Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:58
Tabular Output Report in Format: HTML
Building: HotelLarge
Environment: RUNPERIOD 1 ** William R Fairchild WA USA TMY3 WMO#=727885
Simulation Timestamp: 2023-10-16 08:58:31
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:58:31
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 13654.84 | 1203.57 | 1203.57 |
Net Site Energy | 13654.84 | 1203.57 | 1203.57 |
Total Source Energy | 29174.92 | 2571.55 | 2571.55 |
Net Source Energy | 29174.92 | 2571.55 | 2571.55 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 11345.29 |
Net Conditioned Building Area | 11345.29 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 1634.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 474.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1174.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 261.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1751.30 | 1788.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 679.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1809.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 132.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 451.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 90.78 | 3330.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Refrigeration | 74.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 6900.18 | 6754.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 1634.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 474.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 1174.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 261.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 959.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 762.04 | 1198.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 16.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 13.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 590.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 32.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 616.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 30.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 1809.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 132.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 451.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 90.78 | 3330.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5742.51 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4114.69 | |
Refrigeration | General | 18.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 22.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 33.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 1634.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 474.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 1174.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 261.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 1751.30 | 1788.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 679.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 1809.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 132.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 451.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 90.78 | 3330.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857.19 |
Refrigeration | Unassigned | 74.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 126.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 221.00 | 437.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Other | 260.63 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 608.20 | 595.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 126.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 221.00 | 437.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Other | 260.63 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 608.20 | 595.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 6900.176 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 6900.176 | 100.00 |
Total On-Site and Utility Electric Sources | 6900.176 | 100.00 |
Total Electricity End Uses | 6900.176 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | 0.00 |
Air to Air Heat Recovery for Cooling | 15.73 | 0.29 |
Air to Air Heat Recovery for Heating | 5452.10 | 99.71 |
High-Temperature Geothermal* | 0.00 | 0.00 |
Solar Water Thermal | 0.00 | 0.00 |
Solar Air Thermal | 0.00 | 0.00 |
Total On-Site Thermal Sources | 5467.84 | 100.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 9857.19 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 9857.19 | 100.00 |
Total Water End Uses | 9857.19 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 24.50 |
Time Setpoint Not Met During Occupied Cooling | 5.67 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 6724.67 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2012
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5C
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_PORTANGELES
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneHeatingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneElectricSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |PeakSpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ComfortReportSimple55Monthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |OccupantComfortDataSummaryMonthly
| BASEMENT PEOPLE | RETAIL_1_FLR_1 PEOPLE | RETAIL_2_FLR_1 PEOPLE | LAUNDRY_FLR_1 PEOPLE | CAFE_FLR_1 PEOPLE | LOBBY_FLR_1 PEOPLE | ROOM_1_FLR_3 PEOPLE | ROOM_2_FLR_3 PEOPLE | ROOM_3_MULT19_FLR_3 PEOPLE | ROOM_4_MULT19_FLR_3 PEOPLE | ROOM_5_FLR_3 PEOPLE | ROOM_6_FLR_3 PEOPLE | ROOM_1_FLR_6 PEOPLE | ROOM_2_FLR_6 PEOPLE | ROOM_3_MULT9_FLR_6 PEOPLE | BANQUET_FLR_6 PEOPLE | DINING_FLR_6 PEOPLE | KITCHEN_FLR_6 PEOPLE | STORAGE_FLR_1 PEOPLE | CORRIDOR_FLR_3 PEOPLE | CORRIDOR_FLR_6 PEOPLE | MECH_FLR_1 PEOPLE |ChillerReportMonthly
| COOLSYS1 CHILLER1 |BoilerReportMonthly
| HEATSYS1 BOILER |DXReportMonthly
| VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |WindowReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowEnergyReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWH BOOSTER E WATER HEATER | SWH LAUNDRY G WATER HEATER | SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| VAV WITH REHEAT HEATING COIL | BASEMENT VAV BOX REHEAT COIL | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | MECH_FLR_1 VAV BOX REHEAT COIL | STORAGE_FLR_1 VAV BOX REHEAT COIL | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | CAFE_FLR_1 VAV BOX REHEAT COIL | LOBBY_FLR_1 VAV BOX REHEAT COIL | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | BANQUET_FLR_6 VAV BOX REHEAT COIL | DINING_FLR_6 VAV BOX REHEAT COIL | KITCHEN_FLR_6 VAV BOX REHEAT COIL | FLR_3_DOAS HEATING COIL | ROOM_1_FLR_3 FAN COIL HEATING COIL | ROOM_2_FLR_3 FAN COIL HEATING COIL | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | ROOM_5_FLR_3 FAN COIL HEATING COIL | ROOM_6_FLR_3 FAN COIL HEATING COIL | ROOM_1_FLR_6 FAN COIL HEATING COIL | ROOM_2_FLR_6 FAN COIL HEATING COIL | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | VAV WITH REHEAT COOLING COIL | FLR_3_DOAS COOLING COIL | ROOM_1_FLR_3 FAN COIL COOLING COIL | ROOM_2_FLR_3 FAN COIL COOLING COIL | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | ROOM_5_FLR_3 FAN COIL COOLING COIL | ROOM_6_FLR_3 FAN COIL COOLING COIL | ROOM_1_FLR_6 FAN COIL COOLING COIL | ROOM_2_FLR_6 FAN COIL COOLING COIL | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1 | SWHSYS1 |FanReportMonthly
| FLR_3_DOAS FAN | VAV WITH REHEAT FAN | LAUNDRY_FLR_1 EXHAUST FAN | LOBBY_FLR_1 EXHAUST FAN | BANQUET_FLR_6 EXHAUST FAN | DINING_FLR_6 EXHAUST FAN | KITCHEN_FLR_6 EXHAUST FAN | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 PUMP | SWHSYS1 PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1 | SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV WITH REHEAT | FLR_3_DOAS |AirLoopSystemComponentLoadsMonthly
| VAV WITH REHEAT | FLR_3_DOAS |AirLoopSystemComponentEnergyUseMonthly
| VAV WITH REHEAT | FLR_3_DOAS |MechanicalVentilationLoadsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:58:31
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:58 |
RunPeriod | RUNPERIOD 1 |
Weather File | William R Fairchild WA USA TMY3 WMO#=727885 |
Latitude [deg] | 48.12 |
Longitude [deg] | -123.5 |
Elevation [m] | 91.00 |
Time Zone | -8.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1213.79 | 432.95 | 85.85 | 609.15 | 85.85 |
Gross Window-Wall Ratio [%] | 26.62 | 23.11 | 21.12 | 32.52 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.15 | 26.05 | 24.48 | 36.65 | 24.48 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1213.79 | 432.95 | 85.85 | 609.15 | 85.85 |
Gross Window-Wall Ratio [%] | 26.62 | 23.11 | 21.12 | 32.52 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.15 | 26.05 | 24.48 | 36.65 | 24.48 |
Total | |
Gross Roof Area [m2] | 1978.84 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 1978.83 | Yes | Yes | 4826.41 | 1.00 | 0.00 | 533.77 | 0.00 | 0.00 | 8.7495 | 18.58 | 5.3800 |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 265.76 | 1.00 | 68.84 | 0.00 | 23.26 | 23.26 | 13.0124 | 6.19 | 10.7600 |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 307.76 | 1.00 | 26.57 | 0.00 | 0.00 | 0.00 | 13.0124 | 6.19 | 10.7600 |
MECH_FLR_1 | 164.24 | Yes | Yes | 650.80 | 1.00 | 62.80 | 0.00 | 0.00 | 0.00 | 10.0642 | 61.93 | 5.3800 |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 375.47 | 1.00 | 36.23 | 0.00 | 0.00 | 0.00 | 7.3195 | 46.45 | 2.6900 |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 309.22 | 1.00 | 85.75 | 0.00 | 0.00 | 0.00 | 5.4896 | 9.29 | 597.5300 |
CAFE_FLR_1 | 188.86 | Yes | Yes | 748.35 | 1.00 | 152.17 | 0.00 | 65.50 | 65.50 | 12.8090 | 1.33 | 5.3800 |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 5183.56 | 1.00 | 434.79 | 0.00 | 85.08 | 85.08 | 10.0642 | 3.10 | 8.0700 |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 10.0642 | 26.01 | 6.7500 |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 10.0642 | 26.01 | 6.7500 |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 74.75 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 10.0642 | 16.35 | 10.5200 |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 74.77 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 10.0642 | 16.35 | 10.5200 |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 10.0642 | 26.01 | 6.7500 |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 10.0642 | 26.01 | 6.7500 |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 1186.91 | 4.00 | 48.31 | 0.00 | 15.94 | 15.94 | 3.6597 | 18.58 | 0.0000 |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 118.94 | 1.00 | 39.95 | 0.00 | 13.18 | 13.18 | 10.0642 | 26.01 | 6.7500 |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 118.93 | 1.00 | 39.95 | 0.00 | 13.18 | 13.18 | 10.0642 | 26.01 | 6.7500 |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 74.77 | 9.00 | 20.44 | 0.00 | 6.74 | 6.74 | 10.0642 | 16.35 | 10.5200 |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.19 | 32.19 | 12.8090 | 1.33 | 67.8200 |
DINING_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.19 | 32.19 | 12.8090 | 1.33 | 67.8200 |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 314.87 | 1.00 | 87.33 | 0.00 | 26.37 | 26.37 | 10.9792 | 4.65 | 2936.4163 |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1256.16 | 1.00 | 85.47 | 0.00 | 28.20 | 28.20 | 3.6597 | 18.58 | 0.0000 |
Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1213.79 | 1213.79 | 8.9207 | 7.07 | 41.0885 | |||
Conditioned Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1213.79 | 1213.79 | 8.9207 | 7.07 | 41.0885 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 1978.83 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 8.7495 | 18.58 | 5.3800 | |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 1.00 | RETAIL_1_FLR_1 | GENERAL | RETAIL_1_FLR_1 | 13.0124 | 6.19 | 10.7600 | |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 1.00 | RETAIL_2_FLR_1 | GENERAL | RETAIL_2_FLR_1 | 13.0124 | 6.19 | 10.7600 | |
MECH_FLR_1 | 164.24 | Yes | Yes | 1.00 | MECH_FLR_1 | GENERAL | MECH_FLR_1 | 10.0642 | 61.93 | 5.3800 | |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 1.00 | STORAGE_FLR_1 | GENERAL | STORAGE_FLR_1 | 7.3195 | 46.45 | 2.6900 | |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 1.00 | LAUNDRY_FLR_1 | GENERAL | LAUNDRY_FLR_1 | 5.4896 | 9.29 | 597.5300 | |
CAFE_FLR_1 | 188.86 | Yes | Yes | 1.00 | CAFE_FLR_1 | GENERAL | CAFE_FLR_1 | 12.8090 | 1.33 | 5.3800 | |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 1.00 | LOBBY_FLR_1 | GENERAL | LOBBY_FLR_1 | 10.0642 | 3.10 | 8.0700 | |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_1_FLR_3 | GENERAL | ROOM_1_FLR_3 | 10.0642 | 26.01 | 6.7500 | |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_2_FLR_3 | GENERAL | ROOM_2_FLR_3 | 10.0642 | 26.01 | 6.7500 | |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 76.00 | ROOM_3_MULT19_FLR_3 | GENERAL | ROOM_3_MULT19_FLR_3 | 10.0642 | 16.35 | 10.5200 | |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 76.00 | ROOM_4_MULT19_FLR_3 | GENERAL | ROOM_4_MULT19_FLR_3 | 10.0642 | 16.35 | 10.5200 | |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_5_FLR_3 | GENERAL | ROOM_5_FLR_3 | 10.0642 | 26.01 | 6.7500 | |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 4.00 | ROOM_6_FLR_3 | GENERAL | ROOM_6_FLR_3 | 10.0642 | 26.01 | 6.7500 | |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 4.00 | CORRIDOR_FLR_3 | GENERAL | CORRIDOR_FLR_3 | 3.6597 | 18.58 | 0.0000 | |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 1.00 | ROOM_1_FLR_6 | GENERAL | ROOM_1_FLR_6 | 10.0642 | 26.01 | 6.7500 | |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 1.00 | ROOM_2_FLR_6 | GENERAL | ROOM_2_FLR_6 | 10.0642 | 26.01 | 6.7500 | |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 9.00 | ROOM_3_MULT9_FLR_6 | GENERAL | ROOM_3_MULT9_FLR_6 | 10.0642 | 16.35 | 10.5200 | |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1.00 | BANQUET_FLR_6 | GENERAL | BANQUET_FLR_6 | 12.8090 | 1.33 | 67.8200 | |
DINING_FLR_6 | 331.66 | Yes | Yes | 1.00 | DINING_FLR_6 | GENERAL | DINING_FLR_6 | 12.8090 | 1.33 | 67.8200 | |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 1.00 | KITCHEN_FLR_6 | GENERAL | KITCHEN_FLR_6 | 10.9792 | 4.65 | 2936.4163 | |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1.00 | CORRIDOR_FLR_6 | GENERAL | CORRIDOR_FLR_6 | 3.6597 | 18.58 | 0.0000 | |
Total | 11345.29 | 8.9207 | 3.54 | 41.0885 | |||||||
Conditioned Total | 11345.29 | 8.9207 | 3.54 | 41.0885 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 11345.29 | 11345.29 | 0.00 | 0.00 | 4.6908 | 8.82 | 37.2165 |
Total | 11345.29 | 11345.29 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:58:31
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 22-JUL-18:10 | 11-JAN-17:49 | - | - | - | - | - | - | - | - | - | - | 02-JAN-21:10 |
Heating | 0.00 | 166194.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 167714.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 82807.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 76644.19 | 89612.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 32608.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 75740.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 8954.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 17755.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 4327.00 | 267293.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 2886.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 469437.58 | 523100.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 166194.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 167714.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 82807.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 46461.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 29240.64 | 74976.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 515.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 425.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 14636.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 1482.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 30153.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 972.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 75740.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 8954.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 17755.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Heater | 4327.00 | 267293.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 618.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 1178.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 1089.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:58:31
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 1772.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1501.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 3718.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 828.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 5546.36 | 1939.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 2152.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 5731.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 420.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 1430.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 287.50 | 3610.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 235.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 21852.86 | 7322.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 156.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 132.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 327.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 73.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 488.87 | 170.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 189.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 505.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 37.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 126.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 25.34 | 318.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 20.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1926.16 | 645.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 156.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 132.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 327.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 73.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 488.87 | 170.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 189.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 505.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 37.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 126.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 25.34 | 318.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 20.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1926.16 | 645.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:58:31
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
BASEMENT VAV BOX COMPONENT | 2.48 | 0.608098 | 0.995000 | 2.47 | 1.00 | 0.500000 | 0.000627 | 0.000125 | 2.47 | 16.70 | 0.008000 |
RETAIL_1_FLR_1 VAV BOX COMPONENT | 0.474926 | 0.107613 | 0.995000 | 0.472551 | 0.995000 | 0.500000 | 0.003540 | 0.000042 | 0.472551 | 16.70 | 0.008000 |
RETAIL_2_FLR_1 VAV BOX COMPONENT | 0.237483 | 0.249213 | 0.995000 | 0.236295 | 0.995000 | 0.500000 | 0.001529 | 0.000017 | 0.236295 | 16.70 | 0.008000 |
MECH_FLR_1 VAV BOX COMPONENT | 0.222845 | 0.561617 | 0.995000 | 0.221730 | 1.00 | 0.500000 | 0.000678 | 0.000022 | 0.221730 | 16.70 | 0.008000 |
STORAGE_FLR_1 VAV BOX COMPONENT | 0.109419 | 0.659911 | 0.995000 | 0.108872 | 1.00 | 0.500000 | 0.000577 | 0.000013 | 0.108872 | 16.70 | 0.008000 |
LAUNDRY_FLR_1 VAV BOX COMPONENT | 3.28 | 0.071893 | 0.995000 | 3.27 | 0.995000 | 0.500000 | 0.021030 | 0.000165 | 3.27 | 16.70 | 0.008000 |
CAFE_FLR_1 VAV BOX COMPONENT | 1.87 | 0.076875 | 0.995000 | 1.86 | 0.995000 | 0.500000 | 0.004956 | 0.000138 | 1.86 | 16.70 | 0.008000 |
LOBBY_FLR_1 VAV BOX COMPONENT | 5.17 | 0.192988 | 0.995000 | 5.14 | 0.995000 | 0.500000 | 0.001974 | 0.000356 | 5.14 | 16.70 | 0.008000 |
CORRIDOR_FLR_3 VAV BOX COMPONENT | 1.25 | 0.948663 | 0.995000 | 1.24 | 1.00 | 0.500000 | 0.000402 | 0.000127 | 1.24 | 16.70 | 0.008000 |
BANQUET_FLR_6 VAV BOX COMPONENT | 2.19 | 0.115267 | 0.995000 | 2.18 | 0.995000 | 0.500000 | 0.003305 | 0.000149 | 2.18 | 16.70 | 0.008000 |
DINING_FLR_6 VAV BOX COMPONENT | 2.30 | 0.109884 | 0.995000 | 2.29 | 0.995000 | 0.500000 | 0.003467 | 0.000155 | 2.29 | 16.70 | 0.008000 |
KITCHEN_FLR_6 VAV BOX COMPONENT | 2.32 | 0.815387 | 0.995000 | 2.30 | 0.995000 | 0.500000 | 0.011206 | 0.000113 | 2.30 | 16.70 | 0.008000 |
CORRIDOR_FLR_6 VAV BOX COMPONENT | 0.771151 | 0.407234 | 0.995000 | 0.767295 | 1.00 | 0.500000 | 0.000936 | 0.000088 | 0.767295 | 16.70 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
BASEMENT VAV BOX REHEAT COIL | 14327.12 | 0.000125 | 300.51 |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 4825.41 | 0.000042 | 105.89 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 1993.71 | 0.000017 | 42.95 |
MECH_FLR_1 VAV BOX REHEAT COIL | 2551.24 | 0.000022 | 56.76 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | 1434.23 | 0.000013 | 32.49 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 18849.13 | 0.000165 | 395.21 |
CAFE_FLR_1 VAV BOX REHEAT COIL | 15718.65 | 0.000138 | 338.62 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | 40686.71 | 0.000356 | 871.81 |
ROOM_1_FLR_3 FAN COIL HEATING COIL | 5188.67 | 0.000045 | 148.28 |
ROOM_2_FLR_3 FAN COIL HEATING COIL | 5194.32 | 0.000045 | 148.44 |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | 29731.12 | 0.000260 | 849.63 |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | 29853.37 | 0.000261 | 853.12 |
ROOM_5_FLR_3 FAN COIL HEATING COIL | 5176.67 | 0.000045 | 147.94 |
ROOM_6_FLR_3 FAN COIL HEATING COIL | 5182.33 | 0.000045 | 148.10 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 14547.38 | 0.000127 | 324.28 |
ROOM_1_FLR_6 FAN COIL HEATING COIL | 1653.18 | 0.000014 | 47.24 |
ROOM_2_FLR_6 FAN COIL HEATING COIL | 1654.61 | 0.000014 | 47.28 |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | 7974.44 | 0.000070 | 227.87 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | 17055.32 | 0.000149 | 365.08 |
DINING_FLR_6 VAV BOX REHEAT COIL | 17714.73 | 0.000155 | 378.90 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | 12886.51 | 0.000113 | 269.72 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 10065.78 | 0.000088 | 227.90 |
VAV WITH REHEAT HEATING COIL | 170153.31 | 0.001489 | 2903.30 |
FLR_3_DOAS HEATING COIL | 15471.26 | 0.000135 | 263.98 |
User-Specified Maximum Flow Rate [m3/s] | |
LOBBY_FLR_1 EXHAUST FAN | 0.000000 |
BANQUET_FLR_6 EXHAUST FAN | 0.000000 |
DINING_FLR_6 EXHAUST FAN | 0.000000 |
Design Size Maximum Air Flow Rate [m3/s] | |
ROOM_1_FLR_3 DIRECT AIR | 0.061735 |
ROOM_2_FLR_3 DIRECT AIR | 0.061728 |
ROOM_3_MULT19_FLR_3 DIRECT AIR | 0.837072 |
ROOM_4_MULT19_FLR_3 DIRECT AIR | 0.837300 |
ROOM_5_FLR_3 DIRECT AIR | 0.061735 |
ROOM_6_FLR_3 DIRECT AIR | 0.061728 |
ROOM_1_FLR_6 DIRECT AIR | 0.015434 |
ROOM_2_FLR_6 DIRECT AIR | 0.015432 |
ROOM_3_MULT9_FLR_6 DIRECT AIR | 0.099154 |
Design Size Maximum Supply Air Flow Rate [m3/s] | Design Size Maximum Hot Water Flow [m3/s] | Design Size Maximum Cold Water Flow [m3/s] | |
ROOM_1_FLR_3 FAN COIL | 1.24 | 0.000045 | 0.000532 |
ROOM_2_FLR_3 FAN COIL | 1.11 | 0.000045 | 0.000477 |
ROOM_3_MULT19_FLR_3 FAN COIL | 9.05 | 0.000260 | 0.003814 |
ROOM_4_MULT19_FLR_3 FAN COIL | 5.75 | 0.000261 | 0.002574 |
ROOM_5_FLR_3 FAN COIL | 1.13 | 0.000045 | 0.000484 |
ROOM_6_FLR_3 FAN COIL | 1.02 | 0.000045 | 0.000437 |
ROOM_1_FLR_6 FAN COIL | 0.333458 | 0.000014 | 0.000142 |
ROOM_2_FLR_6 FAN COIL | 0.296105 | 0.000014 | 0.000127 |
ROOM_3_MULT9_FLR_6 FAN COIL | 1.85 | 0.000070 | 0.000796 |
Design Size Maximum Flow Rate [m3/s] | |
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | 1.24 |
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | 1.11 |
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | 9.05 |
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | 5.75 |
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | 1.13 |
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | 1.02 |
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | 0.333458 |
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | 0.296105 |
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | 1.85 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Temperature [C] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | Design Size Design Coil Load [W] | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | 22.50 | 6.70 | 0.008557 | 12.80 | 0.008500 | 0.000532 | 1.24 | |
ROOM_2_FLR_3 FAN COIL COOLING COIL | 22.50 | 6.70 | 0.008564 | 12.80 | 0.008500 | 0.000477 | 1.11 | |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | 22.50 | 6.70 | 0.008499 | 12.80 | 0.008499 | 0.003814 | 9.05 | |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | 22.50 | 6.70 | 0.008741 | 12.80 | 0.008500 | 0.002574 | 5.75 | |
ROOM_5_FLR_3 FAN COIL COOLING COIL | 22.50 | 6.70 | 0.008563 | 12.80 | 0.008500 | 0.000484 | 1.13 | |
ROOM_6_FLR_3 FAN COIL COOLING COIL | 22.50 | 6.70 | 0.008570 | 12.80 | 0.008500 | 0.000437 | 1.02 | |
ROOM_1_FLR_6 FAN COIL COOLING COIL | 22.50 | 6.70 | 0.008554 | 12.80 | 0.008500 | 0.000142 | 0.333458 | |
ROOM_2_FLR_6 FAN COIL COOLING COIL | 22.50 | 6.70 | 0.008560 | 12.80 | 0.008500 | 0.000127 | 0.296105 | |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | 22.50 | 6.70 | 0.008589 | 12.80 | 0.008500 | 0.000796 | 1.85 | |
VAV WITH REHEAT COOLING COIL | 26.40 | 6.70 | 0.008407 | 10.96 | 0.008407 | 0.015129 | 22.56 | 423570.84 |
FLR_3_DOAS COOLING COIL | 26.40 | 6.70 | 0.008407 | 11.92 | 0.008407 | 0.001290 | 2.05 | 36112.10 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV WITH REHEAT | 22.56 | 22.56 | 22.67 | 22.56 | 22.56 | 22.56 | 0.300000 | 1.00 | 22.56 |
FLR_3_DOAS | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 0.300000 | 1.00 | 2.05 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV WITH REHEAT_OA_CONTROLLER | 22.56 | 22.56 |
FLR_3_DOAS_OA_CONTROLLER | 2.05 | 2.05 |
Design Size Nominal Supply Air Flow Rate [m3/s] | |
VAV WITH REHEAT OA HEAT RECOVERY | 22.56 |
FLR_3_DOAS OA HEAT RECOVERY | 2.05 |
Design Size Maximum Flow Rate [m3/s] | |
VAV WITH REHEAT FAN | 22.56 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV WITH REHEAT_COOLC_CONTROLLER | 0.015129 | 0.000031 |
VAV WITH REHEAT_HEATC_CONTROLLER | 0.001489 | |
FLR_3_DOAS_COOLC_CONTROLLER | 0.001290 | 0.000369 |
FLR_3_DOAS_HEATC_CONTROLLER | 0.000135 |
User-Specified Maximum Flow Rate [m3/s] | |
FLR_3_DOAS FAN | 2.05 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.025802 | 5316.91 | |
HEATSYS1 PUMP | 0.003936 | 1185.30 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
HEATSYS1 | 0.003936 | 0.472299 |
COOLSYS1 | 0.025802 | 3.10 |
SWHSYS1 | 0.000375 | 0.045004 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 449889.21 | 449889.21 | 0.003936 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 PUMP | 0.025802 | 3681.07 |
SWHSYS1 PUMP | 0.000375 | 47.91 |
Design Size Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Fluid Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.025802 | 722396.70 | 723021.47 | 82.42 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000375 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:58:31
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesPossible Shadow Receivers | |
RETAIL_1_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
CAFE_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
LOBBY_FLR_1_CEILING_2 | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
Possible Shadow Receivers | |
RETAIL_1_FLR_1_WALL_SOUTH | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | |
RETAIL_2_FLR_1_WALL_WEST | RETAIL_2_FLR_1_WALL_WEST_DOOR | |
STORAGE_FLR_1_WALL_NORTH | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | |
LAUNDRY_FLR_1_WALL_EAST | LAUNDRY_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_EAST | CAFE_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_SOUTH | CAFE_FLR_1_WALL_SOUTH_WINDOW | |
LOBBY_FLR_1_WALL_1_NORTH | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | |
LOBBY_FLR_1_WALL_1_SOUTH | LOBBY_FLR_1_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_SOUTH | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_WEST | ROOM_1_FLR_3_WALL_WEST_WINDOW | |
ROOM_2_FLR_3_WALL_NORTH | ROOM_2_FLR_3_WALL_NORTH_WINDOW | |
ROOM_2_FLR_3_WALL_WEST | ROOM_2_FLR_3_WALL_WEST_WINDOW | |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_4_MULT19_FLR_3_WALL_NORTH | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | |
ROOM_5_FLR_3_WALL_EAST | ROOM_5_FLR_3_WALL_EAST_WINDOW | |
ROOM_5_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_6_FLR_3_WALL_NORTH | ROOM_6_FLR_3_WALL_NORTH_WINDOW | |
ROOM_6_FLR_3_WALL_EAST | ROOM_6_FLR_3_WALL_EAST_WINDOW | |
CORRIDOR_FLR_3_WALL_1_NORTH | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_NORTH | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_SOUTH | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_WEST | ROOM_1_FLR_6_WALL_WEST_WINDOW | |
ROOM_2_FLR_6_WALL_NORTH | ROOM_2_FLR_6_WALL_NORTH_WINDOW | |
ROOM_2_FLR_6_WALL_WEST | ROOM_2_FLR_6_WALL_WEST_WINDOW | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | |
BANQUET_FLR_6_WALL_NORTH | BANQUET_FLR_6_WALL_NORTH_WINDOW | |
DINING_FLR_6_WALL_NORTH | DINING_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_NORTH | KITCHEN_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_EAST | KITCHEN_FLR_6_WALL_EAST_WINDOW | |
KITCHEN_FLR_6_WALL_1_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_6_WALL_1_NORTH | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_NORTH | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:58:31
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:58:31
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 9.30 | 6.70 | 4.10 | 4.20 | 4.20 | 5.90 | 9.00 | 10.00 | 13.30 | 15.00 | 15.70 | 13.40 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | William R Fairchild WA USA TMY3 WMO#=727885 | 48.12 | -123.50 | -8.00 | 91.00 | 100237 | 1.1914 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 9.23 | 11.60 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | HotelLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | DOE-2 |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 22 | 235 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 41.45 | 11.51 | -1.22 | 1 | 1 | 1 | 0.00 | 86.56 | 0.00 | 22.86 | -2.44 | 0.00 | 2.44 | 4826.41 | TARP | DOE-2 | 1978.83 | 0.00 | 0.00 | 0.00 | 13 | 0 | 0 | Yes |
2 | RETAIL_1_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 2.90 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 265.76 | TARP | DOE-2 | 67.07 | 68.84 | 45.58 | 23.26 | 6 | 1 | 0 | Yes |
3 | RETAIL_2_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 9.14 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 5.79 | 12.50 | 0.00 | 3.96 | 3.96 | 307.76 | TARP | DOE-2 | 77.67 | 26.57 | 24.62 | 0.00 | 6 | 1 | 0 | Yes |
4 | MECH_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 61.87 | 17.68 | 1.98 | 1 | 1 | 1 | 53.95 | 69.80 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 650.80 | TARP | DOE-2 | 164.24 | 62.80 | 62.80 | 0.00 | 6 | 0 | 0 | Yes |
5 | STORAGE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 74.37 | 17.68 | 1.98 | 1 | 1 | 1 | 69.80 | 78.94 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 375.47 | TARP | DOE-2 | 94.76 | 36.23 | 28.80 | 0.00 | 6 | 1 | 0 | Yes |
6 | LAUNDRY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 14.33 | 1.98 | 1 | 1 | 1 | 81.99 | 86.56 | 5.79 | 22.86 | 0.00 | 3.96 | 3.96 | 309.22 | TARP | DOE-2 | 78.04 | 85.75 | 83.80 | 0.00 | 6 | 1 | 0 | Yes |
7 | CAFE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 70.26 | 2.90 | 1.98 | 1 | 1 | 1 | 53.95 | 86.56 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 748.35 | TARP | DOE-2 | 188.86 | 152.17 | 84.72 | 65.50 | 7 | 2 | 0 | Yes |
8 | LOBBY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 38.29 | 12.45 | 1.98 | 1 | 1 | 1 | 0.00 | 81.99 | 0.00 | 22.86 | 0.00 | 3.96 | 3.96 | 5183.56 | TARP | DOE-2 | 1308.19 | 434.79 | 345.80 | 85.08 | 18 | 3 | 0 | Yes |
9 | ROOM_1_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
10 | ROOM_2_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
11 | ROOM_3_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 8.53 | 9.14 | 8.53 | 1 | 76 | 1 | 6.71 | 10.36 | 5.79 | 12.50 | 7.01 | 10.06 | 3.05 | 74.75 | TARP | DOE-2 | 24.52 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
12 | ROOM_4_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 12.19 | 19.51 | 8.53 | 1 | 76 | 1 | 10.36 | 14.02 | 16.15 | 22.86 | 7.01 | 10.06 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
13 | ROOM_5_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 10.06 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
14 | ROOM_6_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 18.59 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
15 | CORRIDOR_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 43.28 | 14.33 | 8.53 | 1 | 4 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 7.01 | 10.06 | 3.05 | 1186.91 | TARP | DOE-2 | 389.40 | 48.31 | 32.37 | 15.94 | 20 | 4 | 0 | Yes |
16 | ROOM_1_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 16.15 | 19.20 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
17 | ROOM_2_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 16.15 | 19.20 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.18 | 6 | 2 | 0 | Yes |
18 | ROOM_3_MULT9_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 7.93 | 7.62 | 17.68 | 1 | 9 | 1 | 4.57 | 11.28 | 5.79 | 9.45 | 16.15 | 19.20 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 20.44 | 13.70 | 6.74 | 6 | 1 | 0 | Yes |
19 | BANQUET_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 26.37 | 17.68 | 17.68 | 1 | 1 | 1 | 10.36 | 42.37 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.36 | 32.19 | 6 | 1 | 0 | Yes |
20 | DINING_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 63.55 | 17.68 | 17.68 | 1 | 1 | 1 | 47.55 | 79.55 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.36 | 32.19 | 6 | 1 | 0 | Yes |
21 | KITCHEN_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 82.99 | 14.11 | 17.68 | 1 | 1 | 1 | 79.55 | 86.56 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 314.87 | TARP | DOE-2 | 103.30 | 87.33 | 60.96 | 26.37 | 8 | 3 | 0 | Yes |
22 | CORRIDOR_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 41.51 | 13.35 | 17.68 | 1 | 1 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 1256.16 | TARP | DOE-2 | 412.12 | 85.47 | 57.27 | 28.20 | 15 | 3 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 1978.83 | 106.5 | 18.581 | 5.382E-002 | 8.749 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 14.129 | No |
2 | RETAIL_1_FLR_1 | 67.07 | 10.8 | 6.194 | 0.161 | 13.012 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 23.772 | No |
3 | RETAIL_2_FLR_1 | 77.67 | 12.5 | 6.194 | 0.161 | 13.012 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 23.772 | No |
4 | MECH_FLR_1 | 164.24 | 2.7 | 61.932 | 1.615E-002 | 10.064 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 15.444 | No |
5 | STORAGE_FLR_1 | 94.76 | 2.0 | 46.451 | 2.153E-002 | 7.319 | 2.690 | 0.000 | 0.000 | 0.000 | 0.000 | 10.009 | No |
6 | LAUNDRY_FLR_1 | 78.04 | 8.4 | 9.290 | 0.108 | 5.490 | 61.680 | 535.850 | 0.000 | 0.000 | 0.000 | 603.020 | No |
7 | CAFE_FLR_1 | 188.86 | 142.3 | 1.327 | 0.753 | 12.809 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 18.189 | No |
8 | LOBBY_FLR_1 | 1308.19 | 422.4 | 3.097 | 0.323 | 10.064 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.134 | No |
9 | ROOM_1_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 10.064 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 16.814 | No |
10 | ROOM_2_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 10.064 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 16.814 | No |
11 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 16.349 | 6.116E-002 | 10.064 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 20.584 | No |
12 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 10.064 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 20.584 | No |
13 | ROOM_5_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 10.064 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 16.814 | No |
14 | ROOM_6_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 10.064 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 16.814 | No |
15 | CORRIDOR_FLR_3 | 389.40 | 21.0 | 18.581 | 5.382E-002 | 3.660 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 3.660 | No |
16 | ROOM_1_FLR_6 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 10.064 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 16.814 | No |
17 | ROOM_2_FLR_6 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 10.064 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 16.814 | No |
18 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 10.064 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 20.584 | No |
19 | BANQUET_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 12.809 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 80.629 | No |
20 | DINING_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 12.809 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 80.629 | No |
21 | KITCHEN_FLR_6 | 103.30 | 22.2 | 4.645 | 0.215 | 10.979 | 517.156 | 2419.260 | 0.000 | 0.000 | 0.000 | 2947.395 | No |
22 | CORRIDOR_FLR_6 | 412.12 | 22.2 | 18.581 | 5.382E-002 | 3.660 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 3.660 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | BASEMENT PEOPLE | BLDG_OCC_SCH | BASEMENT | 1978.83 | 106.5 | 106.5 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 106 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | RETAIL_1_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 10.8 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | RETAIL_2_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 12.5 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 13 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | LAUNDRY_FLR_1 PEOPLE | BLDG_OCC_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 8.4 | 0.108 | 9.290 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 8 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | CAFE_FLR_1 PEOPLE | BLDG_OCC_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 142.3 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 142 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | LOBBY_FLR_1 PEOPLE | BLDG_OCC_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 422.4 | 0.323 | 3.097 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 422 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | ROOM_1_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | ROOM_2_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | ROOM_3_MULT19_FLR_3 PEOPLE | ALWAYS_OFF | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 1.5 | 6.116E-002 | 16.349 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 0 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | ROOM_4_MULT19_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | ROOM_5_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | ROOM_6_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | ROOM_1_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | ROOM_2_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | ROOM_3_MULT9_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | BANQUET_FLR_6 PEOPLE | BLDG_OCC_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | DINING_FLR_6 PEOPLE | BLDG_OCC_SCH | DINING_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | KITCHEN_FLR_6 PEOPLE | BLDG_OCC_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 22.2 | 0.215 | 4.645 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | STORAGE_FLR_1 PEOPLE | BLDG_OCC_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 2.0 | 2.153E-002 | 46.451 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | CORRIDOR_FLR_3 PEOPLE | BLDG_OCC_SCH | CORRIDOR_FLR_3 | 389.40 | 21.0 | 21.0 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 21 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
21 | CORRIDOR_FLR_6 PEOPLE | BLDG_OCC_SCH | CORRIDOR_FLR_6 | 412.12 | 22.2 | 22.2 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
22 | MECH_FLR_1 PEOPLE | BLDG_OCC_SCH | MECH_FLR_1 | 164.24 | 2.7 | 2.7 | 1.615E-002 | 61.932 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 3 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_BASEMENT | BASEMENT | 1978.83 | 106.5 | 17313.725 | 8.749 | 162.572 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 17313.725 |
2 | RETAIL_1_FLR_1_LIGHTS | LTG_SCH_RETAIL | RETAIL_1_FLR_1 | 67.07 | 10.8 | 872.757 | 13.012 | 80.594 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 872.757 |
3 | RETAIL_2_FLR_1_LIGHTS | LTG_SCH_RETAIL | RETAIL_2_FLR_1 | 77.67 | 12.5 | 1010.656 | 13.012 | 80.595 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1010.656 |
4 | MECH_FLR_1_LIGHTS | LTG_SCH_MECHANIC | MECH_FLR_1 | 164.24 | 2.7 | 1652.984 | 10.064 | 623.297 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1652.984 |
5 | STORAGE_FLR_1_LIGHTS | LTG_SCH_STORAGE | STORAGE_FLR_1 | 94.76 | 2.0 | 693.586 | 7.319 | 339.993 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 693.586 |
6 | LAUNDRY_FLR_1_LIGHTS | LTG_SCH_LAUNDRY | LAUNDRY_FLR_1 | 78.04 | 8.4 | 428.405 | 5.490 | 51.001 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 428.405 |
7 | CAFE_FLR_1_LIGHTS | LTG_SCH_DINING | CAFE_FLR_1 | 188.86 | 142.3 | 2419.140 | 12.809 | 17.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2419.140 |
8 | LOBBY_FLR_1_LIGHTS | LTG_SCH_LOBBY | LOBBY_FLR_1 | 1308.19 | 422.4 | 13165.908 | 10.064 | 31.167 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 13165.908 |
9 | ROOM_1_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_1_FLR_3 | 39.02 | 1.5 | 392.727 | 10.064 | 261.818 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 392.727 |
10 | ROOM_2_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_2_FLR_3 | 39.02 | 1.5 | 392.681 | 10.064 | 261.787 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 392.681 |
11 | ROOM_3_MULT19_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 246.814 | 10.064 | 164.543 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 246.814 |
12 | ROOM_4_MULT19_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 246.881 | 10.064 | 164.588 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 246.881 |
13 | ROOM_5_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_5_FLR_3 | 39.02 | 1.5 | 392.727 | 10.064 | 261.818 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 392.727 |
14 | ROOM_6_FLR_3_LIGHTS | LTG_SCH_GUESTROOM | ROOM_6_FLR_3 | 39.02 | 1.5 | 392.681 | 10.064 | 261.787 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 392.681 |
15 | CORRIDOR_FLR_3_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_FLR_3 | 389.40 | 21.0 | 1425.114 | 3.660 | 68.002 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1425.114 |
16 | ROOM_1_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_1_FLR_6 | 39.02 | 1.5 | 392.727 | 10.064 | 261.818 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 392.727 |
17 | ROOM_2_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_2_FLR_6 | 39.02 | 1.5 | 392.681 | 10.064 | 261.787 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 392.681 |
18 | ROOM_3_MULT9_FLR_6_LIGHTS | LTG_SCH_GUESTROOM | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 246.881 | 10.064 | 164.588 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 246.881 |
19 | BANQUET_FLR_6_LIGHTS | LTG_SCH_DINING | BANQUET_FLR_6 | 331.66 | 249.9 | 4248.214 | 12.809 | 17.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 4248.214 |
20 | DINING_FLR_6_LIGHTS | LTG_SCH_DINING | DINING_FLR_6 | 331.66 | 249.9 | 4248.214 | 12.809 | 17.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 4248.214 |
21 | KITCHEN_FLR_6_LIGHTS | LTG_SCH_KITCHEN | KITCHEN_FLR_6 | 103.30 | 22.2 | 1134.198 | 10.979 | 51.003 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1134.198 |
22 | CORRIDOR_FLR_6_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_FLR_6 | 412.12 | 22.2 | 1508.264 | 3.660 | 68.001 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1508.264 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | BASEMENT_EQUIP_SCH | BASEMENT | 1978.83 | 106.5 | 10646.106 | 5.380 | 99.964 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10646.106 |
2 | RETAIL_1_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 721.688 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 721.688 |
3 | RETAIL_2_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 835.717 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 835.717 |
4 | MECH_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | MECH_FLR_1 | 164.24 | 2.7 | 883.628 | 5.380 | 333.193 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 883.628 |
5 | STORAGE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 254.902 | 2.690 | 124.952 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 254.902 |
6 | LAUNDRY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 4813.474 | 61.680 | 573.033 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 4813.474 |
7 | CAFE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 1016.077 | 5.380 | 7.140 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1016.077 |
8 | LOBBY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 10557.062 | 8.070 | 24.991 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10557.062 |
9 | ROOM_1_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_1_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
10 | ROOM_2_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_2_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
11 | ROOM_3_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 257.991 | 10.520 | 171.994 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 257.991 |
12 | ROOM_4_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
13 | ROOM_5_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_5_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
14 | ROOM_6_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_6_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
15 | ROOM_1_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_1_FLR_6 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
16 | ROOM_2_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_2_FLR_6 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
17 | ROOM_3_MULT9_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_BASE | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
18 | BANQUET_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
19 | DINING_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | DINING_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
20 | KITCHEN_FLR_6_MISCELEC_EQUIP | KITCHEN_ELEC_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 52482.799 | 508.040 | 2360.050 | 0.200 | 0.500 | 0.100 | 0.200 | Cooking | 0.000 | 15744.840 |
21 | KITCHEN_FLR_6_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 515.917 | 4.994 | 23.200 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 515.917 | 515.917 |
22 | KITCHEN_FLR_6_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 425.833 | 4.122 | 19.149 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 425.833 | 425.833 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LAUNDRY_FLR_1_MISCGAS_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 41817.449 | 535.850 | 4978.268 | 0.000 | 0.500 | 0.000 | 0.500 | Laundry | 0.000 | 41817.449 |
2 | KITCHEN_FLR_6_MISCGAS_EQUIP | KITCHEN_GAS_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 249920.353 | 2419.260 | 11238.437 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 74976.106 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | OVERHEAD DOOR_CON | 2 | 1 | 1 | 0.167 | 1.198 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
3 | INTERIORFURNISHINGS | 3 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 8 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 18 | 3 | 3 | 0.167 | 0.2284 | 0.900 | 0.900 | 0.770 | 0.700 | Rough |
6 | RES_ROOF | 19 | 3 | 3 | 0.167 | 0.2284 | 0.900 | 0.900 | 0.770 | 0.700 | Rough |
7 | NONRES_EXT_WALL_GRD | 21 | 3 | 9 | 0.167 | 0.7376 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | NONRES_EXT_WALL_MID | 22 | 3 | 9 | 0.167 | 1.016 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | NONRES_EXT_WALL_TOP | 23 | 3 | 9 | 0.167 | 1.081 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | RES_EXT_WALL_MID | 25 | 3 | 9 | 0.167 | 1.016 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | RES_EXT_WALL_TOP | 26 | 3 | 9 | 0.167 | 1.081 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | NONRES_FLOOR | 30 | 3 | 7 | 0.167 | 0.1963 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
13 | NONRES_FLOOR_CEILING | 33 | 3 | 7 | 0.167 | 0.1963 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
14 | BASEMENT_FLOOR | 36 | 2 | 7 | 0.333 | 2.705 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
15 | BASEMENT_WALL_NORTH_CFACTOR | 39 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | BASEMENT_WALL_EAST_CFACTOR | 40 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | BASEMENT_WALL_SOUTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
18 | BASEMENT_WALL_WEST_CFACTOR | 42 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8346 |
3 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
10 | RES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
11 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
12 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
13 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.188 |
14 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8173 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7574 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | RES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8173 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
25 | RES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7574 |
26 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
27 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.833 |
28 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
29 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
30 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
31 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
32 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.833 |
33 | M10 200MM CONCRETE BLOCK BASEMENT WALL | 0.2032 | 1.326 | 1842.000 | 912.000 | 0.1532 |
34 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
35 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
36 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
37 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
38 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
39 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
40 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
41 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
42 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
4 | 0 | 1.1981135 | 1.1981135 | 1.1981135 | |
5 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
6 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
7 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
8 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
9 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
10 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
11 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
12 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
13 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
14 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
15 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
16 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
17 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
18 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
19 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
20 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
21 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
22 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
23 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
24 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
25 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
26 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
27 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
28 | 9 | -0.36178815E-14 | 0.27139057E-16 | -0.15868385E-09 | 0.72384540E-16 |
29 | 8 | 0.23132903E-07 | 0.10021651E-12 | 0.39088690E-03 | -0.26302905E-09 |
30 | 7 | -0.12631865E-01 | 0.51350721E-08 | -0.23647662E-01 | 0.14362891E-03 |
31 | 6 | 0.41595524 | 0.17798199E-05 | 0.48111272 | -0.48727686E-02 |
32 | 5 | -5.2940477 | 0.66244475E-04 | -4.5105076 | 0.64467011E-01 |
33 | 4 | 33.460551 | 0.54034224E-03 | 21.710910 | -0.42819988 |
34 | 3 | -112.19991 | 0.11746209E-02 | -56.158897 | 1.5292621 |
35 | 2 | 198.09612 | 0.65921779E-03 | 78.365567 | -2.9160408 |
36 | 1 | -171.52093 | 0.70225444E-04 | -55.397708 | 2.7518339 |
37 | 0 | 57.057407 | 0.39880044E-06 | 15.535293 | |
38 | 9 | -0.27488611E-15 | 0.34931277E-16 | -0.14567168E-09 | -0.34479422E-18 |
39 | 8 | 0.21305634E-07 | 0.13616114E-12 | 0.37179150E-03 | -0.24225240E-09 |
40 | 7 | -0.12062412E-01 | 0.71136536E-08 | -0.22827857E-01 | 0.13715401E-03 |
41 | 6 | 0.40048261 | 0.24848663E-05 | 0.46794369 | -0.46903832E-02 |
42 | 5 | -5.1430590 | 0.93107898E-04 | -4.4094005 | 0.62594814E-01 |
43 | 4 | 32.792724 | 0.76407468E-03 | 21.315792 | -0.41933293 |
44 | 3 | -110.77914 | 0.16699767E-02 | -55.377787 | 1.5087354 |
45 | 2 | 196.68811 | 0.94174532E-03 | 77.649029 | -2.8936813 |
46 | 1 | -171.00089 | 0.10077048E-03 | -55.189078 | 2.7427195 |
47 | 0 | 57.057407 | 0.57514079E-06 | 15.569530 | |
48 | 9 | 0.31336604E-16 | 0.39008580E-16 | -0.14256869E-09 | 0.20136749E-17 |
49 | 8 | 0.20868940E-07 | 0.14443760E-12 | 0.36714717E-03 | -0.23728702E-09 |
50 | 7 | -0.11923636E-01 | 0.75824706E-08 | -0.22627983E-01 | 0.13557608E-03 |
51 | 6 | 0.39671154 | 0.26538398E-05 | 0.46472729 | -0.46459316E-02 |
52 | 5 | -5.1062546 | 0.99607489E-04 | -4.3846760 | 0.62138459E-01 |
53 | 4 | 32.629908 | 0.81865718E-03 | 21.219102 | -0.41717122 |
54 | 3 | -110.43267 | 0.17916944E-02 | -55.186609 | 1.5037299 |
55 | 2 | 196.34465 | 0.10116009E-02 | 77.473776 | -2.8882273 |
56 | 1 | -170.87399 | 0.10836560E-03 | -55.138279 | 2.7404955 |
57 | 0 | 57.057407 | 0.61925266E-06 | 15.578052 | |
58 | 9 | -0.27488611E-15 | 0.34931277E-16 | -0.14567168E-09 | -0.34479422E-18 |
59 | 8 | 0.21305634E-07 | 0.13616114E-12 | 0.37179150E-03 | -0.24225240E-09 |
60 | 7 | -0.12062412E-01 | 0.71136536E-08 | -0.22827857E-01 | 0.13715401E-03 |
61 | 6 | 0.40048261 | 0.24848663E-05 | 0.46794369 | -0.46903832E-02 |
62 | 5 | -5.1430590 | 0.93107898E-04 | -4.4094005 | 0.62594814E-01 |
63 | 4 | 32.792724 | 0.76407468E-03 | 21.315792 | -0.41933293 |
64 | 3 | -110.77914 | 0.16699767E-02 | -55.377787 | 1.5087354 |
65 | 2 | 196.68811 | 0.94174532E-03 | 77.649029 | -2.8936813 |
66 | 1 | -171.00089 | 0.10077048E-03 | -55.189078 | 2.7427195 |
67 | 0 | 57.057407 | 0.57514079E-06 | 15.569530 | |
68 | 9 | 0.31336604E-16 | 0.39008580E-16 | -0.14256869E-09 | 0.20136749E-17 |
69 | 8 | 0.20868940E-07 | 0.14443760E-12 | 0.36714717E-03 | -0.23728702E-09 |
70 | 7 | -0.11923636E-01 | 0.75824706E-08 | -0.22627983E-01 | 0.13557608E-03 |
71 | 6 | 0.39671154 | 0.26538398E-05 | 0.46472729 | -0.46459316E-02 |
72 | 5 | -5.1062546 | 0.99607489E-04 | -4.3846760 | 0.62138459E-01 |
73 | 4 | 32.629908 | 0.81865718E-03 | 21.219102 | -0.41717122 |
74 | 3 | -110.43267 | 0.17916944E-02 | -55.186609 | 1.5037299 |
75 | 2 | 196.34465 | 0.10116009E-02 | 77.473776 | -2.8882273 |
76 | 1 | -170.87399 | 0.10836560E-03 | -55.138279 | 2.7404955 |
77 | 0 | 57.057407 | 0.61925266E-06 | 15.578052 | |
78 | 7 | -0.15963512E-14 | -0.15187529E-16 | -0.22427203E-13 | 0.56155309E-15 |
79 | 6 | 0.17983713E-10 | 0.23594901E-11 | 0.52322926E-09 | -0.18637893E-10 |
80 | 5 | -0.60139213E-07 | 0.11510628E-07 | -0.21924491E-05 | 0.17161312E-06 |
81 | 4 | 0.62746279E-04 | 0.43399923E-05 | 0.17681060E-02 | -0.28244642E-03 |
82 | 3 | -0.90508353E-02 | 0.15320797E-03 | -0.21560640 | 0.43341486E-01 |
83 | 2 | 0.12836503 | 0.66328859E-03 | 2.9007871 | -0.61911613 |
84 | 1 | -0.32478029 | 0.41934727E-03 | -7.1379041 | 1.5697129 |
85 | 0 | 0.20664896 | 0.54311639E-05 | 4.4522013 | |
86 | 7 | -0.22427203E-13 | -0.15187529E-16 | -0.15963512E-14 | 0.56155309E-15 |
87 | 6 | 0.52322926E-09 | 0.23594901E-11 | 0.17983713E-10 | -0.18637893E-10 |
88 | 5 | -0.21924491E-05 | 0.11510628E-07 | -0.60139213E-07 | 0.17161312E-06 |
89 | 4 | 0.17681060E-02 | 0.43399923E-05 | 0.62746279E-04 | -0.28244642E-03 |
90 | 3 | -0.21560640 | 0.15320797E-03 | -0.90508353E-02 | 0.43341486E-01 |
91 | 2 | 2.9007871 | 0.66328859E-03 | 0.12836503 | -0.61911613 |
92 | 1 | -7.1379041 | 0.41934727E-03 | -0.32478029 | 1.5697129 |
93 | 0 | 4.4522013 | 0.54311639E-05 | 0.20664896 | |
94 | 7 | -0.52459208E-15 | -0.63961428E-15 | -0.12292524E-09 | -0.35846135E-17 |
95 | 6 | 0.39860198E-02 | 0.96339020E-07 | 0.40499006E-03 | -0.70890431E-04 |
96 | 5 | -0.20832379 | 0.49172556E-04 | -0.20585669E-01 | 0.38489246E-02 |
97 | 4 | 3.5198270 | 0.18993977E-02 | 0.34924834 | -0.69168259E-01 |
98 | 3 | -23.366787 | 0.13311857E-01 | -2.4329538 | 0.50524779 |
99 | 2 | 64.890127 | 0.19943872E-01 | 7.3672511 | -1.5911358 |
100 | 1 | -76.040094 | 0.56792084E-02 | -9.5568013 | 2.1361271 |
101 | 0 | 31.242244 | 0.96490710E-04 | 4.3344156 | |
102 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
103 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
104 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
105 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
106 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
107 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
108 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
109 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
110 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
111 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
112 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
113 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
114 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
115 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
116 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
117 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
118 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
119 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
120 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
121 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
122 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
123 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
124 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
125 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
126 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
127 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
128 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
129 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
130 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
131 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
132 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
133 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.3856_SHGC_0.4 | 37 | 1 | VerySmooth | 2.191 | 2.191 | 1.000 | 0.401 | ||
2 | RESWINDOW_U_0.3856_SHGC_0.4 | 38 | 1 | VerySmooth | 2.191 | 2.191 | 1.000 | 0.401 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER | SpectralAverage | 3.40174E-002 | 0.31435 | 0.47878 | 0.47878 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11969 | 1.00000 | No | |
2 | RESIDENTIAL WINDOW GLAZING LAYER | SpectralAverage | 3.40174E-002 | 0.31435 | 0.47878 | 0.47878 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11969 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 7 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 1.500 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 3.000 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWH BOOSTER E WATER HEATER | 2.2712E-002 | 8000.0 | 1.240 | 1.1473 |
2 | WaterHeater:Mixed | SWH LAUNDRY G WATER HEATER | 1.1356 | 163316.0 | 0.576 | 0.5074 |
3 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 2.2712 | 175842.6 | 0.260 | 2.5713E-002 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
6 | BASEMENT_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
7 | BASEMENT_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
8 | BASEMENT_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
9 | BASEMENT_CEILING_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
10 | BASEMENT_CEILING_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
11 | BASEMENT_CEILING_6 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
12 | BASEMENT_CEILING_7 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
13 | BASEMENT_CEILING_8 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
14 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
15 | RETAIL_1_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 4 | No | No |
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 1 | No | No |
17 | RETAIL_1_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 3 | No | No |
18 | RETAIL_1_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
19 | RETAIL_1_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
20 | RETAIL_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
21 | RETAIL_1_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
23 | RETAIL_2_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
25 | RETAIL_2_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
26 | RETAIL_2_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
27 | RETAIL_2_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
28 | RETAIL_2_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
29 | RETAIL_2_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
31 | MECH_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
32 | MECH_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
33 | MECH_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
34 | MECH_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
35 | MECH_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
36 | MECH_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
37 | MECH_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
38 | STORAGE_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
40 | STORAGE_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
41 | STORAGE_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
42 | STORAGE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
43 | STORAGE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
44 | STORAGE_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
45 | STORAGE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
46 | LAUNDRY_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
47 | LAUNDRY_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
49 | LAUNDRY_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
50 | LAUNDRY_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
51 | LAUNDRY_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
52 | LAUNDRY_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
54 | CAFE_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 3 | No | No |
55 | CAFE_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
56 | CAFE_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 4 | No | No |
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 1 | No | No |
58 | CAFE_FLR_1_WALL_1_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
59 | CAFE_FLR_1_WALL_2_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
60 | CAFE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
61 | CAFE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
62 | CAFE_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
63 | CAFE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
64 | LOBBY_FLR_1_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
67 | LOBBY_FLR_1_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
68 | LOBBY_FLR_1_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 1 | No | No |
70 | LOBBY_FLR_1_WALL_1_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
71 | LOBBY_FLR_1_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
72 | LOBBY_FLR_1_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
73 | LOBBY_FLR_1_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
74 | LOBBY_FLR_1_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
75 | LOBBY_FLR_1_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
76 | LOBBY_FLR_1_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
77 | LOBBY_FLR_1_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
78 | LOBBY_FLR_1_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
79 | LOBBY_FLR_1_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
80 | LOBBY_FLR_1_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
81 | LOBBY_FLR_1_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
82 | LOBBY_FLR_1_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
83 | LOBBY_FLR_1_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
84 | LOBBY_FLR_1_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
85 | LOBBY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
86 | ROOM_1_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
88 | ROOM_1_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
90 | ROOM_1_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
91 | ROOM_1_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
92 | ROOM_1_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
93 | ROOM_1_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
94 | ROOM_1_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
95 | ROOM_2_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
97 | ROOM_2_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
99 | ROOM_2_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
100 | ROOM_2_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
101 | ROOM_2_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
102 | ROOM_2_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
103 | ROOM_2_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
109 | ROOM_3_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
110 | ROOM_3_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
117 | ROOM_4_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
118 | ROOM_4_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
120 | ROOM_5_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
122 | ROOM_5_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
124 | ROOM_5_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
125 | ROOM_5_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
126 | ROOM_5_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
127 | ROOM_5_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
128 | ROOM_5_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
129 | ROOM_6_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
131 | ROOM_6_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
133 | ROOM_6_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
134 | ROOM_6_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
135 | ROOM_6_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
136 | ROOM_6_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
137 | ROOM_6_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
138 | CORRIDOR_FLR_3_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
147 | CORRIDOR_FLR_3_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
148 | CORRIDOR_FLR_3_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
149 | CORRIDOR_FLR_3_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
150 | CORRIDOR_FLR_3_WALL_4_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
152 | CORRIDOR_FLR_3_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
153 | CORRIDOR_FLR_3_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
154 | CORRIDOR_FLR_3_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
155 | CORRIDOR_FLR_3_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
156 | CORRIDOR_FLR_3_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
157 | CORRIDOR_FLR_3_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
158 | CORRIDOR_FLR_3_FLOOR_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
159 | CORRIDOR_FLR_3_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
160 | CORRIDOR_FLR_3_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
161 | CORRIDOR_FLR_3_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
163 | ROOM_1_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
165 | ROOM_1_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
167 | ROOM_1_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
168 | ROOM_1_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
169 | ROOM_1_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
170 | ROOM_1_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
171 | ROOM_1_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
172 | ROOM_2_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
174 | ROOM_2_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
176 | ROOM_2_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
177 | ROOM_2_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
178 | ROOM_2_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
179 | ROOM_2_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
180 | ROOM_2_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 3 | No | No |
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 2 | No | No |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
186 | ROOM_3_MULT9_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
187 | ROOM_3_MULT9_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
189 | BANQUET_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
191 | BANQUET_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
192 | BANQUET_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
193 | BANQUET_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
194 | BANQUET_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
195 | BANQUET_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
196 | BANQUET_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
197 | DINING_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
198 | DINING_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
199 | DINING_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
200 | DINING_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
201 | DINING_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
202 | DINING_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
203 | DINING_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
204 | DINING_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
205 | KITCHEN_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
207 | KITCHEN_FLR_6_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
212 | KITCHEN_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
213 | KITCHEN_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
214 | KITCHEN_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
215 | KITCHEN_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
216 | KITCHEN_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
217 | CORRIDOR_FLR_6_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
224 | CORRIDOR_FLR_6_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
226 | CORRIDOR_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
227 | CORRIDOR_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
228 | CORRIDOR_FLR_6_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
229 | CORRIDOR_FLR_6_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
230 | CORRIDOR_FLR_6_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
231 | CORRIDOR_FLR_6_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
232 | CORRIDOR_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
233 | CORRIDOR_FLR_6_CEILING_1 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
234 | CORRIDOR_FLR_6_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | RETAIL_1_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 3.921E-002 | 5.846E-004 | 2.885E-004 | 0.531 | 1.000 | 0.000 | 0.000 | 0.000 |
2 | RETAIL_2_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 1.513E-002 | 1.949E-004 | 5.306E-004 | 0.177 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | MECH_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | MECH_FLR_1 | 164.24 | 2.7 | 3.577E-002 | 2.178E-004 | 5.696E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
4 | STORAGE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | STORAGE_FLR_1 | 94.76 | 2.0 | 2.064E-002 | 2.178E-004 | 4.726E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | LAUNDRY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 4.884E-002 | 6.258E-004 | 5.569E-004 | 0.569 | 1.000 | 0.000 | 0.000 | 0.000 |
6 | CAFE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 8.667E-002 | 4.589E-004 | 2.527E-004 | 0.417 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | LOBBY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 0.248 | 1.893E-004 | 3.620E-004 | 0.172 | 1.000 | 0.000 | 0.000 | 0.000 |
8 | ROOM_1_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | ROOM_2_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
10 | ROOM_3_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 6.349E-003 | 2.589E-004 | 5.696E-004 | 0.306 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | ROOM_4_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 6.350E-003 | 2.589E-004 | 5.696E-004 | 0.306 | 1.000 | 0.000 | 0.000 | 0.000 |
12 | ROOM_5_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | ROOM_6_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 5.696E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
14 | CORRIDOR_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_3 | 389.40 | 21.0 | 2.751E-002 | 7.066E-005 | 5.696E-004 | 8.345E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | ROOM_1_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 2.881E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
16 | ROOM_2_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 2.275E-002 | 5.831E-004 | 2.881E-004 | 0.689 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | ROOM_3_MULT9_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 1.164E-002 | 4.746E-004 | 2.589E-004 | 0.561 | 1.000 | 0.000 | 0.000 | 0.000 |
18 | BANQUET_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 5.556E-002 | 1.675E-004 | 1.295E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | DINING_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | DINING_FLR_6 | 331.66 | 249.9 | 5.556E-002 | 1.675E-004 | 1.295E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
20 | KITCHEN_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 4.974E-002 | 4.815E-004 | 2.609E-004 | 0.569 | 1.000 | 0.000 | 0.000 | 0.000 |
21 | CORRIDOR_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_6 | 412.12 | 22.2 | 4.868E-002 | 1.181E-004 | 9.784E-005 | 0.140 | 1.000 | 0.000 | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | ROOM_1_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
2 | ROOM_2_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
3 | ROOM_3_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
4 | ROOM_4_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
5 | ROOM_5_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_5_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
6 | ROOM_6_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_6_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
7 | ROOM_1_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
8 | ROOM_2_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
9 | ROOM_3_MULT9_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | RETAIL_1_FLR_1 | Mixing/Well-Stirred |
3 | RETAIL_2_FLR_1 | Mixing/Well-Stirred |
4 | MECH_FLR_1 | Mixing/Well-Stirred |
5 | STORAGE_FLR_1 | Mixing/Well-Stirred |
6 | LAUNDRY_FLR_1 | Mixing/Well-Stirred |
7 | CAFE_FLR_1 | Mixing/Well-Stirred |
8 | LOBBY_FLR_1 | Mixing/Well-Stirred |
9 | ROOM_1_FLR_3 | Mixing/Well-Stirred |
10 | ROOM_2_FLR_3 | Mixing/Well-Stirred |
11 | ROOM_3_MULT19_FLR_3 | Mixing/Well-Stirred |
12 | ROOM_4_MULT19_FLR_3 | Mixing/Well-Stirred |
13 | ROOM_5_FLR_3 | Mixing/Well-Stirred |
14 | ROOM_6_FLR_3 | Mixing/Well-Stirred |
15 | CORRIDOR_FLR_3 | Mixing/Well-Stirred |
16 | ROOM_1_FLR_6 | Mixing/Well-Stirred |
17 | ROOM_2_FLR_6 | Mixing/Well-Stirred |
18 | ROOM_3_MULT9_FLR_6 | Mixing/Well-Stirred |
19 | BANQUET_FLR_6 | Mixing/Well-Stirred |
20 | DINING_FLR_6 | Mixing/Well-Stirred |
21 | KITCHEN_FLR_6 | Mixing/Well-Stirred |
22 | CORRIDOR_FLR_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 33765.31537 | 33765.31537 | 2.47965 | 2.47965 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | 23.30600 | 8.40224E-003 | 1978.83018 | 106.49900 | 0.85446 | 0.00000 |
2 | BASEMENT | Heating | 1439.64678 | 1439.64678 | 6.23703E-002 | 0.85446 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -4.30000 | 2.65759E-003 | 1978.83018 | 106.49900 | 0.85446 | 0.00000 |
3 | RETAIL_1_FLR_1 | Cooling | 6466.55962 | 6466.55962 | 0.47493 | 0.47493 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 26.17250 | 8.40672E-003 | 67.07136 | 10.82900 | 7.92179E-002 | 0.00000 |
4 | RETAIL_1_FLR_1 | Heating | 2359.52947 | 2359.52947 | 0.10222 | 0.10222 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | -4.30000 | 2.65759E-003 | 67.07136 | 10.82900 | 7.92179E-002 | 0.00000 |
5 | RETAIL_2_FLR_1 | Cooling | 3233.45548 | 3233.45548 | 0.23748 | 0.23748 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 | 26.21800 | 8.40679E-003 | 77.66889 | 12.54000 | 9.17347E-002 | 0.00000 |
6 | RETAIL_2_FLR_1 | Heating | 760.71402 | 760.71402 | 3.29561E-002 | 9.17347E-002 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -4.30000 | 2.65759E-003 | 77.66889 | 12.54000 | 9.17347E-002 | 0.00000 |
7 | MECH_FLR_1 | Cooling | 3034.79529 | 3034.79529 | 0.22284 | 0.22284 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 26.30900 | 8.40693E-003 | 164.24319 | 2.65200 | 0.00000 | 0.00000 |
8 | MECH_FLR_1 | Heating | 1394.55860 | 1394.55860 | 6.04157E-002 | 6.04157E-002 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -4.30000 | 2.65759E-003 | 164.24319 | 2.65200 | 0.00000 | 0.00000 |
9 | STORAGE_FLR_1 | Cooling | 1490.09926 | 1490.09926 | 0.10942 | 0.10942 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 26.40000 | 8.40708E-003 | 94.75927 | 2.04000 | 5.77652E-002 | 0.00000 |
10 | STORAGE_FLR_1 | Heating | 866.24448 | 866.24448 | 3.75278E-002 | 5.77652E-002 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -4.30000 | 2.65759E-003 | 94.75927 | 2.04000 | 5.77652E-002 | 0.00000 |
11 | LAUNDRY_FLR_1 | Cooling | 44695.51748 | 44695.51748 | 3.28229 | 3.28229 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 26.40000 | 8.40708E-003 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
12 | LAUNDRY_FLR_1 | Heating | 1815.44408 | 1815.44408 | 7.86481E-002 | 7.86481E-002 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | -4.30000 | 2.65759E-003 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
13 | CAFE_FLR_1 | Cooling | 25469.38276 | 25469.38276 | 1.87203 | 1.87203 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 26.17250 | 8.40672E-003 | 188.86188 | 142.30000 | 0.67639 | 0.00000 |
14 | CAFE_FLR_1 | Heating | 5997.44110 | 5997.44110 | 0.25982 | 0.67639 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | -4.30000 | 2.65759E-003 | 188.86188 | 142.30000 | 0.67639 | 0.00000 |
15 | LOBBY_FLR_1 | Cooling | 70309.14605 | 70309.14605 | 5.16528 | 5.16528 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 26.24833 | 8.40684E-003 | 1308.18612 | 422.43500 | 1.89399 | 0.00000 |
16 | LOBBY_FLR_1 | Heating | 13866.23776 | 13866.23776 | 0.60072 | 1.89399 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -4.30000 | 2.65759E-003 | 1308.18612 | 422.43500 | 1.89399 | 0.00000 |
17 | ROOM_1_FLR_3 | Cooling | 12580.63778 | 12580.63778 | 1.24494 | 1.24494 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 16:40:00 | 25.36867 | 8.40546E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
18 | ROOM_1_FLR_3 | Heating | 5188.66322 | 5188.66322 | 0.22610 | 0.22610 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | -4.30000 | 2.65759E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
19 | ROOM_2_FLR_3 | Cooling | 11248.27181 | 11248.27181 | 1.11309 | 1.11309 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 25.12600 | 8.40508E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
20 | ROOM_2_FLR_3 | Heating | 5194.31924 | 5194.31924 | 0.22635 | 0.22635 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | -4.30000 | 2.65759E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
21 | ROOM_3_MULT19_FLR_3 | Cooling | 91451.39819 | 91451.39819 | 9.04933 | 9.04933 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 26.17250 | 8.40672E-003 | 24.52384 | 1.50000 | 0.83707 | 0.00000 |
22 | ROOM_3_MULT19_FLR_3 | Heating | 29731.10843 | 29731.10843 | 1.29559 | 1.29559 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | -4.30000 | 2.65759E-003 | 24.52384 | 1.50000 | 0.83707 | 0.00000 |
23 | ROOM_4_MULT19_FLR_3 | Cooling | 58139.32953 | 58139.32953 | 5.75346 | 5.75346 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 26.40000 | 8.40708E-003 | 24.53055 | 1.50000 | 0.83730 | 0.00000 |
24 | ROOM_4_MULT19_FLR_3 | Heating | 29853.35889 | 29853.35889 | 1.30092 | 1.30092 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | -4.30000 | 2.65759E-003 | 24.53055 | 1.50000 | 0.83730 | 0.00000 |
25 | ROOM_5_FLR_3 | Cooling | 11423.97709 | 11423.97709 | 1.13048 | 1.13048 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 22.94200 | 8.40167E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
26 | ROOM_5_FLR_3 | Heating | 5176.66915 | 5176.66915 | 0.22558 | 0.22558 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | -4.30000 | 2.65759E-003 | 39.02202 | 1.50000 | 6.17350E-002 | 0.00000 |
27 | ROOM_6_FLR_3 | Cooling | 10298.39311 | 10298.39311 | 1.01909 | 1.01909 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:10:00 | 21.65283 | 8.39969E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
28 | ROOM_6_FLR_3 | Heating | 5182.32854 | 5182.32854 | 0.22583 | 0.22583 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | -4.30000 | 2.65759E-003 | 39.01745 | 1.50000 | 6.17278E-002 | 0.00000 |
29 | CORRIDOR_FLR_3 | Cooling | 17037.06920 | 17037.06920 | 1.25113 | 1.25113 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:10:00 | 26.40000 | 8.40708E-003 | 389.40468 | 20.95700 | 0.47476 | 0.00000 |
30 | CORRIDOR_FLR_3 | Heating | 8049.46645 | 8049.46645 | 0.34873 | 0.47476 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | -4.30000 | 2.65759E-003 | 389.40468 | 20.95700 | 0.47476 | 0.00000 |
31 | ROOM_1_FLR_6 | Cooling | 3369.73956 | 3369.73956 | 0.33346 | 0.33346 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 25.49000 | 8.40565E-003 | 39.02202 | 1.50000 | 1.54338E-002 | 0.00000 |
32 | ROOM_1_FLR_6 | Heating | 1653.18198 | 1653.18198 | 7.20390E-002 | 7.20390E-002 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | -4.30000 | 2.65759E-003 | 39.02202 | 1.50000 | 1.54338E-002 | 0.00000 |
33 | ROOM_2_FLR_6 | Cooling | 2992.27507 | 2992.27507 | 0.29611 | 0.29611 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 25.12600 | 8.40508E-003 | 39.01745 | 1.50000 | 1.54319E-002 | 0.00000 |
34 | ROOM_2_FLR_6 | Heating | 1654.60650 | 1654.60650 | 7.21011E-002 | 7.21011E-002 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | -4.30000 | 2.65759E-003 | 39.01745 | 1.50000 | 1.54319E-002 | 0.00000 |
35 | ROOM_3_MULT9_FLR_6 | Cooling | 18669.62523 | 18669.62523 | 1.84752 | 1.84752 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 26.24833 | 8.40684E-003 | 24.53055 | 1.50000 | 9.91540E-002 | 0.00000 |
36 | ROOM_3_MULT9_FLR_6 | Heating | 7974.43762 | 7974.43762 | 0.34750 | 0.34750 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | -4.30000 | 2.65759E-003 | 24.53055 | 1.50000 | 9.91540E-002 | 0.00000 |
37 | BANQUET_FLR_6 | Cooling | 29819.49215 | 29819.49215 | 2.19250 | 2.19250 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 26.40000 | 8.40708E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
38 | BANQUET_FLR_6 | Heating | 5666.38285 | 5666.38285 | 0.24548 | 1.18780 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | -4.30000 | 2.65759E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
39 | DINING_FLR_6 | Cooling | 31280.59482 | 31280.59482 | 2.29990 | 2.29990 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:20:00 | 26.40000 | 8.40708E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
40 | DINING_FLR_6 | Heating | 5767.94836 | 5767.94836 | 0.24988 | 1.18780 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 19:20:00 | -4.30000 | 2.65759E-003 | 331.65745 | 249.89600 | 1.18780 | 0.00000 |
41 | KITCHEN_FLR_6 | Cooling | 31445.53133 | 31445.53133 | 2.31521 | 2.31521 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 12:30:00 | 25.58100 | 8.40579E-003 | 103.30446 | 22.23800 | 0.36735 | 0.00000 |
42 | KITCHEN_FLR_6 | Heating | 937.60221 | 937.60221 | 4.06135E-002 | 0.36735 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | -4.30000 | 2.65759E-003 | 103.30446 | 22.23800 | 0.36735 | 0.00000 |
43 | CORRIDOR_FLR_6 | Cooling | 10501.10778 | 10501.10778 | 0.77115 | 0.77115 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 26.40000 | 8.40708E-003 | 412.12471 | 22.18000 | 0.12562 | 0.00000 |
44 | CORRIDOR_FLR_6 | Heating | 6059.60211 | 6059.60211 | 0.26252 | 0.26252 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 19:20:00 | -4.30000 | 2.65759E-003 | 412.12471 | 22.18000 | 0.12562 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV WITH REHEAT | Cooling | Sensible | 367120.94 | 22.55588 | 22.55588 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
2 | VAV WITH REHEAT | Heating | Sensible | 183419.29 | 7.29581 | 7.29581 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 19:20:00 |
3 | FLR_3_DOAS | Cooling | Sensible | 33397.10 | 20.41511 | 2.05125 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
4 | FLR_3_DOAS | Heating | Sensible | 51569.06 | 3.99200 | 2.05125 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.47965 |
2 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.60810 |
3 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.99500 |
4 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.46725 |
5 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
6 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 6.26543E-004 |
8 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.25340E-004 |
9 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.46725 |
10 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
11 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
12 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 14327.11670 |
13 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.25340E-004 |
14 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 300.50608 |
15 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.47493 |
16 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10761 |
17 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.99500 |
18 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.47255 |
19 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.99500 |
20 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
21 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.54045E-003 |
22 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.22148E-005 |
23 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.47255 |
24 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
25 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
26 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 4825.40856 |
27 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.22148E-005 |
28 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 105.88582 |
29 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.23748 |
30 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.24921 |
31 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.99500 |
32 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.23630 |
33 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.99500 |
34 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
35 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.52882E-003 |
36 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.74418E-005 |
37 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.23630 |
38 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
40 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1993.71054 |
41 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.74418E-005 |
42 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 42.94962 |
43 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.22284 |
44 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.56162 |
45 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.99500 |
46 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.22173 |
47 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
48 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
49 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 6.78398E-004 |
50 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.23193E-005 |
51 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.22173 |
52 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
53 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
54 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 2551.23755 |
55 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.23193E-005 |
56 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 56.75998 |
57 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.10942 |
58 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.65991 |
59 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.99500 |
60 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.10887 |
61 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
62 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 5.77351E-004 |
64 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.25473E-005 |
65 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.10887 |
66 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
67 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
68 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1434.23167 |
69 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.25473E-005 |
70 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 32.49217 |
71 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 3.28229 |
72 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 7.18931E-002 |
73 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.99500 |
74 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 3.26588 |
75 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.99500 |
76 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
77 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.10297E-002 |
78 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.64900E-004 |
79 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 3.26588 |
80 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
81 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
82 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 18849.12599 |
83 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.64900E-004 |
84 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 395.21391 |
85 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.87203 |
86 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 7.68752E-002 |
87 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.99500 |
88 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.86267 |
89 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.99500 |
90 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
91 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.95608E-003 |
92 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.37514E-004 |
93 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.86267 |
94 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
96 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 15718.64927 |
97 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.37514E-004 |
98 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 338.62483 |
99 | Fan:ZoneExhaust | LOBBY_FLR_1 EXHAUST FAN | User-Specified Maximum Flow Rate [m3/s] | 0.00000 |
100 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.16528 |
101 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.19299 |
102 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.99500 |
103 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 5.13945 |
104 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.99500 |
105 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
106 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.97421E-003 |
107 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.55945E-004 |
108 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 5.13945 |
109 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
110 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
111 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 40686.71056 |
112 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.55945E-004 |
113 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 871.80933 |
114 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_1_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17350E-002 |
115 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.24494 |
116 | Fan:OnOff | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.24494 |
117 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 4.53927E-005 |
118 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 5.32340E-004 |
119 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 22.50292 |
120 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
121 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.55731E-003 |
122 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
123 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
124 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 5.32340E-004 |
125 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.24494 |
126 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 5188.66763 |
127 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.53927E-005 |
128 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 148.27945 |
129 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_2_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17278E-002 |
130 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.11309 |
131 | Fan:OnOff | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.11309 |
132 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 4.54422E-005 |
133 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 4.76766E-004 |
134 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 22.50290 |
135 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
136 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.56399E-003 |
137 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
138 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
139 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.76766E-004 |
140 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.11309 |
141 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 5194.32365 |
142 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.54422E-005 |
143 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 148.44104 |
144 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_3_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.83707 |
145 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 9.04933 |
146 | Fan:OnOff | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 9.04933 |
147 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 2.60101E-004 |
148 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.81361E-003 |
149 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 22.50342 |
150 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
151 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.49881E-003 |
152 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
153 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.49881E-003 |
154 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.81361E-003 |
155 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 9.04933 |
156 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 29731.11927 |
157 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.60101E-004 |
158 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 849.62915 |
159 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_4_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.83730 |
160 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 5.75346 |
161 | Fan:OnOff | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 5.75346 |
162 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 2.61170E-004 |
163 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.57417E-003 |
164 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 22.50217 |
165 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
166 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.74067E-003 |
167 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
168 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
169 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.57417E-003 |
170 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 5.75346 |
171 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 29853.36980 |
172 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.61170E-004 |
173 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 853.12186 |
174 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_5_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17350E-002 |
175 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.13048 |
176 | Fan:OnOff | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.13048 |
177 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 4.52878E-005 |
178 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 4.84102E-004 |
179 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 22.50291 |
180 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
181 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.56308E-003 |
182 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
183 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
184 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.84102E-004 |
185 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.13048 |
186 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 5176.67355 |
187 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.52878E-005 |
188 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 147.93679 |
189 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_6_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.17278E-002 |
190 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.01909 |
191 | Fan:OnOff | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.01909 |
192 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 4.53373E-005 |
193 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 4.37132E-004 |
194 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 22.50289 |
195 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
196 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.56969E-003 |
197 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
198 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
199 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.37132E-004 |
200 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.01909 |
201 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 5182.33294 |
202 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.53373E-005 |
203 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 148.09847 |
204 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.25113 |
205 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.94866 |
206 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.99500 |
207 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.24488 |
208 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
209 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
210 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.01618E-004 |
211 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.27267E-004 |
212 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.24488 |
213 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
214 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
215 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 14547.38460 |
216 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.27267E-004 |
217 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 324.27675 |
218 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_1_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.54338E-002 |
219 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.33346 |
220 | Fan:OnOff | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.33346 |
221 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.44628E-005 |
222 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 1.42453E-004 |
223 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 22.50294 |
224 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
225 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.55356E-003 |
226 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
227 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
228 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.42453E-004 |
229 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.33346 |
230 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 1653.18350 |
231 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.44628E-005 |
232 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 47.24104 |
233 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_2_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.54319E-002 |
234 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.29611 |
235 | Fan:OnOff | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 0.29611 |
236 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.44752E-005 |
237 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 1.26711E-004 |
238 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 22.50292 |
239 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
240 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.56028E-003 |
241 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
242 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
243 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.26711E-004 |
244 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 0.29611 |
245 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 1654.60802 |
246 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.44752E-005 |
247 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 47.28174 |
248 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ROOM_3_MULT9_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 9.91540E-002 |
249 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.84752 |
250 | Fan:OnOff | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Design Size Maximum Flow Rate [m3/s] | 1.84752 |
251 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 6.97639E-005 |
252 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 7.96248E-004 |
253 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Temperature [C] | 22.50265 |
254 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
255 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.58862E-003 |
256 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
257 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
258 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 7.96248E-004 |
259 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 1.84752 |
260 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size Rated Capacity [W] | 7974.44413 |
261 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.97639E-005 |
262 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 227.87416 |
263 | Fan:ZoneExhaust | BANQUET_FLR_6 EXHAUST FAN | User-Specified Maximum Flow Rate [m3/s] | 0.00000 |
264 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.19250 |
265 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11527 |
266 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.99500 |
267 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.18154 |
