 317.859 | 1/21 00:10:00 | 1/21 00:10:00 | 15242.62 | 15242.62 | 2.888241 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00800000 | 51.6928 | 0.00 | 0.00 | 15328.29 | 15328.29 | ||
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | 3231.925 | 3231.925 | 0.400565 | 0.00002827 | 69.301 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | 3231.93 | 3231.93 | 0.400565 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00831300 | 53.6878 | 1116.63 | 0.00 | 3249.92 | 3249.92 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | 1730.884 | 1730.884 | 0.263933 | 0.00001514 | 36.555 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | 1730.88 | 1730.88 | 0.263933 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00837220 | 54.0656 | 337.01 | 0.00 | 1740.57 | 1740.57 |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | 2204.964 | 2204.964 | 0.304077 | 0.00001929 | 46.891 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | 2204.96 | 2204.96 | 0.304077 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00844743 | 54.5449 | 598.87 | 0.00 | 2217.27 | 2217.27 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | 1171.699 | 1171.699 | 0.155050 | 0.00001025 | 24.995 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | 1171.70 | 1171.70 | 0.155050 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00844176 | 54.5088 | 352.75 | 0.00 | 1178.23 | 1178.23 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 18371.259 | 18371.259 | 3.306217 | 0.00016072 | 384.154 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | 18371.26 | 18371.26 | 3.306217 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00841886 | 54.3624 | 908.49 | 0.00 | 18474.41 | 18474.41 |
CAFE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | 11194.773 | 11194.773 | 1.589557 | 0.00009794 | 237.573 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | 11194.77 | 11194.77 | 1.589557 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00828500 | 53.5095 | 2801.17 | 0.00 | 11257.31 | 11257.31 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 32825.242 | 32825.242 | 5.090031 | 0.00028717 | 692.488 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | 32825.24 | 32825.24 | 5.090031 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00835351 | 53.9465 | 5944.89 | 0.00 | 33008.98 | 33008.98 |
ROOM_1_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 15414.701 | -999.000 | 1.255494 | 0.00055057 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:10:00 | unknown | 8/21 16:10:00 | 15414.70 | 14993.08 | 1.255494 | 22.49 | 15.95 | 0.00862300 | 12.80 | 12.09 | 0.00850000 | 42.09 | 0.01078059 | 23.67 | 0.0000 | 21.11 | 0.00862300 | 55.2876 | 12816.85 | 0.00 | 15433.47 | 14781.44 |
ROOM_1_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 2586.652 | 2586.652 | 0.111578 | 0.00002263 | 73.885 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | 2586.65 | 2586.65 | 0.111578 | 21.11 | 15.17 | 0.00831218 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.11 | 0.00831218 | 53.3175 | 2586.63 | 0.00 | 2788.52 | 2788.52 |
ROOM_2_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 15158.780 | -999.000 | 1.234054 | 0.00054143 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:10:00 | unknown | 8/21 16:10:00 | 15158.78 | 14737.80 | 1.234054 | 22.49 | 15.95 | 0.00862494 | 12.80 | 12.09 | 0.00850000 | 42.09 | 0.01078059 | 23.67 | 0.0000 | 21.11 | 0.00862494 | 55.2998 | 12597.98 | 0.00 | 15177.23 | 14530.15 |
ROOM_2_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 2584.694 | 2584.694 | 0.111493 | 0.00002261 | 73.829 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | 2584.69 | 2584.69 | 0.111493 | 21.11 | 15.17 | 0.00831233 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.11 | 0.00831233 | 53.3185 | 2584.68 | 0.00 | 2786.41 | 2786.41 |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 96372.760 | -999.000 | 7.983661 | 0.00344215 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:20:00 | unknown | 8/21 14:20:00 | 96372.76 | 95171.47 | 7.983661 | 22.49 | 15.89 | 0.00855521 | 12.80 | 12.09 | 0.00850000 | 42.80 | 0.01078182 | 23.86 | 0.0000 | 21.11 | 0.00855521 | 54.8569 | 81507.72 | 0.00 | 96491.94 | 93738.06 |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 19405.551 | 19405.551 | 0.837072 | 0.00016977 | 554.303 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | 19405.55 | 19405.55 | 0.837072 | 21.11 | 15.15 | 0.00828969 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.11 | 0.00828969 | 53.1757 | 15172.27 | 0.00 | 20919.94 | 20919.94 |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 104401.669 | -999.000 | 8.305226 | 0.00372892 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 | unknown | 8/21 15:20:00 | 104401.67 | 99428.19 | 8.305226 | 22.49 | 16.03 | 0.00871878 | 12.80 | 12.09 | 0.00850000 | 42.61 | 0.01078148 | 23.81 | 0.0000 | 21.11 | 0.00871878 | 55.8933 | 84784.52 | 0.00 | 104526.11 | 98152.30 |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 19410.858 | 19410.858 | 0.837300 | 0.00016981 | 554.455 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | 19410.86 | 19410.86 | 0.837300 | 21.11 | 15.15 | 0.00829008 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.11 | 0.00829008 | 53.1782 | 15149.16 | 0.00 | 20925.66 | 20925.66 |
ROOM_5_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 13962.913 | -999.000 | 1.133430 | 0.00049871 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 10:50:00 | unknown | 8/21 10:50:00 | 13962.91 | 13540.26 | 1.133430 | 22.49 | 15.96 | 0.00863653 | 12.80 | 12.09 | 0.00850000 | 40.33 | 0.01077755 | 23.19 | 0.0000 | 21.11 | 0.00863653 | 55.3732 | 11570.74 | 0.00 | 13979.86 | 13351.62 |
ROOM_5_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 2590.212 | 2590.212 | 0.111731 | 0.00002266 | 73.986 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | 2590.21 | 2590.21 | 0.111731 | 21.11 | 15.17 | 0.00831186 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.11 | 0.00831186 | 53.3155 | 2590.19 | 0.00 | 2792.36 | 2792.36 |
ROOM_6_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 13720.180 | -999.000 | 1.113080 | 0.00049004 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 10:30:00 | unknown | 8/21 10:30:00 | 13720.18 | 13297.97 | 1.113080 | 22.49 | 15.96 | 0.00863887 | 12.80 | 12.09 | 0.00850000 | 39.84 | 0.01077673 | 23.05 | 0.0000 | 21.11 | 0.00863887 | 55.3880 | 11362.99 | 0.00 | 13736.82 | 13113.13 |
ROOM_6_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 2588.251 | 2588.251 | 0.111647 | 0.00002264 | 73.930 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | 2588.25 | 2588.25 | 0.111647 | 21.11 | 15.17 | 0.00831202 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.11 | 0.00831202 | 53.3165 | 2588.23 | 0.00 | 2790.24 | 2790.24 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | 11495.128 | 11495.128 | 1.398157 | 0.00010056 | 246.872 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 11495.13 | 11495.13 | 1.398157 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00825560 | 53.3225 | 4112.82 | 0.00 | 11559.10 | 11559.10 |
ROOM_1_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 4198.341 | -999.000 | 0.342804 | 0.00014995 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:00:00 | unknown | 8/21 16:00:00 | 4198.34 | 4092.67 | 0.342804 | 22.49 | 15.94 | 0.00861294 | 12.80 | 12.09 | 0.00850000 | 42.22 | 0.01078081 | 23.70 | 0.0000 | 21.11 | 0.00861294 | 55.2239 | 3499.56 | 0.00 | 4203.46 | 4034.33 |
ROOM_1_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 815.089 | 815.089 | 0.035160 | 0.00000713 | 23.283 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | 815.09 | 815.09 | 0.035160 | 21.11 | 15.12 | 0.00826238 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.11 | 0.00826238 | 53.0022 | 815.08 | 0.00 | 878.70 | 878.70 |
ROOM_2_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 4131.226 | -999.000 | 0.337175 | 0.00014756 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:10:00 | unknown | 8/21 16:10:00 | 4131.23 | 4025.65 | 0.337175 | 22.49 | 15.94 | 0.00861471 | 12.80 | 12.09 | 0.00850000 | 42.09 | 0.01078059 | 23.67 | 0.0000 | 21.11 | 0.00861471 | 55.2351 | 3442.09 | 0.00 | 4136.26 | 3968.37 |
ROOM_2_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 814.769 | 814.769 | 0.035146 | 0.00000713 | 23.274 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | 814.77 | 814.77 | 0.035146 | 21.11 | 15.12 | 0.00826244 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.11 | 0.00826244 | 53.0026 | 814.76 | 0.00 | 878.36 | 878.36 |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 20312.689 | -999.000 | 1.640426 | 0.00072551 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:20:00 | unknown | 8/21 14:20:00 | 20312.69 | 19607.47 | 1.640426 | 22.49 | 15.98 | 0.00865732 | 12.80 | 12.09 | 0.00850000 | 42.80 | 0.01078182 | 23.86 | 0.0000 | 21.11 | 0.00865732 | 55.5050 | 16746.24 | 0.00 | 20337.23 | 19339.83 |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 3967.858 | 3967.858 | 0.171157 | 0.00003471 | 113.341 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | 3967.86 | 3967.86 | 0.171157 | 21.11 | 15.11 | 0.00825128 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.11 | 0.00825128 | 52.9322 | 3967.84 | 0.00 | 4277.51 | 4277.51 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 15392.132 | 15392.132 | 2.386782 | 0.00013466 | 324.716 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | 15392.13 | 15392.13 | 2.386782 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00820115 | 52.9753 | 2791.02 | 0.00 | 15478.29 | 15478.29 |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 15871.771 | 15871.771 | 2.497207 | 0.00013885 | 334.524 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 15871.77 | 15871.77 | 2.497207 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00820756 | 53.0159 | 2687.30 | 0.00 | 15960.64 | 15960.64 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 12416.403 | 12416.403 | 2.352717 | 0.00010862 | 258.923 | 1/21 00:10:00 | 1/21 00:10:00 | 12416.40 | 12416.40 | 2.352717 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00800000 | 51.6928 | 0.00 | 0.00 | 12486.19 | 12486.19 | ||
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | 7354.892 | 7354.892 | 0.840195 | 0.00006434 | 158.817 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 7354.89 | 7354.89 | 0.840195 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00817344 | 52.7986 | 2919.25 | 0.00 | 7395.75 | 7395.75 |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV WITH REHEAT | 1083772.561 | -999.000 | 23.472728 | 0.03870984 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 1083772.56 | 914686.40 | 23.472728 | 42.80 | 23.86 | 0.01078182 | 10.98 | 10.98 | 0.00850000 | 42.80 | 0.01078182 | 23.86 | 99.9676 | 23.99 | 0.00957469 | 51.4524 | 322596.10 | 0.00 | 1084952.64 | 900829.49 |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV WITH REHEAT | 34066.705 | 34066.705 | 7.041818 | 0.00029803 | 652.398 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | 34066.70 | 34066.70 | 7.041818 | 12.70 | 12.70 | 0.00915345 | 16.70 | 13.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 333.2254 | 23.08 | 0.00831288 | 47.2788 | 24569.38 | 0.00 | 39068.31 | 39068.31 |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | FLR_3_DOAS | 92321.212 | -999.000 | 2.051317 | 0.00329750 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 92321.21 | 77917.60 | 2.051317 | 42.80 | 23.86 | 0.01078182 | 11.93 | 11.73 | 0.00850000 | 42.80 | 0.01078182 | 23.86 | 99.9965 | 21.11 | 0.00863912 | 55.3887 | 235370.24 | 0.00 | 92413.81 | 77447.65 |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | FLR_3_DOAS | 2977.141 | 2977.141 | 0.615395 | 0.00002605 | 57.014 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | 2977.14 | 2977.14 | 0.615395 | 12.70 | 12.70 | 0.00915345 | 16.70 | 13.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 333.3216 | 21.11 | 0.00828968 | 53.1756 | 46268.86 | 0.00 | 3414.24 | 3414.24 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:58:09
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
BASEMENT VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | BASEMENT | N/A | N/A | N/A | Yes | Yes | Yes | No | 15242.618 | 15242.618 | 2.888241 | 0.00013335 | 317.859 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.10213513 | 54.44 | 82.22 | 27.78 | 245147.84 | 6.2177 | 6.342859 | 1/21 00:10:00 | unknown | unknown | 1/21 00:10:00 | Sensible | 15242.62 | 15242.62 | 1.0000 | 3.47627202 | 2.888241 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.13333547 | 60.00 | 32.22 | 27.78 | 0.000 | 15242.62 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 51.6928 | 0.00 | 0.00 | 15328.29 | 15328.29 | 3.47627202 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 20.92 | 14.82 | 0.00800000 | 41344.1 | |||
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | RETAIL_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3231.925 | 3231.925 | 0.400565 | 0.00002827 | 69.301 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.10213513 | 54.44 | 82.22 | 27.78 | 245147.84 | 1.3184 | 1.344890 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | Sensible | 3231.93 | 3231.93 | 1.0000 | 0.48211764 | 0.400565 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.02827141 | 60.00 | 32.22 | 27.78 | 0.000 | 3231.93 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 21.00 | 0.00831300 | 21.00 | 0.00831300 | 53.6878 | 1116.63 | 0.00 | 3249.92 | 3249.92 | 0.48211764 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 23.21 | 15.67 | 0.00800000 | 43675.7 | |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | RETAIL_2_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1730.884 | 1730.884 | 0.263933 | 0.00001514 | 36.555 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.10213513 | 54.44 | 82.22 | 27.78 | 245147.84 | 0.7061 | 0.720267 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | Sensible | 1730.88 | 1730.88 | 1.0000 | 0.31766862 | 0.263933 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.01514098 | 60.00 | 32.22 | 27.78 | 0.000 | 1730.88 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 21.00 | 0.00837220 | 21.00 | 0.00837220 | 54.0656 | 337.01 | 0.00 | 1740.57 | 1740.57 | 0.31766862 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 21.97 | 15.21 | 0.00800000 | 42413.9 | |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | MECH_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2204.964 | 2204.964 | 0.304077 | 0.00001929 | 46.891 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.10213513 | 54.44 | 82.22 | 27.78 | 245147.84 | 0.8994 | 0.917544 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | Sensible | 2204.96 | 2204.96 | 1.0000 | 0.36598502 | 0.304077 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.01928802 | 60.00 | 32.22 | 27.78 | 0.000 | 2204.96 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 21.00 | 0.00844743 | 21.00 | 0.00844743 | 54.5449 | 598.87 | 0.00 | 2217.27 | 2217.27 | 0.36598502 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 22.54 | 15.42 | 0.00800000 | 42993.1 | |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | STORAGE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1171.699 | 1171.699 | 0.155050 | 0.00001025 | 24.995 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.10213513 | 54.44 | 82.22 | 27.78 | 245147.84 | 0.4780 | 0.487575 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | Sensible | 1171.70 | 1171.70 | 1.0000 | 0.18661732 | 0.155050 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.01024949 | 60.00 | 32.22 | 27.78 | 0.000 | 1171.70 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 21.00 | 0.00844176 | 21.00 | 0.00844176 | 54.5088 | 352.75 | 0.00 | 1178.23 | 1178.23 | 0.18661732 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 22.79 | 15.52 | 0.00800000 | 43248.4 | |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LAUNDRY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 18371.259 | 18371.259 | 3.306217 | 0.00016072 | 384.154 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.10213513 | 54.44 | 82.22 | 27.78 | 245147.84 | 7.4940 | 7.644770 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | Sensible | 18371.26 | 18371.26 | 1.0000 | 3.97934675 | 3.306217 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.16070339 | 60.00 | 32.22 | 27.78 | 0.000 | 18371.26 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 21.00 | 0.00841886 | 21.00 | 0.00841886 | 54.3624 | 908.49 | 0.00 | 18474.41 | 18474.41 | 3.97934675 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 21.15 | 14.91 | 0.00800000 | 41577.3 | |
CAFE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | CAFE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11194.773 | 11194.773 | 1.589557 | 0.00009794 | 237.573 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.10213513 | 54.44 | 82.22 | 27.78 | 245147.84 | 4.5665 | 4.658443 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | Sensible | 11194.77 | 11194.77 | 1.0000 | 1.91318261 | 1.589557 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.09792677 | 60.00 | 32.22 | 27.78 | 0.000 | 11194.77 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 21.00 | 0.00828500 | 21.00 | 0.00828500 | 53.5095 | 2801.17 | 0.00 | 11257.31 | 11257.31 | 1.91318261 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 22.37 | 15.36 | 0.00800000 | 42818.8 | |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LOBBY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 32825.242 | 32825.242 | 5.090031 | 0.00028717 | 692.488 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.10213513 | 54.44 | 82.22 | 27.78 | 245147.84 | 13.3900 | 13.659457 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | Sensible | 32825.24 | 32825.24 | 1.0000 | 6.12633550 | 5.090031 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.28714024 | 60.00 | 32.22 | 27.78 | 0.000 | 32825.24 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 21.00 | 0.00835351 | 21.00 | 0.00835351 | 53.9465 | 5944.89 | 0.00 | 33008.98 | 33008.98 | 6.12633550 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 21.88 | 15.18 | 0.00800000 | 42322.8 | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 15414.701 | -999.000 | 1.255494 | 0.00055057 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8697 | 1004.8586 | 1.2036 | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.255494 | 1.51110606 | 4197.9300 | 999.8980 | 52.27684156 | 13.37 | 6.70 | 6.67 | 1463761.66 | 1.0531 | 1.053068 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:10:00 | unknown | unknown | unknown | 8/21 16:10:00 | Sensible | 15414.70 | 14993.08 | 1.0000 | 1.51110606 | 1.255494 | 22.49 | 15.95 | 0.00862300 | 44523.1 | 12.80 | 12.09 | 0.00850000 | 34322.2 | 0.55051094 | 6.70 | 13.37 | 6.67 | 0.000 | 15414.70 | 42.09 | 0.01078059 | 23.67 | 0.00000000 | 0.0000 | 21.11 | 0.00862300 | 21.11 | 0.00862300 | 55.2876 | 12816.85 | 0.00 | 15433.47 | 14781.44 | 1.51110606 | 22.49 | 15.95 | 0.00862300 | 44523.1 | 12.91 | 12.10 | 0.00845211 | 34309.8 | |
ROOM_1_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2586.652 | 2586.652 | 0.111578 | 0.00002263 | 73.885 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.255494 | 1.51110606 | 4197.9300 | 999.8980 | 2.10213513 | 54.44 | 82.22 | 27.78 | 245147.84 | 1.0551 | 1.076375 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | Sensible | 2586.65 | 2586.65 | 1.0000 | 0.13429463 | 0.111578 | 21.11 | 15.17 | 0.00831218 | 42327.9 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.02262685 | 60.00 | 32.22 | 27.78 | 0.000 | 2586.65 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 21.11 | 0.00831218 | 21.11 | 0.00831218 | 53.3175 | 2586.63 | 0.00 | 2788.52 | 2788.52 | 0.13429463 | 16.60 | 13.45 | 0.00831218 | 37725.1 | 36.95 | 20.50 | 0.00831218 | 58489.3 | |
ROOM_2_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 15158.780 | -999.000 | 1.234054 | 0.00054143 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8733 | 1004.8586 | 1.2036 | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.234054 | 1.48530117 | 4197.9300 | 999.8980 | 52.27684156 | 13.37 | 6.70 | 6.67 | 1463761.66 | 1.0356 | 1.035585 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:10:00 | unknown | unknown | unknown | 8/21 16:10:00 | Sensible | 15158.78 | 14737.80 | 1.0000 | 1.48530117 | 1.234054 | 22.49 | 15.95 | 0.00862494 | 44528.1 | 12.80 | 12.09 | 0.00850000 | 34322.2 | 0.54137114 | 6.70 | 13.37 | 6.67 | 0.000 | 15158.78 | 42.09 | 0.01078059 | 23.67 | 0.00000000 | 0.0000 | 21.11 | 0.00862494 | 21.11 | 0.00862494 | 55.2998 | 12597.98 | 0.00 | 15177.23 | 14530.15 | 1.48530117 | 22.49 | 15.96 | 0.00862494 | 44528.1 | 12.91 | 12.10 | 0.00845240 | 34309.8 | |
ROOM_2_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2584.694 | 2584.694 | 0.111493 | 0.00002261 | 73.829 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.234054 | 1.48530117 | 4197.9300 | 999.8980 | 2.10213513 | 54.44 | 82.22 | 27.78 | 245147.84 | 1.0543 | 1.075560 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | Sensible | 2584.69 | 2584.69 | 1.0000 | 0.13419296 | 0.111493 | 21.11 | 15.17 | 0.00831233 | 42328.3 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.02260972 | 60.00 | 32.22 | 27.78 | 0.000 | 2584.69 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 21.11 | 0.00831233 | 21.11 | 0.00831233 | 53.3185 | 2584.68 | 0.00 | 2786.41 | 2786.41 | 0.13419296 | 16.60 | 13.45 | 0.00831233 | 37725.5 | 36.95 | 20.50 | 0.00831233 | 58489.7 | |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 96372.760 | -999.000 | 7.983661 | 0.00344215 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7437 | 1004.8586 | 1.2036 | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 7.983661 | 9.60909475 | 4197.9300 | 999.8980 | 52.27684156 | 13.37 | 6.70 | 6.67 | 1463761.66 | 6.5839 | 6.583788 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:20:00 | unknown | unknown | unknown | 8/21 14:20:00 | Sensible | 96372.76 | 95171.47 | 1.0000 | 9.60909475 | 7.983661 | 22.49 | 15.89 | 0.00855521 | 44351.5 | 12.80 | 12.09 | 0.00850000 | 34322.2 | 3.44179628 | 6.70 | 13.37 | 6.67 | 0.000 | 96372.76 | 42.80 | 0.01078182 | 23.86 | 0.00000000 | 0.0000 | 21.11 | 0.00855521 | 21.11 | 0.00855521 | 54.8569 | 81507.72 | 0.00 | 96491.94 | 93738.06 | 9.60909475 | 22.49 | 15.90 | 0.00855521 | 44351.5 | 12.93 | 12.10 | 0.00844171 | 34309.8 | |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 19405.551 | 19405.551 | 0.837072 | 0.00016977 | 554.303 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 7.983661 | 9.60909475 | 4197.9300 | 999.8980 | 2.10213513 | 54.44 | 82.22 | 27.78 | 245147.84 | 7.9159 | 8.075166 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | Sensible | 19405.55 | 19405.55 | 1.0000 | 1.00749507 | 0.837072 | 21.11 | 15.15 | 0.00828969 | 42270.7 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.16975091 | 60.00 | 32.22 | 27.78 | 0.000 | 19405.55 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 21.11 | 0.00828969 | 21.11 | 0.00828969 | 53.1757 | 15172.27 | 0.00 | 20919.94 | 20919.94 | 1.00749507 | 16.60 | 13.43 | 0.00828969 | 37668.2 | 36.95 | 20.48 | 0.00828969 | 58432.5 | |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 104401.669 | -999.000 | 8.305226 | 0.00372892 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.0478 | 1004.8586 | 1.2036 | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 8.305226 | 9.99612829 | 4197.9300 | 999.8980 | 52.27684156 | 13.37 | 6.70 | 6.67 | 1463761.66 | 7.1324 | 7.132290 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 | unknown | unknown | unknown | 8/21 15:20:00 | Sensible | 104401.67 | 99428.19 | 1.0000 | 9.99612829 | 8.305226 | 22.49 | 16.03 | 0.00871878 | 44766.4 | 12.80 | 12.09 | 0.00850000 | 34322.2 | 3.72853569 | 6.70 | 13.37 | 6.67 | 0.000 | 104401.67 | 42.61 | 0.01078148 | 23.81 | 0.00000000 | 0.0000 | 21.11 | 0.00871878 | 21.11 | 0.00871878 | 55.8933 | 84784.52 | 0.00 | 104526.11 | 98152.30 | 9.99612829 | 22.49 | 16.04 | 0.00871878 | 44766.4 | 12.87 | 12.10 | 0.00846624 | 34309.7 | |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 19410.858 | 19410.858 | 0.837300 | 0.00016981 | 554.455 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 8.305226 | 9.99612829 | 4197.9300 | 999.8980 | 2.10213513 | 54.44 | 82.22 | 27.78 | 245147.84 | 7.9180 | 8.077375 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | Sensible | 19410.86 | 19410.86 | 1.0000 | 1.00777057 | 0.837300 | 21.11 | 15.15 | 0.00829008 | 42271.7 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.16979733 | 60.00 | 32.22 | 27.78 | 0.000 | 19410.86 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 21.11 | 0.00829008 | 21.11 | 0.00829008 | 53.1782 | 15149.16 | 0.00 | 20925.66 | 20925.66 | 1.00777057 | 16.60 | 13.43 | 0.00829008 | 37669.2 | 36.95 | 20.48 | 0.00829008 | 58433.5 | |
ROOM_5_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 13962.913 | -999.000 | 1.133430 | 0.00049871 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8949 | 1004.8586 | 1.2036 | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.133430 | 1.36419123 | 4197.9300 | 999.8980 | 52.27684156 | 13.37 | 6.70 | 6.67 | 1463761.66 | 0.9539 | 0.953888 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 10:50:00 | unknown | unknown | unknown | 8/21 10:50:00 | Sensible | 13962.91 | 13540.26 | 1.0000 | 1.36419123 | 1.133430 | 22.49 | 15.96 | 0.00863653 | 44557.5 | 12.80 | 12.09 | 0.00850000 | 34322.2 | 0.49866270 | 6.70 | 13.37 | 6.67 | 0.000 | 13962.91 | 40.33 | 0.01077755 | 23.19 | 0.00000000 | 0.0000 | 21.11 | 0.00863653 | 21.11 | 0.00863653 | 55.3732 | 11570.74 | 0.00 | 13979.86 | 13351.62 | 1.36419123 | 22.49 | 15.97 | 0.00863653 | 44557.5 | 12.90 | 12.10 | 0.00845414 | 34309.8 | |
ROOM_5_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2590.212 | 2590.212 | 0.111731 | 0.00002266 | 73.986 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.133430 | 1.36419123 | 4197.9300 | 999.8980 | 2.10213513 | 54.44 | 82.22 | 27.78 | 245147.84 | 1.0566 | 1.077856 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | Sensible | 2590.21 | 2590.21 | 1.0000 | 0.13447945 | 0.111731 | 21.11 | 15.17 | 0.00831186 | 42327.2 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.02265799 | 60.00 | 32.22 | 27.78 | 0.000 | 2590.21 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 21.11 | 0.00831186 | 21.11 | 0.00831186 | 53.3155 | 2590.19 | 0.00 | 2792.36 | 2792.36 | 0.13447945 | 16.60 | 13.45 | 0.00831186 | 37724.3 | 36.95 | 20.49 | 0.00831186 | 58488.5 | |
ROOM_6_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 13720.180 | -999.000 | 1.113080 | 0.00049004 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8992 | 1004.8586 | 1.2036 | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.113080 | 1.33969778 | 4197.9300 | 999.8980 | 52.27684156 | 13.37 | 6.70 | 6.67 | 1463761.66 | 0.9373 | 0.937306 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 10:30:00 | unknown | unknown | unknown | 8/21 10:30:00 | Sensible | 13720.18 | 13297.97 | 1.0000 | 1.33969778 | 1.113080 | 22.49 | 15.96 | 0.00863887 | 44563.4 | 12.80 | 12.09 | 0.00850000 | 34322.2 | 0.48999389 | 6.70 | 13.37 | 6.67 | 0.000 | 13720.18 | 39.84 | 0.01077673 | 23.05 | 0.00000000 | 0.0000 | 21.11 | 0.00863887 | 21.11 | 0.00863887 | 55.3880 | 11362.99 | 0.00 | 13736.82 | 13113.13 | 1.33969778 | 22.49 | 15.97 | 0.00863887 | 44563.4 | 12.90 | 12.10 | 0.00845449 | 34309.8 | |
ROOM_6_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2588.251 | 2588.251 | 0.111647 | 0.00002264 | 73.930 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.113080 | 1.33969778 | 4197.9300 | 999.8980 | 2.10213513 | 54.44 | 82.22 | 27.78 | 245147.84 | 1.0558 | 1.077040 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | Sensible | 2588.25 | 2588.25 | 1.0000 | 0.13437764 | 0.111647 | 21.11 | 15.17 | 0.00831202 | 42327.5 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.02264084 | 60.00 | 32.22 | 27.78 | 0.000 | 2588.25 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 21.11 | 0.00831202 | 21.11 | 0.00831202 | 53.3165 | 2588.23 | 0.00 | 2790.24 | 2790.24 | 0.13437764 | 16.60 | 13.45 | 0.00831202 | 37724.7 | 36.95 | 20.49 | 0.00831202 | 58488.9 | |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | CORRIDOR_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11495.128 | 11495.128 | 1.398157 | 0.00010056 | 246.872 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.10213513 | 54.44 | 82.22 | 27.78 | 245147.84 | 4.6891 | 4.783429 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 11495.13 | 11495.13 | 1.0000 | 1.68281500 | 1.398157 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.10055414 | 60.00 | 32.22 | 27.78 | 0.000 | 11495.13 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 21.00 | 0.00825560 | 21.00 | 0.00825560 | 53.3225 | 4112.82 | 0.00 | 11559.10 | 11559.10 | 1.68281500 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 23.34 | 15.71 | 0.00800000 | 43803.6 | |
ROOM_1_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 4198.341 | -999.000 | 0.342804 | 0.00014995 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8510 | 1004.8586 | 1.2036 | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.342804 | 0.41259757 | 4197.9300 | 999.8980 | 52.27684156 | 13.37 | 6.70 | 6.67 | 1463761.66 | 0.2868 | 0.286813 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:00:00 | unknown | unknown | unknown | 8/21 16:00:00 | Sensible | 4198.34 | 4092.67 | 1.0000 | 0.41259757 | 0.342804 | 22.49 | 15.94 | 0.00861294 | 44497.6 | 12.80 | 12.09 | 0.00850000 | 34322.2 | 0.14993692 | 6.70 | 13.37 | 6.67 | 0.000 | 4198.34 | 42.22 | 0.01078081 | 23.70 | 0.00000000 | 0.0000 | 21.11 | 0.00861294 | 21.11 | 0.00861294 | 55.2239 | 3499.56 | 0.00 | 4203.46 | 4034.33 | 0.41259757 | 22.49 | 15.95 | 0.00861294 | 44497.6 | 12.91 | 12.10 | 0.00845058 | 34309.8 | |
ROOM_1_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 815.089 | 815.089 | 0.035160 | 0.00000713 | 23.283 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.342804 | 0.41259757 | 4197.9300 | 999.8980 | 2.10213513 | 54.44 | 82.22 | 27.78 | 245147.84 | 0.3325 | 0.339180 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | Sensible | 815.09 | 815.09 | 1.0000 | 0.04231806 | 0.035160 | 21.11 | 15.12 | 0.00826238 | 42201.5 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.00713003 | 60.00 | 32.22 | 27.78 | 0.000 | 815.09 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 21.11 | 0.00826238 | 21.11 | 0.00826238 | 53.0022 | 815.08 | 0.00 | 878.70 | 878.70 | 0.04231806 | 16.60 | 13.40 | 0.00826238 | 37599.0 | 36.95 | 20.46 | 0.00826238 | 58363.2 | |
ROOM_2_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 4131.226 | -999.000 | 0.337175 | 0.00014756 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8543 | 1004.8586 | 1.2036 | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.337175 | 0.40582239 | 4197.9300 | 999.8980 | 52.27684156 | 13.37 | 6.70 | 6.67 | 1463761.66 | 0.2822 | 0.282228 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:10:00 | unknown | unknown | unknown | 8/21 16:10:00 | Sensible | 4131.23 | 4025.65 | 1.0000 | 0.40582239 | 0.337175 | 22.49 | 15.94 | 0.00861471 | 44502.1 | 12.80 | 12.09 | 0.00850000 | 34322.2 | 0.14754000 | 6.70 | 13.37 | 6.67 | 0.000 | 4131.23 | 42.09 | 0.01078059 | 23.67 | 0.00000000 | 0.0000 | 21.11 | 0.00861471 | 21.11 | 0.00861471 | 55.2351 | 3442.09 | 0.00 | 4136.26 | 3968.37 | 0.40582239 | 22.49 | 15.95 | 0.00861471 | 44502.1 | 12.91 | 12.10 | 0.00845085 | 34309.8 | |
ROOM_2_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 814.769 | 814.769 | 0.035146 | 0.00000713 | 23.274 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.337175 | 0.40582239 | 4197.9300 | 999.8980 | 2.10213513 | 54.44 | 82.22 | 27.78 | 245147.84 | 0.3324 | 0.339047 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | Sensible | 814.77 | 814.77 | 1.0000 | 0.04230147 | 0.035146 | 21.11 | 15.12 | 0.00826244 | 42201.6 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.00712723 | 60.00 | 32.22 | 27.78 | 0.000 | 814.77 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 21.11 | 0.00826244 | 21.11 | 0.00826244 | 53.0026 | 814.76 | 0.00 | 878.36 | 878.36 | 0.04230147 | 16.60 | 13.40 | 0.00826244 | 37599.2 | 36.95 | 20.46 | 0.00826244 | 58363.4 | |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 20312.689 | -999.000 | 1.640426 | 0.00072551 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9335 | 1004.8586 | 1.2036 | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.640426 | 1.97440857 | 4197.9300 | 999.8980 | 52.27684156 | 13.37 | 6.70 | 6.67 | 1463761.66 | 1.3877 | 1.387679 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:20:00 | unknown | unknown | unknown | 8/21 14:20:00 | Sensible | 20312.69 | 19607.47 | 1.0000 | 1.97440857 | 1.640426 | 22.49 | 15.98 | 0.00865732 | 44610.2 | 12.80 | 12.09 | 0.00850000 | 34322.2 | 0.72543463 | 6.70 | 13.37 | 6.67 | 0.000 | 20312.69 | 42.80 | 0.01078182 | 23.86 | 0.00000000 | 0.0000 | 21.11 | 0.00865732 | 21.11 | 0.00865732 | 55.5050 | 16746.24 | 0.00 | 20337.23 | 19339.83 | 1.97440857 | 22.49 | 15.98 | 0.00865732 | 44610.2 | 12.89 | 12.10 | 0.00845724 | 34309.8 | |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3967.858 | 3967.858 | 0.171157 | 0.00003471 | 113.341 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.640426 | 1.97440857 | 4197.9300 | 999.8980 | 2.10213513 | 54.44 | 82.22 | 27.78 | 245147.84 | 1.6186 | 1.651131 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | Sensible | 3967.86 | 3967.86 | 1.0000 | 0.20600402 | 0.171157 | 21.11 | 15.11 | 0.00825128 | 42173.2 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.03470901 | 60.00 | 32.22 | 27.78 | 0.000 | 3967.86 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 21.11 | 0.00825128 | 21.11 | 0.00825128 | 52.9322 | 3967.84 | 0.00 | 4277.51 | 4277.51 | 0.20600402 | 16.60 | 13.39 | 0.00825128 | 37570.9 | 36.95 | 20.45 | 0.00825128 | 58335.2 | |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | BANQUET_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 15392.132 | 15392.132 | 2.386782 | 0.00013466 | 324.716 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.10213513 | 54.44 | 82.22 | 27.78 | 245147.84 | 6.2787 | 6.405076 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | Sensible | 15392.13 | 15392.13 | 1.0000 | 2.87271871 | 2.386782 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.13464335 | 60.00 | 32.22 | 27.78 | 0.000 | 15392.13 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 21.00 | 0.00820115 | 21.00 | 0.00820115 | 52.9753 | 2791.02 | 0.00 | 15478.29 | 15478.29 | 2.87271871 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 21.88 | 15.18 | 0.00800000 | 42322.8 | |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | DINING_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 15871.771 | 15871.771 | 2.497207 | 0.00013885 | 334.524 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.10213513 | 54.44 | 82.22 | 27.78 | 245147.84 | 6.4744 | 6.604667 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 15871.77 | 15871.77 | 1.0000 | 3.00562559 | 2.497207 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.13883902 | 60.00 | 32.22 | 27.78 | 0.000 | 15871.77 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 21.00 | 0.00820756 | 21.00 | 0.00820756 | 53.0159 | 2687.30 | 0.00 | 15960.64 | 15960.64 | 3.00562559 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 21.81 | 15.15 | 0.00800000 | 42245.0 | |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | KITCHEN_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12416.403 | 12416.403 | 2.352717 | 0.00010862 | 258.923 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.10213513 | 54.44 | 82.22 | 27.78 | 245147.84 | 5.0649 | 5.166796 | 1/21 00:10:00 | unknown | unknown | 1/21 00:10:00 | Sensible | 12416.40 | 12416.40 | 1.0000 | 2.83171798 | 2.352717 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.10861303 | 60.00 | 32.22 | 27.78 | 0.000 | 12416.40 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 51.6928 | 0.00 | 0.00 | 12486.19 | 12486.19 | 2.83171798 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 20.92 | 14.82 | 0.00800000 | 41344.1 | |||
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | CORRIDOR_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7354.892 | 7354.892 | 0.840195 | 0.00006434 | 158.817 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.10213513 | 54.44 | 82.22 | 27.78 | 245147.84 | 3.0002 | 3.060567 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 7354.89 | 7354.89 | 1.0000 | 1.01125469 | 0.840195 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.06433724 | 60.00 | 32.22 | 27.78 | 0.000 | 7354.89 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 21.00 | 0.00817344 | 21.00 | 0.00817344 | 52.7986 | 2919.25 | 0.00 | 7395.75 | 7395.75 | 1.01125469 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 23.77 | 15.87 | 0.00800000 | 44248.2 | |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 1083772.561 | -999.000 | 23.472728 | 0.03870984 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.8829 | 1004.8586 | 1.2036 | VAV WITH REHEAT FAN | Fan:VariableVolume | 23.472728 | 28.25165746 | 4197.9300 | 999.8980 | 52.27684156 | 13.37 | 6.70 | 6.67 | 1463761.66 | 74.0402 | 74.040234 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | Sensible | 1083772.56 | 914686.40 | 1.0000 | 28.25165746 | 23.472728 | 42.80 | 23.86 | 0.01078182 | 70829.7 | 10.98 | 10.98 | 0.00850000 | 32468.3 | 38.70589597 | 6.70 | 13.37 | 6.67 | 52593.900 | 1031178.66 | 42.80 | 0.01078182 | 23.86 | 23.46513000 | 99.9676 | 23.99 | 0.00958144 | 23.99 | 0.00957469 | 51.4524 | 322596.10 | 0.00 | 1084952.64 | 900829.49 | 28.25165746 | 42.80 | 23.87 | 0.01078182 | 70829.7 | 11.69 | 11.33 | 0.00819834 | 32426.5 | |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 34066.705 | 34066.705 | 7.041818 | 0.00029803 | 652.398 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | VAV WITH REHEAT FAN | Fan:VariableVolume | 23.472728 | 28.25165746 | 4197.9300 | 999.8980 | 2.10213513 | 54.44 | 82.22 | 27.78 | 245147.84 | 13.8964 | 14.176063 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | Sensible | 34066.70 | 34066.70 | 1.0000 | 8.47549724 | 7.041818 | 12.70 | 12.70 | 0.00915345 | 35869.8 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 0.29799999 | 60.00 | 32.22 | 27.78 | 0.000 | 34066.70 | 12.70 | 0.00915345 | 12.70 | 23.46513000 | 333.2254 | 17.37 | 0.00829611 | 23.08 | 0.00831288 | 47.2788 | 24569.38 | 0.00 | 39068.31 | 39068.31 | 8.47549724 | 2.80 | 2.80 | 0.00915345 | 25753.4 | 7.31 | 7.31 | 0.00915345 | 30363.0 | |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 92321.212 | -999.000 | 2.051317 | 0.00329750 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.8829 | 1004.8586 | 1.2036 | FLR_3_DOAS FAN | Fan:ConstantVolume | 2.051245 | 2.46886833 | 4197.9300 | 999.8980 | 52.27684156 | 13.37 | 6.70 | 6.67 | 1463761.66 | 6.3071 | 6.307121 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | Sensible | 92321.21 | 77917.60 | 1.0000 | 2.46895513 | 2.051317 | 42.80 | 23.86 | 0.01078182 | 70829.7 | 11.93 | 11.73 | 0.00850000 | 33436.8 | 3.29716340 | 6.70 | 13.37 | 6.67 | 2195.006 | 90126.21 | 42.80 | 0.01078182 | 23.86 | 2.05124512 | 99.9965 | 21.11 | 0.00863912 | 21.11 | 0.00863912 | 55.3887 | 235370.24 | 0.00 | 92413.81 | 77447.65 | 2.46895513 | 42.80 | 23.87 | 0.01078182 | 70829.7 | 12.19 | 11.73 | 0.00837980 | 33399.3 | |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 2977.141 | 2977.141 | 0.615395 | 0.00002605 | 57.014 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | FLR_3_DOAS FAN | Fan:ConstantVolume | 2.051245 | 2.46886833 | 4197.9300 | 999.8980 | 2.10213513 | 54.44 | 82.22 | 27.78 | 245147.84 | 1.2144 | 1.238868 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | Sensible | 2977.14 | 2977.14 | 1.0000 | 0.74068654 | 0.615395 | 12.70 | 12.70 | 0.00915345 | 35869.8 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 0.02604267 | 60.00 | 32.22 | 27.78 | 0.000 | 2977.14 | 12.70 | 0.00915345 | 12.70 | 2.05124512 | 333.3216 | 21.11 | 0.00829047 | 21.11 | 0.00828968 | 53.1756 | 46268.86 | 0.00 | 3414.24 | 3414.24 | 0.74068654 | 2.80 | 2.80 | 0.00915345 | 25753.4 | 7.31 | 7.31 | 0.00915345 | 30363.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:58:09
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
FLR_3_DOAS_OA_CONTROLLER | DifferentialDryBulb | 2.05 | 2.05 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
BASEMENT | VAV WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
RETAIL_1_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
RETAIL_2_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
MECH_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
STORAGE_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000610 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
LAUNDRY_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CAFE_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
LOBBY_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001448 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORRIDOR_FLR_3 | VAV WITH REHEAT_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
BANQUET_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
DINING_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
KITCHEN_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003556 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORRIDOR_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 0.00 | 8760.00 | 0.00 |
RETAIL_1_FLR_1 | 0.83 | 8638.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 8760.00 | 0.00 |
MECH_FLR_1 | 0.00 | 8760.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 8760.00 | 0.00 |
LAUNDRY_FLR_1 | 6066.83 | 1871.67 | 1328.67 |
CAFE_FLR_1 | 40.33 | 8396.50 | 0.00 |
LOBBY_FLR_1 | 0.00 | 8760.00 | 0.00 |
ROOM_1_FLR_3 | 512.33 | 7294.50 | 0.67 |
ROOM_2_FLR_3 | 446.00 | 7505.17 | 0.83 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.17 | 8607.67 | 0.17 |
ROOM_5_FLR_3 | 513.67 | 7246.33 | 0.50 |
ROOM_6_FLR_3 | 439.67 | 7453.00 | 0.67 |
CORRIDOR_FLR_3 | 0.00 | 8760.00 | 0.00 |
ROOM_1_FLR_6 | 951.83 | 6985.67 | 4.17 |
ROOM_2_FLR_6 | 841.17 | 7194.83 | 3.83 |
ROOM_3_MULT9_FLR_6 | 509.67 | 7048.33 | 2.17 |
BANQUET_FLR_6 | 869.17 | 6965.83 | 0.00 |
DINING_FLR_6 | 1317.17 | 6296.83 | 0.00 |
KITCHEN_FLR_6 | 7738.00 | 6421.83 | 5985.17 |
CORRIDOR_FLR_6 | 0.00 | 8760.00 | 0.00 |
Facility | 7821.67 | 8760.00 | 5985.33 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 0.83 | 0.00 | 0.83 |
ROOM_2_FLR_3 | 0.00 | 1.00 | 0.00 | 1.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 9.67 | 0.00 | 9.67 |
ROOM_5_FLR_3 | 0.00 | 0.33 | 0.00 | 0.33 |
ROOM_6_FLR_3 | 0.00 | 0.50 | 0.00 | 0.50 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 2.33 | 0.00 | 2.33 |
ROOM_2_FLR_6 | 0.00 | 2.67 | 0.00 | 2.67 |
ROOM_3_MULT9_FLR_6 | 0.00 | 2.67 | 0.00 | 2.67 |
BANQUET_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 0.00 | 13.33 | 0.00 | 13.33 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:58:09
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.80 | 106.50 | 4826.41 | 2.203 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.28 | 10.83 | 265.76 | 5.548 | 0.232 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.28 | 12.54 | 307.76 | 3.158 | 0.077 | 0.000 | 0.000 |
MECH_FLR_1 | 1.54 | 2.65 | 650.80 | 1.720 | 0.086 | 0.000 | 0.000 |
STORAGE_FLR_1 | 1.18 | 2.04 | 375.47 | 1.520 | 0.086 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.87 | 8.40 | 309.22 | 39.373 | 0.249 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.58 | 142.30 | 748.35 | 7.827 | 0.182 | 0.000 | 0.000 |
LOBBY_FLR_1 | 245.14 | 422.44 | 5183.56 | 3.619 | 0.075 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.478 | 0.301 | 0.000 | 0.047 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.478 | 0.301 | 0.000 | 0.046 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.543 | 0.134 | 0.000 | 0.074 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.478 | 0.301 | 0.000 | 0.047 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.478 | 0.301 | 0.000 | 0.046 |
CORRIDOR_FLR_3 | 12.16 | 20.96 | 1186.91 | 1.086 | 0.037 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.478 | 0.302 | 0.000 | 0.055 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.478 | 0.302 | 0.000 | 0.054 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.543 | 0.245 | 0.000 | 0.088 |
BANQUET_FLR_6 | 145.01 | 249.90 | 1010.89 | 8.716 | 0.087 | 0.000 | 0.000 |
DINING_FLR_6 | 145.01 | 249.90 | 1010.89 | 9.121 | 0.087 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.90 | 22.24 | 314.87 | 27.741 | 0.251 | 0.000 | 0.000 |
CORRIDOR_FLR_6 | 12.87 | 22.18 | 1256.16 | 2.463 | 0.061 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.80 | 106.50 | 4826.41 | 2.145 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.28 | 10.83 | 265.76 | 5.399 | 0.005 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.28 | 12.54 | 307.76 | 3.072 | 0.002 | 0.000 | 0.000 |
MECH_FLR_1 | 1.54 | 2.65 | 650.80 | 1.673 | 0.002 | 0.000 | 0.000 |
STORAGE_FLR_1 | 1.18 | 2.04 | 375.47 | 1.479 | 0.002 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.87 | 8.40 | 309.22 | 38.296 | 0.005 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.58 | 142.30 | 748.35 | 7.609 | 0.004 | 0.000 | 0.000 |
LOBBY_FLR_1 | 245.14 | 422.44 | 5183.56 | 3.518 | 0.001 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.465 | 0.006 | 0.000 | 0.000 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.465 | 0.006 | 0.000 | 0.000 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.528 | 0.003 | 0.000 | 0.000 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.466 | 0.006 | 0.000 | 0.000 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.465 | 0.006 | 0.000 | 0.000 |
CORRIDOR_FLR_3 | 12.16 | 20.96 | 1186.91 | 1.055 | 0.001 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.465 | 0.006 | 0.000 | 0.000 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.465 | 0.006 | 0.000 | 0.000 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.529 | 0.005 | 0.000 | 0.000 |
BANQUET_FLR_6 | 145.01 | 249.90 | 1010.89 | 8.462 | 0.002 | 0.000 | 0.000 |
DINING_FLR_6 | 145.01 | 249.90 | 1010.89 | 8.857 | 0.002 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.90 | 22.24 | 314.87 | 26.926 | 0.005 | 0.000 | 0.000 |
CORRIDOR_FLR_6 | 12.87 | 22.18 | 1256.16 | 2.396 | 0.001 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:58:09
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | VAV WITH REHEAT | 61.80 | 106.50 | 4826.41 | 1978.83 | 0.0000 | 0.854 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | 6.28 | 10.83 | 265.76 | 67.07 | 0.0000 | 0.079 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | 7.28 | 12.54 | 307.76 | 77.67 | 0.0000 | 0.092 |
MECH_FLR_1 | VAV WITH REHEAT | 1.54 | 2.65 | 650.80 | 164.24 | 0.0000 | 0.000 |
STORAGE_FLR_1 | VAV WITH REHEAT | 1.18 | 2.04 | 375.47 | 94.76 | 0.0000 | 0.058 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | 4.87 | 8.40 | 309.22 | 78.04 | 0.0000 | 0.000 |
CAFE_FLR_1 | VAV WITH REHEAT | 82.58 | 142.30 | 748.35 | 188.86 | 0.0000 | 0.676 |
LOBBY_FLR_1 | VAV WITH REHEAT | 245.14 | 422.44 | 5183.56 | 1308.19 | 0.0000 | 1.894 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.062 |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.062 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 1.50 | 74.75 | 24.52 | 0.0000 | 0.837 | |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 74.77 | 24.53 | 0.0000 | 0.837 |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.062 |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.062 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | 12.16 | 20.96 | 1186.91 | 389.40 | 0.0000 | 0.475 |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.015 |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.015 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 74.77 | 24.53 | 0.0000 | 0.099 |
BANQUET_FLR_6 | VAV WITH REHEAT | 145.01 | 249.90 | 1010.89 | 331.66 | 0.0000 | 1.188 |
DINING_FLR_6 | VAV WITH REHEAT | 145.01 | 249.90 | 1010.89 | 331.66 | 0.0000 | 1.188 |
KITCHEN_FLR_6 | VAV WITH REHEAT | 12.90 | 22.24 | 314.87 | 103.30 | 0.0000 | 0.367 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | 12.87 | 22.18 | 1256.16 | 412.12 | 0.0000 | 0.126 |
Total Facility | 873.39 | 1604.23 | 35184.81 | 11345.29 | 0.0000 | 137.584 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 91042722.24 | 0.00 | 91042722.24 | 0.00 | 91042722.24 | 26946214.98 | 0.00 | 0.00 | 8760.00 | 0.00 |
RETAIL_1_FLR_1 | 12626544.13 | 0.00 | 12626544.13 | 528565.51 | 13155109.63 | 2498216.28 | 0.00 | 0.00 | 8760.00 | 0.00 |
RETAIL_2_FLR_1 | 8319664.25 | 0.00 | 8319664.25 | 204026.95 | 8523691.21 | 2892943.94 | 0.00 | 0.00 | 8760.00 | 0.00 |
MECH_FLR_1 | 9585058.91 | 0.00 | 9585058.91 | 482198.51 | 10067257.42 | 0.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
STORAGE_FLR_1 | 4887462.37 | 0.00 | 4887462.37 | 278201.98 | 5165664.35 | 1821682.01 | 0.00 | 0.00 | 8760.00 | 0.00 |
LAUNDRY_FLR_1 | 0.10E+09 | 0.00 | 0.10E+09 | 658417.44 | 0.10E+09 | 0.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
CAFE_FLR_1 | 50105789.14 | 0.00 | 50105789.14 | 1168423.98 | 51274213.11 | 21330615.53 | 0.00 | 0.00 | 8760.00 | 0.00 |
LOBBY_FLR_1 | 0.16E+09 | 0.00 | 0.16E+09 | 3338454.18 | 0.16E+09 | 59728886.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
ROOM_1_FLR_3 | 1946875.62 | 47826.75 | 1994702.37 | 306793.02 | 2301495.39 | 1946875.62 | 0.00 | 7807.83 | 952.17 | 0.00 |
ROOM_2_FLR_3 | 1946647.51 | 47371.01 | 1994018.52 | 306769.61 | 2300788.13 | 1946647.51 | 0.00 | 7807.83 | 952.17 | 0.00 |
ROOM_3_MULT19_FLR_3 | 26397887.27 | 53332.54 | 26451219.81 | 85598.69 | 26536818.50 | 26397887.27 | 0.00 | 7877.67 | 882.33 | 8760.00 |
ROOM_4_MULT19_FLR_3 | 26405105.73 | 47481.46 | 26452587.19 | 85622.10 | 26538209.29 | 26405105.73 | 0.00 | 7941.05 | 818.95 | 0.00 |
ROOM_5_FLR_3 | 1946875.62 | 48004.94 | 1994880.55 | 306793.02 | 2301673.57 | 1946875.62 | 0.00 | 7807.83 | 952.17 | 0.00 |
ROOM_6_FLR_3 | 1946647.51 | 47559.69 | 1994207.20 | 306769.61 | 2300976.82 | 1946647.51 | 0.00 | 7807.83 | 952.17 | 0.00 |
CORRIDOR_FLR_3 | 44072517.18 | 0.00 | 44072517.18 | 370974.48 | 44443491.67 | 14972100.18 | 0.00 | 0.00 | 8760.00 | 0.00 |
ROOM_1_FLR_6 | 486718.90 | 56407.64 | 543126.55 | 306853.71 | 849980.26 | 486718.90 | 0.00 | 7807.50 | 952.50 | 0.00 |
ROOM_2_FLR_6 | 486661.88 | 55765.04 | 542426.92 | 306830.30 | 849257.22 | 486661.88 | 0.00 | 7807.50 | 952.50 | 0.00 |
ROOM_3_MULT9_FLR_6 | 3126920.42 | 56650.06 | 3183570.48 | 156997.10 | 3340567.57 | 3126920.42 | 0.00 | 7807.50 | 952.50 | 0.00 |
BANQUET_FLR_6 | 75235807.25 | 0.00 | 75235807.25 | 749259.64 | 75985066.89 | 37458366.31 | 0.00 | 0.00 | 8760.00 | 0.00 |
DINING_FLR_6 | 78716606.24 | 0.00 | 78716606.24 | 749259.64 | 79465865.87 | 37458366.31 | 0.00 | 0.00 | 8760.00 | 0.00 |
KITCHEN_FLR_6 | 74242287.17 | 0.00 | 74242287.17 | 670761.09 | 74913048.26 | 11584760.86 | 0.00 | 0.00 | 8760.00 | 0.00 |
CORRIDOR_FLR_6 | 26484515.44 | 0.00 | 26484515.44 | 656503.52 | 27141018.96 | 3961413.96 | 0.00 | 0.00 | 8760.00 | 0.00 |
Total Facility | 0.49E+10 | 9046936.60 | 0.50E+10 | 30915909.62 | 0.50E+10 | 0.43E+10 | 0.00 | 7984.27 | 8760.00 | 8760.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 2.8869 | 0.0000 | 2.8869 | 0.0000 | 2.8869 | 0.8545 | 0.00 | 0.00 | 8760.00 |
RETAIL_1_FLR_1 | 0.4004 | 0.0000 | 0.4004 | 0.0168 | 0.4171 | 0.0792 | 0.00 | 0.00 | 8760.00 |
RETAIL_2_FLR_1 | 0.2638 | 0.0000 | 0.2638 | 0.0065 | 0.2703 | 0.0917 | 0.00 | 0.00 | 8760.00 |
MECH_FLR_1 | 0.3039 | 0.0000 | 0.3039 | 0.0153 | 0.3192 | 0.0000 | 0.00 | 0.00 | 8760.00 |
STORAGE_FLR_1 | 0.1550 | 0.0000 | 0.1550 | 0.0088 | 0.1638 | 0.0578 | 0.00 | 0.00 | 8760.00 |
LAUNDRY_FLR_1 | 3.3051 | 0.0000 | 3.3051 | 0.0209 | 3.3260 | 0.0000 | 0.00 | 0.00 | 8760.00 |
CAFE_FLR_1 | 1.5888 | 0.0000 | 1.5888 | 0.0371 | 1.6259 | 0.6764 | 0.00 | 0.00 | 8760.00 |
LOBBY_FLR_1 | 5.0877 | 0.0000 | 5.0877 | 0.1059 | 5.1936 | 1.8940 | 0.00 | 0.00 | 8760.00 |
ROOM_1_FLR_3 | 0.0617 | 0.0015 | 0.0633 | 0.0097 | 0.0730 | 0.0617 | 0.00 | 7807.83 | 952.17 |
ROOM_2_FLR_3 | 0.0617 | 0.0015 | 0.0632 | 0.0097 | 0.0730 | 0.0617 | 0.00 | 7807.83 | 952.17 |
ROOM_4_MULT19_FLR_3 | 0.8373 | 0.0015 | 0.8388 | 0.0027 | 0.8415 | 0.8373 | 0.00 | 7941.05 | 818.95 |
ROOM_5_FLR_3 | 0.0617 | 0.0015 | 0.0633 | 0.0097 | 0.0730 | 0.0617 | 0.00 | 7807.83 | 952.17 |
ROOM_6_FLR_3 | 0.0617 | 0.0015 | 0.0632 | 0.0097 | 0.0730 | 0.0617 | 0.00 | 7807.83 | 952.17 |
CORRIDOR_FLR_3 | 1.3975 | 0.0000 | 1.3975 | 0.0118 | 1.4093 | 0.4748 | 0.00 | 0.00 | 8760.00 |
ROOM_1_FLR_6 | 0.0154 | 0.0018 | 0.0172 | 0.0097 | 0.0270 | 0.0154 | 0.00 | 7807.50 | 952.50 |
ROOM_2_FLR_6 | 0.0154 | 0.0018 | 0.0172 | 0.0097 | 0.0269 | 0.0154 | 0.00 | 7807.50 | 952.50 |
ROOM_3_MULT9_FLR_6 | 0.0992 | 0.0018 | 0.1010 | 0.0050 | 0.1059 | 0.0992 | 0.00 | 7807.50 | 952.50 |
BANQUET_FLR_6 | 2.3857 | 0.0000 | 2.3857 | 0.0238 | 2.4095 | 1.1878 | 0.00 | 0.00 | 8760.00 |
DINING_FLR_6 | 2.4961 | 0.0000 | 2.4961 | 0.0238 | 2.5198 | 1.1878 | 0.00 | 0.00 | 8760.00 |
KITCHEN_FLR_6 | 2.3542 | 0.0000 | 2.3542 | 0.0213 | 2.3755 | 0.3674 | 0.00 | 0.00 | 8760.00 |
CORRIDOR_FLR_6 | 0.8398 | 0.0000 | 0.8398 | 0.0208 | 0.8606 | 0.1256 | 0.00 | 0.00 | 8760.00 |
Total Facility | 93.2035 | 0.1583 | 93.3619 | 0.7740 | 94.1359 | 73.9670 | 0.00 | 7984.27 | 8760.00 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV WITH REHEAT | 0.11E+10 | 0.00 | 0.11E+10 | 0.22E+09 | 0.00 | 0.00 | 8760.00 | 0.00 |
FLR_3_DOAS | 93713071.71 | 460399.13 | 94173470.84 | 64690340.46 | 0.00 | 0.00 | 8760.00 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV WITH REHEAT | 33.9925 | 0.0000 | 33.9925 | 6.9969 | 0.00 | 0.00 | 8760.00 |
FLR_3_DOAS | 2.9716 | 0.0146 | 2.9862 | 2.0513 | 0.00 | 0.00 | 8760.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV WITH REHEAT | 0.00 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FLR_3_DOAS | 0.00 | 7080.69 | 1679.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV WITH REHEAT | 0.0000 | 33.9925 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
FLR_3_DOAS | 0.0000 | 2.9719 | 2.9722 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:58:09
Surfaces by ClassTotal | Outdoors | |
Wall | 119 | 44 |
Floor | 25 | 0 |
Roof | 33 | 11 |
Internal Mass | 22 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 30 | 30 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 22 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 1306 |
Defaulted Fields | 1181 |
Fields with Defaults | 3945 |
Autosized Fields | 350 |
Autosizable Fields | 402 |
Autocalculated Fields | 280 |
Autocalculatable Fields | 539 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:58:09
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 13537.92 | 154719.14 | 20-JAN-04:00 | 842574.52 | 10-AUG-18:10 |
Electricity:Building | 2943.68 | 36656.90 | 02-JAN-02:10 | 182730.36 | 02-JAN-20:10 |
Electricity:Zone:BASEMENT | 315.54 | 3631.19 | 02-JAN-02:10 | 23630.80 | 02-JAN-20:10 |
Electricity:SpaceType:GENERAL | 2925.41 | 36182.64 | 02-JAN-02:10 | 182063.43 | 02-JAN-20:10 |
InteriorLights:Electricity | 1174.11 | 10291.59 | 02-JAN-02:10 | 93091.76 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BASEMENT | 165.29 | 1501.97 | 02-JAN-02:10 | 13517.00 | 02-JAN-20:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 1174.11 | 10291.59 | 02-JAN-02:10 | 93091.76 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity | 1174.11 | 10291.59 | 02-JAN-02:10 | 93091.76 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 165.29 | 1501.97 | 02-JAN-02:10 | 13517.00 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 1174.11 | 10291.59 | 02-JAN-02:10 | 93091.76 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_1_FLR_1 | 18.59 | 220.70 | 02-JAN-02:10 | 1372.90 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 8.40 | 76.37 | 02-JAN-02:10 | 687.30 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 8.40 | 76.37 | 02-JAN-02:10 | 687.30 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_2_FLR_1 | 21.53 | 255.58 | 02-JAN-02:10 | 1589.82 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 9.73 | 88.43 | 02-JAN-02:10 | 795.89 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 9.73 | 88.43 | 02-JAN-02:10 | 795.89 | 02-JAN-20:10 |
Electricity:Zone:MECH_FLR_1 | 30.66 | 342.02 | 02-JAN-02:10 | 2327.13 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:MECH_FLR_1 | 18.19 | 165.30 | 02-JAN-02:10 | 1487.69 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:MECH_FLR_1 | 18.19 | 165.30 | 02-JAN-02:10 | 1487.69 | 02-JAN-20:10 |
Electricity:Zone:STORAGE_FLR_1 | 6.94 | 81.32 | 02-JAN-02:10 | 515.26 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 3.34 | 30.34 | 02-JAN-02:10 | 273.10 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 3.34 | 30.34 | 02-JAN-02:10 | 273.10 | 02-JAN-20:10 |
Electricity:Zone:LAUNDRY_FLR_1 | 72.06 | 1000.18 | 02-JAN-02:10 | 4910.17 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 4.13 | 37.49 | 02-JAN-02:10 | 337.37 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 4.13 | 37.49 | 02-JAN-02:10 | 337.37 | 02-JAN-20:10 |
Electricity:Zone:CAFE_FLR_1 | 40.96 | 445.13 | 02-JAN-02:10 | 3142.50 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CAFE_FLR_1 | 26.62 | 241.91 | 02-JAN-02:10 | 2177.23 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CAFE_FLR_1 | 26.62 | 241.91 | 02-JAN-02:10 | 2177.23 | 02-JAN-20:10 |
Electricity:Zone:LOBBY_FLR_1 | 293.89 | 3428.00 | 02-JAN-02:10 | 21878.53 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 144.90 | 1316.59 | 02-JAN-02:10 | 11849.32 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 144.90 | 1316.59 | 02-JAN-02:10 | 11849.32 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_3 | 32.70 | 383.52 | 01-JAN-02:10 | 2308.42 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 20.41 | 172.80 | 01-JAN-02:10 | 1570.91 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 20.41 | 172.80 | 01-JAN-02:10 | 1570.91 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_3 | 32.70 | 383.47 | 01-JAN-02:10 | 2308.15 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 20.41 | 172.78 | 01-JAN-02:10 | 1570.72 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 20.41 | 172.78 | 01-JAN-02:10 | 1570.72 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT19_FLR_3 | 472.46 | 5984.83 | 01-JAN-02:10 | 32482.97 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 243.71 | 2063.36 | 01-JAN-02:10 | 18757.86 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 243.71 | 2063.36 | 01-JAN-02:10 | 18757.86 | 01-JAN-19:10 |
Electricity:Zone:ROOM_4_MULT19_FLR_3 | 472.59 | 5986.46 | 01-JAN-02:10 | 32491.86 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 243.77 | 2063.93 | 01-JAN-02:10 | 18762.99 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 243.77 | 2063.93 | 01-JAN-02:10 | 18762.99 | 01-JAN-19:10 |
Electricity:Zone:ROOM_5_FLR_3 | 32.70 | 383.52 | 01-JAN-02:10 | 2308.42 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 20.41 | 172.80 | 01-JAN-02:10 | 1570.91 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 20.41 | 172.80 | 01-JAN-02:10 | 1570.91 | 01-JAN-19:10 |
Electricity:Zone:ROOM_6_FLR_3 | 32.70 | 383.47 | 01-JAN-02:10 | 2308.15 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 20.41 | 172.78 | 01-JAN-02:10 | 1570.72 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 20.41 | 172.78 | 01-JAN-02:10 | 1570.72 | 01-JAN-19:10 |
Electricity:Zone:CORRIDOR_FLR_3 | 62.74 | 570.05 | 02-JAN-02:10 | 5130.41 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 62.74 | 570.05 | 02-JAN-02:10 | 5130.41 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 62.74 | 570.05 | 02-JAN-02:10 | 5130.41 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_6 | 8.18 | 95.88 | 01-JAN-02:10 | 577.11 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 5.10 | 43.20 | 01-JAN-02:10 | 392.73 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 5.10 | 43.20 | 01-JAN-02:10 | 392.73 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_6 | 8.17 | 95.87 | 01-JAN-02:10 | 577.04 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 5.10 | 43.19 | 01-JAN-02:10 | 392.68 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 5.10 | 43.19 | 01-JAN-02:10 | 392.68 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT9_FLR_6 | 55.96 | 708.92 | 01-JAN-02:10 | 3847.72 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 28.87 | 244.41 | 01-JAN-02:10 | 2221.93 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 28.87 | 244.41 | 01-JAN-02:10 | 2221.93 | 01-JAN-19:10 |
Electricity:Zone:BANQUET_FLR_6 | 222.61 | 2674.12 | 02-JAN-02:10 | 10571.30 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 46.75 | 424.82 | 02-JAN-02:10 | 3823.39 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 46.75 | 424.82 | 02-JAN-02:10 | 3823.39 | 02-JAN-20:10 |
Electricity:Zone:DINING_FLR_6 | 222.61 | 2674.12 | 02-JAN-02:10 | 10571.30 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:DINING_FLR_6 | 46.75 | 424.82 | 02-JAN-02:10 | 3823.39 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:DINING_FLR_6 | 46.75 | 424.82 | 02-JAN-02:10 | 3823.39 | 02-JAN-20:10 |
Electricity:Zone:KITCHEN_FLR_6 | 470.78 | 6777.71 | 02-JAN-02:10 | 19298.76 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 12.48 | 113.42 | 02-JAN-02:10 | 1020.78 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 12.48 | 113.42 | 02-JAN-02:10 | 1020.78 | 02-JAN-20:10 |
Electricity:Zone:CORRIDOR_FLR_6 | 16.60 | 150.83 | 02-JAN-02:10 | 1357.44 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 16.60 | 150.83 | 02-JAN-02:10 | 1357.44 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 16.60 | 150.83 | 02-JAN-02:10 | 1357.44 | 02-JAN-20:10 |
InteriorEquipment:Electricity | 1751.30 | 25891.05 | 02-JAN-02:10 | 89674.66 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 150.26 | 2129.22 | 02-JAN-02:10 | 10113.80 | 02-JAN-20:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 1751.30 | 25891.05 | 02-JAN-02:10 | 89674.66 | 02-JAN-07:10 |
MiscPlug:InteriorEquipment:Electricity | 959.56 | 15202.41 | 02-JAN-02:10 | 59492.27 | 02-JAN-07:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 150.26 | 2129.22 | 02-JAN-02:10 | 10113.80 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 959.56 | 15202.41 | 02-JAN-02:10 | 59492.27 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.79 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.79 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 12.29 | 210.72 | 01-JAN-00:10 | 948.23 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 12.29 | 210.72 | 01-JAN-00:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 12.29 | 210.69 | 01-JAN-00:10 | 948.12 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 12.29 | 210.69 | 01-JAN-00:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 228.75 | 3921.46 | 01-JAN-00:10 | 17646.57 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 228.75 | 3921.46 | 01-JAN-00:10 | 17646.57 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 228.82 | 3922.53 | 01-JAN-00:10 | 17651.40 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 228.82 | 3922.53 | 01-JAN-00:10 | 17651.40 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 12.29 | 210.72 | 01-JAN-00:10 | 948.23 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 12.29 | 210.72 | 01-JAN-00:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 12.29 | 210.69 | 01-JAN-00:10 | 948.12 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 12.29 | 210.69 | 01-JAN-00:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 3.07 | 52.68 | 01-JAN-00:10 | 237.06 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 3.07 | 52.68 | 01-JAN-00:10 | 237.06 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 3.07 | 52.67 | 01-JAN-00:10 | 237.03 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 3.07 | 52.67 | 01-JAN-00:10 | 237.03 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 27.10 | 464.51 | 01-JAN-00:10 | 2090.30 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 27.10 | 464.51 | 01-JAN-00:10 | 2090.30 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 440.03 | 6190.03 | 01-JAN-00:10 | 16686.59 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 410.33 | 5248.28 | 01-JAN-00:10 | 15744.84 | 01-JAN-07:10 |
ReachInFreezer:InteriorEquipment:Electricity | 16.27 | 515.92 | 01-JAN-00:10 | 515.92 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 16.27 | 515.92 | 01-JAN-00:10 | 515.92 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 16.27 | 515.92 | 01-JAN-00:10 | 515.92 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 13.43 | 425.83 | 01-JAN-00:10 | 425.83 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 13.43 | 425.83 | 01-JAN-00:10 | 425.83 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 13.43 | 425.83 | 01-JAN-00:10 | 425.83 | 01-JAN-00:10 |
Refrigeration:Electricity | 75.64 | 1297.31 | 20-JAN-23:30 | 3643.47 | 18-AUG-06:40 |
Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 18.27 | 261.51 | 02-JAN-11:30 | 2271.91 | 01-JAN-11:10 |
General:Refrigeration:Electricity | 18.27 | 261.51 | 02-JAN-11:30 | 2271.91 | 01-JAN-11:10 |
General:Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 18.27 | 261.51 | 02-JAN-11:30 | 2271.91 | 01-JAN-11:10 |
Electricity:Plant | 7039.12 | 15504.56 | 20-JAN-04:00 | 574344.01 | 10-AUG-16:00 |
LowTempRefrigeration:Refrigeration:Electricity | 22.60 | 0.00 | 01-JAN-11:10 | 1891.52 | 25-JUL-10:50 |
MedTempRefrigeration:Refrigeration:Electricity | 34.77 | 956.91 | 22-MAR-05:00 | 1200.53 | 14-NOV-14:10 |
Fans:Electricity | 2043.20 | 55976.83 | 11-MAR-06:10 | 85614.72 | 10-AUG-18:20 |
Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Electricity:HVAC | 2645.65 | 73726.15 | 11-MAR-06:10 | 105605.36 | 10-AUG-18:20 |
ExteriorEquipment:Electricity | 679.68 | 10574.27 | 02-JAN-02:20 | 40537.60 | 02-JAN-07:20 |
Transformer:ExteriorEquipment:Electricity | 32.92 | 556.27 | 02-JAN-02:20 | 1912.91 | 02-JAN-21:10 |
ElectricityPurchased:Facility | 13537.92 | 154719.14 | 20-JAN-04:00 | 842574.52 | 10-AUG-18:10 |
ElectricityPurchased:Plant | 13537.92 | 154719.14 | 20-JAN-04:00 | 842574.52 | 10-AUG-18:10 |
Cogeneration:ElectricityPurchased | 13537.92 | 154719.14 | 20-JAN-04:00 | 842574.52 | 10-AUG-18:10 |
General:Cogeneration:ElectricityPurchased | 13537.92 | 154719.14 | 20-JAN-04:00 | 842574.52 | 10-AUG-18:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 13537.92 | 154719.14 | 20-JAN-04:00 | 842574.52 | 10-AUG-18:10 |
ElectricityNet:Plant | 13537.92 | 154719.14 | 20-JAN-04:00 | 842574.52 | 10-AUG-18:10 |
Cogeneration:ElectricityNet | 13537.92 | 154719.14 | 20-JAN-04:00 | 842574.52 | 10-AUG-18:10 |
General:Cogeneration:ElectricityNet | 13537.92 | 154719.14 | 20-JAN-04:00 | 842574.52 | 10-AUG-18:10 |
General:Fans:Electricity | 2043.20 | 55976.83 | 11-MAR-06:10 | 85614.72 | 10-AUG-18:20 |
ExteriorLights:Electricity | 262.70 | 0.00 | 01-JAN-07:10 | 16690.39 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 262.70 | 0.00 | 01-JAN-07:10 | 16690.39 | 01-JAN-00:10 |
ElevatorLift:ExteriorEquipment:Electricity | 616.11 | 9046.01 | 01-JAN-00:10 | 37691.69 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 30.65 | 972.00 | 01-JAN-00:10 | 972.00 | 01-JAN-00:10 |
HeatRecovery:Electricity | 569.53 | 16886.21 | 01-JAN-09:10 | 18408.03 | 01-JAN-02:40 |
General:HeatRecovery:Electricity | 569.53 | 16886.21 | 01-JAN-09:10 | 18408.03 | 01-JAN-02:40 |
WaterSystems:Electricity | 90.77 | 1087.00 | 12-JUL-00:10 | 4739.38 | 22-FEB-07:10 |
Water Heater:WaterSystems:Electricity | 90.77 | 1087.00 | 12-JUL-00:10 | 4739.38 | 22-FEB-07:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 6426.54 | 3895.49 | 20-JAN-08:20 | 552381.45 | 10-AUG-16:00 |
General:Cooling:Electricity | 6426.54 | 3895.49 | 20-JAN-08:20 | 552381.45 | 10-AUG-16:00 |
Pumps:Electricity | 464.43 | 8069.38 | 20-JAN-08:20 | 18680.89 | 30-JUL-16:20 |
General:Pumps:Electricity | 464.43 | 8069.38 | 20-JAN-08:20 | 18680.89 | 30-JUL-16:20 |
WIRED_LTG_ELECTRICITY | 41.33 | 0.00 | 01-JAN-00:10 | 3276.83 | 02-JAN-20:20 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 4842.38 | 40711.00 | 11-AUG-23:10 | 356341.61 | 20-FEB-18:40 |
NaturalGas:Building | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
NaturalGas:SpaceType:GENERAL | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:NaturalGas | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
InteriorEquipment:NaturalGas:SpaceType:GENERAL | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
Laundry:InteriorEquipment:NaturalGas | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
NaturalGas:Plant | 3053.54 | 18467.44 | 16-JUL-07:10 | 268746.66 | 20-FEB-17:40 |
WaterSystems:NaturalGas | 2473.10 | 18467.44 | 04-JAN-00:10 | 221365.59 | 12-JAN-21:40 |
Water Heater:WaterSystems:NaturalGas | 2473.10 | 18467.44 | 04-JAN-00:10 | 221365.59 | 12-JAN-21:40 |
Heating:NaturalGas | 580.44 | 0.00 | 01-MAR-21:50 | 94309.14 | 20-MAR-10:40 |
Boiler:Heating:NaturalGas | 580.44 | 0.00 | 01-MAR-21:50 | 94309.14 | 20-MAR-10:40 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 18094.39 | 3086.77 | 20-JAN-08:20 | 1324559.38 | 19-JUL-15:20 |
PlantLoopCoolingDemand:HVAC | 18094.39 | 3086.77 | 20-JAN-08:20 | 1324559.38 | 19-JUL-15:20 |
CoolingCoils:PlantLoopCoolingDemand | 18094.39 | 3086.77 | 20-JAN-08:20 | 1324559.38 | 19-JUL-15:20 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-21:10 |
Water:Plant | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-21:10 |
WaterSystems:Water | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-21:10 |
Water Heater:WaterSystems:Water | 5742.51 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-19:20 |
MainsWater:Facility | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-21:10 |
MainsWater:Plant | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-21:10 |
WaterSystems:MainsWater | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-21:10 |
Water Heater:WaterSystems:MainsWater | 5742.51 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-19:20 |
WaterUse:WaterSystems:Water | 4114.69 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-07:10 |
WaterUse:WaterSystems:MainsWater | 4114.69 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-07:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 81368.16 | 278731.67 | 03-JAN-04:00 | 5933328.93 | 19-JUL-15:20 |
EnergyTransfer:Building | 8302.26 | 136978.90 | 20-FEB-16:00 | 461680.18 | 16-AUG-18:10 |
EnergyTransfer:Zone:KITCHEN_FLR_6 | 805.44 | 13616.74 | 01-JAN-04:00 | 37193.86 | 30-JUL-10:40 |
Refrigeration:EnergyTransfer | 194.21 | 4042.55 | 20-JAN-23:30 | 10380.12 | 05-DEC-08:30 |
Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 97.11 | 2021.27 | 20-JAN-23:30 | 5190.06 | 05-DEC-08:30 |
General:Refrigeration:EnergyTransfer | 97.11 | 2021.27 | 20-JAN-23:30 | 5190.06 | 05-DEC-08:30 |
General:Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 97.11 | 2021.27 | 20-JAN-23:30 | 5190.06 | 05-DEC-08:30 |
EnergyTransfer:Plant | 44368.51 | 72289.69 | 20-JAN-04:00 | 3208008.87 | 19-JUL-15:20 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 25.90 | 0.00 | 01-JAN-11:10 | 2686.44 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 71.21 | 1820.73 | 22-MAR-05:00 | 2551.60 | 14-NOV-14:10 |
EnergyTransfer:Zone:BASEMENT | 613.10 | 10491.70 | 10-APR-11:00 | 27894.75 | 16-AUG-18:10 |
Heating:EnergyTransfer | 0.56 | 0.00 | 01-JAN-00:10 | 7088.13 | 04-JAN-09:10 |
Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer | 0.56 | 0.00 | 01-JAN-00:10 | 7088.13 | 04-JAN-09:10 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer | 8204.60 | 133963.03 | 20-FEB-16:00 | 457878.86 | 16-AUG-18:10 |
Cooling:EnergyTransfer:Zone:BASEMENT | 613.10 | 10491.70 | 10-APR-11:00 | 27894.75 | 16-AUG-18:10 |
General:Cooling:EnergyTransfer | 8204.60 | 133963.03 | 20-FEB-16:00 | 457878.86 | 16-AUG-18:10 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 613.10 | 10491.70 | 10-APR-11:00 | 27894.75 | 16-AUG-18:10 |
EnergyTransfer:Zone:RETAIL_1_FLR_1 | 76.47 | 480.83 | 01-JAN-06:00 | 4104.64 | 05-AUG-10:40 |
Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 76.47 | 480.83 | 01-JAN-06:00 | 4104.64 | 05-AUG-10:40 |
General:Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 76.47 | 480.83 | 01-JAN-06:00 | 4104.64 | 05-AUG-10:40 |
EnergyTransfer:Zone:RETAIL_2_FLR_1 | 55.13 | 867.12 | 20-FEB-15:40 | 2614.88 | 16-AUG-18:10 |
Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 55.13 | 867.12 | 20-FEB-15:40 | 2614.88 | 16-AUG-18:10 |
General:Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 55.13 | 867.12 | 20-FEB-15:40 | 2614.88 | 16-AUG-18:10 |
EnergyTransfer:Zone:MECH_FLR_1 | 59.36 | 634.42 | 21-JAN-06:00 | 3105.96 | 06-AUG-10:40 |
Heating:EnergyTransfer:Zone:MECH_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:MECH_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 59.36 | 634.42 | 21-JAN-06:00 | 3105.96 | 06-AUG-10:40 |
General:Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 59.36 | 634.42 | 21-JAN-06:00 | 3105.96 | 06-AUG-10:40 |
EnergyTransfer:Zone:STORAGE_FLR_1 | 28.65 | 258.97 | 01-JAN-06:00 | 1592.08 | 05-AUG-10:40 |
Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 28.65 | 258.97 | 01-JAN-06:00 | 1592.08 | 05-AUG-10:40 |
General:Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 28.65 | 258.97 | 01-JAN-06:00 | 1592.08 | 05-AUG-10:40 |
EnergyTransfer:Zone:LAUNDRY_FLR_1 | 638.99 | 9868.56 | 02-JAN-05:00 | 38797.52 | 10-AUG-20:00 |
Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 638.99 | 9868.56 | 02-JAN-05:00 | 38797.52 | 10-AUG-20:00 |
General:Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 638.99 | 9868.56 | 02-JAN-05:00 | 38797.52 | 10-AUG-20:00 |
EnergyTransfer:Zone:CAFE_FLR_1 | 350.26 | 3958.63 | 09-JAN-09:10 | 15792.43 | 16-AUG-18:10 |
Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 350.26 | 3958.63 | 09-JAN-09:10 | 15792.43 | 16-AUG-18:10 |
General:Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 350.26 | 3958.63 | 09-JAN-09:10 | 15792.43 | 16-AUG-18:10 |
EnergyTransfer:Zone:LOBBY_FLR_1 | 1136.08 | 17260.41 | 20-FEB-16:00 | 50598.28 | 10-AUG-19:10 |
Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 1136.08 | 17260.41 | 20-FEB-16:00 | 50598.28 | 10-AUG-19:10 |
General:Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 1136.08 | 17260.41 | 20-FEB-16:00 | 50598.28 | 10-AUG-19:10 |
EnergyTransfer:Zone:ROOM_1_FLR_3 | 129.56 | 1.29 | 01-JAN-05:50 | 12590.41 | 10-AUG-15:10 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 0.04 | 0.00 | 01-JAN-00:10 | 659.07 | 16-DEC-09:10 |
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 0.04 | 0.00 | 01-JAN-00:10 | 659.07 | 16-DEC-09:10 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 129.52 | 0.00 | 01-JAN-05:50 | 12590.41 | 10-AUG-15:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 129.52 | 0.00 | 01-JAN-05:50 | 12590.41 | 10-AUG-15:10 |
EnergyTransfer:Zone:ROOM_2_FLR_3 | 121.82 | 0.40 | 16-JAN-05:30 | 12459.34 | 10-AUG-15:10 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 0.06 | 0.00 | 01-JAN-00:10 | 633.30 | 11-FEB-09:10 |
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 0.06 | 0.00 | 01-JAN-00:10 | 633.30 | 11-FEB-09:10 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 121.76 | 0.00 | 01-JAN-04:20 | 12459.34 | 10-AUG-15:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 121.76 | 0.00 | 01-JAN-04:20 | 12459.34 | 10-AUG-15:10 |
EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 956.70 | 7254.38 | 06-MAR-07:00 | 55025.40 | 21-JUL-20:20 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 956.70 | 7254.38 | 06-MAR-07:00 | 55025.40 | 21-JUL-20:20 |
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 956.70 | 7254.38 | 06-MAR-07:00 | 55025.40 | 21-JUL-20:20 |
EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 1064.73 | 6049.22 | 20-JAN-08:10 | 92242.82 | 05-AUG-18:20 |
Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 0.30 | 0.00 | 01-JAN-00:10 | 5297.00 | 04-JAN-09:10 |
General:Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 0.30 | 0.00 | 01-JAN-00:10 | 5297.00 | 04-JAN-09:10 |
Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 1064.44 | 6049.22 | 20-JAN-08:10 | 92242.82 | 05-AUG-18:20 |
General:Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 1064.44 | 6049.22 | 20-JAN-08:10 | 92242.82 | 05-AUG-18:20 |
EnergyTransfer:Zone:ROOM_5_FLR_3 | 129.60 | 2.20 | 01-JAN-04:30 | 11446.48 | 21-JUL-15:10 |
Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 0.03 | 0.00 | 01-JAN-00:10 | 505.79 | 25-JAN-19:10 |
General:Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 0.03 | 0.00 | 01-JAN-00:10 | 505.79 | 25-JAN-19:10 |
Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 129.57 | 0.00 | 01-JAN-04:30 | 11446.48 | 21-JUL-15:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 129.57 | 0.00 | 01-JAN-04:30 | 11446.48 | 21-JUL-15:10 |
EnergyTransfer:Zone:ROOM_6_FLR_3 | 121.82 | 0.11 | 19-JAN-05:40 | 11388.27 | 21-JUL-15:10 |
Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 0.06 | 0.00 | 01-JAN-00:10 | 502.19 | 23-FEB-19:10 |
General:Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 0.06 | 0.00 | 01-JAN-00:10 | 502.19 | 23-FEB-19:10 |
Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 121.77 | 0.00 | 01-JAN-03:00 | 11388.27 | 21-JUL-15:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 121.77 | 0.00 | 01-JAN-03:00 | 11388.27 | 21-JUL-15:10 |
EnergyTransfer:Zone:CORRIDOR_FLR_3 | 333.10 | 4003.53 | 09-JAN-09:10 | 15960.16 | 05-AUG-10:40 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 333.10 | 4003.53 | 09-JAN-09:10 | 15960.16 | 05-AUG-10:40 |
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 333.10 | 4003.53 | 09-JAN-09:10 | 15960.16 | 05-AUG-10:40 |
EnergyTransfer:Zone:ROOM_1_FLR_6 | 36.23 | 0.03 | 22-FEB-05:10 | 3613.28 | 06-AUG-15:10 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 0.01 | 0.00 | 01-JAN-00:10 | 168.34 | 22-MAR-08:10 |
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 0.01 | 0.00 | 01-JAN-00:10 | 168.34 | 22-MAR-08:10 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 36.22 | 0.00 | 01-JAN-03:00 | 3613.28 | 06-AUG-15:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 36.22 | 0.00 | 01-JAN-03:00 | 3613.28 | 06-AUG-15:10 |
EnergyTransfer:Zone:ROOM_2_FLR_6 | 34.15 | 0.05 | 14-JAN-05:00 | 3584.04 | 21-JUL-15:10 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 0.03 | 0.00 | 01-JAN-00:10 | 212.69 | 20-JAN-09:10 |
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 0.03 | 0.00 | 01-JAN-00:10 | 212.69 | 20-JAN-09:10 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 34.13 | 0.00 | 01-JAN-02:30 | 3584.04 | 21-JUL-15:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 34.13 | 0.00 | 01-JAN-02:30 | 3584.04 | 21-JUL-15:10 |
EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 204.89 | 18.76 | 16-DEC-06:30 | 17447.82 | 26-SEP-15:10 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 0.03 | 0.00 | 01-JAN-00:10 | 767.48 | 04-JAN-09:10 |
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 0.03 | 0.00 | 01-JAN-00:10 | 767.48 | 04-JAN-09:10 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 204.86 | 0.00 | 16-DEC-06:10 | 17447.82 | 26-SEP-15:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 204.86 | 0.00 | 16-DEC-06:10 | 17447.82 | 26-SEP-15:10 |
EnergyTransfer:Zone:BANQUET_FLR_6 | 598.46 | 11588.34 | 09-JAN-09:20 | 25356.51 | 16-AUG-18:10 |
Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 598.46 | 11588.34 | 09-JAN-09:20 | 25356.51 | 16-AUG-18:10 |
General:Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 598.46 | 11588.34 | 09-JAN-09:20 | 25356.51 | 16-AUG-18:10 |
EnergyTransfer:Zone:DINING_FLR_6 | 635.55 | 12844.13 | 09-JAN-09:20 | 26702.46 | 16-AUG-18:10 |
Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 635.55 | 12844.13 | 09-JAN-09:20 | 26702.46 | 16-AUG-18:10 |
General:Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 635.55 | 12844.13 | 09-JAN-09:20 | 26702.46 | 16-AUG-18:10 |
Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 708.33 | 11354.69 | 01-JAN-04:00 | 32120.50 | 30-JUL-10:40 |
General:Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 708.33 | 11354.69 | 01-JAN-04:00 | 32120.50 | 30-JUL-10:40 |
EnergyTransfer:Zone:CORRIDOR_FLR_6 | 172.17 | 807.25 | 03-JAN-07:10 | 9330.25 | 16-JUL-10:40 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 172.17 | 807.25 | 03-JAN-07:10 | 9330.25 | 16-JUL-10:40 |
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 172.17 | 807.25 | 03-JAN-07:10 | 9330.25 | 16-JUL-10:40 |
PlantLoopHeatingDemand:Facility | 869.81 | 6958.34 | 04-JUL-00:10 | 82186.73 | 06-MAR-11:40 |
PlantLoopHeatingDemand:Plant | 479.71 | 4902.14 | 11-JUL-01:00 | 38932.77 | 10-JAN-07:10 |
WaterSystems:PlantLoopHeatingDemand | 479.71 | 4902.14 | 11-JUL-01:00 | 38932.77 | 10-JAN-07:10 |
General:WaterSystems:PlantLoopHeatingDemand | 479.71 | 4902.14 | 11-JUL-01:00 | 38932.77 | 10-JAN-07:10 |
EnergyTransfer:HVAC | 28697.38 | 34421.94 | 27-JAN-05:10 | 2388873.31 | 22-AUG-17:00 |
HeatingCoils:EnergyTransfer | 390.10 | 0.00 | 01-MAR-21:50 | 67976.70 | 20-MAR-10:40 |
PlantLoopHeatingDemand:HVAC | 390.10 | 0.00 | 01-MAR-21:50 | 67976.70 | 20-MAR-10:40 |
HeatingCoils:PlantLoopHeatingDemand | 390.10 | 0.00 | 01-MAR-21:50 | 67976.70 | 20-MAR-10:40 |
CoolingCoils:EnergyTransfer | 18094.39 | 3086.77 | 20-JAN-08:20 | 1324559.38 | 19-JUL-15:20 |
HeatRecoveryForHeating:EnergyTransfer | 30.16 | 0.00 | 01-JAN-00:10 | 115236.97 | 21-MAR-24:00 |
HeatRecoveryForCooling:EnergyTransfer | 10182.72 | 0.00 | 01-JAN-00:10 | 1057908.65 | 22-AUG-17:00 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:EnergyTransfer | 479.71 | 4902.14 | 11-JUL-01:00 | 38932.77 | 10-JAN-07:10 |
WaterUse:WaterSystems:EnergyTransfer | 479.71 | 4902.14 | 11-JUL-01:00 | 38932.77 | 10-JAN-07:10 |
Boilers:EnergyTransfer | 386.99 | 0.00 | 01-MAR-21:50 | 73263.70 | 20-MAR-10:40 |
Chillers:EnergyTransfer | 18489.08 | 11382.85 | 20-JAN-08:20 | 1339141.33 | 19-JUL-15:20 |
HeatRejection:EnergyTransfer | 24915.62 | 15278.34 | 20-JAN-08:20 | 1841418.18 | 19-JUL-15:20 |
General:HeatRejection:EnergyTransfer | 24915.62 | 15278.34 | 20-JAN-08:20 | 1841418.18 | 19-JUL-15:20 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:58:09
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 0.000 | -613.099 | 0.000 | 0.000 | 156.957 | 165.288 | 150.255 | 0.000 | 0.000 | 0.000 | 140.599 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 0.000 | 0.000 | 0.000 | -76.466 | 0.000 | 0.000 | 16.071 | 8.404 | 10.186 | 26.362 | 0.000 | 4.595 | 12.790 | 0.000 | -1.577 | 0.000 | -0.366 | -0.000 |
RETAIL_2_FLR_1 | 0.000 | 0.000 | 0.000 | -55.135 | 0.000 | 0.000 | 18.460 | 9.732 | 11.795 | 0.000 | 0.000 | 1.762 | 13.529 | 0.000 | 0.000 | 0.000 | -0.144 | 0.000 |
MECH_FLR_1 | 0.000 | 0.000 | 0.000 | -59.361 | 0.000 | 0.000 | 3.923 | 18.192 | 12.471 | 0.000 | 0.000 | 4.191 | 20.918 | 0.000 | 0.000 | 0.000 | -0.334 | 0.000 |
STORAGE_FLR_1 | 0.000 | 0.000 | 0.000 | -28.650 | 0.000 | 0.000 | 3.026 | 3.340 | 3.598 | 0.000 | 0.000 | 2.433 | 16.446 | 0.000 | 0.000 | 0.000 | -0.193 | 0.000 |
LAUNDRY_FLR_1 | 0.000 | 0.000 | 0.000 | -638.996 | 0.000 | 0.000 | 12.215 | 4.125 | 658.131 | 0.000 | 0.000 | 5.603 | 0.000 | 0.000 | 0.000 | 0.000 | -0.533 | -40.545 |
CAFE_FLR_1 | 0.000 | 0.000 | 0.000 | -350.258 | 0.000 | 0.000 | 208.160 | 26.624 | 14.341 | 73.616 | 0.000 | 9.964 | 22.996 | 0.000 | -4.614 | 0.000 | -0.829 | -0.000 |
LOBBY_FLR_1 | 0.000 | 0.000 | 0.000 | -1136.088 | 0.000 | 0.000 | 614.926 | 144.896 | 148.998 | 98.561 | 0.000 | 28.352 | 108.938 | 0.000 | -6.095 | 0.000 | -2.488 | -0.000 |
ROOM_1_FLR_3 | 0.099 | -108.843 | 0.000 | -20.727 | 0.000 | 0.000 | 9.632 | 20.410 | 12.292 | 58.303 | 0.000 | 9.984 | 23.894 | 0.000 | -3.762 | 0.000 | -1.282 | -0.001 |
ROOM_2_FLR_3 | 0.183 | -101.214 | 0.000 | -20.663 | 0.000 | 0.000 | 9.639 | 20.407 | 12.291 | 51.728 | 0.000 | 10.010 | 22.604 | 0.000 | -3.749 | 0.000 | -1.235 | -0.000 |
ROOM_3_MULT19_FLR_3 | 0.000 | -623.392 | 0.000 | -333.306 | 0.000 | 0.000 | 0.000 | 243.708 | 228.754 | 300.425 | 0.000 | 43.370 | 193.637 | 0.000 | -29.225 | 0.000 | -23.970 | -0.005 |
ROOM_4_MULT19_FLR_3 | 0.592 | -786.352 | 0.000 | -278.351 | 0.000 | 0.000 | 183.399 | 243.774 | 228.817 | 221.457 | 0.000 | 55.128 | 161.723 | 0.000 | -19.469 | 0.000 | -10.717 | -0.004 |
ROOM_5_FLR_3 | 0.101 | -108.868 | 0.000 | -20.760 | 0.000 | 0.000 | 9.629 | 20.410 | 12.292 | 58.069 | 0.000 | 9.974 | 24.074 | 0.000 | -3.610 | 0.000 | -1.309 | -0.000 |
ROOM_6_FLR_3 | 0.199 | -101.207 | 0.000 | -20.698 | 0.000 | 0.000 | 9.636 | 20.407 | 12.291 | 51.402 | 0.000 | 9.993 | 22.741 | 0.000 | -3.507 | 0.000 | -1.256 | -0.000 |
CORRIDOR_FLR_3 | 0.000 | 0.000 | 0.000 | -333.102 | 0.000 | 0.000 | 121.227 | 62.736 | 0.000 | 63.434 | 0.000 | 12.051 | 78.728 | 0.000 | -4.018 | 0.000 | -1.056 | 0.000 |
ROOM_1_FLR_6 | 0.053 | -31.070 | 0.000 | -5.184 | 0.000 | 0.000 | 2.408 | 5.102 | 3.073 | 14.427 | 0.000 | 2.481 | 9.983 | 0.000 | -0.936 | 0.000 | -0.338 | -0.000 |
ROOM_2_FLR_6 | 0.099 | -29.025 | 0.000 | -5.172 | 0.000 | 0.000 | 2.409 | 5.102 | 3.073 | 12.799 | 0.000 | 2.486 | 9.485 | 0.000 | -0.931 | 0.000 | -0.325 | -0.000 |
ROOM_3_MULT9_FLR_6 | 0.056 | -171.543 | 0.000 | -33.345 | 0.000 | 0.000 | 21.661 | 28.868 | 27.097 | 68.633 | 0.000 | 11.557 | 53.331 | 0.000 | -4.284 | 0.000 | -2.031 | -0.001 |
BANQUET_FLR_6 | 0.000 | 0.000 | 0.000 | -598.466 | 0.000 | 0.000 | 353.683 | 46.753 | 175.857 | 25.218 | 0.000 | 5.982 | 0.000 | 0.000 | -2.587 | 0.000 | -0.671 | -5.769 |
DINING_FLR_6 | 0.000 | 0.000 | 0.000 | -635.557 | 0.000 | 0.000 | 352.416 | 46.753 | 175.857 | 24.729 | 0.000 | 5.933 | 33.319 | 0.000 | -2.766 | 0.000 | -0.684 | -0.001 |
KITCHEN_FLR_6 | 0.000 | 0.000 | 0.000 | -708.331 | 0.000 | 0.000 | 30.238 | 12.482 | 556.656 | 28.251 | 0.000 | 4.484 | 79.354 | 0.000 | -2.355 | 0.000 | -0.780 | 0.000 |
CORRIDOR_FLR_6 | 0.000 | 0.000 | 0.000 | -172.170 | 0.000 | 0.000 | 32.633 | 16.599 | 0.000 | 29.092 | 0.000 | 5.520 | 90.603 | 0.000 | -1.807 | 0.000 | -0.470 | 0.000 |
Total Facility | 1.382 | -2061.515 | 0.000 | -6143.886 | 0.000 | 0.000 | 2172.349 | 1174.112 | 2458.123 | 1206.507 | 0.000 | 245.853 | 1139.691 | 0.000 | -95.292 | 0.000 | -51.009 | -46.328 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 16-AUG-18:10 | 0.00 | 0.00 | 0.00 | -27969.59 | 0.00 | 0.00 | 6161.94 | 12015.03 | 9581.50 | 0.00 | 0.00 | 0.00 | 211.13 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 05-AUG-10:35 | 0.00 | 0.00 | 0.00 | -4162.07 | 0.00 | 0.00 | 260.08 | 190.92 | 252.59 | 2078.01 | 0.00 | 412.39 | 968.08 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 16-AUG-18:10 | 0.00 | 0.00 | 0.00 | -2638.39 | 0.00 | 0.00 | 721.95 | 707.46 | 752.15 | 0.00 | 0.00 | 149.25 | 307.59 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 06-AUG-10:35 | 0.00 | 0.00 | 0.00 | -3127.60 | 0.00 | 0.00 | 64.10 | 495.90 | 353.45 | 0.00 | 0.00 | 322.42 | 1891.74 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 05-AUG-10:35 | 0.00 | 0.00 | 0.00 | -1602.12 | 0.00 | 0.00 | 49.47 | 75.86 | 89.22 | 0.00 | 0.00 | 217.57 | 1169.99 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 10-AUG-20:00 | 0.00 | 0.00 | 0.00 | -38798.25 | 0.00 | 0.00 | 427.09 | 337.37 | 44299.38 | 0.00 | 0.00 | 409.73 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -6675.32 |
CAFE_FLR_1 | 16-AUG-18:10 | 0.00 | 0.00 | 0.00 | -15993.82 | 0.00 | 0.00 | 8232.53 | 1935.31 | 914.47 | 3065.27 | 0.00 | 852.61 | 993.62 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 16-AUG-18:10 | 0.00 | 0.00 | 0.00 | -51060.42 | 0.00 | 0.00 | 24413.37 | 10532.73 | 9501.36 | 4138.31 | 0.00 | 2439.00 | 35.65 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 18-NOV-16:01 | 0.00 | -14336.15 | 0.00 | -734.07 | 0.00 | 0.00 | 130.71 | 518.40 | 305.54 | 4056.01 | 0.00 | 387.01 | 9672.55 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 18-NOV-16:01 | 0.00 | -14021.63 | 0.00 | -730.27 | 0.00 | 0.00 | 130.72 | 518.34 | 305.51 | 3468.67 | 0.00 | 389.31 | 9939.36 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 21-JUL-20:20 | 0.00 | -44203.83 | 0.00 | -10819.54 | 0.00 | 0.00 | 0.00 | 16694.50 | 13725.11 | 9556.94 | 0.00 | 4167.43 | 10879.39 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 18-NOV-16:01 | 0.00 | -98163.41 | 0.00 | -10162.91 | 0.00 | 0.00 | 2483.65 | 6191.79 | 5687.67 | 6854.37 | 0.00 | 2001.14 | 85107.69 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 18-NOV-16:01 | 0.00 | -12994.04 | 0.00 | -735.53 | 0.00 | 0.00 | 130.72 | 518.40 | 305.54 | 1826.27 | 0.00 | 386.09 | 10562.54 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 18-NOV-16:01 | 0.00 | -12691.44 | 0.00 | -731.29 | 0.00 | 0.00 | 130.72 | 518.34 | 305.51 | 1232.33 | 0.00 | 388.63 | 10847.21 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 05-AUG-10:35 | 0.00 | 0.00 | 0.00 | -16017.56 | 0.00 | 0.00 | 1939.44 | 1425.11 | 0.00 | 5740.56 | 0.00 | 1108.08 | 5804.38 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 18-NOV-16:01 | 0.00 | -3902.31 | 0.00 | -183.23 | 0.00 | 0.00 | 32.68 | 129.60 | 76.39 | 1001.60 | 0.00 | 96.25 | 2749.04 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 18-NOV-16:01 | 0.00 | -3817.33 | 0.00 | -182.21 | 0.00 | 0.00 | 32.68 | 129.58 | 76.38 | 856.19 | 0.00 | 96.87 | 2807.84 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 26-SEP-15:02 | 0.00 | -18706.85 | 0.00 | -1214.23 | 0.00 | 0.00 | 529.38 | 622.14 | 603.86 | 5690.76 | 0.00 | 845.56 | 11629.37 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 16-AUG-18:10 | 0.00 | 0.00 | 0.00 | -25716.50 | 0.00 | 0.00 | 14105.24 | 3398.57 | 6747.90 | 1824.60 | 0.00 | 527.76 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -887.58 |
DINING_FLR_6 | 16-AUG-18:10 | 0.00 | 0.00 | 0.00 | -27059.00 | 0.00 | 0.00 | 14057.43 | 3398.57 | 6747.90 | 1803.77 | 0.00 | 526.36 | 524.96 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 30-JUL-10:35 | 0.00 | 0.00 | 0.00 | -32121.77 | 0.00 | 0.00 | 464.17 | 340.26 | 24459.16 | 3591.24 | 0.00 | 493.98 | 2772.96 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 16-JUL-10:35 | 0.00 | 0.00 | 0.00 | -9394.37 | 0.00 | 0.00 | 516.68 | 452.48 | 0.00 | 2173.39 | 0.00 | 427.47 | 5824.35 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 16-AUG-18:02 | 0.00 | -213457.66 | 0.00 | -269736.84 | 0.00 | 0.00 | 84538.67 | 82800.17 | 122526.13 | 62478.51 | 0.00 | 21216.89 | 109634.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 16-DEC-09:03 | 3954.28 | 631.94 | 0.00 | -631.94 | 0.00 | 0.00 | 138.66 | 879.71 | 653.23 | 1825.11 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -4.54 | -7446.46 |
ROOM_2_FLR_3 | 11-FEB-09:03 | 3799.72 | 602.81 | 0.00 | -602.81 | 0.00 | 0.00 | 139.49 | 879.61 | 653.15 | 796.13 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -46.80 | -6221.30 |
ROOM_3_MULT19_FLR_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 07-FEB-09:05 | 26603.47 | 8572.22 | 0.00 | -8572.22 | 0.00 | 0.00 | 1728.76 | 8255.72 | 8433.45 | 6347.00 | 0.00 | 829.65 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -52198.04 |
ROOM_5_FLR_3 | 01-MAR-09:04 | 3408.44 | 632.78 | 0.00 | -632.78 | 0.00 | 0.00 | 87.20 | 691.20 | 453.05 | 2821.56 | 0.00 | 310.48 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -7771.92 |
ROOM_6_FLR_3 | 23-FEB-19:04 | 3515.41 | 631.57 | 0.00 | -631.57 | 0.00 | 0.00 | 335.57 | 1397.95 | 516.20 | 0.00 | 0.00 | 162.53 | 0.00 | 0.00 | -6.04 | 0.00 | 0.00 | -5921.62 |
CORRIDOR_FLR_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 22-MAR-08:03 | 1010.04 | 157.22 | 0.00 | -157.22 | 0.00 | 0.00 | 22.85 | 172.80 | 113.26 | 261.16 | 0.00 | 29.70 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1609.82 |
ROOM_2_FLR_6 | 09-MAR-09:03 | 898.32 | 157.82 | 0.00 | -157.82 | 0.00 | 0.00 | 23.12 | 172.78 | 113.25 | 313.36 | 0.00 | 12.17 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1533.00 |
ROOM_3_MULT9_FLR_6 | 02-MAY-08:04 | 4652.19 | 1016.91 | 0.00 | -1016.91 | 0.00 | 0.00 | 196.27 | 977.65 | 998.70 | 1873.40 | 0.00 | 293.43 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -8991.64 |
BANQUET_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 01-MAR-09:04 | -127939.31 | 169134.02 | 0.00 | -169134.02 | 0.00 | 0.00 | 24159.18 | 41166.03 | 88631.48 | 50133.79 | 0.00 | 7239.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -83390.40 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:58:09
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV WITH REHEAT | 23.5670 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 23.4727 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
FLR_3_DOAS | 2.0513 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.0513 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV WITH REHEAT | 23.4727 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 23.4727 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
FLR_3_DOAS | 2.0513 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.0513 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | VAV WITH REHEAT | 0.000000 | 106.4990 | 0.000432 | 1978.83 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | 0.000000 | 10.8290 | 0.001181 | 67.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | 0.000000 | 12.5400 | 0.001181 | 77.67 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
MECH_FLR_1 | VAV WITH REHEAT | 0.000000 | 2.6520 | 0.000000 | 164.24 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | 0.000000 | 2.0400 | 0.000610 | 94.76 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | 0.000000 | 8.4000 | 0.000000 | 78.04 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | 0.000000 | 142.3000 | 0.003581 | 188.86 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | 0.000000 | 422.4350 | 0.001448 | 1308.19 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1863.81 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1864.32 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | 0.000000 | 83.8280 | 0.000305 | 1557.62 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000396 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000396 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.000000 | 13.5000 | 0.000449 | 220.77 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003581 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DINING_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003581 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | 0.000000 | 22.2380 | 0.003556 | 103.30 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | 0.000000 | 22.1800 | 0.000305 | 412.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV WITH REHEAT | 0.00 | 0.001045 | 6694.0231 | 0.0000 | 0.0000 | 0.0000 | |
FLR_3_DOAS | 0.00 | 0.000441 | 4651.2638 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.8998 | 2.8998 | 2.8882 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4022 | 0.4022 | 0.4006 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2650 | 0.2650 | 0.2639 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3053 | 0.3053 | 0.3041 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1557 | 0.1557 | 0.1550 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.3195 | 3.3195 | 3.3062 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.5959 | 1.5959 | 1.5896 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.1105 | 5.1105 | 5.0900 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8371 | 0.8371 | 0.8371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8373 | 0.8373 | 0.8373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4038 | 1.4038 | 1.3982 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0992 | 0.0992 | 0.0992 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.3964 | 2.3964 | 2.3868 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.5072 | 2.5072 | 2.4972 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.3622 | 2.3622 | 2.3527 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8436 | 0.8436 | 0.8402 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV WITH REHEAT | 23.5670 | 23.4727 | 23.5670 | 23.4727 | 0.0000 | 1.0000 |
FLR_3_DOAS | 2.0513 | 2.0513 | 2.0513 | 2.0513 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.8882 | 2.8882 | 2.8882 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4006 | 0.4006 | 0.4006 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2639 | 0.2639 | 0.2639 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3041 | 0.3041 | 0.3041 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1550 | 0.1550 | 0.1550 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.3062 | 3.3062 | 3.3062 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.5896 | 1.5896 | 1.5896 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.0900 | 5.0900 | 5.0900 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8371 | 0.8371 | 0.8371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8373 | 0.8373 | 0.8373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3982 | 1.3982 | 1.3982 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0992 | 0.0992 | 0.0992 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.3868 | 2.3868 | 2.3868 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.4972 | 2.4972 | 2.4972 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.3527 | 2.3527 | 2.3527 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8402 | 0.8402 | 0.8402 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV WITH REHEAT | 23.4727 | 23.4727 | 23.4727 | 23.4727 | 0.0000 | 1.0000 |
FLR_3_DOAS | 2.0513 | 2.0513 | 2.0513 | 2.0513 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:58:09
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Dubai Intl AP - ARE IWEC2 WMO#=411940 |
Total gross floor area [m2] | 11345.29 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 1978.83 | 1978.83 | 0.00 | 168.00 |
RETAIL_1_FLR_1 | 67.07 | 67.07 | 0.00 | 168.00 |
RETAIL_2_FLR_1 | 77.67 | 77.67 | 0.00 | 168.00 |
MECH_FLR_1 | 164.24 | 164.24 | 0.00 | 168.00 |
STORAGE_FLR_1 | 94.76 | 94.76 | 0.00 | 168.00 |
LAUNDRY_FLR_1 | 78.04 | 78.04 | 0.00 | 168.00 |
CAFE_FLR_1 | 188.86 | 188.86 | 0.00 | 168.00 |
LOBBY_FLR_1 | 1308.19 | 1308.19 | 0.00 | 168.00 |
ROOM_1_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT19_FLR_3 | 24.52 | 24.52 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 24.53 | 24.53 | 0.00 | 168.00 |
ROOM_5_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_6_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
CORRIDOR_FLR_3 | 389.40 | 389.40 | 0.00 | 168.00 |
ROOM_1_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT9_FLR_6 | 24.53 | 24.53 | 0.00 | 168.00 |
BANQUET_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
DINING_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
KITCHEN_FLR_6 | 103.30 | 103.30 | 0.00 | 168.00 |
CORRIDOR_FLR_6 | 412.12 | 412.12 | 0.00 | 168.00 |
Totals | 11345.29 | 11345.29 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 13.33 |
Number of hours not met | 13.33 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 580.44 | 94309.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 6426.54 | 552381.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 1174.11 | 93091.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 262.70 | 16690.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 959.56 | 59492.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 762.04 | 29240.64 | 1198.64 | 74976.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 16.27 | 515.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 13.43 | 425.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Laundry | 0.00 | 0.00 | 590.20 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 32.92 | 1912.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 616.11 | 37691.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 30.65 | 972.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 2043.20 | 85614.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 464.43 | 18680.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- General | 569.53 | 18408.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 90.77 | 4739.38 | 2473.10 | 221365.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 18.27 | 2271.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 22.60 | 1891.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 34.77 | 1200.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 1826.94 | 13537.92 |
Natural Gas | 1788.84 | 4842.38 |
Additional | 0.00 | 0.00 |
Total | 3615.78 | 18380.30 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 103.49 |
Space Heating | 0.00 |
Space Cooling | 566.45 |
Fans (All) | 180.09 |
Service Water Heating | 8.00 |
Receptacle Equipment | 154.36 |
Miscellaneous (All) | 1193.26 |
Subtotal | 1193.26 |
Natural Gas [MJ/m2] | |
Space Heating | 51.16 |
Service Water Heating | 217.98 |
Miscellaneous (All) | 426.82 |
Subtotal | 426.82 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 6.39 |
Space Heating | 3.16 |
Space Cooling | 34.96 |
Fans (All) | 11.12 |
Service Water Heating | 13.95 |
Receptacle Equipment | 19.26 |
Miscellaneous | 11.16 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_KITCHEN | 3061. | 8760. |
LTG_SCH_DINING | 3061. | 8760. |
LTG_SCH_BASEMENT | 2655. | 8760. |
LTG_SCH_LOBBY | 3061. | 8760. |
LTG_SCH_STORAGE | 1339. | 8760. |
LTG_SCH_MECHANIC | 3061. | 8760. |
LTG_SCH_LAUNDRY | 2678. | 8760. |
LTG_SCH_GUESTROOM | 3599. | 8760. |
LTG_SCH_CORRIDOR | 3061. | 8760. |
LTG_SCH_RETAIL | 2678. | 8760. |
WALKIN_OCC_LGHT_SCH_1 | 3061. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
BASEMENT_EQUIP_SCH | 3924. | 8760. |
BLDG_EQUIP_SCH | 3924. | 8760. |
GUESTROOM_EQP_SCH_BASE | 3239. | 8760. |
GUESTROOM_EQP_SCH_ADVA | 2762. | 8760. |
LOBBY_EQP_SCH | 3292. | 8760. |
OFFICE_EQP_SCH | 4941. | 8760. |
EMPLOYEELOUNGE_EQP_SCH | 4044. | 8760. |
LAUNDRYROOM_EQP_ELEC_SCH | 2920. | 2920. |
LAUNDRYROOM_EQP_GAS_SCH | 2920. | 2920. |
MEETINGROOM_EQP_SCH | 1336. | 4745. |
EXERCISEROOM_EQP_SCH | 3832. | 5840. |
KITCHEN_ELEC_EQUIP_SCH | 2172. | 8760. |
KITCHEN_GAS_EQUIP_SCH | 1332. | 8760. |
KITCHEN_EXHAUST_SCH | 6205. | 6205. |
BLDG_ELEVATORS | 2270. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_OCC_SCH | 5026. | 8760. |
GUESTROOM_OCC_SCH | 5515. | 8760. |
LOBBY_OCC_SCH | 2304. | 8760. |
OFFICE_OCC_SCH | 3954. | 8760. |
EMPLOYEELOUNGE_OCC_SCH | 948. | 5475. |
MEETINGROOM_OCC_SCH | 1168. | 4745. |
LAUNDRYROOM_OCC_SCH | 427. | 2920. |
EXERCISEROOM_OCC_SCH | 5292. | 5840. |
INFIL_SCH | 8760. | 8760. |
INFIL_HALF_ON_SCH | 4380. | 8760. |
INFIL_QUARTER_ON_SCH | 2190. | 8760. |
LAUNDRY_SWH_SCH | 2555. | 2555. |
BLDG_SWH_SCH | 3301. | 8760. |
GUESTROOM_SWH_SCH | 2899. | 8760. |
LAUNDRYROOM_SWH_SCH | 2920. | 2920. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
ALWAYS_ON | 8760. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
OCC_GUESTROOM_VENT_CTRL_30MIN | 6570. | 6570. |
OCC_GUESTROOM_VENT_CTRL_20MIN | 6327. | 6327. |
VAC_GUESTROOM_VENTILATION_SCHEDULE | 365. | 365. |
MINOA_MOTORIZEDDAMPER_SCHED | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
ROOM_1_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
FLR_3_DOAS_OAMINOAFRACSCHEDULE | 8760. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 0. | 0. |
LAUNDRY_FLR_1 EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 0. | 0. |
SLIDING_DOORS_VENTILATION_AVAILABILITY_SCH | 3285. | 3285. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
VACGUESTROOM_HTGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 18.89 | 365 | 18.89 | 365 |
VACGUESTROOM_CLGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 23.33 | 365 |
OBCRESET_S_OCCGUESTROOM_HTGSP_SCH_30MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_S_OCCGUESTROOM_CLGSP_SCH_30MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_HTGSP_SCH_30MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_CLGSP_SCH_30MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
HTGSETP_SCH | BASEMENT DUAL SP CONTROL | January | 21.00 | 365 | 21.00 | 365 |
CLGSETP_SCH | BASEMENT DUAL SP CONTROL | July | 24.00 | 365 | 24.00 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:58:09
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Average | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Sum | 192720.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 529331.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 50179.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 59156.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8977.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 5588.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 37203.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 710417.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 2115429.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 100358.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 108269.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 105946.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 2115429.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Average | 288887.05 | 0.00 | 0.00 | 0.00 | 0.00 |
Sum | 6355515.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 8759.67 | 0.33 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8759.67 | 0.33 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8759.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 0.33 | 0.00 | 0.00 | 0.00 |
Average | 8759.97 | 0.03 | 0.00 | 0.00 | 0.00 |
Sum | 192719.33 | 0.67 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 529331.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 50179.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 59156.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8977.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 5588.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 37203.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 710417.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 2115429.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 100358.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 108269.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 105946.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 2115429.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Average | 288887.05 | 0.00 | 0.00 | 0.00 | 0.00 |
Sum | 6355515.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:58:09
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:58:09
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2012
For: Environment
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
For: Environment
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 0B
For: Environment
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY ARE_DUBAI_DUBAIINTL
For: Environment
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.530730E+11 | 23602.19 | 23-JAN-19:10 | 22.42 | 18.03 | 0.628138E+10 | 3889.86 | 20-JAN-22:10 | 22.42 | 18.03 |
February | 0.446337E+11 | 23802.06 | 08-FEB-19:10 | 24.33 | 20.46 | 0.558876E+10 | 3840.08 | 01-FEB-22:10 | 24.33 | 20.46 |
March | 0.449905E+11 | 23982.69 | 01-MAR-19:20 | 28.73 | 20.89 | 0.615907E+10 | 3742.19 | 02-MAR-22:10 | 20.67 | 19.07 |
April | 0.415983E+11 | 23645.97 | 27-APR-19:20 | 31.50 | 21.48 | 0.592492E+10 | 3701.05 | 05-APR-21:10 | 31.50 | 21.48 |
May | 0.450904E+11 | 24911.78 | 31-MAY-20:00 | 40.60 | 20.99 | 0.612766E+10 | 3718.24 | 12-MAY-22:10 | 40.60 | 20.99 |
June | 0.463167E+11 | 25260.59 | 28-JUN-19:10 | 36.00 | 26.30 | 0.595585E+10 | 3753.01 | 30-JUN-22:10 | 31.88 | 26.12 |
July | 0.515636E+11 | 26243.91 | 13-JUL-18:30 | 39.35 | 24.98 | 0.617239E+10 | 3808.47 | 28-JUL-22:10 | 33.25 | 28.47 |
August | 0.567309E+11 | 27969.70 | 16-AUG-18:10 | 40.97 | 26.89 | 0.632834E+10 | 3900.78 | 25-AUG-22:10 | 32.93 | 29.41 |
September | 0.561576E+11 | 27179.95 | 13-SEP-18:10 | 35.73 | 26.47 | 0.616210E+10 | 3939.94 | 22-SEP-22:10 | 30.55 | 26.73 |
October | 0.594768E+11 | 27319.45 | 09-OCT-10:35 | 35.10 | 22.00 | 0.647413E+10 | 4015.70 | 27-OCT-22:10 | 27.58 | 23.44 |
November | 0.572022E+11 | 26685.45 | 05-NOV-10:35 | 31.33 | 19.23 | 0.632122E+10 | 4045.54 | 22-NOV-22:10 | 22.25 | 16.62 |
December | 0.562630E+11 | 25082.13 | 03-DEC-11:35 | 27.33 | 18.33 | 0.640838E+10 | 4009.47 | 01-DEC-22:10 | 27.33 | 18.33 |
Annual Sum or Average | 0.613097E+12 | 0.739042E+11 | ||||||||
Minimum of Months | 0.415983E+11 | 23602.19 | 22.42 | 18.03 | 0.558876E+10 | 3701.05 | 20.67 | 16.62 | ||
Maximum of Months | 0.594768E+11 | 27969.70 | 40.97 | 26.89 | 0.647413E+10 | 4045.54 | 40.60 | 29.41 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.427833E+10 | 3343.83 | 28-JAN-11:35 | 25.33 | 14.47 | 0.619731E+09 | 364.27 | 11-JAN-04:49 | 25.33 | 14.47 |
February | 0.423130E+10 | 3707.44 | 05-FEB-11:35 | 30.33 | 18.87 | 0.560976E+09 | 364.27 | 04-FEB-04:49 | 30.33 | 18.87 |
March | 0.515322E+10 | 3509.39 | 27-MAR-10:35 | 37.00 | 18.58 | 0.623366E+09 | 375.41 | 27-MAR-21:30 | 28.45 | 15.80 |
April | 0.568108E+10 | 3541.04 | 28-APR-10:35 | 39.57 | 18.31 | 0.601731E+09 | 383.38 | 28-APR-21:40 | 30.27 | 17.92 |
May | 0.716865E+10 | 3868.76 | 31-MAY-18:10 | 40.35 | 22.36 | 0.626433E+09 | 400.35 | 31-MAY-21:40 | 34.87 | 22.78 |
June | 0.735799E+10 | 3893.42 | 10-JUN-10:35 | 38.30 | 26.21 | 0.610271E+09 | 404.11 | 09-JUN-21:49 | 38.30 | 26.21 |
July | 0.817961E+10 | 4094.00 | 30-JUL-10:35 | 44.13 | 22.13 | 0.638628E+09 | 417.39 | 21-JUL-21:49 | 44.13 | 22.13 |
August | 0.842362E+10 | 4161.13 | 05-AUG-10:35 | 42.43 | 25.20 | 0.649320E+09 | 413.95 | 16-AUG-22:10 | 34.08 | 27.89 |
September | 0.768237E+10 | 4008.17 | 04-SEP-10:35 | 38.00 | 23.07 | 0.616748E+09 | 403.86 | 06-SEP-21:40 | 33.87 | 27.73 |
October | 0.738785E+10 | 3971.03 | 09-OCT-10:35 | 35.10 | 22.00 | 0.631527E+09 | 393.72 | 05-OCT-21:40 | 35.10 | 22.00 |
November | 0.609915E+10 | 3829.81 | 06-NOV-11:35 | 32.33 | 20.70 | 0.603979E+09 | 380.63 | 01-NOV-21:40 | 32.33 | 20.70 |
December | 0.482219E+10 | 3564.64 | 03-DEC-11:35 | 27.33 | 18.33 | 0.620605E+09 | 364.24 | 01-DEC-00:49 | 27.33 | 18.33 |
Annual Sum or Average | 0.764654E+11 | 0.740331E+10 | ||||||||
Minimum of Months | 0.423130E+10 | 3343.83 | 25.33 | 14.47 | 0.560976E+09 | 364.24 | 25.33 | 14.47 | ||
Maximum of Months | 0.842362E+10 | 4161.13 | 44.13 | 26.21 | 0.649320E+09 | 417.39 | 44.13 | 27.89 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.375138E+10 | 2021.18 | 24-JAN-21:00 | 21.00 | 17.21 | 0.721882E+09 | 443.68 | 24-JAN-22:19 | 20.20 | 16.37 |
February | 0.355659E+10 | 2144.87 | 06-FEB-19:02 | 24.08 | 21.36 | 0.654124E+09 | 454.25 | 07-FEB-22:19 | 24.27 | 19.97 |
March | 0.420641E+10 | 2358.49 | 27-MAR-18:10 | 32.92 | 18.22 | 0.730861E+09 | 465.50 | 27-MAR-22:10 | 27.92 | 15.44 |
April | 0.438140E+10 | 2398.00 | 27-APR-18:10 | 32.83 | 21.90 | 0.709564E+09 | 472.56 | 28-APR-22:10 | 29.75 | 17.96 |
May | 0.501749E+10 | 2554.58 | 31-MAY-18:10 | 40.35 | 22.36 | 0.747528E+09 | 481.82 | 31-MAY-22:10 | 34.02 | 23.07 |
June | 0.502276E+10 | 2539.48 | 01-JUN-18:10 | 36.65 | 23.81 | 0.731465E+09 | 485.08 | 09-JUN-22:10 | 34.25 | 25.66 |
July | 0.537007E+10 | 2580.85 | 31-JUL-18:10 | 39.88 | 25.61 | 0.758828E+09 | 491.10 | 21-JUL-22:10 | 39.88 | 25.61 |
August | 0.546575E+10 | 2638.39 | 16-AUG-18:10 | 40.97 | 26.89 | 0.766896E+09 | 489.28 | 16-AUG-22:10 | 34.08 | 27.89 |
September | 0.505003E+10 | 2510.81 | 06-SEP-18:10 | 35.97 | 26.92 | 0.729250E+09 | 483.69 | 05-SEP-22:10 | 35.97 | 26.92 |
October | 0.495163E+10 | 2428.45 | 05-OCT-18:10 | 34.72 | 22.85 | 0.742873E+09 | 475.34 | 05-OCT-22:10 | 31.67 | 25.32 |
November | 0.438369E+10 | 2310.58 | 01-NOV-18:10 | 30.93 | 24.44 | 0.706947E+09 | 465.98 | 01-NOV-22:10 | 30.00 | 24.30 |
December | 0.397711E+10 | 2139.53 | 06-DEC-19:03 | 25.17 | 19.65 | 0.723505E+09 | 451.24 | 05-DEC-22:19 | 25.17 | 19.65 |
Annual Sum or Average | 0.551343E+11 | 0.872372E+10 | ||||||||
Minimum of Months | 0.355659E+10 | 2021.18 | 21.00 | 17.21 | 0.654124E+09 | 443.68 | 20.20 | 15.44 | ||
Maximum of Months | 0.546575E+10 | 2638.39 | 40.97 | 26.92 | 0.766896E+09 | 491.10 | 39.88 | 27.89 |
Report: ZoneCoolingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.323378E+10 | 2217.05 | 24-JAN-21:00 | 21.00 | 17.21 | 0.151709E+09 | 90.12 | 23-JAN-22:10 | 21.00 | 17.21 |
February | 0.323163E+10 | 2356.25 | 06-FEB-20:10 | 24.00 | 20.97 | 0.137254E+09 | 92.14 | 07-FEB-22:10 | 24.33 | 19.98 |
March | 0.410067E+10 | 2624.38 | 27-MAR-18:02 | 32.92 | 18.22 | 0.152863E+09 | 94.07 | 27-MAR-22:10 | 27.92 | 15.44 |
April | 0.463672E+10 | 2728.47 | 27-APR-18:10 | 32.83 | 21.90 | 0.148130E+09 | 96.24 | 28-APR-22:10 | 29.75 | 17.96 |
May | 0.581875E+10 | 2946.34 | 31-MAY-18:10 | 40.35 | 22.36 | 0.155784E+09 | 98.99 | 31-MAY-22:10 | 34.02 | 23.07 |
June | 0.596889E+10 | 2969.89 | 10-JUN-10:35 | 38.30 | 26.21 | 0.153290E+09 | 99.92 | 09-JUN-22:10 | 38.30 | 26.21 |
July | 0.642239E+10 | 3119.11 | 22-JUL-10:35 | 41.47 | 23.66 | 0.160145E+09 | 102.31 | 21-JUL-22:10 | 41.47 | 23.66 |
August | 0.647732E+10 | 3127.27 | 06-AUG-10:35 | 39.23 | 24.40 | 0.161531E+09 | 101.57 | 04-AUG-22:10 | 39.23 | 24.40 |
September | 0.582845E+10 | 2917.37 | 04-SEP-10:35 | 38.00 | 23.07 | 0.151795E+09 | 99.20 | 05-SEP-22:10 | 33.17 | 27.93 |
October | 0.548059E+10 | 2766.67 | 05-OCT-18:10 | 34.72 | 22.85 | 0.154053E+09 | 96.61 | 05-OCT-22:10 | 31.67 | 25.32 |
November | 0.449208E+10 | 2601.77 | 01-NOV-18:02 | 30.93 | 24.44 | 0.147524E+09 | 94.23 | 01-NOV-22:10 | 30.00 | 24.30 |
December | 0.366936E+10 | 2331.81 | 06-DEC-20:10 | 25.00 | 19.73 | 0.151815E+09 | 91.38 | 11-DEC-22:10 | 24.25 | 21.52 |
Annual Sum or Average | 0.593606E+11 | 0.182589E+10 | ||||||||
Minimum of Months | 0.323163E+10 | 2217.05 | 21.00 | 17.21 | 0.137254E+09 | 90.12 | 21.00 | 15.44 | ||
Maximum of Months | 0.647732E+10 | 3127.27 | 41.47 | 26.21 | 0.161531E+09 | 102.31 | 41.47 | 27.93 |
Report: ZoneCoolingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.135963E+10 | 877.78 | 23-JAN-22:00 | 21.40 | 17.31 | 0.116691E+09 | 68.58 | 25-JAN-02:09 | 20.00 | 14.61 |
February | 0.141077E+10 | 1067.77 | 07-FEB-22:00 | 24.40 | 19.99 | 0.105502E+09 | 68.59 | 07-FEB-22:19 | 24.27 | 19.97 |
March | 0.186832E+10 | 1243.52 | 27-MAR-20:00 | 31.00 | 16.56 | 0.117265E+09 | 70.24 | 27-MAR-22:10 | 27.92 | 15.44 |
April | 0.221009E+10 | 1294.15 | 28-APR-18:02 | 34.08 | 21.01 | 0.113297E+09 | 71.81 | 28-APR-22:10 | 29.75 | 17.96 |
May | 0.290476E+10 | 1475.94 | 31-MAY-18:10 | 40.35 | 22.36 | 0.118616E+09 | 73.94 | 31-MAY-22:10 | 34.02 | 23.07 |
June | 0.300600E+10 | 1523.81 | 10-JUN-10:35 | 38.30 | 26.21 | 0.116604E+09 | 74.63 | 09-JUN-22:10 | 38.30 | 26.21 |
July | 0.324397E+10 | 1599.07 | 22-JUL-10:35 | 41.47 | 23.66 | 0.122001E+09 | 76.57 | 21-JUL-22:10 | 41.47 | 23.66 |
August | 0.327072E+10 | 1601.97 | 05-AUG-10:35 | 42.43 | 25.20 | 0.123083E+09 | 75.87 | 04-AUG-22:10 | 42.43 | 25.20 |
September | 0.292936E+10 | 1492.33 | 04-SEP-10:35 | 38.00 | 23.07 | 0.115616E+09 | 74.11 | 05-SEP-22:10 | 33.17 | 27.93 |
October | 0.270793E+10 | 1341.98 | 05-OCT-18:30 | 34.15 | 23.49 | 0.117515E+09 | 72.19 | 05-OCT-22:10 | 31.67 | 25.32 |
November | 0.212548E+10 | 1234.91 | 01-NOV-20:00 | 30.00 | 22.92 | 0.112958E+09 | 70.54 | 01-NOV-22:10 | 30.00 | 24.30 |
December | 0.161307E+10 | 1003.84 | 11-DEC-22:00 | 24.30 | 21.59 | 0.116692E+09 | 68.58 | 27-DEC-04:00 | 21.00 | 15.46 |
Annual Sum or Average | 0.286501E+11 | 0.139584E+10 | ||||||||
Minimum of Months | 0.135963E+10 | 877.78 | 21.40 | 16.56 | 0.105502E+09 | 68.58 | 20.00 | 14.61 | ||
Maximum of Months | 0.327072E+10 | 1601.97 | 42.43 | 26.21 | 0.123083E+09 | 76.57 | 42.43 | 27.93 |
Report: ZoneCoolingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.514449E+11 | 36349.30 | 24-JAN-21:00 | 21.00 | 17.21 | 0.509556E+09 | 381.81 | 03-JAN-22:10 | 21.00 | 17.21 |
February | 0.469284E+11 | 36758.45 | 07-FEB-21:00 | 25.00 | 20.23 | 0.460529E+09 | 381.79 | 10-FEB-22:10 | 19.33 | 12.88 |
March | 0.528630E+11 | 37506.27 | 27-MAR-20:00 | 31.00 | 16.56 | 0.512128E+09 | 381.79 | 03-MAR-22:10 | 31.00 | 16.56 |
April | 0.521399E+11 | 37754.34 | 28-APR-20:00 | 33.00 | 18.35 | 0.492515E+09 | 381.75 | 28-APR-21:10 | 30.82 | 17.97 |
May | 0.555793E+11 | 38535.87 | 31-MAY-20:00 | 40.60 | 20.99 | 0.508791E+09 | 381.71 | 16-MAY-21:10 | 40.60 | 20.99 |
June | 0.542860E+11 | 38370.95 | 01-JUN-20:00 | 34.00 | 25.28 | 0.493316E+09 | 381.67 | 06-JUN-21:10 | 31.02 | 23.76 |
July | 0.564581E+11 | 38657.04 | 21-JUL-20:00 | 41.00 | 20.45 | 0.506085E+09 | 381.42 | 28-JUL-21:10 | 33.88 | 28.57 |
August | 0.568049E+11 | 38797.52 | 10-AUG-20:00 | 40.00 | 26.72 | 0.509683E+09 | 381.46 | 25-AUG-21:10 | 33.83 | 29.33 |
September | 0.539432E+11 | 38243.74 | 06-SEP-20:00 | 34.90 | 27.67 | 0.491491E+09 | 381.68 | 29-SEP-21:10 | 29.82 | 26.37 |
October | 0.548178E+11 | 37948.11 | 05-OCT-20:00 | 33.00 | 25.07 | 0.508127E+09 | 381.72 | 31-OCT-21:10 | 27.93 | 20.76 |
November | 0.518107E+11 | 37389.24 | 01-NOV-20:00 | 30.00 | 22.92 | 0.492315E+09 | 381.76 | 21-NOV-22:10 | 21.67 | 16.24 |
December | 0.519123E+11 | 36624.96 | 05-DEC-21:00 | 25.00 | 22.11 | 0.508932E+09 | 381.79 | 19-DEC-22:10 | 19.42 | 14.95 |
Annual Sum or Average | 0.638989E+12 | 0.599347E+10 | ||||||||
Minimum of Months | 0.469284E+11 | 36349.30 | 21.00 | 16.56 | 0.460529E+09 | 381.42 | 19.33 | 12.88 | ||
Maximum of Months | 0.568049E+11 | 38797.52 | 41.00 | 27.67 | 0.512128E+09 | 381.81 | 40.60 | 29.33 |
Report: ZoneCoolingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.248973E+11 | 13028.04 | 28-JAN-11:35 | 25.33 | 14.47 | 0.819702E+10 | 5079.44 | 24-JAN-22:40 | 25.33 | 14.47 |
February | 0.233153E+11 | 14369.25 | 05-FEB-11:35 | 30.33 | 18.87 | 0.744902E+10 | 5260.07 | 07-FEB-22:40 | 24.13 | 19.94 |
March | 0.266763E+11 | 14063.67 | 27-MAR-18:03 | 32.92 | 18.22 | 0.834087E+10 | 5394.10 | 27-MAR-21:40 | 28.27 | 15.67 |
April | 0.272635E+11 | 14056.07 | 27-APR-18:05 | 32.83 | 21.90 | 0.811397E+10 | 5481.96 | 28-APR-21:40 | 30.27 | 17.92 |
May | 0.309470E+11 | 15424.80 | 31-MAY-18:10 | 40.35 | 22.36 | 0.858930E+10 | 5623.29 | 31-MAY-21:40 | 34.87 | 22.78 |
June | 0.308137E+11 | 15107.15 | 01-JUN-18:10 | 36.65 | 23.81 | 0.841500E+10 | 5655.86 | 09-JUN-21:49 | 34.58 | 25.83 |
July | 0.333040E+11 | 15626.14 | 31-JUL-18:10 | 39.88 | 25.61 | 0.878256E+10 | 5768.06 | 21-JUL-22:10 | 39.88 | 25.61 |
August | 0.340593E+11 | 15993.55 | 16-AUG-18:10 | 40.97 | 26.89 | 0.890375E+10 | 5743.99 | 16-AUG-22:10 | 34.08 | 27.89 |
September | 0.320008E+11 | 15038.84 | 06-SEP-18:10 | 35.97 | 26.92 | 0.847259E+10 | 5665.28 | 06-SEP-22:10 | 33.67 | 27.24 |
October | 0.320155E+11 | 15135.76 | 09-OCT-10:35 | 35.10 | 22.00 | 0.864594E+10 | 5586.61 | 05-OCT-21:40 | 35.10 | 22.00 |
November | 0.287470E+11 | 14553.16 | 19-NOV-11:35 | 30.00 | 16.27 | 0.815558E+10 | 5484.02 | 01-NOV-22:10 | 30.00 | 16.27 |
December | 0.262155E+11 | 13879.33 | 03-DEC-11:35 | 27.33 | 18.33 | 0.824253E+10 | 5209.97 | 05-DEC-22:40 | 23.00 | 20.68 |
Annual Sum or Average | 0.350255E+12 | 0.100308E+12 | ||||||||
Minimum of Months | 0.233153E+11 | 13028.04 | 25.33 | 14.47 | 0.744902E+10 | 5079.44 | 23.00 | 14.47 | ||
Maximum of Months | 0.340593E+11 | 15993.55 | 40.97 | 26.92 | 0.890375E+10 | 5768.06 | 39.88 | 27.89 |
Report: ZoneCoolingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.831073E+11 | 40478.89 | 23-JAN-19:10 | 22.42 | 18.03 | 0.246900E+11 | 15572.83 | 24-JAN-22:40 | 20.10 | 16.28 |
February | 0.773445E+11 | 42242.25 | 06-FEB-19:10 | 24.08 | 21.36 | 0.224344E+11 | 15928.09 | 07-FEB-22:40 | 24.13 | 19.94 |
March | 0.886014E+11 | 45874.93 | 27-MAR-18:10 | 32.92 | 18.22 | 0.251641E+11 | 16190.15 | 27-MAR-21:49 | 28.08 | 15.55 |
April | 0.899819E+11 | 46571.73 | 27-APR-18:10 | 32.83 | 21.90 | 0.244858E+11 | 16433.06 | 28-APR-21:49 | 30.08 | 17.90 |
May | 0.100579E+12 | 49674.73 | 31-MAY-18:10 | 40.35 | 22.36 | 0.258252E+11 | 16717.22 | 31-MAY-22:10 | 34.02 | 23.07 |
June | 0.100143E+12 | 49235.74 | 01-JUN-18:10 | 36.65 | 23.81 | 0.252639E+11 | 16822.67 | 09-JUN-22:10 | 34.25 | 25.66 |
July | 0.106778E+12 | 50178.93 | 31-JUL-18:10 | 39.88 | 25.61 | 0.262061E+11 | 17017.22 | 21-JUL-22:10 | 39.88 | 25.61 |
August | 0.108382E+12 | 51059.83 | 16-AUG-18:10 | 40.97 | 26.89 | 0.264618E+11 | 16959.98 | 18-AUG-22:10 | 35.58 | 25.76 |
September | 0.101443E+12 | 48647.64 | 06-SEP-18:10 | 35.97 | 26.92 | 0.252105E+11 | 16774.91 | 06-SEP-22:10 | 33.67 | 27.24 |
October | 0.101200E+12 | 47367.41 | 05-OCT-18:10 | 34.72 | 22.85 | 0.257423E+11 | 16579.71 | 05-OCT-22:10 | 31.67 | 25.32 |
November | 0.919038E+11 | 45272.16 | 01-NOV-18:10 | 30.93 | 24.44 | 0.244696E+11 | 16333.27 | 01-NOV-22:10 | 30.00 | 24.30 |
December | 0.866171E+11 | 41941.43 | 06-DEC-19:10 | 25.17 | 19.65 | 0.248467E+11 | 15814.61 | 05-DEC-22:40 | 25.17 | 19.65 |
Annual Sum or Average | 0.113608E+13 | 0.300800E+12 | ||||||||
Minimum of Months | 0.773445E+11 | 40478.89 | 22.42 | 18.03 | 0.224344E+11 | 15572.83 | 20.10 | 15.55 | ||
Maximum of Months | 0.108382E+12 | 51059.83 | 40.97 | 26.92 | 0.264618E+11 | 17017.22 | 39.88 | 27.24 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.113350E+10 | 3699.14 | 16-JAN-16:01 | 23.83 | 13.09 | 98128470.90 | 56.69 | 05-JAN-22:10 | 23.83 | 13.09 |
February | 0.129433E+10 | 3572.62 | 23-FEB-19:01 | 24.50 | 16.52 | 88825723.02 | 56.69 | 14-FEB-22:10 | 24.50 | 16.52 |
March | 0.187904E+10 | 3581.43 | 20-MAR-18:02 | 25.58 | 17.20 | 98730302.89 | 56.70 | 29-MAR-21:10 | 24.00 | 20.62 |
April | 0.237337E+10 | 3740.58 | 01-APR-15:02 | 32.78 | 16.66 | 95726832.25 | 56.70 | 29-APR-00:20 | 27.77 | 18.07 |
May | 0.338740E+10 | 3687.62 | 26-MAY-15:02 | 34.00 | 24.70 | 99167856.26 | 56.70 | 31-MAY-21:30 | 35.20 | 22.63 |
June | 0.359499E+10 | 3687.35 | 27-JUN-15:02 | 38.23 | 26.51 | 96022854.65 | 56.70 | 09-JUN-21:49 | 38.23 | 26.51 |
July | 0.406591E+10 | 3682.70 | 22-JUL-15:02 | 38.00 | 27.98 | 99140586.32 | 56.70 | 13-JUL-22:10 | 38.00 | 27.98 |
August | 0.420035E+10 | 3689.64 | 02-AUG-15:02 | 38.73 | 28.39 | 99248170.34 | 56.70 | 28-AUG-21:40 | 35.83 | 26.58 |
September | 0.359020E+10 | 3703.86 | 21-SEP-15:02 | 34.87 | 27.39 | 95943341.60 | 56.70 | 01-SEP-21:10 | 34.87 | 27.39 |
October | 0.315804E+10 | 3677.40 | 01-OCT-15:02 | 33.95 | 26.07 | 99099360.29 | 56.70 | 03-OCT-00:40 | 29.00 | 23.27 |
November | 0.226349E+10 | 3767.54 | 18-NOV-16:01 | 30.67 | 15.42 | 95799286.56 | 56.70 | 09-NOV-23:10 | 30.67 | 15.42 |
December | 0.143861E+10 | 3591.52 | 25-DEC-16:01 | 25.33 | 17.33 | 98369553.93 | 56.69 | 01-DEC-23:40 | 25.33 | 17.33 |
Annual Sum or Average | 0.323792E+11 | 0.116420E+10 | ||||||||
Minimum of Months | 0.113350E+10 | 3572.62 | 23.83 | 13.09 | 88825723.02 | 56.69 | 23.83 | 13.09 | ||
Maximum of Months | 0.420035E+10 | 3767.54 | 38.73 | 28.39 | 99248170.34 | 56.70 | 38.23 | 27.98 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.858214E+09 | 3619.32 | 16-JAN-16:01 | 23.83 | 13.09 | 97490144.23 | 56.69 | 27-JAN-22:00 | 18.00 | 14.99 |
February | 0.106269E+10 | 3524.50 | 05-FEB-16:02 | 31.83 | 18.84 | 88506782.71 | 56.69 | 27-FEB-22:30 | 20.25 | 16.08 |
March | 0.169136E+10 | 3514.33 | 20-MAR-18:02 | 25.58 | 17.20 | 98597503.72 | 56.70 | 23-MAR-21:10 | 24.00 | 20.71 |
April | 0.227929E+10 | 3668.45 | 01-APR-15:02 | 32.78 | 16.66 | 95708639.08 | 56.70 | 06-APR-21:40 | 25.93 | 17.58 |
May | 0.338393E+10 | 3630.38 | 26-MAY-15:02 | 34.00 | 24.70 | 99172266.87 | 56.70 | 31-MAY-21:49 | 34.53 | 22.92 |
June | 0.363919E+10 | 3627.25 | 27-JUN-15:02 | 38.23 | 26.51 | 96027460.83 | 56.70 | 09-JUN-22:10 | 38.23 | 26.51 |
July | 0.408158E+10 | 3627.14 | 22-JUL-15:02 | 38.00 | 27.98 | 99141363.46 | 56.70 | 03-JUL-22:10 | 38.00 | 27.98 |
August | 0.413917E+10 | 3639.14 | 02-AUG-15:02 | 38.73 | 28.39 | 99247941.80 | 56.70 | 15-AUG-21:49 | 35.17 | 21.92 |
September | 0.340773E+10 | 3622.03 | 18-SEP-15:02 | 34.95 | 25.62 | 95936517.09 | 56.70 | 01-SEP-21:10 | 34.95 | 25.62 |
October | 0.284178E+10 | 3619.00 | 03-OCT-15:02 | 34.97 | 24.83 | 99057018.31 | 56.70 | 04-OCT-00:10 | 29.00 | 21.77 |
November | 0.191615E+10 | 3687.95 | 18-NOV-16:01 | 30.67 | 15.42 | 95648113.62 | 56.70 | 15-NOV-22:10 | 30.67 | 15.42 |
December | 0.113839E+10 | 3489.66 | 27-DEC-16:01 | 21.83 | 15.42 | 97931083.15 | 56.69 | 07-DEC-22:30 | 21.83 | 15.42 |
Annual Sum or Average | 0.304395E+11 | 0.116246E+10 | ||||||||
Minimum of Months | 0.858214E+09 | 3489.66 | 21.83 | 13.09 | 88506782.71 | 56.69 | 18.00 | 14.99 | ||
Maximum of Months | 0.413917E+10 | 3687.95 | 38.73 | 28.39 | 99247941.80 | 56.70 | 38.23 | 27.98 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.697059E+09 | 560.38 | 28-JAN-13:40 | 27.77 | 13.01 | 0.00 | 0.00 | 01-JAN-00:10 | 27.77 | 13.01 |
February | 0.676255E+09 | 635.25 | 05-FEB-13:40 | 31.43 | 19.44 | 0.00 | 0.00 | 01-FEB-00:10 | 31.43 | 19.44 |
March | 0.817748E+09 | 583.45 | 27-MAR-13:30 | 35.50 | 19.59 | 0.00 | 0.00 | 01-MAR-00:10 | 35.50 | 19.59 |
April | 0.904812E+09 | 587.46 | 28-APR-20:20 | 32.33 | 18.25 | 0.00 | 0.00 | 01-APR-00:10 | 32.33 | 18.25 |
May | 0.114301E+10 | 671.37 | 31-MAY-19:20 | 41.60 | 20.85 | 0.00 | 0.00 | 01-MAY-00:10 | 41.60 | 20.85 |
June | 0.116885E+10 | 662.91 | 09-JUN-20:20 | 36.67 | 26.06 | 0.00 | 0.00 | 01-JUN-00:10 | 36.67 | 26.06 |
July | 0.133178E+10 | 724.02 | 21-JUL-20:20 | 40.67 | 20.38 | 0.00 | 0.00 | 01-JUL-00:10 | 40.67 | 20.38 |
August | 0.139729E+10 | 722.82 | 16-AUG-19:20 | 39.87 | 27.59 | 0.00 | 0.00 | 01-AUG-00:10 | 39.87 | 27.59 |
September | 0.129841E+10 | 707.83 | 26-SEP-13:10 | 40.83 | 22.70 | 0.00 | 0.00 | 01-SEP-00:10 | 40.83 | 22.70 |
October | 0.128395E+10 | 717.83 | 09-OCT-13:20 | 37.40 | 20.06 | 0.00 | 0.00 | 01-OCT-00:10 | 37.40 | 20.06 |
November | 0.106202E+10 | 688.80 | 05-NOV-13:30 | 33.20 | 21.19 | 0.00 | 0.00 | 01-NOV-00:10 | 33.20 | 21.19 |
December | 0.806985E+09 | 640.50 | 03-DEC-13:00 | 29.80 | 17.63 | 0.00 | 0.00 | 01-DEC-00:10 | 29.80 | 17.63 |
Annual Sum or Average | 0.125882E+11 | 0.00 | ||||||||
Minimum of Months | 0.676255E+09 | 560.38 | 27.77 | 13.01 | 0.00 | 0.00 | 27.77 | 13.01 | ||
Maximum of Months | 0.139729E+10 | 724.02 | 41.60 | 27.59 | 0.00 | 0.00 | 41.60 | 27.59 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.684293E+09 | 1349.36 | 16-JAN-16:01 | 23.83 | 13.09 | 97133761.09 | 56.69 | 11-JAN-22:10 | 23.83 | 13.09 |
February | 0.706586E+09 | 1351.39 | 07-FEB-19:02 | 26.67 | 20.05 | 88075248.93 | 56.69 | 27-FEB-22:30 | 20.25 | 16.08 |
March | 0.928235E+09 | 1364.23 | 21-MAR-18:02 | 25.83 | 18.40 | 98114909.18 | 56.69 | 17-MAR-22:10 | 25.83 | 18.40 |
April | 0.109483E+10 | 1392.37 | 28-APR-18:02 | 34.08 | 21.01 | 95435942.64 | 56.70 | 28-APR-21:00 | 29.90 | 17.88 |
May | 0.142633E+10 | 1401.23 | 21-MAY-18:02 | 35.35 | 23.79 | 99002811.25 | 56.70 | 04-MAY-22:10 | 35.35 | 23.79 |
June | 0.149010E+10 | 1380.90 | 01-JUN-18:02 | 36.65 | 23.81 | 95903596.97 | 56.70 | 07-JUN-21:49 | 29.00 | 26.61 |
July | 0.163341E+10 | 1403.59 | 21-JUL-18:02 | 41.83 | 23.77 | 99039574.74 | 56.70 | 21-JUL-23:00 | 35.00 | 27.35 |
August | 0.162478E+10 | 1381.82 | 06-AUG-15:02 | 40.85 | 24.99 | 99134569.87 | 56.70 | 06-AUG-00:40 | 40.85 | 24.99 |
September | 0.139732E+10 | 1378.57 | 04-SEP-18:02 | 37.70 | 25.12 | 95759608.45 | 56.70 | 25-SEP-21:40 | 30.40 | 25.86 |
October | 0.125605E+10 | 1389.17 | 09-OCT-18:02 | 33.78 | 22.64 | 98793564.37 | 56.70 | 02-OCT-21:40 | 33.78 | 22.64 |
November | 0.984420E+09 | 1425.34 | 18-NOV-16:01 | 30.67 | 15.42 | 95255030.52 | 56.69 | 02-NOV-21:10 | 30.67 | 15.42 |
December | 0.779385E+09 | 1360.60 | 11-DEC-19:01 | 25.42 | 18.78 | 97448806.39 | 56.69 | 07-DEC-22:40 | 25.42 | 18.78 |
Annual Sum or Average | 0.140057E+11 | 0.115910E+10 | ||||||||
Minimum of Months | 0.684293E+09 | 1349.36 | 23.83 | 13.09 | 88075248.93 | 56.69 | 20.25 | 13.09 | ||
Maximum of Months | 0.163341E+10 | 1425.34 | 41.83 | 25.12 | 99134569.87 | 56.70 | 40.85 | 27.35 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.113561E+10 | 3383.02 | 16-JAN-16:01 | 23.83 | 13.09 | 98312341.64 | 56.69 | 05-JAN-22:10 | 23.83 | 13.09 |
February | 0.127902E+10 | 3295.24 | 23-FEB-19:01 | 24.50 | 16.52 | 88960493.27 | 56.69 | 17-FEB-22:49 | 24.50 | 16.52 |
March | 0.181871E+10 | 3342.04 | 23-MAR-08:62 | 25.83 | 13.67 | 98816611.74 | 56.70 | 01-MAR-23:10 | 25.83 | 13.67 |
April | 0.239582E+10 | 3406.52 | 01-APR-15:02 | 32.78 | 16.66 | 95830688.02 | 56.70 | 29-APR-01:19 | 27.20 | 17.83 |
May | 0.343731E+10 | 3355.93 | 31-MAY-18:02 | 40.35 | 22.36 | 99204420.66 | 56.70 | 09-MAY-21:10 | 40.35 | 22.36 |
June | 0.359182E+10 | 3360.02 | 20-JUN-15:02 | 38.92 | 25.13 | 96035716.93 | 56.70 | 20-JUN-21:10 | 31.87 | 26.17 |
July | 0.407921E+10 | 3352.16 | 23-JUL-15:02 | 38.10 | 26.62 | 99141061.54 | 56.70 | 21-JUL-23:00 | 38.10 | 26.62 |
August | 0.420941E+10 | 3383.15 | 05-AUG-18:02 | 39.92 | 26.01 | 99248642.12 | 56.70 | 06-AUG-00:40 | 36.07 | 25.34 |
September | 0.359275E+10 | 3373.03 | 02-SEP-15:02 | 37.02 | 26.50 | 95959337.86 | 56.70 | 12-SEP-21:00 | 34.10 | 24.53 |
October | 0.317799E+10 | 3350.28 | 03-OCT-15:02 | 34.97 | 24.83 | 99147501.62 | 56.70 | 05-OCT-21:10 | 31.97 | 24.90 |
November | 0.226088E+10 | 3432.37 | 18-NOV-16:01 | 30.67 | 15.42 | 95894680.61 | 56.70 | 10-NOV-22:40 | 30.67 | 15.42 |
December | 0.141281E+10 | 3255.00 | 27-DEC-16:01 | 21.83 | 15.42 | 98507460.96 | 56.69 | 20-DEC-22:30 | 21.83 | 15.42 |
Annual Sum or Average | 0.323913E+11 | 0.116506E+10 | ||||||||
Minimum of Months | 0.113561E+10 | 3255.00 | 21.83 | 13.09 | 88960493.27 | 56.69 | 21.83 | 13.09 | ||
Maximum of Months | 0.420941E+10 | 3432.37 | 40.35 | 26.62 | 99248642.12 | 56.70 | 40.35 | 26.62 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.864883E+09 | 3258.82 | 16-JAN-16:01 | 23.83 | 13.09 | 97606520.60 | 56.69 | 24-JAN-22:10 | 20.25 | 16.41 |
February | 0.104598E+10 | 3166.07 | 04-FEB-19:01 | 24.25 | 17.14 | 88643005.01 | 56.69 | 27-FEB-22:49 | 20.08 | 16.15 |
March | 0.162761E+10 | 3281.70 | 23-MAR-08:62 | 25.83 | 13.67 | 98709908.08 | 56.70 | 01-MAR-22:30 | 25.83 | 13.67 |
April | 0.230027E+10 | 3338.44 | 01-APR-15:02 | 32.78 | 16.66 | 95820724.82 | 56.70 | 13-APR-21:10 | 24.73 | 20.11 |
May | 0.343379E+10 | 3300.94 | 08-MAY-15:02 | 35.02 | 24.00 | 99205181.75 | 56.70 | 11-MAY-21:30 | 33.00 | 19.84 |
June | 0.363604E+10 | 3300.72 | 20-JUN-15:02 | 38.92 | 25.13 | 96036169.95 | 56.70 | 08-JUN-21:40 | 38.92 | 25.13 |
July | 0.409479E+10 | 3325.11 | 15-JUL-18:02 | 40.03 | 26.09 | 99141260.91 | 56.70 | 22-JUL-00:20 | 35.03 | 26.13 |
August | 0.414822E+10 | 3332.12 | 04-AUG-15:02 | 38.00 | 28.10 | 99248743.55 | 56.70 | 02-AUG-00:20 | 38.00 | 28.10 |
September | 0.340984E+10 | 3302.03 | 20-SEP-15:02 | 35.85 | 25.27 | 95956695.13 | 56.70 | 12-SEP-21:40 | 35.85 | 25.27 |
October | 0.285966E+10 | 3266.06 | 09-OCT-18:02 | 33.78 | 22.64 | 99134342.80 | 56.70 | 04-OCT-00:49 | 33.78 | 22.64 |
November | 0.190615E+10 | 3355.66 | 18-NOV-16:01 | 30.67 | 15.42 | 95804813.36 | 56.70 | 14-NOV-22:10 | 30.67 | 15.42 |
December | 0.111422E+10 | 3150.42 | 25-DEC-16:01 | 25.33 | 17.33 | 98025004.38 | 56.69 | 07-DEC-22:49 | 25.33 | 17.33 |
Annual Sum or Average | 0.304415E+11 | 0.116333E+10 | ||||||||
Minimum of Months | 0.864883E+09 | 3150.42 | 23.83 | 13.09 | 88643005.01 | 56.69 | 20.08 | 13.67 | ||
Maximum of Months | 0.414822E+10 | 3355.66 | 40.03 | 28.10 | 99248743.55 | 56.70 | 38.92 | 28.10 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.525050E+10 | 2603.96 | 29-JAN-19:40 | 23.87 | 19.32 | 0.120036E+10 | 716.76 | 24-JAN-22:40 | 23.87 | 19.32 |
February | 0.514316E+10 | 3040.22 | 05-FEB-11:35 | 30.33 | 18.87 | 0.108980E+10 | 738.79 | 07-FEB-22:49 | 24.07 | 19.93 |
March | 0.621902E+10 | 3252.45 | 27-MAR-18:10 | 32.92 | 18.22 | 0.122319E+10 | 758.54 | 27-MAR-21:49 | 28.08 | 15.55 |
April | 0.664475E+10 | 3483.58 | 29-APR-10:35 | 35.90 | 19.60 | 0.120330E+10 | 783.40 | 28-APR-21:49 | 35.90 | 19.60 |
May | 0.770598E+10 | 3732.47 | 31-MAY-18:10 | 40.35 | 22.36 | 0.131537E+10 | 810.22 | 31-MAY-21:49 | 34.53 | 22.92 |
June | 0.775311E+10 | 3783.35 | 10-JUN-10:35 | 38.30 | 26.21 | 0.130362E+10 | 817.41 | 09-JUN-21:00 | 38.30 | 26.21 |
July | 0.830885E+10 | 3981.99 | 22-JUL-10:35 | 41.47 | 23.66 | 0.136795E+10 | 842.00 | 21-JUL-22:10 | 41.47 | 23.66 |
August | 0.842844E+10 | 4004.11 | 05-AUG-10:35 | 42.43 | 25.20 | 0.138690E+10 | 841.32 | 17-AUG-22:10 | 35.50 | 28.69 |
September | 0.777206E+10 | 3790.36 | 04-SEP-10:35 | 38.00 | 23.07 | 0.130548E+10 | 825.68 | 05-SEP-21:49 | 33.50 | 27.87 |
October | 0.759407E+10 | 3573.41 | 09-OCT-10:35 | 35.10 | 22.00 | 0.131131E+10 | 804.56 | 05-OCT-22:10 | 35.10 | 22.00 |
November | 0.668187E+10 | 3296.80 | 05-NOV-10:35 | 31.33 | 19.23 | 0.121019E+10 | 776.92 | 01-NOV-22:10 | 31.33 | 19.23 |
December | 0.577343E+10 | 2975.65 | 03-DEC-11:35 | 27.33 | 18.33 | 0.120509E+10 | 730.55 | 05-DEC-22:49 | 23.00 | 20.78 |
Annual Sum or Average | 0.832752E+11 | 0.151225E+11 | ||||||||
Minimum of Months | 0.514316E+10 | 2603.96 | 23.87 | 18.22 | 0.108980E+10 | 716.76 | 23.00 | 15.55 | ||
Maximum of Months | 0.842844E+10 | 4004.11 | 42.43 | 26.21 | 0.138690E+10 | 842.00 | 41.47 | 28.69 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.117811E+10 | 4003.13 | 16-JAN-16:01 | 23.83 | 13.09 | 98148423.12 | 56.69 | 06-JAN-03:00 | 23.83 | 13.09 |
February | 0.140089E+10 | 3904.81 | 03-FEB-16:01 | 25.25 | 17.88 | 88868443.85 | 56.70 | 13-FEB-02:20 | 13.93 | 11.20 |
March | 0.208885E+10 | 3925.58 | 24-MAR-15:02 | 26.83 | 20.18 | 98750575.73 | 56.70 | 01-MAR-22:49 | 26.83 | 20.18 |
April | 0.268964E+10 | 3962.45 | 30-APR-15:02 | 31.08 | 26.25 | 95736715.64 | 56.70 | 17-APR-21:49 | 31.08 | 26.25 |
May | 0.384688E+10 | 3981.53 | 22-MAY-18:02 | 33.95 | 24.59 | 99177177.25 | 56.70 | 31-MAY-21:49 | 34.53 | 22.92 |
June | 0.407425E+10 | 3997.20 | 08-JUN-15:02 | 36.15 | 27.24 | 96031017.33 | 56.70 | 15-JUN-21:10 | 33.18 | 24.64 |
July | 0.461801E+10 | 4046.79 | 18-JUL-15:02 | 40.72 | 26.45 | 99145311.08 | 56.70 | 31-JUL-22:10 | 35.37 | 25.83 |
August | 0.473807E+10 | 4035.58 | 23-AUG-15:02 | 38.77 | 28.42 | 99252029.59 | 56.70 | 15-AUG-21:49 | 38.77 | 28.42 |
September | 0.402690E+10 | 4013.04 | 04-SEP-15:02 | 40.95 | 24.20 | 95948325.02 | 56.70 | 07-SEP-21:10 | 33.92 | 27.71 |
October | 0.351599E+10 | 3942.14 | 07-OCT-15:02 | 34.93 | 27.55 | 99100275.12 | 56.70 | 11-OCT-00:10 | 28.77 | 21.46 |
November | 0.249430E+10 | 4085.53 | 18-NOV-16:01 | 30.67 | 15.42 | 95811910.88 | 56.70 | 13-NOV-22:10 | 30.67 | 15.42 |
December | 0.154364E+10 | 3867.66 | 07-DEC-16:02 | 25.25 | 17.82 | 98401270.45 | 56.69 | 20-DEC-22:10 | 19.25 | 15.31 |
Annual Sum or Average | 0.362155E+11 | 0.116437E+10 | ||||||||
Minimum of Months | 0.117811E+10 | 3867.66 | 23.83 | 13.09 | 88868443.85 | 56.69 | 13.93 | 11.20 | ||
Maximum of Months | 0.473807E+10 | 4085.53 | 40.95 | 28.42 | 99252029.59 | 56.70 | 38.77 | 28.42 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.874356E+09 | 3917.35 | 16-JAN-16:01 | 23.83 | 13.09 | 97624335.94 | 56.70 | 09-JAN-02:30 | 23.83 | 13.09 |
February | 0.114732E+10 | 3801.28 | 23-FEB-19:01 | 24.50 | 16.52 | 88616795.06 | 56.69 | 12-FEB-02:00 | 24.50 | 16.52 |
March | 0.188499E+10 | 3827.88 | 25-MAR-15:02 | 29.62 | 20.48 | 98667642.89 | 56.70 | 23-MAR-21:10 | 29.62 | 20.48 |
April | 0.259053E+10 | 3920.97 | 30-APR-15:02 | 31.08 | 26.25 | 95724508.19 | 56.70 | 17-APR-21:49 | 31.08 | 26.25 |
May | 0.384308E+10 | 3919.04 | 22-MAY-18:02 | 33.95 | 24.59 | 99181493.32 | 56.70 | 31-MAY-22:10 | 34.02 | 23.07 |
June | 0.411972E+10 | 3987.94 | 09-JUN-15:02 | 41.85 | 25.00 | 96035454.29 | 56.70 | 12-JUN-21:10 | 32.88 | 26.86 |
July | 0.463403E+10 | 3969.50 | 04-JUL-15:02 | 39.73 | 27.36 | 99146535.02 | 56.70 | 03-JUL-22:10 | 39.73 | 27.36 |
August | 0.467426E+10 | 3982.65 | 07-AUG-15:02 | 39.15 | 28.53 | 99251918.62 | 56.70 | 15-AUG-21:00 | 35.00 | 21.72 |
September | 0.383725E+10 | 3923.21 | 24-SEP-15:02 | 33.98 | 26.63 | 95942602.41 | 56.70 | 01-SEP-21:10 | 33.98 | 26.63 |
October | 0.318395E+10 | 3887.00 | 24-OCT-15:02 | 31.82 | 23.47 | 99065712.46 | 56.70 | 02-OCT-23:00 | 31.82 | 23.47 |
November | 0.212360E+10 | 3999.53 | 18-NOV-16:01 | 30.67 | 15.42 | 95690539.24 | 56.70 | 08-NOV-22:10 | 30.67 | 15.42 |
December | 0.121328E+10 | 3775.62 | 27-DEC-16:01 | 21.83 | 15.42 | 98047997.21 | 56.69 | 01-DEC-22:00 | 21.83 | 15.42 |
Annual Sum or Average | 0.341264E+11 | 0.116300E+10 | ||||||||
Minimum of Months | 0.874356E+09 | 3775.62 | 21.83 | 13.09 | 88616795.06 | 56.69 | 21.83 | 13.09 | ||
Maximum of Months | 0.467426E+10 | 3999.53 | 41.85 | 28.53 | 99251918.62 | 56.70 | 39.73 | 27.36 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.113526E+10 | 2153.09 | 12-JAN-16:01 | 22.33 | 16.82 | 98576054.02 | 56.69 | 06-JAN-23:00 | 22.33 | 16.82 |
February | 0.114574E+10 | 2143.18 | 15-FEB-16:02 | 23.83 | 17.38 | 89066347.22 | 56.70 | 06-FEB-23:10 | 23.83 | 17.38 |
March | 0.142156E+10 | 2159.53 | 24-MAR-15:02 | 26.83 | 20.18 | 98816786.97 | 56.70 | 31-MAR-21:30 | 23.90 | 20.59 |
April | 0.161745E+10 | 2178.34 | 26-APR-08:61 | 29.33 | 14.54 | 95742420.77 | 56.70 | 27-APR-23:00 | 27.00 | 17.73 |
May | 0.213130E+10 | 2170.15 | 08-MAY-18:02 | 32.73 | 22.26 | 99153403.68 | 56.70 | 04-MAY-21:10 | 32.73 | 22.26 |
June | 0.220819E+10 | 2181.84 | 27-JUN-15:02 | 38.23 | 26.51 | 96011152.61 | 56.70 | 13-JUN-21:10 | 38.23 | 26.51 |
July | 0.254312E+10 | 2183.46 | 15-JUL-18:02 | 40.03 | 26.09 | 99136585.37 | 56.70 | 21-JUL-23:40 | 36.00 | 26.04 |
August | 0.265556E+10 | 2184.64 | 17-AUG-18:02 | 38.95 | 25.80 | 99246167.67 | 56.70 | 05-AUG-23:49 | 38.95 | 25.80 |
September | 0.240682E+10 | 2213.27 | 26-SEP-15:02 | 38.67 | 25.17 | 95942257.35 | 56.70 | 01-SEP-22:10 | 38.67 | 25.17 |
October | 0.231219E+10 | 2172.13 | 04-OCT-18:02 | 33.77 | 23.33 | 99127266.44 | 56.70 | 18-OCT-21:10 | 29.82 | 21.19 |
November | 0.184082E+10 | 2168.97 | 01-NOV-15:02 | 32.00 | 26.07 | 95905899.99 | 56.70 | 30-NOV-22:40 | 21.90 | 16.98 |
December | 0.134475E+10 | 2157.92 | 04-DEC-16:02 | 26.17 | 20.65 | 98699775.33 | 56.70 | 05-DEC-23:10 | 23.00 | 20.89 |
Annual Sum or Average | 0.227627E+11 | 0.116542E+10 | ||||||||
Minimum of Months | 0.113526E+10 | 2143.18 | 22.33 | 14.54 | 89066347.22 | 56.69 | 21.90 | 16.82 | ||
Maximum of Months | 0.265556E+10 | 2213.27 | 40.03 | 26.51 | 99246167.67 | 56.70 | 38.95 | 26.51 |
Report: ZoneCoolingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.449234E+11 | 20884.93 | 23-JAN-23:00 | 21.00 | 16.55 | 0.153082E+11 | 10008.21 | 23-JAN-23:10 | 20.83 | 16.49 |
February | 0.417545E+11 | 21474.88 | 07-FEB-23:00 | 24.00 | 19.92 | 0.139505E+11 | 10207.15 | 07-FEB-23:10 | 23.83 | 19.77 |
March | 0.478997E+11 | 22939.00 | 27-MAR-18:10 | 32.92 | 18.22 | 0.156963E+11 | 10377.81 | 27-MAR-22:10 | 27.92 | 15.44 |
April | 0.485037E+11 | 23469.07 | 27-APR-18:10 | 32.83 | 21.90 | 0.153296E+11 | 10574.61 | 28-APR-22:10 | 29.75 | 17.96 |
May | 0.534577E+11 | 25225.09 | 31-MAY-18:10 | 40.35 | 22.36 | 0.162500E+11 | 10805.31 | 31-MAY-22:10 | 34.02 | 23.07 |
June | 0.529943E+11 | 24992.81 | 01-JUN-18:10 | 36.65 | 23.81 | 0.159433E+11 | 10867.90 | 09-JUN-22:10 | 34.25 | 25.66 |
July | 0.559664E+11 | 25368.03 | 31-JUL-18:10 | 39.88 | 25.61 | 0.165424E+11 | 10978.83 | 21-JUL-22:10 | 39.88 | 25.61 |
August | 0.560375E+11 | 25715.90 | 16-AUG-18:10 | 40.97 | 26.89 | 0.166454E+11 | 10929.58 | 16-AUG-22:10 | 34.08 | 27.89 |
September | 0.521284E+11 | 24419.04 | 06-SEP-18:10 | 35.97 | 26.92 | 0.157707E+11 | 10773.07 | 06-SEP-22:10 | 33.67 | 27.24 |
October | 0.515797E+11 | 23562.05 | 05-OCT-18:10 | 34.72 | 22.85 | 0.160071E+11 | 10592.91 | 05-OCT-22:10 | 31.67 | 25.32 |
November | 0.471848E+11 | 22438.18 | 01-NOV-18:10 | 30.93 | 24.44 | 0.151721E+11 | 10420.40 | 01-NOV-22:10 | 30.00 | 24.30 |
December | 0.460319E+11 | 21323.83 | 11-DEC-23:00 | 24.00 | 21.17 | 0.154088E+11 | 10155.28 | 11-DEC-23:10 | 24.00 | 21.17 |
Annual Sum or Average | 0.598462E+12 | 0.188025E+12 | ||||||||
Minimum of Months | 0.417545E+11 | 20884.93 | 21.00 | 16.55 | 0.139505E+11 | 10008.21 | 20.83 | 15.44 | ||
Maximum of Months | 0.560375E+11 | 25715.90 | 40.97 | 26.92 | 0.166454E+11 | 10978.83 | 39.88 | 27.89 |
Report: ZoneCoolingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.480161E+11 | 22138.24 | 23-JAN-23:00 | 21.00 | 16.55 | 0.154066E+11 | 10101.54 | 23-JAN-23:10 | 20.83 | 16.49 |
February | 0.445793E+11 | 22764.49 | 07-FEB-23:00 | 24.00 | 19.92 | 0.140462E+11 | 10304.37 | 07-FEB-23:10 | 23.83 | 19.77 |
March | 0.510818E+11 | 24300.54 | 27-MAR-18:10 | 32.92 | 18.22 | 0.158170E+11 | 10475.26 | 27-MAR-22:10 | 27.92 | 15.44 |
April | 0.516342E+11 | 24862.24 | 27-APR-18:10 | 32.83 | 21.90 | 0.154576E+11 | 10670.60 | 28-APR-22:10 | 29.75 | 17.96 |
May | 0.566921E+11 | 26632.08 | 31-MAY-18:10 | 40.35 | 22.36 | 0.163754E+11 | 10883.43 | 31-MAY-22:10 | 34.02 | 23.07 |
June | 0.560805E+11 | 26369.36 | 01-JUN-18:10 | 36.65 | 23.81 | 0.160490E+11 | 10944.48 | 09-JUN-22:10 | 34.25 | 25.66 |
July | 0.590663E+11 | 26721.32 | 31-JUL-18:10 | 39.88 | 25.61 | 0.166254E+11 | 11030.21 | 21-JUL-22:19 | 39.88 | 25.61 |
August | 0.591042E+11 | 27058.42 | 16-AUG-18:10 | 40.97 | 26.89 | 0.167211E+11 | 10983.77 | 16-AUG-22:10 | 34.08 | 27.89 |
September | 0.551520E+11 | 25749.33 | 06-SEP-18:10 | 35.97 | 26.92 | 0.158684E+11 | 10839.34 | 06-SEP-22:10 | 33.67 | 27.24 |
October | 0.547486E+11 | 24906.51 | 05-OCT-18:10 | 34.72 | 22.85 | 0.161249E+11 | 10674.54 | 05-OCT-22:10 | 31.67 | 25.32 |
November | 0.502480E+11 | 23778.05 | 01-NOV-18:10 | 30.93 | 24.44 | 0.152858E+11 | 10513.81 | 01-NOV-22:10 | 30.00 | 24.30 |
December | 0.491490E+11 | 22605.02 | 11-DEC-23:00 | 24.00 | 21.17 | 0.155141E+11 | 10251.79 | 11-DEC-23:10 | 24.00 | 21.17 |
Annual Sum or Average | 0.635552E+12 | 0.189291E+12 | ||||||||
Minimum of Months | 0.445793E+11 | 22138.24 | 21.00 | 16.55 | 0.140462E+11 | 10101.54 | 20.83 | 15.44 | ||
Maximum of Months | 0.591042E+11 | 27058.42 | 40.97 | 26.92 | 0.167211E+11 | 11030.21 | 39.88 | 27.89 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.556305E+11 | 28303.35 | 29-JAN-11:45 | 26.83 | 18.70 | 0.186435E+11 | 11319.66 | 28-JAN-18:19 | 26.83 | 18.70 |
February | 0.510621E+11 | 29022.93 | 05-FEB-11:50 | 30.67 | 18.90 | 0.168461E+11 | 11319.67 | 04-FEB-18:19 | 30.67 | 18.90 |
March | 0.577687E+11 | 29807.63 | 27-MAR-10:50 | 37.50 | 18.71 | 0.186640E+11 | 11319.71 | 18-MAR-17:19 | 37.50 | 18.71 |
April | 0.576883E+11 | 30839.83 | 28-APR-10:50 | 39.78 | 18.42 | 0.180693E+11 | 11319.74 | 22-APR-17:19 | 39.78 | 18.42 |
May | 0.622300E+11 | 31106.05 | 29-MAY-10:40 | 37.30 | 22.20 | 0.186896E+11 | 11319.73 | 27-MAY-17:19 | 37.30 | 22.20 |
June | 0.609925E+11 | 31417.51 | 10-JUN-10:40 | 38.30 | 26.21 | 0.180950E+11 | 11319.72 | 17-JUN-17:19 | 36.67 | 22.74 |
July | 0.638776E+11 | 32127.44 | 30-JUL-10:40 | 44.13 | 22.13 | 0.186997E+11 | 11319.71 | 29-JUL-17:19 | 44.13 | 22.13 |
August | 0.641000E+11 | 32042.32 | 05-AUG-10:40 | 42.43 | 25.20 | 0.187079E+11 | 11319.71 | 12-AUG-17:19 | 38.00 | 27.29 |
September | 0.606048E+11 | 31313.95 | 04-SEP-10:50 | 38.00 | 23.07 | 0.180891E+11 | 11319.72 | 23-SEP-17:19 | 33.00 | 25.65 |
October | 0.610196E+11 | 30675.77 | 09-OCT-10:50 | 35.55 | 20.67 | 0.186803E+11 | 11319.73 | 14-OCT-17:19 | 32.67 | 23.11 |
November | 0.568739E+11 | 29596.13 | 05-NOV-10:50 | 31.82 | 18.97 | 0.180632E+11 | 11319.72 | 04-NOV-17:19 | 31.82 | 18.97 |
December | 0.564851E+11 | 28630.33 | 03-DEC-11:50 | 27.67 | 18.43 | 0.186497E+11 | 11319.65 | 23-DEC-18:19 | 23.63 | 20.42 |
Annual Sum or Average | 0.708333E+12 | 0.219898E+12 | ||||||||
Minimum of Months | 0.510621E+11 | 28303.35 | 26.83 | 18.42 | 0.168461E+11 | 11319.65 | 23.63 | 18.42 | ||
Maximum of Months | 0.641000E+11 | 32127.44 | 44.13 | 26.21 | 0.187079E+11 | 11319.74 | 44.13 | 27.29 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.880942E+10 | 5752.72 | 28-JAN-13:00 | 27.30 | 12.89 | 0.126878E+10 | 745.70 | 09-JAN-03:00 | 27.30 | 12.89 |
February | 0.917117E+10 | 6959.04 | 05-FEB-11:35 | 30.33 | 18.87 | 0.114749E+10 | 747.44 | 07-FEB-22:30 | 24.20 | 19.96 |
March | 0.117094E+11 | 7452.53 | 27-MAR-18:03 | 32.92 | 18.22 | 0.127657E+10 | 769.82 | 27-MAR-21:40 | 28.27 | 15.67 |
April | 0.134638E+11 | 8141.32 | 28-APR-10:35 | 39.57 | 18.31 | 0.123700E+10 | 795.70 | 28-APR-21:40 | 30.27 | 17.92 |
May | 0.170152E+11 | 8596.32 | 31-MAY-18:10 | 40.35 | 22.36 | 0.131849E+10 | 832.66 | 31-MAY-21:49 | 34.53 | 22.92 |
June | 0.174003E+11 | 8953.82 | 10-JUN-10:35 | 38.30 | 26.21 | 0.130851E+10 | 841.30 | 09-JUN-21:00 | 38.30 | 26.21 |
July | 0.189472E+11 | 9393.06 | 16-JUL-10:35 | 39.60 | 27.30 | 0.138716E+10 | 874.99 | 21-JUL-22:10 | 37.83 | 19.83 |
August | 0.191225E+11 | 9335.21 | 05-AUG-10:35 | 42.43 | 25.20 | 0.140127E+10 | 864.62 | 16-AUG-22:10 | 34.08 | 27.89 |
September | 0.172309E+11 | 8730.86 | 04-SEP-10:35 | 38.00 | 23.07 | 0.130151E+10 | 837.69 | 06-SEP-22:10 | 33.67 | 27.24 |
October | 0.162173E+11 | 8174.19 | 09-OCT-10:35 | 35.10 | 22.00 | 0.129965E+10 | 806.83 | 05-OCT-22:10 | 35.10 | 22.00 |
November | 0.129787E+11 | 7488.15 | 05-NOV-10:35 | 31.33 | 19.23 | 0.123165E+10 | 776.25 | 01-NOV-22:10 | 31.33 | 19.23 |
December | 0.101037E+11 | 6241.09 | 03-DEC-11:35 | 27.33 | 18.33 | 0.126891E+10 | 745.70 | 18-DEC-05:19 | 13.00 | 10.66 |
Annual Sum or Average | 0.172170E+12 | 0.154470E+11 | ||||||||
Minimum of Months | 0.880942E+10 | 5752.72 | 27.30 | 12.89 | 0.114749E+10 | 745.70 | 13.00 | 10.66 | ||
Maximum of Months | 0.191225E+11 | 9393.06 | 42.43 | 27.30 | 0.140127E+10 | 874.99 | 38.30 | 27.89 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 2416282.48 | 922.25 | 15-JAN-09:03 | 15.52 |
February | 1456281.82 | 727.42 | 26-FEB-09:03 | 18.38 |
March | 1449227.18 | 729.24 | 01-MAR-09:04 | 27.58 |
April | 980698.26 | 818.94 | 08-APR-08:04 | 23.55 |
May | 170282.66 | 650.34 | 03-MAY-08:04 | 25.50 |
June | 11632.89 | 103.24 | 08-JUN-08:05 | 25.67 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 33.23 |
September | 20207.98 | 219.41 | 25-SEP-08:04 | 25.67 |
October | 663674.91 | 602.93 | 20-OCT-08:04 | 25.67 |
November | 1179643.45 | 604.70 | 17-NOV-09:04 | 24.43 |
December | 2232803.33 | 988.61 | 16-DEC-09:03 | 21.08 |
Annual Sum or Average | 10580734.96 | |||
Minimum of Months | 0.00 | 0.00 | 15.52 | |
Maximum of Months | 2416282.48 | 988.61 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 4377840.80 | 818.67 | 03-JAN-19:03 | 20.33 |
February | 1948625.58 | 949.94 | 11-FEB-09:03 | 20.23 |
March | 1660186.80 | 930.57 | 09-MAR-09:03 | 22.22 |
April | 1015040.43 | 813.38 | 08-APR-08:04 | 23.55 |
May | 162136.60 | 642.63 | 02-MAY-08:04 | 26.50 |
June | 8545.85 | 85.46 | 08-JUN-08:05 | 25.67 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 33.23 |
September | 81317.26 | 338.36 | 25-SEP-08:04 | 25.67 |
October | 1065282.86 | 769.52 | 29-OCT-08:04 | 24.50 |
November | 1806068.94 | 874.58 | 19-NOV-09:04 | 25.40 |
December | 2882505.34 | 790.13 | 23-DEC-09:03 | 20.35 |
Annual Sum or Average | 15007550.47 | |||
Minimum of Months | 0.00 | 0.00 | 20.23 | |
Maximum of Months | 4377840.80 | 949.94 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 1002901.90 | 314.40 | 15-JAN-09:05 | 15.52 |
February | 746165.71 | 350.09 | 07-FEB-09:05 | 24.33 |
March | 468527.15 | 342.05 | 01-MAR-09:04 | 27.58 |
April | 332310.53 | 334.45 | 10-APR-08:05 | 25.25 |
May | 11998.64 | 68.59 | 11-MAY-08:07 | 33.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 31.93 |
October | 72261.18 | 313.96 | 30-OCT-08:05 | 25.50 |
November | 456545.82 | 326.37 | 10-NOV-09:05 | 26.38 |
December | 806876.38 | 339.44 | 11-DEC-09:05 | 23.18 |
Annual Sum or Average | 3897587.32 | |||
Minimum of Months | 0.00 | 0.00 | 15.52 | |
Maximum of Months | 1002901.90 | 350.09 | 33.67 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 2513332.52 | 744.47 | 09-JAN-16:04 | 22.00 |
February | 1623746.98 | 700.41 | 21-FEB-16:04 | 22.33 |
March | 1520906.26 | 852.19 | 01-MAR-09:04 | 27.58 |
April | 356142.96 | 475.22 | 17-APR-08:04 | 26.50 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 31.93 |
October | 4684.28 | 46.84 | 30-OCT-08:05 | 25.50 |
November | 403548.49 | 595.75 | 22-NOV-19:04 | 24.50 |
December | 2054305.53 | 755.34 | 17-DEC-16:04 | 22.17 |
Annual Sum or Average | 8476667.03 | |||
Minimum of Months | 0.00 | 0.00 | 22.00 | |
Maximum of Months | 2513332.52 | 852.19 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 5177355.71 | 844.71 | 28-JAN-16:04 | 24.42 |
February | 2084929.91 | 878.84 | 23-FEB-19:04 | 24.50 |
March | 2038163.17 | 848.93 | 01-MAR-09:04 | 27.58 |
April | 407657.68 | 412.74 | 17-APR-08:04 | 26.50 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 31.93 |
October | 21679.29 | 216.79 | 30-OCT-08:05 | 25.50 |
November | 1215498.08 | 802.78 | 21-NOV-19:04 | 24.27 |
December | 3090747.24 | 862.12 | 12-DEC-09:04 | 24.07 |
Annual Sum or Average | 14036031.08 | |||
Minimum of Months | 0.00 | 0.00 | 24.07 | |
Maximum of Months | 5177355.71 | 878.84 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 6315080.52 | 842.13 | 22-JAN-09:03 | 20.15 |
February | 1733556.86 | 1004.22 | 04-FEB-09:03 | 21.67 |
March | 1484802.73 | 1010.02 | 22-MAR-08:03 | 23.67 |
April | 876267.48 | 756.66 | 13-APR-08:03 | 21.50 |
May | 110185.85 | 492.30 | 03-MAY-08:04 | 25.50 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 33.23 |
September | 34213.73 | 399.16 | 25-SEP-08:04 | 25.67 |
October | 636730.39 | 591.34 | 29-OCT-08:04 | 24.50 |
November | 940322.34 | 665.95 | 04-NOV-08:04 | 25.33 |
December | 1857709.19 | 849.80 | 16-DEC-09:03 | 21.08 |
Annual Sum or Average | 13988869.08 | |||
Minimum of Months | 0.00 | 0.00 | 20.15 | |
Maximum of Months | 6315080.52 | 1010.02 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 15793405.19 | 831.54 | 03-JAN-19:03 | 20.33 |
February | 2951994.90 | 884.57 | 25-FEB-09:03 | 21.00 |
March | 1561240.08 | 898.31 | 09-MAR-09:03 | 22.22 |
April | 905667.38 | 770.74 | 13-APR-08:03 | 21.50 |
May | 115648.06 | 508.66 | 03-MAY-08:04 | 25.50 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 33.23 |
September | 48689.29 | 504.64 | 25-SEP-08:04 | 25.67 |
October | 867615.62 | 706.16 | 31-OCT-08:04 | 25.67 |
November | 1553460.07 | 810.91 | 28-NOV-09:03 | 22.93 |
December | 3895617.45 | 736.06 | 08-DEC-19:04 | 23.33 |
Annual Sum or Average | 27693338.04 | |||
Minimum of Months | 0.00 | 0.00 | 20.33 | |
Maximum of Months | 15793405.19 | 898.31 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 538764.44 | 341.10 | 04-JAN-09:05 | 15.35 |
February | 430261.28 | 326.92 | 07-FEB-09:05 | 24.33 |
March | 542747.30 | 490.69 | 01-MAR-09:04 | 27.58 |
April | 667406.24 | 498.59 | 17-APR-08:04 | 26.50 |
May | 148049.34 | 516.98 | 02-MAY-08:04 | 26.50 |
June | 28991.97 | 131.22 | 08-JUN-08:05 | 25.67 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 33.23 |
September | 2489.74 | 18.56 | 22-SEP-08:05 | 28.10 |
October | 60668.76 | 335.59 | 20-OCT-08:04 | 25.67 |
November | 168942.70 | 329.40 | 05-NOV-08:04 | 24.50 |
December | 464917.48 | 402.07 | 12-DEC-09:04 | 24.07 |
Annual Sum or Average | 3053239.27 | |||
Minimum of Months | 0.00 | 0.00 | 15.35 | |
Maximum of Months | 667406.24 | 516.98 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.140333E+11 | 13517.00 | 02-JAN-20:10 | 0.127587E+11 | 10113.80 | 02-JAN-20:10 |
February | 0.126708E+11 | 13517.00 | 01-FEB-20:10 | 0.115208E+11 | 10113.80 | 01-FEB-20:10 |
March | 0.140766E+11 | 13517.00 | 01-MAR-20:10 | 0.127855E+11 | 10113.80 | 01-MAR-20:10 |
April | 0.135575E+11 | 13517.00 | 03-APR-19:10 | 0.123314E+11 | 10113.80 | 03-APR-19:10 |
May | 0.140576E+11 | 13517.00 | 01-MAY-19:10 | 0.127741E+11 | 10113.80 | 01-MAY-19:10 |
June | 0.136197E+11 | 13517.00 | 01-JUN-19:10 | 0.123716E+11 | 10113.80 | 01-JUN-19:10 |
July | 0.139955E+11 | 13517.00 | 03-JUL-19:10 | 0.127338E+11 | 10113.80 | 03-JUL-19:10 |
August | 0.140820E+11 | 13517.00 | 01-AUG-19:10 | 0.127894E+11 | 10113.80 | 01-AUG-19:10 |
September | 0.135629E+11 | 13517.00 | 01-SEP-19:10 | 0.123352E+11 | 10113.80 | 01-SEP-19:10 |
October | 0.140279E+11 | 13517.00 | 02-OCT-19:10 | 0.127549E+11 | 10113.80 | 02-OCT-19:10 |
November | 0.136089E+11 | 13517.00 | 01-NOV-19:10 | 0.123659E+11 | 10113.80 | 01-NOV-19:10 |
December | 0.139955E+11 | 13517.00 | 01-DEC-20:10 | 0.127338E+11 | 10113.80 | 01-DEC-20:10 |
Annual Sum or Average | 0.165288E+12 | 0.150255E+12 | ||||
Minimum of Months | 0.126708E+11 | 13517.00 | 0.115208E+11 | 10113.80 | ||
Maximum of Months | 0.140820E+11 | 13517.00 | 0.127894E+11 | 10113.80 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.713551E+09 | 687.30 | 02-JAN-20:10 | 0.864900E+09 | 685.60 | 02-JAN-20:10 |
February | 0.644271E+09 | 687.30 | 01-FEB-20:10 | 0.780982E+09 | 685.60 | 01-FEB-20:10 |
March | 0.715750E+09 | 687.30 | 01-MAR-20:10 | 0.866718E+09 | 685.60 | 01-MAR-20:10 |
April | 0.689358E+09 | 687.30 | 03-APR-19:10 | 0.835931E+09 | 685.60 | 03-APR-19:10 |
May | 0.714788E+09 | 687.30 | 01-MAY-19:10 | 0.865939E+09 | 685.60 | 01-MAY-19:10 |
June | 0.692519E+09 | 687.30 | 01-JUN-19:10 | 0.838659E+09 | 685.60 | 01-JUN-19:10 |
July | 0.711626E+09 | 687.30 | 03-JUL-19:10 | 0.863211E+09 | 685.60 | 03-JUL-19:10 |
August | 0.716025E+09 | 687.30 | 01-AUG-19:10 | 0.866978E+09 | 685.60 | 01-AUG-19:10 |
September | 0.689633E+09 | 687.30 | 01-SEP-19:10 | 0.836191E+09 | 685.60 | 01-SEP-19:10 |
October | 0.713276E+09 | 687.30 | 02-OCT-19:10 | 0.864640E+09 | 685.60 | 02-OCT-19:10 |
November | 0.691970E+09 | 687.30 | 01-NOV-19:10 | 0.838269E+09 | 685.60 | 01-NOV-19:10 |
December | 0.711626E+09 | 687.30 | 01-DEC-20:10 | 0.863211E+09 | 685.60 | 01-DEC-20:10 |
Annual Sum or Average | 0.840439E+10 | 0.101856E+11 | ||||
Minimum of Months | 0.644271E+09 | 687.30 | 0.780982E+09 | 685.60 | ||
Maximum of Months | 0.716025E+09 | 687.30 | 0.866978E+09 | 685.60 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.826294E+09 | 795.89 | 02-JAN-20:10 | 0.100156E+10 | 793.93 | 02-JAN-20:10 |
February | 0.746069E+09 | 795.89 | 01-FEB-20:10 | 0.904380E+09 | 793.93 | 01-FEB-20:10 |
March | 0.828841E+09 | 795.89 | 01-MAR-20:10 | 0.100366E+10 | 793.93 | 01-MAR-20:10 |
April | 0.798279E+09 | 795.89 | 03-APR-19:10 | 0.968011E+09 | 793.93 | 03-APR-19:10 |
May | 0.827727E+09 | 795.89 | 01-MAY-19:10 | 0.100276E+10 | 793.93 | 01-MAY-19:10 |
June | 0.801940E+09 | 795.89 | 01-JUN-19:10 | 0.971170E+09 | 793.93 | 01-JUN-19:10 |
July | 0.824066E+09 | 795.89 | 03-JUL-19:10 | 0.999601E+09 | 793.93 | 03-JUL-19:10 |
August | 0.829160E+09 | 795.89 | 01-AUG-19:10 | 0.100396E+10 | 793.93 | 01-AUG-19:10 |
September | 0.798597E+09 | 795.89 | 01-SEP-19:10 | 0.968312E+09 | 793.93 | 01-SEP-19:10 |
October | 0.825976E+09 | 795.89 | 02-OCT-19:10 | 0.100126E+10 | 793.93 | 02-OCT-19:10 |
November | 0.801303E+09 | 795.89 | 01-NOV-19:10 | 0.970719E+09 | 793.93 | 01-NOV-19:10 |
December | 0.824066E+09 | 795.89 | 01-DEC-20:10 | 0.999601E+09 | 793.93 | 01-DEC-20:10 |
Annual Sum or Average | 0.973232E+10 | 0.117950E+11 | ||||
Minimum of Months | 0.746069E+09 | 795.89 | 0.904380E+09 | 793.93 | ||
Maximum of Months | 0.829160E+09 | 795.89 | 0.100396E+10 | 793.93 |
Report: ZoneElectricSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.154452E+10 | 1487.69 | 02-JAN-20:10 | 0.105898E+10 | 839.45 | 02-JAN-20:10 |
February | 0.139456E+10 | 1487.69 | 01-FEB-20:10 | 0.956227E+09 | 839.45 | 01-FEB-20:10 |
March | 0.154928E+10 | 1487.69 | 01-MAR-20:10 | 0.106120E+10 | 839.45 | 01-MAR-20:10 |
April | 0.149215E+10 | 1487.69 | 03-APR-19:10 | 0.102351E+10 | 839.45 | 03-APR-19:10 |
May | 0.154719E+10 | 1487.69 | 01-MAY-19:10 | 0.106025E+10 | 839.45 | 01-MAY-19:10 |
June | 0.149899E+10 | 1487.69 | 01-JUN-19:10 | 0.102685E+10 | 839.45 | 01-JUN-19:10 |
July | 0.154035E+10 | 1487.69 | 03-JUL-19:10 | 0.105691E+10 | 839.45 | 03-JUL-19:10 |
August | 0.154987E+10 | 1487.69 | 01-AUG-19:10 | 0.106152E+10 | 839.45 | 01-AUG-19:10 |
September | 0.149274E+10 | 1487.69 | 01-SEP-19:10 | 0.102382E+10 | 839.45 | 01-SEP-19:10 |
October | 0.154392E+10 | 1487.69 | 02-OCT-19:10 | 0.105866E+10 | 839.45 | 02-OCT-19:10 |
November | 0.149780E+10 | 1487.69 | 01-NOV-19:10 | 0.102637E+10 | 839.45 | 01-NOV-19:10 |
December | 0.154035E+10 | 1487.69 | 01-DEC-20:10 | 0.105691E+10 | 839.45 | 01-DEC-20:10 |
Annual Sum or Average | 0.181917E+11 | 0.124712E+11 | ||||
Minimum of Months | 0.139456E+10 | 1487.69 | 0.956227E+09 | 839.45 | ||
Maximum of Months | 0.154987E+10 | 1487.69 | 0.106152E+10 | 839.45 |
Report: ZoneElectricSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.283535E+09 | 273.10 | 02-JAN-20:10 | 0.305485E+09 | 242.16 | 02-JAN-20:10 |
February | 0.256006E+09 | 273.10 | 01-FEB-20:10 | 0.275845E+09 | 242.16 | 01-FEB-20:10 |
March | 0.284409E+09 | 273.10 | 01-MAR-20:10 | 0.306128E+09 | 242.16 | 01-MAR-20:10 |
April | 0.273921E+09 | 273.10 | 03-APR-19:10 | 0.295253E+09 | 242.16 | 03-APR-19:10 |
May | 0.284026E+09 | 273.10 | 01-MAY-19:10 | 0.305852E+09 | 242.16 | 01-MAY-19:10 |
June | 0.275178E+09 | 273.10 | 01-JUN-19:10 | 0.296217E+09 | 242.16 | 01-JUN-19:10 |
July | 0.282770E+09 | 273.10 | 03-JUL-19:10 | 0.304889E+09 | 242.16 | 03-JUL-19:10 |
August | 0.284518E+09 | 273.10 | 01-AUG-19:10 | 0.306219E+09 | 242.16 | 01-AUG-19:10 |
September | 0.274031E+09 | 273.10 | 01-SEP-19:10 | 0.295345E+09 | 242.16 | 01-SEP-19:10 |
October | 0.283425E+09 | 273.10 | 02-OCT-19:10 | 0.305393E+09 | 242.16 | 02-OCT-19:10 |
November | 0.274959E+09 | 273.10 | 01-NOV-19:10 | 0.296079E+09 | 242.16 | 01-NOV-19:10 |
December | 0.282770E+09 | 273.10 | 01-DEC-20:10 | 0.304889E+09 | 242.16 | 01-DEC-20:10 |
Annual Sum or Average | 0.333955E+10 | 0.359760E+10 | ||||
Minimum of Months | 0.256006E+09 | 273.10 | 0.275845E+09 | 242.16 | ||
Maximum of Months | 0.284518E+09 | 273.10 | 0.306219E+09 | 242.16 |
Report: ZoneElectricSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.350256E+09 | 337.37 | 02-JAN-20:10 | 0.576866E+10 | 4572.80 | 02-JAN-20:10 |
February | 0.316249E+09 | 337.37 | 01-FEB-20:10 | 0.520895E+10 | 4572.80 | 01-FEB-20:10 |
March | 0.351336E+09 | 337.37 | 01-MAR-20:10 | 0.578079E+10 | 4572.80 | 01-MAR-20:10 |
April | 0.338381E+09 | 337.37 | 03-APR-19:10 | 0.557545E+10 | 4572.80 | 03-APR-19:10 |
May | 0.350863E+09 | 337.37 | 01-MAY-19:10 | 0.577559E+10 | 4572.80 | 01-MAY-19:10 |
June | 0.339933E+09 | 337.37 | 01-JUN-19:10 | 0.559364E+10 | 4572.80 | 01-JUN-19:10 |
July | 0.349311E+09 | 337.37 | 03-JUL-19:10 | 0.575740E+10 | 4572.80 | 03-JUL-19:10 |
August | 0.351471E+09 | 337.37 | 01-AUG-19:10 | 0.578252E+10 | 4572.80 | 01-AUG-19:10 |
September | 0.338516E+09 | 337.37 | 01-SEP-19:10 | 0.557718E+10 | 4572.80 | 01-SEP-19:10 |
October | 0.350121E+09 | 337.37 | 02-OCT-19:10 | 0.576693E+10 | 4572.80 | 02-OCT-19:10 |
November | 0.339663E+09 | 337.37 | 01-NOV-19:10 | 0.559104E+10 | 4572.80 | 01-NOV-19:10 |
December | 0.349311E+09 | 337.37 | 01-DEC-20:10 | 0.575740E+10 | 4572.80 | 01-DEC-20:10 |
Annual Sum or Average | 0.412541E+10 | 0.679355E+11 | ||||
Minimum of Months | 0.316249E+09 | 337.37 | 0.520895E+10 | 4572.80 | ||
Maximum of Months | 0.351471E+09 | 337.37 | 0.578252E+10 | 4572.80 |
Report: ZoneElectricSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.226040E+10 | 2177.23 | 02-JAN-20:10 | 0.121771E+10 | 965.27 | 02-JAN-20:10 |
February | 0.204093E+10 | 2177.23 | 01-FEB-20:10 | 0.109956E+10 | 965.27 | 01-FEB-20:10 |
