Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:58
Tabular Output Report in Format: HTML
Building: HotelLarge
Environment: RUNPERIOD 1 ** Miami Intl Ap FL USA TMY3 WMO#=722020
Simulation Timestamp: 2023-10-16 08:58:20
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:58:20
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 17016.64 | 1499.89 | 1499.89 |
Net Site Energy | 17016.64 | 1499.89 | 1499.89 |
Total Source Energy | 43723.16 | 3853.86 | 3853.86 |
Net Source Energy | 43723.16 | 3853.86 | 3853.86 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 11345.29 |
Net Conditioned Building Area | 11345.29 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 468.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 5293.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1174.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 262.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1751.30 | 1788.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 679.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1826.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 459.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 520.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 90.77 | 2623.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Refrigeration | 75.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 12134.96 | 4881.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 468.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 5293.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 1174.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 262.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 959.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 762.04 | 1198.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 16.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 13.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 590.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 32.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 616.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 30.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 1826.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 459.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 520.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 90.77 | 2623.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5742.51 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4114.69 | |
Refrigeration | General | 18.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 22.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 34.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 468.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 5293.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 1174.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 262.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 1751.30 | 1788.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 679.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 1826.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 459.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 520.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 90.77 | 2623.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Refrigeration | Unassigned | 75.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 126.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 676.15 | 272.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Other | 266.82 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 1069.60 | 430.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 126.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 676.15 | 272.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Other | 266.82 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 1069.60 | 430.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 12134.962 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 12134.962 | 100.00 |
Total On-Site and Utility Electric Sources | 12134.962 | 100.00 |
Total Electricity End Uses | 12134.962 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | 0.00 |
Air to Air Heat Recovery for Cooling | 7902.48 | 98.99 |
Air to Air Heat Recovery for Heating | 80.71 | 1.01 |
High-Temperature Geothermal* | 0.00 | 0.00 |
Solar Water Thermal | 0.00 | 0.00 |
Solar Air Thermal | 0.00 | 0.00 |
Total On-Site Thermal Sources | 7983.19 | 100.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 9857.19 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 9857.19 | 100.00 |
Total Water End Uses | 9857.19 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 45.33 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 6066.83 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2012
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 1A
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_FL_MIAMI
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneHeatingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneElectricSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |PeakSpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ComfortReportSimple55Monthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |OccupantComfortDataSummaryMonthly
| BASEMENT PEOPLE | RETAIL_1_FLR_1 PEOPLE | RETAIL_2_FLR_1 PEOPLE | LAUNDRY_FLR_1 PEOPLE | CAFE_FLR_1 PEOPLE | LOBBY_FLR_1 PEOPLE | ROOM_1_FLR_3 PEOPLE | ROOM_2_FLR_3 PEOPLE | ROOM_3_MULT19_FLR_3 PEOPLE | ROOM_4_MULT19_FLR_3 PEOPLE | ROOM_5_FLR_3 PEOPLE | ROOM_6_FLR_3 PEOPLE | ROOM_1_FLR_6 PEOPLE | ROOM_2_FLR_6 PEOPLE | ROOM_3_MULT9_FLR_6 PEOPLE | BANQUET_FLR_6 PEOPLE | DINING_FLR_6 PEOPLE | KITCHEN_FLR_6 PEOPLE | STORAGE_FLR_1 PEOPLE | CORRIDOR_FLR_3 PEOPLE | CORRIDOR_FLR_6 PEOPLE | MECH_FLR_1 PEOPLE |ChillerReportMonthly
| COOLSYS1 CHILLER1 |BoilerReportMonthly
| HEATSYS1 BOILER |DXReportMonthly
| VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |WindowReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowEnergyReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWH BOOSTER E WATER HEATER | SWH LAUNDRY G WATER HEATER | SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| VAV WITH REHEAT HEATING COIL | BASEMENT VAV BOX REHEAT COIL | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | MECH_FLR_1 VAV BOX REHEAT COIL | STORAGE_FLR_1 VAV BOX REHEAT COIL | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | CAFE_FLR_1 VAV BOX REHEAT COIL | LOBBY_FLR_1 VAV BOX REHEAT COIL | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | BANQUET_FLR_6 VAV BOX REHEAT COIL | DINING_FLR_6 VAV BOX REHEAT COIL | KITCHEN_FLR_6 VAV BOX REHEAT COIL | FLR_3_DOAS HEATING COIL | ROOM_1_FLR_3 FAN COIL HEATING COIL | ROOM_2_FLR_3 FAN COIL HEATING COIL | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_5_FLR_3 FAN COIL HEATING COIL | ROOM_6_FLR_3 FAN COIL HEATING COIL | ROOM_1_FLR_6 FAN COIL HEATING COIL | ROOM_2_FLR_6 FAN COIL HEATING COIL | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1 | SWHSYS1 |FanReportMonthly
| FLR_3_DOAS FAN | VAV WITH REHEAT FAN | LAUNDRY_FLR_1 EXHAUST FAN | LOBBY_FLR_1 EXHAUST FAN | BANQUET_FLR_6 EXHAUST FAN | DINING_FLR_6 EXHAUST FAN | KITCHEN_FLR_6 EXHAUST FAN | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 PUMP | SWHSYS1 PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1 | SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV WITH REHEAT | FLR_3_DOAS |AirLoopSystemComponentLoadsMonthly
| VAV WITH REHEAT | FLR_3_DOAS |AirLoopSystemComponentEnergyUseMonthly
| VAV WITH REHEAT | FLR_3_DOAS |MechanicalVentilationLoadsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:58:20
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:58 |
RunPeriod | RUNPERIOD 1 |
Weather File | Miami Intl Ap FL USA TMY3 WMO#=722020 |
Latitude [deg] | 25.82 |
Longitude [deg] | -80.3 |
Elevation [m] | 11.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1213.79 | 432.95 | 85.85 | 609.15 | 85.85 |
Gross Window-Wall Ratio [%] | 26.62 | 23.11 | 21.12 | 32.52 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.15 | 26.05 | 24.48 | 36.65 | 24.48 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1213.79 | 432.95 | 85.85 | 609.15 | 85.85 |
Gross Window-Wall Ratio [%] | 26.62 | 23.11 | 21.12 | 32.52 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.15 | 26.05 | 24.48 | 36.65 | 24.48 |
Total | |
Gross Roof Area [m2] | 1978.84 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 1978.83 | Yes | Yes | 4826.41 | 1.00 | 0.00 | 533.77 | 0.00 | 0.00 | 8.7495 | 18.58 | 5.3800 |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 265.76 | 1.00 | 68.84 | 0.00 | 23.26 | 23.26 | 13.0124 | 6.19 | 10.7600 |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 307.76 | 1.00 | 26.57 | 0.00 | 0.00 | 0.00 | 13.0124 | 6.19 | 10.7600 |
MECH_FLR_1 | 164.24 | Yes | Yes | 650.80 | 1.00 | 62.80 | 0.00 | 0.00 | 0.00 | 10.0642 | 61.93 | 5.3800 |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 375.47 | 1.00 | 36.23 | 0.00 | 0.00 | 0.00 | 7.3195 | 46.45 | 2.6900 |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 309.22 | 1.00 | 85.75 | 0.00 | 0.00 | 0.00 | 5.4896 | 9.29 | 597.5300 |
CAFE_FLR_1 | 188.86 | Yes | Yes | 748.35 | 1.00 | 152.17 | 0.00 | 65.50 | 65.50 | 12.8090 | 1.33 | 5.3800 |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 5183.56 | 1.00 | 434.79 | 0.00 | 85.08 | 85.08 | 10.0642 | 3.10 | 8.0700 |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 10.0642 | 26.01 | 6.7500 |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 10.0642 | 26.01 | 6.7500 |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 74.75 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 10.0642 | 16.35 | 10.5200 |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 74.77 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 10.0642 | 16.35 | 10.5200 |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 10.0642 | 26.01 | 6.7500 |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 10.0642 | 26.01 | 6.7500 |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 1186.91 | 4.00 | 48.31 | 0.00 | 15.94 | 15.94 | 3.6597 | 18.58 | 0.0000 |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 118.94 | 1.00 | 39.95 | 0.00 | 13.18 | 13.18 | 10.0642 | 26.01 | 6.7500 |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 118.93 | 1.00 | 39.95 | 0.00 | 13.18 | 13.18 | 10.0642 | 26.01 | 6.7500 |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 74.77 | 9.00 | 20.44 | 0.00 | 6.74 | 6.74 | 10.0642 | 16.35 | 10.5200 |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.19 | 32.19 | 12.8090 | 1.33 | 67.8200 |
DINING_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.19 | 32.19 | 12.8090 | 1.33 | 67.8200 |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 314.87 | 1.00 | 87.33 | 0.00 | 26.37 | 26.37 | 10.9792 | 4.65 | 2936.4163 |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1256.16 | 1.00 | 85.47 | 0.00 | 28.20 | 28.20 | 3.6597 | 18.58 | 0.0000 |
Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1213.79 | 1213.79 | 8.9207 | 7.07 | 41.0885 | |||
Conditioned Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1213.79 | 1213.79 | 8.9207 | 7.07 | 41.0885 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 1978.83 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 8.7495 | 18.58 | 5.3800 | |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 1.00 | RETAIL_1_FLR_1 | GENERAL | RETAIL_1_FLR_1 | 13.0124 | 6.19 | 10.7600 | |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 1.00 | RETAIL_2_FLR_1 | GENERAL | RETAIL_2_FLR_1 | 13.0124 | 6.19 | 10.7600 | |
MECH_FLR_1 | 164.24 | Yes | Yes | 1.00 | MECH_FLR_1 | GENERAL | MECH_FLR_1 | 10.0642 | 61.93 | 5.3800 | |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 1.00 | STORAGE_FLR_1 | GENERAL | STORAGE_FLR_1 | 7.3195 | 46.45 | 2.6900 | |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 1.00 | LAUNDRY_FLR_1 | GENERAL | LAUNDRY_FLR_1 | 5.4896 | 9.29 | 597.5300 | |
CAFE_FLR_1 | 188.86 | Yes | Yes | 1.00 | CAFE_FLR_1 | GENERAL | CAFE_FLR_1 | 12.8090 | 1.33 | 5.3800 | |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 1.00 | LOBBY_FLR_1 | GENERAL | LOBBY_FLR_1 | 10.0642 | 3.10 | 8.0700 | |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_1_FLR_3 | GENERAL | ROOM_1_FLR_3 | 10.0642 | 26.01 | 6.7500 | |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_2_FLR_3 | GENERAL | ROOM_2_FLR_3 | 10.0642 | 26.01 | 6.7500 | |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 76.00 | ROOM_3_MULT19_FLR_3 | GENERAL | ROOM_3_MULT19_FLR_3 | 10.0642 | 16.35 | 10.5200 | |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 76.00 | ROOM_4_MULT19_FLR_3 | GENERAL | ROOM_4_MULT19_FLR_3 | 10.0642 | 16.35 | 10.5200 | |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_5_FLR_3 | GENERAL | ROOM_5_FLR_3 | 10.0642 | 26.01 | 6.7500 | |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_6_FLR_3 | GENERAL | ROOM_6_FLR_3 | 10.0642 | 26.01 | 6.7500 | |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 4.00 | CORRIDOR_FLR_3 | GENERAL | CORRIDOR_FLR_3 | 3.6597 | 18.58 | 0.0000 | |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 1.00 | ROOM_1_FLR_6 | GENERAL | ROOM_1_FLR_6 | 10.0642 | 26.01 | 6.7500 | |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 1.00 | ROOM_2_FLR_6 | GENERAL | ROOM_2_FLR_6 | 10.0642 | 26.01 | 6.7500 | |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 9.00 | ROOM_3_MULT9_FLR_6 | GENERAL | ROOM_3_MULT9_FLR_6 | 10.0642 | 16.35 | 10.5200 | |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1.00 | BANQUET_FLR_6 | GENERAL | BANQUET_FLR_6 | 12.8090 | 1.33 | 67.8200 | |
DINING_FLR_6 | 331.66 | Yes | Yes | 1.00 | DINING_FLR_6 | GENERAL | DINING_FLR_6 | 12.8090 | 1.33 | 67.8200 | |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 1.00 | KITCHEN_FLR_6 | GENERAL | KITCHEN_FLR_6 | 10.9792 | 4.65 | 2936.4163 | |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1.00 | CORRIDOR_FLR_6 | GENERAL | CORRIDOR_FLR_6 | 3.6597 | 18.58 | 0.0000 | |
Total | 11345.29 | 8.9207 | 3.54 | 41.0885 | |||||||
Conditioned Total | 11345.29 | 8.9207 | 3.54 | 41.0885 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 11345.29 | 11345.29 | 0.00 | 0.00 | 4.6908 | 8.82 | 37.2165 |
Total | 11345.29 | 11345.29 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:58:20
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 27-JUL-18:10 | 17-DEC-17:00 | - | - | - | - | - | - | - | - | - | - | 02-JAN-21:10 |
Heating | 0.00 | 51148.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 317380.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 82800.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 79617.06 | 87521.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 32686.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 72579.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 16647.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 16791.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 4738.75 | 214046.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 2934.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 626175.88 | 352716.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 51148.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 317380.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 82800.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 49434.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 29240.64 | 74976.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 515.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 425.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 12545.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 1560.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 30153.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 972.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 72579.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 16647.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 16791.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 4738.75 | 214046.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 642.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 1186.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 1104.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:58:20
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 508.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 16765.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 3718.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 831.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 5546.36 | 1939.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 2152.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 5784.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 1456.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 1647.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 287.47 | 2844.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 240.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 38431.43 | 5291.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 44.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1477.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 327.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 73.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 488.87 | 170.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 189.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 509.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 128.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 145.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 25.34 | 250.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 21.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 3387.44 | 466.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 44.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1477.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 327.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 73.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 488.87 | 170.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 189.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 509.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 128.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 145.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 25.34 | 250.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 21.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 3387.44 | 466.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:58:20
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
BASEMENT VAV BOX COMPONENT | 2.66 | 0.566525 | 0.995000 | 2.65 | 1.00 | 0.500000 | 0.000673 | 0.000122 | 2.65 | 16.70 | 0.008000 |
RETAIL_1_FLR_1 VAV BOX COMPONENT | 0.293638 | 0.174053 | 0.995000 | 0.292169 | 0.995000 | 0.500000 | 0.002189 | 0.000027 | 0.292169 | 16.70 | 0.008000 |
RETAIL_2_FLR_1 VAV BOX COMPONENT | 0.242241 | 0.244318 | 0.995000 | 0.241029 | 0.995000 | 0.500000 | 0.001559 | 0.000016 | 0.241029 | 16.70 | 0.008000 |
MECH_FLR_1 VAV BOX COMPONENT | 0.261455 | 0.478680 | 0.995000 | 0.260148 | 1.00 | 0.500000 | 0.000796 | 0.000020 | 0.260148 | 16.70 | 0.008000 |
STORAGE_FLR_1 VAV BOX COMPONENT | 0.130529 | 0.553183 | 0.995000 | 0.129877 | 1.00 | 0.500000 | 0.000689 | 0.000011 | 0.129877 | 16.70 | 0.008000 |
LAUNDRY_FLR_1 VAV BOX COMPONENT | 3.27 | 0.072237 | 0.995000 | 3.25 | 0.995000 | 0.500000 | 0.020930 | 0.000161 | 3.25 | 16.70 | 0.008000 |
CAFE_FLR_1 VAV BOX COMPONENT | 1.31 | 0.109897 | 0.995000 | 1.30 | 0.995000 | 0.500000 | 0.003467 | 0.000094 | 1.30 | 16.70 | 0.008000 |
LOBBY_FLR_1 VAV BOX COMPONENT | 4.56 | 0.218686 | 0.995000 | 4.54 | 0.995000 | 0.500000 | 0.001742 | 0.000286 | 4.54 | 16.70 | 0.008000 |
CORRIDOR_FLR_3 VAV BOX COMPONENT | 1.10 | 1.00 | 0.995000 | 1.10 | 1.00 | 0.500000 | 0.000353 | 0.000101 | 1.10 | 16.70 | 0.008000 |
BANQUET_FLR_6 VAV BOX COMPONENT | 2.24 | 0.112981 | 0.995000 | 2.23 | 0.995000 | 0.500000 | 0.003372 | 0.000135 | 2.23 | 16.70 | 0.008000 |
DINING_FLR_6 VAV BOX COMPONENT | 2.35 | 0.107669 | 0.995000 | 2.34 | 0.995000 | 0.500000 | 0.003539 | 0.000140 | 2.34 | 16.70 | 0.008000 |
KITCHEN_FLR_6 VAV BOX COMPONENT | 2.25 | 0.838319 | 0.995000 | 2.24 | 0.995000 | 0.500000 | 0.010899 | 0.000103 | 2.24 | 16.70 | 0.008000 |
CORRIDOR_FLR_6 VAV BOX COMPONENT | 0.663295 | 0.473453 | 0.995000 | 0.659978 | 1.00 | 0.500000 | 0.000805 | 0.000064 | 0.659978 | 16.70 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
BASEMENT VAV BOX REHEAT COIL | 13966.41 | 0.000122 | 291.25 |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 3112.97 | 0.000027 | 68.56 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 1773.53 | 0.000016 | 37.76 |
MECH_FLR_1 VAV BOX REHEAT COIL | 2296.52 | 0.000020 | 49.63 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | 1228.03 | 0.000011 | 26.71 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 18443.65 | 0.000161 | 386.13 |
CAFE_FLR_1 VAV BOX REHEAT COIL | 10789.68 | 0.000094 | 231.87 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | 32731.44 | 0.000286 | 695.87 |
ROOM_1_FLR_3 FAN COIL HEATING COIL | 3659.96 | 0.000032 | 104.57 |
ROOM_2_FLR_3 FAN COIL HEATING COIL | 3660.18 | 0.000032 | 104.58 |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | 21298.53 | 0.000186 | 608.55 |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | 21316.13 | 0.000186 | 609.05 |
ROOM_5_FLR_3 FAN COIL HEATING COIL | 3658.99 | 0.000032 | 104.55 |
ROOM_6_FLR_3 FAN COIL HEATING COIL | 3659.22 | 0.000032 | 104.55 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 11535.77 | 0.000101 | 253.72 |
ROOM_1_FLR_6 FAN COIL HEATING COIL | 1124.65 | 0.000010 | 32.13 |
ROOM_2_FLR_6 FAN COIL HEATING COIL | 1124.88 | 0.000010 | 32.14 |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | 5435.88 | 0.000048 | 155.31 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | 15438.99 | 0.000135 | 327.31 |
DINING_FLR_6 VAV BOX REHEAT COIL | 15947.96 | 0.000140 | 337.74 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | 11816.39 | 0.000103 | 246.41 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 7322.43 | 0.000064 | 162.01 |
VAV WITH REHEAT HEATING COIL | 61543.58 | 0.000538 | 1142.02 |
FLR_3_DOAS HEATING COIL | 5950.05 | 0.000052 | 110.41 |
User-Specified Maximum Flow Rate [m3/s] | |
LOBBY_FLR_1 EXHAUST FAN | 0.000000 |
BANQUET_FLR_6 EXHAUST FAN | 0.000000 |
DINING_FLR_6 EXHAUST FAN | 0.000000 |
Design Size Maximum Air Flow Rate [m3/s] | |
ROOM_1_FLR_3 DIRECT AIR | 0.061735 |
ROOM_2_FLR_3 DIRECT AIR | 0.061728 |
ROOM_3_MULT19_FLR_3 DIRECT AIR | 0.837072 |
ROOM_4_MULT19_FLR_3 DIRECT AIR | 0.837300 |
ROOM_5_FLR_3 DIRECT AIR | 0.061735 |
ROOM_6_FLR_3 DIRECT AIR | 0.061728 |
ROOM_1_FLR_6 DIRECT AIR | 0.015434 |
ROOM_2_FLR_6 DIRECT AIR | 0.015432 |
ROOM_3_MULT9_FLR_6 DIRECT AIR | 0.099154 |
Design Size Maximum Supply Air Flow Rate [m3/s] | Design Size Maximum Hot Water Flow [m3/s] | Design Size Maximum Cold Water Flow [m3/s] | |
ROOM_1_FLR_3 FAN COIL | 1.05 | 0.000032 | 0.000488 |
ROOM_2_FLR_3 FAN COIL | 1.06 | 0.000032 | 0.000492 |
ROOM_3_MULT19_FLR_3 FAN COIL | 5.95 | 0.000186 | 0.002714 |
ROOM_4_MULT19_FLR_3 FAN COIL | 6.95 | 0.000186 | 0.003288 |
ROOM_5_FLR_3 FAN COIL | 0.942610 | 0.000032 | 0.000443 |
ROOM_6_FLR_3 FAN COIL | 0.950587 | 0.000032 | 0.000447 |
ROOM_1_FLR_6 FAN COIL | 0.280254 | 0.000010 | 0.000130 |
ROOM_2_FLR_6 FAN COIL | 0.282749 | 0.000010 | 0.000131 |
ROOM_3_MULT9_FLR_6 FAN COIL | 1.17 | 0.000048 | 0.000553 |
Design Size Maximum Flow Rate [m3/s] | |
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | 1.05 |
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | 1.06 |
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | 5.95 |
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | 6.95 |
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | 0.942610 |
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | 0.950587 |
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | 0.280254 |
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | 0.282749 |
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | 1.17 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Temperature [C] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | Design Size Design Coil Load [W] | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | 22.49 | 6.70 | 0.008872 | 12.80 | 0.008500 | 0.000488 | 1.05 | |
ROOM_2_FLR_3 FAN COIL COOLING COIL | 22.49 | 6.70 | 0.008869 | 12.80 | 0.008500 | 0.000492 | 1.06 | |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | 22.49 | 6.70 | 0.008785 | 12.80 | 0.008500 | 0.002714 | 5.95 | |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | 22.49 | 6.70 | 0.008943 | 12.80 | 0.008500 | 0.003288 | 6.95 | |
ROOM_5_FLR_3 FAN COIL COOLING COIL | 22.49 | 6.70 | 0.008915 | 12.80 | 0.008500 | 0.000443 | 0.942610 | |
ROOM_6_FLR_3 FAN COIL COOLING COIL | 22.49 | 6.70 | 0.008912 | 12.80 | 0.008500 | 0.000447 | 0.950587 | |
ROOM_1_FLR_6 FAN COIL COOLING COIL | 22.49 | 6.70 | 0.008850 | 12.80 | 0.008500 | 0.000130 | 0.280254 | |
ROOM_2_FLR_6 FAN COIL COOLING COIL | 22.49 | 6.70 | 0.008846 | 12.80 | 0.008500 | 0.000131 | 0.282749 | |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | 22.49 | 6.70 | 0.008953 | 12.80 | 0.008500 | 0.000553 | 1.17 | |
VAV WITH REHEAT COOLING COIL | 33.20 | 6.70 | 0.017167 | 11.00 | 0.008500 | 0.040895 | 21.22 | 1144947.37 |
FLR_3_DOAS COOLING COIL | 33.20 | 6.70 | 0.017167 | 11.94 | 0.008500 | 0.003869 | 2.05 | 108329.82 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV WITH REHEAT | 21.22 | 21.22 | 21.32 | 21.22 | 21.22 | 21.22 | 0.300000 | 1.00 | 21.22 |
FLR_3_DOAS | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 0.300000 | 1.00 | 2.05 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV WITH REHEAT_OA_CONTROLLER | 21.22 | 21.21 |
FLR_3_DOAS_OA_CONTROLLER | 2.05 | 2.05 |
Design Size Nominal Supply Air Flow Rate [m3/s] | |
VAV WITH REHEAT OA HEAT RECOVERY | 21.21 |
FLR_3_DOAS OA HEAT RECOVERY | 2.05 |
Design Size Maximum Flow Rate [m3/s] | |
VAV WITH REHEAT FAN | 21.22 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV WITH REHEAT_COOLC_CONTROLLER | 0.040895 | 0.000012 |
VAV WITH REHEAT_HEATC_CONTROLLER | 0.000538 | |
FLR_3_DOAS_COOLC_CONTROLLER | 0.003869 | 0.000123 |
FLR_3_DOAS_HEATC_CONTROLLER | 0.000052 |
User-Specified Maximum Flow Rate [m3/s] | |
FLR_3_DOAS FAN | 2.05 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.053450 | 11014.04 | |
HEATSYS1 PUMP | 0.002439 | 734.63 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
HEATSYS1 | 0.002439 | 0.292725 |
COOLSYS1 | 0.053450 | 6.41 |
SWHSYS1 | 0.000375 | 0.045004 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 278835.82 | 278835.82 | 0.002439 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 PUMP | 0.053450 | 7625.39 |
SWHSYS1 PUMP | 0.000375 | 47.91 |
Design Size Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Fluid Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.053450 | 1496454.60 | 1497043.85 | 170.66 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000375 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:58:20
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesPossible Shadow Receivers | |
RETAIL_1_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
CAFE_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
LOBBY_FLR_1_CEILING_2 | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
Possible Shadow Receivers | |
RETAIL_1_FLR_1_WALL_SOUTH | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | |
RETAIL_2_FLR_1_WALL_WEST | RETAIL_2_FLR_1_WALL_WEST_DOOR | |
STORAGE_FLR_1_WALL_NORTH | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | |
LAUNDRY_FLR_1_WALL_EAST | LAUNDRY_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_EAST | CAFE_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_SOUTH | CAFE_FLR_1_WALL_SOUTH_WINDOW | |
LOBBY_FLR_1_WALL_1_NORTH | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | |
LOBBY_FLR_1_WALL_1_SOUTH | LOBBY_FLR_1_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_SOUTH | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_WEST | ROOM_1_FLR_3_WALL_WEST_WINDOW | |
ROOM_2_FLR_3_WALL_NORTH | ROOM_2_FLR_3_WALL_NORTH_WINDOW | |
ROOM_2_FLR_3_WALL_WEST | ROOM_2_FLR_3_WALL_WEST_WINDOW | |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_4_MULT19_FLR_3_WALL_NORTH | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | |
ROOM_5_FLR_3_WALL_EAST | ROOM_5_FLR_3_WALL_EAST_WINDOW | |
ROOM_5_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_6_FLR_3_WALL_NORTH | ROOM_6_FLR_3_WALL_NORTH_WINDOW | |
ROOM_6_FLR_3_WALL_EAST | ROOM_6_FLR_3_WALL_EAST_WINDOW | |
CORRIDOR_FLR_3_WALL_1_NORTH | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_NORTH | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_SOUTH | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_WEST | ROOM_1_FLR_6_WALL_WEST_WINDOW | |
ROOM_2_FLR_6_WALL_NORTH | ROOM_2_FLR_6_WALL_NORTH_WINDOW | |
ROOM_2_FLR_6_WALL_WEST | ROOM_2_FLR_6_WALL_WEST_WINDOW | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | |
BANQUET_FLR_6_WALL_NORTH | BANQUET_FLR_6_WALL_NORTH_WINDOW | |
DINING_FLR_6_WALL_NORTH | DINING_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_NORTH | KITCHEN_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_EAST | KITCHEN_FLR_6_WALL_EAST_WINDOW | |
KITCHEN_FLR_6_WALL_1_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_6_WALL_1_NORTH | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_NORTH | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:58:20
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:58:20
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 26.30 | 23.60 | 20.30 | 19.40 | 20.90 | 21.60 | 24.10 | 26.40 | 27.70 | 28.10 | 28.00 | 27.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Miami Intl Ap FL USA TMY3 WMO#=722020 | 25.82 | -80.30 | -5.00 | 11.00 | 101193 | 1.2027 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 24.49 | 8.70 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | HotelLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | DOE-2 |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 22 | 235 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 41.45 | 11.51 | -1.22 | 1 | 1 | 1 | 0.00 | 86.56 | 0.00 | 22.86 | -2.44 | 0.00 | 2.44 | 4826.41 | TARP | DOE-2 | 1978.83 | 0.00 | 0.00 | 0.00 | 13 | 0 | 0 | Yes |
2 | RETAIL_1_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 2.90 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 265.76 | TARP | DOE-2 | 67.07 | 68.84 | 45.58 | 23.26 | 6 | 1 | 0 | Yes |
3 | RETAIL_2_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 9.14 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 5.79 | 12.50 | 0.00 | 3.96 | 3.96 | 307.76 | TARP | DOE-2 | 77.67 | 26.57 | 24.62 | 0.00 | 6 | 1 | 0 | Yes |
4 | MECH_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 61.87 | 17.68 | 1.98 | 1 | 1 | 1 | 53.95 | 69.80 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 650.80 | TARP | DOE-2 | 164.24 | 62.80 | 62.80 | 0.00 | 6 | 0 | 0 | Yes |
5 | STORAGE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 74.37 | 17.68 | 1.98 | 1 | 1 | 1 | 69.80 | 78.94 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 375.47 | TARP | DOE-2 | 94.76 | 36.23 | 28.80 | 0.00 | 6 | 1 | 0 | Yes |
6 | LAUNDRY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 14.33 | 1.98 | 1 | 1 | 1 | 81.99 | 86.56 | 5.79 | 22.86 | 0.00 | 3.96 | 3.96 | 309.22 | TARP | DOE-2 | 78.04 | 85.75 | 83.80 | 0.00 | 6 | 1 | 0 | Yes |
7 | CAFE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 70.26 | 2.90 | 1.98 | 1 | 1 | 1 | 53.95 | 86.56 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 748.35 | TARP | DOE-2 | 188.86 | 152.17 | 84.72 | 65.50 | 7 | 2 | 0 | Yes |
8 | LOBBY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 38.29 | 12.45 | 1.98 | 1 | 1 | 1 | 0.00 | 81.99 | 0.00 | 22.86 | 0.00 | 3.96 | 3.96 | 5183.56 | TARP | DOE-2 | 1308.19 | 434.79 | 345.80 | 85.08 | 18 | 3 | 0 | Yes |
9 | ROOM_1_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
10 | ROOM_2_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
11 | ROOM_3_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 8.53 | 9.14 | 8.53 | 1 | 76 | 1 | 6.71 | 10.36 | 5.79 | 12.50 | 7.01 | 10.06 | 3.05 | 74.75 | TARP | DOE-2 | 24.52 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
12 | ROOM_4_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 12.19 | 19.51 | 8.53 | 1 | 76 | 1 | 10.36 | 14.02 | 16.15 | 22.86 | 7.01 | 10.06 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
13 | ROOM_5_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 10.06 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
14 | ROOM_6_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 18.59 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
15 | CORRIDOR_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 43.28 | 14.33 | 8.53 | 1 | 4 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 7.01 | 10.06 | 3.05 | 1186.91 | TARP | DOE-2 | 389.40 | 48.31 | 32.37 | 15.94 | 20 | 4 | 0 | Yes |
16 | ROOM_1_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 16.15 | 19.20 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
17 | ROOM_2_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 16.15 | 19.20 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
18 | ROOM_3_MULT9_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 7.93 | 7.62 | 17.68 | 1 | 9 | 1 | 4.57 | 11.28 | 5.79 | 9.45 | 16.15 | 19.20 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 20.44 | 13.70 | 6.74 | 6 | 1 | 0 | Yes |
19 | BANQUET_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 26.37 | 17.68 | 17.68 | 1 | 1 | 1 | 10.36 | 42.37 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.36 | 32.19 | 6 | 1 | 0 | Yes |
20 | DINING_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 63.55 | 17.68 | 17.68 | 1 | 1 | 1 | 47.55 | 79.55 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.36 | 32.19 | 6 | 1 | 0 | Yes |
21 | KITCHEN_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 82.99 | 14.11 | 17.68 | 1 | 1 | 1 | 79.55 | 86.56 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 314.87 | TARP | DOE-2 | 103.30 | 87.33 | 60.96 | 26.37 | 8 | 3 | 0 | Yes |
22 | CORRIDOR_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 41.51 | 13.35 | 17.68 | 1 | 1 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 1256.16 | TARP | DOE-2 | 412.12 | 85.47 | 57.27 | 28.20 | 15 | 3 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 1978.83 | 106.5 | 18.581 | 5.382E-002 | 8.749 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 14.129 | No |
2 | RETAIL_1_FLR_1 | 67.07 | 10.8 | 6.194 | 0.161 | 13.012 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 23.772 | No |
3 | RETAIL_2_FLR_1 | 77.67 | 12.5 | 6.194 | 0.161 | 13.012 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 23.772 | No |
4 | MECH_FLR_1 | 164.24 | 2.7 | 61.932 | 1.615E-002 | 10.064 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 15.444 | No |
5 | STORAGE_FLR_1 | 94.76 | 2.0 | 46.451 | 2.153E-002 | 7.319 | 2.690 | 0.000 | 0.000 | 0.000 | 0.000 | 10.009 | No |
6 | LAUNDRY_FLR_1 | 78.04 | 8.4 | 9.290 | 0.108 | 5.490 | 61.680 | 535.850 | 0.000 | 0.000 | 0.000 | 603.020 | No |
7 | CAFE_FLR_1 | 188.86 | 142.3 | 1.327 | 0.753 | 12.809 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 18.189 | No |
8 | LOBBY_FLR_1 | 1308.19 | 422.4 | 3.097 | 0.323 | 10.064 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.134 | No |
9 | ROOM_1_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 10.064 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 16.814 | No |
10 | ROOM_2_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 10.064 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 16.814 | No |
11 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 16.349 | 6.116E-002 | 10.064 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 20.584 | No |
12 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 10.064 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 20.584 | No |
13 | ROOM_5_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 10.064 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 16.814 | No |
14 | ROOM_6_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 10.064 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 16.814 | No |
15 | CORRIDOR_FLR_3 | 389.40 | 21.0 | 18.581 | 5.382E-002 | 3.660 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 3.660 | No |
16 | ROOM_1_FLR_6 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 10.064 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 16.814 | No |
17 | ROOM_2_FLR_6 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 10.064 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 16.814 | No |
18 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 10.064 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 20.584 | No |
19 | BANQUET_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 12.809 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 80.629 | No |
20 | DINING_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 12.809 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 80.629 | No |
21 | KITCHEN_FLR_6 | 103.30 | 22.2 | 4.645 | 0.215 | 10.979 | 517.156 | 2419.260 | 0.000 | 0.000 | 0.000 | 2947.395 | No |
22 | CORRIDOR_FLR_6 | 412.12 | 22.2 | 18.581 | 5.382E-002 | 3.660 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 3.660 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | BASEMENT PEOPLE | BLDG_OCC_SCH | BASEMENT | 1978.83 | 106.5 | 106.5 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 106 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | RETAIL_1_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 10.8 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | RETAIL_2_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 12.5 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 13 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | LAUNDRY_FLR_1 PEOPLE | BLDG_OCC_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 8.4 | 0.108 | 9.290 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 8 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | CAFE_FLR_1 PEOPLE | BLDG_OCC_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 142.3 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 142 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | LOBBY_FLR_1 PEOPLE | BLDG_OCC_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 422.4 | 0.323 | 3.097 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 422 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | ROOM_1_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | ROOM_2_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | ROOM_3_MULT19_FLR_3 PEOPLE | ALWAYS_OFF | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 1.5 | 6.116E-002 | 16.349 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 0 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | ROOM_4_MULT19_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | ROOM_5_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | ROOM_6_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | ROOM_1_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | ROOM_2_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | ROOM_3_MULT9_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | BANQUET_FLR_6 PEOPLE | BLDG_OCC_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | DINING_FLR_6 PEOPLE | BLDG_OCC_SCH | DINING_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | KITCHEN_FLR_6 PEOPLE | BLDG_OCC_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 22.2 | 0.215 | 4.645 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | STORAGE_FLR_1 PEOPLE | BLDG_OCC_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 2.0 | 2.153E-002 | 46.451 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | CORRIDOR_FLR_3 PEOPLE | BLDG_OCC_SCH | CORRIDOR_FLR_3 | 389.40 | 21.0 | 21.0 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 21 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
21 | CORRIDOR_FLR_6 PEOPLE | BLDG_OCC_SCH | CORRIDOR_FLR_6 | 412.12 | 22.2 | 22.2 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
22 | MECH_FLR_1 PEOPLE | BLDG_OCC_SCH | MECH_FLR_1 | 164.24 | 2.7 | 2.7 | 1.615E-002 | 61.932 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 3 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_BASEMENT | BASEMENT | 1978.83 | 106.5 | 17313.725 | 8.749 | 162.572 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 17313.725 |
2 | RETAIL_1_FLR_1_LIGHTS | LTG_SCH_RETAIL | RETAIL_1_FLR_1 | 67.07 | 10.8 | 872.757 | 13.012 | 80.594 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 872.757 |
3 | RETAIL_2_FLR_1_LIGHTS | LTG_SCH_RETAIL | RETAIL_2_FLR_1 | 77.67 | 12.5 | 1010.656 | 13.012 | 80.595 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1010.656 |
4 | MECH_FLR_1_LIGHTS | LTG_SCH_MECHANIC | MECH_FLR_1 | 164.24 | 2.7 | 1652.984 | 10.064 | 623.297 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1652.984 |
5 | STORAGE_FLR_1_LIGHTS | LTG_SCH_STORAGE | STORAGE_FLR_1 | 94.76 | 2.0 | 693.586 | 7.319 | 339.993 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 693.586 |
6 | LAUNDRY_FLR_1_LIGHTS | LTG_SCH_LAUNDRY | LAUNDRY_FLR_1 | 78.04 | 8.4 | 428.405 | 5.490 | 51.001 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 428.405 |
7 | CAFE_FLR_1_LIGHTS | LTG_SCH_DINING | CAFE_FLR_1 | 188.86 | 142.3 | 2419.140 | 12.809 | 17.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2419.140 |
8 | LOBBY_FLR_1_LIGHTS | LTG_SCH_LOBBY | LOBBY_FLR_1 | 1308.19 | 422.4 | 13165.908 | 10.064 | 31.167 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 13165.908 |
9 | ROOM_1_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_1_FLR_3 | 39.02 | 1.5 | 392.727 | 10.064 | 261.818 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 392.727 |
10 | ROOM_2_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_2_FLR_3 | 39.02 | 1.5 | 392.681 | 10.064 | 261.787 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 392.681 |
11 | ROOM_3_MULT19_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 246.814 | 10.064 | 164.543 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 246.814 |
12 | ROOM_4_MULT19_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 246.881 | 10.064 | 164.588 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 246.881 |
13 | ROOM_5_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_5_FLR_3 | 39.02 | 1.5 | 392.727 | 10.064 | 261.818 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 392.727 |
14 | ROOM_6_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_6_FLR_3 | 39.02 | 1.5 | 392.681 | 10.064 | 261.787 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 392.681 |
15 | CORRIDOR_FLR_3_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_FLR_3 | 389.40 | 21.0 | 1425.114 | 3.660 | 68.002 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1425.114 |
16 | ROOM_1_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_1_FLR_6 | 39.02 | 1.5 | 392.727 | 10.064 | 261.818 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 392.727 |
17 | ROOM_2_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_2_FLR_6 | 39.02 | 1.5 | 392.681 | 10.064 | 261.787 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 392.681 |
18 | ROOM_3_MULT9_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 246.881 | 10.064 | 164.588 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 246.881 |
19 | BANQUET_FLR_6_LIGHTS | LTG_SCH_DINING | BANQUET_FLR_6 | 331.66 | 249.9 | 4248.214 | 12.809 | 17.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 4248.214 |
20 | DINING_FLR_6_LIGHTS | LTG_SCH_DINING | DINING_FLR_6 | 331.66 | 249.9 | 4248.214 | 12.809 | 17.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 4248.214 |
21 | KITCHEN_FLR_6_LIGHTS | LTG_SCH_KITCHEN | KITCHEN_FLR_6 | 103.30 | 22.2 | 1134.198 | 10.979 | 51.003 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1134.198 |
22 | CORRIDOR_FLR_6_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_FLR_6 | 412.12 | 22.2 | 1508.264 | 3.660 | 68.001 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1508.264 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | BASEMENT_EQUIP_SCH | BASEMENT | 1978.83 | 106.5 | 10646.106 | 5.380 | 99.964 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10646.106 |
2 | RETAIL_1_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 721.688 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 721.688 |
3 | RETAIL_2_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 835.717 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 835.717 |
4 | MECH_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | MECH_FLR_1 | 164.24 | 2.7 | 883.628 | 5.380 | 333.193 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 883.628 |
5 | STORAGE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 254.902 | 2.690 | 124.952 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 254.902 |
6 | LAUNDRY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 4813.474 | 61.680 | 573.033 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 4813.474 |
7 | CAFE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 1016.077 | 5.380 | 7.140 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1016.077 |
8 | LOBBY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 10557.062 | 8.070 | 24.991 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10557.062 |
9 | ROOM_1_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_1_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
10 | ROOM_2_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_2_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
11 | ROOM_3_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 257.991 | 10.520 | 171.994 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 257.991 |
12 | ROOM_4_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
13 | ROOM_5_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_5_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
14 | ROOM_6_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_6_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
15 | ROOM_1_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_1_FLR_6 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
16 | ROOM_2_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_2_FLR_6 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
17 | ROOM_3_MULT9_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
18 | BANQUET_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
19 | DINING_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | DINING_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
20 | KITCHEN_FLR_6_MISCELEC_EQUIP | KITCHEN_ELEC_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 52482.799 | 508.040 | 2360.050 | 0.200 | 0.500 | 0.100 | 0.200 | Cooking | 0.000 | 15744.840 |
21 | KITCHEN_FLR_6_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 515.917 | 4.994 | 23.200 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 515.917 | 515.917 |
22 | KITCHEN_FLR_6_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 425.833 | 4.122 | 19.149 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 425.833 | 425.833 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LAUNDRY_FLR_1_MISCGAS_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 41817.449 | 535.850 | 4978.268 | 0.000 | 0.500 | 0.000 | 0.500 | Laundry | 0.000 | 41817.449 |
2 | KITCHEN_FLR_6_MISCGAS_EQUIP | KITCHEN_GAS_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 249920.353 | 2419.260 | 11238.437 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 74976.106 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.464 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | OVERHEAD DOOR_CON | 2 | 1 | 1 | 0.167 | 1.198 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
3 | INTERIORFURNISHINGS | 3 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 8 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 18 | 3 | 3 | 0.167 | 0.2832 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
6 | RES_ROOF | 19 | 3 | 3 | 0.167 | 0.2832 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
7 | NONRES_EXT_WALL_GRD | 21 | 3 | 9 | 0.167 | 1.214 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | NONRES_EXT_WALL_MID | 22 | 3 | 9 | 0.167 | 1.530 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | NONRES_EXT_WALL_TOP | 23 | 3 | 9 | 0.167 | 1.605 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | RES_EXT_WALL_MID | 25 | 3 | 9 | 0.167 | 1.530 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | RES_EXT_WALL_TOP | 26 | 3 | 9 | 0.167 | 1.605 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | NONRES_FLOOR | 30 | 3 | 7 | 0.167 | 0.4124 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
13 | NONRES_FLOOR_CEILING | 33 | 3 | 7 | 0.167 | 0.4124 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
14 | BASEMENT_FLOOR | 36 | 2 | 7 | 0.333 | 2.705 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
15 | BASEMENT_WALL_NORTH_CFACTOR | 39 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | BASEMENT_WALL_EAST_CFACTOR | 40 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | BASEMENT_WALL_SOUTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
18 | BASEMENT_WALL_WEST_CFACTOR | 42 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2887 |
2 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8346 |
3 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 3.472 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
10 | RES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 3.472 |
11 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
12 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
13 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.6561 |
14 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4862 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4557 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | RES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4862 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
25 | RES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4557 |
26 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
27 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.165 |
28 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
29 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
30 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
31 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
32 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.165 |
33 | M10 200MM CONCRETE BLOCK BASEMENT WALL | 0.2032 | 1.326 | 1842.000 | 912.000 | 0.1532 |
34 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
35 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
36 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
37 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
38 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
39 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
40 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
41 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
42 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.4637404 | 3.4637404 | 3.4637404 | |
3 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
4 | 0 | 1.1981135 | 1.1981135 | 1.1981135 | |
5 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
6 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
7 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
8 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
9 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
10 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
11 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
12 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
13 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
14 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
15 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
16 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
17 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
18 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
19 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
20 | 3 | -0.61927053E-06 | 0.12767249E-08 | -0.37968499E-05 | 0.16832131E-17 |
21 | 2 | 0.77611055 | 0.17315568E-02 | 1.0534842 | -0.72792597E-06 |
22 | 1 | -21.915918 | 0.11588205 | -6.3286394 | 0.20197014 |
23 | 0 | 21.365777 | 0.10835518 | 5.5011278 | |
24 | 3 | -0.61927053E-06 | 0.12767249E-08 | -0.37968499E-05 | 0.16832131E-17 |
25 | 2 | 0.77611055 | 0.17315568E-02 | 1.0534842 | -0.72792597E-06 |
26 | 1 | -21.915918 | 0.11588205 | -6.3286394 | 0.20197014 |
27 | 0 | 21.365777 | 0.10835518 | 5.5011278 | |
28 | 9 | 0.16334608E-14 | 0.44521285E-16 | -0.13626018E-09 | -0.55408550E-17 |
29 | 8 | 0.19978482E-07 | 0.16087698E-12 | 0.35757339E-03 | -0.22716220E-09 |
30 | 7 | -0.11637212E-01 | 0.85329953E-08 | -0.22215339E-01 | 0.13231934E-03 |
31 | 6 | 0.38892783 | 0.29989280E-05 | 0.45807963 | -0.45541807E-02 |
32 | 5 | -5.0302817 | 0.11296145E-03 | -4.3335362 | 0.61196441E-01 |
33 | 4 | 32.293780 | 0.93138689E-03 | 21.019023 | -0.41270848 |
34 | 3 | -109.71729 | 0.20442050E-02 | -54.790969 | 1.4933949 |
35 | 2 | 195.63536 | 0.11570803E-02 | 77.111252 | -2.8769641 |
36 | 1 | -170.61189 | 0.12423857E-03 | -55.033492 | 2.7359019 |
37 | 0 | 57.057407 | 0.71170334E-06 | 15.595873 | |
38 | 9 | 0.10594392E-14 | 0.47202510E-16 | -0.12114953E-09 | -0.13223917E-17 |
39 | 8 | 0.17843092E-07 | 0.19779160E-12 | 0.33399960E-03 | -0.20288210E-09 |
40 | 7 | -0.10929829E-01 | 0.10778020E-07 | -0.21195485E-01 | 0.12427612E-03 |
41 | 6 | 0.36970129 | 0.38290923E-05 | 0.44160549 | -0.43275484E-02 |
42 | 5 | -4.8425837 | 0.14557296E-03 | -4.2065674 | 0.58869135E-01 |
43 | 4 | 31.463113 | 0.12102446E-02 | 20.521745 | -0.40168017 |
44 | 3 | -107.94871 | 0.26756904E-02 | -53.807411 | 1.4678460 |
45 | 2 | 193.88106 | 0.15243179E-02 | 76.211002 | -2.8491083 |
46 | 1 | -169.96333 | 0.16464538E-03 | -54.775095 | 2.7245352 |
47 | 0 | 57.057407 | 0.94931294E-06 | 15.641308 | |
48 | 9 | 0.90003388E-15 | 0.50867187E-16 | -0.11754631E-09 | -0.30069304E-17 |
49 | 8 | 0.17333232E-07 | 0.20603527E-12 | 0.32823068E-03 | -0.19708482E-09 |
50 | 7 | -0.10756240E-01 | 0.11305735E-07 | -0.20945040E-01 | 0.12230235E-03 |
51 | 6 | 0.36498247 | 0.40277709E-05 | 0.43754979 | -0.42719257E-02 |
52 | 5 | -4.7965079 | 0.15349109E-03 | -4.1752560 | 0.58297839E-01 |
53 | 4 | 31.259149 | 0.12787761E-02 | 20.398993 | -0.39897233 |
54 | 3 | -107.51430 | 0.28324589E-02 | -53.564574 | 1.4615707 |
55 | 2 | 193.44998 | 0.16162686E-02 | 75.988960 | -2.8422636 |
56 | 1 | -169.80390 | 0.17483991E-03 | -54.711782 | 2.7217408 |
57 | 0 | 57.057407 | 0.10098010E-05 | 15.652787 | |
58 | 9 | 0.10594392E-14 | 0.47202510E-16 | -0.12114953E-09 | -0.13223917E-17 |
59 | 8 | 0.17843092E-07 | 0.19779160E-12 | 0.33399960E-03 | -0.20288210E-09 |
60 | 7 | -0.10929829E-01 | 0.10778020E-07 | -0.21195485E-01 | 0.12427612E-03 |
61 | 6 | 0.36970129 | 0.38290923E-05 | 0.44160549 | -0.43275484E-02 |
62 | 5 | -4.8425837 | 0.14557296E-03 | -4.2065674 | 0.58869135E-01 |
63 | 4 | 31.463113 | 0.12102446E-02 | 20.521745 | -0.40168017 |
64 | 3 | -107.94871 | 0.26756904E-02 | -53.807411 | 1.4678460 |
65 | 2 | 193.88106 | 0.15243179E-02 | 76.211002 | -2.8491083 |
66 | 1 | -169.96333 | 0.16464538E-03 | -54.775095 | 2.7245352 |
67 | 0 | 57.057407 | 0.94931294E-06 | 15.641308 | |
68 | 9 | 0.90003388E-15 | 0.50867187E-16 | -0.11754631E-09 | -0.30069304E-17 |
69 | 8 | 0.17333232E-07 | 0.20603527E-12 | 0.32823068E-03 | -0.19708482E-09 |
70 | 7 | -0.10756240E-01 | 0.11305735E-07 | -0.20945040E-01 | 0.12230235E-03 |
71 | 6 | 0.36498247 | 0.40277709E-05 | 0.43754979 | -0.42719257E-02 |
72 | 5 | -4.7965079 | 0.15349109E-03 | -4.1752560 | 0.58297839E-01 |
73 | 4 | 31.259149 | 0.12787761E-02 | 20.398993 | -0.39897233 |
74 | 3 | -107.51430 | 0.28324589E-02 | -53.564574 | 1.4615707 |
75 | 2 | 193.44998 | 0.16162686E-02 | 75.988960 | -2.8422636 |
76 | 1 | -169.80390 | 0.17483991E-03 | -54.711782 | 2.7217408 |
77 | 0 | 57.057407 | 0.10098010E-05 | 15.652787 | |
78 | 7 | -0.10696287E-14 | 0.39031946E-16 | -0.22096194E-13 | 0.53014468E-15 |
79 | 6 | 0.18597363E-10 | 0.52355087E-11 | 0.51921923E-09 | -0.18483703E-10 |
80 | 5 | -0.10208356E-06 | 0.25520809E-07 | -0.21786771E-05 | 0.17041956E-06 |
81 | 4 | 0.13587196E-03 | 0.96408156E-05 | 0.17589348E-02 | -0.28090751E-03 |
82 | 3 | -0.20124247E-01 | 0.34048350E-03 | -0.21477792 | 0.43172268E-01 |
83 | 2 | 0.28586126 | 0.14813331E-02 | 2.8938873 | -0.61762740 |
84 | 1 | -0.72340799 | 0.92453067E-03 | -7.1302655 | 1.5680075 |
85 | 0 | 0.46030979 | 0.18706506E-04 | 4.4521723 | |
86 | 7 | -0.22096194E-13 | 0.39031946E-16 | -0.10696287E-14 | 0.53014468E-15 |
87 | 6 | 0.51921923E-09 | 0.52355087E-11 | 0.18597363E-10 | -0.18483703E-10 |
88 | 5 | -0.21786771E-05 | 0.25520809E-07 | -0.10208356E-06 | 0.17041956E-06 |
89 | 4 | 0.17589348E-02 | 0.96408156E-05 | 0.13587196E-03 | -0.28090751E-03 |
90 | 3 | -0.21477792 | 0.34048350E-03 | -0.20124247E-01 | 0.43172268E-01 |
91 | 2 | 2.8938873 | 0.14813331E-02 | 0.28586126 | -0.61762740 |
92 | 1 | -7.1302655 | 0.92453067E-03 | -0.72340799 | 1.5680075 |
93 | 0 | 4.4521723 | 0.18706506E-04 | 0.46030979 | |
94 | 7 | -0.52459208E-15 | -0.63961428E-15 | -0.12292524E-09 | -0.35846135E-17 |
95 | 6 | 0.39860198E-02 | 0.96339020E-07 | 0.40499006E-03 | -0.70890431E-04 |
96 | 5 | -0.20832379 | 0.49172556E-04 | -0.20585669E-01 | 0.38489246E-02 |
97 | 4 | 3.5198270 | 0.18993977E-02 | 0.34924834 | -0.69168259E-01 |
98 | 3 | -23.366787 | 0.13311857E-01 | -2.4329538 | 0.50524779 |
99 | 2 | 64.890127 | 0.19943872E-01 | 7.3672511 | -1.5911358 |
100 | 1 | -76.040094 | 0.56792084E-02 | -9.5568013 | 2.1361271 |
101 | 0 | 31.242244 | 0.96490710E-04 | 4.3344156 | |
102 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
103 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
104 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
105 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
106 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
107 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
108 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
109 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
110 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
111 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
112 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
113 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
114 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
115 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
116 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
117 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
118 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
119 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
120 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
121 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
122 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
123 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
124 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
125 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
126 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
127 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
128 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
129 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
130 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
131 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
132 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
133 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.5119_SHGC_0.25 | 37 | 1 | VerySmooth | 2.910 | 2.910 | 1.000 | 0.251 | ||
2 | RESWINDOW_U_0.5119_SHGC_0.25 | 38 | 1 | VerySmooth | 2.910 | 2.910 | 1.000 | 0.251 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER | SpectralAverage | 1.79780E-002 | 0.16139 | 0.60964 | 0.60964 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.10364 | 1.00000 | No | |
2 | RESIDENTIAL WINDOW GLAZING LAYER | SpectralAverage | 1.79780E-002 | 0.16139 | 0.60964 | 0.60964 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.10364 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 7 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 1.500 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 3.000 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWH BOOSTER E WATER HEATER | 2.2712E-002 | 8000.0 | 1.240 | 1.1473 |
2 | WaterHeater:Mixed | SWH LAUNDRY G WATER HEATER | 1.1356 | 163316.0 | 0.576 | 0.5074 |
3 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 2.2712 | 175842.6 | 0.260 | 2.5713E-002 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
6 | BASEMENT_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
7 | BASEMENT_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
8 | BASEMENT_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
9 | BASEMENT_CEILING_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
10 | BASEMENT_CEILING_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
11 | BASEMENT_CEILING_6 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
12 | BASEMENT_CEILING_7 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
13 | BASEMENT_CEILING_8 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
14 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
15 | RETAIL_1_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 4 | No | No |
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 1 | No | No |
17 | RETAIL_1_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 3 | No | No |
18 | RETAIL_1_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
19 | RETAIL_1_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
20 | RETAIL_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
21 | RETAIL_1_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
23 | RETAIL_2_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
25 | RETAIL_2_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
26 | RETAIL_2_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
27 | RETAIL_2_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
28 | RETAIL_2_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
29 | RETAIL_2_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
31 | MECH_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
32 | MECH_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
33 | MECH_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
34 | MECH_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
35 | MECH_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
36 | MECH_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
37 | MECH_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
38 | STORAGE_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
40 | STORAGE_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
41 | STORAGE_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
42 | STORAGE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
43 | STORAGE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
44 | STORAGE_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
45 | STORAGE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
46 | LAUNDRY_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
47 | LAUNDRY_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
49 | LAUNDRY_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
50 | LAUNDRY_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
51 | LAUNDRY_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
52 | LAUNDRY_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
54 | CAFE_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 3 | No | No |
55 | CAFE_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
56 | CAFE_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 4 | No | No |
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 1 | No | No |
58 | CAFE_FLR_1_WALL_1_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
59 | CAFE_FLR_1_WALL_2_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
60 | CAFE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
61 | CAFE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
62 | CAFE_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
63 | CAFE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
64 | LOBBY_FLR_1_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
67 | LOBBY_FLR_1_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
68 | LOBBY_FLR_1_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 1 | No | No |
70 | LOBBY_FLR_1_WALL_1_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
71 | LOBBY_FLR_1_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
72 | LOBBY_FLR_1_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
73 | LOBBY_FLR_1_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
74 | LOBBY_FLR_1_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
75 | LOBBY_FLR_1_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
76 | LOBBY_FLR_1_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
77 | LOBBY_FLR_1_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
78 | LOBBY_FLR_1_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
79 | LOBBY_FLR_1_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
80 | LOBBY_FLR_1_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
81 | LOBBY_FLR_1_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
82 | LOBBY_FLR_1_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
83 | LOBBY_FLR_1_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
84 | LOBBY_FLR_1_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
85 | LOBBY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
86 | ROOM_1_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
88 | ROOM_1_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
90 | ROOM_1_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
91 | ROOM_1_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
92 | ROOM_1_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
93 | ROOM_1_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
94 | ROOM_1_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
95 | ROOM_2_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
97 | ROOM_2_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
99 | ROOM_2_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
100 | ROOM_2_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
101 | ROOM_2_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
102 | ROOM_2_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
103 | ROOM_2_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
109 | ROOM_3_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
110 | ROOM_3_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
117 | ROOM_4_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
118 | ROOM_4_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
120 | ROOM_5_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
122 | ROOM_5_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
124 | ROOM_5_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
125 | ROOM_5_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
126 | ROOM_5_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
127 | ROOM_5_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
128 | ROOM_5_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
129 | ROOM_6_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
131 | ROOM_6_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
133 | ROOM_6_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
134 | ROOM_6_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
135 | ROOM_6_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
136 | ROOM_6_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
137 | ROOM_6_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
138 | CORRIDOR_FLR_3_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
147 | CORRIDOR_FLR_3_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
148 | CORRIDOR_FLR_3_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
149 | CORRIDOR_FLR_3_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
150 | CORRIDOR_FLR_3_WALL_4_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
152 | CORRIDOR_FLR_3_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
153 | CORRIDOR_FLR_3_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
154 | CORRIDOR_FLR_3_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
155 | CORRIDOR_FLR_3_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
156 | CORRIDOR_FLR_3_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
157 | CORRIDOR_FLR_3_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
158 | CORRIDOR_FLR_3_FLOOR_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
159 | CORRIDOR_FLR_3_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
160 | CORRIDOR_FLR_3_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
161 | CORRIDOR_FLR_3_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
163 | ROOM_1_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
165 | ROOM_1_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
167 | ROOM_1_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
168 | ROOM_1_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
169 | ROOM_1_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
170 | ROOM_1_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
171 | ROOM_1_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
172 | ROOM_2_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
174 | ROOM_2_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
176 | ROOM_2_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
177 | ROOM_2_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
178 | ROOM_2_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
179 | ROOM_2_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
180 | ROOM_2_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 3 | No | No |
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 2 | No | No |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
186 | ROOM_3_MULT9_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
187 | ROOM_3_MULT9_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
189 | BANQUET_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
191 | BANQUET_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
192 | BANQUET_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
193 | BANQUET_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
194 | BANQUET_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
195 | BANQUET_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
196 | BANQUET_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
197 | DINING_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
198 | DINING_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
199 | DINING_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
200 | DINING_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
201 | DINING_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
202 | DINING_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
203 | DINING_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
204 | DINING_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
205 | KITCHEN_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
207 | KITCHEN_FLR_6_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
212 | KITCHEN_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
213 | KITCHEN_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
214 | KITCHEN_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
215 | KITCHEN_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
216 | KITCHEN_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
217 | CORRIDOR_FLR_6_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
224 | CORRIDOR_FLR_6_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
226 | CORRIDOR_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
227 | CORRIDOR_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
228 | CORRIDOR_FLR_6_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
229 | CORRIDOR_FLR_6_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
230 | CORRIDOR_FLR_6_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
231 | CORRIDOR_FLR_6_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
232 | CORRIDOR_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
233 | CORRIDOR_FLR_6_CEILING_1 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
234 | CORRIDOR_FLR_6_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | RETAIL_1_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 7.058E-002 | 1.052E-003 | 5.193E-004 | 0.956 | 1.000 | 0.000 | 0.000 | 0.000 |
2 | RETAIL_2_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 2.724E-002 | 3.507E-004 | 9.551E-004 | 0.319 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | MECH_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | MECH_FLR_1 | 164.24 | 2.7 | 6.438E-002 | 3.920E-004 | 1.025E-003 | 0.356 | 1.000 | 0.000 | 0.000 | 0.000 |
4 | STORAGE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 3.715E-002 | 3.920E-004 | 8.507E-004 | 0.356 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | LAUNDRY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 8.791E-002 | 1.127E-003 | 1.002E-003 | 1.023 | 1.000 | 0.000 | 0.000 | 0.000 |
6 | CAFE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 0.156 | 8.261E-004 | 4.549E-004 | 0.751 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | LOBBY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 0.446 | 3.407E-004 | 6.517E-004 | 0.310 | 1.000 | 0.000 | 0.000 | 0.000 |
8 | ROOM_1_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 4.096E-002 | 1.050E-003 | 1.025E-003 | 1.240 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | ROOM_2_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 4.095E-002 | 1.050E-003 | 1.025E-003 | 1.240 | 1.000 | 0.000 | 0.000 | 0.000 |
10 | ROOM_3_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 1.143E-002 | 4.660E-004 | 1.025E-003 | 0.550 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | ROOM_4_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 1.143E-002 | 4.660E-004 | 1.025E-003 | 0.550 | 1.000 | 0.000 | 0.000 | 0.000 |
12 | ROOM_5_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 4.096E-002 | 1.050E-003 | 1.025E-003 | 1.240 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | ROOM_6_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 4.095E-002 | 1.050E-003 | 1.025E-003 | 1.240 | 1.000 | 0.000 | 0.000 | 0.000 |
14 | CORRIDOR_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_3 | 389.40 | 21.0 | 4.953E-002 | 1.272E-004 | 1.025E-003 | 0.150 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | ROOM_1_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 4.096E-002 | 1.050E-003 | 5.186E-004 | 1.240 | 1.000 | 0.000 | 0.000 | 0.000 |
16 | ROOM_2_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 4.095E-002 | 1.050E-003 | 5.186E-004 | 1.240 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | ROOM_3_MULT9_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 2.096E-002 | 8.543E-004 | 4.660E-004 | 1.009 | 1.000 | 0.000 | 0.000 | 0.000 |
18 | BANQUET_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 0.100 | 3.015E-004 | 2.330E-004 | 0.356 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | DINING_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | DINING_FLR_6 | 331.66 | 249.9 | 0.100 | 3.015E-004 | 2.330E-004 | 0.356 | 1.000 | 0.000 | 0.000 | 0.000 |
20 | KITCHEN_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 8.953E-002 | 8.667E-004 | 4.697E-004 | 1.024 | 1.000 | 0.000 | 0.000 | 0.000 |
21 | CORRIDOR_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_6 | 412.12 | 22.2 | 8.763E-002 | 2.126E-004 | 1.761E-004 | 0.251 | 1.000 | 0.000 | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | ROOM_1_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
2 | ROOM_2_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
3 | ROOM_3_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
4 | ROOM_4_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
5 | ROOM_5_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_5_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
6 | ROOM_6_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_6_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
7 | ROOM_1_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
8 | ROOM_2_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
9 | ROOM_3_MULT9_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | RETAIL_1_FLR_1 | Mixing/Well-Stirred |
3 | RETAIL_2_FLR_1 | Mixing/Well-Stirred |
4 | MECH_FLR_1 | Mixing/Well-Stirred |
5 | STORAGE_FLR_1 | Mixing/Well-Stirred |
6 | LAUNDRY_FLR_1 | Mixing/Well-Stirred |
7 | CAFE_FLR_1 | Mixing/Well-Stirred |
8 | LOBBY_FLR_1 | Mixing/Well-Stirred |
9 | ROOM_1_FLR_3 | Mixing/Well-Stirred |
10 | ROOM_2_FLR_3 | Mixing/Well-Stirred |
11 | ROOM_3_MULT19_FLR_3 | Mixing/Well-Stirred |
12 | ROOM_4_MULT19_FLR_3 | Mixing/Well-Stirred |
13 | ROOM_5_FLR_3 | Mixing/Well-Stirred |
14 | ROOM_6_FLR_3 | Mixing/Well-Stirred |
15 | CORRIDOR_FLR_3 | Mixing/Well-Stirred |
16 | ROOM_1_FLR_6 | Mixing/Well-Stirred |
17 | ROOM_2_FLR_6 | Mixing/Well-Stirred |
18 | ROOM_3_MULT9_FLR_6 | Mixing/Well-Stirred |
19 | BANQUET_FLR_6 | Mixing/Well-Stirred |
20 | DINING_FLR_6 | Mixing/Well-Stirred |
21 | KITCHEN_FLR_6 | Mixing/Well-Stirred |
22 | CORRIDOR_FLR_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 36589.01191 | 36589.01191 | 2.66161 | 2.66161 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 20:50:00 | 29.34750 | 1.71599E-002 | 1978.83018 | 106.49900 | 0.85446 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 0.85446 | 00:10:00 | 8.70000 | 6.99286E-003 | 1978.83018 | 106.49900 | 0.85446 | 0.00000 | |
3 | RETAIL_1_FLR_1 | Cooling | 4035.57954 | 4035.57954 | 0.29364 | 0.29364 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 33.20000 | 1.71672E-002 | 67.07136 | 10.82900 | 7.92179E-002 | 0.00000 |
4 | RETAIL_1_FLR_1 | Heating | 1572.80713 | 1572.80713 | 6.74942E-002 | 7.92179E-002 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 8.70000 | 6.99286E-003 | 67.07136 | 10.82900 | 7.92179E-002 | 0.00000 |
5 | RETAIL_2_FLR_1 | Cooling | 3329.50875 | 3329.50875 | 0.24224 | 0.24224 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:50:00 | 31.70367 | 1.71644E-002 | 77.66889 | 12.54000 | 9.17347E-002 | 0.00000 |
6 | RETAIL_2_FLR_1 | Heating | 502.99216 | 502.99216 | 2.15852E-002 | 9.17347E-002 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 8.70000 | 6.99286E-003 | 77.66889 | 12.54000 | 9.17347E-002 | 0.00000 |
7 | MECH_FLR_1 | Cooling | 3594.32209 | 3594.32209 | 0.26146 | 0.26146 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 30.75450 | 1.71626E-002 | 164.24319 | 2.65200 | 0.00000 | 0.00000 |
8 | MECH_FLR_1 | Heating | 925.33319 | 925.33319 | 3.97094E-002 | 3.97094E-002 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 8.70000 | 6.99286E-003 | 164.24319 | 2.65200 | 0.00000 | 0.00000 |
9 | STORAGE_FLR_1 | Cooling | 1794.42221 | 1794.42221 | 0.13053 | 0.13053 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 31.92700 | 1.71648E-002 | 94.75927 | 2.04000 | 5.77652E-002 | 0.00000 |
10 | STORAGE_FLR_1 | Heating | 543.47567 | 543.47567 | 2.33225E-002 | 5.77652E-002 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 8.70000 | 6.99286E-003 | 94.75927 | 2.04000 | 5.77652E-002 | 0.00000 |
11 | LAUNDRY_FLR_1 | Cooling | 44900.51934 | 44900.51934 | 3.26667 | 3.26667 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 33.06600 | 1.71670E-002 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
12 | LAUNDRY_FLR_1 | Heating | 1311.94393 | 1311.94393 | 5.62998E-002 | 5.62998E-002 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 8.70000 | 6.99286E-003 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
13 | CAFE_FLR_1 | Cooling | 17983.22870 | 17983.22870 | 1.30953 | 1.30953 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 33.20000 | 1.71672E-002 | 188.86188 | 142.30000 | 0.67639 | 0.00000 |
14 | CAFE_FLR_1 | Heating | 3920.75997 | 3920.75997 | 0.16825 | 0.67639 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 8.70000 | 6.99286E-003 | 188.86188 | 142.30000 | 0.67639 | 0.00000 |
15 | LOBBY_FLR_1 | Cooling | 62635.18369 | 62635.18369 | 4.55831 | 4.55831 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 33.20000 | 1.71672E-002 | 1308.18612 | 422.43500 | 1.89399 | 0.00000 |
16 | LOBBY_FLR_1 | Heating | 8822.87733 | 8822.87733 | 0.37862 | 1.89399 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 8.70000 | 6.99286E-003 | 1308.18612 | 422.43500 | 1.89399 | 0.00000 |
17 | ROOM_1_FLR_3 | Cooling | 10694.98336 | 10694.98336 | 1.04854 | 1.04854 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 32.26200 | 1.71654E-002 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
18 | ROOM_1_FLR_3 | Heating | 3659.98235 | 3659.98235 | 0.15798 | 0.15798 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 8.70000 | 6.99286E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
19 | ROOM_2_FLR_3 | Cooling | 10800.34449 | 10800.34449 | 1.05887 | 1.05887 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 32.15033 | 1.71652E-002 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
20 | ROOM_2_FLR_3 | Heating | 3660.21081 | 3660.21081 | 0.15799 | 0.15799 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 8.70000 | 6.99286E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
21 | ROOM_3_MULT19_FLR_3 | Cooling | 60738.62655 | 60738.62655 | 5.95398 | 5.95398 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 33.20000 | 1.71672E-002 | 24.52384 | 1.50000 | 0.83707 | 0.00000 |
22 | ROOM_3_MULT19_FLR_3 | Heating | 21298.59993 | 21298.59993 | 0.91937 | 0.91937 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 8.70000 | 6.99286E-003 | 24.52384 | 1.50000 | 0.83707 | 0.00000 |
23 | ROOM_4_MULT19_FLR_3 | Cooling | 70888.06309 | 70888.06309 | 6.94940 | 6.94940 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:40:00 | 31.81533 | 1.71646E-002 | 24.53055 | 1.50000 | 0.83730 | 0.00000 |
24 | ROOM_4_MULT19_FLR_3 | Heating | 21316.20758 | 21316.20758 | 0.92013 | 0.92013 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 8.70000 | 6.99286E-003 | 24.53055 | 1.50000 | 0.83730 | 0.00000 |
25 | ROOM_5_FLR_3 | Cooling | 9614.46511 | 9614.46511 | 0.94261 | 0.94261 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 30.65400 | 1.71624E-002 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
26 | ROOM_5_FLR_3 | Heating | 3659.02059 | 3659.02059 | 0.15794 | 0.15794 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 8.70000 | 6.99286E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
27 | ROOM_6_FLR_3 | Cooling | 9695.83900 | 9695.83900 | 0.95059 | 0.95059 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 30.65400 | 1.71624E-002 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
28 | ROOM_6_FLR_3 | Heating | 3659.24905 | 3659.24905 | 0.15795 | 0.15795 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 8.70000 | 6.99286E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
29 | CORRIDOR_FLR_3 | Cooling | 15134.36803 | 15134.36803 | 1.10093 | 1.10093 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 32.26200 | 1.71654E-002 | 389.40468 | 20.95700 | 0.47476 | 0.00000 |
30 | CORRIDOR_FLR_3 | Heating | 5760.67018 | 5760.67018 | 0.24721 | 0.47476 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 8.70000 | 6.99286E-003 | 389.40468 | 20.95700 | 0.47476 | 0.00000 |
31 | ROOM_1_FLR_6 | Cooling | 2858.56632 | 2858.56632 | 0.28025 | 0.28025 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 32.26200 | 1.71654E-002 | 39.02202 | 1.50000 | 1.54338E-002 | 0.00000 |
32 | ROOM_1_FLR_6 | Heating | 1124.66297 | 1124.66297 | 4.85464E-002 | 4.85464E-002 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 8.70000 | 6.99286E-003 | 39.02202 | 1.50000 | 1.54338E-002 | 0.00000 |
33 | ROOM_2_FLR_6 | Cooling | 2884.01452 | 2884.01452 | 0.28275 | 0.28275 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 32.26200 | 1.71654E-002 | 39.01745 | 1.50000 | 1.54319E-002 | 0.00000 |
34 | ROOM_2_FLR_6 | Heating | 1124.88987 | 1124.88987 | 4.85562E-002 | 4.85562E-002 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 8.70000 | 6.99286E-003 | 39.01745 | 1.50000 | 1.54319E-002 | 0.00000 |
35 | ROOM_3_MULT9_FLR_6 | Cooling | 11887.51615 | 11887.51615 | 1.16545 | 1.16545 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 33.20000 | 1.71672E-002 | 24.53055 | 1.50000 | 9.91540E-002 | 0.00000 |
36 | ROOM_3_MULT9_FLR_6 | Heating | 5435.91576 | 5435.91576 | 0.23464 | 0.23464 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 8.70000 | 6.99286E-003 | 24.53055 | 1.50000 | 9.91540E-002 | 0.00000 |
37 | BANQUET_FLR_6 | Cooling | 30711.73528 | 30711.73528 | 2.23686 | 2.23686 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 33.20000 | 1.71672E-002 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
38 | BANQUET_FLR_6 | Heating | 3704.57566 | 3704.57566 | 0.15898 | 1.18780 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 8.70000 | 6.99286E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
39 | DINING_FLR_6 | Cooling | 32227.39038 | 32227.39038 | 2.34722 | 2.34722 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 33.20000 | 1.71672E-002 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
40 | DINING_FLR_6 | Heating | 3634.68411 | 3634.68411 | 0.15598 | 1.18780 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 04:20:00 | 8.70000 | 6.99286E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
41 | KITCHEN_FLR_6 | Cooling | 30873.17563 | 30873.17563 | 2.25188 | 2.25188 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 32.59700 | 1.71661E-002 | 103.30446 | 22.23800 | 0.36735 | 0.00000 |
42 | KITCHEN_FLR_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.36735 | 00:10:00 | 8.70000 | 6.99286E-003 | 103.30446 | 22.23800 | 0.36735 | 0.00000 | |
43 | CORRIDOR_FLR_6 | Cooling | 9118.13863 | 9118.13863 | 0.66329 | 0.66329 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 33.20000 | 1.71672E-002 | 412.12471 | 22.18000 | 0.12562 | 0.00000 |
44 | CORRIDOR_FLR_6 | Heating | 3842.74498 | 3842.74498 | 0.16491 | 0.16491 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 04:30:00 | 8.70000 | 6.99286E-003 | 412.12471 | 22.18000 | 0.12562 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV WITH REHEAT | Cooling | Sensible | 522995.19 | 21.21247 | 21.21247 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | VAV WITH REHEAT | Heating | Sensible | 68958.03 | 7.13212 | 7.13212 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 04:30:00 |
3 | FLR_3_DOAS | Cooling | Sensible | 50573.62 | 18.18276 | 2.05125 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | FLR_3_DOAS | Heating | Sensible | 19832.79 | 2.80312 | 2.05125 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.66161 |
2 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.56652 |
3 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.99500 |
4 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.64830 |
5 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
6 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 6.72521E-004 |
8 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.22184E-004 |
9 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.64830 |
10 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
11 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
12 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 13966.40810 |
13 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.22184E-004 |
14 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 291.24536 |
15 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.29364 |
16 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.17405 |
17 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.99500 |
18 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.29217 |
19 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.99500 |
20 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
21 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.18899E-003 |
22 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.72336E-005 |
23 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.29217 |
24 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
25 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
26 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 3112.96912 |
27 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.72336E-005 |
28 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 68.55718 |
29 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.24224 |
30 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.24432 |
31 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.99500 |
32 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.24103 |
33 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.99500 |
34 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
35 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.55944E-003 |
36 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.55156E-005 |
37 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.24103 |
38 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
40 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1773.52546 |
41 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.55156E-005 |
42 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 37.75893 |
43 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.26146 |
44 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.47868 |
45 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.99500 |
46 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.26015 |
47 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
48 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
49 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 7.95939E-004 |
50 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.00910E-005 |
51 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.26015 |
52 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
53 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
54 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 2296.52015 |
55 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.00910E-005 |
56 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 49.63033 |
57 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.13053 |
58 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.55318 |
59 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.99500 |
60 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.12988 |
61 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
62 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 6.88741E-004 |
64 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.07434E-005 |
65 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.12988 |
66 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
67 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
68 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1228.03352 |
69 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.07434E-005 |
70 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 26.71151 |
71 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 3.26667 |
72 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 7.22368E-002 |
73 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.99500 |
74 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 3.25034 |
75 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.99500 |
76 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
77 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.09296E-002 |
78 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.61353E-004 |
79 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 3.25034 |
80 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
81 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
82 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 18443.64925 |
83 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.61353E-004 |
84 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 386.13097 |
85 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.30953 |
86 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10990 |
87 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.99500 |
88 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.30298 |
89 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.99500 |
90 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
91 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.46690E-003 |
92 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.43928E-005 |
93 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.30298 |
94 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
96 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 10789.67552 |
97 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.43928E-005 |
98 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 231.87490 |
99 | Fan:ZoneExhaust | LOBBY_FLR_1 EXHAUST FAN | User-Specified Maximum Flow Rate [m3/s] | 0.00000 |
100 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 4.55831 |
101 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.21869 |
102 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.99500 |
103 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 4.53552 |
104 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.99500 |
105 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
106 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.74223E-003 |
107 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.86349E-004 |
108 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 4.53552 |
109 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
110 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
111 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 32731.43609 |
112 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.86349E-004 |
113 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 695.87081 |
114 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_1_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17350E-002 |
115 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.04854 |
116 | Fan:OnOff | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.04854 |
117 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 3.20189E-005 |
118 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 4.88014E-004 |
119 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 22.48737 |
120 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
121 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.87242E-003 |
122 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
123 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
124 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.88014E-004 |
125 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.04854 |
126 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 3659.95589 |
127 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.20189E-005 |
128 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 104.57399 |
129 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_2_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17278E-002 |
130 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.05887 |
131 | Fan:OnOff | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.05887 |
132 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 3.20209E-005 |
133 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 4.92391E-004 |
134 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 22.48738 |
135 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
136 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.86870E-003 |
137 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
138 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
139 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.92391E-004 |
140 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.05887 |
141 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 3660.18435 |
142 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.20209E-005 |
143 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 104.58052 |
144 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_3_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.83707 |
145 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 5.95398 |
146 | Fan:OnOff | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 5.95398 |
147 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.86329E-004 |
148 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.71443E-003 |
149 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 22.48878 |
150 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
151 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.78469E-003 |
152 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
153 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
154 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.71443E-003 |
155 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 5.95398 |
156 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 21298.52566 |
157 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.86329E-004 |
158 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 608.54680 |
159 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_4_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.83730 |
160 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 6.94940 |
161 | Fan:OnOff | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 6.94940 |
162 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.86483E-004 |
163 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.28815E-003 |
164 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 22.48777 |
165 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
166 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.94306E-003 |
167 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
168 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
169 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.28815E-003 |
170 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 6.94940 |
171 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 21316.13324 |
172 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.86483E-004 |
173 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 609.04986 |
174 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_5_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17350E-002 |
175 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.94261 |
176 | Fan:OnOff | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.94261 |
177 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 3.20105E-005 |
178 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 4.43087E-004 |
179 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 22.48723 |
180 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
181 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.91497E-003 |
182 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
183 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
184 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.43087E-004 |
185 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.94261 |
186 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 3658.99414 |
187 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.20105E-005 |
188 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 104.54651 |
189 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_6_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17278E-002 |
190 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.95059 |
191 | Fan:OnOff | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.95059 |
192 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 3.20125E-005 |
193 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 4.46514E-004 |
194 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 22.48724 |
195 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
196 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.91185E-003 |
197 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
198 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
199 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.46514E-004 |
200 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.95059 |
201 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 3659.22260 |
202 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.20125E-005 |
203 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 104.55304 |
204 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.10093 |
205 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 1.00000 |
206 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.99500 |
207 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.09543 |
208 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
209 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
210 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.53403E-004 |
211 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.00920E-004 |
212 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.09543 |
213 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
214 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
215 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 11535.77444 |
216 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.00920E-004 |
217 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 253.72322 |
218 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_1_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.54338E-002 |
219 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.28025 |
220 | Fan:OnOff | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.28025 |
221 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 9.83897E-006 |
222 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 1.29737E-004 |
223 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 22.48745 |
224 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
225 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.84955E-003 |
226 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
227 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
228 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.29737E-004 |
229 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.28025 |
230 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 1124.65482 |
231 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.83897E-006 |
232 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 32.13355 |
233 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_2_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.54319E-002 |
234 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.28275 |
235 | Fan:OnOff | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.28275 |
236 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 9.84096E-006 |
237 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 1.30788E-004 |
238 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 22.48745 |
239 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
240 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.84615E-003 |
241 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
242 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
243 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.30788E-004 |
244 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.28275 |
245 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 1124.88172 |
246 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.84096E-006 |
247 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 32.14004 |
248 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_3_MULT9_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 9.91540E-002 |
249 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.16545 |
250 | Fan:OnOff | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.16545 |
251 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 4.75555E-005 |
252 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 5.52624E-004 |
253 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 22.48724 |
254 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
255 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.95259E-003 |
256 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
257 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
258 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 5.52624E-004 |
259 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.16545 |
260 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 5435.88386 |
261 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.75555E-005 |
262 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 155.31309 |
263 | Fan:ZoneExhaust | BANQUET_FLR_6 EXHAUST FAN | User-Specified Maximum Flow Rate [m3/s] | 0.00000 |
264 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.23686 |
265 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11298 |
266 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.99500 |
267 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.22568 |
268 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.99500 |
269 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
270 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.37225E-003 |