268 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.99500 |
269 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
270 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.30537E-003 |
271 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.49207E-004 |
272 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.18154 |
273 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
274 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
275 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 17055.31940 |
276 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.49207E-004 |
277 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 365.08170 |
278 | Fan:ZoneExhaust | DINING_FLR_6 EXHAUST FAN | User-Specified Maximum Flow Rate [m3/s] | 0.00000 |
279 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.29990 |
280 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10988 |
281 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.99500 |
282 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.28840 |
283 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.99500 |
284 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
285 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.46728E-003 |
286 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.54976E-004 |
287 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.28840 |
288 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
289 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
290 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 17714.73017 |
291 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.54976E-004 |
292 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 378.89830 |
293 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.31521 |
294 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.81539 |
295 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.99500 |
296 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.30363 |
297 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.99500 |
298 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
299 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.12057E-002 |
300 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.12737E-004 |
301 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.30363 |
302 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
303 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
304 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 12886.51466 |
305 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.12737E-004 |
306 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 269.71648 |
307 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.77115 |
308 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.40723 |
309 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.99500 |
310 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.76730 |
311 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
312 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
313 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 9.35579E-004 |
314 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 8.80598E-005 |
315 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.76730 |
316 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
317 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
318 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 10065.77554 |
319 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.80598E-005 |
320 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 227.89973 |
321 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 22.56044 |
322 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 22.56044 |
323 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 22.67381 |
324 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 22.56044 |
325 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 22.56044 |
326 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 22.56044 |
327 | AirLoopHVAC | VAV WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
328 | AirLoopHVAC | VAV WITH REHEAT | Calculated Heating Air Flow Ratio [] | 1.00000 |
329 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.05132 |
330 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.05132 |
331 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.05132 |
332 | AirLoopHVAC | FLR_3_DOAS | Adjusted Heating Design Air Flow Rate [m3/s] | 2.05132 |
333 | AirLoopHVAC | FLR_3_DOAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.05132 |
334 | AirLoopHVAC | FLR_3_DOAS | Adjusted Main Design Air Flow Rate [m3/s] | 2.05132 |
335 | AirLoopHVAC | FLR_3_DOAS | User Heating Air Flow Ratio [] | 0.30000 |
336 | AirLoopHVAC | FLR_3_DOAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
337 | AirLoopHVAC | VAV WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 22.56044 |
338 | AirLoopHVAC | FLR_3_DOAS | Design Supply Air Flow Rate [m3/s] | 2.05132 |
339 | Controller:OutdoorAir | VAV WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 22.56044 |
340 | Controller:OutdoorAir | VAV WITH REHEAT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 22.55588 |
341 | HeatExchanger:AirToAir:SensibleAndLatent | VAV WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 22.55588 |
342 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 26.40000 |
343 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
344 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.95700 |
345 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.40708E-003 |
346 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.40708E-003 |
347 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 423570.84074 |
348 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.51290E-002 |
349 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 22.56044 |
350 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 170153.30987 |
351 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.48858E-003 |
352 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 2903.29538 |
353 | Fan:VariableVolume | VAV WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 22.56044 |
354 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.51290E-002 |
355 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 3.14754E-005 |
356 | Controller:WaterCoil | VAV WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.48858E-003 |
357 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.05132 |
358 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.05125 |
359 | HeatExchanger:AirToAir:SensibleAndLatent | FLR_3_DOAS OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.05125 |
360 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 26.40000 |
361 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
362 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.91985 |
363 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.40708E-003 |
364 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.40708E-003 |
365 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Coil Load [W] | 36112.10278 |
366 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.28984E-003 |
367 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 2.05132 |
368 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size Rated Capacity [W] | 15471.26131 |
369 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.35349E-004 |
370 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 263.98335 |
371 | Fan:ConstantVolume | FLR_3_DOAS FAN | User-Specified Maximum Flow Rate [m3/s] | 2.05125 |
372 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.28984E-003 |
373 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 3.69186E-004 |
374 | Controller:WaterCoil | FLR_3_DOAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.35349E-004 |
375 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 2.58023E-002 |
376 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 5316.90522 |
377 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 3.93583E-003 |
378 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 0.47230 |
379 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 3.93583E-003 |
380 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 1185.29827 |
381 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
382 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 449889.20891 |
383 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 449889.21000 |
384 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 3.93583E-003 |
385 | PlantLoop | COOLSYS1 | Maximum Loop Flow Rate [m3/s] | 2.58023E-002 |
386 | PlantLoop | COOLSYS1 | Plant Loop Volume [m3] | 3.09628 |
387 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Flow Rate [m3/s] | 2.58023E-002 |
388 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Power Consumption [W] | 3681.07281 |
389 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 2.58023E-002 |
390 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 722396.70310 |
391 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 723021.47000 |
392 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 82.42445 |
393 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 3.75036E-004 |
394 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 4.50044E-002 |
395 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 3.75036E-004 |
396 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 47.90688 |
397 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 3.75036E-004 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | 14400.77 |
2 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 4848.88 |
3 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 2003.71 |
4 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | 2563.47 |
5 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | 1440.98 |
6 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 18946.06 |
7 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | 15797.50 |
8 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | 40891.79 |
9 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COIL HEATING COIL | 5588.77 |
10 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COIL HEATING COIL | 5594.86 |
11 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | 32023.54 |
12 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | 32155.20 |
13 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COIL HEATING COIL | 5575.85 |
14 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COIL HEATING COIL | 5581.95 |
15 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 14617.01 |
16 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COIL HEATING COIL | 1780.60 |
17 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COIL HEATING COIL | 1782.13 |
18 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | 8589.02 |
19 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | 17141.36 |
20 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | 17804.16 |
21 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | 12952.89 |
22 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 10113.20 |
23 | Coil:Heating:Water | VAV WITH REHEAT HEATING COIL | 129454.91 |
24 | Coil:Heating:Water | FLR_3_DOAS HEATING COIL | 11770.74 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COIL COOLING COIL | 21584.43 | 17086.44 | 4498.00 | 0.79 | 2416.78 | 24.51 |
2 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COIL COOLING COIL | 19319.28 | 15287.11 | 4032.16 | 0.79 | 2162.93 | 21.94 |
3 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | 155426.92 | 123471.76 | 31955.16 | 0.79 | 17415.74 | 176.64 |
4 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | 102646.17 | 80387.06 | 22259.10 | 0.78 | 11464.82 | 116.28 |
5 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COIL COOLING COIL | 19618.16 | 15524.48 | 4093.68 | 0.79 | 2196.43 | 22.28 |
6 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COIL COOLING COIL | 17704.01 | 14004.14 | 3699.87 | 0.79 | 1981.92 | 20.10 |
7 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COIL COOLING COIL | 5777.92 | 4574.90 | 1203.02 | 0.79 | 646.98 | 6.56 |
8 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COIL COOLING COIL | 5136.26 | 4065.18 | 1071.08 | 0.79 | 575.07 | 5.83 |
9 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | 32192.73 | 25435.98 | 6756.75 | 0.79 | 3602.88 | 36.54 |
10 | Coil:Cooling:Water | VAV WITH REHEAT COOLING COIL | 530774.70 | 378834.66 | 151940.04 | 0.71 | 65136.51 | 660.65 |
11 | Coil:Cooling:Water | FLR_3_DOAS COOLING COIL | 45302.65 | 32936.56 | 12366.09 | 0.73 | 5220.86 | 52.95 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | 3.72 | 12.68 |
Zone Name | # Surfaces | |
1 | BASEMENT | 14 |
2 | RETAIL_1_FLR_1 | 8 |
3 | RETAIL_2_FLR_1 | 8 |
4 | MECH_FLR_1 | 7 |
5 | STORAGE_FLR_1 | 8 |
6 | LAUNDRY_FLR_1 | 8 |
7 | CAFE_FLR_1 | 10 |
8 | LOBBY_FLR_1 | 22 |
9 | ROOM_1_FLR_3 | 9 |
10 | ROOM_2_FLR_3 | 9 |
11 | ROOM_3_MULT19_FLR_3 | 8 |
12 | ROOM_4_MULT19_FLR_3 | 8 |
13 | ROOM_5_FLR_3 | 9 |
14 | ROOM_6_FLR_3 | 9 |
15 | CORRIDOR_FLR_3 | 25 |
16 | ROOM_1_FLR_6 | 9 |
17 | ROOM_2_FLR_6 | 9 |
18 | ROOM_3_MULT9_FLR_6 | 8 |
19 | BANQUET_FLR_6 | 8 |
20 | DINING_FLR_6 | 8 |
21 | KITCHEN_FLR_6 | 12 |
22 | CORRIDOR_FLR_6 | 19 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.419 | 0.394 | 211.13 | 211.13 | 211.13 | 0.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.419 | 0.394 | 55.76 | 55.76 | 55.76 | 90.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.419 | 0.394 | 211.13 | 211.13 | 211.13 | 180.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_WEST_CFACTOR | 0.419 | 0.394 | 55.76 | 55.76 | 55.76 | 270.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | BASEMENT_FLOOR | 2.705 | 1.632 | 1978.83 | 1978.83 | 1978.83 | 0.00 | 180.00 | 86.56 | 22.86 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | BASEMENT_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | RETAIL_1_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | BASEMENT_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | BASEMENT_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | BASEMENT_CEILING_4 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_CEILING_5 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
11 | BASEMENT_CEILING_6 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | CAFE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
12 | BASEMENT_CEILING_7 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 0.00 | 32.99 | 32.99 | 0.00 | LOBBY_FLR_1_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
13 | BASEMENT_CEILING_8 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 219.63 | 219.63 | 219.63 | 90.00 | 0.00 | 14.82 | 14.82 | 0.00 | LOBBY_FLR_1_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
14 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 3957.66 | 3957.66 | 3957.66 | 0.00 | 90.00 | 3957.66 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
15 | RETAIL_1_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.738 | 0.664 | 22.63 | 45.89 | 22.63 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | Window | RETAIL_1_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 23.26 | 23.26 | 23.26 | 180.00 | 90.00 | 10.92 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
17 | RETAIL_1_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.738 | 0.664 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
18 | RETAIL_1_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | RETAIL_1_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | RETAIL_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 67.07 | 67.07 | 67.07 | 0.00 | 180.00 | 11.58 | 5.79 | 0.00 | BASEMENT_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | RETAIL_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 7.62E-002 | 0.92 | 4 | ||
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 134.14 | 134.14 | 134.14 | 0.00 | 90.00 | 134.14 | 1.00 | 0.00 | RETAIL_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
23 | RETAIL_2_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.738 | 0.664 | 24.62 | 26.57 | 24.62 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | Door | RETAIL_2_FLR_1_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
25 | RETAIL_2_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
26 | RETAIL_2_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | RETAIL_2_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 90.00 | 90.00 | 6.71 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | RETAIL_2_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 77.67 | 77.67 | 77.67 | 0.00 | 180.00 | 11.58 | 6.71 | 0.00 | BASEMENT_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
29 | RETAIL_2_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 155.34 | 155.34 | 155.34 | 0.00 | 90.00 | 155.34 | 1.00 | 0.00 | RETAIL_2_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
31 | MECH_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.738 | 0.664 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | MECH_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | MECH_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 180.00 | 90.00 | 15.85 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | MECH_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | MECH_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 164.24 | 164.24 | 164.24 | 0.00 | 180.00 | 15.85 | 10.36 | 0.00 | BASEMENT_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | MECH_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | MECH_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 328.49 | 328.49 | 328.49 | 0.00 | 90.00 | 328.49 | 1.00 | 0.00 | MECH_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | STORAGE_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.738 | 0.664 | 28.80 | 36.23 | 28.80 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | Door | STORAGE_FLR_1_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.198 | 1.198 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | STORAGE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
41 | STORAGE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 180.00 | 90.00 | 9.14 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
42 | STORAGE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | STORAGE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 94.76 | 94.76 | 94.76 | 0.00 | 180.00 | 9.14 | 10.36 | 0.00 | BASEMENT_CEILING_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
44 | STORAGE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | STORAGE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 189.52 | 189.52 | 189.52 | 0.00 | 90.00 | 189.52 | 1.00 | 0.00 | STORAGE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
46 | LAUNDRY_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.738 | 0.664 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | LAUNDRY_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.738 | 0.664 | 65.68 | 67.63 | 65.68 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | Door | LAUNDRY_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
49 | LAUNDRY_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 180.00 | 90.00 | 4.57 | 3.96 | 0.00 | CAFE_FLR_1_WALL_2_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | LAUNDRY_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 270.00 | 90.00 | 17.07 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
51 | LAUNDRY_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 78.04 | 78.04 | 78.04 | 0.00 | 180.00 | 4.57 | 17.07 | 0.00 | BASEMENT_CEILING_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
52 | LAUNDRY_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 156.08 | 156.08 | 156.08 | 0.00 | 90.00 | 156.08 | 1.00 | 0.00 | LAUNDRY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
54 | CAFE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.738 | 0.664 | 21.00 | 22.95 | 21.00 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CAFE_FLR_1_WALL_EAST_DOOR | Door | CAFE_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | CAFE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.738 | 0.664 | 63.73 | 129.23 | 63.73 | 180.00 | 90.00 | 32.61 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | Window | CAFE_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 65.50 | 65.50 | 65.50 | 180.00 | 90.00 | 30.75 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
58 | CAFE_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 0.00 | 90.00 | 28.04 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | CAFE_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | CAFE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | CAFE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 188.86 | 188.86 | 188.86 | 0.00 | 180.00 | 32.61 | 5.79 | 0.00 | BASEMENT_CEILING_6 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
62 | CAFE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 3.86E-002 | 0.96 | 4 | ||
63 | CAFE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 377.72 | 377.72 | 377.72 | 0.00 | 90.00 | 377.72 | 1.00 | 0.00 | CAFE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
64 | LOBBY_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.738 | 0.664 | 209.87 | 213.77 | 209.87 | 0.00 | 90.00 | 53.95 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
67 | LOBBY_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.738 | 0.664 | 12.08 | 12.08 | 12.08 | 0.00 | 90.00 | 3.05 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
68 | LOBBY_FLR_1_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.738 | 0.664 | 82.79 | 167.88 | 82.79 | 180.00 | 90.00 | 42.37 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | Window | LOBBY_FLR_1_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 85.08 | 85.08 | 85.08 | 180.00 | 90.00 | 39.95 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LOBBY_FLR_1_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.738 | 0.664 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | LOBBY_FLR_1_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | LOBBY_FLR_1_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 180.00 | 90.00 | 28.04 | 3.96 | 0.00 | CAFE_FLR_1_WALL_1_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | LOBBY_FLR_1_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | LOBBY_FLR_1_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | LOBBY_FLR_1_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | LOBBY_FLR_1_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | MECH_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | LOBBY_FLR_1_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
78 | LOBBY_FLR_1_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | LOBBY_FLR_1_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | CAFE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | LOBBY_FLR_1_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | LOBBY_FLR_1_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 180.00 | 32.99 | 32.99 | 0.00 | BASEMENT_CEILING_7 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
82 | LOBBY_FLR_1_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 219.63 | 219.63 | 219.63 | 90.00 | 180.00 | 14.82 | 14.82 | 0.00 | BASEMENT_CEILING_8 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
83 | LOBBY_FLR_1_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 1062.83 | 1062.83 | 1062.83 | 270.00 | 0.00 | 32.60 | 32.60 | 0.00 | LOBBY_FLR_1_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 10 | ||
84 | LOBBY_FLR_1_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 245.35 | 245.35 | 245.35 | 180.00 | 0.00 | 42.37 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.22E-003 | 1.00 | 4 | ||
85 | LOBBY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 2616.37 | 2616.37 | 2616.37 | 0.00 | 90.00 | 2616.37 | 1.00 | 0.00 | LOBBY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | ROOM_1_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.016 | 0.882 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | ROOM_1_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.016 | 0.882 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | Window | ROOM_1_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | ROOM_1_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | ROOM_1_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | ROOM_1_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
93 | ROOM_1_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
94 | ROOM_1_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
95 | ROOM_2_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.016 | 0.882 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
97 | ROOM_2_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.016 | 0.882 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | Window | ROOM_2_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | ROOM_2_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | ROOM_2_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | ROOM_2_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | ROOM_2_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | ROOM_2_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.016 | 0.882 | 7.47 | 11.15 | 7.47 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 3.68 | 3.68 | 3.68 | 180.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | ROOM_3_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 24.52 | 24.52 | 24.52 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
110 | ROOM_3_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 24.52 | 24.52 | 24.52 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.05 | 49.05 | 49.05 | 0.00 | 90.00 | 49.05 | 1.00 | 0.00 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.016 | 0.882 | 7.47 | 11.15 | 7.47 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_4_MULT19_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 3.68 | 3.68 | 3.68 | 0.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
117 | ROOM_4_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
118 | ROOM_4_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
120 | ROOM_5_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.016 | 0.882 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | Window | ROOM_5_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
122 | ROOM_5_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.016 | 0.882 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_5_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
124 | ROOM_5_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
125 | ROOM_5_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
126 | ROOM_5_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
127 | ROOM_5_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
128 | ROOM_5_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_5_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
129 | ROOM_6_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.016 | 0.882 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_6_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
131 | ROOM_6_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 1.016 | 0.882 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | Window | ROOM_6_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
133 | ROOM_6_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
134 | ROOM_6_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
135 | ROOM_6_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
136 | ROOM_6_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
137 | ROOM_6_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_6_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
138 | CORRIDOR_FLR_3_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.016 | 0.882 | 11.83 | 17.65 | 11.83 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 5.82 | 5.82 | 5.82 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.016 | 0.882 | 4.35 | 6.50 | 4.35 | 0.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 2.15 | 2.15 | 2.15 | 0.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.016 | 0.882 | 4.36 | 6.50 | 4.36 | 180.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 2.15 | 2.15 | 2.15 | 180.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.016 | 0.882 | 11.83 | 17.65 | 11.83 | 180.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 5.82 | 5.82 | 5.82 | 180.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 0.00 | 90.00 | 69.50 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | CORRIDOR_FLR_3_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | CORRIDOR_FLR_3_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORRIDOR_FLR_3_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | CORRIDOR_FLR_3_WALL_4_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 180.00 | 90.00 | 69.49 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
152 | CORRIDOR_FLR_3_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | CORRIDOR_FLR_3_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | CORRIDOR_FLR_3_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | CORRIDOR_FLR_3_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | CORRIDOR_FLR_3_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 74.32 | 74.32 | 74.32 | 180.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
157 | CORRIDOR_FLR_3_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 240.77 | 240.77 | 240.77 | 270.00 | 180.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | CORRIDOR_FLR_3_FLOOR_3 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 74.32 | 74.32 | 74.32 | 90.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
159 | CORRIDOR_FLR_3_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
160 | CORRIDOR_FLR_3_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 240.77 | 240.77 | 240.77 | 90.00 | 0.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
161 | CORRIDOR_FLR_3_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.196 | 0.189 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 778.81 | 778.81 | 778.81 | 0.00 | 90.00 | 778.81 | 1.00 | 0.00 | CORRIDOR_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
163 | ROOM_1_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.081 | 0.931 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
165 | ROOM_1_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.081 | 0.931 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | Window | ROOM_1_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
167 | ROOM_1_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
168 | ROOM_1_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
169 | ROOM_1_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | ROOM_1_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.228 | 0.219 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
171 | ROOM_1_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
172 | ROOM_2_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.081 | 0.931 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
174 | ROOM_2_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.081 | 0.931 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | Window | ROOM_2_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
176 | ROOM_2_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
177 | ROOM_2_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
178 | ROOM_2_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | ROOM_2_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.228 | 0.219 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
180 | ROOM_2_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 1.081 | 0.931 | 13.70 | 20.44 | 13.70 | 180.00 | 90.00 | 6.71 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 6.74 | 6.74 | 6.74 | 180.00 | 90.00 | 5.53 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 0.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 90.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | ROOM_3_MULT9_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 6.71 | 3.66 | 0.00 | ROOM_3_MULT9_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
187 | ROOM_3_MULT9_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.228 | 0.219 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 6.71 | 3.66 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
189 | BANQUET_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.081 | 0.931 | 65.36 | 97.55 | 65.36 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | Window | BANQUET_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 32.19 | 32.19 | 32.19 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
191 | BANQUET_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
192 | BANQUET_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
193 | BANQUET_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
194 | BANQUET_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | BANQUET_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
195 | BANQUET_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
196 | BANQUET_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | BANQUET_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
197 | DINING_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.081 | 0.931 | 65.36 | 97.55 | 65.36 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DINING_FLR_6_WALL_NORTH_WINDOW | Window | DINING_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 32.19 | 32.19 | 32.19 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
199 | DINING_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
200 | DINING_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | DINING_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DINING_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DINING_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | DINING_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
203 | DINING_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
204 | DINING_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | DINING_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
205 | KITCHEN_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.081 | 0.931 | 16.77 | 21.37 | 16.77 | 0.00 | 90.00 | 7.01 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | Window | KITCHEN_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
207 | KITCHEN_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.081 | 0.931 | 34.86 | 52.03 | 34.86 | 90.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | Window | KITCHEN_FLR_6_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 17.17 | 17.17 | 17.17 | 90.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.081 | 0.931 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | Window | KITCHEN_FLR_6_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 7.43 | 7.43 | 7.43 | 180.00 | 90.00 | 2.44 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
212 | KITCHEN_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | KITCHEN_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | KITCHEN_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 103.30 | 103.30 | 103.30 | 180.00 | 180.00 | 10.16 | 10.16 | 0.00 | KITCHEN_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
215 | KITCHEN_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 103.30 | 103.30 | 103.30 | 270.00 | 0.00 | 10.16 | 10.16 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
216 | KITCHEN_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 206.61 | 206.61 | 206.61 | 0.00 | 90.00 | 206.61 | 1.00 | 0.00 | KITCHEN_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
217 | CORRIDOR_FLR_6_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.081 | 0.931 | 11.83 | 17.65 | 11.83 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 5.82 | 5.82 | 5.82 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.081 | 0.931 | 10.58 | 15.79 | 10.58 | 0.00 | 90.00 | 5.18 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 5.21 | 5.21 | 5.21 | 0.00 | 90.00 | 4.27 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.081 | 0.931 | 34.86 | 52.03 | 34.86 | 180.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3856_SHGC_0.4 | N/A | 2.191 | No | 17.17 | 17.17 | 17.17 | 180.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
224 | CORRIDOR_FLR_6_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 104.98 | 104.98 | 104.98 | 0.00 | 90.00 | 34.44 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 183.95 | 183.95 | 183.95 | 180.00 | 90.00 | 60.35 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
226 | CORRIDOR_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
227 | CORRIDOR_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 40.88 | 40.88 | 40.88 | 270.00 | 90.00 | 13.41 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
228 | CORRIDOR_FLR_6_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
229 | CORRIDOR_FLR_6_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
230 | CORRIDOR_FLR_6_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
231 | CORRIDOR_FLR_6_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
232 | CORRIDOR_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.196 | 0.187 | 412.12 | 412.12 | 412.12 | 180.00 | 180.00 | 20.30 | 20.30 | 0.00 | CORRIDOR_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 12 | ||
233 | CORRIDOR_FLR_6_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 244.71 | 244.71 | 244.71 | 90.00 | 0.00 | 15.64 | 15.64 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 8 | ||
234 | CORRIDOR_FLR_6_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 167.42 | 167.42 | 167.42 | 270.00 | 0.00 | 12.94 | 12.94 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 824.25 | 824.25 | 824.25 | 0.00 | 90.00 | 824.25 | 1.00 | 0.00 | CORRIDOR_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 5.2623365258E-003 | 1.2711278802E-002 | Pass | Pass | 1.3154118037E-002 | 3.2912598172E-002 | Pass | Pass |
2 | RETAIL_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 2.8056424181E-003 | 2.2619808357E-003 | Pass | Pass | 0.1559146167 | 0.5709625185 | Pass | Pass |
3 | RETAIL_2_FLR_1 | RunPeriod: RUNPERIOD 1 | 1.5222009089E-003 | 1.1448392363E-003 | Pass | Pass | 2.1000204833E-002 | 3.9581332162E-002 | Pass | Pass |
4 | MECH_FLR_1 | RunPeriod: RUNPERIOD 1 | 8.7590414733E-004 | 6.3518476069E-004 | Pass | Pass | 5.0254054477E-002 | 8.8083112936E-002 | Pass | Pass |
5 | STORAGE_FLR_1 | RunPeriod: RUNPERIOD 1 | 7.3735640199E-004 | 5.8347698498E-004 | Pass | Pass | 0.3935060497 | 0.8727603337 | Pass | Pass |
6 | LAUNDRY_FLR_1 | RunPeriod: RUNPERIOD 1 | 4.5068532314E-002 | 0.1381091053 | Pass | Pass | 1.9182102397E-002 | 5.5559894979E-002 | Pass | Pass |
7 | CAFE_FLR_1 | RunPeriod: RUNPERIOD 1 | 3.8905976687E-003 | 6.1276763221E-003 | Pass | Pass | 2.8725664628E-002 | 5.0893171198E-002 | Pass | Pass |
8 | LOBBY_FLR_1 | RunPeriod: RUNPERIOD 1 | 1.6942172878E-003 | 1.3453041884E-003 | Pass | Pass | 2.0889470063E-002 | 4.2423677550E-002 | Pass | Pass |
9 | ROOM_1_FLR_3 | RunPeriod: RUNPERIOD 1 | 3.7671845067E-002 | 0.1321052577 | Pass | Pass | 7.6084375274 | 86.9806950726 | Pass | Pass |
10 | ROOM_2_FLR_3 | RunPeriod: RUNPERIOD 1 | 7.6198652059E-002 | 0.2297708712 | Pass | Pass | 0.3168847591 | 1.6927311196 | Pass | Pass |
11 | ROOM_3_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 2.0865844607E-002 | 3.8527408415E-002 | Pass | Pass | 3.2107522850E-002 | 6.5048796273E-002 | Pass | Pass |
12 | ROOM_4_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 1.7614097657E-002 | 6.4680758334E-002 | Pass | Pass | 0.1608308027 | 0.6767559376 | Pass | Pass |
13 | ROOM_5_FLR_3 | RunPeriod: RUNPERIOD 1 | 4.4836538050E-002 | 0.1255821579 | Pass | Pass | 0.1277388261 | 0.4728897339 | Pass | Pass |
14 | ROOM_6_FLR_3 | RunPeriod: RUNPERIOD 1 | 7.0007751814E-002 | 0.2209586244 | Pass | Pass | 0.4361486565 | 2.4164806535 | Pass | Pass |
15 | CORRIDOR_FLR_3 | RunPeriod: RUNPERIOD 1 | 6.3812172119E-004 | 4.8304849761E-004 | Pass | Pass | 3.9222876311E-002 | 6.5343668307E-002 | Pass | Pass |
16 | ROOM_1_FLR_6 | RunPeriod: RUNPERIOD 1 | 5.8641403791E-002 | 0.2071662096 | Pass | Pass | 0.2071434924 | 0.8419709962 | Pass | Pass |
17 | ROOM_2_FLR_6 | RunPeriod: RUNPERIOD 1 | 9.3757782771E-002 | 0.3051395688 | Pass | Pass | 0.3624285474 | 1.3362502124 | Pass | Pass |
18 | ROOM_3_MULT9_FLR_6 | RunPeriod: RUNPERIOD 1 | 4.8142350995E-002 | 0.2158637755 | Pass | Pass | 0.1899321171 | 0.6235026316 | Pass | Pass |
19 | BANQUET_FLR_6 | RunPeriod: RUNPERIOD 1 | 2.5483023527E-002 | 6.8920311564E-002 | Pass | Pass | 1.2170807723E-002 | 3.5743555358E-002 | Pass | Pass |
20 | DINING_FLR_6 | RunPeriod: RUNPERIOD 1 | 2.7620822775E-002 | 6.9168347657E-002 | Pass | Pass | 1.0992329383E-002 | 3.0770220901E-002 | Pass | Pass |
21 | KITCHEN_FLR_6 | RunPeriod: RUNPERIOD 1 | 7.1005009587E-002 | 0.1153196099 | Pass | Pass | 1.7397091246E-002 | 3.3094615395E-002 | Pass | Pass |
22 | CORRIDOR_FLR_6 | RunPeriod: RUNPERIOD 1 | 1.3178323339E-003 | 1.0752371982E-003 | Pass | Pass | 0.6048549036 | 2.0847357773 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:58:31
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 3443.26 | 127.23 | 1032.85 | 12281.91 | 2691.65 | 19576.92 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:58:31
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | -4.30 | 0.00 | -4.30 | Wetbulb [C] | 1.20 | 110.00 |
WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 26.40 | 9.10 | 17.00 | Wetbulb [C] | 2.10 | 90.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 42.00 | 35 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 40.00 | 22 | |||
Jun | 4.00 | 8 | |||
Jul | 5.00 | 4 | |||
Aug | 7.00 | 8 | |||
Sep | 17.00 | 10 | |||
Oct | 50.00 | 49 | |||
Nov | 69.00 | 59 | |||
Dec | 95.00 | 53 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:58:31
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.399 | 0.419 | 211.13 | 211.13 | 0.00 | 90.00 | N |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.399 | 0.419 | 55.76 | 55.76 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.399 | 0.419 | 211.13 | 211.13 | 180.00 | 90.00 | S |
BASEMENT_WALL_WEST | BASEMENT_WALL_WEST_CFACTOR | 1.00 | 0.399 | 0.419 | 55.76 | 55.76 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.664 | 0.738 | 45.89 | 22.63 | 180.00 | 90.00 | S |
RETAIL_1_FLR_1_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.664 | 0.738 | 22.95 | 22.95 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_CEILING | NONRES_ROOF | 0.23 | 0.221 | 0.228 | 67.07 | 67.07 | 180.00 | 0.00 | |
RETAIL_2_FLR_1_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.664 | 0.738 | 26.57 | 24.62 | 270.00 | 90.00 | W |
MECH_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.664 | 0.738 | 62.80 | 62.80 | 0.00 | 90.00 | N |
STORAGE_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.664 | 0.738 | 36.23 | 28.80 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.664 | 0.738 | 18.12 | 18.12 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.664 | 0.738 | 67.63 | 65.68 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.664 | 0.738 | 22.95 | 21.00 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.664 | 0.738 | 129.23 | 63.73 | 180.00 | 90.00 | S |
CAFE_FLR_1_CEILING | NONRES_ROOF | 0.23 | 0.221 | 0.228 | 188.86 | 188.86 | 180.00 | 0.00 | |
LOBBY_FLR_1_WALL_1_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.664 | 0.738 | 213.77 | 209.87 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_2_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.664 | 0.738 | 12.08 | 12.08 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.664 | 0.738 | 167.88 | 82.79 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_1_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.664 | 0.738 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_CEILING_2 | NONRES_ROOF | 0.23 | 0.221 | 0.228 | 245.35 | 245.35 | 180.00 | 0.00 | |
ROOM_1_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.882 | 1.016 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_1_FLR_3_WALL_WEST | RES_EXT_WALL_MID | 0.30 | 0.882 | 1.016 | 104.06 | 69.72 | 270.00 | 90.00 | W |
ROOM_2_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.882 | 1.016 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_2_FLR_3_WALL_WEST | RES_EXT_WALL_MID | 0.30 | 0.882 | 1.016 | 104.05 | 69.71 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.882 | 1.016 | 847.14 | 567.58 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.882 | 1.016 | 847.37 | 567.71 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_EAST | RES_EXT_WALL_MID | 0.30 | 0.882 | 1.016 | 104.06 | 69.72 | 90.00 | 90.00 | E |
ROOM_5_FLR_3_WALL_SOUTH | RES_EXT_WALL_MID | 0.30 | 0.882 | 1.016 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_NORTH | RES_EXT_WALL_MID | 0.30 | 0.882 | 1.016 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_6_FLR_3_WALL_EAST | RES_EXT_WALL_MID | 0.30 | 0.882 | 1.016 | 104.05 | 69.71 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_1_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.882 | 1.016 | 70.60 | 47.31 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_2_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.882 | 1.016 | 26.01 | 17.42 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.882 | 1.016 | 26.02 | 17.43 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_2_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.882 | 1.016 | 70.60 | 47.31 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_SOUTH | RES_EXT_WALL_TOP | 0.30 | 0.931 | 1.081 | 13.94 | 9.34 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_WEST | RES_EXT_WALL_TOP | 0.30 | 0.931 | 1.081 | 26.01 | 17.43 | 270.00 | 90.00 | W |
ROOM_1_FLR_6_CEILING | RES_ROOF | 0.23 | 0.221 | 0.228 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_2_FLR_6_WALL_NORTH | RES_EXT_WALL_TOP | 0.30 | 0.931 | 1.081 | 13.94 | 9.34 | 0.00 | 90.00 | N |
ROOM_2_FLR_6_WALL_WEST | RES_EXT_WALL_TOP | 0.30 | 0.931 | 1.081 | 26.01 | 17.43 | 270.00 | 90.00 | W |
ROOM_2_FLR_6_CEILING | RES_ROOF | 0.23 | 0.221 | 0.228 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | RES_EXT_WALL_TOP | 0.30 | 0.931 | 1.081 | 183.96 | 123.26 | 180.00 | 90.00 | S |
ROOM_3_MULT9_FLR_6_CEILING | RES_ROOF | 0.23 | 0.221 | 0.228 | 220.77 | 220.77 | 180.00 | 0.00 | |
BANQUET_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.931 | 1.081 | 97.55 | 65.36 | 0.00 | 90.00 | N |
BANQUET_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.221 | 0.228 | 331.66 | 331.66 | 180.00 | 0.00 | |
DINING_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.931 | 1.081 | 97.55 | 65.36 | 0.00 | 90.00 | N |
DINING_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.221 | 0.228 | 331.66 | 331.66 | 180.00 | 0.00 | |
KITCHEN_FLR_6_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.931 | 1.081 | 21.37 | 16.77 | 0.00 | 90.00 | N |
KITCHEN_FLR_6_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.931 | 1.081 | 52.03 | 34.86 | 90.00 | 90.00 | E |
KITCHEN_FLR_6_WALL_1_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.931 | 1.081 | 13.94 | 9.34 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.221 | 0.228 | 103.30 | 103.30 | 270.00 | 0.00 | |
CORRIDOR_FLR_6_WALL_1_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.931 | 1.081 | 17.65 | 11.83 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.931 | 1.081 | 15.79 | 10.58 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.931 | 1.081 | 52.03 | 34.86 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_CEILING_1 | NONRES_ROOF | 0.23 | 0.221 | 0.228 | 244.71 | 244.71 | 90.00 | 0.00 | |
CORRIDOR_FLR_6_CEILING_2 | NONRES_ROOF | 0.23 | 0.221 | 0.228 | 167.42 | 167.42 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_FLOOR | BASEMENT_FLOOR | 0.30 | 1.441 | 2.705 | 1978.83 | 1978.83 | 0.00 | 180.00 | |
BASEMENT_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.186 | 0.196 | 67.07 | 67.07 | 180.00 | 0.00 | |
BASEMENT_CEILING_2 | NONRES_FLOOR_CEILING | 0.30 | 0.186 | 0.196 | 77.67 | 77.67 | 180.00 | 0.00 | |
BASEMENT_CEILING_3 | NONRES_FLOOR_CEILING | 0.30 | 0.186 | 0.196 | 164.24 | 164.24 | 180.00 | 0.00 | |
BASEMENT_CEILING_4 | NONRES_FLOOR_CEILING | 0.30 | 0.186 | 0.196 | 94.76 | 94.76 | 180.00 | 0.00 | |
BASEMENT_CEILING_5 | NONRES_FLOOR_CEILING | 0.30 | 0.186 | 0.196 | 78.04 | 78.04 | 180.00 | 0.00 | |
BASEMENT_CEILING_6 | NONRES_FLOOR_CEILING | 0.30 | 0.186 | 0.196 | 188.86 | 188.86 | 180.00 | 0.00 | |
BASEMENT_CEILING_7 | NONRES_FLOOR_CEILING | 0.30 | 0.186 | 0.196 | 1088.56 | 1088.56 | 180.00 | 0.00 | |
BASEMENT_CEILING_8 | NONRES_FLOOR_CEILING | 0.30 | 0.186 | 0.196 | 219.63 | 219.63 | 90.00 | 0.00 | |
RETAIL_1_FLR_1_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 0.00 | 90.00 | N |
RETAIL_1_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 90.00 | 90.00 | E |
RETAIL_1_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.186 | 0.196 | 67.07 | 67.07 | 0.00 | 180.00 | |
RETAIL_2_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 180.00 | 90.00 | S |
RETAIL_2_FLR_1_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 0.00 | 90.00 | N |
RETAIL_2_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.57 | 26.57 | 90.00 | 90.00 | E |
RETAIL_2_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.186 | 0.196 | 77.67 | 77.67 | 0.00 | 180.00 | |
RETAIL_2_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 77.67 | 77.67 | 180.00 | 0.00 | |
MECH_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
MECH_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 62.80 | 62.80 | 180.00 | 90.00 | S |
MECH_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
MECH_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.186 | 0.196 | 164.24 | 164.24 | 0.00 | 180.00 | |
MECH_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 164.24 | 164.24 | 180.00 | 0.00 | |
STORAGE_FLR_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
STORAGE_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 36.23 | 36.23 | 180.00 | 90.00 | S |
STORAGE_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
STORAGE_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.186 | 0.196 | 94.76 | 94.76 | 0.00 | 180.00 | |
STORAGE_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 94.76 | 94.76 | 180.00 | 0.00 | |
LAUNDRY_FLR_1_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 18.12 | 18.12 | 180.00 | 90.00 | S |
LAUNDRY_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 67.63 | 67.63 | 270.00 | 90.00 | W |
LAUNDRY_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.186 | 0.196 | 78.04 | 78.04 | 0.00 | 180.00 | |
LAUNDRY_FLR_1_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 78.04 | 78.04 | 180.00 | 0.00 | |
CAFE_FLR_1_WALL_1_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.11 | 111.11 | 0.00 | 90.00 | N |
CAFE_FLR_1_WALL_2_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 18.12 | 18.12 | 0.00 | 90.00 | N |
CAFE_FLR_1_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 270.00 | 90.00 | W |
CAFE_FLR_1_FLOOR | NONRES_FLOOR | 0.30 | 0.186 | 0.196 | 188.86 | 188.86 | 0.00 | 180.00 | |
LOBBY_FLR_1_WALL_2_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 45.89 | 45.89 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_3_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.11 | 111.11 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.57 | 26.57 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_4_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 62.80 | 62.80 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_4_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 36.23 | 36.23 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 41.06 | 41.06 | 90.00 | 90.00 | E |
LOBBY_FLR_1_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 22.95 | 22.95 | 90.00 | 90.00 | E |
LOBBY_FLR_1_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 67.63 | 67.63 | 90.00 | 90.00 | E |
LOBBY_FLR_1_FLOOR_1 | NONRES_FLOOR | 0.30 | 0.186 | 0.196 | 1088.56 | 1088.56 | 180.00 | 180.00 | |
LOBBY_FLR_1_FLOOR_2 | NONRES_FLOOR | 0.30 | 0.186 | 0.196 | 219.63 | 219.63 | 90.00 | 180.00 | |
LOBBY_FLR_1_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 1062.83 | 1062.83 | 270.00 | 0.00 | |
ROOM_1_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 0.00 | 90.00 | N |
ROOM_1_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 90.00 | 90.00 | E |
ROOM_1_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 156.09 | 156.09 | 0.00 | 180.00 | |
ROOM_1_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 156.09 | 156.09 | 180.00 | 0.00 | |
ROOM_2_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 90.00 | 90.00 | E |
ROOM_2_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 180.00 | 90.00 | S |
ROOM_2_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 156.07 | 156.07 | 0.00 | 180.00 | |
ROOM_2_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 156.07 | 156.07 | 180.00 | 0.00 | |
ROOM_3_MULT19_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.14 | 847.14 | 0.00 | 90.00 | N |
ROOM_3_MULT19_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 90.00 | 90.00 | E |
ROOM_3_MULT19_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 1863.81 | 1863.81 | 0.00 | 180.00 | |
ROOM_3_MULT19_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 1863.81 | 1863.81 | 180.00 | 0.00 | |
ROOM_4_MULT19_FLR_3_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 90.00 | 90.00 | E |
ROOM_4_MULT19_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.37 | 847.37 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1553.43 | 1553.43 | 270.00 | 90.00 | W |
ROOM_4_MULT19_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 1864.32 | 1864.32 | 0.00 | 180.00 | |
ROOM_4_MULT19_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 1864.32 | 1864.32 | 180.00 | 0.00 | |
ROOM_5_FLR_3_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 270.00 | 90.00 | W |
ROOM_5_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 156.09 | 156.09 | 0.00 | 180.00 | |
ROOM_5_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 156.09 | 156.09 | 180.00 | 0.00 | |
ROOM_6_FLR_3_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 55.74 | 55.74 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 270.00 | 90.00 | W |
ROOM_6_FLR_3_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 156.07 | 156.07 | 0.00 | 180.00 | |
ROOM_6_FLR_3_CEILING | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 156.07 | 156.07 | 180.00 | 0.00 | |
CORRIDOR_FLR_3_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.28 | 847.28 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_4_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_3_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 847.27 | 847.27 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 81.76 | 81.76 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.06 | 104.06 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_WALL_4_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 104.05 | 104.05 | 270.00 | 90.00 | W |
CORRIDOR_FLR_3_FLOOR_1 | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 297.29 | 297.29 | 180.00 | 180.00 | |
CORRIDOR_FLR_3_FLOOR_2 | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 963.06 | 963.06 | 270.00 | 180.00 | |
CORRIDOR_FLR_3_FLOOR_3 | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 297.26 | 297.26 | 90.00 | 180.00 | |
CORRIDOR_FLR_3_CEILING_1 | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 297.29 | 297.29 | 90.00 | 0.00 | |
CORRIDOR_FLR_3_CEILING_2 | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 963.06 | 963.06 | 90.00 | 0.00 | |
CORRIDOR_FLR_3_CEILING_3 | NONRES_FLOOR_CEILING | 0.30 | 0.188 | 0.196 | 297.26 | 297.26 | 90.00 | 0.00 | |
ROOM_1_FLR_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 13.94 | 13.94 | 0.00 | 90.00 | N |
ROOM_1_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.01 | 26.01 | 90.00 | 90.00 | E |
ROOM_1_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 39.02 | 39.02 | 0.00 | 180.00 | |
ROOM_2_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 26.01 | 26.01 | 90.00 | 90.00 | E |
ROOM_2_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 13.94 | 13.94 | 180.00 | 90.00 | S |
ROOM_2_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 39.02 | 39.02 | 0.00 | 180.00 | |
ROOM_3_MULT9_FLR_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 183.96 | 183.96 | 0.00 | 90.00 | N |
ROOM_3_MULT9_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 100.35 | 100.35 | 90.00 | 90.00 | E |
ROOM_3_MULT9_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 100.35 | 100.35 | 270.00 | 90.00 | W |
ROOM_3_MULT9_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 220.77 | 220.77 | 0.00 | 180.00 | |
BANQUET_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
BANQUET_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 180.00 | 90.00 | S |
BANQUET_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
BANQUET_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 331.66 | 331.66 | 0.00 | 180.00 | |
DINING_FLR_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
DINING_FLR_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 180.00 | 90.00 | S |
DINING_FLR_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
DINING_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 331.66 | 331.66 | 0.00 | 180.00 | |
KITCHEN_FLR_6_WALL_2_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 7.43 | 7.43 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 20.44 | 20.44 | 270.00 | 90.00 | W |
KITCHEN_FLR_6_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
KITCHEN_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 103.30 | 103.30 | 180.00 | 180.00 | |
CORRIDOR_FLR_6_WALL_3_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 97.55 | 97.55 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_4_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 104.98 | 104.98 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_1_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 183.95 | 183.95 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_WALL_1_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 11.15 | 11.15 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_2_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 40.88 | 40.88 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_3_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 270.00 | 90.00 | W |
CORRIDOR_FLR_6_WALL_1_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_WALL_2_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 31.59 | 31.59 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_WALL_3_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 20.44 | 20.44 | 90.00 | 90.00 | E |
CORRIDOR_FLR_6_FLOOR | NONRES_FLOOR | 0.30 | 0.185 | 0.196 | 412.12 | 412.12 | 180.00 | 180.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3957.66 | 0.00 | 90.00 | N | ||
RETAIL_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 134.14 | 0.00 | 90.00 | N | ||
RETAIL_2_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 155.34 | 0.00 | 90.00 | N | ||
MECH_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 328.49 | 0.00 | 90.00 | N | ||
STORAGE_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 189.52 | 0.00 | 90.00 | N | ||
LAUNDRY_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 156.08 | 0.00 | 90.00 | N | ||
CAFE_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 377.72 | 0.00 | 90.00 | N | ||
LOBBY_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 2616.37 | 0.00 | 90.00 | N | ||
ROOM_1_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.18 | 0.00 | 90.00 | N | ||
ROOM_2_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.14 | 0.00 | 90.00 | N | ||
ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3727.63 | 0.00 | 90.00 | N | ||
ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3728.64 | 0.00 | 90.00 | N | ||
ROOM_5_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.18 | 0.00 | 90.00 | N | ||
ROOM_6_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 312.14 | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 3115.24 | 0.00 | 90.00 | N | ||
ROOM_1_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 78.04 | 0.00 | 90.00 | N | ||
ROOM_2_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 78.03 | 0.00 | 90.00 | N | ||
ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 441.55 | 0.00 | 90.00 | N | ||
BANQUET_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 663.31 | 0.00 | 90.00 | N | ||
DINING_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 663.31 | 0.00 | 90.00 | N | ||
KITCHEN_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 206.61 | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 824.25 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.3856_SHGC_0.4 | 23.26 | 0.00 | 0.00 | 23.26 | 23.26 | 2.191 | 0.401 | 0.402 | No | RETAIL_1_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
CAFE_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.3856_SHGC_0.4 | 65.50 | 0.00 | 0.00 | 65.50 | 65.50 | 2.191 | 0.401 | 0.402 | No | CAFE_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
LOBBY_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.3856_SHGC_0.4 | 85.08 | 0.00 | 0.00 | 85.08 | 85.08 | 2.191 | 0.401 | 0.402 | No | LOBBY_FLR_1_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.3856_SHGC_0.4 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.191 | 0.401 | 0.402 | No | ROOM_1_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.3856_SHGC_0.4 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.191 | 0.401 | 0.402 | No | ROOM_1_FLR_3_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_2_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.3856_SHGC_0.4 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.191 | 0.401 | 0.402 | No | ROOM_2_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_2_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.3856_SHGC_0.4 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.191 | 0.401 | 0.402 | No | ROOM_2_FLR_3_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.3856_SHGC_0.4 | 3.68 | 0.00 | 0.00 | 3.68 | 279.56 | 2.191 | 0.401 | 0.402 | No | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.3856_SHGC_0.4 | 3.68 | 0.00 | 0.00 | 3.68 | 279.65 | 2.191 | 0.401 | 0.402 | No | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_5_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.3856_SHGC_0.4 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.191 | 0.401 | 0.402 | No | ROOM_5_FLR_3_WALL_EAST | 90.00 | 90.00 | E | |||||||
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.3856_SHGC_0.4 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.191 | 0.401 | 0.402 | No | ROOM_5_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_6_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.3856_SHGC_0.4 | 4.60 | 0.00 | 0.00 | 4.60 | 18.40 | 2.191 | 0.401 | 0.402 | No | ROOM_6_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_6_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.3856_SHGC_0.4 | 8.58 | 0.00 | 0.00 | 8.58 | 34.34 | 2.191 | 0.401 | 0.402 | No | ROOM_6_FLR_3_WALL_EAST | 90.00 | 90.00 | E | |||||||
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.3856_SHGC_0.4 | 5.82 | 0.00 | 0.00 | 5.82 | 23.30 | 2.191 | 0.401 | 0.402 | No | CORRIDOR_FLR_3_WALL_1_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.3856_SHGC_0.4 | 2.15 | 0.00 | 0.00 | 2.15 | 8.59 | 2.191 | 0.401 | 0.402 | No | CORRIDOR_FLR_3_WALL_2_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.3856_SHGC_0.4 | 2.15 | 0.00 | 0.00 | 2.15 | 8.58 | 2.191 | 0.401 | 0.402 | No | CORRIDOR_FLR_3_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.3856_SHGC_0.4 | 5.82 | 0.00 | 0.00 | 5.82 | 23.30 | 2.191 | 0.401 | 0.402 | No | CORRIDOR_FLR_3_WALL_2_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.3856_SHGC_0.4 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.191 | 0.401 | 0.402 | No | ROOM_1_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
ROOM_1_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.3856_SHGC_0.4 | 8.58 | 0.00 | 0.00 | 8.58 | 8.58 | 2.191 | 0.401 | 0.402 | No | ROOM_1_FLR_6_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_2_FLR_6_WALL_NORTH_WINDOW | RESWINDOW_U_0.3856_SHGC_0.4 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.191 | 0.401 | 0.402 | No | ROOM_2_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
ROOM_2_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.3856_SHGC_0.4 | 8.58 | 0.00 | 0.00 | 8.58 | 8.58 | 2.191 | 0.401 | 0.402 | No | ROOM_2_FLR_6_WALL_WEST | 270.00 | 90.00 | W | |||||||
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.3856_SHGC_0.4 | 6.74 | 0.00 | 0.00 | 6.74 | 60.70 | 2.191 | 0.401 | 0.402 | No | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
BANQUET_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.3856_SHGC_0.4 | 32.19 | 0.00 | 0.00 | 32.19 | 32.19 | 2.191 | 0.401 | 0.402 | No | BANQUET_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
DINING_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.3856_SHGC_0.4 | 32.19 | 0.00 | 0.00 | 32.19 | 32.19 | 2.191 | 0.401 | 0.402 | No | DINING_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
KITCHEN_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.3856_SHGC_0.4 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.191 | 0.401 | 0.402 | No | KITCHEN_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | |||||||
KITCHEN_FLR_6_WALL_EAST_WINDOW | NONRESWINDOW_U_0.3856_SHGC_0.4 | 17.17 | 0.00 | 0.00 | 17.17 | 17.17 | 2.191 | 0.401 | 0.402 | No | KITCHEN_FLR_6_WALL_EAST | 90.00 | 90.00 | E | |||||||
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.3856_SHGC_0.4 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.191 | 0.401 | 0.402 | No | KITCHEN_FLR_6_WALL_1_SOUTH | 180.00 | 90.00 | S | |||||||
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.3856_SHGC_0.4 | 5.82 | 0.00 | 0.00 | 5.82 | 5.82 | 2.191 | 0.401 | 0.402 | No | CORRIDOR_FLR_6_WALL_1_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.3856_SHGC_0.4 | 5.21 | 0.00 | 0.00 | 5.21 | 5.21 | 2.191 | 0.401 | 0.402 | No | CORRIDOR_FLR_6_WALL_2_NORTH | 0.00 | 90.00 | N | |||||||
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.3856_SHGC_0.4 | 17.17 | 0.00 | 0.00 | 17.17 | 17.17 | 2.191 | 0.401 | 0.402 | No | CORRIDOR_FLR_6_WALL_2_SOUTH | 180.00 | 90.00 | S | |||||||
Total or Average | 1213.79 | 2.191 | 0.401 | 0.402 | |||||||||||||||||
North Total or Average | 432.95 | 2.191 | 0.401 | 0.402 | |||||||||||||||||
Non-North Total or Average | 780.84 | 2.191 | 0.401 | 0.402 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
RETAIL_2_FLR_1_WALL_WEST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | RETAIL_2_FLR_1_WALL_WEST |
STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | OVERHEAD DOOR_CON | 1.016 | 1.198 | 7.43 | STORAGE_FLR_1_WALL_NORTH |
LAUNDRY_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | LAUNDRY_FLR_1_WALL_EAST |
CAFE_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | CAFE_FLR_1_WALL_EAST |
LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:58:31
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CAFE_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LOBBY_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
BANQUET_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:58:31
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 8.7495 | 1978.83 | 17313.73 | LightsWired | LTG_SCH_BASEMENT | 50.91 | 168.00 | 50.86 | 0.0000 | Y | 165.29 |
RETAIL_1_FLR_1_LIGHTS | RETAIL_1_FLR_1 | RETAIL_1_FLR_1 | GENERAL | 13.0124 | 67.07 | 872.76 | LightsWired | LTG_SCH_RETAIL | 51.36 | 168.00 | 51.30 | 0.0000 | Y | 8.40 |
RETAIL_2_FLR_1_LIGHTS | RETAIL_2_FLR_1 | RETAIL_2_FLR_1 | GENERAL | 13.0124 | 77.67 | 1010.66 | LightsWired | LTG_SCH_RETAIL | 51.36 | 168.00 | 51.30 | 0.0000 | Y | 9.73 |
MECH_FLR_1_LIGHTS | MECH_FLR_1 | MECH_FLR_1 | GENERAL | 10.0642 | 164.24 | 1652.98 | LightsWired | LTG_SCH_MECHANIC | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 18.19 |
STORAGE_FLR_1_LIGHTS | STORAGE_FLR_1 | STORAGE_FLR_1 | GENERAL | 7.3195 | 94.76 | 693.59 | LightsWired | LTG_SCH_STORAGE | 25.68 | 168.00 | 25.65 | 0.0000 | Y | 3.34 |
LAUNDRY_FLR_1_LIGHTS | LAUNDRY_FLR_1 | LAUNDRY_FLR_1 | GENERAL | 5.4896 | 78.04 | 428.40 | LightsWired | LTG_SCH_LAUNDRY | 51.36 | 168.00 | 51.30 | 0.0000 | Y | 4.13 |
CAFE_FLR_1_LIGHTS | CAFE_FLR_1 | CAFE_FLR_1 | GENERAL | 12.8090 | 188.86 | 2419.14 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 26.62 |
LOBBY_FLR_1_LIGHTS | LOBBY_FLR_1 | LOBBY_FLR_1 | GENERAL | 10.0642 | 1308.19 | 13165.91 | LightsWired | LTG_SCH_LOBBY | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 144.89 |
ROOM_1_FLR_3_LIGHTS | ROOM_1_FLR_3 | ROOM_1_FLR_3 | GENERAL | 10.0642 | 156.09 | 1570.91 | LightsWired | LTG_SCH_GUESTROOM | 69.03 | 168.00 | 69.21 | 0.0000 | Y | 20.41 |
ROOM_2_FLR_3_LIGHTS | ROOM_2_FLR_3 | ROOM_2_FLR_3 | GENERAL | 10.0642 | 156.07 | 1570.72 | LightsWired | LTG_SCH_GUESTROOM | 69.03 | 168.00 | 69.21 | 0.0000 | Y | 20.41 |
ROOM_3_MULT19_FLR_3_LIGHTS | ROOM_3_MULT19_FLR_3 | ROOM_3_MULT19_FLR_3 | GENERAL | 10.0642 | 1863.81 | 18757.86 | LightsWired | LTG_SCH_GUESTROOM | 69.03 | 168.00 | 69.21 | 0.0000 | Y | 243.70 |
ROOM_4_MULT19_FLR_3_LIGHTS | ROOM_4_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | GENERAL | 10.0642 | 1864.32 | 18762.99 | LightsWired | LTG_SCH_GUESTROOM | 69.03 | 168.00 | 69.21 | 0.0000 | Y | 243.77 |
ROOM_5_FLR_3_LIGHTS | ROOM_5_FLR_3 | ROOM_5_FLR_3 | GENERAL | 10.0642 | 156.09 | 1570.91 | LightsWired | LTG_SCH_GUESTROOM | 69.03 | 168.00 | 69.21 | 0.0000 | Y | 20.41 |
ROOM_6_FLR_3_LIGHTS | ROOM_6_FLR_3 | ROOM_6_FLR_3 | GENERAL | 10.0642 | 156.07 | 1570.72 | LightsWired | LTG_SCH_GUESTROOM | 69.03 | 168.00 | 69.21 | 0.0000 | Y | 20.41 |
CORRIDOR_FLR_3_LIGHTS | CORRIDOR_FLR_3 | CORRIDOR_FLR_3 | GENERAL | 3.6597 | 1557.62 | 5700.46 | LightsWired | LTG_SCH_CORRIDOR | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 62.73 |
ROOM_1_FLR_6_LIGHTS | ROOM_1_FLR_6 | ROOM_1_FLR_6 | GENERAL | 10.0642 | 39.02 | 392.73 | LightsWired | LTG_SCH_GUESTROOM | 69.03 | 168.00 | 69.21 | 0.0000 | Y | 5.10 |
ROOM_2_FLR_6_LIGHTS | ROOM_2_FLR_6 | ROOM_2_FLR_6 | GENERAL | 10.0642 | 39.02 | 392.68 | LightsWired | LTG_SCH_GUESTROOM | 69.03 | 168.00 | 69.21 | 0.0000 | Y | 5.10 |
ROOM_3_MULT9_FLR_6_LIGHTS | ROOM_3_MULT9_FLR_6 | ROOM_3_MULT9_FLR_6 | GENERAL | 10.0642 | 220.77 | 2221.93 | LightsWired | LTG_SCH_GUESTROOM | 69.03 | 168.00 | 69.21 | 0.0000 | Y | 28.87 |
BANQUET_FLR_6_LIGHTS | BANQUET_FLR_6 | BANQUET_FLR_6 | GENERAL | 12.8090 | 331.66 | 4248.21 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 46.75 |
DINING_FLR_6_LIGHTS | DINING_FLR_6 | DINING_FLR_6 | GENERAL | 12.8090 | 331.66 | 4248.21 | LightsWired | LTG_SCH_DINING | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 46.75 |
KITCHEN_FLR_6_LIGHTS | KITCHEN_FLR_6 | KITCHEN_FLR_6 | GENERAL | 10.9792 | 103.30 | 1134.20 | LightsWired | LTG_SCH_KITCHEN | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 12.48 |
CORRIDOR_FLR_6_LIGHTS | CORRIDOR_FLR_6 | CORRIDOR_FLR_6 | GENERAL | 3.6597 | 412.12 | 1508.26 | LightsWired | LTG_SCH_CORRIDOR | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 16.60 |
Interior Lighting Total | 8.9207 | 11345.29 | 101207.97 | 559.10 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR FACADE LIGHTING | 16690.39 | AstronomicalClock | - | 83.54 | 83.54 | 261.73 | |
Exterior Lighting Total | 16690.39 | 261.73 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:58:31
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
HEATSYS1 BOILER | Boiler:HotWater | 449889.21 | 0.80 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:EIR | 723021.47 | 2.80 | 723148.56 | 2.80 | 3.72 | 12.68 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 14904.39 | 21584.43 | 17086.44 | 4498.00 | 0.79 | - | 2416.78 | 24.51 |
ROOM_2_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 13348.44 | 19319.28 | 15287.11 | 4032.16 | 0.79 | - | 2162.93 | 21.94 |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 106772.85 | 155426.92 | 123471.76 | 31955.16 | 0.79 | - | 17415.74 | 176.64 |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 72071.16 | 102646.17 | 80387.06 | 22259.10 | 0.78 | - | 11464.82 | 116.28 |
ROOM_5_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 13553.81 | 19618.16 | 15524.48 | 4093.68 | 0.79 | - | 2196.43 | 22.28 |
ROOM_6_FLR_3 FAN COIL COOLING COIL | Coil:Cooling:Water | 12238.77 | 17704.01 | 14004.14 | 3699.87 | 0.79 | - | 1981.92 | 20.10 |
ROOM_1_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 3988.37 | 5777.92 | 4574.90 | 1203.02 | 0.79 | - | 646.98 | 6.56 |
ROOM_2_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 3547.63 | 5136.26 | 4065.18 | 1071.08 | 0.79 | - | 575.07 | 5.83 |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | Coil:Cooling:Water | 22293.24 | 32192.73 | 25435.98 | 6756.75 | 0.79 | - | 3602.88 | 36.54 |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | 423570.84 | 530774.70 | 378834.66 | 151940.04 | 0.71 | - | 65136.51 | 660.65 |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | 36112.10 | 45302.65 | 32936.56 | 12366.09 | 0.73 | - | 5220.86 | 52.95 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
BASEMENT VAV BOX REHEAT COIL | Coil:Heating:Water | 14327.12 | 14400.77 | - |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 4825.41 | 4848.88 | - |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1993.71 | 2003.71 | - |
MECH_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 2551.24 | 2563.47 | - |
STORAGE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1434.23 | 1440.98 | - |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 18849.13 | 18946.06 | - |
CAFE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 15718.65 | 15797.50 | - |
LOBBY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 40686.71 | 40891.79 | - |
ROOM_1_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 5188.67 | 5588.77 | - |
ROOM_2_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 5194.32 | 5594.86 | - |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 29731.12 | 32023.54 | - |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 29853.37 | 32155.20 | - |
ROOM_5_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 5176.67 | 5575.85 | - |
ROOM_6_FLR_3 FAN COIL HEATING COIL | Coil:Heating:Water | 5182.33 | 5581.95 | - |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 14547.38 | 14617.01 | - |
ROOM_1_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 1653.18 | 1780.60 | - |
ROOM_2_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 1654.61 | 1782.13 | - |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | Coil:Heating:Water | 7974.44 | 8589.02 | - |
BANQUET_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 17055.32 | 17141.36 | - |
DINING_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 17714.73 | 17804.16 | - |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 12886.51 | 12952.89 | - |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 10065.78 | 10113.20 | - |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | 170153.31 | 129454.91 | - |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | 15471.26 | 11770.74 | - |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
LAUNDRY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 0.16 | 125.00 | 0.24 | 184.35 | 781.25 | 1.00 | 1.15 | General | ||
LOBBY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | General | |||
ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.16 | 270.90 | 1.24 | 2107.83 | 1693.12 | 1.00 | 0.48 | General | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 16:40:00 |
ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.16 | 270.90 | 1.11 | 1884.60 | 1693.12 | 1.00 | 0.49 | General | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 |
ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.16 | 270.90 | 9.05 | 15321.65 | 1693.12 | 1.00 | 0.39 | General | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 |
ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.16 | 270.90 | 5.75 | 9741.33 | 1693.12 | 1.00 | 0.40 | General | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 |
ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.16 | 270.90 | 1.13 | 1914.04 | 1693.12 | 1.00 | 0.49 | General | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 |
ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.16 | 270.90 | 1.02 | 1725.45 | 1693.12 | 1.00 | 0.50 | General | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:10:00 |
ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.16 | 270.90 | 0.33 | 564.59 | 1693.12 | 1.00 | 0.68 | General | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 |
ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.16 | 270.90 | 0.30 | 501.34 | 1693.12 | 1.00 | 0.72 | General | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 |
ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.16 | 270.90 | 1.85 | 3128.09 | 1693.12 | 1.00 | 0.45 | General | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 |
BANQUET_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | General | |||
DINING_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | General | |||
KITCHEN_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 0.16 | 125.00 | 1.89 | 1474.84 | 781.25 | 1.00 | 0.62 | General | ||
VAV WITH REHEAT FAN | Fan:VariableVolume | 0.62 | 1389.42 | 22.56 | 50549.79 | 2240.64 | 1.00 | 1.11 | General | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 19:20:00 |
FLR_3_DOAS FAN | Fan:ConstantVolume | 0.58 | 622.50 | 2.05 | 2194.93 | 1070.05 | 1.00 | 1.30 | General | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 133527.72 | 0.025802 | 5316.91 | 206062.94 | 0.90 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.003936 | 1185.30 | 301156.09 | 0.90 | General |
COOLSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 92445.74 | 0.025802 | 3681.07 | 142664.32 | 0.90 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000375 | 47.91 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWH BOOSTER E WATER HEATER | WaterHeater:Mixed | 0.02 | 8000.00 | 1.00 | 1.24 | 1.15 |
SWH LAUNDRY G WATER HEATER | WaterHeater:Mixed | 1.14 | 163316.00 | 0.80 | 0.58 | 0.51 |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 2.27 | 175842.60 | 0.80 | 0.26 | 0.03 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:58:31
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 33765.32 | 33765.32 | 17.06 | 2.480 | 2.480 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | 24.00 | 24.00 | 0.00921 | 23.31 | 0.00840 | 0.854 | 0.00 |
RETAIL_1_FLR_1 | 6466.56 | 6466.56 | 96.41 | 0.475 | 0.475 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 24.00 | 24.00 | 0.00887 | 26.17 | 0.00841 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 3233.46 | 3233.46 | 41.63 | 0.237 | 0.237 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 | 24.00 | 24.00 | 0.00936 | 26.22 | 0.00841 | 0.092 | 0.00 |
MECH_FLR_1 | 3034.80 | 3034.80 | 18.48 | 0.223 | 0.223 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 24.00 | 24.00 | 0.00869 | 26.31 | 0.00841 | 0.000 | 0.00 |
STORAGE_FLR_1 | 1490.10 | 1490.10 | 15.73 | 0.109 | 0.109 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 24.00 | 24.00 | 0.00879 | 26.40 | 0.00841 | 0.058 | 0.00 |
LAUNDRY_FLR_1 | 44695.52 | 44695.52 | 572.73 | 3.282 | 3.282 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 24.00 | 24.00 | 0.00854 | 26.40 | 0.00841 | 0.000 | 0.00 |
CAFE_FLR_1 | 25469.38 | 25469.38 | 134.86 | 1.872 | 1.872 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 24.00 | 23.99 | 0.00975 | 26.17 | 0.00841 | 0.676 | 0.00 |
LOBBY_FLR_1 | 70309.15 | 70309.15 | 53.75 | 5.165 | 5.165 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 24.00 | 23.99 | 0.00984 | 26.25 | 0.00841 | 1.894 | 0.00 |
ROOM_1_FLR_3 | 12580.64 | 12580.64 | 322.40 | 1.245 | 1.245 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 16:40:00 | 21.11 | 21.11 | 0.00856 | 25.37 | 0.00841 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 11248.27 | 11248.27 | 288.29 | 1.113 | 1.113 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 21.11 | 21.11 | 0.00856 | 25.13 | 0.00841 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 91451.40 | 91451.40 | 3729.08 | 9.049 | 9.049 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 21.11 | 21.11 | 0.00850 | 26.17 | 0.00841 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 58139.33 | 58139.33 | 2370.08 | 5.753 | 5.753 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 21.11 | 21.11 | 0.00874 | 26.40 | 0.00841 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 11423.98 | 11423.98 | 292.76 | 1.130 | 1.130 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 21.11 | 21.11 | 0.00856 | 22.94 | 0.00840 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 10298.39 | 10298.39 | 263.94 | 1.019 | 1.019 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:10:00 | 21.11 | 21.11 | 0.00857 | 21.65 | 0.00840 | 0.062 | 0.00 |
CORRIDOR_FLR_3 | 17037.07 | 17037.07 | 43.75 | 1.251 | 1.251 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:10:00 | 24.00 | 24.00 | 0.00961 | 26.40 | 0.00841 | 0.475 | 0.00 |
ROOM_1_FLR_6 | 3369.74 | 3369.74 | 86.35 | 0.333 | 0.333 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 21.11 | 21.11 | 0.00855 | 25.49 | 0.00841 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 2992.28 | 2992.28 | 76.69 | 0.296 | 0.296 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 21.11 | 21.11 | 0.00856 | 25.13 | 0.00841 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 18669.63 | 18669.63 | 761.08 | 1.848 | 1.848 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 21.11 | 21.11 | 0.00859 | 26.25 | 0.00841 | 0.099 | 0.00 |
BANQUET_FLR_6 | 29819.49 | 29819.49 | 89.91 | 2.193 | 2.193 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 24.00 | 23.99 | 0.01038 | 26.40 | 0.00841 | 1.188 | 0.00 |
DINING_FLR_6 | 31280.59 | 31280.59 | 94.32 | 2.300 | 2.300 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:20:00 | 24.00 | 23.99 | 0.01029 | 26.40 | 0.00841 | 1.188 | 0.00 |
KITCHEN_FLR_6 | 31445.53 | 31445.53 | 304.40 | 2.315 | 2.315 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 12:30:00 | 24.00 | 23.97 | 0.01004 | 25.58 | 0.00841 | 0.367 | 0.00 |
CORRIDOR_FLR_6 | 10501.11 | 10501.11 | 25.48 | 0.771 | 0.771 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 24.00 | 24.00 | 0.00897 | 26.40 | 0.00841 | 0.126 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 1439.65 | 1439.65 | 0.73 | 0.062 | 0.854 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00795 | -4.30 | 0.00266 | 0.854 | 0.00 |
RETAIL_1_FLR_1 | 2359.53 | 2359.53 | 35.18 | 0.102 | 0.102 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | 21.00 | 21.00 | 0.00750 | -4.30 | 0.00266 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 760.71 | 760.71 | 9.79 | 0.033 | 0.092 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00741 | -4.30 | 0.00266 | 0.092 | 0.00 |
MECH_FLR_1 | 1394.56 | 1394.56 | 8.49 | 0.060 | 0.060 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00726 | -4.30 | 0.00266 | 0.000 | 0.00 |
STORAGE_FLR_1 | 866.24 | 866.24 | 9.14 | 0.038 | 0.058 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00731 | -4.30 | 0.00266 | 0.058 | 0.00 |
LAUNDRY_FLR_1 | 1815.44 | 1815.44 | 23.26 | 0.079 | 0.079 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | 21.00 | 21.00 | 0.00723 | -4.30 | 0.00266 | 0.000 | 0.00 |
CAFE_FLR_1 | 5997.44 | 5997.44 | 31.76 | 0.260 | 0.676 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | 21.00 | 21.00 | 0.00756 | -4.30 | 0.00266 | 0.676 | 0.00 |
LOBBY_FLR_1 | 13866.24 | 13866.24 | 10.60 | 0.601 | 1.894 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00746 | -4.30 | 0.00266 | 1.894 | 0.00 |
ROOM_1_FLR_3 | 5188.66 | 5188.66 | 132.97 | 0.226 | 0.226 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | 21.11 | 21.11 | 0.00747 | -4.30 | 0.00266 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 5194.32 | 5194.32 | 133.13 | 0.226 | 0.226 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | 21.11 | 21.11 | 0.00747 | -4.30 | 0.00266 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 29731.11 | 29731.11 | 1212.33 | 1.296 | 1.296 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | 21.11 | 21.11 | 0.00751 | -4.30 | 0.00266 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 29853.36 | 29853.36 | 1216.99 | 1.301 | 1.301 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | 21.11 | 21.11 | 0.00751 | -4.30 | 0.00266 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 5176.67 | 5176.67 | 132.66 | 0.226 | 0.226 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | 21.11 | 21.11 | 0.00747 | -4.30 | 0.00266 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 5182.33 | 5182.33 | 132.82 | 0.226 | 0.226 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | 21.11 | 21.11 | 0.00747 | -4.30 | 0.00266 | 0.062 | 0.00 |
CORRIDOR_FLR_3 | 8049.47 | 8049.47 | 20.67 | 0.349 | 0.475 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | 21.00 | 21.00 | 0.00758 | -4.30 | 0.00266 | 0.475 | 0.00 |
ROOM_1_FLR_6 | 1653.18 | 1653.18 | 42.37 | 0.072 | 0.072 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | 21.11 | 21.11 | 0.00758 | -4.30 | 0.00266 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 1654.61 | 1654.61 | 42.41 | 0.072 | 0.072 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | 21.11 | 21.11 | 0.00758 | -4.30 | 0.00266 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 7974.44 | 7974.44 | 325.08 | 0.347 | 0.347 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | 21.11 | 21.11 | 0.00760 | -4.30 | 0.00266 | 0.099 | 0.00 |
BANQUET_FLR_6 | 5666.38 | 5666.38 | 17.09 | 0.245 | 1.188 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | 21.00 | 21.00 | 0.00769 | -4.30 | 0.00266 | 1.188 | 0.00 |
DINING_FLR_6 | 5767.95 | 5767.95 | 17.39 | 0.250 | 1.188 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 19:20:00 | 21.00 | 21.00 | 0.00770 | -4.30 | 0.00266 | 1.188 | 0.00 |
KITCHEN_FLR_6 | 937.60 | 937.60 | 9.08 | 0.041 | 0.367 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | 21.00 | 21.00 | 0.00467 | -4.30 | 0.00266 | 0.367 | 0.00 |
CORRIDOR_FLR_6 | 6059.60 | 6059.60 | 14.70 | 0.263 | 0.263 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 19:20:00 | 21.00 | 21.00 | 0.00774 | -4.30 | 0.00266 | 0.126 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV WITH REHEAT | 22.56 | 22.56 | 7.30 | 7.30 | 22.5604 | 22.5604 | 22.5604 | 1.0000 | 0.3000 |
FLR_3_DOAS | 20.42 | 2.05 | 3.99 | 2.05 | 2.0513 | 2.0513 | 2.0513 | 1.0000 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
BASEMENT VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | 14327.117 | 14327.117 | 2.467248 | 0.00012534 | 300.506 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 14327.12 | 14327.12 | 2.467248 | 16.70 | 13.09 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00795178 | 50.8633 | 1439.65 | 0.00 | 14407.47 | 14407.47 |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | 4825.409 | 4825.409 | 0.472551 | 0.00004221 | 105.886 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | 4825.41 | 4825.41 | 0.472551 | 16.70 | 13.09 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00749616 | 47.9858 | 2359.53 | 0.00 | 4851.75 | 4851.75 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | 1993.711 | 1993.711 | 0.236295 | 0.00001744 | 42.950 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 1993.71 | 1993.71 | 0.236295 | 16.70 | 13.09 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00740777 | 47.4250 | 760.71 | 0.00 | 2004.79 | 2004.79 |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | 2551.238 | 2551.238 | 0.221730 | 0.00002232 | 56.760 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 2551.24 | 2551.24 | 0.221730 | 16.70 | 13.09 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00726019 | 46.4911 | 1394.56 | 0.00 | 2565.09 | 2565.09 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | 1434.232 | 1434.232 | 0.108872 | 0.00001255 | 32.492 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 1434.23 | 1434.23 | 0.108872 | 16.70 | 13.09 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00730601 | 46.7812 | 866.24 | 0.00 | 1441.97 | 1441.97 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 18849.126 | 18849.126 | 3.265876 | 0.00016490 | 395.214 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | 18849.13 | 18849.13 | 3.265876 | 16.70 | 13.09 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00722922 | 46.2967 | 1815.44 | 0.00 | 18954.86 | 18954.86 |
CAFE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | 15718.649 | 15718.649 | 1.862671 | 0.00013751 | 338.625 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | 15718.65 | 15718.65 | 1.862671 | 16.70 | 13.09 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00755637 | 48.3662 | 5997.44 | 0.00 | 15806.04 | 15806.04 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 40686.711 | 40686.711 | 5.139451 | 0.00035595 | 871.809 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 40686.71 | 40686.71 | 5.139451 | 16.70 | 13.09 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00746228 | 47.7699 | 13866.24 | 0.00 | 40913.28 | 40913.28 |
ROOM_1_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 14904.394 | -999.000 | 1.244936 | 0.00053234 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 16:40:00 | unknown | 8/21 16:40:00 | 14904.39 | 14714.54 | 1.244936 | 22.50 | 15.79 | 0.00855731 | 12.80 | 12.00 | 0.00850000 | 25.37 | 0.00840546 | 16.68 | 0.0000 | 21.11 | 0.00855731 | 54.3135 | 12580.64 | 0.00 | 15056.55 | 14610.62 |
ROOM_1_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 5188.668 | 5188.668 | 0.226101 | 0.00004539 | 148.279 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | 5188.67 | 5188.67 | 0.226101 | 21.11 | 14.31 | 0.00747362 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.11 | 0.00747362 | 47.5184 | 5188.66 | 0.00 | 5593.49 | 5593.49 |
ROOM_2_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 13348.439 | -999.000 | 1.113091 | 0.00047677 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | unknown | 8/21 17:00:00 | 13348.44 | 13158.86 | 1.113091 | 22.50 | 15.80 | 0.00856399 | 12.80 | 12.00 | 0.00850000 | 25.13 | 0.00840508 | 16.59 | 0.0000 | 21.11 | 0.00856399 | 54.3553 | 11248.27 | 0.00 | 13484.59 | 13066.75 |
ROOM_2_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 5194.324 | 5194.324 | 0.226348 | 0.00004544 | 148.441 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | 5194.32 | 5194.32 | 0.226348 | 21.11 | 14.31 | 0.00747417 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.11 | 0.00747417 | 47.5219 | 5194.32 | 0.00 | 5599.59 | 5599.59 |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 106772.845 | -999.000 | 9.049329 | 0.00381361 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | unknown | 8/21 13:30:00 | 106772.85 | 106772.84 | 9.049329 | 22.50 | 15.74 | 0.00849881 | 12.80 | 12.00 | 0.00849881 | 26.17 | 0.00840672 | 16.96 | 0.0000 | 21.11 | 0.00849881 | 53.9460 | 91451.40 | 0.00 | 107848.32 | 105958.05 |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 29731.119 | 29731.119 | 1.295593 | 0.00026010 | 849.629 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | 29731.12 | 29731.12 | 1.295593 | 21.11 | 14.34 | 0.00750938 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.11 | 0.00750938 | 47.7417 | 29731.11 | 0.00 | 32051.00 | 32051.00 |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 72071.162 | -999.000 | 5.753464 | 0.00257417 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | unknown | 8/21 15:00:00 | 72071.16 | 68366.53 | 5.753464 | 22.50 | 15.95 | 0.00874067 | 12.80 | 12.00 | 0.00850000 | 26.40 | 0.00840708 | 17.04 | 0.0000 | 21.11 | 0.00874067 | 55.4621 | 58139.33 | 0.00 | 72789.83 | 67995.52 |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 29853.370 | 29853.370 | 1.300920 | 0.00026117 | 853.122 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | 29853.37 | 29853.37 | 1.300920 | 21.11 | 14.34 | 0.00751109 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.11 | 0.00751109 | 47.7525 | 29853.36 | 0.00 | 32182.79 | 32182.79 |
ROOM_5_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 13553.813 | -999.000 | 1.130478 | 0.00048410 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | unknown | 8/21 10:00:00 | 13553.81 | 13364.03 | 1.130478 | 22.50 | 15.80 | 0.00856308 | 12.80 | 12.00 | 0.00850000 | 22.94 | 0.00840167 | 15.82 | 0.0000 | 21.11 | 0.00856308 | 54.3496 | 11423.98 | 0.00 | 13692.08 | 13270.37 |
ROOM_5_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 5176.674 | 5176.674 | 0.225578 | 0.00004529 | 147.937 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | 5176.67 | 5176.67 | 0.225578 | 21.11 | 14.30 | 0.00747252 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.11 | 0.00747252 | 47.5115 | 5176.67 | 0.00 | 5580.56 | 5580.56 |
ROOM_6_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 12238.768 | -999.000 | 1.019094 | 0.00043713 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:10:00 | unknown | 8/21 09:10:00 | 12238.77 | 12049.72 | 1.019094 | 22.50 | 15.81 | 0.00856969 | 12.80 | 12.00 | 0.00850000 | 21.65 | 0.00839969 | 15.35 | 0.0000 | 21.11 | 0.00856969 | 54.3910 | 10298.39 | 0.00 | 12363.51 | 11966.00 |
ROOM_6_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 5182.333 | 5182.333 | 0.225825 | 0.00004534 | 148.098 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | 5182.33 | 5182.33 | 0.225825 | 21.11 | 14.31 | 0.00747307 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.11 | 0.00747307 | 47.5150 | 5182.33 | 0.00 | 5586.66 | 5586.66 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | 14547.385 | 14547.385 | 1.244879 | 0.00012727 | 324.277 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | 14547.38 | 14547.38 | 1.244879 | 16.70 | 13.09 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00757832 | 48.5036 | 8049.47 | 0.00 | 14626.31 | 14626.31 |
ROOM_1_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 3988.372 | -999.000 | 0.333458 | 0.00014245 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | unknown | 8/21 16:30:00 | 3988.37 | 3940.86 | 0.333458 | 22.50 | 15.79 | 0.00855356 | 12.80 | 12.00 | 0.00850000 | 25.49 | 0.00840565 | 16.72 | 0.0000 | 21.11 | 0.00855356 | 54.2900 | 3369.74 | 0.00 | 4029.11 | 3912.88 |
ROOM_1_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 1653.183 | 1653.183 | 0.072039 | 0.00001446 | 47.241 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | 1653.18 | 1653.18 | 0.072039 | 21.11 | 14.40 | 0.00757795 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.11 | 0.00757795 | 48.1737 | 1653.18 | 0.00 | 1782.17 | 1782.17 |
ROOM_2_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 3547.634 | -999.000 | 0.296105 | 0.00012671 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | unknown | 8/21 17:00:00 | 3547.63 | 3500.14 | 0.296105 | 22.50 | 15.80 | 0.00856028 | 12.80 | 12.00 | 0.00850000 | 25.13 | 0.00840508 | 16.59 | 0.0000 | 21.11 | 0.00856028 | 54.3321 | 2992.28 | 0.00 | 3583.84 | 3475.51 |
ROOM_2_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 1654.608 | 1654.608 | 0.072101 | 0.00001448 | 47.282 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | 1654.61 | 1654.61 | 0.072101 | 21.11 | 14.40 | 0.00757831 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.11 | 0.00757831 | 48.1760 | 1654.61 | 0.00 | 1783.70 | 1783.70 |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 22293.238 | -999.000 | 1.847525 | 0.00079625 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | unknown | 8/21 13:40:00 | 22293.24 | 21857.12 | 1.847525 | 22.50 | 15.82 | 0.00858862 | 12.80 | 12.00 | 0.00850000 | 26.25 | 0.00840684 | 16.99 | 0.0000 | 21.11 | 0.00858862 | 54.5102 | 18669.63 | 0.00 | 22519.90 | 21709.08 |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 7974.444 | 7974.444 | 0.347497 | 0.00006976 | 227.874 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | 7974.44 | 7974.44 | 0.347497 | 21.11 | 14.42 | 0.00759566 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.11 | 0.00759566 | 48.2845 | 7974.44 | 0.00 | 8596.64 | 8596.64 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 17055.319 | 17055.319 | 2.181540 | 0.00014921 | 365.082 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | 17055.32 | 17055.32 | 2.181540 | 16.70 | 13.09 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00769064 | 49.2142 | 5666.38 | 0.00 | 17150.33 | 17150.33 |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 17714.730 | 17714.730 | 2.288398 | 0.00015498 | 378.898 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 19:20:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 19:20:00 | 17714.73 | 17714.73 | 2.288398 | 16.70 | 13.09 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00769576 | 49.2467 | 5767.95 | 0.00 | 17813.43 | 17813.43 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 12886.515 | 12886.515 | 2.303631 | 0.00011274 | 269.716 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | 12886.51 | 12886.51 | 2.303631 | 16.70 | 13.09 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00467342 | 30.0577 | 937.60 | 0.00 | 12958.85 | 12958.85 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | 10065.776 | 10065.776 | 0.767295 | 0.00008806 | 227.900 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 19:20:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 19:20:00 | 10065.78 | 10065.78 | 0.767295 | 16.70 | 13.09 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00774384 | 49.5503 | 6059.60 | 0.00 | 10120.06 | 10120.06 |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV WITH REHEAT | 423570.841 | -999.000 | 22.560437 | 0.01512897 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 423570.84 | 423570.84 | 22.560437 | 26.40 | 17.04 | 0.00840708 | 10.96 | 10.96 | 0.00840708 | 26.40 | 0.00840708 | 17.04 | 99.9798 | 23.99 | 0.00961050 | 51.1177 | 306846.22 | 0.00 | 427330.34 | 406605.80 |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV WITH REHEAT | 170153.310 | 170153.310 | 6.768131 | 0.00148858 | 2903.295 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 19:20:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 19:20:00 | 170153.31 | 170153.31 | 6.768131 | -4.30 | -4.30 | 0.00265759 | 16.70 | 13.09 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 333.2660 | 21.00 | 0.00755857 | 48.3707 | 54412.52 | 0.00 | 156576.45 | 156576.45 |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | FLR_3_DOAS | 36112.103 | -999.000 | 2.051317 | 0.00128984 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 36112.10 | 36112.10 | 2.051317 | 26.40 | 17.04 | 0.00840708 | 11.92 | 11.55 | 0.00840708 | 26.40 | 0.00840708 | 17.04 | 99.9965 | 21.11 | 0.00859361 | 54.5404 | 206305.12 | 0.00 | 36425.73 | 35509.87 |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | FLR_3_DOAS | 15471.261 | 15471.261 | 0.615395 | 0.00013535 | 263.983 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | 15471.26 | 15471.26 | 0.615395 | -4.30 | -4.30 | 0.00265759 | 16.70 | 13.09 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 333.3216 | 21.11 | 0.00751094 | 47.7516 | 91608.67 | 0.00 | 14236.78 | 14236.78 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:58:31
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
BASEMENT VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | BASEMENT | N/A | N/A | N/A | Yes | Yes | Yes | No | 14327.117 | 14327.117 | 2.467248 | 0.00012534 | 300.506 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.93542556 | 54.44 | 82.22 | 27.78 | 458943.41 | 3.1218 | 3.184588 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 14327.12 | 14327.12 | 1.0000 | 2.93941025 | 2.467248 | 16.70 | 13.09 | 0.00800000 | 37036.7 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 0.12532708 | 60.00 | 32.22 | 27.78 | 0.000 | 14327.12 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 21.00 | 0.00795178 | 21.00 | 0.00795178 | 50.8633 | 1439.65 | 0.00 | 14407.47 | 14407.47 | 2.93941025 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 21.41 | 15.00 | 0.00800000 | 41836.2 | |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | RETAIL_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 4825.409 | 4825.409 | 0.472551 | 0.00004221 | 105.886 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.93542556 | 54.44 | 82.22 | 27.78 | 458943.41 | 1.0514 | 1.072577 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | Sensible | 4825.41 | 4825.41 | 1.0000 | 0.56298421 | 0.472551 | 16.70 | 13.09 | 0.00800000 | 37036.7 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 0.04221047 | 60.00 | 32.22 | 27.78 | 0.000 | 4825.41 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 21.00 | 0.00749616 | 21.00 | 0.00749616 | 47.9858 | 2359.53 | 0.00 | 4851.75 | 4851.75 | 0.56298421 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 25.05 | 16.33 | 0.00800000 | 45552.7 | |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | RETAIL_2_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1993.711 | 1993.711 | 0.236295 | 0.00001744 | 42.950 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.93542556 | 54.44 | 82.22 | 27.78 | 458943.41 | 0.4344 | 0.443156 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 1993.71 | 1993.71 | 1.0000 | 0.28151576 | 0.236295 | 16.70 | 13.09 | 0.00800000 | 37036.7 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 0.01744007 | 60.00 | 32.22 | 27.78 | 0.000 | 1993.71 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 21.00 | 0.00740777 | 21.00 | 0.00740777 | 47.4250 | 760.71 | 0.00 | 2004.79 | 2004.79 | 0.28151576 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 23.58 | 15.80 | 0.00800000 | 44056.2 | |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | MECH_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2551.238 | 2551.238 | 0.221730 | 0.00002232 | 56.760 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.93542556 | 54.44 | 82.22 | 27.78 | 458943.41 | 0.5559 | 0.567081 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 2551.24 | 2551.24 | 1.0000 | 0.26416328 | 0.221730 | 16.70 | 13.09 | 0.00800000 | 37036.7 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 0.02231706 | 60.00 | 32.22 | 27.78 | 0.000 | 2551.24 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 21.00 | 0.00726019 | 21.00 | 0.00726019 | 46.4911 | 1394.56 | 0.00 | 2565.09 | 2565.09 | 0.26416328 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 26.12 | 16.71 | 0.00800000 | 46645.0 | |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | STORAGE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1434.232 | 1434.232 | 0.108872 | 0.00001255 | 32.492 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.93542556 | 54.44 | 82.22 | 27.78 | 458943.41 | 0.3125 | 0.318797 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 1434.23 | 1434.23 | 1.0000 | 0.12970653 | 0.108872 | 16.70 | 13.09 | 0.00800000 | 37036.7 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 0.01254600 | 60.00 | 32.22 | 27.78 | 0.000 | 1434.23 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 21.00 | 0.00730601 | 21.00 | 0.00730601 | 46.7812 | 866.24 | 0.00 | 1441.97 | 1441.97 | 0.12970653 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 27.50 | 17.19 | 0.00800000 | 48051.9 | |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LAUNDRY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 18849.126 | 18849.126 | 3.265876 | 0.00016490 | 395.214 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.93542556 | 54.44 | 82.22 | 27.78 | 458943.41 | 4.1071 | 4.189726 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | Sensible | 18849.13 | 18849.13 | 1.0000 | 3.89087329 | 3.265876 | 16.70 | 13.09 | 0.00800000 | 37036.7 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 0.16488356 | 60.00 | 32.22 | 27.78 | 0.000 | 18849.13 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 21.00 | 0.00722922 | 21.00 | 0.00722922 | 46.2967 | 1815.44 | 0.00 | 18954.86 | 18954.86 | 3.89087329 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 21.38 | 14.99 | 0.00800000 | 41806.4 | |
CAFE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | CAFE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 15718.649 | 15718.649 | 1.862671 | 0.00013751 | 338.625 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.93542556 | 54.44 | 82.22 | 27.78 | 458943.41 | 3.4250 | 3.493893 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | Sensible | 15718.65 | 15718.65 | 1.0000 | 2.21913371 | 1.862671 | 16.70 | 13.09 | 0.00800000 | 37036.7 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 0.13749957 | 60.00 | 32.22 | 27.78 | 0.000 | 15718.65 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 21.00 | 0.00755637 | 21.00 | 0.00755637 | 48.3662 | 5997.44 | 0.00 | 15806.04 | 15806.04 | 2.21913371 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 23.58 | 15.81 | 0.00800000 | 44057.3 | |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LOBBY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 40686.711 | 40686.711 | 5.139451 | 0.00035595 | 871.809 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.93542556 | 54.44 | 82.22 | 27.78 | 458943.41 | 8.8653 | 9.043718 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 40686.71 | 40686.71 | 1.0000 | 6.12299777 | 5.139451 | 16.70 | 13.09 | 0.00800000 | 37036.7 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 0.35590878 | 60.00 | 32.22 | 27.78 | 0.000 | 40686.71 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 21.00 | 0.00746228 | 21.00 | 0.00746228 | 47.7699 | 13866.24 | 0.00 | 40913.28 | 40913.28 | 6.12299777 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 23.15 | 15.65 | 0.00800000 | 43616.6 | |
