Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:58
Tabular Output Report in Format: HTML
Building: HotelLarge
Environment: RUNPERIOD 1 ** El Paso International Ap Ut TX USA TMY3 WMO#=722700
Simulation Timestamp: 2023-10-16 08:58:10
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:58:10
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 15119.46 | 1332.66 | 1332.66 |
Net Site Energy | 15119.46 | 1332.66 | 1332.66 |
Total Source Energy | 35528.68 | 3131.58 | 3131.58 |
Net Source Energy | 35528.68 | 3131.58 | 3131.58 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 11345.29 |
Net Conditioned Building Area | 11345.29 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 1215.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 2289.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1174.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 262.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1751.30 | 1788.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 679.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2048.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 253.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 563.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 90.78 | 2927.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Refrigeration | 74.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 9188.28 | 5931.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 1215.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 2289.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 1174.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 262.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 959.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 762.04 | 1198.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 16.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 13.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 590.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 32.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 616.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 30.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 2048.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 253.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 563.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 90.78 | 2927.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5742.51 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4114.69 | |
Refrigeration | General | 18.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 22.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 33.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 1215.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 2289.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 1174.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 262.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 1751.30 | 1788.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 679.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 2048.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 253.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 563.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 90.78 | 2927.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Refrigeration | Unassigned | 74.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 126.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 412.75 | 365.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Other | 270.50 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 809.88 | 522.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 126.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 412.75 | 365.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Other | 270.50 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 809.88 | 522.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 9188.278 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 9188.278 | 100.00 |
Total On-Site and Utility Electric Sources | 9188.278 | 100.00 |
Total Electricity End Uses | 9188.278 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | 0.00 |
Air to Air Heat Recovery for Cooling | 1289.08 | 39.64 |
Air to Air Heat Recovery for Heating | 1962.95 | 60.36 |
High-Temperature Geothermal* | 0.00 | 0.00 |
Solar Water Thermal | 0.00 | 0.00 |
Solar Air Thermal | 0.00 | 0.00 |
Total On-Site Thermal Sources | 3252.03 | 100.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 9857.19 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 9857.19 | 100.00 |
Total Water End Uses | 9857.19 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 13.67 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 7386.50 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2012
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3B
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_TX_ELPASO
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneHeatingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneElectricSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |PeakSpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ComfortReportSimple55Monthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |OccupantComfortDataSummaryMonthly
| BASEMENT PEOPLE | RETAIL_1_FLR_1 PEOPLE | RETAIL_2_FLR_1 PEOPLE | LAUNDRY_FLR_1 PEOPLE | CAFE_FLR_1 PEOPLE | LOBBY_FLR_1 PEOPLE | ROOM_1_FLR_3 PEOPLE | ROOM_2_FLR_3 PEOPLE | ROOM_3_MULT19_FLR_3 PEOPLE | ROOM_4_MULT19_FLR_3 PEOPLE | ROOM_5_FLR_3 PEOPLE | ROOM_6_FLR_3 PEOPLE | ROOM_1_FLR_6 PEOPLE | ROOM_2_FLR_6 PEOPLE | ROOM_3_MULT9_FLR_6 PEOPLE | BANQUET_FLR_6 PEOPLE | DINING_FLR_6 PEOPLE | KITCHEN_FLR_6 PEOPLE | STORAGE_FLR_1 PEOPLE | CORRIDOR_FLR_3 PEOPLE | CORRIDOR_FLR_6 PEOPLE | MECH_FLR_1 PEOPLE |ChillerReportMonthly
| COOLSYS1 CHILLER1 |BoilerReportMonthly
| HEATSYS1 BOILER |DXReportMonthly
| VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |WindowReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowEnergyReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWH BOOSTER E WATER HEATER | SWH LAUNDRY G WATER HEATER | SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| VAV WITH REHEAT HEATING COIL | BASEMENT VAV BOX REHEAT COIL | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | MECH_FLR_1 VAV BOX REHEAT COIL | STORAGE_FLR_1 VAV BOX REHEAT COIL | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | CAFE_FLR_1 VAV BOX REHEAT COIL | LOBBY_FLR_1 VAV BOX REHEAT COIL | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | BANQUET_FLR_6 VAV BOX REHEAT COIL | DINING_FLR_6 VAV BOX REHEAT COIL | KITCHEN_FLR_6 VAV BOX REHEAT COIL | FLR_3_DOAS HEATING COIL | ROOM_1_FLR_3 FAN COIL HEATING COIL | ROOM_2_FLR_3 FAN COIL HEATING COIL | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_5_FLR_3 FAN COIL HEATING COIL | ROOM_6_FLR_3 FAN COIL HEATING COIL | ROOM_1_FLR_6 FAN COIL HEATING COIL | ROOM_2_FLR_6 FAN COIL HEATING COIL | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1 | SWHSYS1 |FanReportMonthly
| FLR_3_DOAS FAN | VAV WITH REHEAT FAN | LAUNDRY_FLR_1 EXHAUST FAN | LOBBY_FLR_1 EXHAUST FAN | BANQUET_FLR_6 EXHAUST FAN | DINING_FLR_6 EXHAUST FAN | KITCHEN_FLR_6 EXHAUST FAN | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 PUMP | SWHSYS1 PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1 | SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV WITH REHEAT | FLR_3_DOAS |AirLoopSystemComponentLoadsMonthly
| VAV WITH REHEAT | FLR_3_DOAS |AirLoopSystemComponentEnergyUseMonthly
| VAV WITH REHEAT | FLR_3_DOAS |MechanicalVentilationLoadsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:58:10
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:58 |
RunPeriod | RUNPERIOD 1 |
Weather File | El Paso International Ap Ut TX USA TMY3 WMO#=722700 |
Latitude [deg] | 31.77 |
Longitude [deg] | -106.5 |
Elevation [m] | 1186.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1213.79 | 432.95 | 85.85 | 609.15 | 85.85 |
Gross Window-Wall Ratio [%] | 26.62 | 23.11 | 21.12 | 32.52 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.15 | 26.05 | 24.48 | 36.65 | 24.48 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1213.79 | 432.95 | 85.85 | 609.15 | 85.85 |
Gross Window-Wall Ratio [%] | 26.62 | 23.11 | 21.12 | 32.52 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.15 | 26.05 | 24.48 | 36.65 | 24.48 |
Total | |
Gross Roof Area [m2] | 1978.84 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 1978.83 | Yes | Yes | 4826.41 | 1.00 | 0.00 | 533.77 | 0.00 | 0.00 | 8.7495 | 18.58 | 5.3800 |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 265.76 | 1.00 | 68.84 | 0.00 | 23.26 | 23.26 | 13.0124 | 6.19 | 10.7600 |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 307.76 | 1.00 | 26.57 | 0.00 | 0.00 | 0.00 | 13.0124 | 6.19 | 10.7600 |
MECH_FLR_1 | 164.24 | Yes | Yes | 650.80 | 1.00 | 62.80 | 0.00 | 0.00 | 0.00 | 10.0642 | 61.93 | 5.3800 |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 375.47 | 1.00 | 36.23 | 0.00 | 0.00 | 0.00 | 7.3195 | 46.45 | 2.6900 |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 309.22 | 1.00 | 85.75 | 0.00 | 0.00 | 0.00 | 5.4896 | 9.29 | 597.5300 |
CAFE_FLR_1 | 188.86 | Yes | Yes | 748.35 | 1.00 | 152.17 | 0.00 | 65.50 | 65.50 | 12.8090 | 1.33 | 5.3800 |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 5183.56 | 1.00 | 434.79 | 0.00 | 85.08 | 85.08 | 10.0642 | 3.10 | 8.0700 |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 10.0642 | 26.01 | 6.7500 |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 10.0642 | 26.01 | 6.7500 |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 74.75 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 10.0642 | 16.35 | 10.5200 |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 74.77 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 10.0642 | 16.35 | 10.5200 |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 10.0642 | 26.01 | 6.7500 |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 10.0642 | 26.01 | 6.7500 |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 1186.91 | 4.00 | 48.31 | 0.00 | 15.94 | 15.94 | 3.6597 | 18.58 | 0.0000 |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 118.94 | 1.00 | 39.95 | 0.00 | 13.18 | 13.18 | 10.0642 | 26.01 | 6.7500 |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 118.93 | 1.00 | 39.95 | 0.00 | 13.18 | 13.18 | 10.0642 | 26.01 | 6.7500 |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 74.77 | 9.00 | 20.44 | 0.00 | 6.74 | 6.74 | 10.0642 | 16.35 | 10.5200 |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.19 | 32.19 | 12.8090 | 1.33 | 67.8200 |
DINING_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.19 | 32.19 | 12.8090 | 1.33 | 67.8200 |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 314.87 | 1.00 | 87.33 | 0.00 | 26.37 | 26.37 | 10.9792 | 4.65 | 2936.4163 |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1256.16 | 1.00 | 85.47 | 0.00 | 28.20 | 28.20 | 3.6597 | 18.58 | 0.0000 |
Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1213.79 | 1213.79 | 8.9207 | 7.07 | 41.0885 | |||
Conditioned Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1213.79 | 1213.79 | 8.9207 | 7.07 | 41.0885 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 1978.83 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 8.7495 | 18.58 | 5.3800 | |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 1.00 | RETAIL_1_FLR_1 | GENERAL | RETAIL_1_FLR_1 | 13.0124 | 6.19 | 10.7600 | |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 1.00 | RETAIL_2_FLR_1 | GENERAL | RETAIL_2_FLR_1 | 13.0124 | 6.19 | 10.7600 | |
MECH_FLR_1 | 164.24 | Yes | Yes | 1.00 | MECH_FLR_1 | GENERAL | MECH_FLR_1 | 10.0642 | 61.93 | 5.3800 | |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 1.00 | STORAGE_FLR_1 | GENERAL | STORAGE_FLR_1 | 7.3195 | 46.45 | 2.6900 | |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 1.00 | LAUNDRY_FLR_1 | GENERAL | LAUNDRY_FLR_1 | 5.4896 | 9.29 | 597.5300 | |
CAFE_FLR_1 | 188.86 | Yes | Yes | 1.00 | CAFE_FLR_1 | GENERAL | CAFE_FLR_1 | 12.8090 | 1.33 | 5.3800 | |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 1.00 | LOBBY_FLR_1 | GENERAL | LOBBY_FLR_1 | 10.0642 | 3.10 | 8.0700 | |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_1_FLR_3 | GENERAL | ROOM_1_FLR_3 | 10.0642 | 26.01 | 6.7500 | |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_2_FLR_3 | GENERAL | ROOM_2_FLR_3 | 10.0642 | 26.01 | 6.7500 | |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 76.00 | ROOM_3_MULT19_FLR_3 | GENERAL | ROOM_3_MULT19_FLR_3 | 10.0642 | 16.35 | 10.5200 | |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 76.00 | ROOM_4_MULT19_FLR_3 | GENERAL | ROOM_4_MULT19_FLR_3 | 10.0642 | 16.35 | 10.5200 | |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_5_FLR_3 | GENERAL | ROOM_5_FLR_3 | 10.0642 | 26.01 | 6.7500 | |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_6_FLR_3 | GENERAL | ROOM_6_FLR_3 | 10.0642 | 26.01 | 6.7500 | |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 4.00 | CORRIDOR_FLR_3 | GENERAL | CORRIDOR_FLR_3 | 3.6597 | 18.58 | 0.0000 | |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 1.00 | ROOM_1_FLR_6 | GENERAL | ROOM_1_FLR_6 | 10.0642 | 26.01 | 6.7500 | |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 1.00 | ROOM_2_FLR_6 | GENERAL | ROOM_2_FLR_6 | 10.0642 | 26.01 | 6.7500 | |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 9.00 | ROOM_3_MULT9_FLR_6 | GENERAL | ROOM_3_MULT9_FLR_6 | 10.0642 | 16.35 | 10.5200 | |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1.00 | BANQUET_FLR_6 | GENERAL | BANQUET_FLR_6 | 12.8090 | 1.33 | 67.8200 | |
DINING_FLR_6 | 331.66 | Yes | Yes | 1.00 | DINING_FLR_6 | GENERAL | DINING_FLR_6 | 12.8090 | 1.33 | 67.8200 | |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 1.00 | KITCHEN_FLR_6 | GENERAL | KITCHEN_FLR_6 | 10.9792 | 4.65 | 2936.4163 | |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1.00 | CORRIDOR_FLR_6 | GENERAL | CORRIDOR_FLR_6 | 3.6597 | 18.58 | 0.0000 | |
Total | 11345.29 | 8.9207 | 3.54 | 41.0885 | |||||||
Conditioned Total | 11345.29 | 8.9207 | 3.54 | 41.0885 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 11345.29 | 11345.29 | 0.00 | 0.00 | 4.6908 | 8.82 | 37.2165 |
Total | 11345.29 | 11345.29 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:58:10
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 05-JUN-19:10 | 26-DEC-17:19 | - | - | - | - | - | - | - | - | - | - | 02-JAN-21:10 |
Heating | 0.00 | 133567.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 224284.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 93091.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 16690.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 88971.67 | 89612.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 33012.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 78213.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 11289.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 18015.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 3773.80 | 244320.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 2894.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 570236.28 | 467500.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 133567.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 224284.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 93091.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 16690.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 58789.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 29240.64 | 74976.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 515.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 425.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 14636.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 1887.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 30153.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 972.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 78213.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 11289.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 18015.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 3773.80 | 244320.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 666.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 1153.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 1073.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:58:10
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 1317.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 7250.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 3718.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 831.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 5546.36 | 1939.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 2152.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 6488.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 803.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 1785.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 287.49 | 3173.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 234.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 29099.28 | 6429.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 116.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 639.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 327.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 73.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 488.87 | 170.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 189.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 571.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 70.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 157.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 25.34 | 279.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 20.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2564.88 | 566.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 116.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 639.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 327.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 73.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 488.87 | 170.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 189.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 571.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 70.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 157.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 25.34 | 279.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 20.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2564.88 | 566.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:58:10
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
BASEMENT VAV BOX COMPONENT | 2.86 | 0.527619 | 0.995000 | 2.84 | 1.00 | 0.500000 | 0.000722 | 0.000114 | 2.84 | 16.70 | 0.008000 |
RETAIL_1_FLR_1 VAV BOX COMPONENT | 0.389359 | 0.131263 | 0.995000 | 0.387412 | 0.995000 | 0.500000 | 0.002903 | 0.000042 | 0.387412 | 16.70 | 0.008000 |
RETAIL_2_FLR_1 VAV BOX COMPONENT | 0.284214 | 0.208237 | 0.995000 | 0.282793 | 0.995000 | 0.500000 | 0.001830 | 0.000020 | 0.282793 | 16.70 | 0.008000 |
MECH_FLR_1 VAV BOX COMPONENT | 0.304343 | 0.411224 | 0.995000 | 0.302822 | 1.00 | 0.500000 | 0.000927 | 0.000028 | 0.302822 | 16.70 | 0.008000 |
STORAGE_FLR_1 VAV BOX COMPONENT | 0.153705 | 0.469774 | 0.995000 | 0.152937 | 1.00 | 0.500000 | 0.000811 | 0.000016 | 0.152937 | 16.70 | 0.008000 |
LAUNDRY_FLR_1 VAV BOX COMPONENT | 3.79 | 0.062268 | 0.995000 | 3.77 | 0.995000 | 0.500000 | 0.024280 | 0.000172 | 3.77 | 16.70 | 0.008000 |
CAFE_FLR_1 VAV BOX COMPONENT | 1.66 | 0.086900 | 0.995000 | 1.65 | 0.995000 | 0.500000 | 0.004384 | 0.000132 | 1.65 | 16.70 | 0.008000 |
LOBBY_FLR_1 VAV BOX COMPONENT | 5.47 | 0.182216 | 0.995000 | 5.44 | 0.995000 | 0.500000 | 0.002091 | 0.000370 | 5.44 | 16.70 | 0.008000 |
CORRIDOR_FLR_3 VAV BOX COMPONENT | 1.36 | 0.871557 | 0.995000 | 1.36 | 1.00 | 0.500000 | 0.000437 | 0.000143 | 1.36 | 16.70 | 0.008000 |
BANQUET_FLR_6 VAV BOX COMPONENT | 2.64 | 0.095713 | 0.995000 | 2.63 | 0.995000 | 0.500000 | 0.003981 | 0.000166 | 2.63 | 16.70 | 0.008000 |
DINING_FLR_6 VAV BOX COMPONENT | 2.77 | 0.091296 | 0.995000 | 2.75 | 0.995000 | 0.500000 | 0.004173 | 0.000172 | 2.75 | 16.70 | 0.008000 |
KITCHEN_FLR_6 VAV BOX COMPONENT | 2.63 | 0.716453 | 0.995000 | 2.62 | 0.995000 | 0.500000 | 0.012753 | 0.000122 | 2.62 | 16.70 | 0.008000 |
CORRIDOR_FLR_6 VAV BOX COMPONENT | 0.844250 | 0.371974 | 0.995000 | 0.840029 | 0.995000 | 0.500000 | 0.001024 | 0.000098 | 0.840029 | 16.70 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
BASEMENT VAV BOX REHEAT COIL | 13021.18 | 0.000114 | 271.53 |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 4770.42 | 0.000042 | 109.12 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 2266.37 | 0.000020 | 49.18 |
MECH_FLR_1 VAV BOX REHEAT COIL | 3192.02 | 0.000028 | 71.41 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | 1782.12 | 0.000016 | 40.43 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 19667.59 | 0.000172 | 413.11 |
CAFE_FLR_1 VAV BOX REHEAT COIL | 15073.10 | 0.000132 | 331.54 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | 42329.07 | 0.000370 | 915.98 |
ROOM_1_FLR_3 FAN COIL HEATING COIL | 6581.78 | 0.000058 | 188.10 |
ROOM_2_FLR_3 FAN COIL HEATING COIL | 6575.24 | 0.000058 | 187.91 |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | 37721.69 | 0.000330 | 1078.03 |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | 37617.71 | 0.000329 | 1075.06 |
ROOM_5_FLR_3 FAN COIL HEATING COIL | 6569.52 | 0.000057 | 187.75 |
ROOM_6_FLR_3 FAN COIL HEATING COIL | 6562.97 | 0.000057 | 187.56 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 16345.59 | 0.000143 | 372.72 |
ROOM_1_FLR_6 FAN COIL HEATING COIL | 2054.07 | 0.000018 | 58.70 |
ROOM_2_FLR_6 FAN COIL HEATING COIL | 2053.25 | 0.000018 | 58.68 |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | 9915.53 | 0.000087 | 283.36 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | 18979.29 | 0.000166 | 408.04 |
DINING_FLR_6 VAV BOX REHEAT COIL | 19688.34 | 0.000172 | 422.90 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | 13990.36 | 0.000122 | 294.27 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 11230.01 | 0.000098 | 260.37 |
VAV WITH REHEAT HEATING COIL | 172635.01 | 0.001510 | 2930.66 |
FLR_3_DOAS HEATING COIL | 14143.00 | 0.000124 | 240.09 |
User-Specified Maximum Flow Rate [m3/s] | |
LOBBY_FLR_1 EXHAUST FAN | 0.000000 |
BANQUET_FLR_6 EXHAUST FAN | 0.000000 |
DINING_FLR_6 EXHAUST FAN | 0.000000 |
Design Size Maximum Air Flow Rate [m3/s] | |
ROOM_1_FLR_3 DIRECT AIR | 0.061735 |
ROOM_2_FLR_3 DIRECT AIR | 0.061728 |
ROOM_3_MULT19_FLR_3 DIRECT AIR | 0.837072 |
ROOM_4_MULT19_FLR_3 DIRECT AIR | 0.837300 |
ROOM_5_FLR_3 DIRECT AIR | 0.061735 |
ROOM_6_FLR_3 DIRECT AIR | 0.061728 |
ROOM_1_FLR_6 DIRECT AIR | 0.015434 |
ROOM_2_FLR_6 DIRECT AIR | 0.015432 |
ROOM_3_MULT9_FLR_6 DIRECT AIR | 0.099154 |
Design Size Maximum Supply Air Flow Rate [m3/s] | Design Size Maximum Hot Water Flow [m3/s] | Design Size Maximum Cold Water Flow [m3/s] | |
ROOM_1_FLR_3 FAN COIL | 1.26 | 0.000058 | 0.000476 |
ROOM_2_FLR_3 FAN COIL | 1.25 | 0.000058 | 0.000473 |
ROOM_3_MULT19_FLR_3 FAN COIL | 7.66 | 0.000330 | 0.002887 |
ROOM_4_MULT19_FLR_3 FAN COIL | 8.25 | 0.000329 | 0.003227 |
ROOM_5_FLR_3 FAN COIL | 1.10 | 0.000057 | 0.000417 |
ROOM_6_FLR_3 FAN COIL | 1.09 | 0.000057 | 0.000414 |
ROOM_1_FLR_6 FAN COIL | 0.340889 | 0.000018 | 0.000129 |
ROOM_2_FLR_6 FAN COIL | 0.338090 | 0.000018 | 0.000128 |
ROOM_3_MULT9_FLR_6 FAN COIL | 1.54 | 0.000087 | 0.000592 |
Design Size Maximum Flow Rate [m3/s] | |
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | 1.26 |
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | 1.25 |
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | 7.66 |
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | 8.25 |
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | 1.10 |
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | 1.09 |
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | 0.340889 |
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | 0.338090 |
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | 1.54 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Temperature [C] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | Design Size Design Coil Load [W] | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | 22.70 | 6.70 | 0.008518 | 12.80 | 0.008500 | 0.000476 | 1.26 | |
ROOM_2_FLR_3 FAN COIL COOLING COIL | 22.70 | 6.70 | 0.008518 | 12.80 | 0.008500 | 0.000473 | 1.25 | |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | 22.70 | 6.70 | 0.008458 | 12.80 | 0.008458 | 0.002887 | 7.66 | |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | 22.70 | 6.70 | 0.008653 | 12.80 | 0.008500 | 0.003227 | 8.25 | |
ROOM_5_FLR_3 FAN COIL COOLING COIL | 22.70 | 6.70 | 0.008519 | 12.80 | 0.008500 | 0.000417 | 1.10 | |
ROOM_6_FLR_3 FAN COIL COOLING COIL | 22.70 | 6.70 | 0.008519 | 12.80 | 0.008500 | 0.000414 | 1.09 | |
ROOM_1_FLR_6 FAN COIL COOLING COIL | 22.70 | 6.70 | 0.008516 | 12.80 | 0.008500 | 0.000129 | 0.340889 | |
ROOM_2_FLR_6 FAN COIL COOLING COIL | 22.70 | 6.70 | 0.008517 | 12.80 | 0.008500 | 0.000128 | 0.338090 | |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | 22.70 | 6.70 | 0.008576 | 12.80 | 0.008500 | 0.000592 | 1.54 | |
VAV WITH REHEAT COOLING COIL | 38.10 | 6.70 | 0.006871 | 10.69 | 0.006871 | 0.026050 | 25.04 | 729331.56 |
FLR_3_DOAS COOLING COIL | 38.10 | 6.70 | 0.006871 | 11.79 | 0.006871 | 0.002048 | 2.05 | 57348.72 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV WITH REHEAT | 25.03 | 25.03 | 25.16 | 25.03 | 25.04 | 25.04 | 0.300000 | 0.999619 | 25.04 |
FLR_3_DOAS | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 0.300000 | 1.00 | 2.05 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV WITH REHEAT_OA_CONTROLLER | 25.04 | 25.04 |
FLR_3_DOAS_OA_CONTROLLER | 2.05 | 2.05 |
Design Size Nominal Supply Air Flow Rate [m3/s] | |
VAV WITH REHEAT OA HEAT RECOVERY | 25.04 |
Design Size Maximum Flow Rate [m3/s] | |
VAV WITH REHEAT FAN | 25.04 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV WITH REHEAT_COOLC_CONTROLLER | 0.026050 | 0.000018 |
VAV WITH REHEAT_HEATC_CONTROLLER | 0.001510 | |
FLR_3_DOAS_COOLC_CONTROLLER | 0.002048 | 0.000232 |
FLR_3_DOAS_HEATC_CONTROLLER | 0.000124 |
User-Specified Maximum Flow Rate [m3/s] | |
FLR_3_DOAS FAN | 2.05 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.036841 | 7591.54 | |
HEATSYS1 PUMP | 0.004241 | 1277.18 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
HEATSYS1 | 0.004241 | 0.508913 |
COOLSYS1 | 0.036841 | 4.42 |
SWHSYS1 | 0.000375 | 0.045004 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 484765.23 | 484765.23 | 0.004241 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 PUMP | 0.036841 | 5255.88 |
SWHSYS1 PUMP | 0.000375 | 47.91 |
Design Size Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Fluid Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.036841 | 1031447.13 | 1032120.29 | 117.66 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000375 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:58:10
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesPossible Shadow Receivers | |
RETAIL_1_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
CAFE_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
LOBBY_FLR_1_CEILING_2 | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
Possible Shadow Receivers | |
RETAIL_1_FLR_1_WALL_SOUTH | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | |
RETAIL_2_FLR_1_WALL_WEST | RETAIL_2_FLR_1_WALL_WEST_DOOR | |
STORAGE_FLR_1_WALL_NORTH | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | |
LAUNDRY_FLR_1_WALL_EAST | LAUNDRY_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_EAST | CAFE_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_SOUTH | CAFE_FLR_1_WALL_SOUTH_WINDOW | |
LOBBY_FLR_1_WALL_1_NORTH | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | |
LOBBY_FLR_1_WALL_1_SOUTH | LOBBY_FLR_1_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_SOUTH | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_WEST | ROOM_1_FLR_3_WALL_WEST_WINDOW | |
ROOM_2_FLR_3_WALL_NORTH | ROOM_2_FLR_3_WALL_NORTH_WINDOW | |
ROOM_2_FLR_3_WALL_WEST | ROOM_2_FLR_3_WALL_WEST_WINDOW | |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_4_MULT19_FLR_3_WALL_NORTH | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | |
ROOM_5_FLR_3_WALL_EAST | ROOM_5_FLR_3_WALL_EAST_WINDOW | |
ROOM_5_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_6_FLR_3_WALL_NORTH | ROOM_6_FLR_3_WALL_NORTH_WINDOW | |
ROOM_6_FLR_3_WALL_EAST | ROOM_6_FLR_3_WALL_EAST_WINDOW | |
CORRIDOR_FLR_3_WALL_1_NORTH | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_NORTH | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_SOUTH | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_WEST | ROOM_1_FLR_6_WALL_WEST_WINDOW | |
ROOM_2_FLR_6_WALL_NORTH | ROOM_2_FLR_6_WALL_NORTH_WINDOW | |
ROOM_2_FLR_6_WALL_WEST | ROOM_2_FLR_6_WALL_WEST_WINDOW | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | |
BANQUET_FLR_6_WALL_NORTH | BANQUET_FLR_6_WALL_NORTH_WINDOW | |
DINING_FLR_6_WALL_NORTH | DINING_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_NORTH | KITCHEN_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_EAST | KITCHEN_FLR_6_WALL_EAST_WINDOW | |
KITCHEN_FLR_6_WALL_1_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_6_WALL_1_NORTH | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_NORTH | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:58:10
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:58:10
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.30 | 11.20 | 6.80 | 8.10 | 10.30 | 12.50 | 19.20 | 23.80 | 27.90 | 27.50 | 26.30 | 23.40 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | El Paso International Ap Ut TX USA TMY3 WMO#=722700 | 31.77 | -106.50 | -7.00 | 1186.00 | 87865 | 1.0443 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 17.94 | 21.10 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | HotelLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | DOE-2 |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 22 | 235 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 41.45 | 11.51 | -1.22 | 1 | 1 | 1 | 0.00 | 86.56 | 0.00 | 22.86 | -2.44 | 0.00 | 2.44 | 4826.41 | TARP | DOE-2 | 1978.83 | 0.00 | 0.00 | 0.00 | 13 | 0 | 0 | Yes |
2 | RETAIL_1_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 2.90 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 265.76 | TARP | DOE-2 | 67.07 | 68.84 | 45.58 | 23.26 | 6 | 1 | 0 | Yes |
3 | RETAIL_2_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 9.14 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 5.79 | 12.50 | 0.00 | 3.96 | 3.96 | 307.76 | TARP | DOE-2 | 77.67 | 26.57 | 24.62 | 0.00 | 6 | 1 | 0 | Yes |
4 | MECH_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 61.87 | 17.68 | 1.98 | 1 | 1 | 1 | 53.95 | 69.80 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 650.80 | TARP | DOE-2 | 164.24 | 62.80 | 62.80 | 0.00 | 6 | 0 | 0 | Yes |
5 | STORAGE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 74.37 | 17.68 | 1.98 | 1 | 1 | 1 | 69.80 | 78.94 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 375.47 | TARP | DOE-2 | 94.76 | 36.23 | 28.80 | 0.00 | 6 | 1 | 0 | Yes |
6 | LAUNDRY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 14.33 | 1.98 | 1 | 1 | 1 | 81.99 | 86.56 | 5.79 | 22.86 | 0.00 | 3.96 | 3.96 | 309.22 | TARP | DOE-2 | 78.04 | 85.75 | 83.80 | 0.00 | 6 | 1 | 0 | Yes |
7 | CAFE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 70.26 | 2.90 | 1.98 | 1 | 1 | 1 | 53.95 | 86.56 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 748.35 | TARP | DOE-2 | 188.86 | 152.17 | 84.72 | 65.50 | 7 | 2 | 0 | Yes |
8 | LOBBY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 38.29 | 12.45 | 1.98 | 1 | 1 | 1 | 0.00 | 81.99 | 0.00 | 22.86 | 0.00 | 3.96 | 3.96 | 5183.56 | TARP | DOE-2 | 1308.19 | 434.79 | 345.80 | 85.08 | 18 | 3 | 0 | Yes |
9 | ROOM_1_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
10 | ROOM_2_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
11 | ROOM_3_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 8.53 | 9.14 | 8.53 | 1 | 76 | 1 | 6.71 | 10.36 | 5.79 | 12.50 | 7.01 | 10.06 | 3.05 | 74.75 | TARP | DOE-2 | 24.52 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
12 | ROOM_4_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 12.19 | 19.51 | 8.53 | 1 | 76 | 1 | 10.36 | 14.02 | 16.15 | 22.86 | 7.01 | 10.06 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
13 | ROOM_5_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 10.06 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
14 | ROOM_6_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 18.59 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
15 | CORRIDOR_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 43.28 | 14.33 | 8.53 | 1 | 4 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 7.01 | 10.06 | 3.05 | 1186.91 | TARP | DOE-2 | 389.40 | 48.31 | 32.37 | 15.94 | 20 | 4 | 0 | Yes |
16 | ROOM_1_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 16.15 | 19.20 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
17 | ROOM_2_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 16.15 | 19.20 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
18 | ROOM_3_MULT9_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 7.93 | 7.62 | 17.68 | 1 | 9 | 1 | 4.57 | 11.28 | 5.79 | 9.45 | 16.15 | 19.20 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 20.44 | 13.70 | 6.74 | 6 | 1 | 0 | Yes |
19 | BANQUET_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 26.37 | 17.68 | 17.68 | 1 | 1 | 1 | 10.36 | 42.37 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.36 | 32.19 | 6 | 1 | 0 | Yes |
20 | DINING_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 63.55 | 17.68 | 17.68 | 1 | 1 | 1 | 47.55 | 79.55 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.36 | 32.19 | 6 | 1 | 0 | Yes |
21 | KITCHEN_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 82.99 | 14.11 | 17.68 | 1 | 1 | 1 | 79.55 | 86.56 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 314.87 | TARP | DOE-2 | 103.30 | 87.33 | 60.96 | 26.37 | 8 | 3 | 0 | Yes |
22 | CORRIDOR_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 41.51 | 13.35 | 17.68 | 1 | 1 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 1256.16 | TARP | DOE-2 | 412.12 | 85.47 | 57.27 | 28.20 | 15 | 3 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 1978.83 | 106.5 | 18.581 | 5.382E-002 | 8.749 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 14.129 | No |
2 | RETAIL_1_FLR_1 | 67.07 | 10.8 | 6.194 | 0.161 | 13.012 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 23.772 | No |
3 | RETAIL_2_FLR_1 | 77.67 | 12.5 | 6.194 | 0.161 | 13.012 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 23.772 | No |
4 | MECH_FLR_1 | 164.24 | 2.7 | 61.932 | 1.615E-002 | 10.064 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 15.444 | No |
5 | STORAGE_FLR_1 | 94.76 | 2.0 | 46.451 | 2.153E-002 | 7.319 | 2.690 | 0.000 | 0.000 | 0.000 | 0.000 | 10.009 | No |
6 | LAUNDRY_FLR_1 | 78.04 | 8.4 | 9.290 | 0.108 | 5.490 | 61.680 | 535.850 | 0.000 | 0.000 | 0.000 | 603.020 | No |
7 | CAFE_FLR_1 | 188.86 | 142.3 | 1.327 | 0.753 | 12.809 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 18.189 | No |
8 | LOBBY_FLR_1 | 1308.19 | 422.4 | 3.097 | 0.323 | 10.064 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.134 | No |
9 | ROOM_1_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 10.064 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 16.814 | No |
10 | ROOM_2_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 10.064 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 16.814 | No |
11 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 16.349 | 6.116E-002 | 10.064 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 20.584 | No |
12 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 10.064 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 20.584 | No |
13 | ROOM_5_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 10.064 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 16.814 | No |
14 | ROOM_6_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 10.064 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 16.814 | No |
15 | CORRIDOR_FLR_3 | 389.40 | 21.0 | 18.581 | 5.382E-002 | 3.660 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 3.660 | No |
16 | ROOM_1_FLR_6 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 10.064 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 16.814 | No |
17 | ROOM_2_FLR_6 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 10.064 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 16.814 | No |
18 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 10.064 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 20.584 | No |
19 | BANQUET_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 12.809 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 80.629 | No |
20 | DINING_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 12.809 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 80.629 | No |
21 | KITCHEN_FLR_6 | 103.30 | 22.2 | 4.645 | 0.215 | 10.979 | 517.156 | 2419.260 | 0.000 | 0.000 | 0.000 | 2947.395 | No |
22 | CORRIDOR_FLR_6 | 412.12 | 22.2 | 18.581 | 5.382E-002 | 3.660 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 3.660 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | BASEMENT PEOPLE | BLDG_OCC_SCH | BASEMENT | 1978.83 | 106.5 | 106.5 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 106 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | RETAIL_1_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 10.8 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | RETAIL_2_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 12.5 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 13 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | LAUNDRY_FLR_1 PEOPLE | BLDG_OCC_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 8.4 | 0.108 | 9.290 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 8 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | CAFE_FLR_1 PEOPLE | BLDG_OCC_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 142.3 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 142 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | LOBBY_FLR_1 PEOPLE | BLDG_OCC_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 422.4 | 0.323 | 3.097 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 422 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | ROOM_1_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | ROOM_2_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | ROOM_3_MULT19_FLR_3 PEOPLE | ALWAYS_OFF | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 1.5 | 6.116E-002 | 16.349 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 0 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | ROOM_4_MULT19_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | ROOM_5_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | ROOM_6_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | ROOM_1_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | ROOM_2_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | ROOM_3_MULT9_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | BANQUET_FLR_6 PEOPLE | BLDG_OCC_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | DINING_FLR_6 PEOPLE | BLDG_OCC_SCH | DINING_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | KITCHEN_FLR_6 PEOPLE | BLDG_OCC_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 22.2 | 0.215 | 4.645 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | STORAGE_FLR_1 PEOPLE | BLDG_OCC_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 2.0 | 2.153E-002 | 46.451 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | CORRIDOR_FLR_3 PEOPLE | BLDG_OCC_SCH | CORRIDOR_FLR_3 | 389.40 | 21.0 | 21.0 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 21 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
21 | CORRIDOR_FLR_6 PEOPLE | BLDG_OCC_SCH | CORRIDOR_FLR_6 | 412.12 | 22.2 | 22.2 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
22 | MECH_FLR_1 PEOPLE | BLDG_OCC_SCH | MECH_FLR_1 | 164.24 | 2.7 | 2.7 | 1.615E-002 | 61.932 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 3 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_BASEMENT | BASEMENT | 1978.83 | 106.5 | 17313.725 | 8.749 | 162.572 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 17313.725 |
2 | RETAIL_1_FLR_1_LIGHTS | LTG_SCH_RETAIL | RETAIL_1_FLR_1 | 67.07 | 10.8 | 872.757 | 13.012 | 80.594 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 872.757 |
3 | RETAIL_2_FLR_1_LIGHTS | LTG_SCH_RETAIL | RETAIL_2_FLR_1 | 77.67 | 12.5 | 1010.656 | 13.012 | 80.595 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1010.656 |
4 | MECH_FLR_1_LIGHTS | LTG_SCH_MECHANIC | MECH_FLR_1 | 164.24 | 2.7 | 1652.984 | 10.064 | 623.297 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1652.984 |
5 | STORAGE_FLR_1_LIGHTS | LTG_SCH_STORAGE | STORAGE_FLR_1 | 94.76 | 2.0 | 693.586 | 7.319 | 339.993 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 693.586 |
6 | LAUNDRY_FLR_1_LIGHTS | LTG_SCH_LAUNDRY | LAUNDRY_FLR_1 | 78.04 | 8.4 | 428.405 | 5.490 | 51.001 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 428.405 |
7 | CAFE_FLR_1_LIGHTS | LTG_SCH_DINING | CAFE_FLR_1 | 188.86 | 142.3 | 2419.140 | 12.809 | 17.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2419.140 |
8 | LOBBY_FLR_1_LIGHTS | LTG_SCH_LOBBY | LOBBY_FLR_1 | 1308.19 | 422.4 | 13165.908 | 10.064 | 31.167 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 13165.908 |
9 | ROOM_1_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_1_FLR_3 | 39.02 | 1.5 | 392.727 | 10.064 | 261.818 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 392.727 |
10 | ROOM_2_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_2_FLR_3 | 39.02 | 1.5 | 392.681 | 10.064 | 261.787 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 392.681 |
11 | ROOM_3_MULT19_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 246.814 | 10.064 | 164.543 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 246.814 |
12 | ROOM_4_MULT19_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 246.881 | 10.064 | 164.588 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 246.881 |
13 | ROOM_5_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_5_FLR_3 | 39.02 | 1.5 | 392.727 | 10.064 | 261.818 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 392.727 |
14 | ROOM_6_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_6_FLR_3 | 39.02 | 1.5 | 392.681 | 10.064 | 261.787 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 392.681 |
15 | CORRIDOR_FLR_3_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_FLR_3 | 389.40 | 21.0 | 1425.114 | 3.660 | 68.002 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1425.114 |
16 | ROOM_1_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_1_FLR_6 | 39.02 | 1.5 | 392.727 | 10.064 | 261.818 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 392.727 |
17 | ROOM_2_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_2_FLR_6 | 39.02 | 1.5 | 392.681 | 10.064 | 261.787 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 392.681 |
18 | ROOM_3_MULT9_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 246.881 | 10.064 | 164.588 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 246.881 |
19 | BANQUET_FLR_6_LIGHTS | LTG_SCH_DINING | BANQUET_FLR_6 | 331.66 | 249.9 | 4248.214 | 12.809 | 17.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 4248.214 |
20 | DINING_FLR_6_LIGHTS | LTG_SCH_DINING | DINING_FLR_6 | 331.66 | 249.9 | 4248.214 | 12.809 | 17.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 4248.214 |
21 | KITCHEN_FLR_6_LIGHTS | LTG_SCH_KITCHEN | KITCHEN_FLR_6 | 103.30 | 22.2 | 1134.198 | 10.979 | 51.003 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1134.198 |
22 | CORRIDOR_FLR_6_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_FLR_6 | 412.12 | 22.2 | 1508.264 | 3.660 | 68.001 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1508.264 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | BASEMENT_EQUIP_SCH | BASEMENT | 1978.83 | 106.5 | 10646.106 | 5.380 | 99.964 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10646.106 |
2 | RETAIL_1_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 721.688 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 721.688 |
3 | RETAIL_2_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 835.717 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 835.717 |
4 | MECH_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | MECH_FLR_1 | 164.24 | 2.7 | 883.628 | 5.380 | 333.193 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 883.628 |
5 | STORAGE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 254.902 | 2.690 | 124.952 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 254.902 |
6 | LAUNDRY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 4813.474 | 61.680 | 573.033 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 4813.474 |
7 | CAFE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 1016.077 | 5.380 | 7.140 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1016.077 |
8 | LOBBY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 10557.062 | 8.070 | 24.991 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10557.062 |
9 | ROOM_1_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_1_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
10 | ROOM_2_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_2_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
11 | ROOM_3_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 257.991 | 10.520 | 171.994 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 257.991 |
12 | ROOM_4_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
13 | ROOM_5_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_5_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
14 | ROOM_6_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_6_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
15 | ROOM_1_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_1_FLR_6 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
16 | ROOM_2_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_2_FLR_6 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
17 | ROOM_3_MULT9_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
18 | BANQUET_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
19 | DINING_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | DINING_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
20 | KITCHEN_FLR_6_MISCELEC_EQUIP | KITCHEN_ELEC_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 52482.799 | 508.040 | 2360.050 | 0.200 | 0.500 | 0.100 | 0.200 | Cooking | 0.000 | 15744.840 |
21 | KITCHEN_FLR_6_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 515.917 | 4.994 | 23.200 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 515.917 | 515.917 |
22 | KITCHEN_FLR_6_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 425.833 | 4.122 | 19.149 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 425.833 | 425.833 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LAUNDRY_FLR_1_MISCGAS_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 41817.449 | 535.850 | 4978.268 | 0.000 | 0.500 | 0.000 | 0.500 | Laundry | 0.000 | 41817.449 |
2 | KITCHEN_FLR_6_MISCGAS_EQUIP | KITCHEN_GAS_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 249920.353 | 2419.260 | 11238.437 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 74976.106 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.464 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | OVERHEAD DOOR_CON | 2 | 1 | 1 | 0.167 | 1.198 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
3 | INTERIORFURNISHINGS | 3 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 8 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 18 | 3 | 3 | 0.167 | 0.2832 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
6 | RES_ROOF | 19 | 3 | 3 | 0.167 | 0.2832 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
7 | NONRES_EXT_WALL_GRD | 21 | 3 | 9 | 0.167 | 0.9686 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | NONRES_EXT_WALL_MID | 22 | 3 | 9 | 0.167 | 1.265 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | NONRES_EXT_WALL_TOP | 23 | 3 | 9 | 0.167 | 1.335 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | RES_EXT_WALL_MID | 25 | 3 | 9 | 0.167 | 1.217 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | RES_EXT_WALL_TOP | 26 | 3 | 9 | 0.167 | 1.286 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | NONRES_FLOOR | 30 | 3 | 7 | 0.167 | 0.1963 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
13 | NONRES_FLOOR_CEILING | 33 | 3 | 7 | 0.167 | 0.1963 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
14 | BASEMENT_FLOOR | 36 | 2 | 7 | 0.333 | 2.705 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
15 | BASEMENT_WALL_NORTH_CFACTOR | 39 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | BASEMENT_WALL_EAST_CFACTOR | 40 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | BASEMENT_WALL_SOUTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
18 | BASEMENT_WALL_WEST_CFACTOR | 42 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2887 |
2 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8346 |
3 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 3.472 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
10 | RES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 3.472 |
11 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
12 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
13 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8651 |
14 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.6234 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5819 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | RES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.6546 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
25 | RES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.6103 |
26 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
27 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.833 |
28 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
29 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
30 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
31 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
32 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.833 |
33 | M10 200MM CONCRETE BLOCK BASEMENT WALL | 0.2032 | 1.326 | 1842.000 | 912.000 | 0.1532 |
34 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
35 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
36 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
37 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
38 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
39 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
40 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
41 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
42 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.4637404 | 3.4637404 | 3.4637404 | |
3 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
4 | 0 | 1.1981135 | 1.1981135 | 1.1981135 | |
5 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
6 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
7 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
8 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
9 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
10 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
11 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
12 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
13 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
14 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
15 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
16 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
17 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
18 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
19 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
20 | 3 | -0.61927053E-06 | 0.12767249E-08 | -0.37968499E-05 | 0.16832131E-17 |
21 | 2 | 0.77611055 | 0.17315568E-02 | 1.0534842 | -0.72792597E-06 |
22 | 1 | -21.915918 | 0.11588205 | -6.3286394 | 0.20197014 |
23 | 0 | 21.365777 | 0.10835518 | 5.5011278 | |
24 | 3 | -0.61927053E-06 | 0.12767249E-08 | -0.37968499E-05 | 0.16832131E-17 |
25 | 2 | 0.77611055 | 0.17315568E-02 | 1.0534842 | -0.72792597E-06 |
26 | 1 | -21.915918 | 0.11588205 | -6.3286394 | 0.20197014 |
27 | 0 | 21.365777 | 0.10835518 | 5.5011278 | |
28 | 9 | 0.28610217E-16 | 0.32712183E-16 | -0.14788665E-09 | 0.15262255E-17 |
29 | 8 | 0.21617198E-07 | 0.13019051E-12 | 0.37508535E-03 | -0.24579497E-09 |
30 | 7 | -0.12160768E-01 | 0.67781631E-08 | -0.22969495E-01 | 0.13827236E-03 |
31 | 6 | 0.40315523 | 0.23644201E-05 | 0.47022156 | -0.47218870E-02 |
32 | 5 | -5.1691419 | 0.88489975E-04 | -4.4269034 | 0.62918229E-01 |
33 | 4 | 32.908103 | 0.72540386E-03 | 21.384224 | -0.42086483 |
34 | 3 | -111.02464 | 0.15839520E-02 | -55.513084 | 1.5122822 |
35 | 2 | 196.93145 | 0.89247901E-03 | 77.773085 | -2.8975455 |
36 | 1 | -171.09078 | 0.95424204E-04 | -55.225093 | 2.7442950 |
37 | 0 | 57.057407 | 0.54416031E-06 | 15.563533 | |
38 | 9 | 0.16021817E-14 | 0.43623596E-16 | -0.13387302E-09 | -0.38399267E-17 |
39 | 8 | 0.19641607E-07 | 0.16693997E-12 | 0.35391383E-03 | -0.22333182E-09 |
40 | 7 | -0.11527600E-01 | 0.88905521E-08 | -0.22057378E-01 | 0.13107300E-03 |
41 | 6 | 0.38594887 | 0.31296587E-05 | 0.45553223 | -0.45190661E-02 |
42 | 5 | -5.0012033 | 0.11804975E-03 | -4.3139252 | 0.60835889E-01 |
43 | 4 | 32.165114 | 0.97455506E-03 | 20.942266 | -0.41100022 |
44 | 3 | -109.44341 | 0.21413112E-02 | -54.639172 | 1.4894383 |
45 | 2 | 195.36376 | 0.12132308E-02 | 76.972220 | -2.8726514 |
46 | 1 | -170.51151 | 0.13038514E-03 | -54.993414 | 2.7341426 |
47 | 0 | 57.057407 | 0.74764616E-06 | 15.602778 | |
48 | 9 | 0.89845624E-15 | 0.45148486E-16 | -0.13053700E-09 | -0.34170761E-17 |
49 | 8 | 0.19169472E-07 | 0.17528607E-12 | 0.34874871E-03 | -0.21796351E-09 |
50 | 7 | -0.11372769E-01 | 0.93896549E-08 | -0.21834212E-01 | 0.12931251E-03 |
51 | 6 | 0.38174081 | 0.33130355E-05 | 0.45193069 | -0.44694638E-02 |
52 | 5 | -4.9601253 | 0.12521571E-03 | -4.2861852 | 0.60326552E-01 |
53 | 4 | 31.983339 | 0.10355575E-02 | 20.833661 | -0.40858686 |
54 | 3 | -109.05644 | 0.22789331E-02 | -54.424381 | 1.4838481 |
55 | 2 | 194.97998 | 0.12930063E-02 | 76.775547 | -2.8665574 |
56 | 1 | -170.36965 | 0.13913733E-03 | -54.936825 | 2.7316564 |
57 | 0 | 57.057407 | 0.79895123E-06 | 15.612614 | |
58 | 9 | 0.12430042E-14 | 0.43603463E-16 | -0.13615479E-09 | -0.52742981E-17 |
59 | 8 | 0.19963588E-07 | 0.16114398E-12 | 0.35741204E-03 | -0.22699287E-09 |
60 | 7 | -0.11632381E-01 | 0.85488282E-08 | -0.22208377E-01 | 0.13226440E-03 |
61 | 6 | 0.38879653 | 0.30047059E-05 | 0.45796739 | -0.45526330E-02 |
62 | 5 | -5.0290001 | 0.11318598E-03 | -4.3326723 | 0.61180550E-01 |
63 | 4 | 32.288109 | 0.93328928E-03 | 21.015642 | -0.41263319 |
64 | 3 | -109.70522 | 0.20484795E-02 | -54.784283 | 1.4932205 |
65 | 2 | 195.62339 | 0.11595496E-02 | 77.105128 | -2.8767741 |
66 | 1 | -170.60747 | 0.12450863E-03 | -55.031726 | 2.7358244 |
67 | 0 | 57.057407 | 0.71328115E-06 | 15.596176 | |
68 | 9 | 0.10418955E-14 | 0.45554749E-16 | -0.13285794E-09 | -0.34221686E-17 |
69 | 8 | 0.19498290E-07 | 0.16949498E-12 | 0.35235048E-03 | -0.22170227E-09 |
70 | 7 | -0.11480752E-01 | 0.90423087E-08 | -0.21989859E-01 | 0.13054032E-03 |
71 | 6 | 0.38467563 | 0.31853038E-05 | 0.45444290 | -0.45040579E-02 |
72 | 5 | -4.9887746 | 0.12022067E-03 | -4.3055366 | 0.60681782E-01 |
73 | 4 | 32.110117 | 0.99300969E-03 | 20.909427 | -0.41027004 |
74 | 3 | -109.32633 | 0.21828955E-02 | -54.574228 | 1.4877470 |
75 | 2 | 195.24766 | 0.12373115E-02 | 76.912747 | -2.8708078 |
76 | 1 | -170.46860 | 0.13302463E-03 | -54.976289 | 2.7333905 |
77 | 0 | 57.057407 | 0.76310210E-06 | 15.605744 | |
78 | 7 | -0.15963512E-14 | -0.15187529E-16 | -0.22427203E-13 | 0.56155309E-15 |
79 | 6 | 0.17983713E-10 | 0.23594901E-11 | 0.52322926E-09 | -0.18637893E-10 |
80 | 5 | -0.60139213E-07 | 0.11510628E-07 | -0.21924491E-05 | 0.17161312E-06 |
81 | 4 | 0.62746279E-04 | 0.43399923E-05 | 0.17681060E-02 | -0.28244642E-03 |
82 | 3 | -0.90508353E-02 | 0.15320797E-03 | -0.21560640 | 0.43341486E-01 |
83 | 2 | 0.12836503 | 0.66328859E-03 | 2.9007871 | -0.61911613 |
84 | 1 | -0.32478029 | 0.41934727E-03 | -7.1379041 | 1.5697129 |
85 | 0 | 0.20664896 | 0.54311639E-05 | 4.4522013 | |
86 | 7 | -0.22427203E-13 | -0.15187529E-16 | -0.15963512E-14 | 0.56155309E-15 |
87 | 6 | 0.52322926E-09 | 0.23594901E-11 | 0.17983713E-10 | -0.18637893E-10 |
88 | 5 | -0.21924491E-05 | 0.11510628E-07 | -0.60139213E-07 | 0.17161312E-06 |
89 | 4 | 0.17681060E-02 | 0.43399923E-05 | 0.62746279E-04 | -0.28244642E-03 |
90 | 3 | -0.21560640 | 0.15320797E-03 | -0.90508353E-02 | 0.43341486E-01 |
91 | 2 | 2.9007871 | 0.66328859E-03 | 0.12836503 | -0.61911613 |
92 | 1 | -7.1379041 | 0.41934727E-03 | -0.32478029 | 1.5697129 |
93 | 0 | 4.4522013 | 0.54311639E-05 | 0.20664896 | |
94 | 7 | -0.52459208E-15 | -0.63961428E-15 | -0.12292524E-09 | -0.35846135E-17 |
95 | 6 | 0.39860198E-02 | 0.96339020E-07 | 0.40499006E-03 | -0.70890431E-04 |
96 | 5 | -0.20832379 | 0.49172556E-04 | -0.20585669E-01 | 0.38489246E-02 |
97 | 4 | 3.5198270 | 0.18993977E-02 | 0.34924834 | -0.69168259E-01 |
98 | 3 | -23.366787 | 0.13311857E-01 | -2.4329538 | 0.50524779 |
99 | 2 | 64.890127 | 0.19943872E-01 | 7.3672511 | -1.5911358 |
100 | 1 | -76.040094 | 0.56792084E-02 | -9.5568013 | 2.1361271 |
101 | 0 | 31.242244 | 0.96490710E-04 | 4.3344156 | |
102 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
103 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
104 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
105 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
106 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
107 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
108 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
109 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
110 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
111 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
112 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
113 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
114 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
115 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
116 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
117 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
118 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
119 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
120 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
121 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
122 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
123 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
124 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
125 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
126 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
127 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
128 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
129 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
130 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
131 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
132 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
133 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.4711_SHGC_0.25 | 37 | 1 | VerySmooth | 2.678 | 2.678 | 1.000 | 0.251 | ||
2 | RESWINDOW_U_0.4711_SHGC_0.25 | 38 | 1 | VerySmooth | 2.678 | 2.678 | 1.000 | 0.251 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER | SpectralAverage | 2.39142E-002 | 0.16139 | 0.61472 | 0.61472 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.11798 | 1.00000 | No | |
2 | RESIDENTIAL WINDOW GLAZING LAYER | SpectralAverage | 2.39142E-002 | 0.16139 | 0.61472 | 0.61472 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.11798 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 7 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 1.500 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 3.000 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWH BOOSTER E WATER HEATER | 2.2712E-002 | 8000.0 | 1.240 | 1.1473 |
2 | WaterHeater:Mixed | SWH LAUNDRY G WATER HEATER | 1.1356 | 163316.0 | 0.576 | 0.5074 |
3 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 2.2712 | 175842.6 | 0.260 | 2.5713E-002 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
6 | BASEMENT_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
7 | BASEMENT_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
8 | BASEMENT_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
9 | BASEMENT_CEILING_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
10 | BASEMENT_CEILING_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
11 | BASEMENT_CEILING_6 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
12 | BASEMENT_CEILING_7 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
13 | BASEMENT_CEILING_8 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
14 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
15 | RETAIL_1_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 4 | No | No |
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 1 | No | No |
17 | RETAIL_1_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 3 | No | No |
18 | RETAIL_1_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
19 | RETAIL_1_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
20 | RETAIL_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
21 | RETAIL_1_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
23 | RETAIL_2_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
25 | RETAIL_2_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
26 | RETAIL_2_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
27 | RETAIL_2_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
28 | RETAIL_2_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
29 | RETAIL_2_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
31 | MECH_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
32 | MECH_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
33 | MECH_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
34 | MECH_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
35 | MECH_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
36 | MECH_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
37 | MECH_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
38 | STORAGE_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
40 | STORAGE_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
41 | STORAGE_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
42 | STORAGE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
43 | STORAGE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
44 | STORAGE_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
45 | STORAGE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
46 | LAUNDRY_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
47 | LAUNDRY_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
49 | LAUNDRY_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
50 | LAUNDRY_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
51 | LAUNDRY_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
52 | LAUNDRY_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
54 | CAFE_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 3 | No | No |
55 | CAFE_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
56 | CAFE_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 4 | No | No |
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 1 | No | No |
58 | CAFE_FLR_1_WALL_1_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
59 | CAFE_FLR_1_WALL_2_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
60 | CAFE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
61 | CAFE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
62 | CAFE_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
63 | CAFE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
64 | LOBBY_FLR_1_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
67 | LOBBY_FLR_1_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
68 | LOBBY_FLR_1_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 1 | No | No |
70 | LOBBY_FLR_1_WALL_1_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
71 | LOBBY_FLR_1_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
72 | LOBBY_FLR_1_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
73 | LOBBY_FLR_1_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
74 | LOBBY_FLR_1_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
75 | LOBBY_FLR_1_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
76 | LOBBY_FLR_1_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
77 | LOBBY_FLR_1_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
78 | LOBBY_FLR_1_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
79 | LOBBY_FLR_1_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
80 | LOBBY_FLR_1_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
81 | LOBBY_FLR_1_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
82 | LOBBY_FLR_1_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
83 | LOBBY_FLR_1_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
84 | LOBBY_FLR_1_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
85 | LOBBY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
86 | ROOM_1_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
88 | ROOM_1_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
90 | ROOM_1_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
91 | ROOM_1_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
92 | ROOM_1_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
93 | ROOM_1_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
94 | ROOM_1_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
95 | ROOM_2_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
97 | ROOM_2_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
99 | ROOM_2_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
100 | ROOM_2_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
101 | ROOM_2_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
102 | ROOM_2_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
103 | ROOM_2_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
109 | ROOM_3_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
110 | ROOM_3_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
117 | ROOM_4_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
118 | ROOM_4_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
120 | ROOM_5_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
122 | ROOM_5_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
124 | ROOM_5_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
125 | ROOM_5_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
126 | ROOM_5_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
127 | ROOM_5_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
128 | ROOM_5_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
129 | ROOM_6_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
131 | ROOM_6_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
133 | ROOM_6_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
134 | ROOM_6_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
135 | ROOM_6_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
136 | ROOM_6_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
137 | ROOM_6_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
138 | CORRIDOR_FLR_3_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
147 | CORRIDOR_FLR_3_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
148 | CORRIDOR_FLR_3_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
149 | CORRIDOR_FLR_3_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
150 | CORRIDOR_FLR_3_WALL_4_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
152 | CORRIDOR_FLR_3_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
153 | CORRIDOR_FLR_3_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
154 | CORRIDOR_FLR_3_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
155 | CORRIDOR_FLR_3_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
156 | CORRIDOR_FLR_3_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
157 | CORRIDOR_FLR_3_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
158 | CORRIDOR_FLR_3_FLOOR_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
159 | CORRIDOR_FLR_3_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
160 | CORRIDOR_FLR_3_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
161 | CORRIDOR_FLR_3_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
163 | ROOM_1_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
165 | ROOM_1_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
167 | ROOM_1_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
168 | ROOM_1_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
169 | ROOM_1_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
170 | ROOM_1_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
171 | ROOM_1_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
172 | ROOM_2_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
174 | ROOM_2_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
176 | ROOM_2_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
177 | ROOM_2_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
178 | ROOM_2_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
179 | ROOM_2_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
180 | ROOM_2_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 3 | No | No |
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 2 | No | No |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
186 | ROOM_3_MULT9_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
187 | ROOM_3_MULT9_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
189 | BANQUET_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
191 | BANQUET_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
192 | BANQUET_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
193 | BANQUET_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
194 | BANQUET_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
195 | BANQUET_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
196 | BANQUET_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
197 | DINING_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
198 | DINING_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
199 | DINING_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
200 | DINING_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
201 | DINING_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
202 | DINING_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
203 | DINING_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
204 | DINING_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
205 | KITCHEN_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
207 | KITCHEN_FLR_6_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
212 | KITCHEN_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
213 | KITCHEN_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
214 | KITCHEN_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
215 | KITCHEN_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
216 | KITCHEN_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
217 | CORRIDOR_FLR_6_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
224 | CORRIDOR_FLR_6_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
226 | CORRIDOR_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
227 | CORRIDOR_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
228 | CORRIDOR_FLR_6_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
229 | CORRIDOR_FLR_6_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
230 | CORRIDOR_FLR_6_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
231 | CORRIDOR_FLR_6_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
232 | CORRIDOR_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
233 | CORRIDOR_FLR_6_CEILING_1 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
234 | CORRIDOR_FLR_6_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | RETAIL_1_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 7.058E-002 | 1.052E-003 | 5.193E-004 | 0.956 | 1.000 | 0.000 | 0.000 | 0.000 |
2 | RETAIL_2_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 2.724E-002 | 3.507E-004 | 9.551E-004 | 0.319 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | MECH_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | MECH_FLR_1 | 164.24 | 2.7 | 6.438E-002 | 3.920E-004 | 1.025E-003 | 0.356 | 1.000 | 0.000 | 0.000 | 0.000 |
4 | STORAGE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 3.715E-002 | 3.920E-004 | 8.507E-004 | 0.356 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | LAUNDRY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 8.791E-002 | 1.127E-003 | 1.002E-003 | 1.023 | 1.000 | 0.000 | 0.000 | 0.000 |
6 | CAFE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 0.156 | 8.261E-004 | 4.549E-004 | 0.751 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | LOBBY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 0.446 | 3.407E-004 | 6.517E-004 | 0.310 | 1.000 | 0.000 | 0.000 | 0.000 |
8 | ROOM_1_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 4.096E-002 | 1.050E-003 | 1.025E-003 | 1.240 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | ROOM_2_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 4.095E-002 | 1.050E-003 | 1.025E-003 | 1.240 | 1.000 | 0.000 | 0.000 | 0.000 |
10 | ROOM_3_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 1.143E-002 | 4.660E-004 | 1.025E-003 | 0.550 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | ROOM_4_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 1.143E-002 | 4.660E-004 | 1.025E-003 | 0.550 | 1.000 | 0.000 | 0.000 | 0.000 |
12 | ROOM_5_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 4.096E-002 | 1.050E-003 | 1.025E-003 | 1.240 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | ROOM_6_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 4.095E-002 | 1.050E-003 | 1.025E-003 | 1.240 | 1.000 | 0.000 | 0.000 | 0.000 |
14 | CORRIDOR_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_3 | 389.40 | 21.0 | 4.953E-002 | 1.272E-004 | 1.025E-003 | 0.150 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | ROOM_1_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 4.096E-002 | 1.050E-003 | 5.186E-004 | 1.240 | 1.000 | 0.000 | 0.000 | 0.000 |
16 | ROOM_2_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 4.095E-002 | 1.050E-003 | 5.186E-004 | 1.240 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | ROOM_3_MULT9_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 2.096E-002 | 8.543E-004 | 4.660E-004 | 1.009 | 1.000 | 0.000 | 0.000 | 0.000 |
18 | BANQUET_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 0.100 | 3.015E-004 | 2.330E-004 | 0.356 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | DINING_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | DINING_FLR_6 | 331.66 | 249.9 | 0.100 | 3.015E-004 | 2.330E-004 | 0.356 | 1.000 | 0.000 | 0.000 | 0.000 |
20 | KITCHEN_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 8.953E-002 | 8.667E-004 | 4.697E-004 | 1.024 | 1.000 | 0.000 | 0.000 | 0.000 |
21 | CORRIDOR_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_6 | 412.12 | 22.2 | 8.763E-002 | 2.126E-004 | 1.761E-004 | 0.251 | 1.000 | 0.000 | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | ROOM_1_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
2 | ROOM_2_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
3 | ROOM_3_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
4 | ROOM_4_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
5 | ROOM_5_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_5_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
6 | ROOM_6_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_6_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
7 | ROOM_1_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
8 | ROOM_2_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
9 | ROOM_3_MULT9_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | RETAIL_1_FLR_1 | Mixing/Well-Stirred |
3 | RETAIL_2_FLR_1 | Mixing/Well-Stirred |
4 | MECH_FLR_1 | Mixing/Well-Stirred |
5 | STORAGE_FLR_1 | Mixing/Well-Stirred |
6 | LAUNDRY_FLR_1 | Mixing/Well-Stirred |
7 | CAFE_FLR_1 | Mixing/Well-Stirred |
8 | LOBBY_FLR_1 | Mixing/Well-Stirred |
9 | ROOM_1_FLR_3 | Mixing/Well-Stirred |
10 | ROOM_2_FLR_3 | Mixing/Well-Stirred |
11 | ROOM_3_MULT19_FLR_3 | Mixing/Well-Stirred |
12 | ROOM_4_MULT19_FLR_3 | Mixing/Well-Stirred |
13 | ROOM_5_FLR_3 | Mixing/Well-Stirred |
14 | ROOM_6_FLR_3 | Mixing/Well-Stirred |
15 | CORRIDOR_FLR_3 | Mixing/Well-Stirred |
16 | ROOM_1_FLR_6 | Mixing/Well-Stirred |
17 | ROOM_2_FLR_6 | Mixing/Well-Stirred |
18 | ROOM_3_MULT9_FLR_6 | Mixing/Well-Stirred |
19 | BANQUET_FLR_6 | Mixing/Well-Stirred |
20 | DINING_FLR_6 | Mixing/Well-Stirred |
21 | KITCHEN_FLR_6 | Mixing/Well-Stirred |
22 | CORRIDOR_FLR_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 34112.29191 | 34112.29191 | 2.85787 | 2.85787 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 20:50:00 | 30.62500 | 6.85962E-003 | 1978.83018 | 106.49900 | 0.85446 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 0.85446 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -5.20000 | 2.80840E-003 | 1978.83018 | 106.49900 | 0.85446 | 0.00000 |
3 | RETAIL_1_FLR_1 | Cooling | 4647.20312 | 4647.20312 | 0.38936 | 0.38936 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 37.99167 | 6.87130E-003 | 67.07136 | 10.82900 | 7.92179E-002 | 0.00000 |
4 | RETAIL_1_FLR_1 | Heating | 2998.71530 | 2998.71530 | 0.14819 | 0.14819 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -5.20000 | 2.80840E-003 | 67.07136 | 10.82900 | 7.92179E-002 | 0.00000 |
5 | RETAIL_2_FLR_1 | Cooling | 3392.09922 | 3392.09922 | 0.28421 | 0.28421 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 36.06333 | 6.86822E-003 | 77.66889 | 12.54000 | 9.17347E-002 | 0.00000 |
6 | RETAIL_2_FLR_1 | Heating | 973.16003 | 973.16003 | 4.80952E-002 | 9.17347E-002 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -5.20000 | 2.80840E-003 | 77.66889 | 12.54000 | 9.17347E-002 | 0.00000 |
7 | MECH_FLR_1 | Cooling | 3633.18445 | 3633.18445 | 0.30434 | 0.30434 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 34.98000 | 6.86649E-003 | 164.24319 | 2.65200 | 0.00000 | 0.00000 |
8 | MECH_FLR_1 | Heating | 1807.62678 | 1807.62678 | 8.93356E-002 | 8.93356E-002 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -5.20000 | 2.80840E-003 | 164.24319 | 2.65200 | 0.00000 | 0.00000 |
9 | STORAGE_FLR_1 | Cooling | 1834.88081 | 1834.88081 | 0.15371 | 0.15371 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 36.06333 | 6.86822E-003 | 94.75927 | 2.04000 | 5.77652E-002 | 0.00000 |
10 | STORAGE_FLR_1 | Heating | 1082.90840 | 1082.90840 | 5.35190E-002 | 5.77652E-002 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -5.20000 | 2.80840E-003 | 94.75927 | 2.04000 | 5.77652E-002 | 0.00000 |
11 | LAUNDRY_FLR_1 | Cooling | 45235.90091 | 45235.90091 | 3.78963 | 3.78963 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 37.58000 | 6.87065E-003 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
12 | LAUNDRY_FLR_1 | Heating | 2432.05620 | 2432.05620 | 0.12019 | 0.12019 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -5.20000 | 2.80840E-003 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
13 | CAFE_FLR_1 | Cooling | 19748.76616 | 19748.76616 | 1.65608 | 1.65608 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 37.99167 | 6.87130E-003 | 188.86188 | 142.30000 | 0.67639 | 0.00000 |
14 | CAFE_FLR_1 | Heating | 7536.21754 | 7536.21754 | 0.37244 | 0.67639 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -5.20000 | 2.80840E-003 | 188.86188 | 142.30000 | 0.67639 | 0.00000 |
15 | LOBBY_FLR_1 | Cooling | 65273.02912 | 65273.02912 | 5.47065 | 5.47065 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 38.10000 | 6.87148E-003 | 1308.18612 | 422.43500 | 1.89399 | 0.00000 |
16 | LOBBY_FLR_1 | Heating | 17434.44623 | 17434.44623 | 0.86164 | 1.89399 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -5.20000 | 2.80840E-003 | 1308.18612 | 422.43500 | 1.89399 | 0.00000 |
17 | ROOM_1_FLR_3 | Cooling | 11139.23111 | 11139.23111 | 1.25746 | 1.25746 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 36.80000 | 6.86940E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
18 | ROOM_1_FLR_3 | Heating | 6582.01508 | 6582.01508 | 0.32718 | 0.32718 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -5.20000 | 2.80840E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
19 | ROOM_2_FLR_3 | Cooling | 11059.32275 | 11059.32275 | 1.24844 | 1.24844 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 36.62667 | 6.86912E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
20 | ROOM_2_FLR_3 | Heating | 6575.47122 | 6575.47122 | 0.32686 | 0.32686 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -5.20000 | 2.80840E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
21 | ROOM_3_MULT19_FLR_3 | Cooling | 67864.35353 | 67864.35353 | 7.66073 | 7.66073 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 38.10000 | 6.87148E-003 | 24.52384 | 1.50000 | 0.83707 | 0.00000 |
22 | ROOM_3_MULT19_FLR_3 | Heating | 37722.34327 | 37722.34327 | 1.87523 | 1.87523 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -5.20000 | 2.80840E-003 | 24.52384 | 1.50000 | 0.83707 | 0.00000 |
23 | ROOM_4_MULT19_FLR_3 | Cooling | 73041.28219 | 73041.28219 | 8.24577 | 8.24577 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 37.71000 | 6.87086E-003 | 24.53055 | 1.50000 | 0.83730 | 0.00000 |
24 | ROOM_4_MULT19_FLR_3 | Heating | 37618.36298 | 37618.36298 | 1.87006 | 1.87006 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -5.20000 | 2.80840E-003 | 24.53055 | 1.50000 | 0.83730 | 0.00000 |
25 | ROOM_5_FLR_3 | Cooling | 9753.72736 | 9753.72736 | 1.10106 | 1.10106 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | 33.81000 | 6.86464E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
26 | ROOM_5_FLR_3 | Heating | 6569.75080 | 6569.75080 | 0.32658 | 0.32658 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -5.20000 | 2.80840E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
27 | ROOM_6_FLR_3 | Cooling | 9674.26559 | 9674.26559 | 1.09209 | 1.09209 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 | 33.48500 | 6.86412E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
28 | ROOM_6_FLR_3 | Heating | 6563.20525 | 6563.20525 | 0.32625 | 0.32625 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -5.20000 | 2.80840E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
29 | CORRIDOR_FLR_3 | Cooling | 16255.55042 | 16255.55042 | 1.36182 | 1.36182 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 37.84000 | 6.87107E-003 | 389.40468 | 20.95700 | 0.47476 | 0.00000 |
30 | CORRIDOR_FLR_3 | Heating | 10146.72041 | 10146.72041 | 0.50148 | 0.50148 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -5.20000 | 2.80840E-003 | 389.40468 | 20.95700 | 0.47476 | 0.00000 |
31 | ROOM_1_FLR_6 | Cooling | 3019.75609 | 3019.75609 | 0.34089 | 0.34089 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 36.80000 | 6.86940E-003 | 39.02202 | 1.50000 | 1.54338E-002 | 0.00000 |
32 | ROOM_1_FLR_6 | Heating | 2054.13890 | 2054.13890 | 0.10211 | 0.10211 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -5.20000 | 2.80840E-003 | 39.02202 | 1.50000 | 1.54338E-002 | 0.00000 |
33 | ROOM_2_FLR_6 | Cooling | 2994.96289 | 2994.96289 | 0.33809 | 0.33809 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 36.80000 | 6.86940E-003 | 39.01745 | 1.50000 | 1.54319E-002 | 0.00000 |
34 | ROOM_2_FLR_6 | Heating | 2053.31535 | 2053.31535 | 0.10207 | 0.10207 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -5.20000 | 2.80840E-003 | 39.01745 | 1.50000 | 1.54319E-002 | 0.00000 |
35 | ROOM_3_MULT9_FLR_6 | Cooling | 13659.77070 | 13659.77070 | 1.54205 | 1.54205 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 38.10000 | 6.87148E-003 | 24.53055 | 1.50000 | 9.91540E-002 | 0.00000 |
36 | ROOM_3_MULT9_FLR_6 | Heating | 9915.79626 | 9915.79626 | 0.49291 | 0.49291 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -5.20000 | 2.80840E-003 | 24.53055 | 1.50000 | 9.91540E-002 | 0.00000 |
37 | BANQUET_FLR_6 | Cooling | 31477.21531 | 31477.21531 | 2.64042 | 2.64042 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 38.10000 | 6.87148E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
38 | BANQUET_FLR_6 | Heating | 6958.27917 | 6958.27917 | 0.34389 | 1.18780 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -5.20000 | 2.80840E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
39 | DINING_FLR_6 | Cooling | 33000.63768 | 33000.63768 | 2.76816 | 2.76816 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 38.10000 | 6.87148E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
40 | DINING_FLR_6 | Heating | 7085.82715 | 7085.82715 | 0.35019 | 1.18780 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | -5.20000 | 2.80840E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
41 | KITCHEN_FLR_6 | Cooling | 31366.80312 | 31366.80312 | 2.63491 | 2.63491 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 36.93000 | 6.86961E-003 | 103.30446 | 22.23800 | 0.36735 | 0.00000 |
42 | KITCHEN_FLR_6 | Heating | 2031.67732 | 2031.67732 | 0.10039 | 0.36735 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | -5.20000 | 2.80840E-003 | 103.30446 | 22.23800 | 0.36735 | 0.00000 |
43 | CORRIDOR_FLR_6 | Cooling | 10077.63626 | 10077.63626 | 0.84425 | 0.84425 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 38.10000 | 6.87148E-003 | 412.12471 | 22.18000 | 0.12562 | 0.00000 |
44 | CORRIDOR_FLR_6 | Heating | 7385.91129 | 7385.91129 | 0.36502 | 0.36502 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | -5.20000 | 2.80840E-003 | 412.12471 | 22.18000 | 0.12562 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV WITH REHEAT | Cooling | Sensible | 664789.32 | 25.03918 | 25.03918 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | VAV WITH REHEAT | Heating | Sensible | 173318.42 | 7.54149 | 7.54149 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 |
3 | FLR_3_DOAS | Cooling | Sensible | 54460.49 | 22.38614 | 2.05125 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | FLR_3_DOAS | Heating | Sensible | 47141.68 | 5.74925 | 2.05125 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.85787 |
2 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.52762 |
3 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.99500 |
4 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.84358 |
5 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
6 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 7.22112E-004 |
8 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.13915E-004 |
9 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.84358 |
10 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
11 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
12 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 13021.18313 |
13 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.13915E-004 |
14 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 271.53433 |
15 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.38936 |
16 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13126 |
17 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.99500 |
18 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.38741 |
19 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.99500 |
20 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
21 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.90257E-003 |
22 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.17337E-005 |
23 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.38741 |
24 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
25 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
26 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 4770.42116 |
27 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.17337E-005 |
28 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 109.12167 |
29 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.28421 |
30 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.20824 |
31 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.99500 |
32 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.28279 |
33 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.99500 |
34 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
35 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.82965E-003 |
36 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.98272E-005 |
37 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.28279 |
38 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
40 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 2266.37274 |
41 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.98272E-005 |
42 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 49.18207 |
43 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.30434 |
44 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.41122 |
45 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.99500 |
46 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.30282 |
47 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
48 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
49 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 9.26502E-004 |
50 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.79252E-005 |
51 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.30282 |
52 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
53 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
54 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 3192.02289 |
55 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.79252E-005 |
56 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 71.41463 |
57 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.15371 |
58 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.46977 |
59 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.99500 |
60 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.15294 |
61 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
62 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 8.11029E-004 |
64 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.55907E-005 |
65 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.15294 |
66 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
67 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
68 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1782.11531 |
69 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.55907E-005 |
70 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 40.42657 |
71 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 3.78963 |
72 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 6.22683E-002 |
73 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.99500 |
74 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 3.77068 |
75 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.99500 |
76 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
77 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.42802E-002 |
78 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.72061E-004 |
79 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 3.77068 |
80 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
81 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
82 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 19667.58846 |
83 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.72061E-004 |
84 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 413.11240 |
85 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.65608 |
86 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 8.68996E-002 |
87 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.99500 |
88 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.64780 |
89 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.99500 |
90 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
91 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.38437E-003 |
92 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.31866E-004 |
93 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.64780 |
94 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
96 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 15073.10390 |
97 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.31866E-004 |
98 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 331.53916 |
99 | Fan:ZoneExhaust | LOBBY_FLR_1 EXHAUST FAN | User-Specified Maximum Flow Rate [m3/s] | 0.00000 |
100 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.47065 |
101 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.18222 |
102 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.99500 |
103 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 5.44330 |
104 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.99500 |
105 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
106 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.09093E-003 |
107 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.70313E-004 |
108 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 5.44330 |
109 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
110 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
111 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 42329.06585 |
112 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.70313E-004 |
113 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 915.98375 |
114 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_1_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17350E-002 |
115 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.25746 |
116 | Fan:OnOff | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.25746 |
117 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 5.75803E-005 |
118 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 4.76020E-004 |
119 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 22.69931 |
120 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
121 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.51776E-003 |
122 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
123 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
124 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.76020E-004 |
125 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.25746 |
126 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 6581.78359 |
127 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.75803E-005 |
128 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 188.10147 |
129 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_2_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17278E-002 |
130 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.24844 |
131 | Fan:OnOff | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.24844 |
132 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 5.75231E-005 |
133 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 4.72617E-004 |
134 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 22.69931 |
135 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
136 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.51786E-003 |
137 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
138 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
139 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.72617E-004 |
140 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.24844 |
141 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 6575.23994 |
142 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.75231E-005 |
143 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 187.91451 |
144 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_3_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.83707 |
145 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 7.66073 |
146 | Fan:OnOff | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 7.66073 |
147 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 3.30006E-004 |
148 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.88700E-003 |
149 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 22.69972 |
150 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
151 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.45810E-003 |
152 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
153 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.45810E-003 |
154 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.88700E-003 |
155 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 7.66073 |
156 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 37721.68784 |
157 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.30006E-004 |
158 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 1078.03274 |
159 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_4_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.83730 |
160 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 8.24577 |
161 | Fan:OnOff | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 8.24577 |
162 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 3.29096E-004 |
163 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.22711E-003 |
164 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 22.69850 |
165 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
166 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.65314E-003 |
167 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
168 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
169 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.22711E-003 |
170 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 8.24577 |
171 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 37617.70918 |
172 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.29096E-004 |
173 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 1075.06217 |
174 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_5_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17350E-002 |
175 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.10106 |
176 | Fan:OnOff | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.10106 |
177 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 5.74730E-005 |
178 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 4.16975E-004 |
179 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 22.69931 |
180 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
181 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.51932E-003 |
182 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
183 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
184 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.16975E-004 |
185 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.10106 |
186 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 6569.51970 |
187 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.74730E-005 |
188 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 187.75109 |
189 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_6_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17278E-002 |
190 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.09209 |
191 | Fan:OnOff | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.09209 |
192 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 5.74158E-005 |
193 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 4.13586E-004 |
194 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 22.69931 |
195 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
196 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.51940E-003 |
197 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
198 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
199 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.13586E-004 |
200 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.09209 |
201 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 6562.97436 |
202 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.74158E-005 |
203 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 187.56409 |
204 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.36182 |
205 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.87156 |
206 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.99500 |
207 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.35501 |
208 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
209 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
210 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.37149E-004 |
211 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.42998E-004 |
212 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.35501 |
213 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
214 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
215 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 16345.58728 |
216 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.42998E-004 |
217 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 372.71510 |
218 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_1_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.54338E-002 |
219 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.34089 |
220 | Fan:OnOff | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.34089 |
221 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.79699E-005 |
222 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 1.29002E-004 |
223 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 22.69931 |
224 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
225 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.51643E-003 |
226 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
227 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
228 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.29002E-004 |
229 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.34089 |
230 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 2054.06943 |
231 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.79699E-005 |
232 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 58.69959 |
233 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_2_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.54319E-002 |
234 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.33809 |
235 | Fan:OnOff | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.33809 |
236 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.79627E-005 |
237 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 1.27947E-004 |
238 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 22.69931 |
239 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
240 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.51655E-003 |
241 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
242 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
243 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.27947E-004 |
244 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.33809 |
245 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 2053.24590 |
246 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.79627E-005 |
247 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 58.67607 |
248 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_3_MULT9_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 9.91540E-002 |
249 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.54205 |
250 | Fan:OnOff | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.54205 |
251 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 8.67454E-005 |
252 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 5.92251E-004 |
253 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 22.69886 |
254 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
255 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.57605E-003 |
256 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
257 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
258 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 5.92251E-004 |
259 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.54205 |
260 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 9915.52688 |
261 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.67454E-005 |
262 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 283.35529 |
263 | Fan:ZoneExhaust | BANQUET_FLR_6 EXHAUST FAN | User-Specified Maximum Flow Rate [m3/s] | 0.00000 |
264 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.64042 |
265 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.57133E-002 |
266 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.99500 |
267 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.62721 |
268 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.99500 |
269 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
270 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.98064E-003 |
271 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.66039E-004 |