271 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.35067E-004 |
272 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.22568 |
273 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
274 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
275 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 15438.99176 |
276 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.35067E-004 |
277 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 327.31152 |
278 | Fan:ZoneExhaust | DINING_FLR_6 EXHAUST FAN | User-Specified Maximum Flow Rate [m3/s] | 0.00000 |
279 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.34722 |
280 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10767 |
281 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.99500 |
282 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.33548 |
283 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.99500 |
284 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
285 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.53862E-003 |
286 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.39520E-004 |
287 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.33548 |
288 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
289 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
290 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 15947.95577 |
291 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.39520E-004 |
292 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 337.73531 |
293 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.25188 |
294 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.83832 |
295 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.99500 |
296 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.24062 |
297 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.99500 |
298 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
299 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.08992E-002 |
300 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.03375E-004 |
301 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.24062 |
302 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
303 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
304 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 11816.38933 |
305 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.03375E-004 |
306 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 246.41043 |
307 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.66329 |
308 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.47345 |
309 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.99500 |
310 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.65998 |
311 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
312 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
313 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 8.04726E-004 |
314 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.40598E-005 |
315 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.65998 |
316 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
317 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
318 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 7322.42882 |
319 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.40598E-005 |
320 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 162.01228 |
321 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 21.21755 |
322 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 21.21755 |
323 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 21.32417 |
324 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 21.21755 |
325 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 21.21755 |
326 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 21.21755 |
327 | AirLoopHVAC | VAV WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
328 | AirLoopHVAC | VAV WITH REHEAT | Calculated Heating Air Flow Ratio [] | 1.00000 |
329 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.05132 |
330 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.05132 |
331 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.05132 |
332 | AirLoopHVAC | FLR_3_DOAS | Adjusted Heating Design Air Flow Rate [m3/s] | 2.05132 |
333 | AirLoopHVAC | FLR_3_DOAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.05132 |
334 | AirLoopHVAC | FLR_3_DOAS | Adjusted Main Design Air Flow Rate [m3/s] | 2.05132 |
335 | AirLoopHVAC | FLR_3_DOAS | User Heating Air Flow Ratio [] | 0.30000 |
336 | AirLoopHVAC | FLR_3_DOAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
337 | AirLoopHVAC | VAV WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 21.21755 |
338 | AirLoopHVAC | FLR_3_DOAS | Design Supply Air Flow Rate [m3/s] | 2.05132 |
339 | Controller:OutdoorAir | VAV WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 21.21755 |
340 | Controller:OutdoorAir | VAV WITH REHEAT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 21.21247 |
341 | HeatExchanger:AirToAir:SensibleAndLatent | VAV WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 21.21247 |
342 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 33.20000 |
343 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
344 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.00309 |
345 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.71672E-002 |
346 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
347 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 1144947.37232 |
348 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.08949E-002 |
349 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 21.21755 |
350 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 61543.58415 |
351 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.38410E-004 |
352 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 1142.02404 |
353 | Fan:VariableVolume | VAV WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 21.21755 |
354 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 4.08949E-002 |
355 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.16443E-005 |
356 | Controller:WaterCoil | VAV WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 5.38410E-004 |
357 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.05132 |
358 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.05125 |
359 | HeatExchanger:AirToAir:SensibleAndLatent | FLR_3_DOAS OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.05125 |
360 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 33.20000 |
361 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
362 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.94186 |
363 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.71672E-002 |
364 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
365 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Coil Load [W] | 108329.82081 |
366 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.86929E-003 |
367 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 2.05132 |
368 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size Rated Capacity [W] | 5950.04693 |
369 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.20536E-005 |
370 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 110.41113 |
371 | Fan:ConstantVolume | FLR_3_DOAS FAN | User-Specified Maximum Flow Rate [m3/s] | 2.05125 |
372 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 3.86929E-003 |
373 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.23069E-004 |
374 | Controller:WaterCoil | FLR_3_DOAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 5.20536E-005 |
375 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 5.34499E-002 |
376 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 11014.04150 |
377 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 2.43938E-003 |
378 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 0.29273 |
379 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 2.43938E-003 |
380 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 734.63336 |
381 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
382 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 278835.82468 |
383 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 278835.82000 |
384 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 2.43938E-003 |
385 | PlantLoop | COOLSYS1 | Maximum Loop Flow Rate [m3/s] | 5.34499E-002 |
386 | PlantLoop | COOLSYS1 | Plant Loop Volume [m3] | 6.41399 |
387 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Flow Rate [m3/s] | 5.34499E-002 |
388 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Power Consumption [W] | 7625.39242 |
389 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 5.34499E-002 |
390 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 1496454.59945 |
391 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 1497043.85000 |
392 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 170.66300 |
393 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 3.75036E-004 |
394 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 4.50044E-002 |
395 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 3.75036E-004 |
396 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 47.90688 |
397 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 3.75036E-004 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | 14038.54 |
2 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 3128.03 |
3 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 1782.51 |
4 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | 2307.99 |
5 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | 1234.13 |
6 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 18538.55 |
7 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | 10843.85 |
8 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | 32897.42 |
9 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | 3941.71 |
10 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | 3941.96 |
11 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | 22938.09 |
12 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | 22957.06 |
13 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | 3940.68 |
14 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | 3940.92 |
15 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 11591.66 |
16 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | 1211.22 |
17 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | 1211.47 |
18 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | 5854.28 |
19 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | 15517.49 |
20 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | 16029.13 |
21 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | 11877.42 |
22 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 7357.68 |
23 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | 55098.44 |
24 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | 5326.93 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | 19045.41 | 14862.37 | 4183.04 | 0.78 | 2098.68 | 21.29 |
2 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | 19222.62 | 15003.60 | 4219.01 | 0.78 | 2118.25 | 21.48 |
3 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | 106764.62 | 83705.91 | 23058.71 | 0.78 | 11771.74 | 119.40 |
4 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | 127516.44 | 99143.27 | 28373.17 | 0.78 | 14045.78 | 142.46 |
5 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | 17226.59 | 13413.16 | 3813.43 | 0.78 | 1897.78 | 19.25 |
6 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | 17364.64 | 13522.84 | 3841.80 | 0.78 | 1913.02 | 19.40 |
7 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | 5073.53 | 3964.00 | 1109.53 | 0.78 | 559.15 | 5.67 |
8 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | 5116.16 | 3998.03 | 1118.13 | 0.78 | 563.86 | 5.72 |
9 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | 21413.41 | 16640.84 | 4772.57 | 0.78 | 2358.57 | 23.92 |
10 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | 715419.77 | 456961.22 | 258458.55 | 0.64 | 89905.40 | 911.87 |
11 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | 67803.65 | 43510.62 | 24293.03 | 0.64 | 8145.92 | 82.62 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | 3.72 | 12.68 |
Zone Name | # Surfaces | |
1 | BASEMENT | 14 |
2 | RETAIL_1_FLR_1 | 8 |
3 | RETAIL_2_FLR_1 | 8 |
4 | MECH_FLR_1 | 7 |
5 | STORAGE_FLR_1 | 8 |
6 | LAUNDRY_FLR_1 | 8 |
7 | CAFE_FLR_1 | 10 |
8 | LOBBY_FLR_1 | 22 |
9 | ROOM_1_FLR_3 | 9 |
10 | ROOM_2_FLR_3 | 9 |
11 | ROOM_3_MULT19_FLR_3 | 8 |
12 | ROOM_4_MULT19_FLR_3 | 8 |
13 | ROOM_5_FLR_3 | 9 |
14 | ROOM_6_FLR_3 | 9 |
15 | CORRIDOR_FLR_3 | 25 |
16 | ROOM_1_FLR_6 | 9 |
17 | ROOM_2_FLR_6 | 9 |
18 | ROOM_3_MULT9_FLR_6 | 8 |
19 | BANQUET_FLR_6 | 8 |
20 | DINING_FLR_6 | 8 |
21 | KITCHEN_FLR_6 | 12 |
22 | CORRIDOR_FLR_6 | 19 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.940 | 0.824 | 211.13 | 211.13 | 211.13 | 0.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.940 | 0.824 | 55.76 | 55.76 | 55.76 | 90.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.940 | 0.824 | 211.13 | 211.13 | 211.13 | 180.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_WEST_CFACTOR | 0.940 | 0.824 | 55.76 | 55.76 | 55.76 | 270.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | BASEMENT_FLOOR | 2.705 | 1.632 | 1978.83 | 1978.83 | 1978.83 | 0.00 | 180.00 | 86.56 | 22.86 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | BASEMENT_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.412 | 0.383 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | RETAIL_1_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | BASEMENT_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.412 | 0.383 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | BASEMENT_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.412 | 0.383 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | BASEMENT_CEILING_4 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.412 | 0.383 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_CEILING_5 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.412 | 0.383 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
11 | BASEMENT_CEILING_6 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.412 | 0.383 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | CAFE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
12 | BASEMENT_CEILING_7 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.412 | 0.383 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 0.00 | 32.99 | 32.99 | 0.00 | LOBBY_FLR_1_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
13 | BASEMENT_CEILING_8 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.412 | 0.383 | 219.63 | 219.63 | 219.63 | 90.00 | 0.00 | 14.82 | 14.82 | 0.00 | LOBBY_FLR_1_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
14 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 3957.66 | 3957.66 | 3957.66 | 0.00 | 90.00 | 3957.66 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
15 | RETAIL_1_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.214 | 1.028 | 22.63 | 45.89 | 22.63 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | Window | RETAIL_1_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5119_SHGC_0.25 | N/A | 2.910 | No | 23.26 | 23.26 | 23.26 | 180.00 | 90.00 | 10.92 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
17 | RETAIL_1_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.214 | 1.028 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
18 | RETAIL_1_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | RETAIL_1_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | RETAIL_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.412 | 0.375 | 67.07 | 67.07 | 67.07 | 0.00 | 180.00 | 11.58 | 5.79 | 0.00 | BASEMENT_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | RETAIL_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 7.62E-002 | 0.92 | 4 | ||
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 134.14 | 134.14 | 134.14 | 0.00 | 90.00 | 134.14 | 1.00 | 0.00 | RETAIL_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
23 | RETAIL_2_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.214 | 1.028 | 24.62 | 26.57 | 24.62 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | Door | RETAIL_2_FLR_1_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
25 | RETAIL_2_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
26 | RETAIL_2_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | RETAIL_2_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 90.00 | 90.00 | 6.71 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | RETAIL_2_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.412 | 0.375 | 77.67 | 77.67 | 77.67 | 0.00 | 180.00 | 11.58 | 6.71 | 0.00 | BASEMENT_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
29 | RETAIL_2_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.412 | 0.383 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 155.34 | 155.34 | 155.34 | 0.00 | 90.00 | 155.34 | 1.00 | 0.00 | RETAIL_2_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
31 | MECH_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.214 | 1.028 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | MECH_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | MECH_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 180.00 | 90.00 | 15.85 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | MECH_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | MECH_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.412 | 0.375 | 164.24 | 164.24 | 164.24 | 0.00 | 180.00 | 15.85 | 10.36 | 0.00 | BASEMENT_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | MECH_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.412 | 0.383 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | MECH_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 328.49 | 328.49 | 328.49 | 0.00 | 90.00 | 328.49 | 1.00 | 0.00 | MECH_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | STORAGE_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.214 | 1.028 | 28.80 | 36.23 | 28.80 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | Door | STORAGE_FLR_1_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.198 | 1.198 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | STORAGE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
41 | STORAGE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 180.00 | 90.00 | 9.14 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
42 | STORAGE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | STORAGE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.412 | 0.375 | 94.76 | 94.76 | 94.76 | 0.00 | 180.00 | 9.14 | 10.36 | 0.00 | BASEMENT_CEILING_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
44 | STORAGE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.412 | 0.383 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | STORAGE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 189.52 | 189.52 | 189.52 | 0.00 | 90.00 | 189.52 | 1.00 | 0.00 | STORAGE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
46 | LAUNDRY_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.214 | 1.028 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | LAUNDRY_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.214 | 1.028 | 65.68 | 67.63 | 65.68 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | Door | LAUNDRY_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
49 | LAUNDRY_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 180.00 | 90.00 | 4.57 | 3.96 | 0.00 | CAFE_FLR_1_WALL_2_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | LAUNDRY_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 270.00 | 90.00 | 17.07 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
51 | LAUNDRY_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.412 | 0.375 | 78.04 | 78.04 | 78.04 | 0.00 | 180.00 | 4.57 | 17.07 | 0.00 | BASEMENT_CEILING_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
52 | LAUNDRY_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.412 | 0.383 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 156.08 | 156.08 | 156.08 | 0.00 | 90.00 | 156.08 | 1.00 | 0.00 | LAUNDRY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
54 | CAFE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.214 | 1.028 | 21.00 | 22.95 | 21.00 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CAFE_FLR_1_WALL_EAST_DOOR | Door | CAFE_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | CAFE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.214 | 1.028 | 63.73 | 129.23 | 63.73 | 180.00 | 90.00 | 32.61 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | Window | CAFE_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5119_SHGC_0.25 | N/A | 2.910 | No | 65.50 | 65.50 | 65.50 | 180.00 | 90.00 | 30.75 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
58 | CAFE_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 0.00 | 90.00 | 28.04 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | CAFE_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | CAFE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | CAFE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.412 | 0.375 | 188.86 | 188.86 | 188.86 | 0.00 | 180.00 | 32.61 | 5.79 | 0.00 | BASEMENT_CEILING_6 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
62 | CAFE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 3.86E-002 | 0.96 | 4 | ||
63 | CAFE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 377.72 | 377.72 | 377.72 | 0.00 | 90.00 | 377.72 | 1.00 | 0.00 | CAFE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
64 | LOBBY_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.214 | 1.028 | 209.87 | 213.77 | 209.87 | 0.00 | 90.00 | 53.95 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
67 | LOBBY_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.214 | 1.028 | 12.08 | 12.08 | 12.08 | 0.00 | 90.00 | 3.05 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
68 | LOBBY_FLR_1_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.214 | 1.028 | 82.79 | 167.88 | 82.79 | 180.00 | 90.00 | 42.37 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | Window | LOBBY_FLR_1_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5119_SHGC_0.25 | N/A | 2.910 | No | 85.08 | 85.08 | 85.08 | 180.00 | 90.00 | 39.95 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LOBBY_FLR_1_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.214 | 1.028 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | LOBBY_FLR_1_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | LOBBY_FLR_1_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 180.00 | 90.00 | 28.04 | 3.96 | 0.00 | CAFE_FLR_1_WALL_1_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | LOBBY_FLR_1_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | LOBBY_FLR_1_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | LOBBY_FLR_1_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | LOBBY_FLR_1_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | MECH_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | LOBBY_FLR_1_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
78 | LOBBY_FLR_1_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | LOBBY_FLR_1_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | CAFE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | LOBBY_FLR_1_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | LOBBY_FLR_1_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.412 | 0.375 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 180.00 | 32.99 | 32.99 | 0.00 | BASEMENT_CEILING_7 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
82 | LOBBY_FLR_1_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.412 | 0.375 | 219.63 | 219.63 | 219.63 | 90.00 | 180.00 | 14.82 | 14.82 | 0.00 | BASEMENT_CEILING_8 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
83 | LOBBY_FLR_1_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.412 | 0.383 | 1062.83 | 1062.83 | 1062.83 | 270.00 | 0.00 | 32.60 | 32.60 | 0.00 | LOBBY_FLR_1_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 10 | ||
84 | LOBBY_FLR_1_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 245.35 | 245.35 | 245.35 | 180.00 | 0.00 | 42.37 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.22E-003 | 1.00 | 4 | ||
85 | LOBBY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 2616.37 | 2616.37 | 2616.37 | 0.00 | 90.00 | 2616.37 | 1.00 | 0.00 | LOBBY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | ROOM_1_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.530 | 1.245 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.5119_SHGC_0.25 | N/A | 2.910 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | ROOM_1_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.530 | 1.245 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | Window | ROOM_1_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.5119_SHGC_0.25 | N/A | 2.910 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | ROOM_1_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | ROOM_1_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | ROOM_1_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.412 | 0.375 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
93 | ROOM_1_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.412 | 0.383 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
94 | ROOM_1_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
95 | ROOM_2_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.530 | 1.245 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.5119_SHGC_0.25 | N/A | 2.910 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
97 | ROOM_2_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.530 | 1.245 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | Window | ROOM_2_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.5119_SHGC_0.25 | N/A | 2.910 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | ROOM_2_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | ROOM_2_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | ROOM_2_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.412 | 0.375 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | ROOM_2_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.412 | 0.383 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | ROOM_2_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.530 | 1.245 | 7.47 | 11.15 | 7.47 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.5119_SHGC_0.25 | N/A | 2.910 | No | 3.68 | 3.68 | 3.68 | 180.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | ROOM_3_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.412 | 0.375 | 24.52 | 24.52 | 24.52 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
110 | ROOM_3_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.412 | 0.383 | 24.52 | 24.52 | 24.52 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.05 | 49.05 | 49.05 | 0.00 | 90.00 | 49.05 | 1.00 | 0.00 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.530 | 1.245 | 7.47 | 11.15 | 7.47 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_4_MULT19_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.5119_SHGC_0.25 | N/A | 2.910 | No | 3.68 | 3.68 | 3.68 | 0.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
117 | ROOM_4_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.412 | 0.375 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
118 | ROOM_4_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.412 | 0.383 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
120 | ROOM_5_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.530 | 1.245 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | Window | ROOM_5_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.5119_SHGC_0.25 | N/A | 2.910 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
122 | ROOM_5_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.530 | 1.245 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_5_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.5119_SHGC_0.25 | N/A | 2.910 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
124 | ROOM_5_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
125 | ROOM_5_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
126 | ROOM_5_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.412 | 0.375 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
127 | ROOM_5_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.412 | 0.383 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
128 | ROOM_5_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_5_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
129 | ROOM_6_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.530 | 1.245 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_6_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.5119_SHGC_0.25 | N/A | 2.910 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
131 | ROOM_6_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.530 | 1.245 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | Window | ROOM_6_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.5119_SHGC_0.25 | N/A | 2.910 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
133 | ROOM_6_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
134 | ROOM_6_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
135 | ROOM_6_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.412 | 0.375 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
136 | ROOM_6_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.412 | 0.383 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
137 | ROOM_6_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_6_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
138 | CORRIDOR_FLR_3_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.530 | 1.245 | 11.83 | 17.65 | 11.83 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5119_SHGC_0.25 | N/A | 2.910 | No | 5.82 | 5.82 | 5.82 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.530 | 1.245 | 4.35 | 6.50 | 4.35 | 0.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5119_SHGC_0.25 | N/A | 2.910 | No | 2.15 | 2.15 | 2.15 | 0.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.530 | 1.245 | 4.36 | 6.50 | 4.36 | 180.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5119_SHGC_0.25 | N/A | 2.910 | No | 2.15 | 2.15 | 2.15 | 180.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.530 | 1.245 | 11.83 | 17.65 | 11.83 | 180.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5119_SHGC_0.25 | N/A | 2.910 | No | 5.82 | 5.82 | 5.82 | 180.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 0.00 | 90.00 | 69.50 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | CORRIDOR_FLR_3_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | CORRIDOR_FLR_3_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORRIDOR_FLR_3_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | CORRIDOR_FLR_3_WALL_4_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 180.00 | 90.00 | 69.49 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
152 | CORRIDOR_FLR_3_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | CORRIDOR_FLR_3_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | CORRIDOR_FLR_3_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | CORRIDOR_FLR_3_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | CORRIDOR_FLR_3_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.412 | 0.375 | 74.32 | 74.32 | 74.32 | 180.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
157 | CORRIDOR_FLR_3_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.412 | 0.375 | 240.77 | 240.77 | 240.77 | 270.00 | 180.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | CORRIDOR_FLR_3_FLOOR_3 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.412 | 0.375 | 74.32 | 74.32 | 74.32 | 90.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
159 | CORRIDOR_FLR_3_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.412 | 0.383 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
160 | CORRIDOR_FLR_3_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.412 | 0.383 | 240.77 | 240.77 | 240.77 | 90.00 | 0.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
161 | CORRIDOR_FLR_3_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.412 | 0.383 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 778.81 | 778.81 | 778.81 | 0.00 | 90.00 | 778.81 | 1.00 | 0.00 | CORRIDOR_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
163 | ROOM_1_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.605 | 1.294 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.5119_SHGC_0.25 | N/A | 2.910 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
165 | ROOM_1_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.605 | 1.294 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | Window | ROOM_1_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.5119_SHGC_0.25 | N/A | 2.910 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
167 | ROOM_1_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
168 | ROOM_1_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
169 | ROOM_1_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.412 | 0.375 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | ROOM_1_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.283 | 0.269 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
171 | ROOM_1_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
172 | ROOM_2_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.605 | 1.294 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.5119_SHGC_0.25 | N/A | 2.910 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
174 | ROOM_2_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.605 | 1.294 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | Window | ROOM_2_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.5119_SHGC_0.25 | N/A | 2.910 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
176 | ROOM_2_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
177 | ROOM_2_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
178 | ROOM_2_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.412 | 0.375 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | ROOM_2_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.283 | 0.269 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
180 | ROOM_2_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.605 | 1.294 | 13.70 | 20.44 | 13.70 | 180.00 | 90.00 | 6.71 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.5119_SHGC_0.25 | N/A | 2.910 | No | 6.74 | 6.74 | 6.74 | 180.00 | 90.00 | 5.53 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 0.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 90.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | ROOM_3_MULT9_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.412 | 0.375 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 6.71 | 3.66 | 0.00 | ROOM_3_MULT9_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
187 | ROOM_3_MULT9_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.283 | 0.269 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 6.71 | 3.66 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
189 | BANQUET_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.605 | 1.294 | 65.36 | 97.55 | 65.36 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | Window | BANQUET_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5119_SHGC_0.25 | N/A | 2.910 | No | 32.19 | 32.19 | 32.19 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
191 | BANQUET_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
192 | BANQUET_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
193 | BANQUET_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
194 | BANQUET_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.412 | 0.375 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | BANQUET_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
195 | BANQUET_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
196 | BANQUET_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | BANQUET_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
197 | DINING_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.605 | 1.294 | 65.36 | 97.55 | 65.36 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DINING_FLR_6_WALL_NORTH_WINDOW | Window | DINING_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5119_SHGC_0.25 | N/A | 2.910 | No | 32.19 | 32.19 | 32.19 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
199 | DINING_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
200 | DINING_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | DINING_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DINING_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DINING_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.412 | 0.375 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | DINING_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
203 | DINING_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
204 | DINING_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | DINING_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
205 | KITCHEN_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.605 | 1.294 | 16.77 | 21.37 | 16.77 | 0.00 | 90.00 | 7.01 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | Window | KITCHEN_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5119_SHGC_0.25 | N/A | 2.910 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
207 | KITCHEN_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.605 | 1.294 | 34.86 | 52.03 | 34.86 | 90.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | Window | KITCHEN_FLR_6_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5119_SHGC_0.25 | N/A | 2.910 | No | 17.17 | 17.17 | 17.17 | 90.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.605 | 1.294 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | Window | KITCHEN_FLR_6_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5119_SHGC_0.25 | N/A | 2.910 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 7.43 | 7.43 | 7.43 | 180.00 | 90.00 | 2.44 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
212 | KITCHEN_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | KITCHEN_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | KITCHEN_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.412 | 0.375 | 103.30 | 103.30 | 103.30 | 180.00 | 180.00 | 10.16 | 10.16 | 0.00 | KITCHEN_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
215 | KITCHEN_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 103.30 | 103.30 | 103.30 | 270.00 | 0.00 | 10.16 | 10.16 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
216 | KITCHEN_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 206.61 | 206.61 | 206.61 | 0.00 | 90.00 | 206.61 | 1.00 | 0.00 | KITCHEN_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
217 | CORRIDOR_FLR_6_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.605 | 1.294 | 11.83 | 17.65 | 11.83 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5119_SHGC_0.25 | N/A | 2.910 | No | 5.82 | 5.82 | 5.82 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.605 | 1.294 | 10.58 | 15.79 | 10.58 | 0.00 | 90.00 | 5.18 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5119_SHGC_0.25 | N/A | 2.910 | No | 5.21 | 5.21 | 5.21 | 0.00 | 90.00 | 4.27 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.605 | 1.294 | 34.86 | 52.03 | 34.86 | 180.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5119_SHGC_0.25 | N/A | 2.910 | No | 17.17 | 17.17 | 17.17 | 180.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
224 | CORRIDOR_FLR_6_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 104.98 | 104.98 | 104.98 | 0.00 | 90.00 | 34.44 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 183.95 | 183.95 | 183.95 | 180.00 | 90.00 | 60.35 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
226 | CORRIDOR_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
227 | CORRIDOR_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 40.88 | 40.88 | 40.88 | 270.00 | 90.00 | 13.41 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
228 | CORRIDOR_FLR_6_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
229 | CORRIDOR_FLR_6_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
230 | CORRIDOR_FLR_6_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
231 | CORRIDOR_FLR_6_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
232 | CORRIDOR_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.412 | 0.375 | 412.12 | 412.12 | 412.12 | 180.00 | 180.00 | 20.30 | 20.30 | 0.00 | CORRIDOR_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 12 | ||
233 | CORRIDOR_FLR_6_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 244.71 | 244.71 | 244.71 | 90.00 | 0.00 | 15.64 | 15.64 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 8 | ||
234 | CORRIDOR_FLR_6_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 167.42 | 167.42 | 167.42 | 270.00 | 0.00 | 12.94 | 12.94 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 824.25 | 824.25 | 824.25 | 0.00 | 90.00 | 824.25 | 1.00 | 0.00 | CORRIDOR_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 1.0123312565E-002 | 1.5529076649E-002 | Pass | Pass | 8.6574210045E-003 | 2.2650915352E-002 | Pass | Pass |
2 | RETAIL_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 4.3552702111E-002 | 5.8683237315E-002 | Pass | Pass | 1.8515056031E-002 | 2.3357103678E-002 | Pass | Pass |
3 | RETAIL_2_FLR_1 | RunPeriod: RUNPERIOD 1 | 8.4917147630E-003 | 1.5502544456E-002 | Pass | Pass | 1.1276603747E-002 | 2.2836817766E-002 | Pass | Pass |
4 | MECH_FLR_1 | RunPeriod: RUNPERIOD 1 | 2.9532623579E-003 | 8.6627287479E-003 | Pass | Pass | 1.1925706467E-002 | 2.2383726876E-002 | Pass | Pass |
5 | STORAGE_FLR_1 | RunPeriod: RUNPERIOD 1 | 6.0317837553E-004 | 4.3770986779E-004 | Pass | Pass | 1.1330029339E-002 | 1.4342601135E-002 | Pass | Pass |
6 | LAUNDRY_FLR_1 | RunPeriod: RUNPERIOD 1 | 3.7637726636E-002 | 0.1096346367 | Pass | Pass | 1.8076855435E-002 | 5.1573298257E-002 | Pass | Pass |
7 | CAFE_FLR_1 | RunPeriod: RUNPERIOD 1 | 5.3090473637E-002 | 7.2367070385E-002 | Pass | Pass | 1.3900089421E-002 | 2.4300555522E-002 | Pass | Pass |
8 | LOBBY_FLR_1 | RunPeriod: RUNPERIOD 1 | 2.1490973824E-002 | 3.1012427834E-002 | Pass | Pass | 1.2372048961E-002 | 2.4844367818E-002 | Pass | Pass |
9 | ROOM_1_FLR_3 | RunPeriod: RUNPERIOD 1 | 9.2612131110E-002 | 0.3211222880 | Pass | Pass | 0.1428757758 | 0.5931658979 | Pass | Pass |
10 | ROOM_2_FLR_3 | RunPeriod: RUNPERIOD 1 | 8.5108449817E-002 | 0.2884979086 | Pass | Pass | 0.1141694445 | 0.4257993122 | Pass | Pass |
11 | ROOM_3_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 1.8434824650E-003 | 1.0351463163E-002 | Pass | Pass | 2.7708955834E-002 | 4.0711076908E-002 | Pass | Pass |
12 | ROOM_4_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 8.2285904259E-002 | 0.2555802670 | Pass | Pass | 9.7869218042E-002 | 0.3460607637 | Pass | Pass |
13 | ROOM_5_FLR_3 | RunPeriod: RUNPERIOD 1 | 9.2609247687E-002 | 0.3339123405 | Pass | Pass | 0.1230183642 | 0.4555168833 | Pass | Pass |
14 | ROOM_6_FLR_3 | RunPeriod: RUNPERIOD 1 | 9.2618757535E-002 | 0.3204904740 | Pass | Pass | 0.1575519771 | 0.6141555660 | Pass | Pass |
15 | CORRIDOR_FLR_3 | RunPeriod: RUNPERIOD 1 | 1.2273396069E-002 | 1.2959152209E-002 | Pass | Pass | 8.9996154084E-003 | 2.2894102470E-002 | Pass | Pass |
16 | ROOM_1_FLR_6 | RunPeriod: RUNPERIOD 1 | 9.2531510247E-002 | 0.3263119625 | Pass | Pass | 0.1453278347 | 0.6314684240 | Pass | Pass |
17 | ROOM_2_FLR_6 | RunPeriod: RUNPERIOD 1 | 8.3356975547E-002 | 0.2897883641 | Pass | Pass | 0.1231118583 | 0.4613293596 | Pass | Pass |
18 | ROOM_3_MULT9_FLR_6 | RunPeriod: RUNPERIOD 1 | 9.2615876950E-002 | 0.3256685305 | Pass | Pass | 9.6684721077E-002 | 0.3208063377 | Pass | Pass |
19 | BANQUET_FLR_6 | RunPeriod: RUNPERIOD 1 | 3.5873902405E-002 | 7.4037139510E-002 | Pass | Pass | 1.0231946703E-002 | 2.3922717946E-002 | Pass | Pass |
20 | DINING_FLR_6 | RunPeriod: RUNPERIOD 1 | 4.0845416108E-002 | 7.4862360589E-002 | Pass | Pass | 1.0039172855E-002 | 2.1354536174E-002 | Pass | Pass |
21 | KITCHEN_FLR_6 | RunPeriod: RUNPERIOD 1 | 5.2635936707E-002 | 0.1278310293 | Pass | Pass | 1.6818114953E-002 | 2.7936700986E-002 | Pass | Pass |
22 | CORRIDOR_FLR_6 | RunPeriod: RUNPERIOD 1 | 1.4746275878E-002 | 2.2881448847E-002 | Pass | Pass | 1.6040857542E-002 | 2.3937498104E-002 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:58:20
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 3139.16 | -214.1 | -681.0 | -12035.9 | 22433.28 | 12641.43 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:58:20
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 8.70 | 0.00 | 8.70 | Wetbulb [C] | 3.80 | 340.00 |
MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 33.20 | 6.70 | 25.30 | Wetbulb [C] | 4.50 | 140.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 65.00 | 29 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 38.00 | 14 | |||
May | 0.00 | 0 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 391.00 | 83 | |||
Sep | 0.00 | 0 | |||
Oct | 225.00 | 40 | |||
Nov | 0.00 | 0 | |||
Dec | 5.00 | 10 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:58:20
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.845 | 0.940 | 211.13 | 211.13 | 0.00 | 90.00 | N |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.845 | 0.940 | 55.76 | 55.76 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.845 | 0.940 | 211.13 | 211.13 | 180.00 | 90.00 | S |
BASEMENT_WALL_WEST | BASEMENT_WALL_WEST_CFACTOR | 1.00 | 0.845 | 0.940 | 55.76 | 55.76 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 1.028 | 1.214 | 45.89 | 22.63 | 180.00 | 90.00 | S |
RETAIL_1_FLR_1_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 1.028 | 1.214 | 22.95 | 22.95 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_CEILING | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 67.07 | 67.07 | 180.00 | 0.00 | |
RETAIL_2_FLR_1_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 1.028 | 1.214 | 26.57 | 24.62 | 270.00 | 90.00 | W |
MECH_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 1.028 | 1.214 | 62.80 | 62.80 | 0.00 | 90.00 | N |
STORAGE_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 1.028 | 1.214 | 36.23 | 28.80 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 1.028 | 1.214 | 18.12 | 18.12 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 1.028 | 1.214 | 67.63 | 65.68 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 1.028 | 1.214 | 22.95 | 21.00 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 1.028 | 1.214 | 129.23 | 63.73 | 180.00 | 90.00 | S |
CAFE_FLR_1_CEILING | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 188.86 | 188.86 | 180.00 | 0.00 | |
LOBBY_FLR_1_WALL_1_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 1.028 | 1.214 | 213.77 | 209.87 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_2_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 1.028 | 1.214 | 12.08 | 12.08 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 1.028 | 1.214 | 167.88 | 82.79 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_1_WEST | NONRES_EXT_WALL_GRD | 0.30 | 1.028 | 1.214 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_CEILING_2 | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 245.35 | 245.35 | 180.00 | 0.00 | |
ROOM_1_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 1.245 | 1.530 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_1_FLR_3_WALL_WEST | RES_EXT_WALL_MID | 0.30 | 1.245 | 1.530 | 104.06 | 69.72 | 270.00 | 90.00 | W |
ROOM_2_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 1.245 | 1.530 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_2_FLR_3_WALL_WEST | RES_EXT_WALL_MID | 0.30 | 1.245 | 1.530 | 104.05 | 69.71 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 1.245 | 1.530 | 847.14 | 567.58 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 1.245 | 1.530 | 847.37 | 567.71 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_EAST | RES_EXT_WALL_MID | 0.30 | 1.245 | 1.530 | 104.06 | 69.72 | 90.00 | 90.00 | E |
ROOM_5_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 1.245 | 1.530 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 1.245 | 1.530 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_6_FLR_3_WALL_EAST | RES_EXT_WALL_MID | 0.30 | 1.245 | 1.530 | 104.05 | 69.71 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_1_NORTH | NONRES_EXT_WALL_MID | 0.30 | 1.245 | 1.530 | 70.60 | 47.31 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_2_NORTH | NONRES_EXT_WALL_MID | 0.30 | 1.245 | 1.530 | 26.01 | 17.42 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 1.245 | 1.530 | 26.02 | 17.43 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_2_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 1.245 | 1.530 | 70.60 | 47.31 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_SOUTH | RES_EXT_WALL_TOP | 0.30 | 1.294 | 1.605 | 13.94 | 9.34 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_WEST | RES_EXT_WALL_TOP | 0.30 | 1.294 | 1.605 | 26.01 | 17.43 | 270.00 | 90.00 | W |
ROOM_1_FLR_6_CEILING | RES_ROOF | 0.55 | 0.273 | 0.283 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_2_FLR_6_WALL_NORTH | RES_EXT_WALL_TOP | 0.30 | 1.294 | 1.605 | 13.94 | 9.34 | 0.00 | 90.00 | N |
ROOM_2_FLR_6_WALL_WEST | RES_EXT_WALL_TOP | 0.30 | 1.294 | 1.605 | 26.01 | 17.43 | 270.00 | 90.00 | W |
ROOM_2_FLR_6_CEILING | RES_ROOF | 0.55 | 0.273 | 0.283 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | RES_EXT_WALL_TOP | 0.30 | 1.294 | 1.605 | 183.96 | 123.26 | 180.00 | 90.00 | S |
ROOM_3_MULT9_FLR_6_CEILING | RES_ROOF | 0.55 | 0.273 | 0.283 | 220.77 | 220.77 | 180.00 | 0.00 | |
BANQUET_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.294 | 1.605 | 97.55 | 65.36 | 0.00 | 90.00 | N |
BANQUET_FLR_6_CEILING | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 331.66 | 331.66 | 180.00 | 0.00 | |
DINING_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.294 | 1.605 | 97.55 | 65.36 | 0.00 | 90.00 | N |
DINING_FLR_6_CEILING | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 331.66 | 331.66 | 180.00 | 0.00 | |
KITCHEN_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.294 | 1.605 | 21.37 | 16.77 | 0.00 | 90.00 | N |
KITCHEN_FLR_6_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.294 | 1.605 | 52.03 | 34.86 | 90.00 | 90.00 | E |
KITCHEN_FLR_6_WALL_1_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.294 | 1.605 | 13.94 | 9.34 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_CEILING | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 103.30 | 103.30 | 270.00 | 0.00 | |
CORRIDOR_FLR_6_WALL_1_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.294 | 1.605 | 17.65 | 11.83 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.294 | 1.605 | 15.79 | 10.58 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.294 | 1.605 | 52.03 | 34.86 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_CEILING_1 | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 244.71 | 244.71 | 90.00 | 0.00 | |
CORRIDOR_FLR_6_CEILING_2 | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 167.42 | 167.42 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_FLOOR | BASEMENT_FLOOR | 0.30 | 1.441 | 2.705 | 1978.83 | 1978.83 | 0.00 | 180.00 | |
BASEMENT_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.371 | 0.412 | 67.07 | 67.07 | 180.00 | 0.00 | |
BASEMENT_CEILING_2 | NONRES_FLOOR_CEILING | 0.30 | 0.371 | 0.412 | 77.67 | 77.67 | 180.00 | 0.00 | |
BASEMENT_CEILING_3 | NONRES_FLOOR_CEILING | 0.30 | 0.371 | 0.412 | 164.24 | 164.24 | 180.00 | 0.00 | |
BASEMENT_CEILING_4 | NONRES_FLOOR_CEILING | 0.30 | 0.371 | 0.412 | 94.76 | 94.76 | 180.00 | 0.00 | |
BASEMENT_CEILING_5 | NONRES_FLOOR_CEILING | 0.30 | 0.371 | 0.412 | 78.04 | 78.04 | 180.00 | 0.00 | |
BASEMENT_CEILING_6 | NONRES_FLOOR_CEILING | 0.30 | 0.371 | 0.412 | 188.86 | 188.86 | 180.00 | 0.00 | |
BASEMENT_CEILING_7 | NONRES_FLOOR_CEILING | 0.30 | 0.371 | 0.412 | 1088.56 | 1088.56 | 180.00 | 0.00 | |
BASEMENT_CEILING_8 | NONRES_FLOOR_CEILING | 0.30 | 0.371 | 0.412 | 219.63 | 219.63 | 90.00 | 0.00 | |
RETAIL_1_FLR_1_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 0.00 | 90.00 | N |
RETAIL_1_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 90.00 | 90.00 | E |
RETAIL_1_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.371 | 0.412 | 67.07 | 67.07 | 0.00 | 180.00 | |
RETAIL_2_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 180.00 | 90.00 | S |
RETAIL_2_FLR_1_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 0.00 | 90.00 | N |
RETAIL_2_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.57 | 26.57 | 90.00 | 90.00 | E |
RETAIL_2_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.371 | 0.412 | 77.67 | 77.67 | 0.00 | 180.00 | |
RETAIL_2_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.379 | 0.412 | 77.67 | 77.67 | 180.00 | 0.00 | |
MECH_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
MECH_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 62.80 | 62.80 | 180.00 | 90.00 | S |
MECH_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
MECH_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.371 | 0.412 | 164.24 | 164.24 | 0.00 | 180.00 | |
MECH_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.379 | 0.412 | 164.24 | 164.24 | 180.00 | 0.00 | |
STORAGE_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
STORAGE_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 36.23 | 36.23 | 180.00 | 90.00 | S |
STORAGE_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
STORAGE_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.371 | 0.412 | 94.76 | 94.76 | 0.00 | 180.00 | |
STORAGE_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.379 | 0.412 | 94.76 | 94.76 | 180.00 | 0.00 | |
LAUNDRY_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 18.12 | 18.12 | 180.00 | 90.00 | S |
LAUNDRY_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 67.63 | 67.63 | 270.00 | 90.00 | W |
LAUNDRY_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.371 | 0.412 | 78.04 | 78.04 | 0.00 | 180.00 | |
LAUNDRY_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.379 | 0.412 | 78.04 | 78.04 | 180.00 | 0.00 | |
CAFE_FLR_1_WALL_1_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.11 | 111.11 | 0.00 | 90.00 | N |
CAFE_FLR_1_WALL_2_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 18.12 | 18.12 | 0.00 | 90.00 | N |
CAFE_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 270.00 | 90.00 | W |
CAFE_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.371 | 0.412 | 188.86 | 188.86 | 0.00 | 180.00 | |
LOBBY_FLR_1_WALL_2_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_3_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.11 | 111.11 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.57 | 26.57 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_4_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 62.80 | 62.80 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_4_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 36.23 | 36.23 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
LOBBY_FLR_1_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 90.00 | 90.00 | E |
LOBBY_FLR_1_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 67.63 | 67.63 | 90.00 | 90.00 | E |
LOBBY_FLR_1_FLOOR_1 | NONRES_FLOOR | 0.30 | 0.371 | 0.412 | 1088.56 | 1088.56 | 180.00 | 180.00 | |
LOBBY_FLR_1_FLOOR_2 | NONRES_FLOOR | 0.30 | 0.371 | 0.412 | 219.63 | 219.63 | 90.00 | 180.00 | |
LOBBY_FLR_1_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.379 | 0.412 | 1062.83 | 1062.83 | 270.00 | 0.00 | |
ROOM_1_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 0.00 | 90.00 | N |
ROOM_1_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 90.00 | 90.00 | E |
ROOM_1_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.364 | 0.412 | 156.09 | 156.09 | 0.00 | 180.00 | |
ROOM_1_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.379 | 0.412 | 156.09 | 156.09 | 180.00 | 0.00 | |
ROOM_2_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 90.00 | 90.00 | E |
ROOM_2_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 180.00 | 90.00 | S |
ROOM_2_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.364 | 0.412 | 156.07 | 156.07 | 0.00 | 180.00 | |
ROOM_2_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.379 | 0.412 | 156.07 | 156.07 | 180.00 | 0.00 | |
ROOM_3_MULT19_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.14 | 847.14 | 0.00 | 90.00 | N |
ROOM_3_MULT19_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 90.00 | 90.00 | E |
ROOM_3_MULT19_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.364 | 0.412 | 1863.81 | 1863.81 | 0.00 | 180.00 | |
ROOM_3_MULT19_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.379 | 0.412 | 1863.81 | 1863.81 | 180.00 | 0.00 | |
ROOM_4_MULT19_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 90.00 | 90.00 | E |
ROOM_4_MULT19_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.37 | 847.37 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 270.00 | 90.00 | W |
ROOM_4_MULT19_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.364 | 0.412 | 1864.32 | 1864.32 | 0.00 | 180.00 | |
ROOM_4_MULT19_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.379 | 0.412 | 1864.32 | 1864.32 | 180.00 | 0.00 | |
ROOM_5_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 270.00 | 90.00 | W |
ROOM_5_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.364 | 0.412 | 156.09 | 156.09 | 0.00 | 180.00 | |
ROOM_5_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.379 | 0.412 | 156.09 | 156.09 | 180.00 | 0.00 | |
ROOM_6_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 270.00 | 90.00 | W |
ROOM_6_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.364 | 0.412 | 156.07 | 156.07 | 0.00 | 180.00 | |
ROOM_6_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.379 | 0.412 | 156.07 | 156.07 | 180.00 | 0.00 | |
CORRIDOR_FLR_3_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.28 | 847.28 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_4_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_3_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.27 | 847.27 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_4_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_FLOOR_1 | NONRES_FLOOR | 0.30 | 0.364 | 0.412 | 297.29 | 297.29 | 180.00 | 180.00 | |
CORRIDOR_FLR_3_FLOOR_2 | NONRES_FLOOR | 0.30 | 0.364 | 0.412 | 963.06 | 963.06 | 270.00 | 180.00 | |
CORRIDOR_FLR_3_FLOOR_3 | NONRES_FLOOR | 0.30 | 0.364 | 0.412 | 297.26 | 297.26 | 90.00 | 180.00 | |
CORRIDOR_FLR_3_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.379 | 0.412 | 297.29 | 297.29 | 90.00 | 0.00 | |
CORRIDOR_FLR_3_CEILING_2 | NONRES_FLOOR_CEILING | 0.30 | 0.379 | 0.412 | 963.06 | 963.06 | 90.00 | 0.00 | |
CORRIDOR_FLR_3_CEILING_3 | NONRES_FLOOR_CEILING | 0.30 | 0.379 | 0.412 | 297.26 | 297.26 | 90.00 | 0.00 | |
ROOM_1_FLR_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 13.94 | 13.94 | 0.00 | 90.00 | N |
ROOM_1_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.01 | 26.01 | 90.00 | 90.00 | E |
ROOM_1_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.364 | 0.412 | 39.02 | 39.02 | 0.00 | 180.00 | |
ROOM_2_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.01 | 26.01 | 90.00 | 90.00 | E |
ROOM_2_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 13.94 | 13.94 | 180.00 | 90.00 | S |
ROOM_2_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.364 | 0.412 | 39.02 | 39.02 | 0.00 | 180.00 | |
ROOM_3_MULT9_FLR_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 183.96 | 183.96 | 0.00 | 90.00 | N |
ROOM_3_MULT9_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 100.35 | 100.35 | 90.00 | 90.00 | E |
ROOM_3_MULT9_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 100.35 | 100.35 | 270.00 | 90.00 | W |
ROOM_3_MULT9_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.364 | 0.412 | 220.77 | 220.77 | 0.00 | 180.00 | |
BANQUET_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
BANQUET_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 180.00 | 90.00 | S |
BANQUET_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
BANQUET_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.364 | 0.412 | 331.66 | 331.66 | 0.00 | 180.00 | |
DINING_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
DINING_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 180.00 | 90.00 | S |
DINING_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
DINING_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.364 | 0.412 | 331.66 | 331.66 | 0.00 | 180.00 | |
KITCHEN_FLR_6_WALL_2_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 7.43 | 7.43 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 20.44 | 20.44 | 270.00 | 90.00 | W |
KITCHEN_FLR_6_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
KITCHEN_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.364 | 0.412 | 103.30 | 103.30 | 180.00 | 180.00 | |
CORRIDOR_FLR_6_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_4_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 104.98 | 104.98 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_1_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 183.95 | 183.95 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 11.15 | 11.15 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 40.88 | 40.88 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 20.44 | 20.44 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.364 | 0.412 | 412.12 | 412.12 | 180.00 | 180.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3957.66 | 0.00 | 90.00 | N | ||
RETAIL_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 134.14 | 0.00 | 90.00 | N | ||
RETAIL_2_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 155.34 | 0.00 | 90.00 | N | ||
MECH_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 328.49 | 0.00 | 90.00 | N | ||
STORAGE_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 189.52 | 0.00 | 90.00 | N | ||
LAUNDRY_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 156.08 | 0.00 | 90.00 | N | ||
CAFE_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 377.72 | 0.00 | 90.00 | N | ||
LOBBY_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 2616.37 | 0.00 | 90.00 | N | ||
ROOM_1_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.18 | 0.00 | 90.00 | N | ||
ROOM_2_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.14 | 0.00 | 90.00 | N | ||
ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3727.63 | 0.00 | 90.00 | N | ||
ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3728.64 | 0.00 | 90.00 | N | ||
ROOM_5_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.18 | 0.00 | 90.00 | N | ||
ROOM_6_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.14 | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3115.24 | 0.00 | 90.00 | N | ||
ROOM_1_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 78.04 | 0.00 | 90.00 | N | ||
ROOM_2_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 78.03 | 0.00 | 90.00 | N | ||
ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 441.55 | 0.00 | 90.00 | N | ||
BANQUET_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 663.31 | 0.00 | 90.00 | N | ||
DINING_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 663.31 | 0.00 | 90.00 | N | ||
KITCHEN_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 206.61 | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 824.25 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.5119_SHGC_0.25 | 23.26 | 0.00 | 0.00 | 23.26 | 23.26 | 2.910 | 0.251 | 0.251 | No | RETAIL_1_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
CAFE_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.5119_SHGC_0.25 | 65.50 | 0.00 | 0.00 | 65.50 | 65.50 | 2.910 | 0.251 | 0.251 | No | CAFE_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
LOBBY_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.5119_SHGC_0.25 | 85.08 | 0.00 | 0.00 | 85.08 | 85.08 | 2.910 | 0.251 | 0.251 | No | LOBBY_FLR_1_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.5119_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.910 | 0.251 | 0.251 | No | ROOM_1_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.5119_SHGC_0.25 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.910 | 0.251 | 0.251 | No | ROOM_1_FLR_3_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_2_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.5119_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.910 | 0.251 | 0.251 | No | ROOM_2_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_2_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.5119_SHGC_0.25 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.910 | 0.251 | 0.251 | No | ROOM_2_FLR_3_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.5119_SHGC_0.25 | 3.68 | 0.00 | 0.00 | 3.68 | 279.56 | 2.910 | 0.251 | 0.251 | No | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.5119_SHGC_0.25 | 3.68 | 0.00 | 0.00 | 3.68 | 279.65 | 2.910 | 0.251 | 0.251 | No | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_5_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.5119_SHGC_0.25 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.910 | 0.251 | 0.251 | No | ROOM_5_FLR_3_WALL_EAST | 90.00 | 90.00 | E | |||||||
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.5119_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.910 | 0.251 | 0.251 | No | ROOM_5_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_6_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.5119_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.910 | 0.251 | 0.251 | No | ROOM_6_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_6_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.5119_SHGC_0.25 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.910 | 0.251 | 0.251 | No | ROOM_6_FLR_3_WALL_EAST | 90.00 | 90.00 | E | |||||||
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.5119_SHGC_0.25 | 5.82 | 0.00 | 0.00 | 5.82 | 23.30 | 2.910 | 0.251 | 0.251 | No | CORRIDOR_FLR_3_WALL_1_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.5119_SHGC_0.25 | 2.15 | 0.00 | 0.00 | 2.15 | 8.59 | 2.910 | 0.251 | 0.251 | No | CORRIDOR_FLR_3_WALL_2_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.5119_SHGC_0.25 | 2.15 | 0.00 | 0.00 | 2.15 | 8.58 | 2.910 | 0.251 | 0.251 | No | CORRIDOR_FLR_3_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.5119_SHGC_0.25 | 5.82 | 0.00 | 0.00 | 5.82 | 23.30 | 2.910 | 0.251 | 0.251 | No | CORRIDOR_FLR_3_WALL_2_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.5119_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.910 | 0.251 | 0.251 | No | ROOM_1_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.5119_SHGC_0.25 | 8.58 | 0.00 | 0.00 | 8.58 | 8.58 | 2.910 | 0.251 | 0.251 | No | ROOM_1_FLR_6_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_2_FLR_6_WALL_NORTH_WINDOW | RESWINDOW_U_0.5119_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.910 | 0.251 | 0.251 | No | ROOM_2_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_2_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.5119_SHGC_0.25 | 8.58 | 0.00 | 0.00 | 8.58 | 8.58 | 2.910 | 0.251 | 0.251 | No | ROOM_2_FLR_6_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.5119_SHGC_0.25 | 6.74 | 0.00 | 0.00 | 6.74 | 60.70 | 2.910 | 0.251 | 0.251 | No | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
BANQUET_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.5119_SHGC_0.25 | 32.19 | 0.00 | 0.00 | 32.19 | 32.19 | 2.910 | 0.251 | 0.251 | No | BANQUET_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
DINING_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.5119_SHGC_0.25 | 32.19 | 0.00 | 0.00 | 32.19 | 32.19 | 2.910 | 0.251 | 0.251 | No | DINING_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
KITCHEN_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.5119_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.910 | 0.251 | 0.251 | No | KITCHEN_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
KITCHEN_FLR_6_WALL_EAST_WINDOW | NONRESWINDOW_U_0.5119_SHGC_0.25 | 17.17 | 0.00 | 0.00 | 17.17 | 17.17 | 2.910 | 0.251 | 0.251 | No | KITCHEN_FLR_6_WALL_EAST | 90.00 | 90.00 | E | |||||||
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.5119_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.910 | 0.251 | 0.251 | No | KITCHEN_FLR_6_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.5119_SHGC_0.25 | 5.82 | 0.00 | 0.00 | 5.82 | 5.82 | 2.910 | 0.251 | 0.251 | No | CORRIDOR_FLR_6_WALL_1_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.5119_SHGC_0.25 | 5.21 | 0.00 | 0.00 | 5.21 | 5.21 | 2.910 | 0.251 | 0.251 | No | CORRIDOR_FLR_6_WALL_2_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.5119_SHGC_0.25 | 17.17 | 0.00 | 0.00 | 17.17 | 17.17 | 2.910 | 0.251 | 0.251 | No | CORRIDOR_FLR_6_WALL_2_SOUTH | 180.00 | 90.00 | S | |||||||
Total or Average | 1213.79 | 2.910 | 0.251 | 0.251 | |||||||||||||||||
North Total or Average | 432.95 | 2.910 | 0.251 | 0.251 | |||||||||||||||||
Non-North Total or Average | 780.84 | 2.910 | 0.251 | 0.251 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
RETAIL_2_FLR_1_WALL_WEST_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | RETAIL_2_FLR_1_WALL_WEST |
STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | OVERHEAD DOOR_CON | 1.016 | 1.198 | 7.43 | STORAGE_FLR_1_WALL_NORTH |
LAUNDRY_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | LAUNDRY_FLR_1_WALL_EAST |
CAFE_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | CAFE_FLR_1_WALL_EAST |
LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:58:20
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
CAFE_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LOBBY_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
BANQUET_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:58:20
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 8.7495 | 1978.83 | 17313.73 | LightsWired | LTG_SCH_BASEMENT | 50.91 | 168.00 | 50.86 | 0.0000 | Y | 165.29 |
RETAIL_1_FLR_1_LIGHTS | RETAIL_1_FLR_1 | RETAIL_1_FLR_1 | GENERAL | 13.0124 | 67.07 | 872.76 | LightsWired | LTG_SCH_RETAIL | 51.36 | 168.00 | 51.30 | 0.0000 | Y | 8.40 |
RETAIL_2_FLR_1_LIGHTS | RETAIL_2_FLR_1 | RETAIL_2_FLR_1 | GENERAL | 13.0124 | 77.67 | 1010.66 | LightsWired | LTG_SCH_RETAIL | 51.36 | 168.00 | 51.30 | 0.0000 | Y | 9.73 |
MECH_FLR_1_LIGHTS | MECH_FLR_1 | MECH_FLR_1 | GENERAL | 10.0642 | 164.24 | 1652.98 | LightsWired | LTG_SCH_MECHANIC | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 18.19 |
STORAGE_FLR_1_LIGHTS | STORAGE_FLR_1 | STORAGE_FLR_1 | GENERAL | 7.3195 | 94.76 | 693.59 | LightsWired | LTG_SCH_STORAGE | 25.68 | 168.00 | 25.65 | 0.0000 | Y | 3.34 |
LAUNDRY_FLR_1_LIGHTS | LAUNDRY_FLR_1 | LAUNDRY_FLR_1 | GENERAL | 5.4896 | 78.04 | 428.40 | LightsWired | LTG_SCH_LAUNDRY | 51.36 | 168.00 | 51.30 | 0.0000 | Y | 4.13 |
CAFE_FLR_1_LIGHTS | CAFE_FLR_1 | CAFE_FLR_1 | GENERAL | 12.8090 | 188.86 | 2419.14 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 26.62 |
LOBBY_FLR_1_LIGHTS | LOBBY_FLR_1 | LOBBY_FLR_1 | GENERAL | 10.0642 | 1308.19 | 13165.91 | LightsWired | LTG_SCH_LOBBY | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 144.89 |
ROOM_1_FLR_3_LIGHTS | ROOM_1_FLR_3 | ROOM_1_FLR_3 | GENERAL | 10.0642 | 156.09 | 1570.91 | LightsWired | LTG_SCH_GUESTROOM | 69.03 | 168.00 | 69.21 | 0.0000 | Y | 20.41 |
ROOM_2_FLR_3_LIGHTS | ROOM_2_FLR_3 | ROOM_2_FLR_3 | GENERAL | 10.0642 | 156.07 | 1570.72 | LightsWired | LTG_SCH_GUESTROOM | 69.03 | 168.00 | 69.21 | 0.0000 | Y | 20.41 |
ROOM_3_MULT19_FLR_3_LIGHTS | ROOM_3_MULT19_FLR_3 | ROOM_3_MULT19_FLR_3 | GENERAL | 10.0642 | 1863.81 | 18757.86 | LightsWired | LTG_SCH_GUESTROOM | 69.03 | 168.00 | 69.21 | 0.0000 | Y | 243.70 |
ROOM_4_MULT19_FLR_3_LIGHTS | ROOM_4_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | GENERAL | 10.0642 | 1864.32 | 18762.99 | LightsWired | LTG_SCH_GUESTROOM | 69.03 | 168.00 | 69.21 | 0.0000 | Y | 243.77 |
ROOM_5_FLR_3_LIGHTS | ROOM_5_FLR_3 | ROOM_5_FLR_3 | GENERAL | 10.0642 | 156.09 | 1570.91 | LightsWired | LTG_SCH_GUESTROOM | 69.03 | 168.00 | 69.21 | 0.0000 | Y | 20.41 |
ROOM_6_FLR_3_LIGHTS | ROOM_6_FLR_3 | ROOM_6_FLR_3 | GENERAL | 10.0642 | 156.07 | 1570.72 | LightsWired | LTG_SCH_GUESTROOM | 69.03 | 168.00 | 69.21 | 0.0000 | Y | 20.41 |
CORRIDOR_FLR_3_LIGHTS | CORRIDOR_FLR_3 | CORRIDOR_FLR_3 | GENERAL | 3.6597 | 1557.62 | 5700.46 | LightsWired | LTG_SCH_CORRIDOR | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 62.73 |
ROOM_1_FLR_6_LIGHTS | ROOM_1_FLR_6 | ROOM_1_FLR_6 | GENERAL | 10.0642 | 39.02 | 392.73 | LightsWired | LTG_SCH_GUESTROOM | 69.03 | 168.00 | 69.21 | 0.0000 | Y | 5.10 |
ROOM_2_FLR_6_LIGHTS | ROOM_2_FLR_6 | ROOM_2_FLR_6 | GENERAL | 10.0642 | 39.02 | 392.68 | LightsWired | LTG_SCH_GUESTROOM | 69.03 | 168.00 | 69.21 | 0.0000 | Y | 5.10 |
ROOM_3_MULT9_FLR_6_LIGHTS | ROOM_3_MULT9_FLR_6 | ROOM_3_MULT9_FLR_6 | GENERAL | 10.0642 | 220.77 | 2221.93 | LightsWired | LTG_SCH_GUESTROOM | 69.03 | 168.00 | 69.21 | 0.0000 | Y | 28.87 |
BANQUET_FLR_6_LIGHTS | BANQUET_FLR_6 | BANQUET_FLR_6 | GENERAL | 12.8090 | 331.66 | 4248.21 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 46.75 |
DINING_FLR_6_LIGHTS | DINING_FLR_6 | DINING_FLR_6 | GENERAL | 12.8090 | 331.66 | 4248.21 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 46.75 |
KITCHEN_FLR_6_LIGHTS | KITCHEN_FLR_6 | KITCHEN_FLR_6 | GENERAL | 10.9792 | 103.30 | 1134.20 | LightsWired | LTG_SCH_KITCHEN | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 12.48 |
CORRIDOR_FLR_6_LIGHTS | CORRIDOR_FLR_6 | CORRIDOR_FLR_6 | GENERAL | 3.6597 | 412.12 | 1508.26 | LightsWired | LTG_SCH_CORRIDOR | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 16.60 |
Interior Lighting Total | 8.9207 | 11345.29 | 101207.97 | 559.10 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR FACADE LIGHTING | 16690.39 | AstronomicalClock | - | 83.82 | 83.82 | 262.62 | |
Exterior Lighting Total | 16690.39 | 262.62 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:58:20
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
HEATSYS1 BOILER | Boiler:HotWater | 278835.82 | 0.80 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:EIR | 1497043.85 | 2.80 | 1497306.99 | 2.80 | 3.72 | 12.68 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 13663.36 | 19045.41 | 14862.37 | 4183.04 | 0.78 | - | 2098.68 | 21.29 |
ROOM_2_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 13785.91 | 19222.62 | 15003.60 | 4219.01 | 0.78 | - | 2118.25 | 21.48 |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 75998.17 | 106764.62 | 83705.91 | 23058.71 | 0.78 | - | 11771.74 | 119.40 |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 92061.17 | 127516.44 | 99143.27 | 28373.17 | 0.78 | - | 14045.78 | 142.46 |
ROOM_5_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 12405.48 | 17226.59 | 13413.16 | 3813.43 | 0.78 | - | 1897.78 | 19.25 |
ROOM_6_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 12501.43 | 17364.64 | 13522.84 | 3841.80 | 0.78 | - | 1913.02 | 19.40 |
ROOM_1_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 3632.37 | 5073.53 | 3964.00 | 1109.53 | 0.78 | - | 559.15 | 5.67 |
ROOM_2_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 3661.77 | 5116.16 | 3998.03 | 1118.13 | 0.78 | - | 563.86 | 5.72 |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 15472.29 | 21413.41 | 16640.84 | 4772.57 | 0.78 | - | 2358.57 | 23.92 |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | 1144947.37 | 715419.77 | 456961.22 | 258458.55 | 0.64 | - | 89905.40 | 911.87 |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | 108329.82 | 67803.65 | 43510.62 | 24293.03 | 0.64 | - | 8145.92 | 82.62 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
BASEMENT VAV BOX REHEAT COIL | Coil:Heating:Water | 13966.41 | 14038.54 | - |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 3112.97 | 3128.03 | - |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1773.53 | 1782.51 | - |
MECH_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 2296.52 | 2307.99 | - |
STORAGE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1228.03 | 1234.13 | - |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 18443.65 | 18538.55 | - |
CAFE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 10789.68 | 10843.85 | - |
LOBBY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 32731.44 | 32897.42 | - |
ROOM_1_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 3659.96 | 3941.71 | - |
ROOM_2_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 3660.18 | 3941.96 | - |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 21298.53 | 22938.09 | - |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 21316.13 | 22957.06 | - |
ROOM_5_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 3658.99 | 3940.68 | - |
ROOM_6_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 3659.22 | 3940.92 | - |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 11535.77 | 11591.66 | - |
ROOM_1_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 1124.65 | 1211.22 | - |
ROOM_2_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 1124.88 | 1211.47 | - |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 5435.88 | 5854.28 | - |
BANQUET_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 15438.99 | 15517.49 | - |
DINING_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 15947.96 | 16029.13 | - |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 11816.39 | 11877.42 | - |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 7322.43 | 7357.68 | - |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | 61543.58 | 55098.44 | - |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | 5950.05 | 5326.93 | - |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
LAUNDRY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 0.16 | 125.00 | 0.24 | 184.35 | 781.25 | 1.00 | 1.15 | General | ||
LOBBY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | General | |||
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.16 | 270.90 | 1.05 | 1775.31 | 1693.12 | 1.00 | 0.49 | General | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 |
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.16 | 270.90 | 1.06 | 1792.80 | 1693.12 | 1.00 | 0.49 | General | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 |
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.16 | 270.90 | 5.95 | 10080.83 | 1693.12 | 1.00 | 0.40 | General | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 |
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.16 | 270.90 | 6.95 | 11766.20 | 1693.12 | 1.00 | 0.39 | General | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:40:00 |
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.16 | 270.90 | 0.94 | 1595.96 | 1693.12 | 1.00 | 0.50 | General | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 |
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.16 | 270.90 | 0.95 | 1609.46 | 1693.12 | 1.00 | 0.50 | General | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 |
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.16 | 270.90 | 0.28 | 474.51 | 1693.12 | 1.00 | 0.73 | General | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 |
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.16 | 270.90 | 0.28 | 478.73 | 1693.12 | 1.00 | 0.73 | General | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 |
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.16 | 270.90 | 1.17 | 1973.24 | 1693.12 | 1.00 | 0.48 | General | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 |
BANQUET_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | General | |||
DINING_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | General | |||
KITCHEN_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 0.16 | 125.00 | 1.89 | 1474.84 | 781.25 | 1.00 | 0.62 | General | ||
VAV WITH REHEAT FAN | Fan:VariableVolume | 0.62 | 1389.42 | 21.22 | 47540.86 | 2240.64 | 1.00 | 1.11 | General | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 04:30:00 |
FLR_3_DOAS FAN | Fan:ConstantVolume | 0.58 | 622.50 | 2.05 | 2194.93 | 1070.05 | 1.00 | 1.30 | General | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 133527.72 | 0.053450 | 11014.04 | 206062.94 | 0.90 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.002439 | 734.63 | 301156.09 | 0.90 | General |
COOLSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 92445.74 | 0.053450 | 7625.39 | 142664.32 | 0.90 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000375 | 47.91 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWH BOOSTER E WATER HEATER | WaterHeater:Mixed | 0.02 | 8000.00 | 1.00 | 1.24 | 1.15 |
SWH LAUNDRY G WATER HEATER | WaterHeater:Mixed | 1.14 | 163316.00 | 0.80 | 0.58 | 0.51 |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 2.27 | 175842.60 | 0.80 | 0.26 | 0.03 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:58:20
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 36589.01 | 36589.01 | 18.49 | 2.662 | 2.662 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 20:50:00 | 24.00 | 24.00 | 0.00916 | 29.35 | 0.01716 | 0.854 | 0.00 |
RETAIL_1_FLR_1 | 4035.58 | 4035.58 | 60.17 | 0.294 | 0.294 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 24.00 | 24.00 | 0.00953 | 33.20 | 0.01717 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 3329.51 | 3329.51 | 42.87 | 0.242 | 0.242 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:50:00 | 24.00 | 24.00 | 0.00955 | 31.70 | 0.01716 | 0.092 | 0.00 |
MECH_FLR_1 | 3594.32 | 3594.32 | 21.88 | 0.261 | 0.261 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 24.00 | 24.00 | 0.00913 | 30.75 | 0.01716 | 0.000 | 0.00 |
STORAGE_FLR_1 | 1794.42 | 1794.42 | 18.94 | 0.131 | 0.131 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 24.00 | 24.00 | 0.00928 | 31.93 | 0.01716 | 0.058 | 0.00 |
LAUNDRY_FLR_1 | 44900.52 | 44900.52 | 575.36 | 3.267 | 3.267 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 24.00 | 24.00 | 0.00860 | 33.07 | 0.01717 | 0.000 | 0.00 |
CAFE_FLR_1 | 17983.23 | 17983.23 | 95.22 | 1.310 | 1.310 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 24.00 | 23.99 | 0.01047 | 33.20 | 0.01717 | 0.676 | 0.00 |
LOBBY_FLR_1 | 62635.18 | 62635.18 | 47.88 | 4.558 | 4.558 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 24.00 | 23.99 | 0.01019 | 33.20 | 0.01717 | 1.894 | 0.00 |
ROOM_1_FLR_3 | 10694.98 | 10694.98 | 274.08 | 1.049 | 1.049 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 21.11 | 21.11 | 0.00887 | 32.26 | 0.01717 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 10800.34 | 10800.34 | 276.81 | 1.059 | 1.059 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 21.11 | 21.11 | 0.00887 | 32.15 | 0.01717 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 60738.63 | 60738.63 | 2476.72 | 5.954 | 5.954 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 21.11 | 21.11 | 0.00878 | 33.20 | 0.01717 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 70888.06 | 70888.06 | 2889.79 | 6.949 | 6.949 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:40:00 | 21.11 | 21.11 | 0.00894 | 31.82 | 0.01716 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 9614.47 | 9614.47 | 246.39 | 0.943 | 0.943 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 21.11 | 21.11 | 0.00891 | 30.65 | 0.01716 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 9695.84 | 9695.84 | 248.50 | 0.951 | 0.951 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 21.11 | 21.11 | 0.00891 | 30.65 | 0.01716 | 0.062 | 0.00 |
CORRIDOR_FLR_3 | 15134.37 | 15134.37 | 38.87 | 1.101 | 1.101 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 24.00 | 24.00 | 0.01006 | 32.26 | 0.01717 | 0.475 | 0.00 |
ROOM_1_FLR_6 | 2858.57 | 2858.57 | 73.26 | 0.280 | 0.280 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 21.11 | 21.11 | 0.00885 | 32.26 | 0.01717 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 2884.01 | 2884.01 | 73.92 | 0.283 | 0.283 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 21.11 | 21.11 | 0.00885 | 32.26 | 0.01717 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 11887.52 | 11887.52 | 484.60 | 1.165 | 1.165 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 21.11 | 21.11 | 0.00895 | 33.20 | 0.01717 | 0.099 | 0.00 |
BANQUET_FLR_6 | 30711.74 | 30711.74 | 92.60 | 2.237 | 2.237 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 24.00 | 23.98 | 0.01041 | 33.20 | 0.01717 | 1.188 | 0.00 |
DINING_FLR_6 | 32227.39 | 32227.39 | 97.17 | 2.347 | 2.347 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 24.00 | 23.98 | 0.01032 | 33.20 | 0.01717 | 1.188 | 0.00 |
KITCHEN_FLR_6 | 30873.18 | 30873.18 | 298.86 | 2.252 | 2.252 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 24.00 | 23.97 | 0.01014 | 32.60 | 0.01717 | 0.367 | 0.00 |
CORRIDOR_FLR_6 | 9118.14 | 9118.14 | 22.12 | 0.663 | 0.663 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 24.00 | 24.00 | 0.00930 | 33.20 | 0.01717 | 0.126 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 0.854 | 00:10:00 | 21.00 | 23.64 | 0.00699 | 8.70 | 0.00699 | 0.854 | 0.00 | |
RETAIL_1_FLR_1 | 1572.81 | 1572.81 | 23.45 | 0.067 | 0.079 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 21.00 | 21.00 | 0.00779 | 8.70 | 0.00699 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 502.99 | 502.99 | 6.48 | 0.022 | 0.092 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 21.00 | 21.00 | 0.00775 | 8.70 | 0.00699 | 0.092 | 0.00 |
MECH_FLR_1 | 925.33 | 925.33 | 5.63 | 0.040 | 0.040 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 21.00 | 21.00 | 0.00770 | 8.70 | 0.00699 | 0.000 | 0.00 |
STORAGE_FLR_1 | 543.48 | 543.48 | 5.74 | 0.023 | 0.058 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 21.00 | 21.00 | 0.00771 | 8.70 | 0.00699 | 0.058 | 0.00 |
LAUNDRY_FLR_1 | 1311.94 | 1311.94 | 16.81 | 0.056 | 0.056 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 21.00 | 21.00 | 0.00771 | 8.70 | 0.00699 | 0.000 | 0.00 |
CAFE_FLR_1 | 3920.76 | 3920.76 | 20.76 | 0.168 | 0.676 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 21.00 | 21.00 | 0.00781 | 8.70 | 0.00699 | 0.676 | 0.00 |
LOBBY_FLR_1 | 8822.88 | 8822.88 | 6.74 | 0.379 | 1.894 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 21.00 | 21.00 | 0.00777 | 8.70 | 0.00699 | 1.894 | 0.00 |
ROOM_1_FLR_3 | 3659.98 | 3659.98 | 93.79 | 0.158 | 0.158 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 21.11 | 21.11 | 0.00779 | 8.70 | 0.00699 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 3660.21 | 3660.21 | 93.81 | 0.158 | 0.158 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 21.11 | 21.11 | 0.00779 | 8.70 | 0.00699 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 21298.60 | 21298.60 | 868.49 | 0.919 | 0.919 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 21.11 | 21.11 | 0.00780 | 8.70 | 0.00699 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 21316.21 | 21316.21 | 868.97 | 0.920 | 0.920 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 21.11 | 21.11 | 0.00780 | 8.70 | 0.00699 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 3659.02 | 3659.02 | 93.77 | 0.158 | 0.158 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 21.11 | 21.11 | 0.00779 | 8.70 | 0.00699 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 3659.25 | 3659.25 | 93.78 | 0.158 | 0.158 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 21.11 | 21.11 | 0.00779 | 8.70 | 0.00699 | 0.062 | 0.00 |
CORRIDOR_FLR_3 | 5760.67 | 5760.67 | 14.79 | 0.247 | 0.475 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00783 | 8.70 | 0.00699 | 0.475 | 0.00 |
ROOM_1_FLR_6 | 1124.66 | 1124.66 | 28.82 | 0.049 | 0.049 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 21.11 | 21.11 | 0.00782 | 8.70 | 0.00699 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 1124.89 | 1124.89 | 28.83 | 0.049 | 0.049 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 21.11 | 21.11 | 0.00782 | 8.70 | 0.00699 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 5435.92 | 5435.92 | 221.60 | 0.235 | 0.235 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 21.11 | 21.11 | 0.00783 | 8.70 | 0.00699 | 0.099 | 0.00 |
BANQUET_FLR_6 | 3704.58 | 3704.58 | 11.17 | 0.159 | 1.188 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 21.00 | 21.00 | 0.00786 | 8.70 | 0.00699 | 1.188 | 0.00 |
DINING_FLR_6 | 3634.68 | 3634.68 | 10.96 | 0.156 | 1.188 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 04:20:00 | 21.00 | 21.00 | 0.00786 | 8.70 | 0.00699 | 1.188 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.367 | 00:10:00 | 21.00 | 23.42 | 0.00675 | 8.70 | 0.00699 | 0.367 | 0.00 | |
CORRIDOR_FLR_6 | 3842.74 | 3842.74 | 9.32 | 0.165 | 0.165 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 04:30:00 | 21.00 | 21.00 | 0.00788 | 8.70 | 0.00699 | 0.126 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV WITH REHEAT | 21.21 | 21.21 | 7.13 | 7.13 | 21.2175 | 21.2175 | 21.2175 | 1.0000 | 0.3000 |
FLR_3_DOAS | 18.18 | 2.05 | 2.80 | 2.05 | 2.0513 | 2.0513 | 2.0513 | 1.0000 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
BASEMENT VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | 13966.408 | 13966.408 | 2.648302 | 0.00012218 | 291.245 | 1/21 00:10:00 | 1/21 00:10:00 | 13966.41 | 13966.41 | 2.648302 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 21.00 | 0.00800000 | 51.6560 | 0.00 | 0.00 | 14044.90 | 14044.90 | ||
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | 3112.969 | 3112.969 | 0.292169 | 0.00002723 | 68.557 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 3112.97 | 3112.97 | 0.292169 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 21.00 | 0.00778658 | 50.2955 | 1572.81 | 0.00 | 3129.94 | 3129.94 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | 1773.525 | 1773.525 | 0.241029 | 0.00001552 | 37.759 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 1773.53 | 1773.53 | 0.241029 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 21.00 | 0.00775321 | 50.0823 | 502.99 | 0.00 | 1783.42 | 1783.42 |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | 2296.520 | 2296.520 | 0.260148 | 0.00002009 | 49.630 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 2296.52 | 2296.52 | 0.260148 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 21.00 | 0.00770362 | 49.7659 | 925.33 | 0.00 | 2309.28 | 2309.28 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | 1228.034 | 1228.034 | 0.129877 | 0.00001074 | 26.712 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 1228.03 | 1228.03 | 0.129877 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 21.00 | 0.00770734 | 49.7896 | 543.48 | 0.00 | 1234.84 | 1234.84 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 18443.649 | 18443.649 | 3.250336 | 0.00016135 | 386.131 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 18443.65 | 18443.65 | 3.250336 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 21.00 | 0.00771145 | 49.8162 | 1311.94 | 0.00 | 18547.16 | 18547.16 |
CAFE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | 10789.676 | 10789.676 | 1.302981 | 0.00009439 | 231.875 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 10789.68 | 10789.68 | 1.302981 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 21.00 | 0.00780610 | 50.4199 | 3920.76 | 0.00 | 10849.71 | 10849.71 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 32731.436 | 32731.436 | 4.535523 | 0.00028635 | 695.871 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 32731.44 | 32731.44 | 4.535523 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 21.00 | 0.00776594 | 50.1635 | 8822.88 | 0.00 | 32914.17 | 32914.17 |
ROOM_1_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 13663.360 | -999.000 | 1.048541 | 0.00048801 | -999.000 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | unknown | 7/21 17:00:00 | 13663.36 | 12592.17 | 1.048541 | 22.49 | 16.16 | 0.00887242 | 12.80 | 12.09 | 0.00850000 | 32.26 | 0.01716543 | 25.09 | 0.0000 | 21.11 | 0.00887242 | 56.8280 | 10694.98 | 0.00 | 13687.30 | 12460.69 |
ROOM_1_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 3659.956 | 3659.956 | 0.157984 | 0.00003202 | 104.574 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 3659.96 | 3659.96 | 0.157984 | 21.11 | 14.69 | 0.00778795 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 21.11 | 0.00778795 | 49.9624 | 3659.98 | 0.00 | 3945.55 | 3945.55 |
ROOM_2_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 13785.907 | -999.000 | 1.058870 | 0.00049239 | -999.000 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | unknown | 7/21 17:10:00 | 13785.91 | 12715.09 | 1.058870 | 22.49 | 16.16 | 0.00886870 | 12.80 | 12.09 | 0.00850000 | 32.15 | 0.01716522 | 25.06 | 0.0000 | 21.11 | 0.00886870 | 56.8045 | 10800.34 | 0.00 | 13810.07 | 12581.76 |
ROOM_2_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 3660.184 | 3660.184 | 0.157994 | 0.00003202 | 104.581 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 3660.18 | 3660.18 | 0.157994 | 21.11 | 14.69 | 0.00778797 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 21.11 | 0.00778797 | 49.9626 | 3660.21 | 0.00 | 3945.80 | 3945.80 |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 75998.167 | -999.000 | 5.953979 | 0.00271443 | -999.000 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | unknown | 7/21 14:50:00 | 75998.17 | 71358.40 | 5.953979 | 22.49 | 16.08 | 0.00878469 | 12.80 | 12.09 | 0.00850000 | 33.20 | 0.01716721 | 25.32 | 0.0000 | 21.11 | 0.00878469 | 56.2698 | 60738.63 | 0.00 | 76133.27 | 70537.47 |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 21298.526 | 21298.526 | 0.919369 | 0.00018633 | 608.547 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 21298.53 | 21298.53 | 0.919369 | 21.11 | 14.70 | 0.00780313 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 21.11 | 0.00780313 | 50.0583 | 21298.60 | 0.00 | 22960.55 | 22960.55 |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 92061.169 | -999.000 | 6.949400 | 0.00328815 | -999.000 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:40:00 | unknown | 7/21 17:40:00 | 92061.17 | 83600.84 | 6.949400 | 22.49 | 16.22 | 0.00894306 | 12.80 | 12.09 | 0.00850000 | 31.82 | 0.01716457 | 24.97 | 0.0000 | 21.11 | 0.00894306 | 57.2720 | 70888.06 | 0.00 | 92220.62 | 82796.81 |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 21316.133 | 21316.133 | 0.920129 | 0.00018648 | 609.050 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 21316.13 | 21316.13 | 0.920129 | 21.11 | 14.70 | 0.00780322 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 21.11 | 0.00780322 | 50.0589 | 21316.21 | 0.00 | 22979.53 | 22979.53 |
ROOM_5_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 12405.479 | -999.000 | 0.942610 | 0.00044309 | -999.000 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | unknown | 7/21 10:00:00 | 12405.48 | 11331.41 | 0.942610 | 22.49 | 16.20 | 0.00891497 | 12.80 | 12.09 | 0.00850000 | 30.65 | 0.01716236 | 24.67 | 0.0000 | 21.11 | 0.00891497 | 57.0968 | 9614.47 | 0.00 | 12427.06 | 11218.75 |
ROOM_5_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 3658.994 | 3658.994 | 0.157943 | 0.00003201 | 104.547 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 3658.99 | 3658.99 | 0.157943 | 21.11 | 14.69 | 0.00778790 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 21.11 | 0.00778790 | 49.9622 | 3659.02 | 0.00 | 3944.52 | 3944.52 |
ROOM_6_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 12501.428 | -999.000 | 0.950587 | 0.00044651 | -999.000 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | unknown | 7/21 10:00:00 | 12501.43 | 11426.47 | 0.950587 | 22.49 | 16.19 | 0.00891185 | 12.80 | 12.09 | 0.00850000 | 30.65 | 0.01716236 | 24.67 | 0.0000 | 21.11 | 0.00891185 | 57.0771 | 9695.84 | 0.00 | 12523.19 | 11312.46 |
ROOM_6_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 3659.223 | 3659.223 | 0.157953 | 0.00003201 | 104.553 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 3659.22 | 3659.22 | 0.157953 | 21.11 | 14.69 | 0.00778793 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 21.11 | 0.00778793 | 49.9623 | 3659.25 | 0.00 | 3944.76 | 3944.76 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | 11535.774 | 11535.774 | 1.095430 | 0.00010092 | 253.723 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 11535.77 | 11535.77 | 1.095430 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 21.00 | 0.00782775 | 50.5578 | 5760.67 | 0.00 | 11598.70 | 11598.70 |
ROOM_1_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 3632.372 | -999.000 | 0.280254 | 0.00012974 | -999.000 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | unknown | 7/21 17:00:00 | 3632.37 | 3363.80 | 0.280254 | 22.49 | 16.14 | 0.00884955 | 12.80 | 12.09 | 0.00850000 | 32.26 | 0.01716543 | 25.09 | 0.0000 | 21.11 | 0.00884955 | 56.6835 | 2858.57 | 0.00 | 3638.76 | 3327.75 |
ROOM_1_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 1124.655 | 1124.655 | 0.048546 | 0.00000984 | 32.134 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 1124.65 | 1124.65 | 0.048546 | 21.11 | 14.72 | 0.00782040 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 21.11 | 0.00782040 | 50.1681 | 1124.66 | 0.00 | 1212.41 | 1212.41 |
ROOM_2_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 3661.774 | -999.000 | 0.282749 | 0.00013079 | -999.000 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | unknown | 7/21 17:00:00 | 3661.77 | 3393.46 | 0.282749 | 22.49 | 16.14 | 0.00884615 | 12.80 | 12.09 | 0.00850000 | 32.26 | 0.01716543 | 25.09 | 0.0000 | 21.11 | 0.00884615 | 56.6621 | 2884.01 | 0.00 | 3668.22 | 3356.97 |
ROOM_2_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 1124.882 | 1124.882 | 0.048556 | 0.00000984 | 32.140 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 1124.88 | 1124.88 | 0.048556 | 21.11 | 14.72 | 0.00782044 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 21.11 | 0.00782044 | 50.1683 | 1124.89 | 0.00 | 1212.66 | 1212.66 |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 15472.292 | -999.000 | 1.165445 | 0.00055262 | -999.000 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | unknown | 7/21 14:40:00 | 15472.29 | 14022.61 | 1.165445 | 22.49 | 16.23 | 0.00895259 | 12.80 | 12.09 | 0.00850000 | 33.20 | 0.01716721 | 25.32 | 0.0000 | 21.11 | 0.00895259 | 57.3340 | 11887.52 | 0.00 | 15499.05 | 13889.27 |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 5435.884 | 5435.884 | 0.234644 | 0.00004756 | 155.313 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 5435.88 | 5435.88 | 0.234644 | 21.11 | 14.72 | 0.00782744 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 21.11 | 0.00782744 | 50.2126 | 5435.92 | 0.00 | 5860.06 | 5860.06 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 15438.992 | 15438.992 | 2.225678 | 0.00013507 | 327.312 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 15438.99 | 15438.99 | 2.225678 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 21.00 | 0.00785972 | 50.7617 | 3704.58 | 0.00 | 15525.26 | 15525.26 |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 15947.956 | 15947.956 | 2.335481 | 0.00013952 | 337.735 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 04:20:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 04:20:00 | 15947.96 | 15947.96 | 2.335481 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 21.00 | 0.00785734 | 50.7466 | 3634.68 | 0.00 | 16037.10 | 16037.10 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 11816.389 | 11816.389 | 2.240617 | 0.00010337 | 246.410 | 1/21 00:10:00 | 1/21 00:10:00 | 11816.39 | 11816.39 | 2.240617 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 21.00 | 0.00800000 | 51.6560 | 0.00 | 0.00 | 11882.80 | 11882.80 | ||
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | 7322.429 | 7322.429 | 0.659978 | 0.00006406 | 162.012 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 04:30:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 04:30:00 | 7322.43 | 7322.43 | 0.659978 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 21.00 | 0.00787883 | 50.8838 | 3842.74 | 0.00 | 7362.27 | 7362.27 |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV WITH REHEAT | 1144947.372 | -999.000 | 21.217549 | 0.04089487 | -999.000 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 1144947.37 | 570594.23 | 21.217549 | 33.20 | 25.32 | 0.01716721 | 11.00 | 11.00 | 0.00850000 | 33.20 | 0.01716721 | 25.32 | 99.9761 | 23.99 | 0.00983433 | 52.7915 | 291395.06 | 0.00 | 1146407.07 | 577418.59 |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV WITH REHEAT | 61543.584 | 61543.584 | 6.365265 | 0.00053841 | 1142.024 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 04:30:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 04:30:00 | 61543.58 | 61543.58 | 6.365265 | 8.70 | 8.70 | 0.00699286 | 16.70 | 13.18 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 333.2535 | 22.68 | 0.00711736 | 41.5360 | 34496.53 | 0.00 | 66715.09 | 66715.09 |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | FLR_3_DOAS | 108329.821 | -999.000 | 2.051317 | 0.00386929 | -999.000 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 108329.82 | 53987.08 | 2.051317 | 33.20 | 25.32 | 0.01716721 | 11.94 | 11.73 | 0.00850000 | 33.20 | 0.01716721 | 25.32 | 99.9965 | 21.11 | 0.00887395 | 56.8347 | 184267.17 | 0.00 | 108457.34 | 54776.98 |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | FLR_3_DOAS | 5950.047 | 5950.047 | 0.615395 | 0.00005205 | 110.411 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 5950.05 | 5950.05 | 0.615395 | 8.70 | 8.70 | 0.00699286 | 16.70 | 13.18 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 333.3216 | 21.11 | 0.00780327 | 50.0592 | 64938.74 | 0.00 | 6450.03 | 6450.03 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:58:20
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
BASEMENT VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | BASEMENT | N/A | N/A | N/A | Yes | Yes | Yes | No | 13966.408 | 13966.408 | 2.648302 | 0.00012218 | 291.245 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.43912859 | 54.44 | 82.22 | 27.78 | 284447.51 | 4.9100 | 5.008828 | 1/21 00:10:00 | unknown | unknown | 1/21 00:10:00 | Sensible | 13966.41 | 13966.41 | 1.0000 | 3.18521618 | 2.648302 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 0.12217177 | 60.00 | 32.22 | 27.78 | 0.000 | 13966.41 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 51.6560 | 0.00 | 0.00 | 14044.90 | 14044.90 | 3.18521618 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 20.92 | 14.82 | 0.00800000 | 41344.1 | |||
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | RETAIL_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3112.969 | 3112.969 | 0.292169 | 0.00002723 | 68.557 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.43912859 | 54.44 | 82.22 | 27.78 | 284447.51 | 1.0944 | 1.116416 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | Sensible | 3112.97 | 3112.97 | 1.0000 | 0.35140350 | 0.292169 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 0.02723083 | 60.00 | 32.22 | 27.78 | 0.000 | 3112.97 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 21.00 | 0.00778658 | 21.00 | 0.00778658 | 50.2955 | 1572.81 | 0.00 | 3129.94 | 3129.94 | 0.35140350 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 25.33 | 16.43 | 0.00800000 | 45841.7 | |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | RETAIL_2_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1773.525 | 1773.525 | 0.241029 | 0.00001552 | 37.759 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.43912859 | 54.44 | 82.22 | 27.78 | 284447.51 | 0.6235 | 0.636046 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | Sensible | 1773.53 | 1773.53 | 1.0000 | 0.28989545 | 0.241029 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 0.01551399 | 60.00 | 32.22 | 27.78 | 0.000 | 1773.53 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 21.00 | 0.00775321 | 21.00 | 0.00775321 | 50.0823 | 502.99 | 0.00 | 1783.42 | 1783.42 | 0.28989545 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 22.63 | 15.46 | 0.00800000 | 43086.7 | |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | MECH_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2296.520 | 2296.520 | 0.260148 | 0.00002009 | 49.630 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.43912859 | 54.44 | 82.22 | 27.78 | 284447.51 | 0.8074 | 0.823610 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | Sensible | 2296.52 | 2296.52 | 1.0000 | 0.31289003 | 0.260148 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 0.02008891 | 60.00 | 32.22 | 27.78 | 0.000 | 2296.52 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 21.00 | 0.00770362 | 21.00 | 0.00770362 | 49.7659 | 925.33 | 0.00 | 2309.28 | 2309.28 | 0.31289003 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 23.84 | 15.90 | 0.00800000 | 44315.2 | |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | STORAGE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1228.034 | 1228.034 | 0.129877 | 0.00001074 | 26.712 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.43912859 | 54.44 | 82.22 | 27.78 | 284447.51 | 0.4317 | 0.440415 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | Sensible | 1228.03 | 1228.03 | 1.0000 | 0.15620762 | 0.129877 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 0.01074228 | 60.00 | 32.22 | 27.78 | 0.000 | 1228.03 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 21.00 | 0.00770734 | 21.00 | 0.00770734 | 49.7896 | 543.48 | 0.00 | 1234.84 | 1234.84 | 0.15620762 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 24.35 | 16.08 | 0.00800000 | 44839.9 | |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LAUNDRY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 18443.649 | 18443.649 | 3.250336 | 0.00016135 | 386.131 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.43912859 | 54.44 | 82.22 | 27.78 | 284447.51 | 6.4840 | 6.614519 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | Sensible | 18443.65 | 18443.65 | 1.0000 | 3.90930530 | 3.250336 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 0.16133663 | 60.00 | 32.22 | 27.78 | 0.000 | 18443.65 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 21.00 | 0.00771145 | 21.00 | 0.00771145 | 49.8162 | 1311.94 | 0.00 | 18547.16 | 18547.16 | 3.90930530 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 21.25 | 14.95 | 0.00800000 | 41679.1 | |