ROOM_1_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 14904.394 | -999.000 | 1.244936 | 0.00053234 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7476 | 1004.8586 | 1.1914 | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.244936 | 1.48318246 | 4197.9300 | 999.8980 | 25.79970433 | 13.37 | 6.70 | 6.67 | 722396.70 | 2.0632 | 2.063148 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 16:40:00 | unknown | unknown | unknown | 8/21 16:40:00 | Sensible | 14904.39 | 14714.54 | 1.0000 | 1.48318246 | 1.244936 | 22.50 | 15.79 | 0.00855731 | 44371.1 | 12.80 | 12.00 | 0.00850000 | 34322.2 | 0.53228617 | 6.70 | 13.37 | 6.67 | 0.000 | 14904.39 | 25.37 | 0.00840546 | 16.68 | 0.00000000 | 0.0000 | 21.11 | 0.00855731 | 21.11 | 0.00855731 | 54.3135 | 12580.64 | 0.00 | 15056.55 | 14610.62 | 1.48318246 | 22.50 | 15.90 | 0.00855731 | 44371.1 | 12.85 | 12.06 | 0.00843823 | 34219.6 | |
ROOM_1_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5188.668 | 5188.668 | 0.226101 | 0.00004539 | 148.279 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.244936 | 1.48318246 | 4197.9300 | 999.8980 | 3.93542556 | 54.44 | 82.22 | 27.78 | 458943.41 | 1.1306 | 1.153321 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | Sensible | 5188.67 | 5188.67 | 1.0000 | 0.26937047 | 0.226101 | 21.11 | 14.31 | 0.00747362 | 40196.7 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 0.04538810 | 60.00 | 32.22 | 27.78 | 0.000 | 5188.67 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 21.11 | 0.00747362 | 21.11 | 0.00747362 | 47.5184 | 5188.66 | 0.00 | 5593.49 | 5593.49 | 0.26937047 | 16.60 | 12.64 | 0.00747362 | 35602.0 | 36.98 | 19.88 | 0.00747362 | 56367.1 | |
ROOM_2_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 13348.439 | -999.000 | 1.113091 | 0.00047677 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7600 | 1004.8586 | 1.1914 | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.113091 | 1.32610551 | 4197.9300 | 999.8980 | 25.79970433 | 13.37 | 6.70 | 6.67 | 722396.70 | 1.8478 | 1.847765 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | unknown | unknown | unknown | 8/21 17:00:00 | Sensible | 13348.44 | 13158.86 | 1.0000 | 1.32610551 | 1.113091 | 22.50 | 15.80 | 0.00856399 | 44388.1 | 12.80 | 12.00 | 0.00850000 | 34322.2 | 0.47671778 | 6.70 | 13.37 | 6.67 | 0.000 | 13348.44 | 25.13 | 0.00840508 | 16.59 | 0.00000000 | 0.0000 | 21.11 | 0.00856399 | 21.11 | 0.00856399 | 54.3553 | 11248.27 | 0.00 | 13484.59 | 13066.75 | 1.32610551 | 22.50 | 15.91 | 0.00856399 | 44388.1 | 12.85 | 12.06 | 0.00843919 | 34219.5 | |
ROOM_2_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5194.324 | 5194.324 | 0.226348 | 0.00004544 | 148.441 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.113091 | 1.32610551 | 4197.9300 | 999.8980 | 3.93542556 | 54.44 | 82.22 | 27.78 | 458943.41 | 1.1318 | 1.154578 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | Sensible | 5194.32 | 5194.32 | 1.0000 | 0.26966410 | 0.226348 | 21.11 | 14.31 | 0.00747417 | 40198.1 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 0.04543757 | 60.00 | 32.22 | 27.78 | 0.000 | 5194.32 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 21.11 | 0.00747417 | 21.11 | 0.00747417 | 47.5219 | 5194.32 | 0.00 | 5599.59 | 5599.59 | 0.26966410 | 16.60 | 12.64 | 0.00747417 | 35603.4 | 36.98 | 19.88 | 0.00747417 | 56368.5 | |
ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 106772.845 | -999.000 | 9.049329 | 0.00381361 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6389 | 1004.8586 | 1.1914 | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 9.049329 | 10.78111762 | 4197.9300 | 999.8980 | 25.79970433 | 13.37 | 6.70 | 6.67 | 722396.70 | 14.7804 | 14.780086 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | unknown | unknown | unknown | 8/21 13:30:00 | Sensible | 106772.85 | 106772.84 | 1.0000 | 10.78111762 | 9.049329 | 22.50 | 15.74 | 0.00849881 | 44222.9 | 12.80 | 12.00 | 0.00849881 | 34319.2 | 3.81321839 | 6.70 | 13.37 | 6.67 | 0.000 | 106772.85 | 26.17 | 0.00840672 | 16.96 | 0.00000000 | 0.0000 | 21.11 | 0.00849881 | 21.11 | 0.00849881 | 53.9460 | 91451.40 | 0.00 | 107848.32 | 105958.05 | 10.78111762 | 22.50 | 15.85 | 0.00849881 | 44222.9 | 12.87 | 12.06 | 0.00842937 | 34219.4 | |
ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 29731.119 | 29731.119 | 1.295593 | 0.00026010 | 849.629 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 9.049329 | 10.78111762 | 4197.9300 | 999.8980 | 3.93542556 | 54.44 | 82.22 | 27.78 | 458943.41 | 6.4782 | 6.608542 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | Sensible | 29731.12 | 29731.12 | 1.0000 | 1.54353275 | 1.295593 | 21.11 | 14.34 | 0.00750938 | 40288.0 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 0.26007427 | 60.00 | 32.22 | 27.78 | 0.000 | 29731.12 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 21.11 | 0.00750938 | 21.11 | 0.00750938 | 47.7417 | 29731.11 | 0.00 | 32051.00 | 32051.00 | 1.54353275 | 16.60 | 12.67 | 0.00750938 | 35692.6 | 36.98 | 19.90 | 0.00750938 | 56457.3 | |
ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 72071.162 | -999.000 | 5.753464 | 0.00257417 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.0885 | 1004.8586 | 1.1914 | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 5.753464 | 6.85451627 | 4197.9300 | 999.8980 | 25.79970433 | 13.37 | 6.70 | 6.67 | 722396.70 | 9.9767 | 9.976487 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | unknown | unknown | unknown | 8/21 15:00:00 | Sensible | 72071.16 | 68366.53 | 1.0000 | 6.85451627 | 5.753464 | 22.50 | 15.95 | 0.00874067 | 44836.6 | 12.80 | 12.00 | 0.00850000 | 34322.2 | 2.57390425 | 6.70 | 13.37 | 6.67 | 0.000 | 72071.16 | 26.40 | 0.00840708 | 17.04 | 0.00000000 | 0.0000 | 21.11 | 0.00874067 | 21.11 | 0.00874067 | 55.4621 | 58139.33 | 0.00 | 72789.83 | 67995.52 | 6.85451627 | 22.50 | 16.06 | 0.00874067 | 44836.6 | 12.79 | 12.06 | 0.00846363 | 34217.4 | |
ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 29853.370 | 29853.370 | 1.300920 | 0.00026117 | 853.122 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 5.753464 | 6.85451627 | 4197.9300 | 999.8980 | 3.93542556 | 54.44 | 82.22 | 27.78 | 458943.41 | 6.5048 | 6.635716 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | Sensible | 29853.37 | 29853.37 | 1.0000 | 1.54987955 | 1.300920 | 21.11 | 14.34 | 0.00751109 | 40292.3 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 0.26114366 | 60.00 | 32.22 | 27.78 | 0.000 | 29853.37 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 21.11 | 0.00751109 | 21.11 | 0.00751109 | 47.7525 | 29853.36 | 0.00 | 32182.79 | 32182.79 | 1.54987955 | 16.60 | 12.67 | 0.00751109 | 35696.9 | 36.98 | 19.90 | 0.00751109 | 56461.6 | |
ROOM_5_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 13553.813 | -999.000 | 1.130478 | 0.00048410 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7583 | 1004.8586 | 1.1914 | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.130478 | 1.34681930 | 4197.9300 | 999.8980 | 25.79970433 | 13.37 | 6.70 | 6.67 | 722396.70 | 1.8762 | 1.876193 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | unknown | unknown | unknown | 8/21 10:00:00 | Sensible | 13553.81 | 13364.03 | 1.0000 | 1.34681930 | 1.130478 | 22.50 | 15.80 | 0.00856308 | 44385.8 | 12.80 | 12.00 | 0.00850000 | 34322.2 | 0.48405237 | 6.70 | 13.37 | 6.67 | 0.000 | 13553.81 | 22.94 | 0.00840167 | 15.82 | 0.00000000 | 0.0000 | 21.11 | 0.00856308 | 21.11 | 0.00856308 | 54.3496 | 11423.98 | 0.00 | 13692.08 | 13270.37 | 1.34681930 | 22.50 | 15.91 | 0.00856308 | 44385.8 | 12.85 | 12.06 | 0.00843906 | 34219.5 | |
ROOM_5_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5176.674 | 5176.674 | 0.225578 | 0.00004529 | 147.937 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.130478 | 1.34681930 | 4197.9300 | 999.8980 | 3.93542556 | 54.44 | 82.22 | 27.78 | 458943.41 | 1.1280 | 1.150655 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | Sensible | 5176.67 | 5176.67 | 1.0000 | 0.26874780 | 0.225578 | 21.11 | 14.30 | 0.00747252 | 40193.9 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 0.04528318 | 60.00 | 32.22 | 27.78 | 0.000 | 5176.67 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 21.11 | 0.00747252 | 21.11 | 0.00747252 | 47.5115 | 5176.67 | 0.00 | 5580.56 | 5580.56 | 0.26874780 | 16.60 | 12.64 | 0.00747252 | 35599.3 | 36.98 | 19.88 | 0.00747252 | 56364.3 | |
ROOM_6_FLR_3 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12238.768 | -999.000 | 1.019094 | 0.00043713 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7706 | 1004.8586 | 1.1914 | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.019094 | 1.21412046 | 4197.9300 | 999.8980 | 25.79970433 | 13.37 | 6.70 | 6.67 | 722396.70 | 1.6942 | 1.694158 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:10:00 | unknown | unknown | unknown | 8/21 09:10:00 | Sensible | 12238.77 | 12049.72 | 1.0000 | 1.21412046 | 1.019094 | 22.50 | 15.81 | 0.00856969 | 44402.6 | 12.80 | 12.00 | 0.00850000 | 34322.2 | 0.43708769 | 6.70 | 13.37 | 6.67 | 0.000 | 12238.77 | 21.65 | 0.00839969 | 15.35 | 0.00000000 | 0.0000 | 21.11 | 0.00856969 | 21.11 | 0.00856969 | 54.3910 | 10298.39 | 0.00 | 12363.51 | 11966.00 | 1.21412046 | 22.50 | 15.91 | 0.00856969 | 44402.6 | 12.85 | 12.06 | 0.00844001 | 34219.5 | |
ROOM_6_FLR_3 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5182.333 | 5182.333 | 0.225825 | 0.00004534 | 148.098 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.019094 | 1.21412046 | 4197.9300 | 999.8980 | 3.93542556 | 54.44 | 82.22 | 27.78 | 458943.41 | 1.1292 | 1.151913 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | Sensible | 5182.33 | 5182.33 | 1.0000 | 0.26904160 | 0.225825 | 21.11 | 14.31 | 0.00747307 | 40195.3 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 0.04533268 | 60.00 | 32.22 | 27.78 | 0.000 | 5182.33 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 21.11 | 0.00747307 | 21.11 | 0.00747307 | 47.5150 | 5182.33 | 0.00 | 5586.66 | 5586.66 | 0.26904160 | 16.60 | 12.64 | 0.00747307 | 35600.7 | 36.98 | 19.88 | 0.00747307 | 56365.7 | |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | CORRIDOR_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 14547.385 | 14547.385 | 1.244879 | 0.00012727 | 324.277 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.93542556 | 54.44 | 82.22 | 27.78 | 458943.41 | 3.1698 | 3.233548 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | Sensible | 14547.38 | 14547.38 | 1.0000 | 1.48311409 | 1.244879 | 16.70 | 13.09 | 0.00800000 | 37036.7 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 0.12725388 | 60.00 | 32.22 | 27.78 | 0.000 | 14547.38 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 21.00 | 0.00757832 | 21.00 | 0.00757832 | 48.5036 | 8049.47 | 0.00 | 14626.31 | 14626.31 | 1.48311409 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 26.27 | 16.76 | 0.00800000 | 46796.6 | |
ROOM_1_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3988.372 | -999.000 | 0.333458 | 0.00014245 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7406 | 1004.8586 | 1.1914 | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.333458 | 0.39727216 | 4197.9300 | 999.8980 | 25.79970433 | 13.37 | 6.70 | 6.67 | 722396.70 | 0.5521 | 0.552092 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | unknown | unknown | unknown | 8/21 16:30:00 | Sensible | 3988.37 | 3940.86 | 1.0000 | 0.39727216 | 0.333458 | 22.50 | 15.79 | 0.00855356 | 44361.6 | 12.80 | 12.00 | 0.00850000 | 34322.2 | 0.14243823 | 6.70 | 13.37 | 6.67 | 0.000 | 3988.37 | 25.49 | 0.00840565 | 16.72 | 0.00000000 | 0.0000 | 21.11 | 0.00855356 | 21.11 | 0.00855356 | 54.2900 | 3369.74 | 0.00 | 4029.11 | 3912.88 | 0.39727216 | 22.50 | 15.90 | 0.00855356 | 44361.6 | 12.85 | 12.06 | 0.00843768 | 34219.7 | |
ROOM_1_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1653.183 | 1653.183 | 0.072039 | 0.00001446 | 47.241 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.333458 | 0.39727216 | 4197.9300 | 999.8980 | 3.93542556 | 54.44 | 82.22 | 27.78 | 458943.41 | 0.3602 | 0.367465 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | Sensible | 1653.18 | 1653.18 | 1.0000 | 0.08582529 | 0.072039 | 21.11 | 14.40 | 0.00757795 | 40461.7 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 0.01446130 | 60.00 | 32.22 | 27.78 | 0.000 | 1653.18 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 21.11 | 0.00757795 | 21.11 | 0.00757795 | 48.1737 | 1653.18 | 0.00 | 1782.17 | 1782.17 | 0.08582529 | 16.60 | 12.74 | 0.00757795 | 35866.2 | 36.98 | 19.95 | 0.00757795 | 56631.2 | |
ROOM_2_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3547.634 | -999.000 | 0.296105 | 0.00012671 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7531 | 1004.8586 | 1.1914 | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.296105 | 0.35277158 | 4197.9300 | 999.8980 | 25.79970433 | 13.37 | 6.70 | 6.67 | 722396.70 | 0.4911 | 0.491083 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | unknown | unknown | unknown | 8/21 17:00:00 | Sensible | 3547.63 | 3500.14 | 1.0000 | 0.35277158 | 0.296105 | 22.50 | 15.80 | 0.00856028 | 44378.7 | 12.80 | 12.00 | 0.00850000 | 34322.2 | 0.12669799 | 6.70 | 13.37 | 6.67 | 0.000 | 3547.63 | 25.13 | 0.00840508 | 16.59 | 0.00000000 | 0.0000 | 21.11 | 0.00856028 | 21.11 | 0.00856028 | 54.3321 | 2992.28 | 0.00 | 3583.84 | 3475.51 | 0.35277158 | 22.50 | 15.91 | 0.00856028 | 44378.7 | 12.85 | 12.06 | 0.00843866 | 34219.6 | |
ROOM_2_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1654.608 | 1654.608 | 0.072101 | 0.00001448 | 47.282 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 0.296105 | 0.35277158 | 4197.9300 | 999.8980 | 3.93542556 | 54.44 | 82.22 | 27.78 | 458943.41 | 0.3605 | 0.367781 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | Sensible | 1654.61 | 1654.61 | 1.0000 | 0.08589924 | 0.072101 | 21.11 | 14.40 | 0.00757831 | 40462.6 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 0.01447376 | 60.00 | 32.22 | 27.78 | 0.000 | 1654.61 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 21.11 | 0.00757831 | 21.11 | 0.00757831 | 48.1760 | 1654.61 | 0.00 | 1783.70 | 1783.70 | 0.08589924 | 16.60 | 12.74 | 0.00757831 | 35867.1 | 36.98 | 19.95 | 0.00757831 | 56632.1 | |
ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 22293.238 | -999.000 | 1.847525 | 0.00079625 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8058 | 1004.8586 | 1.1914 | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.847525 | 2.20108927 | 4197.9300 | 999.8980 | 25.79970433 | 13.37 | 6.70 | 6.67 | 722396.70 | 3.0860 | 3.085953 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | unknown | unknown | unknown | 8/21 13:40:00 | Sensible | 22293.24 | 21857.12 | 1.0000 | 2.20108927 | 1.847525 | 22.50 | 15.82 | 0.00858862 | 44450.5 | 12.80 | 12.00 | 0.00850000 | 34322.2 | 0.79616670 | 6.70 | 13.37 | 6.67 | 0.000 | 22293.24 | 26.25 | 0.00840684 | 16.99 | 0.00000000 | 0.0000 | 21.11 | 0.00858862 | 21.11 | 0.00858862 | 54.5102 | 18669.63 | 0.00 | 22519.90 | 21709.08 | 2.20108927 | 22.50 | 15.93 | 0.00858862 | 44450.5 | 12.84 | 12.06 | 0.00844272 | 34219.2 | |
ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7974.444 | 7974.444 | 0.347497 | 0.00006976 | 227.874 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN | Fan:OnOff | 1.847525 | 2.20108927 | 4197.9300 | 999.8980 | 3.93542556 | 54.44 | 82.22 | 27.78 | 458943.41 | 1.7376 | 1.772535 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | Sensible | 7974.44 | 7974.44 | 1.0000 | 0.41399804 | 0.347497 | 21.11 | 14.42 | 0.00759566 | 40506.8 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 0.06975680 | 60.00 | 32.22 | 27.78 | 0.000 | 7974.44 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 21.11 | 0.00759566 | 21.11 | 0.00759566 | 48.2845 | 7974.44 | 0.00 | 8596.64 | 8596.64 | 0.41399804 | 16.60 | 12.76 | 0.00759566 | 35911.0 | 36.98 | 19.97 | 0.00759566 | 56675.9 | |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | BANQUET_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 17055.319 | 17055.319 | 2.181540 | 0.00014921 | 365.082 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.93542556 | 54.44 | 82.22 | 27.78 | 458943.41 | 3.7162 | 3.791004 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | Sensible | 17055.32 | 17055.32 | 1.0000 | 2.59902561 | 2.181540 | 16.70 | 13.09 | 0.00800000 | 37036.7 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 0.14919215 | 60.00 | 32.22 | 27.78 | 0.000 | 17055.32 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 21.00 | 0.00769064 | 21.00 | 0.00769064 | 49.2142 | 5666.38 | 0.00 | 17150.33 | 17150.33 | 2.59902561 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 23.07 | 15.62 | 0.00800000 | 43533.5 | |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | DINING_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 17714.730 | 17714.730 | 2.288398 | 0.00015498 | 378.898 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.93542556 | 54.44 | 82.22 | 27.78 | 458943.41 | 3.8599 | 3.937576 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 19:20:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 19:20:00 | Sensible | 17714.73 | 17714.73 | 1.0000 | 2.72633374 | 2.288398 | 16.70 | 13.09 | 0.00800000 | 37036.7 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 0.15496038 | 60.00 | 32.22 | 27.78 | 0.000 | 17714.73 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 21.00 | 0.00769576 | 21.00 | 0.00769576 | 49.2467 | 5767.95 | 0.00 | 17813.43 | 17813.43 | 2.72633374 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 23.01 | 15.59 | 0.00800000 | 43468.6 | |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | KITCHEN_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12886.515 | 12886.515 | 2.303631 | 0.00011274 | 269.716 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.93542556 | 54.44 | 82.22 | 27.78 | 458943.41 | 2.8079 | 2.864375 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | Sensible | 12886.51 | 12886.51 | 1.0000 | 2.74448130 | 2.303631 | 16.70 | 13.09 | 0.00800000 | 37036.7 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 0.11272535 | 60.00 | 32.22 | 27.78 | 0.000 | 12886.51 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 19.73 | 0.00467342 | 21.00 | 0.00467342 | 30.0577 | 937.60 | 0.00 | 12958.85 | 12958.85 | 2.74448130 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 21.23 | 14.94 | 0.00800000 | 41656.5 | |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | CORRIDOR_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10065.776 | 10065.776 | 0.767295 | 0.00008806 | 227.900 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 3.93542556 | 54.44 | 82.22 | 27.78 | 458943.41 | 2.1932 | 2.237390 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 19:20:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 19:20:00 | Sensible | 10065.78 | 10065.78 | 1.0000 | 0.91413381 | 0.767295 | 16.70 | 13.09 | 0.00800000 | 37036.7 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 0.08805081 | 60.00 | 32.22 | 27.78 | 0.000 | 10065.78 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 21.00 | 0.00774384 | 21.00 | 0.00774384 | 49.5503 | 6059.60 | 0.00 | 10120.06 | 10120.06 | 0.91413381 | 16.60 | 13.15 | 0.00800000 | 36934.7 | 27.46 | 17.17 | 0.00800000 | 48005.4 | |
VAV WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 423570.841 | -999.000 | 22.560437 | 0.01512897 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.4683 | 1004.8586 | 1.1914 | VAV WITH REHEAT FAN | Fan:VariableVolume | 22.560437 | 26.87787333 | 4197.9300 | 999.8980 | 25.79970433 | 13.37 | 6.70 | 6.67 | 722396.70 | 58.6341 | 58.634105 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | Sensible | 423570.84 | 423570.84 | 1.0000 | 26.87787333 | 22.560437 | 26.40 | 17.04 | 0.00840708 | 47966.0 | 10.96 | 10.96 | 0.00840708 | 32206.9 | 15.12742570 | 6.70 | 13.37 | 6.67 | 50549.786 | 373021.05 | 26.40 | 0.00840708 | 17.04 | 22.55588000 | 99.9798 | 23.99 | 0.00961017 | 23.99 | 0.00961050 | 51.1177 | 306846.22 | 0.00 | 427330.34 | 406605.80 | 26.87787333 | 26.40 | 17.15 | 0.00840708 | 47966.0 | 11.58 | 11.18 | 0.00810140 | 32067.0 | |
VAV WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; CORRIDOR_FLR_6; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 170153.310 | 170153.310 | 6.768131 | 0.00148858 | 2903.295 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | VAV WITH REHEAT FAN | Fan:VariableVolume | 22.560437 | 26.87787333 | 4197.9300 | 999.8980 | 3.93542556 | 54.44 | 82.22 | 27.78 | 458943.41 | 37.0750 | 37.821158 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 19:20:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 19:20:00 | Sensible | 170153.31 | 170153.31 | 1.0000 | 8.06336200 | 6.768131 | -4.30 | -4.30 | 0.00265759 | 2304.4 | 16.70 | 13.09 | 0.00800000 | 37036.7 | 1.48842353 | 60.00 | 32.22 | 27.78 | 0.000 | 170153.31 | -4.30 | 0.00265759 | -4.30 | 22.55588000 | 333.2660 | 20.92 | 0.00748388 | 21.00 | 0.00755857 | 48.3707 | 54412.52 | 0.00 | 156576.45 | 156576.45 | 8.06336200 | 2.80 | 0.02 | 0.00265759 | 9473.9 | 22.03 | 9.93 | 0.00265759 | 28892.1 | |
FLR_3_DOAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 36112.103 | -999.000 | 2.051317 | 0.00128984 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.4683 | 1004.8586 | 1.1914 | FLR_3_DOAS FAN | Fan:ConstantVolume | 2.051245 | 2.44379602 | 4197.9300 | 999.8980 | 25.79970433 | 13.37 | 6.70 | 6.67 | 722396.70 | 4.9989 | 4.998930 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | Sensible | 36112.10 | 36112.10 | 1.0000 | 2.44388195 | 2.051317 | 26.40 | 17.04 | 0.00840708 | 47966.0 | 11.92 | 11.55 | 0.00840708 | 33189.4 | 1.28970906 | 6.70 | 13.37 | 6.67 | 2195.006 | 33917.10 | 26.40 | 0.00840708 | 17.04 | 2.05124512 | 99.9965 | 21.11 | 0.00859088 | 21.11 | 0.00859361 | 54.5404 | 206305.12 | 0.00 | 36425.73 | 35509.87 | 2.44388195 | 26.40 | 17.15 | 0.00840708 | 47966.0 | 12.16 | 11.59 | 0.00825857 | 33061.1 | |
FLR_3_DOAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_1_FLR_6; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 15471.261 | 15471.261 | 0.615395 | 0.00013535 | 263.983 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | FLR_3_DOAS FAN | Fan:ConstantVolume | 2.051245 | 2.44379602 | 4197.9300 | 999.8980 | 3.93542556 | 54.44 | 82.22 | 27.78 | 458943.41 | 3.3711 | 3.438905 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:20:00 | Sensible | 15471.26 | 15471.26 | 1.0000 | 0.73316458 | 0.615395 | -4.30 | -4.30 | 0.00265759 | 2304.4 | 16.70 | 13.09 | 0.00800000 | 37036.7 | 0.13533554 | 60.00 | 32.22 | 27.78 | 0.000 | 15471.26 | -4.30 | 0.00265759 | -4.30 | 2.05124512 | 333.3216 | 21.11 | 0.00751177 | 21.11 | 0.00751094 | 47.7516 | 91608.67 | 0.00 | 14236.78 | 14236.78 | 0.73316458 | 2.80 | 0.02 | 0.00265759 | 9473.9 | 22.03 | 9.93 | 0.00265759 | 28892.1 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:58:31
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
VAV WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 22.56 | 22.56 | - | |||
FLR_3_DOAS_OA_CONTROLLER | DifferentialDryBulb | 2.05 | 2.05 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
BASEMENT | VAV WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
RETAIL_1_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
RETAIL_2_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
MECH_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
STORAGE_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000610 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
LAUNDRY_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CAFE_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
LOBBY_FLR_1 | VAV WITH REHEAT_DCV | 0.000000 | 0.001448 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORRIDOR_FLR_3 | VAV WITH REHEAT_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
BANQUET_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
DINING_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003581 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
KITCHEN_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.003556 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORRIDOR_FLR_6 | VAV WITH REHEAT_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 3.33 | 8760.00 | 3.33 |
RETAIL_1_FLR_1 | 1400.00 | 8709.33 | 1388.00 |
RETAIL_2_FLR_1 | 5.83 | 8760.00 | 5.83 |
MECH_FLR_1 | 109.67 | 8760.00 | 109.67 |
STORAGE_FLR_1 | 247.83 | 8760.00 | 247.83 |
LAUNDRY_FLR_1 | 2583.17 | 5011.83 | 1146.17 |
CAFE_FLR_1 | 118.67 | 8690.00 | 105.50 |
LOBBY_FLR_1 | 0.00 | 8760.00 | 0.00 |
ROOM_1_FLR_3 | 1676.50 | 8449.83 | 1625.83 |
ROOM_2_FLR_3 | 2279.17 | 8615.00 | 2269.50 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 318.00 | 8760.00 | 318.00 |
ROOM_5_FLR_3 | 1607.67 | 8357.33 | 1605.50 |
ROOM_6_FLR_3 | 2250.17 | 8651.33 | 2249.33 |
CORRIDOR_FLR_3 | 161.83 | 8760.00 | 161.83 |
ROOM_1_FLR_6 | 2648.17 | 8305.00 | 2495.17 |
ROOM_2_FLR_6 | 3191.33 | 8511.00 | 3140.00 |
ROOM_3_MULT9_FLR_6 | 1170.83 | 8163.67 | 1002.00 |
BANQUET_FLR_6 | 4.17 | 8683.50 | 0.00 |
DINING_FLR_6 | 34.33 | 8547.50 | 0.00 |
KITCHEN_FLR_6 | 6463.33 | 6838.50 | 4877.17 |
CORRIDOR_FLR_6 | 578.00 | 8760.00 | 578.00 |
Facility | 7465.17 | 8760.00 | 6724.67 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 23.33 | 0.00 | 23.33 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 1.00 | 0.00 | 1.00 |
ROOM_2_FLR_3 | 0.50 | 0.83 | 0.50 | 0.83 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.33 | 1.17 | 0.33 | 1.17 |
ROOM_5_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 0.83 | 0.00 | 0.83 | 0.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 0.00 | 3.17 | 0.00 | 3.17 |
ROOM_2_FLR_6 | 0.17 | 3.00 | 0.17 | 3.00 |
ROOM_3_MULT9_FLR_6 | 0.00 | 1.00 | 0.00 | 1.00 |
BANQUET_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 24.50 | 5.67 | 24.50 | 5.67 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:58:31
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.80 | 106.50 | 4826.41 | 1.856 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.28 | 10.83 | 265.76 | 6.454 | 0.138 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.28 | 12.54 | 307.76 | 2.788 | 0.046 | 0.000 | 0.000 |
MECH_FLR_1 | 1.54 | 2.65 | 650.80 | 1.237 | 0.052 | 0.000 | 0.000 |
STORAGE_FLR_1 | 1.18 | 2.04 | 375.47 | 1.052 | 0.052 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.87 | 8.40 | 309.22 | 38.394 | 0.148 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.58 | 142.30 | 748.35 | 9.041 | 0.109 | 0.000 | 0.000 |
LOBBY_FLR_1 | 245.14 | 422.44 | 5183.56 | 3.602 | 0.045 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.472 | 0.180 | 0.000 | 0.027 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.472 | 0.180 | 0.000 | 0.027 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.536 | 0.080 | 0.000 | 0.043 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.472 | 0.180 | 0.000 | 0.027 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.472 | 0.180 | 0.000 | 0.027 |
CORRIDOR_FLR_3 | 12.16 | 20.96 | 1186.91 | 0.952 | 0.022 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.472 | 0.180 | 0.000 | 0.031 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.472 | 0.180 | 0.000 | 0.031 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.537 | 0.147 | 0.000 | 0.049 |
BANQUET_FLR_6 | 145.01 | 249.90 | 1010.89 | 7.856 | 0.052 | 0.000 | 0.000 |
DINING_FLR_6 | 145.01 | 249.90 | 1010.89 | 8.243 | 0.052 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.90 | 22.24 | 314.87 | 26.786 | 0.149 | 0.000 | 0.000 |
CORRIDOR_FLR_6 | 12.87 | 22.18 | 1256.16 | 2.218 | 0.036 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.80 | 106.50 | 4826.41 | 1.794 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.28 | 10.83 | 265.76 | 6.239 | 0.003 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.28 | 12.54 | 307.76 | 2.695 | 0.001 | 0.000 | 0.000 |
MECH_FLR_1 | 1.54 | 2.65 | 650.80 | 1.195 | 0.001 | 0.000 | 0.000 |
STORAGE_FLR_1 | 1.18 | 2.04 | 375.47 | 1.017 | 0.001 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.87 | 8.40 | 309.22 | 37.056 | 0.003 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.58 | 142.30 | 748.35 | 8.737 | 0.002 | 0.000 | 0.000 |
LOBBY_FLR_1 | 245.14 | 422.44 | 5183.56 | 3.480 | 0.001 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.456 | 0.003 | 0.000 | 0.000 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.456 | 0.003 | 0.000 | 0.000 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.518 | 0.002 | 0.000 | 0.000 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.456 | 0.003 | 0.000 | 0.000 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.456 | 0.003 | 0.000 | 0.000 |
CORRIDOR_FLR_3 | 12.16 | 20.96 | 1186.91 | 0.920 | 0.000 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.456 | 0.003 | 0.000 | 0.000 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.456 | 0.003 | 0.000 | 0.000 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.518 | 0.003 | 0.000 | 0.000 |
BANQUET_FLR_6 | 145.01 | 249.90 | 1010.89 | 7.609 | 0.001 | 0.000 | 0.000 |
DINING_FLR_6 | 145.01 | 249.90 | 1010.89 | 7.985 | 0.001 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.90 | 22.24 | 314.87 | 25.732 | 0.003 | 0.000 | 0.000 |
CORRIDOR_FLR_6 | 12.87 | 22.18 | 1256.16 | 2.144 | 0.001 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:58:31
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | VAV WITH REHEAT | 61.80 | 106.50 | 4826.41 | 1978.83 | 0.0000 | 0.854 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | 6.28 | 10.83 | 265.76 | 67.07 | 0.0000 | 0.079 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | 7.28 | 12.54 | 307.76 | 77.67 | 0.0000 | 0.092 |
MECH_FLR_1 | VAV WITH REHEAT | 1.54 | 2.65 | 650.80 | 164.24 | 0.0000 | 0.000 |
STORAGE_FLR_1 | VAV WITH REHEAT | 1.18 | 2.04 | 375.47 | 94.76 | 0.0000 | 0.058 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | 4.87 | 8.40 | 309.22 | 78.04 | 0.0000 | 0.000 |
CAFE_FLR_1 | VAV WITH REHEAT | 82.58 | 142.30 | 748.35 | 188.86 | 0.0000 | 0.676 |
LOBBY_FLR_1 | VAV WITH REHEAT | 245.14 | 422.44 | 5183.56 | 1308.19 | 0.0000 | 1.894 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.062 |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.062 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 1.50 | 74.75 | 24.52 | 0.0000 | 0.837 | |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 74.77 | 24.53 | 0.0000 | 0.837 |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.062 |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.062 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | 12.16 | 20.96 | 1186.91 | 389.40 | 0.0000 | 0.475 |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 118.94 | 39.02 | 0.0000 | 0.015 |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 118.93 | 39.02 | 0.0000 | 0.015 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.95 | 1.50 | 74.77 | 24.53 | 0.0000 | 0.099 |
BANQUET_FLR_6 | VAV WITH REHEAT | 145.01 | 249.90 | 1010.89 | 331.66 | 0.0000 | 1.188 |
DINING_FLR_6 | VAV WITH REHEAT | 145.01 | 249.90 | 1010.89 | 331.66 | 0.0000 | 1.188 |
KITCHEN_FLR_6 | VAV WITH REHEAT | 12.90 | 22.24 | 314.87 | 103.30 | 0.0000 | 0.367 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | 12.87 | 22.18 | 1256.16 | 412.12 | 0.0000 | 0.126 |
Total Facility | 873.39 | 1604.23 | 35184.81 | 11345.29 | 0.0000 | 137.584 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 77784493.65 | 0.00 | 77784493.65 | 0.00 | 77784493.65 | 26946214.98 | 0.00 | 0.00 | 8760.00 | 0.00 |
RETAIL_1_FLR_1 | 14898036.60 | 0.00 | 14898036.60 | 319403.00 | 15217439.61 | 2498216.28 | 0.00 | 0.00 | 8760.00 | 0.00 |
RETAIL_2_FLR_1 | 7449644.31 | 0.00 | 7449644.31 | 123289.96 | 7572934.28 | 2892943.94 | 0.00 | 0.00 | 8760.00 | 0.00 |
MECH_FLR_1 | 6990452.15 | 0.00 | 6990452.15 | 291384.23 | 7281836.38 | 0.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
STORAGE_FLR_1 | 3432374.57 | 0.00 | 3432374.57 | 168112.65 | 3600487.22 | 1821682.01 | 0.00 | 0.00 | 8760.00 | 0.00 |
LAUNDRY_FLR_1 | 0.10E+09 | 0.00 | 0.10E+09 | 397870.28 | 0.10E+09 | 0.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
CAFE_FLR_1 | 58724089.86 | 0.00 | 58724089.86 | 706058.42 | 59430148.28 | 21330615.53 | 0.00 | 0.00 | 8760.00 | 0.00 |
LOBBY_FLR_1 | 0.16E+09 | 0.00 | 0.16E+09 | 2017370.18 | 0.16E+09 | 59728886.00 | 0.00 | 0.00 | 8760.00 | 0.00 |
ROOM_1_FLR_3 | 1946875.62 | 27936.79 | 1974812.41 | 185391.43 | 2160203.84 | 1946875.62 | 0.00 | 8310.83 | 449.17 | 0.00 |
ROOM_2_FLR_3 | 1946647.51 | 28013.68 | 1974661.19 | 185377.29 | 2160038.48 | 1946647.51 | 0.00 | 8310.83 | 449.17 | 0.00 |
ROOM_3_MULT19_FLR_3 | 26397887.27 | 31461.34 | 26429348.61 | 51726.29 | 26481074.90 | 26397887.27 | 0.00 | 8317.67 | 442.33 | 8760.00 |
ROOM_4_MULT19_FLR_3 | 26405105.73 | 27621.51 | 26432727.24 | 51740.43 | 26484467.67 | 26405105.73 | 0.00 | 8324.18 | 435.82 | 0.00 |
ROOM_5_FLR_3 | 1946875.62 | 27897.14 | 1974772.75 | 185391.43 | 2160164.19 | 1946875.62 | 0.00 | 8310.83 | 449.17 | 0.00 |
ROOM_6_FLR_3 | 1946647.51 | 27931.68 | 1974579.19 | 185377.29 | 2159956.48 | 1946647.51 | 0.00 | 8310.83 | 449.17 | 0.00 |
CORRIDOR_FLR_3 | 39247083.14 | 0.00 | 39247083.14 | 224175.54 | 39471258.68 | 14972100.18 | 0.00 | 0.00 | 8760.00 | 0.00 |
ROOM_1_FLR_6 | 486718.90 | 31732.37 | 518451.27 | 185430.49 | 703881.76 | 486718.90 | 0.00 | 8311.00 | 449.00 | 0.00 |
ROOM_2_FLR_6 | 486661.88 | 31877.63 | 518539.51 | 185416.35 | 703955.85 | 486661.88 | 0.00 | 8311.00 | 449.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 3126920.42 | 31640.24 | 3158560.66 | 94872.73 | 3253433.39 | 3126920.42 | 0.00 | 8311.00 | 449.00 | 0.00 |
BANQUET_FLR_6 | 68777024.56 | 0.00 | 68777024.56 | 452774.66 | 69229799.22 | 37458366.31 | 0.00 | 0.00 | 8760.00 | 0.00 |
DINING_FLR_6 | 72145931.20 | 0.00 | 72145931.20 | 452774.66 | 72598705.86 | 37458366.31 | 0.00 | 0.00 | 8760.00 | 0.00 |
KITCHEN_FLR_6 | 72690838.37 | 0.00 | 72690838.37 | 405338.30 | 73096176.67 | 11584760.86 | 0.00 | 0.00 | 8760.00 | 0.00 |
CORRIDOR_FLR_6 | 24190374.80 | 0.00 | 24190374.80 | 396722.51 | 24587097.30 | 3961413.96 | 0.00 | 0.00 | 8760.00 | 0.00 |
Total Facility | 0.49E+10 | 5285785.99 | 0.49E+10 | 18682123.06 | 0.49E+10 | 0.43E+10 | 0.00 | 8329.64 | 8760.00 | 8760.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 2.4665 | 0.0000 | 2.4665 | 0.0000 | 2.4665 | 0.8545 | 0.00 | 0.00 | 8760.00 |
RETAIL_1_FLR_1 | 0.4724 | 0.0000 | 0.4724 | 0.0101 | 0.4825 | 0.0792 | 0.00 | 0.00 | 8760.00 |
RETAIL_2_FLR_1 | 0.2362 | 0.0000 | 0.2362 | 0.0039 | 0.2401 | 0.0917 | 0.00 | 0.00 | 8760.00 |
MECH_FLR_1 | 0.2217 | 0.0000 | 0.2217 | 0.0092 | 0.2309 | 0.0000 | 0.00 | 0.00 | 8760.00 |
STORAGE_FLR_1 | 0.1088 | 0.0000 | 0.1088 | 0.0053 | 0.1142 | 0.0578 | 0.00 | 0.00 | 8760.00 |
LAUNDRY_FLR_1 | 3.2658 | 0.0000 | 3.2658 | 0.0126 | 3.2784 | 0.0000 | 0.00 | 0.00 | 8760.00 |
CAFE_FLR_1 | 1.8621 | 0.0000 | 1.8621 | 0.0224 | 1.8845 | 0.6764 | 0.00 | 0.00 | 8760.00 |
LOBBY_FLR_1 | 5.1380 | 0.0000 | 5.1380 | 0.0640 | 5.2019 | 1.8940 | 0.00 | 0.00 | 8760.00 |
ROOM_1_FLR_3 | 0.0617 | 0.0009 | 0.0626 | 0.0059 | 0.0685 | 0.0617 | 0.00 | 8310.83 | 449.17 |
ROOM_2_FLR_3 | 0.0617 | 0.0009 | 0.0626 | 0.0059 | 0.0685 | 0.0617 | 0.00 | 8310.83 | 449.17 |
ROOM_4_MULT19_FLR_3 | 0.8373 | 0.0009 | 0.8382 | 0.0016 | 0.8398 | 0.8373 | 0.00 | 8324.18 | 435.82 |
ROOM_5_FLR_3 | 0.0617 | 0.0009 | 0.0626 | 0.0059 | 0.0685 | 0.0617 | 0.00 | 8310.83 | 449.17 |
ROOM_6_FLR_3 | 0.0617 | 0.0009 | 0.0626 | 0.0059 | 0.0685 | 0.0617 | 0.00 | 8310.83 | 449.17 |
CORRIDOR_FLR_3 | 1.2445 | 0.0000 | 1.2445 | 0.0071 | 1.2516 | 0.4748 | 0.00 | 0.00 | 8760.00 |
ROOM_1_FLR_6 | 0.0154 | 0.0010 | 0.0164 | 0.0059 | 0.0223 | 0.0154 | 0.00 | 8311.00 | 449.00 |
ROOM_2_FLR_6 | 0.0154 | 0.0010 | 0.0164 | 0.0059 | 0.0223 | 0.0154 | 0.00 | 8311.00 | 449.00 |
ROOM_3_MULT9_FLR_6 | 0.0992 | 0.0010 | 0.1002 | 0.0030 | 0.1032 | 0.0992 | 0.00 | 8311.00 | 449.00 |
BANQUET_FLR_6 | 2.1809 | 0.0000 | 2.1809 | 0.0144 | 2.1953 | 1.1878 | 0.00 | 0.00 | 8760.00 |
DINING_FLR_6 | 2.2877 | 0.0000 | 2.2877 | 0.0144 | 2.3021 | 1.1878 | 0.00 | 0.00 | 8760.00 |
KITCHEN_FLR_6 | 2.3050 | 0.0000 | 2.3050 | 0.0129 | 2.3179 | 0.3674 | 0.00 | 0.00 | 8760.00 |
CORRIDOR_FLR_6 | 0.7671 | 0.0000 | 0.7671 | 0.0126 | 0.7797 | 0.1256 | 0.00 | 0.00 | 8760.00 |
Total Facility | 91.8361 | 0.0918 | 91.9279 | 0.4677 | 92.3956 | 73.9670 | 0.00 | 8329.64 | 8760.00 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV WITH REHEAT | 0.10E+10 | 0.00 | 0.10E+10 | 0.22E+09 | 0.00 | 0.00 | 8760.00 | 0.00 |
FLR_3_DOAS | 91819351.87 | 266112.37 | 92085464.25 | 64690340.46 | 0.00 | 0.00 | 8760.00 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV WITH REHEAT | 32.0163 | 0.0000 | 32.0163 | 6.9969 | 0.00 | 0.00 | 8760.00 |
FLR_3_DOAS | 2.9116 | 0.0084 | 2.9200 | 2.0513 | 0.00 | 0.00 | 8760.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV WITH REHEAT | 0.00 | 7397.32 | 1314.70 | 0.00 | 47.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FLR_3_DOAS | 0.00 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV WITH REHEAT | 0.0000 | 32.0168 | 32.0386 | 0.0000 | 32.6783 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
FLR_3_DOAS | 0.0000 | 2.9116 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:58:31
Surfaces by ClassTotal | Outdoors | |
Wall | 119 | 44 |
Floor | 25 | 0 |
Roof | 33 | 11 |
Internal Mass | 22 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 30 | 30 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 22 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 1306 |
Defaulted Fields | 1181 |
Fields with Defaults | 3945 |
Autosized Fields | 350 |
Autosizable Fields | 402 |
Autocalculated Fields | 280 |
Autocalculatable Fields | 539 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:58:31
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 6900.18 | 130132.03 | 06-MAY-05:00 | 469437.58 | 22-JUL-18:10 |
Electricity:Building | 2943.68 | 36656.90 | 02-JAN-02:10 | 182730.36 | 02-JAN-20:10 |
Electricity:Zone:BASEMENT | 315.54 | 3631.19 | 02-JAN-02:10 | 23630.80 | 02-JAN-20:10 |
Electricity:SpaceType:GENERAL | 2925.41 | 36182.64 | 02-JAN-02:10 | 182063.43 | 02-JAN-20:10 |
InteriorLights:Electricity | 1174.11 | 10291.59 | 02-JAN-02:10 | 93091.76 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BASEMENT | 165.29 | 1501.97 | 02-JAN-02:10 | 13517.00 | 02-JAN-20:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 1174.11 | 10291.59 | 02-JAN-02:10 | 93091.76 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity | 1174.11 | 10291.59 | 02-JAN-02:10 | 93091.76 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 165.29 | 1501.97 | 02-JAN-02:10 | 13517.00 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 1174.11 | 10291.59 | 02-JAN-02:10 | 93091.76 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_1_FLR_1 | 18.59 | 220.70 | 02-JAN-02:10 | 1372.90 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 8.40 | 76.37 | 02-JAN-02:10 | 687.30 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 8.40 | 76.37 | 02-JAN-02:10 | 687.30 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_2_FLR_1 | 21.53 | 255.58 | 02-JAN-02:10 | 1589.82 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 9.73 | 88.43 | 02-JAN-02:10 | 795.89 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 9.73 | 88.43 | 02-JAN-02:10 | 795.89 | 02-JAN-20:10 |
Electricity:Zone:MECH_FLR_1 | 30.66 | 342.02 | 02-JAN-02:10 | 2327.13 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:MECH_FLR_1 | 18.19 | 165.30 | 02-JAN-02:10 | 1487.69 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:MECH_FLR_1 | 18.19 | 165.30 | 02-JAN-02:10 | 1487.69 | 02-JAN-20:10 |
Electricity:Zone:STORAGE_FLR_1 | 6.94 | 81.32 | 02-JAN-02:10 | 515.26 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 3.34 | 30.34 | 02-JAN-02:10 | 273.10 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 3.34 | 30.34 | 02-JAN-02:10 | 273.10 | 02-JAN-20:10 |
Electricity:Zone:LAUNDRY_FLR_1 | 72.06 | 1000.18 | 02-JAN-02:10 | 4910.17 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 4.13 | 37.49 | 02-JAN-02:10 | 337.37 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 4.13 | 37.49 | 02-JAN-02:10 | 337.37 | 02-JAN-20:10 |
Electricity:Zone:CAFE_FLR_1 | 40.96 | 445.13 | 02-JAN-02:10 | 3142.50 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CAFE_FLR_1 | 26.62 | 241.91 | 02-JAN-02:10 | 2177.23 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CAFE_FLR_1 | 26.62 | 241.91 | 02-JAN-02:10 | 2177.23 | 02-JAN-20:10 |
Electricity:Zone:LOBBY_FLR_1 | 293.89 | 3428.00 | 02-JAN-02:10 | 21878.53 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 144.90 | 1316.59 | 02-JAN-02:10 | 11849.32 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 144.90 | 1316.59 | 02-JAN-02:10 | 11849.32 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_3 | 32.70 | 383.52 | 01-JAN-02:10 | 2308.42 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 20.41 | 172.80 | 01-JAN-02:10 | 1570.91 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 20.41 | 172.80 | 01-JAN-02:10 | 1570.91 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_3 | 32.70 | 383.47 | 01-JAN-02:10 | 2308.15 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 20.41 | 172.78 | 01-JAN-02:10 | 1570.72 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 20.41 | 172.78 | 01-JAN-02:10 | 1570.72 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT19_FLR_3 | 472.46 | 5984.83 | 01-JAN-02:10 | 32482.97 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 243.71 | 2063.36 | 01-JAN-02:10 | 18757.86 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 243.71 | 2063.36 | 01-JAN-02:10 | 18757.86 | 01-JAN-19:10 |
Electricity:Zone:ROOM_4_MULT19_FLR_3 | 472.59 | 5986.46 | 01-JAN-02:10 | 32491.86 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 243.77 | 2063.93 | 01-JAN-02:10 | 18762.99 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 243.77 | 2063.93 | 01-JAN-02:10 | 18762.99 | 01-JAN-19:10 |
Electricity:Zone:ROOM_5_FLR_3 | 32.70 | 383.52 | 01-JAN-02:10 | 2308.42 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 20.41 | 172.80 | 01-JAN-02:10 | 1570.91 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 20.41 | 172.80 | 01-JAN-02:10 | 1570.91 | 01-JAN-19:10 |
Electricity:Zone:ROOM_6_FLR_3 | 32.70 | 383.47 | 01-JAN-02:10 | 2308.15 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 20.41 | 172.78 | 01-JAN-02:10 | 1570.72 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 20.41 | 172.78 | 01-JAN-02:10 | 1570.72 | 01-JAN-19:10 |
Electricity:Zone:CORRIDOR_FLR_3 | 62.74 | 570.05 | 02-JAN-02:10 | 5130.41 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 62.74 | 570.05 | 02-JAN-02:10 | 5130.41 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 62.74 | 570.05 | 02-JAN-02:10 | 5130.41 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_6 | 8.18 | 95.88 | 01-JAN-02:10 | 577.11 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 5.10 | 43.20 | 01-JAN-02:10 | 392.73 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 5.10 | 43.20 | 01-JAN-02:10 | 392.73 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_6 | 8.17 | 95.87 | 01-JAN-02:10 | 577.04 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 5.10 | 43.19 | 01-JAN-02:10 | 392.68 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 5.10 | 43.19 | 01-JAN-02:10 | 392.68 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT9_FLR_6 | 55.96 | 708.92 | 01-JAN-02:10 | 3847.72 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 28.87 | 244.41 | 01-JAN-02:10 | 2221.93 | 01-JAN-19:10 |
LightsWired:InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 28.87 | 244.41 | 01-JAN-02:10 | 2221.93 | 01-JAN-19:10 |
Electricity:Zone:BANQUET_FLR_6 | 222.61 | 2674.12 | 02-JAN-02:10 | 10571.30 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 46.75 | 424.82 | 02-JAN-02:10 | 3823.39 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 46.75 | 424.82 | 02-JAN-02:10 | 3823.39 | 02-JAN-20:10 |
Electricity:Zone:DINING_FLR_6 | 222.61 | 2674.12 | 02-JAN-02:10 | 10571.30 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:DINING_FLR_6 | 46.75 | 424.82 | 02-JAN-02:10 | 3823.39 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:DINING_FLR_6 | 46.75 | 424.82 | 02-JAN-02:10 | 3823.39 | 02-JAN-20:10 |
Electricity:Zone:KITCHEN_FLR_6 | 470.78 | 6777.71 | 02-JAN-02:10 | 19298.76 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 12.48 | 113.42 | 02-JAN-02:10 | 1020.78 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 12.48 | 113.42 | 02-JAN-02:10 | 1020.78 | 02-JAN-20:10 |
Electricity:Zone:CORRIDOR_FLR_6 | 16.60 | 150.83 | 02-JAN-02:10 | 1357.44 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 16.60 | 150.83 | 02-JAN-02:10 | 1357.44 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 16.60 | 150.83 | 02-JAN-02:10 | 1357.44 | 02-JAN-20:10 |
InteriorEquipment:Electricity | 1751.30 | 25891.05 | 02-JAN-02:10 | 89674.66 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 150.26 | 2129.22 | 02-JAN-02:10 | 10113.80 | 02-JAN-20:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 1751.30 | 25891.05 | 02-JAN-02:10 | 89674.66 | 02-JAN-07:10 |
MiscPlug:InteriorEquipment:Electricity | 959.56 | 15202.41 | 02-JAN-02:10 | 59492.27 | 02-JAN-07:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 150.26 | 2129.22 | 02-JAN-02:10 | 10113.80 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 959.56 | 15202.41 | 02-JAN-02:10 | 59492.27 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.79 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.79 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 12.29 | 210.72 | 01-JAN-00:10 | 948.23 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 12.29 | 210.72 | 01-JAN-00:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 12.29 | 210.69 | 01-JAN-00:10 | 948.12 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 12.29 | 210.69 | 01-JAN-00:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 228.75 | 3921.46 | 01-JAN-00:10 | 17646.57 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 228.75 | 3921.46 | 01-JAN-00:10 | 17646.57 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 228.82 | 3922.53 | 01-JAN-00:10 | 17651.40 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 228.82 | 3922.53 | 01-JAN-00:10 | 17651.40 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 12.29 | 210.72 | 01-JAN-00:10 | 948.23 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 12.29 | 210.72 | 01-JAN-00:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 12.29 | 210.69 | 01-JAN-00:10 | 948.12 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 12.29 | 210.69 | 01-JAN-00:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 3.07 | 52.68 | 01-JAN-00:10 | 237.06 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 3.07 | 52.68 | 01-JAN-00:10 | 237.06 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 3.07 | 52.67 | 01-JAN-00:10 | 237.03 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 3.07 | 52.67 | 01-JAN-00:10 | 237.03 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 27.10 | 464.51 | 01-JAN-00:10 | 2090.30 | 01-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 27.10 | 464.51 | 01-JAN-00:10 | 2090.30 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 440.03 | 6190.03 | 01-JAN-00:10 | 16686.59 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 410.33 | 5248.28 | 01-JAN-00:10 | 15744.84 | 01-JAN-07:10 |
ReachInFreezer:InteriorEquipment:Electricity | 16.27 | 515.92 | 01-JAN-00:10 | 515.92 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 16.27 | 515.92 | 01-JAN-00:10 | 515.92 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 16.27 | 515.92 | 01-JAN-00:10 | 515.92 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 13.43 | 425.83 | 01-JAN-00:10 | 425.83 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 13.43 | 425.83 | 01-JAN-00:10 | 425.83 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 13.43 | 425.83 | 01-JAN-00:10 | 425.83 | 01-JAN-00:10 |
Refrigeration:Electricity | 74.39 | 1237.96 | 10-JAN-23:30 | 3643.15 | 18-JUL-07:00 |
Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 18.27 | 261.51 | 02-JAN-11:30 | 2271.91 | 01-JAN-11:10 |
General:Refrigeration:Electricity | 18.27 | 261.51 | 02-JAN-11:30 | 2271.91 | 01-JAN-11:10 |
General:Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 18.27 | 261.51 | 02-JAN-11:30 | 2271.91 | 01-JAN-11:10 |
Electricity:Plant | 753.74 | 2862.54 | 01-NOV-01:20 | 183263.24 | 22-JUL-18:10 |
LowTempRefrigeration:Refrigeration:Electricity | 22.38 | 0.00 | 01-JAN-11:10 | 1901.39 | 20-APR-10:50 |
MedTempRefrigeration:Refrigeration:Electricity | 33.73 | 935.87 | 11-JAN-05:00 | 1197.79 | 18-JUL-13:10 |
Fans:Electricity | 1809.73 | 53944.17 | 04-OCT-01:40 | 76877.01 | 22-JUL-15:20 |
Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Electricity:HVAC | 2294.26 | 55264.56 | 09-AUG-04:40 | 95950.27 | 22-JUL-18:20 |
ExteriorEquipment:Electricity | 679.68 | 10574.27 | 02-JAN-02:20 | 40537.60 | 02-JAN-07:20 |
Transformer:ExteriorEquipment:Electricity | 32.92 | 556.27 | 02-JAN-02:20 | 1912.91 | 02-JAN-21:10 |
ElectricityPurchased:Facility | 6900.18 | 130132.03 | 06-MAY-05:00 | 469437.58 | 22-JUL-18:10 |
ElectricityPurchased:Plant | 6900.18 | 130132.03 | 06-MAY-05:00 | 469437.58 | 22-JUL-18:10 |
Cogeneration:ElectricityPurchased | 6900.18 | 130132.03 | 06-MAY-05:00 | 469437.58 | 22-JUL-18:10 |
General:Cogeneration:ElectricityPurchased | 6900.18 | 130132.03 | 06-MAY-05:00 | 469437.58 | 22-JUL-18:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 6900.18 | 130132.03 | 06-MAY-05:00 | 469437.58 | 22-JUL-18:10 |
ElectricityNet:Plant | 6900.18 | 130132.03 | 06-MAY-05:00 | 469437.58 | 22-JUL-18:10 |
Cogeneration:ElectricityNet | 6900.18 | 130132.03 | 06-MAY-05:00 | 469437.58 | 22-JUL-18:10 |
General:Cogeneration:ElectricityNet | 6900.18 | 130132.03 | 06-MAY-05:00 | 469437.58 | 22-JUL-18:10 |
General:Fans:Electricity | 1809.73 | 53944.17 | 04-OCT-01:40 | 76877.01 | 22-JUL-15:20 |
ExteriorLights:Electricity | 261.73 | 0.00 | 01-JAN-08:20 | 16690.39 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 261.73 | 0.00 | 01-JAN-08:20 | 16690.39 | 01-JAN-00:10 |
ElevatorLift:ExteriorEquipment:Electricity | 616.11 | 9046.01 | 01-JAN-00:10 | 37691.69 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 30.65 | 972.00 | 01-JAN-00:10 | 972.00 | 01-JAN-00:10 |
HeatRecovery:Electricity | 451.61 | 0.00 | 20-APR-15:20 | 17755.68 | 30-APR-17:10 |
General:HeatRecovery:Electricity | 451.61 | 0.00 | 20-APR-15:20 | 17755.68 | 30-APR-17:10 |
WaterSystems:Electricity | 90.78 | 1087.06 | 18-SEP-00:20 | 4739.90 | 02-JAN-07:10 |
Water Heater:WaterSystems:Electricity | 90.78 | 1087.06 | 18-SEP-00:20 | 4739.90 | 02-JAN-07:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 474.04 | 0.00 | 01-JAN-00:10 | 167714.04 | 22-JUL-18:10 |
General:Cooling:Electricity | 474.04 | 0.00 | 01-JAN-00:10 | 167714.04 | 22-JUL-18:10 |
Pumps:Electricity | 132.81 | 216.74 | 11-NOV-08:50 | 8954.24 | 22-JUL-18:10 |
General:Pumps:Electricity | 132.81 | 216.74 | 11-NOV-08:50 | 8954.24 | 22-JUL-18:10 |
WIRED_LTG_ELECTRICITY | 41.33 | 0.00 | 01-JAN-00:10 | 3276.83 | 02-JAN-20:20 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 6754.67 | 48779.99 | 21-JUL-23:20 | 523100.38 | 11-JAN-17:50 |
NaturalGas:Building | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
NaturalGas:SpaceType:GENERAL | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:NaturalGas | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
InteriorEquipment:NaturalGas:SpaceType:GENERAL | 1788.84 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
Laundry:InteriorEquipment:NaturalGas | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:NaturalGas:Zone:LAUNDRY_FLR_1 | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 590.20 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
NaturalGas:Plant | 4965.83 | 29984.18 | 22-JUL-23:30 | 433488.17 | 11-JAN-17:50 |
WaterSystems:NaturalGas | 3330.89 | 18467.44 | 07-JAN-11:10 | 289920.15 | 16-FEB-21:40 |
Water Heater:WaterSystems:NaturalGas | 3330.89 | 18467.44 | 07-JAN-11:10 | 289920.15 | 16-FEB-21:40 |
Heating:NaturalGas | 1634.94 | 1366.33 | 14-AUG-21:10 | 203209.92 | 10-JAN-09:10 |
Boiler:Heating:NaturalGas | 1634.94 | 1366.33 | 14-AUG-21:10 | 203209.92 | 10-JAN-09:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 1418.60 | 0.00 | 01-JAN-00:10 | 661295.17 | 25-JUN-18:20 |
PlantLoopCoolingDemand:HVAC | 1418.60 | 0.00 | 01-JAN-00:10 | 661295.17 | 25-JUN-18:20 |
CoolingCoils:PlantLoopCoolingDemand | 1418.60 | 0.00 | 01-JAN-00:10 | 661295.17 | 25-JUN-18:20 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-21:10 |
Water:Plant | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-21:10 |
WaterSystems:Water | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-21:10 |
Water Heater:WaterSystems:Water | 5742.51 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-19:20 |
MainsWater:Facility | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-21:10 |
MainsWater:Plant | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-21:10 |
WaterSystems:MainsWater | 9857.19 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-21:10 |
Water Heater:WaterSystems:MainsWater | 5742.51 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-19:20 |
WaterUse:WaterSystems:Water | 4114.69 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-07:10 |
WaterUse:WaterSystems:MainsWater | 4114.69 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-07:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 18918.11 | 252580.51 | 18-OCT-13:40 | 2641870.71 | 25-JUN-18:10 |
EnergyTransfer:Building | 5354.46 | 87304.61 | 10-DEC-15:00 | 378982.62 | 22-JUL-18:20 |
EnergyTransfer:Zone:KITCHEN_FLR_6 | 732.01 | 11570.55 | 11-JAN-04:00 | 36298.79 | 23-JUL-10:40 |
Refrigeration:EnergyTransfer | 187.63 | 3686.45 | 10-JAN-23:30 | 10380.41 | 18-JUL-07:00 |
Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 93.82 | 1843.22 | 10-JAN-23:30 | 5190.21 | 18-JUL-07:00 |
General:Refrigeration:EnergyTransfer | 93.82 | 1843.22 | 10-JAN-23:30 | 5190.21 | 18-JUL-07:00 |
General:Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 93.82 | 1843.22 | 10-JAN-23:30 | 5190.21 | 18-JUL-07:00 |
EnergyTransfer:Plant | 5544.61 | 42620.90 | 09-FEB-23:20 | 1532778.63 | 25-JUN-18:20 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 25.74 | 0.00 | 01-JAN-11:10 | 2686.44 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 68.08 | 1757.60 | 11-JAN-05:00 | 2543.38 | 18-JUL-13:10 |
EnergyTransfer:Zone:BASEMENT | 440.29 | 7337.57 | 08-MAY-11:00 | 21036.06 | 13-SEP-18:10 |
Heating:EnergyTransfer | 91.05 | 0.00 | 01-JAN-08:30 | 55022.59 | 12-JAN-16:10 |
Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer | 91.05 | 0.00 | 01-JAN-08:30 | 55022.59 | 12-JAN-16:10 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer | 5169.59 | 77991.50 | 10-DEC-16:00 | 375245.57 | 22-JUL-18:20 |
Cooling:EnergyTransfer:Zone:BASEMENT | 440.29 | 7337.57 | 08-MAY-11:00 | 21036.06 | 13-SEP-18:10 |
General:Cooling:EnergyTransfer | 5169.59 | 77991.50 | 10-DEC-16:00 | 375245.57 | 22-JUL-18:20 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 440.29 | 7337.57 | 08-MAY-11:00 | 21036.06 | 13-SEP-18:10 |
EnergyTransfer:Zone:RETAIL_1_FLR_1 | 33.35 | 0.01 | 21-JAN-04:20 | 4418.15 | 27-SEP-10:40 |
Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 0.61 | 0.00 | 01-JAN-00:10 | 525.39 | 10-JAN-08:00 |
General:Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 0.61 | 0.00 | 01-JAN-00:10 | 525.39 | 10-JAN-08:00 |
Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 32.74 | 0.00 | 02-JAN-02:20 | 4418.15 | 27-SEP-10:40 |
General:Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 32.74 | 0.00 | 02-JAN-02:20 | 4418.15 | 27-SEP-10:40 |
EnergyTransfer:Zone:RETAIL_2_FLR_1 | 36.53 | 289.04 | 10-DEC-15:50 | 2158.78 | 22-JUL-18:10 |
Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 36.53 | 289.04 | 10-DEC-15:50 | 2158.78 | 22-JUL-18:10 |
General:Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 36.53 | 289.04 | 10-DEC-15:50 | 2158.78 | 22-JUL-18:10 |
EnergyTransfer:Zone:MECH_FLR_1 | 23.54 | 0.12 | 10-JAN-17:50 | 1994.41 | 22-JUL-18:20 |
Heating:EnergyTransfer:Zone:MECH_FLR_1 | 0.01 | 0.00 | 01-JAN-00:10 | 187.85 | 12-JAN-05:00 |
General:Heating:EnergyTransfer:Zone:MECH_FLR_1 | 0.01 | 0.00 | 01-JAN-00:10 | 187.85 | 12-JAN-05:00 |
Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 23.53 | 0.00 | 09-JAN-02:40 | 1994.41 | 22-JUL-18:20 |
General:Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 23.53 | 0.00 | 09-JAN-02:40 | 1994.41 | 22-JUL-18:20 |
EnergyTransfer:Zone:STORAGE_FLR_1 | 7.62 | 0.02 | 20-DEC-17:30 | 901.58 | 22-JUL-18:50 |
Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 0.26 | 0.00 | 01-JAN-00:10 | 231.68 | 12-JAN-14:00 |
General:Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 0.26 | 0.00 | 01-JAN-00:10 | 231.68 | 12-JAN-14:00 |
Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 7.37 | 0.00 | 01-JAN-02:40 | 901.58 | 22-JUL-18:50 |
General:Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 7.37 | 0.00 | 01-JAN-02:40 | 901.58 | 22-JUL-18:50 |
EnergyTransfer:Zone:LAUNDRY_FLR_1 | 594.12 | 9017.10 | 09-JAN-05:00 | 36973.20 | 12-JUN-20:00 |
Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 594.12 | 9017.10 | 09-JAN-05:00 | 36973.20 | 12-JUN-20:00 |
General:Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 594.12 | 9017.10 | 09-JAN-05:00 | 36973.20 | 12-JUN-20:00 |
EnergyTransfer:Zone:CAFE_FLR_1 | 250.65 | 974.73 | 10-DEC-16:00 | 16004.01 | 12-SEP-15:20 |
Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 250.65 | 974.73 | 10-DEC-16:00 | 16004.01 | 12-SEP-15:20 |
General:Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 250.65 | 974.73 | 10-DEC-16:00 | 16004.01 | 12-SEP-15:20 |
EnergyTransfer:Zone:LOBBY_FLR_1 | 872.28 | 7751.06 | 10-DEC-16:00 | 44785.43 | 14-AUG-18:20 |
Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 872.28 | 7751.06 | 10-DEC-16:00 | 44785.43 | 14-AUG-18:20 |
General:Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 872.28 | 7751.06 | 10-DEC-16:00 | 44785.43 | 14-AUG-18:20 |
EnergyTransfer:Zone:ROOM_1_FLR_3 | 48.01 | 0.10 | 01-JAN-10:10 | 11891.05 | 13-JUN-18:10 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 13.01 | 0.00 | 01-JAN-08:10 | 4436.27 | 27-DEC-09:10 |
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 13.01 | 0.00 | 01-JAN-08:10 | 4436.27 | 27-DEC-09:10 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 35.00 | 0.00 | 01-JAN-00:10 | 11891.05 | 13-JUN-18:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 35.00 | 0.00 | 01-JAN-00:10 | 11891.05 | 13-JUN-18:10 |
EnergyTransfer:Zone:ROOM_2_FLR_3 | 43.81 | 0.01 | 16-DEC-12:50 | 11501.34 | 13-JUN-18:10 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 16.52 | 0.00 | 01-JAN-08:10 | 4743.82 | 10-JAN-09:10 |
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 16.52 | 0.00 | 01-JAN-08:10 | 4743.82 | 10-JAN-09:10 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 27.29 | 0.00 | 01-JAN-00:10 | 11501.34 | 13-JUN-18:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 27.29 | 0.00 | 01-JAN-00:10 | 11501.34 | 13-JUN-18:10 |
EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 427.51 | 3.27 | 16-DEC-16:50 | 64905.00 | 27-SEP-13:20 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 0.28 | 0.00 | 01-JAN-00:10 | 6418.64 | 17-DEC-04:40 |
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 0.28 | 0.00 | 01-JAN-00:10 | 6418.64 | 17-DEC-04:40 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 427.22 | 0.00 | 14-DEC-02:50 | 64905.00 | 27-SEP-13:20 |
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 427.22 | 0.00 | 14-DEC-02:50 | 64905.00 | 27-SEP-13:20 |
EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 392.16 | 0.63 | 20-DEC-16:50 | 67406.11 | 13-JUN-18:20 |
Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 5.37 | 0.00 | 01-JAN-00:10 | 29085.82 | 11-JAN-16:10 |
General:Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 5.37 | 0.00 | 01-JAN-00:10 | 29085.82 | 11-JAN-16:10 |
Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 386.79 | 0.00 | 01-JAN-16:30 | 67406.11 | 13-JUN-18:20 |
General:Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 386.79 | 0.00 | 01-JAN-16:30 | 67406.11 | 13-JUN-18:20 |
EnergyTransfer:Zone:ROOM_5_FLR_3 | 48.54 | 0.23 | 28-MAY-03:00 | 10757.50 | 23-JUL-08:10 |
Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 13.02 | 0.00 | 01-JAN-08:10 | 4486.89 | 12-JAN-16:10 |
General:Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 13.02 | 0.00 | 01-JAN-08:10 | 4486.89 | 12-JAN-16:10 |
Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 35.52 | 0.00 | 01-JAN-00:10 | 10757.50 | 23-JUL-08:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 35.52 | 0.00 | 01-JAN-00:10 | 10757.50 | 23-JUL-08:10 |
EnergyTransfer:Zone:ROOM_6_FLR_3 | 43.60 | 0.14 | 21-MAY-01:20 | 10398.82 | 23-JUL-08:10 |
Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 16.42 | 0.00 | 01-JAN-08:10 | 4701.52 | 10-JAN-16:10 |
General:Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 16.42 | 0.00 | 01-JAN-08:10 | 4701.52 | 10-JAN-16:10 |
Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 27.18 | 0.00 | 01-JAN-00:10 | 10398.82 | 23-JUL-08:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 27.18 | 0.00 | 01-JAN-00:10 | 10398.82 | 23-JUL-08:10 |
EnergyTransfer:Zone:CORRIDOR_FLR_3 | 169.80 | 0.16 | 18-DEC-08:00 | 12607.30 | 23-JUL-10:40 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 0.39 | 0.00 | 01-JAN-00:10 | 1442.62 | 10-DEC-16:00 |
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 0.39 | 0.00 | 01-JAN-00:10 | 1442.62 | 10-DEC-16:00 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 169.42 | 0.00 | 03-JAN-09:20 | 12607.30 | 23-JUL-10:40 |
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 169.42 | 0.00 | 03-JAN-09:20 | 12607.30 | 23-JUL-10:40 |
EnergyTransfer:Zone:ROOM_1_FLR_6 | 15.01 | 0.02 | 05-NOV-19:20 | 3397.62 | 13-JUN-18:10 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 5.60 | 0.00 | 01-JAN-08:10 | 1497.87 | 27-DEC-16:10 |
General:Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 5.60 | 0.00 | 01-JAN-08:10 | 1497.87 | 27-DEC-16:10 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 9.42 | 0.00 | 01-JAN-00:10 | 3397.62 | 13-JUN-18:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 9.42 | 0.00 | 01-JAN-00:10 | 3397.62 | 13-JUN-18:10 |
EnergyTransfer:Zone:ROOM_2_FLR_6 | 14.08 | 0.03 | 30-JUL-03:30 | 3245.98 | 13-JUN-18:10 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 6.78 | 0.00 | 01-JAN-08:10 | 1564.00 | 27-DEC-16:10 |
General:Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 6.78 | 0.00 | 01-JAN-08:10 | 1564.00 | 27-DEC-16:10 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 7.30 | 0.00 | 01-JAN-00:10 | 3245.98 | 13-JUN-18:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 7.30 | 0.00 | 01-JAN-00:10 | 3245.98 | 13-JUN-18:10 |
EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 80.30 | 0.09 | 18-MAY-23:30 | 18432.75 | 12-SEP-15:10 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 10.84 | 0.00 | 01-JAN-08:10 | 6166.61 | 30-DEC-16:10 |
General:Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 10.84 | 0.00 | 01-JAN-08:10 | 6166.61 | 30-DEC-16:10 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 69.46 | 0.00 | 01-JAN-00:10 | 18432.75 | 12-SEP-15:10 |
General:Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 69.46 | 0.00 | 01-JAN-00:10 | 18432.75 | 12-SEP-15:10 |
EnergyTransfer:Zone:BANQUET_FLR_6 | 488.54 | 8082.10 | 11-JAN-09:30 | 22243.00 | 22-JUL-18:10 |
Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 488.54 | 8082.10 | 11-JAN-09:30 | 22243.00 | 22-JUL-18:10 |
General:Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 488.54 | 8082.10 | 11-JAN-09:30 | 22243.00 | 22-JUL-18:10 |
EnergyTransfer:Zone:DINING_FLR_6 | 525.67 | 9268.81 | 12-JAN-15:00 | 23662.83 | 22-JUL-18:10 |
Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 525.67 | 9268.81 | 12-JAN-15:00 | 23662.83 | 22-JUL-18:10 |
General:Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 525.67 | 9268.81 | 12-JAN-15:00 | 23662.83 | 22-JUL-18:10 |
Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 638.19 | 9425.11 | 11-JAN-04:00 | 31212.90 | 23-JUL-10:40 |
General:Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 638.19 | 9425.11 | 11-JAN-04:00 | 31212.90 | 23-JUL-10:40 |
EnergyTransfer:Zone:CORRIDOR_FLR_6 | 67.02 | 0.02 | 25-DEC-20:00 | 7396.15 | 23-JUL-10:40 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 1.94 | 0.00 | 01-JAN-00:10 | 1747.35 | 10-JAN-08:00 |
General:Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 1.94 | 0.00 | 01-JAN-00:10 | 1747.35 | 10-JAN-08:00 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 65.09 | 0.00 | 01-JAN-01:20 | 7396.15 | 23-JUL-10:40 |
General:Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 65.09 | 0.00 | 01-JAN-01:20 | 7396.15 | 23-JUL-10:40 |
PlantLoopHeatingDemand:Facility | 1930.98 | 18830.63 | 21-JUL-22:10 | 203027.47 | 10-JAN-08:00 |
PlantLoopHeatingDemand:Plant | 798.36 | 10164.92 | 15-AUG-00:20 | 55889.63 | 13-FEB-07:10 |
WaterSystems:PlantLoopHeatingDemand | 798.36 | 10164.92 | 15-AUG-00:20 | 55889.63 | 13-FEB-07:10 |
General:WaterSystems:PlantLoopHeatingDemand | 798.36 | 10164.92 | 15-AUG-00:20 | 55889.63 | 13-FEB-07:10 |
EnergyTransfer:HVAC | 8019.05 | 33881.70 | 13-JUL-07:50 | 822236.10 | 25-JUN-18:10 |
HeatingCoils:EnergyTransfer | 1132.61 | 819.82 | 14-AUG-21:10 | 154295.47 | 10-JAN-09:10 |
PlantLoopHeatingDemand:HVAC | 1132.61 | 819.82 | 14-AUG-21:10 | 154295.47 | 10-JAN-09:10 |
HeatingCoils:PlantLoopHeatingDemand | 1132.61 | 819.82 | 14-AUG-21:10 | 154295.47 | 10-JAN-09:10 |
CoolingCoils:EnergyTransfer | 1418.60 | 0.00 | 01-JAN-00:10 | 661295.17 | 25-JUN-18:20 |
HeatRecoveryForHeating:EnergyTransfer | 5452.10 | 0.00 | 20-APR-15:20 | 640848.05 | 12-JAN-00:10 |
HeatRecoveryForCooling:EnergyTransfer | 15.73 | 0.00 | 01-JAN-00:10 | 206467.96 | 25-JUN-18:00 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:EnergyTransfer | 798.36 | 10164.92 | 15-AUG-00:20 | 55889.63 | 13-FEB-07:10 |
WaterUse:WaterSystems:EnergyTransfer | 798.36 | 10164.92 | 15-AUG-00:20 | 55889.63 | 13-FEB-07:10 |
Boilers:EnergyTransfer | 1122.99 | 820.83 | 14-AUG-21:10 | 158305.36 | 10-JAN-09:10 |
Chillers:EnergyTransfer | 1527.70 | 0.00 | 01-JAN-00:10 | 662950.67 | 25-JUN-18:20 |
HeatRejection:EnergyTransfer | 2001.74 | 0.00 | 01-JAN-00:10 | 824420.51 | 25-JUN-18:20 |
General:HeatRejection:EnergyTransfer | 2001.74 | 0.00 | 01-JAN-00:10 | 824420.51 | 25-JUN-18:20 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:58:31
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 0.000 | -440.291 | 0.000 | 0.000 | 158.390 | 165.288 | 150.255 | 0.000 | 0.000 | 0.000 | 0.001 | 0.000 | 0.000 | 0.000 | 0.000 | -33.642 |
RETAIL_1_FLR_1 | 0.000 | 0.000 | 0.609 | -32.739 | 0.000 | 0.000 | 16.175 | 8.404 | 10.186 | 23.766 | 0.000 | 0.013 | 0.000 | 0.000 | -11.216 | 0.000 | -4.592 | -10.606 |
RETAIL_2_FLR_1 | 0.000 | 0.000 | 0.000 | -36.532 | 0.000 | 0.000 | 18.673 | 9.732 | 11.795 | 0.000 | 0.000 | 0.005 | 0.000 | 0.000 | 0.000 | 0.000 | -1.778 | -1.895 |
MECH_FLR_1 | 0.000 | 0.000 | 0.012 | -23.529 | 0.000 | 0.000 | 3.958 | 18.192 | 12.471 | 0.000 | 0.000 | 0.013 | 0.000 | 0.000 | 0.000 | 0.000 | -4.192 | -6.924 |
STORAGE_FLR_1 | 0.000 | 0.000 | 0.256 | -7.367 | 0.000 | 0.000 | 3.046 | 3.340 | 3.598 | 0.000 | 0.000 | 0.007 | 0.000 | 0.000 | 0.000 | 0.000 | -2.417 | -0.462 |
LAUNDRY_FLR_1 | 0.000 | 0.000 | 0.000 | -594.117 | 0.000 | 0.000 | 12.193 | 4.125 | 658.131 | 0.000 | 0.000 | 0.017 | 0.000 | 0.000 | 0.000 | 0.000 | -5.921 | -74.428 |
CAFE_FLR_1 | 0.000 | 0.000 | 0.000 | -250.649 | 0.000 | 0.000 | 212.375 | 26.624 | 14.341 | 66.580 | 0.000 | 0.029 | 0.000 | 0.000 | -31.627 | 0.000 | -10.162 | -27.512 |
LOBBY_FLR_1 | 0.000 | 0.000 | 0.000 | -872.284 | 0.000 | 0.000 | 628.258 | 144.896 | 148.998 | 88.126 | 0.000 | 0.088 | 0.000 | 0.000 | -42.306 | 0.000 | -29.136 | -66.640 |
ROOM_1_FLR_3 | 17.922 | -25.889 | 0.000 | -14.022 | 0.000 | 0.000 | 9.748 | 20.410 | 12.292 | 43.873 | 0.000 | 0.026 | 0.000 | 0.000 | -26.094 | 0.000 | -11.452 | -26.814 |
ROOM_2_FLR_3 | 21.953 | -19.024 | 0.000 | -13.694 | 0.000 | 0.000 | 9.778 | 20.407 | 12.291 | 30.490 | 0.000 | 0.026 | 0.000 | 0.000 | -26.272 | 0.000 | -11.324 | -24.631 |
ROOM_3_MULT19_FLR_3 | 0.867 | -197.878 | 0.000 | -229.928 | 0.000 | 0.000 | 0.000 | 243.708 | 228.754 | 275.771 | 0.000 | 0.060 | 0.002 | 0.000 | -155.744 | 0.000 | -79.975 | -85.634 |
ROOM_4_MULT19_FLR_3 | 24.437 | -216.247 | 0.000 | -189.606 | 0.000 | 0.000 | 185.223 | 243.774 | 228.817 | 72.265 | 0.000 | 0.248 | 0.000 | 0.000 | -146.923 | 0.000 | -67.223 | -134.765 |
ROOM_5_FLR_3 | 17.884 | -26.272 | 0.000 | -14.113 | 0.000 | 0.000 | 9.739 | 20.410 | 12.292 | 44.320 | 0.000 | 0.026 | 0.000 | 0.000 | -25.634 | 0.000 | -11.483 | -27.170 |
ROOM_6_FLR_3 | 21.799 | -18.694 | 0.000 | -13.858 | 0.000 | 0.000 | 9.764 | 20.407 | 12.291 | 30.668 | 0.000 | 0.026 | 0.000 | 0.000 | -25.608 | 0.000 | -11.377 | -25.418 |
CORRIDOR_FLR_3 | 0.000 | 0.000 | 0.387 | -169.416 | 0.000 | 0.000 | 124.920 | 62.736 | 0.000 | 40.788 | 0.000 | 0.035 | 0.000 | 0.000 | -32.273 | 0.000 | -12.972 | -14.204 |
ROOM_1_FLR_6 | 6.978 | -7.317 | 0.000 | -3.479 | 0.000 | 0.000 | 2.440 | 5.102 | 3.073 | 10.878 | 0.000 | 0.006 | 0.000 | 0.000 | -6.462 | 0.000 | -2.885 | -8.334 |
ROOM_2_FLR_6 | 8.297 | -5.409 | 0.000 | -3.406 | 0.000 | 0.000 | 2.447 | 5.102 | 3.073 | 7.538 | 0.000 | 0.007 | 0.000 | 0.000 | -6.498 | 0.000 | -2.857 | -8.293 |
ROOM_3_MULT9_FLR_6 | 16.836 | -52.392 | 0.000 | -23.057 | 0.000 | 0.000 | 21.858 | 28.868 | 27.097 | 60.404 | 0.000 | 0.038 | 0.000 | 0.000 | -30.695 | 0.000 | -14.120 | -34.836 |
BANQUET_FLR_6 | 0.000 | 0.000 | 0.000 | -488.538 | 0.000 | 0.000 | 359.186 | 46.753 | 175.857 | 8.263 | 0.000 | 0.017 | 0.000 | 0.000 | -17.241 | 0.000 | -6.857 | -77.440 |
DINING_FLR_6 | 0.000 | 0.000 | 0.000 | -525.675 | 0.000 | 0.000 | 357.639 | 46.753 | 175.857 | 8.075 | 0.000 | 0.016 | 0.000 | 0.000 | -17.637 | 0.000 | -6.895 | -38.133 |
KITCHEN_FLR_6 | 0.000 | 0.000 | 0.000 | -638.184 | 0.000 | 0.000 | 30.601 | 12.482 | 556.656 | 21.086 | 0.000 | 0.004 | 36.505 | 0.000 | -12.384 | 0.000 | -6.766 | 0.000 |
CORRIDOR_FLR_6 | 0.000 | 0.000 | 1.936 | -65.088 | 0.000 | 0.000 | 33.105 | 16.599 | 0.000 | 20.094 | 0.000 | 0.015 | 13.440 | 0.000 | -14.344 | 0.000 | -5.757 | -0.001 |
Total Facility | 136.974 | -569.123 | 3.200 | -4649.575 | 0.000 | 0.000 | 2209.516 | 1174.112 | 2458.123 | 852.986 | 0.000 | 0.724 | 49.948 | 0.000 | -628.959 | 0.000 | -310.143 | -727.782 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 13-SEP-18:02 | 0.00 | 0.00 | 0.00 | -21180.23 | 0.00 | 0.00 | 6161.73 | 12015.03 | 9581.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -6578.02 |
RETAIL_1_FLR_1 | 12-SEP-10:35 | 0.00 | 0.00 | 0.00 | -4500.07 | 0.00 | 0.00 | 175.58 | 190.92 | 252.59 | 5792.49 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -41.95 | -1869.56 |
RETAIL_2_FLR_1 | 22-JUL-18:07 | 0.00 | 0.00 | 0.00 | -2163.17 | 0.00 | 0.00 | 621.92 | 619.03 | 668.57 | 0.00 | 0.00 | 38.67 | 214.98 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 22-JUL-18:20 | 0.00 | 0.00 | 0.00 | -1995.49 | 0.00 | 0.00 | 131.53 | 1157.09 | 706.90 | 0.00 | 0.00 | 89.61 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -89.64 |
STORAGE_FLR_1 | 22-JUL-18:25 | 0.00 | 0.00 | 0.00 | -902.39 | 0.00 | 0.00 | 101.17 | 212.41 | 203.92 | 0.00 | 0.00 | 50.80 | 334.08 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 12-JUN-20:00 | 0.00 | 0.00 | 0.00 | -36974.87 | 0.00 | 0.00 | 419.86 | 337.37 | 44299.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -24.28 | -8057.46 |
CAFE_FLR_1 | 23-SEP-10:35 | 0.00 | 0.00 | 0.00 | -16213.68 | 0.00 | 0.00 | 3483.25 | 604.78 | 355.63 | 16652.41 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -80.61 | -4801.79 |
LOBBY_FLR_1 | 14-AUG-18:20 | 0.00 | 0.00 | 0.00 | -44789.97 | 0.00 | 0.00 | 24441.66 | 10532.73 | 9501.36 | 1335.46 | 0.00 | 362.23 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1383.46 |
ROOM_1_FLR_3 | 21-MAY-15:01 | 0.00 | -14202.45 | 0.00 | -651.38 | 0.00 | 0.00 | 130.72 | 518.40 | 305.54 | 10306.36 | 0.00 | 0.00 | 4115.55 | 0.00 | -0.00 | 0.00 | -522.75 | 0.00 |
ROOM_2_FLR_3 | 21-MAY-15:01 | 0.00 | -12718.50 | 0.00 | -651.72 | 0.00 | 0.00 | 130.71 | 518.34 | 305.51 | 9258.32 | 0.00 | 0.00 | 3689.39 | 0.00 | -0.00 | 0.00 | -532.06 | 0.00 |
ROOM_3_MULT19_FLR_3 | 27-SEP-13:20 | 0.00 | -54864.40 | 0.00 | -10035.37 | 0.00 | 0.00 | 0.00 | 5252.20 | 5097.90 | 76654.87 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -294.87 | -21810.34 |
ROOM_4_MULT19_FLR_3 | 12-JUN-18:02 | 0.00 | -67228.01 | 0.00 | -10247.90 | 0.00 | 0.00 | 6374.83 | 16699.06 | 9610.21 | 17268.03 | 0.00 | 393.75 | 27130.02 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 21-MAY-15:01 | 0.00 | -12770.16 | 0.00 | -643.89 | 0.00 | 0.00 | 130.72 | 518.40 | 305.54 | 2834.93 | 0.00 | 0.00 | 10133.38 | 0.00 | -0.00 | 0.00 | -508.93 | 0.00 |
ROOM_6_FLR_3 | 21-MAY-15:01 | 0.00 | -11522.96 | 0.00 | -643.77 | 0.00 | 0.00 | 130.72 | 518.34 | 305.51 | 1793.11 | 0.00 | 0.00 | 9936.21 | 0.00 | -0.00 | 0.00 | -517.15 | 0.00 |
CORRIDOR_FLR_3 | 23-JUL-10:35 | 0.00 | 0.00 | 0.00 | -12651.06 | 0.00 | 0.00 | 2044.88 | 1710.14 | 0.00 | 6836.10 | 0.00 | 0.00 | 2070.82 | 0.00 | -0.00 | 0.00 | -10.88 | 0.00 |
ROOM_1_FLR_6 | 21-MAY-15:01 | 0.00 | -3807.75 | 0.00 | -163.12 | 0.00 | 0.00 | 32.68 | 129.60 | 76.39 | 2554.55 | 0.00 | 0.00 | 1329.35 | 0.00 | -0.00 | 0.00 | -151.70 | 0.00 |
ROOM_2_FLR_6 | 21-MAY-15:01 | 0.00 | -3388.80 | 0.00 | -163.31 | 0.00 | 0.00 | 32.68 | 129.58 | 76.38 | 2293.80 | 0.00 | 0.00 | 1174.81 | 0.00 | -0.00 | 0.00 | -155.14 | 0.00 |
ROOM_3_MULT9_FLR_6 | 07-OCT-15:02 | 0.00 | -21089.06 | 0.00 | -1041.98 | 0.00 | 0.00 | 294.11 | 733.24 | 673.54 | 8849.62 | 0.00 | 0.00 | 12322.25 | 0.00 | -0.00 | 0.00 | -741.71 | 0.00 |
BANQUET_FLR_6 | 22-JUL-18:10 | 0.00 | 0.00 | 0.00 | -22256.39 | 0.00 | 0.00 | 11938.16 | 2973.75 | 6747.90 | 1966.04 | 0.00 | 128.48 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1497.94 |
DINING_FLR_6 | 22-JUL-18:10 | 0.00 | 0.00 | 0.00 | -23677.46 | 0.00 | 0.00 | 11862.93 | 2973.75 | 6747.90 | 1946.73 | 0.00 | 126.56 | 19.59 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 23-JUL-10:35 | 0.00 | 0.00 | 0.00 | -31216.92 | 0.00 | 0.00 | 464.15 | 340.26 | 24459.16 | 3966.47 | 0.00 | 0.00 | 2033.12 | 0.00 | -0.00 | 0.00 | -46.24 | 0.00 |
CORRIDOR_FLR_6 | 23-JUL-10:35 | 0.00 | 0.00 | 0.00 | -7606.36 | 0.00 | 0.00 | 545.54 | 452.48 | 0.00 | 3363.39 | 0.00 | 0.00 | 3247.73 | 0.00 | -0.00 | 0.00 | -2.77 | 0.00 |
Total Facility | 22-JUL-18:02 | 0.00 | -164360.61 | 0.00 | -233619.62 | 0.00 | 0.00 | 72266.65 | 82807.27 | 115371.52 | 67142.94 | 0.00 | 4888.82 | 55503.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 10-JAN-08:00 | 0.00 | 0.00 | 525.32 | 0.00 | 0.00 | 0.00 | 371.28 | 381.83 | 433.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1081.88 | 0.00 | -336.61 | -292.95 |
RETAIL_2_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 12-JAN-05:00 | 0.00 | 0.00 | 187.86 | 0.00 | 0.00 | 0.00 | 197.30 | 165.30 | 176.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -267.09 | -460.09 |
STORAGE_FLR_1 | 12-JAN-14:00 | 0.00 | 0.00 | 231.68 | 0.00 | 0.00 | 0.00 | 33.76 | 75.86 | 89.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -146.85 | -283.67 |
LAUNDRY_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 27-DEC-16:02 | 6469.03 | 290.03 | 0.00 | -290.03 | 0.00 | 0.00 | 293.99 | 439.85 | 273.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1618.93 | 0.00 | -477.01 | -5380.86 |
ROOM_2_FLR_3 | 11-JAN-09:02 | 6297.35 | 286.35 | 0.00 | -286.35 | 0.00 | 0.00 | 108.89 | 691.12 | 452.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1775.75 | 0.00 | -686.01 | -5088.59 |
ROOM_3_MULT19_FLR_3 | 17-DEC-04:40 | 6418.49 | 3428.50 | 0.00 | -3428.50 | 0.00 | 0.00 | 0.00 | 2063.36 | 3921.46 | 0.00 | 0.00 | 0.00 | 2089.25 | 0.00 | -11676.88 | 0.00 | -2815.68 | 0.00 |
ROOM_4_MULT19_FLR_3 | 11-JAN-16:01 | 33490.46 | 4174.59 | 0.00 | -4174.59 | 0.00 | 0.00 | 5471.13 | 5253.64 | 5099.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -9754.09 | 0.00 | -3406.21 | -36154.22 |
ROOM_5_FLR_3 | 27-DEC-16:02 | 6273.83 | 289.04 | 0.00 | -289.04 | 0.00 | 0.00 | 293.99 | 439.85 | 273.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1619.65 | 0.00 | -476.63 | -5185.33 |
ROOM_6_FLR_3 | 10-JAN-16:01 | 6185.74 | 281.08 | 0.00 | -281.08 | 0.00 | 0.00 | 293.99 | 439.80 | 273.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2009.84 | 0.00 | -656.73 | -4526.87 |
CORRIDOR_FLR_3 | 10-DEC-16:00 | 0.00 | 0.00 | 1442.61 | 0.00 | 0.00 | 0.00 | 1388.53 | 1140.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1945.04 | 0.00 | -591.69 | -1434.51 |
ROOM_1_FLR_6 | 27-DEC-16:02 | 1958.86 | 72.80 | 0.00 | -72.80 | 0.00 | 0.00 | 73.50 | 109.96 | 68.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -399.09 | 0.00 | -119.82 | -1691.90 |
ROOM_2_FLR_6 | 27-DEC-16:02 | 1900.89 | 72.00 | 0.00 | -72.00 | 0.00 | 0.00 | 73.50 | 109.95 | 68.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -395.74 | 0.00 | -119.51 | -1637.56 |
ROOM_3_MULT9_FLR_6 | 27-DEC-16:02 | 9670.10 | 472.80 | 0.00 | -472.80 | 0.00 | 0.00 | 661.47 | 622.14 | 603.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1900.33 | 0.00 | -553.17 | -9104.07 |
BANQUET_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 10-JAN-08:00 | 0.00 | 0.00 | 1747.05 | 0.00 | 0.00 | 0.00 | 739.07 | 754.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1386.77 | 0.00 | -429.52 | -1423.96 |
Total Facility | 10-DEC-16:02 | -9247.18 | 86435.84 | 2931.67 | -86435.84 | 0.00 | 0.00 | 37190.68 | 25732.27 | 75340.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -34302.55 | 0.00 | -11769.87 | -85875.20 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:58:31
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV WITH REHEAT | 22.6738 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 22.5604 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
FLR_3_DOAS | 2.0513 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.0513 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV WITH REHEAT | 22.5604 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 22.5604 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
FLR_3_DOAS | 2.0513 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.0513 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | VAV WITH REHEAT | 0.000000 | 106.4990 | 0.000432 | 1978.83 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | 0.000000 | 10.8290 | 0.001181 | 67.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | 0.000000 | 12.5400 | 0.001181 | 77.67 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
MECH_FLR_1 | VAV WITH REHEAT | 0.000000 | 2.6520 | 0.000000 | 164.24 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | 0.000000 | 2.0400 | 0.000610 | 94.76 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | 0.000000 | 8.4000 | 0.000000 | 78.04 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | 0.000000 | 142.3000 | 0.003581 | 188.86 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | 0.000000 | 422.4350 | 0.001448 | 1308.19 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1863.81 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1864.32 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000396 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | 0.000000 | 83.8280 | 0.000305 | 1557.62 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000396 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000396 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.000000 | 13.5000 | 0.000449 | 220.77 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003581 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DINING_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003581 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | 0.000000 | 22.2380 | 0.003556 | 103.30 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | 0.000000 | 22.1800 | 0.000305 | 412.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV WITH REHEAT | 0.00 | 0.001045 | 6694.0231 | 0.0000 | 0.0000 | 0.0000 | |
FLR_3_DOAS | 0.00 | 0.000441 | 4651.2638 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.4796 | 2.4796 | 2.4672 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4749 | 0.4749 | 0.4726 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2375 | 0.2375 | 0.2363 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2228 | 0.2228 | 0.2217 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1094 | 0.1094 | 0.1089 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.2823 | 3.2823 | 3.2659 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.8720 | 1.8720 | 1.8627 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.1653 | 5.1653 | 5.1395 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8371 | 0.8371 | 0.8371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8373 | 0.8373 | 0.8373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2511 | 1.2511 | 1.2449 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0992 | 0.0992 | 0.0992 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.1925 | 2.1925 | 2.1815 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.2999 | 2.2999 | 2.2884 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.3152 | 2.3152 | 2.3036 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7712 | 0.7712 | 0.7673 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV WITH REHEAT | 22.6738 | 22.5604 | 22.6738 | 22.5604 | 0.0000 | 1.0000 |
FLR_3_DOAS | 2.0513 | 2.0513 | 2.0513 | 2.0513 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.4672 | 2.4672 | 2.4672 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4726 | 0.4726 | 0.4726 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2363 | 0.2363 | 0.2363 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2217 | 0.2217 | 0.2217 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1089 | 0.1089 | 0.1089 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.2659 | 3.2659 | 3.2659 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.8627 | 1.8627 | 1.8627 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.1395 | 5.1395 | 5.1395 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8371 | 0.8371 | 0.8371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.8373 | 0.8373 | 0.8373 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0617 | 0.0617 | 0.0617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2449 | 1.2449 | 1.2449 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0154 | 0.0154 | 0.0154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.0992 | 0.0992 | 0.0992 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.1815 | 2.1815 | 2.1815 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.2884 | 2.2884 | 2.2884 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.3036 | 2.3036 | 2.3036 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7673 | 0.7673 | 0.7673 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV WITH REHEAT | 22.5604 | 22.5604 | 22.5604 | 22.5604 | 0.0000 | 1.0000 |
FLR_3_DOAS | 2.0513 | 2.0513 | 2.0513 | 2.0513 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:58:31
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** William R Fairchild WA USA TMY3 WMO#=727885 |
Total gross floor area [m2] | 11345.29 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 1978.83 | 1978.83 | 0.00 | 168.00 |
RETAIL_1_FLR_1 | 67.07 | 67.07 | 0.00 | 168.00 |
RETAIL_2_FLR_1 | 77.67 | 77.67 | 0.00 | 168.00 |
MECH_FLR_1 | 164.24 | 164.24 | 0.00 | 168.00 |
STORAGE_FLR_1 | 94.76 | 94.76 | 0.00 | 168.00 |
LAUNDRY_FLR_1 | 78.04 | 78.04 | 0.00 | 168.00 |
CAFE_FLR_1 | 188.86 | 188.86 | 0.00 | 168.00 |
LOBBY_FLR_1 | 1308.19 | 1308.19 | 0.00 | 168.00 |
ROOM_1_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT19_FLR_3 | 24.52 | 24.52 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 24.53 | 24.53 | 0.00 | 168.00 |
ROOM_5_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_6_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
CORRIDOR_FLR_3 | 389.40 | 389.40 | 0.00 | 168.00 |
ROOM_1_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT9_FLR_6 | 24.53 | 24.53 | 0.00 | 168.00 |
BANQUET_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
DINING_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
KITCHEN_FLR_6 | 103.30 | 103.30 | 0.00 | 168.00 |
CORRIDOR_FLR_6 | 412.12 | 412.12 | 0.00 | 168.00 |
Totals | 11345.29 | 11345.29 | 0.00 |
Data | |
Number of hours heating loads not met | 24.50 |
Number of hours cooling loads not met | 5.67 |
Number of hours not met | 30.17 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 1634.94 | 203209.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 474.04 | 167714.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 1174.11 | 93091.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 261.73 | 16690.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 959.56 | 59492.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 762.04 | 29240.64 | 1198.64 | 74976.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 16.27 | 515.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 13.43 | 425.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Laundry | 0.00 | 0.00 | 590.20 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 32.92 | 1912.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 616.11 | 37691.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 30.65 | 972.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 1809.73 | 76877.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 132.81 | 8954.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- General | 451.61 | 17755.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 90.78 | 4739.90 | 3330.89 | 289920.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 18.27 | 2271.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 22.38 | 1901.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 33.73 | 1197.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 1825.68 | 6900.18 |
Natural Gas | 1788.84 | 6754.67 |
Additional | 0.00 | 0.00 |
Total | 3614.52 | 13654.84 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 103.49 |
Space Heating | 0.00 |
Space Cooling | 41.78 |
Fans (All) | 159.51 |
Service Water Heating | 8.00 |
Receptacle Equipment | 154.36 |
Miscellaneous (All) | 608.20 |
Subtotal | 608.20 |
Natural Gas [MJ/m2] | |
Space Heating | 144.11 |
Service Water Heating | 293.59 |
Miscellaneous (All) | 595.37 |
Subtotal | 595.37 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 8.60 |
Space Heating | 11.97 |
Space Cooling | 3.47 |
Fans (All) | 13.25 |
Service Water Heating | 25.06 |
Receptacle Equipment | 25.93 |
Miscellaneous | 11.72 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_KITCHEN | 3061. | 8760. |
LTG_SCH_DINING | 3061. | 8760. |
LTG_SCH_BASEMENT | 2655. | 8760. |
LTG_SCH_LOBBY | 3061. | 8760. |
LTG_SCH_STORAGE | 1339. | 8760. |
LTG_SCH_MECHANIC | 3061. | 8760. |
LTG_SCH_LAUNDRY | 2678. | 8760. |
LTG_SCH_GUESTROOM | 3599. | 8760. |
LTG_SCH_CORRIDOR | 3061. | 8760. |
LTG_SCH_RETAIL | 2678. | 8760. |
WALKIN_OCC_LGHT_SCH_1 | 3061. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
BASEMENT_EQUIP_SCH | 3924. | 8760. |
BLDG_EQUIP_SCH | 3924. | 8760. |
GUESTROOM_EQP_SCH_BASE | 3239. | 8760. |
GUESTROOM_EQP_SCH_ADVA | 2762. | 8760. |
LOBBY_EQP_SCH | 3292. | 8760. |
OFFICE_EQP_SCH | 4941. | 8760. |
EMPLOYEELOUNGE_EQP_SCH | 4044. | 8760. |
LAUNDRYROOM_EQP_ELEC_SCH | 2920. | 2920. |
LAUNDRYROOM_EQP_GAS_SCH | 2920. | 2920. |
MEETINGROOM_EQP_SCH | 1336. | 4745. |
EXERCISEROOM_EQP_SCH | 3832. | 5840. |
KITCHEN_ELEC_EQUIP_SCH | 2172. | 8760. |
KITCHEN_GAS_EQUIP_SCH | 1332. | 8760. |
KITCHEN_EXHAUST_SCH | 6205. | 6205. |
BLDG_ELEVATORS | 2270. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_OCC_SCH | 5026. | 8760. |
GUESTROOM_OCC_SCH | 5515. | 8760. |
LOBBY_OCC_SCH | 2304. | 8760. |
OFFICE_OCC_SCH | 3954. | 8760. |
EMPLOYEELOUNGE_OCC_SCH | 948. | 5475. |
MEETINGROOM_OCC_SCH | 1168. | 4745. |
LAUNDRYROOM_OCC_SCH | 427. | 2920. |
EXERCISEROOM_OCC_SCH | 5292. | 5840. |
INFIL_SCH | 8760. | 8760. |
INFIL_HALF_ON_SCH | 4380. | 8760. |
INFIL_QUARTER_ON_SCH | 2190. | 8760. |
LAUNDRY_SWH_SCH | 2555. | 2555. |
BLDG_SWH_SCH | 3301. | 8760. |
GUESTROOM_SWH_SCH | 2899. | 8760. |
LAUNDRYROOM_SWH_SCH | 2920. | 2920. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
ALWAYS_ON | 8760. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
OCC_GUESTROOM_VENT_CTRL_30MIN | 6570. | 6570. |
OCC_GUESTROOM_VENT_CTRL_20MIN | 6327. | 6327. |
VAC_GUESTROOM_VENTILATION_SCHEDULE | 365. | 365. |
MINOA_MOTORIZEDDAMPER_SCHED | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
ROOM_1_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
FLR_3_DOAS_OAMINOAFRACSCHEDULE | 8760. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 0. | 0. |
LAUNDRY_FLR_1 EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 0. | 0. |
SLIDING_DOORS_VENTILATION_AVAILABILITY_SCH | 3285. | 3285. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
VACGUESTROOM_HTGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 18.89 | 365 | 18.89 | 365 |
VACGUESTROOM_CLGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 23.33 | 365 |
OBCRESET_S_OCCGUESTROOM_HTGSP_SCH_30MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_S_OCCGUESTROOM_CLGSP_SCH_30MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_HTGSP_SCH_30MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_CLGSP_SCH_30MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
HTGSETP_SCH | BASEMENT DUAL SP CONTROL | January | 21.00 | 365 | 21.00 | 365 |
CLGSETP_SCH | BASEMENT DUAL SP CONTROL | July | 24.00 | 365 | 24.00 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:58:31
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Average | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Sum | 192720.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 529331.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 50179.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 59156.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8977.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 5588.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 37203.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 710417.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 2115429.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 100358.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 108269.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 105946.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 2115429.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Average | 288887.05 | 0.00 | 0.00 | 0.00 | 0.00 |
Sum | 6355515.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Average | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Sum | 192720.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 529331.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 50179.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 59156.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 8977.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 5588.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 37203.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 710417.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 2115429.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 100358.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT9_FLR_6 | 4154.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 1245715.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 108269.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 105946.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 2115429.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Average | 288887.05 | 0.00 | 0.00 | 0.00 | 0.00 |
Sum | 6355515.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:58:31
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:58:31
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2012
For: Environment
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
For: Environment
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5C
For: Environment
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_PORTANGELES
For: Environment
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.370717E+11 | 18958.62 | 20-JAN-21:00 | 1.00 | 0.17 | 0.614828E+10 | 3784.89 | 11-JAN-22:10 | 1.00 | 0.17 |
February | 0.324113E+11 | 18799.56 | 22-FEB-21:00 | 5.00 | 4.08 | 0.554936E+10 | 3755.61 | 01-FEB-22:10 | 5.00 | 4.08 |
March | 0.345787E+11 | 18741.74 | 31-MAR-20:00 | 6.00 | 2.98 | 0.615671E+10 | 3732.66 | 01-MAR-22:10 | 6.00 | 2.98 |
April | 0.337551E+11 | 19630.53 | 27-APR-19:10 | 16.17 | 10.74 | 0.593371E+10 | 3715.47 | 07-APR-21:10 | 16.17 | 10.74 |
May | 0.348489E+11 | 20231.62 | 30-MAY-18:06 | 12.00 | 9.79 | 0.613380E+10 | 3716.80 | 04-MAY-21:10 | 12.00 | 9.79 |
June | 0.347514E+11 | 20588.93 | 21-JUN-19:10 | 18.50 | 14.60 | 0.594948E+10 | 3747.03 | 20-JUN-22:10 | 18.50 | 14.60 |
July | 0.374478E+11 | 20690.53 | 10-JUL-19:10 | 18.67 | 13.72 | 0.613035E+10 | 3794.34 | 07-JUL-22:10 | 18.67 | 13.72 |
August | 0.382292E+11 | 20663.04 | 17-AUG-18:40 | 19.00 | 15.36 | 0.616510E+10 | 3774.54 | 02-AUG-22:10 | 19.00 | 15.36 |
September | 0.385146E+11 | 21180.16 | 13-SEP-18:02 | 17.50 | 14.11 | 0.596858E+10 | 3806.89 | 27-SEP-21:10 | 13.67 | 9.68 |
October | 0.403016E+11 | 19811.37 | 04-OCT-18:10 | 9.67 | 7.79 | 0.617943E+10 | 3812.50 | 27-OCT-21:10 | 8.00 | 8.00 |
November | 0.392155E+11 | 19407.70 | 10-NOV-21:00 | 4.00 | 4.00 | 0.598561E+10 | 3832.66 | 29-NOV-22:10 | 3.00 | 2.55 |
December | 0.391650E+11 | 19119.52 | 20-DEC-21:00 | 7.00 | 6.47 | 0.617080E+10 | 3817.25 | 01-DEC-22:10 | 7.00 | 6.47 |
Annual Sum or Average | 0.440291E+12 | 0.724712E+11 | ||||||||
Minimum of Months | 0.324113E+11 | 18741.74 | 1.00 | 0.17 | 0.554936E+10 | 3715.47 | 1.00 | 0.17 | ||
Maximum of Months | 0.403016E+11 | 21180.16 | 19.00 | 15.36 | 0.617943E+10 | 3832.66 | 19.00 | 15.36 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.116551E+10 | 3751.23 | 15-JAN-11:40 | 8.67 | 6.43 | 0.615798E+09 | 364.33 | 24-JAN-05:30 | 6.00 | 5.49 |
February | 0.138796E+10 | 3947.29 | 04-FEB-11:40 | 7.67 | 5.05 | 0.558538E+09 | 364.32 | 23-FEB-03:39 | 4.00 | 3.53 |
March | 0.113833E+10 | 2811.21 | 25-MAR-11:30 | 11.75 | 8.68 | 0.621509E+09 | 364.32 | 23-MAR-02:09 | 11.75 | 8.68 |
April | 0.343861E+10 | 4043.60 | 30-APR-12:00 | 22.00 | 14.01 | 0.601675E+09 | 364.30 | 24-APR-04:30 | 22.00 | 14.01 |
May | 0.334927E+10 | 3691.53 | 23-MAY-12:00 | 20.00 | 15.13 | 0.621040E+09 | 364.31 | 19-MAY-03:30 | 20.00 | 15.13 |
June | 0.387009E+10 | 3719.81 | 13-JUN-12:00 | 23.00 | 16.68 | 0.602021E+09 | 364.27 | 08-JUN-02:00 | 23.00 | 16.68 |
July | 0.451457E+10 | 3959.08 | 22-JUL-12:00 | 27.00 | 17.16 | 0.619986E+09 | 364.28 | 27-JUL-02:30 | 10.00 | 9.45 |
August | 0.491230E+10 | 4040.09 | 28-AUG-15:15 | 24.00 | 15.59 | 0.623737E+09 | 364.30 | 30-AUG-02:39 | 9.67 | 9.50 |
September | 0.458466E+10 | 4499.17 | 12-SEP-10:35 | 17.67 | 14.44 | 0.603749E+09 | 364.34 | 29-SEP-03:09 | 10.83 | 9.24 |
October | 0.251848E+10 | 4323.16 | 04-OCT-10:35 | 13.07 | 9.87 | 0.620834E+09 | 364.36 | 26-OCT-04:49 | 7.00 | 6.56 |
November | 0.126479E+10 | 3583.44 | 11-NOV-11:40 | 9.00 | 6.87 | 0.598241E+09 | 364.38 | 25-NOV-03:30 | 8.00 | 6.73 |
December | 0.594271E+09 | 3280.02 | 18-DEC-13:30 | 8.00 | 5.46 | 0.611879E+09 | 364.31 | 11-DEC-22:10 | 8.00 | 5.46 |
Annual Sum or Average | 0.327388E+11 | 0.729901E+10 | ||||||||
Minimum of Months | 0.594271E+09 | 2811.21 | 7.67 | 5.05 | 0.558538E+09 | 364.27 | 4.00 | 3.53 | ||
Maximum of Months | 0.491230E+10 | 4499.17 | 27.00 | 17.16 | 0.623737E+09 | 364.38 | 23.00 | 16.68 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.253394E+10 | 1715.87 | 23-JAN-21:00 | 9.00 | 7.43 | 0.717723E+09 | 429.87 | 17-JAN-22:19 | 9.00 | 7.43 |
February | 0.237641E+10 | 1725.63 | 27-FEB-21:00 | 6.00 | 6.00 | 0.649086E+09 | 432.25 | 27-FEB-22:19 | 4.67 | 4.67 |
March | 0.267900E+10 | 1749.82 | 20-MAR-20:00 | 7.00 | 4.68 | 0.721626E+09 | 433.87 | 20-MAR-21:19 | 4.80 | 3.90 |
April | 0.319118E+10 | 2001.47 | 27-APR-18:02 | 17.83 | 10.48 | 0.700126E+09 | 456.07 | 28-APR-21:40 | 11.33 | 8.56 |
May | 0.333800E+10 | 2089.25 | 22-MAY-18:03 | 19.00 | 14.26 | 0.724419E+09 | 458.00 | 23-MAY-21:30 | 12.00 | 9.78 |
June | 0.350079E+10 | 2147.71 | 12-JUN-18:02 | 25.67 | 17.63 | 0.705160E+09 | 463.30 | 21-JUN-22:10 | 12.83 | 11.81 |
July | 0.373327E+10 | 2163.16 | 22-JUL-18:07 | 29.83 | 16.84 | 0.727211E+09 | 465.05 | 25-JUL-22:10 | 13.00 | 12.44 |
August | 0.377833E+10 | 2128.96 | 14-AUG-18:10 | 26.48 | 13.67 | 0.730259E+09 | 459.71 | 14-AUG-21:40 | 16.73 | 11.70 |
September | 0.349415E+10 | 2055.88 | 11-SEP-18:10 | 21.50 | 15.69 | 0.702391E+09 | 460.88 | 11-SEP-22:10 | 12.83 | 11.23 |
October | 0.300950E+10 | 1830.92 | 03-OCT-20:00 | 7.00 | 6.01 | 0.720059E+09 | 444.58 | 03-OCT-21:40 | 8.00 | 6.49 |
November | 0.256617E+10 | 1728.11 | 15-NOV-21:00 | 7.00 | 6.47 | 0.694536E+09 | 431.28 | 15-NOV-22:19 | 5.33 | 4.84 |
December | 0.233166E+10 | 1630.24 | 21-DEC-22:00 | 3.00 | 3.00 | 0.717413E+09 | 424.98 | 21-DEC-22:19 | 3.00 | 3.00 |
Annual Sum or Average | 0.365324E+11 | 0.851001E+10 | ||||||||
Minimum of Months | 0.233166E+10 | 1630.24 | 3.00 | 3.00 | 0.649086E+09 | 424.98 | 3.00 | 3.00 | ||
Maximum of Months | 0.377833E+10 | 2163.16 | 29.83 | 17.63 | 0.730259E+09 | 465.05 | 16.73 | 12.44 |
Report: ZoneCoolingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.113131E+10 | 1393.05 | 18-JAN-21:00 | 8.00 | 6.97 | 0.151697E+09 | 89.15 | 05-JAN-03:09 | 8.00 | 6.97 |
February | 0.107603E+10 | 1344.42 | 22-FEB-21:00 | 5.00 | 4.08 | 0.137151E+09 | 89.15 | 08-FEB-02:39 | 5.00 | 4.08 |
March | 0.149274E+10 | 1483.23 | 20-MAR-20:00 | 7.00 | 4.68 | 0.152411E+09 | 89.15 | 20-MAR-01:39 | 7.00 | 4.68 |
April | 0.206327E+10 | 1787.28 | 30-APR-19:10 | 22.83 | 13.25 | 0.147123E+09 | 91.37 | 28-APR-21:10 | 22.83 | 13.25 |
May | 0.228623E+10 | 1849.85 | 22-MAY-19:00 | 19.00 | 14.26 | 0.152158E+09 | 92.73 | 23-MAY-21:10 | 12.00 | 9.78 |
June | 0.271594E+10 | 1921.57 | 12-JUN-18:40 | 24.67 | 17.00 | 0.147874E+09 | 93.96 | 13-JUN-21:10 | 14.00 | 12.84 |
July | 0.298987E+10 | 1995.46 | 22-JUL-18:20 | 29.67 | 16.87 | 0.152378E+09 | 93.74 | 21-JUL-21:10 | 29.67 | 16.87 |
August | 0.298274E+10 | 1913.65 | 14-AUG-18:30 | 25.45 | 13.46 | 0.152986E+09 | 92.86 | 14-AUG-21:10 | 17.83 | 11.86 |
September | 0.254357E+10 | 1799.39 | 11-SEP-18:50 | 19.50 | 14.98 | 0.147271E+09 | 92.06 | 12-SEP-21:10 | 15.17 | 13.86 |
October | 0.189396E+10 | 1625.67 | 10-OCT-20:00 | 10.00 | 9.41 | 0.151770E+09 | 89.43 | 10-OCT-21:10 | 8.83 | 8.83 |
November | 0.137702E+10 | 1480.96 | 08-NOV-21:00 | 11.00 | 11.00 | 0.146742E+09 | 89.15 | 25-NOV-05:00 | 7.00 | 5.14 |
December | 0.976669E+09 | 1267.13 | 05-DEC-21:00 | 7.00 | 6.46 | 0.151698E+09 | 89.15 | 26-DEC-04:00 | 2.00 | 0.31 |
Annual Sum or Average | 0.235294E+11 | 0.179126E+10 | ||||||||
Minimum of Months | 0.976669E+09 | 1267.13 | 5.00 | 4.08 | 0.137151E+09 | 89.15 | 2.00 | 0.31 | ||
Maximum of Months | 0.298987E+10 | 1995.46 | 29.67 | 17.00 | 0.152986E+09 | 93.96 | 29.67 | 16.87 |
Report: ZoneCoolingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.155788E+09 | 366.86 | 18-JAN-22:00 | 8.00 | 7.45 | 0.116691E+09 | 68.57 | 30-JAN-04:10 | 3.75 | 3.18 |
February | 0.137682E+09 | 331.91 | 07-FEB-22:00 | 7.00 | 7.00 | 0.105502E+09 | 68.58 | 15-FEB-05:40 | 5.33 | 2.47 |
March | 0.289149E+09 | 398.04 | 20-MAR-20:10 | 6.67 | 4.60 | 0.117240E+09 | 68.57 | 07-MAR-01:19 | 6.67 | 4.60 |
April | 0.661618E+09 | 712.24 | 30-APR-19:05 | 22.83 | 13.25 | 0.113126E+09 | 68.57 | 27-APR-03:09 | 22.83 | 13.25 |
May | 0.780142E+09 | 731.11 | 22-MAY-19:40 | 17.67 | 13.35 | 0.116938E+09 | 68.57 | 01-MAY-04:10 | 17.67 | 13.35 |
June | 0.106908E+10 | 860.91 | 13-JUN-19:05 | 20.08 | 15.24 | 0.113381E+09 | 69.41 | 13-JUN-22:10 | 13.83 | 12.78 |
July | 0.122558E+10 | 902.38 | 22-JUL-18:25 | 29.50 | 16.91 | 0.116706E+09 | 69.42 | 21-JUL-22:10 | 29.50 | 16.91 |
August | 0.121774E+10 | 787.07 | 14-AUG-20:40 | 19.03 | 12.06 | 0.117186E+09 | 68.89 | 14-AUG-21:40 | 16.73 | 11.70 |
September | 0.960913E+09 | 712.15 | 12-SEP-21:00 | 15.00 | 13.80 | 0.113071E+09 | 68.57 | 11-SEP-02:00 | 15.00 | 13.80 |
October | 0.530471E+09 | 483.63 | 10-OCT-20:50 | 9.17 | 9.07 | 0.116746E+09 | 68.57 | 27-OCT-00:00 | 9.00 | 8.43 |
November | 0.256938E+09 | 430.97 | 08-NOV-22:00 | 11.00 | 11.00 | 0.112879E+09 | 68.58 | 25-NOV-05:10 | 7.83 | 5.92 |
December | 82365383.03 | 275.45 | 05-DEC-21:00 | 7.00 | 6.46 | 0.116691E+09 | 68.58 | 15-DEC-04:00 | 3.00 | 1.30 |
Annual Sum or Average | 0.736746E+10 | 0.137616E+10 | ||||||||
Minimum of Months | 82365383.03 | 275.45 | 6.67 | 4.60 | 0.105502E+09 | 68.57 | 3.00 | 1.30 | ||
Maximum of Months | 0.122558E+10 | 902.38 | 29.50 | 16.91 | 0.117240E+09 | 69.42 | 29.50 | 16.91 |
Report: ZoneCoolingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.490074E+11 | 35664.57 | 23-JAN-21:00 | 9.00 | 7.43 | 0.511097E+09 | 381.90 | 24-JAN-22:10 | 4.03 | 4.03 |
February | 0.443796E+11 | 35682.37 | 07-FEB-21:00 | 8.00 | 7.45 | 0.462069E+09 | 381.89 | 21-FEB-22:10 | 4.17 | 4.17 |
March | 0.496389E+11 | 35794.37 | 31-MAR-20:00 | 6.00 | 2.98 | 0.513872E+09 | 381.90 | 17-MAR-21:10 | 6.00 | 2.98 |
April | 0.492262E+11 | 36617.29 | 28-APR-20:00 | 13.00 | 9.28 | 0.493774E+09 | 383.29 | 28-APR-21:10 | 11.83 | 8.82 |
May | 0.510488E+11 | 36735.67 | 22-MAY-20:00 | 17.00 | 12.89 | 0.510710E+09 | 386.42 | 23-MAY-21:10 | 12.00 | 9.78 |
June | 0.501419E+11 | 36973.20 | 12-JUN-20:00 | 22.00 | 16.43 | 0.494769E+09 | 383.86 | 23-JUN-21:10 | 12.83 | 10.83 |
July | 0.519335E+11 | 36964.54 | 21-JUL-20:00 | 21.00 | 15.02 | 0.507850E+09 | 390.08 | 26-JUL-21:10 | 12.67 | 11.32 |
August | 0.522112E+11 | 36889.43 | 14-AUG-20:00 | 20.70 | 12.26 | 0.511633E+09 | 385.73 | 23-AUG-21:10 | 11.83 | 9.23 |
September | 0.498672E+11 | 36676.41 | 12-SEP-20:00 | 15.00 | 13.80 | 0.493809E+09 | 387.17 | 27-SEP-21:10 | 13.67 | 9.68 |
October | 0.501730E+11 | 36168.53 | 06-OCT-20:00 | 8.00 | 6.07 | 0.510752E+09 | 381.91 | 17-OCT-21:10 | 11.00 | 11.00 |
November | 0.478377E+11 | 35766.00 | 08-NOV-21:00 | 11.00 | 11.00 | 0.494553E+09 | 381.89 | 17-NOV-22:10 | 6.00 | 5.12 |
December | 0.486516E+11 | 35522.20 | 20-DEC-21:00 | 7.00 | 6.47 | 0.510811E+09 | 381.89 | 22-DEC-22:10 | 3.83 | 3.37 |
Annual Sum or Average | 0.594117E+12 | 0.601570E+10 | ||||||||
Minimum of Months | 0.443796E+11 | 35522.20 | 6.00 | 2.98 | 0.462069E+09 | 381.89 | 3.83 | 2.98 | ||
Maximum of Months | 0.522112E+11 | 36973.20 | 22.00 | 16.43 | 0.513872E+09 | 390.08 | 13.67 | 11.32 |
Report: ZoneCoolingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.166846E+11 | 14641.12 | 07-JAN-11:35 | 6.67 | 4.01 | 0.814339E+10 | 4790.50 | 30-JAN-05:40 | 2.73 | 2.42 |
February | 0.162514E+11 | 15281.79 | 04-FEB-11:40 | 7.67 | 5.05 | 0.736598E+10 | 4790.24 | 27-FEB-04:30 | 6.00 | 6.00 |
March | 0.168251E+11 | 11590.81 | 25-MAR-11:30 | 11.75 | 8.68 | 0.818145E+10 | 4789.75 | 24-MAR-04:49 | 11.75 | 8.68 |
April | 0.229487E+11 | 15241.32 | 28-APR-15:13 | 20.07 | 13.24 | 0.790247E+10 | 4831.94 | 28-APR-21:19 | 11.67 | 8.73 |
May | 0.229502E+11 | 14076.33 | 22-MAY-15:03 | 23.83 | 15.94 | 0.816073E+10 | 4839.04 | 22-MAY-21:30 | 14.50 | 12.46 |
June | 0.237372E+11 | 13984.59 | 13-JUN-15:02 | 26.08 | 17.81 | 0.791211E+10 | 4919.80 | 21-JUN-22:10 | 12.83 | 11.81 |
July | 0.258840E+11 | 14800.29 | 21-JUL-15:13 | 27.33 | 15.92 | 0.814565E+10 | 4939.10 | 24-JUL-22:10 | 13.00 | 13.00 |
August | 0.272186E+11 | 15556.68 | 28-AUG-15:15 | 24.00 | 15.59 | 0.818765E+10 | 4920.92 | 14-AUG-21:30 | 24.00 | 15.59 |
September | 0.261069E+11 | 16211.77 | 23-SEP-10:35 | 18.00 | 14.39 | 0.792096E+10 | 4998.21 | 11-SEP-22:10 | 18.00 | 14.39 |
October | 0.207922E+11 | 15990.71 | 07-OCT-10:35 | 14.67 | 10.10 | 0.815595E+10 | 4789.91 | 28-OCT-03:00 | 8.00 | 7.44 |
November | 0.166773E+11 | 13807.20 | 11-NOV-11:40 | 9.00 | 6.87 | 0.787751E+10 | 4789.95 | 03-NOV-04:49 | 9.00 | 6.87 |
December | 0.145725E+11 | 12611.35 | 18-DEC-13:30 | 8.00 | 5.46 | 0.813932E+10 | 4790.05 | 15-DEC-02:00 | 8.00 | 5.46 |
Annual Sum or Average | 0.250649E+12 | 0.960932E+11 | ||||||||
Minimum of Months | 0.145725E+11 | 11590.81 | 6.67 | 4.01 | 0.736598E+10 | 4789.75 | 2.73 | 2.42 | ||