272 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.62721 |
273 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
274 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
275 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 18979.28790 |
276 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.66039E-004 |
277 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 408.03613 |
278 | Fan:ZoneExhaust | DINING_FLR_6 EXHAUST FAN | User-Specified Maximum Flow Rate [m3/s] | 0.00000 |
279 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.76816 |
280 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.12963E-002 |
281 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.99500 |
282 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.75432 |
283 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.99500 |
284 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
285 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.17322E-003 |
286 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.72242E-004 |
287 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.75432 |
288 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
289 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
290 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 19688.33737 |
291 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.72242E-004 |
292 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 422.90257 |
293 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.63491 |
294 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.71645 |
295 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.99500 |
296 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.62174 |
297 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.99500 |
298 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
299 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.27531E-002 |
300 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.22394E-004 |
301 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.62174 |
302 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
303 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
304 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 13990.36248 |
305 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.22394E-004 |
306 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 294.26821 |
307 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.84425 |
308 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.37197 |
309 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.99500 |
310 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.84003 |
311 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.99500 |
312 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
313 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.02427E-003 |
314 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.82450E-005 |
315 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.84003 |
316 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
317 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
318 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 11230.01150 |
319 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.82450E-005 |
320 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 260.37439 |
321 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 25.02964 |
322 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 25.02964 |
323 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 25.15541 |
324 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 25.02964 |
325 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 25.03918 |
326 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 25.03918 |
327 | AirLoopHVAC | VAV WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
328 | AirLoopHVAC | VAV WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.99962 |
329 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.05132 |
330 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.05132 |
331 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.05132 |
332 | AirLoopHVAC | FLR_3_DOAS | Adjusted Heating Design Air Flow Rate [m3/s] | 2.05132 |
333 | AirLoopHVAC | FLR_3_DOAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.05132 |
334 | AirLoopHVAC | FLR_3_DOAS | Adjusted Main Design Air Flow Rate [m3/s] | 2.05132 |
335 | AirLoopHVAC | FLR_3_DOAS | User Heating Air Flow Ratio [] | 0.30000 |
336 | AirLoopHVAC | FLR_3_DOAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
337 | AirLoopHVAC | VAV WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 25.03918 |
338 | AirLoopHVAC | FLR_3_DOAS | Design Supply Air Flow Rate [m3/s] | 2.05132 |
339 | Controller:OutdoorAir | VAV WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 25.03918 |
340 | Controller:OutdoorAir | VAV WITH REHEAT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 25.03918 |
341 | HeatExchanger:AirToAir:SensibleAndLatent | VAV WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 25.03918 |
342 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 38.10000 |
343 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
344 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.69161 |
345 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 6.87148E-003 |
346 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 6.87148E-003 |
347 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 729331.55542 |
348 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.60500E-002 |
349 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 25.03918 |
350 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 172635.01367 |
351 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.51029E-003 |
352 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 2930.65757 |
353 | Fan:VariableVolume | VAV WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 25.03918 |
354 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.60500E-002 |
355 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.82798E-005 |
356 | Controller:WaterCoil | VAV WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.51029E-003 |
357 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.05132 |
358 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.05125 |
359 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 38.10000 |
360 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
361 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.79311 |
362 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 6.87148E-003 |
363 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 6.87148E-003 |
364 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Coil Load [W] | 57348.72296 |
365 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.04836E-003 |
366 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 2.05132 |
367 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size Rated Capacity [W] | 14143.00265 |
368 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.23729E-004 |
369 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 240.09207 |
370 | Fan:ConstantVolume | FLR_3_DOAS FAN | User-Specified Maximum Flow Rate [m3/s] | 2.05125 |
371 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.04836E-003 |
372 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 2.32474E-004 |
373 | Controller:WaterCoil | FLR_3_DOAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.23729E-004 |
374 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 3.68409E-002 |
375 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 7591.54435 |
376 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 4.24094E-003 |
377 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 0.50891 |
378 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 4.24094E-003 |
379 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 1277.18420 |
380 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
381 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 484765.23309 |
382 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 484765.23000 |
383 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 4.24094E-003 |
384 | PlantLoop | COOLSYS1 | Maximum Loop Flow Rate [m3/s] | 3.68409E-002 |
385 | PlantLoop | COOLSYS1 | Plant Loop Volume [m3] | 4.42091 |
386 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Flow Rate [m3/s] | 3.68409E-002 |
387 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Power Consumption [W] | 5255.88221 |
388 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 3.68409E-002 |
389 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 1031447.12728 |
390 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 1032120.29000 |
391 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 117.66171 |
392 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 3.75036E-004 |
393 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 4.50044E-002 |
394 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 3.75036E-004 |
395 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 47.90688 |
396 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 3.75036E-004 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | 13089.25 |
2 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 4793.45 |
3 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 2277.90 |
4 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | 3207.69 |
5 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | 1790.77 |
6 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 19769.87 |
7 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | 15148.05 |
8 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | 42544.82 |
9 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | 7091.58 |
10 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | 7084.54 |
11 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | 40643.29 |
12 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | 40531.28 |
13 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | 7078.37 |
14 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | 7071.32 |
15 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 16424.66 |
16 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | 2213.08 |
17 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | 2212.20 |
18 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | 10683.09 |
19 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | 19076.44 |
20 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | 19789.18 |
21 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | 14063.05 |
22 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 11283.70 |
23 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | 130015.88 |
24 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | 10651.46 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | 22320.18 | 16417.25 | 5902.93 | 0.74 | 3335.07 | 33.83 |
2 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | 22160.41 | 16299.61 | 5860.81 | 0.74 | 3311.16 | 33.58 |
3 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | 136156.72 | 100208.05 | 35948.67 | 0.74 | 20698.97 | 209.94 |
4 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | 149440.23 | 108787.81 | 40652.42 | 0.73 | 22036.97 | 223.51 |
5 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | 19553.29 | 14379.68 | 5173.61 | 0.74 | 2923.64 | 29.65 |
6 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | 19394.22 | 14262.62 | 5131.61 | 0.74 | 2899.83 | 29.41 |
7 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | 6049.56 | 4450.12 | 1599.44 | 0.74 | 904.05 | 9.17 |
8 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | 6000.01 | 4413.63 | 1586.38 | 0.74 | 896.64 | 9.09 |
9 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | 27624.78 | 20226.52 | 7398.26 | 0.73 | 4105.57 | 41.64 |
10 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | 664290.74 | 409499.04 | 254791.70 | 0.62 | 70658.82 | 716.66 |
11 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | 51198.70 | 32051.32 | 19147.38 | 0.63 | 5018.41 | 50.90 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | 3.72 | 12.68 |
Zone Name | # Surfaces | |
1 | BASEMENT | 14 |
2 | RETAIL_1_FLR_1 | 8 |
3 | RETAIL_2_FLR_1 | 8 |
4 | MECH_FLR_1 | 7 |
5 | STORAGE_FLR_1 | 8 |
6 | LAUNDRY_FLR_1 | 8 |
7 | CAFE_FLR_1 | 10 |
8 | LOBBY_FLR_1 | 22 |
9 | ROOM_1_FLR_3 | 9 |
10 | ROOM_2_FLR_3 | 9 |
11 | ROOM_3_MULT19_FLR_3 | 8 |
12 | ROOM_4_MULT19_FLR_3 | 8 |
13 | ROOM_5_FLR_3 | 9 |
14 | ROOM_6_FLR_3 | 9 |
15 | CORRIDOR_FLR_3 | 25 |
16 | ROOM_1_FLR_6 | 9 |
17 | ROOM_2_FLR_6 | 9 |
18 | ROOM_3_MULT9_FLR_6 | 8 |
19 | BANQUET_FLR_6 | 8 |
20 | DINING_FLR_6 | 8 |
21 | KITCHEN_FLR_6 | 12 |
22 | CORRIDOR_FLR_6 | 19 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.940 | 0.824 | 211.13 | 211.13 | 211.13 | 0.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.940 | 0.824 | 55.76 | 55.76 | 55.76 | 90.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.940 | 0.824 | 211.13 | 211.13 | 211.13 | 180.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_WEST_CFACTOR | 0.940 | 0.824 | 55.76 | 55.76 | 55.76 | 270.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | BASEMENT_FLOOR | 2.705 | 1.632 | 1978.83 | 1978.83 | 1978.83 | 0.00 | 180.00 | 86.56 | 22.86 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | BASEMENT_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | RETAIL_1_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | BASEMENT_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | BASEMENT_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | BASEMENT_CEILING_4 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_CEILING_5 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
11 | BASEMENT_CEILING_6 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | CAFE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
12 | BASEMENT_CEILING_7 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 0.00 | 32.99 | 32.99 | 0.00 | LOBBY_FLR_1_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
13 | BASEMENT_CEILING_8 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 219.63 | 219.63 | 219.63 | 90.00 | 0.00 | 14.82 | 14.82 | 0.00 | LOBBY_FLR_1_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
14 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 3957.66 | 3957.66 | 3957.66 | 0.00 | 90.00 | 3957.66 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
15 | RETAIL_1_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.969 | 0.846 | 22.63 | 45.89 | 22.63 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | Window | RETAIL_1_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.4711_SHGC_0.25 | N/A | 2.678 | No | 23.26 | 23.26 | 23.26 | 180.00 | 90.00 | 10.92 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
17 | RETAIL_1_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.969 | 0.846 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
18 | RETAIL_1_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | RETAIL_1_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | RETAIL_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 67.07 | 67.07 | 67.07 | 0.00 | 180.00 | 11.58 | 5.79 | 0.00 | BASEMENT_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | RETAIL_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 7.62E-002 | 0.92 | 4 | ||
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 134.14 | 134.14 | 134.14 | 0.00 | 90.00 | 134.14 | 1.00 | 0.00 | RETAIL_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
23 | RETAIL_2_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.969 | 0.846 | 24.62 | 26.57 | 24.62 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | Door | RETAIL_2_FLR_1_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
25 | RETAIL_2_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
26 | RETAIL_2_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | RETAIL_2_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 90.00 | 90.00 | 6.71 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | RETAIL_2_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 77.67 | 77.67 | 77.67 | 0.00 | 180.00 | 11.58 | 6.71 | 0.00 | BASEMENT_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
29 | RETAIL_2_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 155.34 | 155.34 | 155.34 | 0.00 | 90.00 | 155.34 | 1.00 | 0.00 | RETAIL_2_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
31 | MECH_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.969 | 0.846 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | MECH_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | MECH_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 180.00 | 90.00 | 15.85 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | MECH_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | MECH_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 164.24 | 164.24 | 164.24 | 0.00 | 180.00 | 15.85 | 10.36 | 0.00 | BASEMENT_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | MECH_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | MECH_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 328.49 | 328.49 | 328.49 | 0.00 | 90.00 | 328.49 | 1.00 | 0.00 | MECH_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | STORAGE_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.969 | 0.846 | 28.80 | 36.23 | 28.80 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | Door | STORAGE_FLR_1_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.198 | 1.198 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | STORAGE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
41 | STORAGE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 180.00 | 90.00 | 9.14 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
42 | STORAGE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | STORAGE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 94.76 | 94.76 | 94.76 | 0.00 | 180.00 | 9.14 | 10.36 | 0.00 | BASEMENT_CEILING_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
44 | STORAGE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | STORAGE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 189.52 | 189.52 | 189.52 | 0.00 | 90.00 | 189.52 | 1.00 | 0.00 | STORAGE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
46 | LAUNDRY_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.969 | 0.846 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | LAUNDRY_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.969 | 0.846 | 65.68 | 67.63 | 65.68 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | Door | LAUNDRY_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
49 | LAUNDRY_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 180.00 | 90.00 | 4.57 | 3.96 | 0.00 | CAFE_FLR_1_WALL_2_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | LAUNDRY_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 270.00 | 90.00 | 17.07 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
51 | LAUNDRY_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 78.04 | 78.04 | 78.04 | 0.00 | 180.00 | 4.57 | 17.07 | 0.00 | BASEMENT_CEILING_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
52 | LAUNDRY_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 156.08 | 156.08 | 156.08 | 0.00 | 90.00 | 156.08 | 1.00 | 0.00 | LAUNDRY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
54 | CAFE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.969 | 0.846 | 21.00 | 22.95 | 21.00 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CAFE_FLR_1_WALL_EAST_DOOR | Door | CAFE_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | CAFE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.969 | 0.846 | 63.73 | 129.23 | 63.73 | 180.00 | 90.00 | 32.61 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | Window | CAFE_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.4711_SHGC_0.25 | N/A | 2.678 | No | 65.50 | 65.50 | 65.50 | 180.00 | 90.00 | 30.75 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
58 | CAFE_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 0.00 | 90.00 | 28.04 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | CAFE_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | CAFE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | CAFE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 188.86 | 188.86 | 188.86 | 0.00 | 180.00 | 32.61 | 5.79 | 0.00 | BASEMENT_CEILING_6 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
62 | CAFE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 3.86E-002 | 0.96 | 4 | ||
63 | CAFE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 377.72 | 377.72 | 377.72 | 0.00 | 90.00 | 377.72 | 1.00 | 0.00 | CAFE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
64 | LOBBY_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.969 | 0.846 | 209.87 | 213.77 | 209.87 | 0.00 | 90.00 | 53.95 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
67 | LOBBY_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.969 | 0.846 | 12.08 | 12.08 | 12.08 | 0.00 | 90.00 | 3.05 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
68 | LOBBY_FLR_1_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.969 | 0.846 | 82.79 | 167.88 | 82.79 | 180.00 | 90.00 | 42.37 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | Window | LOBBY_FLR_1_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.4711_SHGC_0.25 | N/A | 2.678 | No | 85.08 | 85.08 | 85.08 | 180.00 | 90.00 | 39.95 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LOBBY_FLR_1_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.969 | 0.846 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | LOBBY_FLR_1_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | LOBBY_FLR_1_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 180.00 | 90.00 | 28.04 | 3.96 | 0.00 | CAFE_FLR_1_WALL_1_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | LOBBY_FLR_1_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | LOBBY_FLR_1_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | LOBBY_FLR_1_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | LOBBY_FLR_1_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | MECH_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | LOBBY_FLR_1_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
78 | LOBBY_FLR_1_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | LOBBY_FLR_1_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | CAFE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | LOBBY_FLR_1_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | LOBBY_FLR_1_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 180.00 | 32.99 | 32.99 | 0.00 | BASEMENT_CEILING_7 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
82 | LOBBY_FLR_1_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 219.63 | 219.63 | 219.63 | 90.00 | 180.00 | 14.82 | 14.82 | 0.00 | BASEMENT_CEILING_8 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
83 | LOBBY_FLR_1_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 1062.83 | 1062.83 | 1062.83 | 270.00 | 0.00 | 32.60 | 32.60 | 0.00 | LOBBY_FLR_1_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 10 | ||
84 | LOBBY_FLR_1_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 245.35 | 245.35 | 245.35 | 180.00 | 0.00 | 42.37 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.22E-003 | 1.00 | 4 | ||
85 | LOBBY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 2616.37 | 2616.37 | 2616.37 | 0.00 | 90.00 | 2616.37 | 1.00 | 0.00 | LOBBY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | ROOM_1_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.217 | 1.029 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.4711_SHGC_0.25 | N/A | 2.678 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | ROOM_1_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.217 | 1.029 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | Window | ROOM_1_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.4711_SHGC_0.25 | N/A | 2.678 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | ROOM_1_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | ROOM_1_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | ROOM_1_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
93 | ROOM_1_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
94 | ROOM_1_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
95 | ROOM_2_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.217 | 1.029 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.4711_SHGC_0.25 | N/A | 2.678 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
97 | ROOM_2_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.217 | 1.029 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | Window | ROOM_2_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.4711_SHGC_0.25 | N/A | 2.678 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | ROOM_2_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | ROOM_2_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | ROOM_2_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | ROOM_2_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | ROOM_2_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.217 | 1.029 | 7.47 | 11.15 | 7.47 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.4711_SHGC_0.25 | N/A | 2.678 | No | 3.68 | 3.68 | 3.68 | 180.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | ROOM_3_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 24.52 | 24.52 | 24.52 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
110 | ROOM_3_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 24.52 | 24.52 | 24.52 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.05 | 49.05 | 49.05 | 0.00 | 90.00 | 49.05 | 1.00 | 0.00 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.217 | 1.029 | 7.47 | 11.15 | 7.47 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_4_MULT19_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.4711_SHGC_0.25 | N/A | 2.678 | No | 3.68 | 3.68 | 3.68 | 0.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
117 | ROOM_4_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
118 | ROOM_4_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
120 | ROOM_5_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.217 | 1.029 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | Window | ROOM_5_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.4711_SHGC_0.25 | N/A | 2.678 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
122 | ROOM_5_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.217 | 1.029 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_5_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.4711_SHGC_0.25 | N/A | 2.678 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
124 | ROOM_5_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
125 | ROOM_5_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
126 | ROOM_5_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
127 | ROOM_5_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
128 | ROOM_5_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_5_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
129 | ROOM_6_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.217 | 1.029 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_6_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.4711_SHGC_0.25 | N/A | 2.678 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
131 | ROOM_6_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.217 | 1.029 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | Window | ROOM_6_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.4711_SHGC_0.25 | N/A | 2.678 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
133 | ROOM_6_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
134 | ROOM_6_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
135 | ROOM_6_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
136 | ROOM_6_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
137 | ROOM_6_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_6_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
138 | CORRIDOR_FLR_3_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.265 | 1.063 | 11.83 | 17.65 | 11.83 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.4711_SHGC_0.25 | N/A | 2.678 | No | 5.82 | 5.82 | 5.82 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.265 | 1.063 | 4.35 | 6.50 | 4.35 | 0.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.4711_SHGC_0.25 | N/A | 2.678 | No | 2.15 | 2.15 | 2.15 | 0.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.265 | 1.063 | 4.36 | 6.50 | 4.36 | 180.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.4711_SHGC_0.25 | N/A | 2.678 | No | 2.15 | 2.15 | 2.15 | 180.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.265 | 1.063 | 11.83 | 17.65 | 11.83 | 180.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.4711_SHGC_0.25 | N/A | 2.678 | No | 5.82 | 5.82 | 5.82 | 180.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 0.00 | 90.00 | 69.50 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | CORRIDOR_FLR_3_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | CORRIDOR_FLR_3_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORRIDOR_FLR_3_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | CORRIDOR_FLR_3_WALL_4_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 180.00 | 90.00 | 69.49 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
152 | CORRIDOR_FLR_3_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | CORRIDOR_FLR_3_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | CORRIDOR_FLR_3_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | CORRIDOR_FLR_3_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | CORRIDOR_FLR_3_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 74.32 | 74.32 | 74.32 | 180.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
157 | CORRIDOR_FLR_3_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 240.77 | 240.77 | 240.77 | 270.00 | 180.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | CORRIDOR_FLR_3_FLOOR_3 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 74.32 | 74.32 | 74.32 | 90.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
159 | CORRIDOR_FLR_3_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
160 | CORRIDOR_FLR_3_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 240.77 | 240.77 | 240.77 | 90.00 | 0.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
161 | CORRIDOR_FLR_3_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 778.81 | 778.81 | 778.81 | 0.00 | 90.00 | 778.81 | 1.00 | 0.00 | CORRIDOR_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
163 | ROOM_1_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.286 | 1.078 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.4711_SHGC_0.25 | N/A | 2.678 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
165 | ROOM_1_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.286 | 1.078 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | Window | ROOM_1_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.4711_SHGC_0.25 | N/A | 2.678 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
167 | ROOM_1_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
168 | ROOM_1_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
169 | ROOM_1_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | ROOM_1_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.283 | 0.269 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
171 | ROOM_1_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
172 | ROOM_2_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.286 | 1.078 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.4711_SHGC_0.25 | N/A | 2.678 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
174 | ROOM_2_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.286 | 1.078 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | Window | ROOM_2_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.4711_SHGC_0.25 | N/A | 2.678 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
176 | ROOM_2_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
177 | ROOM_2_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
178 | ROOM_2_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | ROOM_2_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.283 | 0.269 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
180 | ROOM_2_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.286 | 1.078 | 13.70 | 20.44 | 13.70 | 180.00 | 90.00 | 6.71 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.4711_SHGC_0.25 | N/A | 2.678 | No | 6.74 | 6.74 | 6.74 | 180.00 | 90.00 | 5.53 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 0.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 90.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | ROOM_3_MULT9_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 6.71 | 3.66 | 0.00 | ROOM_3_MULT9_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
187 | ROOM_3_MULT9_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.283 | 0.269 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 6.71 | 3.66 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
189 | BANQUET_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.335 | 1.112 | 65.36 | 97.55 | 65.36 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | Window | BANQUET_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.4711_SHGC_0.25 | N/A | 2.678 | No | 32.19 | 32.19 | 32.19 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
191 | BANQUET_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
192 | BANQUET_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
193 | BANQUET_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
194 | BANQUET_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | BANQUET_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
195 | BANQUET_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
196 | BANQUET_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | BANQUET_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
197 | DINING_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.335 | 1.112 | 65.36 | 97.55 | 65.36 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DINING_FLR_6_WALL_NORTH_WINDOW | Window | DINING_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.4711_SHGC_0.25 | N/A | 2.678 | No | 32.19 | 32.19 | 32.19 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
199 | DINING_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
200 | DINING_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | DINING_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DINING_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DINING_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | DINING_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
203 | DINING_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
204 | DINING_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | DINING_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
205 | KITCHEN_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.335 | 1.112 | 16.77 | 21.37 | 16.77 | 0.00 | 90.00 | 7.01 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | Window | KITCHEN_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.4711_SHGC_0.25 | N/A | 2.678 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
207 | KITCHEN_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.335 | 1.112 | 34.86 | 52.03 | 34.86 | 90.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | Window | KITCHEN_FLR_6_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.4711_SHGC_0.25 | N/A | 2.678 | No | 17.17 | 17.17 | 17.17 | 90.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.335 | 1.112 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | Window | KITCHEN_FLR_6_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.4711_SHGC_0.25 | N/A | 2.678 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 7.43 | 7.43 | 7.43 | 180.00 | 90.00 | 2.44 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
212 | KITCHEN_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | KITCHEN_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | KITCHEN_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 103.30 | 103.30 | 103.30 | 180.00 | 180.00 | 10.16 | 10.16 | 0.00 | KITCHEN_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
215 | KITCHEN_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 103.30 | 103.30 | 103.30 | 270.00 | 0.00 | 10.16 | 10.16 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
216 | KITCHEN_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 206.61 | 206.61 | 206.61 | 0.00 | 90.00 | 206.61 | 1.00 | 0.00 | KITCHEN_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
217 | CORRIDOR_FLR_6_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.335 | 1.112 | 11.83 | 17.65 | 11.83 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.4711_SHGC_0.25 | N/A | 2.678 | No | 5.82 | 5.82 | 5.82 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.335 | 1.112 | 10.58 | 15.79 | 10.58 | 0.00 | 90.00 | 5.18 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.4711_SHGC_0.25 | N/A | 2.678 | No | 5.21 | 5.21 | 5.21 | 0.00 | 90.00 | 4.27 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.335 | 1.112 | 34.86 | 52.03 | 34.86 | 180.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.4711_SHGC_0.25 | N/A | 2.678 | No | 17.17 | 17.17 | 17.17 | 180.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
224 | CORRIDOR_FLR_6_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 104.98 | 104.98 | 104.98 | 0.00 | 90.00 | 34.44 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 183.95 | 183.95 | 183.95 | 180.00 | 90.00 | 60.35 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
226 | CORRIDOR_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
227 | CORRIDOR_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 40.88 | 40.88 | 40.88 | 270.00 | 90.00 | 13.41 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
228 | CORRIDOR_FLR_6_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
229 | CORRIDOR_FLR_6_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
230 | CORRIDOR_FLR_6_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
231 | CORRIDOR_FLR_6_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
232 | CORRIDOR_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 412.12 | 412.12 | 412.12 | 180.00 | 180.00 | 20.30 | 20.30 | 0.00 | CORRIDOR_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 12 | ||
233 | CORRIDOR_FLR_6_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 244.71 | 244.71 | 244.71 | 90.00 | 0.00 | 15.64 | 15.64 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 8 | ||
234 | CORRIDOR_FLR_6_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 167.42 | 167.42 | 167.42 | 270.00 | 0.00 | 12.94 | 12.94 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 824.25 | 824.25 | 824.25 | 0.00 | 90.00 | 824.25 | 1.00 | 0.00 | CORRIDOR_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 7.1627346445E-003 | 1.4449468564E-002 | Pass | Pass | 1.1619650630E-002 | 2.9112068282E-002 | Pass | Pass |
2 | RETAIL_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 2.4736730873E-002 | 4.8690502093E-002 | Pass | Pass | 5.6460169280E-002 | 6.9303574537E-002 | Pass | Pass |
3 | RETAIL_2_FLR_1 | RunPeriod: RUNPERIOD 1 | 2.3940668790E-003 | 4.9803937829E-003 | Pass | Pass | 1.6977095553E-002 | 3.2129661096E-002 | Pass | Pass |
4 | MECH_FLR_1 | RunPeriod: RUNPERIOD 1 | 1.0242988365E-003 | 6.9923606014E-004 | Pass | Pass | 3.2855212718E-002 | 5.5999379557E-002 | Pass | Pass |
5 | STORAGE_FLR_1 | RunPeriod: RUNPERIOD 1 | 8.7282243137E-004 | 6.3516588787E-004 | Pass | Pass | 7.4340884512E-002 | 0.1154057318 | Pass | Pass |
6 | LAUNDRY_FLR_1 | RunPeriod: RUNPERIOD 1 | 4.4190340268E-002 | 0.1389775826 | Pass | Pass | 1.8935268876E-002 | 5.4653405611E-002 | Pass | Pass |
7 | CAFE_FLR_1 | RunPeriod: RUNPERIOD 1 | 3.0136387400E-002 | 5.8388724095E-002 | Pass | Pass | 2.0754208596E-002 | 3.8747776313E-002 | Pass | Pass |
8 | LOBBY_FLR_1 | RunPeriod: RUNPERIOD 1 | 8.1335662886E-003 | 1.8033214554E-002 | Pass | Pass | 1.6696811263E-002 | 3.3467330392E-002 | Pass | Pass |
9 | ROOM_1_FLR_3 | RunPeriod: RUNPERIOD 1 | 5.3661216840E-002 | 0.2000201130 | Pass | Pass | 0.4819856793 | 3.6146147120 | Pass | Pass |
10 | ROOM_2_FLR_3 | RunPeriod: RUNPERIOD 1 | 5.1082002829E-002 | 0.1761398477 | Pass | Pass | 0.1696866177 | 0.4203025781 | Pass | Pass |
11 | ROOM_3_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 1.3850449947E-002 | 3.2132994685E-002 | Pass | Pass | 3.3312175590E-002 | 5.3066114426E-002 | Pass | Pass |
12 | ROOM_4_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 2.4810449373E-002 | 9.2982555616E-002 | Pass | Pass | 8.9444127489E-002 | 0.1953989576 | Pass | Pass |
13 | ROOM_5_FLR_3 | RunPeriod: RUNPERIOD 1 | 4.9184547321E-002 | 0.1764802445 | Pass | Pass | 0.1418091318 | 0.4616331697 | Pass | Pass |
14 | ROOM_6_FLR_3 | RunPeriod: RUNPERIOD 1 | 3.0523022621E-002 | 9.9645059761E-002 | Pass | Pass | 0.1186581741 | 0.2550942098 | Pass | Pass |
15 | CORRIDOR_FLR_3 | RunPeriod: RUNPERIOD 1 | 5.4838967491E-004 | 4.0578428985E-004 | Pass | Pass | 2.5094880089E-002 | 3.7709929420E-002 | Pass | Pass |
16 | ROOM_1_FLR_6 | RunPeriod: RUNPERIOD 1 | 5.9019358353E-002 | 0.2099447949 | Pass | Pass | 0.1974961534 | 0.4970917513 | Pass | Pass |
17 | ROOM_2_FLR_6 | RunPeriod: RUNPERIOD 1 | 6.3257041607E-002 | 0.2023234723 | Pass | Pass | 0.1913413924 | 0.4921483791 | Pass | Pass |
18 | ROOM_3_MULT9_FLR_6 | RunPeriod: RUNPERIOD 1 | 7.0715954293E-002 | 0.2852772487 | Pass | Pass | 0.1895965153 | 0.5345775664 | Pass | Pass |
19 | BANQUET_FLR_6 | RunPeriod: RUNPERIOD 1 | 2.2303176771E-002 | 6.5571281807E-002 | Pass | Pass | 1.2582857422E-002 | 3.5054548427E-002 | Pass | Pass |
20 | DINING_FLR_6 | RunPeriod: RUNPERIOD 1 | 2.5636486836E-002 | 6.6436541233E-002 | Pass | Pass | 1.1524388879E-002 | 3.0304693184E-002 | Pass | Pass |
21 | KITCHEN_FLR_6 | RunPeriod: RUNPERIOD 1 | 6.7022397065E-002 | 0.1170573512 | Pass | Pass | 1.7664089631E-002 | 3.2757295799E-002 | Pass | Pass |
22 | CORRIDOR_FLR_6 | RunPeriod: RUNPERIOD 1 | 1.3351042201E-003 | 9.1295304683E-004 | Pass | Pass | 0.1709104280 | 0.4643691168 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:58:10
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 3180.47 | 66.95 | 382.79 | 3828.73 | 9975.92 | 17434.87 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:58:10
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | -5.20 | 0.00 | -5.20 | Wetbulb [C] | 2.20 | 20.00 |
EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 38.10 | 13.00 | 18.10 | Wetbulb [C] | 3.90 | 280.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 3.00 | 6 | |||
Feb | 3.00 | 4 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 18.00 | 7 | |||
Jul | 27.00 | 16 | |||
Aug | 41.00 | 15 | |||
Sep | 0.00 | 0 | |||
Oct | 23.00 | 18 | |||
Nov | 0.00 | 0 | |||
Dec | 7.00 | 7 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:58:10
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.845 | 0.940 | 211.13 | 211.13 | 0.00 | 90.00 | N |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.845 | 0.940 | 55.76 | 55.76 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.845 | 0.940 | 211.13 | 211.13 | 180.00 | 90.00 | S |
BASEMENT_WALL_WEST | BASEMENT_WALL_WEST_CFACTOR | 1.00 | 0.845 | 0.940 | 55.76 | 55.76 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.846 | 0.969 | 45.89 | 22.63 | 180.00 | 90.00 | S |
RETAIL_1_FLR_1_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.846 | 0.969 | 22.95 | 22.95 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_CEILING | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 67.07 | 67.07 | 180.00 | 0.00 | |
RETAIL_2_FLR_1_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.846 | 0.969 | 26.57 | 24.62 | 270.00 | 90.00 | W |
MECH_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.846 | 0.969 | 62.80 | 62.80 | 0.00 | 90.00 | N |
STORAGE_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.846 | 0.969 | 36.23 | 28.80 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.846 | 0.969 | 18.12 | 18.12 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.846 | 0.969 | 67.63 | 65.68 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.846 | 0.969 | 22.95 | 21.00 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.846 | 0.969 | 129.23 | 63.73 | 180.00 | 90.00 | S |
CAFE_FLR_1_CEILING | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 188.86 | 188.86 | 180.00 | 0.00 | |
LOBBY_FLR_1_WALL_1_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.846 | 0.969 | 213.77 | 209.87 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_2_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.846 | 0.969 | 12.08 | 12.08 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.846 | 0.969 | 167.88 | 82.79 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_1_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.846 | 0.969 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_CEILING_2 | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 245.35 | 245.35 | 180.00 | 0.00 | |
ROOM_1_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 1.029 | 1.217 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_1_FLR_3_WALL_WEST | RES_EXT_WALL_MID | 0.30 | 1.029 | 1.217 | 104.06 | 69.72 | 270.00 | 90.00 | W |
ROOM_2_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 1.029 | 1.217 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_2_FLR_3_WALL_WEST | RES_EXT_WALL_MID | 0.30 | 1.029 | 1.217 | 104.05 | 69.71 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 1.029 | 1.217 | 847.14 | 567.58 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 1.029 | 1.217 | 847.37 | 567.71 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_EAST | RES_EXT_WALL_MID | 0.30 | 1.029 | 1.217 | 104.06 | 69.72 | 90.00 | 90.00 | E |
ROOM_5_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 1.029 | 1.217 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 1.029 | 1.217 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_6_FLR_3_WALL_EAST | RES_EXT_WALL_MID | 0.30 | 1.029 | 1.217 | 104.05 | 69.71 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_1_NORTH | NONRES_EXT_WALL_MID | 0.30 | 1.063 | 1.265 | 70.60 | 47.31 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_2_NORTH | NONRES_EXT_WALL_MID | 0.30 | 1.063 | 1.265 | 26.01 | 17.42 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 1.063 | 1.265 | 26.02 | 17.43 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_2_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 1.063 | 1.265 | 70.60 | 47.31 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_SOUTH | RES_EXT_WALL_TOP | 0.30 | 1.078 | 1.286 | 13.94 | 9.34 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_WEST | RES_EXT_WALL_TOP | 0.30 | 1.078 | 1.286 | 26.01 | 17.43 | 270.00 | 90.00 | W |
ROOM_1_FLR_6_CEILING | RES_ROOF | 0.55 | 0.273 | 0.283 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_2_FLR_6_WALL_NORTH | RES_EXT_WALL_TOP | 0.30 | 1.078 | 1.286 | 13.94 | 9.34 | 0.00 | 90.00 | N |
ROOM_2_FLR_6_WALL_WEST | RES_EXT_WALL_TOP | 0.30 | 1.078 | 1.286 | 26.01 | 17.43 | 270.00 | 90.00 | W |
ROOM_2_FLR_6_CEILING | RES_ROOF | 0.55 | 0.273 | 0.283 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | RES_EXT_WALL_TOP | 0.30 | 1.078 | 1.286 | 183.96 | 123.26 | 180.00 | 90.00 | S |
ROOM_3_MULT9_FLR_6_CEILING | RES_ROOF | 0.55 | 0.273 | 0.283 | 220.77 | 220.77 | 180.00 | 0.00 | |
BANQUET_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.112 | 1.335 | 97.55 | 65.36 | 0.00 | 90.00 | N |
BANQUET_FLR_6_CEILING | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 331.66 | 331.66 | 180.00 | 0.00 | |
DINING_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.112 | 1.335 | 97.55 | 65.36 | 0.00 | 90.00 | N |
DINING_FLR_6_CEILING | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 331.66 | 331.66 | 180.00 | 0.00 | |
KITCHEN_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.112 | 1.335 | 21.37 | 16.77 | 0.00 | 90.00 | N |
KITCHEN_FLR_6_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.112 | 1.335 | 52.03 | 34.86 | 90.00 | 90.00 | E |
KITCHEN_FLR_6_WALL_1_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.112 | 1.335 | 13.94 | 9.34 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_CEILING | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 103.30 | 103.30 | 270.00 | 0.00 | |
CORRIDOR_FLR_6_WALL_1_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.112 | 1.335 | 17.65 | 11.83 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.112 | 1.335 | 15.79 | 10.58 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.112 | 1.335 | 52.03 | 34.86 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_CEILING_1 | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 244.71 | 244.71 | 90.00 | 0.00 | |
CORRIDOR_FLR_6_CEILING_2 | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 167.42 | 167.42 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_FLOOR | BASEMENT_FLOOR | 0.30 | 1.441 | 2.705 | 1978.83 | 1978.83 | 0.00 | 180.00 | |
BASEMENT_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.186 | 0.196 | 67.07 | 67.07 | 180.00 | 0.00 | |
BASEMENT_CEILING_2 | NONRES_FLOOR_CEILING | 0.30 | 0.186 | 0.196 | 77.67 | 77.67 | 180.00 | 0.00 | |
BASEMENT_CEILING_3 | NONRES_FLOOR_CEILING | 0.30 | 0.186 | 0.196 | 164.24 | 164.24 | 180.00 | 0.00 | |
BASEMENT_CEILING_4 | NONRES_FLOOR_CEILING | 0.30 | 0.186 | 0.196 | 94.76 | 94.76 | 180.00 | 0.00 | |
BASEMENT_CEILING_5 | NONRES_FLOOR_CEILING | 0.30 | 0.186 | 0.196 | 78.04 | 78.04 | 180.00 | 0.00 | |
BASEMENT_CEILING_6 | NONRES_FLOOR_CEILING | 0.30 | 0.186 | 0.196 | 188.86 | 188.86 | 180.00 | 0.00 | |
BASEMENT_CEILING_7 | NONRES_FLOOR_CEILING | 0.30 | 0.186 | 0.196 | 1088.56 | 1088.56 | 180.00 | 0.00 | |
BASEMENT_CEILING_8 | NONRES_FLOOR_CEILING | 0.30 | 0.186 | 0.196 | 219.63 | 219.63 | 90.00 | 0.00 | |
RETAIL_1_FLR_1_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 0.00 | 90.00 | N |
RETAIL_1_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 90.00 | 90.00 | E |
RETAIL_1_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.186 | 0.196 | 67.07 | 67.07 | 0.00 | 180.00 | |
RETAIL_2_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 180.00 | 90.00 | S |
RETAIL_2_FLR_1_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 0.00 | 90.00 | N |
RETAIL_2_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.57 | 26.57 | 90.00 | 90.00 | E |
RETAIL_2_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.186 | 0.196 | 77.67 | 77.67 | 0.00 | 180.00 | |
RETAIL_2_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 77.67 | 77.67 | 180.00 | 0.00 | |
MECH_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
MECH_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 62.80 | 62.80 | 180.00 | 90.00 | S |
MECH_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
MECH_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.186 | 0.196 | 164.24 | 164.24 | 0.00 | 180.00 | |
MECH_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 164.24 | 164.24 | 180.00 | 0.00 | |
STORAGE_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
STORAGE_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 36.23 | 36.23 | 180.00 | 90.00 | S |
STORAGE_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
STORAGE_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.186 | 0.196 | 94.76 | 94.76 | 0.00 | 180.00 | |
STORAGE_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 94.76 | 94.76 | 180.00 | 0.00 | |
LAUNDRY_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 18.12 | 18.12 | 180.00 | 90.00 | S |
LAUNDRY_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 67.63 | 67.63 | 270.00 | 90.00 | W |
LAUNDRY_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.186 | 0.196 | 78.04 | 78.04 | 0.00 | 180.00 | |
LAUNDRY_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 78.04 | 78.04 | 180.00 | 0.00 | |
CAFE_FLR_1_WALL_1_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.11 | 111.11 | 0.00 | 90.00 | N |
CAFE_FLR_1_WALL_2_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 18.12 | 18.12 | 0.00 | 90.00 | N |
CAFE_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 270.00 | 90.00 | W |
CAFE_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.186 | 0.196 | 188.86 | 188.86 | 0.00 | 180.00 | |
LOBBY_FLR_1_WALL_2_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_3_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.11 | 111.11 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.57 | 26.57 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_4_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 62.80 | 62.80 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_4_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 36.23 | 36.23 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
LOBBY_FLR_1_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 90.00 | 90.00 | E |
LOBBY_FLR_1_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 67.63 | 67.63 | 90.00 | 90.00 | E |
LOBBY_FLR_1_FLOOR_1 | NONRES_FLOOR | 0.30 | 0.186 | 0.196 | 1088.56 | 1088.56 | 180.00 | 180.00 | |
LOBBY_FLR_1_FLOOR_2 | NONRES_FLOOR | 0.30 | 0.186 | 0.196 | 219.63 | 219.63 | 90.00 | 180.00 | |
LOBBY_FLR_1_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 1062.83 | 1062.83 | 270.00 | 0.00 | |
ROOM_1_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 0.00 | 90.00 | N |
ROOM_1_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 90.00 | 90.00 | E |
ROOM_1_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 156.09 | 156.09 | 0.00 | 180.00 | |
ROOM_1_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 156.09 | 156.09 | 180.00 | 0.00 | |
ROOM_2_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 90.00 | 90.00 | E |
ROOM_2_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 180.00 | 90.00 | S |
ROOM_2_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 156.07 | 156.07 | 0.00 | 180.00 | |
ROOM_2_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 156.07 | 156.07 | 180.00 | 0.00 | |
ROOM_3_MULT19_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.14 | 847.14 | 0.00 | 90.00 | N |
ROOM_3_MULT19_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 90.00 | 90.00 | E |
ROOM_3_MULT19_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 1863.81 | 1863.81 | 0.00 | 180.00 | |
ROOM_3_MULT19_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 1863.81 | 1863.81 | 180.00 | 0.00 | |
ROOM_4_MULT19_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 90.00 | 90.00 | E |
ROOM_4_MULT19_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.37 | 847.37 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 270.00 | 90.00 | W |
ROOM_4_MULT19_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 1864.32 | 1864.32 | 0.00 | 180.00 | |
ROOM_4_MULT19_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 1864.32 | 1864.32 | 180.00 | 0.00 | |
ROOM_5_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 270.00 | 90.00 | W |
ROOM_5_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 156.09 | 156.09 | 0.00 | 180.00 | |
ROOM_5_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 156.09 | 156.09 | 180.00 | 0.00 | |
ROOM_6_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 270.00 | 90.00 | W |
ROOM_6_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 156.07 | 156.07 | 0.00 | 180.00 | |
ROOM_6_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 156.07 | 156.07 | 180.00 | 0.00 | |
CORRIDOR_FLR_3_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.28 | 847.28 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_4_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_3_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.27 | 847.27 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_4_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_FLOOR_1 | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 297.29 | 297.29 | 180.00 | 180.00 | |
CORRIDOR_FLR_3_FLOOR_2 | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 963.06 | 963.06 | 270.00 | 180.00 | |
CORRIDOR_FLR_3_FLOOR_3 | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 297.26 | 297.26 | 90.00 | 180.00 | |
CORRIDOR_FLR_3_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 297.29 | 297.29 | 90.00 | 0.00 | |
CORRIDOR_FLR_3_CEILING_2 | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 963.06 | 963.06 | 90.00 | 0.00 | |
CORRIDOR_FLR_3_CEILING_3 | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 297.26 | 297.26 | 90.00 | 0.00 | |
ROOM_1_FLR_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 13.94 | 13.94 | 0.00 | 90.00 | N |
ROOM_1_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.01 | 26.01 | 90.00 | 90.00 | E |
ROOM_1_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 39.02 | 39.02 | 0.00 | 180.00 | |
ROOM_2_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.01 | 26.01 | 90.00 | 90.00 | E |
ROOM_2_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 13.94 | 13.94 | 180.00 | 90.00 | S |
ROOM_2_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 39.02 | 39.02 | 0.00 | 180.00 | |
ROOM_3_MULT9_FLR_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 183.96 | 183.96 | 0.00 | 90.00 | N |
ROOM_3_MULT9_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 100.35 | 100.35 | 90.00 | 90.00 | E |
ROOM_3_MULT9_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 100.35 | 100.35 | 270.00 | 90.00 | W |
ROOM_3_MULT9_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 220.77 | 220.77 | 0.00 | 180.00 | |
BANQUET_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
BANQUET_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 180.00 | 90.00 | S |
BANQUET_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
BANQUET_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 331.66 | 331.66 | 0.00 | 180.00 | |
DINING_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
DINING_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 180.00 | 90.00 | S |
DINING_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
DINING_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 331.66 | 331.66 | 0.00 | 180.00 | |
KITCHEN_FLR_6_WALL_2_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 7.43 | 7.43 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 20.44 | 20.44 | 270.00 | 90.00 | W |
KITCHEN_FLR_6_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
KITCHEN_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 103.30 | 103.30 | 180.00 | 180.00 | |
CORRIDOR_FLR_6_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_4_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 104.98 | 104.98 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_1_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 183.95 | 183.95 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 11.15 | 11.15 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 40.88 | 40.88 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 20.44 | 20.44 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 412.12 | 412.12 | 180.00 | 180.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3957.66 | 0.00 | 90.00 | N | ||
RETAIL_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 134.14 | 0.00 | 90.00 | N | ||
RETAIL_2_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 155.34 | 0.00 | 90.00 | N | ||
MECH_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 328.49 | 0.00 | 90.00 | N | ||
STORAGE_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 189.52 | 0.00 | 90.00 | N | ||
LAUNDRY_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 156.08 | 0.00 | 90.00 | N | ||
CAFE_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 377.72 | 0.00 | 90.00 | N | ||
LOBBY_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 2616.37 | 0.00 | 90.00 | N | ||
ROOM_1_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.18 | 0.00 | 90.00 | N | ||
ROOM_2_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.14 | 0.00 | 90.00 | N | ||
ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3727.63 | 0.00 | 90.00 | N | ||
ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3728.64 | 0.00 | 90.00 | N | ||
ROOM_5_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.18 | 0.00 | 90.00 | N | ||
ROOM_6_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.14 | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3115.24 | 0.00 | 90.00 | N | ||
ROOM_1_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 78.04 | 0.00 | 90.00 | N | ||
ROOM_2_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 78.03 | 0.00 | 90.00 | N | ||
ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 441.55 | 0.00 | 90.00 | N | ||
BANQUET_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 663.31 | 0.00 | 90.00 | N | ||
DINING_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 663.31 | 0.00 | 90.00 | N | ||
KITCHEN_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 206.61 | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 824.25 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.4711_SHGC_0.25 | 23.26 | 0.00 | 0.00 | 23.26 | 23.26 | 2.678 | 0.251 | 0.251 | No | RETAIL_1_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
CAFE_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.4711_SHGC_0.25 | 65.50 | 0.00 | 0.00 | 65.50 | 65.50 | 2.678 | 0.251 | 0.251 | No | CAFE_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
LOBBY_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.4711_SHGC_0.25 | 85.08 | 0.00 | 0.00 | 85.08 | 85.08 | 2.678 | 0.251 | 0.251 | No | LOBBY_FLR_1_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.4711_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.678 | 0.251 | 0.251 | No | ROOM_1_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.4711_SHGC_0.25 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.678 | 0.251 | 0.251 | No | ROOM_1_FLR_3_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_2_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.4711_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.678 | 0.251 | 0.251 | No | ROOM_2_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_2_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.4711_SHGC_0.25 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.678 | 0.251 | 0.251 | No | ROOM_2_FLR_3_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.4711_SHGC_0.25 | 3.68 | 0.00 | 0.00 | 3.68 | 279.56 | 2.678 | 0.251 | 0.251 | No | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.4711_SHGC_0.25 | 3.68 | 0.00 | 0.00 | 3.68 | 279.65 | 2.678 | 0.251 | 0.251 | No | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_5_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.4711_SHGC_0.25 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.678 | 0.251 | 0.251 | No | ROOM_5_FLR_3_WALL_EAST | 90.00 | 90.00 | E | |||||||
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.4711_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.678 | 0.251 | 0.251 | No | ROOM_5_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_6_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.4711_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.678 | 0.251 | 0.251 | No | ROOM_6_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_6_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.4711_SHGC_0.25 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.678 | 0.251 | 0.251 | No | ROOM_6_FLR_3_WALL_EAST | 90.00 | 90.00 | E | |||||||
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.4711_SHGC_0.25 | 5.82 | 0.00 | 0.00 | 5.82 | 23.30 | 2.678 | 0.251 | 0.251 | No | CORRIDOR_FLR_3_WALL_1_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.4711_SHGC_0.25 | 2.15 | 0.00 | 0.00 | 2.15 | 8.59 | 2.678 | 0.251 | 0.251 | No | CORRIDOR_FLR_3_WALL_2_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.4711_SHGC_0.25 | 2.15 | 0.00 | 0.00 | 2.15 | 8.58 | 2.678 | 0.251 | 0.251 | No | CORRIDOR_FLR_3_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.4711_SHGC_0.25 | 5.82 | 0.00 | 0.00 | 5.82 | 23.30 | 2.678 | 0.251 | 0.251 | No | CORRIDOR_FLR_3_WALL_2_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.4711_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.678 | 0.251 | 0.251 | No | ROOM_1_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.4711_SHGC_0.25 | 8.58 | 0.00 | 0.00 | 8.58 | 8.58 | 2.678 | 0.251 | 0.251 | No | ROOM_1_FLR_6_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_2_FLR_6_WALL_NORTH_WINDOW | RESWINDOW_U_0.4711_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.678 | 0.251 | 0.251 | No | ROOM_2_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_2_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.4711_SHGC_0.25 | 8.58 | 0.00 | 0.00 | 8.58 | 8.58 | 2.678 | 0.251 | 0.251 | No | ROOM_2_FLR_6_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.4711_SHGC_0.25 | 6.74 | 0.00 | 0.00 | 6.74 | 60.70 | 2.678 | 0.251 | 0.251 | No | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
BANQUET_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.4711_SHGC_0.25 | 32.19 | 0.00 | 0.00 | 32.19 | 32.19 | 2.678 | 0.251 | 0.251 | No | BANQUET_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
DINING_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.4711_SHGC_0.25 | 32.19 | 0.00 | 0.00 | 32.19 | 32.19 | 2.678 | 0.251 | 0.251 | No | DINING_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
KITCHEN_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.4711_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.678 | 0.251 | 0.251 | No | KITCHEN_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
KITCHEN_FLR_6_WALL_EAST_WINDOW | NONRESWINDOW_U_0.4711_SHGC_0.25 | 17.17 | 0.00 | 0.00 | 17.17 | 17.17 | 2.678 | 0.251 | 0.251 | No | KITCHEN_FLR_6_WALL_EAST | 90.00 | 90.00 | E | |||||||
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.4711_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.678 | 0.251 | 0.251 | No | KITCHEN_FLR_6_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.4711_SHGC_0.25 | 5.82 | 0.00 | 0.00 | 5.82 | 5.82 | 2.678 | 0.251 | 0.251 | No | CORRIDOR_FLR_6_WALL_1_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.4711_SHGC_0.25 | 5.21 | 0.00 | 0.00 | 5.21 | 5.21 | 2.678 | 0.251 | 0.251 | No | CORRIDOR_FLR_6_WALL_2_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.4711_SHGC_0.25 | 17.17 | 0.00 | 0.00 | 17.17 | 17.17 | 2.678 | 0.251 | 0.251 | No | CORRIDOR_FLR_6_WALL_2_SOUTH | 180.00 | 90.00 | S | |||||||
Total or Average | 1213.79 | 2.678 | 0.251 | 0.251 | |||||||||||||||||
North Total or Average | 432.95 | 2.678 | 0.251 | 0.251 | |||||||||||||||||
Non-North Total or Average | 780.84 | 2.678 | 0.251 | 0.251 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
RETAIL_2_FLR_1_WALL_WEST_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | RETAIL_2_FLR_1_WALL_WEST |
STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | OVERHEAD DOOR_CON | 1.016 | 1.198 | 7.43 | STORAGE_FLR_1_WALL_NORTH |
LAUNDRY_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | LAUNDRY_FLR_1_WALL_EAST |
CAFE_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | CAFE_FLR_1_WALL_EAST |
LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:58:10
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CAFE_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LOBBY_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
BANQUET_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:58:10
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 8.7495 | 1978.83 | 17313.73 | LightsWired | LTG_SCH_BASEMENT | 50.91 | 168.00 | 50.86 | 0.0000 | Y | 165.29 |
RETAIL_1_FLR_1_LIGHTS | RETAIL_1_FLR_1 | RETAIL_1_FLR_1 | GENERAL | 13.0124 | 67.07 | 872.76 | LightsWired | LTG_SCH_RETAIL | 51.36 | 168.00 | 51.30 | 0.0000 | Y | 8.40 |
RETAIL_2_FLR_1_LIGHTS | RETAIL_2_FLR_1 | RETAIL_2_FLR_1 | GENERAL | 13.0124 | 77.67 | 1010.66 | LightsWired | LTG_SCH_RETAIL | 51.36 | 168.00 | 51.30 | 0.0000 | Y | 9.73 |
MECH_FLR_1_LIGHTS | MECH_FLR_1 | MECH_FLR_1 | GENERAL | 10.0642 | 164.24 | 1652.98 | LightsWired | LTG_SCH_MECHANIC | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 18.19 |
STORAGE_FLR_1_LIGHTS | STORAGE_FLR_1 | STORAGE_FLR_1 | GENERAL | 7.3195 | 94.76 | 693.59 | LightsWired | LTG_SCH_STORAGE | 25.68 | 168.00 | 25.65 | 0.0000 | Y | 3.34 |
LAUNDRY_FLR_1_LIGHTS | LAUNDRY_FLR_1 | LAUNDRY_FLR_1 | GENERAL | 5.4896 | 78.04 | 428.40 | LightsWired | LTG_SCH_LAUNDRY | 51.36 | 168.00 | 51.30 | 0.0000 | Y | 4.13 |
CAFE_FLR_1_LIGHTS | CAFE_FLR_1 | CAFE_FLR_1 | GENERAL | 12.8090 | 188.86 | 2419.14 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 26.62 |
LOBBY_FLR_1_LIGHTS | LOBBY_FLR_1 | LOBBY_FLR_1 | GENERAL | 10.0642 | 1308.19 | 13165.91 | LightsWired | LTG_SCH_LOBBY | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 144.89 |
ROOM_1_FLR_3_LIGHTS | ROOM_1_FLR_3 | ROOM_1_FLR_3 | GENERAL | 10.0642 | 156.09 | 1570.91 | LightsWired | LTG_SCH_GUESTROOM | 69.03 | 168.00 | 69.21 | 0.0000 | Y | 20.41 |
ROOM_2_FLR_3_LIGHTS | ROOM_2_FLR_3 | ROOM_2_FLR_3 | GENERAL | 10.0642 | 156.07 | 1570.72 | LightsWired | LTG_SCH_GUESTROOM | 69.03 | 168.00 | 69.21 | 0.0000 | Y | 20.41 |
ROOM_3_MULT19_FLR_3_LIGHTS | ROOM_3_MULT19_FLR_3 | ROOM_3_MULT19_FLR_3 | GENERAL | 10.0642 | 1863.81 | 18757.86 | LightsWired | LTG_SCH_GUESTROOM | 69.03 | 168.00 | 69.21 | 0.0000 | Y | 243.70 |
ROOM_4_MULT19_FLR_3_LIGHTS | ROOM_4_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | GENERAL | 10.0642 | 1864.32 | 18762.99 | LightsWired | LTG_SCH_GUESTROOM | 69.03 | 168.00 | 69.21 | 0.0000 | Y | 243.77 |
ROOM_5_FLR_3_LIGHTS | ROOM_5_FLR_3 | ROOM_5_FLR_3 | GENERAL | 10.0642 | 156.09 | 1570.91 | LightsWired | LTG_SCH_GUESTROOM | 69.03 | 168.00 | 69.21 | 0.0000 | Y | 20.41 |
ROOM_6_FLR_3_LIGHTS | ROOM_6_FLR_3 | ROOM_6_FLR_3 | GENERAL | 10.0642 | 156.07 | 1570.72 | LightsWired | LTG_SCH_GUESTROOM | 69.03 | 168.00 | 69.21 | 0.0000 | Y | 20.41 |
CORRIDOR_FLR_3_LIGHTS | CORRIDOR_FLR_3 | CORRIDOR_FLR_3 | GENERAL | 3.6597 | 1557.62 | 5700.46 | LightsWired | LTG_SCH_CORRIDOR | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 62.73 |
ROOM_1_FLR_6_LIGHTS | ROOM_1_FLR_6 | ROOM_1_FLR_6 | GENERAL | 10.0642 | 39.02 | 392.73 | LightsWired | LTG_SCH_GUESTROOM | 69.03 | 168.00 | 69.21 | 0.0000 | Y | 5.10 |
ROOM_2_FLR_6_LIGHTS | ROOM_2_FLR_6 | ROOM_2_FLR_6 | GENERAL | 10.0642 | 39.02 | 392.68 | LightsWired | LTG_SCH_GUESTROOM | 69.03 | 168.00 | 69.21 | 0.0000 | Y | 5.10 |
ROOM_3_MULT9_FLR_6_LIGHTS | ROOM_3_MULT9_FLR_6 | ROOM_3_MULT9_FLR_6 | GENERAL | 10.0642 | 220.77 | 2221.93 | LightsWired | LTG_SCH_GUESTROOM | 69.03 | 168.00 | 69.21 | 0.0000 | Y | 28.87 |
BANQUET_FLR_6_LIGHTS | BANQUET_FLR_6 | BANQUET_FLR_6 | GENERAL | 12.8090 | 331.66 | 4248.21 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 46.75 |
DINING_FLR_6_LIGHTS | DINING_FLR_6 | DINING_FLR_6 | GENERAL | 12.8090 | 331.66 | 4248.21 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 46.75 |
KITCHEN_FLR_6_LIGHTS | KITCHEN_FLR_6 | KITCHEN_FLR_6 | GENERAL | 10.9792 | 103.30 | 1134.20 | LightsWired | LTG_SCH_KITCHEN | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 12.48 |
CORRIDOR_FLR_6_LIGHTS | CORRIDOR_FLR_6 | CORRIDOR_FLR_6 | GENERAL | 3.6597 | 412.12 | 1508.26 | LightsWired | LTG_SCH_CORRIDOR | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 16.60 |
Interior Lighting Total | 8.9207 | 11345.29 | 101207.97 | 559.10 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR FACADE LIGHTING | 16690.39 | AstronomicalClock | - | 83.77 | 83.77 | 262.44 | |
Exterior Lighting Total | 16690.39 | 262.44 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:58:10
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
HEATSYS1 BOILER | Boiler:HotWater | 484765.23 | 0.80 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:EIR | 1032120.29 | 2.80 | 1032301.71 | 2.80 | 3.72 | 12.68 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 13327.53 | 22320.18 | 16417.25 | 5902.93 | 0.74 | - | 3335.07 | 33.83 |
ROOM_2_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 13232.26 | 22160.41 | 16299.61 | 5860.81 | 0.74 | - | 3311.16 | 33.58 |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 80829.74 | 136156.72 | 100208.05 | 35948.67 | 0.74 | - | 20698.97 | 209.94 |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 90352.22 | 149440.23 | 108787.81 | 40652.42 | 0.73 | - | 22036.97 | 223.51 |
ROOM_5_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 11674.40 | 19553.29 | 14379.68 | 5173.61 | 0.74 | - | 2923.64 | 29.65 |
ROOM_6_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 11579.51 | 19394.22 | 14262.62 | 5131.61 | 0.74 | - | 2899.83 | 29.41 |
ROOM_1_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 3611.78 | 6049.56 | 4450.12 | 1599.44 | 0.74 | - | 904.05 | 9.17 |
ROOM_2_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 3582.23 | 6000.01 | 4413.63 | 1586.38 | 0.74 | - | 896.64 | 9.09 |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 16581.75 | 27624.78 | 20226.52 | 7398.26 | 0.73 | - | 4105.57 | 41.64 |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | 729331.56 | 664290.74 | 409499.04 | 254791.70 | 0.62 | - | 70658.82 | 716.66 |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | 57348.72 | 51198.70 | 32051.32 | 19147.38 | 0.63 | - | 5018.41 | 50.90 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
BASEMENT VAV BOX REHEAT COIL | Coil:Heating:Water | 13021.18 | 13089.25 | - |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 4770.42 | 4793.45 | - |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 2266.37 | 2277.90 | - |
MECH_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 3192.02 | 3207.69 | - |
STORAGE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1782.12 | 1790.77 | - |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 19667.59 | 19769.87 | - |
CAFE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 15073.10 | 15148.05 | - |
LOBBY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 42329.07 | 42544.82 | - |
ROOM_1_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 6581.78 | 7091.58 | - |
ROOM_2_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 6575.24 | 7084.54 | - |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 37721.69 | 40643.29 | - |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 37617.71 | 40531.28 | - |
ROOM_5_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 6569.52 | 7078.37 | - |
ROOM_6_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 6562.97 | 7071.32 | - |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 16345.59 | 16424.66 | - |
ROOM_1_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 2054.07 | 2213.08 | - |
ROOM_2_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 2053.25 | 2212.20 | - |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 9915.53 | 10683.09 | - |
BANQUET_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 18979.29 | 19076.44 | - |
DINING_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 19688.34 | 19789.18 | - |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 13990.36 | 14063.05 | - |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 11230.01 | 11283.70 | - |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | 172635.01 | 130015.88 | - |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | 14143.00 | 10651.46 | - |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
LAUNDRY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 0.16 | 125.00 | 0.24 | 184.35 | 781.25 | 1.00 | 1.15 | General | ||
LOBBY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | General | |||
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.16 | 270.90 | 1.26 | 2129.05 | 1693.12 | 1.00 | 0.48 | General | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 |
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.16 | 270.90 | 1.25 | 2113.77 | 1693.12 | 1.00 | 0.48 | General | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 |
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.16 | 270.90 | 7.66 | 12970.57 | 1693.12 | 1.00 | 0.39 | General | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 |
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.16 | 270.90 | 8.25 | 13961.11 | 1693.12 | 1.00 | 0.39 | General | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 |
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.16 | 270.90 | 1.10 | 1864.23 | 1693.12 | 1.00 | 0.49 | General | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 |
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.16 | 270.90 | 1.09 | 1849.04 | 1693.12 | 1.00 | 0.49 | General | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 |
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.16 | 270.90 | 0.34 | 577.17 | 1693.12 | 1.00 | 0.68 | General | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 |
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.16 | 270.90 | 0.34 | 572.43 | 1693.12 | 1.00 | 0.68 | General | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 |
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.16 | 270.90 | 1.54 | 2610.88 | 1693.12 | 1.00 | 0.46 | General | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 |
BANQUET_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | General | |||
DINING_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | General | |||
KITCHEN_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 0.16 | 125.00 | 1.89 | 1474.84 | 781.25 | 1.00 | 0.62 | General | ||
VAV WITH REHEAT FAN | Fan:VariableVolume | 0.62 | 1389.42 | 25.04 | 56103.75 | 2240.64 | 1.00 | 1.11 | General | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 |
FLR_3_DOAS FAN | Fan:ConstantVolume | 0.58 | 622.50 | 2.05 | 2194.93 | 1070.05 | 1.00 | 1.30 | General | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 133527.72 | 0.036841 | 7591.54 | 206062.94 | 0.90 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.004241 | 1277.18 | 301156.09 | 0.90 | General |
COOLSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 92445.74 | 0.036841 | 5255.88 | 142664.32 | 0.90 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000375 | 47.91 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWH BOOSTER E WATER HEATER | WaterHeater:Mixed | 0.02 | 8000.00 | 1.00 | 1.24 | 1.15 |
SWH LAUNDRY G WATER HEATER | WaterHeater:Mixed | 1.14 | 163316.00 | 0.80 | 0.58 | 0.51 |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 2.27 | 175842.60 | 0.80 | 0.26 | 0.03 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:58:10
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 34112.29 | 34112.29 | 17.24 | 2.858 | 2.858 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 20:50:00 | 24.00 | 24.00 | 0.00921 | 30.62 | 0.00686 | 0.854 | 0.00 |
RETAIL_1_FLR_1 | 4647.20 | 4647.20 | 69.29 | 0.389 | 0.389 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 24.00 | 24.00 | 0.00894 | 37.99 | 0.00687 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 3392.10 | 3392.10 | 43.67 | 0.284 | 0.284 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 24.00 | 24.00 | 0.00928 | 36.06 | 0.00687 | 0.092 | 0.00 |
MECH_FLR_1 | 3633.18 | 3633.18 | 22.12 | 0.304 | 0.304 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 24.00 | 24.00 | 0.00858 | 34.98 | 0.00687 | 0.000 | 0.00 |
STORAGE_FLR_1 | 1834.88 | 1834.88 | 19.36 | 0.154 | 0.154 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 24.00 | 24.00 | 0.00865 | 36.06 | 0.00687 | 0.058 | 0.00 |
LAUNDRY_FLR_1 | 45235.90 | 45235.90 | 579.65 | 3.790 | 3.790 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 24.00 | 24.00 | 0.00853 | 37.58 | 0.00687 | 0.000 | 0.00 |
CAFE_FLR_1 | 19748.77 | 19748.77 | 104.57 | 1.656 | 1.656 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 24.00 | 23.99 | 0.01006 | 37.99 | 0.00687 | 0.676 | 0.00 |
LOBBY_FLR_1 | 65273.03 | 65273.03 | 49.90 | 5.471 | 5.471 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 24.00 | 23.99 | 0.00991 | 38.10 | 0.00687 | 1.894 | 0.00 |
ROOM_1_FLR_3 | 11139.23 | 11139.23 | 285.46 | 1.257 | 1.257 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 21.11 | 21.11 | 0.00852 | 36.80 | 0.00687 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 11059.32 | 11059.32 | 283.45 | 1.248 | 1.248 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 21.11 | 21.11 | 0.00852 | 36.63 | 0.00687 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 67864.35 | 67864.35 | 2767.28 | 7.661 | 7.661 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 21.11 | 21.11 | 0.00846 | 38.10 | 0.00687 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 73041.28 | 73041.28 | 2977.56 | 8.246 | 8.246 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 21.11 | 21.11 | 0.00865 | 37.71 | 0.00687 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 9753.73 | 9753.73 | 249.95 | 1.101 | 1.101 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | 21.11 | 21.11 | 0.00852 | 33.81 | 0.00686 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 9674.27 | 9674.27 | 247.95 | 1.092 | 1.092 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 | 21.11 | 21.11 | 0.00852 | 33.48 | 0.00686 | 0.062 | 0.00 |
CORRIDOR_FLR_3 | 16255.55 | 16255.55 | 41.74 | 1.362 | 1.362 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 24.00 | 24.00 | 0.00958 | 37.84 | 0.00687 | 0.475 | 0.00 |
ROOM_1_FLR_6 | 3019.76 | 3019.76 | 77.39 | 0.341 | 0.341 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 21.11 | 21.11 | 0.00852 | 36.80 | 0.00687 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 2994.96 | 2994.96 | 76.76 | 0.338 | 0.338 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 21.11 | 21.11 | 0.00852 | 36.80 | 0.00687 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 13659.77 | 13659.77 | 556.85 | 1.542 | 1.542 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 21.11 | 21.11 | 0.00858 | 38.10 | 0.00687 | 0.099 | 0.00 |
BANQUET_FLR_6 | 31477.22 | 31477.22 | 94.91 | 2.640 | 2.640 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 24.00 | 23.98 | 0.01026 | 38.10 | 0.00687 | 1.188 | 0.00 |
DINING_FLR_6 | 33000.64 | 33000.64 | 99.50 | 2.768 | 2.768 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 24.00 | 23.98 | 0.01018 | 38.10 | 0.00687 | 1.188 | 0.00 |
KITCHEN_FLR_6 | 31366.80 | 31366.80 | 303.63 | 2.635 | 2.635 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 24.00 | 23.97 | 0.01002 | 36.93 | 0.00687 | 0.367 | 0.00 |
CORRIDOR_FLR_6 | 10077.64 | 10077.64 | 24.45 | 0.844 | 0.844 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 24.00 | 24.00 | 0.00895 | 38.10 | 0.00687 | 0.126 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 0.854 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 23.40 | 0.00281 | -5.20 | 0.00281 | 0.854 | 0.00 |
RETAIL_1_FLR_1 | 2998.72 | 2998.72 | 44.71 | 0.148 | 0.148 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00740 | -5.20 | 0.00281 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 973.16 | 973.16 | 12.53 | 0.048 | 0.092 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00731 | -5.20 | 0.00281 | 0.092 | 0.00 |
MECH_FLR_1 | 1807.63 | 1807.63 | 11.01 | 0.089 | 0.089 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00715 | -5.20 | 0.00281 | 0.000 | 0.00 |
STORAGE_FLR_1 | 1082.91 | 1082.91 | 11.43 | 0.054 | 0.058 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00717 | -5.20 | 0.00281 | 0.058 | 0.00 |
LAUNDRY_FLR_1 | 2432.06 | 2432.06 | 31.16 | 0.120 | 0.120 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00714 | -5.20 | 0.00281 | 0.000 | 0.00 |
CAFE_FLR_1 | 7536.22 | 7536.22 | 39.90 | 0.372 | 0.676 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00747 | -5.20 | 0.00281 | 0.676 | 0.00 |
LOBBY_FLR_1 | 17434.45 | 17434.45 | 13.33 | 0.862 | 1.894 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00736 | -5.20 | 0.00281 | 1.894 | 0.00 |
ROOM_1_FLR_3 | 6582.02 | 6582.02 | 168.67 | 0.327 | 0.327 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00738 | -5.20 | 0.00281 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 6575.47 | 6575.47 | 168.53 | 0.327 | 0.327 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00738 | -5.20 | 0.00281 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 37722.34 | 37722.34 | 1538.19 | 1.875 | 1.875 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00742 | -5.20 | 0.00281 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 37618.36 | 37618.36 | 1533.53 | 1.870 | 1.870 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00742 | -5.20 | 0.00281 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 6569.75 | 6569.75 | 168.36 | 0.327 | 0.327 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00738 | -5.20 | 0.00281 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 6563.21 | 6563.21 | 168.21 | 0.326 | 0.326 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00738 | -5.20 | 0.00281 | 0.062 | 0.00 |
CORRIDOR_FLR_3 | 10146.72 | 10146.72 | 26.06 | 0.501 | 0.501 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00750 | -5.20 | 0.00281 | 0.475 | 0.00 |
ROOM_1_FLR_6 | 2054.14 | 2054.14 | 52.64 | 0.102 | 0.102 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00749 | -5.20 | 0.00281 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 2053.32 | 2053.32 | 52.63 | 0.102 | 0.102 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00749 | -5.20 | 0.00281 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 9915.80 | 9915.80 | 404.22 | 0.493 | 0.493 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00751 | -5.20 | 0.00281 | 0.099 | 0.00 |
BANQUET_FLR_6 | 6958.28 | 6958.28 | 20.98 | 0.344 | 1.188 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00762 | -5.20 | 0.00281 | 1.188 | 0.00 |
DINING_FLR_6 | 7085.83 | 7085.83 | 21.36 | 0.350 | 1.188 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 21.00 | 21.00 | 0.00763 | -5.20 | 0.00281 | 1.188 | 0.00 |
KITCHEN_FLR_6 | 2031.68 | 2031.68 | 19.67 | 0.100 | 0.367 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | 21.00 | 21.00 | 0.00637 | -5.20 | 0.00281 | 0.367 | 0.00 |
CORRIDOR_FLR_6 | 7385.91 | 7385.91 | 17.92 | 0.365 | 0.365 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 21.00 | 21.00 | 0.00768 | -5.20 | 0.00281 | 0.126 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV WITH REHEAT | 25.04 | 25.04 | 7.54 | 7.54 | 25.0392 | 25.0296 | 25.0392 | 0.9996 | 0.3000 |
FLR_3_DOAS | 22.39 | 2.05 | 5.75 | 2.05 | 2.0513 | 2.0513 | 2.0513 | 1.0000 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
BASEMENT VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | 13021.183 | 13021.183 | 2.843585 | 0.00011391 | 271.534 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 13021.18 | 13021.18 | 2.843585 | 16.70 | 11.86 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00800000 | 44.8527 | 0.00 | 0.00 | 13094.37 | 13094.37 |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | 4770.421 | 4770.421 | 0.387412 | 0.00004173 | 109.122 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 4770.42 | 4770.42 | 0.387412 | 16.70 | 11.86 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00740404 | 41.5530 | 2998.72 | 0.00 | 4796.05 | 4796.05 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | 2266.373 | 2266.373 | 0.282793 | 0.00001983 | 49.182 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 2266.37 | 2266.37 | 0.282793 | 16.70 | 11.86 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00730618 | 41.0087 | 973.16 | 0.00 | 2278.95 | 2278.95 |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | 3192.023 | 3192.023 | 0.302822 | 0.00002793 | 71.415 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 3192.02 | 3192.02 | 0.302822 | 16.70 | 11.86 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00714817 | 40.1319 | 1807.63 | 0.00 | 3209.32 | 3209.32 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | 1782.115 | 1782.115 | 0.152937 | 0.00001559 | 40.427 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 1782.12 | 1782.12 | 0.152937 | 16.70 | 11.86 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00717464 | 40.2789 | 1082.91 | 0.00 | 1791.72 | 1791.72 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 19667.588 | 19667.588 | 3.770679 | 0.00017206 | 413.112 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 19667.59 | 19667.59 | 3.770679 | 16.70 | 11.86 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00713766 | 40.0751 | 2432.06 | 0.00 | 19777.84 | 19777.84 |
CAFE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | 15073.104 | 15073.104 | 1.647800 | 0.00013187 | 331.539 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 15073.10 | 15073.10 | 1.647800 | 16.70 | 11.86 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00746845 | 41.9098 | 7536.22 | 0.00 | 15155.32 | 15155.32 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 42329.066 | 42329.066 | 5.443297 | 0.00037031 | 915.984 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 42329.07 | 42329.07 | 5.443297 | 16.70 | 11.86 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00735889 | 41.3011 | 17434.45 | 0.00 | 42564.09 | 42564.09 |
ROOM_1_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 13327.530 | -999.000 | 1.257465 | 0.00047602 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | unknown | 7/21 16:30:00 | 13327.53 | 13283.11 | 1.257465 | 22.70 | 14.50 | 0.00851776 | 12.80 | 10.82 | 0.00850000 | 36.80 | 0.00686940 | 17.78 | 0.0000 | 21.11 | 0.00851776 | 47.3923 | 11139.23 | 0.00 | 15316.11 | 14687.96 |
ROOM_1_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 6581.784 | 6581.784 | 0.327185 | 0.00005758 | 188.101 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 6581.78 | 6581.78 | 0.327185 | 21.11 | 12.94 | 0.00737699 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.11 | 0.00737699 | 41.1221 | 6582.02 | 0.00 | 7095.27 | 7095.27 |
ROOM_2_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 13232.263 | -999.000 | 1.248444 | 0.00047262 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | unknown | 7/21 16:40:00 | 13232.26 | 13187.91 | 1.248444 | 22.70 | 14.50 | 0.00851786 | 12.80 | 10.82 | 0.00850000 | 36.63 | 0.00686912 | 17.72 | 0.0000 | 21.11 | 0.00851786 | 47.3929 | 11059.32 | 0.00 | 15206.60 | 14582.61 |
ROOM_2_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 6575.240 | 6575.240 | 0.326859 | 0.00005752 | 187.915 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 6575.24 | 6575.24 | 0.326859 | 21.11 | 12.94 | 0.00737648 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.11 | 0.00737648 | 41.1193 | 6575.47 | 0.00 | 7088.21 | 7088.21 |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 80829.736 | -999.000 | 7.660726 | 0.00288700 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | unknown | 7/21 14:10:00 | 80829.74 | 80829.74 | 7.660726 | 22.70 | 14.45 | 0.00845810 | 12.80 | 10.78 | 0.00845810 | 38.10 | 0.00687148 | 18.17 | 0.0000 | 21.11 | 0.00845810 | 47.0641 | 67864.35 | 0.00 | 92978.76 | 89948.01 |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 37721.688 | 37721.688 | 1.875229 | 0.00033001 | 1078.033 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 37721.69 | 37721.69 | 1.875229 | 21.11 | 12.98 | 0.00741847 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.11 | 0.00741847 | 41.3491 | 37722.34 | 0.00 | 40664.98 | 40664.98 |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 90352.222 | -999.000 | 8.245766 | 0.00322711 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | unknown | 7/21 15:30:00 | 90352.22 | 87820.21 | 8.245766 | 22.70 | 14.61 | 0.00865314 | 12.80 | 10.82 | 0.00850000 | 37.71 | 0.00687086 | 18.05 | 0.0000 | 21.11 | 0.00865314 | 48.1364 | 73041.28 | 0.00 | 103614.50 | 96525.49 |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 37617.709 | 37617.709 | 1.870060 | 0.00032910 | 1075.062 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 37617.71 | 37617.71 | 1.870060 | 21.11 | 12.98 | 0.00741690 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.11 | 0.00741690 | 41.3404 | 37618.36 | 0.00 | 40552.89 | 40552.89 |
ROOM_5_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 11674.396 | -999.000 | 1.101060 | 0.00041697 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | unknown | 7/21 10:20:00 | 11674.40 | 11632.08 | 1.101060 | 22.70 | 14.50 | 0.00851932 | 12.80 | 10.82 | 0.00850000 | 33.81 | 0.00686464 | 16.84 | 0.0000 | 21.11 | 0.00851932 | 47.4009 | 9753.73 | 0.00 | 13419.41 | 12863.85 |
ROOM_5_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 6569.520 | 6569.520 | 0.326575 | 0.00005747 | 187.751 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 6569.52 | 6569.52 | 0.326575 | 21.11 | 12.94 | 0.00737596 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.11 | 0.00737596 | 41.1164 | 6569.75 | 0.00 | 7082.05 | 7082.05 |
ROOM_6_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 11579.509 | -999.000 | 1.092090 | 0.00041359 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 | unknown | 7/21 10:10:00 | 11579.51 | 11537.38 | 1.092090 | 22.70 | 14.50 | 0.00851940 | 12.80 | 10.82 | 0.00850000 | 33.48 | 0.00686412 | 16.74 | 0.0000 | 21.11 | 0.00851940 | 47.4013 | 9674.27 | 0.00 | 13310.33 | 12759.07 |
ROOM_6_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 6562.974 | 6562.974 | 0.326250 | 0.00005742 | 187.564 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 6562.97 | 6562.97 | 0.326250 | 21.11 | 12.94 | 0.00737546 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.11 | 0.00737546 | 41.1136 | 6563.21 | 0.00 | 7074.99 | 7074.99 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | 16345.587 | 16345.587 | 1.355013 | 0.00014300 | 372.715 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 16345.59 | 16345.59 | 1.355013 | 16.70 | 11.86 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00749556 | 42.0586 | 10146.72 | 0.00 | 16433.52 | 16433.52 |
ROOM_1_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 3611.779 | -999.000 | 0.340889 | 0.00012900 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | unknown | 7/21 16:30:00 | 3611.78 | 3600.64 | 0.340889 | 22.70 | 14.50 | 0.00851643 | 12.80 | 10.82 | 0.00850000 | 36.80 | 0.00686940 | 17.78 | 0.0000 | 21.11 | 0.00851643 | 47.3850 | 3019.76 | 0.00 | 4150.79 | 3981.71 |
ROOM_1_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 2054.069 | 2054.069 | 0.102109 | 0.00001797 | 58.700 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 2054.07 | 2054.07 | 0.102109 | 21.11 | 13.04 | 0.00748863 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.11 | 0.00748863 | 41.7370 | 2054.14 | 0.00 | 2214.32 | 2214.32 |
ROOM_2_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 3582.235 | -999.000 | 0.338090 | 0.00012795 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | unknown | 7/21 16:30:00 | 3582.23 | 3571.11 | 0.338090 | 22.70 | 14.50 | 0.00851655 | 12.80 | 10.82 | 0.00850000 | 36.80 | 0.00686940 | 17.78 | 0.0000 | 21.11 | 0.00851655 | 47.3856 | 2994.96 | 0.00 | 4116.82 | 3949.02 |
ROOM_2_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 2053.246 | 2053.246 | 0.102068 | 0.00001796 | 58.676 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 2053.25 | 2053.25 | 0.102068 | 21.11 | 13.04 | 0.00748848 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.11 | 0.00748848 | 41.7362 | 2053.32 | 0.00 | 2213.43 | 2213.43 |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 16581.749 | -999.000 | 1.542050 | 0.00059225 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | unknown | 7/21 14:10:00 | 16581.75 | 16347.69 | 1.542050 | 22.70 | 14.55 | 0.00857605 | 12.80 | 10.82 | 0.00850000 | 38.10 | 0.00687148 | 18.17 | 0.0000 | 21.11 | 0.00857605 | 47.7130 | 13659.77 | 0.00 | 19041.16 | 18030.84 |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 9915.527 | 9915.527 | 0.492913 | 0.00008675 | 283.355 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 9915.53 | 9915.53 | 0.492913 | 21.11 | 13.06 | 0.00750998 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.11 | 0.00750998 | 41.8540 | 9915.80 | 0.00 | 10689.13 | 10689.13 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 18979.288 | 18979.288 | 2.627215 | 0.00016604 | 408.036 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 18979.29 | 18979.29 | 2.627215 | 16.70 | 11.86 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00761890 | 42.7428 | 6958.28 | 0.00 | 19084.87 | 19084.87 |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 19688.337 | 19688.337 | 2.754321 | 0.00017224 | 422.903 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 19688.34 | 19688.34 | 2.754321 | 16.70 | 11.86 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00762527 | 42.7783 | 7085.83 | 0.00 | 19797.89 | 19797.89 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 13990.362 | 13990.362 | 2.621738 | 0.00012239 | 294.268 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | 13990.36 | 13990.36 | 2.621738 | 16.70 | 11.86 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00636664 | 35.7965 | 2031.68 | 0.00 | 14068.75 | 14068.75 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | 11230.011 | 11230.011 | 0.840029 | 0.00009825 | 260.374 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 11230.01 | 11230.01 | 0.840029 | 16.70 | 11.86 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00768134 | 43.0887 | 7385.91 | 0.00 | 11290.09 | 11290.09 |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV WITH REHEAT | 729331.555 | -999.000 | 25.039179 | 0.02605003 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 729331.56 | 729331.55 | 25.039179 | 38.10 | 18.17 | 0.00687148 | 10.69 | 8.30 | 0.00687148 | 38.10 | 0.00687148 | 18.17 | 100.0000 | 23.99 | 0.00961027 | 44.8090 | 298671.58 | 0.00 | 666374.53 | 666374.53 |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV WITH REHEAT | 172635.014 | 172635.014 | 7.511754 | 0.00151029 | 2930.658 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 172635.01 | 172635.01 | 7.511754 | -5.20 | -5.20 | 0.00280840 | 16.70 | 11.86 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 333.3333 | 21.69 | 0.00613341 | 33.0624 | 67206.29 | 0.00 | 157216.12 | 157216.12 |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | FLR_3_DOAS | 57348.723 | -999.000 | 2.051317 | 0.00204836 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 57348.72 | 57348.72 | 2.051317 | 38.10 | 18.17 | 0.00687148 | 11.79 | 8.78 | 0.00687148 | 38.10 | 0.00687148 | 18.17 | 99.9965 | 21.11 | 0.00855905 | 47.6192 | 198032.57 | 0.00 | 51614.51 | 51614.51 |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | FLR_3_DOAS | 14143.003 | 14143.003 | 0.615395 | 0.00012373 | 240.092 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 14143.00 | 14143.00 | 0.615395 | -5.20 | -5.20 | 0.00280840 | 16.70 | 11.86 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 333.3216 | 21.11 | 0.00741839 | 41.3487 | 115654.40 | 0.00 | 12879.82 | 12879.82 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:58:10
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
BASEMENT VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | BASEMENT | N/A | N/A | N/A | Yes | Yes | Yes | No | 13021.183 | 13021.183 | 2.843585 | 0.00011391 | 271.534 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.24050511 | 54.44 | 82.22 | 27.78 | 494521.33 | 2.6331 | 2.686080 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 13021.18 | 13021.18 | 1.0000 | 2.96964566 | 2.843585 | 16.70 | 11.86 | 0.00800000 | 37036.7 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.11390337 | 60.00 | 32.22 | 27.78 | 0.000 | 13021.18 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 44.8527 | 0.00 | 0.00 | 13094.37 | 13094.37 | 2.96964566 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 20.92 | 14.82 | 0.00800000 | 41344.1 | |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | RETAIL_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 4770.421 | 4770.421 | 0.387412 | 0.00004173 | 109.122 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.24050511 | 54.44 | 82.22 | 27.78 | 494521.33 | 0.9647 | 0.984068 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 4770.42 | 4770.42 | 1.0000 | 0.40458635 | 0.387412 | 16.70 | 11.86 | 0.00800000 | 37036.7 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.04172947 | 60.00 | 32.22 | 27.78 | 0.000 | 4770.42 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.00 | 0.00740404 | 21.00 | 0.00740404 | 41.5530 | 2998.72 | 0.00 | 4796.05 | 4796.05 | 0.40458635 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 28.23 | 17.44 | 0.00800000 | 48789.0 | |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | RETAIL_2_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2266.373 | 2266.373 | 0.282793 | 0.00001983 | 49.182 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.24050511 | 54.44 | 82.22 | 27.78 | 494521.33 | 0.4583 | 0.467520 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 2266.37 | 2266.37 | 1.0000 | 0.29532925 | 0.282793 | 16.70 | 11.86 | 0.00800000 | 37036.7 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.01982519 | 60.00 | 32.22 | 27.78 | 0.000 | 2266.37 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.00 | 0.00730618 | 21.00 | 0.00730618 | 41.0087 | 973.16 | 0.00 | 2278.95 | 2278.95 | 0.29532925 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 24.17 | 16.02 | 0.00800000 | 44651.4 | |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | MECH_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3192.023 | 3192.023 | 0.302822 | 0.00002793 | 71.415 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.24050511 | 54.44 | 82.22 | 27.78 | 494521.33 | 0.6455 | 0.658468 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 3192.02 | 3192.02 | 1.0000 | 0.31624634 | 0.302822 | 16.70 | 11.86 | 0.00800000 | 37036.7 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.02792236 | 60.00 | 32.22 | 27.78 | 0.000 | 3192.02 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.00 | 0.00714817 | 21.00 | 0.00714817 | 40.1319 | 1807.63 | 0.00 | 3209.32 | 3209.32 | 0.31624634 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 26.55 | 16.86 | 0.00800000 | 47082.9 | |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | STORAGE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1782.115 | 1782.115 | 0.152937 | 0.00001559 | 40.427 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.24050511 | 54.44 | 82.22 | 27.78 | 494521.33 | 0.3604 | 0.367624 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 1782.12 | 1782.12 | 1.0000 | 0.15971647 | 0.152937 | 16.70 | 11.86 | 0.00800000 | 37036.7 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.01558913 | 60.00 | 32.22 | 27.78 | 0.000 | 1782.12 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.00 | 0.00717464 | 21.00 | 0.00717464 | 40.2789 | 1082.91 | 0.00 | 1791.72 | 1791.72 | 0.15971647 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 27.60 | 17.22 | 0.00800000 | 48152.9 | |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LAUNDRY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 19667.588 | 19667.588 | 3.770679 | 0.00017206 | 413.112 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.24050511 | 54.44 | 82.22 | 27.78 | 494521.33 | 3.9771 | 4.057137 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 19667.59 | 19667.59 | 1.0000 | 3.93783934 | 3.770679 | 16.70 | 11.86 | 0.00800000 | 37036.7 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.17204309 | 60.00 | 32.22 | 27.78 | 0.000 | 19667.59 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.00 | 0.00713766 | 21.00 | 0.00713766 | 40.0751 | 2432.06 | 0.00 | 19777.84 | 19777.84 | 3.93783934 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 21.53 | 15.05 | 0.00800000 | 41957.2 | |
CAFE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | CAFE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 15073.104 | 15073.104 | 1.647800 | 0.00013187 | 331.539 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.24050511 | 54.44 | 82.22 | 27.78 | 494521.33 | 3.0480 | 3.109362 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 15073.10 | 15073.10 | 1.0000 | 1.72084947 | 1.647800 | 16.70 | 11.86 | 0.00800000 | 37036.7 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.13185264 | 60.00 | 32.22 | 27.78 | 0.000 | 15073.10 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.00 | 0.00746845 | 21.00 | 0.00746845 | 41.9098 | 7536.22 | 0.00 | 15155.32 | 15155.32 | 1.72084947 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 25.24 | 16.40 | 0.00800000 | 45741.6 | |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LOBBY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 42329.066 | 42329.066 | 5.443297 | 0.00037031 | 915.984 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.24050511 | 54.44 | 82.22 | 27.78 | 494521.33 | 8.5596 | 8.731869 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 42329.07 | 42329.07 | 1.0000 | 5.68460753 | 5.443297 | 16.70 | 11.86 | 0.00800000 | 37036.7 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.37027536 | 60.00 | 32.22 | 27.78 | 0.000 | 42329.07 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.00 | 0.00735889 | 21.00 | 0.00735889 | 41.3011 | 17434.45 | 0.00 | 42564.09 | 42564.09 | 5.68460753 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 23.94 | 15.93 | 0.00800000 | 44422.3 | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 13327.530 | -999.000 | 1.257465 | 0.00047602 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6741 | 1004.8586 | 1.0443 | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.257465 | 1.31321053 | 4197.9300 | 999.8980 | 36.83714336 | 13.37 | 6.70 | 6.67 | 1031447.13 | 1.2921 | 1.292095 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | unknown | unknown | unknown | 7/21 16:30:00 | Sensible | 13327.53 | 13283.11 | 1.0000 | 1.31321053 | 1.257465 | 22.70 | 14.50 | 0.00851776 | 44471.0 | 12.80 | 10.82 | 0.00850000 | 34322.2 | 0.47597105 | 6.70 | 13.37 | 6.67 | 0.000 | 13327.53 | 36.80 | 0.00686940 | 17.78 | 0.00000000 | 0.0000 | 21.11 | 0.00851776 | 21.11 | 0.00851776 | 47.3923 | 11139.23 | 0.00 | 15316.11 | 14687.96 | 1.31321053 | 22.70 | 15.94 | 0.00851776 | 44471.0 | 11.74 | 11.48 | 0.00832816 | 32807.9 | |