CAFE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | CAFE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10789.676 | 10789.676 | 1.302981 | 0.00009439 | 231.875 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.43912859 | 54.44 | 82.22 | 27.78 | 284447.51 | 3.7932 | 3.869544 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | Sensible | 10789.68 | 10789.68 | 1.0000 | 1.56714602 | 1.302981 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 0.09438316 | 60.00 | 32.22 | 27.78 | 0.000 | 10789.68 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 21.00 | 0.00780610 | 21.00 | 0.00780610 | 50.4199 | 3920.76 | 0.00 | 10849.71 | 10849.71 | 1.56714602 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 23.39 | 15.73 | 0.00800000 | 43858.0 | |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LOBBY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 32731.436 | 32731.436 | 4.535523 | 0.00028635 | 695.871 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.43912859 | 54.44 | 82.22 | 27.78 | 284447.51 | 11.5070 | 11.738605 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | Sensible | 32731.44 | 32731.44 | 1.0000 | 5.45505043 | 4.535523 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 0.28631967 | 60.00 | 32.22 | 27.78 | 0.000 | 32731.44 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 21.00 | 0.00776594 | 21.00 | 0.00776594 | 50.1635 | 8822.88 | 0.00 | 32914.17 | 32914.17 | 5.45505043 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 22.52 | 15.42 | 0.00800000 | 42968.4 | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 13663.360 | -999.000 | 1.048541 | 0.00048801 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.3334 | 1004.8586 | 1.2027 | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.048541 | 1.26112051 | 4197.9300 | 999.8980 | 53.44443855 | 13.37 | 6.70 | 6.67 | 1496454.60 | 0.9130 | 0.913032 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | unknown | unknown | unknown | 7/21 17:00:00 | Sensible | 13663.36 | 12592.17 | 1.0000 | 1.26112051 | 1.048541 | 22.49 | 16.16 | 0.00887242 | 45156.5 | 12.80 | 12.09 | 0.00850000 | 34322.2 | 0.48796466 | 6.70 | 13.37 | 6.67 | 0.000 | 13663.36 | 32.26 | 0.01716543 | 25.09 | 0.00000000 | 0.0000 | 21.11 | 0.00887242 | 21.11 | 0.00887242 | 56.8280 | 10694.98 | 0.00 | 13687.30 | 12460.69 | 1.26112051 | 22.49 | 16.17 | 0.00887242 | 45156.5 | 12.81 | 12.09 | 0.00848718 | 34303.2 | |
ROOM_1_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3659.956 | 3659.956 | 0.157984 | 0.00003202 | 104.574 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.048541 | 1.26112051 | 4197.9300 | 999.8980 | 2.43912859 | 54.44 | 82.22 | 27.78 | 284447.51 | 1.2867 | 1.312585 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | Sensible | 3659.96 | 3659.96 | 1.0000 | 0.19001373 | 0.157984 | 21.11 | 14.69 | 0.00778795 | 40995.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 0.03201562 | 60.00 | 32.22 | 27.78 | 0.000 | 3659.96 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 21.11 | 0.00778795 | 21.11 | 0.00778795 | 49.9624 | 3659.98 | 0.00 | 3945.55 | 3945.55 | 0.19001373 | 16.60 | 12.94 | 0.00778795 | 36397.9 | 36.97 | 20.11 | 0.00778795 | 57162.4 | |
ROOM_2_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 13785.907 | -999.000 | 1.058870 | 0.00049239 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.3265 | 1004.8586 | 1.2027 | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.058870 | 1.27354379 | 4197.9300 | 999.8980 | 53.44443855 | 13.37 | 6.70 | 6.67 | 1496454.60 | 0.9212 | 0.921221 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | unknown | unknown | unknown | 7/21 17:10:00 | Sensible | 13785.91 | 12715.09 | 1.0000 | 1.27354379 | 1.058870 | 22.49 | 16.16 | 0.00886870 | 45147.0 | 12.80 | 12.09 | 0.00850000 | 34322.2 | 0.49234123 | 6.70 | 13.37 | 6.67 | 0.000 | 13785.91 | 32.15 | 0.01716522 | 25.06 | 0.00000000 | 0.0000 | 21.11 | 0.00886870 | 21.11 | 0.00886870 | 56.8045 | 10800.34 | 0.00 | 13810.07 | 12581.76 | 1.27354379 | 22.49 | 16.17 | 0.00886870 | 45147.0 | 12.81 | 12.09 | 0.00848668 | 34303.2 | |
ROOM_2_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3660.184 | 3660.184 | 0.157994 | 0.00003202 | 104.581 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.058870 | 1.27354379 | 4197.9300 | 999.8980 | 2.43912859 | 54.44 | 82.22 | 27.78 | 284447.51 | 1.2868 | 1.312666 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | Sensible | 3660.18 | 3660.18 | 1.0000 | 0.19002560 | 0.157994 | 21.11 | 14.69 | 0.00778797 | 40995.9 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 0.03201762 | 60.00 | 32.22 | 27.78 | 0.000 | 3660.18 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 21.11 | 0.00778797 | 21.11 | 0.00778797 | 49.9626 | 3660.21 | 0.00 | 3945.80 | 3945.80 | 0.19002560 | 16.60 | 12.94 | 0.00778797 | 36397.9 | 36.97 | 20.11 | 0.00778797 | 57162.5 | |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 75998.167 | -999.000 | 5.953979 | 0.00271443 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.1703 | 1004.8586 | 1.2027 | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 5.953979 | 7.16108280 | 4197.9300 | 999.8980 | 53.44443855 | 13.37 | 6.70 | 6.67 | 1496454.60 | 5.0785 | 5.078453 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | unknown | unknown | unknown | 7/21 14:50:00 | Sensible | 75998.17 | 71358.40 | 1.0000 | 7.16108280 | 5.953979 | 22.49 | 16.08 | 0.00878469 | 44934.9 | 12.80 | 12.09 | 0.00850000 | 34322.2 | 2.71415086 | 6.70 | 13.37 | 6.67 | 0.000 | 75998.17 | 33.20 | 0.01716721 | 25.32 | 0.00000000 | 0.0000 | 21.11 | 0.00878469 | 21.11 | 0.00878469 | 56.2698 | 60738.63 | 0.00 | 76133.27 | 70537.47 | 7.16108280 | 22.49 | 16.10 | 0.00878469 | 44934.9 | 12.84 | 12.09 | 0.00847520 | 34303.3 | |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 21298.526 | 21298.526 | 0.919369 | 0.00018633 | 608.547 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 5.953979 | 7.16108280 | 4197.9300 | 999.8980 | 2.43912859 | 54.44 | 82.22 | 27.78 | 284447.51 | 7.4877 | 7.638375 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | Sensible | 21298.53 | 21298.53 | 1.0000 | 1.10576053 | 0.919369 | 21.11 | 14.70 | 0.00780313 | 41034.5 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 0.18630979 | 60.00 | 32.22 | 27.78 | 0.000 | 21298.53 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 21.11 | 0.00780313 | 21.11 | 0.00780313 | 50.0583 | 21298.60 | 0.00 | 22960.55 | 22960.55 | 1.10576053 | 16.60 | 12.96 | 0.00780313 | 36436.3 | 36.97 | 20.12 | 0.00780313 | 57200.8 | |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 92061.169 | -999.000 | 6.949400 | 0.00328815 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.4647 | 1004.8586 | 1.2027 | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 6.949400 | 8.35831450 | 4197.9300 | 999.8980 | 53.44443855 | 13.37 | 6.70 | 6.67 | 1496454.60 | 6.1520 | 6.151837 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:40:00 | unknown | unknown | unknown | 7/21 17:40:00 | Sensible | 92061.17 | 83600.84 | 1.0000 | 8.35831450 | 6.949400 | 22.49 | 16.22 | 0.00894306 | 45336.5 | 12.80 | 12.09 | 0.00850000 | 34322.2 | 3.28781481 | 6.70 | 13.37 | 6.67 | 0.000 | 92061.17 | 31.82 | 0.01716457 | 24.97 | 0.00000000 | 0.0000 | 21.11 | 0.00894306 | 21.11 | 0.00894306 | 57.2720 | 70888.06 | 0.00 | 92220.62 | 82796.81 | 8.35831450 | 22.49 | 16.23 | 0.00894306 | 45336.5 | 12.79 | 12.09 | 0.00849648 | 34303.1 | |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 21316.133 | 21316.133 | 0.920129 | 0.00018648 | 609.050 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 6.949400 | 8.35831450 | 4197.9300 | 999.8980 | 2.43912859 | 54.44 | 82.22 | 27.78 | 284447.51 | 7.4939 | 7.644690 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | Sensible | 21316.13 | 21316.13 | 1.0000 | 1.10667467 | 0.920129 | 21.11 | 14.70 | 0.00780322 | 41034.7 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 0.18646381 | 60.00 | 32.22 | 27.78 | 0.000 | 21316.13 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 21.11 | 0.00780322 | 21.11 | 0.00780322 | 50.0589 | 21316.21 | 0.00 | 22979.53 | 22979.53 | 1.10667467 | 16.60 | 12.96 | 0.00780322 | 36436.5 | 36.97 | 20.12 | 0.00780322 | 57201.0 | |
ROOM_5_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12405.479 | -999.000 | 0.942610 | 0.00044309 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.4125 | 1004.8586 | 1.2027 | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.942610 | 1.13371341 | 4197.9300 | 999.8980 | 53.44443855 | 13.37 | 6.70 | 6.67 | 1496454.60 | 0.8290 | 0.828976 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | unknown | unknown | unknown | 7/21 10:00:00 | Sensible | 12405.48 | 11331.41 | 1.0000 | 1.13371341 | 0.942610 | 22.49 | 16.20 | 0.00891497 | 45264.5 | 12.80 | 12.09 | 0.00850000 | 34322.2 | 0.44304149 | 6.70 | 13.37 | 6.67 | 0.000 | 12405.48 | 30.65 | 0.01716236 | 24.67 | 0.00000000 | 0.0000 | 21.11 | 0.00891497 | 21.11 | 0.00891497 | 57.0968 | 9614.47 | 0.00 | 12427.06 | 11218.75 | 1.13371341 | 22.49 | 16.21 | 0.00891497 | 45264.5 | 12.80 | 12.09 | 0.00849282 | 34303.2 | |
ROOM_5_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3658.994 | 3658.994 | 0.157943 | 0.00003201 | 104.547 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.942610 | 1.13371341 | 4197.9300 | 999.8980 | 2.43912859 | 54.44 | 82.22 | 27.78 | 284447.51 | 1.2864 | 1.312240 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | Sensible | 3658.99 | 3658.99 | 1.0000 | 0.18996380 | 0.157943 | 21.11 | 14.69 | 0.00778790 | 40995.7 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 0.03200721 | 60.00 | 32.22 | 27.78 | 0.000 | 3658.99 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 21.11 | 0.00778790 | 21.11 | 0.00778790 | 49.9622 | 3659.02 | 0.00 | 3944.52 | 3944.52 | 0.18996380 | 16.60 | 12.94 | 0.00778790 | 36397.7 | 36.97 | 20.11 | 0.00778790 | 57162.3 | |
ROOM_6_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12501.428 | -999.000 | 0.950587 | 0.00044651 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.4067 | 1004.8586 | 1.2027 | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.950587 | 1.14330795 | 4197.9300 | 999.8980 | 53.44443855 | 13.37 | 6.70 | 6.67 | 1496454.60 | 0.8354 | 0.835387 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | unknown | unknown | unknown | 7/21 10:00:00 | Sensible | 12501.43 | 11426.47 | 1.0000 | 1.14330795 | 0.950587 | 22.49 | 16.19 | 0.00891185 | 45256.6 | 12.80 | 12.09 | 0.00850000 | 34322.2 | 0.44646814 | 6.70 | 13.37 | 6.67 | 0.000 | 12501.43 | 30.65 | 0.01716236 | 24.67 | 0.00000000 | 0.0000 | 21.11 | 0.00891185 | 21.11 | 0.00891185 | 57.0771 | 9695.84 | 0.00 | 12523.19 | 11312.46 | 1.14330795 | 22.49 | 16.21 | 0.00891185 | 45256.6 | 12.80 | 12.09 | 0.00849241 | 34303.2 | |
ROOM_6_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3659.223 | 3659.223 | 0.157953 | 0.00003201 | 104.553 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.950587 | 1.14330795 | 4197.9300 | 999.8980 | 2.43912859 | 54.44 | 82.22 | 27.78 | 284447.51 | 1.2864 | 1.312322 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | Sensible | 3659.22 | 3659.22 | 1.0000 | 0.18997566 | 0.157953 | 21.11 | 14.69 | 0.00778793 | 40995.7 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 0.03200921 | 60.00 | 32.22 | 27.78 | 0.000 | 3659.22 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 21.11 | 0.00778793 | 21.11 | 0.00778793 | 49.9623 | 3659.25 | 0.00 | 3944.76 | 3944.76 | 0.18997566 | 16.60 | 12.94 | 0.00778793 | 36397.8 | 36.97 | 20.11 | 0.00778793 | 57162.4 | |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | CORRIDOR_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11535.774 | 11535.774 | 1.095430 | 0.00010092 | 253.723 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.43912859 | 54.44 | 82.22 | 27.78 | 284447.51 | 4.0555 | 4.137121 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 11535.77 | 11535.77 | 1.0000 | 1.31751622 | 1.095430 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 0.10090969 | 60.00 | 32.22 | 27.78 | 0.000 | 11535.77 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 21.00 | 0.00782775 | 21.00 | 0.00782775 | 50.5578 | 5760.67 | 0.00 | 11598.70 | 11598.70 | 1.31751622 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 25.23 | 16.40 | 0.00800000 | 45738.2 | |
ROOM_1_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3632.372 | -999.000 | 0.280254 | 0.00012974 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.2909 | 1004.8586 | 1.2027 | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.280254 | 0.33707271 | 4197.9300 | 999.8980 | 53.44443855 | 13.37 | 6.70 | 6.67 | 1496454.60 | 0.2427 | 0.242727 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | unknown | unknown | unknown | 7/21 17:00:00 | Sensible | 3632.37 | 3363.80 | 1.0000 | 0.33707271 | 0.280254 | 22.49 | 16.14 | 0.00884955 | 45098.4 | 12.80 | 12.09 | 0.00850000 | 34322.2 | 0.12972425 | 6.70 | 13.37 | 6.67 | 0.000 | 3632.37 | 32.26 | 0.01716543 | 25.09 | 0.00000000 | 0.0000 | 21.11 | 0.00884955 | 21.11 | 0.00884955 | 56.6835 | 2858.57 | 0.00 | 3638.76 | 3327.75 | 0.33707271 | 22.49 | 16.15 | 0.00884955 | 45098.4 | 12.82 | 12.09 | 0.00848411 | 34303.2 | |
ROOM_1_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1124.655 | 1124.655 | 0.048546 | 0.00000984 | 32.134 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.280254 | 0.33707271 | 4197.9300 | 999.8980 | 2.43912859 | 54.44 | 82.22 | 27.78 | 284447.51 | 0.3954 | 0.403339 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | Sensible | 1124.65 | 1124.65 | 1.0000 | 0.05838863 | 0.048546 | 21.11 | 14.72 | 0.00782040 | 41078.2 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 0.00983797 | 60.00 | 32.22 | 27.78 | 0.000 | 1124.65 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 21.11 | 0.00782040 | 21.11 | 0.00782040 | 50.1681 | 1124.66 | 0.00 | 1212.41 | 1212.41 | 0.05838863 | 16.60 | 12.98 | 0.00782040 | 36480.0 | 36.97 | 20.13 | 0.00782040 | 57244.6 | |
ROOM_2_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3661.774 | -999.000 | 0.282749 | 0.00013079 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.2846 | 1004.8586 | 1.2027 | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.282749 | 0.34007358 | 4197.9300 | 999.8980 | 53.44443855 | 13.37 | 6.70 | 6.67 | 1496454.60 | 0.2447 | 0.244692 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | unknown | unknown | unknown | 7/21 17:00:00 | Sensible | 3661.77 | 3393.46 | 1.0000 | 0.34007358 | 0.282749 | 22.49 | 16.14 | 0.00884615 | 45089.8 | 12.80 | 12.09 | 0.00850000 | 34322.2 | 0.13077431 | 6.70 | 13.37 | 6.67 | 0.000 | 3661.77 | 32.26 | 0.01716543 | 25.09 | 0.00000000 | 0.0000 | 21.11 | 0.00884615 | 21.11 | 0.00884615 | 56.6621 | 2884.01 | 0.00 | 3668.22 | 3356.97 | 0.34007358 | 22.49 | 16.15 | 0.00884615 | 45089.8 | 12.82 | 12.09 | 0.00848365 | 34303.2 | |
ROOM_2_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1124.882 | 1124.882 | 0.048556 | 0.00000984 | 32.140 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.282749 | 0.34007358 | 4197.9300 | 999.8980 | 2.43912859 | 54.44 | 82.22 | 27.78 | 284447.51 | 0.3955 | 0.403421 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | Sensible | 1124.88 | 1124.88 | 1.0000 | 0.05840041 | 0.048556 | 21.11 | 14.72 | 0.00782044 | 41078.3 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 0.00983995 | 60.00 | 32.22 | 27.78 | 0.000 | 1124.88 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 21.11 | 0.00782044 | 21.11 | 0.00782044 | 50.1683 | 1124.89 | 0.00 | 1212.66 | 1212.66 | 0.05840041 | 16.60 | 12.98 | 0.00782044 | 36480.1 | 36.97 | 20.13 | 0.00782044 | 57244.7 | |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 15472.292 | -999.000 | 1.165445 | 0.00055262 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.4824 | 1004.8586 | 1.2027 | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.165445 | 1.40172622 | 4197.9300 | 999.8980 | 53.44443855 | 13.37 | 6.70 | 6.67 | 1496454.60 | 1.0339 | 1.033911 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | unknown | unknown | unknown | 7/21 14:40:00 | Sensible | 15472.29 | 14022.61 | 1.0000 | 1.40172622 | 1.165445 | 22.49 | 16.23 | 0.00895259 | 45360.2 | 12.80 | 12.09 | 0.00850000 | 34322.2 | 0.55256771 | 6.70 | 13.37 | 6.67 | 0.000 | 15472.29 | 33.20 | 0.01716721 | 25.32 | 0.00000000 | 0.0000 | 21.11 | 0.00895259 | 21.11 | 0.00895259 | 57.3340 | 11887.52 | 0.00 | 15499.05 | 13889.27 | 1.40172622 | 22.49 | 16.24 | 0.00895259 | 45360.2 | 12.79 | 12.09 | 0.00849772 | 34303.1 | |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5435.884 | 5435.884 | 0.234644 | 0.00004756 | 155.313 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.165445 | 1.40172622 | 4197.9300 | 999.8980 | 2.43912859 | 54.44 | 82.22 | 27.78 | 284447.51 | 1.9110 | 1.949493 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | Sensible | 5435.88 | 5435.88 | 1.0000 | 0.28221499 | 0.234644 | 21.11 | 14.72 | 0.00782744 | 41096.2 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 0.04755063 | 60.00 | 32.22 | 27.78 | 0.000 | 5435.88 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 21.11 | 0.00782744 | 21.11 | 0.00782744 | 50.2126 | 5435.92 | 0.00 | 5860.06 | 5860.06 | 0.28221499 | 16.60 | 12.98 | 0.00782744 | 36497.9 | 36.97 | 20.14 | 0.00782744 | 57262.4 | |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | BANQUET_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 15438.992 | 15438.992 | 2.225678 | 0.00013507 | 327.312 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.43912859 | 54.44 | 82.22 | 27.78 | 284447.51 | 5.4277 | 5.536947 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | Sensible | 15438.99 | 15438.99 | 1.0000 | 2.67690912 | 2.225678 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 0.13505326 | 60.00 | 32.22 | 27.78 | 0.000 | 15438.99 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 21.00 | 0.00785972 | 21.00 | 0.00785972 | 50.7617 | 3704.58 | 0.00 | 15525.26 | 15525.26 | 2.67690912 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 22.29 | 15.33 | 0.00800000 | 42734.4 | |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | DINING_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 15947.956 | 15947.956 | 2.335481 | 0.00013952 | 337.735 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.43912859 | 54.44 | 82.22 | 27.78 | 284447.51 | 5.6066 | 5.719479 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 04:20:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 04:20:00 | Sensible | 15947.96 | 15947.96 | 1.0000 | 2.80897417 | 2.335481 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 0.13950544 | 60.00 | 32.22 | 27.78 | 0.000 | 15947.96 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 21.00 | 0.00785734 | 21.00 | 0.00785734 | 50.7466 | 3634.68 | 0.00 | 16037.10 | 16037.10 | 2.80897417 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 22.20 | 15.30 | 0.00800000 | 42644.0 | |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | KITCHEN_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11816.389 | 11816.389 | 2.240617 | 0.00010337 | 246.410 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.43912859 | 54.44 | 82.22 | 27.78 | 284447.51 | 4.1542 | 4.237759 | 1/21 00:10:00 | unknown | unknown | 1/21 00:10:00 | Sensible | 11816.39 | 11816.39 | 1.0000 | 2.69487718 | 2.240617 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 0.10336438 | 60.00 | 32.22 | 27.78 | 0.000 | 11816.39 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 51.6560 | 0.00 | 0.00 | 11882.80 | 11882.80 | 2.69487718 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 20.92 | 14.82 | 0.00800000 | 41344.1 | |||
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | CORRIDOR_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7322.429 | 7322.429 | 0.659978 | 0.00006406 | 162.012 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.43912859 | 54.44 | 82.22 | 27.78 | 284447.51 | 2.5743 | 2.626072 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 04:30:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 04:30:00 | Sensible | 7322.43 | 7322.43 | 1.0000 | 0.79378166 | 0.659978 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 0.06405327 | 60.00 | 32.22 | 27.78 | 0.000 | 7322.43 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 21.00 | 0.00787883 | 21.00 | 0.00787883 | 50.8838 | 3842.74 | 0.00 | 7362.27 | 7362.27 | 0.79378166 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 25.70 | 16.56 | 0.00800000 | 46209.7 | |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 1144947.372 | -999.000 | 21.217549 | 0.04089487 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1036.7530 | 1004.8586 | 1.2027 | VAV WITH REHEAT FAN | Fan:VariableVolume | 21.217549 | 25.51917288 | 4197.9300 | 999.8980 | 53.44443855 | 13.37 | 6.70 | 6.67 | 1496454.60 | 76.5107 | 76.510665 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | Sensible | 1144947.37 | 570594.23 | 1.0000 | 25.51917288 | 21.217549 | 33.20 | 25.32 | 0.01716721 | 77354.4 | 11.00 | 11.00 | 0.00850000 | 32488.2 | 40.89069558 | 6.70 | 13.37 | 6.67 | 47540.861 | 1097406.51 | 33.20 | 0.01716721 | 25.32 | 21.21247000 | 99.9761 | 23.99 | 0.00979524 | 23.99 | 0.00983433 | 52.7915 | 291395.06 | 0.00 | 1146407.07 | 577418.59 | 25.51917288 | 33.20 | 25.34 | 0.01716721 | 77354.4 | 11.38 | 11.33 | 0.00832671 | 32431.0 | |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 61543.584 | 61543.584 | 6.365265 | 0.00053841 | 1142.024 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | VAV WITH REHEAT FAN | Fan:VariableVolume | 21.217549 | 25.51917288 | 4197.9300 | 999.8980 | 2.43912859 | 54.44 | 82.22 | 27.78 | 284447.51 | 21.6362 | 22.071620 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 04:30:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 04:30:00 | Sensible | 61543.58 | 61543.58 | 1.0000 | 7.65575186 | 6.365265 | 8.70 | 8.70 | 0.00699286 | 26343.9 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 0.53835520 | 60.00 | 32.22 | 27.78 | 0.000 | 61543.58 | 8.70 | 0.00699286 | 8.70 | 21.21247000 | 333.2535 | 17.40 | 0.00763756 | 22.68 | 0.00711736 | 41.5360 | 34496.53 | 0.00 | 66715.09 | 66715.09 | 7.65575186 | 2.80 | 2.80 | 0.00699286 | 20338.7 | 11.36 | 9.92 | 0.00699286 | 29053.0 | |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 108329.821 | -999.000 | 2.051317 | 0.00386929 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1036.7530 | 1004.8586 | 1.2027 | FLR_3_DOAS FAN | Fan:ConstantVolume | 2.051245 | 2.46711237 | 4197.9300 | 999.8980 | 53.44443855 | 13.37 | 6.70 | 6.67 | 1496454.60 | 7.2391 | 7.239098 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | Sensible | 108329.82 | 53987.08 | 1.0000 | 2.46719911 | 2.051317 | 33.20 | 25.32 | 0.01716721 | 77354.4 | 11.94 | 11.73 | 0.00850000 | 33446.3 | 3.86889549 | 6.70 | 13.37 | 6.67 | 2195.006 | 106134.81 | 33.20 | 0.01716721 | 25.32 | 2.05124512 | 99.9965 | 21.11 | 0.00889146 | 21.11 | 0.00887395 | 56.8347 | 184267.17 | 0.00 | 108457.34 | 54776.98 | 2.46719911 | 33.20 | 25.34 | 0.01716721 | 77354.4 | 11.78 | 11.72 | 0.00854298 | 33394.7 | |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 5950.047 | 5950.047 | 0.615395 | 0.00005205 | 110.411 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | FLR_3_DOAS FAN | Fan:ConstantVolume | 2.051245 | 2.46711237 | 4197.9300 | 999.8980 | 2.43912859 | 54.44 | 82.22 | 27.78 | 284447.51 | 2.0918 | 2.133889 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | Sensible | 5950.05 | 5950.05 | 1.0000 | 0.74015973 | 0.615395 | 8.70 | 8.70 | 0.00699286 | 26343.9 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 0.05204830 | 60.00 | 32.22 | 27.78 | 0.000 | 5950.05 | 8.70 | 0.00699286 | 8.70 | 2.05124512 | 333.3216 | 21.11 | 0.00780237 | 21.11 | 0.00780327 | 50.0592 | 64938.74 | 0.00 | 6450.03 | 6450.03 | 0.74015973 | 2.80 | 2.80 | 0.00699286 | 20338.7 | 11.36 | 9.92 | 0.00699286 | 29053.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:58:20
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
FLR_3_DOAS_OA_CONTROLLER | DifferentialDryBulb | 2.05 | 2.05 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
BASEMENT | VAV WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
RETAIL_1_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
RETAIL_2_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
MECH_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
STORAGE_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000610 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
LAUNDRY_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CAFE_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
LOBBY_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001448 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORRIDOR_FLR_3 | VAV WITH REHEAT_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
BANQUET_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
DINING_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
KITCHEN_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003556 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORRIDOR_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 0.00 | 8760.00 | 0.00 |
RETAIL_1_FLR_1 | 210.83 | 8329.17 | 5.17 |
RETAIL_2_FLR_1 | 0.00 | 8760.00 | 0.00 |
MECH_FLR_1 | 0.00 | 8760.00 | 0.00 |
STORAGE_FLR_1 | 1.50 | 8760.00 | 1.50 |
LAUNDRY_FLR_1 | 5861.83 | 1903.50 | 1257.00 |
CAFE_FLR_1 | 202.33 | 8011.50 | 0.00 |
LOBBY_FLR_1 | 0.00 | 8760.00 | 0.00 |
ROOM_1_FLR_3 | 269.17 | 7379.83 | 24.67 |
ROOM_2_FLR_3 | 205.00 | 7604.33 | 45.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 14.50 | 8760.00 | 14.50 |
ROOM_5_FLR_3 | 64.33 | 7174.00 | 21.33 |
ROOM_6_FLR_3 | 54.67 | 7417.83 | 40.17 |
CORRIDOR_FLR_3 | 0.00 | 8760.00 | 0.00 |
ROOM_1_FLR_6 | 782.00 | 7149.50 | 61.67 |
ROOM_2_FLR_6 | 636.17 | 7337.17 | 85.00 |
ROOM_3_MULT9_FLR_6 | 261.67 | 7217.33 | 36.83 |
BANQUET_FLR_6 | 580.33 | 7084.83 | 0.00 |
DINING_FLR_6 | 1060.17 | 6311.83 | 0.00 |
KITCHEN_FLR_6 | 7587.00 | 6379.33 | 6036.33 |
CORRIDOR_FLR_6 | 2.83 | 8760.00 | 2.83 |
Facility | 7707.83 | 8760.00 | 6066.83 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 0.50 | 0.00 | 0.50 |
ROOM_2_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 21.33 | 0.00 | 21.33 |
ROOM_5_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 2.00 | 0.00 | 2.00 |
ROOM_2_FLR_6 | 0.00 | 0.50 | 0.00 | 0.50 |
ROOM_3_MULT9_FLR_6 | 0.00 | 30.00 | 0.00 | 30.00 |
BANQUET_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 0.00 | 45.33 | 0.00 | 45.33 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:58:20
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.80 | 106.50 | 4826.41 | 2.000 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.28 | 10.83 | 265.76 | 4.011 | 0.235 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.28 | 12.54 | 307.76 | 2.856 | 0.078 | 0.000 | 0.000 |
MECH_FLR_1 | 1.54 | 2.65 | 650.80 | 1.457 | 0.087 | 0.000 | 0.000 |
STORAGE_FLR_1 | 1.18 | 2.04 | 375.47 | 1.261 | 0.087 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.87 | 8.40 | 309.22 | 38.328 | 0.251 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.58 | 142.30 | 748.35 | 6.362 | 0.184 | 0.000 | 0.000 |
LOBBY_FLR_1 | 245.14 | 422.44 | 5183.56 | 3.195 | 0.076 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.474 | 0.304 | 0.000 | 0.065 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.474 | 0.304 | 0.000 | 0.066 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.538 | 0.135 | 0.000 | 0.105 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.474 | 0.304 | 0.000 | 0.065 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.474 | 0.304 | 0.000 | 0.066 |
CORRIDOR_FLR_3 | 12.16 | 20.96 | 1186.91 | 0.844 | 0.037 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.474 | 0.305 | 0.000 | 0.078 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.474 | 0.305 | 0.000 | 0.080 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.538 | 0.248 | 0.000 | 0.125 |
BANQUET_FLR_6 | 145.01 | 249.90 | 1010.89 | 8.051 | 0.088 | 0.000 | 0.000 |
DINING_FLR_6 | 145.01 | 249.90 | 1010.89 | 8.450 | 0.088 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.90 | 22.24 | 314.87 | 26.187 | 0.253 | 0.000 | 0.000 |
CORRIDOR_FLR_6 | 12.87 | 22.18 | 1256.16 | 1.917 | 0.062 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.80 | 106.50 | 4826.41 | 1.955 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.28 | 10.83 | 265.76 | 3.914 | 0.005 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.28 | 12.54 | 307.76 | 2.789 | 0.002 | 0.000 | 0.000 |
MECH_FLR_1 | 1.54 | 2.65 | 650.80 | 1.423 | 0.002 | 0.000 | 0.000 |
STORAGE_FLR_1 | 1.18 | 2.04 | 375.47 | 1.232 | 0.002 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.87 | 8.40 | 309.22 | 37.426 | 0.005 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.58 | 142.30 | 748.35 | 6.201 | 0.004 | 0.000 | 0.000 |
LOBBY_FLR_1 | 245.14 | 422.44 | 5183.56 | 3.116 | 0.002 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.462 | 0.006 | 0.000 | 0.000 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.461 | 0.006 | 0.000 | 0.000 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.525 | 0.003 | 0.000 | 0.000 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.463 | 0.006 | 0.000 | 0.000 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.462 | 0.006 | 0.000 | 0.000 |
CORRIDOR_FLR_3 | 12.16 | 20.96 | 1186.91 | 0.822 | 0.001 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.461 | 0.006 | 0.000 | 0.000 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.461 | 0.006 | 0.000 | 0.000 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.525 | 0.005 | 0.000 | 0.000 |
BANQUET_FLR_6 | 145.01 | 249.90 | 1010.89 | 7.842 | 0.002 | 0.000 | 0.000 |
DINING_FLR_6 | 145.01 | 249.90 | 1010.89 | 8.230 | 0.002 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.90 | 22.24 | 314.87 | 25.455 | 0.005 | 0.000 | 0.000 |
CORRIDOR_FLR_6 | 12.87 | 22.18 | 1256.16 | 1.871 | 0.001 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:58:20
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | VAV WITH REHEAT | 61.80 | 106.50 | 4826.41 | 1978.83 | 0.0000 | 0.854 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | 6.28 | 10.83 | 265.76 | 67.07 | 0.0000 | 0.079 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | 7.28 | 12.54 | 307.76 | 77.67 | 0.0000 | 0.092 |
MECH_FLR_1 | VAV WITH REHEAT | 1.54 | 2.65 | 650.80 | 164.24 | 0.0000 | 0.000 |
STORAGE_FLR_1 | VAV WITH REHEAT | 1.18 | 2.04 | 375.47 | 94.76 | 0.0000 | 0.058 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | 4.87 | 8.40 | 309.22 | 78.04 | 0.0000 | 0.000 |
CAFE_FLR_1 | VAV WITH REHEAT | 82.58 | 142.30 | 748.35 | 188.86 | 0.0000 | 0.676 |
LOBBY_FLR_1 | VAV WITH REHEAT | 245.14 | 422.44 | 5183.56 | 1308.19 | 0.0000 | 1.894 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.062 |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.062 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 1.50 | 74.75 | 24.52 | 0.0000 | 0.837 | |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 74.77 | 24.53 | 0.0000 | 0.837 |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.062 |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.062 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | 12.16 | 20.96 | 1186.91 | 389.40 | 0.0000 | 0.475 |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.015 |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.015 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 74.77 | 24.53 | 0.0000 | 0.099 |
BANQUET_FLR_6 | VAV WITH REHEAT | 145.01 | 249.90 | 1010.89 | 331.66 | 0.0000 | 1.188 |
DINING_FLR_6 | VAV WITH REHEAT | 145.01 | 249.90 | 1010.89 | 331.66 | 0.0000 | 1.188 |
KITCHEN_FLR_6 | VAV WITH REHEAT | 12.90 | 22.24 | 314.87 | 103.30 | 0.0000 | 0.367 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | 12.87 | 22.18 | 1256.16 | 412.12 | 0.0000 | 0.126 |
Total Facility | 873.39 | 1604.23 | 35184.81 | 11345.29 | 0.0000 | 137.584 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 83480417.75 | 0.00 | 83480417.75 | 0.00 | 83480417.75 | 26946214.98 | 0.00 | 0.00 | 8760.00 | 0.00 |
RETAIL_1_FLR_1 | 9209833.68 | 0.00 | 9209833.68 | 538771.47 | 9748605.14 | 2498216.28 | 0.00 | 0.00 | 8760.00 | 0.00 |
RETAIL_2_FLR_1 | 7597786.71 | 0.00 | 7597786.71 | 207966.47 | 7805753.18 | 2892943.94 | 0.00 | 0.00 | 8760.00 | 0.00 |
MECH_FLR_1 | 8200445.09 | 0.00 | 8200445.09 | 491509.18 | 8691954.27 | 0.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
STORAGE_FLR_1 | 4094000.82 | 0.00 | 4094000.82 | 283573.72 | 4377574.54 | 1821682.01 | 0.00 | 0.00 | 8760.00 | 0.00 |
LAUNDRY_FLR_1 | 0.10E+09 | 0.00 | 0.10E+09 | 671130.68 | 0.10E+09 | 0.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
CAFE_FLR_1 | 41072880.89 | 0.00 | 41072880.89 | 1190984.83 | 42263865.72 | 21330615.53 | 0.00 | 0.00 | 8760.00 | 0.00 |
LOBBY_FLR_1 | 0.14E+09 | 0.00 | 0.14E+09 | 3402915.69 | 0.15E+09 | 59728886.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
ROOM_1_FLR_3 | 1946875.62 | 66602.95 | 2013478.56 | 312717.28 | 2326195.85 | 1946875.62 | 0.00 | 7650.83 | 1109.17 | 0.00 |
ROOM_2_FLR_3 | 1946647.51 | 67779.04 | 2014426.55 | 312693.42 | 2327119.97 | 1946647.51 | 0.00 | 7650.83 | 1109.17 | 0.00 |
ROOM_3_MULT19_FLR_3 | 26397887.27 | 68920.90 | 26466808.17 | 87251.63 | 26554059.80 | 26397887.27 | 0.00 | 7743.33 | 1016.67 | 8760.00 |
ROOM_4_MULT19_FLR_3 | 26405105.73 | 67797.07 | 26472902.80 | 87275.49 | 26560178.29 | 26405105.73 | 0.00 | 7729.64 | 1030.36 | 0.00 |
ROOM_5_FLR_3 | 1946875.62 | 66705.09 | 2013580.71 | 312717.28 | 2326297.99 | 1946875.62 | 0.00 | 7650.83 | 1109.17 | 0.00 |
ROOM_6_FLR_3 | 1946647.51 | 67871.31 | 2014518.82 | 312693.42 | 2327212.24 | 1946647.51 | 0.00 | 7650.83 | 1109.17 | 0.00 |
CORRIDOR_FLR_3 | 34530404.86 | 0.00 | 34530404.86 | 378138.11 | 34908542.97 | 14972100.18 | 0.00 | 0.00 | 8760.00 | 0.00 |
ROOM_1_FLR_6 | 486718.90 | 80772.42 | 567491.32 | 312779.78 | 880271.10 | 486718.90 | 0.00 | 7637.17 | 1122.83 | 0.00 |
ROOM_2_FLR_6 | 486661.88 | 82366.77 | 569028.65 | 312755.92 | 881784.57 | 486661.88 | 0.00 | 7637.17 | 1122.83 | 0.00 |
ROOM_3_MULT9_FLR_6 | 3126920.42 | 80935.06 | 3207855.48 | 160029.08 | 3367884.56 | 3126920.42 | 0.00 | 7637.53 | 1122.47 | 0.00 |
BANQUET_FLR_6 | 70158343.84 | 0.00 | 70158343.84 | 763729.62 | 70922073.46 | 37458366.31 | 0.00 | 0.00 | 8760.00 | 0.00 |
DINING_FLR_6 | 73619598.85 | 0.00 | 73619598.85 | 763729.62 | 74383328.47 | 37458366.31 | 0.00 | 0.00 | 8760.00 | 0.00 |
KITCHEN_FLR_6 | 70751859.78 | 0.00 | 70751859.78 | 683715.08 | 71435574.86 | 11584760.86 | 0.00 | 0.00 | 8760.00 | 0.00 |
CORRIDOR_FLR_6 | 20803996.07 | 0.00 | 20803996.07 | 669182.16 | 21473178.24 | 3961413.96 | 0.00 | 0.00 | 8760.00 | 0.00 |
Total Facility | 0.48E+10 | 12357954.02 | 0.49E+10 | 31512904.89 | 0.49E+10 | 0.43E+10 | 0.00 | 7801.26 | 8760.00 | 8760.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 2.6471 | 0.0000 | 2.6471 | 0.0000 | 2.6471 | 0.8545 | 0.00 | 0.00 | 8760.00 |
RETAIL_1_FLR_1 | 0.2920 | 0.0000 | 0.2920 | 0.0171 | 0.3091 | 0.0792 | 0.00 | 0.00 | 8760.00 |
RETAIL_2_FLR_1 | 0.2409 | 0.0000 | 0.2409 | 0.0066 | 0.2475 | 0.0917 | 0.00 | 0.00 | 8760.00 |
MECH_FLR_1 | 0.2600 | 0.0000 | 0.2600 | 0.0156 | 0.2756 | 0.0000 | 0.00 | 0.00 | 8760.00 |
STORAGE_FLR_1 | 0.1298 | 0.0000 | 0.1298 | 0.0090 | 0.1388 | 0.0578 | 0.00 | 0.00 | 8760.00 |
LAUNDRY_FLR_1 | 3.2492 | 0.0000 | 3.2492 | 0.0213 | 3.2705 | 0.0000 | 0.00 | 0.00 | 8760.00 |
CAFE_FLR_1 | 1.3024 | 0.0000 | 1.3024 | 0.0378 | 1.3402 | 0.6764 | 0.00 | 0.00 | 8760.00 |
LOBBY_FLR_1 | 4.5335 | 0.0000 | 4.5335 | 0.1079 | 4.6415 | 1.8940 | 0.00 | 0.00 | 8760.00 |
ROOM_1_FLR_3 | 0.0617 | 0.0021 | 0.0638 | 0.0099 | 0.0738 | 0.0617 | 0.00 | 7650.83 | 1109.17 |
ROOM_2_FLR_3 | 0.0617 | 0.0021 | 0.0639 | 0.0099 | 0.0738 | 0.0617 | 0.00 | 7650.83 | 1109.17 |
ROOM_4_MULT19_FLR_3 | 0.8373 | 0.0021 | 0.8395 | 0.0028 | 0.8422 | 0.8373 | 0.00 | 7729.64 | 1030.36 |
ROOM_5_FLR_3 | 0.0617 | 0.0021 | 0.0639 | 0.0099 | 0.0738 | 0.0617 | 0.00 | 7650.83 | 1109.17 |
ROOM_6_FLR_3 | 0.0617 | 0.0022 | 0.0639 | 0.0099 | 0.0738 | 0.0617 | 0.00 | 7650.83 | 1109.17 |
CORRIDOR_FLR_3 | 1.0950 | 0.0000 | 1.0950 | 0.0120 | 1.1069 | 0.4748 | 0.00 | 0.00 | 8760.00 |
ROOM_1_FLR_6 | 0.0154 | 0.0026 | 0.0180 | 0.0099 | 0.0279 | 0.0154 | 0.00 | 7637.17 | 1122.83 |
ROOM_2_FLR_6 | 0.0154 | 0.0026 | 0.0180 | 0.0099 | 0.0280 | 0.0154 | 0.00 | 7637.17 | 1122.83 |
ROOM_3_MULT9_FLR_6 | 0.0992 | 0.0026 | 0.1017 | 0.0051 | 0.1068 | 0.0992 | 0.00 | 7637.53 | 1122.47 |
BANQUET_FLR_6 | 2.2247 | 0.0000 | 2.2247 | 0.0242 | 2.2489 | 1.1878 | 0.00 | 0.00 | 8760.00 |
DINING_FLR_6 | 2.3345 | 0.0000 | 2.3345 | 0.0242 | 2.3587 | 1.1878 | 0.00 | 0.00 | 8760.00 |
KITCHEN_FLR_6 | 2.2435 | 0.0000 | 2.2435 | 0.0217 | 2.2652 | 0.3674 | 0.00 | 0.00 | 8760.00 |
CORRIDOR_FLR_6 | 0.6597 | 0.0000 | 0.6597 | 0.0212 | 0.6809 | 0.1256 | 0.00 | 0.00 | 8760.00 |
Total Facility | 90.0431 | 0.2258 | 90.2689 | 0.7890 | 91.0579 | 73.9670 | 0.00 | 7801.26 | 8760.00 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV WITH REHEAT | 0.97E+09 | 0.00 | 0.97E+09 | 0.22E+09 | 0.00 | 0.00 | 8760.00 | 0.00 |
FLR_3_DOAS | 93579813.88 | 649750.60 | 94229564.48 | 64690340.46 | 0.00 | 0.00 | 8760.00 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV WITH REHEAT | 30.6856 | 0.0000 | 30.6856 | 6.9969 | 0.00 | 0.00 | 8760.00 |
FLR_3_DOAS | 2.9674 | 0.0206 | 2.9880 | 2.0513 | 0.00 | 0.00 | 8760.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV WITH REHEAT | 0.00 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FLR_3_DOAS | 0.00 | 7869.88 | 890.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV WITH REHEAT | 0.0000 | 30.6856 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
FLR_3_DOAS | 0.0000 | 2.9677 | 2.9678 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:58:20
Surfaces by ClassTotal | Outdoors | |
Wall | 119 | 44 |
Floor | 25 | 0 |
Roof | 33 | 11 |
Internal Mass | 22 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 30 | 30 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 22 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 1306 |
Defaulted Fields | 1181 |
Fields with Defaults | 3945 |
Autosized Fields | 350 |
Autosizable Fields | 402 |
Autocalculated Fields | 280 |
Autocalculatable Fields | 539 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:58:20
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 12134.96 | 134519.84 | 25-JAN-03:50 | 626175.88 | 27-JUL-18:10 |
Electricity:Building | 2943.68 | 36656.90 | 02-JAN-02:10 | 182730.36 | 02-JAN-20:10 |
Electricity:Zone:BASEMENT | 315.54 | 3631.19 | 02-JAN-02:10 | 23630.80 | 02-JAN-20:10 |
Electricity:SpaceType:GENERAL | 2925.41 | 36182.64 | 02-JAN-02:10 | 182063.43 | 02-JAN-20:10 |
InteriorLights:Electricity | 1174.11 | 10291.59 | 02-JAN-02:10 | 93091.76 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BASEMENT | 165.29 | 1501.97 | 02-JAN-02:10 | 13517.00 | 02-JAN-20:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 1174.11 | 10291.59 | 02-JAN-02:10 | 93091.76 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity | 1174.11 | 10291.59 | 02-JAN-02:10 | 93091.76 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 165.29 | 1501.97 | 02-JAN-02:10 | 13517.00 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 1174.11 | 10291.59 | 02-JAN-02:10 | 93091.76 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_1_FLR_1 | 18.59 | 220.70 | 02-JAN-02:10 | 1372.90 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 8.40 | 76.37 | 02-JAN-02:10 | 687.30 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 8.40 | 76.37 | 02-JAN-02:10 | 687.30 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_2_FLR_1 | 21.53 | 255.58 | 02-JAN-02:10 | 1589.82 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 9.73 | 88.43 | 02-JAN-02:10 | 795.89 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 9.73 | 88.43 | 02-JAN-02:10 | 795.89 | 02-JAN-20:10 |
Electricity:Zone:MECH_FLR_1 | 30.66 | 342.02 | 02-JAN-02:10 | 2327.13 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:MECH_FLR_1 | 18.19 | 165.30 | 02-JAN-02:10 | 1487.69 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:MECH_FLR_1 | 18.19 | 165.30 | 02-JAN-02:10 | 1487.69 | 02-JAN-20:10 |
Electricity:Zone:STORAGE_FLR_1 | 6.94 | 81.32 | 02-JAN-02:10 | 515.26 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 3.34 | 30.34 | 02-JAN-02:10 | 273.10 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 3.34 | 30.34 | 02-JAN-02:10 | 273.10 | 02-JAN-20:10 |
Electricity:Zone:LAUNDRY_FLR_1 | 72.06 | 1000.18 | 02-JAN-02:10 | 4910.17 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 4.13 | 37.49 | 02-JAN-02:10 | 337.37 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 4.13 | 37.49 | 02-JAN-02:10 | 337.37 | 02-JAN-20:10 |
Electricity:Zone:CAFE_FLR_1 | 40.96 | 445.13 | 02-JAN-02:10 | 3142.50 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CAFE_FLR_1 | 26.62 | 241.91 | 02-JAN-02:10 | 2177.23 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CAFE_FLR_1 | 26.62 | 241.91 | 02-JAN-02:10 | 2177.23 | 02-JAN-20:10 |
Electricity:Zone:LOBBY_FLR_1 | 293.89 | 3428.00 | 02-JAN-02:10 | 21878.53 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 144.90 | 1316.59 | 02-JAN-02:10 | 11849.32 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 144.90 | 1316.59 | 02-JAN-02:10 | 11849.32 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_3 | 32.70 | 383.52 | 01-JAN-02:10 | 2308.42 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 20.41 | 172.80 | 01-JAN-02:10 | 1570.91 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 20.41 | 172.80 | 01-JAN-02:10 | 1570.91 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_3 | 32.70 | 383.47 | 01-JAN-02:10 | 2308.15 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 20.41 | 172.78 | 01-JAN-02:10 | 1570.72 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 20.41 | 172.78 | 01-JAN-02:10 | 1570.72 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT19_FLR_3 | 472.46 | 5984.83 | 01-JAN-02:10 | 32482.97 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 243.71 | 2063.36 | 01-JAN-02:10 | 18757.86 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 243.71 | 2063.36 | 01-JAN-02:10 | 18757.86 | 01-JAN-19:10 |
Electricity:Zone:ROOM_4_MULT19_FLR_3 | 472.59 | 5986.46 | 01-JAN-02:10 | 32491.86 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 243.77 | 2063.93 | 01-JAN-02:10 | 18762.99 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 243.77 | 2063.93 | 01-JAN-02:10 | 18762.99 | 01-JAN-19:10 |
Electricity:Zone:ROOM_5_FLR_3 | 32.70 | 383.52 | 01-JAN-02:10 | 2308.42 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 20.41 | 172.80 | 01-JAN-02:10 | 1570.91 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 20.41 | 172.80 | 01-JAN-02:10 | 1570.91 | 01-JAN-19:10 |
Electricity:Zone:ROOM_6_FLR_3 | 32.70 | 383.47 | 01-JAN-02:10 | 2308.15 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 20.41 | 172.78 | 01-JAN-02:10 | 1570.72 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 20.41 | 172.78 | 01-JAN-02:10 | 1570.72 | 01-JAN-19:10 |
Electricity:Zone:CORRIDOR_FLR_3 | 62.74 | 570.05 | 02-JAN-02:10 | 5130.41 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 62.74 | 570.05 | 02-JAN-02:10 | 5130.41 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 62.74 | 570.05 | 02-JAN-02:10 | 5130.41 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_6 | 8.18 | 95.88 | 01-JAN-02:10 | 577.11 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 5.10 | 43.20 | 01-JAN-02:10 | 392.73 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 5.10 | 43.20 | 01-JAN-02:10 | 392.73 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_6 | 8.17 | 95.87 | 01-JAN-02:10 | 577.04 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 5.10 | 43.19 | 01-JAN-02:10 | 392.68 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 5.10 | 43.19 | 01-JAN-02:10 | 392.68 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT9_FLR_6 | 55.96 | 708.92 | 01-JAN-02:10 | 3847.72 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 28.87 | 244.41 | 01-JAN-02:10 | 2221.93 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 28.87 | 244.41 | 01-JAN-02:10 | 2221.93 | 01-JAN-19:10 |
Electricity:Zone:BANQUET_FLR_6 | 222.61 | 2674.12 | 02-JAN-02:10 | 10571.30 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 46.75 | 424.82 | 02-JAN-02:10 | 3823.39 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 46.75 | 424.82 | 02-JAN-02:10 | 3823.39 | 02-JAN-20:10 |
Electricity:Zone:DINING_FLR_6 | 222.61 | 2674.12 | 02-JAN-02:10 | 10571.30 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:DINING_FLR_6 | 46.75 | 424.82 | 02-JAN-02:10 | 3823.39 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:DINING_FLR_6 | 46.75 | 424.82 | 02-JAN-02:10 | 3823.39 | 02-JAN-20:10 |
Electricity:Zone:KITCHEN_FLR_6 | 470.78 | 6777.71 | 02-JAN-02:10 | 19298.76 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 12.48 | 113.42 | 02-JAN-02:10 | 1020.78 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 12.48 | 113.42 | 02-JAN-02:10 | 1020.78 | 02-JAN-20:10 |
Electricity:Zone:CORRIDOR_FLR_6 | 16.60 | 150.83 | 02-JAN-02:10 | 1357.44 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 16.60 | 150.83 | 02-JAN-02:10 | 1357.44 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 16.60 | 150.83 | 02-JAN-02:10 | 1357.44 | 02-JAN-20:10 |
InteriorEquipment:Electricity | 1751.30 | 25891.05 | 02-JAN-02:10 | 89674.66 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 150.26 | 2129.22 | 02-JAN-02:10 | 10113.80 | 02-JAN-20:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 1751.30 | 25891.05 | 02-JAN-02:10 | 89674.66 | 02-JAN-07:10 |
MiscPlug:InteriorEquipment:Electricity | 959.56 | 15202.41 | 02-JAN-02:10 | 59492.27 | 02-JAN-07:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 150.26 | 2129.22 | 02-JAN-02:10 | 10113.80 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 959.56 | 15202.41 | 02-JAN-02:10 | 59492.27 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.79 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.79 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 12.29 | 210.72 | 01-JAN-00:10 | 948.23 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 12.29 | 210.72 | 01-JAN-00:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 12.29 | 210.69 | 01-JAN-00:10 | 948.12 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 12.29 | 210.69 | 01-JAN-00:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 228.75 | 3921.46 | 01-JAN-00:10 | 17646.57 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 228.75 | 3921.46 | 01-JAN-00:10 | 17646.57 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 228.82 | 3922.53 | 01-JAN-00:10 | 17651.40 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 228.82 | 3922.53 | 01-JAN-00:10 | 17651.40 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 12.29 | 210.72 | 01-JAN-00:10 | 948.23 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 12.29 | 210.72 | 01-JAN-00:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 12.29 | 210.69 | 01-JAN-00:10 | 948.12 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 12.29 | 210.69 | 01-JAN-00:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 3.07 | 52.68 | 01-JAN-00:10 | 237.06 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 3.07 | 52.68 | 01-JAN-00:10 | 237.06 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 3.07 | 52.67 | 01-JAN-00:10 | 237.03 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 3.07 | 52.67 | 01-JAN-00:10 | 237.03 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 27.10 | 464.51 | 01-JAN-00:10 | 2090.30 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 27.10 | 464.51 | 01-JAN-00:10 | 2090.30 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 440.03 | 6190.03 | 01-JAN-00:10 | 16686.59 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 410.33 | 5248.28 | 01-JAN-00:10 | 15744.84 | 01-JAN-07:10 |
ReachInFreezer:InteriorEquipment:Electricity | 16.27 | 515.92 | 01-JAN-00:10 | 515.92 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 16.27 | 515.92 | 01-JAN-00:10 | 515.92 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 16.27 | 515.92 | 01-JAN-00:10 | 515.92 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 13.43 | 425.83 | 01-JAN-00:10 | 425.83 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 13.43 | 425.83 | 01-JAN-00:10 | 425.83 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 13.43 | 425.83 | 01-JAN-00:10 | 425.83 | 01-JAN-00:10 |
Refrigeration:Electricity | 75.79 | 1278.51 | 03-FEB-23:30 | 3644.83 | 25-AUG-06:40 |
Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 18.27 | 261.51 | 02-JAN-11:30 | 2271.91 | 01-JAN-11:10 |
General:Refrigeration:Electricity | 18.27 | 261.51 | 02-JAN-11:30 | 2271.91 | 01-JAN-11:10 |
General:Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 18.27 | 261.51 | 02-JAN-11:30 | 2271.91 | 01-JAN-11:10 |
Electricity:Plant | 5901.99 | 2768.99 | 25-JAN-03:50 | 341058.72 | 27-JUL-18:10 |
LowTempRefrigeration:Refrigeration:Electricity | 22.65 | 0.00 | 01-JAN-11:10 | 1889.43 | 07-NOV-08:20 |
MedTempRefrigeration:Refrigeration:Electricity | 34.87 | 946.12 | 27-JAN-02:10 | 1202.21 | 18-FEB-14:10 |
Fans:Electricity | 1826.65 | 50417.84 | 28-JAN-06:10 | 74877.68 | 30-SEP-15:20 |
Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Electricity:HVAC | 2379.90 | 66550.92 | 28-JAN-06:10 | 92696.42 | 29-JUL-18:20 |
ExteriorEquipment:Electricity | 679.68 | 10574.27 | 02-JAN-02:20 | 40537.60 | 02-JAN-07:20 |
Transformer:ExteriorEquipment:Electricity | 32.92 | 556.27 | 02-JAN-02:20 | 1912.91 | 02-JAN-21:10 |
ElectricityPurchased:Facility | 12134.96 | 134519.84 | 25-JAN-03:50 | 626175.88 | 27-JUL-18:10 |
ElectricityPurchased:Plant | 12134.96 | 134519.84 | 25-JAN-03:50 | 626175.88 | 27-JUL-18:10 |
Cogeneration:ElectricityPurchased | 12134.96 | 134519.84 | 25-JAN-03:50 | 626175.88 | 27-JUL-18:10 |
General:Cogeneration:ElectricityPurchased | 12134.96 | 134519.84 | 25-JAN-03:50 | 626175.88 | 27-JUL-18:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 12134.96 | 134519.84 | 25-JAN-03:50 | 626175.88 | 27-JUL-18:10 |
ElectricityNet:Plant | 12134.96 | 134519.84 | 25-JAN-03:50 | 626175.88 | 27-JUL-18:10 |
Cogeneration:ElectricityNet | 12134.96 | 134519.84 | 25-JAN-03:50 | 626175.88 | 27-JUL-18:10 |
General:Cogeneration:ElectricityNet | 12134.96 | 134519.84 | 25-JAN-03:50 | 626175.88 | 27-JUL-18:10 |
General:Fans:Electricity | 1826.65 | 50417.84 | 28-JAN-06:10 | 74877.68 | 30-SEP-15:20 |
ExteriorLights:Electricity | 262.62 | 0.00 | 01-JAN-07:20 | 16690.39 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 262.62 | 0.00 | 01-JAN-07:20 | 16690.39 | 01-JAN-00:10 |
ElevatorLift:ExteriorEquipment:Electricity | 616.11 | 9046.01 | 01-JAN-00:10 | 37691.69 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 30.65 | 972.00 | 01-JAN-00:10 | 972.00 | 01-JAN-00:10 |
HeatRecovery:Electricity | 520.33 | 15269.97 | 01-JAN-00:10 | 16791.79 | 01-JAN-09:20 |
General:HeatRecovery:Electricity | 520.33 | 15269.97 | 01-JAN-00:10 | 16791.79 | 01-JAN-09:20 |
WaterSystems:Electricity | 90.77 | 1086.98 | 23-AUG-00:10 | 4739.42 | 18-JAN-07:10 |
Water Heater:WaterSystems:Electricity | 90.77 | 1086.98 | 23-AUG-00:10 | 4739.42 | 18-JAN-07:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 5293.72 | 0.00 | 25-JAN-03:50 | 317380.64 | 27-JUL-18:10 |
General:Cooling:Electricity | 5293.72 | 0.00 | 25-JAN-03:50 | 317380.64 | 27-JUL-18:10 |
Pumps:Electricity | 459.98 | 160.64 | 03-FEB-08:20 | 16829.26 | 29-JUL-10:40 |
General:Pumps:Electricity | 459.98 | 160.64 | 03-FEB-08:20 | 16829.26 | 29-JUL-10:40 |
WIRED_LTG_ELECTRICITY | 41.33 | 0.00 | 01-JAN-00:10 | 3276.83 | 02-JAN-20:20 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 4881.68 | 41554.20 | 25-OCT-23:10 | 352716.65 | 17-DEC-18:00 |
NaturalGas:Building | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
NaturalGas:SpaceType:GENERAL | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:NaturalGas | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
InteriorEquipment:NaturalGas:SpaceType:GENERAL | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
Laundry:InteriorEquipment:NaturalGas | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
NaturalGas:Plant | 3092.84 | 18467.44 | 18-MAY-07:10 | 265195.31 | 17-DEC-18:00 |
WaterSystems:NaturalGas | 2623.98 | 18467.44 | 01-JAN-00:10 | 222392.17 | 17-JAN-21:20 |
Water Heater:WaterSystems:NaturalGas | 2623.98 | 18467.44 | 01-JAN-00:10 | 222392.17 | 17-JAN-21:20 |
Heating:NaturalGas | 468.86 | 0.00 | 02-JAN-21:50 | 98398.35 | 20-MAR-10:40 |
Boiler:Heating:NaturalGas | 468.86 | 0.00 | 02-JAN-21:50 | 98398.35 | 20-MAR-10:40 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 16383.96 | 0.00 | 25-JAN-03:50 | 955350.72 | 27-JUL-18:10 |
PlantLoopCoolingDemand:HVAC | 16383.96 | 0.00 | 25-JAN-03:50 | 955350.72 | 27-JUL-18:10 |
CoolingCoils:PlantLoopCoolingDemand | 16383.96 | 0.00 | 25-JAN-03:50 | 955350.72 | 27-JUL-18:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-21:10 |
Water:Plant | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-21:10 |
WaterSystems:Water | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-21:10 |
Water Heater:WaterSystems:Water | 5742.51 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-19:20 |
MainsWater:Facility | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-21:10 |
MainsWater:Plant | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-21:10 |
WaterSystems:MainsWater | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-21:10 |
Water Heater:WaterSystems:MainsWater | 5742.51 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-19:20 |
WaterUse:WaterSystems:Water | 4114.69 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-07:10 |
WaterUse:WaterSystems:MainsWater | 4114.69 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-07:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 72009.40 | 249775.78 | 31-JAN-08:30 | 4196475.15 | 27-JUL-18:10 |
EnergyTransfer:Building | 7554.41 | 125864.02 | 16-MAR-08:20 | 397045.80 | 29-JUL-18:10 |
EnergyTransfer:Zone:KITCHEN_FLR_6 | 788.12 | 12603.26 | 04-FEB-04:00 | 35983.06 | 23-JUL-10:50 |
Refrigeration:EnergyTransfer | 194.83 | 3929.75 | 03-FEB-23:30 | 10388.25 | 25-AUG-06:40 |
Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 97.41 | 1964.88 | 03-FEB-23:30 | 5194.13 | 25-AUG-06:40 |
General:Refrigeration:EnergyTransfer | 97.41 | 1964.88 | 03-FEB-23:30 | 5194.13 | 25-AUG-06:40 |
General:Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 97.41 | 1964.88 | 03-FEB-23:30 | 5194.13 | 25-AUG-06:40 |
EnergyTransfer:Plant | 39785.94 | 36215.22 | 25-JAN-03:50 | 2278271.55 | 27-JUL-18:10 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 25.91 | 0.00 | 01-JAN-11:10 | 2686.44 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 71.50 | 1788.35 | 27-JAN-02:10 | 2556.62 | 18-FEB-14:10 |
EnergyTransfer:Zone:BASEMENT | 571.45 | 10899.84 | 13-MAR-11:00 | 25224.75 | 02-AUG-18:10 |
Heating:EnergyTransfer | 1.25 | 0.00 | 01-JAN-00:10 | 10145.63 | 04-FEB-09:10 |
Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer | 1.25 | 0.00 | 01-JAN-00:10 | 10145.63 | 04-FEB-09:10 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer | 7455.74 | 121059.34 | 04-FEB-07:10 | 393265.51 | 29-JUL-18:10 |
Cooling:EnergyTransfer:Zone:BASEMENT | 571.45 | 10899.84 | 13-MAR-11:00 | 25224.75 | 02-AUG-18:10 |
General:Cooling:EnergyTransfer | 7455.74 | 121059.34 | 04-FEB-07:10 | 393265.51 | 29-JUL-18:10 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 571.45 | 10899.84 | 13-MAR-11:00 | 25224.75 | 02-AUG-18:10 |
EnergyTransfer:Zone:RETAIL_1_FLR_1 | 65.05 | 5.09 | 04-FEB-04:50 | 3492.96 | 08-NOV-11:40 |
Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 150.57 | 04-FEB-07:20 |
General:Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 150.57 | 04-FEB-07:20 |
Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 65.05 | 0.00 | 04-FEB-04:50 | 3492.96 | 08-NOV-11:40 |
General:Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 65.05 | 0.00 | 04-FEB-04:50 | 3492.96 | 08-NOV-11:40 |
EnergyTransfer:Zone:RETAIL_2_FLR_1 | 52.02 | 767.92 | 20-MAR-09:50 | 2374.99 | 29-JUL-18:10 |
Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 52.02 | 767.92 | 20-MAR-09:50 | 2374.99 | 29-JUL-18:10 |
General:Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 52.02 | 767.92 | 20-MAR-09:50 | 2374.99 | 29-JUL-18:10 |
EnergyTransfer:Zone:MECH_FLR_1 | 52.39 | 265.83 | 04-FEB-06:00 | 2584.90 | 29-JUL-18:10 |
Heating:EnergyTransfer:Zone:MECH_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:MECH_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 52.39 | 265.83 | 04-FEB-06:00 | 2584.90 | 29-JUL-18:10 |
General:Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 52.39 | 265.83 | 04-FEB-06:00 | 2584.90 | 29-JUL-18:10 |
EnergyTransfer:Zone:STORAGE_FLR_1 | 24.86 | 47.99 | 04-FEB-07:30 | 1271.40 | 29-JUL-18:10 |
Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 24.86 | 47.99 | 04-FEB-07:30 | 1271.40 | 29-JUL-18:10 |
General:Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 24.86 | 47.99 | 04-FEB-07:30 | 1271.40 | 29-JUL-18:10 |
EnergyTransfer:Zone:LAUNDRY_FLR_1 | 629.71 | 9321.26 | 04-FEB-06:00 | 37904.85 | 27-JUL-20:00 |
Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 629.71 | 9321.26 | 04-FEB-06:00 | 37904.85 | 27-JUL-20:00 |
General:Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 629.71 | 9321.26 | 04-FEB-06:00 | 37904.85 | 27-JUL-20:00 |
EnergyTransfer:Zone:CAFE_FLR_1 | 317.92 | 3212.23 | 16-MAR-08:10 | 14249.61 | 09-DEC-11:40 |
Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 317.92 | 3212.23 | 16-MAR-08:10 | 14249.61 | 09-DEC-11:40 |
General:Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 317.92 | 3212.23 | 16-MAR-08:10 | 14249.61 | 09-DEC-11:40 |
EnergyTransfer:Zone:LOBBY_FLR_1 | 1063.20 | 16916.29 | 16-MAR-09:10 | 45087.94 | 29-JUL-18:10 |
Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 1063.20 | 16916.29 | 16-MAR-09:10 | 45087.94 | 29-JUL-18:10 |
General:Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 1063.20 | 16916.29 | 16-MAR-09:10 | 45087.94 | 29-JUL-18:10 |
EnergyTransfer:Zone:ROOM_1_FLR_3 | 107.46 | 0.05 | 20-MAR-03:30 | 11364.77 | 30-SEP-15:10 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 0.13 | 0.00 | 01-JAN-00:10 | 1569.32 | 04-FEB-07:00 |
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 0.13 | 0.00 | 01-JAN-00:10 | 1569.32 | 04-FEB-07:00 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 107.34 | 0.00 | 25-JAN-02:30 | 11364.77 | 30-SEP-15:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 107.34 | 0.00 | 25-JAN-02:30 | 11364.77 | 30-SEP-15:10 |
EnergyTransfer:Zone:ROOM_2_FLR_3 | 98.77 | 0.24 | 20-DEC-03:50 | 11055.82 | 28-JUL-15:10 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 0.25 | 0.00 | 01-JAN-00:10 | 1981.91 | 16-MAR-08:10 |
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 0.25 | 0.00 | 01-JAN-00:10 | 1981.91 | 16-MAR-08:10 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 98.52 | 0.00 | 09-JAN-04:40 | 11055.82 | 28-JUL-15:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 98.52 | 0.00 | 09-JAN-04:40 | 11055.82 | 28-JUL-15:10 |
EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 823.41 | 6428.04 | 04-FEB-06:00 | 57423.74 | 03-DEC-14:00 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 823.41 | 6428.04 | 04-FEB-06:00 | 57423.74 | 03-DEC-14:00 |
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 823.41 | 6428.04 | 04-FEB-06:00 | 57423.74 | 03-DEC-14:00 |
EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 911.65 | 1271.08 | 04-FEB-06:00 | 79130.96 | 29-JUL-18:20 |
Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 0.27 | 0.00 | 01-JAN-00:10 | 5705.94 | 04-FEB-09:10 |
General:Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 0.27 | 0.00 | 01-JAN-00:10 | 5705.94 | 04-FEB-09:10 |
Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 911.38 | 0.00 | 03-FEB-16:20 | 79130.96 | 29-JUL-18:20 |
General:Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 911.38 | 0.00 | 03-FEB-16:20 | 79130.96 | 29-JUL-18:20 |
EnergyTransfer:Zone:ROOM_5_FLR_3 | 108.45 | 0.16 | 23-JAN-02:10 | 9655.19 | 29-JUL-15:10 |
Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 0.11 | 0.00 | 01-JAN-00:10 | 1641.15 | 04-FEB-07:00 |
General:Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 0.11 | 0.00 | 01-JAN-00:10 | 1641.15 | 04-FEB-07:00 |
Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 108.33 | 0.00 | 23-JAN-02:10 | 9655.19 | 29-JUL-15:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 108.33 | 0.00 | 23-JAN-02:10 | 9655.19 | 29-JUL-15:10 |
EnergyTransfer:Zone:ROOM_6_FLR_3 | 99.62 | 0.56 | 20-MAR-05:30 | 9710.76 | 23-JUL-08:10 |
Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 0.24 | 0.00 | 01-JAN-00:10 | 1888.81 | 04-FEB-06:00 |
General:Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 0.24 | 0.00 | 01-JAN-00:10 | 1888.81 | 04-FEB-06:00 |
Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 99.38 | 0.00 | 09-JAN-04:10 | 9710.76 | 23-JUL-08:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 99.38 | 0.00 | 09-JAN-04:10 | 9710.76 | 23-JUL-08:10 |
EnergyTransfer:Zone:CORRIDOR_FLR_3 | 283.36 | 2335.37 | 04-FEB-07:10 | 12570.33 | 30-JUL-10:40 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 283.36 | 2335.37 | 04-FEB-07:10 | 12570.33 | 30-JUL-10:40 |
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 283.36 | 2335.37 | 04-FEB-07:10 | 12570.33 | 30-JUL-10:40 |
EnergyTransfer:Zone:ROOM_1_FLR_6 | 29.31 | 0.05 | 27-NOV-02:30 | 3127.43 | 29-JUL-15:10 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 0.08 | 0.00 | 01-JAN-00:10 | 603.45 | 16-MAR-08:10 |
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 0.08 | 0.00 | 01-JAN-00:10 | 603.45 | 16-MAR-08:10 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 29.23 | 0.00 | 08-JAN-06:10 | 3127.43 | 29-JUL-15:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 29.23 | 0.00 | 08-JAN-06:10 | 3127.43 | 29-JUL-15:10 |
EnergyTransfer:Zone:ROOM_2_FLR_6 | 27.03 | 0.11 | 14-DEC-03:20 | 3151.49 | 28-JUL-15:10 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 0.14 | 0.00 | 01-JAN-00:10 | 714.87 | 16-MAR-08:10 |
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 0.14 | 0.00 | 01-JAN-00:10 | 714.87 | 16-MAR-08:10 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 26.90 | 0.00 | 08-JAN-06:10 | 3151.49 | 28-JUL-15:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 26.90 | 0.00 | 08-JAN-06:10 | 3151.49 | 28-JUL-15:10 |
EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 172.26 | 4.25 | 05-FEB-06:40 | 14358.73 | 26-JAN-16:10 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 0.04 | 0.00 | 01-JAN-00:10 | 1558.19 | 04-FEB-07:00 |
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 0.04 | 0.00 | 01-JAN-00:10 | 1558.19 | 04-FEB-07:00 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 172.23 | 0.00 | 04-FEB-02:10 | 14358.73 | 26-JAN-16:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 172.23 | 0.00 | 04-FEB-02:10 | 14358.73 | 26-JAN-16:10 |
EnergyTransfer:Zone:BANQUET_FLR_6 | 571.44 | 10647.69 | 16-MAR-08:20 | 23491.95 | 27-JUL-18:10 |
Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 571.44 | 10647.69 | 16-MAR-08:20 | 23491.95 | 27-JUL-18:10 |
General:Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 571.44 | 10647.69 | 16-MAR-08:20 | 23491.95 | 27-JUL-18:10 |
EnergyTransfer:Zone:DINING_FLR_6 | 608.21 | 11941.92 | 16-MAR-08:20 | 24830.75 | 27-JUL-18:10 |
Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 608.21 | 11941.92 | 16-MAR-08:20 | 24830.75 | 27-JUL-18:10 |
General:Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 608.21 | 11941.92 | 16-MAR-08:20 | 24830.75 | 27-JUL-18:10 |
Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 690.70 | 10412.94 | 04-FEB-04:00 | 30917.08 | 23-JUL-10:50 |
General:Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 690.70 | 10412.94 | 04-FEB-04:00 | 30917.08 | 23-JUL-10:50 |
EnergyTransfer:Zone:CORRIDOR_FLR_6 | 148.71 | 39.86 | 04-FEB-08:00 | 7375.06 | 29-JUL-17:20 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 305.94 | 04-FEB-07:10 |
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 305.94 | 04-FEB-07:10 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 148.71 | 0.00 | 04-FEB-06:10 | 7375.06 | 29-JUL-17:20 |
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 148.71 | 0.00 | 04-FEB-06:10 | 7375.06 | 29-JUL-17:20 |
PlantLoopHeatingDemand:Facility | 837.71 | 9044.68 | 30-JUL-00:10 | 85007.64 | 20-MAR-10:40 |
PlantLoopHeatingDemand:Plant | 535.81 | 6417.92 | 19-JUL-00:50 | 39050.24 | 25-JAN-07:10 |
WaterSystems:PlantLoopHeatingDemand | 535.81 | 6417.92 | 19-JUL-00:50 | 39050.24 | 25-JAN-07:10 |
General:WaterSystems:PlantLoopHeatingDemand | 535.81 | 6417.92 | 19-JUL-00:50 | 39050.24 | 25-JAN-07:10 |
EnergyTransfer:HVAC | 24669.05 | 21335.58 | 13-NOV-08:20 | 1524124.30 | 27-JUL-18:10 |
HeatingCoils:EnergyTransfer | 301.90 | 0.00 | 02-JAN-21:50 | 70028.25 | 20-MAR-10:40 |
PlantLoopHeatingDemand:HVAC | 301.90 | 0.00 | 02-JAN-21:50 | 70028.25 | 20-MAR-10:40 |
HeatingCoils:PlantLoopHeatingDemand | 301.90 | 0.00 | 02-JAN-21:50 | 70028.25 | 20-MAR-10:40 |
CoolingCoils:EnergyTransfer | 16383.96 | 0.00 | 25-JAN-03:50 | 955350.72 | 27-JUL-18:10 |
HeatRecoveryForHeating:EnergyTransfer | 80.71 | 0.00 | 01-JAN-00:10 | 287887.68 | 04-FEB-07:00 |
HeatRecoveryForCooling:EnergyTransfer | 7902.48 | 0.00 | 01-JAN-00:10 | 598067.25 | 14-JUL-11:00 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:EnergyTransfer | 535.81 | 6417.92 | 19-JUL-00:50 | 39050.24 | 25-JAN-07:10 |
WaterUse:WaterSystems:EnergyTransfer | 535.81 | 6417.92 | 19-JUL-00:50 | 39050.24 | 25-JAN-07:10 |
Boilers:EnergyTransfer | 299.40 | 0.00 | 02-JAN-21:50 | 76117.71 | 20-MAR-10:40 |
Chillers:EnergyTransfer | 16779.80 | 0.00 | 25-JAN-03:50 | 967946.11 | 27-JUL-18:10 |
HeatRejection:EnergyTransfer | 22073.52 | 0.00 | 25-JAN-03:50 | 1285326.75 | 27-JUL-18:10 |
General:HeatRejection:EnergyTransfer | 22073.52 | 0.00 | 25-JAN-03:50 | 1285326.75 | 27-JUL-18:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:58:20
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 0.000 | -571.454 | 0.000 | 0.000 | 157.215 | 165.288 | 150.255 | 0.000 | 0.000 | 0.000 | 98.696 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 0.000 | 0.000 | 0.001 | -65.052 | 0.000 | 0.000 | 15.931 | 8.404 | 10.186 | 22.828 | 0.000 | 2.563 | 7.367 | 0.000 | -1.715 | 0.000 | -0.512 | -0.000 |
RETAIL_2_FLR_1 | 0.000 | 0.000 | 0.000 | -52.023 | 0.000 | 0.000 | 18.430 | 9.732 | 11.795 | 0.000 | 0.000 | 1.025 | 11.239 | 0.000 | 0.000 | 0.000 | -0.198 | 0.000 |
MECH_FLR_1 | 0.000 | 0.000 | 0.000 | -52.393 | 0.000 | 0.000 | 3.930 | 18.192 | 12.471 | 0.000 | 0.000 | 2.475 | 15.781 | 0.000 | 0.000 | 0.000 | -0.455 | 0.000 |
STORAGE_FLR_1 | 0.000 | 0.000 | 0.000 | -24.858 | 0.000 | 0.000 | 3.033 | 3.340 | 3.598 | 0.000 | 0.000 | 1.445 | 13.705 | 0.000 | 0.000 | 0.000 | -0.262 | 0.000 |
LAUNDRY_FLR_1 | 0.000 | 0.000 | 0.000 | -629.718 | 0.000 | 0.000 | 12.230 | 4.125 | 658.131 | 0.000 | 0.000 | 3.248 | 0.000 | 0.000 | 0.000 | 0.000 | -0.699 | -47.316 |
CAFE_FLR_1 | 0.000 | 0.000 | 0.000 | -317.921 | 0.000 | 0.000 | 204.285 | 26.624 | 14.341 | 63.623 | 0.000 | 5.406 | 10.323 | 0.000 | -5.451 | 0.000 | -1.230 | -0.001 |
LOBBY_FLR_1 | 0.000 | 0.000 | 0.000 | -1063.210 | 0.000 | 0.000 | 610.445 | 144.896 | 148.998 | 85.915 | 0.000 | 16.013 | 67.170 | 0.000 | -6.758 | 0.000 | -3.469 | -0.000 |
ROOM_1_FLR_3 | 0.309 | -86.906 | 0.000 | -20.609 | 0.000 | 0.000 | 9.635 | 20.410 | 12.292 | 48.982 | 0.000 | 5.783 | 15.721 | 0.000 | -4.002 | 0.000 | -1.613 | -0.000 |
ROOM_2_FLR_3 | 0.568 | -78.312 | 0.000 | -20.521 | 0.000 | 0.000 | 9.644 | 20.407 | 12.291 | 41.028 | 0.000 | 5.804 | 14.652 | 0.000 | -3.984 | 0.000 | -1.577 | -0.001 |
ROOM_3_MULT19_FLR_3 | 0.000 | -491.402 | 0.000 | -332.002 | 0.000 | 0.000 | 0.000 | 243.708 | 228.754 | 256.723 | 0.000 | 20.037 | 131.992 | 0.000 | -32.360 | 0.000 | -25.449 | 0.000 |
ROOM_4_MULT19_FLR_3 | 0.744 | -636.032 | 0.000 | -275.781 | 0.000 | 0.000 | 183.606 | 243.774 | 228.817 | 154.791 | 0.000 | 35.574 | 97.772 | 0.000 | -20.530 | 0.000 | -12.735 | -0.005 |
ROOM_5_FLR_3 | 0.295 | -87.847 | 0.000 | -20.662 | 0.000 | 0.000 | 9.629 | 20.410 | 12.292 | 50.138 | 0.000 | 5.762 | 15.464 | 0.000 | -3.838 | 0.000 | -1.643 | -0.001 |
ROOM_6_FLR_3 | 0.541 | -79.090 | 0.000 | -20.585 | 0.000 | 0.000 | 9.638 | 20.407 | 12.291 | 42.074 | 0.000 | 5.772 | 14.284 | 0.000 | -3.726 | 0.000 | -1.605 | -0.001 |
CORRIDOR_FLR_3 | 0.000 | 0.000 | 0.000 | -283.364 | 0.000 | 0.000 | 119.497 | 62.736 | 0.000 | 49.668 | 0.000 | 6.301 | 51.396 | 0.000 | -4.689 | 0.000 | -1.544 | 0.000 |
ROOM_1_FLR_6 | 0.152 | -24.151 | 0.000 | -5.154 | 0.000 | 0.000 | 2.409 | 5.102 | 3.073 | 12.070 | 0.000 | 1.441 | 6.473 | 0.000 | -0.994 | 0.000 | -0.421 | -0.000 |
ROOM_2_FLR_6 | 0.261 | -21.883 | 0.000 | -5.134 | 0.000 | 0.000 | 2.411 | 5.102 | 3.073 | 10.103 | 0.000 | 1.445 | 6.023 | 0.000 | -0.987 | 0.000 | -0.413 | -0.000 |
ROOM_3_MULT9_FLR_6 | 0.121 | -139.117 | 0.000 | -33.190 | 0.000 | 0.000 | 21.664 | 28.868 | 27.097 | 58.721 | 0.000 | 7.015 | 35.780 | 0.000 | -4.538 | 0.000 | -2.421 | -0.001 |
BANQUET_FLR_6 | 0.000 | 0.000 | 0.000 | -571.449 | 0.000 | 0.000 | 351.989 | 46.753 | 175.857 | 17.237 | 0.000 | 3.238 | 0.000 | 0.000 | -2.963 | 0.000 | -0.885 | -19.776 |
DINING_FLR_6 | 0.000 | 0.000 | 0.000 | -608.211 | 0.000 | 0.000 | 350.766 | 46.753 | 175.857 | 16.779 | 0.000 | 3.189 | 18.957 | 0.000 | -3.192 | 0.000 | -0.899 | -0.002 |
KITCHEN_FLR_6 | 0.000 | 0.000 | 0.000 | -690.697 | 0.000 | 0.000 | 30.124 | 12.482 | 556.656 | 23.357 | 0.000 | 2.039 | 69.903 | 0.000 | -2.850 | 0.000 | -1.015 | 0.000 |
CORRIDOR_FLR_6 | 0.000 | 0.000 | 0.001 | -148.708 | 0.000 | 0.000 | 32.541 | 16.599 | 0.000 | 23.395 | 0.000 | 3.102 | 75.657 | 0.000 | -1.952 | 0.000 | -0.635 | 0.000 |
Total Facility | 2.991 | -1644.742 | 0.002 | -5812.699 | 0.000 | 0.000 | 2159.049 | 1174.112 | 2458.123 | 977.432 | 0.000 | 138.678 | 778.354 | 0.000 | -104.529 | 0.000 | -59.680 | -67.105 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 02-AUG-18:10 | 0.00 | 0.00 | 0.00 | -25278.66 | 0.00 | 0.00 | 6161.76 | 12015.03 | 9581.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2479.63 |
RETAIL_1_FLR_1 | 08-NOV-11:35 | 0.00 | 0.00 | 0.00 | -3527.00 | 0.00 | 0.00 | 156.11 | 190.92 | 252.59 | 4236.05 | 0.00 | 86.54 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1395.21 |
RETAIL_2_FLR_1 | 27-JUL-18:10 | 0.00 | 0.00 | 0.00 | -2384.23 | 0.00 | 0.00 | 725.49 | 707.46 | 752.15 | 0.00 | 0.00 | 84.26 | 114.88 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 29-JUL-10:35 | 0.00 | 0.00 | 0.00 | -2616.96 | 0.00 | 0.00 | 65.43 | 413.25 | 309.27 | 0.00 | 0.00 | 207.63 | 1621.38 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 29-JUL-10:35 | 0.00 | 0.00 | 0.00 | -1314.02 | 0.00 | 0.00 | 50.26 | 75.86 | 89.22 | 0.00 | 0.00 | 119.30 | 979.38 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 27-JUL-20:00 | 0.00 | 0.00 | 0.00 | -37905.67 | 0.00 | 0.00 | 425.99 | 337.37 | 44299.38 | 0.00 | 0.00 | 141.80 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -7298.86 |
CAFE_FLR_1 | 09-DEC-11:35 | 0.00 | 0.00 | 0.00 | -14449.99 | 0.00 | 0.00 | 3225.94 | 604.78 | 355.63 | 12040.61 | 0.00 | 220.33 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1997.31 |
LOBBY_FLR_1 | 27-JUL-18:10 | 0.00 | 0.00 | 0.00 | -45395.66 | 0.00 | 0.00 | 24439.44 | 10532.73 | 9501.36 | 2618.31 | 0.00 | 1366.82 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -3062.99 |
ROOM_1_FLR_3 | 24-FEB-16:02 | 0.00 | -12467.77 | 0.00 | -737.56 | 0.00 | 0.00 | 235.29 | 439.85 | 273.93 | 7404.87 | 0.00 | 115.58 | 4735.80 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 24-FEB-16:02 | 0.00 | -12414.75 | 0.00 | -727.56 | 0.00 | 0.00 | 235.28 | 439.80 | 273.90 | 6207.68 | 0.00 | 122.00 | 5863.64 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 03-DEC-14:00 | 0.00 | -46601.78 | 0.00 | -10820.86 | 0.00 | 0.00 | 0.00 | 6190.09 | 5686.12 | 51654.33 | 0.00 | 265.78 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -6373.68 |
ROOM_4_MULT19_FLR_3 | 17-APR-18:02 | 0.00 | -80785.85 | 0.00 | -10293.86 | 0.00 | 0.00 | 6374.59 | 16699.06 | 9610.21 | 6626.57 | 0.00 | 1826.33 | 49942.95 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 24-FEB-19:01 | 0.00 | -11172.82 | 0.00 | -731.73 | 0.00 | 0.00 | 335.51 | 1398.11 | 516.26 | 0.00 | 0.00 | 0.00 | 10295.76 | 0.00 | -532.80 | 0.00 | -108.29 | 0.00 |
ROOM_6_FLR_3 | 29-JUL-15:02 | 0.00 | -11152.73 | 0.00 | -753.26 | 0.00 | 0.00 | 130.71 | 518.34 | 305.51 | 3299.52 | 0.00 | 581.84 | 7070.07 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 30-JUL-10:35 | 0.00 | 0.00 | 0.00 | -12609.33 | 0.00 | 0.00 | 1944.70 | 1710.14 | 0.00 | 4288.70 | 0.00 | 554.58 | 4111.22 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 24-FEB-16:02 | 0.00 | -3321.42 | 0.00 | -184.32 | 0.00 | 0.00 | 58.82 | 109.96 | 68.48 | 1823.41 | 0.00 | 28.22 | 1416.85 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 28-JUL-15:02 | 0.00 | -3319.62 | 0.00 | -189.63 | 0.00 | 0.00 | 58.82 | 109.95 | 68.48 | 1814.39 | 0.00 | 142.64 | 1314.98 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 26-JAN-16:02 | 0.00 | -14372.83 | 0.00 | -1187.91 | 0.00 | 0.00 | 529.40 | 622.14 | 603.86 | 6543.61 | 0.00 | 0.00 | 7709.09 | 0.00 | -0.00 | 0.00 | -447.36 | 0.00 |
BANQUET_FLR_6 | 27-JUL-18:10 | 0.00 | 0.00 | 0.00 | -23847.16 | 0.00 | 0.00 | 14156.44 | 3398.57 | 6747.90 | 1275.71 | 0.00 | 287.11 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2018.57 |
DINING_FLR_6 | 27-JUL-18:10 | 0.00 | 0.00 | 0.00 | -25183.04 | 0.00 | 0.00 | 14103.74 | 3398.57 | 6747.90 | 1253.13 | 0.00 | 285.48 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -605.79 |
KITCHEN_FLR_6 | 23-JUL-10:50 | 0.00 | 0.00 | 0.00 | -30910.63 | 0.00 | 0.00 | 464.20 | 340.26 | 24459.16 | 2823.75 | 0.00 | 226.74 | 2596.52 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 29-JUL-10:35 | 0.00 | 0.00 | 0.00 | -7401.64 | 0.00 | 0.00 | 521.48 | 377.07 | 0.00 | 1864.19 | 0.00 | 255.96 | 4382.94 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 29-JUL-18:02 | 0.00 | -175800.27 | 0.00 | -246050.52 | 0.00 | 0.00 | 71741.18 | 82807.27 | 115371.52 | 38083.19 | 0.00 | 12642.63 | 101205.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 04-FEB-07:20 | 0.00 | 0.00 | 150.57 | 0.00 | 0.00 | 0.00 | 449.85 | 229.10 | 288.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -560.24 | 0.00 | -349.24 | -208.72 |
RETAIL_2_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 16-MAR-08:62 | 4514.27 | 406.08 | 0.00 | -406.08 | 0.00 | 0.00 | 102.04 | 691.20 | 453.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -507.37 | 0.00 | -637.74 | -4615.45 |
ROOM_2_FLR_3 | 26-JAN-09:02 | 4594.80 | 410.35 | 0.00 | -410.35 | 0.00 | 0.00 | 101.55 | 691.12 | 452.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -259.48 | 0.00 | -369.79 | -5211.18 |
ROOM_3_MULT19_FLR_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 03-FEB-16:03 | 28544.92 | 6171.12 | 0.00 | -6171.12 | 0.00 | 0.00 | 4886.62 | 5253.64 | 5099.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -176.02 | 0.00 | -14735.63 | -28872.82 |
ROOM_5_FLR_3 | 16-MAR-15:04 | 3580.86 | 531.96 | 0.00 | -531.96 | 0.00 | 0.00 | 236.33 | 439.85 | 273.93 | 1802.72 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -399.31 | -5934.40 |
ROOM_6_FLR_3 | 24-JAN-16:03 | 3628.71 | 467.00 | 0.00 | -467.00 | 0.00 | 0.00 | 257.34 | 439.80 | 273.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -243.06 | 0.00 | -766.09 | -3590.59 |
CORRIDOR_FLR_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 16-MAR-08:62 | 1340.75 | 92.59 | 0.00 | -92.59 | 0.00 | 0.00 | 26.15 | 172.80 | 113.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -115.35 | 0.00 | -154.05 | -1383.56 |
ROOM_2_FLR_6 | 16-MAR-08:62 | 1360.17 | 86.68 | 0.00 | -86.68 | 0.00 | 0.00 | 26.51 | 172.78 | 113.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -224.93 | 0.00 | -149.96 | -1297.82 |
ROOM_3_MULT9_FLR_6 | 16-MAR-08:62 | 4676.69 | 676.12 | 0.00 | -676.12 | 0.00 | 0.00 | 226.29 | 977.65 | 998.70 | 393.23 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -749.76 | -6522.80 |
BANQUET_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 04-FEB-07:10 | 0.00 | 0.00 | 305.94 | 0.00 | 0.00 | 0.00 | 916.54 | 452.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1008.19 | 0.00 | -448.20 | -218.56 |
Total Facility | 19-MAR-15:05 | -92657.54 | 137481.26 | 0.00 | -137481.26 | 0.00 | 0.00 | 36545.80 | 25732.27 | 75340.19 | 29931.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -34803.90 | -40088.20 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:58:20
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV WITH REHEAT | 21.3242 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 21.2175 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
FLR_3_DOAS | 2.0513 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.0513 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV WITH REHEAT | 21.2175 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 21.2175 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
FLR_3_DOAS | 2.0513 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.0513 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | VAV WITH REHEAT | 0.000000 | 106.4990 | 0.000432 | 1978.83 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | 0.000000 | 10.8290 | 0.001181 | 67.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | 0.000000 | 12.5400 | 0.001181 | 77.67 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
MECH_FLR_1 | VAV WITH REHEAT | 0.000000 | 2.6520 | 0.000000 | 164.24 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | 0.000000 | 2.0400 | 0.000610 | 94.76 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | 0.000000 | 8.4000 | 0.000000 | 78.04 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | 0.000000 | 142.3000 | 0.003581 | 188.86 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | 0.000000 | 422.4350 | 0.001448 | 1308.19 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1863.81 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1864.32 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | 0.000000 | 83.8280 | 0.000305 | 1557.62 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000396 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000396 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.000000 | 13.5000 | 0.000449 | 220.77 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003581 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DINING_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003581 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | 0.000000 | 22.2380 | 0.003556 | 103.30 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | 0.000000 | 22.1800 | 0.000305 | 412.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV WITH REHEAT | 0.00 | 0.001045 | 6694.0231 | 0.0000 | 0.0000 | 0.0000 | |
FLR_3_DOAS | 0.00 | 0.000441 | 4651.2638 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.6616 | 2.6616 | 2.6483 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2936 | 0.2936 | 0.2922 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2422 | 0.2422 | 0.2410 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2615 | 0.2615 | 0.2601 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1305 | 0.1305 | 0.1299 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.2667 | 3.2667 | 3.2503 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3095 | 1.3095 | 1.3030 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 4.5583 | 4.5583 | 4.5355 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8371 | 0.8371 | 0.8371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8373 | 0.8373 | 0.8373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1009 | 1.1009 | 1.0954 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0992 | 0.0992 | 0.0992 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.2369 | 2.2369 | 2.2257 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.3472 | 2.3472 | 2.3355 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.2519 | 2.2519 | 2.2406 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6633 | 0.6633 | 0.6600 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV WITH REHEAT | 21.3242 | 21.2175 | 21.3242 | 21.2175 | 0.0000 | 1.0000 |
FLR_3_DOAS | 2.0513 | 2.0513 | 2.0513 | 2.0513 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.6483 | 2.6483 | 2.6483 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2922 | 0.2922 | 0.2922 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2410 | 0.2410 | 0.2410 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2601 | 0.2601 | 0.2601 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1299 | 0.1299 | 0.1299 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.2503 | 3.2503 | 3.2503 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3030 | 1.3030 | 1.3030 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 4.5355 | 4.5355 | 4.5355 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8371 | 0.8371 | 0.8371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8373 | 0.8373 | 0.8373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0954 | 1.0954 | 1.0954 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0992 | 0.0992 | 0.0992 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.2257 | 2.2257 | 2.2257 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.3355 | 2.3355 | 2.3355 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.2406 | 2.2406 | 2.2406 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6600 | 0.6600 | 0.6600 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV WITH REHEAT | 21.2175 | 21.2175 | 21.2175 | 21.2175 | 0.0000 | 1.0000 |
FLR_3_DOAS | 2.0513 | 2.0513 | 2.0513 | 2.0513 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:58:20
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Miami Intl Ap FL USA TMY3 WMO#=722020 |
Total gross floor area [m2] | 11345.29 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 1978.83 | 1978.83 | 0.00 | 168.00 |
RETAIL_1_FLR_1 | 67.07 | 67.07 | 0.00 | 168.00 |
RETAIL_2_FLR_1 | 77.67 | 77.67 | 0.00 | 168.00 |
MECH_FLR_1 | 164.24 | 164.24 | 0.00 | 168.00 |
STORAGE_FLR_1 | 94.76 | 94.76 | 0.00 | 168.00 |
LAUNDRY_FLR_1 | 78.04 | 78.04 | 0.00 | 168.00 |
CAFE_FLR_1 | 188.86 | 188.86 | 0.00 | 168.00 |
LOBBY_FLR_1 | 1308.19 | 1308.19 | 0.00 | 168.00 |
ROOM_1_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT19_FLR_3 | 24.52 | 24.52 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 24.53 | 24.53 | 0.00 | 168.00 |
ROOM_5_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_6_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
CORRIDOR_FLR_3 | 389.40 | 389.40 | 0.00 | 168.00 |
ROOM_1_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT9_FLR_6 | 24.53 | 24.53 | 0.00 | 168.00 |
BANQUET_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
DINING_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
KITCHEN_FLR_6 | 103.30 | 103.30 | 0.00 | 168.00 |
CORRIDOR_FLR_6 | 412.12 | 412.12 | 0.00 | 168.00 |
Totals | 11345.29 | 11345.29 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 45.33 |
Number of hours not met | 45.33 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 468.86 | 98398.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 5293.72 | 317380.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 1174.11 | 93091.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 262.62 | 16690.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 959.56 | 59492.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 762.04 | 29240.64 | 1198.64 | 74976.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 16.27 | 515.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 13.43 | 425.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Laundry | 0.00 | 0.00 | 590.20 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 32.92 | 1912.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 616.11 | 37691.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 30.65 | 972.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 1826.65 | 74877.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 459.98 | 16829.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- General | 520.33 | 16791.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 90.77 | 4739.42 | 2623.98 | 222392.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 18.27 | 2271.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 22.65 | 1889.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 34.87 | 1202.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 1827.09 | 12134.96 |
Natural Gas | 1788.84 | 4881.68 |
Additional | 0.00 | 0.00 |
Total | 3615.93 | 17016.64 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 103.49 |
Space Heating | 0.00 |
Space Cooling | 466.60 |
Fans (All) | 161.00 |
Service Water Heating | 8.00 |
Receptacle Equipment | 154.36 |
Miscellaneous (All) | 1069.60 |
Subtotal | 1069.60 |
Natural Gas [MJ/m2] | |
Space Heating | 41.33 |
Service Water Heating | 231.28 |
Miscellaneous (All) | 430.28 |
Subtotal | 430.28 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 6.90 |
Space Heating | 2.76 |
Space Cooling | 31.11 |
Fans (All) | 10.73 |
Service Water Heating | 15.95 |
Receptacle Equipment | 20.80 |
Miscellaneous | 11.74 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_KITCHEN | 3061. | 8760. |
LTG_SCH_DINING | 3061. | 8760. |
LTG_SCH_BASEMENT | 2655. | 8760. |
LTG_SCH_LOBBY | 3061. | 8760. |
LTG_SCH_STORAGE | 1339. | 8760. |
LTG_SCH_MECHANIC | 3061. | 8760. |
LTG_SCH_LAUNDRY | 2678. | 8760. |
LTG_SCH_GUESTROOM | 3599. | 8760. |
LTG_SCH_CORRIDOR | 3061. | 8760. |
LTG_SCH_RETAIL | 2678. | 8760. |
WALKIN_OCC_LGHT_SCH_1 | 3061. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
BASEMENT_EQUIP_SCH | 3924. | 8760. |
BLDG_EQUIP_SCH | 3924. | 8760. |
GUESTROOM_EQP_SCH_BASE | 3239. | 8760. |
GUESTROOM_EQP_SCH_ADVA | 2762. | 8760. |
LOBBY_EQP_SCH | 3292. | 8760. |
OFFICE_EQP_SCH | 4941. | 8760. |
EMPLOYEELOUNGE_EQP_SCH | 4044. | 8760. |
LAUNDRYROOM_EQP_ELEC_SCH | 2920. | 2920. |
LAUNDRYROOM_EQP_GAS_SCH | 2920. | 2920. |
MEETINGROOM_EQP_SCH | 1336. | 4745. |
EXERCISEROOM_EQP_SCH | 3832. | 5840. |
KITCHEN_ELEC_EQUIP_SCH | 2172. | 8760. |
KITCHEN_GAS_EQUIP_SCH | 1332. | 8760. |
KITCHEN_EXHAUST_SCH | 6205. | 6205. |
BLDG_ELEVATORS | 2270. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_OCC_SCH | 5026. | 8760. |
GUESTROOM_OCC_SCH | 5515. | 8760. |
LOBBY_OCC_SCH | 2304. | 8760. |
OFFICE_OCC_SCH | 3954. | 8760. |
EMPLOYEELOUNGE_OCC_SCH | 948. | 5475. |
MEETINGROOM_OCC_SCH | 1168. | 4745. |
LAUNDRYROOM_OCC_SCH | 427. | 2920. |
EXERCISEROOM_OCC_SCH | 5292. | 5840. |
INFIL_SCH | 8760. | 8760. |
INFIL_HALF_ON_SCH | 4380. | 8760. |
INFIL_QUARTER_ON_SCH | 2190. | 8760. |
LAUNDRY_SWH_SCH | 2555. | 2555. |
BLDG_SWH_SCH | 3301. | 8760. |
GUESTROOM_SWH_SCH | 2899. | 8760. |
LAUNDRYROOM_SWH_SCH | 2920. | 2920. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
ALWAYS_ON | 8760. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
OCC_GUESTROOM_VENT_CTRL_30MIN | 6570. | 6570. |
OCC_GUESTROOM_VENT_CTRL_20MIN | 6327. | 6327. |
VAC_GUESTROOM_VENTILATION_SCHEDULE | 365. | 365. |
MINOA_MOTORIZEDDAMPER_SCHED | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
ROOM_1_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
FLR_3_DOAS_OAMINOAFRACSCHEDULE | 8760. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 0. | 0. |
LAUNDRY_FLR_1 EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 0. | 0. |
SLIDING_DOORS_VENTILATION_AVAILABILITY_SCH | 3285. | 3285. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
VACGUESTROOM_HTGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 18.89 | 365 | 18.89 | 365 |
VACGUESTROOM_CLGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 23.33 | 365 |
OBCRESET_S_OCCGUESTROOM_HTGSP_SCH_30MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_S_OCCGUESTROOM_CLGSP_SCH_30MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_HTGSP_SCH_30MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_CLGSP_SCH_30MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
HTGSETP_SCH | BASEMENT DUAL SP CONTROL | January | 21.00 | 365 | 21.00 | 365 |
CLGSETP_SCH | BASEMENT DUAL SP CONTROL | July | 24.00 | 365 | 24.00 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:58:20
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Average | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Sum | 192720.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 529331.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 50179.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 59156.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8977.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 5588.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 37203.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 710417.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 2115429.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 100358.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 108269.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 105946.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 2115429.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Average | 288887.05 | 0.00 | 0.00 | 0.00 | 0.00 |
Sum | 6355515.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 8755.50 | 4.50 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 8755.33 | 4.67 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 8740.83 | 19.17 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 8757.67 | 2.33 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 8755.83 | 4.17 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 8754.00 | 6.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 8751.17 | 8.83 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 8752.33 | 7.67 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8751.50 | 8.50 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8740.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 19.17 | 0.00 | 0.00 | 0.00 |
Average | 8757.01 | 2.99 | 0.00 | 0.00 | 0.00 |
Sum | 192654.17 | 65.83 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 529331.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 50179.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 59156.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8977.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 5588.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 37203.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 710417.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 2115429.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 100358.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 108269.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 105946.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 2115429.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Average | 288887.05 | 0.00 | 0.00 | 0.00 | 0.00 |
Sum | 6355515.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:58:20
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:58:20
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2012
For: Environment
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
For: Environment
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 1A
For: Environment
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_FL_MIAMI
For: Environment
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.498403E+11 | 23633.95 | 02-JAN-19:10 | 23.12 | 19.93 | 0.629840E+10 | 3908.60 | 25-JAN-22:10 | 12.70 | 7.25 |
February | 0.428330E+11 | 23184.38 | 16-FEB-19:10 | 23.30 | 19.57 | 0.562558E+10 | 3865.58 | 03-FEB-22:10 | 23.30 | 19.57 |
March | 0.441770E+11 | 22983.63 | 29-MAR-18:20 | 24.80 | 20.45 | 0.618361E+10 | 3800.09 | 01-MAR-22:10 | 24.80 | 20.45 |
April | 0.418398E+11 | 23124.45 | 17-APR-19:10 | 26.83 | 19.37 | 0.594681E+10 | 3759.50 | 18-APR-22:10 | 17.62 | 12.99 |
May | 0.448601E+11 | 23528.64 | 31-MAY-18:50 | 28.30 | 23.96 | 0.616105E+10 | 3782.77 | 26-MAY-22:10 | 28.30 | 23.96 |
June | 0.444324E+11 | 23968.66 | 28-JUN-18:40 | 29.60 | 24.32 | 0.598174E+10 | 3794.14 | 30-JUN-22:10 | 27.45 | 24.25 |
July | 0.483791E+11 | 24888.51 | 27-JUL-18:20 | 31.47 | 25.80 | 0.620443E+10 | 3842.11 | 14-JUL-22:10 | 31.47 | 25.80 |
August | 0.507111E+11 | 25278.77 | 02-AUG-18:10 | 29.90 | 24.73 | 0.630418E+10 | 3887.58 | 25-AUG-22:10 | 27.12 | 24.38 |
September | 0.504234E+11 | 25208.46 | 18-SEP-18:10 | 30.40 | 25.93 | 0.611735E+10 | 3913.45 | 22-SEP-22:10 | 28.30 | 25.74 |
October | 0.523900E+11 | 24955.82 | 05-OCT-18:10 | 28.80 | 23.33 | 0.634038E+10 | 3927.67 | 26-OCT-22:10 | 24.32 | 22.01 |
November | 0.503752E+11 | 24478.59 | 02-NOV-18:10 | 27.12 | 22.55 | 0.614105E+10 | 3925.62 | 10-NOV-23:10 | 22.52 | 20.48 |
December | 0.511901E+11 | 23944.13 | 07-DEC-19:10 | 24.40 | 22.49 | 0.634187E+10 | 3947.76 | 15-DEC-22:10 | 13.72 | 11.89 |
Annual Sum or Average | 0.571451E+12 | 0.736465E+11 | ||||||||
Minimum of Months | 0.418398E+11 | 22983.63 | 23.12 | 19.37 | 0.562558E+10 | 3759.50 | 12.70 | 7.25 | ||
Maximum of Months | 0.523900E+11 | 25278.77 | 31.47 | 25.93 | 0.634187E+10 | 3947.76 | 31.47 | 25.80 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.465022E+10 | 3333.07 | 02-JAN-11:35 | 26.83 | 20.59 | 0.631628E+09 | 403.38 | 13-JAN-22:19 | 24.23 | 21.06 |
February | 0.442074E+10 | 3216.88 | 11-FEB-11:35 | 27.60 | 23.74 | 0.571351E+09 | 390.08 | 09-FEB-22:30 | 27.60 | 23.74 |
March | 0.491198E+10 | 3150.94 | 04-MAR-11:35 | 27.03 | 22.82 | 0.632089E+09 | 396.24 | 27-MAR-21:40 | 24.60 | 21.74 |
April | 0.513727E+10 | 2974.02 | 15-APR-10:35 | 29.27 | 22.89 | 0.611457E+09 | 404.49 | 14-APR-21:40 | 29.27 | 22.89 |
May | 0.563935E+10 | 2886.25 | 22-MAY-18:10 | 30.40 | 23.74 | 0.634265E+09 | 404.85 | 22-MAY-21:49 | 27.30 | 22.27 |
June | 0.571467E+10 | 2975.80 | 11-JUN-10:35 | 30.93 | 23.60 | 0.621781E+09 | 412.31 | 09-JUN-21:00 | 30.93 | 23.60 |
July | 0.612211E+10 | 3123.47 | 29-JUL-17:13 | 34.03 | 24.14 | 0.645286E+09 | 417.83 | 28-JUL-22:10 | 34.03 | 24.14 |
August | 0.599419E+10 | 3099.79 | 19-AUG-10:35 | 31.50 | 24.70 | 0.649100E+09 | 414.51 | 18-AUG-22:10 | 31.50 | 24.70 |
September | 0.603334E+10 | 3317.76 | 24-SEP-10:35 | 30.53 | 25.04 | 0.635530E+09 | 424.59 | 18-SEP-22:10 | 30.53 | 25.04 |
October | 0.617471E+10 | 3354.34 | 07-OCT-10:35 | 31.13 | 24.14 | 0.654702E+09 | 423.35 | 25-OCT-21:40 | 26.30 | 21.54 |
November | 0.539105E+10 | 3526.28 | 08-NOV-11:35 | 27.43 | 21.48 | 0.621765E+09 | 415.70 | 07-NOV-22:40 | 27.43 | 21.48 |
December | 0.486233E+10 | 3453.80 | 09-DEC-11:35 | 27.20 | 22.50 | 0.634856E+09 | 406.20 | 08-DEC-22:30 | 27.20 | 22.50 |
Annual Sum or Average | 0.650520E+11 | 0.754381E+10 | ||||||||
Minimum of Months | 0.442074E+10 | 2886.25 | 26.83 | 20.59 | 0.571351E+09 | 390.08 | 24.23 | 21.06 | ||
Maximum of Months | 0.617471E+10 | 3526.28 | 34.03 | 25.04 | 0.654702E+09 | 424.59 | 34.03 | 25.04 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.391328E+10 | 2132.50 | 02-JAN-19:10 | 23.12 | 19.93 | 0.727771E+09 | 467.90 | 13-JAN-23:10 | 23.90 | 21.21 |
February | 0.366768E+10 | 2137.29 | 11-FEB-19:10 | 23.40 | 21.47 | 0.660678E+09 | 465.09 | 17-FEB-23:10 | 23.90 | 20.81 |
March | 0.414978E+10 | 2212.58 | 13-MAR-18:10 | 27.93 | 22.26 | 0.738354E+09 | 473.89 | 28-MAR-22:10 | 23.80 | 20.10 |
April | 0.425556E+10 | 2292.13 | 17-APR-18:10 | 30.03 | 18.67 | 0.718394E+09 | 480.02 | 14-APR-22:10 | 30.03 | 18.67 |
May | 0.454681E+10 | 2308.51 | 22-MAY-18:10 | 30.40 | 23.74 | 0.747904E+09 | 480.90 | 19-MAY-22:10 | 30.40 | 23.74 |
June | 0.450905E+10 | 2348.05 | 29-JUN-18:10 | 30.00 | 24.76 | 0.729377E+09 | 485.74 | 09-JUN-22:10 | 30.00 | 24.76 |
July | 0.478124E+10 | 2384.21 | 27-JUL-18:10 | 31.83 | 25.86 | 0.753543E+09 | 486.98 | 28-JUL-22:10 | 28.80 | 24.46 |
August | 0.468423E+10 | 2342.66 | 17-AUG-18:10 | 29.82 | 24.66 | 0.754922E+09 | 484.23 | 17-AUG-22:10 | 27.88 | 24.83 |
September | 0.460184E+10 | 2335.10 | 18-SEP-18:10 | 30.40 | 25.93 | 0.729311E+09 | 485.87 | 01-SEP-22:10 | 30.40 | 25.93 |
October | 0.464700E+10 | 2279.37 | 05-OCT-18:10 | 28.80 | 23.33 | 0.748292E+09 | 483.72 | 06-OCT-22:10 | 26.70 | 23.84 |
November | 0.421658E+10 | 2215.54 | 08-NOV-19:10 | 26.10 | 22.26 | 0.714246E+09 | 476.59 | 07-NOV-23:10 | 26.10 | 22.26 |
December | 0.404951E+10 | 2147.11 | 09-DEC-19:10 | 25.00 | 22.31 | 0.730839E+09 | 473.10 | 08-DEC-23:10 | 25.00 | 22.31 |
Annual Sum or Average | 0.520225E+11 | 0.875363E+10 | ||||||||
Minimum of Months | 0.366768E+10 | 2132.50 | 23.12 | 18.67 | 0.660678E+09 | 465.09 | 23.80 | 18.67 | ||
Maximum of Months | 0.478124E+10 | 2384.21 | 31.83 | 25.93 | 0.754922E+09 | 486.98 | 30.40 | 25.93 |
Report: ZoneCoolingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.331704E+10 | 2168.46 | 02-JAN-19:50 | 22.38 | 19.69 | 0.152011E+09 | 93.47 | 06-JAN-22:10 | 24.32 | 22.14 |
February | 0.326363E+10 | 2188.34 | 16-FEB-19:15 | 23.30 | 19.57 | 0.137696E+09 | 94.12 | 17-FEB-22:10 | 23.90 | 20.81 |
March | 0.381026E+10 | 2289.15 | 27-MAR-18:20 | 25.60 | 21.37 | 0.153267E+09 | 94.44 | 28-MAR-21:10 | 24.32 | 20.85 |
April | 0.422360E+10 | 2444.62 | 17-APR-18:10 | 30.03 | 18.67 | 0.148487E+09 | 96.10 | 14-APR-22:10 | 30.03 | 18.67 |
May | 0.489178E+10 | 2487.61 | 22-MAY-18:10 | 30.40 | 23.74 | 0.155198E+09 | 97.45 | 31-MAY-22:10 | 26.98 | 24.25 |
June | 0.504815E+10 | 2586.85 | 11-JUN-10:35 | 30.93 | 23.60 | 0.152498E+09 | 99.15 | 29-JUN-22:10 | 28.90 | 24.77 |
July | 0.532645E+10 | 2616.72 | 29-JUL-10:35 | 32.07 | 25.98 | 0.157501E+09 | 99.51 | 28-JUL-22:10 | 32.07 | 25.98 |
August | 0.507500E+10 | 2567.04 | 20-AUG-10:35 | 31.13 | 25.97 | 0.156758E+09 | 98.73 | 18-AUG-22:10 | 31.13 | 25.97 |
September | 0.495291E+10 | 2494.10 | 18-SEP-18:10 | 30.40 | 25.93 | 0.151244E+09 | 98.62 | 22-SEP-22:10 | 28.30 | 25.74 |
October | 0.478395E+10 | 2418.43 | 05-OCT-18:10 | 28.80 | 23.33 | 0.154275E+09 | 96.86 | 03-OCT-22:10 | 28.80 | 23.33 |
November | 0.411157E+10 | 2328.93 | 22-NOV-19:03 | 26.70 | 23.84 | 0.148110E+09 | 95.70 | 03-NOV-22:10 | 26.70 | 23.84 |
December | 0.358878E+10 | 2239.14 | 07-DEC-19:20 | 24.40 | 22.49 | 0.152243E+09 | 94.46 | 08-DEC-22:10 | 23.98 | 22.48 |
Annual Sum or Average | 0.523931E+11 | 0.181929E+10 | ||||||||
Minimum of Months | 0.326363E+10 | 2168.46 | 22.38 | 18.67 | 0.137696E+09 | 93.47 | 23.90 | 18.67 | ||
Maximum of Months | 0.532645E+10 | 2616.72 | 32.07 | 25.98 | 0.157501E+09 | 99.51 | 32.07 | 25.98 |
Report: ZoneCoolingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.143313E+10 | 983.57 | 13-JAN-21:00 | 24.40 | 20.99 | 0.116715E+09 | 69.76 | 13-JAN-23:10 | 23.90 | 21.21 |
February | 0.145571E+10 | 991.37 | 17-FEB-20:20 | 23.90 | 20.81 | 0.105543E+09 | 70.20 | 17-FEB-23:10 | 23.90 | 20.81 |
March | 0.172626E+10 | 1037.18 | 30-MAR-20:00 | 23.90 | 19.84 | 0.117365E+09 | 70.41 | 28-MAR-22:10 | 23.90 | 19.84 |
April | 0.199076E+10 | 1112.03 | 17-APR-19:10 | 26.83 | 19.37 | 0.113442E+09 | 71.64 | 14-APR-22:10 | 26.83 | 19.37 |
May | 0.237734E+10 | 1189.99 | 31-MAY-18:15 | 28.30 | 23.96 | 0.118247E+09 | 72.60 | 31-MAY-22:10 | 26.98 | 24.25 |
June | 0.248039E+10 | 1293.28 | 11-JUN-10:35 | 30.93 | 23.60 | 0.116092E+09 | 73.90 | 29-JUN-22:10 | 28.90 | 24.77 |
July | 0.262775E+10 | 1313.92 | 29-JUL-10:35 | 32.07 | 25.98 | 0.119843E+09 | 74.18 | 28-JUL-22:10 | 32.07 | 25.98 |
August | 0.248858E+10 | 1294.34 | 19-AUG-10:35 | 31.50 | 24.70 | 0.119479E+09 | 73.66 | 18-AUG-22:10 | 31.50 | 24.70 |
September | 0.243129E+10 | 1282.11 | 24-SEP-10:35 | 30.53 | 25.04 | 0.115218E+09 | 73.68 | 22-SEP-22:10 | 30.53 | 25.04 |
October | 0.232443E+10 | 1134.02 | 05-OCT-19:10 | 28.22 | 23.14 | 0.117661E+09 | 72.36 | 03-OCT-22:10 | 28.22 | 23.14 |
November | 0.192942E+10 | 1079.02 | 22-NOV-21:00 | 26.70 | 23.84 | 0.113226E+09 | 71.57 | 03-NOV-22:10 | 26.70 | 23.84 |
December | 0.159335E+10 | 1022.97 | 07-DEC-21:00 | 23.90 | 22.40 | 0.116766E+09 | 70.57 | 08-DEC-23:10 | 24.50 | 22.98 |
Annual Sum or Average | 0.248584E+11 | 0.138960E+10 | ||||||||
Minimum of Months | 0.143313E+10 | 983.57 | 23.90 | 19.37 | 0.105543E+09 | 69.76 | 23.90 | 19.37 | ||
Maximum of Months | 0.262775E+10 | 1313.92 | 32.07 | 25.98 | 0.119843E+09 | 74.18 | 32.07 | 25.98 |
Report: ZoneCoolingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.517195E+11 | 36756.05 | 02-JAN-21:00 | 22.20 | 19.62 | 0.508177E+09 | 382.20 | 10-JAN-22:10 | 17.62 | 14.98 |
February | 0.471285E+11 | 36726.14 | 16-FEB-21:00 | 23.90 | 20.12 | 0.459214E+09 | 381.91 | 24-FEB-22:10 | 16.02 | 11.81 |
March | 0.527021E+11 | 37145.35 | 27-MAR-20:00 | 24.40 | 20.99 | 0.510719E+09 | 381.90 | 14-MAR-21:10 | 24.40 | 20.99 |
April | 0.517242E+11 | 37390.22 | 17-APR-20:00 | 25.00 | 18.53 | 0.491238E+09 | 381.86 | 18-APR-21:10 | 18.72 | 13.36 |
May | 0.541911E+11 | 37723.94 | 31-MAY-20:00 | 27.80 | 24.12 | 0.507938E+09 | 381.80 | 26-MAY-21:10 | 27.80 | 24.12 |
June | 0.530264E+11 | 37825.24 | 08-JUN-20:00 | 28.90 | 24.83 | 0.492281E+09 | 381.57 | 13-JUN-21:10 | 26.10 | 22.31 |
July | 0.548645E+11 | 37904.85 | 27-JUL-20:00 | 28.90 | 25.60 | 0.505199E+09 | 381.73 | 14-JUL-21:10 | 28.90 | 25.60 |
August | 0.544807E+11 | 37806.30 | 31-AUG-20:00 | 27.80 | 24.58 | 0.508984E+09 | 381.58 | 11-AUG-21:10 | 27.80 | 24.58 |
September | 0.527797E+11 | 37764.94 | 21-SEP-20:00 | 28.90 | 24.82 | 0.490316E+09 | 381.77 | 05-SEP-21:10 | 28.90 | 24.82 |
October | 0.539069E+11 | 37529.17 | 05-OCT-20:00 | 27.80 | 23.03 | 0.506842E+09 | 381.82 | 17-OCT-21:10 | 24.40 | 18.14 |
November | 0.513508E+11 | 37207.32 | 02-NOV-20:00 | 26.70 | 22.81 | 0.490921E+09 | 381.88 | 14-NOV-22:10 | 18.30 | 14.23 |
December | 0.518350E+11 | 36829.09 | 06-DEC-21:00 | 24.40 | 22.09 | 0.507545E+09 | 381.89 | 19-DEC-22:10 | 16.02 | 12.32 |
Annual Sum or Average | 0.629709E+12 | 0.597937E+10 | ||||||||
Minimum of Months | 0.471285E+11 | 36726.14 | 22.20 | 18.53 | 0.459214E+09 | 381.57 | 16.02 | 11.81 | ||
Maximum of Months | 0.548645E+11 | 37904.85 | 28.90 | 25.60 | 0.510719E+09 | 382.20 | 28.90 | 25.60 |
Report: ZoneCoolingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.254724E+11 | 13713.20 | 15-JAN-11:35 | 24.43 | 17.04 | 0.864090E+10 | 5766.85 | 13-JAN-22:40 | 24.43 | 17.04 |
February | 0.233515E+11 | 13613.36 | 11-FEB-11:35 | 27.60 | 23.74 | 0.784585E+10 | 5647.35 | 17-FEB-22:40 | 23.90 | 20.81 |
March | 0.255453E+11 | 13396.57 | 04-MAR-11:35 | 27.03 | 22.82 | 0.873123E+10 | 5671.22 | 13-MAR-22:10 | 24.90 | 22.35 |
April | 0.253636E+11 | 12786.19 | 17-APR-18:10 | 30.03 | 18.67 | 0.846560E+10 | 5710.17 | 14-APR-21:40 | 30.03 | 18.67 |
May | 0.267903E+11 | 12842.85 | 22-MAY-18:10 | 30.40 | 23.74 | 0.883624E+10 | 5745.17 | 22-MAY-22:10 | 26.93 | 22.26 |
June | 0.266047E+11 | 12992.97 | 29-JUN-18:10 | 30.00 | 24.76 | 0.866699E+10 | 5791.92 | 02-JUN-22:10 | 30.00 | 24.76 |
July | 0.280782E+11 | 13326.03 | 27-JUL-18:10 | 31.83 | 25.86 | 0.891706E+10 | 5829.10 | 28-JUL-22:10 | 28.80 | 24.46 |
August | 0.278690E+11 | 13004.92 | 02-AUG-18:10 | 29.90 | 24.73 | 0.899410E+10 | 5818.89 | 18-AUG-22:10 | 28.90 | 24.83 |
September | 0.277996E+11 | 13867.31 | 24-SEP-10:35 | 30.53 | 25.04 | 0.874919E+10 | 5918.51 | 08-SEP-22:10 | 30.53 | 25.04 |
October | 0.287012E+11 | 13955.98 | 07-OCT-10:35 | 31.13 | 24.14 | 0.904552E+10 | 5907.78 | 25-OCT-21:40 | 26.30 | 21.54 |
November | 0.265069E+11 | 14288.84 | 08-NOV-11:35 | 27.43 | 21.48 | 0.859068E+10 | 5848.95 | 07-NOV-22:40 | 27.43 | 21.48 |
December | 0.258352E+11 | 14446.24 | 09-DEC-11:35 | 27.20 | 22.50 | 0.869975E+10 | 5775.20 | 08-DEC-22:40 | 27.20 | 22.50 |
Annual Sum or Average | 0.317918E+12 | 0.104183E+12 | ||||||||
Minimum of Months | 0.233515E+11 | 12786.19 | 24.43 | 17.04 | 0.784585E+10 | 5647.35 | 23.90 | 17.04 | ||
Maximum of Months | 0.287012E+11 | 14446.24 | 31.83 | 25.86 | 0.904552E+10 | 5918.51 | 30.53 | 25.04 |
Report: ZoneCoolingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.842362E+11 | 41098.71 | 02-JAN-19:10 | 23.12 | 19.93 | 0.253423E+11 | 16551.05 | 13-JAN-23:10 | 23.90 | 21.21 |