Maximum of Months | 0.272186E+11 | 16211.77 | 27.33 | 17.81 | 0.818765E+10 | 4998.21 | 24.00 | 15.59 |
Report: ZoneCoolingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.644019E+11 | 36892.47 | 23-JAN-22:00 | 8.00 | 7.45 | 0.242101E+11 | 14809.97 | 23-JAN-22:40 | 8.00 | 7.45 |
February | 0.600211E+11 | 37124.24 | 27-FEB-21:00 | 6.00 | 6.00 | 0.218978E+11 | 14797.29 | 27-FEB-22:40 | 4.33 | 4.33 |
March | 0.661395E+11 | 37567.84 | 20-MAR-20:00 | 7.00 | 4.68 | 0.243509E+11 | 14858.19 | 20-MAR-21:40 | 4.60 | 3.70 |
April | 0.754888E+11 | 41752.33 | 27-APR-18:30 | 17.50 | 10.71 | 0.236258E+11 | 15451.20 | 28-APR-21:40 | 11.33 | 8.56 |
May | 0.776180E+11 | 43368.59 | 22-MAY-18:40 | 19.00 | 14.26 | 0.244511E+11 | 15473.90 | 23-MAY-21:40 | 12.00 | 9.78 |
June | 0.791822E+11 | 44639.07 | 12-JUN-18:40 | 24.67 | 17.00 | 0.238380E+11 | 15718.20 | 21-JUN-22:10 | 12.83 | 11.81 |
July | 0.841051E+11 | 44154.37 | 10-JUL-18:30 | 20.00 | 13.91 | 0.246078E+11 | 15814.29 | 25-JUL-22:10 | 13.00 | 12.44 |
August | 0.859031E+11 | 44790.30 | 14-AUG-18:20 | 25.97 | 13.57 | 0.247509E+11 | 15633.87 | 18-AUG-22:10 | 12.83 | 11.81 |
September | 0.815527E+11 | 43478.52 | 11-SEP-18:02 | 21.50 | 15.69 | 0.237874E+11 | 15745.01 | 11-SEP-22:10 | 12.83 | 11.23 |
October | 0.730035E+11 | 39148.77 | 03-OCT-20:00 | 7.00 | 6.01 | 0.243166E+11 | 15194.31 | 03-OCT-21:40 | 8.00 | 6.49 |
November | 0.641509E+11 | 37318.51 | 15-NOV-21:00 | 7.00 | 6.47 | 0.234391E+11 | 14832.07 | 08-NOV-22:40 | 7.00 | 6.47 |
December | 0.607158E+11 | 35953.02 | 21-DEC-22:00 | 3.00 | 3.00 | 0.241925E+11 | 14628.58 | 21-DEC-22:40 | 3.00 | 3.00 |
Annual Sum or Average | 0.872283E+12 | 0.287468E+12 | ||||||||
Minimum of Months | 0.600211E+11 | 35953.02 | 3.00 | 3.00 | 0.218978E+11 | 14628.58 | 3.00 | 3.00 | ||
Maximum of Months | 0.859031E+11 | 44790.30 | 25.97 | 17.00 | 0.247509E+11 | 15814.29 | 13.00 | 12.44 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 84852359.78 | 2738.75 | 25-JAN-16:01 | 9.00 | 8.43 | 94229815.73 | 56.69 | 29-JAN-00:20 | 7.20 | 6.95 |
February | 0.139778E+09 | 3588.17 | 18-FEB-16:01 | 5.83 | 4.00 | 85755426.63 | 56.69 | 27-FEB-22:19 | 4.67 | 4.67 |
March | 0.125412E+09 | 3467.60 | 31-MAR-15:01 | 7.33 | 4.46 | 94850976.00 | 56.69 | 20-MAR-21:19 | 7.33 | 4.46 |
April | 0.889192E+09 | 3652.25 | 13-APR-15:02 | 12.00 | 7.14 | 94577113.71 | 56.69 | 20-APR-21:00 | 11.00 | 7.91 |
May | 0.102551E+10 | 3713.54 | 21-MAY-15:01 | 18.83 | 10.43 | 97757154.94 | 56.69 | 22-MAY-22:00 | 14.00 | 12.24 |
June | 0.140895E+10 | 3547.78 | 08-JUN-18:02 | 15.83 | 9.50 | 95252642.31 | 56.69 | 13-JUN-21:10 | 14.00 | 12.84 |
July | 0.168836E+10 | 3527.11 | 26-JUL-15:02 | 19.68 | 15.17 | 98443394.03 | 56.69 | 18-JUL-21:30 | 19.68 | 15.17 |
August | 0.161413E+10 | 3486.67 | 27-AUG-18:02 | 16.33 | 13.76 | 98602656.63 | 56.69 | 16-AUG-21:00 | 16.33 | 13.76 |
September | 0.123892E+10 | 3635.31 | 29-SEP-15:01 | 15.67 | 9.39 | 95043107.50 | 56.69 | 12-SEP-22:00 | 15.67 | 9.39 |
October | 0.390735E+09 | 3661.29 | 07-OCT-15:02 | 18.83 | 10.03 | 96067552.05 | 56.69 | 07-OCT-23:10 | 10.83 | 9.32 |
November | 93169345.47 | 3559.11 | 03-NOV-15:01 | 8.83 | 5.57 | 91504513.02 | 56.69 | 30-NOV-00:20 | 3.33 | 3.18 |
December | 51283132.42 | 487.11 | 20-DEC-19:05 | 7.67 | 7.21 | 93194711.01 | 56.69 | 16-DEC-00:20 | 7.67 | 7.21 |
Annual Sum or Average | 0.875029E+10 | 0.113528E+10 | ||||||||
Minimum of Months | 51283132.42 | 487.11 | 5.83 | 4.00 | 85755426.63 | 56.69 | 3.33 | 3.18 | ||
Maximum of Months | 0.168836E+10 | 3713.54 | 19.68 | 15.17 | 98602656.63 | 56.69 | 19.68 | 15.17 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 55506213.90 | 2001.23 | 19-JAN-16:01 | 7.67 | 7.22 | 93299898.07 | 56.69 | 11-JAN-00:10 | 7.67 | 7.22 |
February | 80532454.94 | 2991.45 | 19-FEB-16:02 | 5.17 | 4.17 | 84745538.11 | 56.69 | 10-FEB-00:10 | 5.17 | 4.17 |
March | 97105853.57 | 3004.22 | 20-MAR-18:02 | 7.83 | 5.10 | 94379014.34 | 56.69 | 20-MAR-21:19 | 4.80 | 3.90 |
April | 0.612791E+09 | 3258.57 | 26-APR-15:02 | 14.83 | 9.50 | 93820850.30 | 56.69 | 27-APR-21:10 | 8.83 | 7.27 |
May | 0.839531E+09 | 3342.63 | 21-MAY-15:01 | 18.83 | 10.43 | 97303846.76 | 56.69 | 22-MAY-22:00 | 14.00 | 12.24 |
June | 0.126885E+10 | 3221.88 | 08-JUN-18:02 | 15.83 | 9.50 | 95032198.85 | 56.70 | 26-JUN-21:10 | 14.00 | 14.00 |
July | 0.148768E+10 | 3253.47 | 24-JUL-15:02 | 19.17 | 15.95 | 98216009.94 | 56.70 | 21-JUL-21:10 | 19.17 | 15.95 |
August | 0.127042E+10 | 3236.95 | 19-AUG-15:02 | 20.00 | 15.22 | 98209536.68 | 56.69 | 15-AUG-21:00 | 20.00 | 15.22 |
September | 0.798778E+09 | 3257.18 | 11-SEP-15:02 | 22.00 | 15.85 | 94264340.95 | 56.69 | 12-SEP-22:10 | 15.83 | 13.97 |
October | 0.207611E+09 | 3255.35 | 07-OCT-15:02 | 18.83 | 10.03 | 95128808.07 | 56.69 | 07-OCT-23:10 | 10.83 | 9.32 |
November | 64205485.18 | 1910.06 | 10-NOV-16:02 | 10.33 | 8.12 | 90686411.73 | 56.69 | 01-NOV-23:19 | 10.33 | 8.12 |
December | 38329141.05 | 286.37 | 02-DEC-09:05 | 7.00 | 6.47 | 92647291.81 | 56.69 | 04-DEC-22:19 | 7.00 | 7.00 |
Annual Sum or Average | 0.682134E+10 | 0.112773E+10 | ||||||||
Minimum of Months | 38329141.05 | 286.37 | 5.17 | 4.17 | 84745538.11 | 56.69 | 4.80 | 3.90 | ||
Maximum of Months | 0.148768E+10 | 3342.63 | 22.00 | 15.95 | 98216009.94 | 56.70 | 20.00 | 15.95 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.282151E+09 | 580.61 | 21-JAN-11:25 | 6.00 | 5.05 | 0.00 | 0.00 | 01-JAN-00:10 | 6.00 | 5.05 |
February | 0.273037E+09 | 527.06 | 04-FEB-14:00 | 9.00 | 6.13 | 0.00 | 0.00 | 01-FEB-00:10 | 9.00 | 6.13 |
March | 0.227439E+09 | 252.23 | 25-MAR-11:40 | 11.83 | 8.75 | 0.00 | 0.00 | 01-MAR-00:10 | 11.83 | 8.75 |
April | 0.589924E+09 | 733.86 | 30-APR-12:50 | 22.00 | 13.22 | 0.00 | 0.00 | 01-APR-00:10 | 22.00 | 13.22 |
May | 0.526615E+09 | 586.72 | 22-MAY-13:20 | 22.33 | 15.12 | 0.00 | 0.00 | 01-MAY-00:10 | 22.33 | 15.12 |
June | 0.580889E+09 | 594.29 | 13-JUN-13:20 | 24.37 | 17.19 | 0.00 | 0.00 | 01-JUN-00:10 | 24.37 | 17.19 |
July | 0.672380E+09 | 679.47 | 22-JUL-13:30 | 28.00 | 16.51 | 0.00 | 0.00 | 01-JUL-00:10 | 28.00 | 16.51 |
August | 0.752910E+09 | 721.13 | 20-AUG-13:00 | 23.00 | 14.82 | 0.00 | 0.00 | 01-AUG-00:10 | 23.00 | 14.82 |
September | 0.802729E+09 | 854.01 | 27-SEP-13:20 | 21.33 | 13.25 | 0.00 | 0.00 | 01-SEP-00:10 | 21.33 | 13.25 |
October | 0.476826E+09 | 798.64 | 07-OCT-13:10 | 17.00 | 9.32 | 0.00 | 0.00 | 01-OCT-00:10 | 17.00 | 9.32 |
November | 0.272065E+09 | 559.27 | 11-NOV-13:30 | 9.00 | 7.22 | 0.00 | 0.00 | 01-NOV-00:10 | 9.00 | 7.22 |
December | 0.164394E+09 | 249.69 | 26-DEC-14:30 | 6.00 | 2.98 | 0.00 | 0.00 | 01-DEC-00:10 | 6.00 | 2.98 |
Annual Sum or Average | 0.562136E+10 | 0.00 | ||||||||
Minimum of Months | 0.164394E+09 | 249.69 | 6.00 | 2.98 | 0.00 | 0.00 | 6.00 | 2.98 | ||
Maximum of Months | 0.802729E+09 | 854.01 | 28.00 | 17.19 | 0.00 | 0.00 | 28.00 | 17.19 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.180118E+09 | 801.50 | 29-JAN-19:02 | 9.00 | 8.43 | 95109904.30 | 56.69 | 19-JAN-22:19 | 9.00 | 8.43 |
February | 0.169961E+09 | 868.92 | 12-FEB-09:02 | 2.33 | 1.83 | 86089866.69 | 56.69 | 22-FEB-22:10 | 4.17 | 3.62 |
March | 0.298190E+09 | 909.11 | 20-MAR-18:02 | 7.83 | 5.10 | 96016207.96 | 56.69 | 14-MAR-21:10 | 7.83 | 5.10 |
April | 0.469392E+09 | 973.74 | 22-APR-15:02 | 17.67 | 9.75 | 93727501.70 | 56.69 | 14-APR-21:10 | 17.67 | 9.75 |
May | 0.562973E+09 | 984.28 | 28-MAY-18:01 | 11.83 | 7.52 | 97176156.08 | 56.69 | 22-MAY-22:00 | 11.83 | 7.52 |
June | 0.693290E+09 | 1019.41 | 12-JUN-18:02 | 25.67 | 17.63 | 94584113.05 | 56.69 | 13-JUN-21:40 | 14.00 | 12.84 |
July | 0.748004E+09 | 1008.63 | 10-JUL-15:02 | 22.67 | 16.49 | 97657291.74 | 56.69 | 10-JUL-21:40 | 17.00 | 13.49 |
August | 0.679134E+09 | 980.70 | 14-AUG-15:02 | 25.17 | 16.00 | 97404046.48 | 56.69 | 15-AUG-21:10 | 15.00 | 13.19 |
September | 0.548533E+09 | 972.44 | 11-SEP-18:02 | 21.50 | 15.69 | 93881815.53 | 56.69 | 28-SEP-22:10 | 12.00 | 11.55 |
October | 0.372082E+09 | 920.67 | 07-OCT-15:02 | 18.83 | 10.03 | 96221028.77 | 56.69 | 17-OCT-21:10 | 11.00 | 11.00 |
November | 0.231771E+09 | 887.09 | 26-NOV-09:02 | 5.17 | 2.51 | 92426864.44 | 56.69 | 24-NOV-23:10 | 5.17 | 2.51 |
December | 0.135885E+09 | 735.97 | 02-DEC-09:02 | 7.00 | 6.47 | 94794970.39 | 56.69 | 04-DEC-22:19 | 7.00 | 7.00 |
Annual Sum or Average | 0.508933E+10 | 0.113509E+10 | ||||||||
Minimum of Months | 0.135885E+09 | 735.97 | 2.33 | 1.83 | 86089866.69 | 56.69 | 4.17 | 2.51 | ||
Maximum of Months | 0.748004E+09 | 1019.41 | 25.67 | 17.63 | 97657291.74 | 56.69 | 17.67 | 13.49 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.101048E+09 | 1922.75 | 21-JAN-16:02 | 5.75 | 4.88 | 94192209.60 | 56.69 | 03-JAN-23:49 | 5.75 | 4.88 |
February | 0.122964E+09 | 3066.15 | 04-FEB-16:01 | 7.00 | 5.54 | 85671517.60 | 56.69 | 22-FEB-00:10 | 6.00 | 6.00 |
March | 0.121846E+09 | 2743.32 | 20-MAR-15:01 | 10.83 | 7.32 | 94915691.18 | 56.69 | 20-MAR-21:19 | 4.80 | 3.90 |
April | 0.989263E+09 | 3326.83 | 15-APR-08:62 | 9.33 | 5.61 | 95081505.14 | 56.69 | 20-APR-21:40 | 11.00 | 7.79 |
May | 0.102550E+10 | 3353.59 | 21-MAY-15:01 | 18.83 | 10.43 | 98215974.23 | 56.69 | 22-MAY-22:40 | 14.00 | 12.24 |
June | 0.131743E+10 | 3251.29 | 13-JUN-08:62 | 21.10 | 15.99 | 95461574.65 | 56.69 | 26-JUN-22:00 | 15.00 | 14.41 |
July | 0.159255E+10 | 3270.73 | 23-JUL-08:61 | 19.17 | 15.34 | 98727979.48 | 56.69 | 17-JUL-21:00 | 19.17 | 15.34 |
August | 0.167200E+10 | 3279.39 | 14-AUG-08:62 | 20.17 | 15.19 | 98805440.61 | 56.69 | 16-AUG-21:00 | 16.00 | 14.77 |
September | 0.135976E+10 | 3289.03 | 29-SEP-15:01 | 15.67 | 9.39 | 95407055.04 | 56.69 | 14-SEP-21:00 | 15.67 | 9.39 |
October | 0.412002E+09 | 3310.68 | 07-OCT-15:02 | 18.83 | 10.03 | 96243087.41 | 56.69 | 07-OCT-23:10 | 10.83 | 9.32 |
November | 0.103536E+09 | 3012.74 | 03-NOV-15:01 | 8.83 | 5.57 | 91476795.49 | 56.69 | 30-NOV-00:20 | 3.33 | 3.18 |
December | 62391730.06 | 737.83 | 06-DEC-09:03 | 2.33 | 1.83 | 93276040.03 | 56.69 | 16-DEC-00:20 | 4.00 | 3.69 |
Annual Sum or Average | 0.888029E+10 | 0.113747E+10 | ||||||||
Minimum of Months | 62391730.06 | 737.83 | 2.33 | 1.83 | 85671517.60 | 56.69 | 3.33 | 3.18 | ||
Maximum of Months | 0.167200E+10 | 3353.59 | 21.10 | 15.99 | 98805440.61 | 56.69 | 19.17 | 15.34 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 57277580.07 | 689.84 | 19-JAN-09:03 | 7.17 | 6.56 | 93288258.31 | 56.69 | 14-JAN-00:20 | 7.17 | 6.56 |
February | 71673750.26 | 1830.15 | 20-FEB-09:02 | 3.33 | 2.81 | 84610866.61 | 56.69 | 17-FEB-23:49 | 3.33 | 2.81 |
March | 90713001.60 | 912.17 | 10-MAR-09:02 | 7.17 | 4.01 | 94449778.22 | 56.69 | 15-MAR-23:19 | 2.57 | 1.57 |
April | 0.689306E+09 | 3029.15 | 15-APR-08:62 | 9.33 | 5.61 | 94521053.45 | 56.69 | 27-APR-21:10 | 8.83 | 7.27 |
May | 0.828171E+09 | 3041.75 | 21-MAY-15:01 | 18.83 | 10.43 | 97913353.53 | 56.69 | 22-MAY-22:30 | 14.00 | 12.24 |
June | 0.116849E+10 | 2967.41 | 13-JUN-08:62 | 21.10 | 15.99 | 95336319.08 | 56.69 | 26-JUN-22:00 | 15.00 | 14.41 |
July | 0.137782E+10 | 2986.74 | 23-JUL-08:61 | 19.17 | 15.34 | 98644775.44 | 56.69 | 17-JUL-21:40 | 19.17 | 15.34 |
August | 0.130381E+10 | 3006.14 | 14-AUG-08:62 | 20.17 | 15.19 | 98656837.64 | 56.69 | 16-AUG-21:30 | 16.50 | 14.93 |
September | 0.881116E+09 | 2940.32 | 23-SEP-08:62 | 17.00 | 13.57 | 95022963.70 | 56.69 | 12-SEP-22:10 | 17.00 | 13.57 |
October | 0.218529E+09 | 2842.10 | 07-OCT-15:02 | 18.83 | 10.03 | 95375380.74 | 56.69 | 07-OCT-23:10 | 10.83 | 9.32 |
November | 67051846.44 | 1089.55 | 11-NOV-09:02 | 6.50 | 5.33 | 90655447.98 | 56.69 | 01-NOV-22:49 | 6.50 | 5.33 |
December | 40516547.00 | 505.73 | 11-DEC-09:05 | 3.50 | 2.91 | 92723885.01 | 56.69 | 04-DEC-22:19 | 3.50 | 2.91 |
Annual Sum or Average | 0.679446E+10 | 0.113120E+10 | ||||||||
Minimum of Months | 40516547.00 | 505.73 | 3.33 | 2.81 | 84610866.61 | 56.69 | 2.57 | 1.57 | ||
Maximum of Months | 0.137782E+10 | 3041.75 | 21.10 | 15.99 | 98656837.64 | 56.69 | 19.17 | 15.34 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.172938E+10 | 1577.81 | 23-JAN-22:03 | 8.00 | 7.45 | 0.119882E+10 | 704.49 | 09-JAN-04:40 | 8.00 | 7.45 |
February | 0.186539E+10 | 1873.12 | 04-FEB-14:20 | 9.00 | 6.28 | 0.108386E+10 | 704.48 | 02-FEB-02:20 | 9.00 | 6.28 |
March | 0.218933E+10 | 1761.06 | 20-MAR-18:03 | 7.83 | 5.10 | 0.120445E+10 | 704.47 | 07-MAR-01:49 | 7.83 | 5.10 |
April | 0.425506E+10 | 2984.50 | 30-APR-10:35 | 19.33 | 11.65 | 0.116522E+10 | 730.90 | 28-APR-21:40 | 19.33 | 11.65 |
May | 0.452874E+10 | 2832.46 | 22-MAY-18:10 | 19.00 | 14.26 | 0.120505E+10 | 736.13 | 23-MAY-21:40 | 12.00 | 9.78 |
June | 0.509145E+10 | 2973.33 | 13-JUN-10:35 | 22.00 | 15.85 | 0.117368E+10 | 747.92 | 13-JUN-21:40 | 14.00 | 12.84 |
July | 0.556859E+10 | 3162.57 | 23-JUL-10:35 | 21.00 | 15.99 | 0.121658E+10 | 751.32 | 24-JUL-22:10 | 13.00 | 13.00 |
August | 0.568363E+10 | 3076.09 | 14-AUG-17:08 | 27.00 | 14.28 | 0.122017E+10 | 741.63 | 14-AUG-21:40 | 16.73 | 11.70 |
September | 0.509909E+10 | 2913.29 | 12-SEP-10:35 | 17.67 | 14.44 | 0.117294E+10 | 742.09 | 12-SEP-21:40 | 15.67 | 14.03 |
October | 0.327432E+10 | 2457.14 | 07-OCT-17:12 | 13.67 | 8.88 | 0.119991E+10 | 711.69 | 03-OCT-21:40 | 13.67 | 8.88 |
November | 0.194946E+10 | 1788.08 | 11-NOV-13:00 | 9.00 | 7.43 | 0.115965E+10 | 704.49 | 25-NOV-01:39 | 9.00 | 8.43 |
December | 0.111949E+10 | 1236.39 | 21-DEC-22:03 | 3.00 | 3.00 | 0.119882E+10 | 704.50 | 05-DEC-02:20 | 3.00 | 3.00 |
Annual Sum or Average | 0.423539E+11 | 0.141992E+11 | ||||||||
Minimum of Months | 0.111949E+10 | 1236.39 | 3.00 | 3.00 | 0.108386E+10 | 704.47 | 3.00 | 3.00 | ||
Maximum of Months | 0.568363E+10 | 3162.57 | 27.00 | 15.99 | 0.122017E+10 | 751.32 | 19.33 | 14.03 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 66261860.01 | 2883.16 | 25-JAN-16:01 | 9.00 | 8.43 | 93658254.77 | 56.69 | 03-JAN-22:19 | 9.00 | 8.43 |
February | 0.128113E+09 | 3812.42 | 09-FEB-16:01 | 7.67 | 5.50 | 85254704.03 | 56.69 | 26-FEB-00:20 | 2.00 | 2.00 |
March | 0.108611E+09 | 3676.82 | 10-MAR-16:01 | 7.83 | 4.01 | 94391055.62 | 56.69 | 20-MAR-21:19 | 4.80 | 3.90 |
April | 0.972131E+09 | 3907.50 | 13-APR-15:02 | 12.00 | 7.14 | 94533740.12 | 56.69 | 27-APR-21:10 | 8.83 | 7.27 |
May | 0.110938E+10 | 3970.98 | 21-MAY-15:01 | 18.83 | 10.43 | 97744746.18 | 56.69 | 25-MAY-21:30 | 9.50 | 8.92 |
June | 0.156176E+10 | 3842.59 | 13-JUN-18:02 | 23.37 | 16.34 | 95318216.73 | 56.69 | 25-JUN-03:39 | 10.33 | 9.99 |
July | 0.189851E+10 | 3768.49 | 16-JUL-18:02 | 18.67 | 15.16 | 98510390.55 | 56.70 | 21-JUL-21:10 | 17.00 | 13.87 |
August | 0.178416E+10 | 3758.24 | 10-AUG-15:02 | 20.67 | 15.35 | 98633125.72 | 56.69 | 16-AUG-21:49 | 16.17 | 14.83 |
September | 0.130265E+10 | 3863.96 | 29-SEP-15:01 | 15.67 | 9.39 | 95038521.31 | 56.69 | 14-SEP-21:40 | 15.67 | 9.39 |
October | 0.371877E+09 | 3910.58 | 07-OCT-15:02 | 18.83 | 10.03 | 95712043.57 | 56.69 | 08-OCT-00:49 | 10.00 | 8.90 |
November | 77007576.24 | 3748.33 | 03-NOV-15:01 | 8.83 | 5.57 | 90942839.80 | 56.69 | 01-NOV-22:49 | 8.83 | 5.57 |
December | 35108602.52 | 386.08 | 26-DEC-16:05 | 2.67 | 1.50 | 92720765.02 | 56.69 | 27-DEC-00:20 | 1.67 | 1.38 |
Annual Sum or Average | 0.941557E+10 | 0.113246E+10 | ||||||||
Minimum of Months | 35108602.52 | 386.08 | 2.67 | 1.50 | 85254704.03 | 56.69 | 1.67 | 1.38 | ||
Maximum of Months | 0.189851E+10 | 3970.98 | 23.37 | 16.34 | 98633125.72 | 56.70 | 17.00 | 14.83 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 37762236.83 | 1345.54 | 19-JAN-16:01 | 7.67 | 7.22 | 92819372.87 | 56.69 | 12-JAN-23:49 | 7.67 | 7.22 |
February | 63377857.10 | 2757.61 | 19-FEB-16:02 | 5.17 | 4.17 | 84215653.66 | 56.69 | 04-FEB-00:10 | 5.17 | 4.17 |
March | 83774853.26 | 3199.66 | 20-MAR-18:02 | 7.83 | 5.10 | 93890290.50 | 56.69 | 05-MAR-00:20 | 7.83 | 5.10 |
April | 0.668954E+09 | 3468.02 | 26-APR-15:02 | 14.83 | 9.50 | 93851893.85 | 56.69 | 28-APR-22:49 | 9.33 | 8.03 |
May | 0.901057E+09 | 3552.20 | 21-MAY-15:01 | 18.83 | 10.43 | 97368234.60 | 56.70 | 22-MAY-21:10 | 14.83 | 12.59 |
June | 0.139917E+10 | 3499.22 | 13-JUN-18:02 | 23.37 | 16.34 | 95191066.29 | 56.70 | 21-JUN-21:10 | 13.83 | 12.18 |
July | 0.166967E+10 | 3426.28 | 24-JUL-18:02 | 17.67 | 14.85 | 98389548.13 | 56.69 | 21-JUL-21:10 | 17.67 | 14.85 |
August | 0.139618E+10 | 3396.68 | 27-AUG-15:02 | 18.17 | 14.46 | 98404769.22 | 56.69 | 24-AUG-00:49 | 18.17 | 14.46 |
September | 0.822232E+09 | 3423.80 | 29-SEP-15:01 | 15.67 | 9.39 | 94383476.20 | 56.69 | 14-SEP-03:20 | 15.67 | 9.39 |
October | 0.191869E+09 | 3445.90 | 07-OCT-15:02 | 18.83 | 10.03 | 94741579.97 | 56.69 | 07-OCT-23:10 | 10.83 | 9.32 |
November | 49256655.64 | 1464.58 | 10-NOV-16:02 | 10.33 | 8.12 | 90126301.32 | 56.69 | 29-NOV-00:20 | -1.0 | -1.4 |
December | 17484888.41 | 99.93 | 06-DEC-11:02 | 7.17 | 5.22 | 92327267.86 | 56.69 | 31-DEC-00:10 | 1.00 | 0.58 |
Annual Sum or Average | 0.730080E+10 | 0.112571E+10 | ||||||||
Minimum of Months | 17484888.41 | 99.93 | 5.17 | 4.17 | 84215653.66 | 56.69 | -1.0 | -1.4 | ||
Maximum of Months | 0.166967E+10 | 3552.20 | 23.37 | 16.34 | 98404769.22 | 56.70 | 18.17 | 14.85 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.237727E+09 | 2366.52 | 11-JAN-16:01 | -2.2 | -4.4 | 95665145.61 | 56.69 | 17-JAN-22:19 | 5.10 | 4.61 |
February | 0.277516E+09 | 2401.31 | 18-FEB-16:01 | 5.83 | 4.00 | 86900416.61 | 56.69 | 27-FEB-22:19 | 4.67 | 4.67 |
March | 0.165512E+09 | 2373.54 | 20-MAR-15:01 | 10.83 | 7.32 | 95806587.28 | 56.69 | 20-MAR-21:10 | 4.90 | 3.99 |
April | 0.842885E+09 | 2429.20 | 13-APR-15:02 | 12.00 | 7.14 | 95040993.05 | 56.69 | 13-APR-22:10 | 5.88 | 4.06 |
May | 0.744174E+09 | 2432.77 | 11-MAY-15:01 | 17.17 | 9.62 | 98066384.71 | 56.69 | 22-MAY-22:00 | 14.00 | 12.24 |
June | 0.915565E+09 | 2327.33 | 12-JUN-18:02 | 25.67 | 17.63 | 95340825.96 | 56.69 | 26-JUN-22:00 | 15.00 | 14.41 |
July | 0.112628E+10 | 2345.99 | 26-JUL-15:02 | 19.68 | 15.17 | 98537512.89 | 56.69 | 17-JUL-22:40 | 19.68 | 15.17 |
August | 0.127827E+10 | 2336.78 | 10-AUG-15:02 | 20.67 | 15.35 | 98645076.29 | 56.69 | 15-AUG-22:00 | 14.00 | 12.84 |
September | 0.124299E+10 | 2403.17 | 29-SEP-15:01 | 15.67 | 9.39 | 95374454.25 | 56.70 | 11-SEP-21:10 | 15.67 | 9.39 |
October | 0.568290E+09 | 2459.10 | 07-OCT-15:02 | 18.83 | 10.03 | 96985110.80 | 56.69 | 07-OCT-23:00 | 10.00 | 8.90 |
November | 0.216041E+09 | 2411.53 | 03-NOV-15:01 | 8.83 | 5.57 | 92746682.89 | 56.69 | 03-NOV-21:19 | 4.00 | 2.72 |
December | 0.102292E+09 | 2272.53 | 18-DEC-16:02 | 5.17 | 3.90 | 94513090.98 | 56.69 | 31-DEC-00:10 | 1.00 | 0.58 |
Annual Sum or Average | 0.771755E+10 | 0.114362E+10 | ||||||||
Minimum of Months | 0.102292E+09 | 2272.53 | -2.2 | -4.4 | 86900416.61 | 56.69 | 1.00 | 0.58 | ||
Maximum of Months | 0.127827E+10 | 2459.10 | 25.67 | 17.63 | 98645076.29 | 56.70 | 19.68 | 15.17 |
Report: ZoneCoolingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.375097E+11 | 18575.80 | 18-JAN-23:00 | 7.80 | 7.26 | 0.151136E+11 | 9927.17 | 18-JAN-23:10 | 7.80 | 7.23 |
February | 0.344667E+11 | 18510.29 | 07-FEB-23:00 | 7.00 | 7.00 | 0.136906E+11 | 9900.73 | 07-FEB-23:10 | 6.83 | 6.83 |
March | 0.395466E+11 | 18656.64 | 17-MAR-22:00 | 8.00 | 7.45 | 0.153829E+11 | 9966.63 | 30-MAR-22:10 | 5.43 | 3.80 |
April | 0.412603E+11 | 20484.79 | 29-APR-18:03 | 19.67 | 12.19 | 0.150266E+11 | 10278.38 | 28-APR-21:40 | 19.67 | 12.19 |
May | 0.433936E+11 | 21408.22 | 22-MAY-18:10 | 19.00 | 14.26 | 0.156707E+11 | 10394.22 | 22-MAY-21:40 | 14.33 | 12.38 |
June | 0.438991E+11 | 22203.62 | 12-JUN-18:10 | 25.67 | 17.63 | 0.154314E+11 | 10659.52 | 21-JUN-22:10 | 12.83 | 11.81 |
July | 0.459212E+11 | 22256.21 | 22-JUL-18:10 | 29.83 | 16.84 | 0.159090E+11 | 10647.75 | 25-JUL-22:10 | 13.00 | 12.44 |
August | 0.454661E+11 | 22154.24 | 14-AUG-17:08 | 27.00 | 14.28 | 0.159314E+11 | 10546.80 | 02-AUG-22:10 | 27.00 | 14.28 |
September | 0.421877E+11 | 20493.64 | 11-SEP-18:10 | 21.50 | 15.69 | 0.151503E+11 | 10474.07 | 11-SEP-22:10 | 12.83 | 11.23 |
October | 0.405088E+11 | 19011.88 | 17-OCT-22:00 | 11.00 | 11.00 | 0.153908E+11 | 10072.55 | 12-OCT-22:10 | 11.00 | 11.00 |
November | 0.373596E+11 | 18896.75 | 08-NOV-23:00 | 11.00 | 11.00 | 0.147438E+11 | 10022.46 | 08-NOV-23:10 | 11.00 | 11.00 |
December | 0.370184E+11 | 18252.70 | 04-DEC-23:00 | 7.00 | 7.00 | 0.150809E+11 | 9804.00 | 04-DEC-23:10 | 7.00 | 7.00 |
Annual Sum or Average | 0.488538E+12 | 0.182522E+12 | ||||||||
Minimum of Months | 0.344667E+11 | 18252.70 | 7.00 | 7.00 | 0.136906E+11 | 9804.00 | 5.43 | 3.80 | ||
Maximum of Months | 0.459212E+11 | 22256.21 | 29.83 | 17.63 | 0.159314E+11 | 10659.52 | 27.00 | 14.28 |
Report: ZoneCoolingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.405662E+11 | 19786.82 | 18-JAN-23:00 | 7.80 | 7.26 | 0.152198E+11 | 10035.27 | 18-JAN-23:10 | 7.80 | 7.23 |
February | 0.372250E+11 | 19716.50 | 07-FEB-23:00 | 7.00 | 7.00 | 0.137899E+11 | 10008.08 | 07-FEB-23:10 | 6.83 | 6.83 |
March | 0.426763E+11 | 19886.43 | 17-MAR-22:00 | 8.00 | 7.45 | 0.155085E+11 | 10078.54 | 30-MAR-22:10 | 5.43 | 3.80 |
April | 0.443281E+11 | 21823.48 | 29-APR-18:03 | 19.67 | 12.19 | 0.151584E+11 | 10387.33 | 28-APR-22:10 | 19.67 | 12.19 |
May | 0.466074E+11 | 22778.05 | 22-MAY-18:10 | 19.00 | 14.26 | 0.158167E+11 | 10508.55 | 22-MAY-22:10 | 14.00 | 12.24 |
June | 0.470688E+11 | 23613.89 | 12-JUN-18:10 | 25.67 | 17.63 | 0.155867E+11 | 10782.84 | 21-JUN-22:10 | 12.83 | 11.81 |
July | 0.491871E+11 | 23677.26 | 22-JUL-18:10 | 29.83 | 16.84 | 0.160717E+11 | 10773.52 | 25-JUL-22:10 | 13.00 | 12.44 |
August | 0.487082E+11 | 23569.19 | 14-AUG-17:08 | 27.00 | 14.28 | 0.160817E+11 | 10669.86 | 02-AUG-22:10 | 27.00 | 14.28 |
September | 0.452599E+11 | 21788.01 | 11-SEP-18:10 | 21.50 | 15.69 | 0.152800E+11 | 10582.01 | 11-SEP-22:10 | 12.83 | 11.23 |
October | 0.436206E+11 | 20255.36 | 17-OCT-22:00 | 11.00 | 11.00 | 0.155145E+11 | 10182.65 | 12-OCT-22:10 | 11.00 | 11.00 |
November | 0.403330E+11 | 20135.01 | 08-NOV-23:00 | 11.00 | 11.00 | 0.148567E+11 | 10134.83 | 08-NOV-23:10 | 11.00 | 11.00 |
December | 0.400938E+11 | 19445.97 | 04-DEC-23:00 | 7.00 | 7.00 | 0.151843E+11 | 9910.70 | 04-DEC-23:10 | 7.00 | 7.00 |
Annual Sum or Average | 0.525674E+12 | 0.184069E+12 | ||||||||
Minimum of Months | 0.372250E+11 | 19445.97 | 7.00 | 7.00 | 0.137899E+11 | 9910.70 | 5.43 | 3.80 | ||
Maximum of Months | 0.491871E+11 | 23677.26 | 29.83 | 17.63 | 0.160817E+11 | 10782.84 | 27.00 | 14.28 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.509090E+11 | 26672.72 | 15-JAN-11:50 | 8.83 | 6.51 | 0.186191E+11 | 11319.61 | 07-JAN-18:19 | 8.83 | 6.51 |
February | 0.463822E+11 | 26896.83 | 22-FEB-11:40 | 10.00 | 8.60 | 0.168225E+11 | 11319.56 | 18-FEB-18:19 | 10.00 | 8.60 |
March | 0.520964E+11 | 27770.77 | 25-MAR-10:50 | 11.42 | 8.36 | 0.186356E+11 | 11319.55 | 11-MAR-18:19 | 11.42 | 8.36 |
April | 0.536528E+11 | 30429.54 | 30-APR-10:40 | 19.33 | 11.65 | 0.180535E+11 | 11327.14 | 15-APR-17:10 | 19.33 | 11.65 |
May | 0.557704E+11 | 30306.53 | 23-MAY-10:50 | 20.00 | 14.59 | 0.186590E+11 | 11323.23 | 06-MAY-17:00 | 20.00 | 14.59 |
June | 0.554119E+11 | 30626.29 | 13-JUN-10:40 | 22.00 | 15.85 | 0.180679E+11 | 11319.74 | 10-JUN-17:19 | 22.00 | 15.85 |
July | 0.578396E+11 | 31221.45 | 23-JUL-10:40 | 21.00 | 15.99 | 0.186689E+11 | 11319.75 | 15-JUL-17:19 | 21.00 | 15.99 |
August | 0.578742E+11 | 30773.76 | 14-AUG-17:08 | 27.00 | 14.28 | 0.186732E+11 | 11319.76 | 19-AUG-17:19 | 18.00 | 14.38 |
September | 0.547856E+11 | 29955.44 | 12-SEP-10:40 | 17.67 | 14.44 | 0.180603E+11 | 11334.10 | 30-SEP-17:40 | 11.67 | 8.71 |
October | 0.534044E+11 | 28886.76 | 04-OCT-10:35 | 13.07 | 9.87 | 0.186396E+11 | 11319.87 | 07-OCT-17:49 | 11.67 | 8.56 |
November | 0.498507E+11 | 26686.77 | 11-NOV-11:50 | 9.00 | 6.94 | 0.180231E+11 | 11319.55 | 25-NOV-18:19 | 7.00 | 4.56 |
December | 0.502151E+11 | 25726.04 | 03-DEC-11:50 | 6.83 | 4.26 | 0.186120E+11 | 11319.54 | 02-DEC-18:30 | 6.83 | 4.26 |
Annual Sum or Average | 0.638192E+12 | 0.219535E+12 | ||||||||
Minimum of Months | 0.463822E+11 | 25726.04 | 6.83 | 4.26 | 0.168225E+11 | 11319.54 | 6.83 | 4.26 | ||
Maximum of Months | 0.578742E+11 | 31221.45 | 27.00 | 15.99 | 0.186732E+11 | 11334.10 | 22.00 | 15.99 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.134445E+10 | 3777.44 | 15-JAN-13:00 | 10.00 | 6.68 | 0.126872E+10 | 745.73 | 30-JAN-01:39 | 5.67 | 5.07 |
February | 0.170108E+10 | 4167.31 | 04-FEB-13:40 | 9.00 | 6.13 | 0.114712E+10 | 745.76 | 14-FEB-05:00 | 4.00 | 2.70 |
March | 0.242526E+10 | 4013.48 | 25-MAR-11:50 | 11.92 | 8.82 | 0.127475E+10 | 745.74 | 20-MAR-04:30 | 11.92 | 8.82 |
April | 0.673506E+10 | 6741.10 | 29-APR-17:12 | 20.00 | 12.62 | 0.123139E+10 | 745.69 | 08-APR-03:20 | 20.00 | 12.62 |
May | 0.743841E+10 | 6669.91 | 22-MAY-17:12 | 19.00 | 14.26 | 0.127246E+10 | 745.71 | 18-MAY-04:10 | 19.00 | 14.26 |
June | 0.923583E+10 | 7278.48 | 25-JUN-10:35 | 20.00 | 13.96 | 0.123464E+10 | 751.62 | 13-JUN-21:30 | 20.00 | 13.96 |
July | 0.104667E+11 | 7605.39 | 23-JUL-10:35 | 21.00 | 15.99 | 0.127207E+10 | 754.11 | 21-JUL-21:30 | 21.00 | 15.99 |
August | 0.103789E+11 | 7515.19 | 14-AUG-17:08 | 27.00 | 14.28 | 0.127716E+10 | 745.69 | 26-AUG-00:10 | 14.00 | 11.92 |
September | 0.842491E+10 | 6493.49 | 13-SEP-16:20 | 23.00 | 16.07 | 0.123134E+10 | 745.70 | 18-SEP-00:30 | 12.00 | 9.30 |
October | 0.441052E+10 | 5688.90 | 07-OCT-15:30 | 18.50 | 9.89 | 0.126949E+10 | 745.75 | 28-OCT-03:49 | 8.00 | 7.44 |
November | 0.196168E+10 | 3690.09 | 11-NOV-13:00 | 9.00 | 7.43 | 0.122734E+10 | 745.75 | 21-NOV-01:19 | 2.67 | 2.23 |
December | 0.564803E+09 | 2749.62 | 18-DEC-13:30 | 8.00 | 5.46 | 0.126878E+10 | 745.74 | 21-DEC-01:00 | 5.00 | 4.09 |
Annual Sum or Average | 0.650876E+11 | 0.149753E+11 | ||||||||
Minimum of Months | 0.564803E+09 | 2749.62 | 8.00 | 5.46 | 0.114712E+10 | 745.69 | 2.67 | 2.23 | ||
Maximum of Months | 0.104667E+11 | 7605.39 | 27.00 | 16.07 | 0.127716E+10 | 754.11 | 21.00 | 15.99 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 1.92 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 3.80 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.23 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.47 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.57 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 6.57 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 4.00 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 1.92 | |
Maximum of Months | 0.00 | 0.00 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.142146E+09 | 525.39 | 10-JAN-08:00 | -6.0 |
February | 74547518.04 | 425.65 | 17-FEB-07:20 | -3.7 |
March | 47592495.16 | 276.90 | 16-MAR-06:30 | 1.50 |
April | 1293464.20 | 102.63 | 01-APR-06:20 | 3.33 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.47 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 |
October | 1338224.87 | 137.82 | 28-OCT-06:50 | 4.50 |
November | 57423732.24 | 338.53 | 29-NOV-09:10 | 1.17 |
December | 0.284543E+09 | 448.22 | 30-DEC-09:10 | 0.00 |
Annual Sum or Average | 0.608884E+09 | |||
Minimum of Months | 0.00 | 0.00 | -6.0 | |
Maximum of Months | 0.284543E+09 | 525.39 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 1.92 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 3.80 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.23 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.47 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.57 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 6.57 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 4.00 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 1.92 | |
Maximum of Months | 0.00 | 0.00 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 9917418.00 | 187.85 | 12-JAN-05:00 | -2.0 |
February | 212135.15 | 39.65 | 18-FEB-05:00 | -3.0 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 3.80 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.23 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.47 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.57 |
November | 28911.17 | 9.96 | 29-NOV-04:30 | -0.5 |
December | 1961916.76 | 111.77 | 30-DEC-05:30 | -1.5 |
Annual Sum or Average | 12120381.09 | |||
Minimum of Months | 0.00 | 0.00 | -3.0 | |
Maximum of Months | 9917418.00 | 187.85 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 89230342.80 | 231.68 | 12-JAN-14:00 | -1.0 |
February | 37366151.80 | 138.81 | 18-FEB-05:10 | -2.7 |
March | 7942133.99 | 96.54 | 15-MAR-11:50 | 1.17 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.23 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.47 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.57 |
November | 21027376.52 | 150.93 | 29-NOV-11:05 | 3.17 |
December | 0.100758E+09 | 194.81 | 30-DEC-17:00 | 1.00 |
Annual Sum or Average | 0.256324E+09 | |||
Minimum of Months | 0.00 | 0.00 | -2.7 | |
Maximum of Months | 0.100758E+09 | 231.68 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 1.92 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 3.80 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.23 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.47 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.57 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 6.57 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 4.00 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 1.92 | |
Maximum of Months | 0.00 | 0.00 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 1.92 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 3.80 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.23 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.47 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.57 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 6.57 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 4.00 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 1.92 | |
Maximum of Months | 0.00 | 0.00 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 1.92 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 3.80 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.23 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.47 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.57 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 6.57 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 4.00 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 1.92 | |
Maximum of Months | 0.00 | 0.00 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.651345E+09 | 1610.32 | 03-JAN-16:02 | 3.83 |
February | 0.461183E+09 | 1584.24 | 16-FEB-09:02 | 3.22 |
March | 0.413215E+09 | 1593.71 | 15-MAR-15:02 | 3.00 |
April | 66560429.92 | 1491.04 | 10-APR-15:02 | 7.17 |
May | 44545485.51 | 1514.42 | 05-MAY-08:62 | 8.17 |
June | 3400167.31 | 1000.60 | 18-JUN-08:03 | 13.17 |
July | 3717660.73 | 967.89 | 30-JUL-08:03 | 14.83 |
August | 1947855.19 | 914.28 | 12-AUG-08:03 | 14.33 |
September | 9917799.35 | 835.69 | 06-SEP-18:03 | 12.83 |
October | 0.178661E+09 | 1557.12 | 19-OCT-15:02 | 9.00 |
November | 0.480093E+09 | 1611.49 | 29-NOV-16:02 | 3.83 |
December | 0.938416E+09 | 1617.25 | 27-DEC-16:02 | 3.00 |
Annual Sum or Average | 0.325300E+10 | |||
Minimum of Months | 1947855.19 | 835.69 | 3.00 | |
Maximum of Months | 0.938416E+09 | 1617.25 | 14.83 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.860364E+09 | 1574.35 | 11-JAN-09:02 | -3.8 |
February | 0.629031E+09 | 1548.14 | 17-FEB-09:02 | 1.33 |
March | 0.488573E+09 | 1547.00 | 15-MAR-15:02 | 3.00 |
April | 0.102942E+09 | 1474.45 | 11-APR-08:62 | 7.17 |
May | 53806890.77 | 1470.98 | 05-MAY-08:62 | 8.17 |
June | 3387362.58 | 751.77 | 17-JUN-18:04 | 14.83 |
July | 3866729.08 | 902.05 | 04-JUL-08:03 | 12.00 |
August | 1893840.00 | 883.83 | 12-AUG-08:03 | 14.33 |
September | 18346201.65 | 860.97 | 10-SEP-08:03 | 15.33 |
October | 0.256883E+09 | 1511.30 | 19-OCT-15:02 | 9.00 |
November | 0.627244E+09 | 1566.75 | 29-NOV-16:02 | 3.83 |
December | 0.108363E+10 | 1572.96 | 27-DEC-16:02 | 3.00 |
Annual Sum or Average | 0.412997E+10 | |||
Minimum of Months | 1893840.00 | 751.77 | -3.8 | |
Maximum of Months | 0.108363E+10 | 1574.35 | 15.33 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 1.92 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 3.80 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.23 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.47 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.57 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 6.57 |
December | 3725419.00 | 84.46 | 17-DEC-04:40 | 1.00 |
Annual Sum or Average | 3725419.00 | |||
Minimum of Months | 0.00 | 0.00 | 1.00 | |
Maximum of Months | 3725419.00 | 84.46 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 27783427.33 | 440.66 | 11-JAN-16:01 | -2.2 |
February | 6671581.43 | 413.89 | 17-FEB-16:02 | 5.83 |
March | 1210263.10 | 411.39 | 15-MAR-15:02 | 3.00 |
April | 750051.10 | 301.58 | 01-APR-18:04 | 8.83 |
May | 497928.93 | 226.22 | 26-MAY-08:05 | 10.17 |
June | 144365.99 | 214.47 | 27-JUN-08:06 | 14.67 |
July | 258337.45 | 240.76 | 13-JUL-08:06 | 14.50 |
August | 231018.39 | 347.05 | 04-AUG-08:05 | 14.27 |
September | 564217.09 | 384.97 | 29-SEP-15:04 | 15.67 |
October | 1053268.74 | 257.20 | 06-OCT-18:04 | 11.33 |
November | 5892930.73 | 425.78 | 29-NOV-16:02 | 3.83 |
December | 25600028.96 | 429.77 | 27-DEC-16:02 | 3.00 |
Annual Sum or Average | 70657419.24 | |||
Minimum of Months | 144365.99 | 214.47 | -2.2 | |
Maximum of Months | 27783427.33 | 440.66 | 15.67 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.657742E+09 | 1566.24 | 12-JAN-16:02 | -1.0 |
February | 0.491066E+09 | 1540.00 | 01-FEB-16:02 | 7.00 |
March | 0.419606E+09 | 1547.35 | 15-MAR-15:02 | 3.00 |
April | 62828879.81 | 1443.05 | 10-APR-15:02 | 7.17 |
May | 46004832.58 | 718.33 | 14-MAY-15:04 | 11.83 |
June | 5873596.24 | 823.69 | 03-JUN-15:04 | 16.17 |
July | 2146553.15 | 754.67 | 02-JUL-15:04 | 15.67 |
August | 1027243.20 | 767.80 | 26-AUG-15:04 | 17.00 |
September | 6176835.12 | 664.12 | 08-SEP-15:04 | 14.83 |
October | 0.178596E+09 | 1511.43 | 27-OCT-15:02 | 9.00 |
November | 0.483497E+09 | 1563.86 | 29-NOV-16:02 | 3.83 |
December | 0.900211E+09 | 1568.45 | 27-DEC-16:02 | 3.00 |
Annual Sum or Average | 0.325478E+10 | |||
Minimum of Months | 1027243.20 | 664.12 | -1.0 | |
Maximum of Months | 0.900211E+09 | 1568.45 | 17.00 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.854592E+09 | 1546.43 | 10-JAN-16:01 | -3.0 |
February | 0.670395E+09 | 1502.16 | 25-FEB-16:02 | 5.00 |
March | 0.492996E+09 | 1504.73 | 15-MAR-15:02 | 3.00 |
April | 96790812.37 | 1410.06 | 10-APR-15:02 | 7.17 |
May | 58498975.85 | 704.11 | 04-MAY-08:63 | 9.00 |
June | 6710557.38 | 836.27 | 17-JUN-15:04 | 15.83 |
July | 2551896.36 | 695.18 | 07-JUL-15:04 | 15.83 |
August | 1689714.14 | 671.10 | 22-AUG-15:05 | 17.00 |
September | 13766804.76 | 929.20 | 29-SEP-18:03 | 11.83 |
October | 0.253338E+09 | 1470.42 | 27-OCT-15:02 | 9.00 |
November | 0.623980E+09 | 1522.44 | 29-NOV-16:02 | 3.83 |
December | 0.103078E+10 | 1528.71 | 27-DEC-16:02 | 3.00 |
Annual Sum or Average | 0.410608E+10 | |||
Minimum of Months | 1689714.14 | 671.10 | -3.0 | |
Maximum of Months | 0.103078E+10 | 1546.43 | 17.00 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 20174980.55 | 345.05 | 04-JAN-15:00 | 4.00 |
February | 2862648.94 | 136.45 | 16-FEB-09:03 | 3.22 |
March | 872653.55 | 87.12 | 15-MAR-13:50 | 2.83 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.23 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.47 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.57 |
November | 9304738.01 | 292.90 | 30-NOV-15:00 | 6.00 |
December | 63560192.34 | 360.66 | 10-DEC-16:00 | 4.00 |
Annual Sum or Average | 96775213.39 | |||
Minimum of Months | 0.00 | 0.00 | 2.83 | |
Maximum of Months | 63560192.34 | 360.66 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.109233E+10 | 1944.50 | 03-JAN-16:02 | 3.83 |
February | 0.793206E+09 | 1916.94 | 16-FEB-09:02 | 3.22 |
March | 0.730245E+09 | 1914.52 | 15-MAR-15:02 | 3.00 |
April | 0.158776E+09 | 1824.55 | 11-APR-08:62 | 7.17 |
May | 0.105104E+09 | 1827.26 | 05-MAY-08:62 | 8.17 |
June | 8644107.74 | 973.97 | 03-JUN-08:03 | 11.17 |
July | 10959018.24 | 1009.13 | 30-JUL-08:03 | 14.83 |
August | 2141251.99 | 875.59 | 03-AUG-08:03 | 14.17 |
September | 30947181.73 | 936.73 | 02-SEP-08:03 | 13.33 |
October | 0.375155E+09 | 1888.12 | 19-OCT-15:02 | 9.00 |
November | 0.835954E+09 | 1947.70 | 29-NOV-16:02 | 3.83 |
December | 0.145348E+10 | 1958.86 | 27-DEC-16:02 | 3.00 |
Annual Sum or Average | 0.559694E+10 | |||
Minimum of Months | 2141251.99 | 875.59 | 3.00 | |
Maximum of Months | 0.145348E+10 | 1958.86 | 14.83 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.135997E+10 | 1899.50 | 10-JAN-09:02 | -3.8 |
February | 0.100933E+10 | 1864.74 | 17-FEB-09:02 | 1.33 |
March | 0.831947E+09 | 1856.71 | 15-MAR-08:62 | 2.00 |
April | 0.219555E+09 | 1779.64 | 11-APR-08:62 | 7.17 |
May | 0.123896E+09 | 1774.44 | 05-MAY-08:62 | 8.17 |
June | 9912817.26 | 915.58 | 18-JUN-08:03 | 13.17 |
July | 11604534.19 | 974.37 | 30-JUL-08:03 | 14.83 |
August | 3262681.73 | 833.40 | 26-AUG-15:04 | 17.00 |
September | 56814626.03 | 1741.27 | 20-SEP-08:62 | 11.50 |
October | 0.502124E+09 | 1831.87 | 19-OCT-15:02 | 9.00 |
November | 0.102523E+10 | 1892.13 | 29-NOV-16:02 | 3.83 |
December | 0.162922E+10 | 1900.89 | 27-DEC-16:02 | 3.00 |
Annual Sum or Average | 0.678287E+10 | |||
Minimum of Months | 3262681.73 | 833.40 | -3.8 | |
Maximum of Months | 0.162922E+10 | 1900.89 | 17.00 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.236621E+09 | 1070.10 | 04-JAN-16:02 | 3.92 |
February | 0.164524E+09 | 1047.21 | 02-FEB-09:02 | 4.33 |
March | 0.164627E+09 | 1052.69 | 15-MAR-15:02 | 3.00 |
April | 18305546.71 | 695.91 | 10-APR-15:02 | 7.17 |
May | 15920546.05 | 533.32 | 24-MAY-08:03 | 12.17 |
June | 2304614.68 | 597.78 | 20-JUN-08:03 | 15.17 |
July | 1263677.39 | 569.77 | 12-JUL-08:03 | 13.50 |
August | 882196.67 | 596.54 | 04-AUG-08:03 | 14.27 |
September | 1536864.14 | 488.46 | 17-SEP-08:03 | 12.17 |
October | 46564822.65 | 1027.43 | 27-OCT-15:02 | 9.00 |
November | 0.152706E+09 | 1069.61 | 30-NOV-16:02 | 6.00 |
December | 0.399565E+09 | 1074.45 | 27-DEC-16:02 | 3.00 |
Annual Sum or Average | 0.120482E+10 | |||
Minimum of Months | 882196.67 | 488.46 | 3.00 | |
Maximum of Months | 0.399565E+09 | 1074.45 | 15.17 |
Report: ZoneHeatingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 1.92 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 3.80 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.23 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.47 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.57 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 6.57 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 4.00 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 1.92 | |
Maximum of Months | 0.00 | 0.00 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 1.92 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 3.80 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.23 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.47 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.57 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 6.57 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 4.00 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 1.92 | |
Maximum of Months | 0.00 | 0.00 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 1.92 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 3.80 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.23 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.47 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.57 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 6.57 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 4.00 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 1.92 | |
Maximum of Months | 0.00 | 0.00 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.587317E+09 | 1747.35 | 10-JAN-08:00 | -6.0 |
February | 0.271905E+09 | 1656.21 | 17-FEB-07:30 | -3.5 |
March | 0.102036E+09 | 1028.86 | 16-MAR-06:10 | 1.17 |
April | 6478280.96 | 393.91 | 09-APR-05:00 | 1.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.47 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 |
October | 5362252.79 | 454.56 | 23-OCT-06:10 | 4.00 |
November | 0.161533E+09 | 1395.28 | 29-NOV-09:02 | 1.17 |
December | 0.801419E+09 | 1608.70 | 27-DEC-09:40 | 0.33 |
Annual Sum or Average | 0.193605E+10 | |||
Minimum of Months | 0.00 | 0.00 | -6.0 | |
Maximum of Months | 0.801419E+09 | 1747.35 | 12.43 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.140333E+11 | 13517.00 | 02-JAN-20:10 | 0.127587E+11 | 10113.80 | 02-JAN-20:10 |
February | 0.126708E+11 | 13517.00 | 01-FEB-20:10 | 0.115208E+11 | 10113.80 | 01-FEB-20:10 |
March | 0.140766E+11 | 13517.00 | 01-MAR-20:10 | 0.127855E+11 | 10113.80 | 01-MAR-20:10 |
April | 0.135575E+11 | 13517.00 | 03-APR-19:10 | 0.123314E+11 | 10113.80 | 03-APR-19:10 |
May | 0.140576E+11 | 13517.00 | 01-MAY-19:10 | 0.127741E+11 | 10113.80 | 01-MAY-19:10 |
June | 0.136197E+11 | 13517.00 | 01-JUN-19:10 | 0.123716E+11 | 10113.80 | 01-JUN-19:10 |
July | 0.139955E+11 | 13517.00 | 03-JUL-19:10 | 0.127338E+11 | 10113.80 | 03-JUL-19:10 |
August | 0.140820E+11 | 13517.00 | 01-AUG-19:10 | 0.127894E+11 | 10113.80 | 01-AUG-19:10 |
September | 0.135629E+11 | 13517.00 | 01-SEP-19:10 | 0.123352E+11 | 10113.80 | 01-SEP-19:10 |
October | 0.140279E+11 | 13517.00 | 02-OCT-19:10 | 0.127549E+11 | 10113.80 | 02-OCT-19:10 |
November | 0.136089E+11 | 13517.00 | 01-NOV-19:10 | 0.123659E+11 | 10113.80 | 01-NOV-19:10 |
December | 0.139955E+11 | 13517.00 | 01-DEC-20:10 | 0.127338E+11 | 10113.80 | 01-DEC-20:10 |
Annual Sum or Average | 0.165288E+12 | 0.150255E+12 | ||||
Minimum of Months | 0.126708E+11 | 13517.00 | 0.115208E+11 | 10113.80 | ||
Maximum of Months | 0.140820E+11 | 13517.00 | 0.127894E+11 | 10113.80 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.713551E+09 | 687.30 | 02-JAN-20:10 | 0.864900E+09 | 685.60 | 02-JAN-20:10 |
February | 0.644271E+09 | 687.30 | 01-FEB-20:10 | 0.780982E+09 | 685.60 | 01-FEB-20:10 |
March | 0.715750E+09 | 687.30 | 01-MAR-20:10 | 0.866718E+09 | 685.60 | 01-MAR-20:10 |
April | 0.689358E+09 | 687.30 | 03-APR-19:10 | 0.835931E+09 | 685.60 | 03-APR-19:10 |
May | 0.714788E+09 | 687.30 | 01-MAY-19:10 | 0.865939E+09 | 685.60 | 01-MAY-19:10 |
June | 0.692519E+09 | 687.30 | 01-JUN-19:10 | 0.838659E+09 | 685.60 | 01-JUN-19:10 |
July | 0.711626E+09 | 687.30 | 03-JUL-19:10 | 0.863211E+09 | 685.60 | 03-JUL-19:10 |
August | 0.716025E+09 | 687.30 | 01-AUG-19:10 | 0.866978E+09 | 685.60 | 01-AUG-19:10 |
September | 0.689633E+09 | 687.30 | 01-SEP-19:10 | 0.836191E+09 | 685.60 | 01-SEP-19:10 |
October | 0.713276E+09 | 687.30 | 02-OCT-19:10 | 0.864640E+09 | 685.60 | 02-OCT-19:10 |
November | 0.691970E+09 | 687.30 | 01-NOV-19:10 | 0.838269E+09 | 685.60 | 01-NOV-19:10 |
December | 0.711626E+09 | 687.30 | 01-DEC-20:10 | 0.863211E+09 | 685.60 | 01-DEC-20:10 |
Annual Sum or Average | 0.840439E+10 | 0.101856E+11 | ||||
Minimum of Months | 0.644271E+09 | 687.30 | 0.780982E+09 | 685.60 | ||
Maximum of Months | 0.716025E+09 | 687.30 | 0.866978E+09 | 685.60 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.826294E+09 | 795.89 | 02-JAN-20:10 | 0.100156E+10 | 793.93 | 02-JAN-20:10 |
February | 0.746069E+09 | 795.89 | 01-FEB-20:10 | 0.904380E+09 | 793.93 | 01-FEB-20:10 |
March | 0.828841E+09 | 795.89 | 01-MAR-20:10 | 0.100366E+10 | 793.93 | 01-MAR-20:10 |
April | 0.798279E+09 | 795.89 | 03-APR-19:10 | 0.968011E+09 | 793.93 | 03-APR-19:10 |
May | 0.827727E+09 | 795.89 | 01-MAY-19:10 | 0.100276E+10 | 793.93 | 01-MAY-19:10 |
June | 0.801940E+09 | 795.89 | 01-JUN-19:10 | 0.971170E+09 | 793.93 | 01-JUN-19:10 |
July | 0.824066E+09 | 795.89 | 03-JUL-19:10 | 0.999601E+09 | 793.93 | 03-JUL-19:10 |
August | 0.829160E+09 | 795.89 | 01-AUG-19:10 | 0.100396E+10 | 793.93 | 01-AUG-19:10 |
September | 0.798597E+09 | 795.89 | 01-SEP-19:10 | 0.968312E+09 | 793.93 | 01-SEP-19:10 |
October | 0.825976E+09 | 795.89 | 02-OCT-19:10 | 0.100126E+10 | 793.93 | 02-OCT-19:10 |
November | 0.801303E+09 | 795.89 | 01-NOV-19:10 | 0.970719E+09 | 793.93 | 01-NOV-19:10 |
December | 0.824066E+09 | 795.89 | 01-DEC-20:10 | 0.999601E+09 | 793.93 | 01-DEC-20:10 |
Annual Sum or Average | 0.973232E+10 | 0.117950E+11 | ||||
Minimum of Months | 0.746069E+09 | 795.89 | 0.904380E+09 | 793.93 | ||
Maximum of Months | 0.829160E+09 | 795.89 | 0.100396E+10 | 793.93 |
Report: ZoneElectricSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.154452E+10 | 1487.69 | 02-JAN-20:10 | 0.105898E+10 | 839.45 | 02-JAN-20:10 |
February | 0.139456E+10 | 1487.69 | 01-FEB-20:10 | 0.956227E+09 | 839.45 | 01-FEB-20:10 |
March | 0.154928E+10 | 1487.69 | 01-MAR-20:10 | 0.106120E+10 | 839.45 | 01-MAR-20:10 |
April | 0.149215E+10 | 1487.69 | 03-APR-19:10 | 0.102351E+10 | 839.45 | 03-APR-19:10 |
May | 0.154719E+10 | 1487.69 | 01-MAY-19:10 | 0.106025E+10 | 839.45 | 01-MAY-19:10 |
June | 0.149899E+10 | 1487.69 | 01-JUN-19:10 | 0.102685E+10 | 839.45 | 01-JUN-19:10 |
July | 0.154035E+10 | 1487.69 | 03-JUL-19:10 | 0.105691E+10 | 839.45 | 03-JUL-19:10 |
August | 0.154987E+10 | 1487.69 | 01-AUG-19:10 | 0.106152E+10 | 839.45 | 01-AUG-19:10 |
September | 0.149274E+10 | 1487.69 | 01-SEP-19:10 | 0.102382E+10 | 839.45 | 01-SEP-19:10 |
October | 0.154392E+10 | 1487.69 | 02-OCT-19:10 | 0.105866E+10 | 839.45 | 02-OCT-19:10 |
November | 0.149780E+10 | 1487.69 | 01-NOV-19:10 | 0.102637E+10 | 839.45 | 01-NOV-19:10 |
December | 0.154035E+10 | 1487.69 | 01-DEC-20:10 | 0.105691E+10 | 839.45 | 01-DEC-20:10 |
Annual Sum or Average | 0.181917E+11 | 0.124712E+11 | ||||
Minimum of Months | 0.139456E+10 | 1487.69 | 0.956227E+09 | 839.45 | ||
Maximum of Months | 0.154987E+10 | 1487.69 | 0.106152E+10 | 839.45 |
Report: ZoneElectricSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.283535E+09 | 273.10 | 02-JAN-20:10 | 0.305485E+09 | 242.16 | 02-JAN-20:10 |
February | 0.256006E+09 | 273.10 | 01-FEB-20:10 | 0.275845E+09 | 242.16 | 01-FEB-20:10 |
March | 0.284409E+09 | 273.10 | 01-MAR-20:10 | 0.306128E+09 | 242.16 | 01-MAR-20:10 |
April | 0.273921E+09 | 273.10 | 03-APR-19:10 | 0.295253E+09 | 242.16 | 03-APR-19:10 |
May | 0.284026E+09 | 273.10 | 01-MAY-19:10 | 0.305852E+09 | 242.16 | 01-MAY-19:10 |
June | 0.275178E+09 | 273.10 | 01-JUN-19:10 | 0.296217E+09 | 242.16 | 01-JUN-19:10 |
July | 0.282770E+09 | 273.10 | 03-JUL-19:10 | 0.304889E+09 | 242.16 | 03-JUL-19:10 |
August | 0.284518E+09 | 273.10 | 01-AUG-19:10 | 0.306219E+09 | 242.16 | 01-AUG-19:10 |
September | 0.274031E+09 | 273.10 | 01-SEP-19:10 | 0.295345E+09 | 242.16 | 01-SEP-19:10 |
October | 0.283425E+09 | 273.10 | 02-OCT-19:10 | 0.305393E+09 | 242.16 | 02-OCT-19:10 |
November | 0.274959E+09 | 273.10 | 01-NOV-19:10 | 0.296079E+09 | 242.16 | 01-NOV-19:10 |
December | 0.282770E+09 | 273.10 | 01-DEC-20:10 | 0.304889E+09 | 242.16 | 01-DEC-20:10 |
Annual Sum or Average | 0.333955E+10 | 0.359760E+10 | ||||
Minimum of Months | 0.256006E+09 | 273.10 | 0.275845E+09 | 242.16 | ||
Maximum of Months | 0.284518E+09 | 273.10 | 0.306219E+09 | 242.16 |
Report: ZoneElectricSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.350256E+09 | 337.37 | 02-JAN-20:10 | 0.576866E+10 | 4572.80 | 02-JAN-20:10 |
February | 0.316249E+09 | 337.37 | 01-FEB-20:10 | 0.520895E+10 | 4572.80 | 01-FEB-20:10 |
March | 0.351336E+09 | 337.37 | 01-MAR-20:10 | 0.578079E+10 | 4572.80 | 01-MAR-20:10 |
April | 0.338381E+09 | 337.37 | 03-APR-19:10 | 0.557545E+10 | 4572.80 | 03-APR-19:10 |
May | 0.350863E+09 | 337.37 | 01-MAY-19:10 | 0.577559E+10 | 4572.80 | 01-MAY-19:10 |
June | 0.339933E+09 | 337.37 | 01-JUN-19:10 | 0.559364E+10 | 4572.80 | 01-JUN-19:10 |
July | 0.349311E+09 | 337.37 | 03-JUL-19:10 | 0.575740E+10 | 4572.80 | 03-JUL-19:10 |
August | 0.351471E+09 | 337.37 | 01-AUG-19:10 | 0.578252E+10 | 4572.80 | 01-AUG-19:10 |
September | 0.338516E+09 | 337.37 | 01-SEP-19:10 | 0.557718E+10 | 4572.80 | 01-SEP-19:10 |
October | 0.350121E+09 | 337.37 | 02-OCT-19:10 | 0.576693E+10 | 4572.80 | 02-OCT-19:10 |
November | 0.339663E+09 | 337.37 | 01-NOV-19:10 | 0.559104E+10 | 4572.80 | 01-NOV-19:10 |
December | 0.349311E+09 | 337.37 | 01-DEC-20:10 | 0.575740E+10 | 4572.80 | 01-DEC-20:10 |
Annual Sum or Average | 0.412541E+10 | 0.679355E+11 | ||||
Minimum of Months | 0.316249E+09 | 337.37 | 0.520895E+10 | 4572.80 | ||
Maximum of Months | 0.351471E+09 | 337.37 | 0.578252E+10 | 4572.80 |
Report: ZoneElectricSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.226040E+10 | 2177.23 | 02-JAN-20:10 | 0.121771E+10 | 965.27 | 02-JAN-20:10 |
February | 0.204093E+10 | 2177.23 | 01-FEB-20:10 | 0.109956E+10 | 965.27 | 01-FEB-20:10 |
March | 0.226736E+10 | 2177.23 | 01-MAR-20:10 | 0.122027E+10 | 965.27 | 01-MAR-20:10 |
April | 0.218376E+10 | 2177.23 | 03-APR-19:10 | 0.117692E+10 | 965.27 | 03-APR-19:10 |
May | 0.226431E+10 | 2177.23 | 01-MAY-19:10 | 0.121917E+10 | 965.27 | 01-MAY-19:10 |
June | 0.219377E+10 | 2177.23 | 01-JUN-19:10 | 0.118076E+10 | 965.27 | 01-JUN-19:10 |
July | 0.225430E+10 | 2177.23 | 03-JUL-19:10 | 0.121533E+10 | 965.27 | 03-JUL-19:10 |
August | 0.226823E+10 | 2177.23 | 01-AUG-19:10 | 0.122063E+10 | 965.27 | 01-AUG-19:10 |
September | 0.218463E+10 | 2177.23 | 01-SEP-19:10 | 0.117729E+10 | 965.27 | 01-SEP-19:10 |
October | 0.225952E+10 | 2177.23 | 02-OCT-19:10 | 0.121734E+10 | 965.27 | 02-OCT-19:10 |
November | 0.219203E+10 | 2177.23 | 01-NOV-19:10 | 0.118021E+10 | 965.27 | 01-NOV-19:10 |
December | 0.225430E+10 | 2177.23 | 01-DEC-20:10 | 0.121533E+10 | 965.27 | 01-DEC-20:10 |
Annual Sum or Average | 0.266236E+11 | 0.143405E+11 | ||||
Minimum of Months | 0.204093E+10 | 2177.23 | 0.109956E+10 | 965.27 | ||
Maximum of Months | 0.226823E+10 | 2177.23 | 0.122063E+10 | 965.27 |
Report: ZoneElectricSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.123020E+11 | 11849.32 | 02-JAN-20:10 | 0.126520E+11 | 10029.21 | 02-JAN-20:10 |
February | 0.111075E+11 | 11849.32 | 01-FEB-20:10 | 0.114244E+11 | 10029.21 | 01-FEB-20:10 |
March | 0.123399E+11 | 11849.32 | 01-MAR-20:10 | 0.126786E+11 | 10029.21 | 01-MAR-20:10 |
April | 0.118849E+11 | 11849.32 | 03-APR-19:10 | 0.122282E+11 | 10029.21 | 03-APR-19:10 |
May | 0.123233E+11 | 11849.32 | 01-MAY-19:10 | 0.126672E+11 | 10029.21 | 01-MAY-19:10 |
June | 0.119394E+11 | 11849.32 | 01-JUN-19:10 | 0.122682E+11 | 10029.21 | 01-JUN-19:10 |
July | 0.122688E+11 | 11849.32 | 03-JUL-19:10 | 0.126273E+11 | 10029.21 | 03-JUL-19:10 |
August | 0.123446E+11 | 11849.32 | 01-AUG-19:10 | 0.126824E+11 | 10029.21 | 01-AUG-19:10 |
September | 0.118896E+11 | 11849.32 | 01-SEP-19:10 | 0.122320E+11 | 10029.21 | 01-SEP-19:10 |
October | 0.122972E+11 | 11849.32 | 02-OCT-19:10 | 0.126482E+11 | 10029.21 | 02-OCT-19:10 |
November | 0.119299E+11 | 11849.32 | 01-NOV-19:10 | 0.122624E+11 | 10029.21 | 01-NOV-19:10 |
December | 0.122688E+11 | 11849.32 | 01-DEC-20:10 | 0.126273E+11 | 10029.21 | 01-DEC-20:10 |
Annual Sum or Average | 0.144896E+12 | 0.148998E+12 | ||||
Minimum of Months | 0.111075E+11 | 11849.32 | 0.114244E+11 | 10029.21 | ||
Maximum of Months | 0.123446E+11 | 11849.32 | 0.126824E+11 | 10029.21 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.434056E+09 | 392.73 | 01-JAN-19:10 | 0.261068E+09 | 237.06 | 01-JAN-08:09 |
February | 0.391995E+09 | 392.73 | 01-FEB-20:10 | 0.235798E+09 | 237.06 | 01-FEB-07:10 |
March | 0.430607E+09 | 392.73 | 01-MAR-20:10 | 0.260708E+09 | 237.06 | 01-MAR-07:10 |
April | 0.420554E+09 | 392.73 | 01-APR-18:10 | 0.252705E+09 | 237.06 | 01-APR-07:10 |
May | 0.432331E+09 | 392.73 | 01-MAY-19:10 | 0.260888E+09 | 237.06 | 01-MAY-06:10 |
June | 0.417218E+09 | 392.73 | 01-JUN-19:10 | 0.252344E+09 | 237.06 | 01-JUN-06:10 |
July | 0.435725E+09 | 392.73 | 01-JUL-18:10 | 0.261248E+09 | 237.06 | 01-JUL-07:10 |
August | 0.430607E+09 | 392.73 | 01-AUG-19:10 | 0.260708E+09 | 237.06 | 01-AUG-06:10 |
September | 0.420667E+09 | 392.73 | 01-SEP-19:10 | 0.252705E+09 | 237.06 | 01-SEP-06:10 |
October | 0.434000E+09 | 392.73 | 01-OCT-18:10 | 0.261068E+09 | 237.06 | 01-OCT-07:10 |
November | 0.418886E+09 | 392.73 | 01-NOV-19:10 | 0.252524E+09 | 237.06 | 01-NOV-06:10 |
December | 0.435781E+09 | 392.73 | 01-DEC-20:10 | 0.261248E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.510243E+10 | 0.307301E+10 | ||||
Minimum of Months | 0.391995E+09 | 392.73 | 0.235798E+09 | 237.06 | ||
Maximum of Months | 0.435781E+09 | 392.73 | 0.261248E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.434005E+09 | 392.68 | 01-JAN-19:10 | 0.261038E+09 | 237.03 | 01-JAN-08:09 |
February | 0.391949E+09 | 392.68 | 01-FEB-20:10 | 0.235770E+09 | 237.03 | 01-FEB-07:10 |
March | 0.430556E+09 | 392.68 | 01-MAR-20:10 | 0.260677E+09 | 237.03 | 01-MAR-07:10 |
April | 0.420505E+09 | 392.68 | 01-APR-18:10 | 0.252675E+09 | 237.03 | 01-APR-07:10 |
May | 0.432281E+09 | 392.68 | 01-MAY-19:10 | 0.260857E+09 | 237.03 | 01-MAY-06:10 |
June | 0.417169E+09 | 392.68 | 01-JUN-19:10 | 0.252315E+09 | 237.03 | 01-JUN-06:10 |
July | 0.435674E+09 | 392.68 | 01-JUL-18:10 | 0.261218E+09 | 237.03 | 01-JUL-07:10 |
August | 0.430556E+09 | 392.68 | 01-AUG-19:10 | 0.260677E+09 | 237.03 | 01-AUG-06:10 |
September | 0.420618E+09 | 392.68 | 01-SEP-19:10 | 0.252675E+09 | 237.03 | 01-SEP-06:10 |
October | 0.433949E+09 | 392.68 | 01-OCT-18:10 | 0.261038E+09 | 237.03 | 01-OCT-07:10 |
November | 0.418837E+09 | 392.68 | 01-NOV-19:10 | 0.252495E+09 | 237.03 | 01-NOV-06:10 |
December | 0.435730E+09 | 392.68 | 01-DEC-20:10 | 0.261218E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.510183E+10 | 0.307265E+10 | ||||
Minimum of Months | 0.391949E+09 | 392.68 | 0.235770E+09 | 237.03 | ||
Maximum of Months | 0.435730E+09 | 392.68 | 0.261218E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.272788E+09 | 246.81 | 01-JAN-19:10 | 0.255708E+09 | 232.19 | 01-JAN-08:09 |
February | 0.246354E+09 | 246.81 | 01-FEB-20:10 | 0.230956E+09 | 232.19 | 01-FEB-07:10 |
March | 0.270620E+09 | 246.81 | 01-MAR-20:10 | 0.255355E+09 | 232.19 | 01-MAR-07:10 |
April | 0.264302E+09 | 246.81 | 01-APR-18:10 | 0.247516E+09 | 232.19 | 01-APR-07:10 |
May | 0.271704E+09 | 246.81 | 01-MAY-19:10 | 0.255532E+09 | 232.19 | 01-MAY-06:10 |
June | 0.262205E+09 | 246.81 | 01-JUN-19:10 | 0.247163E+09 | 232.19 | 01-JUN-06:10 |
July | 0.273836E+09 | 246.81 | 01-JUL-18:10 | 0.255885E+09 | 232.19 | 01-JUL-07:10 |
August | 0.270620E+09 | 246.81 | 01-AUG-19:10 | 0.255355E+09 | 232.19 | 01-AUG-06:10 |
September | 0.264373E+09 | 246.81 | 01-SEP-19:10 | 0.247516E+09 | 232.19 | 01-SEP-06:10 |
October | 0.272752E+09 | 246.81 | 01-OCT-18:10 | 0.255708E+09 | 232.19 | 01-OCT-07:10 |
November | 0.263254E+09 | 246.81 | 01-NOV-19:10 | 0.247340E+09 | 232.19 | 01-NOV-06:10 |
December | 0.273872E+09 | 246.81 | 01-DEC-20:10 | 0.255885E+09 | 232.19 | 01-DEC-07:10 |
Annual Sum or Average | 0.320668E+10 | 0.300992E+10 | ||||
Minimum of Months | 0.246354E+09 | 246.81 | 0.230956E+09 | 232.19 | ||
Maximum of Months | 0.273872E+09 | 246.81 | 0.255885E+09 | 232.19 |
Report: ZoneElectricSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.272862E+09 | 246.88 | 01-JAN-19:10 | 0.255778E+09 | 232.26 | 01-JAN-08:09 |
February | 0.246421E+09 | 246.88 | 01-FEB-20:10 | 0.231020E+09 | 232.26 | 01-FEB-07:10 |
March | 0.270694E+09 | 246.88 | 01-MAR-20:10 | 0.255425E+09 | 232.26 | 01-MAR-07:10 |
April | 0.264375E+09 | 246.88 | 01-APR-18:10 | 0.247584E+09 | 232.26 | 01-APR-07:10 |
May | 0.271778E+09 | 246.88 | 01-MAY-19:10 | 0.255602E+09 | 232.26 | 01-MAY-06:10 |
June | 0.262277E+09 | 246.88 | 01-JUN-19:10 | 0.247231E+09 | 232.26 | 01-JUN-06:10 |
July | 0.273911E+09 | 246.88 | 01-JUL-18:10 | 0.255955E+09 | 232.26 | 01-JUL-07:10 |
August | 0.270694E+09 | 246.88 | 01-AUG-19:10 | 0.255425E+09 | 232.26 | 01-AUG-06:10 |
September | 0.264446E+09 | 246.88 | 01-SEP-19:10 | 0.247584E+09 | 232.26 | 01-SEP-06:10 |
October | 0.272827E+09 | 246.88 | 01-OCT-18:10 | 0.255778E+09 | 232.26 | 01-OCT-07:10 |
November | 0.263326E+09 | 246.88 | 01-NOV-19:10 | 0.247408E+09 | 232.26 | 01-NOV-06:10 |
December | 0.273947E+09 | 246.88 | 01-DEC-20:10 | 0.255955E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.320756E+10 | 0.301074E+10 | ||||
Minimum of Months | 0.246421E+09 | 246.88 | 0.231020E+09 | 232.26 | ||
Maximum of Months | 0.273947E+09 | 246.88 | 0.255955E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.434056E+09 | 392.73 | 01-JAN-19:10 | 0.261068E+09 | 237.06 | 01-JAN-08:09 |
February | 0.391995E+09 | 392.73 | 01-FEB-20:10 | 0.235798E+09 | 237.06 | 01-FEB-07:10 |
March | 0.430607E+09 | 392.73 | 01-MAR-20:10 | 0.260708E+09 | 237.06 | 01-MAR-07:10 |
April | 0.420554E+09 | 392.73 | 01-APR-18:10 | 0.252705E+09 | 237.06 | 01-APR-07:10 |
May | 0.432331E+09 | 392.73 | 01-MAY-19:10 | 0.260888E+09 | 237.06 | 01-MAY-06:10 |
June | 0.417218E+09 | 392.73 | 01-JUN-19:10 | 0.252344E+09 | 237.06 | 01-JUN-06:10 |
July | 0.435725E+09 | 392.73 | 01-JUL-18:10 | 0.261248E+09 | 237.06 | 01-JUL-07:10 |
August | 0.430607E+09 | 392.73 | 01-AUG-19:10 | 0.260708E+09 | 237.06 | 01-AUG-06:10 |
September | 0.420667E+09 | 392.73 | 01-SEP-19:10 | 0.252705E+09 | 237.06 | 01-SEP-06:10 |
October | 0.434000E+09 | 392.73 | 01-OCT-18:10 | 0.261068E+09 | 237.06 | 01-OCT-07:10 |
November | 0.418886E+09 | 392.73 | 01-NOV-19:10 | 0.252524E+09 | 237.06 | 01-NOV-06:10 |
December | 0.435781E+09 | 392.73 | 01-DEC-20:10 | 0.261248E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.510243E+10 | 0.307301E+10 | ||||
Minimum of Months | 0.391995E+09 | 392.73 | 0.235798E+09 | 237.06 | ||
Maximum of Months | 0.435781E+09 | 392.73 | 0.261248E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.434005E+09 | 392.68 | 01-JAN-19:10 | 0.261038E+09 | 237.03 | 01-JAN-08:09 |
February | 0.391949E+09 | 392.68 | 01-FEB-20:10 | 0.235770E+09 | 237.03 | 01-FEB-07:10 |
March | 0.430556E+09 | 392.68 | 01-MAR-20:10 | 0.260677E+09 | 237.03 | 01-MAR-07:10 |
April | 0.420505E+09 | 392.68 | 01-APR-18:10 | 0.252675E+09 | 237.03 | 01-APR-07:10 |
May | 0.432281E+09 | 392.68 | 01-MAY-19:10 | 0.260857E+09 | 237.03 | 01-MAY-06:10 |
June | 0.417169E+09 | 392.68 | 01-JUN-19:10 | 0.252315E+09 | 237.03 | 01-JUN-06:10 |
July | 0.435674E+09 | 392.68 | 01-JUL-18:10 | 0.261218E+09 | 237.03 | 01-JUL-07:10 |
August | 0.430556E+09 | 392.68 | 01-AUG-19:10 | 0.260677E+09 | 237.03 | 01-AUG-06:10 |
September | 0.420618E+09 | 392.68 | 01-SEP-19:10 | 0.252675E+09 | 237.03 | 01-SEP-06:10 |
October | 0.433949E+09 | 392.68 | 01-OCT-18:10 | 0.261038E+09 | 237.03 | 01-OCT-07:10 |
November | 0.418837E+09 | 392.68 | 01-NOV-19:10 | 0.252495E+09 | 237.03 | 01-NOV-06:10 |
December | 0.435730E+09 | 392.68 | 01-DEC-20:10 | 0.261218E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.510183E+10 | 0.307265E+10 | ||||
Minimum of Months | 0.391949E+09 | 392.68 | 0.235770E+09 | 237.03 | ||
Maximum of Months | 0.435730E+09 | 392.68 | 0.261218E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.133160E+10 | 1282.60 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.120231E+10 | 1282.60 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.133570E+10 | 1282.60 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.128645E+10 | 1282.60 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.133391E+10 | 1282.60 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.129235E+10 | 1282.60 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.132801E+10 | 1282.60 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.133622E+10 | 1282.60 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.128696E+10 | 1282.60 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.133109E+10 | 1282.60 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.129132E+10 | 1282.60 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.132801E+10 | 1282.60 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.156839E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.120231E+10 | 1282.60 | 0.00 | 0.00 | |
Maximum of Months | 0.133622E+10 | 1282.60 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.434056E+09 | 392.73 | 01-JAN-19:10 | 0.261068E+09 | 237.06 | 01-JAN-08:09 |
February | 0.391995E+09 | 392.73 | 01-FEB-20:10 | 0.235798E+09 | 237.06 | 01-FEB-07:10 |
March | 0.430607E+09 | 392.73 | 01-MAR-20:10 | 0.260708E+09 | 237.06 | 01-MAR-07:10 |
April | 0.420554E+09 | 392.73 | 01-APR-18:10 | 0.252705E+09 | 237.06 | 01-APR-07:10 |
May | 0.432331E+09 | 392.73 | 01-MAY-19:10 | 0.260888E+09 | 237.06 | 01-MAY-06:10 |
June | 0.417218E+09 | 392.73 | 01-JUN-19:10 | 0.252344E+09 | 237.06 | 01-JUN-06:10 |
July | 0.435725E+09 | 392.73 | 01-JUL-18:10 | 0.261248E+09 | 237.06 | 01-JUL-07:10 |
August | 0.430607E+09 | 392.73 | 01-AUG-19:10 | 0.260708E+09 | 237.06 | 01-AUG-06:10 |
September | 0.420667E+09 | 392.73 | 01-SEP-19:10 | 0.252705E+09 | 237.06 | 01-SEP-06:10 |
October | 0.434000E+09 | 392.73 | 01-OCT-18:10 | 0.261068E+09 | 237.06 | 01-OCT-07:10 |
November | 0.418886E+09 | 392.73 | 01-NOV-19:10 | 0.252524E+09 | 237.06 | 01-NOV-06:10 |
December | 0.435781E+09 | 392.73 | 01-DEC-20:10 | 0.261248E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.510243E+10 | 0.307301E+10 | ||||
Minimum of Months | 0.391995E+09 | 392.73 | 0.235798E+09 | 237.06 | ||
Maximum of Months | 0.435781E+09 | 392.73 | 0.261248E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.434005E+09 | 392.68 | 01-JAN-19:10 | 0.261038E+09 | 237.03 | 01-JAN-08:09 |
February | 0.391949E+09 | 392.68 | 01-FEB-20:10 | 0.235770E+09 | 237.03 | 01-FEB-07:10 |
March | 0.430556E+09 | 392.68 | 01-MAR-20:10 | 0.260677E+09 | 237.03 | 01-MAR-07:10 |
April | 0.420505E+09 | 392.68 | 01-APR-18:10 | 0.252675E+09 | 237.03 | 01-APR-07:10 |
May | 0.432281E+09 | 392.68 | 01-MAY-19:10 | 0.260857E+09 | 237.03 | 01-MAY-06:10 |
June | 0.417169E+09 | 392.68 | 01-JUN-19:10 | 0.252315E+09 | 237.03 | 01-JUN-06:10 |
July | 0.435674E+09 | 392.68 | 01-JUL-18:10 | 0.261218E+09 | 237.03 | 01-JUL-07:10 |
August | 0.430556E+09 | 392.68 | 01-AUG-19:10 | 0.260677E+09 | 237.03 | 01-AUG-06:10 |
September | 0.420618E+09 | 392.68 | 01-SEP-19:10 | 0.252675E+09 | 237.03 | 01-SEP-06:10 |
October | 0.433949E+09 | 392.68 | 01-OCT-18:10 | 0.261038E+09 | 237.03 | 01-OCT-07:10 |
November | 0.418837E+09 | 392.68 | 01-NOV-19:10 | 0.252495E+09 | 237.03 | 01-NOV-06:10 |
December | 0.435730E+09 | 392.68 | 01-DEC-20:10 | 0.261218E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.510183E+10 | 0.307265E+10 | ||||
Minimum of Months | 0.391949E+09 | 392.68 | 0.235770E+09 | 237.03 | ||
Maximum of Months | 0.435730E+09 | 392.68 | 0.261218E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.272862E+09 | 246.88 | 01-JAN-19:10 | 0.255778E+09 | 232.26 | 01-JAN-08:09 |
February | 0.246421E+09 | 246.88 | 01-FEB-20:10 | 0.231020E+09 | 232.26 | 01-FEB-07:10 |
March | 0.270694E+09 | 246.88 | 01-MAR-20:10 | 0.255425E+09 | 232.26 | 01-MAR-07:10 |
April | 0.264375E+09 | 246.88 | 01-APR-18:10 | 0.247584E+09 | 232.26 | 01-APR-07:10 |
May | 0.271778E+09 | 246.88 | 01-MAY-19:10 | 0.255602E+09 | 232.26 | 01-MAY-06:10 |
June | 0.262277E+09 | 246.88 | 01-JUN-19:10 | 0.247231E+09 | 232.26 | 01-JUN-06:10 |
July | 0.273911E+09 | 246.88 | 01-JUL-18:10 | 0.255955E+09 | 232.26 | 01-JUL-07:10 |
August | 0.270694E+09 | 246.88 | 01-AUG-19:10 | 0.255425E+09 | 232.26 | 01-AUG-06:10 |
September | 0.264446E+09 | 246.88 | 01-SEP-19:10 | 0.247584E+09 | 232.26 | 01-SEP-06:10 |
October | 0.272827E+09 | 246.88 | 01-OCT-18:10 | 0.255778E+09 | 232.26 | 01-OCT-07:10 |
November | 0.263326E+09 | 246.88 | 01-NOV-19:10 | 0.247408E+09 | 232.26 | 01-NOV-06:10 |
December | 0.273947E+09 | 246.88 | 01-DEC-20:10 | 0.255955E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.320756E+10 | 0.301074E+10 | ||||
Minimum of Months | 0.246421E+09 | 246.88 | 0.231020E+09 | 232.26 | ||
Maximum of Months | 0.273947E+09 | 246.88 | 0.255955E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.396945E+10 | 3823.39 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.358405E+10 | 3823.39 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.398168E+10 | 3823.39 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.383486E+10 | 3823.39 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.397633E+10 | 3823.39 | 01-MAY-19:10 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.385245E+10 | 3823.39 | 01-JUN-19:10 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.395874E+10 | 3823.39 | 03-JUL-19:10 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.398321E+10 | 3823.39 | 01-AUG-19:10 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.383639E+10 | 3823.39 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.396792E+10 | 3823.39 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.384939E+10 | 3823.39 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.395874E+10 | 3823.39 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.467532E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.358405E+10 | 3823.39 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.398321E+10 | 3823.39 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.396945E+10 | 3823.39 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.358405E+10 | 3823.39 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.398168E+10 | 3823.39 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.383486E+10 | 3823.39 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.397633E+10 | 3823.39 | 01-MAY-19:10 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.385245E+10 | 3823.39 | 01-JUN-19:10 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.395874E+10 | 3823.39 | 03-JUL-19:10 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.398321E+10 | 3823.39 | 01-AUG-19:10 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.383639E+10 | 3823.39 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.396792E+10 | 3823.39 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.384939E+10 | 3823.39 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.395874E+10 | 3823.39 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.467532E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.358405E+10 | 3823.39 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.398321E+10 | 3823.39 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.105977E+10 | 1020.78 | 02-JAN-20:10 | 0.373720E+11 | 16686.59 | 01-JAN-07:10 |
February | 0.956878E+09 | 1020.78 | 01-FEB-20:10 | 0.337554E+11 | 16686.59 | 01-FEB-07:10 |
March | 0.106304E+10 | 1020.78 | 01-MAR-20:10 | 0.373720E+11 | 16686.59 | 01-MAR-07:10 |
April | 0.102384E+10 | 1020.78 | 03-APR-19:10 | 0.361665E+11 | 16686.59 | 01-APR-06:10 |
May | 0.106161E+10 | 1020.78 | 01-MAY-19:10 | 0.373720E+11 | 16686.59 | 01-MAY-06:10 |
June | 0.102854E+10 | 1020.78 | 01-JUN-19:10 | 0.361665E+11 | 16686.59 | 01-JUN-06:10 |
July | 0.105691E+10 | 1020.78 | 03-JUL-19:10 | 0.373720E+11 | 16686.59 | 01-JUL-06:10 |
August | 0.106345E+10 | 1020.78 | 01-AUG-19:10 | 0.373720E+11 | 16686.59 | 01-AUG-06:10 |
September | 0.102425E+10 | 1020.78 | 01-SEP-19:10 | 0.361665E+11 | 16686.59 | 01-SEP-06:10 |
October | 0.105936E+10 | 1020.78 | 02-OCT-19:10 | 0.373720E+11 | 16686.59 | 01-OCT-06:10 |
November | 0.102772E+10 | 1020.78 | 01-NOV-19:10 | 0.361665E+11 | 16686.59 | 01-NOV-06:10 |
December | 0.105691E+10 | 1020.78 | 01-DEC-20:10 | 0.373720E+11 | 16686.59 | 01-DEC-07:10 |
Annual Sum or Average | 0.124823E+11 | 0.440025E+12 | ||||
Minimum of Months | 0.956878E+09 | 1020.78 | 0.337554E+11 | 16686.59 | ||
Maximum of Months | 0.106345E+10 | 1020.78 | 0.373720E+11 | 16686.59 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.140929E+10 | 1357.44 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.127246E+10 | 1357.44 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.141364E+10 | 1357.44 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.136151E+10 | 1357.44 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.141173E+10 | 1357.44 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.136775E+10 | 1357.44 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.140549E+10 | 1357.44 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.141418E+10 | 1357.44 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.136205E+10 | 1357.44 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.140875E+10 | 1357.44 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.136667E+10 | 1357.44 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.140549E+10 | 1357.44 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.165990E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.127246E+10 | 1357.44 | 0.00 | 0.00 | |
Maximum of Months | 0.141418E+10 | 1357.44 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.195762E+11 | 0.140333E+11 | 0.127587E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.176991E+11 | 0.126708E+11 | 0.115208E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.196682E+11 | 0.140766E+11 | 0.127855E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.189781E+11 | 0.135575E+11 | 0.123314E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.196176E+11 | 0.140576E+11 | 0.127741E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.190195E+11 | 0.136197E+11 | 0.123716E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.195762E+11 | 0.139955E+11 | 0.127338E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.196590E+11 | 0.140820E+11 | 0.127894E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.189689E+11 | 0.135629E+11 | 0.123352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.195854E+11 | 0.140279E+11 | 0.127549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.189367E+11 | 0.136089E+11 | 0.123659E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.195762E+11 | 0.139955E+11 | 0.127338E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.230861E+12 | 0.165288E+12 | 0.150255E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.176991E+11 | 0.126708E+11 | 0.115208E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.196682E+11 | 0.140820E+11 | 0.127894E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.199054E+10 | 0.713551E+09 | 0.864900E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.562626E+09 |
February | 0.179968E+10 | 0.644271E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.504423E+09 |
March | 0.199990E+10 | 0.715750E+09 | 0.866718E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.502486E+09 |
April | 0.192973E+10 | 0.689358E+09 | 0.835931E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 617930.27 | 0.386046E+09 |
May | 0.199475E+10 | 0.714788E+09 | 0.865939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 258036.21 | 0.363801E+09 |
June | 0.193394E+10 | 0.692519E+09 | 0.838659E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3129631.63 | 0.245937E+09 |
July | 0.199054E+10 | 0.711626E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6142050.82 | 0.201459E+09 |
August | 0.199896E+10 | 0.716025E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1951415.91 | 0.176927E+09 |
September | 0.192879E+10 | 0.689633E+09 | 0.836191E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 495235.93 | 0.242358E+09 |
October | 0.199148E+10 | 0.713276E+09 | 0.864640E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.384806E+09 |
November | 0.192552E+10 | 0.691970E+09 | 0.838269E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.462376E+09 |
December | 0.199054E+10 | 0.711626E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.558901E+09 |
Annual Sum or Average | 0.234744E+11 | 0.840439E+10 | 0.101856E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 12594300.76 | 0.459215E+10 |
Minimum of Months | 0.179968E+10 | 0.644271E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.176927E+09 |
Maximum of Months | 0.199990E+10 | 0.716025E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6142050.82 | 0.562626E+09 |
Report: SpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.230505E+10 | 0.826294E+09 | 0.100156E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.217911E+09 |
February | 0.208403E+10 | 0.746069E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.194944E+09 |
March | 0.231589E+10 | 0.828841E+09 | 0.100366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.194237E+09 |
April | 0.223463E+10 | 0.798279E+09 | 0.968011E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 285966.29 | 0.149153E+09 |
May | 0.230993E+10 | 0.827727E+09 | 0.100276E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 121232.07 | 0.140966E+09 |
June | 0.223950E+10 | 0.801940E+09 | 0.971170E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1242239.61 | 95807569.77 |
July | 0.230505E+10 | 0.824066E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2419784.39 | 78687883.20 |
August | 0.231480E+10 | 0.829160E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 914774.04 | 68857277.63 |
September | 0.223354E+10 | 0.798597E+09 | 0.968312E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 400765.71 | 93211219.97 |
October | 0.230614E+10 | 0.825976E+09 | 0.100126E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148381E+09 |
November | 0.222975E+10 | 0.801303E+09 | 0.970719E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178766E+09 |
December | 0.230505E+10 | 0.824066E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.217356E+09 |
Annual Sum or Average | 0.271834E+11 | 0.973232E+10 | 0.117950E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 5384762.11 | 0.177828E+10 |
Minimum of Months | 0.208403E+10 | 0.746069E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68857277.63 |
Maximum of Months | 0.231589E+10 | 0.829160E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2419784.39 | 0.217911E+09 |
Report: SpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.487480E+09 | 0.154452E+10 | 0.105898E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.514897E+09 |
February | 0.440737E+09 | 0.139456E+10 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.460581E+09 |
March | 0.489771E+09 | 0.154928E+10 | 0.106120E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.458804E+09 |
April | 0.472586E+09 | 0.149215E+10 | 0.102351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 679312.60 | 0.351310E+09 |
May | 0.488511E+09 | 0.154719E+10 | 0.106025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 286563.14 | 0.331842E+09 |
June | 0.473617E+09 | 0.149899E+10 | 0.102685E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2951302.65 | 0.224909E+09 |
July | 0.487480E+09 | 0.154035E+10 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5742523.30 | 0.184277E+09 |
August | 0.489542E+09 | 0.154987E+10 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2171563.81 | 0.160987E+09 |
September | 0.472357E+09 | 0.149274E+10 | 0.102382E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 947668.39 | 0.218718E+09 |
October | 0.487709E+09 | 0.154392E+10 | 0.105866E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.350030E+09 |
November | 0.471555E+09 | 0.149780E+10 | 0.102637E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.422318E+09 |
December | 0.487480E+09 | 0.154035E+10 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.513668E+09 |
Annual Sum or Average | 0.574883E+10 | 0.181917E+11 | 0.124712E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 12778933.89 | 0.419234E+10 |
Minimum of Months | 0.440737E+09 | 0.139456E+10 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160987E+09 |
Maximum of Months | 0.489771E+09 | 0.154987E+10 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5742523.30 | 0.514897E+09 |
Report: SpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.374985E+09 | 0.283535E+09 | 0.305485E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.297067E+09 |
February | 0.339028E+09 | 0.256006E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.265730E+09 |
March | 0.376747E+09 | 0.284409E+09 | 0.306128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.264706E+09 |
April | 0.363528E+09 | 0.273921E+09 | 0.295253E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 392175.87 | 0.202642E+09 |
May | 0.375778E+09 | 0.284026E+09 | 0.305852E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 165331.78 | 0.191354E+09 |
June | 0.364321E+09 | 0.275178E+09 | 0.296217E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1708103.26 | 0.129415E+09 |
July | 0.374985E+09 | 0.282770E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3335238.63 | 0.105857E+09 |
August | 0.376571E+09 | 0.284518E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1256427.69 | 92415286.07 |
September | 0.363352E+09 | 0.274031E+09 | 0.295345E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 546702.04 | 0.125985E+09 |
October | 0.375161E+09 | 0.283425E+09 | 0.305393E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.201948E+09 |
November | 0.362735E+09 | 0.274959E+09 | 0.296079E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.243655E+09 |
December | 0.374985E+09 | 0.282770E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.296359E+09 |
Annual Sum or Average | 0.442217E+10 | 0.333955E+10 | 0.359760E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7403979.27 | 0.241713E+10 |
Minimum of Months | 0.339028E+09 | 0.256006E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92415286.07 |
Maximum of Months | 0.376747E+09 | 0.284518E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3335238.63 | 0.297067E+09 |
Report: SpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.154405E+10 | 0.350256E+09 | 0.576866E+10 | 0.501157E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.721218E+09 |
February | 0.139600E+10 | 0.316249E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.645225E+09 |
March | 0.155131E+10 | 0.351336E+09 | 0.578079E+10 | 0.502211E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.644601E+09 |
April | 0.149688E+10 | 0.338381E+09 | 0.557545E+10 | 0.484372E+11 | 0.00 | 0.00 | 0.00 | 863184.98 | 0.495548E+09 |
May | 0.154732E+10 | 0.350863E+09 | 0.577559E+10 | 0.501759E+11 | 0.00 | 0.00 | 0.00 | 390710.99 | 0.469513E+09 |
June | 0.150015E+10 | 0.339933E+09 | 0.559364E+10 | 0.485952E+11 | 0.00 | 0.00 | 0.00 | 3859815.01 | 0.321653E+09 |
July | 0.154405E+10 | 0.349311E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 7649165.79 | 0.265511E+09 |
August | 0.155059E+10 | 0.351471E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 2855119.35 | 0.234694E+09 |
September | 0.149615E+10 | 0.338516E+09 | 0.557718E+10 | 0.484522E+11 | 0.00 | 0.00 | 0.00 | 1289820.90 | 0.314113E+09 |
October | 0.154478E+10 | 0.350121E+09 | 0.576693E+10 | 0.501006E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.495295E+09 |
November | 0.149361E+10 | 0.339663E+09 | 0.559104E+10 | 0.485726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.594107E+09 |
December | 0.154405E+10 | 0.349311E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.719359E+09 |
Annual Sum or Average | 0.182090E+11 | 0.412541E+10 | 0.679355E+11 | 0.590196E+12 | 0.00 | 0.00 | 0.00 | 16907817.02 | 0.592084E+10 |
Minimum of Months | 0.139600E+10 | 0.316249E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.234694E+09 |
Maximum of Months | 0.155131E+10 | 0.351471E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 7649165.79 | 0.721218E+09 |
Report: SpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.261570E+11 | 0.226040E+10 | 0.121771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124781E+10 |
February | 0.236489E+11 | 0.204093E+10 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111687E+10 |
March | 0.262800E+11 | 0.226736E+10 | 0.122027E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111192E+10 |
April | 0.253579E+11 | 0.218376E+10 | 0.117692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1523170.32 | 0.852515E+09 |
May | 0.262123E+11 | 0.226431E+10 | 0.121917E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 666685.57 | 0.803943E+09 |
June | 0.254132E+11 | 0.219377E+10 | 0.118076E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7158175.13 | 0.543734E+09 |
July | 0.261570E+11 | 0.225430E+10 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13908339.10 | 0.444885E+09 |
August | 0.262677E+11 | 0.226823E+10 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4813520.89 | 0.389400E+09 |
September | 0.253456E+11 | 0.218463E+10 | 0.117729E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1341864.43 | 0.533110E+09 |
October | 0.261693E+11 | 0.225952E+10 | 0.121734E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.849865E+09 |
November | 0.253025E+11 | 0.219203E+10 | 0.118021E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102353E+10 |
December | 0.261570E+11 | 0.225430E+10 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124402E+10 |
Annual Sum or Average | 0.308468E+12 | 0.266236E+11 | 0.143405E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 29411755.44 | 0.101616E+11 |
Minimum of Months | 0.236489E+11 | 0.204093E+10 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.389400E+09 |
Maximum of Months | 0.262800E+11 | 0.226823E+10 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13908339.10 | 0.124781E+10 |
Report: SpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.776503E+11 | 0.123020E+11 | 0.126520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.356738E+10 |
February | 0.702046E+11 | 0.111075E+11 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.319157E+10 |
March | 0.780153E+11 | 0.123399E+11 | 0.126786E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.318047E+10 |
April | 0.752779E+11 | 0.118849E+11 | 0.122282E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 4703995.63 | 0.244243E+10 |
May | 0.778146E+11 | 0.123233E+11 | 0.126672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1982933.05 | 0.230873E+10 |
June | 0.754422E+11 | 0.119394E+11 | 0.122682E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 20414616.59 | 0.157158E+10 |
July | 0.776503E+11 | 0.122688E+11 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 39764807.62 | 0.129286E+10 |
August | 0.779788E+11 | 0.123446E+11 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 15015117.60 | 0.113387E+10 |
September | 0.752414E+11 | 0.118896E+11 | 0.122320E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 6532900.81 | 0.153121E+10 |
October | 0.776868E+11 | 0.122972E+11 | 0.126482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.243097E+10 |
November | 0.751137E+11 | 0.119299E+11 | 0.122624E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.292738E+10 |
December | 0.776503E+11 | 0.122688E+11 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.355792E+10 |
Annual Sum or Average | 0.915726E+12 | 0.144896E+12 | 0.148998E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 88414371.30 | 0.291364E+11 |
Minimum of Months | 0.702046E+11 | 0.111075E+11 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113387E+10 |
Maximum of Months | 0.780153E+11 | 0.123446E+11 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 39764807.62 | 0.356738E+10 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.434056E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.326002E+09 |
February | 0.273974E+09 | 0.391995E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.293975E+09 |
March | 0.303685E+09 | 0.430607E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.291848E+09 |
April | 0.293479E+09 | 0.420554E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 228995.09 | 0.233309E+09 |
May | 0.303504E+09 | 0.432331E+09 | 0.260888E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 65450.92 | 0.221135E+09 |
June | 0.293842E+09 | 0.417218E+09 | 0.252344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 970988.06 | 0.153626E+09 |
July | 0.303141E+09 | 0.435725E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2576440.24 | 0.128345E+09 |
August | 0.303685E+09 | 0.430607E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 728709.87 | 0.114042E+09 |
September | 0.293479E+09 | 0.420667E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 249515.19 | 0.150211E+09 |
October | 0.303322E+09 | 0.434000E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.227613E+09 |
November | 0.293661E+09 | 0.418886E+09 | 0.252524E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.268126E+09 |
December | 0.303141E+09 | 0.435781E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.321586E+09 |
Annual Sum or Average | 0.357224E+10 | 0.510243E+10 | 0.307301E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4820099.37 | 0.272982E+10 |
Minimum of Months | 0.273974E+09 | 0.391995E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114042E+09 |
Maximum of Months | 0.303685E+09 | 0.435781E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2576440.24 | 0.326002E+09 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.434005E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.322061E+09 |
February | 0.273974E+09 | 0.391949E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.289879E+09 |
March | 0.303685E+09 | 0.430556E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.289866E+09 |
April | 0.293479E+09 | 0.420505E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 231146.05 | 0.230173E+09 |
May | 0.303504E+09 | 0.432281E+09 | 0.260857E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 65843.31 | 0.219199E+09 |
June | 0.293842E+09 | 0.417169E+09 | 0.252315E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 969913.63 | 0.152652E+09 |
July | 0.303141E+09 | 0.435674E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2599912.31 | 0.127418E+09 |
August | 0.303685E+09 | 0.430556E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 733104.96 | 0.112461E+09 |
September | 0.293479E+09 | 0.420618E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 254146.71 | 0.147233E+09 |
October | 0.303322E+09 | 0.433949E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.223923E+09 |
November | 0.293661E+09 | 0.418837E+09 | 0.252495E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.264727E+09 |
December | 0.303141E+09 | 0.435730E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.319050E+09 |
Annual Sum or Average | 0.357224E+10 | 0.510183E+10 | 0.307265E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4854066.96 | 0.269864E+10 |
Minimum of Months | 0.273974E+09 | 0.391949E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112461E+09 |
Maximum of Months | 0.303685E+09 | 0.435730E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2599912.31 | 0.322061E+09 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.272788E+09 | 0.255708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96297035.00 |
February | 0.00 | 0.246354E+09 | 0.230956E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87483767.45 |
March | 0.00 | 0.270620E+09 | 0.255355E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85970393.70 |
April | 0.00 | 0.264302E+09 | 0.247516E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18504.03 | 73248693.77 |
May | 0.00 | 0.271704E+09 | 0.255532E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2652.87 | 70173681.22 |
June | 0.00 | 0.262205E+09 | 0.247163E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 138788.52 | 50973767.67 |
July | 0.00 | 0.273836E+09 | 0.255885E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 506435.91 | 44086125.60 |
August | 0.00 | 0.270620E+09 | 0.255355E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 94347.22 | 40314263.81 |
September | 0.00 | 0.264373E+09 | 0.247516E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50314249.46 |
October | 0.00 | 0.272752E+09 | 0.255708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71897361.75 |
November | 0.00 | 0.263254E+09 | 0.247340E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81121972.05 |
December | 0.00 | 0.273872E+09 | 0.255885E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87459761.94 |
Annual Sum or Average | 0.00 | 0.320668E+10 | 0.300992E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 760728.55 | 0.839341E+09 |
Minimum of Months | 0.00 | 0.246354E+09 | 0.230956E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40314263.81 |
Maximum of Months | 0.00 | 0.273872E+09 | 0.255885E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 506435.91 | 96297035.00 |
Report: SpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.272862E+09 | 0.255778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91710379.29 |
February | 0.273974E+09 | 0.246421E+09 | 0.231020E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82256154.29 |
March | 0.303685E+09 | 0.270694E+09 | 0.255425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82564183.75 |
April | 0.293479E+09 | 0.264375E+09 | 0.247584E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 73082.38 | 64268362.26 |
May | 0.303504E+09 | 0.271778E+09 | 0.255602E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 23555.51 | 61127910.91 |
June | 0.293842E+09 | 0.262277E+09 | 0.247231E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 294397.22 | 42242984.31 |
July | 0.303141E+09 | 0.273911E+09 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 774055.98 | 35129724.03 |
August | 0.303685E+09 | 0.270694E+09 | 0.255425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 236120.07 | 30748673.80 |
September | 0.293479E+09 | 0.264446E+09 | 0.247584E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 78951.45 | 40780660.58 |
October | 0.303322E+09 | 0.272827E+09 | 0.255778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63544135.85 |
November | 0.293661E+09 | 0.263326E+09 | 0.247408E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75625829.76 |
December | 0.303141E+09 | 0.273947E+09 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91237714.29 |
Annual Sum or Average | 0.357224E+10 | 0.320756E+10 | 0.301074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1480162.62 | 0.761237E+09 |
Minimum of Months | 0.273974E+09 | 0.246421E+09 | 0.231020E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30748673.80 |
Maximum of Months | 0.303685E+09 | 0.273947E+09 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 774055.98 | 91710379.29 |
Report: SpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.434056E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.325914E+09 |
February | 0.273974E+09 | 0.391995E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.293770E+09 |
March | 0.303685E+09 | 0.430607E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.292382E+09 |
April | 0.293479E+09 | 0.420554E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 237247.41 | 0.235327E+09 |
May | 0.303504E+09 | 0.432331E+09 | 0.260888E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 66511.75 | 0.222884E+09 |
June | 0.293842E+09 | 0.417218E+09 | 0.252344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 981649.09 | 0.154447E+09 |
July | 0.303141E+09 | 0.435725E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2559441.92 | 0.129285E+09 |
August | 0.303685E+09 | 0.430607E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 734431.29 | 0.114771E+09 |
September | 0.293479E+09 | 0.420667E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 255523.02 | 0.151453E+09 |
October | 0.303322E+09 | 0.434000E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.228390E+09 |
November | 0.293661E+09 | 0.418886E+09 | 0.252524E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.268022E+09 |
December | 0.303141E+09 | 0.435781E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.321903E+09 |
Annual Sum or Average | 0.357224E+10 | 0.510243E+10 | 0.307301E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4834804.48 | 0.273855E+10 |
Minimum of Months | 0.273974E+09 | 0.391995E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114771E+09 |
Maximum of Months | 0.303685E+09 | 0.435781E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2559441.92 | 0.325914E+09 |
Report: SpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.434005E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.322058E+09 |
February | 0.273974E+09 | 0.391949E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.289474E+09 |
March | 0.303685E+09 | 0.430556E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.290454E+09 |
April | 0.293479E+09 | 0.420505E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 240029.18 | 0.233386E+09 |
May | 0.303504E+09 | 0.432281E+09 | 0.260857E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 66624.61 | 0.221799E+09 |
June | 0.293842E+09 | 0.417169E+09 | 0.252315E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 982823.41 | 0.154002E+09 |
July | 0.303141E+09 | 0.435674E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2561437.56 | 0.129040E+09 |
August | 0.303685E+09 | 0.430556E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 737322.99 | 0.114377E+09 |
September | 0.293479E+09 | 0.420618E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 259071.51 | 0.150319E+09 |
October | 0.303322E+09 | 0.433949E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.225179E+09 |
November | 0.293661E+09 | 0.418837E+09 | 0.252495E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.264602E+09 |
December | 0.303141E+09 | 0.435730E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.319358E+09 |
Annual Sum or Average | 0.357224E+10 | 0.510183E+10 | 0.307265E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4847309.26 | 0.271405E+10 |
Minimum of Months | 0.273974E+09 | 0.391949E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114377E+09 |
Maximum of Months | 0.303685E+09 | 0.435730E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2561437.56 | 0.322058E+09 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.385223E+10 | 0.133160E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.397144E+09 |
February | 0.348285E+10 | 0.120231E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.355253E+09 |
March | 0.387034E+10 | 0.133570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.353981E+09 |
April | 0.373454E+10 | 0.128645E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 450138.95 | 0.271642E+09 |
May | 0.386038E+10 | 0.133391E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 190054.31 | 0.256658E+09 |
June | 0.374269E+10 | 0.129235E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2042148.79 | 0.174518E+09 |
July | 0.385223E+10 | 0.132801E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4072789.58 | 0.144351E+09 |
August | 0.386853E+10 | 0.133622E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1443684.07 | 0.126450E+09 |
September | 0.373273E+10 | 0.128696E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 432796.45 | 0.170532E+09 |
October | 0.385404E+10 | 0.133109E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.270411E+09 |
November | 0.372639E+10 | 0.129132E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.325879E+09 |
December | 0.385223E+10 | 0.132801E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.396190E+09 |
Annual Sum or Average | 0.454292E+11 | 0.156839E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8631612.15 | 0.324301E+10 |
Minimum of Months | 0.348285E+10 | 0.120231E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126450E+09 |
Maximum of Months | 0.387034E+10 | 0.133622E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4072789.58 | 0.397144E+09 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.434056E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.325068E+09 |
February | 0.273974E+09 | 0.391995E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.293200E+09 |
March | 0.303685E+09 | 0.430607E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.291310E+09 |
April | 0.293479E+09 | 0.420554E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 207775.55 | 0.234374E+09 |
May | 0.303504E+09 | 0.432331E+09 | 0.260888E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 61200.44 | 0.222351E+09 |
June | 0.293842E+09 | 0.417218E+09 | 0.252344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 935263.56 | 0.155000E+09 |
July | 0.303141E+09 | 0.435725E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2506318.53 | 0.129707E+09 |
August | 0.303685E+09 | 0.430607E+09 | 0.260708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 703404.14 | 0.115309E+09 |
September | 0.293479E+09 | 0.420667E+09 | 0.252705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 231162.05 | 0.151353E+09 |
October | 0.303322E+09 | 0.434000E+09 | 0.261068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.227487E+09 |
November | 0.293661E+09 | 0.418886E+09 | 0.252524E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.267193E+09 |
December | 0.303141E+09 | 0.435781E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.321042E+09 |
Annual Sum or Average | 0.357224E+10 | 0.510243E+10 | 0.307301E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4645124.27 | 0.273339E+10 |
Minimum of Months | 0.273974E+09 | 0.391995E+09 | 0.235798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115309E+09 |
Maximum of Months | 0.303685E+09 | 0.435781E+09 | 0.261248E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2506318.53 | 0.325068E+09 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.434005E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.321486E+09 |
February | 0.273974E+09 | 0.391949E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.288964E+09 |
March | 0.303685E+09 | 0.430556E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.289200E+09 |
April | 0.293479E+09 | 0.420505E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 212256.95 | 0.231571E+09 |
May | 0.303504E+09 | 0.432281E+09 | 0.260857E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 61848.26 | 0.220751E+09 |
June | 0.293842E+09 | 0.417169E+09 | 0.252315E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 932169.82 | 0.154438E+09 |
July | 0.303141E+09 | 0.435674E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2514717.17 | 0.129233E+09 |
August | 0.303685E+09 | 0.430556E+09 | 0.260677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 708623.79 | 0.114435E+09 |
September | 0.293479E+09 | 0.420618E+09 | 0.252675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 237944.39 | 0.148828E+09 |
October | 0.303322E+09 | 0.433949E+09 | 0.261038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.223654E+09 |
November | 0.293661E+09 | 0.418837E+09 | 0.252495E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.263749E+09 |
December | 0.303141E+09 | 0.435730E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.319111E+09 |
Annual Sum or Average | 0.357224E+10 | 0.510183E+10 | 0.307265E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4667560.38 | 0.270542E+10 |
Minimum of Months | 0.273974E+09 | 0.391949E+09 | 0.235770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114435E+09 |
Maximum of Months | 0.303685E+09 | 0.435730E+09 | 0.261218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2514717.17 | 0.321486E+09 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.272862E+09 | 0.255778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.170218E+09 |
February | 0.273974E+09 | 0.246421E+09 | 0.231020E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153135E+09 |
March | 0.303685E+09 | 0.270694E+09 | 0.255425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151859E+09 |
April | 0.293479E+09 | 0.264375E+09 | 0.247584E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 116198.26 | 0.120905E+09 |
May | 0.303504E+09 | 0.271778E+09 | 0.255602E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 32389.26 | 0.114408E+09 |
June | 0.293842E+09 | 0.262277E+09 | 0.247231E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 485375.23 | 79381962.58 |
July | 0.303141E+09 | 0.273911E+09 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1289661.86 | 66425890.64 |
August | 0.303685E+09 | 0.270694E+09 | 0.255425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 362593.35 | 59068390.15 |
September | 0.293479E+09 | 0.264446E+09 | 0.247584E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 116496.43 | 77974417.66 |
October | 0.303322E+09 | 0.272827E+09 | 0.255778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118663E+09 |
November | 0.293661E+09 | 0.263326E+09 | 0.247408E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140155E+09 |
December | 0.303141E+09 | 0.273947E+09 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.167818E+09 |
Annual Sum or Average | 0.357224E+10 | 0.320756E+10 | 0.301074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2402714.39 | 0.142001E+10 |
Minimum of Months | 0.273974E+09 | 0.246421E+09 | 0.231020E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59068390.15 |
Maximum of Months | 0.303685E+09 | 0.273947E+09 | 0.255955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1289661.86 | 0.170218E+09 |
Report: SpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.396945E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.821956E+09 |
February | 0.415303E+11 | 0.358405E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.735878E+09 |
March | 0.461508E+11 | 0.398168E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.738992E+09 |
April | 0.445315E+11 | 0.383486E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 940762.33 | 0.575101E+09 |
May | 0.460320E+11 | 0.397633E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 344090.24 | 0.548834E+09 |
June | 0.446286E+11 | 0.385245E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 3737300.10 | 0.385345E+09 |
July | 0.459349E+11 | 0.395874E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 7800297.92 | 0.323488E+09 |
August | 0.461292E+11 | 0.398321E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2861154.30 | 0.286241E+09 |
September | 0.445099E+11 | 0.383639E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1076226.79 | 0.370557E+09 |
October | 0.459565E+11 | 0.396792E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.571206E+09 |
November | 0.444343E+11 | 0.384939E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.679827E+09 |
December | 0.459349E+11 | 0.395874E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.819195E+09 |
Annual Sum or Average | 0.541708E+12 | 0.467532E+11 | 0.175857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 16759831.69 | 0.685662E+10 |
Minimum of Months | 0.415303E+11 | 0.358405E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.286241E+09 |
Maximum of Months | 0.461508E+11 | 0.398321E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 7800297.92 | 0.821956E+09 |
Report: SpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.396945E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.824400E+09 |
February | 0.415303E+11 | 0.358405E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.738201E+09 |
March | 0.461508E+11 | 0.398168E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.741966E+09 |
April | 0.445315E+11 | 0.383486E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 897383.15 | 0.578467E+09 |
May | 0.460320E+11 | 0.397633E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 318541.67 | 0.552688E+09 |
June | 0.446286E+11 | 0.385245E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 3518301.27 | 0.389399E+09 |
July | 0.459349E+11 | 0.395874E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 7555072.15 | 0.327885E+09 |
August | 0.461292E+11 | 0.398321E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2745781.60 | 0.290192E+09 |
September | 0.445099E+11 | 0.383639E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 985140.85 | 0.373807E+09 |
October | 0.459565E+11 | 0.396792E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.574190E+09 |
November | 0.444343E+11 | 0.384939E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.682496E+09 |
December | 0.459349E+11 | 0.395874E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.821520E+09 |
Annual Sum or Average | 0.541708E+12 | 0.467532E+11 | 0.175857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 16020220.69 | 0.689521E+10 |
Minimum of Months | 0.415303E+11 | 0.358405E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.290192E+09 |
Maximum of Months | 0.461508E+11 | 0.398321E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 7555072.15 | 0.824400E+09 |
Report: SpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.408770E+10 | 0.105977E+10 | 0.338870E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.789925E+09 |
February | 0.369574E+10 | 0.956878E+09 | 0.306077E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.708662E+09 |
March | 0.410691E+10 | 0.106304E+10 | 0.338870E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.714948E+09 |
April | 0.396281E+10 | 0.102384E+10 | 0.327939E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.569854E+09 |
May | 0.409635E+10 | 0.106161E+10 | 0.338870E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.546846E+09 |
June | 0.397146E+10 | 0.102854E+10 | 0.327939E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 598721.31 | 0.392875E+09 |
July | 0.408770E+10 | 0.105691E+10 | 0.338870E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 3106966.11 | 0.338057E+09 |
August | 0.410499E+10 | 0.106345E+10 | 0.338870E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 446030.58 | 0.307612E+09 |
September | 0.396089E+10 | 0.102425E+10 | 0.327939E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.385601E+09 |