ROOM_1_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6581.784 | 6581.784 | 0.327185 | 0.00005758 | 188.101 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.257465 | 1.31321053 | 4197.9300 | 999.8980 | 4.24050511 | 54.44 | 82.22 | 27.78 | 494521.33 | 1.3309 | 1.357726 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 6581.78 | 6581.78 | 1.0000 | 0.34168945 | 0.327185 | 21.11 | 12.94 | 0.00737699 | 39950.9 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.05757444 | 60.00 | 32.22 | 27.78 | 0.000 | 6581.78 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.11 | 0.00737699 | 21.11 | 0.00737699 | 41.1221 | 6582.02 | 0.00 | 7095.27 | 7095.27 | 0.34168945 | 16.60 | 12.54 | 0.00737699 | 35357.4 | 36.99 | 19.80 | 0.00737699 | 56122.6 | |
ROOM_2_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 13232.263 | -999.000 | 1.248444 | 0.00047262 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6743 | 1004.8586 | 1.0443 | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.248444 | 1.30379007 | 4197.9300 | 999.8980 | 36.83714336 | 13.37 | 6.70 | 6.67 | 1031447.13 | 1.2829 | 1.282859 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | unknown | unknown | unknown | 7/21 16:40:00 | Sensible | 13232.26 | 13187.91 | 1.0000 | 1.30379007 | 1.248444 | 22.70 | 14.50 | 0.00851786 | 44471.3 | 12.80 | 10.82 | 0.00850000 | 34322.2 | 0.47256874 | 6.70 | 13.37 | 6.67 | 0.000 | 13232.26 | 36.63 | 0.00686912 | 17.72 | 0.00000000 | 0.0000 | 21.11 | 0.00851786 | 21.11 | 0.00851786 | 47.3929 | 11059.32 | 0.00 | 15206.60 | 14582.61 | 1.30379007 | 22.70 | 15.94 | 0.00851786 | 44471.3 | 11.74 | 11.48 | 0.00832815 | 32807.9 | |
ROOM_2_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6575.240 | 6575.240 | 0.326859 | 0.00005752 | 187.915 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.248444 | 1.30379007 | 4197.9300 | 999.8980 | 4.24050511 | 54.44 | 82.22 | 27.78 | 494521.33 | 1.3296 | 1.356376 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 6575.24 | 6575.24 | 1.0000 | 0.34134974 | 0.326859 | 21.11 | 12.94 | 0.00737648 | 39949.7 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.05751720 | 60.00 | 32.22 | 27.78 | 0.000 | 6575.24 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.11 | 0.00737648 | 21.11 | 0.00737648 | 41.1193 | 6575.47 | 0.00 | 7088.21 | 7088.21 | 0.34134974 | 16.60 | 12.54 | 0.00737648 | 35356.1 | 36.99 | 19.80 | 0.00737648 | 56121.4 | |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 80829.736 | -999.000 | 7.660726 | 0.00288700 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.5632 | 1004.8586 | 1.0443 | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 7.660726 | 8.00033924 | 4197.9300 | 999.8980 | 36.83714336 | 13.37 | 6.70 | 6.67 | 1031447.13 | 7.8365 | 7.836391 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | unknown | unknown | unknown | 7/21 14:10:00 | Sensible | 80829.74 | 80829.74 | 1.0000 | 8.00033924 | 7.660726 | 22.70 | 14.45 | 0.00845810 | 44319.7 | 12.80 | 10.78 | 0.00845810 | 34216.4 | 2.88670248 | 6.70 | 13.37 | 6.67 | 0.000 | 80829.74 | 38.10 | 0.00687148 | 18.17 | 0.00000000 | 0.0000 | 21.11 | 0.00845810 | 21.11 | 0.00845810 | 47.0641 | 67864.35 | 0.00 | 92978.76 | 89948.01 | 8.00033924 | 22.70 | 15.89 | 0.00845810 | 44319.7 | 11.68 | 11.44 | 0.00830793 | 32697.8 | |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 37721.688 | 37721.688 | 1.875229 | 0.00033001 | 1078.033 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 7.660726 | 8.00033924 | 4197.9300 | 999.8980 | 4.24050511 | 54.44 | 82.22 | 27.78 | 494521.33 | 7.6279 | 7.781434 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 37721.69 | 37721.69 | 1.0000 | 1.95836160 | 1.875229 | 21.11 | 12.98 | 0.00741847 | 40056.9 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.32997212 | 60.00 | 32.22 | 27.78 | 0.000 | 37721.69 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.11 | 0.00741847 | 21.11 | 0.00741847 | 41.3491 | 37722.34 | 0.00 | 40664.98 | 40664.98 | 1.95836160 | 16.60 | 12.58 | 0.00741847 | 35462.4 | 36.99 | 19.84 | 0.00741847 | 56227.2 | |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 90352.222 | -999.000 | 8.245766 | 0.00322711 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9258 | 1004.8586 | 1.0443 | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 8.245766 | 8.61131531 | 4197.9300 | 999.8980 | 36.83714336 | 13.37 | 6.70 | 6.67 | 1031447.13 | 8.7598 | 8.759590 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | unknown | unknown | unknown | 7/21 15:30:00 | Sensible | 90352.22 | 87820.21 | 1.0000 | 8.61131531 | 8.245766 | 22.70 | 14.61 | 0.00865314 | 44814.5 | 12.80 | 10.82 | 0.00850000 | 34322.2 | 3.22678255 | 6.70 | 13.37 | 6.67 | 0.000 | 90352.22 | 37.71 | 0.00687086 | 18.05 | 0.00000000 | 0.0000 | 21.11 | 0.00865314 | 21.11 | 0.00865314 | 48.1364 | 73041.28 | 0.00 | 103614.50 | 96525.49 | 8.61131531 | 22.70 | 16.06 | 0.00865314 | 44814.5 | 11.72 | 11.47 | 0.00832682 | 32782.1 | |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 37617.709 | 37617.709 | 1.870060 | 0.00032910 | 1075.062 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 8.245766 | 8.61131531 | 4197.9300 | 999.8980 | 4.24050511 | 54.44 | 82.22 | 27.78 | 494521.33 | 7.6069 | 7.759985 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 37617.71 | 37617.71 | 1.0000 | 1.95296345 | 1.870060 | 21.11 | 12.98 | 0.00741690 | 40053.0 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.32906256 | 60.00 | 32.22 | 27.78 | 0.000 | 37617.71 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.11 | 0.00741690 | 21.11 | 0.00741690 | 41.3404 | 37618.36 | 0.00 | 40552.89 | 40552.89 | 1.95296345 | 16.60 | 12.58 | 0.00741690 | 35458.5 | 36.99 | 19.83 | 0.00741690 | 56223.2 | |
ROOM_5_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11674.396 | -999.000 | 1.101060 | 0.00041697 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6770 | 1004.8586 | 1.0443 | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.101060 | 1.14987188 | 4197.9300 | 999.8980 | 36.83714336 | 13.37 | 6.70 | 6.67 | 1031447.13 | 1.1318 | 1.131825 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | unknown | unknown | unknown | 7/21 10:20:00 | Sensible | 11674.40 | 11632.08 | 1.0000 | 1.14987188 | 1.101060 | 22.70 | 14.50 | 0.00851932 | 44475.0 | 12.80 | 10.82 | 0.00850000 | 34322.2 | 0.41693207 | 6.70 | 13.37 | 6.67 | 0.000 | 11674.40 | 33.81 | 0.00686464 | 16.84 | 0.00000000 | 0.0000 | 21.11 | 0.00851932 | 21.11 | 0.00851932 | 47.4009 | 9753.73 | 0.00 | 13419.41 | 12863.85 | 1.14987188 | 22.70 | 15.94 | 0.00851932 | 44475.0 | 11.74 | 11.48 | 0.00832780 | 32804.6 | |
ROOM_5_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6569.520 | 6569.520 | 0.326575 | 0.00005747 | 187.751 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.101060 | 1.14987188 | 4197.9300 | 999.8980 | 4.24050511 | 54.44 | 82.22 | 27.78 | 494521.33 | 1.3285 | 1.355196 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 6569.52 | 6569.52 | 1.0000 | 0.34105278 | 0.326575 | 21.11 | 12.94 | 0.00737596 | 39948.3 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.05746716 | 60.00 | 32.22 | 27.78 | 0.000 | 6569.52 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.11 | 0.00737596 | 21.11 | 0.00737596 | 41.1164 | 6569.75 | 0.00 | 7082.05 | 7082.05 | 0.34105278 | 16.60 | 12.54 | 0.00737596 | 35354.8 | 36.99 | 19.80 | 0.00737596 | 56120.1 | |
ROOM_6_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11579.509 | -999.000 | 1.092090 | 0.00041359 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6771 | 1004.8586 | 1.0443 | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.092090 | 1.14050404 | 4197.9300 | 999.8980 | 36.83714336 | 13.37 | 6.70 | 6.67 | 1031447.13 | 1.1226 | 1.122626 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 | unknown | unknown | unknown | 7/21 10:10:00 | Sensible | 11579.51 | 11537.38 | 1.0000 | 1.14050404 | 1.092090 | 22.70 | 14.50 | 0.00851940 | 44475.2 | 12.80 | 10.82 | 0.00850000 | 34322.2 | 0.41354333 | 6.70 | 13.37 | 6.67 | 0.000 | 11579.51 | 33.48 | 0.00686412 | 16.74 | 0.00000000 | 0.0000 | 21.11 | 0.00851940 | 21.11 | 0.00851940 | 47.4013 | 9674.27 | 0.00 | 13310.33 | 12759.07 | 1.14050404 | 22.70 | 15.94 | 0.00851940 | 44475.2 | 11.74 | 11.48 | 0.00832780 | 32804.6 | |
ROOM_6_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6562.974 | 6562.974 | 0.326250 | 0.00005742 | 187.564 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.092090 | 1.14050404 | 4197.9300 | 999.8980 | 4.24050511 | 54.44 | 82.22 | 27.78 | 494521.33 | 1.3271 | 1.353846 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 6562.97 | 6562.97 | 1.0000 | 0.34071298 | 0.326250 | 21.11 | 12.94 | 0.00737546 | 39947.1 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.05740991 | 60.00 | 32.22 | 27.78 | 0.000 | 6562.97 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.11 | 0.00737546 | 21.11 | 0.00737546 | 41.1136 | 6563.21 | 0.00 | 7074.99 | 7074.99 | 0.34071298 | 16.60 | 12.54 | 0.00737546 | 35353.5 | 36.99 | 19.80 | 0.00737546 | 56118.8 | |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | CORRIDOR_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 16345.587 | 16345.587 | 1.355013 | 0.00014300 | 372.715 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.24050511 | 54.44 | 82.22 | 27.78 | 494521.33 | 3.3053 | 3.371856 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 16345.59 | 16345.59 | 1.0000 | 1.41508301 | 1.355013 | 16.70 | 11.86 | 0.00800000 | 37036.7 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.14298374 | 60.00 | 32.22 | 27.78 | 0.000 | 16345.59 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.00 | 0.00749556 | 21.00 | 0.00749556 | 42.0586 | 10146.72 | 0.00 | 16433.52 | 16433.52 | 1.41508301 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 27.99 | 17.36 | 0.00800000 | 48547.8 | |
ROOM_1_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3611.779 | -999.000 | 0.340889 | 0.00012900 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6716 | 1004.8586 | 1.0443 | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.340889 | 0.35600076 | 4197.9300 | 999.8980 | 36.83714336 | 13.37 | 6.70 | 6.67 | 1031447.13 | 0.3502 | 0.350160 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | unknown | unknown | unknown | 7/21 16:30:00 | Sensible | 3611.78 | 3600.64 | 1.0000 | 0.35600076 | 0.340889 | 22.70 | 14.50 | 0.00851643 | 44467.6 | 12.80 | 10.82 | 0.00850000 | 34322.2 | 0.12898882 | 6.70 | 13.37 | 6.67 | 0.000 | 3611.78 | 36.80 | 0.00686940 | 17.78 | 0.00000000 | 0.0000 | 21.11 | 0.00851643 | 21.11 | 0.00851643 | 47.3850 | 3019.76 | 0.00 | 4150.79 | 3981.71 | 0.35600076 | 22.70 | 15.94 | 0.00851643 | 44467.6 | 11.74 | 11.48 | 0.00832817 | 32808.1 | |
ROOM_1_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2054.069 | 2054.069 | 0.102109 | 0.00001797 | 58.700 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.340889 | 0.35600076 | 4197.9300 | 999.8980 | 4.24050511 | 54.44 | 82.22 | 27.78 | 494521.33 | 0.4154 | 0.423725 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 2054.07 | 2054.07 | 1.0000 | 0.10663580 | 0.102109 | 21.11 | 13.04 | 0.00748863 | 40234.5 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.01796806 | 60.00 | 32.22 | 27.78 | 0.000 | 2054.07 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.11 | 0.00748863 | 21.11 | 0.00748863 | 41.7370 | 2054.14 | 0.00 | 2214.32 | 2214.32 | 0.10663580 | 16.60 | 12.65 | 0.00748863 | 35640.0 | 36.98 | 19.89 | 0.00748863 | 56405.3 | |
ROOM_2_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3582.235 | -999.000 | 0.338090 | 0.00012795 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6718 | 1004.8586 | 1.0443 | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.338090 | 0.35307789 | 4197.9300 | 999.8980 | 36.83714336 | 13.37 | 6.70 | 6.67 | 1031447.13 | 0.3473 | 0.347295 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | unknown | unknown | unknown | 7/21 16:30:00 | Sensible | 3582.23 | 3571.11 | 1.0000 | 0.35307789 | 0.338090 | 22.70 | 14.50 | 0.00851655 | 44467.9 | 12.80 | 10.82 | 0.00850000 | 34322.2 | 0.12793369 | 6.70 | 13.37 | 6.67 | 0.000 | 3582.23 | 36.80 | 0.00686940 | 17.78 | 0.00000000 | 0.0000 | 21.11 | 0.00851655 | 21.11 | 0.00851655 | 47.3856 | 2994.96 | 0.00 | 4116.82 | 3949.02 | 0.35307789 | 22.70 | 15.94 | 0.00851655 | 44467.9 | 11.74 | 11.48 | 0.00832817 | 32808.1 | |
ROOM_2_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2053.246 | 2053.246 | 0.102068 | 0.00001796 | 58.676 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.338090 | 0.35307789 | 4197.9300 | 999.8980 | 4.24050511 | 54.44 | 82.22 | 27.78 | 494521.33 | 0.4152 | 0.423555 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 2053.25 | 2053.25 | 1.0000 | 0.10659305 | 0.102068 | 21.11 | 13.04 | 0.00748848 | 40234.2 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.01796086 | 60.00 | 32.22 | 27.78 | 0.000 | 2053.25 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.11 | 0.00748848 | 21.11 | 0.00748848 | 41.7362 | 2053.32 | 0.00 | 2213.43 | 2213.43 | 0.10659305 | 16.60 | 12.65 | 0.00748848 | 35639.7 | 36.98 | 19.89 | 0.00748848 | 56404.9 | |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 16581.749 | -999.000 | 1.542050 | 0.00059225 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7824 | 1004.8586 | 1.0443 | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.542050 | 1.61041201 | 4197.9300 | 999.8980 | 36.83714336 | 13.37 | 6.70 | 6.67 | 1031447.13 | 1.6076 | 1.607590 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | unknown | unknown | unknown | 7/21 14:10:00 | Sensible | 16581.75 | 16347.69 | 1.0000 | 1.61041201 | 1.542050 | 22.70 | 14.55 | 0.00857605 | 44618.8 | 12.80 | 10.82 | 0.00850000 | 34322.2 | 0.59219016 | 6.70 | 13.37 | 6.67 | 0.000 | 16581.75 | 38.10 | 0.00687148 | 18.17 | 0.00000000 | 0.0000 | 21.11 | 0.00857605 | 21.11 | 0.00857605 | 47.7130 | 13659.77 | 0.00 | 19041.16 | 18030.84 | 1.61041201 | 22.70 | 15.99 | 0.00857605 | 44618.8 | 11.73 | 11.48 | 0.00832736 | 32795.0 | |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9915.527 | 9915.527 | 0.492913 | 0.00008675 | 283.355 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.542050 | 1.61041201 | 4197.9300 | 999.8980 | 4.24050511 | 54.44 | 82.22 | 27.78 | 494521.33 | 2.0051 | 2.045429 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 9915.53 | 9915.53 | 1.0000 | 0.51476444 | 0.492913 | 21.11 | 13.06 | 0.00750998 | 40289.0 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.08673651 | 60.00 | 32.22 | 27.78 | 0.000 | 9915.53 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.11 | 0.00750998 | 21.11 | 0.00750998 | 41.8540 | 9915.80 | 0.00 | 10689.13 | 10689.13 | 0.51476444 | 16.60 | 12.67 | 0.00750998 | 35694.1 | 36.98 | 19.90 | 0.00750998 | 56459.2 | |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | BANQUET_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 18979.288 | 18979.288 | 2.627215 | 0.00016604 | 408.036 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.24050511 | 54.44 | 82.22 | 27.78 | 494521.33 | 3.8379 | 3.915150 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 18979.29 | 18979.29 | 1.0000 | 2.74368389 | 2.627215 | 16.70 | 11.86 | 0.00800000 | 37036.7 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.16602215 | 60.00 | 32.22 | 27.78 | 0.000 | 18979.29 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.00 | 0.00761890 | 21.00 | 0.00761890 | 42.7428 | 6958.28 | 0.00 | 19084.87 | 19084.87 | 2.74368389 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 23.42 | 15.75 | 0.00800000 | 43890.7 | |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | DINING_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 19688.337 | 19688.337 | 2.754321 | 0.00017224 | 422.903 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.24050511 | 54.44 | 82.22 | 27.78 | 494521.33 | 3.9813 | 4.061417 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | Sensible | 19688.34 | 19688.34 | 1.0000 | 2.87642455 | 2.754321 | 16.70 | 11.86 | 0.00800000 | 37036.7 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.17222459 | 60.00 | 32.22 | 27.78 | 0.000 | 19688.34 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.00 | 0.00762527 | 21.00 | 0.00762527 | 42.7783 | 7085.83 | 0.00 | 19797.89 | 19797.89 | 2.87642455 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 23.35 | 15.72 | 0.00800000 | 43817.5 | |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | KITCHEN_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 13990.362 | 13990.362 | 2.621738 | 0.00012239 | 294.268 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.24050511 | 54.44 | 82.22 | 27.78 | 494521.33 | 2.8291 | 2.886008 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | Sensible | 13990.36 | 13990.36 | 1.0000 | 2.73796378 | 2.621738 | 16.70 | 11.86 | 0.00800000 | 37036.7 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.12238131 | 60.00 | 32.22 | 27.78 | 0.000 | 13990.36 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 20.53 | 0.00636664 | 21.00 | 0.00636664 | 35.7965 | 2031.68 | 0.00 | 14068.75 | 14068.75 | 2.73796378 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 21.64 | 15.09 | 0.00800000 | 42073.1 | |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | CORRIDOR_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11230.011 | 11230.011 | 0.840029 | 0.00009825 | 260.374 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.24050511 | 54.44 | 82.22 | 27.78 | 494521.33 | 2.2709 | 2.316588 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | Sensible | 11230.01 | 11230.01 | 1.0000 | 0.87726856 | 0.840029 | 16.70 | 11.86 | 0.00800000 | 37036.7 | 40.00 | 19.53 | 0.00800000 | 60796.0 | 0.09823502 | 60.00 | 32.22 | 27.78 | 0.000 | 11230.01 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.00 | 0.00768134 | 21.00 | 0.00768134 | 43.0887 | 7385.91 | 0.00 | 11290.09 | 11290.09 | 0.87726856 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 29.22 | 17.78 | 0.00800000 | 49804.3 | |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 729331.555 | -999.000 | 25.039179 | 0.02605003 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.6137 | 1004.8586 | 1.0443 | VAV WITH REHEAT FAN | Fan:VariableVolume | 25.039179 | 26.14920951 | 4197.9300 | 999.8980 | 36.83714336 | 13.37 | 6.70 | 6.67 | 1031447.13 | 70.7095 | 70.709544 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | Sensible | 729331.56 | 729331.55 | 1.0000 | 26.14920951 | 25.039179 | 38.10 | 18.17 | 0.00687148 | 55956.2 | 10.69 | 8.30 | 0.00687148 | 28065.1 | 26.04737592 | 6.70 | 13.37 | 6.67 | 56103.752 | 673227.80 | 38.10 | 0.00687148 | 18.17 | 25.03918000 | 100.0000 | 23.99 | 0.00961308 | 23.99 | 0.00961027 | 44.8090 | 298671.58 | 0.00 | 666374.53 | 666374.53 | 26.14920951 | 38.10 | 19.77 | 0.00687148 | 55956.2 | 13.06 | 10.53 | 0.00687148 | 30472.7 | |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 172635.014 | 172635.014 | 7.511754 | 0.00151029 | 2930.658 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | VAV WITH REHEAT FAN | Fan:VariableVolume | 25.039179 | 26.14920951 | 4197.9300 | 999.8980 | 4.24050511 | 54.44 | 82.22 | 27.78 | 494521.33 | 34.9095 | 35.612086 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 172635.01 | 172635.01 | 1.0000 | 7.84476285 | 7.511754 | -5.20 | -5.20 | 0.00280840 | 1771.3 | 16.70 | 11.86 | 0.00800000 | 37036.7 | 1.51013234 | 60.00 | 32.22 | 27.78 | 0.000 | 172635.01 | -5.20 | 0.00280840 | -5.20 | 25.03918000 | 333.3333 | 18.59 | 0.00689841 | 21.69 | 0.00613341 | 33.0624 | 67206.29 | 0.00 | 157216.12 | 157216.12 | 7.84476285 | 2.80 | 0.24 | 0.00280840 | 9851.8 | 22.64 | 10.36 | 0.00280840 | 29892.7 | |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 57348.723 | -999.000 | 2.051317 | 0.00204836 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.6137 | 1004.8586 | 1.0443 | FLR_3_DOAS FAN | Fan:ConstantVolume | 2.051245 | 2.14218037 | 4197.9300 | 999.8980 | 36.83714336 | 13.37 | 6.70 | 6.67 | 1031447.13 | 5.5600 | 5.560025 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | Sensible | 57348.72 | 57348.72 | 1.0000 | 2.14225568 | 2.051317 | 38.10 | 18.17 | 0.00687148 | 55956.2 | 11.79 | 8.78 | 0.00687148 | 29186.0 | 2.04815455 | 6.70 | 13.37 | 6.67 | 2195.006 | 55153.72 | 38.10 | 0.00687148 | 18.17 | 2.05124512 | 99.9965 | 21.11 | 0.00855189 | 21.11 | 0.00855905 | 47.6192 | 198032.57 | 0.00 | 51614.51 | 51614.51 | 2.14225568 | 38.10 | 19.77 | 0.00687148 | 55956.2 | 14.42 | 11.12 | 0.00687148 | 31862.7 | |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 14143.003 | 14143.003 | 0.615395 | 0.00012373 | 240.092 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | FLR_3_DOAS FAN | Fan:ConstantVolume | 2.051245 | 2.14218037 | 4197.9300 | 999.8980 | 4.24050511 | 54.44 | 82.22 | 27.78 | 494521.33 | 2.8599 | 2.917495 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 14143.00 | 14143.00 | 1.0000 | 0.64267671 | 0.615395 | -5.20 | -5.20 | 0.00280840 | 1771.3 | 16.70 | 11.86 | 0.00800000 | 37036.7 | 0.12371654 | 60.00 | 32.22 | 27.78 | 0.000 | 14143.00 | -5.20 | 0.00280840 | -5.20 | 2.05124512 | 333.3216 | 21.11 | 0.00741869 | 21.11 | 0.00741839 | 41.3487 | 115654.40 | 0.00 | 12879.82 | 12879.82 | 0.64267671 | 2.80 | 0.24 | 0.00280840 | 9851.8 | 22.64 | 10.36 | 0.00280840 | 29892.7 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:58:10
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
VAV WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 25.04 | 25.04 | - | |||
FLR_3_DOAS_OA_CONTROLLER | DifferentialDryBulb | 2.05 | 2.05 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
BASEMENT | VAV WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
RETAIL_1_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
RETAIL_2_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
MECH_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
STORAGE_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000610 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
LAUNDRY_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CAFE_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
LOBBY_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001448 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORRIDOR_FLR_3 | VAV WITH REHEAT_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
BANQUET_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
DINING_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
KITCHEN_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003556 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORRIDOR_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 728.33 | 8760.00 | 728.33 |
RETAIL_1_FLR_1 | 969.50 | 8644.67 | 943.83 |
RETAIL_2_FLR_1 | 53.50 | 8760.00 | 53.50 |
MECH_FLR_1 | 969.00 | 8760.00 | 969.00 |
STORAGE_FLR_1 | 1634.00 | 8760.00 | 1634.00 |
LAUNDRY_FLR_1 | 3719.67 | 4265.67 | 1103.33 |
CAFE_FLR_1 | 564.50 | 8636.00 | 541.17 |
LOBBY_FLR_1 | 213.67 | 8760.00 | 213.67 |
ROOM_1_FLR_3 | 1100.83 | 8146.33 | 982.67 |
ROOM_2_FLR_3 | 1937.17 | 8269.67 | 1861.50 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 849.67 | 8760.00 | 849.67 |
ROOM_5_FLR_3 | 952.00 | 8024.83 | 923.67 |
ROOM_6_FLR_3 | 1773.67 | 8127.00 | 1745.00 |
CORRIDOR_FLR_3 | 903.00 | 8760.00 | 903.00 |
ROOM_1_FLR_6 | 1907.67 | 7916.00 | 1557.17 |
ROOM_2_FLR_6 | 2645.67 | 8035.67 | 2381.50 |
ROOM_3_MULT9_FLR_6 | 692.83 | 8006.50 | 564.50 |
BANQUET_FLR_6 | 687.67 | 8450.33 | 594.33 |
DINING_FLR_6 | 781.67 | 8188.83 | 567.67 |
KITCHEN_FLR_6 | 6865.33 | 6689.17 | 5256.50 |
CORRIDOR_FLR_6 | 1356.00 | 8760.00 | 1356.00 |
Facility | 8020.00 | 8760.00 | 7386.50 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 1.67 | 0.00 | 1.67 |
ROOM_2_FLR_3 | 0.00 | 1.00 | 0.00 | 1.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 2.17 | 0.00 | 2.17 |
ROOM_5_FLR_3 | 0.00 | 0.67 | 0.00 | 0.67 |
ROOM_6_FLR_3 | 0.00 | 0.50 | 0.00 | 0.50 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 7.67 | 0.00 | 7.67 |
ROOM_2_FLR_6 | 0.00 | 5.00 | 0.00 | 5.00 |
ROOM_3_MULT9_FLR_6 | 0.00 | 6.17 | 0.00 | 6.17 |
BANQUET_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 0.00 | 13.67 | 0.00 | 13.67 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:58:10
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.80 | 106.50 | 4826.41 | 2.141 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.28 | 10.83 | 265.76 | 5.297 | 0.242 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.28 | 12.54 | 307.76 | 3.339 | 0.081 | 0.000 | 0.000 |
MECH_FLR_1 | 1.54 | 2.65 | 650.80 | 1.690 | 0.090 | 0.000 | 0.000 |
STORAGE_FLR_1 | 1.18 | 2.04 | 375.47 | 1.479 | 0.090 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.87 | 8.40 | 309.22 | 44.343 | 0.259 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.58 | 142.30 | 748.35 | 8.010 | 0.190 | 0.000 | 0.000 |
LOBBY_FLR_1 | 245.14 | 422.44 | 5183.56 | 3.819 | 0.078 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.472 | 0.314 | 0.000 | 0.055 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.472 | 0.314 | 0.000 | 0.055 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.536 | 0.139 | 0.000 | 0.087 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.472 | 0.314 | 0.000 | 0.055 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.472 | 0.314 | 0.000 | 0.055 |
CORRIDOR_FLR_3 | 12.16 | 20.96 | 1186.91 | 1.038 | 0.038 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.472 | 0.314 | 0.000 | 0.066 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.472 | 0.314 | 0.000 | 0.065 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.537 | 0.256 | 0.000 | 0.104 |
BANQUET_FLR_6 | 145.01 | 249.90 | 1010.89 | 9.466 | 0.090 | 0.000 | 0.000 |
DINING_FLR_6 | 145.01 | 249.90 | 1010.89 | 9.925 | 0.090 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.90 | 22.24 | 314.87 | 30.522 | 0.261 | 0.000 | 0.000 |
CORRIDOR_FLR_6 | 12.87 | 22.18 | 1256.16 | 2.430 | 0.064 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.80 | 106.50 | 4826.41 | 2.091 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.28 | 10.83 | 265.76 | 5.173 | 0.005 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.28 | 12.54 | 307.76 | 3.261 | 0.002 | 0.000 | 0.000 |
MECH_FLR_1 | 1.54 | 2.65 | 650.80 | 1.651 | 0.002 | 0.000 | 0.000 |
STORAGE_FLR_1 | 1.18 | 2.04 | 375.47 | 1.445 | 0.002 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.87 | 8.40 | 309.22 | 43.275 | 0.005 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.58 | 142.30 | 748.35 | 7.815 | 0.004 | 0.000 | 0.000 |
LOBBY_FLR_1 | 245.14 | 422.44 | 5183.56 | 3.727 | 0.002 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.460 | 0.006 | 0.000 | 0.000 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.459 | 0.006 | 0.000 | 0.000 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.523 | 0.003 | 0.000 | 0.000 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.461 | 0.006 | 0.000 | 0.000 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.459 | 0.006 | 0.000 | 0.000 |
CORRIDOR_FLR_3 | 12.16 | 20.96 | 1186.91 | 1.013 | 0.001 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.460 | 0.006 | 0.000 | 0.000 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.459 | 0.006 | 0.000 | 0.000 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.523 | 0.005 | 0.000 | 0.000 |
BANQUET_FLR_6 | 145.01 | 249.90 | 1010.89 | 9.224 | 0.002 | 0.000 | 0.000 |
DINING_FLR_6 | 145.01 | 249.90 | 1010.89 | 9.670 | 0.002 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.90 | 22.24 | 314.87 | 29.682 | 0.005 | 0.000 | 0.000 |
CORRIDOR_FLR_6 | 12.87 | 22.18 | 1256.16 | 2.373 | 0.001 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:58:10
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | VAV WITH REHEAT | 61.80 | 106.50 | 4826.41 | 1978.83 | 0.0000 | 0.854 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | 6.28 | 10.83 | 265.76 | 67.07 | 0.0000 | 0.079 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | 7.28 | 12.54 | 307.76 | 77.67 | 0.0000 | 0.092 |
MECH_FLR_1 | VAV WITH REHEAT | 1.54 | 2.65 | 650.80 | 164.24 | 0.0000 | 0.000 |
STORAGE_FLR_1 | VAV WITH REHEAT | 1.18 | 2.04 | 375.47 | 94.76 | 0.0000 | 0.058 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | 4.87 | 8.40 | 309.22 | 78.04 | 0.0000 | 0.000 |
CAFE_FLR_1 | VAV WITH REHEAT | 82.58 | 142.30 | 748.35 | 188.86 | 0.0000 | 0.676 |
LOBBY_FLR_1 | VAV WITH REHEAT | 245.14 | 422.44 | 5183.56 | 1308.19 | 0.0000 | 1.894 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.062 |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.062 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 1.50 | 74.75 | 24.52 | 0.0000 | 0.837 | |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 74.77 | 24.53 | 0.0000 | 0.837 |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.062 |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.062 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | 12.16 | 20.96 | 1186.91 | 389.40 | 0.0000 | 0.475 |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.015 |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.015 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 74.77 | 24.53 | 0.0000 | 0.099 |
BANQUET_FLR_6 | VAV WITH REHEAT | 145.01 | 249.90 | 1010.89 | 331.66 | 0.0000 | 1.188 |
DINING_FLR_6 | VAV WITH REHEAT | 145.01 | 249.90 | 1010.89 | 331.66 | 0.0000 | 1.188 |
KITCHEN_FLR_6 | VAV WITH REHEAT | 12.90 | 22.24 | 314.87 | 103.30 | 0.0000 | 0.367 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | 12.87 | 22.18 | 1256.16 | 412.12 | 0.0000 | 0.126 |
Total Facility | 873.39 | 1604.23 | 35184.81 | 11345.29 | 0.0000 | 137.584 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 89673608.61 | 0.00 | 89673608.61 | 0.00 | 89673608.61 | 26946214.98 | 0.00 | 0.00 | 8760.00 | 0.00 |
RETAIL_1_FLR_1 | 12217187.64 | 0.00 | 12217187.64 | 557686.98 | 12774874.62 | 2498216.28 | 0.00 | 0.00 | 8760.00 | 0.00 |
RETAIL_2_FLR_1 | 8917979.73 | 0.00 | 8917979.73 | 215267.88 | 9133247.61 | 2892943.94 | 0.00 | 0.00 | 8760.00 | 0.00 |
MECH_FLR_1 | 9549607.41 | 0.00 | 9549607.41 | 508765.38 | 10058372.79 | 0.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
STORAGE_FLR_1 | 4822916.34 | 0.00 | 4822916.34 | 293529.60 | 5116445.94 | 1821682.01 | 0.00 | 0.00 | 8760.00 | 0.00 |
LAUNDRY_FLR_1 | 0.12E+09 | 0.00 | 0.12E+09 | 694693.14 | 0.12E+09 | 0.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
CAFE_FLR_1 | 51964038.86 | 0.00 | 51964038.86 | 1232798.65 | 53196837.51 | 21330615.53 | 0.00 | 0.00 | 8760.00 | 0.00 |
LOBBY_FLR_1 | 0.17E+09 | 0.00 | 0.17E+09 | 3522387.32 | 0.18E+09 | 59728886.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
ROOM_1_FLR_3 | 1946875.62 | 56769.43 | 2003645.04 | 323697.46 | 2327342.51 | 1946875.62 | 0.00 | 7863.83 | 896.17 | 0.00 |
ROOM_2_FLR_3 | 1946647.51 | 56308.54 | 2002956.05 | 323672.77 | 2326628.82 | 1946647.51 | 0.00 | 7863.83 | 896.17 | 0.00 |
ROOM_3_MULT19_FLR_3 | 26397887.27 | 61287.72 | 26459174.99 | 90315.22 | 26549490.22 | 26397887.27 | 0.00 | 7930.00 | 830.00 | 8760.00 |
ROOM_4_MULT19_FLR_3 | 26405105.73 | 56209.41 | 26461315.13 | 90339.92 | 26551655.05 | 26405105.73 | 0.00 | 7958.49 | 801.51 | 0.00 |
ROOM_5_FLR_3 | 1946875.62 | 57017.46 | 2003893.08 | 323697.46 | 2327590.54 | 1946875.62 | 0.00 | 7864.00 | 896.00 | 0.00 |
ROOM_6_FLR_3 | 1946647.51 | 56543.92 | 2003191.43 | 323672.77 | 2326864.20 | 1946647.51 | 0.00 | 7864.00 | 896.00 | 0.00 |
CORRIDOR_FLR_3 | 42730889.48 | 0.00 | 42730889.48 | 391415.36 | 43122304.84 | 14972100.18 | 0.00 | 0.00 | 8760.00 | 0.00 |
ROOM_1_FLR_6 | 486718.90 | 67521.47 | 554240.37 | 323763.71 | 878004.08 | 486718.90 | 0.00 | 7860.33 | 899.67 | 0.00 |
ROOM_2_FLR_6 | 486661.88 | 66972.80 | 553634.68 | 323739.01 | 877373.69 | 486661.88 | 0.00 | 7860.33 | 899.67 | 0.00 |
ROOM_3_MULT9_FLR_6 | 3126920.42 | 67555.70 | 3194476.11 | 165648.85 | 3360124.96 | 3126920.42 | 0.00 | 7860.33 | 899.67 | 0.00 |
BANQUET_FLR_6 | 82850300.68 | 0.00 | 82850300.68 | 790549.61 | 83640850.30 | 37458366.31 | 0.00 | 0.00 | 8760.00 | 0.00 |
DINING_FLR_6 | 86858635.41 | 0.00 | 86858635.41 | 790549.61 | 87649185.02 | 37458366.31 | 0.00 | 0.00 | 8760.00 | 0.00 |
KITCHEN_FLR_6 | 82780804.70 | 0.00 | 82780804.70 | 707725.19 | 83488529.89 | 11584760.86 | 0.00 | 0.00 | 8760.00 | 0.00 |
CORRIDOR_FLR_6 | 26490647.96 | 0.00 | 26490647.96 | 692681.92 | 27183329.89 | 3961413.96 | 0.00 | 0.00 | 8760.00 | 0.00 |
Total Facility | 0.50E+10 | 10578834.65 | 0.50E+10 | 32619391.61 | 0.50E+10 | 0.43E+10 | 0.00 | 7996.51 | 8760.00 | 8760.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 2.8435 | 0.0000 | 2.8435 | 0.0000 | 2.8435 | 0.8545 | 0.00 | 0.00 | 8760.00 |
RETAIL_1_FLR_1 | 0.3874 | 0.0000 | 0.3874 | 0.0177 | 0.4051 | 0.0792 | 0.00 | 0.00 | 8760.00 |
RETAIL_2_FLR_1 | 0.2828 | 0.0000 | 0.2828 | 0.0068 | 0.2896 | 0.0917 | 0.00 | 0.00 | 8760.00 |
MECH_FLR_1 | 0.3028 | 0.0000 | 0.3028 | 0.0161 | 0.3189 | 0.0000 | 0.00 | 0.00 | 8760.00 |
STORAGE_FLR_1 | 0.1529 | 0.0000 | 0.1529 | 0.0093 | 0.1622 | 0.0578 | 0.00 | 0.00 | 8760.00 |
LAUNDRY_FLR_1 | 3.7713 | 0.0000 | 3.7713 | 0.0220 | 3.7934 | 0.0000 | 0.00 | 0.00 | 8760.00 |
CAFE_FLR_1 | 1.6478 | 0.0000 | 1.6478 | 0.0391 | 1.6869 | 0.6764 | 0.00 | 0.00 | 8760.00 |
LOBBY_FLR_1 | 5.4432 | 0.0000 | 5.4432 | 0.1117 | 5.5549 | 1.8940 | 0.00 | 0.00 | 8760.00 |
ROOM_1_FLR_3 | 0.0617 | 0.0018 | 0.0635 | 0.0103 | 0.0738 | 0.0617 | 0.00 | 7863.83 | 896.17 |
ROOM_2_FLR_3 | 0.0617 | 0.0018 | 0.0635 | 0.0103 | 0.0738 | 0.0617 | 0.00 | 7863.83 | 896.17 |
ROOM_4_MULT19_FLR_3 | 0.8373 | 0.0018 | 0.8391 | 0.0029 | 0.8419 | 0.8373 | 0.00 | 7958.49 | 801.51 |
ROOM_5_FLR_3 | 0.0617 | 0.0018 | 0.0635 | 0.0103 | 0.0738 | 0.0617 | 0.00 | 7864.00 | 896.00 |
ROOM_6_FLR_3 | 0.0617 | 0.0018 | 0.0635 | 0.0103 | 0.0738 | 0.0617 | 0.00 | 7864.00 | 896.00 |
CORRIDOR_FLR_3 | 1.3550 | 0.0000 | 1.3550 | 0.0124 | 1.3674 | 0.4748 | 0.00 | 0.00 | 8760.00 |
ROOM_1_FLR_6 | 0.0154 | 0.0021 | 0.0176 | 0.0103 | 0.0278 | 0.0154 | 0.00 | 7860.33 | 899.67 |
ROOM_2_FLR_6 | 0.0154 | 0.0021 | 0.0176 | 0.0103 | 0.0278 | 0.0154 | 0.00 | 7860.33 | 899.67 |
ROOM_3_MULT9_FLR_6 | 0.0992 | 0.0021 | 0.1013 | 0.0053 | 0.1065 | 0.0992 | 0.00 | 7860.33 | 899.67 |
BANQUET_FLR_6 | 2.6272 | 0.0000 | 2.6272 | 0.0251 | 2.6522 | 1.1878 | 0.00 | 0.00 | 8760.00 |
DINING_FLR_6 | 2.7543 | 0.0000 | 2.7543 | 0.0251 | 2.7793 | 1.1878 | 0.00 | 0.00 | 8760.00 |
KITCHEN_FLR_6 | 2.6250 | 0.0000 | 2.6250 | 0.0224 | 2.6474 | 0.3674 | 0.00 | 0.00 | 8760.00 |
CORRIDOR_FLR_6 | 0.8400 | 0.0000 | 0.8400 | 0.0220 | 0.8620 | 0.1256 | 0.00 | 0.00 | 8760.00 |
Total Facility | 94.6439 | 0.1878 | 94.8317 | 0.8167 | 95.6484 | 73.9670 | 0.00 | 7996.51 | 8760.00 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV WITH REHEAT | 0.86E+09 | 0.00 | 0.86E+09 | 0.22E+09 | 0.00 | 0.00 | 8760.00 | 0.00 |
FLR_3_DOAS | 70553146.19 | 546186.43 | 71099332.62 | 64690340.46 | 0.00 | 0.00 | 8760.00 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV WITH REHEAT | 27.3019 | 0.0000 | 27.3019 | 6.9969 | 0.00 | 0.00 | 8760.00 |
FLR_3_DOAS | 2.2372 | 0.0173 | 2.2545 | 2.0513 | 0.00 | 0.00 | 8760.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV WITH REHEAT | 0.00 | 789.85 | 0.00 | 0.00 | 7970.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FLR_3_DOAS | 0.00 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV WITH REHEAT | 0.0000 | 27.3380 | 0.0000 | 0.0000 | 27.3018 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
FLR_3_DOAS | 0.0000 | 2.2372 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:58:10
Surfaces by ClassTotal | Outdoors | |
Wall | 119 | 44 |
Floor | 25 | 0 |
Roof | 33 | 11 |
Internal Mass | 22 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 30 | 30 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 22 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 1304 |
Defaulted Fields | 1181 |
Fields with Defaults | 3925 |
Autosized Fields | 349 |
Autosizable Fields | 401 |
Autocalculated Fields | 280 |
Autocalculatable Fields | 539 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:58:10
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 9188.28 | 144339.86 | 15-NOV-03:50 | 570236.28 | 05-JUN-19:10 |
Electricity:Building | 2943.68 | 36656.90 | 02-JAN-02:10 | 182730.36 | 02-JAN-20:10 |
Electricity:Zone:BASEMENT | 315.54 | 3631.19 | 02-JAN-02:10 | 23630.80 | 02-JAN-20:10 |
Electricity:SpaceType:GENERAL | 2925.41 | 36182.64 | 02-JAN-02:10 | 182063.43 | 02-JAN-20:10 |
InteriorLights:Electricity | 1174.11 | 10291.59 | 02-JAN-02:10 | 93091.76 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BASEMENT | 165.29 | 1501.97 | 02-JAN-02:10 | 13517.00 | 02-JAN-20:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 1174.11 | 10291.59 | 02-JAN-02:10 | 93091.76 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity | 1174.11 | 10291.59 | 02-JAN-02:10 | 93091.76 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 165.29 | 1501.97 | 02-JAN-02:10 | 13517.00 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 1174.11 | 10291.59 | 02-JAN-02:10 | 93091.76 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_1_FLR_1 | 18.59 | 220.70 | 02-JAN-02:10 | 1372.90 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 8.40 | 76.37 | 02-JAN-02:10 | 687.30 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 8.40 | 76.37 | 02-JAN-02:10 | 687.30 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_2_FLR_1 | 21.53 | 255.58 | 02-JAN-02:10 | 1589.82 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 9.73 | 88.43 | 02-JAN-02:10 | 795.89 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 9.73 | 88.43 | 02-JAN-02:10 | 795.89 | 02-JAN-20:10 |
Electricity:Zone:MECH_FLR_1 | 30.66 | 342.02 | 02-JAN-02:10 | 2327.13 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:MECH_FLR_1 | 18.19 | 165.30 | 02-JAN-02:10 | 1487.69 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:MECH_FLR_1 | 18.19 | 165.30 | 02-JAN-02:10 | 1487.69 | 02-JAN-20:10 |
Electricity:Zone:STORAGE_FLR_1 | 6.94 | 81.32 | 02-JAN-02:10 | 515.26 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 3.34 | 30.34 | 02-JAN-02:10 | 273.10 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 3.34 | 30.34 | 02-JAN-02:10 | 273.10 | 02-JAN-20:10 |
Electricity:Zone:LAUNDRY_FLR_1 | 72.06 | 1000.18 | 02-JAN-02:10 | 4910.17 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 4.13 | 37.49 | 02-JAN-02:10 | 337.37 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 4.13 | 37.49 | 02-JAN-02:10 | 337.37 | 02-JAN-20:10 |
Electricity:Zone:CAFE_FLR_1 | 40.96 | 445.13 | 02-JAN-02:10 | 3142.50 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CAFE_FLR_1 | 26.62 | 241.91 | 02-JAN-02:10 | 2177.23 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CAFE_FLR_1 | 26.62 | 241.91 | 02-JAN-02:10 | 2177.23 | 02-JAN-20:10 |
Electricity:Zone:LOBBY_FLR_1 | 293.89 | 3428.00 | 02-JAN-02:10 | 21878.53 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 144.90 | 1316.59 | 02-JAN-02:10 | 11849.32 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 144.90 | 1316.59 | 02-JAN-02:10 | 11849.32 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_3 | 32.70 | 383.52 | 01-JAN-02:10 | 2308.42 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 20.41 | 172.80 | 01-JAN-02:10 | 1570.91 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 20.41 | 172.80 | 01-JAN-02:10 | 1570.91 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_3 | 32.70 | 383.47 | 01-JAN-02:10 | 2308.15 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 20.41 | 172.78 | 01-JAN-02:10 | 1570.72 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 20.41 | 172.78 | 01-JAN-02:10 | 1570.72 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT19_FLR_3 | 472.46 | 5984.83 | 01-JAN-02:10 | 32482.97 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 243.71 | 2063.36 | 01-JAN-02:10 | 18757.86 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 243.71 | 2063.36 | 01-JAN-02:10 | 18757.86 | 01-JAN-19:10 |
Electricity:Zone:ROOM_4_MULT19_FLR_3 | 472.59 | 5986.46 | 01-JAN-02:10 | 32491.86 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 243.77 | 2063.93 | 01-JAN-02:10 | 18762.99 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 243.77 | 2063.93 | 01-JAN-02:10 | 18762.99 | 01-JAN-19:10 |
Electricity:Zone:ROOM_5_FLR_3 | 32.70 | 383.52 | 01-JAN-02:10 | 2308.42 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 20.41 | 172.80 | 01-JAN-02:10 | 1570.91 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 20.41 | 172.80 | 01-JAN-02:10 | 1570.91 | 01-JAN-19:10 |
Electricity:Zone:ROOM_6_FLR_3 | 32.70 | 383.47 | 01-JAN-02:10 | 2308.15 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 20.41 | 172.78 | 01-JAN-02:10 | 1570.72 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 20.41 | 172.78 | 01-JAN-02:10 | 1570.72 | 01-JAN-19:10 |
Electricity:Zone:CORRIDOR_FLR_3 | 62.74 | 570.05 | 02-JAN-02:10 | 5130.41 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 62.74 | 570.05 | 02-JAN-02:10 | 5130.41 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 62.74 | 570.05 | 02-JAN-02:10 | 5130.41 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_6 | 8.18 | 95.88 | 01-JAN-02:10 | 577.11 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 5.10 | 43.20 | 01-JAN-02:10 | 392.73 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 5.10 | 43.20 | 01-JAN-02:10 | 392.73 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_6 | 8.17 | 95.87 | 01-JAN-02:10 | 577.04 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 5.10 | 43.19 | 01-JAN-02:10 | 392.68 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 5.10 | 43.19 | 01-JAN-02:10 | 392.68 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT9_FLR_6 | 55.96 | 708.92 | 01-JAN-02:10 | 3847.72 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 28.87 | 244.41 | 01-JAN-02:10 | 2221.93 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 28.87 | 244.41 | 01-JAN-02:10 | 2221.93 | 01-JAN-19:10 |
Electricity:Zone:BANQUET_FLR_6 | 222.61 | 2674.12 | 02-JAN-02:10 | 10571.30 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 46.75 | 424.82 | 02-JAN-02:10 | 3823.39 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 46.75 | 424.82 | 02-JAN-02:10 | 3823.39 | 02-JAN-20:10 |
Electricity:Zone:DINING_FLR_6 | 222.61 | 2674.12 | 02-JAN-02:10 | 10571.30 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:DINING_FLR_6 | 46.75 | 424.82 | 02-JAN-02:10 | 3823.39 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:DINING_FLR_6 | 46.75 | 424.82 | 02-JAN-02:10 | 3823.39 | 02-JAN-20:10 |
Electricity:Zone:KITCHEN_FLR_6 | 470.78 | 6777.71 | 02-JAN-02:10 | 19298.76 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 12.48 | 113.42 | 02-JAN-02:10 | 1020.78 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 12.48 | 113.42 | 02-JAN-02:10 | 1020.78 | 02-JAN-20:10 |
Electricity:Zone:CORRIDOR_FLR_6 | 16.60 | 150.83 | 02-JAN-02:10 | 1357.44 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 16.60 | 150.83 | 02-JAN-02:10 | 1357.44 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 16.60 | 150.83 | 02-JAN-02:10 | 1357.44 | 02-JAN-20:10 |
InteriorEquipment:Electricity | 1751.30 | 25891.05 | 02-JAN-02:10 | 89674.66 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 150.26 | 2129.22 | 02-JAN-02:10 | 10113.80 | 02-JAN-20:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 1751.30 | 25891.05 | 02-JAN-02:10 | 89674.66 | 02-JAN-07:10 |
MiscPlug:InteriorEquipment:Electricity | 959.56 | 15202.41 | 02-JAN-02:10 | 59492.27 | 02-JAN-07:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 150.26 | 2129.22 | 02-JAN-02:10 | 10113.80 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 959.56 | 15202.41 | 02-JAN-02:10 | 59492.27 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.79 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.79 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 12.29 | 210.72 | 01-JAN-00:10 | 948.23 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 12.29 | 210.72 | 01-JAN-00:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 12.29 | 210.69 | 01-JAN-00:10 | 948.12 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 12.29 | 210.69 | 01-JAN-00:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 228.75 | 3921.46 | 01-JAN-00:10 | 17646.57 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 228.75 | 3921.46 | 01-JAN-00:10 | 17646.57 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 228.82 | 3922.53 | 01-JAN-00:10 | 17651.40 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 228.82 | 3922.53 | 01-JAN-00:10 | 17651.40 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 12.29 | 210.72 | 01-JAN-00:10 | 948.23 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 12.29 | 210.72 | 01-JAN-00:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 12.29 | 210.69 | 01-JAN-00:10 | 948.12 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 12.29 | 210.69 | 01-JAN-00:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 3.07 | 52.68 | 01-JAN-00:10 | 237.06 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 3.07 | 52.68 | 01-JAN-00:10 | 237.06 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 3.07 | 52.67 | 01-JAN-00:10 | 237.03 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 3.07 | 52.67 | 01-JAN-00:10 | 237.03 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 27.10 | 464.51 | 01-JAN-00:10 | 2090.30 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 27.10 | 464.51 | 01-JAN-00:10 | 2090.30 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 440.03 | 6190.03 | 01-JAN-00:10 | 16686.59 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 410.33 | 5248.28 | 01-JAN-00:10 | 15744.84 | 01-JAN-07:10 |
ReachInFreezer:InteriorEquipment:Electricity | 16.27 | 515.92 | 01-JAN-00:10 | 515.92 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 16.27 | 515.92 | 01-JAN-00:10 | 515.92 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 16.27 | 515.92 | 01-JAN-00:10 | 515.92 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 13.43 | 425.83 | 01-JAN-00:10 | 425.83 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 13.43 | 425.83 | 01-JAN-00:10 | 425.83 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 13.43 | 425.83 | 01-JAN-00:10 | 425.83 | 01-JAN-00:10 |
Refrigeration:Electricity | 74.19 | 1239.15 | 19-DEC-23:30 | 3639.04 | 18-AUG-07:00 |
Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 18.27 | 261.51 | 02-JAN-11:30 | 2271.91 | 01-JAN-11:10 |
General:Refrigeration:Electricity | 18.27 | 261.51 | 02-JAN-11:30 | 2271.91 | 01-JAN-11:10 |
General:Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 18.27 | 261.51 | 02-JAN-11:30 | 2271.91 | 01-JAN-11:10 |
Electricity:Plant | 2689.87 | 2868.48 | 16-DEC-03:00 | 266085.86 | 14-JUN-18:10 |
LowTempRefrigeration:Refrigeration:Electricity | 22.42 | 0.00 | 01-JAN-11:10 | 1894.02 | 08-JUN-10:50 |
MedTempRefrigeration:Refrigeration:Electricity | 33.50 | 935.73 | 18-DEC-03:10 | 1196.70 | 19-JUL-13:10 |
Fans:Electricity | 2048.85 | 59047.52 | 09-OCT-05:10 | 87624.42 | 27-AUG-18:20 |
Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Electricity:HVAC | 2645.52 | 60927.78 | 11-DEC-11:50 | 107135.08 | 27-AUG-18:20 |
ExteriorEquipment:Electricity | 679.68 | 10574.27 | 02-JAN-02:20 | 40537.60 | 02-JAN-07:20 |
Transformer:ExteriorEquipment:Electricity | 32.92 | 556.27 | 02-JAN-02:20 | 1912.91 | 02-JAN-21:10 |
ElectricityPurchased:Facility | 9188.28 | 144339.86 | 15-NOV-03:50 | 570236.28 | 05-JUN-19:10 |
ElectricityPurchased:Plant | 9188.28 | 144339.86 | 15-NOV-03:50 | 570236.28 | 05-JUN-19:10 |
Cogeneration:ElectricityPurchased | 9188.28 | 144339.86 | 15-NOV-03:50 | 570236.28 | 05-JUN-19:10 |
General:Cogeneration:ElectricityPurchased | 9188.28 | 144339.86 | 15-NOV-03:50 | 570236.28 | 05-JUN-19:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 9188.28 | 144339.86 | 15-NOV-03:50 | 570236.28 | 05-JUN-19:10 |
ElectricityNet:Plant | 9188.28 | 144339.86 | 15-NOV-03:50 | 570236.28 | 05-JUN-19:10 |
Cogeneration:ElectricityNet | 9188.28 | 144339.86 | 15-NOV-03:50 | 570236.28 | 05-JUN-19:10 |
General:Cogeneration:ElectricityNet | 9188.28 | 144339.86 | 15-NOV-03:50 | 570236.28 | 05-JUN-19:10 |
General:Fans:Electricity | 2048.85 | 59047.52 | 09-OCT-05:10 | 87624.42 | 27-AUG-18:20 |
ExteriorLights:Electricity | 262.44 | 0.00 | 01-JAN-07:20 | 16690.39 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 262.44 | 0.00 | 01-JAN-07:20 | 16690.39 | 01-JAN-00:10 |
ElevatorLift:ExteriorEquipment:Electricity | 616.11 | 9046.01 | 01-JAN-00:10 | 37691.69 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 30.65 | 972.00 | 01-JAN-00:10 | 972.00 | 01-JAN-00:10 |
HeatRecovery:Electricity | 563.76 | 0.00 | 01-JAN-11:50 | 18015.63 | 01-JAN-08:10 |
General:HeatRecovery:Electricity | 563.76 | 0.00 | 01-JAN-11:50 | 18015.63 | 01-JAN-08:10 |
WaterSystems:Electricity | 90.78 | 1087.01 | 08-JUN-00:30 | 4739.27 | 28-MAR-06:10 |
Water Heater:WaterSystems:Electricity | 90.78 | 1087.01 | 08-JUN-00:30 | 4739.27 | 28-MAR-06:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 2289.50 | 0.00 | 01-JAN-03:20 | 247961.71 | 14-JUN-18:10 |
General:Cooling:Electricity | 2289.50 | 0.00 | 01-JAN-03:20 | 247961.71 | 14-JUN-18:10 |
Pumps:Electricity | 253.67 | 210.95 | 30-NOV-18:10 | 13002.53 | 21-JUN-16:40 |
General:Pumps:Electricity | 253.67 | 210.95 | 30-NOV-18:10 | 13002.53 | 21-JUN-16:40 |
WIRED_LTG_ELECTRICITY | 41.33 | 0.00 | 01-JAN-00:10 | 3276.83 | 02-JAN-20:20 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 5931.18 | 41863.85 | 03-JUL-23:30 | 467500.63 | 26-DEC-17:20 |
NaturalGas:Building | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
NaturalGas:SpaceType:GENERAL | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:NaturalGas | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
InteriorEquipment:NaturalGas:SpaceType:GENERAL | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
Laundry:InteriorEquipment:NaturalGas | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
NaturalGas:Plant | 4142.35 | 18762.35 | 06-AUG-06:30 | 377888.41 | 26-DEC-17:20 |
WaterSystems:NaturalGas | 2927.15 | 18467.44 | 01-JAN-16:10 | 251113.69 | 09-FEB-22:00 |
Water Heater:WaterSystems:NaturalGas | 2927.15 | 18467.44 | 01-JAN-16:10 | 251113.69 | 09-FEB-22:00 |
Heating:NaturalGas | 1215.20 | 0.00 | 03-APR-21:10 | 201630.34 | 03-FEB-07:10 |
Boiler:Heating:NaturalGas | 1215.20 | 0.00 | 03-APR-21:10 | 201630.34 | 03-FEB-07:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 6886.93 | 0.00 | 01-JAN-03:20 | 857575.87 | 20-JUL-20:40 |
PlantLoopCoolingDemand:HVAC | 6886.93 | 0.00 | 01-JAN-03:20 | 857575.87 | 20-JUL-20:40 |
CoolingCoils:PlantLoopCoolingDemand | 6886.93 | 0.00 | 01-JAN-03:20 | 857575.87 | 20-JUL-20:40 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-21:10 |
Water:Plant | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-21:10 |
WaterSystems:Water | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-21:10 |
Water Heater:WaterSystems:Water | 5742.51 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-19:10 |
MainsWater:Facility | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-21:10 |
MainsWater:Plant | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-21:10 |
WaterSystems:MainsWater | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-21:10 |
Water Heater:WaterSystems:MainsWater | 5742.51 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-19:10 |
WaterUse:WaterSystems:Water | 4114.69 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-07:10 |
WaterUse:WaterSystems:MainsWater | 4114.69 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-07:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 35415.04 | 227247.64 | 30-NOV-11:10 | 3307153.34 | 21-JUL-18:10 |
EnergyTransfer:Building | 6409.92 | 89781.84 | 15-JAN-16:00 | 409787.14 | 15-JUN-18:10 |
EnergyTransfer:Zone:KITCHEN_FLR_6 | 753.34 | 11107.20 | 27-DEC-04:00 | 36022.36 | 02-JUL-10:40 |
Refrigeration:EnergyTransfer | 186.18 | 3693.59 | 19-DEC-23:30 | 10357.17 | 18-AUG-07:00 |
Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 93.09 | 1846.79 | 19-DEC-23:30 | 5178.59 | 18-AUG-07:00 |
General:Refrigeration:EnergyTransfer | 93.09 | 1846.79 | 19-DEC-23:30 | 5178.59 | 18-AUG-07:00 |
General:Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 93.09 | 1846.79 | 19-DEC-23:30 | 5178.59 | 18-AUG-07:00 |
EnergyTransfer:Plant | 18047.26 | 49330.48 | 17-FEB-23:20 | 1979418.87 | 20-JUL-20:40 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 25.69 | 0.00 | 01-JAN-11:10 | 2686.44 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 67.40 | 1757.20 | 18-DEC-03:10 | 2540.09 | 19-JUL-13:10 |
EnergyTransfer:Zone:BASEMENT | 469.86 | 6817.62 | 27-MAR-11:00 | 23494.62 | 07-AUG-18:10 |
Heating:EnergyTransfer | 50.88 | 0.00 | 01-JAN-08:30 | 55935.33 | 26-DEC-16:10 |
Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer | 50.88 | 0.00 | 01-JAN-08:30 | 55935.33 | 26-DEC-16:10 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer | 6265.96 | 86144.95 | 15-JAN-16:00 | 406143.54 | 15-JUN-18:10 |
Cooling:EnergyTransfer:Zone:BASEMENT | 469.86 | 6817.62 | 27-MAR-11:00 | 23494.62 | 07-AUG-18:10 |
General:Cooling:EnergyTransfer | 6265.96 | 86144.95 | 15-JAN-16:00 | 406143.54 | 15-JUN-18:10 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 469.86 | 6817.62 | 27-MAR-11:00 | 23494.62 | 07-AUG-18:10 |
EnergyTransfer:Zone:RETAIL_1_FLR_1 | 51.47 | 0.00 | 30-DEC-00:20 | 3521.49 | 05-OCT-10:40 |
Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 0.51 | 0.00 | 01-JAN-00:10 | 1056.41 | 27-DEC-07:30 |
General:Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 0.51 | 0.00 | 01-JAN-00:10 | 1056.41 | 27-DEC-07:30 |
Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 50.97 | 0.00 | 02-JAN-04:00 | 3521.49 | 05-OCT-10:40 |
General:Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 50.97 | 0.00 | 02-JAN-04:00 | 3521.49 | 05-OCT-10:40 |
EnergyTransfer:Zone:RETAIL_2_FLR_1 | 44.81 | 316.40 | 26-DEC-11:30 | 2412.53 | 15-JUN-18:10 |
Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 44.81 | 316.40 | 26-DEC-11:30 | 2412.53 | 15-JUN-18:10 |
General:Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 44.81 | 316.40 | 26-DEC-11:30 | 2412.53 | 15-JUN-18:10 |
EnergyTransfer:Zone:MECH_FLR_1 | 36.36 | 0.06 | 26-DEC-02:30 | 2585.15 | 03-JUL-18:10 |
Heating:EnergyTransfer:Zone:MECH_FLR_1 | 0.05 | 0.00 | 01-JAN-00:10 | 341.56 | 27-DEC-05:00 |
General:Heating:EnergyTransfer:Zone:MECH_FLR_1 | 0.05 | 0.00 | 01-JAN-00:10 | 341.56 | 27-DEC-05:00 |
Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 36.31 | 0.00 | 05-JAN-04:30 | 2585.15 | 03-JUL-18:10 |
General:Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 36.31 | 0.00 | 05-JAN-04:30 | 2585.15 | 03-JUL-18:10 |
EnergyTransfer:Zone:STORAGE_FLR_1 | 15.68 | 0.01 | 03-MAR-02:00 | 1282.09 | 03-JUL-18:10 |
Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 0.27 | 0.00 | 01-JAN-00:10 | 293.07 | 28-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 0.27 | 0.00 | 01-JAN-00:10 | 293.07 | 28-JAN-07:10 |
Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 15.41 | 0.00 | 02-JAN-02:20 | 1282.09 | 03-JUL-18:10 |
General:Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 15.41 | 0.00 | 02-JAN-02:20 | 1282.09 | 03-JUL-18:10 |
EnergyTransfer:Zone:LAUNDRY_FLR_1 | 613.72 | 8717.33 | 27-DEC-05:00 | 38342.34 | 15-JUN-20:00 |
Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 613.72 | 8717.33 | 27-DEC-05:00 | 38342.34 | 15-JUN-20:00 |
General:Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 613.72 | 8717.33 | 27-DEC-05:00 | 38342.34 | 15-JUN-20:00 |
EnergyTransfer:Zone:CAFE_FLR_1 | 290.74 | 833.66 | 27-DEC-07:30 | 14018.07 | 03-JUL-18:10 |
Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 290.74 | 833.66 | 27-DEC-07:30 | 14018.07 | 03-JUL-18:10 |
General:Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 290.74 | 833.66 | 27-DEC-07:30 | 14018.07 | 03-JUL-18:10 |
EnergyTransfer:Zone:LOBBY_FLR_1 | 969.10 | 8409.06 | 26-DEC-11:30 | 46418.08 | 03-JUL-18:10 |
Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 969.10 | 8409.06 | 26-DEC-11:30 | 46418.08 | 03-JUL-18:10 |
General:Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 969.10 | 8409.06 | 26-DEC-11:30 | 46418.08 | 03-JUL-18:10 |
EnergyTransfer:Zone:ROOM_1_FLR_3 | 78.26 | 0.06 | 09-FEB-21:40 | 12077.92 | 15-JUN-18:10 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 5.85 | 0.00 | 01-JAN-08:10 | 4502.53 | 26-DEC-16:10 |
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 5.85 | 0.00 | 01-JAN-08:10 | 4502.53 | 26-DEC-16:10 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 72.41 | 0.00 | 01-JAN-00:10 | 12077.92 | 15-JUN-18:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 72.41 | 0.00 | 01-JAN-00:10 | 12077.92 | 15-JUN-18:10 |
EnergyTransfer:Zone:ROOM_2_FLR_3 | 72.80 | 0.11 | 02-MAR-16:50 | 12360.10 | 15-JUN-18:10 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 9.35 | 0.00 | 01-JAN-08:10 | 4815.25 | 27-DEC-09:10 |
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 9.35 | 0.00 | 01-JAN-08:10 | 4815.25 | 27-DEC-09:10 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 63.45 | 0.00 | 01-JAN-00:10 | 12360.10 | 15-JUN-18:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 63.45 | 0.00 | 01-JAN-00:10 | 12360.10 | 15-JUN-18:10 |
EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 641.98 | 20.04 | 27-DEC-06:00 | 55907.49 | 22-OCT-13:20 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 20.04 | 27-DEC-06:00 |
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 20.04 | 27-DEC-06:00 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 641.98 | 0.00 | 27-DEC-06:00 | 55907.49 | 22-OCT-13:20 |
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 641.98 | 0.00 | 27-DEC-06:00 | 55907.49 | 22-OCT-13:20 |
EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 612.87 | 0.71 | 29-MAR-05:00 | 80588.28 | 15-JUN-18:20 |
Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 7.21 | 0.00 | 01-JAN-00:10 | 27822.40 | 26-DEC-16:10 |
General:Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 7.21 | 0.00 | 01-JAN-00:10 | 27822.40 | 26-DEC-16:10 |
Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 605.66 | 0.00 | 02-JAN-05:40 | 80588.28 | 15-JUN-18:20 |
General:Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 605.66 | 0.00 | 02-JAN-05:40 | 80588.28 | 15-JUN-18:20 |
EnergyTransfer:Zone:ROOM_5_FLR_3 | 79.05 | 0.02 | 11-DEC-22:00 | 10130.11 | 15-JUN-08:10 |
Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 5.93 | 0.00 | 01-JAN-08:10 | 4500.43 | 26-DEC-16:10 |
General:Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 5.93 | 0.00 | 01-JAN-08:10 | 4500.43 | 26-DEC-16:10 |
Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 73.12 | 0.00 | 01-JAN-00:10 | 10130.11 | 15-JUN-08:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 73.12 | 0.00 | 01-JAN-00:10 | 10130.11 | 15-JUN-08:10 |
EnergyTransfer:Zone:ROOM_6_FLR_3 | 73.14 | 0.15 | 10-MAR-23:50 | 10266.20 | 15-JUN-08:10 |
Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 9.20 | 0.00 | 01-JAN-08:10 | 4535.07 | 26-DEC-16:10 |
General:Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 9.20 | 0.00 | 01-JAN-08:10 | 4535.07 | 26-DEC-16:10 |
Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 63.93 | 0.00 | 01-JAN-00:10 | 10266.20 | 15-JUN-08:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 63.93 | 0.00 | 01-JAN-00:10 | 10266.20 | 15-JUN-08:10 |
EnergyTransfer:Zone:CORRIDOR_FLR_3 | 231.17 | 0.12 | 28-NOV-15:00 | 12977.56 | 15-JUN-18:10 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 0.06 | 0.00 | 01-JAN-00:10 | 1804.88 | 27-DEC-07:30 |
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 0.06 | 0.00 | 01-JAN-00:10 | 1804.88 | 27-DEC-07:30 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 231.12 | 0.00 | 15-JAN-13:20 | 12977.56 | 15-JUN-18:10 |
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 231.12 | 0.00 | 15-JAN-13:20 | 12977.56 | 15-JUN-18:10 |
EnergyTransfer:Zone:ROOM_1_FLR_6 | 22.60 | 0.03 | 18-JAN-20:50 | 3399.15 | 15-JUN-15:10 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 2.62 | 0.00 | 01-JAN-08:10 | 1378.34 | 27-DEC-06:00 |
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 2.62 | 0.00 | 01-JAN-08:10 | 1378.34 | 27-DEC-06:00 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 19.98 | 0.00 | 01-JAN-00:10 | 3399.15 | 15-JUN-15:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 19.98 | 0.00 | 01-JAN-00:10 | 3399.15 | 15-JUN-15:10 |
EnergyTransfer:Zone:ROOM_2_FLR_6 | 21.54 | 0.04 | 22-FEB-23:50 | 3458.39 | 15-JUN-18:10 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 3.85 | 0.00 | 01-JAN-08:10 | 1459.78 | 27-DEC-09:10 |
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 3.85 | 0.00 | 01-JAN-08:10 | 1459.78 | 27-DEC-09:10 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 17.69 | 0.00 | 01-JAN-00:10 | 3458.39 | 15-JUN-18:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 17.69 | 0.00 | 01-JAN-00:10 | 3458.39 | 15-JUN-18:10 |
EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 127.96 | 0.07 | 12-JAN-03:50 | 16505.55 | 01-OCT-15:10 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 4.22 | 0.00 | 01-JAN-00:10 | 5777.37 | 26-DEC-16:10 |
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 4.22 | 0.00 | 01-JAN-00:10 | 5777.37 | 26-DEC-16:10 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 123.74 | 0.00 | 01-JAN-04:00 | 16505.55 | 01-OCT-15:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 123.74 | 0.00 | 01-JAN-04:00 | 16505.55 | 01-OCT-15:10 |
EnergyTransfer:Zone:BANQUET_FLR_6 | 528.87 | 7926.12 | 27-DEC-09:20 | 24154.65 | 15-JUN-18:10 |
Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 528.87 | 7926.12 | 27-DEC-09:20 | 24154.65 | 15-JUN-18:10 |
General:Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 528.87 | 7926.12 | 27-DEC-09:20 | 24154.65 | 15-JUN-18:10 |
EnergyTransfer:Zone:DINING_FLR_6 | 565.57 | 9107.61 | 27-DEC-09:20 | 25543.76 | 15-JUN-18:10 |
Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 565.57 | 9107.61 | 27-DEC-09:20 | 25543.76 | 15-JUN-18:10 |
General:Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 565.57 | 9107.61 | 27-DEC-09:20 | 25543.76 | 15-JUN-18:10 |
Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 660.25 | 8947.94 | 27-DEC-04:00 | 30945.42 | 02-JUL-10:40 |
General:Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 660.25 | 8947.94 | 27-DEC-04:00 | 30945.42 | 02-JUL-10:40 |
EnergyTransfer:Zone:CORRIDOR_FLR_6 | 109.03 | 0.04 | 06-NOV-03:50 | 7752.60 | 03-JUL-10:40 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 1.76 | 0.00 | 01-JAN-00:10 | 2683.58 | 27-DEC-07:30 |
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 1.76 | 0.00 | 01-JAN-00:10 | 2683.58 | 27-DEC-07:30 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 107.28 | 0.00 | 01-JAN-05:40 | 7752.60 | 03-JUL-10:40 |
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 107.28 | 0.00 | 01-JAN-05:40 | 7752.60 | 03-JUL-10:40 |
PlantLoopHeatingDemand:Facility | 1467.40 | 10109.53 | 04-JUL-00:10 | 208609.57 | 03-FEB-07:10 |
PlantLoopHeatingDemand:Plant | 648.50 | 7205.75 | 31-JUL-01:10 | 50235.57 | 30-JAN-07:10 |
WaterSystems:PlantLoopHeatingDemand | 648.50 | 7205.75 | 31-JUL-01:10 | 50235.57 | 30-JAN-07:10 |
General:WaterSystems:PlantLoopHeatingDemand | 648.50 | 7205.75 | 31-JUL-01:10 | 50235.57 | 30-JAN-07:10 |
EnergyTransfer:HVAC | 10957.86 | 21104.68 | 15-DEC-23:40 | 1167960.96 | 20-JUL-15:20 |
HeatingCoils:EnergyTransfer | 818.90 | 0.00 | 03-APR-21:10 | 158410.10 | 03-FEB-07:10 |
PlantLoopHeatingDemand:HVAC | 818.90 | 0.00 | 03-APR-21:10 | 158410.10 | 03-FEB-07:10 |
HeatingCoils:PlantLoopHeatingDemand | 818.90 | 0.00 | 03-APR-21:10 | 158410.10 | 03-FEB-07:10 |
CoolingCoils:EnergyTransfer | 6886.93 | 0.00 | 01-JAN-03:20 | 857575.87 | 20-JUL-20:40 |
HeatRecoveryForHeating:EnergyTransfer | 1962.95 | 0.00 | 01-JAN-11:30 | 554643.66 | 03-FEB-07:00 |
HeatRecoveryForCooling:EnergyTransfer | 1289.08 | 0.00 | 01-JAN-00:10 | 382257.13 | 21-JUL-18:00 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:EnergyTransfer | 648.50 | 7205.75 | 31-JUL-01:10 | 50235.57 | 30-JAN-07:10 |
WaterUse:WaterSystems:EnergyTransfer | 648.50 | 7205.75 | 31-JUL-01:10 | 50235.57 | 30-JAN-07:10 |
Boilers:EnergyTransfer | 812.02 | 0.00 | 03-APR-21:10 | 155354.24 | 03-FEB-07:10 |
Chillers:EnergyTransfer | 7102.07 | 0.00 | 01-JAN-03:20 | 865326.82 | 20-JUL-20:40 |
HeatRejection:EnergyTransfer | 9391.57 | 0.00 | 01-JAN-03:20 | 1081774.12 | 20-JUL-20:40 |
General:HeatRejection:EnergyTransfer | 9391.57 | 0.00 | 01-JAN-03:20 | 1081774.12 | 20-JUL-20:40 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:58:10
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 0.000 | -469.861 | 0.000 | 0.000 | 157.405 | 165.288 | 150.255 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -3.087 |
RETAIL_1_FLR_1 | 0.000 | 0.000 | 0.507 | -50.966 | 0.000 | 0.000 | 16.105 | 8.404 | 10.186 | 25.117 | 0.000 | 1.364 | 0.267 | 0.000 | -7.586 | 0.000 | -3.399 | -0.000 |
RETAIL_2_FLR_1 | 0.000 | 0.000 | 0.000 | -44.813 | 0.000 | 0.000 | 18.568 | 9.732 | 11.795 | 0.000 | 0.000 | 0.527 | 5.501 | 0.000 | 0.000 | 0.000 | -1.310 | -0.000 |
MECH_FLR_1 | 0.000 | 0.000 | 0.054 | -36.306 | 0.000 | 0.000 | 3.948 | 18.192 | 12.471 | 0.000 | 0.000 | 1.269 | 3.452 | 0.000 | 0.000 | 0.000 | -3.080 | -0.000 |
STORAGE_FLR_1 | 0.000 | 0.000 | 0.265 | -15.410 | 0.000 | 0.000 | 3.042 | 3.340 | 3.598 | 0.000 | 0.000 | 0.739 | 6.202 | 0.000 | 0.000 | 0.000 | -1.776 | -0.000 |
LAUNDRY_FLR_1 | 0.000 | 0.000 | 0.000 | -613.724 | 0.000 | 0.000 | 12.209 | 4.125 | 658.131 | 0.000 | 0.000 | 1.651 | 0.000 | 0.000 | 0.000 | 0.000 | -4.385 | -58.007 |
CAFE_FLR_1 | 0.000 | 0.000 | 0.000 | -290.740 | 0.000 | 0.000 | 209.432 | 26.624 | 14.341 | 70.268 | 0.000 | 2.941 | 0.003 | 0.000 | -21.756 | 0.000 | -7.575 | -3.534 |
LOBBY_FLR_1 | 0.000 | 0.000 | 0.000 | -969.106 | 0.000 | 0.000 | 619.925 | 144.896 | 148.998 | 93.713 | 0.000 | 8.454 | 3.607 | 0.000 | -28.774 | 0.000 | -21.712 | -0.001 |
ROOM_1_FLR_3 | 9.207 | -59.259 | 0.000 | -16.504 | 0.000 | 0.000 | 9.679 | 20.410 | 12.292 | 51.205 | 0.000 | 2.908 | 0.001 | 0.000 | -18.013 | 0.000 | -8.629 | -3.296 |
ROOM_2_FLR_3 | 13.390 | -51.274 | 0.000 | -16.214 | 0.000 | 0.000 | 9.711 | 20.407 | 12.291 | 38.872 | 0.000 | 2.916 | 0.000 | 0.000 | -18.589 | 0.000 | -8.428 | -3.081 |
ROOM_3_MULT19_FLR_3 | 0.145 | -375.604 | 0.000 | -266.514 | 0.000 | 0.000 | 0.000 | 243.708 | 228.754 | 287.211 | 0.000 | 11.422 | 51.453 | 0.000 | -111.838 | 0.000 | -68.737 | -0.002 |
ROOM_4_MULT19_FLR_3 | 35.439 | -414.002 | 0.000 | -219.885 | 0.000 | 0.000 | 184.480 | 243.774 | 228.817 | 102.185 | 0.000 | 17.316 | 0.001 | 0.000 | -102.859 | 0.000 | -51.448 | -23.817 |
ROOM_5_FLR_3 | 9.155 | -59.742 | 0.000 | -16.596 | 0.000 | 0.000 | 9.667 | 20.410 | 12.292 | 51.232 | 0.000 | 2.901 | 0.002 | 0.000 | -17.318 | 0.000 | -8.698 | -3.303 |
ROOM_6_FLR_3 | 13.150 | -51.580 | 0.000 | -16.301 | 0.000 | 0.000 | 9.701 | 20.407 | 12.291 | 38.319 | 0.000 | 2.904 | 0.002 | 0.000 | -17.320 | 0.000 | -8.490 | -3.081 |
CORRIDOR_FLR_3 | 0.000 | 0.000 | 0.057 | -231.116 | 0.000 | 0.000 | 122.917 | 62.736 | 0.000 | 46.231 | 0.000 | 3.512 | 26.934 | 0.000 | -21.648 | 0.000 | -9.623 | -0.001 |
ROOM_1_FLR_6 | 3.567 | -16.815 | 0.000 | -4.115 | 0.000 | 0.000 | 2.421 | 5.102 | 3.073 | 12.656 | 0.000 | 0.723 | 0.031 | 0.000 | -4.461 | 0.000 | -2.184 | -0.000 |
ROOM_2_FLR_6 | 4.952 | -14.749 | 0.000 | -4.043 | 0.000 | 0.000 | 2.429 | 5.102 | 3.073 | 9.600 | 0.000 | 0.724 | 0.000 | 0.000 | -4.593 | 0.000 | -2.132 | -0.361 |
ROOM_3_MULT9_FLR_6 | 8.164 | -100.837 | 0.000 | -26.840 | 0.000 | 0.000 | 21.722 | 28.868 | 27.097 | 63.769 | 0.000 | 3.479 | 6.241 | 0.000 | -20.759 | 0.000 | -10.903 | -0.002 |
BANQUET_FLR_6 | 0.000 | 0.000 | 0.000 | -528.872 | 0.000 | 0.000 | 358.630 | 46.753 | 175.857 | 11.654 | 0.000 | 1.754 | 0.000 | 0.000 | -12.523 | 0.000 | -5.087 | -48.166 |
DINING_FLR_6 | 0.000 | 0.000 | 0.000 | -565.570 | 0.000 | 0.000 | 357.455 | 46.753 | 175.857 | 11.374 | 0.000 | 1.731 | 0.001 | 0.000 | -12.879 | 0.000 | -5.112 | -9.610 |
KITCHEN_FLR_6 | 0.000 | 0.000 | 0.000 | -660.243 | 0.000 | 0.000 | 30.427 | 12.482 | 556.656 | 23.593 | 0.000 | 1.109 | 50.779 | 0.000 | -9.676 | 0.000 | -5.127 | 0.000 |
CORRIDOR_FLR_6 | 0.000 | 0.000 | 1.758 | -107.276 | 0.000 | 0.000 | 32.932 | 16.599 | 0.000 | 22.468 | 0.000 | 1.640 | 45.623 | 0.000 | -9.506 | 0.000 | -4.237 | -0.000 |
Total Facility | 97.170 | -1143.863 | 2.641 | -5171.016 | 0.000 | 0.000 | 2192.805 | 1174.112 | 2458.123 | 959.466 | 0.000 | 71.984 | 200.103 | 0.000 | -440.097 | 0.000 | -242.073 | -159.350 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 17-SEP-10:35 | 0.00 | 0.00 | 0.00 | -23757.84 | 0.00 | 0.00 | 2617.70 | 4505.72 | 4258.44 | 0.00 | 0.00 | 0.00 | 12375.97 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 05-OCT-10:35 | 0.00 | 0.00 | 0.00 | -3560.78 | 0.00 | 0.00 | 167.69 | 190.92 | 252.59 | 3980.61 | 0.00 | 100.09 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1131.11 |
RETAIL_2_FLR_1 | 15-JUN-18:10 | 0.00 | 0.00 | 0.00 | -2435.52 | 0.00 | 0.00 | 724.37 | 707.46 | 752.15 | 0.00 | 0.00 | 99.56 | 151.99 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 03-JUL-18:10 | 0.00 | 0.00 | 0.00 | -2596.17 | 0.00 | 0.00 | 152.60 | 1322.39 | 795.27 | 0.00 | 0.00 | 242.20 | 83.71 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 03-JUL-18:10 | 0.00 | 0.00 | 0.00 | -1284.50 | 0.00 | 0.00 | 118.04 | 242.76 | 229.41 | 0.00 | 0.00 | 141.26 | 553.03 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 15-JUN-20:00 | 0.00 | 0.00 | 0.00 | -38341.71 | 0.00 | 0.00 | 424.17 | 337.37 | 44299.38 | 0.00 | 0.00 | 228.89 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -6948.10 |
CAFE_FLR_1 | 17-SEP-10:35 | 0.00 | 0.00 | 0.00 | -14200.64 | 0.00 | 0.00 | 3421.14 | 725.74 | 406.43 | 9556.34 | 0.00 | 325.62 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -234.63 |
LOBBY_FLR_1 | 03-JUL-18:10 | 0.00 | 0.00 | 0.00 | -46890.09 | 0.00 | 0.00 | 24441.73 | 10532.73 | 9501.36 | 2880.71 | 0.00 | 1673.71 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2140.14 |
ROOM_1_FLR_3 | 01-OCT-15:01 | 0.00 | -14947.63 | 0.00 | -639.54 | 0.00 | 0.00 | 130.72 | 518.40 | 305.54 | 8628.52 | 0.00 | 415.51 | 5588.47 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 15-JUN-18:02 | 0.00 | -14843.55 | 0.00 | -638.45 | 0.00 | 0.00 | 335.51 | 1397.95 | 516.20 | 6565.27 | 0.00 | 543.40 | 6123.68 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 22-OCT-13:20 | 0.00 | -47001.15 | 0.00 | -8907.49 | 0.00 | 0.00 | 0.00 | 6190.09 | 5686.12 | 52820.54 | 0.00 | 580.42 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -9368.53 |
ROOM_4_MULT19_FLR_3 | 27-AUG-18:01 | 0.00 | -100554.70 | 0.00 | -8810.78 | 0.00 | 0.00 | 5381.10 | 18762.99 | 9610.21 | 6823.21 | 0.00 | 2280.14 | 66507.83 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 15-JUN-08:61 | 0.00 | -13171.63 | 0.00 | -643.06 | 0.00 | 0.00 | 87.14 | 691.20 | 453.05 | 7870.83 | 0.00 | 296.27 | 4416.20 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 15-JUN-08:61 | 0.00 | -13085.22 | 0.00 | -644.16 | 0.00 | 0.00 | 87.14 | 691.12 | 452.99 | 7988.37 | 0.00 | 295.49 | 4214.26 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 15-JUN-18:10 | 0.00 | 0.00 | 0.00 | -13020.91 | 0.00 | 0.00 | 4576.48 | 4560.37 | 0.00 | 3259.57 | 0.00 | 675.63 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -51.14 |
ROOM_1_FLR_6 | 01-OCT-15:01 | 0.00 | -4055.17 | 0.00 | -160.05 | 0.00 | 0.00 | 32.68 | 129.60 | 76.39 | 2130.83 | 0.00 | 103.18 | 1742.55 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 15-JUN-18:02 | 0.00 | -4023.58 | 0.00 | -159.81 | 0.00 | 0.00 | 83.88 | 349.49 | 129.05 | 1626.16 | 0.00 | 135.14 | 1859.67 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 01-OCT-15:01 | 0.00 | -18723.02 | 0.00 | -1046.09 | 0.00 | 0.00 | 294.11 | 733.24 | 673.54 | 6563.64 | 0.00 | 467.26 | 11037.32 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 15-JUN-18:10 | 0.00 | 0.00 | 0.00 | -24500.71 | 0.00 | 0.00 | 14133.16 | 3398.57 | 6747.90 | 2271.39 | 0.00 | 346.45 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2396.76 |
DINING_FLR_6 | 15-JUN-18:10 | 0.00 | 0.00 | 0.00 | -25885.11 | 0.00 | 0.00 | 14070.16 | 3398.57 | 6747.90 | 2249.84 | 0.00 | 344.73 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -926.10 |
KITCHEN_FLR_6 | 02-JUL-10:35 | 0.00 | 0.00 | 0.00 | -30946.41 | 0.00 | 0.00 | 464.24 | 340.26 | 24459.16 | 2641.99 | 0.00 | 184.76 | 2856.02 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 03-JUL-10:35 | 0.00 | 0.00 | 0.00 | -7804.66 | 0.00 | 0.00 | 351.04 | 377.07 | 0.00 | 1930.13 | 0.00 | 269.20 | 4877.21 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 15-JUN-18:02 | 0.00 | -213537.94 | 0.00 | -239459.02 | 0.00 | 0.00 | 84680.39 | 82800.17 | 122526.13 | 63648.50 | 0.00 | 13894.45 | 85447.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 27-DEC-07:30 | 0.00 | 0.00 | 1056.24 | 0.00 | 0.00 | 0.00 | 364.14 | 381.83 | 433.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1226.69 | 0.00 | -504.37 | -504.17 |
RETAIL_2_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 27-DEC-05:00 | 0.00 | 0.00 | 341.55 | 0.00 | 0.00 | 0.00 | 197.30 | 165.30 | 176.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -464.20 | -416.69 |
STORAGE_FLR_1 | 28-JAN-07:10 | 0.00 | 0.00 | 293.05 | 0.00 | 0.00 | 0.00 | 84.32 | 91.03 | 101.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -253.30 | -317.06 |
LAUNDRY_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 28-NOV-16:01 | 7350.79 | 284.93 | 0.00 | -284.93 | 0.00 | 0.00 | 290.09 | 439.85 | 273.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -562.67 | 0.00 | -376.89 | -7415.11 |
ROOM_2_FLR_3 | 28-NOV-16:01 | 7403.70 | 263.18 | 0.00 | -263.18 | 0.00 | 0.00 | 293.98 | 439.80 | 273.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -579.51 | 0.00 | -361.93 | -7469.94 |
ROOM_3_MULT19_FLR_3 | 27-DEC-06:00 | 20.04 | 12299.55 | 0.00 | -12299.55 | 0.00 | 0.00 | 0.00 | 4126.73 | 3921.46 | 0.00 | 0.00 | 0.00 | 12186.57 | 0.00 | -14706.88 | 0.00 | -5547.92 | 0.00 |
ROOM_4_MULT19_FLR_3 | 11-APR-15:03 | 43372.32 | 5511.25 | 0.00 | -5511.25 | 0.00 | 0.00 | 4899.30 | 5253.64 | 5099.29 | 2724.06 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -14792.43 | -46556.18 |
ROOM_5_FLR_3 | 15-JAN-16:01 | 7052.13 | 282.57 | 0.00 | -282.57 | 0.00 | 0.00 | 161.41 | 518.40 | 305.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -729.24 | 0.00 | -437.92 | -6870.32 |
ROOM_6_FLR_3 | 19-DEC-16:01 | 7097.19 | 259.85 | 0.00 | -259.85 | 0.00 | 0.00 | 293.98 | 439.80 | 273.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1015.38 | 0.00 | -465.86 | -6623.62 |
CORRIDOR_FLR_3 | 27-DEC-07:30 | 0.00 | 0.00 | 1804.65 | 0.00 | 0.00 | 0.00 | 2771.46 | 2850.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3668.39 | 0.00 | -1439.39 | -2318.55 |
ROOM_1_FLR_6 | 28-NOV-16:01 | 2190.54 | 67.26 | 0.00 | -67.26 | 0.00 | 0.00 | 73.50 | 109.96 | 68.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -127.15 | 0.00 | -92.18 | -2223.15 |
ROOM_2_FLR_6 | 28-NOV-16:01 | 2189.36 | 67.01 | 0.00 | -67.01 | 0.00 | 0.00 | 73.50 | 109.95 | 68.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -135.84 | 0.00 | -92.00 | -2213.44 |
ROOM_3_MULT9_FLR_6 | 15-JAN-16:01 | 10181.71 | 493.97 | 0.00 | -493.97 | 0.00 | 0.00 | 357.80 | 733.24 | 673.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -828.36 | 0.00 | -526.74 | -10591.19 |
BANQUET_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 27-DEC-07:30 | 0.00 | 0.00 | 2683.21 | 0.00 | 0.00 | 0.00 | 738.33 | 754.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1614.80 | 0.00 | -634.44 | -1926.44 |
Total Facility | 28-NOV-16:01 | -25542.86 | 117748.85 | 38.39 | -117748.85 | 0.00 | 0.00 | 62257.51 | 25962.78 | 77528.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -18448.84 | 0.00 | -10456.77 | -111339.21 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:58:10
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV WITH REHEAT | 25.1554 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 25.0392 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
FLR_3_DOAS | 2.0513 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.0513 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV WITH REHEAT | 25.0296 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 25.0296 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
FLR_3_DOAS | 2.0513 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.0513 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | VAV WITH REHEAT | 0.000000 | 106.4990 | 0.000432 | 1978.83 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | 0.000000 | 10.8290 | 0.001181 | 67.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | 0.000000 | 12.5400 | 0.001181 | 77.67 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
MECH_FLR_1 | VAV WITH REHEAT | 0.000000 | 2.6520 | 0.000000 | 164.24 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | 0.000000 | 2.0400 | 0.000610 | 94.76 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | 0.000000 | 8.4000 | 0.000000 | 78.04 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | 0.000000 | 142.3000 | 0.003581 | 188.86 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | 0.000000 | 422.4350 | 0.001448 | 1308.19 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1863.81 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1864.32 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | 0.000000 | 83.8280 | 0.000305 | 1557.62 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000396 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000396 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.000000 | 13.5000 | 0.000449 | 220.77 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003581 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DINING_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003581 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | 0.000000 | 22.2380 | 0.003556 | 103.30 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | 0.000000 | 22.1800 | 0.000305 | 412.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV WITH REHEAT | 0.00 | 0.001045 | 6694.0231 | 0.0000 | 0.0000 | 0.0000 | |
FLR_3_DOAS | 0.00 | 0.000441 | 4651.2638 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.8579 | 2.8579 | 2.8436 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3894 | 0.3894 | 0.3874 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2842 | 0.2842 | 0.2828 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3043 | 0.3043 | 0.3028 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1537 | 0.1537 | 0.1529 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.7896 | 3.7896 | 3.7707 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.6561 | 1.6561 | 1.6478 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.4707 | 5.4707 | 5.4433 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8371 | 0.8371 | 0.8371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8373 | 0.8373 | 0.8373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3618 | 1.3618 | 1.3550 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0992 | 0.0992 | 0.0992 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.6404 | 2.6404 | 2.6272 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.7682 | 2.7682 | 2.7543 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.6349 | 2.6349 | 2.6217 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8442 | 0.8442 | 0.8400 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV WITH REHEAT | 25.1554 | 25.0392 | 25.1554 | 25.0296 | 0.0000 | 1.0000 |
FLR_3_DOAS | 2.0513 | 2.0513 | 2.0513 | 2.0513 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.8436 | 2.8436 | 2.8436 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3874 | 0.3874 | 0.3874 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2828 | 0.2828 | 0.2828 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3028 | 0.3028 | 0.3028 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1529 | 0.1529 | 0.1529 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.7707 | 3.7707 | 3.7707 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.6478 | 1.6478 | 1.6478 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.4433 | 5.4433 | 5.4433 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8371 | 0.8371 | 0.8371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8373 | 0.8373 | 0.8373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3550 | 1.3550 | 1.3550 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0992 | 0.0992 | 0.0992 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.6272 | 2.6272 | 2.6272 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.7543 | 2.7543 | 2.7543 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.6217 | 2.6217 | 2.6217 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8400 | 0.8400 | 0.8400 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV WITH REHEAT | 25.0296 | 25.0296 | 25.0296 | 25.0296 | 0.0000 | 1.0000 |
FLR_3_DOAS | 2.0513 | 2.0513 | 2.0513 | 2.0513 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:58:10
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** El Paso International Ap Ut TX USA TMY3 WMO#=722700 |
Total gross floor area [m2] | 11345.29 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 1978.83 | 1978.83 | 0.00 | 168.00 |
RETAIL_1_FLR_1 | 67.07 | 67.07 | 0.00 | 168.00 |
RETAIL_2_FLR_1 | 77.67 | 77.67 | 0.00 | 168.00 |
MECH_FLR_1 | 164.24 | 164.24 | 0.00 | 168.00 |
STORAGE_FLR_1 | 94.76 | 94.76 | 0.00 | 168.00 |
LAUNDRY_FLR_1 | 78.04 | 78.04 | 0.00 | 168.00 |
CAFE_FLR_1 | 188.86 | 188.86 | 0.00 | 168.00 |
LOBBY_FLR_1 | 1308.19 | 1308.19 | 0.00 | 168.00 |
ROOM_1_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT19_FLR_3 | 24.52 | 24.52 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 24.53 | 24.53 | 0.00 | 168.00 |
ROOM_5_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_6_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
CORRIDOR_FLR_3 | 389.40 | 389.40 | 0.00 | 168.00 |
ROOM_1_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT9_FLR_6 | 24.53 | 24.53 | 0.00 | 168.00 |
BANQUET_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
DINING_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
KITCHEN_FLR_6 | 103.30 | 103.30 | 0.00 | 168.00 |
CORRIDOR_FLR_6 | 412.12 | 412.12 | 0.00 | 168.00 |
Totals | 11345.29 | 11345.29 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 13.67 |
Number of hours not met | 13.67 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 1215.20 | 201630.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 2289.50 | 247961.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 1174.11 | 93091.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 262.44 | 16690.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 959.56 | 59492.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 762.04 | 29240.64 | 1198.64 | 74976.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 16.27 | 515.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 13.43 | 425.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Laundry | 0.00 | 0.00 | 590.20 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 32.92 | 1912.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 616.11 | 37691.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 30.65 | 972.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 2048.85 | 87624.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 253.67 | 13002.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- General | 563.76 | 18015.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 90.78 | 4739.27 | 2927.15 | 251113.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 18.27 | 2271.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 22.42 | 1894.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 33.50 | 1196.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 1825.49 | 9188.28 |
Natural Gas | 1788.84 | 5931.18 |
Additional | 0.00 | 0.00 |
Total | 3614.33 | 15119.46 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 103.49 |
Space Heating | 0.00 |
Space Cooling | 201.80 |
Fans (All) | 180.59 |
Service Water Heating | 8.00 |
Receptacle Equipment | 154.36 |
Miscellaneous (All) | 809.88 |
Subtotal | 809.88 |
Natural Gas [MJ/m2] | |
Space Heating | 107.11 |
Service Water Heating | 258.01 |
Miscellaneous (All) | 522.79 |
Subtotal | 522.79 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 7.77 |
Space Heating | 8.04 |
Space Cooling | 15.14 |
Fans (All) | 13.55 |
Service Water Heating | 19.96 |
Receptacle Equipment | 23.41 |
Miscellaneous | 12.13 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_KITCHEN | 3061. | 8760. |
LTG_SCH_DINING | 3061. | 8760. |
LTG_SCH_BASEMENT | 2655. | 8760. |
LTG_SCH_LOBBY | 3061. | 8760. |
LTG_SCH_STORAGE | 1339. | 8760. |
LTG_SCH_MECHANIC | 3061. | 8760. |
LTG_SCH_LAUNDRY | 2678. | 8760. |
LTG_SCH_GUESTROOM | 3599. | 8760. |
LTG_SCH_CORRIDOR | 3061. | 8760. |
LTG_SCH_RETAIL | 2678. | 8760. |
WALKIN_OCC_LGHT_SCH_1 | 3061. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
BASEMENT_EQUIP_SCH | 3924. | 8760. |
BLDG_EQUIP_SCH | 3924. | 8760. |
GUESTROOM_EQP_SCH_BASE | 3239. | 8760. |
GUESTROOM_EQP_SCH_ADVA | 2762. | 8760. |
LOBBY_EQP_SCH | 3292. | 8760. |
OFFICE_EQP_SCH | 4941. | 8760. |
EMPLOYEELOUNGE_EQP_SCH | 4044. | 8760. |
LAUNDRYROOM_EQP_ELEC_SCH | 2920. | 2920. |
LAUNDRYROOM_EQP_GAS_SCH | 2920. | 2920. |
MEETINGROOM_EQP_SCH | 1336. | 4745. |
EXERCISEROOM_EQP_SCH | 3832. | 5840. |
KITCHEN_ELEC_EQUIP_SCH | 2172. | 8760. |
KITCHEN_GAS_EQUIP_SCH | 1332. | 8760. |
KITCHEN_EXHAUST_SCH | 6205. | 6205. |
BLDG_ELEVATORS | 2270. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_OCC_SCH | 5026. | 8760. |
GUESTROOM_OCC_SCH | 5515. | 8760. |
LOBBY_OCC_SCH | 2304. | 8760. |
OFFICE_OCC_SCH | 3954. | 8760. |
EMPLOYEELOUNGE_OCC_SCH | 948. | 5475. |
MEETINGROOM_OCC_SCH | 1168. | 4745. |
LAUNDRYROOM_OCC_SCH | 427. | 2920. |
EXERCISEROOM_OCC_SCH | 5292. | 5840. |
INFIL_SCH | 8760. | 8760. |
INFIL_HALF_ON_SCH | 4380. | 8760. |
INFIL_QUARTER_ON_SCH | 2190. | 8760. |
LAUNDRY_SWH_SCH | 2555. | 2555. |
BLDG_SWH_SCH | 3301. | 8760. |
GUESTROOM_SWH_SCH | 2899. | 8760. |
LAUNDRYROOM_SWH_SCH | 2920. | 2920. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
ALWAYS_ON | 8760. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
OCC_GUESTROOM_VENT_CTRL_30MIN | 6570. | 6570. |
OCC_GUESTROOM_VENT_CTRL_20MIN | 6327. | 6327. |
VAC_GUESTROOM_VENTILATION_SCHEDULE | 365. | 365. |
MINOA_MOTORIZEDDAMPER_SCHED | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
ROOM_1_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
FLR_3_DOAS_OAMINOAFRACSCHEDULE | 8760. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 0. | 0. |
LAUNDRY_FLR_1 EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 0. | 0. |
SLIDING_DOORS_VENTILATION_AVAILABILITY_SCH | 3285. | 3285. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
VACGUESTROOM_HTGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 18.89 | 365 | 18.89 | 365 |
VACGUESTROOM_CLGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 23.33 | 365 |
OBCRESET_S_OCCGUESTROOM_HTGSP_SCH_30MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_S_OCCGUESTROOM_CLGSP_SCH_30MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_HTGSP_SCH_30MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_CLGSP_SCH_30MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
HTGSETP_SCH | BASEMENT DUAL SP CONTROL | January | 21.00 | 365 | 21.00 | 365 |
CLGSETP_SCH | BASEMENT DUAL SP CONTROL | July | 24.00 | 365 | 24.00 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:58:10
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Average | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Sum | 192720.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 529331.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 50179.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 59156.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8977.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 5588.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 37203.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 710417.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 2115429.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 100358.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 108269.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 105946.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 2115429.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Average | 288887.05 | 0.00 | 0.00 | 0.00 | 0.00 |
Sum | 6355515.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Average | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Sum | 192720.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 529331.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 50179.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 59156.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8977.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 5588.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 37203.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 710417.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 2115429.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 100358.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 108269.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 105946.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 2115429.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Average | 288887.05 | 0.00 | 0.00 | 0.00 | 0.00 |
Sum | 6355515.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:58:10
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:58:10
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2012
For: Environment
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
For: Environment
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3B
For: Environment
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_TX_ELPASO
For: Environment
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.399783E+11 | 19555.90 | 12-JAN-19:10 | 15.03 | 8.30 | 0.617557E+10 | 3831.50 | 06-JAN-22:10 | 15.03 | 8.30 |
February | 0.295875E+11 | 18758.35 | 22-FEB-20:10 | 15.18 | 5.09 | 0.552790E+10 | 3761.35 | 01-FEB-22:10 | 15.18 | 5.09 |
March | 0.279918E+11 | 17799.84 | 01-MAR-21:00 | 1.70 | -3.0 | 0.610529E+10 | 3657.91 | 01-MAR-22:10 | 1.02 | -3.3 |
April | 0.284020E+11 | 18271.64 | 07-APR-20:00 | 18.90 | 8.36 | 0.588692E+10 | 3620.15 | 06-APR-21:10 | 18.90 | 8.36 |
May | 0.318967E+11 | 19358.14 | 11-MAY-20:00 | 26.70 | 12.64 | 0.609305E+10 | 3646.77 | 05-MAY-22:10 | 26.70 | 12.64 |
June | 0.335022E+11 | 20361.87 | 08-JUN-20:00 | 27.80 | 15.60 | 0.591341E+10 | 3675.58 | 23-JUN-22:10 | 23.40 | 15.27 |
July | 0.414790E+11 | 22386.27 | 26-JUL-18:50 | 31.23 | 19.55 | 0.614611E+10 | 3793.76 | 07-JUL-22:10 | 31.23 | 19.55 |
August | 0.464708E+11 | 23534.96 | 07-AUG-18:10 | 33.95 | 18.47 | 0.629621E+10 | 3898.89 | 16-AUG-21:10 | 17.80 | 16.68 |
September | 0.487767E+11 | 23757.44 | 17-SEP-10:35 | 29.47 | 15.71 | 0.623020E+10 | 4012.25 | 29-SEP-22:10 | 18.77 | 9.00 |
October | 0.497275E+11 | 23308.91 | 01-OCT-10:35 | 26.67 | 14.26 | 0.648348E+10 | 4046.41 | 13-OCT-21:10 | 12.70 | 11.69 |
November | 0.466973E+11 | 21752.54 | 09-NOV-19:10 | 20.50 | 11.67 | 0.626630E+10 | 4042.90 | 01-NOV-21:10 | 20.50 | 11.67 |
December | 0.453498E+11 | 20408.78 | 01-DEC-21:00 | 6.70 | 2.22 | 0.633229E+10 | 3985.99 | 01-DEC-22:10 | 7.12 | 2.19 |
Annual Sum or Average | 0.469860E+12 | 0.734567E+11 | ||||||||
Minimum of Months | 0.279918E+11 | 17799.84 | 1.70 | -3.0 | 0.552790E+10 | 3620.15 | 1.02 | -3.3 | ||
Maximum of Months | 0.497275E+11 | 23757.44 | 33.95 | 19.55 | 0.648348E+10 | 4046.41 | 31.23 | 19.55 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.244750E+10 | 3022.90 | 01-JAN-11:35 | 13.87 | 8.54 | 0.621948E+09 | 364.26 | 03-JAN-02:00 | 2.80 | 0.09 |
February | 0.256139E+10 | 3122.37 | 07-FEB-11:35 | 19.63 | 9.18 | 0.562773E+09 | 364.27 | 11-FEB-05:49 | 4.68 | 0.24 |
March | 0.300656E+10 | 2938.03 | 05-MAR-11:35 | 16.83 | 7.89 | 0.623913E+09 | 364.26 | 11-MAR-02:49 | 12.02 | 9.75 |
April | 0.407903E+10 | 2815.06 | 04-APR-10:35 | 22.97 | 9.90 | 0.602287E+09 | 382.30 | 19-APR-21:40 | 27.57 | 11.97 |
May | 0.503807E+10 | 3042.50 | 31-MAY-18:02 | 30.92 | 15.25 | 0.622754E+09 | 392.49 | 19-MAY-21:40 | 30.92 | 15.25 |
June | 0.582936E+10 | 3338.82 | 15-JUN-18:10 | 35.92 | 14.47 | 0.610220E+09 | 403.95 | 16-JUN-21:00 | 31.10 | 15.68 |
July | 0.602315E+10 | 3323.83 | 26-JUL-18:10 | 33.77 | 19.75 | 0.626660E+09 | 400.18 | 25-JUL-21:49 | 33.77 | 19.75 |
August | 0.593716E+10 | 3369.31 | 27-AUG-10:35 | 32.03 | 15.07 | 0.630767E+09 | 405.63 | 07-AUG-21:40 | 32.03 | 15.07 |
September | 0.569432E+10 | 3489.09 | 17-SEP-10:35 | 29.47 | 15.71 | 0.611655E+09 | 394.65 | 20-SEP-22:10 | 26.52 | 16.85 |
October | 0.489134E+10 | 3559.87 | 05-OCT-10:35 | 27.60 | 18.63 | 0.629965E+09 | 387.65 | 05-OCT-21:30 | 23.05 | 16.20 |
November | 0.325898E+10 | 3458.94 | 10-NOV-11:35 | 20.93 | 12.02 | 0.605176E+09 | 364.94 | 09-NOV-22:19 | 20.93 | 12.02 |
December | 0.219908E+10 | 2909.21 | 09-DEC-11:40 | 16.10 | 7.03 | 0.621276E+09 | 364.26 | 18-DEC-04:10 | 5.40 | -1.6 |
Annual Sum or Average | 0.509659E+11 | 0.736939E+10 | ||||||||
Minimum of Months | 0.219908E+10 | 2815.06 | 13.87 | 7.03 | 0.562773E+09 | 364.26 | 2.80 | -1.6 | ||
Maximum of Months | 0.602315E+10 | 3559.87 | 35.92 | 19.75 | 0.630767E+09 | 405.63 | 33.77 | 19.75 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.285831E+10 | 1847.61 | 12-JAN-21:00 | 12.80 | 7.31 | 0.718694E+09 | 438.18 | 12-JAN-22:19 | 9.47 | 5.03 |
February | 0.275726E+10 | 1916.25 | 21-FEB-21:00 | 15.00 | 4.44 | 0.650473E+09 | 445.65 | 21-FEB-22:19 | 12.93 | 3.71 |
March | 0.328319E+10 | 2002.14 | 16-MAR-18:01 | 19.82 | 7.14 | 0.725096E+09 | 450.64 | 16-MAR-21:40 | 16.47 | 6.01 |
April | 0.375348E+10 | 2217.48 | 19-APR-18:10 | 29.90 | 13.60 | 0.705989E+09 | 467.22 | 19-APR-22:10 | 26.93 | 11.76 |
May | 0.428642E+10 | 2302.72 | 31-MAY-18:10 | 30.92 | 15.25 | 0.737979E+09 | 477.92 | 19-MAY-22:10 | 30.92 | 15.25 |
June | 0.451008E+10 | 2435.52 | 15-JUN-18:10 | 35.92 | 14.47 | 0.726458E+09 | 487.88 | 16-JUN-22:10 | 30.92 | 15.69 |
July | 0.462676E+10 | 2419.51 | 26-JUL-18:10 | 33.77 | 19.75 | 0.744456E+09 | 483.42 | 25-JUL-22:10 | 33.77 | 19.75 |
August | 0.455716E+10 | 2399.11 | 07-AUG-18:10 | 33.95 | 18.47 | 0.746270E+09 | 482.63 | 07-AUG-21:49 | 29.45 | 17.70 |
September | 0.432334E+10 | 2311.02 | 20-SEP-18:10 | 31.05 | 16.15 | 0.715584E+09 | 476.68 | 20-SEP-22:10 | 26.52 | 16.85 |
October | 0.397260E+10 | 2238.59 | 05-OCT-18:10 | 27.15 | 16.93 | 0.729173E+09 | 470.60 | 05-OCT-22:10 | 22.98 | 16.25 |
November | 0.316893E+10 | 2021.03 | 09-NOV-19:10 | 20.50 | 11.67 | 0.697610E+09 | 452.94 | 09-NOV-22:19 | 18.17 | 10.78 |
December | 0.271562E+10 | 1818.49 | 15-DEC-21:00 | 14.40 | 4.76 | 0.718021E+09 | 435.53 | 15-DEC-22:19 | 14.23 | 4.60 |
Annual Sum or Average | 0.448132E+11 | 0.861580E+10 | ||||||||
Minimum of Months | 0.271562E+10 | 1818.49 | 12.80 | 4.44 | 0.650473E+09 | 435.53 | 9.47 | 3.71 | ||
Maximum of Months | 0.462676E+10 | 2435.52 | 35.92 | 19.75 | 0.746270E+09 | 487.88 | 33.77 | 19.75 |
Report: ZoneCoolingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.122882E+10 | 1563.50 | 03-JAN-21:00 | 14.40 | 6.79 | 0.151697E+09 | 89.15 | 17-JAN-04:40 | 5.60 | 3.88 |
February | 0.143565E+10 | 1778.86 | 07-FEB-20:50 | 15.78 | 7.73 | 0.137151E+09 | 89.16 | 24-FEB-04:00 | 5.60 | 0.21 |
March | 0.205179E+10 | 1965.52 | 16-MAR-20:00 | 17.20 | 5.94 | 0.152415E+09 | 89.80 | 16-MAR-21:10 | 17.02 | 5.96 |
April | 0.311739E+10 | 2228.19 | 19-APR-19:10 | 29.22 | 13.15 | 0.147414E+09 | 93.75 | 21-APR-21:19 | 24.80 | 9.48 |
May | 0.416103E+10 | 2442.52 | 31-MAY-18:10 | 30.92 | 15.25 | 0.153397E+09 | 96.30 | 19-MAY-22:10 | 30.92 | 15.25 |
June | 0.477983E+10 | 2587.17 | 15-JUN-18:10 | 35.92 | 14.47 | 0.150781E+09 | 99.20 | 16-JUN-22:10 | 30.92 | 15.69 |
July | 0.489703E+10 | 2596.05 | 03-JUL-18:10 | 36.28 | 18.94 | 0.154676E+09 | 97.96 | 03-JUL-22:10 | 25.82 | 18.63 |
August | 0.462066E+10 | 2526.66 | 07-AUG-18:10 | 33.95 | 18.47 | 0.154549E+09 | 97.54 | 07-AUG-22:10 | 28.52 | 18.18 |
September | 0.401764E+10 | 2395.61 | 20-SEP-18:02 | 31.05 | 16.15 | 0.148063E+09 | 95.05 | 22-SEP-21:19 | 25.00 | 17.90 |
October | 0.317317E+10 | 2288.28 | 05-OCT-18:20 | 26.50 | 16.93 | 0.152049E+09 | 93.59 | 03-OCT-21:10 | 26.50 | 16.93 |
November | 0.179613E+10 | 1986.67 | 09-NOV-21:00 | 20.00 | 11.27 | 0.146747E+09 | 90.12 | 09-NOV-22:10 | 18.53 | 10.92 |
December | 0.102693E+10 | 1480.93 | 15-DEC-21:00 | 14.40 | 4.76 | 0.151697E+09 | 89.16 | 20-DEC-04:00 | 8.30 | -1.0 |
Annual Sum or Average | 0.363061E+11 | 0.180064E+10 | ||||||||
Minimum of Months | 0.102693E+10 | 1480.93 | 14.40 | 4.76 | 0.137151E+09 | 89.15 | 5.60 | -1.0 | ||
Maximum of Months | 0.489703E+10 | 2596.05 | 36.28 | 18.94 | 0.154676E+09 | 99.20 | 30.92 | 18.63 |
Report: ZoneCoolingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.236821E+09 | 482.31 | 03-JAN-21:10 | 14.13 | 6.70 | 0.116691E+09 | 68.58 | 07-JAN-04:40 | -1.3 | -4.4 |
February | 0.392934E+09 | 603.96 | 07-FEB-22:00 | 15.00 | 7.49 | 0.105501E+09 | 68.58 | 14-FEB-01:00 | 11.10 | 8.31 |
March | 0.665757E+09 | 720.48 | 15-MAR-21:00 | 20.00 | 7.66 | 0.117239E+09 | 68.58 | 11-MAR-02:49 | 20.00 | 7.66 |
April | 0.131565E+10 | 1023.00 | 21-APR-20:00 | 26.10 | 11.77 | 0.113143E+09 | 69.82 | 21-APR-22:10 | 24.13 | 8.96 |
May | 0.193191E+10 | 1151.80 | 31-MAY-19:10 | 29.90 | 14.49 | 0.117209E+09 | 71.81 | 19-MAY-22:10 | 29.90 | 14.49 |
June | 0.233656E+10 | 1284.12 | 15-JUN-18:10 | 35.92 | 14.47 | 0.114804E+09 | 73.89 | 16-JUN-22:10 | 30.92 | 15.69 |
July | 0.239291E+10 | 1284.44 | 03-JUL-18:10 | 36.28 | 18.94 | 0.117824E+09 | 72.79 | 03-JUL-22:10 | 25.82 | 18.63 |
August | 0.222077E+10 | 1231.30 | 07-AUG-18:20 | 33.50 | 18.31 | 0.117873E+09 | 72.65 | 07-AUG-21:49 | 29.45 | 17.70 |
September | 0.186352E+10 | 1092.51 | 21-SEP-20:00 | 25.60 | 16.42 | 0.113222E+09 | 70.83 | 22-SEP-22:10 | 24.90 | 17.87 |
October | 0.133440E+10 | 1026.04 | 05-OCT-20:00 | 23.90 | 16.65 | 0.116768E+09 | 69.77 | 05-OCT-22:10 | 22.98 | 16.25 |
November | 0.546487E+09 | 752.97 | 09-NOV-22:00 | 18.90 | 11.06 | 0.112879E+09 | 68.58 | 08-NOV-01:10 | 18.90 | 11.06 |
December | 0.172537E+09 | 458.27 | 15-DEC-22:00 | 14.40 | 4.62 | 0.116691E+09 | 68.58 | 20-DEC-04:30 | 8.05 | -1.0 |
Annual Sum or Average | 0.154103E+11 | 0.137985E+10 | ||||||||
Minimum of Months | 0.172537E+09 | 458.27 | 14.13 | 4.62 | 0.105501E+09 | 68.58 | -1.3 | -4.4 | ||
Maximum of Months | 0.239291E+10 | 1284.44 | 36.28 | 18.94 | 0.117873E+09 | 73.89 | 30.92 | 18.63 |
Report: ZoneCoolingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.491929E+11 | 35924.14 | 03-JAN-21:00 | 14.40 | 6.79 | 0.510315E+09 | 381.72 | 20-JAN-22:10 | 10.40 | 4.96 |
February | 0.450817E+11 | 36275.22 | 21-FEB-21:00 | 15.00 | 4.44 | 0.461433E+09 | 381.74 | 14-FEB-22:10 | 15.00 | 4.44 |
March | 0.507675E+11 | 36418.54 | 21-MAR-20:00 | 16.70 | 5.61 | 0.513072E+09 | 381.77 | 03-MAR-22:10 | 16.70 | 5.61 |
April | 0.507980E+11 | 37455.04 | 19-APR-20:00 | 28.30 | 12.40 | 0.493079E+09 | 381.73 | 11-APR-21:10 | 28.30 | 12.40 |
May | 0.538274E+11 | 37787.26 | 31-MAY-20:00 | 29.40 | 14.60 | 0.509182E+09 | 381.72 | 05-MAY-21:10 | 29.40 | 14.60 |
June | 0.532481E+11 | 38342.34 | 15-JUN-20:00 | 33.90 | 14.00 | 0.492810E+09 | 381.63 | 30-JUN-21:10 | 28.83 | 15.17 |
July | 0.547057E+11 | 38198.40 | 26-JUL-20:00 | 29.40 | 19.17 | 0.505715E+09 | 381.60 | 07-JUL-21:10 | 29.40 | 19.17 |
August | 0.545148E+11 | 38120.41 | 07-AUG-20:00 | 31.70 | 17.36 | 0.509843E+09 | 381.64 | 25-AUG-21:10 | 27.62 | 14.77 |
September | 0.520501E+11 | 37647.42 | 20-SEP-20:00 | 25.60 | 15.27 | 0.491867E+09 | 381.70 | 26-SEP-21:10 | 20.55 | 11.34 |
October | 0.520921E+11 | 37405.15 | 05-OCT-20:00 | 23.90 | 16.65 | 0.509071E+09 | 381.80 | 10-OCT-21:10 | 14.13 | 9.16 |
November | 0.486277E+11 | 36481.70 | 09-NOV-21:00 | 20.00 | 11.27 | 0.493735E+09 | 381.72 | 17-NOV-22:10 | 11.02 | 3.83 |
December | 0.488149E+11 | 35799.25 | 15-DEC-21:00 | 14.40 | 4.76 | 0.510015E+09 | 381.72 | 05-DEC-22:10 | 14.40 | 4.76 |
Annual Sum or Average | 0.613721E+12 | 0.600014E+10 | ||||||||
Minimum of Months | 0.450817E+11 | 35799.25 | 14.40 | 4.44 | 0.461433E+09 | 381.60 | 10.40 | 3.83 | ||
Maximum of Months | 0.547057E+11 | 38342.34 | 33.90 | 19.17 | 0.513072E+09 | 381.80 | 29.40 | 19.17 |
Report: ZoneCoolingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.204569E+11 | 12726.90 | 01-JAN-11:35 | 13.87 | 8.54 | 0.818808E+10 | 5092.46 | 03-JAN-22:19 | 12.07 | 5.91 |
February | 0.194137E+11 | 13089.37 | 19-FEB-11:35 | 19.03 | 7.40 | 0.741896E+10 | 5267.39 | 06-FEB-22:30 | 19.03 | 7.40 |
March | 0.217415E+11 | 12405.00 | 05-MAR-11:35 | 16.83 | 7.89 | 0.824614E+10 | 5245.91 | 15-MAR-21:40 | 19.60 | 7.41 |
April | 0.235954E+11 | 12875.44 | 19-APR-18:03 | 29.90 | 13.60 | 0.807998E+10 | 5517.48 | 19-APR-21:40 | 27.57 | 11.97 |
May | 0.259589E+11 | 13365.11 | 31-MAY-18:10 | 30.92 | 15.25 | 0.846592E+10 | 5594.55 | 19-MAY-22:10 | 30.92 | 15.25 |
June | 0.272956E+11 | 14106.58 | 14-JUN-18:10 | 37.02 | 14.90 | 0.838694E+10 | 5677.92 | 16-JUN-22:10 | 30.92 | 15.69 |
July | 0.282494E+11 | 14111.07 | 03-JUL-18:10 | 36.28 | 18.94 | 0.861314E+10 | 5640.40 | 25-JUL-21:40 | 30.57 | 17.35 |
August | 0.282619E+11 | 14049.84 | 07-AUG-18:10 | 33.95 | 18.47 | 0.865954E+10 | 5686.68 | 07-AUG-21:40 | 29.90 | 17.57 |
September | 0.275901E+11 | 14200.35 | 17-SEP-10:35 | 29.47 | 15.71 | 0.831695E+10 | 5606.79 | 20-SEP-22:10 | 26.52 | 16.85 |
October | 0.264077E+11 | 14157.01 | 22-OCT-10:35 | 22.23 | 13.01 | 0.847823E+10 | 5544.87 | 05-OCT-21:40 | 22.23 | 13.01 |
November | 0.221888E+11 | 13773.93 | 11-NOV-11:35 | 16.83 | 7.74 | 0.800994E+10 | 5374.14 | 09-NOV-22:19 | 16.83 | 7.74 |
December | 0.195785E+11 | 12324.52 | 10-DEC-11:35 | 15.93 | 7.48 | 0.817206E+10 | 5069.40 | 15-DEC-22:30 | 14.15 | 4.60 |
Annual Sum or Average | 0.290739E+12 | 0.990359E+11 | ||||||||
Minimum of Months | 0.194137E+11 | 12324.52 | 13.87 | 7.40 | 0.741896E+10 | 5069.40 | 12.07 | 4.60 | ||
Maximum of Months | 0.282619E+11 | 14200.35 | 37.02 | 18.94 | 0.865954E+10 | 5686.68 | 30.92 | 17.57 |
Report: ZoneCoolingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.697421E+11 | 37038.98 | 12-JAN-19:10 | 15.03 | 8.30 | 0.244070E+11 | 15432.38 | 03-JAN-22:40 | 15.03 | 8.30 |
February | 0.654859E+11 | 37963.05 | 22-FEB-19:03 | 17.75 | 6.22 | 0.221368E+11 | 15695.37 | 06-FEB-22:40 | 17.75 | 6.22 |
March | 0.744255E+11 | 39314.42 | 16-MAR-18:10 | 19.82 | 7.14 | 0.247386E+11 | 15817.53 | 16-MAR-21:40 | 16.47 | 6.01 |
April | 0.794426E+11 | 43050.52 | 19-APR-18:10 | 29.90 | 13.60 | 0.242778E+11 | 16309.70 | 19-APR-22:10 | 26.93 | 11.76 |
May | 0.875451E+11 | 44823.93 | 31-MAY-18:10 | 30.92 | 15.25 | 0.254906E+11 | 16613.08 | 19-MAY-22:10 | 30.92 | 15.25 |
June | 0.906914E+11 | 46864.58 | 15-JUN-18:10 | 35.92 | 14.47 | 0.251185E+11 | 16862.21 | 16-JUN-22:10 | 30.92 | 15.69 |
July | 0.935526E+11 | 46885.37 | 03-JUL-18:10 | 36.28 | 18.94 | 0.257739E+11 | 16715.74 | 25-JUL-22:10 | 30.00 | 17.07 |
August | 0.927357E+11 | 46323.01 | 07-AUG-18:10 | 33.95 | 18.47 | 0.258506E+11 | 16745.18 | 07-AUG-21:49 | 29.45 | 17.70 |
September | 0.887692E+11 | 44736.94 | 20-SEP-18:10 | 31.05 | 16.15 | 0.247195E+11 | 16526.22 | 22-SEP-22:10 | 24.90 | 17.87 |
October | 0.854536E+11 | 43560.26 | 05-OCT-18:10 | 27.15 | 16.93 | 0.251388E+11 | 16395.09 | 05-OCT-22:10 | 22.98 | 16.25 |
November | 0.734748E+11 | 39725.35 | 09-NOV-19:10 | 20.50 | 11.67 | 0.238037E+11 | 15946.74 | 09-NOV-22:40 | 17.43 | 10.49 |
December | 0.677825E+11 | 36331.62 | 15-DEC-21:00 | 14.40 | 4.76 | 0.243458E+11 | 15407.33 | 15-DEC-22:40 | 14.07 | 4.59 |
Annual Sum or Average | 0.969101E+12 | 0.295802E+12 | ||||||||
Minimum of Months | 0.654859E+11 | 36331.62 | 14.40 | 4.76 | 0.221368E+11 | 15407.33 | 14.07 | 4.59 | ||
Maximum of Months | 0.935526E+11 | 46885.37 | 36.28 | 18.94 | 0.258506E+11 | 16862.21 | 30.92 | 17.87 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.291010E+09 | 3759.58 | 12-JAN-16:01 | 18.72 | 10.12 | 96034064.25 | 56.69 | 03-JAN-22:10 | 18.72 | 10.12 |
February | 0.414130E+09 | 3836.15 | 20-FEB-16:01 | 23.12 | 8.59 | 87307297.40 | 56.69 | 06-FEB-22:40 | 23.12 | 8.59 |
March | 0.701934E+09 | 3824.56 | 16-MAR-15:01 | 22.70 | 8.66 | 97443760.05 | 56.69 | 07-MAR-22:10 | 22.70 | 8.66 |
April | 0.149638E+10 | 3861.25 | 30-APR-15:01 | 30.10 | 12.65 | 95193008.76 | 56.70 | 28-APR-21:30 | 30.10 | 12.65 |
May | 0.223455E+10 | 3885.84 | 20-MAY-15:01 | 32.20 | 15.53 | 98835530.41 | 56.70 | 23-MAY-22:10 | 20.92 | 15.65 |
June | 0.280348E+10 | 3885.67 | 15-JUN-18:02 | 35.92 | 14.47 | 95915397.02 | 56.70 | 16-JUN-21:49 | 31.38 | 15.54 |
July | 0.279262E+10 | 3519.24 | 19-JUL-18:02 | 28.72 | 20.94 | 99033318.08 | 56.70 | 24-JUL-21:10 | 29.63 | 17.48 |