February | 0.774386E+11 | 40953.48 | 11-FEB-19:10 | 23.40 | 21.47 | 0.230240E+11 | 16495.09 | 17-FEB-23:10 | 23.90 | 20.81 |
March | 0.857883E+11 | 42336.72 | 13-MAR-18:10 | 27.93 | 22.26 | 0.257116E+11 | 16526.60 | 28-MAR-22:10 | 23.80 | 20.10 |
April | 0.857087E+11 | 43779.35 | 17-APR-18:10 | 30.03 | 18.67 | 0.249775E+11 | 16696.58 | 14-APR-22:10 | 30.03 | 18.67 |
May | 0.911861E+11 | 44232.74 | 22-MAY-18:10 | 30.40 | 23.74 | 0.260725E+11 | 16752.13 | 22-MAY-22:10 | 26.93 | 22.26 |
June | 0.905825E+11 | 44792.13 | 29-JUN-18:10 | 30.00 | 24.76 | 0.254872E+11 | 16923.98 | 09-JUN-22:10 | 30.00 | 24.76 |
July | 0.949746E+11 | 45394.92 | 27-JUL-18:10 | 31.83 | 25.86 | 0.262289E+11 | 16981.91 | 28-JUL-22:10 | 28.80 | 24.46 |
August | 0.937925E+11 | 44668.12 | 02-AUG-18:10 | 29.90 | 24.73 | 0.263358E+11 | 16942.32 | 18-AUG-22:10 | 28.90 | 24.83 |
September | 0.922545E+11 | 44809.15 | 24-SEP-10:35 | 30.53 | 25.04 | 0.254500E+11 | 17026.34 | 22-SEP-22:10 | 30.53 | 25.04 |
October | 0.941099E+11 | 43584.88 | 05-OCT-18:10 | 28.80 | 23.33 | 0.261582E+11 | 16874.52 | 06-OCT-22:10 | 26.70 | 23.84 |
November | 0.873549E+11 | 42600.44 | 19-NOV-11:35 | 26.70 | 21.43 | 0.250032E+11 | 16796.98 | 03-NOV-22:10 | 26.70 | 21.43 |
December | 0.857761E+11 | 43417.94 | 09-DEC-11:35 | 27.20 | 22.50 | 0.254903E+11 | 16675.54 | 08-DEC-23:10 | 27.20 | 22.50 |
Annual Sum or Average | 0.106320E+13 | 0.305282E+12 | ||||||||
Minimum of Months | 0.774386E+11 | 40953.48 | 23.12 | 18.67 | 0.230240E+11 | 16495.09 | 23.80 | 18.67 | ||
Maximum of Months | 0.949746E+11 | 45394.92 | 31.83 | 25.86 | 0.263358E+11 | 17026.34 | 30.53 | 25.04 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.136024E+10 | 3278.88 | 26-JAN-16:02 | 20.50 | 11.94 | 98228917.33 | 56.70 | 13-JAN-22:40 | 20.50 | 11.94 |
February | 0.149846E+10 | 3301.31 | 24-FEB-16:02 | 25.00 | 13.11 | 88931188.05 | 56.70 | 22-FEB-22:10 | 25.00 | 13.11 |
March | 0.186010E+10 | 3235.14 | 15-MAR-15:01 | 17.30 | 8.90 | 98652830.24 | 56.70 | 31-MAR-22:10 | 23.05 | 18.37 |
April | 0.225081E+10 | 3217.13 | 15-APR-15:02 | 31.20 | 22.93 | 95696040.22 | 56.70 | 15-APR-23:40 | 22.97 | 20.90 |
May | 0.257865E+10 | 3220.81 | 16-MAY-15:02 | 30.40 | 21.78 | 99067533.97 | 56.70 | 19-MAY-00:10 | 25.50 | 22.72 |
June | 0.262556E+10 | 3182.98 | 10-JUN-15:02 | 31.70 | 24.22 | 95937857.78 | 56.70 | 17-JUN-00:00 | 27.20 | 22.19 |
July | 0.292568E+10 | 3229.87 | 28-JUL-15:02 | 35.00 | 25.20 | 99075368.67 | 56.70 | 01-JUL-23:00 | 35.00 | 25.20 |
August | 0.280078E+10 | 3224.39 | 31-AUG-15:02 | 32.12 | 24.95 | 99137611.61 | 56.70 | 23-AUG-22:40 | 32.12 | 24.95 |
September | 0.273142E+10 | 3230.81 | 17-SEP-15:02 | 31.10 | 24.65 | 95862788.06 | 56.70 | 01-SEP-01:39 | 31.10 | 24.65 |
October | 0.264444E+10 | 3202.25 | 06-OCT-15:02 | 29.32 | 23.78 | 99044141.91 | 56.70 | 19-OCT-22:40 | 23.50 | 19.52 |
November | 0.200445E+10 | 3172.94 | 17-NOV-16:02 | 29.13 | 21.96 | 95621202.72 | 56.70 | 30-NOV-22:40 | 25.03 | 22.28 |
December | 0.155374E+10 | 3202.74 | 06-DEC-16:02 | 26.02 | 22.41 | 98266053.14 | 56.70 | 05-DEC-22:10 | 26.02 | 22.41 |
Annual Sum or Average | 0.268343E+11 | 0.116352E+10 | ||||||||
Minimum of Months | 0.136024E+10 | 3172.94 | 17.30 | 8.90 | 88931188.05 | 56.70 | 20.50 | 11.94 | ||
Maximum of Months | 0.292568E+10 | 3301.31 | 35.00 | 25.20 | 99137611.61 | 56.70 | 35.00 | 25.20 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.975476E+09 | 3237.51 | 26-JAN-16:02 | 20.50 | 11.94 | 97502772.93 | 56.69 | 27-JAN-22:10 | 19.40 | 15.40 |
February | 0.120189E+10 | 3285.56 | 24-FEB-16:02 | 25.00 | 13.11 | 88534484.15 | 56.69 | 16-FEB-22:10 | 25.00 | 13.11 |
March | 0.163135E+10 | 3216.86 | 15-MAR-15:01 | 17.30 | 8.90 | 98389943.61 | 56.70 | 30-MAR-22:10 | 23.80 | 20.03 |
April | 0.212975E+10 | 3252.36 | 15-APR-18:02 | 29.82 | 21.94 | 95658846.73 | 56.70 | 04-APR-21:49 | 29.82 | 21.94 |
May | 0.257697E+10 | 3248.03 | 20-MAY-15:02 | 30.00 | 21.38 | 99075954.30 | 56.70 | 17-MAY-00:40 | 30.00 | 21.38 |
June | 0.266574E+10 | 3212.71 | 10-JUN-15:02 | 31.70 | 24.22 | 95956051.13 | 56.70 | 09-JUN-21:10 | 31.70 | 24.22 |
July | 0.295135E+10 | 3262.61 | 28-JUL-15:02 | 35.00 | 25.20 | 99086333.07 | 56.70 | 23-JUL-00:20 | 35.00 | 25.20 |
August | 0.274851E+10 | 3205.15 | 19-AUG-15:02 | 31.70 | 24.44 | 99135096.44 | 56.70 | 18-AUG-21:49 | 31.70 | 24.44 |
September | 0.256490E+10 | 3195.62 | 30-SEP-15:02 | 31.10 | 24.59 | 95838733.35 | 56.70 | 17-SEP-00:10 | 31.10 | 24.59 |
October | 0.232988E+10 | 3202.84 | 18-OCT-15:02 | 27.20 | 19.36 | 98969402.37 | 56.70 | 19-OCT-21:00 | 23.90 | 19.41 |
November | 0.166439E+10 | 3163.54 | 06-NOV-16:02 | 27.80 | 20.07 | 95355950.37 | 56.70 | 07-NOV-22:40 | 24.40 | 22.09 |
December | 0.118906E+10 | 3135.74 | 04-DEC-16:02 | 25.50 | 18.37 | 97701972.48 | 56.69 | 06-DEC-22:10 | 23.90 | 22.40 |
Annual Sum or Average | 0.246293E+11 | 0.116121E+10 | ||||||||
Minimum of Months | 0.975476E+09 | 3135.74 | 17.30 | 8.90 | 88534484.15 | 56.69 | 19.40 | 13.11 | ||
Maximum of Months | 0.295135E+10 | 3285.56 | 35.00 | 25.20 | 99135096.44 | 56.70 | 35.00 | 25.20 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.816848E+09 | 746.42 | 02-JAN-14:30 | 28.90 | 24.11 | 0.00 | 0.00 | 01-JAN-00:10 | 28.90 | 24.11 |
February | 0.745103E+09 | 683.69 | 11-FEB-14:30 | 28.85 | 24.07 | 0.00 | 0.00 | 01-FEB-00:10 | 28.85 | 24.07 |
March | 0.778612E+09 | 569.07 | 02-MAR-14:30 | 25.00 | 17.17 | 0.00 | 0.00 | 01-MAR-00:10 | 25.00 | 17.17 |
April | 0.803100E+09 | 523.51 | 15-APR-19:10 | 28.53 | 21.74 | 0.00 | 0.00 | 01-APR-00:10 | 28.53 | 21.74 |
May | 0.876933E+09 | 507.78 | 22-MAY-20:20 | 28.13 | 22.80 | 0.00 | 0.00 | 01-MAY-00:10 | 28.13 | 22.80 |
June | 0.902508E+09 | 532.63 | 03-JUN-21:00 | 29.40 | 24.47 | 0.00 | 0.00 | 01-JUN-00:10 | 29.40 | 24.47 |
July | 0.978363E+09 | 567.35 | 29-JUL-19:10 | 31.55 | 24.08 | 0.00 | 0.00 | 01-JUL-00:10 | 31.55 | 24.08 |
August | 0.975711E+09 | 551.14 | 20-AUG-20:03 | 28.80 | 24.73 | 0.00 | 0.00 | 01-AUG-00:10 | 28.80 | 24.73 |
September | 0.104153E+10 | 654.23 | 30-SEP-13:30 | 30.85 | 24.73 | 0.00 | 0.00 | 01-SEP-00:10 | 30.85 | 24.73 |
October | 0.110823E+10 | 714.26 | 25-OCT-12:40 | 30.00 | 22.13 | 0.00 | 0.00 | 01-OCT-00:10 | 30.00 | 22.13 |
November | 0.960684E+09 | 747.21 | 07-NOV-13:40 | 28.13 | 20.93 | 0.00 | 0.00 | 01-NOV-00:10 | 28.13 | 20.93 |
December | 0.846727E+09 | 755.58 | 03-DEC-14:00 | 24.40 | 18.35 | 0.00 | 0.00 | 01-DEC-00:10 | 24.40 | 18.35 |
Annual Sum or Average | 0.108344E+11 | 0.00 | ||||||||
Minimum of Months | 0.745103E+09 | 507.78 | 24.40 | 17.17 | 0.00 | 0.00 | 24.40 | 17.17 | ||
Maximum of Months | 0.110823E+10 | 755.58 | 31.55 | 24.73 | 0.00 | 0.00 | 31.55 | 24.73 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.679352E+09 | 1129.77 | 16-JAN-16:02 | 21.60 | 14.75 | 97119184.51 | 56.69 | 18-JAN-22:40 | 21.87 | 16.72 |
February | 0.705468E+09 | 1188.46 | 24-FEB-19:01 | 21.52 | 12.20 | 88050769.13 | 56.69 | 22-FEB-23:10 | 21.52 | 12.20 |
March | 0.852104E+09 | 1185.13 | 14-MAR-18:02 | 24.13 | 14.61 | 97785942.90 | 56.69 | 27-MAR-21:10 | 24.90 | 21.81 |
April | 0.984449E+09 | 1198.42 | 17-APR-18:02 | 30.03 | 18.67 | 95112382.92 | 56.69 | 20-APR-22:00 | 22.20 | 16.64 |
May | 0.117084E+10 | 1183.38 | 20-MAY-18:02 | 28.03 | 21.49 | 98749260.58 | 56.70 | 19-MAY-22:10 | 28.03 | 21.49 |
June | 0.122418E+10 | 1180.01 | 14-JUN-18:02 | 29.32 | 23.40 | 95703939.07 | 56.69 | 13-JUN-21:40 | 29.32 | 23.40 |
July | 0.129227E+10 | 1188.42 | 29-JUL-18:02 | 33.12 | 24.14 | 98854370.55 | 56.69 | 05-JUL-21:40 | 33.12 | 24.14 |
August | 0.121591E+10 | 1172.18 | 19-AUG-18:02 | 29.40 | 24.22 | 98815181.16 | 56.69 | 11-AUG-21:49 | 29.40 | 24.22 |
September | 0.115722E+10 | 1166.52 | 01-SEP-18:02 | 29.90 | 23.26 | 95526859.49 | 56.70 | 12-SEP-21:49 | 26.20 | 23.25 |
October | 0.108144E+10 | 1184.47 | 17-OCT-18:02 | 25.50 | 18.09 | 98520041.31 | 56.70 | 17-OCT-21:10 | 24.40 | 18.14 |
November | 0.891157E+09 | 1177.48 | 20-NOV-19:02 | 26.02 | 20.73 | 94838313.67 | 56.69 | 20-NOV-22:10 | 25.60 | 21.07 |
December | 0.737431E+09 | 1154.06 | 09-DEC-19:02 | 25.00 | 22.31 | 97287878.90 | 56.69 | 18-DEC-22:49 | 19.40 | 17.94 |
Annual Sum or Average | 0.119918E+11 | 0.115636E+10 | ||||||||
Minimum of Months | 0.679352E+09 | 1129.77 | 21.52 | 12.20 | 88050769.13 | 56.69 | 19.40 | 12.20 | ||
Maximum of Months | 0.129227E+10 | 1198.42 | 33.12 | 24.22 | 98854370.55 | 56.70 | 33.12 | 24.22 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.140724E+10 | 2952.88 | 26-JAN-16:02 | 20.50 | 11.94 | 98465061.11 | 56.69 | 02-JAN-22:40 | 20.50 | 11.94 |
February | 0.149567E+10 | 2976.13 | 24-FEB-19:01 | 21.52 | 12.20 | 89133763.56 | 56.69 | 22-FEB-22:10 | 21.52 | 12.20 |
March | 0.182545E+10 | 2936.42 | 20-MAR-15:01 | 19.40 | 10.17 | 98906276.48 | 56.69 | 27-MAR-22:40 | 24.07 | 21.37 |
April | 0.222761E+10 | 2890.40 | 16-APR-15:02 | 31.52 | 21.13 | 95857274.53 | 56.70 | 15-APR-23:49 | 31.52 | 21.13 |
May | 0.258183E+10 | 2859.58 | 20-MAY-15:02 | 30.00 | 21.38 | 99150660.22 | 56.69 | 20-MAY-00:40 | 30.00 | 21.38 |
June | 0.275882E+10 | 2860.88 | 01-JUN-15:02 | 30.00 | 23.17 | 96010037.56 | 56.70 | 02-JUN-21:10 | 28.90 | 24.83 |
July | 0.300733E+10 | 2948.35 | 29-JUL-15:02 | 35.10 | 24.20 | 99126592.62 | 56.70 | 25-JUL-21:10 | 35.10 | 24.20 |
August | 0.280337E+10 | 2869.07 | 31-AUG-15:02 | 32.12 | 24.95 | 99182171.72 | 56.70 | 18-AUG-21:10 | 32.12 | 24.95 |
September | 0.282276E+10 | 2876.42 | 30-SEP-15:02 | 31.10 | 24.59 | 95928167.56 | 56.70 | 01-SEP-21:10 | 31.10 | 24.59 |
October | 0.267655E+10 | 2946.57 | 25-OCT-15:02 | 29.22 | 22.14 | 99117624.99 | 56.70 | 20-OCT-23:40 | 29.22 | 22.14 |
November | 0.201399E+10 | 2861.98 | 14-NOV-16:02 | 23.30 | 15.73 | 95742746.85 | 56.70 | 01-NOV-21:49 | 23.30 | 15.73 |
December | 0.146264E+10 | 2868.86 | 04-DEC-16:02 | 25.50 | 18.37 | 98315494.73 | 56.69 | 01-DEC-22:10 | 25.50 | 18.37 |
Annual Sum or Average | 0.270833E+11 | 0.116494E+10 | ||||||||
Minimum of Months | 0.140724E+10 | 2859.58 | 19.40 | 10.17 | 89133763.56 | 56.69 | 20.50 | 11.94 | ||
Maximum of Months | 0.300733E+10 | 2976.13 | 35.10 | 24.95 | 99182171.72 | 56.70 | 35.10 | 24.95 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.102017E+10 | 2758.50 | 15-JAN-16:02 | 24.72 | 16.69 | 97766699.65 | 56.69 | 13-JAN-22:10 | 24.72 | 16.69 |
February | 0.118876E+10 | 2974.11 | 22-FEB-16:02 | 27.43 | 14.84 | 88825499.61 | 56.69 | 21-FEB-23:10 | 27.43 | 14.84 |
March | 0.158922E+10 | 2852.41 | 01-MAR-16:02 | 24.90 | 15.69 | 98692122.20 | 56.70 | 28-MAR-21:49 | 23.98 | 20.27 |
April | 0.210387E+10 | 2953.08 | 16-APR-15:02 | 31.52 | 21.13 | 95842174.65 | 56.70 | 04-APR-21:00 | 31.52 | 21.13 |
May | 0.258000E+10 | 2878.67 | 20-MAY-08:62 | 27.88 | 22.09 | 99152652.54 | 56.70 | 02-MAY-22:00 | 27.88 | 22.09 |
June | 0.279909E+10 | 2882.64 | 01-JUN-15:02 | 30.00 | 23.17 | 96012305.37 | 56.70 | 02-JUN-21:10 | 28.90 | 24.83 |
July | 0.303301E+10 | 2976.32 | 29-JUL-15:02 | 35.10 | 24.20 | 99128216.98 | 56.70 | 25-JUL-21:10 | 35.10 | 24.20 |
August | 0.275055E+10 | 2854.74 | 19-AUG-15:02 | 31.70 | 24.44 | 99180801.53 | 56.70 | 02-AUG-21:10 | 31.70 | 24.44 |
September | 0.265398E+10 | 2841.01 | 13-SEP-15:02 | 31.32 | 24.14 | 95921394.42 | 56.70 | 08-SEP-21:10 | 31.32 | 24.14 |
October | 0.235607E+10 | 2814.80 | 17-OCT-18:02 | 25.50 | 18.09 | 99087161.63 | 56.69 | 13-OCT-21:40 | 25.50 | 18.09 |
November | 0.166821E+10 | 2817.81 | 14-NOV-16:02 | 23.30 | 15.73 | 95537683.37 | 56.70 | 20-NOV-23:10 | 25.60 | 21.12 |
December | 0.110126E+10 | 2768.21 | 03-DEC-19:02 | 21.60 | 15.54 | 97668404.41 | 56.69 | 06-DEC-22:10 | 23.90 | 22.40 |
Annual Sum or Average | 0.248442E+11 | 0.116282E+10 | ||||||||
Minimum of Months | 0.102017E+10 | 2758.50 | 21.60 | 14.84 | 88825499.61 | 56.69 | 23.90 | 14.84 | ||
Maximum of Months | 0.303301E+10 | 2976.32 | 35.10 | 24.44 | 99180801.53 | 56.70 | 35.10 | 24.83 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.532378E+10 | 2793.51 | 01-JAN-11:35 | 26.30 | 21.34 | 0.124836E+10 | 792.64 | 03-JAN-22:40 | 21.87 | 20.31 |
February | 0.490945E+10 | 2758.98 | 11-FEB-11:35 | 27.60 | 23.74 | 0.113924E+10 | 782.84 | 17-FEB-23:10 | 23.90 | 20.81 |
March | 0.555903E+10 | 2767.13 | 04-MAR-11:35 | 27.03 | 22.82 | 0.127734E+10 | 793.08 | 30-MAR-22:10 | 23.80 | 20.03 |
April | 0.578309E+10 | 2970.30 | 15-APR-10:35 | 29.27 | 22.89 | 0.126827E+10 | 811.40 | 14-APR-21:49 | 29.27 | 22.89 |
May | 0.620770E+10 | 2987.72 | 20-MAY-10:35 | 29.23 | 21.81 | 0.133682E+10 | 818.73 | 22-MAY-22:10 | 26.93 | 22.26 |
June | 0.623179E+10 | 3094.30 | 11-JUN-10:35 | 30.93 | 23.60 | 0.132234E+10 | 832.14 | 29-JUN-22:10 | 28.90 | 24.77 |
July | 0.656798E+10 | 3152.16 | 30-JUL-10:35 | 31.83 | 24.36 | 0.137186E+10 | 836.84 | 28-JUL-22:10 | 31.83 | 24.36 |
August | 0.644841E+10 | 3117.20 | 19-AUG-10:35 | 31.50 | 24.70 | 0.137082E+10 | 837.08 | 21-AUG-21:00 | 27.80 | 24.87 |
September | 0.629199E+10 | 3151.62 | 24-SEP-10:35 | 30.53 | 25.04 | 0.132815E+10 | 843.02 | 22-SEP-22:10 | 30.53 | 25.04 |
October | 0.636304E+10 | 3084.88 | 07-OCT-10:35 | 31.13 | 24.14 | 0.136050E+10 | 828.81 | 25-OCT-21:49 | 26.20 | 21.68 |
November | 0.574420E+10 | 2887.13 | 08-NOV-11:35 | 27.43 | 21.48 | 0.126884E+10 | 815.29 | 10-NOV-22:49 | 22.88 | 20.65 |
December | 0.541054E+10 | 2905.50 | 09-DEC-11:35 | 27.20 | 22.50 | 0.126232E+10 | 803.41 | 08-DEC-23:10 | 27.20 | 22.50 |
Annual Sum or Average | 0.708410E+11 | 0.155549E+11 | ||||||||
Minimum of Months | 0.490945E+10 | 2758.98 | 26.30 | 21.34 | 0.113924E+10 | 782.84 | 21.87 | 20.03 | ||
Maximum of Months | 0.656798E+10 | 3152.16 | 31.83 | 25.04 | 0.137186E+10 | 843.02 | 31.83 | 25.04 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.139721E+10 | 3486.54 | 26-JAN-16:02 | 20.50 | 11.94 | 98226706.66 | 56.70 | 13-JAN-22:30 | 20.50 | 11.94 |
February | 0.158839E+10 | 3505.72 | 24-FEB-16:02 | 25.00 | 13.11 | 88928937.56 | 56.70 | 27-FEB-22:10 | 21.52 | 15.05 |
March | 0.200279E+10 | 3427.73 | 15-MAR-15:01 | 17.30 | 8.90 | 98665977.45 | 56.70 | 31-MAR-21:49 | 23.13 | 18.35 |
April | 0.247653E+10 | 3435.09 | 14-APR-15:02 | 30.40 | 24.46 | 95712002.00 | 56.70 | 03-APR-22:10 | 30.40 | 24.46 |
May | 0.286444E+10 | 3426.50 | 31-MAY-15:02 | 30.82 | 24.59 | 99093954.33 | 56.70 | 21-MAY-00:30 | 30.82 | 24.59 |
June | 0.292480E+10 | 3439.96 | 28-JUN-15:02 | 30.50 | 24.49 | 95959478.16 | 56.70 | 09-JUN-21:10 | 30.50 | 24.49 |
July | 0.326586E+10 | 3442.05 | 20-JUL-15:02 | 31.10 | 24.66 | 99089524.65 | 56.70 | 28-JUL-21:10 | 29.32 | 24.20 |
August | 0.309763E+10 | 3440.26 | 21-AUG-15:02 | 30.37 | 25.25 | 99153104.85 | 56.70 | 31-AUG-00:10 | 26.60 | 23.34 |
September | 0.300094E+10 | 3422.14 | 04-SEP-15:02 | 30.50 | 24.31 | 95869212.91 | 56.70 | 08-SEP-21:10 | 29.90 | 24.64 |
October | 0.285796E+10 | 3431.19 | 22-OCT-15:02 | 29.22 | 23.41 | 99043030.81 | 56.70 | 18-OCT-22:00 | 29.22 | 23.41 |
November | 0.213415E+10 | 3433.91 | 07-NOV-16:02 | 28.22 | 22.20 | 95615559.24 | 56.70 | 10-NOV-22:49 | 22.88 | 20.65 |
December | 0.161978E+10 | 3392.27 | 05-DEC-16:02 | 25.40 | 20.99 | 98245598.06 | 56.70 | 06-DEC-22:00 | 23.90 | 22.40 |
Annual Sum or Average | 0.292305E+11 | 0.116360E+10 | ||||||||
Minimum of Months | 0.139721E+10 | 3392.27 | 17.30 | 8.90 | 88928937.56 | 56.70 | 20.50 | 11.94 | ||
Maximum of Months | 0.326586E+10 | 3505.72 | 31.10 | 25.25 | 99153104.85 | 56.70 | 30.82 | 24.64 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.988357E+09 | 3430.65 | 26-JAN-16:02 | 20.50 | 11.94 | 97552894.03 | 56.69 | 18-JAN-22:10 | 20.50 | 11.94 |
February | 0.127181E+10 | 3482.10 | 24-FEB-16:02 | 25.00 | 13.11 | 88580703.12 | 56.69 | 16-FEB-22:10 | 25.00 | 13.11 |
March | 0.176023E+10 | 3408.01 | 31-MAR-15:02 | 25.78 | 18.38 | 98441157.90 | 56.70 | 30-MAR-21:00 | 25.78 | 18.38 |
April | 0.235002E+10 | 3428.31 | 11-APR-15:02 | 28.80 | 22.61 | 95686579.17 | 56.70 | 04-APR-21:40 | 28.80 | 22.61 |
May | 0.286340E+10 | 3451.97 | 19-MAY-18:02 | 28.12 | 22.04 | 99102232.11 | 56.70 | 21-MAY-00:30 | 25.60 | 22.31 |
June | 0.296688E+10 | 3463.17 | 28-JUN-15:02 | 30.50 | 24.49 | 95974488.84 | 56.70 | 09-JUN-21:10 | 30.50 | 24.49 |
July | 0.329301E+10 | 3509.15 | 28-JUL-15:02 | 35.00 | 25.20 | 99098634.91 | 56.70 | 28-JUL-21:10 | 29.32 | 24.20 |
August | 0.304334E+10 | 3463.48 | 23-AUG-15:02 | 31.52 | 25.44 | 99152828.50 | 56.70 | 17-AUG-00:49 | 31.52 | 25.44 |
September | 0.282680E+10 | 3457.13 | 20-SEP-15:02 | 31.78 | 24.57 | 95852259.17 | 56.70 | 29-SEP-23:49 | 28.30 | 23.88 |
October | 0.252702E+10 | 3416.25 | 25-OCT-15:02 | 29.22 | 22.14 | 98979906.38 | 56.70 | 17-OCT-21:00 | 29.22 | 22.14 |
November | 0.177395E+10 | 3392.73 | 07-NOV-16:02 | 28.22 | 22.20 | 95379558.10 | 56.70 | 22-NOV-22:30 | 26.40 | 23.42 |
December | 0.123092E+10 | 3386.49 | 03-DEC-16:02 | 24.32 | 17.20 | 97704520.61 | 56.69 | 11-DEC-22:40 | 17.97 | 14.16 |
Annual Sum or Average | 0.268957E+11 | 0.116151E+10 | ||||||||
Minimum of Months | 0.988357E+09 | 3386.49 | 20.50 | 11.94 | 88580703.12 | 56.69 | 17.97 | 11.94 | ||
Maximum of Months | 0.329301E+10 | 3509.15 | 35.00 | 25.44 | 99152828.50 | 56.70 | 31.52 | 25.44 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.135202E+10 | 1728.98 | 26-JAN-16:02 | 20.50 | 11.94 | 98698776.72 | 56.69 | 03-JAN-01:19 | 20.50 | 11.94 |
February | 0.126905E+10 | 1723.92 | 24-FEB-16:02 | 25.00 | 13.11 | 89218134.61 | 56.69 | 28-FEB-23:40 | 17.83 | 13.57 |
March | 0.134918E+10 | 1682.95 | 20-MAR-15:01 | 19.40 | 10.17 | 98797919.30 | 56.70 | 28-MAR-21:10 | 24.32 | 20.85 |
April | 0.143400E+10 | 1663.72 | 05-APR-15:02 | 26.70 | 20.52 | 95694428.74 | 56.70 | 11-APR-21:10 | 25.00 | 22.01 |
May | 0.158772E+10 | 1641.30 | 01-MAY-15:02 | 29.90 | 20.98 | 99056557.51 | 56.70 | 04-MAY-21:10 | 25.60 | 21.81 |
June | 0.165597E+10 | 1637.15 | 01-JUN-15:02 | 30.00 | 23.17 | 95926015.35 | 56.70 | 14-JUN-21:40 | 28.30 | 23.17 |
July | 0.180624E+10 | 1678.76 | 28-JUL-15:02 | 35.00 | 25.20 | 99059943.88 | 56.70 | 07-JUL-21:40 | 35.00 | 25.20 |
August | 0.177673E+10 | 1669.98 | 31-AUG-15:02 | 32.12 | 24.95 | 99127961.80 | 56.70 | 30-AUG-21:00 | 32.12 | 24.95 |
September | 0.187821E+10 | 1676.67 | 16-SEP-15:02 | 30.60 | 24.39 | 95897316.14 | 56.70 | 26-SEP-22:10 | 26.73 | 22.71 |
October | 0.195292E+10 | 1679.17 | 25-OCT-15:02 | 29.22 | 22.14 | 99139457.05 | 56.70 | 17-OCT-21:49 | 29.22 | 22.14 |
November | 0.165249E+10 | 1668.47 | 07-NOV-16:02 | 28.22 | 22.20 | 95828440.14 | 56.70 | 20-NOV-22:49 | 25.60 | 21.07 |
December | 0.142198E+10 | 1694.08 | 03-DEC-16:02 | 24.32 | 17.20 | 98665182.30 | 56.70 | 08-DEC-22:40 | 24.23 | 22.72 |
Annual Sum or Average | 0.191365E+11 | 0.116511E+10 | ||||||||
Minimum of Months | 0.126905E+10 | 1637.15 | 19.40 | 10.17 | 89218134.61 | 56.69 | 17.83 | 11.94 | ||
Maximum of Months | 0.195292E+10 | 1728.98 | 35.00 | 25.20 | 99139457.05 | 56.70 | 35.00 | 25.20 |
Report: ZoneCoolingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.445881E+11 | 20835.59 | 13-JAN-23:40 | 23.90 | 21.21 | 0.156225E+11 | 10438.06 | 13-JAN-23:10 | 23.90 | 21.21 |
February | 0.412756E+11 | 20990.78 | 17-FEB-23:40 | 23.90 | 20.81 | 0.142325E+11 | 10488.30 | 17-FEB-23:10 | 23.90 | 20.81 |
March | 0.465429E+11 | 21830.87 | 13-MAR-18:10 | 27.93 | 22.26 | 0.159537E+11 | 10515.07 | 28-MAR-22:10 | 23.80 | 20.10 |
April | 0.469454E+11 | 22828.63 | 17-APR-18:10 | 30.03 | 18.67 | 0.155567E+11 | 10651.27 | 14-APR-22:10 | 30.03 | 18.67 |
May | 0.501634E+11 | 23192.50 | 22-MAY-18:10 | 30.40 | 23.74 | 0.163218E+11 | 10767.14 | 22-MAY-22:10 | 26.93 | 22.26 |
June | 0.496950E+11 | 23582.88 | 29-JUN-18:10 | 30.00 | 24.76 | 0.159858E+11 | 10872.90 | 09-JUN-22:10 | 30.00 | 24.76 |
July | 0.518611E+11 | 23846.50 | 27-JUL-18:10 | 31.83 | 25.86 | 0.164375E+11 | 10880.68 | 28-JUL-22:10 | 28.80 | 24.46 |
August | 0.509300E+11 | 23459.25 | 02-AUG-18:10 | 29.90 | 24.73 | 0.164718E+11 | 10835.71 | 02-AUG-22:10 | 28.90 | 24.51 |
September | 0.491111E+11 | 23011.37 | 18-SEP-18:10 | 30.40 | 25.93 | 0.158264E+11 | 10850.06 | 22-SEP-22:10 | 28.30 | 25.74 |
October | 0.493043E+11 | 22387.99 | 05-OCT-18:10 | 28.80 | 23.33 | 0.161722E+11 | 10710.46 | 03-OCT-22:10 | 28.80 | 23.33 |
November | 0.457669E+11 | 21672.56 | 03-NOV-22:40 | 26.70 | 23.98 | 0.154295E+11 | 10634.65 | 03-NOV-22:10 | 26.70 | 23.98 |
December | 0.452606E+11 | 21132.83 | 08-DEC-23:40 | 24.80 | 23.27 | 0.157089E+11 | 10493.89 | 08-DEC-23:10 | 24.80 | 23.27 |
Annual Sum or Average | 0.571444E+12 | 0.189719E+12 | ||||||||
Minimum of Months | 0.412756E+11 | 20835.59 | 23.90 | 18.67 | 0.142325E+11 | 10438.06 | 23.80 | 18.67 | ||
Maximum of Months | 0.518611E+11 | 23846.50 | 31.83 | 25.93 | 0.164718E+11 | 10880.68 | 30.03 | 25.74 |
Report: ZoneCoolingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.476985E+11 | 22093.35 | 02-JAN-19:10 | 23.12 | 19.93 | 0.157267E+11 | 10529.79 | 06-JAN-23:10 | 23.98 | 22.41 |
February | 0.441135E+11 | 22280.19 | 17-FEB-23:40 | 23.90 | 20.81 | 0.143345E+11 | 10584.75 | 17-FEB-23:10 | 23.90 | 20.81 |
March | 0.497353E+11 | 23173.76 | 13-MAR-18:10 | 27.93 | 22.26 | 0.160738E+11 | 10606.58 | 28-MAR-22:10 | 23.80 | 20.10 |
April | 0.500419E+11 | 24172.36 | 17-APR-18:10 | 30.03 | 18.67 | 0.156737E+11 | 10730.08 | 14-APR-22:10 | 30.03 | 18.67 |
May | 0.533452E+11 | 24559.52 | 22-MAY-18:10 | 30.40 | 23.74 | 0.164367E+11 | 10844.21 | 22-MAY-22:10 | 26.93 | 22.26 |
June | 0.527206E+11 | 24919.77 | 29-JUN-18:10 | 30.00 | 24.76 | 0.160810E+11 | 10938.21 | 09-JUN-22:10 | 30.00 | 24.76 |
July | 0.549346E+11 | 25182.38 | 27-JUL-18:10 | 31.83 | 25.86 | 0.165228E+11 | 10937.87 | 28-JUL-22:10 | 28.80 | 24.46 |
August | 0.540247E+11 | 24786.72 | 02-AUG-18:10 | 29.90 | 24.73 | 0.165649E+11 | 10897.41 | 02-AUG-22:10 | 28.90 | 24.51 |
September | 0.520727E+11 | 24310.40 | 18-SEP-18:10 | 30.40 | 25.93 | 0.159104E+11 | 10906.02 | 22-SEP-22:10 | 28.30 | 25.74 |
October | 0.523738E+11 | 23691.48 | 05-OCT-18:10 | 28.80 | 23.33 | 0.162672E+11 | 10784.88 | 03-OCT-22:10 | 28.80 | 23.33 |
November | 0.487812E+11 | 22944.93 | 02-NOV-18:10 | 27.12 | 22.55 | 0.155339E+11 | 10714.73 | 03-NOV-22:10 | 26.70 | 24.19 |
December | 0.483640E+11 | 22401.89 | 07-DEC-19:10 | 24.40 | 22.49 | 0.158162E+11 | 10578.92 | 08-DEC-23:10 | 24.50 | 22.98 |
Annual Sum or Average | 0.608206E+12 | 0.190942E+12 | ||||||||
Minimum of Months | 0.441135E+11 | 22093.35 | 23.12 | 18.67 | 0.143345E+11 | 10529.79 | 23.80 | 18.67 | ||
Maximum of Months | 0.549346E+11 | 25182.38 | 31.83 | 25.93 | 0.165649E+11 | 10938.21 | 30.03 | 25.74 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.558516E+11 | 29016.77 | 01-JAN-11:50 | 26.20 | 21.28 | 0.186658E+11 | 11319.66 | 28-JAN-18:19 | 22.93 | 20.00 |
February | 0.510776E+11 | 29205.74 | 11-FEB-11:50 | 27.70 | 23.78 | 0.168644E+11 | 11319.72 | 25-FEB-18:19 | 22.43 | 15.34 |
March | 0.572412E+11 | 29387.15 | 27-MAR-10:40 | 26.13 | 21.70 | 0.186809E+11 | 11319.72 | 25-MAR-17:19 | 26.13 | 21.70 |
April | 0.568504E+11 | 30274.81 | 15-APR-10:50 | 29.63 | 22.91 | 0.180819E+11 | 11319.74 | 08-APR-17:19 | 29.63 | 22.91 |
May | 0.597788E+11 | 30301.64 | 31-MAY-10:50 | 32.52 | 24.26 | 0.186937E+11 | 11319.74 | 20-MAY-17:19 | 32.52 | 24.26 |
June | 0.586647E+11 | 30637.70 | 11-JUN-10:50 | 31.02 | 23.55 | 0.180996E+11 | 11319.73 | 10-JUN-17:19 | 31.02 | 23.55 |
July | 0.610127E+11 | 30917.08 | 23-JUL-10:50 | 32.75 | 24.78 | 0.186970E+11 | 11319.73 | 15-JUL-17:19 | 32.75 | 24.78 |
August | 0.603000E+11 | 30600.54 | 19-AUG-10:40 | 31.50 | 24.70 | 0.187006E+11 | 11319.73 | 26-AUG-17:19 | 30.40 | 25.15 |
September | 0.584738E+11 | 30510.58 | 24-SEP-10:50 | 30.82 | 25.18 | 0.180941E+11 | 11319.73 | 16-SEP-17:19 | 30.82 | 25.18 |
October | 0.594337E+11 | 30387.61 | 07-OCT-10:40 | 31.13 | 24.14 | 0.186895E+11 | 11319.72 | 21-OCT-17:19 | 26.67 | 19.93 |
November | 0.558986E+11 | 29251.67 | 03-NOV-10:50 | 28.22 | 23.99 | 0.180759E+11 | 11319.66 | 25-NOV-18:19 | 25.03 | 22.08 |
December | 0.561179E+11 | 29223.04 | 09-DEC-11:40 | 27.20 | 22.50 | 0.186677E+11 | 11319.70 | 02-DEC-18:19 | 27.20 | 22.50 |
Annual Sum or Average | 0.690701E+12 | 0.220011E+12 | ||||||||
Minimum of Months | 0.510776E+11 | 29016.77 | 26.13 | 21.28 | 0.168644E+11 | 11319.66 | 22.43 | 15.34 | ||
Maximum of Months | 0.610127E+11 | 30917.08 | 32.75 | 25.18 | 0.187006E+11 | 11319.74 | 32.75 | 25.18 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.957094E+10 | 6348.01 | 01-JAN-11:35 | 26.30 | 21.34 | 0.127346E+10 | 779.59 | 13-JAN-23:10 | 23.90 | 21.21 |
February | 0.947090E+10 | 6464.67 | 11-FEB-11:35 | 27.60 | 23.74 | 0.115325E+10 | 777.07 | 17-FEB-23:10 | 23.90 | 20.81 |
March | 0.110328E+11 | 6377.72 | 04-MAR-11:35 | 27.03 | 22.82 | 0.128561E+10 | 787.03 | 27-MAR-22:10 | 24.32 | 21.61 |
April | 0.122668E+11 | 6781.01 | 15-APR-10:35 | 29.27 | 22.89 | 0.125565E+10 | 811.83 | 14-APR-21:49 | 29.27 | 22.89 |
May | 0.137000E+11 | 6931.67 | 31-MAY-10:35 | 32.23 | 24.19 | 0.132940E+10 | 823.55 | 22-MAY-22:10 | 32.23 | 24.19 |
June | 0.139394E+11 | 7227.45 | 11-JUN-10:35 | 30.93 | 23.60 | 0.132181E+10 | 844.83 | 09-JUN-22:10 | 30.93 | 23.60 |
July | 0.147896E+11 | 7400.77 | 29-JUL-10:35 | 32.07 | 25.98 | 0.137450E+10 | 853.30 | 28-JUL-22:10 | 32.07 | 25.98 |
August | 0.143072E+11 | 7241.91 | 19-AUG-10:35 | 31.50 | 24.70 | 0.136360E+10 | 842.98 | 02-AUG-22:10 | 31.50 | 24.70 |
September | 0.139438E+11 | 7287.70 | 24-SEP-10:35 | 30.53 | 25.04 | 0.131824E+10 | 852.13 | 22-SEP-22:10 | 30.53 | 25.04 |
October | 0.137774E+11 | 7118.15 | 07-OCT-10:35 | 31.13 | 24.14 | 0.133164E+10 | 826.29 | 06-OCT-22:10 | 31.13 | 24.14 |
November | 0.117460E+11 | 6685.07 | 08-NOV-11:35 | 27.43 | 21.48 | 0.125390E+10 | 808.80 | 03-NOV-22:10 | 27.43 | 21.48 |
December | 0.101631E+11 | 6651.05 | 09-DEC-11:35 | 27.20 | 22.50 | 0.127851E+10 | 790.19 | 08-DEC-23:10 | 27.20 | 22.50 |
Annual Sum or Average | 0.148708E+12 | 0.155396E+11 | ||||||||
Minimum of Months | 0.947090E+10 | 6348.01 | 26.30 | 21.34 | 0.115325E+10 | 777.07 | 23.90 | 20.81 | ||
Maximum of Months | 0.147896E+11 | 7400.77 | 32.23 | 25.98 | 0.137450E+10 | 853.30 | 32.23 | 25.98 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 20.40 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 16.65 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 17.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 27.93 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 22.40 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 24.10 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 16.65 | |
Maximum of Months | 0.00 | 0.00 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 20.40 |
February | 995617.70 | 150.57 | 04-FEB-07:20 | 5.57 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 17.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 27.93 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 22.40 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 24.10 |
Annual Sum or Average | 995617.70 | |||
Minimum of Months | 0.00 | 0.00 | 5.57 | |
Maximum of Months | 995617.70 | 150.57 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 20.40 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 16.65 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 17.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 27.93 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 22.40 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 24.10 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 16.65 | |
Maximum of Months | 0.00 | 0.00 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 20.40 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 16.65 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 17.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 27.93 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 22.40 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 24.10 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 16.65 | |
Maximum of Months | 0.00 | 0.00 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 20.40 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 16.65 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 17.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 27.93 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 22.40 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 24.10 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 16.65 | |
Maximum of Months | 0.00 | 0.00 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 20.40 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 16.65 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 17.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 27.93 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 22.40 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 24.10 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 16.65 | |
Maximum of Months | 0.00 | 0.00 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 20.40 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 16.65 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 17.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 27.93 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 22.40 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 24.10 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 16.65 | |
Maximum of Months | 0.00 | 0.00 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 20.40 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 16.65 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 17.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 27.93 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 22.40 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 24.10 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 16.65 | |
Maximum of Months | 0.00 | 0.00 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 4411923.23 | 652.00 | 25-JAN-16:04 | 17.80 |
February | 11063819.00 | 779.10 | 03-FEB-16:04 | 16.42 |
March | 3997512.48 | 1128.57 | 16-MAR-08:62 | 8.68 |
April | 1057837.24 | 660.17 | 29-APR-08:05 | 23.40 |
May | 717104.18 | 811.78 | 08-MAY-08:04 | 25.18 |
June | 387506.85 | 539.14 | 19-JUN-08:05 | 26.60 |
July | 90517.87 | 355.30 | 03-JUL-08:05 | 26.88 |
August | 463433.88 | 553.57 | 29-AUG-08:05 | 27.38 |
September | 472122.68 | 495.67 | 28-SEP-08:05 | 24.78 |
October | 703774.09 | 791.63 | 18-OCT-08:04 | 26.20 |
November | 1555439.78 | 652.30 | 27-NOV-09:03 | 15.65 |
December | 6573811.35 | 816.54 | 20-DEC-19:03 | 12.62 |
Annual Sum or Average | 31494802.63 | |||
Minimum of Months | 90517.87 | 355.30 | 8.68 | |
Maximum of Months | 11063819.00 | 1128.57 | 27.38 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 11690197.69 | 1148.70 | 26-JAN-09:02 | 13.77 |
February | 17409211.97 | 1116.73 | 04-FEB-09:02 | 10.47 |
March | 7709468.90 | 1146.37 | 16-MAR-08:62 | 8.68 |
April | 1112588.43 | 651.91 | 29-APR-08:05 | 23.40 |
May | 723866.88 | 832.15 | 08-MAY-08:04 | 25.18 |
June | 314203.60 | 509.22 | 19-JUN-08:05 | 26.60 |
July | 40948.27 | 294.91 | 03-JUL-08:05 | 26.88 |
August | 523430.93 | 547.74 | 29-AUG-08:05 | 27.38 |
September | 619316.64 | 517.52 | 07-SEP-08:05 | 25.18 |
October | 1209767.66 | 802.73 | 18-OCT-08:04 | 26.20 |
November | 3265498.31 | 800.18 | 12-NOV-16:03 | 20.00 |
December | 17476158.19 | 1128.51 | 27-DEC-09:02 | 11.47 |
Annual Sum or Average | 62094657.47 | |||
Minimum of Months | 40948.27 | 294.91 | 8.68 | |
Maximum of Months | 17476158.19 | 1148.70 | 27.38 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 20.40 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 16.65 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 17.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 27.93 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 22.40 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 24.10 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 16.65 | |
Maximum of Months | 0.00 | 0.00 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 682165.41 | 370.46 | 24-JAN-16:03 | 16.70 |
February | 457410.56 | 375.60 | 03-FEB-16:03 | 16.42 |
March | 558306.17 | 366.60 | 19-MAR-15:05 | 16.78 |
April | 284336.21 | 339.73 | 20-APR-08:05 | 23.48 |
May | 99577.86 | 195.45 | 11-MAY-08:06 | 24.60 |
June | 159613.29 | 135.39 | 09-JUN-08:07 | 28.98 |
July | 134652.50 | 100.18 | 12-JUL-08:07 | 28.22 |
August | 89379.18 | 142.53 | 12-AUG-18:07 | 26.60 |
September | 7545.36 | 35.73 | 11-SEP-08:07 | 27.48 |
October | 172588.04 | 127.69 | 10-OCT-18:07 | 27.12 |
November | 365432.03 | 331.06 | 15-NOV-09:05 | 23.98 |
December | 585860.61 | 354.55 | 26-DEC-16:04 | 18.12 |
Annual Sum or Average | 3596867.21 | |||
Minimum of Months | 7545.36 | 35.73 | 16.42 | |
Maximum of Months | 682165.41 | 375.60 | 28.98 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 5124433.07 | 705.61 | 25-JAN-16:04 | 17.80 |
February | 10587875.73 | 519.25 | 19-FEB-09:05 | 21.20 |
March | 3602659.10 | 895.21 | 16-MAR-15:04 | 18.48 |
April | 173657.58 | 630.91 | 30-APR-08:05 | 23.12 |
May | 85525.78 | 506.54 | 25-MAY-08:05 | 25.40 |
June | 23766.86 | 237.67 | 15-JUN-08:05 | 23.68 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
August | 53806.14 | 538.06 | 28-AUG-08:05 | 23.72 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 27.05 |
October | 27224.11 | 264.21 | 31-OCT-08:05 | 24.50 |
November | 1044560.03 | 390.43 | 27-NOV-19:05 | 22.20 |
December | 7936852.79 | 643.88 | 20-DEC-19:03 | 12.62 |
Annual Sum or Average | 28660361.19 | |||
Minimum of Months | 0.00 | 0.00 | 12.62 | |
Maximum of Months | 10587875.73 | 895.21 | 27.05 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 13804500.24 | 907.21 | 24-JAN-16:03 | 16.70 |
February | 16278835.32 | 677.94 | 03-FEB-16:03 | 16.42 |
March | 6232025.80 | 690.96 | 16-MAR-18:03 | 18.22 |
April | 194523.46 | 622.87 | 30-APR-08:05 | 23.12 |
May | 104047.81 | 573.58 | 25-MAY-08:05 | 25.40 |
June | 24824.30 | 248.24 | 15-JUN-08:05 | 23.68 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
August | 58226.77 | 524.66 | 28-AUG-08:05 | 23.72 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 27.05 |
October | 85377.22 | 489.97 | 18-OCT-08:04 | 26.20 |
November | 2764793.71 | 653.83 | 29-NOV-09:05 | 25.68 |
December | 20116713.29 | 778.27 | 27-DEC-16:03 | 20.00 |
Annual Sum or Average | 59663867.92 | |||
Minimum of Months | 0.00 | 0.00 | 16.42 | |
Maximum of Months | 20116713.29 | 907.21 | 27.05 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 20.40 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 16.65 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 17.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 27.93 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 22.40 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 24.10 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 16.65 | |
Maximum of Months | 0.00 | 0.00 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 14203971.55 | 846.01 | 25-JAN-09:02 | 11.57 |
February | 21143651.78 | 1288.85 | 04-FEB-09:02 | 10.47 |
March | 11364832.94 | 1340.75 | 16-MAR-08:62 | 8.68 |
April | 1000559.66 | 686.13 | 09-APR-08:04 | 23.90 |
May | 635770.22 | 814.00 | 08-MAY-08:04 | 25.18 |
June | 332313.64 | 425.09 | 22-JUN-08:05 | 24.90 |
July | 78010.70 | 317.11 | 03-JUL-08:05 | 26.88 |
August | 456116.31 | 553.33 | 12-AUG-08:05 | 22.70 |
September | 480426.12 | 448.32 | 26-SEP-08:05 | 24.78 |
October | 735169.14 | 799.81 | 18-OCT-08:04 | 26.20 |
November | 4848462.18 | 596.82 | 29-NOV-09:05 | 25.68 |
December | 20335815.31 | 1080.68 | 15-DEC-09:02 | 10.97 |
Annual Sum or Average | 75615099.54 | |||
Minimum of Months | 78010.70 | 317.11 | 8.68 | |
Maximum of Months | 21143651.78 | 1340.75 | 26.88 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 35388587.17 | 1360.11 | 26-JAN-09:02 | 13.77 |
February | 32120897.26 | 1340.14 | 05-FEB-09:02 | 15.37 |
March | 17760108.78 | 1360.18 | 16-MAR-08:62 | 8.68 |
April | 1075795.20 | 876.24 | 09-APR-08:04 | 23.90 |
May | 587539.77 | 816.81 | 08-MAY-08:04 | 25.18 |
June | 241582.03 | 387.40 | 19-JUN-08:05 | 26.60 |
July | 41030.11 | 279.50 | 03-JUL-08:05 | 26.88 |
August | 472175.50 | 567.39 | 12-AUG-08:05 | 22.70 |
September | 558511.70 | 442.96 | 12-SEP-08:05 | 26.28 |
October | 1118109.78 | 755.97 | 18-OCT-08:04 | 26.20 |
November | 8527790.81 | 1319.92 | 13-NOV-09:02 | 16.65 |
December | 40814680.29 | 1344.12 | 21-DEC-09:02 | 15.65 |
Annual Sum or Average | 0.138707E+09 | |||
Minimum of Months | 41030.11 | 279.50 | 8.68 | |
Maximum of Months | 40814680.29 | 1360.18 | 26.88 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 165792.99 | 297.50 | 09-JAN-09:05 | 15.28 |
February | 2268319.25 | 210.82 | 04-FEB-09:05 | 10.47 |
March | 835034.50 | 519.64 | 16-MAR-08:62 | 8.68 |
April | 371394.21 | 384.10 | 21-APR-08:05 | 24.60 |
May | 72634.84 | 340.86 | 01-MAY-08:05 | 24.78 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
August | 38061.76 | 329.51 | 28-AUG-08:05 | 23.72 |
September | 1124.44 | 11.22 | 15-SEP-08:05 | 25.37 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 27.93 |
November | 96101.75 | 323.73 | 12-NOV-16:05 | 20.00 |
December | 174984.51 | 266.03 | 16-DEC-09:05 | 14.45 |
Annual Sum or Average | 4023448.24 | |||
Minimum of Months | 0.00 | 0.00 | 8.68 | |
Maximum of Months | 2268319.25 | 519.64 | 27.93 |
Report: ZoneHeatingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 20.40 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 16.65 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 17.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 27.93 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 22.40 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 24.10 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 16.65 | |
Maximum of Months | 0.00 | 0.00 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 20.40 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 16.65 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 17.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 27.93 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 22.40 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 24.10 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 16.65 | |
Maximum of Months | 0.00 | 0.00 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 20.40 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 16.65 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 17.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 27.93 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 22.40 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 24.10 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 16.65 | |
Maximum of Months | 0.00 | 0.00 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 20.40 |
February | 940919.02 | 305.94 | 04-FEB-07:10 | 5.28 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 17.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 27.93 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 22.40 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 24.10 |
Annual Sum or Average | 940919.02 | |||
Minimum of Months | 0.00 | 0.00 | 5.28 | |
Maximum of Months | 940919.02 | 305.94 | 28.60 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.140333E+11 | 13517.00 | 02-JAN-20:10 | 0.127587E+11 | 10113.80 | 02-JAN-20:10 |
February | 0.126708E+11 | 13517.00 | 01-FEB-20:10 | 0.115208E+11 | 10113.80 | 01-FEB-20:10 |
March | 0.140766E+11 | 13517.00 | 01-MAR-20:10 | 0.127855E+11 | 10113.80 | 01-MAR-20:10 |
April | 0.135575E+11 | 13517.00 | 03-APR-19:10 | 0.123314E+11 | 10113.80 | 03-APR-19:10 |
May | 0.140576E+11 | 13517.00 | 01-MAY-19:10 | 0.127741E+11 | 10113.80 | 01-MAY-19:10 |
June | 0.136197E+11 | 13517.00 | 01-JUN-19:10 | 0.123716E+11 | 10113.80 | 01-JUN-19:10 |
July | 0.139955E+11 | 13517.00 | 03-JUL-19:10 | 0.127338E+11 | 10113.80 | 03-JUL-19:10 |
August | 0.140820E+11 | 13517.00 | 01-AUG-19:10 | 0.127894E+11 | 10113.80 | 01-AUG-19:10 |
September | 0.135629E+11 | 13517.00 | 01-SEP-19:10 | 0.123352E+11 | 10113.80 | 01-SEP-19:10 |
October | 0.140279E+11 | 13517.00 | 02-OCT-19:10 | 0.127549E+11 | 10113.80 | 02-OCT-19:10 |
November | 0.136089E+11 | 13517.00 | 01-NOV-19:10 | 0.123659E+11 | 10113.80 | 01-NOV-19:10 |
December | 0.139955E+11 | 13517.00 | 01-DEC-20:10 | 0.127338E+11 | 10113.80 | 01-DEC-20:10 |
Annual Sum or Average | 0.165288E+12 | 0.150255E+12 | ||||
Minimum of Months | 0.126708E+11 | 13517.00 | 0.115208E+11 | 10113.80 | ||
Maximum of Months | 0.140820E+11 | 13517.00 | 0.127894E+11 | 10113.80 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.713551E+09 | 687.30 | 02-JAN-20:10 | 0.864900E+09 | 685.60 | 02-JAN-20:10 |
February | 0.644271E+09 | 687.30 | 01-FEB-20:10 | 0.780982E+09 | 685.60 | 01-FEB-20:10 |
March | 0.715750E+09 | 687.30 | 01-MAR-20:10 | 0.866718E+09 | 685.60 | 01-MAR-20:10 |
April | 0.689358E+09 | 687.30 | 03-APR-19:10 | 0.835931E+09 | 685.60 | 03-APR-19:10 |
May | 0.714788E+09 | 687.30 | 01-MAY-19:10 | 0.865939E+09 | 685.60 | 01-MAY-19:10 |
June | 0.692519E+09 | 687.30 | 01-JUN-19:10 | 0.838659E+09 | 685.60 | 01-JUN-19:10 |
July | 0.711626E+09 | 687.30 | 03-JUL-19:10 | 0.863211E+09 | 685.60 | 03-JUL-19:10 |
August | 0.716025E+09 | 687.30 | 01-AUG-19:10 | 0.866978E+09 | 685.60 | 01-AUG-19:10 |
September | 0.689633E+09 | 687.30 | 01-SEP-19:10 | 0.836191E+09 | 685.60 | 01-SEP-19:10 |
October | 0.713276E+09 | 687.30 | 02-OCT-19:10 | 0.864640E+09 | 685.60 | 02-OCT-19:10 |
November | 0.691970E+09 | 687.30 | 01-NOV-19:10 | 0.838269E+09 | 685.60 | 01-NOV-19:10 |
December | 0.711626E+09 | 687.30 | 01-DEC-20:10 | 0.863211E+09 | 685.60 | 01-DEC-20:10 |
Annual Sum or Average | 0.840439E+10 | 0.101856E+11 | ||||
Minimum of Months | 0.644271E+09 | 687.30 | 0.780982E+09 | 685.60 | ||
Maximum of Months | 0.716025E+09 | 687.30 | 0.866978E+09 | 685.60 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.826294E+09 | 795.89 | 02-JAN-20:10 | 0.100156E+10 | 793.93 | 02-JAN-20:10 |
February | 0.746069E+09 | 795.89 | 01-FEB-20:10 | 0.904380E+09 | 793.93 | 01-FEB-20:10 |
March | 0.828841E+09 | 795.89 | 01-MAR-20:10 | 0.100366E+10 | 793.93 | 01-MAR-20:10 |
April | 0.798279E+09 | 795.89 | 03-APR-19:10 | 0.968011E+09 | 793.93 | 03-APR-19:10 |
May | 0.827727E+09 | 795.89 | 01-MAY-19:10 | 0.100276E+10 | 793.93 | 01-MAY-19:10 |
June | 0.801940E+09 | 795.89 | 01-JUN-19:10 | 0.971170E+09 | 793.93 | 01-JUN-19:10 |
July | 0.824066E+09 | 795.89 | 03-JUL-19:10 | 0.999601E+09 | 793.93 | 03-JUL-19:10 |
August | 0.829160E+09 | 795.89 | 01-AUG-19:10 | 0.100396E+10 | 793.93 | 01-AUG-19:10 |
September | 0.798597E+09 | 795.89 | 01-SEP-19:10 | 0.968312E+09 | 793.93 | 01-SEP-19:10 |
October | 0.825976E+09 | 795.89 | 02-OCT-19:10 | 0.100126E+10 | 793.93 | 02-OCT-19:10 |
November | 0.801303E+09 | 795.89 | 01-NOV-19:10 | 0.970719E+09 | 793.93 | 01-NOV-19:10 |
December | 0.824066E+09 | 795.89 | 01-DEC-20:10 | 0.999601E+09 | 793.93 | 01-DEC-20:10 |
Annual Sum or Average | 0.973232E+10 | 0.117950E+11 | ||||
Minimum of Months | 0.746069E+09 | 795.89 | 0.904380E+09 | 793.93 | ||
Maximum of Months | 0.829160E+09 | 795.89 | 0.100396E+10 | 793.93 |
Report: ZoneElectricSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.154452E+10 | 1487.69 | 02-JAN-20:10 | 0.105898E+10 | 839.45 | 02-JAN-20:10 |
February | 0.139456E+10 | 1487.69 | 01-FEB-20:10 | 0.956227E+09 | 839.45 | 01-FEB-20:10 |
March | 0.154928E+10 | 1487.69 | 01-MAR-20:10 | 0.106120E+10 | 839.45 | 01-MAR-20:10 |
April | 0.149215E+10 | 1487.69 | 03-APR-19:10 | 0.102351E+10 | 839.45 | 03-APR-19:10 |
May | 0.154719E+10 | 1487.69 | 01-MAY-19:10 | 0.106025E+10 | 839.45 | 01-MAY-19:10 |
June | 0.149899E+10 | 1487.69 | 01-JUN-19:10 | 0.102685E+10 | 839.45 | 01-JUN-19:10 |
July | 0.154035E+10 | 1487.69 | 03-JUL-19:10 | 0.105691E+10 | 839.45 | 03-JUL-19:10 |
August | 0.154987E+10 | 1487.69 | 01-AUG-19:10 | 0.106152E+10 | 839.45 | 01-AUG-19:10 |
September | 0.149274E+10 | 1487.69 | 01-SEP-19:10 | 0.102382E+10 | 839.45 | 01-SEP-19:10 |
October | 0.154392E+10 | 1487.69 | 02-OCT-19:10 | 0.105866E+10 | 839.45 | 02-OCT-19:10 |
November | 0.149780E+10 | 1487.69 | 01-NOV-19:10 | 0.102637E+10 | 839.45 | 01-NOV-19:10 |
December | 0.154035E+10 | 1487.69 | 01-DEC-20:10 | 0.105691E+10 | 839.45 | 01-DEC-20:10 |
Annual Sum or Average | 0.181917E+11 | 0.124712E+11 | ||||
Minimum of Months | 0.139456E+10 | 1487.69 | 0.956227E+09 | 839.45 | ||
Maximum of Months | 0.154987E+10 | 1487.69 | 0.106152E+10 | 839.45 |
Report: ZoneElectricSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.283535E+09 | 273.10 | 02-JAN-20:10 | 0.305485E+09 | 242.16 | 02-JAN-20:10 |
February | 0.256006E+09 | 273.10 | 01-FEB-20:10 | 0.275845E+09 | 242.16 | 01-FEB-20:10 |
March | 0.284409E+09 | 273.10 | 01-MAR-20:10 | 0.306128E+09 | 242.16 | 01-MAR-20:10 |
April | 0.273921E+09 | 273.10 | 03-APR-19:10 | 0.295253E+09 | 242.16 | 03-APR-19:10 |
May | 0.284026E+09 | 273.10 | 01-MAY-19:10 | 0.305852E+09 | 242.16 | 01-MAY-19:10 |
June | 0.275178E+09 | 273.10 | 01-JUN-19:10 | 0.296217E+09 | 242.16 | 01-JUN-19:10 |
July | 0.282770E+09 | 273.10 | 03-JUL-19:10 | 0.304889E+09 | 242.16 | 03-JUL-19:10 |
August | 0.284518E+09 | 273.10 | 01-AUG-19:10 | 0.306219E+09 | 242.16 | 01-AUG-19:10 |
September | 0.274031E+09 | 273.10 | 01-SEP-19:10 | 0.295345E+09 | 242.16 | 01-SEP-19:10 |
October | 0.283425E+09 | 273.10 | 02-OCT-19:10 | 0.305393E+09 | 242.16 | 02-OCT-19:10 |
November | 0.274959E+09 | 273.10 | 01-NOV-19:10 | 0.296079E+09 | 242.16 | 01-NOV-19:10 |
December | 0.282770E+09 | 273.10 | 01-DEC-20:10 | 0.304889E+09 | 242.16 | 01-DEC-20:10 |
Annual Sum or Average | 0.333955E+10 | 0.359760E+10 | ||||
Minimum of Months | 0.256006E+09 | 273.10 | 0.275845E+09 | 242.16 | ||
Maximum of Months | 0.284518E+09 | 273.10 | 0.306219E+09 | 242.16 |
Report: ZoneElectricSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.350256E+09 | 337.37 | 02-JAN-20:10 | 0.576866E+10 | 4572.80 | 02-JAN-20:10 |
February | 0.316249E+09 | 337.37 | 01-FEB-20:10 | 0.520895E+10 | 4572.80 | 01-FEB-20:10 |
March | 0.351336E+09 | 337.37 | 01-MAR-20:10 | 0.578079E+10 | 4572.80 | 01-MAR-20:10 |
April | 0.338381E+09 | 337.37 | 03-APR-19:10 | 0.557545E+10 | 4572.80 | 03-APR-19:10 |
May | 0.350863E+09 | 337.37 | 01-MAY-19:10 | 0.577559E+10 | 4572.80 | 01-MAY-19:10 |
June | 0.339933E+09 | 337.37 | 01-JUN-19:10 | 0.559364E+10 | 4572.80 | 01-JUN-19:10 |
July | 0.349311E+09 | 337.37 | 03-JUL-19:10 | 0.575740E+10 | 4572.80 | 03-JUL-19:10 |
August | 0.351471E+09 | 337.37 | 01-AUG-19:10 | 0.578252E+10 | 4572.80 | 01-AUG-19:10 |
September | 0.338516E+09 | 337.37 | 01-SEP-19:10 | 0.557718E+10 | 4572.80 | 01-SEP-19:10 |
October | 0.350121E+09 | 337.37 | 02-OCT-19:10 | 0.576693E+10 | 4572.80 | 02-OCT-19:10 |
November | 0.339663E+09 | 337.37 | 01-NOV-19:10 | 0.559104E+10 | 4572.80 | 01-NOV-19:10 |
December | 0.349311E+09 | 337.37 | 01-DEC-20:10 | 0.575740E+10 | 4572.80 | 01-DEC-20:10 |
Annual Sum or Average | 0.412541E+10 | 0.679355E+11 | ||||
Minimum of Months | 0.316249E+09 | 337.37 | 0.520895E+10 | 4572.80 | ||
Maximum of Months | 0.351471E+09 | 337.37 | 0.578252E+10 | 4572.80 |
Report: ZoneElectricSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.226040E+10 | 2177.23 | 02-JAN-20:10 | 0.121771E+10 | 965.27 | 02-JAN-20:10 |
February | 0.204093E+10 | 2177.23 | 01-FEB-20:10 | 0.109956E+10 | 965.27 | 01-FEB-20:10 |
March | 0.226736E+10 | 2177.23 | 01-MAR-20:10 | 0.122027E+10 | 965.27 | 01-MAR-20:10 |
April | 0.218376E+10 | 2177.23 | 03-APR-19:10 | 0.117692E+10 | 965.27 | 03-APR-19:10 |
May | 0.226431E+10 | 2177.23 | 01-MAY-19:10 | 0.121917E+10 | 965.27 | 01-MAY-19:10 |
June | 0.219377E+10 | 2177.23 | 01-JUN-19:10 | 0.118076E+10 | 965.27 | 01-JUN-19:10 |
July | 0.225430E+10 | 2177.23 | 03-JUL-19:10 | 0.121533E+10 | 965.27 | 03-JUL-19:10 |
August | 0.226823E+10 | 2177.23 | 01-AUG-19:10 | 0.122063E+10 | 965.27 | 01-AUG-19:10 |
September | 0.218463E+10 | 2177.23 | 01-SEP-19:10 | 0.117729E+10 | 965.27 | 01-SEP-19:10 |
October | 0.225952E+10 | 2177.23 | 02-OCT-19:10 | 0.121734E+10 | 965.27 | 02-OCT-19:10 |
November | 0.219203E+10 | 2177.23 | 01-NOV-19:10 | 0.118021E+10 | 965.27 | 01-NOV-19:10 |
December | 0.225430E+10 | 2177.23 | 01-DEC-20:10 | 0.121533E+10 | 965.27 | 01-DEC-20:10 |
Annual Sum or Average | 0.266236E+11 | 0.143405E+11 | ||||
Minimum of Months | 0.204093E+10 | 2177.23 | 0.109956E+10 | 965.27 | ||
Maximum of Months | 0.226823E+10 | 2177.23 | 0.122063E+10 | 965.27 |
Report: ZoneElectricSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.123020E+11 | 11849.32 | 02-JAN-20:10 | 0.126520E+11 | 10029.21 | 02-JAN-20:10 |
February | 0.111075E+11 | 11849.32 | 01-FEB-20:10 | 0.114244E+11 | 10029.21 | 01-FEB-20:10 |
March | 0.123399E+11 | 11849.32 | 01-MAR-20:10 | 0.126786E+11 | 10029.21 | 01-MAR-20:10 |
April | 0.118849E+11 | 11849.32 | 03-APR-19:10 | 0.122282E+11 | 10029.21 | 03-APR-19:10 |
May | 0.123233E+11 | 11849.32 | 01-MAY-19:10 | 0.126672E+11 | 10029.21 | 01-MAY-19:10 |
June | 0.119394E+11 | 11849.32 | 01-JUN-19:10 | 0.122682E+11 | 10029.21 | 01-JUN-19:10 |
July | 0.122688E+11 | 11849.32 | 03-JUL-19:10 | 0.126273E+11 | 10029.21 | 03-JUL-19:10 |
August | 0.123446E+11 | 11849.32 | 01-AUG-19:10 | 0.126824E+11 | 10029.21 | 01-AUG-19:10 |
September | 0.118896E+11 | 11849.32 | 01-SEP-19:10 | 0.122320E+11 | 10029.21 | 01-SEP-19:10 |
October | 0.122972E+11 | 11849.32 | 02-OCT-19:10 | 0.126482E+11 | 10029.21 | 02-OCT-19:10 |
November | 0.119299E+11 | 11849.32 | 01-NOV-19:10 | 0.122624E+11 | 10029.21 | 01-NOV-19:10 |
December | 0.122688E+11 | 11849.32 | 01-DEC-20:10 | 0.126273E+11 | 10029.21 | 01-DEC-20:10 |
Annual Sum or Average | 0.144896E+12 | 0.148998E+12 | ||||
Minimum of Months | 0.111075E+11 | 11849.32 | 0.114244E+11 | 10029.21 | ||
Maximum of Months | 0.123446E+11 | 11849.32 | 0.126824E+11 | 10029.21 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.434056E+09 | 392.73 | 01-JAN-19:10 | 0.261068E+09 | 237.06 | 01-JAN-08:09 |
February | 0.391995E+09 | 392.73 | 01-FEB-20:10 | 0.235798E+09 | 237.06 | 01-FEB-07:10 |
March | 0.430607E+09 | 392.73 | 01-MAR-20:10 | 0.260708E+09 | 237.06 | 01-MAR-07:10 |
April | 0.420554E+09 | 392.73 | 01-APR-18:10 | 0.252705E+09 | 237.06 | 01-APR-07:10 |
May | 0.432331E+09 | 392.73 | 01-MAY-19:10 | 0.260888E+09 | 237.06 | 01-MAY-06:10 |
June | 0.417218E+09 | 392.73 | 01-JUN-19:10 | 0.252344E+09 | 237.06 | 01-JUN-06:10 |
July | 0.435725E+09 | 392.73 | 01-JUL-18:10 | 0.261248E+09 | 237.06 | 01-JUL-07:10 |
August | 0.430607E+09 | 392.73 | 01-AUG-19:10 | 0.260708E+09 | 237.06 | 01-AUG-06:10 |
September | 0.420667E+09 | 392.73 | 01-SEP-19:10 | 0.252705E+09 | 237.06 | 01-SEP-06:10 |
October | 0.434000E+09 | 392.73 | 01-OCT-18:10 | 0.261068E+09 | 237.06 | 01-OCT-07:10 |
November | 0.418886E+09 | 392.73 | 01-NOV-19:10 | 0.252524E+09 | 237.06 | 01-NOV-06:10 |
December | 0.435781E+09 | 392.73 | 01-DEC-20:10 | 0.261248E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.510243E+10 | 0.307301E+10 | ||||
Minimum of Months | 0.391995E+09 | 392.73 | 0.235798E+09 | 237.06 | ||
Maximum of Months | 0.435781E+09 | 392.73 | 0.261248E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.434005E+09 | 392.68 | 01-JAN-19:10 | 0.261038E+09 | 237.03 | 01-JAN-08:09 |
February | 0.391949E+09 | 392.68 | 01-FEB-20:10 | 0.235770E+09 | 237.03 | 01-FEB-07:10 |
March | 0.430556E+09 | 392.68 | 01-MAR-20:10 | 0.260677E+09 | 237.03 | 01-MAR-07:10 |
April | 0.420505E+09 | 392.68 | 01-APR-18:10 | 0.252675E+09 | 237.03 | 01-APR-07:10 |
May | 0.432281E+09 | 392.68 | 01-MAY-19:10 | 0.260857E+09 | 237.03 | 01-MAY-06:10 |
June | 0.417169E+09 | 392.68 | 01-JUN-19:10 | 0.252315E+09 | 237.03 | 01-JUN-06:10 |
July | 0.435674E+09 | 392.68 | 01-JUL-18:10 | 0.261218E+09 | 237.03 | 01-JUL-07:10 |
August | 0.430556E+09 | 392.68 | 01-AUG-19:10 | 0.260677E+09 | 237.03 | 01-AUG-06:10 |
September | 0.420618E+09 | 392.68 | 01-SEP-19:10 | 0.252675E+09 | 237.03 | 01-SEP-06:10 |
October | 0.433949E+09 | 392.68 | 01-OCT-18:10 | 0.261038E+09 | 237.03 | 01-OCT-07:10 |
November | 0.418837E+09 | 392.68 | 01-NOV-19:10 | 0.252495E+09 | 237.03 | 01-NOV-06:10 |
December | 0.435730E+09 | 392.68 | 01-DEC-20:10 | 0.261218E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.510183E+10 | 0.307265E+10 | ||||
Minimum of Months | 0.391949E+09 | 392.68 | 0.235770E+09 | 237.03 | ||
Maximum of Months | 0.435730E+09 | 392.68 | 0.261218E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.272788E+09 | 246.81 | 01-JAN-19:10 | 0.255708E+09 | 232.19 | 01-JAN-08:09 |
February | 0.246354E+09 | 246.81 | 01-FEB-20:10 | 0.230956E+09 | 232.19 | 01-FEB-07:10 |
March | 0.270620E+09 | 246.81 | 01-MAR-20:10 | 0.255355E+09 | 232.19 | 01-MAR-07:10 |
April | 0.264302E+09 | 246.81 | 01-APR-18:10 | 0.247516E+09 | 232.19 | 01-APR-07:10 |
May | 0.271704E+09 | 246.81 | 01-MAY-19:10 | 0.255532E+09 | 232.19 | 01-MAY-06:10 |
June | 0.262205E+09 | 246.81 | 01-JUN-19:10 | 0.247163E+09 | 232.19 | 01-JUN-06:10 |
July | 0.273836E+09 | 246.81 | 01-JUL-18:10 | 0.255885E+09 | 232.19 | 01-JUL-07:10 |
August | 0.270620E+09 | 246.81 | 01-AUG-19:10 | 0.255355E+09 | 232.19 | 01-AUG-06:10 |
September | 0.264373E+09 | 246.81 | 01-SEP-19:10 | 0.247516E+09 | 232.19 | 01-SEP-06:10 |
October | 0.272752E+09 | 246.81 | 01-OCT-18:10 | 0.255708E+09 | 232.19 | 01-OCT-07:10 |
November | 0.263254E+09 | 246.81 | 01-NOV-19:10 | 0.247340E+09 | 232.19 | 01-NOV-06:10 |
December | 0.273872E+09 | 246.81 | 01-DEC-20:10 | 0.255885E+09 | 232.19 | 01-DEC-07:10 |
Annual Sum or Average | 0.320668E+10 | 0.300992E+10 | ||||
Minimum of Months | 0.246354E+09 | 246.81 | 0.230956E+09 | 232.19 | ||
Maximum of Months | 0.273872E+09 | 246.81 | 0.255885E+09 | 232.19 |
Report: ZoneElectricSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.272862E+09 | 246.88 | 01-JAN-19:10 | 0.255778E+09 | 232.26 | 01-JAN-08:09 |
February | 0.246421E+09 | 246.88 | 01-FEB-20:10 | 0.231020E+09 | 232.26 | 01-FEB-07:10 |
March | 0.270694E+09 | 246.88 | 01-MAR-20:10 | 0.255425E+09 | 232.26 | 01-MAR-07:10 |
April | 0.264375E+09 | 246.88 | 01-APR-18:10 | 0.247584E+09 | 232.26 | 01-APR-07:10 |
May | 0.271778E+09 | 246.88 | 01-MAY-19:10 | 0.255602E+09 | 232.26 | 01-MAY-06:10 |
June | 0.262277E+09 | 246.88 | 01-JUN-19:10 | 0.247231E+09 | 232.26 | 01-JUN-06:10 |
July | 0.273911E+09 | 246.88 | 01-JUL-18:10 | 0.255955E+09 | 232.26 | 01-JUL-07:10 |
August | 0.270694E+09 | 246.88 | 01-AUG-19:10 | 0.255425E+09 | 232.26 | 01-AUG-06:10 |
September | 0.264446E+09 | 246.88 | 01-SEP-19:10 | 0.247584E+09 | 232.26 | 01-SEP-06:10 |
October | 0.272827E+09 | 246.88 | 01-OCT-18:10 | 0.255778E+09 | 232.26 | 01-OCT-07:10 |
November | 0.263326E+09 | 246.88 | 01-NOV-19:10 | 0.247408E+09 | 232.26 | 01-NOV-06:10 |
December | 0.273947E+09 | 246.88 | 01-DEC-20:10 | 0.255955E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.320756E+10 | 0.301074E+10 | ||||
Minimum of Months | 0.246421E+09 | 246.88 | 0.231020E+09 | 232.26 | ||
Maximum of Months | 0.273947E+09 | 246.88 | 0.255955E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.434056E+09 | 392.73 | 01-JAN-19:10 | 0.261068E+09 | 237.06 | 01-JAN-08:09 |
February | 0.391995E+09 | 392.73 | 01-FEB-20:10 | 0.235798E+09 | 237.06 | 01-FEB-07:10 |
March | 0.430607E+09 | 392.73 | 01-MAR-20:10 | 0.260708E+09 | 237.06 | 01-MAR-07:10 |
April | 0.420554E+09 | 392.73 | 01-APR-18:10 | 0.252705E+09 | 237.06 | 01-APR-07:10 |
May | 0.432331E+09 | 392.73 | 01-MAY-19:10 | 0.260888E+09 | 237.06 | 01-MAY-06:10 |
June | 0.417218E+09 | 392.73 | 01-JUN-19:10 | 0.252344E+09 | 237.06 | 01-JUN-06:10 |
July | 0.435725E+09 | 392.73 | 01-JUL-18:10 | 0.261248E+09 | 237.06 | 01-JUL-07:10 |
August | 0.430607E+09 | 392.73 | 01-AUG-19:10 | 0.260708E+09 | 237.06 | 01-AUG-06:10 |
September | 0.420667E+09 | 392.73 | 01-SEP-19:10 | 0.252705E+09 | 237.06 | 01-SEP-06:10 |
October | 0.434000E+09 | 392.73 | 01-OCT-18:10 | 0.261068E+09 | 237.06 | 01-OCT-07:10 |
November | 0.418886E+09 | 392.73 | 01-NOV-19:10 | 0.252524E+09 | 237.06 | 01-NOV-06:10 |
December | 0.435781E+09 | 392.73 | 01-DEC-20:10 | 0.261248E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.510243E+10 | 0.307301E+10 | ||||
Minimum of Months | 0.391995E+09 | 392.73 | 0.235798E+09 | 237.06 | ||
Maximum of Months | 0.435781E+09 | 392.73 | 0.261248E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.434005E+09 | 392.68 | 01-JAN-19:10 | 0.261038E+09 | 237.03 | 01-JAN-08:09 |
February | 0.391949E+09 | 392.68 | 01-FEB-20:10 | 0.235770E+09 | 237.03 | 01-FEB-07:10 |
March | 0.430556E+09 | 392.68 | 01-MAR-20:10 | 0.260677E+09 | 237.03 | 01-MAR-07:10 |
April | 0.420505E+09 | 392.68 | 01-APR-18:10 | 0.252675E+09 | 237.03 | 01-APR-07:10 |
May | 0.432281E+09 | 392.68 | 01-MAY-19:10 | 0.260857E+09 | 237.03 | 01-MAY-06:10 |
June | 0.417169E+09 | 392.68 | 01-JUN-19:10 | 0.252315E+09 | 237.03 | 01-JUN-06:10 |
July | 0.435674E+09 | 392.68 | 01-JUL-18:10 | 0.261218E+09 | 237.03 | 01-JUL-07:10 |
August | 0.430556E+09 | 392.68 | 01-AUG-19:10 | 0.260677E+09 | 237.03 | 01-AUG-06:10 |
September | 0.420618E+09 | 392.68 | 01-SEP-19:10 | 0.252675E+09 | 237.03 | 01-SEP-06:10 |
October | 0.433949E+09 | 392.68 | 01-OCT-18:10 | 0.261038E+09 | 237.03 | 01-OCT-07:10 |
November | 0.418837E+09 | 392.68 | 01-NOV-19:10 | 0.252495E+09 | 237.03 | 01-NOV-06:10 |
December | 0.435730E+09 | 392.68 | 01-DEC-20:10 | 0.261218E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.510183E+10 | 0.307265E+10 | ||||
Minimum of Months | 0.391949E+09 | 392.68 | 0.235770E+09 | 237.03 | ||
Maximum of Months | 0.435730E+09 | 392.68 | 0.261218E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.133160E+10 | 1282.60 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.120231E+10 | 1282.60 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.133570E+10 | 1282.60 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.128645E+10 | 1282.60 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.133391E+10 | 1282.60 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.129235E+10 | 1282.60 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.132801E+10 | 1282.60 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.133622E+10 | 1282.60 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.128696E+10 | 1282.60 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.133109E+10 | 1282.60 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.129132E+10 | 1282.60 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.132801E+10 | 1282.60 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.156839E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.120231E+10 | 1282.60 | 0.00 | 0.00 | |
Maximum of Months | 0.133622E+10 | 1282.60 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.434056E+09 | 392.73 | 01-JAN-19:10 | 0.261068E+09 | 237.06 | 01-JAN-08:09 |
February | 0.391995E+09 | 392.73 | 01-FEB-20:10 | 0.235798E+09 | 237.06 | 01-FEB-07:10 |
March | 0.430607E+09 | 392.73 | 01-MAR-20:10 | 0.260708E+09 | 237.06 | 01-MAR-07:10 |
April | 0.420554E+09 | 392.73 | 01-APR-18:10 | 0.252705E+09 | 237.06 | 01-APR-07:10 |
May | 0.432331E+09 | 392.73 | 01-MAY-19:10 | 0.260888E+09 | 237.06 | 01-MAY-06:10 |
June | 0.417218E+09 | 392.73 | 01-JUN-19:10 | 0.252344E+09 | 237.06 | 01-JUN-06:10 |
July | 0.435725E+09 | 392.73 | 01-JUL-18:10 | 0.261248E+09 | 237.06 | 01-JUL-07:10 |
August | 0.430607E+09 | 392.73 | 01-AUG-19:10 | 0.260708E+09 | 237.06 | 01-AUG-06:10 |
September | 0.420667E+09 | 392.73 | 01-SEP-19:10 | 0.252705E+09 | 237.06 | 01-SEP-06:10 |
October | 0.434000E+09 | 392.73 | 01-OCT-18:10 | 0.261068E+09 | 237.06 | 01-OCT-07:10 |
November | 0.418886E+09 | 392.73 | 01-NOV-19:10 | 0.252524E+09 | 237.06 | 01-NOV-06:10 |
December | 0.435781E+09 | 392.73 | 01-DEC-20:10 | 0.261248E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.510243E+10 | 0.307301E+10 | ||||
Minimum of Months | 0.391995E+09 | 392.73 | 0.235798E+09 | 237.06 | ||
Maximum of Months | 0.435781E+09 | 392.73 | 0.261248E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.434005E+09 | 392.68 | 01-JAN-19:10 | 0.261038E+09 | 237.03 | 01-JAN-08:09 |
February | 0.391949E+09 | 392.68 | 01-FEB-20:10 | 0.235770E+09 | 237.03 | 01-FEB-07:10 |
March | 0.430556E+09 | 392.68 | 01-MAR-20:10 | 0.260677E+09 | 237.03 | 01-MAR-07:10 |
April | 0.420505E+09 | 392.68 | 01-APR-18:10 | 0.252675E+09 | 237.03 | 01-APR-07:10 |
May | 0.432281E+09 | 392.68 | 01-MAY-19:10 | 0.260857E+09 | 237.03 | 01-MAY-06:10 |
June | 0.417169E+09 | 392.68 | 01-JUN-19:10 | 0.252315E+09 | 237.03 | 01-JUN-06:10 |
July | 0.435674E+09 | 392.68 | 01-JUL-18:10 | 0.261218E+09 | 237.03 | 01-JUL-07:10 |
August | 0.430556E+09 | 392.68 | 01-AUG-19:10 | 0.260677E+09 | 237.03 | 01-AUG-06:10 |
September | 0.420618E+09 | 392.68 | 01-SEP-19:10 | 0.252675E+09 | 237.03 | 01-SEP-06:10 |
October | 0.433949E+09 | 392.68 | 01-OCT-18:10 | 0.261038E+09 | 237.03 | 01-OCT-07:10 |
November | 0.418837E+09 | 392.68 | 01-NOV-19:10 | 0.252495E+09 | 237.03 | 01-NOV-06:10 |
December | 0.435730E+09 | 392.68 | 01-DEC-20:10 | 0.261218E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.510183E+10 | 0.307265E+10 | ||||
Minimum of Months | 0.391949E+09 | 392.68 | 0.235770E+09 | 237.03 | ||
Maximum of Months | 0.435730E+09 | 392.68 | 0.261218E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.272862E+09 | 246.88 | 01-JAN-19:10 | 0.255778E+09 | 232.26 | 01-JAN-08:09 |
February | 0.246421E+09 | 246.88 | 01-FEB-20:10 | 0.231020E+09 | 232.26 | 01-FEB-07:10 |
March | 0.270694E+09 | 246.88 | 01-MAR-20:10 | 0.255425E+09 | 232.26 | 01-MAR-07:10 |
April | 0.264375E+09 | 246.88 | 01-APR-18:10 | 0.247584E+09 | 232.26 | 01-APR-07:10 |
May | 0.271778E+09 | 246.88 | 01-MAY-19:10 | 0.255602E+09 | 232.26 | 01-MAY-06:10 |
June | 0.262277E+09 | 246.88 | 01-JUN-19:10 | 0.247231E+09 | 232.26 | 01-JUN-06:10 |
July | 0.273911E+09 | 246.88 | 01-JUL-18:10 | 0.255955E+09 | 232.26 | 01-JUL-07:10 |
August | 0.270694E+09 | 246.88 | 01-AUG-19:10 | 0.255425E+09 | 232.26 | 01-AUG-06:10 |
September | 0.264446E+09 | 246.88 | 01-SEP-19:10 | 0.247584E+09 | 232.26 | 01-SEP-06:10 |
October | 0.272827E+09 | 246.88 | 01-OCT-18:10 | 0.255778E+09 | 232.26 | 01-OCT-07:10 |
November | 0.263326E+09 | 246.88 | 01-NOV-19:10 | 0.247408E+09 | 232.26 | 01-NOV-06:10 |
December | 0.273947E+09 | 246.88 | 01-DEC-20:10 | 0.255955E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.320756E+10 | 0.301074E+10 | ||||
Minimum of Months | 0.246421E+09 | 246.88 | 0.231020E+09 | 232.26 | ||
Maximum of Months | 0.273947E+09 | 246.88 | 0.255955E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.396945E+10 | 3823.39 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.358405E+10 | 3823.39 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.398168E+10 | 3823.39 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.383486E+10 | 3823.39 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.397633E+10 | 3823.39 | 01-MAY-19:10 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.385245E+10 | 3823.39 | 01-JUN-19:10 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.395874E+10 | 3823.39 | 03-JUL-19:10 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.398321E+10 | 3823.39 | 01-AUG-19:10 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.383639E+10 | 3823.39 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.396792E+10 | 3823.39 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.384939E+10 | 3823.39 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.395874E+10 | 3823.39 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.467532E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.358405E+10 | 3823.39 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.398321E+10 | 3823.39 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.396945E+10 | 3823.39 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.358405E+10 | 3823.39 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.398168E+10 | 3823.39 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.383486E+10 | 3823.39 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.397633E+10 | 3823.39 | 01-MAY-19:10 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.385245E+10 | 3823.39 | 01-JUN-19:10 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.395874E+10 | 3823.39 | 03-JUL-19:10 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.398321E+10 | 3823.39 | 01-AUG-19:10 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.383639E+10 | 3823.39 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.396792E+10 | 3823.39 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.384939E+10 | 3823.39 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.395874E+10 | 3823.39 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.467532E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.358405E+10 | 3823.39 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.398321E+10 | 3823.39 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.105977E+10 | 1020.78 | 02-JAN-20:10 | 0.373720E+11 | 16686.59 | 01-JAN-07:10 |
February | 0.956878E+09 | 1020.78 | 01-FEB-20:10 | 0.337554E+11 | 16686.59 | 01-FEB-07:10 |
March | 0.106304E+10 | 1020.78 | 01-MAR-20:10 | 0.373720E+11 | 16686.59 | 01-MAR-07:10 |
April | 0.102384E+10 | 1020.78 | 03-APR-19:10 | 0.361665E+11 | 16686.59 | 01-APR-06:10 |
May | 0.106161E+10 | 1020.78 | 01-MAY-19:10 | 0.373720E+11 | 16686.59 | 01-MAY-06:10 |
June | 0.102854E+10 | 1020.78 | 01-JUN-19:10 | 0.361665E+11 | 16686.59 | 01-JUN-06:10 |
July | 0.105691E+10 | 1020.78 | 03-JUL-19:10 | 0.373720E+11 | 16686.59 | 01-JUL-06:10 |
August | 0.106345E+10 | 1020.78 | 01-AUG-19:10 | 0.373720E+11 | 16686.59 | 01-AUG-06:10 |
September | 0.102425E+10 | 1020.78 | 01-SEP-19:10 | 0.361665E+11 | 16686.59 | 01-SEP-06:10 |
October | 0.105936E+10 | 1020.78 | 02-OCT-19:10 | 0.373720E+11 | 16686.59 | 01-OCT-06:10 |
November | 0.102772E+10 | 1020.78 | 01-NOV-19:10 | 0.361665E+11 | 16686.59 | 01-NOV-06:10 |
December | 0.105691E+10 | 1020.78 | 01-DEC-20:10 | 0.373720E+11 | 16686.59 | 01-DEC-07:10 |
Annual Sum or Average | 0.124823E+11 | 0.440025E+12 | ||||
Minimum of Months | 0.956878E+09 | 1020.78 | 0.337554E+11 | 16686.59 | ||
Maximum of Months | 0.106345E+10 | 1020.78 | 0.373720E+11 | 16686.59 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.140929E+10 | 1357.44 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.127246E+10 | 1357.44 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.141364E+10 | 1357.44 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.136151E+10 | 1357.44 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.141173E+10 | 1357.44 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.136775E+10 | 1357.44 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.140549E+10 | 1357.44 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.141418E+10 | 1357.44 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.136205E+10 | 1357.44 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.140875E+10 | 1357.44 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.136667E+10 | 1357.44 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.140549E+10 | 1357.44 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.165990E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.127246E+10 | 1357.44 | 0.00 | 0.00 | |
Maximum of Months | 0.141418E+10 | 1357.44 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.195762E+11 | 0.140333E+11 | 0.127587E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.176991E+11 | 0.126708E+11 | 0.115208E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.196682E+11 | 0.140766E+11 | 0.127855E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.189781E+11 | 0.135575E+11 | 0.123314E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.196176E+11 | 0.140576E+11 | 0.127741E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.190195E+11 | 0.136197E+11 | 0.123716E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.195762E+11 | 0.139955E+11 | 0.127338E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.196590E+11 | 0.140820E+11 | 0.127894E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.189689E+11 | 0.135629E+11 | 0.123352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.195854E+11 | 0.140279E+11 | 0.127549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.189367E+11 | 0.136089E+11 | 0.123659E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.195762E+11 | 0.139955E+11 | 0.127338E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.230861E+12 | 0.165288E+12 | 0.150255E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.176991E+11 | 0.126708E+11 | 0.115208E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.196682E+11 | 0.140820E+11 | 0.127894E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.199054E+10 | 0.713551E+09 | 0.864900E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 44645897.07 | 0.157740E+09 |
February | 0.179968E+10 | 0.644271E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 69639015.44 | 96006745.50 |
March | 0.199990E+10 | 0.715750E+09 | 0.866718E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100495E+09 | 83073488.68 |
April | 0.192973E+10 | 0.689358E+09 | 0.835931E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168425E+09 | 9790363.41 |
May | 0.199475E+10 | 0.714788E+09 | 0.865939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.292636E+09 | 96878.85 |
June | 0.193394E+10 | 0.692519E+09 | 0.838659E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.347329E+09 | 0.00 |
July | 0.199054E+10 | 0.711626E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.377031E+09 | 0.00 |
August | 0.199896E+10 | 0.716025E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.367784E+09 | 0.00 |
September | 0.192879E+10 | 0.689633E+09 | 0.836191E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.319441E+09 | 0.00 |
October | 0.199148E+10 | 0.713276E+09 | 0.864640E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.264042E+09 | 1675.56 |
November | 0.192552E+10 | 0.691970E+09 | 0.838269E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150431E+09 | 37545309.04 |
December | 0.199054E+10 | 0.711626E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 61220743.61 | 0.127447E+09 |
Annual Sum or Average | 0.234744E+11 | 0.840439E+10 | 0.101856E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.256312E+10 | 0.511702E+09 |
Minimum of Months | 0.179968E+10 | 0.644271E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 44645897.07 | 0.00 |
Maximum of Months | 0.199990E+10 | 0.716025E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.377031E+09 | 0.157740E+09 |
Report: SpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.230505E+10 | 0.826294E+09 | 0.100156E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21094679.63 | 59769494.63 |
February | 0.208403E+10 | 0.746069E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 31243028.15 | 37694480.00 |
March | 0.231589E+10 | 0.828841E+09 | 0.100366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40409446.33 | 32691382.93 |
April | 0.223463E+10 | 0.798279E+09 | 0.968011E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 65071506.84 | 4107781.10 |
May | 0.230993E+10 | 0.827727E+09 | 0.100276E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111584E+09 | 44253.73 |
June | 0.223950E+10 | 0.801940E+09 | 0.971170E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133523E+09 | 0.00 |
July | 0.230505E+10 | 0.824066E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146534E+09 | 0.00 |
August | 0.231480E+10 | 0.829160E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143864E+09 | 0.00 |
September | 0.223354E+10 | 0.798597E+09 | 0.968312E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128768E+09 | 0.00 |
October | 0.230614E+10 | 0.825976E+09 | 0.100126E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109546E+09 | 27.43 |
November | 0.222975E+10 | 0.801303E+09 | 0.970719E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 64469528.73 | 14556003.92 |
December | 0.230505E+10 | 0.824066E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 28680700.03 | 48693995.83 |
Annual Sum or Average | 0.271834E+11 | 0.973232E+10 | 0.117950E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102479E+10 | 0.197557E+09 |
Minimum of Months | 0.208403E+10 | 0.746069E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21094679.63 | 0.00 |
Maximum of Months | 0.231589E+10 | 0.829160E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146534E+09 | 59769494.63 |
Report: SpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.487480E+09 | 0.154452E+10 | 0.105898E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51235721.69 | 0.138484E+09 |
February | 0.440737E+09 | 0.139456E+10 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 75786952.87 | 86613581.84 |
March | 0.489771E+09 | 0.154928E+10 | 0.106120E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 99805659.76 | 75336077.34 |
April | 0.472586E+09 | 0.149215E+10 | 0.102351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160517E+09 | 9005226.42 |
May | 0.488511E+09 | 0.154719E+10 | 0.106025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.269741E+09 | 87968.19 |
June | 0.473617E+09 | 0.149899E+10 | 0.102685E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.318281E+09 | 0.00 |
July | 0.487480E+09 | 0.154035E+10 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.349122E+09 | 0.00 |
August | 0.489542E+09 | 0.154987E+10 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.345427E+09 | 0.00 |
September | 0.472357E+09 | 0.149274E+10 | 0.102382E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.310232E+09 | 0.00 |
October | 0.487709E+09 | 0.154392E+10 | 0.105866E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.267411E+09 | 0.00 |
November | 0.471555E+09 | 0.149780E+10 | 0.102637E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157575E+09 | 33258658.19 |
December | 0.487480E+09 | 0.154035E+10 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 70211218.76 | 0.112357E+09 |
Annual Sum or Average | 0.574883E+10 | 0.181917E+11 | 0.124712E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.247535E+10 | 0.455142E+09 |
Minimum of Months | 0.440737E+09 | 0.139456E+10 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 51235721.69 | 0.00 |
Maximum of Months | 0.489771E+09 | 0.154987E+10 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.349122E+09 | 0.138484E+09 |
Report: SpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.374985E+09 | 0.283535E+09 | 0.305485E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 29826639.80 | 79800516.74 |
February | 0.339028E+09 | 0.256006E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 44142205.00 | 49749377.64 |
March | 0.376747E+09 | 0.284409E+09 | 0.306128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 58360868.55 | 43345180.98 |
April | 0.363528E+09 | 0.273921E+09 | 0.295253E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 93906400.59 | 5148519.48 |
May | 0.375778E+09 | 0.284026E+09 | 0.305852E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157692E+09 | 50779.28 |
June | 0.364321E+09 | 0.275178E+09 | 0.296217E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185881E+09 | 0.00 |
July | 0.374985E+09 | 0.282770E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.203821E+09 | 0.00 |
August | 0.376571E+09 | 0.284518E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.201343E+09 | 0.00 |
September | 0.363352E+09 | 0.274031E+09 | 0.295345E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181094E+09 | 0.00 |
October | 0.375161E+09 | 0.283425E+09 | 0.305393E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156133E+09 | 0.00 |
November | 0.362735E+09 | 0.274959E+09 | 0.296079E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 92047085.72 | 19102422.70 |
December | 0.374985E+09 | 0.282770E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 40950644.75 | 64671470.87 |
Annual Sum or Average | 0.442217E+10 | 0.333955E+10 | 0.359760E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144520E+10 | 0.261868E+09 |
Minimum of Months | 0.339028E+09 | 0.256006E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 29826639.80 | 0.00 |
Maximum of Months | 0.376747E+09 | 0.284518E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.203821E+09 | 79800516.74 |
Report: SpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.154405E+10 | 0.350256E+09 | 0.576866E+10 | 0.501157E+11 | 0.00 | 0.00 | 0.00 | 64391866.68 | 0.210506E+09 |
February | 0.139600E+10 | 0.316249E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 95866387.03 | 0.133870E+09 |
March | 0.155131E+10 | 0.351336E+09 | 0.578079E+10 | 0.502211E+11 | 0.00 | 0.00 | 0.00 | 0.123199E+09 | 0.114948E+09 |
April | 0.149688E+10 | 0.338381E+09 | 0.557545E+10 | 0.484372E+11 | 0.00 | 0.00 | 0.00 | 0.202297E+09 | 16103501.72 |
May | 0.154732E+10 | 0.350863E+09 | 0.577559E+10 | 0.501759E+11 | 0.00 | 0.00 | 0.00 | 0.352728E+09 | 145365.12 |
June | 0.150015E+10 | 0.339933E+09 | 0.559364E+10 | 0.485952E+11 | 0.00 | 0.00 | 0.00 | 0.426756E+09 | 0.00 |
July | 0.154405E+10 | 0.349311E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 0.472375E+09 | 221176.60 |
August | 0.155059E+10 | 0.351471E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 0.460499E+09 | 0.00 |
September | 0.149615E+10 | 0.338516E+09 | 0.557718E+10 | 0.484522E+11 | 0.00 | 0.00 | 0.00 | 0.413441E+09 | 13282.21 |
October | 0.154478E+10 | 0.350121E+09 | 0.576693E+10 | 0.501006E+11 | 0.00 | 0.00 | 0.00 | 0.347577E+09 | 11100.17 |
November | 0.149361E+10 | 0.339663E+09 | 0.559104E+10 | 0.485726E+11 | 0.00 | 0.00 | 0.00 | 0.199702E+09 | 51553522.30 |
December | 0.154405E+10 | 0.349311E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 88855387.80 | 0.172119E+09 |
Annual Sum or Average | 0.182090E+11 | 0.412541E+10 | 0.679355E+11 | 0.590196E+12 | 0.00 | 0.00 | 0.00 | 0.324769E+10 | 0.699491E+09 |
Minimum of Months | 0.139600E+10 | 0.316249E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 64391866.68 | 0.00 |
Maximum of Months | 0.155131E+10 | 0.351471E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 0.472375E+09 | 0.210506E+09 |
Report: SpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.261570E+11 | 0.226040E+10 | 0.121771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 96960621.59 | 0.370772E+09 |
February | 0.236489E+11 | 0.204093E+10 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150561E+09 | 0.232581E+09 |
March | 0.262800E+11 | 0.226736E+10 | 0.122027E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.202602E+09 | 0.197977E+09 |
April | 0.253579E+11 | 0.218376E+10 | 0.117692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.345753E+09 | 28953507.97 |
May | 0.262123E+11 | 0.226431E+10 | 0.121917E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.606351E+09 | 794560.24 |
June | 0.254132E+11 | 0.219377E+10 | 0.118076E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.728152E+09 | 0.00 |
July | 0.261570E+11 | 0.225430E+10 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.803271E+09 | 0.00 |
August | 0.262677E+11 | 0.226823E+10 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.781162E+09 | 0.00 |
September | 0.253456E+11 | 0.218463E+10 | 0.117729E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.683898E+09 | 0.00 |
October | 0.261693E+11 | 0.225952E+10 | 0.121734E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.558331E+09 | 824212.61 |
November | 0.253025E+11 | 0.219203E+10 | 0.118021E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.317929E+09 | 96189335.82 |
December | 0.261570E+11 | 0.225430E+10 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130807E+09 | 0.301805E+09 |
Annual Sum or Average | 0.308468E+12 | 0.266236E+11 | 0.143405E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.540578E+10 | 0.122990E+10 |
Minimum of Months | 0.236489E+11 | 0.204093E+10 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 96960621.59 | 0.00 |
Maximum of Months | 0.262800E+11 | 0.226823E+10 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.803271E+09 | 0.370772E+09 |
Report: SpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.776503E+11 | 0.123020E+11 | 0.126520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.324437E+09 | 0.103667E+10 |
February | 0.702046E+11 | 0.111075E+11 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.481525E+09 | 0.660496E+09 |
March | 0.780153E+11 | 0.123399E+11 | 0.126786E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.613042E+09 | 0.565590E+09 |
April | 0.752779E+11 | 0.118849E+11 | 0.122282E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100781E+10 | 83032375.09 |
May | 0.778146E+11 | 0.123233E+11 | 0.126672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174552E+10 | 2421896.17 |
June | 0.754422E+11 | 0.119394E+11 | 0.122682E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.209988E+10 | 0.00 |
July | 0.776503E+11 | 0.122688E+11 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.231865E+10 | 0.00 |
August | 0.779788E+11 | 0.123446E+11 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.227020E+10 | 0.00 |
September | 0.752414E+11 | 0.118896E+11 | 0.122320E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.202335E+10 | 0.00 |
October | 0.776868E+11 | 0.122972E+11 | 0.126482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.170077E+10 | 1337494.08 |
November | 0.751137E+11 | 0.119299E+11 | 0.122624E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.992923E+09 | 0.269937E+09 |
December | 0.776503E+11 | 0.122688E+11 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.435226E+09 | 0.849278E+09 |
Annual Sum or Average | 0.915726E+12 | 0.144896E+12 | 0.148998E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160133E+11 | 0.346876E+10 |
Minimum of Months | 0.702046E+11 | 0.111075E+11 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.324437E+09 | 0.00 |
Maximum of Months | 0.780153E+11 | 0.123446E+11 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.231865E+10 | 0.103667E+10 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.434056E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21471652.27 | 98310176.11 |
February | 0.273974E+09 | 0.391995E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 32908225.61 | 59567488.82 |
March | 0.303685E+09 | 0.430607E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 46684966.27 | 52727500.53 |
April | 0.293479E+09 | 0.420554E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 81365315.93 | 6798667.60 |
May | 0.303504E+09 | 0.432331E+09 | 0.260888E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151545E+09 | 294438.93 |
June | 0.293842E+09 | 0.417218E+09 | 0.252344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.186005E+09 | 17572.21 |
July | 0.303141E+09 | 0.435725E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205970E+09 | 36552.25 |
August | 0.303685E+09 | 0.430607E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.201495E+09 | 117337.12 |
September | 0.293479E+09 | 0.420667E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179513E+09 | 0.00 |
October | 0.303322E+09 | 0.434000E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148811E+09 | 89292.77 |
November | 0.293661E+09 | 0.418886E+09 | 0.252524E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 81946321.32 | 24197022.74 |
December | 0.303141E+09 | 0.435781E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 31927351.95 | 79925538.02 |
Annual Sum or Average | 0.357224E+10 | 0.510243E+10 | 0.307301E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136964E+10 | 0.322082E+09 |
Minimum of Months | 0.273974E+09 | 0.391995E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21471652.27 | 0.00 |
Maximum of Months | 0.303685E+09 | 0.435781E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205970E+09 | 98310176.11 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.434005E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 22648199.99 | 94762724.16 |
February | 0.273974E+09 | 0.391949E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 34083509.87 | 58290909.85 |
March | 0.303685E+09 | 0.430556E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 47288873.43 | 51456699.14 |
April | 0.293479E+09 | 0.420505E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 81564436.75 | 6745032.86 |
May | 0.303504E+09 | 0.432281E+09 | 0.260857E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151507E+09 | 295133.15 |
June | 0.293842E+09 | 0.417169E+09 | 0.252315E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185915E+09 | 17574.28 |
July | 0.303141E+09 | 0.435674E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205909E+09 | 36904.87 |
August | 0.303685E+09 | 0.430556E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.201512E+09 | 113751.78 |
September | 0.293479E+09 | 0.420618E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179671E+09 | 0.00 |
October | 0.303322E+09 | 0.433949E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149240E+09 | 80076.30 |
November | 0.293661E+09 | 0.418837E+09 | 0.252495E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 82876903.68 | 23628671.06 |
December | 0.303141E+09 | 0.435730E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 32813034.22 | 77132126.49 |
Annual Sum or Average | 0.357224E+10 | 0.510183E+10 | 0.307265E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137503E+10 | 0.312560E+09 |
Minimum of Months | 0.273974E+09 | 0.391949E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 22648199.99 | 0.00 |
Maximum of Months | 0.303685E+09 | 0.435730E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205909E+09 | 94762724.16 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.272788E+09 | 0.255708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2961711.86 | 40156187.93 |
February | 0.00 | 0.246354E+09 | 0.230956E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4502982.25 | 25850631.05 |
March | 0.00 | 0.270620E+09 | 0.255355E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5470177.50 | 22547440.48 |
April | 0.00 | 0.264302E+09 | 0.247516E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12667654.52 | 6328049.87 |
May | 0.00 | 0.271704E+09 | 0.255532E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 28316427.91 | 799395.15 |
June | 0.00 | 0.262205E+09 | 0.247163E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 37784382.01 | 7264.87 |
July | 0.00 | 0.273836E+09 | 0.255885E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 43045147.21 | 113849.83 |
August | 0.00 | 0.270620E+09 | 0.255355E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 41728816.36 | 118763.31 |
September | 0.00 | 0.264373E+09 | 0.247516E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 36051781.47 | 51364.94 |
October | 0.00 | 0.272752E+09 | 0.255708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 27569033.17 | 696806.28 |
November | 0.00 | 0.263254E+09 | 0.247340E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14080198.92 | 12522152.50 |
December | 0.00 | 0.273872E+09 | 0.255885E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4383774.47 | 33429656.05 |
Annual Sum or Average | 0.00 | 0.320668E+10 | 0.300992E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258562E+09 | 0.142622E+09 |
Minimum of Months | 0.00 | 0.246354E+09 | 0.230956E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2961711.86 | 7264.87 |
Maximum of Months | 0.00 | 0.273872E+09 | 0.255885E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 43045147.21 | 40156187.93 |
Report: SpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.272862E+09 | 0.255778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6959432.70 | 26337319.10 |
February | 0.273974E+09 | 0.246421E+09 | 0.231020E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10402598.47 | 16279071.46 |
March | 0.303685E+09 | 0.270694E+09 | 0.255425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14043190.43 | 14255936.39 |
April | 0.293479E+09 | 0.264375E+09 | 0.247584E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 23630031.21 | 1822995.09 |
May | 0.303504E+09 | 0.271778E+09 | 0.255602E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 42765779.22 | 63687.16 |
June | 0.293842E+09 | 0.262277E+09 | 0.247231E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 52246379.44 | 4692.71 |
July | 0.303141E+09 | 0.273911E+09 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 57783576.22 | 7377.84 |
August | 0.303685E+09 | 0.270694E+09 | 0.255425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 56696257.87 | 13355.94 |
September | 0.293479E+09 | 0.264446E+09 | 0.247584E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 50597640.06 | 0.00 |
October | 0.303322E+09 | 0.272827E+09 | 0.255778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 42354710.48 | 17665.71 |
November | 0.293661E+09 | 0.263326E+09 | 0.247408E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 23982400.37 | 6530020.88 |
December | 0.303141E+09 | 0.273947E+09 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9803992.48 | 21412505.92 |
Annual Sum or Average | 0.357224E+10 | 0.320756E+10 | 0.301074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.391266E+09 | 86744628.19 |
Minimum of Months | 0.273974E+09 | 0.246421E+09 | 0.231020E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6959432.70 | 0.00 |
Maximum of Months | 0.303685E+09 | 0.273947E+09 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 57783576.22 | 26337319.10 |
Report: SpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.434056E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21267325.92 | 99534580.70 |
February | 0.273974E+09 | 0.391995E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 32680498.69 | 60458981.08 |
March | 0.303685E+09 | 0.430607E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 46360884.16 | 54294937.66 |
April | 0.293479E+09 | 0.420554E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 80837961.58 | 7133933.34 |
May | 0.303504E+09 | 0.432331E+09 | 0.260888E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151073E+09 | 305529.61 |
June | 0.293842E+09 | 0.417218E+09 | 0.252344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185524E+09 | 17584.66 |
July | 0.303141E+09 | 0.435725E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205593E+09 | 38325.78 |
August | 0.303685E+09 | 0.430607E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.201185E+09 | 122003.72 |
September | 0.293479E+09 | 0.420667E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179101E+09 | 0.00 |
October | 0.303322E+09 | 0.434000E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148426E+09 | 115716.81 |
November | 0.293661E+09 | 0.418886E+09 | 0.252524E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 81682828.43 | 24614946.35 |
December | 0.303141E+09 | 0.435781E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 31811710.23 | 80253934.44 |
Annual Sum or Average | 0.357224E+10 | 0.510243E+10 | 0.307301E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136554E+10 | 0.326890E+09 |
Minimum of Months | 0.273974E+09 | 0.391995E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21267325.92 | 0.00 |
Maximum of Months | 0.303685E+09 | 0.435781E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205593E+09 | 99534580.70 |
Report: SpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.434005E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21906020.56 | 95796392.60 |
February | 0.273974E+09 | 0.391949E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 33117960.34 | 59168845.47 |
March | 0.303685E+09 | 0.430556E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 46536822.22 | 53170467.48 |
April | 0.293479E+09 | 0.420505E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 80902040.46 | 7107517.33 |
May | 0.303504E+09 | 0.432281E+09 | 0.260857E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151050E+09 | 306596.72 |
June | 0.293842E+09 | 0.417169E+09 | 0.252315E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185480E+09 | 17583.90 |
July | 0.303141E+09 | 0.435674E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205557E+09 | 38679.08 |
August | 0.303685E+09 | 0.430556E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.201191E+09 | 118498.97 |
September | 0.293479E+09 | 0.420618E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179173E+09 | 0.00 |
October | 0.303322E+09 | 0.433949E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148646E+09 | 108038.63 |
November | 0.293661E+09 | 0.418837E+09 | 0.252495E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 82328518.10 | 24101502.95 |
December | 0.303141E+09 | 0.435730E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 32610539.85 | 76890016.33 |
Annual Sum or Average | 0.357224E+10 | 0.510183E+10 | 0.307265E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136850E+10 | 0.316824E+09 |
Minimum of Months | 0.273974E+09 | 0.391949E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21906020.56 | 0.00 |
Maximum of Months | 0.303685E+09 | 0.435730E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205557E+09 | 95796392.60 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.385223E+10 | 0.133160E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31798537.74 | 0.114267E+09 |
February | 0.348285E+10 | 0.120231E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47933247.15 | 72753097.73 |
March | 0.387034E+10 | 0.133570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60394202.69 | 62132797.68 |
April | 0.373454E+10 | 0.128645E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98025620.20 | 10518975.56 |
May | 0.386038E+10 | 0.133391E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.173841E+09 | 399019.61 |
June | 0.374269E+10 | 0.129235E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.208698E+09 | 0.00 |
July | 0.385223E+10 | 0.132801E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.229149E+09 | 0.00 |
August | 0.386853E+10 | 0.133622E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.225564E+09 | 0.00 |
September | 0.373273E+10 | 0.128696E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.197954E+09 | 0.00 |
October | 0.385404E+10 | 0.133109E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162998E+09 | 379869.33 |
November | 0.372639E+10 | 0.129132E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96867587.78 | 32024074.34 |
December | 0.385223E+10 | 0.132801E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42023593.01 | 93577480.21 |
Annual Sum or Average | 0.454292E+11 | 0.156839E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157525E+10 | 0.386053E+09 |
Minimum of Months | 0.348285E+10 | 0.120231E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31798537.74 | 0.00 |
Maximum of Months | 0.387034E+10 | 0.133622E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.229149E+09 | 0.114267E+09 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.434056E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20734531.83 | 99621842.58 |
February | 0.273974E+09 | 0.391995E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 31876009.19 | 60361118.46 |
March | 0.303685E+09 | 0.430607E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 45311386.78 | 53472815.37 |
April | 0.293479E+09 | 0.420554E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 79555515.00 | 7029669.84 |
May | 0.303504E+09 | 0.432331E+09 | 0.260888E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149474E+09 | 338711.29 |
June | 0.293842E+09 | 0.417218E+09 | 0.252344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183992E+09 | 21119.09 |
July | 0.303141E+09 | 0.435725E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.203918E+09 | 44718.08 |
August | 0.303685E+09 | 0.430607E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.199457E+09 | 141416.74 |
September | 0.293479E+09 | 0.420667E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.177564E+09 | 0.00 |
October | 0.303322E+09 | 0.434000E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146838E+09 | 96511.33 |
November | 0.293661E+09 | 0.418886E+09 | 0.252524E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 80446900.64 | 24605979.55 |
December | 0.303141E+09 | 0.435781E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 31039862.62 | 80953842.49 |
Annual Sum or Average | 0.357224E+10 | 0.510243E+10 | 0.307301E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135021E+10 | 0.326688E+09 |
Minimum of Months | 0.273974E+09 | 0.391995E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20734531.83 | 0.00 |
Maximum of Months | 0.303685E+09 | 0.435781E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.203918E+09 | 99621842.58 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.434005E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21602221.59 | 96160904.09 |
February | 0.273974E+09 | 0.391949E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 32685019.09 | 59034792.60 |
March | 0.303685E+09 | 0.430556E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 45664279.41 | 52183827.52 |
April | 0.293479E+09 | 0.420505E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 79683259.80 | 6986478.87 |
May | 0.303504E+09 | 0.432281E+09 | 0.260857E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149437E+09 | 339242.60 |
June | 0.293842E+09 | 0.417169E+09 | 0.252315E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183913E+09 | 21117.56 |
July | 0.303141E+09 | 0.435674E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.203864E+09 | 45067.94 |
August | 0.303685E+09 | 0.430556E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.199466E+09 | 138900.55 |
September | 0.293479E+09 | 0.420618E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.177695E+09 | 0.00 |
October | 0.303322E+09 | 0.433949E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147224E+09 | 87861.58 |
November | 0.293661E+09 | 0.418837E+09 | 0.252495E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 81244277.74 | 24054754.82 |
December | 0.303141E+09 | 0.435730E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 31670850.86 | 78060266.84 |
Annual Sum or Average | 0.357224E+10 | 0.510183E+10 | 0.307265E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135415E+10 | 0.317113E+09 |
Minimum of Months | 0.273974E+09 | 0.391949E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21602221.59 | 0.00 |
Maximum of Months | 0.303685E+09 | 0.435730E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.203864E+09 | 96160904.09 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.272862E+09 | 0.255778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10413852.17 | 52096074.53 |
February | 0.273974E+09 | 0.246421E+09 | 0.231020E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16096565.39 | 31517910.88 |
March | 0.303685E+09 | 0.270694E+09 | 0.255425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 23097174.88 | 27860300.78 |
April | 0.293479E+09 | 0.264375E+09 | 0.247584E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 40753064.27 | 3589432.63 |
May | 0.303504E+09 | 0.271778E+09 | 0.255602E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 76586770.54 | 168352.71 |
June | 0.293842E+09 | 0.262277E+09 | 0.247231E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 94218845.07 | 10796.50 |
July | 0.303141E+09 | 0.273911E+09 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104405E+09 | 21055.24 |
August | 0.303685E+09 | 0.270694E+09 | 0.255425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102105E+09 | 65583.60 |
September | 0.293479E+09 | 0.264446E+09 | 0.247584E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 90734279.50 | 0.00 |
October | 0.303322E+09 | 0.272827E+09 | 0.255778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 74850081.89 | 58774.92 |
November | 0.293661E+09 | 0.263326E+09 | 0.247408E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 40891678.05 | 12946861.79 |
December | 0.303141E+09 | 0.273947E+09 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15685850.43 | 42472412.11 |
Annual Sum or Average | 0.357224E+10 | 0.320756E+10 | 0.301074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.689838E+09 | 0.170808E+09 |
Minimum of Months | 0.273974E+09 | 0.246421E+09 | 0.231020E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10413852.17 | 0.00 |
Maximum of Months | 0.303685E+09 | 0.273947E+09 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104405E+09 | 52096074.53 |
Report: SpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.396945E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 65754793.47 | 0.257790E+09 |
February | 0.415303E+11 | 0.358405E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 96277981.41 | 0.167539E+09 |
March | 0.461508E+11 | 0.398168E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117032E+09 | 0.143469E+09 |
April | 0.445315E+11 | 0.383486E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.196082E+09 | 27888103.91 |
May | 0.460320E+11 | 0.397633E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.348027E+09 | 1964380.45 |
June | 0.446286E+11 | 0.385245E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.425497E+09 | 2581.76 |
July | 0.459349E+11 | 0.395874E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.472953E+09 | 102855.47 |
August | 0.461292E+11 | 0.398321E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.464605E+09 | 0.00 |
September | 0.445099E+11 | 0.383639E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.414703E+09 | 13430.70 |
October | 0.459565E+11 | 0.396792E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.347475E+09 | 1406749.73 |
November | 0.444343E+11 | 0.384939E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.202776E+09 | 72719719.00 |
December | 0.459349E+11 | 0.395874E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 86984832.19 | 0.212052E+09 |
Annual Sum or Average | 0.541708E+12 | 0.467532E+11 | 0.175857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.323817E+10 | 0.884948E+09 |
Minimum of Months | 0.415303E+11 | 0.358405E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 65754793.47 | 0.00 |
Maximum of Months | 0.461508E+11 | 0.398321E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.472953E+09 | 0.257790E+09 |
Report: SpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.396945E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 64314342.17 | 0.261115E+09 |
February | 0.415303E+11 | 0.358405E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 93939588.33 | 0.170051E+09 |
March | 0.461508E+11 | 0.398168E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113313E+09 | 0.145620E+09 |
April | 0.445315E+11 | 0.383486E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.191205E+09 | 29063412.25 |
May | 0.460320E+11 | 0.397633E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.341968E+09 | 2090603.81 |
June | 0.446286E+11 | 0.385245E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.420193E+09 | 5386.13 |
July | 0.459349E+11 | 0.395874E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.468131E+09 | 125489.63 |
August | 0.461292E+11 | 0.398321E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.459461E+09 | 0.00 |
September | 0.445099E+11 | 0.383639E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.410088E+09 | 23183.88 |
October | 0.459565E+11 | 0.396792E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.342518E+09 | 1498875.59 |
November | 0.444343E+11 | 0.384939E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.199002E+09 | 74166211.15 |
December | 0.459349E+11 | 0.395874E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 84711581.55 | 0.214874E+09 |
Annual Sum or Average | 0.541708E+12 | 0.467532E+11 | 0.175857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.318885E+10 | 0.898632E+09 |
Minimum of Months | 0.415303E+11 | 0.358405E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 64314342.17 | 0.00 |
Maximum of Months | 0.461508E+11 | 0.398321E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.468131E+09 | 0.261115E+09 |
Report: SpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.408770E+10 | 0.105977E+10 | 0.338870E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 19034666.72 | 0.293937E+09 |
February | 0.369574E+10 | 0.956878E+09 | 0.306077E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 31267938.27 | 0.185774E+09 |
March | 0.410691E+10 | 0.106304E+10 | 0.338870E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 43010759.13 | 0.164492E+09 |
April | 0.396281E+10 | 0.102384E+10 | 0.327939E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 95602531.74 | 35646985.55 |
May | 0.409635E+10 | 0.106161E+10 | 0.338870E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.225654E+09 | 2839142.42 |
June | 0.397146E+10 | 0.102854E+10 | 0.327939E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 0.300680E+09 | 356600.34 |
July | 0.408770E+10 | 0.105691E+10 | 0.338870E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.342615E+09 | 1238742.69 |
August | 0.410499E+10 | 0.106345E+10 | 0.338870E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.333234E+09 | 1407046.34 |
September | 0.396089E+10 | 0.102425E+10 | 0.327939E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 0.288006E+09 | 608892.61 |
October | 0.408962E+10 | 0.105936E+10 | 0.338870E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.221010E+09 | 2191767.56 |