October | 0.408962E+10 | 0.105936E+10 | 0.338870E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.566164E+09 |
November | 0.395417E+10 | 0.102772E+10 | 0.327939E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.659919E+09 |
December | 0.408770E+10 | 0.105691E+10 | 0.338870E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.785099E+09 |
Annual Sum or Average | 0.482060E+11 | 0.124823E+11 | 0.398993E+12 | 0.359593E+12 | 0.00 | 0.00 | 0.00 | 4151718.01 | 0.676556E+10 |
Minimum of Months | 0.369574E+10 | 0.956878E+09 | 0.306077E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.307612E+09 |
Maximum of Months | 0.410691E+10 | 0.106345E+10 | 0.338870E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 3106966.11 | 0.789925E+09 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.407704E+10 | 0.140929E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.705274E+09 |
February | 0.368610E+10 | 0.127246E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.630911E+09 |
March | 0.409620E+10 | 0.141364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.628896E+09 |
April | 0.395248E+10 | 0.136151E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 742080.08 | 0.482823E+09 |
May | 0.408566E+10 | 0.141173E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 270118.95 | 0.456173E+09 |
June | 0.396110E+10 | 0.136775E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3304913.22 | 0.309642E+09 |
July | 0.407704E+10 | 0.140549E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7077592.08 | 0.254711E+09 |
August | 0.409429E+10 | 0.141418E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2409278.55 | 0.223306E+09 |
September | 0.395056E+10 | 0.136205E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 778091.36 | 0.301852E+09 |
October | 0.407896E+10 | 0.140875E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.480799E+09 |
November | 0.394385E+10 | 0.136667E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.579087E+09 |
December | 0.407704E+10 | 0.140549E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.703597E+09 |
Annual Sum or Average | 0.480803E+11 | 0.165990E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14582074.24 | 0.575707E+10 |
Minimum of Months | 0.368610E+10 | 0.127246E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.223306E+09 |
Maximum of Months | 0.409620E+10 | 0.141418E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7077592.08 | 0.705274E+09 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 11501.89 | 02-JAN-00:10 | 13517.00 | 02-JAN-20:10 | 10113.80 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 11501.89 | 01-FEB-00:10 | 13517.00 | 01-FEB-20:10 | 10113.80 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 11501.89 | 01-MAR-00:10 | 13517.00 | 01-MAR-20:10 | 10113.80 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 11501.89 | 01-APR-00:10 | 13517.00 | 03-APR-19:10 | 10113.80 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 11501.89 | 01-MAY-00:10 | 13517.00 | 01-MAY-19:10 | 10113.80 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 11501.89 | 01-JUN-00:10 | 13517.00 | 01-JUN-19:10 | 10113.80 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 11501.89 | 01-JUL-00:10 | 13517.00 | 03-JUL-19:10 | 10113.80 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 11501.89 | 01-AUG-00:10 | 13517.00 | 01-AUG-19:10 | 10113.80 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 11501.89 | 01-SEP-00:10 | 13517.00 | 01-SEP-19:10 | 10113.80 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 11501.89 | 01-OCT-23:10 | 13517.00 | 02-OCT-19:10 | 10113.80 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 11501.89 | 01-NOV-00:10 | 13517.00 | 01-NOV-19:10 | 10113.80 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 11501.89 | 01-DEC-00:10 | 13517.00 | 01-DEC-20:10 | 10113.80 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 11501.89 | 13517.00 | 10113.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 11501.89 | 13517.00 | 10113.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1169.53 | 02-JAN-00:10 | 687.30 | 02-JAN-20:10 | 685.60 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 347.94 | 11-JAN-23:53 |
February | 1169.53 | 01-FEB-00:10 | 687.30 | 01-FEB-20:10 | 685.60 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 316.24 | 17-FEB-07:00 |
March | 1169.53 | 01-MAR-00:10 | 687.30 | 01-MAR-20:10 | 685.60 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 277.95 | 08-MAR-07:00 |
April | 1169.53 | 01-APR-00:10 | 687.30 | 03-APR-19:10 | 685.60 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.89 | 30-APR-19:00 | 265.44 | 08-APR-06:00 |
May | 1169.53 | 01-MAY-00:10 | 687.30 | 01-MAY-19:10 | 685.60 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.78 | 22-MAY-15:10 | 240.83 | 06-MAY-05:00 |
June | 1169.53 | 01-JUN-00:10 | 687.30 | 01-JUN-19:10 | 685.60 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 68.85 | 13-JUN-17:00 | 186.91 | 07-JUN-05:00 |
July | 1169.53 | 01-JUL-00:10 | 687.30 | 03-JUL-19:10 | 685.60 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 102.02 | 22-JUL-18:00 | 173.76 | 31-JUL-05:00 |
August | 1169.53 | 01-AUG-00:10 | 687.30 | 01-AUG-19:10 | 685.60 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 69.07 | 14-AUG-17:17 | 160.58 | 24-AUG-06:00 |
September | 1169.53 | 01-SEP-00:10 | 687.30 | 01-SEP-19:10 | 685.60 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.27 | 13-SEP-17:00 | 200.65 | 21-SEP-06:00 |
October | 1169.53 | 01-OCT-23:10 | 687.30 | 02-OCT-19:10 | 685.60 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 239.25 | 15-OCT-04:00 |
November | 1169.53 | 01-NOV-00:10 | 687.30 | 01-NOV-19:10 | 685.60 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 295.56 | 29-NOV-02:00 |
December | 1169.53 | 01-DEC-00:10 | 687.30 | 01-DEC-20:10 | 685.60 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 306.62 | 29-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1169.53 | 687.30 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 160.58 | |||||
Maximum of Months | 1169.53 | 687.30 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 102.02 | 347.94 |
Report: PeakSpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1354.32 | 02-JAN-00:10 | 795.89 | 02-JAN-20:10 | 793.93 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 134.36 | 11-JAN-24:00 |
February | 1354.32 | 01-FEB-00:10 | 795.89 | 01-FEB-20:10 | 793.93 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 124.51 | 17-FEB-07:00 |
March | 1354.32 | 01-MAR-00:10 | 795.89 | 01-MAR-20:10 | 793.93 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 107.95 | 08-MAR-07:00 |
April | 1354.32 | 01-APR-00:10 | 795.89 | 03-APR-19:10 | 793.93 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.45 | 30-APR-18:20 | 102.45 | 08-APR-06:00 |
May | 1354.32 | 01-MAY-00:10 | 795.89 | 01-MAY-19:10 | 793.93 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.44 | 22-MAY-15:00 | 92.96 | 06-MAY-05:00 |
June | 1354.32 | 01-JUN-00:10 | 795.89 | 01-JUN-19:10 | 793.93 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.60 | 13-JUN-17:00 | 72.13 | 07-JUN-05:00 |
July | 1354.32 | 01-JUL-00:10 | 795.89 | 03-JUL-19:10 | 793.93 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.38 | 22-JUL-18:00 | 67.09 | 31-JUL-05:00 |
August | 1354.32 | 01-AUG-00:10 | 795.89 | 01-AUG-19:10 | 793.93 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.66 | 14-AUG-17:06 | 61.98 | 20-AUG-05:00 |
September | 1354.32 | 01-SEP-00:10 | 795.89 | 01-SEP-19:10 | 793.93 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.99 | 13-SEP-14:20 | 77.46 | 21-SEP-06:00 |
October | 1354.32 | 01-OCT-23:10 | 795.89 | 02-OCT-19:10 | 793.93 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 92.34 | 15-OCT-04:00 |
November | 1354.32 | 01-NOV-00:10 | 795.89 | 01-NOV-19:10 | 793.93 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 114.84 | 29-NOV-02:00 |
December | 1354.32 | 01-DEC-00:10 | 795.89 | 01-DEC-20:10 | 793.93 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 118.48 | 29-DEC-21:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1354.32 | 795.89 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.98 | |||||
Maximum of Months | 1354.32 | 795.89 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 39.38 | 134.36 |
Report: PeakSpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 286.42 | 02-JAN-00:10 | 1487.69 | 02-JAN-20:10 | 839.45 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 317.53 | 11-JAN-24:00 |
February | 286.42 | 01-FEB-00:10 | 1487.69 | 01-FEB-20:10 | 839.45 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 294.24 | 17-FEB-07:00 |
March | 286.42 | 01-MAR-00:10 | 1487.69 | 01-MAR-20:10 | 839.45 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 255.10 | 08-MAR-07:00 |
April | 286.42 | 01-APR-00:10 | 1487.69 | 03-APR-19:10 | 839.45 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.80 | 30-APR-18:50 | 242.12 | 08-APR-06:00 |
May | 286.42 | 01-MAY-00:10 | 1487.69 | 01-MAY-19:10 | 839.45 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.77 | 22-MAY-15:00 | 219.68 | 06-MAY-05:00 |
June | 286.42 | 01-JUN-00:10 | 1487.69 | 01-JUN-19:10 | 839.45 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 62.88 | 13-JUN-17:00 | 170.47 | 07-JUN-05:00 |
July | 286.42 | 01-JUL-00:10 | 1487.69 | 03-JUL-19:10 | 839.45 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 93.07 | 22-JUL-18:00 | 158.55 | 31-JUL-05:00 |
August | 286.42 | 01-AUG-00:10 | 1487.69 | 01-AUG-19:10 | 839.45 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 63.00 | 14-AUG-17:01 | 146.48 | 20-AUG-05:00 |
September | 286.42 | 01-SEP-00:10 | 1487.69 | 01-SEP-19:10 | 839.45 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.25 | 13-SEP-14:50 | 183.06 | 21-SEP-06:00 |
October | 286.42 | 01-OCT-23:10 | 1487.69 | 02-OCT-19:10 | 839.45 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 218.18 | 15-OCT-04:00 |
November | 286.42 | 01-NOV-00:10 | 1487.69 | 01-NOV-19:10 | 839.45 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 271.39 | 29-NOV-02:00 |
December | 286.42 | 01-DEC-00:10 | 1487.69 | 01-DEC-20:10 | 839.45 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 280.00 | 29-DEC-21:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 286.42 | 1487.69 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 146.48 | |||||
Maximum of Months | 286.42 | 1487.69 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 93.07 | 317.53 |
Report: PeakSpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 220.32 | 02-JAN-00:10 | 273.10 | 02-JAN-20:10 | 242.16 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 183.20 | 11-JAN-23:57 |
February | 220.32 | 01-FEB-00:10 | 273.10 | 01-FEB-20:10 | 242.16 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 169.77 | 17-FEB-07:00 |
March | 220.32 | 01-MAR-00:10 | 273.10 | 01-MAR-20:10 | 242.16 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 147.18 | 08-MAR-07:00 |
April | 220.32 | 01-APR-00:10 | 273.10 | 03-APR-19:10 | 242.16 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.35 | 30-APR-19:00 | 139.70 | 08-APR-06:00 |
May | 220.32 | 01-MAY-00:10 | 273.10 | 01-MAY-19:10 | 242.16 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.33 | 22-MAY-15:00 | 126.75 | 06-MAY-05:00 |
June | 220.32 | 01-JUN-00:10 | 273.10 | 01-JUN-19:10 | 242.16 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.27 | 13-JUN-17:00 | 98.36 | 07-JUN-05:00 |
July | 220.32 | 01-JUL-00:10 | 273.10 | 03-JUL-19:10 | 242.16 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 53.70 | 22-JUL-18:00 | 91.48 | 31-JUL-05:00 |
August | 220.32 | 01-AUG-00:10 | 273.10 | 01-AUG-19:10 | 242.16 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.35 | 14-AUG-17:00 | 84.51 | 20-AUG-05:00 |
September | 220.32 | 01-SEP-00:10 | 273.10 | 01-SEP-19:10 | 242.16 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.26 | 13-SEP-14:30 | 105.62 | 21-SEP-06:00 |
October | 220.32 | 01-OCT-23:10 | 273.10 | 02-OCT-19:10 | 242.16 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 125.89 | 15-OCT-04:00 |
November | 220.32 | 01-NOV-00:10 | 273.10 | 01-NOV-19:10 | 242.16 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 156.58 | 29-NOV-02:00 |
December | 220.32 | 01-DEC-00:10 | 273.10 | 01-DEC-20:10 | 242.16 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 161.55 | 29-DEC-21:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 220.32 | 273.10 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.51 | |||||
Maximum of Months | 220.32 | 273.10 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 53.70 | 183.20 |
Report: PeakSpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 907.20 | 02-JAN-00:10 | 337.37 | 02-JAN-20:10 | 4572.80 | 02-JAN-20:10 | 39726.58 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 460.82 | 10-JAN-22:00 |
February | 907.20 | 01-FEB-00:10 | 337.37 | 01-FEB-20:10 | 4572.80 | 01-FEB-20:10 | 39726.58 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 433.68 | 17-FEB-21:00 |
March | 907.20 | 01-MAR-00:10 | 337.37 | 01-MAR-20:10 | 4572.80 | 01-MAR-20:10 | 39726.58 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 369.96 | 14-MAR-21:00 |
April | 907.20 | 01-APR-00:10 | 337.37 | 03-APR-19:10 | 4572.80 | 03-APR-19:10 | 39726.58 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 44.60 | 30-APR-16:40 | 330.68 | 08-APR-06:00 |
May | 907.20 | 01-MAY-00:10 | 337.37 | 01-MAY-19:10 | 4572.80 | 01-MAY-19:10 | 39726.58 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 43.56 | 22-MAY-15:00 | 299.68 | 06-MAY-05:00 |
June | 907.20 | 01-JUN-00:10 | 337.37 | 01-JUN-19:10 | 4572.80 | 01-JUN-19:10 | 39726.58 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 85.74 | 13-JUN-17:00 | 263.07 | 07-JUN-21:00 |
July | 907.20 | 01-JUL-00:10 | 337.37 | 03-JUL-19:10 | 4572.80 | 03-JUL-19:10 | 39726.58 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 126.95 | 22-JUL-18:00 | 229.43 | 03-JUL-21:00 |
August | 907.20 | 01-AUG-00:10 | 337.37 | 01-AUG-19:10 | 4572.80 | 01-AUG-19:10 | 39726.58 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 86.02 | 14-AUG-17:25 | 200.09 | 24-AUG-06:00 |
September | 907.20 | 01-SEP-00:10 | 337.37 | 01-SEP-19:10 | 4572.80 | 01-SEP-19:10 | 39726.58 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 29.11 | 13-SEP-14:30 | 250.80 | 21-SEP-06:10 |
October | 907.20 | 01-OCT-23:10 | 337.37 | 02-OCT-19:10 | 4572.80 | 02-OCT-19:10 | 39726.58 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 297.64 | 15-OCT-04:00 |
November | 907.20 | 01-NOV-00:10 | 337.37 | 01-NOV-19:10 | 4572.80 | 01-NOV-19:10 | 39726.58 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 401.73 | 28-NOV-21:00 |
December | 907.20 | 01-DEC-00:10 | 337.37 | 01-DEC-20:10 | 4572.80 | 01-DEC-20:10 | 39726.58 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 430.12 | 29-DEC-21:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 907.20 | 337.37 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 200.09 | ||||||
Maximum of Months | 907.20 | 337.37 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 126.95 | 460.82 |
Report: PeakSpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 15368.40 | 02-JAN-00:10 | 2177.23 | 02-JAN-20:10 | 965.27 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 769.54 | 11-JAN-23:57 |
February | 15368.40 | 01-FEB-00:10 | 2177.23 | 01-FEB-20:10 | 965.27 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 713.09 | 17-FEB-07:00 |
March | 15368.40 | 01-MAR-00:10 | 2177.23 | 01-MAR-20:10 | 965.27 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 618.34 | 08-MAR-07:00 |
April | 15368.40 | 01-APR-00:10 | 2177.23 | 03-APR-19:10 | 965.27 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 77.06 | 30-APR-18:30 | 587.04 | 08-APR-06:00 |
May | 15368.40 | 01-MAY-00:10 | 2177.23 | 01-MAY-19:10 | 965.27 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 76.78 | 22-MAY-15:00 | 532.49 | 06-MAY-05:00 |
June | 15368.40 | 01-JUN-00:10 | 2177.23 | 01-JUN-19:10 | 965.27 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 152.21 | 13-JUN-17:00 | 413.11 | 07-JUN-05:00 |
July | 15368.40 | 01-JUL-00:10 | 2177.23 | 03-JUL-19:10 | 965.27 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 225.53 | 22-JUL-18:00 | 384.33 | 31-JUL-05:00 |
August | 15368.40 | 01-AUG-00:10 | 2177.23 | 01-AUG-19:10 | 965.27 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 152.70 | 14-AUG-17:20 | 355.20 | 20-AUG-05:00 |
September | 15368.40 | 01-SEP-00:10 | 2177.23 | 01-SEP-19:10 | 965.27 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.50 | 11-SEP-17:00 | 443.72 | 21-SEP-06:00 |
October | 15368.40 | 01-OCT-23:10 | 2177.23 | 02-OCT-19:10 | 965.27 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 528.83 | 15-OCT-04:00 |
November | 15368.40 | 01-NOV-00:10 | 2177.23 | 01-NOV-19:10 | 965.27 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 657.90 | 29-NOV-02:00 |
December | 15368.40 | 01-DEC-00:10 | 2177.23 | 01-DEC-20:10 | 965.27 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 678.52 | 29-DEC-21:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 15368.40 | 2177.23 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 355.20 | |||||
Maximum of Months | 15368.40 | 2177.23 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 225.53 | 769.54 |
Report: PeakSpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 45622.98 | 02-JAN-00:10 | 11849.32 | 02-JAN-20:10 | 10029.21 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2198.56 | 11-JAN-23:53 |
February | 45622.98 | 01-FEB-00:10 | 11849.32 | 01-FEB-20:10 | 10029.21 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 2037.20 | 17-FEB-07:00 |
March | 45622.98 | 01-MAR-00:10 | 11849.32 | 01-MAR-20:10 | 10029.21 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 1766.04 | 08-MAR-07:00 |
April | 45622.98 | 01-APR-00:10 | 11849.32 | 03-APR-19:10 | 10029.21 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 220.32 | 30-APR-19:00 | 1676.43 | 08-APR-05:50 |
May | 45622.98 | 01-MAY-00:10 | 11849.32 | 01-MAY-19:10 | 10029.21 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 219.76 | 22-MAY-15:00 | 1521.18 | 06-MAY-05:00 |
June | 45622.98 | 01-JUN-00:10 | 11849.32 | 01-JUN-19:10 | 10029.21 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 435.02 | 13-JUN-17:00 | 1180.42 | 07-JUN-05:00 |
July | 45622.98 | 01-JUL-00:10 | 11849.32 | 03-JUL-19:10 | 10029.21 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 644.26 | 22-JUL-18:00 | 1098.06 | 31-JUL-05:00 |
August | 45622.98 | 01-AUG-00:10 | 11849.32 | 01-AUG-19:10 | 10029.21 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 436.18 | 14-AUG-17:01 | 1014.29 | 24-AUG-06:00 |
September | 45622.98 | 01-SEP-00:10 | 11849.32 | 01-SEP-19:10 | 10029.21 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 147.12 | 13-SEP-15:00 | 1277.50 | 20-SEP-24:00 |
October | 45622.98 | 01-OCT-23:10 | 11849.32 | 02-OCT-19:10 | 10029.21 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1510.81 | 15-OCT-04:00 |
November | 45622.98 | 01-NOV-00:10 | 11849.32 | 01-NOV-19:10 | 10029.21 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1879.26 | 29-NOV-02:00 |
December | 45622.98 | 01-DEC-00:10 | 11849.32 | 01-DEC-20:10 | 10029.21 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 1941.16 | 29-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 45622.98 | 11849.32 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1014.29 | |||||
Maximum of Months | 45622.98 | 11849.32 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 644.26 | 2198.56 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 392.73 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 203.17 | 11-JAN-24:00 |
February | 180.00 | 01-FEB-00:10 | 392.73 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 188.35 | 17-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 392.73 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 163.43 | 08-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 392.73 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.19 | 30-APR-18:50 | 155.17 | 08-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 392.73 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.05 | 22-MAY-15:10 | 140.90 | 06-MAY-05:00 |
June | 180.00 | 01-JUN-00:10 | 392.73 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.98 | 13-JUN-17:00 | 109.57 | 07-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 392.73 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 57.12 | 22-JUL-18:10 | 101.98 | 31-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 392.73 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.06 | 14-AUG-17:00 | 94.29 | 20-AUG-05:00 |
September | 180.00 | 01-SEP-00:10 | 392.73 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.47 | 13-SEP-15:10 | 117.58 | 21-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 392.73 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 139.94 | 15-OCT-04:00 |
November | 180.00 | 01-NOV-00:10 | 392.73 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 173.82 | 29-NOV-02:00 |
December | 180.00 | 01-DEC-00:10 | 392.73 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 179.28 | 29-DEC-21:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 392.73 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.29 | |||||
Maximum of Months | 180.00 | 392.73 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 57.12 | 203.17 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 392.68 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 203.16 | 11-JAN-24:00 |
February | 180.00 | 01-FEB-00:10 | 392.68 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 188.34 | 17-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 392.68 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 163.42 | 08-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 392.68 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.19 | 30-APR-19:00 | 155.16 | 08-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 392.68 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.06 | 22-MAY-15:10 | 140.89 | 06-MAY-05:00 |
June | 180.00 | 01-JUN-00:10 | 392.68 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.98 | 13-JUN-17:00 | 109.56 | 07-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 392.68 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 55.91 | 22-JUL-18:10 | 101.97 | 31-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 392.68 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.06 | 14-AUG-17:00 | 94.28 | 20-AUG-05:00 |
September | 180.00 | 01-SEP-00:10 | 392.68 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.47 | 11-SEP-17:00 | 117.57 | 21-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 392.68 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 139.93 | 15-OCT-04:00 |
November | 180.00 | 01-NOV-00:10 | 392.68 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 173.81 | 29-NOV-02:00 |
December | 180.00 | 01-DEC-00:10 | 392.68 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 179.27 | 29-DEC-21:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 392.68 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.28 | |||||
Maximum of Months | 180.00 | 392.68 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 55.91 | 203.16 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 01-JAN-00:10 | 246.81 | 01-JAN-19:10 | 232.19 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 58.72 | 11-JAN-23:53 |
February | 0.00 | 01-FEB-00:10 | 246.81 | 01-FEB-20:10 | 232.19 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 54.79 | 17-FEB-21:00 |
March | 0.00 | 01-MAR-00:10 | 246.81 | 01-MAR-20:10 | 232.19 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 45.90 | 14-MAR-21:00 |
April | 0.00 | 01-APR-00:10 | 246.81 | 01-APR-18:10 | 232.19 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 30-APR-19:00 | 45.33 | 08-APR-06:00 |
May | 0.00 | 01-MAY-00:10 | 246.81 | 01-MAY-19:10 | 232.19 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 22-MAY-15:00 | 41.37 | 07-MAY-05:00 |
June | 0.00 | 01-JUN-00:10 | 246.81 | 01-JUN-19:10 | 232.19 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.74 | 13-JUN-17:00 | 33.36 | 01-JUN-04:30 |
July | 0.00 | 01-JUL-00:10 | 246.81 | 01-JUL-18:10 | 232.19 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.16 | 22-JUL-18:00 | 31.70 | 31-JUL-05:00 |
August | 0.00 | 01-AUG-00:10 | 246.81 | 01-AUG-19:10 | 232.19 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.75 | 14-AUG-17:00 | 30.67 | 24-AUG-06:00 |
September | 0.00 | 01-SEP-00:10 | 246.81 | 01-SEP-19:10 | 232.19 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 37.15 | 20-SEP-24:00 |
October | 0.00 | 01-OCT-00:10 | 246.81 | 01-OCT-18:10 | 232.19 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 42.05 | 07-OCT-04:00 |
November | 0.00 | 01-NOV-00:10 | 246.81 | 01-NOV-19:10 | 232.19 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 49.53 | 28-NOV-21:00 |
December | 0.00 | 01-DEC-00:10 | 246.81 | 01-DEC-20:10 | 232.19 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 50.03 | 26-DEC-20:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 0.00 | 246.81 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.67 | |||||
Maximum of Months | 0.00 | 246.81 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 12.16 | 58.72 |
Report: PeakSpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 246.88 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 56.70 | 11-JAN-23:57 |
February | 180.00 | 01-FEB-00:10 | 246.88 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 52.57 | 17-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 246.88 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 45.61 | 08-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 246.88 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.36 | 30-APR-19:00 | 43.31 | 08-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 246.88 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.04 | 22-MAY-15:10 | 39.32 | 06-MAY-05:00 |
June | 180.00 | 01-JUN-00:10 | 246.88 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.88 | 13-JUN-17:00 | 30.58 | 07-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 246.88 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.95 | 22-JUL-18:10 | 28.46 | 31-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 246.88 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.90 | 14-AUG-17:00 | 26.31 | 20-AUG-05:00 |
September | 180.00 | 01-SEP-00:10 | 246.88 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.48 | 11-SEP-17:00 | 32.82 | 21-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 246.88 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 39.06 | 15-OCT-04:00 |
November | 180.00 | 01-NOV-00:10 | 246.88 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 48.51 | 29-NOV-02:00 |
December | 180.00 | 01-DEC-00:10 | 246.88 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 50.04 | 29-DEC-21:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 246.88 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.31 | |||||
Maximum of Months | 180.00 | 246.88 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 15.95 | 56.70 |
Report: PeakSpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 392.73 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 203.17 | 11-JAN-24:00 |
February | 180.00 | 01-FEB-00:10 | 392.73 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 188.36 | 17-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 392.73 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 163.44 | 08-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 392.73 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.20 | 30-APR-19:00 | 155.17 | 08-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 392.73 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.06 | 22-MAY-15:10 | 140.90 | 06-MAY-05:00 |
June | 180.00 | 01-JUN-00:10 | 392.73 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.98 | 13-JUN-17:00 | 109.57 | 07-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 392.73 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 57.14 | 22-JUL-18:10 | 101.98 | 31-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 392.73 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.06 | 14-AUG-17:00 | 94.29 | 20-AUG-05:00 |
September | 180.00 | 01-SEP-00:10 | 392.73 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.47 | 11-SEP-17:00 | 117.58 | 21-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 392.73 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 139.94 | 15-OCT-04:00 |
November | 180.00 | 01-NOV-00:10 | 392.73 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 173.82 | 29-NOV-02:00 |
December | 180.00 | 01-DEC-00:10 | 392.73 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 179.28 | 29-DEC-21:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 392.73 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.29 | |||||
Maximum of Months | 180.00 | 392.73 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 57.14 | 203.17 |
Report: PeakSpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 392.68 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 203.16 | 11-JAN-24:00 |
February | 180.00 | 01-FEB-00:10 | 392.68 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 188.34 | 17-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 392.68 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 163.42 | 08-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 392.68 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.20 | 30-APR-19:00 | 155.16 | 08-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 392.68 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.06 | 22-MAY-15:10 | 140.89 | 06-MAY-05:00 |
June | 180.00 | 01-JUN-00:10 | 392.68 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.97 | 13-JUN-17:00 | 109.56 | 07-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 392.68 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 57.13 | 22-JUL-18:10 | 101.97 | 31-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 392.68 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.06 | 14-AUG-17:00 | 94.28 | 20-AUG-05:00 |
September | 180.00 | 01-SEP-00:10 | 392.68 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.47 | 11-SEP-17:00 | 117.57 | 21-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 392.68 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 139.93 | 15-OCT-04:00 |
November | 180.00 | 01-NOV-00:10 | 392.68 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 173.81 | 29-NOV-02:00 |
December | 180.00 | 01-DEC-00:10 | 392.68 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 179.27 | 29-DEC-21:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 392.68 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.28 | |||||
Maximum of Months | 180.00 | 392.68 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 57.13 | 203.16 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2263.36 | 02-JAN-00:10 | 1282.60 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 244.68 | 11-JAN-24:00 |
February | 2263.36 | 01-FEB-00:10 | 1282.60 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 226.76 | 17-FEB-07:00 |
March | 2263.36 | 01-MAR-00:10 | 1282.60 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 196.65 | 08-MAR-07:00 |
April | 2263.36 | 01-APR-00:10 | 1282.60 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.84 | 30-APR-17:20 | 186.65 | 08-APR-06:00 |
May | 2263.36 | 01-MAY-00:10 | 1282.60 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.98 | 22-MAY-15:00 | 169.41 | 06-MAY-05:00 |
June | 2263.36 | 01-JUN-00:10 | 1282.60 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.08 | 13-JUN-17:00 | 131.52 | 07-JUN-05:00 |
July | 2263.36 | 01-JUL-00:10 | 1282.60 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.63 | 22-JUL-18:00 | 122.37 | 31-JUL-05:00 |
August | 2263.36 | 01-AUG-00:10 | 1282.60 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.42 | 14-AUG-17:35 | 113.07 | 20-AUG-05:00 |
September | 2263.36 | 01-SEP-00:10 | 1282.60 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.97 | 11-SEP-17:00 | 141.21 | 21-SEP-06:00 |
October | 2263.36 | 01-OCT-23:10 | 1282.60 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 168.25 | 15-OCT-04:00 |
November | 2263.36 | 01-NOV-00:10 | 1282.60 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 209.20 | 29-NOV-02:00 |
December | 2263.36 | 01-DEC-00:10 | 1282.60 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 215.80 | 29-DEC-21:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 2263.36 | 1282.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 113.07 | ||||
Maximum of Months | 2263.36 | 1282.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.63 | 244.68 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 392.73 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 203.66 | 11-JAN-24:00 |
February | 180.00 | 01-FEB-00:10 | 392.73 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 188.84 | 17-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 392.73 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 163.91 | 08-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 392.73 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.79 | 30-APR-19:00 | 155.64 | 08-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 392.73 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.60 | 22-MAY-15:10 | 141.37 | 06-MAY-05:00 |
June | 180.00 | 01-JUN-00:10 | 392.73 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.58 | 13-JUN-17:00 | 110.02 | 07-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 392.73 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 55.70 | 22-JUL-18:10 | 102.43 | 31-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 392.73 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.67 | 14-AUG-17:00 | 94.73 | 20-AUG-05:00 |
September | 180.00 | 01-SEP-00:10 | 392.73 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.07 | 11-SEP-17:00 | 118.04 | 21-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 392.73 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 140.41 | 15-OCT-04:00 |
November | 180.00 | 01-NOV-00:10 | 392.73 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 174.31 | 29-NOV-02:00 |
December | 180.00 | 01-DEC-00:10 | 392.73 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 179.76 | 29-DEC-21:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 392.73 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.73 | |||||
Maximum of Months | 180.00 | 392.73 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 55.70 | 203.66 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 392.68 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 203.65 | 11-JAN-24:00 |
February | 180.00 | 01-FEB-00:10 | 392.68 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 188.83 | 17-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 392.68 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 163.89 | 08-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 392.68 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.76 | 30-APR-19:00 | 155.63 | 08-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 392.68 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.65 | 22-MAY-15:10 | 141.36 | 06-MAY-05:00 |
June | 180.00 | 01-JUN-00:10 | 392.68 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.58 | 13-JUN-17:00 | 110.01 | 07-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 392.68 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 54.44 | 22-JUL-18:10 | 102.42 | 31-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 392.68 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.67 | 14-AUG-17:00 | 94.73 | 20-AUG-05:00 |
September | 180.00 | 01-SEP-00:10 | 392.68 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.07 | 13-SEP-15:10 | 118.03 | 21-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 392.68 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 140.40 | 15-OCT-04:00 |
November | 180.00 | 01-NOV-00:10 | 392.68 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 174.29 | 29-NOV-02:00 |
December | 180.00 | 01-DEC-00:10 | 392.68 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 179.75 | 29-DEC-21:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 392.68 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.73 | |||||
Maximum of Months | 180.00 | 392.68 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 54.44 | 203.65 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 246.88 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 104.20 | 11-JAN-24:00 |
February | 180.00 | 01-FEB-00:10 | 246.88 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 96.62 | 17-FEB-07:00 |
March | 180.00 | 01-MAR-00:10 | 246.88 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 83.86 | 08-MAR-07:00 |
April | 180.00 | 01-APR-00:10 | 246.88 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.62 | 30-APR-19:00 | 79.63 | 08-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 246.88 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.04 | 22-MAY-15:10 | 72.33 | 06-MAY-05:00 |
June | 180.00 | 01-JUN-00:10 | 246.88 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.74 | 13-JUN-17:00 | 56.29 | 07-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 246.88 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.04 | 22-JUL-18:10 | 52.41 | 31-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 246.88 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.79 | 14-AUG-17:00 | 48.47 | 20-AUG-05:00 |
September | 180.00 | 01-SEP-00:10 | 246.88 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 11-SEP-17:00 | 60.39 | 21-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 246.88 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 71.84 | 15-OCT-04:00 |
November | 180.00 | 01-NOV-00:10 | 246.88 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 89.18 | 29-NOV-02:00 |
December | 180.00 | 01-DEC-00:10 | 246.88 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 91.97 | 29-DEC-21:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 180.00 | 246.88 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.47 | |||||
Maximum of Months | 180.00 | 246.88 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 29.04 | 104.20 |
Report: PeakSpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 3823.39 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 514.47 | 11-JAN-23:53 |
February | 26988.77 | 01-FEB-00:10 | 3823.39 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 464.96 | 17-FEB-07:00 |
March | 26988.77 | 01-MAR-00:10 | 3823.39 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 407.38 | 08-MAR-07:00 |
April | 26988.77 | 01-APR-00:10 | 3823.39 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 47.71 | 30-APR-17:40 | 390.08 | 08-APR-05:00 |
May | 26988.77 | 01-MAY-00:10 | 3823.39 | 01-MAY-19:10 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 41.60 | 22-MAY-15:00 | 357.20 | 06-MAY-05:00 |
June | 26988.77 | 01-JUN-00:10 | 3823.39 | 01-JUN-19:10 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 88.72 | 13-JUN-17:00 | 284.85 | 08-JUN-05:00 |
July | 26988.77 | 01-JUL-00:10 | 3823.39 | 03-JUL-19:10 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 131.16 | 22-JUL-18:00 | 266.54 | 05-JUL-05:00 |
August | 26988.77 | 01-AUG-00:10 | 3823.39 | 01-AUG-19:10 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 92.21 | 14-AUG-18:00 | 247.07 | 23-AUG-04:00 |
September | 26988.77 | 01-SEP-00:10 | 3823.39 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.22 | 13-SEP-14:00 | 303.56 | 20-SEP-24:00 |
October | 26988.77 | 01-OCT-23:10 | 3823.39 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 353.08 | 07-OCT-04:00 |
November | 26988.77 | 01-NOV-00:10 | 3823.39 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 433.83 | 29-NOV-02:00 |
December | 26988.77 | 01-DEC-00:10 | 3823.39 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 458.72 | 29-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26988.77 | 3823.39 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 247.07 | |||||
Maximum of Months | 26988.77 | 3823.39 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 131.16 | 514.47 |
Report: PeakSpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 3823.39 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 516.08 | 11-JAN-23:53 |
February | 26988.77 | 01-FEB-00:10 | 3823.39 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 466.21 | 17-FEB-07:00 |
March | 26988.77 | 01-MAR-00:10 | 3823.39 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 408.65 | 08-MAR-07:00 |
April | 26988.77 | 01-APR-00:10 | 3823.39 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 47.44 | 30-APR-16:00 | 390.81 | 08-APR-05:00 |
May | 26988.77 | 01-MAY-00:10 | 3823.39 | 01-MAY-19:10 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.69 | 22-MAY-15:00 | 357.94 | 06-MAY-05:00 |
June | 26988.77 | 01-JUN-00:10 | 3823.39 | 01-JUN-19:10 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 86.71 | 13-JUN-17:00 | 285.68 | 08-JUN-05:00 |
July | 26988.77 | 01-JUL-00:10 | 3823.39 | 03-JUL-19:10 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 129.25 | 22-JUL-18:00 | 267.37 | 05-JUL-05:00 |
August | 26988.77 | 01-AUG-00:10 | 3823.39 | 01-AUG-19:10 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 90.14 | 14-AUG-18:00 | 247.89 | 24-AUG-06:00 |
September | 26988.77 | 01-SEP-00:10 | 3823.39 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.45 | 13-SEP-14:00 | 305.11 | 20-SEP-24:00 |
October | 26988.77 | 01-OCT-23:10 | 3823.39 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 353.74 | 07-OCT-04:00 |
November | 26988.77 | 01-NOV-00:10 | 3823.39 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 434.88 | 29-NOV-02:00 |
December | 26988.77 | 01-DEC-00:10 | 3823.39 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 460.56 | 29-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 26988.77 | 3823.39 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 247.89 | |||||
Maximum of Months | 26988.77 | 3823.39 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 129.25 | 516.08 |
Report: PeakSpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2401.70 | 02-JAN-00:10 | 1020.78 | 02-JAN-20:10 | 15112.11 | 01-JAN-07:10 | 22492.83 | 01-JAN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 473.57 | 10-JAN-08:00 |
February | 2401.70 | 01-FEB-00:10 | 1020.78 | 01-FEB-20:10 | 15112.11 | 01-FEB-07:10 | 22492.83 | 01-FEB-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 433.63 | 17-FEB-07:20 |
March | 2401.70 | 01-MAR-00:10 | 1020.78 | 01-MAR-20:10 | 15112.11 | 01-MAR-07:10 | 22492.83 | 01-MAR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 369.82 | 02-MAR-21:00 |
April | 2401.70 | 01-APR-00:10 | 1020.78 | 03-APR-19:10 | 15112.11 | 01-APR-06:10 | 22492.83 | 01-APR-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 350.22 | 08-APR-06:00 |
May | 2401.70 | 01-MAY-00:10 | 1020.78 | 01-MAY-19:10 | 15112.11 | 01-MAY-06:10 | 22492.83 | 01-MAY-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 311.93 | 06-MAY-05:20 |
June | 2401.70 | 01-JUN-00:10 | 1020.78 | 01-JUN-19:10 | 15112.11 | 01-JUN-06:10 | 22492.83 | 01-JUN-15:09 | 0.00 | 0.00 | 0.00 | 42.39 | 13-JUN-17:00 | 264.49 | 07-JUN-21:00 |
July | 2401.70 | 01-JUL-00:10 | 1020.78 | 03-JUL-19:10 | 15112.11 | 01-JUL-06:10 | 22492.83 | 01-JUL-15:09 | 0.00 | 0.00 | 0.00 | 84.80 | 22-JUL-18:00 | 234.93 | 04-JUL-21:00 |
August | 2401.70 | 01-AUG-00:10 | 1020.78 | 01-AUG-19:10 | 15112.11 | 01-AUG-06:10 | 22492.83 | 01-AUG-15:09 | 0.00 | 0.00 | 0.00 | 42.46 | 14-AUG-18:00 | 225.60 | 24-AUG-06:00 |
September | 2401.70 | 01-SEP-00:10 | 1020.78 | 01-SEP-19:10 | 15112.11 | 01-SEP-06:10 | 22492.83 | 01-SEP-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 271.50 | 21-SEP-06:00 |
October | 2401.70 | 01-OCT-23:10 | 1020.78 | 02-OCT-19:10 | 15112.11 | 01-OCT-06:10 | 22492.83 | 01-OCT-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 329.10 | 06-OCT-07:00 |
November | 2401.70 | 01-NOV-00:10 | 1020.78 | 01-NOV-19:10 | 15112.11 | 01-NOV-06:10 | 22492.83 | 01-NOV-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 397.63 | 28-NOV-21:00 |
December | 2401.70 | 01-DEC-00:10 | 1020.78 | 01-DEC-20:10 | 15112.11 | 01-DEC-07:10 | 22492.83 | 01-DEC-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 424.80 | 29-DEC-21:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 2401.70 | 1020.78 | 15112.11 | 22492.83 | 0.00 | 0.00 | 0.00 | 0.00 | 225.60 | ||||||
Maximum of Months | 2401.70 | 1020.78 | 15112.11 | 22492.83 | 0.00 | 0.00 | 0.00 | 84.80 | 473.57 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2395.44 | 02-JAN-00:10 | 1357.44 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 433.97 | 11-JAN-23:57 |
February | 2395.44 | 01-FEB-00:10 | 1357.44 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 402.30 | 17-FEB-07:00 |
March | 2395.44 | 01-MAR-00:10 | 1357.44 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 348.93 | 08-MAR-07:00 |
April | 2395.44 | 01-APR-00:10 | 1357.44 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.84 | 30-APR-18:50 | 331.26 | 08-APR-06:00 |
May | 2395.44 | 01-MAY-00:10 | 1357.44 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.88 | 22-MAY-15:00 | 300.77 | 06-MAY-05:00 |
June | 2395.44 | 01-JUN-00:10 | 1357.44 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.56 | 13-JUN-17:00 | 233.67 | 07-JUN-05:00 |
July | 2395.44 | 01-JUL-00:10 | 1357.44 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 121.30 | 22-JUL-18:00 | 217.44 | 31-JUL-05:00 |
August | 2395.44 | 01-AUG-00:10 | 1357.44 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.30 | 14-AUG-18:00 | 200.99 | 20-AUG-05:00 |
September | 2395.44 | 01-SEP-00:10 | 1357.44 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.08 | 11-SEP-17:00 | 250.84 | 21-SEP-06:00 |
October | 2395.44 | 01-OCT-23:10 | 1357.44 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 298.66 | 15-OCT-04:00 |
November | 2395.44 | 01-NOV-00:10 | 1357.44 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 371.14 | 29-NOV-02:00 |
December | 2395.44 | 01-DEC-00:10 | 1357.44 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 382.86 | 29-DEC-21:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 2395.44 | 1357.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 200.99 | ||||
Maximum of Months | 2395.44 | 1357.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 121.30 | 433.97 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 18958.62 | 20-JAN-21:00 | 8945.92 | 13517.00 | 10113.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 18799.56 | 22-FEB-21:00 | 8945.92 | 13517.00 | 10113.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 18741.74 | 31-MAR-20:00 | 8945.92 | 13517.00 | 10113.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 19630.53 | 27-APR-19:10 | 17891.83 | 27034.00 | 20227.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 20231.62 | 30-MAY-18:06 | 62621.41 | 84105.23 | 67070.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 20588.93 | 21-JUN-19:10 | 17891.83 | 27034.00 | 20227.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 20690.53 | 10-JUL-19:10 | 17891.83 | 27034.00 | 20227.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 20663.04 | 17-AUG-18:40 | 8945.92 | 12015.03 | 9581.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 21180.16 | 13-SEP-18:02 | 53675.50 | 72090.20 | 57488.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 19811.37 | 04-OCT-18:10 | 53675.50 | 72090.20 | 57488.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 19407.70 | 10-NOV-21:00 | 8945.92 | 13517.00 | 10113.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 19119.52 | 20-DEC-21:00 | 8945.92 | 13517.00 | 10113.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 18741.74 | 8945.92 | 12015.03 | 9581.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21180.16 | 62621.41 | 84105.23 | 67070.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3751.23 | 15-JAN-11:40 | 389.84 | 229.10 | 288.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 154.48 |
February | 3947.29 | 04-FEB-11:40 | 389.84 | 190.92 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 167.10 |
March | 2811.21 | 25-MAR-11:30 | 389.84 | 190.92 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.85 |
April | 4043.60 | 30-APR-12:00 | 389.84 | 229.10 | 288.68 | 0.00 | 0.00 | 0.00 | 0.00 | 4.39 | 0.00 |
May | 3691.53 | 23-MAY-12:00 | 259.90 | 190.92 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.58 |
June | 3719.81 | 13-JUN-12:00 | 259.90 | 190.92 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 23.26 | 0.00 |
July | 3959.08 | 22-JUL-12:00 | 389.84 | 190.92 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 67.25 | 0.00 |
August | 4040.09 | 28-AUG-15:15 | 1299.48 | 381.83 | 505.18 | 0.00 | 0.00 | 0.00 | 0.00 | 27.81 | 0.00 |
September | 4499.17 | 12-SEP-10:35 | 519.79 | 381.83 | 505.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.95 |
October | 4323.16 | 04-OCT-10:35 | 519.79 | 381.83 | 505.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.36 |
November | 3583.44 | 11-NOV-11:40 | 389.84 | 229.10 | 288.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 148.54 |
December | 3280.02 | 18-DEC-13:30 | 259.90 | 190.92 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 164.79 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2811.21 | 259.90 | 190.92 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4499.17 | 1299.48 | 381.83 | 505.18 | 0.00 | 0.00 | 0.00 | 0.00 | 67.25 | 167.10 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1715.87 | 23-JAN-21:00 | 1053.36 | 795.89 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.49 |
February | 1725.63 | 27-FEB-21:00 | 1053.36 | 795.89 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.48 |
March | 1749.82 | 20-MAR-20:00 | 1053.36 | 795.89 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.59 |
April | 2001.47 | 27-APR-18:02 | 6320.16 | 4244.75 | 4512.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.43 |
May | 2089.25 | 22-MAY-18:03 | 6320.16 | 4244.75 | 4512.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.13 |
June | 2147.71 | 12-JUN-18:02 | 6320.16 | 4244.75 | 4512.87 | 0.00 | 0.00 | 0.00 | 0.00 | 20.85 | 0.00 |
July | 2163.16 | 22-JUL-18:07 | 5417.28 | 3714.16 | 4011.44 | 0.00 | 0.00 | 0.00 | 0.00 | 38.67 | 0.00 |
August | 2128.96 | 14-AUG-18:10 | 6320.16 | 4244.75 | 4512.87 | 0.00 | 0.00 | 0.00 | 0.00 | 24.31 | 0.00 |
September | 2055.88 | 11-SEP-18:10 | 6320.16 | 4244.75 | 4512.87 | 0.00 | 0.00 | 0.00 | 0.00 | 2.12 | 0.00 |
October | 1830.92 | 03-OCT-20:00 | 1053.36 | 795.89 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.61 |
November | 1728.11 | 15-NOV-21:00 | 1053.36 | 795.89 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.05 |
December | 1630.24 | 21-DEC-22:00 | 1203.84 | 707.46 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.02 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1630.24 | 1053.36 | 707.46 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2163.16 | 6320.16 | 4244.75 | 4512.87 | 0.00 | 0.00 | 0.00 | 0.00 | 38.67 | 88.02 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1393.05 | 18-JAN-21:00 | 222.77 | 1487.69 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 146.45 |
February | 1344.42 | 22-FEB-21:00 | 222.77 | 1487.69 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 179.81 |
March | 1483.23 | 20-MAR-20:00 | 222.77 | 1487.69 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 158.70 |
April | 1787.28 | 30-APR-19:10 | 381.89 | 2644.77 | 1590.53 | 0.00 | 0.00 | 0.00 | 0.00 | 19.29 | 0.00 |
May | 1849.85 | 22-MAY-19:00 | 222.77 | 1322.39 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.59 |
June | 1921.57 | 12-JUN-18:40 | 222.77 | 1322.39 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 38.83 | 0.00 |
July | 1995.46 | 22-JUL-18:20 | 572.83 | 3471.27 | 2120.71 | 0.00 | 0.00 | 0.00 | 0.00 | 89.61 | 0.00 |
August | 1913.65 | 14-AUG-18:30 | 222.77 | 1322.39 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 46.96 | 0.00 |
September | 1799.39 | 11-SEP-18:50 | 222.77 | 1322.39 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.18 |
October | 1625.67 | 10-OCT-20:00 | 222.77 | 1487.69 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 121.87 |
November | 1480.96 | 08-NOV-21:00 | 222.77 | 1487.69 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 110.78 |
December | 1267.13 | 05-DEC-21:00 | 222.77 | 1487.69 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 153.74 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1267.13 | 222.77 | 1322.39 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1995.46 | 572.83 | 3471.27 | 2120.71 | 0.00 | 0.00 | 0.00 | 0.00 | 89.61 | 179.81 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 366.86 | 18-JAN-22:00 | 195.84 | 242.76 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.51 |
February | 331.91 | 07-FEB-22:00 | 195.84 | 242.76 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.33 |
March | 398.04 | 20-MAR-20:10 | 195.84 | 242.76 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.87 |
April | 712.24 | 30-APR-19:05 | 293.76 | 485.51 | 458.82 | 0.00 | 0.00 | 0.00 | 0.00 | 11.25 | 0.00 |
May | 731.11 | 22-MAY-19:40 | 171.36 | 273.10 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.83 |
June | 860.91 | 13-JUN-19:05 | 342.72 | 546.20 | 484.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.69 |
July | 902.38 | 22-JUL-18:25 | 293.76 | 424.82 | 407.84 | 0.00 | 0.00 | 0.00 | 0.00 | 50.80 | 0.00 |
August | 787.07 | 14-AUG-20:40 | 195.84 | 242.76 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.26 |
September | 712.15 | 12-SEP-21:00 | 195.84 | 242.76 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.91 |
October | 483.63 | 10-OCT-20:50 | 195.84 | 242.76 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.92 |
November | 430.97 | 08-NOV-22:00 | 195.84 | 242.76 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.91 |
December | 275.45 | 05-DEC-21:00 | 171.36 | 273.10 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.70 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 275.45 | 171.36 | 242.76 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 902.38 | 342.72 | 546.20 | 484.31 | 0.00 | 0.00 | 0.00 | 0.00 | 50.80 | 93.87 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 35664.57 | 23-JAN-21:00 | 705.60 | 337.37 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 227.63 |
February | 35682.37 | 07-FEB-21:00 | 705.60 | 337.37 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 246.20 |
March | 35794.37 | 31-MAR-20:00 | 705.60 | 337.37 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 277.40 |
April | 36617.29 | 28-APR-20:00 | 705.60 | 337.37 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 164.84 |
May | 36735.67 | 22-MAY-20:00 | 705.60 | 337.37 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 100.88 |
June | 36973.20 | 12-JUN-20:00 | 705.60 | 337.37 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 24.28 |
July | 36964.54 | 21-JUL-20:00 | 705.60 | 337.37 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 43.55 |
August | 36889.43 | 14-AUG-20:00 | 705.60 | 337.37 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 45.43 |
September | 36676.41 | 12-SEP-20:00 | 705.60 | 337.37 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 134.33 |
October | 36168.53 | 06-OCT-20:00 | 705.60 | 337.37 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 244.63 |
November | 35766.00 | 08-NOV-21:00 | 705.60 | 337.37 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 196.30 |
December | 35522.20 | 20-DEC-21:00 | 705.60 | 337.37 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 260.96 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 35522.20 | 705.60 | 337.37 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 24.28 | |
Maximum of Months | 36973.20 | 705.60 | 337.37 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 277.40 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 14641.12 | 07-JAN-11:35 | 10245.60 | 1209.57 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 391.45 |
February | 15281.79 | 04-FEB-11:40 | 5122.80 | 604.78 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 367.16 |
March | 11590.81 | 25-MAR-11:30 | 5122.80 | 604.78 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 247.10 |
April | 15241.32 | 28-APR-15:13 | 25614.00 | 1814.35 | 1066.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.74 |
May | 14076.33 | 22-MAY-15:03 | 51228.00 | 3628.71 | 2133.76 | 0.00 | 0.00 | 0.00 | 0.00 | 72.66 | 0.00 |
June | 13984.59 | 13-JUN-15:02 | 51228.00 | 3628.71 | 2133.76 | 0.00 | 0.00 | 0.00 | 0.00 | 129.50 | 0.00 |
July | 14800.29 | 21-JUL-15:13 | 25614.00 | 1814.35 | 1066.88 | 0.00 | 0.00 | 0.00 | 0.00 | 160.96 | 0.00 |
August | 15556.68 | 28-AUG-15:15 | 17076.00 | 1209.57 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 65.75 | 0.00 |
September | 16211.77 | 23-SEP-10:35 | 10245.60 | 1209.57 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.61 |
October | 15990.71 | 07-OCT-10:35 | 10245.60 | 1209.57 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 169.99 |
November | 13807.20 | 11-NOV-11:40 | 5122.80 | 725.74 | 406.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 329.30 |
December | 12611.35 | 18-DEC-13:30 | 3415.20 | 604.78 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 360.39 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 11590.81 | 3415.20 | 604.78 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16211.77 | 51228.00 | 3628.71 | 2133.76 | 0.00 | 0.00 | 0.00 | 0.00 | 160.96 | 391.45 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 36892.47 | 23-JAN-22:00 | 40553.76 | 10532.73 | 9501.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1024.10 |
February | 37124.24 | 27-FEB-21:00 | 35484.54 | 11849.32 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1164.36 |
March | 37567.84 | 20-MAR-20:00 | 35484.54 | 11849.32 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1099.46 |
April | 41752.33 | 27-APR-18:30 | 35484.54 | 10532.73 | 9501.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 261.22 |
May | 43368.59 | 22-MAY-18:40 | 35484.54 | 10532.73 | 9501.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 149.54 |
June | 44639.07 | 12-JUN-18:40 | 35484.54 | 10532.73 | 9501.36 | 0.00 | 0.00 | 0.00 | 0.00 | 268.79 | 0.00 |
July | 44154.37 | 10-JUL-18:30 | 35484.54 | 10532.73 | 9501.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.83 |
August | 44790.30 | 14-AUG-18:20 | 70969.08 | 21065.45 | 19002.71 | 0.00 | 0.00 | 0.00 | 0.00 | 362.23 | 0.00 |
September | 43478.52 | 11-SEP-18:02 | 212907.24 | 63196.36 | 57008.13 | 0.00 | 0.00 | 0.00 | 0.00 | 36.74 | 0.00 |
October | 39148.77 | 03-OCT-20:00 | 35484.54 | 11849.32 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1113.90 |
November | 37318.51 | 15-NOV-21:00 | 35484.54 | 11849.32 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1093.56 |
December | 35953.02 | 21-DEC-22:00 | 40553.76 | 10532.73 | 9501.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1446.39 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 35953.02 | 35484.54 | 10532.73 | 9501.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 44790.30 | 212907.24 | 63196.36 | 57008.13 | 0.00 | 0.00 | 0.00 | 0.00 | 362.23 | 1446.39 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2738.75 | 25-JAN-16:01 | 680.40 | 769.75 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.26 |
February | 3588.17 | 18-FEB-16:01 | 378.00 | 907.20 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 120.24 |
March | 3467.60 | 31-MAR-15:01 | 680.40 | 769.75 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.08 |
April | 3652.25 | 13-APR-15:02 | 583.20 | 659.78 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.85 |
May | 3713.54 | 21-MAY-15:01 | 378.00 | 907.20 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.25 |
June | 3547.78 | 08-JUN-18:02 | 831.60 | 2097.16 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.01 |
July | 3527.11 | 26-JUL-15:02 | 583.20 | 659.78 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.51 |
August | 3486.67 | 27-AUG-18:02 | 702.00 | 2356.36 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.93 |
September | 3635.31 | 29-SEP-15:01 | 680.40 | 769.75 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.18 |
October | 3661.29 | 07-OCT-15:02 | 324.00 | 777.60 | 458.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.12 |
November | 3559.11 | 03-NOV-15:01 | 680.40 | 769.75 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.58 |
December | 487.11 | 20-DEC-19:05 | 831.60 | 2097.16 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.22 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 487.11 | 324.00 | 659.78 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.51 | |
Maximum of Months | 3713.54 | 831.60 | 2356.36 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 120.24 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2001.23 | 19-JAN-16:01 | 680.40 | 769.66 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.39 |
February | 2991.45 | 19-FEB-16:02 | 324.00 | 777.51 | 458.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 116.92 |
March | 3004.22 | 20-MAR-18:02 | 831.60 | 2096.92 | 774.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.18 |
April | 3258.57 | 26-APR-15:02 | 583.20 | 659.70 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.25 |
May | 3342.63 | 21-MAY-15:01 | 378.00 | 907.09 | 534.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.29 |
June | 3221.88 | 08-JUN-18:02 | 831.60 | 2096.92 | 774.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.66 |
July | 3253.47 | 24-JUL-15:02 | 583.20 | 659.70 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.86 |
August | 3236.95 | 19-AUG-15:02 | 324.00 | 777.51 | 458.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.93 |
September | 3257.18 | 11-SEP-15:02 | 583.20 | 659.70 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.03 |
October | 3255.35 | 07-OCT-15:02 | 324.00 | 777.51 | 458.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.39 |
November | 1910.06 | 10-NOV-16:02 | 583.20 | 659.70 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.36 |
December | 286.37 | 02-DEC-09:05 | 324.00 | 1319.41 | 979.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.38 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 286.37 | 324.00 | 659.70 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.03 | |
Maximum of Months | 3342.63 | 831.60 | 2096.92 | 979.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 116.92 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 580.61 | 21-JAN-11:25 | 0.00 | 162.90 | 149.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.96 |
February | 527.06 | 04-FEB-14:00 | 0.00 | 81.45 | 74.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.53 |
March | 252.23 | 25-MAR-11:40 | 0.00 | 81.45 | 74.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.59 |
April | 733.86 | 30-APR-12:50 | 0.00 | 81.45 | 74.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.60 |
May | 586.72 | 22-MAY-13:20 | 0.00 | 69.11 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.98 |
June | 594.29 | 13-JUN-13:20 | 0.00 | 69.11 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 1.86 | 0.00 |
July | 679.47 | 22-JUL-13:30 | 0.00 | 81.45 | 74.82 | 0.00 | 0.00 | 0.00 | 0.00 | 8.56 | 0.00 |
August | 721.13 | 20-AUG-13:00 | 0.00 | 81.45 | 74.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.72 |
September | 854.01 | 27-SEP-13:20 | 0.00 | 69.11 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.88 |
October | 798.64 | 07-OCT-13:10 | 0.00 | 81.45 | 74.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.29 |
November | 559.27 | 11-NOV-13:30 | 0.00 | 81.45 | 74.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.67 |
December | 249.69 | 26-DEC-14:30 | 0.00 | 69.11 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.91 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 249.69 | 0.00 | 69.11 | 67.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 854.01 | 0.00 | 162.90 | 149.63 | 0.00 | 0.00 | 0.00 | 0.00 | 8.56 | 34.96 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 801.50 | 29-JAN-19:02 | 585.00 | 1234.41 | 632.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.68 |
February | 868.92 | 12-FEB-09:02 | 324.00 | 829.52 | 959.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.89 |
March | 909.11 | 20-MAR-18:02 | 831.60 | 1318.35 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.56 |
April | 973.74 | 22-APR-15:02 | 324.00 | 488.83 | 449.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.91 |
May | 984.28 | 28-MAY-18:01 | 819.00 | 1728.17 | 885.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.08 |
June | 1019.41 | 12-JUN-18:02 | 831.60 | 1318.35 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 5.18 | 0.00 |
July | 1008.63 | 10-JUL-15:02 | 583.20 | 414.76 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.16 |
August | 980.70 | 14-AUG-15:02 | 583.20 | 414.76 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 5.25 | 0.00 |
September | 972.44 | 11-SEP-18:02 | 831.60 | 1318.35 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.55 |
October | 920.67 | 07-OCT-15:02 | 324.00 | 488.83 | 449.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.99 |
November | 887.09 | 26-NOV-09:02 | 324.00 | 829.52 | 959.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.58 |
December | 735.97 | 02-DEC-09:02 | 324.00 | 829.52 | 959.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.65 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 735.97 | 324.00 | 414.76 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1019.41 | 831.60 | 1728.17 | 959.99 | 0.00 | 0.00 | 0.00 | 0.00 | 5.25 | 37.89 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1922.75 | 21-JAN-16:02 | 324.00 | 777.60 | 458.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.05 |
February | 3066.15 | 04-FEB-16:01 | 378.00 | 907.20 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.86 |
March | 2743.32 | 20-MAR-15:01 | 680.40 | 769.75 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.07 |
April | 3326.83 | 15-APR-08:62 | 324.00 | 1319.56 | 979.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.14 |
May | 3353.59 | 21-MAY-15:01 | 378.00 | 907.20 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.56 |
June | 3251.29 | 13-JUN-08:62 | 216.00 | 1036.80 | 679.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.00 |
July | 3270.73 | 23-JUL-08:61 | 378.00 | 1539.49 | 1143.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.17 |
August | 3279.39 | 14-AUG-08:62 | 216.00 | 1036.80 | 679.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.08 |
September | 3289.03 | 29-SEP-15:01 | 680.40 | 769.75 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.67 |
October | 3310.68 | 07-OCT-15:02 | 324.00 | 777.60 | 458.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.52 |
November | 3012.74 | 03-NOV-15:01 | 680.40 | 769.75 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.10 |
December | 737.83 | 06-DEC-09:03 | 216.00 | 1036.80 | 679.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 135.42 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 737.83 | 216.00 | 769.75 | 458.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.00 | |
Maximum of Months | 3353.59 | 680.40 | 1539.49 | 1143.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 135.42 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 689.84 | 19-JAN-09:03 | 216.00 | 1036.68 | 679.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.53 |
February | 1830.15 | 20-FEB-09:02 | 324.00 | 1319.41 | 979.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 128.78 |
March | 912.17 | 10-MAR-09:02 | 180.00 | 863.90 | 566.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.08 |
April | 3029.15 | 15-APR-08:62 | 324.00 | 1319.41 | 979.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.45 |
May | 3041.75 | 21-MAY-15:01 | 378.00 | 907.09 | 534.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.56 |
June | 2967.41 | 13-JUN-08:62 | 216.00 | 1036.68 | 679.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.58 |
July | 2986.74 | 23-JUL-08:61 | 378.00 | 1539.31 | 1143.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.63 |
August | 3006.14 | 14-AUG-08:62 | 216.00 | 1036.68 | 679.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.45 |
September | 2940.32 | 23-SEP-08:62 | 324.00 | 1319.41 | 979.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.88 |
October | 2842.10 | 07-OCT-15:02 | 324.00 | 777.51 | 458.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.55 |
November | 1089.55 | 11-NOV-09:02 | 324.00 | 1319.41 | 979.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.87 |
December | 505.73 | 11-DEC-09:05 | 216.00 | 1036.68 | 679.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 127.64 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 505.73 | 180.00 | 777.51 | 458.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.58 | |
Maximum of Months | 3041.75 | 378.00 | 1539.31 | 1143.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 128.78 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1577.81 | 23-JAN-22:03 | 6790.07 | 2565.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.07 |
February | 1873.12 | 04-FEB-14:20 | 754.45 | 356.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.58 |
March | 1761.06 | 20-MAR-18:03 | 10562.33 | 6840.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 114.88 |
April | 2984.50 | 30-APR-10:35 | 1508.90 | 855.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.51 |
May | 2832.46 | 22-MAY-18:10 | 10562.33 | 6840.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.38 |
June | 2973.33 | 13-JUN-10:35 | 1005.94 | 712.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 0.00 |
July | 3162.57 | 23-JUL-10:35 | 1508.90 | 855.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.72 |
August | 3076.09 | 14-AUG-17:08 | 10059.36 | 6840.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.10 | 0.00 |
September | 2913.29 | 12-SEP-10:35 | 1005.94 | 712.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.68 |
October | 2457.14 | 07-OCT-17:12 | 6035.62 | 3420.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.36 |
November | 1788.08 | 11-NOV-13:00 | 754.45 | 427.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.10 |
December | 1236.39 | 21-DEC-22:03 | 6790.07 | 2565.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 159.79 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 1236.39 | 754.45 | 356.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3162.57 | 10562.33 | 6840.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.10 | 159.79 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2883.16 | 25-JAN-16:01 | 680.40 | 769.75 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.64 |
February | 3812.42 | 09-FEB-16:01 | 680.40 | 769.75 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.37 |
March | 3676.82 | 10-MAR-16:01 | 680.40 | 769.75 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.06 |
April | 3907.50 | 13-APR-15:02 | 583.20 | 659.78 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.38 |
May | 3970.98 | 21-MAY-15:01 | 378.00 | 907.20 | 534.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.76 |
June | 3842.59 | 13-JUN-18:02 | 831.60 | 2097.16 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 0.00 |
July | 3768.49 | 16-JUL-18:02 | 702.00 | 2356.36 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.79 |
August | 3758.24 | 10-AUG-15:02 | 583.20 | 659.78 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.43 |
September | 3863.96 | 29-SEP-15:01 | 680.40 | 769.75 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.28 |
October | 3910.58 | 07-OCT-15:02 | 324.00 | 777.60 | 458.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.55 |
November | 3748.33 | 03-NOV-15:01 | 680.40 | 769.75 | 479.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.85 |
December | 386.08 | 26-DEC-16:05 | 583.20 | 659.78 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 135.32 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 386.08 | 324.00 | 659.78 | 410.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3970.98 | 831.60 | 2356.36 | 774.39 | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 135.32 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1345.54 | 19-JAN-16:01 | 680.40 | 769.66 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.53 |
February | 2757.61 | 19-FEB-16:02 | 324.00 | 777.51 | 458.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 116.25 |
March | 3199.66 | 20-MAR-18:02 | 831.60 | 2096.92 | 774.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.20 |
April | 3468.02 | 26-APR-15:02 | 583.20 | 659.70 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.87 |
May | 3552.20 | 21-MAY-15:01 | 378.00 | 907.09 | 534.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.85 |
June | 3499.22 | 13-JUN-18:02 | 831.60 | 2096.92 | 774.30 | 0.00 | 0.00 | 0.00 | 0.00 | 2.82 | 0.00 |
July | 3426.28 | 24-JUL-18:02 | 831.60 | 2096.92 | 774.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.64 |
August | 3396.68 | 27-AUG-15:02 | 324.00 | 777.51 | 458.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.48 |
September | 3423.80 | 29-SEP-15:01 | 680.40 | 769.66 | 479.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.82 |
October | 3445.90 | 07-OCT-15:02 | 324.00 | 777.51 | 458.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.69 |
November | 1464.58 | 10-NOV-16:02 | 583.20 | 659.70 | 410.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.66 |
December | 99.93 | 06-DEC-11:02 | 180.00 | 549.75 | 342.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.49 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 99.93 | 180.00 | 549.75 | 342.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3552.20 | 831.60 | 2096.92 | 774.30 | 0.00 | 0.00 | 0.00 | 0.00 | 2.82 | 116.25 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2366.52 | 11-JAN-16:01 | 680.40 | 483.89 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.35 |
February | 2401.31 | 18-FEB-16:01 | 378.00 | 570.30 | 523.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.99 |
March | 2373.54 | 20-MAR-15:01 | 680.40 | 483.89 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.18 |
April | 2429.20 | 13-APR-15:02 | 583.20 | 414.76 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.55 |
May | 2432.77 | 11-MAY-15:01 | 680.40 | 483.89 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.17 |
June | 2327.33 | 12-JUN-18:02 | 831.60 | 1318.35 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 11.04 | 0.00 |
July | 2345.99 | 26-JUL-15:02 | 583.20 | 414.76 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.89 |
August | 2336.78 | 10-AUG-15:02 | 583.20 | 414.76 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.28 |
September | 2403.17 | 29-SEP-15:01 | 680.40 | 483.89 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.19 |
October | 2459.10 | 07-OCT-15:02 | 324.00 | 488.83 | 449.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.39 |
November | 2411.53 | 03-NOV-15:01 | 680.40 | 483.89 | 469.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.89 |
December | 2272.53 | 18-DEC-16:02 | 583.20 | 414.76 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2272.53 | 324.00 | 414.76 | 402.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2459.10 | 831.60 | 1318.35 | 758.70 | 0.00 | 0.00 | 0.00 | 0.00 | 11.04 | 92.35 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 18575.80 | 18-JAN-23:00 | 26988.77 | 2548.93 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 261.22 |
February | 18510.29 | 07-FEB-23:00 | 26988.77 | 2548.93 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 275.28 |
March | 18656.64 | 17-MAR-22:00 | 26988.77 | 2548.93 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 257.03 |
April | 20484.79 | 29-APR-18:03 | 107955.07 | 17842.50 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.40 |
May | 21408.22 | 22-MAY-18:10 | 125947.58 | 20391.43 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.79 |
June | 22203.62 | 12-JUN-18:10 | 125947.58 | 20391.43 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 60.88 | 0.00 |
July | 22256.21 | 22-JUL-18:10 | 107955.07 | 17842.50 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 128.48 | 0.00 |
August | 22154.24 | 14-AUG-17:08 | 119950.08 | 20391.43 | 53983.22 | 0.00 | 0.00 | 0.00 | 0.00 | 88.31 | 0.00 |
September | 20493.64 | 11-SEP-18:10 | 125947.58 | 20391.43 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.26 |
October | 19011.88 | 17-OCT-22:00 | 26988.77 | 2548.93 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 203.33 |
November | 18896.75 | 08-NOV-23:00 | 26988.77 | 2548.93 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 203.21 |
December | 18252.70 | 04-DEC-23:00 | 26988.77 | 2548.93 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 269.23 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 18252.70 | 26988.77 | 2548.93 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22256.21 | 125947.58 | 20391.43 | 53983.22 | 0.00 | 0.00 | 0.00 | 0.00 | 128.48 | 275.28 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 19786.82 | 18-JAN-23:00 | 26988.77 | 2548.93 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 263.13 |
February | 19716.50 | 07-FEB-23:00 | 26988.77 | 2548.93 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 277.18 |
March | 19886.43 | 17-MAR-22:00 | 26988.77 | 2548.93 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 259.02 |
April | 21823.48 | 29-APR-18:03 | 107955.07 | 17842.50 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.43 |
May | 22778.05 | 22-MAY-18:10 | 125947.58 | 20391.43 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.73 |
June | 23613.89 | 12-JUN-18:10 | 125947.58 | 20391.43 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 58.97 | 0.00 |
July | 23677.26 | 22-JUL-18:10 | 107955.07 | 17842.50 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 126.56 | 0.00 |
August | 23569.19 | 14-AUG-17:08 | 119950.08 | 20391.43 | 53983.22 | 0.00 | 0.00 | 0.00 | 0.00 | 86.36 | 0.00 |
September | 21788.01 | 11-SEP-18:10 | 125947.58 | 20391.43 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 |
October | 20255.36 | 17-OCT-22:00 | 26988.77 | 2548.93 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 205.26 |
November | 20135.01 | 08-NOV-23:00 | 26988.77 | 2548.93 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 205.15 |
December | 19445.97 | 04-DEC-23:00 | 26988.77 | 2548.93 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 19445.97 | 26988.77 | 2548.93 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 23677.26 | 125947.58 | 20391.43 | 53983.22 | 0.00 | 0.00 | 0.00 | 0.00 | 126.56 | 277.18 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 26672.72 | 15-JAN-11:50 | 800.57 | 340.26 | 15112.11 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 239.64 |
February | 26896.83 | 22-FEB-11:40 | 533.71 | 283.55 | 15112.11 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 213.16 |
March | 27770.77 | 25-MAR-10:50 | 1601.14 | 567.10 | 30224.21 | 37488.05 | 0.00 | 0.00 | 0.00 | 0.00 | 194.53 |
April | 30429.54 | 30-APR-10:40 | 1601.14 | 680.52 | 30224.21 | 37488.05 | 0.00 | 0.00 | 0.00 | 0.00 | 70.86 |
May | 30306.53 | 23-MAY-10:50 | 533.71 | 283.55 | 15112.11 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 61.27 |
June | 30626.29 | 13-JUN-10:40 | 1067.42 | 567.10 | 30224.21 | 37488.05 | 0.00 | 0.00 | 0.00 | 0.00 | 31.15 |
July | 31221.45 | 23-JUL-10:40 | 1601.14 | 680.52 | 30224.21 | 37488.05 | 0.00 | 0.00 | 0.00 | 0.00 | 46.26 |
August | 30773.76 | 14-AUG-17:08 | 10674.24 | 5444.15 | 120896.85 | 179942.65 | 0.00 | 0.00 | 0.00 | 41.29 | 0.00 |
September | 29955.44 | 12-SEP-10:40 | 1067.42 | 567.10 | 30224.21 | 37488.05 | 0.00 | 0.00 | 0.00 | 0.00 | 97.07 |
October | 28886.76 | 04-OCT-10:35 | 1067.42 | 567.10 | 30224.21 | 37488.05 | 0.00 | 0.00 | 0.00 | 0.00 | 171.25 |
November | 26686.77 | 11-NOV-11:50 | 800.57 | 340.26 | 15112.11 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 234.70 |
December | 25726.04 | 03-DEC-11:50 | 800.57 | 340.26 | 15112.11 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 270.75 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 25726.04 | 533.71 | 283.55 | 15112.11 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 31221.45 | 10674.24 | 5444.15 | 120896.85 | 179942.65 | 0.00 | 0.00 | 0.00 | 41.29 | 270.75 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3777.44 | 15-JAN-13:00 | 798.48 | 452.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 171.07 |
February | 4167.31 | 04-FEB-13:40 | 798.48 | 377.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 184.17 |
March | 4013.48 | 25-MAR-11:50 | 798.48 | 377.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 137.86 |
April | 6741.10 | 29-APR-17:12 | 6387.84 | 3619.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.63 |
May | 6669.91 | 22-MAY-17:12 | 5323.20 | 3619.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.10 |
June | 7278.48 | 25-JUN-10:35 | 1596.96 | 904.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.29 |
July | 7605.39 | 23-JUL-10:35 | 1596.96 | 904.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.77 |
August | 7515.19 | 14-AUG-17:08 | 10646.40 | 7239.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.63 | 0.00 |
September | 6493.49 | 13-SEP-16:20 | 1330.80 | 377.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.63 | 0.00 |
October | 5688.90 | 07-OCT-15:30 | 798.48 | 377.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.95 |
November | 3690.09 | 11-NOV-13:00 | 798.48 | 452.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 185.16 |
December | 2749.62 | 18-DEC-13:30 | 532.32 | 377.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 200.89 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 2749.62 | 532.32 | 377.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7605.39 | 10646.40 | 7239.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.63 | 200.89 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.558669E+12 | 328709.79 | 23-JAN-20:49 | 0.639772E+12 | 523100.38 | 11-JAN-17:49 |
February | 0.502924E+12 | 326790.77 | 22-FEB-20:49 | 0.562239E+12 | 445138.97 | 14-FEB-17:00 |
March | 0.552614E+12 | 328419.46 | 20-MAR-19:49 | 0.613488E+12 | 450634.31 | 05-MAR-17:49 |
April | 0.569749E+12 | 424440.37 | 30-APR-19:19 | 0.540661E+12 | 432792.14 | 04-APR-17:19 |
May | 0.585822E+12 | 371889.35 | 22-MAY-19:10 | 0.552607E+12 | 429094.48 | 15-MAY-17:49 |
June | 0.591862E+12 | 453115.40 | 25-JUN-18:10 | 0.515228E+12 | 419823.11 | 04-JUN-17:49 |
July | 0.633105E+12 | 469437.58 | 22-JUL-18:10 | 0.520091E+12 | 406964.60 | 04-JUL-16:00 |
August | 0.639125E+12 | 437511.97 | 14-AUG-18:10 | 0.513430E+12 | 396842.68 | 09-AUG-17:00 |
September | 0.599318E+12 | 407203.88 | 11-SEP-18:10 | 0.501230E+12 | 402146.69 | 08-SEP-17:49 |
October | 0.571819E+12 | 343334.13 | 02-OCT-19:19 | 0.563306E+12 | 425810.95 | 27-OCT-17:00 |
November | 0.540382E+12 | 328579.91 | 15-NOV-20:00 | 0.584291E+12 | 444123.21 | 26-NOV-17:10 |
December | 0.554789E+12 | 322194.23 | 20-DEC-20:00 | 0.648322E+12 | 501915.04 | 29-DEC-17:30 |
Annual Sum or Average | 0.690018E+13 | 0.675467E+13 | ||||
Minimum of Months | 0.502924E+12 | 322194.23 | 0.501230E+12 | 396842.68 | ||
Maximum of Months | 0.639125E+12 | 469437.58 | 0.648322E+12 | 523100.38 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [J] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.997859E+11 | 0.286107E+11 | 0.148746E+12 | 0.577258E+11 | 0.151285E+12 | 0.601509E+10 | 0.00 | 0.500455E+10 | 0.00 | 0.00 | 0.475276E+11 | 0.770799E+10 | 0.00 |
February | 0.901073E+11 | 0.235435E+11 | 0.134341E+12 | 0.521396E+11 | 0.136131E+12 | 0.578722E+10 | 0.00 | 0.529441E+10 | 0.00 | 0.00 | 0.429545E+11 | 0.696516E+10 | 0.00 |
March | 0.995228E+11 | 0.229126E+11 | 0.148757E+12 | 0.577286E+11 | 0.149486E+12 | 0.693914E+10 | 0.00 | 0.573984E+10 | 0.00 | 0.00 | 0.475471E+11 | 0.770665E+10 | 0.00 |
April | 0.965474E+11 | 0.189870E+11 | 0.143913E+12 | 0.558635E+11 | 0.149628E+12 | 0.133032E+11 | 0.00 | 0.367272E+11 | 0.00 | 0.00 | 0.412220E+11 | 0.746767E+10 | 0.00 |
May | 0.996636E+11 | 0.168239E+11 | 0.148757E+12 | 0.577273E+11 | 0.154383E+12 | 0.138606E+11 | 0.00 | 0.392408E+11 | 0.00 | 0.00 | 0.413242E+11 | 0.770734E+10 | 0.00 |
June | 0.963626E+11 | 0.147910E+11 | 0.143963E+12 | 0.558662E+11 | 0.151869E+12 | 0.153260E+11 | 0.00 | 0.704460E+11 | 0.00 | 0.00 | 0.295990E+11 | 0.745932E+10 | 0.00 |
July | 0.998551E+11 | 0.159427E+11 | 0.148708E+12 | 0.577246E+11 | 0.158288E+12 | 0.169577E+11 | 0.00 | 0.999313E+11 | 0.00 | 0.00 | 0.216121E+11 | 0.771508E+10 | 0.00 |
August | 0.995413E+11 | 0.183761E+11 | 0.148768E+12 | 0.577287E+11 | 0.157827E+12 | 0.174100E+11 | 0.00 | 0.109496E+12 | 0.00 | 0.00 | 0.158725E+11 | 0.770697E+10 | 0.00 |
September | 0.965794E+11 | 0.207895E+11 | 0.143924E+12 | 0.558636E+11 | 0.152101E+12 | 0.155743E+11 | 0.00 | 0.745081E+11 | 0.00 | 0.00 | 0.263392E+11 | 0.746895E+10 | 0.00 |
October | 0.997606E+11 | 0.247552E+11 | 0.148735E+12 | 0.577257E+11 | 0.151580E+12 | 0.108966E+11 | 0.00 | 0.201605E+11 | 0.00 | 0.00 | 0.441759E+11 | 0.770633E+10 | 0.00 |
November | 0.965244E+11 | 0.268181E+11 | 0.143978E+12 | 0.558644E+11 | 0.145341E+12 | 0.668908E+10 | 0.00 | 0.575846E+10 | 0.00 | 0.00 | 0.458800E+11 | 0.745234E+10 | 0.00 |
December | 0.998619E+11 | 0.293818E+11 | 0.148708E+12 | 0.577246E+11 | 0.151814E+12 | 0.404644E+10 | 0.00 | 0.173023E+10 | 0.00 | 0.00 | 0.475568E+11 | 0.771633E+10 | 0.00 |
Annual Sum or Average | 0.117411E+13 | 0.261732E+12 | 0.175130E+13 | 0.679683E+12 | 0.180973E+13 | 0.132805E+12 | 0.00 | 0.474038E+12 | 0.00 | 0.00 | 0.451611E+12 | 0.907801E+11 | 0.00 |
Minimum of Months | 0.901073E+11 | 0.147910E+11 | 0.134341E+12 | 0.521396E+11 | 0.136131E+12 | 0.404644E+10 | 0.00 | 0.173023E+10 | 0.00 | 0.00 | 0.158725E+11 | 0.696516E+10 | 0.00 |
Maximum of Months | 0.998619E+11 | 0.293818E+11 | 0.148768E+12 | 0.577287E+11 | 0.158288E+12 | 0.174100E+11 | 0.00 | 0.109496E+12 | 0.00 | 0.00 | 0.475568E+11 | 0.771633E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.151918E+12 | 0.00 | 0.196158E+12 | 0.00 | 0.291697E+12 | 0.00 | 0.00 |
February | 0.137204E+12 | 0.00 | 0.160371E+12 | 0.00 | 0.264664E+12 | 0.00 | 0.00 |
March | 0.152024E+12 | 0.00 | 0.169699E+12 | 0.00 | 0.291765E+12 | 0.00 | 0.00 |
April | 0.146956E+12 | 0.00 | 0.114933E+12 | 0.00 | 0.278773E+12 | 0.00 | 0.00 |
May | 0.151978E+12 | 0.00 | 0.117614E+12 | 0.00 | 0.283015E+12 | 0.00 | 0.00 |
June | 0.147114E+12 | 0.00 | 0.990932E+11 | 0.00 | 0.269021E+12 | 0.00 | 0.00 |
July | 0.151820E+12 | 0.00 | 0.940916E+11 | 0.00 | 0.274179E+12 | 0.00 | 0.00 |
August | 0.152039E+12 | 0.00 | 0.885188E+11 | 0.00 | 0.272873E+12 | 0.00 | 0.00 |
September | 0.146971E+12 | 0.00 | 0.889284E+11 | 0.00 | 0.265331E+12 | 0.00 | 0.00 |
October | 0.151903E+12 | 0.00 | 0.133560E+12 | 0.00 | 0.277843E+12 | 0.00 | 0.00 |
November | 0.147091E+12 | 0.00 | 0.163434E+12 | 0.00 | 0.273767E+12 | 0.00 | 0.00 |
December | 0.151820E+12 | 0.00 | 0.208538E+12 | 0.00 | 0.287963E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.178884E+13 | 0.00 | 0.163494E+13 | 0.00 | 0.333089E+13 | 0.00 | 0.00 |
Minimum of Months | 0.137204E+12 | 0.00 | 0.885188E+11 | 0.00 | 0.264664E+12 | 0.00 | 0.00 |
Maximum of Months | 0.152039E+12 | 0.00 | 0.208538E+12 | 0.00 | 0.291765E+12 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 93091.76 | 02-JAN-20:10 | 16690.39 | 01-JAN-00:10 | 89674.66 | 02-JAN-07:10 | 40537.60 | 02-JAN-07:19 | 70136.67 | 12-JAN-16:10 | 6042.54 | 21-JAN-10:00 | 0.00 | 01-JAN-00:10 |
February | 93091.76 | 01-FEB-20:10 | 16690.39 | 01-FEB-00:10 | 89674.66 | 01-FEB-07:10 | 40537.60 | 01-FEB-07:19 | 65894.88 | 17-FEB-16:10 | 6106.87 | 19-FEB-16:10 | 0.00 | 01-FEB-00:10 |
March | 93091.76 | 01-MAR-20:10 | 16690.39 | 01-MAR-00:10 | 89674.66 | 01-MAR-07:10 | 40537.60 | 01-MAR-07:19 | 64298.86 | 15-MAR-15:09 | 5884.42 | 20-MAR-16:19 | 0.00 | 01-MAR-00:10 |
April | 93091.76 | 03-APR-19:10 | 16690.39 | 01-APR-00:10 | 89674.66 | 03-APR-06:10 | 40537.60 | 03-APR-06:19 | 76873.48 | 30-APR-15:20 | 8581.04 | 29-APR-16:49 | 0.00 | 01-APR-00:10 |
May | 93091.76 | 01-MAY-19:10 | 16690.39 | 01-MAY-00:10 | 89674.66 | 01-MAY-06:10 | 40537.60 | 01-MAY-06:19 | 72623.81 | 22-MAY-15:09 | 8471.57 | 21-MAY-16:00 | 0.00 | 01-MAY-00:10 |
June | 93091.76 | 01-JUN-19:10 | 16690.39 | 01-JUN-00:10 | 89674.66 | 01-JUN-06:10 | 40537.60 | 01-JUN-06:19 | 75394.20 | 13-JUN-18:19 | 8825.76 | 25-JUN-18:10 | 0.00 | 01-JUN-00:10 |
July | 93091.76 | 03-JUL-19:10 | 16690.39 | 01-JUL-00:10 | 89674.66 | 03-JUL-06:10 | 40537.60 | 03-JUL-06:19 | 76877.01 | 22-JUL-15:20 | 8954.24 | 22-JUL-18:10 | 0.00 | 01-JUL-00:10 |
August | 93091.76 | 01-AUG-19:10 | 16690.39 | 01-AUG-00:10 | 89674.66 | 01-AUG-06:10 | 40537.60 | 01-AUG-06:19 | 74014.04 | 20-AUG-15:09 | 8919.94 | 14-AUG-16:00 | 0.00 | 01-AUG-00:10 |
September | 93091.76 | 01-SEP-19:10 | 16690.39 | 01-SEP-00:10 | 89674.66 | 01-SEP-06:10 | 40537.60 | 01-SEP-06:19 | 73752.24 | 25-SEP-15:20 | 8693.37 | 27-SEP-15:00 | 0.00 | 01-SEP-00:10 |
October | 93091.76 | 02-OCT-19:10 | 16690.39 | 01-OCT-00:10 | 89674.66 | 02-OCT-06:10 | 40537.60 | 02-OCT-06:19 | 70274.88 | 01-OCT-15:09 | 7738.92 | 07-OCT-15:30 | 0.00 | 01-OCT-00:10 |
November | 93091.76 | 01-NOV-19:10 | 16690.39 | 01-NOV-00:10 | 89674.66 | 01-NOV-06:10 | 40537.60 | 01-NOV-06:19 | 67801.53 | 29-NOV-16:10 | 6149.84 | 24-NOV-11:50 | 0.00 | 01-NOV-00:10 |
December | 93091.76 | 01-DEC-20:10 | 16690.39 | 01-DEC-00:10 | 89674.66 | 01-DEC-07:10 | 40537.60 | 01-DEC-07:19 | 69286.88 | 27-DEC-16:10 | 5082.14 | 26-DEC-14:30 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 93091.76 | 16690.39 | 89674.66 | 40537.60 | 64298.86 | 5082.14 | 0.00 | |||||||
Maximum of Months | 93091.76 | 16690.39 | 89674.66 | 40537.60 | 76877.01 | 8954.24 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY {Maximum} [W] | HEATRECOVERY:ELECTRICITY {TIMESTAMP} | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 18897.72 | 21-JAN-10:00 | 0.00 | 0.00 | 17755.68 | 01-JAN-00:10 | 4739.90 | 02-JAN-07:10 | 0.00 |
February | 20020.55 | 19-FEB-16:10 | 0.00 | 0.00 | 17755.68 | 01-FEB-00:10 | 4739.76 | 22-FEB-07:10 | 0.00 |
March | 13036.05 | 25-MAR-20:19 | 0.00 | 0.00 | 17755.68 | 01-MAR-00:10 | 4738.91 | 17-MAR-06:10 | 0.00 |
April | 120587.90 | 30-APR-18:10 | 0.00 | 0.00 | 17755.68 | 30-APR-17:10 | 4738.50 | 10-APR-06:00 | 0.00 |
May | 116124.61 | 22-MAY-15:09 | 0.00 | 0.00 | 17755.68 | 01-MAY-00:10 | 4738.87 | 31-MAY-06:10 | 0.00 |
June | 161469.84 | 25-JUN-18:19 | 0.00 | 0.00 | 17755.68 | 12-JUN-17:10 | 4738.63 | 19-JUN-06:30 | 0.00 |
July | 167714.04 | 22-JUL-18:10 | 0.00 | 0.00 | 17755.68 | 21-JUL-17:10 | 4738.66 | 27-JUL-18:10 | 0.00 |
August | 136463.25 | 14-AUG-18:10 | 0.00 | 0.00 | 17755.68 | 14-AUG-17:10 | 4738.46 | 28-AUG-06:30 | 0.00 |
September | 115962.91 | 13-SEP-15:50 | 0.00 | 0.00 | 17755.68 | 11-SEP-17:10 | 4738.78 | 18-SEP-06:30 | 0.00 |
October | 75575.79 | 07-OCT-15:09 | 0.00 | 0.00 | 17755.68 | 01-OCT-00:10 | 4739.32 | 24-OCT-06:10 | 0.00 |
November | 26968.99 | 24-NOV-11:50 | 0.00 | 0.00 | 17755.68 | 01-NOV-00:10 | 4738.81 | 14-NOV-07:10 | 0.00 |
December | 7486.44 | 26-DEC-12:39 | 0.00 | 0.00 | 17755.68 | 01-DEC-00:10 | 4738.82 | 18-DEC-07:00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 7486.44 | 0.00 | 0.00 | 17755.68 | 4738.46 | 0.00 | |||
Maximum of Months | 167714.04 | 0.00 | 0.00 | 17755.68 | 4739.90 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 328709.79 | 23-JAN-20:49 | 93091.76 | 88971.67 | 16690.39 | 33025.38 | 58039.62 | 5287.55 | 0.00 | 9033.71 | 0.00 |
February | 326790.77 | 22-FEB-20:49 | 93091.76 | 88971.67 | 16690.39 | 33025.38 | 57819.90 | 5156.62 | 0.00 | 7315.46 | 0.00 |
March | 328419.46 | 20-MAR-19:49 | 93091.76 | 88971.67 | 16690.39 | 33025.38 | 57462.95 | 5225.61 | 0.00 | 9293.37 | 0.00 |
April | 424440.37 | 30-APR-19:19 | 87949.43 | 87485.24 | 16690.39 | 32967.42 | 67334.79 | 8151.21 | 0.00 | 101621.97 | 0.00 |
May | 371889.35 | 22-MAY-19:10 | 93091.76 | 88971.67 | 0.00 | 33012.66 | 65693.88 | 7762.25 | 0.00 | 76666.74 | 0.00 |
June | 453115.40 | 25-JUN-18:10 | 82807.27 | 76644.19 | 0.00 | 32602.97 | 72758.06 | 8825.76 | 0.00 | 156610.18 | 0.00 |
July | 469437.58 | 22-JUL-18:10 | 82807.27 | 76644.19 | 0.00 | 32608.13 | 75740.31 | 8954.24 | 0.00 | 167714.04 | 0.00 |
August | 437511.97 | 14-AUG-18:10 | 82800.17 | 79617.06 | 0.00 | 32686.23 | 72582.29 | 8097.84 | 0.00 | 136463.25 | 0.00 |
September | 407203.88 | 11-SEP-18:10 | 82800.17 | 79617.06 | 0.00 | 32686.23 | 68260.93 | 8064.67 | 0.00 | 111903.73 | 0.00 |
October | 343334.13 | 02-OCT-19:19 | 93091.76 | 88971.67 | 16690.39 | 33025.38 | 60783.97 | 6281.12 | 0.00 | 19961.16 | 0.00 |
November | 328579.91 | 15-NOV-20:00 | 93091.76 | 88971.67 | 16690.39 | 33025.38 | 58075.96 | 5296.37 | 0.00 | 8953.87 | 0.00 |
December | 322194.23 | 20-DEC-20:00 | 93091.76 | 88971.67 | 16690.39 | 33025.38 | 56933.01 | 4608.04 | 0.00 | 4368.40 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 322194.23 | 82800.17 | 76644.19 | 0.00 | 32602.97 | 56933.01 | 4608.04 | 0.00 | 4368.40 | 0.00 | |
Maximum of Months | 469437.58 | 93091.76 | 88971.67 | 16690.39 | 33025.38 | 75740.31 | 8954.24 | 0.00 | 167714.04 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 104248.32 | 02-JAN-18:10 | 0.00 | 203209.92 | 10-JAN-09:09 | 0.00 | 289656.02 | 31-JAN-21:30 | 0.00 |
February | 104248.32 | 01-FEB-18:10 | 0.00 | 152664.73 | 17-FEB-07:10 | 0.00 | 289920.15 | 16-FEB-21:40 | 0.00 |
March | 104248.32 | 01-MAR-18:10 | 0.00 | 119187.94 | 15-MAR-08:09 | 0.00 | 289618.33 | 03-MAR-21:30 | 0.00 |
April | 104248.32 | 01-APR-17:10 | 0.00 | 112454.81 | 18-APR-10:39 | 0.00 | 287215.33 | 04-APR-20:19 | 0.00 |
May | 104248.32 | 01-MAY-17:10 | 0.00 | 115745.97 | 18-MAY-10:39 | 0.00 | 283456.88 | 04-MAY-20:40 | 0.00 |
June | 104248.32 | 01-JUN-17:10 | 0.00 | 114377.63 | 07-JUN-10:39 | 0.00 | 274154.56 | 07-JUN-20:19 | 0.00 |
July | 104248.32 | 01-JUL-17:10 | 0.00 | 111406.41 | 03-JUL-10:39 | 0.00 | 250760.43 | 03-JUL-20:00 | 0.00 |
August | 104248.32 | 01-AUG-17:10 | 0.00 | 110406.22 | 08-AUG-10:39 | 0.00 | 250565.72 | 21-AUG-20:40 | 0.00 |
September | 104248.32 | 01-SEP-17:10 | 0.00 | 113519.46 | 08-SEP-10:39 | 0.00 | 253252.95 | 28-SEP-20:49 | 0.00 |
October | 104248.32 | 02-OCT-17:10 | 0.00 | 115511.19 | 17-OCT-10:39 | 0.00 | 272938.46 | 31-OCT-20:40 | 0.00 |
November | 104248.32 | 01-NOV-17:10 | 0.00 | 135348.42 | 29-NOV-09:09 | 0.00 | 276263.30 | 22-NOV-21:40 | 0.00 |
December | 104248.32 | 01-DEC-18:10 | 0.00 | 166881.62 | 27-DEC-09:09 | 0.00 | 287262.92 | 28-DEC-21:19 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 104248.32 | 0.00 | 110406.22 | 0.00 | 250565.72 | 0.00 | |||
Maximum of Months | 104248.32 | 0.00 | 203209.92 | 0.00 | 289920.15 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 7.50 | 20.39 | 7.50 | 20.39 | 0.00 | 20.39 | 0.00 | 20.39 |
February | 0.50 | 20.41 | 0.50 | 20.41 | 0.00 | 20.41 | 0.00 | 20.41 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 15.33 | 20.41 | 15.33 | 20.41 | 0.00 | 20.41 | 0.00 | 20.41 |
Annual Sum or Average | 23.33 | 20.40 | 23.33 | 20.40 | 0.00 | 20.40 | 0.00 | 20.40 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 15.33 | 20.41 | 15.33 | 20.41 | 0.00 | 20.41 | 0.00 | 20.41 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.73 | 0.83 | 21.73 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.72 | 0.17 | 21.72 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 1.00 | 21.73 | 1.00 | 21.73 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.73 | 0.83 | 21.73 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.33 | 20.55 | 0.33 | 20.55 | 0.00 | 20.55 | 0.00 | 20.55 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.76 | 0.33 | 21.76 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.68 | 0.17 | 21.68 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.74 | 0.17 | 21.74 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.93 | 0.17 | 21.93 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.17 | 20.55 | 0.17 | 20.55 | 0.00 | 20.55 | 0.00 | 20.55 |
Annual Sum or Average | 0.50 | 20.55 | 0.50 | 20.55 | 0.83 | 21.10 | 0.83 | 21.31 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.33 | 20.55 | 0.33 | 20.55 | 0.33 | 21.93 | 0.33 | 21.93 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.33 | 20.53 | 0.33 | 20.53 | 0.00 | 20.53 | 0.00 | 20.53 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.69 | 0.17 | 21.69 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.71 | 0.50 | 21.71 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.78 | 0.33 | 21.78 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.70 | 0.17 | 21.70 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.33 | 20.53 | 0.33 | 20.53 | 1.17 | 21.29 | 1.17 | 21.46 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.33 | 20.53 | 0.33 | 20.53 | 0.50 | 21.78 | 0.50 | 21.78 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.50 | 20.54 | 0.50 | 20.54 | 0.00 | 20.54 | 0.00 | 20.54 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.33 | 20.53 | 0.33 | 20.53 | 0.00 | 20.53 | 0.00 | 20.53 |
Annual Sum or Average | 0.83 | 20.53 | 0.83 | 20.53 | 0.00 | 20.53 | 0.00 | 20.53 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.50 | 20.54 | 0.50 | 20.54 | 0.00 | 20.54 | 0.00 | 20.54 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 21.86 | 1.33 | 21.86 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.75 | 0.17 | 21.75 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.75 | 0.17 | 21.75 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.89 | 0.50 | 21.89 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.73 | 0.50 | 21.73 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.70 | 0.50 | 21.70 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 3.17 | 21.81 | 3.17 | 21.81 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 21.89 | 1.33 | 21.89 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.85 | 0.67 | 21.85 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.71 | 0.50 | 21.71 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.74 | 0.67 | 21.74 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 21.79 | 1.17 | 21.79 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.17 | 20.55 | 0.17 | 20.55 | 0.00 | 20.55 | 0.00 | 20.55 |
Annual Sum or Average | 0.17 | 20.55 | 0.17 | 20.55 | 3.00 | 21.65 | 3.00 | 21.71 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 20.55 | 0.17 | 20.55 | 1.17 | 21.85 | 1.17 | 21.85 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.72 | 0.33 | 21.72 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.79 | 0.50 | 21.79 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.75 | 0.17 | 21.75 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 1.00 | 21.76 | 1.00 | 21.76 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.79 | 0.50 | 21.79 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.06 | 3.33 | 21.06 | 3.33 | 21.06 |
February | 672.00 | 21.05 | 0.00 | 21.05 | 0.00 | 21.05 |
March | 744.00 | 21.04 | 0.00 | 21.04 | 0.00 | 21.04 |
April | 720.00 | 21.03 | 0.00 | 21.03 | 0.00 | 21.03 |
May | 744.00 | 21.03 | 0.00 | 21.03 | 0.00 | 21.03 |
June | 720.00 | 21.03 | 0.00 | 21.03 | 0.00 | 21.03 |
July | 744.00 | 21.04 | 0.00 | 21.04 | 0.00 | 21.04 |
August | 744.00 | 21.05 | 0.00 | 21.05 | 0.00 | 21.05 |
September | 720.00 | 21.07 | 0.00 | 21.07 | 0.00 | 21.07 |
October | 744.00 | 21.09 | 0.00 | 21.09 | 0.00 | 21.09 |
November | 720.00 | 21.11 | 0.00 | 21.11 | 0.00 | 21.11 |
December | 744.00 | 21.09 | 0.00 | 21.09 | 0.00 | 21.09 |
Annual Sum or Average | 8760.00 | 21.06 | 3.33 | 21.06 | 3.33 | 21.06 |
Minimum of Months | 672.00 | 21.03 | 0.00 | 21.03 | 0.00 | 21.03 |
Maximum of Months | 744.00 | 21.11 | 3.33 | 21.11 | 3.33 | 21.11 |
Report: ComfortReportSimple55Monthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.95 | 290.33 | 20.92 | 290.33 | 20.91 |
February | 672.00 | 20.99 | 183.83 | 20.97 | 183.83 | 20.95 |
March | 744.00 | 20.99 | 216.67 | 20.98 | 216.67 | 20.98 |
April | 720.00 | 21.04 | 24.33 | 21.04 | 24.33 | 21.04 |
May | 744.00 | 21.01 | 4.17 | 21.01 | 4.17 | 21.01 |
June | 720.00 | 21.01 | 0.00 | 21.01 | 0.00 | 21.01 |
July | 744.00 | 21.02 | 0.00 | 21.02 | 0.00 | 21.02 |
August | 735.67 | 21.05 | 0.00 | 21.05 | 0.00 | 21.05 |
September | 681.00 | 21.05 | 12.00 | 21.07 | 0.00 | 21.07 |
October | 740.67 | 21.03 | 9.33 | 21.03 | 9.33 | 21.03 |
November | 720.00 | 20.98 | 160.50 | 20.97 | 160.50 | 20.96 |
December | 744.00 | 20.88 | 498.83 | 20.85 | 498.83 | 20.84 |
Annual Sum or Average | 8709.33 | 21.00 | 1400.00 | 20.98 | 1388.00 | 20.97 |
Minimum of Months | 672.00 | 20.88 | 0.00 | 20.85 | 0.00 | 20.84 |
Maximum of Months | 744.00 | 21.05 | 498.83 | 21.07 | 498.83 | 21.07 |
Report: ComfortReportSimple55Monthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.00 | 0.83 | 21.00 | 0.83 | 21.00 |
February | 672.00 | 21.01 | 0.00 | 21.01 | 0.00 | 21.01 |
March | 744.00 | 21.01 | 0.00 | 21.01 | 0.00 | 21.01 |
April | 720.00 | 21.04 | 0.00 | 21.04 | 0.00 | 21.04 |
May | 744.00 | 21.05 | 0.00 | 21.05 | 0.00 | 21.05 |
June | 720.00 | 21.08 | 0.00 | 21.08 | 0.00 | 21.08 |
July | 744.00 | 21.09 | 0.00 | 21.09 | 0.00 | 21.09 |
August | 744.00 | 21.09 | 0.00 | 21.09 | 0.00 | 21.09 |
September | 720.00 | 21.07 | 0.00 | 21.07 | 0.00 | 21.07 |
October | 744.00 | 21.02 | 0.00 | 21.02 | 0.00 | 21.02 |
November | 720.00 | 21.01 | 0.00 | 21.01 | 0.00 | 21.01 |
December | 744.00 | 21.00 | 5.00 | 21.00 | 5.00 | 21.00 |
Annual Sum or Average | 8760.00 | 21.04 | 5.83 | 21.04 | 5.83 | 21.04 |
Minimum of Months | 672.00 | 21.00 | 0.00 | 21.00 | 0.00 | 21.00 |
Maximum of Months | 744.00 | 21.09 | 5.00 | 21.09 | 5.00 | 21.09 |
Report: ComfortReportSimple55Monthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.00 | 77.33 | 21.00 | 77.33 | 21.00 |
February | 672.00 | 21.00 | 0.00 | 21.00 | 0.00 | 21.00 |
March | 744.00 | 21.00 | 0.00 | 21.00 | 0.00 | 21.00 |
April | 720.00 | 21.00 | 0.00 | 21.00 | 0.00 | 21.00 |
May | 744.00 | 21.01 | 0.00 | 21.01 | 0.00 | 21.01 |
June | 720.00 | 21.02 | 0.00 | 21.02 | 0.00 | 21.02 |
July | 744.00 | 21.03 | 0.00 | 21.03 | 0.00 | 21.03 |
August | 744.00 | 21.03 | 0.00 | 21.03 | 0.00 | 21.03 |
September | 720.00 | 21.01 | 0.00 | 21.01 | 0.00 | 21.01 |
October | 744.00 | 21.00 | 0.00 | 21.00 | 0.00 | 21.00 |
November | 720.00 | 21.00 | 1.00 | 21.00 | 1.00 | 21.00 |
December | 744.00 | 21.00 | 31.33 | 21.00 | 31.33 | 21.00 |
Annual Sum or Average | 8760.00 | 21.01 | 109.67 | 21.01 | 109.67 | 21.01 |
Minimum of Months | 672.00 | 21.00 | 0.00 | 21.00 | 0.00 | 21.00 |
Maximum of Months | 744.00 | 21.03 | 77.33 | 21.03 | 77.33 | 21.03 |
Report: ComfortReportSimple55Monthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.00 | 129.67 | 21.00 | 129.67 | 21.00 |
February | 672.00 | 21.00 | 10.67 | 21.00 | 10.67 | 21.00 |
March | 744.00 | 21.00 | 2.17 | 21.00 | 2.17 | 21.00 |
April | 720.00 | 21.00 | 0.67 | 21.00 | 0.67 | 21.00 |
May | 744.00 | 21.00 | 0.00 | 21.00 | 0.00 | 21.00 |
June | 720.00 | 21.00 | 0.00 | 21.00 | 0.00 | 21.00 |
July | 744.00 | 21.00 | 0.00 | 21.00 | 0.00 | 21.00 |
August | 744.00 | 21.00 | 0.00 | 21.00 | 0.00 | 21.00 |
September | 720.00 | 21.00 | 0.00 | 21.00 | 0.00 | 21.00 |
October | 744.00 | 21.00 | 0.00 | 21.00 | 0.00 | 21.00 |
November | 720.00 | 21.00 | 16.17 | 21.00 | 16.17 | 21.00 |
December | 744.00 | 21.00 | 88.50 | 21.00 | 88.50 | 21.00 |
Annual Sum or Average | 8760.00 | 21.00 | 247.83 | 21.00 | 247.83 | 21.00 |
Minimum of Months | 672.00 | 21.00 | 0.00 | 21.00 | 0.00 | 21.00 |
Maximum of Months | 744.00 | 21.00 | 129.67 | 21.00 | 129.67 | 21.00 |
Report: ComfortReportSimple55Monthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 541.50 | 21.42 | 164.33 | 21.77 | 85.17 | 21.97 |
February | 487.50 | 21.43 | 153.33 | 21.77 | 78.50 | 21.98 |
March | 533.50 | 21.47 | 172.50 | 21.80 | 96.00 | 22.02 |
April | 477.17 | 21.49 | 181.67 | 21.79 | 94.33 | 22.01 |
May | 433.50 | 21.58 | 214.33 | 21.85 | 101.67 | 22.07 |
June | 261.17 | 21.96 | 277.50 | 22.00 | 104.33 | 22.23 |
July | 244.50 | 22.00 | 301.33 | 21.97 | 103.67 | 22.19 |
August | 248.00 | 22.06 | 313.33 | 22.01 | 109.50 | 22.23 |
September | 278.17 | 21.90 | 258.67 | 22.02 | 103.17 | 22.25 |
October | 461.00 | 21.55 | 210.00 | 21.85 | 100.33 | 22.07 |
November | 498.50 | 21.47 | 176.83 | 21.80 | 88.67 | 22.01 |
December | 547.33 | 21.39 | 159.33 | 21.75 | 80.83 | 21.95 |
Annual Sum or Average | 5011.83 | 21.57 | 2583.17 | 21.86 | 1146.17 | 22.07 |
Minimum of Months | 244.50 | 21.39 | 153.33 | 21.75 | 78.50 | 21.95 |
Maximum of Months | 547.33 | 22.06 | 313.33 | 22.02 | 109.50 | 22.25 |
Report: ComfortReportSimple55Monthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.00 | 34.67 | 21.00 | 34.67 | 21.00 |
February | 669.83 | 21.01 | 1.17 | 21.01 | 1.17 | 21.01 |
March | 744.00 | 21.00 | 0.00 | 21.00 | 0.00 | 21.00 |