August | 0.261629E+10 | 3888.00 | 23-AUG-15:01 | 33.30 | 16.20 | 99038719.64 | 56.70 | 04-AUG-21:10 | 33.30 | 16.20 |
September | 0.234044E+10 | 3887.91 | 11-SEP-15:01 | 29.40 | 13.84 | 95704577.47 | 56.70 | 22-SEP-23:00 | 21.70 | 19.30 |
October | 0.156026E+10 | 3896.79 | 01-OCT-15:01 | 32.62 | 15.84 | 98375869.30 | 56.70 | 18-OCT-21:30 | 21.40 | 16.61 |
November | 0.637583E+09 | 3840.31 | 09-NOV-16:01 | 23.22 | 12.98 | 93997934.52 | 56.69 | 09-NOV-22:00 | 16.70 | 10.18 |
December | 0.213944E+09 | 3706.74 | 17-DEC-16:01 | 15.32 | 4.54 | 95720405.98 | 56.69 | 13-DEC-00:10 | 15.32 | 4.54 |
Annual Sum or Average | 0.181026E+11 | 0.115260E+10 | ||||||||
Minimum of Months | 0.213944E+09 | 3519.24 | 15.32 | 4.54 | 87307297.40 | 56.69 | 15.32 | 4.54 | ||
Maximum of Months | 0.280348E+10 | 3896.79 | 35.92 | 20.94 | 99038719.64 | 56.70 | 33.30 | 19.30 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.112700E+09 | 3612.50 | 12-JAN-16:01 | 18.72 | 10.12 | 94351268.31 | 56.69 | 03-JAN-22:19 | 18.72 | 10.12 |
February | 0.204049E+09 | 3759.91 | 20-FEB-16:01 | 23.12 | 8.59 | 86017634.41 | 56.69 | 06-FEB-22:19 | 23.12 | 8.59 |
March | 0.475679E+09 | 3755.94 | 16-MAR-15:01 | 22.70 | 8.66 | 96545582.05 | 56.69 | 16-MAR-21:30 | 16.65 | 6.00 |
April | 0.131458E+10 | 3825.68 | 30-APR-15:01 | 30.10 | 12.65 | 94927066.23 | 56.69 | 17-APR-01:10 | 30.10 | 12.65 |
May | 0.218520E+10 | 3857.13 | 20-MAY-15:01 | 32.20 | 15.53 | 98801041.11 | 56.70 | 23-MAY-22:10 | 20.92 | 15.65 |
June | 0.281738E+10 | 3870.47 | 15-JUN-18:02 | 35.92 | 14.47 | 95934944.41 | 56.70 | 28-JUN-00:20 | 20.17 | 17.30 |
July | 0.277963E+10 | 3500.64 | 30-JUL-18:02 | 28.80 | 20.02 | 99044750.90 | 56.70 | 24-JUL-21:10 | 28.80 | 20.02 |
August | 0.248230E+10 | 3848.93 | 23-AUG-15:01 | 33.30 | 16.20 | 99007546.72 | 56.70 | 04-AUG-21:10 | 33.30 | 16.20 |
September | 0.200325E+10 | 3834.31 | 11-SEP-15:01 | 29.40 | 13.84 | 95564081.23 | 56.70 | 15-SEP-21:49 | 22.38 | 17.21 |
October | 0.112035E+10 | 3830.17 | 01-OCT-15:01 | 32.62 | 15.84 | 97760995.97 | 56.70 | 04-OCT-22:10 | 23.72 | 17.31 |
November | 0.282604E+09 | 3767.81 | 09-NOV-16:01 | 23.22 | 12.98 | 92705462.41 | 56.69 | 09-NOV-22:10 | 18.53 | 10.92 |
December | 84319218.93 | 3460.05 | 16-DEC-16:02 | 14.72 | 4.08 | 93943541.86 | 56.69 | 13-DEC-00:10 | 14.72 | 4.08 |
Annual Sum or Average | 0.158620E+11 | 0.114460E+10 | ||||||||
Minimum of Months | 84319218.93 | 3460.05 | 14.72 | 4.08 | 86017634.41 | 56.69 | 14.72 | 4.08 | ||
Maximum of Months | 0.281738E+10 | 3870.47 | 35.92 | 20.02 | 99044750.90 | 56.70 | 33.30 | 20.02 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.500266E+09 | 609.96 | 12-JAN-14:30 | 18.60 | 9.87 | 0.00 | 0.00 | 01-JAN-00:10 | 18.60 | 9.87 |
February | 0.474835E+09 | 599.57 | 20-FEB-14:10 | 22.38 | 8.53 | 0.00 | 0.00 | 01-FEB-00:10 | 22.38 | 8.53 |
March | 0.480837E+09 | 503.71 | 16-MAR-13:30 | 22.50 | 9.16 | 0.00 | 0.00 | 01-MAR-00:10 | 22.50 | 9.16 |
April | 0.615775E+09 | 492.06 | 03-APR-14:00 | 26.70 | 11.71 | 0.00 | 0.00 | 01-APR-00:10 | 26.70 | 11.71 |
May | 0.741915E+09 | 512.18 | 19-MAY-20:20 | 30.73 | 14.26 | 0.00 | 0.00 | 01-MAY-00:10 | 30.73 | 14.26 |
June | 0.878804E+09 | 560.98 | 15-JUN-20:20 | 33.70 | 13.91 | 0.00 | 0.00 | 01-JUN-00:10 | 33.70 | 13.91 |
July | 0.923284E+09 | 573.47 | 02-JUL-20:50 | 32.98 | 17.29 | 0.00 | 0.00 | 01-JUL-00:10 | 32.98 | 17.29 |
August | 0.926030E+09 | 577.40 | 06-AUG-19:05 | 34.63 | 17.82 | 0.00 | 0.00 | 01-AUG-00:10 | 34.63 | 17.82 |
September | 0.946650E+09 | 668.56 | 19-SEP-13:30 | 33.35 | 16.80 | 0.00 | 0.00 | 01-SEP-00:10 | 33.35 | 16.80 |
October | 0.852397E+09 | 735.62 | 22-OCT-13:20 | 25.97 | 14.61 | 0.00 | 0.00 | 01-OCT-00:10 | 25.97 | 14.61 |
November | 0.639842E+09 | 683.34 | 09-NOV-13:50 | 23.22 | 12.39 | 0.00 | 0.00 | 01-NOV-00:10 | 23.22 | 12.39 |
December | 0.466444E+09 | 543.88 | 16-DEC-13:40 | 14.63 | 4.10 | 0.00 | 0.00 | 01-DEC-00:10 | 14.63 | 4.10 |
Annual Sum or Average | 0.844708E+10 | 0.00 | ||||||||
Minimum of Months | 0.466444E+09 | 492.06 | 14.63 | 4.10 | 0.00 | 0.00 | 14.63 | 4.10 | ||
Maximum of Months | 0.946650E+09 | 735.62 | 34.63 | 17.82 | 0.00 | 0.00 | 34.63 | 17.82 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.193106E+09 | 1237.57 | 13-JAN-19:02 | 13.12 | 6.39 | 95349766.29 | 56.69 | 03-JAN-22:00 | 13.12 | 6.39 |
February | 0.253903E+09 | 1305.91 | 20-FEB-16:01 | 23.12 | 8.59 | 86529316.73 | 56.69 | 23-FEB-22:10 | 11.93 | 4.94 |
March | 0.400229E+09 | 1357.97 | 15-MAR-18:01 | 21.60 | 8.24 | 96480864.72 | 56.69 | 03-MAR-22:10 | 21.60 | 8.24 |
April | 0.693938E+09 | 1430.39 | 28-APR-18:01 | 28.03 | 14.00 | 94454876.77 | 56.69 | 06-APR-21:49 | 28.03 | 14.00 |
May | 0.983606E+09 | 1438.17 | 13-MAY-18:01 | 31.42 | 15.36 | 98438927.33 | 56.69 | 29-MAY-00:49 | 18.80 | 14.41 |
June | 0.117155E+10 | 1437.32 | 17-JUN-18:02 | 35.45 | 16.60 | 95732159.98 | 56.70 | 22-JUN-21:40 | 23.30 | 16.17 |
July | 0.119575E+10 | 1335.10 | 15-JUL-15:02 | 32.80 | 18.56 | 98842887.19 | 56.70 | 21-JUL-21:40 | 23.90 | 20.77 |
August | 0.108109E+10 | 1439.01 | 27-AUG-18:01 | 33.12 | 16.39 | 98698823.53 | 56.70 | 02-AUG-21:00 | 33.12 | 16.39 |
September | 0.885854E+09 | 1431.17 | 17-SEP-18:01 | 29.95 | 14.68 | 95133334.79 | 56.69 | 07-SEP-21:10 | 29.95 | 14.68 |
October | 0.652720E+09 | 1429.37 | 01-OCT-18:01 | 29.82 | 14.44 | 97295919.23 | 56.69 | 04-OCT-21:10 | 25.32 | 17.67 |
November | 0.297898E+09 | 1324.44 | 08-NOV-19:01 | 20.92 | 10.67 | 92889171.32 | 56.69 | 02-NOV-21:10 | 20.92 | 10.67 |
December | 0.159631E+09 | 1276.22 | 09-DEC-09:01 | 14.40 | 6.77 | 95019223.60 | 56.69 | 13-DEC-22:10 | 7.80 | 4.56 |
Annual Sum or Average | 0.796927E+10 | 0.114487E+10 | ||||||||
Minimum of Months | 0.159631E+09 | 1237.57 | 13.12 | 6.39 | 86529316.73 | 56.69 | 7.80 | 4.56 | ||
Maximum of Months | 0.119575E+10 | 1439.01 | 35.45 | 18.56 | 98842887.19 | 56.70 | 33.12 | 20.77 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.274171E+09 | 3310.05 | 12-JAN-16:01 | 18.72 | 10.12 | 96118899.68 | 56.69 | 03-JAN-22:10 | 18.72 | 10.12 |
February | 0.455966E+09 | 3362.24 | 20-FEB-16:01 | 23.12 | 8.59 | 87726407.39 | 56.69 | 06-FEB-23:10 | 23.12 | 8.59 |
March | 0.712228E+09 | 3360.55 | 16-MAR-15:01 | 22.70 | 8.66 | 97871812.85 | 56.69 | 06-MAR-22:10 | 22.70 | 8.66 |
April | 0.155353E+10 | 3406.27 | 21-APR-15:01 | 32.02 | 15.38 | 95691315.21 | 56.70 | 28-APR-21:40 | 22.07 | 12.89 |
May | 0.226249E+10 | 3437.47 | 30-MAY-08:61 | 26.78 | 12.99 | 99153022.86 | 56.70 | 24-MAY-21:00 | 26.78 | 12.99 |
June | 0.286530E+10 | 3453.68 | 15-JUN-08:61 | 29.78 | 13.66 | 96019535.39 | 56.70 | 20-JUN-21:10 | 27.02 | 16.19 |
July | 0.285107E+10 | 3199.63 | 09-JUL-08:61 | 24.68 | 18.54 | 99118072.33 | 56.70 | 14-JUL-21:10 | 27.33 | 20.00 |
August | 0.266347E+10 | 3427.25 | 23-AUG-15:01 | 33.30 | 16.20 | 99156042.68 | 56.70 | 09-AUG-21:10 | 33.30 | 16.20 |
September | 0.234031E+10 | 3409.22 | 11-SEP-15:01 | 29.40 | 13.84 | 95901315.46 | 56.70 | 13-SEP-00:49 | 23.90 | 17.48 |
October | 0.146487E+10 | 3423.87 | 01-OCT-15:01 | 32.62 | 15.84 | 98515872.05 | 56.70 | 03-OCT-22:10 | 20.10 | 18.04 |
November | 0.606318E+09 | 3373.31 | 09-NOV-16:01 | 23.22 | 12.98 | 94289220.23 | 56.69 | 09-NOV-23:10 | 16.70 | 10.07 |
December | 0.229294E+09 | 3288.81 | 09-DEC-09:01 | 14.40 | 6.77 | 95802214.83 | 56.69 | 13-DEC-00:10 | 6.47 | 5.55 |
Annual Sum or Average | 0.182790E+11 | 0.115536E+10 | ||||||||
Minimum of Months | 0.229294E+09 | 3199.63 | 14.40 | 6.77 | 87726407.39 | 56.69 | 6.47 | 5.55 | ||
Maximum of Months | 0.286530E+10 | 3453.68 | 33.30 | 18.54 | 99156042.68 | 56.70 | 33.30 | 20.00 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 98970386.78 | 2270.82 | 31-JAN-09:02 | 10.78 | 4.13 | 94272920.95 | 56.69 | 03-JAN-22:19 | 10.78 | 4.13 |
February | 0.227766E+09 | 3276.96 | 20-FEB-09:01 | 11.23 | 4.20 | 86322396.75 | 56.69 | 06-FEB-22:19 | 11.23 | 4.20 |
March | 0.479639E+09 | 3300.11 | 22-MAR-15:01 | 23.90 | 8.87 | 96937660.79 | 56.69 | 16-MAR-22:40 | 23.90 | 8.87 |
April | 0.136197E+10 | 3370.34 | 21-APR-15:01 | 32.02 | 15.38 | 95530553.71 | 56.69 | 28-APR-21:19 | 22.43 | 12.87 |
May | 0.220991E+10 | 3415.24 | 30-MAY-08:61 | 26.78 | 12.99 | 99148123.80 | 56.70 | 24-MAY-21:00 | 26.78 | 12.99 |
June | 0.287962E+10 | 3432.35 | 15-JUN-08:61 | 29.78 | 13.66 | 96021125.42 | 56.70 | 20-JUN-21:10 | 27.02 | 16.19 |
July | 0.283793E+10 | 3175.56 | 09-JUL-08:61 | 24.68 | 18.54 | 99118416.09 | 56.70 | 14-JUL-21:10 | 27.33 | 20.00 |
August | 0.252612E+10 | 3389.82 | 23-AUG-15:01 | 33.30 | 16.20 | 99145490.54 | 56.70 | 04-AUG-21:00 | 33.30 | 16.20 |
September | 0.199157E+10 | 3363.17 | 18-SEP-18:01 | 30.55 | 13.88 | 95866109.18 | 56.70 | 08-SEP-21:49 | 30.55 | 13.88 |
October | 0.101415E+10 | 3361.38 | 01-OCT-15:01 | 32.62 | 15.84 | 98021283.60 | 56.70 | 04-OCT-21:00 | 23.90 | 17.47 |
November | 0.268382E+09 | 3265.24 | 11-NOV-09:01 | 11.65 | 7.11 | 92634849.61 | 56.69 | 09-NOV-22:10 | 11.65 | 7.11 |
December | 87426467.33 | 3068.81 | 09-DEC-09:01 | 14.40 | 6.77 | 93930757.62 | 56.69 | 13-DEC-00:10 | 6.47 | 5.55 |
Annual Sum or Average | 0.159835E+11 | 0.114695E+10 | ||||||||
Minimum of Months | 87426467.33 | 2270.82 | 10.78 | 4.13 | 86322396.75 | 56.69 | 6.47 | 4.13 | ||
Maximum of Months | 0.287962E+10 | 3432.35 | 33.30 | 18.54 | 99148123.80 | 56.70 | 33.30 | 20.00 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.272649E+10 | 2019.50 | 12-JAN-21:10 | 12.43 | 7.05 | 0.119883E+10 | 706.46 | 03-JAN-22:30 | 12.43 | 7.05 |
February | 0.301152E+10 | 2223.02 | 21-FEB-17:20 | 21.67 | 7.52 | 0.108454E+10 | 718.77 | 06-FEB-22:40 | 21.67 | 7.52 |
March | 0.386106E+10 | 2443.30 | 16-MAR-18:10 | 19.82 | 7.14 | 0.120634E+10 | 727.33 | 16-MAR-21:40 | 16.47 | 6.01 |
April | 0.508803E+10 | 2790.56 | 30-APR-10:35 | 24.07 | 13.08 | 0.118305E+10 | 759.82 | 21-APR-21:49 | 24.07 | 13.08 |
May | 0.602453E+10 | 2988.55 | 31-MAY-18:10 | 30.92 | 15.25 | 0.126758E+10 | 790.94 | 19-MAY-22:10 | 30.92 | 15.25 |
June | 0.644376E+10 | 3255.23 | 15-JUN-18:10 | 35.92 | 14.47 | 0.128919E+10 | 826.08 | 16-JUN-22:10 | 30.92 | 15.69 |
July | 0.658709E+10 | 3202.42 | 03-JUL-18:10 | 36.28 | 18.94 | 0.131633E+10 | 810.70 | 27-JUL-21:49 | 28.40 | 18.33 |
August | 0.646313E+10 | 3195.71 | 07-AUG-18:10 | 33.95 | 18.47 | 0.131241E+10 | 819.29 | 07-AUG-21:49 | 29.45 | 17.70 |
September | 0.607490E+10 | 3036.52 | 20-SEP-18:10 | 31.05 | 16.15 | 0.124814E+10 | 799.73 | 21-SEP-22:10 | 26.02 | 17.91 |
October | 0.541014E+10 | 2919.31 | 05-OCT-10:35 | 27.60 | 18.63 | 0.123252E+10 | 783.42 | 05-OCT-21:49 | 22.88 | 16.22 |
November | 0.368785E+10 | 2532.30 | 10-NOV-11:35 | 20.93 | 12.02 | 0.116217E+10 | 733.48 | 09-NOV-22:40 | 20.93 | 12.02 |
December | 0.240032E+10 | 1917.06 | 15-DEC-22:03 | 14.32 | 4.61 | 0.119882E+10 | 704.52 | 20-DEC-04:40 | 8.13 | -1.0 |
Annual Sum or Average | 0.577788E+11 | 0.146999E+11 | ||||||||
Minimum of Months | 0.240032E+10 | 1917.06 | 12.43 | 4.61 | 0.108454E+10 | 704.52 | 8.13 | -1.0 | ||
Maximum of Months | 0.658709E+10 | 3255.23 | 36.28 | 18.94 | 0.131633E+10 | 826.08 | 30.92 | 18.33 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.248610E+09 | 4050.02 | 12-JAN-16:01 | 18.72 | 10.12 | 95577812.88 | 56.69 | 03-JAN-22:19 | 18.72 | 10.12 |
February | 0.390109E+09 | 4134.16 | 20-FEB-16:01 | 23.12 | 8.59 | 87042066.83 | 56.69 | 20-FEB-01:10 | 23.12 | 8.59 |
March | 0.703454E+09 | 4127.26 | 14-MAR-15:01 | 23.98 | 9.90 | 97281698.01 | 56.69 | 16-MAR-22:10 | 15.27 | 5.99 |
April | 0.165512E+10 | 4185.30 | 30-APR-15:01 | 30.10 | 12.65 | 95186459.95 | 56.70 | 25-APR-04:19 | 30.10 | 12.65 |
May | 0.251895E+10 | 4206.83 | 20-MAY-15:01 | 32.20 | 15.53 | 98862823.56 | 56.70 | 23-MAY-21:49 | 21.28 | 15.82 |
June | 0.320649E+10 | 4203.83 | 15-JUN-15:02 | 38.22 | 15.87 | 95942424.46 | 56.70 | 19-JUN-01:39 | 24.80 | 16.53 |
July | 0.321434E+10 | 3706.06 | 26-JUL-08:61 | 29.08 | 18.80 | 99064124.72 | 56.70 | 06-JUL-21:10 | 29.08 | 18.80 |
August | 0.298239E+10 | 4206.00 | 23-AUG-15:01 | 33.30 | 16.20 | 99070432.45 | 56.70 | 07-AUG-21:49 | 33.30 | 16.20 |
September | 0.261398E+10 | 4210.81 | 11-SEP-15:01 | 29.40 | 13.84 | 95710199.37 | 56.70 | 07-SEP-22:10 | 29.40 | 13.84 |
October | 0.165992E+10 | 4215.21 | 01-OCT-15:01 | 32.62 | 15.84 | 98327146.24 | 56.70 | 04-OCT-22:40 | 23.17 | 16.85 |
November | 0.614909E+09 | 4141.38 | 09-NOV-16:01 | 23.22 | 12.98 | 93750898.77 | 56.69 | 09-NOV-22:40 | 17.43 | 10.49 |
December | 0.174374E+09 | 3980.47 | 17-DEC-16:01 | 15.32 | 4.54 | 95249776.99 | 56.69 | 15-DEC-22:19 | 15.32 | 4.54 |
Annual Sum or Average | 0.199826E+11 | 0.115107E+10 | ||||||||
Minimum of Months | 0.174374E+09 | 3706.06 | 15.32 | 4.54 | 87042066.83 | 56.69 | 15.27 | 4.54 | ||
Maximum of Months | 0.321434E+10 | 4215.21 | 38.22 | 18.80 | 99070432.45 | 56.70 | 33.30 | 18.80 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 88467892.38 | 3905.56 | 12-JAN-16:01 | 18.72 | 10.12 | 93855983.55 | 56.69 | 04-JAN-00:20 | 18.72 | 10.12 |
February | 0.185794E+09 | 4041.96 | 20-FEB-16:01 | 23.12 | 8.59 | 85733302.50 | 56.69 | 06-FEB-22:40 | 23.12 | 8.59 |
March | 0.469378E+09 | 4036.89 | 16-MAR-15:01 | 22.70 | 8.66 | 96401922.21 | 56.69 | 15-MAR-21:10 | 22.70 | 8.66 |
April | 0.145822E+10 | 4142.67 | 30-APR-15:01 | 30.10 | 12.65 | 94981929.43 | 56.70 | 26-APR-02:30 | 30.10 | 12.65 |
May | 0.246559E+10 | 4171.66 | 20-MAY-15:01 | 32.20 | 15.53 | 98844529.41 | 56.70 | 02-MAY-02:49 | 32.20 | 15.53 |
June | 0.322086E+10 | 4183.35 | 15-JUN-18:02 | 35.92 | 14.47 | 95962329.46 | 56.70 | 16-JUN-22:10 | 30.92 | 15.69 |
July | 0.320034E+10 | 3690.46 | 26-JUL-08:61 | 29.08 | 18.80 | 99076531.03 | 56.70 | 27-JUL-21:10 | 28.80 | 18.36 |
August | 0.283914E+10 | 4159.28 | 23-AUG-15:01 | 33.30 | 16.20 | 99051490.59 | 56.70 | 07-AUG-21:49 | 33.30 | 16.20 |
September | 0.225231E+10 | 4147.11 | 11-SEP-15:01 | 29.40 | 13.84 | 95588524.86 | 56.70 | 13-SEP-21:00 | 21.70 | 17.53 |
October | 0.118511E+10 | 4136.31 | 01-OCT-15:01 | 32.62 | 15.84 | 97811138.60 | 56.70 | 10-OCT-01:39 | 13.90 | 9.09 |
November | 0.259538E+09 | 4052.63 | 09-NOV-16:01 | 23.22 | 12.98 | 92442734.17 | 56.69 | 09-NOV-01:39 | 23.22 | 12.98 |
December | 64245030.83 | 3451.10 | 16-DEC-16:02 | 14.72 | 4.08 | 93454623.04 | 56.69 | 13-DEC-00:10 | 14.72 | 4.08 |
Annual Sum or Average | 0.176890E+11 | 0.114321E+10 | ||||||||
Minimum of Months | 64245030.83 | 3451.10 | 14.72 | 4.08 | 85733302.50 | 56.69 | 13.90 | 4.08 | ||
Maximum of Months | 0.322086E+10 | 4183.35 | 35.92 | 18.80 | 99076531.03 | 56.70 | 33.30 | 18.36 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.590227E+09 | 2144.90 | 12-JAN-16:01 | 18.72 | 10.12 | 97522172.46 | 56.69 | 20-JAN-22:19 | 10.20 | 4.85 |
February | 0.615629E+09 | 2163.14 | 20-FEB-16:01 | 23.12 | 8.59 | 88407106.27 | 56.69 | 06-FEB-22:10 | 23.12 | 8.59 |
March | 0.658002E+09 | 2163.13 | 14-MAR-15:01 | 23.98 | 9.90 | 98009783.40 | 56.69 | 16-MAR-21:00 | 16.10 | 6.03 |
April | 0.101502E+10 | 2159.09 | 03-APR-15:01 | 26.88 | 11.50 | 95291983.39 | 56.69 | 28-APR-22:10 | 21.52 | 12.87 |
May | 0.132144E+10 | 2157.59 | 20-MAY-15:01 | 32.20 | 15.53 | 98826960.97 | 56.69 | 22-MAY-22:00 | 22.80 | 14.76 |
June | 0.164706E+10 | 2155.36 | 12-JUN-15:01 | 33.98 | 15.96 | 95899522.66 | 56.70 | 07-JUN-21:10 | 33.98 | 15.96 |
July | 0.171716E+10 | 1981.99 | 23-JUL-18:02 | 31.02 | 18.90 | 99029496.64 | 56.70 | 26-JUL-21:00 | 27.20 | 18.25 |
August | 0.169997E+10 | 1972.67 | 31-AUG-18:01 | 27.52 | 16.76 | 99053274.08 | 56.70 | 03-AUG-21:40 | 27.52 | 16.76 |
September | 0.167679E+10 | 2180.20 | 30-SEP-15:01 | 28.30 | 13.14 | 95752774.77 | 56.70 | 20-SEP-22:10 | 28.30 | 13.14 |
October | 0.139255E+10 | 2196.57 | 01-OCT-15:01 | 32.62 | 15.84 | 98619859.56 | 56.70 | 18-OCT-21:10 | 21.60 | 16.55 |
November | 0.876308E+09 | 2171.97 | 09-NOV-16:01 | 23.22 | 12.98 | 94877090.60 | 56.69 | 09-NOV-22:00 | 16.70 | 10.18 |
December | 0.538285E+09 | 2113.72 | 30-DEC-16:01 | 12.02 | 4.39 | 97423062.39 | 56.69 | 05-DEC-22:19 | 12.02 | 4.39 |
Annual Sum or Average | 0.137484E+11 | 0.115871E+10 | ||||||||
Minimum of Months | 0.538285E+09 | 1972.67 | 12.02 | 4.39 | 88407106.27 | 56.69 | 10.20 | 4.39 | ||
Maximum of Months | 0.171716E+10 | 2196.57 | 33.98 | 18.90 | 99053274.08 | 56.70 | 33.98 | 18.25 |
Report: ZoneCoolingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.383879E+11 | 19070.69 | 03-JAN-22:20 | 12.07 | 5.91 | 0.149050E+11 | 9769.05 | 03-JAN-22:19 | 12.07 | 5.91 |
February | 0.359952E+11 | 19607.35 | 07-FEB-23:00 | 15.60 | 8.35 | 0.135697E+11 | 9970.03 | 06-FEB-23:10 | 15.60 | 8.35 |
March | 0.416247E+11 | 20039.51 | 15-MAR-22:00 | 19.40 | 7.29 | 0.152631E+11 | 10134.44 | 15-MAR-22:10 | 19.32 | 7.27 |
April | 0.442123E+11 | 22065.71 | 19-APR-18:10 | 29.90 | 13.60 | 0.150953E+11 | 10476.51 | 19-APR-22:10 | 26.93 | 11.76 |
May | 0.486655E+11 | 23213.15 | 31-MAY-18:10 | 30.92 | 15.25 | 0.159465E+11 | 10687.16 | 19-MAY-22:10 | 30.92 | 15.25 |
June | 0.499971E+11 | 24499.85 | 15-JUN-18:10 | 35.92 | 14.47 | 0.157937E+11 | 10850.30 | 16-JUN-22:10 | 30.92 | 15.69 |
July | 0.514189E+11 | 24280.63 | 03-JUL-18:10 | 36.28 | 18.94 | 0.161822E+11 | 10748.27 | 25-JUL-22:10 | 30.00 | 17.07 |
August | 0.503507E+11 | 23987.51 | 07-AUG-18:10 | 33.95 | 18.47 | 0.161545E+11 | 10754.53 | 07-AUG-21:40 | 29.90 | 17.57 |
September | 0.468881E+11 | 22615.40 | 20-SEP-18:10 | 31.05 | 16.15 | 0.153062E+11 | 10521.10 | 22-SEP-22:10 | 24.90 | 17.87 |
October | 0.448065E+11 | 21917.29 | 05-OCT-18:10 | 27.15 | 16.93 | 0.154801E+11 | 10373.23 | 04-OCT-22:10 | 27.15 | 16.93 |
November | 0.389784E+11 | 19951.85 | 09-NOV-22:20 | 18.17 | 10.78 | 0.145649E+11 | 10054.29 | 09-NOV-22:30 | 17.80 | 10.64 |
December | 0.375444E+11 | 19120.60 | 15-DEC-23:00 | 13.90 | 4.56 | 0.148163E+11 | 9809.55 | 15-DEC-23:10 | 13.80 | 4.57 |
Annual Sum or Average | 0.528870E+12 | 0.183077E+12 | ||||||||
Minimum of Months | 0.359952E+11 | 19070.69 | 12.07 | 4.56 | 0.135697E+11 | 9769.05 | 12.07 | 4.57 | ||
Maximum of Months | 0.514189E+11 | 24499.85 | 36.28 | 18.94 | 0.161822E+11 | 10850.30 | 30.92 | 17.87 |
Report: ZoneCoolingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.413369E+11 | 20251.88 | 03-JAN-22:10 | 12.43 | 6.06 | 0.149783E+11 | 9857.13 | 03-JAN-22:19 | 12.07 | 5.91 |
February | 0.387138E+11 | 20815.43 | 07-FEB-23:00 | 15.60 | 8.35 | 0.136433E+11 | 10056.22 | 06-FEB-23:10 | 15.60 | 8.35 |
March | 0.447170E+11 | 21290.66 | 22-MAR-18:10 | 20.22 | 7.33 | 0.153570E+11 | 10229.01 | 15-MAR-22:10 | 20.22 | 7.33 |
April | 0.473129E+11 | 23417.60 | 19-APR-18:10 | 29.90 | 13.60 | 0.152086E+11 | 10572.79 | 19-APR-22:10 | 26.93 | 11.76 |
May | 0.519392E+11 | 24608.28 | 31-MAY-18:10 | 30.92 | 15.25 | 0.160784E+11 | 10781.93 | 19-MAY-22:10 | 30.92 | 15.25 |
June | 0.531142E+11 | 25884.23 | 15-JUN-18:10 | 35.92 | 14.47 | 0.159033E+11 | 10926.48 | 16-JUN-22:10 | 30.92 | 15.69 |
July | 0.546406E+11 | 25630.03 | 03-JUL-18:10 | 36.28 | 18.94 | 0.162967E+11 | 10828.41 | 25-JUL-22:10 | 30.00 | 17.07 |
August | 0.535582E+11 | 25318.51 | 07-AUG-18:10 | 33.95 | 18.47 | 0.162667E+11 | 10816.24 | 07-AUG-21:40 | 29.90 | 17.57 |
September | 0.499603E+11 | 23921.91 | 20-SEP-18:10 | 31.05 | 16.15 | 0.154127E+11 | 10604.98 | 22-SEP-22:10 | 24.90 | 17.87 |
October | 0.479125E+11 | 23218.87 | 05-OCT-18:10 | 27.15 | 16.93 | 0.155777E+11 | 10459.05 | 04-OCT-22:10 | 27.15 | 16.93 |
November | 0.418798E+11 | 21178.26 | 09-NOV-22:10 | 18.53 | 10.92 | 0.146431E+11 | 10144.33 | 09-NOV-22:19 | 18.17 | 10.78 |
December | 0.404819E+11 | 20297.43 | 15-DEC-23:00 | 13.90 | 4.56 | 0.148866E+11 | 9895.48 | 15-DEC-23:10 | 13.80 | 4.57 |
Annual Sum or Average | 0.565567E+12 | 0.184253E+12 | ||||||||
Minimum of Months | 0.387138E+11 | 20251.88 | 12.43 | 4.56 | 0.136433E+11 | 9857.13 | 12.07 | 4.57 | ||
Maximum of Months | 0.546406E+11 | 25884.23 | 36.28 | 18.94 | 0.162967E+11 | 10926.48 | 30.92 | 17.87 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.509864E+11 | 26380.58 | 01-JAN-11:50 | 14.13 | 8.64 | 0.186232E+11 | 11319.39 | 21-JAN-18:19 | 9.83 | 5.36 |
February | 0.471125E+11 | 27731.00 | 20-FEB-11:50 | 20.73 | 8.30 | 0.168317E+11 | 11319.48 | 04-FEB-18:19 | 20.73 | 8.30 |
March | 0.534071E+11 | 27865.57 | 19-MAR-10:50 | 19.03 | 7.15 | 0.186483E+11 | 11319.55 | 18-MAR-17:19 | 19.03 | 7.15 |
April | 0.547888E+11 | 29809.53 | 30-APR-10:40 | 24.07 | 13.08 | 0.180644E+11 | 11319.65 | 15-APR-17:19 | 24.07 | 13.08 |
May | 0.588731E+11 | 30087.43 | 21-MAY-10:50 | 30.03 | 14.61 | 0.186812E+11 | 11319.66 | 06-MAY-17:19 | 30.03 | 14.61 |
June | 0.590953E+11 | 30779.39 | 18-JUN-10:50 | 32.62 | 16.28 | 0.180923E+11 | 11319.65 | 24-JUN-17:19 | 31.67 | 16.29 |
July | 0.609821E+11 | 30956.25 | 02-JUL-10:40 | 32.23 | 20.13 | 0.186883E+11 | 11319.66 | 15-JUL-17:19 | 32.20 | 17.96 |
August | 0.603074E+11 | 30809.68 | 06-AUG-10:40 | 31.67 | 18.03 | 0.186901E+11 | 11319.65 | 19-AUG-17:19 | 31.33 | 15.73 |
September | 0.573197E+11 | 30236.51 | 17-SEP-10:40 | 29.47 | 15.71 | 0.180761E+11 | 11319.65 | 30-SEP-17:19 | 26.47 | 12.09 |
October | 0.561406E+11 | 29612.84 | 05-OCT-10:50 | 27.70 | 18.68 | 0.186595E+11 | 11319.63 | 21-OCT-17:19 | 24.83 | 12.12 |
November | 0.508316E+11 | 27587.58 | 10-NOV-11:50 | 21.02 | 12.06 | 0.180344E+11 | 11319.48 | 18-NOV-18:19 | 13.90 | 3.79 |
December | 0.504082E+11 | 26419.78 | 10-DEC-11:50 | 16.32 | 7.64 | 0.186188E+11 | 11319.39 | 16-DEC-18:19 | 9.43 | 2.03 |
Annual Sum or Average | 0.660253E+12 | 0.219708E+12 | ||||||||
Minimum of Months | 0.471125E+11 | 26380.58 | 14.13 | 7.15 | 0.168317E+11 | 11319.39 | 9.43 | 2.03 | ||
Maximum of Months | 0.609821E+11 | 30956.25 | 32.62 | 20.13 | 0.186901E+11 | 11319.66 | 32.20 | 17.96 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.288691E+10 | 4769.52 | 12-JAN-14:30 | 18.60 | 9.87 | 0.126879E+10 | 745.75 | 26-JAN-05:30 | 1.40 | -1.1 |
February | 0.382025E+10 | 5042.60 | 22-FEB-13:00 | 20.60 | 7.49 | 0.114713E+10 | 745.80 | 24-FEB-05:10 | 5.40 | 0.22 |
March | 0.546427E+10 | 5530.53 | 14-MAR-15:50 | 24.32 | 10.24 | 0.127478E+10 | 745.74 | 01-MAR-05:49 | 24.32 | 10.24 |
April | 0.927115E+10 | 6616.80 | 30-APR-10:35 | 24.07 | 13.08 | 0.123278E+10 | 772.25 | 19-APR-22:10 | 24.07 | 13.08 |
May | 0.124422E+11 | 7067.27 | 21-MAY-10:35 | 29.47 | 14.38 | 0.128380E+10 | 799.90 | 19-MAY-22:10 | 29.47 | 14.38 |
June | 0.146214E+11 | 7698.13 | 17-JUN-17:13 | 36.10 | 16.68 | 0.128851E+10 | 832.68 | 16-JUN-22:10 | 36.10 | 16.68 |
July | 0.150368E+11 | 7803.58 | 03-JUL-10:35 | 34.07 | 18.96 | 0.131954E+10 | 832.94 | 02-JUL-23:19 | 34.07 | 18.96 |
August | 0.143496E+11 | 7618.31 | 07-AUG-17:13 | 35.93 | 18.20 | 0.131399E+10 | 836.10 | 07-AUG-21:49 | 29.45 | 17.70 |
September | 0.126279E+11 | 7168.64 | 03-SEP-10:35 | 26.10 | 18.93 | 0.124843E+10 | 793.66 | 22-SEP-22:10 | 24.90 | 17.87 |
October | 0.959752E+10 | 6950.49 | 05-OCT-10:35 | 27.60 | 18.63 | 0.127471E+10 | 776.67 | 01-OCT-23:19 | 27.60 | 18.63 |
November | 0.486700E+10 | 5517.56 | 03-NOV-15:50 | 23.80 | 13.47 | 0.122746E+10 | 745.74 | 27-NOV-22:10 | 1.83 | -0.3 |
December | 0.229145E+10 | 3806.48 | 16-DEC-13:40 | 14.63 | 4.10 | 0.126875E+10 | 745.76 | 01-DEC-00:40 | 14.63 | 4.10 |
Annual Sum or Average | 0.107276E+12 | 0.151487E+11 | ||||||||
Minimum of Months | 0.229145E+10 | 3806.48 | 14.63 | 4.10 | 0.114713E+10 | 745.74 | 1.40 | -1.1 | ||
Maximum of Months | 0.150368E+11 | 7803.58 | 36.10 | 18.96 | 0.131954E+10 | 836.10 | 36.10 | 18.96 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 6.70 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 6.42 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 7.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 10.60 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 8.95 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 6.42 | |
Maximum of Months | 0.00 | 0.00 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.109949E+09 | 887.86 | 27-JAN-07:30 | -4.2 |
February | 78823572.08 | 909.12 | 03-FEB-07:10 | -5.1 |
March | 43243123.36 | 764.55 | 02-MAR-05:00 | -3.9 |
April | 410897.60 | 130.00 | 12-APR-06:10 | 3.87 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 43883777.54 | 723.12 | 28-NOV-05:00 | -0.6 |
December | 0.230933E+09 | 1056.41 | 27-DEC-07:30 | -4.2 |
Annual Sum or Average | 0.507243E+09 | |||
Minimum of Months | 0.00 | 0.00 | -5.1 | |
Maximum of Months | 0.230933E+09 | 1056.41 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 6.70 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 6.42 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 7.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 10.60 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 8.95 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 6.42 | |
Maximum of Months | 0.00 | 0.00 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 9041394.52 | 316.27 | 28-JAN-06:00 | -3.3 |
February | 7626893.52 | 292.36 | 03-FEB-05:00 | -3.9 |
March | 2288372.44 | 236.54 | 02-MAR-04:50 | -3.7 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 1845520.06 | 182.30 | 28-NOV-04:50 | -0.6 |
December | 33057533.53 | 341.56 | 27-DEC-05:00 | -3.9 |
Annual Sum or Average | 53859714.07 | |||
Minimum of Months | 0.00 | 0.00 | -3.9 | |
Maximum of Months | 33057533.53 | 341.56 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 61964931.08 | 293.07 | 28-JAN-07:10 | -2.9 |
February | 42402309.65 | 276.72 | 03-FEB-07:10 | -5.1 |
March | 11546376.21 | 251.75 | 02-MAR-05:00 | -3.9 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 18870964.07 | 209.23 | 28-NOV-04:40 | -0.6 |
December | 0.130343E+09 | 292.99 | 27-DEC-05:00 | -3.9 |
Annual Sum or Average | 0.265127E+09 | |||
Minimum of Months | 0.00 | 0.00 | -5.1 | |
Maximum of Months | 0.130343E+09 | 293.07 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 6.70 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 6.42 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 7.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 10.60 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 8.95 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 6.42 | |
Maximum of Months | 0.00 | 0.00 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 6.70 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 6.42 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 7.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 10.60 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 8.95 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 6.42 | |
Maximum of Months | 0.00 | 0.00 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 6.70 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 6.42 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 7.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 10.60 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 8.95 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 6.42 | |
Maximum of Months | 0.00 | 0.00 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.372014E+09 | 1834.88 | 15-JAN-16:01 | 10.00 |
February | 0.238582E+09 | 1760.62 | 13-FEB-16:02 | 12.30 |
March | 0.134316E+09 | 1769.65 | 29-MAR-08:62 | 8.87 |
April | 15805829.56 | 1704.16 | 11-APR-08:62 | 6.88 |
May | 1103260.87 | 861.17 | 10-MAY-08:03 | 20.78 |
June | 590973.94 | 456.99 | 25-JUN-08:04 | 22.67 |
July | 836993.26 | 628.07 | 18-JUL-08:04 | 24.08 |
August | 961951.66 | 632.87 | 12-AUG-08:04 | 22.57 |
September | 931535.85 | 660.76 | 27-SEP-08:03 | 19.27 |
October | 3262557.52 | 954.51 | 30-OCT-08:03 | 15.37 |
November | 0.190436E+09 | 1837.69 | 28-NOV-16:01 | 11.52 |
December | 0.504449E+09 | 1803.68 | 02-DEC-16:02 | 8.12 |
Annual Sum or Average | 0.146329E+10 | |||
Minimum of Months | 590973.94 | 456.99 | 6.88 | |
Maximum of Months | 0.504449E+09 | 1837.69 | 24.08 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.609341E+09 | 1836.66 | 15-JAN-16:01 | 10.00 |
February | 0.385902E+09 | 1806.27 | 04-FEB-09:01 | 7.25 |
March | 0.201214E+09 | 1782.63 | 29-MAR-08:62 | 8.87 |
April | 20993663.65 | 1706.50 | 11-APR-08:62 | 6.88 |
May | 1038264.67 | 805.11 | 08-MAY-08:03 | 20.23 |
June | 547324.30 | 424.04 | 23-JUN-08:04 | 21.97 |
July | 776307.87 | 666.56 | 21-JUL-08:04 | 22.30 |
August | 1087888.33 | 669.98 | 23-AUG-08:04 | 24.27 |
September | 1169681.80 | 865.29 | 11-SEP-08:03 | 21.57 |
October | 7878178.48 | 1079.32 | 25-OCT-08:62 | 11.15 |
November | 0.308103E+09 | 1850.92 | 28-NOV-16:01 | 11.52 |
December | 0.799465E+09 | 1826.37 | 13-DEC-09:01 | 9.40 |
Annual Sum or Average | 0.233752E+10 | |||
Minimum of Months | 547324.30 | 424.04 | 6.88 | |
Maximum of Months | 0.799465E+09 | 1850.92 | 24.27 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 6.70 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 6.42 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 7.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 10.60 |
December | 158.21 | 0.26 | 27-DEC-06:00 | -3.3 |
Annual Sum or Average | 158.21 | |||
Minimum of Months | 0.00 | 0.00 | -3.3 | |
Maximum of Months | 158.21 | 0.26 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 20620800.19 | 562.86 | 27-JAN-16:02 | 9.50 |
February | 15412684.98 | 559.35 | 02-FEB-16:02 | 10.60 |
March | 4292490.97 | 553.50 | 02-MAR-16:01 | 12.30 |
April | 1313522.46 | 570.71 | 11-APR-15:03 | 16.78 |
May | 368181.41 | 435.19 | 23-MAY-08:04 | 23.27 |
June | 124752.00 | 312.83 | 23-JUN-08:04 | 21.97 |
July | 55170.03 | 302.99 | 05-JUL-08:05 | 22.57 |
August | 210156.17 | 449.70 | 24-AUG-08:04 | 21.60 |
September | 402359.53 | 430.32 | 21-SEP-08:04 | 23.17 |
October | 1151771.59 | 407.55 | 24-OCT-15:03 | 17.88 |
November | 5531134.35 | 558.91 | 28-NOV-16:01 | 11.52 |
December | 45383597.97 | 569.54 | 28-DEC-16:01 | 10.50 |
Annual Sum or Average | 94866621.66 | |||
Minimum of Months | 55170.03 | 302.99 | 9.50 | |
Maximum of Months | 45383597.97 | 570.71 | 23.27 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.388024E+09 | 1763.03 | 15-JAN-16:01 | 10.00 |
February | 0.223333E+09 | 1692.49 | 13-FEB-16:02 | 12.30 |
March | 0.135824E+09 | 1658.66 | 24-MAR-08:62 | 6.05 |
April | 15177785.98 | 705.99 | 20-APR-08:04 | 20.78 |
May | 283197.87 | 567.54 | 23-MAY-08:04 | 23.27 |
June | 71840.83 | 329.22 | 22-JUN-08:04 | 21.88 |
July | 95548.58 | 601.59 | 07-JUL-08:04 | 23.80 |
August | 338927.49 | 584.48 | 24-AUG-08:04 | 21.60 |
September | 177162.37 | 522.55 | 22-SEP-08:04 | 23.12 |
October | 6324389.23 | 889.98 | 15-OCT-18:03 | 18.72 |
November | 0.205461E+09 | 1758.61 | 28-NOV-16:01 | 11.52 |
December | 0.507900E+09 | 1724.51 | 02-DEC-16:02 | 8.12 |
Annual Sum or Average | 0.148301E+10 | |||
Minimum of Months | 71840.83 | 329.22 | 6.05 | |
Maximum of Months | 0.507900E+09 | 1763.03 | 23.80 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.618835E+09 | 1764.71 | 15-JAN-16:01 | 10.00 |
February | 0.345937E+09 | 1738.62 | 01-FEB-16:01 | 9.90 |
March | 0.196390E+09 | 1724.68 | 02-MAR-16:01 | 12.30 |
April | 20312461.23 | 1116.00 | 11-APR-15:03 | 16.78 |
May | 371351.74 | 584.71 | 23-MAY-08:04 | 23.27 |
June | 71858.18 | 332.75 | 22-JUN-08:04 | 21.88 |
July | 103677.60 | 609.08 | 07-JUL-08:04 | 23.80 |
August | 387822.54 | 652.62 | 17-AUG-18:04 | 25.50 |
September | 412101.99 | 604.36 | 22-SEP-08:04 | 23.12 |
October | 15222719.72 | 931.85 | 31-OCT-18:03 | 16.97 |
November | 0.315941E+09 | 1771.41 | 28-NOV-16:01 | 11.52 |
December | 0.786364E+09 | 1774.29 | 19-DEC-16:01 | 9.22 |
Annual Sum or Average | 0.230035E+10 | |||
Minimum of Months | 71858.18 | 332.75 | 9.22 | |
Maximum of Months | 0.786364E+09 | 1774.29 | 25.50 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 1305670.51 | 222.73 | 27-JAN-07:30 | -4.2 |
February | 889388.26 | 206.56 | 02-FEB-07:10 | -4.0 |
March | 339432.62 | 104.14 | 02-MAR-09:08 | 0.47 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 1632361.19 | 147.62 | 27-NOV-09:07 | 3.98 |
December | 10059523.70 | 451.22 | 27-DEC-07:30 | -4.2 |
Annual Sum or Average | 14226376.28 | |||
Minimum of Months | 0.00 | 0.00 | -4.2 | |
Maximum of Months | 10059523.70 | 451.22 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.657972E+09 | 2187.86 | 15-JAN-16:01 | 10.00 |
February | 0.432493E+09 | 2103.37 | 13-FEB-16:02 | 12.30 |
March | 0.266924E+09 | 2115.94 | 29-MAR-08:62 | 8.87 |
April | 37599693.35 | 2097.14 | 12-APR-08:61 | 11.15 |
May | 1076156.05 | 811.87 | 10-MAY-08:03 | 20.78 |
June | 285618.66 | 321.41 | 25-JUN-08:04 | 22.67 |
July | 447841.87 | 630.40 | 21-JUL-08:04 | 22.30 |
August | 732829.66 | 646.93 | 30-AUG-08:03 | 21.47 |
September | 976969.43 | 715.31 | 26-SEP-08:03 | 20.78 |
October | 14095507.31 | 1021.35 | 28-OCT-08:03 | 13.68 |
November | 0.350652E+09 | 2190.53 | 28-NOV-16:01 | 11.52 |
December | 0.856455E+09 | 2158.30 | 02-DEC-16:02 | 8.12 |
Annual Sum or Average | 0.261971E+10 | |||
Minimum of Months | 285618.66 | 321.41 | 8.12 | |
Maximum of Months | 0.856455E+09 | 2190.53 | 22.67 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.985178E+09 | 2185.17 | 15-JAN-16:01 | 10.00 |
February | 0.638292E+09 | 2162.85 | 04-FEB-09:01 | 7.25 |
March | 0.362838E+09 | 2130.69 | 29-MAR-08:62 | 8.87 |
April | 45907394.94 | 2102.64 | 12-APR-08:61 | 11.15 |
May | 1085330.04 | 824.32 | 10-MAY-08:03 | 20.78 |
June | 229874.38 | 372.85 | 30-JUN-08:04 | 22.38 |
July | 403380.42 | 668.13 | 21-JUL-08:04 | 22.30 |
August | 815084.68 | 776.17 | 30-AUG-08:03 | 21.47 |
September | 1485978.68 | 796.97 | 12-SEP-08:03 | 22.15 |
October | 29190069.47 | 2056.06 | 25-OCT-08:62 | 11.15 |
November | 0.530826E+09 | 2189.36 | 28-NOV-16:01 | 11.52 |
December | 0.125169E+10 | 2178.64 | 13-DEC-09:01 | 9.40 |
Annual Sum or Average | 0.384794E+10 | |||
Minimum of Months | 229874.38 | 372.85 | 7.25 | |
Maximum of Months | 0.125169E+10 | 2189.36 | 22.38 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.108530E+09 | 1131.30 | 15-JAN-16:01 | 10.00 |
February | 72922663.11 | 997.65 | 02-FEB-09:02 | 1.38 |
March | 50396396.88 | 1075.18 | 24-MAR-08:62 | 6.05 |
April | 7223194.65 | 759.75 | 11-APR-08:62 | 6.88 |
May | 815201.69 | 462.70 | 19-MAY-08:04 | 24.27 |
June | 613680.94 | 426.22 | 27-JUN-08:04 | 23.58 |
July | 658238.61 | 463.51 | 07-JUL-08:04 | 23.80 |
August | 655625.51 | 434.94 | 02-AUG-08:04 | 24.18 |
September | 518580.02 | 401.95 | 22-SEP-08:04 | 23.12 |
October | 643224.79 | 434.49 | 15-OCT-08:04 | 13.90 |
November | 60387807.52 | 1115.61 | 28-NOV-16:01 | 11.52 |
December | 0.165579E+09 | 1092.42 | 02-DEC-16:02 | 8.12 |
Annual Sum or Average | 0.468944E+09 | |||
Minimum of Months | 518580.02 | 401.95 | 1.38 | |
Maximum of Months | 0.165579E+09 | 1131.30 | 24.27 |
Report: ZoneHeatingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 6.70 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 6.42 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 7.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 10.60 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 8.95 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 6.42 | |
Maximum of Months | 0.00 | 0.00 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 6.70 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 6.42 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 7.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 10.60 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 8.95 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 6.42 | |
Maximum of Months | 0.00 | 0.00 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 6.70 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 6.42 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 7.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 10.60 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 8.95 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 6.42 | |
Maximum of Months | 0.00 | 0.00 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.387985E+09 | 2457.07 | 27-JAN-07:30 | -4.2 |
February | 0.265251E+09 | 2591.29 | 03-FEB-07:30 | -4.2 |
March | 0.128233E+09 | 2190.29 | 02-MAR-07:10 | -1.6 |
April | 1833503.41 | 502.23 | 12-APR-06:10 | 3.87 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 0.170181E+09 | 1663.81 | 28-NOV-06:10 | 1.02 |
December | 0.804114E+09 | 2683.58 | 27-DEC-07:30 | -4.2 |
Annual Sum or Average | 0.175760E+10 | |||
Minimum of Months | 0.00 | 0.00 | -4.2 | |
Maximum of Months | 0.804114E+09 | 2683.58 | 27.63 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.140333E+11 | 13517.00 | 02-JAN-20:10 | 0.127587E+11 | 10113.80 | 02-JAN-20:10 |
February | 0.126708E+11 | 13517.00 | 01-FEB-20:10 | 0.115208E+11 | 10113.80 | 01-FEB-20:10 |
March | 0.140766E+11 | 13517.00 | 01-MAR-20:10 | 0.127855E+11 | 10113.80 | 01-MAR-20:10 |
April | 0.135575E+11 | 13517.00 | 03-APR-19:10 | 0.123314E+11 | 10113.80 | 03-APR-19:10 |
May | 0.140576E+11 | 13517.00 | 01-MAY-19:10 | 0.127741E+11 | 10113.80 | 01-MAY-19:10 |
June | 0.136197E+11 | 13517.00 | 01-JUN-19:10 | 0.123716E+11 | 10113.80 | 01-JUN-19:10 |
July | 0.139955E+11 | 13517.00 | 03-JUL-19:10 | 0.127338E+11 | 10113.80 | 03-JUL-19:10 |
August | 0.140820E+11 | 13517.00 | 01-AUG-19:10 | 0.127894E+11 | 10113.80 | 01-AUG-19:10 |
September | 0.135629E+11 | 13517.00 | 01-SEP-19:10 | 0.123352E+11 | 10113.80 | 01-SEP-19:10 |
October | 0.140279E+11 | 13517.00 | 02-OCT-19:10 | 0.127549E+11 | 10113.80 | 02-OCT-19:10 |
November | 0.136089E+11 | 13517.00 | 01-NOV-19:10 | 0.123659E+11 | 10113.80 | 01-NOV-19:10 |
December | 0.139955E+11 | 13517.00 | 01-DEC-20:10 | 0.127338E+11 | 10113.80 | 01-DEC-20:10 |
Annual Sum or Average | 0.165288E+12 | 0.150255E+12 | ||||
Minimum of Months | 0.126708E+11 | 13517.00 | 0.115208E+11 | 10113.80 | ||
Maximum of Months | 0.140820E+11 | 13517.00 | 0.127894E+11 | 10113.80 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.713551E+09 | 687.30 | 02-JAN-20:10 | 0.864900E+09 | 685.60 | 02-JAN-20:10 |
February | 0.644271E+09 | 687.30 | 01-FEB-20:10 | 0.780982E+09 | 685.60 | 01-FEB-20:10 |
March | 0.715750E+09 | 687.30 | 01-MAR-20:10 | 0.866718E+09 | 685.60 | 01-MAR-20:10 |
April | 0.689358E+09 | 687.30 | 03-APR-19:10 | 0.835931E+09 | 685.60 | 03-APR-19:10 |
May | 0.714788E+09 | 687.30 | 01-MAY-19:10 | 0.865939E+09 | 685.60 | 01-MAY-19:10 |
June | 0.692519E+09 | 687.30 | 01-JUN-19:10 | 0.838659E+09 | 685.60 | 01-JUN-19:10 |
July | 0.711626E+09 | 687.30 | 03-JUL-19:10 | 0.863211E+09 | 685.60 | 03-JUL-19:10 |
August | 0.716025E+09 | 687.30 | 01-AUG-19:10 | 0.866978E+09 | 685.60 | 01-AUG-19:10 |
September | 0.689633E+09 | 687.30 | 01-SEP-19:10 | 0.836191E+09 | 685.60 | 01-SEP-19:10 |
October | 0.713276E+09 | 687.30 | 02-OCT-19:10 | 0.864640E+09 | 685.60 | 02-OCT-19:10 |
November | 0.691970E+09 | 687.30 | 01-NOV-19:10 | 0.838269E+09 | 685.60 | 01-NOV-19:10 |
December | 0.711626E+09 | 687.30 | 01-DEC-20:10 | 0.863211E+09 | 685.60 | 01-DEC-20:10 |
Annual Sum or Average | 0.840439E+10 | 0.101856E+11 | ||||
Minimum of Months | 0.644271E+09 | 687.30 | 0.780982E+09 | 685.60 | ||
Maximum of Months | 0.716025E+09 | 687.30 | 0.866978E+09 | 685.60 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.826294E+09 | 795.89 | 02-JAN-20:10 | 0.100156E+10 | 793.93 | 02-JAN-20:10 |
February | 0.746069E+09 | 795.89 | 01-FEB-20:10 | 0.904380E+09 | 793.93 | 01-FEB-20:10 |
March | 0.828841E+09 | 795.89 | 01-MAR-20:10 | 0.100366E+10 | 793.93 | 01-MAR-20:10 |
April | 0.798279E+09 | 795.89 | 03-APR-19:10 | 0.968011E+09 | 793.93 | 03-APR-19:10 |
May | 0.827727E+09 | 795.89 | 01-MAY-19:10 | 0.100276E+10 | 793.93 | 01-MAY-19:10 |
June | 0.801940E+09 | 795.89 | 01-JUN-19:10 | 0.971170E+09 | 793.93 | 01-JUN-19:10 |
July | 0.824066E+09 | 795.89 | 03-JUL-19:10 | 0.999601E+09 | 793.93 | 03-JUL-19:10 |
August | 0.829160E+09 | 795.89 | 01-AUG-19:10 | 0.100396E+10 | 793.93 | 01-AUG-19:10 |
September | 0.798597E+09 | 795.89 | 01-SEP-19:10 | 0.968312E+09 | 793.93 | 01-SEP-19:10 |
October | 0.825976E+09 | 795.89 | 02-OCT-19:10 | 0.100126E+10 | 793.93 | 02-OCT-19:10 |
November | 0.801303E+09 | 795.89 | 01-NOV-19:10 | 0.970719E+09 | 793.93 | 01-NOV-19:10 |
December | 0.824066E+09 | 795.89 | 01-DEC-20:10 | 0.999601E+09 | 793.93 | 01-DEC-20:10 |
Annual Sum or Average | 0.973232E+10 | 0.117950E+11 | ||||
Minimum of Months | 0.746069E+09 | 795.89 | 0.904380E+09 | 793.93 | ||
Maximum of Months | 0.829160E+09 | 795.89 | 0.100396E+10 | 793.93 |
Report: ZoneElectricSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.154452E+10 | 1487.69 | 02-JAN-20:10 | 0.105898E+10 | 839.45 | 02-JAN-20:10 |
February | 0.139456E+10 | 1487.69 | 01-FEB-20:10 | 0.956227E+09 | 839.45 | 01-FEB-20:10 |
March | 0.154928E+10 | 1487.69 | 01-MAR-20:10 | 0.106120E+10 | 839.45 | 01-MAR-20:10 |
April | 0.149215E+10 | 1487.69 | 03-APR-19:10 | 0.102351E+10 | 839.45 | 03-APR-19:10 |
May | 0.154719E+10 | 1487.69 | 01-MAY-19:10 | 0.106025E+10 | 839.45 | 01-MAY-19:10 |
June | 0.149899E+10 | 1487.69 | 01-JUN-19:10 | 0.102685E+10 | 839.45 | 01-JUN-19:10 |
July | 0.154035E+10 | 1487.69 | 03-JUL-19:10 | 0.105691E+10 | 839.45 | 03-JUL-19:10 |
August | 0.154987E+10 | 1487.69 | 01-AUG-19:10 | 0.106152E+10 | 839.45 | 01-AUG-19:10 |
September | 0.149274E+10 | 1487.69 | 01-SEP-19:10 | 0.102382E+10 | 839.45 | 01-SEP-19:10 |
October | 0.154392E+10 | 1487.69 | 02-OCT-19:10 | 0.105866E+10 | 839.45 | 02-OCT-19:10 |
November | 0.149780E+10 | 1487.69 | 01-NOV-19:10 | 0.102637E+10 | 839.45 | 01-NOV-19:10 |
December | 0.154035E+10 | 1487.69 | 01-DEC-20:10 | 0.105691E+10 | 839.45 | 01-DEC-20:10 |
Annual Sum or Average | 0.181917E+11 | 0.124712E+11 | ||||
Minimum of Months | 0.139456E+10 | 1487.69 | 0.956227E+09 | 839.45 | ||
Maximum of Months | 0.154987E+10 | 1487.69 | 0.106152E+10 | 839.45 |
Report: ZoneElectricSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.283535E+09 | 273.10 | 02-JAN-20:10 | 0.305485E+09 | 242.16 | 02-JAN-20:10 |
February | 0.256006E+09 | 273.10 | 01-FEB-20:10 | 0.275845E+09 | 242.16 | 01-FEB-20:10 |
March | 0.284409E+09 | 273.10 | 01-MAR-20:10 | 0.306128E+09 | 242.16 | 01-MAR-20:10 |
April | 0.273921E+09 | 273.10 | 03-APR-19:10 | 0.295253E+09 | 242.16 | 03-APR-19:10 |
May | 0.284026E+09 | 273.10 | 01-MAY-19:10 | 0.305852E+09 | 242.16 | 01-MAY-19:10 |
June | 0.275178E+09 | 273.10 | 01-JUN-19:10 | 0.296217E+09 | 242.16 | 01-JUN-19:10 |
July | 0.282770E+09 | 273.10 | 03-JUL-19:10 | 0.304889E+09 | 242.16 | 03-JUL-19:10 |
August | 0.284518E+09 | 273.10 | 01-AUG-19:10 | 0.306219E+09 | 242.16 | 01-AUG-19:10 |
September | 0.274031E+09 | 273.10 | 01-SEP-19:10 | 0.295345E+09 | 242.16 | 01-SEP-19:10 |
October | 0.283425E+09 | 273.10 | 02-OCT-19:10 | 0.305393E+09 | 242.16 | 02-OCT-19:10 |
November | 0.274959E+09 | 273.10 | 01-NOV-19:10 | 0.296079E+09 | 242.16 | 01-NOV-19:10 |
December | 0.282770E+09 | 273.10 | 01-DEC-20:10 | 0.304889E+09 | 242.16 | 01-DEC-20:10 |
Annual Sum or Average | 0.333955E+10 | 0.359760E+10 | ||||
Minimum of Months | 0.256006E+09 | 273.10 | 0.275845E+09 | 242.16 | ||
Maximum of Months | 0.284518E+09 | 273.10 | 0.306219E+09 | 242.16 |
Report: ZoneElectricSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.350256E+09 | 337.37 | 02-JAN-20:10 | 0.576866E+10 | 4572.80 | 02-JAN-20:10 |
February | 0.316249E+09 | 337.37 | 01-FEB-20:10 | 0.520895E+10 | 4572.80 | 01-FEB-20:10 |
March | 0.351336E+09 | 337.37 | 01-MAR-20:10 | 0.578079E+10 | 4572.80 | 01-MAR-20:10 |
April | 0.338381E+09 | 337.37 | 03-APR-19:10 | 0.557545E+10 | 4572.80 | 03-APR-19:10 |
May | 0.350863E+09 | 337.37 | 01-MAY-19:10 | 0.577559E+10 | 4572.80 | 01-MAY-19:10 |
June | 0.339933E+09 | 337.37 | 01-JUN-19:10 | 0.559364E+10 | 4572.80 | 01-JUN-19:10 |
July | 0.349311E+09 | 337.37 | 03-JUL-19:10 | 0.575740E+10 | 4572.80 | 03-JUL-19:10 |
August | 0.351471E+09 | 337.37 | 01-AUG-19:10 | 0.578252E+10 | 4572.80 | 01-AUG-19:10 |
September | 0.338516E+09 | 337.37 | 01-SEP-19:10 | 0.557718E+10 | 4572.80 | 01-SEP-19:10 |
October | 0.350121E+09 | 337.37 | 02-OCT-19:10 | 0.576693E+10 | 4572.80 | 02-OCT-19:10 |
November | 0.339663E+09 | 337.37 | 01-NOV-19:10 | 0.559104E+10 | 4572.80 | 01-NOV-19:10 |
December | 0.349311E+09 | 337.37 | 01-DEC-20:10 | 0.575740E+10 | 4572.80 | 01-DEC-20:10 |
Annual Sum or Average | 0.412541E+10 | 0.679355E+11 | ||||
Minimum of Months | 0.316249E+09 | 337.37 | 0.520895E+10 | 4572.80 | ||
Maximum of Months | 0.351471E+09 | 337.37 | 0.578252E+10 | 4572.80 |
Report: ZoneElectricSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.226040E+10 | 2177.23 | 02-JAN-20:10 | 0.121771E+10 | 965.27 | 02-JAN-20:10 |
February | 0.204093E+10 | 2177.23 | 01-FEB-20:10 | 0.109956E+10 | 965.27 | 01-FEB-20:10 |
March | 0.226736E+10 | 2177.23 | 01-MAR-20:10 | 0.122027E+10 | 965.27 | 01-MAR-20:10 |
April | 0.218376E+10 | 2177.23 | 03-APR-19:10 | 0.117692E+10 | 965.27 | 03-APR-19:10 |
May | 0.226431E+10 | 2177.23 | 01-MAY-19:10 | 0.121917E+10 | 965.27 | 01-MAY-19:10 |
June | 0.219377E+10 | 2177.23 | 01-JUN-19:10 | 0.118076E+10 | 965.27 | 01-JUN-19:10 |
July | 0.225430E+10 | 2177.23 | 03-JUL-19:10 | 0.121533E+10 | 965.27 | 03-JUL-19:10 |
August | 0.226823E+10 | 2177.23 | 01-AUG-19:10 | 0.122063E+10 | 965.27 | 01-AUG-19:10 |
September | 0.218463E+10 | 2177.23 | 01-SEP-19:10 | 0.117729E+10 | 965.27 | 01-SEP-19:10 |
October | 0.225952E+10 | 2177.23 | 02-OCT-19:10 | 0.121734E+10 | 965.27 | 02-OCT-19:10 |
November | 0.219203E+10 | 2177.23 | 01-NOV-19:10 | 0.118021E+10 | 965.27 | 01-NOV-19:10 |
December | 0.225430E+10 | 2177.23 | 01-DEC-20:10 | 0.121533E+10 | 965.27 | 01-DEC-20:10 |
Annual Sum or Average | 0.266236E+11 | 0.143405E+11 | ||||
Minimum of Months | 0.204093E+10 | 2177.23 | 0.109956E+10 | 965.27 | ||
Maximum of Months | 0.226823E+10 | 2177.23 | 0.122063E+10 | 965.27 |
Report: ZoneElectricSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.123020E+11 | 11849.32 | 02-JAN-20:10 | 0.126520E+11 | 10029.21 | 02-JAN-20:10 |
February | 0.111075E+11 | 11849.32 | 01-FEB-20:10 | 0.114244E+11 | 10029.21 | 01-FEB-20:10 |
March | 0.123399E+11 | 11849.32 | 01-MAR-20:10 | 0.126786E+11 | 10029.21 | 01-MAR-20:10 |
April | 0.118849E+11 | 11849.32 | 03-APR-19:10 | 0.122282E+11 | 10029.21 | 03-APR-19:10 |
May | 0.123233E+11 | 11849.32 | 01-MAY-19:10 | 0.126672E+11 | 10029.21 | 01-MAY-19:10 |
June | 0.119394E+11 | 11849.32 | 01-JUN-19:10 | 0.122682E+11 | 10029.21 | 01-JUN-19:10 |
July | 0.122688E+11 | 11849.32 | 03-JUL-19:10 | 0.126273E+11 | 10029.21 | 03-JUL-19:10 |
August | 0.123446E+11 | 11849.32 | 01-AUG-19:10 | 0.126824E+11 | 10029.21 | 01-AUG-19:10 |
September | 0.118896E+11 | 11849.32 | 01-SEP-19:10 | 0.122320E+11 | 10029.21 | 01-SEP-19:10 |
October | 0.122972E+11 | 11849.32 | 02-OCT-19:10 | 0.126482E+11 | 10029.21 | 02-OCT-19:10 |
November | 0.119299E+11 | 11849.32 | 01-NOV-19:10 | 0.122624E+11 | 10029.21 | 01-NOV-19:10 |
December | 0.122688E+11 | 11849.32 | 01-DEC-20:10 | 0.126273E+11 | 10029.21 | 01-DEC-20:10 |
Annual Sum or Average | 0.144896E+12 | 0.148998E+12 | ||||
Minimum of Months | 0.111075E+11 | 11849.32 | 0.114244E+11 | 10029.21 | ||
Maximum of Months | 0.123446E+11 | 11849.32 | 0.126824E+11 | 10029.21 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.434056E+09 | 392.73 | 01-JAN-19:10 | 0.261068E+09 | 237.06 | 01-JAN-08:09 |
February | 0.391995E+09 | 392.73 | 01-FEB-20:10 | 0.235798E+09 | 237.06 | 01-FEB-07:10 |
March | 0.430607E+09 | 392.73 | 01-MAR-20:10 | 0.260708E+09 | 237.06 | 01-MAR-07:10 |
April | 0.420554E+09 | 392.73 | 01-APR-18:10 | 0.252705E+09 | 237.06 | 01-APR-07:10 |
May | 0.432331E+09 | 392.73 | 01-MAY-19:10 | 0.260888E+09 | 237.06 | 01-MAY-06:10 |
June | 0.417218E+09 | 392.73 | 01-JUN-19:10 | 0.252344E+09 | 237.06 | 01-JUN-06:10 |
July | 0.435725E+09 | 392.73 | 01-JUL-18:10 | 0.261248E+09 | 237.06 | 01-JUL-07:10 |
August | 0.430607E+09 | 392.73 | 01-AUG-19:10 | 0.260708E+09 | 237.06 | 01-AUG-06:10 |
September | 0.420667E+09 | 392.73 | 01-SEP-19:10 | 0.252705E+09 | 237.06 | 01-SEP-06:10 |
October | 0.434000E+09 | 392.73 | 01-OCT-18:10 | 0.261068E+09 | 237.06 | 01-OCT-07:10 |
November | 0.418886E+09 | 392.73 | 01-NOV-19:10 | 0.252524E+09 | 237.06 | 01-NOV-06:10 |
December | 0.435781E+09 | 392.73 | 01-DEC-20:10 | 0.261248E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.510243E+10 | 0.307301E+10 | ||||
Minimum of Months | 0.391995E+09 | 392.73 | 0.235798E+09 | 237.06 | ||
Maximum of Months | 0.435781E+09 | 392.73 | 0.261248E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.434005E+09 | 392.68 | 01-JAN-19:10 | 0.261038E+09 | 237.03 | 01-JAN-08:09 |
February | 0.391949E+09 | 392.68 | 01-FEB-20:10 | 0.235770E+09 | 237.03 | 01-FEB-07:10 |
March | 0.430556E+09 | 392.68 | 01-MAR-20:10 | 0.260677E+09 | 237.03 | 01-MAR-07:10 |
April | 0.420505E+09 | 392.68 | 01-APR-18:10 | 0.252675E+09 | 237.03 | 01-APR-07:10 |
May | 0.432281E+09 | 392.68 | 01-MAY-19:10 | 0.260857E+09 | 237.03 | 01-MAY-06:10 |
June | 0.417169E+09 | 392.68 | 01-JUN-19:10 | 0.252315E+09 | 237.03 | 01-JUN-06:10 |
July | 0.435674E+09 | 392.68 | 01-JUL-18:10 | 0.261218E+09 | 237.03 | 01-JUL-07:10 |
August | 0.430556E+09 | 392.68 | 01-AUG-19:10 | 0.260677E+09 | 237.03 | 01-AUG-06:10 |
September | 0.420618E+09 | 392.68 | 01-SEP-19:10 | 0.252675E+09 | 237.03 | 01-SEP-06:10 |
October | 0.433949E+09 | 392.68 | 01-OCT-18:10 | 0.261038E+09 | 237.03 | 01-OCT-07:10 |
November | 0.418837E+09 | 392.68 | 01-NOV-19:10 | 0.252495E+09 | 237.03 | 01-NOV-06:10 |
December | 0.435730E+09 | 392.68 | 01-DEC-20:10 | 0.261218E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.510183E+10 | 0.307265E+10 | ||||
Minimum of Months | 0.391949E+09 | 392.68 | 0.235770E+09 | 237.03 | ||
Maximum of Months | 0.435730E+09 | 392.68 | 0.261218E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.272788E+09 | 246.81 | 01-JAN-19:10 | 0.255708E+09 | 232.19 | 01-JAN-08:09 |
February | 0.246354E+09 | 246.81 | 01-FEB-20:10 | 0.230956E+09 | 232.19 | 01-FEB-07:10 |
March | 0.270620E+09 | 246.81 | 01-MAR-20:10 | 0.255355E+09 | 232.19 | 01-MAR-07:10 |
April | 0.264302E+09 | 246.81 | 01-APR-18:10 | 0.247516E+09 | 232.19 | 01-APR-07:10 |
May | 0.271704E+09 | 246.81 | 01-MAY-19:10 | 0.255532E+09 | 232.19 | 01-MAY-06:10 |
June | 0.262205E+09 | 246.81 | 01-JUN-19:10 | 0.247163E+09 | 232.19 | 01-JUN-06:10 |
July | 0.273836E+09 | 246.81 | 01-JUL-18:10 | 0.255885E+09 | 232.19 | 01-JUL-07:10 |
August | 0.270620E+09 | 246.81 | 01-AUG-19:10 | 0.255355E+09 | 232.19 | 01-AUG-06:10 |
September | 0.264373E+09 | 246.81 | 01-SEP-19:10 | 0.247516E+09 | 232.19 | 01-SEP-06:10 |
October | 0.272752E+09 | 246.81 | 01-OCT-18:10 | 0.255708E+09 | 232.19 | 01-OCT-07:10 |
November | 0.263254E+09 | 246.81 | 01-NOV-19:10 | 0.247340E+09 | 232.19 | 01-NOV-06:10 |
December | 0.273872E+09 | 246.81 | 01-DEC-20:10 | 0.255885E+09 | 232.19 | 01-DEC-07:10 |
Annual Sum or Average | 0.320668E+10 | 0.300992E+10 | ||||
Minimum of Months | 0.246354E+09 | 246.81 | 0.230956E+09 | 232.19 | ||
Maximum of Months | 0.273872E+09 | 246.81 | 0.255885E+09 | 232.19 |
Report: ZoneElectricSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.272862E+09 | 246.88 | 01-JAN-19:10 | 0.255778E+09 | 232.26 | 01-JAN-08:09 |
February | 0.246421E+09 | 246.88 | 01-FEB-20:10 | 0.231020E+09 | 232.26 | 01-FEB-07:10 |
March | 0.270694E+09 | 246.88 | 01-MAR-20:10 | 0.255425E+09 | 232.26 | 01-MAR-07:10 |
April | 0.264375E+09 | 246.88 | 01-APR-18:10 | 0.247584E+09 | 232.26 | 01-APR-07:10 |
May | 0.271778E+09 | 246.88 | 01-MAY-19:10 | 0.255602E+09 | 232.26 | 01-MAY-06:10 |
June | 0.262277E+09 | 246.88 | 01-JUN-19:10 | 0.247231E+09 | 232.26 | 01-JUN-06:10 |
July | 0.273911E+09 | 246.88 | 01-JUL-18:10 | 0.255955E+09 | 232.26 | 01-JUL-07:10 |
August | 0.270694E+09 | 246.88 | 01-AUG-19:10 | 0.255425E+09 | 232.26 | 01-AUG-06:10 |
September | 0.264446E+09 | 246.88 | 01-SEP-19:10 | 0.247584E+09 | 232.26 | 01-SEP-06:10 |
October | 0.272827E+09 | 246.88 | 01-OCT-18:10 | 0.255778E+09 | 232.26 | 01-OCT-07:10 |
November | 0.263326E+09 | 246.88 | 01-NOV-19:10 | 0.247408E+09 | 232.26 | 01-NOV-06:10 |
December | 0.273947E+09 | 246.88 | 01-DEC-20:10 | 0.255955E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.320756E+10 | 0.301074E+10 | ||||
Minimum of Months | 0.246421E+09 | 246.88 | 0.231020E+09 | 232.26 | ||
Maximum of Months | 0.273947E+09 | 246.88 | 0.255955E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.434056E+09 | 392.73 | 01-JAN-19:10 | 0.261068E+09 | 237.06 | 01-JAN-08:09 |
February | 0.391995E+09 | 392.73 | 01-FEB-20:10 | 0.235798E+09 | 237.06 | 01-FEB-07:10 |
March | 0.430607E+09 | 392.73 | 01-MAR-20:10 | 0.260708E+09 | 237.06 | 01-MAR-07:10 |
April | 0.420554E+09 | 392.73 | 01-APR-18:10 | 0.252705E+09 | 237.06 | 01-APR-07:10 |
May | 0.432331E+09 | 392.73 | 01-MAY-19:10 | 0.260888E+09 | 237.06 | 01-MAY-06:10 |
June | 0.417218E+09 | 392.73 | 01-JUN-19:10 | 0.252344E+09 | 237.06 | 01-JUN-06:10 |
July | 0.435725E+09 | 392.73 | 01-JUL-18:10 | 0.261248E+09 | 237.06 | 01-JUL-07:10 |
August | 0.430607E+09 | 392.73 | 01-AUG-19:10 | 0.260708E+09 | 237.06 | 01-AUG-06:10 |
September | 0.420667E+09 | 392.73 | 01-SEP-19:10 | 0.252705E+09 | 237.06 | 01-SEP-06:10 |
October | 0.434000E+09 | 392.73 | 01-OCT-18:10 | 0.261068E+09 | 237.06 | 01-OCT-07:10 |
November | 0.418886E+09 | 392.73 | 01-NOV-19:10 | 0.252524E+09 | 237.06 | 01-NOV-06:10 |
December | 0.435781E+09 | 392.73 | 01-DEC-20:10 | 0.261248E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.510243E+10 | 0.307301E+10 | ||||
Minimum of Months | 0.391995E+09 | 392.73 | 0.235798E+09 | 237.06 | ||
Maximum of Months | 0.435781E+09 | 392.73 | 0.261248E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.434005E+09 | 392.68 | 01-JAN-19:10 | 0.261038E+09 | 237.03 | 01-JAN-08:09 |
February | 0.391949E+09 | 392.68 | 01-FEB-20:10 | 0.235770E+09 | 237.03 | 01-FEB-07:10 |
March | 0.430556E+09 | 392.68 | 01-MAR-20:10 | 0.260677E+09 | 237.03 | 01-MAR-07:10 |
April | 0.420505E+09 | 392.68 | 01-APR-18:10 | 0.252675E+09 | 237.03 | 01-APR-07:10 |
May | 0.432281E+09 | 392.68 | 01-MAY-19:10 | 0.260857E+09 | 237.03 | 01-MAY-06:10 |
June | 0.417169E+09 | 392.68 | 01-JUN-19:10 | 0.252315E+09 | 237.03 | 01-JUN-06:10 |
July | 0.435674E+09 | 392.68 | 01-JUL-18:10 | 0.261218E+09 | 237.03 | 01-JUL-07:10 |
August | 0.430556E+09 | 392.68 | 01-AUG-19:10 | 0.260677E+09 | 237.03 | 01-AUG-06:10 |
September | 0.420618E+09 | 392.68 | 01-SEP-19:10 | 0.252675E+09 | 237.03 | 01-SEP-06:10 |
October | 0.433949E+09 | 392.68 | 01-OCT-18:10 | 0.261038E+09 | 237.03 | 01-OCT-07:10 |
November | 0.418837E+09 | 392.68 | 01-NOV-19:10 | 0.252495E+09 | 237.03 | 01-NOV-06:10 |
December | 0.435730E+09 | 392.68 | 01-DEC-20:10 | 0.261218E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.510183E+10 | 0.307265E+10 | ||||
Minimum of Months | 0.391949E+09 | 392.68 | 0.235770E+09 | 237.03 | ||
Maximum of Months | 0.435730E+09 | 392.68 | 0.261218E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.133160E+10 | 1282.60 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.120231E+10 | 1282.60 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.133570E+10 | 1282.60 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.128645E+10 | 1282.60 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.133391E+10 | 1282.60 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.129235E+10 | 1282.60 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.132801E+10 | 1282.60 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.133622E+10 | 1282.60 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.128696E+10 | 1282.60 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.133109E+10 | 1282.60 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.129132E+10 | 1282.60 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.132801E+10 | 1282.60 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.156839E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.120231E+10 | 1282.60 | 0.00 | 0.00 | |
Maximum of Months | 0.133622E+10 | 1282.60 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.434056E+09 | 392.73 | 01-JAN-19:10 | 0.261068E+09 | 237.06 | 01-JAN-08:09 |
February | 0.391995E+09 | 392.73 | 01-FEB-20:10 | 0.235798E+09 | 237.06 | 01-FEB-07:10 |
March | 0.430607E+09 | 392.73 | 01-MAR-20:10 | 0.260708E+09 | 237.06 | 01-MAR-07:10 |
April | 0.420554E+09 | 392.73 | 01-APR-18:10 | 0.252705E+09 | 237.06 | 01-APR-07:10 |
May | 0.432331E+09 | 392.73 | 01-MAY-19:10 | 0.260888E+09 | 237.06 | 01-MAY-06:10 |
June | 0.417218E+09 | 392.73 | 01-JUN-19:10 | 0.252344E+09 | 237.06 | 01-JUN-06:10 |
July | 0.435725E+09 | 392.73 | 01-JUL-18:10 | 0.261248E+09 | 237.06 | 01-JUL-07:10 |
August | 0.430607E+09 | 392.73 | 01-AUG-19:10 | 0.260708E+09 | 237.06 | 01-AUG-06:10 |
September | 0.420667E+09 | 392.73 | 01-SEP-19:10 | 0.252705E+09 | 237.06 | 01-SEP-06:10 |
October | 0.434000E+09 | 392.73 | 01-OCT-18:10 | 0.261068E+09 | 237.06 | 01-OCT-07:10 |
November | 0.418886E+09 | 392.73 | 01-NOV-19:10 | 0.252524E+09 | 237.06 | 01-NOV-06:10 |
December | 0.435781E+09 | 392.73 | 01-DEC-20:10 | 0.261248E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.510243E+10 | 0.307301E+10 | ||||
Minimum of Months | 0.391995E+09 | 392.73 | 0.235798E+09 | 237.06 | ||
Maximum of Months | 0.435781E+09 | 392.73 | 0.261248E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.434005E+09 | 392.68 | 01-JAN-19:10 | 0.261038E+09 | 237.03 | 01-JAN-08:09 |
February | 0.391949E+09 | 392.68 | 01-FEB-20:10 | 0.235770E+09 | 237.03 | 01-FEB-07:10 |
March | 0.430556E+09 | 392.68 | 01-MAR-20:10 | 0.260677E+09 | 237.03 | 01-MAR-07:10 |
April | 0.420505E+09 | 392.68 | 01-APR-18:10 | 0.252675E+09 | 237.03 | 01-APR-07:10 |
May | 0.432281E+09 | 392.68 | 01-MAY-19:10 | 0.260857E+09 | 237.03 | 01-MAY-06:10 |
June | 0.417169E+09 | 392.68 | 01-JUN-19:10 | 0.252315E+09 | 237.03 | 01-JUN-06:10 |
July | 0.435674E+09 | 392.68 | 01-JUL-18:10 | 0.261218E+09 | 237.03 | 01-JUL-07:10 |
August | 0.430556E+09 | 392.68 | 01-AUG-19:10 | 0.260677E+09 | 237.03 | 01-AUG-06:10 |
September | 0.420618E+09 | 392.68 | 01-SEP-19:10 | 0.252675E+09 | 237.03 | 01-SEP-06:10 |
October | 0.433949E+09 | 392.68 | 01-OCT-18:10 | 0.261038E+09 | 237.03 | 01-OCT-07:10 |
November | 0.418837E+09 | 392.68 | 01-NOV-19:10 | 0.252495E+09 | 237.03 | 01-NOV-06:10 |
December | 0.435730E+09 | 392.68 | 01-DEC-20:10 | 0.261218E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.510183E+10 | 0.307265E+10 | ||||
Minimum of Months | 0.391949E+09 | 392.68 | 0.235770E+09 | 237.03 | ||
Maximum of Months | 0.435730E+09 | 392.68 | 0.261218E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.272862E+09 | 246.88 | 01-JAN-19:10 | 0.255778E+09 | 232.26 | 01-JAN-08:09 |
February | 0.246421E+09 | 246.88 | 01-FEB-20:10 | 0.231020E+09 | 232.26 | 01-FEB-07:10 |
March | 0.270694E+09 | 246.88 | 01-MAR-20:10 | 0.255425E+09 | 232.26 | 01-MAR-07:10 |
April | 0.264375E+09 | 246.88 | 01-APR-18:10 | 0.247584E+09 | 232.26 | 01-APR-07:10 |
May | 0.271778E+09 | 246.88 | 01-MAY-19:10 | 0.255602E+09 | 232.26 | 01-MAY-06:10 |
June | 0.262277E+09 | 246.88 | 01-JUN-19:10 | 0.247231E+09 | 232.26 | 01-JUN-06:10 |
July | 0.273911E+09 | 246.88 | 01-JUL-18:10 | 0.255955E+09 | 232.26 | 01-JUL-07:10 |
August | 0.270694E+09 | 246.88 | 01-AUG-19:10 | 0.255425E+09 | 232.26 | 01-AUG-06:10 |
September | 0.264446E+09 | 246.88 | 01-SEP-19:10 | 0.247584E+09 | 232.26 | 01-SEP-06:10 |
October | 0.272827E+09 | 246.88 | 01-OCT-18:10 | 0.255778E+09 | 232.26 | 01-OCT-07:10 |
November | 0.263326E+09 | 246.88 | 01-NOV-19:10 | 0.247408E+09 | 232.26 | 01-NOV-06:10 |
December | 0.273947E+09 | 246.88 | 01-DEC-20:10 | 0.255955E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.320756E+10 | 0.301074E+10 | ||||
Minimum of Months | 0.246421E+09 | 246.88 | 0.231020E+09 | 232.26 | ||
Maximum of Months | 0.273947E+09 | 246.88 | 0.255955E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.396945E+10 | 3823.39 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.358405E+10 | 3823.39 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.398168E+10 | 3823.39 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.383486E+10 | 3823.39 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.397633E+10 | 3823.39 | 01-MAY-19:10 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.385245E+10 | 3823.39 | 01-JUN-19:10 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.395874E+10 | 3823.39 | 03-JUL-19:10 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.398321E+10 | 3823.39 | 01-AUG-19:10 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.383639E+10 | 3823.39 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.396792E+10 | 3823.39 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.384939E+10 | 3823.39 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.395874E+10 | 3823.39 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.467532E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.358405E+10 | 3823.39 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.398321E+10 | 3823.39 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.396945E+10 | 3823.39 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.358405E+10 | 3823.39 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.398168E+10 | 3823.39 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.383486E+10 | 3823.39 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.397633E+10 | 3823.39 | 01-MAY-19:10 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.385245E+10 | 3823.39 | 01-JUN-19:10 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.395874E+10 | 3823.39 | 03-JUL-19:10 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.398321E+10 | 3823.39 | 01-AUG-19:10 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.383639E+10 | 3823.39 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.396792E+10 | 3823.39 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.384939E+10 | 3823.39 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.395874E+10 | 3823.39 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.467532E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.358405E+10 | 3823.39 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.398321E+10 | 3823.39 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.105977E+10 | 1020.78 | 02-JAN-20:10 | 0.373720E+11 | 16686.59 | 01-JAN-07:10 |
February | 0.956878E+09 | 1020.78 | 01-FEB-20:10 | 0.337554E+11 | 16686.59 | 01-FEB-07:10 |
March | 0.106304E+10 | 1020.78 | 01-MAR-20:10 | 0.373720E+11 | 16686.59 | 01-MAR-07:10 |
April | 0.102384E+10 | 1020.78 | 03-APR-19:10 | 0.361665E+11 | 16686.59 | 01-APR-06:10 |
May | 0.106161E+10 | 1020.78 | 01-MAY-19:10 | 0.373720E+11 | 16686.59 | 01-MAY-06:10 |
June | 0.102854E+10 | 1020.78 | 01-JUN-19:10 | 0.361665E+11 | 16686.59 | 01-JUN-06:10 |
July | 0.105691E+10 | 1020.78 | 03-JUL-19:10 | 0.373720E+11 | 16686.59 | 01-JUL-06:10 |
August | 0.106345E+10 | 1020.78 | 01-AUG-19:10 | 0.373720E+11 | 16686.59 | 01-AUG-06:10 |
September | 0.102425E+10 | 1020.78 | 01-SEP-19:10 | 0.361665E+11 | 16686.59 | 01-SEP-06:10 |
October | 0.105936E+10 | 1020.78 | 02-OCT-19:10 | 0.373720E+11 | 16686.59 | 01-OCT-06:10 |
November | 0.102772E+10 | 1020.78 | 01-NOV-19:10 | 0.361665E+11 | 16686.59 | 01-NOV-06:10 |
December | 0.105691E+10 | 1020.78 | 01-DEC-20:10 | 0.373720E+11 | 16686.59 | 01-DEC-07:10 |
Annual Sum or Average | 0.124823E+11 | 0.440025E+12 | ||||
Minimum of Months | 0.956878E+09 | 1020.78 | 0.337554E+11 | 16686.59 | ||
Maximum of Months | 0.106345E+10 | 1020.78 | 0.373720E+11 | 16686.59 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.140929E+10 | 1357.44 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.127246E+10 | 1357.44 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.141364E+10 | 1357.44 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.136151E+10 | 1357.44 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.141173E+10 | 1357.44 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.136775E+10 | 1357.44 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.140549E+10 | 1357.44 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.141418E+10 | 1357.44 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.136205E+10 | 1357.44 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.140875E+10 | 1357.44 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.136667E+10 | 1357.44 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.140549E+10 | 1357.44 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.165990E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.127246E+10 | 1357.44 | 0.00 | 0.00 | |
Maximum of Months | 0.141418E+10 | 1357.44 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.195762E+11 | 0.140333E+11 | 0.127587E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.176991E+11 | 0.126708E+11 | 0.115208E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.196682E+11 | 0.140766E+11 | 0.127855E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.189781E+11 | 0.135575E+11 | 0.123314E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.196176E+11 | 0.140576E+11 | 0.127741E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.190195E+11 | 0.136197E+11 | 0.123716E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.195762E+11 | 0.139955E+11 | 0.127338E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.196590E+11 | 0.140820E+11 | 0.127894E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.189689E+11 | 0.135629E+11 | 0.123352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.195854E+11 | 0.140279E+11 | 0.127549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.189367E+11 | 0.136089E+11 | 0.123659E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.195762E+11 | 0.139955E+11 | 0.127338E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.230861E+12 | 0.165288E+12 | 0.150255E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.176991E+11 | 0.126708E+11 | 0.115208E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.196682E+11 | 0.140820E+11 | 0.127894E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.199054E+10 | 0.713551E+09 | 0.864900E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.676322E+09 |
February | 0.179968E+10 | 0.644271E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 925812.25 | 0.510842E+09 |
March | 0.199990E+10 | 0.715750E+09 | 0.866718E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5776564.93 | 0.446511E+09 |
April | 0.192973E+10 | 0.689358E+09 | 0.835931E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 80533318.49 | 0.174918E+09 |
May | 0.199475E+10 | 0.714788E+09 | 0.865939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187954E+09 | 54598748.50 |
June | 0.193394E+10 | 0.692519E+09 | 0.838659E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.320220E+09 | 8398096.28 |
July | 0.199054E+10 | 0.711626E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.312766E+09 | 2329491.67 |
August | 0.199896E+10 | 0.716025E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258924E+09 | 12205082.74 |
September | 0.192879E+10 | 0.689633E+09 | 0.836191E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151987E+09 | 56128756.09 |
October | 0.199148E+10 | 0.713276E+09 | 0.864640E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 43940146.17 | 0.198406E+09 |
November | 0.192552E+10 | 0.691970E+09 | 0.838269E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 856605.89 | 0.506288E+09 |
December | 0.199054E+10 | 0.711626E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.751760E+09 |
Annual Sum or Average | 0.234744E+11 | 0.840439E+10 | 0.101856E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136388E+10 | 0.339871E+10 |
Minimum of Months | 0.179968E+10 | 0.644271E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2329491.67 |
Maximum of Months | 0.199990E+10 | 0.716025E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.320220E+09 | 0.751760E+09 |
Report: SpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.230505E+10 | 0.826294E+09 | 0.100156E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.259622E+09 |
February | 0.208403E+10 | 0.746069E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 757922.16 | 0.196163E+09 |
March | 0.231589E+10 | 0.828841E+09 | 0.100366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2662628.53 | 0.172610E+09 |
April | 0.223463E+10 | 0.798279E+09 | 0.968011E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 31130899.29 | 68424718.20 |
May | 0.230993E+10 | 0.827727E+09 | 0.100276E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 70813171.13 | 21838428.85 |
June | 0.223950E+10 | 0.801940E+09 | 0.971170E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121229E+09 | 3539559.89 |
July | 0.230505E+10 | 0.824066E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118460E+09 | 1105184.86 |
August | 0.231480E+10 | 0.829160E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 98948530.83 | 5020139.45 |
September | 0.223354E+10 | 0.798597E+09 | 0.968312E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 61505644.19 | 22880568.97 |
October | 0.230614E+10 | 0.825976E+09 | 0.100126E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20778271.90 | 77061205.15 |
November | 0.222975E+10 | 0.801303E+09 | 0.970719E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 764372.58 | 0.192625E+09 |
December | 0.230505E+10 | 0.824066E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.289058E+09 |
Annual Sum or Average | 0.271834E+11 | 0.973232E+10 | 0.117950E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.527050E+09 | 0.130995E+10 |
Minimum of Months | 0.208403E+10 | 0.746069E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1105184.86 |
Maximum of Months | 0.231589E+10 | 0.829160E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121229E+09 | 0.289058E+09 |
Report: SpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.487480E+09 | 0.154452E+10 | 0.105898E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.613000E+09 |
February | 0.440737E+09 | 0.139456E+10 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1791553.99 | 0.462790E+09 |
March | 0.489771E+09 | 0.154928E+10 | 0.106120E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6308762.60 | 0.406132E+09 |
April | 0.472586E+09 | 0.149215E+10 | 0.102351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 75099786.17 | 0.159652E+09 |
May | 0.488511E+09 | 0.154719E+10 | 0.106025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.170638E+09 | 49990819.41 |
June | 0.473617E+09 | 0.149899E+10 | 0.102685E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.290809E+09 | 7721008.84 |
July | 0.487480E+09 | 0.154035E+10 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.284542E+09 | 2248780.98 |
August | 0.489542E+09 | 0.154987E+10 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.239162E+09 | 11177131.70 |
September | 0.472357E+09 | 0.149274E+10 | 0.102382E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148779E+09 | 51407920.61 |
October | 0.487709E+09 | 0.154392E+10 | 0.105866E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 49987164.44 | 0.178872E+09 |
November | 0.471555E+09 | 0.149780E+10 | 0.102637E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1806815.80 | 0.453686E+09 |
December | 0.487480E+09 | 0.154035E+10 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.682851E+09 |
Annual Sum or Average | 0.574883E+10 | 0.181917E+11 | 0.124712E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126893E+10 | 0.307953E+10 |
Minimum of Months | 0.440737E+09 | 0.139456E+10 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2248780.98 |
Maximum of Months | 0.489771E+09 | 0.154987E+10 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.290809E+09 | 0.682851E+09 |
Report: SpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.374985E+09 | 0.283535E+09 | 0.305485E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.353668E+09 |
February | 0.339028E+09 | 0.256006E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1033682.38 | 0.267005E+09 |
March | 0.376747E+09 | 0.284409E+09 | 0.306128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3639527.29 | 0.234313E+09 |
April | 0.363528E+09 | 0.273921E+09 | 0.295253E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 43625523.35 | 92044161.82 |
May | 0.375778E+09 | 0.284026E+09 | 0.305852E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 99485102.33 | 28735893.13 |
June | 0.364321E+09 | 0.275178E+09 | 0.296217E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169541E+09 | 4423125.79 |
July | 0.374985E+09 | 0.282770E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165893E+09 | 1239335.84 |
August | 0.376571E+09 | 0.284518E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139474E+09 | 6420844.09 |
September | 0.363352E+09 | 0.274031E+09 | 0.295345E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 86651025.79 | 29493092.65 |
October | 0.375161E+09 | 0.283425E+09 | 0.305393E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 29011944.07 | 0.103096E+09 |
November | 0.362735E+09 | 0.274959E+09 | 0.296079E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1042468.51 | 0.261747E+09 |
December | 0.374985E+09 | 0.282770E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.393969E+09 |
Annual Sum or Average | 0.442217E+10 | 0.333955E+10 | 0.359760E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.739397E+09 | 0.177615E+10 |
Minimum of Months | 0.339028E+09 | 0.256006E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1239335.84 |
Maximum of Months | 0.376747E+09 | 0.284518E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169541E+09 | 0.393969E+09 |
Report: SpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.154405E+10 | 0.350256E+09 | 0.576866E+10 | 0.501157E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.864294E+09 |
February | 0.139600E+10 | 0.316249E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 2443059.54 | 0.656389E+09 |
March | 0.155131E+10 | 0.351336E+09 | 0.578079E+10 | 0.502211E+11 | 0.00 | 0.00 | 0.00 | 8376298.50 | 0.581222E+09 |
April | 0.149688E+10 | 0.338381E+09 | 0.557545E+10 | 0.484372E+11 | 0.00 | 0.00 | 0.00 | 92699347.45 | 0.230920E+09 |
May | 0.154732E+10 | 0.350863E+09 | 0.577559E+10 | 0.501759E+11 | 0.00 | 0.00 | 0.00 | 0.217527E+09 | 72639823.35 |
June | 0.150015E+10 | 0.339933E+09 | 0.559364E+10 | 0.485952E+11 | 0.00 | 0.00 | 0.00 | 0.384955E+09 | 11001004.02 |
July | 0.154405E+10 | 0.349311E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 0.376041E+09 | 3846046.83 |
August | 0.155059E+10 | 0.351471E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 0.311947E+09 | 17836158.36 |
September | 0.149615E+10 | 0.338516E+09 | 0.557718E+10 | 0.484522E+11 | 0.00 | 0.00 | 0.00 | 0.190265E+09 | 77009283.53 |
October | 0.154478E+10 | 0.350121E+09 | 0.576693E+10 | 0.501006E+11 | 0.00 | 0.00 | 0.00 | 64125733.20 | 0.264287E+09 |
November | 0.149361E+10 | 0.339663E+09 | 0.559104E+10 | 0.485726E+11 | 0.00 | 0.00 | 0.00 | 2439865.78 | 0.645630E+09 |
December | 0.154405E+10 | 0.349311E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.959736E+09 |
Annual Sum or Average | 0.182090E+11 | 0.412541E+10 | 0.679355E+11 | 0.590196E+12 | 0.00 | 0.00 | 0.00 | 0.165082E+10 | 0.438481E+10 |
Minimum of Months | 0.139600E+10 | 0.316249E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 3846046.83 |
Maximum of Months | 0.155131E+10 | 0.351471E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 0.384955E+09 | 0.959736E+09 |
Report: SpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.261570E+11 | 0.226040E+10 | 0.121771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149468E+10 |
February | 0.236489E+11 | 0.204093E+10 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2768250.28 | 0.113001E+10 |
March | 0.262800E+11 | 0.226736E+10 | 0.122027E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13772942.01 | 0.990308E+09 |
April | 0.253579E+11 | 0.218376E+10 | 0.117692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175916E+09 | 0.395818E+09 |
May | 0.262123E+11 | 0.226431E+10 | 0.121917E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.402778E+09 | 0.128973E+09 |
June | 0.254132E+11 | 0.219377E+10 | 0.118076E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.685292E+09 | 21914976.38 |
July | 0.261570E+11 | 0.225430E+10 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.667679E+09 | 8480608.66 |
August | 0.262677E+11 | 0.226823E+10 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.553714E+09 | 32737818.67 |
September | 0.253456E+11 | 0.218463E+10 | 0.117729E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.335806E+09 | 0.138265E+09 |
October | 0.261693E+11 | 0.225952E+10 | 0.121734E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101069E+09 | 0.452157E+09 |
November | 0.253025E+11 | 0.219203E+10 | 0.118021E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2447086.60 | 0.112024E+10 |
December | 0.261570E+11 | 0.225430E+10 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166155E+10 |
Annual Sum or Average | 0.308468E+12 | 0.266236E+11 | 0.143405E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.294124E+10 | 0.757513E+10 |
Minimum of Months | 0.236489E+11 | 0.204093E+10 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8480608.66 |
Maximum of Months | 0.262800E+11 | 0.226823E+10 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.685292E+09 | 0.166155E+10 |
Report: SpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.776503E+11 | 0.123020E+11 | 0.126520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.426479E+10 |
February | 0.702046E+11 | 0.111075E+11 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 12395668.02 | 0.322851E+10 |
March | 0.780153E+11 | 0.123399E+11 | 0.126786E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 43450353.63 | 0.284955E+10 |
April | 0.752779E+11 | 0.118849E+11 | 0.122282E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.503252E+09 | 0.115278E+10 |
May | 0.778146E+11 | 0.123233E+11 | 0.126672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113847E+10 | 0.387000E+09 |
June | 0.754422E+11 | 0.119394E+11 | 0.122682E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.194515E+10 | 70232721.01 |
July | 0.776503E+11 | 0.122688E+11 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189190E+10 | 27461293.41 |
August | 0.779788E+11 | 0.123446E+11 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158124E+10 | 0.100682E+09 |
September | 0.752414E+11 | 0.118896E+11 | 0.122320E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.991811E+09 | 0.409557E+09 |
October | 0.776868E+11 | 0.122972E+11 | 0.126482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.333870E+09 | 0.130160E+10 |
November | 0.751137E+11 | 0.119299E+11 | 0.122624E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 12469033.76 | 0.317698E+10 |
December | 0.776503E+11 | 0.122688E+11 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.474335E+10 |
Annual Sum or Average | 0.915726E+12 | 0.144896E+12 | 0.148998E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.845402E+10 | 0.217125E+11 |
Minimum of Months | 0.702046E+11 | 0.111075E+11 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27461293.41 |
Maximum of Months | 0.780153E+11 | 0.123446E+11 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.194515E+10 | 0.474335E+10 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.434056E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.398306E+09 |
February | 0.273974E+09 | 0.391995E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 264122.38 | 0.303786E+09 |
March | 0.303685E+09 | 0.430607E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1539162.34 | 0.269842E+09 |
April | 0.293479E+09 | 0.420554E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 36521020.31 | 0.108077E+09 |
May | 0.303504E+09 | 0.432331E+09 | 0.260888E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 92398096.72 | 34642764.83 |
June | 0.293842E+09 | 0.417218E+09 | 0.252344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169060E+09 | 5642296.53 |
July | 0.303141E+09 | 0.435725E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163369E+09 | 1780158.62 |
August | 0.303685E+09 | 0.430607E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135127E+09 | 8778245.71 |
September | 0.293479E+09 | 0.420667E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 77982880.00 | 35382264.97 |
October | 0.303322E+09 | 0.434000E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 22415339.23 | 0.123259E+09 |
November | 0.293661E+09 | 0.418886E+09 | 0.252524E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 343130.97 | 0.300999E+09 |
December | 0.303141E+09 | 0.435781E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.441400E+09 |
Annual Sum or Average | 0.357224E+10 | 0.510243E+10 | 0.307301E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.699020E+09 | 0.203190E+10 |
Minimum of Months | 0.273974E+09 | 0.391995E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1780158.62 |
Maximum of Months | 0.303685E+09 | 0.435781E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169060E+09 | 0.441400E+09 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.434005E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.387777E+09 |
February | 0.273974E+09 | 0.391949E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 291984.44 | 0.295999E+09 |
March | 0.303685E+09 | 0.430556E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1753161.86 | 0.264387E+09 |
April | 0.293479E+09 | 0.420505E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 37078055.55 | 0.106920E+09 |
May | 0.303504E+09 | 0.432281E+09 | 0.260857E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 92524344.28 | 34505418.70 |
June | 0.293842E+09 | 0.417169E+09 | 0.252315E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169006E+09 | 5665906.39 |
July | 0.303141E+09 | 0.435674E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163335E+09 | 1790942.10 |
August | 0.303685E+09 | 0.430556E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135262E+09 | 8708972.27 |
September | 0.293479E+09 | 0.420618E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 78487249.06 | 35110092.65 |
October | 0.303322E+09 | 0.433949E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 23054741.83 | 0.120316E+09 |
November | 0.293661E+09 | 0.418837E+09 | 0.252495E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 356227.59 | 0.293460E+09 |
December | 0.303141E+09 | 0.435730E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.430324E+09 |
Annual Sum or Average | 0.357224E+10 | 0.510183E+10 | 0.307265E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.701149E+09 | 0.198496E+10 |
Minimum of Months | 0.273974E+09 | 0.391949E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1790942.10 |
Maximum of Months | 0.303685E+09 | 0.435730E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169006E+09 | 0.430324E+09 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.272788E+09 | 0.255708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123130E+09 |
February | 0.00 | 0.246354E+09 | 0.230956E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96017416.72 |
March | 0.00 | 0.270620E+09 | 0.255355E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 117008.82 | 87381939.55 |
April | 0.00 | 0.264302E+09 | 0.247516E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7206972.41 | 39803731.48 |
May | 0.00 | 0.271704E+09 | 0.255532E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19265271.24 | 16111073.19 |
June | 0.00 | 0.262205E+09 | 0.247163E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 37713626.27 | 4361473.16 |
July | 0.00 | 0.273836E+09 | 0.255885E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 35085530.13 | 2699133.52 |
August | 0.00 | 0.270620E+09 | 0.255355E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 28639751.76 | 6238688.27 |
September | 0.00 | 0.264373E+09 | 0.247516E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16409772.58 | 17090862.22 |
October | 0.00 | 0.272752E+09 | 0.255708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4181379.08 | 46020083.01 |
November | 0.00 | 0.263254E+09 | 0.247340E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7785.19 | 95561926.51 |
December | 0.00 | 0.273872E+09 | 0.255885E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133371E+09 |
Annual Sum or Average | 0.00 | 0.320668E+10 | 0.300992E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148627E+09 | 0.667787E+09 |
Minimum of Months | 0.00 | 0.246354E+09 | 0.230956E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2699133.52 |
Maximum of Months | 0.00 | 0.273872E+09 | 0.255885E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 37713626.27 | 0.133371E+09 |
Report: SpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.272862E+09 | 0.255778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109706E+09 |
February | 0.273974E+09 | 0.246421E+09 | 0.231020E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 165703.90 | 83426817.27 |
March | 0.303685E+09 | 0.270694E+09 | 0.255425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 704167.97 | 74096215.14 |
April | 0.293479E+09 | 0.264375E+09 | 0.247584E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10932081.37 | 29781092.54 |
May | 0.303504E+09 | 0.271778E+09 | 0.255602E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 26337935.70 | 9570329.06 |
June | 0.293842E+09 | 0.262277E+09 | 0.247231E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 47463381.16 | 1554785.35 |
July | 0.303141E+09 | 0.273911E+09 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 45878455.56 | 492597.97 |
August | 0.303685E+09 | 0.270694E+09 | 0.255425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 38176357.49 | 2377175.20 |
September | 0.293479E+09 | 0.264446E+09 | 0.247584E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 22539063.03 | 9771217.93 |
October | 0.303322E+09 | 0.272827E+09 | 0.255778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7049592.93 | 33532185.03 |
November | 0.293661E+09 | 0.263326E+09 | 0.247408E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 205109.05 | 82176968.41 |
December | 0.303141E+09 | 0.273947E+09 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121677E+09 |
Annual Sum or Average | 0.357224E+10 | 0.320756E+10 | 0.301074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.199452E+09 | 0.558162E+09 |
Minimum of Months | 0.273974E+09 | 0.246421E+09 | 0.231020E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 492597.97 |
Maximum of Months | 0.303685E+09 | 0.273947E+09 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 47463381.16 | 0.121677E+09 |
Report: SpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.434056E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.398972E+09 |
February | 0.273974E+09 | 0.391995E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 263998.67 | 0.306095E+09 |
March | 0.303685E+09 | 0.430607E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1565727.83 | 0.272972E+09 |
April | 0.293479E+09 | 0.420554E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 36421964.03 | 0.110700E+09 |
May | 0.303504E+09 | 0.432331E+09 | 0.260888E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 92114621.99 | 35829764.95 |
June | 0.293842E+09 | 0.417218E+09 | 0.252344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168698E+09 | 5888174.32 |
July | 0.303141E+09 | 0.435725E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162965E+09 | 1871266.99 |
August | 0.303685E+09 | 0.430607E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134833E+09 | 9106491.86 |
September | 0.293479E+09 | 0.420667E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 77866806.10 | 36098441.63 |
October | 0.303322E+09 | 0.434000E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 22447549.40 | 0.124130E+09 |
November | 0.293661E+09 | 0.418886E+09 | 0.252524E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 343592.58 | 0.302399E+09 |
December | 0.303141E+09 | 0.435781E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.441806E+09 |
Annual Sum or Average | 0.357224E+10 | 0.510243E+10 | 0.307301E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.697521E+09 | 0.204587E+10 |
Minimum of Months | 0.273974E+09 | 0.391995E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1871266.99 |
Maximum of Months | 0.303685E+09 | 0.435781E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168698E+09 | 0.441806E+09 |
Report: SpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.434005E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.387591E+09 |
February | 0.273974E+09 | 0.391949E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 322407.84 | 0.297869E+09 |
March | 0.303685E+09 | 0.430556E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1746614.10 | 0.267827E+09 |
April | 0.293479E+09 | 0.420505E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 36495465.66 | 0.109830E+09 |
May | 0.303504E+09 | 0.432281E+09 | 0.260857E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 92124112.27 | 35817459.80 |
June | 0.293842E+09 | 0.417169E+09 | 0.252315E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168667E+09 | 5893344.85 |
July | 0.303141E+09 | 0.435674E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162946E+09 | 1872891.76 |
August | 0.303685E+09 | 0.430556E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134866E+09 | 9056105.89 |
September | 0.293479E+09 | 0.420618E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 77990913.16 | 36001996.50 |
October | 0.303322E+09 | 0.433949E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 22769611.30 | 0.121933E+09 |
November | 0.293661E+09 | 0.418837E+09 | 0.252495E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 472506.74 | 0.293069E+09 |
December | 0.303141E+09 | 0.435730E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.430184E+09 |
Annual Sum or Average | 0.357224E+10 | 0.510183E+10 | 0.307265E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.698402E+09 | 0.199694E+10 |
Minimum of Months | 0.273974E+09 | 0.391949E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1872891.76 |
Maximum of Months | 0.303685E+09 | 0.435730E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168667E+09 | 0.430184E+09 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.385223E+10 | 0.133160E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.473177E+09 |
February | 0.348285E+10 | 0.120231E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1272788.75 | 0.357505E+09 |
March | 0.387034E+10 | 0.133570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4639540.79 | 0.314159E+09 |
April | 0.373454E+10 | 0.128645E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55119898.31 | 0.125628E+09 |
May | 0.386038E+10 | 0.133391E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120940E+09 | 43016798.41 |
June | 0.374269E+10 | 0.129235E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.200896E+09 | 9047488.29 |
July | 0.385223E+10 | 0.132801E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.195427E+09 | 3520098.54 |
August | 0.386853E+10 | 0.133622E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163112E+09 | 11899861.10 |
September | 0.373273E+10 | 0.128696E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101073E+09 | 47233435.26 |
October | 0.385404E+10 | 0.133109E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34215877.89 | 0.142529E+09 |
November | 0.372639E+10 | 0.129132E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1224747.91 | 0.351036E+09 |
December | 0.385223E+10 | 0.132801E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.526927E+09 |
Annual Sum or Average | 0.454292E+11 | 0.156839E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.877920E+09 | 0.240568E+10 |
Minimum of Months | 0.348285E+10 | 0.120231E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3520098.54 |
Maximum of Months | 0.387034E+10 | 0.133622E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.200896E+09 | 0.526927E+09 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.434056E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.397635E+09 |
February | 0.273974E+09 | 0.391995E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 247048.61 | 0.304004E+09 |
March | 0.303685E+09 | 0.430607E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1467769.04 | 0.270745E+09 |
April | 0.293479E+09 | 0.420554E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 35825459.10 | 0.109168E+09 |
May | 0.303504E+09 | 0.432331E+09 | 0.260888E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 91149858.38 | 35306646.05 |
June | 0.293842E+09 | 0.417218E+09 | 0.252344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.167504E+09 | 5876552.45 |
July | 0.303141E+09 | 0.435725E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161609E+09 | 1897393.85 |
August | 0.303685E+09 | 0.430607E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133569E+09 | 9140995.94 |
September | 0.293479E+09 | 0.420667E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 76814317.21 | 35944744.67 |
October | 0.303322E+09 | 0.434000E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21981197.94 | 0.124398E+09 |
November | 0.293661E+09 | 0.418886E+09 | 0.252524E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 325592.12 | 0.301506E+09 |
December | 0.303141E+09 | 0.435781E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.440733E+09 |
Annual Sum or Average | 0.357224E+10 | 0.510243E+10 | 0.307301E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.690493E+09 | 0.203635E+10 |
Minimum of Months | 0.273974E+09 | 0.391995E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1897393.85 |
Maximum of Months | 0.303685E+09 | 0.435781E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.167504E+09 | 0.440733E+09 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.434005E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.386761E+09 |
February | 0.273974E+09 | 0.391949E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 265678.78 | 0.296053E+09 |
March | 0.303685E+09 | 0.430556E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1606520.27 | 0.265288E+09 |
April | 0.293479E+09 | 0.420505E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 36043172.75 | 0.108055E+09 |
May | 0.303504E+09 | 0.432281E+09 | 0.260857E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 91183706.15 | 35180507.70 |
June | 0.293842E+09 | 0.417169E+09 | 0.252315E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.167447E+09 | 5902593.40 |
July | 0.303141E+09 | 0.435674E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161568E+09 | 1907034.96 |
August | 0.303685E+09 | 0.430556E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133646E+09 | 9091976.20 |
September | 0.293479E+09 | 0.420618E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 77171890.98 | 35685032.66 |
October | 0.303322E+09 | 0.433949E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 22293962.60 | 0.121683E+09 |
November | 0.293661E+09 | 0.418837E+09 | 0.252495E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 327818.92 | 0.293845E+09 |
December | 0.303141E+09 | 0.435730E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.429391E+09 |
Annual Sum or Average | 0.357224E+10 | 0.510183E+10 | 0.307265E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.691553E+09 | 0.198884E+10 |
Minimum of Months | 0.273974E+09 | 0.391949E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1907034.96 |
Maximum of Months | 0.303685E+09 | 0.435730E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.167447E+09 | 0.429391E+09 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.272862E+09 | 0.255778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.208938E+09 |
February | 0.273974E+09 | 0.246421E+09 | 0.231020E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 125250.54 | 0.159395E+09 |
March | 0.303685E+09 | 0.270694E+09 | 0.255425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 751653.49 | 0.140950E+09 |
April | 0.293479E+09 | 0.264375E+09 | 0.247584E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18345391.12 | 56310260.10 |
May | 0.303504E+09 | 0.271778E+09 | 0.255602E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 46732682.74 | 18063545.41 |
June | 0.293842E+09 | 0.262277E+09 | 0.247231E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 85811239.96 | 2975924.53 |
July | 0.303141E+09 | 0.273911E+09 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 82806313.09 | 965436.76 |
August | 0.303685E+09 | 0.270694E+09 | 0.255425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 68397580.23 | 4675498.63 |
September | 0.293479E+09 | 0.264446E+09 | 0.247584E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 39280288.98 | 18482974.75 |
October | 0.303322E+09 | 0.272827E+09 | 0.255778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11205646.60 | 64421048.18 |
November | 0.293661E+09 | 0.263326E+09 | 0.247408E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 162160.10 | 0.157074E+09 |
December | 0.303141E+09 | 0.273947E+09 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.231635E+09 |
Annual Sum or Average | 0.357224E+10 | 0.320756E+10 | 0.301074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.353618E+09 | 0.106389E+10 |
Minimum of Months | 0.273974E+09 | 0.246421E+09 | 0.231020E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 965436.76 |
Maximum of Months | 0.303685E+09 | 0.273947E+09 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 85811239.96 | 0.231635E+09 |
Report: SpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.396945E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.979619E+09 |
February | 0.415303E+11 | 0.358405E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2460964.79 | 0.746141E+09 |
March | 0.461508E+11 | 0.398168E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 8831754.25 | 0.665992E+09 |
April | 0.445315E+11 | 0.383486E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104900E+09 | 0.281915E+09 |
May | 0.460320E+11 | 0.397633E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235646E+09 | 0.103665E+09 |
June | 0.446286E+11 | 0.385245E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.403696E+09 | 22743231.37 |
July | 0.459349E+11 | 0.395874E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.389401E+09 | 11515494.72 |
August | 0.461292E+11 | 0.398321E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.327109E+09 | 31778545.91 |
September | 0.445099E+11 | 0.383639E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.208809E+09 | 0.108431E+09 |
October | 0.459565E+11 | 0.396792E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 70230596.24 | 0.314508E+09 |
November | 0.444343E+11 | 0.384939E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2520020.90 | 0.735435E+09 |
December | 0.459349E+11 | 0.395874E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108547E+10 |
Annual Sum or Average | 0.541708E+12 | 0.467532E+11 | 0.175857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175360E+10 | 0.508721E+10 |
Minimum of Months | 0.415303E+11 | 0.358405E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11515494.72 |
Maximum of Months | 0.461508E+11 | 0.398321E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.403696E+09 | 0.108547E+10 |
Report: SpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.396945E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.982141E+09 |
February | 0.415303E+11 | 0.358405E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2429573.76 | 0.748694E+09 |
March | 0.461508E+11 | 0.398168E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 8632181.71 | 0.669139E+09 |
April | 0.445315E+11 | 0.383486E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103148E+09 | 0.284654E+09 |
May | 0.460320E+11 | 0.397633E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.231818E+09 | 0.105495E+09 |
June | 0.446286E+11 | 0.385245E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.399285E+09 | 23338657.35 |
July | 0.459349E+11 | 0.395874E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.384583E+09 | 11963708.66 |
August | 0.461292E+11 | 0.398321E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.323049E+09 | 32672038.09 |
September | 0.445099E+11 | 0.383639E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.206142E+09 | 0.110276E+09 |
October | 0.459565E+11 | 0.396792E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 69278547.17 | 0.317292E+09 |
November | 0.444343E+11 | 0.384939E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2461910.35 | 0.738159E+09 |
December | 0.459349E+11 | 0.395874E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108788E+10 |
Annual Sum or Average | 0.541708E+12 | 0.467532E+11 | 0.175857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.173083E+10 | 0.511171E+10 |
Minimum of Months | 0.415303E+11 | 0.358405E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11963708.66 |
Maximum of Months | 0.461508E+11 | 0.398321E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.399285E+09 | 0.108788E+10 |
Report: SpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.408770E+10 | 0.105977E+10 | 0.338870E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.969728E+09 |
February | 0.369574E+10 | 0.956878E+09 | 0.306077E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.751502E+09 |
March | 0.410691E+10 | 0.106304E+10 | 0.338870E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 332953.60 | 0.681621E+09 |
April | 0.396281E+10 | 0.102384E+10 | 0.327939E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 46250382.58 | 0.291930E+09 |
May | 0.409635E+10 | 0.106161E+10 | 0.338870E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.138741E+09 | 0.104289E+09 |
June | 0.397146E+10 | 0.102854E+10 | 0.327939E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 0.289561E+09 | 21839677.70 |
July | 0.408770E+10 | 0.105691E+10 | 0.338870E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.272415E+09 | 11168887.87 |
August | 0.410499E+10 | 0.106345E+10 | 0.338870E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.219859E+09 | 35536673.19 |
September | 0.396089E+10 | 0.102425E+10 | 0.327939E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 0.113722E+09 | 0.107902E+09 |
October | 0.408962E+10 | 0.105936E+10 | 0.338870E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 27819112.60 | 0.337693E+09 |
November | 0.395417E+10 | 0.102772E+10 | 0.327939E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 9317.60 | 0.748027E+09 |
December | 0.408770E+10 | 0.105691E+10 | 0.338870E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106561E+10 |
Annual Sum or Average | 0.482060E+11 | 0.124823E+11 | 0.398993E+12 | 0.359593E+12 | 0.00 | 0.00 | 0.00 | 0.110871E+10 | 0.512685E+10 |
Minimum of Months | 0.369574E+10 | 0.956878E+09 | 0.306077E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 11168887.87 |
Maximum of Months | 0.410691E+10 | 0.106345E+10 | 0.338870E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.289561E+09 | 0.106561E+10 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.407704E+10 | 0.140929E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.841216E+09 |
February | 0.368610E+10 | 0.127246E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2193266.67 | 0.635784E+09 |
March | 0.409620E+10 | 0.141364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7991797.78 | 0.558857E+09 |
April | 0.395248E+10 | 0.136151E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98699854.65 | 0.220903E+09 |
May | 0.408566E+10 | 0.141173E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.225319E+09 | 69895115.85 |
June | 0.396110E+10 | 0.136775E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.375385E+09 | 11099680.51 |
July | 0.407704E+10 | 0.140549E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.366913E+09 | 3411936.69 |
August | 0.409429E+10 | 0.141418E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.307922E+09 | 16142153.34 |
September | 0.395056E+10 | 0.136205E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190565E+09 | 71958690.85 |
October | 0.407896E+10 | 0.140875E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63144148.21 | 0.247807E+09 |
November | 0.394385E+10 | 0.136667E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2186535.41 | 0.623876E+09 |
December | 0.407704E+10 | 0.140549E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.936343E+09 |
Annual Sum or Average | 0.480803E+11 | 0.165990E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.164032E+10 | 0.423730E+10 |
Minimum of Months | 0.368610E+10 | 0.127246E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3411936.69 |
Maximum of Months | 0.409620E+10 | 0.141418E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.375385E+09 | 0.936343E+09 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 11501.89 | 02-JAN-00:10 | 13517.00 | 02-JAN-20:10 | 10113.80 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 11501.89 | 01-FEB-00:10 | 13517.00 | 01-FEB-20:10 | 10113.80 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 11501.89 | 01-MAR-00:10 | 13517.00 | 01-MAR-20:10 | 10113.80 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 11501.89 | 01-APR-00:10 | 13517.00 | 03-APR-19:10 | 10113.80 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 11501.89 | 01-MAY-00:10 | 13517.00 | 01-MAY-19:10 | 10113.80 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 11501.89 | 01-JUN-00:10 | 13517.00 | 01-JUN-19:10 | 10113.80 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 11501.89 | 01-JUL-00:10 | 13517.00 | 03-JUL-19:10 | 10113.80 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 11501.89 | 01-AUG-00:10 | 13517.00 | 01-AUG-19:10 | 10113.80 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 11501.89 | 01-SEP-00:10 | 13517.00 | 01-SEP-19:10 | 10113.80 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 11501.89 | 01-OCT-23:10 | 13517.00 | 02-OCT-19:10 | 10113.80 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 11501.89 | 01-NOV-00:10 | 13517.00 | 01-NOV-19:10 | 10113.80 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 11501.89 | 01-DEC-00:10 | 13517.00 | 01-DEC-20:10 | 10113.80 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 11501.89 | 13517.00 | 10113.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 11501.89 | 13517.00 | 10113.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1169.53 | 02-JAN-00:10 | 687.30 | 02-JAN-20:10 | 685.60 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 515.20 | 27-JAN-07:00 |