November | 0.395417E+10 | 0.102772E+10 | 0.327939E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 0.106717E+09 | 82961479.94 |
December | 0.408770E+10 | 0.105691E+10 | 0.338870E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 32356974.68 | 0.243988E+09 |
Annual Sum or Average | 0.482060E+11 | 0.124823E+11 | 0.398993E+12 | 0.359593E+12 | 0.00 | 0.00 | 0.00 | 0.203919E+10 | 0.101544E+10 |
Minimum of Months | 0.369574E+10 | 0.956878E+09 | 0.306077E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 19034666.72 | 356600.34 |
Maximum of Months | 0.410691E+10 | 0.106345E+10 | 0.338870E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.342615E+09 | 0.293937E+09 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.407704E+10 | 0.140929E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64483603.01 | 0.193202E+09 |
February | 0.368610E+10 | 0.127246E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96281430.14 | 0.120437E+09 |
March | 0.409620E+10 | 0.141364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127046E+09 | 0.104513E+09 |
April | 0.395248E+10 | 0.136151E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.202775E+09 | 12896772.28 |
May | 0.408566E+10 | 0.141173E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.341184E+09 | 164615.37 |
June | 0.396110E+10 | 0.136775E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.399611E+09 | 0.00 |
July | 0.407704E+10 | 0.140549E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.434380E+09 | 0.00 |
August | 0.409429E+10 | 0.141418E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.433600E+09 | 0.00 |
September | 0.395056E+10 | 0.136205E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.384923E+09 | 0.00 |
October | 0.407896E+10 | 0.140875E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.332499E+09 | 573.58 |
November | 0.394385E+10 | 0.136667E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.198252E+09 | 46797546.48 |
December | 0.407704E+10 | 0.140549E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87258858.83 | 0.156839E+09 |
Annual Sum or Average | 0.480803E+11 | 0.165990E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.310229E+10 | 0.634850E+09 |
Minimum of Months | 0.368610E+10 | 0.127246E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64483603.01 | 0.00 |
Maximum of Months | 0.409620E+10 | 0.141418E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.434380E+09 | 0.193202E+09 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 11501.89 | 02-JAN-00:10 | 13517.00 | 02-JAN-20:10 | 10113.80 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 11501.89 | 01-FEB-00:10 | 13517.00 | 01-FEB-20:10 | 10113.80 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 11501.89 | 01-MAR-00:10 | 13517.00 | 01-MAR-20:10 | 10113.80 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 11501.89 | 01-APR-00:10 | 13517.00 | 03-APR-19:10 | 10113.80 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 11501.89 | 01-MAY-00:10 | 13517.00 | 01-MAY-19:10 | 10113.80 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 11501.89 | 01-JUN-00:10 | 13517.00 | 01-JUN-19:10 | 10113.80 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 11501.89 | 01-JUL-00:10 | 13517.00 | 03-JUL-19:10 | 10113.80 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 11501.89 | 01-AUG-00:10 | 13517.00 | 01-AUG-19:10 | 10113.80 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 11501.89 | 01-SEP-00:10 | 13517.00 | 01-SEP-19:10 | 10113.80 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 11501.89 | 01-OCT-23:10 | 13517.00 | 02-OCT-19:10 | 10113.80 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 11501.89 | 01-NOV-00:10 | 13517.00 | 01-NOV-19:10 | 10113.80 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 11501.89 | 01-DEC-00:10 | 13517.00 | 01-DEC-20:10 | 10113.80 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 11501.89 | 13517.00 | 10113.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 11501.89 | 13517.00 | 10113.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1169.53 | 02-JAN-00:10 | 687.30 | 02-JAN-20:10 | 685.60 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 136.77 | 07-JAN-15:00 | 260.25 | 25-JAN-06:50 |
February | 1169.53 | 01-FEB-00:10 | 687.30 | 01-FEB-20:10 | 685.60 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 143.45 | 02-FEB-14:00 | 363.76 | 04-FEB-07:00 |
March | 1169.53 | 01-MAR-00:10 | 687.30 | 01-MAR-20:10 | 685.60 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 156.19 | 13-MAR-16:00 | 323.10 | 16-MAR-07:00 |
April | 1169.53 | 01-APR-00:10 | 687.30 | 03-APR-19:10 | 685.60 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 210.51 | 17-APR-15:00 | 144.62 | 02-APR-05:40 |
May | 1169.53 | 01-MAY-00:10 | 687.30 | 01-MAY-19:10 | 685.60 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 258.29 | 22-MAY-13:00 | 8.76 | 01-MAY-06:00 |
June | 1169.53 | 01-JUN-00:10 | 687.30 | 01-JUN-19:10 | 685.60 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 220.80 | 11-JUN-13:00 | 0.00 | 01-JUN-00:10 |
July | 1169.53 | 01-JUL-00:10 | 687.30 | 03-JUL-19:10 | 685.60 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 277.81 | 29-JUL-16:00 | 0.00 | 01-JUL-00:10 |
August | 1169.53 | 01-AUG-00:10 | 687.30 | 01-AUG-19:10 | 685.60 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 240.11 | 08-AUG-11:00 | 0.00 | 01-AUG-00:10 |
September | 1169.53 | 01-SEP-00:10 | 687.30 | 01-SEP-19:10 | 685.60 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 209.65 | 08-SEP-16:00 | 0.00 | 01-SEP-00:10 |
October | 1169.53 | 01-OCT-23:10 | 687.30 | 02-OCT-19:10 | 685.60 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 206.00 | 09-OCT-11:00 | 2.79 | 26-OCT-14:00 |
November | 1169.53 | 01-NOV-00:10 | 687.30 | 01-NOV-19:10 | 685.60 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 142.86 | 04-NOV-10:50 | 245.24 | 27-NOV-06:40 |
December | 1169.53 | 01-DEC-00:10 | 687.30 | 01-DEC-20:10 | 685.60 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 125.11 | 24-DEC-14:00 | 297.92 | 15-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1169.53 | 687.30 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 125.11 | 0.00 | |||||
Maximum of Months | 1169.53 | 687.30 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 277.81 | 363.76 |
Report: PeakSpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1354.32 | 02-JAN-00:10 | 795.89 | 02-JAN-20:10 | 793.93 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 63.79 | 02-JAN-14:00 | 100.47 | 25-JAN-07:00 |
February | 1354.32 | 01-FEB-00:10 | 795.89 | 01-FEB-20:10 | 793.93 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.75 | 11-FEB-14:00 | 141.00 | 04-FEB-07:00 |
March | 1354.32 | 01-MAR-00:10 | 795.89 | 01-MAR-20:10 | 793.93 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.11 | 13-MAR-16:00 | 124.69 | 16-MAR-07:00 |
April | 1354.32 | 01-APR-00:10 | 795.89 | 03-APR-19:10 | 793.93 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 88.68 | 17-APR-15:00 | 55.82 | 02-APR-06:00 |
May | 1354.32 | 01-MAY-00:10 | 795.89 | 01-MAY-19:10 | 793.93 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 105.55 | 22-MAY-13:00 | 4.31 | 07-MAY-06:00 |
June | 1354.32 | 01-JUN-00:10 | 795.89 | 01-JUN-19:10 | 793.93 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 89.32 | 11-JUN-13:00 | 0.00 | 01-JUN-00:10 |
July | 1354.32 | 01-JUL-00:10 | 795.89 | 03-JUL-19:10 | 793.93 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 114.37 | 29-JUL-16:00 | 0.00 | 01-JUL-00:10 |
August | 1354.32 | 01-AUG-00:10 | 795.89 | 01-AUG-19:10 | 793.93 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 102.25 | 23-AUG-13:00 | 0.00 | 01-AUG-00:10 |
September | 1354.32 | 01-SEP-00:10 | 795.89 | 01-SEP-19:10 | 793.93 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 89.09 | 13-SEP-13:00 | 0.00 | 01-SEP-00:10 |
October | 1354.32 | 01-OCT-23:10 | 795.89 | 02-OCT-19:10 | 793.93 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 89.07 | 09-OCT-11:00 | 0.05 | 28-OCT-03:00 |
November | 1354.32 | 01-NOV-00:10 | 795.89 | 01-NOV-19:10 | 793.93 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 71.97 | 17-NOV-15:00 | 94.68 | 27-NOV-07:00 |
December | 1354.32 | 01-DEC-00:10 | 795.89 | 01-DEC-20:10 | 793.93 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 63.27 | 10-DEC-14:10 | 115.02 | 15-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1354.32 | 795.89 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 63.27 | 0.00 | |||||
Maximum of Months | 1354.32 | 795.89 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 114.37 | 141.00 |
Report: PeakSpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 286.42 | 02-JAN-00:10 | 1487.69 | 02-JAN-20:10 | 839.45 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 150.79 | 02-JAN-14:00 | 237.40 | 25-JAN-06:50 |
February | 286.42 | 01-FEB-00:10 | 1487.69 | 01-FEB-20:10 | 839.45 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 160.16 | 11-FEB-14:00 | 333.24 | 04-FEB-07:00 |
March | 286.42 | 01-MAR-00:10 | 1487.69 | 01-MAR-20:10 | 839.45 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 158.65 | 13-MAR-16:00 | 294.69 | 16-MAR-07:00 |
April | 286.42 | 01-APR-00:10 | 1487.69 | 03-APR-19:10 | 839.45 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 209.61 | 17-APR-15:00 | 131.91 | 02-APR-05:50 |
May | 286.42 | 01-MAY-00:10 | 1487.69 | 01-MAY-19:10 | 839.45 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 249.45 | 22-MAY-13:00 | 7.91 | 01-MAY-05:30 |
June | 286.42 | 01-JUN-00:10 | 1487.69 | 01-JUN-19:10 | 839.45 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 210.72 | 11-JUN-13:00 | 0.00 | 01-JUN-00:10 |
July | 286.42 | 01-JUL-00:10 | 1487.69 | 03-JUL-19:10 | 839.45 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 270.28 | 29-JUL-16:00 | 0.00 | 01-JUL-00:10 |
August | 286.42 | 01-AUG-00:10 | 1487.69 | 01-AUG-19:10 | 839.45 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 240.72 | 23-AUG-13:00 | 0.00 | 01-AUG-00:10 |
September | 286.42 | 01-SEP-00:10 | 1487.69 | 01-SEP-19:10 | 839.45 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 210.54 | 13-SEP-13:00 | 0.00 | 01-SEP-00:10 |
October | 286.42 | 01-OCT-23:10 | 1487.69 | 02-OCT-19:10 | 839.45 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 210.50 | 09-OCT-11:00 | 0.00 | 01-OCT-00:10 |
November | 286.42 | 01-NOV-00:10 | 1487.69 | 01-NOV-19:10 | 839.45 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 170.31 | 17-NOV-15:00 | 223.75 | 27-NOV-07:00 |
December | 286.42 | 01-DEC-00:10 | 1487.69 | 01-DEC-20:10 | 839.45 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 149.50 | 10-DEC-14:10 | 271.75 | 15-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 286.42 | 1487.69 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 149.50 | 0.00 | |||||
Maximum of Months | 286.42 | 1487.69 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 270.28 | 333.24 |
Report: PeakSpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 220.32 | 02-JAN-00:10 | 273.10 | 02-JAN-20:10 | 242.16 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 87.00 | 02-JAN-14:00 | 136.97 | 25-JAN-07:00 |
February | 220.32 | 01-FEB-00:10 | 273.10 | 01-FEB-20:10 | 242.16 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 92.40 | 11-FEB-14:00 | 192.25 | 04-FEB-07:00 |
March | 220.32 | 01-MAR-00:10 | 273.10 | 01-MAR-20:10 | 242.16 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 91.54 | 13-MAR-16:00 | 169.99 | 16-MAR-07:00 |
April | 220.32 | 01-APR-00:10 | 273.10 | 03-APR-19:10 | 242.16 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 120.92 | 17-APR-15:00 | 76.10 | 02-APR-05:40 |
May | 220.32 | 01-MAY-00:10 | 273.10 | 01-MAY-19:10 | 242.16 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 143.92 | 22-MAY-13:00 | 4.57 | 01-MAY-05:30 |
June | 220.32 | 01-JUN-00:10 | 273.10 | 01-JUN-19:10 | 242.16 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 121.28 | 11-JUN-13:00 | 0.00 | 01-JUN-00:10 |
July | 220.32 | 01-JUL-00:10 | 273.10 | 03-JUL-19:10 | 242.16 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 155.34 | 29-JUL-16:00 | 0.00 | 01-JUL-00:10 |
August | 220.32 | 01-AUG-00:10 | 273.10 | 01-AUG-19:10 | 242.16 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 138.61 | 23-AUG-13:00 | 0.00 | 01-AUG-00:10 |
September | 220.32 | 01-SEP-00:10 | 273.10 | 01-SEP-19:10 | 242.16 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 121.47 | 13-SEP-13:00 | 0.00 | 01-SEP-00:10 |
October | 220.32 | 01-OCT-23:10 | 273.10 | 02-OCT-19:10 | 242.16 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 121.43 | 09-OCT-11:00 | 0.00 | 01-OCT-00:10 |
November | 220.32 | 01-NOV-00:10 | 273.10 | 01-NOV-19:10 | 242.16 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 98.25 | 17-NOV-15:00 | 129.09 | 27-NOV-07:00 |
December | 220.32 | 01-DEC-00:10 | 273.10 | 01-DEC-20:10 | 242.16 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 86.25 | 10-DEC-14:00 | 156.81 | 15-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 220.32 | 273.10 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 86.25 | 0.00 | |||||
Maximum of Months | 220.32 | 273.10 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 155.34 | 192.25 |
Report: PeakSpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 907.20 | 02-JAN-00:10 | 337.37 | 02-JAN-20:10 | 4572.80 | 02-JAN-20:10 | 39726.58 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 206.09 | 02-JAN-14:00 | 341.03 | 24-JAN-22:00 |
February | 907.20 | 01-FEB-00:10 | 337.37 | 01-FEB-20:10 | 4572.80 | 01-FEB-20:10 | 39726.58 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 218.84 | 11-FEB-14:00 | 454.94 | 04-FEB-07:00 |
March | 907.20 | 01-MAR-00:10 | 337.37 | 01-MAR-20:10 | 4572.80 | 01-MAR-20:10 | 39726.58 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 216.74 | 13-MAR-16:00 | 415.36 | 16-MAR-07:00 |
April | 907.20 | 01-APR-00:10 | 337.37 | 03-APR-19:10 | 4572.80 | 03-APR-19:10 | 39726.58 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 286.06 | 17-APR-15:00 | 180.19 | 02-APR-06:00 |
May | 907.20 | 01-MAY-00:10 | 337.37 | 01-MAY-19:10 | 4572.80 | 01-MAY-19:10 | 39726.58 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 340.49 | 22-MAY-13:00 | 17.78 | 01-MAY-06:10 |
June | 907.20 | 01-JUN-00:10 | 337.37 | 01-JUN-19:10 | 4572.80 | 01-JUN-19:10 | 39726.58 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 288.31 | 11-JUN-13:00 | 0.00 | 01-JUN-00:10 |
July | 907.20 | 01-JUL-00:10 | 337.37 | 03-JUL-19:10 | 4572.80 | 03-JUL-19:10 | 39726.58 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 369.00 | 29-JUL-16:00 | 31.29 | 14-JUL-20:00 |
August | 907.20 | 01-AUG-00:10 | 337.37 | 01-AUG-19:10 | 4572.80 | 01-AUG-19:10 | 39726.58 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 330.01 | 23-AUG-13:00 | 0.00 | 01-AUG-00:10 |
September | 907.20 | 01-SEP-00:10 | 337.37 | 01-SEP-19:10 | 4572.80 | 01-SEP-19:10 | 39726.58 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 287.76 | 13-SEP-13:10 | 2.90 | 05-SEP-21:00 |
October | 907.20 | 01-OCT-23:10 | 337.37 | 02-OCT-19:10 | 4572.80 | 02-OCT-19:10 | 39726.58 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 288.94 | 09-OCT-11:00 | 2.93 | 27-OCT-21:00 |
November | 907.20 | 01-NOV-00:10 | 337.37 | 01-NOV-19:10 | 4572.80 | 01-NOV-19:10 | 39726.58 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 232.47 | 17-NOV-15:00 | 305.64 | 27-NOV-06:00 |
December | 907.20 | 01-DEC-00:10 | 337.37 | 01-DEC-20:10 | 4572.80 | 01-DEC-20:10 | 39726.58 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 204.12 | 10-DEC-14:20 | 377.14 | 15-DEC-07:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 907.20 | 337.37 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 204.12 | 0.00 | ||||||
Maximum of Months | 907.20 | 337.37 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 369.00 | 454.94 |
Report: PeakSpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 15368.40 | 02-JAN-00:10 | 2177.23 | 02-JAN-20:10 | 965.27 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 316.40 | 07-JAN-13:00 | 580.39 | 25-JAN-05:20 |
February | 15368.40 | 01-FEB-00:10 | 2177.23 | 01-FEB-20:10 | 965.27 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 337.02 | 02-FEB-14:00 | 807.73 | 04-FEB-07:00 |
March | 15368.40 | 01-MAR-00:10 | 2177.23 | 01-MAR-20:10 | 965.27 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 354.04 | 13-MAR-16:00 | 714.29 | 16-MAR-07:00 |
April | 15368.40 | 01-APR-00:10 | 2177.23 | 03-APR-19:10 | 965.27 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 489.34 | 17-APR-15:00 | 319.92 | 02-APR-05:40 |
May | 15368.40 | 01-MAY-00:10 | 2177.23 | 01-MAY-19:10 | 965.27 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 601.15 | 22-MAY-13:00 | 51.64 | 01-MAY-05:00 |
June | 15368.40 | 01-JUN-00:10 | 2177.23 | 01-JUN-19:10 | 965.27 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 511.38 | 11-JUN-13:00 | 0.00 | 01-JUN-00:10 |
July | 15368.40 | 01-JUL-00:10 | 2177.23 | 03-JUL-19:10 | 965.27 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 652.34 | 29-JUL-16:00 | 0.00 | 01-JUL-00:10 |
August | 15368.40 | 01-AUG-00:10 | 2177.23 | 01-AUG-19:10 | 965.27 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 565.04 | 23-AUG-13:00 | 0.00 | 01-AUG-00:10 |
September | 15368.40 | 01-SEP-00:10 | 2177.23 | 01-SEP-19:10 | 965.27 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 489.44 | 13-SEP-13:00 | 0.00 | 01-SEP-00:10 |
October | 15368.40 | 01-OCT-23:10 | 2177.23 | 02-OCT-19:10 | 965.27 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 482.69 | 09-OCT-11:00 | 38.41 | 28-OCT-03:00 |
November | 15368.40 | 01-NOV-00:10 | 2177.23 | 01-NOV-19:10 | 965.27 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 349.71 | 17-NOV-15:00 | 555.38 | 27-NOV-03:00 |
December | 15368.40 | 01-DEC-00:10 | 2177.23 | 01-DEC-20:10 | 965.27 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 295.57 | 10-DEC-14:00 | 662.51 | 15-DEC-05:20 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 15368.40 | 2177.23 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 295.57 | 0.00 | |||||
Maximum of Months | 15368.40 | 2177.23 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 652.34 | 807.73 |
Report: PeakSpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 45622.98 | 02-JAN-00:10 | 11849.32 | 02-JAN-20:10 | 10029.21 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1039.37 | 02-JAN-14:00 | 1681.06 | 25-JAN-05:40 |
February | 45622.98 | 01-FEB-00:10 | 11849.32 | 01-FEB-20:10 | 10029.21 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1078.91 | 11-FEB-14:00 | 2307.35 | 04-FEB-07:00 |
March | 45622.98 | 01-MAR-00:10 | 11849.32 | 01-MAR-20:10 | 10029.21 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1098.60 | 13-MAR-16:00 | 2064.48 | 16-MAR-05:00 |
April | 45622.98 | 01-APR-00:10 | 11849.32 | 03-APR-19:10 | 10029.21 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1451.34 | 17-APR-15:00 | 948.60 | 02-APR-05:30 |
May | 45622.98 | 01-MAY-00:10 | 11849.32 | 01-MAY-19:10 | 10029.21 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1726.82 | 22-MAY-13:00 | 144.22 | 01-MAY-05:00 |
June | 45622.98 | 01-JUN-00:10 | 11849.32 | 01-JUN-19:10 | 10029.21 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1461.34 | 11-JUN-13:00 | 0.00 | 01-JUN-00:10 |
July | 45622.98 | 01-JUL-00:10 | 11849.32 | 03-JUL-19:10 | 10029.21 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1871.25 | 29-JUL-16:00 | 0.00 | 01-JUL-00:10 |
August | 45622.98 | 01-AUG-00:10 | 11849.32 | 01-AUG-19:10 | 10029.21 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1673.33 | 23-AUG-13:00 | 0.00 | 01-AUG-00:10 |
September | 45622.98 | 01-SEP-00:10 | 11849.32 | 01-SEP-19:10 | 10029.21 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1457.83 | 13-SEP-13:00 | 0.00 | 01-SEP-00:10 |
October | 45622.98 | 01-OCT-23:10 | 11849.32 | 02-OCT-19:10 | 10029.21 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1457.33 | 09-OCT-11:00 | 94.05 | 28-OCT-03:00 |
November | 45622.98 | 01-NOV-00:10 | 11849.32 | 01-NOV-19:10 | 10029.21 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1157.45 | 17-NOV-15:00 | 1596.05 | 27-NOV-03:00 |
December | 45622.98 | 01-DEC-00:10 | 11849.32 | 01-DEC-20:10 | 10029.21 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1020.24 | 10-DEC-14:00 | 1920.57 | 15-DEC-05:40 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 45622.98 | 11849.32 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 1020.24 | 0.00 | |||||
Maximum of Months | 45622.98 | 11849.32 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 1871.25 | 2307.35 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 392.73 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 67.90 | 01-JAN-11:00 | 153.04 | 25-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 392.73 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.87 | 11-FEB-16:10 | 214.05 | 04-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 392.73 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 99.10 | 13-MAR-16:00 | 189.48 | 16-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 392.73 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 130.55 | 17-APR-15:10 | 85.88 | 02-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 392.73 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 144.03 | 29-MAY-16:00 | 20.79 | 10-MAY-15:00 |
June | 180.00 | 01-JUN-00:10 | 392.73 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 126.59 | 10-JUN-16:00 | 7.14 | 05-JUN-15:00 |
July | 180.00 | 01-JUL-00:10 | 392.73 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 170.16 | 29-JUL-16:00 | 7.16 | 14-JUL-17:40 |
August | 180.00 | 01-AUG-00:10 | 392.73 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 132.09 | 21-AUG-16:00 | 12.35 | 28-AUG-13:00 |
September | 180.00 | 01-SEP-00:10 | 392.73 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 132.05 | 20-SEP-16:00 | 0.00 | 01-SEP-00:10 |
October | 180.00 | 01-OCT-00:10 | 392.73 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 125.82 | 14-OCT-16:00 | 20.77 | 26-OCT-14:00 |
November | 180.00 | 01-NOV-00:10 | 392.73 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 96.36 | 17-NOV-16:10 | 144.33 | 27-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 392.73 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 84.04 | 10-DEC-16:10 | 174.93 | 15-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 392.73 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 67.90 | 0.00 | |||||
Maximum of Months | 180.00 | 392.73 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 170.16 | 214.05 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 392.68 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 67.90 | 01-JAN-11:00 | 153.03 | 25-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 392.68 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.86 | 11-FEB-16:10 | 214.03 | 04-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 392.68 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 99.09 | 13-MAR-16:00 | 189.47 | 16-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 392.68 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 130.54 | 17-APR-15:08 | 85.87 | 02-APR-05:40 |
May | 180.00 | 01-MAY-00:10 | 392.68 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 144.02 | 29-MAY-16:00 | 20.78 | 10-MAY-15:00 |
June | 180.00 | 01-JUN-00:10 | 392.68 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 126.58 | 10-JUN-16:00 | 7.14 | 05-JUN-15:00 |
July | 180.00 | 01-JUL-00:10 | 392.68 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 170.15 | 29-JUL-16:00 | 7.16 | 14-JUL-17:40 |
August | 180.00 | 01-AUG-00:10 | 392.68 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 132.07 | 21-AUG-16:00 | 12.05 | 28-AUG-13:00 |
September | 180.00 | 01-SEP-00:10 | 392.68 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 132.03 | 20-SEP-16:00 | 0.00 | 01-SEP-00:10 |
October | 180.00 | 01-OCT-00:10 | 392.68 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 125.81 | 14-OCT-16:00 | 20.76 | 26-OCT-14:00 |
November | 180.00 | 01-NOV-00:10 | 392.68 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 96.35 | 17-NOV-16:10 | 144.32 | 27-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 392.68 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 84.03 | 10-DEC-16:08 | 174.91 | 15-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 392.68 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 67.90 | 0.00 | |||||
Maximum of Months | 180.00 | 392.68 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 170.15 | 214.03 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 01-JAN-00:10 | 246.81 | 01-JAN-19:10 | 232.19 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 18.71 | 02-JAN-14:00 | 50.00 | 25-JAN-07:20 |
February | 0.00 | 01-FEB-00:10 | 246.81 | 01-FEB-20:10 | 232.19 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.39 | 11-FEB-14:00 | 62.52 | 04-FEB-07:00 |
March | 0.00 | 01-MAR-00:10 | 246.81 | 01-MAR-20:10 | 232.19 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.20 | 13-MAR-16:00 | 59.88 | 16-MAR-07:00 |
April | 0.00 | 01-APR-00:10 | 246.81 | 01-APR-18:10 | 232.19 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.31 | 17-APR-15:00 | 31.84 | 02-APR-06:00 |
May | 0.00 | 01-MAY-00:10 | 246.81 | 01-MAY-19:10 | 232.19 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.43 | 22-MAY-13:00 | 9.66 | 01-MAY-06:00 |
June | 0.00 | 01-JUN-00:10 | 246.81 | 01-JUN-19:10 | 232.19 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.53 | 11-JUN-13:00 | 1.99 | 05-JUN-15:00 |
July | 0.00 | 01-JUL-00:10 | 246.81 | 01-JUL-18:10 | 232.19 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.17 | 29-JUL-16:00 | 2.00 | 14-JUL-22:03 |
August | 0.00 | 01-AUG-00:10 | 246.81 | 01-AUG-19:10 | 232.19 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.00 | 23-AUG-13:00 | 4.09 | 28-AUG-12:00 |
September | 0.00 | 01-SEP-00:10 | 246.81 | 01-SEP-19:10 | 232.19 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.44 | 13-SEP-13:00 | 4.06 | 05-SEP-06:00 |
October | 0.00 | 01-OCT-00:10 | 246.81 | 01-OCT-18:10 | 232.19 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.44 | 09-OCT-11:00 | 7.87 | 28-OCT-03:00 |
November | 0.00 | 01-NOV-00:10 | 246.81 | 01-NOV-19:10 | 232.19 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.25 | 17-NOV-15:00 | 48.23 | 27-NOV-07:00 |
December | 0.00 | 01-DEC-00:10 | 246.81 | 01-DEC-20:10 | 232.19 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.55 | 10-DEC-14:00 | 56.16 | 15-DEC-07:20 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 0.00 | 246.81 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 18.55 | 1.99 | |||||
Maximum of Months | 0.00 | 246.81 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 40.17 | 62.52 |
Report: PeakSpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 246.88 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 20.95 | 02-JAN-14:00 | 42.71 | 25-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 246.88 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.29 | 11-FEB-16:10 | 59.74 | 04-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 246.88 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.66 | 13-MAR-16:00 | 52.88 | 16-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 246.88 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.43 | 17-APR-15:10 | 23.97 | 02-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 246.88 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.20 | 29-MAY-16:00 | 5.80 | 10-MAY-15:00 |
June | 180.00 | 01-JUN-00:10 | 246.88 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.33 | 10-JUN-16:00 | 1.99 | 05-JUN-15:00 |
July | 180.00 | 01-JUL-00:10 | 246.88 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 47.49 | 29-JUL-16:00 | 1.99 | 14-JUL-18:00 |
August | 180.00 | 01-AUG-00:10 | 246.88 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.87 | 21-AUG-16:00 | 1.99 | 05-AUG-18:00 |
September | 180.00 | 01-SEP-00:10 | 246.88 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.85 | 20-SEP-16:00 | 0.00 | 01-SEP-00:10 |
October | 180.00 | 01-OCT-00:10 | 246.88 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.12 | 14-OCT-16:00 | 4.31 | 26-OCT-14:00 |
November | 180.00 | 01-NOV-00:10 | 246.88 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.89 | 17-NOV-16:08 | 40.28 | 27-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 246.88 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.46 | 10-DEC-16:10 | 48.82 | 15-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 246.88 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 20.95 | 0.00 | |||||
Maximum of Months | 180.00 | 246.88 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 47.49 | 59.74 |
Report: PeakSpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 392.73 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 67.89 | 01-JAN-11:00 | 153.21 | 25-JAN-09:00 |
February | 180.00 | 01-FEB-00:10 | 392.73 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.87 | 11-FEB-16:08 | 214.05 | 04-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 392.73 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 99.09 | 13-MAR-16:00 | 189.49 | 16-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 392.73 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 130.55 | 17-APR-15:10 | 85.87 | 02-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 392.73 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 144.03 | 29-MAY-16:00 | 20.79 | 10-MAY-15:00 |
June | 180.00 | 01-JUN-00:10 | 392.73 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 126.59 | 10-JUN-15:50 | 7.14 | 05-JUN-15:00 |
July | 180.00 | 01-JUL-00:10 | 392.73 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 170.17 | 29-JUL-16:00 | 7.16 | 14-JUL-17:40 |
August | 180.00 | 01-AUG-00:10 | 392.73 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 132.09 | 21-AUG-16:00 | 12.69 | 28-AUG-13:00 |
September | 180.00 | 01-SEP-00:10 | 392.73 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 132.04 | 20-SEP-16:00 | 0.00 | 01-SEP-00:10 |
October | 180.00 | 01-OCT-00:10 | 392.73 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 125.82 | 14-OCT-16:00 | 20.77 | 26-OCT-14:00 |
November | 180.00 | 01-NOV-00:10 | 392.73 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 96.36 | 17-NOV-16:08 | 144.33 | 27-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 392.73 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 84.04 | 10-DEC-16:08 | 174.93 | 15-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 392.73 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 67.89 | 0.00 | |||||
Maximum of Months | 180.00 | 392.73 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 170.17 | 214.05 |
Report: PeakSpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 392.68 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 67.90 | 01-JAN-11:00 | 153.03 | 25-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 392.68 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.87 | 11-FEB-16:10 | 214.04 | 04-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 392.68 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 99.09 | 13-MAR-16:00 | 189.47 | 16-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 392.68 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 130.54 | 17-APR-15:10 | 85.87 | 02-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 392.68 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 144.02 | 29-MAY-16:00 | 20.79 | 10-MAY-15:00 |
June | 180.00 | 01-JUN-00:10 | 392.68 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 126.58 | 10-JUN-15:50 | 7.14 | 05-JUN-15:00 |
July | 180.00 | 01-JUL-00:10 | 392.68 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 170.15 | 29-JUL-16:00 | 7.16 | 14-JUL-17:40 |
August | 180.00 | 01-AUG-00:10 | 392.68 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 132.08 | 21-AUG-16:00 | 12.39 | 28-AUG-13:00 |
September | 180.00 | 01-SEP-00:10 | 392.68 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 132.03 | 20-SEP-16:00 | 0.00 | 01-SEP-00:10 |
October | 180.00 | 01-OCT-00:10 | 392.68 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 125.80 | 14-OCT-16:00 | 20.76 | 26-OCT-14:00 |
November | 180.00 | 01-NOV-00:10 | 392.68 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 96.35 | 17-NOV-16:10 | 144.32 | 27-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 392.68 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 84.04 | 10-DEC-16:10 | 174.91 | 15-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 392.68 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 67.90 | 0.00 | |||||
Maximum of Months | 180.00 | 392.68 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 170.15 | 214.04 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2263.36 | 02-JAN-00:10 | 1282.60 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.53 | 02-JAN-14:00 | 183.32 | 25-JAN-07:00 |
February | 2263.36 | 01-FEB-00:10 | 1282.60 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 110.38 | 11-FEB-14:00 | 257.08 | 04-FEB-07:00 |
March | 2263.36 | 01-MAR-00:10 | 1282.60 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.74 | 13-MAR-16:00 | 227.39 | 16-MAR-07:00 |
April | 2263.36 | 01-APR-00:10 | 1282.60 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 145.70 | 17-APR-15:00 | 110.99 | 02-APR-05:05 |
May | 2263.36 | 01-MAY-00:10 | 1282.60 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 176.60 | 22-MAY-13:00 | 19.01 | 07-MAY-06:00 |
June | 2263.36 | 01-JUN-00:10 | 1282.60 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 145.29 | 11-JUN-13:00 | 0.00 | 01-JUN-00:10 |
July | 2263.36 | 01-JUL-00:10 | 1282.60 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 188.63 | 29-JUL-16:00 | 0.00 | 01-JUL-00:10 |
August | 2263.36 | 01-AUG-00:10 | 1282.60 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 166.38 | 23-AUG-13:00 | 0.00 | 01-AUG-00:10 |
September | 2263.36 | 01-SEP-00:10 | 1282.60 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 144.96 | 08-SEP-16:00 | 0.00 | 01-SEP-00:10 |
October | 2263.36 | 01-OCT-23:10 | 1282.60 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 145.25 | 09-OCT-11:00 | 14.12 | 28-OCT-03:00 |
November | 2263.36 | 01-NOV-00:10 | 1282.60 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 116.86 | 17-NOV-15:00 | 179.16 | 27-NOV-03:00 |
December | 2263.36 | 01-DEC-00:10 | 1282.60 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.71 | 10-DEC-14:00 | 211.34 | 15-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 2263.36 | 1282.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.71 | 0.00 | ||||
Maximum of Months | 2263.36 | 1282.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 188.63 | 257.08 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 392.73 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 67.19 | 01-JAN-11:00 | 153.85 | 25-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 392.73 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.16 | 11-FEB-16:10 | 214.88 | 04-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 392.73 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 98.40 | 13-MAR-16:00 | 190.30 | 16-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 392.73 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 129.87 | 17-APR-15:10 | 86.65 | 02-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 392.73 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 143.36 | 29-MAY-16:00 | 21.53 | 10-MAY-15:00 |
June | 180.00 | 01-JUN-00:10 | 392.73 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 125.90 | 10-JUN-16:00 | 7.88 | 05-JUN-15:00 |
July | 180.00 | 01-JUL-00:10 | 392.73 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 169.49 | 29-JUL-16:00 | 7.90 | 14-JUL-17:40 |
August | 180.00 | 01-AUG-00:10 | 392.73 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 131.40 | 21-AUG-16:00 | 14.62 | 28-AUG-13:00 |
September | 180.00 | 01-SEP-00:10 | 392.73 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 131.36 | 20-SEP-16:00 | 0.00 | 01-SEP-00:10 |
October | 180.00 | 01-OCT-00:10 | 392.73 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 125.14 | 14-OCT-16:00 | 21.51 | 26-OCT-14:00 |
November | 180.00 | 01-NOV-00:10 | 392.73 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 95.66 | 17-NOV-16:10 | 145.12 | 27-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 392.73 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 83.34 | 10-DEC-16:10 | 175.74 | 15-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 392.73 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 67.19 | 0.00 | |||||
Maximum of Months | 180.00 | 392.73 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 169.49 | 214.88 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 392.68 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 67.18 | 01-JAN-11:00 | 153.83 | 25-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 392.68 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.15 | 11-FEB-16:10 | 214.87 | 04-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 392.68 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 98.39 | 13-MAR-16:00 | 190.28 | 16-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 392.68 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 129.86 | 17-APR-15:10 | 86.64 | 02-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 392.68 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 143.35 | 29-MAY-16:00 | 21.53 | 10-MAY-15:00 |
June | 180.00 | 01-JUN-00:10 | 392.68 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 125.89 | 10-JUN-16:00 | 7.88 | 05-JUN-15:00 |
July | 180.00 | 01-JUL-00:10 | 392.68 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 169.48 | 29-JUL-16:00 | 7.90 | 14-JUL-17:40 |
August | 180.00 | 01-AUG-00:10 | 392.68 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 131.39 | 21-AUG-16:00 | 14.30 | 28-AUG-13:00 |
September | 180.00 | 01-SEP-00:10 | 392.68 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 131.35 | 20-SEP-16:00 | 0.00 | 01-SEP-00:10 |
October | 180.00 | 01-OCT-00:10 | 392.68 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 125.12 | 14-OCT-16:00 | 21.50 | 26-OCT-14:00 |
November | 180.00 | 01-NOV-00:10 | 392.68 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 95.65 | 17-NOV-16:08 | 145.11 | 27-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 392.68 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 83.33 | 10-DEC-16:08 | 175.73 | 15-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 392.68 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 67.18 | 0.00 | |||||
Maximum of Months | 180.00 | 392.68 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 169.48 | 214.87 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 246.88 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 34.38 | 01-JAN-11:00 | 78.72 | 25-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 246.88 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.80 | 11-FEB-16:50 | 109.94 | 04-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 246.88 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 50.35 | 13-MAR-16:00 | 97.37 | 16-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 246.88 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 66.44 | 17-APR-15:10 | 44.33 | 02-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 246.88 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 73.35 | 29-MAY-16:00 | 11.02 | 10-MAY-15:00 |
June | 180.00 | 01-JUN-00:10 | 246.88 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 64.42 | 10-JUN-16:00 | 4.03 | 05-JUN-15:00 |
July | 180.00 | 01-JUL-00:10 | 246.88 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 86.71 | 29-JUL-16:00 | 4.04 | 14-JUL-17:40 |
August | 180.00 | 01-AUG-00:10 | 246.88 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.23 | 21-AUG-16:00 | 6.56 | 28-AUG-13:00 |
September | 180.00 | 01-SEP-00:10 | 246.88 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.19 | 20-SEP-16:00 | 0.00 | 01-SEP-00:10 |
October | 180.00 | 01-OCT-00:10 | 246.88 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 63.99 | 14-OCT-16:00 | 11.01 | 26-OCT-14:00 |
November | 180.00 | 01-NOV-00:10 | 246.88 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 47.73 | 17-NOV-16:10 | 74.25 | 27-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 246.88 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.79 | 10-DEC-16:10 | 89.92 | 15-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 246.88 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 34.38 | 0.00 | |||||
Maximum of Months | 180.00 | 246.88 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 86.71 | 109.94 |
Report: PeakSpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 3823.39 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 231.23 | 02-JAN-14:00 | 394.74 | 25-JAN-05:30 |
February | 26988.77 | 01-FEB-00:10 | 3823.39 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 238.03 | 11-FEB-14:00 | 535.61 | 04-FEB-07:00 |
March | 26988.77 | 01-MAR-00:10 | 3823.39 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 232.47 | 13-MAR-16:00 | 483.07 | 16-MAR-05:00 |
April | 26988.77 | 01-APR-00:10 | 3823.39 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 311.18 | 17-APR-15:00 | 235.20 | 02-APR-06:00 |
May | 26988.77 | 01-MAY-00:10 | 3823.39 | 01-MAY-19:10 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 380.36 | 22-MAY-13:00 | 52.84 | 01-MAY-05:00 |
June | 26988.77 | 01-JUN-00:10 | 3823.39 | 01-JUN-19:10 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 318.06 | 11-JUN-13:00 | 4.11 | 05-JUN-22:00 |
July | 26988.77 | 01-JUL-00:10 | 3823.39 | 03-JUL-19:10 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 411.87 | 29-JUL-16:00 | 18.08 | 14-JUL-22:00 |
August | 26988.77 | 01-AUG-00:10 | 3823.39 | 01-AUG-19:10 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 367.47 | 23-AUG-13:00 | 0.00 | 01-AUG-00:10 |
September | 26988.77 | 01-SEP-00:10 | 3823.39 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 321.83 | 13-SEP-13:00 | 7.12 | 05-SEP-06:00 |
October | 26988.77 | 01-OCT-23:10 | 3823.39 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 322.58 | 09-OCT-11:00 | 40.85 | 28-OCT-03:00 |
November | 26988.77 | 01-NOV-00:10 | 3823.39 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 256.54 | 17-NOV-15:00 | 376.21 | 27-NOV-03:00 |
December | 26988.77 | 01-DEC-00:10 | 3823.39 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 229.18 | 10-DEC-14:00 | 448.49 | 15-DEC-05:30 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26988.77 | 3823.39 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 229.18 | 0.00 | |||||
Maximum of Months | 26988.77 | 3823.39 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 411.87 | 535.61 |
Report: PeakSpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 3823.39 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 231.06 | 02-JAN-14:00 | 395.42 | 25-JAN-05:30 |
February | 26988.77 | 01-FEB-00:10 | 3823.39 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 234.84 | 11-FEB-14:00 | 537.23 | 04-FEB-07:00 |
March | 26988.77 | 01-MAR-00:10 | 3823.39 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 229.63 | 13-MAR-16:00 | 483.92 | 16-MAR-05:00 |
April | 26988.77 | 01-APR-00:10 | 3823.39 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 308.57 | 17-APR-15:00 | 236.47 | 02-APR-06:00 |
May | 26988.77 | 01-MAY-00:10 | 3823.39 | 01-MAY-19:10 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 377.39 | 22-MAY-13:00 | 53.82 | 01-MAY-05:00 |
June | 26988.77 | 01-JUN-00:10 | 3823.39 | 01-JUN-19:10 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 315.30 | 11-JUN-13:00 | 6.51 | 05-JUN-22:00 |
July | 26988.77 | 01-JUL-00:10 | 3823.39 | 03-JUL-19:10 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 410.02 | 29-JUL-16:00 | 20.46 | 14-JUL-22:00 |
August | 26988.77 | 01-AUG-00:10 | 3823.39 | 01-AUG-19:10 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 365.20 | 23-AUG-13:00 | 0.00 | 01-AUG-00:10 |
September | 26988.77 | 01-SEP-00:10 | 3823.39 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 319.30 | 13-SEP-13:00 | 8.94 | 04-SEP-22:00 |
October | 26988.77 | 01-OCT-23:10 | 3823.39 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 320.77 | 09-OCT-11:00 | 41.88 | 28-OCT-03:00 |
November | 26988.77 | 01-NOV-00:10 | 3823.39 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 253.80 | 17-NOV-15:00 | 377.24 | 27-NOV-03:00 |
December | 26988.77 | 01-DEC-00:10 | 3823.39 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 226.95 | 10-DEC-14:00 | 449.17 | 15-DEC-05:30 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26988.77 | 3823.39 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 226.95 | 0.00 | |||||
Maximum of Months | 26988.77 | 3823.39 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 410.02 | 537.23 |
Report: PeakSpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2401.70 | 02-JAN-00:10 | 1020.78 | 02-JAN-20:10 | 15112.11 | 01-JAN-07:10 | 22492.83 | 01-JAN-16:10 | 0.00 | 0.00 | 0.00 | 129.46 | 02-JAN-15:00 | 366.99 | 25-JAN-08:10 |
February | 2401.70 | 01-FEB-00:10 | 1020.78 | 01-FEB-20:10 | 15112.11 | 01-FEB-07:10 | 22492.83 | 01-FEB-16:10 | 0.00 | 0.00 | 0.00 | 140.69 | 11-FEB-14:00 | 483.61 | 04-FEB-07:00 |
March | 2401.70 | 01-MAR-00:10 | 1020.78 | 01-MAR-20:10 | 15112.11 | 01-MAR-07:10 | 22492.83 | 01-MAR-16:10 | 0.00 | 0.00 | 0.00 | 139.49 | 13-MAR-16:00 | 458.26 | 16-MAR-07:00 |
April | 2401.70 | 01-APR-00:10 | 1020.78 | 03-APR-19:10 | 15112.11 | 01-APR-06:10 | 22492.83 | 01-APR-15:09 | 0.00 | 0.00 | 0.00 | 210.97 | 17-APR-15:00 | 221.37 | 02-APR-06:00 |
May | 2401.70 | 01-MAY-00:10 | 1020.78 | 01-MAY-19:10 | 15112.11 | 01-MAY-06:10 | 22492.83 | 01-MAY-15:09 | 0.00 | 0.00 | 0.00 | 266.85 | 22-MAY-13:00 | 64.93 | 10-MAY-15:00 |
June | 2401.70 | 01-JUN-00:10 | 1020.78 | 01-JUN-19:10 | 15112.11 | 01-JUN-06:10 | 22492.83 | 01-JUN-15:09 | 0.00 | 0.00 | 0.00 | 212.51 | 11-JUN-13:00 | 34.94 | 05-JUN-15:00 |
July | 2401.70 | 01-JUL-00:10 | 1020.78 | 03-JUL-19:10 | 15112.11 | 01-JUL-06:10 | 22492.83 | 01-JUL-15:09 | 0.00 | 0.00 | 0.00 | 296.42 | 29-JUL-16:00 | 35.30 | 14-JUL-20:00 |
August | 2401.70 | 01-AUG-00:10 | 1020.78 | 01-AUG-19:10 | 15112.11 | 01-AUG-06:10 | 22492.83 | 01-AUG-15:09 | 0.00 | 0.00 | 0.00 | 255.54 | 23-AUG-13:00 | 51.53 | 28-AUG-12:00 |
September | 2401.70 | 01-SEP-00:10 | 1020.78 | 01-SEP-19:10 | 15112.11 | 01-SEP-06:10 | 22492.83 | 01-SEP-15:09 | 0.00 | 0.00 | 0.00 | 211.96 | 20-SEP-16:00 | 36.80 | 05-SEP-06:10 |
October | 2401.70 | 01-OCT-23:10 | 1020.78 | 02-OCT-19:10 | 15112.11 | 01-OCT-06:10 | 22492.83 | 01-OCT-15:09 | 0.00 | 0.00 | 0.00 | 211.92 | 09-OCT-11:00 | 55.97 | 26-OCT-14:00 |
November | 2401.70 | 01-NOV-00:10 | 1020.78 | 01-NOV-19:10 | 15112.11 | 01-NOV-06:10 | 22492.83 | 01-NOV-15:09 | 0.00 | 0.00 | 0.00 | 156.24 | 17-NOV-15:00 | 343.67 | 27-NOV-07:00 |
December | 2401.70 | 01-DEC-00:10 | 1020.78 | 01-DEC-20:10 | 15112.11 | 01-DEC-07:10 | 22492.83 | 01-DEC-16:10 | 0.00 | 0.00 | 0.00 | 130.11 | 10-DEC-15:00 | 437.65 | 15-DEC-07:30 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 2401.70 | 1020.78 | 15112.11 | 22492.83 | 0.00 | 0.00 | 0.00 | 129.46 | 34.94 | ||||||
Maximum of Months | 2401.70 | 1020.78 | 15112.11 | 22492.83 | 0.00 | 0.00 | 0.00 | 296.42 | 483.61 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2395.44 | 02-JAN-00:10 | 1357.44 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 184.25 | 02-JAN-14:00 | 326.09 | 25-JAN-07:00 |
February | 2395.44 | 01-FEB-00:10 | 1357.44 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 195.05 | 11-FEB-14:00 | 456.69 | 04-FEB-07:00 |
March | 2395.44 | 01-MAR-00:10 | 1357.44 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 204.31 | 13-MAR-16:00 | 404.05 | 16-MAR-07:00 |
April | 2395.44 | 01-APR-00:10 | 1357.44 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 261.28 | 17-APR-15:00 | 182.38 | 02-APR-06:00 |
May | 2395.44 | 01-MAY-00:10 | 1357.44 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 316.25 | 22-MAY-13:00 | 13.51 | 01-MAY-05:40 |
June | 2395.44 | 01-JUN-00:10 | 1357.44 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 257.61 | 11-JUN-13:00 | 0.00 | 01-JUN-00:10 |
July | 2395.44 | 01-JUL-00:10 | 1357.44 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 331.70 | 29-JUL-16:00 | 0.00 | 01-JUL-00:10 |
August | 2395.44 | 01-AUG-00:10 | 1357.44 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 297.02 | 23-AUG-13:00 | 0.00 | 01-AUG-00:10 |
September | 2395.44 | 01-SEP-00:10 | 1357.44 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 260.87 | 13-SEP-13:00 | 0.00 | 01-SEP-00:10 |
October | 2395.44 | 01-OCT-23:10 | 1357.44 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 267.34 | 09-OCT-11:00 | 0.15 | 28-OCT-03:20 |
November | 2395.44 | 01-NOV-00:10 | 1357.44 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 206.61 | 17-NOV-15:00 | 307.44 | 27-NOV-07:00 |
December | 2395.44 | 01-DEC-00:10 | 1357.44 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 181.64 | 10-DEC-14:00 | 372.95 | 15-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 2395.44 | 1357.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 181.64 | 0.00 | ||||
Maximum of Months | 2395.44 | 1357.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 331.70 | 456.69 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 23633.95 | 02-JAN-19:10 | 53675.50 | 72090.20 | 57488.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 23184.38 | 16-FEB-19:10 | 53675.50 | 72090.20 | 57488.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 22983.63 | 29-MAR-18:20 | 17891.83 | 24030.07 | 19162.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 23124.45 | 17-APR-19:10 | 17891.83 | 27034.00 | 20227.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 23528.64 | 31-MAY-18:50 | 8945.92 | 12015.03 | 9581.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 23968.66 | 28-JUN-18:40 | 8945.92 | 12015.03 | 9581.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 24888.51 | 27-JUL-18:20 | 17891.83 | 24030.07 | 19162.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 25278.77 | 02-AUG-18:10 | 53675.50 | 72090.20 | 57488.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 25208.46 | 18-SEP-18:10 | 53675.50 | 72090.20 | 57488.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 24955.82 | 05-OCT-18:10 | 53675.50 | 72090.20 | 57488.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 24478.59 | 02-NOV-18:10 | 53675.50 | 72090.20 | 57488.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 23944.13 | 07-DEC-19:10 | 53675.50 | 72090.20 | 57488.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 22983.63 | 8945.92 | 12015.03 | 9581.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 25278.77 | 53675.50 | 72090.20 | 57488.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3333.07 | 02-JAN-11:35 | 519.79 | 381.83 | 505.18 | 0.00 | 0.00 | 0.00 | 0.00 | 82.83 | 0.00 |
February | 3216.88 | 11-FEB-11:35 | 779.69 | 381.83 | 505.18 | 0.00 | 0.00 | 0.00 | 0.00 | 109.65 | 0.00 |
March | 3150.94 | 04-MAR-11:35 | 779.69 | 381.83 | 505.18 | 0.00 | 0.00 | 0.00 | 0.00 | 101.35 | 0.00 |
April | 2974.02 | 15-APR-10:35 | 779.69 | 381.83 | 505.18 | 0.00 | 0.00 | 0.00 | 0.00 | 164.97 | 0.00 |
May | 2886.25 | 22-MAY-18:10 | 5457.82 | 3665.58 | 3897.11 | 0.00 | 0.00 | 0.00 | 0.00 | 187.21 | 0.00 |
June | 2975.80 | 11-JUN-10:35 | 779.69 | 458.20 | 577.35 | 0.00 | 0.00 | 0.00 | 0.00 | 201.98 | 0.00 |
July | 3123.47 | 29-JUL-17:13 | 2339.06 | 1374.59 | 1515.54 | 0.00 | 0.00 | 0.00 | 0.00 | 249.03 | 0.00 |
August | 3099.79 | 19-AUG-10:35 | 779.69 | 381.83 | 505.18 | 0.00 | 0.00 | 0.00 | 0.00 | 205.88 | 0.00 |
September | 3317.76 | 24-SEP-10:35 | 779.69 | 458.20 | 577.35 | 0.00 | 0.00 | 0.00 | 0.00 | 172.73 | 0.00 |
October | 3354.34 | 07-OCT-10:35 | 779.69 | 381.83 | 505.18 | 0.00 | 0.00 | 0.00 | 0.00 | 181.99 | 0.00 |
November | 3526.28 | 08-NOV-11:35 | 519.79 | 381.83 | 505.18 | 0.00 | 0.00 | 0.00 | 0.00 | 86.54 | 0.00 |
December | 3453.80 | 09-DEC-11:35 | 779.69 | 381.83 | 505.18 | 0.00 | 0.00 | 0.00 | 0.00 | 87.12 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2886.25 | 519.79 | 381.83 | 505.18 | 0.00 | 0.00 | 0.00 | 0.00 | 82.83 | 0.00 | |
Maximum of Months | 3526.28 | 5457.82 | 3665.58 | 3897.11 | 0.00 | 0.00 | 0.00 | 0.00 | 249.03 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2132.50 | 02-JAN-19:10 | 6320.16 | 4244.75 | 4512.87 | 0.00 | 0.00 | 0.00 | 0.00 | 16.91 | 0.00 |
February | 2137.29 | 11-FEB-19:10 | 5417.28 | 3714.16 | 4011.44 | 0.00 | 0.00 | 0.00 | 0.00 | 19.36 | 0.00 |
March | 2212.58 | 13-MAR-18:10 | 6320.16 | 4244.75 | 4512.87 | 0.00 | 0.00 | 0.00 | 0.00 | 54.99 | 0.00 |
April | 2292.13 | 17-APR-18:10 | 6320.16 | 4244.75 | 4512.87 | 0.00 | 0.00 | 0.00 | 0.00 | 71.21 | 0.00 |
May | 2308.51 | 22-MAY-18:10 | 6320.16 | 4244.75 | 4512.87 | 0.00 | 0.00 | 0.00 | 0.00 | 74.21 | 0.00 |
June | 2348.05 | 29-JUN-18:10 | 6320.16 | 4244.75 | 4512.87 | 0.00 | 0.00 | 0.00 | 0.00 | 70.59 | 0.00 |
July | 2384.21 | 27-JUL-18:10 | 6320.16 | 4244.75 | 4512.87 | 0.00 | 0.00 | 0.00 | 0.00 | 84.26 | 0.00 |
August | 2342.66 | 17-AUG-18:10 | 6320.16 | 4244.75 | 4512.87 | 0.00 | 0.00 | 0.00 | 0.00 | 68.94 | 0.00 |
September | 2335.10 | 18-SEP-18:10 | 6320.16 | 4244.75 | 4512.87 | 0.00 | 0.00 | 0.00 | 0.00 | 73.55 | 0.00 |
October | 2279.37 | 05-OCT-18:10 | 6320.16 | 4244.75 | 4512.87 | 0.00 | 0.00 | 0.00 | 0.00 | 61.05 | 0.00 |
November | 2215.54 | 08-NOV-19:10 | 6320.16 | 4244.75 | 4512.87 | 0.00 | 0.00 | 0.00 | 0.00 | 39.95 | 0.00 |
December | 2147.11 | 09-DEC-19:10 | 5417.28 | 3714.16 | 4011.44 | 0.00 | 0.00 | 0.00 | 0.00 | 31.99 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2132.50 | 5417.28 | 3714.16 | 4011.44 | 0.00 | 0.00 | 0.00 | 0.00 | 16.91 | 0.00 | |
Maximum of Months | 2384.21 | 6320.16 | 4244.75 | 4512.87 | 0.00 | 0.00 | 0.00 | 0.00 | 84.26 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2168.46 | 02-JAN-19:50 | 222.77 | 1322.39 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 26.90 | 0.00 |
February | 2188.34 | 16-FEB-19:15 | 445.54 | 2644.77 | 1590.53 | 0.00 | 0.00 | 0.00 | 0.00 | 44.72 | 0.00 |
March | 2289.15 | 27-MAR-18:20 | 445.54 | 2644.77 | 1590.53 | 0.00 | 0.00 | 0.00 | 0.00 | 88.66 | 0.00 |
April | 2444.62 | 17-APR-18:10 | 1336.61 | 7934.32 | 4771.59 | 0.00 | 0.00 | 0.00 | 0.00 | 169.97 | 0.00 |
May | 2487.61 | 22-MAY-18:10 | 1336.61 | 7934.32 | 4771.59 | 0.00 | 0.00 | 0.00 | 0.00 | 175.62 | 0.00 |
June | 2586.85 | 11-JUN-10:35 | 190.94 | 991.79 | 706.90 | 0.00 | 0.00 | 0.00 | 0.00 | 188.02 | 0.00 |
July | 2616.72 | 29-JUL-10:35 | 190.94 | 826.49 | 618.54 | 0.00 | 0.00 | 0.00 | 0.00 | 207.63 | 0.00 |
August | 2567.04 | 20-AUG-10:35 | 190.94 | 991.79 | 706.90 | 0.00 | 0.00 | 0.00 | 0.00 | 190.44 | 0.00 |
September | 2494.10 | 18-SEP-18:10 | 1336.61 | 7934.32 | 4771.59 | 0.00 | 0.00 | 0.00 | 0.00 | 175.40 | 0.00 |
October | 2418.43 | 05-OCT-18:10 | 1336.61 | 7934.32 | 4771.59 | 0.00 | 0.00 | 0.00 | 0.00 | 146.75 | 0.00 |
November | 2328.93 | 22-NOV-19:03 | 1336.61 | 7934.32 | 4771.59 | 0.00 | 0.00 | 0.00 | 0.00 | 109.44 | 0.00 |
December | 2239.14 | 07-DEC-19:20 | 445.54 | 2644.77 | 1590.53 | 0.00 | 0.00 | 0.00 | 0.00 | 65.58 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2168.46 | 190.94 | 826.49 | 618.54 | 0.00 | 0.00 | 0.00 | 0.00 | 26.90 | 0.00 | |
Maximum of Months | 2616.72 | 1336.61 | 7934.32 | 4771.59 | 0.00 | 0.00 | 0.00 | 0.00 | 207.63 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 983.57 | 13-JAN-21:00 | 171.36 | 273.10 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 37.67 | 0.00 |
February | 991.37 | 17-FEB-20:20 | 171.36 | 273.10 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 32.44 | 0.00 |
March | 1037.18 | 30-MAR-20:00 | 171.36 | 273.10 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 32.43 | 0.00 |
April | 1112.03 | 17-APR-19:10 | 342.72 | 546.20 | 484.31 | 0.00 | 0.00 | 0.00 | 0.00 | 64.19 | 0.00 |
May | 1189.99 | 31-MAY-18:15 | 342.72 | 485.51 | 458.82 | 0.00 | 0.00 | 0.00 | 0.00 | 80.31 | 0.00 |
June | 1293.28 | 11-JUN-10:35 | 146.88 | 182.07 | 203.92 | 0.00 | 0.00 | 0.00 | 0.00 | 108.37 | 0.00 |
July | 1313.92 | 29-JUL-10:35 | 146.88 | 151.73 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 119.30 | 0.00 |
August | 1294.34 | 19-AUG-10:35 | 146.88 | 151.73 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 114.12 | 0.00 |
September | 1282.11 | 24-SEP-10:35 | 146.88 | 182.07 | 203.92 | 0.00 | 0.00 | 0.00 | 0.00 | 104.16 | 0.00 |
October | 1134.02 | 05-OCT-19:10 | 171.36 | 273.10 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 78.88 | 0.00 |
November | 1079.02 | 22-NOV-21:00 | 171.36 | 273.10 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 62.77 | 0.00 |
December | 1022.97 | 07-DEC-21:00 | 171.36 | 273.10 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 32.42 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 983.57 | 146.88 | 151.73 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 32.42 | 0.00 | |
Maximum of Months | 1313.92 | 342.72 | 546.20 | 484.31 | 0.00 | 0.00 | 0.00 | 0.00 | 119.30 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 36756.05 | 02-JAN-21:00 | 705.60 | 337.37 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 39.51 |
February | 36726.14 | 16-FEB-21:00 | 705.60 | 337.37 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 5.29 | 0.00 |
March | 37145.35 | 27-MAR-20:00 | 705.60 | 337.37 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 21.18 | 0.00 |
April | 37390.22 | 17-APR-20:00 | 705.60 | 337.37 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 38.34 | 0.00 |
May | 37723.94 | 31-MAY-20:00 | 705.60 | 337.37 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 112.68 | 0.00 |
June | 37825.24 | 08-JUN-20:00 | 705.60 | 337.37 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 141.57 | 0.00 |
July | 37904.85 | 27-JUL-20:00 | 705.60 | 337.37 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 141.80 | 0.00 |
August | 37806.30 | 31-AUG-20:00 | 705.60 | 337.37 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 113.07 | 0.00 |
September | 37764.94 | 21-SEP-20:00 | 705.60 | 337.37 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 141.07 | 0.00 |
October | 37529.17 | 05-OCT-20:00 | 705.60 | 337.37 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 111.65 | 0.00 |
November | 37207.32 | 02-NOV-20:00 | 705.60 | 337.37 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 81.46 | 0.00 |
December | 36829.09 | 06-DEC-21:00 | 705.60 | 337.37 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 19.78 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 36726.14 | 705.60 | 337.37 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 37904.85 | 705.60 | 337.37 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 141.80 | 39.51 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 13713.20 | 15-JAN-11:35 | 10245.60 | 1451.48 | 812.86 | 0.00 | 0.00 | 0.00 | 0.00 | 101.22 | 0.00 |
February | 13613.36 | 11-FEB-11:35 | 10245.60 | 1209.57 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 263.69 | 0.00 |
March | 13396.57 | 04-MAR-11:35 | 10245.60 | 1209.57 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 243.12 | 0.00 |
April | 12786.19 | 17-APR-18:10 | 71719.20 | 11611.87 | 5486.82 | 0.00 | 0.00 | 0.00 | 0.00 | 396.77 | 0.00 |
May | 12842.85 | 22-MAY-18:10 | 71719.20 | 11611.87 | 5486.82 | 0.00 | 0.00 | 0.00 | 0.00 | 414.89 | 0.00 |
June | 12992.97 | 29-JUN-18:10 | 71719.20 | 11611.87 | 5486.82 | 0.00 | 0.00 | 0.00 | 0.00 | 395.94 | 0.00 |
July | 13326.03 | 27-JUL-18:10 | 71719.20 | 11611.87 | 5486.82 | 0.00 | 0.00 | 0.00 | 0.00 | 470.43 | 0.00 |
August | 13004.92 | 02-AUG-18:10 | 71719.20 | 11611.87 | 5486.82 | 0.00 | 0.00 | 0.00 | 0.00 | 391.23 | 0.00 |
September | 13867.31 | 24-SEP-10:35 | 10245.60 | 1451.48 | 812.86 | 0.00 | 0.00 | 0.00 | 0.00 | 408.48 | 0.00 |
October | 13955.98 | 07-OCT-10:35 | 10245.60 | 1209.57 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 430.99 | 0.00 |
November | 14288.84 | 08-NOV-11:35 | 6830.40 | 1209.57 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 232.82 | 0.00 |
December | 14446.24 | 09-DEC-11:35 | 10245.60 | 1209.57 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 220.33 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 12786.19 | 6830.40 | 1209.57 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 101.22 | 0.00 | |
Maximum of Months | 14446.24 | 71719.20 | 11611.87 | 5486.82 | 0.00 | 0.00 | 0.00 | 0.00 | 470.43 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 41098.71 | 02-JAN-19:10 | 212907.24 | 63196.36 | 57008.13 | 0.00 | 0.00 | 0.00 | 0.00 | 253.65 | 0.00 |
February | 40953.48 | 11-FEB-19:10 | 182491.92 | 55296.81 | 50673.90 | 0.00 | 0.00 | 0.00 | 0.00 | 299.49 | 0.00 |
March | 42336.72 | 13-MAR-18:10 | 212907.24 | 63196.36 | 57008.13 | 0.00 | 0.00 | 0.00 | 0.00 | 883.67 | 0.00 |
April | 43779.35 | 17-APR-18:10 | 212907.24 | 63196.36 | 57008.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1150.46 | 0.00 |
May | 44232.74 | 22-MAY-18:10 | 212907.24 | 63196.36 | 57008.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1196.16 | 0.00 |
June | 44792.13 | 29-JUN-18:10 | 212907.24 | 63196.36 | 57008.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1141.21 | 0.00 |
July | 45394.92 | 27-JUL-18:10 | 212907.24 | 63196.36 | 57008.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1366.82 | 0.00 |
August | 44668.12 | 02-AUG-18:10 | 212907.24 | 63196.36 | 57008.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1131.64 | 0.00 |
September | 44809.15 | 24-SEP-10:35 | 30415.32 | 7899.54 | 8445.65 | 0.00 | 0.00 | 0.00 | 0.00 | 1248.71 | 0.00 |
October | 43584.88 | 05-OCT-18:10 | 212907.24 | 63196.36 | 57008.13 | 0.00 | 0.00 | 0.00 | 0.00 | 983.06 | 0.00 |
November | 42600.44 | 19-NOV-11:35 | 30415.32 | 7899.54 | 8445.65 | 0.00 | 0.00 | 0.00 | 0.00 | 734.34 | 0.00 |
December | 43417.94 | 09-DEC-11:35 | 30415.32 | 6582.95 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 792.81 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 40953.48 | 30415.32 | 6582.95 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 253.65 | 0.00 | |
Maximum of Months | 45394.92 | 212907.24 | 63196.36 | 57008.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1366.82 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3278.88 | 26-JAN-16:02 | 583.20 | 659.78 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.01 |
February | 3301.31 | 24-FEB-16:02 | 583.20 | 659.78 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 28.90 | 0.00 |
March | 3235.14 | 15-MAR-15:01 | 680.40 | 769.75 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.95 |
April | 3217.13 | 15-APR-15:02 | 324.00 | 777.60 | 458.31 | 0.00 | 0.00 | 0.00 | 0.00 | 100.68 | 0.00 |
May | 3220.81 | 16-MAY-15:02 | 583.20 | 659.78 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 92.46 | 0.00 |
June | 3182.98 | 10-JUN-15:02 | 324.00 | 777.60 | 458.31 | 0.00 | 0.00 | 0.00 | 0.00 | 107.16 | 0.00 |
July | 3229.87 | 28-JUL-15:02 | 583.20 | 659.78 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 143.76 | 0.00 |
August | 3224.39 | 31-AUG-15:02 | 583.20 | 659.78 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 111.92 | 0.00 |
September | 3230.81 | 17-SEP-15:02 | 324.00 | 777.60 | 458.31 | 0.00 | 0.00 | 0.00 | 0.00 | 99.46 | 0.00 |
October | 3202.25 | 06-OCT-15:02 | 583.20 | 659.78 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 78.51 | 0.00 |
November | 3172.94 | 17-NOV-16:02 | 583.20 | 659.78 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 78.14 | 0.00 |
December | 3202.74 | 06-DEC-16:02 | 583.20 | 659.78 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 40.15 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3172.94 | 324.00 | 659.78 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3301.31 | 680.40 | 777.60 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 143.76 | 65.95 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3237.51 | 26-JAN-16:02 | 583.20 | 659.70 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.44 |
February | 3285.56 | 24-FEB-16:02 | 583.20 | 659.70 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 30.50 | 0.00 |
March | 3216.86 | 15-MAR-15:01 | 680.40 | 769.66 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.10 |
April | 3252.36 | 15-APR-18:02 | 702.00 | 2356.09 | 774.30 | 0.00 | 0.00 | 0.00 | 0.00 | 85.53 | 0.00 |
May | 3248.03 | 20-MAY-15:02 | 324.00 | 777.51 | 458.26 | 0.00 | 0.00 | 0.00 | 0.00 | 87.68 | 0.00 |
June | 3212.71 | 10-JUN-15:02 | 324.00 | 777.51 | 458.26 | 0.00 | 0.00 | 0.00 | 0.00 | 107.20 | 0.00 |
July | 3262.61 | 28-JUL-15:02 | 583.20 | 659.70 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 143.90 | 0.00 |
August | 3205.15 | 19-AUG-15:02 | 324.00 | 777.51 | 458.26 | 0.00 | 0.00 | 0.00 | 0.00 | 107.06 | 0.00 |
September | 3195.62 | 30-SEP-15:02 | 324.00 | 777.51 | 458.26 | 0.00 | 0.00 | 0.00 | 0.00 | 99.96 | 0.00 |
October | 3202.84 | 18-OCT-15:02 | 583.20 | 659.70 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 55.19 | 0.00 |
November | 3163.54 | 06-NOV-16:02 | 583.20 | 659.70 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 62.61 | 0.00 |
December | 3135.74 | 04-DEC-16:02 | 583.20 | 659.70 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 35.86 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3135.74 | 324.00 | 659.70 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3285.56 | 702.00 | 2356.09 | 774.30 | 0.00 | 0.00 | 0.00 | 0.00 | 143.90 | 64.10 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 746.42 | 02-JAN-14:30 | 0.00 | 69.11 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 18.71 | 0.00 |
February | 683.69 | 11-FEB-14:30 | 0.00 | 81.45 | 74.82 | 0.00 | 0.00 | 0.00 | 0.00 | 18.56 | 0.00 |
March | 569.07 | 02-MAR-14:30 | 0.00 | 69.11 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 5.57 | 0.00 |
April | 523.51 | 15-APR-19:10 | 0.00 | 246.81 | 170.27 | 0.00 | 0.00 | 0.00 | 0.00 | 17.35 | 0.00 |
May | 507.78 | 22-MAY-20:20 | 0.00 | 219.66 | 180.59 | 0.00 | 0.00 | 0.00 | 0.00 | 16.07 | 0.00 |
June | 532.63 | 03-JUN-21:00 | 0.00 | 246.81 | 180.59 | 0.00 | 0.00 | 0.00 | 0.00 | 20.33 | 0.00 |
July | 567.35 | 29-JUL-19:10 | 0.00 | 246.81 | 170.27 | 0.00 | 0.00 | 0.00 | 0.00 | 27.26 | 0.00 |
August | 551.14 | 20-AUG-20:03 | 0.00 | 740.44 | 541.78 | 0.00 | 0.00 | 0.00 | 0.00 | 18.33 | 0.00 |
September | 654.23 | 30-SEP-13:30 | 0.00 | 81.45 | 74.82 | 0.00 | 0.00 | 0.00 | 0.00 | 25.05 | 0.00 |
October | 714.26 | 25-OCT-12:40 | 0.00 | 69.11 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 22.21 | 0.00 |
November | 747.21 | 07-NOV-13:40 | 0.00 | 69.11 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 16.03 | 0.00 |
December | 755.58 | 03-DEC-14:00 | 0.00 | 81.45 | 74.82 | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 507.78 | 0.00 | 69.11 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 0.00 | |
Maximum of Months | 755.58 | 0.00 | 740.44 | 541.78 | 0.00 | 0.00 | 0.00 | 0.00 | 27.26 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1129.77 | 16-JAN-16:02 | 324.00 | 488.83 | 449.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.73 |
February | 1188.46 | 24-FEB-19:01 | 970.20 | 1538.07 | 885.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.02 |
March | 1185.13 | 14-MAR-18:02 | 831.60 | 1318.35 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 4.58 | 0.00 |
April | 1198.42 | 17-APR-18:02 | 831.60 | 1318.35 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 24.03 | 0.00 |
May | 1183.38 | 20-MAY-18:02 | 702.00 | 1481.29 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 17.43 | 0.00 |
June | 1180.01 | 14-JUN-18:02 | 831.60 | 1318.35 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 21.62 | 0.00 |
July | 1188.42 | 29-JUL-18:02 | 702.00 | 1481.29 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 33.82 | 0.00 |
August | 1172.18 | 19-AUG-18:02 | 702.00 | 1481.29 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 21.92 | 0.00 |
September | 1166.52 | 01-SEP-18:02 | 831.60 | 1318.35 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 23.60 | 0.00 |
October | 1184.47 | 17-OCT-18:02 | 831.60 | 1318.35 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 9.22 | 0.00 |
November | 1177.48 | 20-NOV-19:02 | 831.60 | 1318.35 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 11.05 | 0.00 |
December | 1154.06 | 09-DEC-19:02 | 702.00 | 1481.29 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 7.54 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1129.77 | 324.00 | 488.83 | 449.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1198.42 | 970.20 | 1538.07 | 885.15 | 0.00 | 0.00 | 0.00 | 0.00 | 33.82 | 2.02 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2952.88 | 26-JAN-16:02 | 583.20 | 659.78 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.87 |
February | 2976.13 | 24-FEB-19:01 | 970.20 | 2446.69 | 903.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.82 |
March | 2936.42 | 20-MAR-15:01 | 680.40 | 769.75 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.32 |
April | 2890.40 | 16-APR-15:02 | 324.00 | 777.60 | 458.31 | 0.00 | 0.00 | 0.00 | 0.00 | 104.70 | 0.00 |
May | 2859.58 | 20-MAY-15:02 | 324.00 | 777.60 | 458.31 | 0.00 | 0.00 | 0.00 | 0.00 | 87.82 | 0.00 |
June | 2860.88 | 01-JUN-15:02 | 583.20 | 659.78 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 87.11 | 0.00 |
July | 2948.35 | 29-JUL-15:02 | 324.00 | 777.60 | 458.31 | 0.00 | 0.00 | 0.00 | 0.00 | 145.32 | 0.00 |
August | 2869.07 | 31-AUG-15:02 | 583.20 | 659.78 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 112.13 | 0.00 |
September | 2876.42 | 30-SEP-15:02 | 324.00 | 777.60 | 458.31 | 0.00 | 0.00 | 0.00 | 0.00 | 99.66 | 0.00 |
October | 2946.57 | 25-OCT-15:02 | 583.20 | 659.78 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 77.83 | 0.00 |
November | 2861.98 | 14-NOV-16:02 | 583.20 | 659.78 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 9.29 | 0.00 |
December | 2868.86 | 04-DEC-16:02 | 583.20 | 659.78 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 34.97 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2859.58 | 324.00 | 659.78 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2976.13 | 970.20 | 2446.69 | 903.46 | 0.00 | 0.00 | 0.00 | 0.00 | 145.32 | 38.32 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2758.50 | 15-JAN-16:02 | 324.00 | 777.51 | 458.26 | 0.00 | 0.00 | 0.00 | 0.00 | 27.24 | 0.00 |
February | 2974.11 | 22-FEB-16:02 | 583.20 | 659.70 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 59.94 | 0.00 |
March | 2852.41 | 01-MAR-16:02 | 583.20 | 659.70 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 29.51 | 0.00 |
April | 2953.08 | 16-APR-15:02 | 324.00 | 777.51 | 458.26 | 0.00 | 0.00 | 0.00 | 0.00 | 105.33 | 0.00 |
May | 2878.67 | 20-MAY-08:62 | 324.00 | 1319.41 | 979.73 | 0.00 | 0.00 | 0.00 | 0.00 | 61.68 | 0.00 |
June | 2882.64 | 01-JUN-15:02 | 583.20 | 659.70 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 87.15 | 0.00 |
July | 2976.32 | 29-JUL-15:02 | 324.00 | 777.51 | 458.26 | 0.00 | 0.00 | 0.00 | 0.00 | 145.46 | 0.00 |
August | 2854.74 | 19-AUG-15:02 | 324.00 | 777.51 | 458.26 | 0.00 | 0.00 | 0.00 | 0.00 | 107.18 | 0.00 |
September | 2841.01 | 13-SEP-15:02 | 583.20 | 659.70 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 102.85 | 0.00 |
October | 2814.80 | 17-OCT-18:02 | 831.60 | 2096.92 | 774.30 | 0.00 | 0.00 | 0.00 | 0.00 | 35.89 | 0.00 |
November | 2817.81 | 14-NOV-16:02 | 583.20 | 659.70 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 12.46 | 0.00 |
December | 2768.21 | 03-DEC-19:02 | 702.00 | 2356.09 | 774.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.85 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2758.50 | 324.00 | 659.70 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2976.32 | 831.60 | 2356.09 | 979.73 | 0.00 | 0.00 | 0.00 | 0.00 | 145.46 | 7.85 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2793.51 | 01-JAN-11:35 | 1508.90 | 855.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.72 | 0.00 |
February | 2758.98 | 11-FEB-11:35 | 1508.90 | 712.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.66 | 0.00 |
March | 2767.13 | 04-MAR-11:35 | 1508.90 | 712.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.78 | 0.00 |
April | 2970.30 | 15-APR-10:35 | 1508.90 | 712.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.35 | 0.00 |
May | 2987.72 | 20-MAY-10:35 | 1508.90 | 712.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.68 | 0.00 |
June | 3094.30 | 11-JUN-10:35 | 1508.90 | 855.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 128.08 | 0.00 |
July | 3152.16 | 30-JUL-10:35 | 1508.90 | 855.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 138.64 | 0.00 |
August | 3117.20 | 19-AUG-10:35 | 1508.90 | 712.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.86 | 0.00 |
September | 3151.62 | 24-SEP-10:35 | 1508.90 | 855.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.94 | 0.00 |
October | 3084.88 | 07-OCT-10:35 | 1508.90 | 712.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 129.80 | 0.00 |
November | 2887.13 | 08-NOV-11:35 | 1005.94 | 712.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.46 | 0.00 |
December | 2905.50 | 09-DEC-11:35 | 1508.90 | 712.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.13 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 2758.98 | 1005.94 | 712.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.72 | 0.00 | |
Maximum of Months | 3152.16 | 1508.90 | 855.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 138.64 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3486.54 | 26-JAN-16:02 | 583.20 | 659.78 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.86 |
February | 3505.72 | 24-FEB-16:02 | 583.20 | 659.78 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 28.22 | 0.00 |
March | 3427.73 | 15-MAR-15:01 | 680.40 | 769.75 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.33 |
April | 3435.09 | 14-APR-15:02 | 583.20 | 659.78 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 91.15 | 0.00 |
May | 3426.50 | 31-MAY-15:02 | 583.20 | 659.78 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 96.59 | 0.00 |
June | 3439.96 | 28-JUN-15:02 | 583.20 | 659.78 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 92.46 | 0.00 |
July | 3442.05 | 20-JUL-15:02 | 583.20 | 659.78 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 99.54 | 0.00 |
August | 3440.26 | 21-AUG-15:02 | 583.20 | 659.78 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 90.59 | 0.00 |
September | 3422.14 | 04-SEP-15:02 | 324.00 | 777.60 | 458.31 | 0.00 | 0.00 | 0.00 | 0.00 | 93.04 | 0.00 |
October | 3431.19 | 22-OCT-15:02 | 324.00 | 777.60 | 458.31 | 0.00 | 0.00 | 0.00 | 0.00 | 77.65 | 0.00 |
November | 3433.91 | 07-NOV-16:02 | 583.20 | 659.78 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 64.55 | 0.00 |
December | 3392.27 | 05-DEC-16:02 | 583.20 | 659.78 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 32.70 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3392.27 | 324.00 | 659.78 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3505.72 | 680.40 | 777.60 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 99.54 | 66.33 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3430.65 | 26-JAN-16:02 | 583.20 | 659.70 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.98 |
February | 3482.10 | 24-FEB-16:02 | 583.20 | 659.70 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 29.95 | 0.00 |
March | 3408.01 | 31-MAR-15:02 | 583.20 | 659.70 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 37.87 | 0.00 |
April | 3428.31 | 11-APR-15:02 | 583.20 | 659.70 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 72.94 | 0.00 |
May | 3451.97 | 19-MAY-18:02 | 831.60 | 2096.92 | 774.30 | 0.00 | 0.00 | 0.00 | 0.00 | 64.76 | 0.00 |
June | 3463.17 | 28-JUN-15:02 | 583.20 | 659.70 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 92.48 | 0.00 |
July | 3509.15 | 28-JUL-15:02 | 583.20 | 659.70 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 142.64 | 0.00 |
August | 3463.48 | 23-AUG-15:02 | 583.20 | 659.70 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 104.23 | 0.00 |
September | 3457.13 | 20-SEP-15:02 | 583.20 | 659.70 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 107.66 | 0.00 |
October | 3416.25 | 25-OCT-15:02 | 583.20 | 659.70 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 77.73 | 0.00 |
November | 3392.73 | 07-NOV-16:02 | 583.20 | 659.70 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 66.24 | 0.00 |
December | 3386.49 | 03-DEC-16:02 | 324.00 | 777.51 | 458.26 | 0.00 | 0.00 | 0.00 | 0.00 | 20.69 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3386.49 | 324.00 | 659.70 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3509.15 | 831.60 | 2096.92 | 774.30 | 0.00 | 0.00 | 0.00 | 0.00 | 142.64 | 23.98 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1728.98 | 26-JAN-16:02 | 583.20 | 414.76 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.70 |
February | 1723.92 | 24-FEB-16:02 | 583.20 | 414.76 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 13.08 | 0.00 |
March | 1682.95 | 20-MAR-15:01 | 680.40 | 483.89 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.46 |
April | 1663.72 | 05-APR-15:02 | 583.20 | 414.76 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 23.72 | 0.00 |
May | 1641.30 | 01-MAY-15:02 | 583.20 | 414.76 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 43.41 | 0.00 |
June | 1637.15 | 01-JUN-15:02 | 583.20 | 414.76 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 43.63 | 0.00 |
July | 1678.76 | 28-JUL-15:02 | 583.20 | 414.76 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 72.72 | 0.00 |
August | 1669.98 | 31-AUG-15:02 | 583.20 | 414.76 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 56.12 | 0.00 |
September | 1676.67 | 16-SEP-15:02 | 324.00 | 488.83 | 449.03 | 0.00 | 0.00 | 0.00 | 0.00 | 46.89 | 0.00 |
October | 1679.17 | 25-OCT-15:02 | 583.20 | 414.76 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 37.52 | 0.00 |
November | 1668.47 | 07-NOV-16:02 | 583.20 | 414.76 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 31.64 | 0.00 |
December | 1694.08 | 03-DEC-16:02 | 324.00 | 488.83 | 449.03 | 0.00 | 0.00 | 0.00 | 0.00 | 7.91 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1637.15 | 324.00 | 414.76 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1728.98 | 680.40 | 488.83 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 72.72 | 21.46 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 20835.59 | 13-JAN-23:40 | 53977.54 | 2548.93 | 13495.81 | 0.00 | 0.00 | 0.00 | 0.00 | 22.84 | 0.00 |
February | 20990.78 | 17-FEB-23:40 | 53977.54 | 2548.93 | 13495.81 | 0.00 | 0.00 | 0.00 | 0.00 | 21.60 | 0.00 |
March | 21830.87 | 13-MAR-18:10 | 125947.58 | 20391.43 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 183.98 | 0.00 |
April | 22828.63 | 17-APR-18:10 | 125947.58 | 20391.43 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 240.89 | 0.00 |
May | 23192.50 | 22-MAY-18:10 | 125947.58 | 20391.43 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 249.59 | 0.00 |
June | 23582.88 | 29-JUN-18:10 | 125947.58 | 20391.43 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 235.92 | 0.00 |
July | 23846.50 | 27-JUL-18:10 | 125947.58 | 20391.43 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 287.11 | 0.00 |
August | 23459.25 | 02-AUG-18:10 | 125947.58 | 20391.43 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 234.42 | 0.00 |
September | 23011.37 | 18-SEP-18:10 | 125947.58 | 20391.43 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 251.64 | 0.00 |
October | 22387.99 | 05-OCT-18:10 | 125947.58 | 20391.43 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 206.92 | 0.00 |
November | 21672.56 | 03-NOV-22:40 | 53977.54 | 2548.93 | 13495.81 | 0.00 | 0.00 | 0.00 | 0.00 | 102.66 | 0.00 |
December | 21132.83 | 08-DEC-23:40 | 53977.54 | 2548.93 | 13495.81 | 0.00 | 0.00 | 0.00 | 0.00 | 49.02 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 20835.59 | 53977.54 | 2548.93 | 13495.81 | 0.00 | 0.00 | 0.00 | 0.00 | 21.60 | 0.00 | |
Maximum of Months | 23846.50 | 125947.58 | 20391.43 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 287.11 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 22093.35 | 02-JAN-19:10 | 125947.58 | 20391.43 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 44.08 | 0.00 |
February | 22280.19 | 17-FEB-23:40 | 53977.54 | 2548.93 | 13495.81 | 0.00 | 0.00 | 0.00 | 0.00 | 18.91 | 0.00 |
March | 23173.76 | 13-MAR-18:10 | 125947.58 | 20391.43 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 181.24 | 0.00 |
April | 24172.36 | 17-APR-18:10 | 125947.58 | 20391.43 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 238.66 | 0.00 |
May | 24559.52 | 22-MAY-18:10 | 125947.58 | 20391.43 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 247.30 | 0.00 |
June | 24919.77 | 29-JUN-18:10 | 125947.58 | 20391.43 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 234.13 | 0.00 |
July | 25182.38 | 27-JUL-18:10 | 125947.58 | 20391.43 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 285.48 | 0.00 |
August | 24786.72 | 02-AUG-18:10 | 125947.58 | 20391.43 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 232.66 | 0.00 |
September | 24310.40 | 18-SEP-18:10 | 125947.58 | 20391.43 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 249.94 | 0.00 |
October | 23691.48 | 05-OCT-18:10 | 125947.58 | 20391.43 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 204.87 | 0.00 |
November | 22944.93 | 02-NOV-18:10 | 125947.58 | 20391.43 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 158.57 | 0.00 |
December | 22401.89 | 07-DEC-19:10 | 125947.58 | 20391.43 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 79.16 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 22093.35 | 53977.54 | 2548.93 | 13495.81 | 0.00 | 0.00 | 0.00 | 0.00 | 18.91 | 0.00 | |
Maximum of Months | 25182.38 | 125947.58 | 20391.43 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 285.48 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 29016.77 | 01-JAN-11:50 | 800.57 | 340.26 | 15112.11 | 18744.03 | 0.00 | 0.00 | 0.00 | 56.43 | 0.00 |
February | 29205.74 | 11-FEB-11:50 | 800.57 | 283.55 | 15112.11 | 18744.03 | 0.00 | 0.00 | 0.00 | 96.41 | 0.00 |
March | 29387.15 | 27-MAR-10:40 | 1067.42 | 567.10 | 30224.21 | 37488.05 | 0.00 | 0.00 | 0.00 | 54.68 | 0.00 |
April | 30274.81 | 15-APR-10:50 | 800.57 | 283.55 | 15112.11 | 18744.03 | 0.00 | 0.00 | 0.00 | 146.08 | 0.00 |
May | 30301.64 | 31-MAY-10:50 | 533.71 | 283.55 | 15112.11 | 18744.03 | 0.00 | 0.00 | 0.00 | 220.71 | 0.00 |
June | 30637.70 | 11-JUN-10:50 | 800.57 | 340.26 | 15112.11 | 18744.03 | 0.00 | 0.00 | 0.00 | 182.43 | 0.00 |
July | 30917.08 | 23-JUL-10:50 | 800.57 | 340.26 | 15112.11 | 18744.03 | 0.00 | 0.00 | 0.00 | 226.74 | 0.00 |
August | 30600.54 | 19-AUG-10:40 | 1601.14 | 567.10 | 30224.21 | 37488.05 | 0.00 | 0.00 | 0.00 | 194.74 | 0.00 |
September | 30510.58 | 24-SEP-10:50 | 800.57 | 340.26 | 15112.11 | 18744.03 | 0.00 | 0.00 | 0.00 | 177.25 | 0.00 |
October | 30387.61 | 07-OCT-10:40 | 1601.14 | 567.10 | 30224.21 | 37488.05 | 0.00 | 0.00 | 0.00 | 185.11 | 0.00 |
November | 29251.67 | 03-NOV-10:50 | 533.71 | 283.55 | 15112.11 | 18744.03 | 0.00 | 0.00 | 0.00 | 109.17 | 0.00 |
December | 29223.04 | 09-DEC-11:40 | 1601.14 | 567.10 | 30224.21 | 37488.05 | 0.00 | 0.00 | 0.00 | 82.73 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 29016.77 | 533.71 | 283.55 | 15112.11 | 18744.03 | 0.00 | 0.00 | 0.00 | 54.68 | 0.00 | |
Maximum of Months | 30917.08 | 1601.14 | 567.10 | 30224.21 | 37488.05 | 0.00 | 0.00 | 0.00 | 226.74 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6348.01 | 01-JAN-11:35 | 1596.96 | 904.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.97 | 0.00 |
February | 6464.67 | 11-FEB-11:35 | 1596.96 | 754.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 159.35 | 0.00 |
March | 6377.72 | 04-MAR-11:35 | 1596.96 | 754.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 147.06 | 0.00 |
April | 6781.01 | 15-APR-10:35 | 1596.96 | 754.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 200.26 | 0.00 |
May | 6931.67 | 31-MAY-10:35 | 1064.64 | 754.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 270.46 | 0.00 |
June | 7227.45 | 11-JUN-10:35 | 1596.96 | 904.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 232.17 | 0.00 |
July | 7400.77 | 29-JUL-10:35 | 1596.96 | 754.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 255.96 | 0.00 |
August | 7241.91 | 19-AUG-10:35 | 1596.96 | 754.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 245.47 | 0.00 |
September | 7287.70 | 24-SEP-10:35 | 1596.96 | 904.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 218.46 | 0.00 |
October | 7118.15 | 07-OCT-10:35 | 1596.96 | 754.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 237.97 | 0.00 |
November | 6685.07 | 08-NOV-11:35 | 1064.64 | 754.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 145.87 | 0.00 |
December | 6651.05 | 09-DEC-11:35 | 1596.96 | 754.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 142.51 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6348.01 | 1064.64 | 754.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.97 | 0.00 | |
Maximum of Months | 7400.77 | 1596.96 | 904.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 270.46 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.832936E+12 | 520208.21 | 06-JAN-20:10 | 0.434275E+12 | 349697.67 | 29-JAN-17:19 |
February | 0.793916E+12 | 532932.23 | 10-FEB-20:10 | 0.390107E+12 | 350826.07 | 05-FEB-17:00 |
March | 0.903291E+12 | 545308.86 | 13-MAR-19:10 | 0.431769E+12 | 351042.42 | 19-MAR-16:49 |
April | 0.954514E+12 | 557253.57 | 14-APR-19:10 | 0.408861E+12 | 345899.58 | 30-APR-16:40 |
May | 0.108626E+13 | 593357.95 | 29-MAY-19:10 | 0.411388E+12 | 343046.55 | 07-MAY-16:30 |
June | 0.112218E+13 | 612478.45 | 29-JUN-19:19 | 0.391168E+12 | 340464.49 | 04-JUN-16:00 |
July | 0.117986E+13 | 626175.88 | 27-JUL-18:10 | 0.399031E+12 | 336739.54 | 04-JUL-16:49 |
August | 0.117515E+13 | 608499.58 | 02-AUG-19:10 | 0.397754E+12 | 336671.93 | 27-AUG-16:00 |
September | 0.112298E+13 | 621202.38 | 18-SEP-18:19 | 0.385466E+12 | 334497.49 | 03-SEP-16:00 |
October | 0.110423E+13 | 595599.98 | 03-OCT-19:10 | 0.403290E+12 | 333494.19 | 01-OCT-16:19 |
November | 0.974049E+12 | 572376.26 | 29-NOV-20:10 | 0.400243E+12 | 344317.59 | 12-NOV-18:30 |
December | 0.885601E+12 | 535563.67 | 10-DEC-20:10 | 0.428326E+12 | 352716.65 | 17-DEC-17:00 |
Annual Sum or Average | 0.121350E+14 | 0.488168E+13 | ||||
Minimum of Months | 0.793916E+12 | 520208.21 | 0.385466E+12 | 333494.19 | ||
Maximum of Months | 0.117986E+13 | 626175.88 | 0.434275E+12 | 352716.65 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [J] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.997859E+11 | 0.250556E+11 | 0.148746E+12 | 0.577258E+11 | 0.148835E+12 | 0.338502E+11 | 0.00 | 0.262151E+12 | 0.00 | 0.00 | 0.426736E+11 | 0.770703E+10 | 0.00 |
February | 0.901073E+11 | 0.216207E+11 | 0.134341E+12 | 0.521396E+11 | 0.135806E+12 | 0.319215E+11 | 0.00 | 0.276178E+12 | 0.00 | 0.00 | 0.390476E+11 | 0.696416E+10 | 0.00 |
March | 0.995228E+11 | 0.225721E+11 | 0.148757E+12 | 0.577286E+11 | 0.150947E+12 | 0.360341E+11 | 0.00 | 0.329865E+12 | 0.00 | 0.00 | 0.437375E+11 | 0.770550E+10 | 0.00 |
April | 0.965474E+11 | 0.205092E+11 | 0.143913E+12 | 0.558635E+11 | 0.149020E+12 | 0.376191E+11 | 0.00 | 0.394556E+12 | 0.00 | 0.00 | 0.427907E+11 | 0.746740E+10 | 0.00 |
May | 0.996636E+11 | 0.199884E+11 | 0.148757E+12 | 0.577273E+11 | 0.156958E+12 | 0.409283E+11 | 0.00 | 0.503221E+12 | 0.00 | 0.00 | 0.448538E+11 | 0.770645E+10 | 0.00 |
June | 0.963626E+11 | 0.187967E+11 | 0.143963E+12 | 0.558662E+11 | 0.154107E+12 | 0.406096E+11 | 0.00 | 0.555244E+12 | 0.00 | 0.00 | 0.435178E+11 | 0.745896E+10 | 0.00 |
July | 0.998551E+11 | 0.195979E+11 | 0.148708E+12 | 0.577246E+11 | 0.160427E+12 | 0.421419E+11 | 0.00 | 0.592290E+12 | 0.00 | 0.00 | 0.449650E+11 | 0.771466E+10 | 0.00 |
August | 0.995413E+11 | 0.206594E+11 | 0.148768E+12 | 0.577287E+11 | 0.158919E+12 | 0.420653E+11 | 0.00 | 0.588352E+12 | 0.00 | 0.00 | 0.449515E+11 | 0.770657E+10 | 0.00 |
September | 0.965794E+11 | 0.212802E+11 | 0.143924E+12 | 0.558636E+11 | 0.154580E+12 | 0.405829E+11 | 0.00 | 0.552925E+12 | 0.00 | 0.00 | 0.435243E+11 | 0.746839E+10 | 0.00 |
October | 0.997606E+11 | 0.233732E+11 | 0.148735E+12 | 0.577257E+11 | 0.158162E+12 | 0.411089E+11 | 0.00 | 0.516331E+12 | 0.00 | 0.00 | 0.448770E+11 | 0.770534E+10 | 0.00 |
November | 0.965244E+11 | 0.238539E+11 | 0.143978E+12 | 0.558644E+11 | 0.149028E+12 | 0.376705E+11 | 0.00 | 0.411026E+12 | 0.00 | 0.00 | 0.424295E+11 | 0.745108E+10 | 0.00 |
December | 0.998619E+11 | 0.253160E+11 | 0.148708E+12 | 0.577246E+11 | 0.149859E+12 | 0.354465E+11 | 0.00 | 0.311584E+12 | 0.00 | 0.00 | 0.429661E+11 | 0.771518E+10 | 0.00 |
Annual Sum or Average | 0.117411E+13 | 0.262623E+12 | 0.175130E+13 | 0.679683E+12 | 0.182665E+13 | 0.459979E+12 | 0.00 | 0.529372E+13 | 0.00 | 0.00 | 0.520334E+12 | 0.907707E+11 | 0.00 |
Minimum of Months | 0.901073E+11 | 0.187967E+11 | 0.134341E+12 | 0.521396E+11 | 0.135806E+12 | 0.319215E+11 | 0.00 | 0.262151E+12 | 0.00 | 0.00 | 0.390476E+11 | 0.696416E+10 | 0.00 |
Maximum of Months | 0.998619E+11 | 0.253160E+11 | 0.148768E+12 | 0.577287E+11 | 0.160427E+12 | 0.421419E+11 | 0.00 | 0.592290E+12 | 0.00 | 0.00 | 0.449650E+11 | 0.771518E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.151918E+12 | 0.00 | 0.473691E+11 | 0.00 | 0.234987E+12 | 0.00 | 0.00 |
February | 0.137204E+12 | 0.00 | 0.418072E+11 | 0.00 | 0.211096E+12 | 0.00 | 0.00 |
March | 0.152024E+12 | 0.00 | 0.500743E+11 | 0.00 | 0.229671E+12 | 0.00 | 0.00 |
April | 0.146956E+12 | 0.00 | 0.454739E+11 | 0.00 | 0.216431E+12 | 0.00 | 0.00 |
May | 0.151978E+12 | 0.00 | 0.419328E+11 | 0.00 | 0.217476E+12 | 0.00 | 0.00 |
June | 0.147114E+12 | 0.00 | 0.381742E+11 | 0.00 | 0.205880E+12 | 0.00 | 0.00 |
July | 0.151820E+12 | 0.00 | 0.365293E+11 | 0.00 | 0.210681E+12 | 0.00 | 0.00 |
August | 0.152039E+12 | 0.00 | 0.336675E+11 | 0.00 | 0.212047E+12 | 0.00 | 0.00 |
September | 0.146971E+12 | 0.00 | 0.292034E+11 | 0.00 | 0.209292E+12 | 0.00 | 0.00 |
October | 0.151903E+12 | 0.00 | 0.291241E+11 | 0.00 | 0.222262E+12 | 0.00 | 0.00 |
November | 0.147091E+12 | 0.00 | 0.321039E+11 | 0.00 | 0.221048E+12 | 0.00 | 0.00 |
December | 0.151820E+12 | 0.00 | 0.434017E+11 | 0.00 | 0.233103E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.178884E+13 | 0.00 | 0.468861E+12 | 0.00 | 0.262398E+13 | 0.00 | 0.00 |
Minimum of Months | 0.137204E+12 | 0.00 | 0.291241E+11 | 0.00 | 0.205880E+12 | 0.00 | 0.00 |
Maximum of Months | 0.152039E+12 | 0.00 | 0.500743E+11 | 0.00 | 0.234987E+12 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 93091.76 | 02-JAN-20:10 | 16690.39 | 01-JAN-00:10 | 89674.66 | 02-JAN-07:10 | 40537.60 | 02-JAN-07:19 | 69289.24 | 02-JAN-16:19 | 16022.02 | 04-JAN-17:00 | 0.00 | 01-JAN-00:10 |
February | 93091.76 | 01-FEB-20:10 | 16690.39 | 01-FEB-00:10 | 89674.66 | 01-FEB-07:10 | 40537.60 | 01-FEB-07:19 | 72202.04 | 11-FEB-16:19 | 16261.20 | 11-FEB-11:50 | 0.00 | 01-FEB-00:10 |
March | 93091.76 | 01-MAR-20:10 | 16690.39 | 01-MAR-00:10 | 89674.66 | 01-MAR-07:10 | 40537.60 | 01-MAR-07:19 | 69031.21 | 25-MAR-15:09 | 16262.39 | 14-MAR-10:39 | 0.00 | 01-MAR-00:10 |
April | 93091.76 | 03-APR-19:10 | 16690.39 | 01-APR-00:10 | 89674.66 | 03-APR-06:10 | 40537.60 | 03-APR-06:19 | 72116.33 | 14-APR-15:20 | 16418.43 | 01-APR-16:40 | 0.00 | 01-APR-00:10 |
May | 93091.76 | 01-MAY-19:10 | 16690.39 | 01-MAY-00:10 | 89674.66 | 01-MAY-06:10 | 40537.60 | 01-MAY-06:19 | 72296.83 | 29-MAY-18:19 | 16564.63 | 28-MAY-10:39 | 0.00 | 01-MAY-00:10 |
June | 93091.76 | 01-JUN-19:10 | 16690.39 | 01-JUN-00:10 | 89674.66 | 01-JUN-06:10 | 40537.60 | 01-JUN-06:19 | 73398.88 | 29-JUN-15:20 | 16655.62 | 26-JUN-10:39 | 0.00 | 01-JUN-00:10 |
July | 93091.76 | 03-JUL-19:10 | 16690.39 | 01-JUL-00:10 | 89674.66 | 03-JUL-06:10 | 40537.60 | 03-JUL-06:19 | 74737.69 | 29-JUL-15:20 | 16829.26 | 29-JUL-10:39 | 0.00 | 01-JUL-00:10 |
August | 93091.76 | 01-AUG-19:10 | 16690.39 | 01-AUG-00:10 | 89674.66 | 01-AUG-06:10 | 40537.60 | 01-AUG-06:19 | 73943.94 | 20-AUG-15:20 | 16738.30 | 20-AUG-10:50 | 0.00 | 01-AUG-00:10 |
September | 93091.76 | 01-SEP-19:10 | 16690.39 | 01-SEP-00:10 | 89674.66 | 01-SEP-06:10 | 40537.60 | 01-SEP-06:19 | 74877.68 | 30-SEP-15:20 | 16647.68 | 24-SEP-10:50 | 0.00 | 01-SEP-00:10 |
October | 93091.76 | 02-OCT-19:10 | 16690.39 | 01-OCT-00:10 | 89674.66 | 02-OCT-06:10 | 40537.60 | 02-OCT-06:19 | 73901.92 | 07-OCT-15:20 | 16582.26 | 03-OCT-10:50 | 0.00 | 01-OCT-00:10 |
November | 93091.76 | 01-NOV-19:10 | 16690.39 | 01-NOV-00:10 | 89674.66 | 01-NOV-06:10 | 40537.60 | 01-NOV-06:19 | 71249.42 | 02-NOV-15:09 | 16407.35 | 03-NOV-10:39 | 0.00 | 01-NOV-00:10 |
December | 93091.76 | 01-DEC-20:10 | 16690.39 | 01-DEC-00:10 | 89674.66 | 01-DEC-07:10 | 40537.60 | 01-DEC-07:19 | 71117.33 | 08-DEC-16:10 | 16181.78 | 24-DEC-11:50 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 93091.76 | 16690.39 | 89674.66 | 40537.60 | 69031.21 | 16022.02 | 0.00 | |||||||
Maximum of Months | 93091.76 | 16690.39 | 89674.66 | 40537.60 | 74877.68 | 16829.26 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY {Maximum} [W] | HEATRECOVERY:ELECTRICITY {TIMESTAMP} | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 220518.53 | 02-JAN-13:00 | 0.00 | 0.00 | 16791.79 | 01-JAN-09:20 | 4739.42 | 18-JAN-07:10 | 0.00 |
February | 241994.72 | 11-FEB-16:19 | 0.00 | 0.00 | 16791.79 | 01-FEB-09:20 | 4739.31 | 15-FEB-07:10 | 0.00 |
March | 233815.87 | 13-MAR-15:20 | 0.00 | 0.00 | 16791.79 | 01-MAR-02:49 | 4738.65 | 02-MAR-19:10 | 0.00 |
April | 266696.36 | 14-APR-15:20 | 0.00 | 0.00 | 16791.79 | 01-APR-00:10 | 4738.77 | 04-APR-06:10 | 0.00 |
May | 281604.93 | 29-MAY-18:10 | 0.00 | 0.00 | 16791.79 | 01-MAY-00:10 | 4738.73 | 30-MAY-18:10 | 0.00 |
June | 293742.52 | 08-JUN-18:10 | 0.00 | 0.00 | 16791.79 | 01-JUN-00:10 | 4738.60 | 15-JUN-18:10 | 0.00 |
July | 317380.64 | 27-JUL-18:10 | 0.00 | 0.00 | 16791.79 | 01-JUL-00:10 | 4738.75 | 27-JUL-18:10 | 0.00 |
August | 307724.77 | 21-AUG-15:00 | 0.00 | 0.00 | 16791.79 | 01-AUG-00:10 | 4738.76 | 24-AUG-18:10 | 0.00 |
September | 305064.73 | 18-SEP-18:10 | 0.00 | 0.00 | 16791.79 | 01-SEP-00:10 | 4738.62 | 21-SEP-18:10 | 0.00 |
October | 287699.51 | 03-OCT-15:20 | 0.00 | 0.00 | 16791.79 | 01-OCT-00:10 | 4738.65 | 31-OCT-06:10 | 0.00 |
November | 251934.19 | 03-NOV-15:20 | 0.00 | 0.00 | 16791.79 | 01-NOV-00:10 | 4738.74 | 08-NOV-07:10 | 0.00 |
December | 223892.20 | 08-DEC-16:10 | 0.00 | 0.00 | 16791.79 | 01-DEC-00:10 | 4738.77 | 26-DEC-19:10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 220518.53 | 0.00 | 0.00 | 16791.79 | 4738.60 | 0.00 | |||
Maximum of Months | 317380.64 | 0.00 | 0.00 | 16791.79 | 4739.42 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 520208.21 | 06-JAN-20:10 | 93091.76 | 88971.67 | 16690.39 | 33012.66 | 62087.48 | 15583.73 | 0.00 | 187916.26 | 0.00 |
February | 532932.23 | 10-FEB-20:10 | 93091.76 | 88971.67 | 16690.39 | 33012.66 | 64196.09 | 15739.06 | 0.00 | 198018.28 | 0.00 |
March | 545308.86 | 13-MAR-19:10 | 93091.76 | 88971.67 | 16690.39 | 33012.66 | 64357.37 | 15962.20 | 0.00 | 209749.18 | 0.00 |
April | 557253.57 | 14-APR-19:10 | 93091.76 | 88971.67 | 16690.39 | 33012.66 | 66055.66 | 15959.86 | 0.00 | 220401.56 | 0.00 |
May | 593357.95 | 29-MAY-19:10 | 87949.43 | 87485.24 | 16690.39 | 32961.22 | 68778.63 | 16217.71 | 0.00 | 260446.72 | 0.00 |
June | 612478.45 | 29-JUN-19:19 | 93091.76 | 88971.67 | 16690.39 | 33025.38 | 69187.21 | 16301.06 | 0.00 | 271735.62 | 0.00 |
July | 626175.88 | 27-JUL-18:10 | 82800.17 | 79617.06 | 0.00 | 32686.23 | 72579.08 | 16647.58 | 0.00 | 317380.64 | 0.00 |
August | 608499.58 | 02-AUG-19:10 | 93091.76 | 88971.67 | 16690.39 | 33012.66 | 69025.97 | 16315.14 | 0.00 | 268065.48 | 0.00 |
September | 621202.38 | 18-SEP-18:19 | 82800.17 | 79617.06 | 16690.39 | 32707.97 | 71494.32 | 16509.21 | 0.00 | 297360.01 | 0.00 |
October | 595599.98 | 03-OCT-19:10 | 93091.76 | 88971.67 | 16690.39 | 33012.66 | 66618.68 | 16228.22 | 0.00 | 257806.00 | 0.00 |
November | 572376.26 | 29-NOV-20:10 | 93091.76 | 88971.67 | 16690.39 | 33012.66 | 63327.66 | 16184.13 | 0.00 | 237772.36 | 0.00 |
December | 535563.67 | 10-DEC-20:10 | 87949.43 | 87485.24 | 16690.39 | 32961.22 | 64364.09 | 15967.23 | 0.00 | 207345.66 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 520208.21 | 82800.17 | 79617.06 | 0.00 | 32686.23 | 62087.48 | 15583.73 | 0.00 | 187916.26 | 0.00 | |
Maximum of Months | 626175.88 | 93091.76 | 88971.67 | 16690.39 | 33025.38 | 72579.08 | 16647.58 | 0.00 | 317380.64 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 104248.32 | 02-JAN-18:10 | 0.00 | 79171.49 | 18-JAN-11:39 | 0.00 | 222392.17 | 17-JAN-21:19 | 0.00 |
February | 104248.32 | 01-FEB-18:10 | 0.00 | 87145.53 | 06-FEB-11:39 | 0.00 | 221607.00 | 01-FEB-21:40 | 0.00 |
March | 104248.32 | 01-MAR-18:10 | 0.00 | 98398.35 | 20-MAR-10:39 | 0.00 | 217147.95 | 01-MAR-21:19 | 0.00 |
April | 104248.32 | 01-APR-17:10 | 0.00 | 83307.82 | 19-APR-10:39 | 0.00 | 215262.11 | 03-APR-20:00 | 0.00 |
May | 104248.32 | 01-MAY-17:10 | 0.00 | 78129.61 | 01-MAY-10:39 | 0.00 | 213367.98 | 01-MAY-20:30 | 0.00 |
June | 104248.32 | 01-JUN-17:10 | 0.00 | 76181.39 | 13-JUN-10:39 | 0.00 | 211412.46 | 01-JUN-20:30 | 0.00 |
July | 104248.32 | 01-JUL-17:10 | 0.00 | 73138.83 | 07-JUL-10:39 | 0.00 | 210091.75 | 05-JUL-20:49 | 0.00 |
August | 104248.32 | 01-AUG-17:10 | 0.00 | 71362.39 | 29-AUG-10:39 | 0.00 | 211070.36 | 31-AUG-20:00 | 0.00 |
September | 104248.32 | 01-SEP-17:10 | 0.00 | 70238.02 | 05-SEP-10:39 | 0.00 | 212809.14 | 29-SEP-20:49 | 0.00 |
October | 104248.32 | 02-OCT-17:10 | 0.00 | 64827.60 | 02-OCT-10:39 | 0.00 | 215047.34 | 31-OCT-20:00 | 0.00 |
November | 104248.32 | 01-NOV-17:10 | 0.00 | 71946.31 | 27-NOV-11:39 | 0.00 | 216839.17 | 30-NOV-21:40 | 0.00 |
December | 104248.32 | 01-DEC-18:10 | 0.00 | 80582.32 | 21-DEC-11:39 | 0.00 | 220138.69 | 31-DEC-22:40 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 104248.32 | 0.00 | 64827.60 | 0.00 | 210091.75 | 0.00 | |||
Maximum of Months | 104248.32 | 0.00 | 98398.35 | 0.00 | 222392.17 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.86 | 0.50 | 21.86 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.50 | 21.86 | 0.50 | 21.86 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.86 | 0.50 | 21.86 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 21.68 | 1.67 | 21.68 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 21.69 | 5.67 | 21.69 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 21.70 | 8.17 | 21.70 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 21.69 | 3.83 | 21.69 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 21.68 | 2.00 | 21.68 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 21.33 | 21.69 | 21.33 | 21.69 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 21.70 | 8.17 | 21.70 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.94 | 0.67 | 21.94 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.70 | 0.17 | 21.70 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.76 | 0.33 | 21.76 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.68 | 0.17 | 21.68 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.73 | 0.50 | 21.73 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.70 | 0.17 | 21.70 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 2.00 | 21.79 | 2.00 | 21.79 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.94 | 0.67 | 21.94 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.72 | 0.17 | 21.72 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.71 | 0.33 | 21.71 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.50 | 21.72 | 0.50 | 21.72 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.72 | 0.33 | 21.72 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 21.82 | 2.50 | 21.82 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 21.95 | 3.00 | 21.95 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.71 | 1.00 | 21.71 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.70 | 1.00 | 21.70 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.67 | 0.33 | 21.67 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 21.71 | 1.67 | 21.71 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 21.73 | 2.17 | 21.73 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 21.84 | 4.50 | 21.84 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 21.91 | 7.17 | 21.91 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 21.85 | 3.50 | 21.85 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 21.87 | 3.17 | 21.87 |
Annual Sum or Average | 0.00 | 0.00 | 30.00 | 21.84 | 30.00 | 21.84 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 21.95 | 7.17 | 21.95 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.24 | 0.00 | 21.24 | 0.00 | 21.24 |
February | 672.00 | 21.14 | 0.00 | 21.14 | 0.00 | 21.14 |
March | 744.00 | 21.07 | 0.00 | 21.07 | 0.00 | 21.07 |
April | 720.00 | 21.04 | 0.00 | 21.04 | 0.00 | 21.04 |
May | 744.00 | 21.06 | 0.00 | 21.06 | 0.00 | 21.06 |
June | 720.00 | 21.07 | 0.00 | 21.07 | 0.00 | 21.07 |
July | 744.00 | 21.12 | 0.00 | 21.12 | 0.00 | 21.12 |
August | 744.00 | 21.21 | 0.00 | 21.21 | 0.00 | 21.21 |
September | 720.00 | 21.25 | 0.00 | 21.25 | 0.00 | 21.25 |
October | 744.00 | 21.28 | 0.00 | 21.28 | 0.00 | 21.28 |
November | 720.00 | 21.30 | 0.00 | 21.30 | 0.00 | 21.30 |
December | 744.00 | 21.29 | 0.00 | 21.29 | 0.00 | 21.29 |
Annual Sum or Average | 8760.00 | 21.17 | 0.00 | 21.17 | 0.00 | 21.17 |
Minimum of Months | 672.00 | 21.04 | 0.00 | 21.04 | 0.00 | 21.04 |
Maximum of Months | 744.00 | 21.30 | 0.00 | 21.30 | 0.00 | 21.30 |
Report: ComfortReportSimple55Monthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 687.83 | 21.19 | 26.83 | 21.26 | 0.00 | 21.26 |
February | 627.00 | 21.20 | 17.00 | 21.23 | 5.17 | 21.23 |
March | 738.17 | 21.19 | 0.00 | 21.19 | 0.00 | 21.19 |
April | 719.00 | 21.20 | 0.00 | 21.20 | 0.00 | 21.20 |
May | 744.00 | 21.20 | 0.00 | 21.20 | 0.00 | 21.20 |
June | 720.00 | 21.28 | 0.00 | 21.28 | 0.00 | 21.28 |
July | 744.00 | 21.38 | 0.00 | 21.38 | 0.00 | 21.38 |
August | 737.33 | 21.39 | 0.00 | 21.39 | 0.00 | 21.39 |
September | 662.50 | 21.50 | 20.50 | 21.54 | 0.00 | 21.54 |
October | 637.50 | 21.44 | 57.33 | 21.57 | 0.00 | 21.57 |
November | 637.67 | 21.31 | 48.50 | 21.44 | 0.00 | 21.44 |
December | 674.17 | 21.21 | 40.67 | 21.33 | 0.00 | 21.33 |
Annual Sum or Average | 8329.17 | 21.29 | 210.83 | 21.33 | 5.17 | 21.33 |
Minimum of Months | 627.00 | 21.19 | 0.00 | 21.19 | 0.00 | 21.19 |
Maximum of Months | 744.00 | 21.50 | 57.33 | 21.57 | 5.17 | 21.57 |
Report: ComfortReportSimple55Monthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.09 | 0.00 | 21.09 | 0.00 | 21.09 |
February | 672.00 | 21.12 | 0.00 | 21.12 | 0.00 | 21.12 |
March | 744.00 | 21.16 | 0.00 | 21.16 | 0.00 | 21.16 |
April | 720.00 | 21.21 | 0.00 | 21.21 | 0.00 | 21.21 |
May | 744.00 | 21.26 | 0.00 | 21.26 | 0.00 | 21.26 |
June | 720.00 | 21.30 | 0.00 | 21.30 | 0.00 | 21.30 |
July | 744.00 | 21.33 | 0.00 | 21.33 | 0.00 | 21.33 |
August | 744.00 | 21.31 | 0.00 | 21.31 | 0.00 | 21.31 |
September | 720.00 | 21.32 | 0.00 | 21.32 | 0.00 | 21.32 |
October | 744.00 | 21.28 | 0.00 | 21.28 | 0.00 | 21.28 |
November | 720.00 | 21.19 | 0.00 | 21.19 | 0.00 | 21.19 |
December | 744.00 | 21.12 | 0.00 | 21.12 | 0.00 | 21.12 |
Annual Sum or Average | 8760.00 | 21.23 | 0.00 | 21.23 | 0.00 | 21.23 |
Minimum of Months | 672.00 | 21.09 | 0.00 | 21.09 | 0.00 | 21.09 |
Maximum of Months | 744.00 | 21.33 | 0.00 | 21.33 | 0.00 | 21.33 |
Report: ComfortReportSimple55Monthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.01 | 0.00 | 21.01 | 0.00 | 21.01 |
February | 672.00 | 21.03 | 0.00 | 21.03 | 0.00 | 21.03 |
March | 744.00 | 21.04 | 0.00 | 21.04 | 0.00 | 21.04 |
April | 720.00 | 21.06 | 0.00 | 21.06 | 0.00 | 21.06 |
May | 744.00 | 21.14 | 0.00 | 21.14 | 0.00 | 21.14 |
June | 720.00 | 21.25 | 0.00 | 21.25 | 0.00 | 21.25 |
July | 744.00 | 21.28 | 0.00 | 21.28 | 0.00 | 21.28 |
August | 744.00 | 21.21 | 0.00 | 21.21 | 0.00 | 21.21 |
September | 720.00 | 21.21 | 0.00 | 21.21 | 0.00 | 21.21 |
October | 744.00 | 21.11 | 0.00 | 21.11 | 0.00 | 21.11 |
November | 720.00 | 21.06 | 0.00 | 21.06 | 0.00 | 21.06 |
December | 744.00 | 21.02 | 0.00 | 21.02 | 0.00 | 21.02 |
Annual Sum or Average | 8760.00 | 21.12 | 0.00 | 21.12 | 0.00 | 21.12 |
Minimum of Months | 672.00 | 21.01 | 0.00 | 21.01 | 0.00 | 21.01 |
Maximum of Months | 744.00 | 21.28 | 0.00 | 21.28 | 0.00 | 21.28 |
Report: ComfortReportSimple55Monthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.00 | 0.00 | 21.00 | 0.00 | 21.00 |
February | 672.00 | 21.00 | 0.00 | 21.00 | 0.00 | 21.00 |
March | 744.00 | 21.01 | 1.50 | 21.01 | 1.50 | 21.01 |
April | 720.00 | 21.02 | 0.00 | 21.02 | 0.00 | 21.02 |
May | 744.00 | 21.07 | 0.00 | 21.07 | 0.00 | 21.07 |
June | 720.00 | 21.17 | 0.00 | 21.17 | 0.00 | 21.17 |
July | 744.00 | 21.20 | 0.00 | 21.20 | 0.00 | 21.20 |