April | 716.83 | 21.02 | 0.00 | 21.02 | 0.00 | 21.02 |
May | 744.00 | 21.00 | 0.00 | 21.00 | 0.00 | 21.00 |
June | 720.00 | 21.00 | 0.00 | 21.00 | 0.00 | 21.00 |
July | 744.00 | 21.01 | 0.00 | 21.01 | 0.00 | 21.01 |
August | 732.67 | 21.02 | 0.00 | 21.02 | 0.00 | 21.02 |
September | 672.83 | 21.02 | 13.17 | 21.04 | 0.00 | 21.04 |
October | 737.83 | 21.02 | 0.00 | 21.02 | 0.00 | 21.02 |
November | 720.00 | 21.00 | 5.50 | 21.00 | 5.50 | 21.00 |
December | 744.00 | 20.99 | 64.17 | 20.98 | 64.17 | 20.98 |
Annual Sum or Average | 8690.00 | 21.01 | 118.67 | 21.01 | 105.50 | 21.01 |
Minimum of Months | 669.83 | 20.99 | 0.00 | 20.98 | 0.00 | 20.98 |
Maximum of Months | 744.00 | 21.02 | 64.17 | 21.04 | 64.17 | 21.04 |
Report: ComfortReportSimple55Monthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.01 | 0.00 | 21.01 | 0.00 | 21.01 |
February | 672.00 | 21.01 | 0.00 | 21.01 | 0.00 | 21.01 |
March | 744.00 | 21.02 | 0.00 | 21.02 | 0.00 | 21.02 |
April | 720.00 | 21.05 | 0.00 | 21.05 | 0.00 | 21.05 |
May | 744.00 | 21.06 | 0.00 | 21.06 | 0.00 | 21.06 |
June | 720.00 | 21.09 | 0.00 | 21.09 | 0.00 | 21.09 |
July | 744.00 | 21.11 | 0.00 | 21.11 | 0.00 | 21.11 |
August | 744.00 | 21.12 | 0.00 | 21.12 | 0.00 | 21.12 |
September | 720.00 | 21.10 | 0.00 | 21.10 | 0.00 | 21.10 |
October | 744.00 | 21.04 | 0.00 | 21.04 | 0.00 | 21.04 |
November | 720.00 | 21.02 | 0.00 | 21.02 | 0.00 | 21.02 |
December | 744.00 | 21.01 | 0.00 | 21.01 | 0.00 | 21.01 |
Annual Sum or Average | 8760.00 | 21.05 | 0.00 | 21.05 | 0.00 | 21.05 |
Minimum of Months | 672.00 | 21.01 | 0.00 | 21.01 | 0.00 | 21.01 |
Maximum of Months | 744.00 | 21.12 | 0.00 | 21.12 | 0.00 | 21.12 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.88 | 358.33 | 20.77 | 358.33 | 20.72 |
February | 672.00 | 21.01 | 220.83 | 20.90 | 220.83 | 20.84 |
March | 744.00 | 20.95 | 196.50 | 20.88 | 196.50 | 20.83 |
April | 700.17 | 21.46 | 8.50 | 21.45 | 7.33 | 21.44 |
May | 718.67 | 21.43 | 3.50 | 21.44 | 0.00 | 21.44 |
June | 669.83 | 21.48 | 9.50 | 21.51 | 0.00 | 21.51 |
July | 669.17 | 21.46 | 16.83 | 21.50 | 0.00 | 21.50 |
August | 664.83 | 21.45 | 10.00 | 21.48 | 0.00 | 21.48 |
September | 666.00 | 21.46 | 9.67 | 21.49 | 0.00 | 21.49 |
October | 737.17 | 21.20 | 32.00 | 21.15 | 32.00 | 21.10 |
November | 720.00 | 20.93 | 224.50 | 20.81 | 224.50 | 20.74 |
December | 744.00 | 20.68 | 586.33 | 20.63 | 586.33 | 20.61 |
Annual Sum or Average | 8449.83 | 21.19 | 1676.50 | 21.10 | 1625.83 | 21.02 |
Minimum of Months | 664.83 | 20.68 | 3.50 | 20.63 | 0.00 | 20.61 |
Maximum of Months | 744.00 | 21.48 | 586.33 | 21.51 | 586.33 | 21.51 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.67 | 495.50 | 20.59 | 495.50 | 20.56 |
February | 672.00 | 20.78 | 373.00 | 20.68 | 373.00 | 20.63 |
March | 744.00 | 20.85 | 300.00 | 20.76 | 300.00 | 20.71 |
April | 714.17 | 21.32 | 15.50 | 21.30 | 15.50 | 21.29 |
May | 732.17 | 21.37 | 0.33 | 21.37 | 0.17 | 21.37 |
June | 688.83 | 21.48 | 5.00 | 21.49 | 0.00 | 21.49 |
July | 697.50 | 21.48 | 4.50 | 21.49 | 0.00 | 21.49 |
August | 707.67 | 21.47 | 0.00 | 21.47 | 0.00 | 21.47 |
September | 706.67 | 21.40 | 0.00 | 21.40 | 0.00 | 21.40 |
October | 744.00 | 21.02 | 54.50 | 20.95 | 54.50 | 20.89 |
November | 720.00 | 20.75 | 353.33 | 20.64 | 353.33 | 20.58 |
December | 744.00 | 20.55 | 677.50 | 20.53 | 677.50 | 20.52 |
Annual Sum or Average | 8615.00 | 21.09 | 2279.17 | 20.96 | 2269.50 | 20.88 |
Minimum of Months | 672.00 | 20.55 | 0.00 | 20.53 | 0.00 | 20.52 |
Maximum of Months | 744.00 | 21.48 | 677.50 | 21.49 | 677.50 | 21.49 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.01 | 128.50 | 20.95 | 128.50 | 20.91 |
February | 672.00 | 21.05 | 22.50 | 21.04 | 22.50 | 21.02 |
March | 744.00 | 21.16 | 3.50 | 21.16 | 3.50 | 21.16 |
April | 720.00 | 21.34 | 0.00 | 21.34 | 0.00 | 21.34 |
May | 744.00 | 21.39 | 0.00 | 21.39 | 0.00 | 21.39 |
June | 720.00 | 21.48 | 0.00 | 21.48 | 0.00 | 21.48 |
July | 744.00 | 21.50 | 0.00 | 21.50 | 0.00 | 21.50 |
August | 744.00 | 21.43 | 0.00 | 21.43 | 0.00 | 21.43 |
September | 720.00 | 21.37 | 0.00 | 21.37 | 0.00 | 21.37 |
October | 744.00 | 21.22 | 0.00 | 21.22 | 0.00 | 21.22 |
November | 720.00 | 21.08 | 26.67 | 21.06 | 26.67 | 21.04 |
December | 744.00 | 20.96 | 136.83 | 20.89 | 136.83 | 20.84 |
Annual Sum or Average | 8760.00 | 21.25 | 318.00 | 21.23 | 318.00 | 21.20 |
Minimum of Months | 672.00 | 20.96 | 0.00 | 20.89 | 0.00 | 20.84 |
Maximum of Months | 744.00 | 21.50 | 136.83 | 21.50 | 136.83 | 21.50 |
Report: ComfortReportSimple55Monthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.87 | 355.00 | 20.77 | 355.00 | 20.72 |
February | 672.00 | 21.00 | 233.00 | 20.90 | 233.00 | 20.85 |
March | 744.00 | 20.98 | 194.67 | 20.91 | 194.67 | 20.86 |
April | 697.00 | 21.56 | 6.50 | 21.55 | 6.50 | 21.55 |
May | 715.00 | 21.52 | 0.00 | 21.52 | 0.00 | 21.52 |
June | 655.67 | 21.49 | 0.33 | 21.49 | 0.00 | 21.49 |
July | 652.17 | 21.46 | 1.67 | 21.47 | 0.00 | 21.47 |
August | 628.67 | 21.39 | 0.17 | 21.39 | 0.00 | 21.39 |
September | 640.83 | 21.47 | 0.00 | 21.47 | 0.00 | 21.47 |
October | 744.00 | 21.26 | 29.67 | 21.21 | 29.67 | 21.17 |
November | 720.00 | 20.92 | 226.50 | 20.81 | 226.50 | 20.74 |
December | 744.00 | 20.70 | 560.17 | 20.64 | 560.17 | 20.62 |
Annual Sum or Average | 8357.33 | 21.21 | 1607.67 | 21.10 | 1605.50 | 21.03 |
Minimum of Months | 628.67 | 20.70 | 0.00 | 20.64 | 0.00 | 20.62 |
Maximum of Months | 744.00 | 21.56 | 560.17 | 21.55 | 560.17 | 21.55 |
Report: ComfortReportSimple55Monthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.67 | 492.67 | 20.59 | 492.67 | 20.56 |
February | 672.00 | 20.75 | 417.67 | 20.68 | 417.67 | 20.65 |
March | 744.00 | 20.88 | 280.50 | 20.80 | 280.50 | 20.76 |
April | 717.50 | 21.51 | 10.67 | 21.49 | 10.67 | 21.48 |
May | 735.67 | 21.51 | 0.00 | 21.51 | 0.00 | 21.51 |
June | 684.67 | 21.55 | 0.17 | 21.55 | 0.00 | 21.55 |
July | 707.17 | 21.60 | 0.67 | 21.60 | 0.00 | 21.60 |
August | 720.67 | 21.61 | 0.00 | 21.61 | 0.00 | 21.61 |
September | 717.67 | 21.60 | 0.00 | 21.60 | 0.00 | 21.60 |
October | 744.00 | 21.09 | 42.83 | 21.03 | 42.83 | 20.98 |
November | 720.00 | 20.74 | 356.83 | 20.63 | 356.83 | 20.58 |
December | 744.00 | 20.57 | 648.17 | 20.53 | 648.17 | 20.52 |
Annual Sum or Average | 8651.33 | 21.17 | 2250.17 | 21.03 | 2249.33 | 20.94 |
Minimum of Months | 672.00 | 20.57 | 0.00 | 20.53 | 0.00 | 20.52 |
Maximum of Months | 744.00 | 21.61 | 648.17 | 21.61 | 648.17 | 21.61 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.00 | 96.67 | 21.00 | 96.67 | 21.00 |
February | 672.00 | 21.00 | 0.00 | 21.00 | 0.00 | 21.00 |
March | 744.00 | 21.00 | 0.00 | 21.00 | 0.00 | 21.00 |
April | 720.00 | 21.03 | 0.00 | 21.03 | 0.00 | 21.03 |
May | 744.00 | 21.02 | 0.00 | 21.02 | 0.00 | 21.02 |
June | 720.00 | 21.06 | 0.00 | 21.06 | 0.00 | 21.06 |
July | 744.00 | 21.12 | 0.00 | 21.12 | 0.00 | 21.12 |
August | 744.00 | 21.11 | 0.00 | 21.11 | 0.00 | 21.11 |
September | 720.00 | 21.09 | 0.00 | 21.09 | 0.00 | 21.09 |
October | 744.00 | 21.01 | 0.00 | 21.01 | 0.00 | 21.01 |
November | 720.00 | 21.00 | 7.17 | 21.00 | 7.17 | 21.00 |
December | 744.00 | 21.00 | 58.00 | 21.00 | 58.00 | 21.00 |
Annual Sum or Average | 8760.00 | 21.04 | 161.83 | 21.04 | 161.83 | 21.03 |
Minimum of Months | 672.00 | 21.00 | 0.00 | 21.00 | 0.00 | 21.00 |
Maximum of Months | 744.00 | 21.12 | 96.67 | 21.12 | 96.67 | 21.12 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.76 | 517.33 | 20.69 | 517.33 | 20.66 |
February | 672.00 | 20.90 | 388.00 | 20.80 | 388.00 | 20.76 |
March | 744.00 | 20.86 | 402.67 | 20.80 | 402.67 | 20.77 |
April | 684.83 | 21.41 | 40.50 | 21.40 | 34.83 | 21.36 |
May | 704.00 | 21.40 | 15.83 | 21.43 | 4.50 | 21.42 |
June | 643.00 | 21.43 | 26.33 | 21.51 | 0.00 | 21.51 |
July | 637.83 | 21.39 | 44.67 | 21.52 | 0.00 | 21.52 |
August | 631.67 | 21.36 | 40.50 | 21.48 | 0.00 | 21.48 |
September | 647.33 | 21.42 | 24.50 | 21.49 | 0.00 | 21.49 |
October | 732.33 | 21.11 | 74.17 | 21.02 | 74.17 | 20.94 |
November | 720.00 | 20.81 | 372.50 | 20.70 | 372.50 | 20.65 |
December | 744.00 | 20.59 | 701.17 | 20.58 | 701.17 | 20.57 |
Annual Sum or Average | 8305.00 | 21.11 | 2648.17 | 21.02 | 2495.17 | 20.94 |
Minimum of Months | 631.67 | 20.59 | 15.83 | 20.58 | 0.00 | 20.57 |
Maximum of Months | 744.00 | 21.43 | 701.17 | 21.52 | 701.17 | 21.52 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.58 | 639.67 | 20.54 | 639.67 | 20.53 |
February | 672.00 | 20.66 | 559.83 | 20.62 | 559.83 | 20.60 |
March | 744.00 | 20.75 | 502.17 | 20.69 | 502.17 | 20.67 |
April | 708.00 | 21.32 | 56.50 | 21.28 | 56.33 | 21.24 |
May | 723.67 | 21.36 | 10.67 | 21.37 | 6.00 | 21.37 |
June | 666.50 | 21.46 | 14.00 | 21.50 | 0.00 | 21.50 |
July | 667.33 | 21.44 | 23.33 | 21.51 | 0.00 | 21.51 |
August | 682.00 | 21.45 | 8.17 | 21.48 | 0.00 | 21.48 |
September | 695.50 | 21.40 | 1.00 | 21.40 | 0.00 | 21.40 |
October | 744.00 | 20.95 | 143.00 | 20.82 | 143.00 | 20.74 |
November | 720.00 | 20.63 | 492.33 | 20.54 | 492.33 | 20.51 |
December | 744.00 | 20.49 | 740.67 | 20.49 | 740.67 | 20.49 |
Annual Sum or Average | 8511.00 | 21.03 | 3191.33 | 20.90 | 3140.00 | 20.82 |
Minimum of Months | 666.50 | 20.49 | 1.00 | 20.49 | 0.00 | 20.49 |
Maximum of Months | 744.00 | 21.46 | 740.67 | 21.51 | 740.67 | 21.51 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 730.17 | 21.12 | 219.50 | 21.00 | 219.50 | 20.93 |
February | 651.00 | 21.19 | 116.83 | 21.11 | 116.83 | 21.05 |
March | 744.00 | 21.15 | 127.33 | 21.08 | 127.33 | 21.03 |
April | 663.17 | 21.46 | 12.33 | 21.50 | 0.00 | 21.50 |
May | 690.17 | 21.43 | 5.00 | 21.44 | 0.00 | 21.44 |
June | 651.83 | 21.46 | 7.33 | 21.48 | 0.00 | 21.48 |
July | 646.67 | 21.41 | 20.67 | 21.47 | 0.00 | 21.47 |
August | 630.33 | 21.36 | 58.00 | 21.53 | 0.00 | 21.53 |
September | 611.50 | 21.37 | 57.83 | 21.54 | 0.00 | 21.54 |
October | 696.67 | 21.25 | 21.50 | 21.25 | 13.83 | 21.23 |
November | 706.67 | 21.14 | 121.33 | 21.05 | 121.33 | 20.98 |
December | 741.50 | 20.95 | 403.17 | 20.83 | 403.17 | 20.78 |
Annual Sum or Average | 8163.67 | 21.27 | 1170.83 | 21.23 | 1002.00 | 21.17 |
Minimum of Months | 611.50 | 20.95 | 5.00 | 20.83 | 0.00 | 20.78 |
Maximum of Months | 744.00 | 21.46 | 403.17 | 21.54 | 403.17 | 21.54 |
Report: ComfortReportSimple55Monthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.36 | 0.00 | 21.36 | 0.00 | 21.36 |
February | 672.00 | 21.37 | 0.00 | 21.37 | 0.00 | 21.37 |
March | 744.00 | 21.45 | 0.00 | 21.45 | 0.00 | 21.45 |
April | 720.00 | 21.55 | 0.00 | 21.55 | 0.00 | 21.55 |
May | 742.17 | 21.61 | 0.00 | 21.61 | 0.00 | 21.61 |
June | 704.83 | 21.72 | 2.00 | 21.72 | 0.00 | 21.72 |
July | 711.17 | 21.70 | 1.50 | 21.71 | 0.00 | 21.71 |
August | 720.50 | 21.68 | 0.67 | 21.69 | 0.00 | 21.69 |
September | 716.83 | 21.60 | 0.00 | 21.60 | 0.00 | 21.60 |
October | 744.00 | 21.48 | 0.00 | 21.48 | 0.00 | 21.48 |
November | 720.00 | 21.41 | 0.00 | 21.41 | 0.00 | 21.41 |
December | 744.00 | 21.34 | 0.00 | 21.34 | 0.00 | 21.34 |
Annual Sum or Average | 8683.50 | 21.52 | 4.17 | 21.52 | 0.00 | 21.52 |
Minimum of Months | 672.00 | 21.34 | 0.00 | 21.34 | 0.00 | 21.34 |
Maximum of Months | 744.00 | 21.72 | 2.00 | 21.72 | 0.00 | 21.72 |
Report: ComfortReportSimple55Monthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.41 | 0.00 | 21.41 | 0.00 | 21.41 |
February | 672.00 | 21.42 | 0.00 | 21.42 | 0.00 | 21.42 |
March | 744.00 | 21.51 | 0.00 | 21.51 | 0.00 | 21.51 |
April | 719.67 | 21.62 | 0.00 | 21.62 | 0.00 | 21.62 |
May | 732.17 | 21.68 | 0.33 | 21.68 | 0.00 | 21.68 |
June | 667.50 | 21.75 | 7.17 | 21.77 | 0.00 | 21.77 |
July | 670.50 | 21.75 | 15.50 | 21.78 | 0.00 | 21.78 |
August | 689.67 | 21.72 | 10.33 | 21.74 | 0.00 | 21.74 |
September | 700.33 | 21.65 | 1.00 | 21.65 | 0.00 | 21.65 |
October | 743.67 | 21.55 | 0.00 | 21.55 | 0.00 | 21.55 |
November | 720.00 | 21.47 | 0.00 | 21.47 | 0.00 | 21.47 |
December | 744.00 | 21.39 | 0.00 | 21.39 | 0.00 | 21.39 |
Annual Sum or Average | 8547.50 | 21.57 | 34.33 | 21.58 | 0.00 | 21.58 |
Minimum of Months | 667.50 | 21.39 | 0.00 | 21.39 | 0.00 | 21.39 |
Maximum of Months | 744.00 | 21.75 | 15.50 | 21.78 | 0.00 | 21.78 |
Report: ComfortReportSimple55Monthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 512.67 | 22.65 | 526.83 | 22.96 | 322.33 | 23.11 |
February | 499.00 | 22.73 | 479.50 | 23.02 | 327.50 | 23.17 |
March | 552.00 | 22.77 | 532.83 | 23.06 | 367.50 | 23.21 |
April | 597.67 | 23.05 | 528.17 | 23.32 | 429.50 | 23.46 |
May | 624.83 | 23.08 | 557.83 | 23.33 | 460.67 | 23.47 |
June | 606.50 | 23.21 | 552.17 | 23.41 | 471.00 | 23.54 |
July | 622.83 | 23.28 | 576.00 | 23.46 | 496.50 | 23.57 |
August | 626.00 | 23.26 | 573.83 | 23.45 | 493.83 | 23.57 |
September | 603.67 | 23.17 | 545.17 | 23.39 | 458.33 | 23.52 |
October | 588.83 | 22.91 | 546.00 | 23.17 | 416.17 | 23.31 |
November | 521.83 | 22.73 | 519.17 | 23.01 | 345.00 | 23.15 |
December | 482.67 | 22.56 | 525.83 | 22.88 | 288.83 | 23.04 |
Annual Sum or Average | 6838.50 | 22.97 | 6463.33 | 23.22 | 4877.17 | 23.36 |
Minimum of Months | 482.67 | 22.56 | 479.50 | 22.88 | 288.83 | 23.04 |
Maximum of Months | 626.00 | 23.28 | 576.00 | 23.46 | 496.50 | 23.57 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.00 | 193.17 | 21.00 | 193.17 | 21.00 |
February | 672.00 | 21.00 | 76.67 | 21.00 | 76.67 | 21.00 |
March | 744.00 | 21.00 | 44.00 | 21.00 | 44.00 | 21.00 |
April | 720.00 | 21.02 | 3.67 | 21.02 | 3.67 | 21.02 |
May | 744.00 | 21.01 | 0.00 | 21.01 | 0.00 | 21.01 |
June | 720.00 | 21.03 | 0.00 | 21.03 | 0.00 | 21.03 |
July | 744.00 | 21.04 | 0.00 | 21.04 | 0.00 | 21.04 |
August | 744.00 | 21.04 | 0.00 | 21.04 | 0.00 | 21.04 |
September | 720.00 | 21.03 | 0.00 | 21.03 | 0.00 | 21.03 |
October | 744.00 | 21.00 | 0.00 | 21.00 | 0.00 | 21.00 |
November | 720.00 | 21.00 | 54.67 | 21.00 | 54.67 | 21.00 |
December | 744.00 | 21.00 | 205.83 | 21.00 | 205.83 | 21.00 |
Annual Sum or Average | 8760.00 | 21.02 | 578.00 | 21.01 | 578.00 | 21.01 |
Minimum of Months | 672.00 | 21.00 | 0.00 | 21.00 | 0.00 | 21.00 |
Maximum of Months | 744.00 | 21.04 | 205.83 | 21.04 | 205.83 | 21.04 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT PEOPLE
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.06172 | 34.07310 | -0.4120 | 8.59739 |
February | 672.00000 | 21.05059 | 35.03809 | -0.4131 | 8.59128 |
March | 744.00000 | 21.03937 | 34.84797 | -0.4211 | 8.73797 |
April | 720.00000 | 21.02970 | 35.38859 | -0.4209 | 8.76435 |
May | 744.00000 | 21.02976 | 42.13857 | -1.5781 | 55.15026 |
June | 720.00000 | 21.03222 | 51.23411 | -1.5201 | 52.00054 |
July | 744.00000 | 21.03984 | 53.54081 | -1.4968 | 50.73775 |
August | 744.00000 | 21.04930 | 53.83779 | -1.4885 | 50.28921 |
September | 720.00000 | 21.07289 | 49.53367 | -1.4964 | 50.74195 |
October | 744.00000 | 21.09219 | 43.56982 | -0.3394 | 7.45921 |
November | 720.00000 | 21.10516 | 38.66087 | -0.3641 | 7.83604 |
December | 744.00000 | 21.08661 | 33.36295 | -0.4034 | 8.44107 |
Annual Sum or Average | 8760.00000 | 21.05747 | 42.14270 | -0.8656 | 26.55518 |
Minimum of Months | 672.00000 | 21.02970 | 33.36295 | -1.5781 | 7.45921 |
Maximum of Months | 744.00000 | 21.10516 | 53.83779 | -0.3394 | 55.15026 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_1_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.94744 | 33.26064 | -0.4997 | 10.60634 |
February | 672.00000 | 20.98582 | 34.16560 | -0.4620 | 9.84374 |
March | 744.00000 | 20.98715 | 33.93491 | -0.4801 | 9.96819 |
April | 720.00000 | 21.03777 | 34.41338 | -0.3482 | 8.06043 |
May | 744.00000 | 21.00934 | 41.22413 | -1.4924 | 50.64538 |
June | 720.00000 | 21.00618 | 50.36561 | -1.3990 | 45.66606 |
July | 744.00000 | 21.01787 | 52.67676 | -1.3529 | 43.33066 |
August | 744.00000 | 21.05640 | 52.88425 | -1.3186 | 41.78949 |
September | 720.00000 | 21.11526 | 48.45245 | -1.3362 | 43.15693 |
October | 744.00000 | 21.03479 | 42.75916 | -0.3539 | 8.02327 |
November | 720.00000 | 20.98331 | 37.93257 | -0.4556 | 9.58927 |
December | 744.00000 | 20.87553 | 32.73684 | -0.5605 | 11.85565 |
Annual Sum or Average | 8760.00000 | 21.00456 | 41.27489 | -0.8408 | 24.47286 |
Minimum of Months | 672.00000 | 20.87553 | 32.73684 | -1.4924 | 8.02327 |
Maximum of Months | 744.00000 | 21.11526 | 52.88425 | -0.3482 | 50.64538 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_2_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.00387 | 34.53269 | -0.4167 | 8.67766 |
February | 672.00000 | 21.00559 | 35.48092 | -0.4059 | 8.46029 |
March | 744.00000 | 21.00854 | 35.26643 | -0.4051 | 8.45998 |
April | 720.00000 | 21.04426 | 35.74405 | -0.3662 | 7.88958 |
May | 744.00000 | 21.04993 | 42.47780 | -1.4981 | 50.82013 |
June | 720.00000 | 21.07541 | 51.51056 | -1.4215 | 46.70987 |
July | 744.00000 | 21.08770 | 53.79819 | -1.3978 | 45.46131 |
August | 744.00000 | 21.08760 | 54.13931 | -1.3940 | 45.23961 |
September | 720.00000 | 21.06753 | 49.93909 | -1.4323 | 47.31149 |
October | 744.00000 | 21.02187 | 44.12297 | -0.3361 | 7.39210 |
November | 720.00000 | 21.00621 | 39.24371 | -0.3845 | 8.13238 |
December | 744.00000 | 21.00118 | 33.86816 | -0.4318 | 8.91898 |
Annual Sum or Average | 8760.00000 | 21.03847 | 42.55058 | -0.8268 | 24.55411 |
Minimum of Months | 672.00000 | 21.00118 | 33.86816 | -1.4981 | 7.39210 |
Maximum of Months | 744.00000 | 21.08770 | 54.13931 | -0.3361 | 50.82013 |
Report: OccupantComfortDataSummaryMonthly
For: LAUNDRY_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.43420 | 31.55631 | 0.27266 | 9.18529 |
February | 672.00000 | 21.43427 | 32.48547 | 0.28143 | 9.28571 |
March | 744.00000 | 21.43732 | 32.23004 | 0.28969 | 9.46975 |
April | 720.00000 | 21.40472 | 32.82967 | 0.31337 | 9.68061 |
May | 744.00000 | 21.40667 | 39.43772 | -0.5271 | 16.05351 |
June | 720.00000 | 21.39815 | 48.38503 | -0.4565 | 14.52854 |
July | 744.00000 | 21.37959 | 50.72411 | -0.4435 | 14.02266 |
August | 744.00000 | 21.40155 | 50.99642 | -0.4299 | 14.01144 |
September | 720.00000 | 21.40791 | 46.78269 | -0.4680 | 14.79203 |
October | 744.00000 | 21.42405 | 40.95051 | 0.34947 | 10.16267 |
November | 720.00000 | 21.43461 | 36.11698 | 0.30686 | 9.65776 |
December | 744.00000 | 21.43267 | 30.89376 | 0.26087 | 9.03669 |
Annual Sum or Average | 8760.00000 | 21.41621 | 39.48898 | -0.0228 | 11.67115 |
Minimum of Months | 672.00000 | 21.37959 | 30.89376 | -0.5271 | 9.03669 |
Maximum of Months | 744.00000 | 21.43732 | 50.99642 | 0.34947 | 16.05351 |
Report: OccupantComfortDataSummaryMonthly
For: CAFE_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.00226 | 35.59898 | -0.3839 | 8.34854 |
February | 672.00000 | 21.01268 | 36.53295 | -0.3529 | 7.88887 |
March | 744.00000 | 21.00257 | 36.33592 | -0.3738 | 8.01717 |
April | 720.00000 | 21.02281 | 36.85842 | -0.2562 | 6.78401 |
May | 744.00000 | 21.00427 | 43.64910 | -1.3688 | 44.09335 |
June | 720.00000 | 21.00367 | 52.76286 | -1.2820 | 39.58763 |
July | 744.00000 | 21.00658 | 55.09147 | -1.2397 | 37.53095 |
August | 744.00000 | 21.02482 | 55.37202 | -1.2086 | 36.16853 |
September | 720.00000 | 21.07274 | 50.96153 | -1.2235 | 37.33907 |
October | 744.00000 | 21.02395 | 45.17744 | -0.2565 | 6.68858 |
November | 720.00000 | 21.00297 | 40.31504 | -0.3476 | 7.71946 |
December | 744.00000 | 20.99110 | 34.93896 | -0.4303 | 9.04312 |
Annual Sum or Average | 8760.00000 | 21.01409 | 43.67380 | -0.7295 | 20.85039 |
Minimum of Months | 672.00000 | 20.99110 | 34.93896 | -1.3688 | 6.68858 |
Maximum of Months | 744.00000 | 21.07274 | 55.37202 | -0.2562 | 44.09335 |
Report: OccupantComfortDataSummaryMonthly
For: LOBBY_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.01207 | 35.83835 | -0.3760 | 8.01452 |
February | 672.00000 | 21.01470 | 36.78126 | -0.3630 | 7.78037 |
March | 744.00000 | 21.01902 | 36.57010 | -0.3650 | 7.81860 |
April | 720.00000 | 21.05333 | 37.04941 | -0.3172 | 7.18985 |
May | 744.00000 | 21.06013 | 43.77446 | -1.4362 | 47.48952 |
June | 720.00000 | 21.09448 | 52.76736 | -1.3561 | 43.24841 |
July | 744.00000 | 21.11262 | 55.02992 | -1.3275 | 41.76874 |
August | 744.00000 | 21.12233 | 55.35222 | -1.3164 | 41.17691 |
September | 720.00000 | 21.09788 | 51.16502 | -1.3531 | 43.12634 |
October | 744.00000 | 21.03652 | 45.39680 | -0.2885 | 6.77902 |
November | 720.00000 | 21.01732 | 40.53865 | -0.3425 | 7.50365 |
December | 744.00000 | 21.00763 | 35.16768 | -0.3942 | 8.27822 |
Annual Sum or Average | 8760.00000 | 21.05420 | 43.82604 | -0.7722 | 22.60545 |
Minimum of Months | 672.00000 | 21.00763 | 35.16768 | -1.4362 | 6.77902 |
Maximum of Months | 744.00000 | 21.12233 | 55.35222 | -0.2885 | 47.48952 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.87506 | 40.81248 | -0.5329 | 11.46644 |
February | 672.00000 | 21.01099 | 41.44099 | -0.4753 | 10.26135 |
March | 744.00000 | 20.95427 | 41.42983 | -0.4872 | 10.20430 |
April | 720.00000 | 21.50820 | 40.58007 | -0.2531 | 7.32898 |
May | 744.00000 | 21.49860 | 46.47286 | -1.3494 | 43.89040 |
June | 720.00000 | 21.61267 | 52.50327 | -1.2220 | 37.72054 |
July | 744.00000 | 21.64289 | 53.22628 | -1.1835 | 36.00391 |
August | 744.00000 | 21.64837 | 53.78535 | -1.1831 | 36.00931 |
September | 720.00000 | 21.60391 | 51.62791 | -1.2502 | 39.22223 |
October | 744.00000 | 21.21730 | 49.35431 | -0.3343 | 7.97714 |
November | 720.00000 | 20.92692 | 45.39799 | -0.4848 | 10.33597 |
December | 744.00000 | 20.68403 | 40.78735 | -0.6107 | 13.24588 |
Annual Sum or Average | 8760.00000 | 21.26574 | 46.48095 | -0.7828 | 22.05005 |
Minimum of Months | 672.00000 | 20.68403 | 40.58007 | -1.3494 | 7.32898 |
Maximum of Months | 744.00000 | 21.64837 | 53.78535 | -0.2531 | 43.89040 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.67223 | 41.26322 | -0.6036 | 13.09608 |
February | 672.00000 | 20.77563 | 41.95598 | -0.5560 | 11.77175 |
March | 744.00000 | 20.85170 | 41.65131 | -0.5227 | 10.92923 |
April | 720.00000 | 21.33755 | 40.95298 | -0.3211 | 7.80124 |
May | 744.00000 | 21.39729 | 46.76085 | -1.4053 | 46.45541 |
June | 720.00000 | 21.55959 | 52.76562 | -1.2547 | 39.04028 |
July | 744.00000 | 21.59245 | 53.65333 | -1.2199 | 37.42763 |
August | 744.00000 | 21.56321 | 54.70448 | -1.2453 | 38.52813 |
September | 720.00000 | 21.43880 | 52.76345 | -1.3553 | 43.85103 |
October | 744.00000 | 21.02274 | 49.86560 | -0.4059 | 8.72640 |
November | 720.00000 | 20.74531 | 45.82413 | -0.5460 | 11.57758 |
December | 744.00000 | 20.55341 | 41.09066 | -0.6548 | 14.46464 |
Annual Sum or Average | 8760.00000 | 21.12712 | 46.96610 | -0.8429 | 23.71552 |
Minimum of Months | 672.00000 | 20.55341 | 40.95298 | -1.4053 | 7.80124 |
Maximum of Months | 744.00000 | 21.59245 | 54.70448 | -0.3211 | 46.45541 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT19_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 0.00000 | ||||
Minimum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_4_MULT19_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.00956 | 39.31170 | -0.4619 | 9.65603 |
February | 672.00000 | 21.05401 | 40.12306 | -0.4408 | 9.10551 |
March | 744.00000 | 21.16173 | 39.62454 | -0.3987 | 8.37612 |
April | 720.00000 | 21.33921 | 39.55758 | -0.3310 | 7.44380 |
May | 744.00000 | 21.38537 | 45.17421 | -1.4376 | 47.64479 |
June | 720.00000 | 21.48207 | 50.81475 | -1.3429 | 42.80827 |
July | 744.00000 | 21.49859 | 52.01907 | -1.3229 | 41.80110 |
August | 744.00000 | 21.43253 | 52.60316 | -1.3520 | 43.20893 |
September | 720.00000 | 21.37362 | 50.52211 | -1.4091 | 46.14980 |
October | 744.00000 | 21.22032 | 47.47956 | -0.3299 | 7.32110 |
November | 720.00000 | 21.07968 | 43.61617 | -0.4077 | 8.56676 |
December | 744.00000 | 20.96175 | 39.02221 | -0.4840 | 10.00934 |
Annual Sum or Average | 8760.00000 | 21.25073 | 45.01653 | -0.8122 | 23.59603 |
Minimum of Months | 672.00000 | 20.96175 | 39.02221 | -1.4376 | 7.32110 |
Maximum of Months | 744.00000 | 21.49859 | 52.60316 | -0.3299 | 47.64479 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_5_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.87037 | 40.81662 | -0.5329 | 11.44515 |
February | 672.00000 | 20.99907 | 41.44969 | -0.4829 | 10.28111 |
March | 744.00000 | 20.98233 | 41.36536 | -0.4814 | 10.10279 |
April | 720.00000 | 21.61740 | 40.41145 | -0.2162 | 7.11036 |
May | 744.00000 | 21.59056 | 46.10919 | -1.3166 | 42.37519 |
June | 720.00000 | 21.65726 | 52.19323 | -1.2161 | 37.50461 |
July | 744.00000 | 21.69381 | 52.91346 | -1.1733 | 35.56916 |
August | 744.00000 | 21.68702 | 53.19258 | -1.1643 | 35.24976 |
September | 720.00000 | 21.67191 | 51.12898 | -1.2123 | 37.53903 |
October | 744.00000 | 21.25815 | 49.20262 | -0.3223 | 7.88274 |
November | 720.00000 | 20.92094 | 45.40903 | -0.4854 | 10.29723 |
December | 744.00000 | 20.70049 | 40.74256 | -0.6018 | 13.02677 |
Annual Sum or Average | 8760.00000 | 21.30483 | 46.27256 | -0.7693 | 21.60714 |
Minimum of Months | 672.00000 | 20.70049 | 40.41145 | -1.3166 | 7.11036 |
Maximum of Months | 744.00000 | 21.69381 | 53.19258 | -0.2162 | 42.37519 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_6_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.67198 | 41.25779 | -0.6026 | 13.06797 |
February | 672.00000 | 20.75218 | 41.98671 | -0.5666 | 11.98943 |
March | 744.00000 | 20.88260 | 41.57097 | -0.5163 | 10.77905 |
April | 720.00000 | 21.51236 | 40.59478 | -0.2708 | 7.34770 |
May | 744.00000 | 21.53444 | 46.29177 | -1.3602 | 44.26604 |
June | 720.00000 | 21.63336 | 52.39523 | -1.2409 | 38.48016 |
July | 744.00000 | 21.68110 | 53.26974 | -1.1994 | 36.56151 |
August | 744.00000 | 21.66612 | 53.91025 | -1.2078 | 36.97149 |
September | 720.00000 | 21.60951 | 51.85778 | -1.2880 | 40.70514 |
October | 744.00000 | 21.08904 | 49.67394 | -0.3883 | 8.46882 |
November | 720.00000 | 20.73821 | 45.83581 | -0.5468 | 11.58136 |
December | 744.00000 | 20.56938 | 41.04455 | -0.6461 | 14.23085 |
Annual Sum or Average | 8760.00000 | 21.19671 | 46.66774 | -0.8214 | 22.94206 |
Minimum of Months | 672.00000 | 20.56938 | 40.59478 | -1.3602 | 7.34770 |
Maximum of Months | 744.00000 | 21.68110 | 53.91025 | -0.2708 | 44.26604 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.76333 | 41.55657 | -0.5974 | 13.11880 |
February | 672.00000 | 20.90290 | 42.17155 | -0.5337 | 11.64028 |
March | 744.00000 | 20.86332 | 42.16738 | -0.5377 | 11.39414 |
April | 720.00000 | 21.50528 | 41.01994 | -0.2578 | 7.71498 |
May | 744.00000 | 21.50094 | 46.95529 | -1.3500 | 44.23786 |
June | 720.00000 | 21.62907 | 52.77685 | -1.2024 | 37.17246 |
July | 744.00000 | 21.65867 | 53.41533 | -1.1583 | 35.22282 |
August | 744.00000 | 21.65702 | 54.02167 | -1.1635 | 35.47960 |
September | 720.00000 | 21.60675 | 52.15922 | -1.2480 | 39.46430 |
October | 744.00000 | 21.14843 | 50.28613 | -0.3708 | 8.72508 |
November | 720.00000 | 20.81402 | 46.29576 | -0.5437 | 11.73432 |
December | 744.00000 | 20.59232 | 41.47143 | -0.6737 | 15.03029 |
Annual Sum or Average | 8760.00000 | 21.22093 | 47.05328 | -0.8052 | 22.65199 |
Minimum of Months | 672.00000 | 20.59232 | 41.01994 | -1.3500 | 7.71498 |
Maximum of Months | 744.00000 | 21.65867 | 54.02167 | -0.2578 | 44.23786 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.57895 | 42.00170 | -0.6658 | 14.85383 |
February | 672.00000 | 20.65950 | 42.72806 | -0.6180 | 13.41404 |
March | 744.00000 | 20.75407 | 42.41441 | -0.5753 | 12.24593 |
April | 720.00000 | 21.35297 | 41.37085 | -0.3251 | 8.15350 |
May | 744.00000 | 21.41759 | 47.22439 | -1.4032 | 46.61602 |
June | 720.00000 | 21.59896 | 53.00514 | -1.2298 | 38.22438 |
July | 744.00000 | 21.63341 | 53.82437 | -1.1887 | 36.34471 |
August | 744.00000 | 21.61009 | 54.88897 | -1.2172 | 37.57154 |
September | 720.00000 | 21.46693 | 53.33250 | -1.3503 | 43.85934 |
October | 744.00000 | 20.94642 | 50.83937 | -0.4468 | 9.61086 |
November | 720.00000 | 20.62988 | 46.74893 | -0.6066 | 13.17670 |
December | 744.00000 | 20.49329 | 41.71939 | -0.7127 | 16.21330 |
Annual Sum or Average | 8760.00000 | 21.09692 | 47.53534 | -0.8635 | 24.26069 |
Minimum of Months | 672.00000 | 20.49329 | 41.37085 | -1.4032 | 8.15350 |
Maximum of Months | 744.00000 | 21.63341 | 54.88897 | -0.3251 | 46.61602 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT9_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.15767 | 41.11465 | -0.4310 | 9.98590 |
February | 672.00000 | 21.25519 | 41.76864 | -0.3853 | 9.09767 |
March | 744.00000 | 21.15053 | 41.74637 | -0.4300 | 9.29721 |
April | 720.00000 | 21.60942 | 41.16497 | -0.2093 | 7.27475 |
May | 744.00000 | 21.56707 | 46.83909 | -1.3355 | 43.48957 |
June | 720.00000 | 21.63666 | 52.52755 | -1.2385 | 38.71588 |
July | 744.00000 | 21.66428 | 53.06111 | -1.1946 | 36.76081 |
August | 744.00000 | 21.66426 | 52.85606 | -1.1701 | 35.83448 |
September | 720.00000 | 21.66480 | 50.59927 | -1.1901 | 37.01282 |
October | 744.00000 | 21.38310 | 49.28881 | -0.2638 | 7.52870 |
November | 720.00000 | 21.17584 | 45.53933 | -0.3961 | 9.11384 |
December | 744.00000 | 20.95447 | 41.08121 | -0.5231 | 11.58945 |
Annual Sum or Average | 8760.00000 | 21.40693 | 46.49332 | -0.7332 | 21.38993 |
Minimum of Months | 672.00000 | 20.95447 | 41.08121 | -1.3355 | 7.27475 |
Maximum of Months | 744.00000 | 21.66480 | 53.06111 | -0.2093 | 43.48957 |
Report: OccupantComfortDataSummaryMonthly
For: BANQUET_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.35818 | 36.75836 | -0.2509 | 6.61145 |
February | 672.00000 | 21.37042 | 37.66685 | -0.2347 | 6.37891 |
March | 744.00000 | 21.44943 | 37.34007 | -0.2009 | 6.10449 |
April | 720.00000 | 21.54937 | 37.68318 | -0.1391 | 5.70167 |
May | 744.00000 | 21.61700 | 44.08814 | -1.1533 | 33.42186 |
June | 720.00000 | 21.74341 | 52.56755 | -1.0283 | 27.82021 |
July | 744.00000 | 21.76189 | 54.72652 | -0.9995 | 26.63157 |
August | 744.00000 | 21.72538 | 55.19160 | -1.0188 | 27.38062 |
September | 720.00000 | 21.60777 | 51.37300 | -1.1103 | 31.44502 |
October | 744.00000 | 21.48388 | 45.89658 | -0.1302 | 5.62886 |
November | 720.00000 | 21.41483 | 41.24827 | -0.1970 | 6.14183 |
December | 744.00000 | 21.34277 | 36.10714 | -0.2648 | 6.70359 |
Annual Sum or Average | 8760.00000 | 21.53624 | 44.25806 | -0.5627 | 15.88720 |
Minimum of Months | 672.00000 | 21.34277 | 36.10714 | -1.1533 | 5.62886 |
Maximum of Months | 744.00000 | 21.76189 | 55.19160 | -0.1302 | 33.42186 |
Report: OccupantComfortDataSummaryMonthly
For: DINING_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.40965 | 36.42933 | -0.2056 | 6.21621 |
February | 672.00000 | 21.42479 | 37.33252 | -0.1891 | 6.00812 |
March | 744.00000 | 21.51249 | 36.98831 | -0.1529 | 5.78523 |
April | 720.00000 | 21.62513 | 37.30507 | -0.0892 | 5.49325 |
May | 744.00000 | 21.70044 | 43.66285 | -1.0797 | 30.10541 |
June | 720.00000 | 21.83972 | 52.06331 | -0.9503 | 24.64042 |
July | 744.00000 | 21.86358 | 54.19345 | -0.9202 | 23.47109 |
August | 744.00000 | 21.81469 | 54.69249 | -0.9438 | 24.33742 |
September | 720.00000 | 21.68299 | 50.93413 | -1.0402 | 28.37295 |
October | 744.00000 | 21.54801 | 45.51296 | -0.0827 | 5.44939 |
November | 720.00000 | 21.47329 | 40.89006 | -0.1503 | 5.84060 |
December | 744.00000 | 21.39201 | 35.78613 | -0.2196 | 6.28156 |
Annual Sum or Average | 8760.00000 | 21.60820 | 43.85293 | -0.5039 | 14.38268 |
Minimum of Months | 672.00000 | 21.39201 | 35.78613 | -1.0797 | 5.44939 |
Maximum of Months | 744.00000 | 21.86358 | 54.69249 | -0.0827 | 30.10541 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.63522 | 35.66377 | 0.69013 | 19.85393 |
February | 672.00000 | 22.68392 | 36.39242 | 0.71594 | 20.80587 |
March | 744.00000 | 22.72352 | 36.09627 | 0.73939 | 21.50267 |
April | 720.00000 | 22.94917 | 36.16667 | 0.86410 | 26.64564 |
May | 744.00000 | 22.96738 | 42.01299 | 0.24604 | 18.12934 |
June | 720.00000 | 23.02794 | 49.72593 | 0.35566 | 19.64257 |
July | 744.00000 | 23.05301 | 51.71168 | 0.39447 | 20.31558 |
August | 744.00000 | 23.04962 | 51.97355 | 0.39265 | 20.35542 |
September | 720.00000 | 23.00191 | 48.35886 | 0.31912 | 19.29420 |
October | 744.00000 | 22.80984 | 43.71574 | 0.83269 | 24.81409 |
November | 720.00000 | 22.67425 | 39.76378 | 0.73680 | 21.21853 |
December | 744.00000 | 22.57215 | 35.21186 | 0.65614 | 18.57992 |
Annual Sum or Average | 8760.00000 | 22.84625 | 42.26687 | 0.57757 | 20.92239 |
Minimum of Months | 672.00000 | 22.57215 | 35.21186 | 0.24604 | 18.12934 |
Maximum of Months | 744.00000 | 23.05301 | 51.97355 | 0.86410 | 26.64564 |
Report: OccupantComfortDataSummaryMonthly
For: STORAGE_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.00005 | 32.90425 | -0.4893 | 10.05886 |
February | 672.00000 | 21.00013 | 33.85261 | -0.4810 | 9.85312 |
March | 744.00000 | 21.00014 | 33.66118 | -0.4746 | 9.73253 |
April | 720.00000 | 21.00014 | 34.20332 | -0.4548 | 9.37515 |
May | 744.00000 | 21.00011 | 40.98647 | -1.6170 | 57.26274 |
June | 720.00000 | 21.00056 | 50.16412 | -1.5447 | 53.33585 |
July | 744.00000 | 21.00101 | 52.51565 | -1.5246 | 52.24161 |
August | 744.00000 | 21.00017 | 52.83877 | -1.5244 | 52.23000 |
September | 720.00000 | 21.00012 | 48.58044 | -1.5607 | 54.22690 |
October | 744.00000 | 21.00013 | 42.58591 | -0.4130 | 8.58758 |
November | 720.00000 | 21.00015 | 37.63356 | -0.4543 | 9.35478 |
December | 744.00000 | 21.00014 | 32.25129 | -0.4981 | 10.20822 |
Annual Sum or Average | 8760.00000 | 21.00024 | 41.05580 | -0.9224 | 28.14969 |
Minimum of Months | 672.00000 | 21.00005 | 32.25129 | -1.6170 | 8.58758 |
Maximum of Months | 744.00000 | 21.00101 | 52.83877 | -0.4130 | 57.26274 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_FLR_3 PEOPLE
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.00043 | 35.14460 | -0.4751 | 9.76278 |
February | 672.00000 | 21.00042 | 36.08490 | -0.4639 | 9.51005 |
March | 744.00000 | 21.00039 | 35.90523 | -0.4636 | 9.51277 |
April | 720.00000 | 21.02518 | 36.35149 | -0.4292 | 8.90837 |
May | 744.00000 | 21.02387 | 43.12250 | -1.5903 | 55.81666 |
June | 720.00000 | 21.05758 | 52.15483 | -1.5158 | 51.76790 |
July | 744.00000 | 21.11695 | 54.30057 | -1.4786 | 49.76482 |
August | 744.00000 | 21.11076 | 54.65412 | -1.4774 | 49.68733 |
September | 720.00000 | 21.08722 | 50.49297 | -1.5139 | 51.69078 |
October | 744.00000 | 21.00620 | 44.76398 | -0.3980 | 8.32612 |
November | 720.00000 | 21.00041 | 39.85830 | -0.4441 | 9.15485 |
December | 744.00000 | 21.00036 | 34.48260 | -0.4906 | 10.05003 |
Annual Sum or Average | 8760.00000 | 21.03603 | 43.14983 | -0.8977 | 27.10267 |
Minimum of Months | 672.00000 | 21.00036 | 34.48260 | -1.5903 | 8.32612 |
Maximum of Months | 744.00000 | 21.11695 | 54.65412 | -0.3980 | 55.81666 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_FLR_6 PEOPLE
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.99985 | 33.46733 | -0.4981 | 10.26713 |
February | 672.00000 | 21.00039 | 34.42074 | -0.4816 | 9.88696 |
March | 744.00000 | 21.00046 | 34.20632 | -0.4744 | 9.74302 |
April | 720.00000 | 21.02039 | 34.71318 | -0.4180 | 8.77681 |
May | 744.00000 | 21.01431 | 41.48071 | -1.5668 | 54.54660 |
June | 720.00000 | 21.02681 | 50.57217 | -1.4807 | 49.89237 |
July | 744.00000 | 21.04221 | 52.86505 | -1.4501 | 48.25386 |
August | 744.00000 | 21.04350 | 53.18602 | -1.4500 | 48.25008 |
September | 720.00000 | 21.02886 | 48.97529 | -1.5015 | 51.04025 |
October | 744.00000 | 21.00210 | 43.10237 | -0.4008 | 8.39882 |
November | 720.00000 | 21.00046 | 38.18268 | -0.4582 | 9.44320 |
December | 744.00000 | 21.00041 | 32.80499 | -0.5152 | 10.58448 |
Annual Sum or Average | 8760.00000 | 21.01505 | 41.53857 | -0.8938 | 26.69254 |
Minimum of Months | 672.00000 | 20.99985 | 32.80499 | -1.5668 | 8.39882 |
Maximum of Months | 744.00000 | 21.04350 | 53.18602 | -0.4008 | 54.54660 |
Report: OccupantComfortDataSummaryMonthly
For: MECH_FLR_1 PEOPLE
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.00007 | 32.63399 | -0.4658 | 9.58517 |
February | 672.00000 | 21.00009 | 33.58532 | -0.4584 | 9.40776 |
March | 744.00000 | 21.00008 | 33.38531 | -0.4522 | 9.30055 |
April | 720.00000 | 21.00283 | 33.92679 | -0.4339 | 8.99223 |
May | 744.00000 | 21.00600 | 40.69518 | -1.5861 | 55.58815 |
June | 720.00000 | 21.02178 | 49.81623 | -1.5104 | 51.47285 |
July | 744.00000 | 21.02946 | 52.14013 | -1.4889 | 50.30888 |
August | 744.00000 | 21.02782 | 52.46850 | -1.4887 | 50.29851 |
September | 720.00000 | 21.01246 | 48.25831 | -1.5287 | 52.49046 |
October | 744.00000 | 21.00015 | 42.30910 | -0.3920 | 8.23621 |
November | 720.00000 | 21.00008 | 37.36069 | -0.4319 | 8.94014 |
December | 744.00000 | 21.00009 | 31.98105 | -0.4740 | 9.71586 |
Annual Sum or Average | 8760.00000 | 21.00847 | 40.75414 | -0.8952 | 27.13513 |
Minimum of Months | 672.00000 | 21.00007 | 31.98105 | -1.5861 | 8.23621 |
Maximum of Months | 744.00000 | 21.02946 | 52.46850 | -0.3920 | 55.58815 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.500455E+10 | 22472.13 | 21-JAN-16:03 | 302.57 | 0.147503E+11 | 0.00 | 0.197549E+11 | 1.20 | 2.95 | 06-JAN-09:05 | 0.00 | 0.00 |
February | 0.529441E+10 | 24598.20 | 09-FEB-16:03 | 300.46 | 0.156053E+11 | 0.00 | 0.208997E+11 | 1.32 | 2.95 | 24-FEB-20:10 | 0.00 | 0.00 |
March | 0.573984E+10 | 22422.81 | 20-MAR-18:02 | 376.63 | 0.169176E+11 | 0.00 | 0.226575E+11 | 1.49 | 2.95 | 08-MAR-19:05 | 0.00 | 0.00 |
April | 0.367272E+11 | 127841.47 | 30-APR-18:03 | 671.21 | 0.115117E+12 | 0.00 | 0.151844E+12 | 2.78 | 4.03 | 29-APR-18:03 | 0.00 | 0.00 |
May | 0.392408E+11 | 125940.75 | 22-MAY-15:03 | 699.39 | 0.121657E+12 | 0.00 | 0.160897E+12 | 2.80 | 4.07 | 22-MAY-18:03 | 0.00 | 0.00 |
June | 0.704460E+11 | 169427.10 | 25-JUN-18:20 | 715.56 | 0.227250E+12 | 0.00 | 0.297696E+12 | 3.01 | 4.35 | 26-JUN-18:03 | 0.00 | 0.00 |
July | 0.999313E+11 | 175531.77 | 22-JUL-18:03 | 743.90 | 0.328192E+12 | 0.00 | 0.428123E+12 | 3.09 | 4.26 | 17-JUL-18:02 | 0.00 | 0.00 |
August | 0.109496E+12 | 147665.75 | 14-AUG-18:03 | 744.00 | 0.364008E+12 | 0.00 | 0.473504E+12 | 3.14 | 4.25 | 16-AUG-18:02 | 0.00 | 0.00 |
September | 0.745081E+11 | 125674.75 | 13-SEP-15:03 | 715.58 | 0.242529E+12 | 0.00 | 0.317037E+12 | 3.03 | 4.23 | 10-SEP-18:02 | 0.00 | 0.00 |
October | 0.201605E+11 | 89495.33 | 07-OCT-15:02 | 586.22 | 0.596110E+11 | 0.00 | 0.797714E+11 | 2.32 | 4.00 | 07-OCT-15:02 | 0.00 | 0.00 |
November | 0.575846E+10 | 26968.99 | 24-NOV-11:50 | 364.17 | 0.169634E+11 | 0.00 | 0.227219E+11 | 1.49 | 2.95 | 01-NOV-00:50 | 0.00 | 0.00 |
December | 0.173023E+10 | 9283.98 | 25-DEC-09:02 | 182.68 | 0.509986E+10 | 0.00 | 0.683010E+10 | 0.72 | 2.95 | 01-DEC-08:00 | 0.00 | 0.00 |
Annual Sum or Average | 0.474038E+12 | 6402.38 | 0.152770E+13 | 0.00 | 0.200174E+13 | 2.20 | 0.00 | 0.00 | ||||
Minimum of Months | 0.173023E+10 | 9283.98 | 182.68 | 0.509986E+10 | 0.00 | 0.683010E+10 | 0.72 | 2.95 | 0.00 | 0.00 | ||
Maximum of Months | 0.109496E+12 | 175531.77 | 744.00 | 0.364008E+12 | 0.00 | 0.473504E+12 | 3.14 | 4.35 | 0.00 | 0.00 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.141449E+12 | 0.00 | 744.00 | 181124.91 | 10-JAN-09:02 | 0.00 | 38.08 | 60.00 | 0.58 | 0.00 | 0.12 | 0.40 | 10-JAN-09:02 |
February | 0.113410E+12 | 0.00 | 672.00 | 124686.34 | 13-FEB-09:02 | 0.00 | 36.99 | 60.00 | 0.50 | 0.00 | 0.10 | 0.28 | 13-FEB-09:02 |
March | 0.119703E+12 | 0.00 | 744.00 | 115676.90 | 04-MAR-16:02 | 0.00 | 37.24 | 60.00 | 0.47 | 0.00 | 0.10 | 0.26 | 04-MAR-16:02 |
April | 0.766344E+11 | 0.00 | 720.00 | 86853.70 | 11-APR-10:35 | 0.00 | 34.26 | 60.00 | 0.28 | 0.00 | 0.07 | 0.19 | 11-APR-10:35 |
May | 0.780615E+11 | 0.00 | 744.00 | 90019.11 | 05-MAY-10:35 | 0.00 | 32.43 | 60.00 | 0.26 | 0.00 | 0.06 | 0.20 | 05-MAY-10:35 |
June | 0.644120E+11 | 0.00 | 720.00 | 88889.83 | 06-JUN-10:35 | 0.00 | 31.19 | 60.00 | 0.22 | 0.00 | 0.06 | 0.20 | 06-JUN-10:35 |
July | 0.603656E+11 | 0.00 | 744.00 | 88642.58 | 03-JUL-10:35 | 0.00 | 30.74 | 60.00 | 0.19 | 0.00 | 0.05 | 0.20 | 03-JUL-10:35 |
August | 0.561626E+11 | 0.00 | 744.00 | 84660.74 | 01-AUG-10:35 | 0.00 | 30.57 | 60.00 | 0.18 | 0.00 | 0.05 | 0.19 | 01-AUG-10:35 |
September | 0.566126E+11 | 0.00 | 720.00 | 86469.58 | 08-SEP-10:40 | 0.00 | 30.97 | 60.00 | 0.19 | 0.00 | 0.05 | 0.19 | 08-SEP-10:40 |
October | 0.902955E+11 | 0.00 | 744.00 | 102972.85 | 19-OCT-08:03 | 0.00 | 34.37 | 60.00 | 0.33 | 0.00 | 0.07 | 0.23 | 19-OCT-08:03 |
November | 0.114621E+12 | 0.00 | 720.00 | 119859.29 | 29-NOV-09:02 | 0.00 | 36.73 | 60.00 | 0.46 | 0.00 | 0.10 | 0.27 | 29-NOV-09:02 |
December | 0.151264E+12 | 0.00 | 744.00 | 147074.25 | 27-DEC-09:03 | 0.00 | 38.25 | 60.00 | 0.63 | 0.00 | 0.13 | 0.33 | 27-DEC-09:03 |
Annual Sum or Average | 0.112299E+13 | 0.00 | 8760.00 | 0.00 | 34.31 | 60.00 | 0.36 | 0.00 | 0.08 | ||||
Minimum of Months | 0.561626E+11 | 0.00 | 672.00 | 84660.74 | 0.00 | 30.57 | 60.00 | 0.18 | 0.00 | 0.05 | 0.19 | ||
Maximum of Months | 0.151264E+12 | 0.00 | 744.00 | 181124.91 | 0.00 | 38.25 | 60.00 | 0.63 | 0.00 | 0.13 | 0.40 |
Report: DXReportMonthly
For: VAV WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 6818783.35 | 0.00 | 0.50 | 6818783.35 | 0.00 | 0.00 | 0.00 | 0.00 | 6819.07 | 29-JAN-06:00 | 6819.07 | 29-JAN-06:00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 |
March | 4067563.16 | 0.00 | 0.82 | 4067563.16 | 0.00 | 0.00 | 0.00 | 0.00 | 6762.51 | 25-MAR-13:00 | 6762.51 | 25-MAR-13:00 | 0.00 | 0.00 | 0.00 |
April | 0.309439E+11 | 0.00 | 85.41 | 0.308306E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 279294.24 | 30-APR-18:10 | 279294.24 | 30-APR-18:10 | 0.00 | 0.00 | 0.00 |
May | 0.333113E+11 | 0.00 | 105.02 | 0.333113E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 257668.21 | 22-MAY-15:30 | 257668.21 | 22-MAY-15:30 | 0.00 | 0.00 | 0.00 |
June | 0.103271E+12 | 0.00 | 300.66 | 0.969350E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 487407.05 | 25-JUN-18:17 | 305733.29 | 12-JUN-18:10 | 0.00 | 0.00 | 0.00 |
July | 0.177173E+12 | 0.00 | 457.83 | 0.169732E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 380312.18 | 22-JUL-10:35 | 343556.89 | 22-JUL-18:10 | 0.00 | 0.00 | 0.00 |
August | 0.210060E+12 | 0.00 | 531.92 | 0.201853E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 349922.15 | 14-AUG-10:35 | 322923.68 | 14-AUG-17:08 | 0.00 | 0.00 | 0.00 |
September | 0.113591E+12 | 0.00 | 339.67 | 0.110409E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 293907.01 | 10-SEP-16:00 | 260576.17 | 11-SEP-17:13 | 0.00 | 0.00 | 0.00 |
October | 0.809054E+10 | 0.00 | 55.97 | 0.809054E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 149490.71 | 07-OCT-15:20 | 149490.71 | 07-OCT-15:20 | 0.00 | 0.00 | 0.00 |
November | 0.223888E+09 | 0.00 | 2.50 | 0.223888E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 68230.25 | 24-NOV-11:50 | 68230.25 | 24-NOV-11:50 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.676676E+12 | 0.00 | 1880.29 | 0.651396E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.210060E+12 | 0.00 | 531.92 | 0.201853E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 487407.05 | 343556.89 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: FLR_3_DOAS COOLING COIL
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 |
April | 0.246108E+10 | 0.00 | 59.17 | 0.245921E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28621.53 | 30-APR-18:02 | 28621.53 | 30-APR-18:02 | 0.00 | 0.00 | 0.00 |
May | 0.246348E+10 | 0.00 | 71.33 | 0.246348E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28400.77 | 22-MAY-15:00 | 28400.77 | 22-MAY-15:00 | 0.00 | 0.00 | 0.00 |
June | 0.833263E+10 | 0.00 | 198.50 | 0.762647E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45838.53 | 25-JUN-18:00 | 30131.67 | 13-JUN-15:02 | 0.00 | 0.00 | 0.00 |
July | 0.147069E+11 | 0.00 | 353.83 | 0.139146E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 34524.85 | 23-JUL-16:00 | 31124.00 | 22-JUL-15:00 | 0.00 | 0.00 | 0.00 |
August | 0.178711E+11 | 0.00 | 428.83 | 0.169080E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 34502.27 | 17-AUG-15:00 | 29172.51 | 14-AUG-15:02 | 0.00 | 0.00 | 0.00 |
September | 0.919189E+10 | 0.00 | 248.83 | 0.876880E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32609.72 | 12-SEP-14:00 | 27620.04 | 13-SEP-15:02 | 0.00 | 0.00 | 0.00 |
October | 0.434540E+09 | 0.00 | 26.50 | 0.434540E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15105.80 | 07-OCT-15:00 | 15105.80 | 07-OCT-15:00 | 0.00 | 0.00 | 0.00 |
November | 6967953.45 | 0.00 | 1.17 | 6967953.45 | 0.00 | 0.00 | 0.00 | 0.00 | 4049.57 | 24-NOV-12:00 | 4049.57 | 24-NOV-12:00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.554687E+11 | 0.00 | 1388.17 | 0.525820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.178711E+11 | 0.00 | 428.83 | 0.169080E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 45838.53 | 31124.00 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 49961726.72 | 0.00 | 12.24 | 27665834.08 | 0.00 | 0.00 | 0.00 | 0.00 | 13848.27 | 25-JAN-16:01 | 13848.27 | 25-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.251777E+09 | 0.00 | 44.43 | 0.223900E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17442.06 | 09-FEB-16:01 | 17442.06 | 09-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.148833E+09 | 0.00 | 35.41 | 0.125953E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17019.93 | 20-MAR-18:02 | 17019.93 | 20-MAR-18:02 | 0.00 | 0.00 | 0.00 |
April | 0.310788E+10 | 0.00 | 369.98 | 0.235885E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17443.39 | 16-APR-18:01 | 17443.39 | 16-APR-18:01 | 0.00 | 0.00 | 0.00 |
May | 0.366562E+10 | 0.00 | 417.38 | 0.242128E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17442.63 | 29-MAY-18:02 | 17442.63 | 29-MAY-18:02 | 0.00 | 0.00 | 0.00 |
June | 0.541757E+10 | 0.00 | 557.44 | 0.314633E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19084.52 | 27-JUN-08:62 | 17441.59 | 08-JUN-18:02 | 0.00 | 0.00 | 0.00 |
July | 0.677845E+10 | 0.00 | 598.73 | 0.395179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18424.54 | 18-JUL-15:02 | 16859.16 | 28-JUL-18:01 | 0.00 | 0.00 | 0.00 |
August | 0.631989E+10 | 0.00 | 646.92 | 0.348576E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19014.40 | 11-AUG-15:01 | 17045.65 | 27-AUG-18:02 | 0.00 | 0.00 | 0.00 |
September | 0.463672E+10 | 0.00 | 520.23 | 0.261315E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18403.18 | 19-SEP-15:02 | 17441.33 | 29-SEP-18:01 | 0.00 | 0.00 | 0.00 |
October | 0.110357E+10 | 0.00 | 176.24 | 0.707337E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17438.84 | 07-OCT-15:02 | 17438.84 | 07-OCT-15:02 | 0.00 | 0.00 | 0.00 |
November | 62416711.75 | 0.00 | 18.04 | 40049363.14 | 0.00 | 0.00 | 0.00 | 0.00 | 17371.64 | 03-NOV-15:01 | 17371.64 | 03-NOV-15:01 | 0.00 | 0.00 | 0.00 |
December | 1333379.28 | 0.00 | 0.39 | 727366.99 | 0.00 | 0.00 | 0.00 | 0.00 | 1758.17 | 20-DEC-19:05 | 1384.32 | 18-DEC-19:05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.315440E+11 | 0.00 | 3397.44 | 0.191028E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 1333379.28 | 0.00 | 0.39 | 727366.99 | 0.00 | 0.00 | 0.00 | 0.00 | 1758.17 | 1384.32 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.677845E+10 | 0.00 | 646.92 | 0.395179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19084.52 | 17443.39 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 6353835.19 | 0.00 | 2.28 | 2612811.09 | 0.00 | 0.00 | 0.00 | 0.00 | 10034.87 | 19-JAN-16:01 | 9265.00 | 19-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 70422738.66 | 0.00 | 16.49 | 61249054.75 | 0.00 | 0.00 | 0.00 | 0.00 | 14748.13 | 19-FEB-16:02 | 14748.13 | 19-FEB-16:02 | 0.00 | 0.00 | 0.00 |
March | 77928660.08 | 0.00 | 21.93 | 68066188.26 | 0.00 | 0.00 | 0.00 | 0.00 | 14838.60 | 20-MAR-18:02 | 14838.60 | 20-MAR-18:02 | 0.00 | 0.00 | 0.00 |
April | 0.195476E+10 | 0.00 | 261.40 | 0.148247E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15607.82 | 17-APR-15:02 | 15607.82 | 17-APR-15:02 | 0.00 | 0.00 | 0.00 |
May | 0.287266E+10 | 0.00 | 344.44 | 0.194040E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15607.24 | 29-MAY-18:02 | 15607.24 | 29-MAY-18:02 | 0.00 | 0.00 | 0.00 |
June | 0.478536E+10 | 0.00 | 514.48 | 0.286091E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17046.44 | 27-JUN-08:62 | 15606.45 | 08-JUN-18:02 | 0.00 | 0.00 | 0.00 |
July | 0.584941E+10 | 0.00 | 556.33 | 0.346332E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16557.58 | 18-JUL-15:02 | 15242.93 | 24-JUL-15:02 | 0.00 | 0.00 | 0.00 |
August | 0.470072E+10 | 0.00 | 567.32 | 0.255919E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16878.89 | 11-AUG-18:02 | 15173.47 | 19-AUG-15:02 | 0.00 | 0.00 | 0.00 |
September | 0.266203E+10 | 0.00 | 386.44 | 0.144750E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16248.04 | 02-SEP-18:02 | 15603.91 | 29-SEP-15:01 | 0.00 | 0.00 | 0.00 |
October | 0.429624E+09 | 0.00 | 80.18 | 0.290441E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15602.71 | 07-OCT-15:02 | 15602.71 | 07-OCT-15:02 | 0.00 | 0.00 | 0.00 |
November | 11172250.42 | 0.00 | 4.28 | 7899018.29 | 0.00 | 0.00 | 0.00 | 0.00 | 8992.55 | 10-NOV-16:02 | 8808.01 | 10-NOV-16:02 | 0.00 | 0.00 | 0.00 |
December | 100458.08 | 0.00 | 0.08 | 30120.70 | 0.00 | 0.00 | 0.00 | 0.00 | 858.75 | 02-DEC-09:05 | 206.31 | 02-DEC-09:05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.234205E+11 | 0.00 | 2755.66 | 0.141841E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 100458.08 | 0.00 | 0.08 | 30120.70 | 0.00 | 0.00 | 0.00 | 0.00 | 858.75 | 206.31 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.584941E+10 | 0.00 | 567.32 | 0.346332E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17046.44 | 15607.82 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.483953E+10 | 0.00 | 116.85 | 0.443967E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40129.05 | 21-JAN-11:25 | 40129.05 | 21-JAN-11:25 | 0.00 | 0.00 | 0.00 |
February | 0.518336E+10 | 0.00 | 128.17 | 0.490526E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35724.21 | 04-FEB-14:00 | 35724.21 | 04-FEB-14:00 | 0.00 | 0.00 | 0.00 |
March | 0.266107E+09 | 0.00 | 25.46 | 0.218088E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12965.78 | 25-MAR-11:40 | 12965.78 | 25-MAR-11:40 | 0.00 | 0.00 | 0.00 |
April | 0.279663E+11 | 0.00 | 444.39 | 0.259005E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 50667.71 | 30-APR-12:30 | 50460.94 | 30-APR-12:30 | 0.00 | 0.00 | 0.00 |
May | 0.219573E+11 | 0.00 | 426.04 | 0.152986E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 41368.51 | 23-MAY-13:00 | 36013.99 | 11-MAY-13:10 | 0.00 | 0.00 | 0.00 |
June | 0.265572E+11 | 0.00 | 512.83 | 0.116983E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 40575.61 | 13-JUN-13:10 | 28316.98 | 13-JUN-13:20 | 0.00 | 0.00 | 0.00 |
July | 0.333793E+11 | 0.00 | 579.96 | 0.154748E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 47050.33 | 22-JUL-13:10 | 38897.14 | 22-JUL-13:30 | 0.00 | 0.00 | 0.00 |
August | 0.400160E+11 | 0.00 | 602.89 | 0.217659E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 51889.83 | 19-AUG-12:50 | 44328.41 | 20-AUG-13:00 | 0.00 | 0.00 | 0.00 |
September | 0.458117E+11 | 0.00 | 573.00 | 0.293918E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 64095.34 | 23-SEP-14:30 | 53830.64 | 13-SEP-13:40 | 0.00 | 0.00 | 0.00 |
October | 0.186119E+11 | 0.00 | 289.03 | 0.147188E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 59066.09 | 07-OCT-13:10 | 59066.09 | 07-OCT-13:10 | 0.00 | 0.00 | 0.00 |
November | 0.375125E+10 | 0.00 | 93.47 | 0.335427E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38365.73 | 11-NOV-13:30 | 38365.73 | 11-NOV-13:30 | 0.00 | 0.00 | 0.00 |
December | 0.193796E+09 | 0.00 | 7.33 | 0.193796E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12782.98 | 26-DEC-14:30 | 12782.98 | 26-DEC-14:30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.228534E+12 | 0.00 | 3799.42 | 0.147360E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.193796E+09 | 0.00 | 7.33 | 0.193796E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12782.98 | 12782.98 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.458117E+11 | 0.00 | 602.89 | 0.293918E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 64095.34 | 59066.09 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.397135E+10 | 0.00 | 188.95 | 0.203052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 68115.58 | 29-JAN-19:02 | 68115.58 | 29-JAN-19:02 | 0.00 | 0.00 | 0.00 |
February | 0.368559E+10 | 0.00 | 178.16 | 0.229004E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 73288.34 | 12-FEB-09:02 | 73288.34 | 12-FEB-09:02 | 0.00 | 0.00 | 0.00 |
March | 0.102947E+11 | 0.00 | 353.15 | 0.740858E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 76155.67 | 11-MAR-09:02 | 76155.67 | 11-MAR-09:02 | 0.00 | 0.00 | 0.00 |
April | 0.233654E+11 | 0.00 | 480.38 | 0.183338E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 79550.06 | 22-APR-15:02 | 79550.06 | 22-APR-15:02 | 0.00 | 0.00 | 0.00 |
May | 0.314232E+11 | 0.00 | 519.76 | 0.219693E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 80746.96 | 23-MAY-15:02 | 80531.40 | 28-MAY-18:01 | 0.00 | 0.00 | 0.00 |
June | 0.457088E+11 | 0.00 | 510.48 | 0.306776E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 89052.07 | 26-JUN-18:02 | 80281.23 | 12-JUN-18:02 | 0.00 | 0.00 | 0.00 |
July | 0.504623E+11 | 0.00 | 528.51 | 0.337060E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 84684.00 | 25-JUL-15:02 | 79644.68 | 10-JUL-15:02 | 0.00 | 0.00 | 0.00 |
August | 0.439096E+11 | 0.00 | 525.67 | 0.274162E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 86170.75 | 11-AUG-15:01 | 78523.23 | 24-AUG-15:02 | 0.00 | 0.00 | 0.00 |
September | 0.319454E+11 | 0.00 | 507.81 | 0.192857E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 84855.17 | 16-SEP-08:62 | 77421.17 | 29-SEP-18:01 | 0.00 | 0.00 | 0.00 |
October | 0.155821E+11 | 0.00 | 459.29 | 0.828760E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 80430.89 | 09-OCT-08:62 | 76703.82 | 07-OCT-18:02 | 0.00 | 0.00 | 0.00 |
November | 0.648716E+10 | 0.00 | 272.43 | 0.329906E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 77258.89 | 08-NOV-19:03 | 74723.89 | 26-NOV-09:02 | 0.00 | 0.00 | 0.00 |
December | 0.205604E+10 | 0.00 | 137.08 | 0.112322E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 62577.53 | 02-DEC-09:02 | 62577.53 | 02-DEC-09:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.268892E+12 | 0.00 | 4661.66 | 0.175828E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.205604E+10 | 0.00 | 137.08 | 0.112322E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 62577.53 | 62577.53 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.504623E+11 | 0.00 | 528.51 | 0.337060E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 89052.07 | 80531.40 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_5_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.108374E+09 | 0.00 | 22.44 | 55059275.29 | 0.00 | 0.00 | 0.00 | 0.00 | 9839.28 | 21-JAN-16:02 | 9078.73 | 21-JAN-16:02 | 0.00 | 0.00 | 0.00 |
February | 0.179290E+09 | 0.00 | 34.22 | 0.121510E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14973.91 | 04-FEB-16:01 | 14973.91 | 04-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.121181E+09 | 0.00 | 37.18 | 81728651.96 | 0.00 | 0.00 | 0.00 | 0.00 | 13338.00 | 20-MAR-15:01 | 13338.00 | 20-MAR-15:01 | 0.00 | 0.00 | 0.00 |
April | 0.350823E+10 | 0.00 | 416.84 | 0.267003E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15850.09 | 17-APR-15:02 | 15850.09 | 17-APR-15:02 | 0.00 | 0.00 | 0.00 |
May | 0.366563E+10 | 0.00 | 455.29 | 0.226648E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15848.97 | 02-MAY-15:02 | 15848.97 | 02-MAY-15:02 | 0.00 | 0.00 | 0.00 |
June | 0.503741E+10 | 0.00 | 553.55 | 0.281164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17451.68 | 27-JUN-08:62 | 15406.52 | 23-JUN-18:01 | 0.00 | 0.00 | 0.00 |
July | 0.633149E+10 | 0.00 | 627.99 | 0.356296E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16843.18 | 28-JUL-15:01 | 15439.44 | 16-JUL-15:02 | 0.00 | 0.00 | 0.00 |
August | 0.663048E+10 | 0.00 | 662.15 | 0.370201E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17293.30 | 11-AUG-15:01 | 15482.57 | 19-AUG-08:62 | 0.00 | 0.00 | 0.00 |
September | 0.519220E+10 | 0.00 | 561.51 | 0.296899E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16866.72 | 02-SEP-08:62 | 15846.22 | 29-SEP-15:01 | 0.00 | 0.00 | 0.00 |
October | 0.118751E+10 | 0.00 | 187.27 | 0.742591E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15845.66 | 07-OCT-15:02 | 15845.66 | 07-OCT-15:02 | 0.00 | 0.00 | 0.00 |
November | 0.105128E+09 | 0.00 | 23.48 | 62226146.73 | 0.00 | 0.00 | 0.00 | 0.00 | 14714.48 | 03-NOV-15:01 | 14714.48 | 03-NOV-15:01 | 0.00 | 0.00 | 0.00 |
December | 29268839.52 | 0.00 | 10.61 | 15325714.17 | 0.00 | 0.00 | 0.00 | 0.00 | 2894.65 | 06-DEC-09:03 | 1730.63 | 06-DEC-09:03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.320962E+11 | 0.00 | 3592.53 | 0.190606E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 29268839.52 | 0.00 | 10.61 | 15325714.17 | 0.00 | 0.00 | 0.00 | 0.00 | 2894.65 | 1730.63 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.663048E+10 | 0.00 | 662.15 | 0.370201E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17451.68 | 15850.09 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_6_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 9111572.95 | 0.00 | 5.69 | 2573627.78 | 0.00 | 0.00 | 0.00 | 0.00 | 2640.41 | 19-JAN-09:03 | 1542.59 | 20-JAN-16:05 | 0.00 | 0.00 | 0.00 |
February | 36580418.67 | 0.00 | 15.18 | 20076180.46 | 0.00 | 0.00 | 0.00 | 0.00 | 9308.76 | 20-FEB-09:02 | 9048.45 | 20-FEB-09:02 | 0.00 | 0.00 | 0.00 |
March | 42920641.72 | 0.00 | 19.13 | 24623906.10 | 0.00 | 0.00 | 0.00 | 0.00 | 3786.21 | 10-MAR-09:02 | 2989.37 | 10-MAR-09:02 | 0.00 | 0.00 | 0.00 |
April | 0.221858E+10 | 0.00 | 317.67 | 0.164160E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14298.66 | 20-APR-08:62 | 14298.66 | 20-APR-08:62 | 0.00 | 0.00 | 0.00 |
May | 0.280307E+10 | 0.00 | 380.46 | 0.176907E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14555.62 | 23-MAY-15:02 | 14296.83 | 21-MAY-15:01 | 0.00 | 0.00 | 0.00 |
June | 0.436619E+10 | 0.00 | 506.63 | 0.251687E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15726.88 | 27-JUN-08:62 | 13889.79 | 23-JUN-18:01 | 0.00 | 0.00 | 0.00 |
July | 0.533014E+10 | 0.00 | 605.85 | 0.305281E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15238.34 | 25-JUL-15:02 | 13907.19 | 10-JUL-15:02 | 0.00 | 0.00 | 0.00 |
August | 0.489475E+10 | 0.00 | 625.93 | 0.266871E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15455.62 | 11-AUG-15:01 | 13964.14 | 05-AUG-15:02 | 0.00 | 0.00 | 0.00 |
September | 0.303582E+10 | 0.00 | 438.58 | 0.166491E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15108.36 | 02-SEP-08:62 | 13873.12 | 23-SEP-08:62 | 0.00 | 0.00 | 0.00 |
October | 0.437056E+09 | 0.00 | 93.90 | 0.250412E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13700.19 | 07-OCT-15:02 | 13700.19 | 07-OCT-15:02 | 0.00 | 0.00 | 0.00 |
November | 14554033.57 | 0.00 | 7.71 | 5069846.51 | 0.00 | 0.00 | 0.00 | 0.00 | 4560.61 | 11-NOV-09:02 | 3984.60 | 11-NOV-09:02 | 0.00 | 0.00 | 0.00 |
December | 1223460.61 | 0.00 | 0.56 | 481602.79 | 0.00 | 0.00 | 0.00 | 0.00 | 1850.75 | 11-DEC-09:05 | 853.08 | 08-DEC-09:05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.231900E+11 | 0.00 | 3017.30 | 0.136172E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 1223460.61 | 0.00 | 0.56 | 481602.79 | 0.00 | 0.00 | 0.00 | 0.00 | 1850.75 | 853.08 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.533014E+10 | 0.00 | 625.93 | 0.305281E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15726.88 | 14298.66 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 9907519.64 | 0.00 | 7.12 | 5915679.90 | 0.00 | 0.00 | 0.00 | 0.00 | 3686.22 | 25-JAN-16:01 | 3686.22 | 25-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 64342783.93 | 0.00 | 35.40 | 59044578.05 | 0.00 | 0.00 | 0.00 | 0.00 | 4669.85 | 09-FEB-16:01 | 4669.85 | 09-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 33232519.72 | 0.00 | 26.48 | 29251211.92 | 0.00 | 0.00 | 0.00 | 0.00 | 4623.00 | 20-MAR-18:02 | 4623.00 | 20-MAR-18:02 | 0.00 | 0.00 | 0.00 |
April | 0.894364E+09 | 0.00 | 337.18 | 0.714605E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4670.34 | 06-APR-18:01 | 4670.34 | 06-APR-18:01 | 0.00 | 0.00 | 0.00 |
May | 0.103773E+10 | 0.00 | 381.87 | 0.722846E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4670.04 | 29-MAY-18:02 | 4670.04 | 29-MAY-18:02 | 0.00 | 0.00 | 0.00 |
June | 0.155390E+10 | 0.00 | 536.89 | 0.960143E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5271.68 | 27-JUN-08:62 | 4669.61 | 08-JUN-18:02 | 0.00 | 0.00 | 0.00 |
July | 0.195809E+10 | 0.00 | 601.03 | 0.120627E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5029.43 | 18-JUL-08:62 | 4527.16 | 16-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.179425E+10 | 0.00 | 637.72 | 0.105276E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5138.51 | 11-AUG-15:01 | 4559.11 | 29-AUG-18:02 | 0.00 | 0.00 | 0.00 |
September | 0.125693E+10 | 0.00 | 487.27 | 0.750021E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4999.27 | 02-SEP-08:62 | 4669.63 | 29-SEP-18:01 | 0.00 | 0.00 | 0.00 |
October | 0.282028E+09 | 0.00 | 140.69 | 0.192192E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4669.02 | 07-OCT-15:02 | 4669.02 | 07-OCT-15:02 | 0.00 | 0.00 | 0.00 |
November | 13681357.36 | 0.00 | 10.93 | 9405639.54 | 0.00 | 0.00 | 0.00 | 0.00 | 4623.13 | 03-NOV-15:01 | 4623.13 | 03-NOV-15:01 | 0.00 | 0.00 | 0.00 |
December | 80784.45 | 0.00 | 0.11 | 65021.44 | 0.00 | 0.00 | 0.00 | 0.00 | 333.51 | 26-DEC-16:05 | 333.51 | 26-DEC-16:05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.889854E+10 | 0.00 | 3202.70 | 0.570251E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 80784.45 | 0.00 | 0.11 | 65021.44 | 0.00 | 0.00 | 0.00 | 0.00 | 333.51 | 333.51 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.195809E+10 | 0.00 | 637.72 | 0.120627E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5271.68 | 4670.34 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 1060553.34 | 0.00 | 1.03 | 476762.93 | 0.00 | 0.00 | 0.00 | 0.00 | 1438.13 | 19-JAN-16:01 | 1354.96 | 19-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 13041292.02 | 0.00 | 14.16 | 10858633.35 | 0.00 | 0.00 | 0.00 | 0.00 | 3402.17 | 19-FEB-16:02 | 3402.17 | 19-FEB-16:02 | 0.00 | 0.00 | 0.00 |
March | 16727962.15 | 0.00 | 15.58 | 14704498.11 | 0.00 | 0.00 | 0.00 | 0.00 | 3981.05 | 20-MAR-18:02 | 3981.05 | 20-MAR-18:02 | 0.00 | 0.00 | 0.00 |
April | 0.572491E+09 | 0.00 | 237.36 | 0.456072E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4150.31 | 17-APR-15:02 | 4150.31 | 17-APR-15:02 | 0.00 | 0.00 | 0.00 |
May | 0.812806E+09 | 0.00 | 318.25 | 0.581077E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4150.09 | 29-MAY-18:02 | 4150.09 | 29-MAY-18:02 | 0.00 | 0.00 | 0.00 |
June | 0.137083E+10 | 0.00 | 498.02 | 0.870226E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4678.84 | 27-JUN-08:62 | 4149.72 | 08-JUN-18:02 | 0.00 | 0.00 | 0.00 |
July | 0.169168E+10 | 0.00 | 569.19 | 0.105812E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4460.58 | 18-JUL-08:62 | 4049.37 | 24-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.134067E+10 | 0.00 | 560.15 | 0.779053E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4518.44 | 11-AUG-15:01 | 4053.57 | 27-AUG-15:02 | 0.00 | 0.00 | 0.00 |
September | 0.718698E+09 | 0.00 | 347.16 | 0.416298E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4310.13 | 02-SEP-18:02 | 4149.17 | 29-SEP-15:01 | 0.00 | 0.00 | 0.00 |
October | 0.106560E+09 | 0.00 | 65.87 | 77854850.43 | 0.00 | 0.00 | 0.00 | 0.00 | 4148.92 | 07-OCT-15:02 | 4148.92 | 07-OCT-15:02 | 0.00 | 0.00 | 0.00 |
November | 1408423.27 | 0.00 | 2.65 | 707075.90 | 0.00 | 0.00 | 0.00 | 0.00 | 1699.14 | 10-NOV-16:02 | 1296.42 | 10-NOV-16:02 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.664598E+10 | 0.00 | 2629.43 | 0.426545E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.169168E+10 | 0.00 | 569.19 | 0.105812E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4678.84 | 4150.31 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.151551E+10 | 0.00 | 157.04 | 0.994676E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 25972.16 | 01-JAN-16:01 | 25972.16 | 01-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.187154E+10 | 0.00 | 177.67 | 0.150479E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25980.12 | 05-FEB-16:01 | 25980.12 | 05-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.695490E+09 | 0.00 | 130.65 | 0.528520E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 25974.45 | 20-MAR-15:01 | 25974.45 | 20-MAR-15:01 | 0.00 | 0.00 | 0.00 |
April | 0.687770E+10 | 0.00 | 470.16 | 0.537162E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25979.53 | 27-APR-18:02 | 25979.53 | 27-APR-18:02 | 0.00 | 0.00 | 0.00 |
May | 0.587780E+10 | 0.00 | 478.90 | 0.343414E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25978.99 | 06-MAY-15:02 | 25978.99 | 06-MAY-15:02 | 0.00 | 0.00 | 0.00 |
June | 0.774384E+10 | 0.00 | 594.27 | 0.404928E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28636.45 | 26-JUN-18:02 | 25341.23 | 23-JUN-18:01 | 0.00 | 0.00 | 0.00 |
July | 0.100107E+11 | 0.00 | 626.86 | 0.546686E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27034.59 | 24-JUL-18:02 | 25767.44 | 05-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.115311E+11 | 0.00 | 667.39 | 0.670179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28673.92 | 11-AUG-15:01 | 25288.95 | 27-AUG-18:02 | 0.00 | 0.00 | 0.00 |
September | 0.111078E+11 | 0.00 | 615.48 | 0.720371E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27647.58 | 19-SEP-15:02 | 25978.35 | 29-SEP-18:01 | 0.00 | 0.00 | 0.00 |
October | 0.432570E+10 | 0.00 | 342.77 | 0.279127E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25978.39 | 07-OCT-18:02 | 25978.39 | 07-OCT-18:02 | 0.00 | 0.00 | 0.00 |
November | 0.124368E+10 | 0.00 | 150.92 | 0.834309E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 25974.12 | 19-NOV-16:01 | 25974.12 | 19-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 0.432071E+09 | 0.00 | 51.37 | 0.362869E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 25539.83 | 18-DEC-16:02 | 25539.83 | 18-DEC-16:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.632330E+11 | 0.00 | 4463.48 | 0.392438E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.432071E+09 | 0.00 | 51.37 | 0.362869E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 25539.83 | 25288.95 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.115311E+11 | 0.00 | 667.39 | 0.720371E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28673.92 | 25980.12 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 563.62 | 364.98 | 198.64 | 563.58 | 505.50 | 0.00 | 0.00 | 0.00 |
February | 683.92 | 416.83 | 267.09 | 701.24 | 488.32 | 0.00 | 0.00 | 0.00 |
March | 422.12 | 122.02 | 300.10 | 355.57 | 407.44 | 0.00 | 0.00 | 0.00 |
April | 865.32 | 383.42 | 481.90 | 1002.76 | 332.88 | 0.00 | 0.00 | 0.00 |
May | 725.42 | 235.00 | 490.43 | 790.01 | 282.58 | 0.00 | 0.00 | 0.00 |
June | 669.64 | 161.95 | 507.69 | 770.09 | 204.28 | 0.00 | 0.00 | 0.00 |
July | 721.80 | 223.30 | 498.49 | 888.76 | 184.21 | 0.00 | 0.00 | 0.00 |
August | 847.76 | 379.84 | 467.92 | 1085.41 | 201.23 | 0.00 | 0.00 | 0.00 |
September | 1015.94 | 599.62 | 416.32 | 1272.02 | 269.39 | 0.00 | 0.00 | 0.00 |
October | 677.90 | 390.83 | 287.07 | 756.45 | 371.25 | 0.00 | 0.00 | 0.00 |
November | 489.54 | 297.70 | 191.84 | 493.20 | 458.89 | 0.00 | 0.00 | 0.00 |
December | 388.47 | 249.10 | 139.37 | 376.12 | 569.67 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 671.57 | 317.45 | 354.12 | 753.62 | 355.66 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 388.47 | 122.02 | 139.37 | 355.57 | 184.21 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1015.94 | 599.62 | 507.69 | 1272.02 | 569.67 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1587.11 | 1027.75 | 559.36 | 1575.35 | 1434.16 | 0.00 | 0.00 | 0.00 |
February | 1925.88 | 1173.78 | 752.10 | 1962.04 | 1382.30 | 0.00 | 0.00 | 0.00 |
March | 1188.66 | 343.60 | 845.06 | 987.72 | 1151.32 | 0.00 | 0.00 | 0.00 |
April | 2436.68 | 1079.69 | 1356.99 | 2811.49 | 931.35 | 0.00 | 0.00 | 0.00 |
May | 2042.74 | 661.73 | 1381.00 | 2211.20 | 790.38 | 0.00 | 0.00 | 0.00 |
June | 1885.66 | 456.04 | 1429.61 | 2156.80 | 567.10 | 0.00 | 0.00 | 0.00 |
July | 2032.53 | 628.81 | 1403.72 | 2492.80 | 510.38 | 0.00 | 0.00 | 0.00 |
August | 2387.23 | 1069.59 | 1317.63 | 3048.21 | 558.05 | 0.00 | 0.00 | 0.00 |
September | 2860.82 | 1688.48 | 1172.34 | 3573.39 | 751.71 | 0.00 | 0.00 | 0.00 |
October | 1908.91 | 1100.54 | 808.37 | 2119.76 | 1047.84 | 0.00 | 0.00 | 0.00 |
November | 1378.50 | 838.29 | 540.21 | 1379.13 | 1303.27 | 0.00 | 0.00 | 0.00 |
December | 1093.90 | 701.44 | 392.46 | 1050.28 | 1628.55 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1891.09 | 893.91 | 997.17 | 2111.25 | 1002.87 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1093.90 | 343.60 | 392.46 | 987.72 | 510.38 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2860.82 | 1688.48 | 1429.61 | 3573.39 | 1628.55 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2061.74 | 1335.10 | 726.64 | 2074.05 | 1920.53 | 0.00 | 0.00 | 0.00 |
February | 2501.82 | 1524.80 | 977.02 | 2586.31 | 1843.63 | 0.00 | 0.00 | 0.00 |
March | 1544.14 | 446.36 | 1097.78 | 1304.86 | 1546.67 | 0.00 | 0.00 | 0.00 |
April | 3165.39 | 1402.59 | 1762.80 | 3725.87 | 1238.41 | 0.00 | 0.00 | 0.00 |
May | 2653.63 | 859.63 | 1794.00 | 2935.78 | 1055.26 | 0.00 | 0.00 | 0.00 |
June | 2449.58 | 592.43 | 1857.15 | 2867.73 | 761.90 | 0.00 | 0.00 | 0.00 |
July | 2640.37 | 816.86 | 1823.51 | 3311.00 | 685.72 | 0.00 | 0.00 | 0.00 |
August | 3101.14 | 1389.46 | 1711.68 | 4041.69 | 745.02 | 0.00 | 0.00 | 0.00 |
September | 3716.37 | 2193.43 | 1522.94 | 4732.38 | 994.91 | 0.00 | 0.00 | 0.00 |
October | 2479.78 | 1429.67 | 1050.12 | 2801.04 | 1397.81 | 0.00 | 0.00 | 0.00 |
November | 1790.75 | 1088.99 | 701.76 | 1816.30 | 1745.41 | 0.00 | 0.00 | 0.00 |
December | 1421.04 | 911.21 | 509.83 | 1379.54 | 2191.37 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2456.63 | 1161.25 | 1295.39 | 2794.44 | 1341.52 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1421.04 | 446.36 | 509.83 | 1304.86 | 685.72 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3716.37 | 2193.43 | 1857.15 | 4732.38 | 2191.37 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 111.44 | 72.16 | 39.27 | 112.58 | 101.00 | 0.00 | 0.00 | 0.00 |
February | 135.22 | 82.42 | 52.81 | 139.18 | 98.49 | 0.00 | 0.00 | 0.00 |
March | 83.46 | 24.13 | 59.33 | 70.69 | 82.00 | 0.00 | 0.00 | 0.00 |
April | 171.09 | 75.81 | 95.28 | 196.27 | 68.65 | 0.00 | 0.00 | 0.00 |
May | 143.43 | 46.46 | 96.97 | 152.56 | 59.30 | 0.00 | 0.00 | 0.00 |
June | 132.40 | 32.02 | 100.38 | 147.52 | 43.13 | 0.00 | 0.00 | 0.00 |
July | 142.71 | 44.15 | 98.56 | 171.25 | 38.80 | 0.00 | 0.00 | 0.00 |
August | 167.62 | 75.10 | 92.52 | 211.47 | 41.77 | 0.00 | 0.00 | 0.00 |
September | 200.87 | 118.55 | 82.32 | 249.94 | 55.49 | 0.00 | 0.00 | 0.00 |
October | 134.03 | 77.27 | 56.76 | 149.48 | 75.06 | 0.00 | 0.00 | 0.00 |
November | 96.79 | 58.86 | 37.93 | 98.07 | 91.82 | 0.00 | 0.00 | 0.00 |
December | 76.81 | 49.25 | 27.56 | 75.27 | 114.38 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 132.78 | 62.77 | 70.02 | 147.65 | 72.36 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 76.81 | 24.13 | 27.56 | 70.69 | 38.80 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 200.87 | 118.55 | 100.38 | 249.94 | 114.38 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.05 | 23.94 | 49.11 | 44.33 | 203.23 | 0.00 | 0.00 | 0.00 |
February | 129.22 | 55.01 | 74.22 | 101.60 | 192.98 | 0.00 | 0.00 | 0.00 |
March | 116.25 | 22.35 | 93.89 | 75.52 | 153.53 | 0.00 | 0.00 | 0.00 |
April | 273.78 | 108.55 | 165.23 | 285.45 | 124.77 | 0.00 | 0.00 | 0.00 |
May | 321.27 | 130.65 | 190.62 | 333.77 | 105.38 | 0.00 | 0.00 | 0.00 |
June | 346.85 | 142.80 | 204.06 | 390.69 | 77.26 | 0.00 | 0.00 | 0.00 |
July | 353.04 | 155.51 | 197.53 | 415.35 | 69.80 | 0.00 | 0.00 | 0.00 |
August | 297.09 | 128.70 | 168.39 | 351.62 | 76.26 | 0.00 | 0.00 | 0.00 |
September | 240.07 | 108.52 | 131.55 | 270.04 | 103.49 | 0.00 | 0.00 | 0.00 |
October | 127.97 | 46.48 | 81.49 | 113.59 | 143.51 | 0.00 | 0.00 | 0.00 |
November | 69.04 | 20.37 | 48.67 | 42.60 | 180.46 | 0.00 | 0.00 | 0.00 |
December | 38.49 | 7.82 | 30.67 | 13.68 | 227.16 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 199.05 | 79.25 | 119.80 | 203.54 | 137.88 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 38.49 | 7.82 | 30.67 | 13.68 | 69.80 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 353.04 | 155.51 | 204.06 | 415.35 | 227.16 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.53 | 0.00 | 19.53 | 2.22 | 111.70 | 0.00 | 0.00 | 0.00 |
February | 30.49 | 0.00 | 30.49 | 6.11 | 105.32 | 0.00 | 0.00 | 0.00 |
March | 42.20 | 0.00 | 42.20 | 17.13 | 84.58 | 0.00 | 0.00 | 0.00 |
April | 68.95 | 0.46 | 68.49 | 48.38 | 66.55 | 0.00 | 0.00 | 0.00 |
May | 86.20 | 4.40 | 81.81 | 61.06 | 53.19 | 0.00 | 0.00 | 0.00 |
June | 94.97 | 5.94 | 89.03 | 85.39 | 39.25 | 0.00 | 0.00 | 0.00 |
July | 90.30 | 5.31 | 84.99 | 87.08 | 35.27 | 0.00 | 0.00 | 0.00 |
August | 71.09 | 1.33 | 69.76 | 67.63 | 39.05 | 0.00 | 0.00 | 0.00 |
September | 53.92 | 0.03 | 53.89 | 44.69 | 55.46 | 0.00 | 0.00 | 0.00 |
October | 34.53 | 0.00 | 34.53 | 17.26 | 77.20 | 0.00 | 0.00 | 0.00 |
November | 20.75 | 0.00 | 20.75 | 3.44 | 97.23 | 0.00 | 0.00 | 0.00 |
December | 14.13 | 0.00 | 14.13 | 0.27 | 121.99 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 52.35 | 1.47 | 50.89 | 36.88 | 73.74 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 14.13 | 0.00 | 14.13 | 0.27 | 35.27 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 94.97 | 5.94 | 89.03 | 87.08 | 121.99 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.05 | 23.94 | 49.11 | 47.05 | 200.70 | 0.00 | 0.00 | 0.00 |
February | 129.22 | 55.01 | 74.22 | 105.46 | 190.28 | 0.00 | 0.00 | 0.00 |
March | 116.25 | 22.35 | 93.89 | 77.43 | 152.44 | 0.00 | 0.00 | 0.00 |
April | 273.78 | 108.55 | 165.23 | 290.15 | 123.30 | 0.00 | 0.00 | 0.00 |
May | 321.27 | 130.65 | 190.62 | 336.77 | 104.62 | 0.00 | 0.00 | 0.00 |
June | 346.85 | 142.80 | 204.06 | 392.57 | 76.80 | 0.00 | 0.00 | 0.00 |
July | 353.04 | 155.51 | 197.53 | 417.58 | 69.26 | 0.00 | 0.00 | 0.00 |
August | 297.09 | 128.70 | 168.39 | 355.27 | 75.21 | 0.00 | 0.00 | 0.00 |
September | 240.07 | 108.52 | 131.55 | 275.39 | 101.53 | 0.00 | 0.00 | 0.00 |
October | 127.97 | 46.48 | 81.49 | 117.57 | 141.39 | 0.00 | 0.00 | 0.00 |
November | 69.04 | 20.37 | 48.67 | 45.13 | 178.15 | 0.00 | 0.00 | 0.00 |
December | 38.49 | 7.82 | 30.67 | 14.91 | 225.23 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 199.05 | 79.25 | 119.80 | 206.61 | 136.32 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 38.49 | 7.82 | 30.67 | 14.91 | 69.26 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 353.04 | 155.51 | 204.06 | 417.58 | 225.23 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.13 | 57.72 | 31.41 | 86.79 | 88.91 | 0.00 | 0.00 | 0.00 |
February | 108.16 | 65.92 | 42.24 | 108.09 | 87.07 | 0.00 | 0.00 | 0.00 |
March | 66.76 | 19.30 | 47.46 | 53.64 | 71.54 | 0.00 | 0.00 | 0.00 |
April | 136.84 | 60.64 | 76.21 | 153.33 | 62.45 | 0.00 | 0.00 | 0.00 |
May | 114.72 | 37.16 | 77.56 | 118.48 | 54.57 | 0.00 | 0.00 | 0.00 |
June | 105.90 | 25.61 | 80.29 | 114.92 | 40.73 | 0.00 | 0.00 | 0.00 |
July | 114.15 | 35.31 | 78.83 | 134.03 | 37.12 | 0.00 | 0.00 | 0.00 |
August | 134.07 | 60.07 | 74.00 | 166.15 | 40.28 | 0.00 | 0.00 | 0.00 |
September | 160.66 | 94.82 | 65.84 | 196.37 | 52.45 | 0.00 | 0.00 | 0.00 |
October | 107.20 | 61.81 | 45.40 | 116.03 | 69.99 | 0.00 | 0.00 | 0.00 |
November | 77.42 | 47.08 | 30.34 | 75.52 | 83.21 | 0.00 | 0.00 | 0.00 |
December | 61.43 | 39.39 | 22.04 | 59.28 | 92.93 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 106.20 | 50.20 | 56.00 | 115.06 | 64.98 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 61.43 | 19.30 | 22.04 | 53.64 | 37.12 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 160.66 | 94.82 | 80.29 | 196.37 | 92.93 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 15.62 | 0.00 | 15.62 | 1.26 | 94.82 | 0.00 | 0.00 | 0.00 |
February | 24.39 | 0.00 | 24.39 | 3.93 | 88.36 | 0.00 | 0.00 | 0.00 |
March | 33.76 | 0.00 | 33.76 | 12.36 | 71.18 | 0.00 | 0.00 | 0.00 |
April | 55.17 | 0.37 | 54.80 | 39.68 | 53.76 | 0.00 | 0.00 | 0.00 |
May | 68.97 | 3.52 | 65.46 | 50.37 | 42.91 | 0.00 | 0.00 | 0.00 |
June | 75.98 | 4.75 | 71.23 | 70.88 | 31.20 | 0.00 | 0.00 | 0.00 |
July | 72.25 | 4.25 | 68.00 | 72.54 | 27.85 | 0.00 | 0.00 | 0.00 |
August | 56.88 | 1.06 | 55.82 | 56.69 | 30.75 | 0.00 | 0.00 | 0.00 |
September | 43.14 | 0.03 | 43.12 | 37.08 | 44.35 | 0.00 | 0.00 | 0.00 |
October | 27.62 | 0.00 | 27.62 | 13.27 | 64.60 | 0.00 | 0.00 | 0.00 |
November | 16.60 | 0.00 | 16.60 | 2.10 | 82.98 | 0.00 | 0.00 | 0.00 |
December | 11.30 | 0.00 | 11.30 | 0.07 | 104.41 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 41.89 | 1.17 | 40.71 | 30.15 | 61.30 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 11.30 | 0.00 | 11.30 | 0.07 | 27.85 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 75.98 | 4.75 | 71.23 | 72.54 | 104.41 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.10 | 29.51 | 44.59 | 43.12 | 200.09 | 0.00 | 0.00 | 0.00 |
February | 111.90 | 41.69 | 70.20 | 73.46 | 188.70 | 0.00 | 0.00 | 0.00 |
March | 116.26 | 22.93 | 93.33 | 74.29 | 151.97 | 0.00 | 0.00 | 0.00 |
April | 311.45 | 146.03 | 165.42 | 328.89 | 119.50 | 0.00 | 0.00 | 0.00 |
May | 327.92 | 143.03 | 184.89 | 338.43 | 101.99 | 0.00 | 0.00 | 0.00 |
June | 324.49 | 129.63 | 194.86 | 359.09 | 74.89 | 0.00 | 0.00 | 0.00 |
July | 331.18 | 140.68 | 190.50 | 383.03 | 67.19 | 0.00 | 0.00 | 0.00 |
August | 314.61 | 150.61 | 163.99 | 372.27 | 72.78 | 0.00 | 0.00 | 0.00 |
September | 282.45 | 150.08 | 132.37 | 321.28 | 99.47 | 0.00 | 0.00 | 0.00 |
October | 137.38 | 57.45 | 79.93 | 123.44 | 140.91 | 0.00 | 0.00 | 0.00 |
November | 71.10 | 24.19 | 46.91 | 41.16 | 176.26 | 0.00 | 0.00 | 0.00 |
December | 52.88 | 19.79 | 33.09 | 26.45 | 220.57 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 204.94 | 88.08 | 116.86 | 207.57 | 134.27 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 52.88 | 19.79 | 33.09 | 26.45 | 67.19 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 331.18 | 150.61 | 194.86 | 383.03 | 220.57 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 111.44 | 72.16 | 39.27 | 112.37 | 100.83 | 0.00 | 0.00 | 0.00 |
February | 135.22 | 82.42 | 52.81 | 139.13 | 98.03 | 0.00 | 0.00 | 0.00 |
March | 83.46 | 24.13 | 59.33 | 70.28 | 81.80 | 0.00 | 0.00 | 0.00 |
April | 171.09 | 75.81 | 95.28 | 194.44 | 68.45 | 0.00 | 0.00 | 0.00 |
May | 143.43 | 46.46 | 96.97 | 151.15 | 58.81 | 0.00 | 0.00 | 0.00 |
June | 132.40 | 32.02 | 100.38 | 146.88 | 42.39 | 0.00 | 0.00 | 0.00 |
July | 142.71 | 44.15 | 98.56 | 170.48 | 38.14 | 0.00 | 0.00 | 0.00 |
August | 167.62 | 75.10 | 92.52 | 210.44 | 41.38 | 0.00 | 0.00 | 0.00 |
September | 200.87 | 118.55 | 82.32 | 248.42 | 55.32 | 0.00 | 0.00 | 0.00 |
October | 134.03 | 77.27 | 56.76 | 148.79 | 74.88 | 0.00 | 0.00 | 0.00 |
November | 96.79 | 58.86 | 37.93 | 97.89 | 91.65 | 0.00 | 0.00 | 0.00 |
December | 76.81 | 49.25 | 27.56 | 74.94 | 114.53 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 132.78 | 62.77 | 70.02 | 146.90 | 72.06 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 76.81 | 24.13 | 27.56 | 70.28 | 38.14 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 200.87 | 118.55 | 100.38 | 248.42 | 114.53 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.53 | 0.00 | 19.53 | 2.04 | 111.45 | 0.00 | 0.00 | 0.00 |
February | 30.49 | 0.00 | 30.49 | 5.79 | 104.63 | 0.00 | 0.00 | 0.00 |
March | 42.20 | 0.00 | 42.20 | 16.72 | 84.40 | 0.00 | 0.00 | 0.00 |
April | 68.95 | 0.46 | 68.49 | 46.22 | 66.56 | 0.00 | 0.00 | 0.00 |
May | 86.20 | 4.40 | 81.81 | 59.42 | 52.85 | 0.00 | 0.00 | 0.00 |
June | 94.97 | 5.94 | 89.03 | 84.64 | 38.71 | 0.00 | 0.00 | 0.00 |
July | 90.30 | 5.31 | 84.99 | 86.12 | 34.77 | 0.00 | 0.00 | 0.00 |
August | 71.09 | 1.33 | 69.76 | 66.09 | 38.71 | 0.00 | 0.00 | 0.00 |
September | 53.92 | 0.03 | 53.89 | 42.59 | 55.52 | 0.00 | 0.00 | 0.00 |
October | 34.53 | 0.00 | 34.53 | 16.50 | 77.08 | 0.00 | 0.00 | 0.00 |
November | 20.75 | 0.00 | 20.75 | 3.25 | 96.94 | 0.00 | 0.00 | 0.00 |
December | 14.13 | 0.00 | 14.13 | 0.22 | 122.02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 52.35 | 1.47 | 50.89 | 35.95 | 73.48 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 14.13 | 0.00 | 14.13 | 0.22 | 34.77 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 94.97 | 5.94 | 89.03 | 86.12 | 122.02 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.10 | 29.51 | 44.59 | 44.93 | 196.49 | 0.00 | 0.00 | 0.00 |
February | 111.90 | 41.69 | 70.20 | 76.40 | 185.01 | 0.00 | 0.00 | 0.00 |
March | 116.26 | 22.93 | 93.33 | 76.02 | 150.74 | 0.00 | 0.00 | 0.00 |
April | 311.45 | 146.03 | 165.42 | 332.74 | 117.98 | 0.00 | 0.00 | 0.00 |
May | 327.92 | 143.03 | 184.89 | 340.91 | 101.19 | 0.00 | 0.00 | 0.00 |
June | 324.49 | 129.63 | 194.86 | 360.71 | 74.49 | 0.00 | 0.00 | 0.00 |
July | 331.18 | 140.68 | 190.50 | 384.89 | 66.69 | 0.00 | 0.00 | 0.00 |
August | 314.61 | 150.61 | 163.99 | 375.13 | 71.77 | 0.00 | 0.00 | 0.00 |
September | 282.45 | 150.08 | 132.37 | 325.40 | 97.57 | 0.00 | 0.00 | 0.00 |
October | 137.38 | 57.45 | 79.93 | 127.01 | 138.62 | 0.00 | 0.00 | 0.00 |
November | 71.10 | 24.19 | 46.91 | 43.13 | 173.25 | 0.00 | 0.00 | 0.00 |
December | 52.88 | 19.79 | 33.09 | 27.35 | 217.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 204.94 | 88.08 | 116.86 | 210.03 | 132.39 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 52.88 | 19.79 | 33.09 | 27.35 | 66.69 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 331.18 | 150.61 | 194.86 | 384.89 | 217.86 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 24.73 | 0.00 | 24.73 | 1.90 | 152.22 | 0.00 | 0.00 | 0.00 |
February | 38.61 | 0.00 | 38.61 | 5.90 | 141.22 | 0.00 | 0.00 | 0.00 |
March | 53.44 | 0.00 | 53.44 | 20.11 | 112.47 | 0.00 | 0.00 | 0.00 |
April | 87.32 | 0.58 | 86.74 | 64.49 | 84.66 | 0.00 | 0.00 | 0.00 |
May | 109.17 | 5.57 | 103.61 | 82.64 | 67.20 | 0.00 | 0.00 | 0.00 |
June | 120.27 | 7.52 | 112.75 | 116.43 | 48.53 | 0.00 | 0.00 | 0.00 |
July | 114.35 | 6.73 | 107.63 | 118.91 | 43.51 | 0.00 | 0.00 | 0.00 |
August | 90.03 | 1.68 | 88.35 | 92.66 | 48.28 | 0.00 | 0.00 | 0.00 |
September | 68.29 | 0.04 | 68.25 | 60.21 | 69.91 | 0.00 | 0.00 | 0.00 |
October | 43.73 | 0.00 | 43.73 | 21.43 | 101.82 | 0.00 | 0.00 | 0.00 |
November | 26.27 | 0.00 | 26.27 | 3.26 | 132.09 | 0.00 | 0.00 | 0.00 |
December | 17.89 | 0.00 | 17.89 | 0.08 | 167.67 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.30 | 1.86 | 64.44 | 49.22 | 97.25 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 17.89 | 0.00 | 17.89 | 0.08 | 43.51 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 120.27 | 7.52 | 112.75 | 118.91 | 167.67 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 9.12 | 0.00 | 9.12 | 0.70 | 56.11 | 0.00 | 0.00 | 0.00 |
February | 14.23 | 0.00 | 14.23 | 2.17 | 52.06 | 0.00 | 0.00 | 0.00 |
March | 19.70 | 0.00 | 19.70 | 7.41 | 41.46 | 0.00 | 0.00 | 0.00 |
April | 32.19 | 0.21 | 31.98 | 23.77 | 31.21 | 0.00 | 0.00 | 0.00 |
May | 40.25 | 2.05 | 38.19 | 30.46 | 24.77 | 0.00 | 0.00 | 0.00 |
June | 44.34 | 2.77 | 41.56 | 42.92 | 17.89 | 0.00 | 0.00 | 0.00 |
July | 42.16 | 2.48 | 39.68 | 43.83 | 16.04 | 0.00 | 0.00 | 0.00 |
August | 33.19 | 0.62 | 32.57 | 34.16 | 17.80 | 0.00 | 0.00 | 0.00 |
September | 25.17 | 0.01 | 25.16 | 22.20 | 25.77 | 0.00 | 0.00 | 0.00 |
October | 16.12 | 0.00 | 16.12 | 7.90 | 37.53 | 0.00 | 0.00 | 0.00 |
November | 9.69 | 0.00 | 9.69 | 1.20 | 48.69 | 0.00 | 0.00 | 0.00 |
December | 6.60 | 0.00 | 6.60 | 0.03 | 61.81 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 24.44 | 0.68 | 23.76 | 18.15 | 35.85 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 6.60 | 0.00 | 6.60 | 0.03 | 16.04 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 44.34 | 2.77 | 41.56 | 43.83 | 61.81 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 52.00 | 33.67 | 18.33 | 52.30 | 49.42 | 0.00 | 0.00 | 0.00 |
February | 63.09 | 38.45 | 24.64 | 65.13 | 47.69 | 0.00 | 0.00 | 0.00 |
March | 38.94 | 11.26 | 27.69 | 32.74 | 39.80 | 0.00 | 0.00 | 0.00 |
April | 79.83 | 35.37 | 44.46 | 93.84 | 31.76 | 0.00 | 0.00 | 0.00 |
May | 66.92 | 21.68 | 45.24 | 73.65 | 27.31 | 0.00 | 0.00 | 0.00 |
June | 61.78 | 14.94 | 46.84 | 72.16 | 19.49 | 0.00 | 0.00 | 0.00 |
July | 66.59 | 20.60 | 45.99 | 83.43 | 17.46 | 0.00 | 0.00 | 0.00 |
August | 78.21 | 35.04 | 43.17 | 102.01 | 18.75 | 0.00 | 0.00 | 0.00 |
September | 93.72 | 55.32 | 38.41 | 119.31 | 25.32 | 0.00 | 0.00 | 0.00 |
October | 62.54 | 36.06 | 26.48 | 70.64 | 35.89 | 0.00 | 0.00 | 0.00 |
November | 45.16 | 27.46 | 17.70 | 45.72 | 45.04 | 0.00 | 0.00 | 0.00 |
December | 35.84 | 22.98 | 12.86 | 34.73 | 56.91 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 61.96 | 29.29 | 32.67 | 70.38 | 34.51 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 35.84 | 11.26 | 12.86 | 32.74 | 17.46 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 93.72 | 55.32 | 46.84 | 119.31 | 56.91 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 141.13 | 91.39 | 49.74 | 141.96 | 134.14 | 0.00 | 0.00 | 0.00 |
February | 171.25 | 104.37 | 66.88 | 176.77 | 129.45 | 0.00 | 0.00 | 0.00 |
March | 105.70 | 30.55 | 75.14 | 88.87 | 108.02 | 0.00 | 0.00 | 0.00 |
April | 216.67 | 96.01 | 120.67 | 254.70 | 86.21 | 0.00 | 0.00 | 0.00 |
May | 181.64 | 58.84 | 122.80 | 199.89 | 74.12 | 0.00 | 0.00 | 0.00 |
June | 167.68 | 40.55 | 127.12 | 195.87 | 52.89 | 0.00 | 0.00 | 0.00 |
July | 180.74 | 55.91 | 124.82 | 226.46 | 47.40 | 0.00 | 0.00 | 0.00 |
August | 212.28 | 95.11 | 117.17 | 276.88 | 50.90 | 0.00 | 0.00 | 0.00 |
September | 254.39 | 150.14 | 104.25 | 323.83 | 68.72 | 0.00 | 0.00 | 0.00 |
October | 169.74 | 97.86 | 71.88 | 191.73 | 97.41 | 0.00 | 0.00 | 0.00 |
November | 122.58 | 74.54 | 48.04 | 124.09 | 122.26 | 0.00 | 0.00 | 0.00 |
December | 97.27 | 62.37 | 34.90 | 94.26 | 154.46 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 168.16 | 79.49 | 88.67 | 191.03 | 93.66 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 97.27 | 30.55 | 34.90 | 88.87 | 47.40 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 254.39 | 150.14 | 127.12 | 323.83 | 154.46 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 111.44 | 72.16 | 39.27 | 112.91 | 99.35 | 0.00 | 0.00 | 0.00 |
February | 135.22 | 82.42 | 52.81 | 139.24 | 97.35 | 0.00 | 0.00 | 0.00 |
March | 83.46 | 24.13 | 59.33 | 70.83 | 80.76 | 0.00 | 0.00 | 0.00 |
April | 171.09 | 75.81 | 95.28 | 194.69 | 68.39 | 0.00 | 0.00 | 0.00 |
May | 143.43 | 46.46 | 96.97 | 150.78 | 59.48 | 0.00 | 0.00 | 0.00 |
June | 132.40 | 32.02 | 100.38 | 145.42 | 43.43 | 0.00 | 0.00 | 0.00 |
July | 142.71 | 44.15 | 98.56 | 169.05 | 39.09 | 0.00 | 0.00 | 0.00 |
August | 167.62 | 75.10 | 92.52 | 209.46 | 41.89 | 0.00 | 0.00 | 0.00 |
September | 200.87 | 118.55 | 82.32 | 248.26 | 55.44 | 0.00 | 0.00 | 0.00 |
October | 134.03 | 77.27 | 56.76 | 149.13 | 74.14 | 0.00 | 0.00 | 0.00 |
November | 96.79 | 58.86 | 37.93 | 98.22 | 90.39 | 0.00 | 0.00 | 0.00 |
December | 76.81 | 49.25 | 27.56 | 75.46 | 113.03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 132.78 | 62.77 | 70.02 | 146.75 | 71.77 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 76.81 | 24.13 | 27.56 | 70.83 | 39.09 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 200.87 | 118.55 | 100.38 | 248.26 | 113.03 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.05 | 23.94 | 49.11 | 44.78 | 199.57 | 0.00 | 0.00 | 0.00 |
February | 129.22 | 55.01 | 74.22 | 101.81 | 190.39 | 0.00 | 0.00 | 0.00 |
March | 116.25 | 22.35 | 93.89 | 75.74 | 151.06 | 0.00 | 0.00 | 0.00 |
April | 273.78 | 108.55 | 165.23 | 282.21 | 124.05 | 0.00 | 0.00 | 0.00 |
May | 321.27 | 130.65 | 190.62 | 329.53 | 105.51 | 0.00 | 0.00 | 0.00 |
June | 346.85 | 142.80 | 204.06 | 385.48 | 77.67 | 0.00 | 0.00 | 0.00 |
July | 353.04 | 155.51 | 197.53 | 410.18 | 70.17 | 0.00 | 0.00 | 0.00 |
August | 297.09 | 128.70 | 168.39 | 347.34 | 76.35 | 0.00 | 0.00 | 0.00 |
September | 240.07 | 108.52 | 131.55 | 267.22 | 103.26 | 0.00 | 0.00 | 0.00 |
October | 127.97 | 46.48 | 81.49 | 113.09 | 141.52 | 0.00 | 0.00 | 0.00 |
November | 69.04 | 20.37 | 48.67 | 42.96 | 177.40 | 0.00 | 0.00 | 0.00 |
December | 38.49 | 7.82 | 30.67 | 13.96 | 224.06 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 199.05 | 79.25 | 119.80 | 201.53 | 136.49 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 38.49 | 7.82 | 30.67 | 13.96 | 70.17 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 353.04 | 155.51 | 204.06 | 410.18 | 224.06 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.53 | 0.00 | 19.53 | 2.41 | 109.66 | 0.00 | 0.00 | 0.00 |
February | 30.49 | 0.00 | 30.49 | 6.39 | 103.75 | 0.00 | 0.00 | 0.00 |
March | 42.20 | 0.00 | 42.20 | 17.42 | 83.16 | 0.00 | 0.00 | 0.00 |
April | 68.95 | 0.46 | 68.49 | 47.14 | 66.18 | 0.00 | 0.00 | 0.00 |
May | 86.20 | 4.40 | 81.81 | 59.38 | 53.22 | 0.00 | 0.00 | 0.00 |
June | 94.97 | 5.94 | 89.03 | 83.18 | 39.45 | 0.00 | 0.00 | 0.00 |
July | 90.30 | 5.31 | 84.99 | 84.90 | 35.47 | 0.00 | 0.00 | 0.00 |
August | 71.09 | 1.33 | 69.76 | 65.89 | 39.13 | 0.00 | 0.00 | 0.00 |
September | 53.92 | 0.03 | 53.89 | 43.73 | 55.29 | 0.00 | 0.00 | 0.00 |
October | 34.53 | 0.00 | 34.53 | 17.35 | 75.98 | 0.00 | 0.00 | 0.00 |
November | 20.75 | 0.00 | 20.75 | 3.69 | 95.35 | 0.00 | 0.00 | 0.00 |
December | 14.13 | 0.00 | 14.13 | 0.34 | 120.19 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 52.35 | 1.47 | 50.89 | 36.13 | 72.92 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 14.13 | 0.00 | 14.13 | 0.34 | 35.47 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 94.97 | 5.94 | 89.03 | 84.90 | 120.19 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.05 | 23.94 | 49.11 | 47.62 | 197.21 | 0.00 | 0.00 | 0.00 |
February | 129.22 | 55.01 | 74.22 | 105.98 | 187.62 | 0.00 | 0.00 | 0.00 |
March | 116.25 | 22.35 | 93.89 | 77.82 | 149.93 | 0.00 | 0.00 | 0.00 |
April | 273.78 | 108.55 | 165.23 | 287.01 | 122.49 | 0.00 | 0.00 | 0.00 |
May | 321.27 | 130.65 | 190.62 | 332.52 | 104.70 | 0.00 | 0.00 | 0.00 |
June | 346.85 | 142.80 | 204.06 | 387.22 | 77.20 | 0.00 | 0.00 | 0.00 |
July | 353.04 | 155.51 | 197.53 | 412.24 | 69.63 | 0.00 | 0.00 | 0.00 |
August | 297.09 | 128.70 | 168.39 | 350.74 | 75.25 | 0.00 | 0.00 | 0.00 |
September | 240.07 | 108.52 | 131.55 | 272.63 | 101.15 | 0.00 | 0.00 | 0.00 |
October | 127.97 | 46.48 | 81.49 | 117.39 | 139.19 | 0.00 | 0.00 | 0.00 |
November | 69.04 | 20.37 | 48.67 | 45.71 | 175.09 | 0.00 | 0.00 | 0.00 |
December | 38.49 | 7.82 | 30.67 | 15.19 | 222.40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 199.05 | 79.25 | 119.80 | 204.67 | 134.90 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 38.49 | 7.82 | 30.67 | 15.19 | 69.63 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 353.04 | 155.51 | 204.06 | 412.24 | 222.40 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 163.43 | 105.83 | 57.60 | 160.11 | 152.15 | 0.00 | 0.00 | 0.00 |
February | 198.32 | 120.87 | 77.45 | 199.21 | 148.59 | 0.00 | 0.00 | 0.00 |
March | 122.40 | 35.38 | 87.02 | 100.09 | 122.30 | 0.00 | 0.00 | 0.00 |
April | 250.92 | 111.18 | 139.74 | 283.13 | 101.38 | 0.00 | 0.00 | 0.00 |
May | 210.35 | 68.14 | 142.21 | 220.50 | 87.32 | 0.00 | 0.00 | 0.00 |
June | 194.18 | 46.96 | 147.22 | 214.72 | 62.86 | 0.00 | 0.00 | 0.00 |
July | 209.30 | 64.75 | 144.55 | 249.37 | 56.48 | 0.00 | 0.00 | 0.00 |
August | 245.83 | 110.14 | 135.68 | 307.15 | 61.16 | 0.00 | 0.00 | 0.00 |
September | 294.59 | 173.87 | 120.72 | 361.61 | 82.58 | 0.00 | 0.00 | 0.00 |
October | 196.57 | 113.33 | 83.24 | 214.73 | 113.00 | 0.00 | 0.00 | 0.00 |
November | 141.95 | 86.32 | 55.63 | 139.69 | 139.17 | 0.00 | 0.00 | 0.00 |
December | 112.65 | 72.23 | 40.41 | 107.00 | 173.21 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 194.74 | 92.05 | 102.68 | 212.82 | 108.15 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 112.65 | 35.38 | 40.41 | 100.09 | 56.48 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 294.59 | 173.87 | 147.22 | 361.61 | 173.21 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 136.67 | 0.00 | 136.67 | 9.89 | 835.58 | 0.00 | 0.00 | 0.00 |
February | 213.42 | 0.00 | 213.42 | 30.75 | 780.02 | 0.00 | 0.00 | 0.00 |
March | 295.36 | 0.00 | 295.36 | 105.63 | 624.85 | 0.00 | 0.00 | 0.00 |
April | 482.63 | 3.21 | 479.42 | 343.86 | 475.44 | 0.00 | 0.00 | 0.00 |
May | 603.41 | 30.77 | 572.64 | 435.27 | 389.09 | 0.00 | 0.00 | 0.00 |
June | 664.75 | 41.58 | 623.17 | 617.34 | 288.80 | 0.00 | 0.00 | 0.00 |
July | 632.05 | 37.17 | 594.87 | 634.01 | 259.60 | 0.00 | 0.00 | 0.00 |
August | 497.63 | 9.31 | 488.32 | 497.01 | 284.36 | 0.00 | 0.00 | 0.00 |
September | 377.45 | 0.22 | 377.22 | 325.08 | 398.28 | 0.00 | 0.00 | 0.00 |
October | 241.68 | 0.00 | 241.68 | 114.02 | 571.60 | 0.00 | 0.00 | 0.00 |
November | 145.21 | 0.00 | 145.21 | 16.90 | 736.03 | 0.00 | 0.00 | 0.00 |
December | 98.89 | 0.00 | 98.89 | 0.39 | 930.31 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 366.45 | 10.26 | 356.19 | 262.03 | 546.72 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 98.89 | 0.00 | 98.89 | 0.39 | 259.60 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 664.75 | 41.58 | 623.17 | 634.01 | 930.31 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 136.67 | 0.00 | 136.67 | 8.95 | 851.48 | 0.00 | 0.00 | 0.00 |
February | 213.42 | 0.00 | 213.42 | 28.55 | 795.04 | 0.00 | 0.00 | 0.00 |
March | 295.36 | 0.00 | 295.36 | 101.52 | 638.60 | 0.00 | 0.00 | 0.00 |
April | 482.63 | 3.21 | 479.42 | 336.35 | 486.21 | 0.00 | 0.00 | 0.00 |
May | 603.41 | 30.77 | 572.64 | 424.87 | 398.44 | 0.00 | 0.00 | 0.00 |
June | 664.75 | 41.58 | 623.17 | 605.76 | 297.53 | 0.00 | 0.00 | 0.00 |
July | 632.05 | 37.17 | 594.87 | 621.98 | 268.02 | 0.00 | 0.00 | 0.00 |
August | 497.63 | 9.31 | 488.32 | 487.18 | 294.03 | 0.00 | 0.00 | 0.00 |
September | 377.45 | 0.22 | 377.22 | 318.01 | 409.65 | 0.00 | 0.00 | 0.00 |
October | 241.68 | 0.00 | 241.68 | 109.98 | 585.69 | 0.00 | 0.00 | 0.00 |
November | 145.21 | 0.00 | 145.21 | 15.48 | 752.42 | 0.00 | 0.00 | 0.00 |
December | 98.89 | 0.00 | 98.89 | 0.27 | 947.62 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 366.45 | 10.26 | 356.19 | 256.07 | 559.28 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 98.89 | 0.00 | 98.89 | 0.27 | 268.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 664.75 | 41.58 | 623.17 | 621.98 | 947.62 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.53 | 0.00 | 19.53 | 4.18 | 102.84 | 0.00 | 0.00 | 0.00 |
February | 30.49 | 0.00 | 30.49 | 9.10 | 98.69 | 0.00 | 0.00 | 0.00 |
March | 42.20 | 0.00 | 42.20 | 23.76 | 79.00 | 0.00 | 0.00 | 0.00 |
April | 68.95 | 0.46 | 68.49 | 61.27 | 63.68 | 0.00 | 0.00 | 0.00 |
May | 86.20 | 4.40 | 81.81 | 75.67 | 54.75 | 0.00 | 0.00 | 0.00 |
June | 94.97 | 5.94 | 89.03 | 103.93 | 41.02 | 0.00 | 0.00 | 0.00 |
July | 90.30 | 5.31 | 84.99 | 106.95 | 37.21 | 0.00 | 0.00 | 0.00 |
August | 71.09 | 1.33 | 69.76 | 85.43 | 39.38 | 0.00 | 0.00 | 0.00 |
September | 53.92 | 0.03 | 53.89 | 57.38 | 52.95 | 0.00 | 0.00 | 0.00 |
October | 34.53 | 0.00 | 34.53 | 24.07 | 72.75 | 0.00 | 0.00 | 0.00 |
November | 20.75 | 0.00 | 20.75 | 6.02 | 91.10 | 0.00 | 0.00 | 0.00 |
December | 14.13 | 0.00 | 14.13 | 1.05 | 116.14 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 52.35 | 1.47 | 50.89 | 46.76 | 70.66 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 14.13 | 0.00 | 14.13 | 1.05 | 37.21 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 94.97 | 5.94 | 89.03 | 106.95 | 116.14 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 148.18 | 59.02 | 89.17 | 105.81 | 367.97 | 0.00 | 0.00 | 0.00 |
February | 223.78 | 83.38 | 140.39 | 172.16 | 353.86 | 0.00 | 0.00 | 0.00 |
March | 232.50 | 45.86 | 186.64 | 183.75 | 286.70 | 0.00 | 0.00 | 0.00 |
April | 622.85 | 292.03 | 330.82 | 730.91 | 231.78 | 0.00 | 0.00 | 0.00 |
May | 655.80 | 286.04 | 369.76 | 745.77 | 209.04 | 0.00 | 0.00 | 0.00 |
June | 648.94 | 259.24 | 389.70 | 795.39 | 156.41 | 0.00 | 0.00 | 0.00 |
July | 662.31 | 281.33 | 380.98 | 848.88 | 141.06 | 0.00 | 0.00 | 0.00 |
August | 629.17 | 301.20 | 327.96 | 826.61 | 147.43 | 0.00 | 0.00 | 0.00 |
September | 564.86 | 300.14 | 264.72 | 715.33 | 191.91 | 0.00 | 0.00 | 0.00 |
October | 274.74 | 114.89 | 159.85 | 288.85 | 265.83 | 0.00 | 0.00 | 0.00 |
November | 142.19 | 48.38 | 93.81 | 101.86 | 329.47 | 0.00 | 0.00 | 0.00 |
December | 105.76 | 39.58 | 66.18 | 64.34 | 420.59 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 409.84 | 176.15 | 233.70 | 466.05 | 258.06 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 105.76 | 39.58 | 66.18 | 64.34 | 141.06 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 662.31 | 301.20 | 389.70 | 848.88 | 420.59 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 111.44 | 72.16 | 39.27 | 120.32 | 93.80 | 0.00 | 0.00 | 0.00 |
February | 135.22 | 82.42 | 52.81 | 148.53 | 93.09 | 0.00 | 0.00 | 0.00 |
March | 83.46 | 24.13 | 59.33 | 80.24 | 77.25 | 0.00 | 0.00 | 0.00 |
April | 171.09 | 75.81 | 95.28 | 213.08 | 64.97 | 0.00 | 0.00 | 0.00 |
May | 143.43 | 46.46 | 96.97 | 168.91 | 59.23 | 0.00 | 0.00 | 0.00 |
June | 132.40 | 32.02 | 100.38 | 167.09 | 43.67 | 0.00 | 0.00 | 0.00 |
July | 142.71 | 44.15 | 98.56 | 192.13 | 39.35 | 0.00 | 0.00 | 0.00 |
August | 167.62 | 75.10 | 92.52 | 231.64 | 40.82 | 0.00 | 0.00 | 0.00 |
September | 200.87 | 118.55 | 82.32 | 267.72 | 52.64 | 0.00 | 0.00 | 0.00 |
October | 134.03 | 77.27 | 56.76 | 161.18 | 70.92 | 0.00 | 0.00 | 0.00 |
November | 96.79 | 58.86 | 37.93 | 104.81 | 86.56 | 0.00 | 0.00 | 0.00 |
December | 76.81 | 49.25 | 27.56 | 79.39 | 109.99 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 132.78 | 62.77 | 70.02 | 161.06 | 69.24 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 76.81 | 24.13 | 27.56 | 79.39 | 39.35 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 200.87 | 118.55 | 100.38 | 267.72 | 109.99 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 24.73 | 0.00 | 24.73 | 1.66 | 152.43 | 0.00 | 0.00 | 0.00 |
February | 38.61 | 0.00 | 38.61 | 5.20 | 141.79 | 0.00 | 0.00 | 0.00 |
March | 53.44 | 0.00 | 53.44 | 19.13 | 112.77 | 0.00 | 0.00 | 0.00 |
April | 87.32 | 0.58 | 86.74 | 61.64 | 85.11 | 0.00 | 0.00 | 0.00 |
May | 109.17 | 5.57 | 103.61 | 79.24 | 67.97 | 0.00 | 0.00 | 0.00 |
June | 120.27 | 7.52 | 112.75 | 112.64 | 49.25 | 0.00 | 0.00 | 0.00 |
July | 114.35 | 6.73 | 107.63 | 115.30 | 43.96 | 0.00 | 0.00 | 0.00 |
August | 90.03 | 1.68 | 88.35 | 89.56 | 48.67 | 0.00 | 0.00 | 0.00 |
September | 68.29 | 0.04 | 68.25 | 57.87 | 70.34 | 0.00 | 0.00 | 0.00 |
October | 43.73 | 0.00 | 43.73 | 20.20 | 102.51 | 0.00 | 0.00 | 0.00 |
November | 26.27 | 0.00 | 26.27 | 2.87 | 132.84 | 0.00 | 0.00 | 0.00 |
December | 17.89 | 0.00 | 17.89 | 0.05 | 168.36 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.30 | 1.86 | 64.44 | 47.33 | 97.79 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 17.89 | 0.00 | 17.89 | 0.05 | 43.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 120.27 | 7.52 | 112.75 | 115.30 | 168.36 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 22.12 | 0.00 | 22.12 | 1.49 | 136.35 | 0.00 | 0.00 | 0.00 |
February | 34.55 | 0.00 | 34.55 | 4.65 | 126.86 | 0.00 | 0.00 | 0.00 |
March | 47.81 | 0.00 | 47.81 | 17.12 | 100.89 | 0.00 | 0.00 | 0.00 |
April | 78.13 | 0.52 | 77.61 | 55.15 | 76.15 | 0.00 | 0.00 | 0.00 |
May | 97.68 | 4.98 | 92.70 | 70.90 | 60.81 | 0.00 | 0.00 | 0.00 |
June | 107.61 | 6.73 | 100.88 | 100.78 | 44.06 | 0.00 | 0.00 | 0.00 |
July | 102.31 | 6.02 | 96.30 | 103.16 | 39.33 | 0.00 | 0.00 | 0.00 |
August | 80.55 | 1.51 | 79.05 | 80.13 | 43.54 | 0.00 | 0.00 | 0.00 |
September | 61.10 | 0.04 | 61.06 | 51.78 | 62.93 | 0.00 | 0.00 | 0.00 |
October | 39.12 | 0.00 | 39.12 | 18.07 | 91.71 | 0.00 | 0.00 | 0.00 |
November | 23.51 | 0.00 | 23.51 | 2.57 | 118.85 | 0.00 | 0.00 | 0.00 |
December | 16.01 | 0.00 | 16.01 | 0.05 | 150.61 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 59.32 | 1.66 | 57.66 | 42.35 | 87.49 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 16.01 | 0.00 | 16.01 | 0.05 | 39.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 107.61 | 6.73 | 100.88 | 103.16 | 150.61 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 416.03 | 269.40 | 146.62 | 415.43 | 395.53 | 0.00 | 0.00 | 0.00 |
February | 504.83 | 307.68 | 197.15 | 516.57 | 383.22 | 0.00 | 0.00 | 0.00 |
March | 311.58 | 90.07 | 221.51 | 257.78 | 319.56 | 0.00 | 0.00 | 0.00 |
April | 638.73 | 283.02 | 355.71 | 741.26 | 255.97 | 0.00 | 0.00 | 0.00 |
May | 535.46 | 173.46 | 362.00 | 578.91 | 221.77 | 0.00 | 0.00 | 0.00 |
June | 494.29 | 119.54 | 374.75 | 566.17 | 158.82 | 0.00 | 0.00 | 0.00 |
July | 532.79 | 164.83 | 367.96 | 656.33 | 141.73 | 0.00 | 0.00 | 0.00 |
August | 625.76 | 280.37 | 345.39 | 805.53 | 151.65 | 0.00 | 0.00 | 0.00 |
September | 749.91 | 442.60 | 307.31 | 945.16 | 204.27 | 0.00 | 0.00 | 0.00 |
October | 500.38 | 288.48 | 211.90 | 559.83 | 289.70 | 0.00 | 0.00 | 0.00 |
November | 361.34 | 219.74 | 141.60 | 362.46 | 362.92 | 0.00 | 0.00 | 0.00 |
December | 286.74 | 183.87 | 102.88 | 275.71 | 457.97 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 495.71 | 234.32 | 261.39 | 556.03 | 278.09 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 286.74 | 90.07 | 102.88 | 257.78 | 141.73 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 749.91 | 442.60 | 374.75 | 945.16 | 457.97 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.150959E+10 | 0.977552E+09 | 0.532037E+09 | 0.150950E+10 | 0.135393E+10 |
February | 0.165454E+10 | 0.100840E+10 | 0.646136E+09 | 0.169645E+10 | 0.118136E+10 |
March | 0.113060E+10 | 0.326821E+09 | 0.803783E+09 | 0.952353E+09 | 0.109129E+10 |
April | 0.224291E+10 | 0.993833E+09 | 0.124907E+10 | 0.259916E+10 | 0.862828E+09 |
May | 0.194297E+10 | 0.629412E+09 | 0.131355E+10 | 0.211598E+10 | 0.756874E+09 |
June | 0.173570E+10 | 0.419778E+09 | 0.131592E+10 | 0.199607E+10 | 0.529504E+09 |
July | 0.193326E+10 | 0.598097E+09 | 0.133516E+10 | 0.238046E+10 | 0.493387E+09 |
August | 0.227063E+10 | 0.101735E+10 | 0.125328E+10 | 0.290717E+10 | 0.538967E+09 |
September | 0.263332E+10 | 0.155420E+10 | 0.107911E+10 | 0.329708E+10 | 0.698258E+09 |
October | 0.181568E+10 | 0.104679E+10 | 0.768888E+09 | 0.202606E+10 | 0.994367E+09 |
November | 0.126888E+10 | 0.771630E+09 | 0.497246E+09 | 0.127837E+10 | 0.118943E+10 |
December | 0.104048E+10 | 0.667184E+09 | 0.373294E+09 | 0.100740E+10 | 0.152581E+10 |
Annual Sum or Average | 0.211785E+11 | 0.100111E+11 | 0.111675E+11 | 0.237661E+11 | 0.112160E+11 |
Minimum of Months | 0.104048E+10 | 0.326821E+09 | 0.373294E+09 | 0.952353E+09 | 0.493387E+09 |
Maximum of Months | 0.263332E+10 | 0.155420E+10 | 0.133516E+10 | 0.329708E+10 | 0.152581E+10 |
Report: WindowEnergyReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.425090E+10 | 0.275272E+10 | 0.149818E+10 | 0.421943E+10 | 0.384126E+10 |
February | 0.465908E+10 | 0.283960E+10 | 0.181948E+10 | 0.474657E+10 | 0.334406E+10 |
March | 0.318371E+10 | 0.920306E+09 | 0.226340E+10 | 0.264551E+10 | 0.308370E+10 |
April | 0.631588E+10 | 0.279857E+10 | 0.351731E+10 | 0.728738E+10 | 0.241406E+10 |
May | 0.547127E+10 | 0.177238E+10 | 0.369888E+10 | 0.592249E+10 | 0.211695E+10 |
June | 0.488762E+10 | 0.118207E+10 | 0.370556E+10 | 0.559043E+10 | 0.146993E+10 |
July | 0.544392E+10 | 0.168420E+10 | 0.375972E+10 | 0.667671E+10 | 0.136701E+10 |
August | 0.639395E+10 | 0.286480E+10 | 0.352915E+10 | 0.816433E+10 | 0.149469E+10 |
September | 0.741524E+10 | 0.437654E+10 | 0.303871E+10 | 0.926222E+10 | 0.194844E+10 |
October | 0.511283E+10 | 0.294769E+10 | 0.216514E+10 | 0.567755E+10 | 0.280653E+10 |
November | 0.357307E+10 | 0.217286E+10 | 0.140021E+10 | 0.357471E+10 | 0.337808E+10 |
December | 0.292991E+10 | 0.187874E+10 | 0.105117E+10 | 0.281308E+10 | 0.436191E+10 |
Annual Sum or Average | 0.596374E+11 | 0.281905E+11 | 0.314469E+11 | 0.665804E+11 | 0.316266E+11 |
Minimum of Months | 0.292991E+10 | 0.920306E+09 | 0.105117E+10 | 0.264551E+10 | 0.136701E+10 |
Maximum of Months | 0.741524E+10 | 0.437654E+10 | 0.375972E+10 | 0.926222E+10 | 0.436191E+10 |
Report: WindowEnergyReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.552217E+10 | 0.357594E+10 | 0.194622E+10 | 0.555513E+10 | 0.514394E+10 |
February | 0.605241E+10 | 0.368880E+10 | 0.236360E+10 | 0.625679E+10 | 0.446012E+10 |
March | 0.413581E+10 | 0.119553E+10 | 0.294029E+10 | 0.349494E+10 | 0.414259E+10 |
April | 0.820468E+10 | 0.363550E+10 | 0.456918E+10 | 0.965744E+10 | 0.320995E+10 |
May | 0.710749E+10 | 0.230242E+10 | 0.480506E+10 | 0.786320E+10 | 0.282640E+10 |