February | 1169.53 | 01-FEB-00:10 | 687.30 | 01-FEB-20:10 | 685.60 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.96 | 22-FEB-16:00 | 541.35 | 03-FEB-07:00 |
March | 1169.53 | 01-MAR-00:10 | 687.30 | 01-MAR-20:10 | 685.60 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 69.95 | 21-MAR-16:00 | 509.39 | 02-MAR-06:00 |
April | 1169.53 | 01-APR-00:10 | 687.30 | 03-APR-19:10 | 685.60 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 188.64 | 21-APR-15:00 | 346.79 | 12-APR-06:00 |
May | 1169.53 | 01-MAY-00:10 | 687.30 | 01-MAY-19:10 | 685.60 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 246.00 | 19-MAY-16:00 | 222.39 | 02-MAY-06:00 |
June | 1169.53 | 01-JUN-00:10 | 687.30 | 01-JUN-19:10 | 685.60 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 309.47 | 02-JUN-17:00 | 113.48 | 13-JUN-05:00 |
July | 1169.53 | 01-JUL-00:10 | 687.30 | 03-JUL-19:10 | 685.60 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 300.53 | 03-JUL-17:00 | 60.06 | 05-JUL-06:00 |
August | 1169.53 | 01-AUG-00:10 | 687.30 | 01-AUG-19:10 | 685.60 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 274.86 | 07-AUG-16:00 | 81.45 | 31-AUG-06:00 |
September | 1169.53 | 01-SEP-00:10 | 687.30 | 01-SEP-19:10 | 685.60 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 209.82 | 19-SEP-16:30 | 245.77 | 30-SEP-06:00 |
October | 1169.53 | 01-OCT-23:10 | 687.30 | 02-OCT-19:10 | 685.60 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 180.18 | 01-OCT-15:00 | 279.79 | 25-OCT-06:00 |
November | 1169.53 | 01-NOV-00:10 | 687.30 | 01-NOV-19:10 | 685.60 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.45 | 08-NOV-15:40 | 436.69 | 28-NOV-05:00 |
December | 1169.53 | 01-DEC-00:10 | 687.30 | 01-DEC-20:10 | 685.60 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 512.89 | 27-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1169.53 | 687.30 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.06 | |||||
Maximum of Months | 1169.53 | 687.30 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 309.47 | 541.35 |
Report: PeakSpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1354.32 | 02-JAN-00:10 | 795.89 | 02-JAN-20:10 | 793.93 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 198.87 | 27-JAN-07:00 |
February | 1354.32 | 01-FEB-00:10 | 795.89 | 01-FEB-20:10 | 793.93 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.41 | 20-FEB-15:00 | 208.98 | 03-FEB-07:00 |
March | 1354.32 | 01-MAR-00:10 | 795.89 | 01-MAR-20:10 | 793.93 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.00 | 21-MAR-16:00 | 196.60 | 02-MAR-05:40 |
April | 1354.32 | 01-APR-00:10 | 795.89 | 03-APR-19:10 | 793.93 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 76.79 | 21-APR-14:00 | 133.83 | 12-APR-06:00 |
May | 1354.32 | 01-MAY-00:10 | 795.89 | 01-MAY-19:10 | 793.93 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 95.81 | 21-MAY-14:00 | 85.87 | 02-MAY-06:00 |
June | 1354.32 | 01-JUN-00:10 | 795.89 | 01-JUN-19:10 | 793.93 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 120.74 | 02-JUN-16:00 | 45.84 | 13-JUN-05:00 |
July | 1354.32 | 01-JUL-00:10 | 795.89 | 03-JUL-19:10 | 793.93 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 117.16 | 02-JUL-16:00 | 23.19 | 05-JUL-06:00 |
August | 1354.32 | 01-AUG-00:10 | 795.89 | 01-AUG-19:10 | 793.93 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 110.06 | 07-AUG-16:00 | 32.54 | 31-AUG-06:00 |
September | 1354.32 | 01-SEP-00:10 | 795.89 | 01-SEP-19:10 | 793.93 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 88.38 | 19-SEP-14:00 | 94.85 | 30-SEP-06:00 |
October | 1354.32 | 01-OCT-23:10 | 795.89 | 02-OCT-19:10 | 793.93 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 81.32 | 01-OCT-15:00 | 108.00 | 25-OCT-06:00 |
November | 1354.32 | 01-NOV-00:10 | 795.89 | 01-NOV-19:10 | 793.93 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.53 | 08-NOV-15:00 | 168.55 | 28-NOV-05:00 |
December | 1354.32 | 01-DEC-00:10 | 795.89 | 01-DEC-20:10 | 793.93 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 199.58 | 27-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1354.32 | 795.89 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.19 | |||||
Maximum of Months | 1354.32 | 795.89 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 120.74 | 208.98 |
Report: PeakSpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 286.42 | 02-JAN-00:10 | 1487.69 | 02-JAN-20:10 | 839.45 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 470.02 | 27-JAN-07:00 |
February | 286.42 | 01-FEB-00:10 | 1487.69 | 01-FEB-20:10 | 839.45 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.77 | 20-FEB-15:00 | 493.87 | 03-FEB-07:00 |
March | 286.42 | 01-MAR-00:10 | 1487.69 | 01-MAR-20:10 | 839.45 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 66.25 | 21-MAR-16:00 | 464.64 | 02-MAR-05:10 |
April | 286.42 | 01-APR-00:10 | 1487.69 | 03-APR-19:10 | 839.45 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 181.45 | 21-APR-14:00 | 316.29 | 12-APR-06:00 |
May | 286.42 | 01-MAY-00:10 | 1487.69 | 01-MAY-19:10 | 839.45 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 226.45 | 21-MAY-14:00 | 202.94 | 02-MAY-06:00 |
June | 286.42 | 01-JUN-00:10 | 1487.69 | 01-JUN-19:10 | 839.45 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 285.34 | 02-JUN-16:00 | 103.50 | 13-JUN-05:00 |
July | 286.42 | 01-JUL-00:10 | 1487.69 | 03-JUL-19:10 | 839.45 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 276.89 | 02-JUL-16:00 | 54.82 | 05-JUL-06:00 |
August | 286.42 | 01-AUG-00:10 | 1487.69 | 01-AUG-19:10 | 839.45 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 260.10 | 07-AUG-16:00 | 74.33 | 31-AUG-06:00 |
September | 286.42 | 01-SEP-00:10 | 1487.69 | 01-SEP-19:10 | 839.45 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 208.89 | 19-SEP-14:00 | 224.16 | 30-SEP-06:00 |
October | 286.42 | 01-OCT-23:10 | 1487.69 | 02-OCT-19:10 | 839.45 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 192.17 | 01-OCT-15:00 | 255.24 | 25-OCT-06:00 |
November | 286.42 | 01-NOV-00:10 | 1487.69 | 01-NOV-19:10 | 839.45 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.52 | 08-NOV-15:00 | 398.33 | 28-NOV-05:00 |
December | 286.42 | 01-DEC-00:10 | 1487.69 | 01-DEC-20:10 | 839.45 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 471.70 | 27-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 286.42 | 1487.69 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.82 | |||||
Maximum of Months | 286.42 | 1487.69 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 285.34 | 493.87 |
Report: PeakSpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 220.32 | 02-JAN-00:10 | 273.10 | 02-JAN-20:10 | 242.16 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 271.16 | 27-JAN-07:00 |
February | 220.32 | 01-FEB-00:10 | 273.10 | 01-FEB-20:10 | 242.16 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.36 | 20-FEB-15:40 | 284.93 | 03-FEB-07:00 |
March | 220.32 | 01-MAR-00:10 | 273.10 | 01-MAR-20:10 | 242.16 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.20 | 21-MAR-16:00 | 268.07 | 02-MAR-06:00 |
April | 220.32 | 01-APR-00:10 | 273.10 | 03-APR-19:10 | 242.16 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 104.71 | 21-APR-14:00 | 182.48 | 12-APR-06:00 |
May | 220.32 | 01-MAY-00:10 | 273.10 | 01-MAY-19:10 | 242.16 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 130.65 | 21-MAY-14:00 | 117.06 | 02-MAY-06:00 |
June | 220.32 | 01-JUN-00:10 | 273.10 | 01-JUN-19:10 | 242.16 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 164.64 | 02-JUN-16:00 | 59.70 | 13-JUN-05:00 |
July | 220.32 | 01-JUL-00:10 | 273.10 | 03-JUL-19:10 | 242.16 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 159.74 | 02-JUL-16:00 | 31.63 | 05-JUL-06:00 |
August | 220.32 | 01-AUG-00:10 | 273.10 | 01-AUG-19:10 | 242.16 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 150.07 | 07-AUG-16:00 | 42.87 | 31-AUG-06:00 |
September | 220.32 | 01-SEP-00:10 | 273.10 | 01-SEP-19:10 | 242.16 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 120.51 | 19-SEP-14:00 | 129.30 | 30-SEP-06:00 |
October | 220.32 | 01-OCT-23:10 | 273.10 | 02-OCT-19:10 | 242.16 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 110.86 | 01-OCT-15:00 | 147.26 | 25-OCT-06:00 |
November | 220.32 | 01-NOV-00:10 | 273.10 | 01-NOV-19:10 | 242.16 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.01 | 08-NOV-15:00 | 229.81 | 28-NOV-05:00 |
December | 220.32 | 01-DEC-00:10 | 273.10 | 01-DEC-20:10 | 242.16 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 272.17 | 27-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 220.32 | 273.10 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.63 | |||||
Maximum of Months | 220.32 | 273.10 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 164.64 | 284.93 |
Report: PeakSpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 907.20 | 02-JAN-00:10 | 337.37 | 02-JAN-20:10 | 4572.80 | 02-JAN-20:10 | 39726.58 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 642.16 | 27-JAN-07:10 |
February | 907.20 | 01-FEB-00:10 | 337.37 | 01-FEB-20:10 | 4572.80 | 01-FEB-20:10 | 39726.58 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 53.29 | 20-FEB-16:00 | 674.18 | 03-FEB-07:00 |
March | 907.20 | 01-MAR-00:10 | 337.37 | 01-MAR-20:10 | 4572.80 | 01-MAR-20:10 | 39726.58 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 90.35 | 21-MAR-16:00 | 634.43 | 02-MAR-05:30 |
April | 907.20 | 01-APR-00:10 | 337.37 | 03-APR-19:10 | 4572.80 | 03-APR-19:10 | 39726.58 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 247.72 | 21-APR-14:40 | 432.10 | 12-APR-06:00 |
May | 907.20 | 01-MAY-00:10 | 337.37 | 01-MAY-19:10 | 4572.80 | 01-MAY-19:10 | 39726.58 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 309.43 | 21-MAY-14:00 | 277.31 | 02-MAY-06:00 |
June | 907.20 | 01-JUN-00:10 | 337.37 | 01-JUN-19:10 | 4572.80 | 01-JUN-19:10 | 39726.58 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 389.61 | 02-JUN-16:00 | 141.14 | 13-JUN-05:00 |
July | 907.20 | 01-JUL-00:10 | 337.37 | 03-JUL-19:10 | 4572.80 | 03-JUL-19:10 | 39726.58 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 378.27 | 02-JUL-16:00 | 93.31 | 18-JUL-21:00 |
August | 907.20 | 01-AUG-00:10 | 337.37 | 01-AUG-19:10 | 4572.80 | 01-AUG-19:10 | 39726.58 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 355.46 | 07-AUG-16:00 | 145.98 | 16-AUG-21:00 |
September | 907.20 | 01-SEP-00:10 | 337.37 | 01-SEP-19:10 | 4572.80 | 01-SEP-19:10 | 39726.58 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 285.20 | 19-SEP-14:00 | 306.23 | 30-SEP-06:00 |
October | 907.20 | 01-OCT-23:10 | 337.37 | 02-OCT-19:10 | 4572.80 | 02-OCT-19:10 | 39726.58 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 262.12 | 01-OCT-15:00 | 351.00 | 25-OCT-06:10 |
November | 907.20 | 01-NOV-00:10 | 337.37 | 01-NOV-19:10 | 4572.80 | 01-NOV-19:10 | 39726.58 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 66.31 | 03-NOV-16:00 | 567.29 | 27-NOV-23:00 |
December | 907.20 | 01-DEC-00:10 | 337.37 | 01-DEC-20:10 | 4572.80 | 01-DEC-20:10 | 39726.58 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 644.12 | 27-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 907.20 | 337.37 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 93.31 | ||||||
Maximum of Months | 907.20 | 337.37 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 389.61 | 674.18 |
Report: PeakSpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 15368.40 | 02-JAN-00:10 | 2177.23 | 02-JAN-20:10 | 965.27 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1139.05 | 27-JAN-07:00 |
February | 15368.40 | 01-FEB-00:10 | 2177.23 | 01-FEB-20:10 | 965.27 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 76.18 | 20-FEB-16:00 | 1196.73 | 03-FEB-07:00 |
March | 15368.40 | 01-MAR-00:10 | 2177.23 | 01-MAR-20:10 | 965.27 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 148.21 | 21-MAR-16:00 | 1126.31 | 02-MAR-05:40 |
April | 15368.40 | 01-APR-00:10 | 2177.23 | 03-APR-19:10 | 965.27 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 429.29 | 21-APR-15:00 | 766.61 | 12-APR-06:00 |
May | 15368.40 | 01-MAY-00:10 | 2177.23 | 01-MAY-19:10 | 965.27 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 547.18 | 21-MAY-14:00 | 491.90 | 02-MAY-06:00 |
June | 15368.40 | 01-JUN-00:10 | 2177.23 | 01-JUN-19:10 | 965.27 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 689.04 | 02-JUN-16:20 | 269.19 | 13-JUN-05:00 |
July | 15368.40 | 01-JUL-00:10 | 2177.23 | 03-JUL-19:10 | 965.27 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 670.85 | 02-JUL-16:00 | 132.91 | 05-JUL-06:00 |
August | 15368.40 | 01-AUG-00:10 | 2177.23 | 01-AUG-19:10 | 965.27 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 619.51 | 07-AUG-16:00 | 182.74 | 31-AUG-06:00 |
September | 15368.40 | 01-SEP-00:10 | 2177.23 | 01-SEP-19:10 | 965.27 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 476.44 | 19-SEP-16:30 | 543.37 | 30-SEP-06:00 |
October | 15368.40 | 01-OCT-23:10 | 2177.23 | 02-OCT-19:10 | 965.27 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 428.57 | 01-OCT-15:00 | 618.78 | 25-OCT-06:00 |
November | 15368.40 | 01-NOV-00:10 | 2177.23 | 01-NOV-19:10 | 965.27 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 96.94 | 08-NOV-15:40 | 965.45 | 28-NOV-05:00 |
December | 15368.40 | 01-DEC-00:10 | 2177.23 | 01-DEC-20:10 | 965.27 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 1143.40 | 27-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 15368.40 | 2177.23 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 132.91 | |||||
Maximum of Months | 15368.40 | 2177.23 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 689.04 | 1196.73 |
Report: PeakSpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 45622.98 | 02-JAN-00:10 | 11849.32 | 02-JAN-20:10 | 10029.21 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 3254.09 | 27-JAN-07:00 |
February | 45622.98 | 01-FEB-00:10 | 11849.32 | 01-FEB-20:10 | 10029.21 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 268.47 | 20-FEB-15:50 | 3419.98 | 03-FEB-07:00 |
March | 45622.98 | 01-MAR-00:10 | 11849.32 | 01-MAR-20:10 | 10029.21 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 458.22 | 21-MAR-16:00 | 3217.26 | 02-MAR-06:00 |
April | 45622.98 | 01-APR-00:10 | 11849.32 | 03-APR-19:10 | 10029.21 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1256.15 | 21-APR-14:00 | 2189.80 | 12-APR-06:00 |
May | 45622.98 | 01-MAY-00:10 | 11849.32 | 01-MAY-19:10 | 10029.21 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1567.59 | 21-MAY-14:00 | 1412.35 | 02-MAY-06:00 |
June | 45622.98 | 01-JUN-00:10 | 11849.32 | 01-JUN-19:10 | 10029.21 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1975.47 | 02-JUN-16:00 | 804.21 | 13-JUN-05:00 |
July | 45622.98 | 01-JUL-00:10 | 11849.32 | 03-JUL-19:10 | 10029.21 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1916.98 | 02-JUL-16:00 | 425.77 | 05-JUL-06:00 |
August | 45622.98 | 01-AUG-00:10 | 11849.32 | 01-AUG-19:10 | 10029.21 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1800.60 | 07-AUG-16:00 | 571.06 | 31-AUG-06:00 |
September | 45622.98 | 01-SEP-00:10 | 11849.32 | 01-SEP-19:10 | 10029.21 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1444.02 | 19-SEP-16:00 | 1564.16 | 30-SEP-06:00 |
October | 45622.98 | 01-OCT-23:10 | 11849.32 | 02-OCT-19:10 | 10029.21 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1330.36 | 01-OCT-15:00 | 1767.77 | 25-OCT-06:00 |
November | 45622.98 | 01-NOV-00:10 | 11849.32 | 01-NOV-19:10 | 10029.21 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 336.00 | 08-NOV-15:00 | 2758.11 | 28-NOV-05:00 |
December | 45622.98 | 01-DEC-00:10 | 11849.32 | 01-DEC-20:10 | 10029.21 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 3266.12 | 27-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 45622.98 | 11849.32 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 425.77 | |||||
Maximum of Months | 45622.98 | 11849.32 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 1975.47 | 3419.98 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 392.73 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 300.81 | 27-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 392.73 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.04 | 20-FEB-16:09 | 316.02 | 03-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 392.73 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.51 | 21-MAR-16:00 | 297.41 | 02-MAR-05:00 |
April | 180.00 | 01-APR-00:10 | 392.73 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 111.91 | 21-APR-15:10 | 202.97 | 12-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 392.73 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 141.97 | 19-MAY-16:00 | 130.81 | 02-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 392.73 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 179.98 | 02-JUN-16:00 | 67.52 | 13-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 392.73 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 174.59 | 02-JUL-16:00 | 36.55 | 05-JUL-06:00 |
August | 180.00 | 01-AUG-00:10 | 392.73 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 163.94 | 07-AUG-16:00 | 48.97 | 31-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 392.73 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 131.02 | 19-SEP-16:00 | 144.33 | 30-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 392.73 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 118.83 | 01-OCT-15:10 | 164.14 | 25-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 392.73 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.22 | 03-NOV-16:00 | 255.22 | 28-NOV-05:00 |
December | 180.00 | 01-DEC-00:10 | 392.73 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 301.94 | 27-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 392.73 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.55 | |||||
Maximum of Months | 180.00 | 392.73 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 179.98 | 316.02 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 392.68 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 300.77 | 27-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 392.68 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.04 | 20-FEB-16:09 | 315.99 | 03-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 392.68 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.51 | 21-MAR-16:00 | 297.38 | 02-MAR-06:00 |
April | 180.00 | 01-APR-00:10 | 392.68 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 111.90 | 21-APR-15:10 | 202.95 | 12-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 392.68 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 141.95 | 19-MAY-16:00 | 130.80 | 02-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 392.68 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 179.97 | 02-JUN-16:00 | 67.52 | 13-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 392.68 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 174.58 | 02-JUL-16:00 | 36.55 | 05-JUL-06:00 |
August | 180.00 | 01-AUG-00:10 | 392.68 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 163.92 | 07-AUG-16:00 | 48.96 | 31-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 392.68 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 131.12 | 19-SEP-16:00 | 144.31 | 30-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 392.68 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 118.82 | 01-OCT-15:10 | 164.12 | 25-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 392.68 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.22 | 03-NOV-16:00 | 255.20 | 28-NOV-05:00 |
December | 180.00 | 01-DEC-00:10 | 392.68 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 301.92 | 27-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 392.68 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.55 | |||||
Maximum of Months | 180.00 | 392.68 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 179.97 | 315.99 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 01-JAN-00:10 | 246.81 | 01-JAN-19:10 | 232.19 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 80.82 | 27-JAN-07:20 |
February | 0.00 | 01-FEB-00:10 | 246.81 | 01-FEB-20:10 | 232.19 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 85.08 | 03-FEB-07:00 |
March | 0.00 | 01-MAR-00:10 | 246.81 | 01-MAR-20:10 | 232.19 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.77 | 21-MAR-16:00 | 78.67 | 02-MAR-05:00 |
April | 0.00 | 01-APR-00:10 | 246.81 | 01-APR-18:10 | 232.19 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.38 | 21-APR-14:00 | 58.82 | 12-APR-06:00 |
May | 0.00 | 01-MAY-00:10 | 246.81 | 01-MAY-19:10 | 232.19 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.38 | 21-MAY-14:00 | 42.87 | 02-MAY-06:00 |
June | 0.00 | 01-JUN-00:10 | 246.81 | 01-JUN-19:10 | 232.19 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.93 | 02-JUN-16:00 | 25.64 | 13-JUN-05:00 |
July | 0.00 | 01-JUL-00:10 | 246.81 | 01-JUL-18:10 | 232.19 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.40 | 02-JUL-16:00 | 16.92 | 05-JUL-06:00 |
August | 0.00 | 01-AUG-00:10 | 246.81 | 01-AUG-19:10 | 232.19 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.41 | 07-AUG-16:00 | 20.33 | 31-AUG-06:00 |
September | 0.00 | 01-SEP-00:10 | 246.81 | 01-SEP-19:10 | 232.19 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.25 | 19-SEP-14:00 | 47.02 | 30-SEP-06:00 |
October | 0.00 | 01-OCT-00:10 | 246.81 | 01-OCT-18:10 | 232.19 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.24 | 01-OCT-15:00 | 51.62 | 11-OCT-06:00 |
November | 0.00 | 01-NOV-00:10 | 246.81 | 01-NOV-19:10 | 232.19 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.55 | 08-NOV-15:00 | 72.03 | 17-NOV-04:00 |
December | 0.00 | 01-DEC-00:10 | 246.81 | 01-DEC-20:10 | 232.19 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 81.07 | 19-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 0.00 | 246.81 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.92 | |||||
Maximum of Months | 0.00 | 246.81 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 43.93 | 85.08 |
Report: PeakSpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 246.88 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 83.95 | 27-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 246.88 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.87 | 20-FEB-16:07 | 88.20 | 03-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 246.88 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.31 | 21-MAR-16:00 | 83.00 | 02-MAR-05:00 |
April | 180.00 | 01-APR-00:10 | 246.88 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.23 | 21-APR-15:10 | 56.65 | 12-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 246.88 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.62 | 19-MAY-16:00 | 36.51 | 02-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 246.88 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 50.23 | 02-JUN-16:00 | 18.84 | 13-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 246.88 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.73 | 02-JUL-16:00 | 10.20 | 05-JUL-06:00 |
August | 180.00 | 01-AUG-00:10 | 246.88 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 45.75 | 07-AUG-16:00 | 13.67 | 31-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 246.88 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.60 | 19-SEP-16:00 | 40.28 | 30-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 246.88 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.17 | 01-OCT-15:07 | 45.81 | 25-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 246.88 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.16 | 03-NOV-16:00 | 71.23 | 28-NOV-05:00 |
December | 180.00 | 01-DEC-00:10 | 246.88 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 84.27 | 27-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 246.88 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.20 | |||||
Maximum of Months | 180.00 | 246.88 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 50.23 | 88.20 |
Report: PeakSpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 392.73 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 300.80 | 27-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 392.73 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.04 | 20-FEB-16:09 | 316.01 | 03-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 392.73 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.51 | 21-MAR-16:00 | 297.41 | 02-MAR-06:00 |
April | 180.00 | 01-APR-00:10 | 392.73 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 111.91 | 21-APR-15:10 | 202.97 | 12-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 392.73 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 141.95 | 19-MAY-16:00 | 130.81 | 02-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 392.73 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 179.98 | 02-JUN-16:00 | 67.52 | 13-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 392.73 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 174.59 | 02-JUL-16:00 | 37.44 | 05-JUL-07:10 |
August | 180.00 | 01-AUG-00:10 | 392.73 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 163.94 | 07-AUG-16:00 | 50.74 | 30-AUG-07:10 |
September | 180.00 | 01-SEP-00:10 | 392.73 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 131.13 | 19-SEP-16:00 | 144.33 | 30-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 392.73 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 118.83 | 01-OCT-15:07 | 164.13 | 25-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 392.73 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.22 | 03-NOV-16:00 | 255.22 | 28-NOV-05:00 |
December | 180.00 | 01-DEC-00:10 | 392.73 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 301.94 | 27-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 392.73 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.44 | |||||
Maximum of Months | 180.00 | 392.73 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 179.98 | 316.01 |
Report: PeakSpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 392.68 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 300.79 | 27-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 392.68 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.04 | 20-FEB-16:07 | 316.00 | 03-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 392.68 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.51 | 21-MAR-16:00 | 297.39 | 02-MAR-05:20 |
April | 180.00 | 01-APR-00:10 | 392.68 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 111.90 | 21-APR-15:10 | 202.95 | 12-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 392.68 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 141.96 | 19-MAY-16:00 | 130.80 | 02-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 392.68 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 179.97 | 02-JUN-16:00 | 67.51 | 13-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 392.68 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 174.58 | 02-JUL-16:00 | 38.01 | 05-JUL-07:10 |
August | 180.00 | 01-AUG-00:10 | 392.68 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 163.93 | 07-AUG-16:00 | 49.90 | 30-AUG-07:10 |
September | 180.00 | 01-SEP-00:10 | 392.68 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 131.13 | 19-SEP-16:00 | 144.31 | 30-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 392.68 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 118.83 | 01-OCT-15:10 | 164.12 | 25-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 392.68 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.22 | 03-NOV-16:00 | 255.20 | 28-NOV-05:00 |
December | 180.00 | 01-DEC-00:10 | 392.68 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 301.91 | 27-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 392.68 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.01 | |||||
Maximum of Months | 180.00 | 392.68 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 179.97 | 316.00 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2263.36 | 02-JAN-00:10 | 1282.60 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 362.20 | 27-JAN-07:00 |
February | 2263.36 | 01-FEB-00:10 | 1282.60 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.90 | 20-FEB-16:00 | 380.57 | 03-FEB-07:00 |
March | 2263.36 | 01-MAR-00:10 | 1282.60 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.05 | 21-MAR-16:00 | 358.08 | 02-MAR-05:10 |
April | 2263.36 | 01-APR-00:10 | 1282.60 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.09 | 21-APR-14:00 | 243.94 | 12-APR-06:00 |
May | 2263.36 | 01-MAY-00:10 | 1282.60 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 164.98 | 19-MAY-14:00 | 156.69 | 02-MAY-06:00 |
June | 2263.36 | 01-JUN-00:10 | 1282.60 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 208.58 | 02-JUN-16:00 | 91.26 | 13-JUN-05:00 |
July | 2263.36 | 01-JUL-00:10 | 1282.60 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 202.81 | 02-JUL-16:00 | 51.66 | 05-JUL-06:00 |
August | 2263.36 | 01-AUG-00:10 | 1282.60 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 186.28 | 07-AUG-16:00 | 65.63 | 31-AUG-06:00 |
September | 2263.36 | 01-SEP-00:10 | 1282.60 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 148.94 | 19-SEP-16:00 | 175.54 | 30-SEP-06:00 |
October | 2263.36 | 01-OCT-23:10 | 1282.60 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 139.39 | 01-OCT-15:00 | 196.97 | 25-OCT-06:00 |
November | 2263.36 | 01-NOV-00:10 | 1282.60 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.00 | 08-NOV-15:00 | 307.05 | 28-NOV-05:00 |
December | 2263.36 | 01-DEC-00:10 | 1282.60 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 363.56 | 27-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 2263.36 | 1282.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.66 | ||||
Maximum of Months | 2263.36 | 1282.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 208.58 | 380.57 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 392.73 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 301.57 | 27-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 392.73 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.40 | 20-FEB-16:06 | 316.79 | 03-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 392.73 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.89 | 21-MAR-16:00 | 298.18 | 02-MAR-06:00 |
April | 180.00 | 01-APR-00:10 | 392.73 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 111.32 | 21-APR-15:07 | 203.69 | 12-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 392.73 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 141.36 | 19-MAY-16:00 | 131.49 | 02-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 392.73 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 179.42 | 02-JUN-16:00 | 68.18 | 13-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 392.73 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 173.85 | 02-JUL-16:00 | 37.21 | 05-JUL-06:00 |
August | 180.00 | 01-AUG-00:10 | 392.73 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 163.30 | 07-AUG-16:00 | 49.63 | 31-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 392.73 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 126.88 | 19-SEP-16:00 | 145.02 | 30-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 392.73 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 118.24 | 01-OCT-15:10 | 164.84 | 25-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 392.73 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.59 | 03-NOV-16:00 | 255.96 | 28-NOV-05:00 |
December | 180.00 | 01-DEC-00:10 | 392.73 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 302.71 | 27-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 392.73 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.21 | |||||
Maximum of Months | 180.00 | 392.73 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 179.42 | 316.79 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 392.68 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 301.55 | 27-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 392.68 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.40 | 20-FEB-16:09 | 316.77 | 03-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 392.68 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.89 | 21-MAR-16:00 | 298.16 | 02-MAR-05:00 |
April | 180.00 | 01-APR-00:10 | 392.68 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 111.31 | 21-APR-15:06 | 203.67 | 12-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 392.68 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 141.36 | 19-MAY-16:00 | 131.48 | 02-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 392.68 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 179.41 | 02-JUN-16:00 | 68.18 | 13-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 392.68 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 173.78 | 02-JUL-16:00 | 37.20 | 05-JUL-06:00 |
August | 180.00 | 01-AUG-00:10 | 392.68 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 163.31 | 07-AUG-16:00 | 49.63 | 31-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 392.68 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 130.51 | 19-SEP-16:00 | 145.01 | 30-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 392.68 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 118.23 | 01-OCT-15:07 | 164.83 | 25-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 392.68 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.59 | 03-NOV-16:00 | 255.95 | 28-NOV-05:00 |
December | 180.00 | 01-DEC-00:10 | 392.68 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 302.68 | 27-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 392.68 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.20 | |||||
Maximum of Months | 180.00 | 392.68 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 179.41 | 316.77 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 246.88 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 154.29 | 27-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 246.88 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.44 | 20-FEB-16:09 | 162.08 | 03-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 246.88 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.41 | 21-MAR-16:00 | 152.56 | 02-MAR-06:00 |
April | 180.00 | 01-APR-00:10 | 246.88 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.95 | 21-APR-15:07 | 104.21 | 12-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 246.88 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 72.34 | 19-MAY-16:00 | 67.28 | 02-MAY-06:00 |
June | 180.00 | 01-JUN-00:10 | 246.88 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 91.80 | 02-JUN-16:00 | 34.88 | 13-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 246.88 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 89.03 | 02-JUL-16:00 | 19.04 | 05-JUL-06:00 |
August | 180.00 | 01-AUG-00:10 | 246.88 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 83.58 | 07-AUG-16:00 | 25.39 | 31-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 246.88 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 66.40 | 19-SEP-16:00 | 74.20 | 30-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 246.88 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.49 | 01-OCT-15:10 | 84.34 | 25-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 246.88 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.62 | 03-NOV-16:00 | 130.96 | 28-NOV-05:00 |
December | 180.00 | 01-DEC-00:10 | 246.88 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 154.87 | 27-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 246.88 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.04 | |||||
Maximum of Months | 180.00 | 246.88 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 91.80 | 162.08 |
Report: PeakSpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 3823.39 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 733.38 | 27-JAN-07:00 |
February | 26988.77 | 01-FEB-00:10 | 3823.39 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 57.51 | 20-FEB-15:20 | 770.65 | 03-FEB-07:00 |
March | 26988.77 | 01-MAR-00:10 | 3823.39 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 99.71 | 22-MAR-13:00 | 728.27 | 02-MAR-05:20 |
April | 26988.77 | 01-APR-00:10 | 3823.39 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 276.90 | 21-APR-14:00 | 505.85 | 12-APR-06:00 |
May | 26988.77 | 01-MAY-00:10 | 3823.39 | 01-MAY-19:10 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 341.62 | 19-MAY-14:00 | 339.24 | 02-MAY-06:00 |
June | 26988.77 | 01-JUN-00:10 | 3823.39 | 01-JUN-19:10 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 428.46 | 02-JUN-16:30 | 198.26 | 13-JUN-05:00 |
July | 26988.77 | 01-JUL-00:10 | 3823.39 | 03-JUL-19:10 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 426.09 | 02-JUL-16:00 | 118.22 | 05-JUL-06:00 |
August | 26988.77 | 01-AUG-00:10 | 3823.39 | 01-AUG-19:10 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 386.19 | 07-AUG-16:00 | 152.23 | 16-AUG-22:53 |
September | 26988.77 | 01-SEP-00:10 | 3823.39 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 316.82 | 19-SEP-14:00 | 370.16 | 30-SEP-06:00 |
October | 26988.77 | 01-OCT-23:10 | 3823.39 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 295.89 | 01-OCT-15:00 | 413.13 | 25-OCT-06:00 |
November | 26988.77 | 01-NOV-00:10 | 3823.39 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 72.64 | 08-NOV-15:00 | 631.18 | 27-NOV-23:00 |
December | 26988.77 | 01-DEC-00:10 | 3823.39 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 736.19 | 27-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26988.77 | 3823.39 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.22 | |||||
Maximum of Months | 26988.77 | 3823.39 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 428.46 | 770.65 |
Report: PeakSpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 3823.39 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 733.56 | 27-JAN-07:00 |
February | 26988.77 | 01-FEB-00:10 | 3823.39 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 57.63 | 20-FEB-15:10 | 770.49 | 03-FEB-07:00 |
March | 26988.77 | 01-MAR-00:10 | 3823.39 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 99.62 | 22-MAR-13:00 | 728.94 | 02-MAR-05:20 |
April | 26988.77 | 01-APR-00:10 | 3823.39 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 274.04 | 21-APR-14:00 | 507.39 | 12-APR-06:00 |
May | 26988.77 | 01-MAY-00:10 | 3823.39 | 01-MAY-19:10 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 338.70 | 19-MAY-14:00 | 340.96 | 02-MAY-06:00 |
June | 26988.77 | 01-JUN-00:10 | 3823.39 | 01-JUN-19:10 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 426.27 | 02-JUN-16:30 | 199.22 | 13-JUN-05:00 |
July | 26988.77 | 01-JUL-00:10 | 3823.39 | 03-JUL-19:10 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 423.77 | 02-JUL-16:00 | 119.48 | 05-JUL-06:00 |
August | 26988.77 | 01-AUG-00:10 | 3823.39 | 01-AUG-19:10 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 384.65 | 07-AUG-16:00 | 154.73 | 16-AUG-22:53 |
September | 26988.77 | 01-SEP-00:10 | 3823.39 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 314.68 | 19-SEP-14:00 | 371.63 | 30-SEP-06:00 |
October | 26988.77 | 01-OCT-23:10 | 3823.39 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 295.78 | 01-OCT-15:00 | 414.47 | 25-OCT-06:00 |
November | 26988.77 | 01-NOV-00:10 | 3823.39 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 72.60 | 08-NOV-15:00 | 633.79 | 27-NOV-23:00 |
December | 26988.77 | 01-DEC-00:10 | 3823.39 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 735.93 | 27-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26988.77 | 3823.39 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 119.48 | |||||
Maximum of Months | 26988.77 | 3823.39 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 426.27 | 770.49 |
Report: PeakSpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2401.70 | 02-JAN-00:10 | 1020.78 | 02-JAN-20:10 | 15112.11 | 01-JAN-07:10 | 22492.83 | 01-JAN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 695.06 | 27-JAN-08:00 |
February | 2401.70 | 01-FEB-00:10 | 1020.78 | 01-FEB-20:10 | 15112.11 | 01-FEB-07:10 | 22492.83 | 01-FEB-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 716.01 | 03-FEB-07:00 |
March | 2401.70 | 01-MAR-00:10 | 1020.78 | 01-MAR-20:10 | 15112.11 | 01-MAR-07:10 | 22492.83 | 01-MAR-16:10 | 0.00 | 0.00 | 0.00 | 23.86 | 22-MAR-13:20 | 649.37 | 02-MAR-05:40 |
April | 2401.70 | 01-APR-00:10 | 1020.78 | 03-APR-19:10 | 15112.11 | 01-APR-06:10 | 22492.83 | 01-APR-15:09 | 0.00 | 0.00 | 0.00 | 184.88 | 21-APR-14:00 | 463.80 | 12-APR-06:00 |
May | 2401.70 | 01-MAY-00:10 | 1020.78 | 01-MAY-19:10 | 15112.11 | 01-MAY-06:10 | 22492.83 | 01-MAY-15:09 | 0.00 | 0.00 | 0.00 | 245.38 | 21-MAY-14:00 | 330.52 | 02-MAY-06:00 |
June | 2401.70 | 01-JUN-00:10 | 1020.78 | 01-JUN-19:10 | 15112.11 | 01-JUN-06:10 | 22492.83 | 01-JUN-15:09 | 0.00 | 0.00 | 0.00 | 328.51 | 02-JUN-16:00 | 181.15 | 13-JUN-05:20 |
July | 2401.70 | 01-JUL-00:10 | 1020.78 | 03-JUL-19:10 | 15112.11 | 01-JUL-06:10 | 22492.83 | 01-JUL-15:09 | 0.00 | 0.00 | 0.00 | 316.43 | 02-JUL-16:00 | 114.27 | 05-JUL-06:00 |
August | 2401.70 | 01-AUG-00:10 | 1020.78 | 01-AUG-19:10 | 15112.11 | 01-AUG-06:10 | 22492.83 | 01-AUG-15:09 | 0.00 | 0.00 | 0.00 | 292.98 | 07-AUG-16:00 | 150.12 | 16-AUG-22:40 |
September | 2401.70 | 01-SEP-00:10 | 1020.78 | 01-SEP-19:10 | 15112.11 | 01-SEP-06:10 | 22492.83 | 01-SEP-15:09 | 0.00 | 0.00 | 0.00 | 220.88 | 19-SEP-14:00 | 337.07 | 30-SEP-06:00 |
October | 2401.70 | 01-OCT-23:10 | 1020.78 | 02-OCT-19:10 | 15112.11 | 01-OCT-06:10 | 22492.83 | 01-OCT-15:09 | 0.00 | 0.00 | 0.00 | 197.28 | 01-OCT-15:00 | 378.27 | 25-OCT-06:00 |
November | 2401.70 | 01-NOV-00:10 | 1020.78 | 01-NOV-19:10 | 15112.11 | 01-NOV-06:10 | 22492.83 | 01-NOV-15:09 | 0.00 | 0.00 | 0.00 | 7.46 | 08-NOV-15:00 | 578.37 | 27-NOV-23:00 |
December | 2401.70 | 01-DEC-00:10 | 1020.78 | 01-DEC-20:10 | 15112.11 | 01-DEC-07:10 | 22492.83 | 01-DEC-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 669.87 | 27-DEC-07:30 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 2401.70 | 1020.78 | 15112.11 | 22492.83 | 0.00 | 0.00 | 0.00 | 0.00 | 114.27 | ||||||
Maximum of Months | 2401.70 | 1020.78 | 15112.11 | 22492.83 | 0.00 | 0.00 | 0.00 | 328.51 | 716.01 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2395.44 | 02-JAN-00:10 | 1357.44 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 642.51 | 27-JAN-07:00 |
February | 2395.44 | 01-FEB-00:10 | 1357.44 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.44 | 20-FEB-16:00 | 675.02 | 03-FEB-07:00 |
March | 2395.44 | 01-MAR-00:10 | 1357.44 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.82 | 21-MAR-16:00 | 635.24 | 02-MAR-05:50 |
April | 2395.44 | 01-APR-00:10 | 1357.44 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 236.94 | 21-APR-15:00 | 433.12 | 12-APR-06:00 |
May | 2395.44 | 01-MAY-00:10 | 1357.44 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 295.16 | 19-MAY-16:00 | 278.74 | 02-MAY-06:00 |
June | 2395.44 | 01-JUN-00:10 | 1357.44 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 369.97 | 02-JUN-16:40 | 143.34 | 13-JUN-05:00 |
July | 2395.44 | 01-JUL-00:10 | 1357.44 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 356.71 | 01-JUL-17:00 | 77.04 | 05-JUL-06:00 |
August | 2395.44 | 01-AUG-00:10 | 1357.44 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 328.55 | 07-AUG-16:00 | 103.62 | 31-AUG-06:00 |
September | 2395.44 | 01-SEP-00:10 | 1357.44 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 265.53 | 19-SEP-16:00 | 307.66 | 30-SEP-06:00 |
October | 2395.44 | 01-OCT-23:10 | 1357.44 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 243.30 | 01-OCT-15:00 | 350.00 | 25-OCT-06:00 |
November | 2395.44 | 01-NOV-00:10 | 1357.44 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.67 | 08-NOV-15:00 | 544.87 | 28-NOV-05:00 |
December | 2395.44 | 01-DEC-00:10 | 1357.44 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 643.62 | 27-DEC-07:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 2395.44 | 1357.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.04 | ||||
Maximum of Months | 2395.44 | 1357.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 369.97 | 675.02 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 19555.90 | 12-JAN-19:10 | 53675.50 | 72090.20 | 57488.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 18758.35 | 22-FEB-20:10 | 8945.92 | 13517.00 | 10113.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 17799.84 | 01-MAR-21:00 | 8945.92 | 13517.00 | 10113.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 18271.64 | 07-APR-20:00 | 8945.92 | 13517.00 | 10113.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 19358.14 | 11-MAY-20:00 | 8945.92 | 13517.00 | 10113.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 20361.87 | 08-JUN-20:00 | 8945.92 | 13517.00 | 10113.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 22386.27 | 26-JUL-18:50 | 8945.92 | 12015.03 | 9581.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 23534.96 | 07-AUG-18:10 | 53675.50 | 72090.20 | 57488.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 23757.44 | 17-SEP-10:35 | 7667.93 | 9011.45 | 8516.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 23308.91 | 01-OCT-10:35 | 7667.93 | 9011.45 | 8516.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 21752.54 | 09-NOV-19:10 | 62621.41 | 84105.23 | 67070.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 20408.78 | 01-DEC-21:00 | 8945.92 | 13517.00 | 10113.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 17799.84 | 7667.93 | 9011.45 | 8516.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 23757.44 | 62621.41 | 84105.23 | 67070.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3022.90 | 01-JAN-11:35 | 779.69 | 458.20 | 577.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 153.21 |
February | 3122.37 | 07-FEB-11:35 | 519.79 | 381.83 | 505.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.65 |
March | 2938.03 | 05-MAR-11:35 | 779.69 | 458.20 | 577.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.67 |
April | 2815.06 | 04-APR-10:35 | 519.79 | 381.83 | 505.18 | 0.00 | 0.00 | 0.00 | 0.00 | 35.87 | 0.00 |
May | 3042.50 | 31-MAY-18:02 | 5457.82 | 3665.58 | 3897.11 | 0.00 | 0.00 | 0.00 | 0.00 | 177.89 | 0.00 |
June | 3338.82 | 15-JUN-18:10 | 5457.82 | 3665.58 | 3897.11 | 0.00 | 0.00 | 0.00 | 0.00 | 257.78 | 0.00 |
July | 3323.83 | 26-JUL-18:10 | 5457.82 | 3665.58 | 3897.11 | 0.00 | 0.00 | 0.00 | 0.00 | 223.27 | 0.00 |
August | 3369.31 | 27-AUG-10:35 | 779.69 | 458.20 | 577.35 | 0.00 | 0.00 | 0.00 | 0.00 | 191.49 | 0.00 |
September | 3489.09 | 17-SEP-10:35 | 779.69 | 458.20 | 577.35 | 0.00 | 0.00 | 0.00 | 0.00 | 140.68 | 0.00 |
October | 3559.87 | 05-OCT-10:35 | 519.79 | 381.83 | 505.18 | 0.00 | 0.00 | 0.00 | 0.00 | 100.09 | 0.00 |
November | 3458.94 | 10-NOV-11:35 | 519.79 | 381.83 | 505.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.85 |
December | 2909.21 | 09-DEC-11:40 | 389.84 | 190.92 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2815.06 | 389.84 | 190.92 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3559.87 | 5457.82 | 3665.58 | 3897.11 | 0.00 | 0.00 | 0.00 | 0.00 | 257.78 | 153.21 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1847.61 | 12-JAN-21:00 | 1053.36 | 795.89 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.31 |
February | 1916.25 | 21-FEB-21:00 | 1053.36 | 795.89 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.32 |
March | 2002.14 | 16-MAR-18:01 | 7373.52 | 4952.21 | 5265.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.46 |
April | 2217.48 | 19-APR-18:10 | 7373.52 | 4952.21 | 5265.02 | 0.00 | 0.00 | 0.00 | 0.00 | 61.37 | 0.00 |
May | 2302.72 | 31-MAY-18:10 | 6320.16 | 4244.75 | 4512.87 | 0.00 | 0.00 | 0.00 | 0.00 | 67.92 | 0.00 |
June | 2435.52 | 15-JUN-18:10 | 6320.16 | 4244.75 | 4512.87 | 0.00 | 0.00 | 0.00 | 0.00 | 99.56 | 0.00 |
July | 2419.51 | 26-JUL-18:10 | 6320.16 | 4244.75 | 4512.87 | 0.00 | 0.00 | 0.00 | 0.00 | 86.35 | 0.00 |
August | 2399.11 | 07-AUG-18:10 | 6320.16 | 4244.75 | 4512.87 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 | 0.00 |
September | 2311.02 | 20-SEP-18:10 | 6320.16 | 4244.75 | 4512.87 | 0.00 | 0.00 | 0.00 | 0.00 | 68.06 | 0.00 |
October | 2238.59 | 05-OCT-18:10 | 7373.52 | 4952.21 | 5265.02 | 0.00 | 0.00 | 0.00 | 0.00 | 41.99 | 0.00 |
November | 2021.03 | 09-NOV-19:10 | 7373.52 | 4952.21 | 5265.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.69 |
December | 1818.49 | 15-DEC-21:00 | 1053.36 | 795.89 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.22 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1818.49 | 1053.36 | 795.89 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2435.52 | 7373.52 | 4952.21 | 5265.02 | 0.00 | 0.00 | 0.00 | 0.00 | 99.56 | 62.31 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1563.50 | 03-JAN-21:00 | 222.77 | 1487.69 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 113.59 |
February | 1778.86 | 07-FEB-20:50 | 222.77 | 1487.69 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.97 |
March | 1965.52 | 16-MAR-20:00 | 222.77 | 1487.69 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.92 |
April | 2228.19 | 19-APR-19:10 | 445.54 | 2975.37 | 1678.89 | 0.00 | 0.00 | 0.00 | 0.00 | 134.08 | 0.00 |
May | 2442.52 | 31-MAY-18:10 | 1336.61 | 7934.32 | 4771.59 | 0.00 | 0.00 | 0.00 | 0.00 | 161.65 | 0.00 |
June | 2587.17 | 15-JUN-18:10 | 1336.61 | 7934.32 | 4771.59 | 0.00 | 0.00 | 0.00 | 0.00 | 236.30 | 0.00 |
July | 2596.05 | 03-JUL-18:10 | 1336.61 | 7934.32 | 4771.59 | 0.00 | 0.00 | 0.00 | 0.00 | 242.20 | 0.00 |
August | 2526.66 | 07-AUG-18:10 | 1336.61 | 7934.32 | 4771.59 | 0.00 | 0.00 | 0.00 | 0.00 | 208.34 | 0.00 |
September | 2395.61 | 20-SEP-18:02 | 1336.61 | 7934.32 | 4771.59 | 0.00 | 0.00 | 0.00 | 0.00 | 164.07 | 0.00 |
October | 2288.28 | 05-OCT-18:20 | 445.54 | 2644.77 | 1590.53 | 0.00 | 0.00 | 0.00 | 0.00 | 91.26 | 0.00 |
November | 1986.67 | 09-NOV-21:00 | 222.77 | 1487.69 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.36 |
December | 1480.93 | 15-DEC-21:00 | 222.77 | 1487.69 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 114.07 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1480.93 | 222.77 | 1487.69 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2596.05 | 1336.61 | 7934.32 | 4771.59 | 0.00 | 0.00 | 0.00 | 0.00 | 242.20 | 114.07 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 482.31 | 03-JAN-21:10 | 195.84 | 242.76 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.24 |
February | 603.96 | 07-FEB-22:00 | 195.84 | 242.76 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.20 |
March | 720.48 | 15-MAR-21:00 | 195.84 | 242.76 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.78 |
April | 1023.00 | 21-APR-20:00 | 171.36 | 273.10 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 48.44 | 0.00 |
May | 1151.80 | 31-MAY-19:10 | 342.72 | 546.20 | 484.31 | 0.00 | 0.00 | 0.00 | 0.00 | 84.22 | 0.00 |
June | 1284.12 | 15-JUN-18:10 | 1028.16 | 1456.53 | 1376.47 | 0.00 | 0.00 | 0.00 | 0.00 | 137.62 | 0.00 |
July | 1284.44 | 03-JUL-18:10 | 1028.16 | 1456.53 | 1376.47 | 0.00 | 0.00 | 0.00 | 0.00 | 141.26 | 0.00 |
August | 1231.30 | 07-AUG-18:20 | 342.72 | 485.51 | 458.82 | 0.00 | 0.00 | 0.00 | 0.00 | 117.10 | 0.00 |
September | 1092.51 | 21-SEP-20:00 | 171.36 | 273.10 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 44.15 | 0.00 |
October | 1026.04 | 05-OCT-20:00 | 171.36 | 273.10 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 27.97 | 0.00 |
November | 752.97 | 09-NOV-22:00 | 195.84 | 242.76 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.58 |
December | 458.27 | 15-DEC-22:00 | 195.84 | 242.76 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.81 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 458.27 | 171.36 | 242.76 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1284.44 | 1028.16 | 1456.53 | 1376.47 | 0.00 | 0.00 | 0.00 | 0.00 | 141.26 | 68.24 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 35924.14 | 03-JAN-21:00 | 705.60 | 337.37 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 225.52 |
February | 36275.22 | 21-FEB-21:00 | 705.60 | 337.37 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 212.38 |
March | 36418.54 | 21-MAR-20:00 | 705.60 | 337.37 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 169.37 |
April | 37455.04 | 19-APR-20:00 | 705.60 | 337.37 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 103.77 | 0.00 |
May | 37787.26 | 31-MAY-20:00 | 705.60 | 337.37 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 130.74 | 0.00 |
June | 38342.34 | 15-JUN-20:00 | 705.60 | 337.37 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 228.89 | 0.00 |
July | 38198.40 | 26-JUL-20:00 | 705.60 | 337.37 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 132.92 | 0.00 |
August | 38120.41 | 07-AUG-20:00 | 705.60 | 337.37 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 183.34 | 0.00 |
September | 37647.42 | 20-SEP-20:00 | 705.60 | 337.37 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 44.03 | 0.00 |
October | 37405.15 | 05-OCT-20:00 | 705.60 | 337.37 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 4.37 | 0.00 |
November | 36481.70 | 09-NOV-21:00 | 705.60 | 337.37 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 91.31 |
December | 35799.25 | 15-DEC-21:00 | 705.60 | 337.37 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 226.50 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 35799.25 | 705.60 | 337.37 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 38342.34 | 705.60 | 337.37 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 228.89 | 226.50 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 12726.90 | 01-JAN-11:35 | 10245.60 | 1451.48 | 812.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 335.36 |
February | 13089.37 | 19-FEB-11:35 | 10245.60 | 1451.48 | 812.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.62 |
March | 12405.00 | 05-MAR-11:35 | 10245.60 | 1451.48 | 812.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 187.03 |
April | 12875.44 | 19-APR-18:03 | 83672.40 | 13547.18 | 6401.28 | 0.00 | 0.00 | 0.00 | 0.00 | 352.93 | 0.00 |
May | 13365.11 | 31-MAY-18:10 | 71719.20 | 11611.87 | 5486.82 | 0.00 | 0.00 | 0.00 | 0.00 | 390.38 | 0.00 |
June | 14106.58 | 14-JUN-18:10 | 71719.20 | 11611.87 | 5486.82 | 0.00 | 0.00 | 0.00 | 0.00 | 613.64 | 0.00 |
July | 14111.07 | 03-JUL-18:10 | 71719.20 | 11611.87 | 5486.82 | 0.00 | 0.00 | 0.00 | 0.00 | 587.75 | 0.00 |
August | 14049.84 | 07-AUG-18:10 | 71719.20 | 11611.87 | 5486.82 | 0.00 | 0.00 | 0.00 | 0.00 | 498.76 | 0.00 |
September | 14200.35 | 17-SEP-10:35 | 10245.60 | 1451.48 | 812.86 | 0.00 | 0.00 | 0.00 | 0.00 | 325.62 | 0.00 |
October | 14157.01 | 22-OCT-10:35 | 10245.60 | 1451.48 | 812.86 | 0.00 | 0.00 | 0.00 | 0.00 | 18.16 | 0.00 |
November | 13773.93 | 11-NOV-11:35 | 10245.60 | 1451.48 | 812.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 219.33 |
December | 12324.52 | 10-DEC-11:35 | 10245.60 | 1451.48 | 812.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 235.07 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 12324.52 | 10245.60 | 1451.48 | 812.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14200.35 | 83672.40 | 13547.18 | 6401.28 | 0.00 | 0.00 | 0.00 | 0.00 | 613.64 | 335.36 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 37038.98 | 12-JAN-19:10 | 212907.24 | 63196.36 | 57008.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 724.64 |
February | 37963.05 | 22-FEB-19:03 | 212907.24 | 63196.36 | 57008.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 384.03 |
March | 39314.42 | 16-MAR-18:10 | 248391.78 | 73729.08 | 66509.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 151.54 |
April | 43050.52 | 19-APR-18:10 | 248391.78 | 73729.08 | 66509.49 | 0.00 | 0.00 | 0.00 | 0.00 | 997.34 | 0.00 |
May | 44823.93 | 31-MAY-18:10 | 212907.24 | 63196.36 | 57008.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1102.03 | 0.00 |
June | 46864.58 | 15-JUN-18:10 | 212907.24 | 63196.36 | 57008.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1629.82 | 0.00 |
July | 46885.37 | 03-JUL-18:10 | 212907.24 | 63196.36 | 57008.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1673.71 | 0.00 |
August | 46323.01 | 07-AUG-18:10 | 212907.24 | 63196.36 | 57008.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1426.27 | 0.00 |
September | 44736.94 | 20-SEP-18:10 | 212907.24 | 63196.36 | 57008.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1109.14 | 0.00 |
October | 43560.26 | 05-OCT-18:10 | 248391.78 | 73729.08 | 66509.49 | 0.00 | 0.00 | 0.00 | 0.00 | 678.18 | 0.00 |
November | 39725.35 | 09-NOV-19:10 | 248391.78 | 73729.08 | 66509.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.74 |
December | 36331.62 | 15-DEC-21:00 | 35484.54 | 11849.32 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 832.53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 36331.62 | 35484.54 | 11849.32 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 46885.37 | 248391.78 | 73729.08 | 66509.49 | 0.00 | 0.00 | 0.00 | 0.00 | 1673.71 | 832.53 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3759.58 | 12-JAN-16:01 | 680.40 | 769.75 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.80 |
February | 3836.15 | 20-FEB-16:01 | 378.00 | 907.20 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 7.10 | 0.00 |
March | 3824.56 | 16-MAR-15:01 | 680.40 | 769.75 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 2.99 | 0.00 |
April | 3861.25 | 30-APR-15:01 | 378.00 | 907.20 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 79.45 | 0.00 |
May | 3885.84 | 20-MAY-15:01 | 378.00 | 907.20 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 99.76 | 0.00 |
June | 3885.67 | 15-JUN-18:02 | 831.60 | 2097.16 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 136.20 | 0.00 |
July | 3519.24 | 19-JUL-18:02 | 831.60 | 2097.16 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 65.59 | 0.00 |
August | 3888.00 | 23-AUG-15:01 | 680.40 | 769.75 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 111.01 | 0.00 |
September | 3887.91 | 11-SEP-15:01 | 680.40 | 769.75 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 71.43 | 0.00 |
October | 3896.79 | 01-OCT-15:01 | 378.00 | 907.20 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 103.88 | 0.00 |
November | 3840.31 | 09-NOV-16:01 | 680.40 | 769.75 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 8.31 | 0.00 |
December | 3706.74 | 17-DEC-16:01 | 378.00 | 907.20 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.79 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3519.24 | 378.00 | 769.75 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3896.79 | 831.60 | 2097.16 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 136.20 | 75.79 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3612.50 | 12-JAN-16:01 | 680.40 | 769.66 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.24 |
February | 3759.91 | 20-FEB-16:01 | 378.00 | 907.09 | 534.64 | 0.00 | 0.00 | 0.00 | 0.00 | 8.64 | 0.00 |
March | 3755.94 | 16-MAR-15:01 | 680.40 | 769.66 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 4.29 | 0.00 |
April | 3825.68 | 30-APR-15:01 | 378.00 | 907.09 | 534.64 | 0.00 | 0.00 | 0.00 | 0.00 | 79.71 | 0.00 |
May | 3857.13 | 20-MAY-15:01 | 378.00 | 907.09 | 534.64 | 0.00 | 0.00 | 0.00 | 0.00 | 99.82 | 0.00 |
June | 3870.47 | 15-JUN-18:02 | 831.60 | 2096.92 | 774.30 | 0.00 | 0.00 | 0.00 | 0.00 | 135.85 | 0.00 |
July | 3500.64 | 30-JUL-18:02 | 702.00 | 2356.09 | 774.30 | 0.00 | 0.00 | 0.00 | 0.00 | 67.60 | 0.00 |
August | 3848.93 | 23-AUG-15:01 | 680.40 | 769.66 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 111.37 | 0.00 |
September | 3834.31 | 11-SEP-15:01 | 680.40 | 769.66 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 72.24 | 0.00 |
October | 3830.17 | 01-OCT-15:01 | 378.00 | 907.09 | 534.64 | 0.00 | 0.00 | 0.00 | 0.00 | 105.05 | 0.00 |
November | 3767.81 | 09-NOV-16:01 | 680.40 | 769.66 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 9.72 | 0.00 |
December | 3460.05 | 16-DEC-16:02 | 324.00 | 777.51 | 458.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3460.05 | 324.00 | 769.66 | 458.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3870.47 | 831.60 | 2356.09 | 774.30 | 0.00 | 0.00 | 0.00 | 0.00 | 135.85 | 74.55 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 609.96 | 12-JAN-14:30 | 0.00 | 69.11 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.57 |
February | 599.57 | 20-FEB-14:10 | 0.00 | 81.45 | 74.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.99 |
March | 503.71 | 16-MAR-13:30 | 0.00 | 69.11 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.60 |
April | 492.06 | 03-APR-14:00 | 0.00 | 69.11 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 9.77 | 0.00 |
May | 512.18 | 19-MAY-20:20 | 0.00 | 219.66 | 180.59 | 0.00 | 0.00 | 0.00 | 0.00 | 21.31 | 0.00 |
June | 560.98 | 15-JUN-20:20 | 0.00 | 219.66 | 180.59 | 0.00 | 0.00 | 0.00 | 0.00 | 29.55 | 0.00 |
July | 573.47 | 02-JUL-20:50 | 0.00 | 246.81 | 180.59 | 0.00 | 0.00 | 0.00 | 0.00 | 27.76 | 0.00 |
August | 577.40 | 06-AUG-19:05 | 0.00 | 493.63 | 340.55 | 0.00 | 0.00 | 0.00 | 0.00 | 32.38 | 0.00 |
September | 668.56 | 19-SEP-13:30 | 0.00 | 69.11 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 28.72 | 0.00 |
October | 735.62 | 22-OCT-13:20 | 0.00 | 81.45 | 74.82 | 0.00 | 0.00 | 0.00 | 0.00 | 7.64 | 0.00 |
November | 683.34 | 09-NOV-13:50 | 0.00 | 69.11 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.48 |
December | 543.88 | 16-DEC-13:40 | 0.00 | 81.45 | 74.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 492.06 | 0.00 | 69.11 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 735.62 | 0.00 | 493.63 | 340.55 | 0.00 | 0.00 | 0.00 | 0.00 | 32.38 | 27.05 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1237.57 | 13-JAN-19:02 | 831.60 | 1318.35 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.19 |
February | 1305.91 | 20-FEB-16:01 | 378.00 | 570.30 | 523.86 | 0.00 | 0.00 | 0.00 | 0.00 | 4.96 | 0.00 |
March | 1357.97 | 15-MAR-18:01 | 970.20 | 1538.07 | 885.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.19 |
April | 1430.39 | 28-APR-18:01 | 970.20 | 1538.07 | 885.15 | 0.00 | 0.00 | 0.00 | 0.00 | 15.70 | 0.00 |
May | 1438.17 | 13-MAY-18:01 | 819.00 | 1728.17 | 885.15 | 0.00 | 0.00 | 0.00 | 0.00 | 25.09 | 0.00 |
June | 1437.32 | 17-JUN-18:02 | 702.00 | 1481.29 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 36.49 | 0.00 |
July | 1335.10 | 15-JUL-15:02 | 324.00 | 488.83 | 449.03 | 0.00 | 0.00 | 0.00 | 0.00 | 29.29 | 0.00 |
August | 1439.01 | 27-AUG-18:01 | 819.00 | 1728.17 | 885.15 | 0.00 | 0.00 | 0.00 | 0.00 | 30.00 | 0.00 |
September | 1431.17 | 17-SEP-18:01 | 819.00 | 1728.17 | 885.15 | 0.00 | 0.00 | 0.00 | 0.00 | 21.14 | 0.00 |
October | 1429.37 | 01-OCT-18:01 | 819.00 | 1728.17 | 885.15 | 0.00 | 0.00 | 0.00 | 0.00 | 20.86 | 0.00 |
November | 1324.44 | 08-NOV-19:01 | 970.20 | 1538.07 | 885.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.16 |
December | 1276.22 | 09-DEC-09:01 | 378.00 | 967.78 | 1119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.76 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1237.57 | 324.00 | 488.83 | 449.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1439.01 | 970.20 | 1728.17 | 1119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 36.49 | 25.19 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3310.05 | 12-JAN-16:01 | 680.40 | 769.75 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.78 |
February | 3362.24 | 20-FEB-16:01 | 378.00 | 907.20 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 7.72 | 0.00 |
March | 3360.55 | 16-MAR-15:01 | 680.40 | 769.75 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 3.31 | 0.00 |
April | 3406.27 | 21-APR-15:01 | 680.40 | 769.75 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 97.91 | 0.00 |
May | 3437.47 | 30-MAY-08:61 | 252.00 | 1209.60 | 792.83 | 0.00 | 0.00 | 0.00 | 0.00 | 44.17 | 0.00 |
June | 3453.68 | 15-JUN-08:61 | 252.00 | 1209.60 | 792.83 | 0.00 | 0.00 | 0.00 | 0.00 | 74.07 | 0.00 |
July | 3199.63 | 09-JUL-08:61 | 378.00 | 1539.49 | 1143.15 | 0.00 | 0.00 | 0.00 | 0.00 | 21.76 | 0.00 |
August | 3427.25 | 23-AUG-15:01 | 680.40 | 769.75 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 110.96 | 0.00 |
September | 3409.22 | 11-SEP-15:01 | 680.40 | 769.75 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 72.00 | 0.00 |
October | 3423.87 | 01-OCT-15:01 | 378.00 | 907.20 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 104.20 | 0.00 |
November | 3373.31 | 09-NOV-16:01 | 680.40 | 769.75 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 8.68 | 0.00 |
December | 3288.81 | 09-DEC-09:01 | 378.00 | 1539.49 | 1143.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.91 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3199.63 | 252.00 | 769.75 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3453.68 | 680.40 | 1539.49 | 1143.15 | 0.00 | 0.00 | 0.00 | 0.00 | 110.96 | 86.91 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2270.82 | 31-JAN-09:02 | 216.00 | 1036.68 | 679.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 115.38 |
February | 3276.96 | 20-FEB-09:01 | 378.00 | 1539.31 | 1143.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 123.99 |
March | 3300.11 | 22-MAR-15:01 | 680.40 | 769.66 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 17.04 | 0.00 |
April | 3370.34 | 21-APR-15:01 | 680.40 | 769.66 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 98.22 | 0.00 |
May | 3415.24 | 30-MAY-08:61 | 252.00 | 1209.46 | 792.74 | 0.00 | 0.00 | 0.00 | 0.00 | 44.01 | 0.00 |
June | 3432.35 | 15-JUN-08:61 | 252.00 | 1209.46 | 792.74 | 0.00 | 0.00 | 0.00 | 0.00 | 73.87 | 0.00 |
July | 3175.56 | 09-JUL-08:61 | 378.00 | 1539.31 | 1143.02 | 0.00 | 0.00 | 0.00 | 0.00 | 21.57 | 0.00 |
August | 3389.82 | 23-AUG-15:01 | 680.40 | 769.66 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 111.32 | 0.00 |
September | 3363.17 | 18-SEP-18:01 | 970.20 | 2446.40 | 903.35 | 0.00 | 0.00 | 0.00 | 0.00 | 84.12 | 0.00 |
October | 3361.38 | 01-OCT-15:01 | 378.00 | 907.09 | 534.64 | 0.00 | 0.00 | 0.00 | 0.00 | 105.41 | 0.00 |
November | 3265.24 | 11-NOV-09:01 | 378.00 | 1539.31 | 1143.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.18 |
December | 3068.81 | 09-DEC-09:01 | 378.00 | 1539.31 | 1143.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.66 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2270.82 | 216.00 | 769.66 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3432.35 | 970.20 | 2446.40 | 1143.02 | 0.00 | 0.00 | 0.00 | 0.00 | 111.32 | 123.99 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2019.50 | 12-JAN-21:10 | 2011.87 | 1140.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 116.35 |
February | 2223.02 | 21-FEB-17:20 | 1257.42 | 356.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.20 | 0.00 |
March | 2443.30 | 16-MAR-18:10 | 12322.72 | 7980.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.26 |
April | 2790.56 | 30-APR-10:35 | 1508.90 | 855.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.77 | 0.00 |
May | 2988.55 | 31-MAY-18:10 | 10562.33 | 6840.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 114.94 | 0.00 |
June | 3255.23 | 15-JUN-18:10 | 10562.33 | 6840.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 168.91 | 0.00 |
July | 3202.42 | 03-JUL-18:10 | 10562.33 | 6840.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 175.68 | 0.00 |
August | 3195.71 | 07-AUG-18:10 | 10562.33 | 6840.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 147.06 | 0.00 |
September | 3036.52 | 20-SEP-18:10 | 10562.33 | 6840.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 113.94 | 0.00 |
October | 2919.31 | 05-OCT-10:35 | 1005.94 | 712.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.59 | 0.00 |
November | 2532.30 | 10-NOV-11:35 | 1005.94 | 712.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.69 |
December | 1917.06 | 15-DEC-22:03 | 6790.07 | 2565.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.45 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 1917.06 | 1005.94 | 356.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3255.23 | 12322.72 | 7980.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 175.68 | 116.35 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4050.02 | 12-JAN-16:01 | 680.40 | 769.75 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.03 |
February | 4134.16 | 20-FEB-16:01 | 378.00 | 907.20 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 6.80 | 0.00 |
March | 4127.26 | 14-MAR-15:01 | 680.40 | 769.75 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 16.17 | 0.00 |
April | 4185.30 | 30-APR-15:01 | 378.00 | 907.20 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 78.51 | 0.00 |
May | 4206.83 | 20-MAY-15:01 | 378.00 | 907.20 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 98.97 | 0.00 |
June | 4203.83 | 15-JUN-15:02 | 583.20 | 659.78 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 157.99 | 0.00 |
July | 3706.06 | 26-JUL-08:61 | 252.00 | 1209.60 | 792.83 | 0.00 | 0.00 | 0.00 | 0.00 | 70.45 | 0.00 |
August | 4206.00 | 23-AUG-15:01 | 680.40 | 769.75 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 110.31 | 0.00 |
September | 4210.81 | 11-SEP-15:01 | 680.40 | 769.75 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 70.58 | 0.00 |
October | 4215.21 | 01-OCT-15:01 | 378.00 | 907.20 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 103.18 | 0.00 |
November | 4141.38 | 09-NOV-16:01 | 680.40 | 769.75 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 7.93 | 0.00 |
December | 3980.47 | 17-DEC-16:01 | 378.00 | 907.20 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.60 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3706.06 | 252.00 | 659.78 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4215.21 | 680.40 | 1209.60 | 792.83 | 0.00 | 0.00 | 0.00 | 0.00 | 157.99 | 75.60 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3905.56 | 12-JAN-16:01 | 680.40 | 769.66 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.33 |
February | 4041.96 | 20-FEB-16:01 | 378.00 | 907.09 | 534.64 | 0.00 | 0.00 | 0.00 | 0.00 | 8.51 | 0.00 |
March | 4036.89 | 16-MAR-15:01 | 680.40 | 769.66 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 4.18 | 0.00 |
April | 4142.67 | 30-APR-15:01 | 378.00 | 907.09 | 534.64 | 0.00 | 0.00 | 0.00 | 0.00 | 78.77 | 0.00 |
May | 4171.66 | 20-MAY-15:01 | 378.00 | 907.09 | 534.64 | 0.00 | 0.00 | 0.00 | 0.00 | 99.02 | 0.00 |
June | 4183.35 | 15-JUN-18:02 | 831.60 | 2096.92 | 774.30 | 0.00 | 0.00 | 0.00 | 0.00 | 135.14 | 0.00 |
July | 3690.46 | 26-JUL-08:61 | 252.00 | 1209.46 | 792.74 | 0.00 | 0.00 | 0.00 | 0.00 | 70.33 | 0.00 |
August | 4159.28 | 23-AUG-15:01 | 680.40 | 769.66 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 110.67 | 0.00 |
September | 4147.11 | 11-SEP-15:01 | 680.40 | 769.66 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 71.43 | 0.00 |
October | 4136.31 | 01-OCT-15:01 | 378.00 | 907.09 | 534.64 | 0.00 | 0.00 | 0.00 | 0.00 | 104.43 | 0.00 |
November | 4052.63 | 09-NOV-16:01 | 680.40 | 769.66 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 9.53 | 0.00 |
December | 3451.10 | 16-DEC-16:02 | 324.00 | 777.51 | 458.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3451.10 | 252.00 | 769.66 | 458.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4183.35 | 831.60 | 2096.92 | 792.74 | 0.00 | 0.00 | 0.00 | 0.00 | 135.14 | 74.09 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2144.90 | 12-JAN-16:01 | 680.40 | 483.89 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.95 |
February | 2163.14 | 20-FEB-16:01 | 378.00 | 570.30 | 523.86 | 0.00 | 0.00 | 0.00 | 0.00 | 2.34 | 0.00 |
March | 2163.13 | 14-MAR-15:01 | 680.40 | 483.89 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 7.04 | 0.00 |
April | 2159.09 | 03-APR-15:01 | 680.40 | 483.89 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 22.76 | 0.00 |
May | 2157.59 | 20-MAY-15:01 | 378.00 | 570.30 | 523.86 | 0.00 | 0.00 | 0.00 | 0.00 | 50.71 | 0.00 |
June | 2155.36 | 12-JUN-15:01 | 680.40 | 483.89 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 60.06 | 0.00 |
July | 1981.99 | 23-JUL-18:02 | 702.00 | 1481.29 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 45.38 | 0.00 |
August | 1972.67 | 31-AUG-18:01 | 970.20 | 1538.07 | 885.15 | 0.00 | 0.00 | 0.00 | 0.00 | 26.49 | 0.00 |
September | 2180.20 | 30-SEP-15:01 | 378.00 | 570.30 | 523.86 | 0.00 | 0.00 | 0.00 | 0.00 | 29.66 | 0.00 |
October | 2196.57 | 01-OCT-15:01 | 378.00 | 570.30 | 523.86 | 0.00 | 0.00 | 0.00 | 0.00 | 51.92 | 0.00 |
November | 2171.97 | 09-NOV-16:01 | 680.40 | 483.89 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 2.79 | 0.00 |
December | 2113.72 | 30-DEC-16:01 | 378.00 | 570.30 | 523.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.12 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1972.67 | 378.00 | 483.89 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2196.57 | 970.20 | 1538.07 | 885.15 | 0.00 | 0.00 | 0.00 | 0.00 | 60.06 | 60.12 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 19070.69 | 03-JAN-22:20 | 26988.77 | 2548.93 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 282.64 |
February | 19607.35 | 07-FEB-23:00 | 26988.77 | 2548.93 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 189.15 |
March | 20039.51 | 15-MAR-22:00 | 26988.77 | 2548.93 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.52 |
April | 22065.71 | 19-APR-18:10 | 146938.85 | 23790.00 | 47235.32 | 0.00 | 0.00 | 0.00 | 0.00 | 209.56 | 0.00 |
May | 23213.15 | 31-MAY-18:10 | 125947.58 | 20391.43 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 230.46 | 0.00 |
June | 24499.85 | 15-JUN-18:10 | 125947.58 | 20391.43 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 346.45 | 0.00 |
July | 24280.63 | 03-JUL-18:10 | 125947.58 | 20391.43 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 358.55 | 0.00 |
August | 23987.51 | 07-AUG-18:10 | 125947.58 | 20391.43 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 303.07 | 0.00 |
September | 22615.40 | 20-SEP-18:10 | 125947.58 | 20391.43 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 237.14 | 0.00 |
October | 21917.29 | 05-OCT-18:10 | 146938.85 | 23790.00 | 47235.32 | 0.00 | 0.00 | 0.00 | 0.00 | 141.46 | 0.00 |
November | 19951.85 | 09-NOV-22:20 | 26988.77 | 2548.93 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 123.53 |
December | 19120.60 | 15-DEC-23:00 | 26988.77 | 2548.93 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 233.54 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 19070.69 | 26988.77 | 2548.93 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 24499.85 | 146938.85 | 23790.00 | 47235.32 | 0.00 | 0.00 | 0.00 | 0.00 | 358.55 | 282.64 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 20251.88 | 03-JAN-22:10 | 80966.30 | 7646.79 | 20243.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 274.83 |
February | 20815.43 | 07-FEB-23:00 | 26988.77 | 2548.93 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 191.52 |
March | 21290.66 | 22-MAR-18:10 | 125947.58 | 20391.43 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.82 |
April | 23417.60 | 19-APR-18:10 | 146938.85 | 23790.00 | 47235.32 | 0.00 | 0.00 | 0.00 | 0.00 | 207.07 | 0.00 |
May | 24608.28 | 31-MAY-18:10 | 125947.58 | 20391.43 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 228.08 | 0.00 |
June | 25884.23 | 15-JUN-18:10 | 125947.58 | 20391.43 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 344.73 | 0.00 |
July | 25630.03 | 03-JUL-18:10 | 125947.58 | 20391.43 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 357.06 | 0.00 |
August | 25318.51 | 07-AUG-18:10 | 125947.58 | 20391.43 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 301.61 | 0.00 |
September | 23921.91 | 20-SEP-18:10 | 125947.58 | 20391.43 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 235.30 | 0.00 |
October | 23218.87 | 05-OCT-18:10 | 146938.85 | 23790.00 | 47235.32 | 0.00 | 0.00 | 0.00 | 0.00 | 139.34 | 0.00 |
November | 21178.26 | 09-NOV-22:10 | 80966.30 | 7646.79 | 20243.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 116.10 |
December | 20297.43 | 15-DEC-23:00 | 26988.77 | 2548.93 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 235.88 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 20251.88 | 26988.77 | 2548.93 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 25884.23 | 146938.85 | 23790.00 | 47235.32 | 0.00 | 0.00 | 0.00 | 0.00 | 357.06 | 274.83 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 26380.58 | 01-JAN-11:50 | 800.57 | 340.26 | 15112.11 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 240.36 |
February | 27731.00 | 20-FEB-11:50 | 800.57 | 340.26 | 15112.11 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 79.43 |
March | 27865.57 | 19-MAR-10:50 | 800.57 | 340.26 | 15112.11 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 118.93 |
April | 29809.53 | 30-APR-10:40 | 1601.14 | 680.52 | 30224.21 | 37488.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.62 |
May | 30087.43 | 21-MAY-10:50 | 800.57 | 340.26 | 15112.11 | 18744.03 | 0.00 | 0.00 | 0.00 | 135.60 | 0.00 |
June | 30779.39 | 18-JUN-10:50 | 800.57 | 340.26 | 15112.11 | 18744.03 | 0.00 | 0.00 | 0.00 | 193.89 | 0.00 |
July | 30956.25 | 02-JUL-10:40 | 1601.14 | 680.52 | 30224.21 | 37488.05 | 0.00 | 0.00 | 0.00 | 184.85 | 0.00 |
August | 30809.68 | 06-AUG-10:40 | 1601.14 | 680.52 | 30224.21 | 37488.05 | 0.00 | 0.00 | 0.00 | 172.76 | 0.00 |
September | 30236.51 | 17-SEP-10:40 | 1601.14 | 680.52 | 30224.21 | 37488.05 | 0.00 | 0.00 | 0.00 | 123.27 | 0.00 |
October | 29612.84 | 05-OCT-10:50 | 533.71 | 283.55 | 15112.11 | 18744.03 | 0.00 | 0.00 | 0.00 | 83.11 | 0.00 |
November | 27587.58 | 10-NOV-11:50 | 533.71 | 283.55 | 15112.11 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 71.82 |
December | 26419.78 | 10-DEC-11:50 | 800.57 | 340.26 | 15112.11 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 184.93 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 26380.58 | 533.71 | 283.55 | 15112.11 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 30956.25 | 1601.14 | 680.52 | 30224.21 | 37488.05 | 0.00 | 0.00 | 0.00 | 193.89 | 240.36 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4769.52 | 12-JAN-14:30 | 532.32 | 377.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.56 |
February | 5042.60 | 22-FEB-13:00 | 532.32 | 377.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.05 |
March | 5530.53 | 14-MAR-15:50 | 1330.80 | 377.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.88 | 0.00 |
April | 6616.80 | 30-APR-10:35 | 1596.96 | 904.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.66 | 0.00 |
May | 7067.27 | 21-MAY-10:35 | 1596.96 | 904.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 182.77 | 0.00 |
June | 7698.13 | 17-JUN-17:13 | 4790.88 | 2714.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 308.76 | 0.00 |
July | 7803.58 | 03-JUL-10:35 | 1064.64 | 754.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 269.20 | 0.00 |
August | 7618.31 | 07-AUG-17:13 | 3992.40 | 2714.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 304.91 | 0.00 |
September | 7168.64 | 03-SEP-10:35 | 1596.96 | 904.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.02 | 0.00 |
October | 6950.49 | 05-OCT-10:35 | 1064.64 | 754.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 141.34 | 0.00 |
November | 5517.56 | 03-NOV-15:50 | 1330.80 | 377.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.89 | 0.00 |
December | 3806.48 | 16-DEC-13:40 | 798.48 | 377.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 153.51 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 3806.48 | 532.32 | 377.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7803.58 | 4790.88 | 2714.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 308.76 | 153.51 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.593837E+12 | 364668.70 | 03-JAN-20:19 | 0.605208E+12 | 438449.10 | 15-JAN-17:40 |
February | 0.563166E+12 | 402264.60 | 06-FEB-20:10 | 0.530227E+12 | 418140.36 | 02-FEB-17:00 |
March | 0.649162E+12 | 431822.64 | 14-MAR-18:10 | 0.562212E+12 | 417357.35 | 01-MAR-18:49 |
April | 0.744868E+12 | 494438.02 | 19-APR-19:10 | 0.485892E+12 | 392706.64 | 10-APR-17:00 |
May | 0.869859E+12 | 526758.56 | 19-MAY-19:10 | 0.467047E+12 | 381032.59 | 07-MAY-17:30 |
June | 0.935561E+12 | 570236.28 | 05-JUN-19:10 | 0.429508E+12 | 355246.73 | 04-JUN-16:10 |
July | 0.102281E+13 | 561057.63 | 25-JUL-19:10 | 0.426603E+12 | 352573.67 | 09-JUL-16:19 |
August | 0.960188E+12 | 549445.33 | 04-AUG-19:10 | 0.421637E+12 | 348345.42 | 20-AUG-16:00 |
September | 0.878788E+12 | 511671.41 | 22-SEP-19:10 | 0.411730E+12 | 347325.69 | 04-SEP-16:49 |
October | 0.763599E+12 | 511672.60 | 04-OCT-19:10 | 0.457615E+12 | 370254.31 | 15-OCT-16:00 |
November | 0.617259E+12 | 422211.34 | 09-NOV-20:00 | 0.519277E+12 | 428661.83 | 27-NOV-17:40 |
December | 0.589177E+12 | 360842.04 | 15-DEC-20:10 | 0.614229E+12 | 467500.63 | 26-DEC-17:19 |
Annual Sum or Average | 0.918828E+13 | 0.593118E+13 | ||||
Minimum of Months | 0.563166E+12 | 360842.04 | 0.411730E+12 | 347325.69 | ||
Maximum of Months | 0.102281E+13 | 570236.28 | 0.614229E+12 | 467500.63 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [J] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.997859E+11 | 0.257766E+11 | 0.148746E+12 | 0.577258E+11 | 0.167485E+12 | 0.112232E+11 | 0.00 | 0.209948E+11 | 0.00 | 0.00 | 0.481696E+11 | 0.770782E+10 | 0.00 |
February | 0.901073E+11 | 0.220513E+11 | 0.134341E+12 | 0.521396E+11 | 0.151388E+12 | 0.131565E+11 | 0.00 | 0.444274E+11 | 0.00 | 0.00 | 0.429734E+11 | 0.696494E+10 | 0.00 |
March | 0.995228E+11 | 0.226622E+11 | 0.148757E+12 | 0.577286E+11 | 0.167230E+12 | 0.169368E+11 | 0.00 | 0.752798E+11 | 0.00 | 0.00 | 0.471151E+11 | 0.770634E+10 | 0.00 |
April | 0.965474E+11 | 0.201687E+11 | 0.143913E+12 | 0.558635E+11 | 0.166397E+12 | 0.228219E+11 | 0.00 | 0.179566E+12 | 0.00 | 0.00 | 0.460731E+11 | 0.746749E+10 | 0.00 |
May | 0.996636E+11 | 0.193275E+11 | 0.148757E+12 | 0.577273E+11 | 0.177247E+12 | 0.267390E+11 | 0.00 | 0.278388E+12 | 0.00 | 0.00 | 0.479846E+11 | 0.770691E+10 | 0.00 |
June | 0.963626E+11 | 0.179455E+11 | 0.143963E+12 | 0.558662E+11 | 0.177209E+12 | 0.279264E+11 | 0.00 | 0.355970E+12 | 0.00 | 0.00 | 0.466965E+11 | 0.745903E+10 | 0.00 |
July | 0.998551E+11 | 0.188768E+11 | 0.148708E+12 | 0.577246E+11 | 0.182968E+12 | 0.297785E+11 | 0.00 | 0.422527E+12 | 0.00 | 0.00 | 0.482531E+11 | 0.771469E+10 | 0.00 |
August | 0.995413E+11 | 0.201687E+11 | 0.148768E+12 | 0.577287E+11 | 0.181010E+12 | 0.290189E+11 | 0.00 | 0.361581E+12 | 0.00 | 0.00 | 0.482494E+11 | 0.770671E+10 | 0.00 |
September | 0.965794E+11 | 0.211501E+11 | 0.143924E+12 | 0.558636E+11 | 0.173202E+12 | 0.270992E+11 | 0.00 | 0.300733E+12 | 0.00 | 0.00 | 0.465730E+11 | 0.746864E+10 | 0.00 |
October | 0.997606E+11 | 0.236937E+11 | 0.148735E+12 | 0.577257E+11 | 0.173246E+12 | 0.237453E+11 | 0.00 | 0.175237E+12 | 0.00 | 0.00 | 0.474067E+11 | 0.770589E+10 | 0.00 |
November | 0.965244E+11 | 0.244648E+11 | 0.143978E+12 | 0.558644E+11 | 0.163241E+12 | 0.148856E+11 | 0.00 | 0.586973E+11 | 0.00 | 0.00 | 0.461197E+11 | 0.745204E+10 | 0.00 |
December | 0.998619E+11 | 0.261572E+11 | 0.148708E+12 | 0.577246E+11 | 0.168222E+12 | 0.103367E+11 | 0.00 | 0.161009E+11 | 0.00 | 0.00 | 0.481468E+11 | 0.771610E+10 | 0.00 |
Annual Sum or Average | 0.117411E+13 | 0.262443E+12 | 0.175130E+13 | 0.679683E+12 | 0.204885E+13 | 0.253668E+12 | 0.00 | 0.228950E+13 | 0.00 | 0.00 | 0.563761E+12 | 0.907766E+11 | 0.00 |
Minimum of Months | 0.901073E+11 | 0.179455E+11 | 0.134341E+12 | 0.521396E+11 | 0.151388E+12 | 0.103367E+11 | 0.00 | 0.161009E+11 | 0.00 | 0.00 | 0.429734E+11 | 0.696494E+10 | 0.00 |
Maximum of Months | 0.998619E+11 | 0.261572E+11 | 0.148768E+12 | 0.577287E+11 | 0.182968E+12 | 0.297785E+11 | 0.00 | 0.422527E+12 | 0.00 | 0.00 | 0.482531E+11 | 0.771610E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.151918E+12 | 0.00 | 0.180679E+12 | 0.00 | 0.272610E+12 | 0.00 | 0.00 |
February | 0.137204E+12 | 0.00 | 0.146903E+12 | 0.00 | 0.246120E+12 | 0.00 | 0.00 |
March | 0.152024E+12 | 0.00 | 0.143946E+12 | 0.00 | 0.266243E+12 | 0.00 | 0.00 |
April | 0.146956E+12 | 0.00 | 0.920208E+11 | 0.00 | 0.246916E+12 | 0.00 | 0.00 |
May | 0.151978E+12 | 0.00 | 0.727320E+11 | 0.00 | 0.242336E+12 | 0.00 | 0.00 |
June | 0.147114E+12 | 0.00 | 0.586329E+11 | 0.00 | 0.223761E+12 | 0.00 | 0.00 |
July | 0.151820E+12 | 0.00 | 0.500492E+11 | 0.00 | 0.224733E+12 | 0.00 | 0.00 |
August | 0.152039E+12 | 0.00 | 0.447590E+11 | 0.00 | 0.224839E+12 | 0.00 | 0.00 |
September | 0.146971E+12 | 0.00 | 0.409287E+11 | 0.00 | 0.223831E+12 | 0.00 | 0.00 |
October | 0.151903E+12 | 0.00 | 0.632874E+11 | 0.00 | 0.242424E+12 | 0.00 | 0.00 |
November | 0.147091E+12 | 0.00 | 0.125142E+12 | 0.00 | 0.247043E+12 | 0.00 | 0.00 |
December | 0.151820E+12 | 0.00 | 0.196115E+12 | 0.00 | 0.266293E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.178884E+13 | 0.00 | 0.121520E+13 | 0.00 | 0.292715E+13 | 0.00 | 0.00 |
Minimum of Months | 0.137204E+12 | 0.00 | 0.409287E+11 | 0.00 | 0.223761E+12 | 0.00 | 0.00 |
Maximum of Months | 0.152039E+12 | 0.00 | 0.196115E+12 | 0.00 | 0.272610E+12 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 93091.76 | 02-JAN-20:10 | 16690.39 | 01-JAN-00:10 | 89674.66 | 02-JAN-07:10 | 40537.60 | 02-JAN-07:19 | 73400.67 | 27-JAN-09:09 | 9414.08 | 03-JAN-14:39 | 0.00 | 01-JAN-00:10 |
February | 93091.76 | 01-FEB-20:10 | 16690.39 | 01-FEB-00:10 | 89674.66 | 01-FEB-07:10 | 40537.60 | 01-FEB-07:19 | 72537.27 | 20-FEB-16:10 | 10621.74 | 20-FEB-16:30 | 0.00 | 01-FEB-00:10 |
March | 93091.76 | 01-MAR-20:10 | 16690.39 | 01-MAR-00:10 | 89674.66 | 01-MAR-07:10 | 40537.60 | 01-MAR-07:19 | 73100.41 | 16-MAR-15:09 | 10740.56 | 22-MAR-16:19 | 0.00 | 01-MAR-00:10 |
April | 93091.76 | 03-APR-19:10 | 16690.39 | 01-APR-00:10 | 89674.66 | 03-APR-06:10 | 40537.60 | 03-APR-06:19 | 81622.77 | 29-APR-15:20 | 11927.90 | 27-APR-10:39 | 0.00 | 01-APR-00:10 |
May | 93091.76 | 01-MAY-19:10 | 16690.39 | 01-MAY-00:10 | 89674.66 | 01-MAY-06:10 | 40537.60 | 01-MAY-06:19 | 86650.16 | 19-MAY-18:19 | 12552.66 | 19-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 93091.76 | 01-JUN-19:10 | 16690.39 | 01-JUN-00:10 | 89674.66 | 01-JUN-06:10 | 40537.60 | 01-JUN-06:19 | 87145.13 | 07-JUN-18:19 | 13002.53 | 21-JUN-16:40 | 0.00 | 01-JUN-00:10 |
July | 93091.76 | 03-JUL-19:10 | 16690.39 | 01-JUL-00:10 | 89674.66 | 03-JUL-06:10 | 40537.60 | 03-JUL-06:19 | 86735.41 | 02-JUL-18:19 | 12882.73 | 06-JUL-15:50 | 0.00 | 01-JUL-00:10 |
August | 93091.76 | 01-AUG-19:10 | 16690.39 | 01-AUG-00:10 | 89674.66 | 01-AUG-06:10 | 40537.60 | 01-AUG-06:19 | 87624.42 | 27-AUG-18:19 | 12510.07 | 23-AUG-18:30 | 0.00 | 01-AUG-00:10 |
September | 93091.76 | 01-SEP-19:10 | 16690.39 | 01-SEP-00:10 | 89674.66 | 01-SEP-06:10 | 40537.60 | 01-SEP-06:19 | 85020.94 | 17-SEP-15:20 | 12541.67 | 19-SEP-16:00 | 0.00 | 01-SEP-00:10 |
October | 93091.76 | 02-OCT-19:10 | 16690.39 | 01-OCT-00:10 | 89674.66 | 02-OCT-06:10 | 40537.60 | 02-OCT-06:19 | 81668.23 | 05-OCT-15:20 | 11976.42 | 01-OCT-10:39 | 0.00 | 01-OCT-00:10 |
November | 93091.76 | 01-NOV-19:10 | 16690.39 | 01-NOV-00:10 | 89674.66 | 01-NOV-06:10 | 40537.60 | 01-NOV-06:19 | 74502.30 | 03-NOV-15:09 | 11367.59 | 03-NOV-16:19 | 0.00 | 01-NOV-00:10 |
December | 93091.76 | 01-DEC-20:10 | 16690.39 | 01-DEC-00:10 | 89674.66 | 01-DEC-07:10 | 40537.60 | 01-DEC-07:19 | 76891.68 | 26-DEC-16:10 | 8700.68 | 09-DEC-11:39 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 93091.76 | 16690.39 | 89674.66 | 40537.60 | 72537.27 | 8700.68 | 0.00 | |||||||
Maximum of Months | 93091.76 | 16690.39 | 89674.66 | 40537.60 | 87624.42 | 13002.53 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY {Maximum} [W] | HEATRECOVERY:ELECTRICITY {TIMESTAMP} | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 83237.47 | 03-JAN-14:00 | 0.00 | 0.00 | 18015.63 | 01-JAN-08:09 | 4738.97 | 02-JAN-07:40 | 0.00 |
February | 109998.80 | 20-FEB-16:10 | 0.00 | 0.00 | 18015.63 | 01-FEB-00:10 | 4739.05 | 07-FEB-07:10 | 0.00 |
March | 114217.20 | 21-MAR-15:09 | 0.00 | 0.00 | 18015.63 | 01-MAR-00:10 | 4739.27 | 28-MAR-06:10 | 0.00 |
April | 175066.99 | 21-APR-15:09 | 0.00 | 0.00 | 18015.63 | 01-APR-07:10 | 4738.71 | 10-APR-06:30 | 0.00 |
May | 204587.12 | 19-MAY-15:20 | 0.00 | 0.00 | 18015.63 | 01-MAY-07:10 | 4739.21 | 31-MAY-06:10 | 0.00 |
June | 247961.71 | 14-JUN-18:10 | 0.00 | 0.00 | 18015.63 | 01-JUN-07:19 | 4738.66 | 20-JUN-06:10 | 0.00 |
July | 247848.57 | 26-JUL-15:20 | 0.00 | 0.00 | 18015.63 | 01-JUL-10:20 | 4738.75 | 03-JUL-18:10 | 0.00 |
August | 231520.94 | 07-AUG-16:19 | 0.00 | 0.00 | 18015.63 | 01-AUG-05:10 | 4738.76 | 29-AUG-06:10 | 0.00 |
September | 201133.57 | 20-SEP-15:20 | 0.00 | 0.00 | 18015.63 | 01-SEP-05:10 | 4738.92 | 19-SEP-06:10 | 0.00 |
October | 192295.32 | 04-OCT-15:20 | 0.00 | 0.00 | 18015.63 | 01-OCT-07:19 | 4739.02 | 11-OCT-06:10 | 0.00 |
November | 113466.06 | 03-NOV-15:00 | 0.00 | 0.00 | 18015.63 | 01-NOV-15:09 | 4739.21 | 21-NOV-07:10 | 0.00 |
December | 66113.46 | 23-DEC-14:00 | 0.00 | 0.00 | 18015.63 | 01-DEC-00:10 | 4738.60 | 18-DEC-07:00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 66113.46 | 0.00 | 0.00 | 18015.63 | 4738.60 | 0.00 | |||
Maximum of Months | 247961.71 | 0.00 | 0.00 | 18015.63 | 4739.27 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 364668.70 | 03-JAN-20:19 | 93091.76 | 88971.67 | 16690.39 | 33025.38 | 65319.99 | 8168.19 | 0.00 | 35051.77 | 0.00 |
February | 402264.60 | 06-FEB-20:10 | 93091.76 | 88971.67 | 16690.39 | 33012.66 | 64704.76 | 9197.62 | 0.00 | 71983.27 | 0.00 |
March | 431822.64 | 14-MAR-18:10 | 82800.17 | 79617.06 | 16690.39 | 32686.23 | 71699.44 | 10466.48 | 0.00 | 112796.53 | 0.00 |
April | 494438.02 | 19-APR-19:10 | 93091.76 | 88971.67 | 16690.39 | 33012.66 | 72889.54 | 10977.64 | 0.00 | 154316.14 | 0.00 |
May | 526758.56 | 19-MAY-19:10 | 93091.76 | 88971.67 | 16690.39 | 33012.66 | 78710.18 | 11084.27 | 0.00 | 180974.91 | 0.00 |
June | 570236.28 | 05-JUN-19:10 | 93091.76 | 88971.67 | 16690.39 | 33012.66 | 78213.03 | 11289.13 | 0.00 | 224284.18 | 0.00 |
July | 561057.63 | 25-JUL-19:10 | 93091.76 | 88971.67 | 16690.39 | 33012.66 | 77907.72 | 11388.66 | 0.00 | 215759.11 | 0.00 |
August | 549445.33 | 04-AUG-19:10 | 93091.76 | 88971.67 | 16690.39 | 33012.66 | 77545.25 | 11414.11 | 0.00 | 204482.65 | 0.00 |
September | 511671.41 | 22-SEP-19:10 | 93091.76 | 88971.67 | 16690.39 | 33012.66 | 74381.77 | 11290.75 | 0.00 | 169762.01 | 0.00 |
October | 511672.60 | 04-OCT-19:10 | 93091.76 | 88971.67 | 16690.39 | 33012.66 | 73553.29 | 11328.72 | 0.00 | 170450.36 | 0.00 |
November | 422211.34 | 09-NOV-20:00 | 93091.76 | 88971.67 | 16690.39 | 33025.38 | 67394.10 | 10055.49 | 0.00 | 88360.43 | 0.00 |
December | 360842.04 | 15-DEC-20:10 | 93091.76 | 88971.67 | 16690.39 | 33012.66 | 64593.55 | 7950.83 | 0.00 | 32416.19 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 360842.04 | 82800.17 | 79617.06 | 16690.39 | 32686.23 | 64593.55 | 7950.83 | 0.00 | 32416.19 | 0.00 | |
Maximum of Months | 570236.28 | 93091.76 | 88971.67 | 16690.39 | 33025.38 | 78710.18 | 11414.11 | 0.00 | 224284.18 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 104248.32 | 02-JAN-18:10 | 0.00 | 183744.30 | 27-JAN-07:19 | 0.00 | 251045.32 | 18-JAN-21:00 | 0.00 |
February | 104248.32 | 01-FEB-18:10 | 0.00 | 201630.34 | 03-FEB-07:10 | 0.00 | 251113.69 | 09-FEB-21:00 | 0.00 |
March | 104248.32 | 01-MAR-18:10 | 0.00 | 167591.07 | 02-MAR-09:09 | 0.00 | 249835.28 | 02-MAR-21:40 | 0.00 |
April | 104248.32 | 01-APR-17:10 | 0.00 | 115174.10 | 11-APR-10:39 | 0.00 | 248120.02 | 03-APR-20:00 | 0.00 |
May | 104248.32 | 01-MAY-17:10 | 0.00 | 96298.93 | 02-MAY-10:39 | 0.00 | 245809.75 | 04-MAY-20:49 | 0.00 |
June | 104248.32 | 01-JUN-17:10 | 0.00 | 86050.42 | 29-JUN-10:39 | 0.00 | 221707.07 | 01-JUN-19:10 | 0.00 |
July | 104248.32 | 01-JUL-17:10 | 0.00 | 91155.07 | 21-JUL-10:39 | 0.00 | 215426.47 | 03-JUL-20:19 | 0.00 |
August | 104248.32 | 01-AUG-17:10 | 0.00 | 89051.04 | 17-AUG-10:39 | 0.00 | 215591.47 | 31-AUG-20:49 | 0.00 |
September | 104248.32 | 01-SEP-17:10 | 0.00 | 84085.49 | 01-SEP-10:39 | 0.00 | 223409.05 | 30-SEP-21:40 | 0.00 |
October | 104248.32 | 02-OCT-17:10 | 0.00 | 93012.78 | 24-OCT-10:39 | 0.00 | 246067.24 | 31-OCT-20:19 | 0.00 |
November | 104248.32 | 01-NOV-17:10 | 0.00 | 151473.99 | 27-NOV-09:09 | 0.00 | 248267.69 | 30-NOV-21:49 | 0.00 |
December | 104248.32 | 01-DEC-18:10 | 0.00 | 197805.94 | 27-DEC-07:10 | 0.00 | 249772.14 | 28-DEC-21:19 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 104248.32 | 0.00 | 84085.49 | 0.00 | 215426.47 | 0.00 | |||
Maximum of Months | 104248.32 | 0.00 | 201630.34 | 0.00 | 251113.69 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.90 | 0.17 | 21.90 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.68 | 0.17 | 21.68 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.72 | 0.50 | 21.72 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.88 | 0.83 | 21.88 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 1.67 | 21.81 | 1.67 | 21.81 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.90 | 0.83 | 21.90 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.68 | 0.17 | 21.68 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.82 | 0.33 | 21.82 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.68 | 0.17 | 21.68 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.68 | 0.17 | 21.68 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.71 | 0.17 | 21.71 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 1.00 | 21.73 | 1.00 | 21.73 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.82 | 0.33 | 21.82 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.71 | 0.50 | 21.71 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 21.74 | 1.33 | 21.74 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.70 | 0.33 | 21.70 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 2.17 | 21.73 | 2.17 | 21.73 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 21.74 | 1.33 | 21.74 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.71 | 0.50 | 21.71 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.71 | 0.17 | 21.71 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.67 | 21.71 | 0.67 | 21.71 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.71 | 0.50 | 21.71 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.75 | 0.50 | 21.75 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.50 | 21.75 | 0.50 | 21.75 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.75 | 0.50 | 21.75 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.74 | 1.00 | 21.74 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 21.70 | 1.17 | 21.70 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.81 | 0.83 | 21.81 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 21.78 | 2.17 | 21.78 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 21.89 | 2.33 | 21.89 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.75 | 0.17 | 21.75 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 7.67 | 21.80 | 7.67 | 21.80 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 21.89 | 2.33 | 21.89 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.75 | 1.00 | 21.75 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 21.73 | 1.33 | 21.73 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.85 | 0.67 | 21.85 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 21.76 | 1.50 | 21.76 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.79 | 0.50 | 21.79 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 5.00 | 21.76 | 5.00 | 21.76 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 21.85 | 1.50 | 21.85 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.76 | 0.33 | 21.76 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.67 | 0.33 | 21.67 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.82 | 0.83 | 21.82 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 21.87 | 2.83 | 21.87 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 21.81 | 1.67 | 21.81 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.88 | 0.17 | 21.88 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 6.17 | 21.83 | 6.17 | 21.83 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 21.88 | 2.83 | 21.88 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.09 | 26.67 | 21.09 | 26.67 | 21.09 |
February | 672.00 | 21.02 | 116.50 | 21.02 | 116.50 | 21.01 |
March | 744.00 | 20.95 | 305.00 | 20.93 | 305.00 | 20.92 |
April | 720.00 | 20.94 | 230.83 | 20.93 | 230.83 | 20.93 |
May | 744.00 | 20.96 | 33.50 | 20.96 | 33.50 | 20.96 |
June | 720.00 | 20.97 | 6.83 | 20.97 | 6.83 | 20.96 |
July | 744.00 | 21.06 | 0.00 | 21.06 | 0.00 | 21.06 |
August | 744.00 | 21.20 | 0.00 | 21.20 | 0.00 | 21.20 |
September | 720.00 | 21.41 | 0.00 | 21.41 | 0.00 | 21.41 |
October | 744.00 | 21.49 | 0.00 | 21.49 | 0.00 | 21.49 |
November | 720.00 | 21.48 | 0.00 | 21.48 | 0.00 | 21.48 |
December | 744.00 | 21.28 | 9.00 | 21.28 | 9.00 | 21.27 |
Annual Sum or Average | 8760.00 | 21.15 | 728.33 | 21.14 | 728.33 | 21.12 |
Minimum of Months | 672.00 | 20.94 | 0.00 | 20.93 | 0.00 | 20.92 |
Maximum of Months | 744.00 | 21.49 | 305.00 | 21.49 | 305.00 | 21.49 |
Report: ComfortReportSimple55Monthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.09 | 169.67 | 21.07 | 169.67 | 21.06 |
February | 672.00 | 21.10 | 157.50 | 21.08 | 157.50 | 21.07 |
March | 744.00 | 21.05 | 163.33 | 21.04 | 163.33 | 21.04 |
April | 720.00 | 21.05 | 55.00 | 21.05 | 55.00 | 21.05 |
May | 744.00 | 21.04 | 6.50 | 21.04 | 6.50 | 21.04 |
June | 720.00 | 21.12 | 0.00 | 21.12 | 0.00 | 21.12 |
July | 744.00 | 21.11 | 0.00 | 21.11 | 0.00 | 21.11 |
August | 743.33 | 21.16 | 0.00 | 21.16 | 0.00 | 21.16 |
September | 673.17 | 21.20 | 7.67 | 21.22 | 0.00 | 21.22 |
October | 686.67 | 21.16 | 18.00 | 21.20 | 0.00 | 21.20 |
November | 709.50 | 21.19 | 122.00 | 21.16 | 122.00 | 21.14 |
December | 744.00 | 21.06 | 269.83 | 21.05 | 269.83 | 21.04 |
Annual Sum or Average | 8644.67 | 21.11 | 969.50 | 21.10 | 943.83 | 21.09 |
Minimum of Months | 672.00 | 21.04 | 0.00 | 21.04 | 0.00 | 21.04 |
Maximum of Months | 744.00 | 21.20 | 269.83 | 21.22 | 269.83 | 21.22 |
Report: ComfortReportSimple55Monthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.01 | 20.33 | 21.01 | 20.33 | 21.01 |
February | 672.00 | 21.02 | 0.00 | 21.02 | 0.00 | 21.02 |
March | 744.00 | 21.04 | 0.83 | 21.04 | 0.83 | 21.04 |
April | 720.00 | 21.10 | 0.00 | 21.10 | 0.00 | 21.10 |
May | 744.00 | 21.17 | 0.00 | 21.17 | 0.00 | 21.17 |
June | 720.00 | 21.27 | 0.00 | 21.27 | 0.00 | 21.27 |
July | 744.00 | 21.24 | 0.00 | 21.24 | 0.00 | 21.24 |
August | 744.00 | 21.23 | 0.00 | 21.23 | 0.00 | 21.23 |
September | 720.00 | 21.19 | 0.00 | 21.19 | 0.00 | 21.19 |
October | 744.00 | 21.10 | 0.00 | 21.10 | 0.00 | 21.10 |
November | 720.00 | 21.03 | 0.00 | 21.03 | 0.00 | 21.03 |
December | 744.00 | 21.01 | 32.33 | 21.01 | 32.33 | 21.01 |
Annual Sum or Average | 8760.00 | 21.12 | 53.50 | 21.12 | 53.50 | 21.12 |
Minimum of Months | 672.00 | 21.01 | 0.00 | 21.01 | 0.00 | 21.01 |
Maximum of Months | 744.00 | 21.27 | 32.33 | 21.27 | 32.33 | 21.27 |
Report: ComfortReportSimple55Monthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.00 | 221.50 | 21.00 | 221.50 | 21.00 |
February | 672.00 | 21.00 | 202.33 | 21.00 | 202.33 | 21.00 |
March | 744.00 | 21.00 | 136.17 | 21.00 | 136.17 | 21.00 |
April | 720.00 | 21.02 | 31.83 | 21.01 | 31.83 | 21.01 |
May | 744.00 | 21.06 | 0.00 | 21.06 | 0.00 | 21.06 |
June | 720.00 | 21.15 | 0.00 | 21.15 | 0.00 | 21.15 |
July | 744.00 | 21.13 | 0.00 | 21.13 | 0.00 | 21.13 |
August | 744.00 | 21.10 | 0.00 | 21.10 | 0.00 | 21.10 |
September | 720.00 | 21.05 | 0.00 | 21.05 | 0.00 | 21.05 |
October | 744.00 | 21.01 | 0.00 | 21.01 | 0.00 | 21.01 |
November | 720.00 | 21.00 | 107.50 | 21.00 | 107.50 | 21.00 |
December | 744.00 | 21.00 | 269.67 | 21.00 | 269.67 | 21.00 |
Annual Sum or Average | 8760.00 | 21.04 | 969.00 | 21.04 | 969.00 | 21.04 |
Minimum of Months | 672.00 | 21.00 | 0.00 | 21.00 | 0.00 | 21.00 |
Maximum of Months | 744.00 | 21.15 | 269.67 | 21.15 | 269.67 | 21.15 |
Report: ComfortReportSimple55Monthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.00 | 297.33 | 21.00 | 297.33 | 21.00 |
February | 672.00 | 21.00 | 343.00 | 21.00 | 343.00 | 21.00 |
March | 744.00 | 21.00 | 254.50 | 21.00 | 254.50 | 21.00 |
April | 720.00 | 21.00 | 102.50 | 21.00 | 102.50 | 21.00 |
May | 744.00 | 21.01 | 7.67 | 21.01 | 7.67 | 21.01 |
June | 720.00 | 21.08 | 0.00 | 21.08 | 0.00 | 21.08 |
July | 744.00 | 21.06 | 0.00 | 21.06 | 0.00 | 21.06 |
August | 744.00 | 21.04 | 0.00 | 21.04 | 0.00 | 21.04 |
September | 720.00 | 21.01 | 0.00 | 21.01 | 0.00 | 21.01 |
October | 744.00 | 21.00 | 1.83 | 21.00 | 1.83 | 21.00 |
November | 720.00 | 21.00 | 200.67 | 21.00 | 200.67 | 21.00 |
December | 744.00 | 21.00 | 426.50 | 21.00 | 426.50 | 21.00 |
Annual Sum or Average | 8760.00 | 21.02 | 1634.00 | 21.01 | 1634.00 | 21.01 |
Minimum of Months | 672.00 | 21.00 | 0.00 | 21.00 | 0.00 | 21.00 |
Maximum of Months | 744.00 | 21.08 | 426.50 | 21.08 | 426.50 | 21.08 |
Report: ComfortReportSimple55Monthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 550.00 | 21.38 | 152.50 | 21.72 | 77.00 | 21.92 |
February | 493.00 | 21.37 | 136.17 | 21.72 | 68.00 | 21.92 |
March | 545.50 | 21.40 | 149.67 | 21.75 | 82.67 | 21.95 |
April | 432.83 | 21.49 | 177.00 | 21.80 | 84.17 | 22.01 |
May | 304.50 | 21.79 | 290.67 | 21.88 | 103.00 | 22.09 |
June | 182.17 | 22.26 | 401.67 | 21.85 | 103.33 | 22.06 |
July | 112.17 | 23.08 | 653.00 | 21.65 | 111.33 | 21.83 |
August | 128.83 | 22.93 | 582.67 | 21.75 | 111.33 | 21.95 |
September | 152.50 | 22.57 | 515.67 | 21.77 | 106.00 | 21.97 |
October | 299.00 | 21.83 | 352.00 | 21.84 | 104.83 | 22.05 |
November | 490.83 | 21.44 | 162.83 | 21.78 | 81.83 | 21.98 |
December | 574.33 | 21.33 | 145.83 | 21.68 | 69.83 | 21.86 |
Annual Sum or Average | 4265.67 | 21.63 | 3719.67 | 21.76 | 1103.33 | 21.96 |
Minimum of Months | 112.17 | 21.33 | 136.17 | 21.65 | 68.00 | 21.83 |
Maximum of Months | 574.33 | 23.08 | 653.00 | 21.88 | 111.33 | 22.09 |
Report: ComfortReportSimple55Monthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 743.33 | 21.08 | 20.00 | 21.08 | 20.00 | 21.08 |
February | 672.00 | 21.10 | 16.50 | 21.10 | 16.50 | 21.10 |
March | 744.00 | 21.07 | 10.50 | 21.07 | 10.50 | 21.07 |
April | 720.00 | 21.16 | 0.00 | 21.16 | 0.00 | 21.16 |
May | 744.00 | 21.23 | 3.67 | 21.23 | 3.67 | 21.23 |
June | 720.00 | 21.37 | 25.67 | 21.38 | 25.67 | 21.39 |
July | 738.33 | 21.35 | 147.17 | 21.43 | 147.17 | 21.49 |
August | 741.67 | 21.38 | 115.00 | 21.44 | 114.83 | 21.48 |
September | 678.83 | 21.38 | 126.83 | 21.43 | 123.00 | 21.47 |
October | 683.00 | 21.30 | 52.00 | 21.34 | 32.67 | 21.36 |
November | 706.83 | 21.19 | 3.67 | 21.19 | 3.67 | 21.19 |
December | 744.00 | 21.06 | 43.50 | 21.06 | 43.50 | 21.06 |
Annual Sum or Average | 8636.00 | 21.22 | 564.50 | 21.25 | 541.17 | 21.27 |
Minimum of Months | 672.00 | 21.06 | 0.00 | 21.06 | 0.00 | 21.06 |
Maximum of Months | 744.00 | 21.38 | 147.17 | 21.44 | 147.17 | 21.49 |
Report: ComfortReportSimple55Monthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.06 | 0.00 | 21.06 | 0.00 | 21.06 |
February | 672.00 | 21.08 | 0.00 | 21.08 | 0.00 | 21.08 |
March | 744.00 | 21.12 | 0.00 | 21.12 | 0.00 | 21.12 |
April | 720.00 | 21.23 | 0.00 | 21.23 | 0.00 | 21.23 |
May | 744.00 | 21.33 | 2.33 | 21.33 | 2.33 | 21.33 |
June | 720.00 | 21.44 | 7.83 | 21.44 | 7.83 | 21.44 |
July | 744.00 | 21.42 | 67.00 | 21.45 | 67.00 | 21.48 |
August | 744.00 | 21.41 | 50.17 | 21.43 | 50.17 | 21.45 |
September | 720.00 | 21.35 | 70.50 | 21.39 | 70.50 | 21.42 |
October | 744.00 | 21.25 | 15.83 | 21.26 | 15.83 | 21.27 |
November | 720.00 | 21.11 | 0.00 | 21.11 | 0.00 | 21.11 |
December | 744.00 | 21.05 | 0.00 | 21.05 | 0.00 | 21.05 |
Annual Sum or Average | 8760.00 | 21.24 | 213.67 | 21.25 | 213.67 | 21.26 |
Minimum of Months | 672.00 | 21.05 | 0.00 | 21.05 | 0.00 | 21.05 |
Maximum of Months | 744.00 | 21.44 | 70.50 | 21.45 | 70.50 | 21.48 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.24 | 213.17 | 21.14 | 213.17 | 21.09 |
February | 672.00 | 21.34 | 164.33 | 21.27 | 164.33 | 21.22 |
March | 744.00 | 21.44 | 112.33 | 21.37 | 112.33 | 21.32 |