August | 744.00 | 21.14 | 0.00 | 21.14 | 0.00 | 21.14 |
September | 720.00 | 21.13 | 0.00 | 21.13 | 0.00 | 21.13 |
October | 744.00 | 21.05 | 0.00 | 21.05 | 0.00 | 21.05 |
November | 720.00 | 21.02 | 0.00 | 21.02 | 0.00 | 21.02 |
December | 744.00 | 21.00 | 0.00 | 21.00 | 0.00 | 21.00 |
Annual Sum or Average | 8760.00 | 21.07 | 1.50 | 21.07 | 1.50 | 21.07 |
Minimum of Months | 672.00 | 21.00 | 0.00 | 21.00 | 0.00 | 21.00 |
Maximum of Months | 744.00 | 21.20 | 1.50 | 21.20 | 1.50 | 21.20 |
Report: ComfortReportSimple55Monthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 250.50 | 21.97 | 355.17 | 21.88 | 104.33 | 22.09 |
February | 216.17 | 22.01 | 349.17 | 21.84 | 93.83 | 22.05 |
March | 212.67 | 22.18 | 419.17 | 21.86 | 108.83 | 22.07 |
April | 142.83 | 22.61 | 489.67 | 21.79 | 104.00 | 21.99 |
May | 127.00 | 22.87 | 555.50 | 21.75 | 107.67 | 21.95 |
June | 110.67 | 23.07 | 572.33 | 21.72 | 105.67 | 21.92 |
July | 110.17 | 23.01 | 602.33 | 21.68 | 106.50 | 21.86 |
August | 122.17 | 22.95 | 553.83 | 21.76 | 109.67 | 21.96 |
September | 109.17 | 23.04 | 567.33 | 21.71 | 103.50 | 21.90 |
October | 132.00 | 22.77 | 545.83 | 21.75 | 106.33 | 21.95 |
November | 164.17 | 22.40 | 455.33 | 21.81 | 101.33 | 22.02 |
December | 206.00 | 22.17 | 396.17 | 21.87 | 105.33 | 22.08 |
Annual Sum or Average | 1903.50 | 22.47 | 5861.83 | 21.78 | 1257.00 | 21.98 |
Minimum of Months | 109.17 | 21.97 | 349.17 | 21.68 | 93.83 | 21.86 |
Maximum of Months | 250.50 | 23.07 | 602.33 | 21.88 | 109.67 | 22.09 |
Report: ComfortReportSimple55Monthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 674.83 | 21.42 | 25.67 | 21.46 | 0.00 | 21.46 |
February | 630.67 | 21.47 | 10.67 | 21.48 | 0.00 | 21.48 |
March | 737.00 | 21.46 | 0.00 | 21.46 | 0.00 | 21.46 |
April | 715.17 | 21.47 | 0.00 | 21.47 | 0.00 | 21.47 |
May | 732.00 | 21.51 | 0.00 | 21.51 | 0.00 | 21.51 |
June | 677.67 | 21.54 | 1.33 | 21.54 | 0.00 | 21.54 |
July | 704.33 | 21.56 | 2.17 | 21.57 | 0.00 | 21.57 |
August | 689.33 | 21.58 | 4.17 | 21.58 | 0.00 | 21.58 |
September | 590.67 | 21.61 | 23.33 | 21.66 | 0.00 | 21.66 |
October | 595.50 | 21.72 | 46.00 | 21.77 | 0.00 | 21.77 |
November | 602.67 | 21.59 | 48.67 | 21.66 | 0.00 | 21.66 |
December | 661.67 | 21.47 | 40.33 | 21.53 | 0.00 | 21.53 |
Annual Sum or Average | 8011.50 | 21.53 | 202.33 | 21.55 | 0.00 | 21.55 |
Minimum of Months | 590.67 | 21.42 | 0.00 | 21.46 | 0.00 | 21.46 |
Maximum of Months | 737.00 | 21.72 | 48.67 | 21.77 | 0.00 | 21.77 |
Report: ComfortReportSimple55Monthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.31 | 0.00 | 21.31 | 0.00 | 21.31 |
February | 672.00 | 21.34 | 0.00 | 21.34 | 0.00 | 21.34 |
March | 744.00 | 21.37 | 0.00 | 21.37 | 0.00 | 21.37 |
April | 720.00 | 21.42 | 0.00 | 21.42 | 0.00 | 21.42 |
May | 744.00 | 21.49 | 0.00 | 21.49 | 0.00 | 21.49 |
June | 720.00 | 21.55 | 0.00 | 21.55 | 0.00 | 21.55 |
July | 744.00 | 21.55 | 0.00 | 21.55 | 0.00 | 21.55 |
August | 744.00 | 21.55 | 0.00 | 21.55 | 0.00 | 21.55 |
September | 720.00 | 21.57 | 0.00 | 21.57 | 0.00 | 21.57 |
October | 744.00 | 21.54 | 0.00 | 21.54 | 0.00 | 21.54 |
November | 720.00 | 21.46 | 0.00 | 21.46 | 0.00 | 21.46 |
December | 744.00 | 21.36 | 0.00 | 21.36 | 0.00 | 21.36 |
Annual Sum or Average | 8760.00 | 21.46 | 0.00 | 21.46 | 0.00 | 21.46 |
Minimum of Months | 672.00 | 21.31 | 0.00 | 21.31 | 0.00 | 21.31 |
Maximum of Months | 744.00 | 21.57 | 0.00 | 21.57 | 0.00 | 21.57 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 692.67 | 21.49 | 3.33 | 21.49 | 2.00 | 21.50 |
February | 613.67 | 21.48 | 10.17 | 21.50 | 5.67 | 21.50 |
March | 662.67 | 21.44 | 6.83 | 21.45 | 4.50 | 21.46 |
April | 617.00 | 21.44 | 10.83 | 21.47 | 0.17 | 21.47 |
May | 604.83 | 21.36 | 17.17 | 21.41 | 0.67 | 21.41 |
June | 573.33 | 21.32 | 23.67 | 21.40 | 0.00 | 21.40 |
July | 580.17 | 21.29 | 39.50 | 21.42 | 0.00 | 21.42 |
August | 593.33 | 21.33 | 47.17 | 21.47 | 5.83 | 21.49 |
September | 564.67 | 21.30 | 38.00 | 21.42 | 0.00 | 21.42 |
October | 593.00 | 21.32 | 36.33 | 21.44 | 1.50 | 21.44 |
November | 613.00 | 21.40 | 19.83 | 21.46 | 1.50 | 21.47 |
December | 671.50 | 21.43 | 16.33 | 21.48 | 2.83 | 21.48 |
Annual Sum or Average | 7379.83 | 21.39 | 269.17 | 21.45 | 24.67 | 21.46 |
Minimum of Months | 564.67 | 21.29 | 3.33 | 21.40 | 0.00 | 21.40 |
Maximum of Months | 692.67 | 21.49 | 47.17 | 21.50 | 5.83 | 21.50 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 728.50 | 21.43 | 3.67 | 21.43 | 3.67 | 21.44 |
February | 644.33 | 21.49 | 9.17 | 21.49 | 8.17 | 21.49 |
March | 686.17 | 21.44 | 6.67 | 21.45 | 6.33 | 21.45 |
April | 635.00 | 21.48 | 6.50 | 21.50 | 0.17 | 21.50 |
May | 606.33 | 21.36 | 17.67 | 21.42 | 1.00 | 21.42 |
June | 570.83 | 21.32 | 26.17 | 21.41 | 0.00 | 21.41 |
July | 578.17 | 21.28 | 40.33 | 21.42 | 0.00 | 21.42 |
August | 596.50 | 21.34 | 40.17 | 21.46 | 6.33 | 21.48 |
September | 574.50 | 21.32 | 21.67 | 21.40 | 0.00 | 21.40 |
October | 623.67 | 21.41 | 15.83 | 21.45 | 4.00 | 21.46 |
November | 652.83 | 21.47 | 7.17 | 21.49 | 5.33 | 21.50 |
December | 707.50 | 21.42 | 10.00 | 21.44 | 10.00 | 21.46 |
Annual Sum or Average | 7604.33 | 21.40 | 205.00 | 21.45 | 45.00 | 21.45 |
Minimum of Months | 570.83 | 21.28 | 3.67 | 21.40 | 0.00 | 21.40 |
Maximum of Months | 728.50 | 21.49 | 40.33 | 21.50 | 10.00 | 21.50 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.39 | 2.17 | 21.39 | 2.17 | 21.40 |
February | 672.00 | 21.46 | 1.83 | 21.46 | 1.83 | 21.46 |
March | 744.00 | 21.49 | 5.00 | 21.49 | 5.00 | 21.50 |
April | 720.00 | 21.60 | 0.17 | 21.60 | 0.17 | 21.60 |
May | 744.00 | 21.67 | 1.50 | 21.67 | 1.50 | 21.68 |
June | 720.00 | 21.69 | 0.00 | 21.69 | 0.00 | 21.69 |
July | 744.00 | 21.71 | 0.17 | 21.71 | 0.17 | 21.71 |
August | 744.00 | 21.68 | 0.67 | 21.68 | 0.67 | 21.68 |
September | 720.00 | 21.68 | 0.00 | 21.68 | 0.00 | 21.68 |
October | 744.00 | 21.64 | 0.50 | 21.64 | 0.50 | 21.64 |
November | 720.00 | 21.54 | 0.67 | 21.54 | 0.67 | 21.54 |
December | 744.00 | 21.43 | 1.83 | 21.43 | 1.83 | 21.43 |
Annual Sum or Average | 8760.00 | 21.58 | 14.50 | 21.58 | 14.50 | 21.58 |
Minimum of Months | 672.00 | 21.39 | 0.00 | 21.39 | 0.00 | 21.40 |
Maximum of Months | 744.00 | 21.71 | 5.00 | 21.71 | 5.00 | 21.71 |
Report: ComfortReportSimple55Monthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 691.67 | 21.53 | 1.83 | 21.53 | 1.50 | 21.53 |
February | 604.67 | 21.50 | 4.17 | 21.50 | 4.17 | 21.50 |
March | 649.17 | 21.46 | 3.33 | 21.47 | 3.00 | 21.48 |
April | 587.00 | 21.37 | 0.67 | 21.38 | 0.00 | 21.38 |
May | 573.83 | 21.27 | 0.83 | 21.27 | 0.67 | 21.28 |
June | 543.00 | 21.23 | 3.67 | 21.25 | 0.00 | 21.25 |
July | 554.33 | 21.21 | 4.83 | 21.23 | 0.00 | 21.23 |
August | 572.83 | 21.27 | 13.33 | 21.31 | 5.83 | 21.33 |
September | 544.00 | 21.24 | 17.83 | 21.30 | 0.00 | 21.30 |
October | 572.83 | 21.27 | 6.50 | 21.29 | 0.83 | 21.29 |
November | 605.83 | 21.41 | 3.17 | 21.42 | 1.33 | 21.42 |
December | 674.83 | 21.46 | 4.17 | 21.47 | 4.00 | 21.48 |
Annual Sum or Average | 7174.00 | 21.36 | 64.33 | 21.38 | 21.33 | 21.38 |
Minimum of Months | 543.00 | 21.21 | 0.67 | 21.23 | 0.00 | 21.23 |
Maximum of Months | 691.67 | 21.53 | 17.83 | 21.53 | 5.83 | 21.53 |
Report: ComfortReportSimple55Monthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 732.83 | 21.50 | 5.17 | 21.50 | 5.17 | 21.50 |
February | 656.33 | 21.58 | 6.50 | 21.58 | 6.50 | 21.58 |
March | 679.00 | 21.50 | 2.83 | 21.51 | 2.83 | 21.51 |
April | 595.83 | 21.40 | 0.50 | 21.40 | 0.00 | 21.40 |
May | 574.00 | 21.27 | 1.50 | 21.28 | 1.00 | 21.28 |
June | 540.33 | 21.22 | 5.00 | 21.24 | 0.00 | 21.24 |
July | 553.33 | 21.21 | 5.17 | 21.23 | 0.00 | 21.23 |
August | 573.83 | 21.27 | 8.83 | 21.30 | 5.83 | 21.32 |
September | 548.67 | 21.25 | 0.17 | 21.25 | 0.00 | 21.25 |
October | 592.83 | 21.33 | 1.17 | 21.33 | 1.17 | 21.34 |
November | 647.83 | 21.49 | 5.83 | 21.51 | 5.67 | 21.52 |
December | 723.00 | 21.46 | 12.00 | 21.48 | 12.00 | 21.51 |
Annual Sum or Average | 7417.83 | 21.38 | 54.67 | 21.40 | 40.17 | 21.40 |
Minimum of Months | 540.33 | 21.21 | 0.17 | 21.23 | 0.00 | 21.23 |
Maximum of Months | 732.83 | 21.58 | 12.00 | 21.58 | 12.00 | 21.58 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.35 | 0.00 | 21.35 | 0.00 | 21.35 |
February | 672.00 | 21.44 | 0.00 | 21.44 | 0.00 | 21.44 |
March | 744.00 | 21.51 | 0.00 | 21.51 | 0.00 | 21.51 |
April | 720.00 | 21.77 | 0.00 | 21.77 | 0.00 | 21.77 |
May | 744.00 | 21.96 | 0.00 | 21.96 | 0.00 | 21.96 |
June | 720.00 | 22.15 | 0.00 | 22.15 | 0.00 | 22.15 |
July | 744.00 | 22.24 | 0.00 | 22.24 | 0.00 | 22.24 |
August | 744.00 | 22.18 | 0.00 | 22.18 | 0.00 | 22.18 |
September | 720.00 | 22.23 | 0.00 | 22.23 | 0.00 | 22.23 |
October | 744.00 | 22.16 | 0.00 | 22.16 | 0.00 | 22.16 |
November | 720.00 | 21.82 | 0.00 | 21.82 | 0.00 | 21.82 |
December | 744.00 | 21.46 | 0.00 | 21.46 | 0.00 | 21.46 |
Annual Sum or Average | 8760.00 | 21.86 | 0.00 | 21.86 | 0.00 | 21.86 |
Minimum of Months | 672.00 | 21.35 | 0.00 | 21.35 | 0.00 | 21.35 |
Maximum of Months | 744.00 | 22.24 | 0.00 | 22.24 | 0.00 | 22.24 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 672.17 | 21.43 | 17.50 | 21.46 | 8.83 | 21.46 |
February | 588.67 | 21.41 | 27.33 | 21.46 | 12.00 | 21.47 |
March | 641.67 | 21.38 | 34.50 | 21.46 | 10.67 | 21.48 |
April | 583.83 | 21.34 | 43.17 | 21.48 | 1.50 | 21.48 |
May | 583.83 | 21.30 | 63.50 | 21.50 | 1.67 | 21.50 |
June | 555.00 | 21.27 | 81.00 | 21.53 | 0.17 | 21.53 |
July | 561.17 | 21.24 | 119.00 | 21.60 | 0.00 | 21.60 |
August | 578.17 | 21.29 | 111.17 | 21.61 | 7.00 | 21.63 |
September | 551.83 | 21.26 | 101.50 | 21.58 | 1.83 | 21.58 |
October | 579.67 | 21.29 | 83.67 | 21.54 | 3.00 | 21.55 |
November | 596.33 | 21.35 | 56.00 | 21.52 | 3.83 | 21.52 |
December | 657.17 | 21.39 | 43.67 | 21.49 | 11.17 | 21.49 |
Annual Sum or Average | 7149.50 | 21.33 | 782.00 | 21.52 | 61.67 | 21.53 |
Minimum of Months | 551.83 | 21.24 | 17.50 | 21.46 | 0.00 | 21.46 |
Maximum of Months | 672.17 | 21.43 | 119.00 | 21.61 | 12.00 | 21.63 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 711.50 | 21.40 | 15.17 | 21.40 | 14.67 | 21.40 |
February | 620.17 | 21.43 | 21.17 | 21.44 | 16.00 | 21.44 |
March | 662.67 | 21.39 | 22.83 | 21.42 | 14.33 | 21.42 |
April | 593.33 | 21.36 | 27.17 | 21.45 | 2.00 | 21.45 |
May | 582.67 | 21.29 | 60.33 | 21.48 | 1.17 | 21.49 |
June | 552.17 | 21.26 | 83.50 | 21.53 | 0.00 | 21.53 |
July | 559.67 | 21.23 | 120.67 | 21.60 | 0.00 | 21.60 |
August | 580.17 | 21.29 | 102.33 | 21.59 | 7.00 | 21.61 |
September | 558.67 | 21.27 | 78.50 | 21.53 | 2.33 | 21.53 |
October | 596.50 | 21.32 | 50.67 | 21.48 | 3.67 | 21.48 |
November | 628.83 | 21.41 | 26.83 | 21.47 | 6.67 | 21.48 |
December | 690.83 | 21.37 | 27.00 | 21.41 | 17.17 | 21.41 |
Annual Sum or Average | 7337.17 | 21.34 | 636.17 | 21.48 | 85.00 | 21.49 |
Minimum of Months | 552.17 | 21.23 | 15.17 | 21.40 | 0.00 | 21.40 |
Maximum of Months | 711.50 | 21.43 | 120.67 | 21.60 | 17.17 | 21.61 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 630.00 | 21.39 | 31.50 | 21.48 | 4.50 | 21.49 |
February | 571.17 | 21.41 | 16.67 | 21.46 | 6.17 | 21.47 |
March | 646.33 | 21.44 | 11.00 | 21.45 | 11.00 | 21.46 |
April | 620.50 | 21.45 | 1.67 | 21.45 | 1.67 | 21.46 |
May | 617.67 | 21.40 | 1.83 | 21.40 | 1.83 | 21.40 |
June | 584.67 | 21.36 | 0.00 | 21.36 | 0.00 | 21.36 |
July | 591.00 | 21.33 | 0.33 | 21.33 | 0.33 | 21.33 |
August | 601.67 | 21.36 | 3.17 | 21.36 | 2.67 | 21.37 |
September | 566.17 | 21.32 | 36.83 | 21.44 | 0.00 | 21.44 |
October | 582.67 | 21.32 | 72.67 | 21.54 | 2.50 | 21.55 |
November | 580.33 | 21.35 | 46.00 | 21.49 | 1.17 | 21.49 |
December | 625.17 | 21.38 | 40.00 | 21.49 | 5.00 | 21.50 |
Annual Sum or Average | 7217.33 | 21.38 | 261.67 | 21.44 | 36.83 | 21.45 |
Minimum of Months | 566.17 | 21.32 | 0.00 | 21.33 | 0.00 | 21.33 |
Maximum of Months | 646.33 | 21.45 | 72.67 | 21.54 | 11.00 | 21.55 |
Report: ComfortReportSimple55Monthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 717.50 | 21.55 | 4.67 | 21.56 | 0.00 | 21.56 |
February | 641.67 | 21.60 | 9.67 | 21.62 | 0.00 | 21.62 |
March | 693.67 | 21.64 | 23.50 | 21.69 | 0.00 | 21.69 |
April | 631.33 | 21.67 | 35.33 | 21.75 | 0.00 | 21.75 |
May | 537.00 | 21.63 | 61.17 | 21.79 | 0.00 | 21.79 |
June | 449.67 | 21.58 | 97.33 | 21.85 | 0.00 | 21.85 |
July | 470.00 | 21.62 | 94.83 | 21.87 | 0.00 | 21.87 |
August | 486.00 | 21.59 | 87.50 | 21.82 | 0.00 | 21.82 |
September | 501.17 | 21.61 | 77.17 | 21.81 | 0.00 | 21.81 |
October | 601.33 | 21.66 | 50.17 | 21.77 | 0.00 | 21.77 |
November | 642.83 | 21.63 | 31.50 | 21.70 | 0.00 | 21.70 |
December | 712.67 | 21.60 | 7.50 | 21.61 | 0.00 | 21.61 |
Annual Sum or Average | 7084.83 | 21.62 | 580.33 | 21.73 | 0.00 | 21.73 |
Minimum of Months | 449.67 | 21.55 | 4.67 | 21.56 | 0.00 | 21.56 |
Maximum of Months | 717.50 | 21.67 | 97.33 | 21.87 | 0.00 | 21.87 |
Report: ComfortReportSimple55Monthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 690.33 | 21.57 | 20.00 | 21.61 | 0.00 | 21.61 |
February | 600.50 | 21.60 | 23.50 | 21.65 | 0.00 | 21.65 |
March | 634.83 | 21.63 | 38.83 | 21.71 | 0.00 | 21.71 |
April | 554.83 | 21.64 | 61.33 | 21.79 | 0.00 | 21.79 |
May | 449.50 | 21.57 | 113.67 | 21.87 | 0.00 | 21.87 |
June | 381.67 | 21.54 | 178.00 | 22.00 | 0.00 | 22.00 |
July | 399.17 | 21.58 | 165.33 | 21.99 | 0.00 | 21.99 |
August | 417.00 | 21.54 | 156.67 | 21.94 | 0.00 | 21.94 |
September | 423.17 | 21.55 | 138.67 | 21.90 | 0.00 | 21.90 |
October | 511.00 | 21.58 | 86.00 | 21.79 | 0.00 | 21.79 |
November | 580.83 | 21.61 | 56.00 | 21.74 | 0.00 | 21.74 |
December | 669.00 | 21.60 | 22.17 | 21.64 | 0.00 | 21.64 |
Annual Sum or Average | 6311.83 | 21.59 | 1060.17 | 21.79 | 0.00 | 21.79 |
Minimum of Months | 381.67 | 21.54 | 20.00 | 21.61 | 0.00 | 21.61 |
Maximum of Months | 690.33 | 21.64 | 178.00 | 22.00 | 0.00 | 22.00 |
Report: ComfortReportSimple55Monthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 579.67 | 23.37 | 588.50 | 23.45 | 486.50 | 23.56 |
February | 514.67 | 23.46 | 534.17 | 23.51 | 445.00 | 23.61 |
March | 556.33 | 23.57 | 608.33 | 23.55 | 501.67 | 23.64 |
April | 517.17 | 23.78 | 608.00 | 23.63 | 499.33 | 23.71 |
May | 526.17 | 23.89 | 663.33 | 23.64 | 525.00 | 23.72 |
June | 510.83 | 23.91 | 676.83 | 23.59 | 510.83 | 23.69 |
July | 527.67 | 23.92 | 695.50 | 23.60 | 527.67 | 23.69 |
August | 526.33 | 23.90 | 688.67 | 23.60 | 526.33 | 23.69 |
September | 507.50 | 23.91 | 668.00 | 23.60 | 507.50 | 23.70 |
October | 521.50 | 23.89 | 656.33 | 23.64 | 520.83 | 23.72 |
November | 525.83 | 23.68 | 601.83 | 23.59 | 493.00 | 23.67 |
December | 565.67 | 23.44 | 597.50 | 23.48 | 492.67 | 23.57 |
Annual Sum or Average | 6379.33 | 23.72 | 7587.00 | 23.57 | 6036.33 | 23.66 |
Minimum of Months | 507.50 | 23.37 | 534.17 | 23.45 | 445.00 | 23.56 |
Maximum of Months | 579.67 | 23.92 | 695.50 | 23.64 | 527.67 | 23.72 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.05 | 0.00 | 21.05 | 0.00 | 21.05 |
February | 672.00 | 21.07 | 2.83 | 21.07 | 2.83 | 21.07 |
March | 744.00 | 21.09 | 0.00 | 21.09 | 0.00 | 21.09 |
April | 720.00 | 21.20 | 0.00 | 21.20 | 0.00 | 21.20 |
May | 744.00 | 21.42 | 0.00 | 21.42 | 0.00 | 21.42 |
June | 720.00 | 21.65 | 0.00 | 21.65 | 0.00 | 21.65 |
July | 744.00 | 21.77 | 0.00 | 21.77 | 0.00 | 21.77 |
August | 744.00 | 21.63 | 0.00 | 21.63 | 0.00 | 21.63 |
September | 720.00 | 21.66 | 0.00 | 21.66 | 0.00 | 21.66 |
October | 744.00 | 21.46 | 0.00 | 21.46 | 0.00 | 21.46 |
November | 720.00 | 21.22 | 0.00 | 21.22 | 0.00 | 21.22 |
December | 744.00 | 21.09 | 0.00 | 21.09 | 0.00 | 21.09 |
Annual Sum or Average | 8760.00 | 21.36 | 2.83 | 21.36 | 2.83 | 21.36 |
Minimum of Months | 672.00 | 21.05 | 0.00 | 21.05 | 0.00 | 21.05 |
Maximum of Months | 744.00 | 21.77 | 2.83 | 21.77 | 2.83 | 21.77 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT PEOPLE
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.23662 | 56.08013 | -0.2046 | 5.99944 |
February | 672.00000 | 21.14439 | 56.66249 | -0.2307 | 6.22115 |
March | 744.00000 | 21.06665 | 58.01592 | -0.2510 | 6.40602 |
April | 720.00000 | 21.04339 | 62.05332 | -0.2375 | 6.23721 |
May | 744.00000 | 21.05863 | 62.73442 | -1.4053 | 45.80930 |
June | 720.00000 | 21.06851 | 62.56940 | -1.3988 | 45.46501 |
July | 744.00000 | 21.12367 | 62.16269 | -1.3729 | 44.09891 |
August | 744.00000 | 21.21011 | 62.15343 | -1.3353 | 42.14130 |
September | 720.00000 | 21.25415 | 61.80037 | -1.3156 | 41.16553 |
October | 744.00000 | 21.28421 | 61.91112 | -0.1521 | 5.54584 |
November | 720.00000 | 21.30006 | 60.27193 | -0.1587 | 5.61057 |
December | 744.00000 | 21.29335 | 58.75123 | -0.1715 | 5.70421 |
Annual Sum or Average | 8760.00000 | 21.17396 | 60.44788 | -0.6889 | 21.79561 |
Minimum of Months | 672.00000 | 21.04339 | 56.08013 | -1.4053 | 5.54584 |
Maximum of Months | 744.00000 | 21.30006 | 62.73442 | -0.1521 | 45.80930 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_1_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.31949 | 56.17497 | -0.1041 | 6.14509 |
February | 672.00000 | 21.30965 | 56.59487 | -0.0952 | 5.97360 |
March | 744.00000 | 21.20234 | 58.21890 | -0.1113 | 5.77096 |
April | 720.00000 | 21.20109 | 62.39231 | -0.0753 | 5.42310 |
May | 744.00000 | 21.19862 | 64.03737 | -1.1718 | 34.06509 |
June | 720.00000 | 21.27787 | 64.28540 | -1.1302 | 32.09681 |
July | 744.00000 | 21.38208 | 63.75069 | -1.0855 | 30.11044 |
August | 744.00000 | 21.40210 | 64.05079 | -1.0845 | 30.19592 |
September | 720.00000 | 21.58880 | 63.01965 | -1.0089 | 27.31003 |
October | 744.00000 | 21.63372 | 62.63529 | 0.06825 | 5.73960 |
November | 720.00000 | 21.49058 | 60.93537 | 0.00085 | 5.91610 |
December | 744.00000 | 21.37621 | 59.16979 | -0.0640 | 6.07304 |
Annual Sum or Average | 8760.00000 | 21.36540 | 61.29537 | -0.4910 | 16.30342 |
Minimum of Months | 672.00000 | 21.19862 | 56.17497 | -1.1718 | 5.42310 |
Maximum of Months | 744.00000 | 21.63372 | 64.28540 | 0.06825 | 34.06509 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_2_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.09232 | 57.29245 | -0.2045 | 6.03486 |
February | 672.00000 | 21.11912 | 57.53295 | -0.1917 | 5.94909 |
March | 744.00000 | 21.15554 | 58.61964 | -0.1732 | 5.83082 |
April | 720.00000 | 21.21128 | 62.47245 | -0.1303 | 5.51500 |
May | 744.00000 | 21.26026 | 63.45759 | -1.2452 | 37.64373 |
June | 720.00000 | 21.30244 | 63.49917 | -1.2253 | 36.67366 |
July | 744.00000 | 21.33292 | 63.20611 | -1.2100 | 35.92697 |
August | 744.00000 | 21.31206 | 63.62523 | -1.2203 | 36.43843 |
September | 720.00000 | 21.32422 | 63.30389 | -1.2114 | 36.03271 |
October | 744.00000 | 21.27806 | 63.46611 | -0.0976 | 5.31548 |
November | 720.00000 | 21.18795 | 61.88681 | -0.1389 | 5.55812 |
December | 744.00000 | 21.12199 | 60.24652 | -0.1751 | 5.77386 |
Annual Sum or Average | 8760.00000 | 21.22537 | 61.57018 | -0.6045 | 18.63520 |
Minimum of Months | 672.00000 | 21.09232 | 57.29245 | -1.2452 | 5.31548 |
Maximum of Months | 744.00000 | 21.33292 | 63.62523 | -0.0976 | 37.64373 |
Report: OccupantComfortDataSummaryMonthly
For: LAUNDRY_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.38791 | 54.01956 | 0.44710 | 11.54982 |
February | 672.00000 | 21.38394 | 54.32146 | 0.45650 | 11.73535 |
March | 744.00000 | 21.38818 | 55.42679 | 0.47364 | 12.08432 |
April | 720.00000 | 21.36491 | 59.40379 | 0.50558 | 12.53121 |
May | 744.00000 | 21.36559 | 60.24392 | -0.3390 | 11.81422 |
June | 720.00000 | 21.36410 | 60.19690 | -0.3233 | 11.54078 |
July | 744.00000 | 21.34394 | 60.07011 | -0.3262 | 11.34186 |
August | 744.00000 | 21.36607 | 60.30427 | -0.3335 | 11.71626 |
September | 720.00000 | 21.35625 | 60.13098 | -0.3304 | 11.54157 |
October | 744.00000 | 21.36346 | 60.27010 | 0.51830 | 12.71169 |
November | 720.00000 | 21.37612 | 58.56262 | 0.49490 | 12.36212 |
December | 744.00000 | 21.38065 | 56.94081 | 0.46490 | 11.75187 |
Annual Sum or Average | 8760.00000 | 21.37003 | 58.34348 | 0.14041 | 11.89022 |
Minimum of Months | 672.00000 | 21.34394 | 54.01956 | -0.3390 | 11.34186 |
Maximum of Months | 744.00000 | 21.38818 | 60.30427 | 0.51830 | 12.71169 |
Report: OccupantComfortDataSummaryMonthly
For: CAFE_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.50439 | 58.48281 | 0.02118 | 5.66074 |
February | 672.00000 | 21.51364 | 58.80932 | 0.03059 | 5.55696 |
March | 744.00000 | 21.46819 | 60.12692 | 0.02288 | 5.45996 |
April | 720.00000 | 21.47668 | 64.09616 | 0.05562 | 5.32628 |
May | 744.00000 | 21.52588 | 65.10302 | -0.9831 | 25.78419 |
June | 720.00000 | 21.60551 | 65.05142 | -0.9419 | 24.22291 |
July | 744.00000 | 21.62128 | 64.80194 | -0.9260 | 23.50019 |
August | 744.00000 | 21.65579 | 65.03807 | -0.9176 | 23.27632 |
September | 720.00000 | 21.77041 | 64.35066 | -0.8604 | 21.20907 |
October | 744.00000 | 21.84051 | 64.08033 | 0.18514 | 6.02758 |
November | 720.00000 | 21.71632 | 62.60857 | 0.12691 | 5.92012 |
December | 744.00000 | 21.56740 | 61.27500 | 0.05918 | 5.72249 |
Annual Sum or Average | 8760.00000 | 21.60585 | 62.83840 | -0.3464 | 13.18992 |
Minimum of Months | 672.00000 | 21.46819 | 58.48281 | -0.9831 | 5.32628 |
Maximum of Months | 744.00000 | 21.84051 | 65.10302 | 0.18514 | 25.78419 |
Report: OccupantComfortDataSummaryMonthly
For: LOBBY_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.30949 | 58.36863 | -0.1120 | 5.52266 |
February | 672.00000 | 21.34190 | 58.59542 | -0.0992 | 5.48539 |
March | 744.00000 | 21.37238 | 59.68735 | -0.0855 | 5.46010 |
April | 720.00000 | 21.41946 | 63.51115 | -0.0461 | 5.28452 |
May | 744.00000 | 21.48958 | 64.35680 | -1.1210 | 31.83994 |
June | 720.00000 | 21.54893 | 64.30933 | -1.0923 | 30.59254 |
July | 744.00000 | 21.55460 | 64.09602 | -1.0861 | 30.29239 |
August | 744.00000 | 21.54751 | 64.46599 | -1.0917 | 30.55787 |
September | 720.00000 | 21.56709 | 64.12512 | -1.0782 | 29.96538 |
October | 744.00000 | 21.53903 | 64.23884 | 0.00426 | 5.21332 |
November | 720.00000 | 21.45663 | 62.68486 | -0.0347 | 5.29114 |
December | 744.00000 | 21.35943 | 61.20851 | -0.0788 | 5.35828 |
Annual Sum or Average | 8760.00000 | 21.45937 | 62.48951 | -0.4959 | 15.97035 |
Minimum of Months | 672.00000 | 21.30949 | 58.36863 | -1.1210 | 5.21332 |
Maximum of Months | 744.00000 | 21.56709 | 64.46599 | 0.00426 | 31.83994 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.61273 | 55.91600 | -0.0982 | 6.05593 |
February | 672.00000 | 21.64520 | 55.42531 | -0.0746 | 6.06428 |
March | 744.00000 | 21.64704 | 55.52574 | -0.0586 | 6.02310 |
April | 720.00000 | 21.70890 | 57.06389 | -0.0061 | 5.90409 |
May | 744.00000 | 21.72643 | 58.14501 | -1.0547 | 29.97466 |
June | 720.00000 | 21.73188 | 58.81234 | -1.0376 | 29.22277 |
July | 744.00000 | 21.73893 | 58.19579 | -1.0195 | 28.50823 |
August | 744.00000 | 21.73212 | 58.87448 | -1.0299 | 28.94170 |
September | 720.00000 | 21.73408 | 58.35692 | -1.0271 | 28.88363 |
October | 744.00000 | 21.73066 | 57.90605 | 0.02623 | 5.90760 |
November | 720.00000 | 21.69103 | 57.53943 | -0.0220 | 5.95562 |
December | 744.00000 | 21.61991 | 58.14869 | -0.0704 | 5.98643 |
Annual Sum or Average | 8760.00000 | 21.69338 | 57.50452 | -0.4585 | 15.67701 |
Minimum of Months | 672.00000 | 21.61273 | 55.42531 | -1.0547 | 5.90409 |
Maximum of Months | 744.00000 | 21.73893 | 58.87448 | 0.02623 | 29.97466 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.47167 | 57.83823 | -0.1552 | 6.18920 |
February | 672.00000 | 21.56387 | 56.81809 | -0.1137 | 6.11548 |
March | 744.00000 | 21.59111 | 56.40022 | -0.0853 | 6.07280 |
April | 720.00000 | 21.70080 | 57.51222 | -0.0146 | 5.86837 |
May | 744.00000 | 21.72725 | 58.14487 | -1.0546 | 29.95988 |
June | 720.00000 | 21.73428 | 58.67794 | -1.0333 | 29.04845 |
July | 744.00000 | 21.74034 | 58.13494 | -1.0168 | 28.39399 |
August | 744.00000 | 21.73101 | 59.08900 | -1.0340 | 29.09037 |
September | 720.00000 | 21.72864 | 58.97575 | -1.0422 | 29.44944 |
October | 744.00000 | 21.71686 | 59.16099 | 0.00800 | 5.83267 |
November | 720.00000 | 21.64413 | 59.27953 | -0.0504 | 5.89732 |
December | 744.00000 | 21.51024 | 60.08543 | -0.1172 | 6.05055 |
Annual Sum or Average | 8760.00000 | 21.65525 | 58.35269 | -0.4781 | 15.72168 |
Minimum of Months | 672.00000 | 21.47167 | 56.40022 | -1.0546 | 5.83267 |
Maximum of Months | 744.00000 | 21.74034 | 60.08543 | 0.00800 | 29.95988 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT19_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 0.00000 | ||||
Minimum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_4_MULT19_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.38959 | 55.13764 | -0.2021 | 6.16302 |
February | 672.00000 | 21.45713 | 55.01451 | -0.1760 | 6.03230 |
March | 744.00000 | 21.48749 | 55.21839 | -0.1595 | 5.99808 |
April | 720.00000 | 21.59660 | 56.77122 | -0.1078 | 5.75523 |
May | 744.00000 | 21.67253 | 56.83643 | -1.1806 | 35.22791 |
June | 720.00000 | 21.69379 | 57.16413 | -1.1570 | 34.20176 |
July | 744.00000 | 21.70549 | 57.10781 | -1.1497 | 33.90415 |
August | 744.00000 | 21.67919 | 57.49784 | -1.1686 | 34.71036 |
September | 720.00000 | 21.67735 | 57.37631 | -1.1714 | 34.85782 |
October | 744.00000 | 21.63909 | 57.52291 | -0.0847 | 5.69264 |
November | 720.00000 | 21.54045 | 57.05159 | -0.1282 | 5.76985 |
December | 744.00000 | 21.42699 | 57.51718 | -0.1723 | 5.95567 |
Annual Sum or Average | 8760.00000 | 21.58098 | 56.69394 | -0.5740 | 17.92781 |
Minimum of Months | 672.00000 | 21.38959 | 55.01451 | -1.1806 | 5.69264 |
Maximum of Months | 744.00000 | 21.70549 | 57.52291 | -0.0847 | 35.22791 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_5_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.65508 | 55.33249 | -0.0868 | 6.05851 |
February | 672.00000 | 21.68205 | 55.15967 | -0.0658 | 6.05136 |
March | 744.00000 | 21.70292 | 55.27277 | -0.0471 | 5.99990 |
April | 720.00000 | 21.73578 | 56.78580 | -0.0010 | 5.95686 |
May | 744.00000 | 21.74119 | 57.99708 | -1.0484 | 29.76934 |
June | 720.00000 | 21.74708 | 58.34743 | -1.0205 | 28.57489 |
July | 744.00000 | 21.75057 | 57.87995 | -1.0084 | 28.11633 |
August | 744.00000 | 21.74177 | 58.78557 | -1.0258 | 28.82745 |
September | 720.00000 | 21.74713 | 57.93268 | -1.0150 | 28.43061 |
October | 744.00000 | 21.74323 | 57.80989 | 0.03154 | 5.94007 |
November | 720.00000 | 21.71213 | 57.55275 | -0.0154 | 5.95136 |
December | 744.00000 | 21.63304 | 58.34259 | -0.0728 | 5.96319 |
Annual Sum or Average | 8760.00000 | 21.71606 | 57.27962 | -0.4504 | 15.52813 |
Minimum of Months | 672.00000 | 21.63304 | 55.15967 | -1.0484 | 5.94007 |
Maximum of Months | 744.00000 | 21.75057 | 58.78557 | 0.03154 | 29.76934 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_6_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.52458 | 57.05243 | -0.1419 | 6.12451 |
February | 672.00000 | 21.62506 | 56.24290 | -0.1014 | 6.07347 |
March | 744.00000 | 21.66422 | 55.96527 | -0.0712 | 6.00071 |
April | 720.00000 | 21.73276 | 57.16436 | -0.0087 | 5.93186 |
May | 744.00000 | 21.74156 | 58.02322 | -1.0483 | 29.75697 |
June | 720.00000 | 21.74803 | 58.24396 | -1.0168 | 28.42384 |
July | 744.00000 | 21.75120 | 57.83573 | -1.0060 | 28.01502 |
August | 744.00000 | 21.74102 | 59.02907 | -1.0297 | 28.96306 |
September | 720.00000 | 21.74441 | 58.62298 | -1.0285 | 28.92810 |
October | 744.00000 | 21.73591 | 58.86495 | 0.01398 | 5.86941 |
November | 720.00000 | 21.67586 | 58.89677 | -0.0435 | 5.88108 |
December | 744.00000 | 21.50896 | 60.26748 | -0.1232 | 6.02408 |
Annual Sum or Average | 8760.00000 | 21.68281 | 58.02966 | -0.4695 | 15.55718 |
Minimum of Months | 672.00000 | 21.50896 | 55.96527 | -1.0483 | 5.86941 |
Maximum of Months | 744.00000 | 21.75120 | 60.26748 | 0.01398 | 29.75697 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.61415 | 56.53730 | -0.0943 | 6.19895 |
February | 672.00000 | 21.64629 | 55.86259 | -0.0662 | 6.20778 |
March | 744.00000 | 21.65130 | 55.78520 | -0.0466 | 6.14935 |
April | 720.00000 | 21.71385 | 57.05818 | 0.01276 | 6.02638 |
May | 744.00000 | 21.73261 | 57.75114 | -1.0236 | 28.85356 |
June | 720.00000 | 21.73750 | 58.22691 | -1.0052 | 28.05247 |
July | 744.00000 | 21.74401 | 57.68449 | -0.9845 | 27.30820 |
August | 744.00000 | 21.73720 | 58.41103 | -0.9990 | 27.85568 |
September | 720.00000 | 21.73765 | 58.00754 | -0.9982 | 27.88746 |
October | 744.00000 | 21.73284 | 57.80163 | 0.04199 | 6.02098 |
November | 720.00000 | 21.69174 | 57.73131 | -0.0114 | 6.06072 |
December | 744.00000 | 21.61761 | 58.68376 | -0.0657 | 6.11397 |
Annual Sum or Average | 8760.00000 | 21.69655 | 57.47168 | -0.4390 | 15.28260 |
Minimum of Months | 672.00000 | 21.61415 | 55.78520 | -1.0236 | 6.02098 |
Maximum of Months | 744.00000 | 21.74401 | 58.68376 | 0.04199 | 28.85356 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.48512 | 58.45714 | -0.1514 | 6.33670 |
February | 672.00000 | 21.57566 | 57.22556 | -0.1045 | 6.26184 |
March | 744.00000 | 21.60243 | 56.60420 | -0.0729 | 6.19498 |
April | 720.00000 | 21.70832 | 57.49396 | 0.00479 | 5.98292 |
May | 744.00000 | 21.73339 | 57.75382 | -1.0233 | 28.83092 |
June | 720.00000 | 21.73955 | 58.10414 | -1.0010 | 27.88402 |
July | 744.00000 | 21.74521 | 57.62426 | -0.9817 | 27.19595 |
August | 744.00000 | 21.73637 | 58.55540 | -1.0035 | 28.00188 |
September | 720.00000 | 21.73307 | 58.57074 | -1.0133 | 28.42087 |
October | 744.00000 | 21.72038 | 58.99350 | 0.02343 | 5.91981 |
November | 720.00000 | 21.64958 | 59.44178 | -0.0398 | 5.98674 |
December | 744.00000 | 21.51274 | 60.60933 | -0.1138 | 6.19222 |
Annual Sum or Average | 8760.00000 | 21.66202 | 58.29359 | -0.4587 | 15.32168 |
Minimum of Months | 672.00000 | 21.48512 | 56.60420 | -1.0233 | 5.91981 |
Maximum of Months | 744.00000 | 21.74521 | 60.60933 | 0.02343 | 28.83092 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT9_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.69086 | 53.97492 | -0.0543 | 6.18332 |
February | 672.00000 | 21.70080 | 54.26119 | -0.0472 | 6.14549 |
March | 744.00000 | 21.68517 | 54.88606 | -0.0540 | 6.06941 |
April | 720.00000 | 21.71036 | 56.73387 | -0.0264 | 5.94768 |
May | 744.00000 | 21.72568 | 57.66104 | -1.0910 | 31.55936 |
June | 720.00000 | 21.73243 | 58.02493 | -1.0695 | 30.60648 |
July | 744.00000 | 21.73950 | 57.67661 | -1.0558 | 30.09904 |
August | 744.00000 | 21.73347 | 57.95463 | -1.0612 | 30.32204 |
September | 720.00000 | 21.74475 | 57.23089 | -1.0359 | 29.41300 |
October | 744.00000 | 21.75006 | 56.67716 | 0.03173 | 6.05826 |
November | 720.00000 | 21.72971 | 55.95298 | 0.00013 | 6.10035 |
December | 744.00000 | 21.69012 | 56.25164 | -0.0344 | 6.12472 |
Annual Sum or Average | 8760.00000 | 21.71945 | 56.45243 | -0.4607 | 16.28219 |
Minimum of Months | 672.00000 | 21.68517 | 53.97492 | -1.0910 | 5.94768 |
Maximum of Months | 744.00000 | 21.75006 | 58.02493 | 0.03173 | 31.55936 |
Report: OccupantComfortDataSummaryMonthly
For: BANQUET_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.59967 | 58.27208 | 0.01808 | 5.50691 |
February | 672.00000 | 21.66052 | 58.40178 | 0.04584 | 5.57374 |
March | 744.00000 | 21.72549 | 59.32091 | 0.07660 | 5.68226 |
April | 720.00000 | 21.82098 | 62.84638 | 0.14122 | 5.83098 |
May | 744.00000 | 21.95212 | 63.27849 | -0.8237 | 20.06594 |
June | 720.00000 | 22.04073 | 62.99530 | -0.7777 | 18.55881 |
July | 744.00000 | 22.04941 | 62.75697 | -0.7686 | 18.15639 |
August | 744.00000 | 22.00932 | 63.22297 | -0.7943 | 19.11327 |
September | 720.00000 | 21.97656 | 63.09250 | -0.8070 | 19.55588 |
October | 744.00000 | 21.87955 | 63.53462 | 0.16919 | 6.01274 |
November | 720.00000 | 21.76607 | 62.26002 | 0.11241 | 5.75267 |
December | 744.00000 | 21.64963 | 60.99384 | 0.05415 | 5.52083 |
Annual Sum or Average | 8760.00000 | 21.84506 | 61.76398 | -0.2816 | 11.31184 |
Minimum of Months | 672.00000 | 21.59967 | 58.27208 | -0.8237 | 5.50691 |
Maximum of Months | 744.00000 | 22.04941 | 63.53462 | 0.16919 | 20.06594 |
Report: OccupantComfortDataSummaryMonthly
For: DINING_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.65794 | 57.84932 | 0.06208 | 5.60455 |
February | 672.00000 | 21.72638 | 57.95408 | 0.09160 | 5.72527 |
March | 744.00000 | 21.79779 | 58.84371 | 0.12414 | 5.89529 |
April | 720.00000 | 21.89861 | 62.33643 | 0.18951 | 6.16035 |
May | 744.00000 | 22.02968 | 62.75762 | -0.7555 | 17.76812 |
June | 720.00000 | 22.10968 | 62.49667 | -0.7138 | 16.50830 |
July | 744.00000 | 22.11044 | 62.28607 | -0.7082 | 16.24444 |
August | 744.00000 | 22.07403 | 62.73677 | -0.7320 | 17.07395 |
September | 720.00000 | 22.03672 | 62.62500 | -0.7468 | 17.55269 |
October | 744.00000 | 21.94297 | 63.06046 | 0.21242 | 6.34971 |
November | 720.00000 | 21.83301 | 61.78540 | 0.15760 | 6.01444 |
December | 744.00000 | 21.71211 | 60.54500 | 0.09887 | 5.68336 |
Annual Sum or Average | 8760.00000 | 21.91165 | 61.28895 | -0.2287 | 10.57694 |
Minimum of Months | 672.00000 | 21.65794 | 57.84932 | -0.7555 | 5.60455 |
Maximum of Months | 744.00000 | 22.11044 | 63.06046 | 0.21242 | 17.76812 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.01453 | 54.98266 | 1.00124 | 30.93443 |
February | 672.00000 | 23.04686 | 55.13519 | 1.02369 | 31.91587 |
March | 744.00000 | 23.07560 | 56.05688 | 1.05028 | 32.88263 |
April | 720.00000 | 23.12692 | 59.39143 | 1.11145 | 35.36061 |
May | 744.00000 | 23.17729 | 60.01357 | 0.53088 | 20.82046 |
June | 720.00000 | 23.21446 | 59.87814 | 0.56559 | 21.29723 |
July | 744.00000 | 23.20948 | 59.74576 | 0.57573 | 21.81918 |
August | 744.00000 | 23.19642 | 60.04850 | 0.55024 | 20.99308 |
September | 720.00000 | 23.20131 | 59.83299 | 0.55600 | 21.18945 |
October | 744.00000 | 23.16281 | 60.07185 | 1.13727 | 36.22159 |
November | 720.00000 | 23.10006 | 58.74571 | 1.08249 | 34.09560 |
December | 744.00000 | 23.02076 | 57.54449 | 1.02315 | 31.65195 |
Annual Sum or Average | 8760.00000 | 23.12920 | 58.47016 | 0.84948 | 28.23823 |
Minimum of Months | 672.00000 | 23.01453 | 54.98266 | 0.53088 | 20.82046 |
Maximum of Months | 744.00000 | 23.21446 | 60.07185 | 1.13727 | 36.22159 |
Report: OccupantComfortDataSummaryMonthly
For: STORAGE_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.00139 | 56.41813 | -0.2958 | 6.93997 |
February | 672.00000 | 21.00256 | 56.78073 | -0.2873 | 6.83974 |
March | 744.00000 | 21.00675 | 58.14788 | -0.2744 | 6.68809 |
April | 720.00000 | 21.01747 | 62.36348 | -0.2378 | 6.23635 |
May | 744.00000 | 21.07388 | 63.94728 | -1.3789 | 44.40746 |
June | 720.00000 | 21.16948 | 64.23956 | -1.3362 | 42.17645 |
July | 744.00000 | 21.19794 | 63.98737 | -1.3250 | 41.59483 |
August | 744.00000 | 21.13745 | 64.60696 | -1.3495 | 42.87285 |
September | 720.00000 | 21.13200 | 64.24019 | -1.3497 | 42.91438 |
October | 744.00000 | 21.05051 | 64.22991 | -0.2088 | 5.92073 |
November | 720.00000 | 21.01936 | 62.00672 | -0.2399 | 6.25810 |
December | 744.00000 | 21.00416 | 59.71944 | -0.2702 | 6.59509 |
Annual Sum or Average | 8760.00000 | 21.06810 | 61.74829 | -0.7154 | 21.71140 |
Minimum of Months | 672.00000 | 21.00139 | 56.41813 | -1.3789 | 5.92073 |
Maximum of Months | 744.00000 | 21.19794 | 64.60696 | -0.2088 | 44.40746 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.35163 | 57.55519 | -0.2146 | 6.23400 |
February | 672.00000 | 21.43735 | 57.64693 | -0.1923 | 5.98928 |
March | 744.00000 | 21.50674 | 58.64867 | -0.1676 | 5.85363 |
April | 720.00000 | 21.77403 | 61.84493 | -0.0797 | 5.23039 |
May | 744.00000 | 21.96137 | 62.54826 | -1.1339 | 32.14790 |
June | 720.00000 | 22.15377 | 62.25308 | -1.0662 | 29.03186 |
July | 744.00000 | 22.23842 | 61.80179 | -1.0378 | 27.77743 |
August | 744.00000 | 22.18474 | 62.32991 | -1.0550 | 28.56405 |
September | 720.00000 | 22.23230 | 61.85793 | -1.0389 | 27.88425 |
October | 744.00000 | 22.16312 | 61.96041 | 0.02390 | 5.03455 |
November | 720.00000 | 21.81767 | 61.13161 | -0.0715 | 5.28573 |
December | 744.00000 | 21.45758 | 60.35761 | -0.1712 | 5.88324 |
Annual Sum or Average | 8760.00000 | 21.85849 | 60.84383 | -0.5192 | 15.47125 |
Minimum of Months | 672.00000 | 21.35163 | 57.55519 | -1.1339 | 5.03455 |
Maximum of Months | 744.00000 | 22.23842 | 62.54826 | 0.02390 | 32.14790 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.05067 | 56.66208 | -0.2575 | 6.56171 |
February | 672.00000 | 21.07093 | 56.93332 | -0.2422 | 6.40419 |
March | 744.00000 | 21.08662 | 58.09452 | -0.2260 | 6.25307 |
April | 720.00000 | 21.20347 | 61.77794 | -0.1622 | 5.69028 |
May | 744.00000 | 21.41590 | 62.23986 | -1.2282 | 36.74058 |
June | 720.00000 | 21.64678 | 61.64668 | -1.1437 | 32.64976 |
July | 744.00000 | 21.76655 | 61.05498 | -1.1013 | 30.69332 |
August | 744.00000 | 21.63271 | 61.86872 | -1.1491 | 32.95101 |
September | 720.00000 | 21.66094 | 61.48783 | -1.1387 | 32.52017 |
October | 744.00000 | 21.46464 | 62.15269 | -0.0846 | 5.23609 |
November | 720.00000 | 21.22168 | 61.07004 | -0.1658 | 5.75052 |
December | 744.00000 | 21.09378 | 59.59471 | -0.2241 | 6.21574 |
Annual Sum or Average | 8760.00000 | 21.36112 | 60.39809 | -0.5959 | 17.37489 |
Minimum of Months | 672.00000 | 21.05067 | 56.66208 | -1.2282 | 5.23609 |
Maximum of Months | 744.00000 | 21.76655 | 62.23986 | -0.0846 | 36.74058 |
Report: OccupantComfortDataSummaryMonthly
For: MECH_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.01345 | 56.05500 | -0.2759 | 6.71332 |
February | 672.00000 | 21.02598 | 56.36974 | -0.2651 | 6.59933 |
March | 744.00000 | 21.03660 | 57.67581 | -0.2508 | 6.44909 |
April | 720.00000 | 21.06381 | 61.79360 | -0.2107 | 6.00382 |
May | 744.00000 | 21.14341 | 63.15427 | -1.3348 | 42.12677 |
June | 720.00000 | 21.24805 | 63.31102 | -1.2895 | 39.80675 |
July | 744.00000 | 21.27879 | 63.04478 | -1.2775 | 39.19996 |
August | 744.00000 | 21.20675 | 63.69408 | -1.3064 | 40.67280 |
September | 720.00000 | 21.20557 | 63.33765 | -1.3050 | 40.62894 |
October | 744.00000 | 21.11294 | 63.43834 | -0.1796 | 5.70803 |
November | 720.00000 | 21.06161 | 61.38142 | -0.2143 | 6.03791 |
December | 744.00000 | 21.02390 | 59.27539 | -0.2487 | 6.37508 |
Annual Sum or Average | 8760.00000 | 21.11888 | 61.06721 | -0.6825 | 20.61288 |
Minimum of Months | 672.00000 | 21.01345 | 56.05500 | -1.3348 | 5.70803 |
Maximum of Months | 744.00000 | 21.27879 | 63.69408 | -0.1796 | 42.12677 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.262151E+12 | 220518.53 | 02-JAN-14:00 | 741.17 | 0.810376E+12 | 0.00 | 0.107253E+13 | 2.98 | 3.93 | 07-JAN-19:02 | 0.00 | 0.00 |
February | 0.276178E+12 | 254325.80 | 11-FEB-16:03 | 665.33 | 0.849247E+12 | 0.00 | 0.112543E+13 | 2.97 | 3.93 | 12-FEB-19:03 | 0.00 | 0.00 |
March | 0.329865E+12 | 246838.95 | 13-MAR-15:03 | 738.67 | 0.102837E+13 | 0.00 | 0.135823E+13 | 3.02 | 3.94 | 19-MAR-08:62 | 0.00 | 0.00 |
April | 0.394556E+12 | 273933.84 | 14-APR-15:03 | 720.00 | 0.122483E+13 | 0.00 | 0.161939E+13 | 3.08 | 3.82 | 25-APR-16:00 | 0.00 | 0.00 |
May | 0.503221E+12 | 290642.90 | 29-MAY-18:03 | 744.00 | 0.159973E+13 | 0.00 | 0.210295E+13 | 3.18 | 3.74 | 24-MAY-18:03 | 0.00 | 0.00 |
June | 0.555244E+12 | 302651.01 | 08-JUN-18:03 | 720.00 | 0.177436E+13 | 0.00 | 0.232960E+13 | 3.20 | 3.69 | 18-JUN-18:03 | 0.00 | 0.00 |
July | 0.592290E+12 | 325242.66 | 27-JUL-18:03 | 744.00 | 0.187576E+13 | 0.00 | 0.246805E+13 | 3.18 | 3.77 | 02-JUL-18:03 | 0.00 | 0.00 |
August | 0.588352E+12 | 307724.77 | 21-AUG-16:00 | 744.00 | 0.187315E+13 | 0.00 | 0.246150E+13 | 3.19 | 3.74 | 12-AUG-08:03 | 0.00 | 0.00 |
September | 0.552925E+12 | 315842.55 | 18-SEP-18:03 | 720.00 | 0.176978E+13 | 0.00 | 0.232270E+13 | 3.21 | 3.70 | 27-SEP-18:03 | 0.00 | 0.00 |
October | 0.516331E+12 | 294975.88 | 03-OCT-15:03 | 744.00 | 0.165827E+13 | 0.00 | 0.217461E+13 | 3.21 | 3.79 | 31-OCT-05:50 | 0.00 | 0.00 |
November | 0.411026E+12 | 267465.13 | 04-NOV-18:03 | 720.00 | 0.132807E+13 | 0.00 | 0.173910E+13 | 3.18 | 3.92 | 25-NOV-09:02 | 0.00 | 0.00 |
December | 0.311584E+12 | 238903.49 | 24-DEC-16:03 | 742.33 | 0.987861E+12 | 0.00 | 0.129944E+13 | 3.06 | 3.96 | 30-DEC-19:02 | 0.00 | 0.00 |
Annual Sum or Average | 0.529372E+13 | 8743.50 | 0.167798E+14 | 0.00 | 0.220735E+14 | 3.12 | 0.00 | 0.00 | ||||
Minimum of Months | 0.262151E+12 | 220518.53 | 665.33 | 0.810376E+12 | 0.00 | 0.107253E+13 | 2.97 | 3.69 | 0.00 | 0.00 | ||
Maximum of Months | 0.592290E+12 | 325242.66 | 744.00 | 0.187576E+13 | 0.00 | 0.246805E+13 | 3.21 | 3.96 | 0.00 | 0.00 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.300872E+11 | 0.00 | 734.56 | 60722.14 | 18-JAN-11:40 | 0.00 | 30.42 | 59.61 | 0.10 | 0.00 | 0.04 | 0.22 | 18-JAN-11:40 |
February | 0.267775E+11 | 0.00 | 653.67 | 67096.09 | 06-FEB-11:40 | 0.00 | 30.37 | 59.11 | 0.10 | 0.00 | 0.04 | 0.24 | 06-FEB-11:40 |
March | 0.326279E+11 | 0.00 | 706.61 | 76117.71 | 20-MAR-10:40 | 0.00 | 30.95 | 58.42 | 0.11 | 0.00 | 0.04 | 0.27 | 20-MAR-10:40 |
April | 0.295541E+11 | 0.00 | 660.33 | 67094.71 | 18-APR-10:35 | 0.00 | 31.27 | 57.42 | 0.10 | 0.00 | 0.04 | 0.24 | 18-APR-10:35 |
May | 0.271795E+11 | 0.00 | 641.69 | 62175.45 | 01-MAY-10:35 | 0.00 | 31.67 | 55.71 | 0.09 | 0.00 | 0.04 | 0.22 | 01-MAY-10:35 |
June | 0.246494E+11 | 0.00 | 591.99 | 60608.83 | 13-JUN-10:35 | 0.00 | 32.05 | 54.59 | 0.09 | 0.00 | 0.03 | 0.22 | 13-JUN-10:35 |
July | 0.234215E+11 | 0.00 | 577.69 | 57541.44 | 07-JUL-10:35 | 0.00 | 31.96 | 53.26 | 0.08 | 0.00 | 0.03 | 0.21 | 07-JUL-10:35 |
August | 0.212880E+11 | 0.00 | 593.17 | 56734.21 | 29-AUG-10:35 | 0.00 | 31.69 | 53.88 | 0.07 | 0.00 | 0.03 | 0.20 | 29-AUG-10:35 |
September | 0.182328E+11 | 0.00 | 568.60 | 53503.53 | 05-SEP-10:40 | 0.00 | 32.18 | 53.89 | 0.06 | 0.00 | 0.03 | 0.19 | 05-SEP-10:40 |
October | 0.180498E+11 | 0.00 | 632.57 | 48951.54 | 02-OCT-10:40 | 0.00 | 32.39 | 55.75 | 0.06 | 0.00 | 0.02 | 0.18 | 02-OCT-10:40 |
November | 0.200005E+11 | 0.00 | 660.79 | 54928.78 | 27-NOV-11:40 | 0.00 | 31.39 | 57.61 | 0.07 | 0.00 | 0.03 | 0.20 | 27-NOV-11:40 |
December | 0.275284E+11 | 0.00 | 722.25 | 61852.08 | 21-DEC-11:40 | 0.00 | 30.85 | 59.13 | 0.09 | 0.00 | 0.04 | 0.22 | 21-DEC-11:40 |
Annual Sum or Average | 0.299397E+12 | 0.00 | 7743.92 | 0.00 | 31.44 | 56.52 | 0.08 | 0.00 | 0.03 | ||||
Minimum of Months | 0.180498E+11 | 0.00 | 568.60 | 48951.54 | 0.00 | 30.37 | 53.26 | 0.06 | 0.00 | 0.02 | 0.18 | ||
Maximum of Months | 0.326279E+11 | 0.00 | 734.56 | 76117.71 | 0.00 | 32.39 | 59.61 | 0.11 | 0.00 | 0.04 | 0.27 |
Report: DXReportMonthly
For: VAV WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.588169E+12 | 0.00 | 670.25 | 0.382147E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 578284.50 | 04-JAN-18:00 | 298749.05 | 07-JAN-11:35 | 0.00 | 0.00 | 0.00 |
February | 0.619413E+12 | 0.00 | 618.43 | 0.419633E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 608170.58 | 11-FEB-11:35 | 310069.82 | 11-FEB-11:35 | 0.00 | 0.00 | 0.00 |
March | 0.757114E+12 | 0.00 | 690.17 | 0.501126E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 596268.05 | 14-MAR-10:35 | 310026.83 | 13-MAR-18:10 | 0.00 | 0.00 | 0.00 |
April | 0.911343E+12 | 0.00 | 720.00 | 0.600445E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 603046.69 | 01-APR-17:12 | 338815.42 | 15-APR-17:12 | 0.00 | 0.00 | 0.00 |
May | 0.121938E+13 | 0.00 | 744.00 | 0.692135E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 695941.36 | 28-MAY-10:35 | 357834.93 | 31-MAY-10:50 | 0.00 | 0.00 | 0.00 |
June | 0.136731E+13 | 0.00 | 720.00 | 0.705696E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 702211.90 | 10-JUN-10:35 | 351671.61 | 11-JUN-10:35 | 0.00 | 0.00 | 0.00 |
July | 0.144135E+13 | 0.00 | 744.00 | 0.745435E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 735216.74 | 29-JUL-10:35 | 375034.43 | 29-JUL-17:13 | 0.00 | 0.00 | 0.00 |
August | 0.144829E+13 | 0.00 | 744.00 | 0.735571E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 729874.45 | 20-AUG-10:35 | 358432.36 | 08-AUG-10:35 | 0.00 | 0.00 | 0.00 |
September | 0.135531E+13 | 0.00 | 720.00 | 0.702928E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 701187.95 | 06-SEP-10:35 | 352052.96 | 09-SEP-10:35 | 0.00 | 0.00 | 0.00 |
October | 0.125873E+13 | 0.00 | 744.00 | 0.692163E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 719322.49 | 04-OCT-10:35 | 352541.95 | 09-OCT-10:50 | 0.00 | 0.00 | 0.00 |
November | 0.100361E+13 | 0.00 | 704.17 | 0.565162E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 655600.26 | 05-NOV-10:35 | 312593.18 | 03-NOV-10:35 | 0.00 | 0.00 | 0.00 |
December | 0.733564E+12 | 0.00 | 670.00 | 0.437330E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 638135.34 | 24-DEC-21:40 | 309229.50 | 10-DEC-11:35 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.127036E+14 | 0.00 | 8489.02 | 0.717977E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.588169E+12 | 0.00 | 618.43 | 0.382147E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 578284.50 | 298749.05 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.144829E+13 | 0.00 | 744.00 | 0.745435E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 735216.74 | 375034.43 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: FLR_3_DOAS COOLING COIL
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.678594E+11 | 0.00 | 629.83 | 0.426226E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 69237.45 | 07-JAN-03:30 | 32142.12 | 02-JAN-15:00 | 0.00 | 0.00 | 0.00 |
February | 0.730381E+11 | 0.00 | 607.50 | 0.481752E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 68133.31 | 11-FEB-19:00 | 32836.20 | 11-FEB-14:00 | 0.00 | 0.00 | 0.00 |
March | 0.884958E+11 | 0.00 | 672.00 | 0.577357E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 71113.56 | 19-MAR-07:30 | 32552.45 | 13-MAR-15:02 | 0.00 | 0.00 | 0.00 |
April | 0.104580E+12 | 0.00 | 718.83 | 0.690403E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 71819.61 | 26-APR-14:30 | 34346.54 | 17-APR-15:00 | 0.00 | 0.00 | 0.00 |
May | 0.131409E+12 | 0.00 | 744.00 | 0.777571E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 80981.70 | 28-MAY-18:00 | 35994.17 | 22-MAY-13:00 | 0.00 | 0.00 | 0.00 |
June | 0.141915E+12 | 0.00 | 720.00 | 0.777573E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 66955.40 | 28-JUN-12:00 | 34670.66 | 11-JUN-13:00 | 0.00 | 0.00 | 0.00 |
July | 0.147828E+12 | 0.00 | 744.00 | 0.811791E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 78320.79 | 02-JUL-17:10 | 36585.74 | 28-JUL-15:00 | 0.00 | 0.00 | 0.00 |
August | 0.150052E+12 | 0.00 | 744.00 | 0.808641E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 78921.70 | 28-AUG-14:10 | 35898.95 | 23-AUG-13:00 | 0.00 | 0.00 | 0.00 |
September | 0.140049E+12 | 0.00 | 720.00 | 0.773878E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 64377.90 | 06-SEP-11:00 | 34832.89 | 20-SEP-14:00 | 0.00 | 0.00 | 0.00 |
October | 0.134316E+12 | 0.00 | 744.00 | 0.776926E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 75497.39 | 01-OCT-07:10 | 34746.76 | 14-OCT-13:00 | 0.00 | 0.00 | 0.00 |
November | 0.111940E+12 | 0.00 | 692.67 | 0.645080E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 78941.50 | 08-NOV-09:00 | 33000.87 | 17-NOV-15:00 | 0.00 | 0.00 | 0.00 |
December | 0.842073E+11 | 0.00 | 655.33 | 0.497458E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 82125.11 | 24-DEC-08:17 | 32506.84 | 10-DEC-15:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.137569E+13 | 0.00 | 8392.17 | 0.804466E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.678594E+11 | 0.00 | 607.50 | 0.426226E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 64377.90 | 32142.12 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.150052E+12 | 0.00 | 744.00 | 0.811791E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 82125.11 | 36585.74 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.549733E+10 | 0.00 | 582.25 | 0.269398E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20555.66 | 07-JAN-09:01 | 15196.03 | 26-JAN-16:02 | 0.00 | 0.00 | 0.00 |
February | 0.632953E+10 | 0.00 | 560.05 | 0.334204E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19741.34 | 02-FEB-09:02 | 15195.07 | 24-FEB-19:01 | 0.00 | 0.00 | 0.00 |
March | 0.817434E+10 | 0.00 | 624.85 | 0.447441E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20369.81 | 19-MAR-08:62 | 15186.97 | 15-MAR-18:02 | 0.00 | 0.00 | 0.00 |
April | 0.101237E+11 | 0.00 | 662.38 | 0.577476E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18893.56 | 16-APR-08:62 | 14733.62 | 15-APR-18:02 | 0.00 | 0.00 | 0.00 |
May | 0.122213E+11 | 0.00 | 698.08 | 0.702649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19719.93 | 24-MAY-18:02 | 14731.00 | 16-MAY-15:02 | 0.00 | 0.00 | 0.00 |
June | 0.128607E+11 | 0.00 | 681.51 | 0.739887E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18550.38 | 13-JUN-08:61 | 14532.73 | 10-JUN-15:02 | 0.00 | 0.00 | 0.00 |
July | 0.143713E+11 | 0.00 | 711.35 | 0.855364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18163.38 | 24-JUL-08:62 | 14665.83 | 28-JUL-15:02 | 0.00 | 0.00 | 0.00 |
August | 0.137867E+11 | 0.00 | 700.13 | 0.805387E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20220.47 | 12-AUG-08:62 | 14661.94 | 31-AUG-15:02 | 0.00 | 0.00 | 0.00 |
September | 0.133697E+11 | 0.00 | 682.32 | 0.779853E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18652.03 | 16-SEP-08:62 | 14675.16 | 17-SEP-15:02 | 0.00 | 0.00 | 0.00 |
October | 0.126403E+11 | 0.00 | 700.45 | 0.729565E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19352.86 | 01-OCT-08:62 | 14629.05 | 14-OCT-15:02 | 0.00 | 0.00 | 0.00 |
November | 0.921094E+10 | 0.00 | 638.93 | 0.492251E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19340.16 | 24-NOV-09:02 | 14642.01 | 17-NOV-16:02 | 0.00 | 0.00 | 0.00 |
December | 0.668336E+10 | 0.00 | 599.64 | 0.335713E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20412.67 | 23-DEC-09:02 | 15181.47 | 20-DEC-16:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.125269E+12 | 0.00 | 7841.94 | 0.706919E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.549733E+10 | 0.00 | 560.05 | 0.269398E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18163.38 | 14532.73 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.143713E+11 | 0.00 | 711.35 | 0.855364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20555.66 | 15196.03 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.360931E+10 | 0.00 | 480.47 | 0.149835E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20730.55 | 07-JAN-09:01 | 15339.17 | 26-JAN-16:02 | 0.00 | 0.00 | 0.00 |
February | 0.486216E+10 | 0.00 | 501.27 | 0.230758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19471.05 | 18-FEB-09:01 | 15334.65 | 24-FEB-16:02 | 0.00 | 0.00 | 0.00 |
March | 0.703085E+10 | 0.00 | 583.94 | 0.363766E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20542.18 | 19-MAR-08:62 | 15300.56 | 15-MAR-15:01 | 0.00 | 0.00 | 0.00 |
April | 0.952975E+10 | 0.00 | 651.75 | 0.531652E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19112.25 | 16-APR-08:62 | 14943.04 | 15-APR-18:02 | 0.00 | 0.00 | 0.00 |
May | 0.122123E+11 | 0.00 | 698.10 | 0.701907E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20268.48 | 24-MAY-18:02 | 14887.34 | 20-MAY-15:02 | 0.00 | 0.00 | 0.00 |
June | 0.130636E+11 | 0.00 | 683.47 | 0.754903E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18647.63 | 13-JUN-08:61 | 14682.60 | 10-JUN-15:02 | 0.00 | 0.00 | 0.00 |
July | 0.144997E+11 | 0.00 | 712.44 | 0.863567E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18473.74 | 02-JUL-18:02 | 14839.95 | 28-JUL-15:02 | 0.00 | 0.00 | 0.00 |
August | 0.135233E+11 | 0.00 | 699.28 | 0.779757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20299.54 | 12-AUG-08:62 | 14646.63 | 19-AUG-15:02 | 0.00 | 0.00 | 0.00 |
September | 0.125306E+11 | 0.00 | 678.35 | 0.708070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18869.74 | 16-SEP-08:62 | 14643.59 | 08-SEP-15:02 | 0.00 | 0.00 | 0.00 |
October | 0.110591E+11 | 0.00 | 690.49 | 0.598321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19526.75 | 01-OCT-08:62 | 14793.07 | 18-OCT-15:02 | 0.00 | 0.00 | 0.00 |
November | 0.747555E+10 | 0.00 | 606.47 | 0.360117E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19491.81 | 24-NOV-09:02 | 14825.79 | 14-NOV-16:02 | 0.00 | 0.00 | 0.00 |
December | 0.484260E+10 | 0.00 | 519.36 | 0.213318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20291.47 | 23-DEC-09:02 | 14825.36 | 20-DEC-16:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.114239E+12 | 0.00 | 7505.39 | 0.625597E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.360931E+10 | 0.00 | 480.47 | 0.149835E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18473.74 | 14643.59 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.144997E+11 | 0.00 | 712.44 | 0.863567E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20730.55 | 15339.17 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.455826E+11 | 0.00 | 631.01 | 0.283158E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 56760.76 | 02-JAN-14:30 | 44761.69 | 02-JAN-14:30 | 0.00 | 0.00 | 0.00 |
February | 0.414757E+11 | 0.00 | 580.44 | 0.251492E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 50980.70 | 11-FEB-14:20 | 43095.66 | 22-FEB-14:50 | 0.00 | 0.00 | 0.00 |
March | 0.422313E+11 | 0.00 | 656.50 | 0.226321E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 45455.82 | 04-MAR-20:20 | 35249.05 | 02-MAR-14:30 | 0.00 | 0.00 | 0.00 |
April | 0.436538E+11 | 0.00 | 687.47 | 0.221405E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 39866.44 | 07-APR-21:00 | 28952.64 | 15-APR-19:10 | 0.00 | 0.00 | 0.00 |
May | 0.501381E+11 | 0.00 | 739.17 | 0.247021E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 42893.49 | 25-MAY-20:50 | 26833.81 | 22-MAY-20:20 | 0.00 | 0.00 | 0.00 |
June | 0.547656E+11 | 0.00 | 720.00 | 0.278189E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 47398.96 | 18-JUN-20:20 | 30321.22 | 03-JUN-21:00 | 0.00 | 0.00 | 0.00 |
July | 0.612697E+11 | 0.00 | 744.00 | 0.332071E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 42047.07 | 29-JUL-19:10 | 35459.18 | 29-JUL-19:10 | 0.00 | 0.00 | 0.00 |
August | 0.610536E+11 | 0.00 | 744.00 | 0.333345E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 41340.99 | 20-AUG-20:03 | 33042.52 | 20-AUG-20:03 | 0.00 | 0.00 | 0.00 |
September | 0.681249E+11 | 0.00 | 720.00 | 0.411311E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 48350.88 | 30-SEP-13:30 | 35708.57 | 23-SEP-12:10 | 0.00 | 0.00 | 0.00 |
October | 0.720983E+11 | 0.00 | 742.83 | 0.447246E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 52569.55 | 25-OCT-12:30 | 40364.81 | 25-OCT-12:40 | 0.00 | 0.00 | 0.00 |
November | 0.595191E+11 | 0.00 | 675.14 | 0.363804E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 55189.48 | 07-NOV-13:30 | 44615.28 | 07-NOV-13:40 | 0.00 | 0.00 | 0.00 |
December | 0.486168E+11 | 0.00 | 627.68 | 0.294926E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 56667.85 | 09-DEC-12:30 | 45453.35 | 03-DEC-14:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.648529E+12 | 0.00 | 8268.25 | 0.369029E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.414757E+11 | 0.00 | 580.44 | 0.221405E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 39866.44 | 26833.81 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.720983E+11 | 0.00 | 744.00 | 0.447246E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 56760.76 | 45453.35 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.449269E+11 | 0.00 | 521.43 | 0.235372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 138891.19 | 07-JAN-09:01 | 93859.06 | 24-JAN-19:01 | 0.00 | 0.00 | 0.00 |
February | 0.495889E+11 | 0.00 | 469.73 | 0.280714E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 129388.70 | 18-FEB-19:02 | 97058.33 | 24-FEB-19:01 | 0.00 | 0.00 | 0.00 |
March | 0.615357E+11 | 0.00 | 529.44 | 0.359941E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 137864.32 | 19-MAR-08:62 | 96637.96 | 14-MAR-18:02 | 0.00 | 0.00 | 0.00 |
April | 0.736779E+11 | 0.00 | 538.09 | 0.456159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 125820.00 | 29-APR-18:02 | 97018.26 | 17-APR-18:02 | 0.00 | 0.00 | 0.00 |
May | 0.914833E+11 | 0.00 | 616.31 | 0.602573E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 138635.74 | 24-MAY-18:02 | 95612.31 | 20-MAY-08:62 | 0.00 | 0.00 | 0.00 |
June | 0.978750E+11 | 0.00 | 624.67 | 0.662440E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 117525.29 | 23-JUN-15:02 | 95497.15 | 17-JUN-08:62 | 0.00 | 0.00 | 0.00 |
July | 0.103723E+12 | 0.00 | 662.78 | 0.704427E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 126891.49 | 02-JUL-18:02 | 95575.59 | 29-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.969086E+11 | 0.00 | 633.36 | 0.644793E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 135273.80 | 12-AUG-08:62 | 94561.89 | 19-AUG-18:02 | 0.00 | 0.00 | 0.00 |
September | 0.919014E+11 | 0.00 | 611.47 | 0.608522E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 117910.02 | 16-SEP-08:62 | 94297.91 | 01-SEP-18:02 | 0.00 | 0.00 | 0.00 |
October | 0.832404E+11 | 0.00 | 581.76 | 0.524719E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 128888.42 | 01-OCT-08:62 | 96481.19 | 17-OCT-18:02 | 0.00 | 0.00 | 0.00 |
November | 0.655798E+11 | 0.00 | 516.91 | 0.386498E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 128391.06 | 24-NOV-09:02 | 97905.99 | 12-NOV-09:02 | 0.00 | 0.00 | 0.00 |
December | 0.511800E+11 | 0.00 | 525.23 | 0.272134E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 133545.72 | 23-DEC-09:02 | 94147.29 | 09-DEC-19:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.911621E+12 | 0.00 | 6831.19 | 0.573829E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.449269E+11 | 0.00 | 469.73 | 0.235372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 117525.29 | 93859.06 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.103723E+12 | 0.00 | 662.78 | 0.704427E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 138891.19 | 97905.99 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_5_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.579143E+10 | 0.00 | 596.14 | 0.303351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18372.60 | 07-JAN-09:01 | 13721.08 | 26-JAN-16:02 | 0.00 | 0.00 | 0.00 |
February | 0.634637E+10 | 0.00 | 575.20 | 0.342013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17500.21 | 18-FEB-09:01 | 13720.45 | 24-FEB-19:01 | 0.00 | 0.00 | 0.00 |
March | 0.803494E+10 | 0.00 | 648.02 | 0.441324E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18429.89 | 19-MAR-08:62 | 13709.61 | 15-MAR-15:01 | 0.00 | 0.00 | 0.00 |
April | 0.100700E+11 | 0.00 | 684.62 | 0.571153E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16793.66 | 29-APR-08:62 | 13221.16 | 19-APR-08:62 | 0.00 | 0.00 | 0.00 |
May | 0.122725E+11 | 0.00 | 711.56 | 0.709469E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17831.74 | 24-MAY-18:02 | 13056.21 | 20-MAY-15:02 | 0.00 | 0.00 | 0.00 |
June | 0.135563E+11 | 0.00 | 696.88 | 0.805376E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16021.98 | 21-JUN-18:02 | 12993.37 | 01-JUN-15:02 | 0.00 | 0.00 | 0.00 |
July | 0.148119E+11 | 0.00 | 723.68 | 0.905932E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16503.21 | 02-JUL-18:02 | 13310.62 | 29-JUL-15:02 | 0.00 | 0.00 | 0.00 |
August | 0.138300E+11 | 0.00 | 710.00 | 0.820418E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18285.23 | 12-AUG-08:62 | 13007.48 | 31-AUG-15:02 | 0.00 | 0.00 | 0.00 |
September | 0.138651E+11 | 0.00 | 696.03 | 0.840389E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16638.77 | 05-SEP-08:62 | 13045.20 | 08-SEP-15:02 | 0.00 | 0.00 | 0.00 |
October | 0.128383E+11 | 0.00 | 714.50 | 0.754117E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17513.28 | 01-OCT-08:62 | 13355.80 | 25-OCT-15:02 | 0.00 | 0.00 | 0.00 |
November | 0.927716E+10 | 0.00 | 652.84 | 0.505158E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17481.22 | 24-NOV-09:02 | 13268.13 | 14-NOV-16:02 | 0.00 | 0.00 | 0.00 |
December | 0.625108E+10 | 0.00 | 598.51 | 0.315066E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18444.89 | 23-DEC-09:02 | 13344.29 | 20-DEC-16:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.126945E+12 | 0.00 | 8007.98 | 0.731377E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.579143E+10 | 0.00 | 575.20 | 0.303351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16021.98 | 12993.37 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.148119E+11 | 0.00 | 723.68 | 0.905932E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18444.89 | 13721.08 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_6_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.389451E+10 | 0.00 | 489.05 | 0.173267E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18642.24 | 07-JAN-09:01 | 12961.58 | 15-JAN-16:02 | 0.00 | 0.00 | 0.00 |
February | 0.484168E+10 | 0.00 | 519.57 | 0.239041E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17557.14 | 18-FEB-09:01 | 13836.07 | 22-FEB-16:02 | 0.00 | 0.00 | 0.00 |
March | 0.685468E+10 | 0.00 | 606.65 | 0.359389E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18563.07 | 19-MAR-08:62 | 13375.00 | 17-MAR-08:62 | 0.00 | 0.00 | 0.00 |
April | 0.946399E+10 | 0.00 | 680.89 | 0.527368E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17000.77 | 29-APR-18:02 | 13471.85 | 16-APR-15:02 | 0.00 | 0.00 | 0.00 |
May | 0.122603E+11 | 0.00 | 712.46 | 0.707278E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18307.32 | 24-MAY-18:02 | 13148.47 | 20-MAY-15:02 | 0.00 | 0.00 | 0.00 |
June | 0.137561E+11 | 0.00 | 698.47 | 0.821296E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16125.98 | 21-JUN-18:02 | 13104.78 | 01-JUN-15:02 | 0.00 | 0.00 | 0.00 |
July | 0.149366E+11 | 0.00 | 724.11 | 0.914412E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16773.25 | 02-JUL-18:02 | 13458.02 | 29-JUL-15:02 | 0.00 | 0.00 | 0.00 |
August | 0.135635E+11 | 0.00 | 709.25 | 0.790627E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18332.99 | 12-AUG-08:62 | 12993.49 | 19-AUG-15:02 | 0.00 | 0.00 | 0.00 |
September | 0.130218E+11 | 0.00 | 692.80 | 0.753970E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16839.37 | 05-SEP-08:62 | 12975.74 | 13-SEP-15:02 | 0.00 | 0.00 | 0.00 |
October | 0.112438E+11 | 0.00 | 706.21 | 0.619810E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17634.97 | 01-OCT-08:62 | 13082.81 | 17-OCT-18:02 | 0.00 | 0.00 | 0.00 |
November | 0.753874E+10 | 0.00 | 614.17 | 0.385848E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17597.36 | 24-NOV-09:02 | 13215.53 | 14-NOV-16:02 | 0.00 | 0.00 | 0.00 |
December | 0.441693E+10 | 0.00 | 503.24 | 0.196275E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18308.78 | 23-DEC-09:02 | 13014.50 | 03-DEC-19:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.115793E+12 | 0.00 | 7656.88 | 0.648858E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.389451E+10 | 0.00 | 489.05 | 0.173267E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16125.98 | 12961.58 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.149366E+11 | 0.00 | 724.11 | 0.914412E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18642.24 | 13836.07 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.144156E+10 | 0.00 | 556.97 | 0.717942E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5663.35 | 07-JAN-09:01 | 4051.79 | 26-JAN-16:02 | 0.00 | 0.00 | 0.00 |
February | 0.171243E+10 | 0.00 | 553.32 | 0.919900E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5429.47 | 02-FEB-09:02 | 4051.52 | 24-FEB-19:01 | 0.00 | 0.00 | 0.00 |
March | 0.224357E+10 | 0.00 | 616.58 | 0.124199E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5599.15 | 19-MAR-08:62 | 4050.10 | 20-MAR-15:01 | 0.00 | 0.00 | 0.00 |
April | 0.282257E+10 | 0.00 | 668.40 | 0.164174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5186.85 | 16-APR-08:62 | 3931.78 | 14-APR-15:02 | 0.00 | 0.00 | 0.00 |
May | 0.342546E+10 | 0.00 | 703.88 | 0.201743E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5334.89 | 24-MAY-18:02 | 3933.63 | 31-MAY-15:02 | 0.00 | 0.00 | 0.00 |
June | 0.360329E+10 | 0.00 | 686.68 | 0.212289E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5046.45 | 13-JUN-08:61 | 3934.69 | 28-JUN-15:02 | 0.00 | 0.00 | 0.00 |
July | 0.402515E+10 | 0.00 | 716.26 | 0.246315E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4915.73 | 24-JUL-08:62 | 3935.10 | 20-JUL-15:02 | 0.00 | 0.00 | 0.00 |
August | 0.382786E+10 | 0.00 | 706.60 | 0.229348E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5581.22 | 12-AUG-08:62 | 3930.78 | 21-AUG-15:02 | 0.00 | 0.00 | 0.00 |
September | 0.368803E+10 | 0.00 | 686.57 | 0.220648E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5143.77 | 16-SEP-08:62 | 3945.59 | 04-SEP-15:02 | 0.00 | 0.00 | 0.00 |
October | 0.343720E+10 | 0.00 | 703.21 | 0.202046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5322.42 | 01-OCT-08:62 | 3946.02 | 22-OCT-15:02 | 0.00 | 0.00 | 0.00 |
November | 0.247786E+10 | 0.00 | 637.94 | 0.134372E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5327.78 | 24-NOV-09:02 | 3916.05 | 20-NOV-16:02 | 0.00 | 0.00 | 0.00 |
December | 0.177414E+10 | 0.00 | 578.18 | 0.910788E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5645.65 | 23-DEC-09:02 | 4047.97 | 20-DEC-16:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.344791E+11 | 0.00 | 7814.58 | 0.199000E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.144156E+10 | 0.00 | 553.32 | 0.717942E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4915.73 | 3916.05 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.402515E+10 | 0.00 | 716.26 | 0.246315E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5663.35 | 4051.79 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.945329E+09 | 0.00 | 454.10 | 0.402077E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5714.15 | 07-JAN-09:01 | 4086.30 | 26-JAN-16:02 | 0.00 | 0.00 | 0.00 |
February | 0.132540E+10 | 0.00 | 495.67 | 0.640397E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5339.79 | 18-FEB-09:01 | 4085.07 | 24-FEB-16:02 | 0.00 | 0.00 | 0.00 |
March | 0.194328E+10 | 0.00 | 579.87 | 0.101694E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5641.16 | 19-MAR-08:62 | 4083.95 | 15-MAR-18:02 | 0.00 | 0.00 | 0.00 |
April | 0.266844E+10 | 0.00 | 664.73 | 0.151290E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5243.10 | 16-APR-08:62 | 3960.39 | 02-APR-18:02 | 0.00 | 0.00 | 0.00 |
May | 0.342405E+10 | 0.00 | 704.77 | 0.201205E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5486.29 | 24-MAY-18:02 | 3970.16 | 19-MAY-18:02 | 0.00 | 0.00 | 0.00 |
June | 0.365590E+10 | 0.00 | 688.70 | 0.216267E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5059.37 | 13-JUN-08:61 | 3964.88 | 28-JUN-15:02 | 0.00 | 0.00 | 0.00 |
July | 0.405891E+10 | 0.00 | 717.75 | 0.248440E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4948.22 | 15-JUL-08:62 | 3981.49 | 28-JUL-15:02 | 0.00 | 0.00 | 0.00 |
August | 0.376171E+10 | 0.00 | 705.14 | 0.222505E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5600.35 | 12-AUG-08:62 | 3975.00 | 06-AUG-15:02 | 0.00 | 0.00 | 0.00 |
September | 0.347283E+10 | 0.00 | 682.14 | 0.199981E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5201.33 | 16-SEP-08:62 | 3973.57 | 20-SEP-15:02 | 0.00 | 0.00 | 0.00 |
October | 0.302530E+10 | 0.00 | 694.87 | 0.165297E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5363.71 | 01-OCT-08:62 | 3949.43 | 14-OCT-15:02 | 0.00 | 0.00 | 0.00 |
November | 0.202302E+10 | 0.00 | 608.71 | 0.984997E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5365.09 | 24-NOV-09:02 | 3964.35 | 14-NOV-16:02 | 0.00 | 0.00 | 0.00 |
December | 0.129114E+10 | 0.00 | 498.49 | 0.579014E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5598.75 | 23-DEC-09:02 | 3961.20 | 03-DEC-16:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.315953E+11 | 0.00 | 7494.95 | 0.176733E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.945329E+09 | 0.00 | 454.10 | 0.402077E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4948.22 | 3949.43 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.405891E+10 | 0.00 | 717.75 | 0.248440E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5714.15 | 4086.30 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.129891E+11 | 0.00 | 662.08 | 0.838847E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23619.09 | 07-JAN-09:01 | 17032.58 | 26-JAN-16:02 | 0.00 | 0.00 | 0.00 |
February | 0.124059E+11 | 0.00 | 598.68 | 0.792331E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22992.84 | 02-FEB-09:02 | 17029.95 | 24-FEB-19:01 | 0.00 | 0.00 | 0.00 |
March | 0.133315E+11 | 0.00 | 654.76 | 0.818121E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23720.52 | 19-MAR-08:62 | 17025.57 | 20-MAR-15:01 | 0.00 | 0.00 | 0.00 |
April | 0.142435E+11 | 0.00 | 661.02 | 0.867965E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21764.66 | 16-APR-08:62 | 16491.66 | 05-APR-15:02 | 0.00 | 0.00 | 0.00 |
May | 0.163781E+11 | 0.00 | 693.64 | 0.998314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23176.37 | 24-MAY-18:02 | 16355.02 | 01-MAY-15:02 | 0.00 | 0.00 | 0.00 |
June | 0.175109E+11 | 0.00 | 678.07 | 0.109835E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 20430.00 | 13-JUN-08:61 | 16226.52 | 01-JUN-15:02 | 0.00 | 0.00 | 0.00 |
July | 0.191637E+11 | 0.00 | 707.29 | 0.122875E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 21396.89 | 02-JUL-18:02 | 16550.55 | 28-JUL-15:02 | 0.00 | 0.00 | 0.00 |
August | 0.188724E+11 | 0.00 | 696.38 | 0.121001E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 23868.60 | 12-AUG-08:62 | 16419.01 | 31-AUG-15:02 | 0.00 | 0.00 | 0.00 |
September | 0.199313E+11 | 0.00 | 684.67 | 0.132801E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 20813.32 | 28-SEP-08:62 | 16534.91 | 29-SEP-15:02 | 0.00 | 0.00 | 0.00 |
October | 0.204146E+11 | 0.00 | 709.93 | 0.138096E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 22524.73 | 01-OCT-08:62 | 16449.09 | 28-OCT-15:02 | 0.00 | 0.00 | 0.00 |
November | 0.168684E+11 | 0.00 | 668.46 | 0.110169E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 22609.12 | 24-NOV-09:02 | 16474.38 | 25-NOV-16:02 | 0.00 | 0.00 | 0.00 |
December | 0.141203E+11 | 0.00 | 657.81 | 0.890404E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23768.39 | 23-DEC-09:02 | 17016.97 | 20-DEC-16:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.196230E+12 | 0.00 | 8072.79 | 0.125538E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.124059E+11 | 0.00 | 598.68 | 0.792331E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20430.00 | 16226.52 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.204146E+11 | 0.00 | 709.93 | 0.138096E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 23868.60 | 17032.58 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 555.54 | 361.23 | 194.31 | 900.07 | 166.72 | 0.00 | 0.00 | 0.00 |
February | 490.42 | 278.92 | 211.50 | 844.33 | 130.15 | 0.00 | 0.00 | 0.00 |
March | 379.01 | 156.70 | 222.31 | 679.10 | 95.01 | 0.00 | 0.00 | 0.00 |
April | 271.75 | 55.67 | 216.09 | 561.84 | 40.43 | 0.00 | 0.00 | 0.00 |
May | 212.18 | 6.74 | 205.44 | 524.16 | 6.56 | 0.00 | 0.00 | 0.00 |
June | 200.14 | 0.42 | 199.72 | 548.84 | 0.36 | 0.00 | 0.00 | 0.00 |
July | 214.16 | 1.80 | 212.36 | 585.41 | 2.30 | 0.00 | 0.00 | 0.00 |
August | 240.75 | 18.00 | 222.75 | 632.33 | 0.13 | 0.00 | 0.00 | 0.00 |
September | 312.20 | 77.13 | 235.07 | 754.22 | 3.77 | 0.00 | 0.00 | 0.00 |
October | 433.29 | 206.02 | 227.26 | 886.28 | 12.12 | 0.00 | 0.00 | 0.00 |
November | 490.86 | 275.48 | 215.37 | 891.20 | 62.50 | 0.00 | 0.00 | 0.00 |
December | 535.60 | 338.19 | 197.42 | 885.80 | 136.38 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 360.73 | 147.45 | 213.28 | 723.87 | 54.39 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 200.14 | 0.42 | 194.31 | 524.16 | 0.13 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 555.54 | 361.23 | 235.07 | 900.07 | 166.72 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1564.36 | 1017.20 | 547.16 | 2522.61 | 500.18 | 0.00 | 0.00 | 0.00 |
February | 1380.98 | 785.42 | 595.57 | 2364.35 | 397.48 | 0.00 | 0.00 | 0.00 |
March | 1067.25 | 441.25 | 626.01 | 1897.89 | 301.51 | 0.00 | 0.00 | 0.00 |
April | 765.24 | 156.76 | 608.48 | 1568.11 | 142.90 | 0.00 | 0.00 | 0.00 |
May | 597.48 | 18.97 | 578.52 | 1438.87 | 28.83 | 0.00 | 0.00 | 0.00 |
June | 563.58 | 1.17 | 562.41 | 1502.50 | 3.88 | 0.00 | 0.00 | 0.00 |
July | 603.05 | 5.06 | 597.99 | 1623.72 | 12.18 | 0.00 | 0.00 | 0.00 |
August | 677.95 | 50.70 | 627.25 | 1743.64 | 2.58 | 0.00 | 0.00 | 0.00 |
September | 879.14 | 217.19 | 661.95 | 2110.43 | 24.80 | 0.00 | 0.00 | 0.00 |
October | 1220.12 | 580.15 | 639.96 | 2481.21 | 54.77 | 0.00 | 0.00 | 0.00 |
November | 1382.22 | 775.75 | 606.47 | 2492.39 | 201.33 | 0.00 | 0.00 | 0.00 |
December | 1508.22 | 952.31 | 555.91 | 2484.75 | 415.20 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1015.79 | 415.21 | 600.58 | 2017.47 | 172.85 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 563.58 | 1.17 | 547.16 | 1438.87 | 2.58 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1564.36 | 1017.20 | 661.95 | 2522.61 | 500.18 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2032.19 | 1321.40 | 710.79 | 3381.22 | 635.96 | 0.00 | 0.00 | 0.00 |
February | 1793.98 | 1020.30 | 773.67 | 3173.01 | 499.94 | 0.00 | 0.00 | 0.00 |
March | 1386.42 | 573.21 | 813.22 | 2549.42 | 377.97 | 0.00 | 0.00 | 0.00 |
April | 994.09 | 203.64 | 790.45 | 2113.68 | 172.51 | 0.00 | 0.00 | 0.00 |
May | 776.16 | 24.64 | 751.52 | 1949.82 | 32.99 | 0.00 | 0.00 | 0.00 |
June | 732.13 | 1.52 | 730.60 | 2040.57 | 3.97 | 0.00 | 0.00 | 0.00 |
July | 783.39 | 6.58 | 776.82 | 2202.27 | 13.52 | 0.00 | 0.00 | 0.00 |
August | 880.69 | 65.86 | 814.83 | 2372.17 | 1.93 | 0.00 | 0.00 | 0.00 |
September | 1142.06 | 282.14 | 859.91 | 2868.12 | 24.48 | 0.00 | 0.00 | 0.00 |
October | 1585.00 | 753.65 | 831.35 | 3368.04 | 53.38 | 0.00 | 0.00 | 0.00 |
November | 1795.58 | 1007.74 | 787.84 | 3367.13 | 246.15 | 0.00 | 0.00 | 0.00 |
December | 1959.26 | 1237.10 | 722.16 | 3333.82 | 523.23 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1319.57 | 539.38 | 780.19 | 2724.35 | 214.30 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 732.13 | 1.52 | 710.79 | 1949.82 | 1.93 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2032.19 | 1321.40 | 859.91 | 3381.22 | 635.96 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 109.84 | 71.42 | 38.42 | 176.69 | 33.73 | 0.00 | 0.00 | 0.00 |
February | 96.96 | 55.15 | 41.82 | 164.45 | 26.26 | 0.00 | 0.00 | 0.00 |
March | 74.94 | 30.98 | 43.95 | 130.10 | 19.13 | 0.00 | 0.00 | 0.00 |
April | 53.73 | 11.01 | 42.72 | 106.85 | 8.16 | 0.00 | 0.00 | 0.00 |
May | 41.95 | 1.33 | 40.62 | 100.95 | 1.29 | 0.00 | 0.00 | 0.00 |
June | 39.57 | 0.08 | 39.49 | 106.98 | 0.09 | 0.00 | 0.00 | 0.00 |
July | 42.34 | 0.36 | 41.99 | 114.71 | 0.45 | 0.00 | 0.00 | 0.00 |
August | 47.60 | 3.56 | 44.04 | 124.05 | 0.03 | 0.00 | 0.00 | 0.00 |
September | 61.73 | 15.25 | 46.48 | 150.02 | 0.68 | 0.00 | 0.00 | 0.00 |
October | 85.67 | 40.73 | 44.93 | 176.10 | 1.95 | 0.00 | 0.00 | 0.00 |
November | 97.05 | 54.47 | 42.58 | 175.81 | 12.17 | 0.00 | 0.00 | 0.00 |
December | 105.90 | 66.86 | 39.03 | 173.69 | 27.41 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 71.32 | 29.15 | 42.17 | 141.59 | 10.88 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 39.57 | 0.08 | 38.42 | 100.95 | 0.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 109.84 | 71.42 | 46.48 | 176.69 | 33.73 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 94.49 | 40.86 | 53.63 | 142.60 | 67.32 | 0.00 | 0.00 | 0.00 |
February | 118.59 | 54.01 | 64.58 | 195.21 | 52.23 | 0.00 | 0.00 | 0.00 |
March | 146.90 | 67.15 | 79.75 | 241.66 | 37.46 | 0.00 | 0.00 | 0.00 |
April | 161.24 | 74.56 | 86.68 | 291.76 | 15.07 | 0.00 | 0.00 | 0.00 |
May | 147.47 | 56.94 | 90.54 | 305.99 | 2.41 | 0.00 | 0.00 | 0.00 |
June | 124.86 | 35.04 | 89.82 | 290.48 | 0.17 | 0.00 | 0.00 | 0.00 |
July | 139.32 | 43.06 | 96.27 | 321.61 | 0.86 | 0.00 | 0.00 | 0.00 |
August | 139.00 | 45.18 | 93.82 | 313.71 | 0.05 | 0.00 | 0.00 | 0.00 |
September | 118.61 | 34.96 | 83.66 | 274.99 | 1.33 | 0.00 | 0.00 | 0.00 |
October | 118.21 | 46.17 | 72.04 | 246.48 | 3.71 | 0.00 | 0.00 | 0.00 |
November | 97.25 | 35.62 | 61.63 | 183.43 | 24.27 | 0.00 | 0.00 | 0.00 |
December | 97.50 | 43.57 | 53.92 | 155.74 | 53.27 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 125.34 | 48.08 | 77.26 | 247.25 | 21.38 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 94.49 | 34.96 | 53.63 | 142.60 | 0.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 161.24 | 74.56 | 96.27 | 321.61 | 67.32 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.33 | 0.00 | 23.33 | 31.12 | 35.24 | 0.00 | 0.00 | 0.00 |
February | 27.61 | 0.00 | 27.61 | 44.21 | 27.21 | 0.00 | 0.00 | 0.00 |
March | 32.94 | 0.00 | 32.94 | 51.88 | 19.79 | 0.00 | 0.00 | 0.00 |
April | 37.01 | 0.21 | 36.79 | 71.00 | 7.85 | 0.00 | 0.00 | 0.00 |
May | 42.02 | 1.72 | 40.30 | 100.44 | 1.25 | 0.00 | 0.00 | 0.00 |
June | 45.04 | 3.24 | 41.80 | 118.66 | 0.10 | 0.00 | 0.00 | 0.00 |
July | 45.63 | 2.27 | 43.35 | 121.60 | 0.47 | 0.00 | 0.00 | 0.00 |
August | 40.41 | 0.42 | 39.98 | 108.56 | 0.03 | 0.00 | 0.00 | 0.00 |
September | 35.78 | 0.01 | 35.77 | 98.73 | 0.69 | 0.00 | 0.00 | 0.00 |
October | 29.96 | 0.00 | 29.96 | 74.86 | 1.84 | 0.00 | 0.00 | 0.00 |
November | 26.05 | 0.00 | 26.05 | 54.05 | 12.49 | 0.00 | 0.00 | 0.00 |
December | 23.07 | 0.00 | 23.07 | 34.58 | 27.82 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 34.10 | 0.66 | 33.44 | 75.96 | 11.16 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 23.07 | 0.00 | 23.07 | 31.12 | 0.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 45.63 | 3.24 | 43.35 | 121.60 | 35.24 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 94.49 | 40.86 | 53.63 | 147.63 | 64.67 | 0.00 | 0.00 | 0.00 |
February | 118.59 | 54.01 | 64.58 | 199.21 | 50.36 | 0.00 | 0.00 | 0.00 |
March | 146.90 | 67.15 | 79.75 | 244.50 | 36.31 | 0.00 | 0.00 | 0.00 |
April | 161.24 | 74.56 | 86.68 | 292.92 | 14.69 | 0.00 | 0.00 | 0.00 |
May | 147.47 | 56.94 | 90.54 | 306.00 | 2.40 | 0.00 | 0.00 | 0.00 |
June | 124.86 | 35.04 | 89.82 | 290.05 | 0.18 | 0.00 | 0.00 | 0.00 |
July | 139.32 | 43.06 | 96.27 | 321.36 | 0.86 | 0.00 | 0.00 | 0.00 |
August | 139.00 | 45.18 | 93.82 | 314.25 | 0.05 | 0.00 | 0.00 | 0.00 |
September | 118.61 | 34.96 | 83.66 | 276.71 | 1.23 | 0.00 | 0.00 | 0.00 |
October | 118.21 | 46.17 | 72.04 | 249.71 | 3.37 | 0.00 | 0.00 | 0.00 |
November | 97.25 | 35.62 | 61.63 | 187.38 | 23.28 | 0.00 | 0.00 | 0.00 |
December | 97.50 | 43.57 | 53.92 | 160.29 | 50.99 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 125.34 | 48.08 | 77.26 | 249.44 | 20.57 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 94.49 | 34.96 | 53.63 | 147.63 | 0.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 161.24 | 74.56 | 96.27 | 321.36 | 64.67 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 87.85 | 57.13 | 30.73 | 136.24 | 36.51 | 0.00 | 0.00 | 0.00 |
February | 77.56 | 44.11 | 33.45 | 126.53 | 29.50 | 0.00 | 0.00 | 0.00 |
March | 59.94 | 24.78 | 35.16 | 99.58 | 23.00 | 0.00 | 0.00 | 0.00 |
April | 42.98 | 8.80 | 34.17 | 81.72 | 12.60 | 0.00 | 0.00 | 0.00 |
May | 33.55 | 1.07 | 32.49 | 73.72 | 3.24 | 0.00 | 0.00 | 0.00 |
June | 31.65 | 0.07 | 31.59 | 77.37 | 0.83 | 0.00 | 0.00 | 0.00 |
July | 33.87 | 0.28 | 33.58 | 84.83 | 1.60 | 0.00 | 0.00 | 0.00 |
August | 38.07 | 2.85 | 35.23 | 90.93 | 0.79 | 0.00 | 0.00 | 0.00 |
September | 49.37 | 12.20 | 37.18 | 113.15 | 3.02 | 0.00 | 0.00 | 0.00 |
October | 68.52 | 32.58 | 35.94 | 134.09 | 5.12 | 0.00 | 0.00 | 0.00 |
November | 77.63 | 43.57 | 34.06 | 134.10 | 15.45 | 0.00 | 0.00 | 0.00 |
December | 84.70 | 53.48 | 31.22 | 134.28 | 31.18 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 57.05 | 23.32 | 33.73 | 107.11 | 13.50 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 31.65 | 0.07 | 30.73 | 73.72 | 0.79 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 87.85 | 57.13 | 37.18 | 136.24 | 36.51 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 18.66 | 0.00 | 18.66 | 26.17 | 28.08 | 0.00 | 0.00 | 0.00 |
February | 22.09 | 0.00 | 22.09 | 37.58 | 21.21 | 0.00 | 0.00 | 0.00 |
March | 26.35 | 0.00 | 26.35 | 44.49 | 14.90 | 0.00 | 0.00 | 0.00 |
April | 29.61 | 0.17 | 29.44 | 60.94 | 5.16 | 0.00 | 0.00 | 0.00 |
May | 33.62 | 1.38 | 32.24 | 85.39 | 0.81 | 0.00 | 0.00 | 0.00 |
June | 36.04 | 2.59 | 33.45 | 99.91 | 0.04 | 0.00 | 0.00 | 0.00 |
July | 36.50 | 1.82 | 34.69 | 102.62 | 0.23 | 0.00 | 0.00 | 0.00 |
August | 32.33 | 0.34 | 31.99 | 92.33 | 0.01 | 0.00 | 0.00 | 0.00 |
September | 28.63 | 0.01 | 28.62 | 83.92 | 0.30 | 0.00 | 0.00 | 0.00 |
October | 23.97 | 0.00 | 23.97 | 64.46 | 1.06 | 0.00 | 0.00 | 0.00 |
November | 20.84 | 0.00 | 20.84 | 46.33 | 9.57 | 0.00 | 0.00 | 0.00 |
December | 18.46 | 0.00 | 18.46 | 29.31 | 22.01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 27.29 | 0.53 | 26.76 | 64.58 | 8.57 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 18.46 | 0.00 | 18.46 | 26.17 | 0.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 36.50 | 2.59 | 34.69 | 102.62 | 28.08 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 104.88 | 50.26 | 54.62 | 156.90 | 64.07 | 0.00 | 0.00 | 0.00 |
February | 121.65 | 56.52 | 65.13 | 195.83 | 48.12 | 0.00 | 0.00 | 0.00 |
March | 148.18 | 70.06 | 78.12 | 237.71 | 33.29 | 0.00 | 0.00 | 0.00 |
April | 161.02 | 71.88 | 89.14 | 291.42 | 14.04 | 0.00 | 0.00 | 0.00 |
May | 152.34 | 60.91 | 91.43 | 315.03 | 2.21 | 0.00 | 0.00 | 0.00 |
June | 149.72 | 57.46 | 92.26 | 333.55 | 0.19 | 0.00 | 0.00 | 0.00 |
July | 154.05 | 55.59 | 98.46 | 348.00 | 0.81 | 0.00 | 0.00 | 0.00 |
August | 140.80 | 47.14 | 93.66 | 318.17 | 0.05 | 0.00 | 0.00 | 0.00 |
September | 135.65 | 48.98 | 86.67 | 305.32 | 1.26 | 0.00 | 0.00 | 0.00 |
October | 124.71 | 53.52 | 71.19 | 258.77 | 3.51 | 0.00 | 0.00 | 0.00 |
November | 101.55 | 40.44 | 61.11 | 188.94 | 22.41 | 0.00 | 0.00 | 0.00 |
December | 82.13 | 29.10 | 53.03 | 128.41 | 51.48 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 131.41 | 53.45 | 77.96 | 256.75 | 20.01 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 82.13 | 29.10 | 53.03 | 128.41 | 0.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 161.02 | 71.88 | 98.46 | 348.00 | 64.07 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 109.84 | 71.42 | 38.42 | 175.72 | 33.57 | 0.00 | 0.00 | 0.00 |
February | 96.96 | 55.15 | 41.82 | 163.64 | 25.94 | 0.00 | 0.00 | 0.00 |
March | 74.94 | 30.98 | 43.95 | 129.10 | 18.71 | 0.00 | 0.00 | 0.00 |
April | 53.73 | 11.01 | 42.72 | 106.19 | 7.78 | 0.00 | 0.00 | 0.00 |
May | 41.95 | 1.33 | 40.62 | 100.66 | 1.25 | 0.00 | 0.00 | 0.00 |
June | 39.57 | 0.08 | 39.49 | 106.08 | 0.10 | 0.00 | 0.00 | 0.00 |
July | 42.34 | 0.36 | 41.99 | 114.15 | 0.45 | 0.00 | 0.00 | 0.00 |
August | 47.60 | 3.56 | 44.04 | 123.90 | 0.03 | 0.00 | 0.00 | 0.00 |
September | 61.73 | 15.25 | 46.48 | 149.38 | 0.69 | 0.00 | 0.00 | 0.00 |
October | 85.67 | 40.73 | 44.93 | 175.73 | 1.88 | 0.00 | 0.00 | 0.00 |
November | 97.05 | 54.47 | 42.58 | 175.35 | 12.03 | 0.00 | 0.00 | 0.00 |
December | 105.90 | 66.86 | 39.03 | 173.65 | 26.97 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 71.32 | 29.15 | 42.17 | 141.02 | 10.72 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 39.57 | 0.08 | 38.42 | 100.66 | 0.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 109.84 | 71.42 | 46.48 | 175.73 | 33.57 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.33 | 0.00 | 23.33 | 30.10 | 35.15 | 0.00 | 0.00 | 0.00 |
February | 27.61 | 0.00 | 27.61 | 43.28 | 27.01 | 0.00 | 0.00 | 0.00 |
March | 32.94 | 0.00 | 32.94 | 50.93 | 19.57 | 0.00 | 0.00 | 0.00 |
April | 37.01 | 0.21 | 36.79 | 70.29 | 7.48 | 0.00 | 0.00 | 0.00 |
May | 42.02 | 1.72 | 40.30 | 100.14 | 1.20 | 0.00 | 0.00 | 0.00 |
June | 45.04 | 3.24 | 41.80 | 117.77 | 0.11 | 0.00 | 0.00 | 0.00 |
July | 45.63 | 2.27 | 43.35 | 121.04 | 0.46 | 0.00 | 0.00 | 0.00 |
August | 40.41 | 0.42 | 39.98 | 108.40 | 0.03 | 0.00 | 0.00 | 0.00 |
September | 35.78 | 0.01 | 35.77 | 98.04 | 0.70 | 0.00 | 0.00 | 0.00 |
October | 29.96 | 0.00 | 29.96 | 74.38 | 1.78 | 0.00 | 0.00 | 0.00 |
November | 26.05 | 0.00 | 26.05 | 53.51 | 12.37 | 0.00 | 0.00 | 0.00 |
December | 23.07 | 0.00 | 23.07 | 34.46 | 27.27 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 34.10 | 0.66 | 33.44 | 75.35 | 11.03 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 23.07 | 0.00 | 23.07 | 30.10 | 0.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 45.63 | 3.24 | 43.35 | 121.04 | 35.15 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 104.88 | 50.26 | 54.62 | 161.61 | 61.29 | 0.00 | 0.00 | 0.00 |
February | 121.65 | 56.52 | 65.13 | 199.56 | 46.30 | 0.00 | 0.00 | 0.00 |
March | 148.18 | 70.06 | 78.12 | 240.37 | 32.19 | 0.00 | 0.00 | 0.00 |
April | 161.02 | 71.88 | 89.14 | 292.52 | 13.68 | 0.00 | 0.00 | 0.00 |
May | 152.34 | 60.91 | 91.43 | 315.06 | 2.20 | 0.00 | 0.00 | 0.00 |
June | 149.72 | 57.46 | 92.26 | 333.15 | 0.19 | 0.00 | 0.00 | 0.00 |
July | 154.05 | 55.59 | 98.46 | 347.76 | 0.81 | 0.00 | 0.00 | 0.00 |
August | 140.80 | 47.14 | 93.66 | 318.71 | 0.05 | 0.00 | 0.00 | 0.00 |
September | 135.65 | 48.98 | 86.67 | 306.99 | 1.18 | 0.00 | 0.00 | 0.00 |
October | 124.71 | 53.52 | 71.19 | 261.90 | 3.20 | 0.00 | 0.00 | 0.00 |
November | 101.55 | 40.44 | 61.11 | 192.80 | 21.45 | 0.00 | 0.00 | 0.00 |
December | 82.13 | 29.10 | 53.03 | 132.91 | 48.91 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 131.41 | 53.45 | 77.96 | 258.85 | 19.18 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 82.13 | 29.10 | 53.03 | 132.91 | 0.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 161.02 | 71.88 | 98.46 | 347.76 | 61.29 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 29.54 | 0.00 | 29.54 | 42.65 | 44.84 | 0.00 | 0.00 | 0.00 |
February | 34.97 | 0.00 | 34.97 | 61.44 | 33.95 | 0.00 | 0.00 | 0.00 |
March | 41.71 | 0.00 | 41.71 | 72.74 | 24.28 | 0.00 | 0.00 | 0.00 |
April | 46.86 | 0.27 | 46.60 | 98.45 | 9.60 | 0.00 | 0.00 | 0.00 |
May | 53.22 | 2.18 | 51.04 | 135.43 | 1.58 | 0.00 | 0.00 | 0.00 |
June | 57.04 | 4.10 | 52.94 | 156.32 | 0.22 | 0.00 | 0.00 | 0.00 |
July | 57.78 | 2.88 | 54.91 | 159.97 | 0.76 | 0.00 | 0.00 | 0.00 |
August | 51.17 | 0.54 | 50.63 | 143.18 | 0.08 | 0.00 | 0.00 | 0.00 |
September | 45.31 | 0.01 | 45.30 | 129.71 | 1.35 | 0.00 | 0.00 | 0.00 |
October | 37.94 | 0.00 | 37.94 | 99.07 | 3.08 | 0.00 | 0.00 | 0.00 |
November | 32.99 | 0.00 | 32.99 | 72.96 | 16.65 | 0.00 | 0.00 | 0.00 |
December | 29.22 | 0.00 | 29.22 | 47.46 | 35.50 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 43.19 | 0.84 | 42.35 | 101.81 | 14.24 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 29.22 | 0.00 | 29.22 | 42.65 | 0.08 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 57.78 | 4.10 | 54.91 | 159.97 | 44.84 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 10.89 | 0.00 | 10.89 | 15.72 | 16.53 | 0.00 | 0.00 | 0.00 |
February | 12.89 | 0.00 | 12.89 | 22.65 | 12.52 | 0.00 | 0.00 | 0.00 |
March | 15.38 | 0.00 | 15.38 | 26.82 | 8.95 | 0.00 | 0.00 | 0.00 |
April | 17.28 | 0.10 | 17.18 | 36.29 | 3.54 | 0.00 | 0.00 | 0.00 |
May | 19.62 | 0.80 | 18.81 | 49.93 | 0.58 | 0.00 | 0.00 | 0.00 |
June | 21.03 | 1.51 | 19.52 | 57.63 | 0.08 | 0.00 | 0.00 | 0.00 |
July | 21.30 | 1.06 | 20.24 | 58.97 | 0.28 | 0.00 | 0.00 | 0.00 |
August | 18.86 | 0.20 | 18.67 | 52.78 | 0.03 | 0.00 | 0.00 | 0.00 |
September | 16.70 | 0.00 | 16.70 | 47.82 | 0.50 | 0.00 | 0.00 | 0.00 |
October | 13.99 | 0.00 | 13.99 | 36.52 | 1.14 | 0.00 | 0.00 | 0.00 |
November | 12.16 | 0.00 | 12.16 | 26.90 | 6.14 | 0.00 | 0.00 | 0.00 |
December | 10.77 | 0.00 | 10.77 | 17.49 | 13.09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 15.92 | 0.31 | 15.61 | 37.53 | 5.25 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 10.77 | 0.00 | 10.77 | 15.72 | 0.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 21.30 | 1.51 | 20.24 | 58.97 | 16.53 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 51.25 | 33.32 | 17.93 | 85.04 | 15.26 | 0.00 | 0.00 | 0.00 |
February | 45.24 | 25.73 | 19.51 | 79.71 | 11.65 | 0.00 | 0.00 | 0.00 |
March | 34.96 | 14.46 | 20.51 | 63.97 | 8.40 | 0.00 | 0.00 | 0.00 |
April | 25.07 | 5.14 | 19.93 | 53.24 | 3.59 | 0.00 | 0.00 | 0.00 |
May | 19.57 | 0.62 | 18.95 | 50.19 | 0.60 | 0.00 | 0.00 | 0.00 |
June | 18.46 | 0.04 | 18.43 | 52.06 | 0.07 | 0.00 | 0.00 | 0.00 |
July | 19.76 | 0.17 | 19.59 | 55.68 | 0.27 | 0.00 | 0.00 | 0.00 |
August | 22.21 | 1.66 | 20.55 | 60.11 | 0.03 | 0.00 | 0.00 | 0.00 |
September | 28.80 | 7.12 | 21.69 | 72.06 | 0.47 | 0.00 | 0.00 | 0.00 |
October | 39.97 | 19.01 | 20.97 | 84.42 | 1.11 | 0.00 | 0.00 | 0.00 |
November | 45.28 | 25.41 | 19.87 | 84.62 | 5.74 | 0.00 | 0.00 | 0.00 |
December | 49.41 | 31.20 | 18.21 | 83.66 | 12.41 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 33.28 | 13.60 | 19.68 | 68.68 | 4.94 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 18.46 | 0.04 | 17.93 | 50.19 | 0.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 51.25 | 33.32 | 21.69 | 85.04 | 15.26 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 139.10 | 90.45 | 48.65 | 230.80 | 41.41 | 0.00 | 0.00 | 0.00 |
February | 122.80 | 69.84 | 52.96 | 216.34 | 31.63 | 0.00 | 0.00 | 0.00 |
March | 94.90 | 39.24 | 55.67 | 173.63 | 22.81 | 0.00 | 0.00 | 0.00 |
April | 68.05 | 13.94 | 54.11 | 144.50 | 9.73 | 0.00 | 0.00 | 0.00 |
May | 53.13 | 1.69 | 51.44 | 136.21 | 1.64 | 0.00 | 0.00 | 0.00 |
June | 50.12 | 0.10 | 50.01 | 141.31 | 0.20 | 0.00 | 0.00 | 0.00 |
July | 53.62 | 0.45 | 53.17 | 151.14 | 0.74 | 0.00 | 0.00 | 0.00 |
August | 60.28 | 4.51 | 55.78 | 163.15 | 0.07 | 0.00 | 0.00 | 0.00 |
September | 78.17 | 19.31 | 58.86 | 195.59 | 1.29 | 0.00 | 0.00 | 0.00 |
October | 108.49 | 51.59 | 56.91 | 229.14 | 3.00 | 0.00 | 0.00 | 0.00 |
November | 122.91 | 68.98 | 53.93 | 229.68 | 15.57 | 0.00 | 0.00 | 0.00 |
December | 134.11 | 84.68 | 49.43 | 227.07 | 33.68 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 90.33 | 36.92 | 53.40 | 186.40 | 13.41 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 50.12 | 0.10 | 48.65 | 136.21 | 0.07 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 139.10 | 90.45 | 58.86 | 230.80 | 41.41 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 109.84 | 71.42 | 38.42 | 174.61 | 33.54 | 0.00 | 0.00 | 0.00 |
February | 96.96 | 55.15 | 41.82 | 162.11 | 26.18 | 0.00 | 0.00 | 0.00 |
March | 74.94 | 30.98 | 43.95 | 127.74 | 19.03 | 0.00 | 0.00 | 0.00 |
April | 53.73 | 11.01 | 42.72 | 104.71 | 8.12 | 0.00 | 0.00 | 0.00 |
May | 41.95 | 1.33 | 40.62 | 99.32 | 1.24 | 0.00 | 0.00 | 0.00 |
June | 39.57 | 0.08 | 39.49 | 105.44 | 0.08 | 0.00 | 0.00 | 0.00 |
July | 42.34 | 0.36 | 41.99 | 113.04 | 0.43 | 0.00 | 0.00 | 0.00 |
August | 47.60 | 3.56 | 44.04 | 122.41 | 0.04 | 0.00 | 0.00 | 0.00 |
September | 61.73 | 15.25 | 46.48 | 148.11 | 0.64 | 0.00 | 0.00 | 0.00 |
October | 85.67 | 40.73 | 44.93 | 174.13 | 1.86 | 0.00 | 0.00 | 0.00 |
November | 97.05 | 54.47 | 42.58 | 173.70 | 11.98 | 0.00 | 0.00 | 0.00 |
December | 105.90 | 66.86 | 39.03 | 171.50 | 27.30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 71.32 | 29.15 | 42.17 | 139.62 | 10.81 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 39.57 | 0.08 | 38.42 | 99.32 | 0.04 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 109.84 | 71.42 | 46.48 | 174.61 | 33.54 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 94.49 | 40.86 | 53.63 | 139.97 | 66.93 | 0.00 | 0.00 | 0.00 |
February | 118.59 | 54.01 | 64.58 | 191.95 | 52.08 | 0.00 | 0.00 | 0.00 |
March | 146.90 | 67.15 | 79.75 | 237.49 | 37.38 | 0.00 | 0.00 | 0.00 |
April | 161.24 | 74.56 | 86.68 | 287.21 | 15.03 | 0.00 | 0.00 | 0.00 |
May | 147.47 | 56.94 | 90.54 | 301.62 | 2.32 | 0.00 | 0.00 | 0.00 |
June | 124.86 | 35.04 | 89.82 | 286.51 | 0.16 | 0.00 | 0.00 | 0.00 |
July | 139.32 | 43.06 | 96.27 | 317.49 | 0.81 | 0.00 | 0.00 | 0.00 |
August | 139.00 | 45.18 | 93.82 | 309.75 | 0.06 | 0.00 | 0.00 | 0.00 |
September | 118.61 | 34.96 | 83.66 | 271.46 | 1.22 | 0.00 | 0.00 | 0.00 |
October | 118.21 | 46.17 | 72.04 | 243.54 | 3.49 | 0.00 | 0.00 | 0.00 |
November | 97.25 | 35.62 | 61.63 | 180.62 | 23.87 | 0.00 | 0.00 | 0.00 |
December | 97.50 | 43.57 | 53.92 | 152.94 | 53.11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 125.34 | 48.08 | 77.26 | 243.66 | 21.24 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 94.49 | 34.96 | 53.63 | 139.97 | 0.06 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 161.24 | 74.56 | 96.27 | 317.49 | 66.93 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.33 | 0.00 | 23.33 | 30.32 | 34.97 | 0.00 | 0.00 | 0.00 |
February | 27.61 | 0.00 | 27.61 | 43.13 | 27.08 | 0.00 | 0.00 | 0.00 |
March | 32.94 | 0.00 | 32.94 | 50.45 | 19.70 | 0.00 | 0.00 | 0.00 |
April | 37.01 | 0.21 | 36.79 | 69.28 | 7.80 | 0.00 | 0.00 | 0.00 |
May | 42.02 | 1.72 | 40.30 | 98.67 | 1.21 | 0.00 | 0.00 | 0.00 |
June | 45.04 | 3.24 | 41.80 | 116.89 | 0.09 | 0.00 | 0.00 | 0.00 |
July | 45.63 | 2.27 | 43.35 | 119.85 | 0.44 | 0.00 | 0.00 | 0.00 |
August | 40.41 | 0.42 | 39.98 | 107.01 | 0.04 | 0.00 | 0.00 | 0.00 |
September | 35.78 | 0.01 | 35.77 | 97.39 | 0.63 | 0.00 | 0.00 | 0.00 |
October | 29.96 | 0.00 | 29.96 | 73.91 | 1.71 | 0.00 | 0.00 | 0.00 |
November | 26.05 | 0.00 | 26.05 | 53.11 | 12.25 | 0.00 | 0.00 | 0.00 |
December | 23.07 | 0.00 | 23.07 | 33.71 | 27.65 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 34.10 | 0.66 | 33.44 | 74.63 | 11.07 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 23.07 | 0.00 | 23.07 | 30.32 | 0.04 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 45.63 | 3.24 | 43.35 | 119.85 | 34.97 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 94.49 | 40.86 | 53.63 | 145.17 | 64.07 | 0.00 | 0.00 | 0.00 |
February | 118.59 | 54.01 | 64.58 | 196.02 | 50.13 | 0.00 | 0.00 | 0.00 |
March | 146.90 | 67.15 | 79.75 | 240.34 | 36.19 | 0.00 | 0.00 | 0.00 |
April | 161.24 | 74.56 | 86.68 | 288.34 | 14.65 | 0.00 | 0.00 | 0.00 |
May | 147.47 | 56.94 | 90.54 | 301.61 | 2.31 | 0.00 | 0.00 | 0.00 |
June | 124.86 | 35.04 | 89.82 | 286.08 | 0.16 | 0.00 | 0.00 | 0.00 |
July | 139.32 | 43.06 | 96.27 | 317.23 | 0.82 | 0.00 | 0.00 | 0.00 |
August | 139.00 | 45.18 | 93.82 | 310.28 | 0.06 | 0.00 | 0.00 | 0.00 |
September | 118.61 | 34.96 | 83.66 | 273.19 | 1.13 | 0.00 | 0.00 | 0.00 |
October | 118.21 | 46.17 | 72.04 | 246.81 | 3.15 | 0.00 | 0.00 | 0.00 |
November | 97.25 | 35.62 | 61.63 | 184.66 | 22.83 | 0.00 | 0.00 | 0.00 |
December | 97.50 | 43.57 | 53.92 | 157.68 | 50.61 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 125.34 | 48.08 | 77.26 | 245.89 | 20.38 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 94.49 | 34.96 | 53.63 | 145.17 | 0.06 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 161.24 | 74.56 | 96.27 | 317.23 | 64.07 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 161.09 | 104.75 | 56.34 | 252.99 | 51.08 | 0.00 | 0.00 | 0.00 |
February | 142.21 | 80.88 | 61.33 | 236.24 | 39.09 | 0.00 | 0.00 | 0.00 |
March | 109.90 | 45.44 | 64.46 | 187.95 | 27.33 | 0.00 | 0.00 | 0.00 |
April | 78.80 | 16.14 | 62.66 | 157.19 | 10.48 | 0.00 | 0.00 | 0.00 |
May | 61.53 | 1.95 | 59.57 | 151.70 | 1.57 | 0.00 | 0.00 | 0.00 |
June | 58.04 | 0.12 | 57.92 | 160.49 | 0.08 | 0.00 | 0.00 | 0.00 |
July | 62.10 | 0.52 | 61.58 | 172.11 | 0.47 | 0.00 | 0.00 | 0.00 |
August | 69.81 | 5.22 | 64.59 | 185.22 | 0.02 | 0.00 | 0.00 | 0.00 |
September | 90.53 | 22.37 | 68.17 | 220.72 | 0.72 | 0.00 | 0.00 | 0.00 |
October | 125.64 | 59.74 | 65.90 | 256.81 | 2.53 | 0.00 | 0.00 | 0.00 |
November | 142.33 | 79.88 | 62.45 | 253.77 | 17.97 | 0.00 | 0.00 | 0.00 |
December | 155.31 | 98.06 | 57.25 | 249.21 | 41.64 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 104.60 | 42.76 | 61.85 | 206.89 | 15.99 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 58.04 | 0.12 | 56.34 | 151.70 | 0.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 161.09 | 104.75 | 68.17 | 256.81 | 51.08 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 163.29 | 0.00 | 163.29 | 223.50 | 275.11 | 0.00 | 0.00 | 0.00 |
February | 193.28 | 0.00 | 193.28 | 322.09 | 218.65 | 0.00 | 0.00 | 0.00 |
March | 230.56 | 0.00 | 230.56 | 382.38 | 166.38 | 0.00 | 0.00 | 0.00 |
April | 259.03 | 1.48 | 257.55 | 526.56 | 75.87 | 0.00 | 0.00 | 0.00 |
May | 294.14 | 12.05 | 282.09 | 717.72 | 16.06 | 0.00 | 0.00 | 0.00 |
June | 315.27 | 22.68 | 292.60 | 836.44 | 2.89 | 0.00 | 0.00 | 0.00 |
July | 319.36 | 15.90 | 303.47 | 866.36 | 7.51 | 0.00 | 0.00 | 0.00 |
August | 282.83 | 2.96 | 279.86 | 770.21 | 2.52 | 0.00 | 0.00 | 0.00 |
September | 250.44 | 0.06 | 250.38 | 709.93 | 13.35 | 0.00 | 0.00 | 0.00 |
October | 209.71 | 0.00 | 209.71 | 546.52 | 24.14 | 0.00 | 0.00 | 0.00 |
November | 182.34 | 0.00 | 182.34 | 394.16 | 107.29 | 0.00 | 0.00 | 0.00 |
December | 161.51 | 0.00 | 161.51 | 250.34 | 224.13 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 238.71 | 4.62 | 234.09 | 546.57 | 93.96 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 161.51 | 0.00 | 161.51 | 223.50 | 2.52 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 319.36 | 22.68 | 303.47 | 866.36 | 275.11 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 163.29 | 0.00 | 163.29 | 215.76 | 289.12 | 0.00 | 0.00 | 0.00 |
February | 193.28 | 0.00 | 193.28 | 312.40 | 232.08 | 0.00 | 0.00 | 0.00 |
March | 230.56 | 0.00 | 230.56 | 370.95 | 178.70 | 0.00 | 0.00 | 0.00 |
April | 259.03 | 1.48 | 257.55 | 513.06 | 85.84 | 0.00 | 0.00 | 0.00 |
May | 294.14 | 12.05 | 282.09 | 698.87 | 19.96 | 0.00 | 0.00 | 0.00 |
June | 315.27 | 22.68 | 292.60 | 816.59 | 4.02 | 0.00 | 0.00 | 0.00 |
July | 319.36 | 15.90 | 303.47 | 848.63 | 9.29 | 0.00 | 0.00 | 0.00 |
August | 282.83 | 2.96 | 279.86 | 750.60 | 3.72 | 0.00 | 0.00 | 0.00 |
September | 250.44 | 0.06 | 250.38 | 693.60 | 16.87 | 0.00 | 0.00 | 0.00 |
October | 209.71 | 0.00 | 209.71 | 530.25 | 28.81 | 0.00 | 0.00 | 0.00 |
November | 182.34 | 0.00 | 182.34 | 380.14 | 115.43 | 0.00 | 0.00 | 0.00 |
December | 161.51 | 0.00 | 161.51 | 241.60 | 237.36 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 238.71 | 4.62 | 234.09 | 532.07 | 101.20 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 161.51 | 0.00 | 161.51 | 215.76 | 3.72 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 319.36 | 22.68 | 303.47 | 848.63 | 289.12 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.33 | 0.00 | 23.33 | 31.26 | 44.78 | 0.00 | 0.00 | 0.00 |
February | 27.61 | 0.00 | 27.61 | 43.51 | 37.55 | 0.00 | 0.00 | 0.00 |
March | 32.94 | 0.00 | 32.94 | 51.98 | 29.41 | 0.00 | 0.00 | 0.00 |
April | 37.01 | 0.21 | 36.79 | 73.49 | 14.96 | 0.00 | 0.00 | 0.00 |
May | 42.02 | 1.72 | 40.30 | 101.26 | 4.48 | 0.00 | 0.00 | 0.00 |
June | 45.04 | 3.24 | 41.80 | 119.30 | 1.08 | 0.00 | 0.00 | 0.00 |
July | 45.63 | 2.27 | 43.35 | 126.00 | 2.00 | 0.00 | 0.00 | 0.00 |
August | 40.41 | 0.42 | 39.98 | 108.35 | 1.23 | 0.00 | 0.00 | 0.00 |
September | 35.78 | 0.01 | 35.77 | 101.29 | 2.98 | 0.00 | 0.00 | 0.00 |
October | 29.96 | 0.00 | 29.96 | 75.95 | 5.50 | 0.00 | 0.00 | 0.00 |
November | 26.05 | 0.00 | 26.05 | 54.45 | 18.75 | 0.00 | 0.00 | 0.00 |
December | 23.07 | 0.00 | 23.07 | 35.45 | 36.79 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 34.10 | 0.66 | 33.44 | 77.02 | 16.53 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 23.07 | 0.00 | 23.07 | 31.26 | 1.08 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 45.63 | 3.24 | 43.35 | 126.00 | 44.78 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 209.74 | 100.51 | 109.23 | 328.42 | 158.60 | 0.00 | 0.00 | 0.00 |
February | 243.28 | 113.02 | 130.26 | 398.58 | 132.41 | 0.00 | 0.00 | 0.00 |
March | 296.35 | 140.11 | 156.24 | 482.37 | 102.03 | 0.00 | 0.00 | 0.00 |
April | 322.01 | 143.75 | 178.26 | 593.51 | 56.69 | 0.00 | 0.00 | 0.00 |
May | 304.66 | 121.80 | 182.86 | 626.36 | 17.13 | 0.00 | 0.00 | 0.00 |
June | 299.42 | 114.92 | 184.51 | 667.07 | 4.12 | 0.00 | 0.00 | 0.00 |
July | 308.07 | 111.17 | 196.90 | 710.13 | 7.54 | 0.00 | 0.00 | 0.00 |
August | 281.59 | 94.28 | 187.31 | 631.77 | 4.79 | 0.00 | 0.00 | 0.00 |
September | 271.28 | 97.96 | 173.32 | 622.86 | 11.27 | 0.00 | 0.00 | 0.00 |
October | 249.41 | 107.04 | 142.37 | 526.95 | 20.82 | 0.00 | 0.00 | 0.00 |
November | 203.09 | 80.88 | 122.21 | 388.01 | 66.70 | 0.00 | 0.00 | 0.00 |
December | 164.25 | 58.20 | 106.06 | 268.65 | 132.99 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 262.80 | 106.89 | 155.91 | 520.87 | 59.27 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 164.25 | 58.20 | 106.06 | 268.65 | 4.12 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 322.01 | 143.75 | 196.90 | 710.13 | 158.60 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 109.84 | 71.42 | 38.42 | 180.34 | 41.63 | 0.00 | 0.00 | 0.00 |
February | 96.96 | 55.15 | 41.82 | 166.60 | 34.95 | 0.00 | 0.00 | 0.00 |
March | 74.94 | 30.98 | 43.95 | 131.73 | 27.77 | 0.00 | 0.00 | 0.00 |
April | 53.73 | 11.01 | 42.72 | 110.07 | 14.93 | 0.00 | 0.00 | 0.00 |
May | 41.95 | 1.33 | 40.62 | 100.38 | 4.51 | 0.00 | 0.00 | 0.00 |
June | 39.57 | 0.08 | 39.49 | 107.12 | 1.06 | 0.00 | 0.00 | 0.00 |
July | 42.34 | 0.36 | 41.99 | 118.53 | 2.00 | 0.00 | 0.00 | 0.00 |
August | 47.60 | 3.56 | 44.04 | 123.41 | 1.26 | 0.00 | 0.00 | 0.00 |
September | 61.73 | 15.25 | 46.48 | 153.56 | 2.97 | 0.00 | 0.00 | 0.00 |
October | 85.67 | 40.73 | 44.93 | 179.03 | 5.44 | 0.00 | 0.00 | 0.00 |
November | 97.05 | 54.47 | 42.58 | 179.13 | 17.67 | 0.00 | 0.00 | 0.00 |
December | 105.90 | 66.86 | 39.03 | 177.81 | 34.78 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 71.32 | 29.15 | 42.17 | 143.86 | 15.66 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 39.57 | 0.08 | 38.42 | 100.38 | 1.06 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 109.84 | 71.42 | 46.48 | 180.34 | 41.63 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 29.54 | 0.00 | 29.54 | 41.69 | 44.04 | 0.00 | 0.00 | 0.00 |
February | 34.97 | 0.00 | 34.97 | 60.72 | 32.98 | 0.00 | 0.00 | 0.00 |
March | 41.71 | 0.00 | 41.71 | 72.29 | 23.22 | 0.00 | 0.00 | 0.00 |
April | 46.86 | 0.27 | 46.60 | 99.01 | 8.04 | 0.00 | 0.00 | 0.00 |
May | 53.22 | 2.18 | 51.04 | 136.69 | 1.27 | 0.00 | 0.00 | 0.00 |
June | 57.04 | 4.10 | 52.94 | 156.99 | 0.10 | 0.00 | 0.00 | 0.00 |
July | 57.78 | 2.88 | 54.91 | 159.89 | 0.54 | 0.00 | 0.00 | 0.00 |
August | 51.17 | 0.54 | 50.63 | 144.77 | 0.02 | 0.00 | 0.00 | 0.00 |
September | 45.31 | 0.01 | 45.30 | 130.92 | 0.68 | 0.00 | 0.00 | 0.00 |
October | 37.94 | 0.00 | 37.94 | 102.09 | 1.97 | 0.00 | 0.00 | 0.00 |
November | 32.99 | 0.00 | 32.99 | 74.42 | 14.97 | 0.00 | 0.00 | 0.00 |
December | 29.22 | 0.00 | 29.22 | 46.81 | 34.74 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 43.19 | 0.84 | 42.35 | 102.39 | 13.47 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 29.22 | 0.00 | 29.22 | 41.69 | 0.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 57.78 | 4.10 | 54.91 | 159.89 | 44.04 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 26.43 | 0.00 | 26.43 | 37.30 | 39.40 | 0.00 | 0.00 | 0.00 |
February | 31.29 | 0.00 | 31.29 | 54.33 | 29.51 | 0.00 | 0.00 | 0.00 |
March | 37.32 | 0.00 | 37.32 | 64.68 | 20.78 | 0.00 | 0.00 | 0.00 |
April | 41.93 | 0.24 | 41.69 | 88.58 | 7.19 | 0.00 | 0.00 | 0.00 |
May | 47.61 | 1.95 | 45.66 | 122.29 | 1.13 | 0.00 | 0.00 | 0.00 |
June | 51.04 | 3.67 | 47.36 | 140.46 | 0.09 | 0.00 | 0.00 | 0.00 |
July | 51.70 | 2.57 | 49.12 | 143.05 | 0.49 | 0.00 | 0.00 | 0.00 |
August | 45.78 | 0.48 | 45.30 | 129.52 | 0.02 | 0.00 | 0.00 | 0.00 |
September | 40.54 | 0.01 | 40.53 | 117.13 | 0.61 | 0.00 | 0.00 | 0.00 |
October | 33.95 | 0.00 | 33.95 | 91.34 | 1.77 | 0.00 | 0.00 | 0.00 |
November | 29.52 | 0.00 | 29.52 | 66.58 | 13.39 | 0.00 | 0.00 | 0.00 |
December | 26.14 | 0.00 | 26.14 | 41.88 | 31.08 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 38.64 | 0.75 | 37.89 | 91.61 | 12.05 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 26.14 | 0.00 | 26.14 | 37.30 | 0.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 51.70 | 3.67 | 49.12 | 143.05 | 39.40 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 410.06 | 266.64 | 143.43 | 673.16 | 119.75 | 0.00 | 0.00 | 0.00 |
February | 362.00 | 205.88 | 156.12 | 631.04 | 90.61 | 0.00 | 0.00 | 0.00 |
March | 279.76 | 115.66 | 164.10 | 507.18 | 64.31 | 0.00 | 0.00 | 0.00 |
April | 200.59 | 41.09 | 159.50 | 425.64 | 24.28 | 0.00 | 0.00 | 0.00 |
May | 156.62 | 4.97 | 151.65 | 405.48 | 3.86 | 0.00 | 0.00 | 0.00 |
June | 147.73 | 0.31 | 147.43 | 419.00 | 0.29 | 0.00 | 0.00 | 0.00 |
July | 158.08 | 1.33 | 156.75 | 445.31 | 1.60 | 0.00 | 0.00 | 0.00 |
August | 177.71 | 13.29 | 164.42 | 485.09 | 0.07 | 0.00 | 0.00 | 0.00 |
September | 230.45 | 56.93 | 173.52 | 577.94 | 1.96 | 0.00 | 0.00 | 0.00 |
October | 319.83 | 152.07 | 167.75 | 680.75 | 5.83 | 0.00 | 0.00 | 0.00 |
November | 362.32 | 203.35 | 158.97 | 677.52 | 41.47 | 0.00 | 0.00 | 0.00 |