June | 0.634930E+10 | 0.153557E+10 | 0.481373E+10 | 0.743315E+10 | 0.197486E+10 |
July | 0.707196E+10 | 0.218787E+10 | 0.488409E+10 | 0.886818E+10 | 0.183663E+10 |
August | 0.830611E+10 | 0.372154E+10 | 0.458457E+10 | 0.108253E+11 | 0.199545E+10 |
September | 0.963282E+10 | 0.568537E+10 | 0.394745E+10 | 0.122663E+11 | 0.257880E+10 |
October | 0.664185E+10 | 0.382922E+10 | 0.281264E+10 | 0.750230E+10 | 0.374390E+10 |
November | 0.464162E+10 | 0.282267E+10 | 0.181896E+10 | 0.470784E+10 | 0.452412E+10 |
December | 0.380613E+10 | 0.244060E+10 | 0.136553E+10 | 0.369496E+10 | 0.586937E+10 |
Annual Sum or Average | 0.774723E+11 | 0.366210E+11 | 0.408513E+11 | 0.881255E+11 | 0.423061E+11 |
Minimum of Months | 0.380613E+10 | 0.119553E+10 | 0.136553E+10 | 0.349494E+10 | 0.183663E+10 |
Maximum of Months | 0.963282E+10 | 0.568537E+10 | 0.488409E+10 | 0.122663E+11 | 0.586937E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.298472E+09 | 0.193279E+09 | 0.105193E+09 | 0.301526E+09 | 0.270507E+09 |
February | 0.327132E+09 | 0.199379E+09 | 0.127753E+09 | 0.336712E+09 | 0.238262E+09 |
March | 0.223541E+09 | 64618063.64 | 0.158923E+09 | 0.189336E+09 | 0.219634E+09 |
April | 0.443463E+09 | 0.196498E+09 | 0.246965E+09 | 0.508733E+09 | 0.177929E+09 |
May | 0.384160E+09 | 0.124445E+09 | 0.259715E+09 | 0.408623E+09 | 0.158836E+09 |
June | 0.343181E+09 | 82997281.99 | 0.260183E+09 | 0.382385E+09 | 0.111801E+09 |
July | 0.382241E+09 | 0.118254E+09 | 0.263986E+09 | 0.458679E+09 | 0.103915E+09 |
August | 0.448945E+09 | 0.201148E+09 | 0.247797E+09 | 0.566394E+09 | 0.111876E+09 |
September | 0.520653E+09 | 0.307293E+09 | 0.213361E+09 | 0.647837E+09 | 0.143818E+09 |
October | 0.358991E+09 | 0.206968E+09 | 0.152023E+09 | 0.400379E+09 | 0.201042E+09 |
November | 0.250879E+09 | 0.152564E+09 | 98314557.38 | 0.254205E+09 | 0.238002E+09 |
December | 0.205721E+09 | 0.131914E+09 | 73806852.46 | 0.201598E+09 | 0.306359E+09 |
Annual Sum or Average | 0.418738E+10 | 0.197936E+10 | 0.220802E+10 | 0.465640E+10 | 0.228198E+10 |
Minimum of Months | 0.205721E+09 | 64618063.64 | 73806852.46 | 0.189336E+09 | 0.103915E+09 |
Maximum of Months | 0.520653E+09 | 0.307293E+09 | 0.263986E+09 | 0.647837E+09 | 0.306359E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.195660E+09 | 64128920.97 | 0.131532E+09 | 0.118727E+09 | 0.544334E+09 |
February | 0.312615E+09 | 0.133073E+09 | 0.179541E+09 | 0.245797E+09 | 0.466858E+09 |
March | 0.311355E+09 | 59870921.37 | 0.251484E+09 | 0.202274E+09 | 0.411226E+09 |
April | 0.709636E+09 | 0.281355E+09 | 0.428281E+09 | 0.739889E+09 | 0.323408E+09 |
May | 0.860491E+09 | 0.349933E+09 | 0.510558E+09 | 0.893982E+09 | 0.282252E+09 |
June | 0.899047E+09 | 0.370125E+09 | 0.528922E+09 | 0.101266E+10 | 0.200262E+09 |
July | 0.945570E+09 | 0.416516E+09 | 0.529053E+09 | 0.111247E+10 | 0.186940E+09 |
August | 0.795714E+09 | 0.344711E+09 | 0.451003E+09 | 0.941790E+09 | 0.204262E+09 |
September | 0.622261E+09 | 0.281272E+09 | 0.340989E+09 | 0.699941E+09 | 0.268256E+09 |
October | 0.342754E+09 | 0.124483E+09 | 0.218272E+09 | 0.304230E+09 | 0.384382E+09 |
November | 0.178958E+09 | 52801937.15 | 0.126156E+09 | 0.110406E+09 | 0.467741E+09 |
December | 0.103093E+09 | 20956149.08 | 82136943.91 | 36640758.67 | 0.608412E+09 |
Annual Sum or Average | 0.627716E+10 | 0.249923E+10 | 0.377793E+10 | 0.641880E+10 | 0.434833E+10 |
Minimum of Months | 0.103093E+09 | 20956149.08 | 82136943.91 | 36640758.67 | 0.186940E+09 |
Maximum of Months | 0.945570E+09 | 0.416516E+09 | 0.529053E+09 | 0.111247E+10 | 0.608412E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 52296148.79 | 0.00 | 52296148.79 | 5933558.99 | 0.299164E+09 |
February | 73759823.15 | 0.00 | 73759823.15 | 14778031.26 | 0.254793E+09 |
March | 0.113018E+09 | 763.87 | 0.113017E+09 | 45886354.12 | 0.226543E+09 |
April | 0.178718E+09 | 1187800.51 | 0.177530E+09 | 0.125396E+09 | 0.172497E+09 |
May | 0.230890E+09 | 11774052.52 | 0.219116E+09 | 0.163538E+09 | 0.142452E+09 |
June | 0.246156E+09 | 15397270.00 | 0.230758E+09 | 0.221322E+09 | 0.101736E+09 |
July | 0.241849E+09 | 14224473.17 | 0.227624E+09 | 0.233241E+09 | 94478050.32 |
August | 0.190413E+09 | 3560925.39 | 0.186852E+09 | 0.181140E+09 | 0.104579E+09 |
September | 0.139769E+09 | 82607.68 | 0.139686E+09 | 0.115834E+09 | 0.143740E+09 |
October | 92475413.30 | 0.00 | 92475413.30 | 46230489.26 | 0.206766E+09 |
November | 53771554.59 | 0.00 | 53771554.59 | 8906821.03 | 0.252023E+09 |
December | 37838893.74 | 0.00 | 37838893.74 | 736250.32 | 0.326748E+09 |
Annual Sum or Average | 0.165095E+10 | 46227893.14 | 0.160473E+10 | 0.116294E+10 | 0.232552E+10 |
Minimum of Months | 37838893.74 | 0.00 | 37838893.74 | 736250.32 | 94478050.32 |
Maximum of Months | 0.246156E+09 | 15397270.00 | 0.230758E+09 | 0.233241E+09 | 0.326748E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.195660E+09 | 64128920.97 | 0.131532E+09 | 0.126026E+09 | 0.537553E+09 |
February | 0.312615E+09 | 0.133073E+09 | 0.179541E+09 | 0.255138E+09 | 0.460333E+09 |
March | 0.311355E+09 | 59870921.37 | 0.251484E+09 | 0.207378E+09 | 0.408305E+09 |
April | 0.709636E+09 | 0.281355E+09 | 0.428281E+09 | 0.752063E+09 | 0.319597E+09 |
May | 0.860491E+09 | 0.349933E+09 | 0.510558E+09 | 0.902014E+09 | 0.280206E+09 |
June | 0.899047E+09 | 0.370125E+09 | 0.528922E+09 | 0.101755E+10 | 0.199072E+09 |
July | 0.945570E+09 | 0.416516E+09 | 0.529053E+09 | 0.111844E+10 | 0.185509E+09 |
August | 0.795714E+09 | 0.344711E+09 | 0.451003E+09 | 0.951549E+09 | 0.201434E+09 |
September | 0.622261E+09 | 0.281272E+09 | 0.340989E+09 | 0.713809E+09 | 0.263171E+09 |
October | 0.342754E+09 | 0.124483E+09 | 0.218272E+09 | 0.314911E+09 | 0.378689E+09 |
November | 0.178958E+09 | 52801937.15 | 0.126156E+09 | 0.116982E+09 | 0.461753E+09 |
December | 0.103093E+09 | 20956149.08 | 82136943.91 | 39933017.18 | 0.603261E+09 |
Annual Sum or Average | 0.627716E+10 | 0.249923E+10 | 0.377793E+10 | 0.651579E+10 | 0.429888E+10 |
Minimum of Months | 0.103093E+09 | 20956149.08 | 82136943.91 | 39933017.18 | 0.185509E+09 |
Maximum of Months | 0.945570E+09 | 0.416516E+09 | 0.529053E+09 | 0.111844E+10 | 0.603261E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.238730E+09 | 0.154592E+09 | 84137898.18 | 0.232469E+09 | 0.238130E+09 |
February | 0.261653E+09 | 0.159471E+09 | 0.102182E+09 | 0.261501E+09 | 0.210643E+09 |
March | 0.178797E+09 | 51684172.32 | 0.127113E+09 | 0.143661E+09 | 0.191606E+09 |
April | 0.354700E+09 | 0.157167E+09 | 0.197533E+09 | 0.397427E+09 | 0.161870E+09 |
May | 0.307267E+09 | 99536592.27 | 0.207730E+09 | 0.317327E+09 | 0.146168E+09 |
June | 0.274490E+09 | 66384623.48 | 0.208105E+09 | 0.297883E+09 | 0.105569E+09 |
July | 0.305732E+09 | 94584426.86 | 0.211147E+09 | 0.358995E+09 | 99408841.43 |
August | 0.359085E+09 | 0.160887E+09 | 0.198198E+09 | 0.445026E+09 | 0.107886E+09 |
September | 0.416440E+09 | 0.245785E+09 | 0.170655E+09 | 0.508980E+09 | 0.135952E+09 |
October | 0.287136E+09 | 0.165542E+09 | 0.121594E+09 | 0.310766E+09 | 0.187453E+09 |
November | 0.200663E+09 | 0.122027E+09 | 78636007.32 | 0.195744E+09 | 0.215690E+09 |
December | 0.164544E+09 | 0.105510E+09 | 59033741.75 | 0.158784E+09 | 0.248892E+09 |
Annual Sum or Average | 0.334924E+10 | 0.158317E+10 | 0.176607E+10 | 0.362856E+10 | 0.204927E+10 |
Minimum of Months | 0.164544E+09 | 51684172.32 | 59033741.75 | 0.143661E+09 | 99408841.43 |
Maximum of Months | 0.416440E+09 | 0.245785E+09 | 0.211147E+09 | 0.508980E+09 | 0.248892E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 41842464.75 | 0.00 | 41842464.75 | 3383701.88 | 0.253966E+09 |
February | 59015680.35 | 0.00 | 59015680.35 | 9510838.88 | 0.213762E+09 |
March | 90426079.04 | 611.18 | 90425467.87 | 33113323.56 | 0.190646E+09 |
April | 0.142993E+09 | 950366.37 | 0.142043E+09 | 0.102841E+09 | 0.139358E+09 |
May | 0.184736E+09 | 9420490.59 | 0.175316E+09 | 0.134907E+09 | 0.114931E+09 |
June | 0.196951E+09 | 12319448.80 | 0.184631E+09 | 0.183716E+09 | 80865322.40 |
July | 0.193505E+09 | 11381086.97 | 0.182124E+09 | 0.194284E+09 | 74587656.09 |
August | 0.152351E+09 | 2849117.93 | 0.149502E+09 | 0.151839E+09 | 82370167.36 |
September | 0.111830E+09 | 66094.90 | 0.111764E+09 | 96100804.10 | 0.114947E+09 |
October | 73990137.15 | 0.00 | 73990137.15 | 35529048.83 | 0.173023E+09 |
November | 43022945.85 | 0.00 | 43022945.85 | 5443946.53 | 0.215092E+09 |
December | 30275127.60 | 0.00 | 30275127.60 | 186279.94 | 0.279647E+09 |
Annual Sum or Average | 0.132094E+10 | 36987216.73 | 0.128395E+10 | 0.950856E+09 | 0.193320E+10 |
Minimum of Months | 30275127.60 | 0.00 | 30275127.60 | 186279.94 | 74587656.09 |
Maximum of Months | 0.196951E+09 | 12319448.80 | 0.184631E+09 | 0.194284E+09 | 0.279647E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.198462E+09 | 79042420.23 | 0.119420E+09 | 0.115492E+09 | 0.535928E+09 |
February | 0.270698E+09 | 0.100866E+09 | 0.169832E+09 | 0.177719E+09 | 0.456499E+09 |
March | 0.311380E+09 | 61414734.22 | 0.249966E+09 | 0.198987E+09 | 0.407046E+09 |
April | 0.807271E+09 | 0.378498E+09 | 0.428772E+09 | 0.852478E+09 | 0.309750E+09 |
May | 0.878305E+09 | 0.383093E+09 | 0.495212E+09 | 0.906452E+09 | 0.273161E+09 |
June | 0.841083E+09 | 0.335996E+09 | 0.505087E+09 | 0.930767E+09 | 0.194113E+09 |
July | 0.887034E+09 | 0.376787E+09 | 0.510247E+09 | 0.102590E+10 | 0.179954E+09 |
August | 0.842638E+09 | 0.403400E+09 | 0.439238E+09 | 0.997095E+09 | 0.194932E+09 |
September | 0.732111E+09 | 0.389014E+09 | 0.343096E+09 | 0.832757E+09 | 0.257828E+09 |
October | 0.367956E+09 | 0.153873E+09 | 0.214083E+09 | 0.330622E+09 | 0.377404E+09 |
November | 0.184287E+09 | 62706204.31 | 0.121580E+09 | 0.106692E+09 | 0.456861E+09 |
December | 0.141644E+09 | 53003264.31 | 88640916.87 | 70837982.01 | 0.590787E+09 |
Annual Sum or Average | 0.646287E+10 | 0.277770E+10 | 0.368517E+10 | 0.654580E+10 | 0.423426E+10 |
Minimum of Months | 0.141644E+09 | 53003264.31 | 88640916.87 | 70837982.01 | 0.179954E+09 |
Maximum of Months | 0.887034E+09 | 0.403400E+09 | 0.510247E+09 | 0.102590E+10 | 0.590787E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.298472E+09 | 0.193279E+09 | 0.105193E+09 | 0.300978E+09 | 0.270068E+09 |
February | 0.327132E+09 | 0.199379E+09 | 0.127753E+09 | 0.336578E+09 | 0.237146E+09 |
March | 0.223541E+09 | 64618063.64 | 0.158923E+09 | 0.188238E+09 | 0.219094E+09 |
April | 0.443463E+09 | 0.196498E+09 | 0.246965E+09 | 0.503996E+09 | 0.177418E+09 |
May | 0.384160E+09 | 0.124445E+09 | 0.259715E+09 | 0.404853E+09 | 0.157519E+09 |
June | 0.343181E+09 | 82997281.99 | 0.260183E+09 | 0.380713E+09 | 0.109875E+09 |
July | 0.382241E+09 | 0.118254E+09 | 0.263986E+09 | 0.456624E+09 | 0.102144E+09 |
August | 0.448945E+09 | 0.201148E+09 | 0.247797E+09 | 0.563652E+09 | 0.110843E+09 |
September | 0.520653E+09 | 0.307293E+09 | 0.213361E+09 | 0.643908E+09 | 0.143394E+09 |
October | 0.358991E+09 | 0.206968E+09 | 0.152023E+09 | 0.398515E+09 | 0.200561E+09 |
November | 0.250879E+09 | 0.152564E+09 | 98314557.38 | 0.253738E+09 | 0.237570E+09 |
December | 0.205721E+09 | 0.131914E+09 | 73806852.46 | 0.200731E+09 | 0.306763E+09 |
Annual Sum or Average | 0.418738E+10 | 0.197936E+10 | 0.220802E+10 | 0.463252E+10 | 0.227239E+10 |
Minimum of Months | 0.205721E+09 | 64618063.64 | 73806852.46 | 0.188238E+09 | 0.102144E+09 |
Maximum of Months | 0.520653E+09 | 0.307293E+09 | 0.263986E+09 | 0.643908E+09 | 0.306763E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 52296148.79 | 0.00 | 52296148.79 | 5452628.70 | 0.298501E+09 |
February | 73759823.15 | 0.00 | 73759823.15 | 14011875.59 | 0.253118E+09 |
March | 0.113018E+09 | 763.87 | 0.113017E+09 | 44778733.77 | 0.226046E+09 |
April | 0.178718E+09 | 1187800.51 | 0.177530E+09 | 0.119792E+09 | 0.172518E+09 |
May | 0.230890E+09 | 11774052.52 | 0.219116E+09 | 0.159164E+09 | 0.141563E+09 |
June | 0.246156E+09 | 15397270.00 | 0.230758E+09 | 0.219387E+09 | 0.100331E+09 |
July | 0.241849E+09 | 14224473.17 | 0.227624E+09 | 0.230665E+09 | 93118212.80 |
August | 0.190413E+09 | 3560925.39 | 0.186852E+09 | 0.177018E+09 | 0.103689E+09 |
September | 0.139769E+09 | 82607.68 | 0.139686E+09 | 0.110397E+09 | 0.143910E+09 |
October | 92475413.30 | 0.00 | 92475413.30 | 44183648.63 | 0.206450E+09 |
November | 53771554.59 | 0.00 | 53771554.59 | 8420373.53 | 0.251274E+09 |
December | 37838893.74 | 0.00 | 37838893.74 | 596211.63 | 0.326823E+09 |
Annual Sum or Average | 0.165095E+10 | 46227893.14 | 0.160473E+10 | 0.113387E+10 | 0.231734E+10 |
Minimum of Months | 37838893.74 | 0.00 | 37838893.74 | 596211.63 | 93118212.80 |
Maximum of Months | 0.246156E+09 | 15397270.00 | 0.230758E+09 | 0.230665E+09 | 0.326823E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.198462E+09 | 79042420.23 | 0.119420E+09 | 0.120334E+09 | 0.526279E+09 |
February | 0.270698E+09 | 0.100866E+09 | 0.169832E+09 | 0.184819E+09 | 0.447567E+09 |
March | 0.311380E+09 | 61414734.22 | 0.249966E+09 | 0.203623E+09 | 0.403732E+09 |
April | 0.807271E+09 | 0.378498E+09 | 0.428772E+09 | 0.862454E+09 | 0.305815E+09 |
May | 0.878305E+09 | 0.383093E+09 | 0.495212E+09 | 0.913085E+09 | 0.271014E+09 |
June | 0.841083E+09 | 0.335996E+09 | 0.505087E+09 | 0.934956E+09 | 0.193086E+09 |
July | 0.887034E+09 | 0.376787E+09 | 0.510247E+09 | 0.103088E+10 | 0.178623E+09 |
August | 0.842638E+09 | 0.403400E+09 | 0.439238E+09 | 0.100476E+10 | 0.192224E+09 |
September | 0.732111E+09 | 0.389014E+09 | 0.343096E+09 | 0.843449E+09 | 0.252892E+09 |
October | 0.367956E+09 | 0.153873E+09 | 0.214083E+09 | 0.340172E+09 | 0.371286E+09 |
November | 0.184287E+09 | 62706204.31 | 0.121580E+09 | 0.111802E+09 | 0.449053E+09 |
December | 0.141644E+09 | 53003264.31 | 88640916.87 | 73260550.40 | 0.583509E+09 |
Annual Sum or Average | 0.646287E+10 | 0.277770E+10 | 0.368517E+10 | 0.662359E+10 | 0.417508E+10 |
Minimum of Months | 0.141644E+09 | 53003264.31 | 88640916.87 | 73260550.40 | 0.178623E+09 |
Maximum of Months | 0.887034E+09 | 0.403400E+09 | 0.510247E+09 | 0.103088E+10 | 0.583509E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 66229772.74 | 0.00 | 66229772.74 | 5100125.80 | 0.407707E+09 |
February | 93412162.03 | 0.00 | 93412162.03 | 14266772.54 | 0.341635E+09 |
March | 0.143130E+09 | 967.39 | 0.143129E+09 | 53853262.42 | 0.301235E+09 |
April | 0.226335E+09 | 1504274.40 | 0.224831E+09 | 0.167162E+09 | 0.219448E+09 |
May | 0.292407E+09 | 14911094.62 | 0.277496E+09 | 0.221343E+09 | 0.179990E+09 |
June | 0.311741E+09 | 19499670.94 | 0.292241E+09 | 0.301777E+09 | 0.125792E+09 |
July | 0.306286E+09 | 18014397.76 | 0.288272E+09 | 0.318477E+09 | 0.116534E+09 |
August | 0.241146E+09 | 4509687.32 | 0.236636E+09 | 0.248174E+09 | 0.129321E+09 |
September | 0.177008E+09 | 104617.41 | 0.176903E+09 | 0.156064E+09 | 0.181214E+09 |
October | 0.117114E+09 | 0.00 | 0.117114E+09 | 57387090.36 | 0.272706E+09 |
November | 68098281.09 | 0.00 | 68098281.09 | 8446420.20 | 0.342367E+09 |
December | 47920571.43 | 0.00 | 47920571.43 | 213442.30 | 0.449076E+09 |
Annual Sum or Average | 0.209083E+10 | 58544709.85 | 0.203228E+10 | 0.155226E+10 | 0.306702E+10 |
Minimum of Months | 47920571.43 | 0.00 | 47920571.43 | 213442.30 | 0.116534E+09 |
Maximum of Months | 0.311741E+09 | 19499670.94 | 0.292241E+09 | 0.318477E+09 | 0.449076E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 24415036.59 | 0.00 | 24415036.59 | 1880117.55 | 0.150298E+09 |
February | 34435590.82 | 0.00 | 34435590.82 | 5259323.10 | 0.125941E+09 |
March | 52763527.24 | 356.62 | 52763170.61 | 19852542.42 | 0.111048E+09 |
April | 83436499.74 | 554537.83 | 82881961.91 | 61622842.00 | 80897459.78 |
May | 0.107793E+09 | 5496846.90 | 0.102297E+09 | 81596345.24 | 66351637.67 |
June | 0.114921E+09 | 7188386.13 | 0.107732E+09 | 0.111247E+09 | 46372209.58 |
July | 0.112910E+09 | 6640852.93 | 0.106269E+09 | 0.117404E+09 | 42959264.91 |
August | 88896459.85 | 1662457.48 | 87234002.37 | 91487312.50 | 47673088.56 |
September | 65252479.21 | 38566.31 | 65213912.90 | 57531756.62 | 66802851.80 |
October | 43173171.48 | 0.00 | 43173171.48 | 21155257.72 | 0.100531E+09 |
November | 25103846.14 | 0.00 | 25103846.14 | 3113700.22 | 0.126211E+09 |
December | 17665506.86 | 0.00 | 17665506.86 | 78683.67 | 0.165548E+09 |
Annual Sum or Average | 0.770766E+09 | 21582004.20 | 0.749184E+09 | 0.572229E+09 | 0.113063E+10 |
Minimum of Months | 17665506.86 | 0.00 | 17665506.86 | 78683.67 | 42959264.91 |
Maximum of Months | 0.114921E+09 | 7188386.13 | 0.107732E+09 | 0.117404E+09 | 0.165548E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.139266E+09 | 90183137.34 | 49082764.60 | 0.140092E+09 | 0.132374E+09 |
February | 0.152638E+09 | 93029421.80 | 59608931.11 | 0.157553E+09 | 0.115376E+09 |
March | 0.104303E+09 | 30150528.10 | 74152630.13 | 87699571.68 | 0.106592E+09 |
April | 0.206918E+09 | 91685143.13 | 0.115233E+09 | 0.243235E+09 | 82328392.75 |
May | 0.179248E+09 | 58065761.49 | 0.121182E+09 | 0.197256E+09 | 73139575.53 |
June | 0.160127E+09 | 38726197.32 | 0.121400E+09 | 0.187050E+09 | 50511708.82 |
July | 0.178352E+09 | 55176861.55 | 0.123175E+09 | 0.223469E+09 | 46772860.82 |
August | 0.209476E+09 | 93855004.78 | 0.115621E+09 | 0.273225E+09 | 50225077.00 |
September | 0.242935E+09 | 0.143382E+09 | 99553201.59 | 0.309252E+09 | 65629877.96 |
October | 0.167504E+09 | 96570534.75 | 70933434.58 | 0.189205E+09 | 96121472.20 |
November | 0.117059E+09 | 71185959.25 | 45873176.30 | 0.118501E+09 | 0.116755E+09 |
December | 95988358.37 | 61550378.44 | 34437979.94 | 93013841.02 | 0.152421E+09 |
Annual Sum or Average | 0.195381E+10 | 0.923561E+09 | 0.103025E+10 | 0.221955E+10 | 0.108825E+10 |
Minimum of Months | 95988358.37 | 30150528.10 | 34437979.94 | 87699571.68 | 46772860.82 |
Maximum of Months | 0.242935E+09 | 0.143382E+09 | 0.123175E+09 | 0.309252E+09 | 0.152421E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.377996E+09 | 0.244775E+09 | 0.133221E+09 | 0.380238E+09 | 0.359290E+09 |
February | 0.414292E+09 | 0.252501E+09 | 0.161791E+09 | 0.427630E+09 | 0.313154E+09 |
March | 0.283100E+09 | 81834700.42 | 0.201265E+09 | 0.238035E+09 | 0.289313E+09 |
April | 0.561618E+09 | 0.248852E+09 | 0.312766E+09 | 0.660191E+09 | 0.223456E+09 |
May | 0.486515E+09 | 0.157602E+09 | 0.328912E+09 | 0.535393E+09 | 0.198516E+09 |
June | 0.434616E+09 | 0.105111E+09 | 0.329506E+09 | 0.507691E+09 | 0.137099E+09 |
July | 0.484084E+09 | 0.149761E+09 | 0.334322E+09 | 0.606541E+09 | 0.126951E+09 |
August | 0.568561E+09 | 0.254742E+09 | 0.313819E+09 | 0.741589E+09 | 0.136321E+09 |
September | 0.659375E+09 | 0.389167E+09 | 0.270208E+09 | 0.839374E+09 | 0.178133E+09 |
October | 0.454640E+09 | 0.262112E+09 | 0.192528E+09 | 0.513540E+09 | 0.260893E+09 |
November | 0.317722E+09 | 0.193213E+09 | 0.124509E+09 | 0.321637E+09 | 0.316898E+09 |
December | 0.260532E+09 | 0.167060E+09 | 93471721.68 | 0.252459E+09 | 0.413702E+09 |
Annual Sum or Average | 0.530305E+10 | 0.250673E+10 | 0.279632E+10 | 0.602432E+10 | 0.295373E+10 |
Minimum of Months | 0.260532E+09 | 81834700.42 | 93471721.68 | 0.238035E+09 | 0.126951E+09 |
Maximum of Months | 0.659375E+09 | 0.389167E+09 | 0.334322E+09 | 0.839374E+09 | 0.413702E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.298472E+09 | 0.193279E+09 | 0.105193E+09 | 0.302417E+09 | 0.266109E+09 |
February | 0.327132E+09 | 0.199379E+09 | 0.127753E+09 | 0.336859E+09 | 0.235504E+09 |
March | 0.223541E+09 | 64618063.64 | 0.158923E+09 | 0.189720E+09 | 0.216298E+09 |
April | 0.443463E+09 | 0.196498E+09 | 0.246965E+09 | 0.504645E+09 | 0.177274E+09 |
May | 0.384160E+09 | 0.124445E+09 | 0.259715E+09 | 0.403837E+09 | 0.159302E+09 |
June | 0.343181E+09 | 82997281.99 | 0.260183E+09 | 0.376917E+09 | 0.112562E+09 |
July | 0.382241E+09 | 0.118254E+09 | 0.263986E+09 | 0.452778E+09 | 0.104691E+09 |
August | 0.448945E+09 | 0.201148E+09 | 0.247797E+09 | 0.561030E+09 | 0.112189E+09 |
September | 0.520653E+09 | 0.307293E+09 | 0.213361E+09 | 0.643478E+09 | 0.143711E+09 |
October | 0.358991E+09 | 0.206968E+09 | 0.152023E+09 | 0.399437E+09 | 0.198570E+09 |
November | 0.250879E+09 | 0.152564E+09 | 98314557.38 | 0.254581E+09 | 0.234289E+09 |
December | 0.205721E+09 | 0.131914E+09 | 73806852.46 | 0.202125E+09 | 0.302728E+09 |
Annual Sum or Average | 0.418738E+10 | 0.197936E+10 | 0.220802E+10 | 0.462783E+10 | 0.226323E+10 |
Minimum of Months | 0.205721E+09 | 64618063.64 | 73806852.46 | 0.189720E+09 | 0.104691E+09 |
Maximum of Months | 0.520653E+09 | 0.307293E+09 | 0.263986E+09 | 0.643478E+09 | 0.302728E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.195660E+09 | 64128920.97 | 0.131532E+09 | 0.119939E+09 | 0.534524E+09 |
February | 0.312615E+09 | 0.133073E+09 | 0.179541E+09 | 0.246297E+09 | 0.460583E+09 |
March | 0.311355E+09 | 59870921.37 | 0.251484E+09 | 0.202868E+09 | 0.404608E+09 |
April | 0.709636E+09 | 0.281355E+09 | 0.428281E+09 | 0.731495E+09 | 0.321543E+09 |
May | 0.860491E+09 | 0.349933E+09 | 0.510558E+09 | 0.882604E+09 | 0.282607E+09 |
June | 0.899047E+09 | 0.370125E+09 | 0.528922E+09 | 0.999152E+09 | 0.201314E+09 |
July | 0.945570E+09 | 0.416516E+09 | 0.529053E+09 | 0.109862E+10 | 0.187950E+09 |
August | 0.795714E+09 | 0.344711E+09 | 0.451003E+09 | 0.930308E+09 | 0.204493E+09 |
September | 0.622261E+09 | 0.281272E+09 | 0.340989E+09 | 0.692641E+09 | 0.267641E+09 |
October | 0.342754E+09 | 0.124483E+09 | 0.218272E+09 | 0.302906E+09 | 0.379034E+09 |
November | 0.178958E+09 | 52801937.15 | 0.126156E+09 | 0.111359E+09 | 0.459825E+09 |
December | 0.103093E+09 | 20956149.08 | 82136943.91 | 37389405.64 | 0.600122E+09 |
Annual Sum or Average | 0.627716E+10 | 0.249923E+10 | 0.377793E+10 | 0.635558E+10 | 0.430424E+10 |
Minimum of Months | 0.103093E+09 | 20956149.08 | 82136943.91 | 37389405.64 | 0.187950E+09 |
Maximum of Months | 0.945570E+09 | 0.416516E+09 | 0.529053E+09 | 0.109862E+10 | 0.600122E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 52296148.79 | 0.00 | 52296148.79 | 6444896.80 | 0.293723E+09 |
February | 73759823.15 | 0.00 | 73759823.15 | 15459905.10 | 0.250999E+09 |
March | 0.113018E+09 | 763.87 | 0.113017E+09 | 46655341.13 | 0.222740E+09 |
April | 0.178718E+09 | 1187800.51 | 0.177530E+09 | 0.122179E+09 | 0.171539E+09 |
May | 0.230890E+09 | 11774052.52 | 0.219116E+09 | 0.159030E+09 | 0.142543E+09 |
June | 0.246156E+09 | 15397270.00 | 0.230758E+09 | 0.215603E+09 | 0.102248E+09 |
July | 0.241849E+09 | 14224473.17 | 0.227624E+09 | 0.227394E+09 | 95013658.90 |
August | 0.190413E+09 | 3560925.39 | 0.186852E+09 | 0.176476E+09 | 0.104793E+09 |
September | 0.139769E+09 | 82607.68 | 0.139686E+09 | 0.113354E+09 | 0.143302E+09 |
October | 92475413.30 | 0.00 | 92475413.30 | 46463774.55 | 0.203493E+09 |
November | 53771554.59 | 0.00 | 53771554.59 | 9563912.95 | 0.247158E+09 |
December | 37838893.74 | 0.00 | 37838893.74 | 909325.64 | 0.321913E+09 |
Annual Sum or Average | 0.165095E+10 | 46227893.14 | 0.160473E+10 | 0.113953E+10 | 0.229947E+10 |
Minimum of Months | 37838893.74 | 0.00 | 37838893.74 | 909325.64 | 95013658.90 |
Maximum of Months | 0.246156E+09 | 15397270.00 | 0.230758E+09 | 0.227394E+09 | 0.321913E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.195660E+09 | 64128920.97 | 0.131532E+09 | 0.127548E+09 | 0.528208E+09 |
February | 0.312615E+09 | 0.133073E+09 | 0.179541E+09 | 0.256379E+09 | 0.453891E+09 |
March | 0.311355E+09 | 59870921.37 | 0.251484E+09 | 0.208422E+09 | 0.401581E+09 |
April | 0.709636E+09 | 0.281355E+09 | 0.428281E+09 | 0.743933E+09 | 0.317500E+09 |
May | 0.860491E+09 | 0.349933E+09 | 0.510558E+09 | 0.890622E+09 | 0.280431E+09 |
June | 0.899047E+09 | 0.370125E+09 | 0.528922E+09 | 0.100368E+10 | 0.200107E+09 |
July | 0.945570E+09 | 0.416516E+09 | 0.529053E+09 | 0.110415E+10 | 0.186499E+09 |
August | 0.795714E+09 | 0.344711E+09 | 0.451003E+09 | 0.939435E+09 | 0.201562E+09 |
September | 0.622261E+09 | 0.281272E+09 | 0.340989E+09 | 0.706659E+09 | 0.262191E+09 |
October | 0.342754E+09 | 0.124483E+09 | 0.218272E+09 | 0.314420E+09 | 0.372818E+09 |
November | 0.178958E+09 | 52801937.15 | 0.126156E+09 | 0.118475E+09 | 0.453830E+09 |
December | 0.103093E+09 | 20956149.08 | 82136943.91 | 40691416.10 | 0.595664E+09 |
Annual Sum or Average | 0.627716E+10 | 0.249923E+10 | 0.377793E+10 | 0.645442E+10 | 0.425428E+10 |
Minimum of Months | 0.103093E+09 | 20956149.08 | 82136943.91 | 40691416.10 | 0.186499E+09 |
Maximum of Months | 0.945570E+09 | 0.416516E+09 | 0.529053E+09 | 0.110415E+10 | 0.595664E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.437738E+09 | 0.283462E+09 | 0.154276E+09 | 0.428844E+09 | 0.407517E+09 |
February | 0.479770E+09 | 0.292408E+09 | 0.187362E+09 | 0.481938E+09 | 0.359469E+09 |
March | 0.327844E+09 | 94768591.74 | 0.233075E+09 | 0.268093E+09 | 0.327567E+09 |
April | 0.650381E+09 | 0.288183E+09 | 0.362198E+09 | 0.733872E+09 | 0.262774E+09 |
May | 0.563408E+09 | 0.182511E+09 | 0.380897E+09 | 0.590598E+09 | 0.233879E+09 |
June | 0.503307E+09 | 0.121723E+09 | 0.381584E+09 | 0.556560E+09 | 0.162928E+09 |
July | 0.560592E+09 | 0.173431E+09 | 0.387162E+09 | 0.667907E+09 | 0.151275E+09 |
August | 0.658421E+09 | 0.295003E+09 | 0.363418E+09 | 0.822674E+09 | 0.163813E+09 |
September | 0.763588E+09 | 0.450674E+09 | 0.312914E+09 | 0.937304E+09 | 0.214043E+09 |
October | 0.526495E+09 | 0.303539E+09 | 0.222957E+09 | 0.575133E+09 | 0.302648E+09 |
November | 0.367938E+09 | 0.223750E+09 | 0.144188E+09 | 0.362076E+09 | 0.360724E+09 |
December | 0.301709E+09 | 0.193464E+09 | 0.108245E+09 | 0.286580E+09 | 0.463935E+09 |
Annual Sum or Average | 0.614119E+10 | 0.290292E+10 | 0.323827E+10 | 0.671158E+10 | 0.341057E+10 |
Minimum of Months | 0.301709E+09 | 94768591.74 | 0.108245E+09 | 0.268093E+09 | 0.151275E+09 |
Maximum of Months | 0.763588E+09 | 0.450674E+09 | 0.387162E+09 | 0.937304E+09 | 0.463935E+09 |
Report: WindowEnergyReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.366059E+09 | 0.00 | 0.366059E+09 | 26497778.32 | 0.223801E+10 |
February | 0.516299E+09 | 0.00 | 0.516299E+09 | 74382455.92 | 0.188701E+10 |
March | 0.791093E+09 | 5346.90 | 0.791088E+09 | 0.282911E+09 | 0.167360E+10 |
April | 0.125098E+10 | 8314288.68 | 0.124266E+10 | 0.891290E+09 | 0.123233E+10 |
May | 0.161617E+10 | 82415246.22 | 0.153375E+10 | 0.116584E+10 | 0.104214E+10 |
June | 0.172303E+10 | 0.107777E+09 | 0.161525E+10 | 0.160015E+10 | 0.748582E+09 |
July | 0.169288E+10 | 99567541.14 | 0.159331E+10 | 0.169814E+10 | 0.695319E+09 |
August | 0.133284E+10 | 24925533.69 | 0.130792E+10 | 0.133119E+10 | 0.761643E+09 |
September | 0.978343E+09 | 578231.83 | 0.977764E+09 | 0.842619E+09 | 0.103235E+10 |
October | 0.647303E+09 | 0.00 | 0.647303E+09 | 0.305403E+09 | 0.153098E+10 |
November | 0.376387E+09 | 0.00 | 0.376387E+09 | 43798847.09 | 0.190778E+10 |
December | 0.264862E+09 | 0.00 | 0.264862E+09 | 1050216.35 | 0.249173E+10 |
Annual Sum or Average | 0.115562E+11 | 0.323583E+09 | 0.112327E+11 | 0.826327E+10 | 0.172415E+11 |
Minimum of Months | 0.264862E+09 | 0.00 | 0.264862E+09 | 1050216.35 | 0.695319E+09 |
Maximum of Months | 0.172303E+10 | 0.107777E+09 | 0.161525E+10 | 0.169814E+10 | 0.249173E+10 |
Report: WindowEnergyReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.366059E+09 | 0.00 | 0.366059E+09 | 23962966.92 | 0.228060E+10 |
February | 0.516299E+09 | 0.00 | 0.516299E+09 | 69061034.79 | 0.192336E+10 |
March | 0.791093E+09 | 5346.90 | 0.791088E+09 | 0.271905E+09 | 0.171042E+10 |
April | 0.125098E+10 | 8314288.68 | 0.124266E+10 | 0.871816E+09 | 0.126026E+10 |
May | 0.161617E+10 | 82415246.22 | 0.153375E+10 | 0.113799E+10 | 0.106719E+10 |
June | 0.172303E+10 | 0.107777E+09 | 0.161525E+10 | 0.157013E+10 | 0.771208E+09 |
July | 0.169288E+10 | 99567541.14 | 0.159331E+10 | 0.166592E+10 | 0.717867E+09 |
August | 0.133284E+10 | 24925533.69 | 0.130792E+10 | 0.130486E+10 | 0.787524E+09 |
September | 0.978343E+09 | 578231.83 | 0.977764E+09 | 0.824276E+09 | 0.106183E+10 |
October | 0.647303E+09 | 0.00 | 0.647303E+09 | 0.294559E+09 | 0.156870E+10 |
November | 0.376387E+09 | 0.00 | 0.376387E+09 | 40115672.81 | 0.195028E+10 |
December | 0.264862E+09 | 0.00 | 0.264862E+09 | 720839.11 | 0.253811E+10 |
Annual Sum or Average | 0.115562E+11 | 0.323583E+09 | 0.112327E+11 | 0.807531E+10 | 0.176373E+11 |
Minimum of Months | 0.264862E+09 | 0.00 | 0.264862E+09 | 720839.11 | 0.717867E+09 |
Maximum of Months | 0.172303E+10 | 0.107777E+09 | 0.161525E+10 | 0.166592E+10 | 0.253811E+10 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 52296148.79 | 0.00 | 52296148.79 | 11197718.70 | 0.275451E+09 |
February | 73759823.15 | 0.00 | 73759823.15 | 22022363.95 | 0.238750E+09 |
March | 0.113018E+09 | 763.87 | 0.113017E+09 | 63645869.80 | 0.211603E+09 |
April | 0.178718E+09 | 1187800.51 | 0.177530E+09 | 0.158808E+09 | 0.165054E+09 |
May | 0.230890E+09 | 11774052.52 | 0.219116E+09 | 0.202687E+09 | 0.146637E+09 |
June | 0.246156E+09 | 15397270.00 | 0.230758E+09 | 0.269392E+09 | 0.106315E+09 |
July | 0.241849E+09 | 14224473.17 | 0.227624E+09 | 0.286452E+09 | 99676313.38 |
August | 0.190413E+09 | 3560925.39 | 0.186852E+09 | 0.228821E+09 | 0.105466E+09 |
September | 0.139769E+09 | 82607.68 | 0.139686E+09 | 0.148719E+09 | 0.137241E+09 |
October | 92475413.30 | 0.00 | 92475413.30 | 64467538.57 | 0.194855E+09 |
November | 53771554.59 | 0.00 | 53771554.59 | 15609586.83 | 0.236142E+09 |
December | 37838893.74 | 0.00 | 37838893.74 | 2809468.21 | 0.311066E+09 |
Annual Sum or Average | 0.165095E+10 | 46227893.14 | 0.160473E+10 | 0.147463E+10 | 0.222826E+10 |
Minimum of Months | 37838893.74 | 0.00 | 37838893.74 | 2809468.21 | 99676313.38 |
Maximum of Months | 0.246156E+09 | 15397270.00 | 0.230758E+09 | 0.286452E+09 | 0.311066E+09 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.396896E+09 | 0.158074E+09 | 0.238823E+09 | 0.283392E+09 | 0.985564E+09 |
February | 0.541358E+09 | 0.201718E+09 | 0.339640E+09 | 0.416486E+09 | 0.856063E+09 |
March | 0.622717E+09 | 0.122821E+09 | 0.499896E+09 | 0.492152E+09 | 0.767910E+09 |
April | 0.161443E+10 | 0.756943E+09 | 0.857483E+09 | 0.189453E+10 | 0.600771E+09 |
May | 0.175648E+10 | 0.766132E+09 | 0.990353E+09 | 0.199746E+10 | 0.559899E+09 |
June | 0.168205E+10 | 0.671945E+09 | 0.101010E+10 | 0.206165E+10 | 0.405408E+09 |
July | 0.177394E+10 | 0.753521E+09 | 0.102042E+10 | 0.227363E+10 | 0.377811E+09 |
August | 0.168516E+10 | 0.806743E+09 | 0.878414E+09 | 0.221398E+10 | 0.394879E+09 |
September | 0.146412E+10 | 0.777974E+09 | 0.686144E+09 | 0.185413E+10 | 0.497441E+09 |
October | 0.735860E+09 | 0.307724E+09 | 0.428136E+09 | 0.773664E+09 | 0.711998E+09 |
November | 0.368547E+09 | 0.125404E+09 | 0.243143E+09 | 0.264021E+09 | 0.853999E+09 |
December | 0.283268E+09 | 0.105999E+09 | 0.177269E+09 | 0.172324E+09 | 0.112652E+10 |
Annual Sum or Average | 0.129248E+11 | 0.555500E+10 | 0.736983E+10 | 0.146974E+11 | 0.813827E+10 |
Minimum of Months | 0.283268E+09 | 0.105999E+09 | 0.177269E+09 | 0.172324E+09 | 0.377811E+09 |
Maximum of Months | 0.177394E+10 | 0.806743E+09 | 0.102042E+10 | 0.227363E+10 | 0.112652E+10 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.298472E+09 | 0.193279E+09 | 0.105193E+09 | 0.322269E+09 | 0.251229E+09 |
February | 0.327132E+09 | 0.199379E+09 | 0.127753E+09 | 0.359331E+09 | 0.225206E+09 |
March | 0.223541E+09 | 64618063.64 | 0.158923E+09 | 0.214922E+09 | 0.206907E+09 |
April | 0.443463E+09 | 0.196498E+09 | 0.246965E+09 | 0.552299E+09 | 0.168399E+09 |
May | 0.384160E+09 | 0.124445E+09 | 0.259715E+09 | 0.452413E+09 | 0.158634E+09 |
June | 0.343181E+09 | 82997281.99 | 0.260183E+09 | 0.433089E+09 | 0.113190E+09 |
July | 0.382241E+09 | 0.118254E+09 | 0.263986E+09 | 0.514612E+09 | 0.105399E+09 |
August | 0.448945E+09 | 0.201148E+09 | 0.247797E+09 | 0.620417E+09 | 0.109330E+09 |
September | 0.520653E+09 | 0.307293E+09 | 0.213361E+09 | 0.693937E+09 | 0.136454E+09 |
October | 0.358991E+09 | 0.206968E+09 | 0.152023E+09 | 0.431693E+09 | 0.189964E+09 |
November | 0.250879E+09 | 0.152564E+09 | 98314557.38 | 0.271668E+09 | 0.224372E+09 |
December | 0.205721E+09 | 0.131914E+09 | 73806852.46 | 0.212650E+09 | 0.294591E+09 |
Annual Sum or Average | 0.418738E+10 | 0.197936E+10 | 0.220802E+10 | 0.507930E+10 | 0.218368E+10 |
Minimum of Months | 0.205721E+09 | 64618063.64 | 73806852.46 | 0.212650E+09 | 0.105399E+09 |
Maximum of Months | 0.520653E+09 | 0.307293E+09 | 0.263986E+09 | 0.693937E+09 | 0.294591E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 66229772.74 | 0.00 | 66229772.74 | 4449959.98 | 0.408268E+09 |
February | 93412162.03 | 0.00 | 93412162.03 | 12584436.32 | 0.343026E+09 |
March | 0.143130E+09 | 967.39 | 0.143129E+09 | 51235960.81 | 0.302038E+09 |
April | 0.226335E+09 | 1504274.40 | 0.224831E+09 | 0.159777E+09 | 0.220599E+09 |
May | 0.292407E+09 | 14911094.62 | 0.277496E+09 | 0.212244E+09 | 0.182051E+09 |
June | 0.311741E+09 | 19499670.94 | 0.292241E+09 | 0.291972E+09 | 0.127645E+09 |
July | 0.306286E+09 | 18014397.76 | 0.288272E+09 | 0.308828E+09 | 0.117733E+09 |
August | 0.241146E+09 | 4509687.32 | 0.236636E+09 | 0.239876E+09 | 0.130351E+09 |
September | 0.177008E+09 | 104617.41 | 0.176903E+09 | 0.150009E+09 | 0.182314E+09 |
October | 0.117114E+09 | 0.00 | 0.117114E+09 | 54101310.62 | 0.274558E+09 |
November | 68098281.09 | 0.00 | 68098281.09 | 7438444.96 | 0.344330E+09 |
December | 47920571.43 | 0.00 | 47920571.43 | 140529.17 | 0.450933E+09 |
Annual Sum or Average | 0.209083E+10 | 58544709.85 | 0.203228E+10 | 0.149266E+10 | 0.308385E+10 |
Minimum of Months | 47920571.43 | 0.00 | 47920571.43 | 140529.17 | 0.117733E+09 |
Maximum of Months | 0.311741E+09 | 19499670.94 | 0.292241E+09 | 0.308828E+09 | 0.450933E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 59256028.61 | 0.00 | 59256028.61 | 3981396.06 | 0.365205E+09 |
February | 83576215.31 | 0.00 | 83576215.31 | 11259342.86 | 0.306906E+09 |
March | 0.128059E+09 | 865.53 | 0.128058E+09 | 45841008.27 | 0.270235E+09 |
April | 0.202503E+09 | 1345880.01 | 0.201157E+09 | 0.142953E+09 | 0.197371E+09 |
May | 0.261618E+09 | 13341012.85 | 0.248277E+09 | 0.189896E+09 | 0.162881E+09 |
June | 0.278916E+09 | 17446429.47 | 0.261469E+09 | 0.261228E+09 | 0.114205E+09 |
July | 0.274036E+09 | 16117549.93 | 0.257918E+09 | 0.276309E+09 | 0.105336E+09 |
August | 0.215754E+09 | 4034834.34 | 0.211720E+09 | 0.214618E+09 | 0.116626E+09 |
September | 0.158370E+09 | 93601.59 | 0.158276E+09 | 0.134214E+09 | 0.163117E+09 |
October | 0.104783E+09 | 0.00 | 0.104783E+09 | 48404647.60 | 0.245648E+09 |
November | 60927790.11 | 0.00 | 60927790.11 | 6655204.89 | 0.308052E+09 |
December | 42874716.83 | 0.00 | 42874716.83 | 125731.98 | 0.403401E+09 |
Annual Sum or Average | 0.187067E+10 | 52380173.73 | 0.181829E+10 | 0.133549E+10 | 0.275898E+10 |
Minimum of Months | 42874716.83 | 0.00 | 42874716.83 | 125731.98 | 0.105336E+09 |
Maximum of Months | 0.278916E+09 | 17446429.47 | 0.261469E+09 | 0.276309E+09 | 0.403401E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.111429E+10 | 0.721568E+09 | 0.392718E+09 | 0.111268E+10 | 0.105939E+10 |
February | 0.122128E+10 | 0.744341E+09 | 0.476939E+09 | 0.124969E+10 | 0.927076E+09 |
March | 0.834544E+09 | 0.241238E+09 | 0.593305E+09 | 0.690428E+09 | 0.855913E+09 |
April | 0.165558E+10 | 0.733585E+09 | 0.921994E+09 | 0.192134E+10 | 0.663471E+09 |
May | 0.143418E+10 | 0.464592E+09 | 0.969593E+09 | 0.155054E+10 | 0.593987E+09 |
June | 0.128120E+10 | 0.309854E+09 | 0.971342E+09 | 0.146751E+10 | 0.411673E+09 |
July | 0.142702E+10 | 0.441478E+09 | 0.985540E+09 | 0.175790E+10 | 0.379599E+09 |
August | 0.167605E+10 | 0.750947E+09 | 0.925100E+09 | 0.215753E+10 | 0.406181E+09 |
September | 0.194375E+10 | 0.114722E+10 | 0.796539E+09 | 0.244985E+10 | 0.529464E+09 |
October | 0.134022E+10 | 0.772674E+09 | 0.567548E+09 | 0.149945E+10 | 0.775929E+09 |
November | 0.936606E+09 | 0.569569E+09 | 0.367038E+09 | 0.939508E+09 | 0.940680E+09 |
December | 0.768016E+09 | 0.492473E+09 | 0.275543E+09 | 0.738469E+09 | 0.122662E+10 |
Annual Sum or Average | 0.156327E+11 | 0.738953E+10 | 0.824320E+10 | 0.175349E+11 | 0.876998E+10 |
Minimum of Months | 0.768016E+09 | 0.241238E+09 | 0.275543E+09 | 0.690428E+09 | 0.379599E+09 |
Maximum of Months | 0.194375E+10 | 0.114722E+10 | 0.985540E+09 | 0.244985E+10 | 0.122662E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 563.58 | 505.50 | 563.62 | 364.98 | 198.64 | 0.00 | 0.00 |
February | 701.24 | 488.32 | 683.92 | 416.83 | 267.09 | 0.00 | 0.00 |
March | 355.57 | 407.44 | 422.12 | 122.02 | 300.10 | 0.00 | 0.00 |
April | 1002.76 | 332.88 | 865.32 | 383.42 | 481.90 | 0.00 | 0.00 |
May | 790.01 | 282.58 | 725.42 | 235.00 | 490.43 | 0.00 | 0.00 |
June | 770.09 | 204.28 | 669.64 | 161.95 | 507.69 | 0.00 | 0.00 |
July | 888.76 | 184.21 | 721.80 | 223.30 | 498.49 | 0.00 | 0.00 |
August | 1085.41 | 201.23 | 847.76 | 379.84 | 467.92 | 0.00 | 0.00 |
September | 1272.02 | 269.39 | 1015.94 | 599.62 | 416.32 | 0.00 | 0.00 |
October | 756.45 | 371.25 | 677.90 | 390.83 | 287.07 | 0.00 | 0.00 |
November | 493.20 | 458.89 | 489.54 | 297.70 | 191.84 | 0.00 | 0.00 |
December | 376.12 | 569.67 | 388.47 | 249.10 | 139.37 | 0.00 | 0.00 |
Annual Sum or Average | 753.62 | 355.66 | 671.57 | 317.45 | 354.12 | 0.00 | 0.00 |
Minimum of Months | 355.57 | 184.21 | 388.47 | 122.02 | 139.37 | 0.00 | 0.00 |
Maximum of Months | 1272.02 | 569.67 | 1015.94 | 599.62 | 507.69 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1575.35 | 1434.16 | 1587.11 | 1027.75 | 559.36 | 0.00 | 0.00 |
February | 1962.04 | 1382.30 | 1925.88 | 1173.78 | 752.10 | 0.00 | 0.00 |
March | 987.72 | 1151.32 | 1188.66 | 343.60 | 845.06 | 0.00 | 0.00 |
April | 2811.49 | 931.35 | 2436.68 | 1079.69 | 1356.99 | 0.00 | 0.00 |
May | 2211.20 | 790.38 | 2042.74 | 661.73 | 1381.00 | 0.00 | 0.00 |
June | 2156.80 | 567.10 | 1885.66 | 456.04 | 1429.61 | 0.00 | 0.00 |
July | 2492.80 | 510.38 | 2032.53 | 628.81 | 1403.72 | 0.00 | 0.00 |
August | 3048.21 | 558.05 | 2387.23 | 1069.59 | 1317.63 | 0.00 | 0.00 |
September | 3573.39 | 751.71 | 2860.82 | 1688.48 | 1172.34 | 0.00 | 0.00 |
October | 2119.76 | 1047.84 | 1908.91 | 1100.54 | 808.37 | 0.00 | 0.00 |
November | 1379.13 | 1303.27 | 1378.50 | 838.29 | 540.21 | 0.00 | 0.00 |
December | 1050.28 | 1628.55 | 1093.90 | 701.44 | 392.46 | 0.00 | 0.00 |
Annual Sum or Average | 2111.25 | 1002.87 | 1891.09 | 893.91 | 997.17 | 0.00 | 0.00 |
Minimum of Months | 987.72 | 510.38 | 1093.90 | 343.60 | 392.46 | 0.00 | 0.00 |
Maximum of Months | 3573.39 | 1628.55 | 2860.82 | 1688.48 | 1429.61 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2074.05 | 1920.53 | 2061.74 | 1335.10 | 726.64 | 0.00 | 0.00 |
February | 2586.31 | 1843.63 | 2501.82 | 1524.80 | 977.02 | 0.00 | 0.00 |
March | 1304.86 | 1546.67 | 1544.14 | 446.36 | 1097.78 | 0.00 | 0.00 |
April | 3725.87 | 1238.41 | 3165.39 | 1402.59 | 1762.80 | 0.00 | 0.00 |
May | 2935.78 | 1055.26 | 2653.63 | 859.63 | 1794.00 | 0.00 | 0.00 |
June | 2867.73 | 761.90 | 2449.58 | 592.43 | 1857.15 | 0.00 | 0.00 |
July | 3311.00 | 685.72 | 2640.37 | 816.86 | 1823.51 | 0.00 | 0.00 |
August | 4041.69 | 745.02 | 3101.14 | 1389.46 | 1711.68 | 0.00 | 0.00 |
September | 4732.38 | 994.91 | 3716.37 | 2193.43 | 1522.94 | 0.00 | 0.00 |
October | 2801.04 | 1397.81 | 2479.78 | 1429.67 | 1050.12 | 0.00 | 0.00 |
November | 1816.30 | 1745.41 | 1790.75 | 1088.99 | 701.76 | 0.00 | 0.00 |
December | 1379.54 | 2191.37 | 1421.04 | 911.21 | 509.83 | 0.00 | 0.00 |
Annual Sum or Average | 2794.44 | 1341.52 | 2456.63 | 1161.25 | 1295.39 | 0.00 | 0.00 |
Minimum of Months | 1304.86 | 685.72 | 1421.04 | 446.36 | 509.83 | 0.00 | 0.00 |
Maximum of Months | 4732.38 | 2191.37 | 3716.37 | 2193.43 | 1857.15 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 147.64 | 294.96 | 184.49 | 96.11 | 88.38 | 0.00 | 0.00 |
February | 236.11 | 286.80 | 264.45 | 137.42 | 127.02 | 0.00 | 0.00 |
March | 144.30 | 233.63 | 199.71 | 46.48 | 153.23 | 0.00 | 0.00 |
April | 479.67 | 191.36 | 444.87 | 184.36 | 260.51 | 0.00 | 0.00 |
May | 483.86 | 162.20 | 464.70 | 177.11 | 287.59 | 0.00 | 0.00 |
June | 537.06 | 119.25 | 479.25 | 174.82 | 304.44 | 0.00 | 0.00 |
July | 585.41 | 107.40 | 495.75 | 199.66 | 296.09 | 0.00 | 0.00 |
August | 562.23 | 117.17 | 464.70 | 203.80 | 260.90 | 0.00 | 0.00 |
September | 518.53 | 157.53 | 440.94 | 227.07 | 213.87 | 0.00 | 0.00 |
October | 260.77 | 216.28 | 262.00 | 123.75 | 138.25 | 0.00 | 0.00 |
November | 135.52 | 267.13 | 165.83 | 79.23 | 86.60 | 0.00 | 0.00 |
December | 80.76 | 333.35 | 115.30 | 57.08 | 58.22 | 0.00 | 0.00 |
Annual Sum or Average | 347.80 | 206.86 | 331.83 | 142.02 | 189.81 | 0.00 | 0.00 |
Minimum of Months | 80.76 | 107.40 | 115.30 | 46.48 | 58.22 | 0.00 | 0.00 |
Maximum of Months | 585.41 | 333.35 | 495.75 | 227.07 | 304.44 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 45.62 | 308.74 | 92.58 | 23.94 | 68.63 | 0.00 | 0.00 |
February | 108.80 | 292.83 | 159.71 | 55.01 | 104.70 | 0.00 | 0.00 |
March | 92.56 | 235.02 | 158.44 | 22.35 | 136.09 | 0.00 | 0.00 |
April | 336.94 | 188.27 | 342.73 | 109.01 | 233.72 | 0.00 | 0.00 |
May | 395.84 | 155.81 | 407.47 | 135.05 | 272.43 | 0.00 | 0.00 |
June | 476.01 | 114.11 | 441.82 | 148.74 | 293.09 | 0.00 | 0.00 |
July | 503.01 | 102.89 | 443.33 | 160.82 | 282.51 | 0.00 | 0.00 |
August | 422.02 | 113.38 | 368.18 | 130.03 | 238.15 | 0.00 | 0.00 |
September | 319.01 | 155.92 | 293.99 | 108.55 | 185.45 | 0.00 | 0.00 |
October | 133.57 | 217.32 | 162.50 | 46.48 | 116.02 | 0.00 | 0.00 |
November | 47.01 | 273.81 | 89.79 | 20.37 | 69.42 | 0.00 | 0.00 |
December | 14.04 | 346.09 | 52.62 | 7.82 | 44.79 | 0.00 | 0.00 |
Annual Sum or Average | 241.70 | 208.27 | 251.40 | 80.72 | 170.68 | 0.00 | 0.00 |
Minimum of Months | 14.04 | 102.89 | 52.62 | 7.82 | 44.79 | 0.00 | 0.00 |
Maximum of Months | 503.01 | 346.09 | 443.33 | 160.82 | 293.09 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 86.79 | 88.91 | 89.13 | 57.72 | 31.41 | 0.00 | 0.00 |
February | 108.09 | 87.07 | 108.16 | 65.92 | 42.24 | 0.00 | 0.00 |
March | 53.64 | 71.54 | 66.76 | 19.30 | 47.46 | 0.00 | 0.00 |
April | 153.33 | 62.45 | 136.84 | 60.64 | 76.21 | 0.00 | 0.00 |
May | 118.48 | 54.57 | 114.72 | 37.16 | 77.56 | 0.00 | 0.00 |
June | 114.92 | 40.73 | 105.90 | 25.61 | 80.29 | 0.00 | 0.00 |
July | 134.03 | 37.12 | 114.15 | 35.31 | 78.83 | 0.00 | 0.00 |
August | 166.15 | 40.28 | 134.07 | 60.07 | 74.00 | 0.00 | 0.00 |
September | 196.37 | 52.45 | 160.66 | 94.82 | 65.84 | 0.00 | 0.00 |
October | 116.03 | 69.99 | 107.20 | 61.81 | 45.40 | 0.00 | 0.00 |
November | 75.52 | 83.21 | 77.42 | 47.08 | 30.34 | 0.00 | 0.00 |
December | 59.28 | 92.93 | 61.43 | 39.39 | 22.04 | 0.00 | 0.00 |
Annual Sum or Average | 115.06 | 64.98 | 106.20 | 50.20 | 56.00 | 0.00 | 0.00 |
Minimum of Months | 53.64 | 37.12 | 61.43 | 19.30 | 22.04 | 0.00 | 0.00 |
Maximum of Months | 196.37 | 92.93 | 160.66 | 94.82 | 80.29 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1.26 | 94.82 | 15.62 | 0.00 | 15.62 | 0.00 | 0.00 |
February | 3.93 | 88.36 | 24.39 | 0.00 | 24.39 | 0.00 | 0.00 |
March | 12.36 | 71.18 | 33.76 | 0.00 | 33.76 | 0.00 | 0.00 |
April | 39.68 | 53.76 | 55.17 | 0.37 | 54.80 | 0.00 | 0.00 |
May | 50.37 | 42.91 | 68.97 | 3.52 | 65.46 | 0.00 | 0.00 |
June | 70.88 | 31.20 | 75.98 | 4.75 | 71.23 | 0.00 | 0.00 |
July | 72.54 | 27.85 | 72.25 | 4.25 | 68.00 | 0.00 | 0.00 |
August | 56.69 | 30.75 | 56.88 | 1.06 | 55.82 | 0.00 | 0.00 |
September | 37.08 | 44.35 | 43.14 | 0.03 | 43.12 | 0.00 | 0.00 |
October | 13.27 | 64.60 | 27.62 | 0.00 | 27.62 | 0.00 | 0.00 |
November | 2.10 | 82.98 | 16.60 | 0.00 | 16.60 | 0.00 | 0.00 |
December | 0.07 | 104.41 | 11.30 | 0.00 | 11.30 | 0.00 | 0.00 |
Annual Sum or Average | 30.15 | 61.30 | 41.89 | 1.17 | 40.71 | 0.00 | 0.00 |
Minimum of Months | 0.07 | 27.85 | 11.30 | 0.00 | 11.30 | 0.00 | 0.00 |
Maximum of Months | 72.54 | 104.41 | 75.98 | 4.75 | 71.23 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 147.98 | 293.41 | 185.53 | 101.67 | 83.86 | 0.00 | 0.00 |
February | 208.39 | 282.52 | 247.12 | 124.11 | 123.01 | 0.00 | 0.00 |
March | 142.92 | 232.12 | 199.72 | 47.06 | 152.66 | 0.00 | 0.00 |
April | 519.21 | 183.83 | 482.54 | 221.84 | 260.70 | 0.00 | 0.00 |
May | 485.88 | 157.10 | 471.35 | 189.49 | 281.86 | 0.00 | 0.00 |
June | 504.07 | 115.37 | 456.89 | 161.65 | 295.24 | 0.00 | 0.00 |
July | 551.73 | 103.54 | 473.89 | 184.83 | 289.07 | 0.00 | 0.00 |
August | 580.48 | 111.93 | 482.22 | 225.71 | 256.51 | 0.00 | 0.00 |
September | 567.14 | 152.23 | 483.32 | 268.64 | 214.68 | 0.00 | 0.00 |
October | 270.88 | 214.44 | 271.41 | 134.72 | 136.69 | 0.00 | 0.00 |
November | 136.18 | 265.04 | 167.89 | 83.05 | 84.84 | 0.00 | 0.00 |
December | 97.84 | 331.55 | 129.69 | 69.04 | 60.65 | 0.00 | 0.00 |
Annual Sum or Average | 351.35 | 203.21 | 337.72 | 150.85 | 186.87 | 0.00 | 0.00 |
Minimum of Months | 97.84 | 103.54 | 129.69 | 47.06 | 60.65 | 0.00 | 0.00 |
Maximum of Months | 580.48 | 331.55 | 483.32 | 268.64 | 295.24 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 41.70 | 302.68 | 93.62 | 29.51 | 64.11 | 0.00 | 0.00 |
February | 77.81 | 285.26 | 142.39 | 41.69 | 100.69 | 0.00 | 0.00 |
March | 90.52 | 232.91 | 158.45 | 22.93 | 135.52 | 0.00 | 0.00 |
April | 375.50 | 181.09 | 380.40 | 146.48 | 233.91 | 0.00 | 0.00 |
May | 398.29 | 152.00 | 414.13 | 147.43 | 266.70 | 0.00 | 0.00 |
June | 444.24 | 112.09 | 419.46 | 135.57 | 283.89 | 0.00 | 0.00 |
July | 469.97 | 100.42 | 421.48 | 145.99 | 275.49 | 0.00 | 0.00 |
August | 440.31 | 109.56 | 385.70 | 151.94 | 233.76 | 0.00 | 0.00 |
September | 364.66 | 149.75 | 336.37 | 150.11 | 186.26 | 0.00 | 0.00 |
October | 140.83 | 213.03 | 171.91 | 57.45 | 114.46 | 0.00 | 0.00 |
November | 42.93 | 266.74 | 91.84 | 24.19 | 67.65 | 0.00 | 0.00 |
December | 22.91 | 335.21 | 67.01 | 19.79 | 47.22 | 0.00 | 0.00 |
Annual Sum or Average | 243.12 | 203.01 | 257.29 | 89.55 | 167.74 | 0.00 | 0.00 |
Minimum of Months | 22.91 | 100.42 | 67.01 | 19.79 | 47.22 | 0.00 | 0.00 |
Maximum of Months | 469.97 | 335.21 | 421.48 | 151.94 | 283.89 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 179.32 | 374.35 | 226.97 | 125.06 | 101.91 | 0.00 | 0.00 |
February | 240.94 | 361.39 | 287.19 | 142.83 | 144.36 | 0.00 | 0.00 |
March | 146.91 | 299.52 | 217.78 | 41.81 | 175.97 | 0.00 | 0.00 |
April | 436.44 | 233.47 | 416.01 | 132.17 | 283.84 | 0.00 | 0.00 |
May | 382.79 | 189.55 | 397.98 | 88.14 | 309.84 | 0.00 | 0.00 |
June | 424.13 | 135.55 | 394.06 | 65.79 | 328.27 | 0.00 | 0.00 |
July | 469.76 | 121.54 | 403.83 | 85.72 | 318.11 | 0.00 | 0.00 |
August | 504.65 | 134.67 | 413.71 | 132.46 | 281.25 | 0.00 | 0.00 |
September | 524.80 | 188.98 | 441.58 | 205.51 | 236.06 | 0.00 | 0.00 |
October | 288.78 | 269.73 | 292.13 | 133.92 | 158.21 | 0.00 | 0.00 |
November | 165.63 | 339.44 | 203.70 | 102.01 | 101.69 | 0.00 | 0.00 |
December | 116.31 | 428.06 | 157.60 | 85.35 | 72.24 | 0.00 | 0.00 |
Annual Sum or Average | 323.34 | 255.84 | 320.85 | 111.31 | 209.54 | 0.00 | 0.00 |
Minimum of Months | 116.31 | 121.54 | 157.60 | 41.81 | 72.24 | 0.00 | 0.00 |
Maximum of Months | 524.80 | 428.06 | 441.58 | 205.51 | 328.27 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 148.72 | 289.95 | 184.49 | 96.11 | 88.38 | 0.00 | 0.00 |
February | 236.59 | 283.27 | 264.45 | 137.42 | 127.02 | 0.00 | 0.00 |
March | 144.69 | 229.94 | 199.71 | 46.48 | 153.23 | 0.00 | 0.00 |
April | 474.80 | 190.34 | 444.87 | 184.36 | 260.51 | 0.00 | 0.00 |
May | 477.71 | 162.39 | 464.70 | 177.11 | 287.59 | 0.00 | 0.00 |
June | 529.66 | 119.86 | 479.25 | 174.82 | 304.44 | 0.00 | 0.00 |
July | 577.94 | 107.98 | 495.75 | 199.66 | 296.09 | 0.00 | 0.00 |
August | 555.86 | 117.29 | 464.70 | 203.80 | 260.90 | 0.00 | 0.00 |
September | 514.03 | 157.25 | 440.94 | 227.07 | 213.87 | 0.00 | 0.00 |
October | 260.03 | 213.45 | 262.00 | 123.75 | 138.25 | 0.00 | 0.00 |
November | 136.24 | 262.85 | 165.83 | 79.23 | 86.60 | 0.00 | 0.00 |
December | 81.51 | 329.17 | 115.30 | 57.08 | 58.22 | 0.00 | 0.00 |
Annual Sum or Average | 344.95 | 204.92 | 331.83 | 142.02 | 189.81 | 0.00 | 0.00 |
Minimum of Months | 81.51 | 107.98 | 115.30 | 46.48 | 58.22 | 0.00 | 0.00 |
Maximum of Months | 577.94 | 329.17 | 495.75 | 227.07 | 304.44 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 46.50 | 303.35 | 92.58 | 23.94 | 68.63 | 0.00 | 0.00 |
February | 109.66 | 288.66 | 159.71 | 55.01 | 104.70 | 0.00 | 0.00 |
March | 93.25 | 231.11 | 158.44 | 22.35 | 136.09 | 0.00 | 0.00 |
April | 332.49 | 187.02 | 342.73 | 109.01 | 233.72 | 0.00 | 0.00 |
May | 389.89 | 155.92 | 407.47 | 135.05 | 272.43 | 0.00 | 0.00 |
June | 468.47 | 114.71 | 441.82 | 148.74 | 293.09 | 0.00 | 0.00 |
July | 495.50 | 103.46 | 443.33 | 160.82 | 282.51 | 0.00 | 0.00 |
August | 415.72 | 113.46 | 368.18 | 130.03 | 238.15 | 0.00 | 0.00 |
September | 315.24 | 155.31 | 293.99 | 108.55 | 185.45 | 0.00 | 0.00 |
October | 133.46 | 213.89 | 162.50 | 46.48 | 116.02 | 0.00 | 0.00 |
November | 47.94 | 268.98 | 89.79 | 20.37 | 69.42 | 0.00 | 0.00 |
December | 14.47 | 341.52 | 52.62 | 7.82 | 44.79 | 0.00 | 0.00 |
Annual Sum or Average | 239.03 | 206.05 | 251.40 | 80.72 | 170.68 | 0.00 | 0.00 |
Minimum of Months | 14.47 | 103.46 | 52.62 | 7.82 | 44.79 | 0.00 | 0.00 |
Maximum of Months | 495.50 | 341.52 | 443.33 | 160.82 | 293.09 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 160.11 | 152.15 | 163.43 | 105.83 | 57.60 | 0.00 | 0.00 |
February | 199.21 | 148.59 | 198.32 | 120.87 | 77.45 | 0.00 | 0.00 |
March | 100.09 | 122.30 | 122.40 | 35.38 | 87.02 | 0.00 | 0.00 |
April | 283.13 | 101.38 | 250.92 | 111.18 | 139.74 | 0.00 | 0.00 |
May | 220.50 | 87.32 | 210.35 | 68.14 | 142.21 | 0.00 | 0.00 |
June | 214.72 | 62.86 | 194.18 | 46.96 | 147.22 | 0.00 | 0.00 |
July | 249.37 | 56.48 | 209.30 | 64.75 | 144.55 | 0.00 | 0.00 |
August | 307.15 | 61.16 | 245.83 | 110.14 | 135.68 | 0.00 | 0.00 |
September | 361.61 | 82.58 | 294.59 | 173.87 | 120.72 | 0.00 | 0.00 |
October | 214.73 | 113.00 | 196.57 | 113.33 | 83.24 | 0.00 | 0.00 |
November | 139.69 | 139.17 | 141.95 | 86.32 | 55.63 | 0.00 | 0.00 |
December | 107.00 | 173.21 | 112.65 | 72.23 | 40.41 | 0.00 | 0.00 |
Annual Sum or Average | 212.82 | 108.15 | 194.74 | 92.05 | 102.68 | 0.00 | 0.00 |
Minimum of Months | 100.09 | 56.48 | 112.65 | 35.38 | 40.41 | 0.00 | 0.00 |
Maximum of Months | 361.61 | 173.21 | 294.59 | 173.87 | 147.22 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 9.89 | 835.58 | 136.67 | 0.00 | 136.67 | 0.00 | 0.00 |
February | 30.75 | 780.02 | 213.42 | 0.00 | 213.42 | 0.00 | 0.00 |
March | 105.63 | 624.85 | 295.36 | 0.00 | 295.36 | 0.00 | 0.00 |
April | 343.86 | 475.44 | 482.63 | 3.21 | 479.42 | 0.00 | 0.00 |
May | 435.27 | 389.09 | 603.41 | 30.77 | 572.64 | 0.00 | 0.00 |
June | 617.34 | 288.80 | 664.75 | 41.58 | 623.17 | 0.00 | 0.00 |
July | 634.01 | 259.60 | 632.05 | 37.17 | 594.87 | 0.00 | 0.00 |
August | 497.01 | 284.36 | 497.63 | 9.31 | 488.32 | 0.00 | 0.00 |
September | 325.08 | 398.28 | 377.45 | 0.22 | 377.22 | 0.00 | 0.00 |
October | 114.02 | 571.60 | 241.68 | 0.00 | 241.68 | 0.00 | 0.00 |
November | 16.90 | 736.03 | 145.21 | 0.00 | 145.21 | 0.00 | 0.00 |
December | 0.39 | 930.31 | 98.89 | 0.00 | 98.89 | 0.00 | 0.00 |
Annual Sum or Average | 262.03 | 546.72 | 366.45 | 10.26 | 356.19 | 0.00 | 0.00 |
Minimum of Months | 0.39 | 259.60 | 98.89 | 0.00 | 98.89 | 0.00 | 0.00 |
Maximum of Months | 634.01 | 930.31 | 664.75 | 41.58 | 623.17 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 8.95 | 851.48 | 136.67 | 0.00 | 136.67 | 0.00 | 0.00 |
February | 28.55 | 795.04 | 213.42 | 0.00 | 213.42 | 0.00 | 0.00 |
March | 101.52 | 638.60 | 295.36 | 0.00 | 295.36 | 0.00 | 0.00 |
April | 336.35 | 486.21 | 482.63 | 3.21 | 479.42 | 0.00 | 0.00 |
May | 424.87 | 398.44 | 603.41 | 30.77 | 572.64 | 0.00 | 0.00 |
June | 605.76 | 297.53 | 664.75 | 41.58 | 623.17 | 0.00 | 0.00 |
July | 621.98 | 268.02 | 632.05 | 37.17 | 594.87 | 0.00 | 0.00 |
August | 487.18 | 294.03 | 497.63 | 9.31 | 488.32 | 0.00 | 0.00 |
September | 318.01 | 409.65 | 377.45 | 0.22 | 377.22 | 0.00 | 0.00 |
October | 109.98 | 585.69 | 241.68 | 0.00 | 241.68 | 0.00 | 0.00 |
November | 15.48 | 752.42 | 145.21 | 0.00 | 145.21 | 0.00 | 0.00 |
December | 0.27 | 947.62 | 98.89 | 0.00 | 98.89 | 0.00 | 0.00 |
Annual Sum or Average | 256.07 | 559.28 | 366.45 | 10.26 | 356.19 | 0.00 | 0.00 |
Minimum of Months | 0.27 | 268.02 | 98.89 | 0.00 | 98.89 | 0.00 | 0.00 |
Maximum of Months | 621.98 | 947.62 | 664.75 | 41.58 | 623.17 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 214.49 | 548.79 | 279.15 | 131.18 | 147.97 | 0.00 | 0.00 |
February | 322.48 | 538.33 | 389.49 | 165.80 | 223.69 | 0.00 | 0.00 |
March | 284.89 | 440.09 | 358.15 | 69.98 | 288.17 | 0.00 | 0.00 |
April | 1000.44 | 355.60 | 862.89 | 368.30 | 494.59 | 0.00 | 0.00 |
May | 985.45 | 318.11 | 885.43 | 336.90 | 548.53 | 0.00 | 0.00 |
June | 1063.75 | 238.43 | 876.31 | 297.20 | 579.11 | 0.00 | 0.00 |
July | 1145.56 | 215.23 | 895.32 | 330.79 | 564.53 | 0.00 | 0.00 |
August | 1141.79 | 225.75 | 867.87 | 377.63 | 490.24 | 0.00 | 0.00 |
September | 1037.12 | 294.20 | 819.65 | 418.73 | 400.92 | 0.00 | 0.00 |
October | 471.38 | 406.78 | 443.30 | 192.16 | 251.13 | 0.00 | 0.00 |
November | 206.64 | 501.09 | 259.72 | 107.24 | 152.48 | 0.00 | 0.00 |
December | 136.39 | 638.33 | 196.69 | 88.83 | 107.87 | 0.00 | 0.00 |
Annual Sum or Average | 668.62 | 392.71 | 594.98 | 240.38 | 354.60 | 0.00 | 0.00 |
Minimum of Months | 136.39 | 215.23 | 196.69 | 69.98 | 107.87 | 0.00 | 0.00 |
Maximum of Months | 1145.56 | 638.33 | 895.32 | 418.73 | 579.11 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 392.31 | 658.05 | 462.88 | 269.40 | 193.48 | 0.00 | 0.00 |
February | 512.63 | 638.08 | 577.99 | 307.68 | 270.31 | 0.00 | 0.00 |
March | 290.49 | 529.70 | 412.83 | 90.07 | 322.76 | 0.00 | 0.00 |
April | 857.44 | 416.60 | 804.17 | 284.12 | 520.05 | 0.00 | 0.00 |
May | 722.16 | 343.67 | 742.31 | 184.01 | 558.31 | 0.00 | 0.00 |
June | 773.31 | 245.85 | 722.16 | 133.80 | 588.37 | 0.00 | 0.00 |
July | 869.35 | 219.57 | 749.45 | 177.57 | 571.88 | 0.00 | 0.00 |
August | 973.40 | 242.04 | 796.35 | 283.56 | 512.79 | 0.00 | 0.00 |
September | 1053.65 | 336.37 | 879.29 | 442.68 | 436.62 | 0.00 | 0.00 |
October | 593.58 | 479.40 | 583.23 | 288.48 | 294.74 | 0.00 | 0.00 |
November | 354.92 | 601.62 | 411.12 | 219.74 | 191.38 | 0.00 | 0.00 |
December | 256.71 | 757.83 | 320.64 | 183.87 | 136.78 | 0.00 | 0.00 |
Annual Sum or Average | 637.18 | 454.84 | 621.33 | 237.84 | 383.49 | 0.00 | 0.00 |
Minimum of Months | 256.71 | 219.57 | 320.64 | 90.07 | 136.78 | 0.00 | 0.00 |
Maximum of Months | 1053.65 | 757.83 | 879.29 | 442.68 | 588.37 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.150950E+10 | 0.135393E+10 | 0.150959E+10 | 0.977552E+09 | 0.532037E+09 | 0.00 | 0.00 |
February | 0.169645E+10 | 0.118136E+10 | 0.165454E+10 | 0.100840E+10 | 0.646136E+09 | 0.00 | 0.00 |
March | 0.952353E+09 | 0.109129E+10 | 0.113060E+10 | 0.326821E+09 | 0.803783E+09 | 0.00 | 0.00 |
April | 0.259916E+10 | 0.862828E+09 | 0.224291E+10 | 0.993833E+09 | 0.124907E+10 | 0.00 | 0.00 |
May | 0.211598E+10 | 0.756874E+09 | 0.194297E+10 | 0.629412E+09 | 0.131355E+10 | 0.00 | 0.00 |
June | 0.199607E+10 | 0.529504E+09 | 0.173570E+10 | 0.419778E+09 | 0.131592E+10 | 0.00 | 0.00 |
July | 0.238046E+10 | 0.493387E+09 | 0.193326E+10 | 0.598097E+09 | 0.133516E+10 | 0.00 | 0.00 |
August | 0.290717E+10 | 0.538967E+09 | 0.227063E+10 | 0.101735E+10 | 0.125328E+10 | 0.00 | 0.00 |
September | 0.329708E+10 | 0.698258E+09 | 0.263332E+10 | 0.155420E+10 | 0.107911E+10 | 0.00 | 0.00 |
October | 0.202606E+10 | 0.994367E+09 | 0.181568E+10 | 0.104679E+10 | 0.768888E+09 | 0.00 | 0.00 |
November | 0.127837E+10 | 0.118943E+10 | 0.126888E+10 | 0.771630E+09 | 0.497246E+09 | 0.00 | 0.00 |
December | 0.100740E+10 | 0.152581E+10 | 0.104048E+10 | 0.667184E+09 | 0.373294E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.237661E+11 | 0.112160E+11 | 0.211785E+11 | 0.100111E+11 | 0.111675E+11 | 0.00 | 0.00 |
Minimum of Months | 0.952353E+09 | 0.493387E+09 | 0.104048E+10 | 0.326821E+09 | 0.373294E+09 | 0.00 | 0.00 |
Maximum of Months | 0.329708E+10 | 0.152581E+10 | 0.263332E+10 | 0.155420E+10 | 0.133516E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.421943E+10 | 0.384126E+10 | 0.425090E+10 | 0.275272E+10 | 0.149818E+10 | 0.00 | 0.00 |
February | 0.474657E+10 | 0.334406E+10 | 0.465908E+10 | 0.283960E+10 | 0.181948E+10 | 0.00 | 0.00 |
March | 0.264551E+10 | 0.308370E+10 | 0.318371E+10 | 0.920306E+09 | 0.226340E+10 | 0.00 | 0.00 |
April | 0.728738E+10 | 0.241406E+10 | 0.631588E+10 | 0.279857E+10 | 0.351731E+10 | 0.00 | 0.00 |
May | 0.592249E+10 | 0.211695E+10 | 0.547127E+10 | 0.177238E+10 | 0.369888E+10 | 0.00 | 0.00 |
June | 0.559043E+10 | 0.146993E+10 | 0.488762E+10 | 0.118207E+10 | 0.370556E+10 | 0.00 | 0.00 |
July | 0.667671E+10 | 0.136701E+10 | 0.544392E+10 | 0.168420E+10 | 0.375972E+10 | 0.00 | 0.00 |
August | 0.816433E+10 | 0.149469E+10 | 0.639395E+10 | 0.286480E+10 | 0.352915E+10 | 0.00 | 0.00 |
September | 0.926222E+10 | 0.194844E+10 | 0.741524E+10 | 0.437654E+10 | 0.303871E+10 | 0.00 | 0.00 |
October | 0.567755E+10 | 0.280653E+10 | 0.511283E+10 | 0.294769E+10 | 0.216514E+10 | 0.00 | 0.00 |
November | 0.357471E+10 | 0.337808E+10 | 0.357307E+10 | 0.217286E+10 | 0.140021E+10 | 0.00 | 0.00 |
December | 0.281308E+10 | 0.436191E+10 | 0.292991E+10 | 0.187874E+10 | 0.105117E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.665804E+11 | 0.316266E+11 | 0.596374E+11 | 0.281905E+11 | 0.314469E+11 | 0.00 | 0.00 |
Minimum of Months | 0.264551E+10 | 0.136701E+10 | 0.292991E+10 | 0.920306E+09 | 0.105117E+10 | 0.00 | 0.00 |
Maximum of Months | 0.926222E+10 | 0.436191E+10 | 0.741524E+10 | 0.437654E+10 | 0.375972E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.555513E+10 | 0.514394E+10 | 0.552217E+10 | 0.357594E+10 | 0.194622E+10 | 0.00 | 0.00 |
February | 0.625679E+10 | 0.446012E+10 | 0.605241E+10 | 0.368880E+10 | 0.236360E+10 | 0.00 | 0.00 |
March | 0.349494E+10 | 0.414259E+10 | 0.413581E+10 | 0.119553E+10 | 0.294029E+10 | 0.00 | 0.00 |
April | 0.965744E+10 | 0.320995E+10 | 0.820468E+10 | 0.363550E+10 | 0.456918E+10 | 0.00 | 0.00 |
May | 0.786320E+10 | 0.282640E+10 | 0.710749E+10 | 0.230242E+10 | 0.480506E+10 | 0.00 | 0.00 |
June | 0.743315E+10 | 0.197486E+10 | 0.634930E+10 | 0.153557E+10 | 0.481373E+10 | 0.00 | 0.00 |
July | 0.886818E+10 | 0.183663E+10 | 0.707196E+10 | 0.218787E+10 | 0.488409E+10 | 0.00 | 0.00 |
August | 0.108253E+11 | 0.199545E+10 | 0.830611E+10 | 0.372154E+10 | 0.458457E+10 | 0.00 | 0.00 |
September | 0.122663E+11 | 0.257880E+10 | 0.963282E+10 | 0.568537E+10 | 0.394745E+10 | 0.00 | 0.00 |
October | 0.750230E+10 | 0.374390E+10 | 0.664185E+10 | 0.382922E+10 | 0.281264E+10 | 0.00 | 0.00 |
November | 0.470784E+10 | 0.452412E+10 | 0.464162E+10 | 0.282267E+10 | 0.181896E+10 | 0.00 | 0.00 |
December | 0.369496E+10 | 0.586937E+10 | 0.380613E+10 | 0.244060E+10 | 0.136553E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.881255E+11 | 0.423061E+11 | 0.774723E+11 | 0.366210E+11 | 0.408513E+11 | 0.00 | 0.00 |
Minimum of Months | 0.349494E+10 | 0.183663E+10 | 0.380613E+10 | 0.119553E+10 | 0.136553E+10 | 0.00 | 0.00 |
Maximum of Months | 0.122663E+11 | 0.586937E+10 | 0.963282E+10 | 0.568537E+10 | 0.488409E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.395437E+09 | 0.790024E+09 | 0.494133E+09 | 0.257408E+09 | 0.236725E+09 | 0.00 | 0.00 |
February | 0.571209E+09 | 0.693819E+09 | 0.639747E+09 | 0.332452E+09 | 0.307294E+09 | 0.00 | 0.00 |
March | 0.386497E+09 | 0.625747E+09 | 0.534896E+09 | 0.124489E+09 | 0.410407E+09 | 0.00 | 0.00 |
April | 0.124329E+10 | 0.496009E+09 | 0.115310E+10 | 0.477853E+09 | 0.675246E+09 | 0.00 | 0.00 |
May | 0.129596E+10 | 0.434444E+09 | 0.124465E+10 | 0.474379E+09 | 0.770273E+09 | 0.00 | 0.00 |
June | 0.139207E+10 | 0.309087E+09 | 0.124223E+10 | 0.453123E+09 | 0.789105E+09 | 0.00 | 0.00 |
July | 0.156795E+10 | 0.287663E+09 | 0.132781E+10 | 0.534771E+09 | 0.793040E+09 | 0.00 | 0.00 |
August | 0.150587E+10 | 0.313820E+09 | 0.124466E+10 | 0.545860E+09 | 0.698800E+09 | 0.00 | 0.00 |
September | 0.134403E+10 | 0.408326E+09 | 0.114291E+10 | 0.588565E+09 | 0.554349E+09 | 0.00 | 0.00 |
October | 0.698458E+09 | 0.579273E+09 | 0.701746E+09 | 0.331451E+09 | 0.370295E+09 | 0.00 | 0.00 |
November | 0.351279E+09 | 0.692409E+09 | 0.429837E+09 | 0.205366E+09 | 0.224470E+09 | 0.00 | 0.00 |
December | 0.216310E+09 | 0.892844E+09 | 0.308814E+09 | 0.152870E+09 | 0.155944E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.109684E+11 | 0.652347E+10 | 0.104645E+11 | 0.447859E+10 | 0.598595E+10 | 0.00 | 0.00 |
Minimum of Months | 0.216310E+09 | 0.287663E+09 | 0.308814E+09 | 0.124489E+09 | 0.155944E+09 | 0.00 | 0.00 |
Maximum of Months | 0.156795E+10 | 0.892844E+09 | 0.132781E+10 | 0.588565E+09 | 0.793040E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.122179E+09 | 0.826936E+09 | 0.247957E+09 | 64128920.97 | 0.183828E+09 | 0.00 | 0.00 |
February | 0.263210E+09 | 0.708421E+09 | 0.386375E+09 | 0.133073E+09 | 0.253301E+09 | 0.00 | 0.00 |
March | 0.247901E+09 | 0.629485E+09 | 0.424373E+09 | 59871685.24 | 0.364501E+09 | 0.00 | 0.00 |
April | 0.873350E+09 | 0.487984E+09 | 0.888354E+09 | 0.282543E+09 | 0.605811E+09 | 0.00 | 0.00 |
May | 0.106022E+10 | 0.417323E+09 | 0.109138E+10 | 0.361707E+09 | 0.729674E+09 | 0.00 | 0.00 |
June | 0.123383E+10 | 0.295764E+09 | 0.114520E+10 | 0.385523E+09 | 0.759681E+09 | 0.00 | 0.00 |
July | 0.134726E+10 | 0.275568E+09 | 0.118742E+10 | 0.430741E+09 | 0.756678E+09 | 0.00 | 0.00 |
August | 0.113035E+10 | 0.303675E+09 | 0.986127E+09 | 0.348272E+09 | 0.637855E+09 | 0.00 | 0.00 |
September | 0.826878E+09 | 0.404146E+09 | 0.762029E+09 | 0.281355E+09 | 0.480675E+09 | 0.00 | 0.00 |
October | 0.357750E+09 | 0.582064E+09 | 0.435230E+09 | 0.124483E+09 | 0.310747E+09 | 0.00 | 0.00 |
November | 0.121839E+09 | 0.709726E+09 | 0.232729E+09 | 52801937.15 | 0.179927E+09 | 0.00 | 0.00 |
December | 37617976.89 | 0.926958E+09 | 0.140932E+09 | 20956149.08 | 0.119976E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.762238E+10 | 0.656805E+10 | 0.792811E+10 | 0.254546E+10 | 0.538265E+10 | 0.00 | 0.00 |
Minimum of Months | 37617976.89 | 0.275568E+09 | 0.140932E+09 | 20956149.08 | 0.119976E+09 | 0.00 | 0.00 |
Maximum of Months | 0.134726E+10 | 0.926958E+09 | 0.118742E+10 | 0.430741E+09 | 0.759681E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.232469E+09 | 0.238130E+09 | 0.238730E+09 | 0.154592E+09 | 84137898.18 | 0.00 | 0.00 |
February | 0.261501E+09 | 0.210643E+09 | 0.261653E+09 | 0.159471E+09 | 0.102182E+09 | 0.00 | 0.00 |
March | 0.143661E+09 | 0.191606E+09 | 0.178797E+09 | 51684172.32 | 0.127113E+09 | 0.00 | 0.00 |
April | 0.397427E+09 | 0.161870E+09 | 0.354700E+09 | 0.157167E+09 | 0.197533E+09 | 0.00 | 0.00 |
May | 0.317327E+09 | 0.146168E+09 | 0.307267E+09 | 99536592.27 | 0.207730E+09 | 0.00 | 0.00 |
June | 0.297883E+09 | 0.105569E+09 | 0.274490E+09 | 66384623.48 | 0.208105E+09 | 0.00 | 0.00 |
July | 0.358995E+09 | 99408841.43 | 0.305732E+09 | 94584426.86 | 0.211147E+09 | 0.00 | 0.00 |
August | 0.445026E+09 | 0.107886E+09 | 0.359085E+09 | 0.160887E+09 | 0.198198E+09 | 0.00 | 0.00 |
September | 0.508980E+09 | 0.135952E+09 | 0.416440E+09 | 0.245785E+09 | 0.170655E+09 | 0.00 | 0.00 |
October | 0.310766E+09 | 0.187453E+09 | 0.287136E+09 | 0.165542E+09 | 0.121594E+09 | 0.00 | 0.00 |
November | 0.195744E+09 | 0.215690E+09 | 0.200663E+09 | 0.122027E+09 | 78636007.32 | 0.00 | 0.00 |
December | 0.158784E+09 | 0.248892E+09 | 0.164544E+09 | 0.105510E+09 | 59033741.75 | 0.00 | 0.00 |
Annual Sum or Average | 0.362856E+10 | 0.204927E+10 | 0.334924E+10 | 0.158317E+10 | 0.176607E+10 | 0.00 | 0.00 |
Minimum of Months | 0.143661E+09 | 99408841.43 | 0.164544E+09 | 51684172.32 | 59033741.75 | 0.00 | 0.00 |
Maximum of Months | 0.508980E+09 | 0.248892E+09 | 0.416440E+09 | 0.245785E+09 | 0.211147E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 3383701.88 | 0.253966E+09 | 41842464.75 | 0.00 | 41842464.75 | 0.00 | 0.00 |
February | 9510838.88 | 0.213762E+09 | 59015680.35 | 0.00 | 59015680.35 | 0.00 | 0.00 |
March | 33113323.56 | 0.190646E+09 | 90426079.04 | 611.18 | 90425467.87 | 0.00 | 0.00 |
April | 0.102841E+09 | 0.139358E+09 | 0.142993E+09 | 950366.37 | 0.142043E+09 | 0.00 | 0.00 |
May | 0.134907E+09 | 0.114931E+09 | 0.184736E+09 | 9420490.59 | 0.175316E+09 | 0.00 | 0.00 |
June | 0.183716E+09 | 80865322.40 | 0.196951E+09 | 12319448.80 | 0.184631E+09 | 0.00 | 0.00 |
July | 0.194284E+09 | 74587656.09 | 0.193505E+09 | 11381086.97 | 0.182124E+09 | 0.00 | 0.00 |
August | 0.151839E+09 | 82370167.36 | 0.152351E+09 | 2849117.93 | 0.149502E+09 | 0.00 | 0.00 |
September | 96100804.10 | 0.114947E+09 | 0.111830E+09 | 66094.90 | 0.111764E+09 | 0.00 | 0.00 |
October | 35529048.83 | 0.173023E+09 | 73990137.15 | 0.00 | 73990137.15 | 0.00 | 0.00 |
November | 5443946.53 | 0.215092E+09 | 43022945.85 | 0.00 | 43022945.85 | 0.00 | 0.00 |
December | 186279.94 | 0.279647E+09 | 30275127.60 | 0.00 | 30275127.60 | 0.00 | 0.00 |
Annual Sum or Average | 0.950856E+09 | 0.193320E+10 | 0.132094E+10 | 36987216.73 | 0.128395E+10 | 0.00 | 0.00 |
Minimum of Months | 186279.94 | 74587656.09 | 30275127.60 | 0.00 | 30275127.60 | 0.00 | 0.00 |
Maximum of Months | 0.194284E+09 | 0.279647E+09 | 0.196951E+09 | 12319448.80 | 0.184631E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.396343E+09 | 0.785869E+09 | 0.496934E+09 | 0.272321E+09 | 0.224613E+09 | 0.00 | 0.00 |
February | 0.504133E+09 | 0.683481E+09 | 0.597830E+09 | 0.300245E+09 | 0.297585E+09 | 0.00 | 0.00 |
March | 0.382799E+09 | 0.621714E+09 | 0.534921E+09 | 0.126033E+09 | 0.408888E+09 | 0.00 | 0.00 |
April | 0.134579E+10 | 0.476488E+09 | 0.125073E+10 | 0.574996E+09 | 0.675737E+09 | 0.00 | 0.00 |
May | 0.130139E+10 | 0.420764E+09 | 0.126247E+10 | 0.507539E+09 | 0.754926E+09 | 0.00 | 0.00 |
June | 0.130654E+10 | 0.299050E+09 | 0.118426E+10 | 0.418994E+09 | 0.765270E+09 | 0.00 | 0.00 |
July | 0.147775E+10 | 0.277318E+09 | 0.126927E+10 | 0.495041E+09 | 0.774234E+09 | 0.00 | 0.00 |
August | 0.155477E+10 | 0.299797E+09 | 0.129158E+10 | 0.604548E+09 | 0.687035E+09 | 0.00 | 0.00 |
September | 0.147003E+10 | 0.394587E+09 | 0.125276E+10 | 0.696307E+09 | 0.556457E+09 | 0.00 | 0.00 |
October | 0.725514E+09 | 0.574343E+09 | 0.726948E+09 | 0.360841E+09 | 0.366107E+09 | 0.00 | 0.00 |
November | 0.352975E+09 | 0.686976E+09 | 0.435166E+09 | 0.215271E+09 | 0.219895E+09 | 0.00 | 0.00 |
December | 0.262053E+09 | 0.888034E+09 | 0.347365E+09 | 0.184917E+09 | 0.162448E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.110801E+11 | 0.640842E+10 | 0.106502E+11 | 0.475705E+10 | 0.589319E+10 | 0.00 | 0.00 |
Minimum of Months | 0.262053E+09 | 0.277318E+09 | 0.347365E+09 | 0.126033E+09 | 0.162448E+09 | 0.00 | 0.00 |
Maximum of Months | 0.155477E+10 | 0.888034E+09 | 0.129158E+10 | 0.696307E+09 | 0.774234E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.111694E+09 | 0.810688E+09 | 0.250758E+09 | 79042420.23 | 0.171716E+09 | 0.00 | 0.00 |
February | 0.188239E+09 | 0.690093E+09 | 0.344458E+09 | 0.100866E+09 | 0.243592E+09 | 0.00 | 0.00 |
March | 0.242440E+09 | 0.623815E+09 | 0.424398E+09 | 61415498.09 | 0.362983E+09 | 0.00 | 0.00 |
April | 0.973304E+09 | 0.469391E+09 | 0.985989E+09 | 0.379686E+09 | 0.606302E+09 | 0.00 | 0.00 |
May | 0.106678E+10 | 0.407109E+09 | 0.110919E+10 | 0.394867E+09 | 0.714327E+09 | 0.00 | 0.00 |
June | 0.115147E+10 | 0.290540E+09 | 0.108724E+10 | 0.351394E+09 | 0.735845E+09 | 0.00 | 0.00 |
July | 0.125877E+10 | 0.268968E+09 | 0.112888E+10 | 0.391012E+09 | 0.737872E+09 | 0.00 | 0.00 |
August | 0.117932E+10 | 0.293458E+09 | 0.103305E+10 | 0.406961E+09 | 0.626091E+09 | 0.00 | 0.00 |
September | 0.945199E+09 | 0.388155E+09 | 0.871879E+09 | 0.389097E+09 | 0.482782E+09 | 0.00 | 0.00 |
October | 0.377190E+09 | 0.570570E+09 | 0.460432E+09 | 0.153873E+09 | 0.306559E+09 | 0.00 | 0.00 |
November | 0.111275E+09 | 0.691380E+09 | 0.238058E+09 | 62706204.31 | 0.175352E+09 | 0.00 | 0.00 |
December | 61355376.08 | 0.897830E+09 | 0.179483E+09 | 53003264.31 | 0.126480E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.766704E+10 | 0.640200E+10 | 0.811382E+10 | 0.282392E+10 | 0.528990E+10 | 0.00 | 0.00 |
Minimum of Months | 61355376.08 | 0.268968E+09 | 0.179483E+09 | 53003264.31 | 0.126480E+09 | 0.00 | 0.00 |
Maximum of Months | 0.125877E+10 | 0.897830E+09 | 0.112888E+10 | 0.406961E+09 | 0.737872E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.480299E+09 | 0.100266E+10 | 0.607907E+09 | 0.334959E+09 | 0.272948E+09 | 0.00 | 0.00 |
February | 0.582872E+09 | 0.874268E+09 | 0.694778E+09 | 0.345530E+09 | 0.349248E+09 | 0.00 | 0.00 |
March | 0.393487E+09 | 0.802235E+09 | 0.583296E+09 | 0.111987E+09 | 0.471310E+09 | 0.00 | 0.00 |
April | 0.113124E+10 | 0.605159E+09 | 0.107831E+10 | 0.342596E+09 | 0.735711E+09 | 0.00 | 0.00 |
May | 0.102527E+10 | 0.507682E+09 | 0.106596E+10 | 0.236076E+09 | 0.829887E+09 | 0.00 | 0.00 |
June | 0.109935E+10 | 0.351356E+09 | 0.102140E+10 | 0.170525E+09 | 0.850879E+09 | 0.00 | 0.00 |
July | 0.125819E+10 | 0.325521E+09 | 0.108163E+10 | 0.229593E+09 | 0.852038E+09 | 0.00 | 0.00 |
August | 0.135165E+10 | 0.360713E+09 | 0.110808E+10 | 0.354769E+09 | 0.753311E+09 | 0.00 | 0.00 |
September | 0.136028E+10 | 0.489840E+09 | 0.114457E+10 | 0.532692E+09 | 0.611878E+09 | 0.00 | 0.00 |
October | 0.773469E+09 | 0.722434E+09 | 0.782431E+09 | 0.358683E+09 | 0.423749E+09 | 0.00 | 0.00 |
November | 0.429308E+09 | 0.879841E+09 | 0.527984E+09 | 0.264399E+09 | 0.263584E+09 | 0.00 | 0.00 |
December | 0.311529E+09 | 0.114651E+10 | 0.422106E+09 | 0.228611E+09 | 0.193496E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.101969E+11 | 0.806822E+10 | 0.101185E+11 | 0.351042E+10 | 0.660804E+10 | 0.00 | 0.00 |
Minimum of Months | 0.311529E+09 | 0.325521E+09 | 0.422106E+09 | 0.111987E+09 | 0.193496E+09 | 0.00 | 0.00 |
Maximum of Months | 0.136028E+10 | 0.114651E+10 | 0.114457E+10 | 0.532692E+09 | 0.852038E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.398322E+09 | 0.776598E+09 | 0.494133E+09 | 0.257408E+09 | 0.236725E+09 | 0.00 | 0.00 |
February | 0.572352E+09 | 0.685284E+09 | 0.639747E+09 | 0.332452E+09 | 0.307294E+09 | 0.00 | 0.00 |
March | 0.387545E+09 | 0.615863E+09 | 0.534896E+09 | 0.124489E+09 | 0.410407E+09 | 0.00 | 0.00 |
April | 0.123068E+10 | 0.493357E+09 | 0.115310E+10 | 0.477853E+09 | 0.675246E+09 | 0.00 | 0.00 |
May | 0.127949E+10 | 0.434958E+09 | 0.124465E+10 | 0.474379E+09 | 0.770273E+09 | 0.00 | 0.00 |
June | 0.137288E+10 | 0.310690E+09 | 0.124223E+10 | 0.453123E+09 | 0.789105E+09 | 0.00 | 0.00 |
July | 0.154796E+10 | 0.289203E+09 | 0.132781E+10 | 0.534771E+09 | 0.793040E+09 | 0.00 | 0.00 |
August | 0.148882E+10 | 0.314159E+09 | 0.124466E+10 | 0.545860E+09 | 0.698800E+09 | 0.00 | 0.00 |
September | 0.133236E+10 | 0.407590E+09 | 0.114291E+10 | 0.588565E+09 | 0.554349E+09 | 0.00 | 0.00 |
October | 0.696451E+09 | 0.571714E+09 | 0.701746E+09 | 0.331451E+09 | 0.370295E+09 | 0.00 | 0.00 |
November | 0.353124E+09 | 0.681299E+09 | 0.429837E+09 | 0.205366E+09 | 0.224470E+09 | 0.00 | 0.00 |
December | 0.218304E+09 | 0.881640E+09 | 0.308814E+09 | 0.152870E+09 | 0.155944E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.108783E+11 | 0.646235E+10 | 0.104645E+11 | 0.447859E+10 | 0.598595E+10 | 0.00 | 0.00 |
Minimum of Months | 0.218304E+09 | 0.289203E+09 | 0.308814E+09 | 0.124489E+09 | 0.155944E+09 | 0.00 | 0.00 |
Maximum of Months | 0.154796E+10 | 0.881640E+09 | 0.132781E+10 | 0.588565E+09 | 0.793040E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.124544E+09 | 0.812483E+09 | 0.247957E+09 | 64128920.97 | 0.183828E+09 | 0.00 | 0.00 |
February | 0.265286E+09 | 0.698337E+09 | 0.386375E+09 | 0.133073E+09 | 0.253301E+09 | 0.00 | 0.00 |
March | 0.249763E+09 | 0.619006E+09 | 0.424373E+09 | 59871685.24 | 0.364501E+09 | 0.00 | 0.00 |
April | 0.861819E+09 | 0.484745E+09 | 0.888354E+09 | 0.282543E+09 | 0.605811E+09 | 0.00 | 0.00 |
May | 0.104429E+10 | 0.417611E+09 | 0.109138E+10 | 0.361707E+09 | 0.729674E+09 | 0.00 | 0.00 |
June | 0.121426E+10 | 0.297337E+09 | 0.114520E+10 | 0.385523E+09 | 0.759681E+09 | 0.00 | 0.00 |
July | 0.132714E+10 | 0.277108E+09 | 0.118742E+10 | 0.430741E+09 | 0.756678E+09 | 0.00 | 0.00 |
August | 0.111345E+10 | 0.303898E+09 | 0.986127E+09 | 0.348272E+09 | 0.637855E+09 | 0.00 | 0.00 |
September | 0.817090E+09 | 0.402570E+09 | 0.762029E+09 | 0.281355E+09 | 0.480675E+09 | 0.00 | 0.00 |
October | 0.357447E+09 | 0.572874E+09 | 0.435230E+09 | 0.124483E+09 | 0.310747E+09 | 0.00 | 0.00 |
November | 0.124256E+09 | 0.697205E+09 | 0.232729E+09 | 52801937.15 | 0.179927E+09 | 0.00 | 0.00 |
December | 38762453.79 | 0.914739E+09 | 0.140932E+09 | 20956149.08 | 0.119976E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.753812E+10 | 0.649791E+10 | 0.792811E+10 | 0.254546E+10 | 0.538265E+10 | 0.00 | 0.00 |
Minimum of Months | 38762453.79 | 0.277108E+09 | 0.140932E+09 | 20956149.08 | 0.119976E+09 | 0.00 | 0.00 |
Maximum of Months | 0.132714E+10 | 0.914739E+09 | 0.118742E+10 | 0.430741E+09 | 0.759681E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.428844E+09 | 0.407517E+09 | 0.437738E+09 | 0.283462E+09 | 0.154276E+09 | 0.00 | 0.00 |
February | 0.481938E+09 | 0.359469E+09 | 0.479770E+09 | 0.292408E+09 | 0.187362E+09 | 0.00 | 0.00 |
March | 0.268093E+09 | 0.327567E+09 | 0.327844E+09 | 94768591.74 | 0.233075E+09 | 0.00 | 0.00 |
April | 0.733872E+09 | 0.262774E+09 | 0.650381E+09 | 0.288183E+09 | 0.362198E+09 | 0.00 | 0.00 |
May | 0.590598E+09 | 0.233879E+09 | 0.563408E+09 | 0.182511E+09 | 0.380897E+09 | 0.00 | 0.00 |
June | 0.556560E+09 | 0.162928E+09 | 0.503307E+09 | 0.121723E+09 | 0.381584E+09 | 0.00 | 0.00 |
July | 0.667907E+09 | 0.151275E+09 | 0.560592E+09 | 0.173431E+09 | 0.387162E+09 | 0.00 | 0.00 |
August | 0.822674E+09 | 0.163813E+09 | 0.658421E+09 | 0.295003E+09 | 0.363418E+09 | 0.00 | 0.00 |
September | 0.937304E+09 | 0.214043E+09 | 0.763588E+09 | 0.450674E+09 | 0.312914E+09 | 0.00 | 0.00 |
October | 0.575133E+09 | 0.302648E+09 | 0.526495E+09 | 0.303539E+09 | 0.222957E+09 | 0.00 | 0.00 |
November | 0.362076E+09 | 0.360724E+09 | 0.367938E+09 | 0.223750E+09 | 0.144188E+09 | 0.00 | 0.00 |
December | 0.286580E+09 | 0.463935E+09 | 0.301709E+09 | 0.193464E+09 | 0.108245E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.671158E+10 | 0.341057E+10 | 0.614119E+10 | 0.290292E+10 | 0.323827E+10 | 0.00 | 0.00 |
Minimum of Months | 0.268093E+09 | 0.151275E+09 | 0.301709E+09 | 94768591.74 | 0.108245E+09 | 0.00 | 0.00 |
Maximum of Months | 0.937304E+09 | 0.463935E+09 | 0.763588E+09 | 0.450674E+09 | 0.387162E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 26497778.32 | 0.223801E+10 | 0.366059E+09 | 0.00 | 0.366059E+09 | 0.00 | 0.00 |
February | 74382455.92 | 0.188701E+10 | 0.516299E+09 | 0.00 | 0.516299E+09 | 0.00 | 0.00 |
March | 0.282911E+09 | 0.167360E+10 | 0.791093E+09 | 5346.90 | 0.791088E+09 | 0.00 | 0.00 |
April | 0.891290E+09 | 0.123233E+10 | 0.125098E+10 | 8314288.68 | 0.124266E+10 | 0.00 | 0.00 |
May | 0.116584E+10 | 0.104214E+10 | 0.161617E+10 | 82415246.22 | 0.153375E+10 | 0.00 | 0.00 |
June | 0.160015E+10 | 0.748582E+09 | 0.172303E+10 | 0.107777E+09 | 0.161525E+10 | 0.00 | 0.00 |
July | 0.169814E+10 | 0.695319E+09 | 0.169288E+10 | 99567541.14 | 0.159331E+10 | 0.00 | 0.00 |
August | 0.133119E+10 | 0.761643E+09 | 0.133284E+10 | 24925533.69 | 0.130792E+10 | 0.00 | 0.00 |
September | 0.842619E+09 | 0.103235E+10 | 0.978343E+09 | 578231.83 | 0.977764E+09 | 0.00 | 0.00 |
October | 0.305403E+09 | 0.153098E+10 | 0.647303E+09 | 0.00 | 0.647303E+09 | 0.00 | 0.00 |
November | 43798847.09 | 0.190778E+10 | 0.376387E+09 | 0.00 | 0.376387E+09 | 0.00 | 0.00 |
December | 1050216.35 | 0.249173E+10 | 0.264862E+09 | 0.00 | 0.264862E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.826327E+10 | 0.172415E+11 | 0.115562E+11 | 0.323583E+09 | 0.112327E+11 | 0.00 | 0.00 |
Minimum of Months | 1050216.35 | 0.695319E+09 | 0.264862E+09 | 0.00 | 0.264862E+09 | 0.00 | 0.00 |
Maximum of Months | 0.169814E+10 | 0.249173E+10 | 0.172303E+10 | 0.107777E+09 | 0.161525E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 23962966.92 | 0.228060E+10 | 0.366059E+09 | 0.00 | 0.366059E+09 | 0.00 | 0.00 |
February | 69061034.79 | 0.192336E+10 | 0.516299E+09 | 0.00 | 0.516299E+09 | 0.00 | 0.00 |
March | 0.271905E+09 | 0.171042E+10 | 0.791093E+09 | 5346.90 | 0.791088E+09 | 0.00 | 0.00 |
April | 0.871816E+09 | 0.126026E+10 | 0.125098E+10 | 8314288.68 | 0.124266E+10 | 0.00 | 0.00 |
May | 0.113799E+10 | 0.106719E+10 | 0.161617E+10 | 82415246.22 | 0.153375E+10 | 0.00 | 0.00 |
June | 0.157013E+10 | 0.771208E+09 | 0.172303E+10 | 0.107777E+09 | 0.161525E+10 | 0.00 | 0.00 |
July | 0.166592E+10 | 0.717867E+09 | 0.169288E+10 | 99567541.14 | 0.159331E+10 | 0.00 | 0.00 |
August | 0.130486E+10 | 0.787524E+09 | 0.133284E+10 | 24925533.69 | 0.130792E+10 | 0.00 | 0.00 |
September | 0.824276E+09 | 0.106183E+10 | 0.978343E+09 | 578231.83 | 0.977764E+09 | 0.00 | 0.00 |
October | 0.294559E+09 | 0.156870E+10 | 0.647303E+09 | 0.00 | 0.647303E+09 | 0.00 | 0.00 |
November | 40115672.81 | 0.195028E+10 | 0.376387E+09 | 0.00 | 0.376387E+09 | 0.00 | 0.00 |
December | 720839.11 | 0.253811E+10 | 0.264862E+09 | 0.00 | 0.264862E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.807531E+10 | 0.176373E+11 | 0.115562E+11 | 0.323583E+09 | 0.112327E+11 | 0.00 | 0.00 |
Minimum of Months | 720839.11 | 0.717867E+09 | 0.264862E+09 | 0.00 | 0.264862E+09 | 0.00 | 0.00 |
Maximum of Months | 0.166592E+10 | 0.253811E+10 | 0.172303E+10 | 0.107777E+09 | 0.161525E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.574489E+09 | 0.146987E+10 | 0.747665E+09 | 0.351352E+09 | 0.396312E+09 | 0.00 | 0.00 |
February | 0.780138E+09 | 0.130232E+10 | 0.942249E+09 | 0.401097E+09 | 0.541152E+09 | 0.00 | 0.00 |
March | 0.763044E+09 | 0.117874E+10 | 0.959275E+09 | 0.187440E+09 | 0.771835E+09 | 0.00 | 0.00 |
April | 0.259313E+10 | 0.921720E+09 | 0.223661E+10 | 0.954629E+09 | 0.128198E+10 | 0.00 | 0.00 |
May | 0.263943E+10 | 0.852034E+09 | 0.237153E+10 | 0.902352E+09 | 0.146918E+10 | 0.00 | 0.00 |
June | 0.275723E+10 | 0.618012E+09 | 0.227138E+10 | 0.770339E+09 | 0.150104E+10 | 0.00 | 0.00 |
July | 0.306827E+10 | 0.576464E+09 | 0.239803E+10 | 0.885999E+09 | 0.151203E+10 | 0.00 | 0.00 |
August | 0.305818E+10 | 0.604639E+09 | 0.232452E+10 | 0.101145E+10 | 0.131306E+10 | 0.00 | 0.00 |
September | 0.268821E+10 | 0.762561E+09 | 0.212454E+10 | 0.108535E+10 | 0.103919E+10 | 0.00 | 0.00 |
October | 0.126253E+10 | 0.108953E+10 | 0.118733E+10 | 0.514692E+09 | 0.672635E+09 | 0.00 | 0.00 |
November | 0.535609E+09 | 0.129882E+10 | 0.673197E+09 | 0.277968E+09 | 0.395230E+09 | 0.00 | 0.00 |
December | 0.365317E+09 | 0.170971E+10 | 0.526828E+09 | 0.237913E+09 | 0.288915E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.210856E+11 | 0.123844E+11 | 0.187632E+11 | 0.758058E+10 | 0.111826E+11 | 0.00 | 0.00 |
Minimum of Months | 0.365317E+09 | 0.576464E+09 | 0.526828E+09 | 0.187440E+09 | 0.288915E+09 | 0.00 | 0.00 |
Maximum of Months | 0.306827E+10 | 0.170971E+10 | 0.239803E+10 | 0.108535E+10 | 0.151203E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.105077E+10 | 0.176252E+10 | 0.123977E+10 | 0.721568E+09 | 0.518204E+09 | 0.00 | 0.00 |
February | 0.124016E+10 | 0.154363E+10 | 0.139827E+10 | 0.744341E+09 | 0.653928E+09 | 0.00 | 0.00 |
March | 0.778059E+09 | 0.141874E+10 | 0.110573E+10 | 0.241240E+09 | 0.864492E+09 | 0.00 | 0.00 |
April | 0.222247E+10 | 0.107984E+10 | 0.208442E+10 | 0.736435E+09 | 0.134798E+10 | 0.00 | 0.00 |
May | 0.193424E+10 | 0.920479E+09 | 0.198821E+10 | 0.492844E+09 | 0.149537E+10 | 0.00 | 0.00 |
June | 0.200443E+10 | 0.637239E+09 | 0.187185E+10 | 0.346800E+09 | 0.152505E+10 | 0.00 | 0.00 |
July | 0.232846E+10 | 0.588090E+09 | 0.200734E+10 | 0.475610E+09 | 0.153173E+10 | 0.00 | 0.00 |
August | 0.260716E+10 | 0.648287E+09 | 0.213295E+10 | 0.759491E+09 | 0.137346E+10 | 0.00 | 0.00 |
September | 0.273105E+10 | 0.871869E+09 | 0.227913E+10 | 0.114741E+10 | 0.113172E+10 | 0.00 | 0.00 |
October | 0.158984E+10 | 0.128402E+10 | 0.156212E+10 | 0.772674E+09 | 0.789445E+09 | 0.00 | 0.00 |
November | 0.919945E+09 | 0.155941E+10 | 0.106563E+10 | 0.569569E+09 | 0.496064E+09 | 0.00 | 0.00 |
December | 0.687564E+09 | 0.202978E+10 | 0.858811E+09 | 0.492473E+09 | 0.366338E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.200941E+11 | 0.143439E+11 | 0.195942E+11 | 0.750046E+10 | 0.120938E+11 | 0.00 | 0.00 |
Minimum of Months | 0.687564E+09 | 0.588090E+09 | 0.858811E+09 | 0.241240E+09 | 0.366338E+09 | 0.00 | 0.00 |
Maximum of Months | 0.273105E+10 | 0.202978E+10 | 0.227913E+10 | 0.114741E+10 | 0.153173E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 4.18 | 3.23 | 2.03 | 1.05 | -4.0 | 28.28 | 62.93 | 0.00 |
February | 4.25 | 3.55 | 2.74 | 1.60 | -5.0 | 43.80 | 86.73 | 0.02 |
March | 5.90 | 4.45 | 2.76 | 1.18 | -1.9 | 68.95 | 35.00 | 0.00 |
April | 8.96 | 6.24 | 3.38 | 1.56 | -0.7 | 96.13 | 186.12 | 0.00 |
May | 9.99 | 8.07 | 6.28 | 3.35 | -0.9 | 110.92 | 199.68 | 0.02 |
June | 13.31 | 11.27 | 9.70 | 3.33 | 3.35 | 121.69 | 199.28 | 0.00 |
July | 15.02 | 12.39 | 10.49 | 3.21 | 4.49 | 111.91 | 220.83 | 0.00 |
August | 15.65 | 12.75 | 10.65 | 2.92 | 3.95 | 91.47 | 211.91 | 0.00 |
September | 13.43 | 11.01 | 9.10 | 2.64 | 1.43 | 68.72 | 198.32 | 0.01 |
October | 9.33 | 8.03 | 6.81 | 1.97 | -1.0 | 48.92 | 91.86 | 0.04 |
November | 6.66 | 5.66 | 4.54 | 2.05 | -2.3 | 30.27 | 53.24 | 0.04 |
December | 4.10 | 3.14 | 1.95 | 2.36 | -5.1 | 20.52 | 40.74 | 0.04 |
Annual Sum or Average | 9.26 | 7.50 | 5.89 | 2.27 | -0.6 | 70.25 | 132.30 | 0.02 |
Minimum of Months | 4.10 | 3.14 | 1.95 | 1.05 | -5.1 | 20.52 | 35.00 | 0.00 |
Maximum of Months | 15.65 | 12.75 | 10.65 | 3.35 | 4.49 | 121.69 | 220.83 | 0.04 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 14.00 | 29-JAN-05:00 | 9.37 | 5.00 | 3.60 | 8.35 | 0.00 | 0.00 |
February | 11.00 | 07-FEB-14:00 | 9.86 | 9.00 | 2.10 | 6.35 | 138.00 | 225.00 |
March | 14.00 | 25-MAR-12:00 | 11.22 | 9.00 | 2.60 | 7.35 | 287.00 | 93.00 |
April | 24.00 | 30-APR-14:00 | 13.13 | 4.00 | 1.50 | 7.75 | 167.50 | 716.00 |
May | 24.00 | 22-MAY-14:00 | 16.08 | 11.00 | 2.60 | 9.33 | 159.00 | 769.00 |
June | 27.00 | 13-JUN-16:00 | 17.53 | 12.00 | 3.10 | 12.41 | 141.50 | 652.50 |
July | 30.00 | 22-JUL-17:00 | 16.80 | 8.00 | 0.00 | 14.28 | 122.00 | 407.00 |
August | 27.00 | 14-AUG-17:19 | 14.18 | 3.33 | 2.60 | 10.37 | 133.00 | 358.83 |
September | 23.00 | 11-SEP-16:00 | 16.22 | 12.00 | 2.60 | 8.74 | 108.00 | 325.50 |
October | 19.00 | 07-OCT-14:00 | 10.10 | 1.00 | 1.50 | 2.22 | 131.00 | 540.50 |
November | 16.00 | 24-NOV-11:00 | 12.01 | 9.00 | 4.10 | 9.33 | 61.50 | 0.00 |
December | 13.00 | 23-DEC-10:00 | 7.64 | 2.00 | 7.70 | 6.75 | 70.50 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 11.00 | 7.64 | 1.00 | 0.00 | 2.22 | 0.00 | 0.00 | |
Maximum of Months | 30.00 | 17.53 | 12.00 | 7.70 | 14.28 | 287.00 | 769.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -6.0 | 10-JAN-07:00 | -7.0 | -9.0 | 0.00 | -20.0 | 0.00 | 0.00 |
February | -4.0 | 17-FEB-06:00 | -4.0 | -4.0 | 0.00 | -20.5 | 0.00 | 0.00 |
March | -1.0 | 08-MAR-06:00 | -1.4 | -2.0 | 0.00 | -14.4 | 17.50 | 184.50 |
April | 0.00 | 08-APR-04:00 | -0.9 | -2.0 | 0.00 | -12.7 | 0.00 | 0.00 |
May | 2.00 | 06-MAY-04:00 | 1.57 | 1.00 | 3.60 | -13.7 | 12.50 | 117.00 |
June | 6.00 | 01-JUN-03:00 | 5.05 | 4.00 | 0.00 | -9.2 | 0.00 | 0.00 |
July | 7.00 | 05-JUL-04:00 | 6.47 | 6.00 | 3.10 | -7.8 | 28.00 | 155.00 |
August | 8.00 | 20-AUG-04:00 | 7.45 | 7.00 | 0.00 | -6.6 | 0.00 | 0.00 |
September | 5.00 | 20-SEP-03:00 | 5.00 | 5.00 | 2.60 | -10.0 | 0.00 | 0.00 |
October | 2.00 | 07-OCT-03:00 | 2.00 | 2.00 | 0.00 | -13.4 | 0.00 | 0.00 |
November | -2.0 | 29-NOV-01:00 | -2.0 | -2.0 | 3.10 | -10.7 | 0.00 | 0.00 |
December | -3.0 | 29-DEC-20:00 | -4.5 | -7.0 | 3.60 | -20.2 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -6.0 | -7.0 | -9.0 | 0.00 | -20.5 | 0.00 | 0.00 | |
Maximum of Months | 8.00 | 7.45 | 7.00 | 3.60 | -6.6 | 28.00 | 184.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 12.44 | 29-JAN-04:00 | 13.00 | 12.00 | 0.00 | 9.13 | 0.00 | 0.00 |
February | 9.86 | 07-FEB-14:00 | 11.00 | 9.00 | 2.10 | 6.35 | 138.00 | 225.00 |
March | 12.00 | 19-MAR-11:00 | 12.00 | 12.00 | 2.60 | 8.15 | 131.00 | 0.00 |
April | 15.39 | 28-APR-07:00 | 16.00 | 15.00 | 0.00 | 5.54 | 119.50 | 626.00 |
May | 16.08 | 22-MAY-14:00 | 24.00 | 11.00 | 2.60 | 9.33 | 159.00 | 769.00 |
June | 19.93 | 25-JUN-17:00 | 22.00 | 19.00 | 0.00 | 15.94 | 136.50 | 360.50 |
July | 17.31 | 22-JUL-09:00 | 26.00 | 12.00 | 4.60 | 11.46 | 224.50 | 619.50 |
August | 17.06 | 14-AUG-12:00 | 24.00 | 13.00 | 2.60 | 9.91 | 205.50 | 669.50 |
September | 16.54 | 10-SEP-15:00 | 21.00 | 14.00 | 3.60 | 8.54 | 160.50 | 483.00 |
October | 13.58 | 17-OCT-14:00 | 16.00 | 12.00 | 0.00 | 12.03 | 144.00 | 44.50 |
November | 12.01 | 24-NOV-11:00 | 16.00 | 9.00 | 4.10 | 9.33 | 61.50 | 0.00 |
December | 7.93 | 02-DEC-12:00 | 9.00 | 7.00 | 0.00 | 2.01 | 135.50 | 84.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 7.93 | 9.00 | 7.00 | 0.00 | 2.01 | 0.00 | 0.00 | |
Maximum of Months | 19.93 | 26.00 | 19.00 | 4.60 | 15.94 | 224.50 | 769.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 12.00 | 29-JAN-04:00 | 13.00 | 12.44 | 0.00 | 9.13 | 0.00 | 0.00 |
February | 9.00 | 07-FEB-14:00 | 11.00 | 9.86 | 2.10 | 6.35 | 138.00 | 225.00 |
March | 12.00 | 19-MAR-11:00 | 12.00 | 12.00 | 2.60 | 8.15 | 131.00 | 0.00 |
April | 15.00 | 28-APR-07:00 | 16.00 | 15.39 | 0.00 | 5.54 | 119.50 | 626.00 |
May | 12.00 | 23-MAY-07:00 | 17.00 | 13.95 | 3.10 | 5.13 | 112.00 | 719.50 |
June | 19.00 | 25-JUN-17:00 | 22.00 | 19.93 | 0.00 | 15.94 | 136.50 | 360.50 |
July | 14.00 | 17-JUL-17:00 | 18.00 | 15.45 | 3.60 | 9.91 | 120.00 | 0.00 |
August | 16.00 | 08-AUG-12:00 | 18.00 | 16.70 | 1.50 | 11.46 | 154.00 | 0.00 |
September | 14.00 | 10-SEP-15:00 | 21.00 | 16.54 | 3.60 | 8.54 | 160.50 | 483.00 |
October | 13.00 | 17-OCT-18:00 | 13.00 | 13.00 | 2.60 | 9.33 | 0.00 | 0.00 |
November | 12.00 | 08-NOV-14:00 | 12.00 | 12.00 | 0.00 | 8.15 | 93.00 | 106.00 |
December | 7.00 | 02-DEC-11:00 | 8.00 | 7.45 | 3.10 | 1.16 | 144.50 | 146.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 7.00 | 8.00 | 7.45 | 0.00 | 1.16 | 0.00 | 0.00 | |
Maximum of Months | 19.00 | 22.00 | 19.93 | 3.60 | 15.94 | 160.50 | 719.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 10.33 | 8.85 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 10.00 | 14.79 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 10.33 | 17.09 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 11.26 | 40.86 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 12.54 | 47.73 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 13.82 | 50.98 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 14.77 | 51.67 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 15.12 | 44.67 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 14.78 | 34.25 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 13.84 | 17.71 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 12.55 | 9.34 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 11.27 | 6.14 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 12.57 | 28.73 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 10.00 | 6.14 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 15.12 | 51.67 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH BOOSTER E WATER HEATER
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.770802E+10 | -0.754278E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -165241720.9 | 81.21 | 0.00 | 0.00 |
February | 0.696509E+10 | -0.681596E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -149127059.3 | 81.21 | 0.00 | 0.00 |
March | 0.770646E+10 | -0.754146E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164995997.1 | 81.21 | 0.00 | 0.00 |
April | 0.746765E+10 | -0.730859E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -159058282.7 | 81.21 | 0.00 | 0.00 |
May | 0.770711E+10 | -0.754280E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164309066.2 | 81.21 | 0.00 | 0.00 |
June | 0.745937E+10 | -0.730053E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -158838996.1 | 81.21 | 0.00 | 0.00 |
July | 0.771492E+10 | -0.755085E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164064555.5 | 81.21 | 0.00 | 0.00 |
August | 0.770688E+10 | -0.754281E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164073399.8 | 81.21 | 0.00 | 0.00 |
September | 0.746885E+10 | -0.730994E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -158912387.4 | 81.21 | 0.00 | 0.00 |
October | 0.770619E+10 | -0.754143E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164753699.7 | 81.21 | 0.00 | 0.00 |
November | 0.745224E+10 | -0.729243E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -159806288.1 | 81.21 | 0.00 | 0.00 |
December | 0.771626E+10 | -0.755084E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -165416589.7 | 81.21 | 0.00 | 0.00 |
Annual Sum or Average | 0.907790E+11 | -0.888404E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.193860E+10 | 81.21 | 0.00 | 0.00 |
Minimum of Months | 0.696509E+10 | -0.755085E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -165416589.7 | 81.21 | 0.00 | 0.00 |
Maximum of Months | 0.771626E+10 | -0.681596E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -149127059.3 | 81.21 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH LAUNDRY G WATER HEATER
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.121962E+12 | -0.120147E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.181494E+10 | 81.27 | 0.00 | 0.00 |
February | 0.110675E+12 | -0.109035E+12 | 0.00 | 0.00 | 672.00 | 0.00 | -0.163971E+10 | 81.28 | 0.00 | 0.00 |
March | 0.121954E+12 | -0.120138E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.181573E+10 | 81.28 | 0.00 | 0.00 |
April | 0.116483E+12 | -0.114726E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.175717E+10 | 81.27 | 0.00 | 0.00 |
May | 0.118180E+12 | -0.116364E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.181575E+10 | 81.27 | 0.00 | 0.00 |
June | 0.112245E+12 | -0.110488E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.175700E+10 | 81.26 | 0.00 | 0.00 |
July | 0.114376E+12 | -0.112561E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.181520E+10 | 81.26 | 0.00 | 0.00 |
August | 0.113773E+12 | -0.111958E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.181503E+10 | 81.26 | 0.00 | 0.00 |
September | 0.110669E+12 | -0.108914E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.175563E+10 | 81.26 | 0.00 | 0.00 |
October | 0.115963E+12 | -0.114149E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.181380E+10 | 81.26 | 0.00 | 0.00 |
November | 0.114338E+12 | -0.112583E+12 | 0.00 | 0.00 | 720.00 | 0.00 | -0.175489E+10 | 81.26 | 0.00 | 0.00 |
December | 0.120338E+12 | -0.118524E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.181399E+10 | 81.27 | 0.00 | 0.00 |
Annual Sum or Average | 0.139096E+13 | -0.136959E+13 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.213688E+11 | 81.27 | 0.00 | 0.00 |
Minimum of Months | 0.110669E+12 | -0.120147E+12 | 0.00 | 0.00 | 672.00 | 0.00 | -0.181575E+10 | 81.26 | 0.00 | 0.00 |
Maximum of Months | 0.121962E+12 | -0.108914E+12 | 0.00 | 0.00 | 744.00 | 0.00 | -0.163971E+10 | 81.28 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.726773E+11 | -0.710927E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.158463E+10 | 58.98 | 0.00 | 0.00 |
February | 0.660875E+11 | -0.646558E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.143172E+10 | 58.98 | 0.00 | 0.00 |
March | 0.727345E+11 | -0.711489E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.158555E+10 | 58.98 | 0.00 | 0.00 |
April | 0.690414E+11 | -0.675066E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.153481E+10 | 58.98 | 0.00 | 0.00 |
May | 0.694824E+11 | -0.678964E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.158595E+10 | 58.98 | 0.00 | 0.00 |
June | 0.654454E+11 | -0.639107E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.153466E+10 | 58.98 | 0.00 | 0.00 |
July | 0.661807E+11 | -0.645952E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.158551E+10 | 58.98 | 0.00 | 0.00 |
August | 0.657282E+11 | -0.641431E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.158510E+10 | 58.98 | 0.00 | 0.00 |
September | 0.640599E+11 | -0.625269E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.153300E+10 | 58.98 | 0.00 | 0.00 |
October | 0.675416E+11 | -0.659583E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.158330E+10 | 58.98 | 0.00 | 0.00 |
November | 0.671790E+11 | -0.656473E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.153172E+10 | 58.98 | 0.00 | 0.00 |
December | 0.712900E+11 | -0.697065E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.158356E+10 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.817448E+12 | -0.798788E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.186595E+11 | 58.98 | 0.00 | 0.00 |
Minimum of Months | 0.640599E+11 | -0.711489E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.158595E+10 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.727345E+11 | -0.625269E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.143172E+10 | 58.98 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 195.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 217.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 215.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 359.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 417.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 410.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 429.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 396.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 337.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 234.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 171.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 131.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3515.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 131.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 429.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.686782E+10 | 68711.33 | 10-JAN-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.113908E+10 | 46783.60 | 17-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 31443508.14 | 13966.71 | 08-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.198026E+09 | 15902.93 | 21-APR-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.276652E+09 | 15970.40 | 12-MAY-12:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.446125E+09 | 18330.89 | 19-JUN-10:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.418641E+09 | 20753.95 | 20-JUL-21:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.175606E+09 | 16219.05 | 31-AUG-09:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.340002E+09 | 16312.18 | 19-SEP-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.254979E+09 | 16024.61 | 08-OCT-11:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.197647E+09 | 19534.77 | 29-NOV-07:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129531E+10 | 34697.09 | 29-DEC-24:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.116413E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 31443508.14 | 13966.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.686782E+10 | 68711.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BASEMENT VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.693226E+10 | 9556.66 | 17-JAN-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.732253E+10 | 9586.18 | 22-FEB-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.956065E+10 | 9623.84 | 25-MAR-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.101910E+11 | 9798.90 | 30-APR-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.106198E+11 | 9783.08 | 23-MAY-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.997001E+10 | 9804.17 | 25-JUN-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.914503E+10 | 9837.67 | 23-JUL-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.846993E+10 | 9786.66 | 19-AUG-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.615982E+10 | 9758.75 | 12-SEP-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.464832E+10 | 9500.98 | 02-OCT-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.383588E+10 | 7706.50 | 13-NOV-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.492672E+10 | 7881.80 | 18-DEC-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.917820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.383588E+10 | 7706.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.106198E+11 | 9837.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.722602E+10 | 3198.33 | 29-JAN-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.620384E+10 | 3194.50 | 26-FEB-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.727964E+10 | 3218.29 | 19-MAR-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.498856E+10 | 3189.34 | 10-APR-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.532488E+10 | 3210.16 | 05-MAY-07:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.465367E+10 | 3171.14 | 07-JUN-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.437251E+10 | 2893.34 | 08-JUL-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.403985E+10 | 2958.74 | 08-AUG-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.403149E+10 | 3130.09 | 08-SEP-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.600001E+10 | 3199.83 | 09-OCT-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.685349E+10 | 3196.47 | 07-NOV-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.780803E+10 | 3187.52 | 24-DEC-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.687820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.403149E+10 | 2893.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.780803E+10 | 3218.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_2_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.163593E+10 | 1259.06 | 04-JAN-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.139777E+10 | 1254.03 | 27-FEB-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.152474E+10 | 1270.52 | 13-MAR-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.102881E+10 | 1228.61 | 11-APR-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.103255E+10 | 1274.42 | 05-MAY-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.814986E+09 | 1207.71 | 09-JUN-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.766441E+09 | 1236.20 | 05-JUL-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.724180E+09 | 1142.02 | 24-AUG-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.780776E+09 | 1176.43 | 07-SEP-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.124145E+10 | 1216.10 | 17-OCT-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.148329E+10 | 1241.10 | 30-NOV-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.182527E+10 | 1269.63 | 29-DEC-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.142562E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.724180E+09 | 1142.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.182527E+10 | 1274.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: MECH_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.278716E+10 | 1629.69 | 12-JAN-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.246070E+10 | 1525.83 | 17-FEB-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.244416E+10 | 1478.71 | 13-MAR-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.186591E+10 | 1439.07 | 08-APR-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.178137E+10 | 1442.50 | 06-MAY-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.129441E+10 | 1253.64 | 02-JUN-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.118836E+10 | 1254.93 | 01-JUL-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.119701E+10 | 1200.19 | 12-AUG-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.142747E+10 | 1271.95 | 07-SEP-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.207755E+10 | 1375.49 | 23-OCT-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.241702E+10 | 1460.12 | 29-NOV-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.292372E+10 | 1553.91 | 30-DEC-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.238648E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.118836E+10 | 1200.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.292372E+10 | 1629.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: STORAGE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.185251E+10 | 948.99 | 10-JAN-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.163611E+10 | 873.51 | 18-FEB-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.165183E+10 | 851.29 | 15-MAR-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.126673E+10 | 801.24 | 08-APR-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.121502E+10 | 810.14 | 05-MAY-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.892815E+09 | 698.29 | 06-JUN-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.815959E+09 | 698.72 | 01-JUL-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.824829E+09 | 650.56 | 12-AUG-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.984713E+09 | 709.68 | 21-SEP-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.141957E+10 | 780.51 | 23-OCT-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.162697E+10 | 882.38 | 29-NOV-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.193252E+10 | 909.47 | 30-DEC-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.161196E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.815959E+09 | 650.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.193252E+10 | 948.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LAUNDRY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.131726E+11 | 12193.52 | 09-JAN-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.118772E+11 | 12013.26 | 18-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.129970E+11 | 12290.18 | 25-MAR-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.127814E+11 | 12891.53 | 30-APR-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.131276E+11 | 12870.70 | 23-MAY-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.128092E+11 | 12898.46 | 25-JUN-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.133377E+11 | 12942.53 | 23-JUL-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.133365E+11 | 12875.41 | 19-AUG-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.127008E+11 | 12838.70 | 12-SEP-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.128401E+11 | 12743.23 | 07-OCT-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.125194E+11 | 12105.42 | 27-NOV-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.133626E+11 | 12105.51 | 11-DEC-04:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.154862E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.118772E+11 | 12013.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.133626E+11 | 12942.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAFE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.161788E+11 | 10402.20 | 24-JAN-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.135413E+11 | 10391.59 | 07-FEB-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.162787E+11 | 10477.69 | 19-MAR-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.101959E+11 | 10384.19 | 10-APR-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.112301E+11 | 10500.41 | 18-MAY-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.986658E+10 | 10480.44 | 05-JUN-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.909917E+10 | 9453.84 | 08-JUL-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.789875E+10 | 10510.06 | 08-AUG-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.762753E+10 | 10488.96 | 08-SEP-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.127336E+11 | 10440.52 | 13-OCT-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.152277E+11 | 10406.86 | 07-NOV-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.181373E+11 | 10364.80 | 23-DEC-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.148015E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.762753E+10 | 9453.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.181373E+11 | 10510.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LOBBY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.264640E+11 | 26086.53 | 04-JAN-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.222360E+11 | 25332.02 | 16-FEB-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.255013E+11 | 25575.15 | 15-MAR-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.164778E+11 | 24821.39 | 10-APR-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.176483E+11 | 24896.30 | 16-MAY-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.150301E+11 | 24569.31 | 07-JUN-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.142178E+11 | 23818.86 | 03-JUL-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.126456E+11 | 23422.08 | 08-AUG-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.119546E+11 | 24611.35 | 08-SEP-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.197355E+11 | 24805.47 | 17-OCT-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.241383E+11 | 25528.37 | 30-NOV-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.298389E+11 | 25942.57 | 01-DEC-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.235888E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.119546E+11 | 23422.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.298389E+11 | 26086.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.151141E+11 | 9541.79 | 04-JAN-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.124121E+11 | 9079.80 | 16-FEB-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.133575E+11 | 8784.29 | 15-MAR-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.513912E+10 | 7357.65 | 10-APR-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.480774E+10 | 6633.08 | 17-MAY-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.230535E+10 | 6006.36 | 07-JUN-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.155512E+10 | 4623.03 | 08-JUL-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.108504E+10 | 5152.54 | 09-AUG-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.220649E+10 | 6373.79 | 08-SEP-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.923466E+10 | 8086.14 | 20-OCT-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.135478E+11 | 9296.34 | 30-NOV-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.176683E+11 | 9553.84 | 15-DEC-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.984333E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.108504E+10 | 4623.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.176683E+11 | 9553.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.127674E+11 | 6570.81 | 09-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.108094E+11 | 6571.01 | 17-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.113013E+11 | 6033.24 | 16-MAR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.691168E+10 | 5395.02 | 09-APR-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.665957E+10 | 4800.70 | 07-MAY-04:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.465581E+10 | 4465.09 | 07-JUN-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.402596E+10 | 3978.80 | 09-JUL-04:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.412631E+10 | 3740.67 | 24-AUG-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.535783E+10 | 4612.37 | 21-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.934364E+10 | 5462.88 | 23-OCT-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.113298E+11 | 6387.92 | 29-NOV-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.137273E+11 | 6571.78 | 31-DEC-05:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.101016E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.402596E+10 | 3740.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.137273E+11 | 6571.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BANQUET_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.353535E+10 | 7411.95 | 10-JAN-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.274671E+10 | 6984.39 | 17-FEB-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.242548E+10 | 6252.53 | 13-MAR-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.120027E+10 | 6564.03 | 14-APR-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.101998E+10 | 6517.85 | 05-MAY-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.581029E+09 | 5845.61 | 06-JUN-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.459100E+09 | 5881.67 | 31-JUL-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.680552E+09 | 6081.30 | 23-AUG-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.103323E+10 | 6626.28 | 21-SEP-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.205568E+10 | 6821.00 | 04-OCT-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.286822E+10 | 6639.31 | 03-NOV-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.381757E+10 | 6764.53 | 26-DEC-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.224232E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.459100E+09 | 5845.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.381757E+10 | 7411.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: DINING_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.286924E+10 | 7003.54 | 10-JAN-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.217374E+10 | 6497.26 | 17-FEB-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.181745E+10 | 5762.22 | 13-MAR-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.753934E+09 | 6092.75 | 14-APR-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.599382E+09 | 5940.97 | 05-MAY-10:45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.282071E+09 | 5274.90 | 06-JUN-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.220545E+09 | 5307.30 | 31-JUL-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.362076E+09 | 5440.09 | 21-AUG-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.617871E+09 | 6063.05 | 21-SEP-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.150350E+10 | 6390.29 | 04-OCT-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.228350E+10 | 6201.21 | 03-NOV-10:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.310587E+10 | 6354.58 | 26-DEC-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.165892E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.220545E+09 | 5274.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.310587E+10 | 7003.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: KITCHEN_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.202129E+10 | 5553.66 | 10-JAN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.182651E+10 | 5313.83 | 26-FEB-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.180255E+10 | 4796.78 | 16-MAR-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.140907E+10 | 4372.55 | 01-APR-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.134174E+10 | 4223.49 | 05-MAY-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.100363E+10 | 3832.16 | 08-JUN-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.964620E+09 | 3498.68 | 09-JUL-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.935764E+09 | 3324.34 | 23-AUG-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.109156E+10 | 3750.75 | 17-SEP-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.154651E+10 | 4445.70 | 23-OCT-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.179307E+10 | 5189.26 | 29-NOV-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.213102E+10 | 5553.65 | 30-DEC-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.178673E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.935764E+09 | 3324.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.213102E+10 | 5553.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: FLR_3_DOAS HEATING COIL