March | 0.226736E+10 | 2177.23 | 01-MAR-20:10 | 0.122027E+10 | 965.27 | 01-MAR-20:10 |
April | 0.218376E+10 | 2177.23 | 03-APR-19:10 | 0.117692E+10 | 965.27 | 03-APR-19:10 |
May | 0.226431E+10 | 2177.23 | 01-MAY-19:10 | 0.121917E+10 | 965.27 | 01-MAY-19:10 |
June | 0.219377E+10 | 2177.23 | 01-JUN-19:10 | 0.118076E+10 | 965.27 | 01-JUN-19:10 |
July | 0.225430E+10 | 2177.23 | 03-JUL-19:10 | 0.121533E+10 | 965.27 | 03-JUL-19:10 |
August | 0.226823E+10 | 2177.23 | 01-AUG-19:10 | 0.122063E+10 | 965.27 | 01-AUG-19:10 |
September | 0.218463E+10 | 2177.23 | 01-SEP-19:10 | 0.117729E+10 | 965.27 | 01-SEP-19:10 |
October | 0.225952E+10 | 2177.23 | 02-OCT-19:10 | 0.121734E+10 | 965.27 | 02-OCT-19:10 |
November | 0.219203E+10 | 2177.23 | 01-NOV-19:10 | 0.118021E+10 | 965.27 | 01-NOV-19:10 |
December | 0.225430E+10 | 2177.23 | 01-DEC-20:10 | 0.121533E+10 | 965.27 | 01-DEC-20:10 |
Annual Sum or Average | 0.266236E+11 | 0.143405E+11 | ||||
Minimum of Months | 0.204093E+10 | 2177.23 | 0.109956E+10 | 965.27 | ||
Maximum of Months | 0.226823E+10 | 2177.23 | 0.122063E+10 | 965.27 |
Report: ZoneElectricSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.123020E+11 | 11849.32 | 02-JAN-20:10 | 0.126520E+11 | 10029.21 | 02-JAN-20:10 |
February | 0.111075E+11 | 11849.32 | 01-FEB-20:10 | 0.114244E+11 | 10029.21 | 01-FEB-20:10 |
March | 0.123399E+11 | 11849.32 | 01-MAR-20:10 | 0.126786E+11 | 10029.21 | 01-MAR-20:10 |
April | 0.118849E+11 | 11849.32 | 03-APR-19:10 | 0.122282E+11 | 10029.21 | 03-APR-19:10 |
May | 0.123233E+11 | 11849.32 | 01-MAY-19:10 | 0.126672E+11 | 10029.21 | 01-MAY-19:10 |
June | 0.119394E+11 | 11849.32 | 01-JUN-19:10 | 0.122682E+11 | 10029.21 | 01-JUN-19:10 |
July | 0.122688E+11 | 11849.32 | 03-JUL-19:10 | 0.126273E+11 | 10029.21 | 03-JUL-19:10 |
August | 0.123446E+11 | 11849.32 | 01-AUG-19:10 | 0.126824E+11 | 10029.21 | 01-AUG-19:10 |
September | 0.118896E+11 | 11849.32 | 01-SEP-19:10 | 0.122320E+11 | 10029.21 | 01-SEP-19:10 |
October | 0.122972E+11 | 11849.32 | 02-OCT-19:10 | 0.126482E+11 | 10029.21 | 02-OCT-19:10 |
November | 0.119299E+11 | 11849.32 | 01-NOV-19:10 | 0.122624E+11 | 10029.21 | 01-NOV-19:10 |
December | 0.122688E+11 | 11849.32 | 01-DEC-20:10 | 0.126273E+11 | 10029.21 | 01-DEC-20:10 |
Annual Sum or Average | 0.144896E+12 | 0.148998E+12 | ||||
Minimum of Months | 0.111075E+11 | 11849.32 | 0.114244E+11 | 10029.21 | ||
Maximum of Months | 0.123446E+11 | 11849.32 | 0.126824E+11 | 10029.21 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.434056E+09 | 392.73 | 01-JAN-19:10 | 0.261068E+09 | 237.06 | 01-JAN-08:09 |
February | 0.391995E+09 | 392.73 | 01-FEB-20:10 | 0.235798E+09 | 237.06 | 01-FEB-07:10 |
March | 0.430607E+09 | 392.73 | 01-MAR-20:10 | 0.260708E+09 | 237.06 | 01-MAR-07:10 |
April | 0.420554E+09 | 392.73 | 01-APR-18:10 | 0.252705E+09 | 237.06 | 01-APR-07:10 |
May | 0.432331E+09 | 392.73 | 01-MAY-19:10 | 0.260888E+09 | 237.06 | 01-MAY-06:10 |
June | 0.417218E+09 | 392.73 | 01-JUN-19:10 | 0.252344E+09 | 237.06 | 01-JUN-06:10 |
July | 0.435725E+09 | 392.73 | 01-JUL-18:10 | 0.261248E+09 | 237.06 | 01-JUL-07:10 |
August | 0.430607E+09 | 392.73 | 01-AUG-19:10 | 0.260708E+09 | 237.06 | 01-AUG-06:10 |
September | 0.420667E+09 | 392.73 | 01-SEP-19:10 | 0.252705E+09 | 237.06 | 01-SEP-06:10 |
October | 0.434000E+09 | 392.73 | 01-OCT-18:10 | 0.261068E+09 | 237.06 | 01-OCT-07:10 |
November | 0.418886E+09 | 392.73 | 01-NOV-19:10 | 0.252524E+09 | 237.06 | 01-NOV-06:10 |
December | 0.435781E+09 | 392.73 | 01-DEC-20:10 | 0.261248E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.510243E+10 | 0.307301E+10 | ||||
Minimum of Months | 0.391995E+09 | 392.73 | 0.235798E+09 | 237.06 | ||
Maximum of Months | 0.435781E+09 | 392.73 | 0.261248E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.434005E+09 | 392.68 | 01-JAN-19:10 | 0.261038E+09 | 237.03 | 01-JAN-08:09 |
February | 0.391949E+09 | 392.68 | 01-FEB-20:10 | 0.235770E+09 | 237.03 | 01-FEB-07:10 |
March | 0.430556E+09 | 392.68 | 01-MAR-20:10 | 0.260677E+09 | 237.03 | 01-MAR-07:10 |
April | 0.420505E+09 | 392.68 | 01-APR-18:10 | 0.252675E+09 | 237.03 | 01-APR-07:10 |
May | 0.432281E+09 | 392.68 | 01-MAY-19:10 | 0.260857E+09 | 237.03 | 01-MAY-06:10 |
June | 0.417169E+09 | 392.68 | 01-JUN-19:10 | 0.252315E+09 | 237.03 | 01-JUN-06:10 |
July | 0.435674E+09 | 392.68 | 01-JUL-18:10 | 0.261218E+09 | 237.03 | 01-JUL-07:10 |
August | 0.430556E+09 | 392.68 | 01-AUG-19:10 | 0.260677E+09 | 237.03 | 01-AUG-06:10 |
September | 0.420618E+09 | 392.68 | 01-SEP-19:10 | 0.252675E+09 | 237.03 | 01-SEP-06:10 |
October | 0.433949E+09 | 392.68 | 01-OCT-18:10 | 0.261038E+09 | 237.03 | 01-OCT-07:10 |
November | 0.418837E+09 | 392.68 | 01-NOV-19:10 | 0.252495E+09 | 237.03 | 01-NOV-06:10 |
December | 0.435730E+09 | 392.68 | 01-DEC-20:10 | 0.261218E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.510183E+10 | 0.307265E+10 | ||||
Minimum of Months | 0.391949E+09 | 392.68 | 0.235770E+09 | 237.03 | ||
Maximum of Months | 0.435730E+09 | 392.68 | 0.261218E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.272788E+09 | 246.81 | 01-JAN-19:10 | 0.255708E+09 | 232.19 | 01-JAN-08:09 |
February | 0.246354E+09 | 246.81 | 01-FEB-20:10 | 0.230956E+09 | 232.19 | 01-FEB-07:10 |
March | 0.270620E+09 | 246.81 | 01-MAR-20:10 | 0.255355E+09 | 232.19 | 01-MAR-07:10 |
April | 0.264302E+09 | 246.81 | 01-APR-18:10 | 0.247516E+09 | 232.19 | 01-APR-07:10 |
May | 0.271704E+09 | 246.81 | 01-MAY-19:10 | 0.255532E+09 | 232.19 | 01-MAY-06:10 |
June | 0.262205E+09 | 246.81 | 01-JUN-19:10 | 0.247163E+09 | 232.19 | 01-JUN-06:10 |
July | 0.273836E+09 | 246.81 | 01-JUL-18:10 | 0.255885E+09 | 232.19 | 01-JUL-07:10 |
August | 0.270620E+09 | 246.81 | 01-AUG-19:10 | 0.255355E+09 | 232.19 | 01-AUG-06:10 |
September | 0.264373E+09 | 246.81 | 01-SEP-19:10 | 0.247516E+09 | 232.19 | 01-SEP-06:10 |
October | 0.272752E+09 | 246.81 | 01-OCT-18:10 | 0.255708E+09 | 232.19 | 01-OCT-07:10 |
November | 0.263254E+09 | 246.81 | 01-NOV-19:10 | 0.247340E+09 | 232.19 | 01-NOV-06:10 |
December | 0.273872E+09 | 246.81 | 01-DEC-20:10 | 0.255885E+09 | 232.19 | 01-DEC-07:10 |
Annual Sum or Average | 0.320668E+10 | 0.300992E+10 | ||||
Minimum of Months | 0.246354E+09 | 246.81 | 0.230956E+09 | 232.19 | ||
Maximum of Months | 0.273872E+09 | 246.81 | 0.255885E+09 | 232.19 |
Report: ZoneElectricSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.272862E+09 | 246.88 | 01-JAN-19:10 | 0.255778E+09 | 232.26 | 01-JAN-08:09 |
February | 0.246421E+09 | 246.88 | 01-FEB-20:10 | 0.231020E+09 | 232.26 | 01-FEB-07:10 |
March | 0.270694E+09 | 246.88 | 01-MAR-20:10 | 0.255425E+09 | 232.26 | 01-MAR-07:10 |
April | 0.264375E+09 | 246.88 | 01-APR-18:10 | 0.247584E+09 | 232.26 | 01-APR-07:10 |
May | 0.271778E+09 | 246.88 | 01-MAY-19:10 | 0.255602E+09 | 232.26 | 01-MAY-06:10 |
June | 0.262277E+09 | 246.88 | 01-JUN-19:10 | 0.247231E+09 | 232.26 | 01-JUN-06:10 |
July | 0.273911E+09 | 246.88 | 01-JUL-18:10 | 0.255955E+09 | 232.26 | 01-JUL-07:10 |
August | 0.270694E+09 | 246.88 | 01-AUG-19:10 | 0.255425E+09 | 232.26 | 01-AUG-06:10 |
September | 0.264446E+09 | 246.88 | 01-SEP-19:10 | 0.247584E+09 | 232.26 | 01-SEP-06:10 |
October | 0.272827E+09 | 246.88 | 01-OCT-18:10 | 0.255778E+09 | 232.26 | 01-OCT-07:10 |
November | 0.263326E+09 | 246.88 | 01-NOV-19:10 | 0.247408E+09 | 232.26 | 01-NOV-06:10 |
December | 0.273947E+09 | 246.88 | 01-DEC-20:10 | 0.255955E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.320756E+10 | 0.301074E+10 | ||||
Minimum of Months | 0.246421E+09 | 246.88 | 0.231020E+09 | 232.26 | ||
Maximum of Months | 0.273947E+09 | 246.88 | 0.255955E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.434056E+09 | 392.73 | 01-JAN-19:10 | 0.261068E+09 | 237.06 | 01-JAN-08:09 |
February | 0.391995E+09 | 392.73 | 01-FEB-20:10 | 0.235798E+09 | 237.06 | 01-FEB-07:10 |
March | 0.430607E+09 | 392.73 | 01-MAR-20:10 | 0.260708E+09 | 237.06 | 01-MAR-07:10 |
April | 0.420554E+09 | 392.73 | 01-APR-18:10 | 0.252705E+09 | 237.06 | 01-APR-07:10 |
May | 0.432331E+09 | 392.73 | 01-MAY-19:10 | 0.260888E+09 | 237.06 | 01-MAY-06:10 |
June | 0.417218E+09 | 392.73 | 01-JUN-19:10 | 0.252344E+09 | 237.06 | 01-JUN-06:10 |
July | 0.435725E+09 | 392.73 | 01-JUL-18:10 | 0.261248E+09 | 237.06 | 01-JUL-07:10 |
August | 0.430607E+09 | 392.73 | 01-AUG-19:10 | 0.260708E+09 | 237.06 | 01-AUG-06:10 |
September | 0.420667E+09 | 392.73 | 01-SEP-19:10 | 0.252705E+09 | 237.06 | 01-SEP-06:10 |
October | 0.434000E+09 | 392.73 | 01-OCT-18:10 | 0.261068E+09 | 237.06 | 01-OCT-07:10 |
November | 0.418886E+09 | 392.73 | 01-NOV-19:10 | 0.252524E+09 | 237.06 | 01-NOV-06:10 |
December | 0.435781E+09 | 392.73 | 01-DEC-20:10 | 0.261248E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.510243E+10 | 0.307301E+10 | ||||
Minimum of Months | 0.391995E+09 | 392.73 | 0.235798E+09 | 237.06 | ||
Maximum of Months | 0.435781E+09 | 392.73 | 0.261248E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.434005E+09 | 392.68 | 01-JAN-19:10 | 0.261038E+09 | 237.03 | 01-JAN-08:09 |
February | 0.391949E+09 | 392.68 | 01-FEB-20:10 | 0.235770E+09 | 237.03 | 01-FEB-07:10 |
March | 0.430556E+09 | 392.68 | 01-MAR-20:10 | 0.260677E+09 | 237.03 | 01-MAR-07:10 |
April | 0.420505E+09 | 392.68 | 01-APR-18:10 | 0.252675E+09 | 237.03 | 01-APR-07:10 |
May | 0.432281E+09 | 392.68 | 01-MAY-19:10 | 0.260857E+09 | 237.03 | 01-MAY-06:10 |
June | 0.417169E+09 | 392.68 | 01-JUN-19:10 | 0.252315E+09 | 237.03 | 01-JUN-06:10 |
July | 0.435674E+09 | 392.68 | 01-JUL-18:10 | 0.261218E+09 | 237.03 | 01-JUL-07:10 |
August | 0.430556E+09 | 392.68 | 01-AUG-19:10 | 0.260677E+09 | 237.03 | 01-AUG-06:10 |
September | 0.420618E+09 | 392.68 | 01-SEP-19:10 | 0.252675E+09 | 237.03 | 01-SEP-06:10 |
October | 0.433949E+09 | 392.68 | 01-OCT-18:10 | 0.261038E+09 | 237.03 | 01-OCT-07:10 |
November | 0.418837E+09 | 392.68 | 01-NOV-19:10 | 0.252495E+09 | 237.03 | 01-NOV-06:10 |
December | 0.435730E+09 | 392.68 | 01-DEC-20:10 | 0.261218E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.510183E+10 | 0.307265E+10 | ||||
Minimum of Months | 0.391949E+09 | 392.68 | 0.235770E+09 | 237.03 | ||
Maximum of Months | 0.435730E+09 | 392.68 | 0.261218E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.133160E+10 | 1282.60 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.120231E+10 | 1282.60 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.133570E+10 | 1282.60 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.128645E+10 | 1282.60 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.133391E+10 | 1282.60 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.129235E+10 | 1282.60 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.132801E+10 | 1282.60 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.133622E+10 | 1282.60 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.128696E+10 | 1282.60 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.133109E+10 | 1282.60 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.129132E+10 | 1282.60 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.132801E+10 | 1282.60 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.156839E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.120231E+10 | 1282.60 | 0.00 | 0.00 | |
Maximum of Months | 0.133622E+10 | 1282.60 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.434056E+09 | 392.73 | 01-JAN-19:10 | 0.261068E+09 | 237.06 | 01-JAN-08:09 |
February | 0.391995E+09 | 392.73 | 01-FEB-20:10 | 0.235798E+09 | 237.06 | 01-FEB-07:10 |
March | 0.430607E+09 | 392.73 | 01-MAR-20:10 | 0.260708E+09 | 237.06 | 01-MAR-07:10 |
April | 0.420554E+09 | 392.73 | 01-APR-18:10 | 0.252705E+09 | 237.06 | 01-APR-07:10 |
May | 0.432331E+09 | 392.73 | 01-MAY-19:10 | 0.260888E+09 | 237.06 | 01-MAY-06:10 |
June | 0.417218E+09 | 392.73 | 01-JUN-19:10 | 0.252344E+09 | 237.06 | 01-JUN-06:10 |
July | 0.435725E+09 | 392.73 | 01-JUL-18:10 | 0.261248E+09 | 237.06 | 01-JUL-07:10 |
August | 0.430607E+09 | 392.73 | 01-AUG-19:10 | 0.260708E+09 | 237.06 | 01-AUG-06:10 |
September | 0.420667E+09 | 392.73 | 01-SEP-19:10 | 0.252705E+09 | 237.06 | 01-SEP-06:10 |
October | 0.434000E+09 | 392.73 | 01-OCT-18:10 | 0.261068E+09 | 237.06 | 01-OCT-07:10 |
November | 0.418886E+09 | 392.73 | 01-NOV-19:10 | 0.252524E+09 | 237.06 | 01-NOV-06:10 |
December | 0.435781E+09 | 392.73 | 01-DEC-20:10 | 0.261248E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.510243E+10 | 0.307301E+10 | ||||
Minimum of Months | 0.391995E+09 | 392.73 | 0.235798E+09 | 237.06 | ||
Maximum of Months | 0.435781E+09 | 392.73 | 0.261248E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.434005E+09 | 392.68 | 01-JAN-19:10 | 0.261038E+09 | 237.03 | 01-JAN-08:09 |
February | 0.391949E+09 | 392.68 | 01-FEB-20:10 | 0.235770E+09 | 237.03 | 01-FEB-07:10 |
March | 0.430556E+09 | 392.68 | 01-MAR-20:10 | 0.260677E+09 | 237.03 | 01-MAR-07:10 |
April | 0.420505E+09 | 392.68 | 01-APR-18:10 | 0.252675E+09 | 237.03 | 01-APR-07:10 |
May | 0.432281E+09 | 392.68 | 01-MAY-19:10 | 0.260857E+09 | 237.03 | 01-MAY-06:10 |
June | 0.417169E+09 | 392.68 | 01-JUN-19:10 | 0.252315E+09 | 237.03 | 01-JUN-06:10 |
July | 0.435674E+09 | 392.68 | 01-JUL-18:10 | 0.261218E+09 | 237.03 | 01-JUL-07:10 |
August | 0.430556E+09 | 392.68 | 01-AUG-19:10 | 0.260677E+09 | 237.03 | 01-AUG-06:10 |
September | 0.420618E+09 | 392.68 | 01-SEP-19:10 | 0.252675E+09 | 237.03 | 01-SEP-06:10 |
October | 0.433949E+09 | 392.68 | 01-OCT-18:10 | 0.261038E+09 | 237.03 | 01-OCT-07:10 |
November | 0.418837E+09 | 392.68 | 01-NOV-19:10 | 0.252495E+09 | 237.03 | 01-NOV-06:10 |
December | 0.435730E+09 | 392.68 | 01-DEC-20:10 | 0.261218E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.510183E+10 | 0.307265E+10 | ||||
Minimum of Months | 0.391949E+09 | 392.68 | 0.235770E+09 | 237.03 | ||
Maximum of Months | 0.435730E+09 | 392.68 | 0.261218E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.272862E+09 | 246.88 | 01-JAN-19:10 | 0.255778E+09 | 232.26 | 01-JAN-08:09 |
February | 0.246421E+09 | 246.88 | 01-FEB-20:10 | 0.231020E+09 | 232.26 | 01-FEB-07:10 |
March | 0.270694E+09 | 246.88 | 01-MAR-20:10 | 0.255425E+09 | 232.26 | 01-MAR-07:10 |
April | 0.264375E+09 | 246.88 | 01-APR-18:10 | 0.247584E+09 | 232.26 | 01-APR-07:10 |
May | 0.271778E+09 | 246.88 | 01-MAY-19:10 | 0.255602E+09 | 232.26 | 01-MAY-06:10 |
June | 0.262277E+09 | 246.88 | 01-JUN-19:10 | 0.247231E+09 | 232.26 | 01-JUN-06:10 |
July | 0.273911E+09 | 246.88 | 01-JUL-18:10 | 0.255955E+09 | 232.26 | 01-JUL-07:10 |
August | 0.270694E+09 | 246.88 | 01-AUG-19:10 | 0.255425E+09 | 232.26 | 01-AUG-06:10 |
September | 0.264446E+09 | 246.88 | 01-SEP-19:10 | 0.247584E+09 | 232.26 | 01-SEP-06:10 |
October | 0.272827E+09 | 246.88 | 01-OCT-18:10 | 0.255778E+09 | 232.26 | 01-OCT-07:10 |
November | 0.263326E+09 | 246.88 | 01-NOV-19:10 | 0.247408E+09 | 232.26 | 01-NOV-06:10 |
December | 0.273947E+09 | 246.88 | 01-DEC-20:10 | 0.255955E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.320756E+10 | 0.301074E+10 | ||||
Minimum of Months | 0.246421E+09 | 246.88 | 0.231020E+09 | 232.26 | ||
Maximum of Months | 0.273947E+09 | 246.88 | 0.255955E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.396945E+10 | 3823.39 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.358405E+10 | 3823.39 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.398168E+10 | 3823.39 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.383486E+10 | 3823.39 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.397633E+10 | 3823.39 | 01-MAY-19:10 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.385245E+10 | 3823.39 | 01-JUN-19:10 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.395874E+10 | 3823.39 | 03-JUL-19:10 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.398321E+10 | 3823.39 | 01-AUG-19:10 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.383639E+10 | 3823.39 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.396792E+10 | 3823.39 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.384939E+10 | 3823.39 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.395874E+10 | 3823.39 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.467532E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.358405E+10 | 3823.39 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.398321E+10 | 3823.39 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.396945E+10 | 3823.39 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.358405E+10 | 3823.39 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.398168E+10 | 3823.39 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.383486E+10 | 3823.39 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.397633E+10 | 3823.39 | 01-MAY-19:10 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.385245E+10 | 3823.39 | 01-JUN-19:10 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.395874E+10 | 3823.39 | 03-JUL-19:10 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.398321E+10 | 3823.39 | 01-AUG-19:10 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.383639E+10 | 3823.39 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.396792E+10 | 3823.39 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.384939E+10 | 3823.39 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.395874E+10 | 3823.39 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.467532E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.358405E+10 | 3823.39 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.398321E+10 | 3823.39 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.105977E+10 | 1020.78 | 02-JAN-20:10 | 0.373720E+11 | 16686.59 | 01-JAN-07:10 |
February | 0.956878E+09 | 1020.78 | 01-FEB-20:10 | 0.337554E+11 | 16686.59 | 01-FEB-07:10 |
March | 0.106304E+10 | 1020.78 | 01-MAR-20:10 | 0.373720E+11 | 16686.59 | 01-MAR-07:10 |
April | 0.102384E+10 | 1020.78 | 03-APR-19:10 | 0.361665E+11 | 16686.59 | 01-APR-06:10 |
May | 0.106161E+10 | 1020.78 | 01-MAY-19:10 | 0.373720E+11 | 16686.59 | 01-MAY-06:10 |
June | 0.102854E+10 | 1020.78 | 01-JUN-19:10 | 0.361665E+11 | 16686.59 | 01-JUN-06:10 |
July | 0.105691E+10 | 1020.78 | 03-JUL-19:10 | 0.373720E+11 | 16686.59 | 01-JUL-06:10 |
August | 0.106345E+10 | 1020.78 | 01-AUG-19:10 | 0.373720E+11 | 16686.59 | 01-AUG-06:10 |
September | 0.102425E+10 | 1020.78 | 01-SEP-19:10 | 0.361665E+11 | 16686.59 | 01-SEP-06:10 |
October | 0.105936E+10 | 1020.78 | 02-OCT-19:10 | 0.373720E+11 | 16686.59 | 01-OCT-06:10 |
November | 0.102772E+10 | 1020.78 | 01-NOV-19:10 | 0.361665E+11 | 16686.59 | 01-NOV-06:10 |
December | 0.105691E+10 | 1020.78 | 01-DEC-20:10 | 0.373720E+11 | 16686.59 | 01-DEC-07:10 |
Annual Sum or Average | 0.124823E+11 | 0.440025E+12 | ||||
Minimum of Months | 0.956878E+09 | 1020.78 | 0.337554E+11 | 16686.59 | ||
Maximum of Months | 0.106345E+10 | 1020.78 | 0.373720E+11 | 16686.59 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.140929E+10 | 1357.44 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.127246E+10 | 1357.44 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.141364E+10 | 1357.44 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.136151E+10 | 1357.44 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.141173E+10 | 1357.44 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.136775E+10 | 1357.44 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.140549E+10 | 1357.44 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.141418E+10 | 1357.44 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.136205E+10 | 1357.44 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.140875E+10 | 1357.44 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.136667E+10 | 1357.44 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.140549E+10 | 1357.44 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.165990E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.127246E+10 | 1357.44 | 0.00 | 0.00 | |
Maximum of Months | 0.141418E+10 | 1357.44 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.195762E+11 | 0.140333E+11 | 0.127587E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.176991E+11 | 0.126708E+11 | 0.115208E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.196682E+11 | 0.140766E+11 | 0.127855E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.189781E+11 | 0.135575E+11 | 0.123314E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.196176E+11 | 0.140576E+11 | 0.127741E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.190195E+11 | 0.136197E+11 | 0.123716E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.195762E+11 | 0.139955E+11 | 0.127338E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.196590E+11 | 0.140820E+11 | 0.127894E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.189689E+11 | 0.135629E+11 | 0.123352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.195854E+11 | 0.140279E+11 | 0.127549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.189367E+11 | 0.136089E+11 | 0.123659E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.195762E+11 | 0.139955E+11 | 0.127338E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.230861E+12 | 0.165288E+12 | 0.150255E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.176991E+11 | 0.126708E+11 | 0.115208E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.196682E+11 | 0.140820E+11 | 0.127894E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.199054E+10 | 0.713551E+09 | 0.864900E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 33887804.85 | 0.138886E+09 |
February | 0.179968E+10 | 0.644271E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 66776700.67 | 84348961.80 |
March | 0.199990E+10 | 0.715750E+09 | 0.866718E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159059E+09 | 44572161.01 |
April | 0.192973E+10 | 0.689358E+09 | 0.835931E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.299329E+09 | 8041683.61 |
May | 0.199475E+10 | 0.714788E+09 | 0.865939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.560093E+09 | 43431.34 |
June | 0.193394E+10 | 0.692519E+09 | 0.838659E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.617525E+09 | 53.25 |
July | 0.199054E+10 | 0.711626E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.739448E+09 | 0.00 |
August | 0.199896E+10 | 0.716025E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.746206E+09 | 0.00 |
September | 0.192879E+10 | 0.689633E+09 | 0.836191E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.588311E+09 | 0.00 |
October | 0.199148E+10 | 0.713276E+09 | 0.864640E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.455869E+09 | 18350.59 |
November | 0.192552E+10 | 0.691970E+09 | 0.838269E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.245875E+09 | 9543078.94 |
December | 0.199054E+10 | 0.711626E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 82818558.08 | 80412534.90 |
Annual Sum or Average | 0.234744E+11 | 0.840439E+10 | 0.101856E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.459520E+10 | 0.365867E+09 |
Minimum of Months | 0.179968E+10 | 0.644271E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 33887804.85 | 0.00 |
Maximum of Months | 0.199990E+10 | 0.716025E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.746206E+09 | 0.138886E+09 |
Report: SpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.230505E+10 | 0.826294E+09 | 0.100156E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13205645.99 | 54453304.95 |
February | 0.208403E+10 | 0.746069E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 25960715.69 | 33181026.00 |
March | 0.231589E+10 | 0.828841E+09 | 0.100366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 60419360.87 | 17552015.76 |
April | 0.223463E+10 | 0.798279E+09 | 0.968011E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113500E+09 | 3124573.10 |
May | 0.230993E+10 | 0.827727E+09 | 0.100276E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.212670E+09 | 19658.35 |
June | 0.223950E+10 | 0.801940E+09 | 0.971170E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.234406E+09 | 746.31 |
July | 0.230505E+10 | 0.824066E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.283120E+09 | 0.00 |
August | 0.231480E+10 | 0.829160E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.287469E+09 | 0.00 |
September | 0.223354E+10 | 0.798597E+09 | 0.968312E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.226859E+09 | 0.00 |
October | 0.230614E+10 | 0.825976E+09 | 0.100126E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.176852E+09 | 7823.71 |
November | 0.222975E+10 | 0.801303E+09 | 0.970719E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 95678363.28 | 3742590.89 |
December | 0.230505E+10 | 0.824066E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 32227722.29 | 31654544.98 |
Annual Sum or Average | 0.271834E+11 | 0.973232E+10 | 0.117950E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.176237E+10 | 0.143736E+09 |
Minimum of Months | 0.208403E+10 | 0.746069E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13205645.99 | 0.00 |
Maximum of Months | 0.231589E+10 | 0.829160E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.287469E+09 | 54453304.95 |
Report: SpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.487480E+09 | 0.154452E+10 | 0.105898E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31392187.01 | 0.126715E+09 |
February | 0.440737E+09 | 0.139456E+10 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 62293384.34 | 76955046.67 |
March | 0.489771E+09 | 0.154928E+10 | 0.106120E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.145658E+09 | 40700489.36 |
April | 0.472586E+09 | 0.149215E+10 | 0.102351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.272252E+09 | 7330062.72 |
May | 0.488511E+09 | 0.154719E+10 | 0.106025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.506922E+09 | 39496.71 |
June | 0.473617E+09 | 0.149899E+10 | 0.102685E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.555492E+09 | 3233.14 |
July | 0.487480E+09 | 0.154035E+10 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.667119E+09 | 0.00 |
August | 0.489542E+09 | 0.154987E+10 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.677754E+09 | 0.00 |
September | 0.472357E+09 | 0.149274E+10 | 0.102382E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.540381E+09 | 0.00 |
October | 0.487709E+09 | 0.154392E+10 | 0.105866E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.424321E+09 | 16618.77 |
November | 0.471555E+09 | 0.149780E+10 | 0.102637E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230208E+09 | 8706180.54 |
December | 0.487480E+09 | 0.154035E+10 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 77389261.98 | 73382656.54 |
Annual Sum or Average | 0.574883E+10 | 0.181917E+11 | 0.124712E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.419118E+10 | 0.333849E+09 |
Minimum of Months | 0.440737E+09 | 0.139456E+10 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 31392187.01 | 0.00 |
Maximum of Months | 0.489771E+09 | 0.154987E+10 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.677754E+09 | 0.126715E+09 |
Report: SpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.374985E+09 | 0.283535E+09 | 0.305485E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18117369.44 | 73097036.05 |
February | 0.339028E+09 | 0.256006E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 36053124.39 | 44382558.45 |
March | 0.376747E+09 | 0.284409E+09 | 0.306128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 84532551.59 | 23450724.74 |
April | 0.363528E+09 | 0.273921E+09 | 0.295253E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158155E+09 | 4229129.63 |
May | 0.375778E+09 | 0.284026E+09 | 0.305852E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.294610E+09 | 22813.13 |
June | 0.364321E+09 | 0.275178E+09 | 0.296217E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.322790E+09 | 923.70 |
July | 0.374985E+09 | 0.282770E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.386889E+09 | 0.00 |
August | 0.376571E+09 | 0.284518E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.392994E+09 | 0.00 |
September | 0.363352E+09 | 0.274031E+09 | 0.295345E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.313832E+09 | 0.00 |
October | 0.375161E+09 | 0.283425E+09 | 0.305393E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.246521E+09 | 9595.85 |
November | 0.362735E+09 | 0.274959E+09 | 0.296079E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133681E+09 | 5019137.38 |
December | 0.374985E+09 | 0.282770E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 44770136.56 | 42308453.21 |
Annual Sum or Average | 0.442217E+10 | 0.333955E+10 | 0.359760E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.243295E+10 | 0.192520E+09 |
Minimum of Months | 0.339028E+09 | 0.256006E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18117369.44 | 0.00 |
Maximum of Months | 0.376747E+09 | 0.284518E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.392994E+09 | 73097036.05 |
Report: SpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.154405E+10 | 0.350256E+09 | 0.576866E+10 | 0.501157E+11 | 0.00 | 0.00 | 0.00 | 40889611.04 | 0.200479E+09 |
February | 0.139600E+10 | 0.316249E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 78464697.25 | 0.124478E+09 |
March | 0.155131E+10 | 0.351336E+09 | 0.578079E+10 | 0.502211E+11 | 0.00 | 0.00 | 0.00 | 0.181649E+09 | 65972892.50 |
April | 0.149688E+10 | 0.338381E+09 | 0.557545E+10 | 0.484372E+11 | 0.00 | 0.00 | 0.00 | 0.349465E+09 | 10635788.13 |
May | 0.154732E+10 | 0.350863E+09 | 0.577559E+10 | 0.501759E+11 | 0.00 | 0.00 | 0.00 | 0.677955E+09 | 108837.21 |
June | 0.150015E+10 | 0.339933E+09 | 0.559364E+10 | 0.485952E+11 | 0.00 | 0.00 | 0.00 | 0.752692E+09 | 1939.86 |
July | 0.154405E+10 | 0.349311E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 0.915439E+09 | 0.00 |
August | 0.155059E+10 | 0.351471E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 0.931256E+09 | 0.00 |
September | 0.149615E+10 | 0.338516E+09 | 0.557718E+10 | 0.484522E+11 | 0.00 | 0.00 | 0.00 | 0.728593E+09 | 0.00 |
October | 0.154478E+10 | 0.350121E+09 | 0.576693E+10 | 0.501006E+11 | 0.00 | 0.00 | 0.00 | 0.559737E+09 | 22788.35 |
November | 0.149361E+10 | 0.339663E+09 | 0.559104E+10 | 0.485726E+11 | 0.00 | 0.00 | 0.00 | 0.291175E+09 | 13435459.31 |
December | 0.154405E+10 | 0.349311E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 95315128.55 | 0.118232E+09 |
Annual Sum or Average | 0.182090E+11 | 0.412541E+10 | 0.679355E+11 | 0.590196E+12 | 0.00 | 0.00 | 0.00 | 0.560263E+10 | 0.533366E+09 |
Minimum of Months | 0.139600E+10 | 0.316249E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 40889611.04 | 0.00 |
Maximum of Months | 0.155131E+10 | 0.351471E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 0.931256E+09 | 0.200479E+09 |
Report: SpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.261570E+11 | 0.226040E+10 | 0.121771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 74877972.06 | 0.311640E+09 |
February | 0.236489E+11 | 0.204093E+10 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.145904E+09 | 0.190385E+09 |
March | 0.262800E+11 | 0.226736E+10 | 0.122027E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.343194E+09 | 0.102025E+09 |
April | 0.253579E+11 | 0.218376E+10 | 0.117692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.645565E+09 | 18711599.12 |
May | 0.262123E+11 | 0.226431E+10 | 0.121917E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120944E+10 | 109029.05 |
June | 0.254132E+11 | 0.219377E+10 | 0.118076E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133390E+10 | 100.60 |
July | 0.261570E+11 | 0.225430E+10 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160734E+10 | 0.00 |
August | 0.262677E+11 | 0.226823E+10 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162817E+10 | 0.00 |
September | 0.253456E+11 | 0.218463E+10 | 0.117729E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127701E+10 | 0.00 |
October | 0.261693E+11 | 0.225952E+10 | 0.121734E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.985052E+09 | 40897.77 |
November | 0.253025E+11 | 0.219203E+10 | 0.118021E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.531980E+09 | 23033204.91 |
December | 0.261570E+11 | 0.225430E+10 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181936E+09 | 0.182578E+09 |
Annual Sum or Average | 0.308468E+12 | 0.266236E+11 | 0.143405E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.996437E+10 | 0.828524E+09 |
Minimum of Months | 0.236489E+11 | 0.204093E+10 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 74877972.06 | 0.00 |
Maximum of Months | 0.262800E+11 | 0.226823E+10 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162817E+10 | 0.311640E+09 |
Report: SpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.776503E+11 | 0.123020E+11 | 0.126520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.214068E+09 | 0.923263E+09 |
February | 0.702046E+11 | 0.111075E+11 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.414417E+09 | 0.568917E+09 |
March | 0.780153E+11 | 0.123399E+11 | 0.126786E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.963318E+09 | 0.310549E+09 |
April | 0.752779E+11 | 0.118849E+11 | 0.122282E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181381E+10 | 60143490.58 |
May | 0.778146E+11 | 0.123233E+11 | 0.126672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.342274E+10 | 600967.68 |
June | 0.754422E+11 | 0.119394E+11 | 0.122682E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.378122E+10 | 14403.72 |
July | 0.776503E+11 | 0.122688E+11 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.457657E+10 | 0.00 |
August | 0.779788E+11 | 0.123446E+11 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.465046E+10 | 0.00 |
September | 0.752414E+11 | 0.118896E+11 | 0.122320E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.365385E+10 | 0.00 |
October | 0.776868E+11 | 0.122972E+11 | 0.126482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.282729E+10 | 295990.60 |
November | 0.751137E+11 | 0.119299E+11 | 0.122624E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151900E+10 | 75281262.99 |
December | 0.776503E+11 | 0.122688E+11 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.515150E+09 | 0.549191E+09 |
Annual Sum or Average | 0.915726E+12 | 0.144896E+12 | 0.148998E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.283519E+11 | 0.248826E+10 |
Minimum of Months | 0.702046E+11 | 0.111075E+11 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.214068E+09 | 0.00 |
Maximum of Months | 0.780153E+11 | 0.123446E+11 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.465046E+10 | 0.923263E+09 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.434056E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8033088.66 | 90059865.44 |
February | 0.273974E+09 | 0.391995E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 26438984.85 | 55714534.94 |
March | 0.303685E+09 | 0.430607E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 73393035.38 | 29308301.22 |
April | 0.293479E+09 | 0.420554E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.152111E+09 | 5588868.69 |
May | 0.303504E+09 | 0.432331E+09 | 0.260888E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.303260E+09 | 86627.32 |
June | 0.293842E+09 | 0.417218E+09 | 0.252344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.338506E+09 | 27972.42 |
July | 0.303141E+09 | 0.435725E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.413176E+09 | 0.00 |
August | 0.303685E+09 | 0.430607E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.421113E+09 | 0.00 |
September | 0.293479E+09 | 0.420667E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.326983E+09 | 0.00 |
October | 0.303322E+09 | 0.434000E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.248214E+09 | 40073.65 |
November | 0.293661E+09 | 0.418886E+09 | 0.252524E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124723E+09 | 6567122.68 |
December | 0.303141E+09 | 0.435781E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 32102440.03 | 51902233.55 |
Annual Sum or Average | 0.357224E+10 | 0.510243E+10 | 0.307301E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.246805E+10 | 0.239296E+09 |
Minimum of Months | 0.273974E+09 | 0.391995E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8033088.66 | 0.00 |
Maximum of Months | 0.303685E+09 | 0.435781E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.421113E+09 | 90059865.44 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.434005E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9633927.58 | 87579358.32 |
February | 0.273974E+09 | 0.391949E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 27292191.00 | 54623317.21 |
March | 0.303685E+09 | 0.430556E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 73990040.89 | 29066920.09 |
April | 0.293479E+09 | 0.420505E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.152201E+09 | 5572435.49 |
May | 0.303504E+09 | 0.432281E+09 | 0.260857E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.303213E+09 | 87616.54 |
June | 0.293842E+09 | 0.417169E+09 | 0.252315E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.338440E+09 | 27976.58 |
July | 0.303141E+09 | 0.435674E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.413121E+09 | 0.00 |
August | 0.303685E+09 | 0.430556E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.421082E+09 | 0.00 |
September | 0.293479E+09 | 0.420618E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.327026E+09 | 0.00 |
October | 0.303322E+09 | 0.433949E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.248472E+09 | 34043.60 |
November | 0.293661E+09 | 0.418837E+09 | 0.252495E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125357E+09 | 6450352.19 |
December | 0.303141E+09 | 0.435730E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 33694148.02 | 50912258.38 |
Annual Sum or Average | 0.357224E+10 | 0.510183E+10 | 0.307265E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.247352E+10 | 0.234354E+09 |
Minimum of Months | 0.273974E+09 | 0.391949E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9633927.58 | 0.00 |
Maximum of Months | 0.303685E+09 | 0.435730E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.421082E+09 | 87579358.32 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.272788E+09 | 0.255708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 968537.56 | 39673166.89 |
February | 0.00 | 0.246354E+09 | 0.230956E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4472224.79 | 26624075.49 |
March | 0.00 | 0.270620E+09 | 0.255355E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13625441.77 | 16372147.23 |
April | 0.00 | 0.264302E+09 | 0.247516E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 31659226.52 | 4995814.30 |
May | 0.00 | 0.271704E+09 | 0.255532E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 70628064.54 | 214728.98 |
June | 0.00 | 0.262205E+09 | 0.247163E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 80959219.39 | 8246.79 |
July | 0.00 | 0.273836E+09 | 0.255885E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101496E+09 | 0.00 |
August | 0.00 | 0.270620E+09 | 0.255355E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103694E+09 | 0.00 |
September | 0.00 | 0.264373E+09 | 0.247516E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 77615252.57 | 6012.30 |
October | 0.00 | 0.272752E+09 | 0.255708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 55108217.61 | 234323.18 |
November | 0.00 | 0.263254E+09 | 0.247340E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 24722821.66 | 6081052.88 |
December | 0.00 | 0.273872E+09 | 0.255885E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4850385.61 | 25882463.67 |
Annual Sum or Average | 0.00 | 0.320668E+10 | 0.300992E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.569799E+09 | 0.120092E+09 |
Minimum of Months | 0.00 | 0.246354E+09 | 0.230956E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 968537.56 | 0.00 |
Maximum of Months | 0.00 | 0.273872E+09 | 0.255885E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103694E+09 | 39673166.89 |
Report: SpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.272862E+09 | 0.255778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3289360.72 | 24285671.13 |
February | 0.273974E+09 | 0.246421E+09 | 0.231020E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8245091.59 | 15045097.33 |
March | 0.303685E+09 | 0.270694E+09 | 0.255425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21474899.77 | 8084045.82 |
April | 0.293479E+09 | 0.264375E+09 | 0.247584E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 42923156.80 | 1555309.26 |
May | 0.303504E+09 | 0.271778E+09 | 0.255602E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 84888141.05 | 21273.86 |
June | 0.293842E+09 | 0.262277E+09 | 0.247231E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 94667918.90 | 7012.59 |
July | 0.303141E+09 | 0.273911E+09 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115492E+09 | 0.00 |
August | 0.303685E+09 | 0.270694E+09 | 0.255425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117732E+09 | 0.00 |
September | 0.293479E+09 | 0.264446E+09 | 0.247584E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 91535379.72 | 0.00 |
October | 0.303322E+09 | 0.272827E+09 | 0.255778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 69734431.97 | 9481.62 |
November | 0.293661E+09 | 0.263326E+09 | 0.247408E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 35647860.18 | 1809319.71 |
December | 0.303141E+09 | 0.273947E+09 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10341198.47 | 14203516.08 |
Annual Sum or Average | 0.357224E+10 | 0.320756E+10 | 0.301074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.695971E+09 | 65020727.38 |
Minimum of Months | 0.273974E+09 | 0.246421E+09 | 0.231020E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3289360.72 | 0.00 |
Maximum of Months | 0.303685E+09 | 0.273947E+09 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117732E+09 | 24285671.13 |
Report: SpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.434056E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7847814.30 | 91009648.14 |
February | 0.273974E+09 | 0.391995E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 26244709.09 | 56387319.27 |
March | 0.303685E+09 | 0.430607E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 73152646.84 | 29666943.85 |
April | 0.293479E+09 | 0.420554E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151769E+09 | 5798884.83 |
May | 0.303504E+09 | 0.432331E+09 | 0.260888E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.303006E+09 | 101479.09 |
June | 0.293842E+09 | 0.417218E+09 | 0.252344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.338344E+09 | 28011.95 |
July | 0.303141E+09 | 0.435725E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.413068E+09 | 0.00 |
August | 0.303685E+09 | 0.430607E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.421005E+09 | 0.00 |
September | 0.293479E+09 | 0.420667E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.326825E+09 | 0.00 |
October | 0.303322E+09 | 0.434000E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.247949E+09 | 55518.75 |
November | 0.293661E+09 | 0.418886E+09 | 0.252524E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124455E+09 | 6795030.56 |
December | 0.303141E+09 | 0.435781E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 31897105.71 | 52470447.03 |
Annual Sum or Average | 0.357224E+10 | 0.510243E+10 | 0.307301E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.246556E+10 | 0.242313E+09 |
Minimum of Months | 0.273974E+09 | 0.391995E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7847814.30 | 0.00 |
Maximum of Months | 0.303685E+09 | 0.435781E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.421005E+09 | 91009648.14 |
Report: SpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.434005E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9076606.38 | 87853689.69 |
February | 0.273974E+09 | 0.391949E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 26728113.69 | 55037033.80 |
March | 0.303685E+09 | 0.430556E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 73399103.50 | 29351454.94 |
April | 0.293479E+09 | 0.420505E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151808E+09 | 5784778.52 |
May | 0.303504E+09 | 0.432281E+09 | 0.260857E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.302966E+09 | 101784.75 |
June | 0.293842E+09 | 0.417169E+09 | 0.252315E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.338290E+09 | 28009.19 |
July | 0.303141E+09 | 0.435674E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.413014E+09 | 0.00 |
August | 0.303685E+09 | 0.430556E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.420970E+09 | 0.00 |
September | 0.293479E+09 | 0.420618E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.326843E+09 | 0.00 |
October | 0.303322E+09 | 0.433949E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.248071E+09 | 50982.83 |
November | 0.293661E+09 | 0.418837E+09 | 0.252495E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124821E+09 | 6690441.05 |
December | 0.303141E+09 | 0.435730E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 33455554.65 | 51253533.00 |
Annual Sum or Average | 0.357224E+10 | 0.510183E+10 | 0.307265E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.246944E+10 | 0.236152E+09 |
Minimum of Months | 0.273974E+09 | 0.391949E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9076606.38 | 0.00 |
Maximum of Months | 0.303685E+09 | 0.435730E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.420970E+09 | 87853689.69 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.385223E+10 | 0.133160E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23499524.36 | 98890110.84 |
February | 0.348285E+10 | 0.120231E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46260862.36 | 60370298.46 |
March | 0.387034E+10 | 0.133570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107748E+09 | 32530837.48 |
April | 0.373454E+10 | 0.128645E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.199586E+09 | 6297231.07 |
May | 0.386038E+10 | 0.133391E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.363903E+09 | 102167.94 |
June | 0.374269E+10 | 0.129235E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.399076E+09 | 8122.59 |
July | 0.385223E+10 | 0.132801E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.482183E+09 | 0.00 |
August | 0.386853E+10 | 0.133622E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.488260E+09 | 0.00 |
September | 0.373273E+10 | 0.128696E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.383310E+09 | 0.00 |
October | 0.385404E+10 | 0.133109E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.297356E+09 | 48051.98 |
November | 0.372639E+10 | 0.129132E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163721E+09 | 7889790.24 |
December | 0.385223E+10 | 0.132801E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57811849.32 | 57782108.14 |
Annual Sum or Average | 0.454292E+11 | 0.156839E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.301271E+10 | 0.263919E+09 |
Minimum of Months | 0.348285E+10 | 0.120231E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23499524.36 | 0.00 |
Maximum of Months | 0.387034E+10 | 0.133622E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.488260E+09 | 98890110.84 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.434056E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7540883.98 | 91755527.45 |
February | 0.273974E+09 | 0.391995E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 25693955.85 | 57007265.95 |
March | 0.303685E+09 | 0.430607E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 71972346.74 | 30019638.63 |
April | 0.293479E+09 | 0.420554E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150339E+09 | 5799136.40 |
May | 0.303504E+09 | 0.432331E+09 | 0.260888E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.301312E+09 | 95752.46 |
June | 0.293842E+09 | 0.417218E+09 | 0.252344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.336663E+09 | 29282.96 |
July | 0.303141E+09 | 0.435725E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.411307E+09 | 0.00 |
August | 0.303685E+09 | 0.430607E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.419253E+09 | 0.00 |
September | 0.293479E+09 | 0.420667E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.325145E+09 | 0.00 |
October | 0.303322E+09 | 0.434000E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.246275E+09 | 42615.95 |
November | 0.293661E+09 | 0.418886E+09 | 0.252524E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123007E+09 | 6824895.86 |
December | 0.303141E+09 | 0.435781E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 31042908.70 | 53008709.36 |
Annual Sum or Average | 0.357224E+10 | 0.510243E+10 | 0.307301E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.244955E+10 | 0.244583E+09 |
Minimum of Months | 0.273974E+09 | 0.391995E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7540883.98 | 0.00 |
Maximum of Months | 0.303685E+09 | 0.435781E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.419253E+09 | 91755527.45 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.434005E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8531500.55 | 89520759.35 |
February | 0.273974E+09 | 0.391949E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 26189883.83 | 56074276.69 |
March | 0.303685E+09 | 0.430556E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 72256600.27 | 29799224.87 |
April | 0.293479E+09 | 0.420505E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150396E+09 | 5784494.58 |
May | 0.303504E+09 | 0.432281E+09 | 0.260857E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.301264E+09 | 97032.11 |
June | 0.293842E+09 | 0.417169E+09 | 0.252315E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.336596E+09 | 29283.92 |
July | 0.303141E+09 | 0.435674E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.411250E+09 | 0.00 |
August | 0.303685E+09 | 0.430556E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.419220E+09 | 0.00 |
September | 0.293479E+09 | 0.420618E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.325171E+09 | 0.00 |
October | 0.303322E+09 | 0.433949E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.246482E+09 | 37028.71 |
November | 0.293661E+09 | 0.418837E+09 | 0.252495E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123523E+09 | 6712096.63 |
December | 0.303141E+09 | 0.435730E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 32085607.80 | 52090400.56 |
Annual Sum or Average | 0.357224E+10 | 0.510183E+10 | 0.307265E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.245297E+10 | 0.240145E+09 |
Minimum of Months | 0.273974E+09 | 0.391949E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8531500.55 | 0.00 |
Maximum of Months | 0.303685E+09 | 0.435730E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.419220E+09 | 89520759.35 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.272862E+09 | 0.255778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3766081.64 | 47967050.55 |
February | 0.273974E+09 | 0.246421E+09 | 0.231020E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13054166.16 | 29611590.13 |
March | 0.303685E+09 | 0.270694E+09 | 0.255425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 36777514.69 | 15483624.48 |
April | 0.293479E+09 | 0.264375E+09 | 0.247584E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 76965558.31 | 2989995.41 |
May | 0.303504E+09 | 0.271778E+09 | 0.255602E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154258E+09 | 46729.64 |
June | 0.293842E+09 | 0.262277E+09 | 0.247231E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172340E+09 | 14978.26 |
July | 0.303141E+09 | 0.273911E+09 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.210502E+09 | 0.00 |
August | 0.303685E+09 | 0.270694E+09 | 0.255425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.214552E+09 | 0.00 |
September | 0.293479E+09 | 0.264446E+09 | 0.247584E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166369E+09 | 0.00 |
October | 0.303322E+09 | 0.272827E+09 | 0.255778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125920E+09 | 28609.82 |
November | 0.293661E+09 | 0.263326E+09 | 0.247408E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 62764362.26 | 3596772.39 |
December | 0.303141E+09 | 0.273947E+09 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15680376.30 | 27662161.85 |
Annual Sum or Average | 0.357224E+10 | 0.320756E+10 | 0.301074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125295E+10 | 0.127402E+09 |
Minimum of Months | 0.273974E+09 | 0.246421E+09 | 0.231020E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3766081.64 | 0.00 |
Maximum of Months | 0.303685E+09 | 0.273947E+09 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.214552E+09 | 47967050.55 |
Report: SpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.396945E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 43362641.68 | 0.236778E+09 |
February | 0.415303E+11 | 0.358405E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 84359291.09 | 0.151843E+09 |
March | 0.461508E+11 | 0.398168E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.196384E+09 | 88284039.41 |
April | 0.445315E+11 | 0.383486E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.373454E+09 | 20721960.79 |
May | 0.460320E+11 | 0.397633E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.720724E+09 | 456315.38 |
June | 0.446286E+11 | 0.385245E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.799925E+09 | 16511.27 |
July | 0.459349E+11 | 0.395874E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.975826E+09 | 0.00 |
August | 0.461292E+11 | 0.398321E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.995148E+09 | 0.00 |
September | 0.445099E+11 | 0.383639E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.777328E+09 | 0.00 |
October | 0.459565E+11 | 0.396792E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.595781E+09 | 198921.23 |
November | 0.444343E+11 | 0.384939E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.315003E+09 | 25474389.66 |
December | 0.459349E+11 | 0.395874E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105029E+09 | 0.147499E+09 |
Annual Sum or Average | 0.541708E+12 | 0.467532E+11 | 0.175857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.598232E+10 | 0.671272E+09 |
Minimum of Months | 0.415303E+11 | 0.358405E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 43362641.68 | 0.00 |
Maximum of Months | 0.461508E+11 | 0.398321E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.995148E+09 | 0.236778E+09 |
Report: SpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.396945E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 42651179.64 | 0.240225E+09 |
February | 0.415303E+11 | 0.358405E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 82930951.75 | 0.154612E+09 |
March | 0.461508E+11 | 0.398168E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192980E+09 | 90438893.93 |
April | 0.445315E+11 | 0.383486E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.367872E+09 | 21462080.71 |
May | 0.460320E+11 | 0.397633E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.714182E+09 | 495734.15 |
June | 0.446286E+11 | 0.385245E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.794301E+09 | 18406.40 |
July | 0.459349E+11 | 0.395874E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.971289E+09 | 0.00 |
August | 0.461292E+11 | 0.398321E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.990950E+09 | 0.00 |
September | 0.445099E+11 | 0.383639E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.772113E+09 | 0.00 |
October | 0.459565E+11 | 0.396792E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.589756E+09 | 216223.06 |
November | 0.444343E+11 | 0.384939E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.310483E+09 | 26334205.03 |
December | 0.459349E+11 | 0.395874E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103183E+09 | 0.150269E+09 |
Annual Sum or Average | 0.541708E+12 | 0.467532E+11 | 0.175857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.593269E+10 | 0.684072E+09 |
Minimum of Months | 0.415303E+11 | 0.358405E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 42651179.64 | 0.00 |
Maximum of Months | 0.461508E+11 | 0.398321E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.990950E+09 | 0.240225E+09 |
Report: SpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.408770E+10 | 0.105977E+10 | 0.338870E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 5453895.54 | 0.279504E+09 |
February | 0.369574E+10 | 0.956878E+09 | 0.306077E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 31664048.90 | 0.182064E+09 |
March | 0.410691E+10 | 0.106304E+10 | 0.338870E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.101895E+09 | 0.101091E+09 |
April | 0.396281E+10 | 0.102384E+10 | 0.327939E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 0.246702E+09 | 20939805.96 |
May | 0.409635E+10 | 0.106161E+10 | 0.338870E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.561999E+09 | 956182.77 |
June | 0.397146E+10 | 0.102854E+10 | 0.327939E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 0.640882E+09 | 98677.11 |
July | 0.408770E+10 | 0.105691E+10 | 0.338870E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.799601E+09 | 0.00 |
August | 0.410499E+10 | 0.106345E+10 | 0.338870E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.815592E+09 | 0.00 |
September | 0.396089E+10 | 0.102425E+10 | 0.327939E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 0.615798E+09 | 0.00 |
October | 0.408962E+10 | 0.105936E+10 | 0.338870E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.443353E+09 | 657786.50 |
November | 0.395417E+10 | 0.102772E+10 | 0.327939E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 0.189726E+09 | 25088415.13 |
December | 0.408770E+10 | 0.105691E+10 | 0.338870E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 31664248.97 | 0.169730E+09 |
Annual Sum or Average | 0.482060E+11 | 0.124823E+11 | 0.398993E+12 | 0.359593E+12 | 0.00 | 0.00 | 0.00 | 0.448433E+10 | 0.780131E+09 |
Minimum of Months | 0.369574E+10 | 0.956878E+09 | 0.306077E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 5453895.54 | 0.00 |
Maximum of Months | 0.410691E+10 | 0.106345E+10 | 0.338870E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.815592E+09 | 0.279504E+09 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.407704E+10 | 0.140929E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40306775.86 | 0.177402E+09 |
February | 0.368610E+10 | 0.127246E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81594707.84 | 0.108251E+09 |
March | 0.409620E+10 | 0.141364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.193270E+09 | 57670202.73 |
April | 0.395248E+10 | 0.136151E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.363068E+09 | 10672568.26 |
May | 0.408566E+10 | 0.141173E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.670953E+09 | 75018.82 |
June | 0.396110E+10 | 0.136775E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.732188E+09 | 5212.81 |
July | 0.407704E+10 | 0.140549E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.873835E+09 | 0.00 |
August | 0.409429E+10 | 0.141418E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.887298E+09 | 0.00 |
September | 0.395056E+10 | 0.136205E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.708729E+09 | 0.00 |
October | 0.407896E+10 | 0.140875E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.560682E+09 | 34016.20 |
November | 0.394385E+10 | 0.136667E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.306174E+09 | 12791364.07 |
December | 0.407704E+10 | 0.140549E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101719E+09 | 0.103366E+09 |
Annual Sum or Average | 0.480803E+11 | 0.165990E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.551982E+10 | 0.470268E+09 |
Minimum of Months | 0.368610E+10 | 0.127246E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40306775.86 | 0.00 |
Maximum of Months | 0.409620E+10 | 0.141418E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.887298E+09 | 0.177402E+09 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 11501.89 | 02-JAN-00:10 | 13517.00 | 02-JAN-20:10 | 10113.80 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 11501.89 | 01-FEB-00:10 | 13517.00 | 01-FEB-20:10 | 10113.80 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 11501.89 | 01-MAR-00:10 | 13517.00 | 01-MAR-20:10 | 10113.80 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 11501.89 | 01-APR-00:10 | 13517.00 | 03-APR-19:10 | 10113.80 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 11501.89 | 01-MAY-00:10 | 13517.00 | 01-MAY-19:10 | 10113.80 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 11501.89 | 01-JUN-00:10 | 13517.00 | 01-JUN-19:10 | 10113.80 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 11501.89 | 01-JUL-00:10 | 13517.00 | 03-JUL-19:10 | 10113.80 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 11501.89 | 01-AUG-00:10 | 13517.00 | 01-AUG-19:10 | 10113.80 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 11501.89 | 01-SEP-00:10 | 13517.00 | 01-SEP-19:10 | 10113.80 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 11501.89 | 01-OCT-23:10 | 13517.00 | 02-OCT-19:10 | 10113.80 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 11501.89 | 01-NOV-00:10 | 13517.00 | 01-NOV-19:10 | 10113.80 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 11501.89 | 01-DEC-00:10 | 13517.00 | 01-DEC-20:10 | 10113.80 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 11501.89 | 13517.00 | 10113.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 11501.89 | 13517.00 | 10113.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1169.53 | 02-JAN-00:10 | 687.30 | 02-JAN-20:10 | 685.60 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 140.31 | 23-JAN-14:00 | 199.18 | 09-JAN-08:00 |
February | 1169.53 | 01-FEB-00:10 | 687.30 | 01-FEB-20:10 | 685.60 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 220.44 | 06-FEB-15:00 | 176.71 | 01-FEB-05:50 |
March | 1169.53 | 01-MAR-00:10 | 687.30 | 01-MAR-20:10 | 685.60 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 338.74 | 27-MAR-11:00 | 153.09 | 08-MAR-06:00 |
April | 1169.53 | 01-APR-00:10 | 687.30 | 03-APR-19:10 | 685.60 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 408.03 | 28-APR-12:00 | 86.62 | 05-APR-05:30 |
May | 1169.53 | 01-MAY-00:10 | 687.30 | 01-MAY-19:10 | 685.60 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 407.57 | 31-MAY-19:00 | 12.93 | 01-MAY-06:00 |
June | 1169.53 | 01-JUN-00:10 | 687.30 | 01-JUN-19:10 | 685.60 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 424.38 | 12-JUN-12:00 | 0.09 | 22-JUN-08:00 |
July | 1169.53 | 01-JUL-00:10 | 687.30 | 03-JUL-19:10 | 685.60 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 469.49 | 21-JUL-12:00 | 0.00 | 01-JUL-00:10 |
August | 1169.53 | 01-AUG-00:10 | 687.30 | 01-AUG-19:10 | 685.60 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 467.34 | 16-AUG-12:00 | 0.00 | 01-AUG-00:10 |
September | 1169.53 | 01-SEP-00:10 | 687.30 | 01-SEP-19:10 | 685.60 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 378.91 | 05-SEP-12:00 | 0.00 | 01-SEP-00:10 |
October | 1169.53 | 01-OCT-23:10 | 687.30 | 02-OCT-19:10 | 685.60 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 322.21 | 04-OCT-12:00 | 8.67 | 29-OCT-07:00 |
November | 1169.53 | 01-NOV-00:10 | 687.30 | 01-NOV-19:10 | 685.60 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 245.00 | 05-NOV-12:00 | 89.18 | 22-NOV-07:00 |
December | 1169.53 | 01-DEC-00:10 | 687.30 | 01-DEC-20:10 | 685.60 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 184.82 | 10-DEC-12:00 | 176.84 | 18-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1169.53 | 687.30 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 140.31 | 0.00 | |||||
Maximum of Months | 1169.53 | 687.30 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 469.49 | 199.18 |
Report: PeakSpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1354.32 | 02-JAN-00:10 | 795.89 | 02-JAN-20:10 | 793.93 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.20 | 23-JAN-14:00 | 76.90 | 09-JAN-08:00 |
February | 1354.32 | 01-FEB-00:10 | 795.89 | 01-FEB-20:10 | 793.93 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 90.91 | 06-FEB-15:00 | 68.17 | 01-FEB-06:00 |
March | 1354.32 | 01-MAR-00:10 | 795.89 | 01-MAR-20:10 | 793.93 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 131.61 | 27-MAR-11:00 | 59.08 | 08-MAR-06:00 |
April | 1354.32 | 01-APR-00:10 | 795.89 | 03-APR-19:10 | 793.93 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 160.48 | 28-APR-12:00 | 33.42 | 05-APR-05:40 |
May | 1354.32 | 01-MAY-00:10 | 795.89 | 01-MAY-19:10 | 793.93 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 156.77 | 31-MAY-19:00 | 5.66 | 01-MAY-06:00 |
June | 1354.32 | 01-JUN-00:10 | 795.89 | 01-JUN-19:10 | 793.93 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 166.04 | 12-JUN-12:00 | 1.24 | 22-JUN-08:00 |
July | 1354.32 | 01-JUL-00:10 | 795.89 | 03-JUL-19:10 | 793.93 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 185.97 | 21-JUL-12:00 | 0.00 | 01-JUL-00:10 |
August | 1354.32 | 01-AUG-00:10 | 795.89 | 01-AUG-19:10 | 793.93 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 186.94 | 16-AUG-12:00 | 0.00 | 01-AUG-00:10 |
September | 1354.32 | 01-SEP-00:10 | 795.89 | 01-SEP-19:10 | 793.93 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 154.77 | 26-SEP-13:00 | 0.00 | 01-SEP-00:10 |
October | 1354.32 | 01-OCT-23:10 | 795.89 | 02-OCT-19:10 | 793.93 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 131.79 | 04-OCT-12:00 | 3.65 | 29-OCT-07:00 |
November | 1354.32 | 01-NOV-00:10 | 795.89 | 01-NOV-19:10 | 793.93 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 102.63 | 05-NOV-12:00 | 34.45 | 22-NOV-07:00 |
December | 1354.32 | 01-DEC-00:10 | 795.89 | 01-DEC-20:10 | 793.93 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 71.93 | 10-DEC-12:00 | 68.23 | 18-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1354.32 | 795.89 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 56.20 | 0.00 | |||||
Maximum of Months | 1354.32 | 795.89 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 186.94 | 76.90 |
Report: PeakSpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 286.42 | 02-JAN-00:10 | 1487.69 | 02-JAN-20:10 | 839.45 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 132.83 | 23-JAN-14:00 | 181.69 | 09-JAN-08:00 |
February | 286.42 | 01-FEB-00:10 | 1487.69 | 01-FEB-20:10 | 839.45 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 214.81 | 06-FEB-15:00 | 161.09 | 01-FEB-06:00 |
March | 286.42 | 01-MAR-00:10 | 1487.69 | 01-MAR-20:10 | 839.45 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 311.05 | 27-MAR-11:00 | 139.62 | 08-MAR-06:00 |
April | 286.42 | 01-APR-00:10 | 1487.69 | 03-APR-19:10 | 839.45 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 379.28 | 28-APR-12:00 | 78.99 | 01-APR-06:00 |
May | 286.42 | 01-MAY-00:10 | 1487.69 | 01-MAY-19:10 | 839.45 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 370.87 | 31-MAY-19:00 | 11.68 | 01-MAY-06:00 |
June | 286.42 | 01-JUN-00:10 | 1487.69 | 01-JUN-19:10 | 839.45 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 392.11 | 12-JUN-12:00 | 5.39 | 22-JUN-08:00 |
July | 286.42 | 01-JUL-00:10 | 1487.69 | 03-JUL-19:10 | 839.45 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 435.91 | 21-JUL-12:00 | 0.00 | 01-JUL-00:10 |
August | 286.42 | 01-AUG-00:10 | 1487.69 | 01-AUG-19:10 | 839.45 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 438.69 | 16-AUG-12:00 | 0.00 | 01-AUG-00:10 |
September | 286.42 | 01-SEP-00:10 | 1487.69 | 01-SEP-19:10 | 839.45 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 365.79 | 26-SEP-13:00 | 0.00 | 01-SEP-00:10 |
October | 286.42 | 01-OCT-23:10 | 1487.69 | 02-OCT-19:10 | 839.45 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 311.42 | 04-OCT-12:00 | 7.86 | 29-OCT-07:00 |
November | 286.42 | 01-NOV-00:10 | 1487.69 | 01-NOV-19:10 | 839.45 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 242.55 | 05-NOV-12:00 | 81.42 | 22-NOV-07:00 |
December | 286.42 | 01-DEC-00:10 | 1487.69 | 01-DEC-20:10 | 839.45 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 169.97 | 10-DEC-12:00 | 161.24 | 18-DEC-05:30 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 286.42 | 1487.69 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 132.83 | 0.00 | |||||
Maximum of Months | 286.42 | 1487.69 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 438.69 | 181.69 |
Report: PeakSpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 220.32 | 02-JAN-00:10 | 273.10 | 02-JAN-20:10 | 242.16 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 76.66 | 23-JAN-14:00 | 104.82 | 09-JAN-08:00 |
February | 220.32 | 01-FEB-00:10 | 273.10 | 01-FEB-20:10 | 242.16 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 123.96 | 06-FEB-15:00 | 92.96 | 01-FEB-06:00 |
March | 220.32 | 01-MAR-00:10 | 273.10 | 01-MAR-20:10 | 242.16 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 179.46 | 27-MAR-11:00 | 80.54 | 08-MAR-06:00 |
April | 220.32 | 01-APR-00:10 | 273.10 | 03-APR-19:10 | 242.16 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 218.82 | 28-APR-12:00 | 45.55 | 05-APR-06:00 |
May | 220.32 | 01-MAY-00:10 | 273.10 | 01-MAY-19:10 | 242.16 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 216.25 | 31-MAY-19:00 | 6.75 | 01-MAY-06:00 |
June | 220.32 | 01-JUN-00:10 | 273.10 | 01-JUN-19:10 | 242.16 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 225.63 | 12-JUN-12:00 | 1.54 | 22-JUN-08:00 |
July | 220.32 | 01-JUL-00:10 | 273.10 | 03-JUL-19:10 | 242.16 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 250.76 | 21-JUL-12:00 | 0.00 | 01-JUL-00:10 |
August | 220.32 | 01-AUG-00:10 | 273.10 | 01-AUG-19:10 | 242.16 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 252.43 | 16-AUG-12:00 | 0.00 | 01-AUG-00:10 |
September | 220.32 | 01-SEP-00:10 | 273.10 | 01-SEP-19:10 | 242.16 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 211.05 | 26-SEP-13:00 | 0.00 | 01-SEP-00:10 |
October | 220.32 | 01-OCT-23:10 | 273.10 | 02-OCT-19:10 | 242.16 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 179.67 | 04-OCT-12:00 | 4.54 | 29-OCT-07:00 |
November | 220.32 | 01-NOV-00:10 | 273.10 | 01-NOV-19:10 | 242.16 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 139.95 | 05-NOV-12:00 | 46.97 | 22-NOV-07:00 |
December | 220.32 | 01-DEC-00:10 | 273.10 | 01-DEC-20:10 | 242.16 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 98.06 | 10-DEC-12:00 | 93.03 | 18-DEC-05:20 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 220.32 | 273.10 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 76.66 | 0.00 | |||||
Maximum of Months | 220.32 | 273.10 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 252.43 | 104.82 |
Report: PeakSpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 907.20 | 02-JAN-00:10 | 337.37 | 02-JAN-20:10 | 4572.80 | 02-JAN-20:10 | 39726.58 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 181.14 | 23-JAN-14:00 | 260.31 | 19-JAN-08:00 |
February | 907.20 | 01-FEB-00:10 | 337.37 | 01-FEB-20:10 | 4572.80 | 01-FEB-20:10 | 39726.58 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 292.95 | 06-FEB-15:00 | 221.33 | 01-FEB-07:10 |
March | 907.20 | 01-MAR-00:10 | 337.37 | 01-MAR-20:10 | 4572.80 | 01-MAR-20:10 | 39726.58 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 425.95 | 27-MAR-11:00 | 191.12 | 08-MAR-06:00 |
April | 907.20 | 01-APR-00:10 | 337.37 | 03-APR-19:10 | 4572.80 | 03-APR-19:10 | 39726.58 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 518.21 | 28-APR-12:00 | 119.61 | 05-APR-07:00 |
May | 907.20 | 01-MAY-00:10 | 337.37 | 01-MAY-19:10 | 4572.80 | 01-MAY-19:10 | 39726.58 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 495.03 | 09-MAY-13:00 | 25.74 | 01-MAY-06:10 |
June | 907.20 | 01-JUN-00:10 | 337.37 | 01-JUN-19:10 | 4572.80 | 01-JUN-19:10 | 39726.58 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 535.89 | 12-JUN-12:00 | 3.23 | 22-JUN-08:00 |
July | 907.20 | 01-JUL-00:10 | 337.37 | 03-JUL-19:10 | 4572.80 | 03-JUL-19:10 | 39726.58 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 600.65 | 21-JUL-12:00 | 0.00 | 01-JUL-00:10 |
August | 907.20 | 01-AUG-00:10 | 337.37 | 01-AUG-19:10 | 4572.80 | 01-AUG-19:10 | 39726.58 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 603.59 | 16-AUG-12:00 | 0.00 | 01-AUG-00:10 |
September | 907.20 | 01-SEP-00:10 | 337.37 | 01-SEP-19:10 | 4572.80 | 01-SEP-19:10 | 39726.58 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 499.67 | 26-SEP-13:00 | 0.00 | 01-SEP-00:10 |
October | 907.20 | 01-OCT-23:10 | 337.37 | 02-OCT-19:10 | 4572.80 | 02-OCT-19:10 | 39726.58 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 425.27 | 04-OCT-12:00 | 10.63 | 29-OCT-07:00 |
November | 907.20 | 01-NOV-00:10 | 337.37 | 01-NOV-19:10 | 4572.80 | 01-NOV-19:10 | 39726.58 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 331.05 | 05-NOV-12:00 | 116.28 | 22-NOV-07:10 |
December | 907.20 | 01-DEC-00:10 | 337.37 | 01-DEC-20:10 | 4572.80 | 01-DEC-20:10 | 39726.58 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 232.07 | 10-DEC-12:00 | 220.10 | 18-DEC-05:40 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 907.20 | 337.37 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 181.14 | 0.00 | ||||||
Maximum of Months | 907.20 | 337.37 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 603.59 | 260.31 |
Report: PeakSpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 15368.40 | 02-JAN-00:10 | 2177.23 | 02-JAN-20:10 | 965.27 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 321.61 | 23-JAN-14:00 | 440.54 | 09-JAN-08:00 |
February | 15368.40 | 01-FEB-00:10 | 2177.23 | 01-FEB-20:10 | 965.27 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 508.75 | 06-FEB-15:00 | 390.60 | 01-FEB-05:30 |
March | 15368.40 | 01-MAR-00:10 | 2177.23 | 01-MAR-20:10 | 965.27 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 753.64 | 27-MAR-11:00 | 338.53 | 08-MAR-06:00 |
April | 15368.40 | 01-APR-00:10 | 2177.23 | 03-APR-19:10 | 965.27 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 918.83 | 28-APR-12:00 | 191.71 | 05-APR-06:00 |
May | 15368.40 | 01-MAY-00:10 | 2177.23 | 01-MAY-19:10 | 965.27 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 898.13 | 31-MAY-19:00 | 28.41 | 01-MAY-06:00 |
June | 15368.40 | 01-JUN-00:10 | 2177.23 | 01-JUN-19:10 | 965.27 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 950.72 | 12-JUN-12:00 | 0.17 | 22-JUN-08:00 |
July | 15368.40 | 01-JUL-00:10 | 2177.23 | 03-JUL-19:10 | 965.27 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1065.01 | 21-JUL-12:00 | 0.00 | 01-JUL-00:10 |
August | 15368.40 | 01-AUG-00:10 | 2177.23 | 01-AUG-19:10 | 965.27 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1066.00 | 16-AUG-12:00 | 0.00 | 01-AUG-00:10 |
September | 15368.40 | 01-SEP-00:10 | 2177.23 | 01-SEP-19:10 | 965.27 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 868.69 | 05-SEP-12:00 | 0.00 | 01-SEP-00:10 |
October | 15368.40 | 01-OCT-23:10 | 2177.23 | 02-OCT-19:10 | 965.27 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 739.71 | 04-OCT-12:00 | 19.08 | 29-OCT-07:00 |
November | 15368.40 | 01-NOV-00:10 | 2177.23 | 01-NOV-19:10 | 965.27 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 556.69 | 05-NOV-12:00 | 197.23 | 22-NOV-07:00 |
December | 15368.40 | 01-DEC-00:10 | 2177.23 | 01-DEC-20:10 | 965.27 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 411.83 | 10-DEC-12:00 | 390.87 | 18-DEC-05:30 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 15368.40 | 2177.23 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 321.61 | 0.00 | |||||
Maximum of Months | 15368.40 | 2177.23 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 1066.00 | 440.54 |
Report: PeakSpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 45622.98 | 02-JAN-00:10 | 11849.32 | 02-JAN-20:10 | 10029.21 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 920.05 | 23-JAN-14:00 | 1261.50 | 20-JAN-06:00 |
February | 45622.98 | 01-FEB-00:10 | 11849.32 | 01-FEB-20:10 | 10029.21 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1487.03 | 06-FEB-15:00 | 1133.10 | 01-FEB-05:40 |
March | 45622.98 | 01-MAR-00:10 | 11849.32 | 01-MAR-20:10 | 10029.21 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2153.69 | 27-MAR-11:00 | 987.19 | 08-MAR-06:00 |
April | 45622.98 | 01-APR-00:10 | 11849.32 | 03-APR-19:10 | 10029.21 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2626.12 | 28-APR-12:00 | 591.50 | 05-APR-05:00 |
May | 45622.98 | 01-MAY-00:10 | 11849.32 | 01-MAY-19:10 | 10029.21 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2553.51 | 31-MAY-19:00 | 131.39 | 01-MAY-06:00 |
June | 45622.98 | 01-JUN-00:10 | 11849.32 | 01-JUN-19:10 | 10029.21 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2717.19 | 12-JUN-12:00 | 24.01 | 22-JUN-08:00 |
July | 45622.98 | 01-JUL-00:10 | 11849.32 | 03-JUL-19:10 | 10029.21 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3042.62 | 21-JUL-12:00 | 0.00 | 01-JUL-00:10 |
August | 45622.98 | 01-AUG-00:10 | 11849.32 | 01-AUG-19:10 | 10029.21 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3058.38 | 16-AUG-12:00 | 0.00 | 01-AUG-00:10 |
September | 45622.98 | 01-SEP-00:10 | 11849.32 | 01-SEP-19:10 | 10029.21 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2532.51 | 26-SEP-13:00 | 0.00 | 01-SEP-00:10 |
October | 45622.98 | 01-OCT-23:10 | 11849.32 | 02-OCT-19:10 | 10029.21 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2156.30 | 04-OCT-12:00 | 102.05 | 29-OCT-07:00 |
November | 45622.98 | 01-NOV-00:10 | 11849.32 | 01-NOV-19:10 | 10029.21 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1679.23 | 05-NOV-12:00 | 597.66 | 22-NOV-05:40 |
December | 45622.98 | 01-DEC-00:10 | 11849.32 | 01-DEC-20:10 | 10029.21 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1177.01 | 10-DEC-12:00 | 1122.07 | 18-DEC-05:40 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 45622.98 | 11849.32 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 920.05 | 0.00 | |||||
Maximum of Months | 45622.98 | 11849.32 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 3058.38 | 1261.50 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 392.73 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 59.01 | 29-JAN-11:00 | 117.57 | 09-JAN-08:00 |
February | 180.00 | 01-FEB-00:10 | 392.73 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 127.27 | 05-FEB-16:08 | 104.45 | 01-FEB-06:00 |
March | 180.00 | 01-MAR-00:10 | 392.73 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 170.24 | 27-MAR-11:00 | 90.76 | 08-MAR-06:00 |
April | 180.00 | 01-APR-00:10 | 392.73 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 214.00 | 28-APR-12:00 | 52.17 | 01-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 392.73 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 239.06 | 31-MAY-19:00 | 15.49 | 01-MAY-07:50 |
June | 180.00 | 01-JUN-00:10 | 392.73 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 235.57 | 09-JUN-15:10 | 29.00 | 22-JUN-08:00 |
July | 180.00 | 01-JUL-00:10 | 392.73 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 253.03 | 21-JUL-12:00 | 0.00 | 01-JUL-00:10 |
August | 180.00 | 01-AUG-00:10 | 392.73 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 254.36 | 16-AUG-12:00 | 0.00 | 01-AUG-00:10 |
September | 180.00 | 01-SEP-00:10 | 392.73 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 226.82 | 04-SEP-15:10 | 0.00 | 01-SEP-00:10 |