December | 395.35 | 249.63 | 145.72 | 663.11 | 97.08 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 266.27 | 108.84 | 157.43 | 548.86 | 37.38 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 147.73 | 0.31 | 143.43 | 405.48 | 0.07 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 410.06 | 266.64 | 173.52 | 680.75 | 119.75 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.148795E+10 | 0.967519E+09 | 0.520433E+09 | 0.241075E+10 | 0.446551E+09 |
February | 0.118642E+10 | 0.674762E+09 | 0.511657E+09 | 0.204261E+10 | 0.314857E+09 |
March | 0.101513E+10 | 0.419697E+09 | 0.595431E+09 | 0.181890E+10 | 0.254480E+09 |
April | 0.704385E+09 | 0.144292E+09 | 0.560093E+09 | 0.145629E+10 | 0.104798E+09 |
May | 0.568300E+09 | 18039893.06 | 0.550260E+09 | 0.140390E+10 | 17567904.18 |
June | 0.518766E+09 | 1079877.92 | 0.517686E+09 | 0.142259E+10 | 946029.98 |
July | 0.573595E+09 | 4816469.25 | 0.568779E+09 | 0.156796E+10 | 6150496.22 |
August | 0.644834E+09 | 48222350.38 | 0.596611E+09 | 0.169363E+10 | 352411.32 |
September | 0.809229E+09 | 0.199919E+09 | 0.609311E+09 | 0.195495E+10 | 9773733.42 |
October | 0.116052E+10 | 0.551817E+09 | 0.608706E+09 | 0.237380E+10 | 32465453.46 |
November | 0.127230E+10 | 0.714056E+09 | 0.558244E+09 | 0.230998E+10 | 0.161993E+09 |
December | 0.143456E+10 | 0.905795E+09 | 0.528761E+09 | 0.237253E+10 | 0.365284E+09 |
Annual Sum or Average | 0.113760E+11 | 0.465001E+10 | 0.672597E+10 | 0.228279E+11 | 0.171522E+10 |
Minimum of Months | 0.518766E+09 | 1079877.92 | 0.511657E+09 | 0.140390E+10 | 352411.32 |
Maximum of Months | 0.148795E+10 | 0.967519E+09 | 0.609311E+09 | 0.241075E+10 | 0.446551E+09 |
Report: WindowEnergyReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.418997E+10 | 0.272447E+10 | 0.146550E+10 | 0.675656E+10 | 0.133968E+10 |
February | 0.334088E+10 | 0.190008E+10 | 0.144079E+10 | 0.571985E+10 | 0.961590E+09 |
March | 0.285853E+10 | 0.118184E+10 | 0.167669E+10 | 0.508332E+10 | 0.807559E+09 |
April | 0.198350E+10 | 0.406316E+09 | 0.157718E+10 | 0.406453E+10 | 0.370384E+09 |
May | 0.160030E+10 | 50799149.42 | 0.154950E+10 | 0.385386E+10 | 77208674.60 |
June | 0.146081E+10 | 3040865.03 | 0.145777E+10 | 0.389448E+10 | 10063266.45 |
July | 0.161521E+10 | 13562859.83 | 0.160164E+10 | 0.434896E+10 | 32617060.45 |
August | 0.181581E+10 | 0.135791E+09 | 0.168002E+10 | 0.467016E+10 | 6911631.55 |
September | 0.227874E+10 | 0.562957E+09 | 0.171578E+10 | 0.547023E+10 | 64293223.72 |
October | 0.326796E+10 | 0.155388E+10 | 0.171408E+10 | 0.664567E+10 | 0.146700E+09 |
November | 0.358271E+10 | 0.201074E+10 | 0.157198E+10 | 0.646028E+10 | 0.521859E+09 |
December | 0.403962E+10 | 0.255066E+10 | 0.148896E+10 | 0.665514E+10 | 0.111208E+10 |
Annual Sum or Average | 0.320340E+11 | 0.130941E+11 | 0.189399E+11 | 0.636230E+11 | 0.545095E+10 |
Minimum of Months | 0.146081E+10 | 3040865.03 | 0.144079E+10 | 0.385386E+10 | 6911631.55 |
Maximum of Months | 0.418997E+10 | 0.272447E+10 | 0.171578E+10 | 0.675656E+10 | 0.133968E+10 |
Report: WindowEnergyReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.544302E+10 | 0.353924E+10 | 0.190377E+10 | 0.905625E+10 | 0.170334E+10 |
February | 0.433999E+10 | 0.246832E+10 | 0.187167E+10 | 0.767614E+10 | 0.120946E+10 |
March | 0.371340E+10 | 0.153528E+10 | 0.217812E+10 | 0.682837E+10 | 0.101236E+10 |
April | 0.257668E+10 | 0.527828E+09 | 0.204885E+10 | 0.547866E+10 | 0.447140E+09 |
May | 0.207888E+10 | 65990986.10 | 0.201288E+10 | 0.522239E+10 | 88357129.81 |
June | 0.189768E+10 | 3950256.73 | 0.189373E+10 | 0.528916E+10 | 10287770.09 |
July | 0.209825E+10 | 17618926.79 | 0.208063E+10 | 0.589857E+10 | 36202971.73 |
August | 0.235884E+10 | 0.176400E+09 | 0.218244E+10 | 0.635362E+10 | 5163901.75 |
September | 0.296021E+10 | 0.731314E+09 | 0.222890E+10 | 0.743417E+10 | 63452857.53 |
October | 0.424526E+10 | 0.201858E+10 | 0.222668E+10 | 0.902096E+10 | 0.142985E+09 |
November | 0.465415E+10 | 0.261206E+10 | 0.204209E+10 | 0.872759E+10 | 0.638017E+09 |
December | 0.524769E+10 | 0.331345E+10 | 0.193424E+10 | 0.892929E+10 | 0.140142E+10 |
Annual Sum or Average | 0.416140E+11 | 0.170100E+11 | 0.246040E+11 | 0.859152E+11 | 0.675819E+10 |
Minimum of Months | 0.189768E+10 | 3950256.73 | 0.187167E+10 | 0.522239E+10 | 5163901.75 |
Maximum of Months | 0.544302E+10 | 0.353924E+10 | 0.222890E+10 | 0.905625E+10 | 0.170334E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.294194E+09 | 0.191295E+09 | 0.102899E+09 | 0.473240E+09 | 90331948.15 |
February | 0.234576E+09 | 0.133412E+09 | 0.101164E+09 | 0.397844E+09 | 63531545.29 |
March | 0.200709E+09 | 82981349.66 | 0.117728E+09 | 0.348447E+09 | 51235444.46 |
April | 0.139270E+09 | 28528948.73 | 0.110741E+09 | 0.276958E+09 | 21152943.78 |
May | 0.112364E+09 | 3566796.69 | 0.108797E+09 | 0.270377E+09 | 3458999.56 |
June | 0.102570E+09 | 213510.41 | 0.102357E+09 | 0.277296E+09 | 233247.64 |
July | 0.113411E+09 | 952298.69 | 0.112459E+09 | 0.307244E+09 | 1216116.21 |
August | 0.127496E+09 | 9534386.88 | 0.117961E+09 | 0.332259E+09 | 88558.66 |
September | 0.160000E+09 | 39527329.16 | 0.120472E+09 | 0.388847E+09 | 1759980.12 |
October | 0.229456E+09 | 0.109104E+09 | 0.120353E+09 | 0.471669E+09 | 5220867.51 |
November | 0.251556E+09 | 0.141181E+09 | 0.110375E+09 | 0.455696E+09 | 31548798.16 |
December | 0.283637E+09 | 0.179091E+09 | 0.104546E+09 | 0.465205E+09 | 73416414.06 |
Annual Sum or Average | 0.224924E+10 | 0.919388E+09 | 0.132985E+10 | 0.446508E+10 | 0.343195E+09 |
Minimum of Months | 0.102570E+09 | 213510.41 | 0.101164E+09 | 0.270377E+09 | 88558.66 |
Maximum of Months | 0.294194E+09 | 0.191295E+09 | 0.120472E+09 | 0.473240E+09 | 90331948.15 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.253088E+09 | 0.109438E+09 | 0.143650E+09 | 0.381933E+09 | 0.180310E+09 |
February | 0.286903E+09 | 0.130669E+09 | 0.156234E+09 | 0.472253E+09 | 0.126362E+09 |
March | 0.393465E+09 | 0.179864E+09 | 0.213602E+09 | 0.647263E+09 | 0.100336E+09 |
April | 0.417943E+09 | 0.193256E+09 | 0.224687E+09 | 0.756246E+09 | 39054260.14 |
May | 0.394988E+09 | 0.152497E+09 | 0.242491E+09 | 0.819569E+09 | 6444345.39 |
June | 0.323637E+09 | 90811701.15 | 0.232825E+09 | 0.752924E+09 | 451753.14 |
July | 0.373167E+09 | 0.115324E+09 | 0.257843E+09 | 0.861408E+09 | 2295073.37 |
August | 0.372297E+09 | 0.121012E+09 | 0.251286E+09 | 0.840235E+09 | 145825.19 |
September | 0.307449E+09 | 90604734.42 | 0.216844E+09 | 0.712762E+09 | 3441109.48 |
October | 0.316622E+09 | 0.123668E+09 | 0.192954E+09 | 0.660173E+09 | 9935247.20 |
November | 0.252061E+09 | 92323391.94 | 0.159737E+09 | 0.475454E+09 | 62918195.90 |
December | 0.261142E+09 | 0.116710E+09 | 0.144432E+09 | 0.417135E+09 | 0.142687E+09 |
Annual Sum or Average | 0.395276E+10 | 0.151618E+10 | 0.243658E+10 | 0.779735E+10 | 0.674381E+09 |
Minimum of Months | 0.252061E+09 | 90604734.42 | 0.143650E+09 | 0.381933E+09 | 145825.19 |
Maximum of Months | 0.417943E+09 | 0.193256E+09 | 0.257843E+09 | 0.861408E+09 | 0.180310E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62480615.07 | 0.00 | 62480615.07 | 83353513.14 | 94395632.35 |
February | 66798791.70 | 0.00 | 66798791.70 | 0.106943E+09 | 65821070.46 |
March | 88222215.26 | 1556.86 | 88220658.39 | 0.138951E+09 | 52999676.95 |
April | 95917903.38 | 547620.98 | 95370282.40 | 0.184026E+09 | 20336796.98 |
May | 0.112552E+09 | 4610857.06 | 0.107941E+09 | 0.269030E+09 | 3335095.82 |
June | 0.116746E+09 | 8396627.57 | 0.108349E+09 | 0.307562E+09 | 262878.22 |
July | 0.122202E+09 | 6082373.67 | 0.116120E+09 | 0.325706E+09 | 1256702.79 |
August | 0.108221E+09 | 1134477.74 | 0.107087E+09 | 0.290777E+09 | 93672.07 |
September | 92738767.59 | 21425.30 | 92717342.29 | 0.255917E+09 | 1775790.52 |
October | 80243081.80 | 0.00 | 80243081.80 | 0.200492E+09 | 4915136.08 |
November | 67521071.96 | 0.00 | 67521071.96 | 0.140105E+09 | 32378272.10 |
December | 61801109.67 | 0.00 | 61801109.67 | 92609106.78 | 74504895.29 |
Annual Sum or Average | 0.107544E+10 | 20794939.18 | 0.105465E+10 | 0.239547E+10 | 0.352076E+09 |
Minimum of Months | 61801109.67 | 0.00 | 61801109.67 | 83353513.14 | 93672.07 |
Maximum of Months | 0.122202E+09 | 8396627.57 | 0.116120E+09 | 0.325706E+09 | 94395632.35 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.253088E+09 | 0.109438E+09 | 0.143650E+09 | 0.395418E+09 | 0.173210E+09 |
February | 0.286903E+09 | 0.130669E+09 | 0.156234E+09 | 0.481927E+09 | 0.121833E+09 |
March | 0.393465E+09 | 0.179864E+09 | 0.213602E+09 | 0.654868E+09 | 97253999.05 |
April | 0.417943E+09 | 0.193256E+09 | 0.224687E+09 | 0.759258E+09 | 38069084.99 |
May | 0.394988E+09 | 0.152497E+09 | 0.242491E+09 | 0.819582E+09 | 6416686.18 |
June | 0.323637E+09 | 90811701.15 | 0.232825E+09 | 0.751798E+09 | 463963.68 |
July | 0.373167E+09 | 0.115324E+09 | 0.257843E+09 | 0.860729E+09 | 2315432.50 |
August | 0.372297E+09 | 0.121012E+09 | 0.251286E+09 | 0.841683E+09 | 138430.19 |
September | 0.307449E+09 | 90604734.42 | 0.216844E+09 | 0.717244E+09 | 3199768.86 |
October | 0.316622E+09 | 0.123668E+09 | 0.192954E+09 | 0.668822E+09 | 9018727.03 |
November | 0.252061E+09 | 92323391.94 | 0.159737E+09 | 0.485700E+09 | 60331170.85 |
December | 0.261142E+09 | 0.116710E+09 | 0.144432E+09 | 0.429329E+09 | 0.136564E+09 |
Annual Sum or Average | 0.395276E+10 | 0.151618E+10 | 0.243658E+10 | 0.786636E+10 | 0.648814E+09 |
Minimum of Months | 0.252061E+09 | 90604734.42 | 0.143650E+09 | 0.395418E+09 | 138430.19 |
Maximum of Months | 0.417943E+09 | 0.193256E+09 | 0.257843E+09 | 0.860729E+09 | 0.173210E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.235309E+09 | 0.153006E+09 | 82302997.65 | 0.364894E+09 | 97781420.27 |
February | 0.187624E+09 | 0.106708E+09 | 80915277.26 | 0.306094E+09 | 71368267.21 |
March | 0.160536E+09 | 66371880.15 | 94163689.54 | 0.266707E+09 | 61608765.86 |
April | 0.111394E+09 | 22818620.98 | 88575365.15 | 0.211829E+09 | 32649015.10 |
May | 89873280.16 | 2852869.99 | 87020410.17 | 0.197460E+09 | 8688711.61 |
June | 82039774.92 | 170774.37 | 81869000.56 | 0.200536E+09 | 2157193.81 |
July | 90710703.00 | 761687.47 | 89949015.53 | 0.227211E+09 | 4296855.71 |
August | 0.101976E+09 | 7625992.90 | 94350425.71 | 0.243551E+09 | 2124044.25 |
September | 0.127974E+09 | 31615575.84 | 96358645.11 | 0.293281E+09 | 7825112.03 |
October | 0.183529E+09 | 87265587.65 | 96262912.52 | 0.359144E+09 | 13718865.81 |
November | 0.201205E+09 | 0.112922E+09 | 88282536.13 | 0.347580E+09 | 40049532.75 |
December | 0.226865E+09 | 0.143244E+09 | 83620064.08 | 0.359650E+09 | 83522498.42 |
Annual Sum or Average | 0.179903E+10 | 0.735364E+09 | 0.106367E+10 | 0.337794E+10 | 0.425790E+09 |
Minimum of Months | 82039774.92 | 170774.37 | 80915277.26 | 0.197460E+09 | 2124044.25 |
Maximum of Months | 0.235309E+09 | 0.153006E+09 | 96358645.11 | 0.364894E+09 | 97781420.27 |
Report: WindowEnergyReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 49991117.79 | 0.00 | 49991117.79 | 70096559.15 | 75202368.82 |
February | 53446117.01 | 0.00 | 53446117.01 | 90902765.60 | 51314685.63 |
March | 70587127.69 | 1245.66 | 70585882.03 | 0.119161E+09 | 39921099.57 |
April | 76744494.28 | 438154.86 | 76306339.42 | 0.157946E+09 | 13385655.68 |
May | 90053455.50 | 3689174.61 | 86364280.90 | 0.228712E+09 | 2172375.97 |
June | 93409270.91 | 6718192.47 | 86691078.44 | 0.258974E+09 | 101216.01 |
July | 97774596.35 | 4866543.94 | 92908052.41 | 0.274848E+09 | 625017.25 |
August | 86588371.69 | 907702.50 | 85680669.19 | 0.247303E+09 | 23584.37 |
September | 74200848.51 | 17142.51 | 74183706.00 | 0.217517E+09 | 764947.25 |
October | 64202974.78 | 0.00 | 64202974.78 | 0.172662E+09 | 2845975.84 |
November | 54024017.81 | 0.00 | 54024017.81 | 0.120097E+09 | 24805621.58 |
December | 49447441.40 | 0.00 | 49447441.40 | 78507998.05 | 58962788.38 |
Annual Sum or Average | 0.860470E+09 | 16638156.53 | 0.843832E+09 | 0.203673E+10 | 0.270125E+09 |
Minimum of Months | 49447441.40 | 0.00 | 49447441.40 | 70096559.15 | 23584.37 |
Maximum of Months | 97774596.35 | 6718192.47 | 92908052.41 | 0.274848E+09 | 75202368.82 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.280909E+09 | 0.134618E+09 | 0.146291E+09 | 0.420244E+09 | 0.171597E+09 |
February | 0.294295E+09 | 0.136722E+09 | 0.157574E+09 | 0.473759E+09 | 0.116412E+09 |
March | 0.396895E+09 | 0.187649E+09 | 0.209246E+09 | 0.636690E+09 | 89169432.79 |
April | 0.417353E+09 | 0.186314E+09 | 0.231039E+09 | 0.755363E+09 | 36403903.04 |
May | 0.408027E+09 | 0.163129E+09 | 0.244897E+09 | 0.843787E+09 | 5913879.06 |
June | 0.388079E+09 | 0.148941E+09 | 0.239138E+09 | 0.864554E+09 | 487278.71 |
July | 0.412596E+09 | 0.148889E+09 | 0.263707E+09 | 0.932074E+09 | 2159813.83 |
August | 0.377126E+09 | 0.126265E+09 | 0.250860E+09 | 0.852187E+09 | 133297.54 |
September | 0.351604E+09 | 0.126961E+09 | 0.224643E+09 | 0.791399E+09 | 3275797.64 |
October | 0.334034E+09 | 0.143355E+09 | 0.190679E+09 | 0.693098E+09 | 9408143.66 |
November | 0.263220E+09 | 0.104823E+09 | 0.158397E+09 | 0.489726E+09 | 58079501.06 |
December | 0.219983E+09 | 77942147.70 | 0.142041E+09 | 0.343926E+09 | 0.137882E+09 |
Annual Sum or Average | 0.414412E+10 | 0.168561E+10 | 0.245851E+10 | 0.809681E+10 | 0.630921E+09 |
Minimum of Months | 0.219983E+09 | 77942147.70 | 0.142041E+09 | 0.343926E+09 | 133297.54 |
Maximum of Months | 0.417353E+09 | 0.187649E+09 | 0.263707E+09 | 0.932074E+09 | 0.171597E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.294194E+09 | 0.191295E+09 | 0.102899E+09 | 0.470645E+09 | 89905644.49 |
February | 0.234576E+09 | 0.133412E+09 | 0.101164E+09 | 0.395876E+09 | 62749023.58 |
March | 0.200709E+09 | 82981349.66 | 0.117728E+09 | 0.345788E+09 | 50106247.87 |
April | 0.139270E+09 | 28528948.73 | 0.110741E+09 | 0.275254E+09 | 20171580.07 |
May | 0.112364E+09 | 3566796.69 | 0.108797E+09 | 0.269599E+09 | 3339281.08 |
June | 0.102570E+09 | 213510.41 | 0.102357E+09 | 0.274957E+09 | 266580.95 |
July | 0.113411E+09 | 952298.69 | 0.112459E+09 | 0.305739E+09 | 1200703.83 |
August | 0.127496E+09 | 9534386.88 | 0.117961E+09 | 0.331864E+09 | 70233.10 |
September | 0.160000E+09 | 39527329.16 | 0.120472E+09 | 0.387201E+09 | 1790989.98 |
October | 0.229456E+09 | 0.109104E+09 | 0.120353E+09 | 0.470673E+09 | 5047820.50 |
November | 0.251556E+09 | 0.141181E+09 | 0.110375E+09 | 0.454503E+09 | 31174310.44 |
December | 0.283637E+09 | 0.179091E+09 | 0.104546E+09 | 0.465092E+09 | 72229486.53 |
Annual Sum or Average | 0.224924E+10 | 0.919388E+09 | 0.132985E+10 | 0.444719E+10 | 0.338052E+09 |
Minimum of Months | 0.102570E+09 | 213510.41 | 0.101164E+09 | 0.269599E+09 | 70233.10 |
Maximum of Months | 0.294194E+09 | 0.191295E+09 | 0.120472E+09 | 0.470673E+09 | 89905644.49 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62480615.07 | 0.00 | 62480615.07 | 80607098.80 | 94134476.34 |
February | 66798791.70 | 0.00 | 66798791.70 | 0.104708E+09 | 65337330.38 |
March | 88222215.26 | 1556.86 | 88220658.39 | 0.136402E+09 | 52410266.70 |
April | 95917903.38 | 547620.98 | 95370282.40 | 0.182187E+09 | 19396620.02 |
May | 0.112552E+09 | 4610857.06 | 0.107941E+09 | 0.268227E+09 | 3213432.32 |
June | 0.116746E+09 | 8396627.57 | 0.108349E+09 | 0.305249E+09 | 297890.60 |
July | 0.122202E+09 | 6082373.67 | 0.116120E+09 | 0.324203E+09 | 1241601.87 |
August | 0.108221E+09 | 1134477.74 | 0.107087E+09 | 0.290351E+09 | 74814.01 |
September | 92738767.59 | 21425.30 | 92717342.29 | 0.254107E+09 | 1809417.12 |
October | 80243081.80 | 0.00 | 80243081.80 | 0.199229E+09 | 4764910.06 |
November | 67521071.96 | 0.00 | 67521071.96 | 0.138690E+09 | 32072638.26 |
December | 61801109.67 | 0.00 | 61801109.67 | 92304065.71 | 73051565.52 |
Annual Sum or Average | 0.107544E+10 | 20794939.18 | 0.105465E+10 | 0.237626E+10 | 0.347805E+09 |
Minimum of Months | 61801109.67 | 0.00 | 61801109.67 | 80607098.80 | 74814.01 |
Maximum of Months | 0.122202E+09 | 8396627.57 | 0.116120E+09 | 0.324203E+09 | 94134476.34 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.280909E+09 | 0.134618E+09 | 0.146291E+09 | 0.432863E+09 | 0.164157E+09 |
February | 0.294295E+09 | 0.136722E+09 | 0.157574E+09 | 0.482772E+09 | 0.112007E+09 |
March | 0.396895E+09 | 0.187649E+09 | 0.209246E+09 | 0.643814E+09 | 86206410.02 |
April | 0.417353E+09 | 0.186314E+09 | 0.231039E+09 | 0.758218E+09 | 35453017.04 |
May | 0.408027E+09 | 0.163129E+09 | 0.244897E+09 | 0.843845E+09 | 5890151.35 |
June | 0.388079E+09 | 0.148941E+09 | 0.239138E+09 | 0.863529E+09 | 499276.96 |
July | 0.412596E+09 | 0.148889E+09 | 0.263707E+09 | 0.931450E+09 | 2179037.58 |
August | 0.377126E+09 | 0.126265E+09 | 0.250860E+09 | 0.853633E+09 | 126574.38 |
September | 0.351604E+09 | 0.126961E+09 | 0.224643E+09 | 0.795720E+09 | 3046783.46 |
October | 0.334034E+09 | 0.143355E+09 | 0.190679E+09 | 0.701463E+09 | 8561586.58 |
November | 0.263220E+09 | 0.104823E+09 | 0.158397E+09 | 0.499736E+09 | 55597790.62 |
December | 0.219983E+09 | 77942147.70 | 0.142041E+09 | 0.355994E+09 | 0.131001E+09 |
Annual Sum or Average | 0.414412E+10 | 0.168561E+10 | 0.245851E+10 | 0.816304E+10 | 0.604726E+09 |
Minimum of Months | 0.219983E+09 | 77942147.70 | 0.142041E+09 | 0.355994E+09 | 126574.38 |
Maximum of Months | 0.417353E+09 | 0.187649E+09 | 0.263707E+09 | 0.931450E+09 | 0.164157E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 79127756.68 | 0.00 | 79127756.68 | 0.114236E+09 | 0.120113E+09 |
February | 84596454.92 | 0.00 | 84596454.92 | 0.148636E+09 | 82135808.66 |
March | 0.111728E+09 | 1971.67 | 0.111726E+09 | 0.194832E+09 | 65034177.94 |
April | 0.121474E+09 | 693527.42 | 0.120780E+09 | 0.255189E+09 | 24872669.40 |
May | 0.142540E+09 | 5839359.54 | 0.136701E+09 | 0.362744E+09 | 4243454.09 |
June | 0.147852E+09 | 10633799.02 | 0.137218E+09 | 0.405180E+09 | 561955.84 |
July | 0.154761E+09 | 7702942.47 | 0.147058E+09 | 0.428459E+09 | 2031783.69 |
August | 0.137055E+09 | 1436744.47 | 0.135618E+09 | 0.383481E+09 | 206807.41 |
September | 0.117448E+09 | 27133.79 | 0.117421E+09 | 0.336208E+09 | 3511661.13 |
October | 0.101623E+09 | 0.00 | 0.101623E+09 | 0.265351E+09 | 8247096.82 |
November | 85511177.30 | 0.00 | 85511177.30 | 0.189122E+09 | 43159581.47 |
December | 78267205.96 | 0.00 | 78267205.96 | 0.127111E+09 | 95095569.61 |
Annual Sum or Average | 0.136198E+10 | 26335478.38 | 0.133565E+10 | 0.321055E+10 | 0.449213E+09 |
Minimum of Months | 78267205.96 | 0.00 | 78267205.96 | 0.114236E+09 | 206807.41 |
Maximum of Months | 0.154761E+09 | 10633799.02 | 0.147058E+09 | 0.428459E+09 | 0.120113E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 29169767.54 | 0.00 | 29169767.54 | 42112190.11 | 44278503.40 |
February | 31185756.15 | 0.00 | 31185756.15 | 54793321.74 | 30278660.05 |
March | 41187518.84 | 726.84 | 41186792.00 | 71823038.55 | 23974290.84 |
April | 44780336.12 | 255662.92 | 44524673.20 | 94073240.15 | 9169095.84 |
May | 52546101.77 | 2152629.72 | 50393472.05 | 0.133722E+09 | 1564312.89 |
June | 54504216.72 | 3920058.63 | 50584158.09 | 0.149366E+09 | 207160.19 |
July | 57051379.78 | 2839623.55 | 54211756.23 | 0.157948E+09 | 748999.60 |
August | 50524228.81 | 529643.50 | 49994585.30 | 0.141367E+09 | 76237.78 |
September | 43296121.35 | 10002.64 | 43286118.71 | 0.123940E+09 | 1294543.70 |
October | 37462371.96 | 0.00 | 37462371.96 | 97819367.83 | 3040488.84 |
November | 31522960.69 | 0.00 | 31522960.69 | 69718213.95 | 15910408.83 |
December | 28852532.91 | 0.00 | 28852532.91 | 46858204.40 | 35056164.55 |
Annual Sum or Average | 0.502083E+09 | 9708347.80 | 0.492375E+09 | 0.118354E+10 | 0.165599E+09 |
Minimum of Months | 28852532.91 | 0.00 | 28852532.91 | 42112190.11 | 76237.78 |
Maximum of Months | 57051379.78 | 3920058.63 | 54211756.23 | 0.157948E+09 | 44278503.40 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.137270E+09 | 89257568.62 | 48012355.27 | 0.227758E+09 | 40865379.26 |
February | 0.109452E+09 | 62249486.00 | 47202813.38 | 0.192829E+09 | 28193786.10 |
March | 93650183.18 | 38718763.36 | 54931419.82 | 0.171335E+09 | 22511829.19 |
April | 64982902.08 | 13311492.51 | 51671409.57 | 0.137991E+09 | 9296487.82 |
May | 52428562.51 | 1664252.96 | 50764309.54 | 0.134417E+09 | 1619139.26 |
June | 47858801.41 | 99623.10 | 47759178.32 | 0.134950E+09 | 194114.29 |
July | 52917082.30 | 444338.73 | 52472743.56 | 0.149142E+09 | 734759.78 |
August | 59489060.90 | 4448706.50 | 55040354.41 | 0.160998E+09 | 68371.56 |
September | 74655163.70 | 18443292.50 | 56211871.19 | 0.186784E+09 | 1228912.51 |
October | 0.107063E+09 | 50907336.51 | 56156024.54 | 0.226116E+09 | 2962841.48 |
November | 0.117375E+09 | 65874561.67 | 51500584.55 | 0.219341E+09 | 14870094.92 |
December | 0.132344E+09 | 83563227.84 | 48780680.41 | 0.224075E+09 | 33233200.75 |
Annual Sum or Average | 0.104949E+10 | 0.428983E+09 | 0.620504E+09 | 0.216574E+10 | 0.155779E+09 |
Minimum of Months | 47858801.41 | 99623.10 | 47202813.38 | 0.134417E+09 | 68371.56 |
Maximum of Months | 0.137270E+09 | 89257568.62 | 56211871.19 | 0.227758E+09 | 40865379.26 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.372579E+09 | 0.242263E+09 | 0.130315E+09 | 0.618183E+09 | 0.110917E+09 |
February | 0.297076E+09 | 0.168958E+09 | 0.128118E+09 | 0.523378E+09 | 76523702.38 |
March | 0.254186E+09 | 0.105091E+09 | 0.149095E+09 | 0.465039E+09 | 61101709.10 |
April | 0.176377E+09 | 36130113.49 | 0.140247E+09 | 0.374535E+09 | 25232569.50 |
May | 0.142302E+09 | 4517122.96 | 0.137785E+09 | 0.364835E+09 | 4394675.14 |
June | 0.129899E+09 | 270397.47 | 0.129628E+09 | 0.366283E+09 | 526865.90 |
July | 0.143628E+09 | 1206026.21 | 0.142422E+09 | 0.404801E+09 | 1994288.33 |
August | 0.161465E+09 | 12074699.40 | 0.149391E+09 | 0.436981E+09 | 185574.39 |
September | 0.202629E+09 | 50058868.35 | 0.152571E+09 | 0.506970E+09 | 3335519.92 |
October | 0.290592E+09 | 0.138173E+09 | 0.152419E+09 | 0.613724E+09 | 8041757.82 |
November | 0.318580E+09 | 0.178797E+09 | 0.139783E+09 | 0.595337E+09 | 40360479.21 |
December | 0.359208E+09 | 0.226808E+09 | 0.132401E+09 | 0.608184E+09 | 90201704.54 |
Annual Sum or Average | 0.284852E+10 | 0.116435E+10 | 0.168417E+10 | 0.587825E+10 | 0.422816E+09 |
Minimum of Months | 0.129899E+09 | 270397.47 | 0.128118E+09 | 0.364835E+09 | 185574.39 |
Maximum of Months | 0.372579E+09 | 0.242263E+09 | 0.152571E+09 | 0.618183E+09 | 0.110917E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.294194E+09 | 0.191295E+09 | 0.102899E+09 | 0.467663E+09 | 89846749.14 |
February | 0.234576E+09 | 0.133412E+09 | 0.101164E+09 | 0.392179E+09 | 63327843.94 |
March | 0.200709E+09 | 82981349.66 | 0.117728E+09 | 0.342150E+09 | 50972816.35 |
April | 0.139270E+09 | 28528948.73 | 0.110741E+09 | 0.271406E+09 | 21058087.15 |
May | 0.112364E+09 | 3566796.69 | 0.108797E+09 | 0.266005E+09 | 3333997.90 |
June | 0.102570E+09 | 213510.41 | 0.102357E+09 | 0.273311E+09 | 214550.75 |
July | 0.113411E+09 | 952298.69 | 0.112459E+09 | 0.302772E+09 | 1159100.62 |
August | 0.127496E+09 | 9534386.88 | 0.117961E+09 | 0.327865E+09 | 112104.45 |
September | 0.160000E+09 | 39527329.16 | 0.120472E+09 | 0.383895E+09 | 1657652.23 |
October | 0.229456E+09 | 0.109104E+09 | 0.120353E+09 | 0.466380E+09 | 4969377.62 |
November | 0.251556E+09 | 0.141181E+09 | 0.110375E+09 | 0.450218E+09 | 31055822.78 |
December | 0.283637E+09 | 0.179091E+09 | 0.104546E+09 | 0.459343E+09 | 73115363.13 |
Annual Sum or Average | 0.224924E+10 | 0.919388E+09 | 0.132985E+10 | 0.440319E+10 | 0.340823E+09 |
Minimum of Months | 0.102570E+09 | 213510.41 | 0.101164E+09 | 0.266005E+09 | 112104.45 |
Maximum of Months | 0.294194E+09 | 0.191295E+09 | 0.120472E+09 | 0.467663E+09 | 89846749.14 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.253088E+09 | 0.109438E+09 | 0.143650E+09 | 0.374898E+09 | 0.179261E+09 |
February | 0.286903E+09 | 0.130669E+09 | 0.156234E+09 | 0.464376E+09 | 0.125987E+09 |
March | 0.393465E+09 | 0.179864E+09 | 0.213602E+09 | 0.636102E+09 | 0.100112E+09 |
April | 0.417943E+09 | 0.193256E+09 | 0.224687E+09 | 0.744440E+09 | 38953862.22 |
May | 0.394988E+09 | 0.152497E+09 | 0.242491E+09 | 0.807866E+09 | 6203636.65 |
June | 0.323637E+09 | 90811701.15 | 0.232825E+09 | 0.742643E+09 | 403730.02 |
July | 0.373167E+09 | 0.115324E+09 | 0.257843E+09 | 0.850369E+09 | 2162046.95 |
August | 0.372297E+09 | 0.121012E+09 | 0.251286E+09 | 0.829637E+09 | 171958.09 |
September | 0.307449E+09 | 90604734.42 | 0.216844E+09 | 0.703615E+09 | 3165429.18 |
October | 0.316622E+09 | 0.123668E+09 | 0.192954E+09 | 0.652284E+09 | 9341823.79 |
November | 0.252061E+09 | 92323391.94 | 0.159737E+09 | 0.468173E+09 | 61882950.56 |
December | 0.261142E+09 | 0.116710E+09 | 0.144432E+09 | 0.409629E+09 | 0.142252E+09 |
Annual Sum or Average | 0.395276E+10 | 0.151618E+10 | 0.243658E+10 | 0.768403E+10 | 0.669897E+09 |
Minimum of Months | 0.252061E+09 | 90604734.42 | 0.143650E+09 | 0.374898E+09 | 171958.09 |
Maximum of Months | 0.417943E+09 | 0.193256E+09 | 0.257843E+09 | 0.850369E+09 | 0.179261E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62480615.07 | 0.00 | 62480615.07 | 81198848.78 | 93674146.48 |
February | 66798791.70 | 0.00 | 66798791.70 | 0.104347E+09 | 65515194.11 |
March | 88222215.26 | 1556.86 | 88220658.39 | 0.135136E+09 | 52775461.88 |
April | 95917903.38 | 547620.98 | 95370282.40 | 0.179582E+09 | 20206553.55 |
May | 0.112552E+09 | 4610857.06 | 0.107941E+09 | 0.264275E+09 | 3232495.95 |
June | 0.116746E+09 | 8396627.57 | 0.108349E+09 | 0.302982E+09 | 238421.65 |
July | 0.122202E+09 | 6082373.67 | 0.116120E+09 | 0.321000E+09 | 1190564.95 |
August | 0.108221E+09 | 1134477.74 | 0.107087E+09 | 0.286627E+09 | 111134.51 |
September | 92738767.59 | 21425.30 | 92717342.29 | 0.252443E+09 | 1630732.51 |
October | 80243081.80 | 0.00 | 80243081.80 | 0.197955E+09 | 4582105.24 |
November | 67521071.96 | 0.00 | 67521071.96 | 0.137669E+09 | 31747538.82 |
December | 61801109.67 | 0.00 | 61801109.67 | 90300527.86 | 74044717.66 |
Annual Sum or Average | 0.107544E+10 | 20794939.18 | 0.105465E+10 | 0.235352E+10 | 0.348949E+09 |
Minimum of Months | 61801109.67 | 0.00 | 61801109.67 | 81198848.78 | 111134.51 |
Maximum of Months | 0.122202E+09 | 8396627.57 | 0.116120E+09 | 0.321000E+09 | 93674146.48 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.253088E+09 | 0.109438E+09 | 0.143650E+09 | 0.388812E+09 | 0.171614E+09 |
February | 0.286903E+09 | 0.130669E+09 | 0.156234E+09 | 0.474204E+09 | 0.121271E+09 |
March | 0.393465E+09 | 0.179864E+09 | 0.213602E+09 | 0.643737E+09 | 96924184.15 |
April | 0.417943E+09 | 0.193256E+09 | 0.224687E+09 | 0.747374E+09 | 37976462.59 |
May | 0.394988E+09 | 0.152497E+09 | 0.242491E+09 | 0.807844E+09 | 6179184.79 |
June | 0.323637E+09 | 90811701.15 | 0.232825E+09 | 0.741520E+09 | 415184.65 |
July | 0.373167E+09 | 0.115324E+09 | 0.257843E+09 | 0.849679E+09 | 2183602.33 |
August | 0.372297E+09 | 0.121012E+09 | 0.251286E+09 | 0.831051E+09 | 163503.78 |
September | 0.307449E+09 | 90604734.42 | 0.216844E+09 | 0.708104E+09 | 2929320.01 |
October | 0.316622E+09 | 0.123668E+09 | 0.192954E+09 | 0.661067E+09 | 8434240.86 |
November | 0.252061E+09 | 92323391.94 | 0.159737E+09 | 0.478647E+09 | 59175041.66 |
December | 0.261142E+09 | 0.116710E+09 | 0.144432E+09 | 0.422335E+09 | 0.135556E+09 |
Annual Sum or Average | 0.395276E+10 | 0.151618E+10 | 0.243658E+10 | 0.775437E+10 | 0.642822E+09 |
Minimum of Months | 0.252061E+09 | 90604734.42 | 0.143650E+09 | 0.388812E+09 | 163503.78 |
Maximum of Months | 0.417943E+09 | 0.193256E+09 | 0.257843E+09 | 0.849679E+09 | 0.171614E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.431464E+09 | 0.280553E+09 | 0.150912E+09 | 0.677617E+09 | 0.136810E+09 |
February | 0.344028E+09 | 0.195661E+09 | 0.148367E+09 | 0.571508E+09 | 94577921.33 |
March | 0.294360E+09 | 0.121700E+09 | 0.172659E+09 | 0.503411E+09 | 73187636.59 |
April | 0.204253E+09 | 41840441.24 | 0.162413E+09 | 0.407427E+09 | 27170169.58 |
May | 0.164793E+09 | 5231049.65 | 0.159561E+09 | 0.406323E+09 | 4198012.81 |
June | 0.150429E+09 | 313133.51 | 0.150116E+09 | 0.415983E+09 | 202273.58 |
July | 0.166328E+09 | 1396637.42 | 0.164931E+09 | 0.460971E+09 | 1268640.48 |
August | 0.186985E+09 | 13983093.38 | 0.173002E+09 | 0.496103E+09 | 60393.46 |
September | 0.234655E+09 | 57970621.67 | 0.176684E+09 | 0.572119E+09 | 1862908.71 |
October | 0.336520E+09 | 0.160011E+09 | 0.176509E+09 | 0.687831E+09 | 6766448.79 |
November | 0.368931E+09 | 0.207056E+09 | 0.161876E+09 | 0.657776E+09 | 46576805.56 |
December | 0.415981E+09 | 0.262654E+09 | 0.153327E+09 | 0.667492E+09 | 0.111524E+09 |
Annual Sum or Average | 0.329873E+10 | 0.134837E+10 | 0.195036E+10 | 0.652456E+10 | 0.504205E+09 |
Minimum of Months | 0.150429E+09 | 313133.51 | 0.148367E+09 | 0.406323E+09 | 60393.46 |
Maximum of Months | 0.431464E+09 | 0.280553E+09 | 0.176684E+09 | 0.687831E+09 | 0.136810E+09 |
Report: WindowEnergyReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.437348E+09 | 0.00 | 0.437348E+09 | 0.598611E+09 | 0.736856E+09 |
February | 0.467574E+09 | 0.00 | 0.467574E+09 | 0.779193E+09 | 0.528952E+09 |
March | 0.617532E+09 | 10897.63 | 0.617521E+09 | 0.102416E+10 | 0.445633E+09 |
April | 0.671400E+09 | 3833201.69 | 0.667567E+09 | 0.136484E+10 | 0.196658E+09 |
May | 0.787833E+09 | 32274777.04 | 0.755559E+09 | 0.192233E+10 | 43008478.21 |
June | 0.817192E+09 | 58774166.93 | 0.758418E+09 | 0.216805E+10 | 7482274.71 |
July | 0.855382E+09 | 42575003.16 | 0.812807E+09 | 0.232045E+10 | 20120539.56 |
August | 0.757519E+09 | 7941043.40 | 0.749578E+09 | 0.206294E+10 | 6743098.86 |
September | 0.649147E+09 | 149971.41 | 0.648997E+09 | 0.184015E+10 | 34600113.66 |
October | 0.561680E+09 | 0.00 | 0.561680E+09 | 0.146381E+10 | 64657980.60 |
November | 0.472630E+09 | 0.00 | 0.472630E+09 | 0.102167E+10 | 0.278102E+09 |
December | 0.432591E+09 | 0.00 | 0.432591E+09 | 0.670504E+09 | 0.600315E+09 |
Annual Sum or Average | 0.752783E+10 | 0.145559E+09 | 0.738227E+10 | 0.172367E+11 | 0.296313E+10 |
Minimum of Months | 0.432591E+09 | 0.00 | 0.432591E+09 | 0.598611E+09 | 6743098.86 |
Maximum of Months | 0.855382E+09 | 58774166.93 | 0.812807E+09 | 0.232045E+10 | 0.736856E+09 |
Report: WindowEnergyReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.437348E+09 | 0.00 | 0.437348E+09 | 0.577903E+09 | 0.774388E+09 |
February | 0.467574E+09 | 0.00 | 0.467574E+09 | 0.755748E+09 | 0.561450E+09 |
March | 0.617532E+09 | 10897.63 | 0.617521E+09 | 0.993551E+09 | 0.478621E+09 |
April | 0.671400E+09 | 3833201.69 | 0.667567E+09 | 0.132984E+10 | 0.222497E+09 |
May | 0.787833E+09 | 32274777.04 | 0.755559E+09 | 0.187185E+10 | 53467106.42 |
June | 0.817192E+09 | 58774166.93 | 0.758418E+09 | 0.211660E+10 | 10428410.16 |
July | 0.855382E+09 | 42575003.16 | 0.812807E+09 | 0.227297E+10 | 24895277.58 |
August | 0.757519E+09 | 7941043.40 | 0.749578E+09 | 0.201041E+10 | 9976421.44 |
September | 0.649147E+09 | 149971.41 | 0.648997E+09 | 0.179782E+10 | 43715557.27 |
October | 0.561680E+09 | 0.00 | 0.561680E+09 | 0.142021E+10 | 77175912.54 |
November | 0.472630E+09 | 0.00 | 0.472630E+09 | 0.985321E+09 | 0.299191E+09 |
December | 0.432591E+09 | 0.00 | 0.432591E+09 | 0.647096E+09 | 0.635738E+09 |
Annual Sum or Average | 0.752783E+10 | 0.145559E+09 | 0.738227E+10 | 0.167793E+11 | 0.319154E+10 |
Minimum of Months | 0.432591E+09 | 0.00 | 0.432591E+09 | 0.577903E+09 | 9976421.44 |
Maximum of Months | 0.855382E+09 | 58774166.93 | 0.812807E+09 | 0.227297E+10 | 0.774388E+09 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62480615.07 | 0.00 | 62480615.07 | 83734277.71 | 0.119950E+09 |
February | 66798791.70 | 0.00 | 66798791.70 | 0.105254E+09 | 90848039.60 |
March | 88222215.26 | 1556.86 | 88220658.39 | 0.139229E+09 | 78779164.76 |
April | 95917903.38 | 547620.98 | 95370282.40 | 0.190479E+09 | 38772206.80 |
May | 0.112552E+09 | 4610857.06 | 0.107941E+09 | 0.271216E+09 | 11992946.81 |
June | 0.116746E+09 | 8396627.57 | 0.108349E+09 | 0.309213E+09 | 2809668.57 |
July | 0.122202E+09 | 6082373.67 | 0.116120E+09 | 0.337487E+09 | 5349463.54 |
August | 0.108221E+09 | 1134477.74 | 0.107087E+09 | 0.290211E+09 | 3301889.66 |
September | 92738767.59 | 21425.30 | 92717342.29 | 0.262549E+09 | 7730764.71 |
October | 80243081.80 | 0.00 | 80243081.80 | 0.203415E+09 | 14736914.35 |
November | 67521071.96 | 0.00 | 67521071.96 | 0.141128E+09 | 48589819.13 |
December | 61801109.67 | 0.00 | 61801109.67 | 94946716.17 | 98530075.19 |
Annual Sum or Average | 0.107544E+10 | 20794939.18 | 0.105465E+10 | 0.242886E+10 | 0.521391E+09 |
Minimum of Months | 61801109.67 | 0.00 | 61801109.67 | 83734277.71 | 2809668.57 |
Maximum of Months | 0.122202E+09 | 8396627.57 | 0.116120E+09 | 0.337487E+09 | 0.119950E+09 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.561778E+09 | 0.269218E+09 | 0.292561E+09 | 0.879643E+09 | 0.424799E+09 |
February | 0.588549E+09 | 0.273424E+09 | 0.315125E+09 | 0.964245E+09 | 0.320325E+09 |
March | 0.793733E+09 | 0.375272E+09 | 0.418462E+09 | 0.129198E+10 | 0.273274E+09 |
April | 0.834647E+09 | 0.372602E+09 | 0.462045E+09 | 0.153839E+10 | 0.146928E+09 |
May | 0.815995E+09 | 0.326235E+09 | 0.489760E+09 | 0.167765E+10 | 45874105.12 |
June | 0.776103E+09 | 0.297862E+09 | 0.478241E+09 | 0.172904E+10 | 10683107.81 |
July | 0.825133E+09 | 0.297756E+09 | 0.527377E+09 | 0.190201E+10 | 20202761.70 |
August | 0.754198E+09 | 0.252513E+09 | 0.501685E+09 | 0.169212E+10 | 12824142.80 |
September | 0.703159E+09 | 0.253905E+09 | 0.449254E+09 | 0.161446E+10 | 29224799.44 |
October | 0.668020E+09 | 0.286690E+09 | 0.381330E+09 | 0.141138E+10 | 55776317.22 |
November | 0.526403E+09 | 0.209630E+09 | 0.316772E+09 | 0.100572E+10 | 0.172880E+09 |
December | 0.439935E+09 | 0.155873E+09 | 0.284062E+09 | 0.719547E+09 | 0.356200E+09 |
Annual Sum or Average | 0.828765E+10 | 0.337098E+10 | 0.491667E+10 | 0.164262E+11 | 0.186899E+10 |
Minimum of Months | 0.439935E+09 | 0.155873E+09 | 0.284062E+09 | 0.719547E+09 | 10683107.81 |
Maximum of Months | 0.834647E+09 | 0.375272E+09 | 0.527377E+09 | 0.190201E+10 | 0.424799E+09 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.294194E+09 | 0.191295E+09 | 0.102899E+09 | 0.483018E+09 | 0.111508E+09 |
February | 0.234576E+09 | 0.133412E+09 | 0.101164E+09 | 0.403030E+09 | 84539627.26 |
March | 0.200709E+09 | 82981349.66 | 0.117728E+09 | 0.352826E+09 | 74369347.38 |
April | 0.139270E+09 | 28528948.73 | 0.110741E+09 | 0.285297E+09 | 38708877.56 |
May | 0.112364E+09 | 3566796.69 | 0.108797E+09 | 0.268860E+09 | 12081111.35 |
June | 0.102570E+09 | 213510.41 | 0.102357E+09 | 0.277646E+09 | 2735309.54 |
July | 0.113411E+09 | 952298.69 | 0.112459E+09 | 0.317470E+09 | 5364678.93 |
August | 0.127496E+09 | 9534386.88 | 0.117961E+09 | 0.330546E+09 | 3374885.04 |
September | 0.160000E+09 | 39527329.16 | 0.120472E+09 | 0.398024E+09 | 7709820.18 |
October | 0.229456E+09 | 0.109104E+09 | 0.120353E+09 | 0.479523E+09 | 14583623.27 |
November | 0.251556E+09 | 0.141181E+09 | 0.110375E+09 | 0.464303E+09 | 45804815.50 |
December | 0.283637E+09 | 0.179091E+09 | 0.104546E+09 | 0.476251E+09 | 93144546.53 |
Annual Sum or Average | 0.224924E+10 | 0.919388E+09 | 0.132985E+10 | 0.453680E+10 | 0.493925E+09 |
Minimum of Months | 0.102570E+09 | 213510.41 | 0.101164E+09 | 0.268860E+09 | 2735309.54 |
Maximum of Months | 0.294194E+09 | 0.191295E+09 | 0.120472E+09 | 0.483018E+09 | 0.111508E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 79127756.68 | 0.00 | 79127756.68 | 0.111673E+09 | 0.117954E+09 |
February | 84596454.92 | 0.00 | 84596454.92 | 0.146895E+09 | 79796420.18 |
March | 0.111728E+09 | 1971.67 | 0.111726E+09 | 0.193629E+09 | 62198641.12 |
April | 0.121474E+09 | 693527.42 | 0.120780E+09 | 0.256633E+09 | 20839760.97 |
May | 0.142540E+09 | 5839359.54 | 0.136701E+09 | 0.366103E+09 | 3395711.01 |
June | 0.147852E+09 | 10633799.02 | 0.137218E+09 | 0.406910E+09 | 268446.77 |
July | 0.154761E+09 | 7702942.47 | 0.147058E+09 | 0.428248E+09 | 1453579.20 |
August | 0.137055E+09 | 1436744.47 | 0.135618E+09 | 0.387741E+09 | 66782.43 |
September | 0.117448E+09 | 27133.79 | 0.117421E+09 | 0.339334E+09 | 1765396.74 |
October | 0.101623E+09 | 0.00 | 0.101623E+09 | 0.273432E+09 | 5287198.26 |
November | 85511177.30 | 0.00 | 85511177.30 | 0.192886E+09 | 38801243.24 |
December | 78267205.96 | 0.00 | 78267205.96 | 0.125372E+09 | 93053408.61 |
Annual Sum or Average | 0.136198E+10 | 26335478.38 | 0.133565E+10 | 0.322886E+10 | 0.424880E+09 |
Minimum of Months | 78267205.96 | 0.00 | 78267205.96 | 0.111673E+09 | 66782.43 |
Maximum of Months | 0.154761E+09 | 10633799.02 | 0.147058E+09 | 0.428248E+09 | 0.117954E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 70795903.72 | 0.00 | 70795903.72 | 99914646.26 | 0.105531E+09 |
February | 75688768.75 | 0.00 | 75688768.75 | 0.131428E+09 | 71394159.48 |
March | 99963347.83 | 1764.06 | 99961583.77 | 0.173241E+09 | 55649359.88 |
April | 0.108683E+09 | 620501.61 | 0.108063E+09 | 0.229611E+09 | 18645413.10 |
May | 0.127531E+09 | 5224497.11 | 0.122306E+09 | 0.327554E+09 | 3038155.51 |
June | 0.132283E+09 | 9514100.27 | 0.122769E+09 | 0.364064E+09 | 240180.34 |
July | 0.138465E+09 | 6891851.82 | 0.131574E+09 | 0.383155E+09 | 1300522.82 |
August | 0.122624E+09 | 1285460.72 | 0.121338E+09 | 0.346913E+09 | 59750.49 |
September | 0.105081E+09 | 24276.70 | 0.105057E+09 | 0.303603E+09 | 1579507.15 |
October | 90922304.24 | 0.00 | 90922304.24 | 0.244640E+09 | 4730971.31 |
November | 76507174.33 | 0.00 | 76507174.33 | 0.172576E+09 | 34715535.73 |
December | 70025965.73 | 0.00 | 70025965.73 | 0.112172E+09 | 83255124.46 |
Annual Sum or Average | 0.121857E+10 | 23562452.29 | 0.119501E+10 | 0.288887E+10 | 0.380140E+09 |
Minimum of Months | 70025965.73 | 0.00 | 70025965.73 | 99914646.26 | 59750.49 |
Maximum of Months | 0.138465E+09 | 9514100.27 | 0.131574E+09 | 0.383155E+09 | 0.105531E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.109832E+10 | 0.714162E+09 | 0.384153E+09 | 0.180299E+10 | 0.320746E+09 |
February | 0.875743E+09 | 0.498067E+09 | 0.377676E+09 | 0.152661E+10 | 0.219212E+09 |
March | 0.749308E+09 | 0.309794E+09 | 0.439514E+09 | 0.135843E+10 | 0.172241E+09 |
April | 0.519937E+09 | 0.106507E+09 | 0.413430E+09 | 0.110326E+10 | 62921583.03 |
May | 0.419488E+09 | 13315914.90 | 0.406172E+09 | 0.108604E+10 | 10337914.29 |
June | 0.382925E+09 | 797097.99 | 0.382128E+09 | 0.108604E+10 | 749488.71 |
July | 0.423397E+09 | 3555214.79 | 0.419842E+09 | 0.119272E+10 | 4289111.12 |
August | 0.475980E+09 | 35594707.33 | 0.440385E+09 | 0.129928E+10 | 188499.47 |
September | 0.597326E+09 | 0.147567E+09 | 0.449759E+09 | 0.149801E+10 | 5087839.93 |
October | 0.856629E+09 | 0.407317E+09 | 0.449312E+09 | 0.182332E+10 | 15622817.92 |
November | 0.939135E+09 | 0.527071E+09 | 0.412063E+09 | 0.175614E+10 | 0.107503E+09 |
December | 0.105890E+10 | 0.668601E+09 | 0.390301E+09 | 0.177607E+10 | 0.260021E+09 |
Annual Sum or Average | 0.839708E+10 | 0.343235E+10 | 0.496474E+10 | 0.173089E+11 | 0.117892E+10 |
Minimum of Months | 0.382925E+09 | 797097.99 | 0.377676E+09 | 0.108604E+10 | 188499.47 |
Maximum of Months | 0.109832E+10 | 0.714162E+09 | 0.449759E+09 | 0.182332E+10 | 0.320746E+09 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 900.07 | 166.72 | 555.54 | 361.23 | 194.31 | 0.00 | 0.00 |
February | 844.33 | 130.15 | 490.42 | 278.92 | 211.50 | 0.00 | 0.00 |
March | 679.10 | 95.01 | 379.01 | 156.70 | 222.31 | 0.00 | 0.00 |
April | 561.84 | 40.43 | 271.75 | 55.67 | 216.09 | 0.00 | 0.00 |
May | 524.16 | 6.56 | 212.18 | 6.74 | 205.44 | 0.00 | 0.00 |
June | 548.84 | 0.36 | 200.14 | 0.42 | 199.72 | 0.00 | 0.00 |
July | 585.41 | 2.30 | 214.16 | 1.80 | 212.36 | 0.00 | 0.00 |
August | 632.33 | 0.13 | 240.75 | 18.00 | 222.75 | 0.00 | 0.00 |
September | 754.22 | 3.77 | 312.20 | 77.13 | 235.07 | 0.00 | 0.00 |
October | 886.28 | 12.12 | 433.29 | 206.02 | 227.26 | 0.00 | 0.00 |
November | 891.20 | 62.50 | 490.86 | 275.48 | 215.37 | 0.00 | 0.00 |
December | 885.80 | 136.38 | 535.60 | 338.19 | 197.42 | 0.00 | 0.00 |
Annual Sum or Average | 723.87 | 54.39 | 360.73 | 147.45 | 213.28 | 0.00 | 0.00 |
Minimum of Months | 524.16 | 0.13 | 200.14 | 0.42 | 194.31 | 0.00 | 0.00 |
Maximum of Months | 900.07 | 166.72 | 555.54 | 361.23 | 235.07 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2522.61 | 500.18 | 1564.36 | 1017.20 | 547.16 | 0.00 | 0.00 |
February | 2364.35 | 397.48 | 1380.98 | 785.42 | 595.57 | 0.00 | 0.00 |
March | 1897.89 | 301.51 | 1067.25 | 441.25 | 626.01 | 0.00 | 0.00 |
April | 1568.11 | 142.90 | 765.24 | 156.76 | 608.48 | 0.00 | 0.00 |
May | 1438.87 | 28.83 | 597.48 | 18.97 | 578.52 | 0.00 | 0.00 |
June | 1502.50 | 3.88 | 563.58 | 1.17 | 562.41 | 0.00 | 0.00 |
July | 1623.72 | 12.18 | 603.05 | 5.06 | 597.99 | 0.00 | 0.00 |
August | 1743.64 | 2.58 | 677.95 | 50.70 | 627.25 | 0.00 | 0.00 |
September | 2110.43 | 24.80 | 879.14 | 217.19 | 661.95 | 0.00 | 0.00 |
October | 2481.21 | 54.77 | 1220.12 | 580.15 | 639.96 | 0.00 | 0.00 |
November | 2492.39 | 201.33 | 1382.22 | 775.75 | 606.47 | 0.00 | 0.00 |
December | 2484.75 | 415.20 | 1508.22 | 952.31 | 555.91 | 0.00 | 0.00 |
Annual Sum or Average | 2017.47 | 172.85 | 1015.79 | 415.21 | 600.58 | 0.00 | 0.00 |
Minimum of Months | 1438.87 | 2.58 | 563.58 | 1.17 | 547.16 | 0.00 | 0.00 |
Maximum of Months | 2522.61 | 500.18 | 1564.36 | 1017.20 | 661.95 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3381.22 | 635.96 | 2032.19 | 1321.40 | 710.79 | 0.00 | 0.00 |
February | 3173.01 | 499.94 | 1793.98 | 1020.30 | 773.67 | 0.00 | 0.00 |
March | 2549.42 | 377.97 | 1386.42 | 573.21 | 813.22 | 0.00 | 0.00 |
April | 2113.68 | 172.51 | 994.09 | 203.64 | 790.45 | 0.00 | 0.00 |
May | 1949.82 | 32.99 | 776.16 | 24.64 | 751.52 | 0.00 | 0.00 |
June | 2040.57 | 3.97 | 732.13 | 1.52 | 730.60 | 0.00 | 0.00 |
July | 2202.27 | 13.52 | 783.39 | 6.58 | 776.82 | 0.00 | 0.00 |
August | 2372.17 | 1.93 | 880.69 | 65.86 | 814.83 | 0.00 | 0.00 |
September | 2868.12 | 24.48 | 1142.06 | 282.14 | 859.91 | 0.00 | 0.00 |
October | 3368.04 | 53.38 | 1585.00 | 753.65 | 831.35 | 0.00 | 0.00 |
November | 3367.13 | 246.15 | 1795.58 | 1007.74 | 787.84 | 0.00 | 0.00 |
December | 3333.82 | 523.23 | 1959.26 | 1237.10 | 722.16 | 0.00 | 0.00 |
Annual Sum or Average | 2724.35 | 214.30 | 1319.57 | 539.38 | 780.19 | 0.00 | 0.00 |
Minimum of Months | 1949.82 | 1.93 | 732.13 | 1.52 | 710.79 | 0.00 | 0.00 |
Maximum of Months | 3381.22 | 635.96 | 2032.19 | 1321.40 | 859.91 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 316.79 | 98.56 | 204.33 | 112.28 | 92.05 | 0.00 | 0.00 |
February | 358.43 | 77.26 | 215.56 | 109.16 | 106.40 | 0.00 | 0.00 |
March | 370.84 | 55.67 | 221.84 | 98.14 | 123.70 | 0.00 | 0.00 |
April | 398.53 | 23.14 | 214.97 | 85.57 | 129.41 | 0.00 | 0.00 |
May | 406.94 | 3.70 | 189.42 | 58.27 | 131.16 | 0.00 | 0.00 |
June | 397.46 | 0.26 | 164.43 | 35.12 | 129.31 | 0.00 | 0.00 |
July | 436.32 | 1.31 | 181.67 | 43.41 | 138.25 | 0.00 | 0.00 |
August | 437.76 | 0.08 | 186.60 | 48.74 | 137.86 | 0.00 | 0.00 |
September | 425.00 | 2.00 | 180.34 | 50.21 | 130.14 | 0.00 | 0.00 |
October | 422.56 | 5.64 | 203.88 | 86.91 | 116.98 | 0.00 | 0.00 |
November | 358.54 | 35.75 | 194.30 | 90.09 | 104.21 | 0.00 | 0.00 |
December | 328.37 | 79.62 | 203.40 | 110.44 | 92.96 | 0.00 | 0.00 |
Annual Sum or Average | 388.30 | 31.73 | 196.66 | 77.23 | 119.43 | 0.00 | 0.00 |
Minimum of Months | 316.79 | 0.08 | 164.43 | 35.12 | 92.05 | 0.00 | 0.00 |
Maximum of Months | 437.76 | 98.56 | 221.84 | 112.28 | 138.25 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 178.17 | 99.33 | 117.82 | 40.86 | 76.96 | 0.00 | 0.00 |
February | 243.17 | 77.32 | 146.21 | 54.01 | 92.19 | 0.00 | 0.00 |
March | 296.03 | 55.75 | 179.84 | 67.15 | 112.69 | 0.00 | 0.00 |
April | 363.86 | 22.47 | 198.25 | 74.77 | 123.48 | 0.00 | 0.00 |
May | 406.39 | 3.59 | 189.49 | 58.66 | 130.84 | 0.00 | 0.00 |
June | 408.70 | 0.28 | 169.90 | 38.27 | 131.63 | 0.00 | 0.00 |
July | 442.96 | 1.33 | 184.95 | 45.33 | 139.62 | 0.00 | 0.00 |
August | 422.81 | 0.08 | 179.40 | 45.60 | 133.80 | 0.00 | 0.00 |
September | 375.45 | 1.92 | 154.39 | 34.96 | 119.43 | 0.00 | 0.00 |
October | 324.56 | 5.20 | 148.17 | 46.17 | 102.00 | 0.00 | 0.00 |
November | 241.41 | 35.74 | 123.30 | 35.62 | 87.68 | 0.00 | 0.00 |
December | 194.38 | 78.32 | 120.57 | 43.57 | 77.00 | 0.00 | 0.00 |
Annual Sum or Average | 325.25 | 31.59 | 159.44 | 48.74 | 110.71 | 0.00 | 0.00 |
Minimum of Months | 178.17 | 0.08 | 117.82 | 34.96 | 76.96 | 0.00 | 0.00 |
Maximum of Months | 442.96 | 99.33 | 198.25 | 74.77 | 139.62 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 136.24 | 36.51 | 87.85 | 57.13 | 30.73 | 0.00 | 0.00 |
February | 126.53 | 29.50 | 77.56 | 44.11 | 33.45 | 0.00 | 0.00 |
March | 99.58 | 23.00 | 59.94 | 24.78 | 35.16 | 0.00 | 0.00 |
April | 81.72 | 12.60 | 42.98 | 8.80 | 34.17 | 0.00 | 0.00 |
May | 73.72 | 3.24 | 33.55 | 1.07 | 32.49 | 0.00 | 0.00 |
June | 77.37 | 0.83 | 31.65 | 0.07 | 31.59 | 0.00 | 0.00 |
July | 84.83 | 1.60 | 33.87 | 0.28 | 33.58 | 0.00 | 0.00 |
August | 90.93 | 0.79 | 38.07 | 2.85 | 35.23 | 0.00 | 0.00 |
September | 113.15 | 3.02 | 49.37 | 12.20 | 37.18 | 0.00 | 0.00 |
October | 134.09 | 5.12 | 68.52 | 32.58 | 35.94 | 0.00 | 0.00 |
November | 134.10 | 15.45 | 77.63 | 43.57 | 34.06 | 0.00 | 0.00 |
December | 134.28 | 31.18 | 84.70 | 53.48 | 31.22 | 0.00 | 0.00 |
Annual Sum or Average | 107.11 | 13.50 | 57.05 | 23.32 | 33.73 | 0.00 | 0.00 |
Minimum of Months | 73.72 | 0.79 | 31.65 | 0.07 | 30.73 | 0.00 | 0.00 |
Maximum of Months | 136.24 | 36.51 | 87.85 | 57.13 | 37.18 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 26.17 | 28.08 | 18.66 | 0.00 | 18.66 | 0.00 | 0.00 |
February | 37.58 | 21.21 | 22.09 | 0.00 | 22.09 | 0.00 | 0.00 |
March | 44.49 | 14.90 | 26.35 | 0.00 | 26.35 | 0.00 | 0.00 |
April | 60.94 | 5.16 | 29.61 | 0.17 | 29.44 | 0.00 | 0.00 |
May | 85.39 | 0.81 | 33.62 | 1.38 | 32.24 | 0.00 | 0.00 |
June | 99.91 | 0.04 | 36.04 | 2.59 | 33.45 | 0.00 | 0.00 |
July | 102.62 | 0.23 | 36.50 | 1.82 | 34.69 | 0.00 | 0.00 |
August | 92.33 | 0.01 | 32.33 | 0.34 | 31.99 | 0.00 | 0.00 |
September | 83.92 | 0.30 | 28.63 | 0.01 | 28.62 | 0.00 | 0.00 |
October | 64.46 | 1.06 | 23.97 | 0.00 | 23.97 | 0.00 | 0.00 |
November | 46.33 | 9.57 | 20.84 | 0.00 | 20.84 | 0.00 | 0.00 |
December | 29.31 | 22.01 | 18.46 | 0.00 | 18.46 | 0.00 | 0.00 |
Annual Sum or Average | 64.58 | 8.57 | 27.29 | 0.53 | 26.76 | 0.00 | 0.00 |
Minimum of Months | 26.17 | 0.01 | 18.46 | 0.00 | 18.46 | 0.00 | 0.00 |
Maximum of Months | 102.62 | 28.08 | 36.50 | 2.59 | 34.69 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 331.59 | 96.60 | 214.72 | 121.68 | 93.04 | 0.00 | 0.00 |
February | 358.94 | 73.52 | 218.61 | 111.66 | 106.95 | 0.00 | 0.00 |
March | 365.79 | 50.97 | 223.12 | 101.04 | 122.08 | 0.00 | 0.00 |
April | 397.47 | 21.68 | 214.75 | 82.89 | 131.86 | 0.00 | 0.00 |
May | 415.65 | 3.41 | 194.29 | 62.24 | 132.05 | 0.00 | 0.00 |
June | 439.63 | 0.29 | 189.29 | 57.54 | 131.75 | 0.00 | 0.00 |
July | 462.14 | 1.25 | 196.39 | 55.94 | 140.44 | 0.00 | 0.00 |
August | 442.07 | 0.08 | 188.40 | 50.70 | 137.70 | 0.00 | 0.00 |
September | 454.70 | 1.95 | 197.38 | 64.23 | 133.15 | 0.00 | 0.00 |
October | 434.50 | 5.40 | 210.38 | 94.26 | 116.13 | 0.00 | 0.00 |
November | 364.19 | 34.33 | 198.60 | 94.91 | 103.69 | 0.00 | 0.00 |
December | 301.32 | 77.71 | 188.03 | 95.97 | 92.06 | 0.00 | 0.00 |
Annual Sum or Average | 397.47 | 30.42 | 202.73 | 82.60 | 120.13 | 0.00 | 0.00 |
Minimum of Months | 301.32 | 0.08 | 188.03 | 50.70 | 92.06 | 0.00 | 0.00 |
Maximum of Months | 462.14 | 96.60 | 223.12 | 121.68 | 140.44 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 189.46 | 94.18 | 128.21 | 50.26 | 77.95 | 0.00 | 0.00 |
February | 240.88 | 71.34 | 149.26 | 56.52 | 92.75 | 0.00 | 0.00 |
March | 289.17 | 49.63 | 181.12 | 70.06 | 111.06 | 0.00 | 0.00 |
April | 362.72 | 21.07 | 198.02 | 72.09 | 125.93 | 0.00 | 0.00 |
May | 415.20 | 3.40 | 194.36 | 62.63 | 131.73 | 0.00 | 0.00 |
June | 450.92 | 0.31 | 194.76 | 60.70 | 134.06 | 0.00 | 0.00 |
July | 468.81 | 1.28 | 199.67 | 57.86 | 141.81 | 0.00 | 0.00 |
August | 427.11 | 0.07 | 181.21 | 47.57 | 133.64 | 0.00 | 0.00 |
September | 405.02 | 1.87 | 171.43 | 48.99 | 122.44 | 0.00 | 0.00 |
October | 336.26 | 4.96 | 154.67 | 53.52 | 101.15 | 0.00 | 0.00 |
November | 245.56 | 33.07 | 127.60 | 40.44 | 87.16 | 0.00 | 0.00 |
December | 166.56 | 75.37 | 105.21 | 29.10 | 76.11 | 0.00 | 0.00 |
Annual Sum or Average | 333.54 | 29.54 | 165.51 | 54.11 | 111.40 | 0.00 | 0.00 |
Minimum of Months | 166.56 | 0.07 | 105.21 | 29.10 | 76.11 | 0.00 | 0.00 |
Maximum of Months | 468.81 | 94.18 | 199.67 | 72.09 | 141.81 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 370.96 | 114.80 | 230.79 | 123.78 | 107.01 | 0.00 | 0.00 |
February | 378.67 | 88.29 | 215.90 | 95.57 | 120.33 | 0.00 | 0.00 |
March | 336.35 | 63.65 | 186.96 | 53.69 | 133.27 | 0.00 | 0.00 |
April | 332.41 | 26.39 | 157.26 | 19.44 | 137.82 | 0.00 | 0.00 |
May | 371.70 | 4.35 | 145.54 | 5.29 | 140.25 | 0.00 | 0.00 |
June | 407.32 | 0.57 | 146.65 | 5.76 | 140.89 | 0.00 | 0.00 |
July | 425.75 | 2.05 | 152.46 | 4.55 | 147.91 | 0.00 | 0.00 |
August | 419.21 | 0.20 | 152.53 | 6.90 | 145.63 | 0.00 | 0.00 |
September | 445.17 | 3.61 | 168.99 | 26.44 | 142.55 | 0.00 | 0.00 |
October | 449.11 | 8.28 | 200.40 | 70.59 | 129.80 | 0.00 | 0.00 |
November | 413.35 | 43.28 | 213.34 | 94.39 | 118.95 | 0.00 | 0.00 |
December | 374.12 | 93.12 | 223.52 | 115.88 | 107.64 | 0.00 | 0.00 |
Annual Sum or Average | 393.74 | 37.17 | 182.71 | 51.67 | 131.05 | 0.00 | 0.00 |
Minimum of Months | 332.41 | 0.20 | 145.54 | 4.55 | 107.01 | 0.00 | 0.00 |
Maximum of Months | 449.11 | 114.80 | 230.79 | 123.78 | 147.91 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 312.15 | 98.04 | 204.33 | 112.28 | 92.05 | 0.00 | 0.00 |
February | 352.88 | 77.07 | 215.56 | 109.16 | 106.40 | 0.00 | 0.00 |
March | 364.29 | 55.47 | 221.84 | 98.14 | 123.70 | 0.00 | 0.00 |
April | 391.81 | 23.04 | 214.97 | 85.57 | 129.41 | 0.00 | 0.00 |
May | 400.94 | 3.56 | 189.42 | 58.27 | 131.16 | 0.00 | 0.00 |
June | 391.96 | 0.24 | 164.43 | 35.12 | 129.31 | 0.00 | 0.00 |
July | 430.53 | 1.24 | 181.67 | 43.41 | 138.25 | 0.00 | 0.00 |
August | 432.16 | 0.10 | 186.60 | 48.74 | 137.86 | 0.00 | 0.00 |
September | 419.56 | 1.86 | 180.34 | 50.21 | 130.14 | 0.00 | 0.00 |
October | 417.64 | 5.33 | 203.88 | 86.91 | 116.98 | 0.00 | 0.00 |
November | 353.65 | 35.19 | 194.30 | 90.09 | 104.21 | 0.00 | 0.00 |
December | 323.41 | 79.38 | 203.40 | 110.44 | 92.96 | 0.00 | 0.00 |
Annual Sum or Average | 382.75 | 31.52 | 196.66 | 77.23 | 119.43 | 0.00 | 0.00 |
Minimum of Months | 312.15 | 0.10 | 164.43 | 35.12 | 92.05 | 0.00 | 0.00 |
Maximum of Months | 432.16 | 98.04 | 221.84 | 112.28 | 138.25 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 174.86 | 98.43 | 117.82 | 40.86 | 76.96 | 0.00 | 0.00 |
February | 238.89 | 76.95 | 146.21 | 54.01 | 92.19 | 0.00 | 0.00 |
March | 290.41 | 55.51 | 179.84 | 67.15 | 112.69 | 0.00 | 0.00 |
April | 357.55 | 22.38 | 198.25 | 74.77 | 123.48 | 0.00 | 0.00 |
May | 400.24 | 3.47 | 189.49 | 58.66 | 130.84 | 0.00 | 0.00 |
June | 402.97 | 0.25 | 169.90 | 38.27 | 131.63 | 0.00 | 0.00 |
July | 437.08 | 1.26 | 184.95 | 45.33 | 139.62 | 0.00 | 0.00 |
August | 417.29 | 0.10 | 179.40 | 45.60 | 133.80 | 0.00 | 0.00 |
September | 370.58 | 1.76 | 154.39 | 34.96 | 119.43 | 0.00 | 0.00 |
October | 320.72 | 4.86 | 148.17 | 46.17 | 102.00 | 0.00 | 0.00 |
November | 237.74 | 35.04 | 123.30 | 35.62 | 87.68 | 0.00 | 0.00 |
December | 190.88 | 77.74 | 120.57 | 43.57 | 77.00 | 0.00 | 0.00 |
Annual Sum or Average | 320.36 | 31.29 | 159.44 | 48.74 | 110.71 | 0.00 | 0.00 |
Minimum of Months | 174.86 | 0.10 | 117.82 | 34.96 | 76.96 | 0.00 | 0.00 |
Maximum of Months | 437.08 | 98.43 | 198.25 | 74.77 | 139.62 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 252.99 | 51.08 | 161.09 | 104.75 | 56.34 | 0.00 | 0.00 |
February | 236.24 | 39.09 | 142.21 | 80.88 | 61.33 | 0.00 | 0.00 |
March | 187.95 | 27.33 | 109.90 | 45.44 | 64.46 | 0.00 | 0.00 |
April | 157.19 | 10.48 | 78.80 | 16.14 | 62.66 | 0.00 | 0.00 |
May | 151.70 | 1.57 | 61.53 | 1.95 | 59.57 | 0.00 | 0.00 |
June | 160.49 | 0.08 | 58.04 | 0.12 | 57.92 | 0.00 | 0.00 |
July | 172.11 | 0.47 | 62.10 | 0.52 | 61.58 | 0.00 | 0.00 |
August | 185.22 | 0.02 | 69.81 | 5.22 | 64.59 | 0.00 | 0.00 |
September | 220.72 | 0.72 | 90.53 | 22.37 | 68.17 | 0.00 | 0.00 |
October | 256.81 | 2.53 | 125.64 | 59.74 | 65.90 | 0.00 | 0.00 |
November | 253.77 | 17.97 | 142.33 | 79.88 | 62.45 | 0.00 | 0.00 |
December | 249.21 | 41.64 | 155.31 | 98.06 | 57.25 | 0.00 | 0.00 |
Annual Sum or Average | 206.89 | 15.99 | 104.60 | 42.76 | 61.85 | 0.00 | 0.00 |
Minimum of Months | 151.70 | 0.02 | 58.04 | 0.12 | 56.34 | 0.00 | 0.00 |
Maximum of Months | 256.81 | 51.08 | 161.09 | 104.75 | 68.17 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 223.50 | 275.11 | 163.29 | 0.00 | 163.29 | 0.00 | 0.00 |
February | 322.09 | 218.65 | 193.28 | 0.00 | 193.28 | 0.00 | 0.00 |
March | 382.38 | 166.38 | 230.56 | 0.00 | 230.56 | 0.00 | 0.00 |
April | 526.56 | 75.87 | 259.03 | 1.48 | 257.55 | 0.00 | 0.00 |
May | 717.72 | 16.06 | 294.14 | 12.05 | 282.09 | 0.00 | 0.00 |
June | 836.44 | 2.89 | 315.27 | 22.68 | 292.60 | 0.00 | 0.00 |
July | 866.36 | 7.51 | 319.36 | 15.90 | 303.47 | 0.00 | 0.00 |
August | 770.21 | 2.52 | 282.83 | 2.96 | 279.86 | 0.00 | 0.00 |
September | 709.93 | 13.35 | 250.44 | 0.06 | 250.38 | 0.00 | 0.00 |
October | 546.52 | 24.14 | 209.71 | 0.00 | 209.71 | 0.00 | 0.00 |
November | 394.16 | 107.29 | 182.34 | 0.00 | 182.34 | 0.00 | 0.00 |
December | 250.34 | 224.13 | 161.51 | 0.00 | 161.51 | 0.00 | 0.00 |
Annual Sum or Average | 546.57 | 93.96 | 238.71 | 4.62 | 234.09 | 0.00 | 0.00 |
Minimum of Months | 223.50 | 2.52 | 161.51 | 0.00 | 161.51 | 0.00 | 0.00 |
Maximum of Months | 866.36 | 275.11 | 319.36 | 22.68 | 303.47 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 215.76 | 289.12 | 163.29 | 0.00 | 163.29 | 0.00 | 0.00 |
February | 312.40 | 232.08 | 193.28 | 0.00 | 193.28 | 0.00 | 0.00 |
March | 370.95 | 178.70 | 230.56 | 0.00 | 230.56 | 0.00 | 0.00 |
April | 513.06 | 85.84 | 259.03 | 1.48 | 257.55 | 0.00 | 0.00 |
May | 698.87 | 19.96 | 294.14 | 12.05 | 282.09 | 0.00 | 0.00 |
June | 816.59 | 4.02 | 315.27 | 22.68 | 292.60 | 0.00 | 0.00 |
July | 848.63 | 9.29 | 319.36 | 15.90 | 303.47 | 0.00 | 0.00 |
August | 750.60 | 3.72 | 282.83 | 2.96 | 279.86 | 0.00 | 0.00 |
September | 693.60 | 16.87 | 250.44 | 0.06 | 250.38 | 0.00 | 0.00 |
October | 530.25 | 28.81 | 209.71 | 0.00 | 209.71 | 0.00 | 0.00 |
November | 380.14 | 115.43 | 182.34 | 0.00 | 182.34 | 0.00 | 0.00 |
December | 241.60 | 237.36 | 161.51 | 0.00 | 161.51 | 0.00 | 0.00 |
Annual Sum or Average | 532.07 | 101.20 | 238.71 | 4.62 | 234.09 | 0.00 | 0.00 |
Minimum of Months | 215.76 | 3.72 | 161.51 | 0.00 | 161.51 | 0.00 | 0.00 |
Maximum of Months | 848.63 | 289.12 | 319.36 | 22.68 | 303.47 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 536.12 | 241.12 | 342.91 | 171.94 | 170.98 | 0.00 | 0.00 |
February | 605.95 | 202.18 | 367.86 | 168.17 | 199.69 | 0.00 | 0.00 |
March | 662.80 | 155.92 | 404.22 | 171.09 | 233.13 | 0.00 | 0.00 |
April | 776.86 | 86.37 | 412.74 | 154.97 | 257.78 | 0.00 | 0.00 |
May | 827.96 | 26.08 | 388.63 | 124.86 | 263.78 | 0.00 | 0.00 |
June | 893.48 | 6.26 | 384.04 | 118.24 | 265.80 | 0.00 | 0.00 |
July | 954.66 | 11.54 | 396.04 | 113.80 | 282.24 | 0.00 | 0.00 |
August | 863.53 | 7.28 | 369.59 | 98.26 | 271.33 | 0.00 | 0.00 |
September | 877.71 | 17.23 | 368.79 | 113.22 | 255.57 | 0.00 | 0.00 |
October | 781.91 | 31.76 | 365.04 | 147.77 | 217.27 | 0.00 | 0.00 |
November | 620.70 | 102.23 | 326.19 | 135.34 | 190.84 | 0.00 | 0.00 |
December | 479.71 | 202.35 | 293.22 | 125.06 | 168.16 | 0.00 | 0.00 |
Annual Sum or Average | 740.65 | 90.36 | 368.22 | 136.71 | 231.52 | 0.00 | 0.00 |
Minimum of Months | 479.71 | 6.26 | 293.22 | 98.26 | 168.16 | 0.00 | 0.00 |
Maximum of Months | 954.66 | 241.12 | 412.74 | 171.94 | 282.24 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 747.26 | 198.30 | 466.04 | 266.64 | 199.40 | 0.00 | 0.00 |
February | 743.85 | 150.87 | 428.25 | 205.88 | 222.37 | 0.00 | 0.00 |
March | 642.92 | 107.07 | 358.80 | 115.67 | 243.13 | 0.00 | 0.00 |
April | 613.12 | 39.40 | 289.39 | 41.60 | 247.79 | 0.00 | 0.00 |
May | 664.38 | 6.18 | 257.45 | 9.10 | 248.35 | 0.00 | 0.00 |
June | 716.44 | 0.48 | 255.81 | 8.08 | 247.73 | 0.00 | 0.00 |
July | 748.25 | 2.62 | 267.56 | 6.78 | 260.78 | 0.00 | 0.00 |
August | 759.38 | 0.12 | 274.66 | 14.31 | 260.36 | 0.00 | 0.00 |
September | 825.98 | 3.25 | 316.30 | 56.95 | 259.35 | 0.00 | 0.00 |
October | 874.15 | 9.55 | 391.72 | 152.07 | 239.64 | 0.00 | 0.00 |
November | 817.41 | 68.73 | 424.83 | 203.35 | 221.48 | 0.00 | 0.00 |
December | 749.46 | 160.56 | 450.71 | 249.63 | 201.09 | 0.00 | 0.00 |
Annual Sum or Average | 741.85 | 61.91 | 348.10 | 110.42 | 237.68 | 0.00 | 0.00 |
Minimum of Months | 613.12 | 0.12 | 255.81 | 6.78 | 199.40 | 0.00 | 0.00 |
Maximum of Months | 874.15 | 198.30 | 466.04 | 266.64 | 260.78 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.241075E+10 | 0.446551E+09 | 0.148795E+10 | 0.967519E+09 | 0.520433E+09 | 0.00 | 0.00 |
February | 0.204261E+10 | 0.314857E+09 | 0.118642E+10 | 0.674762E+09 | 0.511657E+09 | 0.00 | 0.00 |
March | 0.181890E+10 | 0.254480E+09 | 0.101513E+10 | 0.419697E+09 | 0.595431E+09 | 0.00 | 0.00 |
April | 0.145629E+10 | 0.104798E+09 | 0.704385E+09 | 0.144292E+09 | 0.560093E+09 | 0.00 | 0.00 |
May | 0.140390E+10 | 17567904.18 | 0.568300E+09 | 18039893.06 | 0.550260E+09 | 0.00 | 0.00 |
June | 0.142259E+10 | 946029.98 | 0.518766E+09 | 1079877.92 | 0.517686E+09 | 0.00 | 0.00 |
July | 0.156796E+10 | 6150496.22 | 0.573595E+09 | 4816469.25 | 0.568779E+09 | 0.00 | 0.00 |
August | 0.169363E+10 | 352411.32 | 0.644834E+09 | 48222350.38 | 0.596611E+09 | 0.00 | 0.00 |
September | 0.195495E+10 | 9773733.42 | 0.809229E+09 | 0.199919E+09 | 0.609311E+09 | 0.00 | 0.00 |
October | 0.237380E+10 | 32465453.46 | 0.116052E+10 | 0.551817E+09 | 0.608706E+09 | 0.00 | 0.00 |
November | 0.230998E+10 | 0.161993E+09 | 0.127230E+10 | 0.714056E+09 | 0.558244E+09 | 0.00 | 0.00 |
December | 0.237253E+10 | 0.365284E+09 | 0.143456E+10 | 0.905795E+09 | 0.528761E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.228279E+11 | 0.171522E+10 | 0.113760E+11 | 0.465001E+10 | 0.672597E+10 | 0.00 | 0.00 |
Minimum of Months | 0.140390E+10 | 352411.32 | 0.518766E+09 | 1079877.92 | 0.511657E+09 | 0.00 | 0.00 |
Maximum of Months | 0.241075E+10 | 0.446551E+09 | 0.148795E+10 | 0.967519E+09 | 0.609311E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.675656E+10 | 0.133968E+10 | 0.418997E+10 | 0.272447E+10 | 0.146550E+10 | 0.00 | 0.00 |
February | 0.571985E+10 | 0.961590E+09 | 0.334088E+10 | 0.190008E+10 | 0.144079E+10 | 0.00 | 0.00 |
March | 0.508332E+10 | 0.807559E+09 | 0.285853E+10 | 0.118184E+10 | 0.167669E+10 | 0.00 | 0.00 |
April | 0.406453E+10 | 0.370384E+09 | 0.198350E+10 | 0.406316E+09 | 0.157718E+10 | 0.00 | 0.00 |
May | 0.385386E+10 | 77208674.60 | 0.160030E+10 | 50799149.42 | 0.154950E+10 | 0.00 | 0.00 |
June | 0.389448E+10 | 10063266.45 | 0.146081E+10 | 3040865.03 | 0.145777E+10 | 0.00 | 0.00 |
July | 0.434896E+10 | 32617060.45 | 0.161521E+10 | 13562859.83 | 0.160164E+10 | 0.00 | 0.00 |
August | 0.467016E+10 | 6911631.55 | 0.181581E+10 | 0.135791E+09 | 0.168002E+10 | 0.00 | 0.00 |
September | 0.547023E+10 | 64293223.72 | 0.227874E+10 | 0.562957E+09 | 0.171578E+10 | 0.00 | 0.00 |
October | 0.664567E+10 | 0.146700E+09 | 0.326796E+10 | 0.155388E+10 | 0.171408E+10 | 0.00 | 0.00 |
November | 0.646028E+10 | 0.521859E+09 | 0.358271E+10 | 0.201074E+10 | 0.157198E+10 | 0.00 | 0.00 |
December | 0.665514E+10 | 0.111208E+10 | 0.403962E+10 | 0.255066E+10 | 0.148896E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.636230E+11 | 0.545095E+10 | 0.320340E+11 | 0.130941E+11 | 0.189399E+11 | 0.00 | 0.00 |
Minimum of Months | 0.385386E+10 | 6911631.55 | 0.146081E+10 | 3040865.03 | 0.144079E+10 | 0.00 | 0.00 |
Maximum of Months | 0.675656E+10 | 0.133968E+10 | 0.418997E+10 | 0.272447E+10 | 0.171578E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.905625E+10 | 0.170334E+10 | 0.544302E+10 | 0.353924E+10 | 0.190377E+10 | 0.00 | 0.00 |
February | 0.767614E+10 | 0.120946E+10 | 0.433999E+10 | 0.246832E+10 | 0.187167E+10 | 0.00 | 0.00 |
March | 0.682837E+10 | 0.101236E+10 | 0.371340E+10 | 0.153528E+10 | 0.217812E+10 | 0.00 | 0.00 |
April | 0.547866E+10 | 0.447140E+09 | 0.257668E+10 | 0.527828E+09 | 0.204885E+10 | 0.00 | 0.00 |
May | 0.522239E+10 | 88357129.81 | 0.207888E+10 | 65990986.10 | 0.201288E+10 | 0.00 | 0.00 |
June | 0.528916E+10 | 10287770.09 | 0.189768E+10 | 3950256.73 | 0.189373E+10 | 0.00 | 0.00 |
July | 0.589857E+10 | 36202971.73 | 0.209825E+10 | 17618926.79 | 0.208063E+10 | 0.00 | 0.00 |
August | 0.635362E+10 | 5163901.75 | 0.235884E+10 | 0.176400E+09 | 0.218244E+10 | 0.00 | 0.00 |
September | 0.743417E+10 | 63452857.53 | 0.296021E+10 | 0.731314E+09 | 0.222890E+10 | 0.00 | 0.00 |
October | 0.902096E+10 | 0.142985E+09 | 0.424526E+10 | 0.201858E+10 | 0.222668E+10 | 0.00 | 0.00 |
November | 0.872759E+10 | 0.638017E+09 | 0.465415E+10 | 0.261206E+10 | 0.204209E+10 | 0.00 | 0.00 |
December | 0.892929E+10 | 0.140142E+10 | 0.524769E+10 | 0.331345E+10 | 0.193424E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.859152E+11 | 0.675819E+10 | 0.416140E+11 | 0.170100E+11 | 0.246040E+11 | 0.00 | 0.00 |
Minimum of Months | 0.522239E+10 | 5163901.75 | 0.189768E+10 | 3950256.73 | 0.187167E+10 | 0.00 | 0.00 |
Maximum of Months | 0.905625E+10 | 0.170334E+10 | 0.544302E+10 | 0.353924E+10 | 0.222890E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.848502E+09 | 0.263971E+09 | 0.547283E+09 | 0.300734E+09 | 0.246549E+09 | 0.00 | 0.00 |
February | 0.867120E+09 | 0.186917E+09 | 0.521479E+09 | 0.264081E+09 | 0.257398E+09 | 0.00 | 0.00 |
March | 0.993245E+09 | 0.149107E+09 | 0.594175E+09 | 0.262845E+09 | 0.331330E+09 | 0.00 | 0.00 |
April | 0.103298E+10 | 59986320.56 | 0.557213E+09 | 0.221785E+09 | 0.335428E+09 | 0.00 | 0.00 |
May | 0.108995E+10 | 9902586.75 | 0.507352E+09 | 0.156063E+09 | 0.351288E+09 | 0.00 | 0.00 |
June | 0.103022E+10 | 684787.82 | 0.426207E+09 | 91025211.56 | 0.335181E+09 | 0.00 | 0.00 |
July | 0.116865E+10 | 3509614.56 | 0.486578E+09 | 0.116277E+09 | 0.370301E+09 | 0.00 | 0.00 |
August | 0.117249E+10 | 226695.67 | 0.499793E+09 | 0.130546E+09 | 0.369247E+09 | 0.00 | 0.00 |
September | 0.110160E+10 | 5192144.23 | 0.467448E+09 | 0.130132E+09 | 0.337316E+09 | 0.00 | 0.00 |
October | 0.113178E+10 | 15098585.97 | 0.546079E+09 | 0.232772E+09 | 0.313307E+09 | 0.00 | 0.00 |
November | 0.929348E+09 | 92665190.55 | 0.503617E+09 | 0.233505E+09 | 0.270113E+09 | 0.00 | 0.00 |
December | 0.879496E+09 | 0.213259E+09 | 0.544779E+09 | 0.295801E+09 | 0.248978E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.122454E+11 | 0.100052E+10 | 0.620200E+10 | 0.243557E+10 | 0.376644E+10 | 0.00 | 0.00 |
Minimum of Months | 0.848502E+09 | 226695.67 | 0.426207E+09 | 91025211.56 | 0.246549E+09 | 0.00 | 0.00 |
Maximum of Months | 0.117249E+10 | 0.263971E+09 | 0.594175E+09 | 0.300734E+09 | 0.370301E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.477220E+09 | 0.266054E+09 | 0.315569E+09 | 0.109438E+09 | 0.206131E+09 | 0.00 | 0.00 |
February | 0.588267E+09 | 0.187051E+09 | 0.353702E+09 | 0.130669E+09 | 0.223033E+09 | 0.00 | 0.00 |
March | 0.792874E+09 | 0.149309E+09 | 0.481688E+09 | 0.179865E+09 | 0.301822E+09 | 0.00 | 0.00 |
April | 0.943130E+09 | 58252319.37 | 0.513861E+09 | 0.193804E+09 | 0.320057E+09 | 0.00 | 0.00 |
May | 0.108848E+10 | 9618470.52 | 0.507540E+09 | 0.157107E+09 | 0.350432E+09 | 0.00 | 0.00 |
June | 0.105936E+10 | 726331.39 | 0.440383E+09 | 99208328.72 | 0.341174E+09 | 0.00 | 0.00 |
July | 0.118642E+10 | 3559212.35 | 0.495369E+09 | 0.121407E+09 | 0.373962E+09 | 0.00 | 0.00 |
August | 0.113245E+10 | 225241.64 | 0.480518E+09 | 0.122146E+09 | 0.358372E+09 | 0.00 | 0.00 |
September | 0.973159E+09 | 4972818.59 | 0.400187E+09 | 90626159.72 | 0.309561E+09 | 0.00 | 0.00 |
October | 0.869310E+09 | 13929514.34 | 0.396866E+09 | 0.123668E+09 | 0.273197E+09 | 0.00 | 0.00 |
November | 0.625728E+09 | 92632688.66 | 0.319582E+09 | 92323391.94 | 0.227259E+09 | 0.00 | 0.00 |
December | 0.520636E+09 | 0.209767E+09 | 0.322943E+09 | 0.116710E+09 | 0.206233E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.102570E+11 | 0.996099E+09 | 0.502821E+10 | 0.153697E+10 | 0.349123E+10 | 0.00 | 0.00 |
Minimum of Months | 0.477220E+09 | 225241.64 | 0.315569E+09 | 90626159.72 | 0.206131E+09 | 0.00 | 0.00 |
Maximum of Months | 0.118642E+10 | 0.266054E+09 | 0.513861E+09 | 0.193804E+09 | 0.373962E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.364894E+09 | 97781420.27 | 0.235309E+09 | 0.153006E+09 | 82302997.65 | 0.00 | 0.00 |
February | 0.306094E+09 | 71368267.21 | 0.187624E+09 | 0.106708E+09 | 80915277.26 | 0.00 | 0.00 |
March | 0.266707E+09 | 61608765.86 | 0.160536E+09 | 66371880.15 | 94163689.54 | 0.00 | 0.00 |
April | 0.211829E+09 | 32649015.10 | 0.111394E+09 | 22818620.98 | 88575365.15 | 0.00 | 0.00 |
May | 0.197460E+09 | 8688711.61 | 89873280.16 | 2852869.99 | 87020410.17 | 0.00 | 0.00 |
June | 0.200536E+09 | 2157193.81 | 82039774.92 | 170774.37 | 81869000.56 | 0.00 | 0.00 |
July | 0.227211E+09 | 4296855.71 | 90710703.00 | 761687.47 | 89949015.53 | 0.00 | 0.00 |
August | 0.243551E+09 | 2124044.25 | 0.101976E+09 | 7625992.90 | 94350425.71 | 0.00 | 0.00 |
September | 0.293281E+09 | 7825112.03 | 0.127974E+09 | 31615575.84 | 96358645.11 | 0.00 | 0.00 |
October | 0.359144E+09 | 13718865.81 | 0.183529E+09 | 87265587.65 | 96262912.52 | 0.00 | 0.00 |
November | 0.347580E+09 | 40049532.75 | 0.201205E+09 | 0.112922E+09 | 88282536.13 | 0.00 | 0.00 |
December | 0.359650E+09 | 83522498.42 | 0.226865E+09 | 0.143244E+09 | 83620064.08 | 0.00 | 0.00 |
Annual Sum or Average | 0.337794E+10 | 0.425790E+09 | 0.179903E+10 | 0.735364E+09 | 0.106367E+10 | 0.00 | 0.00 |
Minimum of Months | 0.197460E+09 | 2124044.25 | 82039774.92 | 170774.37 | 80915277.26 | 0.00 | 0.00 |
Maximum of Months | 0.364894E+09 | 97781420.27 | 0.235309E+09 | 0.153006E+09 | 96358645.11 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 70096559.15 | 75202368.82 | 49991117.79 | 0.00 | 49991117.79 | 0.00 | 0.00 |
February | 90902765.60 | 51314685.63 | 53446117.01 | 0.00 | 53446117.01 | 0.00 | 0.00 |
March | 0.119161E+09 | 39921099.57 | 70587127.69 | 1245.66 | 70585882.03 | 0.00 | 0.00 |
April | 0.157946E+09 | 13385655.68 | 76744494.28 | 438154.86 | 76306339.42 | 0.00 | 0.00 |
May | 0.228712E+09 | 2172375.97 | 90053455.50 | 3689174.61 | 86364280.90 | 0.00 | 0.00 |
June | 0.258974E+09 | 101216.01 | 93409270.91 | 6718192.47 | 86691078.44 | 0.00 | 0.00 |
July | 0.274848E+09 | 625017.25 | 97774596.35 | 4866543.94 | 92908052.41 | 0.00 | 0.00 |
August | 0.247303E+09 | 23584.37 | 86588371.69 | 907702.50 | 85680669.19 | 0.00 | 0.00 |
September | 0.217517E+09 | 764947.25 | 74200848.51 | 17142.51 | 74183706.00 | 0.00 | 0.00 |
October | 0.172662E+09 | 2845975.84 | 64202974.78 | 0.00 | 64202974.78 | 0.00 | 0.00 |
November | 0.120097E+09 | 24805621.58 | 54024017.81 | 0.00 | 54024017.81 | 0.00 | 0.00 |
December | 78507998.05 | 58962788.38 | 49447441.40 | 0.00 | 49447441.40 | 0.00 | 0.00 |
Annual Sum or Average | 0.203673E+10 | 0.270125E+09 | 0.860470E+09 | 16638156.53 | 0.843832E+09 | 0.00 | 0.00 |
Minimum of Months | 70096559.15 | 23584.37 | 49447441.40 | 0.00 | 49447441.40 | 0.00 | 0.00 |
Maximum of Months | 0.274848E+09 | 75202368.82 | 97774596.35 | 6718192.47 | 92908052.41 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.888134E+09 | 0.258747E+09 | 0.575104E+09 | 0.325914E+09 | 0.249190E+09 | 0.00 | 0.00 |
February | 0.868339E+09 | 0.177866E+09 | 0.528872E+09 | 0.270134E+09 | 0.258738E+09 | 0.00 | 0.00 |
March | 0.979725E+09 | 0.136523E+09 | 0.597604E+09 | 0.270631E+09 | 0.326974E+09 | 0.00 | 0.00 |
April | 0.103024E+10 | 56196544.51 | 0.556623E+09 | 0.214843E+09 | 0.341780E+09 | 0.00 | 0.00 |
May | 0.111328E+10 | 9146237.42 | 0.520390E+09 | 0.166696E+09 | 0.353695E+09 | 0.00 | 0.00 |
June | 0.113951E+10 | 753822.08 | 0.490649E+09 | 0.149155E+09 | 0.341494E+09 | 0.00 | 0.00 |
July | 0.123781E+10 | 3354466.27 | 0.526007E+09 | 0.149841E+09 | 0.376166E+09 | 0.00 | 0.00 |
August | 0.118405E+10 | 203170.76 | 0.504622E+09 | 0.135800E+09 | 0.368822E+09 | 0.00 | 0.00 |
September | 0.117859E+10 | 5057945.84 | 0.511604E+09 | 0.166489E+09 | 0.345115E+09 | 0.00 | 0.00 |
October | 0.116377E+10 | 14452189.23 | 0.563490E+09 | 0.252459E+09 | 0.311031E+09 | 0.00 | 0.00 |
November | 0.943969E+09 | 88994167.64 | 0.514776E+09 | 0.246004E+09 | 0.268773E+09 | 0.00 | 0.00 |
December | 0.807046E+09 | 0.208138E+09 | 0.503620E+09 | 0.257033E+09 | 0.246587E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.125345E+11 | 0.959432E+09 | 0.639336E+10 | 0.260500E+10 | 0.378836E+10 | 0.00 | 0.00 |
Minimum of Months | 0.807046E+09 | 203170.76 | 0.490649E+09 | 0.135800E+09 | 0.246587E+09 | 0.00 | 0.00 |
Maximum of Months | 0.123781E+10 | 0.258747E+09 | 0.597604E+09 | 0.325914E+09 | 0.376166E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.507439E+09 | 0.252261E+09 | 0.343390E+09 | 0.134618E+09 | 0.208771E+09 | 0.00 | 0.00 |
February | 0.582731E+09 | 0.172596E+09 | 0.361094E+09 | 0.136722E+09 | 0.224373E+09 | 0.00 | 0.00 |
March | 0.774520E+09 | 0.132921E+09 | 0.485117E+09 | 0.187651E+09 | 0.297466E+09 | 0.00 | 0.00 |
April | 0.940165E+09 | 54609628.43 | 0.513271E+09 | 0.186862E+09 | 0.326409E+09 | 0.00 | 0.00 |
May | 0.111207E+10 | 9102704.25 | 0.520578E+09 | 0.167740E+09 | 0.352838E+09 | 0.00 | 0.00 |
June | 0.116878E+10 | 796328.34 | 0.504825E+09 | 0.157338E+09 | 0.347487E+09 | 0.00 | 0.00 |
July | 0.125565E+10 | 3418538.18 | 0.534798E+09 | 0.154971E+09 | 0.379827E+09 | 0.00 | 0.00 |
August | 0.114398E+10 | 200081.60 | 0.485347E+09 | 0.127400E+09 | 0.357947E+09 | 0.00 | 0.00 |
September | 0.104981E+10 | 4836873.69 | 0.444343E+09 | 0.126983E+09 | 0.317360E+09 | 0.00 | 0.00 |
October | 0.900644E+09 | 13278465.12 | 0.414277E+09 | 0.143355E+09 | 0.270922E+09 | 0.00 | 0.00 |
November | 0.636482E+09 | 85727018.62 | 0.330741E+09 | 0.104823E+09 | 0.225919E+09 | 0.00 | 0.00 |
December | 0.446111E+09 | 0.201866E+09 | 0.281784E+09 | 77942147.70 | 0.203842E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.105184E+11 | 0.931613E+09 | 0.521957E+10 | 0.170640E+10 | 0.351316E+10 | 0.00 | 0.00 |
Minimum of Months | 0.446111E+09 | 200081.60 | 0.281784E+09 | 77942147.70 | 0.203842E+09 | 0.00 | 0.00 |
Maximum of Months | 0.125565E+10 | 0.252261E+09 | 0.534798E+09 | 0.187651E+09 | 0.379827E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.993591E+09 | 0.307475E+09 | 0.618146E+09 | 0.331521E+09 | 0.286625E+09 | 0.00 | 0.00 |
February | 0.916085E+09 | 0.213580E+09 | 0.522310E+09 | 0.231207E+09 | 0.291103E+09 | 0.00 | 0.00 |
March | 0.900876E+09 | 0.170469E+09 | 0.500751E+09 | 0.143812E+09 | 0.356939E+09 | 0.00 | 0.00 |
April | 0.861613E+09 | 68395269.02 | 0.407614E+09 | 50390796.35 | 0.357223E+09 | 0.00 | 0.00 |
May | 0.995552E+09 | 11655632.24 | 0.389816E+09 | 14173365.17 | 0.375643E+09 | 0.00 | 0.00 |
June | 0.105578E+10 | 1488699.83 | 0.380113E+09 | 14923878.21 | 0.365189E+09 | 0.00 | 0.00 |
July | 0.114032E+10 | 5481659.92 | 0.408357E+09 | 12192930.96 | 0.396164E+09 | 0.00 | 0.00 |
August | 0.112283E+10 | 535915.89 | 0.408534E+09 | 18489793.87 | 0.390044E+09 | 0.00 | 0.00 |
September | 0.115389E+10 | 9362104.02 | 0.438028E+09 | 68539297.28 | 0.369489E+09 | 0.00 | 0.00 |
October | 0.120291E+10 | 22188142.80 | 0.536740E+09 | 0.189080E+09 | 0.347660E+09 | 0.00 | 0.00 |
November | 0.107139E+10 | 0.112174E+09 | 0.552989E+09 | 0.244672E+09 | 0.308318E+09 | 0.00 | 0.00 |
December | 0.100205E+10 | 0.249412E+09 | 0.598672E+09 | 0.310371E+09 | 0.288301E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.124169E+11 | 0.117222E+10 | 0.576207E+10 | 0.162937E+10 | 0.413270E+10 | 0.00 | 0.00 |
Minimum of Months | 0.861613E+09 | 535915.89 | 0.380113E+09 | 12192930.96 | 0.286625E+09 | 0.00 | 0.00 |
Maximum of Months | 0.120291E+10 | 0.307475E+09 | 0.618146E+09 | 0.331521E+09 | 0.396164E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.836055E+09 | 0.262601E+09 | 0.547283E+09 | 0.300734E+09 | 0.246549E+09 | 0.00 | 0.00 |
February | 0.853687E+09 | 0.186447E+09 | 0.521479E+09 | 0.264081E+09 | 0.257398E+09 | 0.00 | 0.00 |
March | 0.975727E+09 | 0.148559E+09 | 0.594175E+09 | 0.262845E+09 | 0.331330E+09 | 0.00 | 0.00 |
April | 0.101556E+10 | 59729715.53 | 0.557213E+09 | 0.221785E+09 | 0.335428E+09 | 0.00 | 0.00 |
May | 0.107387E+10 | 9537036.51 | 0.507352E+09 | 0.156063E+09 | 0.351288E+09 | 0.00 | 0.00 |
June | 0.101595E+10 | 618096.58 | 0.426207E+09 | 91025211.56 | 0.335181E+09 | 0.00 | 0.00 |
July | 0.115314E+10 | 3320283.14 | 0.486578E+09 | 0.116277E+09 | 0.370301E+09 | 0.00 | 0.00 |
August | 0.115750E+10 | 278323.89 | 0.499793E+09 | 0.130546E+09 | 0.369247E+09 | 0.00 | 0.00 |
September | 0.108750E+10 | 4816769.41 | 0.467448E+09 | 0.130132E+09 | 0.337316E+09 | 0.00 | 0.00 |
October | 0.111862E+10 | 14265314.30 | 0.546079E+09 | 0.232772E+09 | 0.313307E+09 | 0.00 | 0.00 |
November | 0.916662E+09 | 91209765.58 | 0.503617E+09 | 0.233505E+09 | 0.270113E+09 | 0.00 | 0.00 |
December | 0.866220E+09 | 0.212615E+09 | 0.544779E+09 | 0.295801E+09 | 0.248978E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.120705E+11 | 0.993997E+09 | 0.620200E+10 | 0.243557E+10 | 0.376644E+10 | 0.00 | 0.00 |
Minimum of Months | 0.836055E+09 | 278323.89 | 0.426207E+09 | 91025211.56 | 0.246549E+09 | 0.00 | 0.00 |
Maximum of Months | 0.115750E+10 | 0.262601E+09 | 0.594175E+09 | 0.300734E+09 | 0.370301E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.468351E+09 | 0.263629E+09 | 0.315569E+09 | 0.109438E+09 | 0.206131E+09 | 0.00 | 0.00 |
February | 0.577921E+09 | 0.186157E+09 | 0.353702E+09 | 0.130669E+09 | 0.223033E+09 | 0.00 | 0.00 |
March | 0.777844E+09 | 0.148670E+09 | 0.481688E+09 | 0.179865E+09 | 0.301822E+09 | 0.00 | 0.00 |
April | 0.926776E+09 | 58003042.28 | 0.513861E+09 | 0.193804E+09 | 0.320057E+09 | 0.00 | 0.00 |
May | 0.107199E+10 | 9283051.54 | 0.507540E+09 | 0.157107E+09 | 0.350432E+09 | 0.00 | 0.00 |
June | 0.104450E+10 | 652814.36 | 0.440383E+09 | 99208328.72 | 0.341174E+09 | 0.00 | 0.00 |
July | 0.117067E+10 | 3363282.57 | 0.495369E+09 | 0.121407E+09 | 0.373962E+09 | 0.00 | 0.00 |
August | 0.111768E+10 | 273835.48 | 0.480518E+09 | 0.122146E+09 | 0.358372E+09 | 0.00 | 0.00 |
September | 0.960545E+09 | 4557936.19 | 0.400187E+09 | 90626159.72 | 0.309561E+09 | 0.00 | 0.00 |
October | 0.859013E+09 | 13007481.17 | 0.396866E+09 | 0.123668E+09 | 0.273197E+09 | 0.00 | 0.00 |
November | 0.616229E+09 | 90835804.83 | 0.319582E+09 | 92323391.94 | 0.227259E+09 | 0.00 | 0.00 |
December | 0.511249E+09 | 0.208214E+09 | 0.322943E+09 | 0.116710E+09 | 0.206233E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.101028E+11 | 0.986647E+09 | 0.502821E+10 | 0.153697E+10 | 0.349123E+10 | 0.00 | 0.00 |
Minimum of Months | 0.468351E+09 | 273835.48 | 0.315569E+09 | 90626159.72 | 0.206131E+09 | 0.00 | 0.00 |
Maximum of Months | 0.117067E+10 | 0.263629E+09 | 0.513861E+09 | 0.193804E+09 | 0.373962E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.677617E+09 | 0.136810E+09 | 0.431464E+09 | 0.280553E+09 | 0.150912E+09 | 0.00 | 0.00 |
February | 0.571508E+09 | 94577921.33 | 0.344028E+09 | 0.195661E+09 | 0.148367E+09 | 0.00 | 0.00 |
March | 0.503411E+09 | 73187636.59 | 0.294360E+09 | 0.121700E+09 | 0.172659E+09 | 0.00 | 0.00 |
April | 0.407427E+09 | 27170169.58 | 0.204253E+09 | 41840441.24 | 0.162413E+09 | 0.00 | 0.00 |
May | 0.406323E+09 | 4198012.81 | 0.164793E+09 | 5231049.65 | 0.159561E+09 | 0.00 | 0.00 |
June | 0.415983E+09 | 202273.58 | 0.150429E+09 | 313133.51 | 0.150116E+09 | 0.00 | 0.00 |
July | 0.460971E+09 | 1268640.48 | 0.166328E+09 | 1396637.42 | 0.164931E+09 | 0.00 | 0.00 |
August | 0.496103E+09 | 60393.46 | 0.186985E+09 | 13983093.38 | 0.173002E+09 | 0.00 | 0.00 |
September | 0.572119E+09 | 1862908.71 | 0.234655E+09 | 57970621.67 | 0.176684E+09 | 0.00 | 0.00 |
October | 0.687831E+09 | 6766448.79 | 0.336520E+09 | 0.160011E+09 | 0.176509E+09 | 0.00 | 0.00 |
November | 0.657776E+09 | 46576805.56 | 0.368931E+09 | 0.207056E+09 | 0.161876E+09 | 0.00 | 0.00 |
December | 0.667492E+09 | 0.111524E+09 | 0.415981E+09 | 0.262654E+09 | 0.153327E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.652456E+10 | 0.504205E+09 | 0.329873E+10 | 0.134837E+10 | 0.195036E+10 | 0.00 | 0.00 |
Minimum of Months | 0.406323E+09 | 60393.46 | 0.150429E+09 | 313133.51 | 0.148367E+09 | 0.00 | 0.00 |
Maximum of Months | 0.687831E+09 | 0.136810E+09 | 0.431464E+09 | 0.280553E+09 | 0.176684E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.598611E+09 | 0.736856E+09 | 0.437348E+09 | 0.00 | 0.437348E+09 | 0.00 | 0.00 |
February | 0.779193E+09 | 0.528952E+09 | 0.467574E+09 | 0.00 | 0.467574E+09 | 0.00 | 0.00 |
March | 0.102416E+10 | 0.445633E+09 | 0.617532E+09 | 10897.63 | 0.617521E+09 | 0.00 | 0.00 |
April | 0.136484E+10 | 0.196658E+09 | 0.671400E+09 | 3833201.69 | 0.667567E+09 | 0.00 | 0.00 |
May | 0.192233E+10 | 43008478.21 | 0.787833E+09 | 32274777.04 | 0.755559E+09 | 0.00 | 0.00 |
June | 0.216805E+10 | 7482274.71 | 0.817192E+09 | 58774166.93 | 0.758418E+09 | 0.00 | 0.00 |
July | 0.232045E+10 | 20120539.56 | 0.855382E+09 | 42575003.16 | 0.812807E+09 | 0.00 | 0.00 |
August | 0.206294E+10 | 6743098.86 | 0.757519E+09 | 7941043.40 | 0.749578E+09 | 0.00 | 0.00 |
September | 0.184015E+10 | 34600113.66 | 0.649147E+09 | 149971.41 | 0.648997E+09 | 0.00 | 0.00 |
October | 0.146381E+10 | 64657980.60 | 0.561680E+09 | 0.00 | 0.561680E+09 | 0.00 | 0.00 |
November | 0.102167E+10 | 0.278102E+09 | 0.472630E+09 | 0.00 | 0.472630E+09 | 0.00 | 0.00 |
December | 0.670504E+09 | 0.600315E+09 | 0.432591E+09 | 0.00 | 0.432591E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.172367E+11 | 0.296313E+10 | 0.752783E+10 | 0.145559E+09 | 0.738227E+10 | 0.00 | 0.00 |
Minimum of Months | 0.598611E+09 | 6743098.86 | 0.432591E+09 | 0.00 | 0.432591E+09 | 0.00 | 0.00 |
Maximum of Months | 0.232045E+10 | 0.736856E+09 | 0.855382E+09 | 58774166.93 | 0.812807E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.577903E+09 | 0.774388E+09 | 0.437348E+09 | 0.00 | 0.437348E+09 | 0.00 | 0.00 |
February | 0.755748E+09 | 0.561450E+09 | 0.467574E+09 | 0.00 | 0.467574E+09 | 0.00 | 0.00 |
March | 0.993551E+09 | 0.478621E+09 | 0.617532E+09 | 10897.63 | 0.617521E+09 | 0.00 | 0.00 |
April | 0.132984E+10 | 0.222497E+09 | 0.671400E+09 | 3833201.69 | 0.667567E+09 | 0.00 | 0.00 |
May | 0.187185E+10 | 53467106.42 | 0.787833E+09 | 32274777.04 | 0.755559E+09 | 0.00 | 0.00 |
June | 0.211660E+10 | 10428410.16 | 0.817192E+09 | 58774166.93 | 0.758418E+09 | 0.00 | 0.00 |
July | 0.227297E+10 | 24895277.58 | 0.855382E+09 | 42575003.16 | 0.812807E+09 | 0.00 | 0.00 |
August | 0.201041E+10 | 9976421.44 | 0.757519E+09 | 7941043.40 | 0.749578E+09 | 0.00 | 0.00 |
September | 0.179782E+10 | 43715557.27 | 0.649147E+09 | 149971.41 | 0.648997E+09 | 0.00 | 0.00 |
October | 0.142021E+10 | 77175912.54 | 0.561680E+09 | 0.00 | 0.561680E+09 | 0.00 | 0.00 |
November | 0.985321E+09 | 0.299191E+09 | 0.472630E+09 | 0.00 | 0.472630E+09 | 0.00 | 0.00 |
December | 0.647096E+09 | 0.635738E+09 | 0.432591E+09 | 0.00 | 0.432591E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.167793E+11 | 0.319154E+10 | 0.752783E+10 | 0.145559E+09 | 0.738227E+10 | 0.00 | 0.00 |
Minimum of Months | 0.577903E+09 | 9976421.44 | 0.432591E+09 | 0.00 | 0.432591E+09 | 0.00 | 0.00 |
Maximum of Months | 0.227297E+10 | 0.774388E+09 | 0.855382E+09 | 58774166.93 | 0.812807E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.143596E+10 | 0.645817E+09 | 0.918453E+09 | 0.460513E+09 | 0.457941E+09 | 0.00 | 0.00 |
February | 0.146592E+10 | 0.489103E+09 | 0.889924E+09 | 0.406836E+09 | 0.483088E+09 | 0.00 | 0.00 |
March | 0.177523E+10 | 0.417621E+09 | 0.108266E+10 | 0.458255E+09 | 0.624410E+09 | 0.00 | 0.00 |
April | 0.201362E+10 | 0.223870E+09 | 0.106984E+10 | 0.401679E+09 | 0.668156E+09 | 0.00 | 0.00 |
May | 0.221762E+10 | 69844011.66 | 0.104091E+10 | 0.334413E+09 | 0.706498E+09 | 0.00 | 0.00 |
June | 0.231589E+10 | 16225171.44 | 0.995419E+09 | 0.306472E+09 | 0.688947E+09 | 0.00 | 0.00 |
July | 0.255696E+10 | 30914393.75 | 0.106075E+10 | 0.304791E+09 | 0.755955E+09 | 0.00 | 0.00 |
August | 0.231287E+10 | 19488691.23 | 0.989915E+09 | 0.263182E+09 | 0.726733E+09 | 0.00 | 0.00 |
September | 0.227503E+10 | 44663434.76 | 0.955897E+09 | 0.293453E+09 | 0.662444E+09 | 0.00 | 0.00 |
October | 0.209428E+10 | 85060485.37 | 0.977720E+09 | 0.395794E+09 | 0.581926E+09 | 0.00 | 0.00 |
November | 0.160884E+10 | 0.264971E+09 | 0.845480E+09 | 0.350811E+09 | 0.494669E+09 | 0.00 | 0.00 |
December | 0.128484E+10 | 0.541974E+09 | 0.785373E+09 | 0.334964E+09 | 0.450409E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.233571E+11 | 0.284955E+10 | 0.116123E+11 | 0.431116E+10 | 0.730118E+10 | 0.00 | 0.00 |
Minimum of Months | 0.128484E+10 | 16225171.44 | 0.785373E+09 | 0.263182E+09 | 0.450409E+09 | 0.00 | 0.00 |
Maximum of Months | 0.255696E+10 | 0.645817E+09 | 0.108266E+10 | 0.460513E+09 | 0.755955E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.200147E+10 | 0.531123E+09 | 0.124824E+10 | 0.714162E+09 | 0.534077E+09 | 0.00 | 0.00 |
February | 0.179951E+10 | 0.364985E+09 | 0.103603E+10 | 0.498067E+09 | 0.537961E+09 | 0.00 | 0.00 |
March | 0.172199E+10 | 0.286772E+09 | 0.960999E+09 | 0.309798E+09 | 0.651201E+09 | 0.00 | 0.00 |
April | 0.158922E+10 | 0.102122E+09 | 0.750094E+09 | 0.107821E+09 | 0.642273E+09 | 0.00 | 0.00 |
May | 0.177948E+10 | 16554625.41 | 0.689559E+09 | 24379771.54 | 0.665179E+09 | 0.00 | 0.00 |
June | 0.185701E+10 | 1256803.30 | 0.663060E+09 | 20944997.28 | 0.642115E+09 | 0.00 | 0.00 |
July | 0.200411E+10 | 7021417.13 | 0.716623E+09 | 18150009.08 | 0.698473E+09 | 0.00 | 0.00 |
August | 0.203393E+10 | 314348.17 | 0.735659E+09 | 38316912.53 | 0.697342E+09 | 0.00 | 0.00 |
September | 0.214094E+10 | 8422915.67 | 0.819855E+09 | 0.147619E+09 | 0.672236E+09 | 0.00 | 0.00 |
October | 0.234132E+10 | 25570185.81 | 0.104917E+10 | 0.407317E+09 | 0.641857E+09 | 0.00 | 0.00 |
November | 0.211873E+10 | 0.178148E+09 | 0.110115E+10 | 0.527071E+09 | 0.574082E+09 | 0.00 | 0.00 |
December | 0.200734E+10 | 0.430057E+09 | 0.120719E+10 | 0.668601E+09 | 0.538594E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.233950E+11 | 0.195235E+10 | 0.109776E+11 | 0.348225E+10 | 0.749539E+10 | 0.00 | 0.00 |
Minimum of Months | 0.158922E+10 | 314348.17 | 0.663060E+09 | 18150009.08 | 0.534077E+09 | 0.00 | 0.00 |
Maximum of Months | 0.234132E+10 | 0.531123E+09 | 0.124824E+10 | 0.714162E+09 | 0.698473E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 19.42 | 15.96 | 13.59 | 3.30 | 9.49 | 57.21 | 169.93 | 0.03 |
February | 20.87 | 16.70 | 13.89 | 5.53 | 11.19 | 68.99 | 182.59 | 0.00 |
March | 21.57 | 17.63 | 15.09 | 5.59 | 12.13 | 85.97 | 199.13 | 0.00 |
April | 24.11 | 19.68 | 17.40 | 4.69 | 15.31 | 97.05 | 212.67 | 0.01 |
May | 26.41 | 22.40 | 20.67 | 5.05 | 18.50 | 110.67 | 177.92 | 0.00 |
June | 27.68 | 24.06 | 22.67 | 3.87 | 20.33 | 120.35 | 147.07 | 0.00 |
July | 28.13 | 24.25 | 22.77 | 2.86 | 20.30 | 124.71 | 163.26 | 0.00 |
August | 27.97 | 24.38 | 23.03 | 3.45 | 20.36 | 120.27 | 145.14 | 0.08 |
September | 27.49 | 23.91 | 22.56 | 3.39 | 20.13 | 107.67 | 134.94 | 0.00 |
October | 26.35 | 22.68 | 21.10 | 3.72 | 17.49 | 81.44 | 160.40 | 0.04 |
November | 23.59 | 20.24 | 18.46 | 4.39 | 14.74 | 70.67 | 140.11 | 0.00 |
December | 20.30 | 17.47 | 15.75 | 3.70 | 12.21 | 59.50 | 147.31 | 0.00 |
Annual Sum or Average | 24.51 | 20.80 | 18.94 | 4.12 | 16.04 | 92.16 | 164.97 | 0.01 |
Minimum of Months | 19.42 | 15.96 | 13.59 | 2.86 | 9.49 | 57.21 | 134.94 | 0.00 |
Maximum of Months | 28.13 | 24.38 | 23.03 | 5.59 | 20.36 | 124.71 | 212.67 | 0.08 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 28.90 | 02-JAN-14:20 | 24.35 | 22.57 | 2.37 | 19.46 | 142.33 | 666.50 |
February | 29.40 | 11-FEB-13:00 | 24.15 | 22.20 | 4.60 | 20.75 | 178.50 | 682.00 |
March | 29.40 | 13-MAR-15:00 | 22.41 | 19.40 | 6.20 | 21.27 | 178.00 | 499.00 |
April | 32.20 | 17-APR-14:00 | 19.76 | 12.80 | 5.20 | 21.27 | 367.00 | 219.50 |
May | 34.40 | 22-MAY-12:00 | 23.24 | 18.30 | 5.70 | 25.99 | 382.50 | 457.50 |
June | 32.20 | 11-JUN-12:00 | 23.83 | 20.60 | 3.60 | 23.15 | 181.50 | 762.50 |
July | 35.60 | 29-JUL-15:00 | 24.39 | 20.00 | 3.60 | 25.66 | 281.50 | 374.50 |
August | 33.90 | 23-AUG-12:00 | 25.44 | 22.20 | 5.70 | 24.50 | 261.50 | 640.00 |
September | 32.20 | 08-SEP-14:00 | 23.42 | 20.00 | 2.10 | 21.61 | 221.50 | 576.00 |
October | 32.20 | 09-OCT-10:00 | 23.83 | 20.60 | 3.10 | 25.16 | 286.50 | 457.50 |
November | 30.00 | 17-NOV-14:00 | 22.20 | 18.90 | 4.10 | 19.35 | 178.50 | 412.50 |
December | 28.90 | 10-DEC-14:20 | 22.91 | 20.40 | 7.87 | 19.82 | 162.67 | 585.17 |
Annual Sum or Average | ||||||||
Minimum of Months | 28.90 | 19.76 | 12.80 | 2.10 | 19.35 | 142.33 | 219.50 | |
Maximum of Months | 35.60 | 25.44 | 22.57 | 7.87 | 25.99 | 382.50 | 762.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 9.40 | 25-JAN-04:00 | 4.59 | -1.7 | 3.10 | -7.3 | 0.00 | 0.00 |
February | 5.00 | 04-FEB-06:00 | 1.99 | -2.8 | 5.70 | -11.9 | 0.00 | 0.00 |
March | 6.70 | 16-MAR-04:00 | 4.49 | 1.70 | 4.60 | -9.2 | 0.00 | 0.00 |
April | 14.40 | 02-APR-05:49 | 13.38 | 12.70 | 1.60 | 0.69 | 0.00 | 0.00 |
May | 20.60 | 01-MAY-04:00 | 19.45 | 18.90 | 1.00 | 7.95 | 0.00 | 0.00 |
June | 22.80 | 05-JUN-14:00 | 20.57 | 19.40 | 2.10 | 18.46 | 245.00 | 55.00 |
July | 22.80 | 02-JUL-15:00 | 21.59 | 21.10 | 4.60 | 20.92 | 155.00 | 8.50 |
August | 22.20 | 12-AUG-06:00 | 21.85 | 21.70 | 2.60 | 20.40 | 65.50 | 0.00 |
September | 22.20 | 05-SEP-05:00 | 21.37 | 21.10 | 2.60 | 13.54 | 0.00 | 0.00 |
October | 21.10 | 28-OCT-02:00 | 20.29 | 20.00 | 2.60 | 8.54 | 0.00 | 0.00 |
November | 10.00 | 27-NOV-02:00 | 8.82 | 7.80 | 3.10 | -4.6 | 0.00 | 0.00 |
December | 7.80 | 15-DEC-05:40 | 5.61 | 3.13 | 6.37 | -7.8 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 5.00 | 1.99 | -2.8 | 1.00 | -11.9 | 0.00 | 0.00 | |
Maximum of Months | 22.80 | 21.85 | 21.70 | 6.37 | 20.92 | 245.00 | 55.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 24.83 | 02-JAN-13:00 | 28.90 | 23.30 | 1.50 | 19.87 | 151.00 | 613.50 |
February | 24.15 | 11-FEB-13:00 | 29.40 | 22.20 | 4.60 | 20.75 | 178.50 | 682.00 |
March | 23.83 | 14-MAR-09:00 | 26.70 | 22.80 | 11.30 | 19.52 | 243.50 | 478.00 |
April | 24.58 | 01-APR-15:00 | 28.30 | 23.30 | 3.60 | 16.30 | 93.50 | 759.50 |
May | 26.05 | 28-MAY-14:00 | 28.90 | 25.00 | 5.20 | 25.66 | 289.00 | 98.50 |
June | 26.06 | 28-JUN-11:00 | 28.90 | 25.00 | 1.50 | 22.98 | 404.50 | 373.50 |
July | 26.39 | 12-JUL-10:00 | 30.60 | 25.00 | 4.60 | 23.82 | 287.50 | 574.00 |
August | 26.46 | 21-AUG-15:00 | 32.20 | 24.40 | 3.60 | 24.50 | 205.50 | 366.00 |
September | 26.31 | 22-SEP-16:00 | 30.00 | 25.00 | 6.20 | 28.91 | 54.00 | 21.00 |
October | 26.52 | 01-OCT-11:00 | 29.40 | 25.60 | 6.20 | 28.43 | 283.50 | 0.00 |
November | 25.31 | 04-NOV-13:00 | 27.80 | 24.40 | 2.10 | 26.48 | 199.00 | 3.00 |
December | 24.31 | 24-DEC-14:00 | 27.20 | 23.30 | 2.10 | 23.66 | 201.50 | 114.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 23.83 | 26.70 | 22.20 | 1.50 | 16.30 | 54.00 | 0.00 | |
Maximum of Months | 26.52 | 32.20 | 25.60 | 11.30 | 28.91 | 404.50 | 759.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 23.30 | 02-JAN-13:00 | 28.90 | 24.83 | 1.50 | 19.87 | 151.00 | 613.50 |
February | 22.80 | 11-FEB-16:19 | 27.60 | 24.09 | 5.70 | 18.94 | 101.33 | 565.33 |
March | 22.80 | 14-MAR-09:20 | 25.57 | 23.60 | 9.63 | 22.18 | 176.17 | 527.17 |
April | 23.30 | 01-APR-14:00 | 27.80 | 24.57 | 5.70 | 15.76 | 108.00 | 831.00 |
May | 25.00 | 28-MAY-12:00 | 27.80 | 25.74 | 6.70 | 22.98 | 249.50 | 244.50 |
June | 25.00 | 06-JUN-18:00 | 27.20 | 25.59 | 3.60 | 23.99 | 17.50 | 0.00 |
July | 25.00 | 12-JUL-03:00 | 27.20 | 25.59 | 1.50 | 19.70 | 0.00 | 0.00 |
August | 25.60 | 21-AUG-11:00 | 28.90 | 26.35 | 2.60 | 23.15 | 567.00 | 173.50 |
September | 25.00 | 22-SEP-00:00 | 27.80 | 25.31 | 3.60 | 20.92 | 0.00 | 0.00 |
October | 25.60 | 01-OCT-11:00 | 29.40 | 26.52 | 6.20 | 28.43 | 283.50 | 0.00 |
November | 24.40 | 05-NOV-01:19 | 26.10 | 24.93 | 2.03 | 16.37 | 0.00 | 0.00 |
December | 23.90 | 24-DEC-08:00 | 23.90 | 23.90 | 2.60 | 17.75 | 168.50 | 167.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 22.80 | 23.90 | 23.60 | 1.50 | 15.76 | 0.00 | 0.00 | |
Maximum of Months | 25.60 | 29.40 | 26.52 | 9.63 | 28.43 | 567.00 | 831.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 24.73 | 28.77 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 25.06 | 35.04 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 26.11 | 42.49 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 27.63 | 49.05 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 29.20 | 48.15 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 30.41 | 45.99 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 30.92 | 49.88 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 30.58 | 45.60 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 29.50 | 40.49 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 27.97 | 35.89 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 26.40 | 29.31 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 25.21 | 26.63 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 27.83 | 39.80 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 24.73 | 26.63 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 30.92 | 49.88 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH BOOSTER E WATER HEATER
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.770695E+10 | -0.754278E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164172207.9 | 81.21 | 0.00 | 0.00 |
February | 0.696417E+10 | -0.681597E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -148202007.5 | 81.21 | 0.00 | 0.00 |
March | 0.770546E+10 | -0.754146E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164000588.0 | 81.21 | 0.00 | 0.00 |
April | 0.746716E+10 | -0.730860E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -158568777.9 | 81.21 | 0.00 | 0.00 |
May | 0.770651E+10 | -0.754279E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -163713757.7 | 81.21 | 0.00 | 0.00 |
June | 0.745886E+10 | -0.730053E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -158328113.3 | 81.21 | 0.00 | 0.00 |
July | 0.771447E+10 | -0.755085E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -163620586.0 | 81.21 | 0.00 | 0.00 |
August | 0.770646E+10 | -0.754281E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -163656269.4 | 81.21 | 0.00 | 0.00 |
September | 0.746830E+10 | -0.730993E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -158364402.7 | 81.21 | 0.00 | 0.00 |
October | 0.770519E+10 | -0.754143E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -163753837.7 | 81.21 | 0.00 | 0.00 |
November | 0.745108E+10 | -0.729244E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -158644553.7 | 81.21 | 0.00 | 0.00 |
December | 0.771501E+10 | -0.755086E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164155210.9 | 81.21 | 0.00 | 0.00 |
Annual Sum or Average | 0.907696E+11 | -0.888404E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.192918E+10 | 81.21 | 0.00 | 0.00 |
Minimum of Months | 0.696417E+10 | -0.755086E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -164172207.9 | 81.21 | 0.00 | 0.00 |
Maximum of Months | 0.771501E+10 | -0.681597E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -148202007.5 | 81.21 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH LAUNDRY G WATER HEATER
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.974759E+11 | -0.956666E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.180925E+10 | 81.26 | 0.00 | 0.00 |
February | 0.875331E+11 | -0.858966E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.163648E+10 | 81.25 | 0.00 | 0.00 |
March | 0.951460E+11 | -0.933318E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.181415E+10 | 81.25 | 0.00 | 0.00 |
April | 0.895805E+11 | -0.878242E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.175632E+10 | 81.25 | 0.00 | 0.00 |
May | 0.898951E+11 | -0.880808E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.181430E+10 | 81.25 | 0.00 | 0.00 |
June | 0.850167E+11 | -0.832614E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.175528E+10 | 81.24 | 0.00 | 0.00 |
July | 0.869910E+11 | -0.851793E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.181170E+10 | 81.23 | 0.00 | 0.00 |
August | 0.875554E+11 | -0.857456E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.180977E+10 | 81.25 | 0.00 | 0.00 |
September | 0.864983E+11 | -0.847484E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.174988E+10 | 81.24 | 0.00 | 0.00 |
October | 0.919776E+11 | -0.901701E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.180750E+10 | 81.25 | 0.00 | 0.00 |
November | 0.915870E+11 | -0.898383E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.174873E+10 | 81.25 | 0.00 | 0.00 |
December | 0.966521E+11 | -0.948449E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.180722E+10 | 81.25 | 0.00 | 0.00 |
Annual Sum or Average | 0.108591E+13 | -0.106459E+13 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.213206E+11 | 81.25 | 0.00 | 0.00 |
Minimum of Months | 0.850167E+11 | -0.956666E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.181430E+10 | 81.23 | 0.00 | 0.00 |
Maximum of Months | 0.974759E+11 | -0.832614E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.163648E+10 | 81.26 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.516122E+11 | -0.500351E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.157707E+10 | 58.98 | 0.00 | 0.00 |
February | 0.461879E+11 | -0.447600E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.142791E+10 | 58.98 | 0.00 | 0.00 |
March | 0.496483E+11 | -0.480641E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.158416E+10 | 58.98 | 0.00 | 0.00 |
April | 0.458655E+11 | -0.443315E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.153399E+10 | 58.98 | 0.00 | 0.00 |
May | 0.450943E+11 | -0.435099E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.158442E+10 | 58.98 | 0.00 | 0.00 |
June | 0.419458E+11 | -0.404129E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.153290E+10 | 58.97 | 0.00 | 0.00 |
July | 0.425608E+11 | -0.409791E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.158169E+10 | 58.97 | 0.00 | 0.00 |
August | 0.430901E+11 | -0.415120E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.157804E+10 | 58.97 | 0.00 | 0.00 |
September | 0.432038E+11 | -0.416784E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.152537E+10 | 58.98 | 0.00 | 0.00 |
October | 0.468636E+11 | -0.452886E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.157501E+10 | 58.98 | 0.00 | 0.00 |
November | 0.475758E+11 | -0.460522E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.152358E+10 | 58.98 | 0.00 | 0.00 |
December | 0.508969E+11 | -0.493222E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.157469E+10 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.554545E+12 | -0.535946E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.185988E+11 | 58.98 | 0.00 | 0.00 |
Minimum of Months | 0.419458E+11 | -0.500351E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.158442E+10 | 58.97 | 0.00 | 0.00 |
Maximum of Months | 0.516122E+11 | -0.404129E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.142791E+10 | 58.98 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 287.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 304.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 362.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 357.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 389.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 388.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 403.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 348.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 349.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 323.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 314.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 282.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4111.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 282.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 403.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 252198.49 | 391.22 | 11-JAN-12:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 76023.04 | 126.71 | 28-FEB-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 3382.24 | 5.64 | 01-MAR-10:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 675292.53 | 1125.49 | 15-NOV-09:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1006896.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 675292.53 | 1125.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BASEMENT VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.139949E+10 | 7650.21 | 02-JAN-11:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.309514E+10 | 9309.42 | 27-FEB-11:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.637394E+10 | 9508.75 | 27-MAR-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.787060E+10 | 9568.70 | 15-APR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.723226E+10 | 9570.47 | 31-MAY-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.659619E+10 | 9592.81 | 11-JUN-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.533477E+10 | 9611.28 | 23-JUL-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.307017E+10 | 9080.26 | 01-AUG-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.209485E+10 | 8130.30 | 11-SEP-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.141170E+10 | 6815.43 | 03-OCT-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.756992E+09 | 6138.05 | 04-NOV-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.697012E+09 | 6274.71 | 10-DEC-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.459331E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.697012E+09 | 6138.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.787060E+10 | 9611.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.108222E+10 | 1640.87 | 26-JAN-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.790755E+09 | 2030.76 | 04-FEB-07:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.796413E+09 | 1894.98 | 16-MAR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.495300E+09 | 1123.42 | 19-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.245533E+09 | 940.31 | 27-MAY-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.114366E+09 | 844.97 | 22-JUN-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 57133174.25 | 617.66 | 17-JUL-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.128413E+09 | 1101.71 | 28-AUG-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 76482989.04 | 647.67 | 26-SEP-07:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.100522E+09 | 762.28 | 31-OCT-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.429425E+09 | 1526.34 | 13-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.942273E+09 | 1713.88 | 27-DEC-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.525883E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 57133174.25 | 617.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.108222E+10 | 2030.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_2_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.636489E+09 | 1118.12 | 31-JAN-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.495128E+09 | 1062.98 | 03-FEB-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.522829E+09 | 1195.49 | 21-MAR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.399297E+09 | 1074.35 | 26-APR-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.356624E+09 | 1117.53 | 01-MAY-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.317648E+09 | 1001.72 | 13-JUN-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.276361E+09 | 926.20 | 03-JUL-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.294142E+09 | 1006.68 | 29-AUG-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.234253E+09 | 911.04 | 06-SEP-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.246813E+09 | 872.23 | 02-OCT-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.352501E+09 | 999.26 | 27-NOV-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.537868E+09 | 1051.23 | 21-DEC-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.466995E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.234253E+09 | 872.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.636489E+09 | 1195.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: MECH_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.152395E+10 | 1537.05 | 25-JAN-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.115542E+10 | 1534.72 | 04-FEB-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.112909E+10 | 1548.79 | 21-MAR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.676269E+09 | 1171.34 | 19-APR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.299234E+09 | 1087.62 | 01-MAY-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.115772E+09 | 746.64 | 19-JUN-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 85416577.90 | 700.09 | 03-JUL-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.207393E+09 | 1001.68 | 29-AUG-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167646E+09 | 817.33 | 05-SEP-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.355266E+09 | 952.95 | 28-OCT-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.713603E+09 | 1298.29 | 13-NOV-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.127653E+10 | 1467.88 | 15-DEC-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.770559E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 85416577.90 | 700.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.152395E+10 | 1548.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: STORAGE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.978621E+09 | 822.07 | 25-JAN-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.741525E+09 | 820.83 | 04-FEB-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.727035E+09 | 828.37 | 21-MAR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.436461E+09 | 627.09 | 19-APR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.184810E+09 | 547.87 | 01-MAY-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 65560852.41 | 391.88 | 19-JUN-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 39966259.11 | 344.89 | 03-JUL-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.119403E+09 | 484.81 | 29-AUG-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 95061787.30 | 441.46 | 05-SEP-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.214901E+09 | 470.18 | 28-OCT-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.462226E+09 | 686.61 | 13-NOV-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.827285E+09 | 809.58 | 15-DEC-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.489286E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 39966259.11 | 344.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.978621E+09 | 828.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LAUNDRY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.127679E+11 | 12499.27 | 02-JAN-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.115369E+11 | 12543.98 | 11-FEB-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.127636E+11 | 12558.78 | 27-MAR-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.125991E+11 | 12637.97 | 15-APR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.130084E+11 | 12640.31 | 31-MAY-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.126424E+11 | 12669.82 | 11-JUN-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.133924E+11 | 12694.23 | 23-JUL-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.131703E+11 | 12665.44 | 19-AUG-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.127088E+11 | 12658.51 | 24-SEP-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.129492E+11 | 12647.34 | 07-OCT-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.121702E+11 | 12547.98 | 03-NOV-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.127628E+11 | 12544.36 | 09-DEC-11:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.152472E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.115369E+11 | 12499.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.133924E+11 | 12694.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAFE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.912121E+09 | 4913.37 | 30-JAN-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.700052E+09 | 4549.48 | 06-FEB-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.107833E+10 | 5391.36 | 16-MAR-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.924914E+09 | 4681.70 | 28-APR-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.882107E+09 | 4459.03 | 25-MAY-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.772408E+09 | 4361.60 | 22-JUN-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.526490E+09 | 4021.93 | 17-JUL-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.545745E+09 | 5006.69 | 28-AUG-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.223691E+09 | 3829.32 | 05-SEP-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.195668E+09 | 4117.47 | 31-OCT-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.412005E+09 | 4913.48 | 24-NOV-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.897430E+09 | 4947.26 | 28-DEC-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.807096E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.195668E+09 | 3829.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.107833E+10 | 5391.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LOBBY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.467458E+10 | 16519.06 | 18-JAN-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.394724E+10 | 17153.25 | 06-FEB-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.542986E+10 | 18878.73 | 20-MAR-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.494683E+10 | 16695.31 | 26-APR-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.456742E+10 | 17488.49 | 01-MAY-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.386442E+10 | 16199.36 | 13-JUN-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.356592E+10 | 15396.97 | 07-JUL-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.346371E+10 | 15193.12 | 07-AUG-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.231685E+10 | 14711.08 | 05-SEP-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.193699E+10 | 13854.54 | 02-OCT-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.256256E+10 | 15301.26 | 27-NOV-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.414701E+10 | 17341.88 | 21-DEC-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.454234E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.193699E+10 | 13854.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.542986E+10 | 18878.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.327948E+09 | 3694.15 | 26-JAN-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.326168E+09 | 4865.48 | 04-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.277364E+09 | 4219.09 | 20-MAR-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 583038.44 | 561.55 | 13-NOV-07:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.427735E+09 | 3823.26 | 21-DEC-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.135980E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.427735E+09 | 4865.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.279335E+10 | 3960.72 | 25-JAN-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.183106E+10 | 4642.07 | 04-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.160896E+10 | 4256.56 | 16-MAR-06:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.460010E+09 | 2212.29 | 19-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 62803787.38 | 1627.80 | 01-MAY-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 19915836.49 | 1283.83 | 28-AUG-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 4997211.05 | 507.46 | 26-SEP-07:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 26220340.42 | 919.73 | 31-OCT-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.833416E+09 | 3386.76 | 27-NOV-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.233358E+10 | 3836.51 | 15-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.997432E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.279335E+10 | 4642.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BANQUET_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.118465E+10 | 6425.62 | 26-JAN-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.786014E+09 | 6078.65 | 03-FEB-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.825128E+09 | 7010.65 | 16-MAR-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.408882E+09 | 5761.81 | 03-APR-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.235240E+09 | 5289.17 | 02-MAY-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.158641E+09 | 4533.30 | 13-JUN-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.139517E+09 | 4316.61 | 18-JUL-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.198257E+09 | 4549.92 | 30-AUG-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.217267E+09 | 4927.45 | 26-SEP-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.339932E+09 | 5237.32 | 20-OCT-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.567506E+09 | 5770.42 | 13-NOV-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.100980E+10 | 6475.97 | 15-DEC-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.607084E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.139517E+09 | 4316.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.118465E+10 | 7010.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: DINING_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.777972E+09 | 6048.70 | 26-JAN-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.478021E+09 | 5568.97 | 03-FEB-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.522821E+09 | 6629.88 | 16-MAR-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.223821E+09 | 5179.05 | 03-APR-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.133502E+09 | 4679.37 | 02-MAY-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.102489E+09 | 4343.26 | 13-JUN-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 97250085.31 | 4132.67 | 25-JUL-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.120174E+09 | 4358.00 | 31-AUG-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.133837E+09 | 4551.44 | 26-SEP-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.204370E+09 | 4892.72 | 20-OCT-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.334640E+09 | 5403.64 | 13-NOV-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.667050E+09 | 6110.39 | 15-DEC-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.379595E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 97250085.31 | 4132.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.777972E+09 | 6629.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: KITCHEN_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.778503E+09 | 3868.65 | 25-JAN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.616918E+09 | 4331.51 | 04-FEB-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.535062E+09 | 3868.78 | 16-MAR-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.300051E+09 | 2710.84 | 19-APR-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.169172E+09 | 2024.82 | 01-MAY-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 77510333.73 | 1355.81 | 19-JUN-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 78896804.24 | 1355.81 | 15-JUL-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.102763E+09 | 1622.29 | 29-AUG-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.101669E+09 | 1463.87 | 06-SEP-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.178733E+09 | 1674.16 | 28-OCT-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.412839E+09 | 3510.38 | 27-NOV-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.698823E+09 | 3869.07 | 21-DEC-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.405094E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 77510333.73 | 1355.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.778503E+09 | 4331.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: FLR_3_DOAS HEATING COIL