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.445327E+09 | 5100.86 | 10-JAN-08:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.120929E+09 | 3317.51 | 17-FEB-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 3005469.02 | 764.00 | 08-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 17644.25 | 0.84 | 30-APR-19:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 11118.50 | 0.91 | 21-MAY-20:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 26777.63 | 0.91 | 21-JUN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 46328.27 | 0.90 | 16-JUL-14:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 58125.16 | 0.90 | 17-AUG-18:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 23299.16 | 0.83 | 19-SEP-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 2014.16 | 0.78 | 11-OCT-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 8384552.07 | 954.61 | 29-NOV-02:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.230384E+09 | 2779.90 | 29-DEC-24:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.808216E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 2014.16 | 0.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.445327E+09 | 5100.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.272163E+10 | 5401.05 | 04-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.198932E+10 | 5381.60 | 01-FEB-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.186531E+10 | 5400.38 | 15-MAR-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.403980E+09 | 5239.10 | 10-APR-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.293063E+09 | 5194.18 | 05-MAY-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 32588910.88 | 3688.78 | 18-JUN-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 41000164.72 | 3557.60 | 30-JUL-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 10527395.61 | 3395.02 | 12-AUG-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 94755200.65 | 3123.80 | 06-SEP-18:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.944164E+09 | 5323.19 | 19-OCT-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.210312E+10 | 5400.91 | 30-NOV-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.374330E+10 | 5401.53 | 16-DEC-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.142428E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 10527395.61 | 3123.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.374330E+10 | 5401.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.352297E+10 | 5313.76 | 06-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.263464E+10 | 5314.38 | 01-FEB-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.218354E+10 | 5312.96 | 15-MAR-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.595344E+09 | 5178.38 | 10-APR-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.360585E+09 | 5120.78 | 05-MAY-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 39207596.75 | 2869.74 | 17-JUN-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 45301955.65 | 3410.02 | 04-JUL-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 15965955.29 | 3342.98 | 12-AUG-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.177248E+09 | 3266.00 | 10-SEP-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.131421E+10 | 5245.70 | 27-OCT-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.267791E+10 | 5313.81 | 21-NOV-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.432379E+10 | 5314.39 | 02-DEC-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.178907E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 15965955.29 | 2869.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.432379E+10 | 5314.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.611320E+09 | 7584.66 | 17-DEC-04:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.611320E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.611320E+09 | 7584.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.537774E+10 | 29610.85 | 11-JAN-16:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.334415E+10 | 28866.68 | 17-FEB-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.112234E+10 | 28797.21 | 15-MAR-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.154683E+09 | 22612.69 | 01-APR-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 72336306.11 | 19741.39 | 26-MAY-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 27269480.67 | 18785.57 | 27-JUN-08:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 35504588.01 | 20724.67 | 13-JUL-08:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 32501804.47 | 25558.68 | 04-AUG-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 64658019.16 | 25854.05 | 29-SEP-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.234207E+09 | 19829.28 | 06-OCT-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.223689E+10 | 29256.84 | 29-NOV-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.648457E+10 | 29394.40 | 27-DEC-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.191868E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 27269480.67 | 18785.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.648457E+10 | 29610.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.277472E+10 | 5311.65 | 04-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.212645E+10 | 5307.08 | 01-FEB-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.191520E+10 | 5310.95 | 15-MAR-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.390223E+09 | 5133.34 | 10-APR-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.304573E+09 | 2733.06 | 14-MAY-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 58507511.81 | 3146.89 | 03-JUN-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 31792508.65 | 2876.28 | 02-JUL-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 9574386.79 | 2967.44 | 26-AUG-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 75798001.03 | 2550.42 | 08-SEP-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.958645E+09 | 5239.26 | 27-OCT-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.214492E+10 | 5311.50 | 30-NOV-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.364919E+10 | 5312.13 | 16-DEC-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144396E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 9574386.79 | 2550.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.364919E+10 | 5312.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.353819E+10 | 5225.95 | 04-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.281377E+10 | 5226.74 | 01-FEB-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.222934E+10 | 5225.21 | 15-MAR-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.555341E+09 | 5071.95 | 10-APR-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.381070E+09 | 2923.91 | 04-MAY-08:63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 75998564.20 | 3206.09 | 17-JUN-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 40157225.28 | 2730.75 | 07-JUL-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 19632641.35 | 2674.59 | 22-AUG-15:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.155493E+09 | 3548.84 | 29-SEP-18:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.130437E+10 | 5163.44 | 27-OCT-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.269280E+10 | 5226.13 | 21-NOV-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.418289E+10 | 5226.67 | 02-DEC-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.179890E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 19632641.35 | 2674.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.418289E+10 | 5226.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.108008E+10 | 1674.58 | 14-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.797625E+09 | 1674.82 | 01-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.752785E+09 | 1674.41 | 16-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.193784E+09 | 1643.08 | 10-APR-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.139148E+09 | 1626.30 | 05-MAY-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 21428835.43 | 906.44 | 03-JUN-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 21359725.24 | 939.39 | 30-JUL-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 5903973.57 | 819.98 | 03-AUG-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 53648764.18 | 872.26 | 02-SEP-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.421755E+09 | 1674.60 | 19-OCT-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.847078E+09 | 1674.96 | 24-NOV-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.140450E+10 | 1674.79 | 05-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.573910E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 5903973.57 | 819.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.140450E+10 | 1674.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.133645E+10 | 1640.83 | 23-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.100758E+10 | 1641.09 | 01-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.858257E+09 | 1640.62 | 16-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.263473E+09 | 1618.69 | 10-APR-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.165748E+09 | 1596.69 | 05-MAY-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 25909419.05 | 869.18 | 18-JUN-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 23130384.30 | 920.47 | 30-JUL-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 11407807.26 | 810.19 | 26-AUG-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 93115162.24 | 1572.28 | 20-SEP-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.554014E+09 | 1640.99 | 16-OCT-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.103300E+10 | 1641.20 | 24-NOV-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.158705E+10 | 1641.02 | 05-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.695914E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 11407807.26 | 810.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.158705E+10 | 1641.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL HEATING COIL
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.246528E+10 | 8256.34 | 04-JAN-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.178202E+10 | 8156.73 | 02-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.185833E+10 | 8214.03 | 15-MAR-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.340286E+09 | 5820.14 | 10-APR-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.305775E+09 | 4505.89 | 24-MAY-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 46547069.21 | 5040.16 | 20-JUN-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 31210456.06 | 4815.72 | 12-JUL-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 8929691.04 | 5029.63 | 04-AUG-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 42138440.10 | 4193.54 | 17-SEP-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.696526E+09 | 8085.60 | 27-OCT-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.175585E+10 | 8257.14 | 30-NOV-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.387065E+10 | 8258.07 | 16-DEC-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.132035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 8929691.04 | 4193.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.387065E+10 | 8258.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 6818783.35 | 6818783.35 | 6819.07 | 29-JAN-06:00 | 6819.07 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 4067563.16 | 4067563.16 | 6762.51 | 25-MAR-13:00 | 6762.51 | 0.00 |
April | 0.00 | 0.00 | 0.309439E+11 | 0.308306E+11 | 279294.24 | 30-APR-18:10 | 279294.24 | 0.04 |
May | 0.00 | 0.00 | 0.333113E+11 | 0.333113E+11 | 257668.21 | 22-MAY-15:30 | 257668.21 | 0.11 |
June | 0.00 | 0.00 | 0.103271E+12 | 0.969350E+11 | 487407.05 | 25-JUN-18:17 | 236831.18 | 0.41 |
July | 0.00 | 0.00 | 0.177173E+12 | 0.169732E+12 | 380312.18 | 22-JUL-10:35 | 317906.95 | 0.61 |
August | 0.00 | 0.00 | 0.210060E+12 | 0.201853E+12 | 349922.15 | 14-AUG-10:35 | 271817.17 | 0.69 |
September | 0.00 | 0.00 | 0.113591E+12 | 0.110409E+12 | 293907.01 | 10-SEP-16:00 | 225845.66 | 0.44 |
October | 0.00 | 0.00 | 0.809054E+10 | 0.809054E+10 | 149490.71 | 07-OCT-15:20 | 149490.71 | 0.03 |
November | 0.00 | 0.00 | 0.223888E+09 | 0.223888E+09 | 68230.25 | 24-NOV-11:50 | 68230.25 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.676676E+12 | 0.651396E+12 | 0.19 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.210060E+12 | 0.201853E+12 | 487407.05 | 317906.95 | 0.69 |
Report: CoilReportMonthly
For: FLR_3_DOAS COOLING COIL
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.246108E+10 | 0.245921E+10 | 28621.53 | 30-APR-18:02 | 28621.53 | 0.03 |
May | 0.00 | 0.00 | 0.246348E+10 | 0.246348E+10 | 28400.77 | 22-MAY-15:00 | 28400.77 | 0.08 |
June | 0.00 | 0.00 | 0.833263E+10 | 0.762647E+10 | 45838.53 | 25-JUN-18:00 | 20538.48 | 0.27 |
July | 0.00 | 0.00 | 0.147069E+11 | 0.139146E+11 | 34524.85 | 23-JUL-16:00 | 24929.04 | 0.47 |
August | 0.00 | 0.00 | 0.178711E+11 | 0.169080E+11 | 34502.27 | 17-AUG-15:00 | 25039.96 | 0.56 |
September | 0.00 | 0.00 | 0.919189E+10 | 0.876880E+10 | 32609.72 | 12-SEP-14:00 | 22710.87 | 0.33 |
October | 0.00 | 0.00 | 0.434540E+09 | 0.434540E+09 | 15105.80 | 07-OCT-15:00 | 15105.80 | 0.01 |
November | 0.00 | 0.00 | 6967953.45 | 6967953.45 | 4049.57 | 24-NOV-12:00 | 4049.57 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.554687E+11 | 0.525820E+11 | 0.15 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.178711E+11 | 0.169080E+11 | 45838.53 | 28621.53 | 0.56 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 49961726.72 | 27665834.08 | 13848.27 | 25-JAN-16:01 | 13848.27 | 0.02 |
February | 0.00 | 0.00 | 0.251777E+09 | 0.223900E+09 | 17442.06 | 09-FEB-16:01 | 17442.06 | 0.02 |
March | 0.00 | 0.00 | 0.148833E+09 | 0.125953E+09 | 17019.93 | 20-MAR-18:02 | 17019.93 | 0.02 |
April | 0.00 | 0.00 | 0.310788E+10 | 0.235885E+10 | 17443.39 | 16-APR-18:01 | 17443.39 | 0.35 |
May | 0.00 | 0.00 | 0.366562E+10 | 0.242128E+10 | 17442.63 | 29-MAY-18:02 | 17442.63 | 0.51 |
June | 0.00 | 0.00 | 0.541757E+10 | 0.314633E+10 | 19084.52 | 27-JUN-08:62 | 14668.52 | 0.77 |
July | 0.00 | 0.00 | 0.677845E+10 | 0.395179E+10 | 18424.54 | 18-JUL-15:02 | 15926.88 | 0.80 |
August | 0.00 | 0.00 | 0.631989E+10 | 0.348576E+10 | 19014.40 | 11-AUG-15:01 | 15263.67 | 0.87 |
September | 0.00 | 0.00 | 0.463672E+10 | 0.261315E+10 | 18403.18 | 19-SEP-15:02 | 15366.04 | 0.71 |
October | 0.00 | 0.00 | 0.110357E+10 | 0.707337E+09 | 17438.84 | 07-OCT-15:02 | 17438.84 | 0.21 |
November | 0.00 | 0.00 | 62416711.75 | 40049363.14 | 17371.64 | 03-NOV-15:01 | 17371.64 | 0.02 |
December | 0.00 | 0.00 | 1333379.28 | 727366.99 | 1758.17 | 20-DEC-19:05 | 625.37 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.315440E+11 | 0.191028E+11 | 0.36 | |||
Minimum of Months | 0.00 | 0.00 | 1333379.28 | 727366.99 | 1758.17 | 625.37 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.677845E+10 | 0.395179E+10 | 19084.52 | 17443.39 | 0.87 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 6353835.19 | 2612811.09 | 10034.87 | 19-JAN-16:01 | 9265.00 | 0.00 |
February | 0.00 | 0.00 | 70422738.66 | 61249054.75 | 14748.13 | 19-FEB-16:02 | 14748.13 | 0.01 |
March | 0.00 | 0.00 | 77928660.08 | 68066188.26 | 14838.60 | 20-MAR-18:02 | 14838.60 | 0.01 |
April | 0.00 | 0.00 | 0.195476E+10 | 0.148247E+10 | 15607.82 | 17-APR-15:02 | 15607.82 | 0.25 |
May | 0.00 | 0.00 | 0.287266E+10 | 0.194040E+10 | 15607.24 | 29-MAY-18:02 | 15607.24 | 0.42 |
June | 0.00 | 0.00 | 0.478536E+10 | 0.286091E+10 | 17046.44 | 27-JUN-08:62 | 13062.12 | 0.71 |
July | 0.00 | 0.00 | 0.584941E+10 | 0.346332E+10 | 16557.58 | 18-JUL-15:02 | 14212.55 | 0.75 |
August | 0.00 | 0.00 | 0.470072E+10 | 0.255919E+10 | 16878.89 | 11-AUG-18:02 | 14066.66 | 0.76 |
September | 0.00 | 0.00 | 0.266203E+10 | 0.144750E+10 | 16248.04 | 02-SEP-18:02 | 13826.67 | 0.53 |
October | 0.00 | 0.00 | 0.429624E+09 | 0.290441E+09 | 15602.71 | 07-OCT-15:02 | 15602.71 | 0.09 |
November | 0.00 | 0.00 | 11172250.42 | 7899018.29 | 8992.55 | 10-NOV-16:02 | 8808.01 | 0.00 |
December | 0.00 | 0.00 | 100458.08 | 30120.70 | 858.75 | 02-DEC-09:05 | 206.31 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.234205E+11 | 0.141841E+11 | 0.30 | |||
Minimum of Months | 0.00 | 0.00 | 100458.08 | 30120.70 | 858.75 | 206.31 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.584941E+10 | 0.346332E+10 | 17046.44 | 15607.82 | 0.76 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.483953E+10 | 0.443967E+10 | 40129.05 | 21-JAN-11:25 | 40129.05 | 0.03 |
February | 0.00 | 0.00 | 0.518336E+10 | 0.490526E+10 | 35724.21 | 04-FEB-14:00 | 35724.21 | 0.02 |
March | 0.00 | 0.00 | 0.266107E+09 | 0.218088E+09 | 12965.78 | 25-MAR-11:40 | 12965.78 | 0.01 |
April | 0.00 | 0.00 | 0.279663E+11 | 0.259005E+11 | 50667.71 | 30-APR-12:30 | 50460.94 | 0.12 |
May | 0.00 | 0.00 | 0.219573E+11 | 0.152986E+11 | 41368.51 | 23-MAY-13:00 | 28397.59 | 0.34 |
June | 0.00 | 0.00 | 0.265572E+11 | 0.116983E+11 | 40575.61 | 13-JUN-13:10 | 28245.03 | 0.68 |
July | 0.00 | 0.00 | 0.333793E+11 | 0.154748E+11 | 47050.33 | 22-JUL-13:10 | 38555.30 | 0.76 |
August | 0.00 | 0.00 | 0.400160E+11 | 0.217659E+11 | 51889.83 | 19-AUG-12:50 | 43061.14 | 0.79 |
September | 0.00 | 0.00 | 0.458117E+11 | 0.293918E+11 | 64095.34 | 23-SEP-14:30 | 52094.47 | 0.72 |
October | 0.00 | 0.00 | 0.186119E+11 | 0.147188E+11 | 59066.09 | 07-OCT-13:10 | 59066.09 | 0.22 |
November | 0.00 | 0.00 | 0.375125E+10 | 0.335427E+10 | 38365.73 | 11-NOV-13:30 | 38365.73 | 0.02 |
December | 0.00 | 0.00 | 0.193796E+09 | 0.193796E+09 | 12782.98 | 26-DEC-14:30 | 12782.98 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.228534E+12 | 0.147360E+12 | 0.31 | |||
Minimum of Months | 0.00 | 0.00 | 0.193796E+09 | 0.193796E+09 | 12782.98 | 12782.98 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.458117E+11 | 0.293918E+11 | 64095.34 | 59066.09 | 0.79 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.397135E+10 | 0.203052E+10 | 68115.58 | 29-JAN-19:02 | 68115.58 | 0.20 |
February | 0.00 | 0.00 | 0.368559E+10 | 0.229004E+10 | 73288.34 | 12-FEB-09:02 | 73288.34 | 0.16 |
March | 0.00 | 0.00 | 0.102947E+11 | 0.740858E+10 | 76155.67 | 11-MAR-09:02 | 76155.67 | 0.27 |
April | 0.00 | 0.00 | 0.233654E+11 | 0.183338E+11 | 79550.06 | 22-APR-15:02 | 79550.06 | 0.45 |
May | 0.00 | 0.00 | 0.314232E+11 | 0.219693E+11 | 80746.96 | 23-MAY-15:02 | 74400.30 | 0.64 |
June | 0.00 | 0.00 | 0.457088E+11 | 0.306776E+11 | 89052.07 | 26-JUN-18:02 | 70853.90 | 0.70 |
July | 0.00 | 0.00 | 0.504623E+11 | 0.337060E+11 | 84684.00 | 25-JUL-15:02 | 73220.53 | 0.71 |
August | 0.00 | 0.00 | 0.439096E+11 | 0.274162E+11 | 86170.75 | 11-AUG-15:01 | 70262.26 | 0.70 |
September | 0.00 | 0.00 | 0.319454E+11 | 0.192857E+11 | 84855.17 | 16-SEP-08:62 | 68510.90 | 0.70 |
October | 0.00 | 0.00 | 0.155821E+11 | 0.828760E+10 | 80430.89 | 09-OCT-08:62 | 72738.18 | 0.58 |
November | 0.00 | 0.00 | 0.648716E+10 | 0.329906E+10 | 77258.89 | 08-NOV-19:03 | 70513.10 | 0.31 |
December | 0.00 | 0.00 | 0.205604E+10 | 0.112322E+10 | 62577.53 | 02-DEC-09:02 | 62577.53 | 0.11 |
Annual Sum or Average | 0.00 | 0.00 | 0.268892E+12 | 0.175828E+12 | 0.46 | |||
Minimum of Months | 0.00 | 0.00 | 0.205604E+10 | 0.112322E+10 | 62577.53 | 62577.53 | 0.11 | |
Maximum of Months | 0.00 | 0.00 | 0.504623E+11 | 0.337060E+11 | 89052.07 | 79550.06 | 0.71 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.108374E+09 | 55059275.29 | 9839.28 | 21-JAN-16:02 | 9078.73 | 0.02 |
February | 0.00 | 0.00 | 0.179290E+09 | 0.121510E+09 | 14973.91 | 04-FEB-16:01 | 14973.91 | 0.03 |
March | 0.00 | 0.00 | 0.121181E+09 | 81728651.96 | 13338.00 | 20-MAR-15:01 | 13338.00 | 0.02 |
April | 0.00 | 0.00 | 0.350823E+10 | 0.267003E+10 | 15850.09 | 17-APR-15:02 | 15850.09 | 0.37 |
May | 0.00 | 0.00 | 0.366563E+10 | 0.226648E+10 | 15848.97 | 02-MAY-15:02 | 15848.97 | 0.56 |
June | 0.00 | 0.00 | 0.503741E+10 | 0.281164E+10 | 17451.68 | 27-JUN-08:62 | 13327.95 | 0.77 |
July | 0.00 | 0.00 | 0.633149E+10 | 0.356296E+10 | 16843.18 | 28-JUL-15:01 | 14472.07 | 0.84 |
August | 0.00 | 0.00 | 0.663048E+10 | 0.370201E+10 | 17293.30 | 11-AUG-15:01 | 13966.24 | 0.89 |
September | 0.00 | 0.00 | 0.519220E+10 | 0.296899E+10 | 16866.72 | 02-SEP-08:62 | 13792.29 | 0.77 |
October | 0.00 | 0.00 | 0.118751E+10 | 0.742591E+09 | 15845.66 | 07-OCT-15:02 | 15845.66 | 0.22 |
November | 0.00 | 0.00 | 0.105128E+09 | 62226146.73 | 14714.48 | 03-NOV-15:01 | 14714.48 | 0.02 |
December | 0.00 | 0.00 | 29268839.52 | 15325714.17 | 2894.65 | 06-DEC-09:03 | 1730.63 | 0.01 |
Annual Sum or Average | 0.00 | 0.00 | 0.320962E+11 | 0.190606E+11 | 0.38 | |||
Minimum of Months | 0.00 | 0.00 | 29268839.52 | 15325714.17 | 2894.65 | 1730.63 | 0.01 | |
Maximum of Months | 0.00 | 0.00 | 0.663048E+10 | 0.370201E+10 | 17451.68 | 15850.09 | 0.89 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 9111572.95 | 2573627.78 | 2640.41 | 19-JAN-09:03 | 1468.00 | 0.01 |
February | 0.00 | 0.00 | 36580418.67 | 20076180.46 | 9308.76 | 20-FEB-09:02 | 9048.45 | 0.02 |
March | 0.00 | 0.00 | 42920641.72 | 24623906.10 | 3786.21 | 10-MAR-09:02 | 2989.37 | 0.02 |
April | 0.00 | 0.00 | 0.221858E+10 | 0.164160E+10 | 14298.66 | 20-APR-08:62 | 14298.66 | 0.31 |
May | 0.00 | 0.00 | 0.280307E+10 | 0.176907E+10 | 14555.62 | 23-MAY-15:02 | 13323.61 | 0.48 |
June | 0.00 | 0.00 | 0.436619E+10 | 0.251687E+10 | 15726.88 | 27-JUN-08:62 | 11962.07 | 0.70 |
July | 0.00 | 0.00 | 0.533014E+10 | 0.305281E+10 | 15238.34 | 25-JUL-15:02 | 13002.45 | 0.81 |
August | 0.00 | 0.00 | 0.489475E+10 | 0.266871E+10 | 15455.62 | 11-AUG-15:01 | 12357.88 | 0.84 |
September | 0.00 | 0.00 | 0.303582E+10 | 0.166491E+10 | 15108.36 | 02-SEP-08:62 | 12218.01 | 0.60 |
October | 0.00 | 0.00 | 0.437056E+09 | 0.250412E+09 | 13700.19 | 07-OCT-15:02 | 13700.19 | 0.11 |
November | 0.00 | 0.00 | 14554033.57 | 5069846.51 | 4560.61 | 11-NOV-09:02 | 3984.60 | 0.01 |
December | 0.00 | 0.00 | 1223460.61 | 481602.79 | 1850.75 | 11-DEC-09:05 | 835.35 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.231900E+11 | 0.136172E+11 | 0.33 | |||
Minimum of Months | 0.00 | 0.00 | 1223460.61 | 481602.79 | 1850.75 | 835.35 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.533014E+10 | 0.305281E+10 | 15726.88 | 14298.66 | 0.84 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 9907519.64 | 5915679.90 | 3686.22 | 25-JAN-16:01 | 3686.22 | 0.01 |
February | 0.00 | 0.00 | 64342783.93 | 59044578.05 | 4669.85 | 09-FEB-16:01 | 4669.85 | 0.01 |
March | 0.00 | 0.00 | 33232519.72 | 29251211.92 | 4623.00 | 20-MAR-18:02 | 4623.00 | 0.01 |
April | 0.00 | 0.00 | 0.894364E+09 | 0.714605E+09 | 4670.34 | 06-APR-18:01 | 4670.34 | 0.30 |
May | 0.00 | 0.00 | 0.103773E+10 | 0.722846E+09 | 4670.04 | 29-MAY-18:02 | 4670.04 | 0.46 |
June | 0.00 | 0.00 | 0.155390E+10 | 0.960143E+09 | 5271.68 | 27-JUN-08:62 | 3837.36 | 0.74 |
July | 0.00 | 0.00 | 0.195809E+10 | 0.120627E+10 | 5029.43 | 18-JUL-08:62 | 3894.66 | 0.81 |
August | 0.00 | 0.00 | 0.179425E+10 | 0.105276E+10 | 5138.51 | 11-AUG-15:01 | 4158.28 | 0.86 |
September | 0.00 | 0.00 | 0.125693E+10 | 0.750021E+09 | 4999.27 | 02-SEP-08:62 | 3818.87 | 0.67 |
October | 0.00 | 0.00 | 0.282028E+09 | 0.192192E+09 | 4669.02 | 07-OCT-15:02 | 4669.02 | 0.16 |
November | 0.00 | 0.00 | 13681357.36 | 9405639.54 | 4623.13 | 03-NOV-15:01 | 4623.13 | 0.01 |
December | 0.00 | 0.00 | 80784.45 | 65021.44 | 333.51 | 26-DEC-16:05 | 333.51 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.889854E+10 | 0.570251E+10 | 0.34 | |||
Minimum of Months | 0.00 | 0.00 | 80784.45 | 65021.44 | 333.51 | 333.51 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.195809E+10 | 0.120627E+10 | 5271.68 | 4670.34 | 0.86 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 1060553.34 | 476762.93 | 1438.13 | 19-JAN-16:01 | 1354.96 | 0.00 |
February | 0.00 | 0.00 | 13041292.02 | 10858633.35 | 3402.17 | 19-FEB-16:02 | 3402.17 | 0.00 |
March | 0.00 | 0.00 | 16727962.15 | 14704498.11 | 3981.05 | 20-MAR-18:02 | 3981.05 | 0.01 |
April | 0.00 | 0.00 | 0.572491E+09 | 0.456072E+09 | 4150.31 | 17-APR-15:02 | 4150.31 | 0.22 |
May | 0.00 | 0.00 | 0.812806E+09 | 0.581077E+09 | 4150.09 | 29-MAY-18:02 | 4150.09 | 0.38 |
June | 0.00 | 0.00 | 0.137083E+10 | 0.870226E+09 | 4678.84 | 27-JUN-08:62 | 3393.30 | 0.69 |
July | 0.00 | 0.00 | 0.169168E+10 | 0.105812E+10 | 4460.58 | 18-JUL-08:62 | 3442.46 | 0.77 |
August | 0.00 | 0.00 | 0.134067E+10 | 0.779053E+09 | 4518.44 | 11-AUG-15:01 | 3616.36 | 0.75 |
September | 0.00 | 0.00 | 0.718698E+09 | 0.416298E+09 | 4310.13 | 02-SEP-18:02 | 3695.48 | 0.48 |
October | 0.00 | 0.00 | 0.106560E+09 | 77854850.43 | 4148.92 | 07-OCT-15:02 | 4148.92 | 0.07 |
November | 0.00 | 0.00 | 1408423.27 | 707075.90 | 1699.14 | 10-NOV-16:02 | 1296.42 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.664598E+10 | 0.426545E+10 | 0.28 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.169168E+10 | 0.105812E+10 | 4678.84 | 4150.31 | 0.77 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL COOLING COIL
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.151551E+10 | 0.994676E+09 | 25972.16 | 01-JAN-16:01 | 25972.16 | 0.16 |
February | 0.00 | 0.00 | 0.187154E+10 | 0.150479E+10 | 25980.12 | 05-FEB-16:01 | 25980.12 | 0.14 |
March | 0.00 | 0.00 | 0.695490E+09 | 0.528520E+09 | 25974.45 | 20-MAR-15:01 | 25974.45 | 0.08 |
April | 0.00 | 0.00 | 0.687770E+10 | 0.537162E+10 | 25979.53 | 27-APR-18:02 | 25979.53 | 0.44 |
May | 0.00 | 0.00 | 0.587780E+10 | 0.343414E+10 | 25978.99 | 06-MAY-15:02 | 25978.99 | 0.61 |
June | 0.00 | 0.00 | 0.774384E+10 | 0.404928E+10 | 28636.45 | 26-JUN-18:02 | 23195.00 | 0.82 |
July | 0.00 | 0.00 | 0.100107E+11 | 0.546686E+10 | 27034.59 | 24-JUL-18:02 | 23943.85 | 0.84 |
August | 0.00 | 0.00 | 0.115311E+11 | 0.670179E+10 | 28673.92 | 11-AUG-15:01 | 23104.73 | 0.90 |
September | 0.00 | 0.00 | 0.111078E+11 | 0.720371E+10 | 27647.58 | 19-SEP-15:02 | 23591.63 | 0.85 |
October | 0.00 | 0.00 | 0.432570E+10 | 0.279127E+10 | 25978.39 | 07-OCT-18:02 | 25978.39 | 0.43 |
November | 0.00 | 0.00 | 0.124368E+10 | 0.834309E+09 | 25974.12 | 19-NOV-16:01 | 25974.12 | 0.14 |
December | 0.00 | 0.00 | 0.432071E+09 | 0.362869E+09 | 25539.83 | 18-DEC-16:02 | 25539.83 | 0.03 |
Annual Sum or Average | 0.00 | 0.00 | 0.632330E+11 | 0.392438E+11 | 0.45 | |||
Minimum of Months | 0.00 | 0.00 | 0.432071E+09 | 0.362869E+09 | 25539.83 | 23104.73 | 0.03 | |
Maximum of Months | 0.00 | 0.00 | 0.115311E+11 | 0.720371E+10 | 28673.92 | 25980.12 | 0.90 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 52811.01 | 181124.91 | 10-JAN-09:02 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 46879.00 | 124686.34 | 13-FEB-09:02 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 44692.09 | 115676.90 | 04-MAR-16:02 |
April | 0.00 | 0.00 | 01-APR-00:10 | 29565.75 | 86853.70 | 11-APR-10:35 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 29144.84 | 90019.11 | 05-MAY-10:35 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 24850.32 | 88889.83 | 06-JUN-10:35 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22537.95 | 88642.58 | 03-JUL-10:35 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 20968.71 | 84660.74 | 01-AUG-10:35 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21841.26 | 86469.58 | 08-SEP-10:40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 33712.49 | 102972.85 | 19-OCT-08:03 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 44221.10 | 119859.29 | 29-NOV-09:02 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 56475.49 | 147074.25 | 27-DEC-09:03 |
Annual Sum or Average | 0.00 | 35609.82 | ||||
Minimum of Months | 0.00 | 0.00 | 20968.71 | 84660.74 | ||
Maximum of Months | 0.00 | 0.00 | 56475.49 | 181124.91 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 5507.15 | 66236.67 | 21-JAN-16:03 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 6450.60 | 72503.24 | 09-FEB-16:03 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 6316.32 | 66091.29 | 20-MAR-18:02 | 0.00 | 0.00 | 01-MAR-00:03 |
April | 44412.29 | 480953.75 | 30-APR-18:03 | 0.00 | 0.00 | 01-APR-00:10 |
May | 45421.38 | 475015.75 | 22-MAY-15:03 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 87673.43 | 696306.66 | 25-JUN-18:20 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 122532.78 | 586470.04 | 23-JUL-18:03 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 135904.85 | 526326.30 | 14-AUG-18:03 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 93568.15 | 504083.82 | 11-SEP-18:03 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 22256.18 | 357903.45 | 07-OCT-15:02 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 6544.53 | 78007.89 | 03-NOV-15:03 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 1904.07 | 27364.55 | 25-DEC-09:02 | 0.00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 48443.00 | 0.00 | ||||
Minimum of Months | 1904.07 | 27364.55 | 0.00 | 0.00 | ||
Maximum of Months | 135904.85 | 696306.66 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 28107.74 | 57262.29 | 30-JAN-07:10 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 28290.00 | 57352.02 | 10-FEB-07:10 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 28129.52 | 57271.83 | 01-MAR-07:10 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27610.44 | 56427.23 | 03-APR-06:10 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 26917.24 | 55165.04 | 02-MAY-06:20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 26226.60 | 53659.01 | 01-JUN-06:20 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25687.17 | 52256.62 | 03-JUL-07:00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25519.24 | 51551.10 | 31-AUG-06:30 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 25693.35 | 52266.40 | 29-SEP-06:10 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26195.49 | 53631.83 | 31-OCT-06:10 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 26894.27 | 55137.63 | 30-NOV-08:00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 27591.49 | 56408.98 | 29-DEC-07:40 |
Annual Sum or Average | 0.00 | 26897.11 | ||||
Minimum of Months | 0.00 | 0.00 | 25519.24 | 51551.10 | ||
Maximum of Months | 0.00 | 0.00 | 28290.00 | 57352.02 |
Report: FanReportMonthly
For: FLR_3_DOAS FAN
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.587890E+10 | 0.89 | 2194.93 | 01-JAN-00:05 | 0.89 |
February | 0.530997E+10 | 0.89 | 2194.93 | 01-FEB-00:03 | 0.88 |
March | 0.587890E+10 | 0.89 | 2194.93 | 01-MAR-00:03 | 0.88 |
April | 0.568926E+10 | 0.89 | 2194.93 | 01-APR-00:10 | 0.89 |
May | 0.587890E+10 | 0.88 | 2194.93 | 01-MAY-00:10 | 0.88 |
June | 0.568926E+10 | 0.88 | 2194.93 | 01-JUN-00:10 | 0.88 |
July | 0.587890E+10 | 0.88 | 2194.93 | 01-JUL-00:10 | 0.88 |
August | 0.587890E+10 | 0.88 | 2194.93 | 01-AUG-00:10 | 0.88 |
September | 0.568926E+10 | 0.88 | 2194.93 | 01-SEP-00:10 | 0.88 |
October | 0.587890E+10 | 0.88 | 2194.93 | 01-OCT-00:10 | 0.88 |
November | 0.568926E+10 | 0.88 | 2194.93 | 01-NOV-00:10 | 0.89 |
December | 0.587890E+10 | 0.89 | 2194.93 | 01-DEC-00:03 | 0.88 |
Annual Sum or Average | 0.692193E+11 | 0.88 | |||
Minimum of Months | 0.530997E+10 | 0.88 | 2194.93 | 0.88 | |
Maximum of Months | 0.587890E+10 | 0.89 | 2194.93 | 0.89 |
Report: FanReportMonthly
For: VAV WITH REHEAT FAN
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.135338E+12 | 1.85 | 50529.57 | 01-JAN-00:05 | 1.85 |
February | 0.122241E+12 | 1.85 | 50529.57 | 01-FEB-00:03 | 1.85 |
March | 0.135338E+12 | 1.85 | 50529.57 | 01-MAR-00:03 | 1.85 |
April | 0.130972E+12 | 1.85 | 50529.57 | 01-APR-00:10 | 1.86 |
May | 0.135337E+12 | 1.85 | 50529.57 | 01-MAY-00:10 | 1.85 |
June | 0.130970E+12 | 1.84 | 50529.57 | 01-JUN-00:10 | 1.85 |
July | 0.135337E+12 | 1.84 | 50529.57 | 01-JUL-00:10 | 1.85 |
August | 0.135338E+12 | 1.84 | 50529.57 | 01-AUG-00:10 | 1.85 |
September | 0.130971E+12 | 1.85 | 50529.57 | 01-SEP-00:10 | 1.84 |
October | 0.135337E+12 | 1.85 | 50529.57 | 01-OCT-00:10 | 1.85 |
November | 0.130973E+12 | 1.85 | 50529.57 | 01-NOV-00:10 | 1.85 |
December | 0.135338E+12 | 1.85 | 50529.57 | 01-DEC-00:03 | 1.85 |
Annual Sum or Average | 0.159349E+13 | 1.85 | |||
Minimum of Months | 0.122241E+12 | 1.84 | 50529.57 | 1.84 | |
Maximum of Months | 0.135338E+12 | 1.85 | 50529.57 | 1.86 |
Report: FanReportMonthly
For: LAUNDRY_FLR_1 EXHAUST FAN
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.493775E+09 | 0.65 | 184.35 | 01-JAN-00:05 | 0.65 |
February | 0.445990E+09 | 0.65 | 184.35 | 01-FEB-00:03 | 0.65 |
March | 0.493775E+09 | 0.65 | 184.35 | 01-MAR-00:03 | 0.65 |
April | 0.477847E+09 | 0.65 | 184.35 | 01-APR-00:10 | 0.65 |
May | 0.493775E+09 | 0.65 | 184.35 | 01-MAY-00:10 | 0.65 |
June | 0.477847E+09 | 0.64 | 184.35 | 01-JUN-00:10 | 0.65 |
July | 0.493775E+09 | 0.64 | 184.35 | 01-JUL-00:10 | 0.64 |
August | 0.493775E+09 | 0.64 | 184.35 | 01-AUG-00:10 | 0.64 |
September | 0.477847E+09 | 0.64 | 184.35 | 01-SEP-00:10 | 0.64 |
October | 0.493775E+09 | 0.64 | 184.35 | 01-OCT-00:10 | 0.65 |
November | 0.477847E+09 | 0.65 | 184.35 | 01-NOV-00:10 | 0.65 |
December | 0.493775E+09 | 0.65 | 184.35 | 01-DEC-00:03 | 0.65 |
Annual Sum or Average | 0.581380E+10 | 0.65 | |||
Minimum of Months | 0.445990E+09 | 0.64 | 184.35 | 0.64 | |
Maximum of Months | 0.493775E+09 | 0.65 | 184.35 | 0.65 |
Report: FanReportMonthly
For: LOBBY_FLR_1 EXHAUST FAN
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: BANQUET_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: DINING_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN_FLR_6 EXHAUST FAN
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.279806E+10 | 0.46 | 1474.84 | 01-JAN-07:10 | 0.64 |
February | 0.252728E+10 | 0.46 | 1474.84 | 01-FEB-07:05 | 0.64 |
March | 0.279806E+10 | 0.46 | 1474.84 | 01-MAR-07:05 | 0.65 |
April | 0.270780E+10 | 0.46 | 1474.84 | 01-APR-06:10 | 0.65 |
May | 0.279806E+10 | 0.46 | 1474.84 | 01-MAY-06:05 | 0.65 |
June | 0.270780E+10 | 0.45 | 1474.84 | 01-JUN-06:05 | 0.64 |
July | 0.279806E+10 | 0.45 | 1474.84 | 01-JUL-06:10 | 0.64 |
August | 0.279806E+10 | 0.45 | 1474.84 | 01-AUG-06:05 | 0.64 |
September | 0.270780E+10 | 0.45 | 1474.84 | 01-SEP-06:05 | 0.64 |
October | 0.279806E+10 | 0.46 | 1474.84 | 01-OCT-06:10 | 0.64 |
November | 0.270780E+10 | 0.46 | 1474.84 | 01-NOV-06:05 | 0.64 |
December | 0.279806E+10 | 0.46 | 1474.84 | 01-DEC-07:05 | 0.65 |
Annual Sum or Average | 0.329449E+11 | 0.46 | |||
Minimum of Months | 0.252728E+10 | 0.45 | 1474.84 | 0.64 | |
Maximum of Months | 0.279806E+10 | 0.46 | 1474.84 | 0.65 |
Report: FanReportMonthly
For: ROOM_1_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.686875E+09 | 1.02 | 2107.83 | 01-JAN-09:02 | 1.40 |
February | 0.551645E+09 | 1.01 | 2107.83 | 01-FEB-09:02 | 1.39 |
March | 0.534991E+09 | 0.99 | 2107.83 | 01-MAR-09:02 | 1.40 |
April | 0.574812E+09 | 1.14 | 2107.83 | 01-APR-15:01 | 1.40 |
May | 0.591030E+09 | 1.12 | 2107.83 | 01-MAY-15:02 | 1.40 |
June | 0.678324E+09 | 1.17 | 2107.83 | 01-JUN-15:01 | 1.39 |
July | 0.821854E+09 | 1.21 | 2107.83 | 01-JUL-15:01 | 1.39 |
August | 0.755775E+09 | 1.23 | 2107.83 | 01-AUG-15:02 | 1.39 |
September | 0.615815E+09 | 1.19 | 2107.83 | 01-SEP-15:02 | 1.39 |
October | 0.453592E+09 | 1.05 | 2107.83 | 01-OCT-15:02 | 1.40 |
November | 0.571880E+09 | 1.01 | 2107.83 | 01-NOV-08:62 | 1.40 |
December | 0.874192E+09 | 1.09 | 2107.83 | 01-DEC-09:02 | 1.40 |
Annual Sum or Average | 0.771078E+10 | 1.10 | |||
Minimum of Months | 0.453592E+09 | 0.99 | 2107.83 | 1.39 | |
Maximum of Months | 0.874192E+09 | 1.23 | 2107.83 | 1.40 |
Report: FanReportMonthly
For: ROOM_2_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.760745E+09 | 1.06 | 1884.60 | 01-JAN-09:02 | 1.40 |
February | 0.597503E+09 | 1.00 | 1884.60 | 01-FEB-09:02 | 1.39 |
March | 0.542267E+09 | 1.00 | 1884.60 | 01-MAR-09:02 | 1.40 |
April | 0.455395E+09 | 1.05 | 1884.60 | 01-APR-15:01 | 1.40 |
May | 0.498527E+09 | 1.06 | 1884.60 | 01-MAY-15:02 | 1.40 |
June | 0.602547E+09 | 1.11 | 1884.60 | 01-JUN-15:01 | 1.39 |
July | 0.716699E+09 | 1.13 | 1884.60 | 01-JUL-15:01 | 1.39 |
August | 0.573652E+09 | 1.11 | 1884.60 | 01-AUG-15:02 | 1.39 |
September | 0.403828E+09 | 1.05 | 1884.60 | 01-SEP-15:02 | 1.39 |
October | 0.423510E+09 | 1.00 | 1884.60 | 01-OCT-15:02 | 1.40 |
November | 0.620410E+09 | 1.01 | 1884.60 | 01-NOV-08:62 | 1.40 |
December | 0.903388E+09 | 1.14 | 1884.60 | 01-DEC-09:02 | 1.40 |
Annual Sum or Average | 0.709847E+10 | 1.06 | |||
Minimum of Months | 0.403828E+09 | 1.00 | 1884.60 | 1.39 | |
Maximum of Months | 0.903388E+09 | 1.14 | 1884.60 | 1.40 |
Report: FanReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.637088E+09 | 0.22 | 3928.14 | 21-JAN-11:25 | 1.40 |
February | 0.682036E+09 | 0.27 | 3591.16 | 04-FEB-14:00 | 1.40 |
March | 56397748.29 | 0.05 | 1726.95 | 25-MAR-11:30 | 1.40 |
April | 0.332395E+10 | 0.86 | 5035.51 | 30-APR-12:30 | 1.40 |
May | 0.274609E+10 | 0.80 | 3760.98 | 23-MAY-13:10 | 1.39 |
June | 0.315642E+10 | 0.99 | 3747.41 | 13-JUN-13:20 | 1.39 |
July | 0.378074E+10 | 1.09 | 4324.70 | 22-JUL-13:30 | 1.40 |
August | 0.433260E+10 | 1.13 | 4601.33 | 20-AUG-13:00 | 1.40 |
September | 0.505645E+10 | 1.11 | 8541.75 | 25-SEP-13:30 | 1.40 |
October | 0.221315E+10 | 0.54 | 8084.70 | 03-OCT-12:50 | 1.40 |
November | 0.504873E+09 | 0.18 | 3792.54 | 11-NOV-13:30 | 1.40 |
December | 0.286190E+09 | 0.14 | 2262.57 | 17-DEC-04:40 | 1.40 |
Annual Sum or Average | 0.267760E+11 | 0.62 | |||
Minimum of Months | 56397748.29 | 0.05 | 1726.95 | 1.39 | |
Maximum of Months | 0.505645E+10 | 1.13 | 8541.75 | 1.40 |
Report: FanReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.198331E+10 | 0.99 | 9741.33 | 01-JAN-09:02 | 1.40 |
February | 0.155444E+10 | 0.99 | 9741.33 | 01-FEB-16:02 | 1.40 |
March | 0.183285E+10 | 0.99 | 9741.33 | 03-MAR-16:02 | 1.40 |
April | 0.305906E+10 | 0.99 | 9741.33 | 01-APR-08:62 | 1.40 |
May | 0.380199E+10 | 0.99 | 9741.33 | 01-MAY-08:62 | 1.40 |
June | 0.512419E+10 | 0.99 | 9741.33 | 01-JUN-08:62 | 1.40 |
July | 0.550248E+10 | 0.99 | 9741.33 | 01-JUL-08:62 | 1.39 |
August | 0.464409E+10 | 0.99 | 9741.33 | 01-AUG-08:62 | 1.39 |
September | 0.351380E+10 | 0.99 | 9741.33 | 01-SEP-15:02 | 1.39 |
October | 0.207581E+10 | 0.99 | 9741.33 | 01-OCT-08:62 | 1.40 |
November | 0.159507E+10 | 0.99 | 9741.33 | 06-NOV-16:02 | 1.40 |
December | 0.204453E+10 | 0.99 | 9741.33 | 01-DEC-16:02 | 1.40 |
Annual Sum or Average | 0.367316E+11 | 0.99 | |||
Minimum of Months | 0.155444E+10 | 0.99 | 9741.33 | 1.39 | |
Maximum of Months | 0.550248E+10 | 0.99 | 9741.33 | 1.40 |
Report: FanReportMonthly
For: ROOM_5_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.651541E+09 | 1.02 | 1914.04 | 01-JAN-16:01 | 1.40 |
February | 0.527540E+09 | 0.99 | 1914.04 | 01-FEB-09:02 | 1.39 |
March | 0.502582E+09 | 0.99 | 1914.04 | 01-MAR-09:02 | 1.40 |
April | 0.589341E+09 | 1.20 | 1914.04 | 01-APR-15:01 | 1.40 |
May | 0.574706E+09 | 1.19 | 1914.04 | 01-MAY-15:02 | 1.40 |
June | 0.620521E+09 | 1.21 | 1914.04 | 01-JUN-08:62 | 1.40 |
July | 0.739810E+09 | 1.26 | 1914.04 | 01-JUL-08:62 | 1.39 |
August | 0.767579E+09 | 1.27 | 1914.04 | 01-AUG-08:62 | 1.39 |
September | 0.655749E+09 | 1.26 | 1914.04 | 01-SEP-15:02 | 1.39 |
October | 0.438673E+09 | 1.06 | 1914.04 | 01-OCT-08:62 | 1.39 |
November | 0.542925E+09 | 1.00 | 1914.04 | 01-NOV-08:62 | 1.40 |
December | 0.798065E+09 | 1.08 | 1914.04 | 01-DEC-09:02 | 1.40 |
Annual Sum or Average | 0.740903E+10 | 1.13 | |||
Minimum of Months | 0.438673E+09 | 0.99 | 1914.04 | 1.39 | |
Maximum of Months | 0.798065E+09 | 1.27 | 1914.04 | 1.40 |
Report: FanReportMonthly
For: ROOM_6_FLR_3 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.717888E+09 | 1.07 | 1725.45 | 01-JAN-09:02 | 1.40 |
February | 0.582476E+09 | 1.00 | 1725.45 | 01-FEB-09:02 | 1.39 |
March | 0.510996E+09 | 0.99 | 1725.45 | 01-MAR-09:02 | 1.40 |
April | 0.454505E+09 | 1.08 | 1725.45 | 03-APR-08:62 | 1.40 |
May | 0.475709E+09 | 1.10 | 1725.45 | 01-MAY-15:02 | 1.40 |
June | 0.545709E+09 | 1.16 | 1725.45 | 01-JUN-08:62 | 1.40 |
July | 0.633057E+09 | 1.23 | 1725.45 | 01-JUL-08:62 | 1.39 |
August | 0.586702E+09 | 1.23 | 1725.45 | 01-AUG-08:62 | 1.39 |
September | 0.429556E+09 | 1.13 | 1725.45 | 01-SEP-15:02 | 1.39 |
October | 0.394940E+09 | 0.99 | 1725.45 | 01-OCT-08:62 | 1.39 |
November | 0.582053E+09 | 1.01 | 1725.45 | 01-NOV-08:62 | 1.40 |
December | 0.823606E+09 | 1.13 | 1725.45 | 01-DEC-09:02 | 1.40 |
Annual Sum or Average | 0.673720E+10 | 1.09 | |||
Minimum of Months | 0.394940E+09 | 0.99 | 1725.45 | 1.39 | |
Maximum of Months | 0.823606E+09 | 1.23 | 1725.45 | 1.40 |
Report: FanReportMonthly
For: ROOM_1_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.225261E+09 | 1.08 | 564.59 | 01-JAN-09:02 | 1.40 |
February | 0.179355E+09 | 1.04 | 564.59 | 01-FEB-09:02 | 1.39 |
March | 0.174125E+09 | 1.01 | 564.59 | 01-MAR-09:02 | 1.40 |
April | 0.176399E+09 | 1.16 | 564.59 | 01-APR-08:62 | 1.40 |
May | 0.176460E+09 | 1.15 | 564.59 | 01-MAY-15:02 | 1.40 |
June | 0.197068E+09 | 1.21 | 564.59 | 01-JUN-15:01 | 1.39 |
July | 0.240630E+09 | 1.24 | 564.59 | 01-JUL-15:01 | 1.39 |
August | 0.214961E+09 | 1.25 | 564.59 | 01-AUG-15:02 | 1.39 |
September | 0.173549E+09 | 1.21 | 564.59 | 01-SEP-15:02 | 1.39 |
October | 0.146486E+09 | 1.06 | 564.59 | 01-OCT-15:02 | 1.40 |
November | 0.188209E+09 | 1.03 | 564.59 | 01-NOV-08:62 | 1.40 |
December | 0.277884E+09 | 1.17 | 564.59 | 01-DEC-09:02 | 1.40 |
Annual Sum or Average | 0.237039E+10 | 1.14 | |||
Minimum of Months | 0.146486E+09 | 1.01 | 564.59 | 1.39 | |
Maximum of Months | 0.277884E+09 | 1.25 | 564.59 | 1.40 |
Report: FanReportMonthly
For: ROOM_2_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.248479E+09 | 1.16 | 501.34 | 01-JAN-09:02 | 1.40 |
February | 0.189787E+09 | 1.07 | 501.34 | 01-FEB-09:02 | 1.39 |
March | 0.174011E+09 | 1.01 | 501.34 | 01-MAR-09:02 | 1.40 |
April | 0.143661E+09 | 1.07 | 501.34 | 01-APR-08:62 | 1.40 |
May | 0.150769E+09 | 1.09 | 501.34 | 01-MAY-15:02 | 1.40 |
June | 0.176966E+09 | 1.16 | 501.34 | 01-JUN-15:01 | 1.39 |
July | 0.210731E+09 | 1.19 | 501.34 | 01-JUL-15:01 | 1.39 |
August | 0.165064E+09 | 1.17 | 501.34 | 01-AUG-15:02 | 1.39 |
September | 0.118133E+09 | 1.07 | 501.34 | 01-SEP-15:02 | 1.39 |
October | 0.137865E+09 | 1.00 | 501.34 | 01-OCT-15:02 | 1.40 |
November | 0.199396E+09 | 1.09 | 501.34 | 01-NOV-08:62 | 1.40 |
December | 0.283910E+09 | 1.29 | 501.34 | 01-DEC-09:02 | 1.40 |
Annual Sum or Average | 0.219877E+10 | 1.11 | |||
Minimum of Months | 0.118133E+09 | 1.00 | 501.34 | 1.39 | |
Maximum of Months | 0.283910E+09 | 1.29 | 501.34 | 1.40 |
Report: FanReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COIL FAN COILFAN_FAN
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.865065E+09 | 1.10 | 3128.09 | 01-JAN-16:01 | 1.40 |
February | 0.741443E+09 | 1.09 | 3128.09 | 01-FEB-09:02 | 1.39 |
March | 0.648256E+09 | 1.01 | 3128.09 | 01-MAR-09:02 | 1.40 |
April | 0.100433E+10 | 1.22 | 3128.09 | 01-APR-15:01 | 1.40 |
May | 0.859611E+09 | 1.18 | 3128.09 | 01-MAY-15:02 | 1.40 |
June | 0.921698E+09 | 1.21 | 3128.09 | 01-JUN-15:01 | 1.39 |
July | 0.113433E+10 | 1.23 | 3128.09 | 01-JUL-08:62 | 1.39 |
August | 0.127847E+10 | 1.25 | 3128.09 | 01-AUG-15:02 | 1.39 |
September | 0.128818E+10 | 1.26 | 3128.09 | 01-SEP-15:02 | 1.39 |
October | 0.787954E+09 | 1.13 | 3128.09 | 01-OCT-08:62 | 1.39 |
November | 0.688681E+09 | 1.07 | 3128.09 | 01-NOV-15:02 | 1.40 |
December | 0.101356E+10 | 1.08 | 3128.09 | 01-DEC-09:02 | 1.40 |
Annual Sum or Average | 0.112316E+11 | 1.15 | |||
Minimum of Months | 0.648256E+09 | 1.01 | 3128.09 | 1.39 | |
Maximum of Months | 0.128818E+10 | 1.26 | 3128.09 | 1.40 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.118418E+10 | 0.106576E+10 | 837.44 | 10-JAN-09:02 | 753.69 | 753.69 | 32.78 | 1.59 |
February | 0.949456E+09 | 0.854511E+09 | 757.57 | 26-FEB-16:02 | 681.81 | 681.81 | 38.01 | 1.26 |
March | 0.101404E+10 | 0.912640E+09 | 739.29 | 04-MAR-16:02 | 665.36 | 665.36 | 36.97 | 1.20 |
April | 0.631779E+09 | 0.568601E+09 | 640.97 | 10-APR-10:40 | 576.87 | 576.87 | 38.59 | 0.94 |
May | 0.612770E+09 | 0.551493E+09 | 631.46 | 18-MAY-10:40 | 568.32 | 568.32 | 36.90 | 0.91 |
June | 0.494033E+09 | 0.444629E+09 | 626.19 | 07-JUN-10:40 | 563.57 | 563.57 | 36.90 | 0.90 |
July | 0.461327E+09 | 0.415194E+09 | 586.74 | 03-JUL-10:40 | 528.07 | 528.07 | 36.39 | 0.82 |
August | 0.427984E+09 | 0.385186E+09 | 592.95 | 08-AUG-10:40 | 533.65 | 533.65 | 35.86 | 0.83 |
September | 0.435561E+09 | 0.392005E+09 | 614.31 | 08-SEP-10:40 | 552.88 | 552.88 | 36.40 | 0.88 |
October | 0.737352E+09 | 0.663617E+09 | 672.13 | 19-OCT-08:03 | 604.91 | 604.91 | 35.68 | 1.01 |
November | 0.961729E+09 | 0.865556E+09 | 762.45 | 26-NOV-16:02 | 686.21 | 686.21 | 38.01 | 1.28 |
December | 0.126690E+10 | 0.114021E+10 | 803.09 | 27-DEC-09:03 | 722.78 | 722.78 | 35.43 | 1.43 |
Annual Sum or Average | 0.917712E+10 | 0.825941E+10 | ||||||
Minimum of Months | 0.427984E+09 | 0.385186E+09 | 586.74 | 528.07 | 528.07 | 32.78 | 0.82 | |
Maximum of Months | 0.126690E+10 | 0.114021E+10 | 837.44 | 753.69 | 753.69 | 38.59 | 1.59 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.692987E+09 | 0.623688E+09 | 2241.16 | 21-JAN-16:03 | 2017.04 | 2017.04 | 6.73 | 4.30 |
February | 0.740198E+09 | 0.666178E+09 | 2426.81 | 20-FEB-09:02 | 2184.13 | 2184.13 | 6.73 | 4.80 |
March | 0.805722E+09 | 0.725149E+09 | 2479.27 | 31-MAR-15:01 | 2231.34 | 2231.34 | 6.73 | 4.95 |
April | 0.365244E+10 | 0.328719E+10 | 4649.55 | 30-APR-19:20 | 4184.60 | 4184.60 | 6.73 | 21.42 |
May | 0.385123E+10 | 0.346611E+10 | 4382.53 | 21-MAY-18:03 | 3944.28 | 3944.28 | 6.73 | 18.62 |
June | 0.522536E+10 | 0.470282E+10 | 5063.48 | 25-JUN-18:03 | 4557.13 | 4557.13 | 6.73 | 23.99 |
July | 0.650999E+10 | 0.585899E+10 | 5194.57 | 22-JUL-18:02 | 4675.12 | 4675.12 | 6.73 | 24.60 |
August | 0.699429E+10 | 0.629486E+10 | 4901.80 | 14-AUG-17:00 | 4411.62 | 4411.62 | 6.73 | 23.13 |
September | 0.553174E+10 | 0.497857E+10 | 4839.94 | 27-SEP-15:13 | 4355.95 | 4355.95 | 6.73 | 22.76 |
October | 0.226243E+10 | 0.203618E+10 | 3991.54 | 07-OCT-15:02 | 3592.39 | 3592.39 | 6.73 | 12.67 |
November | 0.777213E+09 | 0.699492E+09 | 2724.27 | 05-NOV-15:02 | 2451.84 | 2451.84 | 6.73 | 5.68 |
December | 0.230368E+09 | 0.207332E+09 | 1485.51 | 02-DEC-09:02 | 1336.96 | 1336.96 | 6.73 | 2.57 |
Annual Sum or Average | 0.372740E+11 | 0.335466E+11 | ||||||
Minimum of Months | 0.230368E+09 | 0.207332E+09 | 1485.51 | 1336.96 | 1336.96 | 6.73 | 2.57 | |
Maximum of Months | 0.699429E+10 | 0.629486E+10 | 5194.57 | 4675.12 | 4675.12 | 6.73 | 24.60 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.400961E+10 | 0.360865E+10 | 3681.07 | 01-JAN-09:00 | 3312.97 | 3312.97 | 6.76 | 25.80 |
February | 0.398167E+10 | 0.358350E+10 | 3681.07 | 01-FEB-00:03 | 3312.97 | 3312.97 | 6.74 | 25.80 |
March | 0.499106E+10 | 0.449195E+10 | 3681.07 | 01-MAR-06:10 | 3312.97 | 3312.97 | 6.75 | 25.80 |
April | 0.889476E+10 | 0.800528E+10 | 3681.07 | 01-APR-00:10 | 3312.97 | 3312.97 | 6.75 | 25.80 |
May | 0.926828E+10 | 0.834145E+10 | 3681.07 | 01-MAY-00:10 | 3312.97 | 3312.97 | 7.05 | 25.80 |
June | 0.948244E+10 | 0.853420E+10 | 3681.07 | 01-JUN-00:10 | 3312.97 | 3312.97 | 6.90 | 25.80 |
July | 0.985810E+10 | 0.887229E+10 | 3681.07 | 01-JUL-00:10 | 3312.97 | 3312.97 | 6.88 | 25.80 |
August | 0.985939E+10 | 0.887345E+10 | 3681.07 | 01-AUG-00:10 | 3312.97 | 3312.97 | 6.95 | 25.80 |
September | 0.948281E+10 | 0.853453E+10 | 3681.07 | 01-SEP-00:10 | 3312.97 | 3312.97 | 6.96 | 25.80 |
October | 0.776854E+10 | 0.699168E+10 | 3681.07 | 01-OCT-00:10 | 3312.97 | 3312.97 | 6.84 | 25.80 |
November | 0.482596E+10 | 0.434336E+10 | 3681.07 | 01-NOV-00:10 | 3312.97 | 3312.97 | 6.75 | 25.80 |
December | 0.242086E+10 | 0.217877E+10 | 3681.07 | 01-DEC-06:50 | 3312.97 | 3312.97 | 6.74 | 25.80 |
Annual Sum or Average | 0.848435E+11 | 0.763591E+11 | ||||||
Minimum of Months | 0.242086E+10 | 0.217877E+10 | 3681.07 | 3312.97 | 3312.97 | 6.74 | 25.80 | |
Maximum of Months | 0.985939E+10 | 0.887345E+10 | 3681.07 | 3312.97 | 3312.97 | 7.05 | 25.80 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.128314E+09 | 38494137.67 | 47.91 | 01-JAN-00:05 | 14.37 | 14.37 | 48.13 | 0.37 |
February | 0.115896E+09 | 34768898.54 | 47.91 | 01-FEB-00:03 | 14.37 | 14.37 | 48.79 | 0.37 |
March | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAR-00:03 | 14.37 | 14.37 | 48.79 | 0.37 |
April | 0.124175E+09 | 37252391.29 | 47.91 | 01-APR-00:10 | 14.37 | 14.37 | 51.15 | 0.37 |
May | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAY-00:10 | 14.37 | 14.37 | 51.58 | 0.37 |
June | 0.124175E+09 | 37252391.29 | 47.91 | 01-JUN-00:10 | 14.37 | 14.37 | 52.25 | 0.37 |
July | 0.128314E+09 | 38494137.67 | 47.91 | 01-JUL-00:10 | 14.37 | 14.37 | 52.44 | 0.37 |
August | 0.128314E+09 | 38494137.67 | 47.91 | 01-AUG-00:10 | 14.37 | 14.37 | 52.32 | 0.37 |
September | 0.124175E+09 | 37252391.29 | 47.91 | 01-SEP-00:10 | 14.37 | 14.37 | 52.38 | 0.37 |
October | 0.128314E+09 | 38494137.67 | 47.91 | 01-OCT-00:10 | 14.37 | 14.37 | 51.50 | 0.37 |
November | 0.124175E+09 | 37252391.29 | 47.91 | 01-NOV-00:10 | 14.37 | 14.37 | 52.26 | 0.37 |
December | 0.128314E+09 | 38494137.67 | 47.91 | 01-DEC-00:03 | 14.37 | 14.37 | 48.85 | 0.37 |
Annual Sum or Average | 0.151079E+10 | 0.453237E+09 | ||||||
Minimum of Months | 0.115896E+09 | 34768898.54 | 47.91 | 14.37 | 14.37 | 48.13 | 0.37 | |
Maximum of Months | 0.128314E+09 | 38494137.67 | 47.91 | 14.37 | 14.37 | 52.44 | 0.37 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 39.65 | 60.00 | 52811.01 | 181124.91 | 10-JAN-09:02 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 38.06 | 60.00 | 46879.00 | 124686.34 | 13-FEB-09:02 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 39.40 | 60.00 | 44692.09 | 115676.90 | 04-MAR-16:02 |
April | 0.00 | 0.00 | 01-APR-00:10 | 37.82 | 60.00 | 29565.75 | 86853.70 | 11-APR-10:35 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 28.39 | 60.00 | 29144.84 | 90019.11 | 05-MAY-10:35 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.94 | 60.00 | 24850.32 | 88889.83 | 06-JUN-10:35 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 30.55 | 60.00 | 22537.95 | 88642.58 | 03-JUL-10:35 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 28.88 | 60.00 | 20968.71 | 84660.74 | 01-AUG-10:35 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 28.93 | 60.00 | 21841.26 | 86469.58 | 08-SEP-10:40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 31.32 | 60.00 | 33712.49 | 102972.85 | 19-OCT-08:03 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 36.91 | 60.00 | 44221.10 | 119859.29 | 29-NOV-09:02 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 39.58 | 60.00 | 56475.49 | 147074.25 | 27-DEC-09:03 |
Annual Sum or Average | 0.00 | 35609.82 | ||||||
Minimum of Months | 0.00 | 0.00 | 28.39 | 60.00 | 20968.71 | 84660.74 | ||
Maximum of Months | 0.00 | 0.00 | 39.65 | 60.00 | 56475.49 | 181124.91 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 5507.15 | 66236.67 | 21-JAN-16:03 | 7.31 | 6.70 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 6450.60 | 72503.24 | 09-FEB-16:03 | 7.37 | 6.70 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 6316.32 | 66091.29 | 20-MAR-18:02 | 7.31 | 6.70 | 0.00 | 0.00 | 01-MAR-00:03 |
April | 44412.29 | 480953.75 | 30-APR-18:03 | 11.15 | 6.70 | 0.00 | 0.00 | 01-APR-00:10 |
May | 45421.38 | 475015.75 | 22-MAY-15:03 | 11.09 | 6.70 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 87673.43 | 696306.66 | 25-JUN-18:20 | 13.15 | 6.70 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 122532.78 | 586470.04 | 23-JUL-18:03 | 12.13 | 6.70 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 135904.85 | 526326.30 | 14-AUG-18:03 | 11.57 | 6.70 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 93568.15 | 504083.82 | 11-SEP-18:03 | 11.36 | 6.70 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 22256.18 | 357903.45 | 07-OCT-15:02 | 10.01 | 6.70 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 6544.53 | 78007.89 | 03-NOV-15:03 | 7.42 | 6.70 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 1904.07 | 27364.55 | 25-DEC-09:02 | 6.95 | 6.70 | 0.00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 48443.00 | 0.00 | ||||||
Minimum of Months | 1904.07 | 27364.55 | 6.95 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 135904.85 | 696306.66 | 13.15 | 6.70 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 48.13 | 59.70 | 28107.74 | 57262.29 | 30-JAN-07:10 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 48.79 | 59.67 | 28290.00 | 57352.02 | 10-FEB-07:10 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 48.79 | 59.19 | 28129.52 | 57271.83 | 01-MAR-07:10 |
April | 0.00 | 0.00 | 01-APR-00:10 | 51.15 | 58.43 | 27610.44 | 56427.23 | 03-APR-06:10 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 51.58 | 58.71 | 26917.24 | 55165.04 | 02-MAY-06:20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 52.25 | 59.60 | 26226.60 | 53659.01 | 01-JUN-06:20 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 52.44 | 59.63 | 25687.17 | 52256.62 | 03-JUL-07:00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 52.32 | 59.16 | 25519.24 | 51551.10 | 31-AUG-06:30 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 52.38 | 59.28 | 25693.35 | 52266.40 | 29-SEP-06:10 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 51.50 | 59.42 | 26195.49 | 53631.83 | 31-OCT-06:10 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 52.26 | 59.62 | 26894.27 | 55137.63 | 30-NOV-08:00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 48.85 | 59.57 | 27591.49 | 56408.98 | 29-DEC-07:40 |
Annual Sum or Average | 0.00 | 26897.11 | ||||||
Minimum of Months | 0.00 | 0.00 | 48.13 | 58.43 | 25519.24 | 51551.10 | ||
Maximum of Months | 0.00 | 0.00 | 52.44 | 59.70 | 28290.00 | 57352.02 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.119424E+12 | 0.00 | 6818783.35 | 0.135338E+12 | 0.00 | 0.00 |
February | 0.977830E+11 | 0.00 | 0.00 | 0.122241E+12 | 0.00 | 0.00 |
March | 0.107974E+12 | 0.00 | 4067563.16 | 0.135338E+12 | 0.00 | 0.00 |
April | 0.744082E+11 | 0.00 | 0.309439E+11 | 0.130972E+12 | 0.00 | 0.00 |
May | 0.766847E+11 | 0.00 | 0.333113E+11 | 0.135337E+12 | 0.00 | 0.00 |
June | 0.646058E+11 | 0.00 | 0.103271E+12 | 0.130970E+12 | 0.00 | 0.00 |
July | 0.605870E+11 | 0.00 | 0.177173E+12 | 0.135337E+12 | 0.00 | 0.00 |
August | 0.565020E+11 | 0.00 | 0.210060E+12 | 0.135338E+12 | 0.00 | 0.00 |
September | 0.563141E+11 | 0.00 | 0.113591E+12 | 0.130971E+12 | 0.00 | 0.00 |
October | 0.846351E+11 | 0.00 | 0.809054E+10 | 0.135337E+12 | 0.00 | 0.00 |
November | 0.100122E+12 | 0.00 | 0.223888E+09 | 0.130973E+12 | 0.00 | 0.00 |
December | 0.122500E+12 | 0.00 | 0.00 | 0.135338E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.102154E+13 | 0.00 | 0.676676E+12 | 0.159349E+13 | 0.00 | 0.00 |
Minimum of Months | 0.563141E+11 | 0.00 | 0.00 | 0.122241E+12 | 0.00 | 0.00 |
Maximum of Months | 0.122500E+12 | 0.00 | 0.210060E+12 | 0.135338E+12 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.445327E+09 | 0.00 | 0.00 | 0.587890E+10 | 0.00 | 0.00 |
February | 0.120929E+09 | 0.00 | 0.00 | 0.530997E+10 | 0.00 | 0.00 |
March | 3005469.02 | 0.00 | 0.00 | 0.587890E+10 | 0.00 | 0.00 |
April | 17644.25 | 0.00 | 0.246108E+10 | 0.568926E+10 | 0.00 | 0.00 |
May | 11118.50 | 0.00 | 0.246348E+10 | 0.587890E+10 | 0.00 | 0.00 |
June | 26777.63 | 0.00 | 0.833263E+10 | 0.568926E+10 | 0.00 | 0.00 |
July | 46328.27 | 0.00 | 0.147069E+11 | 0.587890E+10 | 0.00 | 0.00 |
August | 58125.16 | 0.00 | 0.178711E+11 | 0.587890E+10 | 0.00 | 0.00 |
September | 23299.16 | 0.00 | 0.919189E+10 | 0.568926E+10 | 0.00 | 0.00 |
October | 2014.16 | 0.00 | 0.434540E+09 | 0.587890E+10 | 0.00 | 0.00 |
November | 8384552.07 | 0.00 | 6967953.45 | 0.568926E+10 | 0.00 | 0.00 |
December | 0.230384E+09 | 0.00 | 0.00 | 0.587890E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.808216E+09 | 0.00 | 0.554687E+11 | 0.692193E+11 | 0.00 | 0.00 |
Minimum of Months | 2014.16 | 0.00 | 0.00 | 0.530997E+10 | 0.00 | 0.00 |
Maximum of Months | 0.445327E+09 | 0.00 | 0.178711E+11 | 0.587890E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.135338E+12 | 6818783.35 | 0.119424E+12 | 0.766710E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.122241E+12 | 0.00 | 0.977830E+11 | 0.695434E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.135338E+12 | 4067563.16 | 0.107974E+12 | 0.637306E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.130972E+12 | 0.309439E+11 | 0.744082E+11 | 0.401432E+12 | 0.474939E+09 | 0.00 | 0.00 | 0.00 |
May | 0.135337E+12 | 0.333113E+11 | 0.766847E+11 | 0.331592E+12 | 0.255735E+09 | 0.00 | 0.00 | 0.00 |
June | 0.130970E+12 | 0.103271E+12 | 0.646058E+11 | 0.127765E+12 | 0.485386E+10 | 0.00 | 0.00 | 0.00 |
July | 0.135337E+12 | 0.177173E+12 | 0.605870E+11 | 0.707958E+11 | 0.717496E+10 | 0.00 | 0.00 | 0.00 |
August | 0.135338E+12 | 0.210060E+12 | 0.565020E+11 | 0.466020E+11 | 0.160124E+10 | 0.00 | 0.00 | 0.00 |
September | 0.130971E+12 | 0.113591E+12 | 0.563141E+11 | 0.133973E+12 | 0.311521E+09 | 0.00 | 0.00 | 0.00 |
October | 0.135337E+12 | 0.809054E+10 | 0.846351E+11 | 0.367665E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.130973E+12 | 0.223888E+09 | 0.100122E+12 | 0.557551E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.135338E+12 | 0.00 | 0.122500E+12 | 0.782085E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.159349E+13 | 0.676676E+12 | 0.102154E+13 | 0.491891E+13 | 0.146723E+11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.122241E+12 | 0.00 | 0.563141E+11 | 0.466020E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.135338E+12 | 0.210060E+12 | 0.122500E+12 | 0.782085E+12 | 0.717496E+10 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.587890E+10 | 0.00 | 0.445327E+09 | 0.793321E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.530997E+10 | 0.00 | 0.120929E+09 | 0.716573E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.587890E+10 | 0.00 | 3005469.02 | 0.673759E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.568926E+10 | 0.246108E+10 | 17644.25 | 0.449408E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.587890E+10 | 0.246348E+10 | 11118.50 | 0.380947E+11 | 13945159.25 | 0.00 | 0.00 | 0.00 |
June | 0.568926E+10 | 0.833263E+10 | 26777.63 | 0.165152E+11 | 0.342164E+09 | 0.00 | 0.00 | 0.00 |
July | 0.587890E+10 | 0.147069E+11 | 46328.27 | 0.964576E+10 | 0.571837E+09 | 0.00 | 0.00 | 0.00 |
August | 0.587890E+10 | 0.178711E+11 | 58125.16 | 0.675595E+10 | 78418695.79 | 0.00 | 0.00 | 0.00 |
September | 0.568926E+10 | 0.919189E+10 | 23299.16 | 0.168176E+11 | 55694609.05 | 0.00 | 0.00 | 0.00 |
October | 0.587890E+10 | 0.434540E+09 | 2014.16 | 0.415926E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.568926E+10 | 6967953.45 | 8384552.07 | 0.593737E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.587890E+10 | 0.00 | 0.230384E+09 | 0.810898E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.692193E+11 | 0.554687E+11 | 0.808216E+09 | 0.533192E+12 | 0.106206E+10 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.530997E+10 | 0.00 | 2014.16 | 0.675595E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.587890E+10 | 0.178711E+11 | 0.445327E+09 | 0.810898E+11 | 0.571837E+09 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV WITH REHEAT
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.135338E+12 | 0.119424E+12 | 6818783.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.122241E+12 | 0.977830E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.135338E+12 | 0.107974E+12 | 4067563.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.130972E+12 | 0.744082E+11 | 0.309439E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.135337E+12 | 0.766847E+11 | 0.333113E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.130970E+12 | 0.646058E+11 | 0.103271E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.135337E+12 | 0.605870E+11 | 0.177173E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.135338E+12 | 0.565020E+11 | 0.210060E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.130971E+12 | 0.563141E+11 | 0.113591E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.135337E+12 | 0.846351E+11 | 0.809054E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.130973E+12 | 0.100122E+12 | 0.223888E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.135338E+12 | 0.122500E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.159349E+13 | 0.102154E+13 | 0.676676E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.122241E+12 | 0.563141E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.135338E+12 | 0.122500E+12 | 0.210060E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: FLR_3_DOAS
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.587890E+10 | 0.445327E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.530997E+10 | 0.120929E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.587890E+10 | 3005469.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.568926E+10 | 17644.25 | 0.246108E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.587890E+10 | 11118.50 | 0.246348E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.568926E+10 | 26777.63 | 0.833263E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.587890E+10 | 46328.27 | 0.147069E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.587890E+10 | 58125.16 | 0.178711E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.568926E+10 | 23299.16 | 0.919189E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.587890E+10 | 2014.16 | 0.434540E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.568926E+10 | 8384552.07 | 6967953.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.587890E+10 | 0.230384E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.692193E+11 | 0.808216E+09 | 0.554687E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.530997E+10 | 2014.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.587890E+10 | 0.445327E+09 | 0.178711E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.700418E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.85 |
February | 0.628221E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.86 |
March | 0.699146E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.85 |
April | 0.658817E+11 | 0.00 | 0.00 | 0.00 | 9090229.39 | 53276.64 | 0.00 | 0.00 | 1.86 |
May | 0.681840E+11 | 0.00 | 0.00 | 0.00 | 9623476.77 | 0.00 | 0.00 | 0.00 | 1.85 |
June | 0.597148E+11 | 0.00 | 357642.44 | 0.00 | 0.364356E+09 | 0.00 | 0.00 | 6049.63 | 1.86 |
July | 0.543777E+11 | 0.00 | 0.00 | 0.00 | 0.352539E+09 | 0.00 | 0.00 | 0.00 | 1.86 |
August | 0.505511E+11 | 0.00 | 0.00 | 0.00 | 99911815.45 | 0.00 | 0.00 | 0.00 | 1.86 |
September | 0.577099E+11 | 0.00 | 0.00 | 0.00 | 21118657.50 | 0.00 | 0.00 | 0.00 | 1.86 |
October | 0.695927E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.86 |
November | 0.673714E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.85 |
December | 0.692839E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.86 |
Annual Sum or Average | 0.765446E+12 | 0.00 | 357642.44 | 0.00 | 0.856639E+09 | 53276.64 | 0.00 | 6049.63 | 1.86 |
Minimum of Months | 0.505511E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.85 |
Maximum of Months | 0.700418E+11 | 0.00 | 357642.44 | 0.00 | 0.364356E+09 | 53276.64 | 0.00 | 6049.63 | 1.86 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.891042E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.450465E+10 | 0.00 | 0.00 | 6.43 |
February | 0.910874E+10 | 0.00 | 0.00 | 4872.19 | 0.00 | 0.288802E+10 | 35529408.13 | 0.00 | 6.47 |
March | 0.109041E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.248665E+10 | 0.00 | 0.00 | 6.44 |
April | 0.124280E+11 | 0.00 | 0.00 | 10070.72 | 1741048.43 | 0.139554E+09 | 50787651.05 | 0.00 | 6.45 |
May | 0.130593E+11 | 0.00 | 0.00 | 0.00 | 1843181.11 | 0.00 | 0.00 | 0.00 | 6.44 |
June | 0.114372E+11 | 0.00 | 0.00 | 0.00 | 69854591.59 | 0.00 | 0.00 | 0.00 | 6.47 |
July | 0.104149E+11 | 0.00 | 0.00 | 0.00 | 67521744.97 | 0.00 | 0.00 | 0.00 | 6.46 |
August | 0.967498E+10 | 403040.08 | 0.00 | 4337.45 | 18733034.65 | 0.00 | 7059503.83 | 0.00 | 6.47 |
September | 0.108526E+11 | 990774.79 | 0.00 | 176960.26 | 3054074.23 | 0.00 | 0.200401E+09 | 0.00 | 6.47 |
October | 0.130350E+11 | 0.00 | 0.00 | 27867.57 | 0.00 | 0.152338E+09 | 0.141699E+09 | 0.00 | 6.47 |
November | 0.104591E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.244453E+10 | 0.00 | 0.00 | 6.42 |
December | 0.564145E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.762847E+10 | 0.00 | 0.00 | 6.47 |
Annual Sum or Average | 0.125926E+12 | 1393814.87 | 0.00 | 224108.19 | 0.162748E+09 | 0.202442E+11 | 0.435476E+09 | 0.00 | 6.45 |
Minimum of Months | 0.564145E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.42 |
Maximum of Months | 0.130593E+11 | 990774.79 | 0.00 | 176960.26 | 69854591.59 | 0.762847E+10 | 0.200401E+09 | 0.00 | 6.47 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.670810E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.78 |
February | 0.601665E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.79 |
March | 0.669592E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.78 |
April | 0.630968E+10 | 0.00 | 0.00 | 0.00 | 870597.37 | 0.00 | 0.00 | 0.00 | 2.79 |
May | 0.653018E+10 | 0.00 | 0.00 | 0.00 | 921668.00 | 0.00 | 0.00 | 0.00 | 2.78 |
June | 0.571906E+10 | 0.00 | 0.00 | 0.00 | 34930231.07 | 0.00 | 0.00 | 0.00 | 2.79 |
July | 0.520791E+10 | 0.00 | 0.00 | 0.00 | 33763709.73 | 0.00 | 0.00 | 0.00 | 2.79 |
August | 0.484143E+10 | 0.00 | 0.00 | 0.00 | 9568841.46 | 0.00 | 0.00 | 0.00 | 2.79 |
September | 0.552704E+10 | 0.00 | 0.00 | 0.00 | 2022594.47 | 0.00 | 0.00 | 0.00 | 2.80 |
October | 0.666509E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.79 |
November | 0.645235E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.77 |
December | 0.663552E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.80 |
Annual Sum or Average | 0.733089E+11 | 0.00 | 0.00 | 0.00 | 82077642.11 | 0.00 | 0.00 | 0.00 | 2.79 |
Minimum of Months | 0.484143E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.77 |
Maximum of Months | 0.670810E+10 | 0.00 | 0.00 | 0.00 | 34930231.07 | 0.00 | 0.00 | 0.00 | 2.80 |
Report: MechanicalVentilationLoadsMonthly
For: MECH_FLR_1
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.601085E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.283769E+09 | 0.00 | 0.00 | 1.23 |
February | 0.562391E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21879456.79 | 0.00 | 0.00 | 1.24 |
March | 0.628319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.23 |
April | 0.592076E+10 | 0.00 | 0.00 | 0.00 | 816934.21 | 0.00 | 0.00 | 0.00 | 1.24 |
May | 0.612766E+10 | 0.00 | 0.00 | 0.00 | 864856.87 | 0.00 | 0.00 | 0.00 | 1.23 |
June | 0.536654E+10 | 0.00 | 0.00 | 0.00 | 32777149.98 | 0.00 | 0.00 | 0.00 | 1.24 |
July | 0.488689E+10 | 0.00 | 0.00 | 0.00 | 31682532.40 | 0.00 | 0.00 | 0.00 | 1.24 |
August | 0.454300E+10 | 0.00 | 0.00 | 0.00 | 8979023.10 | 0.00 | 0.00 | 0.00 | 1.24 |
September | 0.518636E+10 | 0.00 | 0.00 | 0.00 | 1897922.81 | 0.00 | 0.00 | 0.00 | 1.24 |
October | 0.625426E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.24 |
November | 0.604735E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7285286.66 | 0.00 | 0.00 | 1.23 |
December | 0.607117E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155332E+09 | 0.00 | 0.00 | 1.24 |
Annual Sum or Average | 0.683219E+11 | 0.00 | 0.00 | 0.00 | 77018419.37 | 0.468265E+09 | 0.00 | 0.00 | 1.24 |
Minimum of Months | 0.454300E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.23 |
Maximum of Months | 0.628319E+10 | 0.00 | 0.00 | 0.00 | 32777149.98 | 0.283769E+09 | 0.00 | 0.00 | 1.24 |
Report: MechanicalVentilationLoadsMonthly
For: STORAGE_FLR_1
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.185328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123744E+10 | 0.00 | 0.00 | 1.05 |
February | 0.179810E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.974038E+09 | 0.00 | 0.00 | 1.05 |
March | 0.276307E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.322028E+09 | 0.00 | 0.00 | 1.05 |
April | 0.290715E+10 | 0.00 | 0.00 | 0.00 | 401122.01 | 0.00 | 0.00 | 0.00 | 1.05 |
May | 0.300874E+10 | 0.00 | 0.00 | 0.00 | 424652.47 | 0.00 | 0.00 | 0.00 | 1.05 |
June | 0.263502E+10 | 0.00 | 0.00 | 0.00 | 16093874.00 | 0.00 | 0.00 | 0.00 | 1.05 |
July | 0.239951E+10 | 0.00 | 0.00 | 0.00 | 15556406.97 | 0.00 | 0.00 | 0.00 | 1.05 |
August | 0.223066E+10 | 0.00 | 0.00 | 0.00 | 4408780.71 | 0.00 | 0.00 | 0.00 | 1.05 |
September | 0.254655E+10 | 0.00 | 0.00 | 0.00 | 931897.09 | 0.00 | 0.00 | 0.00 | 1.06 |
October | 0.307090E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.05 |
November | 0.248166E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.491215E+09 | 0.00 | 0.00 | 1.05 |
December | 0.122164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183563E+10 | 0.00 | 0.00 | 1.06 |
Annual Sum or Average | 0.289163E+11 | 0.00 | 0.00 | 0.00 | 37816733.24 | 0.486035E+10 | 0.00 | 0.00 | 1.05 |
Minimum of Months | 0.122164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.05 |
Maximum of Months | 0.307090E+10 | 0.00 | 0.00 | 0.00 | 16093874.00 | 0.183563E+10 | 0.00 | 0.00 | 1.06 |
Report: MechanicalVentilationLoadsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.179042E+10 | 0.00 | 0.00 | 63374050.32 | 0.00 | 0.00 | 0.908899E+11 | 0.00 | 38.26 |
February | 0.125076E+10 | 0.00 | 0.00 | 57482686.19 | 0.00 | 0.00 | 0.818759E+11 | 0.00 | 38.47 |
March | 0.107275E+10 | 0.00 | 0.00 | 63756092.31 | 0.00 | 0.00 | 0.914428E+11 | 0.00 | 38.31 |
April | 0.172908E+10 | 11506129.63 | 0.00 | 63111295.77 | 526532.62 | 0.00 | 0.854427E+11 | 0.00 | 38.38 |
May | 0.166456E+10 | 12274803.99 | 0.00 | 65733630.28 | 463713.44 | 0.00 | 0.885518E+11 | 0.00 | 38.28 |
June | 0.154547E+10 | 0.454504E+09 | 0.00 | 62434395.01 | 28272363.05 | 0.00 | 0.774582E+11 | 0.00 | 38.46 |
July | 0.160272E+10 | 0.438090E+09 | 0.00 | 64564072.16 | 28563594.84 | 0.00 | 0.703267E+11 | 0.00 | 38.42 |
August | 0.140899E+10 | 0.127028E+09 | 0.00 | 66872459.87 | 5224391.93 | 0.00 | 0.654558E+11 | 0.00 | 38.47 |
September | 0.137564E+10 | 27189651.24 | 0.00 | 65015329.42 | 764942.84 | 0.00 | 0.749730E+11 | 0.00 | 38.49 |
October | 0.111591E+10 | 0.00 | 0.00 | 64887678.93 | 0.00 | 0.00 | 0.909694E+11 | 0.00 | 38.47 |
November | 0.131342E+10 | 0.00 | 0.00 | 62062287.56 | 0.00 | 0.00 | 0.878337E+11 | 0.00 | 38.20 |
December | 0.201360E+10 | 0.00 | 0.00 | 63081604.07 | 0.00 | 0.00 | 0.896615E+11 | 0.00 | 38.51 |
Annual Sum or Average | 0.178833E+11 | 0.107059E+10 | 0.00 | 0.762376E+09 | 63815538.71 | 0.00 | 0.994881E+12 | 0.00 | 38.39 |
Minimum of Months | 0.107275E+10 | 0.00 | 0.00 | 57482686.19 | 0.00 | 0.00 | 0.654558E+11 | 0.00 | 38.20 |
Maximum of Months | 0.201360E+10 | 0.454504E+09 | 0.00 | 66872459.87 | 28563594.84 | 0.00 | 0.914428E+11 | 0.00 | 38.51 |
Report: MechanicalVentilationLoadsMonthly
For: CAFE_FLR_1
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.525029E+11 | 0.00 | 0.00 | 16011.40 | 0.00 | 0.219377E+09 | 0.156315E+09 | 0.00 | 9.01 |
February | 0.469707E+11 | 0.00 | 0.00 | 82615.13 | 0.00 | 21224036.76 | 0.436116E+09 | 0.00 | 9.06 |
March | 0.527782E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 4439413.77 | 0.00 | 0.00 | 9.02 |
April | 0.489022E+11 | 2936677.87 | 0.00 | 180364.72 | 3926071.03 | 0.00 | 0.835634E+09 | 0.00 | 9.04 |
May | 0.514761E+11 | 0.00 | 0.00 | 0.00 | 7265328.71 | 0.00 | 0.00 | 0.00 | 9.01 |
June | 0.450822E+11 | 0.00 | 0.00 | 0.00 | 0.275348E+09 | 0.00 | 0.00 | 0.00 | 9.06 |
July | 0.410330E+11 | 20606986.12 | 0.00 | 152.72 | 0.245546E+09 | 0.00 | 19941096.53 | 0.00 | 9.05 |
August | 0.379839E+11 | 16066842.19 | 0.00 | 97899.04 | 59362464.51 | 0.00 | 0.180006E+09 | 0.00 | 9.06 |
September | 0.419785E+11 | 3938101.57 | 0.00 | 948988.86 | 12005615.26 | 0.00 | 0.158919E+10 | 0.00 | 9.06 |
October | 0.515440E+11 | 0.00 | 0.00 | 220766.58 | 0.00 | 0.00 | 0.995369E+09 | 0.00 | 9.06 |
November | 0.506530E+11 | 0.00 | 0.00 | 9202.91 | 0.00 | 58673829.08 | 0.150952E+09 | 0.00 | 8.99 |
December | 0.516915E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.614995E+09 | 0.00 | 0.00 | 9.07 |
Annual Sum or Average | 0.572596E+12 | 43548607.75 | 0.00 | 1556001.35 | 0.603453E+09 | 0.918709E+09 | 0.436352E+10 | 0.00 | 9.04 |
Minimum of Months | 0.379839E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.99 |
Maximum of Months | 0.527782E+11 | 20606986.12 | 0.00 | 948988.86 | 0.275348E+09 | 0.614995E+09 | 0.158919E+10 | 0.00 | 9.07 |
Report: MechanicalVentilationLoadsMonthly
For: LOBBY_FLR_1
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.145902E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.59 |
February | 0.130863E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.61 |
March | 0.145637E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.59 |
April | 0.137236E+12 | 0.00 | 0.00 | 0.00 | 18935585.57 | 0.00 | 0.00 | 0.00 | 3.60 |
May | 0.142032E+12 | 0.00 | 0.00 | 0.00 | 20046377.27 | 0.00 | 0.00 | 0.00 | 3.59 |
June | 0.124390E+12 | 0.00 | 0.00 | 0.00 | 0.759736E+09 | 0.00 | 0.00 | 0.00 | 3.61 |
July | 0.113273E+12 | 0.00 | 0.00 | 0.00 | 0.734364E+09 | 0.00 | 0.00 | 0.00 | 3.61 |
August | 0.105302E+12 | 0.00 | 0.00 | 0.00 | 0.208123E+09 | 0.00 | 0.00 | 0.00 | 3.61 |
September | 0.120214E+12 | 0.00 | 0.00 | 0.00 | 43991645.19 | 0.00 | 0.00 | 0.00 | 3.61 |
October | 0.144966E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.61 |
November | 0.140339E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.58 |
December | 0.144323E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.61 |
Annual Sum or Average | 0.159448E+13 | 0.00 | 0.00 | 0.00 | 0.178520E+10 | 0.00 | 0.00 | 0.00 | 3.60 |
Minimum of Months | 0.105302E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.58 |
Maximum of Months | 0.145902E+12 | 0.00 | 0.00 | 0.00 | 0.759736E+09 | 0.00 | 0.00 | 0.00 | 3.61 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_3
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.420974E+09 | 0.00 | 0.00 | 400268.10 | 0.00 | 0.114437E+10 | 84133594.62 | 0.00 | 0.47 |
February | 0.387120E+09 | 0.00 | 0.00 | 1144435.61 | 0.00 | 0.945472E+09 | 0.175599E+09 | 0.00 | 0.47 |
March | 0.460462E+09 | 0.00 | 0.00 | 658331.81 | 0.00 | 0.101065E+10 | 0.180131E+09 | 0.00 | 0.47 |
April | 0.296418E+09 | 0.00 | 0.00 | 9494474.63 | 102828.01 | 0.374554E+09 | 0.100749E+10 | 0.00 | 0.47 |
May | 0.317217E+09 | 242828.13 | 0.00 | 10672420.69 | 0.00 | 0.277805E+09 | 0.111675E+10 | 0.00 | 0.47 |
June | 0.209937E+09 | 13298488.67 | 0.00 | 13136120.22 | 229585.62 | 25118211.85 | 0.121393E+10 | 0.00 | 0.47 |
July | 0.167889E+09 | 9055703.11 | 2189.95 | 15198931.84 | 614468.58 | 37074417.37 | 0.109040E+10 | 2201.37 | 0.47 |
August | 0.106764E+09 | 6183879.28 | 0.00 | 14965937.29 | 413628.23 | 1784607.60 | 0.110641E+10 | 0.00 | 0.47 |
September | 0.195213E+09 | 4300203.21 | 0.00 | 11445444.93 | 50701.70 | 94707703.22 | 0.114423E+10 | 0.00 | 0.47 |
October | 0.395706E+09 | 0.00 | 0.00 | 3638592.73 | 0.00 | 0.716105E+09 | 0.617318E+09 | 0.00 | 0.47 |
November | 0.425483E+09 | 0.00 | 0.00 | 448980.26 | 0.00 | 0.107068E+10 | 0.119146E+09 | 0.00 | 0.47 |
December | 0.336819E+09 | 0.00 | 0.00 | 22166.33 | 0.00 | 0.115444E+10 | 8286891.75 | 0.00 | 0.47 |
Annual Sum or Average | 0.372000E+10 | 33081102.40 | 2189.95 | 81226104.44 | 1411212.13 | 0.685276E+10 | 0.786382E+10 | 2201.37 | 0.47 |
Minimum of Months | 0.106764E+09 | 0.00 | 0.00 | 22166.33 | 0.00 | 1784607.60 | 8286891.75 | 0.00 | 0.47 |
Maximum of Months | 0.460462E+09 | 13298488.67 | 2189.95 | 15198931.84 | 614468.58 | 0.115444E+10 | 0.121393E+10 | 2201.37 | 0.47 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_3
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.394377E+09 | 0.00 | 0.00 | 73501.08 | 0.00 | 0.124186E+10 | 13376032.43 | 0.00 | 0.47 |
February | 0.420245E+09 | 0.00 | 0.00 | 367254.36 | 0.00 | 0.103538E+10 | 53163244.81 | 0.00 | 0.47 |
March | 0.461701E+09 | 0.00 | 0.00 | 381280.55 | 0.00 | 0.107681E+10 | 0.112809E+09 | 0.00 | 0.47 |
April | 0.416152E+09 | 0.00 | 0.00 | 6667451.46 | 102815.96 | 0.493560E+09 | 0.771376E+09 | 0.00 | 0.47 |
May | 0.406651E+09 | 242799.68 | 0.00 | 8864222.21 | 0.00 | 0.329058E+09 | 0.977665E+09 | 0.00 | 0.47 |
June | 0.282108E+09 | 13259484.74 | 0.00 | 12003472.28 | 267004.54 | 25811733.64 | 0.114203E+10 | 0.00 | 0.47 |
July | 0.231096E+09 | 8845676.24 | 1514.28 | 13641900.32 | 823362.44 | 42282950.88 | 0.102339E+10 | 2876.53 | 0.47 |
August | 0.174736E+09 | 4729655.24 | 0.00 | 11981296.40 | 1867079.28 | 2440497.43 | 0.104062E+10 | 0.00 | 0.47 |
September | 0.303005E+09 | 4109350.54 | 0.00 | 7342590.58 | 241044.59 | 0.172698E+09 | 0.962380E+09 | 0.00 | 0.47 |
October | 0.476114E+09 | 0.00 | 0.00 | 1708817.51 | 0.00 | 0.925422E+09 | 0.329320E+09 | 0.00 | 0.47 |
November | 0.427656E+09 | 0.00 | 0.00 | 114705.35 | 0.00 | 0.116152E+10 | 26284762.65 | 0.00 | 0.47 |
December | 0.300714E+09 | 0.00 | 0.00 | 5491.64 | 0.00 | 0.119736E+10 | 1311687.02 | 0.00 | 0.47 |
Annual Sum or Average | 0.429455E+10 | 31186966.44 | 1514.28 | 63151983.75 | 3301306.81 | 0.770420E+10 | 0.645373E+10 | 2876.53 | 0.47 |
Minimum of Months | 0.174736E+09 | 0.00 | 0.00 | 5491.64 | 0.00 | 2440497.43 | 1311687.02 | 0.00 | 0.47 |
Maximum of Months | 0.476114E+09 | 13259484.74 | 1514.28 | 13641900.32 | 1867079.28 | 0.124186E+10 | 0.114203E+10 | 2876.53 | 0.47 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.177363E+11 | 0.00 | 0.00 | 17303730.59 | 0.00 | 0.00 | 0.461725E+10 | 0.00 | 0.53 |
February | 0.151128E+11 | 0.00 | 0.00 | 18866992.44 | 0.00 | 0.00 | 0.533360E+10 | 0.00 | 0.54 |
March | 0.204923E+11 | 0.00 | 0.00 | 2832414.74 | 0.00 | 0.00 | 0.190311E+10 | 0.00 | 0.54 |
April | 0.747969E+10 | 1394255.52 | 0.00 | 89805666.49 | 0.00 | 0.00 | 0.153176E+11 | 0.00 | 0.54 |
May | 0.805206E+10 | 3292531.65 | 0.00 | 75217431.75 | 0.00 | 0.00 | 0.152275E+11 | 0.00 | 0.54 |
June | 0.426935E+10 | 0.183429E+09 | 0.00 | 85512053.41 | 0.00 | 0.00 | 0.154702E+11 | 0.00 | 0.54 |
July | 0.291922E+10 | 0.131178E+09 | 0.00 | 97865355.70 | 0.00 | 0.00 | 0.147530E+11 | 0.00 | 0.54 |
August | 0.160477E+10 | 89456284.70 | 0.00 | 0.120074E+09 | 0.00 | 0.00 | 0.149518E+11 | 0.00 | 0.54 |
September | 0.264711E+10 | 58994368.23 | 0.00 | 0.129853E+09 | 0.00 | 0.00 | 0.168240E+11 | 0.00 | 0.54 |
October | 0.124251E+11 | 0.00 | 0.00 | 57645857.82 | 0.00 | 0.00 | 0.110121E+11 | 0.00 | 0.54 |
November | 0.180046E+11 | 0.00 | 0.00 | 12933941.72 | 0.00 | 0.00 | 0.389072E+10 | 0.00 | 0.53 |
December | 0.192551E+11 | 0.00 | 0.00 | 726945.30 | 0.00 | 0.777077E+09 | 0.299877E+09 | 0.00 | 0.54 |
Annual Sum or Average | 0.129998E+12 | 0.467744E+09 | 0.00 | 0.708638E+09 | 0.00 | 0.777077E+09 | 0.119601E+12 | 0.00 | 0.54 |
Minimum of Months | 0.160477E+10 | 0.00 | 0.00 | 726945.30 | 0.00 | 0.00 | 0.299877E+09 | 0.00 | 0.53 |
Maximum of Months | 0.204923E+11 | 0.183429E+09 | 0.00 | 0.129853E+09 | 0.00 | 0.777077E+09 | 0.168240E+11 | 0.00 | 0.54 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.610905E+10 | 0.00 | 0.00 | 21713866.71 | 0.00 | 0.373019E+10 | 0.125161E+11 | 0.00 | 0.53 |
February | 0.570470E+10 | 0.00 | 0.00 | 20637159.96 | 0.00 | 0.204623E+10 | 0.126993E+11 | 0.00 | 0.54 |
March | 0.626495E+10 | 0.00 | 0.00 | 40887872.94 | 0.00 | 0.142380E+09 | 0.159562E+11 | 0.00 | 0.53 |
April | 0.655318E+10 | 0.00 | 0.00 | 82255216.98 | 1394636.78 | 57505517.97 | 0.162004E+11 | 0.00 | 0.54 |
May | 0.674308E+10 | 705419.07 | 0.00 | 0.101094E+09 | 2588012.92 | 47707513.84 | 0.164693E+11 | 0.00 | 0.53 |
June | 0.519064E+10 | 0.118279E+09 | 0.00 | 0.125204E+09 | 65199625.23 | 20158958.26 | 0.144945E+11 | 0.00 | 0.54 |
July | 0.428597E+10 | 91004533.98 | 0.00 | 0.130196E+09 | 40209734.11 | 15410241.48 | 0.133434E+11 | 0.00 | 0.54 |
August | 0.333212E+10 | 26785440.03 | 0.00 | 0.115757E+09 | 62695306.32 | 13786118.33 | 0.132196E+11 | 0.00 | 0.54 |
September | 0.472163E+10 | 35696907.07 | 0.00 | 92513325.51 | 23313593.07 | 36187881.50 | 0.147560E+11 | 0.00 | 0.54 |
October | 0.663968E+10 | 0.00 | 0.00 | 55520896.92 | 0.00 | 82467027.91 | 0.167235E+11 | 0.00 | 0.54 |
November | 0.604847E+10 | 0.00 | 0.00 | 30469908.75 | 0.00 | 0.121337E+10 | 0.146219E+11 | 0.00 | 0.53 |
December | 0.547271E+10 | 0.00 | 0.00 | 14552493.39 | 0.00 | 0.487943E+10 | 0.997164E+10 | 0.00 | 0.54 |
Annual Sum or Average | 0.670662E+11 | 0.272471E+09 | 0.00 | 0.830803E+09 | 0.195401E+09 | 0.122848E+11 | 0.170972E+12 | 0.00 | 0.54 |
Minimum of Months | 0.333212E+10 | 0.00 | 0.00 | 14552493.39 | 0.00 | 13786118.33 | 0.997164E+10 | 0.00 | 0.53 |
Maximum of Months | 0.674308E+10 | 0.118279E+09 | 0.00 | 0.130196E+09 | 65199625.23 | 0.487943E+10 | 0.167235E+11 | 0.00 | 0.54 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_5_FLR_3
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.428312E+09 | 0.00 | 0.00 | 374045.43 | 0.00 | 0.112950E+10 | 91691218.20 | 0.00 | 0.47 |
February | 0.420614E+09 | 0.00 | 0.00 | 687917.72 | 0.00 | 0.960011E+09 | 0.128022E+09 | 0.00 | 0.47 |
March | 0.459721E+09 | 0.00 | 0.00 | 508484.35 | 0.00 | 0.100208E+10 | 0.189592E+09 | 0.00 | 0.47 |
April | 0.209479E+09 | 102828.01 | 0.00 | 10459665.32 | 0.00 | 0.357078E+09 | 0.111094E+10 | 0.00 | 0.47 |
May | 0.226075E+09 | 242828.13 | 0.00 | 10712050.31 | 0.00 | 0.282704E+09 | 0.120295E+10 | 0.00 | 0.47 |
June | 0.169831E+09 | 12959612.22 | 0.00 | 12539615.00 | 568462.07 | 46007197.97 | 0.123375E+10 | 0.00 | 0.47 |
July | 0.109279E+09 | 9346068.78 | 0.00 | 14228743.13 | 328494.24 | 20692522.39 | 0.116636E+10 | 0.00 | 0.47 |
August | 78647596.98 | 6451127.58 | 0.00 | 15892269.52 | 146379.93 | 1814584.97 | 0.113357E+10 | 0.00 | 0.47 |
September | 0.130780E+09 | 4232500.66 | 50.18 | 13468965.32 | 118293.23 | 69384597.13 | 0.123196E+10 | 60.83 | 0.47 |
October | 0.376498E+09 | 0.00 | 0.00 | 3749482.40 | 0.00 | 0.716297E+09 | 0.636224E+09 | 0.00 | 0.47 |
November | 0.434965E+09 | 0.00 | 0.00 | 434419.02 | 0.00 | 0.106590E+10 | 0.114456E+09 | 0.00 | 0.47 |
December | 0.341149E+09 | 0.00 | 0.00 | 110761.04 | 0.00 | 0.112374E+10 | 34568352.18 | 0.00 | 0.47 |
Annual Sum or Average | 0.338535E+10 | 33334965.37 | 50.18 | 83166418.57 | 1161629.47 | 0.677521E+10 | 0.827408E+10 | 60.83 | 0.47 |
Minimum of Months | 78647596.98 | 0.00 | 0.00 | 110761.04 | 0.00 | 1814584.97 | 34568352.18 | 0.00 | 0.47 |
Maximum of Months | 0.459721E+09 | 12959612.22 | 50.18 | 15892269.52 | 568462.07 | 0.112950E+10 | 0.123375E+10 | 60.83 | 0.47 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_6_FLR_3
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.385245E+09 | 0.00 | 0.00 | 84067.18 | 0.00 | 0.122931E+10 | 35041962.34 | 0.00 | 0.47 |
February | 0.420564E+09 | 0.00 | 0.00 | 191252.21 | 0.00 | 0.103484E+10 | 53558947.17 | 0.00 | 0.47 |
March | 0.461323E+09 | 0.00 | 0.00 | 243410.99 | 0.00 | 0.108406E+10 | 0.106079E+09 | 0.00 | 0.47 |
April | 0.351475E+09 | 102815.96 | 0.00 | 7224660.36 | 0.00 | 0.453260E+09 | 0.875796E+09 | 0.00 | 0.47 |
May | 0.342309E+09 | 242799.68 | 0.00 | 8669989.60 | 0.00 | 0.339966E+09 | 0.103129E+10 | 0.00 | 0.47 |
June | 0.226668E+09 | 12864653.67 | 0.00 | 11303313.02 | 661835.61 | 54906829.65 | 0.116907E+10 | 0.00 | 0.47 |
July | 0.127728E+09 | 9235257.07 | 0.00 | 12646039.01 | 438172.43 | 27977979.80 | 0.114206E+10 | 0.00 | 0.47 |
August | 99199714.33 | 6417126.22 | 1115.42 | 12776928.26 | 178477.43 | 7301165.94 | 0.111050E+10 | 15.45 | 0.47 |
September | 0.228278E+09 | 4144157.94 | 19748.01 | 8845205.50 | 185578.27 | 0.157128E+09 | 0.105117E+10 | 910.91 | 0.47 |
October | 0.488682E+09 | 0.00 | 0.00 | 1540554.83 | 0.00 | 0.905828E+09 | 0.336515E+09 | 0.00 | 0.47 |
November | 0.429567E+09 | 0.00 | 0.00 | 122300.41 | 0.00 | 0.114120E+10 | 44677570.49 | 0.00 | 0.47 |
December | 0.305708E+09 | 0.00 | 0.00 | 22990.41 | 0.00 | 0.118952E+10 | 4143811.80 | 0.00 | 0.47 |
Annual Sum or Average | 0.386675E+10 | 33006810.54 | 20863.43 | 63670711.76 | 1464063.73 | 0.762530E+10 | 0.695992E+10 | 926.36 | 0.47 |
Minimum of Months | 99199714.33 | 0.00 | 0.00 | 22990.41 | 0.00 | 7301165.94 | 4143811.80 | 0.00 | 0.47 |
Maximum of Months | 0.488682E+09 | 12864653.67 | 19748.01 | 12776928.26 | 661835.61 | 0.122931E+10 | 0.116907E+10 | 910.91 | 0.47 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.333629E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.197751E+10 | 0.00 | 0.00 | 0.95 |
February | 0.311353E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.562299E+09 | 0.00 | 0.00 | 0.95 |
March | 0.349902E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.286036E+09 | 0.00 | 0.00 | 0.95 |
April | 0.332414E+11 | 0.00 | 0.00 | 0.00 | 4586582.39 | 0.00 | 0.00 | 0.00 | 0.95 |
May | 0.344031E+11 | 0.00 | 0.00 | 0.00 | 4855638.64 | 0.00 | 0.00 | 0.00 | 0.95 |
June | 0.301298E+11 | 0.00 | 0.00 | 0.00 | 0.184024E+09 | 0.00 | 0.00 | 0.00 | 0.95 |
July | 0.274369E+11 | 0.00 | 0.00 | 0.00 | 0.177878E+09 | 0.00 | 0.00 | 0.00 | 0.95 |
August | 0.255062E+11 | 0.00 | 0.00 | 0.00 | 50411684.18 | 0.00 | 0.00 | 0.00 | 0.95 |
September | 0.291182E+11 | 0.00 | 0.00 | 0.00 | 10655667.58 | 0.00 | 0.00 | 0.00 | 0.95 |
October | 0.351138E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.95 |
November | 0.333605E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.632555E+09 | 0.00 | 0.00 | 0.95 |
December | 0.301858E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.477220E+10 | 0.00 | 0.00 | 0.96 |
Annual Sum or Average | 0.377984E+12 | 0.00 | 0.00 | 0.00 | 0.432411E+09 | 0.823060E+10 | 0.00 | 0.00 | 0.95 |
Minimum of Months | 0.255062E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.95 |
Maximum of Months | 0.351138E+11 | 0.00 | 0.00 | 0.00 | 0.184024E+09 | 0.477220E+10 | 0.00 | 0.00 | 0.96 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_6
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 93803126.07 | 0.00 | 0.00 | 79640.05 | 0.00 | 0.310322E+09 | 8264889.62 | 0.00 | 0.47 |
February | 93632999.62 | 0.00 | 0.00 | 269194.81 | 0.00 | 0.256644E+09 | 26787538.59 | 0.00 | 0.47 |
March | 0.112339E+09 | 0.00 | 0.00 | 139693.56 | 0.00 | 0.277272E+09 | 23223581.78 | 0.00 | 0.47 |
April | 69171838.18 | 0.00 | 0.00 | 2615184.55 | 25707.00 | 0.128662E+09 | 0.221540E+09 | 0.00 | 0.47 |
May | 72874344.05 | 60707.03 | 0.00 | 2898264.55 | 0.00 | 0.102166E+09 | 0.252671E+09 | 0.00 | 0.47 |
June | 44443152.91 | 3334144.17 | 0.00 | 3606771.69 | 47874.40 | 18865563.02 | 0.298615E+09 | 0.00 | 0.47 |
July | 35319420.80 | 2303183.77 | 664.05 | 4221859.29 | 114359.15 | 21474878.42 | 0.266625E+09 | 433.78 | 0.47 |
August | 23967654.65 | 1560081.33 | 0.00 | 4111318.98 | 89295.55 | 3664036.68 | 0.275738E+09 | 0.00 | 0.47 |
September | 42437630.71 | 1080740.07 | 0.00 | 2996195.75 | 6986.16 | 50647165.37 | 0.265318E+09 | 0.00 | 0.47 |
October | 98569110.99 | 0.00 | 0.00 | 882880.15 | 0.00 | 0.224609E+09 | 0.109131E+09 | 0.00 | 0.47 |
November | 0.102396E+09 | 0.00 | 0.00 | 92902.84 | 0.00 | 0.289768E+09 | 11682942.81 | 0.00 | 0.47 |
December | 62856289.90 | 0.00 | 0.00 | 1145.49 | 0.00 | 0.311954E+09 | 80598.90 | 0.00 | 0.47 |
Annual Sum or Average | 0.851811E+09 | 8338856.37 | 664.05 | 21915051.70 | 284222.26 | 0.199605E+10 | 0.175968E+10 | 433.78 | 0.47 |
Minimum of Months | 23967654.65 | 0.00 | 0.00 | 1145.49 | 0.00 | 3664036.68 | 80598.90 | 0.00 | 0.47 |
Maximum of Months | 0.112339E+09 | 3334144.17 | 664.05 | 4221859.29 | 114359.15 | 0.311954E+09 | 0.298615E+09 | 433.78 | 0.47 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_6
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 74206790.37 | 0.00 | 0.00 | 12511.77 | 0.00 | 0.336273E+09 | 1928943.90 | 0.00 | 0.47 |
February | 93763384.35 | 0.00 | 0.00 | 64208.96 | 0.00 | 0.273865E+09 | 9596865.07 | 0.00 | 0.47 |
March | 0.111678E+09 | 0.00 | 0.00 | 79508.52 | 0.00 | 0.285173E+09 | 15994969.29 | 0.00 | 0.47 |
April | 97100313.71 | 0.00 | 0.00 | 1858496.99 | 25703.99 | 0.159683E+09 | 0.163297E+09 | 0.00 | 0.47 |
May | 93088884.26 | 60699.92 | 0.00 | 2408911.89 | 0.00 | 0.118031E+09 | 0.217031E+09 | 0.00 | 0.47 |
June | 55790989.16 | 3327596.78 | 0.00 | 3302808.63 | 54025.54 | 23006875.72 | 0.283387E+09 | 0.00 | 0.47 |
July | 44937102.31 | 2256994.08 | 554.62 | 3808717.93 | 160265.59 | 22833893.35 | 0.256023E+09 | 543.08 | 0.47 |
August | 34416473.37 | 1499905.81 | 0.00 | 3313867.12 | 149277.82 | 8452313.74 | 0.261263E+09 | 0.00 | 0.47 |
September | 71401398.48 | 1070189.23 | 0.00 | 1900202.49 | 17409.55 | 84885024.46 | 0.203170E+09 | 0.00 | 0.47 |
October | 0.118734E+09 | 0.00 | 0.00 | 403912.46 | 0.00 | 0.261974E+09 | 52029366.45 | 0.00 | 0.47 |
November | 95840089.30 | 0.00 | 0.00 | 16759.06 | 0.00 | 0.304997E+09 | 3039284.19 | 0.00 | 0.47 |
December | 39647168.56 | 0.00 | 0.00 | 191.28 | 0.00 | 0.335135E+09 | 65212.29 | 0.00 | 0.47 |
Annual Sum or Average | 0.930605E+09 | 8215385.82 | 554.62 | 17170097.10 | 406682.49 | 0.221431E+10 | 0.146683E+10 | 543.08 | 0.47 |
Minimum of Months | 34416473.37 | 0.00 | 0.00 | 191.28 | 0.00 | 8452313.74 | 65212.29 | 0.00 | 0.47 |
Maximum of Months | 0.118734E+09 | 3327596.78 | 554.62 | 3808717.93 | 160265.59 | 0.336273E+09 | 0.283387E+09 | 543.08 | 0.47 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.528911E+09 | 0.00 | 0.00 | 4524936.58 | 0.00 | 0.137635E+10 | 0.740119E+09 | 0.00 | 0.53 |
February | 0.487105E+09 | 0.00 | 0.00 | 5469641.61 | 0.00 | 0.109702E+10 | 0.834582E+09 | 0.00 | 0.54 |
March | 0.688851E+09 | 0.00 | 0.00 | 2526529.01 | 0.00 | 0.122654E+10 | 0.735230E+09 | 0.00 | 0.54 |
April | 0.309826E+09 | 0.00 | 0.00 | 18542468.80 | 165154.36 | 0.346360E+09 | 0.203633E+10 | 0.00 | 0.54 |
May | 0.404790E+09 | 390011.68 | 0.00 | 16008756.78 | 0.00 | 0.319440E+09 | 0.202621E+10 | 0.00 | 0.54 |
June | 0.281765E+09 | 21066493.42 | 0.00 | 18055153.19 | 661248.86 | 38533860.63 | 0.200999E+10 | 0.00 | 0.54 |
July | 0.229370E+09 | 14792811.60 | 3836.97 | 21190147.59 | 738667.13 | 5759858.73 | 0.184861E+10 | 3216.04 | 0.54 |
August | 0.160141E+09 | 10252043.94 | 0.00 | 24976189.96 | 344360.24 | 2648306.73 | 0.178764E+10 | 0.00 | 0.54 |
September | 0.220314E+09 | 6906652.42 | 0.00 | 25044509.45 | 81433.13 | 27947293.60 | 0.204850E+10 | 0.00 | 0.54 |
October | 0.488234E+09 | 0.00 | 0.00 | 11713737.11 | 0.00 | 0.614843E+09 | 0.166825E+10 | 0.00 | 0.54 |
November | 0.553221E+09 | 0.00 | 0.00 | 3817744.09 | 0.00 | 0.117675E+10 | 0.861324E+09 | 0.00 | 0.53 |
December | 0.525883E+09 | 0.00 | 0.00 | 1284212.29 | 0.00 | 0.159044E+10 | 0.290876E+09 | 0.00 | 0.54 |
Annual Sum or Average | 0.487841E+10 | 53408013.06 | 3836.97 | 0.153154E+09 | 1990863.71 | 0.782264E+10 | 0.168877E+11 | 3216.04 | 0.54 |
Minimum of Months | 0.160141E+09 | 0.00 | 0.00 | 1284212.29 | 0.00 | 2648306.73 | 0.290876E+09 | 0.00 | 0.53 |
Maximum of Months | 0.688851E+09 | 21066493.42 | 3836.97 | 25044509.45 | 738667.13 | 0.159044E+10 | 0.204850E+10 | 3216.04 | 0.54 |
Report: MechanicalVentilationLoadsMonthly
For: BANQUET_FLR_6
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.374970E+11 | 0.00 | 0.00 | 5244079.60 | 0.00 | 0.00 | 0.244287E+11 | 0.00 | 7.82 |
February | 0.328190E+11 | 0.00 | 0.00 | 5141284.54 | 0.00 | 0.00 | 0.227232E+11 | 0.00 | 7.87 |
March | 0.345046E+11 | 0.00 | 0.00 | 7407099.08 | 0.00 | 0.00 | 0.273064E+11 | 0.00 | 7.84 |
April | 0.288966E+11 | 0.00 | 0.00 | 9676223.55 | 8037577.94 | 0.00 | 0.293464E+11 | 0.00 | 7.85 |
May | 0.291916E+11 | 0.00 | 0.00 | 11922520.14 | 8509075.10 | 0.00 | 0.310847E+11 | 0.00 | 7.84 |
June | 0.197633E+11 | 0.142667E+09 | 0.00 | 15160436.58 | 0.179818E+09 | 0.00 | 0.330213E+11 | 0.00 | 7.88 |
July | 0.164298E+11 | 0.101505E+09 | 0.00 | 16346143.63 | 0.210210E+09 | 0.00 | 0.316345E+11 | 0.00 | 7.87 |
August | 0.136318E+11 | 8882584.44 | 0.00 | 15862289.20 | 79459411.03 | 0.00 | 0.310496E+11 | 0.00 | 7.88 |
September | 0.217498E+11 | 876431.78 | 0.00 | 11692472.28 | 17796678.48 | 0.00 | 0.292656E+11 | 0.00 | 7.88 |
October | 0.341878E+11 | 0.00 | 0.00 | 8424911.64 | 0.00 | 0.00 | 0.273376E+11 | 0.00 | 7.87 |
November | 0.348677E+11 | 0.00 | 0.00 | 6563888.59 | 0.00 | 0.00 | 0.246955E+11 | 0.00 | 7.81 |
December | 0.367752E+11 | 0.00 | 0.00 | 4946370.16 | 0.00 | 0.00 | 0.244806E+11 | 0.00 | 7.87 |
Annual Sum or Average | 0.340314E+12 | 0.253931E+09 | 0.00 | 0.118388E+09 | 0.503830E+09 | 0.00 | 0.336374E+12 | 0.00 | 7.86 |
Minimum of Months | 0.136318E+11 | 0.00 | 0.00 | 4946370.16 | 0.00 | 0.00 | 0.227232E+11 | 0.00 | 7.81 |
Maximum of Months | 0.374970E+11 | 0.142667E+09 | 0.00 | 16346143.63 | 0.210210E+09 | 0.00 | 0.330213E+11 | 0.00 | 7.88 |
Report: MechanicalVentilationLoadsMonthly
For: DINING_FLR_6
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.371611E+11 | 0.00 | 0.00 | 7395802.37 | 0.00 | 0.00 | 0.277960E+11 | 0.00 | 8.21 |
February | 0.328960E+11 | 0.00 | 0.00 | 7135616.15 | 0.00 | 0.00 | 0.253650E+11 | 0.00 | 8.25 |
March | 0.330129E+11 | 0.00 | 0.00 | 10130040.27 | 0.00 | 0.00 | 0.318235E+11 | 0.00 | 8.22 |
April | 0.261226E+11 | 1268614.08 | 0.00 | 13250594.67 | 7162668.73 | 0.00 | 0.349702E+11 | 0.00 | 8.24 |
May | 0.254766E+11 | 4836618.45 | 0.00 | 16036876.63 | 4089256.89 | 0.00 | 0.377488E+11 | 0.00 | 8.22 |
June | 0.170275E+11 | 0.185420E+09 | 0.00 | 19963325.29 | 0.152861E+09 | 0.00 | 0.383387E+11 | 0.00 | 8.27 |
July | 0.141041E+11 | 0.194075E+09 | 0.00 | 21367080.06 | 0.132909E+09 | 0.00 | 0.363104E+11 | 0.00 | 8.26 |
August | 0.110347E+11 | 13977214.50 | 0.00 | 20667736.88 | 78692039.05 | 0.00 | 0.358313E+11 | 0.00 | 8.26 |
September | 0.189145E+11 | 919362.06 | 0.00 | 15458161.60 | 18668413.60 | 0.00 | 0.345965E+11 | 0.00 | 8.27 |
October | 0.320776E+11 | 0.00 | 0.00 | 11385368.19 | 0.00 | 0.00 | 0.324590E+11 | 0.00 | 8.26 |
November | 0.344973E+11 | 0.00 | 0.00 | 8950336.09 | 0.00 | 0.00 | 0.279815E+11 | 0.00 | 8.20 |
December | 0.368385E+11 | 0.00 | 0.00 | 7050588.11 | 0.00 | 0.00 | 0.274159E+11 | 0.00 | 8.26 |
Annual Sum or Average | 0.319163E+12 | 0.400497E+09 | 0.00 | 0.158792E+09 | 0.394382E+09 | 0.00 | 0.390637E+12 | 0.00 | 8.24 |
Minimum of Months | 0.110347E+11 | 0.00 | 0.00 | 7050588.11 | 0.00 | 0.00 | 0.253650E+11 | 0.00 | 8.20 |
Maximum of Months | 0.371611E+11 | 0.194075E+09 | 0.00 | 21367080.06 | 0.152861E+09 | 0.00 | 0.383387E+11 | 0.00 | 8.27 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN_FLR_6
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 93060648.41 | 0.00 | 0.00 | 0.653249E+11 | 0.00 | 26.66 |
February | 0.00 | 0.00 | 0.00 | 85526289.23 | 0.00 | 0.00 | 0.585938E+11 | 0.00 | 26.81 |
March | 0.00 | 0.00 | 0.00 | 91566451.75 | 0.00 | 0.00 | 0.652212E+11 | 0.00 | 26.71 |
April | 0.00 | 8516949.01 | 0.00 | 0.107921E+09 | 0.00 | 0.00 | 0.614697E+11 | 0.00 | 26.79 |
May | 0.00 | 9010002.49 | 0.00 | 0.112179E+09 | 0.00 | 0.00 | 0.636175E+11 | 0.00 | 26.73 |
June | 0.00 | 0.341761E+09 | 0.00 | 0.109378E+09 | 0.00 | 0.00 | 0.557037E+11 | 0.00 | 26.86 |
July | 0.00 | 0.330359E+09 | 0.00 | 0.115140E+09 | 0.00 | 0.00 | 0.507091E+11 | 0.00 | 26.85 |
August | 0.00 | 93606999.33 | 0.00 | 0.118733E+09 | 0.00 | 0.00 | 0.471259E+11 | 0.00 | 26.87 |
September | 0.00 | 19779330.33 | 0.00 | 0.113657E+09 | 0.00 | 0.00 | 0.538220E+11 | 0.00 | 26.88 |
October | 0.00 | 0.00 | 0.00 | 98666764.05 | 0.00 | 0.00 | 0.649248E+11 | 0.00 | 26.83 |
November | 0.00 | 0.00 | 0.00 | 90575558.30 | 0.00 | 0.00 | 0.628379E+11 | 0.00 | 26.62 |
December | 0.00 | 0.00 | 0.00 | 92391266.24 | 0.00 | 0.00 | 0.646117E+11 | 0.00 | 26.82 |
Annual Sum or Average | 0.00 | 0.803034E+09 | 0.00 | 0.122879E+10 | 0.00 | 0.00 | 0.713962E+12 | 0.00 | 26.79 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 85526289.23 | 0.00 | 0.00 | 0.471259E+11 | 0.00 | 26.62 |
Maximum of Months | 0.00 | 0.341761E+09 | 0.00 | 0.118733E+09 | 0.00 | 0.00 | 0.653249E+11 | 0.00 | 26.88 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.135707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.821175E+10 | 0.00 | 0.00 | 2.21 |
February | 0.147175E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.481968E+10 | 0.00 | 0.00 | 2.22 |
March | 0.187439E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.299897E+10 | 0.00 | 0.00 | 2.21 |
April | 0.202525E+11 | 0.00 | 0.00 | 0.00 | 2826990.90 | 0.236184E+09 | 0.00 | 0.00 | 2.22 |
May | 0.212047E+11 | 0.00 | 0.00 | 0.00 | 2992826.71 | 0.00 | 0.00 | 0.00 | 2.21 |
June | 0.185708E+11 | 0.00 | 0.00 | 0.00 | 0.113425E+09 | 0.00 | 0.00 | 0.00 | 2.22 |
July | 0.169110E+11 | 0.00 | 0.00 | 0.00 | 0.109637E+09 | 0.00 | 0.00 | 0.00 | 2.22 |
August | 0.157210E+11 | 0.00 | 0.00 | 0.00 | 31071800.42 | 0.00 | 0.00 | 0.00 | 2.22 |
September | 0.179473E+11 | 0.00 | 0.00 | 0.00 | 6567738.84 | 0.00 | 0.00 | 0.00 | 2.22 |
October | 0.212769E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.365865E+09 | 0.00 | 0.00 | 2.22 |
November | 0.173370E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.361501E+10 | 0.00 | 0.00 | 2.21 |
December | 0.933035E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122164E+11 | 0.00 | 0.00 | 2.22 |
Annual Sum or Average | 0.205584E+12 | 0.00 | 0.00 | 0.00 | 0.266521E+09 | 0.324639E+11 | 0.00 | 0.00 | 2.22 |
Minimum of Months | 0.933035E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.21 |
Maximum of Months | 0.212769E+11 | 0.00 | 0.00 | 0.00 | 0.113425E+09 | 0.122164E+11 | 0.00 | 0.00 | 2.22 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:58:31
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.801437E+11 | 0.150263E+11 | 0.116977E+12 | 0.144662E+13 | 0.892820E+11 |
February | 0.129607E+12 | 0.134904E+11 | 0.104535E+12 | 0.130767E+13 | 0.812122E+11 |
March | 0.166277E+12 | 0.135705E+11 | 0.106184E+12 | 0.131539E+13 | 0.867639E+11 |
April | 0.419850E+12 | 0.107476E+11 | 0.850502E+11 | 0.104256E+13 | 0.204634E+12 |
May | 0.546322E+12 | 0.102403E+11 | 0.835440E+11 | 0.990307E+12 | 0.215549E+12 |
June | 0.552776E+12 | 0.711185E+10 | 0.630491E+11 | 0.689759E+12 | 0.347706E+12 |
July | 0.553774E+12 | 0.609857E+10 | 0.556507E+11 | 0.577942E+12 | 0.477745E+12 |
August | 0.443516E+12 | 0.574459E+10 | 0.515821E+11 | 0.525734E+12 | 0.521709E+12 |
September | 0.323649E+12 | 0.711435E+10 | 0.617036E+11 | 0.687067E+12 | 0.364561E+12 |
October | 0.147247E+12 | 0.106151E+11 | 0.873177E+11 | 0.103877E+13 | 0.137557E+12 |
November | 0.589574E+11 | 0.124852E+11 | 0.100032E+12 | 0.120835E+13 | 0.857424E+11 |
December | 0.211363E+11 | 0.149881E+11 | 0.117229E+12 | 0.145154E+13 | 0.791816E+11 |
Annual Sum or Average | 0.344326E+13 | 0.127233E+12 | 0.103285E+13 | 0.122817E+14 | 0.269164E+13 |
Minimum of Months | 0.211363E+11 | 0.574459E+10 | 0.515821E+11 | 0.525734E+12 | 0.791816E+11 |
Maximum of Months | 0.553774E+12 | 0.150263E+11 | 0.117229E+12 | 0.145154E+13 | 0.521709E+12 |