October | 180.00 | 01-OCT-00:10 | 392.73 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 184.59 | 09-OCT-15:10 | 15.47 | 29-OCT-07:10 |
November | 180.00 | 01-NOV-00:10 | 392.73 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 141.22 | 06-NOV-11:00 | 53.74 | 22-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 392.73 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 94.70 | 10-DEC-11:00 | 104.53 | 18-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 392.73 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 59.01 | 0.00 | |||||
Maximum of Months | 180.00 | 392.73 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 254.36 | 117.57 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 392.68 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 59.00 | 29-JAN-11:00 | 117.56 | 09-JAN-08:00 |
February | 180.00 | 01-FEB-00:10 | 392.68 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 127.27 | 05-FEB-16:10 | 104.44 | 01-FEB-06:00 |
March | 180.00 | 01-MAR-00:10 | 392.68 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 170.23 | 27-MAR-11:00 | 90.75 | 08-MAR-06:00 |
April | 180.00 | 01-APR-00:10 | 392.68 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 213.98 | 28-APR-12:00 | 52.16 | 01-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 392.68 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 239.05 | 31-MAY-19:00 | 15.88 | 01-MAY-07:50 |
June | 180.00 | 01-JUN-00:10 | 392.68 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 235.55 | 09-JUN-15:10 | 28.99 | 22-JUN-08:00 |
July | 180.00 | 01-JUL-00:10 | 392.68 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 253.01 | 21-JUL-12:00 | 0.00 | 01-JUL-00:10 |
August | 180.00 | 01-AUG-00:10 | 392.68 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 254.34 | 16-AUG-12:00 | 0.00 | 01-AUG-00:10 |
September | 180.00 | 01-SEP-00:10 | 392.68 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 226.81 | 04-SEP-15:10 | 0.00 | 01-SEP-00:10 |
October | 180.00 | 01-OCT-00:10 | 392.68 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 184.58 | 09-OCT-15:10 | 13.86 | 29-OCT-07:10 |
November | 180.00 | 01-NOV-00:10 | 392.68 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 141.21 | 06-NOV-11:00 | 53.73 | 22-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 392.68 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 94.69 | 10-DEC-11:00 | 104.52 | 18-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 392.68 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 59.00 | 0.00 | |||||
Maximum of Months | 180.00 | 392.68 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 254.34 | 117.56 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 01-JAN-00:10 | 246.81 | 01-JAN-19:10 | 232.19 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 15.58 | 23-JAN-14:00 | 40.76 | 09-JAN-08:00 |
February | 0.00 | 01-FEB-00:10 | 246.81 | 01-FEB-20:10 | 232.19 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.26 | 06-FEB-15:00 | 36.97 | 14-FEB-06:40 |
March | 0.00 | 01-MAR-00:10 | 246.81 | 01-MAR-20:10 | 232.19 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 47.50 | 27-MAR-11:00 | 32.73 | 07-MAR-06:20 |
April | 0.00 | 01-APR-00:10 | 246.81 | 01-APR-18:10 | 232.19 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 59.71 | 28-APR-12:00 | 21.99 | 05-APR-05:00 |
May | 0.00 | 01-MAY-00:10 | 246.81 | 01-MAY-19:10 | 232.19 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 59.62 | 31-MAY-19:00 | 10.25 | 01-MAY-06:00 |
June | 0.00 | 01-JUN-00:10 | 246.81 | 01-JUN-19:10 | 232.19 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 62.14 | 12-JUN-12:00 | 8.09 | 22-JUN-08:00 |
July | 0.00 | 01-JUL-00:10 | 246.81 | 01-JUL-18:10 | 232.19 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 70.60 | 21-JUL-12:00 | 0.00 | 01-JUL-00:10 |
August | 0.00 | 01-AUG-00:10 | 246.81 | 01-AUG-19:10 | 232.19 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 70.97 | 16-AUG-12:00 | 0.00 | 01-AUG-00:10 |
September | 0.00 | 01-SEP-00:10 | 246.81 | 01-SEP-19:10 | 232.19 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 57.29 | 26-SEP-13:00 | 1.29 | 25-SEP-05:05 |
October | 0.00 | 01-OCT-00:10 | 246.81 | 01-OCT-18:10 | 232.19 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 47.56 | 04-OCT-12:00 | 9.63 | 29-OCT-07:00 |
November | 0.00 | 01-NOV-00:10 | 246.81 | 01-NOV-19:10 | 232.19 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.19 | 05-NOV-12:00 | 22.44 | 22-NOV-05:50 |
December | 0.00 | 01-DEC-00:10 | 246.81 | 01-DEC-20:10 | 232.19 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.21 | 10-DEC-12:00 | 36.54 | 31-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 0.00 | 246.81 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 15.58 | 0.00 | |||||
Maximum of Months | 0.00 | 246.81 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 70.97 | 40.76 |
Report: PeakSpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 246.88 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 18.06 | 28-JAN-14:00 | 33.71 | 09-JAN-08:10 |
February | 180.00 | 01-FEB-00:10 | 246.88 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.52 | 05-FEB-16:08 | 29.15 | 01-FEB-06:00 |
March | 180.00 | 01-MAR-00:10 | 246.88 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 47.88 | 27-MAR-11:00 | 25.33 | 08-MAR-06:00 |
April | 180.00 | 01-APR-00:10 | 246.88 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 59.73 | 28-APR-12:00 | 14.92 | 01-APR-07:20 |
May | 180.00 | 01-MAY-00:10 | 246.88 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 66.72 | 31-MAY-19:00 | 3.60 | 01-MAY-07:10 |
June | 180.00 | 01-JUN-00:10 | 246.88 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 65.75 | 09-JUN-15:10 | 7.68 | 22-JUN-08:00 |
July | 180.00 | 01-JUL-00:10 | 246.88 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 70.62 | 21-JUL-12:00 | 0.00 | 01-JUL-00:10 |
August | 180.00 | 01-AUG-00:10 | 246.88 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 70.99 | 16-AUG-12:00 | 0.00 | 01-AUG-00:10 |
September | 180.00 | 01-SEP-00:10 | 246.88 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 63.31 | 04-SEP-15:10 | 0.00 | 01-SEP-00:10 |
October | 180.00 | 01-OCT-00:10 | 246.88 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.52 | 09-OCT-15:10 | 3.86 | 29-OCT-07:10 |
November | 180.00 | 01-NOV-00:10 | 246.88 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.41 | 06-NOV-11:00 | 15.00 | 22-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 246.88 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.43 | 10-DEC-11:00 | 29.17 | 18-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 246.88 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 18.06 | 0.00 | |||||
Maximum of Months | 180.00 | 246.88 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 70.99 | 33.71 |
Report: PeakSpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 392.73 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 59.01 | 29-JAN-11:00 | 119.13 | 19-JAN-08:20 |
February | 180.00 | 01-FEB-00:10 | 392.73 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 127.28 | 05-FEB-16:10 | 104.45 | 01-FEB-06:00 |
March | 180.00 | 01-MAR-00:10 | 392.73 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 170.24 | 27-MAR-11:00 | 90.76 | 08-MAR-06:00 |
April | 180.00 | 01-APR-00:10 | 392.73 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 214.01 | 28-APR-12:00 | 52.94 | 01-APR-07:20 |
May | 180.00 | 01-MAY-00:10 | 392.73 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 239.07 | 31-MAY-19:00 | 21.05 | 01-MAY-07:40 |
June | 180.00 | 01-JUN-00:10 | 392.73 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 235.58 | 09-JUN-15:10 | 29.00 | 22-JUN-08:00 |
July | 180.00 | 01-JUL-00:10 | 392.73 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 253.04 | 21-JUL-12:00 | 0.00 | 01-JUL-00:10 |
August | 180.00 | 01-AUG-00:10 | 392.73 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 254.37 | 16-AUG-12:00 | 0.00 | 01-AUG-00:10 |
September | 180.00 | 01-SEP-00:10 | 392.73 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 226.83 | 04-SEP-15:10 | 0.00 | 01-SEP-00:10 |
October | 180.00 | 01-OCT-00:10 | 392.73 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 184.59 | 09-OCT-15:10 | 19.48 | 29-OCT-07:20 |
November | 180.00 | 01-NOV-00:10 | 392.73 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 141.22 | 06-NOV-11:00 | 53.74 | 22-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 392.73 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 94.69 | 10-DEC-11:00 | 104.53 | 18-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 392.73 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 59.01 | 0.00 | |||||
Maximum of Months | 180.00 | 392.73 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 254.37 | 119.13 |
Report: PeakSpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 392.68 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 59.01 | 29-JAN-11:00 | 117.56 | 09-JAN-08:00 |
February | 180.00 | 01-FEB-00:10 | 392.68 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 127.27 | 05-FEB-16:08 | 104.44 | 01-FEB-06:00 |
March | 180.00 | 01-MAR-00:10 | 392.68 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 170.22 | 27-MAR-11:00 | 90.75 | 08-MAR-06:00 |
April | 180.00 | 01-APR-00:10 | 392.68 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 213.99 | 28-APR-12:00 | 52.30 | 01-APR-07:20 |
May | 180.00 | 01-MAY-00:10 | 392.68 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 239.05 | 31-MAY-19:00 | 21.05 | 01-MAY-07:40 |
June | 180.00 | 01-JUN-00:10 | 392.68 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 235.56 | 09-JUN-15:10 | 29.00 | 22-JUN-08:00 |
July | 180.00 | 01-JUL-00:10 | 392.68 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 253.02 | 21-JUL-12:00 | 0.00 | 01-JUL-00:10 |
August | 180.00 | 01-AUG-00:10 | 392.68 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 254.35 | 16-AUG-12:00 | 0.00 | 01-AUG-00:10 |
September | 180.00 | 01-SEP-00:10 | 392.68 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 226.82 | 04-SEP-15:10 | 0.00 | 01-SEP-00:10 |
October | 180.00 | 01-OCT-00:10 | 392.68 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 184.57 | 09-OCT-15:10 | 17.64 | 29-OCT-07:10 |
November | 180.00 | 01-NOV-00:10 | 392.68 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 141.21 | 06-NOV-11:00 | 53.73 | 22-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 392.68 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 94.69 | 10-DEC-11:00 | 104.52 | 18-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 392.68 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 59.01 | 0.00 | |||||
Maximum of Months | 180.00 | 392.68 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 254.35 | 117.56 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2263.36 | 02-JAN-00:10 | 1282.60 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.58 | 23-JAN-14:00 | 140.44 | 09-JAN-08:00 |
February | 2263.36 | 01-FEB-00:10 | 1282.60 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 160.92 | 06-FEB-15:00 | 124.60 | 01-FEB-06:00 |
March | 2263.36 | 01-MAR-00:10 | 1282.60 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 237.51 | 27-MAR-11:00 | 108.04 | 08-MAR-06:00 |
April | 2263.36 | 01-APR-00:10 | 1282.60 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 283.65 | 28-APR-12:00 | 62.41 | 05-APR-05:00 |
May | 2263.36 | 01-MAY-00:10 | 1282.60 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 275.80 | 31-MAY-19:00 | 16.85 | 01-MAY-06:00 |
June | 2263.36 | 01-JUN-00:10 | 1282.60 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 288.11 | 12-JUN-12:00 | 13.54 | 22-JUN-08:00 |
July | 2263.36 | 01-JUL-00:10 | 1282.60 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 321.55 | 21-JUL-12:00 | 0.00 | 01-JUL-00:10 |
August | 2263.36 | 01-AUG-00:10 | 1282.60 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 322.67 | 16-AUG-12:00 | 0.00 | 01-AUG-00:10 |
September | 2263.36 | 01-SEP-00:10 | 1282.60 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 267.57 | 26-SEP-13:00 | 0.00 | 01-SEP-00:10 |
October | 2263.36 | 01-OCT-23:10 | 1282.60 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 227.12 | 04-OCT-12:00 | 13.56 | 29-OCT-07:00 |
November | 2263.36 | 01-NOV-00:10 | 1282.60 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 177.61 | 05-NOV-12:00 | 63.95 | 22-NOV-07:00 |
December | 2263.36 | 01-DEC-00:10 | 1282.60 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 129.94 | 10-DEC-12:00 | 124.70 | 18-DEC-05:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 2263.36 | 1282.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.58 | 0.00 | ||||
Maximum of Months | 2263.36 | 1282.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 322.67 | 140.44 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 392.73 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 58.30 | 29-JAN-11:00 | 118.35 | 09-JAN-08:00 |
February | 180.00 | 01-FEB-00:10 | 392.73 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 126.59 | 05-FEB-16:10 | 105.23 | 01-FEB-06:00 |
March | 180.00 | 01-MAR-00:10 | 392.73 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 169.58 | 27-MAR-11:00 | 91.53 | 08-MAR-06:00 |
April | 180.00 | 01-APR-00:10 | 392.73 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 213.36 | 28-APR-12:00 | 52.92 | 01-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 392.73 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 238.43 | 31-MAY-19:00 | 16.23 | 01-MAY-07:50 |
June | 180.00 | 01-JUN-00:10 | 392.73 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 234.94 | 09-JUN-15:10 | 29.73 | 22-JUN-08:00 |
July | 180.00 | 01-JUL-00:10 | 392.73 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 252.42 | 21-JUL-12:00 | 0.00 | 01-JUL-00:10 |
August | 180.00 | 01-AUG-00:10 | 392.73 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 253.75 | 16-AUG-12:00 | 0.00 | 01-AUG-00:10 |
September | 180.00 | 01-SEP-00:10 | 392.73 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 226.19 | 04-SEP-15:10 | 0.00 | 01-SEP-00:10 |
October | 180.00 | 01-OCT-00:10 | 392.73 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 183.91 | 09-OCT-15:10 | 15.47 | 29-OCT-07:10 |
November | 180.00 | 01-NOV-00:10 | 392.73 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 140.54 | 06-NOV-11:00 | 54.50 | 22-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 392.73 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 94.00 | 10-DEC-11:00 | 105.31 | 18-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 392.73 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 58.30 | 0.00 | |||||
Maximum of Months | 180.00 | 392.73 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 253.75 | 118.35 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 392.68 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 58.29 | 29-JAN-11:00 | 118.34 | 09-JAN-08:00 |
February | 180.00 | 01-FEB-00:10 | 392.68 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 126.59 | 05-FEB-16:10 | 105.22 | 01-FEB-06:00 |
March | 180.00 | 01-MAR-00:10 | 392.68 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 169.57 | 27-MAR-11:00 | 91.52 | 08-MAR-06:00 |
April | 180.00 | 01-APR-00:10 | 392.68 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 213.35 | 28-APR-12:00 | 52.92 | 01-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 392.68 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 238.41 | 31-MAY-19:00 | 16.75 | 01-MAY-07:50 |
June | 180.00 | 01-JUN-00:10 | 392.68 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 234.92 | 09-JUN-15:10 | 29.72 | 22-JUN-08:00 |
July | 180.00 | 01-JUL-00:10 | 392.68 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 252.41 | 21-JUL-12:00 | 0.00 | 01-JUL-00:10 |
August | 180.00 | 01-AUG-00:10 | 392.68 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 253.73 | 16-AUG-12:00 | 0.00 | 01-AUG-00:10 |
September | 180.00 | 01-SEP-00:10 | 392.68 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 226.17 | 04-SEP-15:10 | 0.00 | 01-SEP-00:10 |
October | 180.00 | 01-OCT-00:10 | 392.68 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 183.91 | 09-OCT-15:10 | 13.90 | 29-OCT-07:10 |
November | 180.00 | 01-NOV-00:10 | 392.68 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 140.52 | 06-NOV-11:00 | 54.49 | 22-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 392.68 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 93.99 | 10-DEC-11:00 | 105.30 | 18-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 392.68 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 58.29 | 0.00 | |||||
Maximum of Months | 180.00 | 392.68 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 253.73 | 118.34 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 246.88 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 29.83 | 29-JAN-11:00 | 61.40 | 19-JAN-08:20 |
February | 180.00 | 01-FEB-00:10 | 246.88 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 64.77 | 05-FEB-16:10 | 53.84 | 01-FEB-06:00 |
March | 180.00 | 01-MAR-00:10 | 246.88 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 86.77 | 27-MAR-11:00 | 46.83 | 08-MAR-06:00 |
April | 180.00 | 01-APR-00:10 | 246.88 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 109.16 | 28-APR-12:00 | 27.08 | 01-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 246.88 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 121.99 | 31-MAY-19:00 | 7.66 | 01-MAY-07:10 |
June | 180.00 | 01-JUN-00:10 | 246.88 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 120.21 | 09-JUN-15:10 | 15.21 | 22-JUN-08:00 |
July | 180.00 | 01-JUL-00:10 | 246.88 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 129.15 | 21-JUL-12:00 | 0.00 | 01-JUL-00:10 |
August | 180.00 | 01-AUG-00:10 | 246.88 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 129.83 | 16-AUG-12:00 | 0.00 | 01-AUG-00:10 |
September | 180.00 | 01-SEP-00:10 | 246.88 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 115.68 | 04-SEP-15:10 | 0.00 | 01-SEP-00:10 |
October | 180.00 | 01-OCT-00:10 | 246.88 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 93.76 | 09-OCT-15:10 | 9.49 | 29-OCT-07:10 |
November | 180.00 | 01-NOV-00:10 | 246.88 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 71.90 | 06-NOV-11:00 | 27.88 | 22-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 246.88 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.09 | 10-DEC-11:00 | 53.88 | 18-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 246.88 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 29.83 | 0.00 | |||||
Maximum of Months | 180.00 | 246.88 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 129.83 | 61.40 |
Report: PeakSpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 3823.39 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 203.35 | 23-JAN-14:00 | 305.14 | 20-JAN-05:30 |
February | 26988.77 | 01-FEB-00:10 | 3823.39 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 330.90 | 06-FEB-15:00 | 275.33 | 14-FEB-06:00 |
March | 26988.77 | 01-MAR-00:10 | 3823.39 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 480.38 | 27-MAR-11:00 | 243.25 | 08-MAR-06:00 |
April | 26988.77 | 01-APR-00:10 | 3823.39 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 586.36 | 28-APR-12:00 | 154.30 | 05-APR-05:00 |
May | 26988.77 | 01-MAY-00:10 | 3823.39 | 01-MAY-19:10 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 558.68 | 09-MAY-12:00 | 54.26 | 01-MAY-06:00 |
June | 26988.77 | 01-JUN-00:10 | 3823.39 | 01-JUN-19:10 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 604.63 | 12-JUN-12:00 | 27.52 | 22-JUN-08:00 |
July | 26988.77 | 01-JUL-00:10 | 3823.39 | 03-JUL-19:10 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 674.87 | 21-JUL-12:00 | 0.00 | 01-JUL-00:10 |
August | 26988.77 | 01-AUG-00:10 | 3823.39 | 01-AUG-19:10 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 680.45 | 16-AUG-12:00 | 0.00 | 01-AUG-00:10 |
September | 26988.77 | 01-SEP-00:10 | 3823.39 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 561.56 | 26-SEP-13:00 | 0.00 | 01-SEP-00:10 |
October | 26988.77 | 01-OCT-23:10 | 3823.39 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 481.04 | 04-OCT-12:00 | 48.02 | 29-OCT-07:00 |
November | 26988.77 | 01-NOV-00:10 | 3823.39 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 370.92 | 05-NOV-12:00 | 154.30 | 22-NOV-07:00 |
December | 26988.77 | 01-DEC-00:10 | 3823.39 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 260.85 | 10-DEC-12:00 | 273.90 | 18-DEC-05:30 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26988.77 | 3823.39 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 203.35 | 0.00 | |||||
Maximum of Months | 26988.77 | 3823.39 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 680.45 | 305.14 |
Report: PeakSpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 3823.39 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 203.29 | 23-JAN-14:00 | 305.98 | 20-JAN-05:30 |
February | 26988.77 | 01-FEB-00:10 | 3823.39 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 329.35 | 06-FEB-15:00 | 276.20 | 01-FEB-05:30 |
March | 26988.77 | 01-MAR-00:10 | 3823.39 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 480.38 | 27-MAR-11:00 | 244.21 | 08-MAR-06:00 |
April | 26988.77 | 01-APR-00:10 | 3823.39 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 583.99 | 28-APR-12:00 | 155.29 | 05-APR-05:00 |
May | 26988.77 | 01-MAY-00:10 | 3823.39 | 01-MAY-19:10 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 556.49 | 09-MAY-12:00 | 55.99 | 01-MAY-06:00 |
June | 26988.77 | 01-JUN-00:10 | 3823.39 | 01-JUN-19:10 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 601.87 | 12-JUN-12:00 | 30.68 | 22-JUN-08:00 |
July | 26988.77 | 01-JUL-00:10 | 3823.39 | 03-JUL-19:10 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 672.90 | 21-JUL-12:00 | 0.00 | 01-JUL-00:10 |
August | 26988.77 | 01-AUG-00:10 | 3823.39 | 01-AUG-19:10 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 678.22 | 16-AUG-12:00 | 0.00 | 01-AUG-00:10 |
September | 26988.77 | 01-SEP-00:10 | 3823.39 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 560.46 | 26-SEP-12:00 | 0.00 | 01-SEP-00:10 |
October | 26988.77 | 01-OCT-23:10 | 3823.39 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 479.57 | 04-OCT-12:00 | 50.11 | 29-OCT-07:00 |
November | 26988.77 | 01-NOV-00:10 | 3823.39 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 367.39 | 05-NOV-12:10 | 155.93 | 22-NOV-07:00 |
December | 26988.77 | 01-DEC-00:10 | 3823.39 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 258.21 | 10-DEC-12:00 | 274.63 | 18-DEC-05:30 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26988.77 | 3823.39 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 203.29 | 0.00 | |||||
Maximum of Months | 26988.77 | 3823.39 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 678.22 | 305.98 |
Report: PeakSpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2401.70 | 02-JAN-00:10 | 1020.78 | 02-JAN-20:10 | 15112.11 | 01-JAN-07:10 | 22492.83 | 01-JAN-16:10 | 0.00 | 0.00 | 0.00 | 109.50 | 23-JAN-14:00 | 303.37 | 20-JAN-07:20 |
February | 2401.70 | 01-FEB-00:10 | 1020.78 | 01-FEB-20:10 | 15112.11 | 01-FEB-07:10 | 22492.83 | 01-FEB-16:10 | 0.00 | 0.00 | 0.00 | 228.63 | 06-FEB-15:00 | 270.97 | 14-FEB-07:00 |
March | 2401.70 | 01-MAR-00:10 | 1020.78 | 01-MAR-20:10 | 15112.11 | 01-MAR-07:10 | 22492.83 | 01-MAR-16:10 | 0.00 | 0.00 | 0.00 | 353.97 | 27-MAR-11:00 | 234.80 | 07-MAR-07:10 |
April | 2401.70 | 01-APR-00:10 | 1020.78 | 03-APR-19:10 | 15112.11 | 01-APR-06:10 | 22492.83 | 01-APR-15:09 | 0.00 | 0.00 | 0.00 | 449.89 | 28-APR-12:00 | 156.39 | 05-APR-07:00 |
May | 2401.70 | 01-MAY-00:10 | 1020.78 | 01-MAY-19:10 | 15112.11 | 01-MAY-06:10 | 22492.83 | 01-MAY-15:09 | 0.00 | 0.00 | 0.00 | 449.38 | 31-MAY-19:00 | 61.12 | 01-MAY-06:30 |
June | 2401.70 | 01-JUN-00:10 | 1020.78 | 01-JUN-19:10 | 15112.11 | 01-JUN-06:10 | 22492.83 | 01-JUN-15:09 | 0.00 | 0.00 | 0.00 | 469.18 | 12-JUN-12:00 | 79.07 | 22-JUN-08:00 |
July | 2401.70 | 01-JUL-00:10 | 1020.78 | 03-JUL-19:10 | 15112.11 | 01-JUL-06:10 | 22492.83 | 01-JUL-15:09 | 0.00 | 0.00 | 0.00 | 535.72 | 21-JUL-12:00 | 0.00 | 01-JUL-00:10 |
August | 2401.70 | 01-AUG-00:10 | 1020.78 | 01-AUG-19:10 | 15112.11 | 01-AUG-06:10 | 22492.83 | 01-AUG-15:09 | 0.00 | 0.00 | 0.00 | 538.54 | 16-AUG-12:00 | 0.00 | 01-AUG-00:10 |
September | 2401.70 | 01-SEP-00:10 | 1020.78 | 01-SEP-19:10 | 15112.11 | 01-SEP-06:10 | 22492.83 | 01-SEP-15:09 | 0.00 | 0.00 | 0.00 | 430.86 | 26-SEP-13:00 | 0.00 | 01-SEP-00:10 |
October | 2401.70 | 01-OCT-23:10 | 1020.78 | 02-OCT-19:10 | 15112.11 | 01-OCT-06:10 | 22492.83 | 01-OCT-15:09 | 0.00 | 0.00 | 0.00 | 354.46 | 04-OCT-12:00 | 67.02 | 29-OCT-07:00 |
November | 2401.70 | 01-NOV-00:10 | 1020.78 | 01-NOV-19:10 | 15112.11 | 01-NOV-06:10 | 22492.83 | 01-NOV-15:09 | 0.00 | 0.00 | 0.00 | 257.17 | 05-NOV-12:00 | 147.94 | 22-NOV-07:00 |
December | 2401.70 | 01-DEC-00:10 | 1020.78 | 01-DEC-20:10 | 15112.11 | 01-DEC-07:10 | 22492.83 | 01-DEC-16:10 | 0.00 | 0.00 | 0.00 | 155.30 | 10-DEC-12:00 | 253.16 | 26-DEC-07:20 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 2401.70 | 1020.78 | 15112.11 | 22492.83 | 0.00 | 0.00 | 0.00 | 109.50 | 0.00 | ||||||
Maximum of Months | 2401.70 | 1020.78 | 15112.11 | 22492.83 | 0.00 | 0.00 | 0.00 | 538.54 | 303.37 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2395.44 | 02-JAN-00:10 | 1357.44 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 178.26 | 23-JAN-14:00 | 250.16 | 09-JAN-08:00 |
February | 2395.44 | 01-FEB-00:10 | 1357.44 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 283.53 | 06-FEB-15:00 | 222.14 | 01-FEB-05:50 |
March | 2395.44 | 01-MAR-00:10 | 1357.44 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 419.91 | 27-MAR-11:00 | 192.82 | 08-MAR-06:00 |
April | 2395.44 | 01-APR-00:10 | 1357.44 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 499.92 | 28-APR-12:00 | 110.26 | 01-APR-06:00 |
May | 2395.44 | 01-MAY-00:10 | 1357.44 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 495.40 | 31-MAY-19:00 | 18.68 | 01-MAY-06:00 |
June | 2395.44 | 01-JUN-00:10 | 1357.44 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 511.59 | 12-JUN-12:00 | 8.69 | 22-JUN-08:00 |
July | 2395.44 | 01-JUL-00:10 | 1357.44 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 565.52 | 21-JUL-12:00 | 0.00 | 01-JUL-00:10 |
August | 2395.44 | 01-AUG-00:10 | 1357.44 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 572.26 | 16-AUG-12:00 | 0.00 | 01-AUG-00:10 |
September | 2395.44 | 01-SEP-00:10 | 1357.44 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 476.50 | 26-SEP-12:00 | 0.00 | 01-SEP-00:10 |
October | 2395.44 | 01-OCT-23:10 | 1357.44 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 405.10 | 04-OCT-12:00 | 13.42 | 29-OCT-07:00 |
November | 2395.44 | 01-NOV-00:10 | 1357.44 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 319.14 | 05-NOV-12:00 | 113.64 | 22-NOV-07:00 |
December | 2395.44 | 01-DEC-00:10 | 1357.44 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 228.78 | 10-DEC-12:00 | 222.37 | 18-DEC-05:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 2395.44 | 1357.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 178.26 | 0.00 | ||||
Maximum of Months | 2395.44 | 1357.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 572.26 | 250.16 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 23602.19 | 23-JAN-19:10 | 53675.50 | 72090.20 | 57488.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 23802.06 | 08-FEB-19:10 | 53675.50 | 72090.20 | 57488.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 23982.69 | 01-MAR-19:20 | 17891.83 | 24030.07 | 19162.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 23645.97 | 27-APR-19:20 | 8945.92 | 13517.00 | 10113.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 24911.78 | 31-MAY-20:00 | 8945.92 | 13517.00 | 10113.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 25260.59 | 28-JUN-19:10 | 17891.83 | 27034.00 | 20227.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 26243.91 | 13-JUL-18:30 | 8945.92 | 12015.03 | 9581.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 27969.70 | 16-AUG-18:10 | 53675.50 | 72090.20 | 57488.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 27179.95 | 13-SEP-18:10 | 53675.50 | 72090.20 | 57488.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 27319.45 | 09-OCT-10:35 | 7667.93 | 9011.45 | 8516.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 26685.45 | 05-NOV-10:35 | 7667.93 | 9011.45 | 8516.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 25082.13 | 03-DEC-11:35 | 7667.93 | 9011.45 | 8516.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 23602.19 | 7667.93 | 9011.45 | 8516.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 27969.70 | 53675.50 | 72090.20 | 57488.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3343.83 | 28-JAN-11:35 | 779.69 | 381.83 | 505.18 | 0.00 | 0.00 | 0.00 | 0.00 | 88.37 | 0.00 |
February | 3707.44 | 05-FEB-11:35 | 779.69 | 458.20 | 577.35 | 0.00 | 0.00 | 0.00 | 0.00 | 182.24 | 0.00 |
March | 3509.39 | 27-MAR-10:35 | 519.79 | 381.83 | 505.18 | 0.00 | 0.00 | 0.00 | 0.00 | 321.34 | 0.00 |
April | 3541.04 | 28-APR-10:35 | 519.79 | 381.83 | 505.18 | 0.00 | 0.00 | 0.00 | 0.00 | 370.00 | 0.00 |
May | 3868.76 | 31-MAY-18:10 | 5457.82 | 3665.58 | 3897.11 | 0.00 | 0.00 | 0.00 | 0.00 | 380.01 | 0.00 |
June | 3893.42 | 10-JUN-10:35 | 779.69 | 381.83 | 505.18 | 0.00 | 0.00 | 0.00 | 0.00 | 342.62 | 0.00 |
July | 4094.00 | 30-JUL-10:35 | 779.69 | 458.20 | 577.35 | 0.00 | 0.00 | 0.00 | 0.00 | 444.61 | 0.00 |
August | 4161.13 | 05-AUG-10:35 | 779.69 | 381.83 | 505.18 | 0.00 | 0.00 | 0.00 | 0.00 | 412.39 | 0.00 |
September | 4008.17 | 04-SEP-10:35 | 779.69 | 458.20 | 577.35 | 0.00 | 0.00 | 0.00 | 0.00 | 332.59 | 0.00 |
October | 3971.03 | 09-OCT-10:35 | 779.69 | 458.20 | 577.35 | 0.00 | 0.00 | 0.00 | 0.00 | 275.14 | 0.00 |
November | 3829.81 | 06-NOV-11:35 | 519.79 | 381.83 | 505.18 | 0.00 | 0.00 | 0.00 | 0.00 | 217.12 | 0.00 |
December | 3564.64 | 03-DEC-11:35 | 779.69 | 458.20 | 577.35 | 0.00 | 0.00 | 0.00 | 0.00 | 124.69 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3343.83 | 519.79 | 381.83 | 505.18 | 0.00 | 0.00 | 0.00 | 0.00 | 88.37 | 0.00 | |
Maximum of Months | 4161.13 | 5457.82 | 3665.58 | 3897.11 | 0.00 | 0.00 | 0.00 | 0.00 | 444.61 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2021.18 | 24-JAN-21:00 | 1053.36 | 795.89 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.57 |
February | 2144.87 | 06-FEB-19:02 | 6320.16 | 4244.75 | 4512.87 | 0.00 | 0.00 | 0.00 | 0.00 | 25.14 | 0.00 |
March | 2358.49 | 27-MAR-18:10 | 6320.16 | 4244.75 | 4512.87 | 0.00 | 0.00 | 0.00 | 0.00 | 93.12 | 0.00 |
April | 2398.00 | 27-APR-18:10 | 6320.16 | 4244.75 | 4512.87 | 0.00 | 0.00 | 0.00 | 0.00 | 92.15 | 0.00 |
May | 2554.58 | 31-MAY-18:10 | 6320.16 | 4244.75 | 4512.87 | 0.00 | 0.00 | 0.00 | 0.00 | 146.58 | 0.00 |
June | 2539.48 | 01-JUN-18:10 | 6320.16 | 4244.75 | 4512.87 | 0.00 | 0.00 | 0.00 | 0.00 | 119.12 | 0.00 |
July | 2580.85 | 31-JUL-18:10 | 6320.16 | 4244.75 | 4512.87 | 0.00 | 0.00 | 0.00 | 0.00 | 142.18 | 0.00 |
August | 2638.39 | 16-AUG-18:10 | 6320.16 | 4244.75 | 4512.87 | 0.00 | 0.00 | 0.00 | 0.00 | 149.25 | 0.00 |
September | 2510.81 | 06-SEP-18:10 | 6320.16 | 4244.75 | 4512.87 | 0.00 | 0.00 | 0.00 | 0.00 | 114.10 | 0.00 |
October | 2428.45 | 05-OCT-18:10 | 6320.16 | 4244.75 | 4512.87 | 0.00 | 0.00 | 0.00 | 0.00 | 106.12 | 0.00 |
November | 2310.58 | 01-NOV-18:10 | 6320.16 | 4244.75 | 4512.87 | 0.00 | 0.00 | 0.00 | 0.00 | 78.39 | 0.00 |
December | 2139.53 | 06-DEC-19:03 | 7373.52 | 4952.21 | 5265.02 | 0.00 | 0.00 | 0.00 | 0.00 | 33.91 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2021.18 | 1053.36 | 795.89 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2638.39 | 7373.52 | 4952.21 | 5265.02 | 0.00 | 0.00 | 0.00 | 0.00 | 149.25 | 2.57 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2217.05 | 24-JAN-21:00 | 222.77 | 1487.69 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.32 |
February | 2356.25 | 06-FEB-20:10 | 222.77 | 1487.69 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 57.45 | 0.00 |
March | 2624.38 | 27-MAR-18:02 | 1336.61 | 7934.32 | 4771.59 | 0.00 | 0.00 | 0.00 | 0.00 | 221.71 | 0.00 |
April | 2728.47 | 27-APR-18:10 | 1336.61 | 7934.32 | 4771.59 | 0.00 | 0.00 | 0.00 | 0.00 | 219.45 | 0.00 |
May | 2946.34 | 31-MAY-18:10 | 1336.61 | 7934.32 | 4771.59 | 0.00 | 0.00 | 0.00 | 0.00 | 346.26 | 0.00 |
June | 2969.89 | 10-JUN-10:35 | 190.94 | 826.49 | 618.54 | 0.00 | 0.00 | 0.00 | 0.00 | 311.92 | 0.00 |
July | 3119.11 | 22-JUL-10:35 | 190.94 | 826.49 | 618.54 | 0.00 | 0.00 | 0.00 | 0.00 | 360.20 | 0.00 |
August | 3127.27 | 06-AUG-10:35 | 190.94 | 991.79 | 706.90 | 0.00 | 0.00 | 0.00 | 0.00 | 322.42 | 0.00 |
September | 2917.37 | 04-SEP-10:35 | 190.94 | 991.79 | 706.90 | 0.00 | 0.00 | 0.00 | 0.00 | 309.57 | 0.00 |
October | 2766.67 | 05-OCT-18:10 | 1336.61 | 7934.32 | 4771.59 | 0.00 | 0.00 | 0.00 | 0.00 | 252.32 | 0.00 |
November | 2601.77 | 01-NOV-18:02 | 1336.61 | 7934.32 | 4771.59 | 0.00 | 0.00 | 0.00 | 0.00 | 187.01 | 0.00 |
December | 2331.81 | 06-DEC-20:10 | 222.77 | 1487.69 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 76.81 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2217.05 | 190.94 | 826.49 | 618.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3127.27 | 1336.61 | 7934.32 | 4771.59 | 0.00 | 0.00 | 0.00 | 0.00 | 360.20 | 0.32 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 877.78 | 23-JAN-22:00 | 195.84 | 242.76 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 4.44 | 0.00 |
February | 1067.77 | 07-FEB-22:00 | 195.84 | 242.76 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 37.79 | 0.00 |
March | 1243.52 | 27-MAR-20:00 | 171.36 | 273.10 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 107.95 | 0.00 |
April | 1294.15 | 28-APR-18:02 | 1028.16 | 1456.53 | 1376.47 | 0.00 | 0.00 | 0.00 | 0.00 | 139.88 | 0.00 |
May | 1475.94 | 31-MAY-18:10 | 1028.16 | 1456.53 | 1376.47 | 0.00 | 0.00 | 0.00 | 0.00 | 201.23 | 0.00 |
June | 1523.81 | 10-JUN-10:35 | 146.88 | 151.73 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 179.46 | 0.00 |
July | 1599.07 | 22-JUL-10:35 | 146.88 | 151.73 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 207.36 | 0.00 |
August | 1601.97 | 05-AUG-10:35 | 146.88 | 151.73 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 217.57 | 0.00 |
September | 1492.33 | 04-SEP-10:35 | 146.88 | 182.07 | 203.92 | 0.00 | 0.00 | 0.00 | 0.00 | 178.35 | 0.00 |
October | 1341.98 | 05-OCT-18:30 | 171.36 | 242.76 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 140.83 | 0.00 |
November | 1234.91 | 01-NOV-20:00 | 171.36 | 273.10 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 98.00 | 0.00 |
December | 1003.84 | 11-DEC-22:00 | 195.84 | 242.76 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 36.68 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 877.78 | 146.88 | 151.73 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 4.44 | 0.00 | |
Maximum of Months | 1601.97 | 1028.16 | 1456.53 | 1376.47 | 0.00 | 0.00 | 0.00 | 0.00 | 217.57 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 36349.30 | 24-JAN-21:00 | 705.60 | 337.37 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 79.61 |
February | 36758.45 | 07-FEB-21:00 | 705.60 | 337.37 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 26.69 | 0.00 |
March | 37506.27 | 27-MAR-20:00 | 705.60 | 337.37 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 185.99 | 0.00 |
April | 37754.34 | 28-APR-20:00 | 705.60 | 337.37 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 229.13 | 0.00 |
May | 38535.87 | 31-MAY-20:00 | 705.60 | 337.37 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 423.34 | 0.00 |
June | 38370.95 | 01-JUN-20:00 | 705.60 | 337.37 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 262.69 | 0.00 |
July | 38657.04 | 21-JUL-20:00 | 705.60 | 337.37 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 420.02 | 0.00 |
August | 38797.52 | 10-AUG-20:00 | 705.60 | 337.37 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 409.73 | 0.00 |
September | 38243.74 | 06-SEP-20:00 | 705.60 | 337.37 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 285.82 | 0.00 |
October | 37948.11 | 05-OCT-20:00 | 705.60 | 337.37 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 238.93 | 0.00 |
November | 37389.24 | 01-NOV-20:00 | 705.60 | 337.37 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 161.65 | 0.00 |
December | 36624.96 | 05-DEC-21:00 | 705.60 | 337.37 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 26.69 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 36349.30 | 705.60 | 337.37 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 38797.52 | 705.60 | 337.37 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 423.34 | 79.61 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 13028.04 | 28-JAN-11:35 | 10245.60 | 1209.57 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 198.69 | 0.00 |
February | 14369.25 | 05-FEB-11:35 | 10245.60 | 1451.48 | 812.86 | 0.00 | 0.00 | 0.00 | 0.00 | 411.01 | 0.00 |
March | 14063.67 | 27-MAR-18:03 | 71719.20 | 11611.87 | 5486.82 | 0.00 | 0.00 | 0.00 | 0.00 | 536.97 | 0.00 |
April | 14056.07 | 27-APR-18:05 | 71719.20 | 11611.87 | 5486.82 | 0.00 | 0.00 | 0.00 | 0.00 | 532.65 | 0.00 |
May | 15424.80 | 31-MAY-18:10 | 71719.20 | 11611.87 | 5486.82 | 0.00 | 0.00 | 0.00 | 0.00 | 838.66 | 0.00 |
June | 15107.15 | 01-JUN-18:10 | 71719.20 | 11611.87 | 5486.82 | 0.00 | 0.00 | 0.00 | 0.00 | 686.61 | 0.00 |
July | 15626.14 | 31-JUL-18:10 | 71719.20 | 11611.87 | 5486.82 | 0.00 | 0.00 | 0.00 | 0.00 | 812.62 | 0.00 |
August | 15993.55 | 16-AUG-18:10 | 71719.20 | 11611.87 | 5486.82 | 0.00 | 0.00 | 0.00 | 0.00 | 852.61 | 0.00 |
September | 15038.84 | 06-SEP-18:10 | 71719.20 | 11611.87 | 5486.82 | 0.00 | 0.00 | 0.00 | 0.00 | 655.50 | 0.00 |
October | 15135.76 | 09-OCT-10:35 | 10245.60 | 1451.48 | 812.86 | 0.00 | 0.00 | 0.00 | 0.00 | 622.54 | 0.00 |
November | 14553.16 | 19-NOV-11:35 | 10245.60 | 1451.48 | 812.86 | 0.00 | 0.00 | 0.00 | 0.00 | 390.27 | 0.00 |
December | 13879.33 | 03-DEC-11:35 | 10245.60 | 1451.48 | 812.86 | 0.00 | 0.00 | 0.00 | 0.00 | 282.06 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 13028.04 | 10245.60 | 1209.57 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 198.69 | 0.00 | |
Maximum of Months | 15993.55 | 71719.20 | 11611.87 | 5486.82 | 0.00 | 0.00 | 0.00 | 0.00 | 852.61 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 40478.89 | 23-JAN-19:10 | 212907.24 | 63196.36 | 57008.13 | 0.00 | 0.00 | 0.00 | 0.00 | 185.62 | 0.00 |
February | 42242.25 | 06-FEB-19:10 | 212907.24 | 63196.36 | 57008.13 | 0.00 | 0.00 | 0.00 | 0.00 | 399.17 | 0.00 |
March | 45874.93 | 27-MAR-18:10 | 212907.24 | 63196.36 | 57008.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1516.14 | 0.00 |
April | 46571.73 | 27-APR-18:10 | 212907.24 | 63196.36 | 57008.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1501.53 | 0.00 |
May | 49674.73 | 31-MAY-18:10 | 212907.24 | 63196.36 | 57008.13 | 0.00 | 0.00 | 0.00 | 0.00 | 2390.59 | 0.00 |
June | 49235.74 | 01-JUN-18:10 | 212907.24 | 63196.36 | 57008.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1944.27 | 0.00 |
July | 50178.93 | 31-JUL-18:10 | 212907.24 | 63196.36 | 57008.13 | 0.00 | 0.00 | 0.00 | 0.00 | 2318.81 | 0.00 |
August | 51059.83 | 16-AUG-18:10 | 212907.24 | 63196.36 | 57008.13 | 0.00 | 0.00 | 0.00 | 0.00 | 2439.00 | 0.00 |
September | 48647.64 | 06-SEP-18:10 | 212907.24 | 63196.36 | 57008.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1862.80 | 0.00 |
October | 47367.41 | 05-OCT-18:10 | 212907.24 | 63196.36 | 57008.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1725.97 | 0.00 |
November | 45272.16 | 01-NOV-18:10 | 212907.24 | 63196.36 | 57008.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1268.15 | 0.00 |
December | 41941.43 | 06-DEC-19:10 | 248391.78 | 73729.08 | 66509.49 | 0.00 | 0.00 | 0.00 | 0.00 | 540.05 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 40478.89 | 212907.24 | 63196.36 | 57008.13 | 0.00 | 0.00 | 0.00 | 0.00 | 185.62 | 0.00 | |
Maximum of Months | 51059.83 | 248391.78 | 73729.08 | 66509.49 | 0.00 | 0.00 | 0.00 | 0.00 | 2439.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3699.14 | 16-JAN-16:01 | 378.00 | 907.20 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 17.60 | 0.00 |
February | 3572.62 | 23-FEB-19:01 | 970.20 | 2446.69 | 903.46 | 0.00 | 0.00 | 0.00 | 0.00 | 25.55 | 0.00 |
March | 3581.43 | 20-MAR-18:02 | 831.60 | 2097.16 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 39.07 | 0.00 |
April | 3740.58 | 01-APR-15:02 | 324.00 | 777.60 | 458.31 | 0.00 | 0.00 | 0.00 | 0.00 | 121.85 | 0.00 |
May | 3687.62 | 26-MAY-15:02 | 583.20 | 659.78 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 134.47 | 0.00 |
June | 3687.35 | 27-JUN-15:02 | 583.20 | 659.78 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 178.56 | 0.00 |
July | 3682.70 | 22-JUL-15:02 | 324.00 | 777.60 | 458.31 | 0.00 | 0.00 | 0.00 | 0.00 | 175.96 | 0.00 |
August | 3689.64 | 02-AUG-15:02 | 583.20 | 659.78 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 183.98 | 0.00 |
September | 3703.86 | 21-SEP-15:02 | 583.20 | 659.78 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 143.88 | 0.00 |
October | 3677.40 | 01-OCT-15:02 | 324.00 | 777.60 | 458.31 | 0.00 | 0.00 | 0.00 | 0.00 | 133.43 | 0.00 |
November | 3767.54 | 18-NOV-16:01 | 378.00 | 907.20 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 96.75 | 0.00 |
December | 3591.52 | 25-DEC-16:01 | 378.00 | 907.20 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 34.66 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3572.62 | 324.00 | 659.78 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 17.60 | 0.00 | |
Maximum of Months | 3767.54 | 970.20 | 2446.69 | 903.46 | 0.00 | 0.00 | 0.00 | 0.00 | 183.98 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3619.32 | 16-JAN-16:01 | 378.00 | 907.09 | 534.64 | 0.00 | 0.00 | 0.00 | 0.00 | 18.23 | 0.00 |
February | 3524.50 | 05-FEB-16:02 | 324.00 | 777.51 | 458.26 | 0.00 | 0.00 | 0.00 | 0.00 | 111.83 | 0.00 |
March | 3514.33 | 20-MAR-18:02 | 831.60 | 2096.92 | 774.30 | 0.00 | 0.00 | 0.00 | 0.00 | 39.22 | 0.00 |
April | 3668.45 | 01-APR-15:02 | 324.00 | 777.51 | 458.26 | 0.00 | 0.00 | 0.00 | 0.00 | 122.20 | 0.00 |
May | 3630.38 | 26-MAY-15:02 | 583.20 | 659.70 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 134.21 | 0.00 |
June | 3627.25 | 27-JUN-15:02 | 583.20 | 659.70 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 178.26 | 0.00 |
July | 3627.14 | 22-JUL-15:02 | 324.00 | 777.51 | 458.26 | 0.00 | 0.00 | 0.00 | 0.00 | 175.73 | 0.00 |
August | 3639.14 | 02-AUG-15:02 | 583.20 | 659.70 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 183.82 | 0.00 |
September | 3622.03 | 18-SEP-15:02 | 583.20 | 659.70 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 144.84 | 0.00 |
October | 3619.00 | 03-OCT-15:02 | 583.20 | 659.70 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 145.34 | 0.00 |
November | 3687.95 | 18-NOV-16:01 | 378.00 | 907.09 | 534.64 | 0.00 | 0.00 | 0.00 | 0.00 | 97.33 | 0.00 |
December | 3489.66 | 27-DEC-16:01 | 680.40 | 769.66 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.93 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3489.66 | 324.00 | 659.70 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3687.95 | 831.60 | 2096.92 | 774.30 | 0.00 | 0.00 | 0.00 | 0.00 | 183.82 | 6.93 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 560.38 | 28-JAN-13:40 | 0.00 | 81.45 | 74.82 | 0.00 | 0.00 | 0.00 | 0.00 | 14.78 | 0.00 |
February | 635.25 | 05-FEB-13:40 | 0.00 | 81.45 | 74.82 | 0.00 | 0.00 | 0.00 | 0.00 | 26.87 | 0.00 |
March | 583.45 | 27-MAR-13:30 | 0.00 | 69.11 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 39.72 | 0.00 |
April | 587.46 | 28-APR-20:20 | 0.00 | 219.66 | 180.59 | 0.00 | 0.00 | 0.00 | 0.00 | 29.62 | 0.00 |
May | 671.37 | 31-MAY-19:20 | 0.00 | 246.81 | 170.27 | 0.00 | 0.00 | 0.00 | 0.00 | 58.15 | 0.00 |
June | 662.91 | 09-JUN-20:20 | 0.00 | 219.66 | 180.59 | 0.00 | 0.00 | 0.00 | 0.00 | 43.00 | 0.00 |
July | 724.02 | 21-JUL-20:20 | 0.00 | 219.66 | 180.59 | 0.00 | 0.00 | 0.00 | 0.00 | 54.83 | 0.00 |
August | 722.82 | 16-AUG-19:20 | 0.00 | 246.81 | 170.27 | 0.00 | 0.00 | 0.00 | 0.00 | 52.77 | 0.00 |
September | 707.83 | 26-SEP-13:10 | 0.00 | 69.11 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 56.19 | 0.00 |
October | 717.83 | 09-OCT-13:20 | 0.00 | 81.45 | 74.82 | 0.00 | 0.00 | 0.00 | 0.00 | 45.64 | 0.00 |
November | 688.80 | 05-NOV-13:30 | 0.00 | 81.45 | 74.82 | 0.00 | 0.00 | 0.00 | 0.00 | 32.64 | 0.00 |
December | 640.50 | 03-DEC-13:00 | 0.00 | 81.45 | 74.82 | 0.00 | 0.00 | 0.00 | 0.00 | 21.60 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 560.38 | 0.00 | 69.11 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 14.78 | 0.00 | |
Maximum of Months | 724.02 | 0.00 | 246.81 | 180.59 | 0.00 | 0.00 | 0.00 | 0.00 | 58.15 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1349.36 | 16-JAN-16:01 | 378.00 | 570.30 | 523.86 | 0.00 | 0.00 | 0.00 | 0.00 | 6.24 | 0.00 |
February | 1351.39 | 07-FEB-19:02 | 831.60 | 1318.35 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 13.42 | 0.00 |
March | 1364.23 | 21-MAR-18:02 | 831.60 | 1318.35 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 10.63 | 0.00 |
April | 1392.37 | 28-APR-18:02 | 831.60 | 1318.35 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 37.09 | 0.00 |
May | 1401.23 | 21-MAY-18:02 | 702.00 | 1481.29 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 40.92 | 0.00 |
June | 1380.90 | 01-JUN-18:02 | 831.60 | 1318.35 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 44.61 | 0.00 |
July | 1403.59 | 21-JUL-18:02 | 831.60 | 1318.35 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 59.86 | 0.00 |
August | 1381.82 | 06-AUG-15:02 | 324.00 | 488.83 | 449.03 | 0.00 | 0.00 | 0.00 | 0.00 | 57.31 | 0.00 |
September | 1378.57 | 04-SEP-18:02 | 702.00 | 1481.29 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 48.00 | 0.00 |
October | 1389.17 | 09-OCT-18:02 | 702.00 | 1481.29 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 36.23 | 0.00 |
November | 1425.34 | 18-NOV-16:01 | 378.00 | 570.30 | 523.86 | 0.00 | 0.00 | 0.00 | 0.00 | 26.33 | 0.00 |
December | 1360.60 | 11-DEC-19:01 | 970.20 | 1538.07 | 885.15 | 0.00 | 0.00 | 0.00 | 0.00 | 9.80 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1349.36 | 324.00 | 488.83 | 449.03 | 0.00 | 0.00 | 0.00 | 0.00 | 6.24 | 0.00 | |
Maximum of Months | 1425.34 | 970.20 | 1538.07 | 885.15 | 0.00 | 0.00 | 0.00 | 0.00 | 59.86 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3383.02 | 16-JAN-16:01 | 378.00 | 907.20 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 16.93 | 0.00 |
February | 3295.24 | 23-FEB-19:01 | 970.20 | 2446.69 | 903.46 | 0.00 | 0.00 | 0.00 | 0.00 | 24.66 | 0.00 |
March | 3342.04 | 23-MAR-08:62 | 216.00 | 1036.80 | 679.57 | 0.00 | 0.00 | 0.00 | 0.00 | 42.36 | 0.00 |
April | 3406.52 | 01-APR-15:02 | 324.00 | 777.60 | 458.31 | 0.00 | 0.00 | 0.00 | 0.00 | 121.66 | 0.00 |
May | 3355.93 | 31-MAY-18:02 | 831.60 | 2097.16 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 202.88 | 0.00 |
June | 3360.02 | 20-JUN-15:02 | 583.20 | 659.78 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 186.72 | 0.00 |
July | 3352.16 | 23-JUL-15:02 | 324.00 | 777.60 | 458.31 | 0.00 | 0.00 | 0.00 | 0.00 | 176.97 | 0.00 |
August | 3383.15 | 05-AUG-18:02 | 702.00 | 2356.36 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 196.83 | 0.00 |
September | 3373.03 | 02-SEP-15:02 | 324.00 | 777.60 | 458.31 | 0.00 | 0.00 | 0.00 | 0.00 | 166.26 | 0.00 |
October | 3350.28 | 03-OCT-15:02 | 583.20 | 659.78 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 144.68 | 0.00 |
November | 3432.37 | 18-NOV-16:01 | 378.00 | 907.20 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 96.52 | 0.00 |
December | 3255.00 | 27-DEC-16:01 | 680.40 | 769.75 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.89 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3255.00 | 216.00 | 659.78 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3432.37 | 970.20 | 2446.69 | 903.46 | 0.00 | 0.00 | 0.00 | 0.00 | 202.88 | 7.89 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3258.82 | 16-JAN-16:01 | 378.00 | 907.09 | 534.64 | 0.00 | 0.00 | 0.00 | 0.00 | 20.32 | 0.00 |
February | 3166.07 | 04-FEB-19:01 | 819.00 | 2748.77 | 903.35 | 0.00 | 0.00 | 0.00 | 0.00 | 21.54 | 0.00 |
March | 3281.70 | 23-MAR-08:62 | 216.00 | 1036.68 | 679.49 | 0.00 | 0.00 | 0.00 | 0.00 | 42.53 | 0.00 |
April | 3338.44 | 01-APR-15:02 | 324.00 | 777.51 | 458.26 | 0.00 | 0.00 | 0.00 | 0.00 | 122.02 | 0.00 |
May | 3300.94 | 08-MAY-15:02 | 583.20 | 659.70 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 145.04 | 0.00 |
June | 3300.72 | 20-JUN-15:02 | 583.20 | 659.70 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 186.38 | 0.00 |
July | 3325.11 | 15-JUL-18:02 | 702.00 | 2356.09 | 774.30 | 0.00 | 0.00 | 0.00 | 0.00 | 197.64 | 0.00 |
August | 3332.12 | 04-AUG-15:02 | 583.20 | 659.70 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 175.40 | 0.00 |
September | 3302.03 | 20-SEP-15:02 | 583.20 | 659.70 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 154.78 | 0.00 |
October | 3266.06 | 09-OCT-18:02 | 702.00 | 2356.09 | 774.30 | 0.00 | 0.00 | 0.00 | 0.00 | 132.27 | 0.00 |
November | 3355.66 | 18-NOV-16:01 | 378.00 | 907.09 | 534.64 | 0.00 | 0.00 | 0.00 | 0.00 | 97.16 | 0.00 |
December | 3150.42 | 25-DEC-16:01 | 378.00 | 907.09 | 534.64 | 0.00 | 0.00 | 0.00 | 0.00 | 35.77 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3150.42 | 216.00 | 659.70 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 20.32 | 0.00 | |
Maximum of Months | 3355.66 | 819.00 | 2748.77 | 903.35 | 0.00 | 0.00 | 0.00 | 0.00 | 197.64 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2603.96 | 29-JAN-19:40 | 1508.90 | 997.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.87 | 0.00 |
February | 3040.22 | 05-FEB-11:35 | 1508.90 | 855.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 133.95 | 0.00 |
March | 3252.45 | 27-MAR-18:10 | 10562.33 | 6840.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 164.41 | 0.00 |
April | 3483.58 | 29-APR-10:35 | 1508.90 | 712.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 202.46 | 0.00 |
May | 3732.47 | 31-MAY-18:10 | 10562.33 | 6840.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 254.70 | 0.00 |
June | 3783.35 | 10-JUN-10:35 | 1508.90 | 712.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 227.44 | 0.00 |
July | 3981.99 | 22-JUL-10:35 | 1508.90 | 712.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 263.91 | 0.00 |
August | 4004.11 | 05-AUG-10:35 | 1508.90 | 712.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 277.02 | 0.00 |
September | 3790.36 | 04-SEP-10:35 | 1508.90 | 855.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 223.38 | 0.00 |
October | 3573.41 | 09-OCT-10:35 | 1508.90 | 855.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 189.08 | 0.00 |
November | 3296.80 | 05-NOV-10:35 | 1508.90 | 855.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 142.44 | 0.00 |
December | 2975.65 | 03-DEC-11:35 | 1508.90 | 855.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.60 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 2603.96 | 1508.90 | 712.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.87 | 0.00 | |
Maximum of Months | 4004.11 | 10562.33 | 6840.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 277.02 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4003.13 | 16-JAN-16:01 | 378.00 | 907.20 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 17.28 | 0.00 |
February | 3904.81 | 03-FEB-16:01 | 680.40 | 769.75 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 32.96 | 0.00 |
March | 3925.58 | 24-MAR-15:02 | 583.20 | 659.78 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 52.38 | 0.00 |
April | 3962.45 | 30-APR-15:02 | 324.00 | 777.60 | 458.31 | 0.00 | 0.00 | 0.00 | 0.00 | 101.06 | 0.00 |
May | 3981.53 | 22-MAY-18:02 | 831.60 | 2097.16 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 133.85 | 0.00 |
June | 3997.20 | 08-JUN-15:02 | 583.20 | 659.78 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 155.94 | 0.00 |
July | 4046.79 | 18-JUL-15:02 | 583.20 | 659.78 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 204.06 | 0.00 |
August | 4035.58 | 23-AUG-15:02 | 583.20 | 659.78 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 184.29 | 0.00 |
September | 4013.04 | 04-SEP-15:02 | 324.00 | 777.60 | 458.31 | 0.00 | 0.00 | 0.00 | 0.00 | 207.39 | 0.00 |
October | 3942.14 | 07-OCT-15:02 | 324.00 | 777.60 | 458.31 | 0.00 | 0.00 | 0.00 | 0.00 | 143.73 | 0.00 |
November | 4085.53 | 18-NOV-16:01 | 378.00 | 907.20 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 96.25 | 0.00 |
December | 3867.66 | 07-DEC-16:02 | 583.20 | 659.78 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 34.37 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3867.66 | 324.00 | 659.78 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 17.28 | 0.00 | |
Maximum of Months | 4085.53 | 831.60 | 2097.16 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 207.39 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3917.35 | 16-JAN-16:01 | 378.00 | 907.09 | 534.64 | 0.00 | 0.00 | 0.00 | 0.00 | 17.96 | 0.00 |
February | 3801.28 | 23-FEB-19:01 | 970.20 | 2446.40 | 903.35 | 0.00 | 0.00 | 0.00 | 0.00 | 25.81 | 0.00 |
March | 3827.88 | 25-MAR-15:02 | 324.00 | 777.51 | 458.26 | 0.00 | 0.00 | 0.00 | 0.00 | 84.90 | 0.00 |
April | 3920.97 | 30-APR-15:02 | 324.00 | 777.51 | 458.26 | 0.00 | 0.00 | 0.00 | 0.00 | 101.04 | 0.00 |
May | 3919.04 | 22-MAY-18:02 | 831.60 | 2096.92 | 774.30 | 0.00 | 0.00 | 0.00 | 0.00 | 133.55 | 0.00 |
June | 3987.94 | 09-JUN-15:02 | 583.20 | 659.70 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 216.29 | 0.00 |
July | 3969.50 | 04-JUL-15:02 | 324.00 | 777.51 | 458.26 | 0.00 | 0.00 | 0.00 | 0.00 | 193.89 | 0.00 |
August | 3982.65 | 07-AUG-15:02 | 583.20 | 659.70 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 187.77 | 0.00 |
September | 3923.21 | 24-SEP-15:02 | 324.00 | 777.51 | 458.26 | 0.00 | 0.00 | 0.00 | 0.00 | 133.58 | 0.00 |
October | 3887.00 | 24-OCT-15:02 | 583.20 | 659.70 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 110.42 | 0.00 |
November | 3999.53 | 18-NOV-16:01 | 378.00 | 907.09 | 534.64 | 0.00 | 0.00 | 0.00 | 0.00 | 96.87 | 0.00 |
December | 3775.62 | 27-DEC-16:01 | 680.40 | 769.66 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.22 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3775.62 | 324.00 | 659.70 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3999.53 | 970.20 | 2446.40 | 903.35 | 0.00 | 0.00 | 0.00 | 0.00 | 216.29 | 7.22 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2153.09 | 12-JAN-16:01 | 680.40 | 483.89 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.18 |
February | 2143.18 | 15-FEB-16:02 | 583.20 | 414.76 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 7.77 | 0.00 |
March | 2159.53 | 24-MAR-15:02 | 583.20 | 414.76 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 26.09 | 0.00 |
April | 2178.34 | 26-APR-08:61 | 252.00 | 760.39 | 776.76 | 0.00 | 0.00 | 0.00 | 0.00 | 42.13 | 0.00 |
May | 2170.15 | 08-MAY-18:02 | 831.60 | 1318.35 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 61.16 | 0.00 |
June | 2181.84 | 27-JUN-15:02 | 583.20 | 414.76 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 90.95 | 0.00 |
July | 2183.46 | 15-JUL-18:02 | 702.00 | 1481.29 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 101.04 | 0.00 |
August | 2184.64 | 17-AUG-18:02 | 831.60 | 1318.35 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 95.43 | 0.00 |
September | 2213.27 | 26-SEP-15:02 | 583.20 | 414.76 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 93.95 | 0.00 |
October | 2172.13 | 04-OCT-18:02 | 831.60 | 1318.35 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 67.01 | 0.00 |
November | 2168.97 | 01-NOV-15:02 | 583.20 | 414.76 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 56.32 | 0.00 |
December | 2157.92 | 04-DEC-16:02 | 583.20 | 414.76 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 21.98 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2143.18 | 252.00 | 414.76 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2213.27 | 831.60 | 1481.29 | 776.76 | 0.00 | 0.00 | 0.00 | 0.00 | 101.04 | 2.18 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 20884.93 | 23-JAN-23:00 | 26988.77 | 2548.93 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.28 |
February | 21474.88 | 07-FEB-23:00 | 26988.77 | 2548.93 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 30.16 | 0.00 |
March | 22939.00 | 27-MAR-18:10 | 125947.58 | 20391.43 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 323.35 | 0.00 |
April | 23469.07 | 27-APR-18:10 | 125947.58 | 20391.43 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 318.08 | 0.00 |
May | 25225.09 | 31-MAY-18:10 | 125947.58 | 20391.43 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 515.24 | 0.00 |
June | 24992.81 | 01-JUN-18:10 | 125947.58 | 20391.43 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 415.16 | 0.00 |
July | 25368.03 | 31-JUL-18:10 | 125947.58 | 20391.43 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 500.13 | 0.00 |
August | 25715.90 | 16-AUG-18:10 | 125947.58 | 20391.43 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 527.76 | 0.00 |
September | 24419.04 | 06-SEP-18:10 | 125947.58 | 20391.43 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 399.62 | 0.00 |
October | 23562.05 | 05-OCT-18:10 | 125947.58 | 20391.43 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 371.26 | 0.00 |
November | 22438.18 | 01-NOV-18:10 | 125947.58 | 20391.43 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 269.63 | 0.00 |
December | 21323.83 | 11-DEC-23:00 | 26988.77 | 2548.93 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 31.69 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 20884.93 | 26988.77 | 2548.93 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 25715.90 | 125947.58 | 20391.43 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 527.76 | 54.28 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 22138.24 | 23-JAN-23:00 | 26988.77 | 2548.93 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.11 |
February | 22764.49 | 07-FEB-23:00 | 26988.77 | 2548.93 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 27.25 | 0.00 |
March | 24300.54 | 27-MAR-18:10 | 125947.58 | 20391.43 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 320.50 | 0.00 |
April | 24862.24 | 27-APR-18:10 | 125947.58 | 20391.43 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 315.18 | 0.00 |
May | 26632.08 | 31-MAY-18:10 | 125947.58 | 20391.43 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 513.03 | 0.00 |
June | 26369.36 | 01-JUN-18:10 | 125947.58 | 20391.43 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 413.12 | 0.00 |
July | 26721.32 | 31-JUL-18:10 | 125947.58 | 20391.43 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 498.48 | 0.00 |
August | 27058.42 | 16-AUG-18:10 | 125947.58 | 20391.43 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 526.36 | 0.00 |
September | 25749.33 | 06-SEP-18:10 | 125947.58 | 20391.43 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 397.75 | 0.00 |
October | 24906.51 | 05-OCT-18:10 | 125947.58 | 20391.43 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 368.86 | 0.00 |
November | 23778.05 | 01-NOV-18:10 | 125947.58 | 20391.43 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 266.74 | 0.00 |
December | 22605.02 | 11-DEC-23:00 | 26988.77 | 2548.93 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 28.80 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 22138.24 | 26988.77 | 2548.93 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 27058.42 | 125947.58 | 20391.43 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 526.36 | 57.11 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 28303.35 | 29-JAN-11:45 | 1601.14 | 680.52 | 30224.21 | 37488.05 | 0.00 | 0.00 | 0.00 | 73.17 | 0.00 |
February | 29022.93 | 05-FEB-11:50 | 800.57 | 340.26 | 15112.11 | 18744.03 | 0.00 | 0.00 | 0.00 | 172.75 | 0.00 |
March | 29807.63 | 27-MAR-10:50 | 1067.42 | 567.10 | 30224.21 | 37488.05 | 0.00 | 0.00 | 0.00 | 341.76 | 0.00 |
April | 30839.83 | 28-APR-10:50 | 533.71 | 283.55 | 15112.11 | 18744.03 | 0.00 | 0.00 | 0.00 | 396.99 | 0.00 |
May | 31106.05 | 29-MAY-10:40 | 1601.14 | 680.52 | 30224.21 | 37488.05 | 0.00 | 0.00 | 0.00 | 334.63 | 0.00 |
June | 31417.51 | 10-JUN-10:40 | 1601.14 | 567.10 | 30224.21 | 37488.05 | 0.00 | 0.00 | 0.00 | 358.73 | 0.00 |
July | 32127.44 | 30-JUL-10:40 | 1601.14 | 680.52 | 30224.21 | 37488.05 | 0.00 | 0.00 | 0.00 | 494.04 | 0.00 |
August | 32042.32 | 05-AUG-10:40 | 1601.14 | 567.10 | 30224.21 | 37488.05 | 0.00 | 0.00 | 0.00 | 456.53 | 0.00 |
September | 31313.95 | 04-SEP-10:50 | 800.57 | 340.26 | 15112.11 | 18744.03 | 0.00 | 0.00 | 0.00 | 353.10 | 0.00 |
October | 30675.77 | 09-OCT-10:50 | 800.57 | 340.26 | 15112.11 | 18744.03 | 0.00 | 0.00 | 0.00 | 294.19 | 0.00 |
November | 29596.13 | 05-NOV-10:50 | 800.57 | 340.26 | 15112.11 | 18744.03 | 0.00 | 0.00 | 0.00 | 202.29 | 0.00 |
December | 28630.33 | 03-DEC-11:50 | 800.57 | 340.26 | 15112.11 | 18744.03 | 0.00 | 0.00 | 0.00 | 95.22 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 28303.35 | 533.71 | 283.55 | 15112.11 | 18744.03 | 0.00 | 0.00 | 0.00 | 73.17 | 0.00 | |
Maximum of Months | 32127.44 | 1601.14 | 680.52 | 30224.21 | 37488.05 | 0.00 | 0.00 | 0.00 | 494.04 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5752.72 | 28-JAN-13:00 | 798.48 | 377.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 160.35 | 0.00 |
February | 6959.04 | 05-FEB-11:35 | 1596.96 | 904.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 237.52 | 0.00 |
March | 7452.53 | 27-MAR-18:03 | 11178.72 | 7239.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 298.50 | 0.00 |
April | 8141.32 | 28-APR-10:35 | 1064.64 | 754.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 450.39 | 0.00 |
May | 8596.32 | 31-MAY-18:10 | 11178.72 | 7239.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 458.03 | 0.00 |
June | 8953.82 | 10-JUN-10:35 | 1596.96 | 754.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 404.21 | 0.00 |
July | 9393.06 | 16-JUL-10:35 | 1596.96 | 904.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 427.47 | 0.00 |
August | 9335.21 | 05-AUG-10:35 | 1596.96 | 754.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 495.44 | 0.00 |
September | 8730.86 | 04-SEP-10:35 | 1596.96 | 904.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 402.81 | 0.00 |
October | 8174.19 | 09-OCT-10:35 | 1596.96 | 904.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 343.01 | 0.00 |
November | 7488.15 | 05-NOV-10:35 | 1596.96 | 904.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 261.28 | 0.00 |
December | 6241.09 | 03-DEC-11:35 | 1596.96 | 904.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 162.10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 5752.72 | 798.48 | 377.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 160.35 | 0.00 | |
Maximum of Months | 9393.06 | 11178.72 | 7239.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 495.44 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.809044E+12 | 496060.77 | 29-JAN-20:10 | 0.462143E+12 | 354407.89 | 01-JAN-18:00 |
February | 0.784773E+12 | 532176.61 | 08-FEB-20:00 | 0.409210E+12 | 356341.61 | 20-FEB-18:40 |
March | 0.926188E+12 | 553812.36 | 28-MAR-19:10 | 0.441220E+12 | 355353.74 | 05-MAR-17:40 |
April | 0.100749E+13 | 610759.01 | 30-APR-18:10 | 0.408363E+12 | 344558.45 | 02-APR-16:00 |
May | 0.120506E+13 | 716083.88 | 30-MAY-18:10 | 0.397441E+12 | 334009.83 | 02-MAY-16:40 |
June | 0.131482E+13 | 744866.69 | 27-JUN-19:00 | 0.370498E+12 | 330412.42 | 18-JUN-16:30 |
July | 0.150177E+13 | 800688.13 | 19-JUL-19:10 | 0.373295E+12 | 325870.89 | 23-JUL-16:49 |
August | 0.153730E+13 | 842574.52 | 10-AUG-18:10 | 0.370972E+12 | 320688.54 | 27-AUG-17:49 |
September | 0.134817E+13 | 767241.58 | 08-SEP-18:10 | 0.366866E+12 | 326612.36 | 24-SEP-16:19 |
October | 0.120459E+13 | 712743.73 | 07-OCT-18:10 | 0.393233E+12 | 329835.10 | 22-OCT-17:00 |
November | 0.100406E+13 | 620502.37 | 01-NOV-18:10 | 0.402177E+12 | 340900.60 | 23-NOV-18:49 |
December | 0.894635E+12 | 538770.29 | 05-DEC-20:10 | 0.446965E+12 | 351975.86 | 15-DEC-18:19 |
Annual Sum or Average | 0.135379E+14 | 0.484238E+13 | ||||
Minimum of Months | 0.784773E+12 | 496060.77 | 0.366866E+12 | 320688.54 | ||
Maximum of Months | 0.153730E+13 | 842574.52 | 0.462143E+12 | 356341.61 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [J] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.997859E+11 | 0.248854E+11 | 0.148746E+12 | 0.577258E+11 | 0.160924E+12 | 0.328305E+11 | 0.00 | 0.223600E+12 | 0.00 | 0.00 | 0.464584E+11 | 0.770740E+10 | 0.00 |
February | 0.901073E+11 | 0.215907E+11 | 0.134341E+12 | 0.521396E+11 | 0.146941E+12 | 0.313983E+11 | 0.00 | 0.253362E+12 | 0.00 | 0.00 | 0.421446E+11 | 0.696466E+10 | 0.00 |
March | 0.995228E+11 | 0.226121E+11 | 0.148757E+12 | 0.577286E+11 | 0.165746E+12 | 0.366088E+11 | 0.00 | 0.333577E+12 | 0.00 | 0.00 | 0.475256E+11 | 0.770606E+10 | 0.00 |
April | 0.965474E+11 | 0.205092E+11 | 0.143913E+12 | 0.558635E+11 | 0.165137E+12 | 0.380229E+11 | 0.00 | 0.426811E+12 | 0.00 | 0.00 | 0.470189E+11 | 0.746747E+10 | 0.00 |
May | 0.996636E+11 | 0.200886E+11 | 0.148757E+12 | 0.577273E+11 | 0.178309E+12 | 0.412174E+11 | 0.00 | 0.595881E+12 | 0.00 | 0.00 | 0.492727E+11 | 0.770659E+10 | 0.00 |
June | 0.963626E+11 | 0.189269E+11 | 0.143963E+12 | 0.558662E+11 | 0.175493E+12 | 0.411490E+11 | 0.00 | 0.721648E+12 | 0.00 | 0.00 | 0.477116E+11 | 0.745910E+10 | 0.00 |
July | 0.998551E+11 | 0.197481E+11 | 0.148708E+12 | 0.577246E+11 | 0.185109E+12 | 0.433710E+11 | 0.00 | 0.883812E+12 | 0.00 | 0.00 | 0.493041E+11 | 0.771459E+10 | 0.00 |
August | 0.995413E+11 | 0.206994E+11 | 0.148768E+12 | 0.577287E+11 | 0.185986E+12 | 0.435915E+11 | 0.00 | 0.917516E+12 | 0.00 | 0.00 | 0.493041E+11 | 0.770646E+10 | 0.00 |
September | 0.965794E+11 | 0.212802E+11 | 0.143924E+12 | 0.558636E+11 | 0.175287E+12 | 0.414968E+11 | 0.00 | 0.752317E+12 | 0.00 | 0.00 | 0.477136E+11 | 0.746842E+10 | 0.00 |
October | 0.997606E+11 | 0.233532E+11 | 0.148735E+12 | 0.577257E+11 | 0.176717E+12 | 0.413694E+11 | 0.00 | 0.593509E+12 | 0.00 | 0.00 | 0.492764E+11 | 0.770549E+10 | 0.00 |
November | 0.965244E+11 | 0.237738E+11 | 0.143978E+12 | 0.558644E+11 | 0.164495E+12 | 0.377875E+11 | 0.00 | 0.421095E+12 | 0.00 | 0.00 | 0.468749E+11 | 0.745142E+10 | 0.00 |
December | 0.998619E+11 | 0.252359E+11 | 0.148708E+12 | 0.577246E+11 | 0.163056E+12 | 0.355888E+11 | 0.00 | 0.303409E+12 | 0.00 | 0.00 | 0.469283E+11 | 0.771553E+10 | 0.00 |
Annual Sum or Average | 0.117411E+13 | 0.262703E+12 | 0.175130E+13 | 0.679683E+12 | 0.204320E+13 | 0.464432E+12 | 0.00 | 0.642654E+13 | 0.00 | 0.00 | 0.569533E+12 | 0.907732E+11 | 0.00 |
Minimum of Months | 0.901073E+11 | 0.189269E+11 | 0.134341E+12 | 0.521396E+11 | 0.146941E+12 | 0.313983E+11 | 0.00 | 0.223600E+12 | 0.00 | 0.00 | 0.421446E+11 | 0.696466E+10 | 0.00 |
Maximum of Months | 0.998619E+11 | 0.252359E+11 | 0.148768E+12 | 0.577287E+11 | 0.185986E+12 | 0.435915E+11 | 0.00 | 0.917516E+12 | 0.00 | 0.00 | 0.493041E+11 | 0.771553E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.151918E+12 | 0.00 | 0.758886E+11 | 0.00 | 0.234336E+12 | 0.00 | 0.00 |
February | 0.137204E+12 | 0.00 | 0.637714E+11 | 0.00 | 0.208235E+12 | 0.00 | 0.00 |
March | 0.152024E+12 | 0.00 | 0.676904E+11 | 0.00 | 0.221506E+12 | 0.00 | 0.00 |
April | 0.146956E+12 | 0.00 | 0.589818E+11 | 0.00 | 0.202425E+12 | 0.00 | 0.00 |
May | 0.151978E+12 | 0.00 | 0.483700E+11 | 0.00 | 0.197093E+12 | 0.00 | 0.00 |
June | 0.147114E+12 | 0.00 | 0.409773E+11 | 0.00 | 0.182407E+12 | 0.00 | 0.00 |
July | 0.151820E+12 | 0.00 | 0.357577E+11 | 0.00 | 0.185716E+12 | 0.00 | 0.00 |
August | 0.152039E+12 | 0.00 | 0.293124E+11 | 0.00 | 0.189621E+12 | 0.00 | 0.00 |
September | 0.146971E+12 | 0.00 | 0.273526E+11 | 0.00 | 0.192542E+12 | 0.00 | 0.00 |
October | 0.151903E+12 | 0.00 | 0.299902E+11 | 0.00 | 0.211339E+12 | 0.00 | 0.00 |
November | 0.147091E+12 | 0.00 | 0.389764E+11 | 0.00 | 0.216109E+12 | 0.00 | 0.00 |
December | 0.151820E+12 | 0.00 | 0.633758E+11 | 0.00 | 0.231769E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.178884E+13 | 0.00 | 0.580445E+12 | 0.00 | 0.247310E+13 | 0.00 | 0.00 |
Minimum of Months | 0.137204E+12 | 0.00 | 0.273526E+11 | 0.00 | 0.182407E+12 | 0.00 | 0.00 |
Maximum of Months | 0.152039E+12 | 0.00 | 0.758886E+11 | 0.00 | 0.234336E+12 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 93091.76 | 02-JAN-20:10 | 16690.39 | 01-JAN-00:10 | 89674.66 | 02-JAN-07:10 | 40537.60 | 02-JAN-07:19 | 72195.69 | 16-JAN-16:10 | 15423.04 | 28-JAN-11:50 | 0.00 | 01-JAN-00:10 |
February | 93091.76 | 01-FEB-20:10 | 16690.39 | 01-FEB-00:10 | 89674.66 | 01-FEB-07:10 | 40537.60 | 01-FEB-07:19 | 74909.82 | 05-FEB-16:10 | 15743.69 | 03-FEB-20:19 | 0.00 | 01-FEB-00:10 |
March | 93091.76 | 01-MAR-20:10 | 16690.39 | 01-MAR-00:10 | 89674.66 | 01-MAR-07:10 | 40537.60 | 01-MAR-07:19 | 79536.60 | 23-MAR-15:09 | 16199.95 | 26-MAR-10:50 | 0.00 | 01-MAR-00:10 |
April | 93091.76 | 03-APR-19:10 | 16690.39 | 01-APR-00:10 | 89674.66 | 03-APR-06:10 | 40537.60 | 03-APR-06:19 | 80453.53 | 24-APR-15:09 | 16483.63 | 30-APR-16:40 | 0.00 | 01-APR-00:10 |
May | 93091.76 | 01-MAY-19:10 | 16690.39 | 01-MAY-00:10 | 89674.66 | 01-MAY-06:10 | 40537.60 | 01-MAY-06:19 | 84210.41 | 19-MAY-15:20 | 17110.27 | 30-MAY-17:00 | 0.00 | 01-MAY-00:10 |
June | 93091.76 | 01-JUN-19:10 | 16690.39 | 01-JUN-00:10 | 89674.66 | 01-JUN-06:10 | 40537.60 | 01-JUN-06:19 | 85384.78 | 15-JUN-15:20 | 18006.14 | 26-JUN-18:10 | 0.00 | 01-JUN-00:10 |
July | 93091.76 | 03-JUL-19:10 | 16690.39 | 01-JUL-00:10 | 89674.66 | 03-JUL-06:10 | 40537.60 | 03-JUL-06:19 | 84936.62 | 21-JUL-15:09 | 18680.89 | 30-JUL-16:19 | 0.00 | 01-JUL-00:10 |
August | 93091.76 | 01-AUG-19:10 | 16690.39 | 01-AUG-00:10 | 89674.66 | 01-AUG-06:10 | 40537.60 | 01-AUG-06:19 | 85614.72 | 10-AUG-18:19 | 18521.92 | 11-AUG-16:00 | 0.00 | 01-AUG-00:10 |
September | 93091.76 | 01-SEP-19:10 | 16690.39 | 01-SEP-00:10 | 89674.66 | 01-SEP-06:10 | 40537.60 | 01-SEP-06:19 | 84595.74 | 04-SEP-15:20 | 18362.41 | 10-SEP-18:10 | 0.00 | 01-SEP-00:10 |
October | 93091.76 | 02-OCT-19:10 | 16690.39 | 01-OCT-00:10 | 89674.66 | 02-OCT-06:10 | 40537.60 | 02-OCT-06:19 | 84168.90 | 19-OCT-15:20 | 17549.81 | 07-OCT-10:39 | 0.00 | 01-OCT-00:10 |
November | 93091.76 | 01-NOV-19:10 | 16690.39 | 01-NOV-00:10 | 89674.66 | 01-NOV-06:10 | 40537.60 | 01-NOV-06:19 | 78638.74 | 01-NOV-15:09 | 16430.83 | 01-NOV-10:50 | 0.00 | 01-NOV-00:10 |
December | 93091.76 | 01-DEC-20:10 | 16690.39 | 01-DEC-00:10 | 89674.66 | 01-DEC-07:10 | 40537.60 | 01-DEC-07:19 | 72587.45 | 08-DEC-16:10 | 15816.07 | 05-DEC-17:19 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 93091.76 | 16690.39 | 89674.66 | 40537.60 | 72195.69 | 15423.04 | 0.00 | |||||||
Maximum of Months | 93091.76 | 16690.39 | 89674.66 | 40537.60 | 85614.72 | 18680.89 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY {Maximum} [W] | HEATRECOVERY:ELECTRICITY {TIMESTAMP} | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 174172.80 | 29-JAN-16:10 | 0.00 | 0.00 | 18408.03 | 01-JAN-02:39 | 4739.33 | 02-JAN-07:10 | 0.00 |
February | 223267.44 | 07-FEB-16:10 | 0.00 | 0.00 | 18408.03 | 01-FEB-03:49 | 4739.38 | 22-FEB-07:10 | 0.00 |
March | 231668.49 | 01-MAR-17:00 | 0.00 | 0.00 | 18408.03 | 01-MAR-00:10 | 4739.18 | 17-MAR-06:10 | 0.00 |
April | 307496.88 | 30-APR-15:09 | 0.00 | 0.00 | 18408.03 | 01-APR-00:10 | 4738.75 | 06-APR-18:10 | 0.00 |
May | 397730.47 | 30-MAY-18:10 | 0.00 | 0.00 | 18408.03 | 01-MAY-00:10 | 4738.72 | 30-MAY-18:10 | 0.00 |
June | 432217.56 | 04-JUN-16:19 | 0.00 | 0.00 | 18408.03 | 01-JUN-00:10 | 4738.71 | 15-JUN-18:10 | 0.00 |
July | 502315.74 | 30-JUL-15:00 | 0.00 | 0.00 | 18408.03 | 01-JUL-00:10 | 4738.75 | 13-JUL-18:10 | 0.00 |
August | 552381.45 | 10-AUG-15:00 | 0.00 | 0.00 | 18408.03 | 01-AUG-00:10 | 4738.64 | 24-AUG-18:10 | 0.00 |
September | 465724.81 | 07-SEP-15:20 | 0.00 | 0.00 | 18408.03 | 01-SEP-00:10 | 4738.78 | 29-SEP-06:10 | 0.00 |
October | 386020.84 | 07-OCT-15:20 | 0.00 | 0.00 | 18408.03 | 01-OCT-00:10 | 4738.94 | 24-OCT-06:10 | 0.00 |
November | 319527.29 | 01-NOV-15:20 | 0.00 | 0.00 | 18408.03 | 01-NOV-00:10 | 4738.72 | 16-NOV-19:10 | 0.00 |
December | 214436.61 | 05-DEC-16:10 | 0.00 | 0.00 | 18408.03 | 01-DEC-08:50 | 4739.37 | 06-DEC-07:10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 174172.80 | 0.00 | 0.00 | 18408.03 | 4738.64 | 0.00 | |||
Maximum of Months | 552381.45 | 0.00 | 0.00 | 18408.03 | 4739.38 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 496060.77 | 29-JAN-20:10 | 87949.43 | 87485.24 | 16690.39 | 32961.22 | 68378.55 | 15058.94 | 0.00 | 163087.41 | 0.00 |
February | 532176.61 | 08-FEB-20:00 | 93091.76 | 88971.67 | 16690.39 | 33025.38 | 69819.91 | 15543.63 | 0.00 | 189964.56 | 0.00 |
March | 553812.36 | 28-MAR-19:10 | 93091.76 | 88971.67 | 16690.39 | 33012.66 | 70305.18 | 15739.15 | 0.00 | 211294.77 | 0.00 |
April | 610759.01 | 30-APR-18:10 | 82807.27 | 76644.19 | 0.00 | 32602.97 | 77509.47 | 16434.64 | 0.00 | 299469.71 | 0.00 |
May | 716083.88 | 30-MAY-18:10 | 82800.17 | 79617.06 | 0.00 | 32686.23 | 80876.67 | 16852.17 | 0.00 | 397730.47 | 0.00 |
June | 744866.69 | 27-JUN-19:00 | 93091.76 | 88971.67 | 16690.39 | 33025.38 | 75430.83 | 16823.48 | 0.00 | 396413.88 | 0.00 |
July | 800688.13 | 19-JUL-19:10 | 93091.76 | 88971.67 | 16690.39 | 33012.66 | 79139.52 | 17863.55 | 0.00 | 446969.50 | 0.00 |
August | 842574.52 | 10-AUG-18:10 | 82800.17 | 79617.06 | 0.00 | 32686.23 | 84299.57 | 18315.36 | 0.00 | 518776.18 | 0.00 |
September | 767241.58 | 08-SEP-18:10 | 82800.17 | 79617.06 | 0.00 | 32686.23 | 80755.08 | 17962.02 | 0.00 | 447894.10 | 0.00 |
October | 712743.73 | 07-OCT-18:10 | 82807.27 | 76644.19 | 16690.39 | 32608.13 | 78172.25 | 17403.62 | 0.00 | 383179.18 | 0.00 |
November | 620502.37 | 01-NOV-18:10 | 82800.17 | 79617.06 | 16690.39 | 32686.23 | 75722.55 | 16206.27 | 0.00 | 290694.87 | 0.00 |
December | 538770.29 | 05-DEC-20:10 | 93091.76 | 88971.67 | 16690.39 | 33012.66 | 66720.66 | 15696.05 | 0.00 | 200024.57 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 496060.77 | 82800.17 | 76644.19 | 0.00 | 32602.97 | 66720.66 | 15058.94 | 0.00 | 163087.41 | 0.00 | |
Maximum of Months | 842574.52 | 93091.76 | 88971.67 | 16690.39 | 33025.38 | 84299.57 | 18315.36 | 0.00 | 518776.18 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 104248.32 | 02-JAN-18:10 | 0.00 | 86877.92 | 30-JAN-11:39 | 0.00 | 221365.59 | 12-JAN-21:40 | 0.00 |
February | 104248.32 | 01-FEB-18:10 | 0.00 | 92486.62 | 21-FEB-11:39 | 0.00 | 217773.17 | 01-FEB-18:19 | 0.00 |
March | 104248.32 | 01-MAR-18:10 | 0.00 | 94309.14 | 20-MAR-10:39 | 0.00 | 215489.51 | 01-MAR-21:19 | 0.00 |
April | 104248.32 | 01-APR-17:10 | 0.00 | 91045.36 | 05-APR-10:39 | 0.00 | 211184.78 | 04-APR-20:00 | 0.00 |
May | 104248.32 | 01-MAY-17:10 | 0.00 | 81105.88 | 01-MAY-10:39 | 0.00 | 207055.81 | 01-MAY-20:00 | 0.00 |
June | 104248.32 | 01-JUN-17:10 | 0.00 | 75575.03 | 30-JUN-10:39 | 0.00 | 202245.15 | 02-JUN-17:30 | 0.00 |
July | 104248.32 | 01-JUL-17:10 | 0.00 | 71812.98 | 03-JUL-10:39 | 0.00 | 199982.44 | 19-JUL-20:40 | 0.00 |
August | 104248.32 | 01-AUG-17:10 | 0.00 | 67886.90 | 01-AUG-10:39 | 0.00 | 203261.67 | 30-AUG-20:30 | 0.00 |
September | 104248.32 | 01-SEP-17:10 | 0.00 | 63428.87 | 25-SEP-10:39 | 0.00 | 207615.95 | 29-SEP-20:49 | 0.00 |
October | 104248.32 | 02-OCT-17:10 | 0.00 | 60019.00 | 30-OCT-10:39 | 0.00 | 212435.53 | 31-OCT-20:30 | 0.00 |
November | 104248.32 | 01-NOV-17:10 | 0.00 | 70572.72 | 29-NOV-11:39 | 0.00 | 215912.89 | 30-NOV-21:00 | 0.00 |
December | 104248.32 | 01-DEC-18:10 | 0.00 | 78709.23 | 21-DEC-11:39 | 0.00 | 218610.15 | 26-DEC-18:10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 104248.32 | 0.00 | 60019.00 | 0.00 | 199982.44 | 0.00 | |||
Maximum of Months | 104248.32 | 0.00 | 94309.14 | 0.00 | 221365.59 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.72 | 0.17 | 21.72 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.71 | 0.17 | 21.71 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.67 | 0.17 | 21.67 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.72 | 0.33 | 21.72 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.83 | 21.71 | 0.83 | 21.71 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.72 | 0.33 | 21.72 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.73 | 0.17 | 21.73 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.72 | 0.33 | 21.72 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.70 | 0.33 | 21.70 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.68 | 0.17 | 21.68 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 1.00 | 21.71 | 1.00 | 21.71 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.73 | 0.33 | 21.73 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.68 | 0.33 | 21.68 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.72 | 0.50 | 21.72 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.73 | 0.67 | 21.73 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 21.68 | 4.00 | 21.68 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 21.69 | 3.67 | 21.69 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.67 | 0.17 | 21.67 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.72 | 0.33 | 21.72 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 9.67 | 21.69 | 9.67 | 21.69 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 21.73 | 4.00 | 21.73 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.69 | 0.17 | 21.69 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.70 | 0.17 | 21.70 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.33 | 21.69 | 0.33 | 21.69 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.70 | 0.17 | 21.70 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.72 | 0.17 | 21.72 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.68 | 0.33 | 21.68 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.50 | 21.70 | 0.50 | 21.70 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.72 | 0.33 | 21.72 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.69 | 0.17 | 21.69 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.75 | 0.67 | 21.75 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.77 | 0.67 | 21.77 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.81 | 0.33 | 21.81 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.68 | 0.17 | 21.68 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.80 | 0.33 | 21.80 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 2.33 | 21.76 | 2.33 | 21.76 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.81 | 0.67 | 21.81 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.78 | 0.67 | 21.78 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.77 | 1.00 | 21.77 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.74 | 0.67 | 21.74 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.69 | 0.33 | 21.69 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 2.67 | 21.75 | 2.67 | 21.75 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.78 | 1.00 | 21.78 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.71 | 0.17 | 21.71 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.72 | 0.50 | 21.72 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 21.76 | 1.83 | 21.76 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.72 | 0.17 | 21.72 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 2.67 | 21.75 | 2.67 | 21.75 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 21.76 | 1.83 | 21.76 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.22 | 0.00 | 21.22 | 0.00 | 21.22 |