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 16088.21 | 0.55 | 03-JAN-09:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 10164.89 | 0.54 | 24-FEB-18:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 10841.74 | 4.55 | 02-MAR-16:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 10483.25 | 0.54 | 30-APR-07:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 9159.30 | 0.55 | 11-MAY-20:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6740.83 | 0.54 | 20-JUN-20:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 8790.63 | 0.54 | 29-JUL-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 5251.23 | 0.54 | 20-AUG-20:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 9623.38 | 0.54 | 04-SEP-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 7210.07 | 0.55 | 26-OCT-05:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 12189.19 | 0.54 | 01-NOV-16:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 15792.48 | 0.54 | 01-DEC-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 122335.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 5251.23 | 0.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16088.21 | 4.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 44069758.06 | 2542.22 | 25-JAN-16:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 60367991.06 | 2944.00 | 03-FEB-16:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 34090633.07 | 3762.67 | 16-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 4882101.47 | 2677.80 | 29-APR-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3407825.82 | 2785.93 | 08-MAY-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 1884180.83 | 2255.73 | 19-JUN-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 467990.42 | 1614.76 | 03-JUL-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 2130807.12 | 2310.31 | 29-AUG-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2188591.24 | 2106.57 | 28-SEP-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 3250616.90 | 2712.57 | 18-OCT-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 14656381.22 | 2489.92 | 27-NOV-09:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 53915591.21 | 2736.92 | 28-DEC-16:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.225312E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 467990.42 | 1614.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 60367991.06 | 3762.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.105859E+09 | 3775.70 | 25-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 92736206.54 | 3788.51 | 04-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 55463987.68 | 3797.22 | 16-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5133334.84 | 2646.09 | 29-APR-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3395843.44 | 2842.75 | 08-MAY-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 1531000.80 | 2148.81 | 19-JUN-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 267373.18 | 1406.93 | 03-JUL-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 2367438.21 | 2287.59 | 29-AUG-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2803186.54 | 2175.63 | 07-SEP-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5437431.97 | 2762.97 | 18-OCT-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 25660037.86 | 2935.63 | 28-NOV-19:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.114953E+09 | 3768.38 | 15-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.415607E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 267373.18 | 1406.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.114953E+09 | 3797.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 82664286.91 | 21830.44 | 24-JAN-16:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 92300133.80 | 21770.85 | 03-FEB-16:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 69788894.48 | 21815.37 | 19-MAR-15:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 40058958.48 | 21821.55 | 20-APR-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 20751402.58 | 16532.94 | 11-MAY-08:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 26648236.23 | 15235.94 | 09-JUN-08:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 26111861.57 | 12941.00 | 12-JUL-08:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 20446252.15 | 15703.12 | 12-AUG-18:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6909071.14 | 8799.75 | 11-SEP-08:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 33918527.13 | 14700.87 | 10-OCT-18:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 58904476.33 | 21626.33 | 15-NOV-09:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 73228066.31 | 21843.04 | 15-DEC-16:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.551730E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 6909071.14 | 8799.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 92300133.80 | 21843.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 51508306.23 | 2790.09 | 25-JAN-16:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 58373055.27 | 2232.83 | 19-FEB-09:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 30027359.90 | 3062.44 | 16-MAR-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 804085.23 | 2624.61 | 30-APR-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 421227.38 | 2177.54 | 25-MAY-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 123019.48 | 1230.19 | 15-JUN-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 274333.01 | 2298.83 | 28-AUG-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 173171.27 | 1333.45 | 31-OCT-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 13182313.09 | 1789.98 | 27-NOV-19:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 64317039.17 | 2501.47 | 20-DEC-19:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.219204E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 64317039.17 | 3062.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.116279E+09 | 3075.49 | 24-JAN-16:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 87068598.94 | 2658.54 | 03-FEB-16:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 47130942.14 | 2743.91 | 16-MAR-18:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 939065.85 | 2593.60 | 30-APR-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 483800.67 | 2414.11 | 25-MAY-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 126521.31 | 1265.21 | 15-JUN-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 333587.02 | 2249.83 | 28-AUG-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 382485.15 | 2098.55 | 18-OCT-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 22729377.54 | 2694.09 | 29-NOV-09:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129726E+09 | 2766.44 | 28-DEC-16:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.405199E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.129726E+09 | 3075.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 27271321.69 | 841.47 | 25-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 26891065.91 | 1140.15 | 04-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 17527491.08 | 1151.12 | 16-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 1187614.39 | 693.84 | 09-APR-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 781938.44 | 809.32 | 08-MAY-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 430544.67 | 468.73 | 22-JUN-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 107381.23 | 375.84 | 03-JUL-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 535368.47 | 580.73 | 12-AUG-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 569814.53 | 492.98 | 26-SEP-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 887539.84 | 797.21 | 18-OCT-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 8133470.63 | 621.94 | 29-NOV-09:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 29719232.03 | 1009.11 | 15-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.114043E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 107381.23 | 375.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 29719232.03 | 1151.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 56690300.28 | 1153.02 | 25-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 40591574.99 | 1158.83 | 04-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 26376275.58 | 1161.83 | 16-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 1260652.42 | 862.51 | 09-APR-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 731251.76 | 810.64 | 08-MAY-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 332934.70 | 436.45 | 19-JUN-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 71212.36 | 343.17 | 03-JUL-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 557605.02 | 592.39 | 12-AUG-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 678325.21 | 484.44 | 12-SEP-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 1321306.74 | 759.76 | 18-OCT-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 12838823.68 | 1136.42 | 13-NOV-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 56555310.61 | 1151.71 | 15-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.198006E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 71212.36 | 343.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 56690300.28 | 1161.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 10357712.65 | 2813.43 | 09-JAN-09:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 37351687.82 | 2129.69 | 04-FEB-09:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 21803445.53 | 4462.58 | 16-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 4285076.56 | 3804.93 | 21-APR-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 1097598.96 | 3459.33 | 01-MAY-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 149866.92 | 718.75 | 13-JUN-08:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 544113.96 | 3335.72 | 28-AUG-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 157626.50 | 827.84 | 15-SEP-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 60305.13 | 703.56 | 02-OCT-08:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 4132993.45 | 3257.29 | 12-NOV-16:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 11001164.85 | 2756.09 | 28-DEC-16:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 90941592.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 37351687.82 | 4462.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.588169E+12 | 0.382147E+12 | 578284.50 | 04-JAN-18:00 | 201566.05 | 0.82 |
February | 0.00 | 0.00 | 0.619413E+12 | 0.419633E+12 | 608170.58 | 11-FEB-11:35 | 310069.82 | 0.84 |
March | 0.00 | 0.00 | 0.757114E+12 | 0.501126E+12 | 596268.05 | 14-MAR-10:35 | 292360.50 | 0.86 |
April | 0.00 | 0.00 | 0.911343E+12 | 0.600445E+12 | 603046.69 | 01-APR-17:12 | 300779.69 | 1.00 |
May | 0.00 | 0.00 | 0.121938E+13 | 0.692135E+12 | 695941.36 | 28-MAY-10:35 | 323584.77 | 1.00 |
June | 0.00 | 0.00 | 0.136731E+13 | 0.705696E+12 | 702211.90 | 10-JUN-10:35 | 345048.33 | 1.00 |
July | 0.00 | 0.00 | 0.144135E+13 | 0.745435E+12 | 735216.74 | 29-JUL-10:35 | 365963.13 | 1.00 |
August | 0.00 | 0.00 | 0.144829E+13 | 0.735571E+12 | 729874.45 | 20-AUG-10:35 | 353888.61 | 1.00 |
September | 0.00 | 0.00 | 0.135531E+13 | 0.702928E+12 | 701187.95 | 06-SEP-10:35 | 331498.84 | 1.00 |
October | 0.00 | 0.00 | 0.125873E+13 | 0.692163E+12 | 719322.49 | 04-OCT-10:35 | 313962.95 | 1.00 |
November | 0.00 | 0.00 | 0.100361E+13 | 0.565162E+12 | 655600.26 | 05-NOV-10:35 | 285984.77 | 0.95 |
December | 0.00 | 0.00 | 0.733564E+12 | 0.437330E+12 | 638135.34 | 24-DEC-21:40 | 221086.16 | 0.88 |
Annual Sum or Average | 0.00 | 0.00 | 0.127036E+14 | 0.717977E+13 | 0.95 | |||
Minimum of Months | 0.00 | 0.00 | 0.588169E+12 | 0.382147E+12 | 578284.50 | 201566.05 | 0.82 | |
Maximum of Months | 0.00 | 0.00 | 0.144829E+13 | 0.745435E+12 | 735216.74 | 365963.13 | 1.00 |
Report: CoilReportMonthly
For: FLR_3_DOAS COOLING COIL
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.678594E+11 | 0.426226E+11 | 69237.45 | 07-JAN-03:30 | 25566.96 | 0.78 |
February | 0.00 | 0.00 | 0.730381E+11 | 0.481752E+11 | 68133.31 | 11-FEB-19:00 | 28972.18 | 0.84 |
March | 0.00 | 0.00 | 0.884958E+11 | 0.577357E+11 | 71113.56 | 19-MAR-07:30 | 26973.70 | 0.85 |
April | 0.00 | 0.00 | 0.104580E+12 | 0.690403E+11 | 71819.61 | 26-APR-14:30 | 28370.87 | 1.00 |
May | 0.00 | 0.00 | 0.131409E+12 | 0.777571E+11 | 80981.70 | 28-MAY-18:00 | 29080.91 | 1.00 |
June | 0.00 | 0.00 | 0.141915E+12 | 0.777573E+11 | 66955.40 | 28-JUN-12:00 | 32703.90 | 1.00 |
July | 0.00 | 0.00 | 0.147828E+12 | 0.811791E+11 | 78320.79 | 02-JUL-17:10 | 27791.28 | 1.00 |
August | 0.00 | 0.00 | 0.150052E+12 | 0.808641E+11 | 78921.70 | 28-AUG-14:10 | 28260.66 | 1.00 |
September | 0.00 | 0.00 | 0.140049E+12 | 0.773878E+11 | 64377.90 | 06-SEP-11:00 | 33420.12 | 1.00 |
October | 0.00 | 0.00 | 0.134316E+12 | 0.776926E+11 | 75497.39 | 01-OCT-07:10 | 27515.07 | 1.00 |
November | 0.00 | 0.00 | 0.111940E+12 | 0.645080E+11 | 78941.50 | 08-NOV-09:00 | 27796.02 | 0.95 |
December | 0.00 | 0.00 | 0.842073E+11 | 0.497458E+11 | 82125.11 | 24-DEC-08:17 | 27737.47 | 0.87 |
Annual Sum or Average | 0.00 | 0.00 | 0.137569E+13 | 0.804466E+12 | 0.94 | |||
Minimum of Months | 0.00 | 0.00 | 0.678594E+11 | 0.426226E+11 | 64377.90 | 25566.96 | 0.78 | |
Maximum of Months | 0.00 | 0.00 | 0.150052E+12 | 0.811791E+11 | 82125.11 | 33420.12 | 1.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.549733E+10 | 0.269398E+10 | 20555.66 | 07-JAN-09:01 | 11635.50 | 0.74 |
February | 0.00 | 0.00 | 0.632953E+10 | 0.334204E+10 | 19741.34 | 02-FEB-09:02 | 11826.15 | 0.80 |
March | 0.00 | 0.00 | 0.817434E+10 | 0.447441E+10 | 20369.81 | 19-MAR-08:62 | 10852.65 | 0.81 |
April | 0.00 | 0.00 | 0.101237E+11 | 0.577476E+10 | 18893.56 | 16-APR-08:62 | 12519.47 | 0.92 |
May | 0.00 | 0.00 | 0.122213E+11 | 0.702649E+10 | 19719.93 | 24-MAY-18:02 | 12068.51 | 0.94 |
June | 0.00 | 0.00 | 0.128607E+11 | 0.739887E+10 | 18550.38 | 13-JUN-08:61 | 12638.09 | 0.95 |
July | 0.00 | 0.00 | 0.143713E+11 | 0.855364E+10 | 18163.38 | 24-JUL-08:62 | 12932.31 | 0.96 |
August | 0.00 | 0.00 | 0.137867E+11 | 0.805387E+10 | 20220.47 | 12-AUG-08:62 | 11669.69 | 0.94 |
September | 0.00 | 0.00 | 0.133697E+11 | 0.779853E+10 | 18652.03 | 16-SEP-08:62 | 12646.74 | 0.95 |
October | 0.00 | 0.00 | 0.126403E+11 | 0.729565E+10 | 19352.86 | 01-OCT-08:62 | 12268.67 | 0.94 |
November | 0.00 | 0.00 | 0.921094E+10 | 0.492251E+10 | 19340.16 | 24-NOV-09:02 | 11431.30 | 0.88 |
December | 0.00 | 0.00 | 0.668336E+10 | 0.335713E+10 | 20412.67 | 23-DEC-09:02 | 11321.18 | 0.80 |
Annual Sum or Average | 0.00 | 0.00 | 0.125269E+12 | 0.706919E+11 | 0.88 | |||
Minimum of Months | 0.00 | 0.00 | 0.549733E+10 | 0.269398E+10 | 18163.38 | 10852.65 | 0.74 | |
Maximum of Months | 0.00 | 0.00 | 0.143713E+11 | 0.855364E+10 | 20555.66 | 12932.31 | 0.96 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.360931E+10 | 0.149835E+10 | 20730.55 | 07-JAN-09:01 | 11595.94 | 0.62 |
February | 0.00 | 0.00 | 0.486216E+10 | 0.230758E+10 | 19471.05 | 18-FEB-09:01 | 12478.48 | 0.73 |
March | 0.00 | 0.00 | 0.703085E+10 | 0.363766E+10 | 20542.18 | 19-MAR-08:62 | 10906.80 | 0.76 |
April | 0.00 | 0.00 | 0.952975E+10 | 0.531652E+10 | 19112.25 | 16-APR-08:62 | 12614.75 | 0.91 |
May | 0.00 | 0.00 | 0.122123E+11 | 0.701907E+10 | 20268.48 | 24-MAY-18:02 | 11981.64 | 0.94 |
June | 0.00 | 0.00 | 0.130636E+11 | 0.754903E+10 | 18647.63 | 13-JUN-08:61 | 12884.20 | 0.95 |
July | 0.00 | 0.00 | 0.144997E+11 | 0.863567E+10 | 18473.74 | 02-JUL-18:02 | 12967.06 | 0.96 |
August | 0.00 | 0.00 | 0.135233E+11 | 0.779757E+10 | 20299.54 | 12-AUG-08:62 | 11848.48 | 0.94 |
September | 0.00 | 0.00 | 0.125306E+11 | 0.708070E+10 | 18869.74 | 16-SEP-08:62 | 12741.60 | 0.94 |
October | 0.00 | 0.00 | 0.110591E+11 | 0.598321E+10 | 19526.75 | 01-OCT-08:62 | 12387.59 | 0.93 |
November | 0.00 | 0.00 | 0.747555E+10 | 0.360117E+10 | 19491.81 | 24-NOV-09:02 | 11441.14 | 0.84 |
December | 0.00 | 0.00 | 0.484260E+10 | 0.213318E+10 | 20291.47 | 23-DEC-09:02 | 11402.96 | 0.69 |
Annual Sum or Average | 0.00 | 0.00 | 0.114239E+12 | 0.625597E+11 | 0.85 | |||
Minimum of Months | 0.00 | 0.00 | 0.360931E+10 | 0.149835E+10 | 18473.74 | 10906.80 | 0.62 | |
Maximum of Months | 0.00 | 0.00 | 0.144997E+11 | 0.863567E+10 | 20730.55 | 12967.06 | 0.96 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.455826E+11 | 0.283158E+11 | 56760.76 | 02-JAN-14:30 | 44761.69 | 0.75 |
February | 0.00 | 0.00 | 0.414757E+11 | 0.251492E+11 | 50980.70 | 11-FEB-14:20 | 36687.16 | 0.78 |
March | 0.00 | 0.00 | 0.422313E+11 | 0.226321E+11 | 45455.82 | 04-MAR-20:20 | 23912.99 | 0.82 |
April | 0.00 | 0.00 | 0.436538E+11 | 0.221405E+11 | 39866.44 | 07-APR-21:00 | 23090.45 | 0.95 |
May | 0.00 | 0.00 | 0.501381E+11 | 0.247021E+11 | 42893.49 | 25-MAY-20:50 | 18106.54 | 0.99 |
June | 0.00 | 0.00 | 0.547656E+11 | 0.278189E+11 | 47398.96 | 18-JUN-20:20 | 21587.74 | 1.00 |
July | 0.00 | 0.00 | 0.612697E+11 | 0.332071E+11 | 42047.07 | 29-JUL-19:10 | 35459.18 | 1.00 |
August | 0.00 | 0.00 | 0.610536E+11 | 0.333345E+11 | 41340.99 | 20-AUG-20:03 | 33042.52 | 1.00 |
September | 0.00 | 0.00 | 0.681249E+11 | 0.411311E+11 | 48350.88 | 30-SEP-13:30 | 33294.14 | 1.00 |
October | 0.00 | 0.00 | 0.720983E+11 | 0.447246E+11 | 52569.55 | 25-OCT-12:30 | 40335.11 | 1.00 |
November | 0.00 | 0.00 | 0.595191E+11 | 0.363804E+11 | 55189.48 | 07-NOV-13:30 | 44603.36 | 0.92 |
December | 0.00 | 0.00 | 0.486168E+11 | 0.294926E+11 | 56667.85 | 09-DEC-12:30 | 44721.57 | 0.81 |
Annual Sum or Average | 0.00 | 0.00 | 0.648529E+12 | 0.369029E+12 | 0.92 | |||
Minimum of Months | 0.00 | 0.00 | 0.414757E+11 | 0.221405E+11 | 39866.44 | 18106.54 | 0.75 | |
Maximum of Months | 0.00 | 0.00 | 0.720983E+11 | 0.447246E+11 | 56760.76 | 44761.69 | 1.00 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.449269E+11 | 0.235372E+11 | 138891.19 | 07-JAN-09:01 | 76922.13 | 0.65 |
February | 0.00 | 0.00 | 0.495889E+11 | 0.280714E+11 | 129388.70 | 18-FEB-19:02 | 81120.76 | 0.66 |
March | 0.00 | 0.00 | 0.615357E+11 | 0.359941E+11 | 137864.32 | 19-MAR-08:62 | 72547.03 | 0.67 |
April | 0.00 | 0.00 | 0.736779E+11 | 0.456159E+11 | 125820.00 | 29-APR-18:02 | 82139.02 | 0.75 |
May | 0.00 | 0.00 | 0.914833E+11 | 0.602573E+11 | 138635.74 | 24-MAY-18:02 | 76960.68 | 0.83 |
June | 0.00 | 0.00 | 0.978750E+11 | 0.662440E+11 | 117525.29 | 23-JUN-15:02 | 88487.41 | 0.87 |
July | 0.00 | 0.00 | 0.103723E+12 | 0.704427E+11 | 126891.49 | 02-JUL-18:02 | 83429.01 | 0.89 |
August | 0.00 | 0.00 | 0.969086E+11 | 0.644793E+11 | 135273.80 | 12-AUG-08:62 | 78284.94 | 0.85 |
September | 0.00 | 0.00 | 0.919014E+11 | 0.608522E+11 | 117910.02 | 16-SEP-08:62 | 88024.07 | 0.85 |
October | 0.00 | 0.00 | 0.832404E+11 | 0.524719E+11 | 128888.42 | 01-OCT-08:62 | 82232.20 | 0.78 |
November | 0.00 | 0.00 | 0.655798E+11 | 0.386498E+11 | 128391.06 | 24-NOV-09:02 | 75110.10 | 0.71 |
December | 0.00 | 0.00 | 0.511800E+11 | 0.272134E+11 | 133545.72 | 23-DEC-09:02 | 77936.81 | 0.70 |
Annual Sum or Average | 0.00 | 0.00 | 0.911621E+12 | 0.573829E+12 | 0.77 | |||
Minimum of Months | 0.00 | 0.00 | 0.449269E+11 | 0.235372E+11 | 117525.29 | 72547.03 | 0.65 | |
Maximum of Months | 0.00 | 0.00 | 0.103723E+12 | 0.704427E+11 | 138891.19 | 88487.41 | 0.89 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.579143E+10 | 0.303351E+10 | 18372.60 | 07-JAN-09:01 | 10640.23 | 0.76 |
February | 0.00 | 0.00 | 0.634637E+10 | 0.342013E+10 | 17500.21 | 18-FEB-09:01 | 11140.89 | 0.82 |
March | 0.00 | 0.00 | 0.803494E+10 | 0.441324E+10 | 18429.89 | 19-MAR-08:62 | 9820.01 | 0.83 |
April | 0.00 | 0.00 | 0.100700E+11 | 0.571153E+10 | 16793.66 | 29-APR-08:62 | 11511.07 | 0.95 |
May | 0.00 | 0.00 | 0.122725E+11 | 0.709469E+10 | 17831.74 | 24-MAY-18:02 | 10902.33 | 0.96 |
June | 0.00 | 0.00 | 0.135563E+11 | 0.805376E+10 | 16021.98 | 21-JUN-18:02 | 11895.94 | 0.97 |
July | 0.00 | 0.00 | 0.148119E+11 | 0.905932E+10 | 16503.21 | 02-JUL-18:02 | 11624.09 | 0.97 |
August | 0.00 | 0.00 | 0.138300E+11 | 0.820418E+10 | 18285.23 | 12-AUG-08:62 | 10552.77 | 0.95 |
September | 0.00 | 0.00 | 0.138651E+11 | 0.840389E+10 | 16638.77 | 05-SEP-08:62 | 11530.79 | 0.97 |
October | 0.00 | 0.00 | 0.128383E+11 | 0.754117E+10 | 17513.28 | 01-OCT-08:62 | 11074.38 | 0.96 |
November | 0.00 | 0.00 | 0.927716E+10 | 0.505158E+10 | 17481.22 | 24-NOV-09:02 | 10315.80 | 0.90 |
December | 0.00 | 0.00 | 0.625108E+10 | 0.315066E+10 | 18444.89 | 23-DEC-09:02 | 10226.73 | 0.80 |
Annual Sum or Average | 0.00 | 0.00 | 0.126945E+12 | 0.731377E+11 | 0.90 | |||
Minimum of Months | 0.00 | 0.00 | 0.579143E+10 | 0.303351E+10 | 16021.98 | 9820.01 | 0.76 | |
Maximum of Months | 0.00 | 0.00 | 0.148119E+11 | 0.905932E+10 | 18444.89 | 11895.94 | 0.97 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.389451E+10 | 0.173267E+10 | 18642.24 | 07-JAN-09:01 | 10658.81 | 0.64 |
February | 0.00 | 0.00 | 0.484168E+10 | 0.239041E+10 | 17557.14 | 18-FEB-09:01 | 11271.98 | 0.75 |
March | 0.00 | 0.00 | 0.685468E+10 | 0.359389E+10 | 18563.07 | 19-MAR-08:62 | 9859.13 | 0.78 |
April | 0.00 | 0.00 | 0.946399E+10 | 0.527368E+10 | 17000.77 | 29-APR-18:02 | 11513.40 | 0.95 |
May | 0.00 | 0.00 | 0.122603E+11 | 0.707278E+10 | 18307.32 | 24-MAY-18:02 | 10809.55 | 0.96 |
June | 0.00 | 0.00 | 0.137561E+11 | 0.821296E+10 | 16125.98 | 21-JUN-18:02 | 12005.82 | 0.97 |
July | 0.00 | 0.00 | 0.149366E+11 | 0.914412E+10 | 16773.25 | 02-JUL-18:02 | 11645.96 | 0.97 |
August | 0.00 | 0.00 | 0.135635E+11 | 0.790627E+10 | 18332.99 | 12-AUG-08:62 | 10700.31 | 0.95 |
September | 0.00 | 0.00 | 0.130218E+11 | 0.753970E+10 | 16839.37 | 05-SEP-08:62 | 11587.60 | 0.96 |
October | 0.00 | 0.00 | 0.112438E+11 | 0.619810E+10 | 17634.97 | 01-OCT-08:62 | 11174.38 | 0.95 |
November | 0.00 | 0.00 | 0.753874E+10 | 0.385848E+10 | 17597.36 | 24-NOV-09:02 | 10312.99 | 0.85 |
December | 0.00 | 0.00 | 0.441693E+10 | 0.196275E+10 | 18308.78 | 23-DEC-09:02 | 10288.68 | 0.68 |
Annual Sum or Average | 0.00 | 0.00 | 0.115793E+12 | 0.648858E+11 | 0.87 | |||
Minimum of Months | 0.00 | 0.00 | 0.389451E+10 | 0.173267E+10 | 16125.98 | 9859.13 | 0.64 | |
Maximum of Months | 0.00 | 0.00 | 0.149366E+11 | 0.914412E+10 | 18642.24 | 12005.82 | 0.97 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.144156E+10 | 0.717942E+09 | 5663.35 | 07-JAN-09:01 | 2996.28 | 0.71 |
February | 0.00 | 0.00 | 0.171243E+10 | 0.919900E+09 | 5429.47 | 02-FEB-09:02 | 3083.37 | 0.80 |
March | 0.00 | 0.00 | 0.224357E+10 | 0.124199E+10 | 5599.15 | 19-MAR-08:62 | 2791.59 | 0.80 |
April | 0.00 | 0.00 | 0.282257E+10 | 0.164174E+10 | 5186.85 | 16-APR-08:62 | 3254.47 | 0.93 |
May | 0.00 | 0.00 | 0.342546E+10 | 0.201743E+10 | 5334.89 | 24-MAY-18:02 | 3172.55 | 0.95 |
June | 0.00 | 0.00 | 0.360329E+10 | 0.212289E+10 | 5046.45 | 13-JUN-08:61 | 3328.62 | 0.95 |
July | 0.00 | 0.00 | 0.402515E+10 | 0.246315E+10 | 4915.73 | 24-JUL-08:62 | 3407.45 | 0.96 |
August | 0.00 | 0.00 | 0.382786E+10 | 0.229348E+10 | 5581.22 | 12-AUG-08:62 | 2988.79 | 0.95 |
September | 0.00 | 0.00 | 0.368803E+10 | 0.220648E+10 | 5143.77 | 16-SEP-08:62 | 3277.30 | 0.95 |
October | 0.00 | 0.00 | 0.343720E+10 | 0.202046E+10 | 5322.42 | 01-OCT-08:62 | 3179.27 | 0.95 |
November | 0.00 | 0.00 | 0.247786E+10 | 0.134372E+10 | 5327.78 | 24-NOV-09:02 | 2930.11 | 0.89 |
December | 0.00 | 0.00 | 0.177414E+10 | 0.910788E+09 | 5645.65 | 23-DEC-09:02 | 2916.18 | 0.77 |
Annual Sum or Average | 0.00 | 0.00 | 0.344791E+11 | 0.199000E+11 | 0.88 | |||
Minimum of Months | 0.00 | 0.00 | 0.144156E+10 | 0.717942E+09 | 4915.73 | 2791.59 | 0.71 | |
Maximum of Months | 0.00 | 0.00 | 0.402515E+10 | 0.246315E+10 | 5663.35 | 3407.45 | 0.96 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.945329E+09 | 0.402077E+09 | 5714.15 | 07-JAN-09:01 | 2991.13 | 0.59 |
February | 0.00 | 0.00 | 0.132540E+10 | 0.640397E+09 | 5339.79 | 18-FEB-09:01 | 3237.97 | 0.72 |
March | 0.00 | 0.00 | 0.194328E+10 | 0.101694E+10 | 5641.16 | 19-MAR-08:62 | 2804.83 | 0.76 |
April | 0.00 | 0.00 | 0.266844E+10 | 0.151290E+10 | 5243.10 | 16-APR-08:62 | 3275.25 | 0.92 |
May | 0.00 | 0.00 | 0.342405E+10 | 0.201205E+10 | 5486.29 | 24-MAY-18:02 | 3140.34 | 0.95 |
June | 0.00 | 0.00 | 0.365590E+10 | 0.216267E+10 | 5059.37 | 13-JUN-08:61 | 3380.71 | 0.96 |
July | 0.00 | 0.00 | 0.405891E+10 | 0.248440E+10 | 4948.22 | 15-JUL-08:62 | 3450.12 | 0.96 |
August | 0.00 | 0.00 | 0.376171E+10 | 0.222505E+10 | 5600.35 | 12-AUG-08:62 | 3033.45 | 0.95 |
September | 0.00 | 0.00 | 0.347283E+10 | 0.199981E+10 | 5201.33 | 16-SEP-08:62 | 3296.98 | 0.95 |
October | 0.00 | 0.00 | 0.302530E+10 | 0.165297E+10 | 5363.71 | 01-OCT-08:62 | 3208.21 | 0.93 |
November | 0.00 | 0.00 | 0.202302E+10 | 0.984997E+09 | 5365.09 | 24-NOV-09:02 | 2931.20 | 0.85 |
December | 0.00 | 0.00 | 0.129114E+10 | 0.579014E+09 | 5598.75 | 23-DEC-09:02 | 2941.53 | 0.67 |
Annual Sum or Average | 0.00 | 0.00 | 0.315953E+11 | 0.176733E+11 | 0.85 | |||
Minimum of Months | 0.00 | 0.00 | 0.945329E+09 | 0.402077E+09 | 4948.22 | 2804.83 | 0.59 | |
Maximum of Months | 0.00 | 0.00 | 0.405891E+10 | 0.248440E+10 | 5714.15 | 3450.12 | 0.96 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.129891E+11 | 0.838847E+10 | 23619.09 | 07-JAN-09:01 | 12783.41 | 0.83 |
February | 0.00 | 0.00 | 0.124059E+11 | 0.792331E+10 | 22992.84 | 02-FEB-09:02 | 13134.77 | 0.85 |
March | 0.00 | 0.00 | 0.133315E+11 | 0.818121E+10 | 23720.52 | 19-MAR-08:62 | 11917.37 | 0.83 |
April | 0.00 | 0.00 | 0.142435E+11 | 0.867965E+10 | 21764.66 | 16-APR-08:62 | 13751.31 | 0.92 |
May | 0.00 | 0.00 | 0.163781E+11 | 0.998314E+10 | 23176.37 | 24-MAY-18:02 | 12985.23 | 0.93 |
June | 0.00 | 0.00 | 0.175109E+11 | 0.109835E+11 | 20430.00 | 13-JUN-08:61 | 14365.82 | 0.94 |
July | 0.00 | 0.00 | 0.191637E+11 | 0.122875E+11 | 21396.89 | 02-JUL-18:02 | 13958.14 | 0.95 |
August | 0.00 | 0.00 | 0.188724E+11 | 0.121001E+11 | 23868.60 | 12-AUG-08:62 | 12627.34 | 0.94 |
September | 0.00 | 0.00 | 0.199313E+11 | 0.132801E+11 | 20813.32 | 28-SEP-08:62 | 14242.15 | 0.95 |
October | 0.00 | 0.00 | 0.204146E+11 | 0.138096E+11 | 22524.73 | 01-OCT-08:62 | 13339.75 | 0.95 |
November | 0.00 | 0.00 | 0.168684E+11 | 0.110169E+11 | 22609.12 | 24-NOV-09:02 | 12428.47 | 0.92 |
December | 0.00 | 0.00 | 0.141203E+11 | 0.890404E+10 | 23768.39 | 23-DEC-09:02 | 12684.80 | 0.87 |
Annual Sum or Average | 0.00 | 0.00 | 0.196230E+12 | 0.125538E+12 | 0.91 | |||
Minimum of Months | 0.00 | 0.00 | 0.124059E+11 | 0.792331E+10 | 20430.00 | 11917.37 | 0.83 | |
Maximum of Months | 0.00 | 0.00 | 0.204146E+11 | 0.138096E+11 | 23868.60 | 14365.82 | 0.95 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 11233.28 | 60722.14 | 18-JAN-11:40 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 11068.74 | 67096.09 | 06-FEB-11:40 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 12181.84 | 76117.71 | 20-MAR-10:40 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11402.04 | 67094.71 | 18-APR-10:35 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10147.67 | 62175.45 | 01-MAY-10:35 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9509.79 | 60608.83 | 13-JUN-10:35 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 8744.58 | 57541.44 | 07-JUL-10:35 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 7948.03 | 56734.21 | 29-AUG-10:35 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 7034.27 | 53503.53 | 05-SEP-10:40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 6739.02 | 48951.54 | 02-OCT-10:40 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 7716.25 | 54928.78 | 27-NOV-11:40 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 10277.94 | 61852.08 | 21-DEC-11:40 |
Annual Sum or Average | 0.00 | 9493.80 | ||||
Minimum of Months | 0.00 | 0.00 | 6739.02 | 48951.54 | ||
Maximum of Months | 0.00 | 0.00 | 12181.84 | 76117.71 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 302559.88 | 856106.84 | 07-JAN-19:02 | 0.00 | 0.00 | 01-JAN-00:03 |
February | 351044.64 | 852956.23 | 11-FEB-16:03 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 383948.18 | 862782.08 | 19-MAR-08:62 | 0.00 | 0.00 | 01-MAR-00:03 |
April | 472543.71 | 866837.27 | 01-APR-15:03 | 0.00 | 0.00 | 01-APR-00:10 |
May | 597269.56 | 910447.94 | 28-MAY-15:03 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 684550.66 | 974223.34 | 08-JUN-18:03 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 700328.25 | 994549.63 | 27-JUL-18:03 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 699352.89 | 950054.48 | 21-AUG-18:03 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 682785.30 | 1006036.25 | 18-SEP-18:03 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 619128.68 | 940360.79 | 29-OCT-18:03 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 512373.74 | 932511.46 | 04-NOV-18:03 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 368825.07 | 867595.97 | 23-DEC-19:03 | 0.00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 532083.95 | 0.00 | ||||
Minimum of Months | 302559.88 | 852956.23 | 0.00 | 0.00 | ||
Maximum of Months | 700328.25 | 1006036.25 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 20265.30 | 40653.20 | 20-JAN-07:20 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 20087.51 | 40517.08 | 03-FEB-07:15 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 19531.38 | 39744.28 | 01-MAR-07:10 |
April | 0.00 | 0.00 | 01-APR-00:10 | 18691.42 | 38037.64 | 03-APR-06:10 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 17836.46 | 36368.87 | 01-MAY-06:10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17184.54 | 34652.15 | 01-JUN-07:00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16893.45 | 33643.94 | 03-JUL-06:50 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17092.96 | 34405.19 | 31-AUG-06:30 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 17671.85 | 35922.08 | 29-SEP-06:20 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18498.15 | 37791.94 | 31-OCT-06:20 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 19354.26 | 39393.91 | 30-NOV-08:00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 19999.10 | 40446.38 | 29-DEC-07:15 |
Annual Sum or Average | 0.00 | 18583.93 | ||||
Minimum of Months | 0.00 | 0.00 | 16893.45 | 33643.94 | ||
Maximum of Months | 0.00 | 0.00 | 20265.30 | 40653.20 |
Report: FanReportMonthly
For: FLR_3_DOAS FAN
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.587890E+10 | 0.87 | 2194.93 | 01-JAN-00:03 | 0.87 |
February | 0.530997E+10 | 0.87 | 2194.93 | 01-FEB-00:03 | 0.87 |
March | 0.587890E+10 | 0.87 | 2194.93 | 01-MAR-00:03 | 0.87 |
April | 0.568926E+10 | 0.87 | 2194.93 | 01-APR-00:10 | 0.87 |
May | 0.587890E+10 | 0.87 | 2194.93 | 01-MAY-00:10 | 0.87 |
June | 0.568926E+10 | 0.87 | 2194.93 | 01-JUN-00:10 | 0.87 |
July | 0.587890E+10 | 0.87 | 2194.93 | 01-JUL-00:10 | 0.87 |
August | 0.587890E+10 | 0.87 | 2194.93 | 01-AUG-00:10 | 0.87 |
September | 0.568926E+10 | 0.87 | 2194.93 | 01-SEP-00:10 | 0.87 |
October | 0.587890E+10 | 0.87 | 2194.93 | 01-OCT-00:10 | 0.87 |
November | 0.568926E+10 | 0.87 | 2194.93 | 01-NOV-00:10 | 0.87 |
December | 0.587890E+10 | 0.87 | 2194.93 | 01-DEC-00:03 | 0.87 |
Annual Sum or Average | 0.692193E+11 | 0.87 | |||
Minimum of Months | 0.530997E+10 | 0.87 | 2194.93 | 0.87 | |
Maximum of Months | 0.587890E+10 | 0.87 | 2194.93 | 0.87 |
Report: FanReportMonthly
For: VAV WITH REHEAT FAN
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.127282E+12 | 1.82 | 47521.84 | 01-JAN-00:03 | 1.82 |
February | 0.114965E+12 | 1.82 | 47521.84 | 01-FEB-00:03 | 1.83 |
March | 0.127283E+12 | 1.82 | 47521.84 | 01-MAR-00:03 | 1.83 |
April | 0.123177E+12 | 1.82 | 47521.84 | 01-APR-00:10 | 1.82 |
May | 0.127283E+12 | 1.82 | 47521.84 | 01-MAY-00:10 | 1.82 |
June | 0.123177E+12 | 1.82 | 47521.84 | 01-JUN-00:10 | 1.82 |
July | 0.127283E+12 | 1.82 | 47521.84 | 01-JUL-00:10 | 1.82 |
August | 0.127283E+12 | 1.82 | 47521.84 | 01-AUG-00:10 | 1.82 |
September | 0.123177E+12 | 1.82 | 47521.84 | 01-SEP-00:10 | 1.82 |
October | 0.127283E+12 | 1.82 | 47521.84 | 01-OCT-00:10 | 1.82 |
November | 0.123177E+12 | 1.82 | 47521.84 | 01-NOV-00:10 | 1.82 |
December | 0.127283E+12 | 1.82 | 47521.84 | 01-DEC-00:03 | 1.82 |
Annual Sum or Average | 0.149865E+13 | 1.82 | |||
Minimum of Months | 0.114965E+12 | 1.82 | 47521.84 | 1.82 | |
Maximum of Months | 0.127283E+12 | 1.82 | 47521.84 | 1.83 |
Report: FanReportMonthly
For: LAUNDRY_FLR_1 EXHAUST FAN
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.493775E+09 | 0.64 | 184.35 | 01-JAN-00:03 | 0.63 |
February | 0.445990E+09 | 0.64 | 184.35 | 01-FEB-00:03 | 0.64 |
March | 0.493775E+09 | 0.64 | 184.35 | 01-MAR-00:03 | 0.64 |
April | 0.477847E+09 | 0.64 | 184.35 | 01-APR-00:10 | 0.63 |
May | 0.493775E+09 | 0.64 | 184.35 | 01-MAY-00:10 | 0.63 |
June | 0.477847E+09 | 0.64 | 184.35 | 01-JUN-00:10 | 0.63 |
July | 0.493775E+09 | 0.64 | 184.35 | 01-JUL-00:10 | 0.63 |
August | 0.493775E+09 | 0.64 | 184.35 | 01-AUG-00:10 | 0.63 |
September | 0.477847E+09 | 0.64 | 184.35 | 01-SEP-00:10 | 0.63 |
October | 0.493775E+09 | 0.64 | 184.35 | 01-OCT-00:10 | 0.63 |
November | 0.477847E+09 | 0.64 | 184.35 | 01-NOV-00:10 | 0.63 |
December | 0.493775E+09 | 0.64 | 184.35 | 01-DEC-00:03 | 0.63 |
Annual Sum or Average | 0.581380E+10 | 0.64 | |||
Minimum of Months | 0.445990E+09 | 0.64 | 184.35 | 0.63 | |
Maximum of Months | 0.493775E+09 | 0.64 | 184.35 | 0.64 |
Report: FanReportMonthly
For: LOBBY_FLR_1 EXHAUST FAN
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: BANQUET_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: DINING_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.279806E+10 | 0.45 | 1474.84 | 01-JAN-07:10 | 0.63 |
February | 0.252728E+10 | 0.45 | 1474.84 | 01-FEB-07:05 | 0.63 |
March | 0.279806E+10 | 0.45 | 1474.84 | 01-MAR-07:05 | 0.64 |
April | 0.270780E+10 | 0.45 | 1474.84 | 01-APR-06:10 | 0.63 |
May | 0.279806E+10 | 0.45 | 1474.84 | 01-MAY-06:05 | 0.63 |
June | 0.270780E+10 | 0.45 | 1474.84 | 01-JUN-06:05 | 0.63 |
July | 0.279806E+10 | 0.45 | 1474.84 | 01-JUL-06:10 | 0.63 |
August | 0.279806E+10 | 0.45 | 1474.84 | 01-AUG-06:05 | 0.63 |
September | 0.270780E+10 | 0.45 | 1474.84 | 01-SEP-06:05 | 0.63 |
October | 0.279806E+10 | 0.45 | 1474.84 | 01-OCT-06:10 | 0.63 |
November | 0.270780E+10 | 0.45 | 1474.84 | 01-NOV-06:05 | 0.63 |
December | 0.279806E+10 | 0.45 | 1474.84 | 01-DEC-07:05 | 0.63 |
Annual Sum or Average | 0.329449E+11 | 0.45 | |||
Minimum of Months | 0.252728E+10 | 0.45 | 1474.84 | 0.63 | |
Maximum of Months | 0.279806E+10 | 0.45 | 1474.84 | 0.64 |
Report: FanReportMonthly
For: ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.580494E+09 | 1.16 | 1775.31 | 01-JAN-09:02 | 1.37 |
February | 0.660358E+09 | 1.21 | 1775.31 | 01-FEB-16:02 | 1.38 |
March | 0.818118E+09 | 1.21 | 1775.31 | 01-MAR-16:02 | 1.38 |
April | 0.100729E+10 | 1.27 | 1775.31 | 01-APR-08:62 | 1.37 |
May | 0.117141E+10 | 1.29 | 1775.31 | 01-MAY-08:62 | 1.37 |
June | 0.120306E+10 | 1.30 | 1775.31 | 01-JUN-08:62 | 1.37 |
July | 0.135959E+10 | 1.32 | 1775.31 | 01-JUL-08:62 | 1.37 |
August | 0.129349E+10 | 1.30 | 1775.31 | 01-AUG-08:62 | 1.37 |
September | 0.126267E+10 | 1.31 | 1775.31 | 01-SEP-08:62 | 1.37 |
October | 0.119498E+10 | 1.30 | 1775.31 | 01-OCT-08:62 | 1.37 |
November | 0.867705E+09 | 1.25 | 1775.31 | 01-NOV-08:62 | 1.37 |
December | 0.670480E+09 | 1.18 | 1775.31 | 01-DEC-09:02 | 1.38 |
Annual Sum or Average | 0.120896E+11 | 1.26 | |||
Minimum of Months | 0.580494E+09 | 1.16 | 1775.31 | 1.37 | |
Maximum of Months | 0.135959E+10 | 1.32 | 1775.31 | 1.38 |
Report: FanReportMonthly
For: ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.419314E+09 | 1.06 | 1792.80 | 01-JAN-09:02 | 1.37 |
February | 0.523236E+09 | 1.12 | 1792.80 | 01-FEB-16:02 | 1.37 |
March | 0.711471E+09 | 1.15 | 1792.80 | 01-MAR-16:02 | 1.38 |
April | 0.940985E+09 | 1.25 | 1792.80 | 01-APR-08:62 | 1.37 |
May | 0.116916E+10 | 1.29 | 1792.80 | 01-MAY-08:62 | 1.37 |
June | 0.122499E+10 | 1.31 | 1792.80 | 01-JUN-08:62 | 1.37 |
July | 0.137437E+10 | 1.32 | 1792.80 | 01-JUL-08:62 | 1.37 |
August | 0.126589E+10 | 1.29 | 1792.80 | 01-AUG-08:62 | 1.37 |
September | 0.117151E+10 | 1.30 | 1792.80 | 01-SEP-08:62 | 1.37 |
October | 0.103121E+10 | 1.28 | 1792.80 | 01-OCT-08:62 | 1.37 |
November | 0.709077E+09 | 1.20 | 1792.80 | 01-NOV-08:62 | 1.37 |
December | 0.516618E+09 | 1.10 | 1792.80 | 01-DEC-09:02 | 1.38 |
Annual Sum or Average | 0.110578E+11 | 1.22 | |||
Minimum of Months | 0.419314E+09 | 1.06 | 1792.80 | 1.37 | |
Maximum of Months | 0.137437E+10 | 1.32 | 1792.80 | 1.38 |
Report: FanReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.434911E+10 | 1.17 | 5764.46 | 02-JAN-14:30 | 1.38 |
February | 0.384781E+10 | 1.19 | 5876.08 | 22-FEB-14:40 | 1.39 |
March | 0.375204E+10 | 1.22 | 3282.17 | 02-MAR-14:30 | 1.38 |
April | 0.390133E+10 | 1.32 | 3011.59 | 15-APR-19:10 | 1.38 |
May | 0.439346E+10 | 1.37 | 2915.33 | 29-MAY-20:20 | 1.38 |
June | 0.466900E+10 | 1.38 | 3081.01 | 03-JUN-21:00 | 1.38 |
July | 0.514548E+10 | 1.38 | 3312.36 | 29-JUL-19:10 | 1.38 |
August | 0.512364E+10 | 1.38 | 3207.23 | 20-AUG-20:03 | 1.38 |
September | 0.577741E+10 | 1.38 | 5042.44 | 30-SEP-13:30 | 1.38 |
October | 0.638503E+10 | 1.38 | 5487.06 | 25-OCT-12:40 | 1.38 |
November | 0.533464E+10 | 1.29 | 5741.52 | 07-NOV-13:30 | 1.38 |
December | 0.448917E+10 | 1.16 | 5773.90 | 03-DEC-14:00 | 1.38 |
Annual Sum or Average | 0.571681E+11 | 1.30 | |||
Minimum of Months | 0.375204E+10 | 1.16 | 2915.33 | 1.38 | |
Maximum of Months | 0.638503E+10 | 1.38 | 5876.08 | 1.39 |
Report: FanReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.438456E+10 | 0.98 | 11766.20 | 01-JAN-09:02 | 1.37 |
February | 0.477492E+10 | 0.98 | 11766.20 | 01-FEB-09:02 | 1.37 |
March | 0.599605E+10 | 0.99 | 11766.20 | 01-MAR-16:02 | 1.38 |
April | 0.725515E+10 | 1.03 | 11766.20 | 01-APR-08:62 | 1.37 |
May | 0.916429E+10 | 1.14 | 11766.20 | 01-MAY-08:62 | 1.37 |
June | 0.996510E+10 | 1.20 | 11766.20 | 01-JUN-08:62 | 1.38 |
July | 0.105976E+11 | 1.23 | 11766.20 | 01-JUL-08:62 | 1.38 |
August | 0.965302E+10 | 1.17 | 11766.20 | 01-AUG-08:62 | 1.38 |
September | 0.909143E+10 | 1.17 | 11766.20 | 01-SEP-08:62 | 1.38 |
October | 0.815083E+10 | 1.08 | 11766.20 | 01-OCT-08:62 | 1.37 |
November | 0.633846E+10 | 0.99 | 11766.20 | 01-NOV-08:62 | 1.37 |
December | 0.488734E+10 | 0.98 | 11766.20 | 01-DEC-09:02 | 1.38 |
Annual Sum or Average | 0.902587E+11 | 1.08 | |||
Minimum of Months | 0.438456E+10 | 0.98 | 11766.20 | 1.37 | |
Maximum of Months | 0.105976E+11 | 1.23 | 11766.20 | 1.38 |
Report: FanReportMonthly
For: ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.600899E+09 | 1.20 | 1595.96 | 01-JAN-09:02 | 1.37 |
February | 0.649454E+09 | 1.23 | 1595.96 | 01-FEB-09:02 | 1.37 |
March | 0.790821E+09 | 1.24 | 1595.96 | 01-MAR-09:02 | 1.38 |
April | 0.989588E+09 | 1.31 | 1595.96 | 01-APR-08:62 | 1.37 |
May | 0.117766E+10 | 1.32 | 1595.96 | 01-MAY-08:62 | 1.37 |
June | 0.129288E+10 | 1.33 | 1595.96 | 01-JUN-08:62 | 1.38 |
July | 0.141502E+10 | 1.34 | 1595.96 | 01-JUL-08:62 | 1.38 |
August | 0.130146E+10 | 1.31 | 1595.96 | 01-AUG-08:62 | 1.37 |
September | 0.131770E+10 | 1.33 | 1595.96 | 01-SEP-08:62 | 1.38 |
October | 0.122543E+10 | 1.32 | 1595.96 | 01-OCT-08:62 | 1.37 |
November | 0.888946E+09 | 1.27 | 1595.96 | 01-NOV-08:62 | 1.37 |
December | 0.625736E+09 | 1.19 | 1595.96 | 01-DEC-09:02 | 1.38 |
Annual Sum or Average | 0.122756E+11 | 1.28 | |||
Minimum of Months | 0.600899E+09 | 1.19 | 1595.96 | 1.37 | |
Maximum of Months | 0.141502E+10 | 1.34 | 1595.96 | 1.38 |
Report: FanReportMonthly
For: ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.431785E+09 | 1.07 | 1609.46 | 01-JAN-09:02 | 1.37 |
February | 0.499507E+09 | 1.16 | 1609.46 | 01-FEB-09:02 | 1.37 |
March | 0.673553E+09 | 1.19 | 1609.46 | 01-MAR-09:02 | 1.38 |
April | 0.920787E+09 | 1.30 | 1609.46 | 01-APR-08:62 | 1.37 |
May | 0.117761E+10 | 1.32 | 1609.46 | 01-MAY-08:62 | 1.37 |
June | 0.131545E+10 | 1.34 | 1609.46 | 01-JUN-08:62 | 1.38 |
July | 0.143009E+10 | 1.34 | 1609.46 | 01-JUL-08:62 | 1.38 |
August | 0.127750E+10 | 1.31 | 1609.46 | 01-AUG-08:62 | 1.37 |
September | 0.123640E+10 | 1.32 | 1609.46 | 01-SEP-08:62 | 1.38 |
October | 0.105363E+10 | 1.31 | 1609.46 | 01-OCT-08:62 | 1.37 |
November | 0.701427E+09 | 1.21 | 1609.46 | 01-NOV-08:62 | 1.37 |
December | 0.466381E+09 | 1.09 | 1609.46 | 01-DEC-09:02 | 1.38 |
Annual Sum or Average | 0.111841E+11 | 1.25 | |||
Minimum of Months | 0.431785E+09 | 1.07 | 1609.46 | 1.37 | |
Maximum of Months | 0.143009E+10 | 1.34 | 1609.46 | 1.38 |
Report: FanReportMonthly
For: ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.156889E+09 | 1.18 | 474.51 | 01-JAN-09:02 | 1.37 |
February | 0.181642E+09 | 1.22 | 474.51 | 01-FEB-16:02 | 1.38 |
March | 0.228092E+09 | 1.22 | 474.51 | 01-MAR-16:02 | 1.38 |
April | 0.284312E+09 | 1.28 | 474.51 | 01-APR-08:62 | 1.37 |
May | 0.332280E+09 | 1.30 | 474.51 | 01-MAY-08:62 | 1.37 |
June | 0.341877E+09 | 1.31 | 474.51 | 01-JUN-08:62 | 1.37 |
July | 0.387764E+09 | 1.33 | 474.51 | 01-JUL-08:62 | 1.37 |
August | 0.364345E+09 | 1.31 | 474.51 | 01-AUG-08:62 | 1.37 |
September | 0.352253E+09 | 1.31 | 474.51 | 01-SEP-08:62 | 1.37 |
October | 0.327836E+09 | 1.30 | 474.51 | 01-OCT-08:62 | 1.37 |
November | 0.236608E+09 | 1.26 | 474.51 | 01-NOV-08:62 | 1.37 |
December | 0.181956E+09 | 1.19 | 474.51 | 01-DEC-09:02 | 1.37 |
Annual Sum or Average | 0.337585E+10 | 1.27 | |||
Minimum of Months | 0.156889E+09 | 1.18 | 474.51 | 1.37 | |
Maximum of Months | 0.387764E+09 | 1.33 | 474.51 | 1.38 |
Report: FanReportMonthly
For: ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.116878E+09 | 1.08 | 478.73 | 01-JAN-09:02 | 1.37 |
February | 0.146364E+09 | 1.16 | 478.73 | 01-FEB-16:02 | 1.37 |
March | 0.200603E+09 | 1.18 | 478.73 | 01-MAR-16:02 | 1.38 |
April | 0.267110E+09 | 1.27 | 478.73 | 01-APR-08:62 | 1.37 |
May | 0.332091E+09 | 1.31 | 478.73 | 01-MAY-08:62 | 1.37 |
June | 0.347703E+09 | 1.32 | 478.73 | 01-JUN-08:62 | 1.37 |
July | 0.391765E+09 | 1.33 | 478.73 | 01-JUL-08:62 | 1.37 |
August | 0.356767E+09 | 1.31 | 478.73 | 01-AUG-08:62 | 1.37 |
September | 0.329270E+09 | 1.31 | 478.73 | 01-SEP-08:62 | 1.37 |
October | 0.284843E+09 | 1.29 | 478.73 | 01-OCT-08:62 | 1.37 |
November | 0.194861E+09 | 1.21 | 478.73 | 01-NOV-15:02 | 1.38 |
December | 0.143685E+09 | 1.13 | 478.73 | 01-DEC-09:02 | 1.37 |
Annual Sum or Average | 0.311194E+10 | 1.24 | |||
Minimum of Months | 0.116878E+09 | 1.08 | 478.73 | 1.37 | |
Maximum of Months | 0.391765E+09 | 1.33 | 478.73 | 1.38 |
Report: FanReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.134147E+10 | 1.25 | 1973.24 | 01-JAN-09:02 | 1.37 |
February | 0.127423E+10 | 1.26 | 1973.24 | 01-FEB-09:02 | 1.37 |
March | 0.132264E+10 | 1.24 | 1973.24 | 01-MAR-09:02 | 1.38 |
April | 0.140231E+10 | 1.27 | 1973.24 | 01-APR-08:62 | 1.37 |
May | 0.158682E+10 | 1.28 | 1973.24 | 01-MAY-08:62 | 1.37 |
June | 0.169497E+10 | 1.30 | 1973.24 | 01-JUN-08:62 | 1.37 |
July | 0.187255E+10 | 1.31 | 1973.24 | 01-JUL-08:62 | 1.37 |
August | 0.183004E+10 | 1.29 | 1973.24 | 01-AUG-08:62 | 1.37 |
September | 0.198969E+10 | 1.31 | 1973.24 | 01-SEP-08:62 | 1.37 |
October | 0.205514E+10 | 1.31 | 1973.24 | 01-OCT-08:62 | 1.37 |
November | 0.170513E+10 | 1.29 | 1973.24 | 01-NOV-08:62 | 1.37 |
December | 0.142404E+10 | 1.25 | 1973.24 | 01-DEC-09:02 | 1.38 |
Annual Sum or Average | 0.194990E+11 | 1.28 | |||
Minimum of Months | 0.127423E+10 | 1.24 | 1973.24 | 1.37 | |
Maximum of Months | 0.205514E+10 | 1.31 | 1973.24 | 1.38 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.232411E+09 | 0.209170E+09 | 377.30 | 18-JAN-11:40 | 339.57 | 339.57 | 32.92 | 0.54 |
February | 0.206140E+09 | 0.185526E+09 | 407.64 | 06-FEB-11:40 | 366.88 | 366.88 | 33.51 | 0.61 |
March | 0.251898E+09 | 0.226708E+09 | 461.85 | 20-MAR-10:40 | 415.67 | 415.67 | 35.93 | 0.76 |
April | 0.232925E+09 | 0.209633E+09 | 406.62 | 18-APR-10:40 | 365.96 | 365.96 | 36.10 | 0.60 |
May | 0.217296E+09 | 0.195566E+09 | 402.17 | 01-MAY-10:40 | 361.95 | 361.95 | 36.73 | 0.59 |
June | 0.199514E+09 | 0.179562E+09 | 387.79 | 13-JUN-10:40 | 349.01 | 349.01 | 36.01 | 0.56 |
July | 0.190099E+09 | 0.171089E+09 | 375.51 | 07-JUL-10:40 | 337.96 | 337.96 | 35.64 | 0.53 |
August | 0.170711E+09 | 0.153640E+09 | 361.41 | 07-AUG-10:40 | 325.27 | 325.27 | 35.12 | 0.50 |
September | 0.149493E+09 | 0.134544E+09 | 346.71 | 05-SEP-10:50 | 312.04 | 312.04 | 34.87 | 0.47 |
October | 0.148596E+09 | 0.133736E+09 | 326.37 | 02-OCT-10:50 | 293.74 | 293.74 | 34.13 | 0.43 |
November | 0.159800E+09 | 0.143820E+09 | 346.71 | 27-NOV-11:40 | 312.04 | 312.04 | 32.24 | 0.47 |
December | 0.215446E+09 | 0.193901E+09 | 391.15 | 21-DEC-11:50 | 352.04 | 352.04 | 35.53 | 0.57 |
Annual Sum or Average | 0.237433E+10 | 0.213689E+10 | ||||||
Minimum of Months | 0.148596E+09 | 0.133736E+09 | 326.37 | 293.74 | 293.74 | 32.24 | 0.43 | |
Maximum of Months | 0.251898E+09 | 0.226708E+09 | 461.85 | 415.67 | 415.67 | 36.73 | 0.76 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.131434E+11 | 0.118291E+11 | 8398.39 | 07-JAN-19:02 | 7558.55 | 7558.55 | 6.73 | 27.86 |
February | 0.133352E+11 | 0.120016E+11 | 8391.53 | 11-FEB-17:50 | 7552.38 | 7552.38 | 6.73 | 27.77 |
March | 0.153764E+11 | 0.138388E+11 | 8441.81 | 13-MAR-18:03 | 7597.63 | 7597.63 | 6.73 | 28.45 |
April | 0.174970E+11 | 0.157473E+11 | 8556.85 | 13-APR-18:03 | 7701.16 | 7701.16 | 6.73 | 30.16 |
May | 0.201588E+11 | 0.181429E+11 | 8710.14 | 29-MAY-18:03 | 7839.13 | 7839.13 | 6.73 | 32.68 |
June | 0.205209E+11 | 0.184688E+11 | 8885.27 | 08-JUN-18:03 | 7996.74 | 7996.74 | 6.73 | 35.65 |
July | 0.213997E+11 | 0.192597E+11 | 8990.03 | 27-JUL-18:03 | 8091.03 | 8091.03 | 6.73 | 37.30 |
August | 0.213425E+11 | 0.192082E+11 | 8836.97 | 21-AUG-18:03 | 7953.28 | 7953.28 | 6.73 | 34.85 |
September | 0.205442E+11 | 0.184898E+11 | 8945.32 | 18-SEP-18:03 | 8050.79 | 8050.79 | 6.73 | 36.62 |
October | 0.204082E+11 | 0.183674E+11 | 8721.31 | 29-OCT-18:03 | 7849.18 | 7849.18 | 6.73 | 32.87 |
November | 0.176215E+11 | 0.158593E+11 | 8696.20 | 04-NOV-18:03 | 7826.58 | 7826.58 | 6.73 | 32.44 |
December | 0.147247E+11 | 0.132522E+11 | 8484.94 | 25-DEC-19:03 | 7636.44 | 7636.44 | 6.73 | 29.07 |
Annual Sum or Average | 0.216072E+12 | 0.194465E+12 | ||||||
Minimum of Months | 0.131434E+11 | 0.118291E+11 | 8391.53 | 7552.38 | 7552.38 | 6.73 | 27.77 | |
Maximum of Months | 0.213997E+11 | 0.192597E+11 | 8990.03 | 8091.03 | 8091.03 | 6.73 | 37.30 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.203461E+11 | 0.183115E+11 | 7625.39 | 01-JAN-00:03 | 6862.85 | 6862.85 | 9.09 | 53.44 |
February | 0.182643E+11 | 0.164379E+11 | 7625.39 | 01-FEB-00:03 | 6862.85 | 6862.85 | 7.18 | 53.44 |
March | 0.202774E+11 | 0.182497E+11 | 7625.39 | 01-MAR-00:03 | 6862.85 | 6862.85 | 7.39 | 53.44 |
April | 0.197650E+11 | 0.177885E+11 | 7625.39 | 01-APR-00:10 | 6862.85 | 6862.85 | 8.48 | 53.44 |
May | 0.204239E+11 | 0.183815E+11 | 7625.39 | 01-MAY-00:10 | 6862.85 | 6862.85 | 8.69 | 53.44 |
June | 0.197650E+11 | 0.177885E+11 | 7625.39 | 01-JUN-00:10 | 6862.85 | 6862.85 | 9.66 | 53.44 |
July | 0.204239E+11 | 0.183815E+11 | 7625.39 | 01-JUL-00:10 | 6862.85 | 6862.85 | 9.54 | 53.44 |
August | 0.204239E+11 | 0.183815E+11 | 7625.39 | 01-AUG-00:10 | 6862.85 | 6862.85 | 10.03 | 53.44 |
September | 0.197650E+11 | 0.177885E+11 | 7625.39 | 01-SEP-00:10 | 6862.85 | 6862.85 | 9.59 | 53.44 |
October | 0.204239E+11 | 0.183815E+11 | 7625.39 | 01-OCT-00:10 | 6862.85 | 6862.85 | 9.56 | 53.44 |
November | 0.197650E+11 | 0.177885E+11 | 7625.39 | 01-NOV-00:10 | 6862.85 | 6862.85 | 8.93 | 53.44 |
December | 0.203781E+11 | 0.183403E+11 | 7625.39 | 01-DEC-00:03 | 6862.85 | 6862.85 | 9.05 | 53.44 |
Annual Sum or Average | 0.240021E+12 | 0.216019E+12 | ||||||
Minimum of Months | 0.182643E+11 | 0.164379E+11 | 7625.39 | 6862.85 | 6862.85 | 7.18 | 53.44 | |
Maximum of Months | 0.204239E+11 | 0.183815E+11 | 7625.39 | 6862.85 | 6862.85 | 10.03 | 53.44 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.128314E+09 | 38494137.67 | 47.91 | 01-JAN-00:03 | 14.37 | 14.37 | 51.18 | 0.37 |
February | 0.115896E+09 | 34768898.54 | 47.91 | 01-FEB-00:03 | 14.37 | 14.37 | 51.64 | 0.37 |
March | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAR-00:03 | 14.37 | 14.37 | 51.36 | 0.37 |
April | 0.124175E+09 | 37252391.29 | 47.91 | 01-APR-00:10 | 14.37 | 14.37 | 53.63 | 0.37 |
May | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAY-00:10 | 14.37 | 14.37 | 53.86 | 0.37 |
June | 0.124175E+09 | 37252391.29 | 47.91 | 01-JUN-00:10 | 14.37 | 14.37 | 54.76 | 0.37 |
July | 0.128314E+09 | 38494137.67 | 47.91 | 01-JUL-00:10 | 14.37 | 14.37 | 54.99 | 0.37 |
August | 0.128314E+09 | 38494137.67 | 47.91 | 01-AUG-00:10 | 14.37 | 14.37 | 54.82 | 0.37 |
September | 0.124175E+09 | 37252391.29 | 47.91 | 01-SEP-00:10 | 14.37 | 14.37 | 54.82 | 0.37 |
October | 0.128314E+09 | 38494137.67 | 47.91 | 01-OCT-00:10 | 14.37 | 14.37 | 54.11 | 0.37 |
November | 0.124175E+09 | 37252391.29 | 47.91 | 01-NOV-00:10 | 14.37 | 14.37 | 53.96 | 0.37 |
December | 0.128314E+09 | 38494137.67 | 47.91 | 01-DEC-00:03 | 14.37 | 14.37 | 51.34 | 0.37 |
Annual Sum or Average | 0.151079E+10 | 0.453237E+09 | ||||||
Minimum of Months | 0.115896E+09 | 34768898.54 | 47.91 | 14.37 | 14.37 | 51.18 | 0.37 | |
Maximum of Months | 0.128314E+09 | 38494137.67 | 47.91 | 14.37 | 14.37 | 54.99 | 0.37 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 25.08 | 60.00 | 11233.28 | 60722.14 | 18-JAN-11:40 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 26.64 | 60.00 | 11068.74 | 67096.09 | 06-FEB-11:40 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 26.53 | 60.00 | 12181.84 | 76117.71 | 20-MAR-10:40 |
April | 0.00 | 0.00 | 01-APR-00:10 | 29.69 | 60.00 | 11402.04 | 67094.71 | 18-APR-10:35 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 29.82 | 60.00 | 10147.67 | 62175.45 | 01-MAY-10:35 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 29.43 | 60.00 | 9509.79 | 60608.83 | 13-JUN-10:35 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 29.37 | 60.00 | 8744.58 | 57541.44 | 07-JUL-10:35 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.37 | 60.00 | 7948.03 | 56734.21 | 29-AUG-10:35 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 29.44 | 60.00 | 7034.27 | 53503.53 | 05-SEP-10:40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 30.07 | 60.00 | 6739.02 | 48951.54 | 02-OCT-10:40 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 30.21 | 60.00 | 7716.25 | 54928.78 | 27-NOV-11:40 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 28.69 | 60.00 | 10277.94 | 61852.08 | 21-DEC-11:40 |
Annual Sum or Average | 0.00 | 9493.80 | ||||||
Minimum of Months | 0.00 | 0.00 | 25.08 | 60.00 | 6739.02 | 48951.54 | ||
Maximum of Months | 0.00 | 0.00 | 30.21 | 60.00 | 12181.84 | 76117.71 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 302559.88 | 856106.84 | 07-JAN-19:02 | 10.52 | 6.70 | 0.00 | 0.00 | 01-JAN-00:03 |
February | 351044.64 | 852956.23 | 11-FEB-16:03 | 10.51 | 6.70 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 383948.18 | 862782.08 | 19-MAR-08:62 | 10.55 | 6.70 | 0.00 | 0.00 | 01-MAR-00:03 |
April | 472543.71 | 866837.27 | 01-APR-15:03 | 10.57 | 6.70 | 0.00 | 0.00 | 01-APR-00:10 |
May | 597269.56 | 910447.94 | 28-MAY-15:03 | 10.77 | 6.70 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 684550.66 | 974223.34 | 08-JUN-18:03 | 11.05 | 6.70 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 700328.25 | 994549.63 | 27-JUL-18:03 | 11.14 | 6.70 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 699352.89 | 950054.48 | 21-AUG-18:03 | 10.94 | 6.70 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 682785.30 | 1006036.25 | 18-SEP-18:03 | 11.19 | 6.70 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 619128.68 | 940360.79 | 29-OCT-18:03 | 10.90 | 6.70 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 512373.74 | 932511.46 | 04-NOV-18:03 | 10.86 | 6.70 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 368825.07 | 867595.97 | 23-DEC-19:03 | 10.57 | 6.70 | 0.00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 532083.95 | 0.00 | ||||||
Minimum of Months | 302559.88 | 852956.23 | 10.51 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 700328.25 | 1006036.25 | 11.19 | 6.70 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 51.18 | 59.85 | 20265.30 | 40653.20 | 20-JAN-07:20 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 51.64 | 59.67 | 20087.51 | 40517.08 | 03-FEB-07:15 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 51.36 | 58.40 | 19531.38 | 39744.28 | 01-MAR-07:10 |
April | 0.00 | 0.00 | 01-APR-00:10 | 53.63 | 58.42 | 18691.42 | 38037.64 | 03-APR-06:10 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 53.86 | 58.48 | 17836.46 | 36368.87 | 01-MAY-06:10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 54.76 | 59.31 | 17184.54 | 34652.15 | 01-JUN-07:00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 54.99 | 59.58 | 16893.45 | 33643.94 | 03-JUL-06:50 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 54.82 | 59.11 | 17092.96 | 34405.19 | 31-AUG-06:30 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 54.82 | 59.57 | 17671.85 | 35922.08 | 29-SEP-06:20 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 54.11 | 59.67 | 18498.15 | 37791.94 | 31-OCT-06:20 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 53.96 | 58.77 | 19354.26 | 39393.91 | 30-NOV-08:00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 51.34 | 58.31 | 19999.10 | 40446.38 | 29-DEC-07:15 |
Annual Sum or Average | 0.00 | 18583.93 | ||||||
Minimum of Months | 0.00 | 0.00 | 51.18 | 58.31 | 16893.45 | 33643.94 | ||
Maximum of Months | 0.00 | 0.00 | 54.99 | 59.85 | 20265.30 | 40653.20 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.298380E+11 | 0.00 | 0.588169E+12 | 0.127282E+12 | 0.00 | 0.00 |
February | 0.265004E+11 | 0.00 | 0.619413E+12 | 0.114965E+12 | 0.00 | 0.00 |
March | 0.325904E+11 | 0.00 | 0.757114E+12 | 0.127283E+12 | 0.00 | 0.00 |
April | 0.297415E+11 | 0.00 | 0.911343E+12 | 0.123177E+12 | 0.00 | 0.00 |
May | 0.273772E+11 | 0.00 | 0.121938E+13 | 0.127283E+12 | 0.00 | 0.00 |
June | 0.248274E+11 | 0.00 | 0.136731E+13 | 0.123177E+12 | 0.00 | 0.00 |
July | 0.235941E+11 | 0.00 | 0.144135E+13 | 0.127283E+12 | 0.00 | 0.00 |
August | 0.214403E+11 | 0.00 | 0.144829E+13 | 0.127283E+12 | 0.00 | 0.00 |
September | 0.183754E+11 | 0.00 | 0.135531E+13 | 0.123177E+12 | 0.00 | 0.00 |
October | 0.181604E+11 | 0.00 | 0.125873E+13 | 0.127283E+12 | 0.00 | 0.00 |
November | 0.200092E+11 | 0.00 | 0.100361E+13 | 0.123177E+12 | 0.00 | 0.00 |
December | 0.272252E+11 | 0.00 | 0.733564E+12 | 0.127283E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.299680E+12 | 0.00 | 0.127036E+14 | 0.149865E+13 | 0.00 | 0.00 |
Minimum of Months | 0.181604E+11 | 0.00 | 0.588169E+12 | 0.114965E+12 | 0.00 | 0.00 |
Maximum of Months | 0.325904E+11 | 0.00 | 0.144829E+13 | 0.127283E+12 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 16088.21 | 0.00 | 0.678594E+11 | 0.587890E+10 | 0.00 | 0.00 |
February | 10164.89 | 0.00 | 0.730381E+11 | 0.530997E+10 | 0.00 | 0.00 |
March | 10841.74 | 0.00 | 0.884958E+11 | 0.587890E+10 | 0.00 | 0.00 |
April | 10483.25 | 0.00 | 0.104580E+12 | 0.568926E+10 | 0.00 | 0.00 |
May | 9159.30 | 0.00 | 0.131409E+12 | 0.587890E+10 | 0.00 | 0.00 |
June | 6740.83 | 0.00 | 0.141915E+12 | 0.568926E+10 | 0.00 | 0.00 |
July | 8790.63 | 0.00 | 0.147828E+12 | 0.587890E+10 | 0.00 | 0.00 |
August | 5251.23 | 0.00 | 0.150052E+12 | 0.587890E+10 | 0.00 | 0.00 |
September | 9623.38 | 0.00 | 0.140049E+12 | 0.568926E+10 | 0.00 | 0.00 |
October | 7210.07 | 0.00 | 0.134316E+12 | 0.587890E+10 | 0.00 | 0.00 |
November | 12189.19 | 0.00 | 0.111940E+12 | 0.568926E+10 | 0.00 | 0.00 |
December | 15792.48 | 0.00 | 0.842073E+11 | 0.587890E+10 | 0.00 | 0.00 |
Annual Sum or Average | 122335.18 | 0.00 | 0.137569E+13 | 0.692193E+11 | 0.00 | 0.00 |
Minimum of Months | 5251.23 | 0.00 | 0.678594E+11 | 0.530997E+10 | 0.00 | 0.00 |
Maximum of Months | 16088.21 | 0.00 | 0.150052E+12 | 0.587890E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.127282E+12 | 0.588169E+12 | 0.298380E+11 | 0.125217E+11 | 0.138372E+12 | 0.00 | 0.00 | 0.00 |
February | 0.114965E+12 | 0.619413E+12 | 0.265004E+11 | 0.171375E+11 | 0.171466E+12 | 0.00 | 0.00 | 0.00 |
March | 0.127283E+12 | 0.757114E+12 | 0.325904E+11 | 0.132702E+11 | 0.285859E+12 | 0.00 | 0.00 | 0.00 |
April | 0.123177E+12 | 0.911343E+12 | 0.297415E+11 | 0.258582E+10 | 0.377056E+12 | 0.00 | 0.00 | 0.00 |
May | 0.127283E+12 | 0.121938E+13 | 0.273772E+11 | 0.00 | 0.736867E+12 | 0.00 | 0.00 | 0.00 |
June | 0.123177E+12 | 0.136731E+13 | 0.248274E+11 | 0.00 | 0.953028E+12 | 0.00 | 0.00 | 0.00 |
July | 0.127283E+12 | 0.144135E+13 | 0.235941E+11 | 0.00 | 0.101775E+13 | 0.00 | 0.00 | 0.00 |
August | 0.127283E+12 | 0.144829E+13 | 0.214403E+11 | 0.00 | 0.103113E+13 | 0.00 | 0.00 | 0.00 |
September | 0.123177E+12 | 0.135531E+13 | 0.183754E+11 | 0.00 | 0.931071E+12 | 0.00 | 0.00 | 0.00 |
October | 0.127283E+12 | 0.125873E+13 | 0.181604E+11 | 0.00 | 0.777788E+12 | 0.00 | 0.00 | 0.00 |
November | 0.123177E+12 | 0.100361E+13 | 0.200092E+11 | 0.494369E+10 | 0.470502E+12 | 0.00 | 0.00 | 0.00 |
December | 0.127283E+12 | 0.733564E+12 | 0.272252E+11 | 0.207733E+11 | 0.238416E+12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.149865E+13 | 0.127036E+14 | 0.299680E+12 | 0.712322E+11 | 0.712930E+13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.114965E+12 | 0.588169E+12 | 0.181604E+11 | 0.00 | 0.138372E+12 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.127283E+12 | 0.144829E+13 | 0.325904E+11 | 0.207733E+11 | 0.103113E+13 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.587890E+10 | 0.678594E+11 | 16088.21 | 0.205720E+10 | 0.137647E+11 | 0.00 | 0.00 | 0.00 |
February | 0.530997E+10 | 0.730381E+11 | 10164.89 | 0.220812E+10 | 0.170978E+11 | 0.00 | 0.00 | 0.00 |
March | 0.587890E+10 | 0.884958E+11 | 10841.74 | 0.185009E+10 | 0.300033E+11 | 0.00 | 0.00 | 0.00 |
April | 0.568926E+10 | 0.104580E+12 | 10483.25 | 56728160.02 | 0.411858E+11 | 0.00 | 0.00 | 0.00 |
May | 0.587890E+10 | 0.131409E+12 | 9159.30 | 0.00 | 0.806956E+11 | 0.00 | 0.00 | 0.00 |
June | 0.568926E+10 | 0.141915E+12 | 6740.83 | 0.00 | 0.103606E+12 | 0.00 | 0.00 | 0.00 |
July | 0.587890E+10 | 0.147828E+12 | 8790.63 | 0.00 | 0.110840E+12 | 0.00 | 0.00 | 0.00 |
August | 0.587890E+10 | 0.150052E+12 | 5251.23 | 0.00 | 0.111911E+12 | 0.00 | 0.00 | 0.00 |
September | 0.568926E+10 | 0.140049E+12 | 9623.38 | 0.00 | 0.102357E+12 | 0.00 | 0.00 | 0.00 |
October | 0.587890E+10 | 0.134316E+12 | 7210.07 | 0.00 | 0.860742E+11 | 0.00 | 0.00 | 0.00 |
November | 0.568926E+10 | 0.111940E+12 | 12189.19 | 0.571323E+09 | 0.509871E+11 | 0.00 | 0.00 | 0.00 |
December | 0.587890E+10 | 0.842073E+11 | 15792.48 | 0.273017E+10 | 0.246607E+11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.692193E+11 | 0.137569E+13 | 122335.18 | 0.947364E+10 | 0.773183E+12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.530997E+10 | 0.678594E+11 | 5251.23 | 0.00 | 0.137647E+11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.587890E+10 | 0.150052E+12 | 16088.21 | 0.273017E+10 | 0.111911E+12 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.127282E+12 | 0.298380E+11 | 0.588169E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.114965E+12 | 0.265004E+11 | 0.619413E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.127283E+12 | 0.325904E+11 | 0.757114E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.123177E+12 | 0.297415E+11 | 0.911343E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.127283E+12 | 0.273772E+11 | 0.121938E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.123177E+12 | 0.248274E+11 | 0.136731E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.127283E+12 | 0.235941E+11 | 0.144135E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.127283E+12 | 0.214403E+11 | 0.144829E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.123177E+12 | 0.183754E+11 | 0.135531E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.127283E+12 | 0.181604E+11 | 0.125873E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.123177E+12 | 0.200092E+11 | 0.100361E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.127283E+12 | 0.272252E+11 | 0.733564E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.149865E+13 | 0.299680E+12 | 0.127036E+14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.114965E+12 | 0.181604E+11 | 0.588169E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.127283E+12 | 0.325904E+11 | 0.144829E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.587890E+10 | 16088.21 | 0.678594E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.530997E+10 | 10164.89 | 0.730381E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.587890E+10 | 10841.74 | 0.884958E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.568926E+10 | 10483.25 | 0.104580E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.587890E+10 | 9159.30 | 0.131409E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.568926E+10 | 6740.83 | 0.141915E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.587890E+10 | 8790.63 | 0.147828E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.587890E+10 | 5251.23 | 0.150052E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.568926E+10 | 9623.38 | 0.140049E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.587890E+10 | 7210.07 | 0.134316E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.568926E+10 | 12189.19 | 0.111940E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.587890E+10 | 15792.48 | 0.842073E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.692193E+11 | 122335.18 | 0.137569E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.530997E+10 | 5251.23 | 0.678594E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.587890E+10 | 16088.21 | 0.150052E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.262209E+11 | 0.00 | 0.00 | 0.00 | 0.192311E+11 | 0.00 | 0.00 | 0.00 | 2.00 |
February | 0.160115E+11 | 0.00 | 0.00 | 0.00 | 0.200933E+11 | 0.00 | 0.00 | 0.00 | 1.99 |
March | 0.153995E+11 | 0.00 | 0.00 | 0.00 | 0.279969E+11 | 0.00 | 0.00 | 0.00 | 1.99 |
April | 0.280847E+10 | 0.00 | 0.00 | 0.00 | 0.355758E+11 | 0.00 | 0.00 | 0.00 | 2.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.662112E+11 | 0.00 | 0.00 | 0.00 | 2.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.855684E+11 | 0.00 | 0.00 | 0.00 | 2.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.912862E+11 | 0.00 | 0.00 | 0.00 | 2.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.927575E+11 | 0.00 | 0.00 | 0.00 | 2.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.839501E+11 | 0.00 | 0.00 | 0.00 | 2.01 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.706361E+11 | 0.00 | 0.00 | 0.00 | 2.01 |
November | 0.629428E+10 | 0.00 | 0.00 | 0.00 | 0.504191E+11 | 0.00 | 0.00 | 0.00 | 2.00 |
December | 0.188427E+11 | 0.00 | 0.00 | 0.00 | 0.290404E+11 | 0.00 | 0.00 | 0.00 | 2.00 |
Annual Sum or Average | 0.855773E+11 | 0.00 | 0.00 | 0.00 | 0.672766E+12 | 0.00 | 0.00 | 0.00 | 2.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.192311E+11 | 0.00 | 0.00 | 0.00 | 1.99 |
Maximum of Months | 0.262209E+11 | 0.00 | 0.00 | 0.00 | 0.927575E+11 | 0.00 | 0.00 | 0.00 | 2.01 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.285899E+10 | 0.193392E+09 | 0.00 | 64586.95 | 0.192825E+10 | 0.00 | 33719990.79 | 0.00 | 4.00 |
February | 0.173264E+10 | 0.141721E+09 | 0.00 | 6193.21 | 0.207504E+10 | 33179049.25 | 613567.11 | 0.00 | 4.00 |
March | 0.169892E+10 | 8418000.97 | 0.00 | 88.55 | 0.308029E+10 | 0.00 | 1933.93 | 0.00 | 4.00 |
April | 0.309840E+09 | 0.00 | 0.00 | 0.00 | 0.392484E+10 | 0.00 | 0.00 | 0.00 | 4.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.730464E+10 | 0.00 | 0.00 | 0.00 | 4.02 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.944019E+10 | 0.00 | 0.00 | 0.00 | 4.01 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.100710E+11 | 0.00 | 0.00 | 0.00 | 4.01 |
August | 0.00 | 37504798.67 | 0.00 | 0.00 | 0.101958E+11 | 0.00 | 0.00 | 0.00 | 4.02 |
September | 0.00 | 0.729782E+09 | 0.00 | 0.00 | 0.853186E+10 | 0.00 | 0.00 | 0.00 | 4.03 |
October | 0.00 | 0.982940E+09 | 0.00 | 0.00 | 0.680987E+10 | 0.00 | 0.00 | 0.00 | 4.03 |
November | 0.686890E+09 | 0.589043E+09 | 0.00 | 21696.76 | 0.497335E+10 | 0.00 | 7493184.97 | 0.00 | 4.01 |
December | 0.207237E+10 | 0.366377E+09 | 0.00 | 7863.38 | 0.283746E+10 | 0.00 | 6413321.28 | 0.00 | 4.00 |
Annual Sum or Average | 0.935965E+10 | 0.304918E+10 | 0.00 | 100428.85 | 0.711726E+11 | 33179049.25 | 48241998.10 | 0.00 | 4.01 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.192825E+10 | 0.00 | 0.00 | 0.00 | 4.00 |
Maximum of Months | 0.285899E+10 | 0.982940E+09 | 0.00 | 64586.95 | 0.101958E+11 | 33179049.25 | 33719990.79 | 0.00 | 4.03 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.238643E+10 | 0.00 | 0.00 | 0.00 | 0.175028E+10 | 0.00 | 0.00 | 0.00 | 2.85 |
February | 0.145725E+10 | 0.00 | 0.00 | 0.00 | 0.182875E+10 | 0.00 | 0.00 | 0.00 | 2.85 |
March | 0.140155E+10 | 0.00 | 0.00 | 0.00 | 0.254807E+10 | 0.00 | 0.00 | 0.00 | 2.85 |
April | 0.255607E+09 | 0.00 | 0.00 | 0.00 | 0.323785E+10 | 0.00 | 0.00 | 0.00 | 2.85 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.602607E+10 | 0.00 | 0.00 | 0.00 | 2.86 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.778782E+10 | 0.00 | 0.00 | 0.00 | 2.86 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.830822E+10 | 0.00 | 0.00 | 0.00 | 2.86 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.844212E+10 | 0.00 | 0.00 | 0.00 | 2.86 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.764053E+10 | 0.00 | 0.00 | 0.00 | 2.86 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.642879E+10 | 0.00 | 0.00 | 0.00 | 2.87 |
November | 0.572860E+09 | 0.00 | 0.00 | 0.00 | 0.458878E+10 | 0.00 | 0.00 | 0.00 | 2.86 |
December | 0.171493E+10 | 0.00 | 0.00 | 0.00 | 0.264305E+10 | 0.00 | 0.00 | 0.00 | 2.85 |
Annual Sum or Average | 0.778863E+10 | 0.00 | 0.00 | 0.00 | 0.612303E+11 | 0.00 | 0.00 | 0.00 | 2.86 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.175028E+10 | 0.00 | 0.00 | 0.00 | 2.85 |
Maximum of Months | 0.238643E+10 | 0.00 | 0.00 | 0.00 | 0.844212E+10 | 0.00 | 0.00 | 0.00 | 2.87 |
Report: MechanicalVentilationLoadsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.257573E+10 | 0.00 | 0.00 | 0.00 | 0.188911E+10 | 0.00 | 0.00 | 0.00 | 1.45 |
February | 0.157284E+10 | 0.00 | 0.00 | 0.00 | 0.197381E+10 | 0.00 | 0.00 | 0.00 | 1.45 |
March | 0.151272E+10 | 0.00 | 0.00 | 0.00 | 0.275019E+10 | 0.00 | 0.00 | 0.00 | 1.45 |
April | 0.275882E+09 | 0.00 | 0.00 | 0.00 | 0.349468E+10 | 0.00 | 0.00 | 0.00 | 1.46 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.650406E+10 | 0.00 | 0.00 | 0.00 | 1.46 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.840555E+10 | 0.00 | 0.00 | 0.00 | 1.46 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.896723E+10 | 0.00 | 0.00 | 0.00 | 1.46 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.911175E+10 | 0.00 | 0.00 | 0.00 | 1.46 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.824658E+10 | 0.00 | 0.00 | 0.00 | 1.46 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.693872E+10 | 0.00 | 0.00 | 0.00 | 1.46 |
November | 0.618299E+09 | 0.00 | 0.00 | 0.00 | 0.495276E+10 | 0.00 | 0.00 | 0.00 | 1.46 |
December | 0.185096E+10 | 0.00 | 0.00 | 0.00 | 0.285270E+10 | 0.00 | 0.00 | 0.00 | 1.45 |
Annual Sum or Average | 0.840642E+10 | 0.00 | 0.00 | 0.00 | 0.660871E+11 | 0.00 | 0.00 | 0.00 | 1.46 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.188911E+10 | 0.00 | 0.00 | 0.00 | 1.45 |
Maximum of Months | 0.257573E+10 | 0.00 | 0.00 | 0.00 | 0.911175E+10 | 0.00 | 0.00 | 0.00 | 1.46 |
Report: MechanicalVentilationLoadsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.128591E+10 | 0.00 | 0.00 | 0.00 | 0.943122E+09 | 0.00 | 0.00 | 0.00 | 1.26 |
February | 0.783371E+09 | 0.00 | 0.00 | 0.00 | 0.985407E+09 | 1854943.49 | 0.00 | 0.00 | 1.26 |
March | 0.754511E+09 | 0.00 | 0.00 | 0.00 | 0.137301E+10 | 701805.99 | 0.00 | 0.00 | 1.26 |
April | 0.137732E+09 | 0.00 | 0.00 | 0.00 | 0.174469E+10 | 0.00 | 0.00 | 0.00 | 1.26 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.324709E+10 | 0.00 | 0.00 | 0.00 | 1.26 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.419640E+10 | 0.00 | 0.00 | 0.00 | 1.26 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.447681E+10 | 0.00 | 0.00 | 0.00 | 1.26 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.454896E+10 | 0.00 | 0.00 | 0.00 | 1.26 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.411703E+10 | 0.00 | 0.00 | 0.00 | 1.26 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.346410E+10 | 0.00 | 0.00 | 0.00 | 1.27 |
November | 0.308680E+09 | 0.00 | 0.00 | 0.00 | 0.247262E+10 | 0.00 | 0.00 | 0.00 | 1.26 |
December | 0.924074E+09 | 0.00 | 0.00 | 0.00 | 0.142419E+10 | 0.00 | 0.00 | 0.00 | 1.26 |
Annual Sum or Average | 0.419428E+10 | 0.00 | 0.00 | 0.00 | 0.329934E+11 | 2556749.48 | 0.00 | 0.00 | 1.26 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.943122E+09 | 0.00 | 0.00 | 0.00 | 1.26 |
Maximum of Months | 0.128591E+10 | 0.00 | 0.00 | 0.00 | 0.454896E+10 | 1854943.49 | 0.00 | 0.00 | 1.27 |
Report: MechanicalVentilationLoadsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.531943E+09 | 0.229122E+11 | 0.00 | 34496234.67 | 0.693328E+09 | 0.00 | 0.316242E+11 | 0.00 | 38.27 |
February | 0.242170E+09 | 0.238829E+11 | 0.00 | 24000619.47 | 0.781358E+09 | 0.00 | 0.193891E+11 | 0.00 | 38.21 |
March | 0.397700E+09 | 0.332103E+11 | 0.00 | 22587070.13 | 0.115366E+10 | 0.00 | 0.184848E+11 | 0.00 | 38.23 |
April | 50055966.14 | 0.419534E+11 | 0.00 | 7780560.34 | 0.171305E+10 | 0.00 | 0.338968E+10 | 0.00 | 38.29 |
May | 0.00 | 0.782894E+11 | 0.00 | 0.00 | 0.297843E+10 | 0.00 | 0.00 | 0.00 | 38.39 |
June | 0.00 | 0.101408E+12 | 0.00 | 0.00 | 0.361633E+10 | 0.00 | 0.00 | 0.00 | 38.35 |
July | 0.00 | 0.108073E+12 | 0.00 | 0.00 | 0.396749E+10 | 0.00 | 0.00 | 0.00 | 38.33 |
August | 0.00 | 0.109945E+12 | 0.00 | 0.00 | 0.390285E+10 | 0.00 | 0.00 | 0.00 | 38.35 |
September | 0.00 | 0.994904E+11 | 0.00 | 0.00 | 0.354771E+10 | 0.00 | 0.00 | 0.00 | 38.43 |
October | 0.00 | 0.836920E+11 | 0.00 | 0.00 | 0.300757E+10 | 0.00 | 0.00 | 0.00 | 38.48 |
November | 91118546.54 | 0.599700E+11 | 0.00 | 9324013.90 | 0.191677E+10 | 0.00 | 0.762532E+10 | 0.00 | 38.34 |
December | 0.328712E+09 | 0.346859E+11 | 0.00 | 27382255.70 | 0.959643E+09 | 0.00 | 0.227787E+11 | 0.00 | 38.26 |
Annual Sum or Average | 0.164170E+10 | 0.797512E+12 | 0.00 | 0.125571E+09 | 0.282382E+11 | 0.00 | 0.103292E+12 | 0.00 | 38.33 |
Minimum of Months | 0.00 | 0.229122E+11 | 0.00 | 0.00 | 0.693328E+09 | 0.00 | 0.00 | 0.00 | 38.21 |
Maximum of Months | 0.531943E+09 | 0.109945E+12 | 0.00 | 34496234.67 | 0.396749E+10 | 0.00 | 0.316242E+11 | 0.00 | 38.48 |
Report: MechanicalVentilationLoadsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.114904E+11 | 0.329657E+10 | 0.00 | 599698.67 | 0.616526E+10 | 0.00 | 0.140983E+10 | 0.00 | 6.35 |
February | 0.677927E+10 | 0.277328E+10 | 0.00 | 322279.87 | 0.711277E+10 | 0.00 | 0.109815E+10 | 0.00 | 6.34 |
March | 0.668658E+10 | 0.358045E+10 | 0.00 | 254680.18 | 0.101942E+11 | 0.00 | 0.889810E+09 | 0.00 | 6.34 |
April | 0.101273E+10 | 0.438912E+10 | 0.00 | 202150.93 | 0.131144E+11 | 0.00 | 0.368854E+09 | 0.00 | 6.35 |
May | 0.00 | 0.883325E+10 | 0.00 | 0.00 | 0.237431E+11 | 0.00 | 0.00 | 0.00 | 6.37 |
June | 0.00 | 0.144718E+11 | 0.00 | 0.00 | 0.276284E+11 | 0.00 | 0.00 | 0.00 | 6.37 |
July | 0.00 | 0.149640E+11 | 0.00 | 0.00 | 0.299494E+11 | 0.00 | 0.00 | 0.00 | 6.36 |
August | 0.00 | 0.163203E+11 | 0.00 | 0.00 | 0.293170E+11 | 0.00 | 0.00 | 0.00 | 6.37 |
September | 0.00 | 0.182097E+11 | 0.00 | 0.00 | 0.230942E+11 | 0.00 | 0.00 | 0.00 | 6.38 |
October | 0.00 | 0.170660E+11 | 0.00 | 0.00 | 0.176874E+11 | 0.00 | 0.00 | 0.00 | 6.39 |
November | 0.274629E+10 | 0.109757E+11 | 0.00 | 196265.51 | 0.138308E+11 | 0.00 | 0.350340E+09 | 0.00 | 6.37 |
December | 0.821371E+10 | 0.541367E+10 | 0.00 | 214159.06 | 0.887440E+10 | 0.00 | 0.105682E+10 | 0.00 | 6.35 |
Annual Sum or Average | 0.369290E+11 | 0.120294E+12 | 0.00 | 1789234.22 | 0.210711E+12 | 0.00 | 0.517381E+10 | 0.00 | 6.36 |
Minimum of Months | 0.00 | 0.277328E+10 | 0.00 | 0.00 | 0.616526E+10 | 0.00 | 0.00 | 0.00 | 6.34 |
Maximum of Months | 0.114904E+11 | 0.182097E+11 | 0.00 | 599698.67 | 0.299494E+11 | 0.00 | 0.140983E+10 | 0.00 | 6.39 |
Report: MechanicalVentilationLoadsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.449063E+11 | 0.00 | 0.00 | 0.00 | 0.329355E+11 | 0.00 | 0.00 | 0.00 | 3.19 |
February | 0.274215E+11 | 0.00 | 0.00 | 0.00 | 0.344122E+11 | 0.00 | 0.00 | 0.00 | 3.18 |
March | 0.263734E+11 | 0.00 | 0.00 | 0.00 | 0.479478E+11 | 0.00 | 0.00 | 0.00 | 3.18 |
April | 0.480983E+10 | 0.00 | 0.00 | 0.00 | 0.609277E+11 | 0.00 | 0.00 | 0.00 | 3.19 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.113394E+12 | 0.00 | 0.00 | 0.00 | 3.20 |
June | 0.00 | 0.143793E+10 | 0.00 | 0.00 | 0.145108E+12 | 0.00 | 0.00 | 0.00 | 3.20 |
July | 0.00 | 0.164141E+10 | 0.00 | 0.00 | 0.154697E+12 | 0.00 | 0.00 | 0.00 | 3.20 |
August | 0.00 | 0.142597E+10 | 0.00 | 0.00 | 0.157432E+12 | 0.00 | 0.00 | 0.00 | 3.20 |
September | 0.00 | 0.137256E+10 | 0.00 | 0.00 | 0.142402E+12 | 0.00 | 0.00 | 0.00 | 3.20 |
October | 0.00 | 0.498343E+09 | 0.00 | 0.00 | 0.120474E+12 | 0.00 | 0.00 | 0.00 | 3.21 |
November | 0.107797E+11 | 99635772.01 | 0.00 | 0.00 | 0.862489E+11 | 0.00 | 0.00 | 0.00 | 3.20 |
December | 0.322703E+11 | 0.00 | 0.00 | 0.00 | 0.497351E+11 | 0.00 | 0.00 | 0.00 | 3.19 |
Annual Sum or Average | 0.146561E+12 | 0.647585E+10 | 0.00 | 0.00 | 0.114571E+13 | 0.00 | 0.00 | 0.00 | 3.19 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.329355E+11 | 0.00 | 0.00 | 0.00 | 3.18 |
Maximum of Months | 0.449063E+11 | 0.164141E+10 | 0.00 | 0.00 | 0.157432E+12 | 0.00 | 0.00 | 0.00 | 3.21 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 93353463.63 | 0.443637E+09 | 614172.50 | 4603700.06 | 49323191.75 | 36840680.62 | 0.468647E+09 | 31912.81 | 0.47 |
February | 41722106.19 | 0.436115E+09 | 541942.71 | 3536759.92 | 47344842.38 | 41714500.34 | 0.263724E+09 | 27347.61 | 0.47 |
March | 62417380.19 | 0.631924E+09 | 555679.90 | 2926948.85 | 48362077.00 | 28278490.28 | 0.249998E+09 | 28089.77 | 0.47 |
April | 5147660.54 | 0.845818E+09 | 755973.86 | 1104929.80 | 48177917.23 | 64041.28 | 45787766.42 | 38867.49 | 0.47 |
May | 0.00 | 0.144072E+10 | 1018693.77 | 0.00 | 77587496.11 | 0.00 | 0.00 | 28169.11 | 0.47 |
June | 0.00 | 0.180463E+10 | 758247.92 | 0.00 | 84914890.79 | 0.00 | 0.00 | 14881.45 | 0.47 |
July | 0.00 | 0.193145E+10 | 187673.09 | 0.00 | 81372268.78 | 0.00 | 0.00 | 3457.67 | 0.47 |
August | 0.00 | 0.195571E+10 | 730797.27 | 0.00 | 98133955.58 | 0.00 | 0.00 | 17900.11 | 0.47 |
September | 0.00 | 0.178827E+10 | 946044.61 | 0.00 | 80505669.81 | 0.00 | 0.00 | 18199.97 | 0.48 |
October | 0.00 | 0.155181E+10 | 958490.70 | 0.00 | 75947138.31 | 0.00 | 0.00 | 27605.28 | 0.48 |
November | 16277451.33 | 0.114524E+10 | 617415.99 | 1269520.70 | 78602238.95 | 11614536.13 | 0.114639E+09 | 20853.56 | 0.47 |
December | 63592521.29 | 0.644071E+09 | 584577.21 | 3234800.99 | 53744361.07 | 51952263.04 | 0.301212E+09 | 28605.74 | 0.47 |
Annual Sum or Average | 0.282511E+09 | 0.146194E+11 | 8269709.53 | 16676660.32 | 0.824016E+09 | 0.170465E+09 | 0.144401E+10 | 285890.56 | 0.47 |
Minimum of Months | 0.00 | 0.436115E+09 | 187673.09 | 0.00 | 47344842.38 | 0.00 | 0.00 | 3457.67 | 0.47 |
Maximum of Months | 93353463.63 | 0.195571E+10 | 1018693.77 | 4603700.06 | 98133955.58 | 51952263.04 | 0.468647E+09 | 38867.49 | 0.48 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.117595E+09 | 0.413822E+09 | 859403.28 | 2701951.27 | 78821283.02 | 92854496.45 | 0.390223E+09 | 45427.06 | 0.47 |
February | 49204918.15 | 0.421341E+09 | 718898.19 | 2476081.11 | 61872914.26 | 58325520.97 | 0.240650E+09 | 39275.91 | 0.47 |
March | 67804098.61 | 0.621006E+09 | 699382.25 | 2294967.56 | 59046749.65 | 47368573.43 | 0.226113E+09 | 38600.80 | 0.47 |
April | 5863116.08 | 0.840638E+09 | 861736.57 | 1028019.73 | 53145232.14 | 64033.78 | 45143123.66 | 40896.37 | 0.47 |
May | 0.00 | 0.144174E+10 | 1016793.38 | 0.00 | 76392222.23 | 0.00 | 0.00 | 28465.19 | 0.47 |
June | 0.00 | 0.180821E+10 | 558634.17 | 0.00 | 81316778.77 | 0.00 | 0.00 | 12088.63 | 0.47 |
July | 0.00 | 0.193409E+10 | 126445.04 | 0.00 | 78553369.81 | 0.00 | 0.00 | 1535.65 | 0.47 |
August | 0.00 | 0.195420E+10 | 804474.05 | 0.00 | 99332038.03 | 0.00 | 0.00 | 20266.02 | 0.47 |
September | 0.00 | 0.177600E+10 | 1020508.03 | 0.00 | 92475309.54 | 0.00 | 0.00 | 24102.00 | 0.48 |
October | 0.00 | 0.153106E+10 | 1684460.41 | 0.00 | 95758103.12 | 0.00 | 0.00 | 47791.02 | 0.48 |
November | 18446462.06 | 0.111717E+10 | 1571010.47 | 895094.03 | 0.105548E+09 | 23282681.64 | 0.101159E+09 | 47694.47 | 0.47 |
December | 83795140.25 | 0.619938E+09 | 976317.25 | 2011226.43 | 77388909.85 | 92389021.73 | 0.241747E+09 | 43826.60 | 0.47 |
Annual Sum or Average | 0.342708E+09 | 0.144792E+11 | 10898063.09 | 11407340.14 | 0.959651E+09 | 0.314284E+09 | 0.124503E+10 | 389969.71 | 0.47 |
Minimum of Months | 0.00 | 0.413822E+09 | 126445.04 | 0.00 | 53145232.14 | 0.00 | 0.00 | 1535.65 | 0.47 |
Maximum of Months | 0.117595E+09 | 0.195420E+10 | 1684460.41 | 2701951.27 | 0.105548E+09 | 92854496.45 | 0.390223E+09 | 47791.02 | 0.48 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.145364E+10 | 0.665502E+10 | 0.00 | 52685356.21 | 37836460.69 | 0.00 | 0.667585E+10 | 0.00 | 0.54 |
February | 0.102440E+10 | 0.654733E+10 | 0.00 | 33668867.06 | 15666599.67 | 0.00 | 0.369707E+10 | 0.00 | 0.54 |
March | 0.129438E+10 | 0.923199E+10 | 0.00 | 21473026.62 | 0.00 | 0.00 | 0.334333E+10 | 0.00 | 0.54 |
April | 0.134566E+09 | 0.121326E+11 | 0.00 | 6970828.72 | 0.00 | 0.00 | 0.564952E+09 | 0.00 | 0.54 |
May | 0.00 | 0.206011E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.54 |
June | 0.00 | 0.256310E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.54 |
July | 0.00 | 0.272946E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.54 |
August | 0.00 | 0.278584E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.54 |
September | 0.00 | 0.253520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.54 |
October | 0.00 | 0.220843E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.54 |
November | 0.481376E+09 | 0.165680E+11 | 0.00 | 12581689.16 | 34830060.97 | 0.00 | 0.145585E+10 | 0.00 | 0.54 |
December | 0.116325E+10 | 0.940677E+10 | 0.00 | 36848462.89 | 63295161.36 | 0.00 | 0.449461E+10 | 0.00 | 0.54 |
Annual Sum or Average | 0.555162E+10 | 0.209363E+12 | 0.00 | 0.164228E+09 | 0.151628E+09 | 0.00 | 0.202317E+11 | 0.00 | 0.54 |
Minimum of Months | 0.00 | 0.654733E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.54 |
Maximum of Months | 0.145364E+10 | 0.278584E+11 | 0.00 | 52685356.21 | 63295161.36 | 0.00 | 0.667585E+10 | 0.00 | 0.54 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.168740E+10 | 0.484241E+10 | 8659714.86 | 42679792.42 | 0.184344E+10 | 20295175.42 | 0.643404E+10 | 167691.14 | 0.54 |
February | 0.702085E+09 | 0.477228E+10 | 5992556.35 | 33606389.57 | 0.178638E+10 | 12938292.45 | 0.400781E+10 | 134177.97 | 0.54 |
March | 0.961860E+09 | 0.725598E+10 | 10132923.03 | 27644446.67 | 0.196819E+10 | 9068062.80 | 0.366189E+10 | 213671.26 | 0.54 |
April | 0.101119E+09 | 0.100614E+11 | 9351238.85 | 10234265.66 | 0.206498E+10 | 205560.23 | 0.595124E+09 | 192629.88 | 0.54 |
May | 0.00 | 0.184096E+11 | 12339612.03 | 0.00 | 0.218470E+10 | 0.00 | 0.00 | 75177.91 | 0.54 |
June | 0.00 | 0.234322E+11 | 20676216.02 | 0.00 | 0.218503E+10 | 0.00 | 0.00 | 118659.80 | 0.54 |
July | 0.00 | 0.251050E+11 | 22449205.49 | 0.00 | 0.217451E+10 | 0.00 | 0.00 | 99158.11 | 0.54 |
August | 0.00 | 0.250030E+11 | 16337665.75 | 0.00 | 0.284664E+10 | 0.00 | 0.00 | 65725.71 | 0.54 |
September | 0.00 | 0.227863E+11 | 4348982.80 | 0.00 | 0.256820E+10 | 0.00 | 0.00 | 5240.09 | 0.54 |
October | 0.00 | 0.189307E+11 | 16093228.90 | 0.00 | 0.314345E+10 | 0.00 | 0.00 | 126093.52 | 0.54 |
November | 0.300177E+09 | 0.133316E+11 | 18566933.68 | 14020206.71 | 0.325698E+10 | 3278960.47 | 0.163286E+10 | 209667.93 | 0.54 |
December | 0.119974E+10 | 0.721888E+10 | 12018250.83 | 33945528.94 | 0.224162E+10 | 13668680.67 | 0.444891E+10 | 136437.39 | 0.54 |
Annual Sum or Average | 0.495238E+10 | 0.181149E+12 | 0.156967E+09 | 0.162131E+09 | 0.282641E+11 | 59454732.04 | 0.207806E+11 | 1544330.70 | 0.54 |
Minimum of Months | 0.00 | 0.477228E+10 | 4348982.80 | 0.00 | 0.178638E+10 | 0.00 | 0.00 | 5240.09 | 0.54 |
Maximum of Months | 0.168740E+10 | 0.251050E+11 | 22449205.49 | 42679792.42 | 0.325698E+10 | 20295175.42 | 0.643404E+10 | 213671.26 | 0.54 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 76451210.15 | 0.453372E+09 | 234539.09 | 4795091.44 | 39985289.92 | 48620222.75 | 0.473579E+09 | 14278.73 | 0.47 |
February | 39543295.08 | 0.444138E+09 | 239495.03 | 3925316.51 | 39641201.44 | 40495773.25 | 0.266733E+09 | 10754.72 | 0.47 |
March | 39960423.88 | 0.643649E+09 | 164310.47 | 3095605.83 | 37051285.20 | 24625579.47 | 0.275939E+09 | 6100.82 | 0.47 |
April | 3186881.17 | 0.863769E+09 | 79642.96 | 1204980.19 | 30936425.96 | 24970.97 | 47687565.71 | 5337.23 | 0.47 |
May | 0.00 | 0.146554E+10 | 176849.78 | 0.00 | 53635135.62 | 0.00 | 0.00 | 3235.82 | 0.47 |
June | 0.00 | 0.183964E+10 | 44410.64 | 0.00 | 50636332.02 | 0.00 | 0.00 | 884.21 | 0.47 |
July | 0.00 | 0.196085E+10 | 0.00 | 0.00 | 52159677.31 | 0.00 | 0.00 | 0.00 | 0.47 |
August | 0.00 | 0.198435E+10 | 41782.02 | 0.00 | 70201881.22 | 0.00 | 0.00 | 2115.48 | 0.47 |
September | 0.00 | 0.181846E+10 | 0.00 | 0.00 | 51281064.32 | 0.00 | 0.00 | 0.00 | 0.48 |
October | 0.00 | 0.157767E+10 | 36273.32 | 0.00 | 51032650.89 | 0.00 | 0.00 | 1007.76 | 0.48 |
November | 14990300.05 | 0.116176E+10 | 256089.52 | 1408105.09 | 62460705.50 | 14193112.58 | 0.113209E+09 | 7264.65 | 0.47 |
December | 67275427.49 | 0.649763E+09 | 239645.10 | 3058926.83 | 48413934.96 | 62648874.09 | 0.287008E+09 | 11753.99 | 0.47 |
Annual Sum or Average | 0.241408E+09 | 0.148629E+11 | 1513037.93 | 17488025.89 | 0.587436E+09 | 0.190609E+09 | 0.146415E+10 | 62733.42 | 0.47 |
Minimum of Months | 0.00 | 0.444138E+09 | 0.00 | 0.00 | 30936425.96 | 0.00 | 0.00 | 0.00 | 0.47 |
Maximum of Months | 76451210.15 | 0.198435E+10 | 256089.52 | 4795091.44 | 70201881.22 | 62648874.09 | 0.473579E+09 | 14278.73 | 0.48 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.124390E+09 | 0.428440E+09 | 560687.51 | 2703896.67 | 64516132.65 | 0.106572E+09 | 0.369708E+09 | 31264.11 | 0.47 |
February | 45097120.21 | 0.433915E+09 | 439449.08 | 2816066.37 | 49592347.91 | 53917052.46 | 0.248826E+09 | 25486.39 | 0.47 |
March | 67053187.34 | 0.635645E+09 | 255491.35 | 2338055.16 | 44870355.47 | 38229679.26 | 0.235959E+09 | 19828.41 | 0.47 |
April | 3331846.01 | 0.859977E+09 | 78578.46 | 1127826.92 | 34623618.25 | 24968.04 | 47613652.28 | 6391.78 | 0.47 |
May | 0.00 | 0.146612E+10 | 176090.37 | 0.00 | 52880249.70 | 0.00 | 0.00 | 3974.14 | 0.47 |
June | 0.00 | 0.184174E+10 | 44362.30 | 0.00 | 48314677.73 | 0.00 | 0.00 | 927.25 | 0.47 |
July | 0.00 | 0.196218E+10 | 0.00 | 0.00 | 50588804.07 | 0.00 | 0.00 | 0.00 | 0.47 |
August | 0.00 | 0.198255E+10 | 109530.71 | 0.00 | 71688187.66 | 0.00 | 0.00 | 2233.77 | 0.47 |
September | 0.00 | 0.181091E+10 | 0.00 | 0.00 | 58607603.04 | 0.00 | 0.00 | 0.00 | 0.48 |
October | 0.00 | 0.156235E+10 | 49531.04 | 0.00 | 66150693.51 | 0.00 | 0.00 | 3585.38 | 0.48 |
November | 21628491.37 | 0.113165E+10 | 404925.28 | 999527.59 | 92267142.21 | 23510567.64 | 97644865.40 | 16134.66 | 0.47 |
December | 88259715.49 | 0.616650E+09 | 656859.93 | 1769160.17 | 81010992.98 | 99578497.40 | 0.230335E+09 | 29224.62 | 0.47 |
Annual Sum or Average | 0.349760E+09 | 0.147321E+11 | 2775506.00 | 11754532.88 | 0.715111E+09 | 0.321833E+09 | 0.123009E+10 | 139050.50 | 0.47 |
Minimum of Months | 0.00 | 0.428440E+09 | 0.00 | 0.00 | 34623618.25 | 0.00 | 0.00 | 0.00 | 0.47 |
Maximum of Months | 0.124390E+09 | 0.198255E+10 | 656859.93 | 2816066.37 | 92267142.21 | 0.106572E+09 | 0.369708E+09 | 31264.11 | 0.48 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.108459E+11 | 0.00 | 0.00 | 0.00 | 0.795466E+10 | 0.00 | 0.00 | 0.00 | 0.84 |
February | 0.662290E+10 | 0.00 | 0.00 | 0.00 | 0.831131E+10 | 0.00 | 0.00 | 0.00 | 0.84 |
March | 0.636976E+10 | 0.00 | 0.00 | 0.00 | 0.115805E+11 | 0.00 | 0.00 | 0.00 | 0.84 |
April | 0.116168E+10 | 0.00 | 0.00 | 0.00 | 0.147154E+11 | 0.00 | 0.00 | 0.00 | 0.84 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.273873E+11 | 0.00 | 0.00 | 0.00 | 0.85 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.353941E+11 | 0.00 | 0.00 | 0.00 | 0.85 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.377592E+11 | 0.00 | 0.00 | 0.00 | 0.85 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.383677E+11 | 0.00 | 0.00 | 0.00 | 0.85 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.347247E+11 | 0.00 | 0.00 | 0.00 | 0.85 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.292175E+11 | 0.00 | 0.00 | 0.00 | 0.85 |
November | 0.260353E+10 | 0.00 | 0.00 | 0.00 | 0.208551E+11 | 0.00 | 0.00 | 0.00 | 0.84 |
December | 0.779401E+10 | 0.00 | 0.00 | 0.00 | 0.120121E+11 | 0.00 | 0.00 | 0.00 | 0.84 |
Annual Sum or Average | 0.353977E+11 | 0.00 | 0.00 | 0.00 | 0.278279E+12 | 0.00 | 0.00 | 0.00 | 0.84 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.795466E+10 | 0.00 | 0.00 | 0.00 | 0.84 |
Maximum of Months | 0.108459E+11 | 0.00 | 0.00 | 0.00 | 0.383677E+11 | 0.00 | 0.00 | 0.00 | 0.85 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 22678497.50 | 0.111776E+09 | 144049.45 | 1099340.96 | 11474560.57 | 25033921.31 | 0.102050E+09 | 6767.80 | 0.47 |
February | 10617167.69 | 0.110210E+09 | 121257.38 | 847611.56 | 10669019.87 | 16327058.09 | 59882441.07 | 6625.14 | 0.47 |
March | 15436919.65 | 0.159587E+09 | 125307.09 | 722945.59 | 10499150.50 | 13505959.45 | 56239275.32 | 5904.40 | 0.47 |
April | 1219561.80 | 0.212655E+09 | 189927.11 | 280037.89 | 10843435.59 | 20509.94 | 11505989.87 | 8783.23 | 0.47 |
May | 0.00 | 0.362672E+09 | 255409.12 | 0.00 | 16905167.04 | 0.00 | 0.00 | 6306.60 | 0.47 |
June | 0.00 | 0.454509E+09 | 206551.97 | 0.00 | 17860949.84 | 0.00 | 0.00 | 3207.37 | 0.47 |
July | 0.00 | 0.486998E+09 | 47034.97 | 0.00 | 16206639.08 | 0.00 | 0.00 | 747.72 | 0.47 |
August | 0.00 | 0.493395E+09 | 201791.54 | 0.00 | 20046984.27 | 0.00 | 0.00 | 4417.64 | 0.47 |
September | 0.00 | 0.449325E+09 | 236401.24 | 0.00 | 17868303.44 | 0.00 | 0.00 | 4659.91 | 0.48 |
October | 0.00 | 0.389614E+09 | 283845.93 | 0.00 | 17280574.85 | 0.00 | 0.00 | 7241.04 | 0.48 |
November | 4069362.83 | 0.288166E+09 | 154615.24 | 293167.47 | 17793758.68 | 7431971.28 | 24155573.49 | 5047.07 | 0.47 |
December | 15647781.12 | 0.162109E+09 | 139971.13 | 746862.19 | 12351759.75 | 22602137.90 | 66001123.18 | 6380.83 | 0.47 |
Annual Sum or Average | 69669290.60 | 0.368102E+10 | 2106162.16 | 3989965.66 | 0.179800E+09 | 84921557.99 | 0.319834E+09 | 66088.74 | 0.47 |
Minimum of Months | 0.00 | 0.110210E+09 | 47034.97 | 0.00 | 10499150.50 | 0.00 | 0.00 | 747.72 | 0.47 |
Maximum of Months | 22678497.50 | 0.493395E+09 | 283845.93 | 1099340.96 | 20046984.27 | 25033921.31 | 0.102050E+09 | 8783.23 | 0.48 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 29234879.89 | 0.106621E+09 | 207427.61 | 620774.79 | 16548451.22 | 49273288.75 | 71714645.38 | 10481.12 | 0.47 |
February | 12154859.46 | 0.106953E+09 | 167709.45 | 582297.43 | 13865024.13 | 23727343.15 | 51199506.06 | 7652.14 | 0.47 |
March | 16921662.84 | 0.157478E+09 | 174905.10 | 559870.92 | 12536406.99 | 19803454.64 | 48610046.58 | 8512.67 | 0.47 |
April | 1290792.11 | 0.211531E+09 | 208855.55 | 261123.90 | 11922021.51 | 20507.54 | 11452149.76 | 9208.15 | 0.47 |
May | 0.00 | 0.363264E+09 | 242082.73 | 0.00 | 16281933.99 | 0.00 | 0.00 | 5826.04 | 0.47 |
June | 0.00 | 0.455490E+09 | 156849.11 | 0.00 | 16874713.27 | 0.00 | 0.00 | 2306.66 | 0.47 |
July | 0.00 | 0.487665E+09 | 31611.38 | 0.00 | 15496537.05 | 0.00 | 0.00 | 383.80 | 0.47 |
August | 0.00 | 0.492787E+09 | 201605.53 | 0.00 | 20594574.54 | 0.00 | 0.00 | 4579.49 | 0.47 |
September | 0.00 | 0.447018E+09 | 271687.31 | 0.00 | 20084258.92 | 0.00 | 0.00 | 5430.22 | 0.48 |
October | 0.00 | 0.384567E+09 | 438838.28 | 0.00 | 22120608.11 | 0.00 | 0.00 | 11158.77 | 0.48 |
November | 4479126.03 | 0.281569E+09 | 407608.39 | 201589.64 | 24097366.84 | 10288783.84 | 20976363.50 | 10215.65 | 0.47 |
December | 20759570.74 | 0.157465E+09 | 241090.61 | 438730.26 | 16871809.96 | 36134563.74 | 47652737.61 | 8959.40 | 0.47 |
Annual Sum or Average | 84840891.07 | 0.365241E+10 | 2750271.04 | 2664386.93 | 0.207294E+09 | 0.139248E+09 | 0.251605E+09 | 84714.09 | 0.47 |
Minimum of Months | 0.00 | 0.106621E+09 | 31611.38 | 0.00 | 11922021.51 | 0.00 | 0.00 | 383.80 | 0.47 |
Maximum of Months | 29234879.89 | 0.492787E+09 | 438838.28 | 620774.79 | 24097366.84 | 49273288.75 | 71714645.38 | 11158.77 | 0.48 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.100993E+09 | 0.742764E+09 | 138318.22 | 11621035.14 | 49888765.70 | 776096.61 | 0.855816E+09 | 845.51 | 0.54 |
February | 50891473.47 | 0.730212E+09 | 70039.16 | 7337148.71 | 47125436.75 | 28607873.34 | 0.476426E+09 | 2613.24 | 0.54 |
March | 75596891.95 | 0.102632E+10 | 304888.87 | 5095196.61 | 66921248.06 | 15299578.43 | 0.455905E+09 | 12381.41 | 0.54 |
April | 8145336.25 | 0.135555E+10 | 552845.96 | 1517588.99 | 81009488.73 | 63675.64 | 73959436.59 | 29876.44 | 0.54 |
May | 0.00 | 0.230609E+10 | 445995.46 | 0.00 | 0.133730E+09 | 0.00 | 0.00 | 6295.20 | 0.54 |
June | 0.00 | 0.289070E+10 | 0.00 | 0.00 | 0.145380E+09 | 0.00 | 0.00 | 0.00 | 0.54 |
July | 0.00 | 0.309028E+10 | 0.00 | 0.00 | 0.142853E+09 | 0.00 | 0.00 | 0.00 | 0.54 |
August | 0.00 | 0.313306E+10 | 235315.62 | 0.00 | 0.166629E+09 | 0.00 | 0.00 | 3248.67 | 0.54 |
September | 0.00 | 0.288601E+10 | 105549.43 | 0.00 | 0.116910E+09 | 0.00 | 0.00 | 16.62 | 0.54 |
October | 0.00 | 0.252167E+10 | 0.00 | 0.00 | 94288801.12 | 0.00 | 0.00 | 0.00 | 0.54 |
November | 19227004.20 | 0.188088E+10 | 262794.16 | 2849279.40 | 85514757.83 | 266778.76 | 0.208618E+09 | 2157.22 | 0.54 |
December | 65796972.32 | 0.107007E+10 | 125239.06 | 8194621.72 | 51569680.50 | 1539423.71 | 0.599027E+09 | 1351.02 | 0.54 |
Annual Sum or Average | 0.320651E+09 | 0.236336E+11 | 2240985.95 | 36614870.57 | 0.118182E+10 | 46553426.49 | 0.266975E+10 | 58785.33 | 0.54 |
Minimum of Months | 0.00 | 0.730212E+09 | 0.00 | 0.00 | 47125436.75 | 0.00 | 0.00 | 0.00 | 0.54 |
Maximum of Months | 0.100993E+09 | 0.313306E+10 | 552845.96 | 11621035.14 | 0.166629E+09 | 28607873.34 | 0.855816E+09 | 29876.44 | 0.54 |
Report: MechanicalVentilationLoadsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.840845E+10 | 0.739567E+10 | 0.00 | 6648984.41 | 0.876648E+10 | 0.00 | 0.136213E+11 | 0.00 | 8.03 |
February | 0.452812E+10 | 0.795508E+10 | 0.00 | 5121134.09 | 0.893171E+10 | 0.00 | 0.892307E+10 | 0.00 | 8.02 |
March | 0.440560E+10 | 0.124451E+11 | 0.00 | 5470191.82 | 0.110840E+11 | 0.00 | 0.853091E+10 | 0.00 | 8.03 |
April | 0.398179E+09 | 0.161365E+11 | 0.00 | 2973974.54 | 0.137620E+11 | 0.00 | 0.195913E+10 | 0.00 | 8.04 |
May | 0.00 | 0.333132E+11 | 0.00 | 0.00 | 0.223318E+11 | 0.00 | 0.00 | 0.00 | 8.07 |
June | 0.00 | 0.471908E+11 | 0.00 | 0.00 | 0.247223E+11 | 0.00 | 0.00 | 0.00 | 8.06 |
July | 0.00 | 0.511503E+11 | 0.00 | 0.00 | 0.255682E+11 | 0.00 | 0.00 | 0.00 | 8.06 |
August | 0.00 | 0.491451E+11 | 0.00 | 0.00 | 0.288098E+11 | 0.00 | 0.00 | 0.00 | 8.06 |
September | 0.00 | 0.438676E+11 | 0.00 | 0.00 | 0.266855E+11 | 0.00 | 0.00 | 0.00 | 8.08 |
October | 0.00 | 0.339470E+11 | 0.00 | 0.00 | 0.254168E+11 | 0.00 | 0.00 | 0.00 | 8.08 |
November | 0.154371E+10 | 0.236270E+11 | 0.00 | 1889976.17 | 0.187460E+11 | 0.00 | 0.374422E+10 | 0.00 | 8.05 |
December | 0.596186E+10 | 0.125288E+11 | 0.00 | 5229650.02 | 0.118773E+11 | 0.00 | 0.986866E+10 | 0.00 | 8.03 |
Annual Sum or Average | 0.252459E+11 | 0.338702E+12 | 0.00 | 27333911.04 | 0.226702E+12 | 0.00 | 0.466473E+11 | 0.00 | 8.05 |
Minimum of Months | 0.00 | 0.739567E+10 | 0.00 | 0.00 | 0.876648E+10 | 0.00 | 0.00 | 0.00 | 8.02 |
Maximum of Months | 0.840845E+10 | 0.511503E+11 | 0.00 | 6648984.41 | 0.288098E+11 | 0.00 | 0.136213E+11 | 0.00 | 8.08 |
Report: MechanicalVentilationLoadsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.766501E+10 | 0.922853E+10 | 0.00 | 8514811.80 | 0.773098E+10 | 0.00 | 0.154501E+11 | 0.00 | 8.43 |
February | 0.428317E+10 | 0.962338E+10 | 0.00 | 6501326.82 | 0.809652E+10 | 0.00 | 0.983050E+10 | 0.00 | 8.42 |
March | 0.430943E+10 | 0.143788E+11 | 0.00 | 6937189.11 | 0.103111E+11 | 0.00 | 0.926411E+10 | 0.00 | 8.42 |
April | 0.324542E+09 | 0.192059E+11 | 0.00 | 3629127.93 | 0.121676E+11 | 0.00 | 0.214856E+10 | 0.00 | 8.44 |
May | 0.00 | 0.396186E+11 | 0.00 | 0.00 | 0.187717E+11 | 0.00 | 0.00 | 0.00 | 8.47 |
June | 0.00 | 0.555073E+11 | 0.00 | 0.00 | 0.199537E+11 | 0.00 | 0.00 | 0.00 | 8.46 |
July | 0.00 | 0.618455E+11 | 0.00 | 0.00 | 0.186579E+11 | 0.00 | 0.00 | 0.00 | 8.46 |
August | 0.00 | 0.580811E+11 | 0.00 | 0.00 | 0.237198E+11 | 0.00 | 0.00 | 0.00 | 8.46 |
September | 0.00 | 0.516159E+11 | 0.00 | 0.00 | 0.224178E+11 | 0.00 | 0.00 | 0.00 | 8.48 |
October | 0.00 | 0.396138E+11 | 0.00 | 0.00 | 0.226787E+11 | 0.00 | 0.00 | 0.00 | 8.48 |
November | 0.133752E+10 | 0.272883E+11 | 0.00 | 2440958.38 | 0.171752E+11 | 0.00 | 0.421083E+10 | 0.00 | 8.45 |
December | 0.562004E+10 | 0.143991E+11 | 0.00 | 6647707.14 | 0.112110E+11 | 0.00 | 0.109903E+11 | 0.00 | 8.43 |
Annual Sum or Average | 0.235397E+11 | 0.400406E+12 | 0.00 | 34671121.18 | 0.192892E+12 | 0.00 | 0.518944E+11 | 0.00 | 8.45 |
Minimum of Months | 0.00 | 0.922853E+10 | 0.00 | 0.00 | 0.773098E+10 | 0.00 | 0.00 | 0.00 | 8.42 |
Maximum of Months | 0.766501E+10 | 0.618455E+11 | 0.00 | 8514811.80 | 0.237198E+11 | 0.00 | 0.154501E+11 | 0.00 | 8.48 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.162985E+11 | 0.00 | 52377587.42 | 0.00 | 0.00 | 0.221459E+11 | 0.00 | 26.12 |
February | 0.00 | 0.170307E+11 | 0.00 | 34419482.30 | 0.00 | 0.00 | 0.135183E+11 | 0.00 | 26.09 |
March | 0.00 | 0.237318E+11 | 0.00 | 33705949.14 | 0.00 | 0.00 | 0.130017E+11 | 0.00 | 26.10 |
April | 0.00 | 0.301635E+11 | 0.00 | 11229057.70 | 0.00 | 0.00 | 0.236592E+10 | 0.00 | 26.16 |
May | 0.00 | 0.561405E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.24 |
June | 0.00 | 0.725608E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.22 |
July | 0.00 | 0.774149E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.21 |
August | 0.00 | 0.786497E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.22 |
September | 0.00 | 0.711863E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.27 |
October | 0.00 | 0.598852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.30 |
November | 0.00 | 0.427384E+11 | 0.00 | 14320293.32 | 0.00 | 0.00 | 0.531395E+10 | 0.00 | 26.19 |
December | 0.00 | 0.246131E+11 | 0.00 | 40118095.51 | 0.00 | 0.00 | 0.159120E+11 | 0.00 | 26.12 |
Annual Sum or Average | 0.00 | 0.570413E+12 | 0.00 | 0.186170E+09 | 0.00 | 0.00 | 0.722578E+11 | 0.00 | 26.19 |
Minimum of Months | 0.00 | 0.162985E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.09 |
Maximum of Months | 0.00 | 0.786497E+11 | 0.00 | 52377587.42 | 0.00 | 0.00 | 0.221459E+11 | 0.00 | 26.30 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.653445E+10 | 0.00 | 0.00 | 0.00 | 0.479255E+10 | 0.00 | 0.00 | 0.00 | 1.91 |
February | 0.394326E+10 | 0.00 | 0.00 | 0.00 | 0.500742E+10 | 46928175.91 | 0.00 | 0.00 | 1.91 |
March | 0.383768E+10 | 0.00 | 0.00 | 0.00 | 0.697704E+10 | 0.00 | 0.00 | 0.00 | 1.91 |
April | 0.699894E+09 | 0.00 | 0.00 | 0.00 | 0.886578E+10 | 0.00 | 0.00 | 0.00 | 1.91 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.165004E+11 | 0.00 | 0.00 | 0.00 | 1.92 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.213243E+11 | 0.00 | 0.00 | 0.00 | 1.92 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.227493E+11 | 0.00 | 0.00 | 0.00 | 1.92 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.231159E+11 | 0.00 | 0.00 | 0.00 | 1.92 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.209210E+11 | 0.00 | 0.00 | 0.00 | 1.92 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.176031E+11 | 0.00 | 0.00 | 0.00 | 1.92 |
November | 0.156858E+10 | 0.00 | 0.00 | 0.00 | 0.125648E+11 | 0.00 | 0.00 | 0.00 | 1.92 |
December | 0.469576E+10 | 0.00 | 0.00 | 0.00 | 0.723711E+10 | 0.00 | 0.00 | 0.00 | 1.91 |
Annual Sum or Average | 0.212796E+11 | 0.00 | 0.00 | 0.00 | 0.167659E+12 | 46928175.91 | 0.00 | 0.00 | 1.92 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.479255E+10 | 0.00 | 0.00 | 0.00 | 1.91 |
Maximum of Months | 0.653445E+10 | 0.00 | 0.00 | 0.00 | 0.231159E+11 | 46928175.91 | 0.00 | 0.00 | 1.92 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:58:20
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.190027E+12 | -962823871.6 | 0.112396E+11 | -0.664023E+11 | 0.110524E+13 |
February | 0.219909E+12 | -0.364378E+10 | 0.349295E+09 | -0.186146E+12 | 0.115474E+13 |
March | 0.307887E+12 | -0.723187E+10 | -0.101514E+11 | -0.379993E+12 | 0.139154E+13 |
April | 0.331400E+12 | -0.122351E+11 | -0.311940E+11 | -0.653130E+12 | 0.165102E+13 |
May | 0.327342E+12 | -0.232371E+11 | -0.777552E+11 | -0.129875E+13 | 0.213417E+13 |
June | 0.287627E+12 | -0.295778E+11 | -0.104906E+12 | -0.167921E+13 | 0.235905E+13 |
July | 0.302040E+12 | -0.315441E+11 | -0.115012E+12 | -0.179041E+13 | 0.249761E+13 |
August | 0.330296E+12 | -0.319336E+11 | -0.115127E+12 | -0.181796E+13 | 0.249034E+13 |
September | 0.246508E+12 | -0.289602E+11 | -0.103874E+12 | -0.164361E+13 | 0.234961E+13 |
October | 0.234782E+12 | -0.244355E+11 | -0.826799E+11 | -0.137970E+13 | 0.220211E+13 |
November | 0.173461E+12 | -0.149767E+11 | -0.462504E+11 | -0.837924E+12 | 0.176681E+13 |
December | 0.187885E+12 | -0.531800E+10 | -0.567211E+10 | -0.302655E+12 | 0.133090E+13 |
Annual Sum or Average | 0.313916E+13 | -0.214056E+12 | -0.681034E+12 | -0.120359E+14 | 0.224331E+14 |
Minimum of Months | 0.173461E+12 | -0.319336E+11 | -0.115127E+12 | -0.181796E+13 | 0.110524E+13 |