April | 708.83 | 21.59 | 17.67 | 21.57 | 17.67 | 21.56 |
May | 686.67 | 21.55 | 0.00 | 21.55 | 0.00 | 21.55 |
June | 632.50 | 21.51 | 6.50 | 21.53 | 0.00 | 21.53 |
July | 598.17 | 21.34 | 58.67 | 21.51 | 12.17 | 21.53 |
August | 617.33 | 21.39 | 34.17 | 21.47 | 6.00 | 21.47 |
September | 593.83 | 21.37 | 32.00 | 21.46 | 4.50 | 21.47 |
October | 691.50 | 21.49 | 12.67 | 21.52 | 3.17 | 21.52 |
November | 713.50 | 21.40 | 128.50 | 21.32 | 128.50 | 21.26 |
December | 744.00 | 21.19 | 320.83 | 21.10 | 320.83 | 21.05 |
Annual Sum or Average | 8146.33 | 21.40 | 1100.83 | 21.38 | 982.67 | 21.33 |
Minimum of Months | 593.83 | 21.19 | 0.00 | 21.10 | 0.00 | 21.05 |
Maximum of Months | 744.00 | 21.59 | 320.83 | 21.57 | 320.83 | 21.56 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.88 | 444.33 | 20.81 | 444.33 | 20.78 |
February | 672.00 | 21.05 | 323.67 | 20.98 | 323.67 | 20.94 |
March | 744.00 | 21.24 | 188.50 | 21.17 | 188.50 | 21.12 |
April | 715.50 | 21.54 | 28.67 | 21.52 | 28.67 | 21.50 |
May | 691.83 | 21.56 | 0.00 | 21.56 | 0.00 | 21.56 |
June | 635.67 | 21.52 | 7.33 | 21.54 | 0.00 | 21.54 |
July | 601.83 | 21.36 | 55.50 | 21.51 | 12.17 | 21.54 |
August | 638.00 | 21.44 | 24.00 | 21.49 | 6.33 | 21.49 |
September | 635.33 | 21.46 | 14.67 | 21.49 | 8.50 | 21.49 |
October | 727.50 | 21.46 | 7.67 | 21.46 | 6.50 | 21.46 |
November | 720.00 | 21.16 | 243.33 | 21.07 | 243.33 | 21.02 |
December | 744.00 | 20.82 | 599.50 | 20.78 | 599.50 | 20.77 |
Annual Sum or Average | 8269.67 | 21.28 | 1937.17 | 21.21 | 1861.50 | 21.14 |
Minimum of Months | 601.83 | 20.82 | 0.00 | 20.78 | 0.00 | 20.77 |
Maximum of Months | 744.00 | 21.56 | 599.50 | 21.56 | 599.50 | 21.56 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.06 | 216.17 | 21.03 | 216.17 | 21.01 |
February | 672.00 | 21.15 | 148.00 | 21.11 | 148.00 | 21.08 |
March | 744.00 | 21.25 | 59.17 | 21.23 | 59.17 | 21.22 |
April | 720.00 | 21.47 | 0.00 | 21.47 | 0.00 | 21.47 |
May | 744.00 | 21.61 | 0.00 | 21.61 | 0.00 | 21.61 |
June | 720.00 | 21.69 | 0.00 | 21.69 | 0.00 | 21.69 |
July | 744.00 | 21.70 | 7.67 | 21.71 | 7.67 | 21.72 |
August | 744.00 | 21.65 | 0.33 | 21.65 | 0.33 | 21.65 |
September | 720.00 | 21.60 | 1.67 | 21.60 | 1.67 | 21.60 |
October | 744.00 | 21.42 | 0.00 | 21.42 | 0.00 | 21.42 |
November | 720.00 | 21.17 | 76.17 | 21.15 | 76.17 | 21.14 |
December | 744.00 | 21.01 | 340.50 | 20.96 | 340.50 | 20.94 |
Annual Sum or Average | 8760.00 | 21.40 | 849.67 | 21.36 | 849.67 | 21.32 |
Minimum of Months | 672.00 | 21.01 | 0.00 | 20.96 | 0.00 | 20.94 |
Maximum of Months | 744.00 | 21.70 | 340.50 | 21.71 | 340.50 | 21.72 |
Report: ComfortReportSimple55Monthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.26 | 211.83 | 21.18 | 211.83 | 21.14 |
February | 672.00 | 21.43 | 132.67 | 21.37 | 132.67 | 21.33 |
March | 744.00 | 21.54 | 101.67 | 21.48 | 101.67 | 21.43 |
April | 711.50 | 21.69 | 14.83 | 21.68 | 14.83 | 21.67 |
May | 693.33 | 21.62 | 0.33 | 21.63 | 0.00 | 21.63 |
June | 598.00 | 21.43 | 3.17 | 21.44 | 0.00 | 21.44 |
July | 558.67 | 21.23 | 21.67 | 21.29 | 8.00 | 21.31 |
August | 580.00 | 21.29 | 11.00 | 21.31 | 6.17 | 21.31 |
September | 574.67 | 21.34 | 7.17 | 21.36 | 1.17 | 21.37 |
October | 685.00 | 21.51 | 5.33 | 21.51 | 5.00 | 21.50 |
November | 719.67 | 21.47 | 128.50 | 21.38 | 128.50 | 21.31 |
December | 744.00 | 21.20 | 313.83 | 21.13 | 313.83 | 21.08 |
Annual Sum or Average | 8024.83 | 21.42 | 952.00 | 21.38 | 923.67 | 21.35 |
Minimum of Months | 558.67 | 21.20 | 0.33 | 21.13 | 0.00 | 21.08 |
Maximum of Months | 744.00 | 21.69 | 313.83 | 21.68 | 313.83 | 21.67 |
Report: ComfortReportSimple55Monthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.88 | 463.17 | 20.83 | 463.17 | 20.81 |
February | 672.00 | 21.12 | 280.50 | 21.06 | 280.50 | 21.02 |
March | 744.00 | 21.36 | 154.50 | 21.29 | 154.50 | 21.25 |
April | 716.67 | 21.67 | 20.67 | 21.65 | 20.67 | 21.64 |
May | 696.00 | 21.63 | 0.33 | 21.63 | 0.00 | 21.63 |
June | 598.50 | 21.43 | 5.00 | 21.45 | 0.00 | 21.45 |
July | 558.17 | 21.22 | 23.17 | 21.30 | 8.00 | 21.32 |
August | 590.17 | 21.32 | 11.50 | 21.34 | 6.67 | 21.34 |
September | 612.50 | 21.45 | 7.17 | 21.47 | 4.00 | 21.47 |
October | 731.00 | 21.53 | 8.50 | 21.53 | 8.33 | 21.53 |
November | 720.00 | 21.14 | 216.17 | 21.08 | 216.17 | 21.04 |
December | 744.00 | 20.82 | 583.00 | 20.78 | 583.00 | 20.77 |
Annual Sum or Average | 8127.00 | 21.29 | 1773.67 | 21.22 | 1745.00 | 21.16 |
Minimum of Months | 558.17 | 20.82 | 0.33 | 20.78 | 0.00 | 20.77 |
Maximum of Months | 744.00 | 21.67 | 583.00 | 21.65 | 583.00 | 21.64 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.00 | 204.00 | 21.00 | 204.00 | 21.00 |
February | 672.00 | 21.01 | 182.67 | 21.00 | 182.67 | 21.00 |
March | 744.00 | 21.01 | 145.33 | 21.01 | 145.33 | 21.01 |
April | 720.00 | 21.14 | 54.17 | 21.13 | 54.17 | 21.12 |
May | 744.00 | 21.45 | 1.33 | 21.45 | 1.33 | 21.45 |
June | 720.00 | 21.90 | 0.00 | 21.90 | 0.00 | 21.90 |
July | 744.00 | 21.83 | 27.17 | 21.82 | 27.17 | 21.82 |
August | 744.00 | 21.76 | 0.00 | 21.76 | 0.00 | 21.76 |
September | 720.00 | 21.64 | 6.17 | 21.64 | 6.17 | 21.64 |
October | 744.00 | 21.23 | 0.00 | 21.23 | 0.00 | 21.23 |
November | 720.00 | 21.02 | 67.50 | 21.02 | 67.50 | 21.02 |
December | 744.00 | 21.00 | 214.67 | 21.00 | 214.67 | 21.00 |
Annual Sum or Average | 8760.00 | 21.33 | 903.00 | 21.30 | 903.00 | 21.28 |
Minimum of Months | 672.00 | 21.00 | 0.00 | 21.00 | 0.00 | 21.00 |
Maximum of Months | 744.00 | 21.90 | 214.67 | 21.90 | 214.67 | 21.90 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.15 | 359.83 | 21.04 | 359.83 | 20.99 |
February | 672.00 | 21.29 | 255.00 | 21.19 | 255.00 | 21.13 |
March | 744.00 | 21.41 | 193.67 | 21.31 | 193.67 | 21.25 |
April | 689.17 | 21.54 | 42.67 | 21.51 | 41.50 | 21.49 |
May | 652.00 | 21.47 | 15.33 | 21.51 | 0.00 | 21.51 |
June | 579.17 | 21.36 | 37.50 | 21.48 | 0.00 | 21.48 |
July | 568.17 | 21.26 | 121.83 | 21.61 | 15.00 | 21.62 |
August | 580.67 | 21.29 | 92.33 | 21.54 | 10.17 | 21.54 |
September | 564.33 | 21.29 | 98.50 | 21.56 | 13.67 | 21.57 |
October | 667.17 | 21.42 | 30.17 | 21.48 | 7.83 | 21.48 |
November | 711.33 | 21.35 | 199.00 | 21.24 | 198.67 | 21.17 |
December | 744.00 | 21.11 | 461.83 | 21.01 | 461.83 | 20.97 |
Annual Sum or Average | 7916.00 | 21.33 | 1907.67 | 21.33 | 1557.17 | 21.27 |
Minimum of Months | 564.33 | 21.11 | 15.33 | 21.01 | 0.00 | 20.97 |
Maximum of Months | 744.00 | 21.54 | 461.83 | 21.61 | 461.83 | 21.62 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.79 | 580.67 | 20.74 | 580.67 | 20.72 |
February | 672.00 | 20.99 | 406.17 | 20.91 | 406.17 | 20.87 |
March | 744.00 | 21.22 | 274.33 | 21.12 | 274.33 | 21.07 |
April | 701.17 | 21.52 | 49.50 | 21.49 | 49.50 | 21.46 |
May | 659.17 | 21.48 | 14.33 | 21.52 | 0.67 | 21.52 |
June | 582.17 | 21.37 | 36.00 | 21.49 | 0.00 | 21.49 |
July | 569.33 | 21.27 | 112.33 | 21.59 | 14.17 | 21.61 |
August | 592.33 | 21.32 | 72.50 | 21.51 | 10.17 | 21.51 |
September | 596.83 | 21.36 | 64.67 | 21.51 | 17.50 | 21.52 |
October | 710.67 | 21.43 | 20.67 | 21.44 | 13.83 | 21.43 |
November | 720.00 | 21.11 | 320.83 | 21.01 | 320.83 | 20.96 |
December | 744.00 | 20.73 | 693.67 | 20.71 | 693.67 | 20.70 |
Annual Sum or Average | 8035.67 | 21.20 | 2645.67 | 21.16 | 2381.50 | 21.09 |
Minimum of Months | 569.33 | 20.73 | 14.33 | 20.71 | 0.00 | 20.70 |
Maximum of Months | 744.00 | 21.52 | 693.67 | 21.59 | 693.67 | 21.61 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 729.17 | 21.47 | 97.83 | 21.41 | 97.83 | 21.35 |
February | 659.50 | 21.54 | 86.33 | 21.48 | 86.33 | 21.44 |
March | 744.00 | 21.57 | 89.17 | 21.51 | 89.17 | 21.46 |
April | 708.00 | 21.62 | 22.83 | 21.60 | 22.83 | 21.59 |
May | 707.17 | 21.61 | 0.00 | 21.61 | 0.00 | 21.61 |
June | 644.67 | 21.54 | 0.00 | 21.54 | 0.00 | 21.54 |
July | 597.00 | 21.34 | 19.67 | 21.38 | 10.83 | 21.40 |
August | 605.83 | 21.35 | 12.67 | 21.39 | 2.83 | 21.39 |
September | 571.83 | 21.31 | 73.50 | 21.53 | 4.33 | 21.54 |
October | 630.50 | 21.37 | 39.17 | 21.48 | 1.50 | 21.48 |
November | 666.00 | 21.42 | 71.67 | 21.39 | 68.83 | 21.35 |
December | 742.83 | 21.50 | 180.00 | 21.40 | 180.00 | 21.33 |
Annual Sum or Average | 8006.50 | 21.48 | 692.83 | 21.48 | 564.50 | 21.45 |
Minimum of Months | 571.83 | 21.31 | 0.00 | 21.38 | 0.00 | 21.33 |
Maximum of Months | 744.00 | 21.62 | 180.00 | 21.61 | 180.00 | 21.61 |
Report: ComfortReportSimple55Monthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.27 | 0.00 | 21.27 | 0.00 | 21.27 |
February | 672.00 | 21.31 | 0.00 | 21.31 | 0.00 | 21.31 |
March | 744.00 | 21.39 | 0.00 | 21.39 | 0.00 | 21.39 |
April | 718.17 | 21.57 | 0.00 | 21.57 | 0.00 | 21.57 |
May | 719.83 | 21.71 | 11.67 | 21.72 | 11.17 | 21.74 |
June | 620.00 | 21.77 | 68.00 | 21.87 | 40.50 | 21.91 |
July | 657.00 | 21.81 | 232.33 | 22.02 | 194.33 | 22.13 |
August | 675.50 | 21.75 | 165.83 | 21.91 | 146.00 | 22.00 |
September | 699.67 | 21.66 | 164.83 | 21.78 | 158.83 | 21.86 |
October | 736.17 | 21.51 | 45.00 | 21.56 | 43.50 | 21.59 |
November | 720.00 | 21.33 | 0.00 | 21.33 | 0.00 | 21.33 |
December | 744.00 | 21.23 | 0.00 | 21.23 | 0.00 | 21.23 |
Annual Sum or Average | 8450.33 | 21.52 | 687.67 | 21.60 | 594.33 | 21.65 |
Minimum of Months | 620.00 | 21.23 | 0.00 | 21.23 | 0.00 | 21.23 |
Maximum of Months | 744.00 | 21.81 | 232.33 | 22.02 | 194.33 | 22.13 |
Report: ComfortReportSimple55Monthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.30 | 0.00 | 21.30 | 0.00 | 21.30 |
February | 672.00 | 21.35 | 0.00 | 21.35 | 0.00 | 21.35 |
March | 744.00 | 21.44 | 0.00 | 21.44 | 0.00 | 21.44 |
April | 711.17 | 21.63 | 0.00 | 21.63 | 0.00 | 21.63 |
May | 686.50 | 21.74 | 22.83 | 21.77 | 9.00 | 21.79 |
June | 550.67 | 21.77 | 94.33 | 21.93 | 38.00 | 21.96 |
July | 586.67 | 21.84 | 257.67 | 22.10 | 184.67 | 22.20 |
August | 625.83 | 21.77 | 187.83 | 21.98 | 140.83 | 22.07 |
September | 675.00 | 21.70 | 169.83 | 21.84 | 153.00 | 21.91 |
October | 729.00 | 21.56 | 49.17 | 21.61 | 42.17 | 21.64 |
November | 720.00 | 21.37 | 0.00 | 21.37 | 0.00 | 21.37 |
December | 744.00 | 21.26 | 0.00 | 21.26 | 0.00 | 21.26 |
Annual Sum or Average | 8188.83 | 21.55 | 781.67 | 21.64 | 567.67 | 21.69 |
Minimum of Months | 550.67 | 21.26 | 0.00 | 21.26 | 0.00 | 21.26 |
Maximum of Months | 744.00 | 21.84 | 257.67 | 22.10 | 184.67 | 22.20 |
Report: ComfortReportSimple55Monthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 540.67 | 22.70 | 519.50 | 23.02 | 342.00 | 23.17 |
February | 515.83 | 22.81 | 475.00 | 23.12 | 338.67 | 23.28 |
March | 588.00 | 22.90 | 526.50 | 23.21 | 398.83 | 23.36 |
April | 601.67 | 23.13 | 530.33 | 23.39 | 443.33 | 23.53 |
May | 617.33 | 23.35 | 578.33 | 23.51 | 499.00 | 23.62 |
June | 539.50 | 23.74 | 612.33 | 23.63 | 506.33 | 23.72 |
July | 532.33 | 23.88 | 715.17 | 23.52 | 532.33 | 23.63 |
August | 536.67 | 23.81 | 676.33 | 23.56 | 525.83 | 23.65 |
September | 540.50 | 23.65 | 622.67 | 23.53 | 501.67 | 23.63 |
October | 593.83 | 23.24 | 579.17 | 23.37 | 475.00 | 23.49 |
November | 562.17 | 22.85 | 515.33 | 23.15 | 378.67 | 23.30 |
December | 520.67 | 22.63 | 514.67 | 22.98 | 314.83 | 23.14 |
Annual Sum or Average | 6689.17 | 23.22 | 6865.33 | 23.34 | 5256.50 | 23.48 |
Minimum of Months | 515.83 | 22.63 | 475.00 | 22.98 | 314.83 | 23.14 |
Maximum of Months | 617.33 | 23.88 | 715.17 | 23.63 | 532.33 | 23.72 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.00 | 244.17 | 21.00 | 244.17 | 21.00 |
February | 672.00 | 21.00 | 255.83 | 21.00 | 255.83 | 21.00 |
March | 744.00 | 21.00 | 208.17 | 21.00 | 208.17 | 21.00 |
April | 720.00 | 21.03 | 78.00 | 21.03 | 78.00 | 21.03 |
May | 744.00 | 21.10 | 11.67 | 21.10 | 11.67 | 21.10 |
June | 720.00 | 21.42 | 0.00 | 21.42 | 0.00 | 21.42 |
July | 744.00 | 21.38 | 0.00 | 21.38 | 0.00 | 21.38 |
August | 744.00 | 21.30 | 0.00 | 21.30 | 0.00 | 21.30 |
September | 720.00 | 21.18 | 0.00 | 21.18 | 0.00 | 21.18 |
October | 744.00 | 21.06 | 0.00 | 21.06 | 0.00 | 21.06 |
November | 720.00 | 21.00 | 164.67 | 21.00 | 164.67 | 21.00 |
December | 744.00 | 21.00 | 393.50 | 21.00 | 393.50 | 21.00 |
Annual Sum or Average | 8760.00 | 21.12 | 1356.00 | 21.11 | 1356.00 | 21.09 |
Minimum of Months | 672.00 | 21.00 | 0.00 | 21.00 | 0.00 | 21.00 |
Maximum of Months | 744.00 | 21.42 | 393.50 | 21.42 | 393.50 | 21.42 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT PEOPLE
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.09147 | 24.30796 | -0.4523 | 9.35966 |
February | 672.00000 | 21.02205 | 21.25327 | -0.5091 | 10.48377 |
March | 744.00000 | 20.94993 | 20.20812 | -0.5461 | 11.28493 |
April | 720.00000 | 20.94067 | 24.20740 | -0.5228 | 10.83063 |
May | 744.00000 | 20.95643 | 35.44579 | -1.6535 | 59.21950 |
June | 720.00000 | 20.96748 | 43.99070 | -1.5891 | 55.73653 |
July | 744.00000 | 21.05561 | 59.28584 | -1.4402 | 47.67899 |
August | 744.00000 | 21.19952 | 55.69429 | -1.3925 | 45.15873 |
September | 720.00000 | 21.40859 | 52.30954 | -1.3253 | 41.70326 |
October | 744.00000 | 21.48767 | 43.55234 | -0.2175 | 6.16003 |
November | 720.00000 | 21.48494 | 25.26539 | -0.3307 | 7.41430 |
December | 744.00000 | 21.28044 | 21.01728 | -0.4118 | 8.63860 |
Annual Sum or Average | 8760.00000 | 21.15430 | 35.65245 | -0.8680 | 26.23726 |
Minimum of Months | 672.00000 | 20.94067 | 20.20812 | -1.6535 | 6.16003 |
Maximum of Months | 744.00000 | 21.48767 | 59.28584 | -0.2175 | 59.21950 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_1_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.08597 | 23.74003 | -0.4454 | 9.71589 |
February | 672.00000 | 21.10154 | 20.63403 | -0.4420 | 9.62894 |
March | 744.00000 | 21.05003 | 19.55892 | -0.4516 | 9.61581 |
April | 720.00000 | 21.05192 | 23.50960 | -0.3804 | 8.40617 |
May | 744.00000 | 21.03671 | 34.72715 | -1.4281 | 47.13228 |
June | 720.00000 | 21.12426 | 43.12092 | -1.2984 | 40.32484 |
July | 744.00000 | 21.11407 | 59.07381 | -1.2074 | 35.77417 |
August | 744.00000 | 21.16385 | 55.50771 | -1.2151 | 36.30304 |
September | 720.00000 | 21.28079 | 52.41485 | -1.1909 | 35.70132 |
October | 744.00000 | 21.27993 | 43.63105 | -0.1778 | 6.59792 |
November | 720.00000 | 21.20758 | 25.12160 | -0.3665 | 8.76625 |
December | 744.00000 | 21.06349 | 20.68677 | -0.4833 | 10.38945 |
Annual Sum or Average | 8760.00000 | 21.12985 | 35.25329 | -0.7593 | 21.60809 |
Minimum of Months | 672.00000 | 21.03671 | 19.55892 | -1.4281 | 6.59792 |
Maximum of Months | 744.00000 | 21.28079 | 59.07381 | -0.1778 | 47.13228 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_2_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.01269 | 24.62156 | -0.4532 | 9.35552 |
February | 672.00000 | 21.01970 | 21.48947 | -0.4621 | 9.51942 |
March | 744.00000 | 21.03983 | 20.35535 | -0.4550 | 9.37414 |
April | 720.00000 | 21.09724 | 24.23620 | -0.3989 | 8.49004 |
May | 744.00000 | 21.16805 | 35.26522 | -1.4535 | 48.47127 |
June | 720.00000 | 21.26906 | 43.51864 | -1.3541 | 43.23972 |
July | 744.00000 | 21.24317 | 59.15419 | -1.2723 | 38.99824 |
August | 744.00000 | 21.22996 | 55.95556 | -1.2986 | 40.33651 |
September | 720.00000 | 21.18642 | 53.33449 | -1.3291 | 41.93655 |
October | 744.00000 | 21.10220 | 44.77351 | -0.2720 | 6.71960 |
November | 720.00000 | 21.03493 | 26.12087 | -0.4220 | 8.81730 |
December | 744.00000 | 21.00660 | 21.53711 | -0.4781 | 9.81213 |
Annual Sum or Average | 8760.00000 | 21.11797 | 35.97137 | -0.8061 | 23.00313 |
Minimum of Months | 672.00000 | 21.00660 | 20.35535 | -1.4535 | 6.71960 |
Maximum of Months | 744.00000 | 21.26906 | 59.15419 | -0.2720 | 48.47127 |
Report: OccupantComfortDataSummaryMonthly
For: LAUNDRY_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.42272 | 22.28409 | 0.22310 | 8.63341 |
February | 672.00000 | 21.42312 | 19.23562 | 0.21952 | 8.56980 |
March | 744.00000 | 21.42510 | 18.12181 | 0.22891 | 8.68980 |
April | 720.00000 | 21.39535 | 22.02038 | 0.27719 | 9.13345 |
May | 744.00000 | 21.38485 | 33.00992 | -0.4987 | 15.25044 |
June | 720.00000 | 21.37131 | 41.49303 | -0.4225 | 13.47079 |
July | 744.00000 | 21.35200 | 56.83143 | -0.3452 | 11.80797 |
August | 744.00000 | 21.37867 | 53.64860 | -0.3625 | 12.39819 |
September | 720.00000 | 21.37915 | 50.91968 | -0.3926 | 12.89039 |
October | 744.00000 | 21.39822 | 42.23340 | 0.38976 | 10.66482 |
November | 720.00000 | 21.42132 | 23.74849 | 0.25162 | 8.95413 |
December | 744.00000 | 21.42003 | 19.24331 | 0.19880 | 8.39461 |
Annual Sum or Average | 8760.00000 | 21.39751 | 33.67286 | -0.0208 | 10.75187 |
Minimum of Months | 672.00000 | 21.35200 | 18.12181 | -0.4987 | 8.39461 |
Maximum of Months | 744.00000 | 21.42510 | 56.83143 | 0.38976 | 15.25044 |
Report: OccupantComfortDataSummaryMonthly
For: CAFE_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.08244 | 26.39085 | -0.3475 | 7.97567 |
February | 672.00000 | 21.10142 | 23.28107 | -0.3452 | 7.91112 |
March | 744.00000 | 21.06982 | 22.19320 | -0.3559 | 7.91356 |
April | 720.00000 | 21.15716 | 26.03922 | -0.2754 | 6.90758 |
May | 744.00000 | 21.22895 | 37.03838 | -1.2699 | 38.96598 |
June | 720.00000 | 21.37047 | 45.17330 | -1.1285 | 32.12569 |
July | 744.00000 | 21.36154 | 60.60819 | -1.0375 | 27.96968 |
August | 744.00000 | 21.38591 | 57.33774 | -1.0488 | 28.49560 |
September | 720.00000 | 21.41246 | 54.51924 | -1.0483 | 28.78048 |
October | 744.00000 | 21.36495 | 46.01554 | -0.0755 | 5.78046 |
November | 720.00000 | 21.21147 | 27.75793 | -0.2716 | 7.27805 |
December | 744.00000 | 21.06103 | 23.34950 | -0.3833 | 8.48501 |
Annual Sum or Average | 8760.00000 | 21.23447 | 37.58218 | -0.6341 | 17.44501 |
Minimum of Months | 672.00000 | 21.06103 | 22.19320 | -1.2699 | 5.78046 |
Maximum of Months | 744.00000 | 21.41246 | 60.60819 | -0.0755 | 38.96598 |
Report: OccupantComfortDataSummaryMonthly
For: LOBBY_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.06344 | 26.05289 | -0.3994 | 8.41195 |
February | 672.00000 | 21.08357 | 22.91852 | -0.4053 | 8.51034 |
March | 744.00000 | 21.11821 | 21.78223 | -0.3991 | 8.40397 |
April | 720.00000 | 21.22542 | 25.58948 | -0.3333 | 7.52847 |
May | 744.00000 | 21.32741 | 36.48670 | -1.3545 | 43.29257 |
June | 720.00000 | 21.43825 | 44.61256 | -1.2470 | 37.89254 |
July | 744.00000 | 21.42241 | 59.99501 | -1.1608 | 33.64728 |
August | 744.00000 | 21.41030 | 56.86345 | -1.1866 | 34.86661 |
September | 720.00000 | 21.34954 | 54.30684 | -1.2225 | 36.61894 |
October | 744.00000 | 21.24896 | 45.89836 | -0.1965 | 6.03058 |
November | 720.00000 | 21.11496 | 27.50474 | -0.3611 | 7.86263 |
December | 744.00000 | 21.04772 | 22.99008 | -0.4262 | 8.84595 |
Annual Sum or Average | 8760.00000 | 21.23829 | 37.18975 | -0.7262 | 20.22968 |
Minimum of Months | 672.00000 | 21.04772 | 21.78223 | -1.3545 | 6.03058 |
Maximum of Months | 744.00000 | 21.43825 | 59.99501 | -0.1965 | 43.29257 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.23690 | 27.62346 | -0.4659 | 10.22334 |
February | 672.00000 | 21.34347 | 24.50994 | -0.4364 | 9.69681 |
March | 744.00000 | 21.43735 | 23.36572 | -0.3907 | 8.95853 |
April | 720.00000 | 21.61392 | 26.77437 | -0.2624 | 7.41543 |
May | 744.00000 | 21.68946 | 35.26326 | -1.2333 | 38.21449 |
June | 720.00000 | 21.73033 | 40.70284 | -1.1299 | 33.28081 |
July | 744.00000 | 21.73198 | 51.81354 | -1.0709 | 30.69165 |
August | 744.00000 | 21.71701 | 49.92010 | -1.1024 | 32.09561 |
September | 720.00000 | 21.71254 | 48.80460 | -1.1216 | 33.12072 |
October | 744.00000 | 21.62276 | 44.57508 | -0.1484 | 6.36346 |
November | 720.00000 | 21.42030 | 29.08235 | -0.3681 | 8.88536 |
December | 744.00000 | 21.19144 | 24.40330 | -0.5110 | 11.10294 |
Annual Sum or Average | 8760.00000 | 21.53798 | 35.65233 | -0.6884 | 19.23214 |
Minimum of Months | 672.00000 | 21.19144 | 23.36572 | -1.2333 | 6.36346 |
Maximum of Months | 744.00000 | 21.73198 | 51.81354 | -0.1484 | 38.21449 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.88444 | 28.10506 | -0.5918 | 12.72906 |
February | 672.00000 | 21.05160 | 24.85206 | -0.5449 | 11.68501 |
March | 744.00000 | 21.24418 | 23.60320 | -0.4632 | 10.02561 |
April | 720.00000 | 21.55290 | 26.87170 | -0.2924 | 7.65010 |
May | 744.00000 | 21.68006 | 35.28526 | -1.2416 | 38.56995 |
June | 720.00000 | 21.73269 | 40.67957 | -1.1277 | 33.16384 |
July | 744.00000 | 21.73312 | 51.85282 | -1.0715 | 30.69000 |
August | 744.00000 | 21.70951 | 50.20867 | -1.1171 | 32.65940 |
September | 720.00000 | 21.68432 | 49.57392 | -1.1635 | 34.82733 |
October | 744.00000 | 21.49964 | 45.39743 | -0.2102 | 6.58298 |
November | 720.00000 | 21.15718 | 29.49377 | -0.4771 | 10.40413 |
December | 744.00000 | 20.82222 | 24.85004 | -0.6419 | 13.99462 |
Annual Sum or Average | 8760.00000 | 21.39733 | 35.98028 | -0.7467 | 20.30505 |
Minimum of Months | 672.00000 | 20.82222 | 23.60320 | -1.2416 | 6.58298 |
Maximum of Months | 744.00000 | 21.73312 | 51.85282 | -0.2102 | 38.56995 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT19_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 0.00000 | ||||
Minimum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_4_MULT19_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.05966 | 26.75396 | -0.5157 | 10.72624 |
February | 672.00000 | 21.14587 | 23.54763 | -0.4996 | 10.38047 |
March | 744.00000 | 21.25138 | 22.44592 | -0.4614 | 9.57719 |
April | 720.00000 | 21.46832 | 25.87732 | -0.3539 | 7.99969 |
May | 744.00000 | 21.60726 | 34.57012 | -1.3613 | 44.02245 |
June | 720.00000 | 21.69077 | 40.25964 | -1.2681 | 39.38127 |
July | 744.00000 | 21.69538 | 52.15259 | -1.1972 | 36.03163 |
August | 744.00000 | 21.64928 | 49.96961 | -1.2431 | 38.11090 |
September | 720.00000 | 21.59768 | 49.09072 | -1.2886 | 40.31506 |
October | 744.00000 | 21.41548 | 44.03211 | -0.2657 | 6.76533 |
November | 720.00000 | 21.17395 | 28.32167 | -0.4598 | 9.56467 |
December | 744.00000 | 21.00785 | 23.54261 | -0.5556 | 11.60994 |
Annual Sum or Average | 8760.00000 | 21.39803 | 35.13230 | -0.7910 | 22.11131 |
Minimum of Months | 672.00000 | 21.00785 | 22.44592 | -1.3613 | 6.76533 |
Maximum of Months | 744.00000 | 21.69538 | 52.15259 | -0.2657 | 44.02245 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_5_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.25815 | 27.57862 | -0.4639 | 10.04868 |
February | 672.00000 | 21.42830 | 24.39954 | -0.4092 | 9.24548 |
March | 744.00000 | 21.54171 | 23.25527 | -0.3635 | 8.62725 |
April | 720.00000 | 21.70974 | 26.64570 | -0.2320 | 7.20315 |
May | 744.00000 | 21.74036 | 35.07551 | -1.2098 | 37.13654 |
June | 720.00000 | 21.75227 | 40.65066 | -1.1133 | 32.63559 |
July | 744.00000 | 21.74927 | 51.66964 | -1.0576 | 30.19763 |
August | 744.00000 | 21.73861 | 49.75837 | -1.0886 | 31.57083 |
September | 720.00000 | 21.74215 | 48.46666 | -1.1103 | 32.67618 |
October | 744.00000 | 21.65102 | 44.63139 | -0.1478 | 6.40980 |
November | 720.00000 | 21.46829 | 29.02077 | -0.3606 | 8.76393 |
December | 744.00000 | 21.20395 | 24.36444 | -0.5065 | 10.88232 |
Annual Sum or Average | 8760.00000 | 21.58231 | 35.54255 | -0.6737 | 18.84467 |
Minimum of Months | 672.00000 | 21.20395 | 23.25527 | -1.2098 | 6.40980 |
Maximum of Months | 744.00000 | 21.75227 | 51.66964 | -0.1478 | 37.13654 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_6_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.87683 | 28.07860 | -0.5960 | 12.70910 |
February | 672.00000 | 21.11846 | 24.73091 | -0.5205 | 11.06954 |
March | 744.00000 | 21.36042 | 23.45945 | -0.4338 | 9.46748 |
April | 720.00000 | 21.67645 | 26.70506 | -0.2564 | 7.33586 |
May | 744.00000 | 21.73945 | 35.09794 | -1.2157 | 37.37499 |
June | 720.00000 | 21.75315 | 40.66519 | -1.1115 | 32.53768 |
July | 744.00000 | 21.74955 | 51.76339 | -1.0583 | 30.20019 |
August | 744.00000 | 21.73535 | 50.01219 | -1.1021 | 32.08270 |
September | 720.00000 | 21.73404 | 48.94718 | -1.1475 | 34.17508 |
October | 744.00000 | 21.56475 | 45.22090 | -0.2038 | 6.58078 |
November | 720.00000 | 21.13773 | 29.50192 | -0.4826 | 10.33292 |
December | 744.00000 | 20.81642 | 24.81031 | -0.6407 | 13.94200 |
Annual Sum or Average | 8760.00000 | 21.43968 | 35.83225 | -0.7323 | 19.87525 |
Minimum of Months | 672.00000 | 20.81642 | 23.45945 | -1.2157 | 6.58078 |
Maximum of Months | 744.00000 | 21.75315 | 51.76339 | -0.2038 | 37.37499 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.15199 | 27.99619 | -0.5180 | 11.46959 |
February | 672.00000 | 21.29051 | 24.74951 | -0.4737 | 10.62198 |
March | 744.00000 | 21.40940 | 23.52746 | -0.4125 | 9.56873 |
April | 720.00000 | 21.61788 | 26.86498 | -0.2518 | 7.58386 |
May | 744.00000 | 21.69755 | 35.30806 | -1.1999 | 36.94414 |
June | 720.00000 | 21.73767 | 40.68105 | -1.0833 | 31.53894 |
July | 744.00000 | 21.73997 | 51.38045 | -1.0259 | 29.06246 |
August | 744.00000 | 21.72599 | 49.76044 | -1.0613 | 30.61255 |
September | 720.00000 | 21.71608 | 48.87165 | -1.0913 | 32.15635 |
October | 744.00000 | 21.61679 | 44.91902 | -0.1442 | 6.55601 |
November | 720.00000 | 21.37710 | 29.36386 | -0.3983 | 9.66067 |
December | 744.00000 | 21.10630 | 24.69150 | -0.5682 | 12.53236 |
Annual Sum or Average | 8760.00000 | 21.51639 | 35.75756 | -0.6872 | 19.08145 |
Minimum of Months | 672.00000 | 21.10630 | 23.52746 | -1.1999 | 6.55601 |
Maximum of Months | 744.00000 | 21.73997 | 51.38045 | -0.1442 | 36.94414 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.78756 | 28.50792 | -0.6497 | 14.33483 |
February | 672.00000 | 20.99283 | 25.10492 | -0.5866 | 12.83918 |
March | 744.00000 | 21.21889 | 23.76741 | -0.4869 | 10.69843 |
April | 720.00000 | 21.57072 | 26.94427 | -0.2797 | 7.78198 |
May | 744.00000 | 21.69180 | 35.32996 | -1.2072 | 37.23364 |
June | 720.00000 | 21.74022 | 40.66149 | -1.0810 | 31.41457 |
July | 744.00000 | 21.74131 | 51.39866 | -1.0265 | 29.05282 |
August | 744.00000 | 21.72125 | 50.02860 | -1.0753 | 31.11335 |
September | 720.00000 | 21.69360 | 49.59931 | -1.1327 | 33.75412 |
October | 744.00000 | 21.51304 | 45.74500 | -0.2044 | 6.74634 |
November | 720.00000 | 21.11016 | 29.79038 | -0.5129 | 11.34488 |
December | 744.00000 | 20.72768 | 25.15994 | -0.7038 | 15.81296 |
Annual Sum or Average | 8760.00000 | 21.37723 | 36.08456 | -0.7468 | 20.22774 |
Minimum of Months | 672.00000 | 20.72768 | 23.76741 | -1.2072 | 6.74634 |
Maximum of Months | 744.00000 | 21.74131 | 51.39866 | -0.2044 | 37.23364 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT9_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.51025 | 28.40566 | -0.3472 | 8.80212 |
February | 672.00000 | 21.56985 | 25.32026 | -0.3362 | 8.57519 |
March | 744.00000 | 21.56931 | 24.15561 | -0.3434 | 8.56191 |
April | 720.00000 | 21.64807 | 27.61817 | -0.2595 | 7.53613 |
May | 744.00000 | 21.69076 | 36.06216 | -1.2680 | 39.90752 |
June | 720.00000 | 21.72757 | 41.43659 | -1.1710 | 35.20167 |
July | 744.00000 | 21.73115 | 51.91378 | -1.1036 | 32.18755 |
August | 744.00000 | 21.72180 | 49.78078 | -1.1204 | 33.03261 |
September | 720.00000 | 21.72392 | 48.60970 | -1.1170 | 33.23012 |
October | 744.00000 | 21.67087 | 44.29408 | -0.1145 | 6.46688 |
November | 720.00000 | 21.56707 | 29.75655 | -0.2837 | 8.16031 |
December | 744.00000 | 21.50503 | 25.29357 | -0.3775 | 9.30834 |
Annual Sum or Average | 8760.00000 | 21.63652 | 36.13335 | -0.6555 | 19.31569 |
Minimum of Months | 672.00000 | 21.50503 | 24.15561 | -1.2680 | 6.46688 |
Maximum of Months | 744.00000 | 21.73115 | 51.91378 | -0.1145 | 39.90752 |
Report: OccupantComfortDataSummaryMonthly
For: BANQUET_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.26528 | 26.66394 | -0.3216 | 7.38585 |
February | 672.00000 | 21.31201 | 23.53182 | -0.3121 | 7.29116 |
March | 744.00000 | 21.39299 | 22.38872 | -0.2800 | 6.87634 |
April | 720.00000 | 21.57787 | 26.06050 | -0.1708 | 6.00747 |
May | 744.00000 | 21.75058 | 36.61912 | -1.0783 | 30.16520 |
June | 720.00000 | 21.93306 | 44.36712 | -0.9254 | 23.84131 |
July | 744.00000 | 21.90552 | 59.18206 | -0.8469 | 20.78562 |
August | 744.00000 | 21.83932 | 56.38717 | -0.9035 | 22.90532 |
September | 720.00000 | 21.69355 | 54.09286 | -0.9941 | 26.50868 |
October | 744.00000 | 21.52572 | 46.06487 | -0.0719 | 5.54842 |
November | 720.00000 | 21.33241 | 28.08113 | -0.2755 | 6.87956 |
December | 744.00000 | 21.22666 | 23.66164 | -0.3588 | 7.86355 |
Annual Sum or Average | 8760.00000 | 21.56420 | 37.36146 | -0.5463 | 14.38001 |
Minimum of Months | 672.00000 | 21.22666 | 22.38872 | -1.0783 | 5.54842 |
Maximum of Months | 744.00000 | 21.93306 | 59.18206 | -0.0719 | 30.16520 |
Report: OccupantComfortDataSummaryMonthly
For: DINING_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.29951 | 26.42840 | -0.2822 | 6.91699 |
February | 672.00000 | 21.35119 | 23.29786 | -0.2716 | 6.82521 |
March | 744.00000 | 21.43936 | 22.14885 | -0.2376 | 6.44893 |
April | 720.00000 | 21.64362 | 25.78408 | -0.1242 | 5.74593 |
May | 744.00000 | 21.83209 | 36.26774 | -1.0065 | 27.10659 |
June | 720.00000 | 22.00838 | 43.99401 | -0.8577 | 21.29711 |
July | 744.00000 | 21.98178 | 58.73441 | -0.7787 | 18.43638 |
August | 744.00000 | 21.91080 | 55.97205 | -0.8368 | 20.45824 |
September | 720.00000 | 21.76036 | 53.70066 | -0.9288 | 23.90713 |
October | 744.00000 | 21.57822 | 45.74227 | -0.0292 | 5.48350 |
November | 720.00000 | 21.37171 | 27.83391 | -0.2352 | 6.47942 |
December | 744.00000 | 21.25914 | 23.43315 | -0.3194 | 7.33337 |
Annual Sum or Average | 8760.00000 | 21.62105 | 37.04727 | -0.4937 | 13.07314 |
Minimum of Months | 672.00000 | 21.25914 | 22.14885 | -1.0065 | 5.48350 |
Maximum of Months | 744.00000 | 22.00838 | 58.73441 | -0.0292 | 27.10659 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.68392 | 26.38521 | 0.65091 | 18.99511 |
February | 672.00000 | 22.77875 | 23.51065 | 0.67991 | 20.01074 |
March | 744.00000 | 22.84798 | 22.36422 | 0.71466 | 21.24991 |
April | 720.00000 | 23.01520 | 25.57177 | 0.83730 | 25.54931 |
May | 744.00000 | 23.10856 | 35.08927 | 0.33780 | 19.08382 |
June | 720.00000 | 23.17763 | 42.62625 | 0.46486 | 20.28481 |
July | 744.00000 | 23.16288 | 56.15785 | 0.54163 | 21.57354 |
August | 744.00000 | 23.14024 | 53.46182 | 0.49691 | 20.69194 |
September | 720.00000 | 23.10037 | 51.13803 | 0.44127 | 20.10801 |
October | 744.00000 | 22.96924 | 43.76715 | 0.92845 | 28.36706 |
November | 720.00000 | 22.79665 | 27.53865 | 0.71712 | 21.22993 |
December | 744.00000 | 22.65283 | 23.70266 | 0.61567 | 18.02481 |
Annual Sum or Average | 8760.00000 | 22.95352 | 36.03647 | 0.61841 | 21.26859 |
Minimum of Months | 672.00000 | 22.65283 | 22.36422 | 0.33780 | 18.02481 |
Maximum of Months | 744.00000 | 23.17763 | 56.15785 | 0.92845 | 28.36706 |
Report: OccupantComfortDataSummaryMonthly
For: STORAGE_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.00012 | 23.19187 | -0.5357 | 11.07120 |
February | 672.00000 | 21.00013 | 20.05601 | -0.5457 | 11.29397 |
March | 744.00000 | 21.00015 | 18.95775 | -0.5415 | 11.17122 |
April | 720.00000 | 21.00104 | 22.92222 | -0.4942 | 10.22152 |
May | 744.00000 | 21.01448 | 34.10409 | -1.5928 | 55.94226 |
June | 720.00000 | 21.08219 | 42.48748 | -1.4997 | 50.89869 |
July | 744.00000 | 21.06352 | 58.74147 | -1.4123 | 46.18389 |
August | 744.00000 | 21.03740 | 55.28578 | -1.4492 | 48.16235 |
September | 720.00000 | 21.00834 | 52.65068 | -1.4855 | 50.14919 |
October | 744.00000 | 21.00130 | 43.65668 | -0.3730 | 8.03217 |
November | 720.00000 | 21.00013 | 24.73200 | -0.5120 | 10.56023 |
December | 744.00000 | 21.00014 | 20.08094 | -0.5587 | 11.56906 |
Annual Sum or Average | 8760.00000 | 21.01749 | 34.84908 | -0.9189 | 27.19785 |
Minimum of Months | 672.00000 | 21.00012 | 18.95775 | -1.5928 | 8.03217 |
Maximum of Months | 744.00000 | 21.08219 | 58.74147 | -0.3730 | 55.94226 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.00053 | 25.36225 | -0.5156 | 10.61439 |
February | 672.00000 | 21.00554 | 22.21158 | -0.5257 | 10.82988 |
March | 744.00000 | 21.01144 | 21.11799 | -0.5251 | 10.79663 |
April | 720.00000 | 21.13520 | 24.90241 | -0.4616 | 9.59347 |
May | 744.00000 | 21.44929 | 35.37029 | -1.4733 | 49.51047 |
June | 720.00000 | 21.89922 | 42.73231 | -1.2702 | 38.83900 |
July | 744.00000 | 21.82869 | 58.05847 | -1.2016 | 35.37675 |
August | 744.00000 | 21.75840 | 55.07887 | -1.2453 | 37.59162 |
September | 720.00000 | 21.63515 | 52.76772 | -1.3010 | 40.44484 |
October | 744.00000 | 21.23136 | 45.17090 | -0.3165 | 7.28632 |
November | 720.00000 | 21.01991 | 26.85485 | -0.4904 | 10.10626 |
December | 744.00000 | 21.00043 | 22.26759 | -0.5372 | 11.06613 |
Annual Sum or Average | 8760.00000 | 21.33294 | 36.09551 | -0.8237 | 22.74591 |
Minimum of Months | 672.00000 | 21.00043 | 21.11799 | -1.4733 | 7.28632 |
Maximum of Months | 744.00000 | 21.89922 | 58.05847 | -0.3165 | 49.51047 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.00053 | 23.83993 | -0.5300 | 10.95946 |
February | 672.00000 | 21.00079 | 20.70471 | -0.5328 | 11.01696 |
March | 744.00000 | 21.00092 | 19.58945 | -0.5248 | 10.82015 |
April | 720.00000 | 21.03217 | 23.50660 | -0.4552 | 9.52173 |
May | 744.00000 | 21.10307 | 34.56012 | -1.5125 | 51.61975 |
June | 720.00000 | 21.41867 | 42.38890 | -1.3281 | 41.84120 |
July | 744.00000 | 21.37818 | 57.95888 | -1.2500 | 37.85815 |
August | 744.00000 | 21.30374 | 54.94477 | -1.3018 | 40.51418 |
September | 720.00000 | 21.18437 | 52.55319 | -1.3715 | 44.16686 |
October | 744.00000 | 21.05857 | 44.08086 | -0.3284 | 7.46525 |
November | 720.00000 | 21.00247 | 25.36620 | -0.4970 | 10.28157 |
December | 744.00000 | 21.00012 | 20.74387 | -0.5583 | 11.57932 |
Annual Sum or Average | 8760.00000 | 21.12425 | 35.12721 | -0.8511 | 24.04964 |
Minimum of Months | 672.00000 | 21.00012 | 19.58945 | -1.5125 | 7.46525 |
Maximum of Months | 744.00000 | 21.41867 | 57.95888 | -0.3284 | 51.61975 |
Report: OccupantComfortDataSummaryMonthly
For: MECH_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.00010 | 23.01065 | -0.5155 | 10.62566 |
February | 672.00000 | 21.00010 | 19.87506 | -0.5259 | 10.84866 |
March | 744.00000 | 21.00026 | 18.77128 | -0.5217 | 10.72878 |
April | 720.00000 | 21.01554 | 22.71621 | -0.4722 | 9.78489 |
May | 744.00000 | 21.05887 | 33.83098 | -1.5533 | 53.81118 |
June | 720.00000 | 21.15471 | 42.13586 | -1.4529 | 48.40056 |
July | 744.00000 | 21.13300 | 58.24297 | -1.3672 | 43.82167 |
August | 744.00000 | 21.09640 | 54.88717 | -1.4066 | 45.90497 |
September | 720.00000 | 21.04740 | 52.30921 | -1.4479 | 48.13818 |
October | 744.00000 | 21.01188 | 43.43142 | -0.3520 | 7.72531 |
November | 720.00000 | 21.00031 | 24.54824 | -0.4924 | 10.14919 |
December | 744.00000 | 21.00007 | 19.90165 | -0.5379 | 11.09099 |
Annual Sum or Average | 8760.00000 | 21.04345 | 34.58122 | -0.8892 | 26.00798 |
Minimum of Months | 672.00000 | 21.00007 | 18.77128 | -1.5533 | 7.72531 |
Maximum of Months | 744.00000 | 21.15471 | 58.24297 | -0.3520 | 53.81118 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.209948E+11 | 93871.28 | 03-JAN-16:01 | 437.64 | 0.604071E+11 | 0.00 | 0.814019E+11 | 1.72 | 3.36 | 03-JAN-16:01 | 0.00 | 0.00 |
February | 0.444274E+11 | 129766.38 | 20-FEB-16:01 | 495.22 | 0.129965E+12 | 0.00 | 0.174392E+12 | 2.15 | 3.71 | 19-FEB-19:01 | 0.00 | 0.00 |
March | 0.752798E+11 | 136163.13 | 21-MAR-15:01 | 612.53 | 0.221399E+12 | 0.00 | 0.296679E+12 | 2.40 | 3.75 | 22-MAR-18:02 | 0.00 | 0.00 |
April | 0.179566E+12 | 200145.02 | 21-APR-15:03 | 706.32 | 0.543500E+12 | 0.00 | 0.723066E+12 | 2.92 | 3.73 | 12-APR-18:01 | 0.00 | 0.00 |
May | 0.278388E+12 | 211448.92 | 19-MAY-15:03 | 744.00 | 0.843371E+12 | 0.00 | 0.112176E+13 | 3.01 | 3.81 | 28-MAY-19:00 | 0.00 | 0.00 |
June | 0.355970E+12 | 269287.56 | 14-JUN-18:03 | 720.00 | 0.105431E+13 | 0.00 | 0.141028E+13 | 3.00 | 3.85 | 28-JUN-08:62 | 0.00 | 0.00 |
July | 0.422527E+12 | 259215.32 | 21-JUL-18:03 | 744.00 | 0.136388E+13 | 0.00 | 0.178640E+13 | 3.25 | 4.18 | 18-JUL-21:00 | 0.00 | 0.00 |
August | 0.361581E+12 | 241415.11 | 04-AUG-15:15 | 744.00 | 0.113868E+13 | 0.00 | 0.150026E+13 | 3.17 | 4.13 | 16-AUG-18:02 | 0.00 | 0.00 |
September | 0.300733E+12 | 214043.22 | 01-SEP-15:03 | 720.00 | 0.980422E+12 | 0.00 | 0.128115E+13 | 3.23 | 4.30 | 23-SEP-18:03 | 0.00 | 0.00 |
October | 0.175237E+12 | 210469.25 | 01-OCT-15:03 | 743.50 | 0.548418E+12 | 0.00 | 0.723655E+12 | 3.03 | 3.94 | 04-OCT-08:62 | 0.00 | 0.00 |
November | 0.586973E+11 | 131370.30 | 09-NOV-16:01 | 538.52 | 0.171513E+12 | 0.00 | 0.230210E+12 | 2.18 | 3.76 | 09-NOV-19:01 | 0.00 | 0.00 |
December | 0.161009E+11 | 73879.01 | 10-DEC-16:01 | 406.95 | 0.462090E+11 | 0.00 | 0.623099E+11 | 1.60 | 3.03 | 10-DEC-16:01 | 0.00 | 0.00 |
Annual Sum or Average | 0.228950E+13 | 7612.68 | 0.710207E+13 | 0.00 | 0.939157E+13 | 2.64 | 0.00 | 0.00 | ||||
Minimum of Months | 0.161009E+11 | 73879.01 | 406.95 | 0.462090E+11 | 0.00 | 0.623099E+11 | 1.60 | 3.03 | 0.00 | 0.00 | ||
Maximum of Months | 0.422527E+12 | 269287.56 | 744.00 | 0.136388E+13 | 0.00 | 0.178640E+13 | 3.25 | 4.30 | 0.00 | 0.00 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.126721E+12 | 0.00 | 744.00 | 160680.34 | 27-JAN-09:02 | 0.00 | 35.12 | 60.00 | 0.48 | 0.00 | 0.10 | 0.33 | 27-JAN-09:02 |
February | 0.101869E+12 | 0.00 | 672.00 | 155354.24 | 03-FEB-07:10 | 0.00 | 34.34 | 60.00 | 0.42 | 0.00 | 0.09 | 0.32 | 03-FEB-07:10 |
March | 0.979744E+11 | 0.00 | 744.00 | 155356.75 | 02-MAR-09:02 | 0.00 | 33.93 | 60.00 | 0.36 | 0.00 | 0.08 | 0.32 | 02-MAR-09:02 |
April | 0.586368E+11 | 0.00 | 713.17 | 91791.34 | 11-APR-08:62 | 0.00 | 32.84 | 59.73 | 0.21 | 0.00 | 0.05 | 0.19 | 11-APR-08:62 |
May | 0.450340E+11 | 0.00 | 716.06 | 78325.35 | 23-MAY-08:04 | 0.00 | 32.72 | 58.96 | 0.15 | 0.00 | 0.03 | 0.16 | 23-MAY-08:04 |
June | 0.360485E+11 | 0.00 | 663.14 | 68798.46 | 23-JUN-08:04 | 0.00 | 33.39 | 57.85 | 0.13 | 0.00 | 0.03 | 0.14 | 23-JUN-08:04 |
July | 0.308091E+11 | 0.00 | 660.14 | 69610.16 | 21-JUL-10:35 | 0.00 | 31.24 | 56.56 | 0.10 | 0.00 | 0.02 | 0.14 | 21-JUL-10:35 |
August | 0.273493E+11 | 0.00 | 667.00 | 66339.21 | 18-AUG-10:35 | 0.00 | 30.08 | 56.70 | 0.08 | 0.00 | 0.02 | 0.14 | 18-AUG-10:35 |
September | 0.248923E+11 | 0.00 | 677.89 | 69422.63 | 15-SEP-08:04 | 0.00 | 29.91 | 58.21 | 0.08 | 0.00 | 0.02 | 0.14 | 15-SEP-08:04 |
October | 0.390698E+11 | 0.00 | 735.81 | 88051.01 | 13-OCT-08:05 | 0.00 | 29.56 | 59.67 | 0.12 | 0.00 | 0.03 | 0.18 | 13-OCT-08:05 |
November | 0.842367E+11 | 0.00 | 720.00 | 148981.37 | 28-NOV-09:02 | 0.00 | 32.95 | 60.00 | 0.32 | 0.00 | 0.07 | 0.31 | 28-NOV-09:02 |
December | 0.139381E+12 | 0.00 | 744.00 | 156975.75 | 27-DEC-09:02 | 0.00 | 35.54 | 60.00 | 0.54 | 0.00 | 0.11 | 0.32 | 27-DEC-09:02 |
Annual Sum or Average | 0.812022E+12 | 0.00 | 8457.19 | 0.00 | 32.62 | 58.96 | 0.25 | 0.00 | 0.05 | ||||
Minimum of Months | 0.248923E+11 | 0.00 | 660.14 | 66339.21 | 0.00 | 29.56 | 56.56 | 0.08 | 0.00 | 0.02 | 0.14 | ||
Maximum of Months | 0.139381E+12 | 0.00 | 744.00 | 160680.34 | 0.00 | 35.54 | 60.00 | 0.54 | 0.00 | 0.11 | 0.33 |
Report: DXReportMonthly
For: VAV WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.201108E+11 | 0.00 | 95.22 | 0.201108E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 192380.40 | 03-JAN-17:00 | 192380.40 | 03-JAN-17:00 | 0.00 | 0.00 | 0.00 |
February | 0.759769E+11 | 0.00 | 199.86 | 0.759769E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 233415.98 | 20-FEB-11:50 | 233415.98 | 20-FEB-11:50 | 0.00 | 0.00 | 0.00 |
March | 0.145448E+12 | 0.00 | 327.59 | 0.145448E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 260781.39 | 14-MAR-17:13 | 260781.39 | 14-MAR-17:13 | 0.00 | 0.00 | 0.00 |
April | 0.382942E+12 | 0.00 | 588.06 | 0.382942E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 333076.85 | 19-APR-18:10 | 333076.85 | 19-APR-18:10 | 0.00 | 0.00 | 0.00 |
May | 0.597793E+12 | 0.00 | 726.83 | 0.591323E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 410770.20 | 28-MAY-10:35 | 365786.80 | 19-MAY-17:12 | 0.00 | 0.00 | 0.00 |
June | 0.736192E+12 | 0.00 | 720.00 | 0.720033E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 450614.15 | 19-JUN-18:10 | 408064.65 | 02-JUN-17:13 | 0.00 | 0.00 | 0.00 |
July | 0.981701E+12 | 0.00 | 744.00 | 0.745816E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 677044.84 | 21-JUL-06:30 | 406142.32 | 03-JUL-17:13 | 0.00 | 0.00 | 0.00 |
August | 0.808393E+12 | 0.00 | 744.00 | 0.700978E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 593511.92 | 01-AUG-21:00 | 390034.35 | 07-AUG-17:13 | 0.00 | 0.00 | 0.00 |
September | 0.694503E+12 | 0.00 | 699.50 | 0.565639E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 536772.07 | 22-SEP-02:00 | 355672.63 | 19-SEP-16:20 | 0.00 | 0.00 | 0.00 |
October | 0.364337E+12 | 0.00 | 591.47 | 0.340216E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 466255.17 | 03-OCT-20:30 | 326774.47 | 05-OCT-16:00 | 0.00 | 0.00 | 0.00 |
November | 0.944464E+11 | 0.00 | 266.29 | 0.944464E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 247738.69 | 03-NOV-16:00 | 247738.69 | 03-NOV-16:00 | 0.00 | 0.00 | 0.00 |
December | 0.146740E+11 | 0.00 | 98.38 | 0.146740E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 127386.92 | 10-DEC-15:00 | 127386.92 | 10-DEC-15:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.491652E+13 | 0.00 | 5801.20 | 0.439760E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.146740E+11 | 0.00 | 95.22 | 0.146740E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 127386.92 | 127386.92 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.981701E+12 | 0.00 | 744.00 | 0.745816E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 677044.84 | 408064.65 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: FLR_3_DOAS COOLING COIL
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.122869E+10 | 0.00 | 63.67 | 0.122869E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18651.05 | 03-JAN-15:00 | 18651.05 | 03-JAN-15:00 | 0.00 | 0.00 | 0.00 |
February | 0.621055E+10 | 0.00 | 159.50 | 0.621055E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24890.15 | 20-FEB-15:00 | 24890.15 | 20-FEB-15:00 | 0.00 | 0.00 | 0.00 |
March | 0.124469E+11 | 0.00 | 278.00 | 0.124469E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 28566.40 | 21-MAR-16:00 | 28566.40 | 21-MAR-16:00 | 0.00 | 0.00 | 0.00 |
April | 0.399969E+11 | 0.00 | 548.50 | 0.399969E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 44409.17 | 21-APR-15:00 | 44409.17 | 21-APR-15:00 | 0.00 | 0.00 | 0.00 |
May | 0.693058E+11 | 0.00 | 713.33 | 0.674714E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 50585.42 | 19-MAY-14:00 | 50585.42 | 19-MAY-14:00 | 0.00 | 0.00 | 0.00 |
June | 0.932452E+11 | 0.00 | 720.00 | 0.894911E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 58655.85 | 02-JUN-17:00 | 58655.85 | 02-JUN-17:00 | 0.00 | 0.00 | 0.00 |
July | 0.127410E+12 | 0.00 | 744.00 | 0.896819E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 65741.82 | 20-JUL-16:00 | 54269.30 | 06-JUL-16:00 | 0.00 | 0.00 | 0.00 |
August | 0.102279E+12 | 0.00 | 744.00 | 0.830713E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 58860.95 | 02-AUG-12:00 | 55376.52 | 07-AUG-16:00 | 0.00 | 0.00 | 0.00 |
September | 0.814589E+11 | 0.00 | 692.83 | 0.629435E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 55192.93 | 14-SEP-10:00 | 48186.26 | 19-SEP-14:00 | 0.00 | 0.00 | 0.00 |
October | 0.377637E+11 | 0.00 | 534.83 | 0.336702E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 52564.31 | 03-OCT-14:00 | 45726.84 | 01-OCT-15:00 | 0.00 | 0.00 | 0.00 |
November | 0.755815E+10 | 0.00 | 211.33 | 0.755815E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26388.16 | 03-NOV-16:00 | 26388.16 | 03-NOV-16:00 | 0.00 | 0.00 | 0.00 |
December | 0.724489E+09 | 0.00 | 54.00 | 0.724489E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11238.20 | 10-DEC-15:00 | 11238.20 | 10-DEC-15:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.579628E+12 | 0.00 | 5464.00 | 0.494495E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.724489E+09 | 0.00 | 54.00 | 0.724489E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11238.20 | 11238.20 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.127410E+12 | 0.00 | 744.00 | 0.896819E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 65741.82 | 58655.85 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.722115E+09 | 0.00 | 158.78 | 0.720641E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18116.34 | 01-JAN-16:02 | 18116.34 | 01-JAN-16:02 | 0.00 | 0.00 | 0.00 |
February | 0.120688E+10 | 0.00 | 205.68 | 0.120552E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18089.20 | 18-FEB-16:01 | 18089.20 | 18-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.226720E+10 | 0.00 | 325.77 | 0.225421E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18096.24 | 12-MAR-15:01 | 18096.24 | 12-MAR-15:01 | 0.00 | 0.00 | 0.00 |
April | 0.546037E+10 | 0.00 | 569.21 | 0.512260E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18122.49 | 17-APR-18:01 | 18122.49 | 17-APR-18:01 | 0.00 | 0.00 | 0.00 |
May | 0.876234E+10 | 0.00 | 678.24 | 0.753288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18730.83 | 28-MAY-08:61 | 18122.69 | 31-MAY-15:02 | 0.00 | 0.00 | 0.00 |
June | 0.115697E+11 | 0.00 | 682.51 | 0.920445E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18607.62 | 28-JUN-08:62 | 18122.56 | 21-JUN-15:02 | 0.00 | 0.00 | 0.00 |
July | 0.127687E+11 | 0.00 | 707.05 | 0.777143E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21980.88 | 19-JUL-08:62 | 16925.78 | 30-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.113529E+11 | 0.00 | 693.06 | 0.718810E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20204.96 | 02-AUG-08:61 | 18121.92 | 23-AUG-15:01 | 0.00 | 0.00 | 0.00 |
September | 0.100953E+11 | 0.00 | 672.88 | 0.634610E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20228.89 | 09-SEP-08:61 | 18122.45 | 18-SEP-18:01 | 0.00 | 0.00 | 0.00 |
October | 0.608411E+10 | 0.00 | 605.17 | 0.415205E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19090.18 | 04-OCT-08:62 | 18121.16 | 19-OCT-15:01 | 0.00 | 0.00 | 0.00 |
November | 0.206946E+10 | 0.00 | 324.78 | 0.188067E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18123.27 | 04-NOV-15:01 | 18123.27 | 04-NOV-15:01 | 0.00 | 0.00 | 0.00 |
December | 0.415065E+09 | 0.00 | 114.52 | 0.415065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18086.00 | 07-DEC-16:01 | 18086.00 | 07-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.727741E+11 | 0.00 | 5737.65 | 0.537937E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.415065E+09 | 0.00 | 114.52 | 0.415065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18086.00 | 16925.78 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.127687E+11 | 0.00 | 707.05 | 0.920445E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21980.88 | 18123.27 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.127140E+09 | 0.00 | 39.62 | 0.126798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17677.89 | 12-JAN-16:01 | 17677.89 | 12-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.423650E+09 | 0.00 | 98.91 | 0.422969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17958.79 | 18-FEB-16:01 | 17958.79 | 18-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.136437E+10 | 0.00 | 231.75 | 0.135368E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17961.97 | 12-MAR-15:01 | 17961.97 | 12-MAR-15:01 | 0.00 | 0.00 | 0.00 |
April | 0.466002E+10 | 0.00 | 523.87 | 0.436151E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17992.74 | 17-APR-18:01 | 17992.74 | 17-APR-18:01 | 0.00 | 0.00 | 0.00 |
May | 0.854167E+10 | 0.00 | 670.25 | 0.733311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18575.57 | 28-MAY-08:61 | 17992.86 | 31-MAY-15:02 | 0.00 | 0.00 | 0.00 |
June | 0.116408E+11 | 0.00 | 683.84 | 0.929468E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18500.58 | 28-JUN-08:62 | 17992.70 | 21-JUN-15:02 | 0.00 | 0.00 | 0.00 |
July | 0.127116E+11 | 0.00 | 707.57 | 0.776970E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21770.64 | 19-JUL-08:62 | 16867.14 | 30-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.107086E+11 | 0.00 | 686.92 | 0.667650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20137.60 | 02-AUG-08:61 | 17992.21 | 23-AUG-15:01 | 0.00 | 0.00 | 0.00 |
September | 0.847497E+10 | 0.00 | 650.85 | 0.499668E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20082.86 | 23-SEP-18:01 | 17993.12 | 18-SEP-18:01 | 0.00 | 0.00 | 0.00 |
October | 0.406830E+10 | 0.00 | 504.51 | 0.259372E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18881.85 | 04-OCT-08:62 | 17992.66 | 25-OCT-15:01 | 0.00 | 0.00 | 0.00 |
November | 0.656897E+09 | 0.00 | 159.03 | 0.558419E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17991.11 | 09-NOV-16:01 | 17991.11 | 09-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 49598812.63 | 0.00 | 17.24 | 49598812.63 | 0.00 | 0.00 | 0.00 | 0.00 | 17361.38 | 16-DEC-16:02 | 17361.38 | 16-DEC-16:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.634276E+11 | 0.00 | 4974.38 | 0.455374E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 49598812.63 | 0.00 | 17.24 | 49598812.63 | 0.00 | 0.00 | 0.00 | 0.00 | 17361.38 | 16867.14 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.127116E+11 | 0.00 | 707.57 | 0.929468E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21770.64 | 17993.12 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.187338E+11 | 0.00 | 329.06 | 0.187338E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 42039.10 | 12-JAN-14:30 | 42039.10 | 12-JAN-14:30 | 0.00 | 0.00 | 0.00 |
February | 0.186891E+11 | 0.00 | 354.31 | 0.186666E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 40287.64 | 07-FEB-13:40 | 40287.64 | 07-FEB-13:40 | 0.00 | 0.00 | 0.00 |
March | 0.178191E+11 | 0.00 | 390.81 | 0.176597E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 32128.75 | 16-MAR-13:30 | 32128.75 | 16-MAR-13:30 | 0.00 | 0.00 | 0.00 |
April | 0.286378E+11 | 0.00 | 544.85 | 0.275079E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 31143.23 | 03-APR-14:00 | 31143.23 | 03-APR-14:00 | 0.00 | 0.00 | 0.00 |
May | 0.372407E+11 | 0.00 | 673.42 | 0.314968E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 32772.64 | 19-MAY-20:20 | 32772.64 | 19-MAY-20:20 | 0.00 | 0.00 | 0.00 |
June | 0.490596E+11 | 0.00 | 710.42 | 0.377855E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 37380.51 | 17-JUN-18:25 | 37380.51 | 17-JUN-18:25 | 0.00 | 0.00 | 0.00 |
July | 0.582359E+11 | 0.00 | 743.17 | 0.294422E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 40363.45 | 02-JUL-20:40 | 40363.45 | 02-JUL-20:40 | 0.00 | 0.00 | 0.00 |
August | 0.552429E+11 | 0.00 | 730.19 | 0.324876E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 40451.04 | 06-AUG-19:05 | 37638.48 | 27-AUG-13:50 | 0.00 | 0.00 | 0.00 |
September | 0.589986E+11 | 0.00 | 698.89 | 0.396780E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 50495.60 | 19-SEP-13:10 | 45036.56 | 17-SEP-13:20 | 0.00 | 0.00 | 0.00 |
October | 0.499915E+11 | 0.00 | 653.11 | 0.393898E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 54374.54 | 22-OCT-13:40 | 49921.86 | 29-OCT-13:00 | 0.00 | 0.00 | 0.00 |
November | 0.320013E+11 | 0.00 | 426.31 | 0.310643E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 48108.55 | 09-NOV-13:50 | 48108.55 | 09-NOV-13:50 | 0.00 | 0.00 | 0.00 |
December | 0.142146E+11 | 0.00 | 293.92 | 0.142146E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 38082.67 | 16-DEC-13:40 | 38082.67 | 16-DEC-13:40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.438865E+12 | 0.00 | 6548.44 | 0.338127E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.142146E+11 | 0.00 | 293.92 | 0.142146E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 31143.23 | 31143.23 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.589986E+11 | 0.00 | 743.17 | 0.396780E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 54374.54 | 49921.86 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.500924E+10 | 0.00 | 185.85 | 0.470017E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 109209.76 | 13-JAN-19:02 | 109209.76 | 13-JAN-19:02 | 0.00 | 0.00 | 0.00 |
February | 0.952481E+10 | 0.00 | 272.78 | 0.888985E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 112954.08 | 20-FEB-09:01 | 112954.08 | 20-FEB-09:01 | 0.00 | 0.00 | 0.00 |
March | 0.182443E+11 | 0.00 | 406.39 | 0.178289E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 115105.18 | 15-MAR-18:01 | 115105.18 | 15-MAR-18:01 | 0.00 | 0.00 | 0.00 |
April | 0.405932E+11 | 0.00 | 508.40 | 0.383877E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 120021.63 | 28-APR-18:01 | 120021.63 | 28-APR-18:01 | 0.00 | 0.00 | 0.00 |
May | 0.650000E+11 | 0.00 | 586.99 | 0.570325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 120151.00 | 28-MAY-08:61 | 120053.67 | 08-MAY-18:01 | 0.00 | 0.00 | 0.00 |
June | 0.833085E+11 | 0.00 | 630.28 | 0.686231E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 120394.27 | 28-JUN-08:62 | 120045.06 | 21-JUN-15:02 | 0.00 | 0.00 | 0.00 |
July | 0.951723E+11 | 0.00 | 655.87 | 0.627338E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 144018.26 | 19-JUL-08:62 | 112770.98 | 28-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.805664E+11 | 0.00 | 616.90 | 0.533239E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 130555.13 | 02-AUG-08:61 | 120062.95 | 27-AUG-18:01 | 0.00 | 0.00 | 0.00 |
September | 0.635069E+11 | 0.00 | 558.06 | 0.400279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 134191.44 | 23-SEP-18:01 | 120060.29 | 17-SEP-18:01 | 0.00 | 0.00 | 0.00 |
October | 0.408900E+11 | 0.00 | 529.25 | 0.266324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 122745.68 | 04-OCT-08:62 | 120029.34 | 01-OCT-18:01 | 0.00 | 0.00 | 0.00 |
November | 0.116994E+11 | 0.00 | 324.31 | 0.996162E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 113548.45 | 11-NOV-09:01 | 113548.45 | 11-NOV-09:01 | 0.00 | 0.00 | 0.00 |
December | 0.336045E+10 | 0.00 | 139.40 | 0.336045E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 111643.78 | 09-DEC-09:01 | 111643.78 | 09-DEC-09:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.516875E+12 | 0.00 | 5414.47 | 0.391502E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.336045E+10 | 0.00 | 139.40 | 0.336045E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 109209.76 | 109209.76 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.951723E+11 | 0.00 | 655.87 | 0.686231E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 144018.26 | 120062.95 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_5_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.609955E+09 | 0.00 | 143.21 | 0.606864E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15862.15 | 12-JAN-16:01 | 15862.15 | 12-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.132023E+10 | 0.00 | 241.57 | 0.131359E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15875.09 | 08-FEB-09:01 | 15875.09 | 08-FEB-09:01 | 0.00 | 0.00 | 0.00 |
March | 0.226342E+10 | 0.00 | 368.39 | 0.225232E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15859.33 | 07-MAR-09:01 | 15859.33 | 07-MAR-09:01 | 0.00 | 0.00 | 0.00 |
April | 0.567944E+10 | 0.00 | 613.27 | 0.532430E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15874.38 | 28-APR-18:01 | 15874.38 | 28-APR-18:01 | 0.00 | 0.00 | 0.00 |
May | 0.888487E+10 | 0.00 | 714.57 | 0.763547E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15875.28 | 31-MAY-15:02 | 15875.28 | 31-MAY-15:02 | 0.00 | 0.00 | 0.00 |
June | 0.118750E+11 | 0.00 | 704.83 | 0.952314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16515.28 | 28-JUN-08:62 | 15875.61 | 21-JUN-15:02 | 0.00 | 0.00 | 0.00 |
July | 0.130746E+11 | 0.00 | 725.33 | 0.807924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19223.52 | 19-JUL-08:62 | 14872.21 | 13-JUL-08:61 | 0.00 | 0.00 | 0.00 |
August | 0.115969E+11 | 0.00 | 716.02 | 0.739006E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17340.53 | 18-AUG-08:62 | 15875.29 | 23-AUG-15:01 | 0.00 | 0.00 | 0.00 |
September | 0.101459E+11 | 0.00 | 693.18 | 0.640534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17531.86 | 23-SEP-18:01 | 15874.26 | 18-SEP-18:01 | 0.00 | 0.00 | 0.00 |
October | 0.564508E+10 | 0.00 | 593.13 | 0.389281E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17124.40 | 09-OCT-08:62 | 15875.17 | 25-OCT-15:01 | 0.00 | 0.00 | 0.00 |
November | 0.190716E+10 | 0.00 | 325.73 | 0.176934E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15873.57 | 09-NOV-16:01 | 15873.57 | 09-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 0.436861E+09 | 0.00 | 108.43 | 0.436861E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15857.54 | 09-DEC-09:01 | 15857.54 | 09-DEC-09:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.734393E+11 | 0.00 | 5947.66 | 0.546294E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.436861E+09 | 0.00 | 108.43 | 0.436861E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15857.54 | 14872.21 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.130746E+11 | 0.00 | 725.33 | 0.952314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19223.52 | 15875.61 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_6_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 59193127.27 | 0.00 | 27.69 | 58573583.11 | 0.00 | 0.00 | 0.00 | 0.00 | 10552.22 | 31-JAN-09:02 | 10552.22 | 31-JAN-09:02 | 0.00 | 0.00 | 0.00 |
February | 0.469791E+09 | 0.00 | 111.19 | 0.464288E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15725.79 | 19-FEB-09:01 | 15725.79 | 19-FEB-09:01 | 0.00 | 0.00 | 0.00 |
March | 0.130087E+10 | 0.00 | 247.94 | 0.129413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15730.28 | 07-MAR-09:01 | 15730.28 | 07-MAR-09:01 | 0.00 | 0.00 | 0.00 |
April | 0.483194E+10 | 0.00 | 564.52 | 0.450165E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15745.13 | 28-APR-18:01 | 15745.13 | 28-APR-18:01 | 0.00 | 0.00 | 0.00 |
May | 0.864751E+10 | 0.00 | 711.20 | 0.741971E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15746.09 | 31-MAY-15:02 | 15746.09 | 31-MAY-15:02 | 0.00 | 0.00 | 0.00 |
June | 0.119435E+11 | 0.00 | 705.56 | 0.962191E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16208.19 | 28-JUN-08:62 | 15746.38 | 21-JUN-15:02 | 0.00 | 0.00 | 0.00 |
July | 0.130094E+11 | 0.00 | 725.56 | 0.805837E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19021.43 | 19-JUL-08:62 | 14724.07 | 09-JUL-08:61 | 0.00 | 0.00 | 0.00 |
August | 0.109444E+11 | 0.00 | 710.78 | 0.685094E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17179.76 | 18-AUG-08:62 | 15745.36 | 27-AUG-15:02 | 0.00 | 0.00 | 0.00 |
September | 0.849771E+10 | 0.00 | 679.95 | 0.507713E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17570.65 | 23-SEP-18:01 | 15745.60 | 11-SEP-08:62 | 0.00 | 0.00 | 0.00 |
October | 0.360323E+10 | 0.00 | 476.94 | 0.231320E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16961.32 | 09-OCT-08:62 | 15743.68 | 01-OCT-18:01 | 0.00 | 0.00 | 0.00 |
November | 0.585874E+09 | 0.00 | 139.24 | 0.514753E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15738.93 | 11-NOV-09:01 | 15738.93 | 11-NOV-09:01 | 0.00 | 0.00 | 0.00 |
December | 42956447.95 | 0.00 | 18.30 | 42956447.95 | 0.00 | 0.00 | 0.00 | 0.00 | 14941.11 | 09-DEC-09:01 | 14941.11 | 09-DEC-09:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.639364E+11 | 0.00 | 5118.86 | 0.462176E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 42956447.95 | 0.00 | 18.30 | 42956447.95 | 0.00 | 0.00 | 0.00 | 0.00 | 10552.22 | 10552.22 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.130094E+11 | 0.00 | 725.56 | 0.962191E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19021.43 | 15746.38 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.154784E+09 | 0.00 | 115.90 | 0.154121E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4910.70 | 01-JAN-16:02 | 4910.70 | 01-JAN-16:02 | 0.00 | 0.00 | 0.00 |
February | 0.294475E+09 | 0.00 | 166.92 | 0.294142E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4903.32 | 18-FEB-16:01 | 4903.32 | 18-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.588547E+09 | 0.00 | 293.32 | 0.585991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4905.26 | 12-MAR-15:01 | 4905.26 | 12-MAR-15:01 | 0.00 | 0.00 | 0.00 |
April | 0.155247E+10 | 0.00 | 553.43 | 0.146061E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4912.21 | 17-APR-18:01 | 4912.21 | 17-APR-18:01 | 0.00 | 0.00 | 0.00 |
May | 0.252069E+10 | 0.00 | 682.72 | 0.218838E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5153.34 | 28-MAY-08:61 | 4912.37 | 31-MAY-15:02 | 0.00 | 0.00 | 0.00 |
June | 0.336670E+10 | 0.00 | 689.85 | 0.271700E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5157.48 | 28-JUN-08:62 | 4912.57 | 05-JUN-18:02 | 0.00 | 0.00 | 0.00 |
July | 0.371169E+10 | 0.00 | 713.59 | 0.236371E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6142.55 | 19-JUL-08:62 | 4527.84 | 04-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.328258E+10 | 0.00 | 703.38 | 0.215465E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5554.53 | 02-AUG-08:61 | 4912.25 | 23-AUG-15:01 | 0.00 | 0.00 | 0.00 |
September | 0.285224E+10 | 0.00 | 671.97 | 0.186364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5617.95 | 09-SEP-08:61 | 4912.41 | 18-SEP-18:01 | 0.00 | 0.00 | 0.00 |
October | 0.165147E+10 | 0.00 | 569.37 | 0.115670E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5258.38 | 04-OCT-08:62 | 4912.05 | 19-OCT-15:01 | 0.00 | 0.00 | 0.00 |
November | 0.511879E+09 | 0.00 | 281.68 | 0.466981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4912.59 | 04-NOV-15:01 | 4912.59 | 04-NOV-15:01 | 0.00 | 0.00 | 0.00 |
December | 84102887.94 | 0.00 | 76.42 | 84102887.94 | 0.00 | 0.00 | 0.00 | 0.00 | 4908.03 | 04-DEC-16:01 | 4908.03 | 04-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.205716E+11 | 0.00 | 5518.55 | 0.154900E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 84102887.94 | 0.00 | 76.42 | 84102887.94 | 0.00 | 0.00 | 0.00 | 0.00 | 4903.32 | 4527.84 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.371169E+10 | 0.00 | 713.59 | 0.271700E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6142.55 | 4912.59 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 23238703.27 | 0.00 | 26.83 | 23161350.58 | 0.00 | 0.00 | 0.00 | 0.00 | 4823.13 | 12-JAN-16:01 | 4823.13 | 12-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 99472589.74 | 0.00 | 80.72 | 99344177.58 | 0.00 | 0.00 | 0.00 | 0.00 | 4862.94 | 18-FEB-16:01 | 4862.94 | 18-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.348853E+09 | 0.00 | 204.33 | 0.346933E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4863.71 | 04-MAR-16:01 | 4863.71 | 04-MAR-16:01 | 0.00 | 0.00 | 0.00 |
April | 0.133726E+10 | 0.00 | 518.73 | 0.125408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4871.93 | 28-APR-18:01 | 4871.93 | 28-APR-18:01 | 0.00 | 0.00 | 0.00 |
May | 0.246120E+10 | 0.00 | 676.97 | 0.213130E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5099.76 | 28-MAY-08:61 | 4872.09 | 31-MAY-15:02 | 0.00 | 0.00 | 0.00 |
June | 0.338670E+10 | 0.00 | 691.07 | 0.274237E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5131.39 | 28-JUN-08:62 | 4872.28 | 05-JUN-18:02 | 0.00 | 0.00 | 0.00 |
July | 0.369689E+10 | 0.00 | 713.79 | 0.236125E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6076.02 | 19-JUL-08:62 | 4491.99 | 04-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.311223E+10 | 0.00 | 699.58 | 0.200664E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5543.01 | 02-AUG-08:61 | 4871.94 | 23-AUG-15:01 | 0.00 | 0.00 | 0.00 |
September | 0.241963E+10 | 0.00 | 656.21 | 0.148379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5544.28 | 09-SEP-08:61 | 4872.06 | 18-SEP-18:01 | 0.00 | 0.00 | 0.00 |
October | 0.111096E+10 | 0.00 | 463.96 | 0.727581E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4954.38 | 03-OCT-18:01 | 4872.18 | 25-OCT-15:01 | 0.00 | 0.00 | 0.00 |
November | 0.158680E+09 | 0.00 | 128.22 | 0.135959E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4871.62 | 09-NOV-16:01 | 4871.62 | 09-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 8212687.31 | 0.00 | 10.45 | 8212687.31 | 0.00 | 0.00 | 0.00 | 0.00 | 4345.74 | 16-DEC-16:02 | 4345.74 | 16-DEC-16:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.181633E+11 | 0.00 | 4870.86 | 0.133206E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 8212687.31 | 0.00 | 10.45 | 8212687.31 | 0.00 | 0.00 | 0.00 | 0.00 | 4345.74 | 4345.74 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.369689E+10 | 0.00 | 713.79 | 0.274237E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6076.02 | 4872.28 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.457271E+10 | 0.00 | 356.79 | 0.453936E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22324.09 | 01-JAN-16:02 | 22324.09 | 01-JAN-16:02 | 0.00 | 0.00 | 0.00 |
February | 0.479250E+10 | 0.00 | 380.88 | 0.476592E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22304.13 | 14-FEB-16:01 | 22304.13 | 14-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.498379E+10 | 0.00 | 445.57 | 0.494855E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22299.62 | 12-MAR-15:01 | 22299.62 | 12-MAR-15:01 | 0.00 | 0.00 | 0.00 |
April | 0.817043E+10 | 0.00 | 594.13 | 0.766155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22325.97 | 26-APR-18:01 | 22325.97 | 26-APR-18:01 | 0.00 | 0.00 | 0.00 |
May | 0.112351E+11 | 0.00 | 680.83 | 0.947273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23009.17 | 28-MAY-08:61 | 22326.83 | 20-MAY-18:02 | 0.00 | 0.00 | 0.00 |
June | 0.149190E+11 | 0.00 | 680.07 | 0.116596E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 22861.68 | 28-JUN-08:62 | 22327.98 | 05-JUN-15:02 | 0.00 | 0.00 | 0.00 |
July | 0.174206E+11 | 0.00 | 705.32 | 0.106592E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 27818.64 | 19-JUL-08:62 | 20900.83 | 23-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.164532E+11 | 0.00 | 699.36 | 0.107000E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 25022.47 | 02-AUG-08:61 | 20868.80 | 24-AUG-18:02 | 0.00 | 0.00 | 0.00 |
September | 0.162297E+11 | 0.00 | 681.58 | 0.110664E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 25483.19 | 23-SEP-18:01 | 22321.41 | 24-SEP-15:01 | 0.00 | 0.00 | 0.00 |
October | 0.126282E+11 | 0.00 | 653.01 | 0.956996E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23681.13 | 04-OCT-08:62 | 22327.04 | 25-OCT-18:01 | 0.00 | 0.00 | 0.00 |
November | 0.730636E+10 | 0.00 | 444.86 | 0.695177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22327.19 | 09-NOV-16:01 | 22327.19 | 09-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 0.402041E+10 | 0.00 | 333.00 | 0.401746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22311.90 | 04-DEC-16:01 | 22311.90 | 04-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.122732E+12 | 0.00 | 6655.40 | 0.960124E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.402041E+10 | 0.00 | 333.00 | 0.401746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22299.62 | 20868.80 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.174206E+11 | 0.00 | 705.32 | 0.116596E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 27818.64 | 22327.98 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 706.15 | 535.07 | 171.08 | 966.31 | 488.35 | 0.00 | 0.00 | 0.00 |
February | 664.38 | 471.17 | 193.21 | 931.83 | 426.84 | 0.00 | 0.00 | 0.00 |
March | 519.74 | 294.46 | 225.28 | 759.87 | 366.80 | 0.00 | 0.00 | 0.00 |
April | 362.15 | 135.95 | 226.20 | 624.30 | 193.52 | 0.00 | 0.00 | 0.00 |
May | 257.00 | 37.69 | 219.31 | 529.28 | 91.56 | 0.00 | 0.00 | 0.00 |
June | 219.82 | 13.83 | 205.99 | 578.17 | 31.64 | 0.00 | 0.00 | 0.00 |
July | 223.23 | 19.79 | 203.44 | 587.73 | 16.67 | 0.00 | 0.00 | 0.00 |
August | 281.79 | 71.59 | 210.20 | 662.86 | 35.29 | 0.00 | 0.00 | 0.00 |
September | 446.25 | 231.85 | 214.40 | 885.96 | 106.12 | 0.00 | 0.00 | 0.00 |
October | 612.55 | 416.17 | 196.38 | 1011.44 | 209.50 | 0.00 | 0.00 | 0.00 |
November | 737.24 | 563.91 | 173.33 | 1059.97 | 399.52 | 0.00 | 0.00 | 0.00 |
December | 724.95 | 544.65 | 180.31 | 971.49 | 531.20 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 478.50 | 276.88 | 201.63 | 796.44 | 240.54 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 219.82 | 13.83 | 171.08 | 529.28 | 16.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 737.24 | 563.91 | 226.20 | 1059.97 | 531.20 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1988.48 | 1506.73 | 481.75 | 2704.81 | 1387.38 | 0.00 | 0.00 | 0.00 |
February | 1870.85 | 1326.79 | 544.06 | 2607.58 | 1212.38 | 0.00 | 0.00 | 0.00 |
March | 1463.55 | 829.18 | 634.37 | 2123.50 | 1041.07 | 0.00 | 0.00 | 0.00 |
April | 1019.80 | 382.82 | 636.98 | 1744.59 | 557.35 | 0.00 | 0.00 | 0.00 |
May | 723.68 | 106.13 | 617.55 | 1474.27 | 272.00 | 0.00 | 0.00 | 0.00 |
June | 618.99 | 38.95 | 580.04 | 1609.26 | 101.92 | 0.00 | 0.00 | 0.00 |
July | 628.60 | 55.73 | 572.87 | 1634.91 | 58.32 | 0.00 | 0.00 | 0.00 |
August | 793.51 | 201.60 | 591.90 | 1852.27 | 115.73 | 0.00 | 0.00 | 0.00 |
September | 1256.61 | 652.87 | 603.74 | 2491.96 | 314.76 | 0.00 | 0.00 | 0.00 |
October | 1724.89 | 1171.91 | 552.99 | 2840.22 | 605.20 | 0.00 | 0.00 | 0.00 |
November | 2076.02 | 1587.93 | 488.09 | 2971.59 | 1135.58 | 0.00 | 0.00 | 0.00 |
December | 2041.42 | 1533.69 | 507.73 | 2716.87 | 1506.63 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1347.44 | 779.68 | 567.76 | 2228.18 | 689.89 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 618.99 | 38.95 | 481.75 | 1474.27 | 58.32 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2076.02 | 1587.93 | 636.98 | 2971.59 | 1506.63 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2583.15 | 1957.32 | 625.82 | 3583.68 | 1839.21 | 0.00 | 0.00 | 0.00 |
February | 2430.34 | 1723.58 | 706.76 | 3461.38 | 1605.98 | 0.00 | 0.00 | 0.00 |
March | 1901.24 | 1077.15 | 824.09 | 2821.64 | 1385.91 | 0.00 | 0.00 | 0.00 |
April | 1324.78 | 497.31 | 827.47 | 2331.15 | 742.00 | 0.00 | 0.00 | 0.00 |
May | 940.11 | 137.87 | 802.24 | 1977.06 | 364.15 | 0.00 | 0.00 | 0.00 |
June | 804.10 | 50.59 | 753.51 | 2164.92 | 134.32 | 0.00 | 0.00 | 0.00 |
July | 816.59 | 72.40 | 744.19 | 2197.35 | 75.81 | 0.00 | 0.00 | 0.00 |
August | 1030.81 | 261.90 | 768.91 | 2487.83 | 149.09 | 0.00 | 0.00 | 0.00 |
September | 1632.41 | 848.12 | 784.29 | 3337.86 | 406.25 | 0.00 | 0.00 | 0.00 |
October | 2240.73 | 1522.37 | 718.36 | 3793.06 | 787.66 | 0.00 | 0.00 | 0.00 |
November | 2696.87 | 2062.81 | 634.06 | 3951.91 | 1496.97 | 0.00 | 0.00 | 0.00 |
December | 2651.92 | 1992.35 | 659.58 | 3595.64 | 2000.72 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1750.40 | 1012.84 | 737.56 | 2971.61 | 912.42 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 804.10 | 50.59 | 625.82 | 1977.06 | 75.81 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2696.87 | 2062.81 | 827.47 | 3951.91 | 2000.72 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 139.62 | 105.79 | 33.83 | 189.77 | 99.30 | 0.00 | 0.00 | 0.00 |
February | 131.36 | 93.16 | 38.20 | 182.58 | 87.08 | 0.00 | 0.00 | 0.00 |
March | 102.76 | 58.22 | 44.54 | 146.71 | 75.62 | 0.00 | 0.00 | 0.00 |
April | 71.60 | 26.88 | 44.73 | 119.50 | 39.98 | 0.00 | 0.00 | 0.00 |
May | 50.81 | 7.45 | 43.36 | 101.00 | 18.69 | 0.00 | 0.00 | 0.00 |
June | 43.46 | 2.73 | 40.73 | 112.55 | 6.46 | 0.00 | 0.00 | 0.00 |
July | 44.14 | 3.91 | 40.22 | 113.72 | 3.57 | 0.00 | 0.00 | 0.00 |
August | 55.72 | 14.16 | 41.56 | 128.68 | 7.24 | 0.00 | 0.00 | 0.00 |
September | 88.23 | 45.84 | 42.39 | 173.13 | 21.71 | 0.00 | 0.00 | 0.00 |
October | 121.11 | 82.28 | 38.83 | 198.36 | 42.85 | 0.00 | 0.00 | 0.00 |
November | 145.77 | 111.49 | 34.27 | 208.64 | 81.15 | 0.00 | 0.00 | 0.00 |
December | 143.34 | 107.69 | 35.65 | 191.91 | 107.57 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 94.61 | 54.74 | 39.87 | 155.35 | 49.09 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 43.46 | 2.73 | 33.83 | 101.00 | 3.57 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 145.77 | 111.49 | 44.73 | 208.64 | 107.57 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 107.40 | 60.54 | 46.87 | 114.77 | 204.95 | 0.00 | 0.00 | 0.00 |
February | 120.90 | 64.15 | 56.75 | 140.05 | 179.43 | 0.00 | 0.00 | 0.00 |
March | 164.97 | 88.46 | 76.51 | 214.04 | 146.42 | 0.00 | 0.00 | 0.00 |
April | 189.31 | 102.11 | 87.19 | 295.74 | 73.78 | 0.00 | 0.00 | 0.00 |
May | 204.29 | 109.33 | 94.96 | 363.41 | 34.54 | 0.00 | 0.00 | 0.00 |
June | 198.79 | 106.74 | 92.05 | 410.06 | 11.98 | 0.00 | 0.00 | 0.00 |
July | 176.54 | 87.72 | 88.82 | 370.09 | 6.45 | 0.00 | 0.00 | 0.00 |
August | 170.94 | 87.09 | 83.85 | 340.68 | 13.39 | 0.00 | 0.00 | 0.00 |
September | 175.49 | 97.97 | 77.52 | 319.63 | 41.01 | 0.00 | 0.00 | 0.00 |
October | 151.21 | 88.52 | 62.68 | 235.09 | 83.90 | 0.00 | 0.00 | 0.00 |
November | 126.16 | 76.76 | 49.40 | 154.89 | 167.74 | 0.00 | 0.00 | 0.00 |
December | 101.75 | 55.25 | 46.51 | 102.71 | 225.76 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 157.45 | 85.45 | 72.00 | 255.61 | 98.73 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 101.75 | 55.25 | 46.51 | 102.71 | 6.45 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 204.29 | 109.33 | 94.96 | 410.06 | 225.76 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.40 | 0.00 | 20.40 | 4.65 | 110.42 | 0.00 | 0.00 | 0.00 |
February | 24.91 | 0.00 | 24.91 | 12.32 | 96.23 | 0.00 | 0.00 | 0.00 |
March | 32.60 | 0.00 | 32.60 | 24.85 | 79.01 | 0.00 | 0.00 | 0.00 |
April | 37.86 | 0.48 | 37.38 | 50.35 | 38.54 | 0.00 | 0.00 | 0.00 |
May | 44.72 | 3.30 | 41.43 | 84.87 | 17.26 | 0.00 | 0.00 | 0.00 |
June | 47.56 | 5.93 | 41.63 | 119.11 | 6.23 | 0.00 | 0.00 | 0.00 |
July | 43.94 | 4.31 | 39.63 | 111.30 | 3.41 | 0.00 | 0.00 | 0.00 |
August | 37.16 | 0.88 | 36.28 | 87.76 | 6.90 | 0.00 | 0.00 | 0.00 |
September | 32.33 | 0.04 | 32.29 | 63.32 | 21.44 | 0.00 | 0.00 | 0.00 |
October | 26.80 | 0.00 | 26.80 | 33.78 | 44.22 | 0.00 | 0.00 | 0.00 |
November | 21.63 | 0.00 | 21.63 | 9.22 | 90.16 | 0.00 | 0.00 | 0.00 |
December | 20.24 | 0.00 | 20.24 | 3.31 | 122.02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 32.55 | 1.25 | 31.30 | 50.61 | 52.78 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.24 | 0.00 | 20.24 | 3.31 | 3.41 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 47.56 | 5.93 | 41.63 | 119.11 | 122.02 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 107.40 | 60.54 | 46.87 | 121.32 | 198.72 | 0.00 | 0.00 | 0.00 |
February | 120.90 | 64.15 | 56.75 | 146.43 | 174.50 | 0.00 | 0.00 | 0.00 |
March | 164.97 | 88.46 | 76.51 | 219.22 | 143.72 | 0.00 | 0.00 | 0.00 |
April | 189.31 | 102.11 | 87.19 | 298.34 | 72.90 | 0.00 | 0.00 | 0.00 |
May | 204.29 | 109.33 | 94.96 | 364.01 | 34.40 | 0.00 | 0.00 | 0.00 |
June | 198.79 | 106.74 | 92.05 | 409.91 | 11.99 | 0.00 | 0.00 | 0.00 |
July | 176.54 | 87.72 | 88.82 | 370.21 | 6.43 | 0.00 | 0.00 | 0.00 |
August | 170.94 | 87.09 | 83.85 | 341.94 | 13.17 | 0.00 | 0.00 | 0.00 |
September | 175.49 | 97.97 | 77.52 | 322.60 | 39.96 | 0.00 | 0.00 | 0.00 |
October | 151.21 | 88.52 | 62.68 | 239.97 | 81.45 | 0.00 | 0.00 | 0.00 |
November | 126.16 | 76.76 | 49.40 | 161.33 | 162.71 | 0.00 | 0.00 | 0.00 |
December | 101.75 | 55.25 | 46.51 | 109.09 | 219.17 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 157.45 | 85.45 | 72.00 | 259.19 | 96.22 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 101.75 | 55.25 | 46.51 | 109.09 | 6.43 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 204.29 | 109.33 | 94.96 | 409.91 | 219.17 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 111.67 | 84.62 | 27.06 | 146.49 | 90.53 | 0.00 | 0.00 | 0.00 |
February | 105.07 | 74.51 | 30.55 | 140.85 | 80.39 | 0.00 | 0.00 | 0.00 |
March | 82.19 | 46.57 | 35.63 | 112.69 | 69.56 | 0.00 | 0.00 | 0.00 |
April | 57.27 | 21.50 | 35.77 | 92.09 | 39.61 | 0.00 | 0.00 | 0.00 |
May | 40.64 | 5.96 | 34.68 | 77.25 | 20.47 | 0.00 | 0.00 | 0.00 |
June | 34.76 | 2.19 | 32.58 | 85.74 | 8.32 | 0.00 | 0.00 | 0.00 |
July | 35.30 | 3.13 | 32.17 | 86.17 | 5.84 | 0.00 | 0.00 | 0.00 |
August | 44.56 | 11.32 | 33.24 | 98.52 | 9.88 | 0.00 | 0.00 | 0.00 |
September | 70.57 | 36.67 | 33.91 | 135.45 | 23.59 | 0.00 | 0.00 | 0.00 |
October | 96.87 | 65.81 | 31.06 | 154.43 | 42.97 | 0.00 | 0.00 | 0.00 |
November | 116.59 | 89.18 | 27.41 | 162.15 | 74.95 | 0.00 | 0.00 | 0.00 |
December | 114.65 | 86.13 | 28.51 | 148.10 | 95.80 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 75.67 | 43.79 | 31.89 | 119.83 | 46.66 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 34.76 | 2.19 | 27.06 | 77.25 | 5.84 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 116.59 | 89.18 | 35.77 | 162.15 | 95.80 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 16.32 | 0.00 | 16.32 | 3.19 | 92.12 | 0.00 | 0.00 | 0.00 |
February | 19.93 | 0.00 | 19.93 | 9.75 | 79.56 | 0.00 | 0.00 | 0.00 |
March | 26.09 | 0.00 | 26.09 | 20.52 | 64.10 | 0.00 | 0.00 | 0.00 |
April | 30.29 | 0.39 | 29.91 | 42.81 | 30.27 | 0.00 | 0.00 | 0.00 |
May | 35.78 | 2.64 | 33.15 | 71.80 | 12.97 | 0.00 | 0.00 | 0.00 |
June | 38.05 | 4.74 | 33.31 | 100.35 | 4.30 | 0.00 | 0.00 | 0.00 |
July | 35.16 | 3.45 | 31.71 | 93.80 | 2.20 | 0.00 | 0.00 | 0.00 |
August | 29.73 | 0.71 | 29.03 | 74.60 | 4.84 | 0.00 | 0.00 | 0.00 |
September | 25.87 | 0.03 | 25.84 | 54.20 | 15.96 | 0.00 | 0.00 | 0.00 |
October | 21.44 | 0.00 | 21.44 | 28.85 | 34.85 | 0.00 | 0.00 | 0.00 |
November | 17.31 | 0.00 | 17.31 | 7.49 | 73.85 | 0.00 | 0.00 | 0.00 |
December | 16.19 | 0.00 | 16.19 | 2.18 | 101.99 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 26.04 | 1.00 | 25.04 | 42.64 | 42.92 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 16.19 | 0.00 | 16.19 | 2.18 | 2.20 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 38.05 | 4.74 | 33.31 | 100.35 | 101.99 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.70 | 55.11 | 46.60 | 95.91 | 194.30 | 0.00 | 0.00 | 0.00 |
February | 136.50 | 77.83 | 58.67 | 153.65 | 166.90 | 0.00 | 0.00 | 0.00 |
March | 168.25 | 92.64 | 75.61 | 209.70 | 134.88 | 0.00 | 0.00 | 0.00 |
April | 202.82 | 112.49 | 90.33 | 311.73 | 66.80 | 0.00 | 0.00 | 0.00 |
May | 209.08 | 113.58 | 95.50 | 369.84 | 31.44 | 0.00 | 0.00 | 0.00 |
June | 209.17 | 116.31 | 92.86 | 427.67 | 11.17 | 0.00 | 0.00 | 0.00 |
July | 187.70 | 98.13 | 89.57 | 389.18 | 6.21 | 0.00 | 0.00 | 0.00 |
August | 178.80 | 91.56 | 87.24 | 354.66 | 12.60 | 0.00 | 0.00 | 0.00 |
September | 177.40 | 101.30 | 76.10 | 318.84 | 37.51 | 0.00 | 0.00 | 0.00 |
October | 135.78 | 73.14 | 62.64 | 202.60 | 78.58 | 0.00 | 0.00 | 0.00 |
November | 121.58 | 70.62 | 50.96 | 134.96 | 156.22 | 0.00 | 0.00 | 0.00 |
December | 101.78 | 53.93 | 47.85 | 91.56 | 213.42 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 160.90 | 88.01 | 72.89 | 255.38 | 92.16 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 101.70 | 53.93 | 46.60 | 91.56 | 6.21 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 209.17 | 116.31 | 95.50 | 427.67 | 213.42 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 139.62 | 105.79 | 33.83 | 189.18 | 98.71 | 0.00 | 0.00 | 0.00 |
February | 131.36 | 93.16 | 38.20 | 180.95 | 86.88 | 0.00 | 0.00 | 0.00 |
March | 102.76 | 58.22 | 44.54 | 144.93 | 75.14 | 0.00 | 0.00 | 0.00 |
April | 71.60 | 26.88 | 44.73 | 117.84 | 39.89 | 0.00 | 0.00 | 0.00 |
May | 50.81 | 7.45 | 43.36 | 99.88 | 18.49 | 0.00 | 0.00 | 0.00 |
June | 43.46 | 2.73 | 40.73 | 111.67 | 6.28 | 0.00 | 0.00 | 0.00 |
July | 44.14 | 3.91 | 40.22 | 113.01 | 3.43 | 0.00 | 0.00 | 0.00 |
August | 55.72 | 14.16 | 41.56 | 128.04 | 7.10 | 0.00 | 0.00 | 0.00 |
September | 88.23 | 45.84 | 42.39 | 172.43 | 21.40 | 0.00 | 0.00 | 0.00 |
October | 121.11 | 82.28 | 38.83 | 197.81 | 42.09 | 0.00 | 0.00 | 0.00 |
November | 145.77 | 111.49 | 34.27 | 207.78 | 80.52 | 0.00 | 0.00 | 0.00 |
December | 143.34 | 107.69 | 35.65 | 191.26 | 107.17 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 94.61 | 54.74 | 39.87 | 154.37 | 48.74 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 43.46 | 2.73 | 33.83 | 99.88 | 3.43 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 145.77 | 111.49 | 44.73 | 207.78 | 107.17 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.40 | 0.00 | 20.40 | 4.36 | 110.03 | 0.00 | 0.00 | 0.00 |
February | 24.91 | 0.00 | 24.91 | 11.52 | 96.73 | 0.00 | 0.00 | 0.00 |
March | 32.60 | 0.00 | 32.60 | 23.60 | 79.17 | 0.00 | 0.00 | 0.00 |
April | 37.86 | 0.48 | 37.38 | 48.59 | 38.61 | 0.00 | 0.00 | 0.00 |
May | 44.72 | 3.30 | 41.43 | 83.60 | 16.98 | 0.00 | 0.00 | 0.00 |
June | 47.56 | 5.93 | 41.63 | 118.32 | 6.06 | 0.00 | 0.00 | 0.00 |
July | 43.94 | 4.31 | 39.63 | 110.64 | 3.28 | 0.00 | 0.00 | 0.00 |
August | 37.16 | 0.88 | 36.28 | 87.04 | 6.75 | 0.00 | 0.00 | 0.00 |
September | 32.33 | 0.04 | 32.29 | 62.48 | 21.23 | 0.00 | 0.00 | 0.00 |
October | 26.80 | 0.00 | 26.80 | 33.08 | 43.61 | 0.00 | 0.00 | 0.00 |
November | 21.63 | 0.00 | 21.63 | 8.79 | 89.52 | 0.00 | 0.00 | 0.00 |
December | 20.24 | 0.00 | 20.24 | 2.98 | 121.94 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 32.55 | 1.25 | 31.30 | 49.79 | 52.62 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.24 | 0.00 | 20.24 | 2.98 | 3.28 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 47.56 | 5.93 | 41.63 | 118.32 | 121.94 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.70 | 55.11 | 46.60 | 101.06 | 186.36 | 0.00 | 0.00 | 0.00 |
February | 136.50 | 77.83 | 58.67 | 159.46 | 161.32 | 0.00 | 0.00 | 0.00 |
March | 168.25 | 92.64 | 75.61 | 214.45 | 131.99 | 0.00 | 0.00 | 0.00 |
April | 202.82 | 112.49 | 90.33 | 313.94 | 65.97 | 0.00 | 0.00 | 0.00 |
May | 209.08 | 113.58 | 95.50 | 370.36 | 31.31 | 0.00 | 0.00 | 0.00 |
June | 209.17 | 116.31 | 92.86 | 427.61 | 11.19 | 0.00 | 0.00 | 0.00 |
July | 187.70 | 98.13 | 89.57 | 389.36 | 6.19 | 0.00 | 0.00 | 0.00 |
August | 178.80 | 91.56 | 87.24 | 355.85 | 12.39 | 0.00 | 0.00 | 0.00 |
September | 177.40 | 101.30 | 76.10 | 321.56 | 36.54 | 0.00 | 0.00 | 0.00 |
October | 135.78 | 73.14 | 62.64 | 207.08 | 76.15 | 0.00 | 0.00 | 0.00 |
November | 121.58 | 70.62 | 50.96 | 141.18 | 150.14 | 0.00 | 0.00 | 0.00 |
December | 101.78 | 53.93 | 47.85 | 95.83 | 204.63 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 160.90 | 88.01 | 72.89 | 258.49 | 89.18 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 101.70 | 53.93 | 46.60 | 95.83 | 6.19 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 209.17 | 116.31 | 95.50 | 427.61 | 204.63 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 25.83 | 0.00 | 25.83 | 4.73 | 147.79 | 0.00 | 0.00 | 0.00 |
February | 31.55 | 0.00 | 31.55 | 15.53 | 126.70 | 0.00 | 0.00 | 0.00 |
March | 41.29 | 0.00 | 41.29 | 33.74 | 100.80 | 0.00 | 0.00 | 0.00 |
April | 47.95 | 0.61 | 47.34 | 71.78 | 46.99 | 0.00 | 0.00 | 0.00 |
May | 56.64 | 4.17 | 52.47 | 118.32 | 20.63 | 0.00 | 0.00 | 0.00 |
June | 60.23 | 7.51 | 52.73 | 160.57 | 7.76 | 0.00 | 0.00 | 0.00 |
July | 55.65 | 5.46 | 50.19 | 150.71 | 4.10 | 0.00 | 0.00 | 0.00 |
August | 47.06 | 1.12 | 45.94 | 120.03 | 8.49 | 0.00 | 0.00 | 0.00 |
September | 40.94 | 0.05 | 40.89 | 87.92 | 26.64 | 0.00 | 0.00 | 0.00 |
October | 33.94 | 0.00 | 33.94 | 47.37 | 54.96 | 0.00 | 0.00 | 0.00 |
November | 27.40 | 0.00 | 27.40 | 11.88 | 117.47 | 0.00 | 0.00 | 0.00 |
December | 25.63 | 0.00 | 25.63 | 3.20 | 164.57 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 41.22 | 1.58 | 39.64 | 69.10 | 68.64 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 25.63 | 0.00 | 25.63 | 3.20 | 4.10 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 60.23 | 7.51 | 52.73 | 160.57 | 164.57 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 9.52 | 0.00 | 9.52 | 1.74 | 54.48 | 0.00 | 0.00 | 0.00 |
February | 11.63 | 0.00 | 11.63 | 5.73 | 46.71 | 0.00 | 0.00 | 0.00 |
March | 15.22 | 0.00 | 15.22 | 12.44 | 37.16 | 0.00 | 0.00 | 0.00 |
April | 17.68 | 0.23 | 17.45 | 26.46 | 17.32 | 0.00 | 0.00 | 0.00 |
May | 20.88 | 1.54 | 19.34 | 43.62 | 7.61 | 0.00 | 0.00 | 0.00 |
June | 22.20 | 2.77 | 19.44 | 59.19 | 2.86 | 0.00 | 0.00 | 0.00 |
July | 20.51 | 2.01 | 18.50 | 55.56 | 1.51 | 0.00 | 0.00 | 0.00 |
August | 17.35 | 0.41 | 16.94 | 44.25 | 3.13 | 0.00 | 0.00 | 0.00 |
September | 15.09 | 0.02 | 15.07 | 32.41 | 9.82 | 0.00 | 0.00 | 0.00 |
October | 12.51 | 0.00 | 12.51 | 17.46 | 20.26 | 0.00 | 0.00 | 0.00 |
November | 10.10 | 0.00 | 10.10 | 4.38 | 43.31 | 0.00 | 0.00 | 0.00 |
December | 9.45 | 0.00 | 9.45 | 1.18 | 60.67 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 15.20 | 0.58 | 14.61 | 25.47 | 25.30 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 9.45 | 0.00 | 9.45 | 1.18 | 1.51 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 22.20 | 2.77 | 19.44 | 59.19 | 60.67 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 65.15 | 49.36 | 15.78 | 89.51 | 47.27 | 0.00 | 0.00 | 0.00 |
February | 61.29 | 43.47 | 17.82 | 86.59 | 40.97 | 0.00 | 0.00 | 0.00 |
March | 47.95 | 27.17 | 20.78 | 70.49 | 34.92 | 0.00 | 0.00 | 0.00 |
April | 33.41 | 12.54 | 20.87 | 59.32 | 17.75 | 0.00 | 0.00 | 0.00 |
May | 23.71 | 3.48 | 20.23 | 51.27 | 8.22 | 0.00 | 0.00 | 0.00 |
June | 20.28 | 1.28 | 19.00 | 56.06 | 2.98 | 0.00 | 0.00 | 0.00 |
July | 20.59 | 1.83 | 18.77 | 56.65 | 1.57 | 0.00 | 0.00 | 0.00 |
August | 26.00 | 6.60 | 19.39 | 63.58 | 3.25 | 0.00 | 0.00 | 0.00 |
September | 41.17 | 21.39 | 19.78 | 84.27 | 9.71 | 0.00 | 0.00 | 0.00 |
October | 56.51 | 38.39 | 18.12 | 95.57 | 19.16 | 0.00 | 0.00 | 0.00 |
November | 68.01 | 52.02 | 15.99 | 99.25 | 37.86 | 0.00 | 0.00 | 0.00 |
December | 66.88 | 50.25 | 16.63 | 90.17 | 51.40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 44.14 | 25.54 | 18.60 | 75.14 | 22.84 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.28 | 1.28 | 15.78 | 51.27 | 1.57 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 68.01 | 52.02 | 20.87 | 99.25 | 51.40 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 176.82 | 133.98 | 42.84 | 242.94 | 128.31 | 0.00 | 0.00 | 0.00 |
February | 166.36 | 117.98 | 48.38 | 235.02 | 111.20 | 0.00 | 0.00 | 0.00 |
March | 130.14 | 73.73 | 56.41 | 191.34 | 94.78 | 0.00 | 0.00 | 0.00 |
April | 90.68 | 34.04 | 56.64 | 161.01 | 48.18 | 0.00 | 0.00 | 0.00 |
May | 64.35 | 9.44 | 54.91 | 139.16 | 22.32 | 0.00 | 0.00 | 0.00 |
June | 55.04 | 3.46 | 51.58 | 152.16 | 8.08 | 0.00 | 0.00 | 0.00 |
July | 55.90 | 4.96 | 50.94 | 153.76 | 4.27 | 0.00 | 0.00 | 0.00 |
August | 70.56 | 17.93 | 52.63 | 172.56 | 8.81 | 0.00 | 0.00 | 0.00 |
September | 111.74 | 58.05 | 53.69 | 228.72 | 26.36 | 0.00 | 0.00 | 0.00 |
October | 153.38 | 104.21 | 49.17 | 259.41 | 52.00 | 0.00 | 0.00 | 0.00 |
November | 184.60 | 141.20 | 43.40 | 269.39 | 102.76 | 0.00 | 0.00 | 0.00 |
December | 181.53 | 136.38 | 45.15 | 244.74 | 139.51 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 119.82 | 69.33 | 50.49 | 203.94 | 61.99 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 55.04 | 3.46 | 42.84 | 139.16 | 4.27 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 184.60 | 141.20 | 56.64 | 269.39 | 139.51 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 139.62 | 105.79 | 33.83 | 188.69 | 98.21 | 0.00 | 0.00 | 0.00 |
February | 131.36 | 93.16 | 38.20 | 181.24 | 86.23 | 0.00 | 0.00 | 0.00 |
March | 102.76 | 58.22 | 44.54 | 144.98 | 75.06 | 0.00 | 0.00 | 0.00 |
April | 71.60 | 26.88 | 44.73 | 117.48 | 39.77 | 0.00 | 0.00 | 0.00 |
May | 50.81 | 7.45 | 43.36 | 99.33 | 18.50 | 0.00 | 0.00 | 0.00 |
June | 43.46 | 2.73 | 40.73 | 111.11 | 6.38 | 0.00 | 0.00 | 0.00 |
July | 44.14 | 3.91 | 40.22 | 111.86 | 3.60 | 0.00 | 0.00 | 0.00 |
August | 55.72 | 14.16 | 41.56 | 126.70 | 7.25 | 0.00 | 0.00 | 0.00 |
September | 88.23 | 45.84 | 42.39 | 170.84 | 21.66 | 0.00 | 0.00 | 0.00 |
October | 121.11 | 82.28 | 38.83 | 196.19 | 42.75 | 0.00 | 0.00 | 0.00 |
November | 145.77 | 111.49 | 34.27 | 207.20 | 80.41 | 0.00 | 0.00 | 0.00 |
December | 143.34 | 107.69 | 35.65 | 191.33 | 106.21 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 94.61 | 54.74 | 39.87 | 153.71 | 48.66 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 43.46 | 2.73 | 33.83 | 99.33 | 3.60 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 145.77 | 111.49 | 44.73 | 207.20 | 106.21 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 107.40 | 60.54 | 46.87 | 113.78 | 202.34 | 0.00 | 0.00 | 0.00 |
February | 120.90 | 64.15 | 56.75 | 138.45 | 177.33 | 0.00 | 0.00 | 0.00 |
March | 164.97 | 88.46 | 76.51 | 211.12 | 144.99 | 0.00 | 0.00 | 0.00 |
April | 189.31 | 102.11 | 87.19 | 291.54 | 73.28 | 0.00 | 0.00 | 0.00 |
May | 204.29 | 109.33 | 94.96 | 358.63 | 34.16 | 0.00 | 0.00 | 0.00 |
June | 198.79 | 106.74 | 92.05 | 405.59 | 11.88 | 0.00 | 0.00 | 0.00 |
July | 176.54 | 87.72 | 88.82 | 365.35 | 6.51 | 0.00 | 0.00 | 0.00 |
August | 170.94 | 87.09 | 83.85 | 336.25 | 13.43 | 0.00 | 0.00 | 0.00 |
September | 175.49 | 97.97 | 77.52 | 315.51 | 40.92 | 0.00 | 0.00 | 0.00 |
October | 151.21 | 88.52 | 62.68 | 232.02 | 83.52 | 0.00 | 0.00 | 0.00 |
November | 126.16 | 76.76 | 49.40 | 153.16 | 165.83 | 0.00 | 0.00 | 0.00 |
December | 101.75 | 55.25 | 46.51 | 102.29 | 222.28 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 157.45 | 85.45 | 72.00 | 252.47 | 97.66 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 101.75 | 55.25 | 46.51 | 102.29 | 6.51 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 204.29 | 109.33 | 94.96 | 405.59 | 222.28 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.40 | 0.00 | 20.40 | 4.89 | 108.88 | 0.00 | 0.00 | 0.00 |
February | 24.91 | 0.00 | 24.91 | 12.36 | 94.99 | 0.00 | 0.00 | 0.00 |
March | 32.60 | 0.00 | 32.60 | 24.51 | 78.27 | 0.00 | 0.00 | 0.00 |
April | 37.86 | 0.48 | 37.38 | 49.09 | 38.34 | 0.00 | 0.00 | 0.00 |
May | 44.72 | 3.30 | 41.43 | 83.31 | 17.09 | 0.00 | 0.00 | 0.00 |
June | 47.56 | 5.93 | 41.63 | 117.43 | 6.17 | 0.00 | 0.00 | 0.00 |
July | 43.94 | 4.31 | 39.63 | 109.36 | 3.44 | 0.00 | 0.00 | 0.00 |
August | 37.16 | 0.88 | 36.28 | 86.13 | 6.91 | 0.00 | 0.00 | 0.00 |
September | 32.33 | 0.04 | 32.29 | 61.83 | 21.38 | 0.00 | 0.00 | 0.00 |
October | 26.80 | 0.00 | 26.80 | 32.87 | 44.02 | 0.00 | 0.00 | 0.00 |
November | 21.63 | 0.00 | 21.63 | 9.18 | 89.13 | 0.00 | 0.00 | 0.00 |
December | 20.24 | 0.00 | 20.24 | 3.55 | 120.06 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 32.55 | 1.25 | 31.30 | 49.74 | 52.19 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.24 | 0.00 | 20.24 | 3.55 | 3.44 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 47.56 | 5.93 | 41.63 | 117.43 | 120.06 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 107.40 | 60.54 | 46.87 | 120.99 | 195.92 | 0.00 | 0.00 | 0.00 |
February | 120.90 | 64.15 | 56.75 | 145.37 | 172.18 | 0.00 | 0.00 | 0.00 |
March | 164.97 | 88.46 | 76.51 | 216.62 | 142.17 | 0.00 | 0.00 | 0.00 |
April | 189.31 | 102.11 | 87.19 | 294.06 | 72.38 | 0.00 | 0.00 | 0.00 |
May | 204.29 | 109.33 | 94.96 | 359.19 | 34.03 | 0.00 | 0.00 | 0.00 |
June | 198.79 | 106.74 | 92.05 | 405.43 | 11.89 | 0.00 | 0.00 | 0.00 |
July | 176.54 | 87.72 | 88.82 | 365.45 | 6.49 | 0.00 | 0.00 | 0.00 |
August | 170.94 | 87.09 | 83.85 | 337.47 | 13.20 | 0.00 | 0.00 | 0.00 |
September | 175.49 | 97.97 | 77.52 | 318.46 | 39.83 | 0.00 | 0.00 | 0.00 |
October | 151.21 | 88.52 | 62.68 | 236.94 | 80.94 | 0.00 | 0.00 | 0.00 |
November | 126.16 | 76.76 | 49.40 | 160.14 | 160.42 | 0.00 | 0.00 | 0.00 |
December | 101.75 | 55.25 | 46.51 | 109.31 | 215.65 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 157.45 | 85.45 | 72.00 | 256.27 | 95.06 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 101.75 | 55.25 | 46.51 | 109.31 | 6.49 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 204.29 | 109.33 | 94.96 | 405.43 | 215.65 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 204.76 | 155.16 | 49.61 | 268.88 | 151.08 | 0.00 | 0.00 | 0.00 |
February | 192.65 | 136.63 | 56.02 | 259.24 | 131.84 | 0.00 | 0.00 | 0.00 |
March | 150.71 | 85.38 | 65.33 | 208.97 | 112.06 | 0.00 | 0.00 | 0.00 |
April | 105.01 | 39.42 | 65.59 | 173.42 | 57.45 | 0.00 | 0.00 | 0.00 |
May | 74.52 | 10.93 | 63.59 | 150.44 | 25.74 | 0.00 | 0.00 | 0.00 |
June | 63.74 | 4.01 | 59.73 | 169.60 | 8.35 | 0.00 | 0.00 | 0.00 |
July | 64.73 | 5.74 | 58.99 | 170.03 | 4.52 | 0.00 | 0.00 | 0.00 |
August | 81.71 | 20.76 | 60.95 | 190.26 | 9.84 | 0.00 | 0.00 | 0.00 |
September | 129.40 | 67.23 | 62.17 | 252.26 | 30.80 | 0.00 | 0.00 | 0.00 |
October | 177.62 | 120.68 | 56.94 | 286.04 | 63.51 | 0.00 | 0.00 | 0.00 |
November | 213.78 | 163.52 | 50.26 | 298.39 | 122.48 | 0.00 | 0.00 | 0.00 |
December | 210.22 | 157.93 | 52.28 | 271.78 | 163.29 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 138.75 | 80.29 | 58.47 | 224.68 | 73.14 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 63.74 | 4.01 | 49.61 | 150.44 | 4.52 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 213.78 | 163.52 | 65.59 | 298.39 | 163.29 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 142.78 | 0.00 | 142.78 | 22.01 | 833.95 | 0.00 | 0.00 | 0.00 |
February | 174.35 | 0.00 | 174.35 | 78.75 | 719.40 | 0.00 | 0.00 | 0.00 |
March | 228.22 | 0.01 | 228.21 | 172.70 | 582.26 | 0.00 | 0.00 | 0.00 |
April | 265.01 | 3.38 | 261.64 | 376.51 | 287.99 | 0.00 | 0.00 | 0.00 |
May | 313.05 | 23.07 | 289.98 | 630.36 | 135.37 | 0.00 | 0.00 | 0.00 |
June | 332.91 | 41.48 | 291.42 | 869.43 | 54.64 | 0.00 | 0.00 | 0.00 |
July | 307.56 | 30.17 | 277.39 | 810.61 | 33.78 | 0.00 | 0.00 | 0.00 |
August | 260.12 | 6.19 | 253.93 | 648.77 | 61.88 | 0.00 | 0.00 | 0.00 |
September | 226.30 | 0.29 | 226.02 | 480.93 | 161.47 | 0.00 | 0.00 | 0.00 |
October | 187.59 | 0.00 | 187.59 | 251.87 | 326.31 | 0.00 | 0.00 | 0.00 |
November | 151.44 | 0.00 | 151.44 | 59.23 | 667.75 | 0.00 | 0.00 | 0.00 |
December | 141.68 | 0.00 | 141.68 | 15.24 | 918.11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 227.84 | 8.76 | 219.09 | 369.55 | 397.10 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 141.68 | 0.00 | 141.68 | 15.24 | 33.78 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 332.91 | 41.48 | 291.42 | 869.43 | 918.11 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 142.78 | 0.00 | 142.78 | 19.89 | 850.73 | 0.00 | 0.00 | 0.00 |
February | 174.35 | 0.00 | 174.35 | 75.05 | 735.06 | 0.00 | 0.00 | 0.00 |
March | 228.22 | 0.01 | 228.21 | 166.72 | 596.59 | 0.00 | 0.00 | 0.00 |
April | 265.01 | 3.38 | 261.64 | 366.52 | 299.43 | 0.00 | 0.00 | 0.00 |
May | 313.05 | 23.07 | 289.98 | 616.07 | 143.68 | 0.00 | 0.00 | 0.00 |
June | 332.91 | 41.48 | 291.42 | 853.20 | 59.27 | 0.00 | 0.00 | 0.00 |
July | 307.56 | 30.17 | 277.39 | 794.30 | 38.23 | 0.00 | 0.00 | 0.00 |
August | 260.12 | 6.19 | 253.93 | 634.14 | 67.82 | 0.00 | 0.00 | 0.00 |
September | 226.30 | 0.29 | 226.02 | 470.36 | 170.73 | 0.00 | 0.00 | 0.00 |
October | 187.59 | 0.00 | 187.59 | 244.52 | 338.74 | 0.00 | 0.00 | 0.00 |
November | 151.44 | 0.00 | 151.44 | 55.69 | 683.34 | 0.00 | 0.00 | 0.00 |
December | 141.68 | 0.00 | 141.68 | 13.80 | 935.16 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 227.84 | 8.76 | 219.09 | 360.68 | 408.39 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 141.68 | 0.00 | 141.68 | 13.80 | 38.23 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 332.91 | 41.48 | 291.42 | 853.20 | 935.16 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.40 | 0.00 | 20.40 | 3.46 | 120.72 | 0.00 | 0.00 | 0.00 |
February | 24.91 | 0.00 | 24.91 | 12.11 | 105.56 | 0.00 | 0.00 | 0.00 |
March | 32.60 | 0.00 | 32.60 | 25.08 | 87.00 | 0.00 | 0.00 | 0.00 |
April | 37.86 | 0.48 | 37.38 | 55.84 | 44.84 | 0.00 | 0.00 | 0.00 |
May | 44.72 | 3.30 | 41.43 | 92.74 | 22.58 | 0.00 | 0.00 | 0.00 |
June | 47.56 | 5.93 | 41.63 | 128.76 | 9.23 | 0.00 | 0.00 | 0.00 |
July | 43.94 | 4.31 | 39.63 | 121.35 | 6.42 | 0.00 | 0.00 | 0.00 |
August | 37.16 | 0.88 | 36.28 | 97.88 | 10.76 | 0.00 | 0.00 | 0.00 |
September | 32.33 | 0.04 | 32.29 | 74.31 | 24.97 | 0.00 | 0.00 | 0.00 |
October | 26.80 | 0.00 | 26.80 | 38.84 | 49.61 | 0.00 | 0.00 | 0.00 |
November | 21.63 | 0.00 | 21.63 | 9.45 | 97.76 | 0.00 | 0.00 | 0.00 |
December | 20.24 | 0.00 | 20.24 | 2.53 | 131.04 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 32.55 | 1.25 | 31.30 | 55.42 | 58.99 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.24 | 0.00 | 20.24 | 2.53 | 6.42 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 47.56 | 5.93 | 41.63 | 128.76 | 131.04 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 203.40 | 110.21 | 93.19 | 200.52 | 412.25 | 0.00 | 0.00 | 0.00 |
February | 272.98 | 155.65 | 117.32 | 325.67 | 358.06 | 0.00 | 0.00 | 0.00 |
March | 336.47 | 185.26 | 151.21 | 440.90 | 295.05 | 0.00 | 0.00 | 0.00 |
April | 405.62 | 224.97 | 180.65 | 658.12 | 157.66 | 0.00 | 0.00 | 0.00 |
May | 418.14 | 227.15 | 190.99 | 774.57 | 84.02 | 0.00 | 0.00 | 0.00 |
June | 418.31 | 232.60 | 185.71 | 892.04 | 34.52 | 0.00 | 0.00 | 0.00 |
July | 375.38 | 196.25 | 179.13 | 816.06 | 24.56 | 0.00 | 0.00 | 0.00 |
August | 357.58 | 183.11 | 174.47 | 750.73 | 40.43 | 0.00 | 0.00 | 0.00 |
September | 354.77 | 202.59 | 152.18 | 688.93 | 89.92 | 0.00 | 0.00 | 0.00 |
October | 271.54 | 146.27 | 125.28 | 437.90 | 176.80 | 0.00 | 0.00 | 0.00 |
November | 243.14 | 141.22 | 101.92 | 288.57 | 332.49 | 0.00 | 0.00 | 0.00 |
December | 203.55 | 107.86 | 95.69 | 193.47 | 445.74 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 321.77 | 176.00 | 145.77 | 539.69 | 203.58 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 203.40 | 107.86 | 93.19 | 193.47 | 24.56 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 418.31 | 232.60 | 190.99 | 892.04 | 445.74 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 139.62 | 105.79 | 33.83 | 193.84 | 105.81 | 0.00 | 0.00 | 0.00 |
February | 131.36 | 93.16 | 38.20 | 186.89 | 93.68 | 0.00 | 0.00 | 0.00 |
March | 102.76 | 58.22 | 44.54 | 150.51 | 81.50 | 0.00 | 0.00 | 0.00 |
April | 71.60 | 26.88 | 44.73 | 125.63 | 45.51 | 0.00 | 0.00 | 0.00 |
May | 50.81 | 7.45 | 43.36 | 108.01 | 23.73 | 0.00 | 0.00 | 0.00 |
June | 43.46 | 2.73 | 40.73 | 121.53 | 9.36 | 0.00 | 0.00 | 0.00 |
July | 44.14 | 3.91 | 40.22 | 123.38 | 6.54 | 0.00 | 0.00 | 0.00 |
August | 55.72 | 14.16 | 41.56 | 139.27 | 10.93 | 0.00 | 0.00 | 0.00 |
September | 88.23 | 45.84 | 42.39 | 185.62 | 24.83 | 0.00 | 0.00 | 0.00 |
October | 121.11 | 82.28 | 38.83 | 207.15 | 47.20 | 0.00 | 0.00 | 0.00 |
November | 145.77 | 111.49 | 34.27 | 215.11 | 86.22 | 0.00 | 0.00 | 0.00 |
December | 143.34 | 107.69 | 35.65 | 196.65 | 112.92 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 94.61 | 54.74 | 39.87 | 162.61 | 53.83 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 43.46 | 2.73 | 33.83 | 108.01 | 6.54 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 145.77 | 111.49 | 44.73 | 215.11 | 112.92 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 25.83 | 0.00 | 25.83 | 4.04 | 149.15 | 0.00 | 0.00 | 0.00 |
February | 31.55 | 0.00 | 31.55 | 14.36 | 127.64 | 0.00 | 0.00 | 0.00 |
March | 41.29 | 0.00 | 41.29 | 31.98 | 101.49 | 0.00 | 0.00 | 0.00 |
April | 47.95 | 0.61 | 47.34 | 69.50 | 47.02 | 0.00 | 0.00 | 0.00 |
May | 56.64 | 4.17 | 52.47 | 117.32 | 19.72 | 0.00 | 0.00 | 0.00 |
June | 60.23 | 7.51 | 52.73 | 160.28 | 6.91 | 0.00 | 0.00 | 0.00 |
July | 55.65 | 5.46 | 50.19 | 149.89 | 3.57 | 0.00 | 0.00 | 0.00 |
August | 47.06 | 1.12 | 45.94 | 119.48 | 7.70 | 0.00 | 0.00 | 0.00 |
September | 40.94 | 0.05 | 40.89 | 86.85 | 25.07 | 0.00 | 0.00 | 0.00 |
October | 33.94 | 0.00 | 33.94 | 45.61 | 54.82 | 0.00 | 0.00 | 0.00 |
November | 27.40 | 0.00 | 27.40 | 10.68 | 118.40 | 0.00 | 0.00 | 0.00 |
December | 25.63 | 0.00 | 25.63 | 2.81 | 165.33 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 41.22 | 1.58 | 39.64 | 68.02 | 68.63 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 25.63 | 0.00 | 25.63 | 2.81 | 3.57 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 60.23 | 7.51 | 52.73 | 160.28 | 165.33 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.11 | 0.00 | 23.11 | 3.62 | 133.45 | 0.00 | 0.00 | 0.00 |
February | 28.22 | 0.00 | 28.22 | 12.85 | 114.20 | 0.00 | 0.00 | 0.00 |
March | 36.94 | 0.00 | 36.94 | 28.61 | 90.80 | 0.00 | 0.00 | 0.00 |
April | 42.90 | 0.55 | 42.35 | 62.18 | 42.07 | 0.00 | 0.00 | 0.00 |
May | 50.68 | 3.73 | 46.94 | 104.96 | 17.64 | 0.00 | 0.00 | 0.00 |
June | 53.89 | 6.72 | 47.17 | 143.40 | 6.18 | 0.00 | 0.00 | 0.00 |
July | 49.79 | 4.88 | 44.90 | 134.11 | 3.20 | 0.00 | 0.00 | 0.00 |
August | 42.11 | 1.00 | 41.11 | 106.90 | 6.89 | 0.00 | 0.00 | 0.00 |
September | 36.63 | 0.05 | 36.59 | 77.70 | 22.43 | 0.00 | 0.00 | 0.00 |
October | 30.37 | 0.00 | 30.37 | 40.81 | 49.05 | 0.00 | 0.00 | 0.00 |
November | 24.51 | 0.00 | 24.51 | 9.55 | 105.94 | 0.00 | 0.00 | 0.00 |
December | 22.93 | 0.00 | 22.93 | 2.51 | 147.92 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 36.88 | 1.42 | 35.46 | 60.86 | 61.41 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 22.93 | 0.00 | 22.93 | 2.51 | 3.20 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 53.89 | 6.72 | 47.17 | 143.40 | 147.92 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 521.24 | 394.96 | 126.28 | 706.57 | 379.97 | 0.00 | 0.00 | 0.00 |
February | 490.41 | 347.79 | 142.61 | 683.01 | 329.63 | 0.00 | 0.00 | 0.00 |
March | 383.64 | 217.35 | 166.29 | 553.33 | 281.15 | 0.00 | 0.00 | 0.00 |
April | 267.32 | 100.35 | 166.97 | 464.96 | 142.38 | 0.00 | 0.00 | 0.00 |
May | 189.70 | 27.82 | 161.88 | 406.70 | 63.27 | 0.00 | 0.00 | 0.00 |
June | 162.26 | 10.21 | 152.05 | 448.20 | 21.22 | 0.00 | 0.00 | 0.00 |
July | 164.78 | 14.61 | 150.17 | 450.84 | 11.08 | 0.00 | 0.00 | 0.00 |
August | 208.00 | 52.85 | 155.16 | 505.48 | 23.66 | 0.00 | 0.00 | 0.00 |
September | 329.40 | 171.14 | 158.26 | 668.32 | 73.31 | 0.00 | 0.00 | 0.00 |
October | 452.15 | 307.19 | 144.96 | 754.91 | 153.04 | 0.00 | 0.00 | 0.00 |
November | 544.19 | 416.24 | 127.94 | 784.50 | 304.18 | 0.00 | 0.00 | 0.00 |
December | 535.12 | 402.02 | 133.09 | 713.65 | 411.26 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 353.20 | 204.38 | 148.83 | 594.35 | 182.16 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 162.26 | 10.21 | 126.28 | 406.70 | 11.08 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 544.19 | 416.24 | 166.97 | 784.50 | 411.26 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.189136E+10 | 0.143314E+10 | 0.458222E+09 | 0.258816E+10 | 0.130800E+10 |
February | 0.160727E+10 | 0.113986E+10 | 0.467406E+09 | 0.225428E+10 | 0.103261E+10 |
March | 0.139207E+10 | 0.788679E+09 | 0.603391E+09 | 0.203523E+10 | 0.982449E+09 |
April | 0.938702E+09 | 0.352379E+09 | 0.586322E+09 | 0.161818E+10 | 0.501597E+09 |
May | 0.688337E+09 | 0.100947E+09 | 0.587390E+09 | 0.141762E+10 | 0.245247E+09 |
June | 0.569764E+09 | 35850177.24 | 0.533914E+09 | 0.149862E+10 | 82013881.80 |
July | 0.597898E+09 | 53010019.83 | 0.544888E+09 | 0.157418E+10 | 44653482.94 |
August | 0.754750E+09 | 0.191758E+09 | 0.562992E+09 | 0.177540E+10 | 94511521.45 |
September | 0.115668E+10 | 0.600953E+09 | 0.555729E+09 | 0.229640E+10 | 0.275052E+09 |
October | 0.164065E+10 | 0.111467E+10 | 0.525978E+09 | 0.270903E+10 | 0.561119E+09 |
November | 0.191093E+10 | 0.146165E+10 | 0.449279E+09 | 0.274745E+10 | 0.103556E+10 |
December | 0.194172E+10 | 0.145878E+10 | 0.482936E+09 | 0.260205E+10 | 0.142276E+10 |
Annual Sum or Average | 0.150901E+11 | 0.873168E+10 | 0.635845E+10 | 0.251166E+11 | 0.758558E+10 |
Minimum of Months | 0.569764E+09 | 35850177.24 | 0.449279E+09 | 0.141762E+10 | 44653482.94 |
Maximum of Months | 0.194172E+10 | 0.146165E+10 | 0.603391E+09 | 0.274745E+10 | 0.142276E+10 |
Report: WindowEnergyReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.532594E+10 | 0.403562E+10 | 0.129032E+10 | 0.724458E+10 | 0.371595E+10 |
February | 0.452597E+10 | 0.320978E+10 | 0.131618E+10 | 0.630826E+10 | 0.293298E+10 |
March | 0.391998E+10 | 0.222087E+10 | 0.169911E+10 | 0.568757E+10 | 0.278840E+10 |
April | 0.264332E+10 | 0.992277E+09 | 0.165105E+10 | 0.452198E+10 | 0.144465E+10 |
May | 0.193831E+10 | 0.284261E+09 | 0.165405E+10 | 0.394869E+10 | 0.728519E+09 |
June | 0.160442E+10 | 0.100952E+09 | 0.150347E+10 | 0.417120E+10 | 0.264166E+09 |
July | 0.168364E+10 | 0.149273E+09 | 0.153437E+10 | 0.437894E+10 | 0.156202E+09 |
August | 0.212533E+10 | 0.539978E+09 | 0.158535E+10 | 0.496111E+10 | 0.309958E+09 |
September | 0.325714E+10 | 0.169224E+10 | 0.156490E+10 | 0.645915E+10 | 0.815853E+09 |
October | 0.461996E+10 | 0.313884E+10 | 0.148112E+10 | 0.760725E+10 | 0.162097E+10 |
November | 0.538106E+10 | 0.411592E+10 | 0.126514E+10 | 0.770236E+10 | 0.294343E+10 |
December | 0.546774E+10 | 0.410783E+10 | 0.135992E+10 | 0.727685E+10 | 0.403535E+10 |
Annual Sum or Average | 0.424928E+11 | 0.245878E+11 | 0.179050E+11 | 0.702679E+11 | 0.217564E+11 |
Minimum of Months | 0.160442E+10 | 0.100952E+09 | 0.126514E+10 | 0.394869E+10 | 0.156202E+09 |
Maximum of Months | 0.546774E+10 | 0.411592E+10 | 0.169911E+10 | 0.770236E+10 | 0.403535E+10 |
Report: WindowEnergyReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.691870E+10 | 0.524250E+10 | 0.167620E+10 | 0.959853E+10 | 0.492615E+10 |
February | 0.587949E+10 | 0.416969E+10 | 0.170980E+10 | 0.837378E+10 | 0.388520E+10 |
March | 0.509227E+10 | 0.288503E+10 | 0.220724E+10 | 0.755747E+10 | 0.371203E+10 |
April | 0.343383E+10 | 0.128902E+10 | 0.214480E+10 | 0.604235E+10 | 0.192327E+10 |
May | 0.251798E+10 | 0.369271E+09 | 0.214871E+10 | 0.529535E+10 | 0.975347E+09 |