February | 672.00 | 21.10 | 0.00 | 21.10 | 0.00 | 21.10 |
March | 744.00 | 21.04 | 0.00 | 21.04 | 0.00 | 21.04 |
April | 720.00 | 21.02 | 0.00 | 21.02 | 0.00 | 21.02 |
May | 744.00 | 21.02 | 0.00 | 21.02 | 0.00 | 21.02 |
June | 720.00 | 21.04 | 0.00 | 21.04 | 0.00 | 21.04 |
July | 744.00 | 21.09 | 0.00 | 21.09 | 0.00 | 21.09 |
August | 744.00 | 21.24 | 0.00 | 21.24 | 0.00 | 21.24 |
September | 720.00 | 21.32 | 0.00 | 21.32 | 0.00 | 21.32 |
October | 744.00 | 21.48 | 0.00 | 21.48 | 0.00 | 21.48 |
November | 720.00 | 21.57 | 0.00 | 21.57 | 0.00 | 21.57 |
December | 744.00 | 21.39 | 0.00 | 21.39 | 0.00 | 21.39 |
Annual Sum or Average | 8760.00 | 21.21 | 0.00 | 21.21 | 0.00 | 21.21 |
Minimum of Months | 672.00 | 21.02 | 0.00 | 21.02 | 0.00 | 21.02 |
Maximum of Months | 744.00 | 21.57 | 0.00 | 21.57 | 0.00 | 21.57 |
Report: ComfortReportSimple55Monthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.01 | 0.00 | 21.01 | 0.00 | 21.01 |
February | 672.00 | 21.03 | 0.00 | 21.03 | 0.00 | 21.03 |
March | 744.00 | 21.03 | 0.00 | 21.03 | 0.00 | 21.03 |
April | 720.00 | 21.03 | 0.00 | 21.03 | 0.00 | 21.03 |
May | 744.00 | 21.09 | 0.00 | 21.09 | 0.00 | 21.09 |
June | 720.00 | 21.13 | 0.00 | 21.13 | 0.00 | 21.13 |
July | 743.33 | 21.28 | 0.00 | 21.28 | 0.00 | 21.28 |
August | 723.17 | 21.39 | 0.00 | 21.39 | 0.00 | 21.39 |
September | 669.83 | 21.25 | 0.83 | 21.25 | 0.00 | 21.25 |
October | 700.83 | 21.21 | 0.00 | 21.21 | 0.00 | 21.21 |
November | 712.83 | 21.15 | 0.00 | 21.15 | 0.00 | 21.15 |
December | 744.00 | 21.04 | 0.00 | 21.04 | 0.00 | 21.04 |
Annual Sum or Average | 8638.00 | 21.14 | 0.83 | 21.14 | 0.00 | 21.14 |
Minimum of Months | 669.83 | 21.01 | 0.00 | 21.01 | 0.00 | 21.01 |
Maximum of Months | 744.00 | 21.39 | 0.83 | 21.39 | 0.00 | 21.39 |
Report: ComfortReportSimple55Monthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.04 | 0.00 | 21.04 | 0.00 | 21.04 |
February | 672.00 | 21.06 | 0.00 | 21.06 | 0.00 | 21.06 |
March | 744.00 | 21.09 | 0.00 | 21.09 | 0.00 | 21.09 |
April | 720.00 | 21.13 | 0.00 | 21.13 | 0.00 | 21.13 |
May | 744.00 | 21.26 | 0.00 | 21.26 | 0.00 | 21.26 |
June | 720.00 | 21.32 | 0.00 | 21.32 | 0.00 | 21.32 |
July | 744.00 | 21.39 | 0.00 | 21.39 | 0.00 | 21.39 |
August | 744.00 | 21.43 | 0.00 | 21.43 | 0.00 | 21.43 |
September | 720.00 | 21.32 | 0.00 | 21.32 | 0.00 | 21.32 |
October | 744.00 | 21.22 | 0.00 | 21.22 | 0.00 | 21.22 |
November | 720.00 | 21.12 | 0.00 | 21.12 | 0.00 | 21.12 |
December | 744.00 | 21.06 | 0.00 | 21.06 | 0.00 | 21.06 |
Annual Sum or Average | 8760.00 | 21.20 | 0.00 | 21.20 | 0.00 | 21.20 |
Minimum of Months | 672.00 | 21.04 | 0.00 | 21.04 | 0.00 | 21.04 |
Maximum of Months | 744.00 | 21.43 | 0.00 | 21.43 | 0.00 | 21.43 |
Report: ComfortReportSimple55Monthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.00 | 0.00 | 21.00 | 0.00 | 21.00 |
February | 672.00 | 21.00 | 0.00 | 21.00 | 0.00 | 21.00 |
March | 744.00 | 21.02 | 0.00 | 21.02 | 0.00 | 21.02 |
April | 720.00 | 21.05 | 0.00 | 21.05 | 0.00 | 21.05 |
May | 744.00 | 21.17 | 0.00 | 21.17 | 0.00 | 21.17 |
June | 720.00 | 21.29 | 0.00 | 21.29 | 0.00 | 21.29 |
July | 744.00 | 21.43 | 0.00 | 21.43 | 0.00 | 21.43 |
August | 744.00 | 21.47 | 0.00 | 21.47 | 0.00 | 21.47 |
September | 720.00 | 21.24 | 0.00 | 21.24 | 0.00 | 21.24 |
October | 744.00 | 21.10 | 0.00 | 21.10 | 0.00 | 21.10 |
November | 720.00 | 21.03 | 0.00 | 21.03 | 0.00 | 21.03 |
December | 744.00 | 21.01 | 0.00 | 21.01 | 0.00 | 21.01 |
Annual Sum or Average | 8760.00 | 21.15 | 0.00 | 21.15 | 0.00 | 21.15 |
Minimum of Months | 672.00 | 21.00 | 0.00 | 21.00 | 0.00 | 21.00 |
Maximum of Months | 744.00 | 21.47 | 0.00 | 21.47 | 0.00 | 21.47 |
Report: ComfortReportSimple55Monthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.00 | 0.00 | 21.00 | 0.00 | 21.00 |
February | 672.00 | 21.00 | 0.00 | 21.00 | 0.00 | 21.00 |
March | 744.00 | 21.00 | 0.00 | 21.00 | 0.00 | 21.00 |
April | 720.00 | 21.01 | 0.00 | 21.01 | 0.00 | 21.01 |
May | 744.00 | 21.10 | 0.00 | 21.10 | 0.00 | 21.10 |
June | 720.00 | 21.21 | 0.00 | 21.21 | 0.00 | 21.21 |
July | 744.00 | 21.36 | 0.00 | 21.36 | 0.00 | 21.36 |
August | 744.00 | 21.40 | 0.00 | 21.40 | 0.00 | 21.40 |
September | 720.00 | 21.16 | 0.00 | 21.16 | 0.00 | 21.16 |
October | 744.00 | 21.04 | 0.00 | 21.04 | 0.00 | 21.04 |
November | 720.00 | 21.00 | 0.00 | 21.00 | 0.00 | 21.00 |
December | 744.00 | 21.00 | 0.00 | 21.00 | 0.00 | 21.00 |
Annual Sum or Average | 8760.00 | 21.11 | 0.00 | 21.11 | 0.00 | 21.11 |
Minimum of Months | 672.00 | 21.00 | 0.00 | 21.00 | 0.00 | 21.00 |
Maximum of Months | 744.00 | 21.40 | 0.00 | 21.40 | 0.00 | 21.40 |
Report: ComfortReportSimple55Monthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 278.50 | 21.94 | 307.83 | 21.97 | 109.50 | 22.19 |
February | 186.67 | 22.28 | 320.67 | 22.01 | 101.33 | 22.24 |
March | 204.83 | 22.31 | 376.67 | 21.99 | 113.67 | 22.21 |
April | 155.67 | 22.58 | 474.50 | 21.83 | 108.17 | 22.04 |
May | 118.00 | 23.12 | 580.50 | 21.77 | 113.50 | 21.97 |
June | 111.83 | 23.18 | 610.17 | 21.72 | 111.83 | 21.92 |
July | 116.50 | 23.03 | 657.33 | 21.66 | 115.67 | 21.84 |
August | 117.17 | 23.12 | 668.67 | 21.68 | 117.17 | 21.87 |
September | 110.50 | 23.16 | 618.83 | 21.70 | 110.17 | 21.89 |
October | 124.00 | 23.02 | 573.83 | 21.77 | 111.67 | 21.97 |
November | 144.50 | 22.72 | 507.83 | 21.82 | 106.67 | 22.03 |
December | 203.50 | 22.27 | 370.00 | 21.97 | 109.33 | 22.19 |
Annual Sum or Average | 1871.67 | 22.60 | 6066.83 | 21.81 | 1328.67 | 22.02 |
Minimum of Months | 110.50 | 21.94 | 307.83 | 21.66 | 101.33 | 21.84 |
Maximum of Months | 278.50 | 23.18 | 668.67 | 22.01 | 117.17 | 22.24 |
Report: ComfortReportSimple55Monthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.05 | 0.00 | 21.05 | 0.00 | 21.05 |
February | 672.00 | 21.08 | 0.00 | 21.08 | 0.00 | 21.08 |
March | 744.00 | 21.12 | 0.00 | 21.12 | 0.00 | 21.12 |
April | 720.00 | 21.17 | 0.00 | 21.17 | 0.00 | 21.17 |
May | 734.67 | 21.31 | 0.00 | 21.31 | 0.00 | 21.31 |
June | 695.33 | 21.36 | 0.83 | 21.36 | 0.00 | 21.36 |
July | 657.83 | 21.39 | 10.33 | 21.41 | 0.00 | 21.41 |
August | 610.50 | 21.41 | 25.17 | 21.46 | 0.00 | 21.46 |
September | 653.33 | 21.45 | 4.00 | 21.45 | 0.00 | 21.45 |
October | 707.00 | 21.43 | 0.00 | 21.43 | 0.00 | 21.43 |
November | 715.00 | 21.26 | 0.00 | 21.26 | 0.00 | 21.26 |
December | 742.83 | 21.09 | 0.00 | 21.09 | 0.00 | 21.09 |
Annual Sum or Average | 8396.50 | 21.26 | 40.33 | 21.26 | 0.00 | 21.26 |
Minimum of Months | 610.50 | 21.05 | 0.00 | 21.05 | 0.00 | 21.05 |
Maximum of Months | 744.00 | 21.45 | 25.17 | 21.46 | 0.00 | 21.46 |
Report: ComfortReportSimple55Monthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.14 | 0.00 | 21.14 | 0.00 | 21.14 |
February | 672.00 | 21.17 | 0.00 | 21.17 | 0.00 | 21.17 |
March | 744.00 | 21.23 | 0.00 | 21.23 | 0.00 | 21.23 |
April | 720.00 | 21.28 | 0.00 | 21.28 | 0.00 | 21.28 |
May | 744.00 | 21.42 | 0.00 | 21.42 | 0.00 | 21.42 |
June | 720.00 | 21.49 | 0.00 | 21.49 | 0.00 | 21.49 |
July | 744.00 | 21.55 | 0.00 | 21.55 | 0.00 | 21.55 |
August | 744.00 | 21.59 | 0.00 | 21.59 | 0.00 | 21.59 |
September | 720.00 | 21.50 | 0.00 | 21.50 | 0.00 | 21.50 |
October | 744.00 | 21.41 | 0.00 | 21.41 | 0.00 | 21.41 |
November | 720.00 | 21.29 | 0.00 | 21.29 | 0.00 | 21.29 |
December | 744.00 | 21.18 | 0.00 | 21.18 | 0.00 | 21.18 |
Annual Sum or Average | 8760.00 | 21.35 | 0.00 | 21.35 | 0.00 | 21.35 |
Minimum of Months | 672.00 | 21.14 | 0.00 | 21.14 | 0.00 | 21.14 |
Maximum of Months | 744.00 | 21.59 | 0.00 | 21.59 | 0.00 | 21.59 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 725.50 | 21.56 | 0.00 | 21.56 | 0.00 | 21.56 |
February | 629.17 | 21.52 | 0.00 | 21.52 | 0.00 | 21.52 |
March | 682.67 | 21.53 | 0.00 | 21.53 | 0.00 | 21.53 |
April | 620.17 | 21.45 | 1.83 | 21.46 | 0.17 | 21.46 |
May | 588.50 | 21.32 | 30.67 | 21.42 | 0.33 | 21.42 |
June | 544.00 | 21.24 | 84.33 | 21.52 | 0.00 | 21.52 |
July | 545.50 | 21.19 | 113.50 | 21.56 | 0.00 | 21.56 |
August | 542.00 | 21.18 | 136.83 | 21.62 | 0.00 | 21.62 |
September | 541.83 | 21.23 | 96.50 | 21.55 | 0.00 | 21.55 |
October | 581.67 | 21.30 | 43.17 | 21.44 | 0.00 | 21.44 |
November | 600.33 | 21.40 | 5.50 | 21.41 | 0.17 | 21.41 |
December | 693.17 | 21.52 | 0.00 | 21.52 | 0.00 | 21.52 |
Annual Sum or Average | 7294.50 | 21.38 | 512.33 | 21.51 | 0.67 | 21.51 |
Minimum of Months | 541.83 | 21.18 | 0.00 | 21.41 | 0.00 | 21.41 |
Maximum of Months | 725.50 | 21.56 | 136.83 | 21.62 | 0.33 | 21.62 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 742.67 | 21.48 | 0.00 | 21.48 | 0.00 | 21.48 |
February | 662.33 | 21.54 | 0.00 | 21.54 | 0.00 | 21.54 |
March | 710.83 | 21.57 | 0.00 | 21.57 | 0.00 | 21.57 |
April | 635.00 | 21.49 | 1.00 | 21.50 | 0.17 | 21.50 |
May | 590.50 | 21.33 | 29.17 | 21.43 | 0.17 | 21.43 |
June | 541.00 | 21.23 | 86.67 | 21.52 | 0.00 | 21.52 |
July | 543.83 | 21.19 | 113.83 | 21.56 | 0.00 | 21.56 |
August | 543.17 | 21.18 | 124.17 | 21.58 | 0.00 | 21.58 |
September | 549.67 | 21.26 | 72.83 | 21.50 | 0.17 | 21.50 |
October | 608.33 | 21.37 | 16.50 | 21.43 | 0.00 | 21.43 |
November | 643.83 | 21.50 | 1.83 | 21.50 | 0.33 | 21.51 |
December | 734.00 | 21.54 | 0.00 | 21.54 | 0.00 | 21.54 |
Annual Sum or Average | 7505.17 | 21.40 | 446.00 | 21.51 | 0.83 | 21.51 |
Minimum of Months | 541.00 | 21.18 | 0.00 | 21.43 | 0.00 | 21.43 |
Maximum of Months | 742.67 | 21.57 | 124.17 | 21.58 | 0.33 | 21.58 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.40 | 0.00 | 21.40 | 0.00 | 21.40 |
February | 672.00 | 21.47 | 0.00 | 21.47 | 0.00 | 21.47 |
March | 744.00 | 21.55 | 0.00 | 21.55 | 0.00 | 21.55 |
April | 720.00 | 21.66 | 0.17 | 21.66 | 0.17 | 21.66 |
May | 741.33 | 21.71 | 0.00 | 21.71 | 0.00 | 21.71 |
June | 693.67 | 21.67 | 0.00 | 21.67 | 0.00 | 21.67 |
July | 691.17 | 21.61 | 0.00 | 21.61 | 0.00 | 21.61 |
August | 689.50 | 21.60 | 0.00 | 21.60 | 0.00 | 21.60 |
September | 705.67 | 21.68 | 0.00 | 21.68 | 0.00 | 21.68 |
October | 742.33 | 21.68 | 0.00 | 21.68 | 0.00 | 21.68 |
November | 720.00 | 21.62 | 0.00 | 21.62 | 0.00 | 21.62 |
December | 744.00 | 21.46 | 0.00 | 21.46 | 0.00 | 21.46 |
Annual Sum or Average | 8607.67 | 21.59 | 0.17 | 21.59 | 0.17 | 21.59 |
Minimum of Months | 672.00 | 21.40 | 0.00 | 21.40 | 0.00 | 21.40 |
Maximum of Months | 744.00 | 21.71 | 0.17 | 21.71 | 0.17 | 21.71 |
Report: ComfortReportSimple55Monthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 740.00 | 21.63 | 0.00 | 21.63 | 0.00 | 21.63 |
February | 655.00 | 21.62 | 0.00 | 21.62 | 0.00 | 21.62 |
March | 690.67 | 21.57 | 0.00 | 21.57 | 0.00 | 21.57 |
April | 599.17 | 21.41 | 0.17 | 21.41 | 0.17 | 21.41 |
May | 553.83 | 21.21 | 10.83 | 21.25 | 0.33 | 21.25 |
June | 530.00 | 21.19 | 72.33 | 21.45 | 0.00 | 21.45 |
July | 543.83 | 21.18 | 135.33 | 21.61 | 0.00 | 21.61 |
August | 541.00 | 21.17 | 170.50 | 21.69 | 0.00 | 21.69 |
September | 532.50 | 21.20 | 95.17 | 21.52 | 0.00 | 21.52 |
October | 560.83 | 21.23 | 26.83 | 21.33 | 0.00 | 21.33 |
November | 588.33 | 21.37 | 2.50 | 21.38 | 0.00 | 21.38 |
December | 711.17 | 21.59 | 0.00 | 21.59 | 0.00 | 21.59 |
Annual Sum or Average | 7246.33 | 21.38 | 513.67 | 21.51 | 0.50 | 21.51 |
Minimum of Months | 530.00 | 21.17 | 0.00 | 21.25 | 0.00 | 21.25 |
Maximum of Months | 740.00 | 21.63 | 170.50 | 21.69 | 0.33 | 21.69 |
Report: ComfortReportSimple55Monthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.50 | 0.00 | 21.50 | 0.00 | 21.50 |
February | 670.83 | 21.60 | 0.00 | 21.60 | 0.00 | 21.60 |
March | 724.50 | 21.63 | 0.00 | 21.63 | 0.00 | 21.63 |
April | 615.00 | 21.46 | 0.17 | 21.46 | 0.17 | 21.46 |
May | 553.33 | 21.21 | 10.67 | 21.25 | 0.00 | 21.25 |
June | 529.00 | 21.19 | 77.00 | 21.46 | 0.00 | 21.46 |
July | 542.50 | 21.18 | 136.17 | 21.61 | 0.00 | 21.61 |
August | 541.33 | 21.17 | 162.67 | 21.67 | 0.00 | 21.67 |
September | 533.33 | 21.20 | 47.17 | 21.37 | 0.00 | 21.37 |
October | 586.33 | 21.32 | 5.33 | 21.34 | 0.00 | 21.34 |
November | 670.33 | 21.60 | 0.17 | 21.60 | 0.17 | 21.60 |
December | 742.50 | 21.58 | 0.33 | 21.58 | 0.33 | 21.58 |
Annual Sum or Average | 7453.00 | 21.41 | 439.67 | 21.51 | 0.67 | 21.51 |
Minimum of Months | 529.00 | 21.17 | 0.00 | 21.25 | 0.00 | 21.25 |
Maximum of Months | 744.00 | 21.63 | 162.67 | 21.67 | 0.33 | 21.67 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.01 | 0.00 | 21.01 | 0.00 | 21.01 |
February | 672.00 | 21.04 | 0.00 | 21.04 | 0.00 | 21.04 |
March | 744.00 | 21.12 | 0.00 | 21.12 | 0.00 | 21.12 |
April | 720.00 | 21.28 | 0.00 | 21.28 | 0.00 | 21.28 |
May | 744.00 | 21.81 | 0.00 | 21.81 | 0.00 | 21.81 |
June | 720.00 | 22.02 | 0.00 | 22.02 | 0.00 | 22.02 |
July | 744.00 | 22.21 | 0.00 | 22.21 | 0.00 | 22.21 |
August | 744.00 | 22.30 | 0.00 | 22.30 | 0.00 | 22.30 |
September | 720.00 | 22.07 | 0.00 | 22.07 | 0.00 | 22.07 |
October | 744.00 | 21.81 | 0.00 | 21.81 | 0.00 | 21.81 |
November | 720.00 | 21.37 | 0.00 | 21.37 | 0.00 | 21.37 |
December | 744.00 | 21.04 | 0.00 | 21.04 | 0.00 | 21.04 |
Annual Sum or Average | 8760.00 | 21.59 | 0.00 | 21.59 | 0.00 | 21.59 |
Minimum of Months | 672.00 | 21.01 | 0.00 | 21.01 | 0.00 | 21.01 |
Maximum of Months | 744.00 | 22.30 | 0.00 | 22.30 | 0.00 | 22.30 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 696.67 | 21.49 | 0.00 | 21.49 | 0.00 | 21.49 |
February | 595.50 | 21.42 | 1.67 | 21.43 | 0.00 | 21.43 |
March | 637.33 | 21.40 | 10.67 | 21.43 | 0.50 | 21.44 |
April | 577.00 | 21.32 | 35.17 | 21.44 | 0.83 | 21.44 |
May | 558.33 | 21.24 | 108.50 | 21.58 | 0.67 | 21.58 |
June | 526.50 | 21.19 | 143.67 | 21.65 | 0.00 | 21.65 |
July | 534.50 | 21.17 | 172.17 | 21.70 | 0.00 | 21.70 |
August | 530.67 | 21.17 | 177.17 | 21.70 | 0.00 | 21.70 |
September | 527.00 | 21.20 | 151.83 | 21.67 | 0.00 | 21.67 |
October | 564.33 | 21.25 | 101.67 | 21.57 | 0.33 | 21.57 |
November | 579.33 | 21.33 | 45.67 | 21.48 | 0.67 | 21.48 |
December | 658.50 | 21.43 | 3.67 | 21.43 | 1.17 | 21.44 |
Annual Sum or Average | 6985.67 | 21.31 | 951.83 | 21.55 | 4.17 | 21.55 |
Minimum of Months | 526.50 | 21.17 | 0.00 | 21.43 | 0.00 | 21.43 |
Maximum of Months | 696.67 | 21.49 | 177.17 | 21.70 | 1.17 | 21.70 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 739.33 | 21.50 | 0.00 | 21.50 | 0.00 | 21.50 |
February | 635.50 | 21.49 | 0.00 | 21.49 | 0.00 | 21.49 |
March | 664.17 | 21.46 | 1.67 | 21.47 | 0.33 | 21.47 |
April | 586.83 | 21.35 | 25.00 | 21.43 | 0.67 | 21.43 |
May | 558.67 | 21.24 | 105.00 | 21.57 | 0.33 | 21.57 |
June | 523.67 | 21.19 | 146.00 | 21.65 | 0.00 | 21.65 |
July | 532.50 | 21.17 | 174.17 | 21.70 | 0.00 | 21.70 |
August | 531.33 | 21.17 | 174.50 | 21.70 | 0.00 | 21.70 |
September | 532.17 | 21.21 | 135.33 | 21.64 | 0.17 | 21.64 |
October | 581.83 | 21.29 | 67.00 | 21.50 | 0.50 | 21.50 |
November | 606.67 | 21.40 | 11.17 | 21.43 | 0.50 | 21.43 |
December | 702.17 | 21.48 | 1.33 | 21.48 | 1.33 | 21.48 |
Annual Sum or Average | 7194.83 | 21.34 | 841.17 | 21.55 | 3.83 | 21.55 |
Minimum of Months | 523.67 | 21.17 | 0.00 | 21.43 | 0.00 | 21.43 |
Maximum of Months | 739.33 | 21.50 | 174.50 | 21.70 | 1.33 | 21.70 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 658.00 | 21.46 | 0.00 | 21.46 | 0.00 | 21.46 |
February | 573.17 | 21.39 | 0.00 | 21.39 | 0.00 | 21.39 |
March | 640.17 | 21.42 | 0.33 | 21.42 | 0.33 | 21.42 |
April | 601.33 | 21.40 | 0.83 | 21.40 | 0.83 | 21.40 |
May | 586.67 | 21.32 | 7.83 | 21.34 | 0.67 | 21.34 |
June | 554.50 | 21.27 | 41.83 | 21.42 | 0.00 | 21.42 |
July | 560.33 | 21.24 | 93.50 | 21.54 | 0.00 | 21.54 |
August | 556.83 | 21.22 | 125.17 | 21.61 | 0.00 | 21.61 |
September | 546.83 | 21.25 | 113.67 | 21.61 | 0.00 | 21.61 |
October | 569.50 | 21.26 | 96.17 | 21.56 | 0.00 | 21.56 |
November | 569.17 | 21.32 | 29.67 | 21.42 | 0.33 | 21.42 |
December | 631.83 | 21.40 | 0.67 | 21.40 | 0.00 | 21.40 |
Annual Sum or Average | 7048.33 | 21.33 | 509.67 | 21.47 | 2.17 | 21.47 |
Minimum of Months | 546.83 | 21.22 | 0.00 | 21.34 | 0.00 | 21.34 |
Maximum of Months | 658.00 | 21.46 | 125.17 | 21.61 | 0.83 | 21.61 |
Report: ComfortReportSimple55Monthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 742.00 | 21.45 | 0.00 | 21.45 | 0.00 | 21.45 |
February | 659.00 | 21.49 | 0.00 | 21.49 | 0.00 | 21.49 |
March | 707.17 | 21.54 | 4.83 | 21.55 | 0.00 | 21.55 |
April | 646.00 | 21.59 | 23.50 | 21.64 | 0.00 | 21.64 |
May | 546.17 | 21.64 | 80.83 | 21.82 | 0.00 | 21.82 |
June | 407.67 | 21.55 | 138.17 | 21.90 | 0.00 | 21.90 |
July | 390.83 | 21.58 | 227.17 | 22.07 | 0.00 | 22.07 |
August | 380.50 | 21.53 | 241.17 | 22.07 | 0.00 | 22.07 |
September | 466.17 | 21.57 | 96.33 | 21.81 | 0.00 | 21.81 |
October | 622.17 | 21.62 | 47.83 | 21.72 | 0.00 | 21.72 |
November | 668.33 | 21.55 | 9.33 | 21.57 | 0.00 | 21.57 |
December | 729.83 | 21.48 | 0.00 | 21.48 | 0.00 | 21.48 |
Annual Sum or Average | 6965.83 | 21.54 | 869.17 | 21.70 | 0.00 | 21.70 |
Minimum of Months | 380.50 | 21.45 | 0.00 | 21.45 | 0.00 | 21.45 |
Maximum of Months | 742.00 | 21.64 | 241.17 | 22.07 | 0.00 | 22.07 |
Report: ComfortReportSimple55Monthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 719.83 | 21.46 | 0.00 | 21.46 | 0.00 | 21.46 |
February | 628.33 | 21.49 | 6.83 | 21.51 | 0.00 | 21.51 |
March | 672.17 | 21.56 | 24.17 | 21.60 | 0.00 | 21.60 |
April | 595.33 | 21.60 | 54.50 | 21.72 | 0.00 | 21.72 |
May | 454.67 | 21.61 | 134.50 | 21.92 | 0.00 | 21.92 |
June | 349.33 | 21.56 | 205.83 | 22.05 | 0.00 | 22.05 |
July | 306.33 | 21.55 | 292.33 | 22.19 | 0.00 | 22.19 |
August | 317.17 | 21.53 | 303.83 | 22.18 | 0.00 | 22.18 |
September | 398.67 | 21.54 | 167.67 | 21.94 | 0.00 | 21.94 |
October | 530.17 | 21.58 | 85.17 | 21.77 | 0.00 | 21.77 |
November | 624.00 | 21.55 | 37.00 | 21.63 | 0.00 | 21.63 |
December | 700.83 | 21.49 | 5.33 | 21.50 | 0.00 | 21.50 |
Annual Sum or Average | 6296.83 | 21.54 | 1317.17 | 21.77 | 0.00 | 21.77 |
Minimum of Months | 306.33 | 21.46 | 0.00 | 21.46 | 0.00 | 21.46 |
Maximum of Months | 719.83 | 21.61 | 303.83 | 22.19 | 0.00 | 22.19 |
Report: ComfortReportSimple55Monthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 595.50 | 23.07 | 571.00 | 23.22 | 463.17 | 23.34 |
February | 524.33 | 23.23 | 527.50 | 23.32 | 436.00 | 23.42 |
March | 564.83 | 23.37 | 594.33 | 23.40 | 490.17 | 23.50 |
April | 512.67 | 23.68 | 602.33 | 23.54 | 491.83 | 23.62 |
May | 523.67 | 23.88 | 689.83 | 23.56 | 523.67 | 23.65 |
June | 511.67 | 23.89 | 713.17 | 23.49 | 511.67 | 23.61 |
July | 531.00 | 23.90 | 739.17 | 23.51 | 531.00 | 23.63 |
August | 533.83 | 23.91 | 744.00 | 23.52 | 533.83 | 23.63 |
September | 508.83 | 23.88 | 702.00 | 23.50 | 508.83 | 23.61 |
October | 520.17 | 23.84 | 671.17 | 23.55 | 519.67 | 23.64 |
November | 516.33 | 23.65 | 597.17 | 23.53 | 492.83 | 23.60 |
December | 579.00 | 23.23 | 586.33 | 23.31 | 482.50 | 23.42 |
Annual Sum or Average | 6421.83 | 23.62 | 7738.00 | 23.46 | 5985.17 | 23.56 |
Minimum of Months | 508.83 | 23.07 | 527.50 | 23.22 | 436.00 | 23.34 |
Maximum of Months | 595.50 | 23.91 | 744.00 | 23.56 | 533.83 | 23.65 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.00 | 0.00 | 21.00 | 0.00 | 21.00 |
February | 672.00 | 21.01 | 0.00 | 21.01 | 0.00 | 21.01 |
March | 744.00 | 21.02 | 0.00 | 21.02 | 0.00 | 21.02 |
April | 720.00 | 21.07 | 0.00 | 21.07 | 0.00 | 21.07 |
May | 744.00 | 21.36 | 0.00 | 21.36 | 0.00 | 21.36 |
June | 720.00 | 21.56 | 0.00 | 21.56 | 0.00 | 21.56 |
July | 744.00 | 21.85 | 0.00 | 21.85 | 0.00 | 21.85 |
August | 744.00 | 21.90 | 0.00 | 21.90 | 0.00 | 21.90 |
September | 720.00 | 21.55 | 0.00 | 21.55 | 0.00 | 21.55 |
October | 744.00 | 21.25 | 0.00 | 21.25 | 0.00 | 21.25 |
November | 720.00 | 21.05 | 0.00 | 21.05 | 0.00 | 21.05 |
December | 744.00 | 21.00 | 0.00 | 21.00 | 0.00 | 21.00 |
Annual Sum or Average | 8760.00 | 21.30 | 0.00 | 21.30 | 0.00 | 21.30 |
Minimum of Months | 672.00 | 21.00 | 0.00 | 21.00 | 0.00 | 21.00 |
Maximum of Months | 744.00 | 21.90 | 0.00 | 21.90 | 0.00 | 21.90 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT PEOPLE
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.21674 | 55.07137 | -0.2077 | 5.99778 |
February | 672.00000 | 21.09801 | 59.35173 | -0.2213 | 6.07714 |
March | 744.00000 | 21.04094 | 57.38955 | -0.2589 | 6.45084 |
April | 720.00000 | 21.01922 | 59.23775 | -0.2605 | 6.50126 |
May | 744.00000 | 21.02159 | 59.99826 | -1.4329 | 47.28757 |
June | 720.00000 | 21.03898 | 61.42350 | -1.4084 | 45.97490 |
July | 744.00000 | 21.08739 | 61.24181 | -1.3795 | 44.44259 |
August | 744.00000 | 21.24051 | 61.08950 | -1.3106 | 40.87178 |
September | 720.00000 | 21.31533 | 60.98628 | -1.2796 | 39.33641 |
October | 744.00000 | 21.47670 | 59.63002 | -0.1011 | 5.31776 |
November | 720.00000 | 21.57440 | 60.42051 | -0.0730 | 5.18637 |
December | 744.00000 | 21.39131 | 58.98762 | -0.1339 | 5.44983 |
Annual Sum or Average | 8760.00000 | 21.21072 | 59.56039 | -0.6751 | 21.67258 |
Minimum of Months | 672.00000 | 21.01922 | 55.07137 | -1.4329 | 5.18637 |
Maximum of Months | 744.00000 | 21.57440 | 61.42350 | -0.0730 | 47.28757 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_1_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.00955 | 55.34884 | -0.2027 | 6.07628 |
February | 672.00000 | 21.03482 | 59.30558 | -0.1581 | 5.72784 |
March | 744.00000 | 21.02997 | 57.15080 | -0.1554 | 5.67503 |
April | 720.00000 | 21.03174 | 59.26184 | -0.1195 | 5.44187 |
May | 744.00000 | 21.09292 | 60.21200 | -1.1590 | 33.42413 |
June | 720.00000 | 21.13060 | 62.40195 | -1.1125 | 31.23017 |
July | 744.00000 | 21.27884 | 62.32978 | -1.0342 | 27.81635 |
August | 744.00000 | 21.40943 | 62.41175 | -0.9764 | 25.46918 |
September | 720.00000 | 21.31573 | 62.67188 | -1.0266 | 27.83096 |
October | 744.00000 | 21.27029 | 61.30750 | 0.00816 | 5.34367 |
November | 720.00000 | 21.15556 | 62.10567 | -0.0526 | 5.36951 |
December | 744.00000 | 21.04048 | 60.02083 | -0.1476 | 5.67798 |
Annual Sum or Average | 8760.00000 | 21.15085 | 60.37266 | -0.5136 | 15.48087 |
Minimum of Months | 672.00000 | 21.00955 | 55.34884 | -1.1590 | 5.34367 |
Maximum of Months | 744.00000 | 21.40943 | 62.67188 | 0.00816 | 33.42413 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_2_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.04162 | 56.11113 | -0.2307 | 6.19848 |
February | 672.00000 | 21.05582 | 60.04547 | -0.1979 | 5.88431 |
March | 744.00000 | 21.08998 | 57.76742 | -0.1938 | 5.88386 |
April | 720.00000 | 21.12958 | 59.59415 | -0.1645 | 5.71951 |
May | 744.00000 | 21.25730 | 60.14678 | -1.2455 | 37.67943 |
June | 720.00000 | 21.32340 | 61.87381 | -1.2049 | 35.69178 |
July | 744.00000 | 21.38654 | 61.92604 | -1.1749 | 34.25758 |
August | 744.00000 | 21.43268 | 62.25831 | -1.1523 | 33.20806 |
September | 720.00000 | 21.32229 | 62.67054 | -1.1966 | 35.30871 |
October | 744.00000 | 21.22474 | 61.76325 | -0.1119 | 5.39312 |
November | 720.00000 | 21.11932 | 62.86897 | -0.1454 | 5.51182 |
December | 744.00000 | 21.05589 | 60.75290 | -0.1924 | 5.83083 |
Annual Sum or Average | 8760.00000 | 21.20425 | 60.64109 | -0.6034 | 18.11975 |
Minimum of Months | 672.00000 | 21.04162 | 56.11113 | -1.2455 | 5.39312 |
Maximum of Months | 744.00000 | 21.43268 | 62.86897 | -0.1119 | 37.67943 |
Report: OccupantComfortDataSummaryMonthly
For: LAUNDRY_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.41047 | 52.95882 | 0.44068 | 11.59854 |
February | 672.00000 | 21.40817 | 56.82125 | 0.47267 | 12.12583 |
March | 744.00000 | 21.41177 | 54.68327 | 0.47696 | 12.28128 |
April | 720.00000 | 21.38739 | 56.54612 | 0.50120 | 12.64799 |
May | 744.00000 | 21.38167 | 57.40713 | -0.3144 | 11.66424 |
June | 720.00000 | 21.38274 | 59.01401 | -0.2916 | 11.32482 |
July | 744.00000 | 21.36192 | 59.18183 | -0.2870 | 10.90160 |
August | 744.00000 | 21.38152 | 59.52264 | -0.2711 | 10.94872 |
September | 720.00000 | 21.37680 | 59.65025 | -0.2968 | 11.26970 |
October | 744.00000 | 21.38486 | 58.70781 | 0.53104 | 13.13423 |
November | 720.00000 | 21.39842 | 59.68321 | 0.51541 | 12.84979 |
December | 744.00000 | 21.40306 | 57.49074 | 0.47460 | 12.06863 |
Annual Sum or Average | 8760.00000 | 21.39064 | 57.63376 | 0.16070 | 11.89810 |
Minimum of Months | 672.00000 | 21.36192 | 52.95882 | -0.3144 | 10.90160 |
Maximum of Months | 744.00000 | 21.41177 | 59.68321 | 0.53104 | 13.13423 |
Report: OccupantComfortDataSummaryMonthly
For: CAFE_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.04598 | 57.94206 | -0.1095 | 5.43507 |
February | 672.00000 | 21.08369 | 61.77973 | -0.0651 | 5.25517 |
March | 744.00000 | 21.12488 | 59.49267 | -0.0575 | 5.22442 |
April | 720.00000 | 21.17306 | 61.25889 | -0.0166 | 5.16069 |
May | 744.00000 | 21.32657 | 61.71644 | -1.0008 | 26.40976 |
June | 720.00000 | 21.39615 | 63.39597 | -0.9500 | 24.33418 |
July | 744.00000 | 21.50423 | 63.28403 | -0.8850 | 21.88297 |
August | 744.00000 | 21.58461 | 63.50444 | -0.8417 | 20.31854 |
September | 720.00000 | 21.51228 | 63.77936 | -0.8806 | 21.73964 |
October | 744.00000 | 21.45176 | 62.80067 | 0.11727 | 5.47431 |
November | 720.00000 | 21.26546 | 64.17082 | 0.04766 | 5.22874 |
December | 744.00000 | 21.08711 | 62.45839 | -0.0551 | 5.23111 |
Annual Sum or Average | 8760.00000 | 21.29762 | 62.12368 | -0.3935 | 12.68576 |
Minimum of Months | 672.00000 | 21.04598 | 57.94206 | -1.0008 | 5.16069 |
Maximum of Months | 744.00000 | 21.58461 | 64.17082 | 0.11727 | 26.40976 |
Report: OccupantComfortDataSummaryMonthly
For: LOBBY_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.13535 | 57.37328 | -0.1654 | 5.70193 |
February | 672.00000 | 21.16669 | 61.21321 | -0.1289 | 5.46204 |
March | 744.00000 | 21.22569 | 58.87983 | -0.1212 | 5.45914 |
April | 720.00000 | 21.28149 | 60.58882 | -0.0882 | 5.37643 |
May | 744.00000 | 21.42137 | 61.06866 | -1.1339 | 32.41596 |
June | 720.00000 | 21.48604 | 62.70894 | -1.0920 | 30.53051 |
July | 744.00000 | 21.55047 | 62.71858 | -1.0584 | 29.06139 |
August | 744.00000 | 21.58841 | 63.07645 | -1.0377 | 28.18503 |
September | 720.00000 | 21.49520 | 63.44250 | -1.0772 | 29.85634 |
October | 744.00000 | 21.41354 | 62.55161 | -0.0209 | 5.21218 |
November | 720.00000 | 21.29392 | 63.75847 | -0.0587 | 5.20109 |
December | 744.00000 | 21.17530 | 61.88090 | -0.1203 | 5.40688 |
Annual Sum or Average | 8760.00000 | 21.35392 | 61.59715 | -0.5109 | 15.71667 |
Minimum of Months | 672.00000 | 21.13535 | 57.37328 | -1.1339 | 5.20109 |
Maximum of Months | 744.00000 | 21.58841 | 63.75847 | -0.0209 | 32.41596 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.60168 | 55.21305 | -0.1222 | 6.01794 |
February | 672.00000 | 21.63241 | 57.35676 | -0.0805 | 5.86223 |
March | 744.00000 | 21.67420 | 54.01503 | -0.0614 | 5.86854 |
April | 720.00000 | 21.71353 | 54.06662 | -0.0181 | 5.85030 |
May | 744.00000 | 21.74392 | 52.92939 | -1.0157 | 28.32215 |
June | 720.00000 | 21.74951 | 55.01754 | -0.9741 | 26.62218 |
July | 744.00000 | 21.75376 | 55.66196 | -0.9421 | 25.35226 |
August | 744.00000 | 21.75451 | 55.96439 | -0.9284 | 24.85521 |
September | 720.00000 | 21.74834 | 55.88648 | -0.9671 | 26.45015 |
October | 744.00000 | 21.74006 | 54.91212 | 0.03883 | 5.89517 |
November | 720.00000 | 21.71723 | 55.78391 | -0.0100 | 5.87126 |
December | 744.00000 | 21.64020 | 58.03691 | -0.0749 | 5.86825 |
Annual Sum or Average | 8760.00000 | 21.70609 | 55.38998 | -0.4318 | 14.45349 |
Minimum of Months | 672.00000 | 21.60168 | 52.92939 | -1.0157 | 5.85030 |
Maximum of Months | 744.00000 | 21.75451 | 58.03691 | 0.03883 | 28.32215 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.47902 | 56.41224 | -0.1705 | 6.07365 |
February | 672.00000 | 21.56741 | 58.50044 | -0.1118 | 5.82525 |
March | 744.00000 | 21.64851 | 54.52806 | -0.0797 | 5.83059 |
April | 720.00000 | 21.70978 | 54.29254 | -0.0249 | 5.82483 |
May | 744.00000 | 21.74468 | 52.91308 | -1.0158 | 28.31665 |
June | 720.00000 | 21.75084 | 54.97746 | -0.9696 | 26.44711 |
July | 744.00000 | 21.75452 | 55.77767 | -0.9397 | 25.25610 |
August | 744.00000 | 21.75448 | 56.14160 | -0.9329 | 24.99422 |
September | 720.00000 | 21.74612 | 56.35571 | -0.9824 | 26.98451 |
October | 744.00000 | 21.73132 | 55.77734 | 0.02041 | 5.80245 |
November | 720.00000 | 21.69324 | 57.15759 | -0.0348 | 5.78821 |
December | 744.00000 | 21.56222 | 59.53426 | -0.1112 | 5.82887 |
Annual Sum or Average | 8760.00000 | 21.67892 | 56.01403 | -0.4482 | 14.46473 |
Minimum of Months | 672.00000 | 21.47902 | 52.91308 | -1.0158 | 5.78821 |
Maximum of Months | 744.00000 | 21.75452 | 59.53426 | 0.02041 | 28.31665 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT19_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 0.00000 | ||||
Minimum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_4_MULT19_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.39616 | 54.07617 | -0.2054 | 6.05138 |
February | 672.00000 | 21.46704 | 55.87526 | -0.1661 | 5.82216 |
March | 744.00000 | 21.55454 | 52.91226 | -0.1473 | 5.82408 |
April | 720.00000 | 21.65891 | 53.09000 | -0.1023 | 5.78520 |
May | 744.00000 | 21.71510 | 52.70471 | -1.1560 | 34.14279 |
June | 720.00000 | 21.72638 | 54.76708 | -1.1237 | 32.72249 |
July | 744.00000 | 21.73314 | 55.79289 | -1.1038 | 31.84516 |
August | 744.00000 | 21.73101 | 56.23003 | -1.1035 | 31.82961 |
September | 720.00000 | 21.71580 | 55.57298 | -1.1355 | 33.27164 |
October | 744.00000 | 21.68850 | 54.60943 | -0.0727 | 5.69348 |
November | 720.00000 | 21.61895 | 55.23915 | -0.1101 | 5.71707 |
December | 744.00000 | 21.45898 | 56.41515 | -0.1660 | 5.81522 |
Annual Sum or Average | 8760.00000 | 21.62268 | 54.76587 | -0.5518 | 17.11004 |
Minimum of Months | 672.00000 | 21.39616 | 52.70471 | -1.1560 | 5.69348 |
Maximum of Months | 744.00000 | 21.73314 | 56.41515 | -0.0727 | 34.14279 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_5_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.63548 | 54.78385 | -0.1154 | 5.98912 |
February | 672.00000 | 21.66120 | 56.96362 | -0.0761 | 5.84483 |
March | 744.00000 | 21.69237 | 53.72372 | -0.0621 | 5.87583 |
April | 720.00000 | 21.73099 | 53.67817 | -0.0133 | 5.88134 |
May | 744.00000 | 21.75230 | 53.11214 | -1.0056 | 27.94923 |
June | 720.00000 | 21.75479 | 55.02489 | -0.9713 | 26.54310 |
July | 744.00000 | 21.75722 | 55.59359 | -0.9393 | 25.27402 |
August | 744.00000 | 21.75797 | 55.92966 | -0.9259 | 24.78406 |
September | 720.00000 | 21.75344 | 55.93470 | -0.9638 | 26.33236 |
October | 744.00000 | 21.74869 | 55.14068 | 0.04441 | 5.91696 |
November | 720.00000 | 21.73277 | 55.64254 | -0.0067 | 5.87479 |
December | 744.00000 | 21.66335 | 57.69504 | -0.0724 | 5.85013 |
Annual Sum or Average | 8760.00000 | 21.72028 | 55.25679 | -0.4278 | 14.39294 |
Minimum of Months | 672.00000 | 21.63548 | 53.11214 | -1.0056 | 5.84483 |
Maximum of Months | 744.00000 | 21.75797 | 57.69504 | 0.04441 | 27.94923 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_6_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.50374 | 56.04847 | -0.1649 | 6.00118 |
February | 672.00000 | 21.59999 | 58.05502 | -0.1070 | 5.78229 |
March | 744.00000 | 21.67517 | 54.26368 | -0.0785 | 5.84261 |
April | 720.00000 | 21.72896 | 53.88706 | -0.0197 | 5.85676 |
May | 744.00000 | 21.75283 | 53.08824 | -1.0060 | 27.95023 |
June | 720.00000 | 21.75572 | 54.93070 | -0.9673 | 26.38690 |
July | 744.00000 | 21.75794 | 55.70202 | -0.9370 | 25.17811 |
August | 744.00000 | 21.75807 | 56.18084 | -0.9299 | 24.90092 |
September | 720.00000 | 21.75205 | 56.43983 | -0.9785 | 26.84444 |
October | 744.00000 | 21.74417 | 55.69056 | 0.02508 | 5.82189 |
November | 720.00000 | 21.71761 | 56.61675 | -0.0319 | 5.78770 |
December | 744.00000 | 21.57955 | 59.21292 | -0.1100 | 5.77764 |
Annual Sum or Average | 8760.00000 | 21.69410 | 55.82893 | -0.4443 | 14.39405 |
Minimum of Months | 672.00000 | 21.50374 | 53.08824 | -1.0060 | 5.77764 |
Maximum of Months | 744.00000 | 21.75807 | 59.21292 | 0.02508 | 27.95023 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.60727 | 55.74068 | -0.1161 | 6.15511 |
February | 672.00000 | 21.64071 | 57.76722 | -0.0673 | 5.97377 |
March | 744.00000 | 21.68009 | 54.27068 | -0.0425 | 5.98719 |
April | 720.00000 | 21.71818 | 53.97826 | 0.00743 | 5.99045 |
May | 744.00000 | 21.74782 | 52.61719 | -0.9686 | 26.68680 |
June | 720.00000 | 21.75291 | 54.53266 | -0.9252 | 24.96567 |
July | 744.00000 | 21.75682 | 55.14463 | -0.8884 | 23.56682 |
August | 744.00000 | 21.75724 | 55.41500 | -0.8770 | 23.18174 |
September | 720.00000 | 21.75086 | 55.42848 | -0.9231 | 24.99772 |
October | 744.00000 | 21.74244 | 54.59112 | 0.06344 | 6.07457 |
November | 720.00000 | 21.72087 | 55.80256 | 0.00878 | 5.98795 |
December | 744.00000 | 21.64586 | 58.38562 | -0.0638 | 5.96846 |
Annual Sum or Average | 8760.00000 | 21.71038 | 55.29001 | -0.4015 | 13.84044 |
Minimum of Months | 672.00000 | 21.60727 | 52.61719 | -0.9686 | 5.96846 |
Maximum of Months | 744.00000 | 21.75724 | 58.38562 | 0.06344 | 26.68680 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.51053 | 56.90384 | -0.1614 | 6.19876 |
February | 672.00000 | 21.59306 | 58.86673 | -0.0962 | 5.92301 |
March | 744.00000 | 21.66461 | 54.76173 | -0.0590 | 5.93948 |
April | 720.00000 | 21.71554 | 54.21736 | 0.00100 | 5.95540 |
May | 744.00000 | 21.74864 | 52.62536 | -0.9686 | 26.67278 |
June | 720.00000 | 21.75426 | 54.56227 | -0.9204 | 24.78740 |
July | 744.00000 | 21.75764 | 55.18418 | -0.8865 | 23.49369 |
August | 744.00000 | 21.75725 | 55.55060 | -0.8816 | 23.31225 |
September | 720.00000 | 21.74919 | 55.78309 | -0.9390 | 25.50606 |
October | 744.00000 | 21.73529 | 55.40986 | 0.04496 | 5.95190 |
November | 720.00000 | 21.70077 | 57.13057 | -0.0158 | 5.87947 |
December | 744.00000 | 21.58675 | 59.89184 | -0.0975 | 5.92154 |
Annual Sum or Average | 8760.00000 | 21.68981 | 55.88827 | -0.4170 | 13.84081 |
Minimum of Months | 672.00000 | 21.51053 | 52.62536 | -0.9686 | 5.87947 |
Maximum of Months | 744.00000 | 21.75764 | 59.89184 | 0.04496 | 26.67278 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT9_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.67219 | 53.43762 | -0.0842 | 6.10332 |
February | 672.00000 | 21.67551 | 55.59434 | -0.0571 | 5.99786 |
March | 744.00000 | 21.69015 | 53.19585 | -0.0551 | 5.98870 |
April | 720.00000 | 21.71662 | 53.50659 | -0.0261 | 5.93765 |
May | 744.00000 | 21.74175 | 52.87648 | -1.0441 | 29.59331 |
June | 720.00000 | 21.74698 | 54.64153 | -1.0125 | 28.24702 |
July | 744.00000 | 21.75286 | 54.97777 | -0.9762 | 26.76647 |
August | 744.00000 | 21.75426 | 55.11158 | -0.9605 | 26.20009 |
September | 720.00000 | 21.74999 | 54.82259 | -0.9811 | 27.18615 |
October | 744.00000 | 21.74788 | 53.72544 | 0.04481 | 6.03855 |
November | 720.00000 | 21.73777 | 54.30635 | 0.01060 | 6.03179 |
December | 744.00000 | 21.68945 | 55.49006 | -0.0467 | 6.00273 |
Annual Sum or Average | 8760.00000 | 21.72318 | 54.29647 | -0.4347 | 15.06166 |
Minimum of Months | 672.00000 | 21.67219 | 52.87648 | -1.0441 | 5.93765 |
Maximum of Months | 744.00000 | 21.75426 | 55.59434 | 0.04481 | 29.59331 |
Report: OccupantComfortDataSummaryMonthly
For: BANQUET_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.45037 | 57.43366 | -0.0230 | 5.32895 |
February | 672.00000 | 21.51011 | 61.07055 | 0.02728 | 5.31728 |
March | 744.00000 | 21.60139 | 58.69313 | 0.05234 | 5.40309 |
April | 720.00000 | 21.71026 | 60.07764 | 0.10933 | 5.63753 |
May | 744.00000 | 21.93239 | 60.18744 | -0.8090 | 19.49476 |
June | 720.00000 | 22.03886 | 61.42610 | -0.7464 | 17.42803 |
July | 744.00000 | 22.12145 | 61.26563 | -0.7015 | 16.04939 |
August | 744.00000 | 22.12223 | 61.70029 | -0.6987 | 16.03598 |
September | 720.00000 | 21.96200 | 62.33808 | -0.7788 | 18.50282 |
October | 744.00000 | 21.80466 | 61.92067 | 0.15973 | 5.92212 |
November | 720.00000 | 21.63594 | 63.45146 | 0.09826 | 5.51804 |
December | 744.00000 | 21.50024 | 61.75216 | 0.02631 | 5.30292 |
Annual Sum or Average | 8760.00000 | 21.78413 | 60.93237 | -0.2755 | 10.52364 |
Minimum of Months | 672.00000 | 21.45037 | 57.43366 | -0.8090 | 5.30292 |
Maximum of Months | 744.00000 | 22.12223 | 63.45146 | 0.15973 | 19.49476 |
Report: OccupantComfortDataSummaryMonthly
For: DINING_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.50116 | 57.07283 | 0.01904 | 5.35584 |
February | 672.00000 | 21.56730 | 60.67786 | 0.07080 | 5.43115 |
March | 744.00000 | 21.67081 | 58.26833 | 0.09892 | 5.57072 |
April | 720.00000 | 21.79291 | 59.60210 | 0.15904 | 5.92348 |
May | 744.00000 | 22.01725 | 59.69619 | -0.7383 | 17.16452 |
June | 720.00000 | 22.11485 | 60.94838 | -0.6798 | 15.39195 |
July | 744.00000 | 22.18121 | 60.83675 | -0.6421 | 14.32888 |
August | 744.00000 | 22.17742 | 61.28153 | -0.6413 | 14.37450 |
September | 720.00000 | 22.03171 | 61.87229 | -0.7151 | 16.46390 |
October | 744.00000 | 21.88161 | 61.44411 | 0.20695 | 6.27975 |
November | 720.00000 | 21.70553 | 63.00315 | 0.14444 | 5.76573 |
December | 744.00000 | 21.55703 | 61.35669 | 0.06969 | 5.41443 |
Annual Sum or Average | 8760.00000 | 21.85155 | 60.49426 | -0.2225 | 9.81252 |
Minimum of Months | 672.00000 | 21.50116 | 57.07283 | -0.7383 | 5.35584 |
Maximum of Months | 744.00000 | 22.18121 | 63.00315 | 0.20695 | 17.16452 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.83803 | 54.29346 | 0.94743 | 28.79568 |
February | 672.00000 | 22.89069 | 57.62831 | 0.99817 | 30.68051 |
March | 744.00000 | 22.94971 | 55.52827 | 1.02340 | 31.73162 |
April | 720.00000 | 23.03567 | 56.99716 | 1.08725 | 34.32147 |
May | 744.00000 | 23.15092 | 57.36182 | 0.56773 | 21.91626 |
June | 720.00000 | 23.18582 | 58.63727 | 0.60856 | 22.58308 |
July | 744.00000 | 23.21864 | 58.59827 | 0.64409 | 23.24306 |
August | 744.00000 | 23.23583 | 58.92001 | 0.65588 | 23.40364 |
September | 720.00000 | 23.16815 | 59.26131 | 0.59605 | 22.31719 |
October | 744.00000 | 23.10273 | 58.71926 | 1.14127 | 36.42092 |
November | 720.00000 | 23.01390 | 59.83759 | 1.08441 | 34.11800 |
December | 744.00000 | 22.88636 | 58.22654 | 0.99904 | 30.64752 |
Annual Sum or Average | 8760.00000 | 23.05724 | 57.82649 | 0.86186 | 28.32922 |
Minimum of Months | 672.00000 | 22.83803 | 54.29346 | 0.56773 | 21.91626 |
Maximum of Months | 744.00000 | 23.23583 | 59.83759 | 1.14127 | 36.42092 |
Report: OccupantComfortDataSummaryMonthly
For: STORAGE_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.99999 | 54.78659 | -0.3082 | 7.03596 |
February | 672.00000 | 21.00011 | 58.88241 | -0.2774 | 6.63158 |
March | 744.00000 | 21.00147 | 56.70122 | -0.2796 | 6.66859 |
April | 720.00000 | 21.00957 | 58.91992 | -0.2532 | 6.41327 |
May | 744.00000 | 21.09817 | 59.90914 | -1.3737 | 44.14758 |
June | 720.00000 | 21.20996 | 62.10800 | -1.3141 | 41.04416 |
July | 744.00000 | 21.35815 | 62.17977 | -1.2585 | 38.21946 |
August | 744.00000 | 21.39828 | 62.64703 | -1.2408 | 37.33351 |
September | 720.00000 | 21.16206 | 63.36064 | -1.3249 | 41.63118 |
October | 744.00000 | 21.04144 | 61.93978 | -0.2123 | 5.97380 |
November | 720.00000 | 21.00444 | 62.26860 | -0.2359 | 6.16764 |
December | 744.00000 | 21.00018 | 59.69042 | -0.2710 | 6.55546 |
Annual Sum or Average | 8760.00000 | 21.10798 | 60.27916 | -0.6983 | 20.73243 |
Minimum of Months | 672.00000 | 20.99999 | 54.78659 | -1.3737 | 5.97380 |
Maximum of Months | 744.00000 | 21.39828 | 63.36064 | -0.2123 | 44.14758 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.00868 | 56.72704 | -0.3062 | 7.00853 |
February | 672.00000 | 21.04059 | 60.64660 | -0.2714 | 6.56920 |
March | 744.00000 | 21.11685 | 58.23736 | -0.2617 | 6.48667 |
April | 720.00000 | 21.28334 | 59.72934 | -0.2075 | 5.99654 |
May | 744.00000 | 21.80993 | 59.00235 | -1.1891 | 34.78720 |
June | 720.00000 | 22.02069 | 60.34402 | -1.1045 | 30.75986 |
July | 744.00000 | 22.21057 | 60.05018 | -1.0376 | 27.78560 |
August | 744.00000 | 22.30381 | 60.24728 | -1.0026 | 26.27631 |
September | 720.00000 | 22.06807 | 61.01660 | -1.0819 | 29.77970 |
October | 744.00000 | 21.80620 | 60.54147 | -0.0636 | 5.13449 |
November | 720.00000 | 21.37384 | 62.61138 | -0.1654 | 5.62287 |
December | 744.00000 | 21.03865 | 61.40739 | -0.2667 | 6.51355 |
Annual Sum or Average | 8760.00000 | 21.59356 | 60.03219 | -0.5817 | 16.11636 |
Minimum of Months | 672.00000 | 21.00868 | 56.72704 | -1.1891 | 5.13449 |
Maximum of Months | 744.00000 | 22.30381 | 62.61138 | -0.0636 | 34.78720 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.00049 | 55.32536 | -0.2851 | 6.77028 |
February | 672.00000 | 21.00718 | 59.30168 | -0.2477 | 6.32226 |
March | 744.00000 | 21.02163 | 57.08764 | -0.2433 | 6.29294 |
April | 720.00000 | 21.07022 | 58.91531 | -0.2035 | 5.95583 |
May | 744.00000 | 21.35534 | 58.92441 | -1.2335 | 37.02655 |
June | 720.00000 | 21.56451 | 60.13444 | -1.1434 | 32.63678 |
July | 744.00000 | 21.84523 | 59.40414 | -1.0404 | 27.98692 |
August | 744.00000 | 21.89825 | 59.70079 | -1.0188 | 27.04800 |
September | 720.00000 | 21.54802 | 60.95887 | -1.1450 | 32.80629 |
October | 744.00000 | 21.24758 | 60.80037 | -0.1281 | 5.42772 |
November | 720.00000 | 21.05427 | 62.19264 | -0.1914 | 5.80018 |
December | 744.00000 | 21.00291 | 60.02555 | -0.2455 | 6.29911 |
Annual Sum or Average | 8760.00000 | 21.30363 | 59.38576 | -0.5958 | 16.75450 |
Minimum of Months | 672.00000 | 21.00049 | 55.32536 | -1.2335 | 5.42772 |
Maximum of Months | 744.00000 | 21.89825 | 62.19264 | -0.1281 | 37.02655 |
Report: OccupantComfortDataSummaryMonthly
For: MECH_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.00053 | 54.59017 | -0.2892 | 6.80417 |
February | 672.00000 | 21.00491 | 58.65087 | -0.2576 | 6.41818 |
March | 744.00000 | 21.01929 | 56.42628 | -0.2568 | 6.42891 |
April | 720.00000 | 21.04755 | 58.51817 | -0.2264 | 6.17002 |
May | 744.00000 | 21.17227 | 59.31801 | -1.3260 | 41.69658 |
June | 720.00000 | 21.29307 | 61.35242 | -1.2641 | 38.53768 |
July | 744.00000 | 21.42850 | 61.40748 | -1.2123 | 35.97299 |
August | 744.00000 | 21.46741 | 61.85115 | -1.1949 | 35.12636 |
September | 720.00000 | 21.23589 | 62.57710 | -1.2786 | 39.29445 |
October | 744.00000 | 21.10000 | 61.33614 | -0.1829 | 5.76290 |
November | 720.00000 | 21.03470 | 61.87524 | -0.2108 | 5.94958 |
December | 744.00000 | 21.00518 | 59.43777 | -0.2512 | 6.34555 |
Annual Sum or Average | 8760.00000 | 21.15195 | 59.77340 | -0.6650 | 19.61787 |
Minimum of Months | 672.00000 | 21.00053 | 54.59017 | -1.3260 | 5.76290 |
Maximum of Months | 744.00000 | 21.46741 | 62.57710 | -0.1829 | 41.69658 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.223600E+12 | 193811.16 | 29-JAN-16:03 | 744.00 | 0.635229E+12 | 0.00 | 0.858829E+12 | 2.82 | 3.82 | 09-JAN-19:02 | 0.00 | 0.00 |
February | 0.253362E+12 | 244449.49 | 07-FEB-16:03 | 672.00 | 0.742634E+12 | 0.00 | 0.995996E+12 | 2.88 | 3.91 | 19-FEB-19:02 | 0.00 | 0.00 |
March | 0.333577E+12 | 240422.73 | 01-MAR-16:03 | 744.00 | 0.969429E+12 | 0.00 | 0.130301E+13 | 2.87 | 3.96 | 24-MAR-08:62 | 0.00 | 0.00 |
April | 0.426811E+12 | 323558.75 | 30-APR-15:03 | 720.00 | 0.126587E+13 | 0.00 | 0.169268E+13 | 2.96 | 3.92 | 30-APR-06:40 | 0.00 | 0.00 |
May | 0.595881E+12 | 412633.00 | 30-MAY-18:03 | 744.00 | 0.168899E+13 | 0.00 | 0.228487E+13 | 2.84 | 3.93 | 01-MAY-07:00 | 0.00 | 0.00 |
June | 0.721648E+12 | 434917.02 | 04-JUN-15:15 | 720.00 | 0.205653E+13 | 0.00 | 0.277818E+13 | 2.87 | 3.64 | 22-JUN-08:62 | 0.00 | 0.00 |
July | 0.883812E+12 | 511716.34 | 19-JUL-15:03 | 744.00 | 0.242893E+13 | 0.00 | 0.331274E+13 | 2.75 | 3.29 | 06-JUL-05:15 | 0.00 | 0.00 |
August | 0.917516E+12 | 555140.36 | 10-AUG-15:15 | 744.00 | 0.251555E+13 | 0.00 | 0.343307E+13 | 2.76 | 3.31 | 27-AUG-06:10 | 0.00 | 0.00 |
September | 0.752317E+12 | 476485.03 | 07-SEP-15:15 | 720.00 | 0.219297E+13 | 0.00 | 0.294528E+13 | 2.94 | 3.60 | 25-SEP-08:03 | 0.00 | 0.00 |
October | 0.593509E+12 | 403733.40 | 07-OCT-18:03 | 744.00 | 0.179203E+13 | 0.00 | 0.238554E+13 | 3.02 | 3.59 | 07-OCT-08:03 | 0.00 | 0.00 |
November | 0.421095E+12 | 335765.64 | 01-NOV-15:03 | 720.00 | 0.128783E+13 | 0.00 | 0.170892E+13 | 3.04 | 3.79 | 07-NOV-07:05 | 0.00 | 0.00 |
December | 0.303409E+12 | 237254.38 | 05-DEC-16:03 | 744.00 | 0.913102E+12 | 0.00 | 0.121651E+13 | 2.95 | 3.85 | 26-DEC-09:02 | 0.00 | 0.00 |
Annual Sum or Average | 0.642654E+13 | 8760.00 | 0.184891E+14 | 0.00 | 0.249156E+14 | 2.89 | 0.00 | 0.00 | ||||
Minimum of Months | 0.223600E+12 | 193811.16 | 672.00 | 0.635229E+12 | 0.00 | 0.858829E+12 | 2.75 | 3.29 | 0.00 | 0.00 | ||
Maximum of Months | 0.917516E+12 | 555140.36 | 744.00 | 0.251555E+13 | 0.00 | 0.343307E+13 | 3.04 | 3.96 | 0.00 | 0.00 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.526205E+11 | 0.00 | 744.00 | 67612.81 | 04-JAN-09:05 | 0.00 | 31.48 | 60.00 | 0.17 | 0.00 | 0.08 | 0.28 | 04-JAN-09:05 |
February | 0.438118E+11 | 0.00 | 672.00 | 71788.38 | 21-FEB-11:40 | 0.00 | 30.82 | 60.00 | 0.16 | 0.00 | 0.08 | 0.30 | 21-FEB-11:40 |
March | 0.464807E+11 | 0.00 | 740.64 | 73263.70 | 20-MAR-10:40 | 0.00 | 30.62 | 59.85 | 0.15 | 0.00 | 0.07 | 0.30 | 20-MAR-10:40 |
April | 0.399610E+11 | 0.00 | 706.19 | 70630.85 | 05-APR-10:40 | 0.00 | 30.79 | 59.39 | 0.14 | 0.00 | 0.06 | 0.29 | 05-APR-10:40 |
May | 0.321962E+11 | 0.00 | 662.83 | 62623.62 | 01-MAY-10:40 | 0.00 | 31.43 | 56.56 | 0.11 | 0.00 | 0.05 | 0.26 | 01-MAY-10:40 |
June | 0.270457E+11 | 0.00 | 621.44 | 60318.94 | 08-JUN-10:35 | 0.00 | 31.50 | 55.69 | 0.10 | 0.00 | 0.04 | 0.25 | 08-JUN-10:35 |
July | 0.233524E+11 | 0.00 | 604.25 | 56173.42 | 03-JUL-10:35 | 0.00 | 31.62 | 54.15 | 0.08 | 0.00 | 0.04 | 0.23 | 03-JUL-10:35 |
August | 0.185993E+11 | 0.00 | 562.60 | 53151.36 | 01-AUG-10:35 | 0.00 | 31.85 | 52.71 | 0.06 | 0.00 | 0.03 | 0.22 | 01-AUG-10:35 |
September | 0.171415E+11 | 0.00 | 598.08 | 48667.75 | 25-SEP-10:35 | 0.00 | 31.60 | 54.86 | 0.06 | 0.00 | 0.03 | 0.20 | 25-SEP-10:35 |
October | 0.185899E+11 | 0.00 | 652.25 | 46899.65 | 30-OCT-10:35 | 0.00 | 30.80 | 56.13 | 0.06 | 0.00 | 0.03 | 0.20 | 30-OCT-10:35 |
November | 0.246227E+11 | 0.00 | 698.39 | 54197.76 | 29-NOV-11:40 | 0.00 | 29.56 | 58.99 | 0.08 | 0.00 | 0.04 | 0.23 | 29-NOV-11:40 |
December | 0.425733E+11 | 0.00 | 744.00 | 60713.87 | 21-DEC-11:40 | 0.00 | 30.64 | 60.00 | 0.14 | 0.00 | 0.07 | 0.25 | 21-DEC-11:40 |
Annual Sum or Average | 0.386995E+12 | 0.00 | 8006.69 | 0.00 | 31.06 | 57.34 | 0.11 | 0.00 | 0.05 | ||||
Minimum of Months | 0.171415E+11 | 0.00 | 562.60 | 46899.65 | 0.00 | 29.56 | 52.71 | 0.06 | 0.00 | 0.03 | 0.20 | ||
Maximum of Months | 0.526205E+11 | 0.00 | 744.00 | 73263.70 | 0.00 | 31.85 | 60.00 | 0.17 | 0.00 | 0.08 | 0.30 |
Report: DXReportMonthly
For: VAV WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.456129E+12 | 0.00 | 697.83 | 0.403828E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 439356.89 | 30-JAN-11:40 | 303523.06 | 29-JAN-11:45 | 0.00 | 0.00 | 0.00 |
February | 0.544112E+12 | 0.00 | 658.42 | 0.437615E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 545545.82 | 03-FEB-20:20 | 344769.51 | 05-FEB-11:50 | 0.00 | 0.00 | 0.00 |
March | 0.712096E+12 | 0.00 | 744.00 | 0.596117E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 547382.19 | 28-MAR-10:50 | 413935.78 | 27-MAR-10:45 | 0.00 | 0.00 | 0.00 |
April | 0.944154E+12 | 0.00 | 720.00 | 0.703969E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 704742.05 | 30-APR-17:12 | 444507.38 | 28-APR-10:50 | 0.00 | 0.00 | 0.00 |
May | 0.125982E+13 | 0.00 | 744.00 | 0.875413E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 862795.46 | 30-MAY-18:00 | 471831.56 | 31-MAY-19:00 | 0.00 | 0.00 | 0.00 |
June | 0.157549E+13 | 0.00 | 720.00 | 0.897679E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 919342.79 | 04-JUN-19:00 | 470627.74 | 12-JUN-10:50 | 0.00 | 0.00 | 0.00 |
July | 0.187551E+13 | 0.00 | 744.00 | 0.991104E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1035475.69 | 18-JUL-21:00 | 503401.66 | 30-JUL-10:50 | 0.00 | 0.00 | 0.00 |
August | 0.194537E+13 | 0.00 | 744.00 | 0.100132E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 1045928.61 | 22-AUG-17:00 | 493742.06 | 05-AUG-10:35 | 0.00 | 0.00 | 0.00 |
September | 0.169244E+13 | 0.00 | 720.00 | 0.888118E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 990850.25 | 08-SEP-17:13 | 449457.80 | 12-SEP-10:50 | 0.00 | 0.00 | 0.00 |
October | 0.135545E+13 | 0.00 | 744.00 | 0.828222E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 963009.21 | 07-OCT-10:35 | 408072.47 | 09-OCT-10:35 | 0.00 | 0.00 | 0.00 |
November | 0.957965E+12 | 0.00 | 720.00 | 0.678163E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 735829.81 | 01-NOV-10:35 | 363880.34 | 06-NOV-11:35 | 0.00 | 0.00 | 0.00 |
December | 0.679451E+12 | 0.00 | 738.33 | 0.506776E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 560030.17 | 25-DEC-10:30 | 333522.32 | 10-DEC-11:35 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.139980E+14 | 0.00 | 8694.58 | 0.880832E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.456129E+12 | 0.00 | 658.42 | 0.403828E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 439356.89 | 303523.06 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.194537E+13 | 0.00 | 744.00 | 0.100132E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 1045928.61 | 503401.66 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: FLR_3_DOAS COOLING COIL
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.514319E+11 | 0.00 | 652.33 | 0.423178E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 64721.81 | 30-JAN-14:10 | 31079.71 | 23-JAN-14:00 | 0.00 | 0.00 | 0.00 |
February | 0.606310E+11 | 0.00 | 639.00 | 0.461374E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 60017.86 | 09-FEB-15:00 | 34427.10 | 06-FEB-15:00 | 0.00 | 0.00 | 0.00 |
March | 0.774445E+11 | 0.00 | 739.67 | 0.630862E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 63399.61 | 31-MAR-09:40 | 37681.73 | 27-MAR-11:20 | 0.00 | 0.00 | 0.00 |
April | 0.988599E+11 | 0.00 | 720.00 | 0.732263E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 75588.96 | 30-APR-06:00 | 40277.62 | 28-APR-12:00 | 0.00 | 0.00 | 0.00 |
May | 0.120480E+12 | 0.00 | 744.00 | 0.862834E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 77866.99 | 29-MAY-13:00 | 39954.46 | 31-MAY-12:00 | 0.00 | 0.00 | 0.00 |
June | 0.145398E+12 | 0.00 | 720.00 | 0.868573E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 79070.25 | 08-JUN-13:00 | 41470.38 | 12-JUN-12:00 | 0.00 | 0.00 | 0.00 |
July | 0.169008E+12 | 0.00 | 744.00 | 0.937825E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 85465.30 | 20-JUL-12:20 | 42934.51 | 21-JUL-12:00 | 0.00 | 0.00 | 0.00 |
August | 0.173955E+12 | 0.00 | 744.00 | 0.942919E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 85506.38 | 08-AUG-13:00 | 43418.23 | 16-AUG-12:00 | 0.00 | 0.00 | 0.00 |
September | 0.155056E+12 | 0.00 | 720.00 | 0.862151E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 82393.43 | 09-SEP-14:00 | 40347.31 | 04-SEP-14:00 | 0.00 | 0.00 | 0.00 |
October | 0.130214E+12 | 0.00 | 744.00 | 0.832961E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 81379.07 | 07-OCT-10:10 | 37927.23 | 04-OCT-12:00 | 0.00 | 0.00 | 0.00 |
November | 0.101203E+12 | 0.00 | 720.00 | 0.712985E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 65315.69 | 01-NOV-14:00 | 35438.41 | 01-NOV-14:00 | 0.00 | 0.00 | 0.00 |
December | 0.743724E+11 | 0.00 | 731.17 | 0.537381E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 67924.64 | 25-DEC-10:40 | 32600.83 | 10-DEC-13:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.135805E+13 | 0.00 | 8618.17 | 0.880531E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.514319E+11 | 0.00 | 639.00 | 0.423178E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 60017.86 | 31079.71 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.173955E+12 | 0.00 | 744.00 | 0.942919E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 85506.38 | 43418.23 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.391671E+10 | 0.00 | 579.46 | 0.161334E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20740.14 | 30-JAN-16:01 | 17704.72 | 16-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.496328E+10 | 0.00 | 567.05 | 0.218693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20249.26 | 07-FEB-09:02 | 17194.28 | 23-FEB-19:01 | 0.00 | 0.00 | 0.00 |
March | 0.749361E+10 | 0.00 | 666.40 | 0.396979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20934.63 | 24-MAR-08:62 | 17304.08 | 23-MAR-08:62 | 0.00 | 0.00 | 0.00 |
April | 0.102041E+11 | 0.00 | 671.93 | 0.583604E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21670.13 | 18-APR-08:62 | 17706.73 | 01-APR-15:02 | 0.00 | 0.00 | 0.00 |
May | 0.154795E+11 | 0.00 | 718.13 | 0.998717E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22475.42 | 01-MAY-08:62 | 17331.28 | 26-MAY-15:02 | 0.00 | 0.00 | 0.00 |
June | 0.173557E+11 | 0.00 | 701.19 | 0.112310E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 21120.28 | 25-JUN-08:62 | 17231.65 | 27-JUN-15:02 | 0.00 | 0.00 | 0.00 |
July | 0.200824E+11 | 0.00 | 729.22 | 0.132848E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 21011.03 | 27-JUL-08:62 | 17138.24 | 22-JUL-15:02 | 0.00 | 0.00 | 0.00 |
August | 0.209158E+11 | 0.00 | 729.72 | 0.139346E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 21228.62 | 27-AUG-08:62 | 17170.57 | 04-AUG-15:02 | 0.00 | 0.00 | 0.00 |
September | 0.177252E+11 | 0.00 | 699.64 | 0.112725E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 21501.91 | 11-SEP-08:62 | 17325.31 | 21-SEP-15:02 | 0.00 | 0.00 | 0.00 |
October | 0.147988E+11 | 0.00 | 711.96 | 0.900977E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21570.95 | 31-OCT-08:61 | 17251.95 | 24-OCT-15:02 | 0.00 | 0.00 | 0.00 |
November | 0.993367E+10 | 0.00 | 670.23 | 0.530631E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21999.56 | 02-NOV-08:61 | 17706.38 | 18-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 0.558190E+10 | 0.00 | 634.60 | 0.237010E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20752.72 | 06-DEC-09:02 | 17121.13 | 25-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.148451E+12 | 0.00 | 8079.53 | 0.900024E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.391671E+10 | 0.00 | 567.05 | 0.161334E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20249.26 | 17121.13 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.209158E+11 | 0.00 | 729.72 | 0.139346E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 22475.42 | 17706.73 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.259738E+10 | 0.00 | 460.57 | 0.963736E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20245.71 | 30-JAN-16:01 | 17405.90 | 16-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.380456E+10 | 0.00 | 518.70 | 0.155190E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19908.71 | 09-FEB-09:02 | 16865.29 | 05-FEB-16:02 | 0.00 | 0.00 | 0.00 |
March | 0.658092E+10 | 0.00 | 639.31 | 0.339873E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20291.96 | 24-MAR-08:62 | 17004.03 | 19-MAR-18:02 | 0.00 | 0.00 | 0.00 |
April | 0.974956E+10 | 0.00 | 668.52 | 0.553866E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21277.52 | 18-APR-08:62 | 17408.59 | 01-APR-15:02 | 0.00 | 0.00 | 0.00 |
May | 0.154647E+11 | 0.00 | 718.37 | 0.100564E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 21508.90 | 01-MAY-08:62 | 17032.97 | 03-MAY-15:02 | 0.00 | 0.00 | 0.00 |
June | 0.175626E+11 | 0.00 | 701.98 | 0.115139E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 20613.48 | 25-JUN-08:62 | 16962.15 | 17-JUN-08:62 | 0.00 | 0.00 | 0.00 |
July | 0.201443E+11 | 0.00 | 729.61 | 0.133768E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 20585.46 | 27-JUL-08:62 | 16916.43 | 10-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.206208E+11 | 0.00 | 729.36 | 0.137083E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 20898.43 | 27-AUG-08:62 | 16924.01 | 19-AUG-15:02 | 0.00 | 0.00 | 0.00 |
September | 0.168432E+11 | 0.00 | 696.40 | 0.104643E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 21204.83 | 11-SEP-08:62 | 16973.90 | 16-SEP-15:02 | 0.00 | 0.00 | 0.00 |
October | 0.132616E+11 | 0.00 | 703.09 | 0.767590E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21107.05 | 08-OCT-08:62 | 17002.38 | 05-OCT-18:02 | 0.00 | 0.00 | 0.00 |
November | 0.819193E+10 | 0.00 | 653.87 | 0.404177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21579.22 | 02-NOV-08:61 | 17407.31 | 18-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 0.405389E+10 | 0.00 | 568.04 | 0.156189E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20420.85 | 24-DEC-16:02 | 16818.20 | 27-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.138875E+12 | 0.00 | 7787.83 | 0.838523E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.259738E+10 | 0.00 | 460.57 | 0.963736E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19908.71 | 16818.20 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.206208E+11 | 0.00 | 729.61 | 0.137083E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 21579.22 | 17408.59 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.322916E+11 | 0.00 | 588.19 | 0.147626E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 35511.47 | 28-JAN-13:40 | 34761.30 | 28-JAN-14:00 | 0.00 | 0.00 | 0.00 |
February | 0.328584E+11 | 0.00 | 546.79 | 0.150550E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 44960.13 | 05-FEB-13:30 | 37106.38 | 04-FEB-13:40 | 0.00 | 0.00 | 0.00 |
March | 0.406195E+11 | 0.00 | 651.92 | 0.203545E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 37238.50 | 27-MAR-13:30 | 31643.84 | 23-MAR-11:50 | 0.00 | 0.00 | 0.00 |
April | 0.493403E+11 | 0.00 | 695.78 | 0.255472E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 40745.11 | 29-APR-20:20 | 34460.95 | 28-APR-12:00 | 0.00 | 0.00 | 0.00 |
May | 0.709784E+11 | 0.00 | 744.00 | 0.402412E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 48059.42 | 31-MAY-19:10 | 41462.07 | 31-MAY-19:20 | 0.00 | 0.00 | 0.00 |
June | 0.781482E+11 | 0.00 | 720.00 | 0.440321E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 50293.68 | 09-JUN-20:20 | 40656.67 | 09-JUN-20:20 | 0.00 | 0.00 | 0.00 |
July | 0.947781E+11 | 0.00 | 744.00 | 0.577032E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 54258.56 | 15-JUL-19:10 | 47593.51 | 21-JUL-19:10 | 0.00 | 0.00 | 0.00 |
August | 0.101881E+12 | 0.00 | 744.00 | 0.647264E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 60665.14 | 10-AUG-20:50 | 46568.51 | 17-AUG-20:30 | 0.00 | 0.00 | 0.00 |
September | 0.922016E+11 | 0.00 | 720.00 | 0.584454E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 53077.19 | 04-SEP-20:10 | 47051.44 | 26-SEP-13:10 | 0.00 | 0.00 | 0.00 |
October | 0.861298E+11 | 0.00 | 744.00 | 0.555559E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 53439.01 | 07-OCT-13:00 | 47820.03 | 09-OCT-12:40 | 0.00 | 0.00 | 0.00 |
November | 0.654870E+11 | 0.00 | 711.67 | 0.386002E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 48993.17 | 05-NOV-13:30 | 44005.00 | 05-NOV-13:30 | 0.00 | 0.00 | 0.00 |
December | 0.419510E+11 | 0.00 | 632.61 | 0.201804E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 45452.40 | 03-DEC-12:40 | 37108.53 | 03-DEC-13:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.786665E+12 | 0.00 | 8242.96 | 0.455204E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.322916E+11 | 0.00 | 546.79 | 0.147626E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 35511.47 | 31643.84 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.101881E+12 | 0.00 | 744.00 | 0.647264E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 60665.14 | 47820.03 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.417280E+11 | 0.00 | 524.59 | 0.204202E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 133946.83 | 29-JAN-09:02 | 113060.39 | 16-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.471529E+11 | 0.00 | 478.86 | 0.247328E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 133489.86 | 09-FEB-09:02 | 113414.67 | 07-FEB-19:02 | 0.00 | 0.00 | 0.00 |
March | 0.627832E+11 | 0.00 | 551.65 | 0.380375E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 134884.75 | 24-MAR-08:62 | 114571.26 | 21-MAR-18:02 | 0.00 | 0.00 | 0.00 |
April | 0.792902E+11 | 0.00 | 599.80 | 0.507480E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 143603.27 | 18-APR-08:62 | 116139.75 | 26-APR-08:61 | 0.00 | 0.00 | 0.00 |
May | 0.110093E+12 | 0.00 | 684.87 | 0.773327E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 139446.85 | 01-MAY-08:62 | 115775.19 | 03-MAY-18:02 | 0.00 | 0.00 | 0.00 |
June | 0.120299E+12 | 0.00 | 672.69 | 0.839077E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 130497.84 | 08-JUN-15:02 | 113975.39 | 17-JUN-18:02 | 0.00 | 0.00 | 0.00 |
July | 0.134847E+12 | 0.00 | 701.37 | 0.931978E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 132089.44 | 27-JUL-08:62 | 115365.13 | 21-JUL-08:62 | 0.00 | 0.00 | 0.00 |
August | 0.135190E+12 | 0.00 | 699.42 | 0.925036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 133738.78 | 08-AUG-08:62 | 113819.66 | 15-AUG-18:02 | 0.00 | 0.00 | 0.00 |
September | 0.114230E+12 | 0.00 | 664.11 | 0.771327E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 132590.11 | 11-SEP-08:62 | 115107.07 | 19-SEP-08:62 | 0.00 | 0.00 | 0.00 |
October | 0.970685E+11 | 0.00 | 654.39 | 0.632065E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 132850.69 | 28-OCT-08:61 | 115402.85 | 09-OCT-18:02 | 0.00 | 0.00 | 0.00 |
November | 0.708765E+11 | 0.00 | 554.26 | 0.425787E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 143604.31 | 02-NOV-08:61 | 118405.81 | 18-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 0.518664E+11 | 0.00 | 524.63 | 0.272382E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 136279.25 | 26-DEC-19:01 | 113613.91 | 11-DEC-19:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.106542E+13 | 0.00 | 7310.63 | 0.691036E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.417280E+11 | 0.00 | 478.86 | 0.204202E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 130497.84 | 113060.39 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.135190E+12 | 0.00 | 701.37 | 0.931978E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 143604.31 | 118405.81 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_5_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.396817E+10 | 0.00 | 576.86 | 0.173058E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18740.07 | 30-JAN-16:01 | 16008.15 | 16-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.492547E+10 | 0.00 | 576.03 | 0.227451E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18511.07 | 08-FEB-09:02 | 15624.45 | 23-FEB-19:01 | 0.00 | 0.00 | 0.00 |
March | 0.723838E+10 | 0.00 | 673.98 | 0.392962E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19254.12 | 24-MAR-08:62 | 16008.52 | 23-MAR-08:62 | 0.00 | 0.00 | 0.00 |
April | 0.103473E+11 | 0.00 | 682.69 | 0.617088E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19603.15 | 18-APR-08:62 | 16009.64 | 01-APR-15:02 | 0.00 | 0.00 | 0.00 |
May | 0.157038E+11 | 0.00 | 726.99 | 0.103613E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 20018.57 | 01-MAY-08:62 | 15631.69 | 25-MAY-15:02 | 0.00 | 0.00 | 0.00 |
June | 0.173525E+11 | 0.00 | 705.91 | 0.115036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 18595.52 | 08-JUN-08:62 | 15599.35 | 20-JUN-15:02 | 0.00 | 0.00 | 0.00 |
July | 0.201581E+11 | 0.00 | 731.58 | 0.138368E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 18484.55 | 20-JUL-08:62 | 15503.05 | 20-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.209801E+11 | 0.00 | 732.34 | 0.145162E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 18627.71 | 08-AUG-08:62 | 15585.40 | 05-AUG-18:02 | 0.00 | 0.00 | 0.00 |
September | 0.177609E+11 | 0.00 | 703.92 | 0.115985E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 18720.04 | 11-SEP-08:62 | 15690.04 | 16-SEP-15:02 | 0.00 | 0.00 | 0.00 |
October | 0.149151E+11 | 0.00 | 723.61 | 0.913909E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19095.98 | 31-OCT-08:61 | 15610.39 | 05-OCT-18:02 | 0.00 | 0.00 | 0.00 |
November | 0.995443E+10 | 0.00 | 683.93 | 0.551267E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19482.85 | 02-NOV-08:61 | 16009.50 | 18-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 0.549937E+10 | 0.00 | 638.29 | 0.246939E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18903.76 | 06-DEC-09:02 | 15473.67 | 27-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.148804E+12 | 0.00 | 8156.14 | 0.930431E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.396817E+10 | 0.00 | 576.03 | 0.173058E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18484.55 | 15473.67 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.209801E+11 | 0.00 | 732.34 | 0.145162E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 20018.57 | 16009.64 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_6_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.266407E+10 | 0.00 | 441.53 | 0.101341E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18277.18 | 30-JAN-16:01 | 15481.30 | 16-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.375615E+10 | 0.00 | 496.05 | 0.159935E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18023.17 | 09-FEB-09:02 | 15130.67 | 04-FEB-09:02 | 0.00 | 0.00 | 0.00 |
March | 0.630254E+10 | 0.00 | 653.24 | 0.330636E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18659.56 | 24-MAR-08:62 | 15721.49 | 23-MAR-08:62 | 0.00 | 0.00 | 0.00 |
April | 0.988631E+10 | 0.00 | 680.69 | 0.585449E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19231.03 | 18-APR-08:62 | 15726.46 | 01-APR-15:02 | 0.00 | 0.00 | 0.00 |
May | 0.156873E+11 | 0.00 | 727.67 | 0.104500E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 19153.51 | 01-MAY-08:62 | 15335.55 | 25-MAY-15:02 | 0.00 | 0.00 | 0.00 |
June | 0.175638E+11 | 0.00 | 706.41 | 0.118489E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 18217.55 | 08-JUN-08:62 | 15270.40 | 20-JUN-15:02 | 0.00 | 0.00 | 0.00 |
July | 0.202282E+11 | 0.00 | 731.95 | 0.139638E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 18213.53 | 20-JUL-08:62 | 15313.73 | 23-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.206836E+11 | 0.00 | 732.07 | 0.142182E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 18269.22 | 08-AUG-08:62 | 15308.77 | 04-AUG-15:02 | 0.00 | 0.00 | 0.00 |
September | 0.168746E+11 | 0.00 | 702.66 | 0.107121E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 18466.38 | 11-SEP-08:62 | 15341.80 | 20-SEP-15:02 | 0.00 | 0.00 | 0.00 |
October | 0.133841E+11 | 0.00 | 717.17 | 0.789008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18839.53 | 31-OCT-08:61 | 15353.07 | 28-OCT-15:02 | 0.00 | 0.00 | 0.00 |
November | 0.821083E+10 | 0.00 | 668.48 | 0.433411E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19333.30 | 02-NOV-08:61 | 15725.66 | 18-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 0.397430E+10 | 0.00 | 543.41 | 0.159775E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19339.76 | 05-DEC-16:02 | 15005.20 | 25-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.139216E+12 | 0.00 | 7801.33 | 0.867885E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.266407E+10 | 0.00 | 441.53 | 0.101341E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18023.17 | 15005.20 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.206836E+11 | 0.00 | 732.07 | 0.142182E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 19339.76 | 15726.46 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.105681E+10 | 0.00 | 541.72 | 0.446556E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5752.55 | 29-JAN-09:02 | 4828.69 | 16-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.138244E+10 | 0.00 | 556.28 | 0.632076E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5683.53 | 07-FEB-09:02 | 4675.86 | 03-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.212847E+10 | 0.00 | 673.51 | 0.115065E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5815.94 | 24-MAR-08:62 | 4724.11 | 23-MAR-08:62 | 0.00 | 0.00 | 0.00 |
April | 0.293432E+10 | 0.00 | 677.17 | 0.173059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6101.06 | 18-APR-08:62 | 4719.70 | 30-APR-15:02 | 0.00 | 0.00 | 0.00 |
May | 0.442350E+10 | 0.00 | 722.22 | 0.294774E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6299.41 | 01-MAY-08:62 | 4736.49 | 22-MAY-18:02 | 0.00 | 0.00 | 0.00 |
June | 0.492305E+10 | 0.00 | 704.01 | 0.327790E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5793.90 | 25-JUN-08:62 | 4700.19 | 08-JUN-15:02 | 0.00 | 0.00 | 0.00 |
July | 0.569392E+10 | 0.00 | 732.01 | 0.387067E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5712.73 | 27-JUL-08:62 | 4700.80 | 28-JUL-15:02 | 0.00 | 0.00 | 0.00 |
August | 0.588733E+10 | 0.00 | 732.07 | 0.403277E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5796.43 | 27-AUG-08:62 | 4706.35 | 08-AUG-15:02 | 0.00 | 0.00 | 0.00 |
September | 0.496770E+10 | 0.00 | 701.86 | 0.324625E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5863.24 | 11-SEP-08:62 | 4697.11 | 22-SEP-15:02 | 0.00 | 0.00 | 0.00 |
October | 0.413974E+10 | 0.00 | 715.41 | 0.259445E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5991.24 | 31-OCT-08:61 | 4720.59 | 11-OCT-18:02 | 0.00 | 0.00 | 0.00 |
November | 0.276883E+10 | 0.00 | 676.43 | 0.151111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6141.22 | 02-NOV-08:61 | 4828.96 | 18-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 0.153552E+10 | 0.00 | 626.09 | 0.672884E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5816.40 | 06-DEC-09:02 | 4688.32 | 07-DEC-16:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.418416E+11 | 0.00 | 8058.80 | 0.261137E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.105681E+10 | 0.00 | 541.72 | 0.446556E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5683.53 | 4675.86 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.588733E+10 | 0.00 | 732.07 | 0.403277E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6299.41 | 4828.96 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.701204E+09 | 0.00 | 430.05 | 0.269791E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5599.02 | 30-JAN-16:01 | 4750.23 | 16-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.107265E+10 | 0.00 | 501.70 | 0.455533E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5586.55 | 09-FEB-09:02 | 4629.46 | 23-FEB-19:01 | 0.00 | 0.00 | 0.00 |
March | 0.188345E+10 | 0.00 | 654.40 | 0.990554E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5612.68 | 29-MAR-08:62 | 4616.72 | 02-MAR-09:01 | 0.00 | 0.00 | 0.00 |
April | 0.281534E+10 | 0.00 | 675.15 | 0.164267E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5994.04 | 18-APR-08:62 | 4662.57 | 30-APR-15:02 | 0.00 | 0.00 | 0.00 |
May | 0.441902E+10 | 0.00 | 722.52 | 0.296115E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6011.90 | 01-MAY-08:62 | 4648.02 | 22-MAY-18:02 | 0.00 | 0.00 | 0.00 |
June | 0.497652E+10 | 0.00 | 704.86 | 0.334389E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5656.12 | 25-JUN-08:62 | 4627.06 | 08-JUN-18:02 | 0.00 | 0.00 | 0.00 |
July | 0.571217E+10 | 0.00 | 732.28 | 0.390776E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5600.52 | 27-JUL-08:62 | 4625.99 | 28-JUL-15:02 | 0.00 | 0.00 | 0.00 |
August | 0.581125E+10 | 0.00 | 732.07 | 0.397350E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5709.35 | 27-AUG-08:62 | 4627.76 | 10-AUG-18:02 | 0.00 | 0.00 | 0.00 |
September | 0.474180E+10 | 0.00 | 700.36 | 0.303180E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5791.88 | 11-SEP-08:62 | 4631.19 | 24-SEP-15:02 | 0.00 | 0.00 | 0.00 |
October | 0.373963E+10 | 0.00 | 708.26 | 0.221686E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5857.64 | 31-OCT-08:61 | 4630.94 | 24-OCT-15:02 | 0.00 | 0.00 | 0.00 |
November | 0.230833E+10 | 0.00 | 662.72 | 0.115948E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6034.63 | 02-NOV-08:61 | 4750.79 | 18-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 0.112405E+10 | 0.00 | 556.86 | 0.447234E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5630.47 | 06-DEC-09:02 | 4589.66 | 27-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.393054E+11 | 0.00 | 7781.23 | 0.244002E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.701204E+09 | 0.00 | 430.05 | 0.269791E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5586.55 | 4589.66 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.581125E+10 | 0.00 | 732.28 | 0.397350E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6034.63 | 4750.79 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.994179E+10 | 0.00 | 664.26 | 0.523006E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27555.22 | 29-JAN-09:02 | 22501.27 | 12-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.105100E+11 | 0.00 | 604.11 | 0.564728E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27190.38 | 08-FEB-09:02 | 22581.96 | 15-FEB-16:02 | 0.00 | 0.00 | 0.00 |
March | 0.129080E+11 | 0.00 | 681.01 | 0.752163E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27918.26 | 24-MAR-08:62 | 22805.21 | 23-MAR-08:62 | 0.00 | 0.00 | 0.00 |
April | 0.154017E+11 | 0.00 | 672.12 | 0.926810E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29479.01 | 18-APR-08:62 | 23211.52 | 26-APR-08:61 | 0.00 | 0.00 | 0.00 |
May | 0.213393E+11 | 0.00 | 715.52 | 0.139917E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 30478.79 | 01-MAY-08:62 | 22755.42 | 08-MAY-18:02 | 0.00 | 0.00 | 0.00 |
June | 0.232099E+11 | 0.00 | 697.17 | 0.152294E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 26780.06 | 25-JUN-08:62 | 22627.34 | 27-JUN-15:02 | 0.00 | 0.00 | 0.00 |
July | 0.273252E+11 | 0.00 | 726.13 | 0.186918E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 26890.57 | 27-JUL-08:62 | 22591.03 | 30-JUL-08:62 | 0.00 | 0.00 | 0.00 |
August | 0.287729E+11 | 0.00 | 726.81 | 0.200384E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 27050.58 | 08-AUG-08:62 | 22602.79 | 17-AUG-18:02 | 0.00 | 0.00 | 0.00 |
September | 0.258049E+11 | 0.00 | 698.81 | 0.176485E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 27184.96 | 11-SEP-08:62 | 22721.78 | 22-SEP-15:02 | 0.00 | 0.00 | 0.00 |
October | 0.238012E+11 | 0.00 | 718.32 | 0.161920E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 27738.90 | 31-OCT-08:61 | 22656.42 | 04-OCT-18:02 | 0.00 | 0.00 | 0.00 |
November | 0.181878E+11 | 0.00 | 688.82 | 0.113101E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 29497.27 | 02-NOV-08:61 | 22543.30 | 04-NOV-18:02 | 0.00 | 0.00 | 0.00 |
December | 0.125767E+11 | 0.00 | 677.62 | 0.692435E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27913.95 | 06-DEC-09:02 | 22603.14 | 06-DEC-16:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.229779E+12 | 0.00 | 8270.70 | 0.147693E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.994179E+10 | 0.00 | 604.11 | 0.523006E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26780.06 | 22501.27 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.287729E+11 | 0.00 | 726.81 | 0.200384E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 30478.79 | 23211.52 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 452.45 | 213.67 | 238.77 | 729.32 | 169.41 | 0.00 | 0.00 | 0.00 |
February | 422.96 | 172.99 | 249.97 | 722.83 | 130.25 | 0.00 | 0.00 | 0.00 |
March | 344.46 | 90.90 | 253.55 | 665.39 | 87.83 | 0.00 | 0.00 | 0.00 |
April | 275.08 | 30.38 | 244.70 | 648.44 | 37.66 | 0.00 | 0.00 | 0.00 |
May | 232.73 | 4.39 | 228.34 | 761.51 | 2.38 | 0.00 | 0.00 | 0.00 |
June | 218.27 | 0.27 | 218.00 | 808.57 | 0.05 | 0.00 | 0.00 | 0.00 |
July | 217.97 | 1.44 | 216.53 | 928.73 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 252.15 | 16.77 | 235.38 | 1007.01 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 334.24 | 76.86 | 257.38 | 1013.61 | 0.50 | 0.00 | 0.00 | 0.00 |
October | 437.79 | 174.49 | 263.30 | 1030.23 | 4.84 | 0.00 | 0.00 | 0.00 |
November | 484.52 | 234.74 | 249.78 | 943.48 | 46.42 | 0.00 | 0.00 | 0.00 |
December | 448.37 | 221.89 | 226.49 | 763.47 | 124.83 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 342.93 | 102.85 | 240.08 | 835.94 | 50.01 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 217.97 | 0.27 | 216.53 | 648.44 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 484.52 | 234.74 | 263.30 | 1030.23 | 169.41 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1274.06 | 601.69 | 672.37 | 2037.90 | 485.67 | 0.00 | 0.00 | 0.00 |
February | 1191.02 | 487.13 | 703.90 | 2021.35 | 377.16 | 0.00 | 0.00 | 0.00 |
March | 969.96 | 255.98 | 713.98 | 1859.31 | 257.03 | 0.00 | 0.00 | 0.00 |
April | 774.62 | 85.55 | 689.06 | 1809.84 | 114.82 | 0.00 | 0.00 | 0.00 |
May | 655.36 | 12.37 | 643.00 | 2117.32 | 8.50 | 0.00 | 0.00 | 0.00 |
June | 614.65 | 0.76 | 613.89 | 2245.58 | 0.28 | 0.00 | 0.00 | 0.00 |
July | 613.79 | 4.06 | 609.73 | 2589.55 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 710.05 | 47.23 | 662.82 | 2816.98 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 941.19 | 216.42 | 724.77 | 2829.93 | 1.82 | 0.00 | 0.00 | 0.00 |
October | 1232.78 | 491.35 | 741.43 | 2878.90 | 18.19 | 0.00 | 0.00 | 0.00 |
November | 1364.38 | 661.02 | 703.36 | 2644.77 | 143.06 | 0.00 | 0.00 | 0.00 |
December | 1262.59 | 624.81 | 637.78 | 2136.52 | 360.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 965.67 | 289.63 | 676.04 | 2334.34 | 146.29 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 613.79 | 0.76 | 609.73 | 1809.84 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1364.38 | 661.02 | 741.43 | 2878.90 | 485.67 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1655.08 | 781.62 | 873.45 | 2708.48 | 641.97 | 0.00 | 0.00 | 0.00 |
February | 1547.21 | 632.81 | 914.40 | 2693.51 | 498.10 | 0.00 | 0.00 | 0.00 |
March | 1260.04 | 332.53 | 927.51 | 2482.38 | 342.12 | 0.00 | 0.00 | 0.00 |
April | 1006.27 | 111.14 | 895.13 | 2422.50 | 154.54 | 0.00 | 0.00 | 0.00 |
May | 851.35 | 16.06 | 835.29 | 2838.07 | 11.71 | 0.00 | 0.00 | 0.00 |
June | 798.46 | 0.99 | 797.47 | 3010.68 | 0.38 | 0.00 | 0.00 | 0.00 |
July | 797.35 | 5.28 | 792.07 | 3477.96 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 922.39 | 61.36 | 861.04 | 3788.08 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 1222.66 | 281.15 | 941.51 | 3804.70 | 2.35 | 0.00 | 0.00 | 0.00 |
October | 1601.46 | 638.30 | 963.16 | 3866.80 | 22.23 | 0.00 | 0.00 | 0.00 |
November | 1772.41 | 858.70 | 913.71 | 3536.20 | 185.48 | 0.00 | 0.00 | 0.00 |
December | 1640.18 | 811.67 | 828.51 | 2841.88 | 475.90 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1254.46 | 376.24 | 878.22 | 3125.35 | 193.26 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 797.35 | 0.99 | 792.07 | 2422.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1772.41 | 858.70 | 963.16 | 3866.80 | 641.97 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.46 | 42.25 | 47.21 | 140.89 | 34.67 | 0.00 | 0.00 | 0.00 |
February | 83.63 | 34.20 | 49.42 | 139.39 | 26.71 | 0.00 | 0.00 | 0.00 |
March | 68.11 | 17.97 | 50.13 | 127.92 | 18.13 | 0.00 | 0.00 | 0.00 |
April | 54.39 | 6.01 | 48.38 | 124.77 | 7.71 | 0.00 | 0.00 | 0.00 |
May | 46.02 | 0.87 | 45.15 | 149.10 | 0.51 | 0.00 | 0.00 | 0.00 |
June | 43.16 | 0.05 | 43.10 | 160.20 | 0.01 | 0.00 | 0.00 | 0.00 |
July | 43.10 | 0.29 | 42.81 | 185.86 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 49.86 | 3.32 | 46.54 | 202.63 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 66.08 | 15.20 | 50.89 | 201.92 | 0.10 | 0.00 | 0.00 | 0.00 |
October | 86.56 | 34.50 | 52.06 | 203.81 | 0.93 | 0.00 | 0.00 | 0.00 |
November | 95.80 | 46.41 | 49.39 | 184.63 | 9.26 | 0.00 | 0.00 | 0.00 |
December | 88.65 | 43.87 | 44.78 | 147.97 | 25.46 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 67.80 | 20.34 | 47.47 | 164.25 | 10.22 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 43.10 | 0.05 | 42.81 | 124.77 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 95.80 | 46.41 | 52.06 | 203.81 | 34.67 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 91.52 | 26.33 | 65.20 | 134.30 | 69.43 | 0.00 | 0.00 | 0.00 |
February | 104.45 | 29.88 | 74.57 | 167.33 | 52.07 | 0.00 | 0.00 | 0.00 |
March | 123.39 | 36.53 | 86.86 | 222.43 | 34.16 | 0.00 | 0.00 | 0.00 |
April | 134.92 | 37.90 | 97.01 | 282.99 | 14.19 | 0.00 | 0.00 | 0.00 |
May | 146.78 | 43.93 | 102.85 | 384.91 | 0.88 | 0.00 | 0.00 | 0.00 |
June | 151.62 | 47.77 | 103.85 | 425.59 | 0.01 | 0.00 | 0.00 | 0.00 |
July | 139.07 | 39.71 | 99.35 | 451.77 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 142.68 | 43.30 | 99.38 | 460.81 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 135.96 | 42.77 | 93.19 | 387.52 | 0.18 | 0.00 | 0.00 | 0.00 |
October | 120.94 | 39.21 | 81.73 | 299.89 | 1.73 | 0.00 | 0.00 | 0.00 |
November | 103.98 | 34.12 | 69.86 | 211.69 | 18.04 | 0.00 | 0.00 | 0.00 |
December | 86.71 | 26.11 | 60.60 | 141.39 | 50.40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 123.57 | 37.32 | 86.25 | 298.30 | 19.96 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 86.71 | 26.11 | 60.60 | 134.30 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 151.62 | 47.77 | 103.85 | 460.81 | 69.43 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 27.55 | 0.00 | 27.55 | 36.52 | 36.25 | 0.00 | 0.00 | 0.00 |
February | 31.58 | 0.00 | 31.58 | 48.64 | 27.29 | 0.00 | 0.00 | 0.00 |
March | 36.28 | 0.00 | 36.28 | 67.95 | 17.97 | 0.00 | 0.00 | 0.00 |
April | 41.01 | 0.16 | 40.84 | 97.54 | 7.43 | 0.00 | 0.00 | 0.00 |
May | 46.10 | 1.41 | 44.69 | 149.62 | 0.44 | 0.00 | 0.00 | 0.00 |
June | 49.28 | 2.76 | 46.52 | 173.22 | 0.01 | 0.00 | 0.00 | 0.00 |
July | 45.28 | 1.36 | 43.92 | 190.97 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 42.19 | 0.42 | 41.76 | 186.83 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 38.34 | 0.01 | 38.33 | 147.54 | 0.10 | 0.00 | 0.00 | 0.00 |
October | 33.97 | 0.00 | 33.97 | 107.72 | 0.90 | 0.00 | 0.00 | 0.00 |
November | 29.17 | 0.00 | 29.17 | 68.18 | 9.28 | 0.00 | 0.00 | 0.00 |
December | 25.71 | 0.00 | 25.71 | 40.89 | 26.14 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 37.23 | 0.51 | 36.71 | 110.00 | 10.41 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 25.71 | 0.00 | 25.71 | 36.52 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 49.28 | 2.76 | 46.52 | 190.97 | 36.25 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 91.52 | 26.33 | 65.20 | 138.25 | 67.28 | 0.00 | 0.00 | 0.00 |
February | 104.45 | 29.88 | 74.57 | 170.45 | 50.59 | 0.00 | 0.00 | 0.00 |
March | 123.39 | 36.53 | 86.86 | 224.40 | 33.39 | 0.00 | 0.00 | 0.00 |
April | 134.92 | 37.90 | 97.01 | 283.93 | 13.99 | 0.00 | 0.00 | 0.00 |
May | 146.78 | 43.93 | 102.85 | 384.93 | 0.87 | 0.00 | 0.00 | 0.00 |
June | 151.62 | 47.77 | 103.85 | 425.17 | 0.01 | 0.00 | 0.00 | 0.00 |
July | 139.07 | 39.71 | 99.35 | 451.63 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 142.68 | 43.30 | 99.38 | 461.35 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 135.96 | 42.77 | 93.19 | 389.29 | 0.17 | 0.00 | 0.00 | 0.00 |
October | 120.94 | 39.21 | 81.73 | 302.97 | 1.60 | 0.00 | 0.00 | 0.00 |
November | 103.98 | 34.12 | 69.86 | 215.19 | 17.20 | 0.00 | 0.00 | 0.00 |
December | 86.71 | 26.11 | 60.60 | 144.86 | 48.61 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 123.57 | 37.32 | 86.25 | 300.11 | 19.35 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 86.71 | 26.11 | 60.60 | 138.25 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 151.62 | 47.77 | 103.85 | 461.35 | 67.28 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 71.55 | 33.79 | 37.76 | 107.70 | 37.36 | 0.00 | 0.00 | 0.00 |
February | 66.89 | 27.36 | 39.53 | 106.93 | 30.34 | 0.00 | 0.00 | 0.00 |
March | 54.47 | 14.38 | 40.10 | 98.04 | 21.85 | 0.00 | 0.00 | 0.00 |
April | 43.50 | 4.80 | 38.70 | 94.99 | 11.21 | 0.00 | 0.00 | 0.00 |
May | 36.81 | 0.69 | 36.11 | 112.49 | 1.39 | 0.00 | 0.00 | 0.00 |
June | 34.52 | 0.04 | 34.48 | 120.95 | 0.05 | 0.00 | 0.00 | 0.00 |
July | 34.47 | 0.23 | 34.24 | 141.75 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 39.88 | 2.65 | 37.22 | 155.22 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 52.86 | 12.15 | 40.70 | 153.70 | 0.32 | 0.00 | 0.00 | 0.00 |
October | 69.23 | 27.59 | 41.64 | 155.33 | 2.50 | 0.00 | 0.00 | 0.00 |
November | 76.62 | 37.12 | 39.50 | 142.01 | 13.01 | 0.00 | 0.00 | 0.00 |
December | 70.91 | 35.09 | 35.82 | 113.60 | 29.26 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.23 | 16.27 | 37.97 | 125.35 | 12.19 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 34.47 | 0.04 | 34.24 | 94.99 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 76.62 | 37.12 | 41.64 | 155.33 | 37.36 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 22.04 | 0.00 | 22.04 | 30.24 | 29.15 | 0.00 | 0.00 | 0.00 |
February | 25.27 | 0.00 | 25.27 | 40.64 | 21.57 | 0.00 | 0.00 | 0.00 |
March | 29.03 | 0.00 | 29.03 | 57.03 | 13.75 | 0.00 | 0.00 | 0.00 |
April | 32.81 | 0.13 | 32.68 | 81.76 | 5.35 | 0.00 | 0.00 | 0.00 |
May | 36.88 | 1.13 | 35.75 | 125.65 | 0.23 | 0.00 | 0.00 | 0.00 |
June | 39.43 | 2.21 | 37.22 | 145.30 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 36.23 | 1.09 | 35.14 | 159.97 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 33.75 | 0.34 | 33.42 | 156.95 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 30.68 | 0.01 | 30.67 | 124.53 | 0.05 | 0.00 | 0.00 | 0.00 |
October | 27.18 | 0.00 | 27.18 | 91.27 | 0.52 | 0.00 | 0.00 | 0.00 |
November | 23.34 | 0.00 | 23.34 | 57.56 | 6.81 | 0.00 | 0.00 | 0.00 |
December | 20.57 | 0.00 | 20.57 | 34.15 | 20.70 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 29.79 | 0.41 | 29.37 | 92.40 | 8.12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.57 | 0.00 | 20.57 | 30.24 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 39.43 | 2.21 | 37.22 | 159.97 | 29.15 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 92.89 | 28.02 | 64.87 | 132.86 | 64.69 | 0.00 | 0.00 | 0.00 |
February | 101.43 | 27.49 | 73.94 | 160.08 | 48.78 | 0.00 | 0.00 | 0.00 |
March | 112.14 | 27.66 | 84.48 | 202.71 | 31.79 | 0.00 | 0.00 | 0.00 |
April | 136.52 | 39.73 | 96.79 | 288.10 | 13.38 | 0.00 | 0.00 | 0.00 |
May | 152.32 | 48.51 | 103.81 | 396.30 | 0.81 | 0.00 | 0.00 | 0.00 |
June | 149.21 | 45.61 | 103.59 | 423.23 | 0.01 | 0.00 | 0.00 | 0.00 |
July | 139.28 | 40.13 | 99.15 | 454.53 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 142.66 | 43.80 | 98.86 | 462.16 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 134.04 | 41.41 | 92.63 | 385.73 | 0.19 | 0.00 | 0.00 | 0.00 |
October | 121.60 | 39.67 | 81.93 | 302.89 | 1.71 | 0.00 | 0.00 | 0.00 |
November | 101.86 | 32.17 | 69.69 | 208.60 | 17.11 | 0.00 | 0.00 | 0.00 |
December | 82.59 | 22.71 | 59.88 | 132.15 | 47.37 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 122.29 | 36.45 | 85.85 | 296.56 | 18.70 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 82.59 | 22.71 | 59.88 | 132.15 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 152.32 | 48.51 | 103.81 | 462.16 | 64.69 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.46 | 42.25 | 47.21 | 140.27 | 34.47 | 0.00 | 0.00 | 0.00 |
February | 83.63 | 34.20 | 49.42 | 138.92 | 26.48 | 0.00 | 0.00 | 0.00 |
March | 68.11 | 17.97 | 50.13 | 127.74 | 17.84 | 0.00 | 0.00 | 0.00 |
April | 54.39 | 6.01 | 48.38 | 124.31 | 7.61 | 0.00 | 0.00 | 0.00 |
May | 46.02 | 0.87 | 45.15 | 148.74 | 0.49 | 0.00 | 0.00 | 0.00 |
June | 43.16 | 0.05 | 43.10 | 160.13 | 0.01 | 0.00 | 0.00 | 0.00 |
July | 43.10 | 0.29 | 42.81 | 185.75 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 49.86 | 3.32 | 46.54 | 202.53 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 66.08 | 15.20 | 50.89 | 201.85 | 0.10 | 0.00 | 0.00 | 0.00 |
October | 86.56 | 34.50 | 52.06 | 203.60 | 0.90 | 0.00 | 0.00 | 0.00 |
November | 95.80 | 46.41 | 49.39 | 184.36 | 9.13 | 0.00 | 0.00 | 0.00 |
December | 88.65 | 43.87 | 44.78 | 147.62 | 25.23 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 67.80 | 20.34 | 47.47 | 163.98 | 10.12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 43.10 | 0.05 | 42.81 | 124.31 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 95.80 | 46.41 | 52.06 | 203.60 | 34.47 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 27.55 | 0.00 | 27.55 | 35.96 | 36.00 | 0.00 | 0.00 | 0.00 |
February | 31.58 | 0.00 | 31.58 | 48.14 | 27.05 | 0.00 | 0.00 | 0.00 |
March | 36.28 | 0.00 | 36.28 | 67.73 | 17.68 | 0.00 | 0.00 | 0.00 |
April | 41.01 | 0.16 | 40.84 | 97.04 | 7.32 | 0.00 | 0.00 | 0.00 |
May | 46.10 | 1.41 | 44.69 | 149.25 | 0.42 | 0.00 | 0.00 | 0.00 |
June | 49.28 | 2.76 | 46.52 | 173.16 | 0.01 | 0.00 | 0.00 | 0.00 |
July | 45.28 | 1.36 | 43.92 | 190.87 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 42.19 | 0.42 | 41.76 | 186.74 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 38.34 | 0.01 | 38.33 | 147.46 | 0.10 | 0.00 | 0.00 | 0.00 |
October | 33.97 | 0.00 | 33.97 | 107.45 | 0.87 | 0.00 | 0.00 | 0.00 |
November | 29.17 | 0.00 | 29.17 | 67.80 | 9.14 | 0.00 | 0.00 | 0.00 |
December | 25.71 | 0.00 | 25.71 | 40.54 | 25.85 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 37.23 | 0.51 | 36.71 | 109.72 | 10.30 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 25.71 | 0.00 | 25.71 | 35.96 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 49.28 | 2.76 | 46.52 | 190.87 | 36.00 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 92.89 | 28.02 | 64.87 | 136.90 | 62.48 | 0.00 | 0.00 | 0.00 |
February | 101.43 | 27.49 | 73.94 | 163.18 | 47.30 | 0.00 | 0.00 | 0.00 |
March | 112.14 | 27.66 | 84.48 | 204.60 | 31.04 | 0.00 | 0.00 | 0.00 |
April | 136.52 | 39.73 | 96.79 | 288.99 | 13.19 | 0.00 | 0.00 | 0.00 |
May | 152.32 | 48.51 | 103.81 | 396.33 | 0.80 | 0.00 | 0.00 | 0.00 |
June | 149.21 | 45.61 | 103.59 | 422.83 | 0.01 | 0.00 | 0.00 | 0.00 |
July | 139.28 | 40.13 | 99.15 | 454.39 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 142.66 | 43.80 | 98.86 | 462.70 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 134.04 | 41.41 | 92.63 | 387.47 | 0.19 | 0.00 | 0.00 | 0.00 |
October | 121.60 | 39.67 | 81.93 | 305.88 | 1.58 | 0.00 | 0.00 | 0.00 |
November | 101.86 | 32.17 | 69.69 | 211.98 | 16.31 | 0.00 | 0.00 | 0.00 |
December | 82.59 | 22.71 | 59.88 | 135.72 | 45.55 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 122.29 | 36.45 | 85.85 | 298.35 | 18.08 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 82.59 | 22.71 | 59.88 | 135.72 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 152.32 | 48.51 | 103.81 | 462.70 | 62.48 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.89 | 0.00 | 34.89 | 51.18 | 43.69 | 0.00 | 0.00 | 0.00 |
February | 39.99 | 0.00 | 39.99 | 69.06 | 31.82 | 0.00 | 0.00 | 0.00 |
March | 45.95 | 0.00 | 45.94 | 96.54 | 19.97 | 0.00 | 0.00 | 0.00 |
April | 51.93 | 0.21 | 51.73 | 137.12 | 7.79 | 0.00 | 0.00 | 0.00 |
May | 58.38 | 1.79 | 56.59 | 202.26 | 0.42 | 0.00 | 0.00 | 0.00 |
June | 62.41 | 3.50 | 58.91 | 231.07 | 0.01 | 0.00 | 0.00 | 0.00 |
July | 57.35 | 1.72 | 55.63 | 251.89 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 53.43 | 0.54 | 52.89 | 245.55 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 48.55 | 0.01 | 48.54 | 196.47 | 0.12 | 0.00 | 0.00 | 0.00 |
October | 43.03 | 0.00 | 43.03 | 146.22 | 1.03 | 0.00 | 0.00 | 0.00 |
November | 36.94 | 0.00 | 36.94 | 96.08 | 10.48 | 0.00 | 0.00 | 0.00 |
December | 32.57 | 0.00 | 32.57 | 58.41 | 30.56 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 47.15 | 0.65 | 46.50 | 148.96 | 12.08 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 32.57 | 0.00 | 32.57 | 51.18 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 62.41 | 3.50 | 58.91 | 251.89 | 43.69 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 12.86 | 0.00 | 12.86 | 18.87 | 16.11 | 0.00 | 0.00 | 0.00 |
February | 14.74 | 0.00 | 14.74 | 25.46 | 11.73 | 0.00 | 0.00 | 0.00 |
March | 16.94 | 0.00 | 16.94 | 35.59 | 7.36 | 0.00 | 0.00 | 0.00 |
April | 19.15 | 0.08 | 19.07 | 50.55 | 2.87 | 0.00 | 0.00 | 0.00 |
May | 21.52 | 0.66 | 20.86 | 74.56 | 0.15 | 0.00 | 0.00 | 0.00 |
June | 23.01 | 1.29 | 21.72 | 85.18 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 21.14 | 0.64 | 20.51 | 92.86 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 19.70 | 0.20 | 19.50 | 90.52 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17.90 | 0.01 | 17.89 | 72.43 | 0.05 | 0.00 | 0.00 | 0.00 |
October | 15.86 | 0.00 | 15.86 | 53.90 | 0.38 | 0.00 | 0.00 | 0.00 |
November | 13.62 | 0.00 | 13.62 | 35.42 | 3.86 | 0.00 | 0.00 | 0.00 |
December | 12.00 | 0.00 | 12.00 | 21.53 | 11.27 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 17.38 | 0.24 | 17.14 | 54.91 | 4.45 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 12.00 | 0.00 | 12.00 | 18.87 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 23.01 | 1.29 | 21.72 | 92.86 | 16.11 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 41.74 | 19.71 | 22.03 | 68.68 | 14.94 | 0.00 | 0.00 | 0.00 |
February | 39.02 | 15.96 | 23.06 | 68.60 | 11.18 | 0.00 | 0.00 | 0.00 |
March | 31.78 | 8.39 | 23.39 | 63.99 | 7.28 | 0.00 | 0.00 | 0.00 |
April | 25.38 | 2.80 | 22.57 | 63.37 | 2.95 | 0.00 | 0.00 | 0.00 |
May | 21.47 | 0.41 | 21.07 | 74.25 | 0.18 | 0.00 | 0.00 | 0.00 |
June | 20.14 | 0.02 | 20.11 | 78.96 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 20.11 | 0.13 | 19.98 | 90.36 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 23.26 | 1.55 | 21.72 | 97.91 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 30.83 | 7.09 | 23.74 | 98.06 | 0.04 | 0.00 | 0.00 | 0.00 |
October | 40.39 | 16.10 | 24.29 | 99.30 | 0.37 | 0.00 | 0.00 | 0.00 |
November | 44.70 | 21.66 | 23.04 | 90.58 | 3.69 | 0.00 | 0.00 | 0.00 |
December | 41.36 | 20.47 | 20.89 | 72.47 | 10.58 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 31.64 | 9.49 | 22.15 | 80.62 | 4.24 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.11 | 0.02 | 19.98 | 63.37 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 44.70 | 21.66 | 24.29 | 99.30 | 14.94 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 113.29 | 53.50 | 59.79 | 186.41 | 40.55 | 0.00 | 0.00 | 0.00 |
February | 105.91 | 43.32 | 62.59 | 186.19 | 30.34 | 0.00 | 0.00 | 0.00 |
March | 86.25 | 22.76 | 63.49 | 173.68 | 19.77 | 0.00 | 0.00 | 0.00 |
April | 68.88 | 7.61 | 61.27 | 172.00 | 8.02 | 0.00 | 0.00 | 0.00 |
May | 58.28 | 1.10 | 57.18 | 201.54 | 0.48 | 0.00 | 0.00 | 0.00 |
June | 54.66 | 0.07 | 54.59 | 214.32 | 0.01 | 0.00 | 0.00 | 0.00 |
July | 54.58 | 0.36 | 54.22 | 245.26 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 63.14 | 4.20 | 58.94 | 265.76 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 83.69 | 19.24 | 64.45 | 266.14 | 0.12 | 0.00 | 0.00 | 0.00 |
October | 109.62 | 43.69 | 65.93 | 269.52 | 0.99 | 0.00 | 0.00 | 0.00 |
November | 121.32 | 58.78 | 62.54 | 245.85 | 10.02 | 0.00 | 0.00 | 0.00 |
December | 112.27 | 55.56 | 56.71 | 196.69 | 28.73 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 85.87 | 25.75 | 60.12 | 218.81 | 11.51 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 54.58 | 0.07 | 54.22 | 172.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 121.32 | 58.78 | 65.93 | 269.52 | 40.55 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.46 | 42.25 | 47.21 | 139.07 | 34.54 | 0.00 | 0.00 | 0.00 |
February | 83.63 | 34.20 | 49.42 | 137.29 | 26.71 | 0.00 | 0.00 | 0.00 |
March | 68.11 | 17.97 | 50.13 | 125.93 | 18.10 | 0.00 | 0.00 | 0.00 |
April | 54.39 | 6.01 | 48.38 | 122.86 | 7.62 | 0.00 | 0.00 | 0.00 |
May | 46.02 | 0.87 | 45.15 | 147.74 | 0.48 | 0.00 | 0.00 | 0.00 |
June | 43.16 | 0.05 | 43.10 | 159.36 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 43.10 | 0.29 | 42.81 | 184.79 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 49.86 | 3.32 | 46.54 | 201.58 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 66.08 | 15.20 | 50.89 | 200.52 | 0.10 | 0.00 | 0.00 | 0.00 |
October | 86.56 | 34.50 | 52.06 | 202.09 | 0.88 | 0.00 | 0.00 | 0.00 |
November | 95.80 | 46.41 | 49.39 | 182.59 | 9.11 | 0.00 | 0.00 | 0.00 |
December | 88.65 | 43.87 | 44.78 | 146.10 | 25.40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 67.80 | 20.34 | 47.47 | 162.66 | 10.18 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 43.10 | 0.05 | 42.81 | 122.86 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 95.80 | 46.41 | 52.06 | 202.09 | 34.54 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 91.52 | 26.33 | 65.20 | 131.47 | 69.00 | 0.00 | 0.00 | 0.00 |
February | 104.45 | 29.88 | 74.57 | 163.96 | 51.98 | 0.00 | 0.00 | 0.00 |
March | 123.39 | 36.53 | 86.86 | 218.53 | 34.06 | 0.00 | 0.00 | 0.00 |
April | 134.92 | 37.90 | 97.01 | 278.83 | 14.05 | 0.00 | 0.00 | 0.00 |
May | 146.78 | 43.93 | 102.85 | 381.31 | 0.85 | 0.00 | 0.00 | 0.00 |
June | 151.62 | 47.77 | 103.85 | 422.71 | 0.01 | 0.00 | 0.00 | 0.00 |
July | 139.07 | 39.71 | 99.35 | 448.78 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 142.68 | 43.30 | 99.38 | 457.88 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 135.96 | 42.77 | 93.19 | 384.79 | 0.17 | 0.00 | 0.00 | 0.00 |
October | 120.94 | 39.21 | 81.73 | 297.23 | 1.65 | 0.00 | 0.00 | 0.00 |
November | 103.98 | 34.12 | 69.86 | 209.01 | 17.78 | 0.00 | 0.00 | 0.00 |
December | 86.71 | 26.11 | 60.60 | 138.60 | 50.20 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 123.57 | 37.32 | 86.25 | 295.17 | 19.85 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 86.71 | 26.11 | 60.60 | 131.47 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 151.62 | 47.77 | 103.85 | 457.88 | 69.00 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 27.55 | 0.00 | 27.55 | 35.53 | 35.96 | 0.00 | 0.00 | 0.00 |
February | 31.58 | 0.00 | 31.58 | 47.37 | 27.22 | 0.00 | 0.00 | 0.00 |
March | 36.28 | 0.00 | 36.28 | 66.50 | 17.92 | 0.00 | 0.00 | 0.00 |
April | 41.01 | 0.16 | 40.84 | 96.00 | 7.37 | 0.00 | 0.00 | 0.00 |
May | 46.10 | 1.41 | 44.69 | 148.29 | 0.42 | 0.00 | 0.00 | 0.00 |
June | 49.28 | 2.76 | 46.52 | 172.09 | 0.01 | 0.00 | 0.00 | 0.00 |
July | 45.28 | 1.36 | 43.92 | 190.03 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 42.19 | 0.42 | 41.76 | 186.04 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 38.34 | 0.01 | 38.33 | 146.84 | 0.10 | 0.00 | 0.00 | 0.00 |
October | 33.97 | 0.00 | 33.97 | 107.00 | 0.85 | 0.00 | 0.00 | 0.00 |
November | 29.17 | 0.00 | 29.17 | 67.32 | 9.13 | 0.00 | 0.00 | 0.00 |
December | 25.71 | 0.00 | 25.71 | 39.86 | 25.99 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 37.23 | 0.51 | 36.71 | 108.95 | 10.34 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 25.71 | 0.00 | 25.71 | 35.53 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 49.28 | 2.76 | 46.52 | 190.03 | 35.96 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 91.52 | 26.33 | 65.20 | 135.37 | 66.76 | 0.00 | 0.00 | 0.00 |
February | 104.45 | 29.88 | 74.57 | 166.98 | 50.45 | 0.00 | 0.00 | 0.00 |
March | 123.39 | 36.53 | 86.86 | 220.43 | 33.28 | 0.00 | 0.00 | 0.00 |
April | 134.92 | 37.90 | 97.01 | 279.76 | 13.85 | 0.00 | 0.00 | 0.00 |
May | 146.78 | 43.93 | 102.85 | 381.33 | 0.84 | 0.00 | 0.00 | 0.00 |
June | 151.62 | 47.77 | 103.85 | 422.28 | 0.01 | 0.00 | 0.00 | 0.00 |
July | 139.07 | 39.71 | 99.35 | 448.64 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 142.68 | 43.30 | 99.38 | 458.43 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 135.96 | 42.77 | 93.19 | 386.58 | 0.16 | 0.00 | 0.00 | 0.00 |
October | 120.94 | 39.21 | 81.73 | 300.35 | 1.52 | 0.00 | 0.00 | 0.00 |
November | 103.98 | 34.12 | 69.86 | 212.54 | 16.93 | 0.00 | 0.00 | 0.00 |
December | 86.71 | 26.11 | 60.60 | 142.03 | 48.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 123.57 | 37.32 | 86.25 | 296.97 | 19.22 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 86.71 | 26.11 | 60.60 | 135.37 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 151.62 | 47.77 | 103.85 | 458.43 | 66.76 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 131.20 | 61.96 | 69.24 | 201.50 | 52.31 | 0.00 | 0.00 | 0.00 |
February | 122.65 | 50.16 | 72.48 | 200.26 | 39.90 | 0.00 | 0.00 | 0.00 |
March | 99.88 | 26.36 | 73.52 | 185.76 | 26.18 | 0.00 | 0.00 | 0.00 |
April | 79.77 | 8.81 | 70.96 | 183.77 | 10.47 | 0.00 | 0.00 | 0.00 |
May | 67.49 | 1.27 | 66.21 | 223.65 | 0.54 | 0.00 | 0.00 | 0.00 |
June | 63.29 | 0.08 | 63.22 | 241.90 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 63.21 | 0.42 | 62.79 | 279.25 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 73.12 | 4.86 | 68.25 | 303.55 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 96.92 | 22.29 | 74.63 | 299.73 | 0.12 | 0.00 | 0.00 | 0.00 |
October | 126.95 | 50.60 | 76.35 | 299.06 | 1.16 | 0.00 | 0.00 | 0.00 |
November | 140.50 | 68.07 | 72.43 | 267.66 | 13.30 | 0.00 | 0.00 | 0.00 |
December | 130.02 | 64.34 | 65.68 | 212.49 | 38.36 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 99.44 | 29.82 | 69.62 | 241.81 | 15.09 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 63.21 | 0.08 | 62.79 | 183.77 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 140.50 | 68.07 | 76.35 | 303.55 | 52.31 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 192.84 | 0.00 | 192.84 | 265.50 | 275.56 | 0.00 | 0.00 | 0.00 |
February | 221.05 | 0.00 | 221.05 | 358.54 | 212.64 | 0.00 | 0.00 | 0.00 |
March | 253.95 | 0.00 | 253.94 | 504.37 | 142.08 | 0.00 | 0.00 | 0.00 |
April | 287.05 | 1.14 | 285.90 | 721.16 | 64.87 | 0.00 | 0.00 | 0.00 |
May | 322.68 | 9.89 | 312.79 | 1083.50 | 5.15 | 0.00 | 0.00 | 0.00 |
June | 344.97 | 19.34 | 325.63 | 1244.77 | 0.19 | 0.00 | 0.00 | 0.00 |
July | 316.98 | 9.53 | 307.45 | 1367.62 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 295.30 | 2.97 | 292.33 | 1341.22 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 268.37 | 0.08 | 268.29 | 1069.19 | 1.07 | 0.00 | 0.00 | 0.00 |
October | 237.81 | 0.00 | 237.81 | 791.60 | 9.60 | 0.00 | 0.00 | 0.00 |
November | 204.15 | 0.00 | 204.15 | 513.78 | 78.27 | 0.00 | 0.00 | 0.00 |
December | 179.99 | 0.00 | 179.99 | 303.17 | 201.74 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 260.58 | 3.59 | 256.99 | 799.65 | 82.04 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 179.99 | 0.00 | 179.99 | 265.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 344.97 | 19.34 | 325.63 | 1367.62 | 275.56 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 192.84 | 0.00 | 192.84 | 258.70 | 289.36 | 0.00 | 0.00 | 0.00 |
February | 221.05 | 0.00 | 221.05 | 349.96 | 225.49 | 0.00 | 0.00 | 0.00 |
March | 253.95 | 0.00 | 253.94 | 493.03 | 152.88 | 0.00 | 0.00 | 0.00 |
April | 287.05 | 1.14 | 285.90 | 705.24 | 71.97 | 0.00 | 0.00 | 0.00 |
May | 322.68 | 9.89 | 312.79 | 1062.33 | 6.38 | 0.00 | 0.00 | 0.00 |
June | 344.97 | 19.34 | 325.63 | 1223.36 | 0.24 | 0.00 | 0.00 | 0.00 |
July | 316.98 | 9.53 | 307.45 | 1348.25 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 295.30 | 2.97 | 292.33 | 1322.41 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 268.37 | 0.08 | 268.29 | 1048.76 | 1.29 | 0.00 | 0.00 | 0.00 |
October | 237.81 | 0.00 | 237.81 | 772.04 | 11.79 | 0.00 | 0.00 | 0.00 |
November | 204.15 | 0.00 | 204.15 | 499.92 | 86.11 | 0.00 | 0.00 | 0.00 |
December | 179.99 | 0.00 | 179.99 | 294.83 | 214.29 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 260.58 | 3.59 | 256.99 | 784.15 | 87.72 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 179.99 | 0.00 | 179.99 | 258.70 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 344.97 | 19.34 | 325.63 | 1348.25 | 289.36 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 27.55 | 0.00 | 27.55 | 38.57 | 43.85 | 0.00 | 0.00 | 0.00 |
February | 31.58 | 0.00 | 31.58 | 51.33 | 35.34 | 0.00 | 0.00 | 0.00 |
March | 36.28 | 0.00 | 36.28 | 71.84 | 23.58 | 0.00 | 0.00 | 0.00 |
April | 41.01 | 0.16 | 40.84 | 102.35 | 11.38 | 0.00 | 0.00 | 0.00 |
May | 46.10 | 1.41 | 44.69 | 154.03 | 1.04 | 0.00 | 0.00 | 0.00 |
June | 49.28 | 2.76 | 46.52 | 176.68 | 0.02 | 0.00 | 0.00 | 0.00 |
July | 45.28 | 1.36 | 43.92 | 195.03 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 42.19 | 0.42 | 41.76 | 190.59 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 38.34 | 0.01 | 38.33 | 150.88 | 0.12 | 0.00 | 0.00 | 0.00 |
October | 33.97 | 0.00 | 33.97 | 111.48 | 1.81 | 0.00 | 0.00 | 0.00 |
November | 29.17 | 0.00 | 29.17 | 73.37 | 13.67 | 0.00 | 0.00 | 0.00 |
December | 25.71 | 0.00 | 25.71 | 44.27 | 32.47 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 37.23 | 0.51 | 36.71 | 113.74 | 13.51 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 25.71 | 0.00 | 25.71 | 38.57 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 49.28 | 2.76 | 46.52 | 195.03 | 43.85 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 185.77 | 56.03 | 129.74 | 287.32 | 155.80 | 0.00 | 0.00 | 0.00 |
February | 202.85 | 54.98 | 147.88 | 340.89 | 126.79 | 0.00 | 0.00 | 0.00 |
March | 224.27 | 55.32 | 168.95 | 427.13 | 85.36 | 0.00 | 0.00 | 0.00 |
April | 273.01 | 79.45 | 193.57 | 599.94 | 42.39 | 0.00 | 0.00 | 0.00 |
May | 304.62 | 97.01 | 207.61 | 811.00 | 3.98 | 0.00 | 0.00 | 0.00 |
June | 298.39 | 91.22 | 207.17 | 858.89 | 0.06 | 0.00 | 0.00 | 0.00 |
July | 278.54 | 80.26 | 198.28 | 923.75 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 285.30 | 87.59 | 197.71 | 939.52 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 268.06 | 82.81 | 185.25 | 788.01 | 0.45 | 0.00 | 0.00 | 0.00 |
October | 243.19 | 79.33 | 163.85 | 627.67 | 6.92 | 0.00 | 0.00 | 0.00 |
November | 203.71 | 64.34 | 139.38 | 446.52 | 50.19 | 0.00 | 0.00 | 0.00 |
December | 165.16 | 45.41 | 119.75 | 288.72 | 117.27 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 244.57 | 72.89 | 171.68 | 613.16 | 48.75 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 165.16 | 45.41 | 119.75 | 287.32 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 304.62 | 97.01 | 207.61 | 939.52 | 155.80 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.46 | 42.25 | 47.21 | 146.37 | 41.33 | 0.00 | 0.00 | 0.00 |
February | 83.63 | 34.20 | 49.42 | 144.54 | 33.99 | 0.00 | 0.00 | 0.00 |
March | 68.11 | 17.97 | 50.13 | 133.47 | 23.25 | 0.00 | 0.00 | 0.00 |
April | 54.39 | 6.01 | 48.38 | 130.56 | 11.48 | 0.00 | 0.00 | 0.00 |
May | 46.02 | 0.87 | 45.15 | 153.86 | 1.08 | 0.00 | 0.00 | 0.00 |
June | 43.16 | 0.05 | 43.10 | 163.58 | 0.02 | 0.00 | 0.00 | 0.00 |
July | 43.10 | 0.29 | 42.81 | 190.17 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 49.86 | 3.32 | 46.54 | 206.98 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 66.08 | 15.20 | 50.89 | 206.56 | 0.11 | 0.00 | 0.00 | 0.00 |
October | 86.56 | 34.50 | 52.06 | 209.79 | 1.82 | 0.00 | 0.00 | 0.00 |
November | 95.80 | 46.41 | 49.39 | 192.35 | 13.28 | 0.00 | 0.00 | 0.00 |
December | 88.65 | 43.87 | 44.78 | 154.52 | 31.16 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 67.80 | 20.34 | 47.47 | 169.56 | 13.03 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 43.10 | 0.05 | 42.81 | 130.56 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 95.80 | 46.41 | 52.06 | 209.79 | 41.33 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.89 | 0.00 | 34.89 | 49.13 | 44.84 | 0.00 | 0.00 | 0.00 |
February | 39.99 | 0.00 | 39.99 | 66.65 | 32.87 | 0.00 | 0.00 | 0.00 |
March | 45.95 | 0.00 | 45.94 | 94.11 | 20.53 | 0.00 | 0.00 | 0.00 |
April | 51.93 | 0.21 | 51.73 | 135.22 | 7.76 | 0.00 | 0.00 | 0.00 |
May | 58.38 | 1.79 | 56.59 | 203.05 | 0.31 | 0.00 | 0.00 | 0.00 |
June | 62.41 | 3.50 | 58.91 | 232.03 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 57.35 | 1.72 | 55.63 | 251.64 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 53.43 | 0.54 | 52.89 | 245.93 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 48.55 | 0.01 | 48.54 | 198.62 | 0.07 | 0.00 | 0.00 | 0.00 |
October | 43.03 | 0.00 | 43.03 | 148.81 | 0.73 | 0.00 | 0.00 | 0.00 |
November | 36.94 | 0.00 | 36.94 | 95.89 | 9.99 | 0.00 | 0.00 | 0.00 |
December | 32.57 | 0.00 | 32.57 | 56.30 | 31.49 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 47.15 | 0.65 | 46.50 | 148.59 | 12.30 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 32.57 | 0.00 | 32.57 | 49.13 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 62.41 | 3.50 | 58.91 | 251.64 | 44.84 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 31.22 | 0.00 | 31.22 | 43.96 | 40.12 | 0.00 | 0.00 | 0.00 |
February | 35.78 | 0.00 | 35.78 | 59.63 | 29.41 | 0.00 | 0.00 | 0.00 |
March | 41.11 | 0.00 | 41.11 | 84.20 | 18.37 | 0.00 | 0.00 | 0.00 |
April | 46.47 | 0.19 | 46.28 | 120.98 | 6.94 | 0.00 | 0.00 | 0.00 |
May | 52.23 | 1.60 | 50.63 | 181.67 | 0.28 | 0.00 | 0.00 | 0.00 |
June | 55.84 | 3.13 | 52.71 | 207.60 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 51.31 | 1.54 | 49.77 | 225.15 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 47.80 | 0.48 | 47.32 | 220.03 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 43.44 | 0.01 | 43.43 | 177.70 | 0.07 | 0.00 | 0.00 | 0.00 |
October | 38.49 | 0.00 | 38.49 | 133.14 | 0.65 | 0.00 | 0.00 | 0.00 |
November | 33.05 | 0.00 | 33.05 | 85.79 | 8.94 | 0.00 | 0.00 | 0.00 |
December | 29.14 | 0.00 | 29.14 | 50.37 | 28.17 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 42.18 | 0.58 | 41.60 | 132.95 | 11.01 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 29.14 | 0.00 | 29.14 | 43.96 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 55.84 | 3.13 | 52.71 | 225.15 | 40.12 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 333.97 | 157.72 | 176.25 | 539.68 | 123.17 | 0.00 | 0.00 | 0.00 |
February | 312.20 | 127.69 | 184.51 | 538.14 | 92.85 | 0.00 | 0.00 | 0.00 |
March | 254.26 | 67.10 | 187.16 | 502.37 | 60.21 | 0.00 | 0.00 | 0.00 |
April | 203.05 | 22.43 | 180.62 | 499.71 | 23.61 | 0.00 | 0.00 | 0.00 |
May | 171.79 | 3.24 | 168.55 | 595.84 | 1.07 | 0.00 | 0.00 | 0.00 |
June | 161.12 | 0.20 | 160.92 | 635.32 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 160.89 | 1.06 | 159.83 | 721.54 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 186.13 | 12.38 | 173.74 | 783.43 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 246.71 | 56.73 | 189.98 | 788.24 | 0.22 | 0.00 | 0.00 | 0.00 |
October | 323.15 | 128.80 | 194.35 | 798.39 | 2.10 | 0.00 | 0.00 | 0.00 |
November | 357.64 | 173.27 | 184.37 | 719.72 | 28.19 | 0.00 | 0.00 | 0.00 |
December | 330.96 | 163.78 | 167.18 | 569.92 | 87.62 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 253.13 | 75.92 | 177.21 | 641.65 | 34.68 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 160.89 | 0.20 | 159.83 | 499.71 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 357.64 | 173.27 | 194.35 | 798.39 | 123.17 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.121183E+10 | 0.572299E+09 | 0.639534E+09 | 0.195342E+10 | 0.453747E+09 |
February | 0.102322E+10 | 0.418497E+09 | 0.604726E+09 | 0.174866E+10 | 0.315089E+09 |
March | 0.922589E+09 | 0.243477E+09 | 0.679112E+09 | 0.178217E+10 | 0.235245E+09 |
April | 0.713015E+09 | 78751018.39 | 0.634264E+09 | 0.168076E+10 | 97617447.38 |
May | 0.623352E+09 | 11762118.07 | 0.611590E+09 | 0.203964E+10 | 6365833.21 |
June | 0.565768E+09 | 699698.30 | 0.565069E+09 | 0.209581E+10 | 130328.87 |
July | 0.583813E+09 | 3863005.71 | 0.579950E+09 | 0.248752E+10 | 0.00 |
August | 0.675368E+09 | 44924291.99 | 0.630443E+09 | 0.269717E+10 | 0.00 |
September | 0.866341E+09 | 0.199212E+09 | 0.667129E+09 | 0.262727E+10 | 1296296.11 |
October | 0.117257E+10 | 0.467356E+09 | 0.705217E+09 | 0.275936E+10 | 12964530.08 |
November | 0.125588E+10 | 0.608453E+09 | 0.647429E+09 | 0.244551E+10 | 0.120311E+09 |
December | 0.120092E+10 | 0.594298E+09 | 0.606627E+09 | 0.204487E+10 | 0.334350E+09 |
Annual Sum or Average | 0.108147E+11 | 0.324359E+10 | 0.757109E+10 | 0.263622E+11 | 0.157712E+10 |
Minimum of Months | 0.565768E+09 | 699698.30 | 0.565069E+09 | 0.168076E+10 | 0.00 |
Maximum of Months | 0.125588E+10 | 0.608453E+09 | 0.705217E+09 | 0.275936E+10 | 0.453747E+09 |
Report: WindowEnergyReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.341244E+10 | 0.161156E+10 | 0.180089E+10 | 0.545832E+10 | 0.130081E+10 |
February | 0.288133E+10 | 0.117846E+10 | 0.170287E+10 | 0.489006E+10 | 0.912422E+09 |
March | 0.259795E+10 | 0.685614E+09 | 0.191234E+10 | 0.497997E+10 | 0.688424E+09 |
April | 0.200780E+10 | 0.221758E+09 | 0.178605E+10 | 0.469112E+10 | 0.297611E+09 |
May | 0.175532E+10 | 33121348.96 | 0.172220E+10 | 0.567103E+10 | 22756113.93 |
June | 0.159317E+10 | 1970304.27 | 0.159120E+10 | 0.582055E+10 | 732516.44 |
July | 0.164398E+10 | 10877969.36 | 0.163310E+10 | 0.693586E+10 | 0.00 |
August | 0.190179E+10 | 0.126504E+09 | 0.177529E+10 | 0.754500E+10 | 0.00 |
September | 0.243956E+10 | 0.560968E+09 | 0.187859E+10 | 0.733518E+10 | 4728417.49 |
October | 0.330189E+10 | 0.131604E+10 | 0.198584E+10 | 0.771084E+10 | 48707899.36 |
November | 0.353648E+10 | 0.171336E+10 | 0.182312E+10 | 0.685525E+10 | 0.370817E+09 |
December | 0.338173E+10 | 0.167350E+10 | 0.170822E+10 | 0.572246E+10 | 0.966535E+09 |
Annual Sum or Average | 0.304534E+11 | 0.913374E+10 | 0.213197E+11 | 0.736156E+11 | 0.461354E+10 |
Minimum of Months | 0.159317E+10 | 1970304.27 | 0.159120E+10 | 0.469112E+10 | 0.00 |
Maximum of Months | 0.353648E+10 | 0.171336E+10 | 0.198584E+10 | 0.771084E+10 | 0.130081E+10 |
Report: WindowEnergyReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.443296E+10 | 0.209350E+10 | 0.233945E+10 | 0.725440E+10 | 0.171945E+10 |
February | 0.374301E+10 | 0.153089E+10 | 0.221212E+10 | 0.651613E+10 | 0.120500E+10 |
March | 0.337488E+10 | 0.890652E+09 | 0.248423E+10 | 0.664881E+10 | 0.916339E+09 |
April | 0.260825E+10 | 0.288076E+09 | 0.232018E+10 | 0.627912E+10 | 0.400565E+09 |
May | 0.228026E+10 | 43026517.26 | 0.223723E+10 | 0.760148E+10 | 31360828.94 |
June | 0.206961E+10 | 2559537.38 | 0.206705E+10 | 0.780367E+10 | 982876.98 |
July | 0.213562E+10 | 14131101.28 | 0.212149E+10 | 0.931536E+10 | 0.00 |
August | 0.247053E+10 | 0.164336E+09 | 0.230620E+10 | 0.101460E+11 | 0.00 |
September | 0.316913E+10 | 0.728729E+09 | 0.244040E+10 | 0.986178E+10 | 6094612.57 |
October | 0.428934E+10 | 0.170962E+10 | 0.257973E+10 | 0.103568E+11 | 59553177.28 |
November | 0.459409E+10 | 0.222576E+10 | 0.236833E+10 | 0.916582E+10 | 0.480760E+09 |
December | 0.439305E+10 | 0.217398E+10 | 0.221908E+10 | 0.761170E+10 | 0.127464E+10 |
Annual Sum or Average | 0.395607E+11 | 0.118652E+11 | 0.276955E+11 | 0.985611E+11 | 0.609475E+10 |
Minimum of Months | 0.206961E+10 | 2559537.38 | 0.206705E+10 | 0.627912E+10 | 0.00 |
Maximum of Months | 0.459409E+10 | 0.222576E+10 | 0.257973E+10 | 0.103568E+11 | 0.171945E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.239601E+09 | 0.113153E+09 | 0.126448E+09 | 0.377373E+09 | 92863752.46 |
February | 0.202309E+09 | 82744003.94 | 0.119565E+09 | 0.337219E+09 | 64623696.24 |
March | 0.182413E+09 | 48139503.57 | 0.134273E+09 | 0.342632E+09 | 48566088.85 |
April | 0.140977E+09 | 15570428.87 | 0.125406E+09 | 0.323414E+09 | 19990249.89 |
May | 0.123249E+09 | 2325572.76 | 0.120923E+09 | 0.399359E+09 | 1355874.05 |
June | 0.111863E+09 | 138342.37 | 0.111725E+09 | 0.415240E+09 | 16723.84 |
July | 0.115431E+09 | 763782.57 | 0.114667E+09 | 0.497821E+09 | 0.00 |
August | 0.133533E+09 | 8882304.10 | 0.124651E+09 | 0.542736E+09 | 0.00 |
September | 0.171292E+09 | 39387619.85 | 0.131904E+09 | 0.523382E+09 | 267643.58 |
October | 0.231839E+09 | 92404393.57 | 0.139435E+09 | 0.545877E+09 | 2488528.25 |
November | 0.248310E+09 | 0.120302E+09 | 0.128009E+09 | 0.478557E+09 | 24002648.59 |
December | 0.237444E+09 | 0.117503E+09 | 0.119941E+09 | 0.396334E+09 | 68194634.01 |
Annual Sum or Average | 0.213826E+10 | 0.641314E+09 | 0.149695E+10 | 0.517994E+10 | 0.322370E+09 |
Minimum of Months | 0.111863E+09 | 138342.37 | 0.111725E+09 | 0.323414E+09 | 0.00 |
Maximum of Months | 0.248310E+09 | 0.120302E+09 | 0.139435E+09 | 0.545877E+09 | 92863752.46 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.245132E+09 | 70510841.87 | 0.174622E+09 | 0.359708E+09 | 0.185963E+09 |
February | 0.252696E+09 | 72293154.79 | 0.180403E+09 | 0.404796E+09 | 0.125970E+09 |
March | 0.330482E+09 | 97845769.85 | 0.232636E+09 | 0.595758E+09 | 91496729.76 |
April | 0.349707E+09 | 98244720.35 | 0.251462E+09 | 0.733512E+09 | 36776656.20 |
May | 0.393123E+09 | 0.117658E+09 | 0.275466E+09 | 0.103093E+10 | 2360054.62 |
June | 0.393008E+09 | 0.123828E+09 | 0.269180E+09 | 0.110314E+10 | 31696.39 |
July | 0.372477E+09 | 0.106371E+09 | 0.266106E+09 | 0.121003E+10 | 0.00 |
August | 0.382161E+09 | 0.115975E+09 | 0.266186E+09 | 0.123422E+10 | 0.00 |
September | 0.352414E+09 | 0.110866E+09 | 0.241548E+09 | 0.100445E+10 | 472730.64 |
October | 0.323913E+09 | 0.105009E+09 | 0.218905E+09 | 0.803216E+09 | 4621900.43 |
November | 0.269513E+09 | 88428078.83 | 0.181085E+09 | 0.548698E+09 | 46754376.57 |
December | 0.232238E+09 | 69919888.64 | 0.162319E+09 | 0.378701E+09 | 0.135001E+09 |
Annual Sum or Average | 0.389687E+10 | 0.117695E+10 | 0.271992E+10 | 0.940716E+10 | 0.629448E+09 |
Minimum of Months | 0.232238E+09 | 69919888.64 | 0.162319E+09 | 0.359708E+09 | 0.00 |
Maximum of Months | 0.393123E+09 | 0.123828E+09 | 0.275466E+09 | 0.123422E+10 | 0.185963E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 73789426.05 | 0.00 | 73789426.05 | 97825699.52 | 97078968.16 |
February | 76398307.43 | 0.00 | 76398307.43 | 0.117667E+09 | 66014681.68 |
March | 97170368.09 | 1164.90 | 97169203.18 | 0.182001E+09 | 48130847.59 |
April | 0.106293E+09 | 423648.45 | 0.105869E+09 | 0.252818E+09 | 19248910.97 |
May | 0.123473E+09 | 3786056.10 | 0.119687E+09 | 0.400731E+09 | 1184060.45 |
June | 0.127741E+09 | 7161555.05 | 0.120580E+09 | 0.448980E+09 | 18580.62 |
July | 0.121291E+09 | 3647867.79 | 0.117643E+09 | 0.511504E+09 | 0.00 |
August | 0.112995E+09 | 1136187.01 | 0.111859E+09 | 0.500407E+09 | 0.00 |
September | 99376681.90 | 30232.96 | 99346448.94 | 0.382431E+09 | 261280.05 |
October | 90994677.48 | 0.00 | 90994677.48 | 0.288513E+09 | 2405821.08 |
November | 75597061.82 | 0.00 | 75597061.82 | 0.176716E+09 | 24051439.18 |
December | 68872881.78 | 0.00 | 68872881.78 | 0.109513E+09 | 70004292.92 |
Annual Sum or Average | 0.117399E+10 | 16186712.25 | 0.115781E+10 | 0.346911E+10 | 0.328399E+09 |
Minimum of Months | 68872881.78 | 0.00 | 68872881.78 | 97825699.52 | 0.00 |
Maximum of Months | 0.127741E+09 | 7161555.05 | 0.120580E+09 | 0.511504E+09 | 97078968.16 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.245132E+09 | 70510841.87 | 0.174622E+09 | 0.370301E+09 | 0.180216E+09 |
February | 0.252696E+09 | 72293154.79 | 0.180403E+09 | 0.412346E+09 | 0.122385E+09 |
March | 0.330482E+09 | 97845769.85 | 0.232636E+09 | 0.601044E+09 | 89434336.53 |
April | 0.349707E+09 | 98244720.35 | 0.251462E+09 | 0.735936E+09 | 36260983.62 |
May | 0.393123E+09 | 0.117658E+09 | 0.275466E+09 | 0.103100E+10 | 2336706.52 |
June | 0.393008E+09 | 0.123828E+09 | 0.269180E+09 | 0.110204E+10 | 32379.38 |
July | 0.372477E+09 | 0.106371E+09 | 0.266106E+09 | 0.120964E+10 | 0.00 |
August | 0.382161E+09 | 0.115975E+09 | 0.266186E+09 | 0.123568E+10 | 0.00 |
September | 0.352414E+09 | 0.110866E+09 | 0.241548E+09 | 0.100903E+10 | 446797.28 |
October | 0.323913E+09 | 0.105009E+09 | 0.218905E+09 | 0.811471E+09 | 4272306.67 |
November | 0.269513E+09 | 88428078.83 | 0.181085E+09 | 0.557785E+09 | 44590116.56 |
December | 0.232238E+09 | 69919888.64 | 0.162319E+09 | 0.388005E+09 | 0.130204E+09 |
Annual Sum or Average | 0.389687E+10 | 0.117695E+10 | 0.271992E+10 | 0.946429E+10 | 0.610178E+09 |
Minimum of Months | 0.232238E+09 | 69919888.64 | 0.162319E+09 | 0.370301E+09 | 0.00 |
Maximum of Months | 0.393123E+09 | 0.123828E+09 | 0.275466E+09 | 0.123568E+10 | 0.180216E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.191643E+09 | 90504684.80 | 0.101138E+09 | 0.288477E+09 | 0.100074E+09 |
February | 0.161815E+09 | 66182041.33 | 95633313.98 | 0.258692E+09 | 73386535.34 |
March | 0.145901E+09 | 38503945.46 | 0.107397E+09 | 0.262577E+09 | 58518539.24 |
April | 0.112759E+09 | 12453866.36 | 0.100305E+09 | 0.246218E+09 | 29055019.29 |
May | 98579426.39 | 1860088.28 | 96719338.11 | 0.301296E+09 | 3736280.20 |
June | 89472966.04 | 110651.89 | 89362314.15 | 0.313513E+09 | 128663.36 |
July | 92326627.88 | 610904.57 | 91715723.31 | 0.379660E+09 | 0.00 |
August | 0.106805E+09 | 7104430.40 | 99700743.65 | 0.415733E+09 | 0.00 |
September | 0.137006E+09 | 31503830.62 | 0.105502E+09 | 0.398400E+09 | 839817.37 |
October | 0.185434E+09 | 73908816.38 | 0.111525E+09 | 0.416037E+09 | 6700747.40 |
November | 0.198609E+09 | 96222111.04 | 0.102386E+09 | 0.368092E+09 | 33730673.98 |
December | 0.189918E+09 | 93983606.78 | 95933929.30 | 0.304270E+09 | 78374987.69 |
Annual Sum or Average | 0.171027E+10 | 0.512949E+09 | 0.119732E+10 | 0.395296E+10 | 0.384546E+09 |
Minimum of Months | 89472966.04 | 110651.89 | 89362314.15 | 0.246218E+09 | 0.00 |
Maximum of Months | 0.198609E+09 | 96222111.04 | 0.111525E+09 | 0.416037E+09 | 0.100074E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 59039365.81 | 0.00 | 59039365.81 | 80982707.35 | 78076789.05 |
February | 61126747.57 | 0.00 | 61126747.57 | 98317636.45 | 52188416.72 |
March | 77746598.86 | 932.05 | 77745666.81 | 0.152748E+09 | 36815514.49 |
April | 85045784.63 | 338963.68 | 84706820.94 | 0.211919E+09 | 13869263.81 |
May | 98791330.93 | 3029246.37 | 95762084.56 | 0.336534E+09 | 622889.14 |
June | 0.102206E+09 | 5730003.48 | 96476416.12 | 0.376630E+09 | 1137.14 |
July | 97045751.09 | 2918681.07 | 94127070.02 | 0.428459E+09 | 0.00 |
August | 90407823.18 | 909070.09 | 89498753.09 | 0.420383E+09 | 0.00 |
September | 79511883.87 | 24189.57 | 79487694.30 | 0.322787E+09 | 130285.48 |
October | 72805391.48 | 0.00 | 72805391.48 | 0.244466E+09 | 1390449.26 |
November | 60485666.11 | 0.00 | 60485666.11 | 0.149203E+09 | 17639523.20 |
December | 55105609.02 | 0.00 | 55105609.02 | 91474927.12 | 55440317.53 |
Annual Sum or Average | 0.939318E+09 | 12951086.32 | 0.926367E+09 | 0.291390E+10 | 0.256175E+09 |
Minimum of Months | 55105609.02 | 0.00 | 55105609.02 | 80982707.35 | 0.00 |
Maximum of Months | 0.102206E+09 | 5730003.48 | 96476416.12 | 0.428459E+09 | 78076789.05 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.248801E+09 | 75041170.44 | 0.173760E+09 | 0.355850E+09 | 0.173264E+09 |
February | 0.245390E+09 | 66506363.82 | 0.178884E+09 | 0.387257E+09 | 0.118010E+09 |
March | 0.300358E+09 | 74088328.54 | 0.226270E+09 | 0.542934E+09 | 85140178.09 |
April | 0.353850E+09 | 0.102969E+09 | 0.250881E+09 | 0.746744E+09 | 34681166.91 |
May | 0.407970E+09 | 0.129921E+09 | 0.278049E+09 | 0.106145E+10 | 2172063.78 |
June | 0.386742E+09 | 0.118227E+09 | 0.268516E+09 | 0.109702E+10 | 26274.39 |
July | 0.373049E+09 | 0.107491E+09 | 0.265558E+09 | 0.121741E+10 | 0.00 |
August | 0.382107E+09 | 0.117315E+09 | 0.264792E+09 | 0.123784E+10 | 0.00 |
September | 0.347433E+09 | 0.107327E+09 | 0.240106E+09 | 0.999818E+09 | 505040.90 |
October | 0.325697E+09 | 0.106247E+09 | 0.219449E+09 | 0.811265E+09 | 4575663.99 |
November | 0.264031E+09 | 83387581.41 | 0.180644E+09 | 0.540702E+09 | 44346215.50 |
December | 0.221202E+09 | 60821109.14 | 0.160381E+09 | 0.353961E+09 | 0.126871E+09 |
Annual Sum or Average | 0.385663E+10 | 0.114934E+10 | 0.270729E+10 | 0.935225E+10 | 0.589592E+09 |
Minimum of Months | 0.221202E+09 | 60821109.14 | 0.160381E+09 | 0.353961E+09 | 0.00 |
Maximum of Months | 0.407970E+09 | 0.129921E+09 | 0.278049E+09 | 0.123784E+10 | 0.173264E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.239601E+09 | 0.113153E+09 | 0.126448E+09 | 0.375697E+09 | 92325957.54 |
February | 0.202309E+09 | 82744003.94 | 0.119565E+09 | 0.336065E+09 | 64065341.67 |
March | 0.182413E+09 | 48139503.57 | 0.134273E+09 | 0.342150E+09 | 47793216.87 |
April | 0.140977E+09 | 15570428.87 | 0.125406E+09 | 0.322221E+09 | 19725794.10 |
May | 0.123249E+09 | 2325572.76 | 0.120923E+09 | 0.398373E+09 | 1304824.57 |
June | 0.111863E+09 | 138342.37 | 0.111725E+09 | 0.415063E+09 | 15135.41 |
July | 0.115431E+09 | 763782.57 | 0.114667E+09 | 0.497523E+09 | 0.00 |
August | 0.133533E+09 | 8882304.10 | 0.124651E+09 | 0.542452E+09 | 0.00 |
September | 0.171292E+09 | 39387619.85 | 0.131904E+09 | 0.523187E+09 | 259779.45 |
October | 0.231839E+09 | 92404393.57 | 0.139435E+09 | 0.545319E+09 | 2420753.21 |
November | 0.248310E+09 | 0.120302E+09 | 0.128009E+09 | 0.477858E+09 | 23658398.42 |
December | 0.237444E+09 | 0.117503E+09 | 0.119941E+09 | 0.395373E+09 | 67579722.18 |
Annual Sum or Average | 0.213826E+10 | 0.641314E+09 | 0.149695E+10 | 0.517128E+10 | 0.319149E+09 |
Minimum of Months | 0.111863E+09 | 138342.37 | 0.111725E+09 | 0.322221E+09 | 0.00 |
Maximum of Months | 0.248310E+09 | 0.120302E+09 | 0.139435E+09 | 0.545319E+09 | 92325957.54 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 73789426.05 | 0.00 | 73789426.05 | 96317372.45 | 96427667.78 |
February | 76398307.43 | 0.00 | 76398307.43 | 0.116460E+09 | 65427321.29 |
March | 97170368.09 | 1164.90 | 97169203.18 | 0.181395E+09 | 47366831.87 |
April | 0.106293E+09 | 423648.45 | 0.105869E+09 | 0.251538E+09 | 18978219.07 |
May | 0.123473E+09 | 3786056.10 | 0.119687E+09 | 0.399750E+09 | 1133593.37 |
June | 0.127741E+09 | 7161555.05 | 0.120580E+09 | 0.448832E+09 | 17001.16 |
July | 0.121291E+09 | 3647867.79 | 0.117643E+09 | 0.511239E+09 | 0.00 |
August | 0.112995E+09 | 1136187.01 | 0.111859E+09 | 0.500160E+09 | 0.00 |
September | 99376681.90 | 30232.96 | 99346448.94 | 0.382209E+09 | 253441.34 |
October | 90994677.48 | 0.00 | 90994677.48 | 0.287790E+09 | 2342355.40 |
November | 75597061.82 | 0.00 | 75597061.82 | 0.175744E+09 | 23692064.26 |
December | 68872881.78 | 0.00 | 68872881.78 | 0.108575E+09 | 69228695.62 |
Annual Sum or Average | 0.117399E+10 | 16186712.25 | 0.115781E+10 | 0.346001E+10 | 0.324867E+09 |
Minimum of Months | 68872881.78 | 0.00 | 68872881.78 | 96317372.45 | 0.00 |
Maximum of Months | 0.127741E+09 | 7161555.05 | 0.120580E+09 | 0.511239E+09 | 96427667.78 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.248801E+09 | 75041170.44 | 0.173760E+09 | 0.366664E+09 | 0.167358E+09 |
February | 0.245390E+09 | 66506363.82 | 0.178884E+09 | 0.394755E+09 | 0.114433E+09 |
March | 0.300358E+09 | 74088328.54 | 0.226270E+09 | 0.547999E+09 | 83138169.70 |
April | 0.353850E+09 | 0.102969E+09 | 0.250881E+09 | 0.749064E+09 | 34195455.58 |
May | 0.407970E+09 | 0.129921E+09 | 0.278049E+09 | 0.106154E+10 | 2150283.50 |
June | 0.386742E+09 | 0.118227E+09 | 0.268516E+09 | 0.109597E+10 | 26966.35 |
July | 0.373049E+09 | 0.107491E+09 | 0.265558E+09 | 0.121703E+10 | 0.00 |
August | 0.382107E+09 | 0.117315E+09 | 0.264792E+09 | 0.123930E+10 | 0.00 |
September | 0.347433E+09 | 0.107327E+09 | 0.240106E+09 | 0.100433E+10 | 479715.97 |
October | 0.325697E+09 | 0.106247E+09 | 0.219449E+09 | 0.819259E+09 | 4232127.20 |
November | 0.264031E+09 | 83387581.41 | 0.180644E+09 | 0.549445E+09 | 42276055.01 |
December | 0.221202E+09 | 60821109.14 | 0.160381E+09 | 0.363522E+09 | 0.122007E+09 |
Annual Sum or Average | 0.385663E+10 | 0.114934E+10 | 0.270729E+10 | 0.940887E+10 | 0.570297E+09 |
Minimum of Months | 0.221202E+09 | 60821109.14 | 0.160381E+09 | 0.363522E+09 | 0.00 |
Maximum of Months | 0.407970E+09 | 0.129921E+09 | 0.278049E+09 | 0.123930E+10 | 0.167358E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93449652.24 | 0.00 | 93449652.24 | 0.137083E+09 | 0.117018E+09 |
February | 96753635.90 | 0.00 | 96753635.90 | 0.167066E+09 | 76969929.01 |
March | 0.123060E+09 | 1475.28 | 0.123059E+09 | 0.258564E+09 | 53489809.88 |
April | 0.134614E+09 | 536524.03 | 0.134077E+09 | 0.355412E+09 | 20198679.52 |
May | 0.156371E+09 | 4794801.17 | 0.151576E+09 | 0.541722E+09 | 1121612.95 |
June | 0.161776E+09 | 9069657.60 | 0.152706E+09 | 0.598946E+09 | 23343.49 |
July | 0.153608E+09 | 4619794.39 | 0.148988E+09 | 0.674659E+09 | 0.00 |
August | 0.143101E+09 | 1438909.16 | 0.141662E+09 | 0.657678E+09 | 0.00 |
September | 0.125854E+09 | 38288.13 | 0.125816E+09 | 0.509242E+09 | 319572.23 |
October | 0.115239E+09 | 0.00 | 0.115239E+09 | 0.391630E+09 | 2766525.84 |
November | 95738908.88 | 0.00 | 95738908.88 | 0.249038E+09 | 27171568.34 |
December | 87223159.14 | 0.00 | 87223159.14 | 0.156456E+09 | 81849520.76 |
Annual Sum or Average | 0.148679E+10 | 20499449.75 | 0.146629E+10 | 0.469750E+10 | 0.380928E+09 |
Minimum of Months | 87223159.14 | 0.00 | 87223159.14 | 0.137083E+09 | 0.00 |
Maximum of Months | 0.161776E+09 | 9069657.60 | 0.152706E+09 | 0.674659E+09 | 0.117018E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 34449411.26 | 0.00 | 34449411.26 | 50534546.71 | 43137628.81 |
February | 35667396.45 | 0.00 | 35667396.45 | 61587450.67 | 28374302.91 |
March | 45365063.15 | 543.85 | 45364519.30 | 95317498.72 | 19718558.76 |
April | 49624130.79 | 197784.97 | 49426345.82 | 0.131020E+09 | 7446069.63 |
May | 57644643.40 | 1767562.25 | 55877081.15 | 0.199701E+09 | 413472.98 |
June | 59637344.24 | 3343451.34 | 56293892.90 | 0.220796E+09 | 8605.38 |
July | 56626099.29 | 1703047.50 | 54923051.79 | 0.248707E+09 | 0.00 |
August | 52752874.96 | 530441.50 | 52222433.46 | 0.242447E+09 | 0.00 |
September | 46395105.20 | 14114.59 | 46380990.61 | 0.187728E+09 | 117807.56 |
October | 42481873.56 | 0.00 | 42481873.56 | 0.144371E+09 | 1019856.37 |
November | 35293326.05 | 0.00 | 35293326.05 | 91805543.42 | 10016565.18 |
December | 32154068.08 | 0.00 | 32154068.08 | 57676023.11 | 30173122.47 |
Annual Sum or Average | 0.548091E+09 | 7556945.99 | 0.540534E+09 | 0.173169E+10 | 0.140426E+09 |
Minimum of Months | 32154068.08 | 0.00 | 32154068.08 | 50534546.71 | 0.00 |
Maximum of Months | 59637344.24 | 3343451.34 | 56293892.90 | 0.248707E+09 | 43137628.81 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.111797E+09 | 52796899.32 | 58999917.39 | 0.183946E+09 | 40019651.85 |
February | 94396760.14 | 38608018.81 | 55788741.33 | 0.165950E+09 | 27045892.64 |
March | 85112998.79 | 22461698.38 | 62651300.41 | 0.171389E+09 | 19508882.52 |
April | 65779073.11 | 7265099.37 | 58513973.74 | 0.164252E+09 | 7654213.09 |
May | 57507388.28 | 1085102.88 | 56422285.41 | 0.198880E+09 | 476580.44 |
June | 52195034.88 | 64549.99 | 52130484.88 | 0.204668E+09 | 7883.18 |
July | 53859749.77 | 356377.87 | 53503371.90 | 0.242027E+09 | 0.00 |
August | 62305968.29 | 4144447.30 | 58161520.99 | 0.262255E+09 | 0.00 |
September | 79923968.40 | 18378104.70 | 61545863.70 | 0.254159E+09 | 115211.96 |
October | 0.108175E+09 | 43115517.68 | 65059579.05 | 0.265964E+09 | 981213.20 |
November | 0.115861E+09 | 56132222.55 | 59728279.89 | 0.234782E+09 | 9573073.28 |
December | 0.110790E+09 | 54826366.57 | 55964108.58 | 0.194099E+09 | 28348647.89 |
Annual Sum or Average | 0.997704E+09 | 0.299234E+09 | 0.698469E+09 | 0.254237E+10 | 0.133731E+09 |
Minimum of Months | 52195034.88 | 64549.99 | 52130484.88 | 0.164252E+09 | 0.00 |
Maximum of Months | 0.115861E+09 | 56132222.55 | 65059579.05 | 0.265964E+09 | 40019651.85 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.303439E+09 | 0.143302E+09 | 0.160138E+09 | 0.499268E+09 | 0.108622E+09 |
February | 0.256212E+09 | 0.104790E+09 | 0.151422E+09 | 0.450422E+09 | 73408084.73 |
March | 0.231014E+09 | 60965643.83 | 0.170048E+09 | 0.465185E+09 | 52951097.62 |
April | 0.178538E+09 | 19718965.73 | 0.158819E+09 | 0.445815E+09 | 20775099.96 |
May | 0.156087E+09 | 2945191.16 | 0.153142E+09 | 0.539800E+09 | 1293536.79 |
June | 0.141668E+09 | 175201.88 | 0.141493E+09 | 0.555510E+09 | 21396.57 |
July | 0.146186E+09 | 967282.44 | 0.145219E+09 | 0.656910E+09 | 0.00 |
August | 0.169111E+09 | 11248877.69 | 0.157862E+09 | 0.711812E+09 | 0.00 |
September | 0.216930E+09 | 49881935.32 | 0.167048E+09 | 0.689840E+09 | 312708.81 |
October | 0.293609E+09 | 0.117024E+09 | 0.176585E+09 | 0.721880E+09 | 2663213.33 |
November | 0.314469E+09 | 0.152354E+09 | 0.162115E+09 | 0.637248E+09 | 25983279.01 |
December | 0.300708E+09 | 0.148810E+09 | 0.151898E+09 | 0.526824E+09 | 76944028.97 |
Annual Sum or Average | 0.270797E+10 | 0.812183E+09 | 0.189579E+10 | 0.690051E+10 | 0.362974E+09 |
Minimum of Months | 0.141668E+09 | 175201.88 | 0.141493E+09 | 0.445815E+09 | 0.00 |
Maximum of Months | 0.314469E+09 | 0.152354E+09 | 0.176585E+09 | 0.721880E+09 | 0.108622E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.239601E+09 | 0.113153E+09 | 0.126448E+09 | 0.372475E+09 | 92503210.61 |
February | 0.202309E+09 | 82744003.94 | 0.119565E+09 | 0.332137E+09 | 64623615.62 |
March | 0.182413E+09 | 48139503.57 | 0.134273E+09 | 0.337278E+09 | 48472788.14 |
April | 0.140977E+09 | 15570428.87 | 0.125406E+09 | 0.318456E+09 | 19750983.09 |
May | 0.123249E+09 | 2325572.76 | 0.120923E+09 | 0.395703E+09 | 1284578.61 |
June | 0.111863E+09 | 138342.37 | 0.111725E+09 | 0.413050E+09 | 11492.16 |
July | 0.115431E+09 | 763782.57 | 0.114667E+09 | 0.494950E+09 | 0.00 |
August | 0.133533E+09 | 8882304.10 | 0.124651E+09 | 0.539901E+09 | 0.00 |
September | 0.171292E+09 | 39387619.85 | 0.131904E+09 | 0.519757E+09 | 254807.65 |
October | 0.231839E+09 | 92404393.57 | 0.139435E+09 | 0.541269E+09 | 2354096.44 |
November | 0.248310E+09 | 0.120302E+09 | 0.128009E+09 | 0.473265E+09 | 23608405.35 |
December | 0.237444E+09 | 0.117503E+09 | 0.119941E+09 | 0.391319E+09 | 68038953.80 |
Annual Sum or Average | 0.213826E+10 | 0.641314E+09 | 0.149695E+10 | 0.512956E+10 | 0.320903E+09 |
Minimum of Months | 0.111863E+09 | 138342.37 | 0.111725E+09 | 0.318456E+09 | 0.00 |
Maximum of Months | 0.248310E+09 | 0.120302E+09 | 0.139435E+09 | 0.541269E+09 | 92503210.61 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.245132E+09 | 70510841.87 | 0.174622E+09 | 0.352127E+09 | 0.184820E+09 |
February | 0.252696E+09 | 72293154.79 | 0.180403E+09 | 0.396644E+09 | 0.125753E+09 |
March | 0.330482E+09 | 97845769.85 | 0.232636E+09 | 0.585318E+09 | 91216213.15 |
April | 0.349707E+09 | 98244720.35 | 0.251462E+09 | 0.722737E+09 | 36420313.87 |
May | 0.393123E+09 | 0.117658E+09 | 0.275466E+09 | 0.102130E+10 | 2267750.56 |
June | 0.393008E+09 | 0.123828E+09 | 0.269180E+09 | 0.109566E+10 | 27235.63 |
July | 0.372477E+09 | 0.106371E+09 | 0.266106E+09 | 0.120202E+10 | 0.00 |
August | 0.382161E+09 | 0.115975E+09 | 0.266186E+09 | 0.122638E+10 | 0.00 |
September | 0.352414E+09 | 0.110866E+09 | 0.241548E+09 | 0.997377E+09 | 451966.77 |
October | 0.323913E+09 | 0.105009E+09 | 0.218905E+09 | 0.796100E+09 | 4416765.36 |
November | 0.269513E+09 | 88428078.83 | 0.181085E+09 | 0.541745E+09 | 46088471.76 |
December | 0.232238E+09 | 69919888.64 | 0.162319E+09 | 0.371229E+09 | 0.134454E+09 |
Annual Sum or Average | 0.389687E+10 | 0.117695E+10 | 0.271992E+10 | 0.930863E+10 | 0.625915E+09 |
Minimum of Months | 0.232238E+09 | 69919888.64 | 0.162319E+09 | 0.352127E+09 | 0.00 |
Maximum of Months | 0.393123E+09 | 0.123828E+09 | 0.275466E+09 | 0.122638E+10 | 0.184820E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 73789426.05 | 0.00 | 73789426.05 | 95161544.37 | 96323804.95 |
February | 76398307.43 | 0.00 | 76398307.43 | 0.114609E+09 | 65851304.04 |
March | 97170368.09 | 1164.90 | 97169203.18 | 0.178114E+09 | 47987563.14 |
April | 0.106293E+09 | 423648.45 | 0.105869E+09 | 0.248844E+09 | 19092826.80 |
May | 0.123473E+09 | 3786056.10 | 0.119687E+09 | 0.397193E+09 | 1137269.00 |
June | 0.127741E+09 | 7161555.05 | 0.120580E+09 | 0.446063E+09 | 16108.61 |
July | 0.121291E+09 | 3647867.79 | 0.117643E+09 | 0.508971E+09 | 0.00 |
August | 0.112995E+09 | 1136187.01 | 0.111859E+09 | 0.498288E+09 | 0.00 |
September | 99376681.90 | 30232.96 | 99346448.94 | 0.380602E+09 | 247814.97 |
October | 90994677.48 | 0.00 | 90994677.48 | 0.286586E+09 | 2270639.53 |
November | 75597061.82 | 0.00 | 75597061.82 | 0.174495E+09 | 23661895.74 |
December | 68872881.78 | 0.00 | 68872881.78 | 0.106774E+09 | 69609244.50 |
Annual Sum or Average | 0.117399E+10 | 16186712.25 | 0.115781E+10 | 0.343570E+10 | 0.326198E+09 |
Minimum of Months | 68872881.78 | 0.00 | 68872881.78 | 95161544.37 | 0.00 |
Maximum of Months | 0.127741E+09 | 7161555.05 | 0.120580E+09 | 0.508971E+09 | 96323804.95 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.245132E+09 | 70510841.87 | 0.174622E+09 | 0.362576E+09 | 0.178804E+09 |
February | 0.252696E+09 | 72293154.79 | 0.180403E+09 | 0.403964E+09 | 0.122046E+09 |
March | 0.330482E+09 | 97845769.85 | 0.232636E+09 | 0.590407E+09 | 89141657.06 |
April | 0.349707E+09 | 98244720.35 | 0.251462E+09 | 0.725131E+09 | 35905877.58 |
May | 0.393123E+09 | 0.117658E+09 | 0.275466E+09 | 0.102136E+10 | 2244795.51 |
June | 0.393008E+09 | 0.123828E+09 | 0.269180E+09 | 0.109456E+10 | 27837.15 |
July | 0.372477E+09 | 0.106371E+09 | 0.266106E+09 | 0.120163E+10 | 0.00 |
August | 0.382161E+09 | 0.115975E+09 | 0.266186E+09 | 0.122786E+10 | 0.00 |
September | 0.352414E+09 | 0.110866E+09 | 0.241548E+09 | 0.100201E+10 | 426647.58 |
October | 0.323913E+09 | 0.105009E+09 | 0.218905E+09 | 0.804452E+09 | 4071989.73 |
November | 0.269513E+09 | 88428078.83 | 0.181085E+09 | 0.550909E+09 | 43890960.01 |
December | 0.232238E+09 | 69919888.64 | 0.162319E+09 | 0.380414E+09 | 0.129472E+09 |
Annual Sum or Average | 0.389687E+10 | 0.117695E+10 | 0.271992E+10 | 0.936526E+10 | 0.606031E+09 |
Minimum of Months | 0.232238E+09 | 69919888.64 | 0.162319E+09 | 0.362576E+09 | 0.00 |
Maximum of Months | 0.393123E+09 | 0.123828E+09 | 0.275466E+09 | 0.122786E+10 | 0.178804E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.351398E+09 | 0.165950E+09 | 0.185447E+09 | 0.539685E+09 | 0.140119E+09 |
February | 0.296706E+09 | 0.121352E+09 | 0.175354E+09 | 0.484477E+09 | 96519884.72 |
March | 0.267526E+09 | 70601201.94 | 0.196924E+09 | 0.497537E+09 | 70130186.69 |
April | 0.206756E+09 | 22835528.24 | 0.183920E+09 | 0.476333E+09 | 27150465.65 |
May | 0.180756E+09 | 3410675.63 | 0.177346E+09 | 0.599028E+09 | 1439568.19 |
June | 0.164058E+09 | 202892.36 | 0.163856E+09 | 0.627002E+09 | 2250.46 |
July | 0.169291E+09 | 1120160.45 | 0.168171E+09 | 0.747939E+09 | 0.00 |
August | 0.195839E+09 | 13026751.39 | 0.182812E+09 | 0.813032E+09 | 0.00 |
September | 0.251216E+09 | 57765724.55 | 0.193450E+09 | 0.776903E+09 | 306814.59 |
October | 0.340014E+09 | 0.135520E+09 | 0.204494E+09 | 0.801005E+09 | 3118351.74 |
November | 0.364171E+09 | 0.176434E+09 | 0.187737E+09 | 0.693770E+09 | 34479431.94 |
December | 0.348235E+09 | 0.172329E+09 | 0.175905E+09 | 0.569126E+09 | 0.102739E+09 |
Annual Sum or Average | 0.313596E+10 | 0.940548E+09 | 0.219542E+10 | 0.762584E+10 | 0.476005E+09 |
Minimum of Months | 0.164058E+09 | 202892.36 | 0.163856E+09 | 0.476333E+09 | 0.00 |
Maximum of Months | 0.364171E+09 | 0.176434E+09 | 0.204494E+09 | 0.813032E+09 | 0.140119E+09 |
Report: WindowEnergyReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.516506E+09 | 0.00 | 0.516506E+09 | 0.711114E+09 | 0.738047E+09 |
February | 0.534768E+09 | 0.00 | 0.534768E+09 | 0.867382E+09 | 0.514416E+09 |
March | 0.680167E+09 | 8154.03 | 0.680159E+09 | 0.135090E+10 | 0.380536E+09 |
April | 0.744024E+09 | 2965426.81 | 0.741058E+09 | 0.186925E+10 | 0.168130E+09 |
May | 0.864277E+09 | 26501389.01 | 0.837775E+09 | 0.290204E+10 | 13781870.43 |
June | 0.894154E+09 | 50128986.72 | 0.844025E+09 | 0.322646E+10 | 480065.24 |
July | 0.849006E+09 | 25534107.42 | 0.823472E+09 | 0.366304E+10 | 0.00 |
August | 0.790934E+09 | 7953007.84 | 0.782981E+09 | 0.359234E+10 | 0.00 |
September | 0.695610E+09 | 211622.67 | 0.695399E+09 | 0.277134E+10 | 2766200.81 |
October | 0.636939E+09 | 0.00 | 0.636939E+09 | 0.212023E+10 | 25699647.42 |
November | 0.529159E+09 | 0.00 | 0.529159E+09 | 0.133172E+10 | 0.202884E+09 |
December | 0.482092E+09 | 0.00 | 0.482092E+09 | 0.812023E+09 | 0.540350E+09 |
Annual Sum or Average | 0.821764E+10 | 0.113303E+09 | 0.810433E+10 | 0.252178E+11 | 0.258709E+10 |
Minimum of Months | 0.482092E+09 | 0.00 | 0.482092E+09 | 0.711114E+09 | 0.00 |
Maximum of Months | 0.894154E+09 | 50128986.72 | 0.844025E+09 | 0.366304E+10 | 0.738047E+09 |
Report: WindowEnergyReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.516506E+09 | 0.00 | 0.516506E+09 | 0.692895E+09 | 0.775033E+09 |
February | 0.534768E+09 | 0.00 | 0.534768E+09 | 0.846614E+09 | 0.545505E+09 |
March | 0.680167E+09 | 8154.03 | 0.680159E+09 | 0.132053E+10 | 0.409482E+09 |
April | 0.744024E+09 | 2965426.81 | 0.741058E+09 | 0.182799E+10 | 0.186549E+09 |
May | 0.864277E+09 | 26501389.01 | 0.837775E+09 | 0.284533E+10 | 17080328.13 |
June | 0.894154E+09 | 50128986.72 | 0.844025E+09 | 0.317094E+10 | 617348.58 |
July | 0.849006E+09 | 25534107.42 | 0.823472E+09 | 0.361116E+10 | 0.00 |
August | 0.790934E+09 | 7953007.84 | 0.782981E+09 | 0.354194E+10 | 0.00 |
September | 0.695610E+09 | 211622.67 | 0.695399E+09 | 0.271838E+10 | 3342489.58 |
October | 0.636939E+09 | 0.00 | 0.636939E+09 | 0.206783E+10 | 31566403.62 |
November | 0.529159E+09 | 0.00 | 0.529159E+09 | 0.129580E+10 | 0.223196E+09 |
December | 0.482092E+09 | 0.00 | 0.482092E+09 | 0.789663E+09 | 0.573954E+09 |
Annual Sum or Average | 0.821764E+10 | 0.113303E+09 | 0.810433E+10 | 0.247291E+11 | 0.276633E+10 |
Minimum of Months | 0.482092E+09 | 0.00 | 0.482092E+09 | 0.692895E+09 | 0.00 |
Maximum of Months | 0.894154E+09 | 50128986.72 | 0.844025E+09 | 0.361116E+10 | 0.775033E+09 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 73789426.05 | 0.00 | 73789426.05 | 0.103301E+09 | 0.117461E+09 |
February | 76398307.43 | 0.00 | 76398307.43 | 0.124169E+09 | 85486462.66 |
March | 97170368.09 | 1164.90 | 97169203.18 | 0.192419E+09 | 63163777.02 |
April | 0.106293E+09 | 423648.45 | 0.105869E+09 | 0.265285E+09 | 29498136.79 |
May | 0.123473E+09 | 3786056.10 | 0.119687E+09 | 0.412542E+09 | 2792517.14 |
June | 0.127741E+09 | 7161555.05 | 0.120580E+09 | 0.457959E+09 | 46117.74 |
July | 0.121291E+09 | 3647867.79 | 0.117643E+09 | 0.522356E+09 | 0.00 |
August | 0.112995E+09 | 1136187.01 | 0.111859E+09 | 0.510486E+09 | 0.00 |
September | 99376681.90 | 30232.96 | 99346448.94 | 0.391092E+09 | 304588.29 |
October | 90994677.48 | 0.00 | 90994677.48 | 0.298588E+09 | 4845555.81 |
November | 75597061.82 | 0.00 | 75597061.82 | 0.190179E+09 | 35438679.72 |
December | 68872881.78 | 0.00 | 68872881.78 | 0.118585E+09 | 86970720.22 |
Annual Sum or Average | 0.117399E+10 | 16186712.25 | 0.115781E+10 | 0.358696E+10 | 0.426008E+09 |
Minimum of Months | 68872881.78 | 0.00 | 68872881.78 | 0.103301E+09 | 0.00 |
Maximum of Months | 0.127741E+09 | 7161555.05 | 0.120580E+09 | 0.522356E+09 | 0.117461E+09 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.497567E+09 | 0.150072E+09 | 0.347495E+09 | 0.769552E+09 | 0.417287E+09 |
February | 0.490746E+09 | 0.133003E+09 | 0.357742E+09 | 0.824673E+09 | 0.306722E+09 |
March | 0.600674E+09 | 0.148166E+09 | 0.452508E+09 | 0.114401E+10 | 0.228622E+09 |
April | 0.707649E+09 | 0.205923E+09 | 0.501727E+09 | 0.155504E+10 | 0.109871E+09 |
May | 0.815881E+09 | 0.259823E+09 | 0.556058E+09 | 0.217220E+10 | 10672807.72 |
June | 0.773430E+09 | 0.236437E+09 | 0.536993E+09 | 0.222624E+10 | 160759.45 |
July | 0.746046E+09 | 0.214967E+09 | 0.531079E+09 | 0.247417E+10 | 0.00 |
August | 0.764161E+09 | 0.234614E+09 | 0.529547E+09 | 0.251642E+10 | 0.00 |
September | 0.694817E+09 | 0.214638E+09 | 0.480178E+09 | 0.204251E+10 | 1170423.07 |
October | 0.651347E+09 | 0.212480E+09 | 0.438867E+09 | 0.168115E+10 | 18544418.44 |
November | 0.528025E+09 | 0.166763E+09 | 0.361262E+09 | 0.115739E+10 | 0.130091E+09 |
December | 0.442373E+09 | 0.121634E+09 | 0.320739E+09 | 0.773303E+09 | 0.314095E+09 |
Annual Sum or Average | 0.771271E+10 | 0.229852E+10 | 0.541420E+10 | 0.193367E+11 | 0.153724E+10 |
Minimum of Months | 0.442373E+09 | 0.121634E+09 | 0.320739E+09 | 0.769552E+09 | 0.00 |
Maximum of Months | 0.815881E+09 | 0.259823E+09 | 0.556058E+09 | 0.251642E+10 | 0.417287E+09 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.239601E+09 | 0.113153E+09 | 0.126448E+09 | 0.392035E+09 | 0.110703E+09 |
February | 0.202309E+09 | 82744003.94 | 0.119565E+09 | 0.349670E+09 | 82219524.52 |
March | 0.182413E+09 | 48139503.57 | 0.134273E+09 | 0.357491E+09 | 62282200.32 |
April | 0.140977E+09 | 15570428.87 | 0.125406E+09 | 0.338419E+09 | 29751950.59 |
May | 0.123249E+09 | 2325572.76 | 0.120923E+09 | 0.412099E+09 | 2884841.54 |
June | 0.111863E+09 | 138342.37 | 0.111725E+09 | 0.424004E+09 | 42465.69 |
July | 0.115431E+09 | 763782.57 | 0.114667E+09 | 0.509342E+09 | 0.00 |
August | 0.133533E+09 | 8882304.10 | 0.124651E+09 | 0.554366E+09 | 0.00 |
September | 0.171292E+09 | 39387619.85 | 0.131904E+09 | 0.535408E+09 | 290567.74 |
October | 0.231839E+09 | 92404393.57 | 0.139435E+09 | 0.561890E+09 | 4869121.56 |
November | 0.248310E+09 | 0.120302E+09 | 0.128009E+09 | 0.498583E+09 | 34414092.05 |
December | 0.237444E+09 | 0.117503E+09 | 0.119941E+09 | 0.413864E+09 | 83461433.86 |
Annual Sum or Average | 0.213826E+10 | 0.641314E+09 | 0.149695E+10 | 0.534717E+10 | 0.410919E+09 |
Minimum of Months | 0.111863E+09 | 138342.37 | 0.111725E+09 | 0.338419E+09 | 0.00 |
Maximum of Months | 0.248310E+09 | 0.120302E+09 | 0.139435E+09 | 0.561890E+09 | 0.110703E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93449652.24 | 0.00 | 93449652.24 | 0.131601E+09 | 0.120105E+09 |
February | 96753635.90 | 0.00 | 96753635.90 | 0.161234E+09 | 79526105.34 |
March | 0.123060E+09 | 1475.28 | 0.123059E+09 | 0.252061E+09 | 54981556.01 |
April | 0.134614E+09 | 536524.03 | 0.134077E+09 | 0.350498E+09 | 20119501.89 |
May | 0.156371E+09 | 4794801.17 | 0.151576E+09 | 0.543850E+09 | 828366.83 |
June | 0.161776E+09 | 9069657.60 | 0.152706E+09 | 0.601418E+09 | 3909.61 |
July | 0.153608E+09 | 4619794.39 | 0.148988E+09 | 0.674003E+09 | 0.00 |
August | 0.143101E+09 | 1438909.16 | 0.141662E+09 | 0.658696E+09 | 0.00 |
September | 0.125854E+09 | 38288.13 | 0.125816E+09 | 0.514813E+09 | 190977.59 |
October | 0.115239E+09 | 0.00 | 0.115239E+09 | 0.398568E+09 | 1955953.80 |
November | 95738908.88 | 0.00 | 95738908.88 | 0.248541E+09 | 25885739.15 |
December | 87223159.14 | 0.00 | 87223159.14 | 0.150797E+09 | 84348513.78 |
Annual Sum or Average | 0.148679E+10 | 20499449.75 | 0.146629E+10 | 0.468608E+10 | 0.387946E+09 |
Minimum of Months | 87223159.14 | 0.00 | 87223159.14 | 0.131601E+09 | 0.00 |
Maximum of Months | 0.161776E+09 | 9069657.60 | 0.152706E+09 | 0.674003E+09 | 0.120105E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 83609757.94 | 0.00 | 83609757.94 | 0.117744E+09 | 0.107455E+09 |
February | 86565844.64 | 0.00 | 86565844.64 | 0.144257E+09 | 71153106.25 |
March | 0.110102E+09 | 1319.94 | 0.110101E+09 | 0.225520E+09 | 49192206.49 |
April | 0.120439E+09 | 480030.08 | 0.119959E+09 | 0.313592E+09 | 18000994.57 |
May | 0.139905E+09 | 4289926.77 | 0.135615E+09 | 0.486585E+09 | 741142.94 |
June | 0.144742E+09 | 8114657.02 | 0.136627E+09 | 0.538091E+09 | 3497.94 |
July | 0.137433E+09 | 4133347.54 | 0.133300E+09 | 0.603033E+09 | 0.00 |
August | 0.128033E+09 | 1287397.47 | 0.126745E+09 | 0.589338E+09 | 0.00 |
September | 0.112602E+09 | 34256.54 | 0.112568E+09 | 0.460605E+09 | 170868.37 |
October | 0.103105E+09 | 0.00 | 0.103105E+09 | 0.356600E+09 | 1750711.47 |
November | 85657964.53 | 0.00 | 85657964.53 | 0.222371E+09 | 23160386.81 |
December | 78038890.97 | 0.00 | 78038890.97 | 0.134919E+09 | 75458424.98 |
Annual Sum or Average | 0.133023E+10 | 18340935.36 | 0.131189E+10 | 0.419265E+10 | 0.347086E+09 |
Minimum of Months | 78038890.97 | 0.00 | 78038890.97 | 0.117744E+09 | 0.00 |
Maximum of Months | 0.144742E+09 | 8114657.02 | 0.136627E+09 | 0.603033E+09 | 0.107455E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.894502E+09 | 0.422435E+09 | 0.472066E+09 | 0.144548E+10 | 0.329897E+09 |
February | 0.755281E+09 | 0.308908E+09 | 0.446373E+09 | 0.130187E+10 | 0.224611E+09 |
March | 0.681001E+09 | 0.179719E+09 | 0.501282E+09 | 0.134556E+10 | 0.161259E+09 |
April | 0.526307E+09 | 58129050.74 | 0.468178E+09 | 0.129526E+10 | 61198560.19 |
May | 0.460124E+09 | 8682056.08 | 0.451442E+09 | 0.159589E+10 | 2861823.13 |
June | 0.417620E+09 | 516473.29 | 0.417103E+09 | 0.164675E+10 | 3413.70 |
July | 0.430939E+09 | 2851427.95 | 0.428088E+09 | 0.193256E+10 | 0.00 |
August | 0.498519E+09 | 33160287.98 | 0.465358E+09 | 0.209834E+10 | 0.00 |
September | 0.639483E+09 | 0.147046E+09 | 0.492437E+09 | 0.204311E+10 | 560967.05 |
October | 0.865524E+09 | 0.344973E+09 | 0.520551E+09 | 0.213840E+10 | 5617340.85 |
November | 0.927016E+09 | 0.449122E+09 | 0.477894E+09 | 0.186552E+10 | 73061902.01 |
December | 0.886450E+09 | 0.438673E+09 | 0.447776E+09 | 0.152648E+10 | 0.234693E+09 |
Annual Sum or Average | 0.798276E+10 | 0.239422E+10 | 0.558855E+10 | 0.202352E+11 | 0.109377E+10 |
Minimum of Months | 0.417620E+09 | 516473.29 | 0.417103E+09 | 0.129526E+10 | 0.00 |
Maximum of Months | 0.927016E+09 | 0.449122E+09 | 0.520551E+09 | 0.213840E+10 | 0.329897E+09 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 729.32 | 169.41 | 452.45 | 213.67 | 238.77 | 0.00 | 0.00 |
February | 722.83 | 130.25 | 422.96 | 172.99 | 249.97 | 0.00 | 0.00 |
March | 665.39 | 87.83 | 344.46 | 90.90 | 253.55 | 0.00 | 0.00 |
April | 648.44 | 37.66 | 275.08 | 30.38 | 244.70 | 0.00 | 0.00 |
May | 761.51 | 2.38 | 232.73 | 4.39 | 228.34 | 0.00 | 0.00 |
June | 808.57 | 0.05 | 218.27 | 0.27 | 218.00 | 0.00 | 0.00 |
July | 928.73 | 0.00 | 217.97 | 1.44 | 216.53 | 0.00 | 0.00 |
August | 1007.01 | 0.00 | 252.15 | 16.77 | 235.38 | 0.00 | 0.00 |
September | 1013.61 | 0.50 | 334.24 | 76.86 | 257.38 | 0.00 | 0.00 |
October | 1030.23 | 4.84 | 437.79 | 174.49 | 263.30 | 0.00 | 0.00 |
November | 943.48 | 46.42 | 484.52 | 234.74 | 249.78 | 0.00 | 0.00 |
December | 763.47 | 124.83 | 448.37 | 221.89 | 226.49 | 0.00 | 0.00 |
Annual Sum or Average | 835.94 | 50.01 | 342.93 | 102.85 | 240.08 | 0.00 | 0.00 |
Minimum of Months | 648.44 | 0.00 | 217.97 | 0.27 | 216.53 | 0.00 | 0.00 |
Maximum of Months | 1030.23 | 169.41 | 484.52 | 234.74 | 263.30 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2037.90 | 485.67 | 1274.06 | 601.69 | 672.37 | 0.00 | 0.00 |
February | 2021.35 | 377.16 | 1191.02 | 487.13 | 703.90 | 0.00 | 0.00 |
March | 1859.31 | 257.03 | 969.96 | 255.98 | 713.98 | 0.00 | 0.00 |
April | 1809.84 | 114.82 | 774.62 | 85.55 | 689.06 | 0.00 | 0.00 |
May | 2117.32 | 8.50 | 655.36 | 12.37 | 643.00 | 0.00 | 0.00 |
June | 2245.58 | 0.28 | 614.65 | 0.76 | 613.89 | 0.00 | 0.00 |
July | 2589.55 | 0.00 | 613.79 | 4.06 | 609.73 | 0.00 | 0.00 |
August | 2816.98 | 0.00 | 710.05 | 47.23 | 662.82 | 0.00 | 0.00 |
September | 2829.93 | 1.82 | 941.19 | 216.42 | 724.77 | 0.00 | 0.00 |
October | 2878.90 | 18.19 | 1232.78 | 491.35 | 741.43 | 0.00 | 0.00 |
November | 2644.77 | 143.06 | 1364.38 | 661.02 | 703.36 | 0.00 | 0.00 |
December | 2136.52 | 360.86 | 1262.59 | 624.81 | 637.78 | 0.00 | 0.00 |
Annual Sum or Average | 2334.34 | 146.29 | 965.67 | 289.63 | 676.04 | 0.00 | 0.00 |
Minimum of Months | 1809.84 | 0.00 | 613.79 | 0.76 | 609.73 | 0.00 | 0.00 |
Maximum of Months | 2878.90 | 485.67 | 1364.38 | 661.02 | 741.43 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2708.48 | 641.97 | 1655.08 | 781.62 | 873.45 | 0.00 | 0.00 |
February | 2693.51 | 498.10 | 1547.21 | 632.81 | 914.40 | 0.00 | 0.00 |
March | 2482.38 | 342.12 | 1260.04 | 332.53 | 927.51 | 0.00 | 0.00 |
April | 2422.50 | 154.54 | 1006.27 | 111.14 | 895.13 | 0.00 | 0.00 |
May | 2838.07 | 11.71 | 851.35 | 16.06 | 835.29 | 0.00 | 0.00 |
June | 3010.68 | 0.38 | 798.46 | 0.99 | 797.47 | 0.00 | 0.00 |
July | 3477.96 | 0.00 | 797.35 | 5.28 | 792.07 | 0.00 | 0.00 |
August | 3788.08 | 0.00 | 922.39 | 61.36 | 861.04 | 0.00 | 0.00 |
September | 3804.70 | 2.35 | 1222.66 | 281.15 | 941.51 | 0.00 | 0.00 |
October | 3866.80 | 22.23 | 1601.46 | 638.30 | 963.16 | 0.00 | 0.00 |
November | 3536.20 | 185.48 | 1772.41 | 858.70 | 913.71 | 0.00 | 0.00 |
December | 2841.88 | 475.90 | 1640.18 | 811.67 | 828.51 | 0.00 | 0.00 |
Annual Sum or Average | 3125.35 | 193.26 | 1254.46 | 376.24 | 878.22 | 0.00 | 0.00 |
Minimum of Months | 2422.50 | 0.00 | 797.35 | 0.99 | 792.07 | 0.00 | 0.00 |
Maximum of Months | 3866.80 | 641.97 | 1772.41 | 858.70 | 963.16 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 273.32 | 102.22 | 180.98 | 68.57 | 112.41 | 0.00 | 0.00 |
February | 306.21 | 78.28 | 188.08 | 64.09 | 123.99 | 0.00 | 0.00 |
March | 350.29 | 52.23 | 191.49 | 54.50 | 136.99 | 0.00 | 0.00 |
April | 407.76 | 21.90 | 189.31 | 43.91 | 145.40 | 0.00 | 0.00 |
May | 534.01 | 1.39 | 192.79 | 44.80 | 147.99 | 0.00 | 0.00 |
June | 585.79 | 0.02 | 194.78 | 47.83 | 146.95 | 0.00 | 0.00 |
July | 637.64 | 0.00 | 182.16 | 40.00 | 142.16 | 0.00 | 0.00 |
August | 663.44 | 0.00 | 192.54 | 46.62 | 145.92 | 0.00 | 0.00 |
September | 589.44 | 0.29 | 202.05 | 57.97 | 144.08 | 0.00 | 0.00 |
October | 503.66 | 2.62 | 207.49 | 73.71 | 133.79 | 0.00 | 0.00 |
November | 395.77 | 26.75 | 199.78 | 80.53 | 119.25 | 0.00 | 0.00 |
December | 288.08 | 74.58 | 175.36 | 69.98 | 105.38 | 0.00 | 0.00 |
Annual Sum or Average | 462.19 | 29.82 | 191.37 | 57.66 | 133.72 | 0.00 | 0.00 |
Minimum of Months | 273.32 | 0.00 | 175.36 | 40.00 | 105.38 | 0.00 | 0.00 |
Maximum of Months | 663.44 | 102.22 | 207.49 | 80.53 | 147.99 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 174.56 | 103.32 | 119.07 | 26.33 | 92.75 | 0.00 | 0.00 |
February | 218.92 | 77.72 | 136.03 | 29.88 | 106.15 | 0.00 | 0.00 |
March | 292.33 | 51.33 | 159.67 | 36.53 | 123.14 | 0.00 | 0.00 |
April | 381.43 | 21.38 | 175.93 | 38.07 | 137.86 | 0.00 | 0.00 |
May | 534.52 | 1.28 | 192.87 | 45.34 | 147.53 | 0.00 | 0.00 |
June | 598.39 | 0.02 | 200.91 | 50.54 | 150.37 | 0.00 | 0.00 |
July | 642.60 | 0.00 | 184.35 | 41.08 | 143.28 | 0.00 | 0.00 |
August | 648.18 | 0.00 | 184.87 | 43.72 | 141.15 | 0.00 | 0.00 |
September | 536.83 | 0.27 | 174.30 | 42.78 | 131.52 | 0.00 | 0.00 |
October | 410.69 | 2.49 | 154.91 | 39.21 | 115.70 | 0.00 | 0.00 |
November | 283.37 | 26.48 | 133.14 | 34.12 | 99.03 | 0.00 | 0.00 |
December | 185.71 | 74.70 | 112.42 | 26.11 | 86.32 | 0.00 | 0.00 |
Annual Sum or Average | 410.07 | 29.72 | 160.80 | 37.83 | 122.96 | 0.00 | 0.00 |
Minimum of Months | 174.56 | 0.00 | 112.42 | 26.11 | 86.32 | 0.00 | 0.00 |
Maximum of Months | 648.18 | 103.32 | 200.91 | 50.54 | 150.37 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 107.70 | 37.36 | 71.55 | 33.79 | 37.76 | 0.00 | 0.00 |
February | 106.93 | 30.34 | 66.89 | 27.36 | 39.53 | 0.00 | 0.00 |
March | 98.04 | 21.85 | 54.47 | 14.38 | 40.10 | 0.00 | 0.00 |
April | 94.99 | 11.21 | 43.50 | 4.80 | 38.70 | 0.00 | 0.00 |
May | 112.49 | 1.39 | 36.81 | 0.69 | 36.11 | 0.00 | 0.00 |
June | 120.95 | 0.05 | 34.52 | 0.04 | 34.48 | 0.00 | 0.00 |
July | 141.75 | 0.00 | 34.47 | 0.23 | 34.24 | 0.00 | 0.00 |
August | 155.22 | 0.00 | 39.88 | 2.65 | 37.22 | 0.00 | 0.00 |
September | 153.70 | 0.32 | 52.86 | 12.15 | 40.70 | 0.00 | 0.00 |
October | 155.33 | 2.50 | 69.23 | 27.59 | 41.64 | 0.00 | 0.00 |
November | 142.01 | 13.01 | 76.62 | 37.12 | 39.50 | 0.00 | 0.00 |
December | 113.60 | 29.26 | 70.91 | 35.09 | 35.82 | 0.00 | 0.00 |
Annual Sum or Average | 125.35 | 12.19 | 54.23 | 16.27 | 37.97 | 0.00 | 0.00 |
Minimum of Months | 94.99 | 0.00 | 34.47 | 0.04 | 34.24 | 0.00 | 0.00 |
Maximum of Months | 155.33 | 37.36 | 76.62 | 37.12 | 41.64 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 30.24 | 29.15 | 22.04 | 0.00 | 22.04 | 0.00 | 0.00 |
February | 40.64 | 21.57 | 25.27 | 0.00 | 25.27 | 0.00 | 0.00 |
March | 57.03 | 13.75 | 29.03 | 0.00 | 29.03 | 0.00 | 0.00 |
April | 81.76 | 5.35 | 32.81 | 0.13 | 32.68 | 0.00 | 0.00 |
May | 125.65 | 0.23 | 36.88 | 1.13 | 35.75 | 0.00 | 0.00 |
June | 145.30 | 0.00 | 39.43 | 2.21 | 37.22 | 0.00 | 0.00 |
July | 159.97 | 0.00 | 36.23 | 1.09 | 35.14 | 0.00 | 0.00 |
August | 156.95 | 0.00 | 33.75 | 0.34 | 33.42 | 0.00 | 0.00 |
September | 124.53 | 0.05 | 30.68 | 0.01 | 30.67 | 0.00 | 0.00 |
October | 91.27 | 0.52 | 27.18 | 0.00 | 27.18 | 0.00 | 0.00 |
November | 57.56 | 6.81 | 23.34 | 0.00 | 23.34 | 0.00 | 0.00 |
December | 34.15 | 20.70 | 20.57 | 0.00 | 20.57 | 0.00 | 0.00 |
Annual Sum or Average | 92.40 | 8.12 | 29.79 | 0.41 | 29.37 | 0.00 | 0.00 |
Minimum of Months | 30.24 | 0.00 | 20.57 | 0.00 | 20.57 | 0.00 | 0.00 |
Maximum of Months | 159.97 | 29.15 | 39.43 | 2.21 | 37.22 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 272.58 | 98.61 | 182.35 | 70.26 | 112.08 | 0.00 | 0.00 |
February | 298.35 | 74.62 | 185.06 | 61.69 | 123.37 | 0.00 | 0.00 |
March | 329.78 | 48.96 | 180.25 | 45.63 | 134.61 | 0.00 | 0.00 |
April | 412.07 | 20.65 | 190.91 | 45.73 | 145.17 | 0.00 | 0.00 |
May | 544.99 | 1.25 | 198.33 | 49.38 | 148.96 | 0.00 | 0.00 |
June | 583.37 | 0.02 | 192.36 | 45.67 | 146.70 | 0.00 | 0.00 |
July | 640.28 | 0.00 | 182.38 | 40.42 | 141.96 | 0.00 | 0.00 |
August | 664.69 | 0.00 | 192.52 | 47.12 | 145.40 | 0.00 | 0.00 |
September | 587.58 | 0.29 | 200.13 | 56.60 | 143.52 | 0.00 | 0.00 |
October | 506.49 | 2.61 | 208.16 | 74.17 | 133.99 | 0.00 | 0.00 |
November | 392.95 | 26.23 | 197.66 | 78.58 | 119.08 | 0.00 | 0.00 |
December | 279.63 | 72.46 | 171.24 | 66.58 | 104.66 | 0.00 | 0.00 |
Annual Sum or Average | 460.34 | 28.62 | 190.10 | 56.78 | 133.32 | 0.00 | 0.00 |
Minimum of Months | 272.58 | 0.00 | 171.24 | 40.42 | 104.66 | 0.00 | 0.00 |
Maximum of Months | 664.69 | 98.61 | 208.16 | 78.58 | 148.96 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 170.50 | 96.13 | 120.44 | 28.02 | 92.42 | 0.00 | 0.00 |
February | 209.76 | 72.79 | 133.01 | 27.49 | 105.52 | 0.00 | 0.00 |
March | 271.45 | 47.85 | 148.42 | 27.66 | 120.76 | 0.00 | 0.00 |
April | 385.83 | 20.31 | 177.52 | 39.89 | 137.64 | 0.00 | 0.00 |
May | 545.58 | 1.22 | 198.42 | 49.92 | 148.50 | 0.00 | 0.00 |
June | 595.99 | 0.02 | 198.49 | 48.38 | 150.11 | 0.00 | 0.00 |
July | 645.26 | 0.00 | 184.57 | 41.49 | 143.07 | 0.00 | 0.00 |
August | 649.44 | 0.00 | 184.85 | 44.22 | 140.63 | 0.00 | 0.00 |
September | 534.93 | 0.28 | 172.38 | 41.42 | 130.96 | 0.00 | 0.00 |
October | 413.28 | 2.41 | 155.57 | 39.67 | 115.91 | 0.00 | 0.00 |
November | 279.26 | 24.93 | 131.03 | 32.17 | 98.86 | 0.00 | 0.00 |
December | 174.82 | 69.95 | 108.30 | 22.71 | 85.59 | 0.00 | 0.00 |
Annual Sum or Average | 407.49 | 27.81 | 159.52 | 36.96 | 122.56 | 0.00 | 0.00 |
Minimum of Months | 170.50 | 0.00 | 108.30 | 22.71 | 85.59 | 0.00 | 0.00 |
Maximum of Months | 649.44 | 96.13 | 198.49 | 49.92 | 150.11 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 322.79 | 112.95 | 202.78 | 73.21 | 129.57 | 0.00 | 0.00 |
February | 348.69 | 84.46 | 199.67 | 59.27 | 140.39 | 0.00 | 0.00 |
March | 369.74 | 54.34 | 180.91 | 31.15 | 149.76 | 0.00 | 0.00 |
April | 422.99 | 21.60 | 165.34 | 10.69 | 154.64 | 0.00 | 0.00 |
May | 552.57 | 1.19 | 159.65 | 3.95 | 155.70 | 0.00 | 0.00 |
June | 609.54 | 0.02 | 160.21 | 4.88 | 155.33 | 0.00 | 0.00 |
July | 680.37 | 0.00 | 153.18 | 2.85 | 150.33 | 0.00 | 0.00 |
August | 699.74 | 0.00 | 159.52 | 6.48 | 153.04 | 0.00 | 0.00 |
September | 633.09 | 0.33 | 180.98 | 26.36 | 154.63 | 0.00 | 0.00 |
October | 568.90 | 2.74 | 208.90 | 59.79 | 149.11 | 0.00 | 0.00 |
November | 467.34 | 27.48 | 216.57 | 80.43 | 136.14 | 0.00 | 0.00 |
December | 347.66 | 79.69 | 198.21 | 76.03 | 122.18 | 0.00 | 0.00 |
Annual Sum or Average | 502.87 | 31.85 | 182.03 | 36.13 | 145.90 | 0.00 | 0.00 |