June | 0.208423E+10 | 0.131142E+09 | 0.195309E+10 | 0.561147E+10 | 0.348151E+09 |
July | 0.218715E+10 | 0.193914E+09 | 0.199323E+10 | 0.588539E+10 | 0.203047E+09 |
August | 0.276092E+10 | 0.701462E+09 | 0.205946E+10 | 0.666340E+10 | 0.399334E+09 |
September | 0.423121E+10 | 0.219832E+10 | 0.203289E+10 | 0.865174E+10 | 0.105299E+10 |
October | 0.600158E+10 | 0.407753E+10 | 0.192406E+10 | 0.101593E+11 | 0.210967E+10 |
November | 0.699030E+10 | 0.534681E+10 | 0.164349E+10 | 0.102434E+11 | 0.388016E+10 |
December | 0.710291E+10 | 0.533630E+10 | 0.176661E+10 | 0.963056E+10 | 0.535873E+10 |
Annual Sum or Average | 0.552006E+11 | 0.319410E+11 | 0.232596E+11 | 0.937127E+11 | 0.287741E+11 |
Minimum of Months | 0.208423E+10 | 0.131142E+09 | 0.164349E+10 | 0.529535E+10 | 0.203047E+09 |
Maximum of Months | 0.710291E+10 | 0.534681E+10 | 0.220724E+10 | 0.102434E+11 | 0.535873E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.373955E+09 | 0.283356E+09 | 90599047.15 | 0.508271E+09 | 0.265975E+09 |
February | 0.317786E+09 | 0.225371E+09 | 92415031.30 | 0.441696E+09 | 0.210668E+09 |
March | 0.275237E+09 | 0.155935E+09 | 0.119302E+09 | 0.392950E+09 | 0.202528E+09 |
April | 0.185599E+09 | 69671463.64 | 0.115927E+09 | 0.309751E+09 | 0.103634E+09 |
May | 0.136098E+09 | 19958985.63 | 0.116139E+09 | 0.270522E+09 | 50062393.52 |
June | 0.112654E+09 | 7088195.76 | 0.105566E+09 | 0.291726E+09 | 16753099.85 |
July | 0.118216E+09 | 10480991.36 | 0.107735E+09 | 0.304593E+09 | 9567278.48 |
August | 0.149228E+09 | 37913864.16 | 0.111315E+09 | 0.344646E+09 | 19390097.41 |
September | 0.228697E+09 | 0.118819E+09 | 0.109878E+09 | 0.448758E+09 | 56262493.37 |
October | 0.324385E+09 | 0.220389E+09 | 0.103996E+09 | 0.531284E+09 | 0.114781E+09 |
November | 0.377825E+09 | 0.288994E+09 | 88830943.98 | 0.540785E+09 | 0.210345E+09 |
December | 0.383911E+09 | 0.288426E+09 | 95485408.74 | 0.514012E+09 | 0.288112E+09 |
Annual Sum or Average | 0.298359E+10 | 0.172640E+10 | 0.125719E+10 | 0.489899E+10 | 0.154808E+10 |
Minimum of Months | 0.112654E+09 | 7088195.76 | 88830943.98 | 0.270522E+09 | 9567278.48 |
Maximum of Months | 0.383911E+09 | 0.288994E+09 | 0.119302E+09 | 0.540785E+09 | 0.288112E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.287674E+09 | 0.162146E+09 | 0.125527E+09 | 0.307411E+09 | 0.548951E+09 |
February | 0.292474E+09 | 0.155192E+09 | 0.137282E+09 | 0.338817E+09 | 0.434077E+09 |
March | 0.441845E+09 | 0.236918E+09 | 0.204927E+09 | 0.573288E+09 | 0.392160E+09 |
April | 0.490686E+09 | 0.264679E+09 | 0.226007E+09 | 0.766568E+09 | 0.191250E+09 |
May | 0.547180E+09 | 0.292832E+09 | 0.254348E+09 | 0.973346E+09 | 92506060.41 |
June | 0.515254E+09 | 0.276659E+09 | 0.238595E+09 | 0.106288E+10 | 31054631.99 |
July | 0.472844E+09 | 0.234945E+09 | 0.237900E+09 | 0.991248E+09 | 17279522.59 |
August | 0.457839E+09 | 0.233254E+09 | 0.224585E+09 | 0.912480E+09 | 35851187.08 |
September | 0.454872E+09 | 0.253932E+09 | 0.200940E+09 | 0.828485E+09 | 0.106296E+09 |
October | 0.404989E+09 | 0.237094E+09 | 0.167895E+09 | 0.629678E+09 | 0.224729E+09 |
November | 0.327016E+09 | 0.198972E+09 | 0.128044E+09 | 0.401485E+09 | 0.434769E+09 |
December | 0.272539E+09 | 0.147971E+09 | 0.124568E+09 | 0.275101E+09 | 0.604667E+09 |
Annual Sum or Average | 0.496521E+10 | 0.269459E+10 | 0.227062E+10 | 0.806078E+10 | 0.311359E+10 |
Minimum of Months | 0.272539E+09 | 0.147971E+09 | 0.124568E+09 | 0.275101E+09 | 17279522.59 |
Maximum of Months | 0.547180E+09 | 0.292832E+09 | 0.254348E+09 | 0.106288E+10 | 0.604667E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54635219.79 | 0.00 | 54635219.79 | 12456338.71 | 0.295746E+09 |
February | 60259072.44 | 0.00 | 60259072.44 | 29807186.92 | 0.232806E+09 |
March | 87327152.96 | 3456.98 | 87323695.98 | 66565134.46 | 0.211612E+09 |
April | 98134921.78 | 1250183.62 | 96884738.16 | 0.130495E+09 | 99904764.61 |
May | 0.119788E+09 | 8827959.99 | 0.110960E+09 | 0.227309E+09 | 46229148.27 |
June | 0.123276E+09 | 15361483.16 | 0.107914E+09 | 0.308742E+09 | 16149571.49 |
July | 0.117686E+09 | 11543657.45 | 0.106142E+09 | 0.298100E+09 | 9132226.64 |
August | 99533259.29 | 2367984.07 | 97165275.22 | 0.235058E+09 | 18473178.00 |
September | 83800633.79 | 105909.72 | 83694724.07 | 0.164123E+09 | 55570941.11 |
October | 71778804.06 | 0.00 | 71778804.06 | 90489365.94 | 0.118435E+09 |
November | 56077421.72 | 0.00 | 56077421.72 | 23885947.42 | 0.233700E+09 |
December | 54212081.06 | 0.00 | 54212081.06 | 8862810.98 | 0.326813E+09 |
Annual Sum or Average | 0.102651E+10 | 39460634.99 | 0.987047E+09 | 0.159589E+10 | 0.166457E+10 |
Minimum of Months | 54212081.06 | 0.00 | 54212081.06 | 8862810.98 | 9132226.64 |
Maximum of Months | 0.123276E+09 | 15361483.16 | 0.110960E+09 | 0.308742E+09 | 0.326813E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.287674E+09 | 0.162146E+09 | 0.125527E+09 | 0.324951E+09 | 0.532255E+09 |
February | 0.292474E+09 | 0.155192E+09 | 0.137282E+09 | 0.354255E+09 | 0.422159E+09 |
March | 0.441845E+09 | 0.236918E+09 | 0.204927E+09 | 0.587163E+09 | 0.384934E+09 |
April | 0.490686E+09 | 0.264679E+09 | 0.226007E+09 | 0.773299E+09 | 0.188959E+09 |
May | 0.547180E+09 | 0.292832E+09 | 0.254348E+09 | 0.974969E+09 | 92124443.53 |
June | 0.515254E+09 | 0.276659E+09 | 0.238595E+09 | 0.106250E+10 | 31077433.16 |
July | 0.472844E+09 | 0.234945E+09 | 0.237900E+09 | 0.991558E+09 | 17219117.19 |
August | 0.457839E+09 | 0.233254E+09 | 0.224585E+09 | 0.915843E+09 | 35262350.48 |
September | 0.454872E+09 | 0.253932E+09 | 0.200940E+09 | 0.836177E+09 | 0.103565E+09 |
October | 0.404989E+09 | 0.237094E+09 | 0.167895E+09 | 0.642727E+09 | 0.218155E+09 |
November | 0.327016E+09 | 0.198972E+09 | 0.128044E+09 | 0.418159E+09 | 0.421743E+09 |
December | 0.272539E+09 | 0.147971E+09 | 0.124568E+09 | 0.292187E+09 | 0.587020E+09 |
Annual Sum or Average | 0.496521E+10 | 0.269459E+10 | 0.227062E+10 | 0.817379E+10 | 0.303447E+10 |
Minimum of Months | 0.272539E+09 | 0.147971E+09 | 0.124568E+09 | 0.292187E+09 | 17219117.19 |
Maximum of Months | 0.547180E+09 | 0.292832E+09 | 0.254348E+09 | 0.106250E+10 | 0.587020E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.299104E+09 | 0.226640E+09 | 72464826.42 | 0.392345E+09 | 0.242469E+09 |
February | 0.254178E+09 | 0.180261E+09 | 73917324.87 | 0.340752E+09 | 0.194475E+09 |
March | 0.220146E+09 | 0.124724E+09 | 95422629.83 | 0.301824E+09 | 0.186310E+09 |
April | 0.148450E+09 | 55726088.50 | 92723544.22 | 0.238688E+09 | 0.102672E+09 |
May | 0.108857E+09 | 15964013.69 | 92892545.85 | 0.206902E+09 | 54827301.07 |
June | 90105188.78 | 5669429.11 | 84435759.67 | 0.222227E+09 | 21556791.11 |
July | 94554156.30 | 8383125.91 | 86171030.39 | 0.230796E+09 | 15651122.90 |
August | 0.119359E+09 | 30325060.49 | 89033931.16 | 0.263875E+09 | 26472808.71 |
September | 0.182921E+09 | 95036114.58 | 87885276.20 | 0.351092E+09 | 61150568.20 |
October | 0.259457E+09 | 0.176276E+09 | 83180150.54 | 0.413633E+09 | 0.115086E+09 |
November | 0.302200E+09 | 0.231149E+09 | 71050625.13 | 0.420291E+09 | 0.194276E+09 |
December | 0.307068E+09 | 0.230695E+09 | 76373138.43 | 0.396671E+09 | 0.256603E+09 |
Annual Sum or Average | 0.238640E+10 | 0.138085E+10 | 0.100555E+10 | 0.377909E+10 | 0.147155E+10 |
Minimum of Months | 90105188.78 | 5669429.11 | 71050625.13 | 0.206902E+09 | 15651122.90 |
Maximum of Months | 0.307068E+09 | 0.231149E+09 | 95422629.83 | 0.420291E+09 | 0.256603E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 43713969.60 | 0.00 | 43713969.60 | 8540331.93 | 0.246730E+09 |
February | 48213648.10 | 0.00 | 48213648.10 | 23580161.30 | 0.192480E+09 |
March | 69870982.94 | 2765.95 | 69868216.99 | 54959432.08 | 0.171676E+09 |
April | 78518344.10 | 1000279.47 | 77518064.63 | 0.110964E+09 | 78461667.44 |
May | 95843144.60 | 7063304.15 | 88779840.45 | 0.192312E+09 | 34732635.61 |
June | 98633813.54 | 12290815.53 | 86342998.01 | 0.260101E+09 | 11158549.39 |
July | 94160895.41 | 9236150.10 | 84924745.31 | 0.251240E+09 | 5897204.96 |
August | 79637162.39 | 1894638.37 | 77742524.03 | 0.199808E+09 | 12967140.09 |
September | 67049393.63 | 84739.01 | 66964654.62 | 0.140499E+09 | 41355941.49 |
October | 57430655.00 | 0.00 | 57430655.00 | 77280343.79 | 93349095.14 |
November | 44867884.08 | 0.00 | 44867884.08 | 19424185.98 | 0.191420E+09 |
December | 43375413.74 | 0.00 | 43375413.74 | 5836933.57 | 0.273183E+09 |
Annual Sum or Average | 0.821315E+09 | 31572692.58 | 0.789743E+09 | 0.134455E+10 | 0.135341E+10 |
Minimum of Months | 43375413.74 | 0.00 | 43375413.74 | 5836933.57 | 5897204.96 |
Maximum of Months | 98633813.54 | 12290815.53 | 88779840.45 | 0.260101E+09 | 0.273183E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.272406E+09 | 0.147604E+09 | 0.124803E+09 | 0.256882E+09 | 0.520408E+09 |
February | 0.330219E+09 | 0.188293E+09 | 0.141926E+09 | 0.371702E+09 | 0.403759E+09 |
March | 0.450634E+09 | 0.248122E+09 | 0.202511E+09 | 0.561662E+09 | 0.361266E+09 |
April | 0.525720E+09 | 0.291582E+09 | 0.234138E+09 | 0.808000E+09 | 0.173156E+09 |
May | 0.560008E+09 | 0.304221E+09 | 0.255786E+09 | 0.990592E+09 | 84197288.95 |
June | 0.542173E+09 | 0.301473E+09 | 0.240700E+09 | 0.110851E+10 | 28959251.99 |
July | 0.502747E+09 | 0.262839E+09 | 0.239908E+09 | 0.104238E+10 | 16628024.76 |
August | 0.478911E+09 | 0.245239E+09 | 0.233671E+09 | 0.949913E+09 | 33743195.45 |
September | 0.459814E+09 | 0.262571E+09 | 0.197243E+09 | 0.826435E+09 | 97230984.79 |
October | 0.363675E+09 | 0.195894E+09 | 0.167781E+09 | 0.542644E+09 | 0.210482E+09 |
November | 0.315129E+09 | 0.183035E+09 | 0.132093E+09 | 0.349813E+09 | 0.404922E+09 |
December | 0.272612E+09 | 0.144459E+09 | 0.128153E+09 | 0.245240E+09 | 0.571621E+09 |
Annual Sum or Average | 0.507405E+10 | 0.277533E+10 | 0.229871E+10 | 0.805377E+10 | 0.290637E+10 |
Minimum of Months | 0.272406E+09 | 0.144459E+09 | 0.124803E+09 | 0.245240E+09 | 16628024.76 |
Maximum of Months | 0.560008E+09 | 0.304221E+09 | 0.255786E+09 | 0.110851E+10 | 0.571621E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.373955E+09 | 0.283356E+09 | 90599047.15 | 0.506693E+09 | 0.264396E+09 |
February | 0.317786E+09 | 0.225371E+09 | 92415031.30 | 0.437743E+09 | 0.210173E+09 |
March | 0.275237E+09 | 0.155935E+09 | 0.119302E+09 | 0.388187E+09 | 0.201265E+09 |
April | 0.185599E+09 | 69671463.64 | 0.115927E+09 | 0.305440E+09 | 0.103389E+09 |
May | 0.136098E+09 | 19958985.63 | 0.116139E+09 | 0.267531E+09 | 49522068.02 |
June | 0.112654E+09 | 7088195.76 | 0.105566E+09 | 0.289460E+09 | 16286581.56 |
July | 0.118216E+09 | 10480991.36 | 0.107735E+09 | 0.302690E+09 | 9187510.80 |
August | 0.149228E+09 | 37913864.16 | 0.111315E+09 | 0.342930E+09 | 19018163.46 |
September | 0.228697E+09 | 0.118819E+09 | 0.109878E+09 | 0.446929E+09 | 55458465.34 |
October | 0.324385E+09 | 0.220389E+09 | 0.103996E+09 | 0.529815E+09 | 0.112743E+09 |
November | 0.377825E+09 | 0.288994E+09 | 88830943.98 | 0.538562E+09 | 0.208696E+09 |
December | 0.383911E+09 | 0.288426E+09 | 95485408.74 | 0.512271E+09 | 0.287035E+09 |
Annual Sum or Average | 0.298359E+10 | 0.172640E+10 | 0.125719E+10 | 0.486825E+10 | 0.153717E+10 |
Minimum of Months | 0.112654E+09 | 7088195.76 | 88830943.98 | 0.267531E+09 | 9187510.80 |
Maximum of Months | 0.383911E+09 | 0.288994E+09 | 0.119302E+09 | 0.538562E+09 | 0.287035E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54635219.79 | 0.00 | 54635219.79 | 11665091.39 | 0.294694E+09 |
February | 60259072.44 | 0.00 | 60259072.44 | 27857895.55 | 0.234019E+09 |
March | 87327152.96 | 3456.98 | 87323695.98 | 63211731.87 | 0.212058E+09 |
April | 98134921.78 | 1250183.62 | 96884738.16 | 0.125950E+09 | 0.100077E+09 |
May | 0.119788E+09 | 8827959.99 | 0.110960E+09 | 0.223921E+09 | 45487642.84 |
June | 0.123276E+09 | 15361483.16 | 0.107914E+09 | 0.306679E+09 | 15708092.15 |
July | 0.117686E+09 | 11543657.45 | 0.106142E+09 | 0.296329E+09 | 8788916.03 |
August | 99533259.29 | 2367984.07 | 97165275.22 | 0.233120E+09 | 18066326.44 |
September | 83800633.79 | 105909.72 | 83694724.07 | 0.161949E+09 | 55023213.21 |
October | 71778804.06 | 0.00 | 71778804.06 | 88610149.52 | 0.116816E+09 |
November | 56077421.72 | 0.00 | 56077421.72 | 22773676.11 | 0.232030E+09 |
December | 54212081.06 | 0.00 | 54212081.06 | 7988188.11 | 0.326610E+09 |
Annual Sum or Average | 0.102651E+10 | 39460634.99 | 0.987047E+09 | 0.157005E+10 | 0.165938E+10 |
Minimum of Months | 54212081.06 | 0.00 | 54212081.06 | 7988188.11 | 8788916.03 |
Maximum of Months | 0.123276E+09 | 15361483.16 | 0.110960E+09 | 0.306679E+09 | 0.326610E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.272406E+09 | 0.147604E+09 | 0.124803E+09 | 0.270666E+09 | 0.499141E+09 |
February | 0.330219E+09 | 0.188293E+09 | 0.141926E+09 | 0.385770E+09 | 0.390260E+09 |
March | 0.450634E+09 | 0.248122E+09 | 0.202511E+09 | 0.574377E+09 | 0.353534E+09 |
April | 0.525720E+09 | 0.291582E+09 | 0.234138E+09 | 0.813721E+09 | 0.170985E+09 |
May | 0.560008E+09 | 0.304221E+09 | 0.255786E+09 | 0.991977E+09 | 83852554.07 |
June | 0.542173E+09 | 0.301473E+09 | 0.240700E+09 | 0.110837E+10 | 28998944.25 |
July | 0.502747E+09 | 0.262839E+09 | 0.239908E+09 | 0.104285E+10 | 16589053.28 |
August | 0.478911E+09 | 0.245239E+09 | 0.233671E+09 | 0.953116E+09 | 33192377.89 |
September | 0.459814E+09 | 0.262571E+09 | 0.197243E+09 | 0.833495E+09 | 94718429.72 |
October | 0.363675E+09 | 0.195894E+09 | 0.167781E+09 | 0.554639E+09 | 0.203947E+09 |
November | 0.315129E+09 | 0.183035E+09 | 0.132093E+09 | 0.365936E+09 | 0.389151E+09 |
December | 0.272612E+09 | 0.144459E+09 | 0.128153E+09 | 0.256663E+09 | 0.548083E+09 |
Annual Sum or Average | 0.507405E+10 | 0.277533E+10 | 0.229871E+10 | 0.815158E+10 | 0.281245E+10 |
Minimum of Months | 0.272406E+09 | 0.144459E+09 | 0.124803E+09 | 0.256663E+09 | 16589053.28 |
Maximum of Months | 0.560008E+09 | 0.304221E+09 | 0.255786E+09 | 0.110837E+10 | 0.548083E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 69192058.57 | 0.00 | 69192058.57 | 12665987.41 | 0.395840E+09 |
February | 76314313.11 | 0.00 | 76314313.11 | 37576296.85 | 0.306502E+09 |
March | 0.110594E+09 | 4378.05 | 0.110590E+09 | 90362184.48 | 0.269992E+09 |
April | 0.124282E+09 | 1583278.67 | 0.122698E+09 | 0.186051E+09 | 0.121799E+09 |
May | 0.151704E+09 | 11180054.31 | 0.140524E+09 | 0.316898E+09 | 55259276.93 |
June | 0.156121E+09 | 19454349.17 | 0.136667E+09 | 0.416193E+09 | 20113469.49 |
July | 0.149041E+09 | 14619313.80 | 0.134422E+09 | 0.403654E+09 | 10972293.11 |
August | 0.126053E+09 | 2998902.41 | 0.123054E+09 | 0.321483E+09 | 22742528.21 |
September | 0.106128E+09 | 134127.98 | 0.105994E+09 | 0.227878E+09 | 69050987.09 |
October | 90903326.35 | 0.00 | 90903326.35 | 0.126876E+09 | 0.147194E+09 |
November | 71018516.32 | 0.00 | 71018516.32 | 30782769.37 | 0.304489E+09 |
December | 68656180.07 | 0.00 | 68656180.07 | 8564463.53 | 0.440771E+09 |
Annual Sum or Average | 0.130001E+10 | 49974404.39 | 0.125003E+10 | 0.217898E+10 | 0.216473E+10 |
Minimum of Months | 68656180.07 | 0.00 | 68656180.07 | 8564463.53 | 10972293.11 |
Maximum of Months | 0.156121E+09 | 19454349.17 | 0.140524E+09 | 0.416193E+09 | 0.440771E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 25507057.81 | 0.00 | 25507057.81 | 4669207.42 | 0.145923E+09 |
February | 28132615.74 | 0.00 | 28132615.74 | 13852178.93 | 0.112989E+09 |
March | 40769649.09 | 1613.93 | 40768035.16 | 33311242.80 | 99530367.87 |
April | 45815375.73 | 583662.08 | 45231713.65 | 68586148.55 | 44900312.74 |
May | 55924379.60 | 4121430.95 | 51802948.65 | 0.116822E+09 | 20370857.58 |
June | 57552732.16 | 7171678.64 | 50381053.51 | 0.153426E+09 | 7414657.69 |
July | 54942788.87 | 5389284.40 | 49553504.47 | 0.148804E+09 | 4044841.57 |
August | 46468205.09 | 1105519.60 | 45362685.49 | 0.118512E+09 | 8383837.59 |
September | 39123254.53 | 49445.13 | 39073809.41 | 84005265.53 | 25455053.02 |
October | 33510730.10 | 0.00 | 33510730.10 | 46771731.75 | 54261707.59 |
November | 26180365.76 | 0.00 | 26180365.76 | 11347803.41 | 0.112247E+09 |
December | 25309510.80 | 0.00 | 25309510.80 | 3157215.88 | 0.162487E+09 |
Annual Sum or Average | 0.479237E+09 | 18422634.73 | 0.460814E+09 | 0.803264E+09 | 0.798008E+09 |
Minimum of Months | 25309510.80 | 0.00 | 25309510.80 | 3157215.88 | 4044841.57 |
Maximum of Months | 57552732.16 | 7171678.64 | 51802948.65 | 0.153426E+09 | 0.162487E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.174486E+09 | 0.132213E+09 | 42273150.31 | 0.239732E+09 | 0.126616E+09 |
February | 0.148278E+09 | 0.105157E+09 | 43120481.20 | 0.209474E+09 | 99115687.37 |
March | 0.128425E+09 | 72758842.37 | 55665836.43 | 0.188811E+09 | 93533600.58 |
April | 86599719.45 | 32508424.18 | 54091295.27 | 0.153758E+09 | 46007024.84 |
May | 63502666.49 | 9312782.27 | 54189884.22 | 0.137329E+09 | 22027258.69 |
June | 52563848.94 | 3307323.58 | 49256525.36 | 0.145309E+09 | 7719518.49 |
July | 55159202.88 | 4890388.33 | 50268814.55 | 0.151731E+09 | 4211016.55 |
August | 69629375.31 | 17690456.23 | 51938919.07 | 0.170285E+09 | 8692911.82 |
September | 0.106709E+09 | 55440358.52 | 51268838.62 | 0.218419E+09 | 25174941.92 |
October | 0.151357E+09 | 0.102833E+09 | 48524052.02 | 0.255986E+09 | 51312988.10 |
November | 0.176291E+09 | 0.134843E+09 | 41448160.50 | 0.257259E+09 | 98133961.42 |
December | 0.179131E+09 | 0.134578E+09 | 44553106.94 | 0.241512E+09 | 0.137672E+09 |
Annual Sum or Average | 0.139213E+10 | 0.805533E+09 | 0.586599E+09 | 0.236960E+10 | 0.720216E+09 |
Minimum of Months | 52563848.94 | 3307323.58 | 41448160.50 | 0.137329E+09 | 4211016.55 |
Maximum of Months | 0.179131E+09 | 0.134843E+09 | 55665836.43 | 0.257259E+09 | 0.137672E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.473590E+09 | 0.358852E+09 | 0.114738E+09 | 0.650681E+09 | 0.343661E+09 |
February | 0.402456E+09 | 0.285418E+09 | 0.117038E+09 | 0.568554E+09 | 0.269020E+09 |
March | 0.348571E+09 | 0.197482E+09 | 0.151088E+09 | 0.512472E+09 | 0.253869E+09 |
April | 0.235049E+09 | 88234512.68 | 0.146815E+09 | 0.417330E+09 | 0.124873E+09 |
May | 0.172359E+09 | 25276795.96 | 0.147082E+09 | 0.372738E+09 | 59786485.66 |
June | 0.142669E+09 | 8976752.69 | 0.133692E+09 | 0.394399E+09 | 20952352.17 |
July | 0.149713E+09 | 13273514.24 | 0.136440E+09 | 0.411829E+09 | 11429560.27 |
August | 0.188988E+09 | 48015516.72 | 0.140973E+09 | 0.462190E+09 | 23594340.77 |
September | 0.289631E+09 | 0.150476E+09 | 0.139154E+09 | 0.592833E+09 | 68329941.80 |
October | 0.410813E+09 | 0.279109E+09 | 0.131704E+09 | 0.694798E+09 | 0.139274E+09 |
November | 0.478491E+09 | 0.365992E+09 | 0.112499E+09 | 0.698252E+09 | 0.266356E+09 |
December | 0.486199E+09 | 0.365273E+09 | 0.120926E+09 | 0.655514E+09 | 0.373669E+09 |
Annual Sum or Average | 0.377853E+10 | 0.218638E+10 | 0.159215E+10 | 0.643159E+10 | 0.195481E+10 |
Minimum of Months | 0.142669E+09 | 8976752.69 | 0.112499E+09 | 0.372738E+09 | 11429560.27 |
Maximum of Months | 0.486199E+09 | 0.365992E+09 | 0.151088E+09 | 0.698252E+09 | 0.373669E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.373955E+09 | 0.283356E+09 | 90599047.15 | 0.505381E+09 | 0.263044E+09 |
February | 0.317786E+09 | 0.225371E+09 | 92415031.30 | 0.438454E+09 | 0.208610E+09 |
March | 0.275237E+09 | 0.155935E+09 | 0.119302E+09 | 0.388320E+09 | 0.201036E+09 |
April | 0.185599E+09 | 69671463.64 | 0.115927E+09 | 0.304519E+09 | 0.103074E+09 |
May | 0.136098E+09 | 19958985.63 | 0.116139E+09 | 0.266049E+09 | 49556093.97 |
June | 0.112654E+09 | 7088195.76 | 0.105566E+09 | 0.288004E+09 | 16530343.82 |
July | 0.118216E+09 | 10480991.36 | 0.107735E+09 | 0.299617E+09 | 9643297.91 |
August | 0.149228E+09 | 37913864.16 | 0.111315E+09 | 0.339346E+09 | 19413502.97 |
September | 0.228697E+09 | 0.118819E+09 | 0.109878E+09 | 0.442817E+09 | 56137432.45 |
October | 0.324385E+09 | 0.220389E+09 | 0.103996E+09 | 0.525471E+09 | 0.114512E+09 |
November | 0.377825E+09 | 0.288994E+09 | 88830943.98 | 0.537059E+09 | 0.208419E+09 |
December | 0.383911E+09 | 0.288426E+09 | 95485408.74 | 0.512464E+09 | 0.284463E+09 |
Annual Sum or Average | 0.298359E+10 | 0.172640E+10 | 0.125719E+10 | 0.484750E+10 | 0.153444E+10 |
Minimum of Months | 0.112654E+09 | 7088195.76 | 88830943.98 | 0.266049E+09 | 9643297.91 |
Maximum of Months | 0.383911E+09 | 0.288994E+09 | 0.119302E+09 | 0.537059E+09 | 0.284463E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.287674E+09 | 0.162146E+09 | 0.125527E+09 | 0.304742E+09 | 0.541946E+09 |
February | 0.292474E+09 | 0.155192E+09 | 0.137282E+09 | 0.334941E+09 | 0.428991E+09 |
March | 0.441845E+09 | 0.236918E+09 | 0.204927E+09 | 0.565463E+09 | 0.388354E+09 |
April | 0.490686E+09 | 0.264679E+09 | 0.226007E+09 | 0.755660E+09 | 0.189934E+09 |
May | 0.547180E+09 | 0.292832E+09 | 0.254348E+09 | 0.960549E+09 | 91499874.81 |
June | 0.515254E+09 | 0.276659E+09 | 0.238595E+09 | 0.105129E+10 | 30798247.87 |
July | 0.472844E+09 | 0.234945E+09 | 0.237900E+09 | 0.978554E+09 | 17435870.30 |
August | 0.457839E+09 | 0.233254E+09 | 0.224585E+09 | 0.900600E+09 | 35959164.71 |
September | 0.454872E+09 | 0.253932E+09 | 0.200940E+09 | 0.817798E+09 | 0.106069E+09 |
October | 0.404989E+09 | 0.237094E+09 | 0.167895E+09 | 0.621448E+09 | 0.223703E+09 |
November | 0.327016E+09 | 0.198972E+09 | 0.128044E+09 | 0.396991E+09 | 0.429833E+09 |
December | 0.272539E+09 | 0.147971E+09 | 0.124568E+09 | 0.273966E+09 | 0.595344E+09 |
Annual Sum or Average | 0.496521E+10 | 0.269459E+10 | 0.227062E+10 | 0.796200E+10 | 0.307987E+10 |
Minimum of Months | 0.272539E+09 | 0.147971E+09 | 0.124568E+09 | 0.273966E+09 | 17435870.30 |
Maximum of Months | 0.547180E+09 | 0.292832E+09 | 0.254348E+09 | 0.105129E+10 | 0.595344E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54635219.79 | 0.00 | 54635219.79 | 13090082.78 | 0.291620E+09 |
February | 60259072.44 | 0.00 | 60259072.44 | 29891877.29 | 0.229809E+09 |
March | 87327152.96 | 3456.98 | 87323695.98 | 65653702.20 | 0.209630E+09 |
April | 98134921.78 | 1250183.62 | 96884738.16 | 0.127232E+09 | 99369693.50 |
May | 0.119788E+09 | 8827959.99 | 0.110960E+09 | 0.223147E+09 | 45786589.22 |
June | 0.123276E+09 | 15361483.16 | 0.107914E+09 | 0.304368E+09 | 16005483.82 |
July | 0.117686E+09 | 11543657.45 | 0.106142E+09 | 0.292911E+09 | 9219139.32 |
August | 99533259.29 | 2367984.07 | 97165275.22 | 0.230692E+09 | 18516185.21 |
September | 83800633.79 | 105909.72 | 83694724.07 | 0.160268E+09 | 55428339.08 |
October | 71778804.06 | 0.00 | 71778804.06 | 88047376.92 | 0.117915E+09 |
November | 56077421.72 | 0.00 | 56077421.72 | 23802646.18 | 0.231026E+09 |
December | 54212081.06 | 0.00 | 54212081.06 | 9518369.81 | 0.321568E+09 |
Annual Sum or Average | 0.102651E+10 | 39460634.99 | 0.987047E+09 | 0.156862E+10 | 0.164589E+10 |
Minimum of Months | 54212081.06 | 0.00 | 54212081.06 | 9518369.81 | 9219139.32 |
Maximum of Months | 0.123276E+09 | 15361483.16 | 0.110960E+09 | 0.304368E+09 | 0.321568E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.287674E+09 | 0.162146E+09 | 0.125527E+09 | 0.324073E+09 | 0.524739E+09 |
February | 0.292474E+09 | 0.155192E+09 | 0.137282E+09 | 0.351681E+09 | 0.416538E+09 |
March | 0.441845E+09 | 0.236918E+09 | 0.204927E+09 | 0.580192E+09 | 0.380784E+09 |
April | 0.490686E+09 | 0.264679E+09 | 0.226007E+09 | 0.762195E+09 | 0.187607E+09 |
May | 0.547180E+09 | 0.292832E+09 | 0.254348E+09 | 0.962059E+09 | 91133723.35 |
June | 0.515254E+09 | 0.276659E+09 | 0.238595E+09 | 0.105088E+10 | 30824805.72 |
July | 0.472844E+09 | 0.234945E+09 | 0.237900E+09 | 0.978831E+09 | 17379968.53 |
August | 0.457839E+09 | 0.233254E+09 | 0.224585E+09 | 0.903873E+09 | 35363549.89 |
September | 0.454872E+09 | 0.253932E+09 | 0.200940E+09 | 0.825443E+09 | 0.103227E+09 |
October | 0.404989E+09 | 0.237094E+09 | 0.167895E+09 | 0.634615E+09 | 0.216780E+09 |
November | 0.327016E+09 | 0.198972E+09 | 0.128044E+09 | 0.415071E+09 | 0.415819E+09 |
December | 0.272539E+09 | 0.147971E+09 | 0.124568E+09 | 0.292782E+09 | 0.577590E+09 |
Annual Sum or Average | 0.496521E+10 | 0.269459E+10 | 0.227062E+10 | 0.808169E+10 | 0.299779E+10 |
Minimum of Months | 0.272539E+09 | 0.147971E+09 | 0.124568E+09 | 0.292782E+09 | 17379968.53 |
Maximum of Months | 0.547180E+09 | 0.292832E+09 | 0.254348E+09 | 0.105088E+10 | 0.577590E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.548441E+09 | 0.415568E+09 | 0.132872E+09 | 0.720156E+09 | 0.404646E+09 |
February | 0.466063E+09 | 0.330528E+09 | 0.135536E+09 | 0.627146E+09 | 0.318940E+09 |
March | 0.403662E+09 | 0.228694E+09 | 0.174968E+09 | 0.559695E+09 | 0.300140E+09 |
April | 0.272199E+09 | 0.102180E+09 | 0.170019E+09 | 0.449515E+09 | 0.148917E+09 |
May | 0.199600E+09 | 29271767.90 | 0.170329E+09 | 0.402926E+09 | 68947983.96 |
June | 0.165218E+09 | 10395519.34 | 0.154822E+09 | 0.439594E+09 | 21655569.63 |
July | 0.173375E+09 | 15371379.69 | 0.158004E+09 | 0.455420E+09 | 12116833.16 |
August | 0.218858E+09 | 55604320.39 | 0.163253E+09 | 0.509593E+09 | 26349933.25 |
September | 0.335406E+09 | 0.174259E+09 | 0.161147E+09 | 0.653871E+09 | 79835313.53 |
October | 0.475742E+09 | 0.323222E+09 | 0.152520E+09 | 0.766136E+09 | 0.170114E+09 |
November | 0.554116E+09 | 0.423837E+09 | 0.130279E+09 | 0.773419E+09 | 0.317477E+09 |
December | 0.563043E+09 | 0.423004E+09 | 0.140039E+09 | 0.727935E+09 | 0.437361E+09 |
Annual Sum or Average | 0.437572E+10 | 0.253194E+10 | 0.184379E+10 | 0.708540E+10 | 0.230650E+10 |
Minimum of Months | 0.165218E+09 | 10395519.34 | 0.130279E+09 | 0.402926E+09 | 12116833.16 |
Maximum of Months | 0.563043E+09 | 0.423837E+09 | 0.174968E+09 | 0.773419E+09 | 0.437361E+09 |
Report: WindowEnergyReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.382432E+09 | 0.00 | 0.382432E+09 | 58951849.05 | 0.223366E+10 |
February | 0.421798E+09 | 0.00 | 0.421798E+09 | 0.190511E+09 | 0.174036E+10 |
March | 0.611267E+09 | 24197.95 | 0.611243E+09 | 0.462566E+09 | 0.155953E+10 |
April | 0.686918E+09 | 8750953.90 | 0.678167E+09 | 0.975923E+09 | 0.746464E+09 |
May | 0.838485E+09 | 61793379.53 | 0.776691E+09 | 0.168836E+10 | 0.362580E+09 |
June | 0.862899E+09 | 0.107526E+09 | 0.755372E+09 | 0.225356E+10 | 0.141621E+09 |
July | 0.823767E+09 | 80802541.81 | 0.742965E+09 | 0.217115E+10 | 90480253.71 |
August | 0.696706E+09 | 16575260.69 | 0.680131E+09 | 0.173765E+10 | 0.165738E+09 |
September | 0.586582E+09 | 741339.97 | 0.585841E+09 | 0.124658E+10 | 0.418525E+09 |
October | 0.502433E+09 | 0.00 | 0.502433E+09 | 0.674602E+09 | 0.873986E+09 |
November | 0.392527E+09 | 0.00 | 0.392527E+09 | 0.153535E+09 | 0.173080E+10 |
December | 0.379470E+09 | 0.00 | 0.379470E+09 | 40832122.20 | 0.245907E+10 |
Annual Sum or Average | 0.718528E+10 | 0.276214E+09 | 0.690907E+10 | 0.116542E+11 | 0.125228E+11 |
Minimum of Months | 0.379470E+09 | 0.00 | 0.379470E+09 | 40832122.20 | 90480253.71 |
Maximum of Months | 0.862899E+09 | 0.107526E+09 | 0.776691E+09 | 0.225356E+10 | 0.245907E+10 |
Report: WindowEnergyReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.382432E+09 | 0.00 | 0.382432E+09 | 53267786.88 | 0.227861E+10 |
February | 0.421798E+09 | 0.00 | 0.421798E+09 | 0.181553E+09 | 0.177825E+10 |
March | 0.611267E+09 | 24197.95 | 0.611243E+09 | 0.446543E+09 | 0.159791E+10 |
April | 0.686918E+09 | 8750953.90 | 0.678167E+09 | 0.950032E+09 | 0.776114E+09 |
May | 0.838485E+09 | 61793379.53 | 0.776691E+09 | 0.165009E+10 | 0.384845E+09 |
June | 0.862899E+09 | 0.107526E+09 | 0.755372E+09 | 0.221150E+10 | 0.153627E+09 |
July | 0.823767E+09 | 80802541.81 | 0.742965E+09 | 0.212746E+10 | 0.102383E+09 |
August | 0.696706E+09 | 16575260.69 | 0.680131E+09 | 0.169849E+10 | 0.181652E+09 |
September | 0.586582E+09 | 741339.97 | 0.585841E+09 | 0.121917E+10 | 0.442545E+09 |
October | 0.502433E+09 | 0.00 | 0.502433E+09 | 0.654921E+09 | 0.907268E+09 |
November | 0.392527E+09 | 0.00 | 0.392527E+09 | 0.144338E+09 | 0.177121E+10 |
December | 0.379470E+09 | 0.00 | 0.379470E+09 | 36967489.12 | 0.250473E+10 |
Annual Sum or Average | 0.718528E+10 | 0.276214E+09 | 0.690907E+10 | 0.113743E+11 | 0.128791E+11 |
Minimum of Months | 0.379470E+09 | 0.00 | 0.379470E+09 | 36967489.12 | 0.102383E+09 |
Maximum of Months | 0.862899E+09 | 0.107526E+09 | 0.776691E+09 | 0.221150E+10 | 0.250473E+10 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54635219.79 | 0.00 | 54635219.79 | 9266987.71 | 0.323329E+09 |
February | 60259072.44 | 0.00 | 60259072.44 | 29297062.30 | 0.255381E+09 |
March | 87327152.96 | 3456.98 | 87323695.98 | 67169779.51 | 0.233027E+09 |
April | 98134921.78 | 1250183.62 | 96884738.16 | 0.144742E+09 | 0.116220E+09 |
May | 0.119788E+09 | 8827959.99 | 0.110960E+09 | 0.248394E+09 | 60469918.49 |
June | 0.123276E+09 | 15361483.16 | 0.107914E+09 | 0.333752E+09 | 23919131.35 |
July | 0.117686E+09 | 11543657.45 | 0.106142E+09 | 0.325028E+09 | 17206397.57 |
August | 99533259.29 | 2367984.07 | 97165275.22 | 0.262167E+09 | 28826847.36 |
September | 83800633.79 | 105909.72 | 83694724.07 | 0.192616E+09 | 64732002.01 |
October | 71778804.06 | 0.00 | 71778804.06 | 0.104040E+09 | 0.132888E+09 |
November | 56077421.72 | 0.00 | 56077421.72 | 24491332.48 | 0.253392E+09 |
December | 54212081.06 | 0.00 | 54212081.06 | 6787997.48 | 0.350976E+09 |
Annual Sum or Average | 0.102651E+10 | 39460634.99 | 0.987047E+09 | 0.174775E+10 | 0.186037E+10 |
Minimum of Months | 54212081.06 | 0.00 | 54212081.06 | 6787997.48 | 17206397.57 |
Maximum of Months | 0.123276E+09 | 15361483.16 | 0.110960E+09 | 0.333752E+09 | 0.350976E+09 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.544774E+09 | 0.295186E+09 | 0.249587E+09 | 0.537065E+09 | 0.110416E+10 |
February | 0.660391E+09 | 0.376560E+09 | 0.283831E+09 | 0.787873E+09 | 0.866230E+09 |
March | 0.901204E+09 | 0.496210E+09 | 0.404994E+09 | 0.118089E+10 | 0.790269E+09 |
April | 0.105137E+10 | 0.583122E+09 | 0.468243E+09 | 0.170585E+10 | 0.408656E+09 |
May | 0.111994E+10 | 0.608399E+09 | 0.511536E+09 | 0.207462E+10 | 0.225027E+09 |
June | 0.108427E+10 | 0.602903E+09 | 0.481366E+09 | 0.231218E+10 | 89477376.49 |
July | 0.100542E+10 | 0.525641E+09 | 0.479782E+09 | 0.218573E+10 | 65784221.29 |
August | 0.957753E+09 | 0.490444E+09 | 0.467309E+09 | 0.201075E+10 | 0.108284E+09 |
September | 0.919563E+09 | 0.525105E+09 | 0.394458E+09 | 0.178571E+10 | 0.233071E+09 |
October | 0.727299E+09 | 0.391760E+09 | 0.335538E+09 | 0.117287E+10 | 0.473539E+09 |
November | 0.630213E+09 | 0.366045E+09 | 0.264168E+09 | 0.747975E+09 | 0.861810E+09 |
December | 0.545185E+09 | 0.288898E+09 | 0.256287E+09 | 0.518186E+09 | 0.119386E+10 |
Annual Sum or Average | 0.101474E+11 | 0.555027E+10 | 0.459710E+10 | 0.170197E+11 | 0.642017E+10 |
Minimum of Months | 0.544774E+09 | 0.288898E+09 | 0.249587E+09 | 0.518186E+09 | 65784221.29 |
Maximum of Months | 0.111994E+10 | 0.608399E+09 | 0.511536E+09 | 0.231218E+10 | 0.119386E+10 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.373955E+09 | 0.283356E+09 | 90599047.15 | 0.519182E+09 | 0.283393E+09 |
February | 0.317786E+09 | 0.225371E+09 | 92415031.30 | 0.452129E+09 | 0.226622E+09 |
March | 0.275237E+09 | 0.155935E+09 | 0.119302E+09 | 0.403136E+09 | 0.218277E+09 |
April | 0.185599E+09 | 69671463.64 | 0.115927E+09 | 0.325628E+09 | 0.117974E+09 |
May | 0.136098E+09 | 19958985.63 | 0.116139E+09 | 0.289282E+09 | 63565526.86 |
June | 0.112654E+09 | 7088195.76 | 0.105566E+09 | 0.315013E+09 | 24257247.86 |
July | 0.118216E+09 | 10480991.36 | 0.107735E+09 | 0.330449E+09 | 17513876.95 |
August | 0.149228E+09 | 37913864.16 | 0.111315E+09 | 0.373012E+09 | 29274860.25 |
September | 0.228697E+09 | 0.118819E+09 | 0.109878E+09 | 0.481127E+09 | 64357464.44 |
October | 0.324385E+09 | 0.220389E+09 | 0.103996E+09 | 0.554834E+09 | 0.126427E+09 |
November | 0.377825E+09 | 0.288994E+09 | 88830943.98 | 0.557566E+09 | 0.223493E+09 |
December | 0.383911E+09 | 0.288426E+09 | 95485408.74 | 0.526694E+09 | 0.302443E+09 |
Annual Sum or Average | 0.298359E+10 | 0.172640E+10 | 0.125719E+10 | 0.512805E+10 | 0.169760E+10 |
Minimum of Months | 0.112654E+09 | 7088195.76 | 88830943.98 | 0.289282E+09 | 17513876.95 |
Maximum of Months | 0.383911E+09 | 0.288994E+09 | 0.119302E+09 | 0.557566E+09 | 0.302443E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 69192058.57 | 0.00 | 69192058.57 | 10824474.14 | 0.399484E+09 |
February | 76314313.11 | 0.00 | 76314313.11 | 34734121.61 | 0.308780E+09 |
March | 0.110594E+09 | 4378.05 | 0.110590E+09 | 85646602.25 | 0.271829E+09 |
April | 0.124282E+09 | 1583278.67 | 0.122698E+09 | 0.180146E+09 | 0.121881E+09 |
May | 0.151704E+09 | 11180054.31 | 0.140524E+09 | 0.314224E+09 | 52811703.49 |
June | 0.156121E+09 | 19454349.17 | 0.136667E+09 | 0.415444E+09 | 17913761.79 |
July | 0.149041E+09 | 14619313.80 | 0.134422E+09 | 0.401478E+09 | 9569400.25 |
August | 0.126053E+09 | 2998902.41 | 0.123054E+09 | 0.320015E+09 | 20611547.23 |
September | 0.106128E+09 | 134127.98 | 0.105994E+09 | 0.225111E+09 | 64993246.29 |
October | 90903326.35 | 0.00 | 90903326.35 | 0.122171E+09 | 0.146841E+09 |
November | 71018516.32 | 0.00 | 71018516.32 | 27677806.78 | 0.306901E+09 |
December | 68656180.07 | 0.00 | 68656180.07 | 7528341.98 | 0.442821E+09 |
Annual Sum or Average | 0.130001E+10 | 49974404.39 | 0.125003E+10 | 0.214500E+10 | 0.216444E+10 |
Minimum of Months | 68656180.07 | 0.00 | 68656180.07 | 7528341.98 | 9569400.25 |
Maximum of Months | 0.156121E+09 | 19454349.17 | 0.140524E+09 | 0.415444E+09 | 0.442821E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 61906396.97 | 0.00 | 61906396.97 | 9684698.02 | 0.357420E+09 |
February | 68278705.09 | 0.00 | 68278705.09 | 31076750.21 | 0.276267E+09 |
March | 98949165.36 | 3917.06 | 98945248.31 | 76628339.55 | 0.243207E+09 |
April | 0.111195E+09 | 1416565.43 | 0.109779E+09 | 0.161177E+09 | 0.109048E+09 |
May | 0.135730E+09 | 10002836.96 | 0.125727E+09 | 0.281137E+09 | 47250831.21 |
June | 0.139682E+09 | 17405879.91 | 0.122276E+09 | 0.371700E+09 | 16027510.55 |
July | 0.133348E+09 | 13079955.45 | 0.120268E+09 | 0.359204E+09 | 8561778.67 |
August | 0.112780E+09 | 2683129.35 | 0.110097E+09 | 0.286319E+09 | 18441229.40 |
September | 94953316.23 | 120004.81 | 94833311.42 | 0.201407E+09 | 58149703.71 |
October | 81331550.52 | 0.00 | 81331550.52 | 0.109307E+09 | 0.131379E+09 |
November | 63540535.64 | 0.00 | 63540535.64 | 24763438.60 | 0.274585E+09 |
December | 61426944.44 | 0.00 | 61426944.44 | 6735636.09 | 0.396177E+09 |
Annual Sum or Average | 0.116312E+10 | 44712288.96 | 0.111841E+10 | 0.191914E+10 | 0.193651E+10 |
Minimum of Months | 61426944.44 | 0.00 | 61426944.44 | 6735636.09 | 8561778.67 |
Maximum of Months | 0.139682E+09 | 17405879.91 | 0.125727E+09 | 0.371700E+09 | 0.396177E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.139608E+10 | 0.105785E+10 | 0.338233E+09 | 0.189247E+10 | 0.101771E+10 |
February | 0.118639E+10 | 0.841376E+09 | 0.345013E+09 | 0.165235E+10 | 0.797446E+09 |
March | 0.102754E+10 | 0.582153E+09 | 0.445390E+09 | 0.148205E+10 | 0.753030E+09 |
April | 0.692896E+09 | 0.260104E+09 | 0.432792E+09 | 0.120518E+10 | 0.369040E+09 |
May | 0.508093E+09 | 74512840.84 | 0.433581E+09 | 0.108929E+10 | 0.169469E+09 |
June | 0.420571E+09 | 26462346.95 | 0.394108E+09 | 0.116174E+10 | 55003997.19 |
July | 0.441336E+09 | 39128663.92 | 0.402208E+09 | 0.120752E+10 | 29674140.16 |
August | 0.557114E+09 | 0.141544E+09 | 0.415570E+09 | 0.135387E+10 | 63374026.53 |
September | 0.853795E+09 | 0.443586E+09 | 0.410209E+09 | 0.173228E+10 | 0.190008E+09 |
October | 0.121103E+10 | 0.822779E+09 | 0.388248E+09 | 0.202195E+10 | 0.409899E+09 |
November | 0.141053E+10 | 0.107890E+10 | 0.331632E+09 | 0.203341E+10 | 0.788431E+09 |
December | 0.143326E+10 | 0.107678E+10 | 0.356475E+09 | 0.191144E+10 | 0.110152E+10 |
Annual Sum or Average | 0.111386E+11 | 0.644518E+10 | 0.469346E+10 | 0.187435E+11 | 0.574461E+10 |
Minimum of Months | 0.420571E+09 | 26462346.95 | 0.331632E+09 | 0.108929E+10 | 29674140.16 |
Maximum of Months | 0.143326E+10 | 0.107890E+10 | 0.445390E+09 | 0.203341E+10 | 0.110152E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 966.31 | 488.35 | 706.15 | 535.07 | 171.08 | 0.00 | 0.00 |
February | 931.83 | 426.84 | 664.38 | 471.17 | 193.21 | 0.00 | 0.00 |
March | 759.87 | 366.80 | 519.74 | 294.46 | 225.28 | 0.00 | 0.00 |
April | 624.30 | 193.52 | 362.15 | 135.95 | 226.20 | 0.00 | 0.00 |
May | 529.28 | 91.56 | 257.00 | 37.69 | 219.31 | 0.00 | 0.00 |
June | 578.17 | 31.64 | 219.82 | 13.83 | 205.99 | 0.00 | 0.00 |
July | 587.73 | 16.67 | 223.23 | 19.79 | 203.44 | 0.00 | 0.00 |
August | 662.86 | 35.29 | 281.79 | 71.59 | 210.20 | 0.00 | 0.00 |
September | 885.96 | 106.12 | 446.25 | 231.85 | 214.40 | 0.00 | 0.00 |
October | 1011.44 | 209.50 | 612.55 | 416.17 | 196.38 | 0.00 | 0.00 |
November | 1059.97 | 399.52 | 737.24 | 563.91 | 173.33 | 0.00 | 0.00 |
December | 971.49 | 531.20 | 724.95 | 544.65 | 180.31 | 0.00 | 0.00 |
Annual Sum or Average | 796.44 | 240.54 | 478.50 | 276.88 | 201.63 | 0.00 | 0.00 |
Minimum of Months | 529.28 | 16.67 | 219.82 | 13.83 | 171.08 | 0.00 | 0.00 |
Maximum of Months | 1059.97 | 531.20 | 737.24 | 563.91 | 226.20 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2704.81 | 1387.38 | 1988.48 | 1506.73 | 481.75 | 0.00 | 0.00 |
February | 2607.58 | 1212.38 | 1870.85 | 1326.79 | 544.06 | 0.00 | 0.00 |
March | 2123.50 | 1041.07 | 1463.55 | 829.18 | 634.37 | 0.00 | 0.00 |
April | 1744.59 | 557.35 | 1019.80 | 382.82 | 636.98 | 0.00 | 0.00 |
May | 1474.27 | 272.00 | 723.68 | 106.13 | 617.55 | 0.00 | 0.00 |
June | 1609.26 | 101.92 | 618.99 | 38.95 | 580.04 | 0.00 | 0.00 |
July | 1634.91 | 58.32 | 628.60 | 55.73 | 572.87 | 0.00 | 0.00 |
August | 1852.27 | 115.73 | 793.51 | 201.60 | 591.90 | 0.00 | 0.00 |
September | 2491.96 | 314.76 | 1256.61 | 652.87 | 603.74 | 0.00 | 0.00 |
October | 2840.22 | 605.20 | 1724.89 | 1171.91 | 552.99 | 0.00 | 0.00 |
November | 2971.59 | 1135.58 | 2076.02 | 1587.93 | 488.09 | 0.00 | 0.00 |
December | 2716.87 | 1506.63 | 2041.42 | 1533.69 | 507.73 | 0.00 | 0.00 |
Annual Sum or Average | 2228.18 | 689.89 | 1347.44 | 779.68 | 567.76 | 0.00 | 0.00 |
Minimum of Months | 1474.27 | 58.32 | 618.99 | 38.95 | 481.75 | 0.00 | 0.00 |
Maximum of Months | 2971.59 | 1506.63 | 2076.02 | 1587.93 | 636.98 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3583.68 | 1839.21 | 2583.15 | 1957.32 | 625.82 | 0.00 | 0.00 |
February | 3461.38 | 1605.98 | 2430.34 | 1723.58 | 706.76 | 0.00 | 0.00 |
March | 2821.64 | 1385.91 | 1901.24 | 1077.15 | 824.09 | 0.00 | 0.00 |
April | 2331.15 | 742.00 | 1324.78 | 497.31 | 827.47 | 0.00 | 0.00 |
May | 1977.06 | 364.15 | 940.11 | 137.87 | 802.24 | 0.00 | 0.00 |
June | 2164.92 | 134.32 | 804.10 | 50.59 | 753.51 | 0.00 | 0.00 |
July | 2197.35 | 75.81 | 816.59 | 72.40 | 744.19 | 0.00 | 0.00 |
August | 2487.83 | 149.09 | 1030.81 | 261.90 | 768.91 | 0.00 | 0.00 |
September | 3337.86 | 406.25 | 1632.41 | 848.12 | 784.29 | 0.00 | 0.00 |
October | 3793.06 | 787.66 | 2240.73 | 1522.37 | 718.36 | 0.00 | 0.00 |
November | 3951.91 | 1496.97 | 2696.87 | 2062.81 | 634.06 | 0.00 | 0.00 |
December | 3595.64 | 2000.72 | 2651.92 | 1992.35 | 659.58 | 0.00 | 0.00 |
Annual Sum or Average | 2971.61 | 912.42 | 1750.40 | 1012.84 | 737.56 | 0.00 | 0.00 |
Minimum of Months | 1977.06 | 75.81 | 804.10 | 50.59 | 625.82 | 0.00 | 0.00 |
Maximum of Months | 3951.91 | 2000.72 | 2696.87 | 2062.81 | 827.47 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 290.34 | 290.06 | 247.02 | 166.33 | 80.69 | 0.00 | 0.00 |
February | 311.83 | 255.71 | 252.26 | 157.31 | 94.95 | 0.00 | 0.00 |
March | 356.39 | 217.67 | 267.73 | 146.67 | 121.05 | 0.00 | 0.00 |
April | 414.31 | 112.83 | 260.91 | 128.99 | 131.92 | 0.00 | 0.00 |
May | 464.33 | 53.16 | 255.11 | 116.78 | 138.32 | 0.00 | 0.00 |
June | 522.61 | 18.44 | 242.25 | 109.47 | 132.78 | 0.00 | 0.00 |
July | 483.75 | 9.96 | 220.68 | 91.63 | 129.05 | 0.00 | 0.00 |
August | 469.31 | 20.58 | 226.65 | 101.24 | 125.41 | 0.00 | 0.00 |
September | 492.56 | 62.51 | 263.72 | 143.81 | 119.91 | 0.00 | 0.00 |
October | 431.38 | 124.68 | 272.32 | 170.80 | 101.51 | 0.00 | 0.00 |
November | 353.23 | 238.59 | 271.93 | 188.26 | 83.67 | 0.00 | 0.00 |
December | 277.09 | 315.79 | 245.09 | 162.93 | 82.16 | 0.00 | 0.00 |
Annual Sum or Average | 405.93 | 142.79 | 252.05 | 140.19 | 111.87 | 0.00 | 0.00 |
Minimum of Months | 277.09 | 9.96 | 220.68 | 91.63 | 80.69 | 0.00 | 0.00 |
Maximum of Months | 522.61 | 315.79 | 272.32 | 188.26 | 138.32 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 121.86 | 305.03 | 127.80 | 60.54 | 67.26 | 0.00 | 0.00 |
February | 155.68 | 267.66 | 145.81 | 64.15 | 81.66 | 0.00 | 0.00 |
March | 241.90 | 220.55 | 197.57 | 88.46 | 109.11 | 0.00 | 0.00 |
April | 348.04 | 110.80 | 227.17 | 102.60 | 124.57 | 0.00 | 0.00 |
May | 448.18 | 50.95 | 249.02 | 112.63 | 136.39 | 0.00 | 0.00 |
June | 528.75 | 17.94 | 246.35 | 112.66 | 133.68 | 0.00 | 0.00 |
July | 481.34 | 9.67 | 220.48 | 92.03 | 128.45 | 0.00 | 0.00 |
August | 429.54 | 19.91 | 208.10 | 87.97 | 120.13 | 0.00 | 0.00 |
September | 385.88 | 61.36 | 207.82 | 98.01 | 109.81 | 0.00 | 0.00 |
October | 273.22 | 125.14 | 178.00 | 88.52 | 89.48 | 0.00 | 0.00 |
November | 167.52 | 249.84 | 147.80 | 76.76 | 71.03 | 0.00 | 0.00 |
December | 107.55 | 336.34 | 121.99 | 55.25 | 66.75 | 0.00 | 0.00 |
Annual Sum or Average | 308.15 | 147.37 | 190.00 | 86.70 | 103.30 | 0.00 | 0.00 |
Minimum of Months | 107.55 | 9.67 | 121.99 | 55.25 | 66.75 | 0.00 | 0.00 |
Maximum of Months | 528.75 | 336.34 | 249.02 | 112.66 | 136.39 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 146.49 | 90.53 | 111.67 | 84.62 | 27.06 | 0.00 | 0.00 |
February | 140.85 | 80.39 | 105.07 | 74.51 | 30.55 | 0.00 | 0.00 |
March | 112.69 | 69.56 | 82.19 | 46.57 | 35.63 | 0.00 | 0.00 |
April | 92.09 | 39.61 | 57.27 | 21.50 | 35.77 | 0.00 | 0.00 |
May | 77.25 | 20.47 | 40.64 | 5.96 | 34.68 | 0.00 | 0.00 |
June | 85.74 | 8.32 | 34.76 | 2.19 | 32.58 | 0.00 | 0.00 |
July | 86.17 | 5.84 | 35.30 | 3.13 | 32.17 | 0.00 | 0.00 |
August | 98.52 | 9.88 | 44.56 | 11.32 | 33.24 | 0.00 | 0.00 |
September | 135.45 | 23.59 | 70.57 | 36.67 | 33.91 | 0.00 | 0.00 |
October | 154.43 | 42.97 | 96.87 | 65.81 | 31.06 | 0.00 | 0.00 |
November | 162.15 | 74.95 | 116.59 | 89.18 | 27.41 | 0.00 | 0.00 |
December | 148.10 | 95.80 | 114.65 | 86.13 | 28.51 | 0.00 | 0.00 |
Annual Sum or Average | 119.83 | 46.66 | 75.67 | 43.79 | 31.89 | 0.00 | 0.00 |
Minimum of Months | 77.25 | 5.84 | 34.76 | 2.19 | 27.06 | 0.00 | 0.00 |
Maximum of Months | 162.15 | 95.80 | 116.59 | 89.18 | 35.77 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3.19 | 92.12 | 16.32 | 0.00 | 16.32 | 0.00 | 0.00 |
February | 9.75 | 79.56 | 19.93 | 0.00 | 19.93 | 0.00 | 0.00 |
March | 20.52 | 64.10 | 26.09 | 0.00 | 26.09 | 0.00 | 0.00 |
April | 42.81 | 30.27 | 30.29 | 0.39 | 29.91 | 0.00 | 0.00 |
May | 71.80 | 12.97 | 35.78 | 2.64 | 33.15 | 0.00 | 0.00 |
June | 100.35 | 4.30 | 38.05 | 4.74 | 33.31 | 0.00 | 0.00 |
July | 93.80 | 2.20 | 35.16 | 3.45 | 31.71 | 0.00 | 0.00 |
August | 74.60 | 4.84 | 29.73 | 0.71 | 29.03 | 0.00 | 0.00 |
September | 54.20 | 15.96 | 25.87 | 0.03 | 25.84 | 0.00 | 0.00 |
October | 28.85 | 34.85 | 21.44 | 0.00 | 21.44 | 0.00 | 0.00 |
November | 7.49 | 73.85 | 17.31 | 0.00 | 17.31 | 0.00 | 0.00 |
December | 2.18 | 101.99 | 16.19 | 0.00 | 16.19 | 0.00 | 0.00 |
Annual Sum or Average | 42.64 | 42.92 | 26.04 | 1.00 | 25.04 | 0.00 | 0.00 |
Minimum of Months | 2.18 | 2.20 | 16.19 | 0.00 | 16.19 | 0.00 | 0.00 |
Maximum of Months | 100.35 | 101.99 | 38.05 | 4.74 | 33.31 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 276.76 | 284.69 | 241.32 | 160.90 | 80.42 | 0.00 | 0.00 |
February | 329.19 | 248.38 | 267.86 | 170.99 | 96.87 | 0.00 | 0.00 |
March | 349.94 | 205.33 | 271.01 | 150.86 | 120.15 | 0.00 | 0.00 |
April | 425.54 | 102.66 | 274.43 | 139.37 | 135.06 | 0.00 | 0.00 |
May | 468.05 | 48.24 | 259.90 | 121.04 | 138.86 | 0.00 | 0.00 |
June | 539.06 | 17.18 | 252.63 | 119.04 | 133.59 | 0.00 | 0.00 |
July | 502.08 | 9.53 | 231.84 | 102.05 | 129.80 | 0.00 | 0.00 |
August | 482.34 | 19.35 | 234.52 | 105.72 | 128.80 | 0.00 | 0.00 |
September | 489.94 | 57.58 | 265.63 | 147.14 | 118.49 | 0.00 | 0.00 |
October | 399.54 | 119.80 | 256.89 | 155.42 | 101.47 | 0.00 | 0.00 |
November | 337.52 | 231.52 | 267.34 | 182.11 | 85.23 | 0.00 | 0.00 |
December | 271.62 | 309.38 | 245.12 | 161.62 | 83.50 | 0.00 | 0.00 |
Annual Sum or Average | 406.14 | 137.28 | 255.51 | 142.75 | 112.76 | 0.00 | 0.00 |
Minimum of Months | 271.62 | 9.53 | 231.84 | 102.05 | 80.42 | 0.00 | 0.00 |
Maximum of Months | 539.06 | 309.38 | 274.43 | 182.11 | 138.86 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 96.22 | 287.20 | 122.10 | 55.11 | 66.99 | 0.00 | 0.00 |
February | 161.11 | 248.18 | 161.41 | 77.83 | 83.58 | 0.00 | 0.00 |
March | 230.31 | 203.43 | 200.85 | 92.64 | 108.21 | 0.00 | 0.00 |
April | 359.17 | 101.22 | 240.68 | 112.98 | 127.71 | 0.00 | 0.00 |
May | 453.64 | 47.97 | 253.81 | 116.88 | 136.93 | 0.00 | 0.00 |
June | 545.91 | 17.23 | 256.73 | 122.24 | 134.50 | 0.00 | 0.00 |
July | 499.94 | 9.42 | 231.64 | 102.44 | 129.20 | 0.00 | 0.00 |
August | 442.81 | 19.06 | 215.97 | 92.45 | 123.52 | 0.00 | 0.00 |
September | 382.46 | 56.19 | 209.73 | 101.34 | 108.39 | 0.00 | 0.00 |
October | 237.40 | 117.00 | 162.58 | 73.14 | 89.44 | 0.00 | 0.00 |
November | 141.67 | 231.36 | 143.21 | 70.62 | 72.60 | 0.00 | 0.00 |
December | 87.73 | 315.49 | 122.02 | 53.93 | 68.09 | 0.00 | 0.00 |
Annual Sum or Average | 303.77 | 137.30 | 193.45 | 89.26 | 104.19 | 0.00 | 0.00 |
Minimum of Months | 87.73 | 9.42 | 122.02 | 53.93 | 66.99 | 0.00 | 0.00 |
Maximum of Months | 545.91 | 315.49 | 256.73 | 122.24 | 136.93 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 317.97 | 356.90 | 277.32 | 183.34 | 93.98 | 0.00 | 0.00 |
February | 328.00 | 310.71 | 270.83 | 161.45 | 109.38 | 0.00 | 0.00 |
March | 303.71 | 263.38 | 234.60 | 100.90 | 133.70 | 0.00 | 0.00 |
April | 318.15 | 129.82 | 189.72 | 47.42 | 142.30 | 0.00 | 0.00 |
May | 351.50 | 57.91 | 165.58 | 18.63 | 146.95 | 0.00 | 0.00 |
June | 427.65 | 21.35 | 157.76 | 15.01 | 142.75 | 0.00 | 0.00 |
July | 416.45 | 11.22 | 152.65 | 14.25 | 138.40 | 0.00 | 0.00 |
August | 400.25 | 23.51 | 160.97 | 26.06 | 134.90 | 0.00 | 0.00 |
September | 433.10 | 72.33 | 208.95 | 79.51 | 129.43 | 0.00 | 0.00 |
October | 417.62 | 144.18 | 256.34 | 142.60 | 113.74 | 0.00 | 0.00 |
November | 370.72 | 287.23 | 290.12 | 193.22 | 96.89 | 0.00 | 0.00 |
December | 311.75 | 388.61 | 283.49 | 186.62 | 96.87 | 0.00 | 0.00 |
Annual Sum or Average | 366.49 | 171.61 | 220.38 | 97.04 | 123.34 | 0.00 | 0.00 |
Minimum of Months | 303.71 | 11.22 | 152.65 | 14.25 | 93.98 | 0.00 | 0.00 |
Maximum of Months | 433.10 | 388.61 | 290.12 | 193.22 | 146.95 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 288.77 | 286.86 | 247.02 | 166.33 | 80.69 | 0.00 | 0.00 |
February | 309.24 | 253.10 | 252.26 | 157.31 | 94.95 | 0.00 | 0.00 |
March | 351.81 | 215.76 | 267.73 | 146.67 | 121.05 | 0.00 | 0.00 |
April | 408.06 | 112.08 | 260.91 | 128.99 | 131.92 | 0.00 | 0.00 |
May | 457.88 | 52.58 | 255.11 | 116.78 | 138.32 | 0.00 | 0.00 |
June | 516.70 | 18.26 | 242.25 | 109.47 | 132.78 | 0.00 | 0.00 |
July | 477.14 | 10.04 | 220.68 | 91.63 | 129.05 | 0.00 | 0.00 |
August | 462.89 | 20.62 | 226.65 | 101.24 | 125.41 | 0.00 | 0.00 |
September | 486.15 | 62.38 | 263.72 | 143.81 | 119.91 | 0.00 | 0.00 |
October | 426.23 | 124.29 | 272.32 | 170.80 | 101.51 | 0.00 | 0.00 |
November | 350.41 | 236.29 | 271.93 | 188.26 | 83.67 | 0.00 | 0.00 |
December | 276.79 | 311.65 | 245.09 | 162.93 | 82.16 | 0.00 | 0.00 |
Annual Sum or Average | 401.33 | 141.46 | 252.05 | 140.19 | 111.87 | 0.00 | 0.00 |
Minimum of Months | 276.79 | 10.04 | 220.68 | 91.63 | 80.69 | 0.00 | 0.00 |
Maximum of Months | 516.70 | 311.65 | 272.32 | 188.26 | 138.32 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 121.93 | 300.84 | 127.80 | 60.54 | 67.26 | 0.00 | 0.00 |
February | 154.73 | 264.17 | 145.81 | 64.15 | 81.66 | 0.00 | 0.00 |
March | 238.92 | 218.23 | 197.57 | 88.46 | 109.11 | 0.00 | 0.00 |
April | 342.47 | 110.04 | 227.17 | 102.60 | 124.57 | 0.00 | 0.00 |
May | 441.82 | 50.43 | 249.02 | 112.63 | 136.39 | 0.00 | 0.00 |
June | 522.59 | 17.80 | 246.35 | 112.66 | 133.68 | 0.00 | 0.00 |
July | 474.65 | 9.77 | 220.48 | 92.03 | 128.45 | 0.00 | 0.00 |
August | 423.44 | 19.96 | 208.10 | 87.97 | 120.13 | 0.00 | 0.00 |
September | 380.25 | 61.17 | 207.82 | 98.01 | 109.81 | 0.00 | 0.00 |
October | 269.24 | 124.39 | 178.00 | 88.52 | 89.48 | 0.00 | 0.00 |
November | 166.29 | 246.52 | 147.80 | 76.76 | 71.03 | 0.00 | 0.00 |
December | 108.29 | 331.13 | 121.99 | 55.25 | 66.75 | 0.00 | 0.00 |
Annual Sum or Average | 304.40 | 145.64 | 190.00 | 86.70 | 103.30 | 0.00 | 0.00 |
Minimum of Months | 108.29 | 9.77 | 121.99 | 55.25 | 66.75 | 0.00 | 0.00 |
Maximum of Months | 522.59 | 331.13 | 249.02 | 112.66 | 136.39 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 268.88 | 151.08 | 204.76 | 155.16 | 49.61 | 0.00 | 0.00 |
February | 259.24 | 131.84 | 192.65 | 136.63 | 56.02 | 0.00 | 0.00 |
March | 208.97 | 112.06 | 150.71 | 85.38 | 65.33 | 0.00 | 0.00 |
April | 173.42 | 57.45 | 105.01 | 39.42 | 65.59 | 0.00 | 0.00 |
May | 150.44 | 25.74 | 74.52 | 10.93 | 63.59 | 0.00 | 0.00 |
June | 169.60 | 8.35 | 63.74 | 4.01 | 59.73 | 0.00 | 0.00 |
July | 170.03 | 4.52 | 64.73 | 5.74 | 58.99 | 0.00 | 0.00 |
August | 190.26 | 9.84 | 81.71 | 20.76 | 60.95 | 0.00 | 0.00 |
September | 252.26 | 30.80 | 129.40 | 67.23 | 62.17 | 0.00 | 0.00 |
October | 286.04 | 63.51 | 177.62 | 120.68 | 56.94 | 0.00 | 0.00 |
November | 298.39 | 122.48 | 213.78 | 163.52 | 50.26 | 0.00 | 0.00 |
December | 271.78 | 163.29 | 210.22 | 157.93 | 52.28 | 0.00 | 0.00 |
Annual Sum or Average | 224.68 | 73.14 | 138.75 | 80.29 | 58.47 | 0.00 | 0.00 |
Minimum of Months | 150.44 | 4.52 | 63.74 | 4.01 | 49.61 | 0.00 | 0.00 |
Maximum of Months | 298.39 | 163.29 | 213.78 | 163.52 | 65.59 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 22.01 | 833.95 | 142.78 | 0.00 | 142.78 | 0.00 | 0.00 |
February | 78.75 | 719.40 | 174.35 | 0.00 | 174.35 | 0.00 | 0.00 |
March | 172.70 | 582.26 | 228.22 | 0.01 | 228.21 | 0.00 | 0.00 |
April | 376.51 | 287.99 | 265.01 | 3.38 | 261.64 | 0.00 | 0.00 |
May | 630.36 | 135.37 | 313.05 | 23.07 | 289.98 | 0.00 | 0.00 |
June | 869.43 | 54.64 | 332.91 | 41.48 | 291.42 | 0.00 | 0.00 |
July | 810.61 | 33.78 | 307.56 | 30.17 | 277.39 | 0.00 | 0.00 |
August | 648.77 | 61.88 | 260.12 | 6.19 | 253.93 | 0.00 | 0.00 |
September | 480.93 | 161.47 | 226.30 | 0.29 | 226.02 | 0.00 | 0.00 |
October | 251.87 | 326.31 | 187.59 | 0.00 | 187.59 | 0.00 | 0.00 |
November | 59.23 | 667.75 | 151.44 | 0.00 | 151.44 | 0.00 | 0.00 |
December | 15.24 | 918.11 | 141.68 | 0.00 | 141.68 | 0.00 | 0.00 |
Annual Sum or Average | 369.55 | 397.10 | 227.84 | 8.76 | 219.09 | 0.00 | 0.00 |
Minimum of Months | 15.24 | 33.78 | 141.68 | 0.00 | 141.68 | 0.00 | 0.00 |
Maximum of Months | 869.43 | 918.11 | 332.91 | 41.48 | 291.42 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 19.89 | 850.73 | 142.78 | 0.00 | 142.78 | 0.00 | 0.00 |
February | 75.05 | 735.06 | 174.35 | 0.00 | 174.35 | 0.00 | 0.00 |
March | 166.72 | 596.59 | 228.22 | 0.01 | 228.21 | 0.00 | 0.00 |
April | 366.52 | 299.43 | 265.01 | 3.38 | 261.64 | 0.00 | 0.00 |
May | 616.07 | 143.68 | 313.05 | 23.07 | 289.98 | 0.00 | 0.00 |
June | 853.20 | 59.27 | 332.91 | 41.48 | 291.42 | 0.00 | 0.00 |
July | 794.30 | 38.23 | 307.56 | 30.17 | 277.39 | 0.00 | 0.00 |
August | 634.14 | 67.82 | 260.12 | 6.19 | 253.93 | 0.00 | 0.00 |
September | 470.36 | 170.73 | 226.30 | 0.29 | 226.02 | 0.00 | 0.00 |
October | 244.52 | 338.74 | 187.59 | 0.00 | 187.59 | 0.00 | 0.00 |
November | 55.69 | 683.34 | 151.44 | 0.00 | 151.44 | 0.00 | 0.00 |
December | 13.80 | 935.16 | 141.68 | 0.00 | 141.68 | 0.00 | 0.00 |
Annual Sum or Average | 360.68 | 408.39 | 227.84 | 8.76 | 219.09 | 0.00 | 0.00 |
Minimum of Months | 13.80 | 38.23 | 141.68 | 0.00 | 141.68 | 0.00 | 0.00 |
Maximum of Months | 853.20 | 935.16 | 332.91 | 41.48 | 291.42 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 373.39 | 614.35 | 363.41 | 216.00 | 147.41 | 0.00 | 0.00 |
February | 506.30 | 538.93 | 429.25 | 248.81 | 180.43 | 0.00 | 0.00 |
March | 604.21 | 451.28 | 471.84 | 243.48 | 228.35 | 0.00 | 0.00 |
April | 833.58 | 242.00 | 515.08 | 252.33 | 262.75 | 0.00 | 0.00 |
May | 973.62 | 128.63 | 513.67 | 237.90 | 275.77 | 0.00 | 0.00 |
June | 1142.12 | 52.89 | 509.34 | 241.26 | 268.07 | 0.00 | 0.00 |
July | 1060.72 | 37.46 | 463.46 | 204.47 | 258.98 | 0.00 | 0.00 |
August | 987.64 | 61.88 | 450.46 | 198.15 | 252.31 | 0.00 | 0.00 |
September | 947.04 | 137.90 | 475.33 | 248.47 | 226.86 | 0.00 | 0.00 |
October | 680.67 | 270.39 | 419.45 | 228.55 | 190.90 | 0.00 | 0.00 |
November | 497.82 | 501.16 | 410.54 | 252.72 | 157.82 | 0.00 | 0.00 |
December | 360.86 | 657.91 | 367.13 | 215.55 | 151.58 | 0.00 | 0.00 |
Annual Sum or Average | 748.13 | 306.81 | 448.93 | 231.99 | 216.94 | 0.00 | 0.00 |
Minimum of Months | 360.86 | 37.46 | 363.41 | 198.15 | 147.41 | 0.00 | 0.00 |
Maximum of Months | 1142.12 | 657.91 | 515.08 | 252.72 | 275.77 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 682.86 | 631.20 | 570.18 | 394.96 | 175.23 | 0.00 | 0.00 |
February | 687.85 | 549.10 | 550.17 | 347.79 | 202.38 | 0.00 | 0.00 |
March | 607.20 | 466.72 | 461.88 | 217.35 | 244.52 | 0.00 | 0.00 |
April | 595.96 | 230.79 | 358.17 | 101.51 | 256.66 | 0.00 | 0.00 |
May | 627.46 | 99.11 | 297.02 | 35.73 | 261.29 | 0.00 | 0.00 |
June | 751.33 | 33.76 | 276.38 | 24.43 | 251.95 | 0.00 | 0.00 |
July | 734.45 | 17.46 | 270.21 | 24.95 | 245.26 | 0.00 | 0.00 |
August | 731.58 | 37.97 | 297.17 | 54.97 | 242.20 | 0.00 | 0.00 |
September | 832.55 | 120.50 | 406.97 | 171.23 | 235.74 | 0.00 | 0.00 |
October | 838.00 | 253.58 | 516.45 | 307.19 | 209.26 | 0.00 | 0.00 |
November | 783.25 | 507.04 | 596.10 | 416.24 | 179.86 | 0.00 | 0.00 |
December | 678.22 | 683.75 | 583.68 | 402.02 | 181.66 | 0.00 | 0.00 |
Annual Sum or Average | 712.45 | 301.43 | 431.31 | 207.38 | 223.93 | 0.00 | 0.00 |
Minimum of Months | 595.96 | 17.46 | 270.21 | 24.43 | 175.23 | 0.00 | 0.00 |
Maximum of Months | 838.00 | 683.75 | 596.10 | 416.24 | 261.29 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.258816E+10 | 0.130800E+10 | 0.189136E+10 | 0.143314E+10 | 0.458222E+09 | 0.00 | 0.00 |
February | 0.225428E+10 | 0.103261E+10 | 0.160727E+10 | 0.113986E+10 | 0.467406E+09 | 0.00 | 0.00 |
March | 0.203523E+10 | 0.982449E+09 | 0.139207E+10 | 0.788679E+09 | 0.603391E+09 | 0.00 | 0.00 |
April | 0.161818E+10 | 0.501597E+09 | 0.938702E+09 | 0.352379E+09 | 0.586322E+09 | 0.00 | 0.00 |
May | 0.141762E+10 | 0.245247E+09 | 0.688337E+09 | 0.100947E+09 | 0.587390E+09 | 0.00 | 0.00 |
June | 0.149862E+10 | 82013881.80 | 0.569764E+09 | 35850177.24 | 0.533914E+09 | 0.00 | 0.00 |
July | 0.157418E+10 | 44653482.94 | 0.597898E+09 | 53010019.83 | 0.544888E+09 | 0.00 | 0.00 |
August | 0.177540E+10 | 94511521.45 | 0.754750E+09 | 0.191758E+09 | 0.562992E+09 | 0.00 | 0.00 |
September | 0.229640E+10 | 0.275052E+09 | 0.115668E+10 | 0.600953E+09 | 0.555729E+09 | 0.00 | 0.00 |
October | 0.270903E+10 | 0.561119E+09 | 0.164065E+10 | 0.111467E+10 | 0.525978E+09 | 0.00 | 0.00 |
November | 0.274745E+10 | 0.103556E+10 | 0.191093E+10 | 0.146165E+10 | 0.449279E+09 | 0.00 | 0.00 |
December | 0.260205E+10 | 0.142276E+10 | 0.194172E+10 | 0.145878E+10 | 0.482936E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.251166E+11 | 0.758558E+10 | 0.150901E+11 | 0.873168E+10 | 0.635845E+10 | 0.00 | 0.00 |
Minimum of Months | 0.141762E+10 | 44653482.94 | 0.569764E+09 | 35850177.24 | 0.449279E+09 | 0.00 | 0.00 |
Maximum of Months | 0.274745E+10 | 0.142276E+10 | 0.194172E+10 | 0.146165E+10 | 0.603391E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.724458E+10 | 0.371595E+10 | 0.532594E+10 | 0.403562E+10 | 0.129032E+10 | 0.00 | 0.00 |
February | 0.630826E+10 | 0.293298E+10 | 0.452597E+10 | 0.320978E+10 | 0.131618E+10 | 0.00 | 0.00 |
March | 0.568757E+10 | 0.278840E+10 | 0.391998E+10 | 0.222087E+10 | 0.169911E+10 | 0.00 | 0.00 |
April | 0.452198E+10 | 0.144465E+10 | 0.264332E+10 | 0.992277E+09 | 0.165105E+10 | 0.00 | 0.00 |
May | 0.394869E+10 | 0.728519E+09 | 0.193831E+10 | 0.284261E+09 | 0.165405E+10 | 0.00 | 0.00 |
June | 0.417120E+10 | 0.264166E+09 | 0.160442E+10 | 0.100952E+09 | 0.150347E+10 | 0.00 | 0.00 |
July | 0.437894E+10 | 0.156202E+09 | 0.168364E+10 | 0.149273E+09 | 0.153437E+10 | 0.00 | 0.00 |
August | 0.496111E+10 | 0.309958E+09 | 0.212533E+10 | 0.539978E+09 | 0.158535E+10 | 0.00 | 0.00 |
September | 0.645915E+10 | 0.815853E+09 | 0.325714E+10 | 0.169224E+10 | 0.156490E+10 | 0.00 | 0.00 |
October | 0.760725E+10 | 0.162097E+10 | 0.461996E+10 | 0.313884E+10 | 0.148112E+10 | 0.00 | 0.00 |
November | 0.770236E+10 | 0.294343E+10 | 0.538106E+10 | 0.411592E+10 | 0.126514E+10 | 0.00 | 0.00 |
December | 0.727685E+10 | 0.403535E+10 | 0.546774E+10 | 0.410783E+10 | 0.135992E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.702679E+11 | 0.217564E+11 | 0.424928E+11 | 0.245878E+11 | 0.179050E+11 | 0.00 | 0.00 |
Minimum of Months | 0.394869E+10 | 0.156202E+09 | 0.160442E+10 | 0.100952E+09 | 0.126514E+10 | 0.00 | 0.00 |
Maximum of Months | 0.770236E+10 | 0.403535E+10 | 0.546774E+10 | 0.411592E+10 | 0.169911E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.959853E+10 | 0.492615E+10 | 0.691870E+10 | 0.524250E+10 | 0.167620E+10 | 0.00 | 0.00 |
February | 0.837378E+10 | 0.388520E+10 | 0.587949E+10 | 0.416969E+10 | 0.170980E+10 | 0.00 | 0.00 |
March | 0.755747E+10 | 0.371203E+10 | 0.509227E+10 | 0.288503E+10 | 0.220724E+10 | 0.00 | 0.00 |
April | 0.604235E+10 | 0.192327E+10 | 0.343383E+10 | 0.128902E+10 | 0.214480E+10 | 0.00 | 0.00 |
May | 0.529535E+10 | 0.975347E+09 | 0.251798E+10 | 0.369271E+09 | 0.214871E+10 | 0.00 | 0.00 |
June | 0.561147E+10 | 0.348151E+09 | 0.208423E+10 | 0.131142E+09 | 0.195309E+10 | 0.00 | 0.00 |
July | 0.588539E+10 | 0.203047E+09 | 0.218715E+10 | 0.193914E+09 | 0.199323E+10 | 0.00 | 0.00 |
August | 0.666340E+10 | 0.399334E+09 | 0.276092E+10 | 0.701462E+09 | 0.205946E+10 | 0.00 | 0.00 |
September | 0.865174E+10 | 0.105299E+10 | 0.423121E+10 | 0.219832E+10 | 0.203289E+10 | 0.00 | 0.00 |
October | 0.101593E+11 | 0.210967E+10 | 0.600158E+10 | 0.407753E+10 | 0.192406E+10 | 0.00 | 0.00 |
November | 0.102434E+11 | 0.388016E+10 | 0.699030E+10 | 0.534681E+10 | 0.164349E+10 | 0.00 | 0.00 |
December | 0.963056E+10 | 0.535873E+10 | 0.710291E+10 | 0.533630E+10 | 0.176661E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.937127E+11 | 0.287741E+11 | 0.552006E+11 | 0.319410E+11 | 0.232596E+11 | 0.00 | 0.00 |
Minimum of Months | 0.529535E+10 | 0.203047E+09 | 0.208423E+10 | 0.131142E+09 | 0.164349E+10 | 0.00 | 0.00 |
Maximum of Months | 0.102434E+11 | 0.535873E+10 | 0.710291E+10 | 0.534681E+10 | 0.220724E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.777656E+09 | 0.776900E+09 | 0.661628E+09 | 0.445502E+09 | 0.216126E+09 | 0.00 | 0.00 |
February | 0.754379E+09 | 0.618611E+09 | 0.610259E+09 | 0.380562E+09 | 0.229697E+09 | 0.00 | 0.00 |
March | 0.954559E+09 | 0.583008E+09 | 0.717083E+09 | 0.392853E+09 | 0.324229E+09 | 0.00 | 0.00 |
April | 0.107389E+10 | 0.292456E+09 | 0.676285E+09 | 0.334351E+09 | 0.341935E+09 | 0.00 | 0.00 |
May | 0.124367E+10 | 0.142373E+09 | 0.683278E+09 | 0.312791E+09 | 0.370487E+09 | 0.00 | 0.00 |
June | 0.135460E+10 | 47804370.03 | 0.627908E+09 | 0.283748E+09 | 0.344161E+09 | 0.00 | 0.00 |
July | 0.129567E+10 | 26676857.38 | 0.591061E+09 | 0.245426E+09 | 0.345635E+09 | 0.00 | 0.00 |
August | 0.125700E+10 | 55119578.42 | 0.607067E+09 | 0.271168E+09 | 0.335899E+09 | 0.00 | 0.00 |
September | 0.127672E+10 | 0.162033E+09 | 0.683569E+09 | 0.372750E+09 | 0.310819E+09 | 0.00 | 0.00 |
October | 0.115540E+10 | 0.333952E+09 | 0.729374E+09 | 0.457483E+09 | 0.271891E+09 | 0.00 | 0.00 |
November | 0.915579E+09 | 0.618423E+09 | 0.704840E+09 | 0.487965E+09 | 0.216875E+09 | 0.00 | 0.00 |
December | 0.742150E+09 | 0.845817E+09 | 0.656450E+09 | 0.436397E+09 | 0.220053E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.128013E+11 | 0.450317E+10 | 0.794880E+10 | 0.442100E+10 | 0.352781E+10 | 0.00 | 0.00 |
Minimum of Months | 0.742150E+09 | 26676857.38 | 0.591061E+09 | 0.245426E+09 | 0.216126E+09 | 0.00 | 0.00 |
Maximum of Months | 0.135460E+10 | 0.845817E+09 | 0.729374E+09 | 0.487965E+09 | 0.370487E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.326400E+09 | 0.816994E+09 | 0.342309E+09 | 0.162146E+09 | 0.180162E+09 | 0.00 | 0.00 |
February | 0.376631E+09 | 0.647534E+09 | 0.352733E+09 | 0.155192E+09 | 0.197541E+09 | 0.00 | 0.00 |
March | 0.647905E+09 | 0.590722E+09 | 0.529172E+09 | 0.236921E+09 | 0.292251E+09 | 0.00 | 0.00 |
April | 0.902129E+09 | 0.287199E+09 | 0.588821E+09 | 0.265930E+09 | 0.322892E+09 | 0.00 | 0.00 |
May | 0.120040E+10 | 0.136474E+09 | 0.666968E+09 | 0.301660E+09 | 0.365308E+09 | 0.00 | 0.00 |
June | 0.137052E+10 | 46503904.38 | 0.638530E+09 | 0.292021E+09 | 0.346509E+09 | 0.00 | 0.00 |
July | 0.128922E+10 | 25909399.17 | 0.590530E+09 | 0.246488E+09 | 0.344041E+09 | 0.00 | 0.00 |
August | 0.115049E+10 | 53322181.28 | 0.557372E+09 | 0.235622E+09 | 0.321750E+09 | 0.00 | 0.00 |
September | 0.100020E+10 | 0.159038E+09 | 0.538673E+09 | 0.254037E+09 | 0.284635E+09 | 0.00 | 0.00 |
October | 0.731800E+09 | 0.335173E+09 | 0.476768E+09 | 0.237094E+09 | 0.239674E+09 | 0.00 | 0.00 |
November | 0.434199E+09 | 0.647597E+09 | 0.383093E+09 | 0.198972E+09 | 0.184121E+09 | 0.00 | 0.00 |
December | 0.288057E+09 | 0.900841E+09 | 0.326751E+09 | 0.147971E+09 | 0.178780E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.971794E+10 | 0.464731E+10 | 0.599172E+10 | 0.273405E+10 | 0.325767E+10 | 0.00 | 0.00 |
Minimum of Months | 0.288057E+09 | 25909399.17 | 0.326751E+09 | 0.147971E+09 | 0.178780E+09 | 0.00 | 0.00 |
Maximum of Months | 0.137052E+10 | 0.900841E+09 | 0.666968E+09 | 0.301660E+09 | 0.365308E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.392345E+09 | 0.242469E+09 | 0.299104E+09 | 0.226640E+09 | 72464826.42 | 0.00 | 0.00 |
February | 0.340752E+09 | 0.194475E+09 | 0.254178E+09 | 0.180261E+09 | 73917324.87 | 0.00 | 0.00 |
March | 0.301824E+09 | 0.186310E+09 | 0.220146E+09 | 0.124724E+09 | 95422629.83 | 0.00 | 0.00 |
April | 0.238688E+09 | 0.102672E+09 | 0.148450E+09 | 55726088.50 | 92723544.22 | 0.00 | 0.00 |
May | 0.206902E+09 | 54827301.07 | 0.108857E+09 | 15964013.69 | 92892545.85 | 0.00 | 0.00 |
June | 0.222227E+09 | 21556791.11 | 90105188.78 | 5669429.11 | 84435759.67 | 0.00 | 0.00 |
July | 0.230796E+09 | 15651122.90 | 94554156.30 | 8383125.91 | 86171030.39 | 0.00 | 0.00 |
August | 0.263875E+09 | 26472808.71 | 0.119359E+09 | 30325060.49 | 89033931.16 | 0.00 | 0.00 |
September | 0.351092E+09 | 61150568.20 | 0.182921E+09 | 95036114.58 | 87885276.20 | 0.00 | 0.00 |
October | 0.413633E+09 | 0.115086E+09 | 0.259457E+09 | 0.176276E+09 | 83180150.54 | 0.00 | 0.00 |
November | 0.420291E+09 | 0.194276E+09 | 0.302200E+09 | 0.231149E+09 | 71050625.13 | 0.00 | 0.00 |
December | 0.396671E+09 | 0.256603E+09 | 0.307068E+09 | 0.230695E+09 | 76373138.43 | 0.00 | 0.00 |
Annual Sum or Average | 0.377909E+10 | 0.147155E+10 | 0.238640E+10 | 0.138085E+10 | 0.100555E+10 | 0.00 | 0.00 |
Minimum of Months | 0.206902E+09 | 15651122.90 | 90105188.78 | 5669429.11 | 71050625.13 | 0.00 | 0.00 |
Maximum of Months | 0.420291E+09 | 0.256603E+09 | 0.307068E+09 | 0.231149E+09 | 95422629.83 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 8540331.93 | 0.246730E+09 | 43713969.60 | 0.00 | 43713969.60 | 0.00 | 0.00 |
February | 23580161.30 | 0.192480E+09 | 48213648.10 | 0.00 | 48213648.10 | 0.00 | 0.00 |
March | 54959432.08 | 0.171676E+09 | 69870982.94 | 2765.95 | 69868216.99 | 0.00 | 0.00 |
April | 0.110964E+09 | 78461667.44 | 78518344.10 | 1000279.47 | 77518064.63 | 0.00 | 0.00 |
May | 0.192312E+09 | 34732635.61 | 95843144.60 | 7063304.15 | 88779840.45 | 0.00 | 0.00 |
June | 0.260101E+09 | 11158549.39 | 98633813.54 | 12290815.53 | 86342998.01 | 0.00 | 0.00 |
July | 0.251240E+09 | 5897204.96 | 94160895.41 | 9236150.10 | 84924745.31 | 0.00 | 0.00 |
August | 0.199808E+09 | 12967140.09 | 79637162.39 | 1894638.37 | 77742524.03 | 0.00 | 0.00 |
September | 0.140499E+09 | 41355941.49 | 67049393.63 | 84739.01 | 66964654.62 | 0.00 | 0.00 |
October | 77280343.79 | 93349095.14 | 57430655.00 | 0.00 | 57430655.00 | 0.00 | 0.00 |
November | 19424185.98 | 0.191420E+09 | 44867884.08 | 0.00 | 44867884.08 | 0.00 | 0.00 |
December | 5836933.57 | 0.273183E+09 | 43375413.74 | 0.00 | 43375413.74 | 0.00 | 0.00 |
Annual Sum or Average | 0.134455E+10 | 0.135341E+10 | 0.821315E+09 | 31572692.58 | 0.789743E+09 | 0.00 | 0.00 |
Minimum of Months | 5836933.57 | 5897204.96 | 43375413.74 | 0.00 | 43375413.74 | 0.00 | 0.00 |
Maximum of Months | 0.260101E+09 | 0.273183E+09 | 98633813.54 | 12290815.53 | 88779840.45 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.741281E+09 | 0.762511E+09 | 0.646361E+09 | 0.430960E+09 | 0.215402E+09 | 0.00 | 0.00 |
February | 0.796386E+09 | 0.600872E+09 | 0.648005E+09 | 0.413664E+09 | 0.234341E+09 | 0.00 | 0.00 |
March | 0.937278E+09 | 0.549960E+09 | 0.725871E+09 | 0.404058E+09 | 0.321813E+09 | 0.00 | 0.00 |
April | 0.110299E+10 | 0.266096E+09 | 0.711319E+09 | 0.361253E+09 | 0.350066E+09 | 0.00 | 0.00 |
May | 0.125361E+10 | 0.129211E+09 | 0.696105E+09 | 0.324180E+09 | 0.371925E+09 | 0.00 | 0.00 |
June | 0.139725E+10 | 44522584.02 | 0.654827E+09 | 0.308561E+09 | 0.346266E+09 | 0.00 | 0.00 |
July | 0.134478E+10 | 25523471.83 | 0.620963E+09 | 0.273320E+09 | 0.347643E+09 | 0.00 | 0.00 |
August | 0.129190E+10 | 51822824.60 | 0.628139E+09 | 0.283153E+09 | 0.344986E+09 | 0.00 | 0.00 |
September | 0.126993E+10 | 0.149255E+09 | 0.688511E+09 | 0.381390E+09 | 0.307121E+09 | 0.00 | 0.00 |
October | 0.107012E+10 | 0.320885E+09 | 0.688060E+09 | 0.416283E+09 | 0.271777E+09 | 0.00 | 0.00 |
November | 0.874857E+09 | 0.600100E+09 | 0.692953E+09 | 0.472029E+09 | 0.220924E+09 | 0.00 | 0.00 |
December | 0.727509E+09 | 0.828653E+09 | 0.656523E+09 | 0.432885E+09 | 0.223638E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.128079E+11 | 0.432941E+10 | 0.805764E+10 | 0.450174E+10 | 0.355590E+10 | 0.00 | 0.00 |
Minimum of Months | 0.727509E+09 | 25523471.83 | 0.620963E+09 | 0.273320E+09 | 0.215402E+09 | 0.00 | 0.00 |
Maximum of Months | 0.139725E+10 | 0.828653E+09 | 0.725871E+09 | 0.472029E+09 | 0.371925E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.257721E+09 | 0.769225E+09 | 0.327041E+09 | 0.147604E+09 | 0.179438E+09 | 0.00 | 0.00 |
February | 0.389757E+09 | 0.600408E+09 | 0.390478E+09 | 0.188293E+09 | 0.202185E+09 | 0.00 | 0.00 |
March | 0.616863E+09 | 0.544867E+09 | 0.537961E+09 | 0.248126E+09 | 0.289835E+09 | 0.00 | 0.00 |
April | 0.930979E+09 | 0.262371E+09 | 0.623855E+09 | 0.292832E+09 | 0.331023E+09 | 0.00 | 0.00 |
May | 0.121503E+10 | 0.128475E+09 | 0.679796E+09 | 0.313049E+09 | 0.366746E+09 | 0.00 | 0.00 |
June | 0.141501E+10 | 44665985.22 | 0.665449E+09 | 0.316834E+09 | 0.348614E+09 | 0.00 | 0.00 |
July | 0.133904E+10 | 25240192.30 | 0.620433E+09 | 0.274383E+09 | 0.346050E+09 | 0.00 | 0.00 |
August | 0.118602E+10 | 51040455.05 | 0.578444E+09 | 0.247607E+09 | 0.330837E+09 | 0.00 | 0.00 |
September | 0.991337E+09 | 0.145635E+09 | 0.543615E+09 | 0.262677E+09 | 0.280938E+09 | 0.00 | 0.00 |
October | 0.635857E+09 | 0.313370E+09 | 0.435454E+09 | 0.195894E+09 | 0.239560E+09 | 0.00 | 0.00 |
November | 0.367207E+09 | 0.599679E+09 | 0.371206E+09 | 0.183035E+09 | 0.188171E+09 | 0.00 | 0.00 |
December | 0.234966E+09 | 0.845007E+09 | 0.326824E+09 | 0.144459E+09 | 0.182365E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.957979E+10 | 0.432998E+10 | 0.610055E+10 | 0.281479E+10 | 0.328576E+10 | 0.00 | 0.00 |
Minimum of Months | 0.234966E+09 | 25240192.30 | 0.326824E+09 | 0.144459E+09 | 0.179438E+09 | 0.00 | 0.00 |
Maximum of Months | 0.141501E+10 | 0.845007E+09 | 0.679796E+09 | 0.316834E+09 | 0.366746E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.851641E+09 | 0.955933E+09 | 0.742775E+09 | 0.491065E+09 | 0.251710E+09 | 0.00 | 0.00 |
February | 0.793493E+09 | 0.751664E+09 | 0.655180E+09 | 0.390575E+09 | 0.264605E+09 | 0.00 | 0.00 |
March | 0.813455E+09 | 0.705424E+09 | 0.628360E+09 | 0.270247E+09 | 0.358112E+09 | 0.00 | 0.00 |
April | 0.824638E+09 | 0.336492E+09 | 0.491746E+09 | 0.122910E+09 | 0.368836E+09 | 0.00 | 0.00 |
May | 0.941448E+09 | 0.155105E+09 | 0.443490E+09 | 49891063.49 | 0.393599E+09 | 0.00 | 0.00 |
June | 0.110847E+10 | 55338327.15 | 0.408907E+09 | 38910104.08 | 0.369997E+09 | 0.00 | 0.00 |
July | 0.111542E+10 | 30060320.72 | 0.408857E+09 | 38172500.78 | 0.370684E+09 | 0.00 | 0.00 |
August | 0.107203E+10 | 62971833.76 | 0.431139E+09 | 69810394.97 | 0.361328E+09 | 0.00 | 0.00 |
September | 0.112261E+10 | 0.187482E+09 | 0.541591E+09 | 0.206100E+09 | 0.335491E+09 | 0.00 | 0.00 |
October | 0.111856E+10 | 0.386175E+09 | 0.686584E+09 | 0.381942E+09 | 0.304642E+09 | 0.00 | 0.00 |
November | 0.960907E+09 | 0.744491E+09 | 0.751982E+09 | 0.500836E+09 | 0.251146E+09 | 0.00 | 0.00 |
December | 0.834998E+09 | 0.104085E+10 | 0.759297E+09 | 0.499852E+09 | 0.259445E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.115577E+11 | 0.541199E+10 | 0.694991E+10 | 0.306031E+10 | 0.388960E+10 | 0.00 | 0.00 |
Minimum of Months | 0.793493E+09 | 30060320.72 | 0.408857E+09 | 38172500.78 | 0.251146E+09 | 0.00 | 0.00 |
Maximum of Months | 0.112261E+10 | 0.104085E+10 | 0.759297E+09 | 0.500836E+09 | 0.393599E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.773455E+09 | 0.768323E+09 | 0.661628E+09 | 0.445502E+09 | 0.216126E+09 | 0.00 | 0.00 |
February | 0.748102E+09 | 0.612308E+09 | 0.610259E+09 | 0.380562E+09 | 0.229697E+09 | 0.00 | 0.00 |
March | 0.942279E+09 | 0.577886E+09 | 0.717083E+09 | 0.392853E+09 | 0.324229E+09 | 0.00 | 0.00 |
April | 0.105768E+10 | 0.290513E+09 | 0.676285E+09 | 0.334351E+09 | 0.341935E+09 | 0.00 | 0.00 |
May | 0.122638E+10 | 0.140842E+09 | 0.683278E+09 | 0.312791E+09 | 0.370487E+09 | 0.00 | 0.00 |
June | 0.133929E+10 | 47323254.57 | 0.627908E+09 | 0.283748E+09 | 0.344161E+09 | 0.00 | 0.00 |
July | 0.127798E+10 | 26890249.03 | 0.591061E+09 | 0.245426E+09 | 0.345635E+09 | 0.00 | 0.00 |
August | 0.123981E+10 | 55241381.62 | 0.607067E+09 | 0.271168E+09 | 0.335899E+09 | 0.00 | 0.00 |
September | 0.126010E+10 | 0.161695E+09 | 0.683569E+09 | 0.372750E+09 | 0.310819E+09 | 0.00 | 0.00 |
October | 0.114160E+10 | 0.332899E+09 | 0.729374E+09 | 0.457483E+09 | 0.271891E+09 | 0.00 | 0.00 |
November | 0.908258E+09 | 0.612459E+09 | 0.704840E+09 | 0.487965E+09 | 0.216875E+09 | 0.00 | 0.00 |
December | 0.741351E+09 | 0.834727E+09 | 0.656450E+09 | 0.436397E+09 | 0.220053E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.126563E+11 | 0.446111E+10 | 0.794880E+10 | 0.442100E+10 | 0.352781E+10 | 0.00 | 0.00 |
Minimum of Months | 0.741351E+09 | 26890249.03 | 0.591061E+09 | 0.245426E+09 | 0.216126E+09 | 0.00 | 0.00 |
Maximum of Months | 0.133929E+10 | 0.834727E+09 | 0.729374E+09 | 0.487965E+09 | 0.370487E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.326587E+09 | 0.805783E+09 | 0.342309E+09 | 0.162146E+09 | 0.180162E+09 | 0.00 | 0.00 |
February | 0.374315E+09 | 0.639089E+09 | 0.352733E+09 | 0.155192E+09 | 0.197541E+09 | 0.00 | 0.00 |
March | 0.639932E+09 | 0.584501E+09 | 0.529172E+09 | 0.236921E+09 | 0.292251E+09 | 0.00 | 0.00 |
April | 0.887684E+09 | 0.285233E+09 | 0.588821E+09 | 0.265930E+09 | 0.322892E+09 | 0.00 | 0.00 |
May | 0.118336E+10 | 0.135075E+09 | 0.666968E+09 | 0.301660E+09 | 0.365308E+09 | 0.00 | 0.00 |
June | 0.135455E+10 | 46128656.68 | 0.638530E+09 | 0.292021E+09 | 0.346509E+09 | 0.00 | 0.00 |
July | 0.127130E+10 | 26160011.87 | 0.590530E+09 | 0.246488E+09 | 0.344041E+09 | 0.00 | 0.00 |
August | 0.113415E+10 | 53466799.00 | 0.557372E+09 | 0.235622E+09 | 0.321750E+09 | 0.00 | 0.00 |
September | 0.985603E+09 | 0.158548E+09 | 0.538673E+09 | 0.254037E+09 | 0.284635E+09 | 0.00 | 0.00 |
October | 0.721145E+09 | 0.333178E+09 | 0.476768E+09 | 0.237094E+09 | 0.239674E+09 | 0.00 | 0.00 |
November | 0.431014E+09 | 0.638986E+09 | 0.383093E+09 | 0.198972E+09 | 0.184121E+09 | 0.00 | 0.00 |
December | 0.290046E+09 | 0.886904E+09 | 0.326751E+09 | 0.147971E+09 | 0.178780E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.959969E+10 | 0.459305E+10 | 0.599172E+10 | 0.273405E+10 | 0.325767E+10 | 0.00 | 0.00 |
Minimum of Months | 0.290046E+09 | 26160011.87 | 0.326751E+09 | 0.147971E+09 | 0.178780E+09 | 0.00 | 0.00 |
Maximum of Months | 0.135455E+10 | 0.886904E+09 | 0.666968E+09 | 0.301660E+09 | 0.365308E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.720156E+09 | 0.404646E+09 | 0.548441E+09 | 0.415568E+09 | 0.132872E+09 | 0.00 | 0.00 |
February | 0.627146E+09 | 0.318940E+09 | 0.466063E+09 | 0.330528E+09 | 0.135536E+09 | 0.00 | 0.00 |
March | 0.559695E+09 | 0.300140E+09 | 0.403662E+09 | 0.228694E+09 | 0.174968E+09 | 0.00 | 0.00 |
April | 0.449515E+09 | 0.148917E+09 | 0.272199E+09 | 0.102180E+09 | 0.170019E+09 | 0.00 | 0.00 |
May | 0.402926E+09 | 68947983.96 | 0.199600E+09 | 29271767.90 | 0.170329E+09 | 0.00 | 0.00 |
June | 0.439594E+09 | 21655569.63 | 0.165218E+09 | 10395519.34 | 0.154822E+09 | 0.00 | 0.00 |
July | 0.455420E+09 | 12116833.16 | 0.173375E+09 | 15371379.69 | 0.158004E+09 | 0.00 | 0.00 |
August | 0.509593E+09 | 26349933.25 | 0.218858E+09 | 55604320.39 | 0.163253E+09 | 0.00 | 0.00 |
September | 0.653871E+09 | 79835313.53 | 0.335406E+09 | 0.174259E+09 | 0.161147E+09 | 0.00 | 0.00 |
October | 0.766136E+09 | 0.170114E+09 | 0.475742E+09 | 0.323222E+09 | 0.152520E+09 | 0.00 | 0.00 |
November | 0.773419E+09 | 0.317477E+09 | 0.554116E+09 | 0.423837E+09 | 0.130279E+09 | 0.00 | 0.00 |
December | 0.727935E+09 | 0.437361E+09 | 0.563043E+09 | 0.423004E+09 | 0.140039E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.708540E+10 | 0.230650E+10 | 0.437572E+10 | 0.253194E+10 | 0.184379E+10 | 0.00 | 0.00 |
Minimum of Months | 0.402926E+09 | 12116833.16 | 0.165218E+09 | 10395519.34 | 0.130279E+09 | 0.00 | 0.00 |
Maximum of Months | 0.773419E+09 | 0.437361E+09 | 0.563043E+09 | 0.423837E+09 | 0.174968E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 58951849.05 | 0.223366E+10 | 0.382432E+09 | 0.00 | 0.382432E+09 | 0.00 | 0.00 |
February | 0.190511E+09 | 0.174036E+10 | 0.421798E+09 | 0.00 | 0.421798E+09 | 0.00 | 0.00 |
March | 0.462566E+09 | 0.155953E+10 | 0.611267E+09 | 24197.95 | 0.611243E+09 | 0.00 | 0.00 |
April | 0.975923E+09 | 0.746464E+09 | 0.686918E+09 | 8750953.90 | 0.678167E+09 | 0.00 | 0.00 |
May | 0.168836E+10 | 0.362580E+09 | 0.838485E+09 | 61793379.53 | 0.776691E+09 | 0.00 | 0.00 |
June | 0.225356E+10 | 0.141621E+09 | 0.862899E+09 | 0.107526E+09 | 0.755372E+09 | 0.00 | 0.00 |
July | 0.217115E+10 | 90480253.71 | 0.823767E+09 | 80802541.81 | 0.742965E+09 | 0.00 | 0.00 |
August | 0.173765E+10 | 0.165738E+09 | 0.696706E+09 | 16575260.69 | 0.680131E+09 | 0.00 | 0.00 |
September | 0.124658E+10 | 0.418525E+09 | 0.586582E+09 | 741339.97 | 0.585841E+09 | 0.00 | 0.00 |
October | 0.674602E+09 | 0.873986E+09 | 0.502433E+09 | 0.00 | 0.502433E+09 | 0.00 | 0.00 |
November | 0.153535E+09 | 0.173080E+10 | 0.392527E+09 | 0.00 | 0.392527E+09 | 0.00 | 0.00 |
December | 40832122.20 | 0.245907E+10 | 0.379470E+09 | 0.00 | 0.379470E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.116542E+11 | 0.125228E+11 | 0.718528E+10 | 0.276214E+09 | 0.690907E+10 | 0.00 | 0.00 |
Minimum of Months | 40832122.20 | 90480253.71 | 0.379470E+09 | 0.00 | 0.379470E+09 | 0.00 | 0.00 |
Maximum of Months | 0.225356E+10 | 0.245907E+10 | 0.862899E+09 | 0.107526E+09 | 0.776691E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 53267786.88 | 0.227861E+10 | 0.382432E+09 | 0.00 | 0.382432E+09 | 0.00 | 0.00 |
February | 0.181553E+09 | 0.177825E+10 | 0.421798E+09 | 0.00 | 0.421798E+09 | 0.00 | 0.00 |
March | 0.446543E+09 | 0.159791E+10 | 0.611267E+09 | 24197.95 | 0.611243E+09 | 0.00 | 0.00 |
April | 0.950032E+09 | 0.776114E+09 | 0.686918E+09 | 8750953.90 | 0.678167E+09 | 0.00 | 0.00 |
May | 0.165009E+10 | 0.384845E+09 | 0.838485E+09 | 61793379.53 | 0.776691E+09 | 0.00 | 0.00 |
June | 0.221150E+10 | 0.153627E+09 | 0.862899E+09 | 0.107526E+09 | 0.755372E+09 | 0.00 | 0.00 |
July | 0.212746E+10 | 0.102383E+09 | 0.823767E+09 | 80802541.81 | 0.742965E+09 | 0.00 | 0.00 |
August | 0.169849E+10 | 0.181652E+09 | 0.696706E+09 | 16575260.69 | 0.680131E+09 | 0.00 | 0.00 |
September | 0.121917E+10 | 0.442545E+09 | 0.586582E+09 | 741339.97 | 0.585841E+09 | 0.00 | 0.00 |
October | 0.654921E+09 | 0.907268E+09 | 0.502433E+09 | 0.00 | 0.502433E+09 | 0.00 | 0.00 |
November | 0.144338E+09 | 0.177121E+10 | 0.392527E+09 | 0.00 | 0.392527E+09 | 0.00 | 0.00 |
December | 36967489.12 | 0.250473E+10 | 0.379470E+09 | 0.00 | 0.379470E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.113743E+11 | 0.128791E+11 | 0.718528E+10 | 0.276214E+09 | 0.690907E+10 | 0.00 | 0.00 |
Minimum of Months | 36967489.12 | 0.102383E+09 | 0.379470E+09 | 0.00 | 0.379470E+09 | 0.00 | 0.00 |
Maximum of Months | 0.221150E+10 | 0.250473E+10 | 0.862899E+09 | 0.107526E+09 | 0.776691E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.100010E+10 | 0.164547E+10 | 0.973364E+09 | 0.578542E+09 | 0.394822E+09 | 0.00 | 0.00 |
February | 0.122485E+10 | 0.130379E+10 | 0.103844E+10 | 0.601931E+09 | 0.436505E+09 | 0.00 | 0.00 |
March | 0.161832E+10 | 0.120870E+10 | 0.126377E+10 | 0.652149E+09 | 0.611620E+09 | 0.00 | 0.00 |
April | 0.216064E+10 | 0.627271E+09 | 0.133510E+10 | 0.654044E+09 | 0.681055E+09 | 0.00 | 0.00 |
May | 0.260774E+10 | 0.344511E+09 | 0.137582E+10 | 0.637186E+09 | 0.738635E+09 | 0.00 | 0.00 |
June | 0.296038E+10 | 0.137089E+09 | 0.132020E+10 | 0.625352E+09 | 0.694846E+09 | 0.00 | 0.00 |
July | 0.284103E+10 | 0.100327E+09 | 0.124132E+10 | 0.547666E+09 | 0.693659E+09 | 0.00 | 0.00 |
August | 0.264528E+10 | 0.165745E+09 | 0.120652E+10 | 0.530726E+09 | 0.675789E+09 | 0.00 | 0.00 |
September | 0.245474E+10 | 0.357446E+09 | 0.123206E+10 | 0.644030E+09 | 0.588031E+09 | 0.00 | 0.00 |
October | 0.182311E+10 | 0.724219E+09 | 0.112346E+10 | 0.612150E+09 | 0.511313E+09 | 0.00 | 0.00 |
November | 0.129034E+10 | 0.129900E+10 | 0.106411E+10 | 0.655039E+09 | 0.409076E+09 | 0.00 | 0.00 |
December | 0.966518E+09 | 0.176213E+10 | 0.983308E+09 | 0.577324E+09 | 0.405984E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.235930E+11 | 0.967570E+10 | 0.141575E+11 | 0.731614E+10 | 0.684134E+10 | 0.00 | 0.00 |
Minimum of Months | 0.966518E+09 | 0.100327E+09 | 0.973364E+09 | 0.530726E+09 | 0.394822E+09 | 0.00 | 0.00 |
Maximum of Months | 0.296038E+10 | 0.176213E+10 | 0.137582E+10 | 0.655039E+09 | 0.738635E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.182898E+10 | 0.169062E+10 | 0.152718E+10 | 0.105785E+10 | 0.469332E+09 | 0.00 | 0.00 |
February | 0.166405E+10 | 0.132839E+10 | 0.133098E+10 | 0.841376E+09 | 0.489606E+09 | 0.00 | 0.00 |
March | 0.162631E+10 | 0.125006E+10 | 0.123709E+10 | 0.582162E+09 | 0.654925E+09 | 0.00 | 0.00 |
April | 0.154473E+10 | 0.598200E+09 | 0.928373E+09 | 0.263104E+09 | 0.665269E+09 | 0.00 | 0.00 |
May | 0.168059E+10 | 0.265465E+09 | 0.795528E+09 | 95695732.11 | 0.699832E+09 | 0.00 | 0.00 |
June | 0.194744E+10 | 87505084.95 | 0.716374E+09 | 63322576.03 | 0.653051E+09 | 0.00 | 0.00 |
July | 0.196716E+10 | 46765894.13 | 0.723725E+09 | 66827933.17 | 0.656897E+09 | 0.00 | 0.00 |
August | 0.195947E+10 | 0.101702E+09 | 0.795946E+09 | 0.147226E+09 | 0.648721E+09 | 0.00 | 0.00 |
September | 0.215798E+10 | 0.312329E+09 | 0.105488E+10 | 0.443840E+09 | 0.611036E+09 | 0.00 | 0.00 |
October | 0.224449E+10 | 0.679177E+09 | 0.138326E+10 | 0.822779E+09 | 0.560482E+09 | 0.00 | 0.00 |
November | 0.203019E+10 | 0.131426E+10 | 0.154509E+10 | 0.107890E+10 | 0.466191E+09 | 0.00 | 0.00 |
December | 0.181655E+10 | 0.183137E+10 | 0.156334E+10 | 0.107678E+10 | 0.486559E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.224680E+11 | 0.950583E+10 | 0.136018E+11 | 0.653986E+10 | 0.706190E+10 | 0.00 | 0.00 |
Minimum of Months | 0.154473E+10 | 46765894.13 | 0.716374E+09 | 63322576.03 | 0.466191E+09 | 0.00 | 0.00 |
Maximum of Months | 0.224449E+10 | 0.183137E+10 | 0.156334E+10 | 0.107890E+10 | 0.699832E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 8.14 | 3.28 | -3.0 | 3.49 | -5.4 | 41.12 | 223.64 | 0.00 |
February | 10.27 | 3.71 | -4.6 | 3.82 | -5.0 | 51.61 | 245.22 | 0.00 |
March | 12.55 | 4.68 | -5.5 | 4.62 | -3.1 | 72.41 | 273.25 | 0.00 |
April | 19.23 | 8.50 | -2.7 | 4.72 | 3.38 | 79.21 | 314.56 | 0.00 |
May | 23.84 | 12.23 | 2.64 | 5.25 | 8.38 | 86.83 | 326.20 | 0.00 |
June | 27.86 | 15.03 | 5.88 | 4.15 | 14.09 | 80.19 | 344.14 | 0.01 |
July | 27.54 | 18.92 | 14.64 | 3.53 | 17.44 | 86.25 | 283.04 | 0.01 |
August | 26.28 | 17.11 | 12.00 | 3.28 | 15.48 | 80.55 | 269.68 | 0.02 |
September | 23.38 | 15.82 | 11.20 | 2.23 | 11.29 | 66.71 | 294.09 | 0.00 |
October | 18.30 | 12.02 | 7.27 | 3.24 | 6.21 | 54.59 | 257.93 | 0.01 |
November | 11.18 | 5.22 | -1.5 | 3.40 | -3.3 | 40.23 | 258.80 | 0.00 |
December | 6.79 | 1.84 | -4.8 | 2.82 | -8.9 | 42.65 | 217.21 | 0.00 |
Annual Sum or Average | 17.98 | 9.90 | 2.67 | 3.71 | 4.26 | 65.29 | 275.60 | 0.00 |
Minimum of Months | 6.79 | 1.84 | -5.5 | 2.23 | -8.9 | 40.23 | 217.21 | 0.00 |
Maximum of Months | 27.86 | 18.92 | 14.64 | 5.25 | 17.44 | 86.83 | 344.14 | 0.02 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 20.60 | 03-JAN-14:00 | 8.39 | -5.0 | 9.80 | 2.22 | 118.50 | 530.50 |
February | 23.30 | 20-FEB-14:00 | 8.88 | -7.8 | 4.10 | 4.10 | 55.00 | 955.00 |
March | 25.00 | 21-MAR-15:00 | 9.53 | -8.3 | 6.20 | 5.54 | 50.00 | 873.00 |
April | 32.20 | 21-APR-13:00 | 15.21 | 2.80 | 13.90 | 18.28 | 265.50 | 638.50 |
May | 35.00 | 19-MAY-13:00 | 17.23 | 6.10 | 10.30 | 21.78 | 145.00 | 874.50 |
June | 38.90 | 02-JUN-15:00 | 16.22 | -1.1 | 4.60 | 20.40 | 234.50 | 284.00 |
July | 38.30 | 01-JUL-16:00 | 19.19 | 8.90 | 3.60 | 26.81 | 165.50 | 256.50 |
August | 37.20 | 07-AUG-15:00 | 17.89 | 6.70 | 5.70 | 24.66 | 143.50 | 615.00 |
September | 33.90 | 19-SEP-13:00 | 16.85 | 6.70 | 3.10 | 17.75 | 113.00 | 912.00 |
October | 32.80 | 01-OCT-14:00 | 15.90 | 4.40 | 5.70 | 16.12 | 127.50 | 736.50 |
November | 23.90 | 03-NOV-15:00 | 13.45 | 6.10 | 5.70 | 12.22 | 48.50 | 648.50 |
December | 18.30 | 10-DEC-14:00 | 7.97 | -2.8 | 7.20 | 4.10 | 123.00 | 52.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 18.30 | 7.97 | -8.3 | 3.10 | 2.22 | 48.50 | 52.50 | |
Maximum of Months | 38.90 | 19.19 | 8.90 | 13.90 | 26.81 | 265.50 | 955.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -4.4 | 27-JAN-06:00 | -7.5 | -15.0 | 3.60 | -23.6 | 0.00 | 0.00 |
February | -5.6 | 03-FEB-06:00 | -7.5 | -11.7 | 1.50 | -23.9 | 0.00 | 0.00 |
March | -3.9 | 02-MAR-04:00 | -6.5 | -12.8 | 1.50 | -21.3 | 0.00 | 0.00 |
April | 3.30 | 12-APR-05:00 | -1.8 | -9.4 | 2.10 | -14.9 | 37.00 | 217.50 |
May | 9.40 | 02-MAY-05:00 | 3.98 | -2.2 | 3.60 | -7.6 | 51.00 | 277.50 |
June | 15.00 | 13-JUN-04:00 | 4.43 | -10.6 | 2.10 | -4.3 | 0.00 | 0.00 |
July | 17.80 | 05-JUL-05:00 | 15.98 | 15.00 | 4.10 | 4.31 | 39.00 | 249.00 |
August | 16.70 | 31-AUG-05:00 | 13.89 | 12.20 | 4.10 | 2.64 | 36.00 | 126.50 |
September | 8.30 | 30-SEP-05:00 | 5.77 | 3.30 | 1.50 | -7.3 | 0.00 | 0.00 |
October | 6.70 | 11-OCT-05:00 | 5.82 | 5.00 | 1.50 | -5.5 | 0.00 | 0.00 |
November | -0.6 | 17-NOV-03:00 | -3.1 | -6.7 | 1.50 | -18.1 | 0.00 | 0.00 |
December | -4.4 | 27-DEC-06:00 | -5.1 | -6.1 | 2.10 | -18.6 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -5.6 | -7.5 | -15.0 | 1.50 | -23.9 | 0.00 | 0.00 | |
Maximum of Months | 17.80 | 15.98 | 15.00 | 4.10 | 4.31 | 51.00 | 277.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.18 | 12-JAN-15:00 | 18.90 | 2.80 | 3.60 | 6.15 | 70.50 | 491.50 |
February | 11.42 | 13-FEB-16:00 | 12.80 | 10.60 | 4.10 | 6.55 | 34.00 | 18.50 |
March | 10.75 | 10-MAR-18:00 | 13.30 | 8.90 | 1.50 | 8.54 | 0.00 | 0.00 |
April | 15.74 | 29-APR-13:00 | 30.00 | 6.70 | 4.10 | 18.28 | 336.50 | 432.50 |
May | 19.12 | 24-MAY-12:00 | 27.80 | 15.00 | 5.20 | 17.57 | 188.50 | 862.00 |
June | 20.21 | 03-JUN-14:00 | 33.90 | 13.90 | 8.80 | 23.66 | 264.50 | 316.00 |
July | 22.88 | 20-JUL-15:39 | 25.53 | 21.87 | 2.93 | 18.99 | 184.00 | 15.83 |
August | 21.18 | 02-AUG-11:00 | 30.60 | 17.20 | 3.60 | 20.75 | 154.50 | 850.00 |
September | 20.65 | 14-SEP-09:00 | 25.00 | 18.90 | 2.10 | 14.47 | 126.50 | 835.50 |
October | 19.64 | 03-OCT-13:00 | 32.80 | 13.30 | 2.60 | 21.44 | 224.50 | 577.50 |
November | 13.57 | 03-NOV-14:00 | 23.30 | 7.20 | 0.00 | 10.88 | 72.50 | 802.00 |
December | 8.30 | 10-DEC-12:00 | 17.20 | -0.6 | 5.70 | 1.58 | 198.50 | 507.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 8.30 | 12.80 | -0.6 | 0.00 | 1.58 | 0.00 | 0.00 | |
Maximum of Months | 22.88 | 33.90 | 21.87 | 8.80 | 23.66 | 336.50 | 862.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 9.00 | 16-JAN-01:00 | 9.00 | 9.00 | 2.10 | 4.51 | 0.00 | 0.00 |
February | 10.60 | 13-FEB-13:09 | 12.20 | 11.24 | 5.53 | 5.71 | 147.33 | 0.00 |
March | 10.00 | 11-MAR-00:00 | 10.60 | 10.24 | 2.10 | 6.15 | 0.00 | 0.00 |
April | 10.60 | 17-APR-01:00 | 17.80 | 13.38 | 7.20 | 3.48 | 0.00 | 0.00 |
May | 15.00 | 24-MAY-10:00 | 25.60 | 18.41 | 7.20 | 15.39 | 171.00 | 872.50 |
June | 17.20 | 19-JUN-17:00 | 23.90 | 19.20 | 3.60 | 15.39 | 86.00 | 324.00 |
July | 22.20 | 20-JUL-14:00 | 24.40 | 22.82 | 4.60 | 17.93 | 283.00 | 59.50 |
August | 18.90 | 01-AUG-20:00 | 22.20 | 19.91 | 4.60 | 17.75 | 0.00 | 0.00 |
September | 19.40 | 22-SEP-01:00 | 20.60 | 19.76 | 1.50 | 16.30 | 0.00 | 0.00 |
October | 17.20 | 03-OCT-19:00 | 23.30 | 19.11 | 4.60 | 18.46 | 0.00 | 0.00 |
November | 10.00 | 01-NOV-09:00 | 13.30 | 11.28 | 3.10 | 8.94 | 123.50 | 0.00 |
December | 6.10 | 13-DEC-00:00 | 8.30 | 7.10 | 7.70 | 3.06 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.10 | 8.30 | 7.10 | 1.50 | 3.06 | 0.00 | 0.00 | |
Maximum of Months | 22.20 | 25.60 | 22.82 | 7.70 | 18.46 | 283.00 | 872.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 15.16 | 28.38 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 15.21 | 35.58 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 16.80 | 47.71 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 19.62 | 58.45 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 22.88 | 63.58 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 25.71 | 66.73 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 27.35 | 58.19 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 27.33 | 54.44 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 25.68 | 50.89 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 22.83 | 39.37 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 19.57 | 32.11 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 16.77 | 26.90 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 21.28 | 46.90 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 15.16 | 26.90 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 27.35 | 66.73 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH BOOSTER E WATER HEATER
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.770788E+10 | -0.754278E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -165107042.0 | 81.21 | 0.00 | 0.00 |
February | 0.696485E+10 | -0.681596E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -148888144.3 | 81.21 | 0.00 | 0.00 |
March | 0.770612E+10 | -0.754148E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164647419.1 | 81.21 | 0.00 | 0.00 |
April | 0.746747E+10 | -0.730860E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -158876340.3 | 81.21 | 0.00 | 0.00 |
May | 0.770670E+10 | -0.754280E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -163906296.1 | 81.21 | 0.00 | 0.00 |
June | 0.745896E+10 | -0.730053E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -158429655.3 | 81.21 | 0.00 | 0.00 |
July | 0.771461E+10 | -0.755086E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -163754766.4 | 81.21 | 0.00 | 0.00 |
August | 0.770662E+10 | -0.754281E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -163819213.2 | 81.21 | 0.00 | 0.00 |
September | 0.746858E+10 | -0.730994E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -158641711.8 | 81.21 | 0.00 | 0.00 |
October | 0.770574E+10 | -0.754144E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164304341.2 | 81.21 | 0.00 | 0.00 |
November | 0.745192E+10 | -0.729244E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -159475520.3 | 81.21 | 0.00 | 0.00 |
December | 0.771604E+10 | -0.755085E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -165192497.5 | 81.21 | 0.00 | 0.00 |
Annual Sum or Average | 0.907755E+11 | -0.888405E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.193504E+10 | 81.21 | 0.00 | 0.00 |
Minimum of Months | 0.696485E+10 | -0.755086E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -165192497.5 | 81.21 | 0.00 | 0.00 |
Maximum of Months | 0.771604E+10 | -0.681596E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -148888144.3 | 81.21 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH LAUNDRY G WATER HEATER
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.113706E+12 | -0.111892E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.181371E+10 | 81.26 | 0.00 | 0.00 |
February | 0.102637E+12 | -0.100997E+12 | 0.00 | 0.00 | 672.00 | 0.00 | -0.164004E+10 | 81.26 | 0.00 | 0.00 |
March | 0.110924E+12 | -0.109106E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.181791E+10 | 81.26 | 0.00 | 0.00 |
April | 0.102723E+12 | -0.100964E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.175950E+10 | 81.26 | 0.00 | 0.00 |
May | 0.100614E+12 | -0.987969E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.181743E+10 | 81.25 | 0.00 | 0.00 |
June | 0.927220E+11 | -0.909636E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.175846E+10 | 81.25 | 0.00 | 0.00 |
July | 0.930444E+11 | -0.912300E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.181443E+10 | 81.25 | 0.00 | 0.00 |
August | 0.930633E+11 | -0.912531E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.181017E+10 | 81.25 | 0.00 | 0.00 |
September | 0.927696E+11 | -0.910241E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.174545E+10 | 81.24 | 0.00 | 0.00 |
October | 0.100683E+12 | -0.988820E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.180148E+10 | 81.25 | 0.00 | 0.00 |
November | 0.102789E+12 | -0.101046E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.174354E+10 | 81.25 | 0.00 | 0.00 |
December | 0.110975E+12 | -0.109168E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.180773E+10 | 81.25 | 0.00 | 0.00 |
Annual Sum or Average | 0.121665E+13 | -0.119532E+13 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.213299E+11 | 81.25 | 0.00 | 0.00 |
Minimum of Months | 0.927220E+11 | -0.111892E+12 | 0.00 | 0.00 | 672.00 | 0.00 | -0.181791E+10 | 81.24 | 0.00 | 0.00 |
Maximum of Months | 0.113706E+12 | -0.909636E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.164004E+10 | 81.26 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.656074E+11 | -0.640241E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.158332E+10 | 58.98 | 0.00 | 0.00 |
February | 0.592152E+11 | -0.577825E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.143270E+10 | 58.98 | 0.00 | 0.00 |
March | 0.632684E+11 | -0.616793E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.158914E+10 | 58.98 | 0.00 | 0.00 |
April | 0.572105E+11 | -0.556723E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.153823E+10 | 58.98 | 0.00 | 0.00 |
May | 0.543520E+11 | -0.527631E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.158882E+10 | 58.98 | 0.00 | 0.00 |
June | 0.486047E+11 | -0.470677E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.153708E+10 | 58.98 | 0.00 | 0.00 |
July | 0.477891E+11 | -0.462044E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.158462E+10 | 58.98 | 0.00 | 0.00 |
August | 0.478502E+11 | -0.462716E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.157859E+10 | 58.98 | 0.00 | 0.00 |
September | 0.486177E+11 | -0.470985E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.151922E+10 | 58.98 | 0.00 | 0.00 |
October | 0.543729E+11 | -0.528062E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.156663E+10 | 58.98 | 0.00 | 0.00 |
November | 0.572361E+11 | -0.557199E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.151623E+10 | 58.98 | 0.00 | 0.00 |
December | 0.632484E+11 | -0.616730E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.157535E+10 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.667373E+12 | -0.648763E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.186099E+11 | 58.98 | 0.00 | 0.00 |
Minimum of Months | 0.477891E+11 | -0.640241E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.158914E+10 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.656074E+11 | -0.462044E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.143270E+10 | 58.98 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 276.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 268.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 351.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 373.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 408.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 398.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 400.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 377.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 365.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 318.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 295.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 289.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4125.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 268.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 408.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.390826E+09 | 39201.22 | 27-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.492491E+09 | 47495.08 | 03-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 72578409.28 | 17221.48 | 10-MAR-08:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 1609.64 | 2.68 | 13-SEP-18:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 17083817.29 | 14287.08 | 06-OCT-07:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 8994225.67 | 16126.68 | 30-NOV-19:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.831826E+09 | 39686.52 | 27-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.181380E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.831826E+09 | 47495.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BASEMENT VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.471418E+10 | 8490.97 | 02-JAN-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.105238E+11 | 8753.52 | 20-FEB-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.163009E+11 | 8761.88 | 19-MAR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.156756E+11 | 8867.44 | 30-APR-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.149304E+11 | 8888.95 | 21-MAY-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.132534E+11 | 8925.38 | 17-JUN-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.748279E+10 | 8930.98 | 02-JUL-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.323694E+10 | 8894.53 | 07-AUG-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.411664E+09 | 6877.51 | 01-SEP-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 60947743.65 | 4535.33 | 05-OCT-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 10684294.40 | 2344.55 | 06-NOV-11:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.718548E+09 | 3793.54 | 10-DEC-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.873197E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 10684294.40 | 2344.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.163009E+11 | 8930.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.374278E+10 | 3093.05 | 27-JAN-07:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.305924E+10 | 3114.29 | 03-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.317947E+10 | 2971.02 | 02-MAR-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.204381E+10 | 2335.66 | 12-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.142931E+10 | 1805.00 | 02-MAY-07:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.707313E+09 | 1300.78 | 30-JUN-07:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.712130E+09 | 1385.79 | 19-JUL-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.794169E+09 | 1645.27 | 16-AUG-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.868491E+09 | 1725.14 | 25-SEP-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.166009E+10 | 2052.38 | 25-OCT-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.285093E+10 | 2936.12 | 28-NOV-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.406719E+10 | 3115.02 | 28-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.251149E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.707313E+09 | 1300.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.406719E+10 | 3115.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_2_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.152282E+10 | 1271.69 | 17-JAN-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.123018E+10 | 1256.21 | 16-FEB-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.119413E+10 | 1322.08 | 29-MAR-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.752235E+09 | 1299.82 | 11-APR-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.541585E+09 | 1135.37 | 02-MAY-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.375947E+09 | 1034.84 | 30-JUN-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.395558E+09 | 1100.00 | 05-JUL-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.411374E+09 | 1106.49 | 17-AUG-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.394780E+09 | 1081.06 | 05-SEP-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.667922E+09 | 1115.74 | 24-OCT-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.112662E+10 | 1279.64 | 27-NOV-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.164589E+10 | 1301.35 | 26-DEC-11:33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.102590E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.375947E+09 | 1034.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.164589E+10 | 1322.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: MECH_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.345891E+10 | 2039.28 | 28-JAN-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.282485E+10 | 2016.69 | 03-FEB-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.270890E+10 | 1961.27 | 02-MAR-04:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.163730E+10 | 1672.34 | 11-APR-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.912333E+09 | 1364.86 | 02-MAY-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.353874E+09 | 1103.31 | 29-JUN-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.383047E+09 | 1040.13 | 21-JUL-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.581378E+09 | 1230.50 | 17-AUG-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.915684E+09 | 1353.98 | 25-SEP-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.171558E+10 | 1524.66 | 25-OCT-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.277467E+10 | 1911.15 | 28-NOV-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.366910E+10 | 2068.88 | 27-DEC-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.219356E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.353874E+09 | 1040.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.366910E+10 | 2068.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: STORAGE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.218804E+10 | 1163.14 | 28-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.179734E+10 | 1147.35 | 03-FEB-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.174891E+10 | 1122.39 | 02-MAR-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.107961E+10 | 961.75 | 11-APR-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.611136E+09 | 773.22 | 02-MAY-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.225693E+09 | 612.53 | 29-JUN-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.243463E+09 | 554.70 | 05-JUL-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.380792E+09 | 669.04 | 17-AUG-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.611577E+09 | 735.48 | 25-SEP-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.113004E+10 | 845.83 | 25-OCT-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.177980E+10 | 1082.45 | 28-NOV-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.231278E+10 | 1163.49 | 28-DEC-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.141092E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.225693E+09 | 554.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.231278E+10 | 1163.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LAUNDRY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.136023E+11 | 12629.16 | 28-JAN-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.119713E+11 | 12438.01 | 02-FEB-04:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130385E+11 | 12437.87 | 02-MAR-04:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.123451E+11 | 13363.58 | 29-APR-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.128487E+11 | 13418.48 | 30-MAY-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.129311E+11 | 13484.27 | 17-JUN-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.133956E+11 | 13484.49 | 03-JUL-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.133067E+11 | 13451.60 | 04-AUG-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.128412E+11 | 13412.23 | 02-SEP-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.129473E+11 | 13370.96 | 05-OCT-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.126406E+11 | 12535.86 | 28-NOV-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.137511E+11 | 12816.47 | 04-DEC-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.155620E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.119713E+11 | 12437.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.137511E+11 | 13484.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAFE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.541119E+10 | 7890.41 | 17-JAN-10:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.417828E+10 | 7887.99 | 03-FEB-07:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.450203E+10 | 7430.58 | 24-MAR-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.294557E+10 | 6427.71 | 11-APR-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.247607E+10 | 5846.65 | 03-MAY-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.165531E+10 | 5584.86 | 29-JUN-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.159408E+10 | 5810.27 | 19-JUL-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.144487E+10 | 6529.62 | 16-AUG-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.951414E+09 | 4352.25 | 25-SEP-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.188446E+10 | 6621.13 | 13-OCT-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.365369E+10 | 8233.99 | 27-NOV-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.610264E+10 | 8576.67 | 27-DEC-07:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.367996E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.951414E+09 | 4352.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.610264E+10 | 8576.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LOBBY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.154165E+11 | 21698.37 | 17-JAN-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121979E+11 | 20710.07 | 13-FEB-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130102E+11 | 20974.05 | 24-MAR-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.924512E+10 | 21066.66 | 11-APR-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.790243E+10 | 19373.22 | 02-MAY-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.595254E+10 | 18603.69 | 30-JUN-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.596978E+10 | 18579.10 | 05-JUL-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.576620E+10 | 17854.83 | 16-AUG-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.455636E+10 | 16846.41 | 05-SEP-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.619831E+10 | 18861.53 | 16-OCT-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.104497E+11 | 22499.17 | 27-NOV-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168490E+11 | 22683.39 | 26-DEC-11:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.113514E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.455636E+10 | 16846.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.168490E+11 | 22683.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.100449E+11 | 8599.62 | 27-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.701599E+10 | 8543.01 | 02-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.590443E+10 | 8124.41 | 02-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.138405E+10 | 5680.82 | 11-APR-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.127262E+09 | 3325.13 | 02-MAY-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 13200557.49 | 2303.38 | 17-AUG-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.110075E+10 | 5280.23 | 14-OCT-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.578413E+10 | 8407.62 | 27-NOV-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.113130E+11 | 9528.78 | 27-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.426878E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.113130E+11 | 9528.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.104812E+11 | 7234.58 | 27-JAN-07:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.824485E+10 | 7333.68 | 03-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.786649E+10 | 6971.84 | 02-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.396083E+10 | 5286.33 | 12-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.174029E+10 | 3634.88 | 02-MAY-07:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.234675E+09 | 1742.81 | 30-JUN-07:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.202830E+09 | 1897.24 | 19-JUL-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.582786E+09 | 2902.00 | 16-AUG-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.137866E+10 | 3850.28 | 25-SEP-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.407826E+10 | 4686.32 | 25-OCT-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.798337E+10 | 6461.23 | 28-NOV-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.114479E+11 | 7335.57 | 28-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.582022E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.202830E+09 | 1742.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.114479E+11 | 7335.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BANQUET_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.423580E+10 | 7796.21 | 27-JAN-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.305171E+10 | 7544.31 | 03-FEB-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.263965E+10 | 7709.60 | 29-MAR-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115275E+10 | 7201.09 | 11-APR-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.586579E+09 | 6242.49 | 02-MAY-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.260948E+09 | 4892.28 | 26-JUN-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.276881E+09 | 4901.05 | 24-JUL-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.441987E+09 | 5438.90 | 22-AUG-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.678210E+09 | 6265.51 | 25-SEP-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.152350E+10 | 6799.41 | 25-OCT-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.311306E+10 | 7286.58 | 17-NOV-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.465287E+10 | 7673.84 | 07-DEC-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.226139E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.260948E+09 | 4892.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.465287E+10 | 7796.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: DINING_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.361455E+10 | 7440.27 | 30-JAN-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.249665E+10 | 7189.49 | 03-FEB-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.204837E+10 | 7253.69 | 29-MAR-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.741507E+09 | 6793.28 | 11-APR-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.331959E+09 | 5703.49 | 02-MAY-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.144866E+09 | 4542.08 | 30-JUN-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.155180E+09 | 4554.23 | 24-JUL-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.252626E+09 | 4924.17 | 22-AUG-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.414266E+09 | 5858.41 | 25-SEP-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.106925E+10 | 6459.20 | 25-OCT-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.254328E+10 | 7007.09 | 17-NOV-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.400872E+10 | 7329.60 | 07-DEC-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.178212E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.144866E+09 | 4542.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.400872E+10 | 7440.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: KITCHEN_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.216207E+10 | 5775.16 | 28-JAN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.176562E+10 | 5841.47 | 03-FEB-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.166254E+10 | 5907.01 | 02-MAR-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.956283E+09 | 4424.71 | 11-APR-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.576081E+09 | 3319.17 | 02-MAY-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.246315E+09 | 2228.39 | 29-JUN-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.231411E+09 | 2228.40 | 05-JUL-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.313589E+09 | 2796.20 | 17-AUG-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.516262E+09 | 3419.34 | 25-SEP-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.101477E+10 | 4166.47 | 25-OCT-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.179501E+10 | 5775.52 | 28-NOV-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.235702E+10 | 6035.96 | 27-DEC-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.135970E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.231411E+09 | 2228.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.235702E+10 | 6035.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: FLR_3_DOAS HEATING COIL