Minimum of Months | 322.79 | 0.00 | 153.18 | 2.85 | 122.18 | 0.00 | 0.00 |
Maximum of Months | 699.74 | 112.95 | 216.57 | 80.43 | 155.70 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 268.71 | 101.71 | 180.98 | 68.57 | 112.41 | 0.00 | 0.00 |
February | 300.75 | 78.19 | 188.08 | 64.09 | 123.99 | 0.00 | 0.00 |
March | 344.39 | 52.08 | 191.49 | 54.50 | 136.99 | 0.00 | 0.00 |
April | 401.69 | 21.67 | 189.31 | 43.91 | 145.40 | 0.00 | 0.00 |
May | 529.05 | 1.33 | 192.79 | 44.80 | 147.99 | 0.00 | 0.00 |
June | 582.06 | 0.01 | 194.78 | 47.83 | 146.95 | 0.00 | 0.00 |
July | 633.58 | 0.00 | 182.16 | 40.00 | 142.16 | 0.00 | 0.00 |
August | 659.45 | 0.00 | 192.54 | 46.62 | 145.92 | 0.00 | 0.00 |
September | 585.31 | 0.27 | 202.05 | 57.97 | 144.08 | 0.00 | 0.00 |
October | 499.28 | 2.49 | 207.49 | 73.71 | 133.79 | 0.00 | 0.00 |
November | 391.06 | 26.36 | 199.78 | 80.53 | 119.25 | 0.00 | 0.00 |
December | 283.45 | 74.35 | 175.36 | 69.98 | 105.38 | 0.00 | 0.00 |
Annual Sum or Average | 457.48 | 29.67 | 191.37 | 57.66 | 133.72 | 0.00 | 0.00 |
Minimum of Months | 268.71 | 0.00 | 175.36 | 40.00 | 105.38 | 0.00 | 0.00 |
Maximum of Months | 659.45 | 101.71 | 207.49 | 80.53 | 147.99 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 170.66 | 102.48 | 119.07 | 26.33 | 92.75 | 0.00 | 0.00 |
February | 214.17 | 77.49 | 136.03 | 29.88 | 106.15 | 0.00 | 0.00 |
March | 286.90 | 51.16 | 159.67 | 36.53 | 123.14 | 0.00 | 0.00 |
April | 375.73 | 21.18 | 175.93 | 38.07 | 137.86 | 0.00 | 0.00 |
May | 529.60 | 1.23 | 192.87 | 45.34 | 147.53 | 0.00 | 0.00 |
June | 594.37 | 0.02 | 200.91 | 50.54 | 150.37 | 0.00 | 0.00 |
July | 638.67 | 0.00 | 184.35 | 41.08 | 143.28 | 0.00 | 0.00 |
August | 644.47 | 0.00 | 184.87 | 43.72 | 141.15 | 0.00 | 0.00 |
September | 533.41 | 0.26 | 174.30 | 42.78 | 131.52 | 0.00 | 0.00 |
October | 407.35 | 2.37 | 154.91 | 39.21 | 115.70 | 0.00 | 0.00 |
November | 279.86 | 26.06 | 133.14 | 34.12 | 99.03 | 0.00 | 0.00 |
December | 181.84 | 74.28 | 112.42 | 26.11 | 86.32 | 0.00 | 0.00 |
Annual Sum or Average | 405.87 | 29.51 | 160.80 | 37.83 | 122.96 | 0.00 | 0.00 |
Minimum of Months | 170.66 | 0.00 | 112.42 | 26.11 | 86.32 | 0.00 | 0.00 |
Maximum of Months | 644.47 | 102.48 | 200.91 | 50.54 | 150.37 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 201.50 | 52.31 | 131.20 | 61.96 | 69.24 | 0.00 | 0.00 |
February | 200.26 | 39.90 | 122.65 | 50.16 | 72.48 | 0.00 | 0.00 |
March | 185.76 | 26.18 | 99.88 | 26.36 | 73.52 | 0.00 | 0.00 |
April | 183.77 | 10.47 | 79.77 | 8.81 | 70.96 | 0.00 | 0.00 |
May | 223.65 | 0.54 | 67.49 | 1.27 | 66.21 | 0.00 | 0.00 |
June | 241.90 | 0.00 | 63.29 | 0.08 | 63.22 | 0.00 | 0.00 |
July | 279.25 | 0.00 | 63.21 | 0.42 | 62.79 | 0.00 | 0.00 |
August | 303.55 | 0.00 | 73.12 | 4.86 | 68.25 | 0.00 | 0.00 |
September | 299.73 | 0.12 | 96.92 | 22.29 | 74.63 | 0.00 | 0.00 |
October | 299.06 | 1.16 | 126.95 | 50.60 | 76.35 | 0.00 | 0.00 |
November | 267.66 | 13.30 | 140.50 | 68.07 | 72.43 | 0.00 | 0.00 |
December | 212.49 | 38.36 | 130.02 | 64.34 | 65.68 | 0.00 | 0.00 |
Annual Sum or Average | 241.81 | 15.09 | 99.44 | 29.82 | 69.62 | 0.00 | 0.00 |
Minimum of Months | 183.77 | 0.00 | 63.21 | 0.08 | 62.79 | 0.00 | 0.00 |
Maximum of Months | 303.55 | 52.31 | 140.50 | 68.07 | 76.35 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 265.50 | 275.56 | 192.84 | 0.00 | 192.84 | 0.00 | 0.00 |
February | 358.54 | 212.64 | 221.05 | 0.00 | 221.05 | 0.00 | 0.00 |
March | 504.37 | 142.08 | 253.95 | 0.00 | 253.94 | 0.00 | 0.00 |
April | 721.16 | 64.87 | 287.05 | 1.14 | 285.90 | 0.00 | 0.00 |
May | 1083.50 | 5.15 | 322.68 | 9.89 | 312.79 | 0.00 | 0.00 |
June | 1244.77 | 0.19 | 344.97 | 19.34 | 325.63 | 0.00 | 0.00 |
July | 1367.62 | 0.00 | 316.98 | 9.53 | 307.45 | 0.00 | 0.00 |
August | 1341.22 | 0.00 | 295.30 | 2.97 | 292.33 | 0.00 | 0.00 |
September | 1069.19 | 1.07 | 268.37 | 0.08 | 268.29 | 0.00 | 0.00 |
October | 791.60 | 9.60 | 237.81 | 0.00 | 237.81 | 0.00 | 0.00 |
November | 513.78 | 78.27 | 204.15 | 0.00 | 204.15 | 0.00 | 0.00 |
December | 303.17 | 201.74 | 179.99 | 0.00 | 179.99 | 0.00 | 0.00 |
Annual Sum or Average | 799.65 | 82.04 | 260.58 | 3.59 | 256.99 | 0.00 | 0.00 |
Minimum of Months | 265.50 | 0.00 | 179.99 | 0.00 | 179.99 | 0.00 | 0.00 |
Maximum of Months | 1367.62 | 275.56 | 344.97 | 19.34 | 325.63 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 258.70 | 289.36 | 192.84 | 0.00 | 192.84 | 0.00 | 0.00 |
February | 349.96 | 225.49 | 221.05 | 0.00 | 221.05 | 0.00 | 0.00 |
March | 493.03 | 152.88 | 253.95 | 0.00 | 253.94 | 0.00 | 0.00 |
April | 705.24 | 71.97 | 287.05 | 1.14 | 285.90 | 0.00 | 0.00 |
May | 1062.33 | 6.38 | 322.68 | 9.89 | 312.79 | 0.00 | 0.00 |
June | 1223.36 | 0.24 | 344.97 | 19.34 | 325.63 | 0.00 | 0.00 |
July | 1348.25 | 0.00 | 316.98 | 9.53 | 307.45 | 0.00 | 0.00 |
August | 1322.41 | 0.00 | 295.30 | 2.97 | 292.33 | 0.00 | 0.00 |
September | 1048.76 | 1.29 | 268.37 | 0.08 | 268.29 | 0.00 | 0.00 |
October | 772.04 | 11.79 | 237.81 | 0.00 | 237.81 | 0.00 | 0.00 |
November | 499.92 | 86.11 | 204.15 | 0.00 | 204.15 | 0.00 | 0.00 |
December | 294.83 | 214.29 | 179.99 | 0.00 | 179.99 | 0.00 | 0.00 |
Annual Sum or Average | 784.15 | 87.72 | 260.58 | 3.59 | 256.99 | 0.00 | 0.00 |
Minimum of Months | 258.70 | 0.00 | 179.99 | 0.00 | 179.99 | 0.00 | 0.00 |
Maximum of Months | 1348.25 | 289.36 | 344.97 | 19.34 | 325.63 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 469.68 | 238.41 | 302.78 | 98.28 | 204.50 | 0.00 | 0.00 |
February | 534.84 | 194.20 | 318.06 | 89.18 | 228.88 | 0.00 | 0.00 |
March | 631.31 | 131.07 | 328.65 | 73.29 | 255.36 | 0.00 | 0.00 |
April | 832.57 | 64.97 | 368.41 | 85.62 | 282.79 | 0.00 | 0.00 |
May | 1118.87 | 6.08 | 396.73 | 99.29 | 297.44 | 0.00 | 0.00 |
June | 1199.15 | 0.10 | 390.83 | 94.03 | 296.80 | 0.00 | 0.00 |
July | 1308.94 | 0.00 | 366.92 | 81.91 | 285.02 | 0.00 | 0.00 |
August | 1337.09 | 0.00 | 377.35 | 91.34 | 286.01 | 0.00 | 0.00 |
September | 1145.45 | 0.68 | 372.49 | 98.02 | 274.47 | 0.00 | 0.00 |
October | 948.93 | 10.54 | 363.72 | 113.83 | 249.89 | 0.00 | 0.00 |
November | 711.90 | 76.79 | 328.68 | 110.75 | 217.93 | 0.00 | 0.00 |
December | 486.31 | 179.70 | 279.53 | 89.28 | 190.25 | 0.00 | 0.00 |
Annual Sum or Average | 895.84 | 74.67 | 349.60 | 93.73 | 255.86 | 0.00 | 0.00 |
Minimum of Months | 469.68 | 0.00 | 279.53 | 73.29 | 190.25 | 0.00 | 0.00 |
Maximum of Months | 1337.09 | 238.41 | 396.73 | 113.83 | 297.44 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 629.05 | 204.41 | 400.08 | 157.72 | 242.36 | 0.00 | 0.00 |
February | 663.41 | 154.12 | 387.98 | 127.69 | 260.29 | 0.00 | 0.00 |
March | 680.60 | 99.02 | 341.31 | 67.10 | 274.21 | 0.00 | 0.00 |
April | 755.85 | 38.25 | 301.45 | 22.82 | 278.63 | 0.00 | 0.00 |
May | 980.50 | 1.60 | 282.41 | 6.63 | 275.77 | 0.00 | 0.00 |
June | 1074.94 | 0.00 | 279.37 | 6.83 | 272.54 | 0.00 | 0.00 |
July | 1198.33 | 0.00 | 269.56 | 4.33 | 265.22 | 0.00 | 0.00 |
August | 1249.39 | 0.00 | 287.36 | 13.40 | 273.96 | 0.00 | 0.00 |
September | 1164.56 | 0.36 | 338.71 | 56.76 | 281.95 | 0.00 | 0.00 |
October | 1080.28 | 3.43 | 404.67 | 128.80 | 275.87 | 0.00 | 0.00 |
November | 900.54 | 46.25 | 427.63 | 173.27 | 254.36 | 0.00 | 0.00 |
December | 674.30 | 144.99 | 392.66 | 163.78 | 228.88 | 0.00 | 0.00 |
Annual Sum or Average | 922.51 | 57.31 | 342.46 | 77.15 | 265.31 | 0.00 | 0.00 |
Minimum of Months | 629.05 | 0.00 | 269.56 | 4.33 | 228.88 | 0.00 | 0.00 |
Maximum of Months | 1249.39 | 204.41 | 427.63 | 173.27 | 281.95 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.195342E+10 | 0.453747E+09 | 0.121183E+10 | 0.572299E+09 | 0.639534E+09 | 0.00 | 0.00 |
February | 0.174866E+10 | 0.315089E+09 | 0.102322E+10 | 0.418497E+09 | 0.604726E+09 | 0.00 | 0.00 |
March | 0.178217E+10 | 0.235245E+09 | 0.922589E+09 | 0.243477E+09 | 0.679112E+09 | 0.00 | 0.00 |
April | 0.168076E+10 | 97617447.38 | 0.713015E+09 | 78751018.39 | 0.634264E+09 | 0.00 | 0.00 |
May | 0.203964E+10 | 6365833.21 | 0.623352E+09 | 11762118.07 | 0.611590E+09 | 0.00 | 0.00 |
June | 0.209581E+10 | 130328.87 | 0.565768E+09 | 699698.30 | 0.565069E+09 | 0.00 | 0.00 |
July | 0.248752E+10 | 0.00 | 0.583813E+09 | 3863005.71 | 0.579950E+09 | 0.00 | 0.00 |
August | 0.269717E+10 | 0.00 | 0.675368E+09 | 44924291.99 | 0.630443E+09 | 0.00 | 0.00 |
September | 0.262727E+10 | 1296296.11 | 0.866341E+09 | 0.199212E+09 | 0.667129E+09 | 0.00 | 0.00 |
October | 0.275936E+10 | 12964530.08 | 0.117257E+10 | 0.467356E+09 | 0.705217E+09 | 0.00 | 0.00 |
November | 0.244551E+10 | 0.120311E+09 | 0.125588E+10 | 0.608453E+09 | 0.647429E+09 | 0.00 | 0.00 |
December | 0.204487E+10 | 0.334350E+09 | 0.120092E+10 | 0.594298E+09 | 0.606627E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.263622E+11 | 0.157712E+10 | 0.108147E+11 | 0.324359E+10 | 0.757109E+10 | 0.00 | 0.00 |
Minimum of Months | 0.168076E+10 | 0.00 | 0.565768E+09 | 699698.30 | 0.565069E+09 | 0.00 | 0.00 |
Maximum of Months | 0.275936E+10 | 0.453747E+09 | 0.125588E+10 | 0.608453E+09 | 0.705217E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.545832E+10 | 0.130081E+10 | 0.341244E+10 | 0.161156E+10 | 0.180089E+10 | 0.00 | 0.00 |
February | 0.489006E+10 | 0.912422E+09 | 0.288133E+10 | 0.117846E+10 | 0.170287E+10 | 0.00 | 0.00 |
March | 0.497997E+10 | 0.688424E+09 | 0.259795E+10 | 0.685614E+09 | 0.191234E+10 | 0.00 | 0.00 |
April | 0.469112E+10 | 0.297611E+09 | 0.200780E+10 | 0.221758E+09 | 0.178605E+10 | 0.00 | 0.00 |
May | 0.567103E+10 | 22756113.93 | 0.175532E+10 | 33121348.96 | 0.172220E+10 | 0.00 | 0.00 |
June | 0.582055E+10 | 732516.44 | 0.159317E+10 | 1970304.27 | 0.159120E+10 | 0.00 | 0.00 |
July | 0.693586E+10 | 0.00 | 0.164398E+10 | 10877969.36 | 0.163310E+10 | 0.00 | 0.00 |
August | 0.754500E+10 | 0.00 | 0.190179E+10 | 0.126504E+09 | 0.177529E+10 | 0.00 | 0.00 |
September | 0.733518E+10 | 4728417.49 | 0.243956E+10 | 0.560968E+09 | 0.187859E+10 | 0.00 | 0.00 |
October | 0.771084E+10 | 48707899.36 | 0.330189E+10 | 0.131604E+10 | 0.198584E+10 | 0.00 | 0.00 |
November | 0.685525E+10 | 0.370817E+09 | 0.353648E+10 | 0.171336E+10 | 0.182312E+10 | 0.00 | 0.00 |
December | 0.572246E+10 | 0.966535E+09 | 0.338173E+10 | 0.167350E+10 | 0.170822E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.736156E+11 | 0.461354E+10 | 0.304534E+11 | 0.913374E+10 | 0.213197E+11 | 0.00 | 0.00 |
Minimum of Months | 0.469112E+10 | 0.00 | 0.159317E+10 | 1970304.27 | 0.159120E+10 | 0.00 | 0.00 |
Maximum of Months | 0.771084E+10 | 0.130081E+10 | 0.353648E+10 | 0.171336E+10 | 0.198584E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.725440E+10 | 0.171945E+10 | 0.443296E+10 | 0.209350E+10 | 0.233945E+10 | 0.00 | 0.00 |
February | 0.651613E+10 | 0.120500E+10 | 0.374301E+10 | 0.153089E+10 | 0.221212E+10 | 0.00 | 0.00 |
March | 0.664881E+10 | 0.916339E+09 | 0.337488E+10 | 0.890652E+09 | 0.248423E+10 | 0.00 | 0.00 |
April | 0.627912E+10 | 0.400565E+09 | 0.260825E+10 | 0.288076E+09 | 0.232018E+10 | 0.00 | 0.00 |
May | 0.760148E+10 | 31360828.94 | 0.228026E+10 | 43026517.26 | 0.223723E+10 | 0.00 | 0.00 |
June | 0.780367E+10 | 982876.98 | 0.206961E+10 | 2559537.38 | 0.206705E+10 | 0.00 | 0.00 |
July | 0.931536E+10 | 0.00 | 0.213562E+10 | 14131101.28 | 0.212149E+10 | 0.00 | 0.00 |
August | 0.101460E+11 | 0.00 | 0.247053E+10 | 0.164336E+09 | 0.230620E+10 | 0.00 | 0.00 |
September | 0.986178E+10 | 6094612.57 | 0.316913E+10 | 0.728729E+09 | 0.244040E+10 | 0.00 | 0.00 |
October | 0.103568E+11 | 59553177.28 | 0.428934E+10 | 0.170962E+10 | 0.257973E+10 | 0.00 | 0.00 |
November | 0.916582E+10 | 0.480760E+09 | 0.459409E+10 | 0.222576E+10 | 0.236833E+10 | 0.00 | 0.00 |
December | 0.761170E+10 | 0.127464E+10 | 0.439305E+10 | 0.217398E+10 | 0.221908E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.985611E+11 | 0.609475E+10 | 0.395607E+11 | 0.118652E+11 | 0.276955E+11 | 0.00 | 0.00 |
Minimum of Months | 0.627912E+10 | 0.00 | 0.206961E+10 | 2559537.38 | 0.206705E+10 | 0.00 | 0.00 |
Maximum of Months | 0.103568E+11 | 0.171945E+10 | 0.459409E+10 | 0.222576E+10 | 0.257973E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.732053E+09 | 0.273799E+09 | 0.484733E+09 | 0.183664E+09 | 0.301069E+09 | 0.00 | 0.00 |
February | 0.740792E+09 | 0.189370E+09 | 0.455005E+09 | 0.155037E+09 | 0.299968E+09 | 0.00 | 0.00 |
March | 0.938211E+09 | 0.139884E+09 | 0.512895E+09 | 0.145985E+09 | 0.366909E+09 | 0.00 | 0.00 |
April | 0.105692E+10 | 56761196.01 | 0.490684E+09 | 0.113815E+09 | 0.376869E+09 | 0.00 | 0.00 |
May | 0.143029E+10 | 3714860.85 | 0.516372E+09 | 0.119983E+09 | 0.396389E+09 | 0.00 | 0.00 |
June | 0.151838E+10 | 48420.23 | 0.504872E+09 | 0.123966E+09 | 0.380905E+09 | 0.00 | 0.00 |
July | 0.170785E+10 | 0.00 | 0.487909E+09 | 0.107135E+09 | 0.380774E+09 | 0.00 | 0.00 |
August | 0.177696E+10 | 0.00 | 0.515694E+09 | 0.124857E+09 | 0.390837E+09 | 0.00 | 0.00 |
September | 0.152783E+10 | 740374.22 | 0.523706E+09 | 0.150254E+09 | 0.373452E+09 | 0.00 | 0.00 |
October | 0.134899E+10 | 7007479.59 | 0.555752E+09 | 0.197413E+09 | 0.358339E+09 | 0.00 | 0.00 |
November | 0.102584E+10 | 69340195.23 | 0.517823E+09 | 0.208730E+09 | 0.309093E+09 | 0.00 | 0.00 |
December | 0.771588E+09 | 0.199749E+09 | 0.469683E+09 | 0.187423E+09 | 0.282260E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.145757E+11 | 0.940414E+09 | 0.603513E+10 | 0.181826E+10 | 0.421686E+10 | 0.00 | 0.00 |
Minimum of Months | 0.732053E+09 | 0.00 | 0.455005E+09 | 0.107135E+09 | 0.282260E+09 | 0.00 | 0.00 |
Maximum of Months | 0.177696E+10 | 0.273799E+09 | 0.555752E+09 | 0.208730E+09 | 0.396389E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.467553E+09 | 0.276721E+09 | 0.318922E+09 | 70510841.87 | 0.248411E+09 | 0.00 | 0.00 |
February | 0.529622E+09 | 0.188008E+09 | 0.329094E+09 | 72293154.79 | 0.256801E+09 | 0.00 | 0.00 |
March | 0.782972E+09 | 0.137492E+09 | 0.427652E+09 | 97846934.75 | 0.329805E+09 | 0.00 | 0.00 |
April | 0.988664E+09 | 55419086.56 | 0.456000E+09 | 98668368.79 | 0.357332E+09 | 0.00 | 0.00 |
May | 0.143165E+10 | 3441016.93 | 0.516596E+09 | 0.121444E+09 | 0.395153E+09 | 0.00 | 0.00 |
June | 0.155102E+10 | 50959.99 | 0.520750E+09 | 0.130990E+09 | 0.389760E+09 | 0.00 | 0.00 |
July | 0.172114E+10 | 0.00 | 0.493768E+09 | 0.110019E+09 | 0.383750E+09 | 0.00 | 0.00 |
August | 0.173609E+10 | 0.00 | 0.495156E+09 | 0.117111E+09 | 0.378045E+09 | 0.00 | 0.00 |
September | 0.139146E+10 | 708000.83 | 0.451791E+09 | 0.110897E+09 | 0.340894E+09 | 0.00 | 0.00 |
October | 0.109998E+10 | 6675555.96 | 0.414908E+09 | 0.105009E+09 | 0.309899E+09 | 0.00 | 0.00 |
November | 0.734499E+09 | 68638837.16 | 0.345110E+09 | 88428078.83 | 0.256682E+09 | 0.00 | 0.00 |
December | 0.497396E+09 | 0.200087E+09 | 0.301111E+09 | 69919888.64 | 0.231191E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.129321E+11 | 0.937242E+09 | 0.507086E+10 | 0.119314E+10 | 0.387772E+10 | 0.00 | 0.00 |
Minimum of Months | 0.467553E+09 | 0.00 | 0.301111E+09 | 69919888.64 | 0.231191E+09 | 0.00 | 0.00 |
Maximum of Months | 0.173609E+10 | 0.276721E+09 | 0.520750E+09 | 0.130990E+09 | 0.395153E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.288477E+09 | 0.100074E+09 | 0.191643E+09 | 90504684.80 | 0.101138E+09 | 0.00 | 0.00 |
February | 0.258692E+09 | 73386535.34 | 0.161815E+09 | 66182041.33 | 95633313.98 | 0.00 | 0.00 |
March | 0.262577E+09 | 58518539.24 | 0.145901E+09 | 38503945.46 | 0.107397E+09 | 0.00 | 0.00 |
April | 0.246218E+09 | 29055019.29 | 0.112759E+09 | 12453866.36 | 0.100305E+09 | 0.00 | 0.00 |
May | 0.301296E+09 | 3736280.20 | 98579426.39 | 1860088.28 | 96719338.11 | 0.00 | 0.00 |
June | 0.313513E+09 | 128663.36 | 89472966.04 | 110651.89 | 89362314.15 | 0.00 | 0.00 |
July | 0.379660E+09 | 0.00 | 92326627.88 | 610904.57 | 91715723.31 | 0.00 | 0.00 |
August | 0.415733E+09 | 0.00 | 0.106805E+09 | 7104430.40 | 99700743.65 | 0.00 | 0.00 |
September | 0.398400E+09 | 839817.37 | 0.137006E+09 | 31503830.62 | 0.105502E+09 | 0.00 | 0.00 |
October | 0.416037E+09 | 6700747.40 | 0.185434E+09 | 73908816.38 | 0.111525E+09 | 0.00 | 0.00 |
November | 0.368092E+09 | 33730673.98 | 0.198609E+09 | 96222111.04 | 0.102386E+09 | 0.00 | 0.00 |
December | 0.304270E+09 | 78374987.69 | 0.189918E+09 | 93983606.78 | 95933929.30 | 0.00 | 0.00 |
Annual Sum or Average | 0.395296E+10 | 0.384546E+09 | 0.171027E+10 | 0.512949E+09 | 0.119732E+10 | 0.00 | 0.00 |
Minimum of Months | 0.246218E+09 | 0.00 | 89472966.04 | 110651.89 | 89362314.15 | 0.00 | 0.00 |
Maximum of Months | 0.416037E+09 | 0.100074E+09 | 0.198609E+09 | 96222111.04 | 0.111525E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 80982707.35 | 78076789.05 | 59039365.81 | 0.00 | 59039365.81 | 0.00 | 0.00 |
February | 98317636.45 | 52188416.72 | 61126747.57 | 0.00 | 61126747.57 | 0.00 | 0.00 |
March | 0.152748E+09 | 36815514.49 | 77746598.86 | 932.05 | 77745666.81 | 0.00 | 0.00 |
April | 0.211919E+09 | 13869263.81 | 85045784.63 | 338963.68 | 84706820.94 | 0.00 | 0.00 |
May | 0.336534E+09 | 622889.14 | 98791330.93 | 3029246.37 | 95762084.56 | 0.00 | 0.00 |
June | 0.376630E+09 | 1137.14 | 0.102206E+09 | 5730003.48 | 96476416.12 | 0.00 | 0.00 |
July | 0.428459E+09 | 0.00 | 97045751.09 | 2918681.07 | 94127070.02 | 0.00 | 0.00 |
August | 0.420383E+09 | 0.00 | 90407823.18 | 909070.09 | 89498753.09 | 0.00 | 0.00 |
September | 0.322787E+09 | 130285.48 | 79511883.87 | 24189.57 | 79487694.30 | 0.00 | 0.00 |
October | 0.244466E+09 | 1390449.26 | 72805391.48 | 0.00 | 72805391.48 | 0.00 | 0.00 |
November | 0.149203E+09 | 17639523.20 | 60485666.11 | 0.00 | 60485666.11 | 0.00 | 0.00 |
December | 91474927.12 | 55440317.53 | 55105609.02 | 0.00 | 55105609.02 | 0.00 | 0.00 |
Annual Sum or Average | 0.291390E+10 | 0.256175E+09 | 0.939318E+09 | 12951086.32 | 0.926367E+09 | 0.00 | 0.00 |
Minimum of Months | 80982707.35 | 0.00 | 55105609.02 | 0.00 | 55105609.02 | 0.00 | 0.00 |
Maximum of Months | 0.428459E+09 | 78076789.05 | 0.102206E+09 | 5730003.48 | 96476416.12 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.730072E+09 | 0.264116E+09 | 0.488402E+09 | 0.188195E+09 | 0.300207E+09 | 0.00 | 0.00 |
February | 0.721765E+09 | 0.180518E+09 | 0.447700E+09 | 0.149250E+09 | 0.298449E+09 | 0.00 | 0.00 |
March | 0.883275E+09 | 0.131125E+09 | 0.482771E+09 | 0.122228E+09 | 0.360543E+09 | 0.00 | 0.00 |
April | 0.106808E+10 | 53522676.70 | 0.494826E+09 | 0.118539E+09 | 0.376287E+09 | 0.00 | 0.00 |
May | 0.145970E+10 | 3352232.30 | 0.531218E+09 | 0.132246E+09 | 0.398972E+09 | 0.00 | 0.00 |
June | 0.151208E+10 | 41409.80 | 0.498606E+09 | 0.118365E+09 | 0.380241E+09 | 0.00 | 0.00 |
July | 0.171493E+10 | 0.00 | 0.488481E+09 | 0.108255E+09 | 0.380226E+09 | 0.00 | 0.00 |
August | 0.178030E+10 | 0.00 | 0.515640E+09 | 0.126198E+09 | 0.389443E+09 | 0.00 | 0.00 |
September | 0.152300E+10 | 764297.82 | 0.518725E+09 | 0.146714E+09 | 0.372010E+09 | 0.00 | 0.00 |
October | 0.135658E+10 | 6987926.51 | 0.557535E+09 | 0.198652E+09 | 0.358884E+09 | 0.00 | 0.00 |
November | 0.101854E+10 | 67981859.78 | 0.512341E+09 | 0.203689E+09 | 0.308652E+09 | 0.00 | 0.00 |
December | 0.748950E+09 | 0.194067E+09 | 0.458646E+09 | 0.178324E+09 | 0.280322E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.145173E+11 | 0.902476E+09 | 0.599489E+10 | 0.179065E+10 | 0.420424E+10 | 0.00 | 0.00 |
Minimum of Months | 0.721765E+09 | 0.00 | 0.447700E+09 | 0.108255E+09 | 0.280322E+09 | 0.00 | 0.00 |
Maximum of Months | 0.178030E+10 | 0.264116E+09 | 0.557535E+09 | 0.203689E+09 | 0.398972E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.456658E+09 | 0.257463E+09 | 0.322590E+09 | 75041170.44 | 0.247549E+09 | 0.00 | 0.00 |
February | 0.507457E+09 | 0.176103E+09 | 0.321789E+09 | 66506363.82 | 0.255282E+09 | 0.00 | 0.00 |
March | 0.727051E+09 | 0.128162E+09 | 0.397529E+09 | 74089493.45 | 0.323439E+09 | 0.00 | 0.00 |
April | 0.100007E+10 | 52636706.97 | 0.460143E+09 | 0.103392E+09 | 0.356751E+09 | 0.00 | 0.00 |
May | 0.146129E+10 | 3280961.06 | 0.531442E+09 | 0.133707E+09 | 0.397736E+09 | 0.00 | 0.00 |
June | 0.154480E+10 | 43967.51 | 0.514483E+09 | 0.125388E+09 | 0.389095E+09 | 0.00 | 0.00 |
July | 0.172827E+10 | 0.00 | 0.494340E+09 | 0.111139E+09 | 0.383202E+09 | 0.00 | 0.00 |
August | 0.173946E+10 | 0.00 | 0.495102E+09 | 0.118451E+09 | 0.376651E+09 | 0.00 | 0.00 |
September | 0.138654E+10 | 731480.17 | 0.446810E+09 | 0.107357E+09 | 0.339453E+09 | 0.00 | 0.00 |
October | 0.110693E+10 | 6451085.50 | 0.416691E+09 | 0.106247E+09 | 0.310444E+09 | 0.00 | 0.00 |
November | 0.723848E+09 | 64627302.65 | 0.339628E+09 | 83387581.41 | 0.256241E+09 | 0.00 | 0.00 |
December | 0.468225E+09 | 0.187364E+09 | 0.290075E+09 | 60821109.14 | 0.229254E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.128506E+11 | 0.876863E+09 | 0.503062E+10 | 0.116553E+10 | 0.386510E+10 | 0.00 | 0.00 |
Minimum of Months | 0.456658E+09 | 0.00 | 0.290075E+09 | 60821109.14 | 0.229254E+09 | 0.00 | 0.00 |
Maximum of Months | 0.173946E+10 | 0.257463E+09 | 0.531442E+09 | 0.133707E+09 | 0.397736E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.864551E+09 | 0.302515E+09 | 0.543135E+09 | 0.196098E+09 | 0.347037E+09 | 0.00 | 0.00 |
February | 0.843554E+09 | 0.204326E+09 | 0.483030E+09 | 0.143398E+09 | 0.339632E+09 | 0.00 | 0.00 |
March | 0.990319E+09 | 0.145532E+09 | 0.484552E+09 | 83429361.34 | 0.401123E+09 | 0.00 | 0.00 |
April | 0.109640E+10 | 55978200.92 | 0.428555E+09 | 27718374.10 | 0.400836E+09 | 0.00 | 0.00 |
May | 0.148000E+10 | 3200003.11 | 0.427609E+09 | 10592657.45 | 0.417017E+09 | 0.00 | 0.00 |
June | 0.157992E+10 | 61228.62 | 0.415276E+09 | 12652860.81 | 0.402624E+09 | 0.00 | 0.00 |
July | 0.182230E+10 | 0.00 | 0.410280E+09 | 7646502.20 | 0.402633E+09 | 0.00 | 0.00 |
August | 0.187419E+10 | 0.00 | 0.427271E+09 | 17362675.64 | 0.409908E+09 | 0.00 | 0.00 |
September | 0.164097E+10 | 864978.59 | 0.469103E+09 | 68312442.74 | 0.400791E+09 | 0.00 | 0.00 |
October | 0.152374E+10 | 7326826.32 | 0.559505E+09 | 0.160140E+09 | 0.399365E+09 | 0.00 | 0.00 |
November | 0.121136E+10 | 71227383.10 | 0.561362E+09 | 0.208487E+09 | 0.352875E+09 | 0.00 | 0.00 |
December | 0.931181E+09 | 0.213441E+09 | 0.530876E+09 | 0.203636E+09 | 0.327239E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.158585E+11 | 0.100447E+10 | 0.574055E+10 | 0.113947E+10 | 0.460108E+10 | 0.00 | 0.00 |
Minimum of Months | 0.843554E+09 | 0.00 | 0.410280E+09 | 7646502.20 | 0.327239E+09 | 0.00 | 0.00 |
Maximum of Months | 0.187419E+10 | 0.302515E+09 | 0.561362E+09 | 0.208487E+09 | 0.417017E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.719713E+09 | 0.272433E+09 | 0.484733E+09 | 0.183664E+09 | 0.301069E+09 | 0.00 | 0.00 |
February | 0.727572E+09 | 0.189166E+09 | 0.455005E+09 | 0.155037E+09 | 0.299968E+09 | 0.00 | 0.00 |
March | 0.922401E+09 | 0.139494E+09 | 0.512895E+09 | 0.145985E+09 | 0.366909E+09 | 0.00 | 0.00 |
April | 0.104119E+10 | 56167377.94 | 0.490684E+09 | 0.113815E+09 | 0.376869E+09 | 0.00 | 0.00 |
May | 0.141700E+10 | 3551326.33 | 0.516372E+09 | 0.119983E+09 | 0.396389E+09 | 0.00 | 0.00 |
June | 0.150871E+10 | 38639.09 | 0.504872E+09 | 0.123966E+09 | 0.380905E+09 | 0.00 | 0.00 |
July | 0.169697E+10 | 0.00 | 0.487909E+09 | 0.107135E+09 | 0.380774E+09 | 0.00 | 0.00 |
August | 0.176628E+10 | 0.00 | 0.515694E+09 | 0.124857E+09 | 0.390837E+09 | 0.00 | 0.00 |
September | 0.151713E+10 | 706421.39 | 0.523706E+09 | 0.150254E+09 | 0.373452E+09 | 0.00 | 0.00 |
October | 0.133727E+10 | 6675342.17 | 0.555752E+09 | 0.197413E+09 | 0.358339E+09 | 0.00 | 0.00 |
November | 0.101363E+10 | 68319303.05 | 0.517823E+09 | 0.208730E+09 | 0.309093E+09 | 0.00 | 0.00 |
December | 0.759185E+09 | 0.199130E+09 | 0.469683E+09 | 0.187423E+09 | 0.282260E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.144271E+11 | 0.935681E+09 | 0.603513E+10 | 0.181826E+10 | 0.421686E+10 | 0.00 | 0.00 |
Minimum of Months | 0.719713E+09 | 0.00 | 0.455005E+09 | 0.107135E+09 | 0.282260E+09 | 0.00 | 0.00 |
Maximum of Months | 0.176628E+10 | 0.272433E+09 | 0.555752E+09 | 0.208730E+09 | 0.396389E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.457096E+09 | 0.274486E+09 | 0.318922E+09 | 70510841.87 | 0.248411E+09 | 0.00 | 0.00 |
February | 0.518130E+09 | 0.187454E+09 | 0.329094E+09 | 72293154.79 | 0.256801E+09 | 0.00 | 0.00 |
March | 0.768420E+09 | 0.137028E+09 | 0.427652E+09 | 97846934.75 | 0.329805E+09 | 0.00 | 0.00 |
April | 0.973887E+09 | 54910840.28 | 0.456000E+09 | 98668368.79 | 0.357332E+09 | 0.00 | 0.00 |
May | 0.141848E+10 | 3305743.16 | 0.516596E+09 | 0.121444E+09 | 0.395153E+09 | 0.00 | 0.00 |
June | 0.154062E+10 | 43945.76 | 0.520750E+09 | 0.130990E+09 | 0.389760E+09 | 0.00 | 0.00 |
July | 0.171060E+10 | 0.00 | 0.493768E+09 | 0.110019E+09 | 0.383750E+09 | 0.00 | 0.00 |
August | 0.172614E+10 | 0.00 | 0.495156E+09 | 0.117111E+09 | 0.378045E+09 | 0.00 | 0.00 |
September | 0.138261E+10 | 674462.55 | 0.451791E+09 | 0.110897E+09 | 0.340894E+09 | 0.00 | 0.00 |
October | 0.109104E+10 | 6340185.28 | 0.414908E+09 | 0.105009E+09 | 0.309899E+09 | 0.00 | 0.00 |
November | 0.725402E+09 | 67551235.92 | 0.345110E+09 | 88428078.83 | 0.256682E+09 | 0.00 | 0.00 |
December | 0.487046E+09 | 0.198939E+09 | 0.301111E+09 | 69919888.64 | 0.231191E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.127995E+11 | 0.930734E+09 | 0.507086E+10 | 0.119314E+10 | 0.387772E+10 | 0.00 | 0.00 |
Minimum of Months | 0.457096E+09 | 0.00 | 0.301111E+09 | 69919888.64 | 0.231191E+09 | 0.00 | 0.00 |
Maximum of Months | 0.172614E+10 | 0.274486E+09 | 0.520750E+09 | 0.130990E+09 | 0.395153E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.539685E+09 | 0.140119E+09 | 0.351398E+09 | 0.165950E+09 | 0.185447E+09 | 0.00 | 0.00 |
February | 0.484477E+09 | 96519884.72 | 0.296706E+09 | 0.121352E+09 | 0.175354E+09 | 0.00 | 0.00 |
March | 0.497537E+09 | 70130186.69 | 0.267526E+09 | 70601201.94 | 0.196924E+09 | 0.00 | 0.00 |
April | 0.476333E+09 | 27150465.65 | 0.206756E+09 | 22835528.24 | 0.183920E+09 | 0.00 | 0.00 |
May | 0.599028E+09 | 1439568.19 | 0.180756E+09 | 3410675.63 | 0.177346E+09 | 0.00 | 0.00 |
June | 0.627002E+09 | 2250.46 | 0.164058E+09 | 202892.36 | 0.163856E+09 | 0.00 | 0.00 |
July | 0.747939E+09 | 0.00 | 0.169291E+09 | 1120160.45 | 0.168171E+09 | 0.00 | 0.00 |
August | 0.813032E+09 | 0.00 | 0.195839E+09 | 13026751.39 | 0.182812E+09 | 0.00 | 0.00 |
September | 0.776903E+09 | 306814.59 | 0.251216E+09 | 57765724.55 | 0.193450E+09 | 0.00 | 0.00 |
October | 0.801005E+09 | 3118351.74 | 0.340014E+09 | 0.135520E+09 | 0.204494E+09 | 0.00 | 0.00 |
November | 0.693770E+09 | 34479431.94 | 0.364171E+09 | 0.176434E+09 | 0.187737E+09 | 0.00 | 0.00 |
December | 0.569126E+09 | 0.102739E+09 | 0.348235E+09 | 0.172329E+09 | 0.175905E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.762584E+10 | 0.476005E+09 | 0.313596E+10 | 0.940548E+09 | 0.219542E+10 | 0.00 | 0.00 |
Minimum of Months | 0.476333E+09 | 0.00 | 0.164058E+09 | 202892.36 | 0.163856E+09 | 0.00 | 0.00 |
Maximum of Months | 0.813032E+09 | 0.140119E+09 | 0.364171E+09 | 0.176434E+09 | 0.204494E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.711114E+09 | 0.738047E+09 | 0.516506E+09 | 0.00 | 0.516506E+09 | 0.00 | 0.00 |
February | 0.867382E+09 | 0.514416E+09 | 0.534768E+09 | 0.00 | 0.534768E+09 | 0.00 | 0.00 |
March | 0.135090E+10 | 0.380536E+09 | 0.680167E+09 | 8154.03 | 0.680159E+09 | 0.00 | 0.00 |
April | 0.186925E+10 | 0.168130E+09 | 0.744024E+09 | 2965426.81 | 0.741058E+09 | 0.00 | 0.00 |
May | 0.290204E+10 | 13781870.43 | 0.864277E+09 | 26501389.01 | 0.837775E+09 | 0.00 | 0.00 |
June | 0.322646E+10 | 480065.24 | 0.894154E+09 | 50128986.72 | 0.844025E+09 | 0.00 | 0.00 |
July | 0.366304E+10 | 0.00 | 0.849006E+09 | 25534107.42 | 0.823472E+09 | 0.00 | 0.00 |
August | 0.359234E+10 | 0.00 | 0.790934E+09 | 7953007.84 | 0.782981E+09 | 0.00 | 0.00 |
September | 0.277134E+10 | 2766200.81 | 0.695610E+09 | 211622.67 | 0.695399E+09 | 0.00 | 0.00 |
October | 0.212023E+10 | 25699647.42 | 0.636939E+09 | 0.00 | 0.636939E+09 | 0.00 | 0.00 |
November | 0.133172E+10 | 0.202884E+09 | 0.529159E+09 | 0.00 | 0.529159E+09 | 0.00 | 0.00 |
December | 0.812023E+09 | 0.540350E+09 | 0.482092E+09 | 0.00 | 0.482092E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.252178E+11 | 0.258709E+10 | 0.821764E+10 | 0.113303E+09 | 0.810433E+10 | 0.00 | 0.00 |
Minimum of Months | 0.711114E+09 | 0.00 | 0.482092E+09 | 0.00 | 0.482092E+09 | 0.00 | 0.00 |
Maximum of Months | 0.366304E+10 | 0.738047E+09 | 0.894154E+09 | 50128986.72 | 0.844025E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.692895E+09 | 0.775033E+09 | 0.516506E+09 | 0.00 | 0.516506E+09 | 0.00 | 0.00 |
February | 0.846614E+09 | 0.545505E+09 | 0.534768E+09 | 0.00 | 0.534768E+09 | 0.00 | 0.00 |
March | 0.132053E+10 | 0.409482E+09 | 0.680167E+09 | 8154.03 | 0.680159E+09 | 0.00 | 0.00 |
April | 0.182799E+10 | 0.186549E+09 | 0.744024E+09 | 2965426.81 | 0.741058E+09 | 0.00 | 0.00 |
May | 0.284533E+10 | 17080328.13 | 0.864277E+09 | 26501389.01 | 0.837775E+09 | 0.00 | 0.00 |
June | 0.317094E+10 | 617348.58 | 0.894154E+09 | 50128986.72 | 0.844025E+09 | 0.00 | 0.00 |
July | 0.361116E+10 | 0.00 | 0.849006E+09 | 25534107.42 | 0.823472E+09 | 0.00 | 0.00 |
August | 0.354194E+10 | 0.00 | 0.790934E+09 | 7953007.84 | 0.782981E+09 | 0.00 | 0.00 |
September | 0.271838E+10 | 3342489.58 | 0.695610E+09 | 211622.67 | 0.695399E+09 | 0.00 | 0.00 |
October | 0.206783E+10 | 31566403.62 | 0.636939E+09 | 0.00 | 0.636939E+09 | 0.00 | 0.00 |
November | 0.129580E+10 | 0.223196E+09 | 0.529159E+09 | 0.00 | 0.529159E+09 | 0.00 | 0.00 |
December | 0.789663E+09 | 0.573954E+09 | 0.482092E+09 | 0.00 | 0.482092E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.247291E+11 | 0.276633E+10 | 0.821764E+10 | 0.113303E+09 | 0.810433E+10 | 0.00 | 0.00 |
Minimum of Months | 0.692895E+09 | 0.00 | 0.482092E+09 | 0.00 | 0.482092E+09 | 0.00 | 0.00 |
Maximum of Months | 0.361116E+10 | 0.775033E+09 | 0.894154E+09 | 50128986.72 | 0.844025E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.125800E+10 | 0.638560E+09 | 0.810957E+09 | 0.263225E+09 | 0.547732E+09 | 0.00 | 0.00 |
February | 0.129388E+10 | 0.469799E+09 | 0.769453E+09 | 0.215747E+09 | 0.553706E+09 | 0.00 | 0.00 |
March | 0.169091E+10 | 0.351049E+09 | 0.880257E+09 | 0.196307E+09 | 0.683950E+09 | 0.00 | 0.00 |
April | 0.215802E+10 | 0.168405E+09 | 0.954919E+09 | 0.221917E+09 | 0.733002E+09 | 0.00 | 0.00 |
May | 0.299678E+10 | 16289263.39 | 0.106260E+10 | 0.265935E+09 | 0.796668E+09 | 0.00 | 0.00 |
June | 0.310820E+10 | 248454.14 | 0.101303E+10 | 0.243737E+09 | 0.769298E+09 | 0.00 | 0.00 |
July | 0.350587E+10 | 0.00 | 0.982768E+09 | 0.219378E+09 | 0.763390E+09 | 0.00 | 0.00 |
August | 0.358127E+10 | 0.00 | 0.101069E+10 | 0.244632E+09 | 0.766056E+09 | 0.00 | 0.00 |
September | 0.296901E+10 | 1764389.05 | 0.965485E+09 | 0.254056E+09 | 0.711429E+09 | 0.00 | 0.00 |
October | 0.254160E+10 | 28235147.41 | 0.974180E+09 | 0.304884E+09 | 0.669296E+09 | 0.00 | 0.00 |
November | 0.184524E+10 | 0.199034E+09 | 0.851932E+09 | 0.287065E+09 | 0.564867E+09 | 0.00 | 0.00 |
December | 0.130253E+10 | 0.481306E+09 | 0.748690E+09 | 0.239136E+09 | 0.509553E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.282513E+11 | 0.235469E+10 | 0.110250E+11 | 0.295602E+10 | 0.806895E+10 | 0.00 | 0.00 |
Minimum of Months | 0.125800E+10 | 0.00 | 0.748690E+09 | 0.196307E+09 | 0.509553E+09 | 0.00 | 0.00 |
Maximum of Months | 0.358127E+10 | 0.638560E+09 | 0.106260E+10 | 0.304884E+09 | 0.796668E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.168485E+10 | 0.547479E+09 | 0.107156E+10 | 0.422435E+09 | 0.649126E+09 | 0.00 | 0.00 |
February | 0.160491E+10 | 0.372839E+09 | 0.938601E+09 | 0.308908E+09 | 0.629693E+09 | 0.00 | 0.00 |
March | 0.182291E+10 | 0.265206E+09 | 0.914163E+09 | 0.179722E+09 | 0.734441E+09 | 0.00 | 0.00 |
April | 0.195917E+10 | 99143935.86 | 0.781360E+09 | 59145604.85 | 0.722215E+09 | 0.00 | 0.00 |
May | 0.262617E+10 | 4276381.96 | 0.756400E+09 | 17766784.03 | 0.738633E+09 | 0.00 | 0.00 |
June | 0.278626E+10 | 9463.05 | 0.724137E+09 | 17700787.91 | 0.706436E+09 | 0.00 | 0.00 |
July | 0.320960E+10 | 0.00 | 0.721980E+09 | 11604569.87 | 0.710375E+09 | 0.00 | 0.00 |
August | 0.334638E+10 | 0.00 | 0.769652E+09 | 35886594.61 | 0.733766E+09 | 0.00 | 0.00 |
September | 0.301853E+10 | 922569.02 | 0.877939E+09 | 0.147118E+09 | 0.730821E+09 | 0.00 | 0.00 |
October | 0.289342E+10 | 9182970.29 | 0.108387E+10 | 0.344973E+09 | 0.738894E+09 | 0.00 | 0.00 |
November | 0.233420E+10 | 0.119879E+09 | 0.110841E+10 | 0.449122E+09 | 0.659291E+09 | 0.00 | 0.00 |
December | 0.180604E+10 | 0.388345E+09 | 0.105171E+10 | 0.438673E+09 | 0.613039E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.290924E+11 | 0.180728E+10 | 0.107998E+11 | 0.243306E+10 | 0.836673E+10 | 0.00 | 0.00 |
Minimum of Months | 0.160491E+10 | 0.00 | 0.721980E+09 | 11604569.87 | 0.613039E+09 | 0.00 | 0.00 |
Maximum of Months | 0.334638E+10 | 0.547479E+09 | 0.110841E+10 | 0.449122E+09 | 0.738894E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 19.24 | 14.74 | 11.63 | 2.95 | 7.91 | 83.00 | 101.34 | 0.00 |
February | 20.75 | 16.26 | 13.46 | 3.66 | 9.80 | 96.50 | 106.33 | 0.00 |
March | 23.12 | 16.75 | 12.67 | 3.48 | 11.63 | 114.51 | 110.36 | 0.00 |
April | 26.49 | 19.17 | 14.91 | 3.36 | 14.65 | 129.52 | 127.73 | 0.00 |
May | 31.37 | 21.91 | 17.14 | 3.30 | 19.37 | 135.62 | 152.47 | 0.00 |
June | 32.97 | 24.78 | 21.39 | 3.95 | 20.59 | 135.23 | 162.31 | 0.00 |
July | 35.08 | 26.48 | 23.16 | 3.85 | 24.14 | 131.49 | 150.69 | 0.00 |
August | 35.31 | 27.02 | 24.10 | 3.89 | 24.33 | 129.32 | 147.63 | 0.00 |
September | 32.49 | 25.68 | 23.13 | 3.64 | 20.59 | 118.70 | 140.92 | 0.00 |
October | 29.53 | 22.66 | 19.34 | 3.16 | 16.84 | 101.82 | 135.23 | 0.00 |
November | 25.53 | 19.62 | 16.50 | 2.98 | 12.88 | 85.82 | 121.41 | 0.00 |
December | 21.13 | 16.84 | 14.23 | 2.84 | 10.14 | 76.46 | 98.30 | 0.00 |
Annual Sum or Average | 27.79 | 21.02 | 17.66 | 3.42 | 16.11 | 111.56 | 129.66 | 0.00 |
Minimum of Months | 19.24 | 14.74 | 11.63 | 2.84 | 7.91 | 76.46 | 98.30 | 0.00 |
Maximum of Months | 35.31 | 27.02 | 24.10 | 3.95 | 24.33 | 135.62 | 162.31 | 0.00 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 28.00 | 23-JAN-13:00 | 16.55 | 9.00 | 4.60 | 16.85 | 268.00 | 249.50 |
February | 32.50 | 06-FEB-14:00 | 17.28 | 6.50 | 6.20 | 21.27 | 242.00 | 327.50 |
March | 38.00 | 27-MAR-10:00 | 18.84 | 6.00 | 7.70 | 21.44 | 329.50 | 440.00 |
April | 42.00 | 28-APR-11:00 | 19.18 | 2.00 | 2.60 | 24.16 | 371.50 | 432.50 |
May | 42.10 | 31-MAY-18:00 | 20.76 | 8.00 | 5.10 | 30.18 | 0.00 | 0.00 |
June | 43.00 | 12-JUN-11:00 | 24.56 | 17.00 | 3.60 | 28.91 | 372.00 | 427.00 |
July | 46.00 | 21-JUL-11:00 | 22.01 | 9.00 | 3.60 | 32.99 | 306.00 | 562.50 |
August | 46.00 | 16-AUG-11:00 | 25.38 | 17.00 | 7.20 | 31.75 | 273.00 | 629.50 |
September | 41.20 | 26-SEP-12:00 | 22.43 | 13.00 | 4.10 | 26.15 | 325.00 | 455.00 |
October | 38.00 | 04-OCT-11:00 | 19.81 | 9.00 | 1.00 | 22.13 | 338.00 | 421.50 |
November | 34.00 | 05-NOV-11:00 | 17.15 | 5.00 | 2.10 | 17.39 | 294.00 | 427.50 |
December | 30.00 | 10-DEC-11:00 | 19.04 | 13.00 | 4.10 | 21.27 | 305.00 | 214.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 28.00 | 16.55 | 2.00 | 1.00 | 16.85 | 0.00 | 0.00 | |
Maximum of Months | 46.00 | 25.38 | 17.00 | 7.70 | 32.99 | 372.00 | 629.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 12.00 | 09-JAN-07:00 | 12.00 | 12.00 | 1.00 | -1.9 | 54.50 | 10.00 |
February | 13.00 | 01-FEB-04:00 | 12.45 | 12.00 | 1.00 | -0.8 | 0.00 | 0.00 |
March | 14.00 | 07-MAR-05:00 | 11.74 | 10.00 | 0.50 | 2.64 | 0.00 | 0.00 |
April | 17.00 | 01-APR-05:00 | 15.74 | 15.00 | 0.50 | 3.69 | 0.00 | 0.00 |
May | 20.40 | 01-MAY-05:00 | 20.40 | 20.40 | 2.10 | 9.33 | 28.50 | 50.50 |
June | 21.00 | 22-JUN-07:00 | 19.59 | 19.00 | 1.50 | 8.35 | 206.50 | 266.00 |
July | 28.00 | 03-JUL-05:00 | 16.06 | 8.00 | 1.00 | 12.41 | 32.50 | 30.50 |
August | 28.80 | 31-AUG-03:00 | 25.95 | 25.00 | 1.50 | 17.03 | 0.00 | 0.00 |
September | 23.00 | 25-SEP-04:00 | 22.27 | 22.00 | 2.10 | 10.88 | 0.00 | 0.00 |
October | 20.60 | 29-OCT-06:00 | 17.24 | 15.40 | 0.50 | 7.15 | 49.50 | 123.00 |
November | 16.90 | 22-NOV-06:00 | 14.44 | 12.90 | 3.10 | 3.06 | 31.00 | 106.50 |
December | 13.00 | 18-DEC-04:00 | 10.82 | 9.00 | 1.80 | -1.4 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 12.00 | 10.82 | 8.00 | 0.50 | -1.9 | 0.00 | 0.00 | |
Maximum of Months | 28.80 | 25.95 | 25.00 | 3.10 | 17.03 | 206.50 | 266.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 20.89 | 30-JAN-13:00 | 23.00 | 20.00 | 3.60 | 18.82 | 266.50 | 27.50 |
February | 23.21 | 07-FEB-15:00 | 28.00 | 21.30 | 6.20 | 18.64 | 178.50 | 219.50 |
March | 23.05 | 28-MAR-10:00 | 28.00 | 21.00 | 7.20 | 23.82 | 374.50 | 58.00 |
April | 26.40 | 30-APR-14:00 | 31.00 | 25.00 | 8.70 | 22.98 | 350.50 | 184.00 |
May | 29.11 | 29-MAY-12:00 | 33.40 | 27.90 | 7.70 | 22.13 | 421.00 | 303.50 |
June | 29.09 | 04-JUN-18:00 | 33.20 | 28.00 | 4.10 | 21.96 | 16.50 | 15.50 |
July | 30.86 | 18-JUL-20:00 | 34.00 | 30.00 | 3.60 | 26.32 | 0.00 | 0.00 |
August | 31.14 | 22-AUG-16:00 | 36.00 | 30.00 | 9.30 | 25.16 | 159.00 | 168.50 |
September | 30.39 | 09-SEP-13:00 | 36.00 | 29.00 | 5.70 | 28.11 | 339.50 | 377.00 |
October | 30.18 | 07-OCT-09:00 | 30.60 | 30.10 | 4.60 | 19.87 | 295.50 | 353.00 |
November | 26.24 | 01-NOV-13:00 | 33.00 | 24.00 | 6.20 | 20.92 | 269.00 | 349.50 |
December | 23.18 | 05-DEC-14:00 | 26.00 | 22.00 | 4.60 | 16.85 | 185.00 | 295.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 20.89 | 23.00 | 20.00 | 3.60 | 16.85 | 0.00 | 0.00 | |
Maximum of Months | 31.14 | 36.00 | 30.10 | 9.30 | 28.11 | 421.00 | 377.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 20.00 | 30-JAN-13:00 | 23.00 | 20.89 | 3.60 | 18.82 | 266.50 | 27.50 |
February | 21.30 | 07-FEB-15:00 | 28.00 | 23.21 | 6.20 | 18.64 | 178.50 | 219.50 |
March | 22.00 | 31-MAR-09:00 | 23.00 | 22.27 | 0.50 | 10.88 | 323.50 | 305.50 |
April | 25.00 | 30-APR-14:00 | 31.00 | 26.40 | 8.70 | 22.98 | 350.50 | 184.00 |
May | 27.90 | 29-MAY-12:00 | 33.40 | 29.11 | 7.70 | 22.13 | 421.00 | 303.50 |
June | 28.00 | 04-JUN-18:00 | 33.20 | 29.09 | 4.10 | 21.96 | 16.50 | 15.50 |
July | 30.00 | 19-JUL-23:19 | 34.00 | 30.86 | 0.83 | 25.33 | 0.00 | 0.00 |
August | 30.00 | 07-AUG-23:19 | 33.00 | 30.56 | 3.43 | 22.30 | 0.00 | 0.00 |
September | 29.00 | 08-SEP-07:00 | 31.00 | 29.41 | 1.50 | 24.33 | 179.00 | 151.00 |
October | 30.10 | 07-OCT-09:00 | 30.60 | 30.18 | 4.60 | 19.87 | 295.50 | 353.00 |
November | 24.00 | 01-NOV-10:00 | 32.00 | 26.10 | 3.10 | 20.05 | 300.50 | 377.00 |
December | 23.00 | 25-DEC-10:00 | 23.00 | 23.00 | 0.80 | 14.10 | 245.00 | 376.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 20.00 | 23.00 | 20.89 | 0.50 | 10.88 | 0.00 | 0.00 | |
Maximum of Months | 30.10 | 34.00 | 30.86 | 8.70 | 25.33 | 421.00 | 377.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 24.90 | 26.90 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 25.87 | 32.18 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 28.18 | 38.22 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 31.32 | 44.91 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 34.39 | 50.41 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 36.58 | 52.39 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 37.28 | 50.68 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 36.29 | 48.56 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 33.90 | 43.99 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 30.75 | 37.43 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 27.69 | 30.34 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 25.55 | 25.09 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 31.09 | 40.13 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 24.90 | 25.09 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 37.28 | 52.39 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH BOOSTER E WATER HEATER
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.770746E+10 | -0.754279E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164675940.2 | 81.21 | 0.00 | 0.00 |
February | 0.696458E+10 | -0.681598E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -148606000.8 | 81.21 | 0.00 | 0.00 |
March | 0.770584E+10 | -0.754148E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164360942.4 | 81.21 | 0.00 | 0.00 |
April | 0.746742E+10 | -0.730859E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -158821831.6 | 81.21 | 0.00 | 0.00 |
May | 0.770658E+10 | -0.754279E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -163789830.9 | 81.21 | 0.00 | 0.00 |
June | 0.745894E+10 | -0.730053E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -158409076.4 | 81.21 | 0.00 | 0.00 |
July | 0.771445E+10 | -0.755085E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -163592867.6 | 81.21 | 0.00 | 0.00 |
August | 0.770635E+10 | -0.754280E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -163543928.2 | 81.21 | 0.00 | 0.00 |
September | 0.746840E+10 | -0.730994E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -158458393.2 | 81.21 | 0.00 | 0.00 |
October | 0.770536E+10 | -0.754143E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -163927177.6 | 81.21 | 0.00 | 0.00 |
November | 0.745131E+10 | -0.729242E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -158881019.7 | 81.21 | 0.00 | 0.00 |
December | 0.771541E+10 | -0.755087E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164539198.4 | 81.21 | 0.00 | 0.00 |
Annual Sum or Average | 0.907721E+11 | -0.888405E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.193161E+10 | 81.21 | 0.00 | 0.00 |
Minimum of Months | 0.696458E+10 | -0.755087E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -164675940.2 | 81.21 | 0.00 | 0.00 |
Maximum of Months | 0.771541E+10 | -0.681598E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -148606000.8 | 81.21 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH LAUNDRY G WATER HEATER
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.971914E+11 | -0.953818E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.180962E+10 | 81.25 | 0.00 | 0.00 |
February | 0.862971E+11 | -0.846594E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.163769E+10 | 81.25 | 0.00 | 0.00 |
March | 0.916335E+11 | -0.898186E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.181481E+10 | 81.25 | 0.00 | 0.00 |
April | 0.835356E+11 | -0.817788E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.175680E+10 | 81.24 | 0.00 | 0.00 |
May | 0.811127E+11 | -0.792973E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.181544E+10 | 81.25 | 0.00 | 0.00 |
June | 0.749086E+11 | -0.731524E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.175620E+10 | 81.24 | 0.00 | 0.00 |
July | 0.762140E+11 | -0.744003E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.181370E+10 | 81.26 | 0.00 | 0.00 |
August | 0.778889E+11 | -0.760802E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.180872E+10 | 81.24 | 0.00 | 0.00 |
September | 0.792885E+11 | -0.775403E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.174821E+10 | 81.25 | 0.00 | 0.00 |
October | 0.872624E+11 | -0.854608E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.180155E+10 | 81.24 | 0.00 | 0.00 |
November | 0.894630E+11 | -0.877223E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.174070E+10 | 81.25 | 0.00 | 0.00 |
December | 0.960828E+11 | -0.942786E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.180419E+10 | 81.25 | 0.00 | 0.00 |
Annual Sum or Average | 0.102088E+13 | -0.999571E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.213076E+11 | 81.25 | 0.00 | 0.00 |
Minimum of Months | 0.749086E+11 | -0.953818E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.181544E+10 | 81.24 | 0.00 | 0.00 |
Maximum of Months | 0.971914E+11 | -0.731524E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.163769E+10 | 81.26 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.513664E+11 | -0.497885E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.157789E+10 | 58.98 | 0.00 | 0.00 |
February | 0.451226E+11 | -0.436929E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.142967E+10 | 58.98 | 0.00 | 0.00 |
March | 0.466135E+11 | -0.450283E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.158519E+10 | 58.98 | 0.00 | 0.00 |
April | 0.406454E+11 | -0.391106E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.153487E+10 | 58.97 | 0.00 | 0.00 |
May | 0.375079E+11 | -0.359220E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.158586E+10 | 58.97 | 0.00 | 0.00 |
June | 0.332092E+11 | -0.316752E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.153395E+10 | 58.97 | 0.00 | 0.00 |
July | 0.332561E+11 | -0.316731E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.158297E+10 | 58.97 | 0.00 | 0.00 |
August | 0.347332E+11 | -0.331566E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.157661E+10 | 58.97 | 0.00 | 0.00 |
September | 0.369754E+11 | -0.354526E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.152279E+10 | 58.97 | 0.00 | 0.00 |
October | 0.427900E+11 | -0.412231E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.156689E+10 | 58.97 | 0.00 | 0.00 |
November | 0.457381E+11 | -0.442256E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.151251E+10 | 58.98 | 0.00 | 0.00 |
December | 0.504034E+11 | -0.488328E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.157058E+10 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.498361E+12 | -0.479781E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.185798E+11 | 58.97 | 0.00 | 0.00 |
Minimum of Months | 0.332092E+11 | -0.497885E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.158586E+10 | 58.97 | 0.00 | 0.00 |
Maximum of Months | 0.513664E+11 | -0.316731E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.142967E+10 | 58.98 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 325.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 308.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 357.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 375.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 405.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 403.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 405.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 395.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 358.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 351.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 318.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 319.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4323.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 308.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 405.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 1555886.44 | 1231.77 | 06-JAN-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1555886.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1555886.44 | 1231.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BASEMENT VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.127488E+10 | 6138.56 | 17-JAN-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.375410E+10 | 9047.78 | 06-FEB-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.865606E+10 | 10314.62 | 27-MAR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.111529E+11 | 10390.15 | 28-APR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.110413E+11 | 10396.58 | 21-MAY-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.864665E+10 | 10417.46 | 10-JUN-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.633182E+10 | 10467.16 | 30-JUL-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.272080E+10 | 10424.05 | 01-AUG-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.107130E+10 | 7099.97 | 05-SEP-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 98695006.02 | 5558.22 | 02-OCT-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 480562.90 | 800.94 | 06-NOV-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 58482452.36 | 4442.31 | 26-DEC-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.548074E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 480562.90 | 800.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.111529E+11 | 10467.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.298381E+10 | 2108.22 | 09-JAN-08:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.240258E+10 | 2108.22 | 21-FEB-07:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.227111E+10 | 1981.24 | 07-MAR-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.165052E+10 | 1794.44 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.711353E+09 | 1259.25 | 02-MAY-07:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.384890E+09 | 965.33 | 30-JUN-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.107118E+09 | 744.65 | 10-JUL-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 49381978.04 | 690.57 | 15-AUG-07:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.258424E+09 | 957.69 | 25-SEP-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.602750E+09 | 1210.66 | 21-OCT-06:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.129797E+10 | 1685.80 | 26-NOV-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.252410E+10 | 2077.77 | 30-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.152440E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 49381978.04 | 690.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.298381E+10 | 2108.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_2_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.106306E+10 | 1136.50 | 20-JAN-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.832409E+09 | 1154.95 | 21-FEB-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.739297E+09 | 1154.81 | 06-MAR-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.533270E+09 | 1052.23 | 10-APR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.318937E+09 | 970.33 | 01-MAY-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.242140E+09 | 884.54 | 08-JUN-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.184089E+09 | 830.94 | 03-JUL-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.137560E+09 | 776.44 | 15-AUG-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.188104E+09 | 884.42 | 25-SEP-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.274909E+09 | 898.60 | 30-OCT-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.461078E+09 | 950.60 | 27-NOV-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.878265E+09 | 1076.68 | 22-DEC-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.585312E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.137560E+09 | 776.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.106306E+10 | 1154.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: MECH_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.226942E+10 | 1472.92 | 14-JAN-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.177671E+10 | 1473.48 | 14-FEB-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.152396E+10 | 1474.90 | 07-MAR-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.943606E+09 | 1322.92 | 01-APR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.242029E+09 | 1019.67 | 01-MAY-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 66233166.99 | 783.59 | 08-JUN-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 17992112.99 | 676.02 | 03-JUL-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 12548828.44 | 704.91 | 22-AUG-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.121760E+09 | 895.22 | 25-SEP-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.414108E+09 | 1027.29 | 30-OCT-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.100529E+10 | 1227.43 | 27-NOV-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.187142E+10 | 1451.23 | 19-DEC-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.102651E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 12548828.44 | 676.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.226942E+10 | 1474.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: STORAGE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.144625E+10 | 783.50 | 08-JAN-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.114084E+10 | 784.03 | 03-FEB-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.990686E+09 | 783.83 | 07-MAR-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.616677E+09 | 695.55 | 05-APR-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.148045E+09 | 526.67 | 02-MAY-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 30598838.03 | 402.60 | 08-JUN-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 4531504.73 | 344.08 | 01-JUL-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 3661136.63 | 274.78 | 22-AUG-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 68560295.76 | 437.44 | 25-SEP-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.268132E+09 | 530.17 | 30-OCT-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.662806E+09 | 636.21 | 27-NOV-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.120969E+10 | 782.42 | 19-DEC-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.659048E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 3661136.63 | 274.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.144625E+10 | 784.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LAUNDRY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.128687E+11 | 11972.32 | 02-JAN-04:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.115056E+11 | 11974.01 | 21-FEB-04:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.125761E+11 | 12432.86 | 27-MAR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.121150E+11 | 12523.87 | 28-APR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125823E+11 | 12528.66 | 13-MAY-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.122403E+11 | 12556.96 | 10-JUN-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.127858E+11 | 12616.88 | 30-JUL-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.127625E+11 | 12609.26 | 05-AUG-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.121944E+11 | 12536.75 | 02-SEP-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.123567E+11 | 12468.05 | 04-OCT-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.117948E+11 | 12403.49 | 04-NOV-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.126748E+11 | 11886.17 | 18-DEC-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.148457E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.115056E+11 | 11886.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.128687E+11 | 12616.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAFE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.413551E+10 | 6612.76 | 09-JAN-09:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.326325E+10 | 6205.96 | 20-FEB-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.330764E+10 | 6215.17 | 14-MAR-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.257154E+10 | 6133.48 | 05-APR-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.157327E+10 | 5128.46 | 15-MAY-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.128199E+10 | 4995.08 | 20-JUN-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.783406E+09 | 4504.06 | 03-JUL-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.504241E+09 | 3854.01 | 14-AUG-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.529105E+09 | 3350.06 | 01-SEP-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.669927E+09 | 2861.44 | 30-OCT-08:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.118893E+10 | 4755.74 | 29-NOV-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.320525E+10 | 7134.44 | 15-DEC-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.230141E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.504241E+09 | 2861.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.413551E+10 | 7134.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LOBBY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.113590E+11 | 18602.90 | 30-JAN-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.902205E+10 | 18833.16 | 21-FEB-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.910155E+10 | 18898.20 | 20-MAR-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.731326E+10 | 18634.42 | 05-APR-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.514069E+10 | 17314.52 | 01-MAY-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.408469E+10 | 16231.89 | 08-JUN-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.313910E+10 | 15461.14 | 03-JUL-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.234587E+10 | 14233.17 | 15-AUG-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.243450E+10 | 13968.70 | 25-SEP-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.281633E+10 | 13704.87 | 30-OCT-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.441418E+10 | 16263.61 | 29-NOV-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.907167E+10 | 18874.64 | 15-DEC-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.702429E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.234587E+10 | 13704.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.113590E+11 | 18898.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.435341E+10 | 5286.11 | 09-JAN-09:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.261787E+10 | 4983.61 | 21-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145162E+10 | 4596.72 | 06-MAR-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.147164E+09 | 3305.08 | 05-APR-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 79549459.36 | 2558.17 | 29-NOV-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.255244E+10 | 5415.09 | 15-DEC-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.112020E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.435341E+10 | 5415.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.639806E+10 | 4763.75 | 03-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.467454E+10 | 4351.47 | 22-FEB-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.384040E+10 | 4086.50 | 07-MAR-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.201728E+10 | 3258.67 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.239032E+09 | 1917.34 | 02-MAY-07:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 1551383.53 | 316.84 | 08-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 44742310.70 | 1212.08 | 25-SEP-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.478952E+09 | 2160.26 | 30-OCT-06:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.226494E+10 | 3258.66 | 27-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.520118E+10 | 4391.92 | 30-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.251607E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.639806E+10 | 4763.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BANQUET_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.186944E+10 | 6205.03 | 03-JAN-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.120307E+10 | 5895.02 | 17-FEB-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.890467E+09 | 5738.93 | 17-MAR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.405180E+09 | 5213.77 | 10-APR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.158533E+09 | 4615.87 | 02-MAY-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.110506E+09 | 4170.87 | 27-JUN-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 88471119.51 | 3946.61 | 07-JUL-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.104333E+09 | 4061.48 | 22-AUG-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.153521E+09 | 4487.24 | 26-SEP-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.291380E+09 | 4951.58 | 31-OCT-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.604267E+09 | 5203.17 | 27-NOV-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.141431E+10 | 5886.71 | 19-DEC-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.729348E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 88471119.51 | 3946.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.186944E+10 | 6205.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: DINING_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.135726E+10 | 5711.13 | 03-JAN-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.789041E+09 | 5447.56 | 17-FEB-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.534496E+09 | 5268.10 | 17-MAR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.193244E+09 | 4669.17 | 10-APR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.100209E+09 | 4151.38 | 02-MAY-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 83618137.81 | 3927.60 | 30-JUN-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 70333547.68 | 3707.04 | 07-JUL-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 85626854.13 | 3830.92 | 22-AUG-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.101065E+09 | 4280.35 | 25-SEP-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.153041E+09 | 4583.73 | 31-OCT-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.304481E+09 | 4660.46 | 28-NOV-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.957692E+09 | 5439.85 | 19-DEC-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.473011E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 70333547.68 | 3707.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.135726E+10 | 5711.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: KITCHEN_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.131592E+10 | 4208.90 | 01-JAN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.102175E+10 | 3918.08 | 21-FEB-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.864440E+09 | 3688.69 | 07-MAR-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.568631E+09 | 3026.86 | 05-APR-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.198412E+09 | 1972.44 | 02-MAY-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 94700950.35 | 1367.09 | 08-JUN-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 33297207.87 | 822.83 | 01-JUL-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 25467146.45 | 822.83 | 27-AUG-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.116095E+09 | 1538.20 | 25-SEP-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.299563E+09 | 2178.50 | 29-OCT-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.675693E+09 | 3113.96 | 22-NOV-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.111108E+10 | 3842.60 | 18-DEC-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.632505E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 25467146.45 | 822.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.131592E+10 | 4208.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: FLR_3_DOAS HEATING COIL
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 112657.79 | 110.12 | 06-JAN-23:37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 19471.53 | 0.57 | 17-FEB-00:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 22908.32 | 0.57 | 01-MAR-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 15816.69 | 0.57 | 17-APR-19:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 12502.15 | 0.57 | 18-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6274.98 | 0.57 | 17-JUN-22:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7144.14 | 0.57 | 04-JUL-00:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6227.77 | 0.57 | 05-AUG-21:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 12923.21 | 0.57 | 07-SEP-03:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 17091.63 | 0.57 | 23-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 20199.36 | 0.57 | 14-NOV-22:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 20363.19 | 0.57 | 10-DEC-23:37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 273580.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 6227.77 | 0.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 112657.79 | 110.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 23455620.70 | 2612.73 | 15-JAN-09:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 8798517.20 | 2340.15 | 15-FEB-19:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6378578.17 | 2346.59 | 02-MAR-09:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 3541787.71 | 2483.01 | 08-APR-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 940147.58 | 2339.10 | 02-MAY-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 201026.61 | 704.09 | 08-JUN-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 375626.42 | 1044.59 | 25-SEP-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 2992268.32 | 2309.71 | 20-OCT-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5208304.49 | 2303.43 | 17-NOV-09:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 11284893.12 | 2442.85 | 16-DEC-09:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 63176770.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 23455620.70 | 2612.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 54247754.24 | 2454.90 | 03-JAN-19:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 15455542.43 | 2367.73 | 11-FEB-09:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 7256466.84 | 2325.93 | 09-MAR-09:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 3672797.75 | 2487.24 | 08-APR-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 872909.82 | 2260.44 | 03-MAY-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 130697.15 | 652.23 | 08-JUN-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 699974.61 | 1425.48 | 25-SEP-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4046686.79 | 2360.80 | 29-OCT-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6819964.22 | 2548.43 | 12-NOV-09:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 18328976.18 | 2403.31 | 16-DEC-09:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.111532E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 54247754.24 | 2548.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.100465E+09 | 19521.96 | 22-JAN-09:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 73040799.15 | 20419.74 | 07-FEB-09:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 48729335.08 | 19643.34 | 01-MAR-09:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 31936887.86 | 19659.46 | 10-APR-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 4721711.76 | 10383.71 | 11-MAY-08:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 1627360.32 | 3350.87 | 20-JUN-08:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 2512339.61 | 4661.56 | 27-JUL-08:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 4263391.27 | 6116.23 | 25-AUG-08:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3757456.19 | 5151.73 | 08-SEP-08:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 11566923.18 | 18679.43 | 30-OCT-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 44224816.48 | 18999.61 | 16-NOV-09:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 85565742.55 | 20077.99 | 11-DEC-09:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.412411E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 1627360.32 | 3350.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.100465E+09 | 20419.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 29351584.44 | 2334.27 | 09-JAN-16:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 11155948.67 | 2266.19 | 23-FEB-19:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 7457278.32 | 2324.51 | 10-MAR-19:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 1908603.51 | 1913.81 | 17-APR-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 54927.62 | 549.28 | 30-OCT-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 2329949.80 | 2319.10 | 22-NOV-19:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 12108684.90 | 2375.28 | 17-DEC-16:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 64366977.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 29351584.44 | 2375.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 66908445.85 | 2339.44 | 03-JAN-19:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 19182964.62 | 2589.28 | 03-FEB-16:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 9866963.71 | 2446.17 | 02-MAR-09:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 2101486.30 | 1713.98 | 18-APR-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 108991.92 | 1089.92 | 30-OCT-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5584988.73 | 2520.93 | 21-NOV-19:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 23092959.94 | 2599.50 | 06-DEC-19:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.126847E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 66908445.85 | 2599.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 17863886.32 | 657.59 | 15-JAN-09:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5183093.35 | 756.58 | 04-FEB-09:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 2000113.18 | 757.58 | 22-MAR-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 904990.91 | 707.48 | 13-APR-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 123849.77 | 494.27 | 03-MAY-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 12823.32 | 98.24 | 08-JUN-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 46171.44 | 412.98 | 25-SEP-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 685110.15 | 576.00 | 29-OCT-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1046526.18 | 636.77 | 04-NOV-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5168893.50 | 659.57 | 15-DEC-16:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 33035458.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17863886.32 | 757.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 36080014.29 | 718.17 | 04-JAN-19:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 9794912.02 | 680.05 | 25-FEB-09:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 2562651.71 | 707.80 | 27-MAR-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 930633.16 | 721.57 | 13-APR-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 128503.03 | 509.24 | 03-MAY-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 2628.70 | 21.81 | 08-JUN-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 81710.67 | 501.09 | 25-SEP-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 919881.25 | 669.15 | 31-OCT-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1582172.05 | 713.39 | 06-NOV-09:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 11192789.19 | 697.95 | 08-DEC-19:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 63275896.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 36080014.29 | 721.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 7285561.18 | 2889.70 | 04-JAN-09:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5379461.94 | 3075.24 | 07-FEB-09:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6889228.29 | 3586.05 | 01-MAR-09:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6167650.86 | 3648.75 | 17-APR-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2061677.86 | 3747.33 | 02-MAY-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 619510.12 | 1606.58 | 08-JUN-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 389263.75 | 799.61 | 22-SEP-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 990383.07 | 3111.20 | 20-OCT-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1934760.41 | 3065.01 | 05-NOV-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7637869.22 | 2993.84 | 12-DEC-09:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 39355366.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7637869.22 | 3747.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.456129E+12 | 0.403828E+12 | 439356.89 | 30-JAN-11:40 | 267721.79 | 0.89 |
February | 0.00 | 0.00 | 0.544112E+12 | 0.437615E+12 | 545545.82 | 03-FEB-20:20 | 246738.88 | 0.97 |
March | 0.00 | 0.00 | 0.712096E+12 | 0.596117E+12 | 547382.19 | 28-MAR-10:50 | 317425.94 | 0.95 |
April | 0.00 | 0.00 | 0.944154E+12 | 0.703969E+12 | 704742.05 | 30-APR-17:12 | 347380.41 | 0.95 |
May | 0.00 | 0.00 | 0.125982E+13 | 0.875413E+12 | 862795.46 | 30-MAY-18:00 | 408556.31 | 0.98 |
June | 0.00 | 0.00 | 0.157549E+13 | 0.897679E+12 | 919342.79 | 04-JUN-19:00 | 382914.64 | 0.99 |
July | 0.00 | 0.00 | 0.187551E+13 | 0.991104E+12 | 1035475.69 | 18-JUL-21:00 | 390927.38 | 1.00 |
August | 0.00 | 0.00 | 0.194537E+13 | 0.100132E+13 | 1045928.61 | 22-AUG-17:00 | 406974.31 | 1.00 |
September | 0.00 | 0.00 | 0.169244E+13 | 0.888118E+12 | 990850.25 | 08-SEP-17:13 | 395174.22 | 1.00 |
October | 0.00 | 0.00 | 0.135545E+13 | 0.828222E+12 | 963009.21 | 07-OCT-10:35 | 380851.36 | 0.98 |
November | 0.00 | 0.00 | 0.957965E+12 | 0.678163E+12 | 735829.81 | 01-NOV-10:35 | 359073.03 | 0.99 |
December | 0.00 | 0.00 | 0.679451E+12 | 0.506776E+12 | 560030.17 | 25-DEC-10:30 | 193115.51 | 0.99 |
Annual Sum or Average | 0.00 | 0.00 | 0.139980E+14 | 0.880832E+13 | 0.97 | |||
Minimum of Months | 0.00 | 0.00 | 0.456129E+12 | 0.403828E+12 | 439356.89 | 193115.51 | 0.89 | |
Maximum of Months | 0.00 | 0.00 | 0.194537E+13 | 0.100132E+13 | 1045928.61 | 408556.31 | 1.00 |
Report: CoilReportMonthly
For: FLR_3_DOAS COOLING COIL
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.514319E+11 | 0.423178E+11 | 64721.81 | 30-JAN-14:10 | 27783.26 | 0.83 |
February | 0.00 | 0.00 | 0.606310E+11 | 0.461374E+11 | 60017.86 | 09-FEB-15:00 | 28164.25 | 0.95 |
March | 0.00 | 0.00 | 0.774445E+11 | 0.630862E+11 | 63399.61 | 31-MAR-09:40 | 23979.69 | 0.95 |
April | 0.00 | 0.00 | 0.988599E+11 | 0.732263E+11 | 75588.96 | 30-APR-06:00 | 25735.96 | 0.97 |
May | 0.00 | 0.00 | 0.120480E+12 | 0.862834E+11 | 77866.99 | 29-MAY-13:00 | 36026.05 | 0.99 |
June | 0.00 | 0.00 | 0.145398E+12 | 0.868573E+11 | 79070.25 | 08-JUN-13:00 | 36143.55 | 1.00 |
July | 0.00 | 0.00 | 0.169008E+12 | 0.937825E+11 | 85465.30 | 20-JUL-12:20 | 37583.01 | 1.00 |
August | 0.00 | 0.00 | 0.173955E+12 | 0.942919E+11 | 85506.38 | 08-AUG-13:00 | 36478.55 | 1.00 |
September | 0.00 | 0.00 | 0.155056E+12 | 0.862151E+11 | 82393.43 | 09-SEP-14:00 | 37038.12 | 1.00 |
October | 0.00 | 0.00 | 0.130214E+12 | 0.832961E+11 | 81379.07 | 07-OCT-10:10 | 32838.48 | 0.98 |
November | 0.00 | 0.00 | 0.101203E+12 | 0.712985E+11 | 65315.69 | 01-NOV-14:00 | 35438.41 | 1.00 |
December | 0.00 | 0.00 | 0.743724E+11 | 0.537381E+11 | 67924.64 | 25-DEC-10:40 | 23843.03 | 0.98 |
Annual Sum or Average | 0.00 | 0.00 | 0.135805E+13 | 0.880531E+12 | 0.97 | |||
Minimum of Months | 0.00 | 0.00 | 0.514319E+11 | 0.423178E+11 | 60017.86 | 23843.03 | 0.83 | |
Maximum of Months | 0.00 | 0.00 | 0.173955E+12 | 0.942919E+11 | 85506.38 | 37583.01 | 1.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.391671E+10 | 0.161334E+10 | 20740.14 | 30-JAN-16:01 | 14923.57 | 0.78 |
February | 0.00 | 0.00 | 0.496328E+10 | 0.218693E+10 | 20249.26 | 07-FEB-09:02 | 14861.25 | 0.84 |
March | 0.00 | 0.00 | 0.749361E+10 | 0.396979E+10 | 20934.63 | 24-MAR-08:62 | 13608.47 | 0.88 |
April | 0.00 | 0.00 | 0.102041E+11 | 0.583604E+10 | 21670.13 | 18-APR-08:62 | 14137.69 | 0.92 |
May | 0.00 | 0.00 | 0.154795E+11 | 0.998717E+10 | 22475.42 | 01-MAY-08:62 | 13840.06 | 0.97 |
June | 0.00 | 0.00 | 0.173557E+11 | 0.112310E+11 | 21120.28 | 25-JUN-08:62 | 14964.23 | 0.97 |
July | 0.00 | 0.00 | 0.200824E+11 | 0.132848E+11 | 21011.03 | 27-JUL-08:62 | 15026.45 | 0.98 |
August | 0.00 | 0.00 | 0.209158E+11 | 0.139346E+11 | 21228.62 | 27-AUG-08:62 | 14904.45 | 0.98 |
September | 0.00 | 0.00 | 0.177252E+11 | 0.112725E+11 | 21501.91 | 11-SEP-08:62 | 14751.29 | 0.97 |
October | 0.00 | 0.00 | 0.147988E+11 | 0.900977E+10 | 21570.95 | 31-OCT-08:61 | 14713.82 | 0.95 |
November | 0.00 | 0.00 | 0.993367E+10 | 0.530631E+10 | 21999.56 | 02-NOV-08:61 | 14484.56 | 0.93 |
December | 0.00 | 0.00 | 0.558190E+10 | 0.237010E+10 | 20752.72 | 06-DEC-09:02 | 13999.68 | 0.85 |
Annual Sum or Average | 0.00 | 0.00 | 0.148451E+12 | 0.900024E+11 | 0.92 | |||
Minimum of Months | 0.00 | 0.00 | 0.391671E+10 | 0.161334E+10 | 20249.26 | 13608.47 | 0.78 | |
Maximum of Months | 0.00 | 0.00 | 0.209158E+11 | 0.139346E+11 | 22475.42 | 15026.45 | 0.98 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.259738E+10 | 0.963736E+09 | 20245.71 | 30-JAN-16:01 | 14433.57 | 0.61 |
February | 0.00 | 0.00 | 0.380456E+10 | 0.155190E+10 | 19908.71 | 09-FEB-09:02 | 14183.15 | 0.77 |
March | 0.00 | 0.00 | 0.658092E+10 | 0.339873E+10 | 20291.96 | 24-MAR-08:62 | 13470.60 | 0.85 |
April | 0.00 | 0.00 | 0.974956E+10 | 0.553866E+10 | 21277.52 | 18-APR-08:62 | 13892.65 | 0.92 |
May | 0.00 | 0.00 | 0.154647E+11 | 0.100564E+11 | 21508.90 | 01-MAY-08:62 | 13994.07 | 0.97 |
June | 0.00 | 0.00 | 0.175626E+11 | 0.115139E+11 | 20613.48 | 25-JUN-08:62 | 14797.92 | 0.97 |
July | 0.00 | 0.00 | 0.201443E+11 | 0.133768E+11 | 20585.46 | 27-JUL-08:62 | 14813.85 | 0.98 |
August | 0.00 | 0.00 | 0.206208E+11 | 0.137083E+11 | 20898.43 | 27-AUG-08:62 | 14638.40 | 0.98 |
September | 0.00 | 0.00 | 0.168432E+11 | 0.104643E+11 | 21204.83 | 11-SEP-08:62 | 14466.49 | 0.97 |
October | 0.00 | 0.00 | 0.132616E+11 | 0.767590E+10 | 21107.05 | 08-OCT-08:62 | 14472.95 | 0.94 |
November | 0.00 | 0.00 | 0.819193E+10 | 0.404177E+10 | 21579.22 | 02-NOV-08:61 | 14047.17 | 0.91 |
December | 0.00 | 0.00 | 0.405389E+10 | 0.156189E+10 | 20420.85 | 24-DEC-16:02 | 14922.45 | 0.76 |
Annual Sum or Average | 0.00 | 0.00 | 0.138875E+12 | 0.838523E+11 | 0.89 | |||
Minimum of Months | 0.00 | 0.00 | 0.259738E+10 | 0.963736E+09 | 19908.71 | 13470.60 | 0.61 | |
Maximum of Months | 0.00 | 0.00 | 0.206208E+11 | 0.137083E+11 | 21579.22 | 14922.45 | 0.98 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.322916E+11 | 0.147626E+11 | 35511.47 | 28-JAN-13:40 | 29528.94 | 0.75 |
February | 0.00 | 0.00 | 0.328584E+11 | 0.150550E+11 | 44960.13 | 05-FEB-13:30 | 36453.69 | 0.81 |
March | 0.00 | 0.00 | 0.406195E+11 | 0.203545E+11 | 37238.50 | 27-MAR-13:30 | 30826.80 | 0.84 |
April | 0.00 | 0.00 | 0.493403E+11 | 0.255472E+11 | 40745.11 | 29-APR-20:20 | 26327.29 | 0.94 |
May | 0.00 | 0.00 | 0.709784E+11 | 0.402412E+11 | 48059.42 | 31-MAY-19:10 | 41268.79 | 1.00 |
June | 0.00 | 0.00 | 0.781482E+11 | 0.440321E+11 | 50293.68 | 09-JUN-20:20 | 40656.67 | 1.00 |
July | 0.00 | 0.00 | 0.947781E+11 | 0.577032E+11 | 54258.56 | 15-JUL-19:10 | 47159.83 | 1.00 |
August | 0.00 | 0.00 | 0.101881E+12 | 0.647264E+11 | 60665.14 | 10-AUG-20:50 | 46210.18 | 1.00 |
September | 0.00 | 0.00 | 0.922016E+11 | 0.584454E+11 | 53077.19 | 04-SEP-20:10 | 44561.94 | 1.00 |
October | 0.00 | 0.00 | 0.861298E+11 | 0.555559E+11 | 53439.01 | 07-OCT-13:00 | 41573.85 | 0.99 |
November | 0.00 | 0.00 | 0.654870E+11 | 0.386002E+11 | 48993.17 | 05-NOV-13:30 | 44005.00 | 0.99 |
December | 0.00 | 0.00 | 0.419510E+11 | 0.201804E+11 | 45452.40 | 03-DEC-12:40 | 36506.17 | 0.85 |
Annual Sum or Average | 0.00 | 0.00 | 0.786665E+12 | 0.455204E+12 | 0.93 | |||
Minimum of Months | 0.00 | 0.00 | 0.322916E+11 | 0.147626E+11 | 35511.47 | 26327.29 | 0.75 | |
Maximum of Months | 0.00 | 0.00 | 0.101881E+12 | 0.647264E+11 | 60665.14 | 47159.83 | 1.00 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.417280E+11 | 0.204202E+11 | 133946.83 | 29-JAN-09:02 | 101330.49 | 0.70 |
February | 0.00 | 0.00 | 0.471529E+11 | 0.247328E+11 | 133489.86 | 09-FEB-09:02 | 97483.11 | 0.71 |
March | 0.00 | 0.00 | 0.627832E+11 | 0.380375E+11 | 134884.75 | 24-MAR-08:62 | 92711.40 | 0.73 |
April | 0.00 | 0.00 | 0.792902E+11 | 0.507480E+11 | 143603.27 | 18-APR-08:62 | 93697.16 | 0.82 |
May | 0.00 | 0.00 | 0.110093E+12 | 0.773327E+11 | 139446.85 | 01-MAY-08:62 | 95534.84 | 0.92 |
June | 0.00 | 0.00 | 0.120299E+12 | 0.839077E+11 | 130497.84 | 08-JUN-15:02 | 106137.89 | 0.93 |
July | 0.00 | 0.00 | 0.134847E+12 | 0.931978E+11 | 132089.44 | 27-JUL-08:62 | 105290.69 | 0.94 |
August | 0.00 | 0.00 | 0.135190E+12 | 0.925036E+11 | 133738.78 | 08-AUG-08:62 | 104398.12 | 0.94 |
September | 0.00 | 0.00 | 0.114230E+12 | 0.771327E+11 | 132590.11 | 11-SEP-08:62 | 105030.05 | 0.92 |