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.273843E+11 | 15911.02 | 27-JAN-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.190765E+11 | 16182.58 | 03-FEB-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.159141E+11 | 15798.57 | 02-MAR-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.437768E+10 | 14148.07 | 12-APR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.346645E+09 | 11023.85 | 02-MAY-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 38046.70 | 0.50 | 13-JUN-10:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 11380.94 | 0.51 | 12-JUL-04:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 25201.66 | 0.51 | 20-AUG-19:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.490805E+09 | 12984.10 | 30-SEP-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.380166E+10 | 13361.51 | 11-OCT-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.185253E+11 | 15049.80 | 28-NOV-01:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.290885E+11 | 15913.62 | 27-DEC-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.119006E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 11380.94 | 0.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.290885E+11 | 16182.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.183203E+10 | 6409.43 | 27-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.123680E+10 | 6389.56 | 02-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.758726E+09 | 6409.67 | 02-MAR-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.103129E+09 | 6214.73 | 11-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5036699.98 | 3326.09 | 10-MAY-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 2907576.20 | 1946.66 | 25-JUN-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 3785026.63 | 2497.61 | 18-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 4419717.58 | 2567.67 | 12-AUG-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 4083784.92 | 2594.20 | 27-SEP-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 36106183.83 | 3537.95 | 30-OCT-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.980392E+09 | 6410.53 | 27-NOV-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.245764E+10 | 6411.18 | 28-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.742506E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 2907576.20 | 1946.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.245764E+10 | 6411.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.274974E+10 | 6396.11 | 26-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.182309E+10 | 6396.48 | 09-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.104340E+10 | 6396.41 | 01-MAR-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.128993E+09 | 6219.41 | 11-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5012107.92 | 3130.48 | 08-MAY-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 2696169.75 | 1833.26 | 23-JUN-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 3579497.58 | 2600.56 | 21-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 4876744.91 | 2688.88 | 23-AUG-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 5472231.14 | 3361.62 | 11-SEP-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 78523069.87 | 4198.04 | 25-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.148247E+10 | 6397.78 | 28-NOV-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.358153E+10 | 6398.18 | 05-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.109094E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 2696169.75 | 1833.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.358153E+10 | 6398.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.113784E+09 | 10141.45 | 27-DEC-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.113784E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.113784E+09 | 10141.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.681306E+10 | 36847.95 | 27-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.463926E+10 | 36621.25 | 02-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.193555E+10 | 36487.98 | 02-MAR-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.143712E+09 | 34831.61 | 11-APR-15:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 35197189.76 | 31073.08 | 23-MAY-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16461998.84 | 26152.06 | 23-JUN-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 12937310.18 | 25754.65 | 05-JUL-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 25980006.53 | 32128.64 | 24-AUG-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 44411384.69 | 30917.69 | 21-SEP-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.107190E+09 | 28234.88 | 24-OCT-15:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.300322E+10 | 36251.64 | 27-NOV-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.110873E+11 | 37147.39 | 26-DEC-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.278643E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 12937310.18 | 25754.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.110873E+11 | 37147.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.190443E+10 | 6188.60 | 15-JAN-16:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.116794E+10 | 6073.13 | 27-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.762834E+09 | 6177.00 | 02-MAR-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 98787588.36 | 2830.91 | 20-APR-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2389726.19 | 2372.37 | 23-MAY-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 353328.58 | 1521.37 | 22-JUN-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 479573.89 | 2471.48 | 07-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1664357.02 | 2431.76 | 24-AUG-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 1468500.56 | 2163.43 | 22-SEP-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 63351801.66 | 3454.34 | 15-OCT-18:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.104653E+10 | 6224.09 | 27-NOV-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.248189E+10 | 6228.32 | 26-DEC-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.753213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 353328.58 | 1521.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.248189E+10 | 6228.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.282500E+10 | 6209.65 | 26-JAN-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.168251E+10 | 6153.86 | 01-FEB-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.101237E+10 | 6206.36 | 02-MAR-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.124237E+09 | 3839.98 | 11-APR-15:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3111393.01 | 2435.20 | 23-MAY-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 330030.06 | 1534.24 | 22-JUN-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 489985.29 | 2499.42 | 07-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1877198.88 | 2675.02 | 17-AUG-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 4415368.15 | 2457.17 | 22-SEP-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.129076E+09 | 3554.57 | 31-OCT-18:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.153638E+10 | 6213.27 | 27-NOV-19:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.356594E+10 | 6213.59 | 03-DEC-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.108857E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 330030.06 | 1534.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.356594E+10 | 6213.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.722460E+09 | 1944.64 | 15-JAN-16:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.491164E+09 | 1943.07 | 09-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.316681E+09 | 1943.13 | 01-MAR-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 49305713.66 | 1905.38 | 11-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2179858.55 | 791.88 | 10-MAY-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 406689.73 | 370.60 | 25-JUN-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 593231.16 | 619.73 | 21-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 873012.70 | 643.99 | 30-AUG-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 1703395.15 | 708.01 | 26-SEP-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 25705464.46 | 949.97 | 28-OCT-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.397406E+09 | 1943.50 | 28-NOV-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.939057E+09 | 1943.78 | 03-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.294754E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 406689.73 | 370.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.939057E+09 | 1944.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.102940E+10 | 1940.52 | 15-JAN-16:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.684877E+09 | 1939.36 | 17-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.410280E+09 | 1939.10 | 01-MAR-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 59403912.41 | 1906.43 | 11-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2239393.97 | 803.40 | 10-MAY-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 340077.35 | 416.28 | 30-JUN-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 545722.22 | 653.23 | 21-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 956577.61 | 764.48 | 30-AUG-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2852158.21 | 781.41 | 12-SEP-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 48114159.32 | 1871.63 | 25-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.578366E+09 | 1939.74 | 30-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.130236E+10 | 1939.69 | 14-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.411973E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 340077.35 | 416.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.130236E+10 | 1940.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.154729E+10 | 9104.82 | 15-JAN-16:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.107487E+10 | 8754.12 | 02-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.783393E+09 | 9158.67 | 02-MAR-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.135345E+09 | 6619.06 | 11-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 10216121.59 | 4314.50 | 19-MAY-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6373056.73 | 4023.64 | 27-JUN-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6656137.65 | 4294.53 | 07-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6921374.13 | 3976.89 | 02-AUG-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 5543709.83 | 3804.68 | 13-SEP-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 21320459.34 | 3790.55 | 15-OCT-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.886317E+09 | 9142.63 | 27-NOV-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.220624E+10 | 9244.17 | 26-DEC-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.669049E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 5543709.83 | 3790.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.220624E+10 | 9244.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.201108E+11 | 0.201108E+11 | 192380.40 | 03-JAN-17:00 | 192380.40 | 0.00 |
February | 0.00 | 0.00 | 0.759769E+11 | 0.759769E+11 | 233415.98 | 20-FEB-11:50 | 233415.98 | 0.00 |
March | 0.00 | 0.00 | 0.145448E+12 | 0.145448E+12 | 260781.39 | 14-MAR-17:13 | 260781.39 | 0.00 |
April | 0.00 | 0.00 | 0.382942E+12 | 0.382942E+12 | 333076.85 | 19-APR-18:10 | 333076.85 | 0.09 |
May | 0.00 | 0.00 | 0.597793E+12 | 0.591323E+12 | 410770.20 | 28-MAY-10:35 | 314247.27 | 0.28 |
June | 0.00 | 0.00 | 0.736192E+12 | 0.720033E+12 | 450614.15 | 19-JUN-18:10 | 294508.50 | 0.57 |
July | 0.00 | 0.00 | 0.981701E+12 | 0.745816E+12 | 677044.84 | 21-JUL-06:30 | 218290.62 | 0.99 |
August | 0.00 | 0.00 | 0.808393E+12 | 0.700978E+12 | 593511.92 | 01-AUG-21:00 | 250046.73 | 0.94 |
September | 0.00 | 0.00 | 0.694503E+12 | 0.565639E+12 | 536772.07 | 22-SEP-02:00 | 191855.83 | 0.81 |
October | 0.00 | 0.00 | 0.364337E+12 | 0.340216E+12 | 466255.17 | 03-OCT-20:30 | 245848.47 | 0.48 |
November | 0.00 | 0.00 | 0.944464E+11 | 0.944464E+11 | 247738.69 | 03-NOV-16:00 | 247738.69 | 0.04 |
December | 0.00 | 0.00 | 0.146740E+11 | 0.146740E+11 | 127386.92 | 10-DEC-15:00 | 127386.92 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.491652E+13 | 0.439760E+13 | 0.35 | |||
Minimum of Months | 0.00 | 0.00 | 0.146740E+11 | 0.146740E+11 | 127386.92 | 127386.92 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.981701E+12 | 0.745816E+12 | 677044.84 | 333076.85 | 0.99 |
Report: CoilReportMonthly
For: FLR_3_DOAS COOLING COIL
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.122869E+10 | 0.122869E+10 | 18651.05 | 03-JAN-15:00 | 18651.05 | 0.00 |
February | 0.00 | 0.00 | 0.621055E+10 | 0.621055E+10 | 24890.15 | 20-FEB-15:00 | 24890.15 | 0.00 |
March | 0.00 | 0.00 | 0.124469E+11 | 0.124469E+11 | 28566.40 | 21-MAR-16:00 | 28566.40 | 0.00 |
April | 0.00 | 0.00 | 0.399969E+11 | 0.399969E+11 | 44409.17 | 21-APR-15:00 | 44409.17 | 0.08 |
May | 0.00 | 0.00 | 0.693058E+11 | 0.674714E+11 | 50585.42 | 19-MAY-14:00 | 50585.42 | 0.26 |
June | 0.00 | 0.00 | 0.932452E+11 | 0.894911E+11 | 58655.85 | 02-JUN-17:00 | 58655.85 | 0.50 |
July | 0.00 | 0.00 | 0.127410E+12 | 0.896819E+11 | 65741.82 | 20-JUL-16:00 | 26241.67 | 0.98 |
August | 0.00 | 0.00 | 0.102279E+12 | 0.830713E+11 | 58860.95 | 02-AUG-12:00 | 38266.78 | 0.88 |
September | 0.00 | 0.00 | 0.814589E+11 | 0.629435E+11 | 55192.93 | 14-SEP-10:00 | 26667.06 | 0.78 |
October | 0.00 | 0.00 | 0.377637E+11 | 0.336702E+11 | 52564.31 | 03-OCT-14:00 | 44755.97 | 0.42 |
November | 0.00 | 0.00 | 0.755815E+10 | 0.755815E+10 | 26388.16 | 03-NOV-16:00 | 26388.16 | 0.02 |
December | 0.00 | 0.00 | 0.724489E+09 | 0.724489E+09 | 11238.20 | 10-DEC-15:00 | 11238.20 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.579628E+12 | 0.494495E+12 | 0.33 | |||
Minimum of Months | 0.00 | 0.00 | 0.724489E+09 | 0.724489E+09 | 11238.20 | 11238.20 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.127410E+12 | 0.896819E+11 | 65741.82 | 58655.85 | 0.98 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.722115E+09 | 0.720641E+09 | 18116.34 | 01-JAN-16:02 | 18116.34 | 0.00 |
February | 0.00 | 0.00 | 0.120688E+10 | 0.120552E+10 | 18089.20 | 18-FEB-16:01 | 18089.20 | 0.00 |
March | 0.00 | 0.00 | 0.226720E+10 | 0.225421E+10 | 18096.24 | 12-MAR-15:01 | 18096.24 | 0.01 |
April | 0.00 | 0.00 | 0.546037E+10 | 0.512260E+10 | 18122.49 | 17-APR-18:01 | 18122.49 | 0.12 |
May | 0.00 | 0.00 | 0.876234E+10 | 0.753288E+10 | 18730.83 | 28-MAY-08:61 | 15791.43 | 0.32 |
June | 0.00 | 0.00 | 0.115697E+11 | 0.920445E+10 | 18607.62 | 28-JUN-08:62 | 14858.64 | 0.59 |
July | 0.00 | 0.00 | 0.127687E+11 | 0.777143E+10 | 21980.88 | 19-JUL-08:62 | 13086.78 | 0.95 |
August | 0.00 | 0.00 | 0.113529E+11 | 0.718810E+10 | 20204.96 | 02-AUG-08:61 | 15063.62 | 0.91 |
September | 0.00 | 0.00 | 0.100953E+11 | 0.634610E+10 | 20228.89 | 09-SEP-08:61 | 15043.87 | 0.86 |
October | 0.00 | 0.00 | 0.608411E+10 | 0.415205E+10 | 19090.18 | 04-OCT-08:62 | 14556.48 | 0.56 |
November | 0.00 | 0.00 | 0.206946E+10 | 0.188067E+10 | 18123.27 | 04-NOV-15:01 | 18123.27 | 0.08 |
December | 0.00 | 0.00 | 0.415065E+09 | 0.415065E+09 | 18086.00 | 07-DEC-16:01 | 18086.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.727741E+11 | 0.537937E+11 | 0.37 | |||
Minimum of Months | 0.00 | 0.00 | 0.415065E+09 | 0.415065E+09 | 18086.00 | 13086.78 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.127687E+11 | 0.920445E+10 | 21980.88 | 18123.27 | 0.95 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.127140E+09 | 0.126798E+09 | 17677.89 | 12-JAN-16:01 | 17677.89 | 0.00 |
February | 0.00 | 0.00 | 0.423650E+09 | 0.422969E+09 | 17958.79 | 18-FEB-16:01 | 17958.79 | 0.00 |
March | 0.00 | 0.00 | 0.136437E+10 | 0.135368E+10 | 17961.97 | 12-MAR-15:01 | 17961.97 | 0.01 |
April | 0.00 | 0.00 | 0.466002E+10 | 0.436151E+10 | 17992.74 | 17-APR-18:01 | 17992.74 | 0.12 |
May | 0.00 | 0.00 | 0.854167E+10 | 0.733311E+10 | 18575.57 | 28-MAY-08:61 | 15765.81 | 0.32 |
June | 0.00 | 0.00 | 0.116408E+11 | 0.929468E+10 | 18500.58 | 28-JUN-08:62 | 14940.58 | 0.59 |
July | 0.00 | 0.00 | 0.127116E+11 | 0.776970E+10 | 21770.64 | 19-JUL-08:62 | 13007.86 | 0.95 |
August | 0.00 | 0.00 | 0.107086E+11 | 0.667650E+10 | 20137.60 | 02-AUG-08:61 | 14912.58 | 0.90 |
September | 0.00 | 0.00 | 0.847497E+10 | 0.499668E+10 | 20082.86 | 23-SEP-18:01 | 14542.33 | 0.83 |
October | 0.00 | 0.00 | 0.406830E+10 | 0.259372E+10 | 18881.85 | 04-OCT-08:62 | 14216.10 | 0.48 |
November | 0.00 | 0.00 | 0.656897E+09 | 0.558419E+09 | 17991.11 | 09-NOV-16:01 | 17991.11 | 0.05 |
December | 0.00 | 0.00 | 49598812.63 | 49598812.63 | 17361.38 | 16-DEC-16:02 | 17361.38 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.634276E+11 | 0.455374E+11 | 0.36 | |||
Minimum of Months | 0.00 | 0.00 | 49598812.63 | 49598812.63 | 17361.38 | 13007.86 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.127116E+11 | 0.929468E+10 | 21770.64 | 17992.74 | 0.95 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.187338E+11 | 0.187338E+11 | 42039.10 | 12-JAN-14:30 | 42039.10 | 0.00 |
February | 0.00 | 0.00 | 0.186891E+11 | 0.186666E+11 | 40287.64 | 07-FEB-13:40 | 40287.64 | 0.00 |
March | 0.00 | 0.00 | 0.178191E+11 | 0.176597E+11 | 32128.75 | 16-MAR-13:30 | 32128.75 | 0.01 |
April | 0.00 | 0.00 | 0.286378E+11 | 0.275079E+11 | 31143.23 | 03-APR-14:00 | 31143.23 | 0.07 |
May | 0.00 | 0.00 | 0.372407E+11 | 0.314968E+11 | 32772.64 | 19-MAY-20:20 | 32772.64 | 0.25 |
June | 0.00 | 0.00 | 0.490596E+11 | 0.377855E+11 | 37380.51 | 17-JUN-18:25 | 37380.51 | 0.50 |
July | 0.00 | 0.00 | 0.582359E+11 | 0.294422E+11 | 40363.45 | 02-JUL-20:40 | 40363.45 | 0.99 |
August | 0.00 | 0.00 | 0.552429E+11 | 0.324876E+11 | 40451.04 | 06-AUG-19:05 | 36600.03 | 0.88 |
September | 0.00 | 0.00 | 0.589986E+11 | 0.396780E+11 | 50495.60 | 19-SEP-13:10 | 39667.71 | 0.78 |
October | 0.00 | 0.00 | 0.499915E+11 | 0.393898E+11 | 54374.54 | 22-OCT-13:40 | 46505.12 | 0.48 |
November | 0.00 | 0.00 | 0.320013E+11 | 0.310643E+11 | 48108.55 | 09-NOV-13:50 | 48108.55 | 0.06 |
December | 0.00 | 0.00 | 0.142146E+11 | 0.142146E+11 | 38082.67 | 16-DEC-13:40 | 38082.67 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.438865E+12 | 0.338127E+12 | 0.34 | |||
Minimum of Months | 0.00 | 0.00 | 0.142146E+11 | 0.142146E+11 | 31143.23 | 31143.23 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.589986E+11 | 0.396780E+11 | 54374.54 | 48108.55 | 0.99 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.500924E+10 | 0.470017E+10 | 109209.76 | 13-JAN-19:02 | 109209.76 | 0.02 |
February | 0.00 | 0.00 | 0.952481E+10 | 0.888985E+10 | 112954.08 | 20-FEB-09:01 | 112954.08 | 0.05 |
March | 0.00 | 0.00 | 0.182443E+11 | 0.178289E+11 | 115105.18 | 15-MAR-18:01 | 115105.18 | 0.02 |
April | 0.00 | 0.00 | 0.405932E+11 | 0.383877E+11 | 120021.63 | 28-APR-18:01 | 120021.63 | 0.10 |
May | 0.00 | 0.00 | 0.650000E+11 | 0.570325E+11 | 120151.00 | 28-MAY-08:61 | 107700.72 | 0.27 |
June | 0.00 | 0.00 | 0.833085E+11 | 0.686231E+11 | 120394.27 | 28-JUN-08:62 | 99367.24 | 0.53 |
July | 0.00 | 0.00 | 0.951723E+11 | 0.627338E+11 | 144018.26 | 19-JUL-08:62 | 87423.24 | 0.88 |
August | 0.00 | 0.00 | 0.805664E+11 | 0.533239E+11 | 130555.13 | 02-AUG-08:61 | 100805.18 | 0.80 |
September | 0.00 | 0.00 | 0.635069E+11 | 0.400279E+11 | 134191.44 | 23-SEP-18:01 | 93536.45 | 0.69 |
October | 0.00 | 0.00 | 0.408900E+11 | 0.266324E+11 | 122745.68 | 04-OCT-08:62 | 97013.02 | 0.49 |
November | 0.00 | 0.00 | 0.116994E+11 | 0.996162E+10 | 113548.45 | 11-NOV-09:01 | 113548.45 | 0.10 |
December | 0.00 | 0.00 | 0.336045E+10 | 0.336045E+10 | 111643.78 | 09-DEC-09:01 | 111643.78 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.516875E+12 | 0.391502E+12 | 0.33 | |||
Minimum of Months | 0.00 | 0.00 | 0.336045E+10 | 0.336045E+10 | 109209.76 | 87423.24 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.951723E+11 | 0.686231E+11 | 144018.26 | 120021.63 | 0.88 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.609955E+09 | 0.606864E+09 | 15862.15 | 12-JAN-16:01 | 15862.15 | 0.00 |
February | 0.00 | 0.00 | 0.132023E+10 | 0.131359E+10 | 15875.09 | 08-FEB-09:01 | 15875.09 | 0.00 |
March | 0.00 | 0.00 | 0.226342E+10 | 0.225232E+10 | 15859.33 | 07-MAR-09:01 | 15859.33 | 0.01 |
April | 0.00 | 0.00 | 0.567944E+10 | 0.532430E+10 | 15874.38 | 28-APR-18:01 | 15874.38 | 0.13 |
May | 0.00 | 0.00 | 0.888487E+10 | 0.763547E+10 | 15875.28 | 31-MAY-15:02 | 15875.28 | 0.33 |
June | 0.00 | 0.00 | 0.118750E+11 | 0.952314E+10 | 16515.28 | 28-JUN-08:62 | 13847.20 | 0.62 |
July | 0.00 | 0.00 | 0.130746E+11 | 0.807924E+10 | 19223.52 | 19-JUL-08:62 | 11380.51 | 0.97 |
August | 0.00 | 0.00 | 0.115969E+11 | 0.739006E+10 | 17340.53 | 18-AUG-08:62 | 13382.53 | 0.94 |
September | 0.00 | 0.00 | 0.101459E+11 | 0.640534E+10 | 17531.86 | 23-SEP-18:01 | 13278.85 | 0.89 |
October | 0.00 | 0.00 | 0.564508E+10 | 0.389281E+10 | 17124.40 | 09-OCT-08:62 | 12718.95 | 0.55 |
November | 0.00 | 0.00 | 0.190716E+10 | 0.176934E+10 | 15873.57 | 09-NOV-16:01 | 15873.57 | 0.07 |
December | 0.00 | 0.00 | 0.436861E+09 | 0.436861E+09 | 15857.54 | 09-DEC-09:01 | 15857.54 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.734393E+11 | 0.546294E+11 | 0.38 | |||
Minimum of Months | 0.00 | 0.00 | 0.436861E+09 | 0.436861E+09 | 15857.54 | 11380.51 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.130746E+11 | 0.952314E+10 | 19223.52 | 15875.28 | 0.97 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 59193127.27 | 58573583.11 | 10552.22 | 31-JAN-09:02 | 10552.22 | 0.00 |
February | 0.00 | 0.00 | 0.469791E+09 | 0.464288E+09 | 15725.79 | 19-FEB-09:01 | 15725.79 | 0.00 |
March | 0.00 | 0.00 | 0.130087E+10 | 0.129413E+10 | 15730.28 | 07-MAR-09:01 | 15730.28 | 0.01 |
April | 0.00 | 0.00 | 0.483194E+10 | 0.450165E+10 | 15745.13 | 28-APR-18:01 | 15745.13 | 0.12 |
May | 0.00 | 0.00 | 0.864751E+10 | 0.741971E+10 | 15746.09 | 31-MAY-15:02 | 15746.09 | 0.34 |
June | 0.00 | 0.00 | 0.119435E+11 | 0.962191E+10 | 16208.19 | 28-JUN-08:62 | 13827.34 | 0.62 |
July | 0.00 | 0.00 | 0.130094E+11 | 0.805837E+10 | 19021.43 | 19-JUL-08:62 | 11300.26 | 0.98 |
August | 0.00 | 0.00 | 0.109444E+11 | 0.685094E+10 | 17179.76 | 18-AUG-08:62 | 13283.23 | 0.93 |
September | 0.00 | 0.00 | 0.849771E+10 | 0.507713E+10 | 17570.65 | 23-SEP-18:01 | 12809.35 | 0.87 |
October | 0.00 | 0.00 | 0.360323E+10 | 0.231320E+10 | 16961.32 | 09-OCT-08:62 | 12250.01 | 0.47 |
November | 0.00 | 0.00 | 0.585874E+09 | 0.514753E+09 | 15738.93 | 11-NOV-09:01 | 15738.93 | 0.04 |
December | 0.00 | 0.00 | 42956447.95 | 42956447.95 | 14941.11 | 09-DEC-09:01 | 14941.11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.639364E+11 | 0.462176E+11 | 0.37 | |||
Minimum of Months | 0.00 | 0.00 | 42956447.95 | 42956447.95 | 10552.22 | 10552.22 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.130094E+11 | 0.962191E+10 | 19021.43 | 15746.09 | 0.98 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.154784E+09 | 0.154121E+09 | 4910.70 | 01-JAN-16:02 | 4910.70 | 0.00 |
February | 0.00 | 0.00 | 0.294475E+09 | 0.294142E+09 | 4903.32 | 18-FEB-16:01 | 4903.32 | 0.00 |
March | 0.00 | 0.00 | 0.588547E+09 | 0.585991E+09 | 4905.26 | 12-MAR-15:01 | 4905.26 | 0.01 |
April | 0.00 | 0.00 | 0.155247E+10 | 0.146061E+10 | 4912.21 | 17-APR-18:01 | 4912.21 | 0.12 |
May | 0.00 | 0.00 | 0.252069E+10 | 0.218838E+10 | 5153.34 | 28-MAY-08:61 | 4252.16 | 0.32 |
June | 0.00 | 0.00 | 0.336670E+10 | 0.271700E+10 | 5157.48 | 28-JUN-08:62 | 3976.40 | 0.60 |
July | 0.00 | 0.00 | 0.371169E+10 | 0.236371E+10 | 6142.55 | 19-JUL-08:62 | 3436.52 | 0.96 |
August | 0.00 | 0.00 | 0.328258E+10 | 0.215465E+10 | 5554.53 | 02-AUG-08:61 | 4039.46 | 0.92 |
September | 0.00 | 0.00 | 0.285224E+10 | 0.186364E+10 | 5617.95 | 09-SEP-08:61 | 4001.36 | 0.86 |
October | 0.00 | 0.00 | 0.165147E+10 | 0.115670E+10 | 5258.38 | 04-OCT-08:62 | 3869.90 | 0.53 |
November | 0.00 | 0.00 | 0.511879E+09 | 0.466981E+09 | 4912.59 | 04-NOV-15:01 | 4912.59 | 0.07 |
December | 0.00 | 0.00 | 84102887.94 | 84102887.94 | 4908.03 | 04-DEC-16:01 | 4908.03 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.205716E+11 | 0.154900E+11 | 0.37 | |||
Minimum of Months | 0.00 | 0.00 | 84102887.94 | 84102887.94 | 4903.32 | 3436.52 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.371169E+10 | 0.271700E+10 | 6142.55 | 4912.59 | 0.96 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 23238703.27 | 23161350.58 | 4823.13 | 12-JAN-16:01 | 4823.13 | 0.00 |
February | 0.00 | 0.00 | 99472589.74 | 99344177.58 | 4862.94 | 18-FEB-16:01 | 4862.94 | 0.00 |
March | 0.00 | 0.00 | 0.348853E+09 | 0.346933E+09 | 4863.71 | 04-MAR-16:01 | 4863.71 | 0.01 |
April | 0.00 | 0.00 | 0.133726E+10 | 0.125408E+10 | 4871.93 | 28-APR-18:01 | 4871.93 | 0.12 |
May | 0.00 | 0.00 | 0.246120E+10 | 0.213130E+10 | 5099.76 | 28-MAY-08:61 | 4231.25 | 0.32 |
June | 0.00 | 0.00 | 0.338670E+10 | 0.274237E+10 | 5131.39 | 28-JUN-08:62 | 3998.39 | 0.60 |
July | 0.00 | 0.00 | 0.369689E+10 | 0.236125E+10 | 6076.02 | 19-JUL-08:62 | 3414.32 | 0.96 |
August | 0.00 | 0.00 | 0.311223E+10 | 0.200664E+10 | 5543.01 | 02-AUG-08:61 | 3987.28 | 0.92 |
September | 0.00 | 0.00 | 0.241963E+10 | 0.148379E+10 | 5544.28 | 09-SEP-08:61 | 3961.24 | 0.84 |
October | 0.00 | 0.00 | 0.111096E+10 | 0.727581E+09 | 4954.38 | 03-OCT-18:01 | 4308.88 | 0.44 |
November | 0.00 | 0.00 | 0.158680E+09 | 0.135959E+09 | 4871.62 | 09-NOV-16:01 | 4871.62 | 0.05 |
December | 0.00 | 0.00 | 8212687.31 | 8212687.31 | 4345.74 | 16-DEC-16:02 | 4345.74 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.181633E+11 | 0.133206E+11 | 0.36 | |||
Minimum of Months | 0.00 | 0.00 | 8212687.31 | 8212687.31 | 4345.74 | 3414.32 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.369689E+10 | 0.274237E+10 | 6076.02 | 4871.93 | 0.96 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.457271E+10 | 0.453936E+10 | 22324.09 | 01-JAN-16:02 | 22324.09 | 0.01 |
February | 0.00 | 0.00 | 0.479250E+10 | 0.476592E+10 | 22304.13 | 14-FEB-16:01 | 22304.13 | 0.02 |
March | 0.00 | 0.00 | 0.498379E+10 | 0.494855E+10 | 22299.62 | 12-MAR-15:01 | 22299.62 | 0.01 |
April | 0.00 | 0.00 | 0.817043E+10 | 0.766155E+10 | 22325.97 | 26-APR-18:01 | 22325.97 | 0.13 |
May | 0.00 | 0.00 | 0.112351E+11 | 0.947273E+10 | 23009.17 | 28-MAY-08:61 | 19625.03 | 0.35 |
June | 0.00 | 0.00 | 0.149190E+11 | 0.116596E+11 | 22861.68 | 28-JUN-08:62 | 17933.58 | 0.62 |
July | 0.00 | 0.00 | 0.174206E+11 | 0.106592E+11 | 27818.64 | 19-JUL-08:62 | 15683.33 | 0.95 |
August | 0.00 | 0.00 | 0.164532E+11 | 0.107000E+11 | 25022.47 | 02-AUG-08:61 | 18548.79 | 0.93 |
September | 0.00 | 0.00 | 0.162297E+11 | 0.110664E+11 | 25483.19 | 23-SEP-18:01 | 18283.10 | 0.87 |
October | 0.00 | 0.00 | 0.126282E+11 | 0.956996E+10 | 23681.13 | 04-OCT-08:62 | 18206.80 | 0.62 |
November | 0.00 | 0.00 | 0.730636E+10 | 0.695177E+10 | 22327.19 | 09-NOV-16:01 | 22327.19 | 0.11 |
December | 0.00 | 0.00 | 0.402041E+10 | 0.401746E+10 | 22311.90 | 04-DEC-16:01 | 22311.90 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.122732E+12 | 0.960124E+11 | 0.39 | |||
Minimum of Months | 0.00 | 0.00 | 0.402041E+10 | 0.401746E+10 | 22299.62 | 15683.33 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.174206E+11 | 0.116596E+11 | 27818.64 | 22327.19 | 0.95 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 47312.08 | 160680.34 | 27-JAN-09:02 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 42108.64 | 155354.24 | 03-FEB-07:10 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 36579.44 | 155356.75 | 02-MAR-09:02 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22622.22 | 91791.34 | 11-APR-08:62 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 16813.78 | 78325.35 | 23-MAY-08:04 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13907.61 | 68798.46 | 23-JUN-08:04 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11502.78 | 69610.16 | 21-JUL-10:35 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 10211.06 | 66339.21 | 18-AUG-10:35 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 9603.50 | 69422.63 | 15-SEP-08:04 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14586.99 | 88051.01 | 13-OCT-08:05 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 32498.72 | 148981.37 | 28-NOV-09:02 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 52039.07 | 156975.75 | 27-DEC-09:02 |
Annual Sum or Average | 0.00 | 25749.05 | ||||
Minimum of Months | 0.00 | 0.00 | 9603.50 | 66339.21 | ||
Maximum of Months | 0.00 | 0.00 | 52039.07 | 160680.34 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 22553.43 | 314961.77 | 03-JAN-16:01 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 53722.21 | 463141.95 | 20-FEB-16:01 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 82660.88 | 481240.13 | 15-MAR-18:01 | 0.00 | 0.00 | 01-MAR-00:03 |
April | 209683.57 | 605429.93 | 19-APR-18:03 | 0.00 | 0.00 | 01-APR-00:10 |
May | 314878.61 | 640072.46 | 21-MAY-18:03 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 406754.43 | 738298.13 | 19-JUN-18:03 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 509212.93 | 943292.64 | 19-JUL-08:62 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 425135.68 | 802634.21 | 02-AUG-18:03 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 378249.18 | 713539.79 | 03-SEP-18:03 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 204755.95 | 698127.49 | 04-OCT-18:03 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 66170.14 | 469389.97 | 09-NOV-16:01 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 17252.46 | 223789.65 | 10-DEC-16:01 | 0.00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 225205.18 | 0.00 | ||||
Minimum of Months | 17252.46 | 223789.65 | 0.00 | 0.00 | ||
Maximum of Months | 509212.93 | 943292.64 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 25474.12 | 51727.49 | 30-JAN-07:50 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 25455.78 | 51721.75 | 01-FEB-07:50 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 24601.52 | 50754.91 | 01-MAR-07:20 |
April | 0.00 | 0.00 | 01-APR-00:10 | 23055.20 | 47839.30 | 03-APR-06:40 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 21280.26 | 44486.96 | 01-MAY-06:20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 19743.58 | 40782.56 | 01-JUN-06:15 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18838.55 | 38099.17 | 03-JUL-06:15 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18863.50 | 38237.61 | 31-AUG-06:40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 19756.74 | 40797.67 | 29-SEP-06:15 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 21296.80 | 44533.53 | 31-OCT-06:50 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 23074.28 | 48075.30 | 30-NOV-08:00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 24599.56 | 50643.54 | 29-DEC-08:00 |
Annual Sum or Average | 0.00 | 22151.34 | ||||
Minimum of Months | 0.00 | 0.00 | 18838.55 | 38099.17 | ||
Maximum of Months | 0.00 | 0.00 | 25474.12 | 51727.49 |
Report: FanReportMonthly
For: FLR_3_DOAS FAN
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.587890E+10 | 1.01 | 2194.93 | 01-JAN-00:05 | 1.01 |
February | 0.530997E+10 | 1.01 | 2194.93 | 01-FEB-00:03 | 1.01 |
March | 0.587890E+10 | 1.01 | 2194.93 | 01-MAR-00:03 | 1.01 |
April | 0.568926E+10 | 1.01 | 2194.93 | 01-APR-00:10 | 1.02 |
May | 0.587890E+10 | 1.01 | 2194.93 | 01-MAY-00:10 | 1.01 |
June | 0.568926E+10 | 1.01 | 2194.93 | 01-JUN-00:10 | 1.01 |
July | 0.587890E+10 | 1.00 | 2194.93 | 01-JUL-00:10 | 1.00 |
August | 0.587890E+10 | 1.00 | 2194.93 | 01-AUG-00:10 | 1.00 |
September | 0.568926E+10 | 1.00 | 2194.93 | 01-SEP-00:10 | 1.00 |
October | 0.587890E+10 | 1.01 | 2194.93 | 01-OCT-00:10 | 1.01 |
November | 0.568926E+10 | 1.01 | 2194.93 | 01-NOV-00:10 | 1.01 |
December | 0.587890E+10 | 1.01 | 2194.93 | 01-DEC-00:03 | 1.01 |
Annual Sum or Average | 0.692193E+11 | 1.01 | |||
Minimum of Months | 0.530997E+10 | 1.00 | 2194.93 | 1.00 | |
Maximum of Months | 0.587890E+10 | 1.01 | 2194.93 | 1.02 |
Report: FanReportMonthly
For: VAV WITH REHEAT FAN
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.150076E+12 | 2.12 | 56081.31 | 01-JAN-11:50 | 2.11 |
February | 0.135562E+12 | 2.12 | 56081.31 | 01-FEB-19:07 | 2.13 |
March | 0.150094E+12 | 2.12 | 56081.31 | 01-MAR-19:07 | 2.13 |
April | 0.145271E+12 | 2.12 | 56081.31 | 01-APR-09:20 | 2.12 |
May | 0.150126E+12 | 2.11 | 56081.31 | 01-MAY-09:20 | 2.12 |
June | 0.145296E+12 | 2.10 | 56081.31 | 01-JUN-07:45 | 2.12 |
July | 0.150136E+12 | 2.09 | 56081.31 | 01-JUL-08:00 | 2.09 |
August | 0.150131E+12 | 2.10 | 56081.31 | 01-AUG-06:30 | 2.09 |
September | 0.145286E+12 | 2.10 | 56081.31 | 01-SEP-06:40 | 2.09 |
October | 0.150108E+12 | 2.10 | 56081.31 | 01-OCT-10:01 | 2.11 |
November | 0.145246E+12 | 2.12 | 56081.31 | 01-NOV-10:35 | 2.10 |
December | 0.150073E+12 | 2.12 | 56081.31 | 01-DEC-19:06 | 2.12 |
Annual Sum or Average | 0.176740E+13 | 2.11 | |||
Minimum of Months | 0.135562E+12 | 2.09 | 56081.31 | 2.09 | |
Maximum of Months | 0.150136E+12 | 2.12 | 56081.31 | 2.13 |
Report: FanReportMonthly
For: LAUNDRY_FLR_1 EXHAUST FAN
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.493775E+09 | 0.74 | 184.35 | 01-JAN-00:05 | 0.74 |
February | 0.445990E+09 | 0.74 | 184.35 | 01-FEB-00:03 | 0.74 |
March | 0.493775E+09 | 0.74 | 184.35 | 01-MAR-00:03 | 0.74 |
April | 0.477847E+09 | 0.74 | 184.35 | 01-APR-00:10 | 0.74 |
May | 0.493775E+09 | 0.74 | 184.35 | 01-MAY-00:10 | 0.74 |
June | 0.477847E+09 | 0.73 | 184.35 | 01-JUN-00:10 | 0.74 |
July | 0.493775E+09 | 0.73 | 184.35 | 01-JUL-00:10 | 0.73 |
August | 0.493775E+09 | 0.73 | 184.35 | 01-AUG-00:10 | 0.73 |
September | 0.477847E+09 | 0.73 | 184.35 | 01-SEP-00:10 | 0.73 |
October | 0.493775E+09 | 0.73 | 184.35 | 01-OCT-00:10 | 0.74 |
November | 0.477847E+09 | 0.74 | 184.35 | 01-NOV-00:10 | 0.74 |
December | 0.493775E+09 | 0.74 | 184.35 | 01-DEC-00:03 | 0.74 |
Annual Sum or Average | 0.581380E+10 | 0.74 | |||
Minimum of Months | 0.445990E+09 | 0.73 | 184.35 | 0.73 | |
Maximum of Months | 0.493775E+09 | 0.74 | 184.35 | 0.74 |
Report: FanReportMonthly
For: LOBBY_FLR_1 EXHAUST FAN
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: BANQUET_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: DINING_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.279806E+10 | 0.52 | 1474.84 | 01-JAN-07:10 | 0.74 |
February | 0.252728E+10 | 0.52 | 1474.84 | 01-FEB-07:10 | 0.74 |
March | 0.279806E+10 | 0.52 | 1474.84 | 01-MAR-07:10 | 0.74 |
April | 0.270780E+10 | 0.52 | 1474.84 | 01-APR-06:10 | 0.74 |
May | 0.279806E+10 | 0.52 | 1474.84 | 01-MAY-06:05 | 0.74 |
June | 0.270780E+10 | 0.52 | 1474.84 | 01-JUN-06:05 | 0.74 |
July | 0.279806E+10 | 0.52 | 1474.84 | 01-JUL-06:10 | 0.73 |
August | 0.279806E+10 | 0.52 | 1474.84 | 01-AUG-06:05 | 0.73 |
September | 0.270780E+10 | 0.52 | 1474.84 | 01-SEP-06:05 | 0.73 |
October | 0.279806E+10 | 0.52 | 1474.84 | 01-OCT-06:10 | 0.73 |
November | 0.270780E+10 | 0.52 | 1474.84 | 01-NOV-06:05 | 0.73 |
December | 0.279806E+10 | 0.52 | 1474.84 | 01-DEC-07:05 | 0.74 |
Annual Sum or Average | 0.329449E+11 | 0.52 | |||
Minimum of Months | 0.252728E+10 | 0.52 | 1474.84 | 0.73 | |
Maximum of Months | 0.279806E+10 | 0.52 | 1474.84 | 0.74 |
Report: FanReportMonthly
For: ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.540703E+09 | 1.19 | 2129.05 | 01-JAN-16:02 | 1.59 |
February | 0.465066E+09 | 1.23 | 2129.05 | 01-FEB-09:02 | 1.60 |
March | 0.501955E+09 | 1.26 | 2129.05 | 01-MAR-09:02 | 1.60 |
April | 0.715629E+09 | 1.39 | 2129.05 | 01-APR-15:01 | 1.60 |
May | 0.105698E+10 | 1.46 | 2129.05 | 01-MAY-15:01 | 1.60 |
June | 0.134764E+10 | 1.51 | 2129.05 | 01-JUN-08:61 | 1.60 |
July | 0.134748E+10 | 1.51 | 2129.05 | 01-JUL-08:61 | 1.58 |
August | 0.125599E+10 | 1.48 | 2129.05 | 01-AUG-08:61 | 1.58 |
September | 0.112016E+10 | 1.49 | 2129.05 | 01-SEP-08:62 | 1.58 |
October | 0.731670E+09 | 1.38 | 2129.05 | 01-OCT-08:62 | 1.59 |
November | 0.521232E+09 | 1.30 | 2129.05 | 02-NOV-15:01 | 1.59 |
December | 0.608036E+09 | 1.19 | 2129.05 | 02-DEC-09:02 | 1.60 |
Annual Sum or Average | 0.102125E+11 | 1.37 | |||
Minimum of Months | 0.465066E+09 | 1.19 | 2129.05 | 1.58 | |
Maximum of Months | 0.134764E+10 | 1.51 | 2129.05 | 1.60 |
Report: FanReportMonthly
For: ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.637136E+09 | 1.15 | 2113.77 | 01-JAN-16:02 | 1.59 |
February | 0.484885E+09 | 1.16 | 2113.77 | 01-FEB-09:02 | 1.60 |
March | 0.456437E+09 | 1.17 | 2113.77 | 01-MAR-09:02 | 1.60 |
April | 0.629013E+09 | 1.32 | 2113.77 | 01-APR-15:01 | 1.60 |
May | 0.103214E+10 | 1.44 | 2113.77 | 01-MAY-15:01 | 1.60 |
June | 0.135869E+10 | 1.51 | 2113.77 | 01-JUN-08:61 | 1.60 |
July | 0.134328E+10 | 1.51 | 2113.77 | 01-JUL-08:61 | 1.58 |
August | 0.118166E+10 | 1.47 | 2113.77 | 01-AUG-08:61 | 1.58 |
September | 0.949617E+09 | 1.44 | 2113.77 | 01-SEP-08:62 | 1.58 |
October | 0.517759E+09 | 1.26 | 2113.77 | 01-OCT-15:01 | 1.59 |
November | 0.461066E+09 | 1.17 | 2113.77 | 02-NOV-08:62 | 1.59 |
December | 0.762239E+09 | 1.18 | 2113.77 | 01-DEC-09:02 | 1.60 |
Annual Sum or Average | 0.981391E+10 | 1.32 | |||
Minimum of Months | 0.456437E+09 | 1.15 | 2113.77 | 1.58 | |
Maximum of Months | 0.135869E+10 | 1.51 | 2113.77 | 1.60 |
Report: FanReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.206039E+10 | 0.71 | 3973.35 | 12-JAN-14:30 | 1.60 |
February | 0.207588E+10 | 0.85 | 3829.45 | 07-FEB-13:40 | 1.60 |
March | 0.205961E+10 | 0.84 | 3150.58 | 16-MAR-13:30 | 1.60 |
April | 0.320742E+10 | 1.21 | 3066.36 | 04-APR-13:30 | 1.60 |
May | 0.405904E+10 | 1.45 | 3195.96 | 19-MAY-20:20 | 1.60 |
June | 0.510173E+10 | 1.57 | 3652.29 | 18-JUN-20:03 | 1.59 |
July | 0.542736E+10 | 1.58 | 3938.37 | 02-JUL-19:40 | 1.59 |
August | 0.538554E+10 | 1.56 | 3872.80 | 06-AUG-19:05 | 1.59 |
September | 0.569742E+10 | 1.54 | 6724.91 | 19-SEP-13:10 | 1.59 |
October | 0.514611E+10 | 1.40 | 7324.17 | 22-OCT-13:20 | 1.59 |
November | 0.334255E+10 | 0.95 | 6568.71 | 10-NOV-11:35 | 1.59 |
December | 0.164376E+10 | 0.65 | 3653.81 | 16-DEC-13:40 | 1.61 |
Annual Sum or Average | 0.452068E+11 | 1.19 | |||
Minimum of Months | 0.164376E+10 | 0.65 | 3066.36 | 1.59 | |
Maximum of Months | 0.569742E+10 | 1.58 | 7324.17 | 1.61 |
Report: FanReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.266236E+10 | 1.13 | 13961.11 | 05-JAN-09:02 | 1.61 |
February | 0.255771E+10 | 1.13 | 13961.11 | 01-FEB-09:02 | 1.60 |
March | 0.297381E+10 | 1.13 | 13961.11 | 01-MAR-16:01 | 1.61 |
April | 0.492843E+10 | 1.15 | 13961.11 | 01-APR-08:62 | 1.60 |
May | 0.776848E+10 | 1.26 | 13961.11 | 01-MAY-15:01 | 1.60 |
June | 0.987675E+10 | 1.39 | 13961.11 | 01-JUN-08:61 | 1.60 |
July | 0.101578E+11 | 1.40 | 13961.11 | 01-JUL-08:61 | 1.59 |
August | 0.887603E+10 | 1.32 | 13961.11 | 01-AUG-08:61 | 1.58 |
September | 0.685595E+10 | 1.23 | 13961.11 | 01-SEP-08:62 | 1.58 |
October | 0.461932E+10 | 1.14 | 13961.11 | 01-OCT-08:62 | 1.59 |
November | 0.253393E+10 | 1.13 | 13961.11 | 03-NOV-15:02 | 1.59 |
December | 0.333189E+10 | 1.13 | 13961.11 | 02-DEC-16:02 | 1.60 |
Annual Sum or Average | 0.671425E+11 | 1.21 | |||
Minimum of Months | 0.253393E+10 | 1.13 | 13961.11 | 1.58 | |
Maximum of Months | 0.101578E+11 | 1.40 | 13961.11 | 1.61 |
Report: FanReportMonthly
For: ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.490110E+09 | 1.14 | 1864.23 | 01-JAN-16:02 | 1.59 |
February | 0.429992E+09 | 1.23 | 1864.23 | 01-FEB-19:02 | 1.60 |
March | 0.475939E+09 | 1.31 | 1864.23 | 01-MAR-19:02 | 1.60 |
April | 0.720706E+09 | 1.48 | 1864.23 | 01-APR-08:62 | 1.60 |
May | 0.105510E+10 | 1.54 | 1864.23 | 01-MAY-08:62 | 1.60 |
June | 0.139904E+10 | 1.56 | 1864.23 | 01-JUN-08:61 | 1.60 |
July | 0.138785E+10 | 1.55 | 1864.23 | 01-JUL-08:61 | 1.59 |
August | 0.128276E+10 | 1.53 | 1864.23 | 01-AUG-08:61 | 1.58 |
September | 0.110928E+10 | 1.53 | 1864.23 | 01-SEP-08:62 | 1.58 |
October | 0.680801E+09 | 1.41 | 1864.23 | 01-OCT-08:62 | 1.59 |
November | 0.484420E+09 | 1.30 | 1864.23 | 02-NOV-15:01 | 1.59 |
December | 0.558495E+09 | 1.15 | 1864.23 | 02-DEC-16:02 | 1.60 |
Annual Sum or Average | 0.100745E+11 | 1.39 | |||
Minimum of Months | 0.429992E+09 | 1.14 | 1864.23 | 1.58 | |
Maximum of Months | 0.139904E+10 | 1.56 | 1864.23 | 1.60 |
Report: FanReportMonthly
For: ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.584721E+09 | 1.13 | 1849.04 | 04-JAN-19:02 | 1.60 |
February | 0.425193E+09 | 1.14 | 1849.04 | 01-FEB-09:02 | 1.60 |
March | 0.409004E+09 | 1.14 | 1849.04 | 01-MAR-16:01 | 1.61 |
April | 0.631275E+09 | 1.40 | 1849.04 | 01-APR-08:62 | 1.60 |
May | 0.103003E+10 | 1.53 | 1849.04 | 01-MAY-08:62 | 1.60 |
June | 0.140935E+10 | 1.56 | 1849.04 | 01-JUN-08:61 | 1.60 |
July | 0.138521E+10 | 1.55 | 1849.04 | 01-JUL-08:61 | 1.59 |
August | 0.120916E+10 | 1.52 | 1849.04 | 01-AUG-08:61 | 1.58 |
September | 0.924760E+09 | 1.51 | 1849.04 | 01-SEP-08:62 | 1.58 |
October | 0.466593E+09 | 1.26 | 1849.04 | 01-OCT-08:62 | 1.59 |
November | 0.421857E+09 | 1.14 | 1849.04 | 02-NOV-08:62 | 1.59 |
December | 0.703675E+09 | 1.16 | 1849.04 | 01-DEC-16:01 | 1.60 |
Annual Sum or Average | 0.960083E+10 | 1.34 | |||
Minimum of Months | 0.409004E+09 | 1.13 | 1849.04 | 1.58 | |
Maximum of Months | 0.140935E+10 | 1.56 | 1849.04 | 1.61 |
Report: FanReportMonthly
For: ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.170737E+09 | 1.21 | 577.17 | 01-JAN-16:02 | 1.59 |
February | 0.143466E+09 | 1.23 | 577.17 | 01-FEB-09:02 | 1.60 |
March | 0.150400E+09 | 1.27 | 577.17 | 01-MAR-09:02 | 1.60 |
April | 0.205474E+09 | 1.41 | 577.17 | 01-APR-15:01 | 1.60 |
May | 0.304140E+09 | 1.48 | 577.17 | 01-MAY-15:01 | 1.60 |
June | 0.396985E+09 | 1.53 | 577.17 | 01-JUN-08:61 | 1.60 |
July | 0.397311E+09 | 1.52 | 577.17 | 01-JUL-08:61 | 1.58 |
August | 0.368654E+09 | 1.50 | 577.17 | 01-AUG-08:61 | 1.58 |
September | 0.319263E+09 | 1.49 | 577.17 | 01-SEP-08:62 | 1.58 |
October | 0.203095E+09 | 1.40 | 577.17 | 01-OCT-08:62 | 1.59 |
November | 0.153975E+09 | 1.31 | 577.17 | 02-NOV-08:62 | 1.59 |
December | 0.196482E+09 | 1.20 | 577.17 | 02-DEC-09:02 | 1.60 |
Annual Sum or Average | 0.300998E+10 | 1.38 | |||
Minimum of Months | 0.143466E+09 | 1.20 | 577.17 | 1.58 | |
Maximum of Months | 0.397311E+09 | 1.53 | 577.17 | 1.60 |
Report: FanReportMonthly
For: ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.205875E+09 | 1.20 | 572.43 | 01-JAN-09:02 | 1.59 |
February | 0.154713E+09 | 1.17 | 572.43 | 01-FEB-09:02 | 1.60 |
March | 0.139580E+09 | 1.19 | 572.43 | 01-MAR-09:02 | 1.60 |
April | 0.183744E+09 | 1.37 | 572.43 | 01-APR-15:01 | 1.60 |
May | 0.298234E+09 | 1.47 | 572.43 | 01-MAY-15:01 | 1.60 |
June | 0.400965E+09 | 1.53 | 572.43 | 01-JUN-08:61 | 1.60 |
July | 0.395975E+09 | 1.52 | 572.43 | 01-JUL-08:61 | 1.58 |
August | 0.348812E+09 | 1.49 | 572.43 | 01-AUG-08:61 | 1.58 |
September | 0.272634E+09 | 1.47 | 572.43 | 01-SEP-08:62 | 1.58 |
October | 0.148302E+09 | 1.28 | 572.43 | 01-OCT-15:01 | 1.59 |
November | 0.146275E+09 | 1.20 | 572.43 | 02-NOV-08:62 | 1.59 |
December | 0.248806E+09 | 1.23 | 572.43 | 01-DEC-09:02 | 1.60 |
Annual Sum or Average | 0.294391E+10 | 1.34 | |||
Minimum of Months | 0.139580E+09 | 1.17 | 572.43 | 1.58 | |
Maximum of Months | 0.400965E+09 | 1.53 | 572.43 | 1.60 |
Report: FanReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.886654E+09 | 1.37 | 2610.88 | 01-JAN-16:02 | 1.59 |
February | 0.806345E+09 | 1.38 | 2610.88 | 01-FEB-16:01 | 1.61 |
March | 0.799120E+09 | 1.36 | 2610.88 | 01-MAR-16:01 | 1.60 |
April | 0.102961E+10 | 1.43 | 2610.88 | 01-APR-15:01 | 1.60 |
May | 0.134636E+10 | 1.47 | 2610.88 | 01-MAY-15:01 | 1.60 |
June | 0.174725E+10 | 1.50 | 2610.88 | 01-JUN-08:61 | 1.60 |
July | 0.181920E+10 | 1.50 | 2610.88 | 01-JUL-08:61 | 1.58 |
August | 0.179914E+10 | 1.49 | 2610.88 | 01-AUG-08:61 | 1.58 |
September | 0.179273E+10 | 1.50 | 2610.88 | 01-SEP-08:62 | 1.58 |
October | 0.145419E+10 | 1.45 | 2610.88 | 01-OCT-08:62 | 1.59 |
November | 0.105525E+10 | 1.40 | 2610.88 | 02-NOV-15:01 | 1.59 |
December | 0.924601E+09 | 1.36 | 2610.88 | 01-DEC-16:01 | 1.60 |
Annual Sum or Average | 0.154605E+11 | 1.44 | |||
Minimum of Months | 0.799120E+09 | 1.36 | 2610.88 | 1.58 | |
Maximum of Months | 0.181920E+10 | 1.50 | 2610.88 | 1.61 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.102359E+10 | 0.921227E+09 | 843.97 | 27-JAN-07:10 | 759.57 | 759.57 | 36.97 | 1.46 |
February | 0.816573E+09 | 0.734915E+09 | 870.94 | 03-FEB-07:10 | 783.84 | 783.84 | 36.27 | 1.57 |
March | 0.794822E+09 | 0.715340E+09 | 836.65 | 02-MAR-09:03 | 752.99 | 752.99 | 34.10 | 1.43 |
April | 0.479087E+09 | 0.431178E+09 | 602.55 | 11-APR-08:04 | 542.29 | 542.29 | 33.37 | 0.82 |
May | 0.373849E+09 | 0.336464E+09 | 511.06 | 23-MAY-08:04 | 459.95 | 459.95 | 31.47 | 0.66 |
June | 0.310579E+09 | 0.279521E+09 | 469.90 | 30-JUN-10:40 | 422.91 | 422.91 | 35.38 | 0.59 |
July | 0.249368E+09 | 0.224431E+09 | 470.20 | 05-JUL-10:40 | 423.18 | 423.18 | 34.09 | 0.59 |
August | 0.211009E+09 | 0.189908E+09 | 453.55 | 24-AUG-08:04 | 408.19 | 408.19 | 32.59 | 0.56 |
September | 0.192054E+09 | 0.172849E+09 | 410.32 | 01-SEP-10:40 | 369.29 | 369.29 | 31.77 | 0.50 |
October | 0.296780E+09 | 0.267102E+09 | 513.12 | 13-OCT-08:05 | 461.81 | 461.81 | 28.12 | 0.66 |
November | 0.686247E+09 | 0.617622E+09 | 822.48 | 27-NOV-09:02 | 740.23 | 740.23 | 34.22 | 1.38 |
December | 0.111620E+10 | 0.100458E+10 | 886.32 | 27-DEC-07:10 | 797.69 | 797.69 | 37.69 | 1.63 |
Annual Sum or Average | 0.655016E+10 | 0.589514E+10 | ||||||
Minimum of Months | 0.192054E+09 | 0.172849E+09 | 410.32 | 369.29 | 369.29 | 28.12 | 0.50 | |
Maximum of Months | 0.111620E+10 | 0.100458E+10 | 886.32 | 797.69 | 797.69 | 37.69 | 1.63 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.179055E+10 | 0.161150E+10 | 4443.38 | 03-JAN-16:01 | 3999.04 | 3999.04 | 6.73 | 10.07 |
February | 0.285382E+10 | 0.256844E+10 | 5306.36 | 20-FEB-16:01 | 4775.72 | 4775.72 | 6.73 | 14.56 |
March | 0.442394E+10 | 0.398155E+10 | 5413.53 | 15-MAR-18:01 | 4872.18 | 4872.18 | 6.73 | 15.36 |
April | 0.885420E+10 | 0.796878E+10 | 6216.86 | 30-APR-10:40 | 5595.17 | 5595.17 | 6.73 | 26.01 |
May | 0.121595E+11 | 0.109435E+11 | 7072.91 | 30-MAY-18:03 | 6365.62 | 6365.62 | 6.73 | 33.44 |
June | 0.138684E+11 | 0.124816E+11 | 7628.85 | 06-JUN-18:03 | 6865.96 | 6865.96 | 6.73 | 36.01 |
July | 0.153235E+11 | 0.137911E+11 | 7404.16 | 02-JUL-18:50 | 6663.74 | 6663.74 | 6.73 | 35.07 |
August | 0.146022E+11 | 0.131420E+11 | 7205.74 | 23-AUG-18:30 | 6485.17 | 6485.17 | 6.73 | 34.14 |
September | 0.131598E+11 | 0.118438E+11 | 7076.96 | 19-SEP-17:00 | 6369.26 | 6369.26 | 6.73 | 33.47 |
October | 0.925235E+10 | 0.832712E+10 | 6421.35 | 01-OCT-10:40 | 5779.21 | 5779.21 | 6.73 | 28.58 |
November | 0.388578E+10 | 0.349720E+10 | 5980.17 | 03-NOV-15:02 | 5382.15 | 5382.15 | 6.73 | 22.13 |
December | 0.139212E+10 | 0.125291E+10 | 3782.95 | 09-DEC-16:01 | 3404.65 | 3404.65 | 6.73 | 7.78 |
Annual Sum or Average | 0.101566E+12 | 0.914095E+11 | ||||||
Minimum of Months | 0.139212E+10 | 0.125291E+10 | 3782.95 | 3404.65 | 3404.65 | 6.73 | 7.78 | |
Maximum of Months | 0.153235E+11 | 0.137911E+11 | 7628.85 | 6865.96 | 6865.96 | 6.73 | 36.01 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.828072E+10 | 0.745265E+10 | 5255.88 | 01-JAN-00:05 | 4730.29 | 4730.29 | 6.75 | 36.84 |
February | 0.937019E+10 | 0.843317E+10 | 5255.88 | 01-FEB-09:03 | 4730.29 | 4730.29 | 6.76 | 36.84 |
March | 0.115897E+11 | 0.104308E+11 | 5255.88 | 01-MAR-00:03 | 4730.29 | 4730.29 | 6.76 | 36.84 |
April | 0.133644E+11 | 0.120280E+11 | 5255.88 | 01-APR-00:10 | 4730.29 | 4730.29 | 6.79 | 36.84 |
May | 0.140774E+11 | 0.126696E+11 | 5255.88 | 01-MAY-00:10 | 4730.29 | 4730.29 | 8.35 | 36.84 |
June | 0.136232E+11 | 0.122609E+11 | 5255.88 | 01-JUN-00:10 | 4730.29 | 4730.29 | 8.93 | 36.84 |
July | 0.140774E+11 | 0.126696E+11 | 5255.88 | 01-JUL-00:10 | 4730.29 | 4730.29 | 9.15 | 36.84 |
August | 0.140774E+11 | 0.126696E+11 | 5255.88 | 01-AUG-00:10 | 4730.29 | 4730.29 | 9.51 | 36.84 |
September | 0.136232E+11 | 0.122609E+11 | 5255.88 | 01-SEP-00:10 | 4730.29 | 4730.29 | 9.20 | 36.84 |
October | 0.140679E+11 | 0.126611E+11 | 5255.88 | 01-OCT-00:10 | 4730.29 | 4730.29 | 7.46 | 36.84 |
November | 0.101894E+11 | 0.917042E+10 | 5255.88 | 01-NOV-00:10 | 4730.29 | 4730.29 | 6.83 | 36.84 |
December | 0.770002E+10 | 0.693002E+10 | 5255.88 | 01-DEC-00:03 | 4730.29 | 4730.29 | 6.76 | 36.84 |
Annual Sum or Average | 0.144041E+12 | 0.129637E+12 | ||||||
Minimum of Months | 0.770002E+10 | 0.693002E+10 | 5255.88 | 4730.29 | 4730.29 | 6.75 | 36.84 | |
Maximum of Months | 0.140774E+11 | 0.126696E+11 | 5255.88 | 4730.29 | 4730.29 | 9.51 | 36.84 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.128314E+09 | 38494137.67 | 47.91 | 01-JAN-00:05 | 14.37 | 14.37 | 49.20 | 0.37 |
February | 0.115896E+09 | 34768898.54 | 47.91 | 01-FEB-00:03 | 14.37 | 14.37 | 49.55 | 0.37 |
March | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAR-00:03 | 14.37 | 14.37 | 49.81 | 0.37 |
April | 0.124175E+09 | 37252391.29 | 47.91 | 01-APR-00:10 | 14.37 | 14.37 | 52.92 | 0.37 |
May | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAY-00:10 | 14.37 | 14.37 | 53.37 | 0.37 |
June | 0.124175E+09 | 37252391.29 | 47.91 | 01-JUN-00:10 | 14.37 | 14.37 | 53.40 | 0.37 |
July | 0.128314E+09 | 38494137.67 | 47.91 | 01-JUL-00:10 | 14.37 | 14.37 | 54.41 | 0.37 |
August | 0.128314E+09 | 38494137.67 | 47.91 | 01-AUG-00:10 | 14.37 | 14.37 | 54.26 | 0.37 |
September | 0.124175E+09 | 37252391.29 | 47.91 | 01-SEP-00:10 | 14.37 | 14.37 | 54.27 | 0.37 |
October | 0.128314E+09 | 38494137.67 | 47.91 | 01-OCT-00:10 | 14.37 | 14.37 | 53.26 | 0.37 |
November | 0.124175E+09 | 37252391.29 | 47.91 | 01-NOV-00:10 | 14.37 | 14.37 | 52.66 | 0.37 |
December | 0.128314E+09 | 38494137.67 | 47.91 | 01-DEC-00:03 | 14.37 | 14.37 | 50.42 | 0.37 |
Annual Sum or Average | 0.151079E+10 | 0.453237E+09 | ||||||
Minimum of Months | 0.115896E+09 | 34768898.54 | 47.91 | 14.37 | 14.37 | 49.20 | 0.37 | |
Maximum of Months | 0.128314E+09 | 38494137.67 | 47.91 | 14.37 | 14.37 | 54.41 | 0.37 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 36.75 | 60.00 | 47312.08 | 160680.34 | 27-JAN-09:02 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 38.18 | 60.00 | 42108.64 | 155354.24 | 03-FEB-07:10 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 38.02 | 60.00 | 36579.44 | 155356.75 | 02-MAR-09:02 |
April | 0.00 | 0.00 | 01-APR-00:10 | 32.34 | 60.00 | 22622.22 | 91791.34 | 11-APR-08:62 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 31.29 | 60.00 | 16813.78 | 78325.35 | 23-MAY-08:04 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 30.15 | 60.00 | 13907.61 | 68798.46 | 23-JUN-08:04 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 29.62 | 60.00 | 11502.78 | 69610.16 | 21-JUL-10:35 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.27 | 60.00 | 10211.06 | 66339.21 | 18-AUG-10:35 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 28.46 | 60.00 | 9603.50 | 69422.63 | 15-SEP-08:04 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.23 | 60.00 | 14586.99 | 88051.01 | 13-OCT-08:05 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 31.89 | 60.00 | 32498.72 | 148981.37 | 28-NOV-09:02 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 37.36 | 60.00 | 52039.07 | 156975.75 | 27-DEC-09:02 |
Annual Sum or Average | 0.00 | 25749.05 | ||||||
Minimum of Months | 0.00 | 0.00 | 25.23 | 60.00 | 9603.50 | 66339.21 | ||
Maximum of Months | 0.00 | 0.00 | 38.18 | 60.00 | 52039.07 | 160680.34 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 22553.43 | 314961.77 | 03-JAN-16:01 | 8.74 | 6.70 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 53722.21 | 463141.95 | 20-FEB-16:01 | 9.70 | 6.70 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 82660.88 | 481240.13 | 15-MAR-18:01 | 9.82 | 6.70 | 0.00 | 0.00 | 01-MAR-00:03 |
April | 209683.57 | 605429.93 | 19-APR-18:03 | 10.62 | 6.70 | 0.00 | 0.00 | 01-APR-00:10 |
May | 314878.61 | 640072.46 | 21-MAY-18:03 | 10.85 | 6.70 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 406754.43 | 738298.13 | 19-JUN-18:03 | 11.48 | 6.70 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 509212.93 | 943292.64 | 19-JUL-08:62 | 12.81 | 6.70 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 425135.68 | 802634.21 | 02-AUG-18:03 | 11.90 | 6.70 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 378249.18 | 713539.79 | 03-SEP-18:03 | 11.32 | 6.70 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 204755.95 | 698127.49 | 04-OCT-18:03 | 11.22 | 6.70 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 66170.14 | 469389.97 | 09-NOV-16:01 | 9.74 | 6.70 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 17252.46 | 223789.65 | 10-DEC-16:01 | 8.15 | 6.70 | 0.00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 225205.18 | 0.00 | ||||||
Minimum of Months | 17252.46 | 223789.65 | 8.15 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 509212.93 | 943292.64 | 12.81 | 6.70 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 49.20 | 59.72 | 25474.12 | 51727.49 | 30-JAN-07:50 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 49.55 | 58.79 | 25455.78 | 51721.75 | 01-FEB-07:50 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 49.81 | 58.90 | 24601.52 | 50754.91 | 01-MAR-07:20 |
April | 0.00 | 0.00 | 01-APR-00:10 | 52.92 | 59.47 | 23055.20 | 47839.30 | 03-APR-06:40 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 53.37 | 59.42 | 21280.26 | 44486.96 | 01-MAY-06:20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 53.40 | 58.57 | 19743.58 | 40782.56 | 01-JUN-06:15 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 54.41 | 59.72 | 18838.55 | 38099.17 | 03-JUL-06:15 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 54.26 | 59.04 | 18863.50 | 38237.61 | 31-AUG-06:40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 54.27 | 59.39 | 19756.74 | 40797.67 | 29-SEP-06:15 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 53.26 | 59.44 | 21296.80 | 44533.53 | 31-OCT-06:50 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 52.66 | 58.32 | 23074.28 | 48075.30 | 30-NOV-08:00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 50.42 | 59.81 | 24599.56 | 50643.54 | 29-DEC-08:00 |
Annual Sum or Average | 0.00 | 22151.34 | ||||||
Minimum of Months | 0.00 | 0.00 | 49.20 | 58.32 | 18838.55 | 38099.17 | ||
Maximum of Months | 0.00 | 0.00 | 54.41 | 59.81 | 25474.12 | 51727.49 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.809861E+11 | 0.00 | 0.201108E+11 | 0.150076E+12 | 0.00 | 0.00 |
February | 0.708501E+11 | 0.00 | 0.759769E+11 | 0.135562E+12 | 0.00 | 0.00 |
March | 0.758770E+11 | 0.00 | 0.145448E+12 | 0.150094E+12 | 0.00 | 0.00 |
April | 0.539197E+11 | 0.00 | 0.382942E+12 | 0.145271E+12 | 0.00 | 0.00 |
May | 0.450141E+11 | 0.00 | 0.597793E+12 | 0.150126E+12 | 0.00 | 0.00 |
June | 0.363420E+11 | 0.00 | 0.736192E+12 | 0.145296E+12 | 0.00 | 0.00 |
July | 0.310427E+11 | 0.00 | 0.981701E+12 | 0.150136E+12 | 0.00 | 0.00 |
August | 0.275266E+11 | 0.00 | 0.808393E+12 | 0.150131E+12 | 0.00 | 0.00 |
September | 0.245386E+11 | 0.00 | 0.694503E+12 | 0.145286E+12 | 0.00 | 0.00 |
October | 0.350683E+11 | 0.00 | 0.364337E+12 | 0.150108E+12 | 0.00 | 0.00 |
November | 0.565146E+11 | 0.00 | 0.944464E+11 | 0.145246E+12 | 0.00 | 0.00 |
December | 0.837277E+11 | 0.00 | 0.146740E+11 | 0.150073E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.621408E+12 | 0.00 | 0.491652E+13 | 0.176740E+13 | 0.00 | 0.00 |
Minimum of Months | 0.245386E+11 | 0.00 | 0.146740E+11 | 0.135562E+12 | 0.00 | 0.00 |
Maximum of Months | 0.837277E+11 | 0.00 | 0.981701E+12 | 0.150136E+12 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.273843E+11 | 0.00 | 0.122869E+10 | 0.587890E+10 | 0.00 | 0.00 |
February | 0.190765E+11 | 0.00 | 0.621055E+10 | 0.530997E+10 | 0.00 | 0.00 |
March | 0.159141E+11 | 0.00 | 0.124469E+11 | 0.587890E+10 | 0.00 | 0.00 |
April | 0.437768E+10 | 0.00 | 0.399969E+11 | 0.568926E+10 | 0.00 | 0.00 |
May | 0.346645E+09 | 0.00 | 0.693058E+11 | 0.587890E+10 | 0.00 | 0.00 |
June | 38046.70 | 0.00 | 0.932452E+11 | 0.568926E+10 | 0.00 | 0.00 |
July | 11380.94 | 0.00 | 0.127410E+12 | 0.587890E+10 | 0.00 | 0.00 |
August | 25201.66 | 0.00 | 0.102279E+12 | 0.587890E+10 | 0.00 | 0.00 |
September | 0.490805E+09 | 0.00 | 0.814589E+11 | 0.568926E+10 | 0.00 | 0.00 |
October | 0.380166E+10 | 0.00 | 0.377637E+11 | 0.587890E+10 | 0.00 | 0.00 |
November | 0.185253E+11 | 0.00 | 0.755815E+10 | 0.568926E+10 | 0.00 | 0.00 |
December | 0.290885E+11 | 0.00 | 0.724489E+09 | 0.587890E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.119006E+12 | 0.00 | 0.579628E+12 | 0.692193E+11 | 0.00 | 0.00 |
Minimum of Months | 11380.94 | 0.00 | 0.724489E+09 | 0.530997E+10 | 0.00 | 0.00 |
Maximum of Months | 0.290885E+11 | 0.00 | 0.127410E+12 | 0.587890E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.150076E+12 | 0.201108E+11 | 0.809861E+11 | 0.447916E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.135562E+12 | 0.759769E+11 | 0.708501E+11 | 0.314634E+12 | 0.316773E+09 | 0.00 | 0.00 | 0.00 |
March | 0.150094E+12 | 0.145448E+12 | 0.758770E+11 | 0.238212E+12 | 0.242167E+10 | 0.00 | 0.00 | 0.00 |
April | 0.145271E+12 | 0.382942E+12 | 0.539197E+11 | 0.564316E+11 | 0.517158E+11 | 0.00 | 0.00 | 0.00 |
May | 0.150126E+12 | 0.597793E+12 | 0.450141E+11 | 0.136527E+11 | 0.130575E+12 | 0.00 | 0.00 | 0.00 |
June | 0.145296E+12 | 0.736192E+12 | 0.363420E+11 | 0.131832E+11 | 0.241434E+12 | 0.00 | 0.00 | 0.00 |
July | 0.150136E+12 | 0.981701E+12 | 0.310427E+11 | 0.656806E+09 | 0.409835E+12 | 0.00 | 0.00 | 0.00 |
August | 0.150131E+12 | 0.808393E+12 | 0.275266E+11 | 0.452285E+10 | 0.251293E+12 | 0.00 | 0.00 | 0.00 |
September | 0.145286E+12 | 0.694503E+12 | 0.245386E+11 | 0.812478E+10 | 0.159961E+12 | 0.00 | 0.00 | 0.00 |
October | 0.150108E+12 | 0.364337E+12 | 0.350683E+11 | 0.364697E+11 | 0.408133E+11 | 0.00 | 0.00 | 0.00 |
November | 0.145246E+12 | 0.944464E+11 | 0.565146E+11 | 0.281688E+12 | 0.716029E+09 | 0.00 | 0.00 | 0.00 |
December | 0.150073E+12 | 0.146740E+11 | 0.837277E+11 | 0.547459E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.176740E+13 | 0.491652E+13 | 0.621408E+12 | 0.196295E+13 | 0.128908E+13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.135562E+12 | 0.146740E+11 | 0.245386E+11 | 0.656806E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.150136E+12 | 0.981701E+12 | 0.837277E+11 | 0.547459E+12 | 0.409835E+12 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.587890E+10 | 0.122869E+10 | 0.273843E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.530997E+10 | 0.621055E+10 | 0.190765E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.587890E+10 | 0.124469E+11 | 0.159141E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.568926E+10 | 0.399969E+11 | 0.437768E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.587890E+10 | 0.693058E+11 | 0.346645E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.568926E+10 | 0.932452E+11 | 38046.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.587890E+10 | 0.127410E+12 | 11380.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.587890E+10 | 0.102279E+12 | 25201.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.568926E+10 | 0.814589E+11 | 0.490805E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.587890E+10 | 0.377637E+11 | 0.380166E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.568926E+10 | 0.755815E+10 | 0.185253E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.587890E+10 | 0.724489E+09 | 0.290885E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.692193E+11 | 0.579628E+12 | 0.119006E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.530997E+10 | 0.724489E+09 | 11380.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.587890E+10 | 0.127410E+12 | 0.290885E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.150076E+12 | 0.809861E+11 | 0.201108E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.135562E+12 | 0.708501E+11 | 0.759769E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.150094E+12 | 0.758770E+11 | 0.145448E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.145271E+12 | 0.539197E+11 | 0.382942E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.150126E+12 | 0.450141E+11 | 0.597793E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.145296E+12 | 0.363420E+11 | 0.736192E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.150136E+12 | 0.310427E+11 | 0.981701E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.150131E+12 | 0.275266E+11 | 0.808393E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.145286E+12 | 0.245386E+11 | 0.694503E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.150108E+12 | 0.350683E+11 | 0.364337E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.145246E+12 | 0.565146E+11 | 0.944464E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.150073E+12 | 0.837277E+11 | 0.146740E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.176740E+13 | 0.621408E+12 | 0.491652E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.135562E+12 | 0.245386E+11 | 0.146740E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.150136E+12 | 0.837277E+11 | 0.981701E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.587890E+10 | 0.273843E+11 | 0.122869E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.530997E+10 | 0.190765E+11 | 0.621055E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.587890E+10 | 0.159141E+11 | 0.124469E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.568926E+10 | 0.437768E+10 | 0.399969E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.587890E+10 | 0.346645E+09 | 0.693058E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.568926E+10 | 38046.70 | 0.932452E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.587890E+10 | 11380.94 | 0.127410E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.587890E+10 | 25201.66 | 0.102279E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.568926E+10 | 0.490805E+09 | 0.814589E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.587890E+10 | 0.380166E+10 | 0.377637E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.568926E+10 | 0.185253E+11 | 0.755815E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.587890E+10 | 0.290885E+11 | 0.724489E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.692193E+11 | 0.119006E+12 | 0.579628E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.530997E+10 | 11380.94 | 0.724489E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.587890E+10 | 0.290885E+11 | 0.127410E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.704897E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.14 |
February | 0.574923E+11 | 0.00 | 0.00 | 0.00 | 1016797.94 | 0.00 | 0.00 | 0.00 | 2.13 |
March | 0.568749E+11 | 0.00 | 1294454.31 | 0.00 | 47443850.07 | 0.569601E+09 | 0.00 | 234232.17 | 2.14 |
April | 0.319406E+11 | 0.00 | 0.213700E+09 | 0.00 | 0.172750E+10 | 77481966.95 | 0.00 | 3957304.73 | 2.14 |
May | 0.157247E+11 | 0.00 | 0.264044E+09 | 0.00 | 0.530600E+10 | 9258254.07 | 0.00 | 3288028.95 | 2.14 |
June | 0.479149E+10 | 0.00 | 0.217923E+09 | 0.00 | 0.102459E+11 | 0.00 | 0.00 | 1966999.47 | 2.15 |
July | 0.304615E+09 | 0.00 | 4035668.78 | 0.00 | 0.307897E+11 | 0.00 | 0.00 | 17538.11 | 2.15 |
August | 0.310689E+10 | 0.00 | 0.00 | 0.00 | 0.147104E+11 | 0.00 | 0.00 | 0.00 | 2.15 |
September | 0.106773E+11 | 0.00 | 0.00 | 0.00 | 0.127392E+11 | 0.00 | 0.00 | 0.00 | 2.16 |
October | 0.375426E+11 | 0.00 | 0.00 | 0.00 | 0.233539E+10 | 0.00 | 0.00 | 0.00 | 2.15 |
November | 0.608677E+11 | 0.00 | 0.00 | 0.00 | 22241198.04 | 0.00 | 0.00 | 0.00 | 2.13 |
December | 0.710390E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.13 |
Annual Sum or Average | 0.420852E+12 | 0.00 | 0.700997E+09 | 0.00 | 0.779247E+11 | 0.656341E+09 | 0.00 | 9464103.42 | 2.14 |
Minimum of Months | 0.304615E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.13 |
Maximum of Months | 0.710390E+11 | 0.00 | 0.264044E+09 | 0.00 | 0.307897E+11 | 0.569601E+09 | 0.00 | 3957304.73 | 2.16 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.752765E+10 | 0.00 | 0.00 | 9000.29 | 0.00 | 0.202965E+10 | 46253076.58 | 0.00 | 5.28 |
February | 0.678453E+10 | 32325.87 | 0.00 | 13034.30 | 106203.31 | 0.103099E+10 | 17248973.45 | 0.00 | 5.28 |
March | 0.714882E+10 | 0.00 | 0.00 | 0.00 | 6672048.53 | 0.677455E+09 | 0.00 | 0.00 | 5.29 |
April | 0.432476E+10 | 0.00 | 0.00 | 0.00 | 0.265009E+09 | 37406733.77 | 0.00 | 0.00 | 5.29 |
May | 0.214361E+10 | 0.00 | 0.00 | 0.00 | 0.759314E+09 | 0.00 | 0.00 | 0.00 | 5.31 |
June | 0.652796E+09 | 0.00 | 0.00 | 0.00 | 0.142586E+10 | 0.00 | 0.00 | 0.00 | 5.31 |
July | 41500931.64 | 0.00 | 0.00 | 0.00 | 0.419536E+10 | 0.00 | 0.00 | 0.00 | 5.32 |
August | 0.423284E+09 | 3304997.79 | 0.00 | 0.00 | 0.200085E+10 | 0.00 | 0.00 | 0.00 | 5.31 |
September | 0.145468E+10 | 0.188536E+09 | 0.00 | 0.00 | 0.154706E+10 | 0.00 | 0.00 | 0.00 | 5.33 |
October | 0.509679E+10 | 95678875.07 | 0.00 | 118187.94 | 0.222497E+09 | 0.00 | 17915952.95 | 0.00 | 5.31 |
November | 0.732532E+10 | 2618586.88 | 0.00 | 93935.73 | 411567.63 | 0.828086E+09 | 0.139152E+09 | 0.00 | 5.27 |
December | 0.704450E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.263390E+10 | 0.00 | 0.00 | 5.26 |
Annual Sum or Average | 0.499682E+11 | 0.290171E+09 | 0.00 | 234158.26 | 0.104231E+11 | 0.723750E+10 | 0.220570E+09 | 0.00 | 5.30 |
Minimum of Months | 41500931.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.26 |
Maximum of Months | 0.752765E+10 | 0.188536E+09 | 0.00 | 118187.94 | 0.419536E+10 | 0.263390E+10 | 0.139152E+09 | 0.00 | 5.33 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.701016E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 |
February | 0.571757E+10 | 0.00 | 0.00 | 0.00 | 101119.87 | 0.00 | 0.00 | 0.00 | 3.33 |
March | 0.571282E+10 | 0.00 | 0.00 | 0.00 | 4870285.64 | 0.00 | 0.00 | 0.00 | 3.34 |
April | 0.318418E+10 | 0.00 | 0.00 | 0.00 | 0.193444E+09 | 0.00 | 0.00 | 0.00 | 3.33 |
May | 0.156474E+10 | 0.00 | 0.00 | 0.00 | 0.554264E+09 | 0.00 | 0.00 | 0.00 | 3.35 |
June | 0.476511E+09 | 0.00 | 0.00 | 0.00 | 0.104081E+10 | 0.00 | 0.00 | 0.00 | 3.35 |
July | 30293753.19 | 0.00 | 0.00 | 0.00 | 0.306241E+10 | 0.00 | 0.00 | 0.00 | 3.35 |
August | 0.308978E+09 | 0.00 | 0.00 | 0.00 | 0.146294E+10 | 0.00 | 0.00 | 0.00 | 3.35 |
September | 0.106185E+10 | 0.00 | 0.00 | 0.00 | 0.126691E+10 | 0.00 | 0.00 | 0.00 | 3.36 |
October | 0.373358E+10 | 0.00 | 0.00 | 0.00 | 0.232253E+09 | 0.00 | 0.00 | 0.00 | 3.34 |
November | 0.605325E+10 | 0.00 | 0.00 | 0.00 | 2211872.10 | 0.00 | 0.00 | 0.00 | 3.32 |
December | 0.706478E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.32 |
Annual Sum or Average | 0.419187E+11 | 0.00 | 0.00 | 0.00 | 0.782022E+10 | 0.00 | 0.00 | 0.00 | 3.34 |
Minimum of Months | 30293753.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.32 |
Maximum of Months | 0.706478E+10 | 0.00 | 0.00 | 0.00 | 0.306241E+10 | 0.00 | 0.00 | 0.00 | 3.36 |
Report: MechanicalVentilationLoadsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.722559E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.281070E+09 | 0.00 | 0.00 | 1.69 |
February | 0.591008E+10 | 0.00 | 0.00 | 0.00 | 108281.82 | 0.212443E+09 | 0.00 | 0.00 | 1.68 |
March | 0.605552E+10 | 0.00 | 0.00 | 0.00 | 5215230.04 | 61914420.34 | 0.00 | 0.00 | 1.69 |
April | 0.340970E+10 | 0.00 | 0.00 | 0.00 | 0.207145E+09 | 0.00 | 0.00 | 0.00 | 1.69 |
May | 0.167556E+10 | 0.00 | 0.00 | 0.00 | 0.593520E+09 | 0.00 | 0.00 | 0.00 | 1.69 |
June | 0.510260E+09 | 0.00 | 0.00 | 0.00 | 0.111453E+10 | 0.00 | 0.00 | 0.00 | 1.69 |
July | 32439348.22 | 0.00 | 0.00 | 0.00 | 0.327931E+10 | 0.00 | 0.00 | 0.00 | 1.70 |
August | 0.330862E+09 | 0.00 | 0.00 | 0.00 | 0.156655E+10 | 0.00 | 0.00 | 0.00 | 1.70 |
September | 0.113706E+10 | 0.00 | 0.00 | 0.00 | 0.135664E+10 | 0.00 | 0.00 | 0.00 | 1.70 |
October | 0.399802E+10 | 0.00 | 0.00 | 0.00 | 0.248703E+09 | 0.00 | 0.00 | 0.00 | 1.69 |
November | 0.641512E+10 | 0.00 | 0.00 | 0.00 | 2368530.86 | 66858506.02 | 0.00 | 0.00 | 1.68 |
December | 0.668588E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.879272E+09 | 0.00 | 0.00 | 1.68 |
Annual Sum or Average | 0.433861E+11 | 0.00 | 0.00 | 0.00 | 0.837409E+10 | 0.150156E+10 | 0.00 | 0.00 | 1.69 |
Minimum of Months | 32439348.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.68 |
Maximum of Months | 0.722559E+10 | 0.00 | 0.00 | 0.00 | 0.327931E+10 | 0.879272E+09 | 0.00 | 0.00 | 1.70 |
Report: MechanicalVentilationLoadsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.255061E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124054E+10 | 0.00 | 0.00 | 1.48 |
February | 0.241884E+10 | 0.00 | 0.00 | 0.00 | 54686.45 | 0.673268E+09 | 0.00 | 0.00 | 1.47 |
March | 0.284468E+10 | 0.00 | 0.00 | 0.00 | 2633890.29 | 0.244865E+09 | 0.00 | 0.00 | 1.48 |
April | 0.172203E+10 | 0.00 | 0.00 | 0.00 | 0.104616E+09 | 0.00 | 0.00 | 0.00 | 1.48 |
May | 0.846221E+09 | 0.00 | 0.00 | 0.00 | 0.299750E+09 | 0.00 | 0.00 | 0.00 | 1.48 |
June | 0.257701E+09 | 0.00 | 0.00 | 0.00 | 0.562880E+09 | 0.00 | 0.00 | 0.00 | 1.48 |
July | 16383109.37 | 0.00 | 0.00 | 0.00 | 0.165618E+10 | 0.00 | 0.00 | 0.00 | 1.49 |
August | 0.167098E+09 | 0.00 | 0.00 | 0.00 | 0.791169E+09 | 0.00 | 0.00 | 0.00 | 1.48 |
September | 0.574257E+09 | 0.00 | 0.00 | 0.00 | 0.685153E+09 | 0.00 | 0.00 | 0.00 | 1.49 |
October | 0.201915E+10 | 0.00 | 0.00 | 0.00 | 0.125604E+09 | 0.00 | 0.00 | 0.00 | 1.48 |
November | 0.283627E+10 | 0.00 | 0.00 | 0.00 | 1196198.51 | 0.437381E+09 | 0.00 | 0.00 | 1.47 |
December | 0.207272E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174798E+10 | 0.00 | 0.00 | 1.47 |
Annual Sum or Average | 0.183260E+11 | 0.00 | 0.00 | 0.00 | 0.422924E+10 | 0.434403E+10 | 0.00 | 0.00 | 1.48 |
Minimum of Months | 16383109.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.47 |
Maximum of Months | 0.284468E+10 | 0.00 | 0.00 | 0.00 | 0.165618E+10 | 0.174798E+10 | 0.00 | 0.00 | 1.49 |
Report: MechanicalVentilationLoadsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.175162E+10 | 0.00 | 0.00 | 65693493.32 | 0.00 | 0.00 | 0.916844E+11 | 0.00 | 44.24 |
February | 0.119385E+10 | 1348304.61 | 0.00 | 60066590.20 | 0.00 | 0.00 | 0.750083E+11 | 0.00 | 44.23 |
March | 0.812177E+09 | 62903586.44 | 0.00 | 68028185.65 | 2035468.06 | 0.00 | 0.753219E+11 | 0.00 | 44.31 |
April | 0.362258E+09 | 0.247668E+10 | 0.00 | 53394594.37 | 0.102684E+09 | 0.00 | 0.420513E+11 | 0.00 | 44.26 |
May | 88971891.39 | 0.705758E+10 | 0.00 | 40363667.28 | 0.332946E+09 | 0.00 | 0.207365E+11 | 0.00 | 44.44 |
June | 20757754.67 | 0.134005E+11 | 0.00 | 21684573.39 | 0.477899E+09 | 0.00 | 0.631128E+10 | 0.00 | 44.44 |
July | 0.00 | 0.396654E+11 | 0.00 | 2983725.95 | 0.117139E+10 | 0.00 | 0.400945E+09 | 0.00 | 44.51 |
August | 3258641.85 | 0.189151E+11 | 0.00 | 14245036.79 | 0.593580E+09 | 0.00 | 0.410259E+10 | 0.00 | 44.47 |
September | 46902003.15 | 0.163757E+11 | 0.00 | 25776173.05 | 0.517921E+09 | 0.00 | 0.140872E+11 | 0.00 | 44.60 |
October | 0.505848E+09 | 0.300384E+10 | 0.00 | 57105694.22 | 93543585.73 | 0.00 | 0.492334E+11 | 0.00 | 44.41 |
November | 0.126608E+10 | 29129822.81 | 0.00 | 65580130.08 | 362673.88 | 0.00 | 0.794090E+11 | 0.00 | 44.11 |
December | 0.201411E+10 | 0.00 | 0.00 | 64919938.63 | 0.00 | 0.00 | 0.921487E+11 | 0.00 | 44.09 |
Annual Sum or Average | 0.806583E+10 | 0.100988E+12 | 0.00 | 0.539842E+09 | 0.329237E+10 | 0.00 | 0.550495E+12 | 0.00 | 44.34 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 2983725.95 | 0.00 | 0.00 | 0.400945E+09 | 0.00 | 44.09 |
Maximum of Months | 0.201411E+10 | 0.396654E+11 | 0.00 | 68028185.65 | 0.117139E+10 | 0.00 | 0.921487E+11 | 0.00 | 44.60 |
Report: MechanicalVentilationLoadsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.396207E+11 | 0.00 | 0.00 | 208494.68 | 0.00 | 0.00 | 0.122642E+10 | 0.00 | 7.98 |
February | 0.324196E+11 | 240750.86 | 0.00 | 337787.53 | 348462.94 | 0.00 | 0.895736E+09 | 0.00 | 7.98 |
March | 0.326038E+11 | 3716910.38 | 0.00 | 76466.69 | 24661682.07 | 0.00 | 0.684106E+09 | 0.00 | 8.00 |
April | 0.170507E+11 | 45149509.57 | 0.00 | 578528.01 | 0.108203E+10 | 0.00 | 0.150252E+10 | 0.00 | 7.99 |
May | 0.713753E+10 | 59637835.29 | 0.00 | 1401925.64 | 0.316999E+10 | 0.00 | 0.197860E+10 | 0.00 | 8.03 |
June | 0.136139E+10 | 0.715679E+09 | 0.00 | 2087792.70 | 0.534902E+10 | 0.00 | 0.141309E+10 | 0.00 | 8.03 |
July | 73214552.46 | 0.490114E+10 | 0.00 | 441497.05 | 0.129432E+11 | 0.00 | 0.102862E+09 | 0.00 | 8.05 |
August | 0.785340E+09 | 0.210664E+10 | 0.00 | 1224656.97 | 0.641773E+10 | 0.00 | 0.101381E+10 | 0.00 | 8.04 |
September | 0.446965E+10 | 0.256650E+10 | 0.00 | 1084889.84 | 0.481562E+10 | 0.00 | 0.171654E+10 | 0.00 | 8.06 |
October | 0.184618E+11 | 0.688666E+09 | 0.00 | 1629377.82 | 0.664647E+09 | 0.00 | 0.329177E+10 | 0.00 | 8.02 |
November | 0.325557E+11 | 11543759.37 | 0.00 | 940319.75 | 1344564.16 | 0.00 | 0.271495E+10 | 0.00 | 7.97 |
December | 0.402402E+11 | 0.00 | 0.00 | 109474.36 | 0.00 | 0.00 | 0.925331E+09 | 0.00 | 7.96 |
Annual Sum or Average | 0.226780E+12 | 0.110989E+11 | 0.00 | 10121211.05 | 0.344686E+11 | 0.00 | 0.174657E+11 | 0.00 | 8.01 |
Minimum of Months | 73214552.46 | 0.00 | 0.00 | 76466.69 | 0.00 | 0.00 | 0.102862E+09 | 0.00 | 7.96 |
Maximum of Months | 0.402402E+11 | 0.490114E+10 | 0.00 | 2087792.70 | 0.129432E+11 | 0.00 | 0.329177E+10 | 0.00 | 8.06 |
Report: MechanicalVentilationLoadsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.134934E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.81 |
February | 0.110054E+12 | 0.00 | 0.00 | 0.00 | 1946392.90 | 0.00 | 0.00 | 0.00 | 3.81 |
March | 0.109963E+12 | 0.00 | 0.00 | 0.00 | 93745073.42 | 0.00 | 0.00 | 0.00 | 3.81 |
April | 0.612903E+11 | 0.00 | 0.00 | 0.00 | 0.372349E+10 | 0.00 | 0.00 | 0.00 | 3.81 |
May | 0.301058E+11 | 0.00 | 0.00 | 9746.61 | 0.106687E+11 | 0.00 | 12796771.78 | 0.00 | 3.83 |
June | 0.914006E+10 | 0.128712E+09 | 0.00 | 44932.26 | 0.199052E+11 | 0.00 | 31953369.90 | 0.00 | 3.83 |
July | 0.581228E+09 | 0.222759E+09 | 0.00 | 3204.21 | 0.587237E+11 | 0.00 | 1874603.28 | 0.00 | 3.84 |
August | 0.594103E+10 | 81522703.83 | 0.00 | 5556.88 | 0.280777E+11 | 0.00 | 6281044.87 | 0.00 | 3.83 |
September | 0.204389E+11 | 22681356.67 | 0.00 | 0.00 | 0.243632E+11 | 0.00 | 0.00 | 0.00 | 3.84 |
October | 0.718654E+11 | 0.00 | 0.00 | 0.00 | 0.447050E+10 | 0.00 | 0.00 | 0.00 | 3.83 |
November | 0.116515E+12 | 0.00 | 0.00 | 0.00 | 42574938.75 | 0.00 | 0.00 | 0.00 | 3.80 |
December | 0.135986E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.79 |
Annual Sum or Average | 0.806814E+12 | 0.455675E+09 | 0.00 | 63439.96 | 0.150071E+12 | 0.00 | 52905789.83 | 0.00 | 3.82 |
Minimum of Months | 0.581228E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.79 |
Maximum of Months | 0.135986E+12 | 0.222759E+09 | 0.00 | 44932.26 | 0.587237E+11 | 0.00 | 31953369.90 | 0.00 | 3.84 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.542632E+09 | 0.00 | 0.00 | 2730288.05 | 0.00 | 0.156521E+10 | 0.577636E+09 | 0.00 | 0.47 |
February | 0.391044E+09 | 0.00 | 0.00 | 3710534.97 | 0.00 | 0.109856E+10 | 0.605074E+09 | 0.00 | 0.47 |
March | 0.323244E+09 | 2260543.40 | 438.58 | 6243855.52 | 28969.00 | 0.822827E+09 | 0.787779E+09 | 160.66 | 0.47 |
April | 0.120079E+09 | 0.122589E+09 | 27180.79 | 7187642.83 | 4227700.86 | 0.144393E+09 | 0.641340E+09 | 2260.66 | 0.47 |
May | 28905605.30 | 0.420357E+09 | 130319.40 | 5898791.18 | 17889871.51 | 320919.13 | 0.326284E+09 | 13782.52 | 0.47 |
June | 1855261.39 | 0.907237E+09 | 345884.90 | 1737874.99 | 29512497.85 | 35237.60 | 54145827.23 | 24149.83 | 0.47 |
July | 0.00 | 0.196697E+10 | 1511534.50 | 18633.64 | 88170806.10 | 0.00 | 95340.02 | 38380.51 | 0.47 |
August | 2506562.88 | 0.118744E+10 | 820140.89 | 1006148.82 | 54150119.51 | 54046.84 | 26519333.26 | 36262.41 | 0.47 |
September | 14359107.83 | 0.831863E+09 | 491199.85 | 3903211.89 | 38786985.03 | 215941.25 | 0.202204E+09 | 27291.17 | 0.47 |
October | 0.125675E+09 | 0.200567E+09 | 174420.39 | 8176159.61 | 9653150.28 | 46067326.71 | 0.769295E+09 | 4863.97 | 0.47 |
November | 0.328840E+09 | 1250661.69 | 0.00 | 5845015.70 | 0.00 | 0.930610E+09 | 0.833550E+09 | 0.00 | 0.47 |
December | 0.584198E+09 | 0.00 | 0.00 | 1879083.29 | 0.00 | 0.184788E+10 | 0.468683E+09 | 0.00 | 0.47 |
Annual Sum or Average | 0.246334E+10 | 0.564053E+10 | 3501119.31 | 48337240.47 | 0.242420E+09 | 0.645617E+10 | 0.529261E+10 | 147151.73 | 0.47 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 18633.64 | 0.00 | 0.00 | 95340.02 | 0.00 | 0.47 |
Maximum of Months | 0.584198E+09 | 0.196697E+10 | 1511534.50 | 8176159.61 | 88170806.10 | 0.184788E+10 | 0.833550E+09 | 38380.51 | 0.47 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.582478E+09 | 0.00 | 0.00 | 740015.22 | 0.00 | 0.193695E+10 | 0.167725E+09 | 0.00 | 0.47 |
February | 0.425227E+09 | 0.00 | 0.00 | 1562667.20 | 0.00 | 0.140141E+10 | 0.269945E+09 | 0.00 | 0.47 |
March | 0.362255E+09 | 2071701.89 | 4609.60 | 4041050.39 | 212080.76 | 0.103554E+10 | 0.538027E+09 | 1451.08 | 0.47 |
April | 0.131868E+09 | 0.117647E+09 | 43201.84 | 6301396.86 | 9136615.98 | 0.167669E+09 | 0.607054E+09 | 4031.35 | 0.47 |
May | 29872050.44 | 0.418324E+09 | 175588.11 | 5790288.48 | 19826355.16 | 320881.53 | 0.325384E+09 | 13907.94 | 0.47 |
June | 1791706.20 | 0.907336E+09 | 311791.91 | 1774510.99 | 29339602.23 | 21327.21 | 54179887.72 | 22582.35 | 0.47 |
July | 0.00 | 0.196839E+10 | 1408962.23 | 19394.29 | 86622660.81 | 0.00 | 94566.02 | 35566.25 | 0.47 |
August | 2524855.31 | 0.117961E+10 | 846012.52 | 965444.67 | 61797843.19 | 61289.64 | 26530977.15 | 39840.78 | 0.47 |
September | 16232329.93 | 0.818273E+09 | 534654.27 | 3297857.81 | 52230302.65 | 281279.60 | 0.200845E+09 | 28223.51 | 0.47 |
October | 0.157244E+09 | 0.185527E+09 | 213980.40 | 5386291.74 | 24621510.90 | 0.112002E+09 | 0.674471E+09 | 11602.97 | 0.47 |
November | 0.400964E+09 | 944925.70 | 0.00 | 2428459.44 | 305589.46 | 0.123761E+10 | 0.457594E+09 | 0.00 | 0.47 |
December | 0.589588E+09 | 0.00 | 0.00 | 392135.63 | 0.00 | 0.221984E+10 | 92478176.01 | 0.00 | 0.47 |
Annual Sum or Average | 0.270004E+10 | 0.559812E+10 | 3538800.87 | 32699512.72 | 0.284093E+09 | 0.811171E+10 | 0.341433E+10 | 157206.24 | 0.47 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 19394.29 | 0.00 | 0.00 | 94566.02 | 0.00 | 0.47 |
Maximum of Months | 0.589588E+09 | 0.196839E+10 | 1408962.23 | 6301396.86 | 86622660.81 | 0.221984E+10 | 0.674471E+09 | 39840.78 | 0.47 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.219859E+11 | 0.00 | 0.00 | 56825739.85 | 0.00 | 0.00 | 0.144070E+11 | 0.00 | 0.54 |
February | 0.153731E+11 | 0.00 | 0.00 | 59889846.55 | 0.00 | 0.00 | 0.130193E+11 | 0.00 | 0.54 |
March | 0.149061E+11 | 31051860.03 | 0.00 | 58096017.64 | 0.00 | 0.00 | 0.113418E+11 | 0.00 | 0.54 |
April | 0.476821E+10 | 0.171992E+10 | 0.00 | 52306088.42 | 0.00 | 0.00 | 0.755894E+10 | 0.00 | 0.54 |
May | 0.737532E+09 | 0.594419E+10 | 0.00 | 37199165.22 | 0.00 | 0.00 | 0.412566E+10 | 0.00 | 0.54 |
June | 16646598.14 | 0.127065E+11 | 0.00 | 10965885.02 | 0.00 | 0.00 | 0.755754E+09 | 0.00 | 0.54 |
July | 0.00 | 0.278869E+11 | 0.00 | 108086.04 | 0.00 | 0.00 | 1437294.56 | 0.00 | 0.54 |
August | 10079560.39 | 0.168464E+11 | 0.00 | 7145526.63 | 0.00 | 0.00 | 0.390715E+09 | 0.00 | 0.54 |
September | 90761303.67 | 0.118113E+11 | 0.00 | 31213930.72 | 1001403.44 | 0.00 | 0.287028E+10 | 0.00 | 0.54 |
October | 0.178212E+10 | 0.285282E+10 | 0.00 | 94283409.92 | 0.00 | 0.00 | 0.109941E+11 | 0.00 | 0.54 |
November | 0.136458E+11 | 16957850.79 | 0.00 | 93508601.92 | 0.00 | 0.00 | 0.147191E+11 | 0.00 | 0.54 |
December | 0.253194E+11 | 0.00 | 0.00 | 45408955.60 | 0.00 | 13599587.27 | 0.139788E+11 | 0.00 | 0.53 |
Annual Sum or Average | 0.986357E+11 | 0.798160E+11 | 0.00 | 0.546951E+09 | 1001403.44 | 13599587.27 | 0.941628E+11 | 0.00 | 0.54 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 108086.04 | 0.00 | 0.00 | 1437294.56 | 0.00 | 0.53 |
Maximum of Months | 0.253194E+11 | 0.278869E+11 | 0.00 | 94283409.92 | 1001403.44 | 13599587.27 | 0.147191E+11 | 0.00 | 0.54 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.823249E+10 | 0.00 | 0.00 | 24254265.87 | 0.00 | 0.789779E+10 | 0.203051E+11 | 0.00 | 0.53 |
February | 0.603625E+10 | 0.00 | 0.00 | 35661559.96 | 0.00 | 0.540043E+10 | 0.169877E+11 | 0.00 | 0.53 |
March | 0.514496E+10 | 24125556.89 | 165000.90 | 59481858.59 | 6714154.33 | 0.140747E+10 | 0.197012E+11 | 55638.98 | 0.54 |
April | 0.199085E+10 | 0.111432E+10 | 3501293.18 | 77254870.25 | 0.602251E+09 | 35344778.25 | 0.102794E+11 | 317017.97 | 0.54 |
May | 0.440679E+09 | 0.496674E+10 | 2478905.26 | 64491488.01 | 0.976353E+09 | 1819181.74 | 0.439474E+10 | 244235.63 | 0.54 |
June | 25731269.04 | 0.116231E+11 | 3132214.15 | 18571593.63 | 0.108362E+10 | 135299.81 | 0.739142E+09 | 100231.63 | 0.54 |
July | 0.00 | 0.255000E+11 | 6105094.02 | 256522.40 | 0.238847E+10 | 0.00 | 1289280.77 | 42118.36 | 0.54 |
August | 34444617.09 | 0.148629E+11 | 4789719.50 | 11349151.53 | 0.198316E+10 | 526936.42 | 0.361731E+09 | 155884.51 | 0.54 |
September | 0.271203E+09 | 0.974999E+10 | 7237279.40 | 36927121.18 | 0.205803E+10 | 2371128.31 | 0.268257E+10 | 244363.64 | 0.54 |
October | 0.233159E+10 | 0.204097E+10 | 3008029.81 | 71234460.36 | 0.809429E+09 | 28482551.72 | 0.104427E+11 | 190059.16 | 0.54 |
November | 0.574231E+10 | 3647610.54 | 0.00 | 42824578.25 | 13314877.35 | 0.242349E+10 | 0.202576E+11 | 0.00 | 0.53 |
December | 0.880341E+10 | 0.00 | 0.00 | 17959705.48 | 0.00 | 0.134742E+11 | 0.170724E+11 | 0.00 | 0.53 |
Annual Sum or Average | 0.390539E+11 | 0.698858E+11 | 30417536.22 | 0.460267E+09 | 0.992134E+10 | 0.306721E+11 | 0.123226E+12 | 1349549.87 | 0.54 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 256522.40 | 0.00 | 0.00 | 1289280.77 | 0.00 | 0.53 |
Maximum of Months | 0.880341E+10 | 0.255000E+11 | 7237279.40 | 77254870.25 | 0.238847E+10 | 0.134742E+11 | 0.203051E+11 | 317017.97 | 0.54 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.591497E+09 | 0.00 | 0.00 | 2254587.55 | 0.00 | 0.153997E+10 | 0.554490E+09 | 0.00 | 0.47 |
February | 0.383770E+09 | 0.00 | 0.00 | 4240990.60 | 0.00 | 0.999054E+09 | 0.711323E+09 | 0.00 | 0.47 |
March | 0.281545E+09 | 2234999.75 | 17947.32 | 6487133.35 | 34935.61 | 0.796437E+09 | 0.855625E+09 | 2228.97 | 0.47 |
April | 66940133.15 | 0.122097E+09 | 218005.61 | 8917545.31 | 4516959.76 | 0.136173E+09 | 0.700969E+09 | 13486.31 | 0.47 |
May | 10250340.29 | 0.424284E+09 | 178608.24 | 7113873.26 | 13918663.53 | 55353.74 | 0.343990E+09 | 10170.71 | 0.47 |
June | 958341.65 | 0.919782E+09 | 8274.16 | 2013595.13 | 17328378.49 | 21329.71 | 54780934.72 | 1288.97 | 0.47 |
July | 0.00 | 0.200675E+10 | 87030.76 | 27458.52 | 49855404.08 | 0.00 | 86515.14 | 4373.05 | 0.47 |
August | 1612476.87 | 0.121158E+10 | 292591.13 | 1168881.22 | 30556205.12 | 45181.64 | 27259552.06 | 11627.41 | 0.47 |
September | 7196756.83 | 0.848651E+09 | 145148.49 | 4412984.62 | 22366976.66 | 24143.43 | 0.209049E+09 | 5061.15 | 0.47 |
October | 99529925.17 | 0.201377E+09 | 238734.00 | 8529349.86 | 8774988.62 | 89392431.97 | 0.751762E+09 | 8135.31 | 0.47 |
November | 0.307291E+09 | 1250661.69 | 0.00 | 5985834.46 | 0.00 | 0.925234E+09 | 0.860333E+09 | 0.00 | 0.47 |
December | 0.633815E+09 | 0.00 | 0.00 | 1727320.37 | 0.00 | 0.179407E+10 | 0.473028E+09 | 0.00 | 0.47 |
Annual Sum or Average | 0.238441E+10 | 0.573801E+10 | 1186339.71 | 52879554.25 | 0.147353E+09 | 0.628048E+10 | 0.554270E+10 | 56371.88 | 0.47 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 27458.52 | 0.00 | 0.00 | 86515.14 | 0.00 | 0.47 |
Maximum of Months | 0.633815E+09 | 0.200675E+10 | 292591.13 | 8917545.31 | 49855404.08 | 0.179407E+10 | 0.860333E+09 | 13486.31 | 0.47 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.606919E+09 | 0.00 | 0.00 | 385258.22 | 0.00 | 0.189744E+10 | 0.183153E+09 | 0.00 | 0.47 |
February | 0.441904E+09 | 0.00 | 0.00 | 1736706.41 | 0.00 | 0.127397E+10 | 0.380529E+09 | 0.00 | 0.47 |
March | 0.368197E+09 | 1925487.83 | 9366.96 | 3995512.91 | 351319.47 | 0.936276E+09 | 0.631398E+09 | 3669.06 | 0.47 |
April | 0.106181E+09 | 0.120653E+09 | 464433.30 | 7848382.77 | 5684155.31 | 0.152140E+09 | 0.646723E+09 | 28936.73 | 0.47 |
May | 10385951.61 | 0.424314E+09 | 237337.72 | 6991488.57 | 13775276.57 | 55347.25 | 0.343935E+09 | 13296.61 | 0.47 |
June | 915930.38 | 0.920043E+09 | 8260.61 | 2059077.66 | 16957527.03 | 21327.21 | 54771096.87 | 1301.41 | 0.47 |
July | 0.00 | 0.200611E+10 | 86640.32 | 28150.21 | 50252227.64 | 0.00 | 85810.09 | 4752.78 | 0.47 |
August | 1641542.72 | 0.120801E+10 | 290564.80 | 1123117.82 | 33979328.73 | 45176.35 | 27272729.88 | 13618.10 | 0.47 |
September | 8344585.94 | 0.842337E+09 | 387069.42 | 3736753.88 | 28331955.99 | 1782156.09 | 0.206793E+09 | 10556.37 | 0.47 |
October | 0.145555E+09 | 0.191888E+09 | 444660.69 | 5481441.81 | 18015071.23 | 0.174169E+09 | 0.623897E+09 | 26954.93 | 0.47 |
November | 0.419169E+09 | 260240.15 | 8653.10 | 2126209.08 | 981604.59 | 0.120399E+10 | 0.473314E+09 | 17.31 | 0.47 |
December | 0.610483E+09 | 0.00 | 0.00 | 296824.47 | 0.00 | 0.215931E+10 | 0.132206E+09 | 0.00 | 0.47 |
Annual Sum or Average | 0.271970E+10 | 0.571554E+10 | 1936986.92 | 35808923.82 | 0.168328E+09 | 0.779921E+10 | 0.370408E+10 | 103103.29 | 0.47 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 28150.21 | 0.00 | 0.00 | 85810.09 | 0.00 | 0.47 |
Maximum of Months | 0.610483E+09 | 0.200611E+10 | 464433.30 | 7848382.77 | 50252227.64 | 0.215931E+10 | 0.646723E+09 | 28936.73 | 0.47 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.333359E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.253533E+09 | 0.00 | 0.00 | 1.03 |
February | 0.272998E+11 | 0.00 | 0.00 | 0.00 | 484520.26 | 96215046.83 | 0.00 | 0.00 | 1.03 |
March | 0.272948E+11 | 0.00 | 0.00 | 0.00 | 23336186.41 | 78429087.91 | 0.00 | 0.00 | 1.04 |
April | 0.152571E+11 | 0.00 | 0.00 | 0.00 | 0.926897E+09 | 0.00 | 0.00 | 0.00 | 1.04 |
May | 0.749750E+10 | 0.00 | 0.00 | 0.00 | 0.265578E+10 | 0.00 | 0.00 | 0.00 | 1.04 |
June | 0.228322E+10 | 0.00 | 0.00 | 0.00 | 0.498710E+10 | 0.00 | 0.00 | 0.00 | 1.04 |
July | 0.145154E+09 | 0.00 | 0.00 | 0.00 | 0.146737E+11 | 0.00 | 0.00 | 0.00 | 1.04 |
August | 0.148048E+10 | 0.00 | 0.00 | 0.00 | 0.700973E+10 | 0.00 | 0.00 | 0.00 | 1.04 |
September | 0.508790E+10 | 0.00 | 0.00 | 0.00 | 0.607044E+10 | 0.00 | 0.00 | 0.00 | 1.05 |
October | 0.178896E+11 | 0.00 | 0.00 | 0.00 | 0.111285E+10 | 0.00 | 0.00 | 0.00 | 1.04 |
November | 0.287882E+11 | 0.00 | 0.00 | 0.00 | 10598281.82 | 0.216215E+09 | 0.00 | 0.00 | 1.03 |
December | 0.329681E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.883131E+09 | 0.00 | 0.00 | 1.03 |
Annual Sum or Average | 0.199328E+12 | 0.00 | 0.00 | 0.00 | 0.374709E+11 | 0.152752E+10 | 0.00 | 0.00 | 1.04 |
Minimum of Months | 0.145154E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.03 |
Maximum of Months | 0.333359E+11 | 0.00 | 0.00 | 0.00 | 0.146737E+11 | 0.883131E+09 | 0.00 | 0.00 | 1.05 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.132440E+09 | 0.00 | 0.00 | 589623.28 | 0.00 | 0.439722E+09 | 99301224.72 | 0.00 | 0.47 |
February | 97046008.22 | 0.00 | 0.00 | 866875.23 | 0.00 | 0.325136E+09 | 0.101549E+09 | 0.00 | 0.47 |
March | 79691198.91 | 566251.34 | 0.00 | 1547175.39 | 6276.57 | 0.257452E+09 | 0.146333E+09 | 0.00 | 0.47 |
April | 29065039.68 | 30903744.14 | 1982.08 | 1831106.88 | 805695.95 | 49771719.88 | 0.147582E+09 | 34.42 | 0.47 |
May | 6870973.56 | 0.105904E+09 | 22956.67 | 1495525.25 | 3668889.52 | 1470252.01 | 80515685.15 | 1764.13 | 0.47 |
June | 460562.62 | 0.228673E+09 | 54201.98 | 430202.11 | 5549699.06 | 8809.40 | 13543976.18 | 2588.36 | 0.47 |
July | 0.00 | 0.496313E+09 | 327869.22 | 4209.24 | 17528238.99 | 0.00 | 24284.18 | 5085.43 | 0.47 |
August | 631287.79 | 0.300044E+09 | 160940.33 | 244812.77 | 10399579.46 | 15324.21 | 6630098.18 | 5797.82 | 0.47 |
September | 3593187.95 | 0.209765E+09 | 119618.45 | 957204.05 | 7901938.02 | 627885.69 | 49992327.56 | 5330.70 | 0.47 |
October | 29659656.17 | 50608807.43 | 14856.43 | 2048025.90 | 1974885.59 | 34970621.69 | 0.170625E+09 | 1193.79 | 0.47 |
November | 79497088.02 | 312665.42 | 0.00 | 1385383.28 | 0.00 | 0.273893E+09 | 0.169936E+09 | 0.00 | 0.47 |
December | 0.140610E+09 | 0.00 | 0.00 | 381487.97 | 0.00 | 0.516580E+09 | 68088328.12 | 0.00 | 0.47 |
Annual Sum or Average | 0.599565E+09 | 0.142309E+10 | 702425.16 | 11781631.35 | 47835203.16 | 0.189965E+10 | 0.105412E+10 | 21794.66 | 0.47 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 4209.24 | 0.00 | 0.00 | 24284.18 | 0.00 | 0.47 |
Maximum of Months | 0.140610E+09 | 0.496313E+09 | 327869.22 | 2048025.90 | 17528238.99 | 0.516580E+09 | 0.170625E+09 | 5797.82 | 0.47 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.130141E+09 | 0.00 | 0.00 | 136440.79 | 0.00 | 0.518848E+09 | 22848037.80 | 0.00 | 0.47 |
February | 0.100434E+09 | 0.00 | 0.00 | 351940.45 | 0.00 | 0.377533E+09 | 46216908.24 | 0.00 | 0.47 |
March | 87771839.99 | 530173.47 | 102.87 | 991035.94 | 42150.36 | 0.291458E+09 | 0.104746E+09 | 34.14 | 0.47 |
April | 32438130.95 | 30471208.58 | 2797.63 | 1602305.65 | 1233525.41 | 58871903.72 | 0.135311E+09 | 209.51 | 0.47 |
May | 7317462.67 | 0.105746E+09 | 22727.92 | 1465416.70 | 3814961.30 | 1794313.35 | 79764657.15 | 1761.79 | 0.47 |
June | 448222.24 | 0.228798E+09 | 37223.33 | 438840.11 | 5414750.01 | 5331.80 | 13549463.89 | 2094.66 | 0.47 |
July | 0.00 | 0.496323E+09 | 298738.25 | 4313.04 | 17487593.54 | 0.00 | 24177.04 | 4565.26 | 0.47 |
August | 631213.83 | 0.298617E+09 | 167798.05 | 234754.05 | 11782756.18 | 15322.41 | 6639351.40 | 6308.15 | 0.47 |
September | 3904410.70 | 0.206839E+09 | 107702.01 | 802905.33 | 10813663.05 | 3433651.19 | 47023173.98 | 5808.03 | 0.47 |
October | 38203247.38 | 47969648.51 | 36387.81 | 1316541.86 | 4586262.35 | 60033009.47 | 0.137723E+09 | 1281.75 | 0.47 |
November | 93888389.60 | 248847.11 | 0.00 | 552241.71 | 63781.68 | 0.354262E+09 | 75947060.41 | 0.00 | 0.47 |
December | 0.126135E+09 | 0.00 | 0.00 | 66891.62 | 0.00 | 0.587940E+09 | 11433626.08 | 0.00 | 0.47 |
Annual Sum or Average | 0.621312E+09 | 0.141554E+10 | 673477.86 | 7963627.25 | 55239443.87 | 0.225419E+10 | 0.681226E+09 | 22063.28 | 0.47 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 4313.04 | 0.00 | 0.00 | 24177.04 | 0.00 | 0.47 |
Maximum of Months | 0.130141E+09 | 0.496323E+09 | 298738.25 | 1602305.65 | 17487593.54 | 0.587940E+09 | 0.137723E+09 | 6308.15 | 0.47 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.552081E+09 | 0.00 | 0.00 | 12409182.75 | 0.00 | 0.167389E+10 | 0.207922E+10 | 0.00 | 0.54 |
February | 0.389811E+09 | 0.00 | 0.00 | 12681291.15 | 0.00 | 0.114497E+10 | 0.182280E+10 | 0.00 | 0.54 |
March | 0.384853E+09 | 3623486.55 | 0.00 | 12808593.14 | 54712.92 | 0.908937E+09 | 0.180943E+10 | 0.00 | 0.54 |
April | 0.163067E+09 | 0.196466E+09 | 59076.22 | 10989127.11 | 7200873.62 | 0.194355E+09 | 0.109798E+10 | 3911.88 | 0.54 |
May | 42578244.49 | 0.668697E+09 | 223797.74 | 8161473.08 | 35154363.19 | 2891381.28 | 0.526837E+09 | 34907.62 | 0.54 |
June | 3005512.84 | 0.144950E+10 | 643903.86 | 2299123.98 | 54925106.77 | 34258.12 | 87453540.04 | 59641.21 | 0.54 |
July | 0.00 | 0.315472E+10 | 2272082.26 | 26791.67 | 0.146246E+09 | 0.00 | 156263.97 | 67629.10 | 0.54 |
August | 4025846.62 | 0.191445E+10 | 1285242.24 | 1508406.04 | 79716224.37 | 78209.08 | 42709482.28 | 63632.02 | 0.54 |
September | 22609586.27 | 0.135241E+10 | 799390.71 | 6303523.11 | 45950318.27 | 261546.73 | 0.325268E+09 | 42588.27 | 0.54 |
October | 0.162516E+09 | 0.329173E+09 | 92275.45 | 17485635.93 | 8658375.25 | 5000801.94 | 0.133955E+10 | 3268.87 | 0.54 |
November | 0.384367E+09 | 2008715.67 | 0.00 | 18415273.99 | 0.00 | 0.961762E+09 | 0.200646E+10 | 0.00 | 0.53 |
December | 0.610523E+09 | 0.00 | 0.00 | 11180334.40 | 0.00 | 0.203605E+10 | 0.200425E+10 | 0.00 | 0.53 |
Annual Sum or Average | 0.271944E+10 | 0.907105E+10 | 5375768.47 | 0.114269E+09 | 0.377906E+09 | 0.692823E+10 | 0.131421E+11 | 275578.98 | 0.54 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 26791.67 | 0.00 | 0.00 | 156263.97 | 0.00 | 0.53 |
Maximum of Months | 0.610523E+09 | 0.315472E+10 | 2272082.26 | 18415273.99 | 0.146246E+09 | 0.203605E+10 | 0.207922E+10 | 67629.10 | 0.54 |
Report: MechanicalVentilationLoadsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.382661E+11 | 0.00 | 0.00 | 5642412.84 | 0.00 | 0.00 | 0.268544E+11 | 0.00 | 9.43 |
February | 0.282856E+11 | 0.00 | 0.00 | 6361877.81 | 939429.29 | 0.00 | 0.248258E+11 | 0.00 | 9.43 |
March | 0.241267E+11 | 4300223.20 | 0.00 | 9530805.60 | 40945969.52 | 0.00 | 0.289374E+11 | 0.00 | 9.45 |
April | 0.945879E+10 | 0.477316E+09 | 0.00 | 14475801.06 | 0.131983E+10 | 0.00 | 0.201086E+11 | 0.00 | 9.45 |
May | 0.217058E+10 | 0.204437E+10 | 0.00 | 19091886.75 | 0.310488E+10 | 0.00 | 0.123471E+11 | 0.00 | 9.49 |
June | 0.236768E+09 | 0.572026E+10 | 0.00 | 16138106.19 | 0.394916E+10 | 0.00 | 0.417400E+10 | 0.00 | 9.50 |
July | 9561112.55 | 0.192540E+11 | 0.00 | 2785666.61 | 0.919661E+10 | 0.00 | 0.269090E+09 | 0.00 | 9.52 |
August | 0.191136E+09 | 0.771821E+10 | 0.00 | 9676038.11 | 0.587286E+10 | 0.00 | 0.266967E+10 | 0.00 | 9.50 |
September | 0.175605E+10 | 0.629365E+10 | 0.00 | 9960346.48 | 0.547623E+10 | 0.00 | 0.809884E+10 | 0.00 | 9.53 |
October | 0.117667E+11 | 0.777677E+09 | 0.00 | 12330482.81 | 0.138002E+10 | 0.00 | 0.229069E+11 | 0.00 | 9.48 |
November | 0.291744E+11 | 0.00 | 0.00 | 7392373.02 | 20548854.61 | 0.00 | 0.270545E+11 | 0.00 | 9.41 |
December | 0.409080E+11 | 0.00 | 0.00 | 4541406.01 | 0.00 | 0.00 | 0.247211E+11 | 0.00 | 9.40 |
Annual Sum or Average | 0.186350E+12 | 0.422898E+11 | 0.00 | 0.117927E+09 | 0.303620E+11 | 0.00 | 0.202967E+12 | 0.00 | 9.47 |
Minimum of Months | 9561112.55 | 0.00 | 0.00 | 2785666.61 | 0.00 | 0.00 | 0.269090E+09 | 0.00 | 9.40 |
Maximum of Months | 0.409080E+11 | 0.192540E+11 | 0.00 | 19091886.75 | 0.919661E+10 | 0.00 | 0.289374E+11 | 0.00 | 9.53 |
Report: MechanicalVentilationLoadsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.380289E+11 | 0.00 | 0.00 | 7536976.33 | 0.00 | 0.00 | 0.302406E+11 | 0.00 | 9.89 |
February | 0.271802E+11 | 0.00 | 0.00 | 8421470.90 | 984879.31 | 0.00 | 0.284990E+11 | 0.00 | 9.89 |
March | 0.215402E+11 | 4832978.27 | 0.00 | 12539288.94 | 42602245.57 | 0.00 | 0.340886E+11 | 0.00 | 9.91 |
April | 0.789076E+10 | 0.788989E+09 | 0.00 | 17997670.63 | 0.109510E+10 | 0.00 | 0.231043E+11 | 0.00 | 9.91 |
May | 0.177563E+10 | 0.303451E+10 | 0.00 | 22819760.56 | 0.236387E+10 | 0.00 | 0.134416E+11 | 0.00 | 9.96 |
June | 0.189281E+09 | 0.782403E+10 | 0.00 | 18616122.62 | 0.231320E+10 | 0.00 | 0.443318E+10 | 0.00 | 9.96 |
July | 8934307.43 | 0.230734E+11 | 0.00 | 3170537.96 | 0.675363E+10 | 0.00 | 0.282948E+09 | 0.00 | 9.98 |
August | 0.149271E+09 | 0.978196E+10 | 0.00 | 11276319.57 | 0.446665E+10 | 0.00 | 0.284881E+10 | 0.00 | 9.97 |
September | 0.147074E+10 | 0.781628E+10 | 0.00 | 11913652.71 | 0.452304E+10 | 0.00 | 0.885946E+10 | 0.00 | 9.99 |
October | 0.102028E+11 | 0.925725E+09 | 0.00 | 15553528.25 | 0.133636E+10 | 0.00 | 0.261457E+11 | 0.00 | 9.94 |
November | 0.280126E+11 | 0.00 | 0.00 | 9666461.12 | 21543017.41 | 0.00 | 0.309347E+11 | 0.00 | 9.86 |
December | 0.403997E+11 | 0.00 | 0.00 | 6285361.29 | 0.00 | 0.00 | 0.284030E+11 | 0.00 | 9.86 |
Annual Sum or Average | 0.176849E+12 | 0.532498E+11 | 0.00 | 0.145797E+09 | 0.229170E+11 | 0.00 | 0.231282E+12 | 0.00 | 9.93 |
Minimum of Months | 8934307.43 | 0.00 | 0.00 | 3170537.96 | 0.00 | 0.00 | 0.282948E+09 | 0.00 | 9.86 |
Maximum of Months | 0.403997E+11 | 0.230734E+11 | 0.00 | 22819760.56 | 0.675363E+10 | 0.00 | 0.340886E+11 | 0.00 | 9.99 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 94977107.03 | 0.00 | 0.00 | 0.649206E+11 | 0.00 | 30.39 |
February | 0.00 | 937470.74 | 0.00 | 88863366.71 | 0.00 | 0.00 | 0.529449E+11 | 0.00 | 30.40 |
March | 0.00 | 45186808.59 | 0.00 | 0.100995E+09 | 0.00 | 0.00 | 0.528890E+11 | 0.00 | 30.47 |
April | 0.00 | 0.179847E+10 | 0.00 | 76373912.52 | 0.00 | 0.00 | 0.294565E+11 | 0.00 | 30.47 |
May | 0.00 | 0.515480E+10 | 0.00 | 53364917.94 | 0.00 | 0.00 | 0.144574E+11 | 0.00 | 30.62 |
June | 0.00 | 0.968284E+10 | 0.00 | 31077791.00 | 0.00 | 0.00 | 0.438727E+10 | 0.00 | 30.65 |
July | 0.00 | 0.284561E+11 | 0.00 | 3732646.90 | 0.00 | 0.00 | 0.277135E+09 | 0.00 | 30.69 |
August | 0.00 | 0.135986E+11 | 0.00 | 19372751.48 | 0.00 | 0.00 | 0.284549E+10 | 0.00 | 30.65 |
September | 0.00 | 0.117722E+11 | 0.00 | 33500898.87 | 0.00 | 0.00 | 0.981368E+10 | 0.00 | 30.73 |
October | 0.00 | 0.215877E+10 | 0.00 | 85659495.91 | 0.00 | 0.00 | 0.345432E+11 | 0.00 | 30.57 |
November | 0.00 | 20525026.38 | 0.00 | 98406143.22 | 0.00 | 0.00 | 0.560503E+11 | 0.00 | 30.32 |
December | 0.00 | 0.00 | 0.00 | 93431722.54 | 0.00 | 0.00 | 0.654263E+11 | 0.00 | 30.29 |
Annual Sum or Average | 0.00 | 0.726884E+11 | 0.00 | 0.779756E+09 | 0.00 | 0.00 | 0.388012E+12 | 0.00 | 30.52 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 3732646.90 | 0.00 | 0.00 | 0.277135E+09 | 0.00 | 30.29 |
Maximum of Months | 0.00 | 0.284561E+11 | 0.00 | 0.100995E+09 | 0.00 | 0.00 | 0.654263E+11 | 0.00 | 30.73 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.154018E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.542172E+10 | 0.00 | 0.00 | 2.42 |
February | 0.140599E+11 | 0.00 | 0.00 | 0.00 | 300374.18 | 0.292402E+10 | 0.00 | 0.00 | 2.42 |
March | 0.149973E+11 | 0.00 | 0.00 | 0.00 | 14467068.36 | 0.197248E+10 | 0.00 | 0.00 | 2.43 |
April | 0.938079E+10 | 0.00 | 0.00 | 0.00 | 0.574622E+09 | 77737743.16 | 0.00 | 0.00 | 2.42 |
May | 0.464801E+10 | 0.00 | 0.00 | 0.00 | 0.164643E+10 | 0.00 | 0.00 | 0.00 | 2.44 |
June | 0.141546E+10 | 0.00 | 0.00 | 0.00 | 0.309171E+10 | 0.00 | 0.00 | 0.00 | 2.44 |
July | 89986877.73 | 0.00 | 0.00 | 0.00 | 0.909683E+10 | 0.00 | 0.00 | 0.00 | 2.44 |
August | 0.917811E+09 | 0.00 | 0.00 | 0.00 | 0.434562E+10 | 0.00 | 0.00 | 0.00 | 2.44 |
September | 0.315420E+10 | 0.00 | 0.00 | 0.00 | 0.376332E+10 | 0.00 | 0.00 | 0.00 | 2.44 |
October | 0.110905E+11 | 0.00 | 0.00 | 0.00 | 0.689903E+09 | 0.00 | 0.00 | 0.00 | 2.43 |
November | 0.151321E+11 | 0.00 | 0.00 | 0.00 | 6570313.79 | 0.284896E+10 | 0.00 | 0.00 | 2.42 |
December | 0.135154E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.747035E+10 | 0.00 | 0.00 | 2.41 |
Annual Sum or Average | 0.103803E+12 | 0.00 | 0.00 | 0.00 | 0.232298E+11 | 0.207153E+11 | 0.00 | 0.00 | 2.43 |
Minimum of Months | 89986877.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.41 |
Maximum of Months | 0.154018E+11 | 0.00 | 0.00 | 0.00 | 0.909683E+10 | 0.747035E+10 | 0.00 | 0.00 | 2.44 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:58:10
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.189099E+12 | 0.183042E+11 | 0.797357E+11 | 0.109797E+13 | 0.149805E+12 |
February | 0.196158E+12 | 0.142762E+11 | 0.622894E+11 | 0.846446E+12 | 0.232359E+12 |
March | 0.315088E+12 | 0.130853E+11 | 0.588030E+11 | 0.767540E+12 | 0.357047E+12 |
April | 0.325824E+12 | 0.520145E+10 | 0.300491E+11 | 0.286220E+12 | 0.771129E+12 |
May | 0.356766E+12 | 96615653.85 | 0.112203E+11 | -0.200461E+11 | 0.116536E+13 |
June | 0.338943E+12 | -0.422232E+10 | -0.633785E+10 | -0.281023E+12 | 0.144865E+13 |
July | 0.327833E+12 | -0.110673E+11 | -0.292418E+11 | -0.696658E+12 | 0.182212E+13 |
August | 0.297900E+12 | -0.574660E+10 | -0.816995E+10 | -0.360902E+12 | 0.153401E+13 |
September | 0.255024E+12 | -0.271310E+10 | 0.232373E+10 | -0.174417E+12 | 0.131313E+13 |
October | 0.239520E+12 | 0.539958E+10 | 0.327787E+11 | 0.317544E+12 | 0.763479E+12 |
November | 0.185123E+12 | 0.142014E+11 | 0.636573E+11 | 0.842253E+12 | 0.285331E+12 |
December | 0.153192E+12 | 0.201368E+11 | 0.856823E+11 | 0.120364E+13 | 0.133499E+12 |
Annual Sum or Average | 0.318047E+13 | 0.669523E+11 | 0.382790E+12 | 0.382857E+13 | 0.997591E+13 |
Minimum of Months | 0.153192E+12 | -0.110673E+11 | -0.292418E+11 | -0.696658E+12 | 0.133499E+12 |
Maximum of Months | 0.356766E+12 | 0.201368E+11 | 0.856823E+11 | 0.120364E+13 | 0.182212E+13 |