October | 0.00 | 0.00 | 0.970685E+11 | 0.632065E+11 | 132850.69 | 28-OCT-08:61 | 104850.28 | 0.87 |
November | 0.00 | 0.00 | 0.708765E+11 | 0.425787E+11 | 143604.31 | 02-NOV-08:61 | 94890.44 | 0.77 |
December | 0.00 | 0.00 | 0.518664E+11 | 0.272382E+11 | 136279.25 | 26-DEC-19:01 | 99437.75 | 0.71 |
Annual Sum or Average | 0.00 | 0.00 | 0.106542E+13 | 0.691036E+12 | 0.83 | |||
Minimum of Months | 0.00 | 0.00 | 0.417280E+11 | 0.204202E+11 | 130497.84 | 92711.40 | 0.70 | |
Maximum of Months | 0.00 | 0.00 | 0.135190E+12 | 0.931978E+11 | 143604.31 | 106137.89 | 0.94 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.396817E+10 | 0.173058E+10 | 18740.07 | 30-JAN-16:01 | 13466.99 | 0.77 |
February | 0.00 | 0.00 | 0.492547E+10 | 0.227451E+10 | 18511.07 | 08-FEB-09:02 | 13889.29 | 0.86 |
March | 0.00 | 0.00 | 0.723838E+10 | 0.392962E+10 | 19254.12 | 24-MAR-08:62 | 12816.61 | 0.89 |
April | 0.00 | 0.00 | 0.103473E+11 | 0.617088E+10 | 19603.15 | 18-APR-08:62 | 12819.78 | 0.94 |
May | 0.00 | 0.00 | 0.157038E+11 | 0.103613E+11 | 20018.57 | 01-MAY-08:62 | 12946.90 | 0.98 |
June | 0.00 | 0.00 | 0.173525E+11 | 0.115036E+11 | 18595.52 | 08-JUN-08:62 | 13815.21 | 0.98 |
July | 0.00 | 0.00 | 0.201581E+11 | 0.138368E+11 | 18484.55 | 20-JUL-08:62 | 13874.80 | 0.98 |
August | 0.00 | 0.00 | 0.209801E+11 | 0.145162E+11 | 18627.71 | 08-AUG-08:62 | 13797.09 | 0.98 |
September | 0.00 | 0.00 | 0.177609E+11 | 0.115985E+11 | 18720.04 | 11-SEP-08:62 | 13747.71 | 0.98 |
October | 0.00 | 0.00 | 0.149151E+11 | 0.913909E+10 | 19095.98 | 31-OCT-08:61 | 13540.15 | 0.97 |
November | 0.00 | 0.00 | 0.995443E+10 | 0.551267E+10 | 19482.85 | 02-NOV-08:61 | 13335.99 | 0.95 |
December | 0.00 | 0.00 | 0.549937E+10 | 0.246939E+10 | 18903.76 | 06-DEC-09:02 | 13197.63 | 0.86 |
Annual Sum or Average | 0.00 | 0.00 | 0.148804E+12 | 0.930431E+11 | 0.93 | |||
Minimum of Months | 0.00 | 0.00 | 0.396817E+10 | 0.173058E+10 | 18484.55 | 12816.61 | 0.77 | |
Maximum of Months | 0.00 | 0.00 | 0.209801E+11 | 0.145162E+11 | 20018.57 | 13889.29 | 0.98 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.266407E+10 | 0.101341E+10 | 18277.18 | 30-JAN-16:01 | 13014.80 | 0.59 |
February | 0.00 | 0.00 | 0.375615E+10 | 0.159935E+10 | 18023.17 | 09-FEB-09:02 | 12890.05 | 0.74 |
March | 0.00 | 0.00 | 0.630254E+10 | 0.330636E+10 | 18659.56 | 24-MAR-08:62 | 12680.94 | 0.87 |
April | 0.00 | 0.00 | 0.988631E+10 | 0.585449E+10 | 19231.03 | 18-APR-08:62 | 12587.86 | 0.93 |
May | 0.00 | 0.00 | 0.156873E+11 | 0.104500E+11 | 19153.51 | 01-MAY-08:62 | 13009.56 | 0.98 |
June | 0.00 | 0.00 | 0.175638E+11 | 0.118489E+11 | 18217.55 | 08-JUN-08:62 | 13599.10 | 0.98 |
July | 0.00 | 0.00 | 0.202282E+11 | 0.139638E+11 | 18213.53 | 20-JUL-08:62 | 13599.77 | 0.98 |
August | 0.00 | 0.00 | 0.206836E+11 | 0.142182E+11 | 18269.22 | 08-AUG-08:62 | 13569.71 | 0.98 |
September | 0.00 | 0.00 | 0.168746E+11 | 0.107121E+11 | 18466.38 | 11-SEP-08:62 | 13462.06 | 0.98 |
October | 0.00 | 0.00 | 0.133841E+11 | 0.789008E+10 | 18839.53 | 31-OCT-08:61 | 13255.62 | 0.96 |
November | 0.00 | 0.00 | 0.821083E+10 | 0.433411E+10 | 19333.30 | 02-NOV-08:61 | 12990.76 | 0.93 |
December | 0.00 | 0.00 | 0.397430E+10 | 0.159775E+10 | 19339.76 | 05-DEC-16:02 | 12996.52 | 0.73 |
Annual Sum or Average | 0.00 | 0.00 | 0.139216E+12 | 0.867885E+11 | 0.89 | |||
Minimum of Months | 0.00 | 0.00 | 0.266407E+10 | 0.101341E+10 | 18023.17 | 12587.86 | 0.59 | |
Maximum of Months | 0.00 | 0.00 | 0.206836E+11 | 0.142182E+11 | 19339.76 | 13599.77 | 0.98 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.105681E+10 | 0.446556E+09 | 5752.55 | 29-JAN-09:02 | 4014.13 | 0.72 |
February | 0.00 | 0.00 | 0.138244E+10 | 0.632076E+09 | 5683.53 | 07-FEB-09:02 | 3974.37 | 0.83 |
March | 0.00 | 0.00 | 0.212847E+10 | 0.115065E+10 | 5815.94 | 24-MAR-08:62 | 3541.38 | 0.90 |
April | 0.00 | 0.00 | 0.293432E+10 | 0.173059E+10 | 6101.06 | 18-APR-08:62 | 3780.61 | 0.93 |
May | 0.00 | 0.00 | 0.442350E+10 | 0.294774E+10 | 6299.41 | 01-MAY-08:62 | 3680.20 | 0.97 |
June | 0.00 | 0.00 | 0.492305E+10 | 0.327790E+10 | 5793.90 | 25-JUN-08:62 | 4060.95 | 0.98 |
July | 0.00 | 0.00 | 0.569392E+10 | 0.387067E+10 | 5712.73 | 27-JUL-08:62 | 4106.89 | 0.98 |
August | 0.00 | 0.00 | 0.588733E+10 | 0.403277E+10 | 5796.43 | 27-AUG-08:62 | 4059.85 | 0.98 |
September | 0.00 | 0.00 | 0.496770E+10 | 0.324625E+10 | 5863.24 | 11-SEP-08:62 | 4022.33 | 0.97 |
October | 0.00 | 0.00 | 0.413974E+10 | 0.259445E+10 | 5991.24 | 31-OCT-08:61 | 3949.87 | 0.96 |
November | 0.00 | 0.00 | 0.276883E+10 | 0.151111E+10 | 6141.22 | 02-NOV-08:61 | 3867.85 | 0.94 |
December | 0.00 | 0.00 | 0.153552E+10 | 0.672884E+09 | 5816.40 | 06-DEC-09:02 | 3712.81 | 0.84 |
Annual Sum or Average | 0.00 | 0.00 | 0.418416E+11 | 0.261137E+11 | 0.92 | |||
Minimum of Months | 0.00 | 0.00 | 0.105681E+10 | 0.446556E+09 | 5683.53 | 3541.38 | 0.72 | |
Maximum of Months | 0.00 | 0.00 | 0.588733E+10 | 0.403277E+10 | 6299.41 | 4106.89 | 0.98 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.701204E+09 | 0.269791E+09 | 5599.02 | 30-JAN-16:01 | 4062.50 | 0.57 |
February | 0.00 | 0.00 | 0.107265E+10 | 0.455533E+09 | 5586.55 | 09-FEB-09:02 | 3807.34 | 0.75 |
March | 0.00 | 0.00 | 0.188345E+10 | 0.990554E+09 | 5612.68 | 29-MAR-08:62 | 3719.95 | 0.87 |
April | 0.00 | 0.00 | 0.281534E+10 | 0.164267E+10 | 5994.04 | 18-APR-08:62 | 3718.32 | 0.93 |
May | 0.00 | 0.00 | 0.441902E+10 | 0.296115E+10 | 6011.90 | 01-MAY-08:62 | 3746.56 | 0.97 |
June | 0.00 | 0.00 | 0.497652E+10 | 0.334389E+10 | 5656.12 | 25-JUN-08:62 | 4020.12 | 0.98 |
July | 0.00 | 0.00 | 0.571217E+10 | 0.390776E+10 | 5600.52 | 27-JUL-08:62 | 4051.42 | 0.98 |
August | 0.00 | 0.00 | 0.581125E+10 | 0.397350E+10 | 5709.35 | 27-AUG-08:62 | 3990.28 | 0.98 |
September | 0.00 | 0.00 | 0.474180E+10 | 0.303180E+10 | 5791.88 | 11-SEP-08:62 | 3943.84 | 0.97 |
October | 0.00 | 0.00 | 0.373963E+10 | 0.221686E+10 | 5857.64 | 31-OCT-08:61 | 3894.58 | 0.95 |
November | 0.00 | 0.00 | 0.230833E+10 | 0.115948E+10 | 6034.63 | 02-NOV-08:61 | 3760.83 | 0.92 |
December | 0.00 | 0.00 | 0.112405E+10 | 0.447234E+09 | 5630.47 | 06-DEC-09:02 | 3591.83 | 0.75 |
Annual Sum or Average | 0.00 | 0.00 | 0.393054E+11 | 0.244002E+11 | 0.89 | |||
Minimum of Months | 0.00 | 0.00 | 0.701204E+09 | 0.269791E+09 | 5586.55 | 3591.83 | 0.57 | |
Maximum of Months | 0.00 | 0.00 | 0.581125E+10 | 0.397350E+10 | 6034.63 | 4062.50 | 0.98 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.994179E+10 | 0.523006E+10 | 27555.22 | 29-JAN-09:02 | 19721.12 | 0.89 |
February | 0.00 | 0.00 | 0.105100E+11 | 0.564728E+10 | 27190.38 | 08-FEB-09:02 | 19706.52 | 0.90 |
March | 0.00 | 0.00 | 0.129080E+11 | 0.752163E+10 | 27918.26 | 24-MAR-08:62 | 17474.99 | 0.90 |
April | 0.00 | 0.00 | 0.154017E+11 | 0.926810E+10 | 29479.01 | 18-APR-08:62 | 18120.79 | 0.93 |
May | 0.00 | 0.00 | 0.213393E+11 | 0.139917E+11 | 30478.79 | 01-MAY-08:62 | 17297.05 | 0.96 |
June | 0.00 | 0.00 | 0.232099E+11 | 0.152294E+11 | 26780.06 | 25-JUN-08:62 | 20159.11 | 0.97 |
July | 0.00 | 0.00 | 0.273252E+11 | 0.186918E+11 | 26890.57 | 27-JUL-08:62 | 20099.45 | 0.98 |
August | 0.00 | 0.00 | 0.287729E+11 | 0.200384E+11 | 27050.58 | 08-AUG-08:62 | 20009.97 | 0.98 |
September | 0.00 | 0.00 | 0.258049E+11 | 0.176485E+11 | 27184.96 | 11-SEP-08:62 | 19938.48 | 0.97 |
October | 0.00 | 0.00 | 0.238012E+11 | 0.161920E+11 | 27738.90 | 31-OCT-08:61 | 19633.36 | 0.96 |
November | 0.00 | 0.00 | 0.181878E+11 | 0.113101E+11 | 29497.27 | 02-NOV-08:61 | 18660.14 | 0.96 |
December | 0.00 | 0.00 | 0.125767E+11 | 0.692435E+10 | 27913.95 | 06-DEC-09:02 | 18727.15 | 0.91 |
Annual Sum or Average | 0.00 | 0.00 | 0.229779E+12 | 0.147693E+12 | 0.94 | |||
Minimum of Months | 0.00 | 0.00 | 0.994179E+10 | 0.523006E+10 | 26780.06 | 17297.05 | 0.89 | |
Maximum of Months | 0.00 | 0.00 | 0.287729E+11 | 0.200384E+11 | 30478.79 | 20159.11 | 0.98 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 19646.24 | 67612.81 | 04-JAN-09:05 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 18110.02 | 71788.38 | 21-FEB-11:40 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 17353.89 | 73263.70 | 20-MAR-10:40 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15417.06 | 70630.85 | 05-APR-10:40 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 12020.69 | 62623.62 | 01-MAY-10:40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 10434.28 | 60318.94 | 08-JUN-10:35 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 8718.80 | 56173.42 | 03-JUL-10:35 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 6944.20 | 53151.36 | 01-AUG-10:35 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 6613.22 | 48667.75 | 25-SEP-10:35 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 6940.67 | 46899.65 | 30-OCT-10:35 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9499.51 | 54197.76 | 29-NOV-11:40 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 15895.06 | 60713.87 | 21-DEC-11:40 |
Annual Sum or Average | 0.00 | 12271.53 | ||||
Minimum of Months | 0.00 | 0.00 | 6613.22 | 46899.65 | ||
Maximum of Months | 0.00 | 0.00 | 19646.24 | 73263.70 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 237167.47 | 733651.35 | 09-JAN-19:02 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 306975.02 | 809469.42 | 07-FEB-16:03 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 361943.43 | 831921.19 | 28-MAR-18:03 | 0.00 | 0.00 | 01-MAR-00:03 |
April | 488373.96 | 1025479.41 | 30-APR-18:03 | 0.00 | 0.00 | 01-APR-00:10 |
May | 630595.86 | 1156701.78 | 30-MAY-18:03 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 793414.14 | 1267567.19 | 26-JUN-18:03 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 906857.74 | 1360022.62 | 19-JUL-15:03 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 939199.89 | 1356762.51 | 11-AUG-18:03 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 846052.32 | 1359506.95 | 10-SEP-18:03 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 669067.22 | 1244079.72 | 07-OCT-18:03 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 496846.31 | 1026399.61 | 01-NOV-15:03 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 340913.26 | 824106.43 | 05-DEC-16:03 | 0.00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 586284.91 | 0.00 | ||||
Minimum of Months | 237167.47 | 733651.35 | 0.00 | 0.00 | ||
Maximum of Months | 939199.89 | 1360022.62 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 20173.52 | 40496.02 | 13-JAN-07:20 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 19646.95 | 40041.41 | 01-FEB-07:10 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 18401.38 | 38142.58 | 01-MAR-08:00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 16683.57 | 34618.30 | 03-APR-06:50 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 15012.05 | 31228.90 | 01-MAY-06:40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13823.97 | 28089.02 | 01-JUN-07:00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 13432.43 | 26587.31 | 31-JUL-06:30 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 13983.69 | 28568.10 | 31-AUG-06:40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 15277.46 | 31675.70 | 29-SEP-06:20 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16984.95 | 35508.44 | 31-OCT-07:00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 18650.75 | 38583.71 | 30-NOV-07:20 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 19817.25 | 40234.70 | 29-DEC-08:00 |
Annual Sum or Average | 0.00 | 16808.63 | ||||
Minimum of Months | 0.00 | 0.00 | 13432.43 | 26587.31 | ||
Maximum of Months | 0.00 | 0.00 | 20173.52 | 40496.02 |
Report: FanReportMonthly
For: FLR_3_DOAS FAN
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.587890E+10 | 0.87 | 2194.93 | 01-JAN-00:05 | 0.87 |
February | 0.530997E+10 | 0.87 | 2194.93 | 01-FEB-00:03 | 0.87 |
March | 0.587890E+10 | 0.87 | 2194.93 | 01-MAR-00:03 | 0.87 |
April | 0.568926E+10 | 0.87 | 2194.93 | 01-APR-00:10 | 0.87 |
May | 0.587890E+10 | 0.87 | 2194.93 | 01-MAY-00:10 | 0.87 |
June | 0.568926E+10 | 0.87 | 2194.93 | 01-JUN-00:10 | 0.87 |
July | 0.587890E+10 | 0.87 | 2194.93 | 01-JUL-00:10 | 0.87 |
August | 0.587890E+10 | 0.87 | 2194.93 | 01-AUG-00:10 | 0.87 |
September | 0.568926E+10 | 0.87 | 2194.93 | 01-SEP-00:10 | 0.87 |
October | 0.587890E+10 | 0.87 | 2194.93 | 01-OCT-00:10 | 0.87 |
November | 0.568926E+10 | 0.87 | 2194.93 | 01-NOV-00:10 | 0.87 |
December | 0.587890E+10 | 0.87 | 2194.93 | 01-DEC-00:03 | 0.87 |
Annual Sum or Average | 0.692193E+11 | 0.87 | |||
Minimum of Months | 0.530997E+10 | 0.87 | 2194.93 | 0.87 | |
Maximum of Months | 0.587890E+10 | 0.87 | 2194.93 | 0.87 |
Report: FanReportMonthly
For: VAV WITH REHEAT FAN
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.140811E+12 | 1.82 | 52572.86 | 01-JAN-00:05 | 1.82 |
February | 0.127184E+12 | 1.82 | 52572.86 | 01-FEB-00:03 | 1.82 |
March | 0.140811E+12 | 1.82 | 52572.86 | 01-MAR-00:03 | 1.82 |
April | 0.136269E+12 | 1.82 | 52572.86 | 01-APR-00:10 | 1.82 |
May | 0.140811E+12 | 1.82 | 52572.86 | 01-MAY-00:10 | 1.82 |
June | 0.136269E+12 | 1.82 | 52572.86 | 01-JUN-00:10 | 1.82 |
July | 0.140810E+12 | 1.82 | 52572.86 | 01-JUL-00:10 | 1.82 |
August | 0.140810E+12 | 1.82 | 52572.86 | 01-AUG-00:10 | 1.82 |
September | 0.136269E+12 | 1.82 | 52572.86 | 01-SEP-00:10 | 1.82 |
October | 0.140811E+12 | 1.82 | 52572.86 | 01-OCT-00:10 | 1.82 |
November | 0.136269E+12 | 1.82 | 52572.86 | 01-NOV-00:10 | 1.82 |
December | 0.140811E+12 | 1.82 | 52572.86 | 01-DEC-00:03 | 1.82 |
Annual Sum or Average | 0.165794E+13 | 1.82 | |||
Minimum of Months | 0.127184E+12 | 1.82 | 52572.86 | 1.82 | |
Maximum of Months | 0.140811E+12 | 1.82 | 52572.86 | 1.82 |
Report: FanReportMonthly
For: LAUNDRY_FLR_1 EXHAUST FAN
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.493775E+09 | 0.64 | 184.35 | 01-JAN-00:05 | 0.64 |
February | 0.445990E+09 | 0.64 | 184.35 | 01-FEB-00:03 | 0.64 |
March | 0.493775E+09 | 0.64 | 184.35 | 01-MAR-00:03 | 0.63 |
April | 0.477847E+09 | 0.64 | 184.35 | 01-APR-00:10 | 0.63 |
May | 0.493775E+09 | 0.64 | 184.35 | 01-MAY-00:10 | 0.63 |
June | 0.477847E+09 | 0.63 | 184.35 | 01-JUN-00:10 | 0.63 |
July | 0.493775E+09 | 0.63 | 184.35 | 01-JUL-00:10 | 0.63 |
August | 0.493775E+09 | 0.63 | 184.35 | 01-AUG-00:10 | 0.63 |
September | 0.477847E+09 | 0.63 | 184.35 | 01-SEP-00:10 | 0.63 |
October | 0.493775E+09 | 0.64 | 184.35 | 01-OCT-00:10 | 0.63 |
November | 0.477847E+09 | 0.63 | 184.35 | 01-NOV-00:10 | 0.63 |
December | 0.493775E+09 | 0.64 | 184.35 | 01-DEC-00:03 | 0.64 |
Annual Sum or Average | 0.581380E+10 | 0.64 | |||
Minimum of Months | 0.445990E+09 | 0.63 | 184.35 | 0.63 | |
Maximum of Months | 0.493775E+09 | 0.64 | 184.35 | 0.64 |
Report: FanReportMonthly
For: LOBBY_FLR_1 EXHAUST FAN
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: BANQUET_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: DINING_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.279806E+10 | 0.45 | 1474.84 | 01-JAN-07:10 | 0.64 |
February | 0.252728E+10 | 0.45 | 1474.84 | 01-FEB-07:05 | 0.63 |
March | 0.279806E+10 | 0.45 | 1474.84 | 01-MAR-07:05 | 0.63 |
April | 0.270780E+10 | 0.45 | 1474.84 | 01-APR-06:10 | 0.63 |
May | 0.279806E+10 | 0.45 | 1474.84 | 01-MAY-06:05 | 0.63 |
June | 0.270780E+10 | 0.45 | 1474.84 | 01-JUN-06:05 | 0.63 |
July | 0.279806E+10 | 0.45 | 1474.84 | 01-JUL-06:10 | 0.63 |
August | 0.279806E+10 | 0.45 | 1474.84 | 01-AUG-06:05 | 0.63 |
September | 0.270780E+10 | 0.45 | 1474.84 | 01-SEP-06:05 | 0.63 |
October | 0.279806E+10 | 0.45 | 1474.84 | 01-OCT-06:10 | 0.63 |
November | 0.270780E+10 | 0.45 | 1474.84 | 01-NOV-06:05 | 0.63 |
December | 0.279806E+10 | 0.45 | 1474.84 | 01-DEC-07:05 | 0.64 |
Annual Sum or Average | 0.329449E+11 | 0.45 | |||
Minimum of Months | 0.252728E+10 | 0.45 | 1474.84 | 0.63 | |
Maximum of Months | 0.279806E+10 | 0.45 | 1474.84 | 0.64 |
Report: FanReportMonthly
For: ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.482002E+09 | 1.15 | 2125.71 | 01-JAN-16:01 | 1.38 |
February | 0.552263E+09 | 1.19 | 2125.71 | 01-FEB-16:02 | 1.38 |
March | 0.828571E+09 | 1.24 | 2125.71 | 01-MAR-09:01 | 1.37 |
April | 0.108000E+10 | 1.29 | 2125.71 | 01-APR-08:62 | 1.37 |
May | 0.160829E+10 | 1.33 | 2125.71 | 01-MAY-08:62 | 1.37 |
June | 0.174526E+10 | 1.34 | 2125.71 | 01-JUN-08:62 | 1.38 |
July | 0.202535E+10 | 1.35 | 2125.71 | 01-JUL-08:62 | 1.37 |
August | 0.211757E+10 | 1.35 | 2125.71 | 01-AUG-08:62 | 1.37 |
September | 0.174565E+10 | 1.34 | 2125.71 | 01-SEP-08:62 | 1.37 |
October | 0.147875E+10 | 1.32 | 2125.71 | 01-OCT-08:62 | 1.37 |
November | 0.100056E+10 | 1.28 | 2125.71 | 01-NOV-08:61 | 1.37 |
December | 0.615700E+09 | 1.20 | 2125.71 | 01-DEC-09:02 | 1.38 |
Annual Sum or Average | 0.152800E+11 | 1.28 | |||
Minimum of Months | 0.482002E+09 | 1.15 | 2125.71 | 1.37 | |
Maximum of Months | 0.211757E+10 | 1.35 | 2125.71 | 1.38 |
Report: FanReportMonthly
For: ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.358516E+09 | 1.02 | 2089.41 | 01-JAN-16:01 | 1.38 |
February | 0.441327E+09 | 1.11 | 2089.41 | 01-FEB-16:02 | 1.38 |
March | 0.732500E+09 | 1.19 | 2089.41 | 01-MAR-09:01 | 1.37 |
April | 0.103348E+10 | 1.28 | 2089.41 | 01-APR-08:62 | 1.37 |
May | 0.160983E+10 | 1.33 | 2089.41 | 01-MAY-08:62 | 1.37 |
June | 0.177751E+10 | 1.34 | 2089.41 | 01-JUN-08:62 | 1.38 |
July | 0.205255E+10 | 1.35 | 2089.41 | 01-JUL-08:62 | 1.37 |
August | 0.209180E+10 | 1.35 | 2089.41 | 01-AUG-08:62 | 1.37 |
September | 0.165276E+10 | 1.33 | 2089.41 | 01-SEP-08:62 | 1.37 |
October | 0.132357E+10 | 1.30 | 2089.41 | 01-OCT-08:62 | 1.37 |
November | 0.837119E+09 | 1.25 | 2089.41 | 01-NOV-08:61 | 1.37 |
December | 0.469920E+09 | 1.10 | 2089.41 | 01-DEC-09:02 | 1.38 |
Annual Sum or Average | 0.143809E+11 | 1.25 | |||
Minimum of Months | 0.358516E+09 | 1.02 | 2089.41 | 1.37 | |
Maximum of Months | 0.209180E+10 | 1.35 | 2089.41 | 1.38 |
Report: FanReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.351325E+10 | 1.09 | 3753.63 | 28-JAN-13:50 | 1.38 |
February | 0.340499E+10 | 1.12 | 4044.32 | 04-FEB-13:50 | 1.38 |
March | 0.427780E+10 | 1.21 | 3795.60 | 27-MAR-12:30 | 1.38 |
April | 0.498033E+10 | 1.33 | 3583.34 | 28-APR-20:20 | 1.38 |
May | 0.667366E+10 | 1.38 | 4167.56 | 31-MAY-19:20 | 1.38 |
June | 0.693560E+10 | 1.38 | 4149.52 | 09-JUN-20:20 | 1.38 |
July | 0.809480E+10 | 1.38 | 6281.82 | 21-JUL-20:50 | 1.38 |
August | 0.857870E+10 | 1.38 | 6130.63 | 05-AUG-19:10 | 1.38 |
September | 0.787771E+10 | 1.38 | 4426.56 | 26-SEP-13:10 | 1.38 |
October | 0.769187E+10 | 1.38 | 6827.63 | 29-OCT-12:10 | 1.38 |
November | 0.608543E+10 | 1.36 | 4283.81 | 05-NOV-13:30 | 1.38 |
December | 0.420398E+10 | 1.17 | 3958.00 | 03-DEC-13:00 | 1.38 |
Annual Sum or Average | 0.723181E+11 | 1.30 | |||
Minimum of Months | 0.340499E+10 | 1.09 | 3583.34 | 1.38 | |
Maximum of Months | 0.857870E+10 | 1.38 | 6827.63 | 1.38 |
Report: FanReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.444529E+10 | 0.98 | 14061.79 | 01-JAN-09:02 | 1.38 |
February | 0.474530E+10 | 0.99 | 14061.79 | 01-FEB-16:02 | 1.38 |
March | 0.662674E+10 | 1.02 | 14061.79 | 01-MAR-09:01 | 1.38 |
April | 0.855204E+10 | 1.15 | 14061.79 | 01-APR-08:62 | 1.37 |
May | 0.119580E+11 | 1.27 | 14061.79 | 01-MAY-08:62 | 1.37 |
June | 0.129858E+11 | 1.29 | 14061.79 | 01-JUN-08:62 | 1.38 |
July | 0.148704E+11 | 1.30 | 14061.79 | 01-JUL-08:62 | 1.38 |
August | 0.148146E+11 | 1.29 | 14061.79 | 01-AUG-08:62 | 1.38 |
September | 0.118507E+11 | 1.27 | 14061.79 | 01-SEP-08:62 | 1.37 |
October | 0.101170E+11 | 1.21 | 14061.79 | 01-OCT-08:62 | 1.37 |
November | 0.721623E+10 | 1.06 | 14061.79 | 01-NOV-08:61 | 1.37 |
December | 0.516086E+10 | 0.98 | 14061.79 | 01-DEC-09:02 | 1.38 |
Annual Sum or Average | 0.113343E+12 | 1.15 | |||
Minimum of Months | 0.444529E+10 | 0.98 | 14061.79 | 1.37 | |
Maximum of Months | 0.148704E+11 | 1.30 | 14061.79 | 1.38 |
Report: FanReportMonthly
For: ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.475284E+09 | 1.16 | 1919.04 | 01-JAN-16:01 | 1.38 |
February | 0.537790E+09 | 1.21 | 1919.04 | 01-FEB-16:02 | 1.38 |
March | 0.781906E+09 | 1.25 | 1919.04 | 01-MAR-09:01 | 1.37 |
April | 0.107904E+10 | 1.31 | 1919.04 | 01-APR-08:62 | 1.37 |
May | 0.165130E+10 | 1.35 | 1919.04 | 01-MAY-08:62 | 1.37 |
June | 0.174917E+10 | 1.35 | 1919.04 | 01-JUN-08:62 | 1.38 |
July | 0.203923E+10 | 1.35 | 1919.04 | 01-JUL-08:62 | 1.37 |
August | 0.212808E+10 | 1.35 | 1919.04 | 01-AUG-08:62 | 1.38 |
September | 0.175989E+10 | 1.35 | 1919.04 | 01-SEP-08:62 | 1.37 |
October | 0.152394E+10 | 1.34 | 1919.04 | 01-OCT-08:62 | 1.37 |
November | 0.100307E+10 | 1.31 | 1919.04 | 01-NOV-08:61 | 1.37 |
December | 0.591868E+09 | 1.21 | 1919.04 | 01-DEC-09:02 | 1.38 |
Annual Sum or Average | 0.153206E+11 | 1.30 | |||
Minimum of Months | 0.475284E+09 | 1.16 | 1919.04 | 1.37 | |
Maximum of Months | 0.212808E+10 | 1.35 | 1919.04 | 1.38 |
Report: FanReportMonthly
For: ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.356967E+09 | 1.00 | 1884.58 | 01-JAN-16:01 | 1.38 |
February | 0.421939E+09 | 1.08 | 1884.58 | 01-FEB-16:02 | 1.38 |
March | 0.687939E+09 | 1.22 | 1884.58 | 01-MAR-09:01 | 1.37 |
April | 0.103040E+10 | 1.30 | 1884.58 | 01-APR-08:62 | 1.37 |
May | 0.165095E+10 | 1.35 | 1884.58 | 01-MAY-08:62 | 1.37 |
June | 0.177647E+10 | 1.35 | 1884.58 | 01-JUN-08:62 | 1.38 |
July | 0.206497E+10 | 1.35 | 1884.58 | 01-JUL-08:62 | 1.37 |
August | 0.211092E+10 | 1.35 | 1884.58 | 01-AUG-08:62 | 1.38 |
September | 0.167065E+10 | 1.34 | 1884.58 | 01-SEP-08:62 | 1.37 |
October | 0.134720E+10 | 1.33 | 1884.58 | 01-OCT-08:62 | 1.37 |
November | 0.816148E+09 | 1.28 | 1884.58 | 01-NOV-08:61 | 1.37 |
December | 0.447262E+09 | 1.07 | 1884.58 | 01-DEC-09:02 | 1.38 |
Annual Sum or Average | 0.143818E+11 | 1.25 | |||
Minimum of Months | 0.356967E+09 | 1.00 | 1884.58 | 1.37 | |
Maximum of Months | 0.211092E+10 | 1.35 | 1884.58 | 1.38 |
Report: FanReportMonthly
For: ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.134770E+09 | 1.18 | 580.41 | 01-JAN-16:01 | 1.38 |
February | 0.154114E+09 | 1.21 | 580.41 | 01-FEB-16:02 | 1.38 |
March | 0.236274E+09 | 1.26 | 580.41 | 01-MAR-09:01 | 1.37 |
April | 0.312170E+09 | 1.30 | 580.41 | 01-APR-15:02 | 1.38 |
May | 0.464600E+09 | 1.34 | 580.41 | 01-MAY-08:62 | 1.37 |
June | 0.503991E+09 | 1.35 | 580.41 | 01-JUN-08:62 | 1.38 |
July | 0.587341E+09 | 1.35 | 580.41 | 01-JUL-08:62 | 1.37 |
August | 0.605918E+09 | 1.35 | 580.41 | 01-AUG-08:62 | 1.37 |
September | 0.497015E+09 | 1.34 | 580.41 | 01-SEP-08:62 | 1.37 |
October | 0.416062E+09 | 1.33 | 580.41 | 01-OCT-08:62 | 1.37 |
November | 0.280287E+09 | 1.30 | 580.41 | 01-NOV-08:61 | 1.37 |
December | 0.169415E+09 | 1.22 | 580.41 | 01-DEC-09:02 | 1.38 |
Annual Sum or Average | 0.436196E+10 | 1.29 | |||
Minimum of Months | 0.134770E+09 | 1.18 | 580.41 | 1.37 | |
Maximum of Months | 0.605918E+09 | 1.35 | 580.41 | 1.38 |
Report: FanReportMonthly
For: ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.105485E+09 | 1.07 | 570.88 | 01-JAN-16:01 | 1.38 |
February | 0.125935E+09 | 1.15 | 570.88 | 01-FEB-16:02 | 1.38 |
March | 0.210932E+09 | 1.24 | 570.88 | 01-MAR-09:01 | 1.37 |
April | 0.300208E+09 | 1.29 | 570.88 | 01-APR-15:02 | 1.38 |
May | 0.465718E+09 | 1.34 | 570.88 | 01-MAY-08:62 | 1.37 |
June | 0.513968E+09 | 1.35 | 570.88 | 01-JUN-08:62 | 1.38 |
July | 0.592623E+09 | 1.36 | 570.88 | 01-JUL-08:62 | 1.37 |
August | 0.598852E+09 | 1.35 | 570.88 | 01-AUG-08:62 | 1.37 |
September | 0.471839E+09 | 1.34 | 570.88 | 01-SEP-08:62 | 1.37 |
October | 0.375497E+09 | 1.31 | 570.88 | 01-OCT-08:62 | 1.37 |
November | 0.236572E+09 | 1.27 | 570.88 | 01-NOV-08:61 | 1.37 |
December | 0.132513E+09 | 1.14 | 570.88 | 01-DEC-09:02 | 1.38 |
Annual Sum or Average | 0.413014E+10 | 1.27 | |||
Minimum of Months | 0.105485E+09 | 1.07 | 570.88 | 1.37 | |
Maximum of Months | 0.598852E+09 | 1.36 | 570.88 | 1.38 |
Report: FanReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.107083E+10 | 1.24 | 2777.45 | 01-JAN-09:02 | 1.38 |
February | 0.108968E+10 | 1.24 | 2777.45 | 01-FEB-16:02 | 1.38 |
March | 0.138192E+10 | 1.27 | 2777.45 | 01-MAR-09:01 | 1.38 |
April | 0.162523E+10 | 1.29 | 2777.45 | 01-APR-08:62 | 1.37 |
May | 0.224502E+10 | 1.33 | 2777.45 | 01-MAY-08:62 | 1.37 |
June | 0.236120E+10 | 1.33 | 2777.45 | 01-JUN-08:62 | 1.38 |
July | 0.280097E+10 | 1.34 | 2777.45 | 01-JUL-08:62 | 1.37 |
August | 0.295806E+10 | 1.35 | 2777.45 | 01-AUG-08:62 | 1.37 |
September | 0.261745E+10 | 1.34 | 2777.45 | 01-SEP-08:62 | 1.37 |
October | 0.246093E+10 | 1.33 | 2777.45 | 01-OCT-08:62 | 1.37 |
November | 0.187585E+10 | 1.32 | 2777.45 | 01-NOV-08:61 | 1.37 |
December | 0.128240E+10 | 1.26 | 2777.45 | 01-DEC-09:02 | 1.38 |
Annual Sum or Average | 0.237695E+11 | 1.30 | |||
Minimum of Months | 0.107083E+10 | 1.24 | 2777.45 | 1.37 | |
Maximum of Months | 0.295806E+10 | 1.35 | 2777.45 | 1.38 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.384687E+09 | 0.346218E+09 | 392.95 | 30-JAN-11:40 | 353.65 | 353.65 | 34.70 | 0.64 |
February | 0.316700E+09 | 0.285030E+09 | 412.39 | 21-FEB-11:40 | 371.15 | 371.15 | 35.50 | 0.70 |
March | 0.336905E+09 | 0.303215E+09 | 421.03 | 20-MAR-10:40 | 378.93 | 378.93 | 36.09 | 0.73 |
April | 0.299210E+09 | 0.269289E+09 | 414.31 | 05-APR-10:40 | 372.88 | 372.88 | 36.12 | 0.71 |
May | 0.252586E+09 | 0.227327E+09 | 387.12 | 01-MAY-10:50 | 348.40 | 348.40 | 37.60 | 0.62 |
June | 0.213640E+09 | 0.192276E+09 | 370.33 | 20-JUN-10:40 | 333.30 | 333.30 | 36.51 | 0.57 |
July | 0.186100E+09 | 0.167490E+09 | 361.00 | 03-JUL-10:40 | 324.90 | 324.90 | 36.26 | 0.55 |
August | 0.149606E+09 | 0.134646E+09 | 344.54 | 01-AUG-10:40 | 310.08 | 310.08 | 35.90 | 0.51 |
September | 0.138271E+09 | 0.124444E+09 | 314.14 | 25-SEP-10:40 | 282.73 | 282.73 | 33.64 | 0.44 |
October | 0.148017E+09 | 0.133215E+09 | 303.69 | 02-OCT-10:40 | 273.32 | 273.32 | 33.35 | 0.42 |
November | 0.186266E+09 | 0.167640E+09 | 329.91 | 29-NOV-11:40 | 296.92 | 296.92 | 32.57 | 0.47 |
December | 0.312808E+09 | 0.281527E+09 | 391.36 | 15-DEC-11:40 | 352.23 | 352.23 | 36.98 | 0.63 |
Annual Sum or Average | 0.292480E+10 | 0.263232E+10 | ||||||
Minimum of Months | 0.138271E+09 | 0.124444E+09 | 303.69 | 273.32 | 273.32 | 32.57 | 0.42 | |
Maximum of Months | 0.384687E+09 | 0.346218E+09 | 421.03 | 378.93 | 378.93 | 37.60 | 0.73 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.123398E+11 | 0.111058E+11 | 8019.63 | 09-JAN-19:02 | 7217.67 | 7217.67 | 6.73 | 24.91 |
February | 0.129214E+11 | 0.116293E+11 | 8315.92 | 06-FEB-19:02 | 7484.33 | 7484.33 | 6.73 | 28.67 |
March | 0.161659E+11 | 0.145493E+11 | 8350.16 | 28-MAR-18:03 | 7515.15 | 7515.15 | 6.73 | 29.19 |
April | 0.182663E+11 | 0.164397E+11 | 8922.28 | 30-APR-18:03 | 8030.05 | 8030.05 | 6.73 | 38.30 |
May | 0.208588E+11 | 0.187729E+11 | 9512.77 | 30-MAY-18:00 | 8561.49 | 8561.49 | 6.73 | 44.12 |
June | 0.214779E+11 | 0.193301E+11 | 10615.46 | 26-JUN-18:03 | 9553.91 | 9553.91 | 6.73 | 50.24 |
July | 0.230789E+11 | 0.207710E+11 | 11018.87 | 19-JUL-18:02 | 9916.98 | 9916.98 | 6.73 | 51.84 |
August | 0.233360E+11 | 0.210024E+11 | 11058.20 | 11-AUG-18:02 | 9952.38 | 9952.38 | 6.73 | 51.99 |
September | 0.219011E+11 | 0.197110E+11 | 11007.41 | 10-SEP-18:02 | 9906.67 | 9906.67 | 6.73 | 51.80 |
October | 0.211154E+11 | 0.190039E+11 | 10024.86 | 07-OCT-18:03 | 9022.37 | 9022.37 | 6.73 | 47.39 |
November | 0.181438E+11 | 0.163294E+11 | 8779.63 | 01-NOV-18:03 | 7901.66 | 7901.66 | 6.73 | 36.28 |
December | 0.151700E+11 | 0.136530E+11 | 8248.12 | 04-DEC-19:03 | 7423.30 | 7423.30 | 6.73 | 27.70 |
Annual Sum or Average | 0.224775E+12 | 0.202298E+12 | ||||||
Minimum of Months | 0.123398E+11 | 0.111058E+11 | 8019.63 | 7217.67 | 7217.67 | 6.73 | 24.91 | |
Maximum of Months | 0.233360E+11 | 0.210024E+11 | 11058.20 | 9952.38 | 9952.38 | 6.73 | 51.99 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.199777E+11 | 0.179799E+11 | 7458.80 | 01-JAN-00:05 | 6712.92 | 6712.92 | 7.12 | 52.28 |
February | 0.180443E+11 | 0.162399E+11 | 7458.80 | 01-FEB-00:03 | 6712.92 | 6712.92 | 7.39 | 52.28 |
March | 0.199777E+11 | 0.179799E+11 | 7458.80 | 01-MAR-00:03 | 6712.92 | 6712.92 | 8.61 | 52.28 |
April | 0.193332E+11 | 0.173999E+11 | 7458.80 | 01-APR-00:10 | 6712.92 | 6712.92 | 8.94 | 52.28 |
May | 0.199777E+11 | 0.179799E+11 | 7458.80 | 01-MAY-00:10 | 6712.92 | 6712.92 | 9.75 | 52.28 |
June | 0.193332E+11 | 0.173999E+11 | 7458.80 | 01-JUN-00:10 | 6712.92 | 6712.92 | 9.70 | 52.28 |
July | 0.199777E+11 | 0.179799E+11 | 7458.80 | 01-JUL-00:10 | 6712.92 | 6712.92 | 10.67 | 52.28 |
August | 0.199777E+11 | 0.179799E+11 | 7458.80 | 01-AUG-00:10 | 6712.92 | 6712.92 | 11.13 | 52.28 |
September | 0.193332E+11 | 0.173999E+11 | 7458.80 | 01-SEP-00:10 | 6712.92 | 6712.92 | 10.20 | 52.28 |
October | 0.199777E+11 | 0.179799E+11 | 7458.80 | 01-OCT-00:10 | 6712.92 | 6712.92 | 10.59 | 52.28 |
November | 0.193332E+11 | 0.173999E+11 | 7458.80 | 01-NOV-00:10 | 6712.92 | 6712.92 | 9.18 | 52.28 |
December | 0.199777E+11 | 0.179799E+11 | 7458.80 | 01-DEC-00:03 | 6712.92 | 6712.92 | 8.08 | 52.28 |
Annual Sum or Average | 0.235221E+12 | 0.211699E+12 | ||||||
Minimum of Months | 0.180443E+11 | 0.162399E+11 | 7458.80 | 6712.92 | 6712.92 | 7.12 | 52.28 | |
Maximum of Months | 0.199777E+11 | 0.179799E+11 | 7458.80 | 6712.92 | 6712.92 | 11.13 | 52.28 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.128314E+09 | 38494137.67 | 47.91 | 01-JAN-00:05 | 14.37 | 14.37 | 51.54 | 0.37 |
February | 0.115896E+09 | 34768898.54 | 47.91 | 01-FEB-00:03 | 14.37 | 14.37 | 51.97 | 0.37 |
March | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAR-00:03 | 14.37 | 14.37 | 52.30 | 0.37 |
April | 0.124175E+09 | 37252391.29 | 47.91 | 01-APR-00:10 | 14.37 | 14.37 | 53.96 | 0.37 |
May | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAY-00:10 | 14.37 | 14.37 | 55.09 | 0.37 |
June | 0.124175E+09 | 37252391.29 | 47.91 | 01-JUN-00:10 | 14.37 | 14.37 | 55.74 | 0.37 |
July | 0.128314E+09 | 38494137.67 | 47.91 | 01-JUL-00:10 | 14.37 | 14.37 | 55.04 | 0.37 |
August | 0.128314E+09 | 38494137.67 | 47.91 | 01-AUG-00:10 | 14.37 | 14.37 | 56.03 | 0.37 |
September | 0.124175E+09 | 37252391.29 | 47.91 | 01-SEP-00:10 | 14.37 | 14.37 | 55.70 | 0.37 |
October | 0.128314E+09 | 38494137.67 | 47.91 | 01-OCT-00:10 | 14.37 | 14.37 | 54.10 | 0.37 |
November | 0.124175E+09 | 37252391.29 | 47.91 | 01-NOV-00:10 | 14.37 | 14.37 | 54.76 | 0.37 |
December | 0.128314E+09 | 38494137.67 | 47.91 | 01-DEC-00:03 | 14.37 | 14.37 | 51.86 | 0.37 |
Annual Sum or Average | 0.151079E+10 | 0.453237E+09 | ||||||
Minimum of Months | 0.115896E+09 | 34768898.54 | 47.91 | 14.37 | 14.37 | 51.54 | 0.37 | |
Maximum of Months | 0.128314E+09 | 38494137.67 | 47.91 | 14.37 | 14.37 | 56.03 | 0.37 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 31.40 | 60.00 | 19646.24 | 67612.81 | 04-JAN-09:05 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 28.88 | 60.00 | 18110.02 | 71788.38 | 21-FEB-11:40 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 26.17 | 60.00 | 17353.89 | 73263.70 | 20-MAR-10:40 |
April | 0.00 | 0.00 | 01-APR-00:10 | 29.29 | 60.00 | 15417.06 | 70630.85 | 05-APR-10:40 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 29.24 | 60.00 | 12020.69 | 62623.62 | 01-MAY-10:40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.63 | 60.00 | 10434.28 | 60318.94 | 08-JUN-10:35 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 29.03 | 60.00 | 8718.80 | 56173.42 | 03-JUL-10:35 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 28.88 | 60.00 | 6944.20 | 53151.36 | 01-AUG-10:35 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 29.36 | 60.00 | 6613.22 | 48667.75 | 25-SEP-10:35 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 28.52 | 60.00 | 6940.67 | 46899.65 | 30-OCT-10:35 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 29.64 | 60.00 | 9499.51 | 54197.76 | 29-NOV-11:40 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 25.10 | 60.00 | 15895.06 | 60713.87 | 21-DEC-11:40 |
Annual Sum or Average | 0.00 | 12271.53 | ||||||
Minimum of Months | 0.00 | 0.00 | 25.10 | 60.00 | 6613.22 | 46899.65 | ||
Maximum of Months | 0.00 | 0.00 | 31.40 | 60.00 | 19646.24 | 73263.70 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 237167.47 | 733651.35 | 09-JAN-19:02 | 10.05 | 6.70 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 306975.02 | 809469.42 | 07-FEB-16:03 | 10.40 | 6.70 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 361943.43 | 831921.19 | 28-MAR-18:03 | 10.50 | 6.70 | 0.00 | 0.00 | 01-MAR-00:03 |
April | 488373.96 | 1025479.41 | 30-APR-18:03 | 11.38 | 6.70 | 0.00 | 0.00 | 01-APR-00:10 |
May | 630595.86 | 1156701.78 | 30-MAY-18:03 | 11.98 | 6.70 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 793414.14 | 1267567.19 | 26-JUN-18:03 | 12.49 | 6.70 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 906857.74 | 1360022.62 | 19-JUL-15:03 | 12.91 | 6.70 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 939199.89 | 1356762.51 | 11-AUG-18:03 | 12.90 | 6.70 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 846052.32 | 1359506.95 | 10-SEP-18:03 | 12.91 | 6.70 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 669067.22 | 1244079.72 | 07-OCT-18:03 | 12.38 | 6.70 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 496846.31 | 1026399.61 | 01-NOV-15:03 | 11.39 | 6.70 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 340913.26 | 824106.43 | 05-DEC-16:03 | 10.46 | 6.70 | 0.00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 586284.91 | 0.00 | ||||||
Minimum of Months | 237167.47 | 733651.35 | 10.05 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 939199.89 | 1360022.62 | 12.91 | 6.70 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 51.54 | 59.78 | 20173.52 | 40496.02 | 13-JAN-07:20 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 51.97 | 59.11 | 19646.95 | 40041.41 | 01-FEB-07:10 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 52.30 | 59.85 | 18401.38 | 38142.58 | 01-MAR-08:00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 53.96 | 58.32 | 16683.57 | 34618.30 | 03-APR-06:50 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 55.09 | 59.05 | 15012.05 | 31228.90 | 01-MAY-06:40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 55.74 | 59.41 | 13823.97 | 28089.02 | 01-JUN-07:00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 55.04 | 58.22 | 13432.43 | 26587.31 | 31-JUL-06:30 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 56.03 | 59.72 | 13983.69 | 28568.10 | 31-AUG-06:40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 55.70 | 59.59 | 15277.46 | 31675.70 | 29-SEP-06:20 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 54.10 | 58.66 | 16984.95 | 35508.44 | 31-OCT-07:00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 54.76 | 59.68 | 18650.75 | 38583.71 | 30-NOV-07:20 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 51.86 | 58.65 | 19817.25 | 40234.70 | 29-DEC-08:00 |
Annual Sum or Average | 0.00 | 16808.63 | ||||||
Minimum of Months | 0.00 | 0.00 | 51.54 | 58.22 | 13432.43 | 26587.31 | ||
Maximum of Months | 0.00 | 0.00 | 56.03 | 59.85 | 20173.52 | 40496.02 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.526963E+11 | 0.00 | 0.456129E+12 | 0.140811E+12 | 0.00 | 0.00 |
February | 0.440038E+11 | 0.00 | 0.544112E+12 | 0.127184E+12 | 0.00 | 0.00 |
March | 0.467478E+11 | 0.00 | 0.712096E+12 | 0.140811E+12 | 0.00 | 0.00 |
April | 0.402283E+11 | 0.00 | 0.944154E+12 | 0.136269E+12 | 0.00 | 0.00 |
May | 0.324541E+11 | 0.00 | 0.125982E+13 | 0.140811E+12 | 0.00 | 0.00 |
June | 0.272679E+11 | 0.00 | 0.157549E+13 | 0.136269E+12 | 0.00 | 0.00 |
July | 0.235459E+11 | 0.00 | 0.187551E+13 | 0.140810E+12 | 0.00 | 0.00 |
August | 0.187520E+11 | 0.00 | 0.194537E+13 | 0.140810E+12 | 0.00 | 0.00 |
September | 0.172815E+11 | 0.00 | 0.169244E+13 | 0.136269E+12 | 0.00 | 0.00 |
October | 0.187245E+11 | 0.00 | 0.135545E+13 | 0.140811E+12 | 0.00 | 0.00 |
November | 0.247544E+11 | 0.00 | 0.957965E+12 | 0.136269E+12 | 0.00 | 0.00 |
December | 0.427303E+11 | 0.00 | 0.679451E+12 | 0.140811E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.389187E+12 | 0.00 | 0.139980E+14 | 0.165794E+13 | 0.00 | 0.00 |
Minimum of Months | 0.172815E+11 | 0.00 | 0.456129E+12 | 0.127184E+12 | 0.00 | 0.00 |
Maximum of Months | 0.526963E+11 | 0.00 | 0.194537E+13 | 0.140811E+12 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 112657.79 | 0.00 | 0.514319E+11 | 0.587890E+10 | 0.00 | 0.00 |
February | 19471.53 | 0.00 | 0.606310E+11 | 0.530997E+10 | 0.00 | 0.00 |
March | 22908.32 | 0.00 | 0.774445E+11 | 0.587890E+10 | 0.00 | 0.00 |
April | 15816.69 | 0.00 | 0.988599E+11 | 0.568926E+10 | 0.00 | 0.00 |
May | 12502.15 | 0.00 | 0.120480E+12 | 0.587890E+10 | 0.00 | 0.00 |
June | 6274.98 | 0.00 | 0.145398E+12 | 0.568926E+10 | 0.00 | 0.00 |
July | 7144.14 | 0.00 | 0.169008E+12 | 0.587890E+10 | 0.00 | 0.00 |
August | 6227.77 | 0.00 | 0.173955E+12 | 0.587890E+10 | 0.00 | 0.00 |
September | 12923.21 | 0.00 | 0.155056E+12 | 0.568926E+10 | 0.00 | 0.00 |
October | 17091.63 | 0.00 | 0.130214E+12 | 0.587890E+10 | 0.00 | 0.00 |
November | 20199.36 | 0.00 | 0.101203E+12 | 0.568926E+10 | 0.00 | 0.00 |
December | 20363.19 | 0.00 | 0.743724E+11 | 0.587890E+10 | 0.00 | 0.00 |
Annual Sum or Average | 273580.75 | 0.00 | 0.135805E+13 | 0.692193E+11 | 0.00 | 0.00 |
Minimum of Months | 6227.77 | 0.00 | 0.514319E+11 | 0.530997E+10 | 0.00 | 0.00 |
Maximum of Months | 112657.79 | 0.00 | 0.173955E+12 | 0.587890E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.140811E+12 | 0.456129E+12 | 0.526963E+11 | 0.606574E+10 | 0.437859E+11 | 0.00 | 0.00 | 0.00 |
February | 0.127184E+12 | 0.544112E+12 | 0.440038E+11 | 0.197290E+10 | 0.939659E+11 | 0.00 | 0.00 | 0.00 |
March | 0.140811E+12 | 0.712096E+12 | 0.467478E+11 | 0.808052E+10 | 0.182188E+12 | 0.00 | 0.00 | 0.00 |
April | 0.136269E+12 | 0.944154E+12 | 0.402283E+11 | 0.625130E+10 | 0.432372E+12 | 0.00 | 0.00 | 0.00 |
May | 0.140811E+12 | 0.125982E+13 | 0.324541E+11 | 0.202759E+09 | 0.875743E+12 | 0.00 | 0.00 | 0.00 |
June | 0.136269E+12 | 0.157549E+13 | 0.272679E+11 | 6602965.04 | 0.129588E+13 | 0.00 | 0.00 | 0.00 |
July | 0.140810E+12 | 0.187551E+13 | 0.235459E+11 | 0.00 | 0.166658E+13 | 0.00 | 0.00 | 0.00 |
August | 0.140810E+12 | 0.194537E+13 | 0.187520E+11 | 0.00 | 0.174422E+13 | 0.00 | 0.00 | 0.00 |
September | 0.136269E+12 | 0.169244E+13 | 0.172815E+11 | 0.00 | 0.141783E+13 | 0.00 | 0.00 | 0.00 |
October | 0.140811E+12 | 0.135545E+13 | 0.187245E+11 | 0.162380E+10 | 0.954109E+12 | 0.00 | 0.00 | 0.00 |
November | 0.136269E+12 | 0.957965E+12 | 0.247544E+11 | 0.114303E+10 | 0.420666E+12 | 0.00 | 0.00 | 0.00 |
December | 0.140811E+12 | 0.679451E+12 | 0.427303E+11 | 0.227728E+10 | 0.142161E+12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.165794E+13 | 0.139980E+14 | 0.389187E+12 | 0.276239E+11 | 0.926950E+13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.127184E+12 | 0.456129E+12 | 0.172815E+11 | 0.00 | 0.437859E+11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.140811E+12 | 0.194537E+13 | 0.526963E+11 | 0.808052E+10 | 0.174422E+13 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.587890E+10 | 0.514319E+11 | 112657.79 | 0.137238E+10 | 0.294445E+10 | 0.00 | 0.00 | 0.00 |
February | 0.530997E+10 | 0.606310E+11 | 19471.53 | 0.347736E+09 | 0.836257E+10 | 0.00 | 0.00 | 0.00 |
March | 0.587890E+10 | 0.774445E+11 | 22908.32 | 0.314559E+09 | 0.176376E+11 | 0.00 | 0.00 | 0.00 |
April | 0.568926E+10 | 0.988599E+11 | 15816.69 | 0.259783E+09 | 0.426897E+11 | 0.00 | 0.00 | 0.00 |
May | 0.587890E+10 | 0.120480E+12 | 12502.15 | 2152146.16 | 0.885895E+11 | 0.00 | 0.00 | 0.00 |
June | 0.568926E+10 | 0.145398E+12 | 6274.98 | 0.00 | 0.127612E+12 | 0.00 | 0.00 | 0.00 |
July | 0.587890E+10 | 0.169008E+12 | 7144.14 | 0.00 | 0.162116E+12 | 0.00 | 0.00 | 0.00 |
August | 0.587890E+10 | 0.173955E+12 | 6227.77 | 0.00 | 0.170145E+12 | 0.00 | 0.00 | 0.00 |
September | 0.568926E+10 | 0.155056E+12 | 12923.21 | 0.00 | 0.139592E+12 | 0.00 | 0.00 | 0.00 |
October | 0.587890E+10 | 0.130214E+12 | 17091.63 | 21944774.60 | 0.959460E+11 | 0.00 | 0.00 | 0.00 |
November | 0.568926E+10 | 0.101203E+12 | 20199.36 | 3556283.49 | 0.440893E+11 | 0.00 | 0.00 | 0.00 |
December | 0.587890E+10 | 0.743724E+11 | 20363.19 | 0.216783E+09 | 0.134980E+11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.692193E+11 | 0.135805E+13 | 273580.75 | 0.253889E+10 | 0.913222E+12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.530997E+10 | 0.514319E+11 | 6227.77 | 0.00 | 0.294445E+10 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.587890E+10 | 0.173955E+12 | 112657.79 | 0.137238E+10 | 0.170145E+12 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.140811E+12 | 0.526963E+11 | 0.456129E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.127184E+12 | 0.440038E+11 | 0.544112E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.140811E+12 | 0.467478E+11 | 0.712096E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.136269E+12 | 0.402283E+11 | 0.944154E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.140811E+12 | 0.324541E+11 | 0.125982E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.136269E+12 | 0.272679E+11 | 0.157549E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.140810E+12 | 0.235459E+11 | 0.187551E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.140810E+12 | 0.187520E+11 | 0.194537E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.136269E+12 | 0.172815E+11 | 0.169244E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.140811E+12 | 0.187245E+11 | 0.135545E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.136269E+12 | 0.247544E+11 | 0.957965E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.140811E+12 | 0.427303E+11 | 0.679451E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.165794E+13 | 0.389187E+12 | 0.139980E+14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.127184E+12 | 0.172815E+11 | 0.456129E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.140811E+12 | 0.526963E+11 | 0.194537E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.587890E+10 | 112657.79 | 0.514319E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.530997E+10 | 19471.53 | 0.606310E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.587890E+10 | 22908.32 | 0.774445E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.568926E+10 | 15816.69 | 0.988599E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.587890E+10 | 12502.15 | 0.120480E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.568926E+10 | 6274.98 | 0.145398E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.587890E+10 | 7144.14 | 0.169008E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.587890E+10 | 6227.77 | 0.173955E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.568926E+10 | 12923.21 | 0.155056E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.587890E+10 | 17091.63 | 0.130214E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.568926E+10 | 20199.36 | 0.101203E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.587890E+10 | 20363.19 | 0.743724E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.692193E+11 | 273580.75 | 0.135805E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.530997E+10 | 6227.77 | 0.514319E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.587890E+10 | 112657.79 | 0.173955E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.311115E+11 | 0.00 | 0.00 | 0.00 | 0.419838E+10 | 0.00 | 0.00 | 0.00 | 2.18 |
February | 0.178661E+11 | 0.00 | 0.00 | 0.00 | 0.916547E+10 | 0.00 | 0.00 | 0.00 | 2.19 |
March | 0.123671E+11 | 0.00 | 0.00 | 0.00 | 0.151153E+11 | 0.00 | 0.00 | 0.00 | 2.20 |
April | 0.233372E+10 | 0.00 | 0.00 | 0.00 | 0.343351E+11 | 0.00 | 0.00 | 0.00 | 2.20 |
May | 0.174892E+09 | 0.00 | 2395447.28 | 0.00 | 0.643945E+11 | 0.00 | 0.00 | 416.19 | 2.21 |
June | 13960373.35 | 0.00 | 0.00 | 0.00 | 0.103574E+12 | 0.00 | 0.00 | 0.00 | 2.23 |
July | 14614281.12 | 0.00 | 0.00 | 0.00 | 0.135418E+12 | 0.00 | 0.00 | 0.00 | 2.23 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.143097E+12 | 0.00 | 0.00 | 0.00 | 2.23 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.117458E+12 | 0.00 | 0.00 | 0.00 | 2.21 |
October | 0.240015E+09 | 0.00 | 0.00 | 0.00 | 0.762647E+11 | 0.00 | 0.00 | 0.00 | 2.20 |
November | 0.232926E+10 | 0.00 | 0.00 | 0.00 | 0.358863E+11 | 0.00 | 0.00 | 0.00 | 2.19 |
December | 0.159730E+11 | 0.00 | 0.00 | 0.00 | 0.152871E+11 | 0.00 | 0.00 | 0.00 | 2.18 |
Annual Sum or Average | 0.824242E+11 | 0.00 | 2395447.28 | 0.00 | 0.754193E+12 | 0.00 | 0.00 | 416.19 | 2.20 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.419838E+10 | 0.00 | 0.00 | 0.00 | 2.18 |
Maximum of Months | 0.311115E+11 | 0.00 | 2395447.28 | 0.00 | 0.143097E+12 | 0.00 | 0.00 | 416.19 | 2.23 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.431480E+10 | 0.00 | 0.00 | 0.00 | 0.582265E+09 | 0.00 | 0.00 | 0.00 | 5.48 |
February | 0.247782E+10 | 0.00 | 0.00 | 0.00 | 0.127114E+10 | 0.00 | 0.00 | 0.00 | 5.50 |
March | 0.171517E+10 | 0.00 | 0.00 | 0.00 | 0.209631E+10 | 0.00 | 0.00 | 0.00 | 5.53 |
April | 0.323659E+09 | 0.00 | 0.00 | 0.00 | 0.476187E+10 | 0.00 | 0.00 | 0.00 | 5.54 |
May | 24255440.56 | 0.00 | 0.00 | 0.00 | 0.893109E+10 | 0.00 | 0.00 | 0.00 | 5.56 |
June | 1936137.96 | 0.00 | 0.00 | 0.00 | 0.143644E+11 | 0.00 | 0.00 | 0.00 | 5.61 |
July | 2026827.20 | 81346433.18 | 0.00 | 0.00 | 0.186995E+11 | 0.00 | 0.00 | 0.00 | 5.62 |
August | 0.00 | 0.723796E+09 | 0.00 | 0.00 | 0.191220E+11 | 0.00 | 0.00 | 0.00 | 5.61 |
September | 0.00 | 0.935918E+09 | 0.00 | 0.00 | 0.153541E+11 | 0.00 | 0.00 | 0.00 | 5.57 |
October | 33287203.50 | 0.614146E+09 | 0.00 | 0.00 | 0.996286E+10 | 0.00 | 0.00 | 0.00 | 5.53 |
November | 0.323040E+09 | 25488234.88 | 0.00 | 0.00 | 0.495152E+10 | 0.00 | 0.00 | 0.00 | 5.51 |
December | 0.221527E+10 | 0.00 | 0.00 | 0.00 | 0.212014E+10 | 0.00 | 0.00 | 0.00 | 5.50 |
Annual Sum or Average | 0.114313E+11 | 0.238069E+10 | 0.00 | 0.00 | 0.102217E+12 | 0.00 | 0.00 | 0.00 | 5.55 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.582265E+09 | 0.00 | 0.00 | 0.00 | 5.48 |
Maximum of Months | 0.431480E+10 | 0.935918E+09 | 0.00 | 0.00 | 0.191220E+11 | 0.00 | 0.00 | 0.00 | 5.62 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.284303E+10 | 0.00 | 0.00 | 0.00 | 0.383656E+09 | 0.00 | 0.00 | 0.00 | 3.12 |
February | 0.163264E+10 | 0.00 | 0.00 | 0.00 | 0.837559E+09 | 0.00 | 0.00 | 0.00 | 3.13 |
March | 0.113013E+10 | 0.00 | 0.00 | 0.00 | 0.138127E+10 | 0.00 | 0.00 | 0.00 | 3.15 |
April | 0.213260E+09 | 0.00 | 0.00 | 0.00 | 0.313761E+10 | 0.00 | 0.00 | 0.00 | 3.15 |
May | 15981975.73 | 0.00 | 0.00 | 0.00 | 0.588472E+10 | 0.00 | 0.00 | 0.00 | 3.16 |
June | 1275726.56 | 0.00 | 0.00 | 0.00 | 0.946475E+10 | 0.00 | 0.00 | 0.00 | 3.19 |
July | 1335481.95 | 0.00 | 0.00 | 0.00 | 0.123747E+11 | 0.00 | 0.00 | 0.00 | 3.20 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.130765E+11 | 0.00 | 0.00 | 0.00 | 3.19 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.107335E+11 | 0.00 | 0.00 | 0.00 | 3.17 |
October | 21933028.89 | 0.00 | 0.00 | 0.00 | 0.696922E+10 | 0.00 | 0.00 | 0.00 | 3.15 |
November | 0.212852E+09 | 0.00 | 0.00 | 0.00 | 0.327936E+10 | 0.00 | 0.00 | 0.00 | 3.14 |
December | 0.145964E+10 | 0.00 | 0.00 | 0.00 | 0.139697E+10 | 0.00 | 0.00 | 0.00 | 3.13 |
Annual Sum or Average | 0.753209E+10 | 0.00 | 0.00 | 0.00 | 0.689199E+11 | 0.00 | 0.00 | 0.00 | 3.16 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.383656E+09 | 0.00 | 0.00 | 0.00 | 3.12 |
Maximum of Months | 0.284303E+10 | 0.00 | 0.00 | 0.00 | 0.130765E+11 | 0.00 | 0.00 | 0.00 | 3.20 |
Report: MechanicalVentilationLoadsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.327545E+10 | 0.00 | 0.00 | 0.00 | 0.442009E+09 | 0.00 | 0.00 | 0.00 | 1.70 |
February | 0.188096E+10 | 0.00 | 0.00 | 0.00 | 0.964949E+09 | 0.00 | 0.00 | 0.00 | 1.71 |
March | 0.130202E+10 | 0.00 | 0.00 | 0.00 | 0.159135E+10 | 0.00 | 0.00 | 0.00 | 1.71 |
April | 0.245696E+09 | 0.00 | 0.00 | 0.00 | 0.361483E+10 | 0.00 | 0.00 | 0.00 | 1.72 |
May | 18412783.77 | 0.00 | 0.00 | 0.00 | 0.677976E+10 | 0.00 | 0.00 | 0.00 | 1.72 |
June | 1469760.54 | 0.00 | 0.00 | 0.00 | 0.109043E+11 | 0.00 | 0.00 | 0.00 | 1.74 |
July | 1538604.54 | 0.00 | 0.00 | 0.00 | 0.142569E+11 | 0.00 | 0.00 | 0.00 | 1.74 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.150654E+11 | 0.00 | 0.00 | 0.00 | 1.74 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.123661E+11 | 0.00 | 0.00 | 0.00 | 1.73 |
October | 25268973.32 | 0.00 | 0.00 | 0.00 | 0.802922E+10 | 0.00 | 0.00 | 0.00 | 1.71 |
November | 0.245226E+09 | 0.00 | 0.00 | 0.00 | 0.377815E+10 | 0.00 | 0.00 | 0.00 | 1.71 |
December | 0.168165E+10 | 0.00 | 0.00 | 0.00 | 0.160944E+10 | 0.00 | 0.00 | 0.00 | 1.70 |
Annual Sum or Average | 0.867770E+10 | 0.00 | 0.00 | 0.00 | 0.794024E+11 | 0.00 | 0.00 | 0.00 | 1.72 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.442009E+09 | 0.00 | 0.00 | 0.00 | 1.70 |
Maximum of Months | 0.327545E+10 | 0.00 | 0.00 | 0.00 | 0.150654E+11 | 0.00 | 0.00 | 0.00 | 1.74 |
Report: MechanicalVentilationLoadsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.167017E+10 | 0.00 | 0.00 | 0.00 | 0.225382E+09 | 0.00 | 0.00 | 0.00 | 1.50 |
February | 0.959110E+09 | 0.00 | 0.00 | 0.00 | 0.492032E+09 | 0.00 | 0.00 | 0.00 | 1.51 |
March | 0.663906E+09 | 0.00 | 0.00 | 0.00 | 0.811438E+09 | 0.00 | 0.00 | 0.00 | 1.52 |
April | 0.125281E+09 | 0.00 | 0.00 | 0.00 | 0.184322E+10 | 0.00 | 0.00 | 0.00 | 1.52 |
May | 9388756.88 | 0.00 | 0.00 | 0.00 | 0.345703E+10 | 0.00 | 0.00 | 0.00 | 1.52 |
June | 749437.16 | 0.00 | 0.00 | 0.00 | 0.556015E+10 | 0.00 | 0.00 | 0.00 | 1.54 |
July | 784541.01 | 0.00 | 0.00 | 0.00 | 0.726966E+10 | 0.00 | 0.00 | 0.00 | 1.54 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.768189E+10 | 0.00 | 0.00 | 0.00 | 1.54 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.630551E+10 | 0.00 | 0.00 | 0.00 | 1.53 |
October | 12884757.14 | 0.00 | 0.00 | 0.00 | 0.409413E+10 | 0.00 | 0.00 | 0.00 | 1.51 |
November | 0.125042E+09 | 0.00 | 0.00 | 0.00 | 0.192649E+10 | 0.00 | 0.00 | 0.00 | 1.51 |
December | 0.857482E+09 | 0.00 | 0.00 | 0.00 | 0.820661E+09 | 0.00 | 0.00 | 0.00 | 1.51 |
Annual Sum or Average | 0.442479E+10 | 0.00 | 0.00 | 0.00 | 0.404876E+11 | 0.00 | 0.00 | 0.00 | 1.52 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.225382E+09 | 0.00 | 0.00 | 0.00 | 1.50 |
Maximum of Months | 0.167017E+10 | 0.00 | 0.00 | 0.00 | 0.768189E+10 | 0.00 | 0.00 | 0.00 | 1.54 |
Report: MechanicalVentilationLoadsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.132780E+09 | 0.467897E+10 | 0.00 | 49275273.72 | 0.127751E+09 | 0.00 | 0.354383E+11 | 0.00 | 38.96 |
February | 46646246.68 | 0.102364E+11 | 0.00 | 31287310.56 | 0.258920E+09 | 0.00 | 0.203763E+11 | 0.00 | 39.09 |
March | 16840824.32 | 0.167784E+11 | 0.00 | 29970032.81 | 0.527732E+09 | 0.00 | 0.141121E+11 | 0.00 | 39.29 |
April | 4632721.39 | 0.380271E+11 | 0.00 | 7465009.27 | 0.128213E+10 | 0.00 | 0.265935E+10 | 0.00 | 39.30 |
May | 0.00 | 0.715103E+11 | 0.00 | 1845517.65 | 0.221308E+10 | 0.00 | 0.198356E+09 | 0.00 | 39.45 |
June | 0.00 | 0.115164E+12 | 0.00 | 148166.17 | 0.340647E+10 | 0.00 | 15832506.80 | 0.00 | 39.81 |
July | 0.00 | 0.150484E+12 | 0.00 | 284752.11 | 0.453560E+10 | 0.00 | 16444460.02 | 0.00 | 39.86 |
August | 0.00 | 0.158813E+12 | 0.00 | 0.00 | 0.499728E+10 | 0.00 | 0.00 | 0.00 | 39.77 |
September | 0.00 | 0.130517E+12 | 0.00 | 0.00 | 0.394889E+10 | 0.00 | 0.00 | 0.00 | 39.52 |
October | 4420881.19 | 0.844228E+11 | 0.00 | 1268787.82 | 0.288800E+10 | 0.00 | 0.269059E+09 | 0.00 | 39.25 |
November | 5585616.66 | 0.397019E+11 | 0.00 | 5976566.28 | 0.138370E+10 | 0.00 | 0.265486E+10 | 0.00 | 39.12 |
December | 33126529.18 | 0.170441E+11 | 0.00 | 29531559.50 | 0.458780E+09 | 0.00 | 0.182246E+11 | 0.00 | 39.03 |
Annual Sum or Average | 0.244033E+09 | 0.837378E+12 | 0.00 | 0.157053E+09 | 0.260283E+11 | 0.00 | 0.939653E+11 | 0.00 | 39.37 |
Minimum of Months | 0.00 | 0.467897E+10 | 0.00 | 0.00 | 0.127751E+09 | 0.00 | 0.00 | 0.00 | 38.96 |
Maximum of Months | 0.132780E+09 | 0.158813E+12 | 0.00 | 49275273.72 | 0.499728E+10 | 0.00 | 0.354383E+11 | 0.00 | 39.86 |
Report: MechanicalVentilationLoadsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.169604E+11 | 760635.34 | 0.00 | 12214.21 | 0.230984E+10 | 0.00 | 0.162014E+09 | 0.00 | 7.73 |
February | 0.966913E+10 | 0.453922E+09 | 0.00 | 21125.30 | 0.459034E+10 | 0.00 | 0.163556E+09 | 0.00 | 7.76 |
March | 0.660116E+10 | 0.684559E+09 | 0.00 | 157444.96 | 0.763422E+10 | 0.00 | 0.204984E+09 | 0.00 | 7.80 |
April | 0.111706E+10 | 0.200916E+10 | 0.00 | 140356.25 | 0.168873E+11 | 0.00 | 0.167174E+09 | 0.00 | 7.81 |
May | 58919493.02 | 0.108546E+11 | 0.00 | 173491.63 | 0.245866E+11 | 0.00 | 37159638.25 | 0.00 | 7.84 |
June | 1009713.25 | 0.204745E+11 | 0.00 | 19726.85 | 0.365277E+11 | 0.00 | 6653716.83 | 0.00 | 7.92 |
July | 2958115.00 | 0.323484E+11 | 0.00 | 49684.88 | 0.421794E+11 | 0.00 | 5035238.27 | 0.00 | 7.93 |
August | 0.00 | 0.383262E+11 | 0.00 | 0.00 | 0.404278E+11 | 0.00 | 0.00 | 0.00 | 7.92 |
September | 0.00 | 0.308746E+11 | 0.00 | 0.00 | 0.337689E+11 | 0.00 | 0.00 | 0.00 | 7.86 |
October | 80289776.33 | 0.173335E+11 | 0.00 | 46750.08 | 0.246391E+11 | 0.00 | 51756751.28 | 0.00 | 7.81 |
November | 0.120849E+10 | 0.440040E+10 | 0.00 | 27531.94 | 0.153498E+11 | 0.00 | 73399670.47 | 0.00 | 7.77 |
December | 0.857542E+10 | 0.411395E+09 | 0.00 | 24413.92 | 0.800194E+10 | 0.00 | 0.215370E+09 | 0.00 | 7.75 |
Annual Sum or Average | 0.442748E+11 | 0.158172E+12 | 0.00 | 672740.02 | 0.256903E+12 | 0.00 | 0.108710E+10 | 0.00 | 7.83 |
Minimum of Months | 0.00 | 760635.34 | 0.00 | 0.00 | 0.230984E+10 | 0.00 | 0.00 | 0.00 | 7.73 |
Maximum of Months | 0.169604E+11 | 0.383262E+11 | 0.00 | 173491.63 | 0.421794E+11 | 0.00 | 0.215370E+09 | 0.00 | 7.93 |
Report: MechanicalVentilationLoadsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.548288E+11 | 0.00 | 0.00 | 0.00 | 0.739893E+10 | 0.00 | 0.00 | 0.00 | 3.58 |
February | 0.314860E+11 | 0.00 | 0.00 | 0.00 | 0.161526E+11 | 0.00 | 0.00 | 0.00 | 3.59 |
March | 0.217949E+11 | 0.00 | 0.00 | 0.00 | 0.266381E+11 | 0.00 | 0.00 | 0.00 | 3.61 |
April | 0.411278E+10 | 0.00 | 0.00 | 0.00 | 0.605098E+11 | 0.00 | 0.00 | 0.00 | 3.61 |
May | 0.308217E+09 | 0.544655E+09 | 0.00 | 0.00 | 0.112944E+12 | 0.00 | 0.00 | 0.00 | 3.63 |
June | 24602772.82 | 0.281408E+10 | 0.00 | 0.00 | 0.179717E+12 | 0.00 | 0.00 | 0.00 | 3.66 |
July | 25755173.56 | 0.517572E+10 | 0.00 | 0.00 | 0.233475E+12 | 0.00 | 0.00 | 0.00 | 3.67 |
August | 0.00 | 0.726432E+10 | 0.00 | 0.00 | 0.244919E+12 | 0.00 | 0.00 | 0.00 | 3.66 |
September | 0.00 | 0.250312E+10 | 0.00 | 0.00 | 0.204496E+12 | 0.00 | 0.00 | 0.00 | 3.63 |
October | 0.422985E+09 | 0.127245E+09 | 0.00 | 0.00 | 0.134276E+12 | 0.00 | 0.00 | 0.00 | 3.61 |
November | 0.410492E+10 | 0.00 | 0.00 | 0.00 | 0.632435E+11 | 0.00 | 0.00 | 0.00 | 3.59 |
December | 0.281497E+11 | 0.00 | 0.00 | 0.00 | 0.269409E+11 | 0.00 | 0.00 | 0.00 | 3.58 |
Annual Sum or Average | 0.145259E+12 | 0.184292E+11 | 0.00 | 0.00 | 0.131071E+13 | 0.00 | 0.00 | 0.00 | 3.62 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.739893E+10 | 0.00 | 0.00 | 0.00 | 3.58 |
Maximum of Months | 0.548288E+11 | 0.726432E+10 | 0.00 | 0.00 | 0.244919E+12 | 0.00 | 0.00 | 0.00 | 3.67 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 75908218.87 | 0.129690E+09 | 332971.11 | 5269935.39 | 16623638.93 | 7877882.52 | 0.591647E+09 | 28450.63 | 0.47 |
February | 39645854.66 | 0.242677E+09 | 400869.67 | 3729473.81 | 25318243.53 | 549132.15 | 0.334705E+09 | 20997.31 | 0.47 |
March | 24539818.91 | 0.361835E+09 | 176861.14 | 3691010.35 | 21110473.31 | 461746.95 | 0.213774E+09 | 21078.46 | 0.48 |
April | 4226854.85 | 0.760404E+09 | 303283.79 | 1333804.93 | 35162910.49 | 37042.61 | 29710500.63 | 27704.25 | 0.48 |
May | 0.00 | 0.134573E+10 | 180187.62 | 97203.89 | 31441328.78 | 0.00 | 329019.09 | 7249.04 | 0.48 |
June | 0.00 | 0.208681E+10 | 124711.12 | 4764.53 | 41770513.01 | 0.00 | 9901.18 | 398.42 | 0.48 |
July | 0.00 | 0.270214E+10 | 0.00 | 0.00 | 43788025.37 | 0.00 | 0.00 | 0.00 | 0.48 |
August | 0.00 | 0.285954E+10 | 0.00 | 0.00 | 45063253.13 | 0.00 | 0.00 | 0.00 | 0.48 |
September | 0.00 | 0.236234E+10 | 72972.67 | 0.00 | 51912482.50 | 0.00 | 0.00 | 799.24 | 0.48 |
October | 166719.98 | 0.157134E+10 | 884971.99 | 311948.50 | 51457223.72 | 8438.62 | 1149322.45 | 25110.82 | 0.48 |
November | 1507405.23 | 0.845842E+09 | 923140.98 | 578433.04 | 44882198.40 | 17593.33 | 26532210.89 | 48153.48 | 0.48 |
December | 30242629.52 | 0.367064E+09 | 568573.11 | 3617591.06 | 32851273.27 | 1073091.98 | 0.298348E+09 | 54694.77 | 0.47 |
Annual Sum or Average | 0.176238E+09 | 0.156354E+11 | 3968543.20 | 18634165.51 | 0.441382E+09 | 10024928.16 | 0.149621E+10 | 234636.44 | 0.48 |
Minimum of Months | 0.00 | 0.129690E+09 | 0.00 | 0.00 | 16623638.93 | 0.00 | 0.00 | 0.00 | 0.47 |
Maximum of Months | 75908218.87 | 0.285954E+10 | 923140.98 | 5269935.39 | 51912482.50 | 7877882.52 | 0.591647E+09 | 54694.77 | 0.48 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 90368132.99 | 0.114305E+09 | 319199.73 | 3737949.79 | 31984478.24 | 41495163.16 | 0.545022E+09 | 48896.21 | 0.47 |
February | 42748904.57 | 0.232745E+09 | 441604.21 | 2953356.58 | 35176710.61 | 1095455.95 | 0.331788E+09 | 22428.72 | 0.47 |
March | 27043162.20 | 0.356687E+09 | 204188.60 | 3280882.40 | 26183173.83 | 460087.96 | 0.211654E+09 | 24984.76 | 0.48 |
April | 4330625.67 | 0.759094E+09 | 338444.09 | 1285979.44 | 36343991.23 | 37038.27 | 29650422.77 | 28195.79 | 0.48 |
May | 0.00 | 0.134684E+10 | 180541.85 | 97947.71 | 30165337.32 | 0.00 | 328225.34 | 6872.85 | 0.48 |
June | 0.00 | 0.208876E+10 | 89924.01 | 4797.86 | 39602404.79 | 0.00 | 9866.14 | 303.23 | 0.48 |
July | 0.00 | 0.270294E+10 | 0.00 | 0.00 | 42666264.35 | 0.00 | 0.00 | 0.00 | 0.48 |
August | 0.00 | 0.285923E+10 | 0.00 | 0.00 | 45033331.72 | 0.00 | 0.00 | 0.00 | 0.48 |
September | 0.00 | 0.235686E+10 | 518938.66 | 0.00 | 56662843.52 | 0.00 | 0.00 | 3111.16 | 0.48 |
October | 246727.86 | 0.155615E+10 | 1412873.31 | 252135.35 | 65921336.18 | 8437.63 | 1128936.98 | 40984.37 | 0.48 |
November | 1602870.02 | 0.829401E+09 | 1094902.27 | 489967.00 | 61024790.24 | 17591.27 | 26521859.12 | 70659.82 | 0.48 |
December | 33514424.68 | 0.348303E+09 | 861168.20 | 2739738.82 | 51241571.12 | 945758.24 | 0.296042E+09 | 85302.20 | 0.47 |
Annual Sum or Average | 0.199855E+09 | 0.155513E+11 | 5461784.93 | 14842754.94 | 0.522006E+09 | 44059532.48 | 0.144215E+10 | 331739.11 | 0.48 |
Minimum of Months | 0.00 | 0.114305E+09 | 0.00 | 0.00 | 26183173.83 | 0.00 | 0.00 | 0.00 | 0.47 |
Maximum of Months | 90368132.99 | 0.285923E+10 | 1412873.31 | 3737949.79 | 65921336.18 | 41495163.16 | 0.545022E+09 | 85302.20 | 0.48 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.196297E+10 | 0.198878E+10 | 0.00 | 59044057.47 | 0.00 | 0.00 | 0.720771E+10 | 0.00 | 0.54 |
February | 0.113571E+10 | 0.363950E+10 | 0.00 | 35422232.67 | 0.00 | 0.00 | 0.396275E+10 | 0.00 | 0.54 |
March | 0.649160E+09 | 0.519509E+10 | 0.00 | 30955919.55 | 0.00 | 0.00 | 0.260751E+10 | 0.00 | 0.54 |
April | 50806595.57 | 0.107885E+11 | 0.00 | 11715530.11 | 3149821.34 | 0.00 | 0.416225E+09 | 0.00 | 0.55 |
May | 0.00 | 0.186757E+11 | 0.00 | 776522.55 | 0.00 | 0.00 | 5002678.87 | 0.00 | 0.55 |
June | 0.00 | 0.288634E+11 | 0.00 | 23321.33 | 0.00 | 0.00 | 175532.60 | 0.00 | 0.55 |
July | 0.00 | 0.372324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.55 |
August | 0.00 | 0.393839E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.55 |
September | 0.00 | 0.327361E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.55 |
October | 0.00 | 0.220161E+11 | 0.00 | 4045504.63 | 0.00 | 0.00 | 18143012.44 | 0.00 | 0.54 |
November | 50956318.46 | 0.120906E+11 | 0.00 | 5744501.84 | 0.00 | 0.00 | 0.331573E+09 | 0.00 | 0.54 |
December | 0.700105E+09 | 0.542962E+10 | 0.00 | 37609920.09 | 1315131.00 | 0.00 | 0.378128E+10 | 0.00 | 0.54 |
Annual Sum or Average | 0.454971E+10 | 0.218040E+12 | 0.00 | 0.185338E+09 | 4464952.34 | 0.00 | 0.183304E+11 | 0.00 | 0.55 |
Minimum of Months | 0.00 | 0.198878E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.54 |
Maximum of Months | 0.196297E+10 | 0.393839E+11 | 0.00 | 59044057.47 | 3149821.34 | 0.00 | 0.720771E+10 | 0.00 | 0.55 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.128050E+10 | 0.124992E+10 | 4211007.71 | 67087254.52 | 0.734871E+09 | 16474172.23 | 0.786818E+10 | 325342.56 | 0.54 |
February | 0.657369E+09 | 0.278126E+10 | 5242181.56 | 46252824.80 | 0.853669E+09 | 5616583.74 | 0.442605E+10 | 323023.80 | 0.54 |
March | 0.424376E+09 | 0.429036E+10 | 1655113.60 | 43255777.51 | 0.904348E+09 | 3802187.49 | 0.281709E+10 | 143889.04 | 0.54 |
April | 65237177.73 | 0.977218E+10 | 3823946.26 | 14763589.92 | 0.101840E+10 | 476256.58 | 0.398401E+09 | 210379.27 | 0.54 |
May | 0.00 | 0.176761E+11 | 901816.76 | 1016712.46 | 0.100381E+10 | 0.00 | 4764069.27 | 8694.21 | 0.54 |
June | 0.00 | 0.274636E+11 | 0.00 | 40612.43 | 0.140764E+10 | 0.00 | 158295.87 | 0.00 | 0.55 |
July | 0.00 | 0.355561E+11 | 0.00 | 0.00 | 0.168647E+10 | 0.00 | 0.00 | 0.00 | 0.55 |
August | 0.00 | 0.375167E+11 | 0.00 | 0.00 | 0.187795E+10 | 0.00 | 0.00 | 0.00 | 0.55 |
September | 0.00 | 0.307939E+11 | 0.00 | 0.00 | 0.195116E+10 | 0.00 | 0.00 | 0.00 | 0.55 |
October | 3823697.82 | 0.201904E+11 | 2810671.50 | 2483809.83 | 0.182882E+10 | 95206.16 | 15791870.67 | 43273.77 | 0.54 |
November | 21310814.54 | 0.103230E+11 | 11157417.09 | 6467868.75 | 0.175940E+10 | 37281.42 | 0.360564E+09 | 343137.66 | 0.54 |
December | 0.487835E+09 | 0.402597E+10 | 9294231.77 | 45444458.41 | 0.139677E+10 | 6177184.81 | 0.398077E+10 | 389614.39 | 0.54 |
Annual Sum or Average | 0.294045E+10 | 0.201639E+12 | 39096386.25 | 0.226813E+09 | 0.164233E+11 | 32678872.44 | 0.198718E+11 | 1787354.70 | 0.54 |
Minimum of Months | 0.00 | 0.124992E+10 | 0.00 | 0.00 | 0.734871E+09 | 0.00 | 0.00 | 0.00 | 0.54 |
Maximum of Months | 0.128050E+10 | 0.375167E+11 | 11157417.09 | 67087254.52 | 0.195116E+10 | 16474172.23 | 0.786818E+10 | 389614.39 | 0.55 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 72776719.60 | 0.131619E+09 | 297531.21 | 5566555.26 | 14718767.41 | 16024202.47 | 0.586335E+09 | 39342.68 | 0.47 |
February | 36752220.04 | 0.243518E+09 | 596527.18 | 3945708.10 | 24269925.37 | 575245.79 | 0.337357E+09 | 33333.75 | 0.47 |
March | 24320684.53 | 0.363103E+09 | 523754.95 | 3739903.76 | 19489755.67 | 468336.29 | 0.213937E+09 | 27466.51 | 0.48 |
April | 3663700.88 | 0.769016E+09 | 306055.50 | 1476738.70 | 26562901.22 | 16188.14 | 30151575.30 | 12468.59 | 0.48 |
May | 0.00 | 0.135315E+10 | 0.00 | 105985.14 | 24208526.54 | 0.00 | 320237.84 | 0.00 | 0.48 |
June | 0.00 | 0.209563E+10 | 0.00 | 4619.17 | 33078983.61 | 0.00 | 10046.54 | 0.00 | 0.48 |
July | 0.00 | 0.271069E+10 | 0.00 | 0.00 | 35243022.52 | 0.00 | 0.00 | 0.00 | 0.48 |
August | 0.00 | 0.287013E+10 | 0.00 | 0.00 | 34473568.72 | 0.00 | 0.00 | 0.00 | 0.48 |
September | 0.00 | 0.237280E+10 | 0.00 | 0.00 | 41529472.69 | 0.00 | 0.00 | 0.00 | 0.48 |
October | 68965.43 | 0.158709E+10 | 28112.21 | 408938.53 | 36588834.67 | 0.00 | 1158525.59 | 152.45 | 0.48 |
November | 1235373.18 | 0.855401E+09 | 447589.57 | 627565.54 | 35832284.31 | 11240.41 | 26761463.37 | 14921.76 | 0.48 |
December | 28867520.44 | 0.369055E+09 | 915014.68 | 3749557.95 | 30512864.36 | 970184.04 | 0.299694E+09 | 54849.46 | 0.47 |
Annual Sum or Average | 0.167685E+09 | 0.157212E+11 | 3114585.30 | 19625572.16 | 0.356509E+09 | 18065397.14 | 0.149573E+10 | 182535.21 | 0.48 |
Minimum of Months | 0.00 | 0.131619E+09 | 0.00 | 0.00 | 14718767.41 | 0.00 | 0.00 | 0.00 | 0.47 |
Maximum of Months | 72776719.60 | 0.287013E+10 | 915014.68 | 5566555.26 | 41529472.69 | 16024202.47 | 0.586335E+09 | 54849.46 | 0.48 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 91349680.95 | 0.108291E+09 | 370979.31 | 3963508.18 | 37953893.42 | 55436364.72 | 0.529874E+09 | 41951.42 | 0.47 |
February | 43186588.46 | 0.232341E+09 | 547373.22 | 3060311.19 | 35452495.19 | 1498168.89 | 0.330840E+09 | 45671.24 | 0.47 |
March | 28306924.43 | 0.359604E+09 | 674126.67 | 3312914.81 | 22773995.89 | 464782.44 | 0.210353E+09 | 46688.76 | 0.48 |
April | 3698407.16 | 0.766168E+09 | 304303.89 | 1423579.11 | 29317749.36 | 16186.25 | 30165893.63 | 14182.89 | 0.48 |
May | 0.00 | 0.135354E+10 | 0.00 | 106730.92 | 23655263.83 | 0.00 | 319442.13 | 0.00 | 0.48 |
June | 0.00 | 0.209744E+10 | 0.00 | 4652.72 | 31020542.79 | 0.00 | 10011.27 | 0.00 | 0.48 |
July | 0.00 | 0.271192E+10 | 0.00 | 0.00 | 33694104.92 | 0.00 | 0.00 | 0.00 | 0.48 |
August | 0.00 | 0.286882E+10 | 0.00 | 0.00 | 35445781.51 | 0.00 | 0.00 | 0.00 | 0.48 |
September | 0.00 | 0.236678E+10 | 0.00 | 0.00 | 47258039.60 | 0.00 | 0.00 | 0.00 | 0.48 |
October | 115832.43 | 0.157804E+10 | 27438.94 | 345027.45 | 45457016.28 | 0.00 | 1175377.94 | 822.41 | 0.48 |
November | 1438601.88 | 0.841947E+09 | 1116052.21 | 529175.11 | 48479965.90 | 11239.09 | 26653271.32 | 48156.23 | 0.48 |
December | 35005726.28 | 0.344563E+09 | 1146885.49 | 2803796.05 | 54691929.74 | 5157050.21 | 0.290276E+09 | 89632.69 | 0.47 |
Annual Sum or Average | 0.203102E+09 | 0.156294E+11 | 4187159.73 | 15549695.55 | 0.445201E+09 | 62583791.60 | 0.141967E+10 | 287105.62 | 0.48 |
Minimum of Months | 0.00 | 0.108291E+09 | 0.00 | 0.00 | 22773995.89 | 0.00 | 0.00 | 0.00 | 0.47 |
Maximum of Months | 91349680.95 | 0.286882E+10 | 1146885.49 | 3963508.18 | 54691929.74 | 55436364.72 | 0.529874E+09 | 89632.69 | 0.48 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.150607E+11 | 0.00 | 0.00 | 0.00 | 0.203238E+10 | 0.00 | 0.00 | 0.00 | 1.07 |
February | 0.864874E+10 | 0.00 | 0.00 | 0.00 | 0.443688E+10 | 0.00 | 0.00 | 0.00 | 1.08 |
March | 0.598675E+10 | 0.00 | 0.00 | 0.00 | 0.731711E+10 | 0.00 | 0.00 | 0.00 | 1.08 |
April | 0.112972E+10 | 0.00 | 0.00 | 0.00 | 0.166212E+11 | 0.00 | 0.00 | 0.00 | 1.08 |
May | 84662779.48 | 0.00 | 0.00 | 0.00 | 0.311737E+11 | 0.00 | 0.00 | 0.00 | 1.09 |
June | 6758022.82 | 0.00 | 0.00 | 0.00 | 0.501385E+11 | 0.00 | 0.00 | 0.00 | 1.10 |
July | 7074570.49 | 0.00 | 0.00 | 0.00 | 0.655539E+11 | 0.00 | 0.00 | 0.00 | 1.10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.692712E+11 | 0.00 | 0.00 | 0.00 | 1.10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.568597E+11 | 0.00 | 0.00 | 0.00 | 1.09 |
October | 0.116188E+09 | 0.00 | 0.00 | 0.00 | 0.369187E+11 | 0.00 | 0.00 | 0.00 | 1.08 |
November | 0.112756E+10 | 0.00 | 0.00 | 0.00 | 0.173721E+11 | 0.00 | 0.00 | 0.00 | 1.08 |
December | 0.773231E+10 | 0.00 | 0.00 | 0.00 | 0.740028E+10 | 0.00 | 0.00 | 0.00 | 1.07 |
Annual Sum or Average | 0.399004E+11 | 0.00 | 0.00 | 0.00 | 0.365096E+12 | 0.00 | 0.00 | 0.00 | 1.09 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.203238E+10 | 0.00 | 0.00 | 0.00 | 1.07 |
Maximum of Months | 0.150607E+11 | 0.00 | 0.00 | 0.00 | 0.692712E+11 | 0.00 | 0.00 | 0.00 | 1.10 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 17966665.31 | 32938011.58 | 64842.39 | 1273540.85 | 3662023.19 | 17845129.13 | 0.133090E+09 | 3879.82 | 0.47 |
February | 9727948.43 | 61509329.64 | 76032.97 | 922071.18 | 5515715.07 | 3207430.60 | 80800025.34 | 3303.75 | 0.48 |
March | 5938293.55 | 91271333.45 | 44556.17 | 927640.16 | 4465155.82 | 556997.76 | 53193664.17 | 4928.73 | 0.48 |
April | 1044793.60 | 0.191471E+09 | 61754.85 | 337151.31 | 7435972.75 | 9260.65 | 7435845.20 | 6003.93 | 0.48 |
May | 0.00 | 0.337518E+09 | 20930.71 | 24967.31 | 6798839.56 | 0.00 | 81588.43 | 1207.54 | 0.48 |
June | 0.00 | 0.523532E+09 | 0.00 | 1247.47 | 8644814.65 | 0.00 | 2418.96 | 0.00 | 0.48 |
July | 0.00 | 0.677706E+09 | 0.00 | 0.00 | 8777667.07 | 0.00 | 0.00 | 0.00 | 0.48 |
August | 0.00 | 0.716934E+09 | 0.00 | 0.00 | 9218189.77 | 0.00 | 0.00 | 0.00 | 0.48 |
September | 0.00 | 0.592253E+09 | 18059.97 | 0.00 | 11310128.98 | 0.00 | 0.00 | 383.00 | 0.48 |
October | 39966.07 | 0.393855E+09 | 185675.63 | 84726.06 | 11880962.77 | 2109.65 | 282305.61 | 6094.49 | 0.48 |
November | 388422.50 | 0.212751E+09 | 203461.34 | 136648.79 | 9960774.85 | 4398.33 | 6629441.00 | 9060.61 | 0.48 |
December | 7225731.71 | 92787506.46 | 145632.15 | 871346.90 | 7191643.38 | 2149385.19 | 73073841.23 | 9749.73 | 0.47 |
Annual Sum or Average | 42331821.17 | 0.392452E+10 | 820946.17 | 4579340.01 | 94861887.86 | 23774711.32 | 0.354590E+09 | 44611.62 | 0.48 |
Minimum of Months | 0.00 | 32938011.58 | 0.00 | 0.00 | 3662023.19 | 0.00 | 0.00 | 0.00 | 0.47 |
Maximum of Months | 17966665.31 | 0.716934E+09 | 203461.34 | 1273540.85 | 11880962.77 | 17845129.13 | 0.133090E+09 | 9749.73 | 0.48 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 21603605.83 | 30803736.91 | 72908.50 | 883348.72 | 5780377.89 | 39557287.03 | 0.108112E+09 | 7437.39 | 0.47 |
February | 10378288.97 | 59559173.62 | 63635.98 | 723169.07 | 7470167.16 | 7530754.37 | 76014172.62 | 3542.42 | 0.48 |
March | 6222915.83 | 90682734.47 | 44941.32 | 826660.08 | 5042260.73 | 568470.25 | 52991447.37 | 4814.93 | 0.48 |
April | 1079178.37 | 0.191039E+09 | 61532.93 | 325175.74 | 7844097.66 | 9259.57 | 7412402.86 | 6217.91 | 0.48 |
May | 0.00 | 0.337731E+09 | 20870.42 | 25153.53 | 6545552.84 | 0.00 | 81389.73 | 1265.24 | 0.48 |
June | 0.00 | 0.523964E+09 | 0.00 | 1255.79 | 8150623.07 | 0.00 | 2410.21 | 0.00 | 0.48 |
July | 0.00 | 0.677745E+09 | 0.00 | 0.00 | 8658058.99 | 0.00 | 0.00 | 0.00 | 0.48 |
August | 0.00 | 0.716690E+09 | 0.00 | 0.00 | 9377076.94 | 0.00 | 0.00 | 0.00 | 0.48 |
September | 0.00 | 0.591171E+09 | 46413.36 | 0.00 | 12292834.53 | 0.00 | 0.00 | 529.32 | 0.48 |
October | 59544.40 | 0.391180E+09 | 218895.20 | 67823.15 | 14472594.32 | 2109.41 | 279582.49 | 8598.85 | 0.48 |
November | 400717.51 | 0.208980E+09 | 191605.12 | 115293.80 | 13710824.43 | 4397.82 | 6637662.73 | 15198.64 | 0.48 |
December | 8086533.15 | 89582256.83 | 189798.93 | 648249.63 | 10332898.13 | 6176273.01 | 68399487.04 | 17845.60 | 0.47 |
Annual Sum or Average | 47830784.07 | 0.390913E+10 | 910601.76 | 3616129.51 | 0.109677E+09 | 53848551.45 | 0.319930E+09 | 65450.29 | 0.48 |
Minimum of Months | 0.00 | 30803736.91 | 0.00 | 0.00 | 5042260.73 | 0.00 | 0.00 | 0.00 | 0.47 |
Maximum of Months | 21603605.83 | 0.716690E+09 | 218895.20 | 883348.72 | 14472594.32 | 39557287.03 | 0.108112E+09 | 17845.60 | 0.48 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.100014E+09 | 0.220791E+09 | 220143.20 | 12290616.03 | 14557633.90 | 1791385.02 | 0.979197E+09 | 9543.06 | 0.54 |
February | 59186014.54 | 0.404757E+09 | 283994.88 | 7720326.51 | 26051291.74 | 610734.75 | 0.540609E+09 | 19192.43 | 0.54 |
March | 37350968.80 | 0.586562E+09 | 157051.39 | 6467597.87 | 28642020.53 | 507286.48 | 0.345105E+09 | 15198.22 | 0.54 |
April | 6769165.38 | 0.122610E+10 | 527233.05 | 2053460.80 | 51637768.12 | 72705.26 | 47813962.05 | 47182.49 | 0.54 |
May | 0.00 | 0.215335E+10 | 405969.78 | 142431.77 | 58430736.72 | 0.00 | 542134.49 | 13878.23 | 0.54 |
June | 0.00 | 0.333809E+10 | 365132.61 | 6408.56 | 80510641.89 | 0.00 | 17146.37 | 2393.34 | 0.55 |
July | 0.00 | 0.433010E+10 | 0.00 | 0.00 | 80201126.56 | 0.00 | 0.00 | 0.00 | 0.55 |
August | 0.00 | 0.458400E+10 | 0.00 | 0.00 | 81158981.75 | 0.00 | 0.00 | 0.00 | 0.55 |
September | 0.00 | 0.379261E+10 | 227996.98 | 0.00 | 84863065.97 | 0.00 | 0.00 | 124.78 | 0.55 |
October | 197719.69 | 0.253918E+10 | 160827.08 | 596939.15 | 68529955.92 | 13553.45 | 1820093.77 | 4778.23 | 0.54 |
November | 2259431.00 | 0.138594E+10 | 265920.53 | 1058639.32 | 45953683.77 | 0.00 | 42674274.68 | 15046.24 | 0.54 |
December | 42391862.86 | 0.611973E+09 | 610559.08 | 7891890.07 | 30707250.23 | 1459889.80 | 0.483547E+09 | 22735.71 | 0.54 |
Annual Sum or Average | 0.248169E+09 | 0.251734E+11 | 3224828.58 | 38228310.07 | 0.651244E+09 | 4455554.77 | 0.244132E+10 | 150072.72 | 0.54 |
Minimum of Months | 0.00 | 0.220791E+09 | 0.00 | 0.00 | 14557633.90 | 0.00 | 0.00 | 0.00 | 0.54 |
Maximum of Months | 0.100014E+09 | 0.458400E+10 | 610559.08 | 12290616.03 | 84863065.97 | 1791385.02 | 0.979197E+09 | 47182.49 | 0.55 |
Report: MechanicalVentilationLoadsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.959831E+10 | 0.794047E+09 | 0.00 | 8634894.06 | 0.267541E+10 | 0.00 | 0.161030E+11 | 0.00 | 8.61 |
February | 0.458011E+10 | 0.333994E+10 | 0.00 | 6256444.07 | 0.423422E+10 | 0.00 | 0.101778E+11 | 0.00 | 8.64 |
March | 0.277315E+10 | 0.582307E+10 | 0.00 | 8398526.89 | 0.666790E+10 | 0.00 | 0.743837E+10 | 0.00 | 8.69 |
April | 0.383004E+09 | 0.153402E+11 | 0.00 | 3905784.01 | 0.130336E+11 | 0.00 | 0.154163E+10 | 0.00 | 8.70 |
May | 7654082.43 | 0.373632E+11 | 0.00 | 1322552.04 | 0.158530E+11 | 0.00 | 0.135550E+09 | 0.00 | 8.74 |
June | 0.00 | 0.655940E+11 | 0.00 | 144833.09 | 0.199970E+11 | 0.00 | 11391728.35 | 0.00 | 8.82 |
July | 0.00 | 0.928275E+11 | 0.00 | 304383.63 | 0.190790E+11 | 0.00 | 11772553.56 | 0.00 | 8.84 |
August | 0.00 | 0.968553E+11 | 0.00 | 0.00 | 0.213970E+11 | 0.00 | 0.00 | 0.00 | 8.82 |
September | 0.00 | 0.721478E+11 | 0.00 | 0.00 | 0.249170E+11 | 0.00 | 0.00 | 0.00 | 8.76 |
October | 28317767.71 | 0.400649E+11 | 0.00 | 588566.71 | 0.229587E+11 | 0.00 | 0.169437E+09 | 0.00 | 8.69 |
November | 0.585921E+09 | 0.145348E+11 | 0.00 | 1893390.16 | 0.151209E+11 | 0.00 | 0.133704E+10 | 0.00 | 8.65 |
December | 0.384855E+10 | 0.469218E+10 | 0.00 | 6257660.31 | 0.794077E+10 | 0.00 | 0.934495E+10 | 0.00 | 8.63 |
Annual Sum or Average | 0.218050E+11 | 0.449377E+12 | 0.00 | 37707034.97 | 0.173874E+12 | 0.00 | 0.462709E+11 | 0.00 | 8.72 |
Minimum of Months | 0.00 | 0.794047E+09 | 0.00 | 0.00 | 0.267541E+10 | 0.00 | 0.00 | 0.00 | 8.61 |
Maximum of Months | 0.959831E+10 | 0.968553E+11 | 0.00 | 8634894.06 | 0.249170E+11 | 0.00 | 0.161030E+11 | 0.00 | 8.84 |
Report: MechanicalVentilationLoadsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.854056E+10 | 0.120110E+10 | 0.00 | 11262379.43 | 0.242887E+10 | 0.00 | 0.183476E+11 | 0.00 | 9.01 |
February | 0.388306E+10 | 0.411983E+10 | 0.00 | 8195444.12 | 0.380475E+10 | 0.00 | 0.115560E+11 | 0.00 | 9.04 |
March | 0.233451E+10 | 0.687555E+10 | 0.00 | 10670994.56 | 0.619332E+10 | 0.00 | 0.834757E+10 | 0.00 | 9.09 |
April | 0.267339E+09 | 0.192299E+11 | 0.00 | 4735645.01 | 0.104566E+11 | 0.00 | 0.174569E+10 | 0.00 | 9.10 |
May | 6658090.46 | 0.452846E+11 | 0.00 | 1518798.93 | 0.103937E+11 | 0.00 | 0.143037E+09 | 0.00 | 9.14 |
June | 0.00 | 0.780945E+11 | 0.00 | 162047.08 | 0.114564E+11 | 0.00 | 11908255.58 | 0.00 | 9.23 |
July | 0.00 | 0.105428E+12 | 0.00 | 337342.36 | 0.116554E+11 | 0.00 | 12298336.64 | 0.00 | 9.25 |
August | 0.00 | 0.110751E+12 | 0.00 | 0.00 | 0.129720E+11 | 0.00 | 0.00 | 0.00 | 9.23 |
September | 0.00 | 0.843654E+11 | 0.00 | 0.00 | 0.171901E+11 | 0.00 | 0.00 | 0.00 | 9.16 |
October | 19819695.00 | 0.467235E+11 | 0.00 | 716617.47 | 0.192159E+11 | 0.00 | 0.186983E+09 | 0.00 | 9.09 |
November | 0.371562E+09 | 0.169354E+11 | 0.00 | 2404254.50 | 0.140924E+11 | 0.00 | 0.163994E+10 | 0.00 | 9.06 |
December | 0.335338E+10 | 0.607695E+10 | 0.00 | 8109146.78 | 0.714047E+10 | 0.00 | 0.104490E+11 | 0.00 | 9.03 |
Annual Sum or Average | 0.187769E+11 | 0.525086E+12 | 0.00 | 48112670.24 | 0.127000E+12 | 0.00 | 0.524400E+11 | 0.00 | 9.12 |
Minimum of Months | 0.00 | 0.120110E+10 | 0.00 | 0.00 | 0.242887E+10 | 0.00 | 0.00 | 0.00 | 9.01 |
Maximum of Months | 0.854056E+10 | 0.110751E+12 | 0.00 | 11262379.43 | 0.192159E+11 | 0.00 | 0.183476E+11 | 0.00 | 9.25 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.342337E+10 | 0.00 | 67190145.21 | 0.00 | 0.00 | 0.252792E+11 | 0.00 | 27.41 |
February | 0.00 | 0.747346E+10 | 0.00 | 44953652.19 | 0.00 | 0.00 | 0.145107E+11 | 0.00 | 27.51 |
March | 0.00 | 0.123279E+11 | 0.00 | 39941115.66 | 0.00 | 0.00 | 0.100353E+11 | 0.00 | 27.66 |
April | 0.00 | 0.280080E+11 | 0.00 | 10698334.48 | 0.00 | 0.00 | 0.189035E+10 | 0.00 | 27.69 |
May | 0.00 | 0.525389E+11 | 0.00 | 2406597.09 | 0.00 | 0.00 | 0.140058E+09 | 0.00 | 27.81 |
June | 0.00 | 0.845006E+11 | 0.00 | 209701.79 | 0.00 | 0.00 | 11162204.66 | 0.00 | 28.07 |
July | 0.00 | 0.110486E+12 | 0.00 | 328795.04 | 0.00 | 0.00 | 11575774.68 | 0.00 | 28.12 |
August | 0.00 | 0.116759E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.06 |
September | 0.00 | 0.958257E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.87 |
October | 0.00 | 0.622080E+11 | 0.00 | 2512573.52 | 0.00 | 0.00 | 0.193029E+09 | 0.00 | 27.67 |
November | 0.00 | 0.292671E+11 | 0.00 | 7800269.40 | 0.00 | 0.00 | 0.188960E+10 | 0.00 | 27.55 |
December | 0.00 | 0.124643E+11 | 0.00 | 39646606.01 | 0.00 | 0.00 | 0.129732E+11 | 0.00 | 27.47 |
Annual Sum or Average | 0.00 | 0.615282E+12 | 0.00 | 0.215688E+09 | 0.00 | 0.00 | 0.669342E+11 | 0.00 | 27.74 |
Minimum of Months | 0.00 | 0.342337E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.41 |
Maximum of Months | 0.00 | 0.116759E+12 | 0.00 | 67190145.21 | 0.00 | 0.00 | 0.252792E+11 | 0.00 | 28.12 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.905041E+10 | 0.00 | 0.00 | 0.00 | 0.122132E+10 | 0.00 | 0.00 | 0.00 | 2.43 |
February | 0.519729E+10 | 0.00 | 0.00 | 0.00 | 0.266626E+10 | 0.00 | 0.00 | 0.00 | 2.44 |
March | 0.359762E+10 | 0.00 | 0.00 | 0.00 | 0.439707E+10 | 0.00 | 0.00 | 0.00 | 2.45 |
April | 0.678884E+09 | 0.00 | 0.00 | 0.00 | 0.998816E+10 | 0.00 | 0.00 | 0.00 | 2.46 |
May | 50876438.05 | 0.00 | 0.00 | 0.00 | 0.187332E+11 | 0.00 | 0.00 | 0.00 | 2.47 |
June | 4061101.36 | 0.00 | 0.00 | 0.00 | 0.301297E+11 | 0.00 | 0.00 | 0.00 | 2.49 |
July | 4251324.48 | 0.00 | 0.00 | 0.00 | 0.393933E+11 | 0.00 | 0.00 | 0.00 | 2.50 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.416272E+11 | 0.00 | 0.00 | 0.00 | 2.49 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.341687E+11 | 0.00 | 0.00 | 0.00 | 2.47 |
October | 69820803.40 | 0.00 | 0.00 | 0.00 | 0.221856E+11 | 0.00 | 0.00 | 0.00 | 2.46 |
November | 0.677586E+09 | 0.00 | 0.00 | 0.00 | 0.104394E+11 | 0.00 | 0.00 | 0.00 | 2.44 |
December | 0.464658E+10 | 0.00 | 0.00 | 0.00 | 0.444705E+10 | 0.00 | 0.00 | 0.00 | 2.44 |
Annual Sum or Average | 0.239774E+11 | 0.00 | 0.00 | 0.00 | 0.219397E+12 | 0.00 | 0.00 | 0.00 | 2.46 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.122132E+10 | 0.00 | 0.00 | 0.00 | 2.43 |
Maximum of Months | 0.905041E+10 | 0.00 | 0.00 | 0.00 | 0.416272E+11 | 0.00 | 0.00 | 0.00 | 2.50 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:58:09
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.130531E+12 | 0.350651E+10 | 0.271457E+11 | 0.192419E+12 | 0.897000E+12 |
February | 0.155004E+12 | -161079898.3 | 0.128027E+11 | -0.181019E+11 | 0.102964E+13 |
March | 0.202952E+12 | -0.308815E+10 | 0.226237E+10 | -0.197928E+12 | 0.133963E+13 |
April | 0.224792E+12 | -0.112913E+11 | -0.333198E+11 | -0.698460E+12 | 0.172720E+13 |
May | 0.240336E+12 | -0.226029E+11 | -0.780942E+11 | -0.143130E+13 | 0.231747E+13 |
June | 0.237419E+12 | -0.337755E+11 | -0.128220E+12 | -0.218658E+13 | 0.280813E+13 |
July | 0.230122E+12 | -0.432023E+11 | -0.166803E+12 | -0.283230E+13 | 0.334154E+13 |
August | 0.224813E+12 | -0.454711E+11 | -0.178637E+12 | -0.297422E+13 | 0.346035E+13 |
September | 0.183669E+12 | -0.377401E+11 | -0.144544E+12 | -0.242707E+13 | 0.297147E+13 |
October | 0.141217E+12 | -0.255963E+11 | -0.877489E+11 | -0.161062E+13 | 0.241332E+13 |
November | 0.107027E+12 | -0.117125E+11 | -0.328496E+11 | -0.710746E+12 | 0.173905E+13 |
December | 0.110502E+12 | -0.206651E+10 | 0.555616E+10 | -0.133201E+12 | 0.125273E+13 |
Annual Sum or Average | 0.218839E+13 | -0.233201E+12 | -0.802449E+12 | -0.150281E+14 | 0.252975E+14 |
Minimum of Months | 0.107027E+12 | -0.454711E+11 | -0.178637E+12 | -0.297422E+13 | 0.897000E+12 |
Maximum of Months | 0.240336E+12 | 0.350651E+10 | 0.271457E+11 | 0.192419E+12 | 0.346035E+13 |